AG1-106 Final System Impact Study (Retool 1) Report

v1.00 released 2025-12-08 18:21

Thelma 230 kV

16.0 MW Capacity / 23.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Oak Lessee, LLC, d/b/a Oak Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the TC1 projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.
Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of TC1 projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Northhampton County, North Carolina. This project is an increase to the developer’s AB1-132 project(s), which will share the same Point of Interconnection. The AG1-106 project is a 23.0 MW uprate (16.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 143.0 MW with 100.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG1-106
Project Name:
Thelma 230 kV
Project Developer Name:
Oak Lessee, LLC, d/b/a Oak Solar, LLC
State:
North Carolina
County:
Northhampton
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
143.0
MWE:
23.0
MWC:
16.0
Fuel Type:
Solar
Basecase Study Year:
2027

Physical Interconnection Facility Study

Not Required

A Physical Interconnection Facilities Study is not required for this project.

Point of Interconnection

AG1-106 will interconnect on the Dominion transmission system at Thelma 230 kV substation as an uprate to AB1-132, it will share the same POI and interconnection switchyard with AB1-132/AC1-086

 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AG1-106 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AG1-106Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$15,012,381$15,012,381
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$1,018,000$0
Total$16,030,381$15,012,381

* Contributes to calculation for Security. See Security Section of this report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AB1-132/AG1-106

Security has been calculated for the AB1-132/AG1-106 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AB1-132/AG1-106
Project(s): AB1-132/AG1-106
Final Agreement Security (A): $15,012,381
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $15,012,381
Security on Hand with PJM (D): $8,327,122
Additional Security Due at Agreement Execution (E): C − D = $6,685,259
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

The New Service Request Project will interconnect with the Dominion transmission system at the existing AB1-132/AC1-086 switching station at the Thelma 230 kV Sub.

No TO Interconnection Facilities or Physical Network Upgrades are required for this project.

Should AB1-132/AC1-086 withdraw  the Interconnection Request, AG1-106 will assume the Interconnection Facilities, Stand Alone Network Upgrades, and Network Upgrades costs identified in the AB1-132/AC1-086 study report for connection to the Dominion System.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG1-106 was evaluated as a 23.0 MW (16.0 MW Capacity) injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1CPLE/DVP
3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line
DVP_P7-1: LN 2058-2181_SRT-A
TowerAC119.41 %313.0B373.752.38
GD1DVP
6BUCKING-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC113.03 %571.52B645.990.82
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC110.49 %1204.0C1330.342.94
GD1DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC108.7 %1204.0C1308.782.94
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC142.63 %812.0C1158.141.81
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC133.85 %663.64B888.271.21
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 217_SRT-A
SingleAC109.77 %663.64B728.51.14
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P4-2: 246T247_SRT-A
BreakerAC112.58 %830.0C934.438.68
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P4-2: 24642_SRT-A
BreakerAC107.8 %830.0C894.718.59
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P4-2: 24662_SRT-A
BreakerAC107.79 %830.0C894.668.58
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC100.22 %678.68B680.185.5
GD1DVP
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2092_SRT-A
SingleAC118.32 %571.52B676.242.66
GD1DVP
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2131_SRT-A
SingleAC116.14 %571.52B663.742.66
GD1DVP
6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line
DVP_P4-2: 246T247_SRT-A
BreakerAC119.67 %699.0C836.512.11
GD1DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: H2T557_SRT-S
BreakerAC132.14 %1065.0C1407.282.63
GD1DVP
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC114.05 %559.3B637.860.82
GD1DVP
6HORNRTN-AD1-056 TP 230.0 kV Ckt 1 line
DVP_P4-2: 254T2141_SRT-A
BreakerAC133.57 %541.0C722.6122.95
GD1DVP
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
DVP_P1-2: LN 2092_SRT-A
SingleAC113.42 %571.52B648.232.66
GD1DVP
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
DVP_P1-2: LN 2131_SRT-A
SingleAC111.23 %571.52B635.732.66
GD1DVP
6POE-6TYLER1 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC104.13 %541.0C563.341.67
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P4-2: 246T247_SRT-A
BreakerAC123.57 %830.0C1025.658.68
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC112.21 %678.68B761.575.5
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
SingleAC111.1 %678.68B753.985.97
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC106.16 %3940.0C4182.745.66
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC104.22 %3940.0C4106.125.37
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H1T567_SRT-A
BreakerAC103.44 %3940.0C4075.555.6
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
SingleAC100.39 %1058.16B1062.251.17
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC108.98 %3940.0C4293.984.13
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC104.85 %3940.0C4130.985.85
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S_SENS
BreakerAC102.96 %3940.0C4056.765.61
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S_SENS
SingleAC102.07 %3220.44B3287.013.81
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC102.59 %3144.0C3225.324.24
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC102.48 %3144.0C3221.974.5
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC102.48 %3144.0C3221.974.5
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC102.48 %3144.0C3221.814.5
GD1DVP
AD1-056 TP-6HATHAWAY 230.0 kV Ckt 1 line
DVP_P4-2: 254T2141_SRT-A
BreakerAC150.56 %541.0C814.5422.95
GD1DVP
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
DVP_P4-2: 246T247_SRT-A
BreakerAC123.02 %830.0C1021.048.68
GD1DVP
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 556_SRT-S-3
SingleAC109.42 %678.68B742.635.5
GD1DVP
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
SingleAC108.28 %678.68B734.845.97

Details for 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2058-2181_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.41 %
Rating:313.0 MVA
Rating Type:B
MVA to Mitigate:373.75
MW Contribution:2.38
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2058-2181_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.28 %
Rating:313.0 MVA
Rating Type:B
MVA to Mitigate:354.58
MW Contribution:2.4
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933982AD1-022 E
Adder
1.62117647058823521.378
927146AC1-208 E
50/50
6.0296.029
316049AB1-081 C OP
50/50
3.8543.854
3145393UNCAMP
Adder
1.8752941176470591.594
933981AD1-022 C
Adder
2.97764705882352982.531
900672V4-068 E
Adder
0.168235294117647040.143
3151261ROARAP2
50/50
0.8440.844
3137643SOCKMAN
Adder
0.40.34
316212AC1-099 C
50/50
0.4520.452
919710AA2-057 E
50/50
8.3988.398
316319Z2-044 C
50/50
0.5230.523
934522AD1-076 E
Adder
1.97411764705882351.678
943172AE2-346 E
Adder
0.31294117647058830.266
918492AA1-063AE OP
Adder
2.2223529411764711.889
962571AG1-106 C
50/50
1.6531.653
917332KELFORD E
50/50
1.3871.387
925122AB2-169 E
Adder
2.0305882352941181.726
932631AC2-084 C
50/50
1.4371.437
316274AC1-208 C
50/50
13.57713.577
917342Z2-044 E
50/50
1.4831.483
3151311EDGECMA
50/50
21.06121.061
934512AD1-075 E
Adder
1.35764705882352941.154
934502AD1-074 E
Adder
5.4305882352941184.616
924516AB2-100 E1
Adder
1.24470588235294131.058
918512AA1-065 E OP
Adder
2.24588235294117671.909
966621AG1-532 C
Adder
0.58470588235294120.497
918532AA1-067 E
Adder
0.28117647058823530.239
316141AB2-099 E
Adder
0.130588235294117640.111
316088AB2-174 E
Adder
3.11764705882352942.65
923994AB2-040_E
Adder
3.1117647058823532.645
3151361ROSEMG1
50/50
1.3891.389
961672AG1-007 E
50/50
0.5310.531
960082AF2-299 E
Adder
0.51882352941176470.441
946281AF1-292 C
Adder
0.64470588235294120.548
926071AC1-086 C
50/50
12.78312.783
316317KELFORD C
50/50
0.3020.302
927021AC1-189 C
50/50
6.0266.026
924152AB2-059 E OP
50/50
14.32214.322
946282AF1-292 E
Adder
0.42941176470588230.365
957861AF2-080 C
50/50
5.4735.473
917512Z2-088 E OP1
50/50
4.2784.278
316210AC1-098 C
50/50
1.351.35
926206AC1-098 E
50/50
5.2255.225
316327AA2-057 C
50/50
2.7552.755
961942AG1-037 E
Adder
0.174117647058823520.148
961941AG1-037 C
Adder
0.260.221
3151391GASTONA
50/50
1.8581.858
3151381ROSEMG2
50/50
0.650.65
934332AD1-057 E
50/50
1.9141.914
934331AD1-057 C
50/50
3.6763.676
934321AD1-056 C
50/50
6.596.59
934322AD1-056 E
50/50
3.5743.574
927022AC1-189 E
50/50
3.0023.002
925595AC1-034 E
50/50
13.58513.585
3145413WATKINS
Adder
0.240.204
960081AF2-299 C
Adder
0.77882352941176480.662
926072AC1-086 E
50/50
5.8185.818
957862AF2-080 E
50/50
2.4262.426
923263AB1-132 E OP
50/50
3.723.72
3151411GASTONB
50/50
1.8581.858
3156063AA2-053SOLA
50/50
0.8980.898
3151281ROARAP4
50/50
0.7990.799
3156011CONETOE2SOL
50/50
1.0931.093
966622AG1-532 E
Adder
0.38941176470588240.331
922923AB1-081 E OP
50/50
10.1110.11
962572AG1-106 E
50/50
0.7230.723
926214AC1-099 E
50/50
1.7261.726
932632AC2-084 E
50/50
4.6194.619
934501AD1-074 C
Adder
10.6670588235294139.067
924517AB2-100 E2
Adder
1.24470588235294131.058
3151371ROSEMS1
50/50
0.860.86
961671AG1-007 C
50/50
0.9370.937
316359AB2-059 C OP
50/50
4.5434.543
920042AA2-088 E OP
Adder
4.582352941176473.895
934521AD1-076 C
Adder
3.8741176470588243.293
934511AD1-075 C
Adder
2.66705882352941172.267
3145723EMPORIA
Adder
0.189411764705882360.161
316011AB1-132 C OP
50/50
1.4191.419
923573AB1-173 E OP
Adder
1.65882352941176461.41
919692AA2-053 E OP
50/50
2.5162.516
925785AC1-054 E
Adder
1.18705882352941171.009
316263AC1-034 C
50/50
18.00818.008
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.1150.115
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.3950.395
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.2431.243
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
2.4822.482
G-007ALTFEXP_G-007A->PJM
CMTX
0.3460.346
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.8040.804
VTFLTFEXP_VFT->PJM
CMTX
0.9190.919
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.7690.769
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.2722.272
MDUPJM->LTFIMP_MDU
CLTF
0.0820.082
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
2.5362.536
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.5711.571

Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.03 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:645.99
MW Contribution:0.82
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.98 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:685.72
MW Contribution:0.8
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316336AC2-165 C
Adder
-5.884705882352941-5.002
934611AD1-087 C
80/20
2.212.21
316049AB1-081 C OP
80/20
0.4770.477
3151611KERR 4
80/20
1.5611.561
3137643SOCKMAN
80/20
0.3520.352
316212AC1-099 C
80/20
0.1130.113
316319Z2-044 C
80/20
0.0740.074
937481AD2-202 C
80/20
0.6410.641
3151641KERR 7
80/20
1.5611.561
316123AC1-075 C
80/20
0.9530.953
316205AC1-080 C
80/20
0.3190.319
3151261ROARAP2
80/20
0.6810.681
3147043LAWRENC
80/20
0.2660.266
3151621KERR 5
80/20
1.5611.561
316222AC1-221 C
80/20
1.5791.579
3151411GASTONB
80/20
0.9230.923
316181AB2-040 GEN
80/20
0.6330.633
3156063AA2-053SOLA
80/20
0.6790.679
3151281ROARAP4
80/20
0.6440.644
316238AB2-078 C O1
80/20
0.5670.567
316237AB2-079 C O1
80/20
0.5670.567
938821AE1-108 C
Adder
-10.596470588235293-9.007
962571AG1-106 C
80/20
0.8210.821
932631AC2-084 C
80/20
0.3610.361
316274AC1-208 C
80/20
3.5413.541
3151311EDGECMA
80/20
5.0375.037
3151601KERR 3
80/20
1.5611.561
3151581KERR 1
80/20
0.5570.557
3152661PLYWOOD A
80/20
1.751.75
941011AE2-092 C
Adder
-9.714117647058824-8.257
966621AG1-532 C
80/20
0.7060.706
316003AC1-222 C
80/20
1.3481.348
936161AD2-022 C
80/20
3.6193.619
313506AB1-173 C OP
80/20
0.5620.562
3151361ROSEMG1
80/20
0.6210.621
957481AF2-042 C
80/20
97.99997.999
946281AF1-292 C
80/20
0.7790.779
926071AC1-086 C
80/20
6.3516.351
3151531CLOVER1
80/20
22.47222.472
964241AG1-285 C
80/20
25.13225.132
316034AC1-036 C
80/20
0.5340.534
962561AG1-105 C
80/20
14.16114.161
942671AE2-283 C
80/20
1.5211.521
316129AC1-054 C
80/20
1.1891.189
316131AB2-060 C
80/20
2.662.66
3138533PONTONDP
80/20
1.7311.731
316118AC1-105 C
80/20
1.3691.369
316217AC1-145 C
80/20
0.1690.169
3151391GASTONA
80/20
0.9230.923
3151381ROSEMG2
80/20
0.2910.291
934331AD1-057 C
80/20
1.1031.103
934321AD1-056 C
80/20
1.9781.978
958211AF2-115 C
80/20
5.8435.843
316210AC1-098 C
80/20
0.3390.339
316327AA2-057 C
80/20
0.4730.473
316239AB2-077 C O1
80/20
0.5670.567
935171AD1-152 C
80/20
2.1552.155
964791AG1-342 C
80/20
5.5355.535
960081AF2-299 C
80/20
0.9410.941
3151541CLOVER2
80/20
22.26222.262
3151631KERR 6
80/20
1.5611.561
936261AD2-033 C
80/20
27.64927.649
961791AG1-021 C
80/20
4.6754.675
3144293JTRSVLE
80/20
1.0761.076
316248AF1-058 C
80/20
0.450.45
936171AD2-023 C
80/20
2.1112.111
941801AE2-185 C
80/20
1.9561.956
316322AB2-045 C
80/20
1.2941.294
316087AB2-174 C
80/20
0.5880.588
313527AB2-043 C
80/20
0.9080.908
3151591KERR 2
80/20
1.5611.561
316283AC2-100 C
80/20
1.2351.235
3156073AA1-063SOLA
80/20
0.5840.584
3151371ROSEMS1
80/20
0.3840.384
934621AD1-088 C
80/20
18.88618.886
316359AB2-059 C OP
80/20
0.5620.562
946301AF1-294 C
80/20
9.6099.609
942461AE2-259 C
80/20
31.13331.133
316197AC1-042 C
80/20
0.1420.142
316011AB1-132 C OP
80/20
0.7050.705
316263AC1-034 C
80/20
2.2292.229
959311AF2-222 C
80/20
38.88338.883
942751AE2-291 C
80/20
8.1298.129
3151561HALLBR1
80/20
0.5580.558
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.0479.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.0847.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1891.189
LAGNLTFEXP_LAGN->PJM
CLTF
2.5082.508
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1162.116
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.17235.172
CPLELTFEXP_CPLE->PJM
CLTF
4.444.44
TVALTFEXP_TVA->PJM
CLTF
1.9591.959
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072
NYPJM->LTFIMP_NY
CLTF
0.3750.375
LGEELTFEXP_LGEE->PJM
CLTF
0.3550.355
WECLTFEXP_WEC->PJM
CLTF
0.1880.188

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.49 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1330.34
MW Contribution:2.94
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.67 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1404.76
MW Contribution:2.88
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961942AG1-037 E
Adder
0.167058823529411760.142
961941AG1-037 C
Adder
0.251764705882352950.214
3151391GASTONA
50/50
2.2972.297
3151381ROSEMG2
50/50
0.7050.705
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934332AD1-057 E
Adder
1.21529411764705891.033
934331AD1-057 C
Adder
2.33411764705882341.984
934321AD1-056 C
Adder
4.1835294117647063.556
934322AD1-056 E
Adder
2.26941176470588251.929
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
3151051BRUNSWICKS1
50/50
12.19612.196
963042AG1-153 E
50/50
5.9665.966
927021AC1-189 C
Adder
4.5788235294117653.892
940541AE2-040 C
50/50
3.3223.322
940481AE2-033 C
50/50
18.24118.241
940482AE2-033 E
50/50
12.29712.297
923263AB1-132 E OP
50/50
4.64.6
3151411GASTONB
50/50
2.2972.297
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
3152441Z1-086 ST
50/50
13.14613.146
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
926274AC1-105 E
Adder
1.50823529411764711.282
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934521AD1-076 C
Adder
4.7823529411764714.065
934511AD1-075 C
Adder
3.2917647058823532.798
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
936172AD2-023 E
Adder
1.21058823529411751.029
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
963041AG1-153 C
50/50
3.9773.977
957862AF2-080 E
Adder
1.84352941176470591.567
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
918492AA1-063AE OP
Adder
2.40470588235294122.044
962571AG1-106 C
50/50
2.0442.044
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
316087AB2-174 C
50/50
0.9180.918
962572AG1-106 E
50/50
0.8940.894
926214AC1-099 E
Adder
0.70941176470588230.603
932632AC2-084 E
Adder
1.89764705882352951.613
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
964792AG1-342 E
Adder
1.34588235294117631.144
932763AC2-100 E
Adder
1.3917647058823531.183
919692AA2-053 E OP
Adder
2.6788235294117652.277
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
927146AC1-208 E
Adder
2.45294117647058842.085
934622AD1-088 E
Adder
2.72588235294117662.317
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
316315AB2-025 C
50/50
0.4720.472
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
957861AF2-080 C
Adder
4.1588235294117653.535
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151041BRUNSWICKG3
50/50
5.8715.871
3151021BRUNSWICKG1
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.7 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1308.78
MW Contribution:2.94
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.88 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1383.11
MW Contribution:2.88
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961942AG1-037 E
Adder
0.167058823529411760.142
961941AG1-037 C
Adder
0.251764705882352950.214
3151391GASTONA
50/50
2.2972.297
3151381ROSEMG2
50/50
0.7050.705
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934332AD1-057 E
Adder
1.21529411764705891.033
934331AD1-057 C
Adder
2.33411764705882341.984
934321AD1-056 C
Adder
4.1835294117647063.556
934322AD1-056 E
Adder
2.26941176470588251.929
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
940541AE2-040 C
50/50
3.3223.322
940481AE2-033 C
50/50
18.24118.241
940482AE2-033 E
50/50
12.29712.297
923263AB1-132 E OP
50/50
4.64.6
3151411GASTONB
50/50
2.2972.297
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
3152441Z1-086 ST
50/50
13.14613.146
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
926274AC1-105 E
Adder
1.50823529411764711.282
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
3151051BRUNSWICKS1
50/50
12.19612.196
963042AG1-153 E
50/50
5.9665.966
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
936172AD2-023 E
Adder
1.21058823529411751.029
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
963041AG1-153 C
50/50
3.9773.977
957862AF2-080 E
Adder
1.84352941176470591.567
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
918492AA1-063AE OP
Adder
2.40470588235294122.044
962571AG1-106 C
50/50
2.0442.044
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
316087AB2-174 C
50/50
0.9180.918
962572AG1-106 E
50/50
0.8940.894
926214AC1-099 E
Adder
0.70941176470588230.603
932632AC2-084 E
Adder
1.89764705882352951.613
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
964792AG1-342 E
Adder
1.34588235294117631.144
932763AC2-100 E
Adder
1.3917647058823531.183
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934521AD1-076 C
Adder
4.7823529411764714.065
934511AD1-075 C
Adder
3.2917647058823532.798
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
927146AC1-208 E
Adder
2.45294117647058842.085
934622AD1-088 E
Adder
2.72588235294117662.317
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
316315AB2-025 C
50/50
0.4720.472
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
957861AF2-080 C
Adder
4.1588235294117653.535
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151041BRUNSWICKG3
50/50
5.8715.871
3151021BRUNSWICKG1
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.63 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1158.14
MW Contribution:1.81
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.2 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1065.31
MW Contribution:1.79
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150781HOPHCF2
50/50
1.6821.682
942001AE2-212 C
50/50
2.3882.388
939192AE1-149 E
50/50
5.125.12
939312AE1-162 E
Adder
0.54941176470588240.467
934065AD1-033 E
Adder
1.53411764705882361.304
937226AE2-253 E
Adder
1.80588235294117651.535
934501AD1-074 C
Adder
12.22470588235294110.391
924517AB2-100 E2
Adder
1.5282352941176471.299
957482AF2-042 E
Adder
12.9811.033
961671AG1-007 C
Adder
0.36235294117647060.308
934621AD1-088 C
Adder
3.18117647058823572.704
935172AD1-152 E
Adder
1.86235294117647051.583
3150791HOPHCF3
50/50
1.6821.682
926662AC1-147 E
Adder
0.420.357
916192Z1-068 E
Adder
0.58588235294117650.498
957492AF2-043 E
Adder
0.4717647058823530.401
923852AB2-025 E
50/50
0.7170.717
939412AE1-173 E
Adder
23.37764705882352719.871
961942AG1-037 E
Adder
0.132941176470588230.113
961941AG1-037 C
Adder
0.198823529411764730.169
941032AE2-094 E
Adder
7.6070588235294126.466
941031AE2-094 C
Adder
16.9847058823529414.437
934332AD1-057 E
Adder
0.76705882352941180.652
934331AD1-057 C
Adder
1.47294117647058821.252
934321AD1-056 C
Adder
2.642.244
934322AD1-056 E
Adder
1.4317647058823531.217
927022AC1-189 E
Adder
1.59882352941176481.359
925595AC1-034 E
Adder
1.95294117647058821.66
942341AE2-247 C
Adder
0.69882352941176470.594
943462AF1-017 E
Adder
1.03058823529411760.876
958162AF2-110 E
Adder
0.81058823529411760.689
919153AA1-139 E2
Adder
1.27058823529411781.08
934512AD1-075 E
Adder
1.5552941176470591.322
934502AD1-074 E
Adder
6.222352941176475.289
924516AB2-100 E1
Adder
1.5282352941176471.299
918512AA1-065 E OP
Adder
2.12470588235294141.806
966621AG1-532 C
Adder
0.67999999999999990.578
918532AA1-067 E
Adder
0.269411764705882350.229
924022AB2-043 E O1
Adder
1.73764705882352951.477
3150801HOPHCF4
50/50
2.5532.553
316349AD2-085 C
Adder
1.61058823529411771.369
935112AD1-144 E
Adder
0.315294117647058840.268
944582AF1-123 E
Adder
31.66823529411764726.918
944592AF1-124 E
Adder
31.78352941176470427.016
923832AB2-022 E
Adder
0.397647058823529460.338
938772AE1-103 E
Adder
1.55882352941176471.325
916042Z1-036 E
Adder
9.7517647058823538.289
960082AF2-299 E
Adder
0.60352941176470590.513
946281AF1-292 C
Adder
0.74941176470588230.637
926071AC1-086 C
Adder
9.7470588235294138.285
963042AG1-153 E
Adder
3.4917647058823532.968
927021AC1-189 C
Adder
3.2094117647058832.728
939191AE1-149 C
50/50
7.6817.681
3143316POE
50/50
1.2311.231
901082W1-029 E
Adder
10.5541176470588248.971
926206AC1-098 E
Adder
1.4682352941176471.248
964791AG1-342 C
Adder
1.1482352941176470.976
3150651CHESTF6
50/50
25.13725.137
946262AF1-291 E
50/50
1.8721.872
934576AD1-082 E
50/50
2.7072.707
944602AF1-125 E
Adder
31.17176470588235326.496
3145506HICKORY
Adder
0.6682352941176470.568
943612AF1-032 E
Adder
0.30705882352941180.261
957871AF2-081 C
Adder
3.10588235294117652.64
940492AE2-034 E
Adder
1.08941176470588250.926
934522AD1-076 E
Adder
2.2623529411764711.923
943172AE2-346 E
Adder
0.238823529411764740.203
964241AG1-285 C
Adder
4.1952941176470593.566
924152AB2-059 E OP
Adder
2.0588235294117651.75
962561AG1-105 C
Adder
2.89529411764705862.461
925332AB2-190 E
50/50
4.8614.861
927226AC1-216 E
Adder
4.2082352941176473.577
936666AD2-085 E
Adder
2.62823529411764722.234
941591AE2-156 C
Adder
5.6635294117647064.814
944591AF1-124 C
Adder
13.87882352941176711.797
944601AF1-125 C
Adder
13.61647058823529511.574
938771AE1-103 C
Adder
1.1282352941176470.959
3145413WATKINS
Adder
0.271764705882352960.231
960081AF2-299 C
Adder
0.90588235294117650.77
926072AC1-086 E
Adder
4.4364705882352943.771
944011AF1-069 C
Adder
5.5494117647058824.717
963041AG1-153 C
Adder
2.32823529411764741.979
957862AF2-080 E
Adder
1.29176470588235311.098
962562AG1-105 E
Adder
1.93058823529411771.641
940432AE2-027 E
Adder
3.68588235294117663.133
934012AD1-025 E
Adder
5.4482352941176474.631
913392Y1-086 E
Adder
0.70470588235294120.599
939411AE1-173 C
Adder
35.0670588235294129.807
3137643SOCKMAN
Adder
0.315294117647058840.268
919710AA2-057 E
Adder
1.58117647058823541.344
918492AA1-063AE OP
Adder
1.7070588235294121.451
962571AG1-106 C
Adder
1.26117647058823531.072
917332KELFORD E
Adder
0.65058823529411770.553
925122AB2-169 E
Adder
2.1235294117647061.805
316274AC1-208 C
Adder
3.6705882352941183.12
917342Z2-044 E
Adder
0.235294117647058850.2
937482AD2-202 E
Adder
0.36941176470588240.314
3151311EDGECMA
Adder
6.0682352941176485.158
3150771HOPHCF1
50/50
1.6821.682
940431AE2-027 C
Adder
5.5282352941176474.699
942002AE2-212 E
50/50
1.5921.592
316132AB2-190 C
50/50
2.4992.499
944581AF1-123 C
Adder
13.82941176470588311.755
941101AE2-104 C
Adder
1.2482352941176471.061
316141AB2-099 E
Adder
0.098823529411764710.084
316088AB2-174 E
Adder
3.04352941176470632.587
923994AB2-040_E
Adder
2.8235294117647062.4
957481AF2-042 C
Adder
19.4705882352941216.55
961672AG1-007 E
Adder
0.204705882352941150.174
924322AB2-079 E O1
Adder
0.448235294117647070.381
961611AG1-000B C
Adder
7.286.188
940541AE2-040 C
50/50
1.7731.773
940481AE2-033 C
50/50
9.8069.806
940482AE2-033 E
50/50
6.6116.611
923263AB1-132 E OP
Adder
2.8364705882352942.411
924312AB2-078 E O1
Adder
0.448235294117647070.381
926274AC1-105 E
Adder
0.860.731
944641AF1-129 C
50/50
138.059138.059
316240AF1-291 C
50/50
2.8082.808
924814AB2-134 E
Adder
6.8941176470588245.86
316381AD1-082 C
50/50
0.7750.775
942342AE2-247 E
Adder
0.96470588235294120.82
919152AA1-139 E1
Adder
1.27058823529411781.08
920042AA2-088 E OP
Adder
4.2552941176470593.617
934521AD1-076 C
Adder
4.443.774
934511AD1-075 C
Adder
3.0564705882352942.598
3145723EMPORIA
Adder
0.205882352941176460.175
923573AB1-173 E OP
Adder
1.50588235294117641.28
919692AA2-053 E OP
Adder
1.7835294117647061.516
925785AC1-054 E
Adder
1.32352941176470581.125
316263AC1-034 C
Adder
2.5882352941176472.2
3150761HOPPOLC
50/50
1.0581.058
3145256KINGFORK
Adder
0.33882352941176470.288
925522AC1-027 E
Adder
0.380.323
941102AE2-104 E
Adder
1.98470588235294131.687
957872AF2-081 E
Adder
1.33058823529411761.131
962572AG1-106 E
Adder
0.55176470588235290.469
926214AC1-099 E
Adder
0.484705882352941150.412
932632AC2-084 E
Adder
1.2988235294117651.104
964242AG1-285 E
Adder
2.7964705882352942.377
924162AB2-060 E OP
Adder
1.41882352941176461.206
964792AG1-342 E
Adder
0.76588235294117660.651
316315AB2-025 C
50/50
0.2520.252
946282AF1-292 E
Adder
0.50.425
944012AF1-069 E
Adder
2.1552941176470591.832
957861AF2-080 C
Adder
2.9152941176470592.478
917512Z2-088 E OP1
Adder
1.88000000000000011.598
3150731STONECA
50/50
4.7614.761
935161AD1-151 C
50/50
9.2889.288
932046AC2-012 E
Adder
4.1552941176470593.532
958161AF2-110 C
Adder
0.50941176470588230.433
938531AE1-072 C
Adder
5.49411764705882364.67
3145393UNCAMP
Adder
2.362.006
933981AD1-022 C
Adder
3.22705882352941182.743
900672V4-068 E
Adder
0.14235294117647060.121
924302AB2-077 E O1
Adder
0.448235294117647070.381
935162AD1-151 E
50/50
6.1926.192
943461AF1-017 C
Adder
0.6317647058823530.537
932596AC2-079 E
Adder
4.2658823529411763.626
316311AC2-079 C
Adder
2.61529411764705882.223
938532AE1-072 E
Adder
2.8635294117647062.434
3146326AYDLETT TAP
Adder
0.424705882352941160.361
917122Z2-027 E
Adder
0.435294117647058830.37
920692AA2-178 E
Adder
1.45294117647058841.235
966622AG1-532 E
Adder
0.452941176470588240.385
922923AB1-081 E OP
Adder
1.45294117647058841.235
316084AB2-161 E
50/50
3.3973.397
316083AB2-161 C
50/50
0.340.34
3145946PLYMOUTH TP
Adder
0.116470588235294130.099
933982AD1-022 E
Adder
1.75647058823529421.493
927146AC1-208 E
Adder
1.62941176470588231.385
934622AD1-088 E
Adder
1.53176470588235311.302
934612AD1-087 E
Adder
1.26235294117647071.073
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.0758.075
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.5166.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.081.08
LAGNLTFEXP_LAGN->PJM
CLTF
2.3232.323
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.8981.898
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.93631.936
CPLELTFEXP_CPLE->PJM
CLTF
3.9843.984
TVALTFEXP_TVA->PJM
CLTF
1.811.81
O66PJM->LTFIMP_O-066
CMTX_NF
6.2766.276
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9850.985
SIGELTFEXP_SIGE->PJM
CLTF
0.0650.065
NYPJM->LTFIMP_NY
CLTF
0.4640.464
LGEELTFEXP_LGEE->PJM
CLTF
0.3190.319
WECLTFEXP_WEC->PJM
CLTF
0.1690.169

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.85 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:888.27
MW Contribution:1.21
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.9 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:921.81
MW Contribution:1.19
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150801HOPHCF4
80/20
2.5782.578
316349AD2-085 C
80/20
1.6511.651
3150731STONECA
80/20
4.8074.807
935161AD1-151 C
80/20
9.5159.515
3151221GRAVEL6
80/20
1.141.14
3151201GRAVEL4
80/20
1.1421.142
958161AF2-110 C
80/20
0.5350.535
938531AE1-072 C
Adder
6.04588235294117655.139
933981AD1-022 C
Adder
3.26941176470588252.779
3151261ROARAP2
80/20
0.5670.567
3147043LAWRENC
80/20
0.1270.127
3152411Z1-086 GT1
80/20
3.8333.833
3151211GRAVEL5
80/20
1.1271.127
943461AF1-017 C
80/20
0.6470.647
316311AC2-079 C
80/20
2.6862.686
944641AF1-129 C
80/20
137.537137.537
316240AF1-291 C
80/20
2.7922.792
3151191GRAVEL3
80/20
1.1271.127
316381AD1-082 C
80/20
0.7760.776
934521AD1-076 C
Adder
4.5247058823529423.846
934511AD1-075 C
Adder
3.1141176470588232.647
316011AB1-132 C OP
80/20
1.0341.034
316263AC1-034 C
Adder
2.44235294117647062.076
316083AB2-161 C
80/20
0.340.34
940641AE2-051 C
80/20
6.3516.351
316336AC2-165 C
Adder
-2.925882352941177-2.487
939411AE1-173 C
80/20
32.73632.736
3137643SOCKMAN
80/20
0.30.3
3151031BRUNSWICKG2
80/20
2.9812.981
3150761HOPPOLC
80/20
1.0681.068
933291AC2-141 C
Adder
9.0470588235294127.69
316087AB2-174 C
80/20
0.5210.521
961611AG1-000B C
80/20
7.6267.626
316236AE1-162 C
80/20
0.1440.144
940541AE2-040 C
80/20
1.6761.676
940481AE2-033 C
80/20
9.2759.275
3151411GASTONB
80/20
1.3541.354
316181AB2-040 GEN
80/20
0.5530.553
3156063AA2-053SOLA
80/20
0.6110.611
3151281ROARAP4
80/20
0.5360.536
3152441Z1-086 ST
80/20
6.6736.673
3152431Z1-086 GT3
80/20
3.8323.832
3152421Z1-086 GT2
80/20
3.8323.832
3150651CHESTF6
80/20
25.04225.042
957871AF2-081 C
Adder
3.42823529411764752.914
3151151S HAMPT1
80/20
0.5930.593
962571AG1-106 C
80/20
1.2051.205
316274AC1-208 C
Adder
3.50823529411764762.982
3151311EDGECMA
Adder
5.7282352941176474.869
3151171GRAVELC
80/20
0.3880.388
942341AE2-247 C
80/20
0.7150.715
966621AG1-532 C
80/20
0.6420.642
3150771HOPHCF1
80/20
1.6981.698
940431AE2-027 C
80/20
5.4285.428
316132AB2-190 C
80/20
2.552.55
944581AF1-123 C
Adder
15.41882352941176613.106
941101AE2-104 C
80/20
1.3111.311
3156083AA2-088SOLA
80/20
0.4240.424
313506AB1-173 C OP
80/20
0.4910.491
3151361ROSEMG1
80/20
0.8890.889
957481AF2-042 C
Adder
16.9176470588235314.38
316023AB2-100 C2
80/20
0.4810.481
946281AF1-292 C
80/20
0.7080.708
926071AC1-086 C
80/20
9.3179.317
3151051BRUNSWICKS1
80/20
6.1926.192
927021AC1-189 C
Adder
3.0858823529411772.623
316315AB2-025 C
80/20
0.2380.238
957861AF2-080 C
Adder
2.8035294117647062.383
3150791HOPHCF3
80/20
1.6981.698
316369AC1-216 C
80/20
0.90.9
961941AG1-037 C
Adder
0.196470588235294150.167
3151391GASTONA
80/20
1.3541.354
3151381ROSEMG2
80/20
0.4160.416
941031AE2-094 C
80/20
14.70614.706
934331AD1-057 C
Adder
1.39882352941176481.189
934321AD1-056 C
Adder
2.50705882352941162.131
316033AB2-134 GEN
80/20
1.1791.179
934011AD1-025 C
80/20
1.4591.459
939191AE1-149 C
80/20
7.67.6
316365AB2-100 C1
80/20
0.4810.481
3151041BRUNSWICKG3
80/20
2.9812.981
3151021BRUNSWICKG1
80/20
2.9812.981
941591AE2-156 C
Adder
6.2764705882352945.335
944591AF1-124 C
Adder
15.47294117647058813.152
944601AF1-125 C
Adder
15.18117647058823612.904
938771AE1-103 C
80/20
1.1561.156
960081AF2-299 C
80/20
0.8560.856
944011AF1-069 C
80/20
4.8054.805
963041AG1-153 C
Adder
2.0188235294117651.716
3150781HOPHCF2
80/20
1.6981.698
942001AE2-212 C
80/20
2.3582.358
3151161SURRY 1
80/20
11.09811.098
934501AD1-074 C
Adder
12.4576470588235310.589
3156073AA1-063SOLA
80/20
0.570.57
3151371ROSEMS1
80/20
0.5510.551
961671AG1-007 C
Adder
0.34588235294117650.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.8996.899
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.7315.731
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9380.938
LAGNLTFEXP_LAGN->PJM
CLTF
2.0572.057
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7131.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.64628.646
CPLELTFEXP_CPLE->PJM
CLTF
3.5953.595
TVALTFEXP_TVA->PJM
CLTF
1.6011.601
SIGELTFEXP_SIGE->PJM
CLTF
0.0560.056
NYPJM->LTFIMP_NY
CLTF
0.4310.431
LGEELTFEXP_LGEE->PJM
CLTF
0.2740.274
WECLTFEXP_WEC->PJM
CLTF
0.1450.145

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.77 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:728.5
MW Contribution:1.14
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.54 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:707.05
MW Contribution:1.11
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316083AB2-161 C
80/20
0.3740.374
316072AD1-144 C
80/20
0.0920.092
3150731STONECA
80/20
5.8035.803
935161AD1-151 C
80/20
10.99910.999
3151221GRAVEL6
80/20
1.2011.201
3151201GRAVEL4
80/20
1.2021.202
958161AF2-110 C
80/20
0.4930.493
938531AE1-072 C
Adder
5.1458823529411764.374
315614AA2-178 C
80/20
0.5030.503
933981AD1-022 C
80/20
2.92.9
3151261ROARAP2
80/20
0.5210.521
3147043LAWRENC
80/20
0.1170.117
316140AB2-099 C
80/20
0.0340.034
3137643SOCKMAN
80/20
0.2790.279
316212AC1-099 C
80/20
0.110.11
961611AG1-000B C
80/20
8.238.23
316236AE1-162 C
80/20
0.1430.143
316375AC2-012 C
80/20
0.4130.413
940541AE2-040 C
80/20
1.7111.711
940481AE2-033 C
80/20
9.4279.427
3151411GASTONB
80/20
1.2821.282
316181AB2-040 GEN
80/20
0.520.52
3156063AA2-053SOLA
80/20
0.560.56
3151281ROARAP4
80/20
0.4930.493
3150651CHESTF6
80/20
31.16731.167
957871AF2-081 C
Adder
2.91294117647058842.476
3151151S HAMPT1
80/20
0.5450.545
962571AG1-106 C
80/20
1.1411.141
932631AC2-084 C
80/20
0.3490.349
316274AC1-208 C
80/20
3.1613.161
3151171GRAVELC
80/20
0.4080.408
942341AE2-247 C
80/20
0.7240.724
316246AF1-032 C
80/20
0.0890.089
966621AG1-532 C
80/20
0.6130.613
3150771HOPHCF1
80/20
2.052.05
940431AE2-027 C
80/20
6.666.66
316132AB2-190 C
80/20
2.9822.982
944581AF1-123 C
Adder
13.0152941176470611.063
941101AE2-104 C
80/20
1.2091.209
3156083AA2-088SOLA
80/20
0.3880.388
313506AB1-173 C OP
80/20
0.4620.462
3151361ROSEMG1
80/20
0.8370.837
3150801HOPHCF4
80/20
3.1113.111
316349AD2-085 C
80/20
1.6711.671
316023AB2-100 C2
80/20
0.4730.473
946281AF1-292 C
80/20
0.6770.677
926071AC1-086 C
80/20
8.8218.821
316317KELFORD C
80/20
0.1250.125
316315AB2-025 C
80/20
0.2430.243
3150791HOPHCF3
80/20
2.052.05
316369AC1-216 C
80/20
1.0251.025
943171AE2-346 C
80/20
0.0790.079
961941AG1-037 C
80/20
0.1780.178
3151391GASTONA
80/20
1.2821.282
3151381ROSEMG2
80/20
0.3920.392
934331AD1-057 C
80/20
1.2741.274
934321AD1-056 C
80/20
2.2852.285
316033AB2-134 GEN
80/20
1.3431.343
934011AD1-025 C
80/20
1.6611.661
939191AE1-149 C
80/20
8.6748.674
316365AB2-100 C1
80/20
0.4730.473
316318V4-068 C
80/20
0.0290.029
316210AC1-098 C
80/20
0.3280.328
941591AE2-156 C
Adder
5.457647058823534.639
944591AF1-124 C
Adder
13.0623529411764711.103
944601AF1-125 C
Adder
12.8152941176470610.893
938771AE1-103 C
80/20
1.0631.063
960081AF2-299 C
80/20
0.8180.818
3151211GRAVEL5
80/20
1.1871.187
943461AF1-017 C
80/20
0.6550.655
316311AC2-079 C
80/20
2.6932.693
3150761HOPPOLC
80/20
1.2891.289
316305AF2-043 C
80/20
0.1080.108
316087AB2-174 C
80/20
0.4920.492
3150781HOPHCF2
80/20
2.052.05
942001AE2-212 C
80/20
2.8572.857
3151161SURRY 1
80/20
11.68311.683
940491AE2-034 C
80/20
0.370.37
934501AD1-074 C
80/20
11.00411.004
3156021HOLLOMANSOL
80/20
0.6320.632
3156073AA1-063SOLA
80/20
0.5230.523
3151371ROSEMS1
80/20
0.5190.519
944641AF1-129 C
80/20
171.179171.179
316240AF1-291 C
80/20
3.4573.457
3151191GRAVEL3
80/20
1.1871.187
316381AD1-082 C
80/20
0.8530.853
934521AD1-076 C
80/20
3.9963.996
934511AD1-075 C
80/20
2.7512.751
316011AB1-132 C OP
80/20
0.9790.979
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.844.84
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.2794.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.6820.682
LAGNLTFEXP_LAGN->PJM
CLTF
1.5581.558
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.3561.356
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.36622.366
CPLELTFEXP_CPLE->PJM
CLTF
2.8462.846
TVALTFEXP_TVA->PJM
CLTF
1.211.21
SIGELTFEXP_SIGE->PJM
CLTF
0.040.04
NYPJM->LTFIMP_NY
CLTF
0.3360.336
LGEELTFEXP_LGEE->PJM
CLTF
0.1940.194
WECLTFEXP_WEC->PJM
CLTF
0.1020.102

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 246T247_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.58 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:934.43
MW Contribution:8.68
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 246T247_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.26 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:989.84
MW Contribution:8.71
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940491AE2-034 C
50/50
0.8920.892
934501AD1-074 C
50/50
31.71231.712
924517AB2-100 E2
50/50
8.748.74
3156021HOLLOMANSOL
50/50
2.4892.489
3156073AA1-063SOLA
50/50
1.9971.997
3151371ROSEMS1
50/50
2.6872.687
961671AG1-007 C
50/50
1.1341.134
316359AB2-059 C OP
50/50
2.062.06
961942AG1-037 E
50/50
0.440.44
943171AE2-346 C
50/50
0.2930.293
961941AG1-037 C
50/50
0.660.66
3151391GASTONA
50/50
6.7836.783
3151381ROSEMG2
50/50
2.0322.032
934332AD1-057 E
50/50
3.0163.016
934331AD1-057 C
50/50
5.7925.792
934321AD1-056 C
50/50
10.38210.382
934322AD1-056 E
50/50
5.6325.632
927022AC1-189 E
50/50
4.9224.922
925595AC1-034 E
50/50
6.1616.161
934512AD1-075 E
50/50
4.0364.036
934502AD1-074 E
50/50
16.14316.143
924516AB2-100 E1
50/50
8.748.74
918512AA1-065 E OP
50/50
7.487.48
966621AG1-532 C
50/50
3.413.41
918532AA1-067 E
50/50
0.8120.812
916042Z1-036 E
Adder
15.8176470588235313.445
316023AB2-100 C2
50/50
2.92.9
960082AF2-299 E
50/50
3.0313.031
946281AF1-292 C
50/50
3.7633.763
926071AC1-086 C
50/50
46.67446.674
316317KELFORD C
50/50
0.4920.492
927021AC1-189 C
50/50
9.889.88
924152AB2-059 E OP
50/50
6.4956.495
940492AE2-034 E
50/50
2.3862.386
934522AD1-076 E
50/50
5.875.87
943172AE2-346 E
50/50
0.7920.792
918492AA1-063AE OP
50/50
5.7985.798
962571AG1-106 C
50/50
6.0376.037
917332KELFORD E
50/50
2.262.26
925122AB2-169 E
50/50
5.9415.941
932631AC2-084 C
50/50
1.4091.409
316274AC1-208 C
50/50
12.9912.99
917342Z2-044 E
50/50
0.7670.767
3151311EDGECMA
50/50
19.40219.402
3156083AA2-088SOLA
50/50
1.0541.054
316141AB2-099 E
50/50
0.330.33
316088AB2-174 E
50/50
14.27714.277
313506AB1-173 C OP
50/50
2.3482.348
923994AB2-040_E
50/50
12.80412.804
3151361ROSEMG1
50/50
4.3384.338
316005AA1-067 C
50/50
0.3090.309
961672AG1-007 E
50/50
0.6430.643
923263AB1-132 E OP
50/50
13.58313.583
3151411GASTONB
50/50
6.7836.783
316181AB2-040 GEN
50/50
2.6442.644
316174AB2-169_C
50/50
1.0821.082
3156063AA2-053SOLA
50/50
2.4332.433
3151281ROARAP4
50/50
2.1872.187
3156011CONETOE2SOL
50/50
1.4931.493
920042AA2-088 E OP
50/50
10.51910.519
934521AD1-076 C
50/50
11.51711.517
934511AD1-075 C
50/50
7.9287.928
3145723EMPORIA
50/50
1.0091.009
316011AB1-132 C OP
50/50
5.1795.179
923573AB1-173 E OP
50/50
6.8296.829
919692AA2-053 E OP
50/50
6.826.82
925785AC1-054 E
50/50
3.6613.661
316263AC1-034 C
50/50
8.1678.167
3145413WATKINS
Adder
0.46352941176470590.394
960081AF2-299 C
50/50
4.5464.546
926072AC1-086 E
50/50
21.24321.243
957862AF2-080 E
50/50
3.9783.978
315614AA2-178 C
50/50
1.2131.213
933981AD1-022 C
50/50
9.1829.182
900672V4-068 E
50/50
0.4080.408
3151261ROARAP2
50/50
2.3112.311
3147043LAWRENC
50/50
0.5750.575
920692AA2-178 E
50/50
3.1813.181
966622AG1-532 E
50/50
2.2732.273
922923AB1-081 E OP
50/50
4.5854.585
316087AB2-174 C
50/50
2.5792.579
962572AG1-106 E
50/50
2.6412.641
926214AC1-099 E
50/50
1.6921.692
932632AC2-084 E
50/50
4.5274.527
3145946PLYMOUTH TP
50/50
0.2950.295
933982AD1-022 E
50/50
4.9994.999
927146AC1-208 E
50/50
5.7685.768
316049AB1-081 C OP
50/50
1.7481.748
3152921DOMTR78
50/50
1.3421.342
316140AB2-099 C
50/50
0.1260.126
3137643SOCKMAN
50/50
1.3241.324
316212AC1-099 C
50/50
0.4430.443
919710AA2-057 E
50/50
5.3045.304
316319Z2-044 C
50/50
0.2710.271
946282AF1-292 E
50/50
2.5092.509
316129AC1-054 C
50/50
1.2981.298
957861AF2-080 C
50/50
8.9748.974
917512Z2-088 E OP1
50/50
5.8425.842
316365AB2-100 C1
50/50
2.92.9
316318V4-068 C
50/50
0.0920.092
316210AC1-098 C
50/50
1.3231.323
926206AC1-098 E
50/50
5.1215.121
316327AA2-057 C
50/50
1.741.74
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.32112.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4748.474
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5081.508
LAGNLTFEXP_LAGN->PJM
CLTF
2.9042.904
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5332.533
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.08239.082
CPLELTFEXP_CPLE->PJM
CLTF
5.3135.313
TVALTFEXP_TVA->PJM
CLTF
2.2652.265
O66PJM->LTFIMP_O-066
CMTX_NF
5.1955.195
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8170.817
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092
NYPJM->LTFIMP_NY
CLTF
0.3730.373
LGEELTFEXP_LGEE->PJM
CLTF
0.470.47
WECLTFEXP_WEC->PJM
CLTF
0.2520.252

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 24642_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.8 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:894.71
MW Contribution:8.59
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316023AB2-100 C2
50/50
2.8872.887
960082AF2-299 E
50/50
3.0163.016
946281AF1-292 C
50/50
3.7453.745
926071AC1-086 C
50/50
46.21146.211
316317KELFORD C
50/50
0.4790.479
927021AC1-189 C
50/50
9.5629.562
924152AB2-059 E OP
50/50
6.3716.371
3145413WATKINS
Adder
0.48352941176470590.411
960081AF2-299 C
50/50
4.5244.524
926072AC1-086 E
50/50
21.03221.032
957862AF2-080 E
50/50
3.853.85
923263AB1-132 E OP
50/50
13.44913.449
3151411GASTONB
50/50
6.7166.716
316181AB2-040 GEN
50/50
2.6272.627
316174AB2-169_C
50/50
1.0031.003
3156063AA2-053SOLA
50/50
2.4022.402
3151281ROARAP4
50/50
2.1662.166
3156011CONETOE2SOL
50/50
1.451.45
3145393UNCAMP
Adder
3.4082352941176472.897
933981AD1-022 C
50/50
8.3948.394
900672V4-068 E
50/50
0.4050.405
3151261ROARAP2
50/50
2.2892.289
3147043LAWRENC
50/50
0.5720.572
3156083AA2-088SOLA
50/50
1.0641.064
316141AB2-099 E
50/50
0.3220.322
316088AB2-174 E
50/50
14.1914.19
313506AB1-173 C OP
50/50
2.3322.332
316087AB2-174 C
50/50
2.5632.563
962572AG1-106 E
50/50
2.6152.615
926214AC1-099 E
50/50
1.6591.659
932632AC2-084 E
50/50
4.4394.439
920692AA2-178 E
Adder
2.65882352941176462.26
966622AG1-532 E
50/50
2.2622.262
922923AB1-081 E OP
50/50
4.4974.497
920042AA2-088 E OP
50/50
10.62410.624
934521AD1-076 C
50/50
10.25610.256
934511AD1-075 C
50/50
7.067.06
3145723EMPORIA
50/50
1.0031.003
316011AB1-132 C OP
50/50
5.1285.128
923573AB1-173 E OP
50/50
6.7836.783
919692AA2-053 E OP
50/50
6.7336.733
925785AC1-054 E
50/50
3.6243.624
316263AC1-034 C
50/50
8.0118.011
3145946PLYMOUTH TP
50/50
0.2610.261
933982AD1-022 E
50/50
4.574.57
927146AC1-208 E
50/50
5.6755.675
316049AB1-081 C OP
50/50
1.7151.715
3152921DOMTR78
50/50
1.2181.218
316140AB2-099 C
50/50
0.1230.123
3137643SOCKMAN
50/50
1.3131.313
316212AC1-099 C
50/50
0.4340.434
919710AA2-057 E
50/50
5.215.21
316319Z2-044 C
50/50
0.2660.266
940492AE2-034 E
Adder
1.99411764705882361.695
934522AD1-076 E
50/50
5.2285.228
943172AE2-346 E
50/50
0.7720.772
918492AA1-063AE OP
50/50
5.7695.769
962571AG1-106 C
50/50
5.9775.977
917332KELFORD E
50/50
2.22.2
925122AB2-169 E
50/50
5.5085.508
932631AC2-084 C
50/50
1.3821.382
316274AC1-208 C
50/50
12.78112.781
917342Z2-044 E
50/50
0.7530.753
3151311EDGECMA
50/50
19.02419.024
934512AD1-075 E
50/50
3.5943.594
934502AD1-074 E
50/50
14.37614.376
924516AB2-100 E1
50/50
8.7018.701
918512AA1-065 E OP
50/50
7.1897.189
966621AG1-532 C
50/50
3.3933.393
918532AA1-067 E
50/50
0.780.78
923994AB2-040_E
50/50
12.71812.718
3151361ROSEMG1
50/50
4.2934.293
316005AA1-067 C
50/50
0.2970.297
961672AG1-007 E
50/50
0.6260.626
946282AF1-292 E
50/50
2.4962.496
316129AC1-054 C
50/50
1.2851.285
957861AF2-080 C
50/50
8.6848.684
917512Z2-088 E OP1
50/50
5.6735.673
961942AG1-037 E
50/50
0.4290.429
943171AE2-346 C
50/50
0.2860.286
961941AG1-037 C
50/50
0.6430.643
3151391GASTONA
50/50
6.7166.716
3151381ROSEMG2
50/50
2.012.01
934332AD1-057 E
50/50
2.9742.974
934331AD1-057 C
50/50
5.7115.711
934321AD1-056 C
50/50
10.23710.237
934322AD1-056 E
50/50
5.5535.553
927022AC1-189 E
50/50
4.7634.763
925595AC1-034 E
50/50
6.0436.043
316365AB2-100 C1
50/50
2.8872.887
316318V4-068 C
50/50
0.0910.091
316210AC1-098 C
50/50
1.2971.297
926206AC1-098 E
50/50
5.0225.022
316327AA2-057 C
50/50
1.7091.709
934501AD1-074 C
50/50
28.2428.24
924517AB2-100 E2
50/50
8.7018.701
3156021HOLLOMANSOL
50/50
2.3922.392
3156073AA1-063SOLA
50/50
1.9871.987
3151371ROSEMS1
50/50
2.6592.659
961671AG1-007 C
50/50
1.1041.104
316359AB2-059 C OP
50/50
2.0212.021
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.98911.989
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.2518.251
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4681.468
LAGNLTFEXP_LAGN->PJM
CLTF
2.8282.828
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4672.467
CBM South 2LTFEXP_CBM-S2->PJM
CBM
38.0738.07
CPLELTFEXP_CPLE->PJM
CLTF
5.1745.174
TVALTFEXP_TVA->PJM
CLTF
2.2062.206
O66PJM->LTFIMP_O-066
CMTX_NF
5.085.08
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7990.799
SIGELTFEXP_SIGE->PJM
CLTF
0.090.09
NYPJM->LTFIMP_NY
CLTF
0.3650.365
LGEELTFEXP_LGEE->PJM
CLTF
0.4580.458
WECLTFEXP_WEC->PJM
CLTF
0.2450.245

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 24662_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 24662_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.79 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:894.66
MW Contribution:8.58
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 24662_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.89 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:945.25
MW Contribution:8.6
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
50/50
27.99627.996
924517AB2-100 E2
50/50
8.6958.695
3156021HOLLOMANSOL
50/50
2.382.38
3156073AA1-063SOLA
50/50
1.9761.976
3151371ROSEMS1
50/50
2.6552.655
961671AG1-007 C
50/50
1.1011.101
316359AB2-059 C OP
50/50
2.0172.017
961942AG1-037 E
50/50
0.4290.429
943171AE2-346 C
50/50
0.2860.286
961941AG1-037 C
50/50
0.6430.643
3151391GASTONA
50/50
6.7066.706
3151381ROSEMG2
50/50
2.0072.007
934332AD1-057 E
50/50
2.9682.968
934331AD1-057 C
50/50
5.75.7
934321AD1-056 C
50/50
10.21910.219
934322AD1-056 E
50/50
5.5435.543
927022AC1-189 E
50/50
4.7464.746
925595AC1-034 E
50/50
6.0316.031
934512AD1-075 E
50/50
3.5633.563
934502AD1-074 E
50/50
14.25214.252
924516AB2-100 E1
50/50
8.6958.695
918512AA1-065 E OP
50/50
7.1527.152
966621AG1-532 C
50/50
3.393.39
918532AA1-067 E
50/50
0.7770.777
923263AB1-132 E OP
50/50
13.42813.428
3151411GASTONB
50/50
6.7066.706
316181AB2-040 GEN
50/50
2.6232.623
316174AB2-169_C
50/50
0.9970.997
3156063AA2-053SOLA
50/50
2.3982.398
3151281ROARAP4
50/50
2.1612.161
3156011CONETOE2SOL
50/50
1.4451.445
316023AB2-100 C2
50/50
2.8852.885
960082AF2-299 E
50/50
3.0133.013
946281AF1-292 C
50/50
3.7413.741
926071AC1-086 C
50/50
46.14246.142
316317KELFORD C
50/50
0.480.48
927021AC1-189 C
50/50
9.5289.528
924152AB2-059 E OP
50/50
6.3586.358
3145413WATKINS
Adder
0.46823529411764710.398
960081AF2-299 C
50/50
4.5194.519
926072AC1-086 E
50/50
21.00121.001
957862AF2-080 E
50/50
3.8363.836
3145393UNCAMP
Adder
3.25058823529411762.763
933981AD1-022 C
50/50
8.3318.331
900672V4-068 E
50/50
0.4020.402
3151261ROARAP2
50/50
2.2842.284
3147043LAWRENC
50/50
0.5710.571
3156083AA2-088SOLA
50/50
1.0481.048
316141AB2-099 E
50/50
0.3220.322
316088AB2-174 E
50/50
14.17214.172
313506AB1-173 C OP
50/50
2.3292.329
923994AB2-040_E
50/50
12.712.7
3151361ROSEMG1
50/50
4.2874.287
316005AA1-067 C
50/50
0.2960.296
961672AG1-007 E
50/50
0.6240.624
940492AE2-034 E
Adder
1.97058823529411781.675
934522AD1-076 E
50/50
5.1825.182
943172AE2-346 E
50/50
0.7720.772
918492AA1-063AE OP
50/50
5.7385.738
962571AG1-106 C
50/50
5.9685.968
917332KELFORD E
50/50
2.2022.202
316087AB2-174 C
50/50
2.5592.559
962572AG1-106 E
50/50
2.6112.611
926214AC1-099 E
50/50
1.6581.658
932632AC2-084 E
50/50
4.4354.435
920042AA2-088 E OP
50/50
10.46410.464
934521AD1-076 C
50/50
10.16810.168
934511AD1-075 C
50/50
6.9996.999
3145723EMPORIA
50/50
1.0021.002
316011AB1-132 C OP
50/50
5.125.12
923573AB1-173 E OP
50/50
6.7736.773
919692AA2-053 E OP
50/50
6.7216.721
925785AC1-054 E
50/50
3.6173.617
316263AC1-034 C
50/50
7.9947.994
920692AA2-178 E
Adder
2.62823529411764722.234
966622AG1-532 E
50/50
2.262.26
922923AB1-081 E OP
50/50
4.4884.488
3145946PLYMOUTH TP
50/50
0.2580.258
933982AD1-022 E
50/50
4.5364.536
927146AC1-208 E
50/50
5.6665.666
316049AB1-081 C OP
50/50
1.7111.711
3152921DOMTR78
50/50
1.2091.209
316140AB2-099 C
50/50
0.1230.123
3137643SOCKMAN
50/50
1.311.31
316212AC1-099 C
50/50
0.4340.434
919710AA2-057 E
50/50
5.2015.201
316319Z2-044 C
50/50
0.2650.265
925122AB2-169 E
50/50
5.4735.473
932631AC2-084 C
50/50
1.381.38
316274AC1-208 C
50/50
12.76112.761
917342Z2-044 E
50/50
0.7520.752
3151311EDGECMA
50/50
18.98218.982
946282AF1-292 E
50/50
2.4942.494
316129AC1-054 C
50/50
1.2831.283
957861AF2-080 C
50/50
8.6538.653
917512Z2-088 E OP1
50/50
5.6555.655
316365AB2-100 C1
50/50
2.8852.885
316318V4-068 C
50/50
0.090.09
316210AC1-098 C
50/50
1.2961.296
926206AC1-098 E
50/50
5.0185.018
316327AA2-057 C
50/50
1.7071.707
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.98111.981
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.2418.241
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4661.466
LAGNLTFEXP_LAGN->PJM
CLTF
2.8242.824
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4612.461
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3838
CPLELTFEXP_CPLE->PJM
CLTF
5.1645.164
TVALTFEXP_TVA->PJM
CLTF
2.2032.203
O66PJM->LTFIMP_O-066
CMTX_NF
5.0655.065
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7960.796
SIGELTFEXP_SIGE->PJM
CLTF
0.090.09
NYPJM->LTFIMP_NY
CLTF
0.3630.363
LGEELTFEXP_LGEE->PJM
CLTF
0.4570.457
WECLTFEXP_WEC->PJM
CLTF
0.2450.245

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.22 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:680.18
MW Contribution:5.5
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.36 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:701.52
MW Contribution:5.49
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
1.4941.494
3151611KERR 4
80/20
0.8620.862
933981AD1-022 C
80/20
5.6875.687
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
3151621KERR 5
80/20
0.8620.862
3152921DOMTR78
80/20
0.8540.854
316140AB2-099 C
80/20
0.0920.092
3137643SOCKMAN
80/20
1.2371.237
316212AC1-099 C
80/20
0.3680.368
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8620.862
3151411GASTONB
80/20
6.1766.176
316181AB2-040 GEN
80/20
2.5112.511
316174AB2-169_C
80/20
0.7190.719
3151151S HAMPT1
80/20
0.9570.957
962571AG1-106 C
80/20
5.4965.496
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22611.226
3151311EDGECMA
80/20
16.55516.555
3151601KERR 3
80/20
0.8620.862
3151581KERR 1
80/20
0.3080.308
3152661PLYWOOD A
80/20
0.6390.639
966621AG1-532 C
80/20
3.2993.299
3156083AA2-088SOLA
80/20
0.9350.935
313506AB1-173 C OP
80/20
2.2292.229
3151361ROSEMG1
80/20
3.9363.936
316005AA1-067 C
80/20
0.2210.221
957481AF2-042 C
80/20
24.31224.312
316023AB2-100 C2
80/20
2.7732.773
946281AF1-292 C
80/20
3.6413.641
926071AC1-086 C
80/20
42.49342.493
316317KELFORD C
80/20
0.370.37
927021AC1-189 C
80/20
7.5497.549
3151531CLOVER1
80/20
5.8195.819
964241AG1-285 C
80/20
7.2257.225
316034AC1-036 C
80/20
0.1240.124
962561AG1-105 C
80/20
5.2875.287
316129AC1-054 C
80/20
1.341.34
957861AF2-080 C
80/20
6.8566.856
316131AB2-060 C
80/20
1.0341.034
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4891.489
316239AB2-077 C O1
80/20
0.2290.229
964791AG1-342 C
80/20
2.0352.035
943171AE2-346 C
80/20
0.2140.214
961941AG1-037 C
80/20
0.4820.482
3151391GASTONA
80/20
6.1766.176
3151381ROSEMG2
80/20
1.8431.843
934331AD1-057 C
80/20
5.1335.133
934321AD1-056 C
80/20
9.2019.201
958211AF2-115 C
80/20
1.1351.135
960081AF2-299 C
80/20
4.3984.398
3151631KERR 6
80/20
0.8620.862
936261AD2-033 C
80/20
8.0298.029
961791AG1-021 C
80/20
0.9080.908
3144293JTRSVLE
80/20
0.2090.209
3156063AA2-053SOLA
80/20
2.1582.158
3151281ROARAP4
80/20
2.0092.009
3156011CONETOE2SOL
80/20
1.1751.175
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
316087AB2-174 C
80/20
2.4642.464
313527AB2-043 C
80/20
0.3630.363
3151591KERR 2
80/20
0.8620.862
934501AD1-074 C
80/20
19.36119.361
3156021HOLLOMANSOL
80/20
1.5861.586
3156073AA1-063SOLA
80/20
1.8141.814
3151371ROSEMS1
80/20
2.4382.438
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4044.404
316359AB2-059 C OP
80/20
1.7611.761
946301AF1-294 C
80/20
1.8661.866
934521AD1-076 C
80/20
7.0327.032
934511AD1-075 C
80/20
4.844.84
316011AB1-132 C OP
80/20
4.7154.715
316263AC1-034 C
80/20
6.9816.981
959311AF2-222 C
80/20
8.6368.636
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.20711.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.5767.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.3611.361
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1882.188
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.15434.154
CPLELTFEXP_CPLE->PJM
CLTF
4.5894.589
TVALTFEXP_TVA->PJM
CLTF
2.0182.018
SIGELTFEXP_SIGE->PJM
CLTF
0.0840.084
NYPJM->LTFIMP_NY
CLTF
0.3660.366
LGEELTFEXP_LGEE->PJM
CLTF
0.4310.431
WECLTFEXP_WEC->PJM
CLTF
0.2290.229

Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.32 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:676.24
MW Contribution:2.66
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.4 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:716.68
MW Contribution:2.65
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
315614AA2-178 C
80/20
3.1813.181
933981AD1-022 C
80/20
18.40618.406
3151261ROARAP2
80/20
1.211.21
3147043LAWRENC
80/20
0.1460.146
934521AD1-076 C
80/20
25.10225.102
934511AD1-075 C
80/20
17.27917.279
316011AB1-132 C OP
80/20
2.2832.283
316263AC1-034 C
80/20
6.2256.225
316049AB1-081 C OP
80/20
1.3321.332
3156116Z1-036WIND
80/20
1.3161.316
3152921DOMTR78
80/20
2.6612.661
316140AB2-099 C
80/20
0.1610.161
3137643SOCKMAN
80/20
0.5730.573
316212AC1-099 C
80/20
0.3860.386
316319Z2-044 C
80/20
0.2070.207
316087AB2-174 C
80/20
0.8050.805
3151411GASTONB
80/20
2.992.99
316181AB2-040 GEN
80/20
0.9190.919
316174AB2-169_C
80/20
1.9111.911
3156063AA2-053SOLA
80/20
1.5851.585
3151281ROARAP4
80/20
1.1451.145
3156011CONETOE2SOL
80/20
1.5831.583
3151151S HAMPT1
80/20
0.4350.435
962571AG1-106 C
80/20
2.6612.661
932631AC2-084 C
80/20
1.2271.227
316274AC1-208 C
80/20
9.5699.569
3151311EDGECMA
80/20
14.76714.767
966621AG1-532 C
80/20
0.8350.835
3156083AA2-088SOLA
80/20
0.6410.641
313506AB1-173 C OP
80/20
0.8160.816
3151361ROSEMG1
80/20
1.9891.989
316005AA1-067 C
80/20
0.4290.429
316023AB2-100 C2
80/20
0.5940.594
946281AF1-292 C
80/20
0.9210.921
926071AC1-086 C
80/20
20.57620.576
316317KELFORD C
80/20
0.5890.589
927021AC1-189 C
80/20
11.49811.498
316129AC1-054 C
80/20
0.6740.674
957861AF2-080 C
80/20
10.44310.443
943171AE2-346 C
80/20
0.3740.374
961941AG1-037 C
80/20
0.8430.843
3151391GASTONA
80/20
2.992.99
3151381ROSEMG2
80/20
0.9310.931
934331AD1-057 C
80/20
3.3453.345
934321AD1-056 C
80/20
5.9965.996
316365AB2-100 C1
80/20
0.5940.594
316318V4-068 C
80/20
0.0840.084
316210AC1-098 C
80/20
1.1521.152
316327AA2-057 C
80/20
1.3351.335
960081AF2-299 C
80/20
1.1131.113
940491AE2-034 C
80/20
2.3412.341
934501AD1-074 C
80/20
69.11769.117
3156021HOLLOMANSOL
80/20
4.1274.127
3156073AA1-063SOLA
80/20
1.1081.108
3151371ROSEMS1
80/20
1.2321.232
961671AG1-007 C
80/20
1.1121.112
316359AB2-059 C OP
80/20
1.571.57
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.90912.909
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4168.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5351.535
LAGNLTFEXP_LAGN->PJM
CLTF
2.8432.843
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4372.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.337.3
CPLELTFEXP_CPLE->PJM
CLTF
5.1125.112
TVALTFEXP_TVA->PJM
CLTF
2.2172.217
SIGELTFEXP_SIGE->PJM
CLTF
0.0950.095
NYPJM->LTFIMP_NY
CLTF
0.2690.269
LGEELTFEXP_LGEE->PJM
CLTF
0.4860.486
WECLTFEXP_WEC->PJM
CLTF
0.2620.262

Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2131_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.14 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:663.74
MW Contribution:2.66
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2131_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.21 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:709.9
MW Contribution:2.66
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938531AE1-072 C
Adder
-6.952941176470588-5.91
315614AA2-178 C
80/20
3.1823.182
933981AD1-022 C
80/20
18.40918.409
3151261ROARAP2
80/20
1.211.21
3147043LAWRENC
80/20
0.1460.146
934521AD1-076 C
80/20
25.10625.106
934511AD1-075 C
80/20
17.28217.282
316011AB1-132 C OP
80/20
2.2842.284
316263AC1-034 C
80/20
6.2276.227
316049AB1-081 C OP
80/20
1.3331.333
3152921DOMTR78
80/20
2.6612.661
316140AB2-099 C
80/20
0.1610.161
3137643SOCKMAN
80/20
0.5730.573
316212AC1-099 C
80/20
0.3860.386
316319Z2-044 C
80/20
0.2070.207
316087AB2-174 C
80/20
0.8060.806
3151411GASTONB
80/20
2.9912.991
316181AB2-040 GEN
80/20
0.920.92
316174AB2-169_C
80/20
1.9121.912
3156063AA2-053SOLA
80/20
1.5851.585
3151281ROARAP4
80/20
1.1451.145
3156011CONETOE2SOL
80/20
1.5831.583
3151151S HAMPT1
80/20
0.4350.435
962571AG1-106 C
80/20
2.6622.662
932631AC2-084 C
80/20
1.2281.228
316274AC1-208 C
80/20
9.5729.572
3151311EDGECMA
80/20
14.77214.772
966621AG1-532 C
80/20
0.8350.835
3156083AA2-088SOLA
80/20
0.6420.642
313506AB1-173 C OP
80/20
0.8170.817
3151361ROSEMG1
80/20
1.9891.989
316005AA1-067 C
80/20
0.4290.429
316023AB2-100 C2
80/20
0.5940.594
946281AF1-292 C
80/20
0.9220.922
926071AC1-086 C
80/20
20.58320.583
316317KELFORD C
80/20
0.5890.589
927021AC1-189 C
80/20
11.50111.501
316129AC1-054 C
80/20
0.6750.675
957861AF2-080 C
80/20
10.44510.445
943171AE2-346 C
80/20
0.3750.375
961941AG1-037 C
80/20
0.8430.843
3151391GASTONA
80/20
2.9912.991
3151381ROSEMG2
80/20
0.9320.932
934331AD1-057 C
80/20
3.3463.346
934321AD1-056 C
80/20
5.9985.998
316365AB2-100 C1
80/20
0.5940.594
316318V4-068 C
80/20
0.0840.084
316210AC1-098 C
80/20
1.1531.153
316327AA2-057 C
80/20
1.3361.336
960081AF2-299 C
80/20
1.1141.114
940491AE2-034 C
80/20
2.3422.342
934501AD1-074 C
80/20
69.12869.128
3156021HOLLOMANSOL
80/20
4.1284.128
3156073AA1-063SOLA
80/20
1.1081.108
3151371ROSEMS1
80/20
1.2321.232
961671AG1-007 C
80/20
1.1131.113
316359AB2-059 C OP
80/20
1.5711.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.00413.004
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4538.453
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5441.544
LAGNLTFEXP_LAGN->PJM
CLTF
2.8532.853
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.442.44
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.35737.357
CPLELTFEXP_CPLE->PJM
CLTF
5.1185.118
TVALTFEXP_TVA->PJM
CLTF
2.2252.225
SIGELTFEXP_SIGE->PJM
CLTF
0.0950.095
NYPJM->LTFIMP_NY
CLTF
0.2650.265
LGEELTFEXP_LGEE->PJM
CLTF
0.4890.489
WECLTFEXP_WEC->PJM
CLTF
0.2640.264

Details for 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 246T247_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.67 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:836.51
MW Contribution:2.11
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 246T247_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.64 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:864.22
MW Contribution:2.08
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316321Z2-027 C
50/50
1.5441.544
940491AE2-034 C
50/50
3.1343.134
934501AD1-074 C
50/50
75.03275.032
3156021HOLLOMANSOL
50/50
2.2042.204
961671AG1-007 C
50/50
0.6860.686
961942AG1-037 E
50/50
0.3050.305
943171AE2-346 C
50/50
0.2030.203
961941AG1-037 C
50/50
0.4580.458
934332AD1-057 E
Adder
1.00470588235294110.854
934331AD1-057 C
Adder
1.93058823529411771.641
934321AD1-056 C
Adder
3.462.941
934322AD1-056 E
Adder
1.87647058823529411.595
927022AC1-189 E
50/50
3.5923.592
934512AD1-075 E
50/50
9.5499.549
934502AD1-074 E
50/50
38.19538.195
918512AA1-065 E OP
50/50
6.6246.624
918532AA1-067 E
50/50
0.7160.716
901082W1-029 E
50/50
123.737123.737
316318V4-068 C
50/50
0.0470.047
316210AC1-098 C
50/50
0.6420.642
926206AC1-098 E
50/50
2.4872.487
923832AB2-022 E
50/50
5.4965.496
916042Z1-036 E
50/50
96.06196.061
926071AC1-086 C
Adder
11.3541176470588239.651
316317KELFORD C
50/50
0.320.32
927021AC1-189 C
50/50
7.2117.211
926072AC1-086 E
Adder
5.1670588235294134.392
957862AF2-080 E
50/50
2.9032.903
913392Y1-086 E
50/50
9.7359.735
3156116Z1-036WIND
50/50
2.212.21
3152921DOMTR78
50/50
2.6812.681
316140AB2-099 C
50/50
0.0870.087
316212AC1-099 C
50/50
0.2150.215
919710AA2-057 E
Adder
2.33411764705882341.984
940492AE2-034 E
50/50
8.3778.377
934522AD1-076 E
50/50
13.88913.889
943172AE2-346 E
50/50
0.5490.549
962571AG1-106 C
Adder
1.4682352941176471.248
917332KELFORD E
50/50
1.4691.469
925122AB2-169 E
50/50
9.4689.468
932631AC2-084 C
50/50
0.6840.684
316274AC1-208 C
Adder
5.3917647058823544.583
917342Z2-044 E
Adder
0.34117647058823530.29
3151311EDGECMA
Adder
8.8164705882352947.494
316320Y1-086 C
50/50
0.9750.975
316141AB2-099 E
50/50
0.2290.229
316005AA1-067 C
50/50
0.2730.273
961672AG1-007 E
50/50
0.3890.389
313526AB2-022 C
50/50
1.6681.668
923263AB1-132 E OP
Adder
3.30470588235294162.809
316174AB2-169_C
50/50
1.7241.724
3156011CONETOE2SOL
50/50
0.9840.984
934521AD1-076 C
50/50
27.2527.25
934511AD1-075 C
50/50
18.75818.758
919692AA2-053 E OP
Adder
2.4470588235294122.08
962572AG1-106 E
Adder
0.64235294117647070.546
926214AC1-099 E
50/50
0.8210.821
932632AC2-084 E
50/50
2.1982.198
957861AF2-080 C
50/50
6.5496.549
938531AE1-072 C
Adder
-13.638823529411765-11.593
315614AA2-178 C
50/50
4.2584.258
933981AD1-022 C
50/50
17.16617.166
900672V4-068 E
50/50
0.210.21
917122Z2-027 E
50/50
5.7015.701
3156056W1-029WIND
50/50
3.0163.016
920692AA2-178 E
50/50
11.16911.169
3145946PLYMOUTH TP
50/50
0.7450.745
933982AD1-022 E
50/50
9.3459.345
927146AC1-208 E
Adder
2.3941176470588242.035
917512Z2-088 E OP1
50/50
3.853.85
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.2317.231
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.8824.882
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.8750.875
LAGNLTFEXP_LAGN->PJM
CLTF
1.6671.667
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.4751.475
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.37422.374
CPLELTFEXP_CPLE->PJM
CLTF
3.0943.094
TVALTFEXP_TVA->PJM
CLTF
1.2981.298
O66PJM->LTFIMP_O-066
CMTX_NF
2.5732.573
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4050.405
SIGELTFEXP_SIGE->PJM
CLTF
0.0540.054
NYPJM->LTFIMP_NY
CLTF
0.1830.183
LGEELTFEXP_LGEE->PJM
CLTF
0.2730.273
WECLTFEXP_WEC->PJM
CLTF
0.1470.147

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: H2T557_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.14 %
Rating:1065.0 MVA
Rating Type:C
MVA to Mitigate:1407.28
MW Contribution:2.63
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: H2T557_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.17 %
Rating:1065.0 MVA
Rating Type:C
MVA to Mitigate:1780.31
MW Contribution:3.08
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3142296MT RD221
50/50
0.1860.186
316004AC1-112 C
50/50
0.4420.442
942001AE2-212 C
Adder
2.1905882352941181.862
3150501FOURRIVERG
50/50
6.2846.284
939192AE1-149 E
Adder
6.6870588235294125.684
939312AE1-162 E
Adder
1.24705882352941181.06
934065AD1-033 E
Adder
3.9752941176470593.379
937226AE2-253 E
Adder
4.6070588235294123.916
943741AF1-042 C
Adder
2.81529411764705852.393
934501AD1-074 C
Adder
24.36705882352941220.712
962861AG1-135 C
Adder
5.8517647058823544.974
924517AB2-100 E2
Adder
2.0282352941176471.724
3141813NORNECK
Adder
0.84941176470588230.722
3150451FOUR RIVERC
50/50
5.0385.038
3150471FOUR RIVERE
50/50
4.0644.064
966872AG1-558 E
50/50
1.7921.792
966871AG1-558 C
50/50
3.5563.556
316076AC2-137 E
Adder
1.54705882352941181.315
3150841SPRUNCB
Adder
10.1282352941176488.609
3150831SPRUNCA
Adder
10.1282352941176488.609
923842AB2-024 E
Adder
1.81529411764705871.543
316157AD2-030 E
Adder
1.1635294117647060.989
926662AC1-147 E
Adder
1.06705882352941180.907
916192Z1-068 E
Adder
1.50117647058823531.276
957492AF2-043 E
Adder
1.12941176470588230.96
923852AB2-025 E
Adder
0.86235294117647050.733
939412AE1-173 E
Adder
40.66352941176470634.564
964211AG1-282 C
Adder
1.95411764705882351.661
961942AG1-037 E
Adder
0.235294117647058850.2
961941AG1-037 C
Adder
0.352941176470588260.3
941032AE2-094 E
Adder
10.4941176470588248.92
941031AE2-094 C
Adder
23.43176470588235519.917
926412AC1-112 E
50/50
1.5121.512
3150681DARBY 2
50/50
3.2633.263
934781AD1-105 C
50/50
1.5491.549
942341AE2-247 C
Adder
1.25176470588235311.064
943462AF1-017 E
Adder
1.8482352941176471.571
958162AF2-110 E
Adder
1.74470588235294131.483
919153AA1-139 E2
Adder
3.21764705882352952.735
934512AD1-075 E
Adder
3.10117647058823562.636
934502AD1-074 E
Adder
12.40352941176470510.543
924516AB2-100 E1
Adder
2.0282352941176471.724
918512AA1-065 E OP
Adder
3.88823529411764753.305
940642AE2-051 E
Adder
7.3317647058823536.232
966621AG1-532 C
Adder
0.94117647058823540.8
963612AG1-210 E
Adder
0.95647058823529410.813
930122AB1-027 E
50/50
1.8591.859
316169AC1-164 GEN
Adder
43.8917647058823537.308
316349AD2-085 C
Adder
2.8882352941176472.455
935112AD1-144 E
Adder
0.77529411764705890.659
944582AF1-123 E
Adder
82.2352941176470769.9
944592AF1-124 E
Adder
82.532941176470670.153
923832AB2-022 E
Adder
0.96823529411764710.823
938772AE1-103 E
Adder
3.09647058823529432.632
916042Z1-036 E
Adder
21.6647058823529418.415
960082AF2-299 E
Adder
0.83647058823529410.711
946281AF1-292 C
Adder
1.03882352941176470.883
926071AC1-086 C
Adder
14.17176470588235312.046
957971AF2-091 C
Adder
1.66117647058823531.412
939261AE1-157 C
Adder
9.7317647058823548.272
966882AG1-559 E
Adder
1.02588235294117650.872
3150461FOUR RIVERD
50/50
4.0644.064
939191AE1-149 C
Adder
10.0305882352941188.526
3143316POE
Adder
1.24941176470588241.062
934146AD1-041 E
Adder
3.52588235294117652.997
957601AF2-054 C
Adder
2.07411764705882361.763
901082W1-029 E
Adder
24.7470588235294121.035
958261AF2-120 C
Adder
6.0223529411764715.119
3150441FOUR RIVERB
50/50
4.1244.124
3150651CHESTF6
Adder
20.39176470588235217.333
946262AF1-291 E
Adder
1.54705882352941181.315
3130536PAPERMILL
Adder
6.6941176470588245.69
939602AE1-190 E
Adder
1.41058823529411771.199
934576AD1-082 E
Adder
3.94470588235294173.353
933292AC2-141 E
Adder
10.1388235294117658.618
944602AF1-125 E
Adder
80.9447058823529368.803
3145506HICKORY
Adder
1.7235294117647061.465
943612AF1-032 E
Adder
0.73411764705882350.624
957871AF2-081 C
Adder
7.8682352941176476.688
936591AD2-074 C
Adder
5.3811764705882354.574
940492AE2-034 E
Adder
2.2764705882352941.935
934522AD1-076 E
Adder
4.5105882352941183.834
943172AE2-346 E
Adder
0.42235294117647060.359
918492AA1-063AE OP
Adder
2.78000000000000022.363
962571AG1-106 C
Adder
1.83294117647058831.558
3150601CHESTF5
Adder
70.6552941176470660.057
925332AB2-190 E
Adder
8.1470588235294116.925
927226AC1-216 E
Adder
7.5517647058823536.419
962962AG1-145 E
Adder
1.38941176470588231.181
936666AD2-085 E
Adder
4.7117647058823534.005
941591AE2-156 C
Adder
14.40941176470588112.248
944591AF1-124 C
Adder
36.0430.634
944601AF1-125 C
Adder
35.35882352941176530.055
938771AE1-103 C
Adder
2.24235294117647041.906
3145413WATKINS
Adder
0.51529411764705880.438
964212AG1-282 E
Adder
1.30235294117647071.107
960081AF2-299 C
Adder
1.2552941176470591.067
926072AC1-086 E
Adder
6.4505882352941175.483
944011AF1-069 C
Adder
4.4164705882352953.754
966881AG1-559 C
Adder
2.03647058823529431.731
3150701DARBY 4
50/50
3.2783.278
3150731STONECA
Adder
7.29647058823529456.202
935161AD1-151 C
Adder
16.05058823529411813.643
315052AA1-145 CT2
50/50
6.5666.566
3150671DARBY 1
50/50
3.2593.259
940432AE2-027 E
Adder
9.0447058823529417.688
934012AD1-025 E
Adder
9.777647058823538.311
939612AE1-191 E
Adder
5.6423529411764714.796
957602AF2-054 E
Adder
1.38235294117647081.175
913392Y1-086 E
Adder
1.71647058823529421.459
939411AE1-173 C
Adder
60.99529411764705651.846
958262AF2-120 E
Adder
4.0152941176470593.413
966661AG1-536 C
Adder
5.184.403
316078AC2-138 E
Adder
0.89294117647058820.759
944491AF1-114 C
Adder
4.88705882352941154.154
944641AF1-129 C
Adder
111.9952941176470695.196
316240AF1-291 C
Adder
2.32117647058823541.973
924814AB2-134 E
Adder
12.37058823529411810.515
942342AE2-247 E
Adder
1.7282352941176471.469
919152AA1-139 E1
Adder
3.21764705882352952.735
920042AA2-088 E OP
Adder
7.6305882352941186.486
934521AD1-076 C
Adder
8.8494117647058837.522
934511AD1-075 C
Adder
6.0917647058823535.178
939246AE1-155 E
Adder
8.3858823529411777.128
3145723EMPORIA
Adder
0.289411764705882370.246
923573AB1-173 E OP
Adder
2.1847058823529411.857
957972AF2-091 E
Adder
2.29411764705882341.95
940431AE2-027 C
Adder
13.56705882352941311.532
942002AE2-212 E
Adder
1.46000000000000021.241
934392AD1-063 E
Adder
1.0717647058823530.911
944581AF1-123 C
Adder
35.91176470588235530.525
941101AE2-104 C
Adder
2.68823529411764732.285
943742AF1-042 E
Adder
4.5941176470588233.905
962862AG1-135 E
Adder
3.9011764705882353.316
966662AG1-536 E
Adder
6.9611764705882355.917
316141AB2-099 E
Adder
0.176470588235294130.15
316088AB2-174 E
Adder
4.3517647058823533.699
923994AB2-040_E
Adder
4.0952941176470593.481
944492AF1-114 E
Adder
6.7482352941176475.736
315051AA1-145 CT1
50/50
6.5696.569
927041AC1-191 C
50/50
14.27914.279
3142366NRTHEST
50/50
0.2420.242
3138116ELKO L286
Adder
1.61294117647058831.371
961611AG1-000B C
Adder
14.80117647058823512.581
940541AE2-040 C
Adder
2.13058823529411741.811
940481AE2-033 C
Adder
11.9247058823529410.136
940482AE2-033 E
Adder
8.0388235294117656.833
923263AB1-132 E OP
Adder
4.1247058823529413.506
963611AG1-210 C
Adder
0.63764705882352950.542
316312AB1-027 C
50/50
0.7090.709
944631AF1-128 C
Adder
44.20941176470588437.578
938552AE1-074 E
Adder
1.21058823529411751.029
316160AE1-175 E
Adder
1.14588235294117660.974
3150921YORKTN3
Adder
107.5905882352941291.452
934782AD1-105 E
50/50
6.4256.425
3145256KINGFORK
Adder
0.83411764705882350.709
925522AC1-027 E
Adder
0.97294117647058820.827
933291AC2-141 C
Adder
23.7529411764705920.19
926755AC1-161 E
Adder
10.1388235294117658.618
941102AE2-104 E
Adder
4.2741176470588243.633
957872AF2-081 E
Adder
3.3717647058823532.866
936592AD2-074 E
Adder
8.7800000000000017.463
962572AG1-106 E
Adder
0.80235294117647070.682
3150431FOUR RIVERA
50/50
4.1244.124
925865AC1-065 E
Adder
16.6414.144
961951AG1-038 C
Adder
3.1117647058823532.645
961952AG1-038 E
Adder
4.297647058823533.653
946282AF1-292 E
Adder
0.69294117647058820.589
936582AD2-073 E
Adder
0.99294117647058820.844
939262AE1-157 E
Adder
5.2788235294117654.487
932046AC2-012 E
Adder
10.5517647058823528.969
958161AF2-110 C
Adder
1.09647058823529430.932
938531AE1-072 C
Adder
13.81411764705882611.742
3145393UNCAMP
Adder
4.6082352941176473.917
933981AD1-022 C
Adder
6.2894117647058835.346
900672V4-068 E
Adder
0.25294117647058820.215
3150481FOUR RIVERF
50/50
4.9634.963
927042AC1-191 E
50/50
7.1137.113
3150691DARBY 3
50/50
3.2743.274
935162AD1-151 E
Adder
10.7000000000000019.095
316233AE1-074 C
Adder
2.40235294117647062.042
940551AE2-041 C
Adder
7.1435294117647066.072
957832AF2-077 E
Adder
1.33764705882352941.137
943461AF1-017 C
Adder
1.13294117647058810.963
932596AC2-079 E
Adder
7.8070588235294126.636
316311AC2-079 C
Adder
4.7847058823529424.067
938532AE1-072 E
Adder
7.2011764705882366.121
3146326AYDLETT TAP
Adder
1.06588235294117650.906
917122Z2-027 E
Adder
1.04588235294117650.889
920692AA2-178 E
Adder
3.0352941176470592.58
966622AG1-532 E
Adder
0.62705882352941180.533
926785AC1-164_E
Adder
19.72000000000000216.762
943471AF1-018 C
Adder
7.1435294117647066.072
316084AB2-161 E
Adder
4.9517647058823524.209
3145946PLYMOUTH TP
Adder
0.234117647058823540.199
933982AD1-022 E
Adder
3.4235294117647062.91
940641AE2-051 C
Adder
10.9988235294117669.349
926472AC1-118 E
Adder
0.95294117647058830.81
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.3964.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0520.052
MECLTFEXP_MEC->PJM
CLTF
0.2980.298
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.1280.128
LAGNLTFEXP_LAGN->PJM
CLTF
2.0762.076
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.6452.645
CBM South 2LTFEXP_CBM-S2->PJM
CBM
41.47141.471
CPLELTFEXP_CPLE->PJM
CLTF
5.5585.558
TVALTFEXP_TVA->PJM
CLTF
1.5691.569
O66PJM->LTFIMP_O-066
CMTX_NF
10.11910.119
G-007PJM->LTFIMP_G-007
CMTX_NF
1.5811.581
SIGELTFEXP_SIGE->PJM
CLTF
0.0090.009
NYPJM->LTFIMP_NY
CLTF
0.8060.806

Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.05 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:637.86
MW Contribution:0.82
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.13 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:677.49
MW Contribution:0.8
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151261ROARAP2
80/20
0.6820.682
3147043LAWRENC
80/20
0.2660.266
3151621KERR 5
80/20
1.5621.562
316336AC2-165 C
Adder
-5.881176470588235-4.999
934611AD1-087 C
80/20
2.212.21
316049AB1-081 C OP
80/20
0.4780.478
3151611KERR 4
80/20
1.5621.562
3137643SOCKMAN
80/20
0.3530.353
316212AC1-099 C
80/20
0.1140.114
316319Z2-044 C
80/20
0.0740.074
937481AD2-202 C
80/20
0.6410.641
3151641KERR 7
80/20
1.5621.562
316123AC1-075 C
80/20
0.9540.954
316205AC1-080 C
80/20
0.3190.319
316222AC1-221 C
80/20
1.581.58
316087AB2-174 C
80/20
0.5890.589
313527AB2-043 C
80/20
0.9080.908
3151591KERR 2
80/20
1.5621.562
316283AC2-100 C
80/20
1.2351.235
3151411GASTONB
80/20
0.9240.924
316181AB2-040 GEN
80/20
0.6330.633
3156063AA2-053SOLA
80/20
0.680.68
3151281ROARAP4
80/20
0.6450.645
316238AB2-078 C O1
80/20
0.5670.567
316237AB2-079 C O1
80/20
0.5670.567
938821AE1-108 C
Adder
-10.591764705882353-9.003
962571AG1-106 C
80/20
0.8220.822
932631AC2-084 C
80/20
0.3610.361
316274AC1-208 C
80/20
3.5443.544
3151311EDGECMA
80/20
5.0435.043
3151601KERR 3
80/20
1.5621.562
3151581KERR 1
80/20
0.5580.558
3152661PLYWOOD A
80/20
1.751.75
941011AE2-092 C
Adder
-9.709411764705882-8.253
966621AG1-532 C
80/20
0.7060.706
316003AC1-222 C
80/20
1.3491.349
936161AD2-022 C
80/20
3.6223.622
313506AB1-173 C OP
80/20
0.5620.562
3151361ROSEMG1
80/20
0.6210.621
957481AF2-042 C
80/20
98.01698.016
946281AF1-292 C
80/20
0.7790.779
926071AC1-086 C
80/20
6.3586.358
3151531CLOVER1
80/20
22.47722.477
964241AG1-285 C
80/20
25.13725.137
316034AC1-036 C
80/20
0.5340.534
962561AG1-105 C
80/20
14.16414.164
942671AE2-283 C
80/20
1.5231.523
316129AC1-054 C
80/20
1.1891.189
316131AB2-060 C
80/20
2.6612.661
3138533PONTONDP
80/20
1.7321.732
316118AC1-105 C
80/20
1.3691.369
316217AC1-145 C
80/20
0.1690.169
3151391GASTONA
80/20
0.9240.924
3151381ROSEMG2
80/20
0.2910.291
934331AD1-057 C
80/20
1.1051.105
934321AD1-056 C
80/20
1.981.98
958211AF2-115 C
80/20
5.8445.844
316210AC1-098 C
80/20
0.3390.339
316327AA2-057 C
80/20
0.4730.473
316239AB2-077 C O1
80/20
0.5670.567
935171AD1-152 C
80/20
2.1562.156
964791AG1-342 C
80/20
5.5375.537
960081AF2-299 C
80/20
0.9420.942
3151541CLOVER2
80/20
22.26722.267
3151631KERR 6
80/20
1.5621.562
936261AD2-033 C
80/20
27.65427.654
961791AG1-021 C
80/20
4.6754.675
3144293JTRSVLE
80/20
1.0761.076
316248AF1-058 C
80/20
0.450.45
936171AD2-023 C
80/20
2.1132.113
941801AE2-185 C
80/20
1.9581.958
3156073AA1-063SOLA
80/20
0.5850.585
3151371ROSEMS1
80/20
0.3850.385
934621AD1-088 C
80/20
18.88918.889
316359AB2-059 C OP
80/20
0.5630.563
946301AF1-294 C
80/20
9.619.61
942461AE2-259 C
80/20
31.13731.137
316197AC1-042 C
80/20
0.1420.142
316011AB1-132 C OP
80/20
0.7060.706
316263AC1-034 C
80/20
2.2322.232
959311AF2-222 C
80/20
38.88938.889
942751AE2-291 C
80/20
8.1328.132
3151561HALLBR1
80/20
0.5580.558
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.1489.148
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.1237.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1991.199
LAGNLTFEXP_LAGN->PJM
CLTF
2.5182.518
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1192.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
35.23335.233
CPLELTFEXP_CPLE->PJM
CLTF
4.4464.446
TVALTFEXP_TVA->PJM
CLTF
1.9681.968
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072
NYPJM->LTFIMP_NY
CLTF
0.3720.372
LGEELTFEXP_LGEE->PJM
CLTF
0.3590.359
WECLTFEXP_WEC->PJM
CLTF
0.190.19

Details for 6HORNRTN-AD1-056 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 254T2141_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6HORNRTN-AD1-056 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 254T2141_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.57 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:722.61
MW Contribution:22.95
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6HORNRTN-AD1-056 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 254T2141_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.72 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:723.44
MW Contribution:22.95
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151371ROSEMS1
50/50
7.4827.482
3151391GASTONA
50/50
17.93517.935
3151381ROSEMG2
50/50
5.6565.656
926071AC1-086 C
50/50
123.404123.404
962571AG1-106 C
50/50
15.96215.962
926072AC1-086 E
50/50
56.16556.165
3151361ROSEMG1
50/50
12.07912.079
923263AB1-132 E OP
50/50
35.91435.914
3151411GASTONB
50/50
17.93517.935
316011AB1-132 C OP
50/50
13.69413.694
962572AG1-106 E
50/50
6.9836.983
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1330.133
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.4150.415
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.180.18
O66PJM->LTFIMP_O-066
CMTX_NF
1.6111.611
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.2390.239
G-007PJM->LTFIMP_G-007
CMTX_NF
0.2510.251
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0840.084
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.6180.618
MDUPJM->LTFIMP_MDU
CLTF
0.0240.024
NYPJM->LTFIMP_NY
CLTF
0.1320.132
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.5030.503
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1380.138

Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.42 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:648.23
MW Contribution:2.66
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.5 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:688.68
MW Contribution:2.65
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
1.3321.332
3156116Z1-036WIND
80/20
1.3161.316
3152921DOMTR78
80/20
2.6612.661
316140AB2-099 C
80/20
0.1610.161
3137643SOCKMAN
80/20
0.5730.573
316212AC1-099 C
80/20
0.3860.386
316319Z2-044 C
80/20
0.2070.207
315614AA2-178 C
80/20
3.1813.181
933981AD1-022 C
80/20
18.40618.406
3151261ROARAP2
80/20
1.211.21
3147043LAWRENC
80/20
0.1460.146
316087AB2-174 C
80/20
0.8050.805
3151411GASTONB
80/20
2.992.99
316181AB2-040 GEN
80/20
0.9190.919
316174AB2-169_C
80/20
1.9111.911
3156063AA2-053SOLA
80/20
1.5851.585
3151281ROARAP4
80/20
1.1451.145
3156011CONETOE2SOL
80/20
1.5831.583
3151151S HAMPT1
80/20
0.4350.435
962571AG1-106 C
80/20
2.6612.661
932631AC2-084 C
80/20
1.2271.227
316274AC1-208 C
80/20
9.5699.569
3151311EDGECMA
80/20
14.76714.767
966621AG1-532 C
80/20
0.8350.835
3156083AA2-088SOLA
80/20
0.6410.641
313506AB1-173 C OP
80/20
0.8160.816
3151361ROSEMG1
80/20
1.9891.989
316005AA1-067 C
80/20
0.4290.429
316023AB2-100 C2
80/20
0.5940.594
946281AF1-292 C
80/20
0.9210.921
926071AC1-086 C
80/20
20.57620.576
316317KELFORD C
80/20
0.5890.589
927021AC1-189 C
80/20
11.49811.498
316129AC1-054 C
80/20
0.6740.674
957861AF2-080 C
80/20
10.44310.443
943171AE2-346 C
80/20
0.3740.374
961941AG1-037 C
80/20
0.8430.843
3151391GASTONA
80/20
2.992.99
3151381ROSEMG2
80/20
0.9310.931
934331AD1-057 C
80/20
3.3453.345
934321AD1-056 C
80/20
5.9965.996
316365AB2-100 C1
80/20
0.5940.594
316318V4-068 C
80/20
0.0840.084
316210AC1-098 C
80/20
1.1521.152
316327AA2-057 C
80/20
1.3351.335
960081AF2-299 C
80/20
1.1131.113
940491AE2-034 C
80/20
2.3412.341
934501AD1-074 C
80/20
69.11769.117
3156021HOLLOMANSOL
80/20
4.1274.127
3156073AA1-063SOLA
80/20
1.1081.108
3151371ROSEMS1
80/20
1.2321.232
961671AG1-007 C
80/20
1.1121.112
316359AB2-059 C OP
80/20
1.571.57
934521AD1-076 C
80/20
25.10225.102
934511AD1-075 C
80/20
17.27917.279
316011AB1-132 C OP
80/20
2.2832.283
316263AC1-034 C
80/20
6.2256.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.90912.909
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4168.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5351.535
LAGNLTFEXP_LAGN->PJM
CLTF
2.8432.843
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4372.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.337.3
CPLELTFEXP_CPLE->PJM
CLTF
5.1125.112
TVALTFEXP_TVA->PJM
CLTF
2.2172.217
SIGELTFEXP_SIGE->PJM
CLTF
0.0950.095
NYPJM->LTFIMP_NY
CLTF
0.2690.269
LGEELTFEXP_LGEE->PJM
CLTF
0.4860.486
WECLTFEXP_WEC->PJM
CLTF
0.2620.262

Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2131_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.23 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:635.73
MW Contribution:2.66
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2131_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.31 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:681.91
MW Contribution:2.66
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
1.3331.333
3152921DOMTR78
80/20
2.6612.661
316140AB2-099 C
80/20
0.1610.161
3137643SOCKMAN
80/20
0.5730.573
938531AE1-072 C
Adder
-6.952941176470588-5.91
315614AA2-178 C
80/20
3.1823.182
933981AD1-022 C
80/20
18.40918.409
3151261ROARAP2
80/20
1.211.21
3147043LAWRENC
80/20
0.1460.146
316212AC1-099 C
80/20
0.3860.386
316319Z2-044 C
80/20
0.2070.207
3151411GASTONB
80/20
2.9912.991
316181AB2-040 GEN
80/20
0.920.92
316174AB2-169_C
80/20
1.9121.912
3156063AA2-053SOLA
80/20
1.5851.585
3151281ROARAP4
80/20
1.1451.145
3156011CONETOE2SOL
80/20
1.5831.583
3151151S HAMPT1
80/20
0.4350.435
962571AG1-106 C
80/20
2.6622.662
932631AC2-084 C
80/20
1.2281.228
316274AC1-208 C
80/20
9.5729.572
3151311EDGECMA
80/20
14.77214.772
966621AG1-532 C
80/20
0.8350.835
3156083AA2-088SOLA
80/20
0.6420.642
313506AB1-173 C OP
80/20
0.8170.817
3151361ROSEMG1
80/20
1.9891.989
316005AA1-067 C
80/20
0.4290.429
316023AB2-100 C2
80/20
0.5940.594
946281AF1-292 C
80/20
0.9220.922
926071AC1-086 C
80/20
20.58320.583
316317KELFORD C
80/20
0.5890.589
927021AC1-189 C
80/20
11.50111.501
316129AC1-054 C
80/20
0.6750.675
957861AF2-080 C
80/20
10.44510.445
943171AE2-346 C
80/20
0.3750.375
961941AG1-037 C
80/20
0.8430.843
3151391GASTONA
80/20
2.9912.991
3151381ROSEMG2
80/20
0.9320.932
934331AD1-057 C
80/20
3.3463.346
934321AD1-056 C
80/20
5.9985.998
316365AB2-100 C1
80/20
0.5940.594
316318V4-068 C
80/20
0.0840.084
316210AC1-098 C
80/20
1.1531.153
316327AA2-057 C
80/20
1.3361.336
960081AF2-299 C
80/20
1.1141.114
316087AB2-174 C
80/20
0.8060.806
940491AE2-034 C
80/20
2.3422.342
934501AD1-074 C
80/20
69.12869.128
3156021HOLLOMANSOL
80/20
4.1284.128
3156073AA1-063SOLA
80/20
1.1081.108
3151371ROSEMS1
80/20
1.2321.232
961671AG1-007 C
80/20
1.1131.113
316359AB2-059 C OP
80/20
1.5711.571
934521AD1-076 C
80/20
25.10625.106
934511AD1-075 C
80/20
17.28217.282
316011AB1-132 C OP
80/20
2.2842.284
316263AC1-034 C
80/20
6.2276.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.00413.004
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4538.453
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5441.544
LAGNLTFEXP_LAGN->PJM
CLTF
2.8532.853
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.442.44
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.35737.357
CPLELTFEXP_CPLE->PJM
CLTF
5.1185.118
TVALTFEXP_TVA->PJM
CLTF
2.2252.225
SIGELTFEXP_SIGE->PJM
CLTF
0.0950.095
NYPJM->LTFIMP_NY
CLTF
0.2650.265
LGEELTFEXP_LGEE->PJM
CLTF
0.4890.489
WECLTFEXP_WEC->PJM
CLTF
0.2640.264

Details for 6POE-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6POE-6TYLER1 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.13 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:563.34
MW Contribution:1.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6POE-6TYLER1 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:588.85
MW Contribution:1.63
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
923852AB2-025 E
50/50
0.7230.723
939412AE1-173 E
Adder
19.10941176470588216.243
961942AG1-037 E
Adder
0.105882352941176470.09
961941AG1-037 C
Adder
0.158823529411764720.135
941032AE2-094 E
Adder
7.1447058823529426.073
941031AE2-094 C
Adder
15.95176470588235213.559
934332AD1-057 E
Adder
0.69411764705882350.59
934331AD1-057 C
Adder
1.3317647058823531.132
934321AD1-056 C
Adder
2.3882352941176472.03
934322AD1-056 E
Adder
1.2952941176470591.101
940541AE2-040 C
50/50
1.7881.788
940481AE2-033 C
50/50
9.8449.844
316349AD2-085 C
Adder
1.69882352941176461.444
938772AE1-103 E
Adder
1.20117647058823531.021
960082AF2-299 E
Adder
0.57764705882352940.491
946281AF1-292 C
Adder
0.71764705882352940.61
926071AC1-086 C
Adder
8.9552941176470597.612
963042AG1-153 E
Adder
3.28588235294117672.793
927021AC1-189 C
Adder
2.7035294117647062.298
964241AG1-285 C
Adder
4.1470588235294123.525
924152AB2-059 E OP
Adder
1.83411764705882341.559
962561AG1-105 C
Adder
2.82588235294117672.402
936666AD2-085 E
Adder
2.77176470588235272.356
938771AE1-103 C
Adder
0.87058823529411770.74
3145413WATKINS
Adder
0.215294117647058830.183
960081AF2-299 C
Adder
0.86705882352941180.737
926072AC1-086 E
Adder
4.0752941176470593.464
944011AF1-069 C
Adder
5.2117647058823534.43
963041AG1-153 C
Adder
2.1905882352941181.862
957862AF2-080 E
Adder
1.08823529411764720.925
962562AG1-105 E
Adder
1.8835294117647061.601
940482AE2-033 E
50/50
6.6366.636
923263AB1-132 E OP
Adder
2.60588235294117652.215
925612AC1-036 E
Adder
0.260.221
924312AB2-078 E O1
Adder
0.440.374
926274AC1-105 E
Adder
0.83529411764705890.71
3145393UNCAMP
Adder
1.841.564
900672V4-068 E
Adder
0.116470588235294130.099
924302AB2-077 E O1
Adder
0.440.374
316141AB2-099 E
Adder
0.080.068
316088AB2-174 E
Adder
2.8647058823529412.435
923994AB2-040_E
Adder
2.63529411764705922.24
957481AF2-042 C
Adder
18.75411764705882315.941
961672AG1-007 E
Adder
0.17764705882352940.151
924322AB2-079 E O1
Adder
0.440.374
962572AG1-106 E
Adder
0.50705882352941180.431
926214AC1-099 E
Adder
0.420.357
932632AC2-084 E
Adder
1.12235294117647060.954
964242AG1-285 E
Adder
2.76470588235294162.35
924162AB2-060 E OP
Adder
1.39764705882352951.188
964792AG1-342 E
Adder
0.74588235294117660.634
943461AF1-017 C
Adder
0.66588235294117650.566
932596AC2-079 E
Adder
4.3541176470588243.701
316311AC2-079 C
Adder
2.6682352941176472.268
966622AG1-532 E
Adder
0.434117647058823550.369
922923AB1-081 E OP
Adder
1.2952941176470591.101
944641AF1-129 C
Adder
-70.29176470588236-59.748
316240AF1-291 C
Adder
-2.144705882352941-1.823
316381AD1-082 C
50/50
1.0531.053
942342AE2-247 E
Adder
1.01647058823529420.864
920042AA2-088 E OP
Adder
3.4941176470588242.97
3145723EMPORIA
Adder
0.196470588235294150.167
923573AB1-173 E OP
Adder
1.40588235294117661.195
919692AA2-053 E OP
Adder
1.57764705882352941.341
925785AC1-054 E
Adder
1.22941176470588221.045
316263AC1-034 C
Adder
2.30588235294117631.96
316084AB2-161 E
50/50
4.6154.615
316083AB2-161 C
50/50
0.4620.462
927146AC1-208 E
Adder
1.43647058823529421.221
934622AD1-088 E
Adder
1.5035294117647061.278
934612AD1-087 E
Adder
1.21882352941176491.036
939411AE1-173 C
Adder
28.66352941176470624.364
3137643SOCKMAN
Adder
0.289411764705882370.246
919710AA2-057 E
Adder
1.39647058823529411.187
934576AD1-082 E
50/50
3.6773.677
943172AE2-346 E
Adder
0.191764705882352950.163
918492AA1-063AE OP
Adder
1.49058823529411751.267
962571AG1-106 C
Adder
1.15882352941176480.985
917332KELFORD E
Adder
0.53411764705882360.454
316274AC1-208 C
Adder
3.23411764705882382.749
917342Z2-044 E
Adder
0.209411764705882350.178
937482AD2-202 E
Adder
0.35647058823529410.303
3151311EDGECMA
Adder
5.4047058823529424.594
942341AE2-247 C
Adder
0.73647058823529410.626
943462AF1-017 E
Adder
1.08705882352941190.924
924516AB2-100 E1
Adder
1.4764705882352941.255
966621AG1-532 C
Adder
0.65058823529411770.553
924022AB2-043 E O1
Adder
1.7070588235294121.451
3147223TWITTYS
Adder
0.288235294117647030.245
316315AB2-025 C
50/50
0.2540.254
946282AF1-292 E
Adder
0.47882352941176470.407
944012AF1-069 E
Adder
2.02470588235294141.721
957861AF2-080 C
Adder
2.4564705882352942.088
917512Z2-088 E OP1
Adder
1.60588235294117651.365
927022AC1-189 E
Adder
1.34705882352941191.145
925595AC1-034 E
Adder
1.74000000000000021.479
939191AE1-149 C
50/50
11.48911.489
3143316POE
50/50
2.8062.806
926206AC1-098 E
Adder
1.26941176470588221.079
964791AG1-342 C
Adder
1.11882352941176480.951
939192AE1-149 E
50/50
7.667.66
924517AB2-100 E2
Adder
1.4764705882352941.255
957482AF2-042 E
Adder
12.50352941176470610.628
961671AG1-007 C
Adder
0.31294117647058830.266
934621AD1-088 C
Adder
3.12235294117647082.654
935172AD1-152 E
Adder
1.7964705882352941.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.5019.501
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7336.733
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1821.182
LAGNLTFEXP_LAGN->PJM
CLTF
2.3242.324
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7591.759
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.05430.054
CPLELTFEXP_CPLE->PJM
CLTF
3.6893.689
TVALTFEXP_TVA->PJM
CLTF
1.8151.815
O66PJM->LTFIMP_O-066
CMTX_NF
4.8534.853
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7620.762
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072
NYPJM->LTFIMP_NY
CLTF
0.3510.351
LGEELTFEXP_LGEE->PJM
CLTF
0.3660.366
WECLTFEXP_WEC->PJM
CLTF
0.1950.195

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 246T247_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.57 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1025.65
MW Contribution:8.68
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316023AB2-100 C2
50/50
2.8992.899
960082AF2-299 E
50/50
3.033.03
946281AF1-292 C
50/50
3.7633.763
926071AC1-086 C
50/50
46.66546.665
316317KELFORD C
50/50
0.4920.492
927021AC1-189 C
50/50
9.8769.876
924152AB2-059 E OP
50/50
6.4936.493
3145413WATKINS
Adder
0.46352941176470590.394
960081AF2-299 C
50/50
4.5464.546
926072AC1-086 E
50/50
21.23921.239
957862AF2-080 E
50/50
3.9763.976
940541AE2-040 C
50/50
11.90111.901
940481AE2-033 C
50/50
64.71464.714
940482AE2-033 E
50/50
43.62743.627
923263AB1-132 E OP
50/50
13.58113.581
3151411GASTONB
50/50
6.7826.782
316181AB2-040 GEN
50/50
2.6442.644
316174AB2-169_C
50/50
1.0811.081
3156063AA2-053SOLA
50/50
2.4322.432
3151281ROARAP4
50/50
2.1862.186
3156011CONETOE2SOL
50/50
1.4931.493
933981AD1-022 C
50/50
9.1789.178
900672V4-068 E
50/50
0.4080.408
3151261ROARAP2
50/50
2.3112.311
3147043LAWRENC
50/50
0.5750.575
3156083AA2-088SOLA
50/50
1.0531.053
316141AB2-099 E
50/50
0.330.33
316088AB2-174 E
50/50
14.27414.274
313506AB1-173 C OP
50/50
2.3472.347
923994AB2-040_E
50/50
12.80212.802
3151361ROSEMG1
50/50
4.3384.338
316005AA1-067 C
50/50
0.3090.309
961672AG1-007 E
50/50
0.6420.642
316087AB2-174 C
50/50
2.5782.578
962572AG1-106 E
50/50
2.6412.641
926214AC1-099 E
50/50
1.6911.691
932632AC2-084 E
50/50
4.5254.525
920692AA2-178 E
Adder
3.17882352941176462.702
966622AG1-532 E
50/50
2.2732.273
922923AB1-081 E OP
50/50
4.5834.583
920042AA2-088 E OP
50/50
10.51410.514
934521AD1-076 C
Adder
11.5117647058823539.785
934511AD1-075 C
Adder
7.9247058823529416.736
3145723EMPORIA
50/50
1.0091.009
316011AB1-132 C OP
50/50
5.1785.178
923573AB1-173 E OP
50/50
6.8286.828
919692AA2-053 E OP
50/50
6.8186.818
925785AC1-054 E
50/50
3.6593.659
316263AC1-034 C
50/50
8.1648.164
3145946PLYMOUTH TP
Adder
0.29529411764705880.251
933982AD1-022 E
50/50
4.9974.997
927146AC1-208 E
50/50
5.7665.766
316049AB1-081 C OP
50/50
1.7471.747
316140AB2-099 C
50/50
0.1260.126
3137643SOCKMAN
50/50
1.3231.323
316212AC1-099 C
50/50
0.4430.443
919710AA2-057 E
50/50
5.3025.302
316319Z2-044 C
50/50
0.2710.271
940492AE2-034 E
Adder
2.38470588235294122.027
934522AD1-076 E
Adder
5.8670588235294124.987
943172AE2-346 E
50/50
0.7920.792
918492AA1-063AE OP
50/50
5.7965.796
962571AG1-106 C
50/50
6.0366.036
917332KELFORD E
50/50
2.262.26
925122AB2-169 E
50/50
5.9385.938
932631AC2-084 C
50/50
1.4081.408
316274AC1-208 C
50/50
12.98612.986
917342Z2-044 E
50/50
0.7670.767
3151311EDGECMA
50/50
19.39519.395
934512AD1-075 E
Adder
4.0341176470588243.429
934502AD1-074 E
Adder
16.1352941176470613.715
924516AB2-100 E1
50/50
8.7398.739
918512AA1-065 E OP
50/50
7.4787.478
966621AG1-532 C
50/50
3.4093.409
918532AA1-067 E
50/50
0.8110.811
316315AB2-025 C
50/50
1.691.69
946282AF1-292 E
50/50
2.5082.508
316129AC1-054 C
50/50
1.2981.298
957861AF2-080 C
50/50
8.978.97
917512Z2-088 E OP1
50/50
5.845.84
923852AB2-025 E
50/50
4.8134.813
961942AG1-037 E
50/50
0.440.44
943171AE2-346 C
50/50
0.2930.293
961941AG1-037 C
50/50
0.660.66
3151391GASTONA
50/50
6.7826.782
3151381ROSEMG2
50/50
2.0312.031
934332AD1-057 E
50/50
3.0153.015
934331AD1-057 C
50/50
5.795.79
934321AD1-056 C
50/50
10.3810.38
934322AD1-056 E
50/50
5.635.63
927022AC1-189 E
50/50
4.924.92
925595AC1-034 E
50/50
6.1596.159
316365AB2-100 C1
50/50
2.8992.899
316318V4-068 C
50/50
0.0920.092
316210AC1-098 C
50/50
1.3221.322
926206AC1-098 E
50/50
5.1195.119
316327AA2-057 C
50/50
1.741.74
934501AD1-074 C
Adder
31.6976470588235326.943
924517AB2-100 E2
50/50
8.7398.739
3156021HOLLOMANSOL
50/50
2.4882.488
3156073AA1-063SOLA
50/50
1.9971.997
3151371ROSEMS1
50/50
2.6872.687
961671AG1-007 C
50/50
1.1341.134
316359AB2-059 C OP
50/50
2.062.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.20112.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4278.427
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4961.496
LAGNLTFEXP_LAGN->PJM
CLTF
2.8922.892
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.532.53
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.00939.009
CPLELTFEXP_CPLE->PJM
CLTF
5.3075.307
TVALTFEXP_TVA->PJM
CLTF
2.2552.255
O66PJM->LTFIMP_O-066
CMTX_NF
5.2435.243
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8240.824
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092
NYPJM->LTFIMP_NY
CLTF
0.3770.377
LGEELTFEXP_LGEE->PJM
CLTF
0.4660.466
WECLTFEXP_WEC->PJM
CLTF
0.250.25

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.21 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:761.57
MW Contribution:5.5
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.21 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:781.94
MW Contribution:5.49
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
1.4931.493
3151611KERR 4
80/20
0.8610.861
933981AD1-022 C
80/20
5.6845.684
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
3151621KERR 5
80/20
0.8610.861
3152921DOMTR78
80/20
0.8530.853
316140AB2-099 C
80/20
0.0920.092
3137643SOCKMAN
80/20
1.2371.237
316212AC1-099 C
80/20
0.3680.368
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8610.861
940541AE2-040 C
80/20
11.68811.688
940481AE2-033 C
80/20
63.40163.401
3151411GASTONB
80/20
6.1746.174
316181AB2-040 GEN
80/20
2.512.51
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1572.157
3151281ROARAP4
80/20
2.0092.009
3156011CONETOE2SOL
80/20
1.1751.175
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
3151151S HAMPT1
80/20
0.9560.956
962571AG1-106 C
80/20
5.4955.495
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22211.222
3151311EDGECMA
80/20
16.54816.548
3151601KERR 3
80/20
0.8610.861
3151581KERR 1
80/20
0.3070.307
3152661PLYWOOD A
80/20
0.6380.638
966621AG1-532 C
80/20
3.2983.298
3156083AA2-088SOLA
80/20
0.9350.935
313506AB1-173 C OP
80/20
2.2292.229
3151361ROSEMG1
80/20
3.9353.935
316005AA1-067 C
80/20
0.2210.221
957481AF2-042 C
80/20
24.2924.29
316023AB2-100 C2
80/20
2.7732.773
946281AF1-292 C
80/20
3.643.64
926071AC1-086 C
80/20
42.48542.485
316317KELFORD C
80/20
0.3690.369
927021AC1-189 C
80/20
7.5457.545
3151531CLOVER1
80/20
5.8145.814
964241AG1-285 C
80/20
7.2197.219
316034AC1-036 C
80/20
0.1230.123
962561AG1-105 C
80/20
5.2835.283
316315AB2-025 C
80/20
1.661.66
316129AC1-054 C
80/20
1.341.34
957861AF2-080 C
80/20
6.8536.853
316131AB2-060 C
80/20
1.0331.033
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
943171AE2-346 C
80/20
0.2140.214
961941AG1-037 C
80/20
0.4820.482
3151391GASTONA
80/20
6.1746.174
3151381ROSEMG2
80/20
1.8431.843
934331AD1-057 C
80/20
5.1315.131
934321AD1-056 C
80/20
9.1989.198
958211AF2-115 C
80/20
1.1341.134
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4881.488
316239AB2-077 C O1
80/20
0.2290.229
964791AG1-342 C
80/20
2.0342.034
960081AF2-299 C
80/20
4.3984.398
3151631KERR 6
80/20
0.8610.861
936261AD2-033 C
80/20
8.0238.023
961791AG1-021 C
80/20
0.9070.907
3144293JTRSVLE
80/20
0.2090.209
316087AB2-174 C
80/20
2.4642.464
313527AB2-043 C
80/20
0.3630.363
3151591KERR 2
80/20
0.8610.861
934501AD1-074 C
80/20
19.34719.347
3156021HOLLOMANSOL
80/20
1.5851.585
3156073AA1-063SOLA
80/20
1.8141.814
3151371ROSEMS1
80/20
2.4382.438
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4014.401
316359AB2-059 C OP
80/20
1.761.76
946301AF1-294 C
80/20
1.8641.864
934521AD1-076 C
80/20
7.0267.026
934511AD1-075 C
80/20
4.8374.837
316011AB1-132 C OP
80/20
4.7154.715
316263AC1-034 C
80/20
6.9786.978
959311AF2-222 C
80/20
8.6298.629
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.08611.086
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.537.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.351.35
LAGNLTFEXP_LAGN->PJM
CLTF
2.5652.565
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1852.185
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.08134.081
CPLELTFEXP_CPLE->PJM
CLTF
4.5834.583
TVALTFEXP_TVA->PJM
CLTF
2.0082.008
SIGELTFEXP_SIGE->PJM
CLTF
0.0830.083
NYPJM->LTFIMP_NY
CLTF
0.370.37
LGEELTFEXP_LGEE->PJM
CLTF
0.4270.427
WECLTFEXP_WEC->PJM
CLTF
0.2270.227

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.1 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:753.98
MW Contribution:5.97
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.29 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:816.35
MW Contribution:5.98
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
1.711.71
3151611KERR 4
80/20
0.6570.657
3156116Z1-036WIND
80/20
0.2550.255
3152921DOMTR78
80/20
1.211.21
316140AB2-099 C
80/20
0.1220.122
3137643SOCKMAN
80/20
1.3091.309
316212AC1-099 C
80/20
0.4330.433
316319Z2-044 C
80/20
0.2650.265
3151641KERR 7
80/20
0.6570.657
315614AA2-178 C
80/20
1.0031.003
933981AD1-022 C
80/20
8.3398.339
3151261ROARAP2
80/20
2.2812.281
3147043LAWRENC
80/20
0.5710.571
3151621KERR 5
80/20
0.6570.657
316087AB2-174 C
80/20
2.5582.558
313527AB2-043 C
80/20
0.2330.233
940541AE2-040 C
80/20
11.88611.886
940481AE2-033 C
80/20
64.6164.61
3151411GASTONB
80/20
6.7056.705
316181AB2-040 GEN
80/20
2.6212.621
316174AB2-169_C
80/20
0.9970.997
3156063AA2-053SOLA
80/20
2.3932.393
3151281ROARAP4
80/20
2.1582.158
3156011CONETOE2SOL
80/20
1.4451.445
316238AB2-078 C O1
80/20
0.1480.148
316237AB2-079 C O1
80/20
0.1480.148
3151151S HAMPT1
80/20
1.0411.041
962571AG1-106 C
80/20
5.9675.967
932631AC2-084 C
80/20
1.3771.377
316274AC1-208 C
80/20
12.73812.738
3151311EDGECMA
80/20
18.97618.976
3151601KERR 3
80/20
0.6570.657
3151581KERR 1
80/20
0.2350.235
966621AG1-532 C
80/20
3.3883.388
3156083AA2-088SOLA
80/20
1.0451.045
313506AB1-173 C OP
80/20
2.3272.327
3151361ROSEMG1
80/20
4.2864.286
316005AA1-067 C
80/20
0.2960.296
316023AB2-100 C2
80/20
2.8842.884
946281AF1-292 C
80/20
3.743.74
926071AC1-086 C
80/20
46.13446.134
316317KELFORD C
80/20
0.4770.477
927021AC1-189 C
80/20
9.5299.529
962561AG1-105 C
80/20
3.043.04
316315AB2-025 C
80/20
1.6881.688
316129AC1-054 C
80/20
1.2811.281
957861AF2-080 C
80/20
8.6558.655
316131AB2-060 C
80/20
0.6590.659
943171AE2-346 C
80/20
0.2840.284
961941AG1-037 C
80/20
0.6390.639
3151391GASTONA
80/20
6.7056.705
3151381ROSEMG2
80/20
2.0072.007
934331AD1-057 C
80/20
5.6995.699
934321AD1-056 C
80/20
10.21610.216
316365AB2-100 C1
80/20
2.8842.884
316318V4-068 C
80/20
0.090.09
316210AC1-098 C
80/20
1.2931.293
316327AA2-057 C
80/20
1.7041.704
316239AB2-077 C O1
80/20
0.1480.148
964791AG1-342 C
80/20
1.1391.139
938771AE1-103 C
80/20
1.2891.289
960081AF2-299 C
80/20
4.5184.518
3151631KERR 6
80/20
0.6570.657
936261AD2-033 C
80/20
4.7864.786
3151591KERR 2
80/20
0.6570.657
940491AE2-034 C
80/20
0.7380.738
934501AD1-074 C
80/20
28.02128.021
3156021HOLLOMANSOL
80/20
2.3822.382
3156073AA1-063SOLA
80/20
1.9731.973
3151371ROSEMS1
80/20
2.6552.655
961671AG1-007 C
80/20
1.1011.101
316359AB2-059 C OP
80/20
2.0162.016
934521AD1-076 C
80/20
10.17610.176
934511AD1-075 C
80/20
7.0057.005
316011AB1-132 C OP
80/20
5.125.12
316263AC1-034 C
80/20
7.9897.989
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.86411.864
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.1968.196
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4551.455
LAGNLTFEXP_LAGN->PJM
CLTF
2.8132.813
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4592.459
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.93537.935
CPLELTFEXP_CPLE->PJM
CLTF
5.1585.158
TVALTFEXP_TVA->PJM
CLTF
2.1942.194
SIGELTFEXP_SIGE->PJM
CLTF
0.0890.089
NYPJM->LTFIMP_NY
CLTF
0.3670.367
LGEELTFEXP_LGEE->PJM
CLTF
0.4530.453
WECLTFEXP_WEC->PJM
CLTF
0.2430.243

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.16 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4182.74
MW Contribution:5.66
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.7 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4637.48
MW Contribution:5.7
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
939192AE1-149 E
Adder
8.7694117647058827.454
939312AE1-162 E
Adder
1.95882352941176491.665
3150991CHESPKB
50/50
1.1051.105
934065AD1-033 E
50/50
7.7977.797
937226AE2-253 E
50/50
9.0629.062
934501AD1-074 C
Adder
50.2447058823529442.708
924517AB2-100 E2
Adder
4.23058823529411753.596
957482AF2-042 E
50/50
55.48555.485
961671AG1-007 C
Adder
1.33294117647058831.133
934621AD1-088 C
Adder
13.82823529411764711.754
935172AD1-152 E
Adder
7.9105882352941186.724
926662AC1-147 E
50/50
2.0262.026
916192Z1-068 E
50/50
2.92.9
957492AF2-043 E
Adder
2.16705882352941171.842
923852AB2-025 E
50/50
1.7231.723
939412AE1-173 E
50/50
105.86105.86
961942AG1-037 E
Adder
0.494117647058823550.42
961941AG1-037 C
Adder
0.74117647058823530.63
941032AE2-094 E
50/50
32.01732.017
941031AE2-094 C
50/50
71.48571.485
934332AD1-057 E
Adder
2.5917647058823532.203
934331AD1-057 C
Adder
4.9764705882352954.23
934321AD1-056 C
Adder
8.927.582
934322AD1-056 E
Adder
4.8388235294117664.113
927022AC1-189 E
Adder
5.9882352941176475.09
925595AC1-034 E
Adder
7.0494117647058835.992
942341AE2-247 C
Adder
2.11764705882352941.8
943462AF1-017 E
Adder
3.12588235294117662.657
958162AF2-110 E
Adder
3.24941176470588242.762
316388AE2-253 GEN
50/50
3.0473.047
919153AA1-139 E2
50/50
6.336.33
934512AD1-075 E
Adder
6.3941176470588235.435
934502AD1-074 E
Adder
25.5776470588235321.741
924516AB2-100 E1
Adder
4.23058823529411753.596
918512AA1-065 E OP
Adder
8.1470588235294116.925
940642AE2-051 E
50/50
20.9220.92
966621AG1-532 C
Adder
2.0317647058823531.727
918532AA1-067 E
Adder
1.02823529411764710.874
924022AB2-043 E O1
Adder
7.1670588235294126.092
3147223TWITTYS
Adder
1.2588235294117651.07
959312AF2-222 E
Adder
2.9682352941176472.523
316349AD2-085 C
Adder
4.8858823529411764.153
935112AD1-144 E
Adder
1.38117647058823521.174
3151091ELIZAR2
50/50
4.8274.827
944582AF1-123 E
50/50
161.69161.69
944592AF1-124 E
50/50
162.275162.275
923832AB2-022 E
50/50
1.9081.908
938772AE1-103 E
Adder
6.0023529411764715.102
916042Z1-036 E
Adder
43.3141176470588236.817
960082AF2-299 E
Adder
1.80588235294117651.535
946281AF1-292 C
Adder
2.24235294117647041.906
926071AC1-086 C
Adder
30.4329411764705925.868
3151051BRUNSWICKS1
50/50
30.03530.035
963042AG1-153 E
50/50
14.69214.692
927021AC1-189 C
Adder
12.02000000000000110.217
964241AG1-285 C
Adder
17.9658823529411815.271
924152AB2-059 E OP
Adder
7.4317647058823546.317
962561AG1-105 C
Adder
12.04705882352941210.24
934576AD1-082 E
Adder
5.7482352941176484.886
916191Z1-068 C
50/50
0.0680.068
933292AC2-141 E
50/50
20.76320.763
316294AC1-161 C
50/50
7.9487.948
944602AF1-125 E
50/50
159.152159.152
3145506HICKORY
50/50
3.3883.388
943612AF1-032 E
Adder
1.40823529411764731.197
957871AF2-081 C
50/50
15.47915.479
940492AE2-034 E
Adder
4.6305882352941183.936
934522AD1-076 E
Adder
9.3011764705882357.906
943172AE2-346 E
Adder
0.88941176470588230.756
918492AA1-063AE OP
Adder
5.9423529411764715.051
961611AG1-000B C
Adder
19.52941176470588416.6
316375AC2-012 C
50/50
2.0662.066
313526AB2-022 C
50/50
0.5790.579
940541AE2-040 C
Adder
4.263.621
940481AE2-033 C
Adder
23.97176470588235420.376
940482AE2-033 E
Adder
16.1613.736
923263AB1-132 E OP
Adder
8.8564705882352937.528
3152441Z1-086 ST
50/50
32.38732.387
3152431Z1-086 GT3
50/50
18.59718.597
3152421Z1-086 GT2
50/50
18.59718.597
925612AC1-036 E
Adder
1.13647058823529410.966
924312AB2-078 E O1
Adder
1.84705882352941191.57
926274AC1-105 E
Adder
3.63.06
942342AE2-247 E
Adder
2.92470588235294172.486
316036AC1-147 C
50/50
0.5640.564
919152AA1-139 E1
50/50
6.336.33
316018AA1-139 ULT2
50/50
1.6761.676
920042AA2-088 E OP
Adder
15.59882352941176513.259
934521AD1-076 C
Adder
18.24823529411764515.511
934511AD1-075 C
Adder
12.56117647058823510.677
3145723EMPORIA
Adder
0.62470588235294120.531
923573AB1-173 E OP
Adder
4.7517647058823534.039
919692AA2-053 E OP
Adder
6.1282352941176475.209
925785AC1-054 E
Adder
4.8741176470588234.143
316263AC1-034 C
Adder
9.344705882352947.943
959311AF2-222 C
Adder
21.718.445
936666AD2-085 E
Adder
7.9705882352941196.775
941591AE2-156 C
50/50
27.4127.41
3151081ELIZAR1
50/50
4.9124.912
316316AC1-027 C
50/50
0.4870.487
944591AF1-124 C
50/50
70.86170.861
944601AF1-125 C
50/50
69.52369.523
938771AE1-103 C
Adder
4.3470588235294113.695
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.70823529411764732.302
926072AC1-086 E
Adder
13.85058823529411711.773
944011AF1-069 C
50/50
23.35723.357
963041AG1-153 C
50/50
9.7959.795
957862AF2-080 E
Adder
4.844.114
962562AG1-105 E
Adder
8.0317647058823526.827
932046AC2-012 E
50/50
20.04320.043
958161AF2-110 C
Adder
2.04352941176470631.737
316017AA1-139 ULT1
50/50
1.6761.676
938531AE1-072 C
50/50
27.18327.183
3145393UNCAMP
Adder
9.0117647058823537.66
933981AD1-022 C
Adder
13.02235294117647211.069
900672V4-068 E
Adder
0.52352941176470590.445
3152411Z1-086 GT1
50/50
18.60518.605
924302AB2-077 E O1
Adder
1.84705882352941191.57
943461AF1-017 C
Adder
1.91529411764705881.628
932596AC2-079 E
Adder
13.36941176470588411.364
316311AC2-079 C
Adder
8.1941176470588236.965
938532AE1-072 E
50/50
14.1714.17
3146326AYDLETT TAP
50/50
2.0962.096
917122Z2-027 E
Adder
2.061.751
920692AA2-178 E
Adder
6.1741176470588245.248
966622AG1-532 E
Adder
1.35411764705882361.151
922923AB1-081 E OP
Adder
5.2458823529411764.459
3150981CHESPKA
50/50
0.6670.667
316185AD1-033 C
50/50
1.9111.911
944581AF1-123 C
50/50
70.6170.61
941101AE2-104 C
Adder
5.00705882352941254.256
316320Y1-086 C
50/50
0.3390.339
316141AB2-099 E
Adder
0.370588235294117660.315
316088AB2-174 E
Adder
9.4435294117647068.027
923994AB2-040_E
Adder
8.9094117647058837.573
957481AF2-042 C
50/50
83.22783.227
961672AG1-007 E
Adder
0.75529411764705890.642
924322AB2-079 E O1
Adder
1.84705882352941191.57
962571AG1-106 C
Adder
3.9364705882352943.346
917332KELFORD E
Adder
2.39764705882352922.038
925122AB2-169 E
Adder
8.4305882352941197.166
316274AC1-208 C
Adder
12.93882352941176410.998
917342Z2-044 E
Adder
0.84705882352941180.72
937482AD2-202 E
Adder
1.57764705882352941.341
3151311EDGECMA
Adder
21.84705882352941218.57
3150921YORKTN3
Adder
152.65647058823532129.758
3145256KINGFORK
Adder
1.48823529411764691.265
925522AC1-027 E
50/50
1.8771.877
933291AC2-141 C
50/50
48.6448.64
926755AC1-161 E
50/50
20.76320.763
941102AE2-104 E
Adder
7.966.766
957872AF2-081 E
50/50
6.6346.634
962572AG1-106 E
Adder
1.72235294117647061.464
926214AC1-099 E
Adder
1.73647058823529421.476
932632AC2-084 E
Adder
4.6458823529411763.949
964242AG1-285 E
Adder
11.97764705882352810.181
924162AB2-060 E OP
Adder
5.8752941176470594.994
964792AG1-342 E
Adder
3.1905882352941182.712
316084AB2-161 E
Adder
7.2141176470588236.132
3145946PLYMOUTH TP
Adder
0.48235294117647060.41
933982AD1-022 E
Adder
7.0894117647058836.026
940641AE2-051 C
50/50
31.3831.38
927146AC1-208 E
Adder
5.74470588235294164.883
934622AD1-088 E
Adder
6.6576470588235295.659
934612AD1-087 E
Adder
5.3905882352941184.582
913392Y1-086 E
50/50
3.383.38
939411AE1-173 C
50/50
158.79158.79
3137643SOCKMAN
Adder
1.03058823529411760.876
3151031BRUNSWICKG2
50/50
14.45714.457
919710AA2-057 E
Adder
5.6458823529411774.799
3151101ELIZAR3
50/50
4.9744.974
316315AB2-025 C
50/50
0.6050.605
946282AF1-292 E
Adder
1.49529411764705871.271
944012AF1-069 E
50/50
9.0749.074
957861AF2-080 C
Adder
10.917647058823539.28
917512Z2-088 E OP1
Adder
6.9717647058823535.926
939191AE1-149 C
Adder
13.15411764705882411.181
3143316POE
Adder
1.71764705882352931.46
901082W1-029 E
Adder
48.63529411764706441.34
926206AC1-098 E
Adder
5.25647058823529444.468
3151041BRUNSWICKG3
50/50
14.45714.457
3151021BRUNSWICKG1
50/50
14.45714.457
964791AG1-342 C
Adder
4.7858823529411764.068
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.88834.888
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.38927.389
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.6044.604
LAGNLTFEXP_LAGN->PJM
CLTF
9.689.68
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6337.633
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.923129.923
CPLELTFEXP_CPLE->PJM
CLTF
16.01716.017
TVALTFEXP_TVA->PJM
CLTF
7.5637.563
O66PJM->LTFIMP_O-066
CMTX_NF
29.52729.527
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6364.636
SIGELTFEXP_SIGE->PJM
CLTF
0.2790.279
NYPJM->LTFIMP_NY
CLTF
2.172.17
LGEELTFEXP_LGEE->PJM
CLTF
1.3891.389
WECLTFEXP_WEC->PJM
CLTF
0.7290.729

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.22 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4106.12
MW Contribution:5.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
932046AC2-012 E
50/50
18.21618.216
958161AF2-110 C
Adder
1.8752941176470591.594
316017AA1-139 ULT1
50/50
1.5241.524
938531AE1-072 C
50/50
24.73924.739
3145393UNCAMP
Adder
8.3505882352941197.098
933981AD1-022 C
Adder
12.09058823529411710.277
900672V4-068 E
Adder
0.490588235294117660.417
3152411Z1-086 GT1
50/50
17.81217.812
924302AB2-077 E O1
Adder
1.77764705882352941.511
316084AB2-161 E
Adder
6.8258823529411765.802
3145946PLYMOUTH TP
Adder
0.44705882352941180.38
933982AD1-022 E
Adder
6.582352941176475.595
940641AE2-051 C
50/50
29.73129.731
927146AC1-208 E
Adder
5.44117647058823554.625
934622AD1-088 E
Adder
6.4094117647058835.448
934611AD1-087 C
50/50
1.7961.796
934612AD1-087 E
50/50
5.1825.182
913392Y1-086 E
Adder
3.08235294117647072.62
939411AE1-173 C
50/50
149.153149.153
3137643SOCKMAN
Adder
0.97882352941176460.832
3151031BRUNSWICKG2
50/50
13.84313.843
919710AA2-057 E
Adder
5.3541176470588244.551
937481AD2-202 C
50/50
0.5210.521
942341AE2-247 C
Adder
1.9647058823529411.67
943462AF1-017 E
Adder
2.90117647058823552.466
958162AF2-110 E
Adder
2.98235294117647072.535
316388AE2-253 GEN
50/50
2.7712.771
919153AA1-139 E2
50/50
5.7585.758
934512AD1-075 E
Adder
5.9258823529411765.037
934502AD1-074 E
Adder
23.70588235294117420.15
924516AB2-100 E1
Adder
4.042352941176473.436
918512AA1-065 E OP
Adder
7.6023529411764716.462
940642AE2-051 E
50/50
19.82119.821
966621AG1-532 C
Adder
1.94000000000000021.649
918532AA1-067 E
Adder
0.96823529411764710.823
924022AB2-043 E O1
Adder
6.95.865
3147223TWITTYS
Adder
1.21764705882352931.035
959312AF2-222 E
Adder
14.06705882352941311.957
934576AD1-082 E
Adder
5.4388235294117654.623
916191Z1-068 C
50/50
0.0610.061
933292AC2-141 E
50/50
18.61818.618
316294AC1-161 C
50/50
7.1277.127
944602AF1-125 E
50/50
144.526144.526
3145506HICKORY
50/50
3.0783.078
943612AF1-032 E
Adder
1.28470588235294141.092
957871AF2-081 C
50/50
14.0814.08
940492AE2-034 E
Adder
4.2752941176470593.634
934522AD1-076 E
Adder
8.6200000000000017.327
943172AE2-346 E
Adder
0.8317647058823530.707
918492AA1-063AE OP
Adder
5.6035294117647064.763
962571AG1-106 C
Adder
3.73764705882352953.177
917332KELFORD E
Adder
2.25058823529411761.913
925122AB2-169 E
Adder
7.8694117647058836.689
316274AC1-208 C
Adder
12.25411764705882510.416
917342Z2-044 E
Adder
0.80352941176470590.683
937482AD2-202 E
50/50
1.5171.517
3151311EDGECMA
Adder
20.7705882352941217.655
316185AD1-033 C
50/50
1.7361.736
944581AF1-123 C
50/50
64.12164.121
941101AE2-104 C
Adder
4.5952941176470593.906
316141AB2-099 E
Adder
0.347058823529411750.295
316088AB2-174 E
Adder
8.997647058823537.648
923994AB2-040_E
Adder
8.487.208
957481AF2-042 C
50/50
79.94679.946
961672AG1-007 E
Adder
0.71529411764705890.608
924322AB2-079 E O1
Adder
1.77764705882352941.511
943902AF1-058 E
Adder
1.65647058823529411.408
316349AD2-085 C
Adder
4.5341176470588243.854
935112AD1-144 E
Adder
1.2588235294117651.07
3151091ELIZAR2
50/50
4.3864.386
944582AF1-123 E
50/50
146.831146.831
944592AF1-124 E
50/50
147.363147.363
923832AB2-022 E
Adder
1.74000000000000021.479
938772AE1-103 E
Adder
5.5529411764705884.72
916042Z1-036 E
Adder
39.78705882352941433.819
960082AF2-299 E
Adder
1.7247058823529411.466
946281AF1-292 C
Adder
2.14117647058823521.82
926071AC1-086 C
Adder
28.90117647058823624.566
3151051BRUNSWICKS1
50/50
28.75928.759
963042AG1-153 E
50/50
14.06814.068
927021AC1-189 C
Adder
11.3505882352941179.648
3151531CLOVER1
50/50
18.24618.246
964241AG1-285 C
Adder
17.3105882352941214.714
924152AB2-059 E OP
Adder
7.0658823529411776.006
962561AG1-105 C
Adder
11.6047058823529429.864
3151101ELIZAR3
50/50
4.5194.519
316315AB2-025 C
50/50
0.5820.582
946282AF1-292 E
Adder
1.4270588235294121.213
944012AF1-069 E
50/50
8.6848.684
957861AF2-080 C
Adder
10.3094117647058838.763
917512Z2-088 E OP1
Adder
6.5941176470588245.605
939191AE1-149 C
Adder
12.63647058823529410.741
3143316POE
Adder
1.67647058823529421.425
901082W1-029 E
Adder
44.4776470588235337.806
926206AC1-098 E
Adder
4.9670588235294124.222
3151041BRUNSWICKG3
50/50
13.84313.843
3151021BRUNSWICKG1
50/50
13.84313.843
964791AG1-342 C
Adder
4.6105882352941173.919
926662AC1-147 E
Adder
1.84117647058823521.565
916192Z1-068 E
50/50
2.6352.635
957492AF2-043 E
Adder
1.97647058823529421.68
923852AB2-025 E
50/50
1.6571.657
939412AE1-173 E
50/50
99.43599.435
961942AG1-037 E
Adder
0.462352941176470630.393
961941AG1-037 C
Adder
0.69294117647058820.589
941032AE2-094 E
50/50
30.64130.641
941031AE2-094 C
50/50
68.41468.414
934332AD1-057 E
Adder
2.46235294117647062.093
934331AD1-057 C
Adder
4.72941176470588154.02
934321AD1-056 C
Adder
8.477647058823537.206
934322AD1-056 E
Adder
4.59882352941176453.909
927022AC1-189 E
Adder
5.6541176470588244.806
925595AC1-034 E
Adder
6.702352941176475.697
936262AD2-033 E
Adder
10.6635294117647069.064
936666AD2-085 E
Adder
7.397647058823536.288
941591AE2-156 C
50/50
24.9124.91
3151081ELIZAR1
50/50
4.4634.463
316316AC1-027 C
50/50
0.4430.443
944591AF1-124 C
50/50
64.34964.349
944601AF1-125 C
50/50
63.13463.134
938771AE1-103 C
Adder
4.0211764705882363.418
3145413WATKINS
Adder
0.94941176470588240.807
960081AF2-299 C
Adder
2.58705882352941162.199
926072AC1-086 E
Adder
13.15411764705882411.181
944011AF1-069 C
50/50
22.35322.353
963041AG1-153 C
50/50
9.3799.379
957862AF2-080 E
Adder
4.5705882352941173.885
3151541CLOVER2
50/50
18.07618.076
936261AD2-033 C
Adder
15.9952941176470613.596
962562AG1-105 E
Adder
7.7364705882352946.576
961611AG1-000B C
Adder
18.02352941176470615.32
316375AC2-012 C
50/50
1.8781.878
940541AE2-040 C
50/50
4.0974.097
940481AE2-033 C
50/50
23.03323.033
940482AE2-033 E
50/50
15.52815.528
923263AB1-132 E OP
Adder
8.4105882352941177.149
3152441Z1-086 ST
50/50
31.00731.007
3152431Z1-086 GT3
50/50
17.80517.805
3152421Z1-086 GT2
50/50
17.80517.805
925612AC1-036 E
Adder
1.09882352941176480.934
924312AB2-078 E O1
Adder
1.77764705882352941.511
926274AC1-105 E
Adder
3.4682352941176472.948
943461AF1-017 C
Adder
1.77764705882352941.511
932596AC2-079 E
Adder
12.38941176470588310.531
316311AC2-079 C
Adder
7.5929411764705886.454
938532AE1-072 E
50/50
12.89612.896
3146326AYDLETT TAP
50/50
1.9081.908
917122Z2-027 E
Adder
1.88117647058823521.599
920692AA2-178 E
Adder
5.74.845
966622AG1-532 E
Adder
1.29294117647058831.099
922923AB1-081 E OP
Adder
4.9882352941176474.24
3150921YORKTN3
Adder
46.1517647058823539.229
3145256KINGFORK
Adder
1.35529411764705881.152
925522AC1-027 E
50/50
1.7051.705
933291AC2-141 C
50/50
43.61643.616
926755AC1-161 E
50/50
18.61818.618
941102AE2-104 E
Adder
7.3058823529411766.21
957872AF2-081 E
50/50
6.0346.034
962572AG1-106 E
Adder
1.63529411764705881.39
926214AC1-099 E
Adder
1.64117647058823551.395
932632AC2-084 E
Adder
4.3905882352941183.732
964242AG1-285 E
Adder
11.549.809
924162AB2-060 E OP
Adder
5.6588235294117644.81
964792AG1-342 E
Adder
3.07411764705882362.613
939192AE1-149 E
Adder
8.424705882352947.161
939312AE1-162 E
Adder
1.79058823529411781.522
934065AD1-033 E
50/50
7.0817.081
937226AE2-253 E
50/50
8.2398.239
934501AD1-074 C
Adder
46.5682352941176539.583
924517AB2-100 E2
Adder
4.042352941176473.436
957482AF2-042 E
50/50
53.29753.297
961671AG1-007 C
Adder
1.26235294117647071.073
934621AD1-088 C
Adder
13.31176470588235211.315
935172AD1-152 E
Adder
7.6094117647058826.468
942342AE2-247 E
Adder
2.71411764705882372.307
919152AA1-139 E1
50/50
5.7585.758
316018AA1-139 ULT2
50/50
1.5241.524
920042AA2-088 E OP
Adder
14.57411764705882412.388
934521AD1-076 C
Adder
16.9129411764705914.376
934511AD1-075 C
Adder
11.6423529411764739.896
3145723EMPORIA
Adder
0.59647058823529410.507
923573AB1-173 E OP
Adder
4.5223529411764713.844
919692AA2-053 E OP
Adder
5.797647058823534.928
925785AC1-054 E
Adder
4.65176470588235353.954
316263AC1-034 C
Adder
8.8847058823529417.552
959311AF2-222 C
Adder
20.9952941176470617.846
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.99436.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.67827.678
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.7584.758
LAGNLTFEXP_LAGN->PJM
CLTF
9.6549.654
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.3487.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
126.03126.03
CPLELTFEXP_CPLE->PJM
CLTF
15.41515.415
TVALTFEXP_TVA->PJM
CLTF
7.567.56
O66PJM->LTFIMP_O-066
CMTX_NF
30.16830.168
G-007PJM->LTFIMP_G-007
CMTX_NF
4.7394.739
SIGELTFEXP_SIGE->PJM
CLTF
0.2910.291
NYPJM->LTFIMP_NY
CLTF
2.22.2
LGEELTFEXP_LGEE->PJM
CLTF
1.4681.468
WECLTFEXP_WEC->PJM
CLTF
0.7690.769

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T567_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.44 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4075.55
MW Contribution:5.6
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316349AD2-085 C
Adder
4.8305882352941174.106
935112AD1-144 E
Adder
1.3835294117647061.176
3151091ELIZAR2
50/50
4.8964.896
944582AF1-123 E
50/50
164.574164.574
944592AF1-124 E
50/50
165.171165.171
923832AB2-022 E
Adder
1.93411764705882351.644
938772AE1-103 E
Adder
6.0094117647058825.108
916042Z1-036 E
Adder
43.71058823529412537.154
960082AF2-299 E
Adder
1.78117647058823541.514
946281AF1-292 C
Adder
2.21058823529411751.879
926071AC1-086 C
Adder
30.1129411764705925.596
3151051BRUNSWICKS1
50/50
30.06830.068
963042AG1-153 E
50/50
14.70814.708
927021AC1-189 C
Adder
11.97411764705882410.178
964241AG1-285 C
Adder
17.77647058823529515.11
924152AB2-059 E OP
Adder
7.3811764705882366.274
962561AG1-105 C
Adder
11.92235294117647210.134
961611AG1-000B C
Adder
5.04.25
3152331SURRY 2
50/50
39.09439.094
932046AC2-012 E
50/50
20.31420.314
958161AF2-110 C
Adder
2.0517647058823531.744
316017AA1-139 ULT1
50/50
1.7031.703
938531AE1-072 C
50/50
27.61527.615
3145393UNCAMP
Adder
9.017647058823537.665
933981AD1-022 C
Adder
13.06588235294117711.106
900672V4-068 E
Adder
0.52235294117647060.444
3152411Z1-086 GT1
50/50
18.63118.631
924302AB2-077 E O1
Adder
1.82588235294117651.552
3150921YORKTN3
Adder
148.4764705882353126.205
943461AF1-017 C
Adder
1.89411764705882371.61
932596AC2-079 E
Adder
13.2447058823529411.258
316311AC2-079 C
Adder
8.117647058823536.9
938532AE1-072 E
50/50
14.39614.396
3146326AYDLETT TAP
50/50
2.1292.129
917122Z2-027 E
Adder
2.08705882352941161.774
920692AA2-178 E
Adder
6.2129411764705885.281
966622AG1-532 E
Adder
1.3352941176470591.135
922923AB1-081 E OP
Adder
5.2094117647058834.428
942342AE2-247 E
Adder
2.89058823529411772.457
919152AA1-139 E1
50/50
6.4346.434
316018AA1-139 ULT2
50/50
1.7031.703
920042AA2-088 E OP
Adder
15.5623529411764713.228
934521AD1-076 C
Adder
18.32705882352941315.578
934511AD1-075 C
Adder
12.6152941176470610.723
3145723EMPORIA
Adder
0.61647058823529410.524
923573AB1-173 E OP
Adder
4.6976470588235293.993
919692AA2-053 E OP
Adder
6.08588235294117655.173
925785AC1-054 E
Adder
4.8317647058823534.107
316263AC1-034 C
Adder
9.287.888
959311AF2-222 C
Adder
21.34470588235294418.143
316084AB2-161 E
Adder
6.937647058823535.897
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
933982AD1-022 E
Adder
7.11294117647058856.046
940641AE2-051 C
50/50
31.61831.618
927146AC1-208 E
Adder
5.7070588235294124.851
934622AD1-088 E
Adder
6.6058823529411775.615
934612AD1-087 E
Adder
5.3611764705882364.557
913392Y1-086 E
Adder
3.42705882352941152.913
939411AE1-173 C
50/50
160.299160.299
3137643SOCKMAN
Adder
1.02117647058823540.868
3151031BRUNSWICKG2
50/50
14.47314.473
919710AA2-057 E
Adder
5.6082352941176474.767
316375AC2-012 C
50/50
2.0942.094
940541AE2-040 C
Adder
4.16470588235294153.54
940481AE2-033 C
Adder
23.45176470588235419.934
940482AE2-033 E
Adder
15.81058823529411813.439
923263AB1-132 E OP
Adder
8.7635294117647067.449
3152441Z1-086 ST
50/50
32.43232.432
3152431Z1-086 GT3
50/50
18.62318.623
3152421Z1-086 GT2
50/50
18.62318.623
925612AC1-036 E
Adder
1.11882352941176480.951
924312AB2-078 E O1
Adder
1.82588235294117651.552
926274AC1-105 E
Adder
3.5647058823529413.03
3145256KINGFORK
Adder
1.49058823529411751.267
925522AC1-027 E
50/50
1.9061.906
933291AC2-141 C
50/50
50.29350.293
926755AC1-161 E
50/50
21.46921.469
941102AE2-104 E
Adder
7.99294117647058756.794
957872AF2-081 E
50/50
6.7436.743
962572AG1-106 E
Adder
1.7035294117647061.448
926214AC1-099 E
Adder
1.72705882352941181.468
932632AC2-084 E
Adder
4.623.927
964242AG1-285 E
Adder
11.85176470588235310.074
924162AB2-060 E OP
Adder
5.8058823529411764.935
964792AG1-342 E
Adder
3.1588235294117652.685
934576AD1-082 E
Adder
5.5282352941176474.699
916191Z1-068 C
50/50
0.0690.069
933292AC2-141 E
50/50
21.46921.469
316294AC1-161 C
50/50
8.2198.219
944602AF1-125 E
50/50
161.991161.991
3145506HICKORY
50/50
3.4483.448
943612AF1-032 E
Adder
1.42235294117647081.209
957871AF2-081 C
50/50
15.73315.733
940492AE2-034 E
Adder
4.663.961
934522AD1-076 E
Adder
9.3411764705882367.94
943172AE2-346 E
Adder
0.88823529411764710.755
918492AA1-063AE OP
Adder
5.9070588235294125.021
962571AG1-106 C
Adder
3.8952941176470593.311
917332KELFORD E
Adder
2.39058823529411772.032
925122AB2-169 E
Adder
8.4411764705882367.175
316274AC1-208 C
Adder
12.85294117647058910.925
917342Z2-044 E
Adder
0.84117647058823530.715
937482AD2-202 E
Adder
1.56941176470588251.334
3151311EDGECMA
Adder
21.6952941176470618.441
942341AE2-247 C
Adder
2.09411764705882361.78
943462AF1-017 E
Adder
3.09058823529411742.627
958162AF2-110 E
Adder
3.2635294117647062.774
316388AE2-253 GEN
50/50
3.0993.099
919153AA1-139 E2
50/50
6.4346.434
934512AD1-075 E
Adder
6.422352941176475.459
934502AD1-074 E
Adder
25.6882352941176521.835
924516AB2-100 E1
Adder
4.1635294117647063.539
918512AA1-065 E OP
Adder
8.1494117647058816.927
940642AE2-051 E
50/50
21.07921.079
966621AG1-532 C
Adder
2.00352941176470621.703
918532AA1-067 E
Adder
1.02588235294117650.872
924022AB2-043 E O1
Adder
7.0847058823529416.022
3147223TWITTYS
Adder
1.241.054
959312AF2-222 E
Adder
14.30117647058823712.156
316185AD1-033 C
50/50
1.9451.945
944581AF1-123 C
50/50
71.8771.87
941101AE2-104 C
Adder
5.0270588235294114.273
316141AB2-099 E
Adder
0.36941176470588240.314
316088AB2-174 E
Adder
9.3282352941176477.929
923994AB2-040_E
Adder
8.8082352941176477.487
957481AF2-042 C
Adder
82.8776470588235370.446
961672AG1-007 E
Adder
0.7517647058823530.639
924322AB2-079 E O1
Adder
1.82588235294117651.552
943902AF1-058 E
Adder
1.70235294117647061.447
936666AD2-085 E
Adder
7.8811764705882356.699
941591AE2-156 C
50/50
27.78727.787
3151081ELIZAR1
50/50
4.9824.982
316316AC1-027 C
50/50
0.4950.495
944591AF1-124 C
50/50
72.12672.126
944601AF1-125 C
50/50
70.76370.763
938771AE1-103 C
Adder
4.3517647058823533.699
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.6705882352941182.27
926072AC1-086 E
Adder
13.70588235294117811.65
944011AF1-069 C
50/50
23.40523.405
963041AG1-153 C
50/50
9.8059.805
957862AF2-080 E
Adder
4.8211764705882354.098
962562AG1-105 E
Adder
7.9482352941176486.756
3151101ELIZAR3
50/50
5.0455.045
946282AF1-292 E
Adder
1.47411764705882351.253
944012AF1-069 E
50/50
9.0929.092
957861AF2-080 C
Adder
10.8752941176470599.244
917512Z2-088 E OP1
Adder
6.9388235294117645.898
926662AC1-147 E
Adder
2.05411764705882361.746
916192Z1-068 E
50/50
2.9452.945
957492AF2-043 E
Adder
2.18823529411764731.86
923852AB2-025 E
Adder
1.6847058823529411.432
939412AE1-173 E
50/50
106.866106.866
961942AG1-037 E
Adder
0.49294117647058820.419
961941AG1-037 C
Adder
0.740.629
941032AE2-094 E
50/50
32.08232.082
941031AE2-094 C
50/50
71.63171.631
934332AD1-057 E
Adder
2.56941176470588272.184
934331AD1-057 C
Adder
4.9341176470588244.194
934321AD1-056 C
Adder
8.844705882352947.518
934322AD1-056 E
Adder
4.797647058823534.078
927022AC1-189 E
Adder
5.9647058823529415.07
925595AC1-034 E
Adder
7.0011764705882355.951
3143316POE
Adder
1.61411764705882371.372
901082W1-029 E
Adder
49.1811764705882441.804
926206AC1-098 E
Adder
5.2270588235294114.443
3151041BRUNSWICKG3
50/50
14.47314.473
3151021BRUNSWICKG1
50/50
14.47314.473
964791AG1-342 C
Adder
4.737647058823534.027
939312AE1-162 E
Adder
1.93058823529411771.641
3150991CHESPKB
50/50
1.121.12
934065AD1-033 E
50/50
7.9347.934
937226AE2-253 E
50/50
9.2149.214
934501AD1-074 C
Adder
50.4623529411764742.893
924517AB2-100 E2
Adder
4.1635294117647063.539
957482AF2-042 E
Adder
55.2517647058823546.964
961671AG1-007 C
Adder
1.32588235294117651.127
934621AD1-088 C
Adder
13.7211.662
935172AD1-152 E
Adder
7.8611764705882366.682
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.34332.343
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.24226.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.3444.344
LAGNLTFEXP_LAGN->PJM
CLTF
9.3599.359
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.5637.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
128.067128.067
CPLELTFEXP_CPLE->PJM
CLTF
15.87115.871
TVALTFEXP_TVA->PJM
CLTF
7.2977.297
O66PJM->LTFIMP_O-066
CMTX_NF
27.12727.127
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2584.258
SIGELTFEXP_SIGE->PJM
CLTF
0.2610.261
NYPJM->LTFIMP_NY
CLTF
2.0052.005
LGEELTFEXP_LGEE->PJM
CLTF
1.2871.287
WECLTFEXP_WEC->PJM
CLTF
0.6770.677

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.39 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1062.25
MW Contribution:1.17
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.68 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1086.53
MW Contribution:1.12
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
80/20
11.53811.538
316336AC2-165 C
Adder
-10.758823529411764-9.145
934611AD1-087 C
80/20
0.6230.623
3151611KERR 4
80/20
0.4940.494
958161AF2-110 C
Adder
0.53058823529411770.451
316017AA1-139 ULT1
80/20
0.4540.454
938531AE1-072 C
80/20
7.3717.371
315614AA2-178 C
80/20
0.6580.658
933981AD1-022 C
80/20
3.6993.699
3151261ROARAP2
80/20
0.5930.593
3147043LAWRENC
80/20
0.130.13
3152411Z1-086 GT1
80/20
7.0067.006
3151621KERR 5
80/20
0.4940.494
3156116Z1-036WIND
80/20
0.2750.275
939411AE1-173 C
80/20
55.12655.126
3152921DOMTR78
80/20
0.5790.579
316140AB2-099 C
80/20
0.0410.041
3137643SOCKMAN
80/20
0.3050.305
316212AC1-099 C
80/20
0.1360.136
3151031BRUNSWICKG2
80/20
5.4215.421
937481AD2-202 C
80/20
0.1810.181
3151641KERR 7
80/20
0.4940.494
916191Z1-068 C
80/20
0.0180.018
316294AC1-161 C
80/20
2.1972.197
957871AF2-081 C
80/20
4.1964.196
962571AG1-106 C
80/20
1.1691.169
932631AC2-084 C
80/20
0.4330.433
316274AC1-208 C
80/20
3.8963.896
3151311EDGECMA
Adder
6.8129411764705895.791
3151601KERR 3
80/20
0.4940.494
3151581KERR 1
80/20
0.1760.176
941011AE2-092 C
Adder
-4.452941176470588-3.785
942341AE2-247 C
Adder
0.50235294117647060.427
316246AF1-032 C
80/20
0.1150.115
316388AE2-253 GEN
80/20
0.8260.826
966621AG1-532 C
80/20
0.6010.601
936161AD2-022 C
Adder
3.0882352941176472.625
3150981CHESPKA
80/20
0.1750.175
316185AD1-033 C
80/20
0.5160.516
944581AF1-123 C
80/20
19.1219.12
941101AE2-104 C
Adder
1.31.105
316320Y1-086 C
80/20
0.0920.092
3156083AA2-088SOLA
80/20
0.4390.439
313506AB1-173 C OP
80/20
0.4830.483
3151361ROSEMG1
80/20
0.8780.878
957481AF2-042 C
80/20
28.34128.341
316349AD2-085 C
Adder
1.15882352941176480.985
3151091ELIZAR2
80/20
1.2731.273
316023AB2-100 C2
80/20
0.4150.415
946281AF1-292 C
80/20
0.6630.663
926071AC1-086 C
80/20
9.0389.038
316317KELFORD C
80/20
0.1530.153
3151051BRUNSWICKS1
80/20
11.26211.262
927021AC1-189 C
Adder
3.66117647058823573.112
3151531CLOVER1
80/20
6.3346.334
964241AG1-285 C
80/20
5.3655.365
962561AG1-105 C
Adder
3.70941176470588243.153
3151101ELIZAR3
80/20
1.3121.312
316315AB2-025 C
80/20
0.1780.178
316129AC1-054 C
80/20
0.5240.524
957861AF2-080 C
Adder
3.3247058823529412.826
316365AB2-100 C1
80/20
0.4150.415
316318V4-068 C
80/20
0.0340.034
316210AC1-098 C
80/20
0.4070.407
3151041BRUNSWICKG3
80/20
5.4215.421
3151021BRUNSWICKG1
80/20
5.4215.421
935171AD1-152 C
80/20
0.6380.638
964791AG1-342 C
Adder
1.48470588235294131.262
943171AE2-346 C
80/20
0.0950.095
961941AG1-037 C
80/20
0.2130.213
3151391GASTONA
80/20
1.3141.314
3151381ROSEMG2
80/20
0.4110.411
941031AE2-094 C
80/20
27.16527.165
934331AD1-057 C
Adder
1.52117647058823541.293
934321AD1-056 C
Adder
2.72588235294117662.317
941591AE2-156 C
80/20
7.2027.202
3151081ELIZAR1
80/20
1.2951.295
316316AC1-027 C
80/20
0.130.13
944591AF1-124 C
80/20
19.18819.188
944601AF1-125 C
80/20
18.82618.826
938771AE1-103 C
Adder
1.16941176470588240.994
960081AF2-299 C
80/20
0.8010.801
944011AF1-069 C
80/20
8.8768.876
963041AG1-153 C
80/20
3.6733.673
3151541CLOVER2
80/20
6.2756.275
3151631KERR 6
80/20
0.4940.494
936261AD2-033 C
Adder
4.2364705882352943.601
936171AD2-023 C
Adder
1.80117647058823521.531
316375AC2-012 C
80/20
0.5420.542
313526AB2-022 C
80/20
0.1570.157
940541AE2-040 C
80/20
1.2541.254
940481AE2-033 C
80/20
7.0627.062
3151411GASTONB
80/20
1.3141.314
316181AB2-040 GEN
80/20
0.5450.545
316174AB2-169_C
80/20
0.4470.447
3156063AA2-053SOLA
80/20
0.6450.645
3151281ROARAP4
80/20
0.5610.561
3152441Z1-086 ST
80/20
12.19612.196
3152431Z1-086 GT3
80/20
7.0037.003
3152421Z1-086 GT2
80/20
7.0037.003
938821AE1-108 C
Adder
-4.716470588235294-4.009
943461AF1-017 C
Adder
0.454117647058823570.386
316311AC2-079 C
Adder
1.9682352941176471.673
3156056W1-029WIND
80/20
0.3220.322
933291AC2-141 C
80/20
13.44213.442
316305AF2-043 C
80/20
0.1410.141
316087AB2-174 C
80/20
0.5050.505
3151591KERR 2
80/20
0.4940.494
3150991CHESPKB
80/20
0.290.29
316321Z2-027 C
80/20
0.1520.152
940491AE2-034 C
80/20
0.4850.485
934501AD1-074 C
80/20
14.21814.218
3156021HOLLOMANSOL
80/20
0.7790.779
3156073AA1-063SOLA
80/20
0.5950.595
3151371ROSEMS1
80/20
0.5440.544
961671AG1-007 C
Adder
0.410588235294117640.349
934621AD1-088 C
80/20
4.3624.362
316036AC1-147 C
80/20
0.1480.148
316018AA1-139 ULT2
80/20
0.4540.454
934521AD1-076 C
80/20
5.1645.164
934511AD1-075 C
80/20
3.5543.554
316011AB1-132 C OP
80/20
1.0031.003
316263AC1-034 C
Adder
2.91411764705882352.477
959311AF2-222 C
Adder
5.57411764705882454.738
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091
NYPJM->LTFIMP_NY
CLTF
0.5140.514
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
WECLTFEXP_WEC->PJM
CLTF
0.2390.239

