AG1-124 Final System Impact Study (Retool 1) Report

v1.00 released 2025-12-08 18:21

Gladstone 138 kV

53.01 MW Capacity / 90.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Wild Rose Solar Project, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Appalachian Power Company.

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the TC1 projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.
Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of TC1 projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Solar generating facility located in the Appalachian Power Company zone — Nelson County, Virginia. The installed facilities will have a total capability of 90.0 MW with 53.01 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG1-124
Project Name:
Gladstone 138 kV
Project Developer Name:
Wild Rose Solar Project, LLC
State:
Virginia
County:
Nelson
Transmission Owner:
Appalachian Power Company
MFO:
90.0
MWE:
90.0
MWC:
53.01
Fuel Type:
Solar
Basecase Study Year:
2027

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG1-124 will interconnect on the AEP Appalachian Power Company transmission system via a newly constructed 138 kV station tapping the Riverville - Gladstone 138 kV line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AG1-124 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AG1-124Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$1,838,092$1,838,092
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$7,960,528$7,960,528
Network Upgrades$2,115,949$2,115,949
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$7,818,051$7,818,051
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$19,732,620$19,732,620

* Contributes to calculation for Security. See Security Section of this report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AG1-124

Security has been calculated for the AG1-124 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AG1-124
Project(s): AG1-124
Final Agreement Security (A): $19,732,620
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $19,732,620
Security on Hand with PJM (D): $23,074,006
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

AG1-124 will interconnect with the AEP transmission system via a new station cut into the Riverville - Gladstone 138 kV Circuit. The estimates provided in this report are preliminary in nature, as they were determined without the benefit of detailed engineering studies. Final estimates will require an on-site review and coordination to determine final construction requirements.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9536.0

Riverville - Gladstone 138 kV Circuit: New AG1-124 138 kV Switching Station tie-in. Install two (2) new steel, 75', double circuit, two-pole dead-end structures on concrete piers with anchor bolt cages, and three (3) spans of ACSR 795 26/7 (Drake) transmission line conductor with 7#8 Alumoweld shield wire in the existing Riverville - Gladstone 138 kV Right of Way, cutting in the New AG1-124 138 kV Station in an in-and-out arrangement from an existing structure.

$1,180,398$271,140$246,708$56,669$1,754,915$1,754,915
n9534.0

Riverville - Gladstone 138 kV and New AG1-124 138 kV Switching Station: Final Tie in for Fiber installation.

$274,711$34,898$45,211$6,214$361,034$361,034
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9537.0

Riverville - Gladstone 138 kV Circuit: Construct a new 138 kV ring bus station; initially populated with three (3) circuit breakers, expandable to four (4) breakers. • Three (3) 138 kV 40 kA circuit breakers with associated control relaying. • One (1) 16' x 27' DICM. • Six (6) breaker disconnect switches. • Three (3) line disconnect motor operated air breaker (MOAB) switches with associated control relaying, one (1) each on the line exits to the AG1-124 collector, Gladstone 138 kV, and Riverville 138 kV stations. • Six (6) single phase CCVTs, three (3) each on the line exits to the Riverville and Gladstone 138 kV Stations. • Two (2) single phase station service voltage transformers (SSVT). • Two (2) Monopole dead-end take off structures, one (1) each for the line exits to Riverville and Gladstone 138 kV Stations. • A direct fiber current differential line protection relay scheme for the line to the Riverville 138 kV Station. • A direct fiber current differential line protection relay scheme for the line to the Gladstone 138 kV Station. • Associated conductors (buswork, ground grid, jumpers), telecom terminal equipment, insulators, arresters, foundations, and structures.

$4,206,032$2,521,702$503,150$301,661$7,532,545$7,532,545
n9535.0

New AG1-124 138 kV Switching Station: Install two (2) station exit transitions and two (2) new fiber optic cable paths, one (1) consisting of 0.3 miles of underground ADLT cable and the other consisting of 0.1 miles of optical ground wire (OPGW) fiber optic shield wire.

