AG1-153 Final System Impact Study (Retool 2) Report

v2.00 released 2026-05-14 11:56

Heritage 500 kV

30.0 MW Capacity / 75.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia), and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.

The AG1-153 Final System Impact Study (Retool 1) Report is available for download here.

Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Brunswick County, Virginia. The installed facilities will have a total capability of 75.0 MW with 30.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG1-153
Project Name:
Heritage 500 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
State:
Virginia
County:
Brunswick
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
75.0
MWE:
75.0
MWC:
30.0
Battery Storage Specification:
300.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2027

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG1-153 will interconnect on the Dominion transmission system as direct connect at Heritage 500 kV Substation.

 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AG1-153 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AG1-153Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$4,822,863$4,822,863
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$1,958,524$1,958,524
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$1,759,557$1,759,557
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0
AFS - Non-PJM Violations$0 **$0 **
Total$8,540,944$8,540,944

* Contributes to calculation for Security. See Security Requirement Section of this report for additional detail.

** This value reflects the results at the time of the report posting and it is subject to change. AFS – Non-PJM Violations are not subject to Security. For latest AFS – Non-PJM Violations, please refer to the latest Affected System Study Report for your project.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AG1-153

Security has been calculated for the AG1-153 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AG1-153
Project(s): AG1-153
Final Agreement Security (A): $8,540,944
Portion of Costs Already Paid (B): $747,280
Revised Net Security (C): A − B = $7,793,664
Security on Hand with PJM (D): $7,899,657
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

The New Service Request Project will interconnect with the Dominion transmission system via a direct connect to the Heritage 500 kV Sub. The required work for the interconnection of the New Service Request Project to the Dominion Transmission System is detailed in the following tables.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n8316

Expansion of Existing Heritage 500 kV Substation

$875,457$738,668$270,404$73,995$1,958,524$1,958,524
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Transmission Owner Interconnection Facilities, including one (1) new 500 kV engineered steel 3-pole structure is to be installed outside the fence of the interconnection substation, to terminate the Project Developer’s generator lead line, and line conductor from the backbone structure to the bus position in the switchyard of the interconnection substation.

$3,362,312$838,141$553,656$68,754$4,822,863$4,822,863

Based on the scope of work for the Interconnection Facilities, it is expected to take 62 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

 

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG1-153 was evaluated as a 75.0 MW (30.0 MW Capacity) injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC109.81 %1204.0C1322.089.94
GD1DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC108.01 %1204.0C1300.429.94
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC141.99 %812.0C1152.995.82
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC133.67 %663.64B887.072.02
GD1DVP
6POE-6TYLER1 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC103.31 %541.0C558.915.48
GD1DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC113.54 %1056.8C1199.8611.7
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC106.13 %3940.0C4181.5224.49
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC104.17 %3940.0C4104.3323.45
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H1T567_SRT-A
BreakerAC103.4 %3940.0C4073.9124.51
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC108.99 %3940.0C4294.1322.88
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC104.84 %3940.0C4130.7322.74
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S_SENS
BreakerAC102.96 %3940.0C4056.6421.88
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S_SENS
SingleAC101.85 %3220.44B3279.978.59
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC102.49 %3144.0C3222.3717.14
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC102.39 %3144.0C3219.0816.91
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC102.39 %3144.0C3219.0816.91
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC102.38 %3144.0C3218.9216.91

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.81 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1322.08
MW Contribution:9.94
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.0 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1396.59
MW Contribution:9.8
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
963042AG1-153 E
50/50
5.9665.966
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
316315AB2-025 C
50/50
0.4720.472
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
3152441Z1-086 ST
50/50
13.14613.146
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934511AD1-075 C
Adder
3.2917647058823532.798
934521AD1-076 C
Adder
4.7823529411764714.065
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
316087AB2-174 C
50/50
0.9180.918
932632AC2-084 E
Adder
1.89764705882352951.613
926214AC1-099 E
Adder
0.70941176470588230.603
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
964792AG1-342 E
Adder
1.34588235294117631.144
932763AC2-100 E
Adder
1.3917647058823531.183
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
918492AA1-063AE OP
Adder
2.40470588235294122.044
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151021BRUNSWICKG1
50/50
5.8715.871
3151041BRUNSWICKG3
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
940541AE2-040 C
50/50
3.3223.322
940482AE2-033 E
50/50
12.29712.297
940481AE2-033 C
50/50
18.24118.241
923263AB1-132 E OP
50/50
4.64.6
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
926274AC1-105 E
Adder
1.50823529411764711.282
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961941AG1-037 C
Adder
0.251764705882352950.214
961942AG1-037 E
Adder
0.167058823529411760.142
3151381ROSEMG2
50/50
0.7050.705
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934321AD1-056 C
Adder
4.1835294117647063.556
934332AD1-057 E
Adder
1.21529411764705891.033
934322AD1-056 E
Adder
2.26941176470588251.929
934331AD1-057 C
Adder
2.33411764705882341.984
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
3151391GASTONA
50/50
2.2972.297
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
963041AG1-153 C
50/50
3.9773.977
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
936172AD2-023 E
Adder
1.21058823529411751.029
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
927146AC1-208 E
Adder
2.45294117647058842.085
934622AD1-088 E
Adder
2.72588235294117662.317
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151411GASTONB
50/50
2.2972.297
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
3151051BRUNSWICKS1
50/50
12.19612.196
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.01 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1300.42
MW Contribution:9.94
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.2 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1374.95
MW Contribution:9.8
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
3152441Z1-086 ST
50/50
13.14613.146
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
918492AA1-063AE OP
Adder
2.40470588235294122.044
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151021BRUNSWICKG1
50/50
5.8715.871
940541AE2-040 C
50/50
3.3223.322
940482AE2-033 E
50/50
12.29712.297
940481AE2-033 C
50/50
18.24118.241
923263AB1-132 E OP
50/50
4.64.6
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
926274AC1-105 E
Adder
1.50823529411764711.282
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961941AG1-037 C
Adder
0.251764705882352950.214
961942AG1-037 E
Adder
0.167058823529411760.142
3151381ROSEMG2
50/50
0.7050.705
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934321AD1-056 C
Adder
4.1835294117647063.556
934332AD1-057 E
Adder
1.21529411764705891.033
934322AD1-056 E
Adder
2.26941176470588251.929
934331AD1-057 C
Adder
2.33411764705882341.984
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
3151391GASTONA
50/50
2.2972.297
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
963041AG1-153 C
50/50
3.9773.977
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
316087AB2-174 C
50/50
0.9180.918
932632AC2-084 E
Adder
1.89764705882352951.613
926214AC1-099 E
Adder
0.70941176470588230.603
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
964792AG1-342 E
Adder
1.34588235294117631.144
932763AC2-100 E
Adder
1.3917647058823531.183
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934511AD1-075 C
Adder
3.2917647058823532.798
934521AD1-076 C
Adder
4.7823529411764714.065
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
3151041BRUNSWICKG3
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
927146AC1-208 E
Adder
2.45294117647058842.085
934622AD1-088 E
Adder
2.72588235294117662.317
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151411GASTONB
50/50
2.2972.297
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
963042AG1-153 E
50/50
5.9665.966
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
936172AD2-023 E
Adder
1.21058823529411751.029
316315AB2-025 C
50/50
0.4720.472
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
3151051BRUNSWICKS1
50/50
12.19612.196
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.99 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1152.99
MW Contribution:5.82
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.71 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1061.35
MW Contribution:5.76
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150801HOPHCF4
50/50
2.5532.553
316349AD2-085 C
Adder
1.61058823529411771.369
935112AD1-144 E
Adder
0.315294117647058840.268
944582AF1-123 E
Adder
31.66823529411764726.918
944592AF1-124 E
Adder
31.78352941176470427.016
923832AB2-022 E
Adder
0.397647058823529460.338
938772AE1-103 E
Adder
1.55882352941176471.325
916042Z1-036 E
Adder
9.7517647058823538.289
960082AF2-299 E
Adder
0.60352941176470590.513
946281AF1-292 C
Adder
0.74941176470588230.637
926071AC1-086 C
Adder
9.7470588235294138.285
963042AG1-153 E
Adder
3.4917647058823532.968
927021AC1-189 C
Adder
3.2094117647058832.728
964241AG1-285 C
Adder
4.1952941176470593.566
924152AB2-059 E OP
Adder
2.0588235294117651.75
962561AG1-105 C
Adder
2.89529411764705862.461
316315AB2-025 C
50/50
0.2520.252
946282AF1-292 E
Adder
0.50.425
944012AF1-069 E
Adder
2.1552941176470591.832
917512Z2-088 E OP1
Adder
1.88000000000000011.598
3150791HOPHCF3
50/50
1.6821.682
926662AC1-147 E
Adder
0.420.357
916192Z1-068 E
Adder
0.58588235294117650.498
957492AF2-043 E
Adder
0.4717647058823530.401
923852AB2-025 E
50/50
0.7170.717
939412AE1-173 E
Adder
23.37764705882352719.871
961941AG1-037 C
Adder
0.198823529411764730.169
961942AG1-037 E
Adder
0.132941176470588230.113
941032AE2-094 E
Adder
7.6070588235294126.466
941031AE2-094 C
Adder
16.9847058823529414.437
934321AD1-056 C
Adder
2.642.244
934332AD1-057 E
Adder
0.76705882352941180.652
934322AD1-056 E
Adder
1.4317647058823531.217
934331AD1-057 C
Adder
1.47294117647058821.252
927022AC1-189 E
Adder
1.59882352941176481.359
925595AC1-034 E
Adder
1.95294117647058821.66
3150771HOPHCF1
50/50
1.6821.682
940431AE2-027 C
Adder
5.5282352941176474.699
942002AE2-212 E
50/50
1.5921.592
316132AB2-190 C
50/50
2.4992.499
944581AF1-123 C
Adder
13.82941176470588311.755
941101AE2-104 C
Adder
1.2482352941176471.061
316141AB2-099 E
Adder
0.098823529411764710.084
316088AB2-174 E
Adder
3.04352941176470632.587
923994AB2-040_E
Adder
2.8235294117647062.4
957481AF2-042 C
Adder
19.4705882352941216.55
961672AG1-007 E
Adder
0.204705882352941150.174
924322AB2-079 E O1
Adder
0.448235294117647070.381
935162AD1-151 E
50/50
6.1926.192
943461AF1-017 C
Adder
0.6317647058823530.537
932596AC2-079 E
Adder
4.2658823529411763.626
316311AC2-079 C
Adder
2.61529411764705882.223
938532AE1-072 E
Adder
2.8635294117647062.434
3146326AYDLETT TAP
Adder
0.424705882352941160.361
917122Z2-027 E
Adder
0.435294117647058830.37
920692AA2-178 E
Adder
1.45294117647058841.235
966622AG1-532 E
Adder
0.452941176470588240.385
922923AB1-081 E OP
Adder
1.45294117647058841.235
944641AF1-129 C
50/50
138.059138.059
316240AF1-291 C
50/50
2.8082.808
924814AB2-134 E
Adder
6.8941176470588245.86
316381AD1-082 C
50/50
0.7750.775
942342AE2-247 E
Adder
0.96470588235294120.82
919152AA1-139 E1
Adder
1.27058823529411781.08
920042AA2-088 E OP
Adder
4.2552941176470593.617
934511AD1-075 C
Adder
3.0564705882352942.598
934521AD1-076 C
Adder
4.443.774
3145723EMPORIA
Adder
0.205882352941176460.175
923573AB1-173 E OP
Adder
1.50588235294117641.28
919692AA2-053 E OP
Adder
1.7835294117647061.516
925785AC1-054 E
Adder
1.32352941176470581.125
316263AC1-034 C
Adder
2.5882352941176472.2
3150781HOPHCF2
50/50
1.6821.682
942001AE2-212 C
50/50
2.3882.388
939192AE1-149 E
50/50
5.125.12
939312AE1-162 E
Adder
0.54941176470588240.467
934065AD1-033 E
Adder
1.53411764705882361.304
937226AE2-253 E
Adder
1.80588235294117651.535
934501AD1-074 C
Adder
12.22470588235294110.391
924517AB2-100 E2
Adder
1.5282352941176471.299
957482AF2-042 E
Adder
12.9811.033
961671AG1-007 C
Adder
0.36235294117647060.308
934621AD1-088 C
Adder
3.18117647058823572.704
935172AD1-152 E
Adder
1.86235294117647051.583
942341AE2-247 C
Adder
0.69882352941176470.594
943462AF1-017 E
Adder
1.03058823529411760.876
958162AF2-110 E
Adder
0.81058823529411760.689
919153AA1-139 E2
Adder
1.27058823529411781.08
934512AD1-075 E
Adder
1.5552941176470591.322
934502AD1-074 E
Adder
6.222352941176475.289
924516AB2-100 E1
Adder
1.5282352941176471.299
918512AA1-065 E OP
Adder
2.12470588235294141.806
966621AG1-532 C
Adder
0.67999999999999990.578
918532AA1-067 E
Adder
0.269411764705882350.229
924022AB2-043 E O1
Adder
1.73764705882352951.477
3150651CHESTF6
50/50
25.13725.137
946262AF1-291 E
50/50
1.8721.872
940432AE2-027 E
Adder
3.68588235294117663.133
934012AD1-025 E
Adder
5.4482352941176474.631
913392Y1-086 E
Adder
0.70470588235294120.599
939411AE1-173 C
Adder
35.0670588235294129.807
3137643SOCKMAN
Adder
0.315294117647058840.268
919710AA2-057 E
Adder
1.58117647058823541.344
3150761HOPPOLC
50/50
1.0581.058
3145256KINGFORK
Adder
0.33882352941176470.288
925522AC1-027 E
Adder
0.380.323
941102AE2-104 E
Adder
1.98470588235294131.687
957872AF2-081 E
Adder
1.33058823529411761.131
932632AC2-084 E
Adder
1.2988235294117651.104
926214AC1-099 E
Adder
0.484705882352941150.412
964242AG1-285 E
Adder
2.7964705882352942.377
924162AB2-060 E OP
Adder
1.41882352941176461.206
964792AG1-342 E
Adder
0.76588235294117660.651
934576AD1-082 E
50/50
2.7072.707
944602AF1-125 E
Adder
31.17176470588235326.496
3145506HICKORY
Adder
0.6682352941176470.568
943612AF1-032 E
Adder
0.30705882352941180.261
957871AF2-081 C
Adder
3.10588235294117652.64
940492AE2-034 E
Adder
1.08941176470588250.926
934522AD1-076 E
Adder
2.2623529411764711.923
943172AE2-346 E
Adder
0.238823529411764740.203
918492AA1-063AE OP
Adder
1.7070588235294121.451
917332KELFORD E
Adder
0.65058823529411770.553
925122AB2-169 E
Adder
2.1235294117647061.805
316274AC1-208 C
Adder
3.6705882352941183.12
917342Z2-044 E
Adder
0.235294117647058850.2
937482AD2-202 E
Adder
0.36941176470588240.314
3151311EDGECMA
Adder
6.0682352941176485.158
939191AE1-149 C
50/50
7.6817.681
3143316POE
50/50
1.2311.231
901082W1-029 E
Adder
10.5541176470588248.971
926206AC1-098 E
Adder
1.4682352941176471.248
964791AG1-342 C
Adder
1.1482352941176470.976
961611AG1-000B C
Adder
7.286.188
940541AE2-040 C
50/50
1.7731.773
940482AE2-033 E
50/50
6.6116.611
940481AE2-033 C
50/50
9.8069.806
923263AB1-132 E OP
Adder
2.8364705882352942.411
924312AB2-078 E O1
Adder
0.448235294117647070.381
926274AC1-105 E
Adder
0.860.731
925332AB2-190 E
50/50
4.8614.861
927226AC1-216 E
Adder
4.2082352941176473.577
936666AD2-085 E
Adder
2.62823529411764722.234
941591AE2-156 C
Adder
5.6635294117647064.814
944601AF1-125 C
Adder
13.61647058823529511.574
944591AF1-124 C
Adder
13.87882352941176711.797
938771AE1-103 C
Adder
1.1282352941176470.959
3145413WATKINS
Adder
0.271764705882352960.231
960081AF2-299 C
Adder
0.90588235294117650.77
926072AC1-086 E
Adder
4.4364705882352943.771
944011AF1-069 C
Adder
5.5494117647058824.717
963041AG1-153 C
Adder
2.32823529411764741.979
962562AG1-105 E
Adder
1.93058823529411771.641
316084AB2-161 E
50/50
3.3973.397
316083AB2-161 C
50/50
0.340.34
3145946PLYMOUTH TP
Adder
0.116470588235294130.099
933982AD1-022 E
Adder
1.75647058823529421.493
927146AC1-208 E
Adder
1.62941176470588231.385
934622AD1-088 E
Adder
1.53176470588235311.302
934612AD1-087 E
Adder
1.26235294117647071.073
3150731STONECA
50/50
4.7614.761
935161AD1-151 C
50/50
9.2889.288
932046AC2-012 E
Adder
4.1552941176470593.532
958161AF2-110 C
Adder
0.50941176470588230.433
938531AE1-072 C
Adder
5.49411764705882364.67
3145393UNCAMP
Adder
2.362.006
933981AD1-022 C
Adder
3.22705882352941182.743
900672V4-068 E
Adder
0.14235294117647060.121
924302AB2-077 E O1
Adder
0.448235294117647070.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.0758.075
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.5166.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.081.08
LAGNLTFEXP_LAGN->PJM
CLTF
2.3232.323
NYPJM->LTFIMP_NY
CLTF
0.4640.464
LGEELTFEXP_LGEE->PJM
CLTF
0.3190.319
WECLTFEXP_WEC->PJM
CLTF
0.1690.169
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9850.985
SIGELTFEXP_SIGE->PJM
CLTF
0.0650.065
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.8981.898
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.93631.936
CPLELTFEXP_CPLE->PJM
CLTF
3.9843.984
TVALTFEXP_TVA->PJM
CLTF
1.811.81
O66PJM->LTFIMP_O-066
CMTX_NF
6.2766.276

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.67 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:887.07
MW Contribution:2.02
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.35 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:918.17
MW Contribution:1.99
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961611AG1-000B C
80/20
7.6267.626
316236AE1-162 C
80/20
0.1440.144
940541AE2-040 C
80/20
1.6761.676
940481AE2-033 C
80/20
9.2759.275
316181AB2-040 GEN
80/20
0.5530.553
3156063AA2-053SOLA
80/20
0.6110.611
3151281ROARAP4
80/20
0.5360.536
3150801HOPHCF4
80/20
2.5772.577
316349AD2-085 C
80/20
1.6511.651
316023AB2-100 C2
80/20
0.4810.481
946281AF1-292 C
80/20
0.7080.708
926071AC1-086 C
80/20
9.3179.317
927021AC1-189 C
Adder
3.0858823529411772.623
941591AE2-156 C
Adder
6.2764705882352945.335
944601AF1-125 C
Adder
15.18117647058823612.904
944591AF1-124 C
Adder
15.47294117647058813.152
938771AE1-103 C
80/20
1.1561.156
960081AF2-299 C
80/20
0.8560.856
3151391GASTONA
80/20
1.3541.354
944011AF1-069 C
80/20
4.8054.805
963041AG1-153 C
Adder
2.0188235294117651.716
316315AB2-025 C
80/20
0.2380.238
3151051BRUNSWICKS1
80/20
6.1926.192
3150791HOPHCF3
80/20
1.6981.698
316369AC1-216 C
80/20
0.90.9
961941AG1-037 C
Adder
0.196470588235294150.167
3151381ROSEMG2
80/20
0.4160.416
941031AE2-094 C
80/20
14.70614.706
934321AD1-056 C
Adder
2.50705882352941162.131
934331AD1-057 C
Adder
1.39882352941176481.189
316033AB2-134 GEN
80/20
1.1791.179
934011AD1-025 C
80/20
1.4591.459
939191AE1-149 C
80/20
7.67.6
316365AB2-100 C1
80/20
0.4810.481
3151021BRUNSWICKG1
80/20
2.9812.981
3151041BRUNSWICKG3
80/20
2.9812.981
3150771HOPHCF1
80/20
1.6981.698
940431AE2-027 C
80/20
5.4285.428
316132AB2-190 C
80/20
2.552.55
944581AF1-123 C
Adder
15.41882352941176613.106
941101AE2-104 C
80/20
1.3111.311
3156083AA2-088SOLA
80/20
0.4240.424
313506AB1-173 C OP
80/20
0.4910.491
3151361ROSEMG1
80/20
0.8890.889
957481AF2-042 C
Adder
16.9176470588235314.38
3151211GRAVEL5
80/20
1.1271.127
943461AF1-017 C
80/20
0.6470.647
316311AC2-079 C
80/20
2.6862.686
3152441Z1-086 ST
80/20
6.6726.672
944641AF1-129 C
80/20
137.537137.537
316240AF1-291 C
80/20
2.7922.792
3151191GRAVEL3
80/20
1.1271.127
3151161SURRY 1
80/20
11.09811.098
316381AD1-082 C
80/20
0.7760.776
934511AD1-075 C
Adder
3.1141176470588232.647
934521AD1-076 C
Adder
4.5247058823529423.846
316011AB1-132 C OP
80/20
1.0341.034
316263AC1-034 C
Adder
2.44235294117647062.076
3150781HOPHCF2
80/20
1.6981.698
942001AE2-212 C
80/20
2.3582.358
934501AD1-074 C
Adder
12.4576470588235310.589
3156073AA1-063SOLA
80/20
0.570.57
3151371ROSEMS1
80/20
0.5510.551
961671AG1-007 C
Adder
0.34588235294117650.294
934621AD1-088 C
Adder
2.76235294117647052.348
3151171GRAVELC
80/20
0.3880.388
942341AE2-247 C
80/20
0.7150.715
966621AG1-532 C
80/20
0.6420.642
3150651CHESTF6
80/20
25.04225.042
957871AF2-081 C
Adder
3.42823529411764752.914
3151151S HAMPT1
80/20
0.5930.593
316274AC1-208 C
Adder
3.50823529411764762.982
3151311EDGECMA
Adder
5.7282352941176474.869
939411AE1-173 C
80/20
32.73632.736
3137643SOCKMAN
80/20
0.30.3
3151031BRUNSWICKG2
80/20
2.9812.981
3150761HOPPOLC
80/20
1.0681.068
933291AC2-141 C
Adder
9.0470588235294127.69
316087AB2-174 C
80/20
0.5210.521
316083AB2-161 C
80/20
0.340.34
940641AE2-051 C
80/20
6.3516.351
316336AC2-165 C
Adder
-2.925882352941177-2.487
3152431Z1-086 GT3
80/20
3.8323.832
3152421Z1-086 GT2
80/20
3.8323.832
3150731STONECA
80/20
4.8074.807
935161AD1-151 C
80/20
9.5159.515
3151221GRAVEL6
80/20
1.141.14
3151201GRAVEL4
80/20
1.1421.142
958161AF2-110 C
80/20
0.5350.535
938531AE1-072 C
Adder
6.04588235294117655.139
933981AD1-022 C
Adder
3.26941176470588252.779
3151411GASTONB
80/20
1.3541.354
3151261ROARAP2
80/20
0.5670.567
3147043LAWRENC
80/20
0.1270.127
3152411Z1-086 GT1
80/20
3.8333.833
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.8996.899
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.7315.731
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9380.938
LAGNLTFEXP_LAGN->PJM
CLTF
2.0572.057
NYPJM->LTFIMP_NY
CLTF
0.4310.431
LGEELTFEXP_LGEE->PJM
CLTF
0.2740.274
WECLTFEXP_WEC->PJM
CLTF
0.1450.145
SIGELTFEXP_SIGE->PJM
CLTF
0.0560.056
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7131.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.64628.646
CPLELTFEXP_CPLE->PJM
CLTF
3.5953.595
TVALTFEXP_TVA->PJM
CLTF
1.6011.601

Details for 6POE-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6POE-6TYLER1 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.31 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:558.91
MW Contribution:5.48
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6POE-6TYLER1 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.59 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:587.46
MW Contribution:5.39
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943461AF1-017 C
Adder
0.66588235294117650.566
932596AC2-079 E
Adder
4.3541176470588243.701
316311AC2-079 C
Adder
2.6682352941176472.268
966622AG1-532 E
Adder
0.434117647058823550.369
922923AB1-081 E OP
Adder
1.2952941176470591.101
316141AB2-099 E
Adder
0.080.068
316088AB2-174 E
Adder
2.8647058823529412.435
923994AB2-040_E
Adder
2.63529411764705922.24
957481AF2-042 C
Adder
18.75411764705882315.941
961672AG1-007 E
Adder
0.17764705882352940.151
924322AB2-079 E O1
Adder
0.440.374
942341AE2-247 C
Adder
0.73647058823529410.626
943462AF1-017 E
Adder
1.08705882352941190.924
924516AB2-100 E1
Adder
1.4764705882352941.255
923852AB2-025 E
50/50
0.7230.723
939412AE1-173 E
Adder
19.10941176470588216.243
961941AG1-037 C
Adder
0.158823529411764720.135
961942AG1-037 E
Adder
0.105882352941176470.09
941032AE2-094 E
Adder
7.1447058823529426.073
941031AE2-094 C
Adder
15.95176470588235213.559
934321AD1-056 C
Adder
2.3882352941176472.03
934332AD1-057 E
Adder
0.69411764705882350.59
934322AD1-056 E
Adder
1.2952941176470591.101
934331AD1-057 C
Adder
1.3317647058823531.132
927022AC1-189 E
Adder
1.34705882352941191.145
925595AC1-034 E
Adder
1.74000000000000021.479
936666AD2-085 E
Adder
2.77176470588235272.356
938771AE1-103 C
Adder
0.87058823529411770.74
3145413WATKINS
Adder
0.215294117647058830.183
960081AF2-299 C
Adder
0.86705882352941180.737
926072AC1-086 E
Adder
4.0752941176470593.464
944011AF1-069 C
Adder
5.2117647058823534.43
963041AG1-153 C
Adder
2.1905882352941181.862
962562AG1-105 E
Adder
1.8835294117647061.601
932632AC2-084 E
Adder
1.12235294117647060.954
926214AC1-099 E
Adder
0.420.357
964242AG1-285 E
Adder
2.76470588235294162.35
924162AB2-060 E OP
Adder
1.39764705882352951.188
964792AG1-342 E
Adder
0.74588235294117660.634
944641AF1-129 C
Adder
-70.29176470588236-59.748
316240AF1-291 C
Adder
-2.144705882352941-1.823
316381AD1-082 C
50/50
1.0531.053
942342AE2-247 E
Adder
1.01647058823529420.864
920042AA2-088 E OP
Adder
3.4941176470588242.97
3145723EMPORIA
Adder
0.196470588235294150.167
923573AB1-173 E OP
Adder
1.40588235294117661.195
919692AA2-053 E OP
Adder
1.57764705882352941.341
925785AC1-054 E
Adder
1.22941176470588221.045
316263AC1-034 C
Adder
2.30588235294117631.96
939192AE1-149 E
50/50
7.667.66
924517AB2-100 E2
Adder
1.4764705882352941.255
957482AF2-042 E
Adder
12.50352941176470610.628
961671AG1-007 C
Adder
0.31294117647058830.266
934621AD1-088 C
Adder
3.12235294117647082.654
935172AD1-152 E
Adder
1.7964705882352941.527
939411AE1-173 C
Adder
28.66352941176470624.364
3137643SOCKMAN
Adder
0.289411764705882370.246
919710AA2-057 E
Adder
1.39647058823529411.187
939191AE1-149 C
50/50
11.48911.489
3143316POE
50/50
2.8062.806
926206AC1-098 E
Adder
1.26941176470588221.079
964791AG1-342 C
Adder
1.11882352941176480.951
966621AG1-532 C
Adder
0.65058823529411770.553
924022AB2-043 E O1
Adder
1.7070588235294121.451
3147223TWITTYS
Adder
0.288235294117647030.245
940541AE2-040 C
50/50
1.7881.788
940482AE2-033 E
50/50
6.6366.636
940481AE2-033 C
50/50
9.8449.844
923263AB1-132 E OP
Adder
2.60588235294117652.215
925612AC1-036 E
Adder
0.260.221
924312AB2-078 E O1
Adder
0.440.374
926274AC1-105 E
Adder
0.83529411764705890.71
316084AB2-161 E
50/50
4.6154.615
316083AB2-161 C
50/50
0.4620.462
927146AC1-208 E
Adder
1.43647058823529421.221
934622AD1-088 E
Adder
1.5035294117647061.278
934612AD1-087 E
Adder
1.21882352941176491.036
3145393UNCAMP
Adder
1.841.564
900672V4-068 E
Adder
0.116470588235294130.099
924302AB2-077 E O1
Adder
0.440.374
316349AD2-085 C
Adder
1.69882352941176461.444
938772AE1-103 E
Adder
1.20117647058823531.021
960082AF2-299 E
Adder
0.57764705882352940.491
946281AF1-292 C
Adder
0.71764705882352940.61
926071AC1-086 C
Adder
8.9552941176470597.612
963042AG1-153 E
Adder
3.28588235294117672.793
927021AC1-189 C
Adder
2.7035294117647062.298
964241AG1-285 C
Adder
4.1470588235294123.525
924152AB2-059 E OP
Adder
1.83411764705882341.559
962561AG1-105 C
Adder
2.82588235294117672.402
316315AB2-025 C
50/50
0.2540.254
946282AF1-292 E
Adder
0.47882352941176470.407
944012AF1-069 E
Adder
2.02470588235294141.721
917512Z2-088 E OP1
Adder
1.60588235294117651.365
934576AD1-082 E
50/50
3.6773.677
943172AE2-346 E
Adder
0.191764705882352950.163
918492AA1-063AE OP
Adder
1.49058823529411751.267
917332KELFORD E
Adder
0.53411764705882360.454
316274AC1-208 C
Adder
3.23411764705882382.749
917342Z2-044 E
Adder
0.209411764705882350.178
937482AD2-202 E
Adder
0.35647058823529410.303
3151311EDGECMA
Adder
5.4047058823529424.594
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.5019.501
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7336.733
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1821.182
LAGNLTFEXP_LAGN->PJM
CLTF
2.3242.324
NYPJM->LTFIMP_NY
CLTF
0.3510.351
LGEELTFEXP_LGEE->PJM
CLTF
0.3660.366
WECLTFEXP_WEC->PJM
CLTF
0.1950.195
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7620.762
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7591.759
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.05430.054
CPLELTFEXP_CPLE->PJM
CLTF
3.6893.689
TVALTFEXP_TVA->PJM
CLTF
1.8151.815
O66PJM->LTFIMP_O-066
CMTX_NF
4.8534.853

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.54 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1199.86
MW Contribution:11.7
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.15 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1216.93
MW Contribution:11.66
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
944581AF1-123 C
Adder
17.0976470588235314.533
957481AF2-042 C
50/50
35.70935.709
924322AB2-079 E O1
Adder
0.45058823529411770.383
946302AF1-294 E
Adder
1.02352941176470580.87
943902AF1-058 E
Adder
0.58823529411764710.5
938532AE1-072 E
Adder
3.1047058823529412.639
3146326AYDLETT TAP
Adder
0.455294117647058850.387
3152441Z1-086 ST
50/50
15.62215.622
3147133PAMPLIN
Adder
0.377647058823529450.321
927264AC1-222 E
Adder
1.781.513
942001AE2-212 C
Adder
-2.8705882352941177-2.44
934065AD1-033 E
Adder
1.87294117647058831.592
937226AE2-253 E
Adder
2.081.768
957482AF2-042 E
50/50
23.80623.806
934621AD1-088 C
50/50
5.5965.596
946301AF1-294 C
Adder
1.2082352941176471.027
942461AE2-259 C
Adder
3.32588235294117632.827
935172AD1-152 E
Adder
3.1047058823529412.639
919153AA1-139 E2
Adder
1.42117647058823531.208
940642AE2-051 E
50/50
9.9019.901
966621AG1-532 C
Adder
-1.14-0.969
924022AB2-043 E O1
Adder
1.75058823529411781.488
3147223TWITTYS
Adder
0.42235294117647060.359
959312AF2-222 E
Adder
4.8764705882352944.145
913392Y1-086 E
Adder
0.66235294117647060.563
939411AE1-173 C
50/50
67.01167.011
3137643SOCKMAN
Adder
-0.34352941176470586-0.292
3151031BRUNSWICKG2
50/50
6.916.91
925522AC1-027 E
Adder
0.430588235294117660.366
933292AC2-141 E
Adder
6.3529411764705895.4
944602AF1-125 E
Adder
38.536470588235332.756
3145506HICKORY
Adder
0.80470588235294130.684
957871AF2-081 C
Adder
3.47411764705882352.953
937482AD2-202 E
50/50
0.6470.647
961792AG1-021 E
Adder
0.50117647058823530.426
3151021BRUNSWICKG1
50/50
6.916.91
3151041BRUNSWICKG3
50/50
6.916.91
942462AE2-259 E
Adder
2.21764705882352951.885
964791AG1-342 C
Adder
1.43529411764705881.22
925612AC1-036 E
Adder
0.381176470588235340.324
924312AB2-078 E O1
Adder
0.45058823529411770.383
926274AC1-105 E
Adder
1.15529411764705880.982
926662AC1-147 E
Adder
0.448235294117647070.381
916192Z1-068 E
Adder
0.6682352941176470.568
939412AE1-173 E
50/50
44.67444.674
941032AE2-094 E
50/50
15.74915.749
941031AE2-094 C
50/50
35.16335.163
934321AD1-056 C
Adder
-2.142352941176471-1.821
934331AD1-057 C
Adder
-1.1952941176470588-1.016
936262AD2-033 E
Adder
2.89058823529411772.457
958211AF2-115 C
Adder
0.73529411764705890.625
941591AE2-156 C
Adder
6.1035294117647065.188
944601AF1-125 C
Adder
16.8341176470588214.309
944591AF1-124 C
Adder
17.15764705882352814.584
944011AF1-069 C
50/50
11.48911.489
963041AG1-153 C
50/50
4.6824.682
936261AD2-033 C
Adder
4.3352941176470593.685
961791AG1-021 C
Adder
0.58823529411764710.5
962562AG1-105 E
Adder
2.3352941176470591.985
926755AC1-161 E
Adder
6.3529411764705895.4
933291AC2-141 C
Adder
14.88235294117647112.65
957872AF2-081 E
Adder
1.48941176470588241.266
964242AG1-285 E
Adder
3.99647058823529383.397
924162AB2-060 E OP
Adder
1.4435294117647061.227
964792AG1-342 E
Adder
0.95647058823529410.813
932763AC2-100 E
Adder
1.14235294117647060.971
944641AF1-129 C
Adder
-99.89764705882352-84.913
316240AF1-291 C
Adder
-2.2705882352941176-1.93
919152AA1-139 E1
Adder
1.42117647058823531.208
3145723EMPORIA
Adder
-0.3270588235294118-0.278
959311AF2-222 C
Adder
7.2776470588235296.186
944582AF1-123 E
Adder
39.15058823529411633.278
944592AF1-124 E
Adder
39.2929411764705933.399
937481AD2-202 C
50/50
0.2220.222
940641AE2-051 C
50/50
14.85114.851
3152431Z1-086 GT3
50/50
8.9728.972
3152421Z1-086 GT2
50/50
8.9728.972
934622AD1-088 E
50/50
2.6942.694
934612AD1-087 E
50/50
2.212.21
934611AD1-087 C
50/50
0.7660.766
927255AC1-221 E
Adder
1.70117647058823531.446
932046AC2-012 E
Adder
4.4317647058823533.767
938531AE1-072 C
Adder
5.95529411764705955.062
3152411Z1-086 GT1
50/50
8.9758.975
924302AB2-077 E O1
Adder
0.45058823529411770.383
923832AB2-022 E
Adder
0.374117647058823550.318
946281AF1-292 C
Adder
-1.2576470588235293-1.069
963042AG1-153 E
50/50
7.0227.022
3151541CLOVER2
50/50
7.7177.717
964241AG1-285 C
Adder
5.9952941176470595.096
958212AF2-115 E
Adder
0.62588235294117660.532
962561AG1-105 C
Adder
3.50352941176470622.978
944012AF1-069 E
50/50
4.4634.463
3151051BRUNSWICKS1
50/50
14.35614.356
3151531CLOVER1
50/50
7.797.79
3138533PONTONDP
Adder
0.217647058823529420.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.10812.108
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4868.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4991.499
LAGNLTFEXP_LAGN->PJM
CLTF
2.9182.918
NYPJM->LTFIMP_NY
CLTF
0.4470.447
LGEELTFEXP_LGEE->PJM
CLTF
0.4670.467
WECLTFEXP_WEC->PJM
CLTF
0.2490.249
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9710.971
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9681.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.24536.245
CPLELTFEXP_CPLE->PJM
CLTF
4.1284.128
TVALTFEXP_TVA->PJM
CLTF
2.2832.283
O66PJM->LTFIMP_O-066
CMTX_NF
6.1826.182

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.13 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4181.52
MW Contribution:24.49
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.66 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4635.61
MW Contribution:24.49
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316349AD2-085 C
Adder
4.8858823529411764.153
935112AD1-144 E
Adder
1.38117647058823521.174
944582AF1-123 E
50/50
161.69161.69
944592AF1-124 E
50/50
162.275162.275
923832AB2-022 E
50/50
1.9081.908
938772AE1-103 E
Adder
6.0023529411764715.102
916042Z1-036 E
Adder
43.3141176470588236.817
960082AF2-299 E
Adder
1.80588235294117651.535
946281AF1-292 C
Adder
2.24235294117647041.906
926071AC1-086 C
Adder
30.4329411764705925.868
963042AG1-153 E
50/50
14.69214.692
927021AC1-189 C
Adder
12.02000000000000110.217
964241AG1-285 C
Adder
17.9658823529411815.271
924152AB2-059 E OP
Adder
7.4317647058823546.317
962561AG1-105 C
Adder
12.04705882352941210.24
3151101ELIZAR3
50/50
4.9744.974
3151081ELIZAR1
50/50
4.9124.912
3151091ELIZAR2
50/50
4.8264.826
316315AB2-025 C
50/50
0.6050.605
946282AF1-292 E
Adder
1.49529411764705871.271
944012AF1-069 E
50/50
9.0749.074
3151051BRUNSWICKS1
50/50
30.03530.035
917512Z2-088 E OP1
Adder
6.9717647058823535.926
3150981CHESPKA
50/50
0.6670.667
316185AD1-033 C
50/50
1.9111.911
944581AF1-123 C
50/50
70.6170.61
941101AE2-104 C
Adder
5.00705882352941254.256
316320Y1-086 C
50/50
0.3390.339
316141AB2-099 E
Adder
0.370588235294117660.315
316088AB2-174 E
Adder
9.4435294117647068.027
923994AB2-040_E
Adder
8.9094117647058837.573
957481AF2-042 C
50/50
83.22783.227
961672AG1-007 E
Adder
0.75529411764705890.642
924322AB2-079 E O1
Adder
1.84705882352941191.57
943902AF1-058 E
Adder
1.71882352941176491.461
943461AF1-017 C
Adder
1.91529411764705881.628
932596AC2-079 E
Adder
13.36941176470588411.364
316311AC2-079 C
Adder
8.1941176470588236.965
938532AE1-072 E
50/50
14.1714.17
3146326AYDLETT TAP
50/50
2.0962.096
917122Z2-027 E
Adder
2.061.751
920692AA2-178 E
Adder
6.1741176470588245.248
966622AG1-532 E
Adder
1.35411764705882361.151
3152441Z1-086 ST
50/50
32.38632.386
922923AB1-081 E OP
Adder
5.2458823529411764.459
942342AE2-247 E
Adder
2.92470588235294172.486
316036AC1-147 C
50/50
0.5640.564
316018AA1-139 ULT2
50/50
1.6761.676
919152AA1-139 E1
50/50
6.336.33
920042AA2-088 E OP
Adder
15.59882352941176513.259
934511AD1-075 C
Adder
12.56117647058823510.677
934521AD1-076 C
Adder
18.24823529411764515.511
3145723EMPORIA
Adder
0.62470588235294120.531
923573AB1-173 E OP
Adder
4.7517647058823534.039
919692AA2-053 E OP
Adder
6.1282352941176475.209
925785AC1-054 E
Adder
4.8741176470588234.143
316263AC1-034 C
Adder
9.344705882352947.943
959311AF2-222 C
Adder
21.718.445
939192AE1-149 E
Adder
8.7694117647058827.454
939312AE1-162 E
Adder
1.95882352941176491.665
3150991CHESPKB
50/50
1.1051.105
934065AD1-033 E
50/50
7.7977.797
937226AE2-253 E
50/50
9.0629.062
934501AD1-074 C
Adder
50.2447058823529442.708
924517AB2-100 E2
Adder
4.23058823529411753.596
957482AF2-042 E
50/50
55.48555.485
961671AG1-007 C
Adder
1.33294117647058831.133
934621AD1-088 C
Adder
13.82823529411764711.754
935172AD1-152 E
Adder
7.9105882352941186.724
942341AE2-247 C
Adder
2.11764705882352941.8
943462AF1-017 E
Adder
3.12588235294117662.657
958162AF2-110 E
Adder
3.24941176470588242.762
316388AE2-253 GEN
50/50
3.0473.047
919153AA1-139 E2
50/50
6.336.33
934512AD1-075 E
Adder
6.3941176470588235.435
934502AD1-074 E
Adder
25.5776470588235321.741
924516AB2-100 E1
Adder
4.23058823529411753.596
918512AA1-065 E OP
Adder
8.1470588235294116.925
940642AE2-051 E
50/50
20.9220.92
966621AG1-532 C
Adder
2.0317647058823531.727
918532AA1-067 E
Adder
1.02823529411764710.874
924022AB2-043 E O1
Adder
7.1670588235294126.092
3147223TWITTYS
Adder
1.2588235294117651.07
959312AF2-222 E
Adder
14.53882352941176512.358
913392Y1-086 E
50/50
3.383.38
939411AE1-173 C
50/50
158.79158.79
3137643SOCKMAN
Adder
1.03058823529411760.876
3151031BRUNSWICKG2
50/50
14.45814.458
919710AA2-057 E
Adder
5.6458823529411774.799
3150921YORKTN3
Adder
152.65647058823532129.758
3145256KINGFORK
Adder
1.48823529411764691.265
925522AC1-027 E
50/50
1.8771.877
926755AC1-161 E
50/50
20.76320.763
933291AC2-141 C
50/50
48.6448.64
941102AE2-104 E
Adder
7.966.766
957872AF2-081 E
50/50
6.6346.634
932632AC2-084 E
Adder
4.6458823529411763.949
926214AC1-099 E
Adder
1.73647058823529421.476
964242AG1-285 E
Adder
11.97764705882352810.181
924162AB2-060 E OP
Adder
5.8752941176470594.994
964792AG1-342 E
Adder
3.1905882352941182.712
934576AD1-082 E
Adder
5.7482352941176484.886
916191Z1-068 C
50/50
0.0680.068
933292AC2-141 E
50/50
20.76320.763
316294AC1-161 C
50/50
7.9487.948
944602AF1-125 E
50/50
159.152159.152
3145506HICKORY
50/50
3.3883.388
943612AF1-032 E
Adder
1.40823529411764731.197
957871AF2-081 C
50/50
15.47915.479
940492AE2-034 E
Adder
4.6305882352941183.936
934522AD1-076 E
Adder
9.3011764705882357.906
943172AE2-346 E
Adder
0.88941176470588230.756
918492AA1-063AE OP
Adder
5.9423529411764715.051
917332KELFORD E
Adder
2.39764705882352922.038
925122AB2-169 E
Adder
8.4305882352941197.166
316274AC1-208 C
Adder
12.93882352941176410.998
917342Z2-044 E
Adder
0.84705882352941180.72
937482AD2-202 E
Adder
1.57764705882352941.341
3151311EDGECMA
Adder
21.84705882352941218.57
939191AE1-149 C
Adder
13.15411764705882411.181
3143316POE
Adder
1.71764705882352931.46
901082W1-029 E
Adder
48.63529411764706441.34
926206AC1-098 E
Adder
5.25647058823529444.468
3151021BRUNSWICKG1
50/50
14.45814.458
3151041BRUNSWICKG3
50/50
14.45814.458
964791AG1-342 C
Adder
4.7858823529411764.068
961611AG1-000B C
Adder
19.52941176470588416.6
316375AC2-012 C
50/50
2.0662.066
313526AB2-022 C
50/50
0.5790.579
940541AE2-040 C
Adder
4.263.621
940482AE2-033 E
Adder
16.1613.736
940481AE2-033 C
Adder
23.97176470588235420.376
923263AB1-132 E OP
Adder
8.8564705882352937.528
925612AC1-036 E
Adder
1.13647058823529410.966
924312AB2-078 E O1
Adder
1.84705882352941191.57
926274AC1-105 E
Adder
3.63.06
926662AC1-147 E
50/50
2.0262.026
916192Z1-068 E
50/50
2.92.9
957492AF2-043 E
Adder
2.16705882352941171.842
923852AB2-025 E
50/50
1.7231.723
939412AE1-173 E
50/50
105.86105.86
961941AG1-037 C
Adder
0.74117647058823530.63
961942AG1-037 E
Adder
0.494117647058823550.42
941032AE2-094 E
50/50
32.01732.017
941031AE2-094 C
50/50
71.48571.485
934321AD1-056 C
Adder
8.927.582
934332AD1-057 E
Adder
2.5917647058823532.203
934322AD1-056 E
Adder
4.8388235294117664.113
934331AD1-057 C
Adder
4.9764705882352954.23
927022AC1-189 E
Adder
5.9882352941176475.09
925595AC1-034 E
Adder
7.0494117647058835.992
936666AD2-085 E
Adder
7.9705882352941196.775
941591AE2-156 C
50/50
27.4127.41
316316AC1-027 C
50/50
0.4870.487
944601AF1-125 C
50/50
69.52369.523
944591AF1-124 C
50/50
70.86170.861
938771AE1-103 C
Adder
4.3470588235294113.695
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.70823529411764732.302
926072AC1-086 E
Adder
13.85058823529411711.773
944011AF1-069 C
50/50
23.35723.357
963041AG1-153 C
50/50
9.7959.795
936261AD2-033 C
Adder
6.71764705882352955.71
962562AG1-105 E
Adder
8.0317647058823526.827
316084AB2-161 E
Adder
7.2141176470588236.132
3145946PLYMOUTH TP
Adder
0.48235294117647060.41
933982AD1-022 E
Adder
7.0894117647058836.026
940641AE2-051 C
50/50
31.3831.38
3152431Z1-086 GT3
50/50
18.59918.599
3152421Z1-086 GT2
50/50
18.59918.599
927146AC1-208 E
Adder
5.74470588235294164.883
934622AD1-088 E
Adder
6.6576470588235295.659
934612AD1-087 E
Adder
5.3905882352941184.582
932046AC2-012 E
50/50
20.04320.043
958161AF2-110 C
Adder
2.04352941176470631.737
316017AA1-139 ULT1
50/50
1.6761.676
938531AE1-072 C
50/50
27.18327.183
3145393UNCAMP
Adder
9.0117647058823537.66
933981AD1-022 C
Adder
13.02235294117647211.069
900672V4-068 E
Adder
0.52352941176470590.445
3152411Z1-086 GT1
50/50
18.60518.605
924302AB2-077 E O1
Adder
1.84705882352941191.57
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.88834.888
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.38927.389
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.6044.604
LAGNLTFEXP_LAGN->PJM
CLTF
9.689.68
NYPJM->LTFIMP_NY
CLTF
2.172.17
LGEELTFEXP_LGEE->PJM
CLTF
1.3891.389
WECLTFEXP_WEC->PJM
CLTF
0.7290.729
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6364.636
SIGELTFEXP_SIGE->PJM
CLTF
0.2790.279
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6337.633
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.923129.923
CPLELTFEXP_CPLE->PJM
CLTF
16.01716.017
TVALTFEXP_TVA->PJM
CLTF
7.5637.563
O66PJM->LTFIMP_O-066
CMTX_NF
29.52729.527

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.17 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4104.33
MW Contribution:23.45
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943461AF1-017 C
Adder
1.77764705882352941.511
932596AC2-079 E
Adder
12.38941176470588310.531
316311AC2-079 C
Adder
7.5929411764705886.454
938532AE1-072 E
50/50
12.89612.896
3146326AYDLETT TAP
50/50
1.9081.908
917122Z2-027 E
Adder
1.88117647058823521.599
920692AA2-178 E
Adder
5.74.845
966622AG1-532 E
Adder
1.29294117647058831.099
3152441Z1-086 ST
50/50
31.00631.006
922923AB1-081 E OP
Adder
4.9882352941176474.24
942342AE2-247 E
Adder
2.71411764705882372.307
316018AA1-139 ULT2
50/50
1.5241.524
919152AA1-139 E1
50/50
5.7585.758
920042AA2-088 E OP
Adder
14.57411764705882412.388
934511AD1-075 C
Adder
11.6423529411764739.896
934521AD1-076 C
Adder
16.9129411764705914.376
3145723EMPORIA
Adder
0.59647058823529410.507
923573AB1-173 E OP
Adder
4.5223529411764713.844
919692AA2-053 E OP
Adder
5.797647058823534.928
925785AC1-054 E
Adder
4.65176470588235353.954
316263AC1-034 C
Adder
8.8847058823529417.552
959311AF2-222 C
Adder
20.9952941176470617.846
936666AD2-085 E
Adder
7.397647058823536.288
941591AE2-156 C
50/50
24.9124.91
316316AC1-027 C
50/50
0.4430.443
944601AF1-125 C
50/50
63.13463.134
944591AF1-124 C
50/50
64.34964.349
938771AE1-103 C
Adder
4.0211764705882363.418
3145413WATKINS
Adder
0.94941176470588240.807
960081AF2-299 C
Adder
2.58705882352941162.199
926072AC1-086 E
Adder
13.15411764705882411.181
944011AF1-069 C
50/50
22.35322.353
963041AG1-153 C
50/50
9.3799.379
936261AD2-033 C
Adder
15.9952941176470613.596
962562AG1-105 E
Adder
7.7364705882352946.576
926662AC1-147 E
Adder
1.84117647058823521.565
916192Z1-068 E
50/50
2.6352.635
957492AF2-043 E
Adder
1.97647058823529421.68
923852AB2-025 E
50/50
1.6571.657
939412AE1-173 E
50/50
99.43599.435
961941AG1-037 C
Adder
0.69294117647058820.589
961942AG1-037 E
Adder
0.462352941176470630.393
941032AE2-094 E
50/50
30.64130.641
941031AE2-094 C
50/50
68.41468.414
934321AD1-056 C
Adder
8.477647058823537.206
934332AD1-057 E
Adder
2.46235294117647062.093
934322AD1-056 E
Adder
4.59882352941176453.909
934331AD1-057 C
Adder
4.72941176470588154.02
927022AC1-189 E
Adder
5.6541176470588244.806
925595AC1-034 E
Adder
6.702352941176475.697
936262AD2-033 E
Adder
10.6635294117647069.064
939192AE1-149 E
Adder
8.424705882352947.161
939312AE1-162 E
Adder
1.79058823529411781.522
934065AD1-033 E
50/50
7.0817.081
937226AE2-253 E
50/50
8.2398.239
934501AD1-074 C
Adder
46.5682352941176539.583
924517AB2-100 E2
Adder
4.042352941176473.436
957482AF2-042 E
50/50
53.29753.297
961671AG1-007 C
Adder
1.26235294117647071.073
934621AD1-088 C
Adder
13.31176470588235211.315
935172AD1-152 E
Adder
7.6094117647058826.468
913392Y1-086 E
Adder
3.08235294117647072.62
939411AE1-173 C
50/50
149.153149.153
939191AE1-149 C
Adder
12.63647058823529410.741
3143316POE
Adder
1.67647058823529421.425
901082W1-029 E
Adder
44.4776470588235337.806
926206AC1-098 E
Adder
4.9670588235294124.222
3151021BRUNSWICKG1
50/50
13.84413.844
3151041BRUNSWICKG3
50/50
13.84413.844
964791AG1-342 C
Adder
4.6105882352941173.919
316185AD1-033 C
50/50
1.7361.736
944581AF1-123 C
50/50
64.12164.121
941101AE2-104 C
Adder
4.5952941176470593.906
316141AB2-099 E
Adder
0.347058823529411750.295
316088AB2-174 E
Adder
8.997647058823537.648
923994AB2-040_E
Adder
8.487.208
957481AF2-042 C
50/50
79.94679.946
961672AG1-007 E
Adder
0.71529411764705890.608
924322AB2-079 E O1
Adder
1.77764705882352941.511
943902AF1-058 E
Adder
1.65647058823529411.408
961611AG1-000B C
Adder
18.02352941176470615.32
316375AC2-012 C
50/50
1.8781.878
940541AE2-040 C
50/50
4.0974.097
940482AE2-033 E
50/50
15.52815.528
940481AE2-033 C
50/50
23.03323.033
923263AB1-132 E OP
Adder
8.4105882352941177.149
925612AC1-036 E
Adder
1.09882352941176480.934
924312AB2-078 E O1
Adder
1.77764705882352941.511
926274AC1-105 E
Adder
3.4682352941176472.948
316084AB2-161 E
Adder
6.8258823529411765.802
3145946PLYMOUTH TP
Adder
0.44705882352941180.38
933982AD1-022 E
Adder
6.582352941176475.595
940641AE2-051 C
50/50
29.73129.731
3152431Z1-086 GT3
50/50
17.80617.806
3152421Z1-086 GT2
50/50
17.80617.806
927146AC1-208 E
Adder
5.44117647058823554.625
934622AD1-088 E
Adder
6.4094117647058835.448
934612AD1-087 E
50/50
5.1825.182
934611AD1-087 C
50/50
1.7961.796
932046AC2-012 E
50/50
18.21618.216
958161AF2-110 C
Adder
1.8752941176470591.594
316017AA1-139 ULT1
50/50
1.5241.524
938531AE1-072 C
50/50
24.73924.739
3145393UNCAMP
Adder
8.3505882352941197.098
933981AD1-022 C
Adder
12.09058823529411710.277
900672V4-068 E
Adder
0.490588235294117660.417
3152411Z1-086 GT1
50/50
17.81217.812
924302AB2-077 E O1
Adder
1.77764705882352941.511
316349AD2-085 C
Adder
4.5341176470588243.854
935112AD1-144 E
Adder
1.2588235294117651.07
944582AF1-123 E
50/50
146.831146.831
944592AF1-124 E
50/50
147.363147.363
923832AB2-022 E
Adder
1.74000000000000021.479
938772AE1-103 E
Adder
5.5529411764705884.72
916042Z1-036 E
Adder
39.78705882352941433.819
960082AF2-299 E
Adder
1.7247058823529411.466
946281AF1-292 C
Adder
2.14117647058823521.82
926071AC1-086 C
Adder
28.90117647058823624.566
963042AG1-153 E
50/50
14.06814.068
927021AC1-189 C
Adder
11.3505882352941179.648
3151541CLOVER2
50/50
18.07518.075
964241AG1-285 C
Adder
17.3105882352941214.714
924152AB2-059 E OP
Adder
7.0658823529411776.006
962561AG1-105 C
Adder
11.6047058823529429.864
3151101ELIZAR3
50/50
4.524.52
3151081ELIZAR1
50/50
4.4634.463
3151091ELIZAR2
50/50
4.3854.385
316315AB2-025 C
50/50
0.5820.582
946282AF1-292 E
Adder
1.4270588235294121.213
944012AF1-069 E
50/50
8.6848.684
3151051BRUNSWICKS1
50/50
28.7628.76
917512Z2-088 E OP1
Adder
6.5941176470588245.605
3151531CLOVER1
50/50
18.24518.245
3137643SOCKMAN
Adder
0.97882352941176460.832
3151031BRUNSWICKG2
50/50
13.84413.844
919710AA2-057 E
Adder
5.3541176470588244.551
937481AD2-202 C
50/50
0.5210.521
3150921YORKTN3
Adder
64.9600000000000155.216
3145256KINGFORK
Adder
1.35529411764705881.152
925522AC1-027 E
50/50
1.7051.705
926755AC1-161 E
50/50
18.61818.618
933291AC2-141 C
50/50
43.61643.616
941102AE2-104 E
Adder
7.3058823529411766.21
957872AF2-081 E
50/50
6.0346.034
932632AC2-084 E
Adder
4.3905882352941183.732
926214AC1-099 E
Adder
1.64117647058823551.395
964242AG1-285 E
Adder
11.549.809
924162AB2-060 E OP
Adder
5.6588235294117644.81
964792AG1-342 E
Adder
3.07411764705882362.613
942341AE2-247 C
Adder
1.9647058823529411.67
943462AF1-017 E
Adder
2.90117647058823552.466
958162AF2-110 E
Adder
2.98235294117647072.535
316388AE2-253 GEN
50/50
2.7712.771
919153AA1-139 E2
50/50
5.7585.758
934512AD1-075 E
Adder
5.9258823529411765.037
934502AD1-074 E
Adder
23.70588235294117420.15
924516AB2-100 E1
Adder
4.042352941176473.436
918512AA1-065 E OP
Adder
7.6023529411764716.462
940642AE2-051 E
50/50
19.82119.821
966621AG1-532 C
Adder
1.94000000000000021.649
918532AA1-067 E
Adder
0.96823529411764710.823
924022AB2-043 E O1
Adder
6.95.865
3147223TWITTYS
Adder
1.21764705882352931.035
959312AF2-222 E
Adder
14.06705882352941311.957
934576AD1-082 E
Adder
5.4388235294117654.623
916191Z1-068 C
50/50
0.0610.061
933292AC2-141 E
50/50
18.61818.618
316294AC1-161 C
50/50
7.1277.127
944602AF1-125 E
50/50
144.526144.526
3145506HICKORY
50/50
3.0783.078
943612AF1-032 E
Adder
1.28470588235294141.092
957871AF2-081 C
50/50
14.0814.08
940492AE2-034 E
Adder
4.2752941176470593.634
934522AD1-076 E
Adder
8.6200000000000017.327
943172AE2-346 E
Adder
0.8317647058823530.707
918492AA1-063AE OP
Adder
5.6035294117647064.763
917332KELFORD E
Adder
2.25058823529411761.913
925122AB2-169 E
Adder
7.8694117647058836.689
316274AC1-208 C
Adder
12.25411764705882510.416
917342Z2-044 E
Adder
0.80352941176470590.683
937482AD2-202 E
50/50
1.5171.517
3151311EDGECMA
Adder
20.7705882352941217.655
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.99436.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.67827.678
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.7584.758
LAGNLTFEXP_LAGN->PJM
CLTF
9.6549.654
NYPJM->LTFIMP_NY
CLTF
2.22.2
LGEELTFEXP_LGEE->PJM
CLTF
1.4681.468
WECLTFEXP_WEC->PJM
CLTF
0.7690.769
G-007PJM->LTFIMP_G-007
CMTX_NF
4.7394.739
SIGELTFEXP_SIGE->PJM
CLTF
0.2910.291
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.3487.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
126.03126.03
CPLELTFEXP_CPLE->PJM
CLTF
15.41515.415
TVALTFEXP_TVA->PJM
CLTF
7.567.56
O66PJM->LTFIMP_O-066
CMTX_NF
30.16830.168