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.98 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4293.98
MW Contribution:4.13
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150731STONECA
Adder
10.1976470588235298.668
935161AD1-151 C
Adder
24.22470588235294320.591
932046AC2-012 E
50/50
20.89320.893
958161AF2-110 C
Adder
2.16823529411764731.843
938531AE1-072 C
Adder
27.99411764705882523.795
3145393UNCAMP
Adder
9.5200000000000018.092
933981AD1-022 C
Adder
13.5152941176470611.488
900672V4-068 E
Adder
0.54941176470588240.467
3152411Z1-086 GT1
50/50
17.32817.328
316084AB2-161 E
Adder
8.717647058823537.41
3145946PLYMOUTH TP
Adder
0.50.425
933982AD1-022 E
Adder
7.3576470588235296.254
940641AE2-051 C
50/50
29.19229.192
316336AC2-165 C
Adder
14.85411764705882312.626
934622AD1-088 E
Adder
6.9164705882352945.879
934612AD1-087 E
Adder
5.42823529411764754.614
940432AE2-027 E
Adder
13.04588235294117711.089
934012AD1-025 E
Adder
15.07294117647058812.812
913392Y1-086 E
Adder
3.48941176470588272.966
939411AE1-173 C
50/50
151.032151.032
933502AC2-165 E
Adder
11.189.503
3151031BRUNSWICKG2
50/50
13.50613.506
3150651CHESTF6
Adder
27.96823529411764823.773
946262AF1-291 E
Adder
2.17647058823529441.85
942341AE2-247 C
Adder
2.362.006
943462AF1-017 E
Adder
3.48470588235294132.962
958162AF2-110 E
Adder
3.4494117647058822.932
919153AA1-139 E2
Adder
6.5152941176470595.538
934512AD1-075 E
Adder
6.6317647058823535.637
934502AD1-074 E
Adder
26.5247058823529422.546
924516AB2-100 E1
Adder
4.4917647058823533.818
940642AE2-051 E
50/50
19.46119.461
966621AG1-532 C
Adder
2.15411764705882371.831
934576AD1-082 E
Adder
6.9458823529411775.904
916191Z1-068 C
50/50
0.070.07
933292AC2-141 E
50/50
20.7620.76
316294AC1-161 C
50/50
7.9477.947
944602AF1-125 E
50/50
163.5163.5
3145506HICKORY
50/50
3.4833.483
943612AF1-032 E
Adder
1.4682352941176471.248
957871AF2-081 C
Adder
15.93294117647058713.543
940492AE2-034 E
Adder
4.84.08
934522AD1-076 E
Adder
9.6458823529411778.199
918492AA1-063AE OP
Adder
6.2388235294117655.303
962571AG1-106 C
Adder
3.9470588235294123.355
937482AD2-202 E
Adder
1.58941176470588231.351
940431AE2-027 C
Adder
19.56823529411764516.633
942002AE2-212 E
Adder
2.23058823529411751.896
316185AD1-033 C
50/50
1.9651.965
944581AF1-123 C
50/50
72.53972.539
941101AE2-104 C
Adder
5.3141176470588244.517
316088AB2-174 E
Adder
9.988.483
923994AB2-040_E
Adder
9.4011764705882357.991
957481AF2-042 C
Adder
82.7976470588235370.378
316349AD2-085 C
Adder
5.4458823529411764.629
935112AD1-144 E
Adder
1.48117647058823531.259
3151091ELIZAR2
50/50
5.0195.019
944582AF1-123 E
50/50
166.107166.107
944592AF1-124 E
50/50
166.709166.709
923832AB2-022 E
Adder
1.96941176470588241.674
938772AE1-103 E
Adder
6.3458823529411775.394
916042Z1-036 E
Adder
44.8811764705882438.149
960082AF2-299 E
Adder
1.91529411764705881.628
946281AF1-292 C
Adder
2.37764705882352922.021
926071AC1-086 C
Adder
31.96588235294117627.171
3151051BRUNSWICKS1
50/50
28.05828.058
963042AG1-153 E
50/50
13.72513.725
3151101ELIZAR3
50/50
5.1725.172
316315AB2-025 C
50/50
0.650.65
946282AF1-292 E
Adder
1.58588235294117651.348
944012AF1-069 E
50/50
8.3958.395
939191AE1-149 C
Adder
16.88000000000000314.348
3143316POE
50/50
2.1752.175
901082W1-029 E
Adder
50.41764705882352642.855
3151041BRUNSWICKG3
50/50
13.50613.506
3151021BRUNSWICKG1
50/50
13.50613.506
3150841SPRUNCB
Adder
14.05529411764705811.947
3150831SPRUNCA
Adder
14.05529411764705811.947
926662AC1-147 E
Adder
2.1117647058823531.795
916192Z1-068 E
50/50
3.0013.001
957492AF2-043 E
Adder
2.25882352941176471.92
923852AB2-025 E
50/50
1.8511.851
939412AE1-173 E
50/50
100.688100.688
923862AB2-026 E
Adder
1.9247058823529411.636
941032AE2-094 E
50/50
29.62229.622
941031AE2-094 C
50/50
66.13866.138
925332AB2-190 E
Adder
12.07529411764705810.264
927226AC1-216 E
Adder
11.6423529411764739.896
936666AD2-085 E
Adder
8.8858823529411777.553
941591AE2-156 C
50/50
28.55328.553
3151081ELIZAR1
50/50
5.1085.108
316316AC1-027 C
50/50
0.5040.504
944591AF1-124 C
50/50
72.79772.797
944601AF1-125 C
50/50
71.42271.422
938771AE1-103 C
Adder
4.5952941176470593.906
3145413WATKINS
Adder
1.07882352941176470.917
960081AF2-299 C
Adder
2.87294117647058832.442
926072AC1-086 E
Adder
14.54823529411764812.366
944011AF1-069 C
50/50
21.6121.61
963041AG1-153 C
50/50
9.159.15
961611AG1-000B C
Adder
24.2858823529411820.643
316375AC2-012 C
50/50
2.1542.154
940541AE2-040 C
50/50
4.5764.576
940481AE2-033 C
50/50
25.70925.709
940482AE2-033 E
50/50
17.33217.332
923263AB1-132 E OP
Adder
9.3023529411764717.907
3152441Z1-086 ST
50/50
30.16330.163
3152431Z1-086 GT3
50/50
17.32117.321
3152421Z1-086 GT2
50/50
17.32117.321
935162AD1-151 E
Adder
16.1505882352941213.728
316233AE1-074 C
50/50
4.1784.178
943461AF1-017 C
Adder
2.1352941176470591.815
932596AC2-079 E
Adder
14.80823529411764712.587
316311AC2-079 C
Adder
9.0764705882352947.715
938532AE1-072 E
Adder
14.59294117647058912.404
3146326AYDLETT TAP
Adder
2.161.836
917122Z2-027 E
Adder
2.12941176470588231.81
920692AA2-178 E
Adder
6.45.44
966622AG1-532 E
Adder
1.43647058823529421.221
938552AE1-074 E
50/50
2.1052.105
3150921YORKTN3
Adder
175.7670588235294149.402
3145256KINGFORK
Adder
1.5952941176470591.356
925522AC1-027 E
50/50
1.9431.943
933291AC2-141 C
50/50
48.63248.632
926755AC1-161 E
50/50
20.7620.76
941102AE2-104 E
Adder
8.4494117647058827.182
957872AF2-081 E
Adder
6.8282352941176485.804
938562AE1-075 E
Adder
1.64117647058823551.395
942001AE2-212 C
Adder
3.34588235294117632.844
939192AE1-149 E
Adder
11.2529411764705879.565
939312AE1-162 E
Adder
2.22705882352941181.893
934065AD1-033 E
50/50
8.0198.019
937226AE2-253 E
Adder
9.322352941176477.924
934501AD1-074 C
Adder
52.1070588235294144.291
958502AF2-144 E
Adder
1.89058823529411771.607
924517AB2-100 E2
Adder
4.4917647058823533.818
957482AF2-042 E
Adder
55.1988235294117646.919
934621AD1-088 C
Adder
14.36470588235294312.21
944641AF1-129 C
Adder
153.60588235294117130.565
316240AF1-291 C
Adder
3.2635294117647062.774
924814AB2-134 E
Adder
19.07058823529411716.21
942342AE2-247 E
Adder
3.262.771
919152AA1-139 E1
Adder
6.5152941176470595.538
920042AA2-088 E OP
Adder
16.40941176470588313.948
934521AD1-076 C
Adder
18.92352941176470816.085
934511AD1-075 C
Adder
13.02705882352941211.073
3145723EMPORIA
Adder
0.66117647058823540.562
923573AB1-173 E OP
Adder
5.0141176470588234.262
316303AF2-085
50/50
6.8996.899
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.00241.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.98729.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.2215.221
LAGNLTFEXP_LAGN->PJM
CLTF
10.36610.366
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6737.673
CBM South 2LTFEXP_CBM-S2->PJM
CBM
132.286132.286
CPLELTFEXP_CPLE->PJM
CLTF
16.09616.096
TVALTFEXP_TVA->PJM
CLTF
8.1488.148
O66PJM->LTFIMP_O-066
CMTX_NF
37.46537.465
G-007PJM->LTFIMP_G-007
CMTX_NF
5.8875.887
SIGELTFEXP_SIGE->PJM
CLTF
0.3220.322
NYPJM->LTFIMP_NY
CLTF
2.7212.721
LGEELTFEXP_LGEE->PJM
CLTF
1.6421.642
WECLTFEXP_WEC->PJM
CLTF
0.8540.854

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.85 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4130.98
MW Contribution:5.85
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.17 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4734.56
MW Contribution:6.05
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942001AE2-212 C
Adder
3.1211764705882352.653
939192AE1-149 E
Adder
10.7800000000000019.163
939312AE1-162 E
Adder
2.21058823529411751.879
934065AD1-033 E
50/50
8.0978.097
937226AE2-253 E
50/50
9.4079.407
934501AD1-074 C
Adder
52.03294117647059444.228
958502AF2-144 E
Adder
1.76470588235294111.5
924517AB2-100 E2
Adder
4.4035294117647063.743
957482AF2-042 E
Adder
54.5552941176470646.372
934621AD1-088 C
Adder
14.14588235294117512.024
3150841SPRUNCB
Adder
12.67882352941176410.777
3150831SPRUNCA
Adder
12.67882352941176410.777
926662AC1-147 E
Adder
2.12823529411764721.809
916192Z1-068 E
50/50
3.0273.027
957492AF2-043 E
Adder
2.2717647058823531.931
923852AB2-025 E
Adder
1.80470588235294121.534
939412AE1-173 E
50/50
100.92100.92
923862AB2-026 E
Adder
1.7964705882352941.527
961942AG1-037 E
Adder
0.51176470588235290.435
961941AG1-037 C
Adder
0.76823529411764710.653
941032AE2-094 E
50/50
29.48329.483
941031AE2-094 C
50/50
65.82865.828
942341AE2-247 C
Adder
2.33294117647058831.983
943462AF1-017 E
Adder
3.44470588235294132.928
958162AF2-110 E
Adder
3.45058823529411772.933
316388AE2-253 GEN
50/50
3.1643.164
919153AA1-139 E2
Adder
6.57294117647058855.587
934512AD1-075 E
Adder
6.622352941176475.629
934502AD1-074 E
Adder
26.48705882352941322.514
924516AB2-100 E1
Adder
4.4035294117647063.743
918512AA1-065 E OP
Adder
8.4305882352941197.166
940642AE2-051 E
50/50
19.46619.466
966621AG1-532 C
Adder
2.11529411764705881.798
939191AE1-149 C
Adder
16.1694117647058813.744
3143316POE
Adder
2.0705882352941181.76
901082W1-029 E
Adder
50.6800000000000143.078
3151041BRUNSWICKG3
50/50
13.42713.427
3151021BRUNSWICKG1
50/50
13.42713.427
316349AD2-085 C
Adder
5.3835294117647054.576
935112AD1-144 E
Adder
1.48470588235294131.262
3151091ELIZAR2
50/50
5.0595.059
944582AF1-123 E
50/50
167.759167.759
944592AF1-124 E
50/50
168.367168.367
923832AB2-022 E
Adder
1.98352941176470581.686
938772AE1-103 E
Adder
6.3270588235294125.378
916042Z1-036 E
Adder
45.0211764705882438.268
960082AF2-299 E
Adder
1.88000000000000011.598
946281AF1-292 C
Adder
2.33411764705882341.984
926071AC1-086 C
Adder
31.48235294117647226.76
3151051BRUNSWICKS1
50/50
27.89527.895
963042AG1-153 E
50/50
13.64513.645
964241AG1-285 C
Adder
18.8416.014
925332AB2-190 E
Adder
11.5164705882352939.789
927226AC1-216 E
Adder
11.2188235294117659.536
962962AG1-145 E
Adder
2.0305882352941181.726
936666AD2-085 E
Adder
8.7835294117647067.466
941591AE2-156 C
50/50
28.7728.77
940432AE2-027 E
Adder
12.12235294117647110.304
934012AD1-025 E
Adder
14.52470588235294212.346
913392Y1-086 E
Adder
3.51411764705882362.987
946262AF1-291 E
Adder
2.00235294117647071.702
934576AD1-082 E
Adder
6.7411764705882365.73
916191Z1-068 C
50/50
0.0710.071
933292AC2-141 E
50/50
21.18321.183
316294AC1-161 C
50/50
8.1098.109
944602AF1-125 E
50/50
165.126165.126
3145506HICKORY
50/50
3.5173.517
943612AF1-032 E
Adder
1.4764705882352941.255
957871AF2-081 C
Adder
16.07411764705882413.663
940492AE2-034 E
Adder
4.8023529411764714.082
934522AD1-076 E
Adder
9.6317647058823528.187
943172AE2-346 E
Adder
0.92117647058823540.783
918492AA1-063AE OP
Adder
6.1705882352941185.245
962571AG1-106 C
Adder
4.07176470588235253.461
917332KELFORD E
Adder
2.4741176470588242.103
925122AB2-169 E
Adder
8.6764705882352937.375
937482AD2-202 E
Adder
1.5682352941176471.333
940431AE2-027 C
Adder
18.18352941176470615.456
942002AE2-212 E
Adder
2.0811764705882351.769
316185AD1-033 C
50/50
1.9851.985
944581AF1-123 C
50/50
73.26173.261
941101AE2-104 C
Adder
5.3152941176470594.518
316141AB2-099 E
Adder
0.38352941176470590.326
316088AB2-174 E
Adder
9.8129411764705888.341
923994AB2-040_E
Adder
9.2505882352941197.863
957481AF2-042 C
Adder
81.8317647058823669.557
961611AG1-000B C
Adder
23.7620.196
316375AC2-012 C
50/50
2.172.17
940541AE2-040 C
Adder
4.4623529411764713.793
940481AE2-033 C
Adder
25.0882352941176521.325
940482AE2-033 E
Adder
16.9129411764705914.376
923263AB1-132 E OP
Adder
9.162352941176477.788
3152441Z1-086 ST
50/50
29.99929.999
3152431Z1-086 GT3
50/50
17.22617.226
3152421Z1-086 GT2
50/50
17.22617.226
944641AF1-129 C
Adder
128.6564705882353109.358
316240AF1-291 C
Adder
3.0047058823529412.554
924814AB2-134 E
Adder
18.37647058823529315.62
942342AE2-247 E
Adder
3.22235294117647042.739
919152AA1-139 E1
Adder
6.57294117647058855.587
920042AA2-088 E OP
Adder
16.29647058823529413.852
934521AD1-076 C
Adder
18.8976470588235316.063
934511AD1-075 C
Adder
13.00823529411764811.057
3145723EMPORIA
Adder
0.65058823529411770.553
923573AB1-173 E OP
Adder
4.9341176470588244.194
919692AA2-053 E OP
Adder
6.3423529411764715.391
938552AE1-074 E
50/50
1.9361.936
316160AE1-175 E
Adder
1.67529411764705881.424
3150921YORKTN3
Adder
176.88117647058823150.349
3145256KINGFORK
Adder
1.61.36
925522AC1-027 E
50/50
1.961.96
933291AC2-141 C
50/50
49.62549.625
926755AC1-161 E
50/50
21.18321.183
941102AE2-104 E
Adder
8.4505882352941187.183
3151081ELIZAR1
50/50
5.1485.148
316316AC1-027 C
50/50
0.5090.509
944591AF1-124 C
50/50
73.52173.521
944601AF1-125 C
50/50
72.13372.133
938771AE1-103 C
Adder
4.582352941176473.895
3145413WATKINS
Adder
1.07411764705882360.913
960081AF2-299 C
Adder
2.822.397
926072AC1-086 E
Adder
14.32823529411764712.179
944011AF1-069 C
50/50
21.50921.509
963041AG1-153 C
50/50
9.0979.097
3150731STONECA
Adder
9.5694117647058838.134
935161AD1-151 C
Adder
23.2152941176470619.733
932046AC2-012 E
50/50
21.04921.049
958161AF2-110 C
Adder
2.16941176470588241.844
938531AE1-072 C
Adder
28.2329411764705923.998
3145393UNCAMP
Adder
9.4858823529411778.063
933981AD1-022 C
Adder
13.48352941176470711.461
900672V4-068 E
Adder
0.54588235294117650.464
3152411Z1-086 GT1
50/50
17.23317.233
935162AD1-151 E
Adder
15.4776470588235313.156
316233AE1-074 C
50/50
3.8433.843
943461AF1-017 C
Adder
2.1105882352941181.794
932596AC2-079 E
Adder
14.6612.461
316311AC2-079 C
Adder
8.9858823529411777.638
938532AE1-072 E
Adder
14.7176470588235312.51
3146326AYDLETT TAP
Adder
2.17764705882352951.851
917122Z2-027 E
Adder
2.1435294117647061.822
920692AA2-178 E
Adder
6.4035294117647065.443
966622AG1-532 E
Adder
1.41058823529411771.199
957872AF2-081 E
Adder
6.88823529411764755.855
938562AE1-075 E
Adder
1.53176470588235311.302
962572AG1-106 E
Adder
1.78117647058823541.514
964242AG1-285 E
Adder
12.5610.676
316084AB2-161 E
Adder
8.467.191
3145946PLYMOUTH TP
Adder
0.50.425
933982AD1-022 E
Adder
7.346.239
940641AE2-051 C
50/50
29.19929.199
934622AD1-088 E
Adder
6.8105882352941185.789
934612AD1-087 E
Adder
5.3588235294117644.555
939411AE1-173 C
50/50
151.38151.38
3137643SOCKMAN
Adder
1.06823529411764720.908
3151031BRUNSWICKG2
50/50
13.42713.427
3151101ELIZAR3
50/50
5.2135.213
946282AF1-292 E
Adder
1.5564705882352941.323
944012AF1-069 E
50/50
8.3568.356
316303AF2-085
50/50
6.4766.476
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.34537.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.31928.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8474.847
LAGNLTFEXP_LAGN->PJM
CLTF
9.8929.892
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.547.54
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.173129.173
CPLELTFEXP_CPLE->PJM
CLTF
15.81915.819
TVALTFEXP_TVA->PJM
CLTF
7.767.76
O66PJM->LTFIMP_O-066
CMTX_NF
34.77734.777
G-007PJM->LTFIMP_G-007
CMTX_NF
5.4635.463
SIGELTFEXP_SIGE->PJM
CLTF
0.2970.297
NYPJM->LTFIMP_NY
CLTF
2.5392.539
LGEELTFEXP_LGEE->PJM
CLTF
1.4991.499
WECLTFEXP_WEC->PJM
CLTF
0.780.78

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.96 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4056.76
MW Contribution:5.61
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316349AD2-085 C
Adder
5.09882352941176454.334
935112AD1-144 E
Adder
1.3882352941176471.18
3151091ELIZAR2
50/50
4.7134.713
944582AF1-123 E
50/50
156.119156.119
944592AF1-124 E
50/50
156.684156.684
923832AB2-022 E
Adder
1.8517647058823531.574
938772AE1-103 E
Adder
5.9670588235294125.072
916042Z1-036 E
Adder
42.2247058823529435.891
960082AF2-299 E
Adder
1.81058823529411761.539
946281AF1-292 C
Adder
2.24823529411764731.911
926071AC1-086 C
Adder
30.19411764705882525.665
3151051BRUNSWICKS1
50/50
26.83226.832
963042AG1-153 E
50/50
13.12513.125
964241AG1-285 C
Adder
6.4458823529411775.479
935161AD1-151 C
Adder
22.3418.989
932046AC2-012 E
50/50
19.61519.615
958161AF2-110 C
Adder
2.03529411764705871.73
938531AE1-072 C
Adder
26.31411764705882622.367
3145393UNCAMP
Adder
8.9552941176470597.612
933981AD1-022 C
Adder
12.73411764705882410.824
900672V4-068 E
Adder
0.51764705882352950.44
3152411Z1-086 GT1
50/50
16.57316.573
935162AD1-151 E
Adder
14.89411764705882412.66
316233AE1-074 C
50/50
3.8973.897
943461AF1-017 C
Adder
2.01.7
932596AC2-079 E
Adder
13.86941176470588211.789
316311AC2-079 C
Adder
8.5011764705882367.226
938532AE1-072 E
Adder
13.7176470588235311.66
3146326AYDLETT TAP
Adder
2.02941176470588271.725
917122Z2-027 E
Adder
2.00235294117647071.702
920692AA2-178 E
Adder
6.0258823529411775.122
966622AG1-532 E
Adder
1.35764705882352941.154
944641AF1-129 C
Adder
140.53529411764706119.455
316240AF1-291 C
Adder
2.99294117647058842.544
924814AB2-134 E
Adder
17.61647058823529514.974
942342AE2-247 E
Adder
3.0517647058823532.594
919152AA1-139 E1
Adder
6.1235294117647065.205
920042AA2-088 E OP
Adder
15.46470588235294113.145
934521AD1-076 C
Adder
17.82705882352941315.153
934511AD1-075 C
Adder
12.27176470588235310.431
3145723EMPORIA
Adder
0.62588235294117660.532
923573AB1-173 E OP
Adder
4.744.029
316084AB2-161 E
Adder
8.1282352941176486.909
3145946PLYMOUTH TP
Adder
0.47058823529411770.4
933982AD1-022 E
Adder
6.9329411764705885.893
940641AE2-051 C
50/50
27.86227.862
316336AC2-165 C
Adder
14.02588235294117811.922
934622AD1-088 E
Adder
6.5941176470588245.605
934612AD1-087 E
Adder
5.17764705882352954.401
940432AE2-027 E
Adder
11.99411764705882410.195
934012AD1-025 E
Adder
13.92352941176470811.835
913392Y1-086 E
Adder
3.282.788
939411AE1-173 C
50/50
143.648143.648
933502AC2-165 E
Adder
10.5564705882352968.973
3137643SOCKMAN
Adder
1.02470588235294110.871
3151031BRUNSWICKG2
50/50
12.91612.916
961611AG1-000B C
Adder
22.53529411764706219.155
316375AC2-012 C
50/50
2.0222.022
940541AE2-040 C
50/50
4.3194.319
940481AE2-033 C
50/50
24.26824.268
940482AE2-033 E
50/50
16.3616.36
923263AB1-132 E OP
Adder
8.7870588235294127.469
3152441Z1-086 ST
50/50
28.8528.85
3152431Z1-086 GT3
50/50
16.56616.566
3152421Z1-086 GT2
50/50
16.56616.566
938552AE1-074 E
50/50
1.9631.963
3150921YORKTN3
Adder
163.19176470588235138.713
3145256KINGFORK
Adder
1.49529411764705871.271
925522AC1-027 E
50/50
1.8261.826
933291AC2-141 C
50/50
45.72845.728
926755AC1-161 E
50/50
19.5219.52
941102AE2-104 E
Adder
7.9317647058823536.742
957872AF2-081 E
Adder
6.4188235294117665.456
938562AE1-075 E
Adder
1.55058823529411781.318
962572AG1-106 E
Adder
1.7082352941176471.452
3150651CHESTF6
Adder
25.5882352941176521.75
946262AF1-291 E
Adder
1.99529411764705891.696
934576AD1-082 E
Adder
6.4764705882352945.505
916191Z1-068 C
50/50
0.0660.066
933292AC2-141 E
50/50
19.5219.52
316294AC1-161 C
50/50
7.4737.473
944602AF1-125 E
50/50
153.669153.669
3145506HICKORY
50/50
3.2743.274
943612AF1-032 E
Adder
1.38000000000000011.173
957871AF2-081 C
Adder
14.97647058823529412.73
940492AE2-034 E
Adder
4.5188235294117653.841
934522AD1-076 E
Adder
9.0858823529411777.723
918492AA1-063AE OP
Adder
5.8905882352941185.007
962571AG1-106 C
Adder
3.90588235294117643.32
937482AD2-202 E
Adder
1.5152941176470591.288
942341AE2-247 C
Adder
2.21058823529411751.879
943462AF1-017 E
Adder
3.2623529411764712.773
958162AF2-110 E
Adder
3.2376470588235292.752
919153AA1-139 E2
Adder
6.1235294117647065.205
934512AD1-075 E
Adder
6.2470588235294125.31
934502AD1-074 E
Adder
24.98705882352941321.239
924516AB2-100 E1
Adder
4.2411764705882353.605
940642AE2-051 E
50/50
18.57518.575
966621AG1-532 C
Adder
2.03647058823529431.731
940431AE2-027 C
Adder
17.9905882352941215.292
942002AE2-212 E
Adder
2.0588235294117651.75
316185AD1-033 C
50/50
1.8471.847
944581AF1-123 C
50/50
68.17868.178
941101AE2-104 C
Adder
4.9894117647058824.241
316088AB2-174 E
Adder
9.4352941176470598.02
923994AB2-040_E
Adder
8.8870588235294117.554
957481AF2-042 C
Adder
79.0188235294117667.166
925332AB2-190 E
Adder
11.1200000000000019.452
927226AC1-216 E
Adder
10.7541176470588239.141
936666AD2-085 E
Adder
8.327.072
941591AE2-156 C
50/50
26.80726.807
3151081ELIZAR1
50/50
4.7964.796
316316AC1-027 C
50/50
0.4740.474
944591AF1-124 C
50/50
68.4268.42
944601AF1-125 C
50/50
67.12767.127
938771AE1-103 C
Adder
4.3211764705882353.673
3145413WATKINS
Adder
1.0152941176470590.863
960081AF2-299 C
Adder
2.7152941176470592.308
926072AC1-086 E
Adder
13.7423529411764711.681
944011AF1-069 C
50/50
20.67620.676
963041AG1-153 C
50/50
8.758.75
3151101ELIZAR3
50/50
4.8574.857
316315AB2-025 C
50/50
0.6130.613
946282AF1-292 E
Adder
1.49882352941176471.274
944012AF1-069 E
50/50
8.0328.032
3150841SPRUNCB
Adder
12.87647058823529510.945
3150831SPRUNCA
Adder
12.87647058823529510.945
926662AC1-147 E
Adder
1.98235294117647071.685
916192Z1-068 E
50/50
2.8192.819
957492AF2-043 E
Adder
2.12235294117647081.804
923852AB2-025 E
50/50
1.7471.747
939412AE1-173 E
50/50
95.76595.765
923862AB2-026 E
Adder
1.81882352941176471.546
941032AE2-094 E
50/50
28.34228.342
941031AE2-094 C
50/50
63.2863.28
939191AE1-149 C
Adder
15.69529411764705913.341
3143316POE
50/50
2.0282.028
901082W1-029 E
Adder
47.440.29
3151041BRUNSWICKG3
50/50
12.91612.916
3151021BRUNSWICKG1
50/50
12.91612.916
942001AE2-212 C
Adder
3.08941176470588232.626
939192AE1-149 E
Adder
10.4635294117647078.894
939312AE1-162 E
Adder
2.07764705882352941.766
934065AD1-033 E
50/50
7.5367.536
937226AE2-253 E
Adder
8.7623529411764727.448
934501AD1-074 C
Adder
49.0858823529411841.723
958502AF2-144 E
Adder
1.78705882352941181.519
924517AB2-100 E2
Adder
4.2411764705882353.605
957482AF2-042 E
Adder
52.67882352941176544.777
934621AD1-088 C
Adder
13.69411764705882511.64
316303AF2-085
50/50
6.5326.532
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.98737.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.12228.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8684.868
LAGNLTFEXP_LAGN->PJM
CLTF
9.7559.755
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.2837.283
CBM South 2LTFEXP_CBM-S2->PJM
CBM
125.379125.379
CPLELTFEXP_CPLE->PJM
CLTF
15.2815.28
TVALTFEXP_TVA->PJM
CLTF
7.6637.663
O66PJM->LTFIMP_O-066
CMTX_NF
35.08335.083
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5125.512
SIGELTFEXP_SIGE->PJM
CLTF
0.30.3
NYPJM->LTFIMP_NY
CLTF
2.5532.553
LGEELTFEXP_LGEE->PJM
CLTF
1.5241.524
WECLTFEXP_WEC->PJM
CLTF
0.7920.792

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.07 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3287.01
MW Contribution:3.81
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943471AF1-018 C
Adder
7.9588235294117656.765
316083AB2-161 C
80/20
0.7870.787
316072AD1-144 C
80/20
0.4020.402
940641AE2-051 C
80/20
27.30727.307
316336AC2-165 C
Adder
13.69411764705882511.64
934611AD1-087 C
80/20
1.761.76
3150731STONECA
Adder
8.9505882352941187.608
935161AD1-151 C
Adder
21.46588235294117618.246
3151221GRAVEL6
80/20
3.4833.483
3151201GRAVEL4
80/20
3.4873.487
958161AF2-110 C
80/20
1.9761.976
316017AA1-139 ULT1
80/20
1.5751.575
938531AE1-072 C
80/20
25.56125.561
933981AD1-022 C
Adder
12.39411764705882410.535
3152411Z1-086 GT1
80/20
16.26716.267
3150851SPRUNCC
80/20
0.2220.222
3156116Z1-036WIND
80/20
0.9440.944
939411AE1-173 C
80/20
140.502140.502
3137643SOCKMAN
Adder
1.00.85
3151031BRUNSWICKG2
80/20
12.67612.676
937481AD2-202 C
80/20
0.5110.511
3150651CHESTF6
Adder
24.50588235294117520.83
916191Z1-068 C
80/20
0.0640.064
316294AC1-161 C
80/20
7.267.26
957871AF2-081 C
80/20
14.54714.547
936591AD2-074 C
Adder
5.7647058823529424.9
3151151S HAMPT1
80/20
2.1352.135
316313AB2-026 C
80/20
0.5480.548
962571AG1-106 C
Adder
3.80823529411764743.237
316274AC1-208 C
Adder
12.4023529411764710.542
3151311EDGECMA
Adder
20.74352941176470817.632
942341AE2-247 C
80/20
2.1432.143
316246AF1-032 C
80/20
0.4130.413
316388AE2-253 GEN
80/20
2.8622.862
966621AG1-532 C
Adder
1.9870588235294121.689
3150861SPRUNCD
80/20
0.2220.222
940431AE2-027 C
Adder
17.26588235294117614.676
3150981CHESPKA
80/20
0.6340.634
316185AD1-033 C
80/20
1.7941.794
944581AF1-123 C
80/20
66.2266.22
941101AE2-104 C
80/20
4.8434.843
316320Y1-086 C
80/20
0.3190.319
316405AF2-144 C
80/20
0.4280.428
957481AF2-042 C
80/20
77.49977.499
316169AC1-164 GEN
Adder
44.9588235294117738.215
316349AD2-085 C
80/20
4.9434.943
3151091ELIZAR2
80/20
4.5754.575
316258AE1-075 C
80/20
0.5030.503
316023AB2-100 C2
80/20
1.3721.372
946281AF1-292 C
Adder
2.19294117647058861.864
926071AC1-086 C
Adder
29.4425.024
3151051BRUNSWICKS1
80/20
26.33426.334
927021AC1-189 C
Adder
11.4094117647058839.698
3151531CLOVER1
80/20
17.87817.878
964241AG1-285 C
Adder
17.89058823529411815.207
962561AG1-105 C
Adder
11.8176470588235310.045
3151101ELIZAR3
80/20
4.7154.715
316315AB2-025 C
80/20
0.5980.598
961951AG1-038 C
Adder
3.3341176470588242.834
957861AF2-080 C
Adder
10.3623529411764718.808
3138533PONTONDP
Adder
0.87294117647058820.742
939191AE1-149 C
80/20
15.16215.162
957601AF2-054 C
Adder
2.37764705882352922.021
316365AB2-100 C1
80/20
1.3721.372
3151041BRUNSWICKG3
80/20
12.67612.676
3151021BRUNSWICKG1
80/20
12.67612.676
964791AG1-342 C
Adder
4.6788235294117653.977
3150841SPRUNCB
80/20
12.34712.347
3150831SPRUNCA
80/20
12.34712.347
961941AG1-037 C
Adder
0.71058823529411760.604
941031AE2-094 C
80/20
62.11762.117
934331AD1-057 C
Adder
4.7623529411764714.048
934321AD1-056 C
Adder
8.5376470588235297.257
958211AF2-115 C
Adder
2.94705882352941152.505
3150601CHESTF5
Adder
76.7117647058823665.205
941591AE2-156 C
80/20
26.02126.021
3151081ELIZAR1
80/20
4.6564.656
316316AC1-027 C
80/20
0.460.46
944591AF1-124 C
80/20
66.45566.455
944601AF1-125 C
80/20
65.265.2
938771AE1-103 C
80/20
4.24.2
960081AF2-299 C
Adder
2.64941176470588242.252
944011AF1-069 C
80/20
20.29620.296
963041AG1-153 C
80/20
8.5888.588
3151541CLOVER2
80/20
17.71117.711
936261AD2-033 C
Adder
17.57529411764705814.939
961791AG1-021 C
Adder
2.35764705882352972.004
961611AG1-000B C
Adder
21.72352941176470518.465
316236AE1-162 C
80/20
0.4930.493
3152331SURRY 2
80/20
34.47834.478
316375AC2-012 C
80/20
1.9631.963
313526AB2-022 C
80/20
0.5460.546
940541AE2-040 C
80/20
4.2084.208
940481AE2-033 C
80/20
23.64823.648
3152441Z1-086 ST
80/20
28.31628.316
3152431Z1-086 GT3
80/20
16.2616.26
3152421Z1-086 GT2
80/20
16.2616.26
316233AE1-074 C
80/20
3.7763.776
940551AE2-041 C
Adder
7.9588235294117656.765
3151211GRAVEL5
80/20
3.4433.443
943461AF1-017 C
80/20
1.9381.938
316311AC2-079 C
80/20
8.2428.242
3156056W1-029WIND
80/20
1.1231.123
944631AF1-128 C
Adder
48.040.8
3150921YORKTN3
Adder
157.0388235294118133.483
933291AC2-141 C
80/20
44.42644.426
316305AF2-043 C
80/20
0.5050.505
942001AE2-212 C
80/20
2.9732.973
3151161SURRY 1
80/20
33.88933.889
3150991CHESPKB
80/20
1.051.05
316321Z2-027 C
80/20
0.5270.527
943741AF1-042 C
Adder
3.01647058823529422.564
934501AD1-074 C
Adder
47.763529411764740.599
961671AG1-007 C
Adder
1.26588235294117671.076
934621AD1-088 C
80/20
13.42613.426
946301AF1-294 C
Adder
4.8470588235294124.12
942461AE2-259 C
Adder
12.70588235294117810.8
944641AF1-129 C
Adder
134.59058823529412114.402
316240AF1-291 C
Adder
2.86941176470588262.439
316381AD1-082 C
80/20
1.7951.795
316036AC1-147 C
80/20
0.5360.536
316018AA1-139 ULT2
80/20
1.5751.575
934521AD1-076 C
Adder
17.34705882352941214.745
934511AD1-075 C
Adder
11.94117647058823610.15
316263AC1-034 C
Adder
8.8741176470588247.543
959311AF2-222 C
Adder
23.07176470588235519.611
316303AF2-085
80/20
6.3826.382
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.6437.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.68227.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8064.806
LAGNLTFEXP_LAGN->PJM
CLTF
9.5879.587
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1347.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.889122.889
CPLELTFEXP_CPLE->PJM
CLTF
14.96614.966
TVALTFEXP_TVA->PJM
CLTF
7.5327.532
SIGELTFEXP_SIGE->PJM
CLTF
0.2960.296
NYPJM->LTFIMP_NY
CLTF
2.4692.469
LGEELTFEXP_LGEE->PJM
CLTF
1.5071.507
WECLTFEXP_WEC->PJM
CLTF
0.7840.784

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.59 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3225.32
MW Contribution:4.24
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.29 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3436.04
MW Contribution:4.2
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
939192AE1-149 E
Adder
4.0364705882352953.431
939312AE1-162 E
50/50
1.9371.937
3150991CHESPKB
50/50
1.1761.176
934065AD1-033 E
50/50
8.3718.371
937226AE2-253 E
50/50
9.6579.657
316321Z2-027 C
50/50
0.5770.577
940491AE2-034 C
50/50
1.6591.659
934501AD1-074 C
Adder
46.7858823529411839.768
924517AB2-100 E2
Adder
2.92235294117647062.484
957482AF2-042 E
Adder
39.0611764705882433.202
961671AG1-007 C
Adder
1.05647058823529430.898
934621AD1-088 C
Adder
9.7717647058823538.306
935172AD1-152 E
Adder
5.5847058823529414.747
926662AC1-147 E
50/50
2.1552.155
916192Z1-068 E
50/50
3.0983.098
957492AF2-043 E
50/50
2.2332.233
923852AB2-025 E
Adder
1.06941176470588250.909
939412AE1-173 E
50/50
88.25188.251
961942AG1-037 E
Adder
0.427058823529411770.363
961941AG1-037 C
Adder
0.640.544
941032AE2-094 E
50/50
22.37122.371
941031AE2-094 C
50/50
49.94849.948
934332AD1-057 E
Adder
1.96588235294117661.671
934331AD1-057 C
Adder
3.7752941176470593.209
934321AD1-056 C
Adder
6.7670588235294115.752
934322AD1-056 E
Adder
3.6705882352941183.12
927022AC1-189 E
Adder
4.86235294117647054.133
925595AC1-034 E
Adder
5.4105882352941184.599
936262AD2-033 E
Adder
7.8811764705882356.699
942341AE2-247 C
Adder
1.93764705882352951.647
961611AG1-000B C
Adder
17.5717647058823514.936
316236AE1-162 C
50/50
0.4750.475
3152331SURRY 2
50/50
52.22852.228
316375AC2-012 C
50/50
2.1982.198
313526AB2-022 C
50/50
0.6030.603
940541AE2-040 C
Adder
2.6435294117647062.247
940481AE2-033 C
Adder
15.09058823529411912.827
940482AE2-033 E
Adder
10.1729411764705898.647
923263AB1-132 E OP
Adder
6.6282352941176485.634
925612AC1-036 E
Adder
0.80823529411764720.687
924312AB2-078 E O1
Adder
1.3164705882352941.119
926274AC1-105 E
Adder
2.5482352941176472.166
3144216WINCHST
50/50
0.1770.177
316349AD2-085 C
Adder
4.4694117647058833.799
935112AD1-144 E
50/50
1.4091.409
3151091ELIZAR2
50/50
5.1465.146
944582AF1-123 E
50/50
173.752173.752
944592AF1-124 E
50/50
174.381174.381
923832AB2-022 E
50/50
1.9881.988
938772AE1-103 E
50/50
5.6365.636
916042Z1-036 E
50/50
42.96342.963
960082AF2-299 E
Adder
1.27882352941176471.087
946281AF1-292 C
Adder
1.58823529411764721.35
926071AC1-086 C
Adder
22.77647058823529519.36
963042AG1-153 E
Adder
10.2835294117647068.741
927021AC1-189 C
Adder
9.768.296
964241AG1-285 C
Adder
12.75176470588235310.839
924152AB2-059 E OP
Adder
5.70470588235294154.849
962561AG1-105 C
Adder
8.5494117647058847.267
927226AC1-216 E
Adder
6.8258823529411765.802
962962AG1-145 E
Adder
1.36235294117647051.158
936666AD2-085 E
Adder
7.2929411764705886.199
941591AE2-156 C
50/50
29.1829.18
3151081ELIZAR1
50/50
5.2375.237
316316AC1-027 C
50/50
0.520.52
944591AF1-124 C
50/50
76.14876.148
944601AF1-125 C
50/50
74.70974.709
938771AE1-103 C
50/50
4.0814.081
3145413WATKINS
Adder
0.93058823529411770.791
960081AF2-299 C
Adder
1.91882352941176481.631
926072AC1-086 E
Adder
10.3658823529411768.811
944011AF1-069 C
50/50
16.3216.32
963041AG1-153 C
Adder
6.8564705882352955.828
957862AF2-080 E
Adder
3.9294117647058823.34
936261AD2-033 C
Adder
11.82117647058823610.048
962562AG1-105 E
Adder
5.74.845
932046AC2-012 E
50/50
21.31821.318
958161AF2-110 C
50/50
2.0262.026
316017AA1-139 ULT1
50/50
1.781.78
938531AE1-072 C
50/50
28.76728.767
3145393UNCAMP
Adder
8.367.106
315614AA2-178 C
50/50
2.2542.254
933981AD1-022 C
Adder
11.96352941176470710.169
900672V4-068 E
Adder
0.452941176470588240.385
924302AB2-077 E O1
Adder
1.3164705882352941.119
3150981CHESPKA
50/50
0.7090.709
316185AD1-033 C
50/50
2.0522.052
944581AF1-123 C
50/50
75.87875.878
941101AE2-104 C
50/50
4.9664.966
316320Y1-086 C
50/50
0.3530.353
316141AB2-099 E
Adder
0.320.272
316088AB2-174 E
Adder
6.877647058823535.846
923994AB2-040_E
Adder
6.5694117647058825.584
957481AF2-042 C
Adder
58.59176470588235549.803
961672AG1-007 E
Adder
0.59882352941176480.509
924322AB2-079 E O1
Adder
1.3164705882352941.119
943902AF1-058 E
Adder
1.21411764705882351.032
316160AE1-175 E
Adder
1.12470588235294120.956
3150921YORKTN3
50/50
162.48162.48
3145256KINGFORK
50/50
1.5181.518
925522AC1-027 E
50/50
2.0032.003
933291AC2-141 C
50/50
57.34757.347
926755AC1-161 E
50/50
24.4824.48
941102AE2-104 E
50/50
7.8957.895
316305AF2-043 C
50/50
0.5470.547
957872AF2-081 E
50/50
7.0467.046
962572AG1-106 E
Adder
1.28941176470588251.096
926214AC1-099 E
Adder
1.38941176470588231.181
932632AC2-084 E
Adder
3.71882352941176463.161
964242AG1-285 E
Adder
8.5011764705882367.226
924162AB2-060 E OP
Adder
4.1870588235294123.559
964792AG1-342 E
Adder
2.2623529411764711.923
924814AB2-134 E
Adder
11.1823529411764729.505
942342AE2-247 E
Adder
2.6752941176470592.274
316036AC1-147 C
50/50
0.60.6
919152AA1-139 E1
50/50
6.7236.723
316018AA1-139 ULT2
50/50
1.781.78
920042AA2-088 E OP
Adder
13.60117647058823611.561
934521AD1-076 C
Adder
16.99176470588235314.443
934511AD1-075 C
Adder
11.6964705882352959.942
3145723EMPORIA
Adder
0.44705882352941180.38
923573AB1-173 E OP
Adder
3.50352941176470622.978
957832AF2-077 E
Adder
1.38000000000000011.173
943461AF1-017 C
Adder
1.75294117647058821.49
932596AC2-079 E
Adder
12.36705882352941210.512
316311AC2-079 C
Adder
7.586.443
938532AE1-072 E
50/50
14.99614.996
3146326AYDLETT TAP
50/50
2.2162.216
917122Z2-027 E
50/50
2.1312.131
3156056W1-029WIND
50/50
1.211.21
920692AA2-178 E
50/50
5.9125.912
966622AG1-532 E
Adder
0.95882352941176460.815
922923AB1-081 E OP
Adder
4.0270588235294123.423
919692AA2-053 E OP
Adder
4.8294117647058834.105
925785AC1-054 E
Adder
3.63176470588235353.087
316263AC1-034 C
Adder
7.1729411764705896.097
959311AF2-222 C
Adder
15.45647058823529513.138
316084AB2-161 E
Adder
5.6282352941176474.784
316072AD1-144 C
50/50
0.4210.421
3145946PLYMOUTH TP
Adder
0.451764705882352960.384
933982AD1-022 E
Adder
6.5129411764705885.536
940641AE2-051 C
50/50
24.20324.203
927146AC1-208 E
Adder
4.5117647058823533.835
934622AD1-088 E
Adder
4.70470588235294153.999
934612AD1-087 E
Adder
3.80117647058823543.231
927255AC1-221 E
Adder
3.5270588235294122.998
934012AD1-025 E
Adder
8.837647058823537.512
913392Y1-086 E
50/50
3.5213.521
3156116Z1-036WIND
50/50
0.9890.989
939411AE1-173 C
50/50
132.376132.376
3137643SOCKMAN
Adder
0.77882352941176480.662
919710AA2-057 E
Adder
4.43.74
934576AD1-082 E
Adder
4.4847058823529413.812
916191Z1-068 C
50/50
0.0720.072
933292AC2-141 E
50/50
24.4824.48
316294AC1-161 C
50/50
9.3719.371
944602AF1-125 E
50/50
171.025171.025
3145506HICKORY
50/50
3.633.63
943612AF1-032 E
50/50
1.4511.451
957871AF2-081 C
50/50
16.44116.441
940492AE2-034 E
50/50
4.4344.434
934522AD1-076 E
Adder
8.667.361
943172AE2-346 E
Adder
0.76823529411764710.653
918492AA1-063AE OP
Adder
4.80941176470588254.088
962571AG1-106 C
Adder
2.94588235294117642.504
917332KELFORD E
Adder
2.01647058823529421.714
925122AB2-169 E
Adder
7.4694117647058836.349
316274AC1-208 C
Adder
10.168.636
917342Z2-044 E
Adder
0.65529411764705890.557
937482AD2-202 E
Adder
1.1129411764705880.946
3151311EDGECMA
Adder
16.76352941176470814.249
943462AF1-017 E
Adder
2.86000000000000032.431
958162AF2-110 E
50/50
3.2233.223
316246AF1-032 C
50/50
0.4470.447
316388AE2-253 GEN
50/50
3.2483.248
919153AA1-139 E2
50/50
6.7236.723
934512AD1-075 E
Adder
5.95411764705882355.061
934502AD1-074 E
Adder
23.81647058823529420.244
924516AB2-100 E1
Adder
2.92235294117647062.484
918512AA1-065 E OP
Adder
7.1905882352941186.112
940642AE2-051 E
50/50
16.13516.135
966621AG1-532 C
Adder
1.43882352941176481.223
918532AA1-067 E
Adder
0.85764705882352940.729
924022AB2-043 E O1
Adder
5.1070588235294124.341
3147223TWITTYS
Adder
0.89647058823529410.762
959312AF2-222 E
Adder
10.3552941176470598.802
3151101ELIZAR3
50/50
5.3035.303
946282AF1-292 E
Adder
1.05882352941176470.9
944012AF1-069 E
50/50
6.346.34
957861AF2-080 C
Adder
8.8647058823529427.535
917512Z2-088 E OP1
Adder
5.58588235294117654.748
939191AE1-149 C
Adder
8.8411764705882367.515
901082W1-029 E
50/50
49.64949.649
926206AC1-098 E
Adder
4.2070588235294123.576
964791AG1-342 C
Adder
3.39411764705882352.885
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.74418.744
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.28317.283
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.712.71
LAGNLTFEXP_LAGN->PJM
CLTF
6.3446.344
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.515.51
CBM South 2LTFEXP_CBM-S2->PJM
CBM
91.70491.704
CPLELTFEXP_CPLE->PJM
CLTF
11.56611.566
TVALTFEXP_TVA->PJM
CLTF
4.9264.926
O66PJM->LTFIMP_O-066
CMTX_NF
19.32919.329
G-007PJM->LTFIMP_G-007
CMTX_NF
3.0313.031
SIGELTFEXP_SIGE->PJM
CLTF
0.160.16
NYPJM->LTFIMP_NY
CLTF
1.4491.449
LGEELTFEXP_LGEE->PJM
CLTF
0.760.76
WECLTFEXP_WEC->PJM
CLTF
0.3980.398

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.97
MW Contribution:4.5
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.97
MW Contribution:4.5
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.81
MW Contribution:4.5
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.28 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3435.8
MW Contribution:4.49
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401

Details for AD1-056 TP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P4-2: 254T2141_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AD1-056 TP-6HATHAWAY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 254T2141_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.56 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:814.54
MW Contribution:22.95
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AD1-056 TP-6HATHAWAY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 254T2141_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.65 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:815.0
MW Contribution:22.95
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151371ROSEMS1
50/50
7.4827.482
3151391GASTONA
50/50
17.93517.935
3151381ROSEMG2
50/50
5.6565.656
934332AD1-057 E
50/50
11.27311.273
934331AD1-057 C
50/50
21.64821.648
934321AD1-056 C
50/50
38.80738.807
934322AD1-056 E
50/50
21.04921.049
926071AC1-086 C
50/50
123.404123.404
962571AG1-106 C
50/50
15.96215.962
926072AC1-086 E
50/50
56.16556.165
316011AB1-132 C OP
50/50
13.69413.694
3151361ROSEMG1
50/50
12.07912.079
923263AB1-132 E OP
50/50
35.91435.914
3151411GASTONB
50/50
17.93517.935
962572AG1-106 E
50/50
6.9836.983
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1330.133
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.4150.415
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.180.18
O66PJM->LTFIMP_O-066
CMTX_NF
1.6111.611
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.2390.239
G-007PJM->LTFIMP_G-007
CMTX_NF
0.2510.251
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0840.084
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.6180.618
MDUPJM->LTFIMP_MDU
CLTF
0.0240.024
NYPJM->LTFIMP_NY
CLTF
0.1320.132
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.5030.503
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1380.138

Details for AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 246T247_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.02 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1021.04
MW Contribution:8.68
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316023AB2-100 C2
50/50
2.92.9
960082AF2-299 E
50/50
3.0313.031
946281AF1-292 C
50/50
3.7633.763
926071AC1-086 C
50/50
46.67446.674
316317KELFORD C
50/50
0.4920.492
927021AC1-189 C
50/50
9.889.88
924152AB2-059 E OP
50/50
6.4956.495
3145413WATKINS
Adder
0.46352941176470590.394
960081AF2-299 C
50/50
4.5464.546
926072AC1-086 E
50/50
21.24321.243
957862AF2-080 E
50/50
3.9783.978
940481AE2-033 C
50/50
64.7264.72
940482AE2-033 E
50/50
43.63243.632
923263AB1-132 E OP
50/50
13.58313.583
3151411GASTONB
50/50
6.7836.783
316181AB2-040 GEN
50/50
2.6442.644
316174AB2-169_C
50/50
1.0821.082
3156063AA2-053SOLA
50/50
2.4332.433
3151281ROARAP4
50/50
2.1872.187
3156011CONETOE2SOL
50/50
1.4931.493
315614AA2-178 C
50/50
1.2131.213
933981AD1-022 C
50/50
9.1829.182
900672V4-068 E
50/50
0.4080.408
3151261ROARAP2
50/50
2.3112.311
3147043LAWRENC
50/50
0.5750.575
3156083AA2-088SOLA
50/50
1.0541.054
316141AB2-099 E
50/50
0.330.33
316088AB2-174 E
50/50
14.27714.277
313506AB1-173 C OP
50/50
2.3482.348
923994AB2-040_E
50/50
12.80412.804
3151361ROSEMG1
50/50
4.3384.338
316005AA1-067 C
50/50
0.3090.309
961672AG1-007 E
50/50
0.6430.643
316087AB2-174 C
50/50
2.5792.579
962572AG1-106 E
50/50
2.6412.641
926214AC1-099 E
50/50
1.6921.692
932632AC2-084 E
50/50
4.5274.527
920692AA2-178 E
50/50
3.1813.181
966622AG1-532 E
50/50
2.2732.273
922923AB1-081 E OP
50/50
4.5854.585
920042AA2-088 E OP
50/50
10.51910.519
934521AD1-076 C
50/50
11.51711.517
934511AD1-075 C
50/50
7.9287.928
3145723EMPORIA
50/50
1.0091.009
316011AB1-132 C OP
50/50
5.1795.179
923573AB1-173 E OP
50/50
6.8296.829
919692AA2-053 E OP
50/50
6.826.82
925785AC1-054 E
50/50
3.6613.661
316263AC1-034 C
50/50
8.1678.167
3145946PLYMOUTH TP
50/50
0.2950.295
933982AD1-022 E
50/50
4.9994.999
927146AC1-208 E
50/50
5.7685.768
316049AB1-081 C OP
50/50
1.7481.748
3152921DOMTR78
50/50
1.3421.342
316140AB2-099 C
50/50
0.1260.126
3137643SOCKMAN
50/50
1.3241.324
316212AC1-099 C
50/50
0.4430.443
919710AA2-057 E
50/50
5.3045.304
316319Z2-044 C
50/50
0.2710.271
940492AE2-034 E
50/50
2.3862.386
934522AD1-076 E
50/50
5.875.87
943172AE2-346 E
50/50
0.7920.792
918492AA1-063AE OP
50/50
5.7985.798
962571AG1-106 C
50/50
6.0376.037
917332KELFORD E
50/50
2.262.26
925122AB2-169 E
50/50
5.9415.941
932631AC2-084 C
50/50
1.4091.409
316274AC1-208 C
50/50
12.9912.99
917342Z2-044 E
50/50
0.7670.767
3151311EDGECMA
50/50
19.40219.402
934512AD1-075 E
50/50
4.0364.036
934502AD1-074 E
50/50
16.14316.143
924516AB2-100 E1
50/50
8.748.74
918512AA1-065 E OP
50/50
7.487.48
966621AG1-532 C
50/50
3.413.41
918532AA1-067 E
50/50
0.8120.812
946282AF1-292 E
50/50
2.5092.509
316129AC1-054 C
50/50
1.2981.298
957861AF2-080 C
50/50
8.9748.974
917512Z2-088 E OP1
50/50
5.8425.842
961942AG1-037 E
50/50
0.440.44
943171AE2-346 C
50/50
0.2930.293
961941AG1-037 C
50/50
0.660.66
3151391GASTONA
50/50
6.7836.783
3151381ROSEMG2
50/50
2.0322.032
934332AD1-057 E
50/50
3.0163.016
934331AD1-057 C
50/50
5.7925.792
934321AD1-056 C
50/50
10.38210.382
934322AD1-056 E
50/50
5.6325.632
927022AC1-189 E
50/50
4.9224.922
925595AC1-034 E
50/50
6.1616.161
316365AB2-100 C1
50/50
2.92.9
316318V4-068 C
50/50
0.0920.092
316210AC1-098 C
50/50
1.3231.323
926206AC1-098 E
50/50
5.1215.121
316327AA2-057 C
50/50
1.741.74
940491AE2-034 C
50/50
0.8920.892
934501AD1-074 C
50/50
31.71231.712
924517AB2-100 E2
50/50
8.748.74
3156021HOLLOMANSOL
50/50
2.4892.489
3156073AA1-063SOLA
50/50
1.9971.997
3151371ROSEMS1
50/50
2.6872.687
961671AG1-007 C
50/50
1.1341.134
316359AB2-059 C OP
50/50
2.062.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.32112.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4748.474
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5081.508
LAGNLTFEXP_LAGN->PJM
CLTF
2.9042.904
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5332.533
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.08239.082
CPLELTFEXP_CPLE->PJM
CLTF
5.3135.313
TVALTFEXP_TVA->PJM
CLTF
2.2652.265
O66PJM->LTFIMP_O-066
CMTX_NF
5.1955.195
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8170.817
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092
NYPJM->LTFIMP_NY
CLTF
0.3730.373
LGEELTFEXP_LGEE->PJM
CLTF
0.470.47
WECLTFEXP_WEC->PJM
CLTF
0.2520.252

Details for AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556_SRT-S-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.42 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:742.63
MW Contribution:5.5
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 556_SRT-S-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.42 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:762.95
MW Contribution:5.49
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
1.4941.494
3151611KERR 4
80/20
0.8620.862
933981AD1-022 C
80/20
5.6875.687
3151261ROARAP2
80/20
2.1232.123
3147043LAWRENC
80/20
0.5790.579
3151621KERR 5
80/20
0.8620.862
3152921DOMTR78
80/20
0.8540.854
316140AB2-099 C
80/20
0.0920.092
3137643SOCKMAN
80/20
1.2371.237
316212AC1-099 C
80/20
0.3680.368
316319Z2-044 C
80/20
0.2310.231
3151641KERR 7
80/20
0.8620.862
940481AE2-033 C
80/20
63.40763.407
3151411GASTONB
80/20
6.1766.176
316181AB2-040 GEN
80/20
2.5112.511
316174AB2-169_C
80/20
0.7190.719
3156063AA2-053SOLA
80/20
2.1582.158
3151281ROARAP4
80/20
2.0092.009
3156011CONETOE2SOL
80/20
1.1751.175
316238AB2-078 C O1
80/20
0.2290.229
316237AB2-079 C O1
80/20
0.2290.229
3151151S HAMPT1
80/20
0.9570.957
962571AG1-106 C
80/20
5.4965.496
932631AC2-084 C
80/20
1.171.17
316274AC1-208 C
80/20
11.22611.226
3151311EDGECMA
80/20
16.55516.555
3151601KERR 3
80/20
0.8620.862
3151581KERR 1
80/20
0.3080.308
3152661PLYWOOD A
80/20
0.6390.639
966621AG1-532 C
80/20
3.2993.299
3156083AA2-088SOLA
80/20
0.9350.935
313506AB1-173 C OP
80/20
2.2292.229
3151361ROSEMG1
80/20
3.9363.936
316005AA1-067 C
80/20
0.2210.221
957481AF2-042 C
80/20
24.31224.312
316023AB2-100 C2
80/20
2.7732.773
946281AF1-292 C
80/20
3.6413.641
926071AC1-086 C
80/20
42.49342.493
316317KELFORD C
80/20
0.370.37
927021AC1-189 C
80/20
7.5497.549
3151531CLOVER1
80/20
5.8195.819
964241AG1-285 C
80/20
7.2257.225
316034AC1-036 C
80/20
0.1240.124
962561AG1-105 C
80/20
5.2875.287
316129AC1-054 C
80/20
1.341.34
957861AF2-080 C
80/20
6.8566.856
316131AB2-060 C
80/20
1.0341.034
3138533PONTONDP
80/20
0.3360.336
316118AC1-105 C
80/20
0.4840.484
943171AE2-346 C
80/20
0.2140.214
961941AG1-037 C
80/20
0.4820.482
3151391GASTONA
80/20
6.1766.176
3151381ROSEMG2
80/20
1.8431.843
934331AD1-057 C
80/20
5.1335.133
934321AD1-056 C
80/20
9.2019.201
958211AF2-115 C
80/20
1.1351.135
316365AB2-100 C1
80/20
2.7732.773
316318V4-068 C
80/20
0.0750.075
316210AC1-098 C
80/20
1.0991.099
316327AA2-057 C
80/20
1.4891.489
316239AB2-077 C O1
80/20
0.2290.229
964791AG1-342 C
80/20
2.0352.035
960081AF2-299 C
80/20
4.3984.398
3151631KERR 6
80/20
0.8620.862
936261AD2-033 C
80/20
8.0298.029
961791AG1-021 C
80/20
0.9080.908
3144293JTRSVLE
80/20
0.2090.209
316087AB2-174 C
80/20
2.4642.464
313527AB2-043 C
80/20
0.3630.363
3151591KERR 2
80/20
0.8620.862
934501AD1-074 C
80/20
19.36119.361
3156021HOLLOMANSOL
80/20
1.5861.586
3156073AA1-063SOLA
80/20
1.8141.814
3151371ROSEMS1
80/20
2.4382.438
961671AG1-007 C
80/20
0.9120.912
934621AD1-088 C
80/20
4.4044.404
316359AB2-059 C OP
80/20
1.7611.761
946301AF1-294 C
80/20
1.8661.866
934521AD1-076 C
80/20
7.0327.032
934511AD1-075 C
80/20
4.844.84
316011AB1-132 C OP
80/20
4.7154.715
316263AC1-034 C
80/20
6.9816.981
959311AF2-222 C
80/20
8.6368.636
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.20711.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.5767.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.3611.361
LAGNLTFEXP_LAGN->PJM
CLTF
2.5782.578
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.1882.188
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.15434.154
CPLELTFEXP_CPLE->PJM
CLTF
4.5894.589
TVALTFEXP_TVA->PJM
CLTF
2.0182.018
SIGELTFEXP_SIGE->PJM
CLTF
0.0840.084
NYPJM->LTFIMP_NY
CLTF
0.3660.366
LGEELTFEXP_LGEE->PJM
CLTF
0.4310.431
WECLTFEXP_WEC->PJM
CLTF
0.2290.229

Details for AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.28 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:734.84
MW Contribution:5.97
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.5 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:797.42
MW Contribution:5.99
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316049AB1-081 C OP
80/20
1.7111.711
3151611KERR 4
80/20
0.6570.657
315614AA2-178 C
80/20
1.0031.003
933981AD1-022 C
80/20
8.3438.343
3151261ROARAP2
80/20
2.2822.282
3147043LAWRENC
80/20
0.5710.571
3151621KERR 5
80/20
0.6570.657
3156116Z1-036WIND
80/20
0.2550.255
3152921DOMTR78
80/20
1.2111.211
316140AB2-099 C
80/20
0.1220.122
3137643SOCKMAN
80/20
1.311.31
316212AC1-099 C
80/20
0.4330.433
316319Z2-044 C
80/20
0.2650.265
3151641KERR 7
80/20
0.6570.657
940481AE2-033 C
80/20
64.61764.617
3151411GASTONB
80/20
6.7066.706
316181AB2-040 GEN
80/20
2.6222.622
316174AB2-169_C
80/20
0.9980.998
3156063AA2-053SOLA
80/20
2.3942.394
3151281ROARAP4
80/20
2.1592.159
3156011CONETOE2SOL
80/20
1.4461.446
316238AB2-078 C O1
80/20
0.1480.148
316237AB2-079 C O1
80/20
0.1480.148
3151151S HAMPT1
80/20
1.0421.042
962571AG1-106 C
80/20
5.9685.968
932631AC2-084 C
80/20
1.3771.377
316274AC1-208 C
80/20
12.74212.742
3151311EDGECMA
80/20
18.98318.983
3151601KERR 3
80/20
0.6570.657
3151581KERR 1
80/20
0.2350.235
966621AG1-532 C
80/20
3.3893.389
3156083AA2-088SOLA
80/20
1.0451.045
313506AB1-173 C OP
80/20
2.3282.328
3151361ROSEMG1
80/20
4.2874.287
316005AA1-067 C
80/20
0.2960.296
316023AB2-100 C2
80/20
2.8852.885
946281AF1-292 C
80/20
3.743.74
926071AC1-086 C
80/20
46.14346.143
316317KELFORD C
80/20
0.4770.477
927021AC1-189 C
80/20
9.5339.533
962561AG1-105 C
80/20
3.0443.044
316129AC1-054 C
80/20
1.2821.282
957861AF2-080 C
80/20
8.6598.659
316131AB2-060 C
80/20
0.660.66
943171AE2-346 C
80/20
0.2840.284
961941AG1-037 C
80/20
0.6390.639
3151391GASTONA
80/20
6.7066.706
3151381ROSEMG2
80/20
2.0072.007
934331AD1-057 C
80/20
5.7015.701
934321AD1-056 C
80/20
10.21910.219
316365AB2-100 C1
80/20
2.8852.885
316318V4-068 C
80/20
0.090.09
316210AC1-098 C
80/20
1.2931.293
316327AA2-057 C
80/20
1.7051.705
316239AB2-077 C O1
80/20
0.1480.148
964791AG1-342 C
80/20
1.141.14
938771AE1-103 C
80/20
1.2911.291
960081AF2-299 C
80/20
4.5194.519
3151631KERR 6
80/20
0.6570.657
936261AD2-033 C
80/20
4.7924.792
316087AB2-174 C
80/20
2.5592.559
313527AB2-043 C
80/20
0.2330.233
3151591KERR 2
80/20
0.6570.657
940491AE2-034 C
80/20
0.7380.738
934501AD1-074 C
80/20
28.03528.035
3156021HOLLOMANSOL
80/20
2.3832.383
3156073AA1-063SOLA
80/20
1.9741.974
3151371ROSEMS1
80/20
2.6552.655
961671AG1-007 C
80/20
1.1011.101
316359AB2-059 C OP
80/20
2.0162.016
934521AD1-076 C
80/20
10.18210.182
934511AD1-075 C
80/20
7.0097.009
316011AB1-132 C OP
80/20
5.125.12
316263AC1-034 C
80/20
7.9927.992
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.98411.984
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.2438.243
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4671.467
LAGNLTFEXP_LAGN->PJM
CLTF
2.8252.825
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4622.462
CBM South 2LTFEXP_CBM-S2->PJM
CBM
38.00838.008
CPLELTFEXP_CPLE->PJM
CLTF
5.1655.165
TVALTFEXP_TVA->PJM
CLTF
2.2042.204
SIGELTFEXP_SIGE->PJM
CLTF
0.090.09
NYPJM->LTFIMP_NY
CLTF
0.3630.363
LGEELTFEXP_LGEE->PJM
CLTF
0.4570.457
WECLTFEXP_WEC->PJM
CLTF
0.2450.245
CONTINGENCY 'DVP_P7-1: LN 2058-2181_SRT-A'
 OPEN BRANCH FROM BUS 304222 TO BUS 313845 CKT 1   /*6ROCKYMT230T 230.0 - 6HATHAWAY    230.0
 OPEN BRANCH FROM BUS 304226 TO BUS 314591 CKT 1   /*6PA-RMOUNT#4 230.0 - 6NASH        230.0
 OPEN BRANCH FROM BUS 313844 TO BUS 313845 CKT 2   /*3HATHAWAY    115.0 - 6HATHAWAY    230.0
 OPEN BRANCH FROM BUS 313845 TO BUS 314591 CKT 1   /*6HATHAWAY    230.0 - 6NASH        230.0
 OPEN BUS 304226                                   /*6PA-RMOUNT#4 230.0
 OPEN BUS 314591                                   /*6NASH        230.0
END
CONTINGENCY 'DVP_P1-2: LN 556_SRT-S-3'
 OPEN BRANCH FROM BUS 313995 TO BUS 314936 CKT 1                /*8FINNEYWOOD  500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 217_SRT-A'
 OPEN BRANCH FROM BUS 314225 TO BUS 314227 CKT 1   /*6CHARCTY     230.0 - 6LAKESIDE    230.0
 OPEN BRANCH FROM BUS 314225 TO BUS 314260 CKT 1   /*6CHARCTY     230.0 - 6VARINA      230.0
 OPEN BRANCH FROM BUS 314260 TO BUS 314287 CKT 1   /*6VARINA      230.0 - 6CHESTF B    230.0
 OPEN BUS 314225                                   /*6CHARCTY     230.0
 OPEN BUS 314260                                   /*6VARINA      230.0
END
CONTINGENCY 'DVP_P4-2: 246T247_SRT-A'
 OPEN BRANCH FROM BUS 313713 TO BUS 314648 CKT 1   /*6SWAMP       230.0 - 6SUNBURY     230.0
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314537 TO BUS 314648 CKT 1   /*6SUFFOLK     230.0 - 6SUNBURY     230.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
 OPEN BUS 314648                                   /*6SUNBURY     230.0
END
CONTINGENCY 'DVP_P4-2: 24642_SRT-A'
 OPEN BRANCH FROM BUS 314536 TO BUS 314537 CKT 3   /*3SUFFOLK     115.0 - 6SUFFOLK     230.0
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314537 TO BUS 314928 CKT 2   /*6SUFFOLK     230.0 - 8SUFFOLK     500.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
END
CONTINGENCY 'DVP_P4-2: 24662_SRT-A'
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314568 TO BUS 314569 CKT 1   /*3EARLEYS     115.0 - 6EARLEYS     230.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
END
CONTINGENCY 'DVP_P1-2: LN 2092_SRT-A'
 OPEN BRANCH FROM BUS 313714 TO BUS 313885 CKT 1   /*6PEMBROKE    230.0 - 6WALBMRL     230.0
 OPEN BRANCH FROM BUS 313885 TO BUS 314662 CKT 1   /*6WALBMRL     230.0 - 6S HERTFORD  230.0
 OPEN BRANCH FROM BUS 314651 TO BUS 314662 CKT 1   /*6WINFALL     230.0 - 6S HERTFORD  230.0
 OPEN BUS 313885                                   /*6WALBMRL     230.0
 OPEN BUS 314662                                   /*6S HERTFORD  230.0
END
CONTINGENCY 'DVP_P1-2: LN 2131_SRT-A'
 OPEN BRANCH FROM BUS 313015 TO BUS 313714 CKT 1   /*6CHOWAN      230.0 - 6PEMBROKE    230.0
 OPEN BRANCH FROM BUS 313015 TO BUS 314637 CKT 1   /*6CHOWAN      230.0 - 6EDENTON     230.0
 OPEN BRANCH FROM BUS 314203 TO BUS 314637 CKT 1   /*6MACKEYS     230.0 - 6EDENTON     230.0
 OPEN BUS 313015                                   /*6CHOWAN      230.0
 OPEN BUS 314637                                   /*6EDENTON     230.0
END
CONTINGENCY 'DVP_P4-2: H2T557_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 254T2141_SRT-A'
 OPEN BRANCH FROM BUS 313725 TO BUS 314583 CKT 1   /*6DRY BREAD   230.0 - 6LAKEVEW     230.0
 OPEN BRANCH FROM BUS 314561 TO BUS 314583 CKT 1   /*6CAROLNA     230.0 - 6LAKEVEW     230.0
END
CONTINGENCY 'DVP_P1-2: LN 246_SRT-A'
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A'
 OPEN BRANCH FROM BUS 314218 TO BUS 314196 CKT 1   /*6ELMONT      230.0 - 6LADYSMITH   230.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1   /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T567_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
314554 to 304223 ckt 1
314677 to 314747 ckt 1
314282 to 314285 ckt 1
314285 to 314316 ckt 1
314287 to 314276 ckt 1
314563 to 940480 ckt 1
314569 to 314575 ckt 1
314638 to 314647 ckt 1
314218 to 314908 ckt 1
314692 to 314677 ckt 1
314579 to 934320 ckt 1
314575 to 314537 ckt 1
314331 to 314263 ckt 1
314435 to 314282 ckt 1
314902 to 314914 ckt 1
314914 to 314322 ckt 1
314914 to 314918 ckt 1
314924 to 314903 ckt 1
934320 to 313845 ckt 1
940480 to 314435 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC100.89 %984.18B992.941.85
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
SingleAC108.46 %678.68B736.135.99
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A
SingleAC104.8 %678.68B711.275.47
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Base Case
SingleAC102.72 %678.68A697.115.48
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC113.38 %3940.0C4467.25.25
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.8 %3220.44B3342.683.63
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC104.31 %3637.0C3793.695.34
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC111.92 %4070.2B4555.564.26
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC111.48 %5011.0C5586.286.13
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC101.04 %4070.2B4112.53.59
GD1DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC100.32 %3220.44B3230.792.18
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC119.82 %3220.44B3858.593.99
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC117.79 %3940.0C4641.115.79
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC111.38 %3220.44B3586.782.07
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
SingleAC111.09 %3220.44B3577.612.19
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC110.41 %3940.0C4350.173.12
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T594_SRT-S
BreakerAC106.75 %3940.0C4205.812.98
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC116.97 %3220.44B3767.032.47
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC114.22 %3220.44B3678.492.84
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC111.99 %3940.0C4412.363.71
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC121.18 %3220.44B3902.622.4
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC120.07 %3220.44B3866.792.78
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC117.55 %3940.0C4631.323.64

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.89 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:992.94
MW Contribution:1.85
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.1050.105
961941AG1-037 C
80/20
0.2370.237
3151391GASTONA
80/20
2.0712.071
934321AD1-056 C
80/20
3.7443.744
934331AD1-057 C
80/20
2.0892.089
958211AF2-115 C
Adder
0.80.68
3151531CLOVER1
80/20
6.056.05
941031AE2-094 C
80/20
22.06822.068
316365AB2-100 C1
80/20
0.7990.799
3156083AA2-088SOLA
80/20
0.4670.467
316003AC1-222 C
80/20
0.4260.426
957481AF2-042 C
80/20
26.38726.387
315614AA2-178 C
80/20
0.5670.567
3151411GASTONB
80/20
2.0712.071
316181AB2-040 GEN
80/20
0.8530.853
3147043LAWRENC
80/20
0.2030.203
940481AE2-033 C
80/20
16.46516.465
940541AE2-040 C
80/20
2.9992.999
3152441Z1-086 ST
80/20
10.00810.008
316005AA1-067 C
80/20
0.1280.128
316210AC1-098 C
80/20
0.50.5
316318V4-068 C
80/20
0.0370.037
313506AB1-173 C OP
80/20
0.7570.757
966621AG1-532 C
80/20
1.041.04
3151601KERR 3
80/20
0.5540.554
3151581KERR 1
80/20
0.1980.198
935171AD1-152 C
80/20
0.620.62
3151021BRUNSWICKG1
80/20
4.4774.477
3151041BRUNSWICKG3
80/20
4.4774.477
934521AD1-076 C
80/20
4.8074.807
934511AD1-075 C
80/20
3.3093.309
316212AC1-099 C
80/20
0.1680.168
316263AC1-034 C
80/20
3.5493.549
3156073AA1-063SOLA
80/20
0.7530.753
3151381ROSEMG2
80/20
0.6340.634
960081AF2-299 C
80/20
1.3861.386
936261AD2-033 C
80/20
5.4245.424
316248AF1-058 C
80/20
0.140.14
961791AG1-021 C
Adder
0.640.544
938771AE1-103 C
Adder
0.96705882352941170.822
963041AG1-153 C
80/20
3.0443.044
3151051BRUNSWICKS1
80/20
9.3029.302
944011AF1-069 C
80/20
7.217.21
316087AB2-174 C
80/20
0.8150.815
3151591KERR 2
80/20
0.5540.554
959311AF2-222 C
80/20
6.6486.648
937481AD2-202 C
80/20
0.1730.173
3151031BRUNSWICKG2
80/20
4.4774.477
316240AF1-291 C
Adder
-1.6611764705882353-1.412
944641AF1-129 C
Adder
-92.12117647058824-78.303
934501AD1-074 C
80/20
13.23613.236
961671AG1-007 C
80/20
0.4820.482
940491AE2-034 C
80/20
0.4170.417
316359AB2-059 C OP
80/20
0.8920.892
316283AC2-100 C
80/20
0.510.51
946301AF1-294 C
Adder
1.3164705882352941.119
934621AD1-088 C
80/20
4.424.42
942001AE2-212 C
Adder
-3.9329411764705884-3.343
316140AB2-099 C
80/20
0.0450.045
3152921DOMTR78
80/20
0.5570.557
316319Z2-044 C
80/20
0.1130.113
3151641KERR 7
80/20
0.5540.554
313527AB2-043 C
80/20
0.2380.238
3151261ROARAP2
80/20
0.8190.819
3152411Z1-086 GT1
80/20
5.755.75
3152421Z1-086 GT2
80/20
5.7485.748
3156021HOLLOMANSOL
80/20
0.830.83
316011AB1-132 C OP
80/20
1.5811.581
3151371ROSEMS1
80/20
0.8390.839
3137643SOCKMAN
80/20
0.4490.449
939411AE1-173 C
80/20
41.75841.758
927021AC1-189 C
80/20
4.1534.153
926071AC1-086 C
80/20
14.30114.301
946281AF1-292 C
80/20
1.1471.147
964241AG1-285 C
80/20
5.5515.551
962561AG1-105 C
80/20
4.0224.022
316034AC1-036 C
80/20
0.0950.095
316118AC1-105 C
80/20
0.4080.408
932631AC2-084 C
80/20
0.5330.533
316274AC1-208 C
80/20
4.9624.962
962571AG1-106 C
80/20
1.851.85
3151311EDGECMA
80/20
8.3398.339
3152661PLYWOOD A
80/20
0.5410.541
3151361ROSEMG1
80/20
1.3551.355
316327AA2-057 C
80/20
0.7010.701
3151151S HAMPT1
80/20
0.570.57
316239AB2-077 C O1
80/20
0.1510.151
964791AG1-342 C
80/20
1.5971.597
933981AD1-022 C
80/20
3.5783.578
316174AB2-169_C
80/20
0.4490.449
3156063AA2-053SOLA
80/20
0.860.86
3151281ROARAP4
80/20
0.7750.775
316049AB1-081 C OP
80/20
0.7570.757
316238AB2-078 C O1
80/20
0.1510.151
3156011CONETOE2SOL
80/20
0.6290.629
3151611KERR 4
80/20
0.5540.554
3151621KERR 5
80/20
0.5540.554
316237AB2-079 C O1
80/20
0.1510.151
316222AC1-221 C
80/20
0.6320.632
934611AD1-087 C
80/20
0.5960.596
3152431Z1-086 GT3
80/20
5.7485.748
940641AE2-051 C
80/20
9.0359.035
316317KELFORD C
80/20
0.1760.176
957861AF2-080 C
80/20
3.7723.772
316023AB2-100 C2
80/20
0.7990.799
316129AC1-054 C
80/20
0.6480.648
3151631KERR 6
80/20
0.5540.554
316315AB2-025 C
80/20
0.4250.425
316131AB2-060 C
80/20
0.680.68
3138533PONTONDP
Adder
0.237647058823529430.202
3151541CLOVER2
80/20
5.9935.993
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.95317.953
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.57311.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1342.134
LAGNLTFEXP_LAGN->PJM
CLTF
3.8673.867
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.6422.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.16446.164
CPLELTFEXP_CPLE->PJM
CLTF
5.5395.539
TVALTFEXP_TVA->PJM
CLTF
3.0473.047
SIGELTFEXP_SIGE->PJM
CLTF
0.1330.133
NYPJM->LTFIMP_NY
CLTF
0.5840.584
LGEELTFEXP_LGEE->PJM
CLTF
0.6950.695
WECLTFEXP_WEC->PJM
CLTF
0.3670.367

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:736.13
MW Contribution:5.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.2840.284
961941AG1-037 C
80/20
0.6420.642
3151391GASTONA
80/20
6.76.7
934321AD1-056 C
80/20
10.25810.258
934331AD1-057 C
80/20
5.7225.722
958211AF2-115 C
80/20
0.790.79
3151381ROSEMG2
80/20
2.0062.006
960081AF2-299 C
80/20
4.5664.566
936261AD2-033 C
80/20
6.4546.454
961791AG1-021 C
80/20
0.6320.632
938771AE1-103 C
80/20
1.2731.273
316365AB2-100 C1
80/20
2.8782.878
3156083AA2-088SOLA
80/20
1.0451.045
315614AA2-178 C
80/20
0.9970.997
3151411GASTONB
80/20
6.76.7
316181AB2-040 GEN
80/20
2.6392.639
3147043LAWRENC
80/20
0.5880.588
316005AA1-067 C
80/20
0.2960.296
316210AC1-098 C
80/20
1.2971.297
316318V4-068 C
80/20
0.090.09
313506AB1-173 C OP
80/20
2.3432.343
966621AG1-532 C
80/20
3.4243.424
3151601KERR 3
80/20
0.7120.712
3151581KERR 1
80/20
0.2540.254
932631AC2-084 C
80/20
1.3811.381
316274AC1-208 C
80/20
12.83612.836
962571AG1-106 C
80/20
5.9855.985
3151311EDGECMA
80/20
19.08119.081
3152661PLYWOOD A
80/20
0.3910.391
934521AD1-076 C
80/20
10.18310.183
934511AD1-075 C
80/20
7.017.01
316212AC1-099 C
80/20
0.4340.434
316263AC1-034 C
80/20
8.0388.038
3156073AA1-063SOLA
80/20
1.9821.982
316087AB2-174 C
80/20
2.5762.576
3151591KERR 2
80/20
0.7120.712
959311AF2-222 C
80/20
7.5547.554
927021AC1-189 C
80/20
9.5779.577
926071AC1-086 C
80/20
46.26846.268
946281AF1-292 C
80/20
3.783.78
964241AG1-285 C
80/20
7.0017.001
962561AG1-105 C
80/20
3.8843.884
316034AC1-036 C
80/20
0.110.11
316118AC1-105 C
80/20
0.3030.303
3144293JTRSVLE
80/20
0.1450.145
934501AD1-074 C
80/20
28.03828.038
961671AG1-007 C
80/20
1.1061.106
940491AE2-034 C
80/20
0.7340.734
316359AB2-059 C OP
80/20
2.0212.021
3156116Z1-036WIND
80/20
0.2510.251
946301AF1-294 C
80/20
1.31.3
316140AB2-099 C
80/20
0.1220.122
3152921DOMTR78
80/20
1.2081.208
316319Z2-044 C
80/20
0.2660.266
3151641KERR 7
80/20
0.7120.712
313527AB2-043 C
80/20
0.3120.312
3151261ROARAP2
80/20
2.2952.295
3156021HOLLOMANSOL
80/20
2.3822.382
316011AB1-132 C OP
80/20
5.1165.116
3151371ROSEMS1
80/20
2.6542.654
3137643SOCKMAN
80/20
1.3221.322
933981AD1-022 C
80/20
8.3538.353
316174AB2-169_C
80/20
0.9970.997
3156063AA2-053SOLA
80/20
2.4062.406
3151281ROARAP4
80/20
2.1722.172
316049AB1-081 C OP
80/20
1.7151.715
316238AB2-078 C O1
80/20
0.1950.195
3151361ROSEMG1
80/20
4.2844.284
316327AA2-057 C
80/20
1.711.71
3151151S HAMPT1
80/20
1.0351.035
316239AB2-077 C O1
80/20
0.1950.195
964791AG1-342 C
80/20
1.4341.434
3156011CONETOE2SOL
80/20
1.4481.448
3151611KERR 4
80/20
0.7120.712
3151621KERR 5
80/20
0.7120.712
316237AB2-079 C O1
80/20
0.1950.195
316317KELFORD C
80/20
0.4780.478
957861AF2-080 C
80/20
8.6988.698
316023AB2-100 C2
80/20
2.8782.878
316129AC1-054 C
80/20
1.321.32
3151631KERR 6
80/20
0.7120.712
316131AB2-060 C
80/20
0.8840.884
3138533PONTONDP
80/20
0.2340.234
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.04115.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.5619.561
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.7731.773
LAGNLTFEXP_LAGN->PJM
CLTF
3.1853.185
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5172.517
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.76439.764
CPLELTFEXP_CPLE->PJM
CLTF
5.2785.278
TVALTFEXP_TVA->PJM
CLTF
2.5052.505
SIGELTFEXP_SIGE->PJM
CLTF
0.1110.111
NYPJM->LTFIMP_NY
CLTF
0.4240.424
LGEELTFEXP_LGEE->PJM
CLTF
0.5780.578
WECLTFEXP_WEC->PJM
CLTF
0.3070.307

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.8 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:711.27
MW Contribution:5.47
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.2110.211
961941AG1-037 C
80/20
0.4770.477
3151391GASTONA
80/20
6.1266.126
934321AD1-056 C
80/20
9.4289.428
934331AD1-057 C
80/20
5.2595.259
3151381ROSEMG2
80/20
1.8351.835
960081AF2-299 C
80/20
4.3064.306
936171AD2-023 C
80/20
2.0082.008
936261AD2-033 C
80/20
5.5815.581
938771AE1-103 C
80/20
1.1451.145
316365AB2-100 C1
80/20
2.7382.738
3156083AA2-088SOLA
80/20
0.8980.898
315614AA2-178 C
80/20
0.6860.686
3151411GASTONB
80/20
6.1266.126
316181AB2-040 GEN
80/20
2.4442.444
3147043LAWRENC
80/20
0.5520.552
316005AA1-067 C
80/20
0.2330.233
316210AC1-098 C
80/20
1.1041.104
316318V4-068 C
80/20
0.0730.073
313506AB1-173 C OP
80/20
2.1692.169
966621AG1-532 C
80/20
3.233.23
3151601KERR 3
80/20
0.6330.633
3151581KERR 1
80/20
0.2260.226
936161AD2-022 C
80/20
3.4423.442
932631AC2-084 C
80/20
1.1761.176
316274AC1-208 C
80/20
11.28911.289
962571AG1-106 C
80/20
5.4715.471
3151311EDGECMA
80/20
17.61917.619
934521AD1-076 C
80/20
7.0037.003
934511AD1-075 C
80/20
4.8214.821
316212AC1-099 C
80/20
0.370.37
316263AC1-034 C
80/20
7.4217.421
3156073AA1-063SOLA
80/20
1.7541.754
316087AB2-174 C
80/20
2.42.4
3151591KERR 2
80/20
0.6330.633
959311AF2-222 C
80/20
6.4496.449
927021AC1-189 C
80/20
8.0138.013
934501AD1-074 C
80/20
19.28319.283
961671AG1-007 C
80/20
0.970.97
940491AE2-034 C
80/20
0.5050.505
316359AB2-059 C OP
80/20
1.8661.866
316140AB2-099 C
80/20
0.0910.091
3152921DOMTR78
80/20
0.8630.863
316319Z2-044 C
80/20
0.2410.241
3151641KERR 7
80/20
0.6330.633
313527AB2-043 C
80/20
0.2770.277
3151261ROARAP2
80/20
2.0572.057
3156021HOLLOMANSOL
80/20
1.581.58
316011AB1-132 C OP
80/20
4.6784.678
3151371ROSEMS1
80/20
2.4282.428
3137643SOCKMAN
80/20
1.2051.205
933981AD1-022 C
80/20
5.6735.673
316174AB2-169_C
80/20
0.7390.739
3156063AA2-053SOLA
80/20
2.0962.096
3151281ROARAP4
80/20
1.9471.947
316049AB1-081 C OP
80/20
1.5831.583
316238AB2-078 C O1
80/20
0.1730.173
926071AC1-086 C
80/20
42.342.3
946281AF1-292 C
80/20
3.5653.565
964241AG1-285 C
80/20
6.1446.144
962561AG1-105 C
80/20
3.4083.408
316034AC1-036 C
80/20
0.0940.094
3151361ROSEMG1
80/20
3.923.92
316327AA2-057 C
80/20
1.5281.528
3151151S HAMPT1
80/20
0.9030.903
316239AB2-077 C O1
80/20
0.1730.173
964791AG1-342 C
80/20
1.2551.255
3156011CONETOE2SOL
80/20
1.2441.244
3151611KERR 4
80/20
0.6330.633
3151621KERR 5
80/20
0.6330.633
316237AB2-079 C O1
80/20
0.1730.173
316317KELFORD C
80/20
0.3680.368
957861AF2-080 C
80/20
7.2787.278
316023AB2-100 C2
80/20
2.7382.738
316129AC1-054 C
80/20
1.1791.179
3151631KERR 6
80/20
0.6330.633
316131AB2-060 C
80/20
0.7820.782
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.22922.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.65213.652
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.5732.573
LAGNLTFEXP_LAGN->PJM
CLTF
4.5044.504
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1753.175
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.41853.418
CPLELTFEXP_CPLE->PJM
CLTF
6.6566.656
TVALTFEXP_TVA->PJM
CLTF
3.5423.542
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
NYPJM->LTFIMP_NY
CLTF
0.4770.477
LGEELTFEXP_LGEE->PJM
CLTF
0.8450.845
WECLTFEXP_WEC->PJM
CLTF
0.4510.451