$322,644$51,611$46,319$7,409$427,983$427,983
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

• Installation of one (1) new steel, 85’, single circuit, single pole dead end structure and one span of aluminum conductor steel-reinforced (ACSR) 795 26/7 (Drake) transmission line conductor with 7#8 Alumoweld shield wire for the generation lead circuit extending from the New AG1-124 138 kV Switching Station. • Extension of two (2) underground all dielectric loose tube (ADLT) fiber optic cables from the New AG1-124 138 kV Switching Station control house to fiber demarcation splice boxes to support direct fiber relaying between the New AG1-124 138 kV and Project Developer's collector stations. • Installation of one (1) Monopole dead-end take off structure for the generation lead circuit line exit. • Installation of three (3) single phase coupling capacitor voltage transformers (CCVTs) on the generation lead circuit. • Installation of a dual, direct-fiber, current differential protection scheme for the generation lead circuit. • Installation of a standard revenue metering package, including three (3) single phase current transformers (CT), three (3) single phase voltage transformers (VT), associated structures and foundations, one (1) ethernet switch, and one (1) drop in control module (DICM)-installed metering panel, for the generation lead circuit at the New AG1-124 138 kV Switching Station.

$1,086,495$487,514$185,291$78,792$1,838,092$1,838,092

Based on the scope of work for the Interconnection Facilities, it is expected to take 26 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

The minimum and maximum schedules reflect the amount of time, in months, that AEP projects their portion of the construction project scope elapsing from the time of agreement. Final agreements will reflect an "on or before" date, allowing all parties to c, including remote end work, considering the Project Developer selection of the Option To Build, allocating the long lead material ordering as part of the Project Developer scope. The maximum schedule is based off of AEP assumed long lead material ordering not considering allocation of existing material production slots, advanced progress enabled by Engineering and Procurement Agreements, or other schedule expediting methods. AEP may be able to allocate material production slots for long lead time materials to expedite this schedule. Final agreements will reflect an "on or before" date, allowing all parties to complete their scope of work prior to the agreement date, should there be means to expedite. Any material ordering or construction work done prior to Engineering and Procurement or Generation Interconnection Agreements is done solely at the Project Developers risk. There is a potential that any work done or materials ordered prior to these agreements and the ensuing detailed engineering processes does not meet AEP specifications, resulting in rejection of the completed work.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG1-124 was evaluated as a 90.0 MW (53.01 MW Capacity) injection in the AEP area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP/DVP
AE1-108 TP-4BREMO 138.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-A
BreakerAC148.6 %167.0B248.1611.27
GD1AEP/DVP
AE1-108 TP-4BREMO 138.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC147.33 %167.0B246.0311.27
GD1AEP/DVP
AE1-108 TP-4BREMO 138.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC118.01 %167.0B197.076.64

Details for AE1-108 TP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
AE1-108 TP-4BREMO 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.6 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:248.16
MW Contribution:11.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926646AC1-145 E
Adder
0.8717647058823530.741
942671AE2-283 C
Adder
1.4317647058823531.217
942672AE2-283 E
Adder
1.27882352941176471.087
941011AE2-092 C
Adder
-6.147058823529411-5.225
941801AE2-185 C
Adder
1.84117647058823521.565
941802AE2-185 E
Adder
1.22705882352941181.043
958131AF2-107 C
50/50
9.4419.441
958132AF2-107 E
50/50
5.1745.174
962751AG1-124 C
50/50
6.6376.637
962752AG1-124 E
50/50
4.6314.631
926516AC1-122_E
Adder
1.3564705882352941.153
925665AC1-042 E
Adder
1.3317647058823531.132
938821AE1-108 C
50/50
63.27263.272
938822AE1-108 E
50/50
30.1930.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.48215.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.6516.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.7437.743
G-007PJM->LTFIMP_G-007
CMTX_NF
0.5810.581
NYPJM->LTFIMP_NY
CLTF
0.2430.243
LGEELTFEXP_LGEE->PJM
CLTF
0.6190.619
WECLTFEXP_WEC->PJM
CLTF
0.3120.312
CPLELTFEXP_CPLE->PJM
CLTF
0.3510.351
TVALTFEXP_TVA->PJM
CLTF
1.5161.516
MECLTFEXP_MEC->PJM
CLTF
1.5521.552
LAGNLTFEXP_LAGN->PJM
CLTF
1.8021.802
SIGELTFEXP_SIGE->PJM
CLTF
0.1070.107
O66PJM->LTFIMP_O-066
CMTX_NF
3.6833.683
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.1720.172