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T567_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.4 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4073.91
MW Contribution:24.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316185AD1-033 C
50/50
1.9451.945
944581AF1-123 C
50/50
71.8771.87
941101AE2-104 C
Adder
5.0270588235294114.273
316141AB2-099 E
Adder
0.36941176470588240.314
3152331SURRY 2
50/50
39.09539.095
943461AF1-017 C
Adder
1.89411764705882371.61
932596AC2-079 E
Adder
13.2447058823529411.258
316311AC2-079 C
Adder
8.117647058823536.9
938532AE1-072 E
50/50
14.39614.396
3146326AYDLETT TAP
50/50
2.1292.129
917122Z2-027 E
Adder
2.08705882352941161.774
920692AA2-178 E
Adder
6.2129411764705885.281
966622AG1-532 E
Adder
1.3352941176470591.135
3152441Z1-086 ST
50/50
32.43132.431
922923AB1-081 E OP
Adder
5.2094117647058834.428
926662AC1-147 E
Adder
2.05411764705882361.746
916192Z1-068 E
50/50
2.9452.945
957492AF2-043 E
Adder
2.18823529411764731.86
923852AB2-025 E
Adder
1.6847058823529411.432
939412AE1-173 E
50/50
106.866106.866
961941AG1-037 C
Adder
0.740.629
961942AG1-037 E
Adder
0.49294117647058820.419
941032AE2-094 E
50/50
32.08232.082
941031AE2-094 C
50/50
71.63171.631
934321AD1-056 C
Adder
8.844705882352947.518
934332AD1-057 E
Adder
2.56941176470588272.184
934322AD1-056 E
Adder
4.797647058823534.078
934331AD1-057 C
Adder
4.9341176470588244.194
936666AD2-085 E
Adder
7.8811764705882356.699
941591AE2-156 C
50/50
27.78727.787
316316AC1-027 C
50/50
0.4950.495
944601AF1-125 C
50/50
70.76370.763
944591AF1-124 C
50/50
72.12672.126
938771AE1-103 C
Adder
4.3517647058823533.699
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.6705882352941182.27
926072AC1-086 E
Adder
13.70588235294117811.65
944011AF1-069 C
50/50
23.40523.405
963041AG1-153 C
50/50
9.8059.805
936261AD2-033 C
Adder
5.8058823529411764.935
962562AG1-105 E
Adder
7.9482352941176486.756
3150921YORKTN3
Adder
148.4764705882353126.205
3145256KINGFORK
Adder
1.49058823529411751.267
925522AC1-027 E
50/50
1.9061.906
926755AC1-161 E
50/50
21.46921.469
933291AC2-141 C
50/50
50.29350.293
941102AE2-104 E
Adder
7.99294117647058756.794
957872AF2-081 E
50/50
6.7436.743
932632AC2-084 E
Adder
4.623.927
926214AC1-099 E
Adder
1.72705882352941181.468
964242AG1-285 E
Adder
11.85176470588235310.074
924162AB2-060 E OP
Adder
5.8058823529411764.935
964792AG1-342 E
Adder
3.1588235294117652.685
942342AE2-247 E
Adder
2.89058823529411772.457
316018AA1-139 ULT2
50/50
1.7031.703
919152AA1-139 E1
50/50
6.4346.434
920042AA2-088 E OP
Adder
15.5623529411764713.228
934511AD1-075 C
Adder
12.6152941176470610.723
934521AD1-076 C
Adder
18.32705882352941315.578
3145723EMPORIA
Adder
0.61647058823529410.524
923573AB1-173 E OP
Adder
4.6976470588235293.993
919692AA2-053 E OP
Adder
6.08588235294117655.173
925785AC1-054 E
Adder
4.8317647058823534.107
316263AC1-034 C
Adder
9.287.888
959311AF2-222 C
Adder
21.34470588235294418.143
927022AC1-189 E
Adder
5.9647058823529415.07
925595AC1-034 E
Adder
7.0011764705882355.951
939312AE1-162 E
Adder
1.93058823529411771.641
3150991CHESPKB
50/50
1.121.12
934065AD1-033 E
50/50
7.9347.934
937226AE2-253 E
50/50
9.2149.214
934501AD1-074 C
Adder
50.4623529411764742.893
924517AB2-100 E2
Adder
4.1635294117647063.539
957482AF2-042 E
Adder
55.2517647058823546.964
961671AG1-007 C
Adder
1.32588235294117651.127
934621AD1-088 C
Adder
13.7211.662
935172AD1-152 E
Adder
7.8611764705882366.682
913392Y1-086 E
Adder
3.42705882352941152.913
939411AE1-173 C
50/50
160.299160.299
3137643SOCKMAN
Adder
1.02117647058823540.868
3151031BRUNSWICKG2
50/50
14.47314.473
919710AA2-057 E
Adder
5.6082352941176474.767
3143316POE
Adder
1.61411764705882371.372
901082W1-029 E
Adder
49.1811764705882441.804
926206AC1-098 E
Adder
5.2270588235294114.443
3151021BRUNSWICKG1
50/50
14.47314.473
3151041BRUNSWICKG3
50/50
14.47314.473
964791AG1-342 C
Adder
4.737647058823534.027
316088AB2-174 E
Adder
9.3282352941176477.929
923994AB2-040_E
Adder
8.8082352941176477.487
957481AF2-042 C
Adder
82.8776470588235370.446
961672AG1-007 E
Adder
0.7517647058823530.639
924322AB2-079 E O1
Adder
1.82588235294117651.552
943902AF1-058 E
Adder
1.70235294117647061.447
942341AE2-247 C
Adder
2.09411764705882361.78
943462AF1-017 E
Adder
3.09058823529411742.627
958162AF2-110 E
Adder
3.2635294117647062.774
316388AE2-253 GEN
50/50
3.0993.099
919153AA1-139 E2
50/50
6.4346.434
934512AD1-075 E
Adder
6.422352941176475.459
934502AD1-074 E
Adder
25.6882352941176521.835
924516AB2-100 E1
Adder
4.1635294117647063.539
918512AA1-065 E OP
Adder
8.1494117647058816.927
940642AE2-051 E
50/50
21.07921.079
966621AG1-532 C
Adder
2.00352941176470621.703
918532AA1-067 E
Adder
1.02588235294117650.872
924022AB2-043 E O1
Adder
7.0847058823529416.022
3147223TWITTYS
Adder
1.241.054
959312AF2-222 E
Adder
14.30117647058823712.156
961611AG1-000B C
Adder
18.65882352941176615.86
316375AC2-012 C
50/50
2.0942.094
940541AE2-040 C
Adder
4.16470588235294153.54
940482AE2-033 E
Adder
15.81058823529411813.439
940481AE2-033 C
Adder
23.45176470588235419.934
923263AB1-132 E OP
Adder
8.7635294117647067.449
925612AC1-036 E
Adder
1.11882352941176480.951
924312AB2-078 E O1
Adder
1.82588235294117651.552
926274AC1-105 E
Adder
3.5647058823529413.03
316084AB2-161 E
Adder
6.937647058823535.897
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
933982AD1-022 E
Adder
7.11294117647058856.046
940641AE2-051 C
50/50
31.61831.618
3152431Z1-086 GT3
50/50
18.62518.625
3152421Z1-086 GT2
50/50
18.62518.625
927146AC1-208 E
Adder
5.7070588235294124.851
934622AD1-088 E
Adder
6.6058823529411775.615
934612AD1-087 E
Adder
5.3611764705882364.557
932046AC2-012 E
50/50
20.31420.314
958161AF2-110 C
Adder
2.0517647058823531.744
316017AA1-139 ULT1
50/50
1.7031.703
938531AE1-072 C
50/50
27.61527.615
3145393UNCAMP
Adder
9.017647058823537.665
933981AD1-022 C
Adder
13.06588235294117711.106
900672V4-068 E
Adder
0.52235294117647060.444
3152411Z1-086 GT1
50/50
18.63118.631
924302AB2-077 E O1
Adder
1.82588235294117651.552
316349AD2-085 C
Adder
4.8305882352941174.106
935112AD1-144 E
Adder
1.3835294117647061.176
944582AF1-123 E
50/50
164.574164.574
944592AF1-124 E
50/50
165.171165.171
923832AB2-022 E
Adder
1.93411764705882351.644
938772AE1-103 E
Adder
6.0094117647058825.108
916042Z1-036 E
Adder
43.71058823529412537.154
960082AF2-299 E
Adder
1.78117647058823541.514
946281AF1-292 C
Adder
2.21058823529411751.879
926071AC1-086 C
Adder
30.1129411764705925.596
963042AG1-153 E
50/50
14.70814.708
927021AC1-189 C
Adder
11.97411764705882410.178
964241AG1-285 C
Adder
17.77647058823529515.11
924152AB2-059 E OP
Adder
7.3811764705882366.274
962561AG1-105 C
Adder
11.92235294117647210.134
3151101ELIZAR3
50/50
5.0455.045
3151081ELIZAR1
50/50
4.9824.982
3151091ELIZAR2
50/50
4.8954.895
946282AF1-292 E
Adder
1.47411764705882351.253
944012AF1-069 E
50/50
9.0929.092
3151051BRUNSWICKS1
50/50
30.06830.068
917512Z2-088 E OP1
Adder
6.9388235294117645.898
934576AD1-082 E
Adder
5.5282352941176474.699
916191Z1-068 C
50/50
0.0690.069
933292AC2-141 E
50/50
21.46921.469
316294AC1-161 C
50/50
8.2198.219
944602AF1-125 E
50/50
161.991161.991
3145506HICKORY
50/50
3.4483.448
943612AF1-032 E
Adder
1.42235294117647081.209
957871AF2-081 C
50/50
15.73315.733
940492AE2-034 E
Adder
4.663.961
934522AD1-076 E
Adder
9.3411764705882367.94
943172AE2-346 E
Adder
0.88823529411764710.755
918492AA1-063AE OP
Adder
5.9070588235294125.021
917332KELFORD E
Adder
2.39058823529411772.032
925122AB2-169 E
Adder
8.4411764705882367.175
316274AC1-208 C
Adder
12.85294117647058910.925
917342Z2-044 E
Adder
0.84117647058823530.715
937482AD2-202 E
Adder
1.56941176470588251.334
3151311EDGECMA
Adder
21.6952941176470618.441
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.34332.343
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.24226.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.3444.344
LAGNLTFEXP_LAGN->PJM
CLTF
9.3599.359
NYPJM->LTFIMP_NY
CLTF
2.0052.005
LGEELTFEXP_LGEE->PJM
CLTF
1.2871.287
WECLTFEXP_WEC->PJM
CLTF
0.6770.677
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2584.258
SIGELTFEXP_SIGE->PJM
CLTF
0.2610.261
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.5637.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
128.067128.067
CPLELTFEXP_CPLE->PJM
CLTF
15.87115.871
TVALTFEXP_TVA->PJM
CLTF
7.2977.297
O66PJM->LTFIMP_O-066
CMTX_NF
27.12727.127

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.99 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4294.13
MW Contribution:22.88
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
16.1505882352941213.728
316233AE1-074 C
50/50
4.1784.178
943461AF1-017 C
Adder
2.1352941176470591.815
932596AC2-079 E
Adder
14.80823529411764712.587
316311AC2-079 C
Adder
9.0764705882352947.715
938532AE1-072 E
Adder
14.59294117647058912.404
3146326AYDLETT TAP
Adder
2.161.836
917122Z2-027 E
Adder
2.12941176470588231.81
920692AA2-178 E
Adder
6.45.44
966622AG1-532 E
Adder
1.43647058823529421.221
3152441Z1-086 ST
50/50
30.16230.162
944641AF1-129 C
Adder
153.60588235294117130.565
316240AF1-291 C
Adder
3.2635294117647062.774
924814AB2-134 E
Adder
19.07058823529411716.21
942342AE2-247 E
Adder
3.262.771
919152AA1-139 E1
Adder
6.5152941176470595.538
920042AA2-088 E OP
Adder
16.40941176470588313.948
934511AD1-075 C
Adder
13.02705882352941211.073
934521AD1-076 C
Adder
18.92352941176470816.085
3145723EMPORIA
Adder
0.66117647058823540.562
923573AB1-173 E OP
Adder
5.0141176470588234.262
925332AB2-190 E
Adder
12.07529411764705810.264
927226AC1-216 E
Adder
11.6423529411764739.896
936666AD2-085 E
Adder
8.8858823529411777.553
941591AE2-156 C
50/50
28.55328.553
316316AC1-027 C
50/50
0.5040.504
944601AF1-125 C
50/50
71.42271.422
944591AF1-124 C
50/50
72.79772.797
938771AE1-103 C
Adder
4.5952941176470593.906
3145413WATKINS
Adder
1.07882352941176470.917
960081AF2-299 C
Adder
2.87294117647058832.442
926072AC1-086 E
Adder
14.54823529411764812.366
944011AF1-069 C
50/50
21.6121.61
963041AG1-153 C
50/50
9.159.15
3150831SPRUNCA
Adder
14.05529411764705811.947
3150841SPRUNCB
Adder
14.05529411764705811.947
926662AC1-147 E
Adder
2.1117647058823531.795
916192Z1-068 E
50/50
3.0013.001
957492AF2-043 E
Adder
2.25882352941176471.92
923852AB2-025 E
50/50
1.8511.851
939412AE1-173 E
50/50
100.688100.688
923862AB2-026 E
Adder
1.9247058823529411.636
961941AG1-037 C
Adder
0.77294117647058820.657
961942AG1-037 E
Adder
0.51529411764705880.438
941032AE2-094 E
50/50
29.62229.622
941031AE2-094 C
50/50
66.13866.138
942001AE2-212 C
Adder
3.34588235294117632.844
939192AE1-149 E
Adder
11.2529411764705879.565
939312AE1-162 E
Adder
2.22705882352941181.893
934065AD1-033 E
50/50
8.0198.019
937226AE2-253 E
Adder
9.322352941176477.924
934501AD1-074 C
Adder
52.1070588235294144.291
958502AF2-144 E
Adder
1.89058823529411771.607
924517AB2-100 E2
Adder
4.4917647058823533.818
957482AF2-042 E
Adder
55.1988235294117646.919
934621AD1-088 C
Adder
14.36470588235294312.21
940432AE2-027 E
Adder
13.04588235294117711.089
934012AD1-025 E
Adder
15.07294117647058812.812
913392Y1-086 E
Adder
3.48941176470588272.966
939411AE1-173 C
50/50
151.032151.032
933502AC2-165 E
Adder
11.189.503
3137643SOCKMAN
Adder
1.08470588235294120.922
3151031BRUNSWICKG2
50/50
13.50613.506
939191AE1-149 C
Adder
16.88000000000000314.348
3143316POE
50/50
2.1752.175
901082W1-029 E
Adder
50.41764705882352642.855
3151021BRUNSWICKG1
50/50
13.50613.506
3151041BRUNSWICKG3
50/50
13.50613.506
940431AE2-027 C
Adder
19.56823529411764516.633
942002AE2-212 E
Adder
2.23058823529411751.896
316185AD1-033 C
50/50
1.9651.965
944581AF1-123 C
50/50
72.53972.539
941101AE2-104 C
Adder
5.3141176470588244.517
316141AB2-099 E
Adder
0.38705882352941180.329
316088AB2-174 E
Adder
9.988.483
923994AB2-040_E
Adder
9.4011764705882357.991
957481AF2-042 C
Adder
82.7976470588235370.378
961611AG1-000B C
Adder
24.2858823529411820.643
316375AC2-012 C
50/50
2.1542.154
940541AE2-040 C
50/50
4.5764.576
940482AE2-033 E
50/50
17.33217.332
940481AE2-033 C
50/50
25.70925.709
923263AB1-132 E OP
Adder
9.3023529411764717.907
316084AB2-161 E
Adder
8.717647058823537.41
3145946PLYMOUTH TP
Adder
0.50.425
933982AD1-022 E
Adder
7.3576470588235296.254
940641AE2-051 C
50/50
29.19229.192
316336AC2-165 C
Adder
14.85411764705882312.626
3152431Z1-086 GT3
50/50
17.32217.322
3152421Z1-086 GT2
50/50
17.32217.322
934622AD1-088 E
Adder
6.9164705882352945.879
934612AD1-087 E
Adder
5.42823529411764754.614
3150731STONECA
Adder
10.1976470588235298.668
935161AD1-151 C
Adder
24.22470588235294320.591
932046AC2-012 E
50/50
20.89320.893
958161AF2-110 C
Adder
2.16823529411764731.843
938531AE1-072 C
Adder
27.99411764705882523.795
3145393UNCAMP
Adder
9.5200000000000018.092
933981AD1-022 C
Adder
13.5152941176470611.488
900672V4-068 E
Adder
0.54941176470588240.467
3152411Z1-086 GT1
50/50
17.32817.328
316349AD2-085 C
Adder
5.4458823529411764.629
935112AD1-144 E
Adder
1.48117647058823531.259
944582AF1-123 E
50/50
166.107166.107
944592AF1-124 E
50/50
166.709166.709
923832AB2-022 E
Adder
1.96941176470588241.674
938772AE1-103 E
Adder
6.3458823529411775.394
916042Z1-036 E
Adder
44.8811764705882438.149
960082AF2-299 E
Adder
1.91529411764705881.628
946281AF1-292 C
Adder
2.37764705882352922.021
926071AC1-086 C
Adder
31.96588235294117627.171
963042AG1-153 E
50/50
13.72513.725
3151101ELIZAR3
50/50
5.1725.172
3151081ELIZAR1
50/50
5.1085.108
3151091ELIZAR2
50/50
5.0195.019
316315AB2-025 C
50/50
0.650.65
946282AF1-292 E
Adder
1.58588235294117651.348
944012AF1-069 E
50/50
8.3958.395
3151051BRUNSWICKS1
50/50
28.05928.059
938552AE1-074 E
50/50
2.1052.105
3150921YORKTN3
Adder
175.7670588235294149.402
3145256KINGFORK
Adder
1.5952941176470591.356
925522AC1-027 E
50/50
1.9431.943
926755AC1-161 E
50/50
20.7620.76
933291AC2-141 C
50/50
48.63248.632
941102AE2-104 E
Adder
8.4494117647058827.182
957872AF2-081 E
Adder
6.8282352941176485.804
938562AE1-075 E
Adder
1.64117647058823551.395
942341AE2-247 C
Adder
2.362.006
943462AF1-017 E
Adder
3.48470588235294132.962
958162AF2-110 E
Adder
3.4494117647058822.932
919153AA1-139 E2
Adder
6.5152941176470595.538
934512AD1-075 E
Adder
6.6317647058823535.637
934502AD1-074 E
Adder
26.5247058823529422.546
924516AB2-100 E1
Adder
4.4917647058823533.818
918512AA1-065 E OP
Adder
0.250588235294117670.213
940642AE2-051 E
50/50
19.46119.461
966621AG1-532 C
Adder
2.15411764705882371.831
3150651CHESTF6
Adder
27.96823529411764823.773
946262AF1-291 E
Adder
2.17647058823529441.85
934576AD1-082 E
Adder
6.9458823529411775.904
916191Z1-068 C
50/50
0.070.07
933292AC2-141 E
50/50
20.7620.76
316294AC1-161 C
50/50
7.9477.947
944602AF1-125 E
50/50
163.5163.5
3145506HICKORY
50/50
3.4833.483
943612AF1-032 E
Adder
1.4682352941176471.248
957871AF2-081 C
Adder
15.93294117647058713.543
940492AE2-034 E
Adder
4.84.08
934522AD1-076 E
Adder
9.6458823529411778.199
943172AE2-346 E
Adder
0.92823529411764720.789
918492AA1-063AE OP
Adder
6.2388235294117655.303
937482AD2-202 E
Adder
1.58941176470588231.351
316303AF2-085
50/50
6.8996.899
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.00241.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.98729.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.2215.221
LAGNLTFEXP_LAGN->PJM
CLTF
10.36610.366
NYPJM->LTFIMP_NY
CLTF
2.7212.721
LGEELTFEXP_LGEE->PJM
CLTF
1.6421.642
WECLTFEXP_WEC->PJM
CLTF
0.8540.854
G-007PJM->LTFIMP_G-007
CMTX_NF
5.8875.887
SIGELTFEXP_SIGE->PJM
CLTF
0.3220.322
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6737.673
CBM South 2LTFEXP_CBM-S2->PJM
CBM
132.286132.286
CPLELTFEXP_CPLE->PJM
CLTF
16.09616.096
TVALTFEXP_TVA->PJM
CLTF
8.1488.148
O66PJM->LTFIMP_O-066
CMTX_NF
37.46537.465

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.84 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4130.73
MW Contribution:22.74
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.16 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4734.49
MW Contribution:23.03
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316349AD2-085 C
Adder
5.3835294117647054.576
935112AD1-144 E
Adder
1.48470588235294131.262
944582AF1-123 E
50/50
167.759167.759
944592AF1-124 E
50/50
168.367168.367
923832AB2-022 E
Adder
1.98352941176470581.686
938772AE1-103 E
Adder
6.3270588235294125.378
916042Z1-036 E
Adder
45.0211764705882438.268
960082AF2-299 E
Adder
1.88000000000000011.598
946281AF1-292 C
Adder
2.33411764705882341.984
926071AC1-086 C
Adder
31.48235294117647226.76
963042AG1-153 E
50/50
13.64513.645
964241AG1-285 C
Adder
18.8416.014
3151101ELIZAR3
50/50
5.2135.213
3151081ELIZAR1
50/50
5.1485.148
3151091ELIZAR2
50/50
5.0595.059
946282AF1-292 E
Adder
1.5564705882352941.323
944012AF1-069 E
50/50
8.3568.356
3151051BRUNSWICKS1
50/50
27.89627.896
3150831SPRUNCA
Adder
12.67882352941176410.777
3150841SPRUNCB
Adder
12.67882352941176410.777
926662AC1-147 E
Adder
2.12823529411764721.809
916192Z1-068 E
50/50
3.0273.027
957492AF2-043 E
Adder
2.2717647058823531.931
923852AB2-025 E
Adder
1.80470588235294121.534
939412AE1-173 E
50/50
100.92100.92
923862AB2-026 E
Adder
1.7964705882352941.527
940431AE2-027 C
Adder
18.18352941176470615.456
942002AE2-212 E
Adder
2.0811764705882351.769
316185AD1-033 C
50/50
1.9851.985
944581AF1-123 C
50/50
73.26173.261
941101AE2-104 C
Adder
5.3152941176470594.518
316141AB2-099 E
Adder
0.38352941176470590.326
316088AB2-174 E
Adder
9.8129411764705888.341
923994AB2-040_E
Adder
9.2505882352941197.863
957481AF2-042 C
Adder
81.8317647058823669.557
935162AD1-151 E
Adder
15.4776470588235313.156
316233AE1-074 C
50/50
3.8433.843
943461AF1-017 C
Adder
2.1105882352941181.794
932596AC2-079 E
Adder
14.6612.461
316311AC2-079 C
Adder
8.9858823529411777.638
938532AE1-072 E
Adder
14.7176470588235312.51
3146326AYDLETT TAP
Adder
2.17764705882352951.851
917122Z2-027 E
Adder
2.1435294117647061.822
920692AA2-178 E
Adder
6.4035294117647065.443
966622AG1-532 E
Adder
1.41058823529411771.199
3152441Z1-086 ST
50/50
29.99829.998
944641AF1-129 C
Adder
134.3435294117647114.192
316240AF1-291 C
Adder
3.0047058823529412.554
924814AB2-134 E
Adder
18.37647058823529315.62
942342AE2-247 E
Adder
3.22235294117647042.739
919152AA1-139 E1
Adder
6.57294117647058855.587
920042AA2-088 E OP
Adder
16.29647058823529413.852
934511AD1-075 C
Adder
13.00823529411764811.057
934521AD1-076 C
Adder
18.8976470588235316.063
3145723EMPORIA
Adder
0.65058823529411770.553
923573AB1-173 E OP
Adder
4.9341176470588244.194
919692AA2-053 E OP
Adder
6.3423529411764715.391
942001AE2-212 C
Adder
3.1211764705882352.653
939192AE1-149 E
Adder
10.7800000000000019.163
939312AE1-162 E
Adder
2.21058823529411751.879
934065AD1-033 E
50/50
8.0978.097
937226AE2-253 E
50/50
9.4079.407
934501AD1-074 C
Adder
52.03294117647059444.228
958502AF2-144 E
Adder
1.76470588235294111.5
924517AB2-100 E2
Adder
4.4035294117647063.743
957482AF2-042 E
Adder
54.5552941176470646.372
934621AD1-088 C
Adder
14.14588235294117512.024
942341AE2-247 C
Adder
2.33294117647058831.983
943462AF1-017 E
Adder
3.44470588235294132.928
958162AF2-110 E
Adder
3.45058823529411772.933
316388AE2-253 GEN
50/50
3.1643.164
919153AA1-139 E2
Adder
6.57294117647058855.587
934512AD1-075 E
Adder
6.622352941176475.629
934502AD1-074 E
Adder
26.48705882352941322.514
924516AB2-100 E1
Adder
4.4035294117647063.743
918512AA1-065 E OP
Adder
8.4305882352941197.166
940642AE2-051 E
50/50
19.46619.466
966621AG1-532 C
Adder
2.11529411764705881.798
940432AE2-027 E
Adder
12.12235294117647110.304
934012AD1-025 E
Adder
14.52470588235294212.346
913392Y1-086 E
Adder
3.51411764705882362.987
939411AE1-173 C
50/50
151.38151.38
3137643SOCKMAN
Adder
1.06823529411764720.908
3151031BRUNSWICKG2
50/50
13.42813.428
938552AE1-074 E
50/50
1.9361.936
316160AE1-175 E
Adder
1.67529411764705881.424
3150921YORKTN3
Adder
176.88117647058823150.349
3145256KINGFORK
Adder
1.61.36
925522AC1-027 E
50/50
1.961.96
926755AC1-161 E
50/50
21.18321.183
933291AC2-141 C
50/50
49.62549.625
941102AE2-104 E
Adder
8.4505882352941187.183
957872AF2-081 E
Adder
6.88823529411764755.855
938562AE1-075 E
Adder
1.53176470588235311.302
964242AG1-285 E
Adder
12.5610.676
946262AF1-291 E
Adder
2.00235294117647071.702
934576AD1-082 E
Adder
6.7411764705882365.73
916191Z1-068 C
50/50
0.0710.071
933292AC2-141 E
50/50
21.18321.183
316294AC1-161 C
50/50
8.1098.109
944602AF1-125 E
50/50
165.126165.126
3145506HICKORY
50/50
3.5173.517
943612AF1-032 E
Adder
1.4764705882352941.255
957871AF2-081 C
Adder
16.07411764705882413.663
940492AE2-034 E
Adder
4.8023529411764714.082
934522AD1-076 E
Adder
9.6317647058823528.187
943172AE2-346 E
Adder
0.92117647058823540.783
918492AA1-063AE OP
Adder
6.1705882352941185.245
917332KELFORD E
Adder
2.4741176470588242.103
925122AB2-169 E
Adder
8.6764705882352937.375
937482AD2-202 E
Adder
1.5682352941176471.333
939191AE1-149 C
Adder
16.1694117647058813.744
3143316POE
Adder
2.0705882352941181.76
901082W1-029 E
Adder
50.6800000000000143.078
3151021BRUNSWICKG1
50/50
13.42813.428
3151041BRUNSWICKG3
50/50
13.42813.428
961611AG1-000B C
Adder
23.7620.196
316375AC2-012 C
50/50
2.172.17
940541AE2-040 C
Adder
4.4623529411764713.793
940482AE2-033 E
Adder
16.9129411764705914.376
940481AE2-033 C
Adder
25.0882352941176521.325
923263AB1-132 E OP
Adder
9.162352941176477.788
961941AG1-037 C
Adder
0.76823529411764710.653
961942AG1-037 E
Adder
0.51176470588235290.435
941032AE2-094 E
50/50
29.48329.483
941031AE2-094 C
50/50
65.82865.828
925332AB2-190 E
Adder
11.5164705882352939.789
927226AC1-216 E
Adder
11.2188235294117659.536
962962AG1-145 E
Adder
2.0305882352941181.726
936666AD2-085 E
Adder
8.7835294117647067.466
941591AE2-156 C
50/50
28.7728.77
316316AC1-027 C
50/50
0.5090.509
944601AF1-125 C
50/50
72.13372.133
944591AF1-124 C
50/50
73.52173.521
938771AE1-103 C
Adder
4.582352941176473.895
3145413WATKINS
Adder
1.07411764705882360.913
960081AF2-299 C
Adder
2.822.397
926072AC1-086 E
Adder
14.32823529411764712.179
944011AF1-069 C
50/50
21.50921.509
963041AG1-153 C
50/50
9.0979.097
316084AB2-161 E
Adder
8.467.191
3145946PLYMOUTH TP
Adder
0.50.425
933982AD1-022 E
Adder
7.346.239
940641AE2-051 C
50/50
29.19929.199
3152431Z1-086 GT3
50/50
17.22717.227
3152421Z1-086 GT2
50/50
17.22717.227
934622AD1-088 E
Adder
6.8105882352941185.789
934612AD1-087 E
Adder
5.3588235294117644.555
3150731STONECA
Adder
9.5694117647058838.134
935161AD1-151 C
Adder
23.2152941176470619.733
932046AC2-012 E
50/50
21.04921.049
958161AF2-110 C
Adder
2.16941176470588241.844
938531AE1-072 C
Adder
28.2329411764705923.998
3145393UNCAMP
Adder
9.4858823529411778.063
933981AD1-022 C
Adder
13.48352941176470711.461
900672V4-068 E
Adder
0.54588235294117650.464
3152411Z1-086 GT1
50/50
17.23317.233
316303AF2-085
50/50
6.4766.476
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.34537.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.31928.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8474.847
LAGNLTFEXP_LAGN->PJM
CLTF
9.8929.892
NYPJM->LTFIMP_NY
CLTF
2.5392.539
LGEELTFEXP_LGEE->PJM
CLTF
1.4991.499
WECLTFEXP_WEC->PJM
CLTF
0.780.78
G-007PJM->LTFIMP_G-007
CMTX_NF
5.4635.463
SIGELTFEXP_SIGE->PJM
CLTF
0.2970.297
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.547.54
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.173129.173
CPLELTFEXP_CPLE->PJM
CLTF
15.81915.819
TVALTFEXP_TVA->PJM
CLTF
7.767.76
O66PJM->LTFIMP_O-066
CMTX_NF
34.77734.777

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.96 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4056.64
MW Contribution:21.88
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
14.89411764705882412.66
316233AE1-074 C
50/50
3.8973.897
943461AF1-017 C
Adder
2.01.7
932596AC2-079 E
Adder
13.86941176470588211.789
316311AC2-079 C
Adder
8.5011764705882367.226
938532AE1-072 E
Adder
13.7176470588235311.66
3146326AYDLETT TAP
Adder
2.02941176470588271.725
917122Z2-027 E
Adder
2.00235294117647071.702
920692AA2-178 E
Adder
6.0258823529411775.122
966622AG1-532 E
Adder
1.35764705882352941.154
3152441Z1-086 ST
50/50
28.84928.849
925332AB2-190 E
Adder
11.1200000000000019.452
927226AC1-216 E
Adder
10.7541176470588239.141
936666AD2-085 E
Adder
8.327.072
941591AE2-156 C
50/50
26.80726.807
316316AC1-027 C
50/50
0.4740.474
944601AF1-125 C
50/50
67.12767.127
944591AF1-124 C
50/50
68.4268.42
938771AE1-103 C
Adder
4.3211764705882353.673
3145413WATKINS
Adder
1.0152941176470590.863
960081AF2-299 C
Adder
2.7152941176470592.308
926072AC1-086 E
Adder
13.7423529411764711.681
944011AF1-069 C
50/50
20.67620.676
963041AG1-153 C
50/50
8.758.75
938552AE1-074 E
50/50
1.9631.963
3150921YORKTN3
Adder
163.19176470588235138.713
3145256KINGFORK
Adder
1.49529411764705871.271
925522AC1-027 E
50/50
1.8261.826
926755AC1-161 E
50/50
19.5219.52
933291AC2-141 C
50/50
45.72845.728
941102AE2-104 E
Adder
7.9317647058823536.742
957872AF2-081 E
Adder
6.4188235294117665.456
938562AE1-075 E
Adder
1.55058823529411781.318
944641AF1-129 C
Adder
140.53529411764706119.455
316240AF1-291 C
Adder
2.99294117647058842.544
924814AB2-134 E
Adder
17.61647058823529514.974
942342AE2-247 E
Adder
3.0517647058823532.594
919152AA1-139 E1
Adder
6.1235294117647065.205
920042AA2-088 E OP
Adder
15.46470588235294113.145
934511AD1-075 C
Adder
12.27176470588235310.431
934521AD1-076 C
Adder
17.82705882352941315.153
3145723EMPORIA
Adder
0.62588235294117660.532
923573AB1-173 E OP
Adder
4.744.029
3150831SPRUNCA
Adder
12.87647058823529510.945
3150841SPRUNCB
Adder
12.87647058823529510.945
926662AC1-147 E
Adder
1.98235294117647071.685
916192Z1-068 E
50/50
2.8192.819
957492AF2-043 E
Adder
2.12235294117647081.804
923852AB2-025 E
50/50
1.7471.747
939412AE1-173 E
50/50
95.76595.765
923862AB2-026 E
Adder
1.81882352941176471.546
941032AE2-094 E
50/50
28.34228.342
941031AE2-094 C
50/50
63.2863.28
942001AE2-212 C
Adder
3.08941176470588232.626
939192AE1-149 E
Adder
10.4635294117647078.894
939312AE1-162 E
Adder
2.07764705882352941.766
934065AD1-033 E
50/50
7.5367.536
937226AE2-253 E
Adder
8.7623529411764727.448
934501AD1-074 C
Adder
49.0858823529411841.723
958502AF2-144 E
Adder
1.78705882352941181.519
924517AB2-100 E2
Adder
4.2411764705882353.605
957482AF2-042 E
Adder
52.67882352941176544.777
934621AD1-088 C
Adder
13.69411764705882511.64
940432AE2-027 E
Adder
11.99411764705882410.195
934012AD1-025 E
Adder
13.92352941176470811.835
913392Y1-086 E
Adder
3.282.788
939411AE1-173 C
50/50
143.648143.648
933502AC2-165 E
Adder
10.5564705882352968.973
3137643SOCKMAN
Adder
1.02470588235294110.871
3151031BRUNSWICKG2
50/50
12.91612.916
939191AE1-149 C
Adder
15.69529411764705913.341
3143316POE
50/50
2.0282.028
901082W1-029 E
Adder
47.440.29
3151021BRUNSWICKG1
50/50
12.91612.916
3151041BRUNSWICKG3
50/50
12.91612.916
940431AE2-027 C
Adder
17.9905882352941215.292
942002AE2-212 E
Adder
2.0588235294117651.75
316185AD1-033 C
50/50
1.8471.847
944581AF1-123 C
50/50
68.17868.178
941101AE2-104 C
Adder
4.9894117647058824.241
316088AB2-174 E
Adder
9.4352941176470598.02
923994AB2-040_E
Adder
8.8870588235294117.554
957481AF2-042 C
Adder
79.0188235294117667.166
942341AE2-247 C
Adder
2.21058823529411751.879
961611AG1-000B C
Adder
22.53529411764706219.155
316375AC2-012 C
50/50
2.0222.022
940541AE2-040 C
50/50
4.3194.319
940482AE2-033 E
50/50
16.3616.36
940481AE2-033 C
50/50
24.26824.268
923263AB1-132 E OP
Adder
8.7870588235294127.469
316084AB2-161 E
Adder
8.1282352941176486.909
3145946PLYMOUTH TP
Adder
0.47058823529411770.4
933982AD1-022 E
Adder
6.9329411764705885.893
940641AE2-051 C
50/50
27.86227.862
316336AC2-165 C
Adder
14.02588235294117811.922
3152431Z1-086 GT3
50/50
16.56716.567
3152421Z1-086 GT2
50/50
16.56716.567
934622AD1-088 E
Adder
6.5941176470588245.605
934612AD1-087 E
Adder
5.17764705882352954.401
935161AD1-151 C
Adder
22.3418.989
932046AC2-012 E
50/50
19.61519.615
958161AF2-110 C
Adder
2.03529411764705871.73
938531AE1-072 C
Adder
26.31411764705882622.367
3145393UNCAMP
Adder
8.9552941176470597.612
933981AD1-022 C
Adder
12.73411764705882410.824
900672V4-068 E
Adder
0.51764705882352950.44
3152411Z1-086 GT1
50/50
16.57316.573
316349AD2-085 C
Adder
5.09882352941176454.334
935112AD1-144 E
Adder
1.3882352941176471.18
944582AF1-123 E
50/50
156.119156.119
944592AF1-124 E
50/50
156.684156.684
923832AB2-022 E
Adder
1.8517647058823531.574
938772AE1-103 E
Adder
5.9670588235294125.072
916042Z1-036 E
Adder
42.2247058823529435.891
960082AF2-299 E
Adder
1.81058823529411761.539
946281AF1-292 C
Adder
2.24823529411764731.911
926071AC1-086 C
Adder
30.19411764705882525.665
963042AG1-153 E
50/50
13.12513.125
964241AG1-285 C
Adder
12.04352941176470710.237
3151101ELIZAR3
50/50
4.8574.857
3151081ELIZAR1
50/50
4.7964.796
3151091ELIZAR2
50/50
4.7134.713
316315AB2-025 C
50/50
0.6130.613
946282AF1-292 E
Adder
1.49882352941176471.274
944012AF1-069 E
50/50
8.0328.032
3151051BRUNSWICKS1
50/50
26.83226.832
943462AF1-017 E
Adder
3.2623529411764712.773
958162AF2-110 E
Adder
3.2376470588235292.752
919153AA1-139 E2
Adder
6.1235294117647065.205
934512AD1-075 E
Adder
6.2470588235294125.31
934502AD1-074 E
Adder
24.98705882352941321.239
924516AB2-100 E1
Adder
4.2411764705882353.605
940642AE2-051 E
50/50
18.57518.575
966621AG1-532 C
Adder
2.03647058823529431.731
3150651CHESTF6
Adder
25.5882352941176521.75
946262AF1-291 E
Adder
1.99529411764705891.696
934576AD1-082 E
Adder
6.4764705882352945.505
916191Z1-068 C
50/50
0.0660.066
933292AC2-141 E
50/50
19.5219.52
316294AC1-161 C
50/50
7.4737.473
944602AF1-125 E
50/50
153.669153.669
3145506HICKORY
50/50
3.2743.274
943612AF1-032 E
Adder
1.38000000000000011.173
957871AF2-081 C
Adder
14.97647058823529412.73
940492AE2-034 E
Adder
4.5188235294117653.841
934522AD1-076 E
Adder
9.0858823529411777.723
918492AA1-063AE OP
Adder
5.8905882352941185.007
937482AD2-202 E
Adder
1.5152941176470591.288
316303AF2-085
50/50
6.5326.532
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.98737.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.12228.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8684.868
LAGNLTFEXP_LAGN->PJM
CLTF
9.7559.755
NYPJM->LTFIMP_NY
CLTF
2.5532.553
LGEELTFEXP_LGEE->PJM
CLTF
1.5241.524
WECLTFEXP_WEC->PJM
CLTF
0.7920.792
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5125.512
SIGELTFEXP_SIGE->PJM
CLTF
0.30.3
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.2837.283
CBM South 2LTFEXP_CBM-S2->PJM
CBM
125.379125.379
CPLELTFEXP_CPLE->PJM
CLTF
15.2815.28
TVALTFEXP_TVA->PJM
CLTF
7.6637.663
O66PJM->LTFIMP_O-066
CMTX_NF
35.08335.083

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.85 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3279.97
MW Contribution:8.59
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316169AC1-164 GEN
Adder
44.9588235294117738.215
316349AD2-085 C
80/20
4.9434.943
316258AE1-075 C
80/20
0.5030.503
316023AB2-100 C2
80/20
1.3721.372
946281AF1-292 C
Adder
2.19294117647058861.864
926071AC1-086 C
Adder
29.4425.024
927021AC1-189 C
Adder
11.4094117647058839.698
3151541CLOVER2
80/20
17.7117.71
964241AG1-285 C
Adder
17.89058823529411815.207
962561AG1-105 C
Adder
11.8176470588235310.045
3150601CHESTF5
Adder
76.7117647058823665.205
941591AE2-156 C
80/20
26.02126.021
316316AC1-027 C
80/20
0.460.46
944601AF1-125 C
80/20
65.265.2
944591AF1-124 C
80/20
66.45566.455
938771AE1-103 C
80/20
4.24.2
960081AF2-299 C
Adder
2.64941176470588242.252
944011AF1-069 C
80/20
20.29620.296
963041AG1-153 C
80/20
8.5888.588
936261AD2-033 C
Adder
17.57529411764705814.939
961791AG1-021 C
Adder
2.35764705882352972.004
3151101ELIZAR3
80/20
4.7154.715
3151081ELIZAR1
80/20
4.6564.656
3151091ELIZAR2
80/20
4.5754.575
316315AB2-025 C
80/20
0.5980.598
961951AG1-038 C
Adder
3.3341176470588242.834
3151051BRUNSWICKS1
80/20
26.33526.335
3151531CLOVER1
80/20
17.87717.877
3138533PONTONDP
Adder
0.87294117647058820.742
3150831SPRUNCA
80/20
12.34712.347
3150841SPRUNCB
80/20
12.34712.347
961941AG1-037 C
Adder
0.71058823529411760.604
941031AE2-094 C
80/20
62.11762.117
934321AD1-056 C
Adder
8.5376470588235297.257
934331AD1-057 C
Adder
4.7623529411764714.048
958211AF2-115 C
Adder
2.94705882352941152.505
939191AE1-149 C
80/20
15.16215.162
957601AF2-054 C
Adder
2.37764705882352922.021
316365AB2-100 C1
80/20
1.3721.372
3151021BRUNSWICKG1
80/20
12.67612.676
3151041BRUNSWICKG3
80/20
12.67612.676
3150861SPRUNCD
80/20
0.2220.222
940431AE2-027 C
Adder
17.26588235294117614.676
3150981CHESPKA
80/20
0.6340.634
316185AD1-033 C
80/20
1.7941.794
944581AF1-123 C
80/20
66.2266.22
941101AE2-104 C
80/20
4.8434.843
316320Y1-086 C
80/20
0.3190.319
316405AF2-144 C
80/20
0.4280.428
957481AF2-042 C
80/20
77.49977.499
961611AG1-000B C
Adder
21.72352941176470518.465
316233AE1-074 C
80/20
3.7763.776
940551AE2-041 C
Adder
7.9588235294117656.765
3151211GRAVEL5
80/20
3.4433.443
3152331SURRY 2
80/20
34.47934.479
943461AF1-017 C
80/20
1.9381.938
316311AC2-079 C
80/20
8.2428.242
3156056W1-029WIND
80/20
1.1231.123
3152441Z1-086 ST
80/20
28.31528.315
944641AF1-129 C
Adder
134.59058823529412114.402
316240AF1-291 C
Adder
2.86941176470588262.439
3151161SURRY 1
80/20
33.88933.889
316381AD1-082 C
80/20
1.7951.795
316036AC1-147 C
80/20
0.5360.536
316018AA1-139 ULT2
80/20
1.5751.575
934511AD1-075 C
Adder
11.94117647058823610.15
934521AD1-076 C
Adder
17.34705882352941214.745
316263AC1-034 C
Adder
8.8741176470588247.543
959311AF2-222 C
Adder
23.07176470588235519.611
942001AE2-212 C
80/20
2.9732.973
3150991CHESPKB
80/20
1.051.05
316321Z2-027 C
80/20
0.5270.527
943741AF1-042 C
Adder
3.01647058823529422.564
934501AD1-074 C
Adder
47.763529411764740.599
962861AG1-135 C
Adder
6.1588235294117655.235
961671AG1-007 C
Adder
1.26588235294117671.076
934621AD1-088 C
80/20
13.42613.426
946301AF1-294 C
Adder
4.8470588235294124.12
942461AE2-259 C
Adder
12.70588235294117810.8
942341AE2-247 C
80/20
2.1432.143
316246AF1-032 C
80/20
0.4130.413
316388AE2-253 GEN
80/20
2.8622.862
966621AG1-532 C
Adder
1.9870588235294121.689
3150651CHESTF6
Adder
24.50588235294117520.83
916191Z1-068 C
80/20
0.0640.064
316294AC1-161 C
80/20
7.267.26
957871AF2-081 C
80/20
14.54714.547
936591AD2-074 C
Adder
5.7647058823529424.9
3151151S HAMPT1
80/20
2.1352.135
316313AB2-026 C
80/20
0.5480.548
316274AC1-208 C
Adder
12.4023529411764710.542
3151311EDGECMA
Adder
20.74352941176470817.632
3150851SPRUNCC
80/20
0.2220.222
3156116Z1-036WIND
80/20
0.9440.944
939411AE1-173 C
80/20
140.502140.502
3137643SOCKMAN
Adder
1.00.85
3151031BRUNSWICKG2
80/20
12.67612.676
937481AD2-202 C
80/20
0.5110.511
944631AF1-128 C
Adder
48.040.8
3150921YORKTN3
Adder
157.0388235294118133.483
933291AC2-141 C
80/20
44.42644.426
316305AF2-043 C
80/20
0.5050.505
964791AG1-342 C
Adder
4.6788235294117653.977
316236AE1-162 C
80/20
0.4930.493
316375AC2-012 C
80/20
1.9631.963
313526AB2-022 C
80/20
0.5460.546
940541AE2-040 C
80/20
4.2084.208
940481AE2-033 C
80/20
23.64823.648
943471AF1-018 C
Adder
7.9588235294117656.765
316083AB2-161 C
80/20
0.7870.787
316072AD1-144 C
80/20
0.4020.402
940641AE2-051 C
80/20
27.30727.307
316336AC2-165 C
Adder
13.69411764705882511.64
3152431Z1-086 GT3
80/20
16.26116.261
3152421Z1-086 GT2
80/20
16.26116.261
934611AD1-087 C
80/20
1.761.76
3150731STONECA
Adder
8.9505882352941187.608
935161AD1-151 C
Adder
21.46588235294117618.246
3151221GRAVEL6
80/20
3.4833.483
3151201GRAVEL4
80/20
3.4873.487
958161AF2-110 C
80/20
1.9761.976
316017AA1-139 ULT1
80/20
1.5751.575
938531AE1-072 C
80/20
25.56125.561
933981AD1-022 C
Adder
12.39411764705882410.535
3152411Z1-086 GT1
80/20
16.26616.266
316303AF2-085
80/20
6.3826.382
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.6437.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.68227.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8064.806
LAGNLTFEXP_LAGN->PJM
CLTF
9.5879.587
NYPJM->LTFIMP_NY
CLTF
2.4692.469
LGEELTFEXP_LGEE->PJM
CLTF
1.5071.507
WECLTFEXP_WEC->PJM
CLTF
0.7840.784
SIGELTFEXP_SIGE->PJM
CLTF
0.2960.296
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1347.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.889122.889
CPLELTFEXP_CPLE->PJM
CLTF
14.96614.966
TVALTFEXP_TVA->PJM
CLTF
7.5327.532

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.49 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3222.37
MW Contribution:17.14
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3432.65
MW Contribution:17.13
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150981CHESPKA
50/50
0.7090.709
316185AD1-033 C
50/50
2.0522.052
944581AF1-123 C
50/50
75.87875.878
941101AE2-104 C
50/50
4.9664.966
957832AF2-077 E
Adder
1.38000000000000011.173
3152331SURRY 2
50/50
52.22952.229
943461AF1-017 C
Adder
1.75294117647058821.49
932596AC2-079 E
Adder
12.36705882352941210.512
316311AC2-079 C
Adder
7.586.443
938532AE1-072 E
50/50
14.99614.996
3146326AYDLETT TAP
50/50
2.2162.216
917122Z2-027 E
50/50
2.1312.131
3156056W1-029WIND
50/50
1.211.21
920692AA2-178 E
50/50
5.9125.912
966622AG1-532 E
Adder
0.95882352941176460.815
922923AB1-081 E OP
Adder
4.0270588235294123.423
316320Y1-086 C
50/50
0.3530.353
316141AB2-099 E
Adder
0.320.272
316088AB2-174 E
Adder
6.877647058823535.846
923994AB2-040_E
Adder
6.5694117647058825.584
957481AF2-042 C
Adder
58.59176470588235549.803
961672AG1-007 E
Adder
0.59882352941176480.509
924322AB2-079 E O1
Adder
1.3164705882352941.119
943902AF1-058 E
Adder
1.21411764705882351.032
942341AE2-247 C
Adder
1.93764705882352951.647
943462AF1-017 E
Adder
2.86000000000000032.431
958162AF2-110 E
50/50
3.2233.223
316246AF1-032 C
50/50
0.4470.447
316388AE2-253 GEN
50/50
3.2483.248
919153AA1-139 E2
50/50
6.7236.723
934512AD1-075 E
Adder
5.95411764705882355.061
934502AD1-074 E
Adder
23.81647058823529420.244
924516AB2-100 E1
Adder
2.92235294117647062.484
918512AA1-065 E OP
Adder
7.1905882352941186.112
940642AE2-051 E
50/50
16.13516.135
966621AG1-532 C
Adder
1.43882352941176481.223
918532AA1-067 E
Adder
0.85764705882352940.729
924022AB2-043 E O1
Adder
5.1070588235294124.341
3147223TWITTYS
Adder
0.89647058823529410.762
959312AF2-222 E
Adder
10.3552941176470598.802
934576AD1-082 E
Adder
4.4847058823529413.812
916191Z1-068 C
50/50
0.0720.072
933292AC2-141 E
50/50
24.4824.48
316294AC1-161 C
50/50
9.3719.371
944602AF1-125 E
50/50
171.025171.025
3145506HICKORY
50/50
3.633.63
943612AF1-032 E
50/50
1.4511.451
957871AF2-081 C
50/50
16.44116.441
940492AE2-034 E
50/50
4.4344.434
934522AD1-076 E
Adder
8.667.361
943172AE2-346 E
Adder
0.76823529411764710.653
918492AA1-063AE OP
Adder
4.80941176470588254.088
917332KELFORD E
Adder
2.01647058823529421.714
925122AB2-169 E
Adder
7.4694117647058836.349
316274AC1-208 C
Adder
10.168.636
961611AG1-000B C
Adder
17.5717647058823514.936
316236AE1-162 C
50/50
0.4750.475
316375AC2-012 C
50/50
2.1982.198
313526AB2-022 C
50/50
0.6030.603
940541AE2-040 C
Adder
2.6435294117647062.247
940482AE2-033 E
Adder
10.1729411764705898.647
940481AE2-033 C
Adder
15.09058823529411912.827
926662AC1-147 E
50/50
2.1552.155
916192Z1-068 E
50/50
3.0983.098
957492AF2-043 E
50/50
2.2332.233
923852AB2-025 E
Adder
1.06941176470588250.909
939412AE1-173 E
50/50
88.25188.251
961941AG1-037 C
Adder
0.640.544
961942AG1-037 E
Adder
0.427058823529411770.363
941032AE2-094 E
50/50
22.37122.371
941031AE2-094 C
50/50
49.94849.948
934321AD1-056 C
Adder
6.7670588235294115.752
934332AD1-057 E
Adder
1.96588235294117661.671
934322AD1-056 E
Adder
3.6705882352941183.12
934331AD1-057 C
Adder
3.7752941176470593.209
927022AC1-189 E
Adder
4.86235294117647054.133
925595AC1-034 E
Adder
5.4105882352941184.599
936262AD2-033 E
Adder
7.8811764705882356.699
927226AC1-216 E
Adder
6.8258823529411765.802
962962AG1-145 E
Adder
1.36235294117647051.158
936666AD2-085 E
Adder
7.2929411764705886.199
941591AE2-156 C
50/50
29.1829.18
316316AC1-027 C
50/50
0.520.52
944601AF1-125 C
50/50
74.70974.709
944591AF1-124 C
50/50
76.14876.148
938771AE1-103 C
50/50
4.0814.081
3145413WATKINS
Adder
0.93058823529411770.791
960081AF2-299 C
Adder
1.91882352941176481.631
926072AC1-086 E
Adder
10.3658823529411768.811
944011AF1-069 C
50/50
16.3216.32
963041AG1-153 C
Adder
6.8564705882352955.828
936261AD2-033 C
Adder
11.82117647058823610.048
962562AG1-105 E
Adder
5.74.845
316160AE1-175 E
Adder
1.12470588235294120.956
3150921YORKTN3
50/50
162.48162.48
3145256KINGFORK
50/50
1.5181.518
925522AC1-027 E
50/50
2.0032.003
926755AC1-161 E
50/50
24.4824.48
933291AC2-141 C
50/50
57.34757.347
941102AE2-104 E
50/50
7.8957.895
316305AF2-043 C
50/50
0.5470.547
957872AF2-081 E
50/50
7.0467.046
932632AC2-084 E
Adder
3.71882352941176463.161
926214AC1-099 E
Adder
1.38941176470588231.181
964242AG1-285 E
Adder
8.5011764705882367.226
924162AB2-060 E OP
Adder
4.1870588235294123.559
964792AG1-342 E
Adder
2.2623529411764711.923
932763AC2-100 E
Adder
2.3941176470588242.035
924814AB2-134 E
Adder
11.1823529411764729.505
942342AE2-247 E
Adder
2.6752941176470592.274
316036AC1-147 C
50/50
0.60.6
316018AA1-139 ULT2
50/50
1.781.78
919152AA1-139 E1
50/50
6.7236.723
920042AA2-088 E OP
Adder
13.60117647058823611.561
934511AD1-075 C
Adder
11.6964705882352959.942
934521AD1-076 C
Adder
16.99176470588235314.443
3145723EMPORIA
Adder
0.44705882352941180.38
923573AB1-173 E OP
Adder
3.50352941176470622.978
919692AA2-053 E OP
Adder
4.8294117647058834.105
925785AC1-054 E
Adder
3.63176470588235353.087
316263AC1-034 C
Adder
7.1729411764705896.097
959311AF2-222 C
Adder
15.45647058823529513.138
939192AE1-149 E
Adder
5.8941176470588235.01
939312AE1-162 E
50/50
1.9371.937
3150991CHESPKB
50/50
1.1761.176
934065AD1-033 E
50/50
8.3718.371
937226AE2-253 E
50/50
9.6579.657
316321Z2-027 C
50/50
0.5770.577
940491AE2-034 C
50/50
1.6591.659
934501AD1-074 C
Adder
46.7858823529411839.768
924517AB2-100 E2
Adder
2.92235294117647062.484
957482AF2-042 E
Adder
39.0611764705882433.202
961671AG1-007 C
Adder
1.05647058823529430.898
934621AD1-088 C
Adder
9.7717647058823538.306
935172AD1-152 E
Adder
5.5847058823529414.747
934012AD1-025 E
Adder
8.837647058823537.512
913392Y1-086 E
50/50
3.5213.521
3156116Z1-036WIND
50/50
0.9890.989
939411AE1-173 C
50/50
132.376132.376
3137643SOCKMAN
Adder
0.77882352941176480.662
919710AA2-057 E
Adder
4.43.74
939191AE1-149 C
Adder
8.8411764705882367.515
901082W1-029 E
50/50
49.64949.649
926206AC1-098 E
Adder
4.2070588235294123.576
964791AG1-342 C
Adder
3.39411764705882352.885
923263AB1-132 E OP
Adder
6.6282352941176485.634
925612AC1-036 E
Adder
0.80823529411764720.687
924312AB2-078 E O1
Adder
1.3164705882352941.119
926274AC1-105 E
Adder
2.5482352941176472.166
316084AB2-161 E
Adder
5.6282352941176474.784
316072AD1-144 C
50/50
0.4210.421
3145946PLYMOUTH TP
Adder
0.451764705882352960.384
933982AD1-022 E
Adder
6.5129411764705885.536
940641AE2-051 C
50/50
24.20324.203
927146AC1-208 E
Adder
4.5117647058823533.835
934622AD1-088 E
Adder
4.70470588235294153.999
934612AD1-087 E
Adder
3.80117647058823543.231
927255AC1-221 E
Adder
3.5270588235294122.998
935161AD1-151 C
Adder
9.2600000000000027.871
932046AC2-012 E
50/50
21.31821.318
958161AF2-110 C
50/50
2.0262.026
316017AA1-139 ULT1
50/50
1.781.78
938531AE1-072 C
50/50
28.76728.767
3145393UNCAMP
Adder
8.367.106
315614AA2-178 C
50/50
2.2542.254
933981AD1-022 C
Adder
11.96352941176470710.169
900672V4-068 E
Adder
0.452941176470588240.385
924302AB2-077 E O1
Adder
1.3164705882352941.119
3144216WINCHST
50/50
0.1770.177
316349AD2-085 C
Adder
4.4694117647058833.799
935112AD1-144 E
50/50
1.4091.409
944582AF1-123 E
50/50
173.752173.752
944592AF1-124 E
50/50
174.381174.381
923832AB2-022 E
50/50
1.9881.988
938772AE1-103 E
50/50
5.6365.636
916042Z1-036 E
50/50
42.96342.963
960082AF2-299 E
Adder
1.27882352941176471.087
946281AF1-292 C
Adder
1.58823529411764721.35
926071AC1-086 C
Adder
22.77647058823529519.36
963042AG1-153 E
Adder
10.2835294117647068.741
927021AC1-189 C
Adder
9.768.296
964241AG1-285 C
Adder
12.75176470588235310.839
924152AB2-059 E OP
Adder
5.70470588235294154.849
962561AG1-105 C
Adder
8.5494117647058847.267
3151101ELIZAR3
50/50
5.3035.303
3151081ELIZAR1
50/50
5.2375.237
3151091ELIZAR2
50/50
5.1465.146
946282AF1-292 E
Adder
1.05882352941176470.9
944012AF1-069 E
50/50
6.346.34
917512Z2-088 E OP1
Adder
5.58588235294117654.748
917342Z2-044 E
Adder
0.65529411764705890.557
937482AD2-202 E
Adder
1.1129411764705880.946
3151311EDGECMA
Adder
16.76352941176470814.249
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.74418.744
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.28317.283
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.712.71
LAGNLTFEXP_LAGN->PJM
CLTF
6.3446.344
NYPJM->LTFIMP_NY
CLTF
1.4491.449
LGEELTFEXP_LGEE->PJM
CLTF
0.760.76
WECLTFEXP_WEC->PJM
CLTF
0.3980.398
G-007PJM->LTFIMP_G-007
CMTX_NF
3.0313.031
SIGELTFEXP_SIGE->PJM
CLTF
0.160.16
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.515.51
CBM South 2LTFEXP_CBM-S2->PJM
CBM
91.70491.704
CPLELTFEXP_CPLE->PJM
CLTF
11.56611.566
TVALTFEXP_TVA->PJM
CLTF
4.9264.926
O66PJM->LTFIMP_O-066
CMTX_NF
19.32919.329