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.72 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:697.11
MW Contribution:5.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.2130.213
961941AG1-037 C
80/20
0.480.48
3151391GASTONA
80/20
6.1336.133
934321AD1-056 C
80/20
9.1359.135
934331AD1-057 C
80/20
5.0965.096
958211AF2-115 C
80/20
0.7340.734
316365AB2-100 C1
80/20
2.7652.765
3156083AA2-088SOLA
80/20
0.9250.925
315614AA2-178 C
80/20
0.7290.729
3151411GASTONB
80/20
6.1336.133
316181AB2-040 GEN
80/20
2.4632.463
3147043LAWRENC
80/20
0.5590.559
940481AE2-033 C
80/20
63.69463.694
940541AE2-040 C
80/20
11.74711.747
316005AA1-067 C
80/20
0.220.22
316210AC1-098 C
80/20
1.0791.079
316318V4-068 C
80/20
0.0740.074
313506AB1-173 C OP
80/20
2.1872.187
966621AG1-532 C
80/20
3.2633.263
3151601KERR 3
80/20
0.6440.644
3151581KERR 1
80/20
0.230.23
932631AC2-084 C
80/20
1.1481.148
316274AC1-208 C
80/20
11.02211.022
962571AG1-106 C
80/20
5.4785.478
3151311EDGECMA
80/20
16.35316.353
934521AD1-076 C
80/20
7.217.21
934511AD1-075 C
80/20
4.9634.963
316212AC1-099 C
80/20
0.3610.361
316263AC1-034 C
80/20
6.8836.883
3156073AA1-063SOLA
80/20
1.7721.772
316087AB2-174 C
80/20
2.4212.421
3151591KERR 2
80/20
0.6440.644
959311AF2-222 C
80/20
7.0127.012
3151381ROSEMG2
80/20
1.831.83
960081AF2-299 C
80/20
4.3514.351
936261AD2-033 C
80/20
5.9895.989
961791AG1-021 C
80/20
0.5880.588
938771AE1-103 C
80/20
1.2791.279
934501AD1-074 C
80/20
19.85319.853
961671AG1-007 C
80/20
0.9040.904
940491AE2-034 C
80/20
0.5370.537
316359AB2-059 C OP
80/20
1.731.73
3156116Z1-036WIND
80/20
0.2010.201
946301AF1-294 C
80/20
1.2081.208
316140AB2-099 C
80/20
0.0910.091
3152921DOMTR78
80/20
0.8660.866
316319Z2-044 C
80/20
0.2270.227
3151641KERR 7
80/20
0.6440.644
313527AB2-043 C
80/20
0.290.29
3151261ROARAP2
80/20
2.0652.065
3156021HOLLOMANSOL
80/20
1.5911.591
316011AB1-132 C OP
80/20
4.6834.683
3151371ROSEMS1
80/20
2.422.42
3137643SOCKMAN
80/20
1.2121.212
933981AD1-022 C
80/20
5.7955.795
316174AB2-169_C
80/20
0.7240.724
3156063AA2-053SOLA
80/20
2.1042.104
3151281ROARAP4
80/20
1.9541.954
927021AC1-189 C
80/20
7.5047.504
926071AC1-086 C
80/20
42.34842.348
946281AF1-292 C
80/20
3.6023.602
964241AG1-285 C
80/20
6.4946.494
962561AG1-105 C
80/20
3.5683.568
316034AC1-036 C
80/20
0.1020.102
3144293JTRSVLE
80/20
0.1350.135
3151361ROSEMG1
80/20
3.9083.908
316327AA2-057 C
80/20
1.461.46
3151151S HAMPT1
80/20
0.9570.957
316239AB2-077 C O1
80/20
0.1810.181
964791AG1-342 C
80/20
1.3141.314
316049AB1-081 C OP
80/20
1.4681.468
316238AB2-078 C O1
80/20
0.1810.181
3156011CONETOE2SOL
80/20
1.1621.162
3151611KERR 4
80/20
0.6440.644
3151621KERR 5
80/20
0.6440.644
316237AB2-079 C O1
80/20
0.1810.181
316317KELFORD C
80/20
0.3660.366
957861AF2-080 C
80/20
6.8156.815
316023AB2-100 C2
80/20
2.7652.765
316129AC1-054 C
80/20
1.1891.189
3151631KERR 6
80/20
0.6440.644
316315AB2-025 C
80/20
1.6631.663
316131AB2-060 C
80/20
0.820.82
3138533PONTONDP
80/20
0.2180.218
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.06512.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.7657.765
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4321.432
LAGNLTFEXP_LAGN->PJM
CLTF
2.5962.596
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.0622.062
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.61632.616
CPLELTFEXP_CPLE->PJM
CLTF
4.3234.323
TVALTFEXP_TVA->PJM
CLTF
2.0422.042
SIGELTFEXP_SIGE->PJM
CLTF
0.0890.089
NYPJM->LTFIMP_NY
CLTF
0.370.37
LGEELTFEXP_LGEE->PJM
CLTF
0.4650.465
WECLTFEXP_WEC->PJM
CLTF
0.2460.246

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.38 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4467.2
MW Contribution:5.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.33882352941176470.288
961672AG1-007 E
Adder
0.71058823529411760.604
923994AB2-040_E
Adder
8.2247058823529416.991
316088AB2-174 E
Adder
8.7141176470588247.407
924322AB2-079 E O1
Adder
1.6447058823529411.398
943902AF1-058 E
Adder
1.65529411764705881.407
957481AF2-042 C
50/50
79.02379.023
316294AC1-161 C
50/50
6.8696.869
944581AF1-123 C
50/50
62.37662.376
316185AD1-033 C
50/50
1.6591.659
916191Z1-068 C
50/50
0.0590.059
941101AE2-104 C
Adder
4.4388235294117653.773
923263AB1-132 E OP
Adder
8.217647058823536.985
940481AE2-033 C
50/50
22.31122.311
940482AE2-033 E
50/50
15.04115.041
940541AE2-040 C
50/50
3.9673.967
924312AB2-078 E O1
Adder
1.6447058823529411.398
926274AC1-105 E
Adder
3.4082352941176472.897
3152441Z1-086 ST
50/50
30.18730.187
316375AC2-012 C
50/50
1.8031.803
918512AA1-065 E OP
Adder
7.42823529411764756.314
918532AA1-067 E
Adder
0.95764705882352940.814
934502AD1-074 E
Adder
23.0929411764705919.629
934512AD1-075 E
Adder
5.7729411764705894.907
924516AB2-100 E1
Adder
3.9282352941176473.339
966621AG1-532 C
Adder
1.87411764705882341.593
919153AA1-139 E2
50/50
5.535.53
316388AE2-253 GEN
50/50
2.652.65
924022AB2-043 E O1
Adder
6.3552941176470595.402
3151021BRUNSWICKG1
50/50
13.49313.493
3151041BRUNSWICKG3
50/50
13.49313.493
940642AE2-051 E
50/50
19.2519.25
942341AE2-247 C
Adder
1.89411764705882371.61
943462AF1-017 E
Adder
2.7964705882352942.377
958162AF2-110 E
Adder
2.8811764705882352.449
934501AD1-074 C
Adder
45.3647058823529438.56
961671AG1-007 C
Adder
1.25411764705882361.066
924517AB2-100 E2
Adder
3.9282352941176473.339
937226AE2-253 E
50/50
7.9097.909
935172AD1-152 E
Adder
7.5717647058823536.436
934621AD1-088 C
50/50
13.2613.26
957482AF2-042 E
50/50
52.68252.682
939192AE1-149 E
Adder
8.0705882352941176.86
939312AE1-162 E
Adder
1.72117647058823551.463
934065AD1-033 E
50/50
6.7926.792
920692AA2-178 E
Adder
5.5388235294117654.708
922923AB1-081 E OP
Adder
4.9682352941176474.223
966622AG1-532 E
Adder
1.24941176470588241.062
917122Z2-027 E
Adder
1.81294117647058831.541
3146326AYDLETT TAP
50/50
1.8341.834
926214AC1-099 E
Adder
1.61294117647058831.371
932632AC2-084 E
Adder
4.3164705882352943.669
962572AG1-106 E
Adder
1.59764705882352961.358
957872AF2-081 E
50/50
5.7955.795
316018AA1-139 ULT2
50/50
1.4591.459
924162AB2-060 E OP
Adder
5.2141176470588244.432
964242AG1-285 E
Adder
9.9188235294117648.431
964792AG1-342 E
Adder
2.9682352941176472.523
932763AC2-100 E
Adder
3.2952941176470592.801
926755AC1-161 E
50/50
18.00718.007
933291AC2-141 C
50/50
42.18342.183
3150921YORKTN3
Adder
106.1988235294117790.269
925522AC1-027 E
50/50
1.641.64
941102AE2-104 E
Adder
7.0576470588235295.999
3145256KINGFORK
Adder
1.30823529411764721.112
919710AA2-057 E
Adder
5.2964705882352944.502
3137643SOCKMAN
Adder
0.95176470588235310.809
913392Y1-086 E
Adder
2.9682352941176472.523
939411AE1-173 C
50/50
144.742144.742
938532AE1-072 E
50/50
12.39212.392
927264AC1-222 E
Adder
5.0905882352941184.327
3152411Z1-086 GT1
50/50
17.34217.342
3152421Z1-086 GT2
50/50
17.33717.337
943461AF1-017 C
Adder
1.71411764705882371.457
316311AC2-079 C
Adder
7.3223529411764716.224
932596AC2-079 E
Adder
11.94588235294117610.154
927021AC1-189 C
Adder
11.2564705882352949.568
926071AC1-086 C
Adder
28.2376470588235324.002
924152AB2-059 E OP
Adder
7.0388235294117655.983
946281AF1-292 C
Adder
2.0682352941176471.758
960082AF2-299 E
Adder
1.66588235294117641.416
916042Z1-036 E
Adder
38.52941176470588432.75
923832AB2-022 E
Adder
1.67529411764705881.424
964241AG1-285 C
Adder
14.8776470588235312.646
962561AG1-105 C
Adder
11.1211764705882359.453
938772AE1-103 E
Adder
5.3788235294117654.572
963042AG1-153 E
50/50
13.7613.76
944592AF1-124 E
50/50
143.351143.351
944582AF1-123 E
50/50
142.834142.834
3151091ELIZAR2
50/50
4.2124.212
316349AD2-085 C
Adder
4.3705882352941173.715
935112AD1-144 E
Adder
1.21411764705882351.032
961942AG1-037 E
Adder
0.451764705882352960.384
961941AG1-037 C
Adder
0.6764705882352940.575
927022AC1-189 E
Adder
5.6070588235294124.766
934322AD1-056 E
Adder
4.5447058823529413.863
934332AD1-057 E
Adder
2.43411764705882352.069
934321AD1-056 C
Adder
8.3788235294117657.122
934331AD1-057 C
Adder
4.6741176470588233.973
925595AC1-034 E
Adder
6.6764705882352945.675
923852AB2-025 E
50/50
1.6041.604
3151531CLOVER1
50/50
18.02218.022
941031AE2-094 C
50/50
66.68466.684
941032AE2-094 E
50/50
29.86629.866
939412AE1-173 E
50/50
96.49596.495
3151081ELIZAR1
50/50
4.2884.288
926662AC1-147 E
Adder
1.77411764705882361.508
916192Z1-068 E
50/50
2.5342.534
957492AF2-043 E
Adder
1.9105882352941181.624
943172AE2-346 E
Adder
0.81176470588235290.69
917332KELFORD E
Adder
2.2035294117647061.873
925122AB2-169 E
Adder
7.7223529411764716.564
934522AD1-076 E
Adder
8.397647058823537.138
940492AE2-034 E
Adder
4.1541176470588243.531
316274AC1-208 C
Adder
12.05058823529411810.243
962571AG1-106 C
Adder
3.6529411764705883.105
917342Z2-044 E
Adder
0.79764705882352950.678
3151311EDGECMA
Adder
20.6976470588235317.593
918492AA1-063AE OP
Adder
5.4552941176470594.637
957871AF2-081 C
50/50
13.52313.523
937482AD2-202 E
50/50
1.5031.503
3145506HICKORY
50/50
2.9532.953
933292AC2-141 E
50/50
18.00718.007
934576AD1-082 E
Adder
5.2247058823529414.441
944602AF1-125 E
50/50
140.592140.592
943612AF1-032 E
Adder
1.24117647058823531.055
926206AC1-098 E
Adder
4.8835294117647064.151
964791AG1-342 C
Adder
4.4517647058823523.784
901082W1-029 E
Adder
42.9564705882352936.513
3143316POE
Adder
1.6082352941176471.367
939191AE1-149 C
Adder
12.10588235294117610.29
957862AF2-080 E
Adder
4.53176470588235253.852
926072AC1-086 E
Adder
12.85176470588235310.924
960081AF2-299 C
Adder
2.4988235294117652.124
3145413WATKINS
Adder
0.92117647058823540.783
962562AG1-105 E
Adder
7.41411764705882356.302
938771AE1-103 C
Adder
3.8941176470588243.31
963041AG1-153 C
50/50
9.1739.173
3151051BRUNSWICKS1
50/50
28.03428.034
944011AF1-069 C
50/50
21.78821.788
944591AF1-124 C
50/50
62.59862.598
944601AF1-125 C
50/50
61.41561.415
3151101ELIZAR3
50/50
4.3424.342
941591AE2-156 C
50/50
24.00724.007
936666AD2-085 E
Adder
7.1317647058823546.062
933981AD1-022 C
Adder
11.78823529411764610.02
900672V4-068 E
Adder
0.47764705882352950.406
938531AE1-072 C
50/50
23.77123.771
924302AB2-077 E O1
Adder
1.6447058823529411.398
3145393UNCAMP
Adder
8.0941176470588236.88
932046AC2-012 E
50/50
17.5517.55
958161AF2-110 C
Adder
1.8117647058823531.54
933982AD1-022 E
Adder
6.417647058823535.455
3145946PLYMOUTH TP
Adder
0.435294117647058830.37
927146AC1-208 E
Adder
5.3517647058823544.549
316017AA1-139 ULT1
50/50
1.4591.459
927255AC1-221 E
Adder
4.84941176470588254.122
934612AD1-087 E
50/50
5.1365.136
934611AD1-087 C
50/50
1.7741.774
934622AD1-088 E
50/50
6.3856.385
3152431Z1-086 GT3
50/50
17.33717.337
940641AE2-051 C
50/50
28.87528.875
316084AB2-161 E
Adder
6.5576470588235295.574
934521AD1-076 C
Adder
16.4752941176470614.004
934511AD1-075 C
Adder
11.3411764705882369.64
919692AA2-053 E OP
Adder
5.65176470588235354.804
316263AC1-034 C
Adder
8.8505882352941177.523
923573AB1-173 E OP
Adder
4.3858823529411773.728
3145723EMPORIA
Adder
0.57647058823529410.49
920042AA2-088 E OP
Adder
14.1647058823529412.04
925785AC1-054 E
Adder
4.5188235294117653.841
919152AA1-139 E1
50/50
5.535.53
937481AD2-202 C
50/50
0.5150.515
3151031BRUNSWICKG2
50/50
13.49313.493
942342AE2-247 E
Adder
2.61647058823529432.224
957861AF2-080 C
Adder
10.2235294117647058.69
917512Z2-088 E OP1
Adder
6.54705882352941255.565
946282AF1-292 E
Adder
1.37882352941176461.172
316315AB2-025 C
50/50
0.5620.562
3151541CLOVER2
50/50
17.85317.853
944012AF1-069 E
50/50
8.4648.464
316316AC1-027 C
50/50
0.4240.424
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.25255.252
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.53435.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.5866.586
LAGNLTFEXP_LAGN->PJM
CLTF
11.79711.797
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6257.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
136.078136.078
CPLELTFEXP_CPLE->PJM
CLTF
15.98515.985
TVALTFEXP_TVA->PJM
CLTF
9.3529.352
O66PJM->LTFIMP_O-066
CMTX_NF
36.00236.002
G-007PJM->LTFIMP_G-007
CMTX_NF
5.665.66
SIGELTFEXP_SIGE->PJM
CLTF
0.4160.416
NYPJM->LTFIMP_NY
CLTF
2.5842.584
LGEELTFEXP_LGEE->PJM
CLTF
2.1892.189
WECLTFEXP_WEC->PJM
CLTF
1.1371.137

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.8 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3342.68
MW Contribution:3.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.2980.298
961941AG1-037 C
80/20
0.6730.673
3151391GASTONA
80/20
4.0664.066
934321AD1-056 C
Adder
8.332941176470597.083
934331AD1-057 C
Adder
4.6482352941176473.951
958211AF2-115 C
Adder
2.28235294117647051.94
3151531CLOVER1
80/20
17.9517.95
941031AE2-094 C
80/20
66.45566.455
3151081ELIZAR1
80/20
4.2584.258
3151381ROSEMG2
80/20
1.271.27
960081AF2-299 C
80/20
2.4842.484
936171AD2-023 C
Adder
5.5152941176470584.688
936261AD2-033 C
Adder
14.72470588235294112.516
961791AG1-021 C
Adder
1.82588235294117651.552
316365AB2-100 C1
80/20
1.2911.291
3156083AA2-088SOLA
80/20
1.4051.405
957481AF2-042 C
80/20
78.71578.715
940431AE2-027 C
Adder
11.395294117647069.686
316294AC1-161 C
80/20
6.8246.824
944581AF1-123 C
80/20
61.95761.957
316185AD1-033 C
80/20
1.6481.648
916191Z1-068 C
80/20
0.0580.058
941101AE2-104 C
80/20
4.4074.407
315614AA2-178 C
80/20
2.0912.091
3151411GASTONB
80/20
4.0664.066
316181AB2-040 GEN
80/20
1.6831.683
3147043LAWRENC
80/20
0.3980.398
940481AE2-033 C
80/20
22.18122.181
940541AE2-040 C
80/20
3.9443.944
3152441Z1-086 ST
80/20
30.08130.081
961611AG1-000B C
Adder
17.0670588235294114.507
316375AC2-012 C
80/20
1.7911.791
316072AD1-144 C
80/20
0.3590.359
316210AC1-098 C
80/20
1.251.25
316318V4-068 C
80/20
0.1070.107
313506AB1-173 C OP
80/20
1.4941.494
966621AG1-532 C
80/20
1.8631.863
316320Y1-086 C
80/20
0.2940.294
316388AE2-253 GEN
80/20
2.6322.632
936161AD2-022 C
Adder
9.455294117647068.037
935171AD1-152 C
80/20
1.8271.827
3151021BRUNSWICKG1
80/20
13.44613.446
3151041BRUNSWICKG3
80/20
13.44613.446
942341AE2-247 C
80/20
1.881.88
316246AF1-032 C
80/20
0.3780.378
932631AC2-084 C
80/20
1.3311.331
316274AC1-208 C
80/20
11.98411.984
962571AG1-106 C
80/20
3.6323.632
3151311EDGECMA
Adder
20.58941176470588317.501
957871AF2-081 C
80/20
13.4313.43
934521AD1-076 C
80/20
16.37216.372
934511AD1-075 C
80/20
11.2711.27
316212AC1-099 C
80/20
0.4180.418
316263AC1-034 C
Adder
8.8035294117647057.483
3156073AA1-063SOLA
80/20
1.8611.861
316087AB2-174 C
80/20
1.561.56
316321Z2-027 C
80/20
0.4860.486
959311AF2-222 C
Adder
18.28823529411764815.545
937481AD2-202 C
80/20
0.5130.513
3151031BRUNSWICKG2
80/20
13.44613.446
316036AC1-147 C
80/20
0.4890.489
316305AF2-043 C
80/20
0.4630.463
938771AE1-103 C
80/20
3.8693.869
963041AG1-153 C
80/20
9.1419.141
3151051BRUNSWICKS1
80/20
27.93627.936
944011AF1-069 C
80/20
21.71321.713
944591AF1-124 C
80/20
62.17762.177
944601AF1-125 C
80/20
61.00261.002
3151101ELIZAR3
80/20
4.3114.311
941591AE2-156 C
80/20
23.83823.838
934501AD1-074 C
80/20
45.0845.08
961671AG1-007 C
Adder
1.2482352941176471.061
940491AE2-034 C
80/20
1.5381.538
3156116Z1-036WIND
80/20
0.8770.877
946301AF1-294 C
Adder
3.75411764705882333.191
934621AD1-088 C
80/20
13.20613.206
942001AE2-212 C
Adder
2.11411764705882371.797
316140AB2-099 C
80/20
0.1280.128
3152921DOMTR78
80/20
1.8181.818
316018AA1-139 ULT2
80/20
1.4491.449
933291AC2-141 C
80/20
41.90441.904
3150921YORKTN3
Adder
127.84235294117647108.666
3151261ROARAP2
80/20
1.8341.834
3156056W1-029WIND
80/20
1.0361.036
3152411Z1-086 GT1
80/20
17.28117.281
3152421Z1-086 GT2
80/20
17.27717.277
943461AF1-017 C
80/20
1.7011.701
316311AC2-079 C
80/20
7.2667.266
3156021HOLLOMANSOL
80/20
2.4482.448
316011AB1-132 C OP
80/20
3.1053.105
3151371ROSEMS1
80/20
1.681.68
3137643SOCKMAN
80/20
0.9470.947
939411AE1-173 C
80/20
144.1144.1
3150991CHESPKB
80/20
0.9580.958
933981AD1-022 C
80/20
11.71411.714
316174AB2-169_C
80/20
1.3931.393
3156063AA2-053SOLA
80/20
1.9981.998
3151281ROARAP4
80/20
1.7351.735
938531AE1-072 C
80/20
23.60823.608
935161AD1-151 C
Adder
15.27058823529411812.98
958161AF2-110 C
80/20
1.7981.798
927021AC1-189 C
Adder
11.1952941176470599.516
926071AC1-086 C
80/20
28.07728.077
946281AF1-292 C
80/20
2.0562.056
964241AG1-285 C
Adder
14.80352941176470712.583
962561AG1-105 C
Adder
11.0694117647058839.409
3151091ELIZAR2
80/20
4.1834.183
316349AD2-085 C
80/20
4.3374.337
3151361ROSEMG1
80/20
2.7122.712
3151151S HAMPT1
80/20
1.9741.974
964791AG1-342 C
Adder
4.4317647058823533.767
939191AE1-149 C
Adder
11.99058823529411710.192
3150981CHESPKA
80/20
0.5780.578
313526AB2-022 C
80/20
0.5040.504
316017AA1-139 ULT1
80/20
1.4491.449
934611AD1-087 C
80/20
1.7671.767
3152431Z1-086 GT3
80/20
17.27717.277
940641AE2-051 C
80/20
28.76428.764
3152331SURRY 2
80/20
30.82730.827
316317KELFORD C
80/20
0.4760.476
957861AF2-080 C
Adder
10.167058823529418.642
316023AB2-100 C2
80/20
1.2911.291
316129AC1-054 C
80/20
1.5891.589
316315AB2-025 C
80/20
0.5580.558
3138533PONTONDP
Adder
0.6764705882352940.575
3151541CLOVER2
80/20
17.78217.782
316316AC1-027 C
80/20
0.4210.421
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.0655.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.38335.383
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.566.56
LAGNLTFEXP_LAGN->PJM
CLTF
11.74411.744
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.597.59
CBM South 2LTFEXP_CBM-S2->PJM
CBM
135.46135.46
CPLELTFEXP_CPLE->PJM
CLTF
15.91315.913
TVALTFEXP_TVA->PJM
CLTF
9.319.31
SIGELTFEXP_SIGE->PJM
CLTF
0.4150.415
NYPJM->LTFIMP_NY
CLTF
2.5592.559
LGEELTFEXP_LGEE->PJM
CLTF
2.182.18
WECLTFEXP_WEC->PJM
CLTF
1.1331.133

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.31 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:3793.69
MW Contribution:5.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
53.8447058823529445.768
924517AB2-100 E2
Adder
3.87764705882352923.296
3156116Z1-036WIND
50/50
1.1111.111
937226AE2-253 E
50/50
10.53510.535
3141813NORNECK
Adder
1.24235294117647071.056
962861AG1-135 C
Adder
8.9694117647058827.624
939192AE1-149 E
Adder
9.628.177
943741AF1-042 C
Adder
4.3658823529411773.711
939312AE1-162 E
50/50
2.4312.431
934065AD1-033 E
50/50
9.1079.107
3137643SOCKMAN
Adder
0.96588235294117640.821
913392Y1-086 E
50/50
3.893.89
316078AC2-138 E
Adder
1.30588235294117671.11
958262AF2-120 E
Adder
6.1329411764705885.213
966661AG1-536 C
Adder
7.9129411764705886.726
939612AE1-191 E
Adder
8.9247058823529427.586
957602AF2-054 E
Adder
2.24117647058823531.905
939411AE1-173 C
50/50
144.69144.69
934012AD1-025 E
Adder
14.63647058823529612.441
3151161SURRY 1
50/50
40.01440.014
3150991CHESPKB
50/50
1.3041.304
920692AA2-178 E
Adder
6.7435294117647065.732
961942AG1-037 E
Adder
0.50470588235294120.429
961941AG1-037 C
Adder
0.75764705882352950.644
923852AB2-025 E
Adder
1.53294117647058831.303
941031AE2-094 C
Adder
55.5058823529411847.18
941032AE2-094 E
Adder
24.8621.131
316076AC2-137 E
Adder
1.77294117647058821.507
964211AG1-282 C
Adder
2.87176470588235282.441
923842AB2-024 E
Adder
2.84000000000000032.414
316157AD2-030 E
Adder
1.88588235294117661.603
939412AE1-173 E
50/50
96.4696.46
3151081ELIZAR1
50/50
5.7935.793
926662AC1-147 E
50/50
2.3992.399
916192Z1-068 E
50/50
3.4083.408
957492AF2-043 E
50/50
2.5222.522
918512AA1-065 E OP
Adder
8.4494117647058827.182
934502AD1-074 E
Adder
27.4094117647058823.298
934512AD1-075 E
Adder
6.8529411764705895.825
924516AB2-100 E1
Adder
3.87764705882352923.296
316320Y1-086 C
50/50
0.3880.388
919153AA1-139 E2
50/50
7.3487.348
316388AE2-253 GEN
50/50
3.5313.531
940642AE2-051 E
50/50
17.58317.583
963612AG1-210 E
Adder
1.39882352941176481.189
316159AE1-175 C
50/50
0.7040.704
942341AE2-247 C
Adder
2.40705882352941152.046
943462AF1-017 E
Adder
3.55294117647058853.02
958162AF2-110 E
50/50
3.7353.735
316246AF1-032 C
50/50
0.5030.503
926071AC1-086 C
Adder
28.7023529411764724.397
916042Z1-036 E
50/50
48.46248.462
923832AB2-022 E
50/50
2.1962.196
938772AE1-103 E
Adder
6.6011764705882355.611
963042AG1-153 E
Adder
11.4941176470588249.77
316169AC1-164 GEN
50/50
65.01265.012
944592AF1-124 E
50/50
192.429192.429
944582AF1-123 E
50/50
191.735191.735
3151091ELIZAR2
50/50
5.6915.691
316349AD2-085 C
Adder
5.5541176470588244.721
935112AD1-144 E
50/50
1.661.66
901082W1-029 E
50/50
55.655.6
958261AF2-120 C
Adder
9.1988235294117657.819
939191AE1-149 C
Adder
14.42941176470588312.265
934146AD1-041 E
Adder
5.5776470588235294.741
957601AF2-054 C
Adder
3.36117647058823542.857
316382AG1-145 C
50/50
0.6360.636
3150981CHESPKA
50/50
0.7870.787
943172AE2-346 E
Adder
0.90941176470588240.773
917332KELFORD E
Adder
2.42.04
925122AB2-169 E
Adder
8.6941176470588237.39
934522AD1-076 E
Adder
9.9670588235294128.472
940492AE2-034 E
Adder
5.057647058823534.299
962571AG1-106 C
Adder
3.71294117647058863.156
918492AA1-063AE OP
Adder
5.82352941176470654.95
957871AF2-081 C
50/50
17.9717.97
3145506HICKORY
50/50
3.9493.949
936591AD2-074 C
Adder
8.3435294117647067.092
3130536PAPERMILL
Adder
10.4988235294117648.924
939602AE1-190 E
Adder
2.23058823529411751.896
933292AC2-141 E
50/50
25.37725.377
934576AD1-082 E
Adder
6.4070588235294125.446
944602AF1-125 E
50/50
188.725188.725
943612AF1-032 E
50/50
1.6391.639
926072AC1-086 E
Adder
13.06352941176470511.104
960081AF2-299 C
Adder
2.12235294117647081.804
3145413WATKINS
Adder
1.09647058823529430.932
938771AE1-103 C
Adder
4.7799999999999994.063
963041AG1-153 C
Adder
7.662352941176476.513
944011AF1-069 C
Adder
18.13647058823529415.416
3150601CHESTF5
Adder
80.1388235294117768.118
964212AG1-282 E
Adder
1.91529411764705881.628
925332AB2-190 E
Adder
11.1811764705882369.504
962962AG1-145 E
50/50
2.6032.603
927226AC1-216 E
Adder
11.3047058823529419.609
944591AF1-124 C
50/50
84.02984.029
944601AF1-125 C
50/50
82.44182.441
3151101ELIZAR3
50/50
5.8665.866
941591AE2-156 C
50/50
32.45632.456
936666AD2-085 E
Adder
9.0611764705882357.702
933981AD1-022 C
Adder
13.8411.764
900672V4-068 E
Adder
0.53882352941176470.458
938531AE1-072 C
50/50
31.50731.507
3145393UNCAMP
Adder
9.815294117647068.343
935161AD1-151 C
Adder
22.94117647058823619.5
932046AC2-012 E
50/50
23.72823.728
958161AF2-110 C
50/50
2.3482.348
933982AD1-022 E
Adder
7.5341176470588246.404
3145946PLYMOUTH TP
Adder
0.51882352941176470.441
313526AB2-022 C
50/50
0.6650.665
316017AA1-139 ULT1
50/50
1.9391.939
940641AE2-051 C
50/50
26.37426.374
926785AC1-164_E
50/50
29.20829.208
943471AF1-018 C
Adder
11.3211764705882359.623
934521AD1-076 C
Adder
19.5552941176470616.622
934511AD1-075 C
Adder
13.46117647058823511.442
919692AA2-053 E OP
Adder
5.8800000000000014.998
923573AB1-173 E OP
Adder
4.3988235294117643.739
3145723EMPORIA
Adder
0.57058823529411760.485
920042AA2-088 E OP
Adder
16.1705882352941213.745
316321Z2-027 C
50/50
0.6380.638
919152AA1-139 E1
50/50
7.3487.348
939246AE1-155 E
Adder
12.80941176470588310.888
924814AB2-134 E
Adder
18.51882352941176515.741
316036AC1-147 C
50/50
0.6650.665
942342AE2-247 E
Adder
3.3247058823529412.826
316305AF2-043 C
50/50
0.6160.616
316141AB2-099 E
Adder
0.37882352941176470.322
923994AB2-040_E
Adder
8.2482352941176477.011
316088AB2-174 E
Adder
8.6929411764705897.389
966662AG1-536 E
Adder
10.6329411764705889.038
962862AG1-135 E
Adder
5.985.083
943742AF1-042 E
Adder
7.1235294117647056.055
934392AD1-063 E
Adder
1.69764705882352951.443
316294AC1-161 C
50/50
9.6819.681
944581AF1-123 C
50/50
83.73183.731
316185AD1-033 C
50/50
2.2242.224
916191Z1-068 C
50/50
0.0790.079
941101AE2-104 C
50/50
5.7555.755
3152331SURRY 2
50/50
52.5452.54
923263AB1-132 E OP
Adder
8.3529411764705897.1
940481AE2-033 C
Adder
21.4117647058823518.2
940482AE2-033 E
Adder
14.43529411764705912.27
940541AE2-040 C
Adder
3.79058823529411763.222
3138116ELKO L286
Adder
1.84941176470588251.572
963611AG1-210 C
Adder
0.93294117647058830.793
957831AF2-077 C
50/50
0.570.57
961611AG1-000B C
Adder
25.22588235294117721.442
316375AC2-012 C
50/50
2.4382.438
316072AD1-144 C
50/50
0.4940.494
962572AG1-106 E
Adder
1.62470588235294121.381
957872AF2-081 E
50/50
7.7017.701
316018AA1-139 ULT2
50/50
1.9391.939
944631AF1-128 C
Adder
50.1435294117647142.622
936592AD2-074 E
Adder
13.61411764705882311.572
316160AE1-175 E
50/50
2.1482.148
926755AC1-161 E
50/50
25.37725.377
933291AC2-141 C
50/50
59.4559.45
3150921YORKTN3
50/50
222.183222.183
925522AC1-027 E
50/50
2.2062.206
941102AE2-104 E
50/50
9.159.15
3145256KINGFORK
50/50
1.7881.788
944012AF1-069 E
Adder
7.04588235294117655.989
961952AG1-038 E
Adder
6.66352941176470555.664
961951AG1-038 C
Adder
4.8258823529411774.102
925865AC1-065 E
Adder
25.8294117647058821.955
3144216WINCHST
50/50
0.2410.241
316316AC1-027 C
50/50
0.5710.571
917122Z2-027 E
50/50
2.3642.364
3146326AYDLETT TAP
50/50
2.4292.429
938532AE1-072 E
50/50
16.42416.424
3156056W1-029WIND
50/50
1.351.35
940551AE2-041 C
Adder
11.3211764705882359.623
935162AD1-151 E
Adder
15.29411764705882413
957832AF2-077 E
50/50
2.4692.469
943461AF1-017 C
Adder
2.17764705882352951.851
316311AC2-079 C
Adder
9.3282352941176477.929
932596AC2-079 E
Adder
15.21999999999999912.937
316084AB2-161 E
Adder
8.0411764705882356.835
316236AE1-162 C
50/50
0.5940.594
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.41628.416
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.24623.246
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.853.85
LAGNLTFEXP_LAGN->PJM
CLTF
8.2678.267
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.5566.556
CBM South 2LTFEXP_CBM-S2->PJM
CBM
111.34111.34
CPLELTFEXP_CPLE->PJM
CLTF
13.75813.758
TVALTFEXP_TVA->PJM
CLTF
6.4816.481
O66PJM->LTFIMP_O-066
CMTX_NF
27.4327.43
G-007PJM->LTFIMP_G-007
CMTX_NF
4.3044.304
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
NYPJM->LTFIMP_NY
CLTF
2.0382.038
LGEELTFEXP_LGEE->PJM
CLTF
1.1621.162
WECLTFEXP_WEC->PJM
CLTF
0.5990.599

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.92 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4555.56
MW Contribution:4.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.82117647058823530.698
934321AD1-056 C
Adder
9.6541176470588248.206
934331AD1-057 C
Adder
5.3847058823529414.577
941031AE2-094 C
Adder
59.24117647058823650.355
3150831SPRUNCA
Adder
15.78000000000000113.413
3150841SPRUNCB
Adder
15.78000000000000113.413
966871AG1-558 C
Adder
4.0835294117647063.471
316075AC2-137 C
80/20
0.6870.687
964211AG1-282 C
Adder
2.9811764705882352.534
3150801HOPHCF4
80/20
6.5586.558
316369AC1-216 C
80/20
2.8462.846
960081AF2-299 C
Adder
2.92.465
936261AD2-033 C
Adder
18.25529411764705815.517
938771AE1-103 C
Adder
4.9788235294117654.232
963041AG1-153 C
Adder
8.3011764705882357.056
944011AF1-069 C
Adder
19.35647058823529316.453
3150621CHESTS7
80/20
3.1823.182
3150601CHESTF5
80/20
113.981113.981
944591AF1-124 C
Adder
80.4988235294117868.424
944601AF1-125 C
Adder
78.9788235294117767.132
941591AE2-156 C
Adder
31.64823529411764726.901
957481AF2-042 C
Adder
77.7682352941176466.103
940431AE2-027 C
Adder
22.58000000000000219.193
3150681DARBY 2
80/20
4.5764.576
316294AC1-161 C
80/20
8.8498.849
944581AF1-123 C
Adder
80.2141176470588368.182
941101AE2-104 C
Adder
5.8423529411764714.966
940481AE2-033 C
Adder
25.6411764705882421.795
940541AE2-040 C
Adder
4.5529411764705883.87
927041AC1-191 C
Adder
16.39529411764705813.936
963611AG1-210 C
Adder
0.95764705882352940.814
961611AG1-000B C
80/20
28.34928.349
966621AG1-532 C
Adder
2.1752941176470591.849
3150771HOPHCF1
80/20
4.324.32
316159AE1-175 C
80/20
0.7120.712
942341AE2-247 C
Adder
2.5964705882352942.207
316274AC1-208 C
Adder
14.04588235294117711.939
962571AG1-106 C
Adder
4.2647058823529413.625
3151311EDGECMA
Adder
23.6270588235294120.083
957871AF2-081 C
Adder
17.51647058823529314.889
3150651CHESTF6
Adder
32.7447058823529427.833
936591AD2-074 C
Adder
8.7058823529411787.4
316033AB2-134 GEN
80/20
3.7293.729
934011AD1-025 C
80/20
4.6114.611
934521AD1-076 C
Adder
20.41647058823529517.354
934511AD1-075 C
Adder
14.05411764705882411.946
316263AC1-034 C
Adder
10.102352941176478.587
316240AF1-291 C
Adder
3.78000000000000023.213
944641AF1-129 C
Adder
179.8423529411765152.866
3142296MT RD221
80/20
0.2170.217
316004AC1-112 C
80/20
0.5960.596
3150781HOPHCF2
80/20
4.324.32
3150761HOPPOLC
80/20
2.7172.717
927021AC1-189 C
Adder
13.13058823529411811.161
926071AC1-086 C
Adder
32.9752941176470628.029
946281AF1-292 C
Adder
2.40117647058823552.041
964241AG1-285 C
Adder
17.71058823529411815.054
316169AC1-164 GEN
80/20
73.90473.904
316349AD2-085 C
Adder
5.9917647058823535.093
934501AD1-074 C
Adder
56.2176470588235347.785
961671AG1-007 C
Adder
1.44941176470588241.232
934621AD1-088 C
Adder
13.69294117647058911.639
942001AE2-212 C
Adder
3.73882352941176473.178
3150671DARBY 1
80/20
4.574.57
3150641CHESTS8
80/20
3.5113.511
962861AG1-135 C
Adder
9.3188235294117667.921
943741AF1-042 C
Adder
4.5552941176470593.872
944631AF1-128 C
80/20
71.31971.319
933291AC2-141 C
80/20
54.34454.344
3150921YORKTN3
80/20
215.99215.99
3151191GRAVEL3
80/20
4.4484.448
316233AE1-074 C
Adder
4.08588235294117653.473
3150691DARBY 3
80/20
4.5924.592
940551AE2-041 C
Adder
12.16117647058823610.337
943461AF1-017 C
Adder
2.34941176470588251.997
316311AC2-079 C
Adder
9.984705882352948.487
3137643SOCKMAN
Adder
1.1117647058823530.945
316312AB1-027 C
80/20
0.9570.957
966661AG1-536 C
Adder
8.2105882352941186.979
939411AE1-173 C
Adder
145.74235294117648123.881
3151161SURRY 1
80/20
43.78743.787
933981AD1-022 C
Adder
14.54588235294117712.364
938531AE1-072 C
Adder
30.76823529411764526.153
3142366NRTHEST
80/20
0.330.33
3150701DARBY 4
80/20
4.5974.597
3150731STONECA
80/20
12.27512.275
935161AD1-151 C
80/20
28.71928.719
958161AF2-110 C
Adder
2.38352941176470572.026
3143096IRON208
80/20
0.7870.787
958261AF2-120 C
Adder
9.5447058823529418.113
939191AE1-149 C
Adder
18.60588235294117615.815
957601AF2-054 C
Adder
3.56235294117647073.028
316132AB2-190 C
80/20
7.3677.367
316382AG1-145 C
80/20
0.6420.642
957861AF2-080 C
Adder
11.92588235294117810.137
3150631CHESTG8
80/20
6.826.82
3150611CHESTG7
80/20
6.936.93
3150791HOPHCF3
80/20
4.324.32
961951AG1-038 C
Adder
5.035294117647064.28
3144216WINCHST
80/20
0.2370.237
316336AC2-165 C
Adder
13.90823529411764711.822
940641AE2-051 C
Adder
26.97529411764705622.929
943471AF1-018 C
Adder
12.16117647058823610.337
3152331SURRY 2
80/20
45.81645.816
3151201GRAVEL4
80/20
4.5054.505
3151221GRAVEL6
80/20
4.54.5
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.27284.272
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.64648.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5619.561
LAGNLTFEXP_LAGN->PJM
CLTF
15.45715.457
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4058.405
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.686156.686
CPLELTFEXP_CPLE->PJM
CLTF
17.60717.607
TVALTFEXP_TVA->PJM
CLTF
12.412.4
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62
NYPJM->LTFIMP_NY
CLTF
4.1344.134
LGEELTFEXP_LGEE->PJM
CLTF
3.3563.356
WECLTFEXP_WEC->PJM
CLTF
1.7261.726

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.48 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5586.28
MW Contribution:6.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.410588235294117640.349
923994AB2-040_E
Adder
9.5835294117647068.146
316088AB2-174 E
Adder
10.1435294117647078.622
957481AF2-042 C
Adder
64.6541176470588354.956
942002AE2-212 E
Adder
2.49058823529411782.117
940431AE2-027 C
Adder
22.57058823529411719.185
3150681DARBY 2
50/50
4.5734.573
943742AF1-042 E
Adder
7.42705882352941156.313
934392AD1-063 E
Adder
1.8235294117647061.55
944581AF1-123 C
Adder
80.1835294117647168.156
941101AE2-104 C
Adder
5.8411764705882354.965
923263AB1-132 E OP
Adder
9.595294117647068.156
940481AE2-033 C
Adder
25.63411764705882621.789
940482AE2-033 E
Adder
17.28117647058823514.689
940541AE2-040 C
Adder
4.5517647058823533.869
927041AC1-191 C
Adder
16.38352941176470513.926
3138116ELKO L286
50/50
2.5282.528
961611AG1-000B C
Adder
28.33647058823529424.086
962572AG1-106 E
Adder
1.86588235294117651.586
957872AF2-081 E
Adder
7.50470588235294046.379
938552AE1-074 E
Adder
2.05764705882352941.749
944631AF1-128 C
50/50
71.28371.283
936592AD2-074 E
Adder
14.19411764705882312.065
316160AE1-175 E
50/50
2.1682.168
926755AC1-161 E
Adder
23.1894117647058819.711
933291AC2-141 C
Adder
54.3223529411764746.174
3150921YORKTN3
Adder
215.8894117647059183.506
925522AC1-027 E
Adder
2.14588235294117661.824
941102AE2-104 E
Adder
9.2858823529411767.893
3145256KINGFORK
Adder
1.78823529411764711.52
934501AD1-074 C
Adder
56.2023529411764747.772
924517AB2-100 E2
Adder
4.5505882352941183.868
937226AE2-253 E
Adder
10.2482352941176478.711
942001AE2-212 C
Adder
3.73647058823529443.176
3150671DARBY 1
50/50
4.5674.567
3150641CHESTS8
50/50
3.5093.509
939192AE1-149 E
Adder
12.39882352941176410.539
943741AF1-042 C
Adder
4.5517647058823533.869
939312AE1-162 E
Adder
2.54117647058823562.16
934065AD1-033 E
Adder
8.8270588235294137.503
3137643SOCKMAN
Adder
1.1117647058823530.945
913392Y1-086 E
Adder
3.8282352941176473.254
940432AE2-027 E
Adder
15.04705882352941212.79
316312AB1-027 C
50/50
0.9560.956
939612AE1-191 E
Adder
9.628.177
957602AF2-054 E
Adder
2.37411764705882342.018
939411AE1-173 C
Adder
145.69882352941175123.844
934012AD1-025 E
Adder
17.78941176470588215.121
920692AA2-178 E
Adder
6.9352941176470585.895
966622AG1-532 E
Adder
1.45058823529411771.233
917122Z2-027 E
Adder
2.3352941176470591.985
3146326AYDLETT TAP
Adder
2.3717647058823532.016
938532AE1-072 E
Adder
16.0329411764705913.628
316233AE1-074 C
Adder
4.08588235294117653.473
927042AC1-191 E
Adder
8.1611764705882366.937
3150691DARBY 3
50/50
4.5894.589
940551AE2-041 C
Adder
12.15411764705882410.331
935162AD1-151 E
Adder
19.1376470588235316.267
957832AF2-077 E
Adder
2.49294117647058842.119
943461AF1-017 C
Adder
2.34941176470588251.997
316311AC2-079 C
Adder
9.9811764705882358.484
932596AC2-079 E
Adder
16.2847058823529413.842
961942AG1-037 E
Adder
0.54705882352941180.465
961941AG1-037 C
Adder
0.82117647058823530.698
923852AB2-025 E
Adder
1.84117647058823521.565
941031AE2-094 C
Adder
59.2294117647058850.345
941032AE2-094 E
Adder
26.52705882352941222.548
3150831SPRUNCA
Adder
15.77411764705882313.408
3150841SPRUNCB
Adder
15.77411764705882313.408
966872AG1-558 E
Adder
2.0552941176470591.747
966871AG1-558 C
Adder
4.083.468
316076AC2-137 E
50/50
2.4242.424
316075AC2-137 C
50/50
0.6870.687
923842AB2-024 E
Adder
3.07294117647058852.612
316157AD2-030 E
Adder
1.99764705882352931.698
939412AE1-173 E
Adder
97.132941176470682.563
926662AC1-147 E
Adder
2.34000000000000031.989
916192Z1-068 E
Adder
3.3141176470588242.817
957492AF2-043 E
Adder
2.48941176470588272.116
918512AA1-065 E OP
Adder
9.0517647058823547.694
934502AD1-074 E
Adder
28.60941176470588624.318
934512AD1-075 E
Adder
7.1529411764705896.08
924516AB2-100 E1
Adder
4.5505882352941183.868
966621AG1-532 C
Adder
2.1752941176470591.849
919153AA1-139 E2
Adder
7.166.086
940642AE2-051 E
Adder
17.97882352941176615.282
926412AC1-112 E
50/50
2.0462.046
316159AE1-175 C
50/50
0.7110.711
942341AE2-247 C
Adder
2.5964705882352942.207
943462AF1-017 E
Adder
3.8317647058823533.257
958162AF2-110 E
Adder
3.79058823529411763.222
926071AC1-086 C
Adder
32.9682352941176528.023
946281AF1-292 C
Adder
2.40117647058823552.041
960082AF2-299 E
Adder
1.93294117647058841.643
916042Z1-036 E
Adder
48.916470588235341.579
923832AB2-022 E
Adder
2.16117647058823531.837
938772AE1-103 E
Adder
6.8741176470588235.843
963042AG1-153 E
Adder
12.44941176470588410.582
930122AB1-027 E
50/50
2.5162.516
316169AC1-164 GEN
50/50
73.86273.862
944592AF1-124 E
Adder
184.2764705882353156.635
944582AF1-123 E
Adder
183.61176470588234156.07
316349AD2-085 C
Adder
5.9894117647058835.091
935112AD1-144 E
Adder
1.66000000000000011.411
901082W1-029 E
Adder
55.2529411764705946.965
3143316POE
Adder
2.31058823529411761.964
939191AE1-149 C
Adder
18.59882352941176415.809
934146AD1-041 E
Adder
6.0129411764705885.111
957601AF2-054 C
Adder
3.56117647058823563.027
316382AG1-145 C
50/50
0.6420.642
943172AE2-346 E
Adder
0.98588235294117640.838
917332KELFORD E
Adder
2.63882352941176462.243
925122AB2-169 E
Adder
9.3470588235294127.945
934522AD1-076 E
Adder
10.4035294117647078.843
940492AE2-034 E
Adder
5.2011764705882364.421
962571AG1-106 C
Adder
4.2647058823529413.625
918492AA1-063AE OP
Adder
6.5082352941176485.532
957871AF2-081 C
Adder
17.5105882352941214.884
3145506HICKORY
Adder
3.83058823529411763.256
946262AF1-291 E
Adder
2.5188235294117652.141
3150651CHESTF6
Adder
32.7305882352941227.821
936591AD2-074 C
Adder
8.77.395
3130536PAPERMILL
Adder
11.342352941176479.641
939602AE1-190 E
Adder
2.40470588235294122.044
933292AC2-141 E
Adder
23.1894117647058819.711
934576AD1-082 E
Adder
7.6470588235294126.5
944602AF1-125 E
Adder
180.73058823529414153.621
943612AF1-032 E
Adder
1.61764705882352941.375
926072AC1-086 E
Adder
15.0047058823529412.754
960081AF2-299 C
Adder
2.92.465
3145413WATKINS
Adder
1.15882352941176480.985
938771AE1-103 C
Adder
4.9776470588235294.231
963041AG1-153 C
Adder
8.37.055
944011AF1-069 C
Adder
19.35294117647058716.45
3150621CHESTS7
50/50
3.183.18
3150601CHESTF5
50/50
113.923113.923
925332AB2-190 E
Adder
14.35882352941176512.205
962962AG1-145 E
50/50
2.6282.628
927226AC1-216 E
Adder
13.74117647058823411.68
944591AF1-124 C
Adder
80.4682352941176568.398
944601AF1-125 C
Adder
78.9482352941176467.106
941591AE2-156 C
Adder
31.63647058823529426.891
936666AD2-085 E
Adder
9.7729411764705898.307
933981AD1-022 C
Adder
14.54117647058823512.36
900672V4-068 E
Adder
0.58235294117647060.495
938531AE1-072 C
Adder
30.75647058823529526.143
3145393UNCAMP
Adder
10.2788235294117658.737
3142366NRTHEST
50/50
0.330.33
3150701DARBY 4
50/50
4.5944.594
3150731STONECA
Adder
12.26941176470588210.429
935161AD1-151 C
Adder
28.70588235294117424.4
932046AC2-012 E
Adder
23.15176470588235319.679
958161AF2-110 C
Adder
2.38352941176470572.026
933982AD1-022 E
Adder
7.9164705882352956.729
3145946PLYMOUTH TP
Adder
0.540.459
940641AE2-051 C
Adder
26.96705882352941322.922
926785AC1-164_E
50/50
33.18433.184
943471AF1-018 C
Adder
12.15411764705882410.331
3152331SURRY 2
50/50
45.79645.796
316084AB2-161 E
Adder
9.597647058823538.158
934521AD1-076 C
Adder
20.41176470588235517.35
934511AD1-075 C
Adder
14.05058823529411811.943
919692AA2-053 E OP
Adder
6.6552941176470595.657
923573AB1-173 E OP
Adder
5.11176470588235254.345
3145723EMPORIA
Adder
0.66941176470588230.569
920042AA2-088 E OP
Adder
17.4414.824
919152AA1-139 E1
Adder
7.166.086
316240AF1-291 C
Adder
3.7788235294117653.212
944641AF1-129 C
Adder
179.7623529411765152.798
3142296MT RD221
50/50
0.2170.217
316004AC1-112 C
50/50
0.5960.596
924814AB2-134 E
Adder
22.5082352941176519.132
942342AE2-247 E
Adder
3.58470588235294143.047
946282AF1-292 E
Adder
1.61.36
944012AF1-069 E
Adder
7.5176470588235296.39
3150631CHESTG8
50/50
6.8166.816
3150611CHESTG7
50/50
6.9276.927
961952AG1-038 E
Adder
6.9482352941176475.906
961951AG1-038 C
Adder
5.0317647058823534.277
925865AC1-065 E
Adder
28.22117647058823723.988
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.33484.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.67448.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5679.567
LAGNLTFEXP_LAGN->PJM
CLTF
15.46415.464
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4068.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.721156.721
CPLELTFEXP_CPLE->PJM
CLTF
17.60917.609
TVALTFEXP_TVA->PJM
CLTF
12.40612.406
O66PJM->LTFIMP_O-066
CMTX_NF
58.60758.607
G-007PJM->LTFIMP_G-007
CMTX_NF
9.2239.223
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62
NYPJM->LTFIMP_NY
CLTF
4.1384.138
LGEELTFEXP_LGEE->PJM
CLTF
3.3583.358
WECLTFEXP_WEC->PJM
CLTF
1.7271.727

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4112.5
MW Contribution:3.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.69764705882352940.593
934321AD1-056 C
Adder
8.1541176470588246.931
934331AD1-057 C
Adder
4.5482352941176483.866
941031AE2-094 C
Adder
50.196470588235342.667
3150831SPRUNCA
Adder
10.6141176470588259.022
3150841SPRUNCB
Adder
10.6141176470588259.022
966871AG1-558 C
Adder
3.3847058823529412.877
316075AC2-137 C
80/20
0.5730.573
964211AG1-282 C
Adder
2.5270588235294122.148
316369AC1-216 C
80/20
2.3642.364
3151081ELIZAR1
80/20
4.8584.858
957481AF2-042 C
Adder
64.7188235294117655.011
3152191CUNINGD
80/20
17.70617.706
940431AE2-027 C
Adder
18.18117647058823715.454
316294AC1-161 C
80/20
7.7077.707
944581AF1-123 C
80/20
69.29269.292
316185AD1-033 C
80/20
1.8591.859
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
55
940481AE2-033 C
Adder
21.37647058823529618.17
940541AE2-040 C
Adder
3.7941176470588243.225
927041AC1-191 C
Adder
13.58823529411764911.55
963611AG1-210 C
Adder
0.81058823529411760.689
957831AF2-077 C
80/20
0.4940.494
961611AG1-000B C
80/20
23.84623.846
316375AC2-012 C
80/20
2.0492.049
316072AD1-144 C
80/20
0.4250.425
966621AG1-532 C
Adder
1.81764705882352941.545
316320Y1-086 C
80/20
0.3290.329
316388AE2-253 GEN
80/20
2.9612.961
316159AE1-175 C
80/20
0.6130.613
942341AE2-247 C
Adder
2.21.87
316246AF1-032 C
80/20
0.4270.427
934521AD1-076 C
Adder
17.4447058823529414.828
934511AD1-075 C
Adder
12.00823529411764810.207
316263AC1-034 C
Adder
8.5517647058823547.269
316321Z2-027 C
80/20
0.5420.542
316240AF1-291 C
Adder
3.02705882352941162.573
944641AF1-129 C
Adder
143.61529411764707122.073
3142296MT RD221
80/20
0.180.18
316004AC1-112 C
80/20
0.5060.506
316036AC1-147 C
80/20
0.5590.559
316305AF2-043 C
80/20
0.5230.523
960081AF2-299 C
Adder
2.4235294117647062.06
938771AE1-103 C
Adder
4.2458823529411773.609
963041AG1-153 C
Adder
7.0223529411764725.969
944011AF1-069 C
Adder
16.40117647058823613.941
3150621CHESTS7
80/20
2.5762.576
3150601CHESTF5
80/20
92.29692.296
944591AF1-124 C
80/20
69.53869.538
944601AF1-125 C
80/20
68.22568.225
3151101ELIZAR3
80/20
4.9194.919
941591AE2-156 C
80/20
27.25627.256
934501AD1-074 C
Adder
48.0341176470588340.829
961671AG1-007 C
Adder
1.22941176470588221.045
934621AD1-088 C
Adder
11.2658823529411789.576
942001AE2-212 C
Adder
3.01764705882352932.565
3150641CHESTS8
80/20
2.8432.843
962861AG1-135 C
Adder
7.9105882352941186.724
943741AF1-042 C
Adder
3.87058823529411773.29
316018AA1-139 ULT2
80/20
1.6281.628
3152181CUNINGC
80/20
7.9167.916
944631AF1-128 C
80/20
57.75157.751
933291AC2-141 C
80/20
47.32947.329
3150921YORKTN3
80/20
186.63186.63
3151191GRAVEL3
80/20
3.7583.758
940551AE2-041 C
Adder
10.3670588235294128.812
943461AF1-017 C
Adder
1.99058823529411751.692
316311AC2-079 C
Adder
8.4682352941176487.198
3137643SOCKMAN
Adder
0.93411764705882360.794
316312AB1-027 C
80/20
0.8120.812
966661AG1-536 C
Adder
6.96705882352941155.922
939411AE1-173 C
Adder
124.68470588235294105.982
3151161SURRY 1
80/20
36.99336.993
3150991CHESPKB
80/20
1.0961.096
927021AC1-189 C
Adder
11.1482352941176499.476
926071AC1-086 C
Adder
27.76352941176470823.599
946281AF1-292 C
Adder
2.00588235294117641.705
316169AC1-164 GEN
80/20
63.00863.008
3151091ELIZAR2
80/20
4.7734.773
316349AD2-085 C
Adder
5.0752941176470594.314
316274AC1-208 C
Adder
11.86588235294117810.086
962571AG1-106 C
Adder
3.5905882352941183.052
3151311EDGECMA
Adder
20.00352941176470617.003
957871AF2-081 C
80/20
15.09215.092
3150651CHESTF6
Adder
26.14823529411764722.226
936591AD2-074 C
Adder
7.3964705882352946.287
316033AB2-134 GEN
80/20
3.0983.098
934011AD1-025 C
80/20
3.8313.831
958261AF2-120 C
Adder
8.16.885
939191AE1-149 C
Adder
15.33294117647058713.033
957601AF2-054 C
Adder
3.03647058823529432.581
316382AG1-145 C
80/20
0.5540.554
3151171GRAVELC
80/20
1.2921.292
3150981CHESPKA
80/20
0.6610.661
933981AD1-022 C
Adder
12.41647058823529510.554
938531AE1-072 C
80/20
26.50226.502
3150731STONECA
Adder
9.9858823529411778.488
935161AD1-151 C
80/20
23.75423.754
958161AF2-110 C
80/20
2.042.04
313526AB2-022 C
80/20
0.5630.563
316017AA1-139 ULT1
80/20
1.6281.628
940641AE2-051 C
Adder
23.00823529411764719.557
943471AF1-018 C
Adder
10.3670588235294128.812
3152331SURRY 2
80/20
40.26840.268
3151201GRAVEL4
80/20
3.8063.806
3151211GRAVEL5
80/20
3.7583.758
3151221GRAVEL6
80/20
3.8023.802
316236AE1-162 C
80/20
0.5280.528
957861AF2-080 C
Adder
10.1247058823529418.606
3152161CUNINGA
80/20
7.9167.916
3152171CUNINGB
80/20
7.9167.916
3150631CHESTG8
80/20
5.5225.522
3150611CHESTG7
80/20
5.6125.612
961951AG1-038 C
Adder
4.277647058823533.636
3144216WINCHST
80/20
0.2040.204
316316AC1-027 C
80/20
0.4790.479
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.17274.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.32542.325
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.3698.369
LAGNLTFEXP_LAGN->PJM
CLTF
13.38813.388
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1467.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
133.887133.887
CPLELTFEXP_CPLE->PJM
CLTF
14.96914.969
TVALTFEXP_TVA->PJM
CLTF
10.74810.748
SIGELTFEXP_SIGE->PJM
CLTF
0.5440.544
NYPJM->LTFIMP_NY
CLTF
3.5973.597
LGEELTFEXP_LGEE->PJM
CLTF
2.952.95
WECLTFEXP_WEC->PJM
CLTF
1.5171.517

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.32 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3230.79
MW Contribution:2.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.41529411764705880.353
941031AE2-094 C
Adder
30.39411764705882425.835
3150391LDYSMT3
80/20
4.4174.417
3150831SPRUNCA
80/20
8.2198.219
3150841SPRUNCB
Adder
8.2188235294117656.986
966871AG1-558 C
80/20
2.1962.196
316075AC2-137 C
80/20
0.3470.347
964211AG1-282 C
Adder
1.65294117647058841.405
957481AF2-042 C
Adder
40.39647058823529634.337
3150401LDYSMT4
80/20
4.4254.425
940431AE2-027 C
Adder
11.5988235294117659.859
3150681DARBY 2
80/20
2.3542.354
944581AF1-123 C
Adder
39.80941176470588533.838
941101AE2-104 C
Adder
2.92000000000000042.482
940481AE2-033 C
Adder
13.13529411764705811.165
940541AE2-040 C
Adder
2.33294117647058831.983
3150371LDYSMT1
80/20
4.2494.249
927041AC1-191 C
80/20
8.8178.817
963611AG1-210 C
Adder
0.53882352941176470.458
961611AG1-000B C
Adder
14.23176470588235412.097
966621AG1-532 C
Adder
1.1164705882352940.949
3152261N ANNA2
80/20
26.0926.09
942341AE2-247 C
Adder
1.30470588235294121.109
960081AF2-299 C
Adder
1.48823529411764691.265
938771AE1-103 C
Adder
2.5011764705882352.126
963041AG1-153 C
Adder
4.2658823529411763.626
944011AF1-069 C
Adder
9.9305882352941198.441
966881AG1-559 C
80/20
2.2882.288
3150621CHESTS7
80/20
1.6141.614
3150601CHESTF5
80/20
57.83757.837
944591AF1-124 C
Adder
39.9505882352941233.958
944601AF1-125 C
Adder
39.1964705882352933.317
941591AE2-156 C
Adder
15.7305882352941213.371
934521AD1-076 C
Adder
10.2717647058823538.731
934511AD1-075 C
Adder
7.0705882352941176.01
3150411LDYSMT5
80/20
4.4394.439
316240AF1-291 C
Adder
1.94470588235294131.653
944641AF1-129 C
Adder
92.5282352941176578.649
3150451FOUR RIVERC
80/20
3.6073.607
3142296MT RD221
80/20
0.1140.114
316004AC1-112 C
80/20
0.3050.305
934501AD1-074 C
Adder
28.28352941176470724.041
934621AD1-088 C
Adder
7.1611764705882356.087
942001AE2-212 C
Adder
1.92117647058823531.633
3150671DARBY 1
80/20
2.3512.351
3150641CHESTS8
80/20
1.7811.781
962861AG1-135 C
Adder
5.0788235294117654.317
943741AF1-042 C
Adder
2.45411764705882352.086
3152251N ANNA1
80/20
26.07926.079
3150381LDYSMT2
80/20
4.3034.303
316233AE1-074 C
Adder
2.1552941176470591.832
3150691DARBY 3
80/20
2.3622.362
940551AE2-041 C
Adder
6.2364705882352955.301
943461AF1-017 C
Adder
1.18117647058823531.004
316311AC2-079 C
Adder
5.0141176470588234.262
3150471FOUR RIVERE
80/20
2.9092.909
315052AA1-145 CT2
80/20
4.74.7
3150851SPRUNCC
80/20
0.1470.147
944631AF1-128 C
80/20
36.1936.19
933291AC2-141 C
Adder
26.7822.763
3150921YORKTN3
Adder
107.0694117647058991.009
3137643SOCKMAN
Adder
0.56941176470588240.484
316312AB1-027 C
80/20
0.4890.489
966661AG1-536 C
Adder
4.4905882352941183.817
939411AE1-173 C
Adder
73.6611764705882562.612
926071AC1-086 C
Adder
16.83294117647058714.308
946281AF1-292 C
Adder
1.23176470588235291.047
939261AE1-157 C
80/20
13.3213.32
316169AC1-164 GEN
80/20
36.80636.806
316349AD2-085 C
Adder
3.0105882352941182.559
962571AG1-106 C
Adder
2.17764705882352951.851
957871AF2-081 C
Adder
8.7129411764705887.406
3150651CHESTF6
Adder
16.84705882352941214.32
3150461FOUR RIVERD
80/20
2.9092.909
3150441FOUR RIVERB
80/20
2.9522.952
3150861SPRUNCD
80/20
0.1470.147
936591AD2-074 C
Adder
4.6894117647058823.986
3143096IRON208
80/20
0.4040.404
958261AF2-120 C
Adder
5.2200000000000014.437
939191AE1-149 C
Adder
9.4788235294117668.057
957601AF2-054 C
Adder
1.83764705882352961.562
933981AD1-022 C
Adder
7.3258823529411776.227
938531AE1-072 C
Adder
15.30823529411764713.012
315051AA1-145 CT1
80/20
4.7034.703
3142366NRTHEST
80/20
0.1710.171
3150701DARBY 4
80/20
2.3652.365
3150731STONECA
Adder
6.2458823529411775.309
935161AD1-151 C
Adder
14.5176470588235312.34
958161AF2-110 C
Adder
1.19176470588235281.013
316336AC2-165 C
Adder
7.7411764705882356.58
3150481FOUR RIVERF
80/20
3.5533.553
940641AE2-051 C
Adder
13.71529411764705811.658
943471AF1-018 C
Adder
6.2364705882352955.301
3150431FOUR RIVERA
80/20
2.9522.952
3150631CHESTG8
80/20
3.4613.461
3150611CHESTG7
80/20
3.5173.517
961951AG1-038 C
Adder
2.7117647058823532.305
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.86545.865
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.97725.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.1595.159
LAGNLTFEXP_LAGN->PJM
CLTF
8.1928.192
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.3484.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.51781.517
CPLELTFEXP_CPLE->PJM
CLTF
9.1099.109
TVALTFEXP_TVA->PJM
CLTF
6.5746.574
SIGELTFEXP_SIGE->PJM
CLTF
0.3350.335
NYPJM->LTFIMP_NY
CLTF
2.8322.832
LGEELTFEXP_LGEE->PJM
CLTF
1.8211.821
WECLTFEXP_WEC->PJM
CLTF
0.9380.938

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.82 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3858.59
MW Contribution:3.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.74470588235294120.633
934321AD1-056 C
Adder
9.0458823529411777.689
934331AD1-057 C
Adder
5.04588235294117654.289
958211AF2-115 C
Adder
3.0058823529411772.555
3151531CLOVER1
80/20
18.57418.574
316258AE1-075 C
80/20
0.5130.513
941031AE2-094 C
80/20
63.15563.155
3150831SPRUNCA
80/20
13.15813.158
3150841SPRUNCB
80/20
13.15813.158
3151081ELIZAR1
80/20
4.824.82
960081AF2-299 C
Adder
2.74941176470588242.337
936261AD2-033 C
Adder
17.81058823529411615.139
961791AG1-021 C
Adder
2.40470588235294122.044
938771AE1-103 C
80/20
4.3814.381
963041AG1-153 C
80/20
8.7798.779
3151051BRUNSWICKS1
80/20
26.8326.83
944011AF1-069 C
80/20
20.63520.635
3150601CHESTF5
Adder
83.0647058823529570.605
944591AF1-124 C
80/20
69.22169.221
944601AF1-125 C
80/20
67.91467.914
3151101ELIZAR3
80/20
4.8814.881
941591AE2-156 C
80/20
27.03327.033
316365AB2-100 C1
80/20
1.4231.423
957481AF2-042 C
80/20
80.37380.373
940431AE2-027 C
Adder
18.39647058823529615.637
316294AC1-161 C
80/20
7.5057.505
944581AF1-123 C
80/20
68.97668.976
316185AD1-033 C
80/20
1.8511.851
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
5.0455.045
940481AE2-033 C
80/20
24.49624.496
940541AE2-040 C
80/20
4.3564.356
3152441Z1-086 ST
80/20
28.79528.795
961611AG1-000B C
Adder
22.90588235294117719.47
316375AC2-012 C
80/20
2.0322.032
316072AD1-144 C
80/20
0.4180.418
966621AG1-532 C
Adder
2.06235294117647071.753
316320Y1-086 C
80/20
0.330.33
316388AE2-253 GEN
80/20
2.9552.955
3151021BRUNSWICKG1
80/20
12.91412.914
3151041BRUNSWICKG3
80/20
12.91412.914
942341AE2-247 C
80/20
2.2382.238
316246AF1-032 C
80/20
0.4280.428
316274AC1-208 C
Adder
13.08588235294117711.123
962571AG1-106 C
Adder
3.98941176470588273.391
3151311EDGECMA
Adder
22.1658823529411818.841
957871AF2-081 C
80/20
15.07515.075
316405AF2-144 C
80/20
0.4360.436
3150651CHESTF6
Adder
26.27176470588235422.331
3150861SPRUNCD
80/20
0.2360.236
934521AD1-076 C
Adder
18.1705882352941215.445
934511AD1-075 C
Adder
12.50823529411764710.632
316263AC1-034 C
Adder
9.488.058
316321Z2-027 C
80/20
0.5460.546
959311AF2-222 C
Adder
22.66470588235294419.265
3151031BRUNSWICKG2
80/20
12.91412.914
316240AF1-291 C
Adder
3.0682352941176472.608
944641AF1-129 C
Adder
144.29529411764705122.651
316036AC1-147 C
80/20
0.5540.554
316305AF2-043 C
80/20
0.5240.524
927021AC1-189 C
Adder
12.14117647058823710.32
926071AC1-086 C
Adder
30.83882352941176626.213
946281AF1-292 C
Adder
2.2752941176470591.934
964241AG1-285 C
Adder
17.31176470588235414.715
962561AG1-105 C
Adder
12.25882352941176610.42
316169AC1-164 GEN
Adder
49.0282352941176541.674
3151091ELIZAR2
80/20
4.7354.735
316349AD2-085 C
80/20
5.1625.162
934501AD1-074 C
Adder
50.0317647058823542.527
961671AG1-007 C
Adder
1.34941176470588231.147
3156116Z1-036WIND
80/20
0.9810.981
946301AF1-294 C
Adder
4.9423529411764714.201
942461AE2-259 C
Adder
12.99058823529411711.042
934621AD1-088 C
80/20
14.01914.019
942001AE2-212 C
80/20
3.1513.151
316018AA1-139 ULT2
80/20
1.6261.626
3150851SPRUNCC
80/20
0.2360.236
944631AF1-128 C
Adder
51.9752941176470644.179
933291AC2-141 C
80/20
46.08646.086
3150921YORKTN3
Adder
165.5670588235294140.732
3151191GRAVEL3
80/20
3.6113.611
3156056W1-029WIND
80/20
1.1641.164
3152411Z1-086 GT1
80/20
16.54216.542
3152421Z1-086 GT2
80/20
16.53816.538
316233AE1-074 C
80/20
3.9163.916
940551AE2-041 C
Adder
8.4917647058823537.218
943461AF1-017 C
80/20
2.0242.024
316311AC2-079 C
80/20
8.6058.605
3137643SOCKMAN
Adder
1.04352941176470580.887
939411AE1-173 C
80/20
143.49143.49
316381AD1-082 C
80/20
1.8751.875
3151161SURRY 1
80/20
35.54335.543
3150991CHESPKB
80/20
1.0871.087
933981AD1-022 C
Adder
12.98823529411764711.04
938531AE1-072 C
80/20
26.49826.498
3150731STONECA
Adder
9.5788235294117648.142
935161AD1-151 C
Adder
22.80117647058823519.381
316083AB2-161 C
80/20
0.8230.823
958161AF2-110 C
80/20
2.0582.058
964791AG1-342 C
Adder
4.884.148
316313AB2-026 C
80/20
0.5590.559
939191AE1-149 C
80/20
15.94215.942
957601AF2-054 C
Adder
2.53058823529411742.151
3150981CHESPKA
80/20
0.6560.656
957861AF2-080 C
Adder
11.0270588235294129.373
316023AB2-100 C2
80/20
1.4231.423
316315AB2-025 C
80/20
0.6170.617
3138533PONTONDP
Adder
0.89058823529411770.757
3151541CLOVER2
80/20
18.418.4
316316AC1-027 C
80/20
0.4760.476
313526AB2-022 C
80/20
0.5650.565
316017AA1-139 ULT1
80/20
1.6261.626
3152431Z1-086 GT3
80/20
16.53816.538
316336AC2-165 C
Adder
14.04941176470588411.942
940641AE2-051 C
80/20
27.74527.745
943471AF1-018 C
Adder
8.4917647058823537.218
3152331SURRY 2
80/20
35.95635.956
3151201GRAVEL4
80/20
3.6573.657
3151211GRAVEL5
80/20
3.6113.611
3151221GRAVEL6
80/20
3.6533.653
316236AE1-162 C
80/20
0.5140.514
316303AF2-085
80/20
6.4786.478
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.12565.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.22440.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6237.623
LAGNLTFEXP_LAGN->PJM
CLTF
13.13513.135
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.9747.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
144.491144.491
CPLELTFEXP_CPLE->PJM
CLTF
16.71416.714
TVALTFEXP_TVA->PJM
CLTF
10.46710.467
SIGELTFEXP_SIGE->PJM
CLTF
0.4870.487
NYPJM->LTFIMP_NY
CLTF
3.1863.186
LGEELTFEXP_LGEE->PJM
CLTF
2.5932.593
WECLTFEXP_WEC->PJM
CLTF
1.3381.338

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.79 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4641.11
MW Contribution:5.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961942AG1-037 E
Adder
0.50117647058823530.426
961941AG1-037 C
Adder
0.7517647058823530.639
923852AB2-025 E
50/50
1.7791.779
923862AB2-026 E
Adder
1.8317647058823531.557
941031AE2-094 C
50/50
63.56663.566
941032AE2-094 E
50/50
28.4728.47
3150831SPRUNCA
Adder
13.36352941176470611.359
3150841SPRUNCB
Adder
13.36352941176470611.359
939412AE1-173 E
50/50
96.42796.427
3151081ELIZAR1
50/50
4.8744.874
926662AC1-147 E
Adder
2.02235294117647071.719
916192Z1-068 E
50/50
2.8712.871
957492AF2-043 E
Adder
2.16705882352941171.842
316141AB2-099 E
Adder
0.37647058823529410.32
923994AB2-040_E
Adder
9.1117647058823537.745
316088AB2-174 E
Adder
9.6611764705882348.212
957481AF2-042 C
Adder
80.9247058823529468.786
942002AE2-212 E
Adder
2.13058823529411741.811
940431AE2-027 C
Adder
18.6823529411764715.88
316294AC1-161 C
50/50
7.5867.586
944581AF1-123 C
50/50
69.72769.727
316185AD1-033 C
50/50
1.8711.871
916191Z1-068 C
50/50
0.0670.067
941101AE2-104 C
Adder
5.1011764705882364.336
923263AB1-132 E OP
Adder
9.0588235294117647.7
940481AE2-033 C
50/50
24.72924.729
940482AE2-033 E
50/50
16.67116.671
940541AE2-040 C
50/50
4.3984.398
3152441Z1-086 ST
50/50
28.98428.984
961611AG1-000B C
Adder
23.2270588235294119.743
316375AC2-012 C
50/50
2.0552.055
918512AA1-065 E OP
Adder
8.2458823529411777.009
934502AD1-074 E
Adder
25.72941176470588321.87
934512AD1-075 E
Adder
6.4317647058823535.467
924516AB2-100 E1
Adder
4.3447058823529413.693
966621AG1-532 C
Adder
2.0811764705882351.769
919153AA1-139 E2
Adder
6.2317647058823535.297
3151021BRUNSWICKG1
50/50
12.99912.999
3151041BRUNSWICKG3
50/50
12.99912.999
940642AE2-051 E
50/50
18.62918.629
942341AE2-247 C
Adder
2.2635294117647061.924
943462AF1-017 E
Adder
3.34117647058823542.84
958162AF2-110 E
Adder
3.31058823529411762.814
926072AC1-086 E
Adder
14.16705882352941312.042
960081AF2-299 C
Adder
2.7741176470588242.358
3145413WATKINS
Adder
1.04117647058823540.885
938771AE1-103 C
Adder
4.4282352941176473.764
963041AG1-153 C
50/50
8.8378.837
934521AD1-076 C
Adder
18.35647058823529315.603
934511AD1-075 C
Adder
12.6352941176470610.74
919692AA2-053 E OP
Adder
6.2482352941176475.311
923573AB1-173 E OP
Adder
4.8588235294117644.13
3145723EMPORIA
Adder
0.640.544
920042AA2-088 E OP
Adder
15.88941176470588313.506
919152AA1-139 E1
Adder
6.2317647058823535.297
3151031BRUNSWICKG2
50/50
12.99912.999
316240AF1-291 C
Adder
3.11647058823529432.649
944641AF1-129 C
Adder
146.62823529411764124.634
924814AB2-134 E
Adder
18.2270588235294115.493
942342AE2-247 E
Adder
3.12588235294117662.657
934501AD1-074 C
Adder
50.5435294117647142.962
924517AB2-100 E2
Adder
4.3447058823529413.693
937226AE2-253 E
Adder
8.9129411764705877.576
934621AD1-088 C
Adder
14.11647058823529511.999
957482AF2-042 E
Adder
53.94941176470588645.857
958502AF2-144 E
Adder
1.81.53
942001AE2-212 C
Adder
3.19647058823529442.717
939192AE1-149 E
Adder
10.7658823529411769.151
939312AE1-162 E
Adder
2.13058823529411741.811
934065AD1-033 E
50/50
7.6627.662
920692AA2-178 E
Adder
6.19058823529411755.262
966622AG1-532 E
Adder
1.3870588235294121.179
917122Z2-027 E
Adder
2.04352941176470631.737
3146326AYDLETT TAP
Adder
2.06705882352941161.757
938532AE1-072 E
Adder
13.96470588235294111.87
3152411Z1-086 GT1
50/50
16.65116.651
3152421Z1-086 GT2
50/50
16.64616.646
316233AE1-074 C
50/50
3.9613.961
935162AD1-151 E
Adder
15.43176470588235513.117
943461AF1-017 C
Adder
2.0482352941176471.741
316311AC2-079 C
Adder
8.7047058823529427.399
932596AC2-079 E
Adder
14.20352941176470712.073
962572AG1-106 E
Adder
1.76117647058823561.497
957872AF2-081 E
Adder
6.53176470588235255.552
938562AE1-075 E
Adder
1.56235294117647071.328
938552AE1-074 E
50/50
1.9951.995
926755AC1-161 E
50/50
19.88619.886
933291AC2-141 C
50/50
46.58646.586
3150921YORKTN3
Adder
168.0623529411765142.853
925522AC1-027 E
50/50
1.8591.859
941102AE2-104 E
Adder
8.1105882352941186.894
3145256KINGFORK
Adder
1.52941176470588251.3
3137643SOCKMAN
Adder
1.05294117647058830.895
913392Y1-086 E
Adder
3.3447058823529412.843
940432AE2-027 E
Adder
12.45529411764705910.587
939411AE1-173 C
50/50
144.64144.64
934012AD1-025 E
Adder
14.40588235294117712.245
926071AC1-086 C
Adder
31.12823529411764826.459
946281AF1-292 C
Adder
2.2964705882352941.952
960082AF2-299 E
Adder
1.84941176470588251.572
916042Z1-036 E
Adder
43.2517647058823636.764
923832AB2-022 E
Adder
1.8882352941176471.605
938772AE1-103 E
Adder
6.115294117647065.198
963042AG1-153 E
50/50
13.25613.256
944592AF1-124 E
50/50
160.246160.246
944582AF1-123 E
50/50
159.668159.668
3151091ELIZAR2
50/50
4.7894.789
316349AD2-085 C
Adder
5.2223529411764714.439
935112AD1-144 E
Adder
1.42000000000000021.207
943172AE2-346 E
Adder
0.90235294117647060.767
934522AD1-076 E
Adder
9.3564705882352957.953
940492AE2-034 E
Adder
4.6423529411764713.946
962571AG1-106 C
Adder
4.0258823529411773.422
918492AA1-063AE OP
Adder
6.065.151
957871AF2-081 C
Adder
15.24000000000000212.954
937482AD2-202 E
Adder
1.561.326
3145506HICKORY
50/50
3.3283.328
946262AF1-291 E
Adder
2.07764705882352941.766
3150651CHESTF6
Adder
26.6976470588235322.693
933292AC2-141 E
50/50
19.88619.886
934576AD1-082 E
Adder
6.6517647058823535.654
944602AF1-125 E
50/50
157.162157.162
943612AF1-032 E
Adder
1.40941176470588241.198
901082W1-029 E
Adder
48.43294117647058541.168
3143316POE
50/50
2.082.08
939191AE1-149 C
Adder
16.1494117647058813.727
3151051BRUNSWICKS1
50/50
27.00627.006
944011AF1-069 C
50/50
20.76920.769
925332AB2-190 E
Adder
11.5352941176470599.805
927226AC1-216 E
Adder
11.1270588235294129.458
944591AF1-124 C
50/50
69.97569.975
944601AF1-125 C
50/50
68.65368.653
3151101ELIZAR3
50/50
4.9354.935
941591AE2-156 C
50/50
27.33727.337
936666AD2-085 E
Adder
8.5211764705882367.243
933981AD1-022 C
Adder
13.12117647058823711.153
900672V4-068 E
Adder
0.53294117647058830.453
938531AE1-072 C
Adder
26.78823529411764822.77
3145393UNCAMP
Adder
9.1811764705882367.804
3150731STONECA
Adder
9.735294117647068.275
935161AD1-151 C
Adder
23.14823529411764719.676
932046AC2-012 E
50/50
20.00120.001
958161AF2-110 C
Adder
2.0811764705882351.769
933982AD1-022 E
Adder
7.1423529411764716.071
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
934612AD1-087 E
Adder
5.3305882352941174.531
934622AD1-088 E
Adder
6.79647058823529455.777
3152431Z1-086 GT3
50/50
16.64616.646
316336AC2-165 C
Adder
5.537647058823534.707
940641AE2-051 C
50/50
27.94427.944
316084AB2-161 E
Adder
8.3482352941176477.096
946282AF1-292 E
Adder
1.53058823529411761.301
316315AB2-025 C
50/50
0.6230.623
944012AF1-069 E
50/50
8.0688.068
316316AC1-027 C
50/50
0.4810.481
316303AF2-085
50/50
6.5316.531
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.46965.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.49440.494
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6697.669
LAGNLTFEXP_LAGN->PJM
CLTF
13.22813.228
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.0368.036
CBM South 2LTFEXP_CBM-S2->PJM
CBM
145.599145.599
CPLELTFEXP_CPLE->PJM
CLTF
16.84316.843
TVALTFEXP_TVA->PJM
CLTF
10.54210.542
O66PJM->LTFIMP_O-066
CMTX_NF
45.24145.241
G-007PJM->LTFIMP_G-007
CMTX_NF
7.1157.115
SIGELTFEXP_SIGE->PJM
CLTF
0.490.49
NYPJM->LTFIMP_NY
CLTF
3.2313.231
LGEELTFEXP_LGEE->PJM
CLTF
2.6092.609
WECLTFEXP_WEC->PJM
CLTF
1.3461.346