Details for AE1-108 TP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
AE1-108 TP-4BREMO 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.33 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:246.03
MW Contribution:11.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926646AC1-145 E
Adder
0.87294117647058820.742
942671AE2-283 C
Adder
1.43294117647058821.218
942672AE2-283 E
Adder
1.27882352941176471.087
941011AE2-092 C
Adder
-6.140000000000001-5.219
941801AE2-185 C
Adder
1.84235294117647071.566
941802AE2-185 E
Adder
1.2282352941176471.044
958131AF2-107 C
50/50
9.4429.442
958132AF2-107 E
50/50
5.1745.174
962751AG1-124 C
50/50
6.6386.638
962752AG1-124 E
50/50
4.6324.632
926516AC1-122_E
Adder
1.3564705882352941.153
925665AC1-042 E
Adder
1.33294117647058831.133
938821AE1-108 C
50/50
63.27863.278
938822AE1-108 E
50/50
30.19330.193
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.49515.495
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.6596.659
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.7747.774
G-007PJM->LTFIMP_G-007
CMTX_NF
0.580.58
NYPJM->LTFIMP_NY
CLTF
0.2430.243
LGEELTFEXP_LGEE->PJM
CLTF
0.620.62
WECLTFEXP_WEC->PJM
CLTF
0.3120.312
CPLELTFEXP_CPLE->PJM
CLTF
0.3550.355
TVALTFEXP_TVA->PJM
CLTF
1.5181.518
MECLTFEXP_MEC->PJM
CLTF
1.5541.554
LAGNLTFEXP_LAGN->PJM
CLTF
1.8051.805
SIGELTFEXP_SIGE->PJM
CLTF
0.1070.107
O66PJM->LTFIMP_O-066
CMTX_NF
3.6773.677
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.1740.174

Details for AE1-108 TP-4BREMO 138.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
AE1-108 TP-4BREMO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.01 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:197.07
MW Contribution:6.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
942671AE2-283 C
80/20
1.4331.433
24288905REUSENS
80/20
0.0550.055
941011AE2-092 C
Adder
-6.135294117647059-5.215
941801AE2-185 C
80/20
1.8421.842
958131AF2-107 C
80/20
9.4439.443
962751AG1-124 C
80/20
6.6386.638
316217AC1-145 C
80/20
0.1580.158
270173AC1-122 C
80/20
0.470.47
316197AC1-042 C
80/20
0.1330.133
938821AE1-108 C
80/20
63.2863.28
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.49715.497
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.666.66
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.7787.778
NYPJM->LTFIMP_NY
CLTF
0.2430.243
LGEELTFEXP_LGEE->PJM
CLTF
0.620.62
WECLTFEXP_WEC->PJM
CLTF
0.3120.312
CPLELTFEXP_CPLE->PJM
CLTF
0.3550.355
TVALTFEXP_TVA->PJM
CLTF
1.5181.518
MECLTFEXP_MEC->PJM
CLTF
1.5541.554
LAGNLTFEXP_LAGN->PJM
CLTF
1.8051.805
SIGELTFEXP_SIGE->PJM
CLTF
0.1070.107
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.1740.174
CONTINGENCY 'DVP_P4-2: 547T566_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314901 TO BUS 314987 CKT 1   /*8BATH CO     500.0 - 8LEXINGTN SC 500.0
 OPEN BRANCH FROM BUS 314912 TO BUS 314987 CKT 1   /*8LEXNGTN     500.0 - 8LEXINGTN SC 500.0
 OPEN BUS 314987                                   /*8LEXINGTN SC 500.0
END
CONTINGENCY 'DVP_P4-2: 56602_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1   /*6LEXNGT2     230.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
938820 to 314746 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP/DVP
AE1-108 TP-4BREMO 138.0 kV Ckt 1 line
AEP_P1-2_242515_248184_SRT-A
OPAC108.59 %167.0B181.3410.24