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.39 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3219.08
MW Contribution:16.91
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
3152331SURRY 2
50/50
52.46452.464
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
316316AC1-027 C
50/50
0.5240.524
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
926755AC1-161 E
50/50
24.52424.524
933291AC2-141 C
50/50
57.45157.451
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
932632AC2-084 E
Adder
3.8494117647058823.272
926214AC1-099 E
Adder
1.43882352941176481.223
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
316018AA1-139 ULT2
50/50
1.7931.793
919152AA1-139 E1
50/50
6.7746.774
920042AA2-088 E OP
Adder
14.01647058823529311.914
934511AD1-075 C
Adder
11.92941176470588310.14
934521AD1-076 C
Adder
17.32941176470588514.73
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
944601AF1-125 C
50/50
75.19275.192
944591AF1-124 C
50/50
76.6476.64
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
936261AD2-033 C
Adder
12.05176470588235410.244
962562AG1-105 E
Adder
5.75647058823529444.893
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961941AG1-037 C
Adder
0.65882352941176480.56
961942AG1-037 E
Adder
0.43882352941176470.373
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934321AD1-056 C
Adder
7.0682352941176476.008
934332AD1-057 E
Adder
2.05294117647058851.745
934322AD1-056 E
Adder
3.83411764705882343.259
934331AD1-057 C
Adder
3.94352941176470573.352
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
936262AD2-033 E
Adder
8.0352941176470596.83
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
939191AE1-149 C
Adder
9.8705882352941188.39
3143316POE
Adder
1.15647058823529410.983
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
943902AF1-058 E
Adder
1.21882352941176491.036
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940482AE2-033 E
Adder
11.5564705882352949.823
940481AE2-033 C
Adder
17.1423529411764714.571
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
927255AC1-221 E
Adder
2.40941176470588262.048
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
3151101ELIZAR3
50/50
5.3455.345
3151081ELIZAR1
50/50
5.2785.278
3151091ELIZAR2
50/50
5.1875.187
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
917512Z2-088 E OP1
Adder
5.7423529411764714.881
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.39 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3219.08
MW Contribution:16.91
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
3152331SURRY 2
50/50
52.46452.464
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
926755AC1-161 E
50/50
24.52424.524
933291AC2-141 C
50/50
57.45157.451
941102AE2-104 E
50/50
8.0328.032
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
316018AA1-139 ULT2
50/50
1.7931.793
919152AA1-139 E1
50/50
6.7746.774
920042AA2-088 E OP
Adder
14.01647058823529311.914
934511AD1-075 C
Adder
11.92941176470588310.14
934521AD1-076 C
Adder
17.32941176470588514.73
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
316316AC1-027 C
50/50
0.5240.524
944601AF1-125 C
50/50
75.19275.192
944591AF1-124 C
50/50
76.6476.64
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
936261AD2-033 C
Adder
12.05176470588235410.244
962562AG1-105 E
Adder
5.75647058823529444.893
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961941AG1-037 C
Adder
0.65882352941176480.56
961942AG1-037 E
Adder
0.43882352941176470.373
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934321AD1-056 C
Adder
7.0682352941176476.008
934332AD1-057 E
Adder
2.05294117647058851.745
934322AD1-056 E
Adder
3.83411764705882343.259
934331AD1-057 C
Adder
3.94352941176470573.352
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
936262AD2-033 E
Adder
8.0352941176470596.83
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
939191AE1-149 C
Adder
9.8705882352941188.39
3143316POE
Adder
1.15647058823529410.983
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
943902AF1-058 E
Adder
1.21882352941176491.036
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940482AE2-033 E
Adder
11.5564705882352949.823
940481AE2-033 C
Adder
17.1423529411764714.571
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
927255AC1-221 E
Adder
2.40941176470588262.048
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
3151101ELIZAR3
50/50
5.3455.345
3151081ELIZAR1
50/50
5.2785.278
3151091ELIZAR2
50/50
5.1875.187
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
917512Z2-088 E OP1
Adder
5.7423529411764714.881
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
932632AC2-084 E
Adder
3.8494117647058823.272
926214AC1-099 E
Adder
1.43882352941176481.223
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.38 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3218.92
MW Contribution:16.91
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.16 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3432.06
MW Contribution:16.98
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
3152331SURRY 2
50/50
52.46452.464
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
943902AF1-058 E
Adder
1.21882352941176491.036
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961941AG1-037 C
Adder
0.65882352941176480.56
961942AG1-037 E
Adder
0.43882352941176470.373
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934321AD1-056 C
Adder
7.0682352941176476.008
934332AD1-057 E
Adder
2.05294117647058851.745
934322AD1-056 E
Adder
3.83411764705882343.259
934331AD1-057 C
Adder
3.94352941176470573.352
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
936262AD2-033 E
Adder
8.0352941176470596.83
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
316316AC1-027 C
50/50
0.5240.524
944601AF1-125 C
50/50
75.19275.192
944591AF1-124 C
50/50
76.6476.64
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
936261AD2-033 C
Adder
12.05176470588235410.244
962562AG1-105 E
Adder
5.75647058823529444.893
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
926755AC1-161 E
50/50
24.52424.524
933291AC2-141 C
50/50
57.45157.451
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
932632AC2-084 E
Adder
3.8494117647058823.272
926214AC1-099 E
Adder
1.43882352941176481.223
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
316018AA1-139 ULT2
50/50
1.7931.793
919152AA1-139 E1
50/50
6.7746.774
920042AA2-088 E OP
Adder
14.01647058823529311.914
934511AD1-075 C
Adder
11.92941176470588310.14
934521AD1-076 C
Adder
17.32941176470588514.73
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
939191AE1-149 C
Adder
9.8705882352941188.39
3143316POE
Adder
1.15647058823529410.983
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940482AE2-033 E
Adder
11.5564705882352949.823
940481AE2-033 C
Adder
17.1423529411764714.571
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
927255AC1-221 E
Adder
2.40941176470588262.048
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
3151101ELIZAR3
50/50
5.3455.345
3151081ELIZAR1
50/50
5.2785.278
3151091ELIZAR2
50/50
5.1875.187
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
917512Z2-088 E OP1
Adder
5.7423529411764714.881
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A'
 OPEN BRANCH FROM BUS 314218 TO BUS 314196 CKT 1   /*6ELMONT      230.0 - 6LADYSMITH   230.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1   /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T567_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
314282 to 314285 ckt 1
314285 to 314316 ckt 1
314287 to 314276 ckt 1
314331 to 314263 ckt 1
314902 to 314282 ckt 2
314902 to 314914 ckt 1
314914 to 314918 ckt 1
314924 to 314903 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC100.29 %984.18B987.043.04
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC113.32 %3940.0C4464.9222.93
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.39 %3220.44B3329.549.14
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC104.31 %3637.0C3793.6519.16
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC111.58 %4070.2B4541.478.3
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC111.48 %5011.0C5586.0620.75
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC100.74 %4070.2B4100.487.02
GD1DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: 545T552_SRT-S
BreakerAC107.93 %3940.0C4252.5611.21
GD1DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC100.26 %3220.44B3228.894.27
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
SingleAC102.3 %1058.16B1082.523.61
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC119.4 %3220.44B3845.288.78
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC117.79 %3940.0C4640.8822.09
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC111.63 %3220.44B3595.095.14
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
SingleAC110.86 %3220.44B3570.055.39
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC110.14 %3940.0C4339.5313.4
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC116.71 %3220.44B3758.565.7
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC113.93 %3220.44B3669.135.89
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC111.88 %3940.0C4408.0814.79
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC106.7 %4070.2B4342.9817.25
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC102.59 %4070.2B4175.6217.25
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC120.93 %3220.44B3894.335.54
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC119.78 %3220.44B3857.575.76
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC117.54 %3940.0C4631.2414.45
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC104.04 %4070.2B4234.717.1

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.29 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:987.04
MW Contribution:3.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943171AE2-346 C
80/20
0.1050.105
961941AG1-037 C
80/20
0.2370.237
3151391GASTONA
80/20
2.0712.071
3151261ROARAP2
80/20
0.8190.819
3152421Z1-086 GT2
80/20
5.7485.748
3152441Z1-086 ST
80/20
10.00810.008
3152411Z1-086 GT1
80/20
5.755.75
944641AF1-129 C
Adder
-92.12117647058824-78.303
316240AF1-291 C
Adder
-1.6611764705882353-1.412
934521AD1-076 C
80/20
4.8074.807
934511AD1-075 C
80/20
3.3093.309
3156073AA1-063SOLA
80/20
0.7530.753
316087AB2-174 C
80/20
0.8150.815
316212AC1-099 C
80/20
0.1680.168
316263AC1-034 C
80/20
3.5493.549
937481AD2-202 C
80/20
0.1730.173
3151591KERR 2
80/20
0.5540.554
959311AF2-222 C
80/20
6.6486.648
942001AE2-212 C
Adder
-3.9329411764705884-3.343
940491AE2-034 C
80/20
0.4170.417
934501AD1-074 C
80/20
13.23613.236
3151031BRUNSWICKG2
80/20
4.4784.478
961671AG1-007 C
80/20
0.4820.482
316359AB2-059 C OP
80/20
0.8920.892
934621AD1-088 C
80/20
4.424.42
946301AF1-294 C
Adder
1.3164705882352941.119
316283AC2-100 C
80/20
0.510.51
3152921DOMTR78
80/20
0.5570.557
316140AB2-099 C
80/20
0.0450.045
938771AE1-103 C
Adder
0.96705882352941170.822
960081AF2-299 C
80/20
1.3861.386
3156083AA2-088SOLA
80/20
0.4670.467
316365AB2-100 C1
80/20
0.7990.799
3151021BRUNSWICKG1
80/20
4.4784.478
957481AF2-042 C
80/20
26.38726.387
316003AC1-222 C
80/20
0.4260.426
932631AC2-084 C
80/20
0.5330.533
316274AC1-208 C
80/20
4.9624.962
3151311EDGECMA
80/20
8.3398.339
3152661PLYWOOD A
80/20
0.5410.541
946281AF1-292 C
80/20
1.1471.147
926071AC1-086 C
80/20
14.30114.301
927021AC1-189 C
80/20
4.1534.153
964241AG1-285 C
80/20
5.5515.551
316034AC1-036 C
80/20
0.0950.095
962561AG1-105 C
80/20
4.0224.022
316118AC1-105 C
80/20
0.4080.408
940641AE2-051 C
80/20
9.0359.035
3152431Z1-086 GT3
80/20
5.7485.748
3156011CONETOE2SOL
80/20
0.6290.629
934611AD1-087 C
80/20
0.5960.596
3151611KERR 4
80/20
0.5540.554
3151621KERR 5
80/20
0.5540.554
316237AB2-079 C O1
80/20
0.1510.151
316222AC1-221 C
80/20
0.6320.632
933981AD1-022 C
80/20
3.5783.578
316174AB2-169_C
80/20
0.4490.449
3156063AA2-053SOLA
80/20
0.860.86
3151281ROARAP4
80/20
0.7750.775
316049AB1-081 C OP
80/20
0.7570.757
316238AB2-078 C O1
80/20
0.1510.151
316318V4-068 C
80/20
0.0370.037
966621AG1-532 C
80/20
1.041.04
313506AB1-173 C OP
80/20
0.7570.757
316210AC1-098 C
80/20
0.50.5
316005AA1-067 C
80/20
0.1280.128
3151601KERR 3
80/20
0.5540.554
3151581KERR 1
80/20
0.1980.198
935171AD1-152 C
80/20
0.620.62
315614AA2-178 C
80/20
0.5670.567
940541AE2-040 C
80/20
2.9992.999
940481AE2-033 C
80/20
16.46516.465
3151411GASTONB
80/20
2.0712.071
316181AB2-040 GEN
80/20
0.8530.853
3147043LAWRENC
80/20
0.2030.203
316319Z2-044 C
80/20
0.1130.113
3151641KERR 7
80/20
0.5540.554
313527AB2-043 C
80/20
0.2380.238
941031AE2-094 C
80/20
22.06822.068
934331AD1-057 C
80/20
2.0892.089
934321AD1-056 C
80/20
3.7443.744
3151531CLOVER1
80/20
6.056.05
3151541CLOVER2
80/20
5.9935.993
958211AF2-115 C
Adder
0.80.68
3151381ROSEMG2
80/20
0.6340.634
944011AF1-069 C
80/20
7.217.21
963041AG1-153 C
80/20
3.0443.044
3151051BRUNSWICKS1
80/20
9.3029.302
936261AD2-033 C
80/20
5.4245.424
961791AG1-021 C
Adder
0.640.544
316248AF1-058 C
80/20
0.140.14
316315AB2-025 C
80/20
0.4250.425
316023AB2-100 C2
80/20
0.7990.799
316317KELFORD C
80/20
0.1760.176
316129AC1-054 C
80/20
0.6480.648
3151631KERR 6
80/20
0.5540.554
316131AB2-060 C
80/20
0.680.68
3138533PONTONDP
Adder
0.237647058823529430.202
3151151S HAMPT1
80/20
0.570.57
3151361ROSEMG1
80/20
1.3551.355
3151041BRUNSWICKG3
80/20
4.4784.478
316327AA2-057 C
80/20
0.7010.701
316239AB2-077 C O1
80/20
0.1510.151
964791AG1-342 C
80/20
1.5971.597
939411AE1-173 C
80/20
41.75841.758
3156021HOLLOMANSOL
80/20
0.830.83
316011AB1-132 C OP
80/20
1.5811.581
3151371ROSEMS1
80/20
0.8390.839
3137643SOCKMAN
80/20
0.4490.449
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.95317.953
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.57311.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1342.134
LAGNLTFEXP_LAGN->PJM
CLTF
3.8673.867
NYPJM->LTFIMP_NY
CLTF
0.5840.584
LGEELTFEXP_LGEE->PJM
CLTF
0.6950.695
WECLTFEXP_WEC->PJM
CLTF
0.3670.367
SIGELTFEXP_SIGE->PJM
CLTF
0.1330.133
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.6422.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.16446.164
CPLELTFEXP_CPLE->PJM
CLTF
5.5395.539
TVALTFEXP_TVA->PJM
CLTF
3.0473.047

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.32 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4464.92
MW Contribution:22.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943461AF1-017 C
Adder
1.71411764705882371.457
932596AC2-079 E
Adder
11.94588235294117610.154
316311AC2-079 C
Adder
7.3223529411764716.224
938532AE1-072 E
50/50
12.39212.392
3146326AYDLETT TAP
50/50
1.8341.834
917122Z2-027 E
Adder
1.81294117647058831.541
920692AA2-178 E
Adder
5.5388235294117654.708
966622AG1-532 E
Adder
1.24941176470588241.062
3152421Z1-086 GT2
50/50
17.33717.337
3152441Z1-086 ST
50/50
30.18730.187
3152411Z1-086 GT1
50/50
17.34217.342
922923AB1-081 E OP
Adder
4.9682352941176474.223
927264AC1-222 E
Adder
5.0905882352941184.327
916191Z1-068 C
50/50
0.0590.059
941101AE2-104 C
Adder
4.4388235294117653.773
316185AD1-033 C
50/50
1.6591.659
944581AF1-123 C
50/50
62.37662.376
316294AC1-161 C
50/50
6.8696.869
316141AB2-099 E
Adder
0.33882352941176470.288
316088AB2-174 E
Adder
8.7141176470588247.407
923994AB2-040_E
Adder
8.2247058823529416.991
3151021BRUNSWICKG1
50/50
13.49413.494
961672AG1-007 E
Adder
0.71058823529411760.604
957481AF2-042 C
50/50
79.02379.023
924322AB2-079 E O1
Adder
1.6447058823529411.398
943902AF1-058 E
Adder
1.65529411764705881.407
934576AD1-082 E
Adder
5.2247058823529414.441
943612AF1-032 E
Adder
1.24117647058823531.055
3145506HICKORY
50/50
2.9532.953
944602AF1-125 E
50/50
140.592140.592
957871AF2-081 C
50/50
13.52313.523
933292AC2-141 E
50/50
18.00718.007
940492AE2-034 E
Adder
4.1541176470588243.531
934522AD1-076 E
Adder
8.397647058823537.138
943172AE2-346 E
Adder
0.81176470588235290.69
918492AA1-063AE OP
Adder
5.4552941176470594.637
925122AB2-169 E
Adder
7.7223529411764716.564
917332KELFORD E
Adder
2.2035294117647061.873
316274AC1-208 C
Adder
12.05058823529411810.243
917342Z2-044 E
Adder
0.79764705882352950.678
3151311EDGECMA
Adder
20.6976470588235317.593
937482AD2-202 E
50/50
1.5031.503
935112AD1-144 E
Adder
1.21411764705882351.032
316349AD2-085 C
Adder
4.3705882352941173.715
3151091ELIZAR2
50/50
4.2124.212
944582AF1-123 E
50/50
142.834142.834
944592AF1-124 E
50/50
143.351143.351
923832AB2-022 E
Adder
1.67529411764705881.424
938772AE1-103 E
Adder
5.3788235294117654.572
916042Z1-036 E
Adder
38.52941176470588432.75
960082AF2-299 E
Adder
1.66588235294117641.416
946281AF1-292 C
Adder
2.0682352941176471.758
926071AC1-086 C
Adder
28.2376470588235324.002
963042AG1-153 E
50/50
13.7613.76
927021AC1-189 C
Adder
11.2564705882352949.568
924152AB2-059 E OP
Adder
7.0388235294117655.983
964241AG1-285 C
Adder
14.8776470588235312.646
962561AG1-105 C
Adder
11.1211764705882359.453
316084AB2-161 E
Adder
6.5576470588235295.574
316017AA1-139 ULT1
50/50
1.4591.459
3145946PLYMOUTH TP
Adder
0.435294117647058830.37
933982AD1-022 E
Adder
6.417647058823535.455
940641AE2-051 C
50/50
28.87528.875
3152431Z1-086 GT3
50/50
17.33717.337
927146AC1-208 E
Adder
5.3517647058823544.549
934622AD1-088 E
50/50
6.3856.385
934611AD1-087 C
50/50
1.7741.774
934612AD1-087 E
50/50
5.1365.136
927255AC1-221 E
Adder
4.84941176470588254.122
932046AC2-012 E
50/50
17.5517.55
958161AF2-110 C
Adder
1.8117647058823531.54
938531AE1-072 C
50/50
23.77123.771
3145393UNCAMP
Adder
8.0941176470588236.88
933981AD1-022 C
Adder
11.78823529411764610.02
900672V4-068 E
Adder
0.47764705882352950.406
924302AB2-077 E O1
Adder
1.6447058823529411.398
943462AF1-017 E
Adder
2.7964705882352942.377
942341AE2-247 C
Adder
1.89411764705882371.61
958162AF2-110 E
Adder
2.8811764705882352.449
316388AE2-253 GEN
50/50
2.652.65
919153AA1-139 E2
50/50
5.535.53
934502AD1-074 E
Adder
23.0929411764705919.629
934512AD1-075 E
Adder
5.7729411764705894.907
918512AA1-065 E OP
Adder
7.42823529411764756.314
924516AB2-100 E1
Adder
3.9282352941176473.339
940642AE2-051 E
50/50
19.2519.25
966621AG1-532 C
Adder
1.87411764705882341.593
918532AA1-067 E
Adder
0.95764705882352940.814
924022AB2-043 E O1
Adder
6.3552941176470595.402
316375AC2-012 C
50/50
1.8031.803
940541AE2-040 C
50/50
3.9673.967
940481AE2-033 C
50/50
22.31122.311
940482AE2-033 E
50/50
15.04115.041
923263AB1-132 E OP
Adder
8.217647058823536.985
924312AB2-078 E O1
Adder
1.6447058823529411.398
926274AC1-105 E
Adder
3.4082352941176472.897
3150921YORKTN3
Adder
124.22470588235294105.591
3145256KINGFORK
Adder
1.30823529411764721.112
925522AC1-027 E
50/50
1.641.64
941102AE2-104 E
Adder
7.0576470588235295.999
957872AF2-081 E
50/50
5.7955.795
316018AA1-139 ULT2
50/50
1.4591.459
933291AC2-141 C
50/50
42.18342.183
926755AC1-161 E
50/50
18.00718.007
932632AC2-084 E
Adder
4.3164705882352943.669
926214AC1-099 E
Adder
1.61294117647058831.371
924162AB2-060 E OP
Adder
5.2141176470588244.432
964242AG1-285 E
Adder
9.9188235294117648.431
964792AG1-342 E
Adder
2.9682352941176472.523
932763AC2-100 E
Adder
3.2952941176470592.801
942342AE2-247 E
Adder
2.61647058823529432.224
919152AA1-139 E1
50/50
5.535.53
934521AD1-076 C
Adder
16.4752941176470614.004
934511AD1-075 C
Adder
11.3411764705882369.64
920042AA2-088 E OP
Adder
14.1647058823529412.04
3145723EMPORIA
Adder
0.57647058823529410.49
923573AB1-173 E OP
Adder
4.3858823529411773.728
919692AA2-053 E OP
Adder
5.65176470588235354.804
925785AC1-054 E
Adder
4.5188235294117653.841
316263AC1-034 C
Adder
8.8505882352941177.523
937481AD2-202 C
50/50
0.5150.515
926662AC1-147 E
Adder
1.77411764705882361.508
3151081ELIZAR1
50/50
4.2884.288
916192Z1-068 E
50/50
2.5342.534
957492AF2-043 E
Adder
1.9105882352941181.624
923852AB2-025 E
50/50
1.6041.604
939412AE1-173 E
50/50
96.49596.495
961942AG1-037 E
Adder
0.451764705882352960.384
961941AG1-037 C
Adder
0.6764705882352940.575
941031AE2-094 C
50/50
66.68466.684
941032AE2-094 E
50/50
29.86629.866
934331AD1-057 C
Adder
4.6741176470588233.973
934322AD1-056 E
Adder
4.5447058823529413.863
934332AD1-057 E
Adder
2.43411764705882352.069
934321AD1-056 C
Adder
8.3788235294117657.122
927022AC1-189 E
Adder
5.6070588235294124.766
925595AC1-034 E
Adder
6.6764705882352945.675
3151531CLOVER1
50/50
18.02218.022
3151541CLOVER2
50/50
17.85317.853
936666AD2-085 E
Adder
7.1317647058823546.062
941591AE2-156 C
50/50
24.00724.007
3151101ELIZAR3
50/50
4.3424.342
944591AF1-124 C
50/50
62.59862.598
944601AF1-125 C
50/50
61.41561.415
938771AE1-103 C
Adder
3.8941176470588243.31
3145413WATKINS
Adder
0.92117647058823540.783
960081AF2-299 C
Adder
2.4988235294117652.124
926072AC1-086 E
Adder
12.85176470588235310.924
944011AF1-069 C
50/50
21.78821.788
963041AG1-153 C
50/50
9.1739.173
3151051BRUNSWICKS1
50/50
28.03428.034
962562AG1-105 E
Adder
7.41411764705882356.302
316316AC1-027 C
50/50
0.4240.424
316315AB2-025 C
50/50
0.5620.562
946282AF1-292 E
Adder
1.37882352941176461.172
944012AF1-069 E
50/50
8.4648.464
917512Z2-088 E OP1
Adder
6.54705882352941255.565
939191AE1-149 C
Adder
12.10588235294117610.29
3143316POE
Adder
1.6082352941176471.367
901082W1-029 E
Adder
42.9564705882352936.513
926206AC1-098 E
Adder
4.8835294117647064.151
3151041BRUNSWICKG3
50/50
13.49413.494
964791AG1-342 C
Adder
4.4517647058823523.784
939192AE1-149 E
Adder
8.0705882352941176.86
939312AE1-162 E
Adder
1.72117647058823551.463
934065AD1-033 E
50/50
6.7926.792
937226AE2-253 E
50/50
7.9097.909
934501AD1-074 C
Adder
45.3647058823529438.56
924517AB2-100 E2
Adder
3.9282352941176473.339
3151031BRUNSWICKG2
50/50
13.49413.494
961671AG1-007 C
Adder
1.25411764705882361.066
957482AF2-042 E
50/50
52.68252.682
934621AD1-088 C
50/50
13.2613.26
935172AD1-152 E
Adder
7.5717647058823536.436
913392Y1-086 E
Adder
2.9682352941176472.523
939411AE1-173 C
50/50
144.742144.742
3137643SOCKMAN
Adder
0.95176470588235310.809
919710AA2-057 E
Adder
5.2964705882352944.502
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.25255.252
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.53435.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.5866.586
LAGNLTFEXP_LAGN->PJM
CLTF
11.79711.797
NYPJM->LTFIMP_NY
CLTF
2.5842.584
LGEELTFEXP_LGEE->PJM
CLTF
2.1892.189
WECLTFEXP_WEC->PJM
CLTF
1.1371.137
G-007PJM->LTFIMP_G-007
CMTX_NF
5.665.66
SIGELTFEXP_SIGE->PJM
CLTF
0.4160.416
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6257.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
136.078136.078
CPLELTFEXP_CPLE->PJM
CLTF
15.98515.985
TVALTFEXP_TVA->PJM
CLTF
9.3529.352
O66PJM->LTFIMP_O-066
CMTX_NF
36.00236.002

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.39 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3329.54
MW Contribution:9.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151081ELIZAR1
80/20
4.2584.258
943171AE2-346 C
80/20
0.2980.298
961941AG1-037 C
80/20
0.6730.673
3151391GASTONA
80/20
4.0664.066
941031AE2-094 C
80/20
66.45566.455
934331AD1-057 C
Adder
4.6482352941176473.951
934321AD1-056 C
Adder
8.332941176470597.083
3151531CLOVER1
80/20
17.9517.95
3151541CLOVER2
80/20
17.78117.781
958211AF2-115 C
Adder
2.28235294117647051.94
943461AF1-017 C
80/20
1.7011.701
316311AC2-079 C
80/20
7.2667.266
3156056W1-029WIND
80/20
1.0361.036
3151261ROARAP2
80/20
1.8341.834
3152421Z1-086 GT2
80/20
17.27717.277
3152441Z1-086 ST
80/20
30.08230.082
3152411Z1-086 GT1
80/20
17.28217.282
316036AC1-147 C
80/20
0.4890.489
316305AF2-043 C
80/20
0.4630.463
316321Z2-027 C
80/20
0.4860.486
934521AD1-076 C
80/20
16.37216.372
934511AD1-075 C
80/20
11.2711.27
3156073AA1-063SOLA
80/20
1.8611.861
316087AB2-174 C
80/20
1.561.56
316212AC1-099 C
80/20
0.4180.418
316263AC1-034 C
Adder
8.8035294117647057.483
937481AD2-202 C
80/20
0.5130.513
959311AF2-222 C
Adder
18.28823529411764815.545
942001AE2-212 C
Adder
2.11411764705882371.797
3156116Z1-036WIND
80/20
0.8770.877
940491AE2-034 C
80/20
1.5381.538
934501AD1-074 C
80/20
45.0845.08
3151031BRUNSWICKG2
80/20
13.44613.446
961671AG1-007 C
Adder
1.2482352941176471.061
934621AD1-088 C
80/20
13.20613.206
946301AF1-294 C
Adder
3.75411764705882333.191
3150921YORKTN3
Adder
127.84235294117647108.666
316018AA1-139 ULT2
80/20
1.4491.449
933291AC2-141 C
80/20
41.90441.904
3152921DOMTR78
80/20
1.8181.818
316140AB2-099 C
80/20
0.1280.128
941591AE2-156 C
80/20
23.83823.838
3151101ELIZAR3
80/20
4.3114.311
944591AF1-124 C
80/20
62.17762.177
944601AF1-125 C
80/20
61.00261.002
938771AE1-103 C
80/20
3.8693.869
960081AF2-299 C
80/20
2.4842.484
3151381ROSEMG2
80/20
1.271.27
944011AF1-069 C
80/20
21.71321.713
963041AG1-153 C
80/20
9.1419.141
3151051BRUNSWICKS1
80/20
27.93527.935
936261AD2-033 C
Adder
14.72470588235294112.516
961791AG1-021 C
Adder
1.82588235294117651.552
936171AD2-023 C
Adder
5.5152941176470584.688
940431AE2-027 C
Adder
11.395294117647069.686
916191Z1-068 C
80/20
0.0580.058
941101AE2-104 C
80/20
4.4074.407
316185AD1-033 C
80/20
1.6481.648
944581AF1-123 C
80/20
61.95761.957
316294AC1-161 C
80/20
6.8246.824
3156083AA2-088SOLA
80/20
1.4051.405
316365AB2-100 C1
80/20
1.2911.291
3151021BRUNSWICKG1
80/20
13.44613.446
957481AF2-042 C
80/20
78.71578.715
957871AF2-081 C
80/20
13.4313.43
932631AC2-084 C
80/20
1.3311.331
316274AC1-208 C
80/20
11.98411.984
3151311EDGECMA
Adder
20.58941176470588317.501
942341AE2-247 C
80/20
1.881.88
316246AF1-032 C
80/20
0.3780.378
316388AE2-253 GEN
80/20
2.6322.632
316320Y1-086 C
80/20
0.2940.294
316318V4-068 C
80/20
0.1070.107
966621AG1-532 C
80/20
1.8631.863
313506AB1-173 C OP
80/20
1.4941.494
316210AC1-098 C
80/20
1.251.25
935171AD1-152 C
80/20
1.8271.827
3152331SURRY 2
80/20
30.82730.827
316017AA1-139 ULT1
80/20
1.4491.449
313526AB2-022 C
80/20
0.5040.504
940641AE2-051 C
80/20
28.76428.764
3152431Z1-086 GT3
80/20
17.27717.277
934611AD1-087 C
80/20
1.7671.767
316349AD2-085 C
80/20
4.3374.337
3151091ELIZAR2
80/20
4.1834.183
946281AF1-292 C
80/20
2.0562.056
926071AC1-086 C
80/20
28.07728.077
927021AC1-189 C
Adder
11.1952941176470599.516
964241AG1-285 C
Adder
14.80352941176470712.583
962561AG1-105 C
Adder
11.0694117647058839.409
935161AD1-151 C
Adder
15.27058823529411812.98
958161AF2-110 C
80/20
1.7981.798
938531AE1-072 C
80/20
23.60823.608
933981AD1-022 C
80/20
11.71411.714
316174AB2-169_C
80/20
1.3931.393
3156063AA2-053SOLA
80/20
1.9981.998
3151281ROARAP4
80/20
1.7351.735
936161AD2-022 C
Adder
9.455294117647068.037
961611AG1-000B C
Adder
17.0670588235294114.507
316072AD1-144 C
80/20
0.3590.359
316375AC2-012 C
80/20
1.7911.791
315614AA2-178 C
80/20
2.0912.091
940541AE2-040 C
80/20
3.9443.944
940481AE2-033 C
80/20
22.18122.181
3151411GASTONB
80/20
4.0664.066
316181AB2-040 GEN
80/20
1.6831.683
3147043LAWRENC
80/20
0.3980.398
316316AC1-027 C
80/20
0.4210.421
316315AB2-025 C
80/20
0.5580.558
316023AB2-100 C2
80/20
1.2911.291
316317KELFORD C
80/20
0.4760.476
316129AC1-054 C
80/20
1.5891.589
3138533PONTONDP
Adder
0.6764705882352940.575
939191AE1-149 C
Adder
11.99058823529411710.192
3150981CHESPKA
80/20
0.5780.578
3151151S HAMPT1
80/20
1.9741.974
3151361ROSEMG1
80/20
2.7122.712
3151041BRUNSWICKG3
80/20
13.44613.446
964791AG1-342 C
Adder
4.4317647058823533.767
3150991CHESPKB
80/20
0.9580.958
939411AE1-173 C
80/20
144.1144.1
3156021HOLLOMANSOL
80/20
2.4482.448
316011AB1-132 C OP
80/20
3.1053.105
3151371ROSEMS1
80/20
1.681.68
3137643SOCKMAN
80/20
0.9470.947
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.0655.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.38335.383
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.566.56
LAGNLTFEXP_LAGN->PJM
CLTF
11.74411.744
NYPJM->LTFIMP_NY
CLTF
2.5592.559
LGEELTFEXP_LGEE->PJM
CLTF
2.182.18
WECLTFEXP_WEC->PJM
CLTF
1.1331.133
SIGELTFEXP_SIGE->PJM
CLTF
0.4150.415
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.597.59
CBM South 2LTFEXP_CBM-S2->PJM
CBM
135.46135.46
CPLELTFEXP_CPLE->PJM
CLTF
15.91315.913
TVALTFEXP_TVA->PJM
CLTF
9.319.31

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.31 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:3793.65
MW Contribution:19.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935161AD1-151 C
Adder
22.94117647058823619.5
932046AC2-012 E
50/50
23.72823.728
958161AF2-110 C
50/50
2.3482.348
938531AE1-072 C
50/50
31.50731.507
3145393UNCAMP
Adder
9.815294117647068.343
933981AD1-022 C
Adder
13.8411.764
963611AG1-210 C
Adder
0.93294117647058830.793
3138116ELKO L286
Adder
1.84941176470588251.572
961611AG1-000B C
Adder
25.22588235294117721.442
316072AD1-144 C
50/50
0.4940.494
316375AC2-012 C
50/50
2.4382.438
940541AE2-040 C
Adder
3.79058823529411763.222
940481AE2-033 C
Adder
21.4117647058823518.2
940482AE2-033 E
Adder
14.43529411764705912.27
923263AB1-132 E OP
Adder
8.3529411764705897.1
957831AF2-077 C
50/50
0.570.57
316169AC1-164 GEN
50/50
65.01265.012
935112AD1-144 E
50/50
1.661.66
316349AD2-085 C
Adder
5.5541176470588244.721
3151091ELIZAR2
50/50
5.6915.691
944582AF1-123 E
50/50
191.735191.735
944592AF1-124 E
50/50
192.429192.429
923832AB2-022 E
50/50
2.1962.196
938772AE1-103 E
Adder
6.6011764705882355.611
916042Z1-036 E
50/50
48.46248.462
960082AF2-299 E
Adder
1.01882352941176470.866
946281AF1-292 C
Adder
2.03764705882352941.732
926071AC1-086 C
Adder
28.7023529411764724.397
963042AG1-153 E
Adder
11.4941176470588249.77
923842AB2-024 E
Adder
2.84000000000000032.414
316076AC2-137 E
Adder
1.77294117647058821.507
926662AC1-147 E
50/50
2.3992.399
3151081ELIZAR1
50/50
5.7935.793
916192Z1-068 E
50/50
3.4083.408
957492AF2-043 E
50/50
2.5222.522
923852AB2-025 E
Adder
1.53294117647058831.303
939412AE1-173 E
50/50
96.4696.46
961942AG1-037 E
Adder
0.50470588235294120.429
961941AG1-037 C
Adder
0.75764705882352950.644
941031AE2-094 C
Adder
55.5058823529411847.18
962962AG1-145 E
50/50
2.6032.603
3150601CHESTF5
Adder
80.1388235294117768.118
925332AB2-190 E
Adder
11.1811764705882369.504
927226AC1-216 E
Adder
11.3047058823529419.609
936666AD2-085 E
Adder
9.0611764705882357.702
941591AE2-156 C
50/50
32.45632.456
3151101ELIZAR3
50/50
5.8665.866
944591AF1-124 C
50/50
84.02984.029
944601AF1-125 C
50/50
82.44182.441
938771AE1-103 C
Adder
4.7799999999999994.063
3145413WATKINS
Adder
1.09647058823529430.932
960081AF2-299 C
Adder
2.46117647058823552.092
926072AC1-086 E
Adder
13.06352941176470511.104
944011AF1-069 C
Adder
18.13647058823529415.416
963041AG1-153 C
Adder
7.662352941176476.513
964212AG1-282 E
Adder
1.91529411764705881.628
961952AG1-038 E
Adder
6.66352941176470555.664
961951AG1-038 C
Adder
4.8258823529411774.102
925865AC1-065 E
Adder
25.8294117647058821.955
3144216WINCHST
50/50
0.2410.241
316316AC1-027 C
50/50
0.5710.571
944012AF1-069 E
Adder
7.04588235294117655.989
941032AE2-094 E
Adder
24.8621.131
316157AD2-030 E
Adder
1.88588235294117661.603
964211AG1-282 C
Adder
2.87176470588235282.441
958261AF2-120 C
Adder
9.1988235294117657.819
934146AD1-041 E
Adder
5.5776470588235294.741
316382AG1-145 C
50/50
0.6360.636
939191AE1-149 C
Adder
14.42941176470588312.265
3150981CHESPKA
50/50
0.7870.787
901082W1-029 E
50/50
55.655.6
957601AF2-054 C
Adder
3.36117647058823542.857
966662AG1-536 E
Adder
10.6329411764705889.038
962862AG1-135 E
Adder
5.985.083
943742AF1-042 E
Adder
7.1235294117647056.055
934392AD1-063 E
Adder
1.69764705882352951.443
916191Z1-068 C
50/50
0.0790.079
941101AE2-104 C
50/50
5.7555.755
316185AD1-033 C
50/50
2.2242.224
944581AF1-123 C
50/50
83.73183.731
316294AC1-161 C
50/50
9.6819.681
316141AB2-099 E
Adder
0.37882352941176470.322
316088AB2-174 E
Adder
8.6929411764705897.389
923994AB2-040_E
Adder
8.2482352941176477.011
940551AE2-041 C
Adder
11.3211764705882359.623
935162AD1-151 E
Adder
15.29411764705882413
943461AF1-017 C
Adder
2.17764705882352951.851
932596AC2-079 E
Adder
15.21999999999999912.937
316311AC2-079 C
Adder
9.3282352941176477.929
938532AE1-072 E
50/50
16.42416.424
3146326AYDLETT TAP
50/50
2.4292.429
917122Z2-027 E
50/50
2.3642.364
3156056W1-029WIND
50/50
1.351.35
920692AA2-178 E
Adder
6.7435294117647065.732
957832AF2-077 E
50/50
2.4692.469
939246AE1-155 E
Adder
12.80941176470588310.888
924814AB2-134 E
Adder
18.51882352941176515.741
942342AE2-247 E
Adder
3.3247058823529412.826
316036AC1-147 C
50/50
0.6650.665
316305AF2-043 C
50/50
0.6160.616
919152AA1-139 E1
50/50
7.3487.348
316321Z2-027 C
50/50
0.6380.638
934521AD1-076 C
Adder
19.5552941176470616.622
934511AD1-075 C
Adder
13.46117647058823511.442
920042AA2-088 E OP
Adder
16.1705882352941213.745
3145723EMPORIA
Adder
0.57058823529411760.485
923573AB1-173 E OP
Adder
4.3988235294117643.739
919692AA2-053 E OP
Adder
5.8800000000000014.998
3141813NORNECK
Adder
1.24235294117647071.056
962861AG1-135 C
Adder
8.9694117647058827.624
943741AF1-042 C
Adder
4.3658823529411773.711
939192AE1-149 E
Adder
9.628.177
939312AE1-162 E
50/50
2.4312.431
934065AD1-033 E
50/50
9.1079.107
937226AE2-253 E
50/50
10.53510.535
3156116Z1-036WIND
50/50
1.1111.111
934501AD1-074 C
Adder
53.8447058823529445.768
924517AB2-100 E2
Adder
3.87764705882352923.296
963612AG1-210 E
Adder
1.39882352941176481.189
316159AE1-175 C
50/50
0.7040.704
943462AF1-017 E
Adder
3.55294117647058853.02
942341AE2-247 C
Adder
2.40705882352941152.046
316246AF1-032 C
50/50
0.5030.503
958162AF2-110 E
50/50
3.7353.735
316388AE2-253 GEN
50/50
3.5313.531
919153AA1-139 E2
50/50
7.3487.348
316320Y1-086 C
50/50
0.3880.388
934502AD1-074 E
Adder
27.4094117647058823.298
934512AD1-075 E
Adder
6.8529411764705895.825
918512AA1-065 E OP
Adder
8.4494117647058827.182
924516AB2-100 E1
Adder
3.87764705882352923.296
940642AE2-051 E
50/50
17.58317.583
966621AG1-532 C
Adder
1.84588235294117651.569
936591AD2-074 C
Adder
8.3435294117647067.092
939602AE1-190 E
Adder
2.23058823529411751.896
3130536PAPERMILL
Adder
10.4988235294117648.924
934576AD1-082 E
Adder
6.4070588235294125.446
943612AF1-032 E
50/50
1.6391.639
3145506HICKORY
50/50
3.9493.949
944602AF1-125 E
50/50
188.725188.725
957871AF2-081 C
50/50
17.9717.97
933292AC2-141 E
50/50
25.37725.377
940492AE2-034 E
Adder
5.057647058823534.299
934522AD1-076 E
Adder
9.9670588235294128.472
943172AE2-346 E
Adder
0.90941176470588240.773
918492AA1-063AE OP
Adder
5.82352941176470654.95
925122AB2-169 E
Adder
8.6941176470588237.39
917332KELFORD E
Adder
2.42.04
316078AC2-138 E
Adder
1.30588235294117671.11
966661AG1-536 C
Adder
7.9129411764705886.726
958262AF2-120 E
Adder
6.1329411764705885.213
939612AE1-191 E
Adder
8.9247058823529427.586
934012AD1-025 E
Adder
14.63647058823529612.441
3151161SURRY 1
50/50
40.01540.015
3150991CHESPKB
50/50
1.3041.304
913392Y1-086 E
50/50
3.893.89
939411AE1-173 C
50/50
144.69144.69
3137643SOCKMAN
Adder
0.96588235294117640.821
957602AF2-054 E
Adder
2.24117647058823531.905
936592AD2-074 E
Adder
13.61411764705882311.572
316160AE1-175 E
50/50
2.1482.148
944631AF1-128 C
Adder
50.1435294117647142.622
3150921YORKTN3
50/50
222.183222.183
3145256KINGFORK
50/50
1.7881.788
925522AC1-027 E
50/50
2.2062.206
941102AE2-104 E
50/50
9.159.15
957872AF2-081 E
50/50
7.7017.701
316018AA1-139 ULT2
50/50
1.9391.939
933291AC2-141 C
50/50
59.4559.45
926755AC1-161 E
50/50
25.37725.377
943471AF1-018 C
Adder
11.3211764705882359.623
926785AC1-164_E
50/50
29.20829.208
316236AE1-162 C
50/50
0.5940.594
316084AB2-161 E
Adder
8.0411764705882356.835
3152331SURRY 2
50/50
52.5452.54
316017AA1-139 ULT1
50/50
1.9391.939
313526AB2-022 C
50/50
0.6650.665
3145946PLYMOUTH TP
Adder
0.51882352941176470.441
933982AD1-022 E
Adder
7.5341176470588246.404
940641AE2-051 C
50/50
26.37426.374
900672V4-068 E
Adder
0.53882352941176470.458
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.41628.416
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.24623.246
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.853.85
LAGNLTFEXP_LAGN->PJM
CLTF
8.2678.267
NYPJM->LTFIMP_NY
CLTF
2.0382.038
LGEELTFEXP_LGEE->PJM
CLTF
1.1621.162
WECLTFEXP_WEC->PJM
CLTF
0.5990.599
G-007PJM->LTFIMP_G-007
CMTX_NF
4.3044.304
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.5566.556
CBM South 2LTFEXP_CBM-S2->PJM
CBM
111.34111.34
CPLELTFEXP_CPLE->PJM
CLTF
13.75813.758
TVALTFEXP_TVA->PJM
CLTF
6.4816.481
O66PJM->LTFIMP_O-066
CMTX_NF
27.4327.43

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.58 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4541.47
MW Contribution:8.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316075AC2-137 C
80/20
0.6870.687
3150611CHESTG7
80/20
6.9316.931
3150801HOPHCF4
80/20
6.5586.558
316369AC1-216 C
80/20
2.8462.846
3150831SPRUNCA
Adder
15.78000000000000113.413
3150841SPRUNCB
Adder
15.78000000000000113.413
961941AG1-037 C
Adder
0.82117647058823530.698
941031AE2-094 C
Adder
59.24117647058823650.355
934331AD1-057 C
Adder
5.3847058823529414.577
934321AD1-056 C
Adder
9.6541176470588248.206
966871AG1-558 C
Adder
4.0835294117647063.471
964211AG1-282 C
Adder
2.9811764705882352.534
3150601CHESTF5
80/20
113.981113.981
3150631CHESTG8
80/20
6.826.82
3150621CHESTS7
80/20
3.1823.182
941591AE2-156 C
Adder
31.64823529411764726.901
944591AF1-124 C
Adder
80.4988235294117868.424
944601AF1-125 C
Adder
78.9788235294117767.132
938771AE1-103 C
Adder
4.9788235294117654.232
960081AF2-299 C
Adder
2.92.465
944011AF1-069 C
Adder
19.35647058823529316.453
963041AG1-153 C
Adder
8.3011764705882357.056
936261AD2-033 C
Adder
18.25529411764705815.517
940551AE2-041 C
Adder
12.16117647058823610.337
3150691DARBY 3
80/20
4.5924.592
943461AF1-017 C
Adder
2.34941176470588251.997
316311AC2-079 C
Adder
9.984705882352948.487
316233AE1-074 C
Adder
4.08588235294117653.473
3150781HOPHCF2
80/20
4.324.32
3150761HOPPOLC
80/20
2.7172.717
316004AC1-112 C
80/20
0.5960.596
944641AF1-129 C
Adder
179.8423529411765152.866
316240AF1-291 C
Adder
3.78000000000000023.213
934521AD1-076 C
Adder
20.41647058823529517.354
934511AD1-075 C
Adder
14.05411764705882411.946
3142296MT RD221
80/20
0.2170.217
316263AC1-034 C
Adder
10.102352941176478.587
962861AG1-135 C
Adder
9.3188235294117667.921
943741AF1-042 C
Adder
4.5552941176470593.872
3150641CHESTS8
80/20
3.5113.511
3150671DARBY 1
80/20
4.574.57
942001AE2-212 C
Adder
3.73882352941176473.178
934501AD1-074 C
Adder
56.2176470588235347.785
961671AG1-007 C
Adder
1.44941176470588241.232
934621AD1-088 C
Adder
13.69294117647058911.639
944631AF1-128 C
80/20
71.31971.319
3150921YORKTN3
80/20
215.99215.99
3151191GRAVEL3
80/20
4.4484.448
933291AC2-141 C
80/20
54.34454.344
316169AC1-164 GEN
80/20
73.90473.904
316349AD2-085 C
Adder
5.9917647058823535.093
946281AF1-292 C
Adder
2.40117647058823552.041
926071AC1-086 C
Adder
32.9752941176470628.029
927021AC1-189 C
Adder
13.13058823529411811.161
964241AG1-285 C
Adder
17.71058823529411815.054
940431AE2-027 C
Adder
22.58000000000000219.193
3150681DARBY 2
80/20
4.5764.576
941101AE2-104 C
Adder
5.8423529411764714.966
944581AF1-123 C
Adder
80.2141176470588368.182
316294AC1-161 C
80/20
8.8498.849
957481AF2-042 C
Adder
77.7682352941176466.103
936591AD2-074 C
Adder
8.7058823529411787.4
934011AD1-025 C
80/20
4.6114.611
316033AB2-134 GEN
80/20
3.7293.729
3150651CHESTF6
Adder
32.7447058823529427.833
957871AF2-081 C
Adder
17.51647058823529314.889
316274AC1-208 C
Adder
14.04588235294117711.939
3151311EDGECMA
Adder
23.6270588235294120.083
316159AE1-175 C
80/20
0.7120.712
3150771HOPHCF1
80/20
4.324.32
942341AE2-247 C
Adder
2.5964705882352942.207
966621AG1-532 C
Adder
2.1752941176470591.849
943471AF1-018 C
Adder
12.16117647058823610.337
3151221GRAVEL6
80/20
4.54.5
3151201GRAVEL4
80/20
4.5054.505
3152331SURRY 2
80/20
45.81645.816
940641AE2-051 C
Adder
26.97529411764705622.929
316336AC2-165 C
Adder
13.90823529411764711.822
3150731STONECA
80/20
12.27512.275
935161AD1-151 C
80/20
28.71928.719
3150701DARBY 4
80/20
4.5974.597
3142366NRTHEST
80/20
0.330.33
958161AF2-110 C
Adder
2.38352941176470572.026
938531AE1-072 C
Adder
30.76823529411764526.153
933981AD1-022 C
Adder
14.54588235294117712.364
963611AG1-210 C
Adder
0.95764705882352940.814
961611AG1-000B C
80/20
28.34928.349
940541AE2-040 C
Adder
4.5529411764705883.87
940481AE2-033 C
Adder
25.6411764705882421.795
927041AC1-191 C
Adder
16.39529411764705813.936
961951AG1-038 C
Adder
5.035294117647064.28
3144216WINCHST
80/20
0.2370.237
3150791HOPHCF3
80/20
4.324.32
958261AF2-120 C
Adder
9.5447058823529418.113
316382AG1-145 C
80/20
0.6420.642
3143096IRON208
80/20
0.7870.787
316132AB2-190 C
80/20
7.3677.367
939191AE1-149 C
Adder
18.60588235294117615.815
957601AF2-054 C
Adder
3.56235294117647073.028
966661AG1-536 C
Adder
8.2105882352941186.979
316312AB1-027 C
80/20
0.9570.957
3151161SURRY 1
80/20
43.78843.788
939411AE1-173 C
Adder
145.74235294117648123.881
3137643SOCKMAN
Adder
1.1117647058823530.945
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.27284.272
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.64648.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5619.561
LAGNLTFEXP_LAGN->PJM
CLTF
15.45715.457
NYPJM->LTFIMP_NY
CLTF
4.1344.134
LGEELTFEXP_LGEE->PJM
CLTF
3.3563.356
WECLTFEXP_WEC->PJM
CLTF
1.7261.726
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4058.405
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.686156.686
CPLELTFEXP_CPLE->PJM
CLTF
17.60717.607
TVALTFEXP_TVA->PJM
CLTF
12.412.4

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.48 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5586.06
MW Contribution:20.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936591AD2-074 C
Adder
8.77.395
939602AE1-190 E
Adder
2.40470588235294122.044
3130536PAPERMILL
Adder
11.342352941176479.641
3150651CHESTF6
Adder
32.7305882352941227.821
946262AF1-291 E
Adder
2.5188235294117652.141
934576AD1-082 E
Adder
7.6470588235294126.5
943612AF1-032 E
Adder
1.61764705882352941.375
3145506HICKORY
Adder
3.83058823529411763.256
944602AF1-125 E
Adder
180.73058823529414153.621
957871AF2-081 C
Adder
17.5105882352941214.884
933292AC2-141 E
Adder
23.1894117647058819.711
940492AE2-034 E
Adder
5.2011764705882364.421
934522AD1-076 E
Adder
10.4035294117647078.843
943172AE2-346 E
Adder
0.98588235294117640.838
918492AA1-063AE OP
Adder
6.5082352941176485.532
925122AB2-169 E
Adder
9.3470588235294127.945
917332KELFORD E
Adder
2.63882352941176462.243
940551AE2-041 C
Adder
12.15411764705882410.331
935162AD1-151 E
Adder
19.1376470588235316.267
3150691DARBY 3
50/50
4.5894.589
943461AF1-017 C
Adder
2.34941176470588251.997
932596AC2-079 E
Adder
16.2847058823529413.842
316311AC2-079 C
Adder
9.9811764705882358.484
938532AE1-072 E
Adder
16.0329411764705913.628
3146326AYDLETT TAP
Adder
2.3717647058823532.016
917122Z2-027 E
Adder
2.3352941176470591.985
920692AA2-178 E
Adder
6.9352941176470585.895
316233AE1-074 C
Adder
4.08588235294117653.473
966622AG1-532 E
Adder
1.45058823529411771.233
927042AC1-191 E
Adder
8.1611764705882366.937
957832AF2-077 E
Adder
2.49294117647058842.119
316169AC1-164 GEN
50/50
73.86273.862
930122AB1-027 E
50/50
2.5162.516
935112AD1-144 E
Adder
1.66000000000000011.411
316349AD2-085 C
Adder
5.9894117647058835.091
944582AF1-123 E
Adder
183.61176470588234156.07
944592AF1-124 E
Adder
184.2764705882353156.635
923832AB2-022 E
Adder
2.16117647058823531.837
943471AF1-018 C
Adder
12.15411764705882410.331
926785AC1-164_E
50/50
33.18433.184
316084AB2-161 E
Adder
9.597647058823538.158
3152331SURRY 2
50/50
45.79645.796
3145946PLYMOUTH TP
Adder
0.540.459
933982AD1-022 E
Adder
7.9164705882352956.729
940641AE2-051 C
Adder
26.96705882352941322.922
3150731STONECA
Adder
12.26941176470588210.429
935161AD1-151 C
Adder
28.70588235294117424.4
3150701DARBY 4
50/50
4.5944.594
3142366NRTHEST
50/50
0.330.33
932046AC2-012 E
Adder
23.15176470588235319.679
958161AF2-110 C
Adder
2.38352941176470572.026
938531AE1-072 C
Adder
30.75647058823529526.143
3145393UNCAMP
Adder
10.2788235294117658.737
933981AD1-022 C
Adder
14.54117647058823512.36
900672V4-068 E
Adder
0.58235294117647060.495
316159AE1-175 C
50/50
0.7110.711
926412AC1-112 E
50/50
2.0462.046
943462AF1-017 E
Adder
3.8317647058823533.257
942341AE2-247 C
Adder
2.5964705882352942.207
958162AF2-110 E
Adder
3.79058823529411763.222
919153AA1-139 E2
Adder
7.166.086
3138116ELKO L286
50/50
2.5282.528
961611AG1-000B C
Adder
28.33647058823529424.086
940541AE2-040 C
Adder
4.5517647058823533.869
940481AE2-033 C
Adder
25.63411764705882621.789
940482AE2-033 E
Adder
17.28117647058823514.689
923263AB1-132 E OP
Adder
9.595294117647068.156
927041AC1-191 C
Adder
16.38352941176470513.926
936592AD2-074 E
Adder
14.19411764705882312.065
316160AE1-175 E
50/50
2.1682.168
944631AF1-128 C
50/50
71.28371.283
3150921YORKTN3
Adder
215.8894117647059183.506
3145256KINGFORK
Adder
1.78823529411764711.52
925522AC1-027 E
Adder
2.14588235294117661.824
941102AE2-104 E
Adder
9.2858823529411767.893
957872AF2-081 E
Adder
7.50470588235294046.379
933291AC2-141 C
Adder
54.3223529411764746.174
926755AC1-161 E
Adder
23.1894117647058819.711
938552AE1-074 E
Adder
2.05764705882352941.749
938772AE1-103 E
Adder
6.8741176470588235.843
916042Z1-036 E
Adder
48.916470588235341.579
960082AF2-299 E
Adder
1.93294117647058841.643
946281AF1-292 C
Adder
2.40117647058823552.041
926071AC1-086 C
Adder
32.9682352941176528.023
963042AG1-153 E
Adder
12.44941176470588410.582
923842AB2-024 E
Adder
3.07294117647058852.612
316075AC2-137 C
50/50
0.6870.687
316076AC2-137 E
50/50
2.4242.424
3150611CHESTG7
50/50
6.9276.927
3150831SPRUNCA
Adder
15.77411764705882313.408
3150841SPRUNCB
Adder
15.77411764705882313.408
926662AC1-147 E
Adder
2.34000000000000031.989
916192Z1-068 E
Adder
3.3141176470588242.817
957492AF2-043 E
Adder
2.48941176470588272.116
923852AB2-025 E
Adder
1.84117647058823521.565
939412AE1-173 E
Adder
97.132941176470682.563
961942AG1-037 E
Adder
0.54705882352941180.465
961941AG1-037 C
Adder
0.82117647058823530.698
941031AE2-094 C
Adder
59.2294117647058850.345
941032AE2-094 E
Adder
26.52705882352941222.548
966871AG1-558 C
Adder
4.083.468
966872AG1-558 E
Adder
2.0552941176470591.747
316157AD2-030 E
Adder
1.99764705882352931.698
962962AG1-145 E
50/50
2.6282.628
3150601CHESTF5
50/50
113.923113.923
3150631CHESTG8
50/50
6.8166.816
3150621CHESTS7
50/50
3.183.18
925332AB2-190 E
Adder
14.35882352941176512.205
927226AC1-216 E
Adder
13.74117647058823411.68
936666AD2-085 E
Adder
9.7729411764705898.307
941591AE2-156 C
Adder
31.63647058823529426.891
944591AF1-124 C
Adder
80.4682352941176568.398
944601AF1-125 C
Adder
78.9482352941176467.106
938771AE1-103 C
Adder
4.9776470588235294.231
3145413WATKINS
Adder
1.15882352941176480.985
960081AF2-299 C
Adder
2.92.465
926072AC1-086 E
Adder
15.0047058823529412.754
944011AF1-069 C
Adder
19.35294117647058716.45
963041AG1-153 C
Adder
8.37.055
961952AG1-038 E
Adder
6.9482352941176475.906
961951AG1-038 C
Adder
5.0317647058823534.277
925865AC1-065 E
Adder
28.22117647058823723.988
946282AF1-292 E
Adder
1.61.36
944012AF1-069 E
Adder
7.5176470588235296.39
934146AD1-041 E
Adder
6.0129411764705885.111
316382AG1-145 C
50/50
0.6420.642
939191AE1-149 C
Adder
18.59882352941176415.809
3143316POE
Adder
2.31058823529411761.964
901082W1-029 E
Adder
55.2529411764705946.965
957601AF2-054 C
Adder
3.56117647058823563.027
943742AF1-042 E
Adder
7.42705882352941156.313
934392AD1-063 E
Adder
1.8235294117647061.55
940431AE2-027 C
Adder
22.57058823529411719.185
3150681DARBY 2
50/50
4.5734.573
942002AE2-212 E
Adder
2.49058823529411782.117
941101AE2-104 C
Adder
5.8411764705882354.965
944581AF1-123 C
Adder
80.1835294117647168.156
316141AB2-099 E
Adder
0.410588235294117640.349
316088AB2-174 E
Adder
10.1435294117647078.622
923994AB2-040_E
Adder
9.5835294117647068.146
957481AF2-042 C
Adder
70.616470588235360.024
924814AB2-134 E
Adder
22.5082352941176519.132
316004AC1-112 C
50/50
0.5960.596
944641AF1-129 C
Adder
179.7623529411765152.798
316240AF1-291 C
Adder
3.7788235294117653.212
942342AE2-247 E
Adder
3.58470588235294143.047
919152AA1-139 E1
Adder
7.166.086
934521AD1-076 C
Adder
20.41176470588235517.35
934511AD1-075 C
Adder
14.05058823529411811.943
920042AA2-088 E OP
Adder
17.4414.824
3142296MT RD221
50/50
0.2170.217
3145723EMPORIA
Adder
0.66941176470588230.569
923573AB1-173 E OP
Adder
5.11176470588235254.345
919692AA2-053 E OP
Adder
6.6552941176470595.657
943741AF1-042 C
Adder
4.5517647058823533.869
3150641CHESTS8
50/50
3.5093.509
3150671DARBY 1
50/50
4.5674.567
939192AE1-149 E
Adder
12.39882352941176410.539
939312AE1-162 E
Adder
2.54117647058823562.16
942001AE2-212 C
Adder
3.73647058823529443.176
934065AD1-033 E
Adder
8.8270588235294137.503
937226AE2-253 E
Adder
10.2482352941176478.711
934501AD1-074 C
Adder
56.2023529411764747.772
924517AB2-100 E2
Adder
4.5505882352941183.868
939612AE1-191 E
Adder
9.628.177
940432AE2-027 E
Adder
15.04705882352941212.79
934012AD1-025 E
Adder
17.78941176470588215.121
316312AB1-027 C
50/50
0.9560.956
913392Y1-086 E
Adder
3.8282352941176473.254
939411AE1-173 C
Adder
145.69882352941175123.844
3137643SOCKMAN
Adder
1.1117647058823530.945
957602AF2-054 E
Adder
2.37411764705882342.018
934502AD1-074 E
Adder
28.60941176470588624.318
934512AD1-075 E
Adder
7.1529411764705896.08
918512AA1-065 E OP
Adder
9.0517647058823547.694
924516AB2-100 E1
Adder
4.5505882352941183.868
940642AE2-051 E
Adder
17.97882352941176615.282
966621AG1-532 C
Adder
2.1752941176470591.849
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.33484.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.67448.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5679.567
LAGNLTFEXP_LAGN->PJM
CLTF
15.46415.464
NYPJM->LTFIMP_NY
CLTF
4.1384.138
LGEELTFEXP_LGEE->PJM
CLTF
3.3583.358
WECLTFEXP_WEC->PJM
CLTF
1.7271.727
G-007PJM->LTFIMP_G-007
CMTX_NF
9.2239.223
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4068.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.721156.721
CPLELTFEXP_CPLE->PJM
CLTF
17.60917.609
TVALTFEXP_TVA->PJM
CLTF
12.40612.406
O66PJM->LTFIMP_O-066
CMTX_NF
58.60758.607