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.38 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3586.78
MW Contribution:2.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.37294117647058830.317
934321AD1-056 C
Adder
4.7070588235294134.001
934331AD1-057 C
Adder
2.6258823529411772.232
958211AF2-115 C
80/20
1.7961.796
3151531CLOVER1
80/20
10.82910.829
208900BRIS G1
80/20
-2.405-2.405
3151761LOISA E
80/20
6.8276.827
3151771S ANNAG1
80/20
3.2623.262
3151791S ANNAG2
80/20
3.2623.262
3151781S ANNAS1
80/20
1.6761.676
316258AE1-075 C
80/20
0.320.32
941031AE2-094 C
80/20
37.11337.113
960081AF2-299 C
80/20
1.4551.455
936261AD2-033 C
80/20
10.37510.375
961791AG1-021 C
80/20
1.4371.437
938771AE1-103 C
Adder
2.10235294117647081.787
963041AG1-153 C
80/20
5.1375.137
3151051BRUNSWICKS1
80/20
15.69915.699
316170AC1-121 C
80/20
2.952.95
944011AF1-069 C
80/20
12.12612.126
316045AC1-158 C2
80/20
18.51718.517
944591AF1-124 C
Adder
32.1611764705882427.337
944601AF1-125 C
Adder
31.55411764705882826.821
941591AE2-156 C
Adder
12.43294117647058910.568
316365AB2-100 C1
80/20
0.7450.745
957481AF2-042 C
80/20
47.06247.062
3151801S ANNAS2
80/20
1.6761.676
944581AF1-123 C
Adder
32.0470588235294127.24
941101AE2-104 C
Adder
2.35411764705882342.001
3147043LAWRENC
80/20
0.240.24
940481AE2-033 C
80/20
12.91312.913
940541AE2-040 C
80/20
2.2982.298
3152441Z1-086 ST
80/20
16.87216.872
966001AG1-469 C
80/20
2.3822.382
966621AG1-532 C
80/20
1.0911.091
935171AD1-152 C
80/20
1.0991.099
3151021BRUNSWICKG1
80/20
7.5567.556
3151041BRUNSWICKG3
80/20
7.5567.556
934861AD1-115 C
80/20
3.3063.306
3152261N ANNA2
80/20
103.964103.964
942341AE2-247 C
Adder
1.03882352941176470.883
316274AC1-208 C
Adder
6.785.763
962571AG1-106 C
Adder
2.0682352941176471.758
957871AF2-081 C
Adder
7.0094117647058835.958
316405AF2-144 C
80/20
0.2720.272
934521AD1-076 C
Adder
8.8564705882352937.528
934511AD1-075 C
Adder
6.0964705882352945.182
316087AB2-174 C
80/20
0.9080.908
959311AF2-222 C
80/20
13.30313.303
937481AD2-202 C
80/20
0.3090.309
3151031BRUNSWICKG2
80/20
7.5567.556
927021AC1-189 C
Adder
6.225.287
926071AC1-086 C
Adder
15.98823529411764713.59
946281AF1-292 C
80/20
1.2041.204
964241AG1-285 C
80/20
9.9749.974
962561AG1-105 C
Adder
6.9729411764705885.927
316034AC1-036 C
80/20
0.1860.186
3144293JTRSVLE
80/20
0.3290.329
316044AC1-158 C1
80/20
18.51718.517
316349AD2-085 C
Adder
2.3964705882352942.037
934501AD1-074 C
Adder
24.38588235294117720.728
961671AG1-007 C
Adder
0.69647058823529410.592
946301AF1-294 C
80/20
2.9542.954
942461AE2-259 C
80/20
7.9867.986
934621AD1-088 C
80/20
8.2538.253
208901BRIS G2
80/20
-2.846-2.846
316192AB2-158 C
80/20
4.3254.325
942001AE2-212 C
Adder
1.40235294117647061.192
313527AB2-043 C
80/20
0.4090.409
3152251N ANNA1
80/20
103.92103.92
933291AC2-141 C
Adder
21.0423529411764717.886
3152411Z1-086 GT1
80/20
9.6939.693
3152421Z1-086 GT2
80/20
9.699.69
316233AE1-074 C
80/20
2.0672.067
943461AF1-017 C
Adder
0.94000000000000010.799
316311AC2-079 C
Adder
3.99647058823529383.397
3137643SOCKMAN
Adder
0.54588235294117650.464
3151741LOISA C
80/20
3.3493.349
3151721LOISA A
80/20
3.3313.331
939411AE1-173 C
80/20
78.11378.113
933981AD1-022 C
Adder
6.3599999999999995.406
938531AE1-072 C
Adder
12.33529411764705810.485
316238AB2-078 C O1
80/20
0.2590.259
958161AF2-110 C
Adder
0.96117647058823530.817
316239AB2-077 C O1
80/20
0.2590.259
964791AG1-342 C
Adder
2.77294117647058872.357
3151731LOISA B
80/20
3.3493.349
3151751LOISA D
80/20
3.3493.349
316313AB2-026 C
80/20
0.3480.348
316164AC1-076_C
80/20
1.0891.089
939191AE1-149 C
Adder
7.2929411764705886.199
957861AF2-080 C
Adder
5.6494117647058824.802
316023AB2-100 C2
80/20
0.7450.745
316315AB2-025 C
80/20
0.3250.325
316131AB2-060 C
80/20
1.1781.178
3138533PONTONDP
80/20
0.5320.532
3151541CLOVER2
80/20
10.72710.727
316257AC1-043 C
80/20
6.6126.612
316254AC1-120 C
80/20
8.5918.591
316237AB2-079 C O1
80/20
0.2590.259
934611AD1-087 C
80/20
1.0661.066
3152431Z1-086 GT3
80/20
9.699.69
316336AC2-165 C
80/20
8.8748.874
940641AE2-051 C
80/20
15.75815.758
316303AF2-085
80/20
3.8763.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.20919.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.12316.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6672.667
LAGNLTFEXP_LAGN->PJM
CLTF
5.7055.705
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2194.219
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.82173.821
CPLELTFEXP_CPLE->PJM
CLTF
8.8538.853
TVALTFEXP_TVA->PJM
CLTF
4.5224.522
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165
NYPJM->LTFIMP_NY
CLTF
2.292.29
LGEELTFEXP_LGEE->PJM
CLTF
0.8350.835
WECLTFEXP_WEC->PJM
CLTF
0.4130.413

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.09 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3577.61
MW Contribution:2.19
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.39411764705882360.335
934321AD1-056 C
Adder
4.9729411764705894.227
934331AD1-057 C
Adder
2.7741176470588242.358
958211AF2-115 C
80/20
1.8751.875
3151531CLOVER1
80/20
11.34911.349
208900BRIS G1
80/20
-2.414-2.414
3151761LOISA E
80/20
6.316.31
3151771S ANNAG1
80/20
3.0413.041
3151791S ANNAG2
80/20
3.0413.041
3151781S ANNAS1
80/20
1.5631.563
316258AE1-075 C
80/20
0.3330.333
941031AE2-094 C
80/20
38.91138.911
3150831SPRUNCA
Adder
6.1623529411764715.238
3150841SPRUNCB
Adder
6.1623529411764715.238
960081AF2-299 C
80/20
1.5351.535
936261AD2-033 C
80/20
10.85610.856
961791AG1-021 C
80/20
1.51.5
938771AE1-103 C
Adder
2.2329411764705881.898
963041AG1-153 C
80/20
5.3875.387
3151051BRUNSWICKS1
80/20
16.46316.463
944011AF1-069 C
80/20
12.71412.714
944591AF1-124 C
Adder
34.2229.087
944601AF1-125 C
Adder
33.5741176470588328.538
941591AE2-156 C
Adder
13.23882352941176611.253
316365AB2-100 C1
80/20
0.7870.787
957481AF2-042 C
80/20
49.31549.315
3151801S ANNAS2
80/20
1.5631.563
940431AE2-027 C
Adder
8.3129411764705887.066
944581AF1-123 C
Adder
34.0988235294117728.984
941101AE2-104 C
Adder
2.50470588235294132.129
316181AB2-040 GEN
80/20
1.0311.031
3147043LAWRENC
80/20
0.2530.253
940481AE2-033 C
80/20
13.63113.631
940541AE2-040 C
80/20
2.4262.426
3152441Z1-086 ST
80/20
17.69217.692
966001AG1-469 C
80/20
1.9821.982
961611AG1-000B C
Adder
10.3129411764705888.766
313506AB1-173 C OP
80/20
0.9150.915
966621AG1-532 C
80/20
1.1511.151
935171AD1-152 C
80/20
1.1531.153
3151021BRUNSWICKG1
80/20
7.9247.924
3151041BRUNSWICKG3
80/20
7.9247.924
3152261N ANNA2
80/20
106.999106.999
942341AE2-247 C
Adder
1.10588235294117650.94
316274AC1-208 C
Adder
7.1635294117647066.089
962571AG1-106 C
Adder
2.1847058823529411.857
3151311EDGECMA
Adder
12.21411764705882410.382
957871AF2-081 C
Adder
7.4588235294117656.34
316405AF2-144 C
80/20
0.2830.283
3150651CHESTF6
Adder
11.5976470588235319.858
934521AD1-076 C
Adder
9.3952941176470587.986
934511AD1-075 C
Adder
6.46705882352941155.497
316263AC1-034 C
Adder
5.2270588235294114.443
316087AB2-174 C
80/20
0.9580.958
959311AF2-222 C
80/20
13.90913.909
937481AD2-202 C
80/20
0.3240.324
3151031BRUNSWICKG2
80/20
7.9247.924
316240AF1-291 C
Adder
1.37882352941176461.172
944641AF1-129 C
Adder
63.6988235294117654.144
927021AC1-189 C
Adder
6.5788235294117645.592
926071AC1-086 C
Adder
16.8929411764705914.359
946281AF1-292 C
80/20
1.2711.271
964241AG1-285 C
80/20
10.44910.449
962561AG1-105 C
Adder
7.3152941176470596.218
316034AC1-036 C
80/20
0.1950.195
3144293JTRSVLE
80/20
0.3440.344
316349AD2-085 C
Adder
2.5505882352941182.168
934501AD1-074 C
Adder
25.86823529411764621.988
961671AG1-007 C
Adder
0.73647058823529410.626
946301AF1-294 C
80/20
3.0833.083
942461AE2-259 C
Adder
8.3117647058823547.065
934621AD1-088 C
80/20
8.6418.641
208901BRIS G2
80/20
-2.857-2.857
316192AB2-158 C
80/20
4.2764.276
942001AE2-212 C
Adder
1.49882352941176471.274
313527AB2-043 C
80/20
0.4290.429
3152251N ANNA1
80/20
106.954106.954
933291AC2-141 C
Adder
22.41294117647058619.051
3152411Z1-086 GT1
80/20
10.16410.164
3152421Z1-086 GT2
80/20
10.16110.161
316233AE1-074 C
80/20
2.1822.182
943461AF1-017 C
Adder
1.00.85
316311AC2-079 C
Adder
4.2541176470588233.616
3137643SOCKMAN
Adder
0.57647058823529410.49
3151741LOISA C
80/20
3.0953.095
3151721LOISA A
80/20
3.0793.079
939411AE1-173 C
80/20
82.26382.263
933981AD1-022 C
Adder
6.7447058823529415.733
938531AE1-072 C
Adder
13.12352941176470511.155
316238AB2-078 C O1
80/20
0.2720.272
958161AF2-110 C
Adder
1.02235294117647070.869
316239AB2-077 C O1
80/20
0.2720.272
964791AG1-342 C
Adder
2.9105882352941182.474
3151731LOISA B
80/20
3.0953.095
3151751LOISA D
80/20
3.0953.095
316313AB2-026 C
80/20
0.3630.363
939191AE1-149 C
Adder
7.7752941176470596.609
957861AF2-080 C
Adder
5.9741176470588245.078
316023AB2-100 C2
80/20
0.7870.787
316315AB2-025 C
80/20
0.3440.344
316131AB2-060 C
80/20
1.2351.235
3138533PONTONDP
80/20
0.5550.555
3151541CLOVER2
80/20
11.24311.243
316237AB2-079 C O1
80/20
0.2720.272
934611AD1-087 C
80/20
1.1171.117
3152431Z1-086 GT3
80/20
10.16110.161
316336AC2-165 C
80/20
9.2269.226
940641AE2-051 C
80/20
16.55416.554
316303AF2-085
80/20
4.064.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.24822.248
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.65817.658
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.9882.988
LAGNLTFEXP_LAGN->PJM
CLTF
6.1746.174
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4574.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
78.26878.268
CPLELTFEXP_CPLE->PJM
CLTF
9.3529.352
TVALTFEXP_TVA->PJM
CLTF
4.8954.895
SIGELTFEXP_SIGE->PJM
CLTF
0.1860.186
NYPJM->LTFIMP_NY
CLTF
2.2912.291
LGEELTFEXP_LGEE->PJM
CLTF
0.9480.948
WECLTFEXP_WEC->PJM
CLTF
0.4740.474

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.41 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4350.17
MW Contribution:3.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.195294117647058840.166
961672AG1-007 E
Adder
0.414117647058823530.352
923994AB2-040_E
Adder
4.9741176470588234.228
316088AB2-174 E
Adder
5.2858823529411774.493
924322AB2-079 E O1
Adder
1.10588235294117650.94
943902AF1-058 E
Adder
1.04352941176470580.887
946302AF1-294 E
Adder
2.59294117647058852.204
957481AF2-042 C
Adder
49.0341176470588341.679
3151801S ANNAS2
50/50
1.5681.568
942002AE2-212 E
Adder
0.99176470588235290.843
944581AF1-123 C
Adder
33.8670588235294128.787
941101AE2-104 C
Adder
2.48705882352941152.114
923263AB1-132 E OP
Adder
4.8811764705882354.149
940481AE2-033 C
Adder
13.54823529411764811.516
940482AE2-033 E
Adder
9.1341176470588247.764
940541AE2-040 C
Adder
2.4117647058823532.05
924312AB2-078 E O1
Adder
1.10588235294117650.94
925612AC1-036 E
Adder
0.7117647058823530.605
926274AC1-105 E
Adder
2.1788235294117651.852
966001AG1-469 C
50/50
2.0062.006
926740AC1-158 E2
50/50
51.18251.182
926214AC1-099 E
Adder
0.94705882352941180.805
932632AC2-084 E
Adder
2.53411764705882362.154
962572AG1-106 E
Adder
0.94941176470588240.807
957872AF2-081 E
Adder
3.17411764705882372.698
924162AB2-060 E OP
Adder
3.54470588235294143.013
964242AG1-285 E
Adder
6.9188235294117655.881
964792AG1-342 E
Adder
1.92588235294117661.637
932763AC2-100 E
Adder
2.00588235294117641.705
938562AE1-075 E
Adder
1.00.85
3152251N ANNA1
50/50
106.841106.841
938552AE1-074 E
Adder
1.09294117647058830.929
926755AC1-161 E
Adder
9.502352941176478.077
933291AC2-141 C
Adder
22.2618.921
925522AC1-027 E
Adder
0.89764705882352950.763
941102AE2-104 E
Adder
3.9541176470588243.361
3145256KINGFORK
Adder
0.72352941176470590.615
934501AD1-074 C
Adder
25.6821.828
961671AG1-007 C
Adder
0.73058823529411760.621
924517AB2-100 E2
Adder
2.36470588235294082.01
937226AE2-253 E
Adder
4.3282352941176473.679
946301AF1-294 C
Adder
3.06235294117647072.603
935172AD1-152 E
Adder
4.7270588235294114.018
942461AE2-259 C
Adder
8.257647058823537.019
934621AD1-088 C
Adder
8.5905882352941177.302
957482AF2-042 E
Adder
32.6894117647058927.786
208901BRIS G2
50/50
-2.946-2.946
958502AF2-144 E
Adder
1.15294117647058810.98
316192AB2-158 C
50/50
4.2784.278
942001AE2-212 C
Adder
1.48705882352941181.264
939192AE1-149 E
Adder
5.1470588235294124.375
939312AE1-162 E
Adder
0.97647058823529410.83
934065AD1-033 E
Adder
3.70941176470588243.153
919710AA2-057 E
Adder
3.1117647058823532.645
3137643SOCKMAN
Adder
0.57294117647058830.487
913392Y1-086 E
Adder
1.63411764705882371.389
933502AC2-165 E
Adder
6.9070588235294135.871
3151741LOISA C
50/50
3.1063.106
3151721LOISA A
50/50
3.093.09
939411AE1-173 C
Adder
81.8247058823529469.551
920692AA2-178 E
Adder
3.1141176470588232.647
922923AB1-081 E OP
Adder
2.9105882352941182.474
966622AG1-532 E
Adder
0.76235294117647070.648
917122Z2-027 E
Adder
1.00.85
3146326AYDLETT TAP
Adder
1.00588235294117640.855
938532AE1-072 E
Adder
6.7941176470588245.775
927264AC1-222 E
Adder
3.20470588235294152.724
3147133PAMPLIN
Adder
0.82352941176470580.7
966002AG1-469 E
50/50
1.0031.003
926739AC1-158 E1
50/50
51.18251.182
316233AE1-074 C
Adder
2.17058823529411751.845
943461AF1-017 C
Adder
0.99294117647058820.844
316311AC2-079 C
Adder
4.2247058823529413.591
932596AC2-079 E
Adder
6.8929411764705895.859
961942AG1-037 E
Adder
0.26117647058823530.222
961941AG1-037 C
Adder
0.391764705882352960.333
927022AC1-189 E
Adder
3.25058823529411762.763
934322AD1-056 E
Adder
2.6764705882352942.275
934332AD1-057 E
Adder
1.43411764705882371.219
934321AD1-056 C
Adder
4.9352941176470594.195
934331AD1-057 C
Adder
2.75294117647058822.34
925595AC1-034 E
Adder
3.91058823529411773.324
923852AB2-025 E
Adder
0.97529411764705880.829
936262AD2-033 E
Adder
7.1882352941176476.11
958211AF2-115 C
Adder
1.86235294117647051.583
208900BRIS G1
50/50
-2.489-2.489
3151761LOISA E
50/50
6.3326.332
3151771S ANNAG1
50/50
3.0513.051
3151791S ANNAG2
50/50
3.0513.051
3151781S ANNAS1
50/50
1.5681.568
923862AB2-026 E
Adder
1.17294117647058820.997
941031AE2-094 C
50/50
38.72138.721
941032AE2-094 E
50/50
17.34217.342
3150831SPRUNCA
Adder
6.117647058823535.2
3150841SPRUNCB
Adder
6.117647058823535.2
939412AE1-173 E
Adder
54.5505882352941246.368
926662AC1-147 E
Adder
0.97176470588235290.826
916192Z1-068 E
Adder
1.38588235294117631.178
957492AF2-043 E
Adder
1.05294117647058830.895
918512AA1-065 E OP
Adder
4.2588235294117653.62
918532AA1-067 E
Adder
0.55176470588235290.469
934502AD1-074 E
Adder
13.07176470588235311.111
934512AD1-075 E
Adder
3.26823529411764732.778
924516AB2-100 E1
Adder
2.36470588235294082.01
966621AG1-532 C
Adder
1.1435294117647060.972
919153AA1-139 E2
Adder
3.02941176470588272.575
924022AB2-043 E O1
Adder
4.2929411764705883.649
3147223TWITTYS
Adder
0.78941176470588240.671
959312AF2-222 E
Adder
9.2564705882352957.868
3152261N ANNA2
50/50
106.886106.886
940642AE2-051 E
50/50
10.98110.981
942341AE2-247 C
Adder
1.09764705882352940.933
943462AF1-017 E
Adder
1.621.377
958162AF2-110 E
Adder
1.61411764705882371.372
927021AC1-189 C
Adder
6.5247058823529425.546
926071AC1-086 C
Adder
16.77411764705882314.258
924152AB2-059 E OP
Adder
4.122352941176473.504
946281AF1-292 C
Adder
1.26235294117647071.073
960082AF2-299 E
Adder
1.01647058823529420.864
916042Z1-036 E
Adder
21.48117647058823518.259
923832AB2-022 E
Adder
0.92235294117647060.784
964241AG1-285 C
Adder
10.3776470588235298.821
962561AG1-105 C
Adder
7.2635294117647076.174
958212AF2-115 E
Adder
1.58588235294117651.348
938772AE1-103 E
Adder
3.0611764705882352.602
963042AG1-153 E
Adder
8.0388235294117656.833
925022AB2-158 E
50/50
11.37311.373
316044AC1-158 C1
50/50
19.56819.568
944592AF1-124 E
Adder
77.8317647058823566.157
944582AF1-123 E
Adder
77.5517647058823565.919
316349AD2-085 C
Adder
2.53294117647058852.153
935112AD1-144 E
Adder
0.67176470588235290.571
926206AC1-098 E
Adder
2.86705882352941142.437
964791AG1-342 C
Adder
2.88941176470588262.456
901082W1-029 E
Adder
23.76705882352941420.202
942462AE2-259 E
Adder
5.5047058823529414.679
3151731LOISA B
50/50
3.1063.106
3151751LOISA D
50/50
3.1063.106
3143316POE
Adder
1.04235294117647070.886
939191AE1-149 C
Adder
7.7200000000000016.562
943172AE2-346 E
Adder
0.46941176470588240.399
917332KELFORD E
Adder
1.281.088
925122AB2-169 E
Adder
4.4105882352941183.749
934522AD1-076 E
Adder
4.7541176470588244.041
940492AE2-034 E
Adder
2.3364705882352941.986
316274AC1-208 C
Adder
7.1094117647058826.043
962571AG1-106 C
Adder
2.16941176470588241.844
917342Z2-044 E
Adder
0.46823529411764710.398
3151311EDGECMA
Adder
12.11411764705882510.297
918492AA1-063AE OP
Adder
3.22705882352941182.743
957871AF2-081 C
Adder
7.4070588235294126.296
961792AG1-021 E
Adder
1.26941176470588221.079
937482AD2-202 E
Adder
0.94117647058823540.8
3145506HICKORY
Adder
1.61411764705882371.372
933292AC2-141 E
Adder
9.502352941176478.077
934576AD1-082 E
Adder
3.19882352941176462.719
944602AF1-125 E
Adder
76.3341176470588364.884
943612AF1-032 E
Adder
0.68470588235294120.582
957862AF2-080 E
Adder
2.6270588235294122.233
926072AC1-086 E
Adder
7.6341176470588236.489
960081AF2-299 C
Adder
1.52470588235294141.296
3145413WATKINS
Adder
0.52941176470588240.45
936261AD2-033 C
Adder
10.782352941176479.165
962562AG1-105 E
Adder
4.842352941176474.116
961791AG1-021 C
Adder
1.48941176470588241.266
938771AE1-103 C
Adder
2.21764705882352951.885
924032AB2-045 E
Adder
1.08588235294117650.923
963041AG1-153 C
Adder
5.3588235294117644.555
944011AF1-069 C
50/50
12.65212.652
316045AC1-158 C2
50/50
19.56819.568
944591AF1-124 C
Adder
33.9870588235294128.889
944601AF1-125 C
Adder
33.3447058823529428.343
941591AE2-156 C
Adder
13.14823529411764711.176
936666AD2-085 E
Adder
4.1329411764705883.513
933981AD1-022 C
Adder
6.6952941176470595.691
900672V4-068 E
Adder
0.276470588235294130.235
938531AE1-072 C
Adder
13.03294117647058811.078
924302AB2-077 E O1
Adder
1.10588235294117650.94
3145393UNCAMP
Adder
4.622352941176473.929
932046AC2-012 E
Adder
9.6164705882352938.174
958161AF2-110 C
Adder
1.0152941176470590.863
933982AD1-022 E
Adder
3.6447058823529413.098
3145946PLYMOUTH TP
Adder
0.245882352941176470.209
927146AC1-208 E
Adder
3.1564705882352942.683
927255AC1-221 E
Adder
2.9588235294117652.515
934612AD1-087 E
Adder
3.2152941176470592.733
934622AD1-088 E
Adder
4.1364705882352943.516
316336AC2-165 C
Adder
9.177647058823537.801
940641AE2-051 C
50/50
16.47216.472
316084AB2-161 E
Adder
4.0141176470588233.412
934521AD1-076 C
Adder
9.3258823529411777.927
934511AD1-075 C
Adder
6.425.457
919692AA2-053 E OP
Adder
3.36117647058823542.857
316263AC1-034 C
Adder
5.1835294117647064.406
923573AB1-173 E OP
Adder
2.6529411764705882.255
3145723EMPORIA
Adder
0.350588235294117640.298
920042AA2-088 E OP
Adder
8.226.987
925785AC1-054 E
Adder
2.79764705882352962.378
919152AA1-139 E1
Adder
3.02941176470588272.575
959311AF2-222 C
Adder
13.8152941176470611.743
942342AE2-247 E
Adder
1.5164705882352941.289
957861AF2-080 C
Adder
5.9270588235294125.038
917512Z2-088 E OP1
Adder
3.8047058823529413.234
946282AF1-292 E
Adder
0.84117647058823530.715
3138533PONTONDP
Adder
0.55176470588235290.469
944012AF1-069 E
50/50
4.9154.915
316303AF2-085
50/50
4.0434.043
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.05120.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.83616.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7842.784
LAGNLTFEXP_LAGN->PJM
CLTF
5.9595.959
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4084.408
CBM South 2LTFEXP_CBM-S2->PJM
CBM
77.11777.117
CPLELTFEXP_CPLE->PJM
CLTF
9.2519.251
TVALTFEXP_TVA->PJM
CLTF
4.7224.722
O66PJM->LTFIMP_O-066
CMTX_NF
32.20632.206
G-007PJM->LTFIMP_G-007
CMTX_NF
5.0575.057
SIGELTFEXP_SIGE->PJM
CLTF
0.1730.173
NYPJM->LTFIMP_NY
CLTF
2.3732.373
LGEELTFEXP_LGEE->PJM
CLTF
0.8720.872
WECLTFEXP_WEC->PJM
CLTF
0.4310.431

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.75 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4205.81
MW Contribution:2.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.187058823529411780.159
923994AB2-040_E
Adder
4.7588235294117654.045
923263AB1-132 E OP
Adder
4.66470588235294153.965
940481AE2-033 C
Adder
12.94470588235294211.003
940482AE2-033 E
Adder
8.7270588235294117.418
940541AE2-040 C
Adder
2.3035294117647061.958
924312AB2-078 E O1
Adder
1.06588235294117650.906
925612AC1-036 E
Adder
0.68823529411764710.585
926274AC1-105 E
Adder
2.09764705882352941.783
966001AG1-469 C
50/50
2.4612.461
925672AC1-043 E
50/50
11.48611.486
926740AC1-158 E2
50/50
48.49548.495
926214AC1-099 E
Adder
0.90470588235294120.769
934501AD1-074 C
Adder
24.44941176470588220.782
924517AB2-100 E2
Adder
2.26000000000000021.921
937226AE2-253 E
Adder
4.1070588235294123.491
946301AF1-294 C
Adder
2.96705882352941152.522
935172AD1-152 E
Adder
4.5494117647058833.867
942461AE2-259 C
Adder
8.0294117647058826.825
934621AD1-088 C
Adder
8.277647058823537.036
957482AF2-042 E
Adder
31.4626.741
208901BRIS G2
50/50
-2.864-2.864
958502AF2-144 E
Adder
1.11764705882352940.95
316192AB2-158 C
50/50
4.384.38
942001AE2-212 C
Adder
1.40588235294117661.195
939192AE1-149 E
Adder
4.87529411764705944.144
934065AD1-033 E
Adder
3.5188235294117652.991
919710AA2-057 E
Adder
2.97647058823529382.53
3137643SOCKMAN
Adder
0.54705882352941180.465
913392Y1-086 E
Adder
1.5517647058823531.319
933502AC2-165 E
Adder
6.7129411764705895.706
3151741LOISA C
50/50
3.4533.453
3151721LOISA A
50/50
3.4353.435
939411AE1-173 C
Adder
78.2905882352941166.547
920692AA2-178 E
Adder
2.9635294117647062.519
966622AG1-532 E
Adder
0.72941176470588230.62
917122Z2-027 E
Adder
0.94941176470588240.807
3146326AYDLETT TAP
Adder
0.95411764705882360.811
938532AE1-072 E
Adder
6.4470588235294135.48
927264AC1-222 E
Adder
3.0847058823529412.622
3147133PAMPLIN
Adder
0.79882352941176480.679
966002AG1-469 E
50/50
1.231.23
926739AC1-158 E1
50/50
48.49548.495
316233AE1-074 C
Adder
2.07294117647058851.762
943461AF1-017 C
Adder
0.94235294117647060.801
316311AC2-079 C
Adder
4.00705882352941253.406
932596AC2-079 E
Adder
6.5388235294117655.558
961942AG1-037 E
Adder
0.249411764705882360.212
961941AG1-037 C
Adder
0.37294117647058830.317
927022AC1-189 E
Adder
3.10588235294117652.64
934322AD1-056 E
Adder
2.562.176
934332AD1-057 E
Adder
1.37058823529411771.165
934321AD1-056 C
Adder
4.7188235294117654.011
934331AD1-057 C
Adder
2.6329411764705882.238
923852AB2-025 E
Adder
0.9317647058823530.792
936262AD2-033 E
Adder
6.9435294117647075.902
958211AF2-115 C
Adder
1.80470588235294121.534
208900BRIS G1
50/50
-2.42-2.42
3151761LOISA E
50/50
7.047.04
3151771S ANNAG1
50/50
3.3573.357
3151791S ANNAG2
50/50
3.3573.357
3151781S ANNAS1
50/50
1.7251.725
923862AB2-026 E
Adder
1.13764705882352950.967
941031AE2-094 C
50/50
37.19337.193
941032AE2-094 E
50/50
16.65816.658
939412AE1-173 E
Adder
52.19411764705882544.365
926662AC1-147 E
Adder
0.92117647058823540.783
916192Z1-068 E
Adder
1.31411764705882361.117
957492AF2-043 E
Adder
0.99882352941176470.849
918512AA1-065 E OP
Adder
4.06000000000000053.451
918532AA1-067 E
Adder
0.52705882352941180.448
934502AD1-074 E
Adder
12.44588235294117810.579
934512AD1-075 E
Adder
3.1117647058823532.645
924516AB2-100 E1
Adder
2.26000000000000021.921
966621AG1-532 C
Adder
1.09411764705882360.93
919153AA1-139 E2
Adder
2.8741176470588242.443
924022AB2-043 E O1
Adder
4.1364705882352943.516
3147223TWITTYS
Adder
0.76235294117647070.648
959312AF2-222 E
Adder
8.9494117647058827.607
934861AD1-115 C
50/50
3.523.52
3152261N ANNA2
50/50
104.075104.075
940642AE2-051 E
50/50
10.52910.529
942341AE2-247 C
Adder
1.04117647058823540.885
943462AF1-017 E
Adder
1.53764705882352941.307
958162AF2-110 E
Adder
1.53176470588235311.302
927021AC1-189 C
Adder
6.2352941176470595.3
926071AC1-086 C
Adder
16.0282352941176513.624
946281AF1-292 C
Adder
1.2082352941176471.027
960082AF2-299 E
Adder
0.97294117647058820.827
916042Z1-036 E
Adder
20.41647058823529517.354
923832AB2-022 E
Adder
0.87529411764705890.744
964241AG1-285 C
Adder
10.0105882352941198.509
962561AG1-105 C
Adder
6.9952941176470595.946
958212AF2-115 E
Adder
1.53764705882352941.307
938772AE1-103 E
Adder
2.91176470588235332.475
963042AG1-153 E
Adder
7.7235294117647076.565
925022AB2-158 E
50/50
11.64111.641
316044AC1-158 C1
50/50
18.54118.541
944592AF1-124 E
Adder
73.8458823529411762.769
944582AF1-123 E
Adder
73.5862.543
316349AD2-085 C
Adder
2.40235294117647062.042
935112AD1-144 E
Adder
0.63647058823529420.541
926206AC1-098 E
Adder
2.742.329
964791AG1-342 C
Adder
2.7823529411764712.365
901082W1-029 E
Adder
22.56941176470588319.184
942462AE2-259 E
Adder
5.3529411764705884.55
3151731LOISA B
50/50
3.4533.453
3151751LOISA D
50/50
3.4533.453
3143316POE
Adder
0.99058823529411770.842
316164AC1-076_C
50/50
1.1111.111
939191AE1-149 C
Adder
7.3129411764705896.216
943172AE2-346 E
Adder
0.448235294117647070.381
917332KELFORD E
Adder
1.22235294117647041.039
925122AB2-169 E
Adder
4.2058823529411773.575
934522AD1-076 E
Adder
4.5258823529411773.847
940492AE2-034 E
Adder
2.2223529411764711.889
316274AC1-208 C
Adder
6.7976470588235295.778
962571AG1-106 C
Adder
2.07294117647058851.762
917342Z2-044 E
Adder
0.448235294117647070.381
918492AA1-063AE OP
Adder
3.08235294117647072.62
957871AF2-081 C
Adder
7.0282352941176475.974
961792AG1-021 E
Adder
1.22941176470588221.045
937482AD2-202 E
Adder
0.90588235294117650.77
3145506HICKORY
Adder
1.53058823529411761.301
933292AC2-141 E
Adder
9.0070588235294127.656
934576AD1-082 E
Adder
3.0317647058823532.577
944602AF1-125 E
Adder
72.4247058823529461.561
943612AF1-032 E
Adder
0.64941176470588250.552
957862AF2-080 E
Adder
2.5105882352941182.134
926072AC1-086 E
Adder
7.29529411764705856.201
960081AF2-299 C
Adder
1.45882352941176461.24
3145413WATKINS
Adder
0.50352941176470590.428
936261AD2-033 C
Adder
10.415294117647068.853
962562AG1-105 E
Adder
4.6635294117647063.964
961791AG1-021 C
Adder
1.4435294117647061.227
938771AE1-103 C
Adder
2.1082352941176471.792
924032AB2-045 E
Adder
1.06588235294117650.906
963041AG1-153 C
Adder
5.1482352941176474.376
316170AC1-121 C
50/50
3.0753.075
944011AF1-069 C
50/50
12.15212.152
316045AC1-158 C2
50/50
18.54118.541
944591AF1-124 C
Adder
32.24705882352941427.41
944601AF1-125 C
Adder
31.6376470588235326.892
941591AE2-156 C
Adder
12.46588235294117710.596
936666AD2-085 E
Adder
3.923.332
933981AD1-022 C
Adder
6.3764705882352955.42
900672V4-068 E
Adder
0.26352941176470590.224
938531AE1-072 C
Adder
12.36823529411764810.513
924302AB2-077 E O1
Adder
1.06588235294117650.906
3145393UNCAMP
Adder
4.3976470588235293.738
926486AC1-120 E
50/50
4.6124.612
932046AC2-012 E
Adder
9.1176470588235297.75
958161AF2-110 C
Adder
0.96352941176470590.819
933982AD1-022 E
Adder
3.47058823529411782.95
3145946PLYMOUTH TP
Adder
0.234117647058823540.199
927146AC1-208 E
Adder
3.01882352941176452.566
927255AC1-221 E
Adder
2.84470588235294162.418
934612AD1-087 E
Adder
3.09529411764705882.631
934622AD1-088 E
Adder
3.98588235294117643.388
316336AC2-165 C
Adder
8.9188235294117667.581
926004AC1-076_E
50/50
6.3656.365
940641AE2-051 C
50/50
15.79315.793
316084AB2-161 E
Adder
3.8047058823529413.234
934521AD1-076 C
Adder
8.8788235294117657.547
934511AD1-075 C
Adder
6.1117647058823535.195
919692AA2-053 E OP
Adder
3.2129411764705882.731
923573AB1-173 E OP
Adder
2.53764705882352942.157
3145723EMPORIA
Adder
0.33529411764705880.285
920042AA2-088 E OP
Adder
7.8352941176470596.66
925785AC1-054 E
Adder
2.6835294117647062.281
919152AA1-139 E1
Adder
2.8741176470588242.443
959311AF2-222 C
Adder
13.3576470588235311.354
926502AC1-121 E
50/50
1.4471.447
942342AE2-247 E
Adder
1.43764705882352951.222
316088AB2-174 E
Adder
5.0564705882352944.298
924322AB2-079 E O1
Adder
1.06588235294117650.906
943902AF1-058 E
Adder
1.00470588235294110.854
946302AF1-294 E
Adder
2.51294117647058852.136
957481AF2-042 C
Adder
47.1905882352941240.112
3151801S ANNAS2
50/50
1.7251.725
942002AE2-212 E
Adder
0.93764705882352950.797
944581AF1-123 C
Adder
32.1329411764705927.313
941101AE2-104 C
Adder
2.362.006
932632AC2-084 E
Adder
2.4211764705882352.058
962572AG1-106 E
Adder
0.90705882352941180.771
957872AF2-081 E
Adder
3.0117647058823532.56
924162AB2-060 E OP
Adder
3.4164705882352942.904
964242AG1-285 E
Adder
6.6741176470588245.673
964792AG1-342 E
Adder
1.85529411764705881.577
932763AC2-100 E
Adder
1.9282352941176471.639
934862AD1-115 E
50/50
5.7435.743
938562AE1-075 E
Adder
0.96941176470588230.824
3152251N ANNA1
50/50
104.031104.031
938552AE1-074 E
Adder
1.04470588235294120.888
926755AC1-161 E
Adder
9.0070588235294127.656
933291AC2-141 C
Adder
21.09882352941176717.934
925522AC1-027 E
Adder
0.85058823529411760.723
941102AE2-104 E
Adder
3.75294117647058823.19
3145256KINGFORK
Adder
0.68588235294117650.583
957861AF2-080 C
Adder
5.6635294117647064.814
946282AF1-292 E
Adder
0.80470588235294130.684
3138533PONTONDP
Adder
0.53411764705882360.454
316257AC1-043 C
50/50
7.047.04
316254AC1-120 C
50/50
8.9538.953
944012AF1-069 E
50/50
4.7214.721
316303AF2-085
50/50
3.8863.886
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.05119.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.10316.103
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6562.656
LAGNLTFEXP_LAGN->PJM
CLTF
5.7065.706
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2284.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.97573.975
CPLELTFEXP_CPLE->PJM
CLTF
8.8738.873
TVALTFEXP_TVA->PJM
CLTF
4.5234.523
O66PJM->LTFIMP_O-066
CMTX_NF
31.31531.315
G-007PJM->LTFIMP_G-007
CMTX_NF
4.9174.917
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165
NYPJM->LTFIMP_NY
CLTF
2.3072.307
LGEELTFEXP_LGEE->PJM
CLTF
0.8310.831
WECLTFEXP_WEC->PJM
CLTF
0.410.41

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.97 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3767.03
MW Contribution:2.47
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.454117647058823570.386
934321AD1-056 C
Adder
5.5882352941176484.75
934331AD1-057 C
Adder
3.11764705882352942.65
958211AF2-115 C
Adder
2.0152941176470591.713
3151531CLOVER1
80/20
12.09912.099
208900BRIS G1
80/20
-2.561-2.561
3151761LOISA E
80/20
4.8664.866
3151771S ANNAG1
80/20
2.372.37
3151791S ANNAG2
80/20
2.372.37
3151781S ANNAS1
80/20
1.2181.218
316258AE1-075 C
80/20
0.3530.353
941031AE2-094 C
80/20
41.10641.106
3150831SPRUNCA
Adder
7.7905882352941186.622
3150841SPRUNCB
Adder
7.7905882352941186.622
3151081ELIZAR1
80/20
2.8512.851
960081AF2-299 C
80/20
1.7191.719
936261AD2-033 C
Adder
11.7211764705882359.963
961791AG1-021 C
Adder
1.61176470588235321.37
938771AE1-103 C
80/20
2.6332.633
963041AG1-153 C
80/20
5.7035.703
3151051BRUNSWICKS1
80/20
17.42917.429
944011AF1-069 C
80/20
13.43113.431
3150601CHESTF5
Adder
45.29058823529411638.497
944591AF1-124 C
80/20
41.04941.049
944601AF1-125 C
80/20
40.27340.273
3151101ELIZAR3
80/20
2.8872.887
941591AE2-156 C
80/20
15.98415.984
316365AB2-100 C1
80/20
0.8850.885
957481AF2-042 C
80/20
52.44752.447
3151801S ANNAS2
80/20
1.2181.218
940431AE2-027 C
Adder
10.6976470588235299.093
316294AC1-161 C
80/20
4.4154.415
944581AF1-123 C
80/20
40.90340.903
316185AD1-033 C
80/20
1.0971.097
916191Z1-068 C
80/20
0.0390.039
941101AE2-104 C
80/20
3.0013.001
316181AB2-040 GEN
80/20
1.1581.158
3147043LAWRENC
80/20
0.2810.281
940481AE2-033 C
80/20
15.30215.302
940541AE2-040 C
80/20
2.7232.723
3152441Z1-086 ST
80/20
18.71718.717
966001AG1-469 C
Adder
1.43764705882352951.222
961611AG1-000B C
Adder
13.19882352941176511.219
316375AC2-012 C
80/20
1.2021.202
316072AD1-144 C
80/20
0.2460.246
313506AB1-173 C OP
80/20
1.0281.028
966621AG1-532 C
80/20
1.2891.289
316320Y1-086 C
80/20
0.1960.196
316388AE2-253 GEN
80/20
1.7531.753
935171AD1-152 C
80/20
1.2331.233
3151021BRUNSWICKG1
80/20
8.3898.389
3151041BRUNSWICKG3
80/20
8.3898.389
3152261N ANNA2
80/20
92.75992.759
942341AE2-247 C
80/20
1.3311.331
316246AF1-032 C
80/20
0.2540.254
316274AC1-208 C
Adder
8.077647058823536.866
962571AG1-106 C
Adder
2.4670588235294122.097
3151311EDGECMA
Adder
13.67647058823529511.625
957871AF2-081 C
80/20
8.9458.945
316405AF2-144 C
80/20
0.30.3
3150651CHESTF6
Adder
15.16470588235294212.89
3150861SPRUNCD
80/20
0.140.14
934521AD1-076 C
Adder
10.9623529411764719.318
934511AD1-075 C
Adder
7.54588235294117656.414
316263AC1-034 C
Adder
5.8505882352941184.973
316087AB2-174 C
80/20
1.0751.075
316321Z2-027 C
80/20
0.3250.325
959311AF2-222 C
Adder
14.9976470588235312.748
937481AD2-202 C
80/20
0.3460.346
3151031BRUNSWICKG2
80/20
8.3898.389
316240AF1-291 C
Adder
1.78117647058823541.514
944641AF1-129 C
Adder
83.2882352941176570.795
316036AC1-147 C
80/20
0.3280.328
316305AF2-043 C
80/20
0.3110.311
927021AC1-189 C
Adder
7.4435294117647066.327
926071AC1-086 C
Adder
19.07647058823529616.215
946281AF1-292 C
80/20
1.4231.423
964241AG1-285 C
Adder
11.3035294117647079.608
962561AG1-105 C
Adder
7.9117647058823526.725
3151091ELIZAR2
80/20
2.8012.801
316349AD2-085 C
80/20
3.0713.071
934501AD1-074 C
Adder
30.18352941176470625.656
961671AG1-007 C
Adder
0.82941176470588230.705
946301AF1-294 C
Adder
3.3141176470588242.817
942461AE2-259 C
Adder
8.8929411764705887.559
934621AD1-088 C
80/20
9.29.2
208901BRIS G2
80/20
-3.03-3.03
316192AB2-158 C
80/20
3.5593.559
942001AE2-212 C
Adder
1.8635294117647061.584
316018AA1-139 ULT2
80/20
0.9650.965
3152251N ANNA1
80/20
92.7292.72
3150851SPRUNCC
80/20
0.140.14
944631AF1-128 C
Adder
28.33882352941176624.088
933291AC2-141 C
80/20
27.11427.114
3150921YORKTN3
Adder
92.4352941176470578.57
3156056W1-029WIND
80/20
0.6930.693
3152411Z1-086 GT1
80/20
10.75310.753
3152421Z1-086 GT2
80/20
10.7510.75
316233AE1-074 C
80/20
2.4792.479
943461AF1-017 C
80/20
1.2041.204
316311AC2-079 C
80/20
5.125.12
3137643SOCKMAN
Adder
0.64823529411764710.551
3151741LOISA C
80/20
2.3872.387
3151721LOISA A
80/20
2.3742.374
939411AE1-173 C
80/20
90.4790.47
316381AD1-082 C
80/20
1.1161.116
3150991CHESPKB
80/20
0.6430.643
933981AD1-022 C
Adder
7.84941176470588256.672
938531AE1-072 C
80/20
15.7315.73
3150731STONECA
Adder
5.4352941176470594.62
935161AD1-151 C
Adder
13.03882352941176511.083
316083AB2-161 C
80/20
0.4890.489
958161AF2-110 C
80/20
1.2251.225
964791AG1-342 C
Adder
3.14588235294117662.674
3151731LOISA B
80/20
2.3872.387
3151751LOISA D
80/20
2.3872.387
316313AB2-026 C
80/20
0.3850.385
939191AE1-149 C
80/20
9.4869.486
3150981CHESPKA
80/20
0.3880.388
957861AF2-080 C
Adder
6.7600000000000015.746
316023AB2-100 C2
80/20
0.8850.885
316315AB2-025 C
80/20
0.3860.386
3138533PONTONDP
Adder
0.59764705882352940.508
3151541CLOVER2
80/20
11.98611.986
316316AC1-027 C
80/20
0.2820.282
313526AB2-022 C
80/20
0.3360.336
316017AA1-139 ULT1
80/20
0.9650.965
934611AD1-087 C
80/20
1.1911.191
3152431Z1-086 GT3
80/20
10.7510.75
316336AC2-165 C
80/20
9.7879.787
940641AE2-051 C
80/20
17.817.8
316303AF2-085
80/20
4.3034.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.18225.182
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.8619.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.3753.375
LAGNLTFEXP_LAGN->PJM
CLTF
6.9186.918
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.8954.895
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.42786.427
CPLELTFEXP_CPLE->PJM
CLTF
10.2710.27
TVALTFEXP_TVA->PJM
CLTF
5.5015.501
SIGELTFEXP_SIGE->PJM
CLTF
0.2110.211
NYPJM->LTFIMP_NY
CLTF
2.4542.454
LGEELTFEXP_LGEE->PJM
CLTF
1.0841.084
WECLTFEXP_WEC->PJM
CLTF
0.5370.537

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.22 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3678.49
MW Contribution:2.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.53764705882352950.457
934321AD1-056 C
Adder
6.3870588235294125.429
934331AD1-057 C
Adder
3.5635294117647063.029
958211AF2-115 C
Adder
2.14705882352941171.825
941031AE2-094 C
80/20
42.24742.247
3150831SPRUNCA
80/20
10.42510.425
3150841SPRUNCB
80/20
10.42510.425
966871AG1-558 C
Adder
2.56235294117647072.178
964211AG1-282 C
Adder
2.07882352941176451.767
3150801HOPHCF4
80/20
4.1494.149
3151081ELIZAR1
80/20
3.6013.601
960081AF2-299 C
Adder
1.95294117647058821.66
936261AD2-033 C
Adder
12.57294117647058810.687
961791AG1-021 C
Adder
1.71764705882352931.46
938771AE1-103 C
Adder
3.22705882352941182.743
963041AG1-153 C
Adder
5.8858823529411765.003
944011AF1-069 C
80/20
13.80413.804
966881AG1-559 C
Adder
2.45176470588235332.084
3150601CHESTF5
Adder
70.4105882352941159.849
944591AF1-124 C
80/20
51.4651.46
944601AF1-125 C
80/20
50.48850.488
3151101ELIZAR3
80/20
3.6473.647
941591AE2-156 C
80/20
20.20920.209
957481AF2-042 C
Adder
54.6470588235294146.45
940431AE2-027 C
80/20
14.61614.616
316294AC1-161 C
80/20
5.5975.597
944581AF1-123 C
80/20
51.27751.277
941101AE2-104 C
Adder
3.75764705882352963.194
940481AE2-033 C
Adder
17.43882352941176714.823
940541AE2-040 C
Adder
3.10117647058823562.636
927041AC1-191 C
Adder
10.2870588235294128.744
963611AG1-210 C
Adder
0.68235294117647060.58
961611AG1-000B C
Adder
17.92352941176470415.235
316375AC2-012 C
80/20
1.521.52
966621AG1-532 C
Adder
1.46470588235294131.245
934861AD1-115 C
Adder
-3.06-2.601
3152261N ANNA2
80/20
56.72156.721
3150771HOPHCF1
80/20
2.7332.733
942341AE2-247 C
Adder
1.67764705882352931.426
316274AC1-208 C
Adder
9.2835294117647067.891
962571AG1-106 C
Adder
2.84117647058823542.415
3151311EDGECMA
Adder
15.55647058823529613.223
957871AF2-081 C
Adder
11.2117647058823529.53
3150651CHESTF6
80/20
21.09121.091
3150861SPRUNCD
80/20
0.1870.187
936591AD2-074 C
Adder
5.8552941176470594.977
934521AD1-076 C
Adder
13.2411.254
934511AD1-075 C
Adder
9.1141176470588237.747
316263AC1-034 C
Adder
6.6529411764705895.655
959311AF2-222 C
Adder
16.0552941176470613.647
316240AF1-291 C
80/20
2.4442.444
944641AF1-129 C
80/20
115.84115.84
3150781HOPHCF2
80/20
2.7332.733
3150761HOPPOLC
80/20
1.7191.719
927021AC1-189 C
Adder
8.6023529411764727.312
926071AC1-086 C
Adder
21.9611764705882418.667
946281AF1-292 C
Adder
1.61647058823529431.374
964241AG1-285 C
Adder
12.1610.336
962561AG1-105 C
Adder
8.5058823529411767.23
939261AE1-157 C
Adder
14.10235294117647211.987
316169AC1-164 GEN
Adder
43.66588235294117537.116
3151091ELIZAR2
80/20
3.5383.538
316349AD2-085 C
Adder
3.87058823529411773.29
934501AD1-074 C
Adder
36.4552941176470630.987
961671AG1-007 C
Adder
0.95176470588235310.809
946301AF1-294 C
Adder
3.5305882352941183.001
942461AE2-259 C
Adder
9.4035294117647077.993
934621AD1-088 C
Adder
9.6105882352941188.169
942001AE2-212 C
80/20
2.4472.447
962861AG1-135 C
Adder
6.3647058823529425.41
943741AF1-042 C
Adder
3.06352941176470632.604
3152251N ANNA1
80/20
56.69756.697
3150851SPRUNCC
80/20
0.1870.187
944631AF1-128 C
Adder
44.0564705882352937.448
933291AC2-141 C
80/20
34.37234.372
3150921YORKTN3
Adder
133.0105882352941113.059
316233AE1-074 C
80/20
2.8742.874
940551AE2-041 C
Adder
7.6152941176470596.473
943461AF1-017 C
Adder
1.51764705882352961.29
316311AC2-079 C
Adder
6.4458823529411775.479
3137643SOCKMAN
Adder
0.74235294117647070.631
966661AG1-536 C
Adder
5.6341176470588234.789
939411AE1-173 C
80/20
99.71499.714
3150991CHESPKB
80/20
0.8130.813
933981AD1-022 C
Adder
9.4470588235294128.03
938531AE1-072 C
Adder
19.70000000000000316.745
3142366NRTHEST
80/20
0.2040.204
3150731STONECA
80/20
7.7657.765
935161AD1-151 C
Adder
18.16235294117647215.438
958161AF2-110 C
Adder
1.53294117647058831.303
964791AG1-342 C
Adder
3.38000000000000032.873
3143096IRON208
80/20
0.4940.494
958261AF2-120 C
Adder
6.5505882352941175.568
939191AE1-149 C
80/20
12.15312.153
957601AF2-054 C
Adder
2.26000000000000021.921
957861AF2-080 C
Adder
7.8129411764705896.641
3138533PONTONDP
Adder
0.63647058823529420.541
316257AC1-043 C
Adder
-6.121176470588236-5.203
316254AC1-120 C
Adder
-6.376470588235295-5.42
3150791HOPHCF3
80/20
2.7332.733
961951AG1-038 C
Adder
3.3858823529411772.878
316336AC2-165 C
Adder
10.1788235294117648.652
940641AE2-051 C
80/20
18.8818.88
943471AF1-018 C
Adder
7.6152941176470596.473
3152331SURRY 2
80/20
27.86527.865
316303AF2-085
80/20
4.4474.447
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.72830.728
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.33523.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.0414.041
LAGNLTFEXP_LAGN->PJM
CLTF
8.0268.026
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.4135.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69496.694
CPLELTFEXP_CPLE->PJM
CLTF
11.35211.352
TVALTFEXP_TVA->PJM
CLTF
6.4156.415
SIGELTFEXP_SIGE->PJM
CLTF
0.2560.256
NYPJM->LTFIMP_NY
CLTF
2.72.7
LGEELTFEXP_LGEE->PJM
CLTF
1.331.33
WECLTFEXP_WEC->PJM
CLTF
0.6540.654

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.99 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4412.36
MW Contribution:3.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.237647058823529430.202
923994AB2-040_E
Adder
5.8811764705882354.999
316088AB2-174 E
Adder
6.242352941176475.306
924322AB2-079 E O1
Adder
1.25764705882352931.069
946302AF1-294 E
Adder
2.9258823529411772.487
957481AF2-042 C
Adder
54.4729411764705946.302
923263AB1-132 E OP
Adder
5.80941176470588254.938
940481AE2-033 C
Adder
15.98588235294117513.588
940482AE2-033 E
Adder
10.777647058823539.161
940541AE2-040 C
Adder
2.84470588235294162.418
3151801S ANNAS2
50/50
1.2331.233
942002AE2-212 E
Adder
1.31294117647058851.116
940431AE2-027 C
Adder
11.3411764705882369.64
944581AF1-123 C
Adder
43.0529411764705936.595
941101AE2-104 C
Adder
3.1588235294117652.685
918512AA1-065 E OP
Adder
5.2011764705882364.421
934502AD1-074 E
Adder
16.13411764705882613.714
934512AD1-075 E
Adder
4.0341176470588243.429
924516AB2-100 E1
Adder
2.82.38
966621AG1-532 C
Adder
1.34705882352941191.145
919153AA1-139 E2
Adder
3.8505882352941183.273
924022AB2-043 E O1
Adder
4.8811764705882354.149
934501AD1-074 C
Adder
31.6952941176470626.941
924517AB2-100 E2
Adder
2.82.38
937226AE2-253 E
Adder
5.5047058823529414.679
946301AF1-294 C
Adder
3.45529411764705862.937
935172AD1-152 E
Adder
5.2941176470588234.5
942461AE2-259 C
Adder
9.2705882352941187.88
934621AD1-088 C
Adder
9.5599999999999998.126
957482AF2-042 E
Adder
36.31529411764705630.868
208901BRIS G2
50/50
-3.245-3.245
958502AF2-144 E
Adder
1.2764705882352941.085
316192AB2-158 C
50/50
3.5873.587
942001AE2-212 C
Adder
1.96941176470588241.674
924312AB2-078 E O1
Adder
1.25764705882352931.069
925612AC1-036 E
Adder
0.80588235294117660.685
3152441Z1-086 ST
50/50
19.40819.408
966001AG1-469 C
Adder
1.46235294117647091.243
961611AG1-000B C
Adder
13.98823529411764911.89
962572AG1-106 E
Adder
1.12941176470588230.96
957872AF2-081 E
Adder
4.0352941176470593.43
924162AB2-060 E OP
Adder
4.0294117647058823.425
964242AG1-285 E
Adder
7.8564705882352946.678
938562AE1-075 E
Adder
1.1082352941176470.942
3152251N ANNA1
50/50
93.18793.187
938552AE1-074 E
50/50
1.3051.305
926755AC1-161 E
Adder
12.19411764705882510.365
933291AC2-141 C
Adder
28.56588235294117724.281
925522AC1-027 E
Adder
1.14588235294117660.974
941102AE2-104 E
Adder
5.0223529411764714.269
3145256KINGFORK
Adder
0.93882352941176480.798
939192AE1-149 E
Adder
6.6670588235294125.667
939312AE1-162 E
Adder
1.29647058823529431.102
934065AD1-033 E
Adder
4.7282352941176474.019
3137643SOCKMAN
Adder
0.67882352941176470.577
913392Y1-086 E
Adder
2.0705882352941181.76
933502AC2-165 E
Adder
7.6611764705882356.512
940432AE2-027 E
Adder
7.5611764705882356.427
939411AE1-173 C
50/50
94.23794.237
934012AD1-025 E
Adder
8.6341176470588247.339
920692AA2-178 E
Adder
3.86941176470588263.289
966622AG1-532 E
Adder
0.89882352941176480.764
917122Z2-027 E
Adder
1.26588235294117671.076
3146326AYDLETT TAP
Adder
1.27764705882352961.086
938532AE1-072 E
Adder
8.6305882352941187.336
3147133PAMPLIN
Adder
0.92823529411764720.789
3152411Z1-086 GT1
50/50
11.14911.149
3152421Z1-086 GT2
50/50
11.14611.146
966002AG1-469 E
Adder
0.73058823529411760.621
316233AE1-074 C
50/50
2.5912.591
935162AD1-151 E
Adder
0.93764705882352950.797
943461AF1-017 C
Adder
1.26823529411764711.078
316311AC2-079 C
Adder
5.3905882352941184.582
932596AC2-079 E
Adder
8.7952941176470587.476
926071AC1-086 C
Adder
19.96117647058823516.967
961942AG1-037 E
Adder
0.317647058823529450.27
961941AG1-037 C
Adder
0.476470588235294150.405
923852AB2-025 E
Adder
1.15058823529411770.978
936262AD2-033 E
Adder
8.1458823529411776.924
958211AF2-115 C
Adder
2.1011764705882351.786
3151761LOISA E
50/50
4.9314.931
3151771S ANNAG1
50/50
2.42.4
3151791S ANNAG2
50/50
2.42.4
3151781S ANNAS1
50/50
1.2331.233
923862AB2-026 E
Adder
1.31.105
941031AE2-094 C
50/50
42.60742.607
941032AE2-094 E
50/50
19.08319.083
3150831SPRUNCA
Adder
8.2435294117647067.007
3150841SPRUNCB
Adder
8.2435294117647067.007
939412AE1-173 E
50/50
62.82462.824
926662AC1-147 E
Adder
1.24470588235294131.058
916192Z1-068 E
Adder
1.77058823529411761.505
957492AF2-043 E
Adder
1.341.139
943172AE2-346 E
Adder
0.5717647058823530.486
917332KELFORD E
Adder
1.54588235294117651.314
934522AD1-076 E
Adder
5.8670588235294124.987
940492AE2-034 E
Adder
2.90235294117647062.467
962571AG1-106 C
Adder
2.58235294117647032.195
918492AA1-063AE OP
Adder
3.87294117647058833.292
957871AF2-081 C
Adder
9.4164705882352948.004
961792AG1-021 E
Adder
1.4317647058823531.217
937482AD2-202 E
Adder
1.04941176470588250.892
3145506HICKORY
Adder
2.05411764705882361.746
946262AF1-291 E
Adder
1.261.071
3150651CHESTF6
Adder
16.10470588235294213.689
933292AC2-141 E
Adder
12.19411764705882510.365
934576AD1-082 E
Adder
4.1188235294117653.501
944602AF1-125 E
Adder
97.0388235294117782.483
943612AF1-032 E
Adder
0.87058823529411770.74
3147223TWITTYS
Adder
0.89294117647058820.759
959312AF2-222 E
Adder
10.4764705882352948.905
3151021BRUNSWICKG1
50/50
8.78.7
3151041BRUNSWICKG3
50/50
8.78.7
3152261N ANNA2
50/50
93.22693.226
940642AE2-051 E
50/50
12.32512.325
942341AE2-247 C
Adder
1.40235294117647061.192
943462AF1-017 E
Adder
2.06941176470588231.759
958162AF2-110 E
Adder
2.0505882352941181.743
946281AF1-292 C
Adder
1.48705882352941181.264
960082AF2-299 E
Adder
1.19764705882352951.018
916042Z1-036 E
Adder
26.91882352941176422.881
923832AB2-022 E
Adder
1.1682352941176470.993
964241AG1-285 C
Adder
11.78352941176470610.016
958212AF2-115 E
Adder
1.78941176470588231.521
938772AE1-103 E
Adder
3.8211764705882363.248
963042AG1-153 E
50/50
8.8728.872
925022AB2-158 E
50/50
9.5359.535
944592AF1-124 E
Adder
98.9435294117647184.102
944582AF1-123 E
Adder
98.5858823529411883.798
316349AD2-085 C
Adder
3.23411764705882382.749
935112AD1-144 E
Adder
0.8717647058823530.741
901082W1-029 E
Adder
30.02588235294117425.522
942462AE2-259 E
Adder
6.1800000000000015.253
3151731LOISA B
50/50
2.4192.419
3151751LOISA D
50/50
2.4192.419
3143316POE
Adder
1.30941176470588231.113
939191AE1-149 C
Adder
10.0011764705882348.501
926072AC1-086 E
Adder
9.0847058823529427.722
960081AF2-299 C
Adder
1.7964705882352941.527
3145413WATKINS
Adder
0.65411764705882360.556
936261AD2-033 C
Adder
12.2210.387
961791AG1-021 C
Adder
1.68117647058823551.429
938771AE1-103 C
Adder
2.7670588235294122.352
963041AG1-153 C
50/50
5.9155.915
3151051BRUNSWICKS1
50/50
18.07518.075
944011AF1-069 C
50/50
13.92113.921
927226AC1-216 E
Adder
6.6694117647058825.669
944591AF1-124 C
Adder
43.2058823529411836.725
944601AF1-125 C
Adder
42.3894117647058836.031
941591AE2-156 C
Adder
16.83647058823529414.311
936666AD2-085 E
Adder
5.2764705882352954.485
933981AD1-022 C
Adder
8.247.004
900672V4-068 E
Adder
0.33764705882352940.287
938531AE1-072 C
Adder
16.55647058823529614.073
924302AB2-077 E O1
Adder
1.25764705882352931.069
3145393UNCAMP
Adder
5.7482352941176484.886
935161AD1-151 C
Adder
13.84941176470588311.772
932046AC2-012 E
Adder
12.31647058823529410.469
958161AF2-110 C
Adder
1.28941176470588251.096
933982AD1-022 E
Adder
4.4858823529411773.813
3145946PLYMOUTH TP
Adder
0.30352941176470590.258
934612AD1-087 E
Adder
3.5835294117647063.046
934622AD1-088 E
Adder
4.6035294117647063.913
3152431Z1-086 GT3
50/50
11.14611.146
316336AC2-165 C
Adder
10.1788235294117648.652
940641AE2-051 C
50/50
18.48718.487
316084AB2-161 E
Adder
5.1694117647058834.394
934521AD1-076 C
Adder
11.5105882352941199.784
934511AD1-075 C
Adder
7.9235294117647066.735
919692AA2-053 E OP
Adder
4.00705882352941253.406
923573AB1-173 E OP
Adder
3.1364705882352942.666
3145723EMPORIA
Adder
0.414117647058823530.352
920042AA2-088 E OP
Adder
10.0447058823529418.538
925785AC1-054 E
Adder
3.24941176470588242.762
919152AA1-139 E1
Adder
3.8505882352941183.273
959311AF2-222 C
Adder
15.63529411764705813.29
3151031BRUNSWICKG2
50/50
8.78.7
316240AF1-291 C
Adder
1.88941176470588261.606
944641AF1-129 C
Adder
88.4505882352941375.183
924814AB2-134 E
Adder
10.9235294117647069.285
942342AE2-247 E
Adder
1.93529411764705881.645
946282AF1-292 E
Adder
0.99176470588235290.843
3138533PONTONDP
Adder
0.62235294117647070.529
944012AF1-069 E
50/50
5.4085.408
316303AF2-085
50/50
4.464.46
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.02528.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.37921.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.6863.686
LAGNLTFEXP_LAGN->PJM
CLTF
7.3867.386
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1255.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.8190.81
CPLELTFEXP_CPLE->PJM
CLTF
10.7510.75
TVALTFEXP_TVA->PJM
CLTF
5.8785.878
O66PJM->LTFIMP_O-066
CMTX_NF
35.46935.469
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5685.568
SIGELTFEXP_SIGE->PJM
CLTF
0.2320.232
NYPJM->LTFIMP_NY
CLTF
2.6122.612
LGEELTFEXP_LGEE->PJM
CLTF
1.1951.195
WECLTFEXP_WEC->PJM
CLTF
0.5950.595

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.18 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3902.62
MW Contribution:2.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.44235294117647060.376
316365AB2-100 C1
80/20
0.8620.862
957481AF2-042 C
80/20
51.00351.003
3151801S ANNAS2
80/20
1.3621.362
940431AE2-027 C
Adder
10.4682352941176488.898
316294AC1-161 C
80/20
4.314.31
944581AF1-123 C
80/20
39.90939.909
316185AD1-033 C
80/20
1.071.07
916191Z1-068 C
80/20
0.0380.038
941101AE2-104 C
80/20
2.9282.928
3147043LAWRENC
80/20
0.2730.273
940481AE2-033 C
80/20
14.89114.891
940541AE2-040 C
80/20
2.652.65
3152441Z1-086 ST
80/20
18.16818.168
966001AG1-469 C
80/20
1.9591.959
961611AG1-000B C
Adder
12.91058823529411910.974
316375AC2-012 C
80/20
1.1731.173
966621AG1-532 C
80/20
1.2551.255
316320Y1-086 C
80/20
0.1920.192
316388AE2-253 GEN
80/20
1.711.71
935171AD1-152 C
80/20
1.1991.199
3151021BRUNSWICKG1
80/20
8.1438.143
3151041BRUNSWICKG3
80/20
8.1438.143
934861AD1-115 C
Adder
2.8482352941176472.421
3152261N ANNA2
80/20
89.07389.073
942341AE2-247 C
80/20
1.2991.299
316246AF1-032 C
80/20
0.2480.248
934521AD1-076 C
Adder
10.6788235294117659.077
934511AD1-075 C
Adder
7.3517647058823536.249
316263AC1-034 C
Adder
5.6858823529411774.833
316087AB2-174 C
80/20
1.0461.046
316321Z2-027 C
80/20
0.3170.317
959311AF2-222 C
Adder
14.6623529411764712.463
937481AD2-202 C
80/20
0.3360.336
3151031BRUNSWICKG2
80/20
8.1438.143
316240AF1-291 C
Adder
1.7435294117647061.482
944641AF1-129 C
Adder
81.5517647058823669.319
316036AC1-147 C
80/20
0.320.32
316305AF2-043 C
80/20
0.3030.303
960081AF2-299 C
80/20
1.6731.673
936261AD2-033 C
Adder
11.4505882352941189.733
961791AG1-021 C
Adder
1.57882352941176471.342
938771AE1-103 C
80/20
2.5672.567
963041AG1-153 C
80/20
5.5365.536
3151051BRUNSWICKS1
80/20
16.91816.918
316170AC1-121 C
80/20
2.7242.724
944011AF1-069 C
80/20
13.03613.036
316045AC1-158 C2
80/20
19.41919.419
944591AF1-124 C
80/20
40.05140.051
944601AF1-125 C
80/20
39.29539.295
3151101ELIZAR3
80/20
2.8172.817
941591AE2-156 C
80/20
15.615.6
934501AD1-074 C
Adder
29.40470588235294324.994
961671AG1-007 C
Adder
0.80588235294117660.685
946301AF1-294 C
Adder
3.2458823529411762.759
942461AE2-259 C
Adder
8.7329411764705887.423
934621AD1-088 C
80/20
8.9588.958
208901BRIS G2
80/20
-3.11-3.11
316192AB2-158 C
80/20
3.6253.625
942001AE2-212 C
Adder
1.82117647058823541.548
3156056W1-029WIND
80/20
0.6760.676
3152411Z1-086 GT1
80/20
10.43710.437
3152421Z1-086 GT2
80/20
10.43410.434
316233AE1-074 C
80/20
2.4172.417
943461AF1-017 C
80/20
1.1751.175
316311AC2-079 C
80/20
4.9964.996
316018AA1-139 ULT2
80/20
0.9420.942
3152251N ANNA1
80/20
89.03589.035
3150851SPRUNCC
80/20
0.1370.137
933291AC2-141 C
80/20
26.46526.465
3150921YORKTN3
Adder
90.5694117647058876.984
3137643SOCKMAN
Adder
0.6317647058823530.537
3151741LOISA C
80/20
2.7082.708
3151721LOISA A
80/20
2.6942.694
939411AE1-173 C
80/20
87.96287.962
316381AD1-082 C
80/20
1.0891.089
3150991CHESPKB
80/20
0.6270.627
927021AC1-189 C
Adder
7.2364705882352946.151
926071AC1-086 C
Adder
18.5623529411764715.778
946281AF1-292 C
80/20
1.3851.385
964241AG1-285 C
Adder
11.0294117647058829.375
962561AG1-105 C
Adder
7.70470588235294156.549
316044AC1-158 C1
80/20
19.41919.419
3151091ELIZAR2
80/20
2.7332.733
316349AD2-085 C
80/20
2.9972.997
934321AD1-056 C
Adder
5.4329411764705894.618
934331AD1-057 C
Adder
3.0305882352941182.576
958211AF2-115 C
Adder
1.97411764705882351.678
3151531CLOVER1
80/20
11.76811.768
208900BRIS G1
80/20
-2.628-2.628
3151761LOISA E
80/20
5.5225.522
3151771S ANNAG1
80/20
2.6512.651
3151791S ANNAG2
80/20
2.6512.651
3151781S ANNAS1
80/20
1.3621.362
316258AE1-075 C
80/20
0.3460.346
941031AE2-094 C
80/20
39.89839.898
3150831SPRUNCA
Adder
7.6235294117647066.48
3150841SPRUNCB
Adder
7.6235294117647066.48
3151081ELIZAR1
80/20
2.7822.782
316274AC1-208 C
Adder
7.857647058823536.679
962571AG1-106 C
Adder
2.40117647058823552.041
3151311EDGECMA
Adder
13.28823529411764811.295
957871AF2-081 C
80/20
8.7288.728
316405AF2-144 C
80/20
0.2940.294
3150651CHESTF6
Adder
14.84823529411764812.621
3150861SPRUNCD
80/20
0.1370.137
964791AG1-342 C
Adder
3.06352941176470632.604
3151731LOISA B
80/20
2.7082.708
3151751LOISA D
80/20
2.7082.708
316313AB2-026 C
80/20
0.3770.377
316164AC1-076_C
80/20
1.1141.114
939191AE1-149 C
80/20
9.2629.262
3150981CHESPKA
80/20
0.3780.378
933981AD1-022 C
Adder
7.6458823529411766.499
938531AE1-072 C
80/20
15.34615.346
3150731STONECA
Adder
5.3258823529411774.527
935161AD1-151 C
Adder
12.7647058823529410.85
316083AB2-161 C
80/20
0.4780.478
958161AF2-110 C
80/20
1.1951.195
313526AB2-022 C
80/20
0.3280.328
316017AA1-139 ULT1
80/20
0.9420.942
934611AD1-087 C
80/20
1.1591.159
3152431Z1-086 GT3
80/20
10.43410.434
316336AC2-165 C
80/20
9.6099.609
940641AE2-051 C
80/20
17.2917.29
957861AF2-080 C
Adder
6.57294117647058855.587
316023AB2-100 C2
80/20
0.8620.862
316315AB2-025 C
80/20
0.3750.375
3138533PONTONDP
Adder
0.58470588235294120.497
3151541CLOVER2
80/20
11.65811.658
316257AC1-043 C
Adder
5.697647058823534.843
316254AC1-120 C
80/20
7.9327.932
316316AC1-027 C
80/20
0.2750.275
316303AF2-085
80/20
4.1844.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.96121.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.49718.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.0623.062
LAGNLTFEXP_LAGN->PJM
CLTF
6.5316.531
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.744.74
CBM South 2LTFEXP_CBM-S2->PJM
CBM
83.40383.403
CPLELTFEXP_CPLE->PJM
CLTF
9.9459.945
TVALTFEXP_TVA->PJM
CLTF
5.1955.195
SIGELTFEXP_SIGE->PJM
CLTF
0.1910.191
NYPJM->LTFIMP_NY
CLTF
2.5322.532
LGEELTFEXP_LGEE->PJM
CLTF
0.9710.971
WECLTFEXP_WEC->PJM
CLTF
0.4740.474

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.07 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3866.79
MW Contribution:2.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.52705882352941180.448
934321AD1-056 C
Adder
6.2529411764705895.315
934331AD1-057 C
Adder
3.4882352941176472.965
958211AF2-115 C
Adder
2.12470588235294141.806
941031AE2-094 C
80/20
41.37341.373
3150831SPRUNCA
80/20
10.21910.219
3150841SPRUNCB
80/20
10.21910.219
966871AG1-558 C
Adder
2.50941176470588222.133
964211AG1-282 C
Adder
2.0317647058823531.727
3150801HOPHCF4
80/20
4.0644.064
3151081ELIZAR1
80/20
3.5273.527
960081AF2-299 C
Adder
1.91411764705882351.627
936261AD2-033 C
Adder
12.4023529411764710.542
961791AG1-021 C
Adder
1.70000000000000021.445
938771AE1-103 C
Adder
3.162.686
963041AG1-153 C
Adder
5.7647058823529424.9
944011AF1-069 C
80/20
13.51813.518
316045AC1-158 C2
80/20
14.96214.962
966881AG1-559 C
Adder
2.3964705882352942.037
3150601CHESTF5
Adder
68.9811764705882458.634
944591AF1-124 C
80/20
50.39950.399
944601AF1-125 C
80/20
49.44749.447
3151101ELIZAR3
80/20
3.5723.572
941591AE2-156 C
80/20
19.79319.793
957481AF2-042 C
Adder
53.64117647058823545.595
940431AE2-027 C
80/20
14.31814.318
316294AC1-161 C
80/20
5.4825.482
944581AF1-123 C
80/20
50.22150.221
941101AE2-104 C
Adder
3.683.128
940481AE2-033 C
Adder
17.08117647058823614.519
940541AE2-040 C
Adder
3.03764705882352942.582
927041AC1-191 C
Adder
10.0729411764705888.562
963611AG1-210 C
Adder
0.66705882352941170.567
961611AG1-000B C
Adder
17.55647058823529614.923
316375AC2-012 C
80/20
1.4881.488
966621AG1-532 C
Adder
1.43529411764705881.22
3152261N ANNA2
80/20
55.34655.346
3150771HOPHCF1
80/20
2.6772.677
942341AE2-247 C
Adder
1.64235294117647061.396
316274AC1-208 C
Adder
9.0917647058823537.728
962571AG1-106 C
Adder
2.7823529411764712.365
3151311EDGECMA
Adder
15.22352941176470512.94
957871AF2-081 C
Adder
10.989.333
3150651CHESTF6
80/20
20.66420.664
3150861SPRUNCD
80/20
0.1830.183
936591AD2-074 C
Adder
5.7258823529411764.867
934521AD1-076 C
Adder
12.96470588235294111.02
934511AD1-075 C
Adder
8.9247058823529427.586
316263AC1-034 C
Adder
6.5105882352941185.534
959311AF2-222 C
Adder
15.85294117647058913.475
316240AF1-291 C
80/20
2.3942.394
944641AF1-129 C
80/20
113.49113.49
3150781HOPHCF2
80/20
2.6772.677
3150761HOPPOLC
80/20
1.6841.684
927021AC1-189 C
Adder
8.4188235294117647.156
926071AC1-086 C
Adder
21.50823529411764718.282
946281AF1-292 C
Adder
1.58470588235294121.347
964241AG1-285 C
Adder
11.97764705882352810.181
962561AG1-105 C
Adder
8.3588235294117657.105
316044AC1-158 C1
80/20
14.96214.962
939261AE1-157 C
Adder
13.77647058823529511.71
316169AC1-164 GEN
Adder
42.77176470588235436.356
3151091ELIZAR2
80/20
3.4653.465
316349AD2-085 C
Adder
3.79058823529411763.222
934501AD1-074 C
Adder
35.6976470588235330.343
961671AG1-007 C
Adder
0.9317647058823530.792
946301AF1-294 C
Adder
3.4941176470588242.97
942461AE2-259 C
Adder
9.347.939
934621AD1-088 C
Adder
9.4482352941176488.031
316192AB2-158 C
80/20
2.1182.118
942001AE2-212 C
80/20
2.3972.397
962861AG1-135 C
Adder
6.222352941176475.289
943741AF1-042 C
Adder
2.9964705882352942.547
3152251N ANNA1
80/20
55.32355.323
3150851SPRUNCC
80/20
0.1830.183
944631AF1-128 C
Adder
43.1623529411764736.688
933291AC2-141 C
80/20
33.66433.664
3150921YORKTN3
Adder
130.26705882352942110.727
316233AE1-074 C
80/20
2.8192.819
940551AE2-041 C
Adder
7.4541176470588246.336
943461AF1-017 C
Adder
1.48588235294117641.263
316311AC2-079 C
Adder
6.3129411764705885.366
3137643SOCKMAN
Adder
0.72705882352941180.618
966661AG1-536 C
Adder
5.5082352941176484.682
939411AE1-173 C
80/20
97.64897.648
3150991CHESPKB
80/20
0.7960.796
933981AD1-022 C
Adder
9.2505882352941197.863
938531AE1-072 C
Adder
19.2929411764705916.399
3142366NRTHEST
80/20
0.20.2
3150731STONECA
80/20
7.6067.606
935161AD1-151 C
Adder
17.79176470588235415.123
958161AF2-110 C
Adder
1.50117647058823531.276
964791AG1-342 C
Adder
3.32117647058823542.823
316164AC1-076_C
80/20
0.9930.993
3143096IRON208
80/20
0.4840.484
958261AF2-120 C
Adder
6.4035294117647065.443
939191AE1-149 C
80/20
11.90511.905
957601AF2-054 C
Adder
2.2117647058823531.88
957861AF2-080 C
Adder
7.6458823529411766.499
3138533PONTONDP
Adder
0.62941176470588240.535
3150791HOPHCF3
80/20
2.6772.677
961951AG1-038 C
Adder
3.3117647058823532.815
316336AC2-165 C
Adder
10.1094117647058828.593
940641AE2-051 C
80/20
18.48818.488
943471AF1-018 C
Adder
7.4541176470588246.336
3152331SURRY 2
80/20
27.29427.294
316303AF2-085
80/20
4.3634.363
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.65727.657
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.08222.082
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.7473.747
LAGNLTFEXP_LAGN->PJM
CLTF
7.6777.677
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.2865.286
CBM South 2LTFEXP_CBM-S2->PJM
CBM
94.17394.173
CPLELTFEXP_CPLE->PJM
CLTF
11.08811.088
TVALTFEXP_TVA->PJM
CLTF
6.1396.139
SIGELTFEXP_SIGE->PJM
CLTF
0.2370.237
NYPJM->LTFIMP_NY
CLTF
2.8062.806
LGEELTFEXP_LGEE->PJM
CLTF
1.2221.222
WECLTFEXP_WEC->PJM
CLTF
0.5950.595