Details for AE1-108 TP-4BREMO 138.0 kV Ckt 1 line l/o AEP_P1-2_242515_248184_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
AE1-108 TP-4BREMO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_242515_248184_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.59 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:181.34
MW Contribution:10.24
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
941011AE2-092 C
Adder
-5.4282352941176475-4.614
958131AF2-107 C
50/50
9.29.2
958132AF2-107 E
50/50
5.0425.042
962751AG1-124 C
50/50
6.0336.033
962752AG1-124 E
50/50
4.214.21
938821AE1-108 C
50/50
63.45263.452
938822AE1-108 E
50/50
30.27630.276
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.1838.183
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.4283.428
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.4653.465
G-007PJM->LTFIMP_G-007
CMTX_NF
0.3050.305
NYPJM->LTFIMP_NY
CLTF
0.1250.125
LGEELTFEXP_LGEE->PJM
CLTF
0.3260.326
WECLTFEXP_WEC->PJM
CLTF
0.1650.165
CPLELTFEXP_CPLE->PJM
CLTF
0.1050.105
TVALTFEXP_TVA->PJM
CLTF
0.7720.772
MECLTFEXP_MEC->PJM
CLTF
0.8120.812
LAGNLTFEXP_LAGN->PJM
CLTF
0.9150.915
SIGELTFEXP_SIGE->PJM
CLTF
0.0560.056
O66PJM->LTFIMP_O-066
CMTX_NF
1.9291.929
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0530.053
CONTINGENCY 'AEP_P1-2_242515_248184_SRT-A'
 OPEN BRANCH FROM BUS 242515 TO BUS 248184 CKT 1   /*05JOSHUA     765.0 - 05YEAT7      765.0
END
938820 to 314746 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P1-2_#5366_42_SRT-A-1
OPAC100.93 %285.76B288.415.92
GD1DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P1-2_#5366_42_SRT-A-1
OPAC101.1 %285.76B288.915.92
GD1AEP/DVP
AE1-108 TP-4BREMO 138.0 kV Ckt 1 line
Base Case
OPAC107.39 %167.0A179.3410.24

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P1-2_#5366_42_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#5366_42_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.93 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:288.41
MW Contribution:5.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
24728405LEESVG
50/50
1.3291.329
3151561HALLBR1
50/50
2.242.24
926646AC1-145 E
50/50
3.7973.797
942671AE2-283 C
50/50
6.2366.236
942672AE2-283 E
50/50
5.5685.568
942751AE2-291 C
50/50
30.9430.94
942752AE2-291 E
50/50
20.62720.627
940081AE1-250 C
50/50
10.17910.179
940082AE1-250 E
50/50
6.7866.786
941801AE2-185 C
50/50
8.0188.018
941802AE2-185 E
50/50
5.3455.345
24684305SMG1
50/50
1.1971.197
24684405SMG2
50/50
3.2973.297
24684505SMG3
50/50
2.0262.026
24684605SMG4
50/50
3.2973.297
24684705SMG5
50/50
1.2521.252
316003AC1-222 C
50/50
5.0075.007
926055AC1-083 E
50/50
8.4158.415
927264AC1-222 E
50/50
20.52320.523
962751AG1-124 C
Adder
3.48588235294117642.963
962752AG1-124 E
Adder
2.43294117647058842.068
316217AC1-145 C
50/50
0.6890.689
270197AC1-083 C
50/50
0.840.84
270173AC1-122 C
50/50
0.890.89
926516AC1-122_E
50/50
2.5722.572
316197AC1-042 C
50/50
0.5790.579
925665AC1-042 E
50/50
5.85.8
316123AC1-075 C
50/50
3.5893.589
925997AC1-075 E
50/50
12.4912.49
316205AC1-080 C
50/50
1.1991.199
926024AC1-080 E
50/50
4.1444.144
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.3476.347
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.451.45
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
0.2550.255
NYPJM->LTFIMP_NY
CLTF
0.0970.097
LGEELTFEXP_LGEE->PJM
CLTF
0.2620.262
WECLTFEXP_WEC->PJM
CLTF
0.1270.127
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.7150.715
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2460.246
TVALTFEXP_TVA->PJM
CLTF
0.1930.193
MECLTFEXP_MEC->PJM
CLTF
0.5260.526
LAGNLTFEXP_LAGN->PJM
CLTF
0.1510.151
SIGELTFEXP_SIGE->PJM
CLTF
0.0410.041
O66PJM->LTFIMP_O-066
CMTX_NF
1.6111.611
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.2571.257