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.74 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4100.48
MW Contribution:7.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316075AC2-137 C
80/20
0.5730.573
3150611CHESTG7
80/20
5.6125.612
316369AC1-216 C
80/20
2.3642.364
3150831SPRUNCA
Adder
10.6141176470588259.022
3150841SPRUNCB
Adder
10.6141176470588259.022
3151081ELIZAR1
80/20
4.8584.858
961941AG1-037 C
Adder
0.69764705882352940.593
941031AE2-094 C
Adder
50.196470588235342.667
934331AD1-057 C
Adder
4.5482352941176483.866
934321AD1-056 C
Adder
8.1541176470588246.931
966871AG1-558 C
Adder
3.3847058823529412.877
964211AG1-282 C
Adder
2.5270588235294122.148
940551AE2-041 C
Adder
10.3670588235294128.812
943461AF1-017 C
Adder
1.99058823529411751.692
316311AC2-079 C
Adder
8.4682352941176487.198
316004AC1-112 C
80/20
0.5060.506
944641AF1-129 C
Adder
143.61529411764707122.073
316240AF1-291 C
Adder
3.02705882352941162.573
316036AC1-147 C
80/20
0.5590.559
316305AF2-043 C
80/20
0.5230.523
316321Z2-027 C
80/20
0.5420.542
934521AD1-076 C
Adder
17.4447058823529414.828
934511AD1-075 C
Adder
12.00823529411764810.207
3142296MT RD221
80/20
0.180.18
316263AC1-034 C
Adder
8.5517647058823547.269
962861AG1-135 C
Adder
7.9105882352941186.724
943741AF1-042 C
Adder
3.87058823529411773.29
3150641CHESTS8
80/20
2.8432.843
942001AE2-212 C
Adder
3.01764705882352932.565
934501AD1-074 C
Adder
48.0341176470588340.829
961671AG1-007 C
Adder
1.22941176470588221.045
934621AD1-088 C
Adder
11.2658823529411789.576
944631AF1-128 C
80/20
57.75157.751
3150921YORKTN3
80/20
186.63186.63
3151191GRAVEL3
80/20
3.7583.758
316018AA1-139 ULT2
80/20
1.6281.628
933291AC2-141 C
80/20
47.32947.329
3152181CUNINGC
80/20
7.9167.916
3150601CHESTF5
80/20
92.29692.296
3150631CHESTG8
80/20
5.5225.522
3150621CHESTS7
80/20
2.5762.576
941591AE2-156 C
80/20
27.25627.256
3151101ELIZAR3
80/20
4.9194.919
944591AF1-124 C
80/20
69.53869.538
944601AF1-125 C
80/20
68.22568.225
938771AE1-103 C
Adder
4.2458823529411773.609
960081AF2-299 C
Adder
2.4235294117647062.06
944011AF1-069 C
Adder
16.40117647058823613.941
963041AG1-153 C
Adder
7.0223529411764725.969
940431AE2-027 C
Adder
18.18117647058823715.454
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
55
316185AD1-033 C
80/20
1.8591.859
944581AF1-123 C
80/20
69.29269.292
316294AC1-161 C
80/20
7.7077.707
957481AF2-042 C
Adder
64.7188235294117655.011
3152191CUNINGD
80/20
17.70617.706
936591AD2-074 C
Adder
7.3964705882352946.287
934011AD1-025 C
80/20
3.8313.831
316033AB2-134 GEN
80/20
3.0983.098
3150651CHESTF6
Adder
26.14823529411764722.226
957871AF2-081 C
80/20
15.09215.092
316274AC1-208 C
Adder
11.86588235294117810.086
3151311EDGECMA
Adder
20.00352941176470617.003
943471AF1-018 C
Adder
10.3670588235294128.812
3151221GRAVEL6
80/20
3.8023.802
3151201GRAVEL4
80/20
3.8063.806
3151211GRAVEL5
80/20
3.7583.758
316236AE1-162 C
80/20
0.5280.528
3152331SURRY 2
80/20
40.26840.268
316017AA1-139 ULT1
80/20
1.6281.628
313526AB2-022 C
80/20
0.5630.563
940641AE2-051 C
Adder
23.00823529411764719.557
316169AC1-164 GEN
80/20
63.00863.008
316349AD2-085 C
Adder
5.0752941176470594.314
3151091ELIZAR2
80/20
4.7734.773
946281AF1-292 C
Adder
2.00588235294117641.705
926071AC1-086 C
Adder
27.76352941176470823.599
927021AC1-189 C
Adder
11.1482352941176499.476
3150731STONECA
Adder
9.9858823529411778.488
935161AD1-151 C
80/20
23.75423.754
958161AF2-110 C
80/20
2.042.04
938531AE1-072 C
80/20
26.50226.502
933981AD1-022 C
Adder
12.41647058823529510.554
316159AE1-175 C
80/20
0.6130.613
942341AE2-247 C
Adder
2.21.87
316246AF1-032 C
80/20
0.4270.427
316388AE2-253 GEN
80/20
2.9612.961
316320Y1-086 C
80/20
0.3290.329
966621AG1-532 C
Adder
1.81764705882352941.545
963611AG1-210 C
Adder
0.81058823529411760.689
961611AG1-000B C
80/20
23.84623.846
316072AD1-144 C
80/20
0.4250.425
316375AC2-012 C
80/20
2.0492.049
940541AE2-040 C
Adder
3.7941176470588243.225
940481AE2-033 C
Adder
21.37647058823529618.17
927041AC1-191 C
Adder
13.58823529411764911.55
957831AF2-077 C
80/20
0.4940.494
961951AG1-038 C
Adder
4.277647058823533.636
3144216WINCHST
80/20
0.2040.204
316316AC1-027 C
80/20
0.4790.479
3152161CUNINGA
80/20
7.9167.916
3152171CUNINGB
80/20
7.9167.916
958261AF2-120 C
Adder
8.16.885
316382AG1-145 C
80/20
0.5540.554
3151171GRAVELC
80/20
1.2921.292
939191AE1-149 C
Adder
15.33294117647058713.033
3150981CHESPKA
80/20
0.6610.661
957601AF2-054 C
Adder
3.03647058823529432.581
966661AG1-536 C
Adder
6.96705882352941155.922
316312AB1-027 C
80/20
0.8120.812
3151161SURRY 1
80/20
36.99436.994
3150991CHESPKB
80/20
1.0961.096
939411AE1-173 C
Adder
124.68470588235294105.982
3137643SOCKMAN
Adder
0.93411764705882360.794
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.17274.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.32542.325
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.3698.369
LAGNLTFEXP_LAGN->PJM
CLTF
13.38813.388
NYPJM->LTFIMP_NY
CLTF
3.5973.597
LGEELTFEXP_LGEE->PJM
CLTF
2.952.95
WECLTFEXP_WEC->PJM
CLTF
1.5171.517
SIGELTFEXP_SIGE->PJM
CLTF
0.5440.544
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1467.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
133.887133.887
CPLELTFEXP_CPLE->PJM
CLTF
14.96914.969
TVALTFEXP_TVA->PJM
CLTF
10.74810.748

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.93 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4252.56
MW Contribution:11.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150731STONECA
Adder
6.46823529411764755.498
935161AD1-151 C
Adder
15.04823529411764812.791
3150701DARBY 4
50/50
2.4382.438
3142366NRTHEST
50/50
0.1760.176
932046AC2-012 E
Adder
11.9823529411764710.185
958161AF2-110 C
Adder
1.24117647058823531.055
938531AE1-072 C
Adder
15.94470588235294213.553
3145393UNCAMP
Adder
5.3964705882352944.587
933981AD1-022 C
Adder
7.6564705882352946.508
900672V4-068 E
Adder
0.308235294117647050.262
315051AA1-145 CT1
50/50
4.7834.783
3138116ELKO L286
50/50
1.3131.313
961611AG1-000B C
Adder
14.76705882352941212.552
940541AE2-040 C
Adder
2.442.074
940481AE2-033 C
Adder
13.74117647058823411.68
940482AE2-033 E
Adder
9.2635294117647067.874
927041AC1-191 C
Adder
9.0164705882352937.664
936592AD2-074 E
Adder
7.7847058823529426.617
316160AE1-175 E
Adder
1.11058823529411770.944
944631AF1-128 C
Adder
37.3682352941176531.763
3150921YORKTN3
Adder
110.8188235294117694.196
3145256KINGFORK
Adder
0.92823529411764720.789
925522AC1-027 E
Adder
1.11058823529411770.944
941102AE2-104 E
Adder
4.8364705882352944.111
957872AF2-081 E
Adder
3.88941176470588263.306
316169AC1-164 GEN
Adder
37.8729411764705932.192
930122AB1-027 E
50/50
1.3221.322
935112AD1-144 E
Adder
0.86117647058823530.732
316349AD2-085 C
Adder
3.13411764705882372.664
944582AF1-123 E
Adder
94.9280.682
944592AF1-124 E
Adder
95.2635294117647180.974
923832AB2-022 E
Adder
1.12235294117647060.954
938772AE1-103 E
Adder
3.60352941176470633.063
916042Z1-036 E
Adder
25.53647058823529321.706
960082AF2-299 E
Adder
1.040.884
946281AF1-292 C
Adder
1.29176470588235311.098
963042AG1-153 E
Adder
6.7294117647058825.72
966882AG1-559 E
50/50
1.1551.155
939261AE1-157 C
Adder
13.28588235294117611.293
923842AB2-024 E
Adder
1.61176470588235321.37
316075AC2-137 C
50/50
0.3570.357
316076AC2-137 E
50/50
1.2591.259
3150831SPRUNCA
Adder
8.5294117647058827.25
3150841SPRUNCB
Adder
8.5294117647058827.25
926662AC1-147 E
Adder
1.2117647058823531.03
916192Z1-068 E
Adder
1.71529411764705891.458
957492AF2-043 E
Adder
1.29176470588235311.098
923852AB2-025 E
Adder
0.98705882352941180.839
939412AE1-173 E
Adder
51.40235294117647443.692
961942AG1-037 E
Adder
0.290588235294117650.247
961941AG1-037 C
Adder
0.435294117647058830.37
941031AE2-094 C
Adder
31.94588235294117627.154
941032AE2-094 E
Adder
14.3082352941176512.162
966871AG1-558 C
Adder
2.24588235294117671.909
966872AG1-558 E
Adder
1.1317647058823530.962
923862AB2-026 E
Adder
1.02941176470588250.875
316157AD2-030 E
Adder
1.05647058823529430.898
962962AG1-145 E
Adder
1.34588235294117631.144
3150601CHESTF5
Adder
59.7211764705882350.763
925332AB2-190 E
Adder
7.537647058823536.407
927226AC1-216 E
Adder
7.19176470588235356.113
936666AD2-085 E
Adder
5.11411764705882454.347
941591AE2-156 C
Adder
16.3729411764705913.917
944591AF1-124 C
Adder
41.5988235294117735.359
944601AF1-125 C
Adder
40.81294117647059534.691
938771AE1-103 C
Adder
2.60941176470588232.218
3145413WATKINS
Adder
0.60941176470588240.518
960081AF2-299 C
Adder
1.56117647058823541.327
944011AF1-069 C
Adder
10.437647058823538.872
963041AG1-153 C
Adder
4.4858823529411773.813
966881AG1-559 C
50/50
2.2942.294
961952AG1-038 E
Adder
3.81058823529411763.239
961951AG1-038 C
Adder
2.7588235294117652.345
925865AC1-065 E
Adder
14.8929411764705912.659
946282AF1-292 E
Adder
0.86117647058823530.732
944012AF1-069 E
Adder
4.0552941176470593.447
3150431FOUR RIVERA
50/50
3.0033.003
939262AE1-157 E
Adder
7.2070588235294136.126
934146AD1-041 E
Adder
3.17647058823529442.7
939191AE1-149 C
Adder
9.8564705882352958.378
3143316POE
Adder
1.23411764705882351.049
901082W1-029 E
Adder
28.74235294117647424.431
957601AF2-054 C
Adder
1.8835294117647061.601
962862AG1-135 E
Adder
3.43764705882352972.922
943742AF1-042 E
Adder
4.07294117647058853.462
934392AD1-063 E
Adder
0.960.816
940431AE2-027 C
Adder
12.02823529411764810.224
3150681DARBY 2
50/50
2.4262.426
942002AE2-212 E
Adder
1.33058823529411761.131
941101AE2-104 C
Adder
3.04235294117647072.586
944581AF1-123 C
Adder
41.45176470588235435.234
316141AB2-099 E
Adder
0.217647058823529420.185
316088AB2-174 E
Adder
5.4517647058823534.634
923994AB2-040_E
Adder
1.6270588235294121.383
940551AE2-041 C
Adder
6.3964705882352955.437
935162AD1-151 E
Adder
10.0317647058823528.527
3150691DARBY 3
50/50
2.4352.435
943461AF1-017 C
Adder
1.22941176470588221.045
932596AC2-079 E
Adder
8.517647058823537.24
316311AC2-079 C
Adder
5.2200000000000014.437
938532AE1-072 E
Adder
8.3117647058823547.065
3146326AYDLETT TAP
Adder
1.22941176470588221.045
917122Z2-027 E
Adder
1.21294117647058821.031
920692AA2-178 E
Adder
3.6352941176470593.09
316233AE1-074 C
Adder
2.25058823529411761.913
966622AG1-532 E
Adder
0.780.663
927042AC1-191 E
Adder
4.4917647058823533.818
957832AF2-077 E
Adder
1.29764705882352941.103
924814AB2-134 E
Adder
11.78117647058823510.014
316004AC1-112 C
50/50
0.3130.313
944641AF1-129 C
Adder
95.9141176470588381.527
316240AF1-291 C
Adder
2.01647058823529421.714
942342AE2-247 E
Adder
1.87647058823529411.595
919152AA1-139 E1
Adder
3.71058823529411753.154
934521AD1-076 C
Adder
10.7329411764705889.123
934511AD1-075 C
Adder
7.38823529411764756.28
920042AA2-088 E OP
Adder
9.2247058823529417.841
3142296MT RD221
50/50
0.1170.117
3145723EMPORIA
Adder
0.360.306
962861AG1-135 C
Adder
5.1564705882352944.383
943741AF1-042 C
Adder
2.4964705882352942.122
3150671DARBY 1
50/50
2.4232.423
939192AE1-149 E
Adder
6.5717647058823535.586
939312AE1-162 E
Adder
1.31882352941176471.121
942001AE2-212 C
Adder
1.99647058823529421.697
934065AD1-033 E
Adder
4.5682352941176473.883
937226AE2-253 E
Adder
5.30941176470588254.513
934501AD1-074 C
Adder
29.5529411764705925.12
924517AB2-100 E2
Adder
2.4388235294117652.073
958502AF2-144 E
Adder
1.0117647058823530.86
226896D-009
Adder
-1.4576470588235295-1.239
926412AC1-112 E
50/50
1.0751.075
943462AF1-017 E
Adder
2.00588235294117641.705
942341AE2-247 C
Adder
1.35882352941176481.155
958162AF2-110 E
Adder
1.97411764705882351.678
919153AA1-139 E2
Adder
3.71058823529411753.154
934502AD1-074 E
Adder
15.04470588235294112.788
934512AD1-075 E
Adder
3.76117647058823533.197
918512AA1-065 E OP
Adder
4.7847058823529424.067
924516AB2-100 E1
Adder
2.4388235294117652.073
940642AE2-051 E
Adder
9.5882352941176498.15
966621AG1-532 C
Adder
1.17058823529411770.995
3152261N ANNA2
50/50
28.62228.622
226704AOCX4-046 E
Adder
-2.8423529411764705-2.416
936591AD2-074 C
Adder
4.7717647058823534.056
939602AE1-190 E
Adder
1.27058823529411781.08
3130536PAPERMILL
Adder
5.95411764705882355.061
3150651CHESTF6
Adder
17.46352941176470714.844
946262AF1-291 E
Adder
1.34470588235294121.143
934576AD1-082 E
Adder
4.0317647058823533.427
943612AF1-032 E
Adder
0.840.714
3145506HICKORY
Adder
1.98352941176470581.686
944602AF1-125 E
Adder
93.4294117647058979.415
957871AF2-081 C
Adder
9.0741176470588247.713
933292AC2-141 E
Adder
11.89764705882352810.113
940492AE2-034 E
Adder
2.72588235294117662.317
934522AD1-076 E
Adder
5.4705882352941194.65
943172AE2-346 E
Adder
0.52235294117647060.444
918492AA1-063AE OP
Adder
3.47058823529411782.95
3150461FOUR RIVERD
50/50
2.9592.959
3150441FOUR RIVERB
50/50
3.0033.003
939612AE1-191 E
Adder
5.0823529411764714.32
940432AE2-027 E
Adder
8.0188235294117656.816
934012AD1-025 E
Adder
9.3117647058823547.915
316312AB1-027 C
50/50
0.5020.502
913392Y1-086 E
Adder
1.9870588235294121.689
939411AE1-173 C
Adder
77.103529411764765.538
933502AC2-165 E
Adder
6.177647058823535.251
3150451FOUR RIVERC
50/50
3.6693.669
957602AF2-054 E
Adder
1.2552941176470591.067
933291AC2-141 C
Adder
27.87176470588235223.691
926755AC1-161 E
Adder
11.89764705882352810.113
938552AE1-074 E
Adder
1.13294117647058810.963
938562AE1-075 E
Adder
0.87764705882352940.746
3150471FOUR RIVERE
50/50
2.9592.959
315052AA1-145 CT2
50/50
4.7814.781
3152251N ANNA1
50/50
28.6128.61
943471AF1-018 C
Adder
6.3964705882352955.437
926785AC1-164_E
Adder
17.0152941176470614.463
316084AB2-161 E
Adder
5.06000000000000054.301
3145946PLYMOUTH TP
Adder
0.283529411764705860.241
933982AD1-022 E
Adder
4.1682352941176483.543
940641AE2-051 C
Adder
14.38235294117647112.225
316336AC2-165 C
Adder
8.2082352941176486.977
3150481FOUR RIVERF
50/50
3.6143.614
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.34851.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.44428.444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.7125.712
LAGNLTFEXP_LAGN->PJM
CLTF
8.98.9
NYPJM->LTFIMP_NY
CLTF
3.113.11
LGEELTFEXP_LGEE->PJM
CLTF
2.0262.026
WECLTFEXP_WEC->PJM
CLTF
1.0481.048
G-007PJM->LTFIMP_G-007
CMTX_NF
7.0597.059
SIGELTFEXP_SIGE->PJM
CLTF
0.3720.372
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.6074.607
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.84786.847
CPLELTFEXP_CPLE->PJM
CLTF
9.659.65
TVALTFEXP_TVA->PJM
CLTF
7.1437.143
O66PJM->LTFIMP_O-066
CMTX_NF
44.79944.799

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.26 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3228.89
MW Contribution:4.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940551AE2-041 C
Adder
6.2364705882352955.301
3150691DARBY 3
80/20
2.3622.362
943461AF1-017 C
Adder
1.18117647058823531.004
316311AC2-079 C
Adder
5.0141176470588234.262
316233AE1-074 C
Adder
2.1552941176470591.832
3150381LDYSMT2
80/20
4.3034.303
316004AC1-112 C
80/20
0.3050.305
944641AF1-129 C
Adder
92.5282352941176578.649
316240AF1-291 C
Adder
1.94470588235294131.653
934521AD1-076 C
Adder
10.2717647058823538.731
934511AD1-075 C
Adder
7.0705882352941176.01
3142296MT RD221
80/20
0.1140.114
3150411LDYSMT5
80/20
4.4394.439
962861AG1-135 C
Adder
5.0788235294117654.317
943741AF1-042 C
Adder
2.45411764705882352.086
3150641CHESTS8
80/20
1.7811.781
3150671DARBY 1
80/20
2.3512.351
942001AE2-212 C
Adder
1.92117647058823531.633
934501AD1-074 C
Adder
28.28352941176470724.041
934621AD1-088 C
Adder
7.1611764705882356.087
940431AE2-027 C
Adder
11.5988235294117659.859
3150681DARBY 2
80/20
2.3542.354
941101AE2-104 C
Adder
2.92000000000000042.482
944581AF1-123 C
Adder
39.80941176470588533.838
957481AF2-042 C
Adder
40.39647058823529634.337
3150401LDYSMT4
80/20
4.4254.425
936591AD2-074 C
Adder
4.6894117647058823.986
3150651CHESTF6
Adder
16.84705882352941214.32
3150861SPRUNCD
80/20
0.1470.147
957871AF2-081 C
Adder
8.7129411764705887.406
3150461FOUR RIVERD
80/20
2.9092.909
3150441FOUR RIVERB
80/20
2.9522.952
316169AC1-164 GEN
80/20
36.80636.806
316349AD2-085 C
Adder
3.0105882352941182.559
946281AF1-292 C
Adder
1.23176470588235291.047
926071AC1-086 C
Adder
16.83294117647058714.308
939261AE1-157 C
80/20
13.3213.32
943471AF1-018 C
Adder
6.2364705882352955.301
940641AE2-051 C
Adder
13.71529411764705811.658
316336AC2-165 C
Adder
7.7411764705882356.58
3150481FOUR RIVERF
80/20
3.5533.553
3150731STONECA
Adder
6.2458823529411775.309
935161AD1-151 C
Adder
14.5176470588235312.34
3150701DARBY 4
80/20
2.3652.365
3142366NRTHEST
80/20
0.1710.171
958161AF2-110 C
Adder
1.19176470588235281.013
938531AE1-072 C
Adder
15.30823529411764713.012
933981AD1-022 C
Adder
7.3258823529411776.227
315051AA1-145 CT1
80/20
4.7034.703
942341AE2-247 C
Adder
1.30470588235294121.109
966621AG1-532 C
Adder
1.1164705882352940.949
3152261N ANNA2
80/20
26.0926.09
963611AG1-210 C
Adder
0.53882352941176470.458
961611AG1-000B C
Adder
14.23176470588235412.097
940541AE2-040 C
Adder
2.33294117647058831.983
940481AE2-033 C
Adder
13.13529411764705811.165
927041AC1-191 C
80/20
8.8178.817
3150371LDYSMT1
80/20
4.2494.249
944631AF1-128 C
80/20
36.1936.19
3150921YORKTN3
Adder
107.0694117647058991.009
3150851SPRUNCC
80/20
0.1470.147
933291AC2-141 C
Adder
26.7822.763
3150471FOUR RIVERE
80/20
2.9092.909
315052AA1-145 CT2
80/20
4.74.7
3152251N ANNA1
80/20
26.07926.079
316075AC2-137 C
80/20
0.3470.347
3150611CHESTG7
80/20
3.5173.517
3150831SPRUNCA
Adder
8.2188235294117656.986
3150841SPRUNCB
80/20
8.2198.219
961941AG1-037 C
Adder
0.41529411764705880.353
941031AE2-094 C
Adder
30.39411764705882425.835
966871AG1-558 C
80/20
2.1962.196
3150391LDYSMT3
80/20
4.4174.417
964211AG1-282 C
Adder
1.65294117647058841.405
3150601CHESTF5
80/20
57.83757.837
3150631CHESTG8
80/20
3.4613.461
3150621CHESTS7
80/20
1.6141.614
941591AE2-156 C
Adder
15.7305882352941213.371
944591AF1-124 C
Adder
39.9505882352941233.958
944601AF1-125 C
Adder
39.1964705882352933.317
938771AE1-103 C
Adder
2.5011764705882352.126
960081AF2-299 C
Adder
1.48823529411764691.265
944011AF1-069 C
Adder
9.9305882352941198.441
963041AG1-153 C
Adder
4.2658823529411763.626
966881AG1-559 C
80/20
2.2882.288
961951AG1-038 C
Adder
2.7117647058823532.305
3150431FOUR RIVERA
80/20
2.9522.952
958261AF2-120 C
Adder
5.2200000000000014.437
3143096IRON208
80/20
0.4040.404
939191AE1-149 C
Adder
9.4788235294117668.057
957601AF2-054 C
Adder
1.83764705882352961.562
966661AG1-536 C
Adder
4.4905882352941183.817
316312AB1-027 C
80/20
0.4890.489
939411AE1-173 C
Adder
73.6611764705882562.612
3137643SOCKMAN
Adder
0.56941176470588240.484
3150451FOUR RIVERC
80/20
3.6073.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.86545.865
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.97725.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.1595.159
LAGNLTFEXP_LAGN->PJM
CLTF
8.1928.192
NYPJM->LTFIMP_NY
CLTF
2.8322.832
LGEELTFEXP_LGEE->PJM
CLTF
1.8211.821
WECLTFEXP_WEC->PJM
CLTF
0.9380.938
SIGELTFEXP_SIGE->PJM
CLTF
0.3350.335
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.3484.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.51781.517
CPLELTFEXP_CPLE->PJM
CLTF
9.1099.109
TVALTFEXP_TVA->PJM
CLTF
6.5746.574

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.3 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1082.52
MW Contribution:3.61
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151081ELIZAR1
80/20
1.2251.225
943171AE2-346 C
80/20
0.090.09
961941AG1-037 C
80/20
0.2040.204
3151391GASTONA
80/20
1.2541.254
941031AE2-094 C
80/20
26.65326.653
934331AD1-057 C
80/20
1.4711.471
934321AD1-056 C
80/20
2.6372.637
3151531CLOVER1
80/20
6.2476.247
3151541CLOVER2
80/20
6.1886.188
943461AF1-017 C
Adder
0.427058823529411770.363
316311AC2-079 C
Adder
1.8517647058823531.574
3156056W1-029WIND
80/20
0.3040.304
3151261ROARAP2
80/20
0.5630.563
3152421Z1-086 GT2
80/20
6.8556.855
3152441Z1-086 ST
80/20
11.93511.935
3152411Z1-086 GT1
80/20
6.8566.856
316036AC1-147 C
80/20
0.140.14
316305AF2-043 C
80/20
0.1340.134
316321Z2-027 C
80/20
0.1430.143
934521AD1-076 C
80/20
4.9354.935
934511AD1-075 C
80/20
3.3973.397
3156073AA1-063SOLA
80/20
0.5640.564
316087AB2-174 C
80/20
0.4750.475
316212AC1-099 C
80/20
0.130.13
316263AC1-034 C
Adder
2.8352941176470592.41
937481AD2-202 C
80/20
0.1780.178
3151591KERR 2
80/20
0.460.46
3156116Z1-036WIND
80/20
0.260.26
940491AE2-034 C
80/20
0.460.46
934501AD1-074 C
80/20
13.58913.589
3151031BRUNSWICKG2
80/20
5.3085.308
961671AG1-007 C
Adder
0.398823529411764740.339
934621AD1-088 C
80/20
4.3734.373
316283AC2-100 C
80/20
0.5020.502
316018AA1-139 ULT2
80/20
0.4260.426
933291AC2-141 C
80/20
12.90812.908
3152921DOMTR78
80/20
0.5530.553
316140AB2-099 C
80/20
0.0390.039
3151641KERR 7
80/20
0.460.46
941591AE2-156 C
80/20
6.8286.828
3151101ELIZAR3
80/20
1.241.24
944591AF1-124 C
80/20
18.6218.62
944601AF1-125 C
80/20
18.26818.268
938771AE1-103 C
Adder
1.1117647058823530.945
960081AF2-299 C
80/20
0.7530.753
3151381ROSEMG2
80/20
0.3930.393
944011AF1-069 C
80/20
8.7098.709
963041AG1-153 C
80/20
3.6093.609
3151051BRUNSWICKS1
80/20
11.02811.028
316248AF1-058 C
80/20
0.130.13
936171AD2-023 C
Adder
1.81764705882352941.545
916191Z1-068 C
80/20
0.0170.017
941101AE2-104 C
Adder
1.23294117647058821.048
316185AD1-033 C
80/20
0.4830.483
944581AF1-123 C
80/20
18.55418.554
316294AC1-161 C
80/20
2.1022.102
3156083AA2-088SOLA
80/20
0.4170.417
316365AB2-100 C1
80/20
0.3950.395
3151021BRUNSWICKG1
80/20
5.3085.308
957481AF2-042 C
80/20
28.07228.072
957871AF2-081 C
80/20
3.9453.945
932631AC2-084 C
80/20
0.4150.415
316274AC1-208 C
80/20
3.7453.745
3151311EDGECMA
Adder
6.6317647058823535.637
941011AE2-092 C
Adder
-4.542352941176471-3.861
316017AA1-139 ULT1
80/20
0.4260.426
313526AB2-022 C
80/20
0.1480.148
940641AE2-051 C
80/20
11.28211.282
3152431Z1-086 GT3
80/20
6.8556.855
934611AD1-087 C
80/20
0.6150.615
3151611KERR 4
80/20
0.460.46
3151621KERR 5
80/20
0.460.46
316336AC2-165 C
Adder
-10.934117647058825-9.294
316222AC1-221 C
80/20
0.6220.622
316349AD2-085 C
Adder
1.08823529411764720.925
3151091ELIZAR2
80/20
1.2031.203
946281AF1-292 C
80/20
0.6230.623
926071AC1-086 C
80/20
8.6598.659
927021AC1-189 C
Adder
3.55058823529411743.018
964241AG1-285 C
Adder
3.8988235294117653.314
962561AG1-105 C
Adder
3.34823529411764742.846
958161AF2-110 C
Adder
0.50352941176470590.428
938531AE1-072 C
80/20
6.9356.935
933981AD1-022 C
80/20
3.5393.539
316174AB2-169_C
80/20
0.4290.429
3156063AA2-053SOLA
80/20
0.6120.612
3151281ROARAP4
80/20
0.5320.532
942341AE2-247 C
Adder
0.4717647058823530.401
316246AF1-032 C
80/20
0.1090.109
316388AE2-253 GEN
80/20
0.7730.773
316320Y1-086 C
80/20
0.0860.086
316318V4-068 C
80/20
0.0320.032
966621AG1-532 C
80/20
0.5650.565
313506AB1-173 C OP
80/20
0.4550.455
316210AC1-098 C
80/20
0.390.39
3151601KERR 3
80/20
0.460.46
3151581KERR 1
80/20
0.1640.164
935171AD1-152 C
80/20
0.6280.628
936161AD2-022 C
Adder
3.11647058823529432.649
316375AC2-012 C
80/20
0.5120.512
315614AA2-178 C
80/20
0.6260.626
940541AE2-040 C
80/20
1.21.2
940481AE2-033 C
80/20
6.7556.755
3151411GASTONB
80/20
1.2541.254
316181AB2-040 GEN
80/20
0.5130.513
938821AE1-108 C
Adder
-4.681176470588236-3.979
316316AC1-027 C
80/20
0.1220.122
316315AB2-025 C
80/20
0.170.17
316023AB2-100 C2
80/20
0.3950.395
316317KELFORD C
80/20
0.1460.146
316129AC1-054 C
80/20
0.4920.492
3151631KERR 6
80/20
0.460.46
3150981CHESPKA
80/20
0.1650.165
3151361ROSEMG1
80/20
0.840.84
3151041BRUNSWICKG3
80/20
5.3085.308
316327AA2-057 C
80/20
0.5450.545
964791AG1-342 C
Adder
1.35764705882352941.154
3150991CHESPKB
80/20
0.2740.274
939411AE1-173 C
80/20
53.71753.717
3156021HOLLOMANSOL
80/20
0.7440.744
316011AB1-132 C OP
80/20
0.9580.958
3151371ROSEMS1
80/20
0.520.52
3137643SOCKMAN
80/20
0.290.29
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.11814.118
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.08110.081
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.7671.767
LAGNLTFEXP_LAGN->PJM
CLTF
3.483.48
NYPJM->LTFIMP_NY
CLTF
0.5550.555
LGEELTFEXP_LGEE->PJM
CLTF
0.550.55
WECLTFEXP_WEC->PJM
CLTF
0.2910.291
SIGELTFEXP_SIGE->PJM
CLTF
0.1080.108
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5692.569
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.4944.49
CPLELTFEXP_CPLE->PJM
CLTF
5.3885.388
TVALTFEXP_TVA->PJM
CLTF
2.7252.725

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.4 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3845.28
MW Contribution:8.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150831SPRUNCA
80/20
13.15813.158
3150841SPRUNCB
80/20
13.15813.158
3151081ELIZAR1
80/20
4.824.82
961941AG1-037 C
Adder
0.74470588235294120.633
941031AE2-094 C
80/20
63.15563.155
934331AD1-057 C
Adder
5.04588235294117654.289
934321AD1-056 C
Adder
9.0458823529411777.689
3151531CLOVER1
80/20
18.57418.574
3151541CLOVER2
80/20
18.39918.399
316258AE1-075 C
80/20
0.5130.513
958211AF2-115 C
Adder
3.0058823529411772.555
3150601CHESTF5
Adder
83.0647058823529570.605
941591AE2-156 C
80/20
27.03327.033
3151101ELIZAR3
80/20
4.8814.881
944591AF1-124 C
80/20
69.22169.221
944601AF1-125 C
80/20
67.91467.914
938771AE1-103 C
80/20
4.3814.381
960081AF2-299 C
Adder
2.74941176470588242.337
944011AF1-069 C
80/20
20.63520.635
963041AG1-153 C
80/20
8.7798.779
3151051BRUNSWICKS1
80/20
26.8326.83
936261AD2-033 C
Adder
17.81058823529411615.139
961791AG1-021 C
Adder
2.40470588235294122.044
940551AE2-041 C
Adder
8.4917647058823537.218
943461AF1-017 C
80/20
2.0242.024
316311AC2-079 C
80/20
8.6058.605
3156056W1-029WIND
80/20
1.1641.164
316233AE1-074 C
80/20
3.9163.916
3152421Z1-086 GT2
80/20
16.53816.538
3152441Z1-086 ST
80/20
28.79528.795
3152411Z1-086 GT1
80/20
16.54216.542
944641AF1-129 C
Adder
144.29529411764705122.651
316240AF1-291 C
Adder
3.0682352941176472.608
316036AC1-147 C
80/20
0.5540.554
316305AF2-043 C
80/20
0.5240.524
316321Z2-027 C
80/20
0.5460.546
934521AD1-076 C
Adder
18.1705882352941215.445
934511AD1-075 C
Adder
12.50823529411764710.632
316263AC1-034 C
Adder
9.488.058
959311AF2-222 C
Adder
22.66470588235294419.265
942001AE2-212 C
80/20
3.1513.151
3156116Z1-036WIND
80/20
0.9810.981
934501AD1-074 C
Adder
50.0317647058823542.527
3151031BRUNSWICKG2
80/20
12.91412.914
961671AG1-007 C
Adder
1.34941176470588231.147
934621AD1-088 C
80/20
14.01914.019
946301AF1-294 C
Adder
4.9423529411764714.201
942461AE2-259 C
Adder
12.99058823529411711.042
944631AF1-128 C
Adder
51.9752941176470644.179
3150921YORKTN3
Adder
165.5670588235294140.732
3151191GRAVEL3
80/20
3.6113.611
3150851SPRUNCC
80/20
0.2360.236
316018AA1-139 ULT2
80/20
1.6261.626
933291AC2-141 C
80/20
46.08646.086
316169AC1-164 GEN
Adder
49.0282352941176541.674
316349AD2-085 C
80/20
5.1625.162
3151091ELIZAR2
80/20
4.7364.736
946281AF1-292 C
Adder
2.2752941176470591.934
926071AC1-086 C
Adder
30.83882352941176626.213
927021AC1-189 C
Adder
12.14117647058823710.32
964241AG1-285 C
Adder
17.31176470588235414.715
962561AG1-105 C
Adder
12.25882352941176610.42
940431AE2-027 C
Adder
18.39647058823529615.637
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
5.0455.045
316185AD1-033 C
80/20
1.8511.851
944581AF1-123 C
80/20
68.97668.976
316294AC1-161 C
80/20
7.5057.505
316365AB2-100 C1
80/20
1.4231.423
3151021BRUNSWICKG1
80/20
12.91412.914
957481AF2-042 C
80/20
80.37380.373
3150651CHESTF6
Adder
26.27176470588235422.331
3150861SPRUNCD
80/20
0.2360.236
957871AF2-081 C
80/20
15.07515.075
316274AC1-208 C
Adder
13.08588235294117711.123
3151311EDGECMA
Adder
22.1658823529411818.841
316405AF2-144 C
80/20
0.4360.436
942341AE2-247 C
80/20
2.2382.238
316246AF1-032 C
80/20
0.4280.428
316388AE2-253 GEN
80/20
2.9552.955
316320Y1-086 C
80/20
0.330.33
966621AG1-532 C
Adder
2.06235294117647071.753
943471AF1-018 C
Adder
8.4917647058823537.218
3151221GRAVEL6
80/20
3.6533.653
3151201GRAVEL4
80/20
3.6573.657
3151211GRAVEL5
80/20
3.6113.611
316236AE1-162 C
80/20
0.5140.514
3152331SURRY 2
80/20
35.95635.956
316017AA1-139 ULT1
80/20
1.6261.626
313526AB2-022 C
80/20
0.5650.565
940641AE2-051 C
80/20
27.74527.745
3152431Z1-086 GT3
80/20
16.53816.538
316336AC2-165 C
Adder
14.04941176470588411.942
3150731STONECA
Adder
9.5788235294117648.142
935161AD1-151 C
Adder
22.80117647058823519.381
316083AB2-161 C
80/20
0.8230.823
958161AF2-110 C
80/20
2.0582.058
938531AE1-072 C
80/20
26.49826.498
933981AD1-022 C
Adder
12.98823529411764711.04
961611AG1-000B C
Adder
22.90588235294117719.47
316072AD1-144 C
80/20
0.4180.418
316375AC2-012 C
80/20
2.0322.032
940541AE2-040 C
80/20
4.3564.356
940481AE2-033 C
80/20
24.49624.496
939191AE1-149 C
80/20
15.94215.942
3150981CHESPKA
80/20
0.6560.656
3151041BRUNSWICKG3
80/20
12.91412.914
316313AB2-026 C
80/20
0.5590.559
964791AG1-342 C
Adder
4.884.148
957601AF2-054 C
Adder
2.53058823529411742.151
316316AC1-027 C
80/20
0.4760.476
316315AB2-025 C
80/20
0.6170.617
316023AB2-100 C2
80/20
1.4231.423
3138533PONTONDP
Adder
0.89058823529411770.757
3151161SURRY 1
80/20
35.54335.543
316381AD1-082 C
80/20
1.8751.875
3150991CHESPKB
80/20
1.0871.087
939411AE1-173 C
80/20
143.49143.49
3137643SOCKMAN
Adder
1.04352941176470580.887
316303AF2-085
80/20
6.4786.478
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.12565.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.22440.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6237.623
LAGNLTFEXP_LAGN->PJM
CLTF
13.13513.135
NYPJM->LTFIMP_NY
CLTF
3.1863.186
LGEELTFEXP_LGEE->PJM
CLTF
2.5932.593
WECLTFEXP_WEC->PJM
CLTF
1.3381.338
SIGELTFEXP_SIGE->PJM
CLTF
0.4870.487
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.9747.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
144.491144.491
CPLELTFEXP_CPLE->PJM
CLTF
16.71416.714
TVALTFEXP_TVA->PJM
CLTF
10.46710.467

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.79 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4640.88
MW Contribution:22.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
15.43176470588235513.117
943461AF1-017 C
Adder
2.0482352941176471.741
932596AC2-079 E
Adder
14.20352941176470712.073
316311AC2-079 C
Adder
8.7047058823529427.399
938532AE1-072 E
Adder
13.96470588235294111.87
3146326AYDLETT TAP
Adder
2.06705882352941161.757
917122Z2-027 E
Adder
2.04352941176470631.737
920692AA2-178 E
Adder
6.19058823529411755.262
316233AE1-074 C
50/50
3.9613.961
966622AG1-532 E
Adder
1.3870588235294121.179
3152421Z1-086 GT2
50/50
16.64616.646
3152441Z1-086 ST
50/50
28.98428.984
3152411Z1-086 GT1
50/50
16.65116.651
924814AB2-134 E
Adder
18.2270588235294115.493
944641AF1-129 C
Adder
146.62823529411764124.634
316240AF1-291 C
Adder
3.11647058823529432.649
939192AE1-149 E
Adder
10.7658823529411769.151
939312AE1-162 E
Adder
2.13058823529411741.811
942001AE2-212 C
Adder
3.19647058823529442.717
934065AD1-033 E
50/50
7.6627.662
937226AE2-253 E
Adder
8.9129411764705877.576
934501AD1-074 C
Adder
50.5435294117647142.962
924517AB2-100 E2
Adder
4.3447058823529413.693
3151031BRUNSWICKG2
50/50
12.99912.999
957482AF2-042 E
Adder
53.94941176470588645.857
934621AD1-088 C
Adder
14.11647058823529511.999
958502AF2-144 E
Adder
1.81.53
940431AE2-027 C
Adder
18.6823529411764715.88
942002AE2-212 E
Adder
2.13058823529411741.811
916191Z1-068 C
50/50
0.0670.067
941101AE2-104 C
Adder
5.1011764705882364.336
316185AD1-033 C
50/50
1.8711.871
944581AF1-123 C
50/50
69.72769.727
316294AC1-161 C
50/50
7.5867.586
316141AB2-099 E
Adder
0.37647058823529410.32
316088AB2-174 E
Adder
9.6611764705882348.212
923994AB2-040_E
Adder
9.1117647058823537.745
3151021BRUNSWICKG1
50/50
12.99912.999
957481AF2-042 C
Adder
80.9247058823529468.786
3150651CHESTF6
Adder
26.6976470588235322.693
946262AF1-291 E
Adder
2.07764705882352941.766
934576AD1-082 E
Adder
6.6517647058823535.654
943612AF1-032 E
Adder
1.40941176470588241.198
3145506HICKORY
50/50
3.3283.328
944602AF1-125 E
50/50
157.162157.162
957871AF2-081 C
Adder
15.24000000000000212.954
933292AC2-141 E
50/50
19.88619.886
940492AE2-034 E
Adder
4.6423529411764713.946
934522AD1-076 E
Adder
9.3564705882352957.953
943172AE2-346 E
Adder
0.90235294117647060.767
918492AA1-063AE OP
Adder
6.065.151
937482AD2-202 E
Adder
1.561.326
935112AD1-144 E
Adder
1.42000000000000021.207
316349AD2-085 C
Adder
5.2223529411764714.439
3151091ELIZAR2
50/50
4.7894.789
944582AF1-123 E
50/50
159.668159.668
944592AF1-124 E
50/50
160.246160.246
923832AB2-022 E
Adder
1.8882352941176471.605
938772AE1-103 E
Adder
6.115294117647065.198
916042Z1-036 E
Adder
43.2517647058823636.764
960082AF2-299 E
Adder
1.84941176470588251.572
946281AF1-292 C
Adder
2.2964705882352941.952
926071AC1-086 C
Adder
31.12823529411764826.459
963042AG1-153 E
50/50
13.25613.256
316084AB2-161 E
Adder
8.3482352941176477.096
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
933982AD1-022 E
Adder
7.1423529411764716.071
940641AE2-051 C
50/50
27.94427.944
3152431Z1-086 GT3
50/50
16.64616.646
934622AD1-088 E
Adder
6.79647058823529455.777
934612AD1-087 E
Adder
5.3305882352941174.531
316336AC2-165 C
Adder
11.2529411764705879.565
3150731STONECA
Adder
9.735294117647068.275
935161AD1-151 C
Adder
23.14823529411764719.676
932046AC2-012 E
50/50
20.00120.001
958161AF2-110 C
Adder
2.0811764705882351.769
938531AE1-072 C
Adder
26.78823529411764822.77
3145393UNCAMP
Adder
9.1811764705882367.804
933981AD1-022 C
Adder
13.12117647058823711.153
900672V4-068 E
Adder
0.53294117647058830.453
943462AF1-017 E
Adder
3.34117647058823542.84
942341AE2-247 C
Adder
2.2635294117647061.924
958162AF2-110 E
Adder
3.31058823529411762.814
919153AA1-139 E2
Adder
6.2317647058823535.297
934502AD1-074 E
Adder
25.72941176470588321.87
934512AD1-075 E
Adder
6.4317647058823535.467
918512AA1-065 E OP
Adder
8.2458823529411777.009
924516AB2-100 E1
Adder
4.3447058823529413.693
940642AE2-051 E
50/50
18.62918.629
966621AG1-532 C
Adder
2.0811764705882351.769
961611AG1-000B C
Adder
23.2270588235294119.743
316375AC2-012 C
50/50
2.0552.055
940541AE2-040 C
50/50
4.3984.398
940481AE2-033 C
50/50
24.72924.729
940482AE2-033 E
50/50
16.67116.671
923263AB1-132 E OP
Adder
9.0588235294117647.7
3150921YORKTN3
Adder
168.0623529411765142.853
3145256KINGFORK
Adder
1.52941176470588251.3
925522AC1-027 E
50/50
1.8591.859
941102AE2-104 E
Adder
8.1105882352941186.894
957872AF2-081 E
Adder
6.53176470588235255.552
933291AC2-141 C
50/50
46.58646.586
926755AC1-161 E
50/50
19.88619.886
938552AE1-074 E
50/50
1.9951.995
938562AE1-075 E
Adder
1.56235294117647071.328
942342AE2-247 E
Adder
3.12588235294117662.657
919152AA1-139 E1
Adder
6.2317647058823535.297
934521AD1-076 C
Adder
18.35647058823529315.603
934511AD1-075 C
Adder
12.6352941176470610.74
920042AA2-088 E OP
Adder
15.88941176470588313.506
3145723EMPORIA
Adder
0.640.544
923573AB1-173 E OP
Adder
4.8588235294117644.13
919692AA2-053 E OP
Adder
6.2482352941176475.311
3150831SPRUNCA
Adder
13.36352941176470611.359
3150841SPRUNCB
Adder
13.36352941176470611.359
926662AC1-147 E
Adder
2.02235294117647071.719
3151081ELIZAR1
50/50
4.8744.874
916192Z1-068 E
50/50
2.8712.871
957492AF2-043 E
Adder
2.16705882352941171.842
923852AB2-025 E
50/50
1.7791.779
939412AE1-173 E
50/50
96.42796.427
961942AG1-037 E
Adder
0.50117647058823530.426
961941AG1-037 C
Adder
0.7517647058823530.639
941031AE2-094 C
50/50
63.56663.566
941032AE2-094 E
50/50
28.4728.47
923862AB2-026 E
Adder
1.8317647058823531.557
925332AB2-190 E
Adder
11.5352941176470599.805
927226AC1-216 E
Adder
11.1270588235294129.458
936666AD2-085 E
Adder
8.5211764705882367.243
941591AE2-156 C
50/50
27.33727.337
3151101ELIZAR3
50/50
4.9364.936
944591AF1-124 C
50/50
69.97569.975
944601AF1-125 C
50/50
68.65368.653
938771AE1-103 C
Adder
4.4282352941176473.764
3145413WATKINS
Adder
1.04117647058823540.885
960081AF2-299 C
Adder
2.7741176470588242.358
926072AC1-086 E
Adder
14.16705882352941312.042
944011AF1-069 C
50/50
20.76920.769
963041AG1-153 C
50/50
8.8378.837
3151051BRUNSWICKS1
50/50
27.00627.006
316316AC1-027 C
50/50
0.4810.481
316315AB2-025 C
50/50
0.6230.623
946282AF1-292 E
Adder
1.53058823529411761.301
944012AF1-069 E
50/50
8.0688.068
939191AE1-149 C
Adder
16.1494117647058813.727
3143316POE
50/50
2.082.08
901082W1-029 E
Adder
48.43294117647058541.168
3151041BRUNSWICKG3
50/50
12.99912.999
940432AE2-027 E
Adder
12.45529411764705910.587
934012AD1-025 E
Adder
14.40588235294117712.245
913392Y1-086 E
Adder
3.3447058823529412.843
939411AE1-173 C
50/50
144.64144.64
3137643SOCKMAN
Adder
1.05294117647058830.895
316303AF2-085
50/50
6.5316.531
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.46965.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.49440.494
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6697.669
LAGNLTFEXP_LAGN->PJM
CLTF
13.22813.228
NYPJM->LTFIMP_NY
CLTF
3.2313.231
LGEELTFEXP_LGEE->PJM
CLTF
2.6092.609
WECLTFEXP_WEC->PJM
CLTF
1.3461.346
G-007PJM->LTFIMP_G-007
CMTX_NF
7.1157.115
SIGELTFEXP_SIGE->PJM
CLTF
0.490.49
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.0368.036
CBM South 2LTFEXP_CBM-S2->PJM
CBM
145.599145.599
CPLELTFEXP_CPLE->PJM
CLTF
16.84316.843
TVALTFEXP_TVA->PJM
CLTF
10.54210.542
O66PJM->LTFIMP_O-066
CMTX_NF
45.24145.241

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.63 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3595.09
MW Contribution:5.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.37294117647058830.317
941031AE2-094 C
80/20
37.11337.113
934331AD1-057 C
Adder
2.6258823529411772.232
934321AD1-056 C
Adder
4.7070588235294134.001
3151531CLOVER1
80/20
10.82910.829
3151541CLOVER2
80/20
10.72710.727
316258AE1-075 C
80/20
0.320.32
958211AF2-115 C
80/20
1.7961.796
3151791S ANNAG2
80/20
3.2623.262
3151771S ANNAG1
80/20
3.2623.262
3151781S ANNAS1
80/20
1.6761.676
3151761LOISA E
80/20
6.8276.827
208900BRIS G1
80/20
-2.405-2.405
941591AE2-156 C
Adder
12.43294117647058910.568
944591AF1-124 C
Adder
32.1611764705882427.337
944601AF1-125 C
Adder
31.55411764705882826.821
938771AE1-103 C
Adder
2.10235294117647081.787
960081AF2-299 C
80/20
1.4551.455
944011AF1-069 C
80/20
12.12612.126
963041AG1-153 C
80/20
5.1375.137
3151051BRUNSWICKS1
80/20
15.69915.699
936261AD2-033 C
80/20
10.37510.375
961791AG1-021 C
80/20
1.4371.437
316045AC1-158 C2
80/20
18.51718.517
316170AC1-121 C
80/20
2.952.95
943461AF1-017 C
Adder
0.94000000000000010.799
316311AC2-079 C
Adder
3.99647058823529383.397
316233AE1-074 C
80/20
2.0672.067
3152421Z1-086 GT2
80/20
9.699.69
3152441Z1-086 ST
80/20
16.87216.872
3152411Z1-086 GT1
80/20
9.6939.693
934521AD1-076 C
Adder
8.8564705882352937.528
934511AD1-075 C
Adder
6.0964705882352945.182
316087AB2-174 C
80/20
0.9080.908
316263AC1-034 C
Adder
4.9470588235294124.205
937481AD2-202 C
80/20
0.3090.309
959311AF2-222 C
80/20
13.30313.303
942001AE2-212 C
Adder
1.40235294117647061.192
934501AD1-074 C
Adder
24.38588235294117720.728
3151031BRUNSWICKG2
80/20
7.5577.557
961671AG1-007 C
Adder
0.69647058823529410.592
934621AD1-088 C
80/20
8.2538.253
946301AF1-294 C
80/20
2.9542.954
942461AE2-259 C
80/20
7.9867.986
316192AB2-158 C
80/20
4.3254.325
208901BRIS G2
80/20
-2.846-2.846
933291AC2-141 C
Adder
21.0423529411764717.886
313527AB2-043 C
80/20
0.4090.409
3152251N ANNA1
80/20
103.92103.92
316349AD2-085 C
Adder
2.3964705882352942.037
946281AF1-292 C
80/20
1.2041.204
926071AC1-086 C
Adder
15.98823529411764713.59
927021AC1-189 C
Adder
6.225.287
964241AG1-285 C
80/20
9.9749.974
316034AC1-036 C
80/20
0.1860.186
962561AG1-105 C
Adder
6.9729411764705885.927
3144293JTRSVLE
80/20
0.3290.329
316044AC1-158 C1
80/20
18.51718.517
941101AE2-104 C
Adder
2.35411764705882342.001
944581AF1-123 C
Adder
32.0470588235294127.24
316365AB2-100 C1
80/20
0.7450.745
3151021BRUNSWICKG1
80/20
7.5577.557
957481AF2-042 C
80/20
47.06247.062
3151801S ANNAS2
80/20
1.6761.676
957871AF2-081 C
Adder
7.0094117647058835.958
316274AC1-208 C
Adder
6.785.763
3151311EDGECMA
Adder
11.569.826
316405AF2-144 C
80/20
0.2720.272
942341AE2-247 C
Adder
1.03882352941176470.883
966621AG1-532 C
80/20
1.0911.091
935171AD1-152 C
80/20
1.0991.099
3152261N ANNA2
80/20
103.963103.963
934861AD1-115 C
80/20
3.3063.306
940641AE2-051 C
80/20
15.75815.758
3152431Z1-086 GT3
80/20
9.699.69
934611AD1-087 C
80/20
1.0661.066
316237AB2-079 C O1
80/20
0.2590.259
316336AC2-165 C
80/20
8.8748.874
958161AF2-110 C
Adder
0.96117647058823530.817
938531AE1-072 C
Adder
12.33529411764705810.485
933981AD1-022 C
Adder
6.3599999999999995.406
316238AB2-078 C O1
80/20
0.2590.259
940541AE2-040 C
80/20
2.2982.298
940481AE2-033 C
80/20
12.91312.913
3147043LAWRENC
80/20
0.240.24
966001AG1-469 C
80/20
2.3822.382
316315AB2-025 C
80/20
0.3250.325
316023AB2-100 C2
80/20
0.7450.745
316131AB2-060 C
80/20
1.1781.178
3138533PONTONDP
80/20
0.5320.532
3151721LOISA A
80/20
3.3313.331
316254AC1-120 C
80/20
8.5918.591
316257AC1-043 C
80/20
6.6126.612
939191AE1-149 C
Adder
7.2929411764705886.199
3151041BRUNSWICKG3
80/20
7.5577.557
316239AB2-077 C O1
80/20
0.2590.259
316313AB2-026 C
80/20
0.3480.348
964791AG1-342 C
Adder
2.77294117647058872.357
3151751LOISA D
80/20
3.3493.349
3151731LOISA B
80/20
3.3493.349
316164AC1-076_C
80/20
1.0891.089
939411AE1-173 C
80/20
78.11378.113
3137643SOCKMAN
Adder
0.54588235294117650.464
3151741LOISA C
80/20
3.3493.349
316303AF2-085
80/20
3.8763.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.20919.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.12316.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6672.667
LAGNLTFEXP_LAGN->PJM
CLTF
5.7055.705
NYPJM->LTFIMP_NY
CLTF
2.292.29
LGEELTFEXP_LGEE->PJM
CLTF
0.8350.835
WECLTFEXP_WEC->PJM
CLTF
0.4130.413
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2194.219
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.82173.821
CPLELTFEXP_CPLE->PJM
CLTF
8.8538.853
TVALTFEXP_TVA->PJM
CLTF
4.5224.522