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.55 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4631.32
MW Contribution:3.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961942AG1-037 E
Adder
0.311764705882352940.265
961941AG1-037 C
Adder
0.46705882352941180.397
923852AB2-025 E
Adder
1.1282352941176470.959
936262AD2-033 E
Adder
8.0141176470588256.812
958211AF2-115 C
Adder
2.0717647058823531.761
316141AB2-099 E
Adder
0.234117647058823540.199
923994AB2-040_E
Adder
5.76941176470588254.904
316088AB2-174 E
Adder
6.1235294117647065.205
924322AB2-079 E O1
Adder
1.23529411764705891.05
946302AF1-294 E
Adder
2.88470588235294122.452
957481AF2-042 C
Adder
53.3270588235294245.328
3151801S ANNAS2
50/50
1.381.38
942002AE2-212 E
Adder
1.2952941176470591.101
940431AE2-027 C
Adder
11.2058823529411789.525
944581AF1-123 C
Adder
42.37411764705882436.018
941101AE2-104 C
Adder
3.10941176470588232.643
923263AB1-132 E OP
Adder
5.697647058823534.843
940481AE2-033 C
Adder
15.6752941176470613.324
940482AE2-033 E
Adder
10.5670588235294118.982
940541AE2-040 C
Adder
2.78823529411764742.37
924312AB2-078 E O1
Adder
1.23529411764705891.05
925612AC1-036 E
Adder
0.79294117647058830.674
966001AG1-469 C
50/50
1.9871.987
925672AC1-043 E
Adder
9.4635294117647078.044
926740AC1-158 E2
50/50
50.96750.967
961611AG1-000B C
Adder
13.8152941176470611.743
918512AA1-065 E OP
Adder
5.1070588235294124.341
934502AD1-074 E
Adder
15.85176470588235313.474
934512AD1-075 E
Adder
3.96235294117647063.368
924516AB2-100 E1
Adder
2.74588235294117672.334
966621AG1-532 C
Adder
1.32117647058823541.123
919153AA1-139 E2
Adder
3.78941176470588253.221
924022AB2-043 E O1
Adder
4.7941176470588244.075
3147223TWITTYS
Adder
0.87882352941176480.747
959312AF2-222 E
Adder
10.3129411764705888.766
934861AD1-115 C
Adder
2.92.465
3152261N ANNA2
50/50
89.60989.609
940642AE2-051 E
50/50
12.05212.052
942341AE2-247 C
Adder
1.38000000000000011.173
943462AF1-017 E
Adder
2.03764705882352941.732
958162AF2-110 E
Adder
2.01764705882352931.715
934521AD1-076 C
Adder
11.3094117647058829.613
934511AD1-075 C
Adder
7.7847058823529426.617
919692AA2-053 E OP
Adder
3.93176470588235333.342
923573AB1-173 E OP
Adder
3.07647058823529432.615
934501AD1-074 C
Adder
31.13882352941176626.468
924517AB2-100 E2
Adder
2.74588235294117672.334
937226AE2-253 E
Adder
5.4188235294117654.606
946301AF1-294 C
Adder
3.4070588235294122.896
935172AD1-152 E
Adder
5.1847058823529414.407
942461AE2-259 C
Adder
9.1658823529411777.791
934621AD1-088 C
Adder
9.3717647058823547.966
957482AF2-042 E
Adder
35.55176470588235630.219
208901BRIS G2
50/50
-3.356-3.356
958502AF2-144 E
Adder
1.2588235294117651.07
316192AB2-158 C
50/50
3.6573.657
942001AE2-212 C
Adder
1.94235294117647061.651
939192AE1-149 E
Adder
6.5694117647058825.584
939312AE1-162 E
Adder
1.27764705882352961.086
934065AD1-033 E
Adder
4.6541176470588243.956
920692AA2-178 E
Adder
3.8023529411764713.232
966622AG1-532 E
Adder
0.88117647058823530.749
917122Z2-027 E
Adder
1.24470588235294131.058
3146326AYDLETT TAP
Adder
1.25764705882352931.069
938532AE1-072 E
Adder
8.4941176470588247.22
3147133PAMPLIN
Adder
0.91529411764705890.778
966002AG1-469 E
50/50
0.9930.993
926739AC1-158 E1
50/50
50.96750.967
316233AE1-074 C
Adder
2.5458823529411772.164
935162AD1-151 E
Adder
9.1294117647058827.76
943461AF1-017 C
Adder
1.2482352941176471.061
316311AC2-079 C
Adder
5.3070588235294124.511
932596AC2-079 E
Adder
8.6588235294117667.36
926214AC1-099 E
Adder
1.1082352941176470.942
932632AC2-084 E
Adder
2.96705882352941152.522
962572AG1-106 E
Adder
1.1082352941176470.942
957872AF2-081 E
Adder
3.9717647058823533.376
924162AB2-060 E OP
Adder
3.95764705882352933.364
964242AG1-285 E
Adder
7.7211764705882356.563
934862AD1-115 E
Adder
4.73176470588235354.022
938562AE1-075 E
Adder
1.0917647058823530.928
3152251N ANNA1
50/50
89.57189.571
938552AE1-074 E
Adder
1.28235294117647071.09
926755AC1-161 E
Adder
12.0070588235294110.206
933291AC2-141 C
Adder
28.12941176470588223.91
925522AC1-027 E
Adder
1.1282352941176470.959
941102AE2-104 E
Adder
4.9423529411764714.201
3145256KINGFORK
Adder
0.92470588235294130.786
3137643SOCKMAN
Adder
0.66588235294117650.566
913392Y1-086 E
Adder
2.03647058823529431.731
933502AC2-165 E
Adder
7.5705882352941176.435
3151741LOISA C
50/50
2.7452.745
3151721LOISA A
50/50
2.7312.731
940432AE2-027 E
Adder
7.4705882352941186.35
939411AE1-173 C
Adder
92.2811764705882478.439
934012AD1-025 E
Adder
8.5352941176470597.255
926071AC1-086 C
Adder
19.57647058823529616.64
946281AF1-292 C
Adder
1.45882352941176461.24
960082AF2-299 E
Adder
1.17529411764705880.999
916042Z1-036 E
Adder
26.4694117647058822.499
923832AB2-022 E
Adder
1.14941176470588240.977
964241AG1-285 C
Adder
11.5811764705882349.844
962561AG1-105 C
Adder
8.0894117647058836.876
958212AF2-115 E
Adder
1.76470588235294111.5
938772AE1-103 E
Adder
3.75764705882352963.194
963042AG1-153 E
Adder
8.6682352941176477.368
925022AB2-158 E
50/50
9.7219.721
316044AC1-158 C1
50/50
19.48619.486
944592AF1-124 E
Adder
97.3823529411764882.775
944582AF1-123 E
Adder
97.0317647058823782.477
316349AD2-085 C
Adder
3.1835294117647062.706
935112AD1-144 E
Adder
0.85764705882352940.729
208900BRIS G1
50/50
-2.836-2.836
3151761LOISA E
50/50
5.5965.596
3151771S ANNAG1
50/50
2.6852.685
3151791S ANNAG2
50/50
2.6852.685
3151781S ANNAS1
50/50
1.381.38
923862AB2-026 E
Adder
1.28117647058823541.089
941031AE2-094 C
50/50
41.61841.618
941032AE2-094 E
50/50
18.6418.64
3150831SPRUNCA
Adder
8.1435294117647056.922
3150841SPRUNCB
Adder
8.1435294117647056.922
939412AE1-173 E
Adder
61.5211764705882452.293
926662AC1-147 E
Adder
1.22588235294117661.042
916192Z1-068 E
Adder
1.74235294117647071.481
957492AF2-043 E
Adder
1.31882352941176471.121
943172AE2-346 E
Adder
0.56117647058823530.477
917332KELFORD E
Adder
1.51764705882352961.29
925122AB2-169 E
Adder
5.2764705882352954.485
934522AD1-076 E
Adder
5.7635294117647064.899
940492AE2-034 E
Adder
2.85176470588235282.424
316274AC1-208 C
Adder
8.2905882352941187.047
962571AG1-106 C
Adder
2.53176470588235342.152
918492AA1-063AE OP
Adder
3.80117647058823543.231
957871AF2-081 C
Adder
9.2670588235294127.877
961792AG1-021 E
Adder
1.4117647058823531.2
937482AD2-202 E
Adder
1.02705882352941180.873
3145506HICKORY
Adder
2.02235294117647071.719
946262AF1-291 E
Adder
1.24470588235294131.058
3150651CHESTF6
Adder
15.92588235294117813.537
933292AC2-141 E
Adder
12.0070588235294110.206
934576AD1-082 E
Adder
4.0564705882352943.448
944602AF1-125 E
Adder
95.5082352941176581.182
943612AF1-032 E
Adder
0.85764705882352940.729
926206AC1-098 E
Adder
3.35647058823529452.853
901082W1-029 E
Adder
29.54000000000000325.109
942462AE2-259 E
Adder
6.1105882352941175.194
3151731LOISA B
50/50
2.7452.745
3151751LOISA D
50/50
2.7452.745
3143316POE
Adder
1.28823529411764711.095
316164AC1-076_C
50/50
1.1311.131
939191AE1-149 C
Adder
9.8529411764705898.375
926072AC1-086 E
Adder
8.9094117647058837.573
960081AF2-299 C
Adder
1.76235294117647071.498
3145413WATKINS
Adder
0.64235294117647070.546
936261AD2-033 C
Adder
12.02117647058823610.218
962562AG1-105 E
Adder
5.3929411764705884.584
961791AG1-021 C
Adder
1.65764705882352951.409
938771AE1-103 C
Adder
2.72117647058823582.313
963041AG1-153 C
Adder
5.7788235294117654.912
316170AC1-121 C
50/50
2.7692.769
944011AF1-069 C
50/50
13.59813.598
316045AC1-158 C2
50/50
19.48619.486
925332AB2-190 E
Adder
6.8164705882352945.794
927226AC1-216 E
Adder
6.5917647058823535.603
944591AF1-124 C
Adder
42.5247058823529436.146
944601AF1-125 C
Adder
41.7211764705882435.463
941591AE2-156 C
Adder
16.57647058823529614.09
936666AD2-085 E
Adder
5.195294117647064.416
933981AD1-022 C
Adder
8.0941176470588236.88
900672V4-068 E
Adder
0.33058823529411770.281
938531AE1-072 C
Adder
16.29411764705882213.85
924302AB2-077 E O1
Adder
1.23529411764705891.05
3145393UNCAMP
Adder
5.65176470588235354.804
926486AC1-120 E
50/50
4.1534.153
935161AD1-151 C
Adder
13.69411764705882511.64
932046AC2-012 E
Adder
12.12705882352941210.308
958161AF2-110 C
Adder
1.26823529411764711.078
933982AD1-022 E
Adder
4.4070588235294123.746
3145946PLYMOUTH TP
Adder
0.29882352941176470.254
927146AC1-208 E
Adder
1.16941176470588240.994
934612AD1-087 E
Adder
3.50941176470588272.983
934622AD1-088 E
Adder
4.5117647058823533.835
316336AC2-165 C
Adder
10.0588235294117668.55
926004AC1-076_E
50/50
6.486.48
940641AE2-051 C
50/50
18.07818.078
316084AB2-161 E
Adder
5.0917647058823544.328
3145723EMPORIA
Adder
0.405882352941176470.345
920042AA2-088 E OP
Adder
9.8670588235294128.387
925785AC1-054 E
Adder
3.18705882352941172.709
919152AA1-139 E1
Adder
3.78941176470588253.221
959311AF2-222 C
Adder
15.39294117647058813.084
926502AC1-121 E
50/50
1.3031.303
316240AF1-291 C
Adder
1.86705882352941191.587
944641AF1-129 C
Adder
87.4717647058823574.351
924814AB2-134 E
Adder
10.7988235294117659.179
942342AE2-247 E
Adder
1.90588235294117661.62
946282AF1-292 E
Adder
0.97294117647058820.827
3138533PONTONDP
Adder
0.61411764705882350.522
316257AC1-043 C
Adder
5.84.93
316254AC1-120 C
50/50
8.0618.061
944012AF1-069 E
50/50
5.2835.283
316303AF2-085
50/50
4.3644.364
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.22125.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.23820.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.4183.418
LAGNLTFEXP_LAGN->PJM
CLTF
7.0687.068
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0035.003
CBM South 2LTFEXP_CBM-S2->PJM
CBM
88.42988.429
CPLELTFEXP_CPLE->PJM
CLTF
10.49610.496
TVALTFEXP_TVA->PJM
CLTF
5.6275.627
O66PJM->LTFIMP_O-066
CMTX_NF
36.7236.72
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7645.764
SIGELTFEXP_SIGE->PJM
CLTF
0.2140.214
NYPJM->LTFIMP_NY
CLTF
2.7142.714
LGEELTFEXP_LGEE->PJM
CLTF
1.0981.098
WECLTFEXP_WEC->PJM
CLTF
0.5410.541
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 246_SRT-A'
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A'
 OPEN BRANCH FROM BUS 304183 TO BUS 314935 CKT 1   /*8WAKE 500 TT 500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314063 TO BUS 314916 CKT 1                /*6MORRSVL     230.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 568T575_SRT-A'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1   /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1   /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
314282 to 314285 ckt 1
314563 to 940480 ckt 1
314435 to 314282 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 314922 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314934 to 314916 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC100.11 %984.18B985.291.65
GD1DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 567_SRT-A
OPAC117.72 %934.92B1100.621.77
GD1DVP
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.74 %984.18B1020.961.65
GD1DVP
6CHOWAN-6PEMBROKE 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
OPAC102.05 %733.2B748.252.46
GD1DVP
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Base Case
OPAC109.02 %678.68A739.927.86
GD1DVP
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2092_SRT-A
OPAC166.69 %571.52B952.643.83
GD1DVP
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Base Case
OPAC111.43 %571.52A636.853.16
GD1DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
DVP_P1-2: LN 557_SRT-S
OPAC108.08 %879.84B950.941.78
GD1CPLE/DVP
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
RKYMT-WILS230_&_RKYMT-SHARPB115_SRT-S
OPAC106.07 %478.0B507.022.44
GD1DVP
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
OPAC102.75 %733.2B753.42.46
GD1DVP
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
DVP_P1-2: LN 2092_SRT-A
OPAC161.64 %571.52B923.833.83
GD1DVP
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Base Case
OPAC106.53 %571.52A608.853.16
GD1DVP
6PEMBROKE-6WALBMRL 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
OPAC118.52 %733.2B868.962.46
GD1DVP
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
OPAC116.77 %733.2B856.132.46
GD1DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Base Case
OPAC127.47 %678.68A865.087.86
GD1DVP
6THELMA-6LAKEVEW 230.0 kV Ckt 1 line
DVP_P1-2: LN 225_SRT-A
OPAC122.05 %441.8B539.222.96
GD1DVP
6THELMA-6LAKEVEW 230.0 kV Ckt 2 line
DVP_P1-2: LN 213_SRT-A
OPAC122.04 %441.8B539.1922.96
GD1DVP
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.68 %984.18B1020.421.65
GD1DVP
6WALBMRL-6S HERTFORD 230.0 kV Ckt 1 line
DVP_P1-2: LN 246_SRT-A
OPAC117.19 %733.2B859.242.46
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
OPAC104.12 %3220.44A3352.994.49
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC136.21 %2442.12B3326.44.98
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
OPAC109.93 %2858.0B3141.723.27
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
OPAC126.88 %1058.16B1342.551.68
GD1DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC106.42 %2442.12B2598.933.1
GD1DVP
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Base Case
OPAC124.4 %678.68A844.267.86

Details for 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.11 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:985.29
MW Contribution:1.65
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:96.98 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:954.41
MW Contribution:1.58
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.332941176470588240.283
961672AG1-007 E
Adder
0.188235294117647060.16
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
963041AG1-153 C
Adder
1.9482352941176471.656
963042AG1-153 E
Adder
2.92235294117647062.484
966621AG1-532 C
Adder
0.61294117647058830.521
966622AG1-532 E
Adder
0.408235294117647030.347
3145413WATKINS
Adder
0.26470588235294120.225
3145723EMPORIA
Adder
0.185882352941176470.158
3151311EDGECMA
Adder
5.5117647058823534.685
918492AA1-063AE OP
Adder
1.59411764705882361.355
918532AA1-067 E
Adder
0.251764705882352950.214
919692AA2-053 E OP
Adder
1.64941176470588241.402
920042AA2-088 E OP
Adder
4.0811764705882353.469
925785AC1-054 E
Adder
1.2082352941176471.027
927146AC1-208 E
Adder
1.51.275
934521AD1-076 C
Adder
4.377647058823533.721
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
944011AF1-069 C
Adder
4.6141176470588243.922
944012AF1-069 E
Adder
1.7917647058823531.523
960081AF2-299 C
Adder
0.81647058823529410.694
960082AF2-299 E
Adder
0.54470588235294130.463
316141AB2-099 E
Adder
0.095294117647058830.081
900672V4-068 E
Adder
0.136470588235294120.116
917342Z2-044 E
Adder
0.215294117647058830.183
922923AB1-081 E OP
Adder
1.321.122
923263AB1-132 E OP
Adder
2.582.193
923573AB1-173 E OP
Adder
1.36823529411764721.163
924162AB2-060 E OP
Adder
1.3117647058823531.115
924302AB2-077 E O1
Adder
0.41176470588235290.35
924312AB2-078 E O1
Adder
0.41176470588235290.35
924322AB2-079 E O1
Adder
0.41176470588235290.35
940492AE2-034 E
Adder
1.09058823529411760.927
941031AE2-094 C
Adder
14.12000000000000112.002
941032AE2-094 E
Adder
6.3247058823529425.376
946281AF1-292 C
Adder
0.67529411764705880.574
946282AF1-292 E
Adder
0.45058823529411770.383
957481AF2-042 C
Adder
17.0152941176470614.463
957482AF2-042 E
Adder
11.3435294117647069.642
957861AF2-080 C
Adder
2.7023529411764712.297
957862AF2-080 E
Adder
1.19764705882352951.018
3145393UNCAMP
Adder
2.3247058823529411.976
916042Z1-036 E
Adder
9.9682352941176488.473
938771AE1-103 C
Adder
1.11764705882352940.95
938772AE1-103 E
Adder
1.5435294117647061.312
3143316POE
50/50
1.0861.086
3145256KINGFORK
Adder
0.357647058823529430.304
3145506HICKORY
Adder
0.72352941176470590.615
3150651CHESTF6
50/50
21.89721.897
3150731STONECA
50/50
4.5124.512
3150761HOPPOLC
50/50
1.0021.002
3150771HOPHCF1
50/50
1.5941.594
3150781HOPHCF2
50/50
1.5941.594
3150791HOPHCF3
50/50
1.5941.594
3150801HOPHCF4
50/50
2.4192.419
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
926662AC1-147 E
Adder
0.452941176470588240.385
926755AC1-161 E
Adder
3.78588235294117673.218
927226AC1-216 E
Adder
4.122352941176473.504
935112AD1-144 E
Adder
0.33176470588235290.282
942341AE2-247 C
Adder
0.68470588235294120.582
942342AE2-247 E
Adder
0.94470588235294130.803
943461AF1-017 C
Adder
0.61882352941176480.526
943462AF1-017 E
Adder
1.00941176470588250.858
943612AF1-032 E
Adder
0.320.272
316132AB2-190 C
50/50
2.4122.412
913392Y1-086 E
Adder
0.74470588235294120.633
916192Z1-068 E
Adder
0.63294117647058830.538
923832AB2-022 E
Adder
0.421176470588235260.358
923852AB2-025 E
Adder
0.6317647058823530.537
939312AE1-162 E
Adder
0.5717647058823530.486
946262AF1-291 E
50/50
1.6321.632
957492AF2-043 E
Adder
0.49294117647058820.419
901082W1-029 E
Adder
10.9870588235294139.339
917122Z2-027 E
Adder
0.457647058823529460.389
925332AB2-190 E
50/50
4.6914.691
925522AC1-027 E
Adder
0.410588235294117640.349
942001AE2-212 C
50/50
2.1112.111
942002AE2-212 E
50/50
1.4081.408
957871AF2-081 C
Adder
3.34117647058823542.84
957872AF2-081 E
Adder
1.4317647058823531.217
958161AF2-110 C
Adder
0.51764705882352950.44
958162AF2-110 E
Adder
0.82470588235294120.701
917512Z2-088 E OP1
Adder
1.73411764705882351.474
926071AC1-086 C
Adder
8.8647058823529427.535
926072AC1-086 E
Adder
4.0352941176470593.43
927021AC1-189 C
Adder
2.97529411764705862.529
927022AC1-189 E
Adder
1.48235294117647071.26
933291AC2-141 C
Adder
8.8694117647058827.539
933292AC2-141 E
Adder
3.78588235294117673.218
934621AD1-088 C
Adder
2.86941176470588262.439
934622AD1-088 E
Adder
1.38117647058823521.174
939411AE1-173 C
Adder
31.5352941176470626.805
939412AE1-173 E
Adder
21.0235294117647117.87
934012AD1-025 E
Adder
5.3364705882352944.536
933981AD1-022 C
Adder
3.162.686
933982AD1-022 E
Adder
1.721.462
962572AG1-106 E
Adder
0.50117647058823530.426
962571AG1-106 C
Adder
1.14705882352941170.975
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
3146326AYDLETT TAP
Adder
0.455294117647058850.387
316240AF1-291 C
50/50
2.4482.448
316263AC1-034 C
Adder
2.3517647058823531.999
316274AC1-208 C
Adder
3.3788235294117652.872
917332KELFORD E
Adder
0.61411764705882350.522
924516AB2-100 E1
Adder
1.36823529411764721.163
924517AB2-100 E2
Adder
1.36823529411764721.163
925595AC1-034 E
Adder
1.77411764705882361.508
926206AC1-098 E
Adder
1.35999999999999991.156
926214AC1-099 E
Adder
0.44941176470588240.382
934065AD1-033 E
Adder
1.6670588235294121.417
937226AE2-253 E
Adder
1.9482352941176471.656
918512AA1-065 E OP
Adder
2.04235294117647071.736
919153AA1-139 E2
Adder
1.36588235294117651.161
919152AA1-139 E1
Adder
1.36588235294117651.161
919710AA2-057 E
Adder
1.44823529411764731.231
920692AA2-178 E
Adder
1.4552941176470591.237
923994AB2-040_E
Adder
2.56588235294117652.181
924022AB2-043 E O1
Adder
1.60117647058823541.361
924152AB2-059 E OP
Adder
1.87058823529411791.59
924814AB2-134 E
Adder
6.7529411764705885.74
316083AB2-161 C
50/50
0.3210.321
316084AB2-161 E
50/50
3.213.21
925122AB2-169 E
Adder
2.04352941176470631.737
316088AB2-174 E
Adder
2.7588235294117652.345
932046AC2-012 E
Adder
4.4823529411764713.81
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
316381AD1-082 C
50/50
0.7330.733
934576AD1-082 E
50/50
2.5582.558
316349AD2-085 C
Adder
1.57882352941176471.342
936666AD2-085 E
Adder
2.5752941176470592.189
961611AG1-000B C
Adder
7.342352941176476.241
941591AE2-156 C
Adder
6.1141176470588245.197
944581AF1-123 C
Adder
15.03411764705882412.779
944582AF1-123 E
Adder
34.4258823529411829.262
944591AF1-124 C
Adder
15.08705882352941312.824
944592AF1-124 E
Adder
34.55058823529411429.368
944601AF1-125 C
Adder
14.80235294117647312.582
944602AF1-125 E
Adder
33.8847058823529428.802
964241AG1-285 C
Adder
3.85882352941176483.28
964242AG1-285 E
Adder
2.5717647058823532.186
3137643SOCKMAN
Adder
0.288235294117647030.245
932632AC2-084 E
Adder
1.20235294117647061.022
934321AD1-056 C
Adder
2.3988235294117652.039
934322AD1-056 E
Adder
1.30117647058823541.106
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934501AD1-074 C
Adder
12.05529411764705810.247
934502AD1-074 E
Adder
6.1364705882352945.216
934511AD1-075 C
Adder
3.01411764705882362.562
934512AD1-075 E
Adder
1.53411764705882361.304
934612AD1-087 E
Adder
1.1117647058823530.945
935161AD1-151 C
50/50
9.0229.022
935162AD1-151 E
50/50
6.0156.015
935172AD1-152 E
Adder
1.6435294117647061.397
937482AD2-202 E
Adder
0.32588235294117650.277
938531AE1-072 C
Adder
5.8905882352941185.007
938532AE1-072 E
Adder
3.07058823529411742.61
939191AE1-149 C
50/50
7.1377.137
939192AE1-149 E
50/50
4.7584.758
940431AE2-027 C
Adder
7.0447058823529425.988
940432AE2-027 E
Adder
4.6964705882352943.992
940481AE2-033 C
Adder
8.6517647058823537.354
940482AE2-033 E
Adder
5.8329411764705884.958
940541AE2-040 C
Adder
1.56117647058823541.327
940641AE2-051 C
Adder
6.0952941176470595.181
940642AE2-051 E
Adder
4.0635294117647063.454
941101AE2-104 C
Adder
1.26941176470588221.079
941102AE2-104 E
Adder
2.0188235294117651.716
944641AF1-129 C
50/50
120.262120.262
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.72 %
Rating:934.92 MVA
Rating Type:B
MVA to Mitigate:1100.62
MW Contribution:1.77
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:124.05 %
Rating:934.92 MVA
Rating Type:B
MVA to Mitigate:1159.8
MW Contribution:1.81
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.250588235294117670.213
961942AG1-037 E
Adder
0.167058823529411760.142
3145413WATKINS
Adder
0.371764705882352940.316
918492AA1-063AE OP
Adder
1.9235294117647061.635
919692AA2-053 E OP
Adder
1.9247058823529411.636
920042AA2-088 E OP
Adder
5.4247058823529414.611
934521AD1-076 C
Adder
6.4588235294117655.49
934522AD1-076 E
Adder
3.2917647058823532.798
943172AE2-346 E
Adder
0.30.255
316141AB2-099 E
Adder
0.124705882352941180.106
900672V4-068 E
Adder
0.178823529411764710.152
923263AB1-132 E OP
Adder
2.76588235294117672.351
940492AE2-034 E
Adder
1.67529411764705881.424
3145393UNCAMP
Adder
3.34588235294117632.844
916042Z1-036 E
Adder
16.12117647058823513.703
938771AE1-103 C
Adder
1.63411764705882371.389
938772AE1-103 E
Adder
2.25764705882352961.919
3141843SHACKLE
50/50
0.6030.603
3143316POE
Adder
0.72470588235294120.616
3145256KINGFORK
Adder
0.64941176470588250.552
3145506HICKORY
Adder
1.3035294117647061.108
3150601CHESTF5
Adder
61.6852.428
3150651CHESTF6
Adder
10.5635294117647058.979
3150731STONECA
Adder
5.1505882352941184.378
3150831SPRUNCA
Adder
4.643.944
3150841SPRUNCB
Adder
4.643.944
3150921YORKTN3
Adder
101.5176470588235486.29
925865AC1-065 E
50/50
18.90818.908
926412AC1-112 E
Adder
0.95058823529411770.808
926472AC1-118 E
Adder
1.07411764705882360.913
926662AC1-147 E
Adder
0.80941176470588230.688
926755AC1-161 E
Adder
7.7070588235294126.551
927226AC1-216 E
Adder
5.5894117647058834.751
934392AD1-063 E
50/50
1.2811.281
935112AD1-144 E
Adder
0.60235294117647060.512
936582AD2-073 E
Adder
1.1482352941176470.976
936591AD2-074 C
50/50
6.2326.232
936592AD2-074 E
50/50
10.16810.168
942341AE2-247 C
Adder
0.88823529411764710.755
942342AE2-247 E
Adder
1.22588235294117661.042
943461AF1-017 C
Adder
0.80352941176470590.683
943462AF1-017 E
Adder
1.31058823529411781.114
943612AF1-032 E
Adder
0.5564705882352940.473
943741AF1-042 C
50/50
3.2613.261
943742AF1-042 E
50/50
5.3215.321
944491AF1-114 C
Adder
5.0717647058823534.311
944492AF1-114 E
Adder
7.0035294117647065.953
961951AG1-038 C
50/50
3.6043.604
961952AG1-038 E
50/50
4.9774.977
966661AG1-536 C
50/50
6.0266.026
966662AG1-536 E
50/50
8.0978.097
316075AC2-137 C
50/50
0.4510.451
316076AC2-137 E
50/50
1.5851.585
316078AC2-138 E
Adder
1.04235294117647070.886
316156AD2-030 C
50/50
0.4250.425
316157AD2-030 E
50/50
1.331.33
913392Y1-086 E
Adder
1.29176470588235311.098
916192Z1-068 E
Adder
1.13647058823529410.966
923832AB2-022 E
Adder
0.72941176470588230.62
923842AB2-024 E
50/50
2.2272.227
923852AB2-025 E
Adder
0.53647058823529410.456
930122AB1-027 E
Adder
1.1682352941176470.993
939312AE1-162 E
Adder
0.95764705882352940.814
946262AF1-291 E
Adder
0.81058823529411760.689
957492AF2-043 E
Adder
0.85647058823529410.728
957601AF2-054 C
50/50
2.372.37
957602AF2-054 E
50/50
1.581.58
962861AG1-135 C
50/50
6.7996.799
962862AG1-135 E
50/50
4.5334.533
962962AG1-145 E
50/50
1.5371.537
963611AG1-210 C
Adder
0.74470588235294120.633
963612AG1-210 E
Adder
1.11764705882352940.95
964211AG1-282 C
50/50
2.3232.323
964212AG1-282 E
50/50
1.5491.549
901082W1-029 E
Adder
18.5929411764705915.804
917122Z2-027 E
Adder
0.78588235294117660.668
925332AB2-190 E
Adder
5.91411764705882355.027
925522AC1-027 E
Adder
0.73647058823529410.626
942001AE2-212 C
Adder
1.18941176470588221.011
942002AE2-212 E
Adder
0.79294117647058830.674
957832AF2-077 E
Adder
1.39411764705882371.185
957871AF2-081 C
Adder
5.94117647058823555.05
957872AF2-081 E
Adder
2.5458823529411772.164
957971AF2-091 C
Adder
1.7247058823529411.466
957972AF2-091 E
Adder
2.38117647058823542.024
958161AF2-110 C
Adder
0.81411764705882350.692
958162AF2-110 E
Adder
1.29411764705882361.1
3138116ELKO L286
50/50
1.6531.653
3141813NORNECK
Adder
0.99176470588235290.843
926071AC1-086 C
Adder
9.502352941176478.077
926072AC1-086 E
Adder
4.3247058823529423.676
933291AC2-141 C
Adder
18.0552941176470615.347
933292AC2-141 E
Adder
7.7070588235294126.551
939411AE1-173 C
Adder
43.0494117647058836.592
939412AE1-173 E
Adder
28.724.395
934012AD1-025 E
Adder
7.2364705882352946.151
933981AD1-022 C
Adder
4.5705882352941173.885
933982AD1-022 E
Adder
2.48823529411764752.115
962572AG1-106 E
Adder
0.53764705882352950.457
962571AG1-106 C
Adder
1.22941176470588221.045
3130536PAPERMILL
50/50
8.178.17
3145946PLYMOUTH TP
Adder
0.171764705882352930.146
3146326AYDLETT TAP
Adder
0.80352941176470590.683
316059AD1-063 C
50/50
0.3140.314
316159AE1-175 C
50/50
0.4180.418
316160AE1-175 E
50/50
1.2681.268
316169AC1-164 GEN
50/50
59.62859.628
316240AF1-291 C
Adder
1.21647058823529421.034
316314AB2-024 C
50/50
0.3640.364
316382AG1-145 C
50/50
0.3770.377
917332KELFORD E
Adder
0.78588235294117660.668
924516AB2-100 E1
Adder
1.31411764705882361.117
924517AB2-100 E2
Adder
1.31411764705882361.117
926785AC1-164_E
50/50
26.78926.789
934065AD1-033 E
Adder
3.0082352941176472.557
937226AE2-253 E
Adder
3.48117647058823552.959
939611AE1-191 C
50/50
1.5481.548
939612AE1-191 E
50/50
6.4276.427
316201AC1-065 C
50/50
1.8491.849
316404AE1-155 C
50/50
2.3762.376
939246AE1-155 E
50/50
9.7559.755
918512AA1-065 E OP
Adder
2.78823529411764742.37
919153AA1-139 E2
Adder
2.4294117647058822.065
919152AA1-139 E1
Adder
2.4294117647058822.065
920692AA2-178 E
Adder
2.23411764705882381.899
924814AB2-134 E
Adder
9.155294117647067.782
316084AB2-161 E
Adder
3.2882352941176472.795
925122AB2-169 E
Adder
2.8305882352941182.406
932046AC2-012 E
Adder
8.0047058823529426.804
316311AC2-079 C
Adder
3.4117647058823532.9
932596AC2-079 E
Adder
5.5670588235294124.732
316280AD1-041 C
50/50
0.9810.981
934146AD1-041 E
50/50
4.0174.017
934576AD1-082 E
Adder
2.622.227
316349AD2-085 C
Adder
2.0482352941176471.741
936666AD2-085 E
Adder
3.34117647058823542.84
961611AG1-000B C
Adder
11.3023529411764719.607
941591AE2-156 C
Adder
10.929411764705889.29
944581AF1-123 C
Adder
27.16823529411764723.093
944582AF1-123 E
Adder
62.2117647058823652.88
944591AF1-124 C
Adder
27.26470588235294223.175
944592AF1-124 E
Adder
62.43647058823529553.071
944601AF1-125 C
Adder
26.7494117647058822.737
944602AF1-125 E
Adder
61.2352941176470652.05
944631AF1-128 C
Adder
38.5941176470588232.805
958261AF2-120 C
50/50
7.0057.005
958262AF2-120 E
50/50
4.674.67
934501AD1-074 C
Adder
17.7847058823529415.117
934502AD1-074 E
Adder
9.0529411764705887.695
934511AD1-075 C
Adder
4.4458823529411773.779
934512AD1-075 E
Adder
2.2635294117647061.924
935161AD1-151 C
Adder
11.755294117647069.992
935162AD1-151 E
Adder
7.837647058823536.662
938531AE1-072 C
Adder
10.4258823529411768.862
938532AE1-072 E
Adder
5.4352941176470594.62
939191AE1-149 C
Adder
6.3788235294117655.422
939192AE1-149 E
Adder
4.2529411764705883.615
939601AE1-190 C
50/50
0.3840.384
939602AE1-190 E
50/50
1.6071.607
940431AE2-027 C
Adder
8.0564705882352946.848
940432AE2-027 E
Adder
5.3717647058823534.566
940481AE2-033 C
Adder
7.4635294117647066.344
940482AE2-033 E
Adder
5.0317647058823534.277
940541AE2-040 C
Adder
1.32705882352941161.128
940551AE2-041 C
50/50
8.5438.543
940641AE2-051 C
Adder
7.5435294117647066.412
940642AE2-051 E
Adder
5.0282352941176474.274
941101AE2-104 C
Adder
1.99529411764705891.696
941102AE2-104 E
Adder
3.1717647058823532.696
943471AF1-018 C
50/50
8.5438.543
944641AF1-129 C
Adder
58.0164705882352949.314
957191AF2-013 C
Adder
8.1011764705882366.886
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.8251.825
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.0931.093
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.8973.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.11329.113
G-007PJM->LTFIMP_G-007
CMTX_NF
1.1231.123
NYPJM->LTFIMP_NY
CLTF
0.5590.559
LGEELTFEXP_LGEE->PJM
CLTF
0.0680.068
WECLTFEXP_WEC->PJM
CLTF
0.0320.032
CPLELTFEXP_CPLE->PJM
CLTF
3.8353.835
TVALTFEXP_TVA->PJM
CLTF
1.2591.259
MECLTFEXP_MEC->PJM
CLTF
0.4280.428
LAGNLTFEXP_LAGN->PJM
CLTF
1.6451.645
SIGELTFEXP_SIGE->PJM
CLTF
0.0210.021
O66PJM->LTFIMP_O-066
CMTX_NF
7.1797.179

Details for 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.74 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1020.96
MW Contribution:1.65
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.61 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:990.18
MW Contribution:1.58
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.332941176470588240.283
961672AG1-007 E
Adder
0.188235294117647060.16
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
963041AG1-153 C
Adder
1.9482352941176471.656
963042AG1-153 E
Adder
2.92235294117647062.484
966621AG1-532 C
Adder
0.61294117647058830.521
966622AG1-532 E
Adder
0.408235294117647030.347
3145413WATKINS
Adder
0.26470588235294120.225
3145723EMPORIA
Adder
0.185882352941176470.158
3151311EDGECMA
Adder
5.5117647058823534.685
918492AA1-063AE OP
Adder
1.59411764705882361.355
918532AA1-067 E
Adder
0.251764705882352950.214
919692AA2-053 E OP
Adder
1.64941176470588241.402
920042AA2-088 E OP
Adder
4.0811764705882353.469
925785AC1-054 E
Adder
1.2082352941176471.027
927146AC1-208 E
Adder
1.51.275
934521AD1-076 C
Adder
4.377647058823533.721
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
944011AF1-069 C
Adder
4.6141176470588243.922
944012AF1-069 E
Adder
1.7917647058823531.523
960081AF2-299 C
Adder
0.81647058823529410.694
960082AF2-299 E
Adder
0.54470588235294130.463
316141AB2-099 E
Adder
0.095294117647058830.081
900672V4-068 E
Adder
0.136470588235294120.116
917342Z2-044 E
Adder
0.215294117647058830.183
922923AB1-081 E OP
Adder
1.321.122
923263AB1-132 E OP
Adder
2.582.193
923573AB1-173 E OP
Adder
1.36823529411764721.163
924162AB2-060 E OP
Adder
1.3117647058823531.115
924302AB2-077 E O1
Adder
0.41176470588235290.35
924312AB2-078 E O1
Adder
0.41176470588235290.35
924322AB2-079 E O1
Adder
0.41176470588235290.35
940492AE2-034 E
Adder
1.09058823529411760.927
941031AE2-094 C
Adder
14.12000000000000112.002
941032AE2-094 E
Adder
6.3247058823529425.376
946281AF1-292 C
Adder
0.67529411764705880.574
946282AF1-292 E
Adder
0.45058823529411770.383
957481AF2-042 C
Adder
17.0152941176470614.463
957482AF2-042 E
Adder
11.3435294117647069.642
957861AF2-080 C
Adder
2.7023529411764712.297
957862AF2-080 E
Adder
1.19764705882352951.018
3145393UNCAMP
Adder
2.3247058823529411.976
916042Z1-036 E
Adder
9.9682352941176488.473
938771AE1-103 C
Adder
1.11764705882352940.95
938772AE1-103 E
Adder
1.5435294117647061.312
3143316POE
50/50
1.0861.086
3145256KINGFORK
Adder
0.357647058823529430.304
3145506HICKORY
Adder
0.72352941176470590.615
3150651CHESTF6
50/50
21.89721.897
3150731STONECA
50/50
4.5124.512
3150761HOPPOLC
50/50
1.0021.002
3150771HOPHCF1
50/50
1.5941.594
3150781HOPHCF2
50/50
1.5941.594
3150791HOPHCF3
50/50
1.5941.594
3150801HOPHCF4
50/50
2.4192.419
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
926662AC1-147 E
Adder
0.452941176470588240.385
926755AC1-161 E
Adder
3.78588235294117673.218
927226AC1-216 E
Adder
4.122352941176473.504
935112AD1-144 E
Adder
0.33176470588235290.282
942341AE2-247 C
Adder
0.68470588235294120.582
942342AE2-247 E
Adder
0.94470588235294130.803
943461AF1-017 C
Adder
0.61882352941176480.526
943462AF1-017 E
Adder
1.00941176470588250.858
943612AF1-032 E
Adder
0.320.272
316132AB2-190 C
50/50
2.4122.412
913392Y1-086 E
Adder
0.74470588235294120.633
916192Z1-068 E
Adder
0.63294117647058830.538
923832AB2-022 E
Adder
0.421176470588235260.358
923852AB2-025 E
Adder
0.6317647058823530.537
939312AE1-162 E
Adder
0.5717647058823530.486
946262AF1-291 E
50/50
1.6321.632
957492AF2-043 E
Adder
0.49294117647058820.419
901082W1-029 E
Adder
10.9870588235294139.339
917122Z2-027 E
Adder
0.457647058823529460.389
925332AB2-190 E
50/50
4.6914.691
925522AC1-027 E
Adder
0.410588235294117640.349
942001AE2-212 C
50/50
2.1112.111
942002AE2-212 E
50/50
1.4081.408
957871AF2-081 C
Adder
3.34117647058823542.84
957872AF2-081 E
Adder
1.4317647058823531.217
958161AF2-110 C
Adder
0.51764705882352950.44
958162AF2-110 E
Adder
0.82470588235294120.701
917512Z2-088 E OP1
Adder
1.73411764705882351.474
926071AC1-086 C
Adder
8.8647058823529427.535
926072AC1-086 E
Adder
4.0352941176470593.43
927021AC1-189 C
Adder
2.97529411764705862.529
927022AC1-189 E
Adder
1.48235294117647071.26
933291AC2-141 C
Adder
8.8694117647058827.539
933292AC2-141 E
Adder
3.78588235294117673.218
934621AD1-088 C
Adder
2.86941176470588262.439
934622AD1-088 E
Adder
1.38117647058823521.174
939411AE1-173 C
Adder
31.5352941176470626.805
939412AE1-173 E
Adder
21.0235294117647117.87
934012AD1-025 E
Adder
5.3364705882352944.536
933981AD1-022 C
Adder
3.162.686
933982AD1-022 E
Adder
1.721.462
962572AG1-106 E
Adder
0.50117647058823530.426
962571AG1-106 C
Adder
1.14705882352941170.975
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
3146326AYDLETT TAP
Adder
0.455294117647058850.387
316240AF1-291 C
50/50
2.4482.448
316263AC1-034 C
Adder
2.3517647058823531.999
316274AC1-208 C
Adder
3.3788235294117652.872
917332KELFORD E
Adder
0.61411764705882350.522
924516AB2-100 E1
Adder
1.36823529411764721.163
924517AB2-100 E2
Adder
1.36823529411764721.163
925595AC1-034 E
Adder
1.77411764705882361.508
926206AC1-098 E
Adder
1.35999999999999991.156
926214AC1-099 E
Adder
0.44941176470588240.382
934065AD1-033 E
Adder
1.6670588235294121.417
937226AE2-253 E
Adder
1.9482352941176471.656
918512AA1-065 E OP
Adder
2.04235294117647071.736
919153AA1-139 E2
Adder
1.36588235294117651.161
919152AA1-139 E1
Adder
1.36588235294117651.161
919710AA2-057 E
Adder
1.44823529411764731.231
920692AA2-178 E
Adder
1.4552941176470591.237
923994AB2-040_E
Adder
2.56588235294117652.181
924022AB2-043 E O1
Adder
1.60117647058823541.361
924152AB2-059 E OP
Adder
1.87058823529411791.59
924814AB2-134 E
Adder
6.7529411764705885.74
316083AB2-161 C
50/50
0.3210.321
316084AB2-161 E
50/50
3.213.21
925122AB2-169 E
Adder
2.04352941176470631.737
316088AB2-174 E
Adder
2.7588235294117652.345
932046AC2-012 E
Adder
4.4823529411764713.81
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
316381AD1-082 C
50/50
0.7330.733
934576AD1-082 E
50/50
2.5582.558
316349AD2-085 C
Adder
1.57882352941176471.342
936666AD2-085 E
Adder
2.5752941176470592.189
961611AG1-000B C
Adder
7.342352941176476.241
941591AE2-156 C
Adder
6.1141176470588245.197
944581AF1-123 C
Adder
15.03411764705882412.779
944582AF1-123 E
Adder
34.4258823529411829.262
944591AF1-124 C
Adder
15.08705882352941312.824
944592AF1-124 E
Adder
34.55058823529411429.368
944601AF1-125 C
Adder
14.80235294117647312.582
944602AF1-125 E
Adder
33.8847058823529428.802
964241AG1-285 C
Adder
3.85882352941176483.28
964242AG1-285 E
Adder
2.5717647058823532.186
3137643SOCKMAN
Adder
0.288235294117647030.245
932632AC2-084 E
Adder
1.20235294117647061.022
934321AD1-056 C
Adder
2.3988235294117652.039
934322AD1-056 E
Adder
1.30117647058823541.106
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934501AD1-074 C
Adder
12.05529411764705810.247
934502AD1-074 E
Adder
6.1364705882352945.216
934511AD1-075 C
Adder
3.01411764705882362.562
934512AD1-075 E
Adder
1.53411764705882361.304
934612AD1-087 E
Adder
1.1117647058823530.945
935161AD1-151 C
50/50
9.0229.022
935162AD1-151 E
50/50
6.0156.015
935172AD1-152 E
Adder
1.6435294117647061.397
937482AD2-202 E
Adder
0.32588235294117650.277
938531AE1-072 C
Adder
5.8905882352941185.007
938532AE1-072 E
Adder
3.07058823529411742.61
939191AE1-149 C
50/50
7.1377.137
939192AE1-149 E
50/50
4.7584.758
940431AE2-027 C
Adder
7.0447058823529425.988
940432AE2-027 E
Adder
4.6964705882352943.992
940481AE2-033 C
Adder
8.6517647058823537.354
940482AE2-033 E
Adder
5.8329411764705884.958
940541AE2-040 C
Adder
1.56117647058823541.327
940641AE2-051 C
Adder
6.0952941176470595.181
940642AE2-051 E
Adder
4.0635294117647063.454
941101AE2-104 C
Adder
1.26941176470588221.079
941102AE2-104 E
Adder
2.0188235294117651.716
944641AF1-129 C
50/50
120.262120.262
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883

Details for 6CHOWAN-6PEMBROKE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHOWAN-6PEMBROKE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:748.25
MW Contribution:2.46
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHOWAN-6PEMBROKE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.87 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:783.54
MW Contribution:2.44
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
50/50
0.8010.801
961672AG1-007 E
50/50
0.4540.454
961941AG1-037 C
50/50
0.530.53
961942AG1-037 E
50/50
0.3530.353
3145723EMPORIA
Adder
0.174117647058823520.148
3151311EDGECMA
50/50
10.30210.302
3151361ROSEMG1
50/50
1.2891.289
3151371ROSEMS1
50/50
0.7980.798
3151381ROSEMG2
50/50
0.6030.603
3151391GASTONA
50/50
1.9231.923
918492AA1-063AE OP
Adder
2.0835294117647061.771
918532AA1-067 E
50/50
0.8370.837
919692AA2-053 E OP
50/50
2.8352.835
920042AA2-088 E OP
Adder
4.2329411764705883.598
927146AC1-208 E
50/50
2.7832.783
934521AD1-076 C
50/50
31.87131.871
934522AD1-076 E
50/50
16.24416.244
943171AE2-346 C
50/50
0.2360.236
943172AE2-346 E
50/50
0.6360.636
3156011CONETOE2SOL
50/50
1.151.15
3156063AA2-053SOLA
50/50
1.0121.012
316140AB2-099 C
50/50
0.1010.101
316141AB2-099 E
50/50
0.2650.265
900672V4-068 E
50/50
0.2380.238
917342Z2-044 E
50/50
0.3980.398
922923AB1-081 E OP
50/50
2.4132.413
923263AB1-132 E OP
50/50
3.8513.851
923573AB1-173 E OP
Adder
1.52470588235294141.296
940491AE2-034 C
50/50
3.6663.666
940492AE2-034 E
50/50
9.89.8
957861AF2-080 C
50/50
7.6547.654
957862AF2-080 E
50/50
3.3933.393
3151411GASTONB
50/50
1.9231.923
3152921DOMTR78
50/50
3.1353.135
917512Z2-088 E OP1
50/50
4.4994.499
926071AC1-086 C
50/50
13.23213.232
926072AC1-086 E
50/50
6.0226.022
927021AC1-189 C
50/50
8.4278.427
927022AC1-189 E
50/50
4.1984.198
933981AD1-022 C
50/50
20.07120.071
933982AD1-022 E
50/50
10.92710.927
962572AG1-106 E
50/50
0.7490.749
962571AG1-106 C
50/50
1.7111.711
3145946PLYMOUTH TP
50/50
0.8710.871
316005AA1-067 C
50/50
0.3190.319
316011AB1-132 C OP
50/50
1.4681.468
316049AB1-081 C OP
50/50
0.920.92
316210AC1-098 C
50/50
0.7470.747
316212AC1-099 C
50/50
0.250.25
316263AC1-034 C
50/50
4.2984.298
316274AC1-208 C
50/50
6.2686.268
316317KELFORD C
50/50
0.3720.372
316318V4-068 C
50/50
0.0530.053
316319Z2-044 C
50/50
0.1410.141
917332KELFORD E
50/50
1.711.71
924516AB2-100 E1
Adder
1.14470588235294120.973
924517AB2-100 E2
Adder
1.14470588235294120.973
925595AC1-034 E
50/50
3.2423.242
926206AC1-098 E
50/50
2.8932.893
926214AC1-099 E
50/50
0.9560.956
3156021HOLLOMANSOL
50/50
2.5732.573
918512AA1-065 E OP
50/50
7.7337.733
316327AA2-057 C
50/50
0.8920.892
919710AA2-057 E
50/50
2.722.72
315614AA2-178 C
50/50
4.9824.982
920692AA2-178 E
50/50
13.06713.067
923994AB2-040_E
Adder
2.86000000000000032.431
316359AB2-059 C OP
50/50
1.0841.084
924152AB2-059 E OP
50/50
3.4183.418
316174AB2-169_C
50/50
2.0162.016
925122AB2-169 E
50/50
11.07111.071
316088AB2-174 E
Adder
2.86235294117647052.433
3137643SOCKMAN
Adder
0.368235294117647050.313
932631AC2-084 C
50/50
0.7960.796
932632AC2-084 E
50/50
2.5572.557
934321AD1-056 C
50/50
4.0394.039
934322AD1-056 E
50/50
2.1912.191
934331AD1-057 C
50/50
2.2532.253
934332AD1-057 E
50/50
1.1731.173
934501AD1-074 C
50/50
87.75587.755
934502AD1-074 E
50/50
44.67244.672
934511AD1-075 C
50/50
21.93921.939
934512AD1-075 E
50/50
11.16811.168
938531AE1-072 C
Adder
-9.841176470588236-8.365
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7381.738
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.1399.139
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.9675.967
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.51826.518
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4280.428
NYPJM->LTFIMP_NY
CLTF
0.190.19
LGEELTFEXP_LGEE->PJM
CLTF
0.3440.344
WECLTFEXP_WEC->PJM
CLTF
0.1860.186
CPLELTFEXP_CPLE->PJM
CLTF
3.6463.646
TVALTFEXP_TVA->PJM
CLTF
1.5721.572
MECLTFEXP_MEC->PJM
CLTF
1.0871.087
LAGNLTFEXP_LAGN->PJM
CLTF
2.0172.017
SIGELTFEXP_SIGE->PJM
CLTF
0.0670.067
O66PJM->LTFIMP_O-066
CMTX_NF
2.7222.722

Details for 6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.02 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:739.92
MW Contribution:7.86
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.6 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:791.36
MW Contribution:7.88
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
50/50
0.9020.902
961672AG1-007 E
50/50
0.5110.511
961941AG1-037 C
50/50
0.480.48
961942AG1-037 E
50/50
0.320.32
966621AG1-532 C
50/50
3.2323.232
966622AG1-532 E
50/50
2.1552.155
313506AB1-173 C OP
50/50
2.1742.174
3145413WATKINS
50/50
0.4340.434
3145723EMPORIA
50/50
0.9510.951
3147043LAWRENC
50/50
0.5440.544
3151261ROARAP2
50/50
2.0552.055
3151281ROARAP4
50/50
1.9441.944
3151311EDGECMA
50/50
16.316.3
3151361ROSEMG1
50/50
3.9143.914
3151371ROSEMS1
50/50
2.4252.425
3151381ROSEMG2
50/50
1.8331.833
3151391GASTONA
50/50
6.1446.144
918492AA1-063AE OP
50/50
5.1285.128
918532AA1-067 E
50/50
0.5790.579
919692AA2-053 E OP
50/50
5.8745.874
920042AA2-088 E OP
50/50
9.2489.248
925785AC1-054 E
50/50
3.2573.257
927146AC1-208 E
50/50
4.8664.866
934521AD1-076 C
Adder
7.246.154
934522AD1-076 E
Adder
3.6905882352941183.137
943171AE2-346 C
50/50
0.2130.213
943172AE2-346 E
50/50
0.5760.576
960081AF2-299 C
50/50
4.3094.309
960082AF2-299 E
50/50
2.8732.873
3156011CONETOE2SOL
50/50
1.1641.164
3156063AA2-053SOLA
50/50
2.0952.095
316129AC1-054 C
50/50
1.1551.155
316140AB2-099 C
50/50
0.0910.091
316141AB2-099 E
50/50
0.240.24
900672V4-068 E
50/50
0.330.33
917342Z2-044 E
50/50
0.6430.643
922923AB1-081 E OP
50/50
3.8493.849
923263AB1-132 E OP
50/50
12.30412.304
923573AB1-173 E OP
50/50
6.3246.324
946281AF1-292 C
50/50
3.5673.567
946282AF1-292 E
50/50
2.3782.378
957861AF2-080 C
50/50
6.8036.803
957862AF2-080 E
50/50
3.0163.016
3145393UNCAMP
Adder
3.1317647058823532.662
3151151S HAMPT1
50/50
0.9640.964
3151411GASTONB
50/50
6.1446.144
3156073AA1-063SOLA
50/50
1.7661.766
3156083AA2-088SOLA
50/50
0.9260.926
917512Z2-088 E OP1
50/50
4.5534.553
926071AC1-086 C
50/50
42.27842.278
926072AC1-086 E
50/50
19.24219.242
927021AC1-189 C
50/50
7.497.49
927022AC1-189 E
50/50
3.7313.731
933981AD1-022 C
50/50
5.8155.815
933982AD1-022 E
50/50
3.1653.165
962572AG1-106 E
50/50
2.3922.392
962571AG1-106 C
50/50
5.4685.468
3145946PLYMOUTH TP
Adder
0.18470588235294120.157
316005AA1-067 C
50/50
0.2210.221
316011AB1-132 C OP
50/50
4.6924.692
316023AB2-100 C2
50/50
2.7732.773
316049AB1-081 C OP
50/50
1.4681.468
316210AC1-098 C
50/50
1.0771.077
316212AC1-099 C
50/50
0.3610.361
316263AC1-034 C
50/50
6.8576.857
316274AC1-208 C
50/50
10.95810.958
316317KELFORD C
50/50
0.3660.366
316318V4-068 C
50/50
0.0740.074
316319Z2-044 C
50/50
0.2270.227
316365AB2-100 C1
50/50
2.7732.773
917332KELFORD E
50/50
1.6811.681
924516AB2-100 E1
50/50
8.3588.358
924517AB2-100 E2
50/50
8.3588.358
925595AC1-034 E
50/50
5.1725.172
926206AC1-098 E
50/50
4.1714.171
926214AC1-099 E
50/50
1.3781.378
3156021HOLLOMANSOL
50/50
1.5991.599
918512AA1-065 E OP
50/50
4.8064.806
316327AA2-057 C
50/50
1.4581.458
919710AA2-057 E
50/50
4.4424.442
316181AB2-040 GEN
50/50
2.4492.449
923994AB2-040_E
50/50
11.85811.858
316359AB2-059 C OP
50/50
1.731.73
924152AB2-059 E OP
50/50
5.4535.453
316174AB2-169_C
50/50
0.7280.728
925122AB2-169 E
50/50
3.9953.995
316087AB2-174 C
50/50
2.4072.407
316088AB2-174 E
50/50
13.32913.329
3137643SOCKMAN
50/50
1.2021.202
932631AC2-084 C
50/50
1.1471.147
932632AC2-084 E
50/50
3.6863.686
934321AD1-056 C
50/50
9.1149.114
934322AD1-056 E
50/50
4.9434.943
934331AD1-057 C
50/50
5.0845.084
934332AD1-057 E
50/50
2.6472.647
934501AD1-074 C
Adder
19.93647058823529516.946
934502AD1-074 E
Adder
10.1482352941176478.626
934511AD1-075 C
Adder
4.9835294117647064.236
934512AD1-075 E
Adder
2.53764705882352942.157
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.0232.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.6319.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7166.716
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.27631.276
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6890.689
NYPJM->LTFIMP_NY
CLTF
0.3160.316
LGEELTFEXP_LGEE->PJM
CLTF
0.3690.369
WECLTFEXP_WEC->PJM
CLTF
0.1970.197
CPLELTFEXP_CPLE->PJM
CLTF
4.2444.244
TVALTFEXP_TVA->PJM
CLTF
1.8021.802
MECLTFEXP_MEC->PJM
CLTF
1.1871.187
LAGNLTFEXP_LAGN->PJM
CLTF
2.312.31
SIGELTFEXP_SIGE->PJM
CLTF
0.0730.073
O66PJM->LTFIMP_O-066
CMTX_NF
4.3814.381

Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:166.69 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:952.64
MW Contribution:3.83
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:173.55 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:991.87
MW Contribution:3.82
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
50/50
1.1121.112
961672AG1-007 E
50/50
0.630.63
961941AG1-037 C
50/50
0.8430.843
961942AG1-037 E
50/50
0.5620.562
966621AG1-532 C
50/50
0.8350.835
966622AG1-532 E
50/50
0.5560.556
313506AB1-173 C OP
50/50
0.8160.816
3145723EMPORIA
50/50
0.2710.271
3151261ROARAP2
50/50
1.211.21
3151281ROARAP4
50/50
1.1451.145
3151311EDGECMA
50/50
14.76714.767
3151361ROSEMG1
50/50
1.9891.989
3151371ROSEMS1
50/50
1.2321.232
3151381ROSEMG2
50/50
0.9310.931
3151391GASTONA
50/50
2.992.99
918492AA1-063AE OP
50/50
3.2163.216
918532AA1-067 E
50/50
1.1251.125
919692AA2-053 E OP
50/50
4.4424.442
920042AA2-088 E OP
50/50
6.4046.404
925785AC1-054 E
Adder
1.90117647058823551.616
927146AC1-208 E
50/50
4.2494.249
934521AD1-076 C
50/50
25.10225.102
934522AD1-076 E
50/50
12.79412.794
943171AE2-346 C
50/50
0.3740.374
943172AE2-346 E
50/50
1.0111.011
960081AF2-299 C
50/50
1.1131.113
960082AF2-299 E
50/50
0.7420.742
3156011CONETOE2SOL
50/50
1.5831.583
3156063AA2-053SOLA
50/50
1.5851.585
316140AB2-099 C
50/50
0.1610.161
316141AB2-099 E
50/50
0.4210.421
900672V4-068 E
50/50
0.3710.371
917342Z2-044 E
50/50
0.5880.588
922923AB1-081 E OP
50/50
3.4943.494
923263AB1-132 E OP
50/50
5.9885.988
923573AB1-173 E OP
50/50
2.3742.374
940491AE2-034 C
50/50
2.3412.341
940492AE2-034 E
50/50
6.2586.258
946281AF1-292 C
50/50
0.9210.921
946282AF1-292 E
50/50
0.6140.614
957861AF2-080 C
50/50
10.44310.443
957862AF2-080 E
50/50
4.6294.629
916042Z1-036 E
50/50
57.18957.189
3151411GASTONB
50/50
2.992.99
3152921DOMTR78
50/50
2.6612.661
3156073AA1-063SOLA
50/50
1.1081.108
3156083AA2-088SOLA
50/50
0.6410.641
3156116Z1-036WIND
50/50
1.3161.316
917512Z2-088 E OP1
50/50
6.1936.193
926071AC1-086 C
50/50
20.57620.576
926072AC1-086 E
50/50
9.3659.365
927021AC1-189 C
50/50
11.49811.498
927022AC1-189 E
50/50
5.7275.727
933981AD1-022 C
50/50
18.40618.406
933982AD1-022 E
50/50
10.0210.02
962572AG1-106 E
50/50
1.1641.164
962571AG1-106 C
50/50
2.6612.661
3145946PLYMOUTH TP
50/50
0.6620.662
316005AA1-067 C
50/50
0.4290.429
316011AB1-132 C OP
50/50
2.2832.283
316023AB2-100 C2
50/50
0.5940.594
316049AB1-081 C OP
50/50
1.3321.332
316210AC1-098 C
50/50
1.1521.152
316212AC1-099 C
50/50
0.3860.386
316263AC1-034 C
50/50
6.2256.225
316274AC1-208 C
50/50
9.5699.569
316317KELFORD C
50/50
0.5890.589
316318V4-068 C
50/50
0.0840.084
316319Z2-044 C
50/50
0.2070.207
316365AB2-100 C1
50/50
0.5940.594
917332KELFORD E
50/50
2.7032.703
924516AB2-100 E1
50/50
1.791.79
924517AB2-100 E2
50/50
1.791.79
925595AC1-034 E
50/50
4.6964.696
926206AC1-098 E
50/50
4.4614.461
926214AC1-099 E
50/50
1.4741.474
3156021HOLLOMANSOL
50/50
4.1274.127
918512AA1-065 E OP
50/50
12.40212.402
316327AA2-057 C
50/50
1.3351.335
919710AA2-057 E
50/50
4.074.07
315614AA2-178 C
50/50
3.1813.181
920692AA2-178 E
50/50
8.3448.344
316181AB2-040 GEN
50/50
0.9190.919
923994AB2-040_E
50/50
4.4524.452
316359AB2-059 C OP
50/50
1.571.57
924152AB2-059 E OP
50/50
4.954.95
316174AB2-169_C
50/50
1.9111.911
925122AB2-169 E
50/50
10.49610.496
316087AB2-174 C
50/50
0.8050.805
316088AB2-174 E
50/50
4.4594.459
3137643SOCKMAN
50/50
0.5730.573
932631AC2-084 C
50/50
1.2271.227
932632AC2-084 E
50/50
3.9433.943
934321AD1-056 C
50/50
5.9965.996
934322AD1-056 E
50/50
3.2523.252
934331AD1-057 C
50/50
3.3453.345
934332AD1-057 E
50/50
1.7421.742
934501AD1-074 C
50/50
69.11769.117
934502AD1-074 E
50/50
35.18435.184
934511AD1-075 C
50/50
17.27917.279
934512AD1-075 E
50/50
8.7968.796
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4372.437
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.90912.909
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4168.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.337.3
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6050.605
NYPJM->LTFIMP_NY
CLTF
0.2690.269
LGEELTFEXP_LGEE->PJM
CLTF
0.4860.486
WECLTFEXP_WEC->PJM
CLTF
0.2620.262
CPLELTFEXP_CPLE->PJM
CLTF
5.1125.112
TVALTFEXP_TVA->PJM
CLTF
2.2172.217
MECLTFEXP_MEC->PJM
CLTF
1.5351.535
LAGNLTFEXP_LAGN->PJM
CLTF
2.8432.843
SIGELTFEXP_SIGE->PJM
CLTF
0.0950.095
O66PJM->LTFIMP_O-066
CMTX_NF
3.8433.843

Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.43 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:636.85
MW Contribution:3.16
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.25 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:670.11
MW Contribution:3.15
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
50/50
0.8770.877
961672AG1-007 E
50/50
0.4970.497
961941AG1-037 C
50/50
0.7020.702
961942AG1-037 E
50/50
0.4680.468
966621AG1-532 C
Adder
0.6917647058823530.588
966622AG1-532 E
Adder
0.46117647058823530.392
313506AB1-173 C OP
50/50
0.6750.675
3145723EMPORIA
Adder
0.22470588235294120.191
3151261ROARAP2
50/50
11
3151281ROARAP4
50/50
0.9460.946
3151311EDGECMA
50/50
11.80811.808
3151361ROSEMG1
50/50
1.6391.639
3151371ROSEMS1
50/50
1.0151.015
3151381ROSEMG2
50/50
0.7680.768
3151391GASTONA
50/50
2.4722.472
918492AA1-063AE OP
50/50
2.6512.651
918532AA1-067 E
50/50
0.8740.874
919692AA2-053 E OP
50/50
3.6823.682
920042AA2-088 E OP
Adder
5.2376470588235294.452
925785AC1-054 E
Adder
1.57058823529411761.335
927146AC1-208 E
50/50
3.4873.487
934521AD1-076 C
50/50
12.94512.945
934522AD1-076 E
50/50
6.5986.598
943171AE2-346 C
50/50
0.3120.312
943172AE2-346 E
50/50
0.8430.843
960081AF2-299 C
Adder
0.92117647058823540.783
960082AF2-299 E
Adder
0.61411764705882350.522
3156011CONETOE2SOL
50/50
1.2431.243
3156063AA2-053SOLA
50/50
1.3141.314
316140AB2-099 C
50/50
0.1340.134
316141AB2-099 E
50/50
0.3510.351
900672V4-068 E
50/50
0.3070.307
917342Z2-044 E
50/50
0.4760.476
922923AB1-081 E OP
50/50
2.8072.807
923263AB1-132 E OP
50/50
4.954.95
923573AB1-173 E OP
50/50
1.9641.964
940491AE2-034 C
50/50
0.8630.863
940492AE2-034 E
50/50
2.3072.307
946281AF1-292 C
Adder
0.76235294117647070.648
946282AF1-292 E
Adder
0.50823529411764710.432
957861AF2-080 C
50/50
8.1668.166
957862AF2-080 E
50/50
3.623.62
916042Z1-036 E
Adder
9.7517647058823538.289
3151411GASTONB
50/50
2.4722.472
3152921DOMTR78
50/50
1.4921.492
3156073AA1-063SOLA
50/50
0.9130.913
917512Z2-088 E OP1
50/50
4.8634.863
926071AC1-086 C
50/50
17.00917.009
926072AC1-086 E
50/50
7.7427.742
927021AC1-189 C
50/50
8.9918.991
927022AC1-189 E
50/50
4.4794.479
933981AD1-022 C
50/50
11.12811.128
933982AD1-022 E
50/50
6.0586.058
962572AG1-106 E
50/50
0.9630.963
962571AG1-106 C
50/50
2.22.2
3145946PLYMOUTH TP
50/50
0.3260.326
316005AA1-067 C
50/50
0.3330.333
316011AB1-132 C OP
50/50
1.8881.888
316049AB1-081 C OP
50/50
1.071.07
316210AC1-098 C
50/50
0.9490.949
316212AC1-099 C
50/50
0.3180.318
316263AC1-034 C
50/50
4.9994.999
316274AC1-208 C
50/50
7.8537.853
316317KELFORD C
50/50
0.4890.489
316318V4-068 C
50/50
0.0690.069
316319Z2-044 C
50/50
0.1680.168
917332KELFORD E
50/50
2.2482.248
924516AB2-100 E1
Adder
1.48352941176470581.261
924517AB2-100 E2
Adder
1.48352941176470581.261
925595AC1-034 E
50/50
3.7713.771
926206AC1-098 E
50/50
3.6753.675
926214AC1-099 E
50/50
1.2141.214
3156021HOLLOMANSOL
50/50
3.4513.451
918512AA1-065 E OP
50/50
10.3710.37
316327AA2-057 C
50/50
1.0871.087
919710AA2-057 E
50/50
3.3143.314
315614AA2-178 C
50/50
1.1731.173
920692AA2-178 E
50/50
3.0763.076
316181AB2-040 GEN
50/50
0.7610.761
923994AB2-040_E
50/50
3.6833.683
316359AB2-059 C OP
50/50
1.2611.261
924152AB2-059 E OP
50/50
3.9763.976
316174AB2-169_C
50/50
1.1891.189
925122AB2-169 E
50/50
6.5316.531
316088AB2-174 E
Adder
3.68941176470588243.136
3137643SOCKMAN
50/50
0.4740.474
932631AC2-084 C
50/50
1.0111.011
932632AC2-084 E
50/50
3.2493.249
934321AD1-056 C
50/50
4.8664.866
934322AD1-056 E
50/50
2.6392.639
934331AD1-057 C
50/50
2.7142.714
934332AD1-057 E
50/50
1.4131.413
934501AD1-074 C
50/50
35.64335.643
934502AD1-074 E
50/50
18.14418.144
934511AD1-075 C
50/50
8.9118.911
934512AD1-075 E
50/50
4.5364.536
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9321.932
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.35910.359
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7216.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.62929.629
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4730.473
NYPJM->LTFIMP_NY
CLTF
0.210.21
LGEELTFEXP_LGEE->PJM
CLTF
0.3890.389
WECLTFEXP_WEC->PJM
CLTF
0.210.21
CPLELTFEXP_CPLE->PJM
CLTF
4.0524.052
TVALTFEXP_TVA->PJM
CLTF
1.7681.768
MECLTFEXP_MEC->PJM
CLTF
1.2291.229
LAGNLTFEXP_LAGN->PJM
CLTF
2.2672.267
SIGELTFEXP_SIGE->PJM
CLTF
0.0760.076
O66PJM->LTFIMP_O-066
CMTX_NF
3.0083.008

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.08 %
Rating:879.84 MVA
Rating Type:B
MVA to Mitigate:950.94
MW Contribution:1.78
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:132.71 %
Rating:879.84 MVA
Rating Type:B
MVA to Mitigate:1167.6
MW Contribution:2.02
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.238823529411764740.203
961942AG1-037 E
Adder
0.158823529411764720.135
966621AG1-532 C
Adder
0.63647058823529420.541
966622AG1-532 E
Adder
0.424705882352941160.361
3145413WATKINS
Adder
0.348235294117647030.296
3145723EMPORIA
Adder
0.195294117647058840.166
918492AA1-063AE OP
Adder
1.88000000000000011.598
920042AA2-088 E OP
Adder
5.164.386
934521AD1-076 C
Adder
5.9847058823529415.087
934522AD1-076 E
Adder
3.0505882352941182.593
943172AE2-346 E
Adder
0.28588235294117650.243
944011AF1-069 C
Adder
2.9870588235294122.539
960081AF2-299 C
Adder
0.84823529411764710.721
960082AF2-299 E
Adder
0.56588235294117650.481
316141AB2-099 E
Adder
0.118823529411764720.101
900672V4-068 E
Adder
0.170588235294117650.145
923263AB1-132 E OP
Adder
2.78941176470588252.371
923573AB1-173 E OP
Adder
1.4764705882352941.255
940492AE2-034 E
Adder
1.53882352941176471.308
941031AE2-094 C
Adder
15.84470588235294213.468
941032AE2-094 E
Adder
7.0964705882352946.032
946281AF1-292 C
Adder
0.70235294117647060.597
946282AF1-292 E
Adder
0.46823529411764710.398
3145393UNCAMP
Adder
3.11647058823529432.649
916042Z1-036 E
Adder
14.65058823529411712.453
938771AE1-103 C
Adder
1.5164705882352941.289
938772AE1-103 E
Adder
2.09411764705882361.78
3142296MT RD221
50/50
0.1260.126
3142366NRTHEST
50/50
0.1640.164
3143316POE
Adder
0.84470588235294120.718
3145256KINGFORK
Adder
0.56470588235294120.48
3145506HICKORY
Adder
1.16588235294117660.991
3150501FOURRIVERG
50/50
4.254.25
3150601CHESTF5
Adder
47.7840.613
3150651CHESTF6
Adder
13.78941176470588211.721
3150671DARBY 1
50/50
2.2042.204
3150681DARBY 2
50/50
2.2072.207
3150691DARBY 3
50/50
2.2142.214
3150701DARBY 4
50/50
2.2172.217
3150731STONECA
Adder
4.9341176470588244.194
3150831SPRUNCA
Adder
6.84941176470588255.822
3150841SPRUNCB
Adder
6.84941176470588255.822
3150921YORKTN3
Adder
72.7576470588235461.844
925865AC1-065 E
Adder
11.2529411764705879.565
926412AC1-112 E
50/50
1.0221.022
926472AC1-118 E
Adder
0.64470588235294120.548
926662AC1-147 E
Adder
0.72117647058823530.613
926755AC1-161 E
Adder
6.8564705882352955.828
927226AC1-216 E
Adder
5.1070588235294124.341
934392AD1-063 E
Adder
0.72470588235294120.616
934781AD1-105 C
50/50
1.0481.048
934782AD1-105 E
50/50
4.3454.345
935112AD1-144 E
Adder
0.52352941176470590.445
936582AD2-073 E
Adder
0.67176470588235290.571
936591AD2-074 C
Adder
3.63882352941176463.093
936592AD2-074 E
Adder
5.9376470588235295.047
942341AE2-247 C
Adder
0.84705882352941180.72
942342AE2-247 E
Adder
1.16941176470588240.994
943461AF1-017 C
Adder
0.76588235294117660.651
943462AF1-017 E
Adder
1.24941176470588241.062
943612AF1-032 E
Adder
0.49647058823529410.422
943741AF1-042 C
Adder
1.90352941176470611.618
943742AF1-042 E
Adder
3.10705882352941172.641
944491AF1-114 C
Adder
3.30470588235294162.809
944492AF1-114 E
Adder
4.5635294117647063.879
961951AG1-038 C
Adder
2.1047058823529411.789
961952AG1-038 E
Adder
2.9058823529411772.47
966661AG1-536 C
Adder
3.50352941176470622.978
966662AG1-536 E
Adder
4.7070588235294134.001
966871AG1-558 C
50/50
2.4052.405
966872AG1-558 E
50/50
1.2121.212
966881AG1-559 C
Adder
1.37764705882352941.171
966882AG1-559 E
Adder
0.69411764705882350.59
316076AC2-137 E
Adder
1.04588235294117650.889
316078AC2-138 E
Adder
0.60352941176470590.513
316157AD2-030 E
Adder
0.78705882352941180.669
913392Y1-086 E
Adder
1.160.986
916192Z1-068 E
Adder
1.0152941176470590.863
923832AB2-022 E
Adder
0.65529411764705890.557
923842AB2-024 E
Adder
1.2282352941176471.044
923852AB2-025 E
Adder
0.58235294117647060.495
930122AB1-027 E
50/50
1.2571.257
938552AE1-074 E
Adder
0.81882352941176460.696
939312AE1-162 E
Adder
0.84352941176470590.717
946262AF1-291 E
Adder
1.04588235294117650.889
957492AF2-043 E
Adder
0.76352941176470590.649
957601AF2-054 C
Adder
1.40235294117647061.192
957602AF2-054 E
Adder
0.93529411764705890.795
962861AG1-135 C
Adder
3.9564705882352943.363
962862AG1-135 E
Adder
2.63764705882352952.242
962962AG1-145 E
Adder
0.94000000000000010.799
963611AG1-210 C
Adder
0.431764705882352940.367
963612AG1-210 E
Adder
0.64705882352941180.55
964211AG1-282 C
Adder
1.32117647058823541.123
964212AG1-282 E
Adder
0.88117647058823530.749
901082W1-029 E
Adder
16.73529411764705814.225
917122Z2-027 E
Adder
0.70705882352941170.601
925332AB2-190 E
Adder
5.5094117647058834.683
925522AC1-027 E
Adder
0.65764705882352950.559
942001AE2-212 C
Adder
1.48117647058823531.259
942002AE2-212 E
Adder
0.98705882352941180.839
957832AF2-077 E
Adder
0.90470588235294120.769
957871AF2-081 C
Adder
5.3211764705882354.523
957872AF2-081 E
Adder
2.281.938
957971AF2-091 C
Adder
1.12352941176470590.955
957972AF2-091 E
Adder
1.5517647058823531.319
958161AF2-110 C
Adder
0.74235294117647070.631
958162AF2-110 E
Adder
1.181.003
3138116ELKO L286
Adder
1.09058823529411760.927
3141813NORNECK
Adder
0.57411764705882350.488
926071AC1-086 C
Adder
9.5835294117647068.146
926072AC1-086 E
Adder
4.36235294117647053.708
933291AC2-141 C
Adder
16.0623529411764713.653
933292AC2-141 E
Adder
6.8564705882352955.828
939411AE1-173 C
Adder
41.24705882352941435.06
939412AE1-173 E
Adder
27.4976470588235323.373
934012AD1-025 E
Adder
6.6117647058823535.62
927041AC1-191 C
50/50
9.6569.656
927042AC1-191 E
50/50
4.814.81
933981AD1-022 C
Adder
4.2529411764705883.615
933982AD1-022 E
Adder
2.3152941176470591.968
962572AG1-106 E
Adder
0.54235294117647060.461
962571AG1-106 C
Adder
1.241.054
3130536PAPERMILL
Adder
4.5270588235294123.848
3145946PLYMOUTH TP
Adder
0.158823529411764720.135
3146326AYDLETT TAP
Adder
0.720.612
316004AC1-112 C
50/50
0.2990.299
316160AE1-175 E
Adder
0.77529411764705890.659
316169AC1-164 GEN
Adder
29.68117647058823425.229
316233AE1-074 C
Adder
1.62470588235294121.381
316240AF1-291 C
Adder
1.56941176470588251.334
316312AB1-027 C
50/50
0.4790.479
924516AB2-100 E1
Adder
1.3717647058823531.166
924517AB2-100 E2
Adder
1.3717647058823531.166
926785AC1-164_E
Adder
13.3352941176470611.335
934065AD1-033 E
Adder
2.68823529411764732.285
937226AE2-253 E
Adder
3.1152941176470592.648
939612AE1-191 E
Adder
3.8152941176470593.243
315051AA1-145 CT1
50/50
4.4424.442
315052AA1-145 CT2
50/50
4.444.44
939246AE1-155 E
Adder
5.6705882352941184.82
918512AA1-065 E OP
Adder
2.62941176470588232.235
919153AA1-139 E2
Adder
2.1752941176470591.849
919152AA1-139 E1
Adder
2.1752941176470591.849
920692AA2-178 E
Adder
2.05294117647058851.745
923994AB2-040_E
Adder
2.76941176470588252.354
924814AB2-134 E
Adder
8.3647058823529427.11
316084AB2-161 E
Adder
3.34823529411764742.846
316088AB2-174 E
Adder
2.94235294117647062.501
932046AC2-012 E
Adder
7.1352941176470596.065
316311AC2-079 C
Adder
3.2352941176470592.75
932596AC2-079 E
Adder
5.284.488
934146AD1-041 E
Adder
2.38470588235294122.027
934576AD1-082 E
Adder
2.6682352941176472.268
316349AD2-085 C
Adder
1.95294117647058821.66
936666AD2-085 E
Adder
3.18705882352941172.709
961611AG1-000B C
Adder
10.0094117647058818.508
941591AE2-156 C
Adder
9.744705882352948.283
944581AF1-123 C
Adder
24.2847058823529420.642
944582AF1-123 E
Adder
55.6105882352941247.269
944591AF1-124 C
Adder
24.37176470588235620.716
944592AF1-124 E
Adder
55.81176470588235447.44
944601AF1-125 C
Adder
23.9117647058823520.325
944602AF1-125 E
Adder
54.7376470588235346.527
944631AF1-128 C
Adder
29.89647058823529225.412
958261AF2-120 C
Adder
4.07294117647058853.462
958262AF2-120 E
Adder
2.7152941176470592.308
934501AD1-074 C
Adder
16.4776470588235314.006
934502AD1-074 E
Adder
8.3882352941176477.13
934511AD1-075 C
Adder
4.1188235294117653.501
934512AD1-075 E
Adder
2.09647058823529431.782
935161AD1-151 C
Adder
10.8541176470588259.226
935162AD1-151 E
Adder
7.235294117647066.15
938531AE1-072 C
Adder
9.3411764705882367.94
938532AE1-072 E
Adder
4.8694117647058834.139
939191AE1-149 C
Adder
6.78235294117647055.765
939192AE1-149 E
Adder
4.5223529411764713.844
939261AE1-157 C
Adder
6.5811764705882365.594
939262AE1-157 E
Adder
3.56941176470588233.034
939602AE1-190 E
Adder
0.95411764705882360.811
940431AE2-027 C
Adder
9.175294117647067.799
940432AE2-027 E
Adder
6.1164705882352945.199
940481AE2-033 C
Adder
8.0647058823529436.855
940482AE2-033 E
Adder
5.4364705882352954.621
940541AE2-040 C
Adder
1.44117647058823551.225
940551AE2-041 C
Adder
4.8305882352941174.106
940641AE2-051 C
Adder
7.4376470588235296.322
940642AE2-051 E
Adder
4.9588235294117654.215
941101AE2-104 C
Adder
1.81764705882352941.545
941102AE2-104 E
Adder
2.89058823529411772.457
943471AF1-018 C
Adder
4.8305882352941174.106
944641AF1-129 C
Adder
75.7352941176470664.375
3150431FOUR RIVERA
50/50
2.7882.788
3150441FOUR RIVERB
50/50
2.7882.788
3150451FOUR RIVERC
50/50
3.4073.407
3150461FOUR RIVERD
50/50
2.7482.748
3150471FOUR RIVERE
50/50
2.7482.748
3150481FOUR RIVERF
50/50
3.3563.356
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7881.788
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.9732.973
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.04428.044
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0691.069
NYPJM->LTFIMP_NY
CLTF
0.5450.545
CPLELTFEXP_CPLE->PJM
CLTF
3.7593.759
TVALTFEXP_TVA->PJM
CLTF
1.0611.061
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0350.035
MECLTFEXP_MEC->PJM
CLTF
0.2010.201
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0870.087
LAGNLTFEXP_LAGN->PJM
CLTF
1.4041.404
SIGELTFEXP_SIGE->PJM
CLTF
0.0060.006
O66PJM->LTFIMP_O-066
CMTX_NF
6.8436.843

Details for 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o RKYMT-WILS230_&_RKYMT-SHARPB115_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
Contingency Name:
RKYMT-WILS230_&_RKYMT-SHARPB115_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.07 %
Rating:478.0 MVA
Rating Type:B
MVA to Mitigate:507.02
MW Contribution:2.44
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
Contingency Name:
RKYMT-WILS230_&_RKYMT-SHARPB115_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.18 %
Rating:478.0 MVA
Rating Type:B
MVA to Mitigate:478.87
MW Contribution:2.48
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
50/50
1.251.25
961672AG1-007 E
50/50
0.7090.709
961941AG1-037 C
50/50
0.4240.424
961942AG1-037 E
50/50
0.2820.282
966621AG1-532 C
Adder
0.58941176470588240.501
966622AG1-532 E
Adder
0.39294117647058830.334
3145413WATKINS
Adder
0.32588235294117650.277
3145723EMPORIA
Adder
0.188235294117647060.16
3151311EDGECMA
50/50
13.61713.617
3151361ROSEMG1
50/50
1.321.32
3151371ROSEMS1
50/50
0.8170.817
3151381ROSEMG2
50/50
0.6180.618
3151391GASTONA
50/50
1.9091.909
918492AA1-063AE OP
Adder
2.2552941176470591.917
918532AA1-067 E
50/50
1.4951.495
919692AA2-053 E OP
50/50
2.5922.592
920042AA2-088 E OP
Adder
5.7423529411764714.881
925785AC1-054 E
Adder
1.1082352941176470.942
927146AC1-208 E
50/50
2.8172.817
934521AD1-076 C
50/50
11.47511.475
934522AD1-076 E
50/50
5.8495.849
943171AE2-346 C
50/50
0.1880.188
943172AE2-346 E
50/50
0.5080.508
960081AF2-299 C
Adder
0.78588235294117660.668
960082AF2-299 E
Adder
0.52352941176470590.445
3156011CONETOE2SOL
50/50
1.8621.862
3156063AA2-053SOLA
50/50
0.9250.925
316140AB2-099 C
50/50
0.0810.081
316141AB2-099 E
50/50
0.2120.212
900672V4-068 E
50/50
0.2360.236
917342Z2-044 E
50/50
0.4590.459
922923AB1-081 E OP
50/50
2.9882.988
923263AB1-132 E OP
50/50
3.8233.823
923573AB1-173 E OP
Adder
1.57882352941176471.342
940491AE2-034 C
50/50
0.9190.919
940492AE2-034 E
50/50
2.4562.456
946281AF1-292 C
Adder
0.65058823529411770.553
946282AF1-292 E
Adder
0.434117647058823550.369
957861AF2-080 C
50/50
12.88512.885
957862AF2-080 E
50/50
5.7125.712
3145393UNCAMP
Adder
2.66588235294117662.266
916042Z1-036 E
50/50
17.44917.449
938771AE1-103 C
Adder
1.22235294117647041.039
938772AE1-103 E
Adder
1.68705882352941171.434
943612AF1-032 E
Adder
0.28588235294117650.243
3151411GASTONB
50/50
1.9091.909
3152921DOMTR78
50/50
1.6181.618
3156116Z1-036WIND
50/50
0.4010.401
913392Y1-086 E
Adder
0.81411764705882350.692
923832AB2-022 E
Adder
0.460.391
957492AF2-043 E
Adder
0.440.374
901082W1-029 E
Adder
14.01882352941176511.916
917122Z2-027 E
Adder
0.53882352941176470.458
957871AF2-081 C
Adder
2.9035294117647062.468
957872AF2-081 E
Adder
1.24470588235294131.058
958161AF2-110 C
Adder
0.434117647058823550.369
958162AF2-110 E
Adder
0.69058823529411760.587
917512Z2-088 E OP1
50/50
7.2857.285
926071AC1-086 C
50/50
13.13513.135
926072AC1-086 E
50/50
5.9785.978
927021AC1-189 C
50/50
14.18714.187
927022AC1-189 E
50/50
7.0677.067
933981AD1-022 C
50/50
8.3658.365
933982AD1-022 E
50/50
4.5544.554
962572AG1-106 E
50/50
0.7430.743
962571AG1-106 C
50/50
1.6991.699
3145946PLYMOUTH TP
50/50
0.2960.296
3146326AYDLETT TAP
Adder
0.42235294117647060.359
316005AA1-067 C
50/50
0.570.57
316011AB1-132 C OP
50/50
1.4581.458
316049AB1-081 C OP
50/50
1.1391.139
316210AC1-098 C
50/50
0.710.71
316212AC1-099 C
50/50
0.2380.238
316263AC1-034 C
50/50
5.3235.323
316274AC1-208 C
50/50
6.3436.343
316317KELFORD C
50/50
0.3030.303
316318V4-068 C
50/50
0.0530.053
316319Z2-044 C
50/50
0.1620.162
917332KELFORD E
50/50
1.3911.391
924516AB2-100 E1
Adder
1.31294117647058851.116
924517AB2-100 E2
Adder
1.31294117647058851.116
925595AC1-034 E
50/50
4.0154.015
926206AC1-098 E
50/50
2.752.75
926214AC1-099 E
50/50
0.9080.908
3156021HOLLOMANSOL
50/50
1.8471.847
918512AA1-065 E OP
50/50
5.5525.552
919153AA1-139 E2
Adder
1.18705882352941171.009
919152AA1-139 E1
Adder
1.18705882352941171.009
316327AA2-057 C
50/50
0.9750.975
919710AA2-057 E
50/50
2.9712.971
315614AA2-178 C
50/50
1.2481.248
920692AA2-178 E
50/50
3.2743.274
923994AB2-040_E
Adder
2.9611764705882352.517
316359AB2-059 C OP
50/50
1.3431.343
924152AB2-059 E OP
50/50
4.2334.233
316174AB2-169_C
50/50
1.5541.554
925122AB2-169 E
50/50
8.5338.533
316088AB2-174 E
Adder
3.0152941176470592.563
316311AC2-079 C
Adder
1.65058823529411771.403
932596AC2-079 E
Adder
2.69411764705882372.29
3137643SOCKMAN
Adder
0.370588235294117660.315
932631AC2-084 C
50/50
0.7560.756
932632AC2-084 E
50/50
2.432.43
934321AD1-056 C
50/50
4.7644.764
934322AD1-056 E
50/50
2.5842.584
934331AD1-057 C
50/50
2.6572.657
934332AD1-057 E
50/50
1.3841.384
934501AD1-074 C
50/50
31.59531.595
934502AD1-074 E
50/50
16.08316.083
934511AD1-075 C
50/50
7.8997.899
934512AD1-075 E
50/50
4.0214.021
938531AE1-072 C
Adder
5.3705882352941184.565
938532AE1-072 E
Adder
2.82.38
940481AE2-033 C
Adder
4.7576470588235294.044
940482AE2-033 E
Adder
3.2082352941176472.727
941101AE2-104 C
Adder
1.06352941176470580.904
941102AE2-104 E
Adder
1.69176470588235281.438
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
1.3941.394
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
5.8875.887
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.3390.339
G-007ALTFEXP_G-007A->PJM
CMTX
0.8590.859
VTFLTFEXP_VFT->PJM
CMTX
2.2892.289
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
4.6924.692
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.2223.222
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.4161.416
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.0014.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.6630.663
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.0942.094
MDUPJM->LTFIMP_MDU
CLTF
0.1430.143