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P1-2_#5366_42_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#5366_42_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:101.1 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:288.91
MW Contribution:5.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
24728405LEESVG
50/50
1.3291.329
3151561HALLBR1
50/50
2.242.24
926646AC1-145 E
50/50
3.7973.797
942671AE2-283 C
50/50
6.2366.236
942672AE2-283 E
50/50
5.5685.568
942751AE2-291 C
50/50
30.9430.94
942752AE2-291 E
50/50
20.62720.627
940081AE1-250 C
50/50
10.17910.179
940082AE1-250 E
50/50
6.7866.786
941801AE2-185 C
50/50
8.0188.018
941802AE2-185 E
50/50
5.3455.345
24684305SMG1
50/50
1.1971.197
24684405SMG2
50/50
3.2973.297
24684505SMG3
50/50
2.0262.026
24684605SMG4
50/50
3.2973.297
24684705SMG5
50/50
1.2521.252
316003AC1-222 C
50/50
5.0075.007
926055AC1-083 E
50/50
8.4158.415
927264AC1-222 E
50/50
20.52320.523
962751AG1-124 C
Adder
3.48588235294117642.963
962752AG1-124 E
Adder
2.43294117647058842.068
316217AC1-145 C
50/50
0.6890.689
270197AC1-083 C
50/50
0.840.84
270173AC1-122 C
50/50
0.890.89
926516AC1-122_E
50/50
2.5722.572
316197AC1-042 C
50/50
0.5790.579
925665AC1-042 E
50/50
5.85.8
316123AC1-075 C
50/50
3.5893.589
925997AC1-075 E
50/50
12.4912.49
316205AC1-080 C
50/50
1.1991.199
926024AC1-080 E
50/50
4.1444.144
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.3476.347
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.451.45
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
0.2550.255
NYPJM->LTFIMP_NY
CLTF
0.0970.097
LGEELTFEXP_LGEE->PJM
CLTF
0.2620.262
WECLTFEXP_WEC->PJM
CLTF
0.1270.127
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.7150.715
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2460.246
TVALTFEXP_TVA->PJM
CLTF
0.1930.193
MECLTFEXP_MEC->PJM
CLTF
0.5260.526
LAGNLTFEXP_LAGN->PJM
CLTF
0.1510.151
SIGELTFEXP_SIGE->PJM
CLTF
0.0410.041
O66PJM->LTFIMP_O-066
CMTX_NF
1.6111.611
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.2571.257

Details for AE1-108 TP-4BREMO 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
AE1-108 TP-4BREMO 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.39 %
Rating:167.0 MVA
Rating Type:A
MVA to Mitigate:179.34
MW Contribution:10.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
941011AE2-092 C
Adder
-5.444705882352942-4.628
958131AF2-107 C
50/50
9.1979.197
958132AF2-107 E
50/50
5.045.04
962751AG1-124 C
50/50
6.0316.031
962752AG1-124 E
50/50
4.2084.208
938821AE1-108 C
50/50
63.43463.434
938822AE1-108 E
50/50
30.26730.267
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.1898.189
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.413.41
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.3233.323
G-007PJM->LTFIMP_G-007
CMTX_NF
0.2970.297
NYPJM->LTFIMP_NY
CLTF
0.1210.121
LGEELTFEXP_LGEE->PJM
CLTF
0.3260.326
WECLTFEXP_WEC->PJM
CLTF
0.1650.165
CPLELTFEXP_CPLE->PJM
CLTF
0.0870.087
TVALTFEXP_TVA->PJM
CLTF
0.7650.765
MECLTFEXP_MEC->PJM
CLTF
0.810.81
LAGNLTFEXP_LAGN->PJM
CLTF
0.9070.907
SIGELTFEXP_SIGE->PJM
CLTF
0.0560.056
O66PJM->LTFIMP_O-066
CMTX_NF
1.8821.882
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0440.044
CONTINGENCY 'AEP_P1-2_#5366_42_SRT-A-1'
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 314668 CKT Z1   /*05BANSTR     138.0 - 4BANISTR     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 940080 CKT 1    /*05BANSTR     138.0 - AE1-250 TP   138.0
END
313168 to 314696 ckt 1
316000 to 313168 ckt 1
938820 to 314746 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AG1-124 was evaluated as a 90.0 MW injection in the AEP area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests AG1-124 and AG1-494 in PJM Transition Cycle 1, Cluster 54 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 54 projects.

 

This analysis is effectively a screening study to determine whether the addition of the cluster 54 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

The load flow scenario for the analysis was based on the RTEP 2027 summer peak load case, modified to include applicable projects. Cluster 54 projects have been dispatched online at maximum power output, with 1.0 voltage at the terminal bus.