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.86 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3570.05
MW Contribution:5.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150831SPRUNCA
Adder
6.1623529411764715.238
3150841SPRUNCB
Adder
6.1623529411764715.238
961941AG1-037 C
Adder
0.39411764705882360.335
941031AE2-094 C
80/20
38.91138.911
934331AD1-057 C
Adder
2.7741176470588242.358
934321AD1-056 C
Adder
4.9729411764705894.227
3151531CLOVER1
80/20
11.34911.349
3151541CLOVER2
80/20
11.24311.243
316258AE1-075 C
80/20
0.3330.333
958211AF2-115 C
80/20
1.8751.875
3151791S ANNAG2
80/20
3.0413.041
3151771S ANNAG1
80/20
3.0413.041
3151781S ANNAS1
80/20
1.5631.563
3151761LOISA E
80/20
6.316.31
208900BRIS G1
80/20
-2.414-2.414
941591AE2-156 C
Adder
13.23882352941176611.253
944591AF1-124 C
Adder
34.2229.087
944601AF1-125 C
Adder
33.5741176470588328.538
938771AE1-103 C
Adder
2.2329411764705881.898
960081AF2-299 C
80/20
1.5351.535
944011AF1-069 C
80/20
12.71412.714
963041AG1-153 C
80/20
5.3875.387
3151051BRUNSWICKS1
80/20
16.46316.463
936261AD2-033 C
80/20
10.85610.856
961791AG1-021 C
80/20
1.51.5
943461AF1-017 C
Adder
1.00.85
316311AC2-079 C
Adder
4.2541176470588233.616
316233AE1-074 C
80/20
2.1822.182
3152421Z1-086 GT2
80/20
10.16110.161
3152441Z1-086 ST
80/20
17.69217.692
3152411Z1-086 GT1
80/20
10.16410.164
944641AF1-129 C
Adder
63.6988235294117654.144
316240AF1-291 C
Adder
1.37882352941176461.172
934521AD1-076 C
Adder
9.3952941176470587.986
934511AD1-075 C
Adder
6.46705882352941155.497
316087AB2-174 C
80/20
0.9580.958
316263AC1-034 C
Adder
5.2270588235294114.443
937481AD2-202 C
80/20
0.3240.324
959311AF2-222 C
80/20
13.90913.909
942001AE2-212 C
Adder
1.49882352941176471.274
934501AD1-074 C
Adder
25.86823529411764621.988
3151031BRUNSWICKG2
80/20
7.9247.924
961671AG1-007 C
Adder
0.73647058823529410.626
934621AD1-088 C
80/20
8.6418.641
946301AF1-294 C
80/20
3.0833.083
942461AE2-259 C
Adder
8.3117647058823547.065
316192AB2-158 C
80/20
4.2764.276
208901BRIS G2
80/20
-2.857-2.857
933291AC2-141 C
Adder
22.41294117647058619.051
313527AB2-043 C
80/20
0.4290.429
3152251N ANNA1
80/20
106.954106.954
316349AD2-085 C
Adder
2.5505882352941182.168
946281AF1-292 C
80/20
1.2711.271
926071AC1-086 C
Adder
16.8929411764705914.359
927021AC1-189 C
Adder
6.5788235294117645.592
964241AG1-285 C
80/20
10.44910.449
316034AC1-036 C
80/20
0.1950.195
962561AG1-105 C
Adder
7.3152941176470596.218
3144293JTRSVLE
80/20
0.3440.344
940431AE2-027 C
Adder
8.3129411764705887.066
941101AE2-104 C
Adder
2.50470588235294132.129
944581AF1-123 C
Adder
34.0988235294117728.984
316365AB2-100 C1
80/20
0.7870.787
3151021BRUNSWICKG1
80/20
7.9247.924
957481AF2-042 C
80/20
49.31549.315
3151801S ANNAS2
80/20
1.5631.563
3150651CHESTF6
Adder
11.5976470588235319.858
957871AF2-081 C
Adder
7.4588235294117656.34
316274AC1-208 C
Adder
7.1635294117647066.089
3151311EDGECMA
Adder
12.21411764705882410.382
316405AF2-144 C
80/20
0.2830.283
942341AE2-247 C
Adder
1.10588235294117650.94
966621AG1-532 C
80/20
1.1511.151
313506AB1-173 C OP
80/20
0.9150.915
935171AD1-152 C
80/20
1.1531.153
3152261N ANNA2
80/20
106.999106.999
940641AE2-051 C
80/20
16.55416.554
3152431Z1-086 GT3
80/20
10.16110.161
934611AD1-087 C
80/20
1.1171.117
316237AB2-079 C O1
80/20
0.2720.272
316336AC2-165 C
80/20
9.2269.226
958161AF2-110 C
Adder
1.02235294117647070.869
938531AE1-072 C
Adder
13.12352941176470511.155
933981AD1-022 C
Adder
6.7447058823529415.733
316238AB2-078 C O1
80/20
0.2720.272
961611AG1-000B C
Adder
10.3129411764705888.766
940541AE2-040 C
80/20
2.4262.426
940481AE2-033 C
80/20
13.63113.631
316181AB2-040 GEN
80/20
1.0311.031
3147043LAWRENC
80/20
0.2530.253
966001AG1-469 C
80/20
1.9821.982
316315AB2-025 C
80/20
0.3440.344
316023AB2-100 C2
80/20
0.7870.787
316131AB2-060 C
80/20
1.2351.235
3138533PONTONDP
80/20
0.5550.555
3151721LOISA A
80/20
3.0793.079
939191AE1-149 C
Adder
7.7752941176470596.609
3151041BRUNSWICKG3
80/20
7.9247.924
316239AB2-077 C O1
80/20
0.2720.272
316313AB2-026 C
80/20
0.3630.363
964791AG1-342 C
Adder
2.9105882352941182.474
3151751LOISA D
80/20
3.0953.095
3151731LOISA B
80/20
3.0953.095
939411AE1-173 C
80/20
82.26382.263
3137643SOCKMAN
Adder
0.57647058823529410.49
3151741LOISA C
80/20
3.0953.095
316303AF2-085
80/20
4.064.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.24822.248
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.65817.658
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.9882.988
LAGNLTFEXP_LAGN->PJM
CLTF
6.1746.174
NYPJM->LTFIMP_NY
CLTF
2.2912.291
LGEELTFEXP_LGEE->PJM
CLTF
0.9480.948
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
SIGELTFEXP_SIGE->PJM
CLTF
0.1860.186
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4574.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
78.26878.268
CPLELTFEXP_CPLE->PJM
CLTF
9.3529.352
TVALTFEXP_TVA->PJM
CLTF
4.8954.895

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.14 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4339.53
MW Contribution:13.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934576AD1-082 E
Adder
3.19882352941176462.719
943461AF1-017 C
Adder
0.99294117647058820.844
932596AC2-079 E
Adder
6.8929411764705895.859
316311AC2-079 C
Adder
4.2247058823529413.591
938532AE1-072 E
Adder
6.7941176470588245.775
3146326AYDLETT TAP
Adder
1.00588235294117640.855
316084AB2-161 E
Adder
4.0141176470588233.412
3145946PLYMOUTH TP
Adder
0.245882352941176470.209
933982AD1-022 E
Adder
3.6447058823529413.098
940641AE2-051 C
50/50
16.47216.472
927146AC1-208 E
Adder
3.1564705882352942.683
934622AD1-088 E
Adder
4.1364705882352943.516
934612AD1-087 E
Adder
3.2152941176470592.733
316336AC2-165 C
Adder
9.177647058823537.801
927255AC1-221 E
Adder
2.9588235294117652.515
932046AC2-012 E
Adder
9.6164705882352938.174
958161AF2-110 C
Adder
1.0152941176470590.863
938531AE1-072 C
Adder
13.03294117647058811.078
3145393UNCAMP
Adder
4.622352941176473.929
933981AD1-022 C
Adder
6.6952941176470595.691
900672V4-068 E
Adder
0.276470588235294130.235
924302AB2-077 E O1
Adder
1.10588235294117650.94
940541AE2-040 C
Adder
2.4117647058823532.05
940481AE2-033 C
Adder
13.54823529411764811.516
940482AE2-033 E
Adder
9.1341176470588247.764
923263AB1-132 E OP
Adder
4.8811764705882354.149
924312AB2-078 E O1
Adder
1.10588235294117650.94
925612AC1-036 E
Adder
0.7117647058823530.605
926274AC1-105 E
Adder
2.1788235294117651.852
966001AG1-469 C
50/50
2.0062.006
926740AC1-158 E2
50/50
51.18251.182
3145256KINGFORK
Adder
0.72352941176470590.615
925522AC1-027 E
Adder
0.89764705882352950.763
941102AE2-104 E
Adder
3.9541176470588243.361
957872AF2-081 E
Adder
3.17411764705882372.698
933291AC2-141 C
Adder
22.2618.921
926755AC1-161 E
Adder
9.502352941176478.077
938552AE1-074 E
Adder
1.09294117647058830.929
932632AC2-084 E
Adder
2.53411764705882362.154
926214AC1-099 E
Adder
0.94705882352941180.805
924162AB2-060 E OP
Adder
3.54470588235294143.013
964242AG1-285 E
Adder
6.9188235294117655.881
938562AE1-075 E
Adder
1.00.85
964792AG1-342 E
Adder
1.92588235294117661.637
932763AC2-100 E
Adder
2.00588235294117641.705
3152251N ANNA1
50/50
106.841106.841
935112AD1-144 E
Adder
0.67176470588235290.571
316349AD2-085 C
Adder
2.53294117647058852.153
944582AF1-123 E
Adder
77.5517647058823565.919
944592AF1-124 E
Adder
77.8317647058823566.157
923832AB2-022 E
Adder
0.92235294117647060.784
938772AE1-103 E
Adder
3.0611764705882352.602
916042Z1-036 E
Adder
21.48117647058823518.259
960082AF2-299 E
Adder
1.01647058823529420.864
946281AF1-292 C
Adder
1.26235294117647071.073
926071AC1-086 C
Adder
16.77411764705882314.258
963042AG1-153 E
Adder
8.0388235294117656.833
927021AC1-189 C
Adder
6.5247058823529425.546
924152AB2-059 E OP
Adder
4.122352941176473.504
964241AG1-285 C
Adder
10.3776470588235298.821
962561AG1-105 C
Adder
7.2635294117647076.174
958212AF2-115 E
Adder
1.58588235294117651.348
925022AB2-158 E
50/50
11.37311.373
316044AC1-158 C1
50/50
19.56819.568
3150831SPRUNCA
Adder
6.117647058823535.2
3150841SPRUNCB
Adder
6.117647058823535.2
926662AC1-147 E
Adder
0.97176470588235290.826
916192Z1-068 E
Adder
1.38588235294117631.178
957492AF2-043 E
Adder
1.05294117647058830.895
923852AB2-025 E
Adder
0.97529411764705880.829
939412AE1-173 E
Adder
54.5505882352941246.368
961942AG1-037 E
Adder
0.26117647058823530.222
961941AG1-037 C
Adder
0.391764705882352960.333
941031AE2-094 C
50/50
38.72138.721
941032AE2-094 E
50/50
17.34217.342
934331AD1-057 C
Adder
2.75294117647058822.34
934322AD1-056 E
Adder
2.6764705882352942.275
934332AD1-057 E
Adder
1.43411764705882371.219
934321AD1-056 C
Adder
4.9352941176470594.195
927022AC1-189 E
Adder
3.25058823529411762.763
925595AC1-034 E
Adder
3.91058823529411773.324
936262AD2-033 E
Adder
7.1882352941176476.11
923862AB2-026 E
Adder
1.17294117647058820.997
958211AF2-115 C
Adder
1.86235294117647051.583
3151791S ANNAG2
50/50
3.0513.051
3151771S ANNAG1
50/50
3.0513.051
3151781S ANNAS1
50/50
1.5681.568
3151761LOISA E
50/50
6.3326.332
208900BRIS G1
50/50
-2.489-2.489
936666AD2-085 E
Adder
4.1329411764705883.513
941591AE2-156 C
Adder
13.14823529411764711.176
944591AF1-124 C
Adder
33.9870588235294128.889
944601AF1-125 C
Adder
33.3447058823529428.343
938771AE1-103 C
Adder
2.21764705882352951.885
3145413WATKINS
Adder
0.52941176470588240.45
960081AF2-299 C
Adder
1.52470588235294141.296
926072AC1-086 E
Adder
7.6341176470588236.489
944011AF1-069 C
50/50
12.65212.652
963041AG1-153 C
Adder
5.3588235294117644.555
936261AD2-033 C
Adder
10.782352941176479.165
962562AG1-105 E
Adder
4.842352941176474.116
961791AG1-021 C
Adder
1.48941176470588241.266
924032AB2-045 E
Adder
1.08588235294117650.923
316045AC1-158 C2
50/50
19.56819.568
946282AF1-292 E
Adder
0.84117647058823530.715
944012AF1-069 E
50/50
4.9154.915
917512Z2-088 E OP1
Adder
3.8047058823529413.234
3138533PONTONDP
Adder
0.55176470588235290.469
3151721LOISA A
50/50
3.093.09
939191AE1-149 C
Adder
7.7200000000000016.562
3143316POE
Adder
1.04235294117647070.886
901082W1-029 E
Adder
23.76705882352941420.202
926206AC1-098 E
Adder
2.86705882352941142.437
964791AG1-342 C
Adder
2.88941176470588262.456
942462AE2-259 E
Adder
5.5047058823529414.679
3151751LOISA D
50/50
3.1063.106
3151731LOISA B
50/50
3.1063.106
942002AE2-212 E
Adder
0.99176470588235290.843
941101AE2-104 C
Adder
2.48705882352941152.114
944581AF1-123 C
Adder
33.8670588235294128.787
316141AB2-099 E
Adder
0.195294117647058840.166
316088AB2-174 E
Adder
5.2858823529411774.493
923994AB2-040_E
Adder
4.9741176470588234.228
961672AG1-007 E
Adder
0.414117647058823530.352
957481AF2-042 C
Adder
49.0341176470588341.679
924322AB2-079 E O1
Adder
1.10588235294117650.94
946302AF1-294 E
Adder
2.59294117647058852.204
943902AF1-058 E
Adder
1.04352941176470580.887
3151801S ANNAS2
50/50
1.5681.568
917122Z2-027 E
Adder
1.00.85
920692AA2-178 E
Adder
3.1141176470588232.647
316233AE1-074 C
Adder
2.17058823529411751.845
966622AG1-532 E
Adder
0.76235294117647070.648
922923AB1-081 E OP
Adder
2.9105882352941182.474
3147133PAMPLIN
Adder
0.82352941176470580.7
927264AC1-222 E
Adder
3.20470588235294152.724
966002AG1-469 E
50/50
1.0031.003
926739AC1-158 E1
50/50
51.18251.182
942342AE2-247 E
Adder
1.5164705882352941.289
919152AA1-139 E1
Adder
3.02941176470588272.575
934521AD1-076 C
Adder
9.3258823529411777.927
934511AD1-075 C
Adder
6.425.457
920042AA2-088 E OP
Adder
8.226.987
3145723EMPORIA
Adder
0.350588235294117640.298
923573AB1-173 E OP
Adder
2.6529411764705882.255
919692AA2-053 E OP
Adder
3.36117647058823542.857
925785AC1-054 E
Adder
2.79764705882352962.378
316263AC1-034 C
Adder
5.1835294117647064.406
959311AF2-222 C
Adder
13.8152941176470611.743
939192AE1-149 E
Adder
5.1470588235294124.375
939312AE1-162 E
Adder
0.97647058823529410.83
942001AE2-212 C
Adder
1.48705882352941181.264
934065AD1-033 E
Adder
3.70941176470588243.153
937226AE2-253 E
Adder
4.3282352941176473.679
934501AD1-074 C
Adder
25.6821.828
924517AB2-100 E2
Adder
2.36470588235294082.01
961671AG1-007 C
Adder
0.73058823529411760.621
957482AF2-042 E
Adder
32.6894117647058927.786
934621AD1-088 C
Adder
8.5905882352941177.302
935172AD1-152 E
Adder
4.7270588235294114.018
958502AF2-144 E
Adder
1.15294117647058810.98
946301AF1-294 C
Adder
3.06235294117647072.603
942461AE2-259 C
Adder
8.257647058823537.019
316192AB2-158 C
50/50
4.2784.278
208901BRIS G2
50/50
-2.946-2.946
913392Y1-086 E
Adder
1.63411764705882371.389
943462AF1-017 E
Adder
1.621.377
942341AE2-247 C
Adder
1.09764705882352940.933
958162AF2-110 E
Adder
1.61411764705882371.372
919153AA1-139 E2
Adder
3.02941176470588272.575
934502AD1-074 E
Adder
13.07176470588235311.111
934512AD1-075 E
Adder
3.26823529411764732.778
918512AA1-065 E OP
Adder
4.2588235294117653.62
924516AB2-100 E1
Adder
2.36470588235294082.01
940642AE2-051 E
50/50
10.98110.981
966621AG1-532 C
Adder
1.1435294117647060.972
918532AA1-067 E
Adder
0.55176470588235290.469
924022AB2-043 E O1
Adder
4.2929411764705883.649
3147223TWITTYS
Adder
0.78941176470588240.671
959312AF2-222 E
Adder
9.2564705882352957.868
3152261N ANNA2
50/50
106.886106.886
943612AF1-032 E
Adder
0.68470588235294120.582
3145506HICKORY
Adder
1.61411764705882371.372
944602AF1-125 E
Adder
76.3341176470588364.884
957871AF2-081 C
Adder
7.4070588235294126.296
933292AC2-141 E
Adder
9.502352941176478.077
940492AE2-034 E
Adder
2.3364705882352941.986
934522AD1-076 E
Adder
4.7541176470588244.041
943172AE2-346 E
Adder
0.46941176470588240.399
918492AA1-063AE OP
Adder
3.22705882352941182.743
925122AB2-169 E
Adder
4.4105882352941183.749
917332KELFORD E
Adder
1.281.088
316274AC1-208 C
Adder
7.1094117647058826.043
917342Z2-044 E
Adder
0.46823529411764710.398
3151311EDGECMA
Adder
12.11411764705882510.297
937482AD2-202 E
Adder
0.94117647058823540.8
961792AG1-021 E
Adder
1.26941176470588221.079
939411AE1-173 C
Adder
81.8247058823529469.551
3137643SOCKMAN
Adder
0.57294117647058830.487
919710AA2-057 E
Adder
3.1117647058823532.645
933502AC2-165 E
Adder
6.9070588235294135.871
3151741LOISA C
50/50
3.1063.106
316303AF2-085
50/50
4.0434.043
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.05120.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.83616.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7842.784
LAGNLTFEXP_LAGN->PJM
CLTF
5.9595.959
NYPJM->LTFIMP_NY
CLTF
2.3732.373
LGEELTFEXP_LGEE->PJM
CLTF
0.8720.872
WECLTFEXP_WEC->PJM
CLTF
0.4310.431
G-007PJM->LTFIMP_G-007
CMTX_NF
5.0575.057
SIGELTFEXP_SIGE->PJM
CLTF
0.1730.173
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4084.408
CBM South 2LTFEXP_CBM-S2->PJM
CBM
77.11777.117
CPLELTFEXP_CPLE->PJM
CLTF
9.2519.251
TVALTFEXP_TVA->PJM
CLTF
4.7224.722
O66PJM->LTFIMP_O-066
CMTX_NF
32.20632.206

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.71 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3758.56
MW Contribution:5.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150831SPRUNCA
Adder
7.7905882352941186.622
3150841SPRUNCB
Adder
7.7905882352941186.622
3151081ELIZAR1
80/20
2.8512.851
961941AG1-037 C
Adder
0.454117647058823570.386
941031AE2-094 C
80/20
41.10641.106
934331AD1-057 C
Adder
3.11764705882352942.65
934321AD1-056 C
Adder
5.5882352941176484.75
3151531CLOVER1
80/20
12.09912.099
3151541CLOVER2
80/20
11.98511.985
316258AE1-075 C
80/20
0.3530.353
958211AF2-115 C
Adder
2.0152941176470591.713
3151791S ANNAG2
80/20
2.372.37
3151771S ANNAG1
80/20
2.372.37
3151781S ANNAS1
80/20
1.2181.218
3151761LOISA E
80/20
4.8664.866
208900BRIS G1
80/20
-2.56-2.56
3150601CHESTF5
Adder
45.29058823529411638.497
941591AE2-156 C
80/20
15.98415.984
3151101ELIZAR3
80/20
2.8872.887
944591AF1-124 C
80/20
41.04941.049
944601AF1-125 C
80/20
40.27340.273
938771AE1-103 C
80/20
2.6332.633
960081AF2-299 C
80/20
1.7191.719
944011AF1-069 C
80/20
13.43113.431
963041AG1-153 C
80/20
5.7035.703
3151051BRUNSWICKS1
80/20
17.42917.429
936261AD2-033 C
Adder
11.7211764705882359.963
961791AG1-021 C
Adder
1.61176470588235321.37
943461AF1-017 C
80/20
1.2041.204
316311AC2-079 C
80/20
5.125.12
3156056W1-029WIND
80/20
0.6930.693
316233AE1-074 C
80/20
2.4792.479
3152421Z1-086 GT2
80/20
10.7510.75
3152441Z1-086 ST
80/20
18.71718.717
3152411Z1-086 GT1
80/20
10.75310.753
944641AF1-129 C
Adder
83.2882352941176570.795
316240AF1-291 C
Adder
1.78117647058823541.514
316036AC1-147 C
80/20
0.3280.328
316305AF2-043 C
80/20
0.3110.311
316321Z2-027 C
80/20
0.3250.325
934521AD1-076 C
Adder
10.9623529411764719.318
934511AD1-075 C
Adder
7.54588235294117656.414
316087AB2-174 C
80/20
1.0751.075
316263AC1-034 C
Adder
5.8505882352941184.973
937481AD2-202 C
80/20
0.3460.346
959311AF2-222 C
Adder
14.9976470588235312.748
942001AE2-212 C
Adder
1.8635294117647061.584
934501AD1-074 C
Adder
30.18352941176470625.656
3151031BRUNSWICKG2
80/20
8.3898.389
961671AG1-007 C
Adder
0.82941176470588230.705
934621AD1-088 C
80/20
9.29.2
946301AF1-294 C
Adder
3.3141176470588242.817
942461AE2-259 C
Adder
8.8929411764705887.559
316192AB2-158 C
80/20
3.5593.559
208901BRIS G2
80/20
-3.03-3.03
944631AF1-128 C
Adder
28.33882352941176624.088
3150921YORKTN3
Adder
92.4352941176470578.57
3150851SPRUNCC
80/20
0.140.14
316018AA1-139 ULT2
80/20
0.9650.965
933291AC2-141 C
80/20
27.11427.114
3152251N ANNA1
80/20
92.7292.72
316349AD2-085 C
80/20
3.0713.071
3151091ELIZAR2
80/20
2.8012.801
946281AF1-292 C
80/20
1.4231.423
926071AC1-086 C
Adder
19.07647058823529616.215
927021AC1-189 C
Adder
7.4435294117647066.327
964241AG1-285 C
Adder
11.3035294117647079.608
962561AG1-105 C
Adder
7.9117647058823526.725
940431AE2-027 C
Adder
10.6976470588235299.093
916191Z1-068 C
80/20
0.0390.039
941101AE2-104 C
80/20
3.0013.001
316185AD1-033 C
80/20
1.0971.097
944581AF1-123 C
80/20
40.90340.903
316294AC1-161 C
80/20
4.4154.415
316365AB2-100 C1
80/20
0.8850.885
3151021BRUNSWICKG1
80/20
8.3898.389
957481AF2-042 C
80/20
52.44752.447
3151801S ANNAS2
80/20
1.2181.218
3150651CHESTF6
Adder
15.16470588235294212.89
3150861SPRUNCD
80/20
0.140.14
957871AF2-081 C
80/20
8.9458.945
316274AC1-208 C
Adder
8.077647058823536.866
3151311EDGECMA
Adder
13.67647058823529511.625
316405AF2-144 C
80/20
0.30.3
942341AE2-247 C
80/20
1.3311.331
316246AF1-032 C
80/20
0.2540.254
316388AE2-253 GEN
80/20
1.7531.753
316320Y1-086 C
80/20
0.1960.196
966621AG1-532 C
80/20
1.2891.289
313506AB1-173 C OP
80/20
1.0281.028
935171AD1-152 C
80/20
1.2331.233
3152261N ANNA2
80/20
92.75992.759
316017AA1-139 ULT1
80/20
0.9650.965
313526AB2-022 C
80/20
0.3360.336
940641AE2-051 C
80/20
17.817.8
3152431Z1-086 GT3
80/20
10.7510.75
934611AD1-087 C
80/20
1.1911.191
316336AC2-165 C
80/20
9.7879.787
3150731STONECA
Adder
5.4352941176470594.62
935161AD1-151 C
Adder
13.03882352941176511.083
316083AB2-161 C
80/20
0.4890.489
958161AF2-110 C
80/20
1.2251.225
938531AE1-072 C
80/20
15.7315.73
933981AD1-022 C
Adder
7.84941176470588256.672
961611AG1-000B C
Adder
13.19882352941176511.219
316072AD1-144 C
80/20
0.2460.246
316375AC2-012 C
80/20
1.2021.202
940541AE2-040 C
80/20
2.7232.723
940481AE2-033 C
80/20
15.30215.302
316181AB2-040 GEN
80/20
1.1581.158
3147043LAWRENC
80/20
0.2810.281
966001AG1-469 C
Adder
1.43764705882352951.222
939191AE1-149 C
80/20
9.4869.486
3150981CHESPKA
80/20
0.3880.388
3151041BRUNSWICKG3
80/20
8.3898.389
316313AB2-026 C
80/20
0.3850.385
964791AG1-342 C
Adder
3.14588235294117662.674
3151751LOISA D
80/20
2.3872.387
3151731LOISA B
80/20
2.3872.387
316316AC1-027 C
80/20
0.2820.282
316315AB2-025 C
80/20
0.3860.386
316023AB2-100 C2
80/20
0.8850.885
3138533PONTONDP
Adder
0.59764705882352940.508
3151721LOISA A
80/20
2.3742.374
316381AD1-082 C
80/20
1.1161.116
3150991CHESPKB
80/20
0.6430.643
939411AE1-173 C
80/20
90.4790.47
3137643SOCKMAN
Adder
0.64823529411764710.551
3151741LOISA C
80/20
2.3872.387
316303AF2-085
80/20
4.3034.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.18225.182
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.8619.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.3753.375
LAGNLTFEXP_LAGN->PJM
CLTF
6.9186.918
NYPJM->LTFIMP_NY
CLTF
2.4542.454
LGEELTFEXP_LGEE->PJM
CLTF
1.0841.084
WECLTFEXP_WEC->PJM
CLTF
0.5370.537
SIGELTFEXP_SIGE->PJM
CLTF
0.2110.211
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.8954.895
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.42786.427
CPLELTFEXP_CPLE->PJM
CLTF
10.2710.27
TVALTFEXP_TVA->PJM
CLTF
5.5015.501

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.93 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3669.13
MW Contribution:5.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150801HOPHCF4
80/20
4.1494.149
3150831SPRUNCA
80/20
10.42510.425
3150841SPRUNCB
80/20
10.42510.425
3151081ELIZAR1
80/20
3.6013.601
961941AG1-037 C
Adder
0.53764705882352950.457
941031AE2-094 C
80/20
42.24742.247
934331AD1-057 C
Adder
3.5635294117647063.029
934321AD1-056 C
Adder
6.3870588235294125.429
966871AG1-558 C
Adder
2.56235294117647072.178
958211AF2-115 C
Adder
2.14705882352941171.825
964211AG1-282 C
Adder
2.07882352941176451.767
3150601CHESTF5
Adder
70.4105882352941159.849
941591AE2-156 C
80/20
20.20920.209
3151101ELIZAR3
80/20
3.6473.647
944591AF1-124 C
80/20
51.4651.46
944601AF1-125 C
80/20
50.48850.488
938771AE1-103 C
Adder
3.22705882352941182.743
960081AF2-299 C
Adder
1.95294117647058821.66
944011AF1-069 C
80/20
13.80413.804
963041AG1-153 C
Adder
5.8858823529411765.003
936261AD2-033 C
Adder
12.57294117647058810.687
961791AG1-021 C
Adder
1.71764705882352931.46
966881AG1-559 C
Adder
2.45176470588235332.084
940551AE2-041 C
Adder
7.6152941176470596.473
943461AF1-017 C
Adder
1.51764705882352961.29
316311AC2-079 C
Adder
6.4458823529411775.479
316233AE1-074 C
80/20
2.8742.874
3150781HOPHCF2
80/20
2.7332.733
3150761HOPPOLC
80/20
1.7191.719
944641AF1-129 C
80/20
115.84115.84
316240AF1-291 C
80/20
2.4442.444
934521AD1-076 C
Adder
13.2411.254
934511AD1-075 C
Adder
9.1141176470588237.747
316263AC1-034 C
Adder
6.6529411764705895.655
959311AF2-222 C
Adder
16.0552941176470613.647
962861AG1-135 C
Adder
6.3647058823529425.41
943741AF1-042 C
Adder
3.06352941176470632.604
942001AE2-212 C
80/20
2.4472.447
934501AD1-074 C
Adder
36.4552941176470630.987
961671AG1-007 C
Adder
0.95176470588235310.809
934621AD1-088 C
Adder
9.6105882352941188.169
946301AF1-294 C
Adder
3.5305882352941183.001
942461AE2-259 C
Adder
9.4035294117647077.993
944631AF1-128 C
Adder
44.0564705882352937.448
3150921YORKTN3
Adder
133.0105882352941113.059
3150851SPRUNCC
80/20
0.1870.187
933291AC2-141 C
80/20
34.37234.372
3152251N ANNA1
80/20
56.69756.697
316169AC1-164 GEN
Adder
43.66588235294117537.116
316349AD2-085 C
Adder
3.87058823529411773.29
3151091ELIZAR2
80/20
3.5383.538
946281AF1-292 C
Adder
1.61647058823529431.374
926071AC1-086 C
Adder
21.9611764705882418.667
927021AC1-189 C
Adder
8.6023529411764727.312
964241AG1-285 C
Adder
12.1610.336
962561AG1-105 C
Adder
8.5058823529411767.23
939261AE1-157 C
Adder
14.10235294117647211.987
940431AE2-027 C
80/20
14.61614.616
941101AE2-104 C
Adder
3.75764705882352963.194
944581AF1-123 C
80/20
51.27751.277
316294AC1-161 C
80/20
5.5975.597
957481AF2-042 C
Adder
54.6470588235294146.45
936591AD2-074 C
Adder
5.8552941176470594.977
3150651CHESTF6
80/20
21.09121.091
3150861SPRUNCD
80/20
0.1870.187
957871AF2-081 C
Adder
11.2117647058823529.53
316274AC1-208 C
Adder
9.2835294117647067.891
3151311EDGECMA
Adder
15.55647058823529613.223
3150771HOPHCF1
80/20
2.7332.733
942341AE2-247 C
Adder
1.67764705882352931.426
966621AG1-532 C
Adder
1.46470588235294131.245
3152261N ANNA2
80/20
56.72156.721
934861AD1-115 C
Adder
-3.06-2.601
943471AF1-018 C
Adder
7.6152941176470596.473
3152331SURRY 2
80/20
27.86527.865
940641AE2-051 C
80/20
18.8818.88
316336AC2-165 C
Adder
10.1788235294117648.652
3150731STONECA
80/20
7.7657.765
935161AD1-151 C
Adder
18.16235294117647215.438
3142366NRTHEST
80/20
0.2040.204
958161AF2-110 C
Adder
1.53294117647058831.303
938531AE1-072 C
Adder
19.70000000000000316.745
933981AD1-022 C
Adder
9.4470588235294128.03
963611AG1-210 C
Adder
0.68235294117647060.58
961611AG1-000B C
Adder
17.92352941176470415.235
316375AC2-012 C
80/20
1.521.52
940541AE2-040 C
Adder
3.10117647058823562.636
940481AE2-033 C
Adder
17.43882352941176714.823
958261AF2-120 C
Adder
6.5505882352941175.568
3143096IRON208
80/20
0.4940.494
939191AE1-149 C
80/20
12.15312.153
964791AG1-342 C
Adder
3.38000000000000032.873
957601AF2-054 C
Adder
2.26000000000000021.921
927041AC1-191 C
Adder
10.2870588235294128.744
961951AG1-038 C
Adder
3.3858823529411772.878
3150791HOPHCF3
80/20
2.7332.733
3138533PONTONDP
Adder
0.63647058823529420.541
316254AC1-120 C
Adder
-6.376470588235295-5.42
316257AC1-043 C
Adder
-6.121176470588236-5.203
966661AG1-536 C
Adder
5.6341176470588234.789
3150991CHESPKB
80/20
0.8130.813
939411AE1-173 C
80/20
99.71499.714
3137643SOCKMAN
Adder
0.74235294117647070.631
316303AF2-085
80/20
4.4474.447
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.72830.728
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.33523.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.0414.041
LAGNLTFEXP_LAGN->PJM
CLTF
8.0268.026
NYPJM->LTFIMP_NY
CLTF
2.72.7
LGEELTFEXP_LGEE->PJM
CLTF
1.331.33
WECLTFEXP_WEC->PJM
CLTF
0.6540.654
SIGELTFEXP_SIGE->PJM
CLTF
0.2560.256
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.4135.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69496.694
CPLELTFEXP_CPLE->PJM
CLTF
11.35211.352
TVALTFEXP_TVA->PJM
CLTF
6.4156.415

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.88 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4408.08
MW Contribution:14.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
4.4752941176470593.804
943461AF1-017 C
Adder
1.26823529411764711.078
940431AE2-027 C
Adder
11.3411764705882369.64
942002AE2-212 E
Adder
1.31294117647058851.116
941101AE2-104 C
Adder
3.1588235294117652.685
944581AF1-123 C
Adder
43.0529411764705936.595
316141AB2-099 E
Adder
0.237647058823529430.202
316088AB2-174 E
Adder
6.242352941176475.306
923994AB2-040_E
Adder
5.8811764705882354.999
3151021BRUNSWICKG1
50/50
8.78.7
957481AF2-042 C
Adder
54.4729411764705946.302
924322AB2-079 E O1
Adder
1.25764705882352931.069
946302AF1-294 E
Adder
2.9258823529411772.487
3151801S ANNAS2
50/50
1.2331.233
3150651CHESTF6
Adder
16.10470588235294213.689
946262AF1-291 E
Adder
1.261.071
934576AD1-082 E
Adder
4.1188235294117653.501
943612AF1-032 E
Adder
0.87058823529411770.74
3145506HICKORY
Adder
2.05411764705882361.746
944602AF1-125 E
Adder
97.0388235294117782.483
957871AF2-081 C
Adder
9.4164705882352948.004
933292AC2-141 E
Adder
12.19411764705882510.365
940492AE2-034 E
Adder
2.90235294117647062.467
934522AD1-076 E
Adder
5.8670588235294124.987
943172AE2-346 E
Adder
0.5717647058823530.486
918492AA1-063AE OP
Adder
3.87294117647058833.292
917332KELFORD E
Adder
1.54588235294117651.314
937482AD2-202 E
Adder
1.04941176470588250.892
961792AG1-021 E
Adder
1.4317647058823531.217
932596AC2-079 E
Adder
8.7952941176470587.476
316311AC2-079 C
Adder
5.3905882352941184.582
938532AE1-072 E
Adder
8.6305882352941187.336
3146326AYDLETT TAP
Adder
1.27764705882352961.086
917122Z2-027 E
Adder
1.26588235294117671.076
920692AA2-178 E
Adder
3.86941176470588263.289
316233AE1-074 C
50/50
2.5912.591
966622AG1-532 E
Adder
0.89882352941176480.764
3152421Z1-086 GT2
50/50
11.14611.146
3152441Z1-086 ST
50/50
19.40819.408
3152411Z1-086 GT1
50/50
11.14911.149
3147133PAMPLIN
Adder
0.92823529411764720.789
966002AG1-469 E
Adder
0.73058823529411760.621
935112AD1-144 E
Adder
0.8717647058823530.741
316349AD2-085 C
Adder
3.23411764705882382.749
944582AF1-123 E
Adder
98.5858823529411883.798
944592AF1-124 E
Adder
98.9435294117647184.102
923832AB2-022 E
Adder
1.1682352941176470.993
938772AE1-103 E
Adder
3.8211764705882363.248
916042Z1-036 E
Adder
26.91882352941176422.881
960082AF2-299 E
Adder
1.19764705882352951.018
946281AF1-292 C
Adder
1.48705882352941181.264
926071AC1-086 C
Adder
19.96117647058823516.967
963042AG1-153 E
50/50
8.8728.872
964241AG1-285 C
Adder
11.78352941176470610.016
958212AF2-115 E
Adder
1.78941176470588231.521
925022AB2-158 E
50/50
9.5359.535
316084AB2-161 E
Adder
5.1694117647058834.394
3145946PLYMOUTH TP
Adder
0.30352941176470590.258
933982AD1-022 E
Adder
4.4858823529411773.813
940641AE2-051 C
50/50
18.48718.487
3152431Z1-086 GT3
50/50
11.14611.146
934622AD1-088 E
Adder
4.6035294117647063.913
934612AD1-087 E
Adder
3.5835294117647063.046
316336AC2-165 C
Adder
10.1788235294117648.652
935161AD1-151 C
Adder
13.84941176470588311.772
932046AC2-012 E
Adder
12.31647058823529410.469
958161AF2-110 C
Adder
1.28941176470588251.096
938531AE1-072 C
Adder
16.55647058823529614.073
3145393UNCAMP
Adder
5.7482352941176484.886
933981AD1-022 C
Adder
8.247.004
900672V4-068 E
Adder
0.33764705882352940.287
924302AB2-077 E O1
Adder
1.25764705882352931.069
943462AF1-017 E
Adder
2.06941176470588231.759
942341AE2-247 C
Adder
1.40235294117647061.192
958162AF2-110 E
Adder
2.0505882352941181.743
919153AA1-139 E2
Adder
3.8505882352941183.273
934502AD1-074 E
Adder
16.13411764705882613.714
934512AD1-075 E
Adder
4.0341176470588243.429
918512AA1-065 E OP
Adder
5.2011764705882364.421
924516AB2-100 E1
Adder
2.82.38
940642AE2-051 E
50/50
12.32512.325
966621AG1-532 C
Adder
1.34705882352941191.145
924022AB2-043 E O1
Adder
4.8811764705882354.149
3147223TWITTYS
Adder
0.89294117647058820.759
959312AF2-222 E
Adder
10.4764705882352948.905
3152261N ANNA2
50/50
93.22693.226
961611AG1-000B C
Adder
13.98823529411764911.89
940541AE2-040 C
Adder
2.84470588235294162.418
940481AE2-033 C
Adder
15.98588235294117513.588
940482AE2-033 E
Adder
10.777647058823539.161
923263AB1-132 E OP
Adder
5.80941176470588254.938
924312AB2-078 E O1
Adder
1.25764705882352931.069
925612AC1-036 E
Adder
0.80588235294117660.685
966001AG1-469 C
Adder
1.46235294117647091.243
3145256KINGFORK
Adder
0.93882352941176480.798
925522AC1-027 E
Adder
1.14588235294117660.974
941102AE2-104 E
Adder
5.0223529411764714.269
957872AF2-081 E
Adder
4.0352941176470593.43
933291AC2-141 C
Adder
28.56588235294117724.281
926755AC1-161 E
Adder
12.19411764705882510.365
938552AE1-074 E
50/50
1.3051.305
924162AB2-060 E OP
Adder
4.0294117647058823.425
964242AG1-285 E
Adder
7.8564705882352946.678
938562AE1-075 E
Adder
1.1082352941176470.942
3152251N ANNA1
50/50
93.18793.187
3150831SPRUNCA
Adder
8.2435294117647067.007
3150841SPRUNCB
Adder
8.2435294117647067.007
926662AC1-147 E
Adder
1.24470588235294131.058
916192Z1-068 E
Adder
1.77058823529411761.505
957492AF2-043 E
Adder
1.341.139
923852AB2-025 E
Adder
1.15058823529411770.978
939412AE1-173 E
50/50
62.82462.824
961942AG1-037 E
Adder
0.317647058823529450.27
961941AG1-037 C
Adder
0.476470588235294150.405
941031AE2-094 C
50/50
42.60742.607
941032AE2-094 E
50/50
19.08319.083
936262AD2-033 E
Adder
8.1458823529411776.924
923862AB2-026 E
Adder
1.31.105
958211AF2-115 C
Adder
2.1011764705882351.786
3151791S ANNAG2
50/50
2.42.4
3151771S ANNAG1
50/50
2.42.4
3151781S ANNAS1
50/50
1.2331.233
3151761LOISA E
50/50
4.9314.931
208900BRIS G1
50/50
-2.742-2.742
927226AC1-216 E
Adder
6.6694117647058825.669
936666AD2-085 E
Adder
5.2764705882352954.485
941591AE2-156 C
Adder
16.83647058823529414.311
944591AF1-124 C
Adder
43.2058823529411836.725
944601AF1-125 C
Adder
42.3894117647058836.031
938771AE1-103 C
Adder
2.7670588235294122.352
3145413WATKINS
Adder
0.65411764705882360.556
960081AF2-299 C
Adder
1.7964705882352941.527
926072AC1-086 E
Adder
9.0847058823529427.722
944011AF1-069 C
50/50
13.92113.921
963041AG1-153 C
50/50
5.9155.915
3151051BRUNSWICKS1
50/50
18.07518.075
936261AD2-033 C
Adder
12.2210.387
961791AG1-021 C
Adder
1.68117647058823551.429
946282AF1-292 E
Adder
0.99176470588235290.843
944012AF1-069 E
50/50
5.4085.408
3138533PONTONDP
Adder
0.62235294117647070.529
939191AE1-149 C
Adder
10.0011764705882348.501
3143316POE
Adder
1.30941176470588231.113
901082W1-029 E
Adder
30.02588235294117425.522
3151041BRUNSWICKG3
50/50
8.78.7
942462AE2-259 E
Adder
6.1800000000000015.253
3151731LOISA B
50/50
2.4192.419
924814AB2-134 E
Adder
10.9235294117647069.285
944641AF1-129 C
Adder
88.4505882352941375.183
316240AF1-291 C
Adder
1.88941176470588261.606
942342AE2-247 E
Adder
1.93529411764705881.645
919152AA1-139 E1
Adder
3.8505882352941183.273
934521AD1-076 C
Adder
11.5105882352941199.784
934511AD1-075 C
Adder
7.9235294117647066.735
920042AA2-088 E OP
Adder
10.0447058823529418.538
3145723EMPORIA
Adder
0.414117647058823530.352
923573AB1-173 E OP
Adder
3.1364705882352942.666
919692AA2-053 E OP
Adder
4.00705882352941253.406
925785AC1-054 E
Adder
3.24941176470588242.762
959311AF2-222 C
Adder
15.63529411764705813.29
939192AE1-149 E
Adder
6.6670588235294125.667
939312AE1-162 E
Adder
1.29647058823529431.102
942001AE2-212 C
Adder
1.96941176470588241.674
934065AD1-033 E
Adder
4.7282352941176474.019
937226AE2-253 E
Adder
5.5047058823529414.679
934501AD1-074 C
Adder
31.6952941176470626.941
924517AB2-100 E2
Adder
2.82.38
3151031BRUNSWICKG2
50/50
8.78.7
957482AF2-042 E
Adder
36.31529411764705630.868
934621AD1-088 C
Adder
9.5599999999999998.126
935172AD1-152 E
Adder
5.2941176470588234.5
958502AF2-144 E
Adder
1.2764705882352941.085
946301AF1-294 C
Adder
3.45529411764705862.937
942461AE2-259 C
Adder
9.2705882352941187.88
316192AB2-158 C
50/50
3.5873.587
208901BRIS G2
50/50
-3.245-3.245
940432AE2-027 E
Adder
7.5611764705882356.427
934012AD1-025 E
Adder
8.6341176470588247.339
913392Y1-086 E
Adder
2.0705882352941181.76
939411AE1-173 C
50/50
94.23794.237
3137643SOCKMAN
Adder
0.67882352941176470.577
933502AC2-165 E
Adder
7.6611764705882356.512
3151741LOISA C
50/50
2.4192.419
316303AF2-085
50/50
4.464.46
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.02528.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.37921.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.6863.686
LAGNLTFEXP_LAGN->PJM
CLTF
7.3867.386
NYPJM->LTFIMP_NY
CLTF
2.6122.612
LGEELTFEXP_LGEE->PJM
CLTF
1.1951.195
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5685.568
SIGELTFEXP_SIGE->PJM
CLTF
0.2320.232
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1255.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.8190.81
CPLELTFEXP_CPLE->PJM
CLTF
10.7510.75
TVALTFEXP_TVA->PJM
CLTF
5.8785.878
O66PJM->LTFIMP_O-066
CMTX_NF
35.46935.469

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4342.98
MW Contribution:17.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
941031AE2-094 C
80/20
119.094119.094
3151531CLOVER1
80/20
32.84832.848
3151541CLOVER2
80/20
32.5432.54
958211AF2-115 C
80/20
3.33.3
24684605SMG4
80/20
3.2353.235
964211AG1-282 C
Adder
-1.7882352941176471-1.52
944011AF1-069 C
80/20
38.91238.912
3152421Z1-086 GT2
80/20
32.07932.079
3152441Z1-086 ST
80/20
55.85555.855
3152411Z1-086 GT1
80/20
32.08832.088
944641AF1-129 C
Adder
-95.19529411764705-80.916
316240AF1-291 C
Adder
-2.031764705882353-1.727
316263AC1-034 C
80/20
4.5164.516
937481AD2-202 C
80/20
0.9380.938
3151591KERR 2
80/20
1.8191.819
959311AF2-222 C
80/20
25.13225.132
316205AC1-080 C
80/20
0.5050.505
316123AC1-075 C
80/20
1.5121.512
942751AE2-291 C
80/20
13.51213.512
3151561HALLBR1
80/20
1.2391.239
24684305SMG1
80/20
1.1751.175
942001AE2-212 C
Adder
-2.1176470588235294-1.8
3151031BRUNSWICKG2
80/20
25.36925.369
316359AB2-059 C OP
80/20
1.1351.135
934621AD1-088 C
80/20
24.38424.384
946301AF1-294 C
80/20
5.4265.426
942461AE2-259 C
80/20
14.02314.023
316283AC2-100 C
80/20
2.3262.326
316197AC1-042 C
80/20
0.3460.346
933291AC2-141 C
Adder
-33.98823529411765-28.89
3151641KERR 7
80/20
1.8191.819
313527AB2-043 C
80/20
0.8060.806
963041AG1-153 C
80/20
17.24617.246
3151051BRUNSWICKS1
80/20
52.70552.705
936261AD2-033 C
80/20
19.83719.837
961791AG1-021 C
80/20
2.642.64
316248AF1-058 C
80/20
0.6420.642
936171AD2-023 C
80/20
7.4677.467
941801AE2-185 C
80/20
4.7984.798
964241AG1-285 C
80/20
19.39519.395
3151021BRUNSWICKG1
80/20
25.36925.369
957481AF2-042 C
80/20
148.174148.174
316003AC1-222 C
80/20
1.9581.958
24684405SMG2
80/20
3.2353.235
3151311EDGECMA
80/20
10.35810.358
3152661PLYWOOD A
80/20
2.3542.354
3151601KERR 3
80/20
1.8191.819
3151581KERR 1
80/20
0.650.65
935171AD1-152 C
80/20
3.2243.224
936161AD2-022 C
80/20
12.80112.801
270197AC1-083 C
80/20
0.9970.997
940641AE2-051 C
Adder
-22.240000000000002-18.904
3152431Z1-086 GT3
80/20
32.07932.079
934611AD1-087 C
80/20
3.2323.232
3151611KERR 4
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
316237AB2-079 C O1
80/20
0.5160.516
316222AC1-221 C
80/20
2.9052.905
316034AC1-036 C
80/20
0.3540.354
962561AG1-105 C
80/20
15.92115.921
316118AC1-105 C
80/20
1.7691.769
3144293JTRSVLE
80/20
0.6050.605
316217AC1-145 C
80/20
0.4120.412
942671AE2-283 C
80/20
3.7323.732
943811AF1-049 C
80/20
9.4269.426
938741AE1-100 C
80/20
0.7290.729
941671AE2-166 C
80/20
5.7085.708
938531AE1-072 C
Adder
-16.896470588235296-14.362
316049AB1-081 C OP
80/20
0.9630.963
316238AB2-078 C O1
80/20
0.5160.516
316322AB2-045 C
80/20
0.2670.267
24728405LEESVG
80/20
0.9740.974
316129AC1-054 C
80/20
1.1861.186
3151631KERR 6
80/20
1.8191.819
316131AB2-060 C
80/20
2.3152.315
3138533PONTONDP
80/20
0.9780.978
24684505SMG3
80/20
1.9881.988
24684705SMG5
80/20
1.2291.229
941431AE2-140 C
80/20
14.14314.143
3151041BRUNSWICKG3
80/20
25.36925.369
316239AB2-077 C O1
80/20
0.5160.516
964791AG1-342 C
80/20
6.5026.502
940081AE1-250 C
80/20
13.65313.653
957601AF2-054 C
Adder
-1.8941176470588237-1.61
940601AE2-047 C
80/20
4.254.25
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.59 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4175.62
MW Contribution:17.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151531CLOVER1
80/20
32.84832.848
3151541CLOVER2
80/20
32.5432.54
958211AF2-115 C
80/20
3.33.3
24684605SMG4
80/20
3.2353.235
964211AG1-282 C
Adder
-1.7882352941176471-1.52
3152421Z1-086 GT2
80/20
32.07932.079
3152441Z1-086 ST
80/20
55.85555.855
3152411Z1-086 GT1
80/20
32.08832.088
944641AF1-129 C
Adder
-95.19529411764705-80.916
316240AF1-291 C
Adder
-2.031764705882353-1.727
316263AC1-034 C
80/20
4.5164.516
937481AD2-202 C
80/20
0.9380.938
3151591KERR 2
80/20
1.8191.819
959311AF2-222 C
80/20
25.13225.132
316205AC1-080 C
80/20
0.5050.505
316123AC1-075 C
80/20
1.5121.512
942751AE2-291 C
80/20
13.51213.512
3151561HALLBR1
80/20
1.2391.239
24684305SMG1
80/20
1.1751.175
942001AE2-212 C
Adder
-2.1176470588235294-1.8
3151031BRUNSWICKG2
80/20
25.36925.369
316359AB2-059 C OP
80/20
1.1351.135
934621AD1-088 C
80/20
24.38424.384
946301AF1-294 C
80/20
5.4265.426
942461AE2-259 C
80/20
14.02314.023
316283AC2-100 C
80/20
2.3262.326
316197AC1-042 C
80/20
0.3460.346
933291AC2-141 C
Adder
-33.98823529411765-28.89
3151641KERR 7
80/20
1.8191.819
313527AB2-043 C
80/20
0.8060.806
963041AG1-153 C
80/20
17.24617.246
3151051BRUNSWICKS1
80/20
52.70552.705
936261AD2-033 C
80/20
19.83719.837
961791AG1-021 C
80/20
2.642.64
316248AF1-058 C
80/20
0.6420.642
936171AD2-023 C
80/20
7.4677.467
941801AE2-185 C
80/20
4.7984.798
3151021BRUNSWICKG1
80/20
25.36925.369
957481AF2-042 C
80/20
148.174148.174
316003AC1-222 C
80/20
1.9581.958
24684405SMG2
80/20
3.2353.235
3151311EDGECMA
80/20
10.35810.358
3152661PLYWOOD A
80/20
2.3542.354
940641AE2-051 C
Adder
-22.240000000000002-18.904
3152431Z1-086 GT3
80/20
32.07932.079
934611AD1-087 C
80/20
3.2323.232
3151611KERR 4
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
316237AB2-079 C O1
80/20
0.5160.516
316222AC1-221 C
80/20
2.9052.905
964241AG1-285 C
80/20
19.39519.395
316034AC1-036 C
80/20
0.3540.354
962561AG1-105 C
80/20
15.92115.921
316118AC1-105 C
80/20
1.7691.769
3144293JTRSVLE
80/20
0.6050.605
316217AC1-145 C
80/20
0.4120.412
942671AE2-283 C
80/20
3.7323.732
943811AF1-049 C
80/20
9.4269.426
938741AE1-100 C
80/20
0.7290.729
941671AE2-166 C
80/20
5.7085.708
938531AE1-072 C
Adder
-16.896470588235296-14.362
316049AB1-081 C OP
80/20
0.9630.963
316238AB2-078 C O1
80/20
0.5160.516
316322AB2-045 C
80/20
0.2670.267
3151601KERR 3
80/20
1.8191.819
3151581KERR 1
80/20
0.650.65
935171AD1-152 C
80/20
3.2243.224
936161AD2-022 C
80/20
12.80112.801
270197AC1-083 C
80/20
0.9970.997
24728405LEESVG
80/20
0.9740.974
316129AC1-054 C
80/20
1.1861.186
3151631KERR 6
80/20
1.8191.819
316131AB2-060 C
80/20
2.3152.315
3138533PONTONDP
80/20
0.9780.978
24684505SMG3
80/20
1.9881.988
24684705SMG5
80/20
1.2291.229
941431AE2-140 C
80/20
14.14314.143
3151041BRUNSWICKG3
80/20
25.36925.369
316239AB2-077 C O1
80/20
0.5160.516
964791AG1-342 C
80/20
6.5026.502
940081AE1-250 C
80/20
13.65313.653
957601AF2-054 C
Adder
-1.8941176470588237-1.61
940601AE2-047 C
80/20
4.254.25
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.93 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3894.33
MW Contribution:5.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150831SPRUNCA
Adder
7.6235294117647066.48
3150841SPRUNCB
Adder
7.6235294117647066.48
3151081ELIZAR1
80/20
2.7822.782
961941AG1-037 C
Adder
0.44235294117647060.376
941031AE2-094 C
80/20
39.89839.898
934331AD1-057 C
Adder
3.0305882352941182.576
934321AD1-056 C
Adder
5.4329411764705894.618
3151531CLOVER1
80/20
11.76811.768
3151541CLOVER2
80/20
11.65811.658
316258AE1-075 C
80/20
0.3460.346
958211AF2-115 C
Adder
1.97411764705882351.678
3151791S ANNAG2
80/20
2.6512.651
3151771S ANNAG1
80/20
2.6512.651
3151781S ANNAS1
80/20
1.3621.362
3151761LOISA E
80/20
5.5225.522
208900BRIS G1
80/20
-2.628-2.628
941591AE2-156 C
80/20
15.615.6
3151101ELIZAR3
80/20
2.8172.817
944591AF1-124 C
80/20
40.05140.051
944601AF1-125 C
80/20
39.29539.295
938771AE1-103 C
80/20
2.5672.567
960081AF2-299 C
80/20
1.6731.673
944011AF1-069 C
80/20
13.03613.036
963041AG1-153 C
80/20
5.5365.536
3151051BRUNSWICKS1
80/20
16.91816.918
936261AD2-033 C
Adder
11.4505882352941189.733
961791AG1-021 C
Adder
1.57882352941176471.342
316045AC1-158 C2
80/20
19.41819.418
316170AC1-121 C
80/20
2.7242.724
943461AF1-017 C
80/20
1.1751.175
316311AC2-079 C
80/20
4.9964.996
3156056W1-029WIND
80/20
0.6760.676
316233AE1-074 C
80/20
2.4172.417
3152421Z1-086 GT2
80/20
10.43410.434
3152441Z1-086 ST
80/20
18.16818.168
3152411Z1-086 GT1
80/20
10.43710.437
944641AF1-129 C
Adder
81.5517647058823669.319
316240AF1-291 C
Adder
1.7435294117647061.482
316036AC1-147 C
80/20
0.320.32
316305AF2-043 C
80/20
0.3030.303
316321Z2-027 C
80/20
0.3170.317
934521AD1-076 C
Adder
10.6788235294117659.077
934511AD1-075 C
Adder
7.3517647058823536.249
316087AB2-174 C
80/20
1.0461.046
316263AC1-034 C
Adder
5.6858823529411774.833
937481AD2-202 C
80/20
0.3360.336
959311AF2-222 C
Adder
14.6623529411764712.463
942001AE2-212 C
Adder
1.82117647058823541.548
934501AD1-074 C
Adder
29.40470588235294324.994
3151031BRUNSWICKG2
80/20
8.1438.143
961671AG1-007 C
Adder
0.80588235294117660.685
934621AD1-088 C
80/20
8.9588.958
946301AF1-294 C
Adder
3.2458823529411762.759
942461AE2-259 C
Adder
8.7329411764705887.423
316192AB2-158 C
80/20
3.6253.625
208901BRIS G2
80/20
-3.11-3.11
3150921YORKTN3
Adder
90.5694117647058876.984
3150851SPRUNCC
80/20
0.1370.137
316018AA1-139 ULT2
80/20
0.9420.942
933291AC2-141 C
80/20
26.46526.465
3152251N ANNA1
80/20
89.03589.035
316349AD2-085 C
80/20
2.9972.997
3151091ELIZAR2
80/20
2.7332.733
946281AF1-292 C
80/20
1.3851.385
926071AC1-086 C
Adder
18.5623529411764715.778
927021AC1-189 C
Adder
7.2364705882352946.151
964241AG1-285 C
Adder
11.0294117647058829.375
962561AG1-105 C
Adder
7.70470588235294156.549
316044AC1-158 C1
80/20
19.41819.418
940431AE2-027 C
Adder
10.4682352941176488.898
916191Z1-068 C
80/20
0.0380.038
941101AE2-104 C
80/20
2.9282.928
316185AD1-033 C
80/20
1.071.07
944581AF1-123 C
80/20
39.90939.909
316294AC1-161 C
80/20
4.314.31
316365AB2-100 C1
80/20
0.8620.862
3151021BRUNSWICKG1
80/20
8.1438.143
957481AF2-042 C
80/20
51.00351.003
3151801S ANNAS2
80/20
1.3621.362
3150651CHESTF6
Adder
14.84823529411764812.621
3150861SPRUNCD
80/20
0.1370.137
957871AF2-081 C
80/20
8.7288.728
316274AC1-208 C
Adder
7.857647058823536.679
3151311EDGECMA
Adder
13.28823529411764811.295
316405AF2-144 C
80/20
0.2940.294
942341AE2-247 C
80/20
1.2991.299
316246AF1-032 C
80/20
0.2480.248
316388AE2-253 GEN
80/20
1.711.71
316320Y1-086 C
80/20
0.1920.192
966621AG1-532 C
80/20
1.2551.255
935171AD1-152 C
80/20
1.1991.199
3152261N ANNA2
80/20
89.07389.073
934861AD1-115 C
Adder
2.8482352941176472.421
316017AA1-139 ULT1
80/20
0.9420.942
313526AB2-022 C
80/20
0.3280.328
940641AE2-051 C
80/20
17.2917.29
3152431Z1-086 GT3
80/20
10.43410.434
934611AD1-087 C
80/20
1.1591.159
316336AC2-165 C
80/20
9.6099.609
3150731STONECA
Adder
5.3258823529411774.527
935161AD1-151 C
Adder
12.7647058823529410.85
316083AB2-161 C
80/20
0.4780.478
958161AF2-110 C
80/20
1.1951.195
938531AE1-072 C
80/20
15.34615.346
933981AD1-022 C
Adder
7.6458823529411766.499
961611AG1-000B C
Adder
12.91058823529411910.974
316375AC2-012 C
80/20
1.1731.173
940541AE2-040 C
80/20
2.652.65
940481AE2-033 C
80/20
14.89114.891
3147043LAWRENC
80/20
0.2730.273
966001AG1-469 C
80/20
1.9591.959
939191AE1-149 C
80/20
9.2629.262
3150981CHESPKA
80/20
0.3780.378
3151041BRUNSWICKG3
80/20
8.1438.143
316313AB2-026 C
80/20
0.3770.377
964791AG1-342 C
Adder
3.06352941176470632.604
3151751LOISA D
80/20
2.7082.708
3151731LOISA B
80/20
2.7082.708
316164AC1-076_C
80/20
1.1141.114
316316AC1-027 C
80/20
0.2750.275
316315AB2-025 C
80/20
0.3750.375
316023AB2-100 C2
80/20
0.8620.862
3138533PONTONDP
Adder
0.58470588235294120.497
3151721LOISA A
80/20
2.6942.694
316254AC1-120 C
80/20
7.9327.932
316257AC1-043 C
Adder
5.697647058823534.843
316381AD1-082 C
80/20
1.0891.089
3150991CHESPKB
80/20
0.6270.627
939411AE1-173 C
80/20
87.96287.962
3137643SOCKMAN
Adder
0.6317647058823530.537
3151741LOISA C
80/20
2.7082.708
316303AF2-085
80/20
4.1844.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.96121.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.49718.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.0623.062
LAGNLTFEXP_LAGN->PJM
CLTF
6.5316.531
NYPJM->LTFIMP_NY
CLTF
2.5322.532
LGEELTFEXP_LGEE->PJM
CLTF
0.9710.971
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
SIGELTFEXP_SIGE->PJM
CLTF
0.1910.191
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.744.74
CBM South 2LTFEXP_CBM-S2->PJM
CBM
83.40383.403
CPLELTFEXP_CPLE->PJM
CLTF
9.9459.945
TVALTFEXP_TVA->PJM
CLTF
5.1955.195