Details for 6MACKEYS-6EDENTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.75 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:753.4
MW Contribution:2.46
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.59 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:788.85
MW Contribution:2.44
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
50/50
0.8010.801
961672AG1-007 E
50/50
0.4540.454
961941AG1-037 C
50/50
0.530.53
961942AG1-037 E
50/50
0.3530.353
3145723EMPORIA
Adder
0.174117647058823520.148
3151311EDGECMA
50/50
10.30210.302
3151361ROSEMG1
50/50
1.2891.289
3151371ROSEMS1
50/50
0.7980.798
3151381ROSEMG2
50/50
0.6030.603
3151391GASTONA
50/50
1.9231.923
918492AA1-063AE OP
Adder
2.0835294117647061.771
918532AA1-067 E
50/50
0.8370.837
919692AA2-053 E OP
50/50
2.8352.835
920042AA2-088 E OP
Adder
4.2329411764705883.598
927146AC1-208 E
50/50
2.7832.783
934521AD1-076 C
50/50
31.87131.871
934522AD1-076 E
50/50
16.24416.244
943171AE2-346 C
50/50
0.2360.236
943172AE2-346 E
50/50
0.6360.636
3156011CONETOE2SOL
50/50
1.151.15
3156063AA2-053SOLA
50/50
1.0121.012
316140AB2-099 C
50/50
0.1010.101
316141AB2-099 E
50/50
0.2650.265
900672V4-068 E
50/50
0.2380.238
917342Z2-044 E
50/50
0.3980.398
922923AB1-081 E OP
50/50
2.4132.413
923263AB1-132 E OP
50/50
3.8513.851
923573AB1-173 E OP
Adder
1.52470588235294141.296
940491AE2-034 C
50/50
3.6663.666
940492AE2-034 E
50/50
9.89.8
957861AF2-080 C
50/50
7.6547.654
957862AF2-080 E
50/50
3.3933.393
3151411GASTONB
50/50
1.9231.923
3152921DOMTR78
50/50
3.1353.135
917512Z2-088 E OP1
50/50
4.4994.499
926071AC1-086 C
50/50
13.23213.232
926072AC1-086 E
50/50
6.0226.022
927021AC1-189 C
50/50
8.4278.427
927022AC1-189 E
50/50
4.1984.198
933981AD1-022 C
50/50
20.07120.071
933982AD1-022 E
50/50
10.92710.927
962572AG1-106 E
50/50
0.7490.749
962571AG1-106 C
50/50
1.7111.711
3145946PLYMOUTH TP
50/50
0.8710.871
316005AA1-067 C
50/50
0.3190.319
316011AB1-132 C OP
50/50
1.4681.468
316049AB1-081 C OP
50/50
0.920.92
316210AC1-098 C
50/50
0.7470.747
316212AC1-099 C
50/50
0.250.25
316263AC1-034 C
50/50
4.2984.298
316274AC1-208 C
50/50
6.2686.268
316317KELFORD C
50/50
0.3720.372
316318V4-068 C
50/50
0.0530.053
316319Z2-044 C
50/50
0.1410.141
917332KELFORD E
50/50
1.711.71
924516AB2-100 E1
Adder
1.14470588235294120.973
924517AB2-100 E2
Adder
1.14470588235294120.973
925595AC1-034 E
50/50
3.2423.242
926206AC1-098 E
50/50
2.8932.893
926214AC1-099 E
50/50
0.9560.956
3156021HOLLOMANSOL
50/50
2.5732.573
918512AA1-065 E OP
50/50
7.7337.733
316327AA2-057 C
50/50
0.8920.892
919710AA2-057 E
50/50
2.722.72
315614AA2-178 C
50/50
4.9824.982
920692AA2-178 E
50/50
13.06713.067
923994AB2-040_E
Adder
2.86000000000000032.431
316359AB2-059 C OP
50/50
1.0841.084
924152AB2-059 E OP
50/50
3.4183.418
316174AB2-169_C
50/50
2.0162.016
925122AB2-169 E
50/50
11.07111.071
316088AB2-174 E
Adder
2.86235294117647052.433
3137643SOCKMAN
Adder
0.368235294117647050.313
932631AC2-084 C
50/50
0.7960.796
932632AC2-084 E
50/50
2.5572.557
934321AD1-056 C
50/50
4.0394.039
934322AD1-056 E
50/50
2.1912.191
934331AD1-057 C
50/50
2.2532.253
934332AD1-057 E
50/50
1.1731.173
934501AD1-074 C
50/50
87.75587.755
934502AD1-074 E
50/50
44.67244.672
934511AD1-075 C
50/50
21.93921.939
934512AD1-075 E
50/50
11.16811.168
938531AE1-072 C
Adder
-9.841176470588236-8.365
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7381.738
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.1399.139
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.9675.967
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.51826.518
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4280.428
NYPJM->LTFIMP_NY
CLTF
0.190.19
LGEELTFEXP_LGEE->PJM
CLTF
0.3440.344
WECLTFEXP_WEC->PJM
CLTF
0.1860.186
CPLELTFEXP_CPLE->PJM
CLTF
3.6463.646
TVALTFEXP_TVA->PJM
CLTF
1.5721.572
MECLTFEXP_MEC->PJM
CLTF
1.0871.087
LAGNLTFEXP_LAGN->PJM
CLTF
2.0172.017
SIGELTFEXP_SIGE->PJM
CLTF
0.0670.067
O66PJM->LTFIMP_O-066
CMTX_NF
2.7222.722

Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:161.64 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:923.83
MW Contribution:3.83
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2092_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:168.52 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:963.14
MW Contribution:3.82
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
50/50
1.1121.112
961672AG1-007 E
50/50
0.630.63
961941AG1-037 C
50/50
0.8430.843
961942AG1-037 E
50/50
0.5620.562
966621AG1-532 C
50/50
0.8350.835
966622AG1-532 E
50/50
0.5560.556
313506AB1-173 C OP
50/50
0.8160.816
3145723EMPORIA
50/50
0.2710.271
3151261ROARAP2
50/50
1.211.21
3151281ROARAP4
50/50
1.1451.145
3151311EDGECMA
50/50
14.76714.767
3151361ROSEMG1
50/50
1.9891.989
3151371ROSEMS1
50/50
1.2321.232
3151381ROSEMG2
50/50
0.9310.931
3151391GASTONA
50/50
2.992.99
918492AA1-063AE OP
50/50
3.2163.216
918532AA1-067 E
50/50
1.1251.125
919692AA2-053 E OP
50/50
4.4424.442
920042AA2-088 E OP
50/50
6.4046.404
925785AC1-054 E
Adder
1.90117647058823551.616
927146AC1-208 E
50/50
4.2494.249
934521AD1-076 C
50/50
25.10225.102
934522AD1-076 E
50/50
12.79412.794
943171AE2-346 C
50/50
0.3740.374
943172AE2-346 E
50/50
1.0111.011
960081AF2-299 C
50/50
1.1131.113
960082AF2-299 E
50/50
0.7420.742
3156011CONETOE2SOL
50/50
1.5831.583
3156063AA2-053SOLA
50/50
1.5851.585
316140AB2-099 C
50/50
0.1610.161
316141AB2-099 E
50/50
0.4210.421
900672V4-068 E
50/50
0.3710.371
917342Z2-044 E
50/50
0.5880.588
922923AB1-081 E OP
50/50
3.4943.494
923263AB1-132 E OP
50/50
5.9885.988
923573AB1-173 E OP
50/50
2.3742.374
940491AE2-034 C
50/50
2.3412.341
940492AE2-034 E
50/50
6.2586.258
946281AF1-292 C
50/50
0.9210.921
946282AF1-292 E
50/50
0.6140.614
957861AF2-080 C
50/50
10.44310.443
957862AF2-080 E
50/50
4.6294.629
916042Z1-036 E
50/50
57.18957.189
3151411GASTONB
50/50
2.992.99
3152921DOMTR78
50/50
2.6612.661
3156073AA1-063SOLA
50/50
1.1081.108
3156083AA2-088SOLA
50/50
0.6410.641
3156116Z1-036WIND
50/50
1.3161.316
917512Z2-088 E OP1
50/50
6.1936.193
926071AC1-086 C
50/50
20.57620.576
926072AC1-086 E
50/50
9.3659.365
927021AC1-189 C
50/50
11.49811.498
927022AC1-189 E
50/50
5.7275.727
933981AD1-022 C
50/50
18.40618.406
933982AD1-022 E
50/50
10.0210.02
962572AG1-106 E
50/50
1.1641.164
962571AG1-106 C
50/50
2.6612.661
3145946PLYMOUTH TP
50/50
0.6620.662
316005AA1-067 C
50/50
0.4290.429
316011AB1-132 C OP
50/50
2.2832.283
316023AB2-100 C2
50/50
0.5940.594
316049AB1-081 C OP
50/50
1.3321.332
316210AC1-098 C
50/50
1.1521.152
316212AC1-099 C
50/50
0.3860.386
316263AC1-034 C
50/50
6.2256.225
316274AC1-208 C
50/50
9.5699.569
316317KELFORD C
50/50
0.5890.589
316318V4-068 C
50/50
0.0840.084
316319Z2-044 C
50/50
0.2070.207
316365AB2-100 C1
50/50
0.5940.594
917332KELFORD E
50/50
2.7032.703
924516AB2-100 E1
50/50
1.791.79
924517AB2-100 E2
50/50
1.791.79
925595AC1-034 E
50/50
4.6964.696
926206AC1-098 E
50/50
4.4614.461
926214AC1-099 E
50/50
1.4741.474
3156021HOLLOMANSOL
50/50
4.1274.127
918512AA1-065 E OP
50/50
12.40212.402
316327AA2-057 C
50/50
1.3351.335
919710AA2-057 E
50/50
4.074.07
315614AA2-178 C
50/50
3.1813.181
920692AA2-178 E
50/50
8.3448.344
316181AB2-040 GEN
50/50
0.9190.919
923994AB2-040_E
50/50
4.4524.452
316359AB2-059 C OP
50/50
1.571.57
924152AB2-059 E OP
50/50
4.954.95
316174AB2-169_C
50/50
1.9111.911
925122AB2-169 E
50/50
10.49610.496
316087AB2-174 C
50/50
0.8050.805
316088AB2-174 E
50/50
4.4594.459
3137643SOCKMAN
50/50
0.5730.573
932631AC2-084 C
50/50
1.2271.227
932632AC2-084 E
50/50
3.9433.943
934321AD1-056 C
50/50
5.9965.996
934322AD1-056 E
50/50
3.2523.252
934331AD1-057 C
50/50
3.3453.345
934332AD1-057 E
50/50
1.7421.742
934501AD1-074 C
50/50
69.11769.117
934502AD1-074 E
50/50
35.18435.184
934511AD1-075 C
50/50
17.27917.279
934512AD1-075 E
50/50
8.7968.796
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.4372.437
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.90912.909
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4168.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.337.3
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6050.605
NYPJM->LTFIMP_NY
CLTF
0.2690.269
LGEELTFEXP_LGEE->PJM
CLTF
0.4860.486
WECLTFEXP_WEC->PJM
CLTF
0.2620.262
CPLELTFEXP_CPLE->PJM
CLTF
5.1125.112
TVALTFEXP_TVA->PJM
CLTF
2.2172.217
MECLTFEXP_MEC->PJM
CLTF
1.5351.535
LAGNLTFEXP_LAGN->PJM
CLTF
2.8432.843
SIGELTFEXP_SIGE->PJM
CLTF
0.0950.095
O66PJM->LTFIMP_O-066
CMTX_NF
3.8433.843

Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.53 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:608.85
MW Contribution:3.16
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.35 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:642.1
MW Contribution:3.15
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
50/50
0.8770.877
961672AG1-007 E
50/50
0.4970.497
961941AG1-037 C
50/50
0.7020.702
961942AG1-037 E
50/50
0.4680.468
966621AG1-532 C
Adder
0.6917647058823530.588
966622AG1-532 E
Adder
0.46117647058823530.392
313506AB1-173 C OP
50/50
0.6750.675
3145723EMPORIA
Adder
0.22470588235294120.191
3151261ROARAP2
50/50
11
3151281ROARAP4
50/50
0.9460.946
3151311EDGECMA
50/50
11.80811.808
3151361ROSEMG1
50/50
1.6391.639
3151371ROSEMS1
50/50
1.0151.015
3151381ROSEMG2
50/50
0.7680.768
3151391GASTONA
50/50
2.4722.472
918492AA1-063AE OP
50/50
2.6512.651
918532AA1-067 E
50/50
0.8740.874
919692AA2-053 E OP
50/50
3.6823.682
920042AA2-088 E OP
Adder
5.2376470588235294.452
925785AC1-054 E
Adder
1.57058823529411761.335
927146AC1-208 E
50/50
3.4873.487
934521AD1-076 C
50/50
12.94512.945
934522AD1-076 E
50/50
6.5986.598
943171AE2-346 C
50/50
0.3120.312
943172AE2-346 E
50/50
0.8430.843
960081AF2-299 C
Adder
0.92117647058823540.783
960082AF2-299 E
Adder
0.61411764705882350.522
3156011CONETOE2SOL
50/50
1.2431.243
3156063AA2-053SOLA
50/50
1.3141.314
316140AB2-099 C
50/50
0.1340.134
316141AB2-099 E
50/50
0.3510.351
900672V4-068 E
50/50
0.3070.307
917342Z2-044 E
50/50
0.4760.476
922923AB1-081 E OP
50/50
2.8072.807
923263AB1-132 E OP
50/50
4.954.95
923573AB1-173 E OP
50/50
1.9641.964
940491AE2-034 C
50/50
0.8630.863
940492AE2-034 E
50/50
2.3072.307
946281AF1-292 C
Adder
0.76235294117647070.648
946282AF1-292 E
Adder
0.50823529411764710.432
957861AF2-080 C
50/50
8.1668.166
957862AF2-080 E
50/50
3.623.62
916042Z1-036 E
Adder
9.7517647058823538.289
3151411GASTONB
50/50
2.4722.472
3152921DOMTR78
50/50
1.4921.492
3156073AA1-063SOLA
50/50
0.9130.913
917512Z2-088 E OP1
50/50
4.8634.863
926071AC1-086 C
50/50
17.00917.009
926072AC1-086 E
50/50
7.7427.742
927021AC1-189 C
50/50
8.9918.991
927022AC1-189 E
50/50
4.4794.479
933981AD1-022 C
50/50
11.12811.128
933982AD1-022 E
50/50
6.0586.058
962572AG1-106 E
50/50
0.9630.963
962571AG1-106 C
50/50
2.22.2
3145946PLYMOUTH TP
50/50
0.3260.326
316005AA1-067 C
50/50
0.3330.333
316011AB1-132 C OP
50/50
1.8881.888
316049AB1-081 C OP
50/50
1.071.07
316210AC1-098 C
50/50
0.9490.949
316212AC1-099 C
50/50
0.3180.318
316263AC1-034 C
50/50
4.9994.999
316274AC1-208 C
50/50
7.8537.853
316317KELFORD C
50/50
0.4890.489
316318V4-068 C
50/50
0.0690.069
316319Z2-044 C
50/50
0.1680.168
917332KELFORD E
50/50
2.2482.248
924516AB2-100 E1
Adder
1.48352941176470581.261
924517AB2-100 E2
Adder
1.48352941176470581.261
925595AC1-034 E
50/50
3.7713.771
926206AC1-098 E
50/50
3.6753.675
926214AC1-099 E
50/50
1.2141.214
3156021HOLLOMANSOL
50/50
3.4513.451
918512AA1-065 E OP
50/50
10.3710.37
316327AA2-057 C
50/50
1.0871.087
919710AA2-057 E
50/50
3.3143.314
315614AA2-178 C
50/50
1.1731.173
920692AA2-178 E
50/50
3.0763.076
316181AB2-040 GEN
50/50
0.7610.761
923994AB2-040_E
50/50
3.6833.683
316359AB2-059 C OP
50/50
1.2611.261
924152AB2-059 E OP
50/50
3.9763.976
316174AB2-169_C
50/50
1.1891.189
925122AB2-169 E
50/50
6.5316.531
316088AB2-174 E
Adder
3.68941176470588243.136
3137643SOCKMAN
50/50
0.4740.474
932631AC2-084 C
50/50
1.0111.011
932632AC2-084 E
50/50
3.2493.249
934321AD1-056 C
50/50
4.8664.866
934322AD1-056 E
50/50
2.6392.639
934331AD1-057 C
50/50
2.7142.714
934332AD1-057 E
50/50
1.4131.413
934501AD1-074 C
50/50
35.64335.643
934502AD1-074 E
50/50
18.14418.144
934511AD1-075 C
50/50
8.9118.911
934512AD1-075 E
50/50
4.5364.536
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9321.932
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.35910.359
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7216.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.62929.629
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4730.473
NYPJM->LTFIMP_NY
CLTF
0.210.21
LGEELTFEXP_LGEE->PJM
CLTF
0.3890.389
WECLTFEXP_WEC->PJM
CLTF
0.210.21
CPLELTFEXP_CPLE->PJM
CLTF
4.0524.052
TVALTFEXP_TVA->PJM
CLTF
1.7681.768
MECLTFEXP_MEC->PJM
CLTF
1.2291.229
LAGNLTFEXP_LAGN->PJM
CLTF
2.2672.267
SIGELTFEXP_SIGE->PJM
CLTF
0.0760.076
O66PJM->LTFIMP_O-066
CMTX_NF
3.0083.008

Details for 6PEMBROKE-6WALBMRL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6PEMBROKE-6WALBMRL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:118.52 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:868.96
MW Contribution:2.46
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6PEMBROKE-6WALBMRL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:123.37 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:904.57
MW Contribution:2.44
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
50/50
0.8010.801
961672AG1-007 E
50/50
0.4540.454
961941AG1-037 C
50/50
0.530.53
961942AG1-037 E
50/50
0.3530.353
3151311EDGECMA
50/50
10.28910.289
3151361ROSEMG1
50/50
1.2871.287
3151371ROSEMS1
50/50
0.7970.797
3151381ROSEMG2
50/50
0.6030.603
3151391GASTONA
50/50
1.9211.921
918492AA1-063AE OP
Adder
2.0811764705882351.769
918532AA1-067 E
50/50
0.8360.836
919692AA2-053 E OP
50/50
2.8322.832
927146AC1-208 E
50/50
2.782.78
934521AD1-076 C
50/50
31.86231.862
934522AD1-076 E
50/50
16.2416.24
943171AE2-346 C
50/50
0.2350.235
943172AE2-346 E
50/50
0.6360.636
3156011CONETOE2SOL
50/50
1.1491.149
3156063AA2-053SOLA
50/50
1.011.01
316140AB2-099 C
50/50
0.1010.101
316141AB2-099 E
50/50
0.2650.265
900672V4-068 E
50/50
0.2370.237
917342Z2-044 E
50/50
0.3980.398
922923AB1-081 E OP
50/50
2.412.41
923263AB1-132 E OP
50/50
3.8463.846
923573AB1-173 E OP
Adder
1.52235294117647071.294
940491AE2-034 C
50/50
3.6663.666
940492AE2-034 E
50/50
9.7989.798
957861AF2-080 C
50/50
7.6477.647
957862AF2-080 E
50/50
3.393.39
916042Z1-036 E
50/50
112.394112.394
3151411GASTONB
50/50
1.9211.921
3152921DOMTR78
50/50
3.1343.134
3156116Z1-036WIND
50/50
2.5862.586
917512Z2-088 E OP1
50/50
4.4954.495
926071AC1-086 C
50/50
13.21613.216
926072AC1-086 E
50/50
6.0156.015
927021AC1-189 C
50/50
8.428.42
927022AC1-189 E
50/50
4.1944.194
933981AD1-022 C
50/50
20.06420.064
933982AD1-022 E
50/50
10.92310.923
962572AG1-106 E
50/50
0.7480.748
962571AG1-106 C
50/50
1.7091.709
3145946PLYMOUTH TP
50/50
0.8710.871
316005AA1-067 C
50/50
0.3190.319
316011AB1-132 C OP
50/50
1.4671.467
316049AB1-081 C OP
50/50
0.9190.919
316210AC1-098 C
50/50
0.7460.746
316212AC1-099 C
50/50
0.250.25
316263AC1-034 C
50/50
4.2924.292
316274AC1-208 C
50/50
6.2616.261
316317KELFORD C
50/50
0.3720.372
316318V4-068 C
50/50
0.0530.053
316319Z2-044 C
50/50
0.140.14
917332KELFORD E
50/50
1.7081.708
925595AC1-034 E
50/50
3.2383.238
926206AC1-098 E
50/50
2.892.89
926214AC1-099 E
50/50
0.9550.955
3156021HOLLOMANSOL
50/50
2.5722.572
918512AA1-065 E OP
50/50
7.7297.729
316327AA2-057 C
50/50
0.8910.891
919710AA2-057 E
50/50
2.7162.716
315614AA2-178 C
50/50
4.9814.981
920692AA2-178 E
50/50
13.06413.064
923994AB2-040_E
Adder
2.8552941176470592.427
316359AB2-059 C OP
50/50
1.0831.083
924152AB2-059 E OP
50/50
3.4143.414
316174AB2-169_C
50/50
2.0152.015
925122AB2-169 E
50/50
11.06611.066
316088AB2-174 E
Adder
2.8564705882352942.428
3137643SOCKMAN
Adder
0.368235294117647050.313
932631AC2-084 C
50/50
0.7950.795
932632AC2-084 E
50/50
2.5552.555
934321AD1-056 C
50/50
4.0344.034
934322AD1-056 E
50/50
2.1882.188
934331AD1-057 C
50/50
2.252.25
934332AD1-057 E
50/50
1.1721.172
934501AD1-074 C
50/50
87.7387.73
934502AD1-074 E
50/50
44.65944.659
934511AD1-075 C
50/50
21.93221.932
934512AD1-075 E
50/50
11.16511.165
938531AE1-072 C
Adder
-9.852941176470589-8.375
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7331.733
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.928.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.8825.882
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.38626.386
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4420.442
NYPJM->LTFIMP_NY
CLTF
0.1970.197
LGEELTFEXP_LGEE->PJM
CLTF
0.3360.336
WECLTFEXP_WEC->PJM
CLTF
0.1810.181
CPLELTFEXP_CPLE->PJM
CLTF
3.6343.634
TVALTFEXP_TVA->PJM
CLTF
1.5541.554
MECLTFEXP_MEC->PJM
CLTF
1.0671.067
LAGNLTFEXP_LAGN->PJM
CLTF
1.9941.994
SIGELTFEXP_SIGE->PJM
CLTF
0.0660.066
O66PJM->LTFIMP_O-066
CMTX_NF
2.8092.809

Details for 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:116.77 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:856.13
MW Contribution:2.46
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:121.62 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:891.74
MW Contribution:2.44
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
50/50
0.8010.801
961672AG1-007 E
50/50
0.4540.454
961941AG1-037 C
50/50
0.530.53
961942AG1-037 E
50/50
0.3530.353
3151311EDGECMA
50/50
10.28910.289
3151361ROSEMG1
50/50
1.2871.287
3151371ROSEMS1
50/50
0.7970.797
3151381ROSEMG2
50/50
0.6030.603
3151391GASTONA
50/50
1.9211.921
918492AA1-063AE OP
Adder
2.0811764705882351.769
918532AA1-067 E
50/50
0.8360.836
919692AA2-053 E OP
50/50
2.8322.832
927146AC1-208 E
50/50
2.782.78
934521AD1-076 C
50/50
31.86231.862
934522AD1-076 E
50/50
16.2416.24
943171AE2-346 C
50/50
0.2350.235
943172AE2-346 E
50/50
0.6360.636
3156011CONETOE2SOL
50/50
1.1491.149
3156063AA2-053SOLA
50/50
1.011.01
316140AB2-099 C
50/50
0.1010.101
316141AB2-099 E
50/50
0.2650.265
900672V4-068 E
50/50
0.2370.237
917342Z2-044 E
50/50
0.3980.398
922923AB1-081 E OP
50/50
2.412.41
923263AB1-132 E OP
50/50
3.8463.846
923573AB1-173 E OP
Adder
1.52235294117647071.294
940491AE2-034 C
50/50
3.6663.666
940492AE2-034 E
50/50
9.7989.798
957861AF2-080 C
50/50
7.6477.647
957862AF2-080 E
50/50
3.393.39
916042Z1-036 E
50/50
112.394112.394
3151411GASTONB
50/50
1.9211.921
3152921DOMTR78
50/50
3.1343.134
3156116Z1-036WIND
50/50
2.5862.586
917512Z2-088 E OP1
50/50
4.4954.495
926071AC1-086 C
50/50
13.21613.216
926072AC1-086 E
50/50
6.0156.015
927021AC1-189 C
50/50
8.428.42
927022AC1-189 E
50/50
4.1944.194
933981AD1-022 C
50/50
20.06420.064
933982AD1-022 E
50/50
10.92310.923
962572AG1-106 E
50/50
0.7480.748
962571AG1-106 C
50/50
1.7091.709
3145946PLYMOUTH TP
50/50
0.8710.871
316005AA1-067 C
50/50
0.3190.319
316011AB1-132 C OP
50/50
1.4671.467
316049AB1-081 C OP
50/50
0.9190.919
316210AC1-098 C
50/50
0.7460.746
316212AC1-099 C
50/50
0.250.25
316263AC1-034 C
50/50
4.2924.292
316274AC1-208 C
50/50
6.2616.261
316317KELFORD C
50/50
0.3720.372
316318V4-068 C
50/50
0.0530.053
316319Z2-044 C
50/50
0.140.14
917332KELFORD E
50/50
1.7081.708
925595AC1-034 E
50/50
3.2383.238
926206AC1-098 E
50/50
2.892.89
926214AC1-099 E
50/50
0.9550.955
3156021HOLLOMANSOL
50/50
2.5722.572
918512AA1-065 E OP
50/50
7.7297.729
316327AA2-057 C
50/50
0.8910.891
919710AA2-057 E
50/50
2.7162.716
315614AA2-178 C
50/50
4.9814.981
920692AA2-178 E
50/50
13.06413.064
923994AB2-040_E
Adder
2.8552941176470592.427
316359AB2-059 C OP
50/50
1.0831.083
924152AB2-059 E OP
50/50
3.4143.414
316174AB2-169_C
50/50
2.0152.015
925122AB2-169 E
50/50
11.06611.066
316088AB2-174 E
Adder
2.8564705882352942.428
3137643SOCKMAN
Adder
0.368235294117647050.313
932631AC2-084 C
50/50
0.7950.795
932632AC2-084 E
50/50
2.5552.555
934321AD1-056 C
50/50
4.0344.034
934322AD1-056 E
50/50
2.1882.188
934331AD1-057 C
50/50
2.252.25
934332AD1-057 E
50/50
1.1721.172
934501AD1-074 C
50/50
87.7387.73
934502AD1-074 E
50/50
44.65944.659
934511AD1-075 C
50/50
21.93221.932
934512AD1-075 E
50/50
11.16511.165
938531AE1-072 C
Adder
-9.852941176470589-8.375
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7331.733
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.928.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.8825.882
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.38626.386
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4420.442
NYPJM->LTFIMP_NY
CLTF
0.1970.197
LGEELTFEXP_LGEE->PJM
CLTF
0.3360.336
WECLTFEXP_WEC->PJM
CLTF
0.1810.181
CPLELTFEXP_CPLE->PJM
CLTF
3.6343.634
TVALTFEXP_TVA->PJM
CLTF
1.5541.554
MECLTFEXP_MEC->PJM
CLTF
1.0671.067
LAGNLTFEXP_LAGN->PJM
CLTF
1.9941.994
SIGELTFEXP_SIGE->PJM
CLTF
0.0660.066
O66PJM->LTFIMP_O-066
CMTX_NF
2.8092.809

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.47 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:865.08
MW Contribution:7.86
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:132.38 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:898.41
MW Contribution:7.87
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
50/50
0.9020.902
961672AG1-007 E
50/50
0.5110.511
961941AG1-037 C
50/50
0.480.48
961942AG1-037 E
50/50
0.320.32
966621AG1-532 C
50/50
3.2313.231
966622AG1-532 E
50/50
2.1542.154
313506AB1-173 C OP
50/50
2.1742.174
3145413WATKINS
50/50
0.4340.434
3145723EMPORIA
50/50
0.9510.951
3147043LAWRENC
50/50
0.5440.544
3151261ROARAP2
50/50
2.0542.054
3151281ROARAP4
50/50
1.9431.943
3151311EDGECMA
50/50
16.29316.293
3151361ROSEMG1
50/50
3.9133.913
3151371ROSEMS1
50/50
2.4242.424
3151381ROSEMG2
50/50
1.8331.833
3151391GASTONA
50/50
6.1436.143
918492AA1-063AE OP
50/50
5.1265.126
918532AA1-067 E
50/50
0.5780.578
919692AA2-053 E OP
50/50
5.8725.872
920042AA2-088 E OP
50/50
9.2439.243
925785AC1-054 E
50/50
3.2563.256
927146AC1-208 E
50/50
4.8644.864
934521AD1-076 C
Adder
7.235294117647066.15
934522AD1-076 E
Adder
3.6882352941176473.135
943171AE2-346 C
50/50
0.2130.213
943172AE2-346 E
50/50
0.5750.575
960081AF2-299 C
50/50
4.3084.308
960082AF2-299 E
50/50
2.8722.872
3156011CONETOE2SOL
50/50
1.1631.163
3156063AA2-053SOLA
50/50
2.0952.095
316129AC1-054 C
50/50
1.1551.155
316140AB2-099 C
50/50
0.0910.091
316141AB2-099 E
50/50
0.240.24
900672V4-068 E
50/50
0.330.33
917342Z2-044 E
50/50
0.6430.643
922923AB1-081 E OP
50/50
3.8483.848
923263AB1-132 E OP
50/50
12.30112.301
923573AB1-173 E OP
50/50
6.3236.323
946281AF1-292 C
50/50
3.5663.566
946282AF1-292 E
50/50
2.3782.378
957861AF2-080 C
50/50
6.86.8
957862AF2-080 E
50/50
3.0143.014
3151151S HAMPT1
50/50
0.9630.963
3151411GASTONB
50/50
6.1436.143
3156073AA1-063SOLA
50/50
1.7661.766
3156083AA2-088SOLA
50/50
0.9260.926
923852AB2-025 E
50/50
4.7594.759
917512Z2-088 E OP1
50/50
4.554.55
926071AC1-086 C
50/50
42.26942.269
926072AC1-086 E
50/50
19.23819.238
927021AC1-189 C
50/50
7.4877.487
927022AC1-189 E
50/50
3.7293.729
933981AD1-022 C
50/50
5.8115.811
933982AD1-022 E
50/50
3.1633.163
962572AG1-106 E
50/50
2.3922.392
962571AG1-106 C
50/50
5.4675.467
316005AA1-067 C
50/50
0.220.22
316011AB1-132 C OP
50/50
4.6914.691
316023AB2-100 C2
50/50
2.7722.772
316049AB1-081 C OP
50/50
1.4671.467
316210AC1-098 C
50/50
1.0771.077
316212AC1-099 C
50/50
0.3610.361
316263AC1-034 C
50/50
6.8536.853
316274AC1-208 C
50/50
10.95410.954
316315AB2-025 C
50/50
1.6711.671
316317KELFORD C
50/50
0.3660.366
316318V4-068 C
50/50
0.0740.074
316319Z2-044 C
50/50
0.2270.227
316365AB2-100 C1
50/50
2.7722.772
917332KELFORD E
50/50
1.681.68
924516AB2-100 E1
50/50
8.3568.356
924517AB2-100 E2
50/50
8.3568.356
925595AC1-034 E
50/50
5.175.17
926206AC1-098 E
50/50
4.1694.169
926214AC1-099 E
50/50
1.3771.377
3156021HOLLOMANSOL
50/50
1.5981.598
918512AA1-065 E OP
50/50
4.8034.803
316327AA2-057 C
50/50
1.4571.457
919710AA2-057 E
50/50
4.4414.441
316181AB2-040 GEN
50/50
2.4482.448
923994AB2-040_E
50/50
11.85511.855
316359AB2-059 C OP
50/50
1.7291.729
924152AB2-059 E OP
50/50
5.4515.451
316174AB2-169_C
50/50
0.7270.727
925122AB2-169 E
50/50
3.9923.992
316087AB2-174 C
50/50
2.4072.407
316088AB2-174 E
50/50
13.32613.326
3137643SOCKMAN
50/50
1.2021.202
932631AC2-084 C
50/50
1.1471.147
932632AC2-084 E
50/50
3.6853.685
934321AD1-056 C
50/50
9.1119.111
934322AD1-056 E
50/50
4.9424.942
934331AD1-057 C
50/50
5.0825.082
934332AD1-057 E
50/50
2.6472.647
934501AD1-074 C
Adder
19.92235294117647416.934
934502AD1-074 E
Adder
10.1411764705882358.62
934511AD1-075 C
Adder
4.97999999999999954.233
934512AD1-075 E
Adder
2.53529411764705872.155
940481AE2-033 C
50/50
63.78563.785
940482AE2-033 E
50/50
43.00143.001
940541AE2-040 C
50/50
11.76711.767
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.022.02
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.519.51
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.6696.669
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.20331.203
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6960.696
NYPJM->LTFIMP_NY
CLTF
0.320.32
LGEELTFEXP_LGEE->PJM
CLTF
0.3650.365
WECLTFEXP_WEC->PJM
CLTF
0.1950.195
CPLELTFEXP_CPLE->PJM
CLTF
4.2374.237
TVALTFEXP_TVA->PJM
CLTF
1.7921.792
MECLTFEXP_MEC->PJM
CLTF
1.1761.176
LAGNLTFEXP_LAGN->PJM
CLTF
2.2982.298
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072
O66PJM->LTFIMP_O-066
CMTX_NF
4.4294.429

Details for 6THELMA-6LAKEVEW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 225_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6THELMA-6LAKEVEW 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 225_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:122.05 %
Rating:441.8 MVA
Rating Type:B
MVA to Mitigate:539.2
MW Contribution:22.96
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6THELMA-6LAKEVEW 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 225_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:121.99 %
Rating:441.8 MVA
Rating Type:B
MVA to Mitigate:538.95
MW Contribution:22.96
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151391GASTONA
50/50
17.94817.948
923263AB1-132 E OP
50/50
35.94335.943
3151411GASTONB
50/50
17.94817.948
926071AC1-086 C
50/50
123.504123.504
926072AC1-086 E
50/50
56.21156.211
962572AG1-106 E
50/50
6.9896.989
962571AG1-106 C
50/50
15.97515.975
316011AB1-132 C OP
50/50
13.70513.705
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.1590.159
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.1190.119
G-007PJM->LTFIMP_G-007
CMTX_NF
0.1670.167
NYPJM->LTFIMP_NY
CLTF
0.0880.088
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.3330.333
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0920.092
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0560.056
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.410.41
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0880.088
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.2750.275
O66PJM->LTFIMP_O-066
CMTX_NF
1.0681.068
MDUPJM->LTFIMP_MDU
CLTF
0.0160.016

Details for 6THELMA-6LAKEVEW 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 213_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6THELMA-6LAKEVEW 230.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 213_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:122.04 %
Rating:441.8 MVA
Rating Type:B
MVA to Mitigate:539.19
MW Contribution:22.96
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6THELMA-6LAKEVEW 230.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 213_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:121.99 %
Rating:441.8 MVA
Rating Type:B
MVA to Mitigate:538.95
MW Contribution:22.96
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151391GASTONA
50/50
17.94817.948
923263AB1-132 E OP
50/50
35.94335.943
3151411GASTONB
50/50
17.94817.948
926071AC1-086 C
50/50
123.504123.504
926072AC1-086 E
50/50
56.21156.211
962572AG1-106 E
50/50
6.9896.989
962571AG1-106 C
50/50
15.97515.975
316011AB1-132 C OP
50/50
13.70513.705
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.1590.159
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.1190.119
G-007PJM->LTFIMP_G-007
CMTX_NF
0.1670.167
NYPJM->LTFIMP_NY
CLTF
0.0880.088
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.3330.333
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.0920.092
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.0560.056
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.410.41
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0880.088
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.2750.275
O66PJM->LTFIMP_O-066
CMTX_NF
1.0681.068
MDUPJM->LTFIMP_MDU
CLTF
0.0160.016

Details for 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.68 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1020.42
MW Contribution:1.65
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.56 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:989.69
MW Contribution:1.58
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.332941176470588240.283
961672AG1-007 E
Adder
0.188235294117647060.16
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
963041AG1-153 C
Adder
1.9482352941176471.656
963042AG1-153 E
Adder
2.92235294117647062.484
966621AG1-532 C
Adder
0.61294117647058830.521
966622AG1-532 E
Adder
0.408235294117647030.347
3145413WATKINS
Adder
0.26470588235294120.225
3145723EMPORIA
Adder
0.185882352941176470.158
3151311EDGECMA
Adder
5.5117647058823534.685
918492AA1-063AE OP
Adder
1.59411764705882361.355
918532AA1-067 E
Adder
0.251764705882352950.214
919692AA2-053 E OP
Adder
1.64941176470588241.402
920042AA2-088 E OP
Adder
4.0811764705882353.469
925785AC1-054 E
Adder
1.2082352941176471.027
927146AC1-208 E
Adder
1.51.275
934521AD1-076 C
Adder
4.377647058823533.721
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
944011AF1-069 C
Adder
4.6141176470588243.922
944012AF1-069 E
Adder
1.7917647058823531.523
960081AF2-299 C
Adder
0.81647058823529410.694
960082AF2-299 E
Adder
0.54470588235294130.463
316141AB2-099 E
Adder
0.095294117647058830.081
900672V4-068 E
Adder
0.136470588235294120.116
917342Z2-044 E
Adder
0.215294117647058830.183
922923AB1-081 E OP
Adder
1.321.122
923263AB1-132 E OP
Adder
2.582.193
923573AB1-173 E OP
Adder
1.36823529411764721.163
924162AB2-060 E OP
Adder
1.3117647058823531.115
924302AB2-077 E O1
Adder
0.41176470588235290.35
924312AB2-078 E O1
Adder
0.41176470588235290.35
924322AB2-079 E O1
Adder
0.41176470588235290.35
940492AE2-034 E
Adder
1.09058823529411760.927
941031AE2-094 C
Adder
14.12000000000000112.002
941032AE2-094 E
Adder
6.3247058823529425.376
946281AF1-292 C
Adder
0.67529411764705880.574
946282AF1-292 E
Adder
0.45058823529411770.383
957481AF2-042 C
Adder
17.0152941176470614.463
957482AF2-042 E
Adder
11.3435294117647069.642
957861AF2-080 C
Adder
2.7023529411764712.297
957862AF2-080 E
Adder
1.19764705882352951.018
3145393UNCAMP
Adder
2.3247058823529411.976
916042Z1-036 E
Adder
9.9682352941176488.473
938771AE1-103 C
Adder
1.11764705882352940.95
938772AE1-103 E
Adder
1.5435294117647061.312
3143316POE
50/50
1.0861.086
3145256KINGFORK
Adder
0.357647058823529430.304
3145506HICKORY
Adder
0.72352941176470590.615
3150651CHESTF6
50/50
21.89721.897
3150731STONECA
50/50
4.5124.512
3150761HOPPOLC
50/50
1.0021.002
3150771HOPHCF1
50/50
1.5941.594
3150781HOPHCF2
50/50
1.5941.594
3150791HOPHCF3
50/50
1.5941.594
3150801HOPHCF4
50/50
2.4192.419
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
926662AC1-147 E
Adder
0.452941176470588240.385
926755AC1-161 E
Adder
3.78588235294117673.218
927226AC1-216 E
Adder
4.122352941176473.504
935112AD1-144 E
Adder
0.33176470588235290.282
942341AE2-247 C
Adder
0.68470588235294120.582
942342AE2-247 E
Adder
0.94470588235294130.803
943461AF1-017 C
Adder
0.61882352941176480.526
943462AF1-017 E
Adder
1.00941176470588250.858
943612AF1-032 E
Adder
0.320.272
316132AB2-190 C
50/50
2.4122.412
913392Y1-086 E
Adder
0.74470588235294120.633
916192Z1-068 E
Adder
0.63294117647058830.538
923832AB2-022 E
Adder
0.421176470588235260.358
923852AB2-025 E
Adder
0.6317647058823530.537
939312AE1-162 E
Adder
0.5717647058823530.486
946262AF1-291 E
50/50
1.6321.632
957492AF2-043 E
Adder
0.49294117647058820.419
901082W1-029 E
Adder
10.9870588235294139.339
917122Z2-027 E
Adder
0.457647058823529460.389
925332AB2-190 E
50/50
4.6914.691
925522AC1-027 E
Adder
0.410588235294117640.349
942001AE2-212 C
50/50
2.1112.111
942002AE2-212 E
50/50
1.4081.408
957871AF2-081 C
Adder
3.34117647058823542.84
957872AF2-081 E
Adder
1.4317647058823531.217
958161AF2-110 C
Adder
0.51764705882352950.44
958162AF2-110 E
Adder
0.82470588235294120.701
917512Z2-088 E OP1
Adder
1.73411764705882351.474
926071AC1-086 C
Adder
8.8647058823529427.535
926072AC1-086 E
Adder
4.0352941176470593.43
927021AC1-189 C
Adder
2.97529411764705862.529
927022AC1-189 E
Adder
1.48235294117647071.26
933291AC2-141 C
Adder
8.8694117647058827.539
933292AC2-141 E
Adder
3.78588235294117673.218
934621AD1-088 C
Adder
2.86941176470588262.439
934622AD1-088 E
Adder
1.38117647058823521.174
939411AE1-173 C
Adder
31.5352941176470626.805
939412AE1-173 E
Adder
21.0235294117647117.87
934012AD1-025 E
Adder
5.3364705882352944.536
933981AD1-022 C
Adder
3.162.686
933982AD1-022 E
Adder
1.721.462
962572AG1-106 E
Adder
0.50117647058823530.426
962571AG1-106 C
Adder
1.14705882352941170.975
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
3146326AYDLETT TAP
Adder
0.455294117647058850.387
316240AF1-291 C
50/50
2.4482.448
316263AC1-034 C
Adder
2.3517647058823531.999
316274AC1-208 C
Adder
3.3788235294117652.872
917332KELFORD E
Adder
0.61411764705882350.522
924516AB2-100 E1
Adder
1.36823529411764721.163
924517AB2-100 E2
Adder
1.36823529411764721.163
925595AC1-034 E
Adder
1.77411764705882361.508
926206AC1-098 E
Adder
1.35999999999999991.156
926214AC1-099 E
Adder
0.44941176470588240.382
934065AD1-033 E
Adder
1.6670588235294121.417
937226AE2-253 E
Adder
1.9482352941176471.656
918512AA1-065 E OP
Adder
2.04235294117647071.736
919153AA1-139 E2
Adder
1.36588235294117651.161
919152AA1-139 E1
Adder
1.36588235294117651.161
919710AA2-057 E
Adder
1.44823529411764731.231
920692AA2-178 E
Adder
1.4552941176470591.237
923994AB2-040_E
Adder
2.56588235294117652.181
924022AB2-043 E O1
Adder
1.60117647058823541.361
924152AB2-059 E OP
Adder
1.87058823529411791.59
924814AB2-134 E
Adder
6.7529411764705885.74
316083AB2-161 C
50/50
0.3210.321
316084AB2-161 E
50/50
3.213.21
925122AB2-169 E
Adder
2.04352941176470631.737
316088AB2-174 E
Adder
2.7588235294117652.345
932046AC2-012 E
Adder
4.4823529411764713.81
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
316381AD1-082 C
50/50
0.7330.733
934576AD1-082 E
50/50
2.5582.558
316349AD2-085 C
Adder
1.57882352941176471.342
936666AD2-085 E
Adder
2.5752941176470592.189
961611AG1-000B C
Adder
7.342352941176476.241
941591AE2-156 C
Adder
6.1141176470588245.197
944581AF1-123 C
Adder
15.03411764705882412.779
944582AF1-123 E
Adder
34.4258823529411829.262
944591AF1-124 C
Adder
15.08705882352941312.824
944592AF1-124 E
Adder
34.55058823529411429.368
944601AF1-125 C
Adder
14.80235294117647312.582
944602AF1-125 E
Adder
33.8847058823529428.802
964241AG1-285 C
Adder
3.85882352941176483.28
964242AG1-285 E
Adder
2.5717647058823532.186
3137643SOCKMAN
Adder
0.288235294117647030.245
932632AC2-084 E
Adder
1.20235294117647061.022
934321AD1-056 C
Adder
2.3988235294117652.039
934322AD1-056 E
Adder
1.30117647058823541.106
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934501AD1-074 C
Adder
12.05529411764705810.247
934502AD1-074 E
Adder
6.1364705882352945.216
934511AD1-075 C
Adder
3.01411764705882362.562
934512AD1-075 E
Adder
1.53411764705882361.304
934612AD1-087 E
Adder
1.1117647058823530.945
935161AD1-151 C
50/50
9.0229.022
935162AD1-151 E
50/50
6.0156.015
935172AD1-152 E
Adder
1.6435294117647061.397
937482AD2-202 E
Adder
0.32588235294117650.277
938531AE1-072 C
Adder
5.8905882352941185.007
938532AE1-072 E
Adder
3.07058823529411742.61
939191AE1-149 C
50/50
7.1377.137
939192AE1-149 E
50/50
4.7584.758
940431AE2-027 C
Adder
7.0447058823529425.988
940432AE2-027 E
Adder
4.6964705882352943.992
940481AE2-033 C
Adder
8.6517647058823537.354
940482AE2-033 E
Adder
5.8329411764705884.958
940541AE2-040 C
Adder
1.56117647058823541.327
940641AE2-051 C
Adder
6.0952941176470595.181
940642AE2-051 E
Adder
4.0635294117647063.454
941101AE2-104 C
Adder
1.26941176470588221.079
941102AE2-104 E
Adder
2.0188235294117651.716
944641AF1-129 C
50/50
120.262120.262
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883

Details for 6WALBMRL-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6WALBMRL-6S HERTFORD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:117.19 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:859.24
MW Contribution:2.46
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6WALBMRL-6S HERTFORD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 246_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:122.04 %
Rating:733.2 MVA
Rating Type:B
MVA to Mitigate:894.8
MW Contribution:2.44
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
50/50
0.8010.801
961672AG1-007 E
50/50
0.4540.454
961941AG1-037 C
50/50
0.530.53
961942AG1-037 E
50/50
0.3530.353
3151311EDGECMA
50/50
10.28910.289
3151361ROSEMG1
50/50
1.2871.287
3151371ROSEMS1
50/50
0.7970.797
3151381ROSEMG2
50/50
0.6030.603
3151391GASTONA
50/50
1.9211.921
918492AA1-063AE OP
Adder
2.0811764705882351.769
918532AA1-067 E
50/50
0.8360.836
919692AA2-053 E OP
50/50
2.8322.832
927146AC1-208 E
50/50
2.782.78
934521AD1-076 C
50/50
31.86231.862
934522AD1-076 E
50/50
16.2416.24
943171AE2-346 C
50/50
0.2350.235
943172AE2-346 E
50/50
0.6360.636
3156011CONETOE2SOL
50/50
1.1491.149
3156063AA2-053SOLA
50/50
1.011.01
316140AB2-099 C
50/50
0.1010.101
316141AB2-099 E
50/50
0.2650.265
900672V4-068 E
50/50
0.2370.237
917342Z2-044 E
50/50
0.3980.398
922923AB1-081 E OP
50/50
2.412.41
923263AB1-132 E OP
50/50
3.8463.846
923573AB1-173 E OP
Adder
1.52235294117647071.294
940491AE2-034 C
50/50
3.6663.666
940492AE2-034 E
50/50
9.7989.798
957861AF2-080 C
50/50
7.6477.647
957862AF2-080 E
50/50
3.393.39
916042Z1-036 E
50/50
112.394112.394
3151411GASTONB
50/50
1.9211.921
3152921DOMTR78
50/50
3.1343.134
3156116Z1-036WIND
50/50
2.5862.586
917512Z2-088 E OP1
50/50
4.4954.495
926071AC1-086 C
50/50
13.21613.216
926072AC1-086 E
50/50
6.0156.015
927021AC1-189 C
50/50
8.428.42
927022AC1-189 E
50/50
4.1944.194
933981AD1-022 C
50/50
20.06420.064
933982AD1-022 E
50/50
10.92310.923
962572AG1-106 E
50/50
0.7480.748
962571AG1-106 C
50/50
1.7091.709
3145946PLYMOUTH TP
50/50
0.8710.871
316005AA1-067 C
50/50
0.3190.319
316011AB1-132 C OP
50/50
1.4671.467
316049AB1-081 C OP
50/50
0.9190.919
316210AC1-098 C
50/50
0.7460.746
316212AC1-099 C
50/50
0.250.25
316263AC1-034 C
50/50
4.2924.292
316274AC1-208 C
50/50
6.2616.261
316317KELFORD C
50/50
0.3720.372
316318V4-068 C
50/50
0.0530.053
316319Z2-044 C
50/50
0.140.14
917332KELFORD E
50/50
1.7081.708
925595AC1-034 E
50/50
3.2383.238
926206AC1-098 E
50/50
2.892.89
926214AC1-099 E
50/50
0.9550.955
3156021HOLLOMANSOL
50/50
2.5722.572
918512AA1-065 E OP
50/50
7.7297.729
316327AA2-057 C
50/50
0.8910.891
919710AA2-057 E
50/50
2.7162.716
315614AA2-178 C
50/50
4.9814.981
920692AA2-178 E
50/50
13.06413.064
923994AB2-040_E
Adder
2.8552941176470592.427
316359AB2-059 C OP
50/50
1.0831.083
924152AB2-059 E OP
50/50
3.4143.414
316174AB2-169_C
50/50
2.0152.015
925122AB2-169 E
50/50
11.06611.066
316088AB2-174 E
Adder
2.8564705882352942.428
3137643SOCKMAN
Adder
0.368235294117647050.313
932631AC2-084 C
50/50
0.7950.795
932632AC2-084 E
50/50
2.5552.555
934321AD1-056 C
50/50
4.0344.034
934322AD1-056 E
50/50
2.1882.188
934331AD1-057 C
50/50
2.252.25
934332AD1-057 E
50/50
1.1721.172
934501AD1-074 C
50/50
87.7387.73
934502AD1-074 E
50/50
44.65944.659
934511AD1-075 C
50/50
21.93221.932
934512AD1-075 E
50/50
11.16511.165
938531AE1-072 C
Adder
-9.852941176470589-8.375
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7331.733
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.928.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.8825.882
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.38626.386
G-007PJM->LTFIMP_G-007
CMTX_NF
0.4420.442
NYPJM->LTFIMP_NY
CLTF
0.1970.197
LGEELTFEXP_LGEE->PJM
CLTF
0.3360.336
WECLTFEXP_WEC->PJM
CLTF
0.1810.181
CPLELTFEXP_CPLE->PJM
CLTF
3.6343.634
TVALTFEXP_TVA->PJM
CLTF
1.5541.554
MECLTFEXP_MEC->PJM
CLTF
1.0671.067
LAGNLTFEXP_LAGN->PJM
CLTF
1.9941.994
SIGELTFEXP_SIGE->PJM
CLTF
0.0660.066
O66PJM->LTFIMP_O-066
CMTX_NF
2.8092.809

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.12 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3352.99
MW Contribution:4.49
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3492.91
MW Contribution:4.38
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
1.05882352941176470.9
961672AG1-007 E
Adder
0.60.51
961791AG1-021 C
Adder
1.63058823529411771.386
961792AG1-021 E
Adder
1.38941176470588231.181
961941AG1-037 C
Adder
0.5717647058823530.486
961942AG1-037 E
Adder
0.381176470588235340.324
963041AG1-153 C
50/50
8.3218.321
963042AG1-153 E
50/50
12.48112.481
964791AG1-342 C
Adder
3.96470588235294133.37
964792AG1-342 E
Adder
2.6435294117647062.247
966621AG1-532 C
50/50
1.6281.628
966622AG1-532 E
50/50
1.0851.085
3138533PONTONDP
Adder
0.60352941176470590.513
3145413WATKINS
Adder
0.7717647058823530.656
3145723EMPORIA
50/50
0.50.5
3147133PAMPLIN
Adder
0.89882352941176480.764
3151311EDGECMA
Adder
17.50705882352941214.881
3151531CLOVER1
50/50
15.90515.905
3151541CLOVER2
50/50
15.75715.757
918492AA1-063AE OP
Adder
4.65058823529411753.953
918532AA1-067 E
Adder
0.80588235294117660.685
919692AA2-053 E OP
Adder
4.8352941176470594.11
920042AA2-088 E OP
Adder
11.94941176470588210.157
925785AC1-054 E
Adder
3.94000000000000043.349
926274AC1-105 E
Adder
2.9882352941176472.54
927146AC1-208 E
Adder
4.5541176470588243.871
934521AD1-076 C
Adder
13.81176470588235411.74
934522AD1-076 E
Adder
7.045.984
943172AE2-346 E
Adder
0.68588235294117650.583
943902AF1-058 E
Adder
1.42941176470588241.215
944011AF1-069 C
50/50
19.88619.886
944012AF1-069 E
50/50
7.7257.725
959311AF2-222 C
Adder
17.79058823529411615.122
959312AF2-222 E
Adder
11.9210.132
960081AF2-299 C
50/50
2.1712.171
960082AF2-299 E
50/50
1.4471.447
316141AB2-099 E
Adder
0.28588235294117650.243
900672V4-068 E
Adder
0.402352941176470640.342
917342Z2-044 E
Adder
0.6764705882352940.575
922923AB1-081 E OP
Adder
4.20470588235294153.574
923263AB1-132 E OP
Adder
7.0270588235294125.973
923573AB1-173 E OP
Adder
3.78941176470588253.221
924162AB2-060 E OP
Adder
4.8364705882352944.111
924302AB2-077 E O1
Adder
1.52117647058823541.293
924312AB2-078 E O1
Adder
1.52117647058823541.293
924322AB2-079 E O1
Adder
1.52117647058823541.293
925612AC1-036 E
Adder
0.93294117647058830.793
940492AE2-034 E
Adder
3.4764705882352942.955
941031AE2-094 C
50/50
60.86460.864
941032AE2-094 E
50/50
27.25927.259
946281AF1-292 C
50/50
1.7971.797
946282AF1-292 E
50/50
1.1981.198
946301AF1-294 C
Adder
3.3517647058823532.849
946302AF1-294 E
Adder
2.83882352941176472.413
957481AF2-042 C
50/50
69.9469.94
957482AF2-042 E
50/50
46.62746.627
957861AF2-080 C
Adder
8.6200000000000017.327
957862AF2-080 E
Adder
3.8211764705882363.248
958211AF2-115 C
Adder
2.03764705882352941.732
958212AF2-115 E
Adder
1.73647058823529421.476
3145393UNCAMP
Adder
6.7635294117647065.749
916042Z1-036 E
Adder
32.1705882352941227.345
938771AE1-103 C
Adder
3.24823529411764732.761
938772AE1-103 E
Adder
4.4858823529411773.813
313526AB2-022 C
50/50
0.4240.424
3143316POE
Adder
1.30823529411764721.112
3145256KINGFORK
Adder
1.06588235294117650.906
3145506HICKORY
50/50
2.4672.467
926662AC1-147 E
Adder
1.46588235294117641.246
926755AC1-161 E
50/50
14.89414.894
935112AD1-144 E
Adder
0.98941176470588230.841
942341AE2-247 C
Adder
1.54941176470588231.317
942342AE2-247 E
Adder
2.141.819
943461AF1-017 C
Adder
1.40235294117647061.192
943462AF1-017 E
Adder
2.2870588235294121.944
943612AF1-032 E
Adder
1.02823529411764710.874
3151021BRUNSWICKG1
50/50
12.28212.282
3151031BRUNSWICKG2
50/50
12.28212.282
3151041BRUNSWICKG3
50/50
12.28212.282
3151051BRUNSWICKS1
50/50
25.51625.516
3151081ELIZAR1
50/50
3.5563.556
3151091ELIZAR2
50/50
3.4953.495
3151101ELIZAR3
50/50
3.6013.601
3152411Z1-086 GT1
50/50
15.81615.816
3152421Z1-086 GT2
50/50
15.81115.811
3152431Z1-086 GT3
50/50
15.81115.811
3152441Z1-086 ST
50/50
27.53327.533
913392Y1-086 E
50/50
2.4762.476
916192Z1-068 E
50/50
2.1052.105
923832AB2-022 E
50/50
1.3981.398
923852AB2-025 E
50/50
1.3891.389
939312AE1-162 E
Adder
1.37058823529411771.165
957492AF2-043 E
Adder
1.58117647058823541.344
901082W1-029 E
Adder
35.7705882352941230.405
917122Z2-027 E
50/50
1.5121.512
925522AC1-027 E
50/50
1.3621.362
957871AF2-081 C
50/50
11.29311.293
957872AF2-081 E
50/50
4.844.84
958161AF2-110 C
Adder
1.49647058823529421.272
958162AF2-110 E
Adder
2.38000000000000032.023
3147223TWITTYS
Adder
1.03411764705882360.879
917512Z2-088 E OP1
Adder
5.5247058823529414.696
926071AC1-086 C
Adder
24.1447058823529420.523
926072AC1-086 E
Adder
10.9894117647058819.341
927021AC1-189 C
Adder
9.4905882352941178.067
927022AC1-189 E
Adder
4.7282352941176474.019
936261AD2-033 C
Adder
13.51176470588235311.485
936262AD2-033 E
Adder
9.0082352941176477.657
933291AC2-141 C
50/50
34.8934.89
933292AC2-141 E
50/50
14.89414.894
934621AD1-088 C
50/50
11.53711.537
934622AD1-088 E
50/50
5.5555.555
939411AE1-173 C
50/50
128.665128.665
939412AE1-173 E
50/50
85.77785.777
916191Z1-068 C
50/50
0.0490.049
933981AD1-022 C
Adder
9.8917647058823528.408
933982AD1-022 E
Adder
5.3847058823529414.577
962572AG1-106 E
Adder
1.36588235294117651.161
962571AG1-106 C
Adder
3.1235294117647062.655
3145946PLYMOUTH TP
Adder
0.364705882352941160.31
3146326AYDLETT TAP
50/50
1.5311.531
316023AB2-100 C2
50/50
1.1231.123
316185AD1-033 C
50/50
1.391.39
316263AC1-034 C
Adder
7.4894117647058826.366
316274AC1-208 C
Adder
10.255294117647068.717
316294AC1-161 C
50/50
5.7015.701
316315AB2-025 C
50/50
0.4880.488
316316AC1-027 C
50/50
0.3530.353
316320Y1-086 C
50/50
0.2480.248
316321Z2-027 C
50/50
0.410.41
316365AB2-100 C1
50/50
1.1231.123
917332KELFORD E
Adder
1.8635294117647061.584
924516AB2-100 E1
50/50
3.3843.384
924517AB2-100 E2
50/50
3.3843.384
925595AC1-034 E
Adder
5.65058823529411754.803
926206AC1-098 E
Adder
4.1470588235294123.525
926214AC1-099 E
Adder
1.36941176470588231.164
927255AC1-221 E
Adder
4.1411764705882363.52
927264AC1-222 E
Adder
4.3282352941176473.679
932763AC2-100 E
Adder
2.80941176470588252.388
934065AD1-033 E
50/50
5.6715.671
937226AE2-253 E
50/50
6.6066.606
918512AA1-065 E OP
Adder
6.2505882352941175.313
316017AA1-139 ULT1
50/50
1.2231.223
316018AA1-139 ULT2
50/50
1.2231.223
919153AA1-139 E2
50/50
4.6184.618
919152AA1-139 E1
50/50
4.6184.618
919710AA2-057 E
Adder
4.49411764705882363.82
920692AA2-178 E
Adder
4.6352941176470593.94
923994AB2-040_E
Adder
7.1047058823529416.039
924022AB2-043 E O1
Adder
5.9035294117647065.018
924152AB2-059 E OP
Adder
5.9564705882352945.063
316084AB2-161 E
Adder
5.26941176470588254.479
925122AB2-169 E
Adder
6.4858823529411775.513
316087AB2-174 C
50/50
1.3621.362
316088AB2-174 E
50/50
7.5427.542
316375AC2-012 C
50/50
1.4951.495
932046AC2-012 E
50/50
14.50114.501
316311AC2-079 C
Adder
5.9964705882352955.097
932596AC2-079 E
Adder
9.7835294117647078.316
934576AD1-082 E
Adder
4.1988235294117653.569
316349AD2-085 C
Adder
3.5752941176470593.039
936666AD2-085 E
Adder
5.8329411764705884.958
316388AE2-253 GEN
50/50
2.2212.221
961611AG1-000B C
Adder
5.824.947
941591AE2-156 C
50/50
19.83519.835
944581AF1-123 C
50/50
51.37451.374
944582AF1-123 E
50/50
117.641117.641
944591AF1-124 C
50/50
51.55751.557
944592AF1-124 E
50/50
118.067118.067
944601AF1-125 C
50/50
50.58350.583
944602AF1-125 E
50/50
115.795115.795
962561AG1-105 C
Adder
9.9705882352941188.475
962562AG1-105 E
Adder
6.6470588235294125.65
964241AG1-285 C
50/50
14.87614.876
964242AG1-285 E
50/50
9.9189.918
3137643SOCKMAN
Adder
0.81882352941176460.696
932632AC2-084 E
Adder
3.66588235294117663.116
934321AD1-056 C
Adder
7.126.052
934322AD1-056 E
Adder
3.86117647058823543.282
934331AD1-057 C
Adder
3.9717647058823533.376
934332AD1-057 E
Adder
2.0682352941176471.758
934501AD1-074 C
Adder
38.0305882352941232.326
934502AD1-074 E
Adder
19.3616.456
934511AD1-075 C
Adder
9.507058823529418.081
934512AD1-075 E
Adder
4.844.114
934611AD1-087 C
50/50
1.5661.566
934612AD1-087 E
50/50
4.5174.517
935171AD1-152 C
50/50
1.6091.609
935172AD1-152 E
50/50
6.6176.617
937481AD2-202 C
50/50
0.4540.454
937482AD2-202 E
50/50
1.3221.322
938531AE1-072 C
50/50
19.84719.847
938532AE1-072 E
50/50
10.34610.346
939191AE1-149 C
Adder
9.5941176470588238.155
939192AE1-149 E
Adder
6.3964705882352955.437
940481AE2-033 C
50/50
19.30519.305
940482AE2-033 E
50/50
13.01513.015
940541AE2-040 C
50/50
3.4343.434
940641AE2-051 C
50/50
26.11526.115
940642AE2-051 E
50/50
17.4117.41
941101AE2-104 C
Adder
3.66705882352941173.117
941102AE2-104 E
Adder
5.8305882352941184.956
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.3016.301
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.47229.472
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.8122.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
107.493107.493
G-007PJM->LTFIMP_G-007
CMTX_NF
3.5513.551
NYPJM->LTFIMP_NY
CLTF
1.6611.661
LGEELTFEXP_LGEE->PJM
CLTF
1.1651.165
WECLTFEXP_WEC->PJM
CLTF
0.6140.614
CPLELTFEXP_CPLE->PJM
CLTF
13.22113.221
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
MECLTFEXP_MEC->PJM
CLTF
3.8563.856
LAGNLTFEXP_LAGN->PJM
CLTF
8.048.04
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
O66PJM->LTFIMP_O-066
CMTX_NF
22.61622.616

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:136.21 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3326.4
MW Contribution:4.98
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:145.97 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3564.84
MW Contribution:5.01
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.71294117647058820.606
961942AG1-037 E
Adder
0.475294117647058870.404
963041AG1-153 C
Adder
7.1717647058823536.096
963042AG1-153 E
Adder
10.757647058823539.144
966621AG1-532 C
Adder
1.72705882352941181.468
966622AG1-532 E
Adder
1.1517647058823530.979
3145413WATKINS
Adder
1.03764705882352940.882
3145723EMPORIA
Adder
0.53411764705882360.454
918492AA1-063AE OP
Adder
5.464705882352944.645
918532AA1-067 E
Adder
0.94588235294117650.804
919692AA2-053 E OP
Adder
5.50588235294117644.68
920042AA2-088 E OP
Adder
15.25058823529411712.963
934521AD1-076 C
Adder
18.52705882352941215.748
934522AD1-076 E
Adder
9.4435294117647068.027
943172AE2-346 E
Adder
0.85647058823529410.728
944011AF1-069 C
Adder
17.03647058823529314.481
944012AF1-069 E
Adder
6.6188235294117655.626
960081AF2-299 C
Adder
2.3023529411764711.957
960082AF2-299 E
Adder
1.53529411764705871.305
316141AB2-099 E
Adder
0.35647058823529410.303
900672V4-068 E
Adder
0.50705882352941180.431
923263AB1-132 E OP
Adder
7.79647058823529456.627
923573AB1-173 E OP
Adder
4.1152941176470593.498
940492AE2-034 E
Adder
4.8058823529411764.085
941031AE2-094 C
Adder
52.14117647058823544.32
941032AE2-094 E
Adder
23.3529411764705919.85
946281AF1-292 C
Adder
1.90588235294117661.62
946282AF1-292 E
Adder
1.27058823529411781.08
3145393UNCAMP
Adder
9.2964705882352947.902
916042Z1-036 E
50/50
46.21946.219
938771AE1-103 C
Adder
4.5305882352941173.851
938772AE1-103 E
Adder
6.257647058823535.319
313526AB2-022 C
50/50
0.640.64
3144216WINCHST
50/50
0.2310.231
3145256KINGFORK
50/50
1.7041.704
3145506HICKORY
50/50
3.8083.808
3150601CHESTF5
Adder
72.936470588235361.996
3150921YORKTN3
50/50
212.818212.818
925865AC1-065 E
Adder
24.48470588235294420.812
926662AC1-147 E
50/50
2.2972.297
926755AC1-161 E
50/50
24.37824.378
927226AC1-216 E
Adder
10.5317647058823528.952
934392AD1-063 E
Adder
1.61529411764705881.373
935112AD1-144 E
50/50
1.5821.582
936591AD2-074 C
Adder
7.8788235294117656.697
936592AD2-074 E
Adder
12.85529411764705910.927
942341AE2-247 C
Adder
2.2741176470588241.933
942342AE2-247 E
Adder
3.142.669
943461AF1-017 C
Adder
2.05764705882352941.749
943462AF1-017 E
Adder
3.35647058823529452.853
943612AF1-032 E
50/50
1.5651.565
943741AF1-042 C
Adder
4.122352941176473.504
943742AF1-042 E
Adder
6.7258823529411765.717
961951AG1-038 C
Adder
4.5564705882352943.873
961952AG1-038 E
Adder
6.2929411764705885.349
966661AG1-536 C
Adder
7.4564705882352956.338
966662AG1-536 E
Adder
10.0188235294117658.516
3150981CHESPKA
50/50
0.7560.756
3150991CHESPKB
50/50
1.2531.253
3151081ELIZAR1
50/50
5.5655.565
3151091ELIZAR2
50/50
5.4685.468
3151101ELIZAR3
50/50
5.6365.636
3151161SURRY 1
50/50
37.92137.921
3152331SURRY 2
50/50
50.93450.934
3156056W1-029WIND
50/50
1.2961.296
3156116Z1-036WIND
50/50
1.0631.063
316076AC2-137 E
Adder
1.64117647058823551.395
316078AC2-138 E
Adder
1.26470588235294111.075
316157AD2-030 E
Adder
1.7917647058823531.523
913392Y1-086 E
50/50
3.7343.734
916192Z1-068 E
50/50
3.2743.274
923832AB2-022 E
50/50
2.1082.108
923842AB2-024 E
Adder
2.7035294117647062.298
923852AB2-025 E
Adder
1.42470588235294131.211
939312AE1-162 E
50/50
2.3092.309
957492AF2-043 E
50/50
2.4072.407
957601AF2-054 C
Adder
3.1929411764705882.714
957602AF2-054 E
Adder
2.12823529411764721.809
962861AG1-135 C
Adder
8.4564705882352957.188
962862AG1-135 E
Adder
5.63764705882352954.792
962962AG1-145 E
50/50
2.4882.488
963611AG1-210 C
Adder
0.90352941176470590.768
963612AG1-210 E
Adder
1.35529411764705881.152
964211AG1-282 C
Adder
2.76588235294117672.351
964212AG1-282 E
Adder
1.84352941176470591.567
901082W1-029 E
50/50
53.16253.162
917122Z2-027 E
50/50
2.2672.267
925332AB2-190 E
Adder
10.335294117647068.785
925522AC1-027 E
50/50
2.1192.119
957831AF2-077 C
50/50
0.5460.546
957832AF2-077 E
50/50
2.3562.356
957871AF2-081 C
50/50
17.30217.302
957872AF2-081 E
50/50
7.4157.415
958161AF2-110 C
50/50
2.2342.234
958162AF2-110 E
50/50
3.5543.554
3138116ELKO L286
Adder
1.71058823529411771.454
3141813NORNECK
Adder
1.20352941176470571.023
926071AC1-086 C
Adder
26.78823529411764822.77
926072AC1-086 E
Adder
12.19176470588235310.363
933291AC2-141 C
50/50
57.10857.108
933292AC2-141 E
50/50
24.37824.378
939411AE1-173 C
50/50
137.269137.269
939412AE1-173 E
50/50
91.51291.512
934012AD1-025 E
Adder
13.63529411764705811.59
916191Z1-068 C
50/50
0.0760.076
933981AD1-022 C
Adder
13.0952941176470611.131
933982AD1-022 E
Adder
7.1294117647058826.06
962572AG1-106 E
Adder
1.5164705882352941.289
962571AG1-106 C
Adder
3.4647058823529412.945
3130536PAPERMILL
Adder
9.9929411764705888.494
3145946PLYMOUTH TP
Adder
0.491764705882352940.418
3146326AYDLETT TAP
50/50
2.3362.336
316036AC1-147 C
50/50
0.6390.639
316072AD1-144 C
50/50
0.4730.473
316159AE1-175 C
50/50
0.6760.676
316160AE1-175 E
50/50
2.0532.053
316169AC1-164 GEN
50/50
61.5761.57
316185AD1-033 C
50/50
2.1522.152
316236AE1-162 C
50/50
0.5660.566
316246AF1-032 C
50/50
0.4820.482
316294AC1-161 C
50/50
9.3329.332
316305AF2-043 C
50/50
0.590.59
316316AC1-027 C
50/50
0.550.55
316320Y1-086 C
50/50
0.3740.374
316321Z2-027 C
50/50
0.6140.614
316382AG1-145 C
50/50
0.610.61
917332KELFORD E
Adder
2.25294117647058821.915
924516AB2-100 E1
Adder
3.61411764705882373.072
924517AB2-100 E2
Adder
3.61411764705882373.072
926206AC1-098 E
Adder
4.72941176470588154.02
926214AC1-099 E
Adder
1.56235294117647071.328
926785AC1-164_E
50/50
27.66227.662
934065AD1-033 E
50/50
8.788.78
937226AE2-253 E
50/50
10.1510.15
939612AE1-191 E
Adder
8.4670588235294127.197
939246AE1-155 E
Adder
12.06941176470588310.259
918512AA1-065 E OP
Adder
7.9635294117647066.769
316017AA1-139 ULT1
50/50
1.8731.873
316018AA1-139 ULT2
50/50
1.8731.873
919153AA1-139 E2
50/50
7.0757.075
919152AA1-139 E1
50/50
7.0757.075
920692AA2-178 E
Adder
6.4070588235294125.446
923994AB2-040_E
Adder
7.7152941176470586.558
924814AB2-134 E
Adder
17.2517647058823514.664
316084AB2-161 E
Adder
7.497647058823536.373
925122AB2-169 E
Adder
8.1847058823529426.957
316088AB2-174 E
Adder
8.1305882352941186.911
316375AC2-012 C
50/50
2.3432.343
932046AC2-012 E
50/50
22.72422.724
316311AC2-079 C
Adder
8.827.497
932596AC2-079 E
Adder
14.39058823529411812.232
934146AD1-041 E
Adder
5.2917647058823534.498
934576AD1-082 E
Adder
5.9741176470588245.078
316349AD2-085 C
Adder
5.2458823529411764.459
936666AD2-085 E
Adder
8.5588235294117647.275
316388AE2-253 GEN
50/50
3.4133.413
961611AG1-000B C
Adder
23.74470588235294220.183
941591AE2-156 C
50/50
31.07431.074
944581AF1-123 C
50/50
79.48679.486
944582AF1-123 E
50/50
182.015182.015
944591AF1-124 C
50/50
79.76979.769
944592AF1-124 E
50/50
182.674182.674
944601AF1-125 C
50/50
78.26278.262
944602AF1-125 E
50/50
179.158179.158
944631AF1-128 C
Adder
26.26705882352941422.327
958261AF2-120 C
Adder
8.6682352941176477.368
958262AF2-120 E
Adder
5.7788235294117654.912
3137643SOCKMAN
Adder
0.90352941176470590.768
932632AC2-084 E
Adder
4.183.553
934501AD1-074 C
Adder
51.01411764705882543.362
934502AD1-074 E
Adder
25.96941176470588522.074
934511AD1-075 C
Adder
12.75411764705882310.841
934512AD1-075 E
Adder
6.4917647058823525.518
935161AD1-151 C
Adder
21.28588235294117618.093
935162AD1-151 E
Adder
14.19058823529411712.062
938531AE1-072 C
50/50
30.31830.318
938532AE1-072 E
50/50
15.80515.805
939191AE1-149 C
Adder
13.30705882352941111.311
939192AE1-149 E
Adder
8.8705882352941187.54
939602AE1-190 E
Adder
2.1164705882352941.799
940481AE2-033 C
Adder
19.89882352941176816.914
940482AE2-033 E
Adder
13.4152941176470611.403
940541AE2-040 C
Adder
3.5223529411764712.994
940551AE2-041 C
Adder
10.7682352941176489.153
940641AE2-051 C
50/50
24.9624.96
940642AE2-051 E
50/50
16.6416.64
941101AE2-104 C
50/50
5.4755.475
941102AE2-104 E
50/50
8.7058.705
943471AF1-018 C
Adder
10.7682352941176489.153
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.8765.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.55415.554
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.85316.853
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69696.696
G-007PJM->LTFIMP_G-007
CMTX_NF
3.3653.365
NYPJM->LTFIMP_NY
CLTF
1.6271.627
LGEELTFEXP_LGEE->PJM
CLTF
0.6520.652
WECLTFEXP_WEC->PJM
CLTF
0.3380.338
CPLELTFEXP_CPLE->PJM
CLTF
12.33712.337
TVALTFEXP_TVA->PJM
CLTF
4.9324.932
MECLTFEXP_MEC->PJM
CLTF
2.4842.484
LAGNLTFEXP_LAGN->PJM
CLTF
6.3726.372
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143
O66PJM->LTFIMP_O-066
CMTX_NF
21.46821.468

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:109.93 %
Rating:2858.0 MVA
Rating Type:B
MVA to Mitigate:3141.72
MW Contribution:3.27
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:119.94 %
Rating:2858.0 MVA
Rating Type:B
MVA to Mitigate:3427.77
MW Contribution:No Reportable Contribution
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.458823529411764740.39
961942AG1-037 E
Adder
0.30588235294117650.26
966621AG1-532 C
Adder
1.14705882352941170.975
966622AG1-532 E
Adder
0.76470588235294120.65
3145413WATKINS
Adder
0.6682352941176470.568
3145723EMPORIA
Adder
0.354117647058823540.301
918492AA1-063AE OP
Adder
3.55176470588235343.019
918532AA1-067 E
Adder
0.60823529411764710.517
919692AA2-053 E OP
Adder
3.58235294117647073.045
920042AA2-088 E OP
Adder
9.8517647058823558.374
927146AC1-208 E
Adder
3.30941176470588252.813
934521AD1-076 C
Adder
11.7235294117647079.965
934522AD1-076 E
Adder
5.9752941176470595.079
943172AE2-346 E
Adder
0.55058823529411770.468
960081AF2-299 C
Adder
1.52941176470588251.3
960082AF2-299 E
Adder
1.020.867
316141AB2-099 E
Adder
0.229411764705882370.195
900672V4-068 E
Adder
0.32705882352941180.278
923263AB1-132 E OP
Adder
5.1258823529411774.357
923573AB1-173 E OP
Adder
2.7117647058823532.305
940492AE2-034 E
Adder
3.02588235294117652.572
946281AF1-292 C
Adder
1.26588235294117671.076
946282AF1-292 E
Adder
0.84470588235294120.718
3145393UNCAMP
Adder
5.9858823529411775.088
916042Z1-036 E
Adder
28.93529411764705724.595
938771AE1-103 C
Adder
2.9152941176470592.478
938772AE1-103 E
Adder
4.0258823529411773.422
3142296MT RD221
50/50
0.1530.153
3142366NRTHEST
50/50
0.2230.223
3143316POE
Adder
1.3152941176470591.118
3145256KINGFORK
Adder
1.10117647058823540.936
3145506HICKORY
Adder
2.33764705882352961.987
3150601CHESTF5
50/50
76.90776.907
3150611CHESTG7
50/50
4.6934.693
3150621CHESTS7
50/50
2.1542.154
3150631CHESTG8
50/50
4.6184.618
3150641CHESTS8
50/50
2.3772.377
3150651CHESTF6
Adder
20.2152941176470617.183
3150671DARBY 1
50/50
3.1283.128
3150681DARBY 2
50/50
3.1313.131
3150691DARBY 3
50/50
3.1423.142
3150701DARBY 4
50/50
3.1463.146
3150731STONECA
Adder
7.8588235294117646.68
3150831SPRUNCA
Adder
9.3611764705882357.957
3150841SPRUNCB
Adder
9.3611764705882357.957
3150921YORKTN3
Adder
145.0894117647059123.326
925865AC1-065 E
Adder
20.03529411764706217.03
926412AC1-112 E
50/50
1.481.48
926472AC1-118 E
Adder
0.96117647058823530.817
926662AC1-147 E
Adder
1.43294117647058821.218
926755AC1-161 E
Adder
14.40352941176470712.243
927226AC1-216 E
Adder
8.7458823529411777.434
934392AD1-063 E
Adder
1.30705882352941181.111
934782AD1-105 E
Adder
4.7164705882352944.009
935112AD1-144 E
Adder
1.02235294117647070.869
936582AD2-073 E
Adder
1.06470588235294120.905
936591AD2-074 C
Adder
6.2517647058823535.314
936592AD2-074 E
Adder
10.2011764705882358.671
942341AE2-247 C
Adder
1.5552941176470591.322
942342AE2-247 E
Adder
2.14823529411764721.826
943461AF1-017 C
Adder
1.40705882352941171.196
943462AF1-017 E
Adder
2.2964705882352941.952
943612AF1-032 E
Adder
0.980.833
943741AF1-042 C
Adder
3.2717647058823532.781
943742AF1-042 E
Adder
5.337647058823534.537
961951AG1-038 C
Adder
3.61529411764705883.073
961952AG1-038 E
Adder
4.9929411764705884.244
966661AG1-536 C
Adder
5.9235294117647065.035
966662AG1-536 E
Adder
7.966.766
966871AG1-558 C
Adder
2.89764705882352972.463
966872AG1-558 E
Adder
1.46000000000000021.241
3152161CUNINGA
50/50
7.7587.758
3152171CUNINGB
50/50
7.7587.758
3152181CUNINGC
50/50
7.7587.758
3152191CUNINGD
50/50
17.35517.355
3152331SURRY 2
50/50
30.62730.627
316075AC2-137 C
50/50
0.4910.491
316076AC2-137 E
50/50
1.7271.727
316078AC2-138 E
Adder
1.00588235294117640.855
316157AD2-030 E
Adder
1.41764705882352951.205
913392Y1-086 E
Adder
2.3117647058823531.965
916192Z1-068 E
Adder
2.02588235294117651.722
923832AB2-022 E
Adder
1.30470588235294121.109
923842AB2-024 E
50/50
2.2162.216
923852AB2-025 E
Adder
0.97176470588235290.826
930122AB1-027 E
50/50
1.8191.819
938552AE1-074 E
Adder
1.06235294117647070.903
939312AE1-162 E
Adder
1.58823529411764721.35
946262AF1-291 E
Adder
1.5435294117647061.312
957492AF2-043 E
Adder
1.50823529411764711.282
957601AF2-054 C
Adder
2.52588235294117652.147
957602AF2-054 E
Adder
1.6835294117647061.431
962861AG1-135 C
Adder
6.71647058823529355.709
962862AG1-135 E
Adder
4.4776470588235293.806
962962AG1-145 E
50/50
1.8271.827
963611AG1-210 C
Adder
0.71882352941176480.611
963612AG1-210 E
Adder
1.07764705882352940.916
964211AG1-282 C
Adder
2.2223529411764711.889
964212AG1-282 E
Adder
1.48117647058823531.259
901082W1-029 E
Adder
33.1517647058823528.179
917122Z2-027 E
Adder
1.40588235294117661.195
925332AB2-190 E
Adder
9.162352941176477.788
925522AC1-027 E
Adder
1.31294117647058851.116
942001AE2-212 C
Adder
2.2223529411764711.889
942002AE2-212 E
Adder
1.48117647058823531.259
957832AF2-077 E
Adder
1.71764705882352931.46
957871AF2-081 C
Adder
10.6494117647058819.052
957872AF2-081 E
Adder
4.5647058823529413.88
958161AF2-110 C
Adder
1.43411764705882371.219
958162AF2-110 E
Adder
2.281.938
3138116ELKO L286
50/50
1.8011.801
3141813NORNECK
Adder
0.95647058823529410.813
926071AC1-086 C
Adder
17.6129411764705914.971
926072AC1-086 E
Adder
8.0164705882352956.814
933291AC2-141 C
Adder
33.74117647058823628.68
933292AC2-141 E
Adder
14.40352941176470712.243
939411AE1-173 C
Adder
76.4011764705882464.941
939412AE1-173 E
Adder
50.9341176470588243.294
934012AD1-025 E
Adder
11.3223529411764729.624
927041AC1-191 C
Adder
11.635294117647069.89
927042AC1-191 E
Adder
5.7952941176470594.926
933981AD1-022 C
Adder
8.3070588235294117.061
933982AD1-022 E
Adder
4.5223529411764713.844
962572AG1-106 E
Adder
0.99647058823529410.847
962571AG1-106 C
Adder
2.27764705882352961.936
3130536PAPERMILL
50/50
8.1698.169
3145946PLYMOUTH TP
Adder
0.310588235294117660.264
3146326AYDLETT TAP
Adder
1.441.224
316004AC1-112 C
50/50
0.4320.432
316159AE1-175 C
50/50
0.4960.496
316160AE1-175 E
50/50
1.5071.507
316169AC1-164 GEN
50/50
53.95453.954
316233AE1-074 C
Adder
2.10941176470588231.793
316240AF1-291 C
Adder
2.3141176470588241.967
316274AC1-208 C
Adder
7.4541176470588246.336
316312AB1-027 C
50/50
0.6940.694
316314AB2-024 C
50/50
0.3620.362
316382AG1-145 C
50/50
0.4480.448
917332KELFORD E
Adder
1.45058823529411771.233
924516AB2-100 E1
Adder
2.41411764705882352.052
924517AB2-100 E2
Adder
2.41411764705882352.052
926206AC1-098 E
Adder
3.06470588235294142.605
926214AC1-099 E
Adder
1.01294117647058820.861
926785AC1-164_E
50/50
24.2424.24
934065AD1-033 E
Adder
5.3917647058823544.583
937226AE2-253 E
Adder
6.2411764705882355.305
939612AE1-191 E
Adder
6.8270588235294125.803
939246AE1-155 E
Adder
9.5882352941176498.15
918512AA1-065 E OP
Adder
5.0905882352941184.327
919153AA1-139 E2
Adder
4.3552941176470593.702
919152AA1-139 E1
Adder
4.3552941176470593.702
920692AA2-178 E
Adder
4.0352941176470593.43
923994AB2-040_E
Adder
5.0835294117647054.321
924814AB2-134 E
Adder
14.32588235294117712.177
316084AB2-161 E
Adder
5.71764705882352954.86
925122AB2-169 E
Adder
5.2152941176470584.433
316088AB2-174 E
Adder
5.3717647058823534.566
932046AC2-012 E
Adder
14.1776470588235312.051
316311AC2-079 C
Adder
5.9847058823529415.087
932596AC2-079 E
Adder
9.7647058823529428.3
934146AD1-041 E
Adder
4.2670588235294113.627
934576AD1-082 E
Adder
4.5564705882352943.873
316349AD2-085 C
Adder
3.58941176470588273.051
936666AD2-085 E
Adder
5.8564705882352944.978
961611AG1-000B C
Adder
17.96705882352941315.272
941591AE2-156 C
Adder
19.37058823529411816.465
944581AF1-123 C
Adder
48.7494117647058841.437
944582AF1-123 E
Adder
111.6294117647058994.885
944591AF1-124 C
Adder
48.9223529411764841.584
944592AF1-124 E
Adder
112.0341176470588295.229
944601AF1-125 C
Adder
47.9976470588235340.798
944602AF1-125 E
Adder
109.8776470588235393.396
944631AF1-128 C
Adder
48.1223529411764740.904
958261AF2-120 C
Adder
6.8858823529411765.853
958262AF2-120 E
Adder
4.5905882352941183.902
3137643SOCKMAN
Adder
0.5917647058823530.503
932632AC2-084 E
Adder
2.70941176470588242.303
934501AD1-074 C
Adder
32.2827.438
934502AD1-074 E
Adder
16.43176470588235513.967
934511AD1-075 C
Adder
8.0694117647058836.859
934512AD1-075 E
Adder
4.1082352941176473.492
935161AD1-151 C
Adder
18.2952941176470615.551
935162AD1-151 E
Adder
12.19647058823529510.367
938531AE1-072 C
Adder
18.68117647058823415.879
938532AE1-072 E
Adder
9.7388235294117668.278
939191AE1-149 C
Adder
11.035294117647069.38
939192AE1-149 E
Adder
7.3564705882352946.253
939602AE1-190 E
Adder
1.7070588235294121.451
940431AE2-027 C
Adder
13.85176470588235311.774
940432AE2-027 E
Adder
9.2341176470588247.849
940481AE2-033 C
Adder
13.53647058823529511.506
940482AE2-033 E
Adder
9.1258823529411767.757
940541AE2-040 C
Adder
2.40235294117647062.042
940551AE2-041 C
Adder
8.7105882352941187.404
940641AE2-051 C
Adder
13.3423529411764711.341
940642AE2-051 E
Adder
8.8941176470588247.56
941101AE2-104 C
Adder
3.51411764705882362.987
941102AE2-104 E
Adder
5.58588235294117654.748
943471AF1-018 C
Adder
8.7105882352941187.404
944641AF1-129 C
Adder
111.0294117647058894.375
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.9423.942
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.18932.189
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.77619.776
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
70.76170.761
G-007PJM->LTFIMP_G-007
CMTX_NF
4.7184.718
NYPJM->LTFIMP_NY
CLTF
2.1242.124
LGEELTFEXP_LGEE->PJM
CLTF
1.2851.285
WECLTFEXP_WEC->PJM
CLTF
0.6630.663
CPLELTFEXP_CPLE->PJM
CLTF
8.2628.262
TVALTFEXP_TVA->PJM
CLTF
5.1295.129
MECLTFEXP_MEC->PJM
CLTF
3.7623.762
LAGNLTFEXP_LAGN->PJM
CLTF
6.4396.439
SIGELTFEXP_SIGE->PJM
CLTF
0.2410.241
O66PJM->LTFIMP_O-066
CMTX_NF
29.9829.98