 

Cluster 54 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 111 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

       a)       Steady-state operation (20 second run),

       a)       Three-phase faults with normal clearing time; (and with unsuccessful high-speed reclosing),

       b)       Single-phase bus faults with normal clearing time,

       c)       Single-phase faults with stuck breaker,

       d)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure,

       e)       Three-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing).

 

For all simulations, the queue projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all of the fault contingencies tested on the 2027 peak load case:

       a)       Cluster 54 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 54 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

AG1-124 and AG1-494 meet the 0.95 leading and lagging PF requirement.

The composite short-circuit ratio (CSCR) assessment was performed forinverter-based renewable generation units which are within one (1) substation away AG1-124 and AG1-494. CSCR results are summarized in Table 4 to Table 9 and revealed a minimum and maximum CSCR values of 3.99 for P1.16 and 6.08 for P4.21 & P4.22, respectively.

 

High voltage spikes occurred in the simulations immediately after fault clearing for some of the contingencies studied (i.e. fault where spike is observed]). The voltage spike is a known artifact of the WECC generic renewable models as stated in the WECC Solar Plant Dynamic Model Guidelines: “It should be noted that generic dynamic models for inverter-based generator tend to produce a short-duration (a cycle or shorter) voltage spike at fault inception and clearing. These spikes should be ignored in most cases, as they do not represent the performance of actual hardware. They are simply a consequence of the model’s limited bandwidth, integration time step, and the way current injection models interface with the network solution.” 

 

The IPCMD and IQCMD states in the REGCA1 model of AG1-494 GEN, and AG1-124 GEN showed erratic behavior for some contingencies in which these generators have been disconnected as part of the contingency event. Since the machine is disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

Non-queue project AE1-108:

 

In the previous phase (phase 2) of the dynamic simulation analysis for Cluster 54, the relay pick-up time of AE1-108, instance 93882501 (VTGTPAT) was adjusted to 0.25 seconds to prevent tripping under one contingency. For this phase of the study (phase 3) the relay pick-up time for 93882501 (VTGTPAT) of AE1-108 was restored to original setting 0.0 seconds. No trippings of this unit were observed in this study.

 

No mitigations were found to be required.

Table 1: TC1 Cluster 54 Projects

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

54

AG1-124

Solar

AEP

90

90

53.01

Gladstone 138 kV

AG1-494

Battery

AEP

50

50

20

Boxwood-Amherst 138 kV

 

 

 

Reactive Power Analysis

The reactive power capability of AG1-124 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

(No dependencies were identified)

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 312.A.1.b and as outlined in PJM Manual 14H, Section 13, in Phase III of the Cycle, PJM coordinates with the Affected System Operators to conduct any studies required to determine the impact of the New Service Request on any Affected System and will include the Affected System Study results in Phase III System Impact Study, if available from the Affected System Operator.

If your project required an Affected System Study, the results are shown below from the Affected System Operator.

For more details, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM will list any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG1-124 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$2,419,500
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$2,163,751
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$1,380,077
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$763,670
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$601,942
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$489,111
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0N/A
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0N/A
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0N/A
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0N/A
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0N/A
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0N/A
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0N/A
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0N/A
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0N/A
Grand Total:$7,818,051

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / dom-397
Title
ELIMINATED FOR TC1: Wreck and rebuild 7.3 miles of 138 kV Line No. 8 between AE1-108 and Bremo with (1) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 7.3 miles of 138 kV Line No. 8 between AE1-108 and Bremo with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$23,887,052
Discounted Total Cost ($USD)
$6,247,695
Allocated Cost ($USD)
$6,247,695
Time Estimate
43 to 44 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
4BREMO-AE1-108 TP 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A237.0 MVA
(All)B262.0 MVA
(All)C273.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG1-12411.3 MW100.0%$6,247,695

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / AEPAPRJV007
Title
ELIMINATED FOR TC1: Mitigation work on 6.5 Miles of 138 kV transmission line from Scottsville Station to Arvonia Station.
Description
•Acquire LiDAR data for Scottsville Station to STR 268 of the Reusens – Scottsville - Bremo Bluff line needed for detailed line design. •Replace 3 structures and 1 floating dead ends along the Reusens – Scottsville – Bremo Bluff line determined in preliminary engineering study.
Total Cost ($USD)
$4,759,000
Discounted Total Cost ($USD)
$1,244,724
Allocated Cost ($USD)
$1,244,724
Time Estimate
29 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
4BREMO-AE1-108 TP 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMB173.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG1-12411.3 MW100.0%$1,244,724