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.78 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3857.57
MW Contribution:5.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150801HOPHCF4
80/20
4.0644.064
3150831SPRUNCA
80/20
10.21910.219
3150841SPRUNCB
80/20
10.21910.219
3151081ELIZAR1
80/20
3.5273.527
961941AG1-037 C
Adder
0.52705882352941180.448
941031AE2-094 C
80/20
41.37341.373
934331AD1-057 C
Adder
3.4882352941176472.965
934321AD1-056 C
Adder
6.2529411764705895.315
966871AG1-558 C
Adder
2.50941176470588222.133
958211AF2-115 C
Adder
2.12470588235294141.806
964211AG1-282 C
Adder
2.0317647058823531.727
3150601CHESTF5
Adder
68.9811764705882458.634
941591AE2-156 C
80/20
19.79319.793
3151101ELIZAR3
80/20
3.5723.572
944591AF1-124 C
80/20
50.39950.399
944601AF1-125 C
80/20
49.44749.447
938771AE1-103 C
Adder
3.162.686
960081AF2-299 C
Adder
1.91411764705882351.627
944011AF1-069 C
80/20
13.51813.518
963041AG1-153 C
Adder
5.7647058823529424.9
936261AD2-033 C
Adder
12.4023529411764710.542
961791AG1-021 C
Adder
1.70000000000000021.445
316045AC1-158 C2
80/20
14.96214.962
966881AG1-559 C
Adder
2.3964705882352942.037
940551AE2-041 C
Adder
7.4541176470588246.336
943461AF1-017 C
Adder
1.48588235294117641.263
316311AC2-079 C
Adder
6.3129411764705885.366
316233AE1-074 C
80/20
2.8192.819
3150781HOPHCF2
80/20
2.6772.677
3150761HOPPOLC
80/20
1.6841.684
944641AF1-129 C
80/20
113.49113.49
316240AF1-291 C
80/20
2.3942.394
934521AD1-076 C
Adder
12.96470588235294111.02
934511AD1-075 C
Adder
8.9247058823529427.586
316263AC1-034 C
Adder
6.5105882352941185.534
959311AF2-222 C
Adder
15.85294117647058913.475
962861AG1-135 C
Adder
6.222352941176475.289
943741AF1-042 C
Adder
2.9964705882352942.547
942001AE2-212 C
80/20
2.3972.397
934501AD1-074 C
Adder
35.6976470588235330.343
961671AG1-007 C
Adder
0.9317647058823530.792
934621AD1-088 C
Adder
9.4482352941176488.031
946301AF1-294 C
Adder
3.4941176470588242.97
942461AE2-259 C
Adder
9.347.939
316192AB2-158 C
80/20
2.1182.118
944631AF1-128 C
Adder
43.1623529411764736.688
3150921YORKTN3
Adder
130.26705882352942110.727
3150851SPRUNCC
80/20
0.1830.183
933291AC2-141 C
80/20
33.66433.664
3152251N ANNA1
80/20
55.32355.323
316169AC1-164 GEN
Adder
42.77176470588235436.356
316349AD2-085 C
Adder
3.79058823529411763.222
3151091ELIZAR2
80/20
3.4653.465
946281AF1-292 C
Adder
1.58470588235294121.347
926071AC1-086 C
Adder
21.50823529411764718.282
927021AC1-189 C
Adder
8.4188235294117647.156
964241AG1-285 C
Adder
11.97764705882352810.181
962561AG1-105 C
Adder
8.3588235294117657.105
316044AC1-158 C1
80/20
14.96214.962
939261AE1-157 C
Adder
13.77647058823529511.71
940431AE2-027 C
80/20
14.31814.318
941101AE2-104 C
Adder
3.683.128
944581AF1-123 C
80/20
50.22150.221
316294AC1-161 C
80/20
5.4825.482
957481AF2-042 C
Adder
53.64117647058823545.595
936591AD2-074 C
Adder
5.7258823529411764.867
3150651CHESTF6
80/20
20.66420.664
3150861SPRUNCD
80/20
0.1830.183
957871AF2-081 C
Adder
10.989.333
316274AC1-208 C
Adder
9.0917647058823537.728
3151311EDGECMA
Adder
15.22352941176470512.94
3150771HOPHCF1
80/20
2.6772.677
942341AE2-247 C
Adder
1.64235294117647061.396
966621AG1-532 C
Adder
1.43529411764705881.22
3152261N ANNA2
80/20
55.34655.346
943471AF1-018 C
Adder
7.4541176470588246.336
3152331SURRY 2
80/20
27.29427.294
940641AE2-051 C
80/20
18.48818.488
316336AC2-165 C
Adder
10.1094117647058828.593
3150731STONECA
80/20
7.6067.606
935161AD1-151 C
Adder
17.79176470588235415.123
3142366NRTHEST
80/20
0.20.2
958161AF2-110 C
Adder
1.50117647058823531.276
938531AE1-072 C
Adder
19.2929411764705916.399
933981AD1-022 C
Adder
9.2505882352941197.863
963611AG1-210 C
Adder
0.66705882352941170.567
961611AG1-000B C
Adder
17.55647058823529614.923
316375AC2-012 C
80/20
1.4881.488
940541AE2-040 C
Adder
3.03764705882352942.582
940481AE2-033 C
Adder
17.08117647058823614.519
927041AC1-191 C
Adder
10.0729411764705888.562
958261AF2-120 C
Adder
6.4035294117647065.443
3143096IRON208
80/20
0.4840.484
939191AE1-149 C
80/20
11.90511.905
964791AG1-342 C
Adder
3.32117647058823542.823
957601AF2-054 C
Adder
2.2117647058823531.88
316164AC1-076_C
80/20
0.9930.993
961951AG1-038 C
Adder
3.3117647058823532.815
3150791HOPHCF3
80/20
2.6772.677
3138533PONTONDP
Adder
0.62941176470588240.535
966661AG1-536 C
Adder
5.5082352941176484.682
3150991CHESPKB
80/20
0.7960.796
939411AE1-173 C
80/20
97.64897.648
3137643SOCKMAN
Adder
0.72705882352941180.618
316303AF2-085
80/20
4.3634.363
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.65727.657
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.08222.082
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.7473.747
LAGNLTFEXP_LAGN->PJM
CLTF
7.6777.677
NYPJM->LTFIMP_NY
CLTF
2.8062.806
LGEELTFEXP_LGEE->PJM
CLTF
1.2221.222
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
SIGELTFEXP_SIGE->PJM
CLTF
0.2370.237
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.2865.286
CBM South 2LTFEXP_CBM-S2->PJM
CBM
94.17394.173
CPLELTFEXP_CPLE->PJM
CLTF
11.08811.088
TVALTFEXP_TVA->PJM
CLTF
6.1396.139

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.54 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4631.24
MW Contribution:14.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
935162AD1-151 E
Adder
9.1294117647058827.76
943461AF1-017 C
Adder
1.2482352941176471.061
932596AC2-079 E
Adder
8.6588235294117667.36
316311AC2-079 C
Adder
5.3070588235294124.511
938532AE1-072 E
Adder
8.4941176470588247.22
3146326AYDLETT TAP
Adder
1.25764705882352931.069
917122Z2-027 E
Adder
1.24470588235294131.058
920692AA2-178 E
Adder
3.8023529411764713.232
316233AE1-074 C
Adder
2.5458823529411772.164
966622AG1-532 E
Adder
0.88117647058823530.749
3147133PAMPLIN
Adder
0.91529411764705890.778
966002AG1-469 E
50/50
0.9930.993
926739AC1-158 E1
50/50
50.96750.967
939192AE1-149 E
Adder
6.5694117647058825.584
939312AE1-162 E
Adder
1.27764705882352961.086
942001AE2-212 C
Adder
1.94235294117647061.651
934065AD1-033 E
Adder
4.6541176470588243.956
937226AE2-253 E
Adder
5.4188235294117654.606
934501AD1-074 C
Adder
31.13882352941176626.468
924517AB2-100 E2
Adder
2.74588235294117672.334
957482AF2-042 E
Adder
35.55176470588235630.219
934621AD1-088 C
Adder
9.3717647058823547.966
935172AD1-152 E
Adder
5.1847058823529414.407
958502AF2-144 E
Adder
1.2588235294117651.07
946301AF1-294 C
Adder
3.4070588235294122.896
942461AE2-259 C
Adder
9.1658823529411777.791
316192AB2-158 C
50/50
3.6573.657
940431AE2-027 C
Adder
11.2058823529411789.525
942002AE2-212 E
Adder
1.2952941176470591.101
941101AE2-104 C
Adder
3.10941176470588232.643
944581AF1-123 C
Adder
42.37411764705882436.018
316141AB2-099 E
Adder
0.234117647058823540.199
316088AB2-174 E
Adder
6.1235294117647065.205
923994AB2-040_E
Adder
5.76941176470588254.904
957481AF2-042 C
Adder
53.3270588235294245.328
924322AB2-079 E O1
Adder
1.23529411764705891.05
946302AF1-294 E
Adder
2.88470588235294122.452
3151801S ANNAS2
50/50
1.381.38
3150651CHESTF6
Adder
15.92588235294117813.537
946262AF1-291 E
Adder
1.24470588235294131.058
934576AD1-082 E
Adder
4.0564705882352943.448
943612AF1-032 E
Adder
0.85764705882352940.729
3145506HICKORY
Adder
2.02235294117647071.719
944602AF1-125 E
Adder
95.5082352941176581.182
957871AF2-081 C
Adder
9.2670588235294127.877
933292AC2-141 E
Adder
12.0070588235294110.206
940492AE2-034 E
Adder
2.85176470588235282.424
934522AD1-076 E
Adder
5.7635294117647064.899
943172AE2-346 E
Adder
0.56117647058823530.477
918492AA1-063AE OP
Adder
3.80117647058823543.231
925122AB2-169 E
Adder
5.2764705882352954.485
917332KELFORD E
Adder
1.51764705882352961.29
316274AC1-208 C
Adder
8.2905882352941187.047
937482AD2-202 E
Adder
1.02705882352941180.873
961792AG1-021 E
Adder
1.4117647058823531.2
935112AD1-144 E
Adder
0.85764705882352940.729
316349AD2-085 C
Adder
3.1835294117647062.706
944582AF1-123 E
Adder
97.0317647058823782.477
944592AF1-124 E
Adder
97.3823529411764882.775
923832AB2-022 E
Adder
1.14941176470588240.977
938772AE1-103 E
Adder
3.75764705882352963.194
916042Z1-036 E
Adder
26.4694117647058822.499
960082AF2-299 E
Adder
1.17529411764705880.999
946281AF1-292 C
Adder
1.45882352941176461.24
926071AC1-086 C
Adder
19.57647058823529616.64
963042AG1-153 E
Adder
8.6682352941176477.368
964241AG1-285 C
Adder
11.5811764705882349.844
962561AG1-105 C
Adder
8.0894117647058836.876
958212AF2-115 E
Adder
1.76470588235294111.5
925022AB2-158 E
50/50
9.7219.721
316044AC1-158 C1
50/50
19.48619.486
316084AB2-161 E
Adder
5.0917647058823544.328
3145946PLYMOUTH TP
Adder
0.29882352941176470.254
933982AD1-022 E
Adder
4.4070588235294123.746
940641AE2-051 C
50/50
18.07818.078
927146AC1-208 E
Adder
3.68117647058823533.129
934622AD1-088 E
Adder
4.5117647058823533.835
934612AD1-087 E
Adder
3.50941176470588272.983
316336AC2-165 C
Adder
10.0588235294117668.55
926004AC1-076_E
50/50
6.486.48
3150731STONECA
Adder
0.92705882352941180.788
935161AD1-151 C
Adder
13.69411764705882511.64
932046AC2-012 E
Adder
12.12705882352941210.308
958161AF2-110 C
Adder
1.26823529411764711.078
938531AE1-072 C
Adder
16.29411764705882213.85
3145393UNCAMP
Adder
5.65176470588235354.804
933981AD1-022 C
Adder
8.0941176470588236.88
900672V4-068 E
Adder
0.33058823529411770.281
924302AB2-077 E O1
Adder
1.23529411764705891.05
926486AC1-120 E
50/50
4.1534.153
943462AF1-017 E
Adder
2.03764705882352941.732
942341AE2-247 C
Adder
1.38000000000000011.173
958162AF2-110 E
Adder
2.01764705882352931.715
919153AA1-139 E2
Adder
3.78941176470588253.221
934502AD1-074 E
Adder
15.85176470588235313.474
934512AD1-075 E
Adder
3.96235294117647063.368
918512AA1-065 E OP
Adder
5.1070588235294124.341
924516AB2-100 E1
Adder
2.74588235294117672.334
940642AE2-051 E
50/50
12.05212.052
966621AG1-532 C
Adder
1.32117647058823541.123
924022AB2-043 E O1
Adder
4.7941176470588244.075
3147223TWITTYS
Adder
0.87882352941176480.747
959312AF2-222 E
Adder
10.3129411764705888.766
3152261N ANNA2
50/50
89.60889.608
934861AD1-115 C
Adder
2.92.465
961611AG1-000B C
Adder
13.8152941176470611.743
940541AE2-040 C
Adder
2.78823529411764742.37
940481AE2-033 C
Adder
15.6752941176470613.324
940482AE2-033 E
Adder
10.5670588235294118.982
923263AB1-132 E OP
Adder
5.697647058823534.843
924312AB2-078 E O1
Adder
1.23529411764705891.05
925612AC1-036 E
Adder
0.79294117647058830.674
966001AG1-469 C
50/50
1.9871.987
926740AC1-158 E2
50/50
50.96750.967
925672AC1-043 E
Adder
9.4635294117647078.044
3145256KINGFORK
Adder
0.92470588235294130.786
925522AC1-027 E
Adder
1.1282352941176470.959
941102AE2-104 E
Adder
4.9423529411764714.201
957872AF2-081 E
Adder
3.9717647058823533.376
933291AC2-141 C
Adder
28.12941176470588223.91
926755AC1-161 E
Adder
12.0070588235294110.206
938552AE1-074 E
Adder
1.28235294117647071.09
932632AC2-084 E
Adder
2.96705882352941152.522
926214AC1-099 E
Adder
1.1082352941176470.942
924162AB2-060 E OP
Adder
3.95764705882352933.364
964242AG1-285 E
Adder
7.7211764705882356.563
938562AE1-075 E
Adder
1.0917647058823530.928
3152251N ANNA1
50/50
89.57189.571
934862AD1-115 E
Adder
4.73176470588235354.022
924814AB2-134 E
Adder
10.7988235294117659.179
944641AF1-129 C
Adder
87.4717647058823574.351
316240AF1-291 C
Adder
1.86705882352941191.587
942342AE2-247 E
Adder
1.90588235294117661.62
919152AA1-139 E1
Adder
3.78941176470588253.221
934521AD1-076 C
Adder
11.3094117647058829.613
934511AD1-075 C
Adder
7.7847058823529426.617
920042AA2-088 E OP
Adder
9.8670588235294128.387
3145723EMPORIA
Adder
0.405882352941176470.345
923573AB1-173 E OP
Adder
3.07647058823529432.615
919692AA2-053 E OP
Adder
3.93176470588235333.342
925785AC1-054 E
Adder
3.18705882352941172.709
959311AF2-222 C
Adder
15.39294117647058813.084
926502AC1-121 E
50/50
1.3031.303
3150831SPRUNCA
Adder
8.1435294117647056.922
3150841SPRUNCB
Adder
8.1435294117647056.922
926662AC1-147 E
Adder
1.22588235294117661.042
916192Z1-068 E
Adder
1.74235294117647071.481
957492AF2-043 E
Adder
1.31882352941176471.121
923852AB2-025 E
Adder
1.1282352941176470.959
939412AE1-173 E
Adder
61.5211764705882452.293
961942AG1-037 E
Adder
0.311764705882352940.265
961941AG1-037 C
Adder
0.46705882352941180.397
941031AE2-094 C
50/50
41.61841.618
941032AE2-094 E
50/50
18.6418.64
936262AD2-033 E
Adder
8.0141176470588256.812
923862AB2-026 E
Adder
1.28117647058823541.089
958211AF2-115 C
Adder
2.0717647058823531.761
3151791S ANNAG2
50/50
2.6852.685
3151771S ANNAG1
50/50
2.6852.685
3151781S ANNAS1
50/50
1.381.38
3151761LOISA E
50/50
5.5965.596
208900BRIS G1
50/50
-2.836-2.836
925332AB2-190 E
Adder
6.8164705882352945.794
927226AC1-216 E
Adder
6.5917647058823535.603
936666AD2-085 E
Adder
5.195294117647064.416
941591AE2-156 C
Adder
16.57647058823529614.09
944591AF1-124 C
Adder
42.5247058823529436.146
944601AF1-125 C
Adder
41.7211764705882435.463
938771AE1-103 C
Adder
2.72117647058823582.313
3145413WATKINS
Adder
0.64235294117647070.546
960081AF2-299 C
Adder
1.76235294117647071.498
926072AC1-086 E
Adder
8.9094117647058837.573
944011AF1-069 C
50/50
13.59813.598
963041AG1-153 C
Adder
5.7788235294117654.912
936261AD2-033 C
Adder
12.02117647058823610.218
962562AG1-105 E
Adder
5.3929411764705884.584
961791AG1-021 C
Adder
1.65764705882352951.409
316045AC1-158 C2
50/50
19.48619.486
316170AC1-121 C
50/50
2.7692.769
946282AF1-292 E
Adder
0.97294117647058820.827
944012AF1-069 E
50/50
5.2835.283
3138533PONTONDP
Adder
0.61411764705882350.522
3151721LOISA A
50/50
2.7312.731
316254AC1-120 C
50/50
8.0618.061
316257AC1-043 C
Adder
5.84.93
939191AE1-149 C
Adder
9.8529411764705898.375
3143316POE
Adder
1.28823529411764711.095
901082W1-029 E
Adder
29.54000000000000325.109
926206AC1-098 E
Adder
3.35647058823529452.853
942462AE2-259 E
Adder
6.1105882352941175.194
3151751LOISA D
50/50
2.7452.745
3151731LOISA B
50/50
2.7452.745
316164AC1-076_C
50/50
1.1311.131
208901BRIS G2
50/50
-3.356-3.356
940432AE2-027 E
Adder
7.4705882352941186.35
934012AD1-025 E
Adder
8.5352941176470597.255
913392Y1-086 E
Adder
2.03647058823529431.731
939411AE1-173 C
Adder
92.2811764705882478.439
3137643SOCKMAN
Adder
0.66588235294117650.566
933502AC2-165 E
Adder
7.5705882352941176.435
3151741LOISA C
50/50
2.7452.745
316303AF2-085
50/50
4.3644.364
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.22125.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.23820.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.4183.418
LAGNLTFEXP_LAGN->PJM
CLTF
7.0687.068
NYPJM->LTFIMP_NY
CLTF
2.7142.714
LGEELTFEXP_LGEE->PJM
CLTF
1.0981.098
WECLTFEXP_WEC->PJM
CLTF
0.5410.541
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7645.764
SIGELTFEXP_SIGE->PJM
CLTF
0.2140.214
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0035.003
CBM South 2LTFEXP_CBM-S2->PJM
CBM
88.42988.429
CPLELTFEXP_CPLE->PJM
CLTF
10.49610.496
TVALTFEXP_TVA->PJM
CLTF
5.6275.627
O66PJM->LTFIMP_O-066
CMTX_NF
36.7236.72

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4234.7
MW Contribution:17.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
941031AE2-094 C
80/20
138.215138.215
3151531CLOVER1
80/20
28.86828.868
3151541CLOVER2
80/20
28.59828.598
958211AF2-115 C
80/20
2.8862.886
24684605SMG4
80/20
3.0033.003
964211AG1-282 C
Adder
-1.7011764705882353-1.446
3152421Z1-086 GT2
80/20
33.46433.464
3152441Z1-086 ST
80/20
58.26658.266
3152411Z1-086 GT1
80/20
33.47333.473
944641AF1-129 C
Adder
-90.49176470588236-76.918
316240AF1-291 C
Adder
-1.9317647058823528-1.642
316263AC1-034 C
80/20
4.3284.328
937481AD2-202 C
80/20
0.8240.824
3151591KERR 2
80/20
1.6151.615
959311AF2-222 C
80/20
22.05622.056
316205AC1-080 C
80/20
0.4520.452
316123AC1-075 C
80/20
1.3531.353
942751AE2-291 C
80/20
12.11212.112
3151561HALLBR1
80/20
1.1241.124
24684305SMG1
80/20
1.0911.091
942001AE2-212 C
Adder
-2.010588235294118-1.709
3151031BRUNSWICKG2
80/20
25.15725.157
316359AB2-059 C OP
80/20
1.0881.088
934621AD1-088 C
80/20
21.36821.368
946301AF1-294 C
80/20
4.7464.746
942461AE2-259 C
80/20
12.19912.199
316283AC2-100 C
80/20
2.1162.116
316197AC1-042 C
80/20
0.3150.315
933291AC2-141 C
Adder
-32.203529411764706-27.373
3151641KERR 7
80/20
1.6151.615
313527AB2-043 C
80/20
0.7110.711
944011AF1-069 C
80/20
45.1645.16
963041AG1-153 C
80/20
17.10317.103
3151051BRUNSWICKS1
80/20
52.26552.265
936261AD2-033 C
80/20
17.43217.432
961791AG1-021 C
80/20
2.3092.309
316248AF1-058 C
80/20
0.5710.571
936171AD2-023 C
80/20
7.0937.093
941801AE2-185 C
80/20
4.3664.366
3151021BRUNSWICKG1
80/20
25.15725.157
957481AF2-042 C
80/20
129.887129.887
316003AC1-222 C
80/20
1.7441.744
24684405SMG2
80/20
3.0033.003
3152661PLYWOOD A
80/20
2.0932.093
3151601KERR 3
80/20
1.6151.615
3151581KERR 1
80/20
0.5770.577
935171AD1-152 C
80/20
2.8492.849
936161AD2-022 C
80/20
12.15912.159
270197AC1-083 C
80/20
0.9340.934
940641AE2-051 C
Adder
-21.040000000000003-17.884
3152431Z1-086 GT3
80/20
33.46433.464
934611AD1-087 C
80/20
2.842.84
3151611KERR 4
80/20
1.6151.615
3151621KERR 5
80/20
1.6151.615
316237AB2-079 C O1
80/20
0.4550.455
316222AC1-221 C
80/20
2.6372.637
964241AG1-285 C
80/20
17.07617.076
316034AC1-036 C
80/20
0.3110.311
962561AG1-105 C
80/20
14.10814.108
316118AC1-105 C
80/20
1.5721.572
3144293JTRSVLE
80/20
0.5290.529
316217AC1-145 C
80/20
0.3750.375
942671AE2-283 C
80/20
3.3963.396
943811AF1-049 C
80/20
8.9298.929
938741AE1-100 C
80/20
0.690.69
941671AE2-166 C
80/20
5.45.4
938531AE1-072 C
Adder
-16.01294117647059-13.611
316049AB1-081 C OP
80/20
0.9230.923
316238AB2-078 C O1
80/20
0.4550.455
316322AB2-045 C
80/20
0.2270.227
24728405LEESVG
80/20
0.8940.894
316129AC1-054 C
80/20
1.0481.048
3151631KERR 6
80/20
1.6151.615
316131AB2-060 C
80/20
2.042.04
3138533PONTONDP
80/20
0.8550.855
24684505SMG3
80/20
1.8451.845
24684705SMG5
80/20
1.1411.141
941431AE2-140 C
80/20
13.39313.393
3151041BRUNSWICKG3
80/20
25.15725.157
316239AB2-077 C O1
80/20
0.4550.455
964791AG1-342 C
80/20
5.7665.766
940081AE1-250 C
80/20
12.86112.861
957601AF2-054 C
Adder
-1.8-1.53
940601AE2-047 C
80/20
4.0274.027
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846
NYPJM->LTFIMP_NY
CLTF
2.1082.108
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
WECLTFEXP_WEC->PJM
CLTF
1.451.45
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: 545T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1                /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 568T575_SRT-A'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1   /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1   /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 314940 TO BUS 941030 CKT 1   /*8ROGERS RD   500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314282 to 314285 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 314922 ckt 1
314914 to 314322 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314936 to 314902 ckt 1
314934 to 314916 ckt 1
941030 to 314902 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC101.12 %678.68B686.285.61
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC100.08 %678.68B679.215.61
GD1DVP
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.25 %984.18B1016.214.87
GD1DVP
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.2 %984.18B1015.684.87
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
OPAC104.13 %3220.44A3353.3620.8
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC136.2 %2442.12B3326.1517.93
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC115.81 %4070.2B4713.5819.2
GD1DVP
8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
DVP_P1-2: LN N ANNA-KRAKEN_SRT-A
OPAC107.4 %3220.44B3458.6210.85
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
OPAC126.34 %1058.16B1336.889.18
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
OPAC108.69 %4070.2B4423.7143.41
GD1DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC106.0 %2442.12B2588.6116.38
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
OPAC105.29 %3220.44B3390.9612.01
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.93 %4070.2B4311.6943.01

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:101.12 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:686.28
MW Contribution:5.61
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.67 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:730.77
MW Contribution:5.83
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316239AB2-077 C O1
50/50
0.2330.233
942462AE2-259 E
50/50
9.6239.623
964791AG1-342 C
Adder
2.18117647058823531.854
940642AE2-051 E
Adder
4.1988235294117653.569
924516AB2-100 E1
Adder
1.11058823529411770.944
966621AG1-532 C
Adder
0.61058823529411770.519
944011AF1-069 C
Adder
4.9870588235294124.239
963041AG1-153 C
Adder
2.2447058823529411.908
960081AF2-299 C
Adder
0.81294117647058820.691
936261AD2-033 C
50/50
11.9511.95
3144293JTRSVLE
50/50
0.4860.486
961791AG1-021 C
50/50
2.1112.111
962562AG1-105 E
Adder
3.74705882352941183.185
924032AB2-045 E
50/50
2.9052.905
963042AG1-153 E
Adder
3.3670588235294122.862
316258AE1-075 C
50/50
0.4640.464
946281AF1-292 C
Adder
0.67294117647058820.572
960082AF2-299 E
Adder
0.54235294117647060.461
964241AG1-285 C
50/50
9.7319.731
316034AC1-036 C
50/50
0.2210.221
958212AF2-115 E
50/50
2.2482.248
962561AG1-105 C
Adder
5.6211764705882354.778
3147223TWITTYS
50/50
0.8960.896
959312AF2-222 E
50/50
10.86410.864
924022AB2-043 E O1
50/50
3.7383.738
316313AB2-026 C
50/50
0.5060.506
918492AA1-063AE OP
Adder
1.64941176470588241.402
937482AD2-202 E
Adder
0.62470588235294120.531
961792AG1-021 E
50/50
1.7981.798
3151921BEARGRDN G2
50/50
13.38913.389
316233AE1-074 C
Adder
1.20705882352941171.026
966622AG1-532 E
Adder
0.407058823529411750.346
3147133PAMPLIN
50/50
1.231.23
316322AB2-045 C
50/50
0.6480.648
927264AC1-222 E
Adder
2.09764705882352941.783
924302AB2-077 E O1
50/50
0.9490.949
3145723EMPORIA
Adder
0.187058823529411780.159
923573AB1-173 E OP
Adder
1.4035294117647061.193
919692AA2-053 E OP
Adder
1.73294117647058841.473
925785AC1-054 E
Adder
1.7588235294117651.495
959311AF2-222 C
50/50
16.21416.214
940451AE2-029 C
Adder
-2.1529411764705886-1.83
939411AE1-173 C
Adder
32.29058823529411627.447
933502AC2-165 E
50/50
11.611.6
3137643SOCKMAN
Adder
0.30117647058823530.256
938552AE1-074 E
Adder
0.60823529411764710.517
938562AE1-075 E
50/50
1.3971.397
964242AG1-285 E
50/50
6.4876.487
313527AB2-043 C
50/50
0.3720.372
924162AB2-060 E OP
50/50
3.163.16
964792AG1-342 E
Adder
1.45411764705882351.236
3151911BEARGRDN G1
50/50
13.38913.389
932763AC2-100 E
Adder
1.15411764705882350.981
940641AE2-051 C
Adder
6.297647058823535.353
316336AC2-165 C
50/50
15.41215.412
934622AD1-088 E
50/50
3.2433.243
934612AD1-087 E
Adder
2.13647058823529431.816
3151931BEARGRDN S1
50/50
17.3217.32
927255AC1-221 E
Adder
1.72235294117647061.464
944012AF1-069 E
Adder
1.93764705882352951.647
946282AF1-292 E
Adder
0.44941176470588240.382
316131AB2-060 C
50/50
1.0971.097
3138533PONTONDP
50/50
0.7820.782
3150831SPRUNCA
Adder
3.52.975
3150841SPRUNCB
Adder
3.52.975
939412AE1-173 E
Adder
21.52705882352941218.298
941032AE2-094 E
Adder
6.83647058823529455.811
941031AE2-094 C
Adder
15.26470588235294212.975
923852AB2-025 E
Adder
0.428235294117647050.364
923862AB2-026 E
50/50
1.6391.639
936262AD2-033 E
50/50
7.9677.967
958211AF2-115 C
50/50
2.6382.638
316405AF2-144 C
50/50
0.3950.395
957481AF2-042 C
Adder
31.1270588235294126.458
316088AB2-174 E
Adder
2.8035294117647062.383
923994AB2-040_E
Adder
2.6317647058823532.237
924322AB2-079 E O1
50/50
0.9490.949
946302AF1-294 E
50/50
3.6743.674
943902AF1-058 E
Adder
0.69647058823529410.592
940541AE2-040 C
Adder
1.05764705882352940.899
940482AE2-033 E
Adder
4.0447058823529413.438
940481AE2-033 C
Adder
6.05.1
925612AC1-036 E
50/50
0.8090.809
316237AB2-079 C O1
50/50
0.2330.233
924312AB2-078 E O1
50/50
0.9490.949
316238AB2-078 C O1
50/50
0.2330.233
926274AC1-105 E
Adder
1.55058823529411781.318
938821AE1-108 C
Adder
7.7941176470588236.625
958502AF2-144 E
50/50
1.611.61
924517AB2-100 E2
Adder
1.11058823529411770.944
957482AF2-042 E
Adder
20.7517647058823517.639
934621AD1-088 C
50/50
6.7356.735
935172AD1-152 E
Adder
3.09058823529411742.627
946301AF1-294 C
50/50
4.3394.339
942461AE2-259 C
50/50
14.43514.435
938822AE1-108 E
Adder
3.71882352941176463.161
316303AF2-085
50/50
2.1712.171
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.16230.162
TVALTFEXP_TVA->PJM
CLTF
1.171.17
LAGNLTFEXP_LAGN->PJM
CLTF
1.5461.546
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.3713.371
NYPJM->LTFIMP_NY
CLTF
0.4340.434
MECLTFEXP_MEC->PJM
CLTF
0.2690.269
O66PJM->LTFIMP_O-066
CMTX_NF
5.2725.272
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8220.822
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0190.019
SIGELTFEXP_SIGE->PJM
CLTF
0.010.01
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CPLELTFEXP_CPLE->PJM
CLTF
4.0014.001
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0350.035
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9041.904

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.08 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:679.21
MW Contribution:5.61
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.62 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:723.63
MW Contribution:5.83
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316239AB2-077 C O1
50/50
0.2330.233
942462AE2-259 E
50/50
9.6239.623
964791AG1-342 C
Adder
2.18117647058823531.854
944011AF1-069 C
Adder
4.9870588235294124.239
963041AG1-153 C
Adder
2.2447058823529411.908
960081AF2-299 C
Adder
0.81294117647058820.691
936261AD2-033 C
50/50
11.9511.95
3144293JTRSVLE
50/50
0.4860.486
961791AG1-021 C
50/50
2.1112.111
962562AG1-105 E
Adder
3.74705882352941183.185
924032AB2-045 E
50/50
2.9052.905
963042AG1-153 E
Adder
3.3670588235294122.862
316258AE1-075 C
50/50
0.4640.464
946281AF1-292 C
Adder
0.67294117647058820.572
960082AF2-299 E
Adder
0.54235294117647060.461
964241AG1-285 C
50/50
9.7319.731
316034AC1-036 C
50/50
0.2210.221
958212AF2-115 E
50/50
2.2482.248
962561AG1-105 C
Adder
5.6211764705882354.778
940642AE2-051 E
Adder
4.1988235294117653.569
924516AB2-100 E1
Adder
1.11058823529411770.944
966621AG1-532 C
Adder
0.61058823529411770.519
3147223TWITTYS
50/50
0.8960.896
959312AF2-222 E
50/50
10.86410.864
924022AB2-043 E O1
50/50
3.7383.738
316313AB2-026 C
50/50
0.5060.506
918492AA1-063AE OP
Adder
1.64941176470588241.402
937482AD2-202 E
Adder
0.62470588235294120.531
961792AG1-021 E
50/50
1.7981.798
3151921BEARGRDN G2
50/50
13.38913.389
316233AE1-074 C
Adder
1.20705882352941171.026
966622AG1-532 E
Adder
0.407058823529411750.346
3147133PAMPLIN
50/50
1.231.23
316322AB2-045 C
50/50
0.6480.648
927264AC1-222 E
Adder
2.09764705882352941.783
924302AB2-077 E O1
50/50
0.9490.949
3145723EMPORIA
Adder
0.187058823529411780.159
923573AB1-173 E OP
Adder
1.4035294117647061.193
919692AA2-053 E OP
Adder
1.73294117647058841.473
925785AC1-054 E
Adder
1.7588235294117651.495
959311AF2-222 C
50/50
16.21416.214
940451AE2-029 C
Adder
-2.1529411764705886-1.83
939411AE1-173 C
Adder
32.29058823529411627.447
933502AC2-165 E
50/50
11.611.6
3137643SOCKMAN
Adder
0.30117647058823530.256
938552AE1-074 E
Adder
0.60823529411764710.517
938562AE1-075 E
50/50
1.3971.397
964242AG1-285 E
50/50
6.4876.487
313527AB2-043 C
50/50
0.3720.372
924162AB2-060 E OP
50/50
3.163.16
964792AG1-342 E
Adder
1.45411764705882351.236
3151911BEARGRDN G1
50/50
13.38913.389
932763AC2-100 E
Adder
1.15411764705882350.981
940641AE2-051 C
Adder
6.297647058823535.353
316336AC2-165 C
50/50
15.41215.412
934622AD1-088 E
50/50
3.2433.243
934612AD1-087 E
Adder
2.13647058823529431.816
3151931BEARGRDN S1
50/50
17.3217.32
927255AC1-221 E
Adder
1.72235294117647061.464
944012AF1-069 E
Adder
1.93764705882352951.647
946282AF1-292 E
Adder
0.44941176470588240.382
316131AB2-060 C
50/50
1.0971.097
3138533PONTONDP
50/50
0.7820.782
3150831SPRUNCA
Adder
3.52.975
3150841SPRUNCB
Adder
3.52.975
939412AE1-173 E
Adder
21.52705882352941218.298
941032AE2-094 E
Adder
6.83647058823529455.811
941031AE2-094 C
Adder
15.26470588235294212.975
923852AB2-025 E
Adder
0.428235294117647050.364
923862AB2-026 E
50/50
1.6391.639
936262AD2-033 E
50/50
7.9677.967
958211AF2-115 C
50/50
2.6382.638
316405AF2-144 C
50/50
0.3950.395
957481AF2-042 C
Adder
31.1270588235294126.458
316088AB2-174 E
Adder
2.8035294117647062.383
923994AB2-040_E
Adder
2.6317647058823532.237
924322AB2-079 E O1
50/50
0.9490.949
946302AF1-294 E
50/50
3.6743.674
943902AF1-058 E
Adder
0.69647058823529410.592
940541AE2-040 C
Adder
1.05764705882352940.899
940482AE2-033 E
Adder
4.0447058823529413.438
940481AE2-033 C
Adder
6.05.1
925612AC1-036 E
50/50
0.8090.809
316237AB2-079 C O1
50/50
0.2330.233
924312AB2-078 E O1
50/50
0.9490.949
316238AB2-078 C O1
50/50
0.2330.233
926274AC1-105 E
Adder
1.55058823529411781.318
938821AE1-108 C
Adder
7.7941176470588236.625
958502AF2-144 E
50/50
1.611.61
924517AB2-100 E2
Adder
1.11058823529411770.944
957482AF2-042 E
Adder
20.7517647058823517.639
934621AD1-088 C
50/50
6.7356.735
935172AD1-152 E
Adder
3.09058823529411742.627
946301AF1-294 C
50/50
4.3394.339
942461AE2-259 C
50/50
14.43514.435
938822AE1-108 E
Adder
3.71882352941176463.161
316303AF2-085
50/50
2.1712.171
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CPLELTFEXP_CPLE->PJM
CLTF
4.0014.001
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0350.035
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9041.904
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8220.822
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0190.019
SIGELTFEXP_SIGE->PJM
CLTF
0.010.01
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.16230.162
TVALTFEXP_TVA->PJM
CLTF
1.171.17
LAGNLTFEXP_LAGN->PJM
CLTF
1.5461.546
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.3713.371
NYPJM->LTFIMP_NY
CLTF
0.4340.434
MECLTFEXP_MEC->PJM
CLTF
0.2690.269
O66PJM->LTFIMP_O-066
CMTX_NF
5.2725.272

Details for 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.25 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1016.21
MW Contribution:4.87
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.15 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:985.63
MW Contribution:4.65
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3143316POE
50/50
1.0861.086
939191AE1-149 C
50/50
7.1377.137
901082W1-029 E
Adder
10.9870588235294139.339
926206AC1-098 E
Adder
1.35999999999999991.156
944011AF1-069 C
Adder
4.6141176470588243.922
941591AE2-156 C
Adder
6.1141176470588245.197
925332AB2-190 E
50/50
4.6914.691
944591AF1-124 C
Adder
15.08705882352941312.824
944601AF1-125 C
Adder
14.80235294117647312.582
927226AC1-216 E
Adder
4.122352941176473.504
936666AD2-085 E
Adder
2.5752941176470592.189
963041AG1-153 C
Adder
1.9482352941176471.656
938771AE1-103 C
Adder
1.11764705882352940.95
3145413WATKINS
Adder
0.26470588235294120.225
960081AF2-299 C
Adder
0.81647058823529410.694
926072AC1-086 E
Adder
4.0352941176470593.43
944582AF1-123 E
Adder
34.4258823529411829.262
944592AF1-124 E
Adder
34.55058823529411429.368
935112AD1-144 E
Adder
0.33176470588235290.282
316349AD2-085 C
Adder
1.57882352941176471.342
923832AB2-022 E
Adder
0.421176470588235260.358
963042AG1-153 E
Adder
2.92235294117647062.484
938772AE1-103 E
Adder
1.5435294117647061.312
916042Z1-036 E
Adder
9.9682352941176488.473
946281AF1-292 C
Adder
0.67529411764705880.574
960082AF2-299 E
Adder
0.54470588235294130.463
926071AC1-086 C
Adder
8.8647058823529427.535
964241AG1-285 C
Adder
3.85882352941176483.28
927021AC1-189 C
Adder
2.97529411764705862.529
924152AB2-059 E OP
Adder
1.87058823529411791.59
940642AE2-051 E
Adder
4.0635294117647063.454
316132AB2-190 C
50/50
2.4122.412
919153AA1-139 E2
Adder
1.36588235294117651.161
943462AF1-017 E
Adder
1.00941176470588250.858
942341AE2-247 C
Adder
0.68470588235294120.582
958162AF2-110 E
Adder
0.82470588235294120.701
924516AB2-100 E1
Adder
1.36823529411764721.163
934512AD1-075 E
Adder
1.53411764705882361.304
934502AD1-074 E
Adder
6.1364705882352945.216
966621AG1-532 C
Adder
0.61294117647058830.521
918512AA1-065 E OP
Adder
2.04235294117647071.736
924022AB2-043 E O1
Adder
1.60117647058823541.361
918532AA1-067 E
Adder
0.251764705882352950.214
933292AC2-141 E
Adder
3.78588235294117673.218
946262AF1-291 E
50/50
1.6321.632
3150651CHESTF6
50/50
21.89721.897
944602AF1-125 E
Adder
33.8847058823529428.802
3145506HICKORY
Adder
0.72352941176470590.615
934576AD1-082 E
50/50
2.5582.558
957871AF2-081 C
Adder
3.34117647058823542.84
943612AF1-032 E
Adder
0.320.272
940492AE2-034 E
Adder
1.09058823529411760.927
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
918492AA1-063AE OP
Adder
1.59411764705882361.355
937482AD2-202 E
Adder
0.32588235294117650.277
917332KELFORD E
Adder
0.61411764705882350.522
925122AB2-169 E
Adder
2.04352941176470631.737
935162AD1-151 E
50/50
6.0156.015
938532AE1-072 E
Adder
3.07058823529411742.61
3146326AYDLETT TAP
Adder
0.455294117647058850.387
943461AF1-017 C
Adder
0.61882352941176480.526
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
917122Z2-027 E
Adder
0.457647058823529460.389
920692AA2-178 E
Adder
1.4552941176470591.237
966622AG1-532 E
Adder
0.408235294117647030.347
922923AB1-081 E OP
Adder
1.321.122
3150731STONECA
50/50
4.5124.512
932046AC2-012 E
Adder
4.4823529411764713.81
935161AD1-151 C
50/50
9.0229.022
938531AE1-072 C
Adder
5.8905882352941185.007
958161AF2-110 C
Adder
0.51764705882352950.44
3145393UNCAMP
Adder
2.3247058823529411.976
933981AD1-022 C
Adder
3.162.686
900672V4-068 E
Adder
0.136470588235294120.116
924302AB2-077 E O1
Adder
0.41176470588235290.35
316240AF1-291 C
50/50
2.4482.448
944641AF1-129 C
50/50
120.262120.262
924814AB2-134 E
Adder
6.7529411764705885.74
316381AD1-082 C
50/50
0.7330.733
919152AA1-139 E1
Adder
1.36588235294117651.161
942342AE2-247 E
Adder
0.94470588235294130.803
920042AA2-088 E OP
Adder
4.0811764705882353.469
934511AD1-075 C
Adder
3.01411764705882362.562
934521AD1-076 C
Adder
4.377647058823533.721
3145723EMPORIA
Adder
0.185882352941176470.158
923573AB1-173 E OP
Adder
1.36823529411764721.163
919692AA2-053 E OP
Adder
1.64941176470588241.402
925785AC1-054 E
Adder
1.2082352941176471.027
316263AC1-034 C
Adder
2.3517647058823531.999
939411AE1-173 C
Adder
31.5352941176470626.805
940432AE2-027 E
Adder
4.6964705882352943.992
934012AD1-025 E
Adder
5.3364705882352944.536
913392Y1-086 E
Adder
0.74470588235294120.633
3137643SOCKMAN
Adder
0.288235294117647030.245
919710AA2-057 E
Adder
1.44823529411764731.231
926755AC1-161 E
Adder
3.78588235294117673.218
933291AC2-141 C
Adder
8.8694117647058827.539
3150761HOPPOLC
50/50
1.0021.002
925522AC1-027 E
Adder
0.410588235294117640.349
957872AF2-081 E
Adder
1.4317647058823531.217
3145256KINGFORK
Adder
0.357647058823529430.304
941102AE2-104 E
Adder
2.0188235294117651.716
964242AG1-285 E
Adder
2.5717647058823532.186
926214AC1-099 E
Adder
0.44941176470588240.382
932632AC2-084 E
Adder
1.20235294117647061.022
924162AB2-060 E OP
Adder
1.3117647058823531.115
940641AE2-051 C
Adder
6.0952941176470595.181
316084AB2-161 E
50/50
3.213.21
316083AB2-161 C
50/50
0.3210.321
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
933982AD1-022 E
Adder
1.721.462
934622AD1-088 E
Adder
1.38117647058823521.174
934612AD1-087 E
Adder
1.1117647058823530.945
927146AC1-208 E
Adder
1.51.275
944012AF1-069 E
Adder
1.7917647058823531.523
946282AF1-292 E
Adder
0.45058823529411770.383
917512Z2-088 E OP1
Adder
1.73411764705882351.474
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
939412AE1-173 E
Adder
21.0235294117647117.87
941032AE2-094 E
Adder
6.3247058823529425.376
941031AE2-094 C
Adder
14.12000000000000112.002
3150801HOPHCF4
50/50
2.4192.419
3150791HOPHCF3
50/50
1.5941.594
926662AC1-147 E
Adder
0.452941176470588240.385
916192Z1-068 E
Adder
0.63294117647058830.538
957492AF2-043 E
Adder
0.49294117647058820.419
923852AB2-025 E
Adder
0.6317647058823530.537
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
934321AD1-056 C
Adder
2.3988235294117652.039
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934322AD1-056 E
Adder
1.30117647058823541.106
927022AC1-189 E
Adder
1.48235294117647071.26
925595AC1-034 E
Adder
1.77411764705882361.508
316274AC1-208 C
Adder
3.3788235294117652.872
917342Z2-044 E
Adder
0.215294117647058830.183
3151311EDGECMA
Adder
5.5117647058823534.685
942002AE2-212 E
50/50
1.4081.408
940431AE2-027 C
Adder
7.0447058823529425.988
3150771HOPHCF1
50/50
1.5941.594
944581AF1-123 C
Adder
15.03411764705882412.779
941101AE2-104 C
Adder
1.26941176470588221.079
957481AF2-042 C
Adder
17.0152941176470614.463
316088AB2-174 E
Adder
2.7588235294117652.345
316141AB2-099 E
Adder
0.095294117647058830.081
923994AB2-040_E
Adder
2.56588235294117652.181
924322AB2-079 E O1
Adder
0.41176470588235290.35
961672AG1-007 E
Adder
0.188235294117647060.16
961611AG1-000B C
Adder
7.342352941176476.241
940541AE2-040 C
Adder
1.56117647058823541.327
940482AE2-033 E
Adder
5.8329411764705884.958
940481AE2-033 C
Adder
8.6517647058823537.354
923263AB1-132 E OP
Adder
2.582.193
924312AB2-078 E O1
Adder
0.41176470588235290.35
942001AE2-212 C
50/50
2.1112.111
939192AE1-149 E
50/50
4.7584.758
3150781HOPHCF2
50/50
1.5941.594
934065AD1-033 E
Adder
1.6670588235294121.417
939312AE1-162 E
Adder
0.5717647058823530.486
937226AE2-253 E
Adder
1.9482352941176471.656
924517AB2-100 E2
Adder
1.36823529411764721.163
934501AD1-074 C
Adder
12.05529411764705810.247
957482AF2-042 E
Adder
11.3435294117647069.642
934621AD1-088 C
Adder
2.86941176470588262.439
935172AD1-152 E
Adder
1.6435294117647061.397
961671AG1-007 C
Adder
0.332941176470588240.283
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
NYPJM->LTFIMP_NY
CLTF
0.4360.436
TVALTFEXP_TVA->PJM
CLTF
1.561.56
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
WECLTFEXP_WEC->PJM
CLTF
0.140.14
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004