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.88 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1342.55
MW Contribution:1.68
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.67 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1350.99
MW Contribution:1.61
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.410588235294117640.349
961672AG1-007 E
Adder
0.232941176470588260.198
961941AG1-037 C
Adder
0.212941176470588240.181
961942AG1-037 E
Adder
0.14235294117647060.121
963041AG1-153 C
50/50
3.6733.673
963042AG1-153 E
50/50
5.5095.509
964791AG1-342 C
Adder
1.48470588235294131.262
964792AG1-342 E
Adder
0.99058823529411770.842
966621AG1-532 C
Adder
0.60117647058823530.511
966622AG1-532 E
Adder
0.40.34
3145413WATKINS
Adder
0.279999999999999970.238
3145723EMPORIA
Adder
0.18470588235294120.157
3151311EDGECMA
Adder
6.8129411764705895.791
918492AA1-063AE OP
Adder
1.72705882352941181.468
918532AA1-067 E
Adder
0.30941176470588240.263
919692AA2-053 E OP
Adder
1.80705882352941181.536
920042AA2-088 E OP
Adder
4.3847058823529413.727
925785AC1-054 E
Adder
1.47764705882352951.256
926274AC1-105 E
Adder
1.13764705882352950.967
927146AC1-208 E
Adder
1.72941176470588241.47
934521AD1-076 C
Adder
5.1635294117647064.389
934522AD1-076 E
Adder
2.6317647058823532.237
943172AE2-346 E
Adder
0.255294117647058840.217
943902AF1-058 E
Adder
0.55294117647058830.47
944011AF1-069 C
50/50
8.8768.876
944012AF1-069 E
50/50
3.4483.448
959311AF2-222 C
Adder
5.57411764705882454.738
959312AF2-222 E
Adder
3.73411764705882383.174
960081AF2-299 C
Adder
0.80117647058823540.681
960082AF2-299 E
Adder
0.53411764705882360.454
316141AB2-099 E
Adder
0.107058823529411760.091
900672V4-068 E
Adder
0.149411764705882360.127
917342Z2-044 E
Adder
0.26117647058823530.222
922923AB1-081 E OP
Adder
1.63529411764705881.39
923263AB1-132 E OP
Adder
2.6305882352941182.236
923573AB1-173 E OP
Adder
1.40588235294117661.195
924162AB2-060 E OP
Adder
1.71764705882352931.46
924302AB2-077 E O1
Adder
0.54823529411764720.466
924312AB2-078 E O1
Adder
0.54823529411764720.466
924322AB2-079 E O1
Adder
0.54823529411764720.466
925612AC1-036 E
Adder
0.30.255
940492AE2-034 E
Adder
1.2952941176470591.101
941011AE2-092 C
Adder
-4.452941176470588-3.785
941031AE2-094 C
50/50
27.16527.165
941032AE2-094 E
50/50
12.16712.167
946281AF1-292 C
Adder
0.66352941176470580.564
946282AF1-292 E
Adder
0.44235294117647060.376
957481AF2-042 C
Adder
28.3424.089
957482AF2-042 E
Adder
18.89411764705882416.06
957861AF2-080 C
Adder
3.3247058823529412.826
957862AF2-080 E
Adder
1.47411764705882351.253
3145393UNCAMP
Adder
2.44352941176470572.077
916042Z1-036 E
Adder
11.93411764705882510.144
938771AE1-103 C
Adder
1.16941176470588240.994
938772AE1-103 E
Adder
1.61529411764705881.373
3145256KINGFORK
Adder
0.367058823529411770.312
3145506HICKORY
Adder
0.91764705882352950.78
926662AC1-147 E
Adder
0.53176470588235290.452
926755AC1-161 E
Adder
5.7376470588235294.877
935112AD1-144 E
Adder
0.339999999999999970.289
942341AE2-247 C
Adder
0.50235294117647060.427
942342AE2-247 E
Adder
0.69411764705882350.59
943461AF1-017 C
Adder
0.454117647058823570.386
943462AF1-017 E
Adder
0.74117647058823530.63
943612AF1-032 E
Adder
0.374117647058823550.318
3151021BRUNSWICKG1
50/50
5.4215.421
3151031BRUNSWICKG2
50/50
5.4215.421
3151041BRUNSWICKG3
50/50
5.4215.421
3151051BRUNSWICKS1
50/50
11.26311.263
3152411Z1-086 GT1
50/50
7.0067.006
3152421Z1-086 GT2
50/50
7.0037.003
3152431Z1-086 GT3
50/50
7.0037.003
3152441Z1-086 ST
50/50
12.19612.196
913392Y1-086 E
Adder
0.91764705882352950.78
916192Z1-068 E
Adder
0.77294117647058820.657
923832AB2-022 E
Adder
0.51764705882352950.44
923852AB2-025 E
Adder
0.50705882352941180.431
939312AE1-162 E
Adder
0.41294117647058820.351
957492AF2-043 E
Adder
0.57529411764705880.489
901082W1-029 E
Adder
13.19764705882352911.218
917122Z2-027 E
Adder
0.55999999999999990.476
925522AC1-027 E
Adder
0.50.425
957871AF2-081 C
Adder
4.1964705882352953.567
957872AF2-081 E
Adder
1.79882352941176471.529
958161AF2-110 C
Adder
0.53058823529411770.451
958162AF2-110 E
Adder
0.84352941176470590.717
3147223TWITTYS
Adder
0.332941176470588240.283
917512Z2-088 E OP1
Adder
2.1352941176470591.815
926071AC1-086 C
Adder
9.037647058823537.682
926072AC1-086 E
Adder
4.11294117647058853.496
927021AC1-189 C
Adder
3.66117647058823573.112
927022AC1-189 E
Adder
1.8235294117647061.55
936261AD2-033 C
Adder
4.2364705882352943.601
936262AD2-033 E
Adder
2.8247058823529412.401
933291AC2-141 C
Adder
13.44235294117647211.426
933292AC2-141 E
Adder
5.7376470588235294.877
934621AD1-088 C
Adder
4.3611764705882353.707
934622AD1-088 E
Adder
2.11.785
939411AE1-173 C
50/50
55.12655.126
939412AE1-173 E
50/50
36.75136.751
933981AD1-022 C
Adder
3.73.145
933982AD1-022 E
Adder
2.01411764705882361.712
962572AG1-106 E
Adder
0.51176470588235290.435
962571AG1-106 C
Adder
1.16941176470588240.994
3145946PLYMOUTH TP
Adder
0.136470588235294120.116
3146326AYDLETT TAP
Adder
0.56823529411764710.483
316263AC1-034 C
Adder
2.91411764705882352.477
316274AC1-208 C
Adder
3.8952941176470593.311
316336AC2-165 C
Adder
-10.758823529411764-9.145
917332KELFORD E
Adder
0.70117647058823530.596
924516AB2-100 E1
Adder
1.25176470588235311.064
924517AB2-100 E2
Adder
1.25176470588235311.064
925595AC1-034 E
Adder
2.19764705882352951.868
926206AC1-098 E
Adder
1.57411764705882361.338
926214AC1-099 E
Adder
0.520.442
927255AC1-221 E
Adder
1.65176470588235281.404
927264AC1-222 E
Adder
1.66470588235294131.415
932763AC2-100 E
Adder
1.12117647058823520.953
934065AD1-033 E
Adder
2.10705882352941171.791
937226AE2-253 E
Adder
2.4552941176470592.087
918512AA1-065 E OP
Adder
2.34000000000000031.989
919153AA1-139 E2
Adder
1.71529411764705891.458
919152AA1-139 E1
Adder
1.71529411764705891.458
919710AA2-057 E
Adder
1.72588235294117661.467
920692AA2-178 E
Adder
1.72705882352941181.468
923994AB2-040_E
Adder
2.63647058823529432.241
924022AB2-043 E O1
Adder
2.11764705882352941.8
924152AB2-059 E OP
Adder
2.31764705882352961.97
925122AB2-169 E
Adder
2.4564705882352942.088
316088AB2-174 E
Adder
2.7941176470588242.375
932046AC2-012 E
Adder
5.2588235294117654.47
316311AC2-079 C
Adder
1.9682352941176471.673
932596AC2-079 E
Adder
3.2117647058823532.73
316349AD2-085 C
Adder
1.15882352941176480.985
936666AD2-085 E
Adder
1.89058823529411771.607
941591AE2-156 C
Adder
7.202352941176476.122
944581AF1-123 C
Adder
19.11999999999999716.252
944582AF1-123 E
Adder
43.7823529411764837.215
944591AF1-124 C
Adder
19.18823529411764616.31
944592AF1-124 E
Adder
43.9411764705882437.35
944601AF1-125 C
Adder
18.82588235294117516.002
944602AF1-125 E
Adder
43.0952941176470636.631
962561AG1-105 C
Adder
3.70941176470588243.153
962562AG1-105 E
Adder
2.4729411764705882.102
964241AG1-285 C
Adder
5.3647058823529414.56
964242AG1-285 E
Adder
3.57647058823529433.04
3137643SOCKMAN
Adder
0.30470588235294120.259
932632AC2-084 E
Adder
1.3917647058823531.183
934321AD1-056 C
Adder
2.72588235294117662.317
934322AD1-056 E
Adder
1.47882352941176461.257
934331AD1-057 C
Adder
1.52117647058823541.293
934332AD1-057 E
Adder
0.7917647058823530.673
934501AD1-074 C
Adder
14.2176470588235312.085
934502AD1-074 E
Adder
7.237647058823536.152
934511AD1-075 C
Adder
3.55411764705882363.021
934512AD1-075 E
Adder
1.80941176470588251.538
934612AD1-087 E
Adder
1.79882352941176471.529
935172AD1-152 E
Adder
2.6258823529411772.232
936161AD2-022 C
Adder
3.0882352941176472.625
936162AD2-022 E
Adder
1.85294117647058831.575
936171AD2-023 C
Adder
1.80117647058823521.531
936172AD2-023 E
Adder
0.97764705882352940.831
937482AD2-202 E
Adder
0.52588235294117650.447
938531AE1-072 C
Adder
7.3705882352941176.265
938532AE1-072 E
Adder
3.84235294117647053.266
938821AE1-108 C
Adder
-4.716470588235294-4.009
940481AE2-033 C
Adder
7.0611764705882366.002
940482AE2-033 E
Adder
4.7611764705882354.047
940541AE2-040 C
Adder
1.25411764705882361.066
940641AE2-051 C
50/50
11.53811.538
940642AE2-051 E
50/50
7.6927.692
941101AE2-104 C
Adder
1.31.105
941102AE2-104 E
Adder
2.06588235294117651.756
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0921.092
NYPJM->LTFIMP_NY
CLTF
0.5140.514
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
WECLTFEXP_WEC->PJM
CLTF
0.2390.239
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091
O66PJM->LTFIMP_O-066
CMTX_NF
6.9576.957

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.42 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2598.93
MW Contribution:3.1
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.96 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2758.53
MW Contribution:3.04
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.73882352941176480.628
961672AG1-007 E
Adder
0.41882352941176470.356
961791AG1-021 C
Adder
1.33058823529411761.131
961792AG1-021 E
Adder
1.13294117647058810.963
961941AG1-037 C
Adder
0.367058823529411770.312
961942AG1-037 E
Adder
0.244705882352941160.208
963041AG1-153 C
50/50
6.556.55
963042AG1-153 E
50/50
9.8259.825
964791AG1-342 C
Adder
3.09882352941176452.634
964792AG1-342 E
Adder
2.06588235294117651.756
966621AG1-532 C
Adder
1.15411764705882350.981
966622AG1-532 E
Adder
0.76941176470588240.654
3138533PONTONDP
Adder
0.49294117647058820.419
3145413WATKINS
Adder
0.451764705882352960.384
3145723EMPORIA
Adder
0.352941176470588260.3
3147133PAMPLIN
Adder
0.740.629
3151311EDGECMA
Adder
12.4152941176470610.553
3151531CLOVER1
50/50
12.55212.552
3151541CLOVER2
50/50
12.43612.436
918492AA1-063AE OP
Adder
3.0882352941176472.625
918532AA1-067 E
Adder
0.54705882352941180.465
919692AA2-053 E OP
Adder
3.30000000000000032.805
920042AA2-088 E OP
Adder
7.3835294117647066.276
925785AC1-054 E
Adder
2.882.448
926274AC1-105 E
Adder
2.3364705882352941.986
927146AC1-208 E
Adder
3.14470588235294152.673
934521AD1-076 C
Adder
9.1176470588235297.75
934522AD1-076 E
Adder
4.6470588235294123.95
943172AE2-346 E
Adder
0.440.374
943902AF1-058 E
Adder
1.11882352941176480.951
944011AF1-069 C
50/50
15.67315.673
944012AF1-069 E
50/50
6.0886.088
959311AF2-222 C
Adder
14.27882352941176512.137
959312AF2-222 E
Adder
9.5670588235294118.132
960081AF2-299 C
Adder
1.541.309
960082AF2-299 E
Adder
1.02588235294117650.872
316141AB2-099 E
Adder
0.183529411764705890.156
900672V4-068 E
Adder
0.254117647058823560.216
917342Z2-044 E
Adder
0.475294117647058870.404
922923AB1-081 E OP
Adder
2.9811764705882352.534
923263AB1-132 E OP
Adder
4.8517647058823534.124
923573AB1-173 E OP
Adder
2.65411764705882322.256
924162AB2-060 E OP
Adder
3.78117647058823543.214
924302AB2-077 E O1
Adder
1.18705882352941171.009
924312AB2-078 E O1
Adder
1.18705882352941171.009
924322AB2-079 E O1
Adder
1.18705882352941171.009
925612AC1-036 E
Adder
0.74705882352941180.635
940492AE2-034 E
Adder
2.3152941176470591.968
941031AE2-094 C
50/50
47.96747.967
941032AE2-094 E
50/50
21.48321.483
946281AF1-292 C
Adder
1.27411764705882361.083
946282AF1-292 E
Adder
0.84941176470588230.722
946301AF1-294 C
Adder
2.73529411764705932.325
946302AF1-294 E
Adder
2.3164705882352941.969
957481AF2-042 C
50/50
55.26355.263
957482AF2-042 E
50/50
36.84236.842
957861AF2-080 C
Adder
5.9388235294117655.048
957862AF2-080 E
Adder
2.6329411764705882.238
958211AF2-115 C
Adder
1.6635294117647061.414
958212AF2-115 E
Adder
1.41647058823529411.204
3145393UNCAMP
Adder
3.8517647058823533.274
916042Z1-036 E
Adder
21.67647058823529718.425
938771AE1-103 C
Adder
1.81647058823529431.544
938772AE1-103 E
Adder
2.50941176470588222.133
3143316POE
Adder
0.80823529411764720.687
3145506HICKORY
50/50
2.1612.161
926662AC1-147 E
Adder
1.23058823529411781.046
926755AC1-161 E
50/50
37.13537.135
3151021BRUNSWICKG1
50/50
9.6689.668
3151031BRUNSWICKG2
50/50
9.6689.668
3151041BRUNSWICKG3
50/50
9.6689.668
3151051BRUNSWICKS1
50/50
20.08620.086
3151081ELIZAR1
50/50
3.033.03
3151091ELIZAR2
50/50
2.9782.978
3151101ELIZAR3
50/50
3.0693.069
3152411Z1-086 GT1
50/50
12.45512.455
3152421Z1-086 GT2
50/50
12.4512.45
3152431Z1-086 GT3
50/50
12.4512.45
3152441Z1-086 ST
50/50
21.68121.681
913392Y1-086 E
Adder
1.8917647058823531.608
916192Z1-068 E
50/50
1.7941.794
923832AB2-022 E
Adder
1.06823529411764720.908
923852AB2-025 E
Adder
0.98588235294117640.838
957601AF2-054 C
Adder
-1.2505882352941176-1.063
901082W1-029 E
Adder
23.54352941176470520.012
917122Z2-027 E
Adder
1.1117647058823530.945
925522AC1-027 E
50/50
1.1581.158
957871AF2-081 C
50/50
9.4939.493
957872AF2-081 E
50/50
4.0684.068
3147223TWITTYS
Adder
0.82823529411764710.704
917512Z2-088 E OP1
Adder
3.83294117647058833.258
926071AC1-086 C
Adder
16.6705882352941214.17
926072AC1-086 E
Adder
7.5870588235294126.449
927021AC1-189 C
Adder
6.5388235294117655.558
927022AC1-189 E
Adder
3.25764705882352962.769
936261AD2-033 C
Adder
10.7294117647058829.12
936262AD2-033 E
Adder
7.1529411764705896.08
933291AC2-141 C
50/50
86.99486.994
933292AC2-141 E
50/50
37.13537.135
934621AD1-088 C
50/50
9.1619.161
934622AD1-088 E
50/50
4.4114.411
939411AE1-173 C
50/50
86.92186.921
939412AE1-173 E
50/50
57.94757.947
916191Z1-068 C
50/50
0.0420.042
933981AD1-022 C
Adder
6.4741176470588245.503
933982AD1-022 E
Adder
3.52470588235294142.996
962572AG1-106 E
Adder
0.9435294117647060.802
962571AG1-106 C
Adder
2.1564705882352941.833
3145946PLYMOUTH TP
Adder
0.24117647058823530.205
3146326AYDLETT TAP
Adder
1.25647058823529421.068
316185AD1-033 C
50/50
1.2261.226
316263AC1-034 C
Adder
5.31058823529411854.514
316274AC1-208 C
Adder
7.0835294117647066.021
316294AC1-161 C
50/50
14.21614.216
316316AC1-027 C
50/50
0.3010.301
917332KELFORD E
Adder
1.2282352941176471.044
924516AB2-100 E1
Adder
2.3717647058823532.016
924517AB2-100 E2
Adder
2.3717647058823532.016
925595AC1-034 E
Adder
4.00588235294117643.405
926206AC1-098 E
Adder
2.8317647058823532.407
926214AC1-099 E
Adder
0.93529411764705890.795
927255AC1-221 E
Adder
3.2152941176470592.733
927264AC1-222 E
Adder
3.3870588235294122.879
932763AC2-100 E
Adder
2.1788235294117651.852
934065AD1-033 E
50/50
5.0045.004
937226AE2-253 E
50/50
5.6435.643
918512AA1-065 E OP
Adder
3.98941176470588273.391
316017AA1-139 ULT1
50/50
1.0281.028
316018AA1-139 ULT2
50/50
1.0281.028
919153AA1-139 E2
50/50
3.8823.882
919152AA1-139 E1
50/50
3.8823.882
919710AA2-057 E
Adder
3.1364705882352942.666
920692AA2-178 E
Adder
3.0870588235294122.624
923994AB2-040_E
Adder
4.9776470588235294.231
924022AB2-043 E O1
Adder
4.6082352941176473.917
924152AB2-059 E OP
Adder
4.2235294117647063.59
925122AB2-169 E
Adder
4.3388235294117653.688
316088AB2-174 E
Adder
5.3035294117647064.508
316375AC2-012 C
50/50
1.2551.255
932046AC2-012 E
50/50
12.1712.17
316388AE2-253 GEN
50/50
1.8981.898
941591AE2-156 C
50/50
16.7516.75
944581AF1-123 C
50/50
45.64445.644
944582AF1-123 E
50/50
104.52104.52
944591AF1-124 C
50/50
45.80645.806
944592AF1-124 E
50/50
104.898104.898
944601AF1-125 C
50/50
44.94144.941
944602AF1-125 E
50/50
102.879102.879
962561AG1-105 C
Adder
7.7917647058823536.623
962562AG1-105 E
Adder
5.1941176470588244.415
964241AG1-285 C
Adder
11.7588235294117649.995
964242AG1-285 E
Adder
7.846.664
3137643SOCKMAN
Adder
0.56941176470588240.484
932632AC2-084 E
Adder
2.50352941176470622.128
934321AD1-056 C
Adder
4.99411764705882364.245
934322AD1-056 E
Adder
2.70941176470588242.303
934331AD1-057 C
Adder
2.78588235294117632.368
934332AD1-057 E
Adder
1.45058823529411771.233
934501AD1-074 C
Adder
25.10470588235294221.339
934502AD1-074 E
Adder
12.7810.863
934511AD1-075 C
Adder
6.2764705882352945.335
934512AD1-075 E
Adder
3.19529411764705932.716
934611AD1-087 C
50/50
1.2361.236
934612AD1-087 E
50/50
3.5653.565
935172AD1-152 E
Adder
5.2058823529411774.425
937481AD2-202 C
50/50
0.3590.359
937482AD2-202 E
50/50
1.0431.043
938531AE1-072 C
50/50
16.39816.398
938532AE1-072 E
50/50
8.5488.548
940481AE2-033 C
Adder
13.6776470588235311.626
940482AE2-033 E
Adder
9.2211764705882357.838
940541AE2-040 C
Adder
2.4364705882352942.071
940641AE2-051 C
50/50
26.4726.47
940642AE2-051 E
50/50
17.64717.647
942461AE2-259 C
Adder
6.5341176470588245.554
942462AE2-259 E
Adder
4.3564705882352943.703
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.7574.757
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.52724.527
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.91517.915
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.65881.658
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1242.124
NYPJM->LTFIMP_NY
CLTF
0.9860.986
LGEELTFEXP_LGEE->PJM
CLTF
0.950.95
WECLTFEXP_WEC->PJM
CLTF
0.5060.506
CPLELTFEXP_CPLE->PJM
CLTF
9.989.98
TVALTFEXP_TVA->PJM
CLTF
4.8674.867
MECLTFEXP_MEC->PJM
CLTF
3.1033.103
LAGNLTFEXP_LAGN->PJM
CLTF
6.2356.235
SIGELTFEXP_SIGE->PJM
CLTF
0.1890.189
O66PJM->LTFIMP_O-066
CMTX_NF
13.52713.527

Details for AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:124.4 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:844.26
MW Contribution:7.86
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-033 TP-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:129.93 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:881.78
MW Contribution:7.88
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
50/50
0.9020.902
961672AG1-007 E
50/50
0.5110.511
961941AG1-037 C
50/50
0.480.48
961942AG1-037 E
50/50
0.320.32
966621AG1-532 C
50/50
3.2323.232
966622AG1-532 E
50/50
2.1552.155
313506AB1-173 C OP
50/50
2.1742.174
3145413WATKINS
50/50
0.4340.434
3145723EMPORIA
50/50
0.9510.951
3147043LAWRENC
50/50
0.5440.544
3151261ROARAP2
50/50
2.0552.055
3151281ROARAP4
50/50
1.9441.944
3151311EDGECMA
50/50
16.316.3
3151361ROSEMG1
50/50
3.9143.914
3151371ROSEMS1
50/50
2.4252.425
3151381ROSEMG2
50/50
1.8331.833
3151391GASTONA
50/50
6.1446.144
918492AA1-063AE OP
50/50
5.1285.128
918532AA1-067 E
50/50
0.5790.579
919692AA2-053 E OP
50/50
5.8745.874
920042AA2-088 E OP
50/50
9.2489.248
925785AC1-054 E
50/50
3.2573.257
927146AC1-208 E
50/50
4.8664.866
934521AD1-076 C
Adder
7.246.154
934522AD1-076 E
Adder
3.6905882352941183.137
943171AE2-346 C
50/50
0.2130.213
943172AE2-346 E
50/50
0.5760.576
960081AF2-299 C
50/50
4.3094.309
960082AF2-299 E
50/50
2.8732.873
3156011CONETOE2SOL
50/50
1.1641.164
3156063AA2-053SOLA
50/50
2.0952.095
316129AC1-054 C
50/50
1.1551.155
316140AB2-099 C
50/50
0.0910.091
316141AB2-099 E
50/50
0.240.24
900672V4-068 E
50/50
0.330.33
917342Z2-044 E
50/50
0.6430.643
922923AB1-081 E OP
50/50
3.8493.849
923263AB1-132 E OP
50/50
12.30412.304
923573AB1-173 E OP
50/50
6.3246.324
946281AF1-292 C
50/50
3.5673.567
946282AF1-292 E
50/50
2.3782.378
957861AF2-080 C
50/50
6.8036.803
957862AF2-080 E
50/50
3.0163.016
3145393UNCAMP
Adder
3.1317647058823532.662
3151151S HAMPT1
50/50
0.9640.964
3151411GASTONB
50/50
6.1446.144
3156073AA1-063SOLA
50/50
1.7661.766
3156083AA2-088SOLA
50/50
0.9260.926
917512Z2-088 E OP1
50/50
4.5534.553
926071AC1-086 C
50/50
42.27842.278
926072AC1-086 E
50/50
19.24219.242
927021AC1-189 C
50/50
7.497.49
927022AC1-189 E
50/50
3.7313.731
933981AD1-022 C
50/50
5.8155.815
933982AD1-022 E
50/50
3.1653.165
962572AG1-106 E
50/50
2.3922.392
962571AG1-106 C
50/50
5.4685.468
3145946PLYMOUTH TP
Adder
0.18470588235294120.157
316005AA1-067 C
50/50
0.2210.221
316011AB1-132 C OP
50/50
4.6924.692
316023AB2-100 C2
50/50
2.7732.773
316049AB1-081 C OP
50/50
1.4681.468
316210AC1-098 C
50/50
1.0771.077
316212AC1-099 C
50/50
0.3610.361
316263AC1-034 C
50/50
6.8576.857
316274AC1-208 C
50/50
10.95810.958
316317KELFORD C
50/50
0.3660.366
316318V4-068 C
50/50
0.0740.074
316319Z2-044 C
50/50
0.2270.227
316365AB2-100 C1
50/50
2.7732.773
917332KELFORD E
50/50
1.6811.681
924516AB2-100 E1
50/50
8.3588.358
924517AB2-100 E2
50/50
8.3588.358
925595AC1-034 E
50/50
5.1725.172
926206AC1-098 E
50/50
4.1714.171
926214AC1-099 E
50/50
1.3781.378
3156021HOLLOMANSOL
50/50
1.5991.599
918512AA1-065 E OP
50/50
4.8064.806
316327AA2-057 C
50/50
1.4581.458
919710AA2-057 E
50/50
4.4424.442
316181AB2-040 GEN
50/50
2.4492.449
923994AB2-040_E
50/50
11.85811.858
316359AB2-059 C OP
50/50
1.731.73
924152AB2-059 E OP
50/50
5.4535.453
316174AB2-169_C
50/50
0.7280.728
925122AB2-169 E
50/50
3.9953.995
316087AB2-174 C
50/50
2.4072.407
316088AB2-174 E
50/50
13.32913.329
3137643SOCKMAN
50/50
1.2021.202
932631AC2-084 C
50/50
1.1471.147
932632AC2-084 E
50/50
3.6863.686
934321AD1-056 C
50/50
9.1149.114
934322AD1-056 E
50/50
4.9434.943
934331AD1-057 C
50/50
5.0845.084
934332AD1-057 E
50/50
2.6472.647
934501AD1-074 C
Adder
19.93647058823529516.946
934502AD1-074 E
Adder
10.1482352941176478.626
934511AD1-075 C
Adder
4.9835294117647064.236
934512AD1-075 E
Adder
2.53764705882352942.157
940481AE2-033 C
50/50
63.79163.791
940482AE2-033 E
50/50
43.00543.005
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.0232.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.6319.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7166.716
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.27631.276
G-007PJM->LTFIMP_G-007
CMTX_NF
0.6890.689
NYPJM->LTFIMP_NY
CLTF
0.3160.316
LGEELTFEXP_LGEE->PJM
CLTF
0.3690.369
WECLTFEXP_WEC->PJM
CLTF
0.1970.197
CPLELTFEXP_CPLE->PJM
CLTF
4.2444.244
TVALTFEXP_TVA->PJM
CLTF
1.8021.802
MECLTFEXP_MEC->PJM
CLTF
1.1871.187
LAGNLTFEXP_LAGN->PJM
CLTF
2.312.31
SIGELTFEXP_SIGE->PJM
CLTF
0.0730.073
O66PJM->LTFIMP_O-066
CMTX_NF
4.3814.381
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 246_SRT-A'
 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1   /*6SUFFOLK     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1   /*6EARLEYS     230.0 - 6NUCO TP     230.0
 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1   /*6NUCO TP     230.0 - 6NUCOR       230.0
 OPEN BUS 314575                                   /*6NUCO TP     230.0
 OPEN BUS 314590                                   /*6NUCOR       230.0
END
CONTINGENCY 'DVP_P1-2: LN 2092_SRT-A'
 OPEN BRANCH FROM BUS 313714 TO BUS 313885 CKT 1   /*6PEMBROKE    230.0 - 6WALBMRL     230.0
 OPEN BRANCH FROM BUS 313885 TO BUS 314662 CKT 1   /*6WALBMRL     230.0 - 6S HERTFORD  230.0
 OPEN BRANCH FROM BUS 314651 TO BUS 314662 CKT 1   /*6WINFALL     230.0 - 6S HERTFORD  230.0
 OPEN BUS 313885                                   /*6WALBMRL     230.0
 OPEN BUS 314662                                   /*6S HERTFORD  230.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'RKYMT-WILS230_&_RKYMT-SHARPB115_SRT-S'
 OPEN BRANCH FROM BUS 304219 TO BUS 304223 CKT 1   /*3W-SHARPB    115.0 - 3ROCKYMT115T 115.0
 OPEN BRANCH FROM BUS 304222 TO BUS 304228 CKT 1   /*6ROCKYMT230T 230.0 - 6WILSON230 T 230.0
END
CONTINGENCY 'DVP_P1-2: LN 225_SRT-A'
 OPEN BRANCH FROM BUS 314583 TO BUS 314611 CKT 2   /*6LAKEVEW     230.0 - 6THELMA      230.0
END
CONTINGENCY 'DVP_P1-2: LN 213_SRT-A'
 OPEN BRANCH FROM BUS 314583 TO BUS 314611 CKT 1   /*6LAKEVEW     230.0 - 6THELMA      230.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
314225 to 314227 ckt 1
314214 to 314903 ckt 1
314287 to 314260 ckt 1
313015 to 313714 ckt 1
314563 to 940480 ckt 1
314569 to 314575 ckt 1
314218 to 314908 ckt 2
314574 to 304451 ckt 1
314203 to 314637 ckt 1
314575 to 314537 ckt 1
313714 to 313885 ckt 1
314662 to 314651 ckt 1
314435 to 314282 ckt 1
314611 to 314583 ckt 1
314611 to 314583 ckt 2
314260 to 314225 ckt 1
313885 to 314662 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314914 to 314322 ckt 1
314923 to 314924 ckt 1
940480 to 314435 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 2201_SRT-A
OPAC112.45 %252.86B284.351.73
GD1DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S-1
OPAC111.78 %1058.16B1182.781.73
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Base Case
OPAC104.11 %2442.12A2542.463.75

Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 2201_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.45 %
Rating:252.86 MVA
Rating Type:B
MVA to Mitigate:284.35
MW Contribution:1.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
0.67176470588235290.571
961792AG1-021 E
Adder
0.5717647058823530.486
964791AG1-342 C
Adder
1.3564705882352941.153
964792AG1-342 E
Adder
0.90352941176470590.768
966621AG1-532 C
50/50
4.3954.395
966622AG1-532 E
50/50
2.932.93
313506AB1-173 C OP
50/50
2.3342.334
3138533PONTONDP
Adder
0.248235294117647050.211
3145723EMPORIA
50/50
1.2311.231
3147043LAWRENC
50/50
0.740.74
3151261ROARAP2
50/50
1.1521.152
3151281ROARAP4
50/50
1.091.09
918492AA1-063AE OP
50/50
2.7952.795
919692AA2-053 E OP
50/50
3.1533.153
920042AA2-088 E OP
Adder
4.6305882352941183.936
925785AC1-054 E
50/50
2.0962.096
927146AC1-208 E
Adder
2.18117647058823531.854
959311AF2-222 C
Adder
7.8188235294117656.646
959312AF2-222 E
Adder
5.2388235294117654.453
960081AF2-299 C
50/50
5.865.86
960082AF2-299 E
50/50
3.9073.907
3156063AA2-053SOLA
50/50
1.1211.121
316129AC1-054 C
50/50
0.7410.741
316131AB2-060 C
50/50
0.8950.895
900672V4-068 E
Adder
0.149411764705882360.127
923263AB1-132 E OP
Adder
2.7023529411764712.297
923573AB1-173 E OP
50/50
6.8126.812
924162AB2-060 E OP
50/50
2.5852.585
924302AB2-077 E O1
Adder
0.79529411764705890.676
924312AB2-078 E O1
Adder
0.79529411764705890.676
924322AB2-079 E O1
Adder
0.79529411764705890.676
925612AC1-036 E
Adder
0.41647058823529410.354
946281AF1-292 C
50/50
4.8514.851
946282AF1-292 E
50/50
3.2343.234
946301AF1-294 C
Adder
1.38117647058823521.174
946302AF1-294 E
Adder
1.16941176470588240.994
958211AF2-115 C
Adder
0.840.714
958212AF2-115 E
Adder
0.71529411764705890.608
3156073AA1-063SOLA
50/50
0.9590.959
3147223TWITTYS
Adder
0.46117647058823530.392
926071AC1-086 C
Adder
9.2870588235294127.894
926072AC1-086 E
Adder
4.2270588235294123.593
936261AD2-033 C
Adder
6.6258823529411775.632
936262AD2-033 E
Adder
4.4164705882352953.754
962572AG1-106 E
Adder
0.52588235294117650.447
962571AG1-106 C
Adder
1.20117647058823531.021
316274AC1-208 C
Adder
4.9105882352941184.174
917332KELFORD E
Adder
0.63764705882352950.542
924516AB2-100 E1
Adder
1.23882352941176471.053
924517AB2-100 E2
Adder
1.23882352941176471.053
926206AC1-098 E
Adder
1.7470588235294121.485
926214AC1-099 E
Adder
0.57647058823529410.49
919710AA2-057 E
Adder
1.7070588235294121.451
316181AB2-040 GEN
50/50
2.6292.629
923994AB2-040_E
50/50
12.77312.773
313527AB2-043 C
50/50
0.3160.316
924022AB2-043 E O1
50/50
3.1813.181
316087AB2-174 C
50/50
2.8212.821
316088AB2-174 E
50/50
15.67415.674
962561AG1-105 C
Adder
3.72941176470588243.17
962562AG1-105 E
Adder
2.48588235294117642.113
964241AG1-285 C
Adder
7.126.052
964242AG1-285 E
Adder
4.7470588235294124.035
3137643SOCKMAN
50/50
1.0011.001
932632AC2-084 E
Adder
1.5435294117647061.312
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.7010.701
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.4494.449
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.8192.819
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.39311.393
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3410.341
NYPJM->LTFIMP_NY
CLTF
0.1550.155
LGEELTFEXP_LGEE->PJM
CLTF
0.1740.174
WECLTFEXP_WEC->PJM
CLTF
0.0910.091
CPLELTFEXP_CPLE->PJM
CLTF
1.471.47
TVALTFEXP_TVA->PJM
CLTF
0.7390.739
MECLTFEXP_MEC->PJM
CLTF
0.5250.525
LAGNLTFEXP_LAGN->PJM
CLTF
0.9350.935
SIGELTFEXP_SIGE->PJM
CLTF
0.0330.033
O66PJM->LTFIMP_O-066
CMTX_NF
2.1672.167

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.78 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1182.78
MW Contribution:1.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
0.97294117647058820.827
961792AG1-021 E
Adder
0.82823529411764710.704
963041AG1-153 C
Adder
2.2623529411764711.923
963042AG1-153 E
Adder
3.39411764705882352.885
966621AG1-532 C
Adder
0.63882352941176480.543
966622AG1-532 E
Adder
0.42588235294117650.362
3138533PONTONDP
Adder
0.360.306
3145413WATKINS
Adder
0.30941176470588240.263
3145723EMPORIA
Adder
0.196470588235294150.167
3147133PAMPLIN
Adder
0.54941176470588240.467
918492AA1-063AE OP
Adder
1.8117647058823531.54
919692AA2-053 E OP
Adder
1.86823529411764721.588
920042AA2-088 E OP
Adder
4.724.012
944011AF1-069 C
Adder
5.2235294117647074.44
944012AF1-069 E
Adder
2.02941176470588271.725
959311AF2-222 C
Adder
8.5341176470588237.254
959312AF2-222 E
Adder
5.71764705882352954.86
960081AF2-299 C
Adder
0.8517647058823530.724
960082AF2-299 E
Adder
0.56823529411764710.483
900672V4-068 E
Adder
0.157647058823529420.134
923263AB1-132 E OP
Adder
2.70941176470588242.303
923573AB1-173 E OP
Adder
1.47764705882352951.256
924162AB2-060 E OP
Adder
2.0117647058823531.71
924302AB2-077 E O1
Adder
0.62117647058823530.528
924312AB2-078 E O1
Adder
0.62117647058823530.528
924322AB2-079 E O1
Adder
0.62117647058823530.528
925612AC1-036 E
Adder
0.435294117647058830.37
940492AE2-034 E
Adder
1.33882352941176451.138
941011AE2-092 C
Adder
6.9470588235294125.905
941012AE2-092 E
Adder
4.6305882352941183.936
941031AE2-094 C
Adder
15.98588235294117513.588
941032AE2-094 E
Adder
7.166.086
946281AF1-292 C
Adder
0.70588235294117650.6
946282AF1-292 E
Adder
0.47058823529411770.4
946301AF1-294 C
Adder
1.99882352941176491.699
946302AF1-294 E
Adder
1.69294117647058841.439
957481AF2-042 C
Adder
23.21647058823529619.734
957482AF2-042 E
Adder
15.4776470588235313.156
958211AF2-115 C
Adder
1.21529411764705891.033
958212AF2-115 E
Adder
1.0352941176470590.88
3145393UNCAMP
Adder
2.72117647058823582.313
916042Z1-036 E
Adder
12.43647058823529310.571
938771AE1-103 C
Adder
1.3117647058823531.115
938772AE1-103 E
Adder
1.8117647058823531.54
924032AB2-045 E
Adder
0.94941176470588240.807
933502AC2-165 E
50/50
10.19910.199
3143096IRON208
50/50
0.330.33
3143316POE
Adder
0.75647058823529410.643
3145256KINGFORK
Adder
0.455294117647058850.387
3145506HICKORY
Adder
0.94470588235294130.803
3150601CHESTF5
Adder
39.4470588235294233.53
3150651CHESTF6
Adder
11.96588235294117610.171
3150731STONECA
Adder
4.1494117647058823.527
3150831SPRUNCA
50/50
9.4469.446
3150841SPRUNCB
50/50
9.4469.446
3150921YORKTN3
Adder
52.8152941176470644.893
925865AC1-065 E
Adder
7.73058823529411756.571
926412AC1-112 E
Adder
0.56470588235294120.48
926662AC1-147 E
Adder
0.58117647058823530.494
926755AC1-161 E
Adder
0.59529411764705890.506
927226AC1-216 E
Adder
4.20352941176470553.573
934392AD1-063 E
Adder
0.487058823529411770.414
935112AD1-144 E
Adder
0.42235294117647060.359
942341AE2-247 C
Adder
0.71294117647058820.606
942342AE2-247 E
Adder
0.98470588235294120.837
943461AF1-017 C
Adder
0.64470588235294120.548
943462AF1-017 E
Adder
1.0517647058823530.894
943612AF1-032 E
Adder
0.405882352941176470.345
958502AF2-144 E
50/50
1.7771.777
966871AG1-558 C
Adder
1.27764705882352961.086
966872AG1-558 E
Adder
0.64352941176470590.547
316076AC2-137 E
Adder
0.73529411764705890.625
316157AD2-030 E
Adder
0.53411764705882360.454
913392Y1-086 E
Adder
0.9552941176470590.812
916192Z1-068 E
Adder
0.820.697
923832AB2-022 E
Adder
0.53882352941176470.458
923842AB2-024 E
Adder
0.82235294117647050.699
923852AB2-025 E
Adder
0.54941176470588240.467
923862AB2-026 E
50/50
1.8081.808
930122AB1-027 E
Adder
0.69529411764705880.591
938552AE1-074 E
50/50
1.8811.881
938562AE1-075 E
50/50
1.5421.542
939312AE1-162 E
Adder
0.67999999999999990.578
946262AF1-291 E
Adder
0.91058823529411770.774
957492AF2-043 E
Adder
0.62470588235294120.531
957601AF2-054 C
Adder
0.95294117647058830.81
957602AF2-054 E
Adder
0.63529411764705890.54
962962AG1-145 E
Adder
0.65529411764705890.557
901082W1-029 E
Adder
13.8976470588235311.813
917122Z2-027 E
Adder
0.58470588235294120.497
925332AB2-190 E
Adder
4.5752941176470593.889
925522AC1-027 E
Adder
0.53176470588235290.452
942001AE2-212 C
Adder
1.3035294117647061.108
942002AE2-212 E
Adder
0.86941176470588230.739
957832AF2-077 E
Adder
0.63529411764705890.54
957871AF2-081 C
Adder
4.3329411764705883.683
957872AF2-081 E
Adder
1.85647058823529431.578
958161AF2-110 C
Adder
0.61529411764705890.523
958162AF2-110 E
Adder
0.97882352941176460.832
3138116ELKO L286
Adder
0.76588235294117660.651
3147223TWITTYS
Adder
0.48235294117647060.41
926071AC1-086 C
Adder
9.3082352941176477.912
926072AC1-086 E
Adder
4.2364705882352943.601
936261AD2-033 C
Adder
6.5000000000000015.525
936262AD2-033 E
Adder
4.3329411764705883.683
933291AC2-141 C
Adder
12.51176470588235310.635
934621AD1-088 C
Adder
4.3294117647058833.68
934622AD1-088 E
Adder
2.08470588235294141.772
939411AE1-173 C
Adder
37.3388235294117631.738
939412AE1-173 E
Adder
24.89294117647058621.159
934012AD1-025 E
Adder
5.44117647058823554.625
927041AC1-191 C
Adder
5.1282352941176474.359
927042AC1-191 E
Adder
2.55411764705882362.171
962572AG1-106 E
Adder
0.52705882352941180.448
962571AG1-106 C
Adder
1.20352941176470571.023
3130536PAPERMILL
Adder
3.0341176470588242.579
3146326AYDLETT TAP
Adder
0.58823529411764710.5
316160AE1-175 E
Adder
0.54117647058823540.46
316169AC1-164 GEN
Adder
19.79647058823529816.827
316233AE1-074 C
50/50
3.7333.733
316240AF1-291 C
Adder
1.36588235294117651.161
316258AE1-075 C
50/50
0.5110.511
316313AB2-026 C
50/50
0.5570.557
316336AC2-165 C
50/50
13.55213.552
316405AF2-144 C
50/50
0.4340.434
924516AB2-100 E1
Adder
1.32117647058823541.123
924517AB2-100 E2
Adder
1.32117647058823541.123
926785AC1-164_E
Adder
8.8941176470588247.56
934065AD1-033 E
Adder
2.1752941176470591.849
937226AE2-253 E
Adder
2.53176470588235342.152
939612AE1-191 E
Adder
2.6082352941176472.217
919153AA1-139 E2
Adder
1.7717647058823531.506
919152AA1-139 E1
Adder
1.7717647058823531.506
920692AA2-178 E
Adder
1.78588235294117651.518
923994AB2-040_E
Adder
2.76941176470588252.354
924022AB2-043 E O1
Adder
2.4235294117647062.06
924814AB2-134 E
Adder
6.8847058823529425.852
316084AB2-161 E
Adder
2.8764705882352942.445
316088AB2-174 E
Adder
2.94705882352941152.505
932046AC2-012 E
Adder
5.7529411764705884.89
316311AC2-079 C
Adder
2.71999999999999982.312
932596AC2-079 E
Adder
4.4376470588235293.772
934146AD1-041 E
Adder
1.63058823529411771.386
934576AD1-082 E
Adder
2.2917647058823531.948
316349AD2-085 C
Adder
1.6447058823529411.398
936666AD2-085 E
Adder
2.6835294117647062.281
961611AG1-000B C
Adder
8.1152941176470596.898
941591AE2-156 C
Adder
7.8529411764705886.675
944581AF1-123 C
Adder
19.50352941176470616.578
944582AF1-123 E
Adder
44.6637.961
944591AF1-124 C
Adder
19.5717647058823516.636
944592AF1-124 E
Adder
44.82117647058823538.098
944601AF1-125 C
Adder
19.2023529411764716.322
944602AF1-125 E
Adder
43.9588235294117737.365
944631AF1-128 C
Adder
24.6823529411764720.98
964241AG1-285 C
Adder
6.0305882352941185.126
964242AG1-285 E
Adder
4.0211764705882363.418
3137643SOCKMAN
Adder
0.317647058823529450.27
934612AD1-087 E
Adder
1.55882352941176471.325
935161AD1-151 C
Adder
8.9764705882352947.63
935162AD1-151 E
Adder
5.9847058823529415.087
937482AD2-202 E
Adder
0.456470588235294130.388
938531AE1-072 C
Adder
7.6223529411764716.479
938532AE1-072 E
Adder
3.9729411764705883.377
938821AE1-108 C
Adder
8.4270588235294127.163
938822AE1-108 E
Adder
4.0211764705882363.418
939191AE1-149 C
Adder
5.8976470588235295.013
939192AE1-149 E
Adder
3.93176470588235333.342
939602AE1-190 E
Adder
0.6517647058823530.554
940431AE2-027 C
Adder
7.9682352941176476.773
940432AE2-027 E
Adder
5.3129411764705894.516
940481AE2-033 C
Adder
7.6223529411764716.479
940482AE2-033 E
Adder
5.13882352941176554.368
940541AE2-040 C
Adder
1.35764705882352941.154
940551AE2-041 C
Adder
3.25058823529411762.763
940641AE2-051 C
Adder
7.0152941176470595.963
940642AE2-051 E
Adder
4.67764705882352953.976
941101AE2-104 C
Adder
1.50823529411764711.282
941102AE2-104 E
Adder
2.39764705882352922.038
942461AE2-259 C
Adder
5.83647058823529454.961
942462AE2-259 E
Adder
3.8917647058823533.308
943471AF1-018 C
Adder
3.25058823529411762.763
944641AF1-129 C
Adder
65.7211764705882355.863
3150851SPRUNCC
50/50
0.1690.169
3150861SPRUNCD
50/50
0.1690.169
316303AF2-085
50/50
7.0277.027
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.2422.242
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.08118.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.29711.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.62940.629
G-007PJM->LTFIMP_G-007
CMTX_NF
2.112.11
NYPJM->LTFIMP_NY
CLTF
0.9630.963
LGEELTFEXP_LGEE->PJM
CLTF
0.7270.727
WECLTFEXP_WEC->PJM
CLTF
0.3730.373
CPLELTFEXP_CPLE->PJM
CLTF
4.6984.698
TVALTFEXP_TVA->PJM
CLTF
2.952.95
MECLTFEXP_MEC->PJM
CLTF
2.1322.132
LAGNLTFEXP_LAGN->PJM
CLTF
3.6953.695
SIGELTFEXP_SIGE->PJM
CLTF
0.1370.137
O66PJM->LTFIMP_O-066
CMTX_NF
13.41813.418

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.11 %
Rating:2442.12 MVA
Rating Type:A
MVA to Mitigate:2542.46
MW Contribution:3.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.55529411764705880.472
961942AG1-037 E
Adder
0.370588235294117660.315
963041AG1-153 C
Adder
4.884.148
963042AG1-153 E
Adder
7.3188235294117656.221
966621AG1-532 C
Adder
1.27294117647058851.082
966622AG1-532 E
Adder
0.84823529411764710.721
3145413WATKINS
Adder
0.82235294117647050.699
3145723EMPORIA
Adder
0.39411764705882360.335
918492AA1-063AE OP
Adder
4.17764705882352953.551
918532AA1-067 E
Adder
0.72588235294117650.617
919692AA2-053 E OP
Adder
4.1705882352941183.545
920042AA2-088 E OP
Adder
11.93294117647058910.143
927146AC1-208 E
Adder
3.8470588235294123.27
934521AD1-076 C
Adder
14.67647058823529312.475
934522AD1-076 E
Adder
7.48117647058823556.359
943172AE2-346 E
Adder
0.66705882352941170.567
944011AF1-069 C
Adder
11.532941176470599.803
944012AF1-069 E
Adder
4.47999999999999953.808
960081AF2-299 C
Adder
1.69647058823529421.442
960082AF2-299 E
Adder
1.13058823529411770.961
316141AB2-099 E
Adder
0.27764705882352940.236
900672V4-068 E
Adder
0.395294117647058850.336
923263AB1-132 E OP
Adder
5.86235294117647054.983
923573AB1-173 E OP
Adder
3.06235294117647072.603
940492AE2-034 E
Adder
3.8317647058823533.257
941031AE2-094 C
Adder
35.2988235294117730.004
941032AE2-094 E
Adder
15.80941176470588313.438
946281AF1-292 C
Adder
1.40470588235294121.194
946282AF1-292 E
Adder
0.93647058823529420.796
957861AF2-080 C
Adder
7.47999999999999956.358
957862AF2-080 E
Adder
3.3152941176470592.818
3145393UNCAMP
Adder
7.4105882352941186.299
916042Z1-036 E
Adder
37.13529411764706431.565
938771AE1-103 C
Adder
3.62470588235294143.081
938772AE1-103 E
Adder
5.00588235294117644.255
3143316POE
Adder
1.19294117647058821.014
3144216WINCHST
50/50
0.20.2
3145256KINGFORK
50/50
1.4051.405
3145506HICKORY
50/50
3.0893.089
3150601CHESTF5
Adder
66.756.695
3150731STONECA
Adder
6.8694117647058835.839
3150921YORKTN3
50/50
185.501185.501
925865AC1-065 E
Adder
22.29058823529411618.947
926472AC1-118 E
Adder
1.13411764705882350.964
926662AC1-147 E
50/50
1.8821.882
926755AC1-161 E
50/50
20.21420.214
927226AC1-216 E
Adder
8.9599999999999997.616
934392AD1-063 E
50/50
1.4751.475
935112AD1-144 E
50/50
1.3041.304
936582AD2-073 E
Adder
1.23176470588235291.047
936591AD2-074 C
Adder
7.2670588235294116.177
936592AD2-074 E
Adder
11.85764705882353110.079
942341AE2-247 C
Adder
1.84117647058823521.565
942342AE2-247 E
Adder
2.54235294117647072.161
943461AF1-017 C
Adder
1.66588235294117641.416
943462AF1-017 E
Adder
2.71882352941176462.311
943612AF1-032 E
Adder
1.2764705882352941.085
943741AF1-042 C
Adder
3.8023529411764713.232
943742AF1-042 E
Adder
6.20470588235294155.274
961951AG1-038 C
Adder
4.20352941176470553.573
961952AG1-038 E
Adder
5.8035294117647064.933
966661AG1-536 C
Adder
6.91529411764705955.878
966662AG1-536 E
Adder
9.2917647058823527.898
3150981CHESPKA
50/50
0.6170.617
3150991CHESPKB
50/50
1.0231.023
3151081ELIZAR1
50/50
4.5444.544
3151091ELIZAR2
50/50
4.4644.464
3151101ELIZAR3
50/50
4.6014.601
3152331SURRY 2
50/50
43.89143.891
316076AC2-137 E
Adder
1.53647058823529431.306
316078AC2-138 E
Adder
1.1482352941176470.976
316157AD2-030 E
Adder
1.6270588235294121.383
913392Y1-086 E
Adder
3.0235294117647062.57
916192Z1-068 E
50/50
2.672.67
923832AB2-022 E
Adder
1.7070588235294121.451
923842AB2-024 E
50/50
2.4762.476
923852AB2-025 E
Adder
1.040.884
939312AE1-162 E
Adder
1.9235294117647061.635
957492AF2-043 E
Adder
1.9635294117647061.669
957601AF2-054 C
Adder
2.92.465
957602AF2-054 E
Adder
1.93294117647058841.643
962861AG1-135 C
Adder
7.8329411764705896.658
962862AG1-135 E
Adder
5.2211764705882354.438
962962AG1-145 E
50/50
2.2212.221
963611AG1-210 C
Adder
0.820.697
963612AG1-210 E
Adder
1.23058823529411781.046
964211AG1-282 C
Adder
2.5270588235294122.148
964212AG1-282 E
Adder
1.6847058823529411.432
901082W1-029 E
Adder
43.0176470588235336.565
917122Z2-027 E
Adder
1.83411764705882341.559
925332AB2-190 E
Adder
8.8411764705882367.515
925522AC1-027 E
50/50
1.7291.729
957831AF2-077 C
50/50
0.4830.483
957832AF2-077 E
50/50
2.0912.091
957871AF2-081 C
50/50
14.02714.027
957872AF2-081 E
50/50
6.0126.012
958161AF2-110 C
Adder
1.81529411764705871.543
958162AF2-110 E
Adder
2.8870588235294122.454
3138116ELKO L286
Adder
1.60117647058823541.361
3141813NORNECK
Adder
1.09294117647058830.929
926071AC1-086 C
Adder
20.14470588235294517.123
926072AC1-086 E
Adder
9.1682352941176477.793
927021AC1-189 C
Adder
8.235294117647067
927022AC1-189 E
Adder
4.1023529411764713.487
933291AC2-141 C
50/50
47.35447.354
933292AC2-141 E
50/50
20.21420.214
939411AE1-173 C
Adder
101.4858823529411986.263
939412AE1-173 E
Adder
67.656470588235357.508
934012AD1-025 E
Adder
11.69.86
916191Z1-068 C
50/50
0.0620.062
933981AD1-022 C
Adder
10.3435294117647068.792
933982AD1-022 E
Adder
5.6317647058823534.787
962572AG1-106 E
Adder
1.140.969
962571AG1-106 C
Adder
2.60588235294117652.215
3130536PAPERMILL
50/50
9.1469.146
3145946PLYMOUTH TP
Adder
0.38941176470588240.331
3146326AYDLETT TAP
50/50
1.8931.893
316036AC1-147 C
50/50
0.5220.522
316059AD1-063 C
50/50
0.360.36
316072AD1-144 C
50/50
0.3890.389
316159AE1-175 C
50/50
0.6010.601
316160AE1-175 E
50/50
1.8321.832
316169AC1-164 GEN
50/50
57.50657.506
316185AD1-033 C
50/50
1.7411.741
316274AC1-208 C
Adder
8.6647058823529427.365
316294AC1-161 C
50/50
7.7117.711
316314AB2-024 C
50/50
0.4030.403
316316AC1-027 C
50/50
0.4470.447
316382AG1-145 C
50/50
0.5420.542
917332KELFORD E
Adder
1.74000000000000021.479
924516AB2-100 E1
Adder
2.6788235294117652.277
924517AB2-100 E2
Adder
2.6788235294117652.277
926206AC1-098 E
Adder
3.5952941176470593.056
926214AC1-099 E
Adder
1.18705882352941171.009
926785AC1-164_E
50/50
25.83625.836
934065AD1-033 E
50/50
7.137.13
937226AE2-253 E
50/50
8.238.23
939612AE1-191 E
Adder
7.76.545
939246AE1-155 E
Adder
11.1941176470588259.515
918512AA1-065 E OP
Adder
6.2364705882352955.301
316017AA1-139 ULT1
50/50
1.5131.513
316018AA1-139 ULT2
50/50
1.5131.513
919153AA1-139 E2
50/50
5.7365.736
919152AA1-139 E1
50/50
5.7365.736
920692AA2-178 E
Adder
5.1082352941176474.342
923994AB2-040_E
Adder
5.7423529411764714.881
924814AB2-134 E
Adder
14.67647058823529312.475
316084AB2-161 E
Adder
6.0352941176470595.13
925122AB2-169 E
Adder
6.3976470588235295.438
316088AB2-174 E
Adder
6.03294117647058855.128
316375AC2-012 C
50/50
1.9131.913
932046AC2-012 E
50/50
18.61318.613
316311AC2-079 C
Adder
7.1458823529411766.074
932596AC2-079 E
Adder
11.6588235294117669.91
934146AD1-041 E
Adder
4.8129411764705894.091
934576AD1-082 E
Adder
4.80941176470588254.088
316349AD2-085 C
Adder
4.2482352941176483.611
936666AD2-085 E
Adder
6.9317647058823545.892
316388AE2-253 GEN
50/50
2.7582.758
961611AG1-000B C
Adder
20.0529411764705917.045
941591AE2-156 C
50/50
25.46125.461
944581AF1-123 C
50/50
65.6165.61
944582AF1-123 E
50/50
150.24150.24
944591AF1-124 C
50/50
65.84465.844
944592AF1-124 E
50/50
150.785150.785
944601AF1-125 C
50/50
64.664.6
944602AF1-125 E
50/50
147.882147.882
944631AF1-128 C
Adder
41.73529411764706535.475
958261AF2-120 C
Adder
8.0388235294117656.833
958262AF2-120 E
Adder
5.3588235294117644.555
3137643SOCKMAN
Adder
0.6764705882352940.575
932632AC2-084 E
Adder
3.17764705882352952.701
934501AD1-074 C
Adder
40.41176470588235534.35
934502AD1-074 E
Adder
20.57176470588235517.486
934511AD1-075 C
Adder
10.102352941176478.587
934512AD1-075 E
Adder
5.1435294117647064.372
935161AD1-151 C
Adder
18.1615.436
935162AD1-151 E
Adder
12.10588235294117610.29
938531AE1-072 C
50/50
24.57324.573
938532AE1-072 E
50/50
12.8112.81
939191AE1-149 C
Adder
10.6576470588235289.059
939192AE1-149 E
Adder
7.1047058823529416.039
939602AE1-190 E
Adder
1.9247058823529411.636
940431AE2-027 C
Adder
10.9364705882352939.296
940432AE2-027 E
Adder
3.88235294117647063.3
940481AE2-033 C
Adder
14.5623529411764712.378
940482AE2-033 E
Adder
9.817647058823538.345
940541AE2-040 C
Adder
2.5717647058823532.186
940551AE2-041 C
Adder
9.8305882352941178.356
940641AE2-051 C
Adder
17.715.045
940642AE2-051 E
Adder
11.79999999999999910.03
941101AE2-104 C
Adder
4.4482352941176473.781
941102AE2-104 E
Adder
7.0717647058823536.011
943471AF1-018 C
Adder
9.8305882352941178.356
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.274.27
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.05913.059
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.06213.062
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
70.8670.86
G-007PJM->LTFIMP_G-007
CMTX_NF
2.7242.724
NYPJM->LTFIMP_NY
CLTF
1.3121.312
LGEELTFEXP_LGEE->PJM
CLTF
0.5530.553
WECLTFEXP_WEC->PJM
CLTF
0.2830.283
CPLELTFEXP_CPLE->PJM
CLTF
8.9638.963
TVALTFEXP_TVA->PJM
CLTF
3.7783.778
MECLTFEXP_MEC->PJM
CLTF
1.9921.992
LAGNLTFEXP_LAGN->PJM
CLTF
4.854.85
SIGELTFEXP_SIGE->PJM
CLTF
0.1170.117
O66PJM->LTFIMP_O-066
CMTX_NF
17.37617.376
CONTINGENCY 'DVP_P1-2: LN 2201_SRT-A'
 OPEN BRANCH FROM BUS 313725 TO BUS 314563 CKT 1   /*6DRY BREAD   230.0 - 6CLUBHSE     230.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
314562 to 314563 ckt 1
314322 to 314914 ckt 1
314903 to 314908 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AG1-106 was evaluated as a 23.0 MW injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

(No impacts were found for this analysis)

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

(No impacts were found for this analysis)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 1 Cluster 39 are listed in Table 1 below. This report will cover the TC1 Phase 3 dynamic analysis of Cluster 39 projects.

 

 

Table 1: Transition Cycle 1 Cluster 39 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO

(MW)

MWE

(MW)

MWC

(MW)

Point of Interconnection

39

AF2-080

Solar

Dominion

150

70

48.5

Chinquapin - Everetts 230 kV

AG1-106

Solar

Dominion

323

23

16

Thelma 230 kV

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 39 projects will meet the dynamics requirements of the NERC, Dominion Energy, and PJM reliability standards.

 

The load flow case finalized for Phase 2 was used as a starting point and was updated based on latest Cluster 39 data, Dominion Energy recommended transmission changes and withdrawn generation. Projects in vicinity of Cluster 39 have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer. The dynamic models for Cluster 39 projects were updated based on the latest DP2 data and include any tuning adjustments recommended during Phase 2.

 

Cluster 39 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. 211 contingencies were studied, each with a 30 second simulation time period. The studied contingencies included:

The contingencies were updated based on topology changes due to any Dominion Energy recommended transmission changes or generation withdrawals.

 

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all of the fault contingencies tested on the RTEP 2027 summer peak case:

 

  • Cluster 39 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  • The system with Cluster 39 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

Oscillations were observed at the Gaston units for contingencies P4.43, P4.48, P4.52, P4.57, and P4.58. These oscillations did not met Dominion’s 4% damping criteria for local area and were observed to be pre-existing but was exacerbated by dispatched generation at Thelma.  The damping angle with changes to the generation dispatched at Thelma. The results indicate that reducing generation in the surrounding area leads to improved damping performance at Gaston and it is concluded that the oscillations at Gaston were not caused by the TC1 Cluster 39 projects.

 

The Transmission Owner has elected to upgrade the Hathaway 115 kV substation by splitting the existing 115 kV bus into two separate buses with a 115 kV line on each bus and the tie switch between line 55 and 80 was closed. Additionally, Line #1001 was opened at Battleboro, resulting in it becoming a radial line from Chestnut Substation. Contingency definitions at the Hathaway 115 kV substation were updated based on topology change, and the analysis was performed. Oscillations at Gaston continue to persist and were unaffected by the topology changes. No other violations occurred.

 

AF2-080 queue project did not meet the 0.95 lagging power factor measured at high side of the main transformer. When the facility was tested at its maximum lagging reactive capability, voltages above 1.10 p.u. were observed at the inverter terminal. To ensure that the facility can provide its lagging power factor without high voltages at the inverter terminal, it is recommended that the tap on the high side of the main transformer be adjusted from 1.0 to 1.025. An additional 5.42 Mvar is required to meet the 0.95 lagging power factor. The AF2-080 queue project met the 0.95 leading power factor measured at high side of the main transformer.

 

AG1-106 is an uprate of AB1-132 and AC1-086. The measurement point for the power factor requirements per the Interconnection Service Agreement (ISA) is at the generator terminals for AB1-132 and AC1-086.  AG1-106’s power factor requirements is measured at the high side of the station transformer.  Due to this three power factor assessments were included to bound the lagging deficiencies observed.  The following lagging deficiencies were observed for AG1-106 depending on the measurement’s points enforced for each test.

 

  • With AG1-106 online, and AB1-132 and AC1-086 offline to ensure the losses created by the AB1-132 and AC1-086 generators are not counted against AG1-106. The facility met the 0.95 lagging and leading power factor requirements measured at the high side of the main transformer.
  • With AG1-106 and AB1-132 online, AC1-086 offline to consider the shared high side of main station transformer. AB1-132’s measurement point in the ISA is not enforced in this test. The facility met the 0.95 lagging and leading power factor requirements measured at the high side of the main transformer. However, voltage violation were observed at the generator terminals with the voltage of 1.196 p.u. at AB1-132 and 1.147 p.u. at AG1-106.
  • AG1-106, AB1-132, and AC1-086 online to consider the shared high side of main station transformer. AB1-132 and AC1-086 measurement point in the ISA are not enforced in this test. The lagging power factor deficiency is 49.38 Mvar.

 

No mitigation was required.

Reactive Power Analysis

The reactive power capability of AG1-106 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-065Earleys 230kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA1-145Four Rivers 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-088Boykins-Handsome 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB1-173Brink-Trego 115kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-100Clubhouse-Lakeview 230kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-065Harmony Village-Shackleford 115kVUnder Construction
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-080Perth-Hickory Grove 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-112Old Church 34.5kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-216Hopewell-Surry 230kVIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-084Dawson-South Justice 115kVPartially in Service - Under Construction
AC2-100Halifax-Person 230kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVPartially in Service - Under Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-149Disputanta-Poe 115 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-247Myrtle-Windsor 115 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-299Fields 34.5 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-153Heritage 500 kVActive
AG1-210Northern Neck 34.5 kVWithdrawn
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-536Garner-Northern Neck 115 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
V4-068Murphy's 34.5kVIn Service
W1-029Winfall 230kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z1-068Birdneck 34.5kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-088Tarboro-Everetts 230kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 312.A.1.b and as outlined in PJM Manual 14H, Section 13, in Phase III of the Cycle, PJM coordinates with the Affected System Operators to conduct any studies required to determine the impact of the New Service Request on any Affected System and will include the Affected System Study results in Phase III System Impact Study, if available from the Affected System Operator.

If your project required an Affected System Study, the results are shown below from the Affected System Operator.

For more details, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM will list any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE) Identified Impacts
Note: Please communicate with the Affected System Operator regarding the status of the Affected System Study for your project.
Impacted FacilityTransmission OwnerReinforcementCostCost Allocated to AG1-106Scenarios
  • Rocky Mount 230.0 - Nash 230.0 CKT 1
  • Rocky Mount 230.0 - Hathaway 230.0 CKT 1
CPLE Reconductor 4.73 miles with bundled 795 ACSS and replace substation components to get 3000A (City of Rocky Mount – Nash 230 kV)
Reconductor 4.73 miles with bundled 795 ACSS and
replace substation components to get 3000A (City
of Rocky Mount – Nash 230 kV)
$14,033,000$971,000
  • Rocky Mount 230.0 - Rocky Mount 115.0 CKT 1
CPLE Replace transformer protection panel, uprate CT ratios, and revise relay settings
Replace transformer protection panel, uprate CT
ratios, and revise relay settings
$619,000$47,000
  • Greenville 230.0 - Everetts 230.0 CKT 1
CPLE Reconductor one side of Everetts to Greenville 230 kV Line. Upgrade the terminal equipment.
Reconductor one side of Everetts to Greenville 230
kV Line. Upgrade the terminal equipment.
$150,000$0
  • Contingent
  • Greenville 230.0 - Everetts 230.0 CKT 1
CPLE Rebuild aging double circuit 230kV towers of Everetts to Greenville Line
Rebuild aging double circuit 230kV towers of
Everetts to Greenville Line
$19,000,000$0
  • Contingent
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG1-106 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn6872Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C.Cost Allocated$8,545,448
Dominionn9200.0Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" conductors.Cost Allocated$5,435,780
Dominionn9204.0Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.Cost Allocated$949,798
Dominionn9201.0Replace wave trap at Carson 230 kV (Carson - Sapony).Cost Allocated$81,355
Dominions2824Rebuild 230 kV Line #2056 from Hornertown to Hathaway.Contingent$0N/A
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Non-Contingent$0N/A
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Non-Contingent$0N/A
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Non-Contingent$0N/A
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Non-Contingent$0N/A
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Non-Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Non-Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Non-Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Non-Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Non-Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Non-Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationNon-Contingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0N/A
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Non-Contingent$0N/A
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Non-Contingent$0N/A
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Non-Contingent$0N/A
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Non-Contingent$0N/A
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Non-Contingent$0N/A
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Non-Contingent$0N/A
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Non-Contingent$0N/A
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Non-Contingent$0N/A
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Non-Contingent$0N/A
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Non-Contingent$0N/A
Dominionn8492.1Two Breaker Additions at Fentress Substation.Non-Contingent$0N/A
Grand Total:$15,012,381

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n6872
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6872 / dom-047
Title
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C.
Description
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C
Total Cost ($USD)
$59,572,939
Discounted Total Cost ($USD)
$59,572,939
Allocated Cost ($USD)
$8,545,448
Time Estimate
Dec 31 2029

Contributor

FacilityContingency
6CLUBHSE-AE2-033 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1168.0 MVA
(All)B1195.0 MVA
(All)C1348.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-04224.3 MW40.2%$23,940,647
AF2-08013.0 MW21.4%$12,754,165
AF2-2227.6 MW12.5%$7,438,616
AG1-1068.7 MW14.3%$8,545,448
AG1-2857.0 MW11.6%$6,894,063

System Reinforcement: n9200.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9200.0 / TC1-PH2-DOM-005
Title
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" conductors.
Description
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$38,691,326
Discounted Total Cost ($USD)
$38,691,326
Allocated Cost ($USD)
$5,435,780
Time Estimate
45 to 46 Months

Contributor

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA797.0 MVA
SUMB797.0 MVA
SUMC1115.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-04224.3 MW39.3%$15,216,675
AF2-08012.9 MW21.0%$8,110,757
AF2-2228.6 MW14.0%$5,405,710
AG1-1068.7 MW14.0%$5,435,780
AG1-2857.2 MW11.7%$4,522,403

System Reinforcement: n9204.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9204.0 / TC1-PH2-DOM-014
Title
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C
Total Cost ($USD)
$6,764,273
Discounted Total Cost ($USD)
$6,764,273
Allocated Cost ($USD)
$949,798
Time Estimate
42 to 43 Months

Contributor

FacilityContingency
6SAPONY-AE2-033 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA876.0 MVA
SUMB956.0 MVA
SUMC1163.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-04224.3 MW39.3%$2,660,923
AF2-08013.0 MW21.0%$1,417,583
AF2-2228.6 MW14.0%$945,201
AG1-1068.7 MW14.0%$949,798
AG1-2857.2 MW11.7%$790,769

System Reinforcement: n9201.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9201.0 / TC1-PH2-DOM-006
Title
Replace wave trap at Carson 230 kV (Carson - Sapony).
Description
Replace wave trap at Carson 230 kV (Carson - Sapony).
Total Cost ($USD)
$521,941
Discounted Total Cost ($USD)
$521,941
Allocated Cost ($USD)
$81,355
Time Estimate
14 to 15 Months

Contributor

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA876.0 MVA
SUMB956.0 MVA
SUMC1163.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF2-04224.3 MW43.6%$227,742
AF2-0806.9 MW12.3%$64,253
AF2-2228.6 MW15.5%$80,905
AG1-1068.7 MW15.6%$81,355
AG1-2857.2 MW13.0%$67,685

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
Dominion facility ratings: 379/390/449 MVA Winter | 372/384/441 MVA LL | 342/352/405 MVA Summer.
Description
Dominion facility ratings: 379/390/449 MVA Winter | 372/384/441 MVA LL | 342/352/405 MVA Summer.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
3ROCKYMT115T-3BTLEBRO 115.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA342.0 MVA
SUMB352.0 MVA
SUMC405.0 MVA

System Reinforcement: n9112.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9112.0 / TC1-PH2-DOM-063
Title
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Description
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Total Cost ($USD)
$87,030,447
Discounted Total Cost ($USD)
$87,030,447
Allocated Cost ($USD)
$0
Time Estimate
46 to 47 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-106 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-106 could receive cost allocation. Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 is a potential Aggregate Pool Contributor.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A797.0 MVA
(All)B797.0 MVA
(All)C1115.0 MVA

System Reinforcement: n9265.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9265.0 / TC1-PH2-DOM-064
Title
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Description
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Total Cost ($USD)
$396,021
Discounted Total Cost ($USD)
$396,021
Allocated Cost ($USD)
$0
Time Estimate
14 to 15 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-106 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-106 could receive cost allocation. Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 is a potential Aggregate Pool Contributor.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A876.0 MVA
(All)B956.0 MVA
(All)C1163.0 MVA

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Discounted Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-106 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-106 could receive cost allocation. Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 is a potential Aggregate Pool Contributor.

FacilityContingency
6BUCKING-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A796.0 MVA
(All)B796.0 MVA
(All)C964.0 MVA

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Discounted Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-106 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-106 could receive cost allocation. Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 is a potential Aggregate Pool Contributor.

FacilityContingency
6BUCKING-6FARMVIL 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A797.0 MVA
(All)B797.0 MVA
(All)C1116.0 MVA

System Reinforcement: n9681.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9681.0
Title
Upgrade 1.04 Miles of 230kV transmission line 249 from 249/86 to 249/93
Description
Reconductor 1.04 miles of 2*636 ACSR 24/7 MOT 150 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" MOT 250 on 230 kV line 249 between Carson and Chaparral
Total Cost ($USD)
$3,042,004
Discounted Total Cost ($USD)
$3,042,004
Allocated Cost ($USD)
$0
Time Estimate
20 to 21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-106 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-106 could receive cost allocation. Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1442.0 MVA
LLB1540.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1493.0 MVA
WINB1587.0 MVA
WINC1631.0 MVA

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1047.0 MVA
(All)B1047.0 MVA
(All)C1204.0 MVA
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA

System Reinforcement: s3222.1
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3222.1
Title
Rebuild approximately 44.3 miles of 230kV Line #246 between Earleys and Suffolk to current 230kV standards. The normal rating of the line conductor will be 1573 MVA.
Description
Rebuild approximately 44.3 miles of 230kV Line #246 between Earleys and Suffolk to current 230kV standards. The normal rating of the line conductor will be 1573 MVA.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG1-106 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1809.0 MVA
6SUFFOLK-6NUCO TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1195.0 MVA
(All)B1195.0 MVA
(All)C1673.0 MVA

System Reinforcement: n9252.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9252.0 / TC1-PH2-DOM-047
Title
Rebuild 3.81 miles of Line 2021 between Elizabeth City and Shawboro with double bundled (2) 768.2 ACSS/TW (20/7) "Maumee" conductor.
Description
Rebuild 3.81 miles of Line 2021 between Elizabeth City and Shawboro, specifically, between structures 2021/31 and 2021/62, with double bundled (2) 768.2 ACSS/TW (20/7) "Maumee" conductor at 250 degrees C.
Total Cost ($USD)
$12,801,638
Discounted Total Cost ($USD)
$12,801,638
Allocated Cost ($USD)
$0
Time Estimate
15 to 16 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-106 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-106 could receive cost allocation. Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 is a potential Aggregate Pool Contributor.

FacilityContingency
6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1167.0 MVA
(All)B1195.0 MVA
(All)C1348.0 MVA

System Reinforcement: n9207.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9207.0 / TC1-PH2-DOM-018
Title
Replace 6ELMONT 230 kV to 8ELMONT 500 kV circuit 1 with larger transformer (3-480 MVA single phase transformer).
Description
Replace 6ELMONT 230 KV to 8ELMONT 500 kV ckt 1 with Larger XFRM. (3-480 MVA Single Phase XFRM).
Total Cost ($USD)
$38,254,469
Discounted Total Cost ($USD)
$38,254,469
Allocated Cost ($USD)
$0
Time Estimate
59 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-106 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-106 could receive cost allocation. Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 is a potential Aggregate Pool Contributor.

FacilityContingency
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA

System Reinforcement: s2824
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s2824
Title
Rebuild 230 kV Line #2056 from Hornertown to Hathaway.
Description
Rebuild approximately 28.9 miles of Line #2056 Hornertown to Hathaway with current 230kV standard construction practices. The new conductor will have a minimum normal summer rating of 1573 MVA. Terminal equipment will be upgraded as needed. Projected ISD: 12/31/2026
Cost Information
Time Estimate
Dec 31 2026

Contingent

Note: Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 may need this upgrade in-service to be deliverable to the PJM system. If AG1-106 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6HATHAWAY-AD1-056 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1809.0 MVA
6HORNRTN-AD1-056 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1809.0 MVA

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Discounted Total Cost ($USD)
$37,836,293
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-106 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-106 could receive cost allocation. Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 is a potential Aggregate Pool Contributor.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not ContingentTopology Changing

Note 1: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not ContingentTopology Changing

Note 1: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6WINFALL-6S HERTFORD 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.315
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.315
Title
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Description
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Apr 22 2030

Not Contingent

Note: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Discounted Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-106 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-106 could receive cost allocation. Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b3692
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3692
Title
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.
Description
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy with current 500 kV standards construction practices to achieve a summer rating of 4330 MVA. Projected ISD: 06/01/2026
Cost Information
Time Estimate
Jun 01 2026

Not Contingent

Note: AG1-106 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-106 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4330.0 MVA
(All)B4330.0 MVA
(All)C5011.0 MVA

System Reinforcement: n9264.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9264.0 / TC1-PH1-DOM-080
Title
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Description
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Total Cost ($USD)
$582,006
Discounted Total Cost ($USD)
$582,006
Allocated Cost ($USD)
$0
Time Estimate
12 to 13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-106 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-106 could receive cost allocation. Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 is a potential Aggregate Pool Contributor.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2650.0 MVA
(All)B2831.0 MVA
(All)C3663.0 MVA

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Discounted Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-106 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-106 could receive cost allocation. Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-040
Title
ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 18.75 miles of Line 594 between Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$128,018,212
Discounted Total Cost ($USD)
$128,018,212
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-106 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-106 could receive cost allocation. Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9247.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9247.0 / TC1-PH2-DOM-041
Title
ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 14.02 miles of Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA
Total Cost ($USD)
$99,636,684
Discounted Total Cost ($USD)
$99,636,684
Allocated Cost ($USD)
$0
Time Estimate
48 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-106 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-106 could receive cost allocation. Although AG1-106 may not presently have cost responsibility for this upgrade, AG1-106 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n8492.2

AG1-106 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Allocated Cost ($USD)
$0
Time Estimate
15 to 16 Months
Cost Alloc Type
Non-Contingent

System Reinforcement: n9259.0

AG1-106 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Allocated Cost ($USD)
$0
Time Estimate
38 to 39 Months
Cost Alloc Type
Non-Contingent

System Reinforcement: n9267.0

AG1-106 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months
Cost Alloc Type
Non-Contingent

System Reinforcement: n9630.0

AG1-106 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.325

AG1-106 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: s3047.2

AG1-106 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s3047.2
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3047.2
Title
Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.
Description
Install (2) 1400 MVA 500-230 kV transformers and associated 500 kV and 230 kV equipment (breakers, switches, leads) at Vint Hill Substation to supply the area with a 500 kV source Cut and loop 500 kV line #535 Loudoun – Meadowbrook and #569 Loudoun - Morrisville as the 500 kV sources into the proposed 500 kV ring bus Vint Hill Substation will be expanded to the north of the existing site to accommodate the 500 kV ring required for the addition of the new transformers Existing terminations for 230 kV line #2174 Wheeler – Vint Hill, line #2101 Bristers – Vint Hill, and line #2163 Liberty – Vint Hill will be rearranged to terminate into the expanded Vint Hill Substation 230 kV line #2114 Remington CT – Rollins Ford will also be cut and looped into the expanded Vint Hill Substation due to spatial constraints along the existing right-of-way.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.312

AG1-106 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.313

AG1-106 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.313
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.313
Title
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Description
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.356

AG1-106 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.356
Title
Build a new 500 kV line from Vint Hill to Wishing Star.
Description
Build a new 500kV line from Vint Hill to Wishing Star. The line will be supported on single circuit monopoles. New conductor to have a summer rating of 4357 MVA. Line length is approximately 16.59 miles
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.357

AG1-106 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.357
Title
Build a new 500 kV line from Morrisville to Vint Hill.
Description
Build a new 500kV line from Morrisville to Vint Hill. New conductor to have a summer rating of 4357 MVA. Line length is approximately 19.71 miles.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.354

AG1-106 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.354
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.354
Title
Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.
Description
Install terminal equipment at Wishing Star substation to support a 5000A line to Vint Hill. Update relay settings for 500kV Lines #546 and #590.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: n8492

AG1-106 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Allocated Cost ($USD)
$0
Time Estimate
26 to 27 Months
Cost Alloc Type
Non-Contingent

System Reinforcement: n8492.1

AG1-106 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months
Cost Alloc Type
Non-Contingent

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG1-106


AG1-106 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AG1-106 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Non-Contingent$0
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Non-Contingent$0
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Non-Contingent$0
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Non-Contingent$0
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Non-Contingent$0
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Non-Contingent$0
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Non-Contingent$0
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Non-Contingent$0
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Non-Contingent$0
Dominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Non-Contingent$0
Dominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationNon-Contingent$0
Dominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Non-Contingent$0
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Non-Contingent$0
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Non-Contingent$0
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Non-Contingent$0
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Non-Contingent$0
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Non-Contingent$0
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Non-Contingent$0
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Non-Contingent$0
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Non-Contingent$0
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Non-Contingent$0
Dominionn8492.1Two Breaker Additions at Fentress Substation.Non-Contingent$0
Region Topology Upgrade Total:$0

Attachments

AG1-106 One Line Diagram

AG1-106 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.