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / AEPAPRJV008
Title
ELIMINATED FOR TC1: Upgrade a 0.6 mile portion of the Arvonia – Bremo Bluff (VEPCO) 138 kV line.
Description
"•Acquire LiDAR data for Scottsville Station to STR 268 of the Reusens – Scottsville - Bremo Bluff line needed for detailed line design. •Upgrade a 0.6 mile portion of the Arvonia – Bremo Bluff (VEPCO) 138 kV line by installing one floating deadend and replacing one structure"
Total Cost ($USD)
$1,245,000
Discounted Total Cost ($USD)
$325,632
Allocated Cost ($USD)
$325,632
Time Estimate
15 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

FacilityContingency
4BREMO-AE1-108 TP 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA257.0 MVA
SUMB359.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG1-12411.3 MW100.0%$325,632

System Reinforcement: n8492

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Allocated Cost ($USD)
$2,419,500
Time Estimate
26 to 27 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$11,942,543
AF1-12414.9488 %$11,984,793
AF1-12514.6652 %$11,757,425
AF1-2940.3084 %$247,251
AF2-04229.0898 %$23,321,955
AF2-1150.1881 %$150,804
AF2-1205.5338 %$4,436,574
AF2-2223.7926 %$3,040,614
AG1-0210.1505 %$120,659
AG1-1243.0179 %$2,419,519
AG1-1355.3024 %$4,251,055
AG1-2852.8388 %$2,275,931
AG1-5365.2677 %$4,223,235

System Reinforcement: n9630.0

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$2,163,751
Time Estimate
Dec 31 2029
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$10,680,181
AF1-12414.9488 %$10,717,966
AF1-12514.6652 %$10,514,631
AF1-2940.3084 %$221,116
AF2-04229.0898 %$20,856,756
AF2-1150.1881 %$134,864
AF2-1205.5338 %$3,967,615
AF2-2223.7926 %$2,719,212
AG1-0210.1505 %$107,905
AG1-1243.0179 %$2,163,769
AG1-1355.3024 %$3,801,706
AG1-2852.8388 %$2,035,358
AG1-5365.2677 %$3,776,827

System Reinforcement: n9267.0

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Allocated Cost ($USD)
$1,380,077
Time Estimate
45 to 46 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$6,811,998
AF1-12414.9488 %$6,836,097
AF1-12514.6652 %$6,706,407
AF1-2940.3084 %$141,032
AF2-04229.0898 %$13,302,787
AF2-1150.1881 %$86,018
AF2-1205.5338 %$2,530,611
AF2-2223.7926 %$1,734,359
AG1-0210.1505 %$68,824
AG1-1243.0179 %$1,380,088
AG1-1355.3024 %$2,424,791
AG1-2852.8388 %$1,298,185
AG1-5365.2677 %$2,408,923

System Reinforcement: n9259.0

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Allocated Cost ($USD)
$763,670
Time Estimate
38 to 39 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$3,769,444
AF1-12414.9488 %$3,782,779
AF1-12514.6652 %$3,711,014
AF1-2940.3084 %$78,040
AF2-04229.0898 %$7,361,145
AF2-1150.1881 %$47,599
AF2-1205.5338 %$1,400,323
AF2-2223.7926 %$959,714
AG1-0210.1505 %$38,084
AG1-1243.0179 %$763,677
AG1-1355.3024 %$1,341,767
AG1-2852.8388 %$718,356
AG1-5365.2677 %$1,332,986

System Reinforcement: n8492.1

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Allocated Cost ($USD)
$601,942
Time Estimate
30 to 36 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$2,971,158
AF1-12414.9488 %$2,981,670
AF1-12514.6652 %$2,925,103
AF1-2940.3084 %$61,513
AF2-04229.0898 %$5,802,216
AF2-1150.1881 %$37,518
AF2-1205.5338 %$1,103,765
AF2-2223.7926 %$756,467
AG1-0210.1505 %$30,019
AG1-1243.0179 %$601,947
AG1-1355.3024 %$1,057,610
AG1-2852.8388 %$566,224
AG1-5365.2677 %$1,050,689