Details for 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.2 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1015.68
MW Contribution:4.87
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.1 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:985.14
MW Contribution:4.65
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3143316POE
50/50
1.0861.086
939191AE1-149 C
50/50
7.1377.137
901082W1-029 E
Adder
10.9870588235294139.339
926206AC1-098 E
Adder
1.35999999999999991.156
944011AF1-069 C
Adder
4.6141176470588243.922
941591AE2-156 C
Adder
6.1141176470588245.197
925332AB2-190 E
50/50
4.6914.691
944591AF1-124 C
Adder
15.08705882352941312.824
944601AF1-125 C
Adder
14.80235294117647312.582
927226AC1-216 E
Adder
4.122352941176473.504
936666AD2-085 E
Adder
2.5752941176470592.189
963041AG1-153 C
Adder
1.9482352941176471.656
938771AE1-103 C
Adder
1.11764705882352940.95
3145413WATKINS
Adder
0.26470588235294120.225
960081AF2-299 C
Adder
0.81647058823529410.694
926072AC1-086 E
Adder
4.0352941176470593.43
944582AF1-123 E
Adder
34.4258823529411829.262
944592AF1-124 E
Adder
34.55058823529411429.368
935112AD1-144 E
Adder
0.33176470588235290.282
316349AD2-085 C
Adder
1.57882352941176471.342
923832AB2-022 E
Adder
0.421176470588235260.358
963042AG1-153 E
Adder
2.92235294117647062.484
938772AE1-103 E
Adder
1.5435294117647061.312
916042Z1-036 E
Adder
9.9682352941176488.473
946281AF1-292 C
Adder
0.67529411764705880.574
960082AF2-299 E
Adder
0.54470588235294130.463
926071AC1-086 C
Adder
8.8647058823529427.535
964241AG1-285 C
Adder
3.85882352941176483.28
927021AC1-189 C
Adder
2.97529411764705862.529
924152AB2-059 E OP
Adder
1.87058823529411791.59
940642AE2-051 E
Adder
4.0635294117647063.454
316132AB2-190 C
50/50
2.4122.412
919153AA1-139 E2
Adder
1.36588235294117651.161
943462AF1-017 E
Adder
1.00941176470588250.858
942341AE2-247 C
Adder
0.68470588235294120.582
958162AF2-110 E
Adder
0.82470588235294120.701
924516AB2-100 E1
Adder
1.36823529411764721.163
934512AD1-075 E
Adder
1.53411764705882361.304
934502AD1-074 E
Adder
6.1364705882352945.216
966621AG1-532 C
Adder
0.61294117647058830.521
918512AA1-065 E OP
Adder
2.04235294117647071.736
924022AB2-043 E O1
Adder
1.60117647058823541.361
918532AA1-067 E
Adder
0.251764705882352950.214
935162AD1-151 E
50/50
6.0156.015
938532AE1-072 E
Adder
3.07058823529411742.61
3146326AYDLETT TAP
Adder
0.455294117647058850.387
943461AF1-017 C
Adder
0.61882352941176480.526
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
917122Z2-027 E
Adder
0.457647058823529460.389
920692AA2-178 E
Adder
1.4552941176470591.237
966622AG1-532 E
Adder
0.408235294117647030.347
922923AB1-081 E OP
Adder
1.321.122
3150731STONECA
50/50
4.5124.512
932046AC2-012 E
Adder
4.4823529411764713.81
935161AD1-151 C
50/50
9.0229.022
938531AE1-072 C
Adder
5.8905882352941185.007
958161AF2-110 C
Adder
0.51764705882352950.44
3145393UNCAMP
Adder
2.3247058823529411.976
933981AD1-022 C
Adder
3.162.686
900672V4-068 E
Adder
0.136470588235294120.116
924302AB2-077 E O1
Adder
0.41176470588235290.35
316240AF1-291 C
50/50
2.4482.448
944641AF1-129 C
50/50
120.262120.262
924814AB2-134 E
Adder
6.7529411764705885.74
316381AD1-082 C
50/50
0.7330.733
919152AA1-139 E1
Adder
1.36588235294117651.161
942342AE2-247 E
Adder
0.94470588235294130.803
920042AA2-088 E OP
Adder
4.0811764705882353.469
934511AD1-075 C
Adder
3.01411764705882362.562
934521AD1-076 C
Adder
4.377647058823533.721
3145723EMPORIA
Adder
0.185882352941176470.158
923573AB1-173 E OP
Adder
1.36823529411764721.163
919692AA2-053 E OP
Adder
1.64941176470588241.402
925785AC1-054 E
Adder
1.2082352941176471.027
316263AC1-034 C
Adder
2.3517647058823531.999
939411AE1-173 C
Adder
31.5352941176470626.805
940432AE2-027 E
Adder
4.6964705882352943.992
934012AD1-025 E
Adder
5.3364705882352944.536
913392Y1-086 E
Adder
0.74470588235294120.633
3137643SOCKMAN
Adder
0.288235294117647030.245
919710AA2-057 E
Adder
1.44823529411764731.231
926755AC1-161 E
Adder
3.78588235294117673.218
933291AC2-141 C
Adder
8.8694117647058827.539
3150761HOPPOLC
50/50
1.0021.002
925522AC1-027 E
Adder
0.410588235294117640.349
957872AF2-081 E
Adder
1.4317647058823531.217
3145256KINGFORK
Adder
0.357647058823529430.304
941102AE2-104 E
Adder
2.0188235294117651.716
964242AG1-285 E
Adder
2.5717647058823532.186
926214AC1-099 E
Adder
0.44941176470588240.382
932632AC2-084 E
Adder
1.20235294117647061.022
924162AB2-060 E OP
Adder
1.3117647058823531.115
940641AE2-051 C
Adder
6.0952941176470595.181
316084AB2-161 E
50/50
3.213.21
316083AB2-161 C
50/50
0.3210.321
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
933982AD1-022 E
Adder
1.721.462
934622AD1-088 E
Adder
1.38117647058823521.174
934612AD1-087 E
Adder
1.1117647058823530.945
927146AC1-208 E
Adder
1.51.275
944012AF1-069 E
Adder
1.7917647058823531.523
946282AF1-292 E
Adder
0.45058823529411770.383
917512Z2-088 E OP1
Adder
1.73411764705882351.474
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
939412AE1-173 E
Adder
21.0235294117647117.87
941032AE2-094 E
Adder
6.3247058823529425.376
941031AE2-094 C
Adder
14.12000000000000112.002
3150801HOPHCF4
50/50
2.4192.419
3150791HOPHCF3
50/50
1.5941.594
926662AC1-147 E
Adder
0.452941176470588240.385
916192Z1-068 E
Adder
0.63294117647058830.538
957492AF2-043 E
Adder
0.49294117647058820.419
923852AB2-025 E
Adder
0.6317647058823530.537
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
934321AD1-056 C
Adder
2.3988235294117652.039
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934322AD1-056 E
Adder
1.30117647058823541.106
927022AC1-189 E
Adder
1.48235294117647071.26
925595AC1-034 E
Adder
1.77411764705882361.508
933292AC2-141 E
Adder
3.78588235294117673.218
946262AF1-291 E
50/50
1.6321.632
3150651CHESTF6
50/50
21.89721.897
944602AF1-125 E
Adder
33.8847058823529428.802
3145506HICKORY
Adder
0.72352941176470590.615
934576AD1-082 E
50/50
2.5582.558
957871AF2-081 C
Adder
3.34117647058823542.84
943612AF1-032 E
Adder
0.320.272
940492AE2-034 E
Adder
1.09058823529411760.927
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
918492AA1-063AE OP
Adder
1.59411764705882361.355
937482AD2-202 E
Adder
0.32588235294117650.277
917332KELFORD E
Adder
0.61411764705882350.522
925122AB2-169 E
Adder
2.04352941176470631.737
316274AC1-208 C
Adder
3.3788235294117652.872
917342Z2-044 E
Adder
0.215294117647058830.183
3151311EDGECMA
Adder
5.5117647058823534.685
942002AE2-212 E
50/50
1.4081.408
940431AE2-027 C
Adder
7.0447058823529425.988
3150771HOPHCF1
50/50
1.5941.594
944581AF1-123 C
Adder
15.03411764705882412.779
941101AE2-104 C
Adder
1.26941176470588221.079
957481AF2-042 C
Adder
17.0152941176470614.463
316088AB2-174 E
Adder
2.7588235294117652.345
316141AB2-099 E
Adder
0.095294117647058830.081
923994AB2-040_E
Adder
2.56588235294117652.181
924322AB2-079 E O1
Adder
0.41176470588235290.35
961672AG1-007 E
Adder
0.188235294117647060.16
961611AG1-000B C
Adder
7.342352941176476.241
940541AE2-040 C
Adder
1.56117647058823541.327
940482AE2-033 E
Adder
5.8329411764705884.958
940481AE2-033 C
Adder
8.6517647058823537.354
923263AB1-132 E OP
Adder
2.582.193
924312AB2-078 E O1
Adder
0.41176470588235290.35
942001AE2-212 C
50/50
2.1112.111
939192AE1-149 E
50/50
4.7584.758
3150781HOPHCF2
50/50
1.5941.594
934065AD1-033 E
Adder
1.6670588235294121.417
939312AE1-162 E
Adder
0.5717647058823530.486
937226AE2-253 E
Adder
1.9482352941176471.656
924517AB2-100 E2
Adder
1.36823529411764721.163
934501AD1-074 C
Adder
12.05529411764705810.247
957482AF2-042 E
Adder
11.3435294117647069.642
934621AD1-088 C
Adder
2.86941176470588262.439
935172AD1-152 E
Adder
1.6435294117647061.397
961671AG1-007 C
Adder
0.332941176470588240.283
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
WECLTFEXP_WEC->PJM
CLTF
0.140.14
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
NYPJM->LTFIMP_NY
CLTF
0.4360.436
TVALTFEXP_TVA->PJM
CLTF
1.561.56
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.13 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3353.36
MW Contribution:20.8
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3493.11
MW Contribution:20.39
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
919152AA1-139 E1
50/50
4.6184.618
316018AA1-139 ULT2
50/50
1.2231.223
942342AE2-247 E
Adder
2.141.819
920042AA2-088 E OP
Adder
11.94941176470588210.157
934511AD1-075 C
Adder
9.507058823529418.081
934521AD1-076 C
Adder
13.81176470588235411.74
3145723EMPORIA
50/50
0.50.5
923573AB1-173 E OP
Adder
3.78941176470588253.221
919692AA2-053 E OP
Adder
4.8352941176470594.11
944581AF1-123 C
50/50
51.37451.374
316185AD1-033 C
50/50
1.391.39
941101AE2-104 C
Adder
3.66705882352941173.117
316320Y1-086 C
50/50
0.2480.248
3151041BRUNSWICKG3
50/50
12.28212.282
3151021BRUNSWICKG1
50/50
12.28212.282
957481AF2-042 C
50/50
69.9469.94
3143316POE
Adder
1.30823529411764721.112
939191AE1-149 C
Adder
9.5941176470588238.155
901082W1-029 E
Adder
35.7705882352941230.405
316365AB2-100 C1
50/50
1.1231.123
926206AC1-098 E
Adder
4.1470588235294123.525
935171AD1-152 C
50/50
1.6091.609
964791AG1-342 C
Adder
3.96470588235294133.37
940642AE2-051 E
50/50
17.4117.41
316388AE2-253 GEN
50/50
2.2212.221
919153AA1-139 E2
50/50
4.6184.618
943462AF1-017 E
Adder
2.2870588235294121.944
942341AE2-247 C
Adder
1.54941176470588231.317
958162AF2-110 E
Adder
2.38000000000000032.023
924516AB2-100 E1
50/50
3.3843.384
934512AD1-075 E
Adder
4.844.114
934502AD1-074 E
Adder
19.3616.456
966621AG1-532 C
50/50
1.6281.628
918512AA1-065 E OP
Adder
6.2505882352941175.313
3147223TWITTYS
Adder
1.03411764705882360.879
959312AF2-222 E
Adder
11.9210.132
924022AB2-043 E O1
Adder
5.9035294117647065.018
918532AA1-067 E
Adder
0.80588235294117660.685
944011AF1-069 C
50/50
19.88619.886
3151091ELIZAR2
50/50
3.4943.494
3151081ELIZAR1
50/50
3.5563.556
941591AE2-156 C
50/50
19.83519.835
944591AF1-124 C
50/50
51.55751.557
944601AF1-125 C
50/50
50.58350.583
316316AC1-027 C
50/50
0.3530.353
936666AD2-085 E
Adder
5.8329411764705884.958
963041AG1-153 C
50/50
8.3218.321
938771AE1-103 C
Adder
3.24823529411764732.761
3145413WATKINS
Adder
0.7717647058823530.656
960081AF2-299 C
50/50
2.1712.171
926072AC1-086 E
Adder
10.9894117647058819.341
3151531CLOVER1
50/50
15.90415.904
936261AD2-033 C
Adder
13.51176470588235311.485
961791AG1-021 C
Adder
1.63058823529411771.386
962562AG1-105 E
Adder
6.6470588235294125.65
3151101ELIZAR3
50/50
3.6013.601
944582AF1-123 E
50/50
117.641117.641
944592AF1-124 E
50/50
118.067118.067
935112AD1-144 E
Adder
0.98941176470588230.841
316349AD2-085 C
Adder
3.5752941176470593.039
923832AB2-022 E
50/50
1.3981.398
963042AG1-153 E
50/50
12.48112.481
938772AE1-103 E
Adder
4.4858823529411773.813
916042Z1-036 E
Adder
32.1705882352941227.345
316023AB2-100 C2
50/50
1.1231.123
946281AF1-292 C
50/50
1.7971.797
960082AF2-299 E
50/50
1.4471.447
926071AC1-086 C
Adder
24.1447058823529420.523
3151541CLOVER2
50/50
15.75715.757
964241AG1-285 C
50/50
14.87614.876
958212AF2-115 E
Adder
1.73647058823529421.476
927021AC1-189 C
Adder
9.4905882352941178.067
962561AG1-105 C
Adder
9.9705882352941188.475
924152AB2-059 E OP
Adder
5.9564705882352945.063
933292AC2-141 E
50/50
14.89414.894
316294AC1-161 C
50/50
5.7015.701
944602AF1-125 E
50/50
115.795115.795
916191Z1-068 C
50/50
0.0490.049
3145506HICKORY
50/50
2.4672.467
934576AD1-082 E
Adder
4.1988235294117653.569
957871AF2-081 C
50/50
11.29311.293
943612AF1-032 E
Adder
1.02823529411764710.874
940492AE2-034 E
Adder
3.4764705882352942.955
934522AD1-076 E
Adder
7.045.984
943172AE2-346 E
Adder
0.68588235294117650.583
918492AA1-063AE OP
Adder
4.65058823529411753.953
937482AD2-202 E
50/50
1.3221.322
917332KELFORD E
Adder
1.8635294117647061.584
925122AB2-169 E
Adder
6.4858823529411775.513
316274AC1-208 C
Adder
10.255294117647068.717
961792AG1-021 E
Adder
1.38941176470588231.181
917342Z2-044 E
Adder
0.6764705882352940.575
3151311EDGECMA
Adder
17.50705882352941214.881
938532AE1-072 E
50/50
10.34610.346
3146326AYDLETT TAP
50/50
1.5311.531
943461AF1-017 C
Adder
1.40235294117647061.192
316311AC2-079 C
Adder
5.9964705882352955.097
932596AC2-079 E
Adder
9.7835294117647078.316
3152431Z1-086 GT3
50/50
15.81115.811
3152441Z1-086 ST
50/50
27.53227.532
917122Z2-027 E
50/50
1.5121.512
920692AA2-178 E
Adder
4.6352941176470593.94
966622AG1-532 E
50/50
1.0851.085
3147133PAMPLIN
Adder
0.89882352941176480.764
922923AB1-081 E OP
Adder
4.20470588235294153.574
927264AC1-222 E
Adder
4.3282352941176473.679
932046AC2-012 E
50/50
14.50114.501
316017AA1-139 ULT1
50/50
1.2231.223
938531AE1-072 C
50/50
19.84719.847
958161AF2-110 C
Adder
1.49647058823529421.272
3152411Z1-086 GT1
50/50
15.81615.816
3152421Z1-086 GT2
50/50
15.81115.811
3145393UNCAMP
Adder
6.7635294117647065.749
933981AD1-022 C
Adder
9.8917647058823528.408
900672V4-068 E
Adder
0.402352941176470640.342
924302AB2-077 E O1
Adder
1.52117647058823541.293
925785AC1-054 E
Adder
3.94000000000000043.349
959311AF2-222 C
Adder
17.79058823529411615.122
316263AC1-034 C
Adder
7.4894117647058826.366
939411AE1-173 C
50/50
128.665128.665
913392Y1-086 E
50/50
2.4762.476
3137643SOCKMAN
Adder
0.81882352941176460.696
937481AD2-202 C
50/50
0.4540.454
919710AA2-057 E
Adder
4.49411764705882363.82
926755AC1-161 E
50/50
14.89414.894
933291AC2-141 C
50/50
34.8934.89
925522AC1-027 E
50/50
1.3621.362
957872AF2-081 E
50/50
4.844.84
3145256KINGFORK
Adder
1.06588235294117650.906
3150921YORKTN3
Adder
6.2929411764705885.349
941102AE2-104 E
Adder
5.8305882352941184.956
316087AB2-174 C
50/50
1.3621.362
964242AG1-285 E
50/50
9.9189.918
926214AC1-099 E
Adder
1.36941176470588231.164
932632AC2-084 E
Adder
3.66588235294117663.116
924162AB2-060 E OP
Adder
4.8364705882352944.111
964792AG1-342 E
Adder
2.6435294117647062.247
932763AC2-100 E
Adder
2.80941176470588252.388
940641AE2-051 C
50/50
26.11526.115
316084AB2-161 E
Adder
5.26941176470588254.479
3145946PLYMOUTH TP
Adder
0.364705882352941160.31
933982AD1-022 E
Adder
5.3847058823529414.577
934622AD1-088 E
50/50
5.5555.555
934611AD1-087 C
50/50
1.5661.566
934612AD1-087 E
50/50
4.5174.517
927146AC1-208 E
Adder
4.5541176470588243.871
927255AC1-221 E
Adder
4.1411764705882363.52
944012AF1-069 E
50/50
7.7257.725
316315AB2-025 C
50/50
0.4880.488
946282AF1-292 E
50/50
1.1981.198
3138533PONTONDP
Adder
0.60352941176470590.513
917512Z2-088 E OP1
Adder
5.5247058823529414.696
939412AE1-173 E
50/50
85.77785.777
941032AE2-094 E
50/50
27.25927.259
941031AE2-094 C
50/50
60.86460.864
926662AC1-147 E
Adder
1.46588235294117641.246
916192Z1-068 E
50/50
2.1052.105
957492AF2-043 E
Adder
1.58117647058823541.344
923852AB2-025 E
50/50
1.3891.389
3151051BRUNSWICKS1
50/50
25.51625.516
961941AG1-037 C
Adder
0.5717647058823530.486
961942AG1-037 E
Adder
0.381176470588235340.324
936262AD2-033 E
Adder
9.0082352941176477.657
958211AF2-115 C
Adder
2.03764705882352941.732
934321AD1-056 C
Adder
7.126.052
934331AD1-057 C
Adder
3.9717647058823533.376
934332AD1-057 E
Adder
2.0682352941176471.758
934322AD1-056 E
Adder
3.86117647058823543.282
927022AC1-189 E
Adder
4.7282352941176474.019
925595AC1-034 E
Adder
5.65058823529411754.803
316088AB2-174 E
50/50
7.5427.542
316141AB2-099 E
Adder
0.28588235294117650.243
923994AB2-040_E
Adder
7.1047058823529416.039
924322AB2-079 E O1
Adder
1.52117647058823541.293
946302AF1-294 E
Adder
2.83882352941176472.413
961672AG1-007 E
Adder
0.60.51
943902AF1-058 E
Adder
1.42941176470588241.215
316375AC2-012 C
50/50
1.4951.495
961611AG1-000B C
Adder
13.21058823529411611.229
313526AB2-022 C
50/50
0.4240.424
940541AE2-040 C
50/50
3.4343.434
940482AE2-033 E
50/50
13.01513.015
940481AE2-033 C
50/50
19.30519.305
923263AB1-132 E OP
Adder
7.0270588235294125.973
925612AC1-036 E
Adder
0.93294117647058830.793
924312AB2-078 E O1
Adder
1.52117647058823541.293
926274AC1-105 E
Adder
2.9882352941176472.54
939192AE1-149 E
Adder
6.3964705882352955.437
934065AD1-033 E
50/50
5.6715.671
939312AE1-162 E
Adder
1.37058823529411771.165
937226AE2-253 E
50/50
6.6066.606
316321Z2-027 C
50/50
0.410.41
3151031BRUNSWICKG2
50/50
12.28212.282
924517AB2-100 E2
50/50
3.3843.384
934501AD1-074 C
Adder
38.0305882352941232.326
957482AF2-042 E
50/50
46.62746.627
934621AD1-088 C
50/50
11.53711.537
935172AD1-152 E
50/50
6.6176.617
946301AF1-294 C
Adder
3.3517647058823532.849
961671AG1-007 C
Adder
1.05882352941176470.9
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.47229.472
G-007PJM->LTFIMP_G-007
CMTX_NF
3.5513.551
CPLELTFEXP_CPLE->PJM
CLTF
13.22113.221
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.1651.165
MECLTFEXP_MEC->PJM
CLTF
3.8563.856
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.3016.301
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.8122.81
NYPJM->LTFIMP_NY
CLTF
1.6611.661
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
O66PJM->LTFIMP_O-066
CMTX_NF
22.61622.616
CBM South 2LTFEXP_CBM-S2->PJM
CBM
107.493107.493
WECLTFEXP_WEC->PJM
CLTF
0.6140.614
LAGNLTFEXP_LAGN->PJM
CLTF
8.048.04

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:136.2 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3326.15
MW Contribution:17.93
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:145.97 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3564.81
MW Contribution:18.09
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933292AC2-141 E
50/50
24.37824.378
316294AC1-161 C
50/50
9.3329.332
944602AF1-125 E
50/50
179.158179.158
916191Z1-068 C
50/50
0.0760.076
3145506HICKORY
50/50
3.8083.808
934576AD1-082 E
Adder
5.9741176470588245.078
957871AF2-081 C
50/50
17.30217.302
943612AF1-032 E
50/50
1.5651.565
3130536PAPERMILL
Adder
9.9929411764705888.494
939602AE1-190 E
Adder
2.1164705882352941.799
940492AE2-034 E
Adder
4.8058823529411764.085
934522AD1-076 E
Adder
9.4435294117647068.027
936591AD2-074 C
Adder
7.8788235294117656.697
943172AE2-346 E
Adder
0.85647058823529410.728
918492AA1-063AE OP
Adder
5.464705882352944.645
917332KELFORD E
Adder
2.25294117647058821.915
925122AB2-169 E
Adder
8.1847058823529426.957
926755AC1-161 E
50/50
24.37824.378
933291AC2-141 C
50/50
57.10857.108
925522AC1-027 E
50/50
2.1192.119
944631AF1-128 C
Adder
31.06000000000000226.401
3151161SURRY 1
50/50
37.9237.92
957872AF2-081 E
50/50
7.4157.415
3145256KINGFORK
50/50
1.7041.704
3150921YORKTN3
50/50
212.818212.818
316305AF2-043 C
50/50
0.590.59
316160AE1-175 E
50/50
2.0532.053
941102AE2-104 E
50/50
8.7058.705
936592AD2-074 E
Adder
12.85529411764705910.927
926214AC1-099 E
Adder
1.56235294117647071.328
932632AC2-084 E
Adder
4.183.553
316036AC1-147 C
50/50
0.6390.639
924814AB2-134 E
Adder
17.2517647058823514.664
919152AA1-139 E1
50/50
7.0757.075
316018AA1-139 ULT2
50/50
1.8731.873
942342AE2-247 E
Adder
3.142.669
920042AA2-088 E OP
Adder
15.25058823529411712.963
934511AD1-075 C
Adder
12.75411764705882310.841
934521AD1-076 C
Adder
18.52705882352941215.748
3145723EMPORIA
Adder
0.53411764705882360.454
939246AE1-155 E
Adder
12.06941176470588310.259
923573AB1-173 E OP
Adder
4.1152941176470593.498
919692AA2-053 E OP
Adder
5.50588235294117644.68
3150981CHESPKA
50/50
0.7560.756
944581AF1-123 C
50/50
79.48679.486
316185AD1-033 C
50/50
2.1522.152
941101AE2-104 C
50/50
5.4755.475
316320Y1-086 C
50/50
0.3740.374
934392AD1-063 E
Adder
1.61529411764705881.373
943742AF1-042 E
Adder
6.7258823529411765.717
962862AG1-135 E
Adder
5.63764705882352954.792
966662AG1-536 E
Adder
10.0188235294117658.516
316088AB2-174 E
Adder
8.1305882352941186.911
316141AB2-099 E
Adder
0.35647058823529410.303
923994AB2-040_E
Adder
7.7152941176470586.558
939191AE1-149 C
Adder
13.30705882352941111.311
316159AE1-175 C
50/50
0.6760.676
901082W1-029 E
50/50
53.16253.162
934146AD1-041 E
Adder
5.2917647058823534.498
957601AF2-054 C
Adder
3.1929411764705882.714
958261AF2-120 C
Adder
8.6682352941176477.368
926206AC1-098 E
Adder
4.72941176470588154.02
940642AE2-051 E
50/50
16.6416.64
316388AE2-253 GEN
50/50
3.4133.413
919153AA1-139 E2
50/50
7.0757.075
943462AF1-017 E
Adder
3.35647058823529452.853
942341AE2-247 C
Adder
2.2741176470588241.933
316246AF1-032 C
50/50
0.4820.482
316382AG1-145 C
50/50
0.610.61
958162AF2-110 E
50/50
3.5543.554
924516AB2-100 E1
Adder
3.61411764705882373.072
934512AD1-075 E
Adder
6.4917647058823525.518
934502AD1-074 E
Adder
25.96941176470588522.074
966621AG1-532 C
Adder
1.72705882352941181.468
918512AA1-065 E OP
Adder
7.9635294117647066.769
963612AG1-210 E
Adder
1.35529411764705881.152
918532AA1-067 E
Adder
0.94588235294117650.804
944011AF1-069 C
Adder
17.03647058823529314.481
3151091ELIZAR2
50/50
5.4685.468
3151081ELIZAR1
50/50
5.5655.565
941591AE2-156 C
50/50
31.07431.074
925332AB2-190 E
Adder
10.335294117647068.785
944591AF1-124 C
50/50
79.76979.769
944601AF1-125 C
50/50
78.26278.262
316316AC1-027 C
50/50
0.550.55
927226AC1-216 E
Adder
10.5317647058823528.952
3150601CHESTF5
Adder
72.936470588235361.996
936666AD2-085 E
Adder
8.5588235294117647.275
962962AG1-145 E
50/50
2.4882.488
963041AG1-153 C
Adder
7.1717647058823536.096
938771AE1-103 C
Adder
4.5305882352941173.851
3145413WATKINS
Adder
1.03764705882352940.882
960081AF2-299 C
Adder
2.3023529411764711.957
964212AG1-282 E
Adder
1.84352941176470591.567
926072AC1-086 E
Adder
12.19176470588235310.363
939412AE1-173 E
50/50
91.51291.512
941032AE2-094 E
Adder
23.3529411764705919.85
941031AE2-094 C
Adder
52.14117647058823544.32
926662AC1-147 E
50/50
2.2972.297
916192Z1-068 E
50/50
3.2743.274
316076AC2-137 E
Adder
1.64117647058823551.395
957492AF2-043 E
50/50
2.4072.407
923852AB2-025 E
Adder
1.42470588235294131.211
923842AB2-024 E
Adder
2.7035294117647062.298
316157AD2-030 E
Adder
1.7917647058823531.523
964211AG1-282 C
Adder
2.76588235294117672.351
961941AG1-037 C
Adder
0.71294117647058820.606
961942AG1-037 E
Adder
0.475294117647058870.404
3151101ELIZAR3
50/50
5.6365.636
944582AF1-123 E
50/50
182.015182.015
944592AF1-124 E
50/50
182.674182.674
3144216WINCHST
50/50
0.2310.231
935112AD1-144 E
50/50
1.5821.582
316349AD2-085 C
Adder
5.2458823529411764.459
316169AC1-164 GEN
50/50
61.5761.57
923832AB2-022 E
50/50
2.1082.108
963042AG1-153 E
Adder
10.757647058823539.144
938772AE1-103 E
Adder
6.257647058823535.319
916042Z1-036 E
50/50
46.21946.219
946281AF1-292 C
Adder
1.90588235294117661.62
960082AF2-299 E
Adder
1.53529411764705871.305
926071AC1-086 C
Adder
26.78823529411764822.77
3152331SURRY 2
50/50
50.93450.934
935162AD1-151 E
Adder
14.19058823529411712.062
938532AE1-072 E
50/50
15.80515.805
3146326AYDLETT TAP
50/50
2.3362.336
943461AF1-017 C
Adder
2.05764705882352941.749
316311AC2-079 C
Adder
8.827.497
932596AC2-079 E
Adder
14.39058823529411812.232
917122Z2-027 E
50/50
2.2672.267
3156056W1-029WIND
50/50
1.2961.296
957832AF2-077 E
50/50
2.3562.356
940551AE2-041 C
Adder
10.7682352941176489.153
920692AA2-178 E
Adder
6.4070588235294125.446
966622AG1-532 E
Adder
1.1517647058823530.979
932046AC2-012 E
50/50
22.72422.724
935161AD1-151 C
Adder
21.28588235294117618.093
316017AA1-139 ULT1
50/50
1.8731.873
938531AE1-072 C
50/50
30.31830.318
958161AF2-110 C
50/50
2.2342.234
3145393UNCAMP
Adder
9.2964705882352947.902
933981AD1-022 C
Adder
13.0952941176470611.131
900672V4-068 E
Adder
0.50705882352941180.431
940641AE2-051 C
50/50
24.9624.96
316084AB2-161 E
Adder
7.497647058823536.373
316072AD1-144 C
50/50
0.4730.473
926785AC1-164_E
50/50
27.66227.662
943471AF1-018 C
Adder
10.7682352941176489.153
3145946PLYMOUTH TP
Adder
0.491764705882352940.418
933982AD1-022 E
Adder
7.1294117647058826.06
939192AE1-149 E
Adder
8.8705882352941187.54
3150991CHESPKB
50/50
1.2531.253
934065AD1-033 E
50/50
8.788.78
939312AE1-162 E
50/50
2.3092.309
937226AE2-253 E
50/50
10.1510.15
316321Z2-027 C
50/50
0.6140.614
924517AB2-100 E2
Adder
3.61411764705882373.072
934501AD1-074 C
Adder
51.01411764705882543.362
943741AF1-042 C
Adder
4.122352941176473.504
962861AG1-135 C
Adder
8.4564705882352957.188
3141813NORNECK
Adder
1.20352941176470571.023
939411AE1-173 C
50/50
137.269137.269
934012AD1-025 E
Adder
13.63529411764705811.59
913392Y1-086 E
50/50
3.7343.734
939612AE1-191 E
Adder
8.4670588235294127.197
3156116Z1-036WIND
50/50
1.0631.063
957602AF2-054 E
Adder
2.12823529411764721.809
966661AG1-536 C
Adder
7.4564705882352956.338
958262AF2-120 E
Adder
5.7788235294117654.912
316078AC2-138 E
Adder
1.26470588235294111.075
3137643SOCKMAN
Adder
0.90352941176470590.768
944012AF1-069 E
Adder
6.6188235294117655.626
925865AC1-065 E
Adder
24.48470588235294420.812
961951AG1-038 C
Adder
4.5564705882352943.873
961952AG1-038 E
Adder
6.2929411764705885.349
946282AF1-292 E
Adder
1.27058823529411781.08
316375AC2-012 C
50/50
2.3432.343
316236AE1-162 C
50/50
0.5660.566
961611AG1-000B C
Adder
23.74470588235294220.183
3138116ELKO L286
Adder
1.71058823529411771.454
313526AB2-022 C
50/50
0.640.64
940541AE2-040 C
Adder
3.5223529411764712.994
940482AE2-033 E
Adder
13.4152941176470611.403
940481AE2-033 C
Adder
19.89882352941176816.914
957831AF2-077 C
50/50
0.5460.546
963611AG1-210 C
Adder
0.90352941176470590.768
923263AB1-132 E OP
Adder
7.79647058823529456.627
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.6520.652
MECLTFEXP_MEC->PJM
CLTF
2.4842.484
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.8765.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.55415.554
G-007PJM->LTFIMP_G-007
CMTX_NF
3.3653.365
CPLELTFEXP_CPLE->PJM
CLTF
12.33712.337
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69696.696
WECLTFEXP_WEC->PJM
CLTF
0.3380.338
LAGNLTFEXP_LAGN->PJM
CLTF
6.3726.372
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.85316.853
NYPJM->LTFIMP_NY
CLTF
1.6271.627
TVALTFEXP_TVA->PJM
CLTF
4.9324.932
O66PJM->LTFIMP_O-066
CMTX_NF
21.46821.468

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4713.58
MW Contribution:19.2
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:137.16 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5582.72
MW Contribution:20.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
938552AE1-074 E
Adder
1.90000000000000011.615
926755AC1-161 E
50/50
22.27722.277
933291AC2-141 C
50/50
52.18752.187
925522AC1-027 E
Adder
2.05294117647058851.745
944631AF1-128 C
50/50
67.28467.284
957872AF2-081 E
Adder
7.1717647058823536.096
3145256KINGFORK
Adder
1.70470588235294131.449
3150921YORKTN3
50/50
208.205208.205
316160AE1-175 E
50/50
2.0922.092
316312AB1-027 C
50/50
0.8920.892
941102AE2-104 E
Adder
8.815294117647067.493
936592AD2-074 E
Adder
13.95176470588235211.859
316240AF1-291 C
Adder
3.5117647058823532.985
944641AF1-129 C
Adder
166.98352941176472141.936
924814AB2-134 E
Adder
21.28941176470588218.096
3150641CHESTS8
50/50
3.3243.324
919152AA1-139 E1
Adder
6.8435294117647065.817
942342AE2-247 E
Adder
3.39176470588235322.883
920042AA2-088 E OP
Adder
16.25647058823529513.818
934511AD1-075 C
Adder
13.12352941176470511.155
934521AD1-076 C
Adder
19.0647058823529416.205
3145723EMPORIA
Adder
0.61764705882352940.525
939246AE1-155 E
Adder
13.111.135
923573AB1-173 E OP
Adder
4.7082352941176474.002
933292AC2-141 E
50/50
22.27722.277
316294AC1-161 C
50/50
8.5288.528
946262AF1-291 E
Adder
2.34117647058823541.99
3150651CHESTF6
Adder
30.4035294117647125.843
944602AF1-125 E
Adder
172.25764705882355146.419
3145506HICKORY
Adder
3.66705882352941173.117
934576AD1-082 E
Adder
7.1941176470588246.115
957871AF2-081 C
Adder
16.73529411764705814.225
943612AF1-032 E
Adder
1.54117647058823541.31
3130536PAPERMILL
Adder
11.0400000000000019.384
939602AE1-190 E
Adder
2.33764705882352961.987
940492AE2-034 E
Adder
4.8823529411764714.15
934522AD1-076 E
Adder
9.7164705882352948.259
936591AD2-074 C
Adder
8.5505882352941187.268
943172AE2-346 E
Adder
0.91294117647058830.776
918492AA1-063AE OP
Adder
6.0129411764705885.111
917332KELFORD E
Adder
2.43058823529411772.066
925122AB2-169 E
Adder
8.6200000000000017.327
942002AE2-212 E
Adder
2.31764705882352961.97
940431AE2-027 C
Adder
21.05411764705882417.896
944581AF1-123 C
Adder
76.4247058823529464.961
941101AE2-104 C
Adder
5.5447058823529414.713
934392AD1-063 E
Adder
1.77411764705882361.508
943742AF1-042 E
Adder
7.3000000000000016.205
962862AG1-135 E
Adder
6.1188235294117645.201
966662AG1-536 E
Adder
10.8741176470588249.243
316088AB2-174 E
Adder
9.3494117647058837.947
316141AB2-099 E
Adder
0.380.323
923994AB2-040_E
Adder
8.8282352941176477.504
3143316POE
Adder
2.15411764705882371.831
939191AE1-149 C
Adder
17.43176470588235514.817
316159AE1-175 C
50/50
0.6890.689
901082W1-029 E
Adder
52.4682352941176544.598
934146AD1-041 E
Adder
5.8435294117647054.967
957601AF2-054 C
Adder
3.4647058823529412.945
958261AF2-120 C
Adder
9.4070588235294137.996
940642AE2-051 E
Adder
16.92588235294117614.387
3150681DARBY 2
50/50
4.2574.257
919153AA1-139 E2
Adder
6.8435294117647065.817
943462AF1-017 E
Adder
3.62470588235294143.081
942341AE2-247 C
Adder
2.4552941176470592.087
316382AG1-145 C
50/50
0.6220.622
926412AC1-112 E
50/50
1.9031.903
958162AF2-110 E
Adder
3.5988235294117653.059
924516AB2-100 E1
Adder
4.20352941176470553.573
934512AD1-075 E
Adder
6.685.678
934502AD1-074 E
Adder
26.72117647058823722.713
966621AG1-532 C
Adder
2.00705882352941161.706
918512AA1-065 E OP
Adder
8.397647058823537.138
963612AG1-210 E
Adder
1.47058823529411781.25
944011AF1-069 C
Adder
18.02352941176470615.32
941591AE2-156 C
Adder
30.2317647058823525.697
925332AB2-190 E
Adder
13.54588235294117611.514
944591AF1-124 C
Adder
76.6964705882352965.192
944601AF1-125 C
Adder
75.2470588235294163.96
927226AC1-216 E
Adder
12.9976470588235311.048
3150601CHESTF5
50/50
107.532107.532
936666AD2-085 E
Adder
9.244705882352947.858
962962AG1-145 E
50/50
2.5352.535
963041AG1-153 C
Adder
7.67882352941176556.527
938771AE1-103 C
Adder
4.6882352941176473.985
3145413WATKINS
Adder
1.08705882352941190.924
960081AF2-299 C
Adder
2.6764705882352942.275
964212AG1-282 E
Adder
2.01294117647058851.711
944582AF1-123 E
Adder
175.0035294117647148.753
944592AF1-124 E
Adder
175.63764705882355149.292
3150631CHESTG8
50/50
6.4576.457
3144216WINCHST
50/50
0.2290.229
935112AD1-144 E
Adder
1.58235294117647051.345
316349AD2-085 C
Adder
5.6658823529411774.816
930122AB1-027 E
50/50
2.342.34
316169AC1-164 GEN
50/50
71.02671.026
923832AB2-022 E
Adder
2.0588235294117651.75
963042AG1-153 E
Adder
11.517647058823539.79
938772AE1-103 E
Adder
6.4741176470588245.503
916042Z1-036 E
Adder
46.2035294117647139.273
946281AF1-292 C
Adder
2.2152941176470591.883
960082AF2-299 E
Adder
1.78470588235294111.517
926071AC1-086 C
Adder
8.492941176470597.219
316233AE1-074 C
Adder
3.7705882352941183.205
3152331SURRY 2
50/50
44.51344.513
935162AD1-151 E
Adder
18.0752941176470615.364
3150691DARBY 3
50/50
4.2724.272
938532AE1-072 E
Adder
15.31411764705882413.017
3146326AYDLETT TAP
Adder
2.26588235294117621.926
943461AF1-017 C
Adder
2.2223529411764711.889
316311AC2-079 C
Adder
9.4458823529411768.029
932596AC2-079 E
Adder
15.41176470588235313.1
917122Z2-027 E
Adder
2.22117647058823531.888
957832AF2-077 E
Adder
2.41411764705882352.052
927042AC1-191 E
Adder
7.4741176470588236.353
940551AE2-041 C
Adder
11.82823529411764710.054
920692AA2-178 E
Adder
6.5094117647058835.533
966622AG1-532 E
Adder
1.33882352941176451.138
3150731STONECA
Adder
11.5258823529411789.797
932046AC2-012 E
Adder
22.12352941176470718.805
935161AD1-151 C
Adder
27.11411764705882623.047
3150701DARBY 4
50/50
4.2774.277
938531AE1-072 C
Adder
29.3776470588235324.971
958161AF2-110 C
Adder
2.2623529411764711.923
3145393UNCAMP
Adder
9.664705882352948.215
933981AD1-022 C
Adder
13.55882352941176611.525
900672V4-068 E
Adder
0.54235294117647060.461
940641AE2-051 C
Adder
25.38941176470588321.581
316084AB2-161 E
Adder
9.0294117647058827.675
926785AC1-164_E
50/50
31.9131.91
943471AF1-018 C
Adder
11.82823529411764710.054
3145946PLYMOUTH TP
Adder
0.50470588235294120.429
933982AD1-022 E
Adder
7.3811764705882366.274
942001AE2-212 C
Adder
3.4764705882352942.955
939192AE1-149 E
Adder
11.6211764705882359.878
934065AD1-033 E
Adder
8.4505882352941187.183
939312AE1-162 E
Adder
2.4211764705882352.058
937226AE2-253 E
Adder
9.88.33
316004AC1-112 C
50/50
0.5560.556
924517AB2-100 E2
Adder
4.20352941176470553.573
934501AD1-074 C
Adder
52.4929411764705944.619
943741AF1-042 C
Adder
4.4741176470588243.803
962861AG1-135 C
Adder
9.177647058823537.801
3141813NORNECK
Adder
1.30588235294117671.11
939411AE1-173 C
Adder
137.65882352941176117.01
940432AE2-027 E
Adder
14.03647058823529311.931
934012AD1-025 E
Adder
16.82705882352941314.303
913392Y1-086 E
Adder
3.6470588235294123.1
939612AE1-191 E
Adder
9.3494117647058837.947
957602AF2-054 E
Adder
2.31058823529411761.964
966661AG1-536 C
Adder
8.0929411764705876.879
958262AF2-120 E
Adder
6.2717647058823545.331
316078AC2-138 E
Adder
1.37294117647058831.167
944012AF1-069 E
Adder
7.0023529411764715.952
3150621CHESTS7
50/50
3.0123.012
3150611CHESTG7
50/50
6.5626.562
316075AC2-137 C
50/50
0.6540.654
925865AC1-065 E
Adder
27.3976470588235323.288
961951AG1-038 C
Adder
4.9458823529411764.204
961952AG1-038 E
Adder
6.8294117647058825.805
946282AF1-292 E
Adder
1.47764705882352951.256
3150831SPRUNCA
Adder
14.5823529411764712.395
3150841SPRUNCB
Adder
14.5823529411764712.395
939412AE1-173 E
Adder
91.772941176470678.007
941032AE2-094 E
Adder
24.70588235294117821
941031AE2-094 C
Adder
55.1635294117647146.889
926662AC1-147 E
Adder
2.2364705882352941.901
916192Z1-068 E
Adder
3.16941176470588242.694
316076AC2-137 E
50/50
2.32.3
957492AF2-043 E
Adder
2.37058823529411772.015
923852AB2-025 E
Adder
1.7117647058823531.455
966872AG1-558 E
Adder
1.88235294117647081.6
966871AG1-558 C
Adder
3.73647058823529443.176
923842AB2-024 E
Adder
2.99058823529411732.542
316157AD2-030 E
Adder
1.94470588235294131.653
964211AG1-282 C
Adder
3.02000000000000052.567
961941AG1-037 C
Adder
0.76117647058823530.647
961942AG1-037 E
Adder
0.50705882352941180.431
961611AG1-000B C
Adder
26.9129411764705922.876
3138116ELKO L286
50/50
2.3992.399
940541AE2-040 C
Adder
4.2317647058823533.597
940482AE2-033 E
Adder
16.0529411764705913.645
940481AE2-033 C
Adder
23.8117647058823520.24
927041AC1-191 C
Adder
15.00352941176470612.753
963611AG1-210 C
Adder
0.980.833
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.912122.912
WECLTFEXP_WEC->PJM
CLTF
0.9390.939
LAGNLTFEXP_LAGN->PJM
CLTF
10.28110.281
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.55730.557
NYPJM->LTFIMP_NY
CLTF
3.1153.115
TVALTFEXP_TVA->PJM
CLTF
8.1358.135
O66PJM->LTFIMP_O-066
CMTX_NF
43.443.4
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.3345.33
G-007PJM->LTFIMP_G-007
CMTX_NF
6.8256.825
CPLELTFEXP_CPLE->PJM
CLTF
14.714.7
SIGELTFEXP_SIGE->PJM
CLTF
0.3490.349
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.8191.819
MECLTFEXP_MEC->PJM
CLTF
5.5435.543
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.017.01

Details for 8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN N ANNA-KRAKEN_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN N ANNA-KRAKEN_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.4 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3458.62
MW Contribution:10.85
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3143316POE
Adder
1.23411764705882351.049
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
Adder
28.4624.191
934146AD1-041 E
Adder
3.2635294117647062.774
957601AF2-054 C
Adder
1.93529411764705881.645
3150401LDYSMT4
50/50
4.714.71
958261AF2-120 C
Adder
5.5129411764705884.686
944011AF1-069 C
Adder
10.1705882352941178.645
941591AE2-156 C
Adder
16.31294117647058813.866
925332AB2-190 E
Adder
7.6082352941176476.467
944591AF1-124 C
Adder
41.3152941176470635.118
944601AF1-125 C
Adder
40.53529411764705534.455
927226AC1-216 E
Adder
7.2470588235294126.16
3150601CHESTF5
Adder
60.84352941176470651.717
936666AD2-085 E
Adder
5.0894117647058824.326
962962AG1-145 E
Adder
1.36470588235294121.16
963041AG1-153 C
Adder
4.3411764705882353.69
938771AE1-103 C
Adder
2.5717647058823532.186
3145413WATKINS
Adder
0.59882352941176480.509
966881AG1-559 C
50/50
2.4312.431
960081AF2-299 C
Adder
1.51411764705882361.287
964212AG1-282 E
Adder
1.1835294117647061.006
944582AF1-123 E
Adder
94.272941176470680.132
944592AF1-124 E
Adder
94.6141176470588280.422
935112AD1-144 E
Adder
0.85882352941176470.73
316349AD2-085 C
Adder
3.122.652
930122AB1-027 E
50/50
1.3631.363
316169AC1-164 GEN
Adder
38.76588235294117632.951
923832AB2-022 E
Adder
1.11411764705882340.947
963042AG1-153 E
Adder
6.5117647058823535.535
938772AE1-103 E
Adder
3.55058823529411743.018
916042Z1-036 E
Adder
25.1621.386
966882AG1-559 E
50/50
1.2241.224
939261AE1-157 C
50/50
14.14114.141
946281AF1-292 C
Adder
1.25294117647058821.065
960082AF2-299 E
Adder
1.00941176470588250.858
3150391LDYSMT3
50/50
4.7014.701
926071AC1-086 C
Adder
4.4835294117647063.811
940642AE2-051 E
Adder
9.4270588235294128.013
919153AA1-139 E2
Adder
3.6929411764705883.139
943462AF1-017 E
Adder
1.99647058823529421.697
942341AE2-247 C
Adder
1.3517647058823531.149
926412AC1-112 E
50/50
1.1081.108
958162AF2-110 E
Adder
1.961.666
924516AB2-100 E1
Adder
2.37411764705882342.018
934512AD1-075 E
Adder
3.6682352941176473.118
934502AD1-074 E
Adder
14.67411764705882512.473
966621AG1-532 C
Adder
1.13529411764705880.965
918512AA1-065 E OP
Adder
4.6411764705882353.945
963612AG1-210 E
Adder
0.8717647058823530.741
316233AE1-074 C
Adder
2.2647058823529411.925
935162AD1-151 E
Adder
10.1176470588235298.6
3150691DARBY 3
50/50
2.5052.505
938532AE1-072 E
Adder
8.2670588235294127.027
3146326AYDLETT TAP
Adder
1.2235294117647061.04
943461AF1-017 C
Adder
1.2235294117647061.04
316311AC2-079 C
Adder
5.1941176470588244.415
932596AC2-079 E
Adder
8.4741176470588247.203
917122Z2-027 E
Adder
1.20352941176470571.023
957832AF2-077 E
Adder
1.321.122
3150481FOUR RIVERF
50/50
3.7933.793
315051AA1-145 CT1
50/50
5.025.02
927042AC1-191 E
Adder
4.6929411764705893.989
940551AE2-041 C
Adder
6.585.593
920692AA2-178 E
Adder
3.56117647058823563.027
966622AG1-532 E
Adder
0.75647058823529410.643
3150381LDYSMT2
50/50
4.584.58
3150731STONECA
Adder
6.54705882352941255.565
932046AC2-012 E
Adder
11.9410.149
935161AD1-151 C
Adder
15.17647058823529512.9
3150701DARBY 4
50/50
2.5082.508
938531AE1-072 C
Adder
15.85882352941176513.48
958161AF2-110 C
Adder
1.23176470588235291.047
3145393UNCAMP
Adder
5.30941176470588254.513
933981AD1-022 C
Adder
7.457647058823536.339
900672V4-068 E
Adder
0.30.255
316240AF1-291 C
Adder
2.03764705882352941.732
944641AF1-129 C
Adder
97.016470588235382.464
924814AB2-134 E
Adder
11.87058823529411810.09
919152AA1-139 E1
Adder
3.6929411764705883.139
942342AE2-247 E
Adder
1.86705882352941191.587
920042AA2-088 E OP
Adder
8.9988235294117667.649
934511AD1-075 C
Adder
7.2058823529411776.125
934521AD1-076 C
Adder
10.4682352941176488.898
3145723EMPORIA
Adder
0.349411764705882370.297
939246AE1-155 E
Adder
7.6764705882352946.525
923573AB1-173 E OP
Adder
2.65529411764705922.257
939411AE1-173 C
Adder
76.0247058823529364.621
940432AE2-027 E
Adder
8.097647058823536.883
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
Adder
1.97294117647058841.677
3150451FOUR RIVERC
50/50
3.853.85
939612AE1-191 E
Adder
5.2223529411764714.439
957602AF2-054 E
Adder
1.29058823529411761.097
933502AC2-165 E
Adder
5.9823529411764715.085
966661AG1-536 C
Adder
4.742352941176474.031
958262AF2-120 E
Adder
3.67529411764705933.124
316078AC2-138 E
Adder
0.81411764705882350.692
938552AE1-074 E
Adder
1.14117647058823520.97
926755AC1-161 E
Adder
11.85176470588235310.074
933291AC2-141 C
Adder
27.76352941176470823.599
925522AC1-027 E
Adder
1.10705882352941170.941
944631AF1-128 C
Adder
38.0705882352941232.36
940641AE2-051 C
Adder
14.1412.019
316084AB2-161 E
Adder
5.0552941176470584.297
926785AC1-164_E
Adder
17.41647058823529514.804
943471AF1-018 C
Adder
6.585.593
316336AC2-165 C
Adder
7.9482352941176486.756
3145946PLYMOUTH TP
Adder
0.276470588235294130.235
933982AD1-022 E
Adder
4.06000000000000053.451
944012AF1-069 E
Adder
3.95058823529411773.358
3150431FOUR RIVERA
50/50
3.1513.151
925865AC1-065 E
Adder
15.30588235294117713.01
939262AE1-157 E
50/50
7.677.67
961951AG1-038 C
Adder
2.86235294117647052.433
961952AG1-038 E
Adder
3.95294117647058843.36
946282AF1-292 E
Adder
0.83529411764705890.71
3150831SPRUNCA
Adder
8.6470588235294117.35
3150841SPRUNCB
Adder
8.6470588235294117.35
939412AE1-173 E
Adder
50.6835294117647143.081
941032AE2-094 E
Adder
13.94000000000000111.849
941031AE2-094 C
Adder
31.1258823529411826.457
926662AC1-147 E
Adder
1.20705882352941171.026
916192Z1-068 E
Adder
1.70941176470588241.453
316076AC2-137 E
Adder
1.28941176470588251.096
957492AF2-043 E
Adder
1.28352941176470581.091
923852AB2-025 E
Adder
0.97058823529411760.825
966872AG1-558 E
Adder
1.18235294117647041.005
966871AG1-558 C
Adder
2.34588235294117631.994
923842AB2-024 E
Adder
1.66000000000000011.411
923862AB2-026 E
Adder
1.00352941176470580.853
316157AD2-030 E
Adder
1.08588235294117650.923
964211AG1-282 C
Adder
1.77411764705882361.508
961941AG1-037 C
Adder
0.42235294117647060.359
961942AG1-037 E
Adder
0.28117647058823530.239
933292AC2-141 E
Adder
11.85176470588235310.074
946262AF1-291 E
Adder
1.35764705882352941.154
3150651CHESTF6
Adder
17.66352941176470615.014
944602AF1-125 E
Adder
92.7929411764705978.874
3145506HICKORY
Adder
1.97647058823529421.68
934576AD1-082 E
Adder
4.0270588235294123.423
957871AF2-081 C
Adder
9.0294117647058827.675
943612AF1-032 E
Adder
0.83411764705882350.709
3150441FOUR RIVERB
50/50
3.1513.151
3130536PAPERMILL
Adder
6.1294117647058835.21
939602AE1-190 E
Adder
1.30588235294117671.11
940492AE2-034 E
Adder
2.6705882352941182.27
934522AD1-076 E
Adder
5.3364705882352944.536
936591AD2-074 C
Adder
4.9494117647058824.207
943172AE2-346 E
Adder
0.50588235294117640.43
918492AA1-063AE OP
Adder
3.35882352941176482.855
942002AE2-212 E
Adder
1.33882352941176451.138
940431AE2-027 C
Adder
12.14705882352941110.325
944581AF1-123 C
Adder
41.16941176470588534.994
941101AE2-104 C
Adder
3.02000000000000052.567
3150461FOUR RIVERD
50/50
3.1063.106
934392AD1-063 E
Adder
0.98705882352941180.839
943742AF1-042 E
Adder
4.2258823529411773.592
962862AG1-135 E
Adder
3.5752941176470593.039
966662AG1-536 E
Adder
6.3717647058823535.416
316088AB2-174 E
Adder
5.2764705882352954.485
316141AB2-099 E
Adder
0.210588235294117630.179
923994AB2-040_E
Adder
4.9776470588235294.231
3142366NRTHEST
50/50
0.1810.181
961611AG1-000B C
Adder
14.83882352941176412.613
3138116ELKO L286
Adder
1.34470588235294121.143
940541AE2-040 C
Adder
2.40117647058823552.041
940482AE2-033 E
Adder
9.1023529411764727.737
940481AE2-033 C
Adder
13.50235294117647211.477
927041AC1-191 C
Adder
9.428.007
3150371LDYSMT1
50/50
4.5224.522
963611AG1-210 C
Adder
0.58117647058823530.494
957872AF2-081 E
Adder
3.86941176470588263.289
3145256KINGFORK
Adder
0.92470588235294130.786
3150921YORKTN3
Adder
111.7541176470588294.991
316160AE1-175 E
Adder
1.12588235294117660.957
316312AB1-027 C
50/50
0.520.52
941102AE2-104 E
Adder
4.8011764705882364.081
315052AA1-145 CT2
50/50
5.0185.018
938562AE1-075 E
Adder
0.85529411764705890.727
936592AD2-074 E
Adder
8.0764705882352946.865
3150411LDYSMT5
50/50
4.7244.724
934782AD1-105 E
Adder
4.277647058823533.636
942001AE2-212 C
Adder
2.0082352941176471.707
939192AE1-149 E
Adder
6.585.593
934065AD1-033 E
Adder
4.5529411764705883.87
939312AE1-162 E
Adder
1.321.122
937226AE2-253 E
Adder
5.2858823529411774.493
3142296MT RD221
50/50
0.1210.121
316004AC1-112 C
50/50
0.3240.324
3150471FOUR RIVERE
50/50
3.1063.106
958502AF2-144 E
Adder
0.98588235294117640.838
924517AB2-100 E2
Adder
2.37411764705882342.018
934501AD1-074 C
Adder
28.82588235294117524.502
943741AF1-042 C
Adder
2.5905882352941182.202
962861AG1-135 C
Adder
5.36235294117647054.558
3141813NORNECK
Adder
0.77411764705882360.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.83518.835
NYPJM->LTFIMP_NY
CLTF
2.4112.411
TVALTFEXP_TVA->PJM
CLTF
4.9434.943
O66PJM->LTFIMP_O-066
CMTX_NF
34.15334.153
CBM South 2LTFEXP_CBM-S2->PJM
CBM
71.47471.474
WECLTFEXP_WEC->PJM
CLTF
0.6070.607
LAGNLTFEXP_LAGN->PJM
CLTF
6.236.23
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.1741.174
MECLTFEXP_MEC->PJM
CLTF
3.5063.506
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.0244.024
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.37329.373
G-007PJM->LTFIMP_G-007
CMTX_NF
5.3775.377
CPLELTFEXP_CPLE->PJM
CLTF
8.4398.439
SIGELTFEXP_SIGE->PJM
CLTF
0.2230.223

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.34 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1336.88
MW Contribution:9.18
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.16 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1345.51
MW Contribution:9.02
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926755AC1-161 E
Adder
5.7376470588235294.877
933291AC2-141 C
Adder
13.44235294117647211.426
925522AC1-027 E
Adder
0.50.425
957872AF2-081 E
Adder
1.79882352941176471.529
3145256KINGFORK
Adder
0.367058823529411770.312
941102AE2-104 E
Adder
2.06588235294117651.756
964242AG1-285 E
Adder
3.57647058823529433.04
919152AA1-139 E1
Adder
1.71529411764705891.458
942342AE2-247 E
Adder
0.69411764705882350.59
920042AA2-088 E OP
Adder
4.3847058823529413.727
934511AD1-075 C
Adder
3.55411764705882363.021
934521AD1-076 C
Adder
5.1635294117647064.389
3145723EMPORIA
Adder
0.18470588235294120.157
923573AB1-173 E OP
Adder
1.40588235294117661.195
919692AA2-053 E OP
Adder
1.80705882352941181.536
925785AC1-054 E
Adder
1.47764705882352951.256
959311AF2-222 C
Adder
5.57411764705882454.738
316263AC1-034 C
Adder
2.91411764705882352.477
933292AC2-141 E
Adder
5.7376470588235294.877
944602AF1-125 E
Adder
43.0952941176470636.631
3145506HICKORY
Adder
0.91764705882352950.78
957871AF2-081 C
Adder
4.1964705882352953.567
943612AF1-032 E
Adder
0.374117647058823550.318
940492AE2-034 E
Adder
1.2952941176470591.101
934522AD1-076 E
Adder
2.6317647058823532.237
943172AE2-346 E
Adder
0.255294117647058840.217
918492AA1-063AE OP
Adder
1.72705882352941181.468
944581AF1-123 C
Adder
19.11999999999999716.252
941101AE2-104 C
Adder
1.31.105
3151041BRUNSWICKG3
50/50
5.4215.421
3151021BRUNSWICKG1
50/50
5.4215.421
957481AF2-042 C
Adder
28.3424.089
316088AB2-174 E
Adder
2.7941176470588242.375
316141AB2-099 E
Adder
0.107058823529411760.091
923994AB2-040_E
Adder
2.63647058823529432.241
924322AB2-079 E O1
Adder
0.54823529411764720.466
961672AG1-007 E
Adder
0.232941176470588260.198
943902AF1-058 E
Adder
0.55294117647058830.47
901082W1-029 E
Adder
13.19764705882352911.218
926206AC1-098 E
Adder
1.57411764705882361.338
964791AG1-342 C
Adder
1.48470588235294131.262
940642AE2-051 E
50/50
7.6927.692
919153AA1-139 E2
Adder
1.71529411764705891.458
943462AF1-017 E
Adder
0.74117647058823530.63
942341AE2-247 C
Adder
0.50235294117647060.427
958162AF2-110 E
Adder
0.84352941176470590.717
924516AB2-100 E1
Adder
1.25176470588235311.064
934512AD1-075 E
Adder
1.80941176470588251.538
934502AD1-074 E
Adder
7.237647058823536.152
966621AG1-532 C
Adder
0.60117647058823530.511
918512AA1-065 E OP
Adder
2.34000000000000031.989
3147223TWITTYS
Adder
0.332941176470588240.283
959312AF2-222 E
Adder
3.73411764705882383.174
924022AB2-043 E O1
Adder
2.11764705882352941.8
918532AA1-067 E
Adder
0.30941176470588240.263
936161AD2-022 C
Adder
3.0882352941176472.625
944011AF1-069 C
50/50
8.8768.876
941591AE2-156 C
Adder
7.202352941176476.122
944591AF1-124 C
Adder
19.18823529411764616.31
944601AF1-125 C
Adder
18.82588235294117516.002
936666AD2-085 E
Adder
1.89058823529411771.607
963041AG1-153 C
50/50
3.6733.673
938771AE1-103 C
Adder
1.16941176470588240.994
3145413WATKINS
Adder
0.279999999999999970.238
960081AF2-299 C
Adder
0.80117647058823540.681
926072AC1-086 E
Adder
4.11294117647058853.496
936261AD2-033 C
Adder
4.2364705882352943.601
962562AG1-105 E
Adder
2.4729411764705882.102
936171AD2-023 C
Adder
1.80117647058823521.531
944582AF1-123 E
Adder
43.7823529411764837.215
944592AF1-124 E
Adder
43.9411764705882437.35
935112AD1-144 E
Adder
0.339999999999999970.289
316349AD2-085 C
Adder
1.15882352941176480.985
923832AB2-022 E
Adder
0.51764705882352950.44
963042AG1-153 E
50/50
5.5095.509
938772AE1-103 E
Adder
1.61529411764705881.373
916042Z1-036 E
Adder
11.93411764705882510.144
946281AF1-292 C
Adder
0.66352941176470580.564
960082AF2-299 E
Adder
0.53411764705882360.454
926071AC1-086 C
Adder
9.037647058823537.682
964241AG1-285 C
Adder
5.3647058823529414.56
927021AC1-189 C
Adder
3.66117647058823573.112
962561AG1-105 C
Adder
3.70941176470588243.153
924152AB2-059 E OP
Adder
2.31764705882352961.97
936172AD2-023 E
Adder
0.97764705882352940.831
937482AD2-202 E
Adder
0.52588235294117650.447
917332KELFORD E
Adder
0.70117647058823530.596
925122AB2-169 E
Adder
2.4564705882352942.088
316274AC1-208 C
Adder
3.8952941176470593.311
917342Z2-044 E
Adder
0.26117647058823530.222
3151311EDGECMA
Adder
6.8129411764705895.791
941011AE2-092 C
Adder
-4.452941176470588-3.785
938532AE1-072 E
Adder
3.84235294117647053.266
3146326AYDLETT TAP
Adder
0.56823529411764710.483
943461AF1-017 C
Adder
0.454117647058823570.386
316311AC2-079 C
Adder
1.9682352941176471.673
932596AC2-079 E
Adder
3.2117647058823532.73
3152431Z1-086 GT3
50/50
7.0047.004
3152441Z1-086 ST
50/50
12.19612.196
917122Z2-027 E
Adder
0.55999999999999990.476
920692AA2-178 E
Adder
1.72705882352941181.468
966622AG1-532 E
Adder
0.40.34
922923AB1-081 E OP
Adder
1.63529411764705881.39
927264AC1-222 E
Adder
1.66470588235294131.415
932046AC2-012 E
Adder
5.2588235294117654.47
938531AE1-072 C
Adder
7.3705882352941176.265
958161AF2-110 C
Adder
0.53058823529411770.451
3152411Z1-086 GT1
50/50
7.0067.006
3152421Z1-086 GT2
50/50
7.0047.004
3145393UNCAMP
Adder
2.44352941176470572.077
933981AD1-022 C
Adder
3.73.145
900672V4-068 E
Adder
0.149411764705882360.127
924302AB2-077 E O1
Adder
0.54823529411764720.466
940641AE2-051 C
50/50
11.53811.538
316336AC2-165 C
Adder
-10.758823529411764-9.145
3145946PLYMOUTH TP
Adder
0.136470588235294120.116
933982AD1-022 E
Adder
2.01411764705882361.712
934622AD1-088 E
Adder
2.11.785
934612AD1-087 E
Adder
1.79882352941176471.529
927146AC1-208 E
Adder
1.72941176470588241.47
927255AC1-221 E
Adder
1.65176470588235281.404
934065AD1-033 E
Adder
2.10705882352941171.791
939312AE1-162 E
Adder
0.41294117647058820.351
937226AE2-253 E
Adder
2.4552941176470592.087
3151031BRUNSWICKG2
50/50
5.4215.421
924517AB2-100 E2
Adder
1.25176470588235311.064
934501AD1-074 C
Adder
14.2176470588235312.085
957482AF2-042 E
Adder
18.89411764705882416.06
934621AD1-088 C
Adder
4.3611764705882353.707
935172AD1-152 E
Adder
2.6258823529411772.232
961671AG1-007 C
Adder
0.410588235294117640.349
936162AD2-022 E
Adder
1.85294117647058831.575
939411AE1-173 C
50/50
55.12655.126
913392Y1-086 E
Adder
0.91764705882352950.78
3137643SOCKMAN
Adder
0.30470588235294120.259
919710AA2-057 E
Adder
1.72588235294117661.467
926214AC1-099 E
Adder
0.520.442
932632AC2-084 E
Adder
1.3917647058823531.183
924162AB2-060 E OP
Adder
1.71764705882352931.46
964792AG1-342 E
Adder
0.99058823529411770.842
932763AC2-100 E
Adder
1.12117647058823520.953
944012AF1-069 E
50/50
3.4483.448
946282AF1-292 E
Adder
0.44235294117647060.376
917512Z2-088 E OP1
Adder
2.1352941176470591.815
939412AE1-173 E
50/50
36.75136.751
941032AE2-094 E
50/50
12.16712.167
941031AE2-094 C
50/50
27.16527.165
926662AC1-147 E
Adder
0.53176470588235290.452
916192Z1-068 E
Adder
0.77294117647058820.657
957492AF2-043 E
Adder
0.57529411764705880.489
923852AB2-025 E
Adder
0.50705882352941180.431
3151051BRUNSWICKS1
50/50
11.26311.263
961941AG1-037 C
Adder
0.212941176470588240.181
961942AG1-037 E
Adder
0.14235294117647060.121
936262AD2-033 E
Adder
2.8247058823529412.401
934321AD1-056 C
Adder
2.72588235294117662.317
934331AD1-057 C
Adder
1.52117647058823541.293
934332AD1-057 E
Adder
0.7917647058823530.673
934322AD1-056 E
Adder
1.47882352941176461.257
927022AC1-189 E
Adder
1.8235294117647061.55
925595AC1-034 E
Adder
2.19764705882352951.868
940541AE2-040 C
Adder
1.25411764705882361.066
940482AE2-033 E
Adder
4.7611764705882354.047
940481AE2-033 C
Adder
7.0611764705882366.002
923263AB1-132 E OP
Adder
2.6305882352941182.236
925612AC1-036 E
Adder
0.30.255
924312AB2-078 E O1
Adder
0.54823529411764720.466
926274AC1-105 E
Adder
1.13764705882352950.967
938821AE1-108 C
Adder
-4.716470588235294-4.009
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0921.092
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
WECLTFEXP_WEC->PJM
CLTF
0.2390.239
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
NYPJM->LTFIMP_NY
CLTF
0.5140.514
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
O66PJM->LTFIMP_O-066
CMTX_NF
6.9576.957