System Reinforcement: n8492.2

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Allocated Cost ($USD)
$489,111
Time Estimate
15 to 16 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
ProjectPercent AllocationAllocated Cost ($USD)
AF1-12314.8961 %$2,414,229
AF1-12414.9488 %$2,422,770
AF1-12514.6652 %$2,376,807
AF1-2940.3084 %$49,983
AF2-04229.0898 %$4,714,620
AF2-1150.1881 %$30,486
AF2-1205.5338 %$896,870
AF2-2223.7926 %$614,671
AG1-0210.1505 %$24,392
AG1-1243.0179 %$489,115
AG1-1355.3024 %$859,366
AG1-2852.8388 %$460,088
AG1-5365.2677 %$853,743

System Reinforcement: b4000.357

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.352

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.351

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.350

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.349

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.348

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.346

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.345

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.344

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.325

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.326

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.327

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: s3047.2

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s3047.2
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3047.2
Title
Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.
Description
Install (2) 1400 MVA 500-230 kV transformers and associated 500 kV and 230 kV equipment (breakers, switches, leads) at Vint Hill Substation to supply the area with a 500 kV source Cut and loop 500 kV line #535 Loudoun – Meadowbrook and #569 Loudoun - Morrisville as the 500 kV sources into the proposed 500 kV ring bus Vint Hill Substation will be expanded to the north of the existing site to accommodate the 500 kV ring required for the addition of the new transformers Existing terminations for 230 kV line #2174 Wheeler – Vint Hill, line #2101 Bristers – Vint Hill, and line #2163 Liberty – Vint Hill will be rearranged to terminate into the expanded Vint Hill Substation 230 kV line #2114 Remington CT – Rollins Ford will also be cut and looped into the expanded Vint Hill Substation due to spatial constraints along the existing right-of-way.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.312

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.313

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.313
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.313
Title
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Description
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.356

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.356
Title
Build a new 500 kV line from Vint Hill to Wishing Star.
Description
Build a new 500kV line from Vint Hill to Wishing Star. The line will be supported on single circuit monopoles. New conductor to have a summer rating of 4357 MVA. Line length is approximately 16.59 miles
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.357

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.357
Title
Build a new 500 kV line from Morrisville to Vint Hill.
Description
Build a new 500kV line from Morrisville to Vint Hill. New conductor to have a summer rating of 4357 MVA. Line length is approximately 19.71 miles.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.354

AG1-124 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.354
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.354
Title
Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.
Description
Install terminal equipment at Wishing Star substation to support a 5000A line to Vint Hill. Update relay settings for 500kV Lines #546 and #590.
Cost Information
Cost Alloc Type
Contingent

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG1-124


AG1-124 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowDominion(Pending) / dom-397ELIMINATED FOR TC1: Wreck and rebuild 7.3 miles of 138 kV Line No. 8 between AE1-108 and Bremo with (1) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.Eliminated11.3 MW100.0%Cost Allocated$6,247,695
Load FlowDominion(Pending) / AEPAPRJV007ELIMINATED FOR TC1: Mitigation work on 6.5 Miles of 138 kV transmission line from Scottsville Station to Arvonia Station.Eliminated11.3 MW100.0%Cost Allocated$1,244,724
Load FlowDominion(Pending) / AEPAPRJV008ELIMINATED FOR TC1: Upgrade a 0.6 mile portion of the Arvonia – Bremo Bluff (VEPCO) 138 kV line.Eliminated11.3 MW100.0%Cost Allocated$325,632
Contributions into Topology or Eliminated Reinforcement Total:$7,818,051
AG1-124 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Cost Allocated$2,419,500
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Cost Allocated$2,163,751
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Cost Allocated$1,380,077
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Cost Allocated$763,670
Dominionn8492.1Two Breaker Additions at Fentress Substation.Cost Allocated$601,942
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Cost Allocated$489,111
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Contingent$0
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Contingent$0
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Contingent$0
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Contingent$0
Dominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0
Dominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationContingent$0
Dominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Contingent$0
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Contingent$0
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Contingent$0
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Contingent$0
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Contingent$0
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Contingent$0
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Contingent$0
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Contingent$0
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Contingent$0
Region Topology Upgrade Total:$7,818,051

Attachments

AG1-124 One Line Diagram

AG1-124 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.