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.69 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4423.71
MW Contribution:43.41
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:114.82 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4673.36
MW Contribution:43.12
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316240AF1-291 C
Adder
-1.863529411764706-1.584
944641AF1-129 C
Adder
-87.13882352941177-74.068
925785AC1-054 E
Adder
3.75647058823529443.193
959311AF2-222 C
50/50
34.76234.762
942751AE2-291 C
Adder
13.03294117647058811.078
3151041BRUNSWICKG3
50/50
25.63425.634
3151021BRUNSWICKG1
50/50
25.63425.634
957481AF2-042 C
50/50
147.496147.496
924322AB2-079 E O1
50/50
2.6052.605
946302AF1-294 E
Adder
5.377647058823534.571
943902AF1-058 E
50/50
2.7082.708
24401205PINNACLE
Adder
1.62588235294117631.382
957601AF2-054 C
Adder
-1.72-1.462
316239AB2-077 C O1
50/50
0.6390.639
935171AD1-152 C
50/50
3.2363.236
942462AE2-259 E
Adder
10.6764705882352939.075
964791AG1-342 C
50/50
7.2097.209
925997AC1-075 E
Adder
5.1705882352941174.395
3147223TWITTYS
50/50
2.0152.015
959312AF2-222 E
50/50
23.29123.291
924022AB2-043 E O1
50/50
10.1410.14
316003AC1-222 C
50/50
2.0082.008
926024AC1-080 E
Adder
1.71529411764705891.458
936161AD2-022 C
Adder
12.41176470588235310.55
944011AF1-069 C
50/50
39.18539.185
963041AG1-153 C
50/50
17.36617.366
3151531CLOVER1
50/50
32.82832.828
936261AD2-033 C
50/50
24.11624.116
3151631KERR 6
50/50
1.991.99
961791AG1-021 C
Adder
3.08941176470588232.626
962562AG1-105 E
50/50
11.97711.977
924032AB2-045 E
Adder
1.26941176470588221.079
316248AF1-058 C
50/50
0.6640.664
936171AD2-023 C
Adder
7.246.154
963042AG1-153 E
50/50
26.04926.049
3151541CLOVER2
50/50
32.52432.524
964241AG1-285 C
50/50
28.57228.572
316034AC1-036 C
50/50
0.4960.496
958212AF2-115 E
Adder
3.2894117647058822.796
962561AG1-105 C
50/50
17.96517.965
936172AD2-023 E
Adder
3.9305882352941183.341
937482AD2-202 E
50/50
2.7272.727
3151581KERR 1
50/50
0.7110.711
3151601KERR 3
50/50
1.991.99
961792AG1-021 E
Adder
2.6317647058823532.237
3152661PLYWOOD A
50/50
2.4812.481
3152431Z1-086 GT3
50/50
32.41332.413
3152441Z1-086 ST
50/50
56.44256.442
3147133PAMPLIN
50/50
1.8091.809
927264AC1-222 E
50/50
8.2018.201
938531AE1-072 C
Adder
-16.06705882352941-13.657
3152411Z1-086 GT1
50/50
32.42432.424
3152421Z1-086 GT2
50/50
32.41332.413
924302AB2-077 E O1
50/50
2.6052.605
3151621KERR 5
50/50
1.991.99
316222AC1-221 C
50/50
2.9122.912
942752AE2-291 E
Adder
8.6882352941176467.385
940641AE2-051 C
Adder
-21.288235294117648-18.095
934622AD1-088 E
50/50
11.49611.496
934611AD1-087 C
50/50
3.233.23
934612AD1-087 E
50/50
9.3199.319
3151611KERR 4
50/50
1.991.99
927255AC1-221 E
50/50
7.6147.614
942001AE2-212 C
Adder
-1.9541176470588235-1.661
3151031BRUNSWICKG2
50/50
25.63425.634
957482AF2-042 E
50/50
98.33198.331
934621AD1-088 C
50/50
23.87723.877
935172AD1-152 E
50/50
13.31413.314
946301AF1-294 C
Adder
6.3505882352941185.398
942461AE2-259 C
Adder
16.0152941176470613.613
936162AD2-022 E
Adder
7.4470588235294126.33
937481AD2-202 C
50/50
0.9370.937
3151641KERR 7
50/50
1.991.99
933291AC2-141 C
Adder
-31.96117647058824-27.167
964242AG1-285 E
50/50
19.04819.048
313527AB2-043 C
50/50
1.011.01
924162AB2-060 E OP
50/50
8.3338.333
3151591KERR 2
50/50
1.991.99
964792AG1-342 E
50/50
4.8064.806
932763AC2-100 E
50/50
5.1295.129
316283AC2-100 C
50/50
2.3312.331
944012AF1-069 E
50/50
15.22215.222
316131AB2-060 C
50/50
2.8942.894
3138533PONTONDP
Adder
1.14470588235294120.973
316118AC1-105 C
50/50
1.8951.895
941032AE2-094 E
50/50
53.71353.713
941031AE2-094 C
50/50
119.928119.928
3151051BRUNSWICKS1
50/50
53.25453.254
936262AD2-033 E
50/50
16.07816.078
958211AF2-115 C
Adder
3.86117647058823543.282
925612AC1-036 E
50/50
1.8171.817
316237AB2-079 C O1
50/50
0.6390.639
924312AB2-078 E O1
50/50
2.6052.605
316238AB2-078 C O1
50/50
0.6390.639
926274AC1-105 E
50/50
5.5465.546
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.04159.041
G-007PJM->LTFIMP_G-007
CMTX_NF
4.1284.128
CPLELTFEXP_CPLE->PJM
CLTF
19.79519.795
SIGELTFEXP_SIGE->PJM
CLTF
0.4430.443
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
2.2642.264
MECLTFEXP_MEC->PJM
CLTF
7.1897.189
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.4399.439
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.12440.124
NYPJM->LTFIMP_NY
CLTF
1.8831.883
TVALTFEXP_TVA->PJM
CLTF
10.7110.71
O66PJM->LTFIMP_O-066
CMTX_NF
26.2626.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
169.426169.426
WECLTFEXP_WEC->PJM
CLTF
1.2081.208
LAGNLTFEXP_LAGN->PJM
CLTF
13.6813.68

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.0 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2588.61
MW Contribution:16.38
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.54 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2748.4
MW Contribution:16.33
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
919152AA1-139 E1
50/50
3.8823.882
316018AA1-139 ULT2
50/50
1.0281.028
920042AA2-088 E OP
Adder
7.3835294117647066.276
934511AD1-075 C
Adder
6.2764705882352945.335
934521AD1-076 C
Adder
9.1176470588235297.75
3145723EMPORIA
Adder
0.352941176470588260.3
923573AB1-173 E OP
Adder
2.65411764705882322.256
919692AA2-053 E OP
Adder
3.30000000000000032.805
925785AC1-054 E
Adder
2.882.448
959311AF2-222 C
Adder
14.27882352941176512.137
316263AC1-034 C
Adder
5.31058823529411854.514
944581AF1-123 C
50/50
45.64445.644
316185AD1-033 C
50/50
1.2261.226
3151041BRUNSWICKG3
50/50
9.6689.668
3151021BRUNSWICKG1
50/50
9.6689.668
957481AF2-042 C
50/50
55.26355.263
316088AB2-174 E
Adder
5.3035294117647064.508
316141AB2-099 E
Adder
0.183529411764705890.156
923994AB2-040_E
Adder
4.9776470588235294.231
924322AB2-079 E O1
Adder
1.18705882352941171.009
946302AF1-294 E
Adder
2.3164705882352941.969
961672AG1-007 E
Adder
0.41882352941176470.356
943902AF1-058 E
Adder
1.11882352941176480.951
3143316POE
Adder
0.80823529411764720.687
901082W1-029 E
Adder
23.54352941176470520.012
957601AF2-054 C
Adder
-1.2505882352941176-1.063
926206AC1-098 E
Adder
2.8317647058823532.407
942462AE2-259 E
Adder
4.3564705882352943.703
964791AG1-342 C
Adder
3.09882352941176452.634
940642AE2-051 E
50/50
17.64717.647
316388AE2-253 GEN
50/50
1.8981.898
919153AA1-139 E2
50/50
3.8823.882
924516AB2-100 E1
Adder
2.3717647058823532.016
934512AD1-075 E
Adder
3.19529411764705932.716
934502AD1-074 E
Adder
12.7810.863
966621AG1-532 C
Adder
1.15411764705882350.981
918512AA1-065 E OP
Adder
3.98941176470588273.391
3147223TWITTYS
Adder
0.82823529411764710.704
959312AF2-222 E
Adder
9.5670588235294118.132
924022AB2-043 E O1
Adder
4.6082352941176473.917
918532AA1-067 E
Adder
0.54705882352941180.465
944011AF1-069 C
50/50
15.67315.673
3151091ELIZAR2
50/50
2.9782.978
3151081ELIZAR1
50/50
3.033.03
941591AE2-156 C
50/50
16.7516.75
944591AF1-124 C
50/50
45.80645.806
944601AF1-125 C
50/50
44.94144.941
316316AC1-027 C
50/50
0.3010.301
963041AG1-153 C
50/50
6.556.55
938771AE1-103 C
Adder
1.81647058823529431.544
3145413WATKINS
Adder
0.451764705882352960.384
960081AF2-299 C
Adder
1.541.309
926072AC1-086 E
Adder
7.5870588235294126.449
3151531CLOVER1
50/50
12.55212.552
936261AD2-033 C
Adder
10.7294117647058829.12
961791AG1-021 C
Adder
1.33058823529411761.131
962562AG1-105 E
Adder
5.1941176470588244.415
3151101ELIZAR3
50/50
3.0693.069
944582AF1-123 E
50/50
104.52104.52
944592AF1-124 E
50/50
104.898104.898
923832AB2-022 E
Adder
1.06823529411764720.908
963042AG1-153 E
50/50
9.8259.825
938772AE1-103 E
Adder
2.50941176470588222.133
916042Z1-036 E
Adder
21.67647058823529718.425
946281AF1-292 C
Adder
1.27411764705882361.083
960082AF2-299 E
Adder
1.02588235294117650.872
926071AC1-086 C
Adder
16.6705882352941214.17
3151541CLOVER2
50/50
12.43612.436
964241AG1-285 C
Adder
11.7588235294117649.995
958212AF2-115 E
Adder
1.41647058823529411.204
927021AC1-189 C
Adder
6.5388235294117655.558
962561AG1-105 C
Adder
7.7917647058823536.623
924152AB2-059 E OP
Adder
4.2235294117647063.59
933292AC2-141 E
50/50
37.13537.135
316294AC1-161 C
50/50
14.21614.216
944602AF1-125 E
50/50
102.879102.879
916191Z1-068 C
50/50
0.0420.042
3145506HICKORY
50/50
2.1612.161
957871AF2-081 C
50/50
9.4939.493
940492AE2-034 E
Adder
2.3152941176470591.968
934522AD1-076 E
Adder
4.6470588235294123.95
943172AE2-346 E
Adder
0.440.374
918492AA1-063AE OP
Adder
3.0882352941176472.625
937482AD2-202 E
50/50
1.0431.043
917332KELFORD E
Adder
1.2282352941176471.044
925122AB2-169 E
Adder
4.3388235294117653.688
316274AC1-208 C
Adder
7.0835294117647066.021
961792AG1-021 E
Adder
1.13294117647058810.963
917342Z2-044 E
Adder
0.475294117647058870.404
3151311EDGECMA
Adder
12.4152941176470610.553
938532AE1-072 E
50/50
8.5488.548
3146326AYDLETT TAP
Adder
1.25647058823529421.068
3152431Z1-086 GT3
50/50
12.4512.45
3152441Z1-086 ST
50/50
21.68121.681
917122Z2-027 E
Adder
1.1117647058823530.945
920692AA2-178 E
Adder
3.0870588235294122.624
966622AG1-532 E
Adder
0.76941176470588240.654
3147133PAMPLIN
Adder
0.740.629
922923AB1-081 E OP
Adder
2.9811764705882352.534
927264AC1-222 E
Adder
3.3870588235294122.879
932046AC2-012 E
50/50
12.1712.17
316017AA1-139 ULT1
50/50
1.0281.028
938531AE1-072 C
50/50
16.39816.398
3152411Z1-086 GT1
50/50
12.45512.455
3152421Z1-086 GT2
50/50
12.4512.45
3145393UNCAMP
Adder
3.8517647058823533.274
933981AD1-022 C
Adder
6.4741176470588245.503
900672V4-068 E
Adder
0.254117647058823560.216
924302AB2-077 E O1
Adder
1.18705882352941171.009
940641AE2-051 C
50/50
26.4726.47
3145946PLYMOUTH TP
Adder
0.24117647058823530.205
933982AD1-022 E
Adder
3.52470588235294142.996
934622AD1-088 E
50/50
4.4114.411
934611AD1-087 C
50/50
1.2361.236
934065AD1-033 E
50/50
5.0045.004
937226AE2-253 E
50/50
5.6435.643
3151031BRUNSWICKG2
50/50
9.6689.668
924517AB2-100 E2
Adder
2.3717647058823532.016
934501AD1-074 C
Adder
25.10470588235294221.339
957482AF2-042 E
50/50
36.84236.842
934621AD1-088 C
50/50
9.1619.161
935172AD1-152 E
Adder
5.2058823529411774.425
946301AF1-294 C
Adder
2.73529411764705932.325
942461AE2-259 C
Adder
6.5341176470588245.554
961671AG1-007 C
Adder
0.73882352941176480.628
939411AE1-173 C
50/50
86.92186.921
913392Y1-086 E
Adder
1.8917647058823531.608
3137643SOCKMAN
Adder
0.56941176470588240.484
937481AD2-202 C
50/50
0.3590.359
919710AA2-057 E
Adder
3.1364705882352942.666
926755AC1-161 E
50/50
37.13537.135
933291AC2-141 C
50/50
86.99486.994
925522AC1-027 E
50/50
1.1581.158
957872AF2-081 E
50/50
4.0684.068
964242AG1-285 E
Adder
7.846.664
926214AC1-099 E
Adder
0.93529411764705890.795
932632AC2-084 E
Adder
2.50352941176470622.128
924162AB2-060 E OP
Adder
3.78117647058823543.214
964792AG1-342 E
Adder
2.06588235294117651.756
932763AC2-100 E
Adder
2.1788235294117651.852
934612AD1-087 E
50/50
3.5653.565
927146AC1-208 E
Adder
3.14470588235294152.673
927255AC1-221 E
Adder
3.2152941176470592.733
944012AF1-069 E
50/50
6.0886.088
946282AF1-292 E
Adder
0.84941176470588230.722
3138533PONTONDP
Adder
0.49294117647058820.419
917512Z2-088 E OP1
Adder
3.83294117647058833.258
939412AE1-173 E
50/50
57.94757.947
941032AE2-094 E
50/50
21.48321.483
941031AE2-094 C
50/50
47.96747.967
926662AC1-147 E
Adder
1.23058823529411781.046
916192Z1-068 E
50/50
1.7941.794
923852AB2-025 E
Adder
0.98588235294117640.838
3151051BRUNSWICKS1
50/50
20.08620.086
961941AG1-037 C
Adder
0.367058823529411770.312
961942AG1-037 E
Adder
0.244705882352941160.208
936262AD2-033 E
Adder
7.1529411764705896.08
958211AF2-115 C
Adder
1.6635294117647061.414
934321AD1-056 C
Adder
4.99411764705882364.245
934331AD1-057 C
Adder
2.78588235294117632.368
934332AD1-057 E
Adder
1.45058823529411771.233
934322AD1-056 E
Adder
2.70941176470588242.303
927022AC1-189 E
Adder
3.25764705882352962.769
925595AC1-034 E
Adder
4.00588235294117643.405
316375AC2-012 C
50/50
1.2551.255
940541AE2-040 C
Adder
2.4364705882352942.071
940482AE2-033 E
Adder
9.2211764705882357.838
940481AE2-033 C
Adder
13.6776470588235311.626
923263AB1-132 E OP
Adder
4.8517647058823534.124
925612AC1-036 E
Adder
0.74705882352941180.635
924312AB2-078 E O1
Adder
1.18705882352941171.009
926274AC1-105 E
Adder
2.3364705882352941.986
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.65881.658
WECLTFEXP_WEC->PJM
CLTF
0.5060.506
LAGNLTFEXP_LAGN->PJM
CLTF
6.2356.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.91517.915
NYPJM->LTFIMP_NY
CLTF
0.9860.986
TVALTFEXP_TVA->PJM
CLTF
4.8674.867
O66PJM->LTFIMP_O-066
CMTX_NF
13.52713.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.52724.527
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1242.124
CPLELTFEXP_CPLE->PJM
CLTF
9.989.98
SIGELTFEXP_SIGE->PJM
CLTF
0.1890.189
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.950.95
MECLTFEXP_MEC->PJM
CLTF
3.1033.103
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.7574.757

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.29 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3390.96
MW Contribution:12.01
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:138.84 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4471.41
MW Contribution:14.41
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
933292AC2-141 E
Adder
12.22823529411764710.394
946262AF1-291 E
Adder
1.36823529411764721.163
3150651CHESTF6
Adder
17.73411764705882415.074
944602AF1-125 E
Adder
95.9941176470588381.595
3145506HICKORY
Adder
2.04352941176470631.737
934576AD1-082 E
Adder
4.1482352941176473.526
957871AF2-081 C
Adder
9.347.939
943612AF1-032 E
Adder
0.86235294117647050.733
3152251N ANNA1
50/50
47.25147.251
316192AB2-158 C
50/50
1.8991.899
938552AE1-074 E
50/50
1.2191.219
926755AC1-161 E
Adder
12.22823529411764710.394
933291AC2-141 C
Adder
28.64705882352941324.35
925522AC1-027 E
Adder
1.1435294117647060.972
944631AF1-128 C
Adder
37.24352941176470531.657
957872AF2-081 E
Adder
4.0035294117647063.403
3145256KINGFORK
Adder
0.94941176470588240.807
3150921YORKTN3
Adder
111.6988235294117794.944
316160AE1-175 E
Adder
1.10705882352941170.941
941102AE2-104 E
Adder
4.9623529411764714.218
938562AE1-075 E
Adder
0.92941176470588240.79
936592AD2-074 E
Adder
8.1388235294117656.918
316240AF1-291 C
Adder
2.05294117647058851.745
944641AF1-129 C
Adder
97.3976470588235282.788
924814AB2-134 E
Adder
11.94705882352941210.155
919152AA1-139 E1
Adder
3.823.247
942342AE2-247 E
Adder
1.92705882352941171.638
926502AC1-121 E
Adder
1.02470588235294110.871
920042AA2-088 E OP
Adder
9.3552941176470597.952
934511AD1-075 C
Adder
3.1717647058823532.696
934521AD1-076 C
Adder
10.8305882352941179.206
939246AE1-155 E
Adder
7.7800000000000016.613
3130536PAPERMILL
Adder
6.0070588235294125.106
939602AE1-190 E
Adder
1.29058823529411761.097
940492AE2-034 E
Adder
2.7635294117647062.349
936591AD2-074 C
Adder
4.9882352941176474.24
3152261N ANNA2
50/50
47.2747.27
3150861SPRUNCD
50/50
0.1580.158
942002AE2-212 E
Adder
1.36705882352941171.162
940431AE2-027 C
Adder
12.27647058823529510.435
944581AF1-123 C
Adder
42.58941176470588636.201
941101AE2-104 C
Adder
3.1211764705882352.653
934392AD1-063 E
Adder
0.97058823529411760.825
943742AF1-042 E
Adder
4.2588235294117653.62
962862AG1-135 E
Adder
3.6188235294117653.076
966662AG1-536 E
Adder
6.4588235294117655.49
3143316POE
Adder
1.28352941176470581.091
939191AE1-149 C
Adder
10.152941176470598.63
901082W1-029 E
Adder
29.42941176470588325.015
934146AD1-041 E
Adder
3.22588235294117662.742
957601AF2-054 C
Adder
1.91764705882352931.63
958261AF2-120 C
Adder
5.5870588235294124.749
316164AC1-076_C
50/50
1.0121.012
940642AE2-051 E
50/50
10.40710.407
919153AA1-139 E2
Adder
3.823.247
943462AF1-017 E
Adder
2.061.751
942341AE2-247 C
Adder
1.39529411764705881.186
926412AC1-112 E
Adder
1.03294117647058830.878
958162AF2-110 E
Adder
2.02588235294117651.722
924516AB2-100 E1
Adder
2.50705882352941162.131
934502AD1-074 E
Adder
15.18117647058823612.904
316044AC1-158 C1
50/50
15.00715.007
944011AF1-069 C
Adder
11.3364705882352949.636
941591AE2-156 C
Adder
16.84235294117647214.316
925332AB2-190 E
Adder
7.6305882352941186.486
944591AF1-124 C
Adder
42.74117647058823636.33
944601AF1-125 C
Adder
41.9329411764705935.643
927226AC1-216 E
Adder
7.2941176470588246.2
3150601CHESTF5
Adder
59.5223529411764750.594
936666AD2-085 E
Adder
5.2529411764705884.465
962962AG1-145 E
Adder
1.34235294117647071.141
963041AG1-153 C
Adder
4.8047058823529414.084
938771AE1-103 C
Adder
2.66470588235294152.265
3145413WATKINS
Adder
0.62117647058823530.528
966881AG1-559 C
Adder
2.14941176470588241.827
316170AC1-121 C
Adder
2.1788235294117651.852
3150831SPRUNCA
50/50
8.7958.795
3150841SPRUNCB
50/50
8.7958.795
925022AB2-158 E
50/50
5.0315.031
944582AF1-123 E
Adder
97.5247058823529582.896
944592AF1-124 E
Adder
97.8776470588235383.196
935112AD1-144 E
Adder
0.88235294117647060.75
316349AD2-085 C
Adder
3.222.737
930122AB1-027 E
Adder
1.27058823529411781.08
316169AC1-164 GEN
Adder
37.0447058823529431.488
923832AB2-022 E
Adder
1.1517647058823530.979
963042AG1-153 E
Adder
7.2070588235294136.126
938772AE1-103 E
Adder
3.67882352941176463.127
916042Z1-036 E
Adder
26.0235294117647122.12
966882AG1-559 E
Adder
1.08235294117647070.92
939261AE1-157 C
Adder
12.43411764705882510.569
926739AC1-158 E1
50/50
39.12239.122
316233AE1-074 C
50/50
2.4192.419
935162AD1-151 E
Adder
10.1647058823529428.64
938532AE1-072 E
Adder
8.5517647058823547.269
3146326AYDLETT TAP
Adder
1.26470588235294111.075
943461AF1-017 C
Adder
1.26235294117647071.073
316311AC2-079 C
Adder
5.3611764705882364.557
932596AC2-079 E
Adder
8.7482352941176477.436
917122Z2-027 E
Adder
1.24470588235294131.058
957832AF2-077 E
Adder
1.31411764705882361.117
927042AC1-191 E
Adder
4.3941176470588243.735
940551AE2-041 C
Adder
6.4717647058823545.501
920692AA2-178 E
Adder
3.6835294117647063.131
3150731STONECA
Adder
6.53294117647058855.553
932046AC2-012 E
Adder
12.32588235294117710.477
935161AD1-151 C
Adder
15.24705882352941312.96
938531AE1-072 C
Adder
16.40352941176470513.943
958161AF2-110 C
Adder
1.27411764705882361.083
3145393UNCAMP
Adder
5.5035294117647064.678
926486AC1-120 E
Adder
3.26823529411764732.778
926004AC1-076_E
50/50
5.7785.778
940641AE2-051 C
50/50
15.61115.611
316084AB2-161 E
Adder
5.2058823529411774.425
926785AC1-164_E
Adder
16.64352941176470714.147
943471AF1-018 C
Adder
6.4717647058823545.501
3145946PLYMOUTH TP
Adder
0.287058823529411760.244
942001AE2-212 C
Adder
2.0505882352941181.743
939192AE1-149 E
Adder
6.7682352941176475.753
934065AD1-033 E
Adder
4.7094117647058834.003
939312AE1-162 E
Adder
1.3482352941176471.146
937226AE2-253 E
Adder
5.4670588235294124.647
958502AF2-144 E
Adder
1.07058823529411760.91
924517AB2-100 E2
Adder
2.50705882352941162.131
934501AD1-074 C
Adder
29.82235294117647225.349
943741AF1-042 C
Adder
2.61058823529411742.219
962861AG1-135 C
Adder
5.42823529411764754.614
3150851SPRUNCC
50/50
0.1580.158
939411AE1-173 C
50/50
82.56982.569
940432AE2-027 E
Adder
8.1835294117647066.956
934012AD1-025 E
Adder
9.442352941176478.026
913392Y1-086 E
Adder
2.041.734
939612AE1-191 E
Adder
5.162352941176474.388
957602AF2-054 E
Adder
1.27882352941176471.087
966661AG1-536 C
Adder
4.8058823529411764.085
958262AF2-120 E
Adder
3.7247058823529413.166
316045AC1-158 C2
50/50
15.00715.007
944012AF1-069 E
Adder
4.4035294117647063.743
925865AC1-065 E
Adder
15.09882352941176512.834
316254AC1-120 C
Adder
6.3435294117647065.392
939262AE1-157 E
Adder
6.7447058823529415.733
961951AG1-038 C
Adder
2.88470588235294122.452
961952AG1-038 E
Adder
3.98470588235294133.387
939412AE1-173 E
50/50
55.04655.046
941032AE2-094 E
Adder
15.53882352941176513.208
941031AE2-094 C
Adder
34.69411764705882529.49
926662AC1-147 E
Adder
1.24588235294117641.059
916192Z1-068 E
Adder
1.76588235294117651.501
316076AC2-137 E
Adder
1.23411764705882351.049
957492AF2-043 E
Adder
1.32705882352941161.128
923852AB2-025 E
Adder
1.0352941176470590.88
966872AG1-558 E
Adder
1.10705882352941170.941
966871AG1-558 C
Adder
2.1964705882352941.867
923842AB2-024 E
Adder
1.62470588235294121.381
923862AB2-026 E
Adder
1.08941176470588250.926
316157AD2-030 E
Adder
1.07647058823529430.915
926740AC1-158 E2
50/50
39.12239.122
961611AG1-000B C
Adder
15.01294117647058712.761
3138116ELKO L286
Adder
1.28705882352941181.094
940541AE2-040 C
Adder
2.562.176
940482AE2-033 E
Adder
9.6941176470588258.24
940481AE2-033 C
Adder
14.37882352941176512.222
927041AC1-191 C
Adder
8.827.497
316303AF2-085
50/50
3.7313.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.39910.399
NYPJM->LTFIMP_NY
CLTF
1.9221.922
TVALTFEXP_TVA->PJM
CLTF
3.2553.255
O66PJM->LTFIMP_O-066
CMTX_NF
25.06225.062
CBM South 2LTFEXP_CBM-S2->PJM
CBM
66.04366.043
WECLTFEXP_WEC->PJM
CLTF
0.1350.135
LAGNLTFEXP_LAGN->PJM
CLTF
4.1614.161
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.310.31
MECLTFEXP_MEC->PJM
CLTF
1.3051.305
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.9713.971
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.2045.204
G-007PJM->LTFIMP_G-007
CMTX_NF
3.9253.925
CPLELTFEXP_CPLE->PJM
CLTF
8.348.34
SIGELTFEXP_SIGE->PJM
CLTF
0.0740.074

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.93 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4311.69
MW Contribution:43.01
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.26 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4569.37
MW Contribution:42.76
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316240AF1-291 C
Adder
-1.7670588235294118-1.502
944641AF1-129 C
Adder
-82.61058823529412-70.219
925785AC1-054 E
Adder
3.30235294117647052.807
959311AF2-222 C
50/50
30.29330.293
942751AE2-291 C
Adder
11.5670588235294139.832
3151041BRUNSWICKG3
50/50
25.39725.397
3151021BRUNSWICKG1
50/50
25.39725.397
957481AF2-042 C
50/50
128.648128.648
924322AB2-079 E O1
50/50
2.2822.282
946302AF1-294 E
Adder
4.6788235294117653.977
943902AF1-058 E
50/50
2.3942.394
24401205PINNACLE
Adder
1.53647058823529431.306
957601AF2-054 C
Adder
-1.6305882352941177-1.386
316239AB2-077 C O1
50/50
0.5590.559
935171AD1-152 C
50/50
2.8452.845
942462AE2-259 E
Adder
9.2458823529411777.859
964791AG1-342 C
50/50
6.3476.347
925997AC1-075 E
Adder
4.5835294117647063.896
3147223TWITTYS
50/50
1.7561.756
959312AF2-222 E
50/50
20.29620.296
924022AB2-043 E O1
50/50
8.8758.875
316003AC1-222 C
50/50
1.7761.776
926024AC1-080 E
Adder
1.52117647058823541.293
936161AD2-022 C
Adder
11.7541176470588239.991
944011AF1-069 C
50/50
45.64245.642
963041AG1-153 C
50/50
17.20617.206
3151531CLOVER1
50/50
28.70728.707
936261AD2-033 C
50/50
21.05721.057
3151631KERR 6
50/50
1.7561.756
961791AG1-021 C
Adder
2.68823529411764732.285
962562AG1-105 E
50/50
10.53610.536
316248AF1-058 C
50/50
0.5870.587
936171AD2-023 C
Adder
6.8564705882352955.828
963042AG1-153 E
50/50
25.80825.808
3151541CLOVER2
50/50
28.44128.441
964241AG1-285 C
50/50
24.94424.944
316034AC1-036 C
50/50
0.4320.432
958212AF2-115 E
Adder
2.86235294117647052.433
962561AG1-105 C
50/50
15.80415.804
936172AD2-023 E
Adder
3.7223529411764713.164
937482AD2-202 E
50/50
2.3852.385
3151581KERR 1
50/50
0.6270.627
3151601KERR 3
50/50
1.7561.756
961792AG1-021 E
Adder
2.28941176470588251.946
3152661PLYWOOD A
50/50
2.1912.191
3152431Z1-086 GT3
50/50
33.83433.834
3152441Z1-086 ST
50/50
58.91758.917
3147133PAMPLIN
50/50
1.5711.571
927264AC1-222 E
50/50
7.2547.254
938531AE1-072 C
Adder
-15.17764705882353-12.901
3152411Z1-086 GT1
50/50
33.84633.846
3152421Z1-086 GT2
50/50
33.83433.834
924302AB2-077 E O1
50/50
2.2822.282
3151621KERR 5
50/50
1.7561.756
316222AC1-221 C
50/50
2.632.63
942752AE2-291 E
Adder
7.7105882352941186.554
942001AE2-212 C
Adder
-1.851764705882353-1.574
3151031BRUNSWICKG2
50/50
25.39725.397
957482AF2-042 E
50/50
85.76685.766
937481AD2-202 C
50/50
0.820.82
3151641KERR 7
50/50
1.7561.756
933291AC2-141 C
Adder
-30.18235294117647-25.655
964242AG1-285 E
50/50
16.62916.629
313527AB2-043 C
50/50
0.8840.884
924162AB2-060 E OP
50/50
7.2927.292
3151591KERR 2
50/50
1.7561.756
964792AG1-342 E
50/50
4.2324.232
932763AC2-100 E
50/50
4.6444.644
316283AC2-100 C
50/50
2.112.11
940641AE2-051 C
Adder
-20.06823529411765-17.058
934622AD1-088 E
50/50
10.02610.026
934611AD1-087 C
50/50
2.8252.825
934612AD1-087 E
50/50
8.158.15
3151611KERR 4
50/50
1.7561.756
927255AC1-221 E
50/50
6.8776.877
944012AF1-069 E
50/50
17.73117.731
316131AB2-060 C
50/50
2.5322.532
3138533PONTONDP
Adder
0.99529411764705880.846
316118AC1-105 C
50/50
1.6721.672
941032AE2-094 E
50/50
62.56462.564
941031AE2-094 C
50/50
139.691139.691
3151051BRUNSWICKS1
50/50
52.76252.762
936262AD2-033 E
50/50
14.03814.038
958211AF2-115 C
Adder
3.362.856
925612AC1-036 E
50/50
1.5841.584
316237AB2-079 C O1
50/50
0.5590.559
924312AB2-078 E O1
50/50
2.2822.282
316238AB2-078 C O1
50/50
0.5590.559
926274AC1-105 E
50/50
4.8944.894
934621AD1-088 C
50/50
20.82320.823
935172AD1-152 E
50/50
11.70511.705
946301AF1-294 C
Adder
5.5247058823529414.696
942461AE2-259 C
Adder
13.86823529411764811.788
936162AD2-022 E
Adder
7.0529411764705895.995
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.3338.33
NYPJM->LTFIMP_NY
CLTF
1.8141.814
TVALTFEXP_TVA->PJM
CLTF
10.24910.249
O66PJM->LTFIMP_O-066
CMTX_NF
25.2725.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
162.815162.815
WECLTFEXP_WEC->PJM
CLTF
1.1471.147
LAGNLTFEXP_LAGN->PJM
CLTF
13.09813.098
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
2.1482.148
MECLTFEXP_MEC->PJM
CLTF
6.8436.843
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.0719.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5656
G-007PJM->LTFIMP_G-007
CMTX_NF
3.9723.972
CPLELTFEXP_CPLE->PJM
CLTF
19.02319.023
SIGELTFEXP_SIGE->PJM
CLTF
0.4210.421
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN N ANNA-KRAKEN_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 313483 CKT 1   /*8NO ANNA     500.0 - 8KRAKEN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314287 to 314260 ckt 1
314260 to 314225 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 313483 ckt 1
314914 to 314322 ckt 1
314936 to 314902 ckt 1
314923 to 314924 ckt 1
314934 to 314916 ckt 1
941030 to 314902 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC106.19 %661.76B702.745.43
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC108.87 %661.76B720.455.43
GD1DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S-1
OPAC111.78 %1058.16B1182.765.66
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC102.58 %661.76B678.865.43
GD1DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
OPAC103.49 %4070.2B4212.3113.34
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Base Case
OPAC104.09 %2442.12A2541.9912.2
GD1DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
OPAC103.53 %4070.2B4213.913.57
GD1DVP
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
DVP_P1-2: LN 568_SRT-S
OPAC113.01 %3220.44B3639.358.07
GD1DVP
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.31 %4070.2B4286.2742.76
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Base Case
OPAC104.94 %3220.44A3379.5410.87

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.19 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:702.74
MW Contribution:5.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316405AF2-144 C
50/50
0.370.37
941011AE2-092 C
50/50
17.02117.021
961792AG1-021 E
50/50
1.7281.728
937482AD2-202 E
Adder
0.59882352941176480.509
918492AA1-063AE OP
Adder
1.62117647058823521.378
938552AE1-074 E
Adder
0.58705882352941170.499
938562AE1-075 E
50/50
1.3151.315
932763AC2-100 E
Adder
1.14117647058823520.97
964242AG1-285 E
50/50
6.6676.667
964792AG1-342 E
50/50
1.4521.452
924162AB2-060 E OP
50/50
3.1523.152
313527AB2-043 C
50/50
0.3710.371
940451AE2-029 C
Adder
-2.101176470588235-1.786
959311AF2-222 C
50/50
16.12516.125
925785AC1-054 E
Adder
1.72941176470588241.47
3145723EMPORIA
Adder
0.183529411764705890.156
923573AB1-173 E OP
Adder
1.38235294117647081.175
919692AA2-053 E OP
Adder
1.70470588235294131.449
958502AF2-144 E
50/50
1.5161.516
938822AE1-108 E
50/50
11.96911.969
942461AE2-259 C
50/50
13.72813.728
946301AF1-294 C
50/50
4.174.17
935172AD1-152 E
Adder
2.9870588235294122.539
934621AD1-088 C
50/50
6.3766.376
957482AF2-042 E
Adder
19.8305882352941216.856
924517AB2-100 E2
Adder
1.08941176470588250.926
946302AF1-294 E
50/50
3.5313.531
943902AF1-058 E
Adder
0.69411764705882350.59
924322AB2-079 E O1
50/50
0.9480.948
957481AF2-042 C
Adder
29.74705882352941425.285
316088AB2-174 E
Adder
2.76235294117647052.348
923994AB2-040_E
Adder
2.5917647058823532.203
316313AB2-026 C
50/50
0.4750.475
3151921BEARGRDN G2
50/50
12.47412.474
942462AE2-259 E
50/50
9.1529.152
964791AG1-342 C
50/50
2.1782.178
316239AB2-077 C O1
50/50
0.2320.232
959312AF2-222 E
50/50
10.80310.803
3147223TWITTYS
50/50
0.8950.895
924022AB2-043 E O1
50/50
3.7383.738
924516AB2-100 E1
Adder
1.08941176470588250.926
966621AG1-532 C
Adder
0.60117647058823530.511
940642AE2-051 E
Adder
4.0647058823529413.455
924032AB2-045 E
50/50
2.7232.723
961791AG1-021 C
50/50
2.0282.028
936261AD2-033 C
50/50
11.6911.69
962562AG1-105 E
50/50
3.7423.742
963041AG1-153 C
Adder
2.1717647058823531.846
960081AF2-299 C
Adder
0.80117647058823540.681
944011AF1-069 C
Adder
4.8258823529411774.102
3150831SPRUNCA
Adder
3.4141176470588242.902
3150841SPRUNCB
Adder
3.4141176470588242.902
316258AE1-075 C
50/50
0.4360.436
923862AB2-026 E
50/50
1.5431.543
941012AE2-092 E
50/50
11.34711.347
958211AF2-115 C
50/50
2.5362.536
936262AD2-033 E
50/50
7.7937.793
923852AB2-025 E
Adder
0.41764705882352940.355
941032AE2-094 E
Adder
6.615294117647065.623
941031AE2-094 C
Adder
14.76941176470588212.554
939412AE1-173 E
Adder
20.8635294117647117.734
958212AF2-115 E
50/50
2.162.16
3144293JTRSVLE
50/50
0.4650.465
316034AC1-036 C
50/50
0.220.22
964241AG1-285 C
50/50
1010
962561AG1-105 C
50/50
5.6135.613
963042AG1-153 E
Adder
3.25764705882352962.769
946281AF1-292 C
Adder
0.66352941176470580.564
960082AF2-299 E
Adder
0.53411764705882360.454
3138533PONTONDP
50/50
0.7510.751
316131AB2-060 C
50/50
1.0911.091
946282AF1-292 E
Adder
0.44235294117647060.376
944012AF1-069 E
Adder
1.87411764705882341.593
316233AE1-074 C
Adder
1.16470588235294130.99
958132AF2-107 E
50/50
1.9941.994
3147133PAMPLIN
50/50
1.1881.188
927264AC1-222 E
Adder
2.12235294117647081.804
966622AG1-532 E
Adder
0.401176470588235360.341
958131AF2-107 C
50/50
3.6383.638
316322AB2-045 C
50/50
0.6050.605
924302AB2-077 E O1
50/50
0.9480.948
316238AB2-078 C O1
50/50
0.2320.232
316336AC2-165 C
50/50
14.4814.48
3151931BEARGRDN S1
50/50
16.13716.137
927255AC1-221 E
Adder
1.70000000000000021.445
316237AB2-079 C O1
50/50
0.2320.232
934622AD1-088 E
50/50
3.073.07
934612AD1-087 E
Adder
2.04705882352941161.74
940641AE2-051 C
Adder
6.0976470588235295.183
933502AC2-165 E
50/50
10.89810.898
3151911BEARGRDN G1
50/50
12.47412.474
3137643SOCKMAN
Adder
0.296470588235294150.252
939411AE1-173 C
Adder
31.29411764705882626.6
938821AE1-108 C
50/50
25.08525.085
925612AC1-036 E
50/50
0.8080.808
926274AC1-105 E
Adder
1.54705882352941181.315
924312AB2-078 E O1
50/50
0.9480.948
940541AE2-040 C
Adder
1.03294117647058830.878
940481AE2-033 C
Adder
5.8647058823529424.985
940482AE2-033 E
Adder
3.9541176470588243.361
316303AF2-085
50/50
2.082.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.6554.655
NYPJM->LTFIMP_NY
CLTF
0.4910.491
TVALTFEXP_TVA->PJM
CLTF
1.461.46
O66PJM->LTFIMP_O-066
CMTX_NF
6.1316.131
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.59331.593
WECLTFEXP_WEC->PJM
CLTF
0.0570.057
LAGNLTFEXP_LAGN->PJM
CLTF
1.8911.891
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.1180.118
MECLTFEXP_MEC->PJM
CLTF
0.5720.572
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9351.935
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.2992.299
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9570.957
CPLELTFEXP_CPLE->PJM
CLTF
4.0634.063
SIGELTFEXP_SIGE->PJM
CLTF
0.030.03

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.87 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:720.45
MW Contribution:5.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316405AF2-144 C
50/50
0.370.37
941011AE2-092 C
50/50
17.02117.021
961792AG1-021 E
50/50
1.7281.728
937482AD2-202 E
Adder
0.59882352941176480.509
918492AA1-063AE OP
Adder
1.62117647058823521.378
938552AE1-074 E
Adder
0.58705882352941170.499
938562AE1-075 E
50/50
1.3151.315
932763AC2-100 E
Adder
1.14117647058823520.97
964242AG1-285 E
50/50
6.6676.667
964792AG1-342 E
50/50
1.4521.452
924162AB2-060 E OP
50/50
3.1523.152
313527AB2-043 C
50/50
0.3710.371
940451AE2-029 C
Adder
-2.101176470588235-1.786
959311AF2-222 C
50/50
16.12516.125
925785AC1-054 E
Adder
1.72941176470588241.47
3145723EMPORIA
Adder
0.183529411764705890.156
923573AB1-173 E OP
Adder
1.38235294117647081.175
919692AA2-053 E OP
Adder
1.70470588235294131.449
958502AF2-144 E
50/50
1.5161.516
938822AE1-108 E
50/50
11.96911.969
942461AE2-259 C
50/50
13.72813.728
946301AF1-294 C
50/50
4.174.17
935172AD1-152 E
Adder
2.9870588235294122.539
934621AD1-088 C
50/50
6.3766.376
957482AF2-042 E
Adder
19.8305882352941216.856
924517AB2-100 E2
Adder
1.08941176470588250.926
946302AF1-294 E
50/50
3.5313.531
943902AF1-058 E
Adder
0.69411764705882350.59
924322AB2-079 E O1
50/50
0.9480.948
957481AF2-042 C
Adder
29.74705882352941425.285
316088AB2-174 E
Adder
2.76235294117647052.348
923994AB2-040_E
Adder
2.5917647058823532.203
316313AB2-026 C
50/50
0.4750.475
3151921BEARGRDN G2
50/50
12.47412.474
942462AE2-259 E
50/50
9.1529.152
964791AG1-342 C
50/50
2.1782.178
316239AB2-077 C O1
50/50
0.2320.232
959312AF2-222 E
50/50
10.80310.803
3147223TWITTYS
50/50
0.8950.895
924022AB2-043 E O1
50/50
3.7383.738
924516AB2-100 E1
Adder
1.08941176470588250.926
966621AG1-532 C
Adder
0.60117647058823530.511
940642AE2-051 E
Adder
4.0647058823529413.455
924032AB2-045 E
50/50
2.7232.723
961791AG1-021 C
50/50
2.0282.028
936261AD2-033 C
50/50
11.6911.69
962562AG1-105 E
50/50
3.7423.742
963041AG1-153 C
Adder
2.1717647058823531.846
960081AF2-299 C
Adder
0.80117647058823540.681
944011AF1-069 C
Adder
4.8258823529411774.102
3150831SPRUNCA
Adder
3.4141176470588242.902
3150841SPRUNCB
Adder
3.4141176470588242.902
316258AE1-075 C
50/50
0.4360.436
923862AB2-026 E
50/50
1.5431.543
941012AE2-092 E
50/50
11.34711.347
958211AF2-115 C
50/50
2.5362.536
936262AD2-033 E
50/50
7.7937.793
923852AB2-025 E
Adder
0.41764705882352940.355
941032AE2-094 E
Adder
6.615294117647065.623
941031AE2-094 C
Adder
14.76941176470588212.554
939412AE1-173 E
Adder
20.8635294117647117.734
958212AF2-115 E
50/50
2.162.16
3144293JTRSVLE
50/50
0.4650.465
316034AC1-036 C
50/50
0.220.22
964241AG1-285 C
50/50
1010
962561AG1-105 C
50/50
5.6135.613
963042AG1-153 E
Adder
3.25764705882352962.769
946281AF1-292 C
Adder
0.66352941176470580.564
960082AF2-299 E
Adder
0.53411764705882360.454
3138533PONTONDP
50/50
0.7510.751
316131AB2-060 C
50/50
1.0911.091
946282AF1-292 E
Adder
0.44235294117647060.376
944012AF1-069 E
Adder
1.87411764705882341.593
316233AE1-074 C
Adder
1.16470588235294130.99
958132AF2-107 E
50/50
1.9941.994
3147133PAMPLIN
50/50
1.1881.188
927264AC1-222 E
Adder
2.12235294117647081.804
966622AG1-532 E
Adder
0.401176470588235360.341
958131AF2-107 C
50/50
3.6383.638
316322AB2-045 C
50/50
0.6050.605
924302AB2-077 E O1
50/50
0.9480.948
316238AB2-078 C O1
50/50
0.2320.232
316336AC2-165 C
50/50
14.4814.48
3151931BEARGRDN S1
50/50
16.13716.137
927255AC1-221 E
Adder
1.70000000000000021.445
316237AB2-079 C O1
50/50
0.2320.232
934622AD1-088 E
50/50
3.073.07
934612AD1-087 E
Adder
2.04705882352941161.74
940641AE2-051 C
Adder
6.0976470588235295.183
933502AC2-165 E
50/50
10.89810.898
3151911BEARGRDN G1
50/50
12.47412.474
3137643SOCKMAN
Adder
0.296470588235294150.252
939411AE1-173 C
Adder
31.29411764705882626.6
938821AE1-108 C
50/50
25.08525.085
925612AC1-036 E
50/50
0.8080.808
926274AC1-105 E
Adder
1.54705882352941181.315
924312AB2-078 E O1
50/50
0.9480.948
940541AE2-040 C
Adder
1.03294117647058830.878
940481AE2-033 C
Adder
5.8647058823529424.985
940482AE2-033 E
Adder
3.9541176470588243.361
316303AF2-085
50/50
2.082.08
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.1180.118
MECLTFEXP_MEC->PJM
CLTF
0.5720.572
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9351.935
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.2992.299
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9570.957
CPLELTFEXP_CPLE->PJM
CLTF
4.0634.063
SIGELTFEXP_SIGE->PJM
CLTF
0.030.03
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.59331.593
WECLTFEXP_WEC->PJM
CLTF
0.0570.057
LAGNLTFEXP_LAGN->PJM
CLTF
1.8911.891
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.6554.655
NYPJM->LTFIMP_NY
CLTF
0.4910.491
TVALTFEXP_TVA->PJM
CLTF
1.461.46
O66PJM->LTFIMP_O-066
CMTX_NF
6.1316.131

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.78 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1182.76
MW Contribution:5.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150861SPRUNCD
50/50
0.1690.169
316405AF2-144 C
50/50
0.4340.434
3150651CHESTF6
Adder
11.96588235294117610.171
946262AF1-291 E
Adder
0.91058823529411770.774
941011AE2-092 C
Adder
6.9470588235294125.905
961792AG1-021 E
Adder
0.82823529411764710.704
937482AD2-202 E
Adder
0.456470588235294130.388
934576AD1-082 E
Adder
2.2917647058823531.948
918492AA1-063AE OP
Adder
1.8117647058823531.54
933292AC2-141 E
Adder
2.30588235294117631.96
940492AE2-034 E
Adder
1.33882352941176451.138
944602AF1-125 E
Adder
43.9588235294117737.365
957871AF2-081 C
Adder
4.3329411764705883.683
3145506HICKORY
Adder
0.94470588235294130.803
943612AF1-032 E
Adder
0.405882352941176470.345
3130536PAPERMILL
Adder
3.0341176470588242.579
939602AE1-190 E
Adder
0.6517647058823530.554
944631AF1-128 C
Adder
24.6823529411764720.98
3150851SPRUNCC
50/50
0.1690.169
938552AE1-074 E
50/50
1.8811.881
938562AE1-075 E
50/50
1.5421.542
964242AG1-285 E
Adder
4.0211764705882363.418
924162AB2-060 E OP
Adder
2.0117647058823531.71
316160AE1-175 E
Adder
0.54117647058823540.46
933291AC2-141 C
Adder
12.51176470588235310.635
957872AF2-081 E
Adder
1.85647058823529431.578
925522AC1-027 E
Adder
0.53176470588235290.452
941102AE2-104 E
Adder
2.39764705882352922.038
3145256KINGFORK
Adder
0.455294117647058850.387
3150921YORKTN3
Adder
52.8152941176470644.893
944641AF1-129 C
Adder
65.7211764705882355.863
316240AF1-291 C
Adder
1.36588235294117651.161
959311AF2-222 C
Adder
8.5341176470588237.254
3145723EMPORIA
Adder
0.196470588235294150.167
923573AB1-173 E OP
Adder
1.47764705882352951.256
919692AA2-053 E OP
Adder
1.86823529411764721.588
924814AB2-134 E
Adder
6.8847058823529425.852
920042AA2-088 E OP
Adder
4.724.012
942342AE2-247 E
Adder
0.98470588235294120.837
919152AA1-139 E1
Adder
1.7717647058823531.506
958502AF2-144 E
50/50
1.7771.777
938822AE1-108 E
Adder
4.0211764705882363.418
942001AE2-212 C
Adder
1.3035294117647061.108
942461AE2-259 C
Adder
5.83647058823529454.961
946301AF1-294 C
Adder
1.99882352941176491.699
939192AE1-149 E
Adder
3.93176470588235333.342
934621AD1-088 C
Adder
4.3294117647058833.68
957482AF2-042 E
Adder
15.4776470588235313.156
924517AB2-100 E2
Adder
1.32117647058823541.123
937226AE2-253 E
Adder
2.53176470588235342.152
934065AD1-033 E
Adder
2.1752941176470591.849
939312AE1-162 E
Adder
0.67999999999999990.578
942002AE2-212 E
Adder
0.86941176470588230.739
946302AF1-294 E
Adder
1.69294117647058841.439
940431AE2-027 C
Adder
7.9682352941176476.773
924322AB2-079 E O1
Adder
0.62117647058823530.528
957481AF2-042 C
Adder
23.21647058823529619.734
316088AB2-174 E
Adder
2.94705882352941152.505
923994AB2-040_E
Adder
2.76941176470588252.354
944581AF1-123 C
Adder
19.50352941176470616.578
941101AE2-104 C
Adder
1.50823529411764711.282
934392AD1-063 E
Adder
0.487058823529411770.414
3143096IRON208
50/50
0.330.33
316313AB2-026 C
50/50
0.5570.557
3143316POE
Adder
0.75647058823529410.643
942462AE2-259 E
Adder
3.8917647058823533.308
939191AE1-149 C
Adder
5.8976470588235295.013
901082W1-029 E
Adder
13.8976470588235311.813
934146AD1-041 E
Adder
1.63058823529411771.386
957601AF2-054 C
Adder
0.95294117647058830.81
926412AC1-112 E
Adder
0.56470588235294120.48
959312AF2-222 E
Adder
5.71764705882352954.86
3147223TWITTYS
Adder
0.48235294117647060.41
924022AB2-043 E O1
Adder
2.4235294117647062.06
924516AB2-100 E1
Adder
1.32117647058823541.123
966621AG1-532 C
Adder
0.63882352941176480.543
940642AE2-051 E
Adder
4.67764705882352953.976
943462AF1-017 E
Adder
1.0517647058823530.894
942341AE2-247 C
Adder
0.71294117647058820.606
919153AA1-139 E2
Adder
1.7717647058823531.506
958162AF2-110 E
Adder
0.97882352941176460.832
3150601CHESTF5
Adder
39.4470588235294233.53
924032AB2-045 E
Adder
0.94941176470588240.807
961791AG1-021 C
Adder
0.97294117647058820.827
936261AD2-033 C
Adder
6.5000000000000015.525
925332AB2-190 E
Adder
4.5752941176470593.889
963041AG1-153 C
Adder
2.2623529411764711.923
960081AF2-299 C
Adder
0.8517647058823530.724
944011AF1-069 C
Adder
5.2235294117647074.44
926072AC1-086 E
Adder
4.2364705882352943.601
927226AC1-216 E
Adder
4.20352941176470553.573
3145413WATKINS
Adder
0.30941176470588240.263
936666AD2-085 E
Adder
2.6835294117647062.281
962962AG1-145 E
Adder
0.65529411764705890.557
938771AE1-103 C
Adder
1.3117647058823531.115
944591AF1-124 C
Adder
19.5717647058823516.636
944601AF1-125 C
Adder
19.2023529411764716.322
941591AE2-156 C
Adder
7.8529411764705886.675
316076AC2-137 E
Adder
0.73529411764705890.625
966872AG1-558 E
Adder
0.64352941176470590.547
966871AG1-558 C
Adder
1.27764705882352961.086
3150831SPRUNCA
50/50
9.4469.446
3150841SPRUNCB
50/50
9.4469.446
316258AE1-075 C
50/50
0.5110.511
923862AB2-026 E
50/50
1.8081.808
941012AE2-092 E
Adder
4.6305882352941183.936
958211AF2-115 C
Adder
1.21529411764705891.033
936262AD2-033 E
Adder
4.3329411764705883.683
923852AB2-025 E
Adder
0.54941176470588240.467
941032AE2-094 E
Adder
7.166.086
941031AE2-094 C
Adder
15.98588235294117513.588
939412AE1-173 E
Adder
24.89294117647058621.159
916192Z1-068 E
Adder
0.820.697
926662AC1-147 E
Adder
0.58117647058823530.494
957492AF2-043 E
Adder
0.62470588235294120.531
923842AB2-024 E
Adder
0.82235294117647050.699
316157AD2-030 E
Adder
0.53411764705882360.454
316169AC1-164 GEN
Adder
19.79647058823529816.827
930122AB1-027 E
Adder
0.69529411764705880.591
958212AF2-115 E
Adder
1.0352941176470590.88
964241AG1-285 C
Adder
6.0305882352941185.126
963042AG1-153 E
Adder
3.39411764705882352.885
946281AF1-292 C
Adder
0.70588235294117650.6
960082AF2-299 E
Adder
0.56823529411764710.483
926071AC1-086 C
Adder
9.3082352941176477.912
316349AD2-085 C
Adder
1.6447058823529411.398
938772AE1-103 E
Adder
1.8117647058823531.54
916042Z1-036 E
Adder
12.43647058823529310.571
944592AF1-124 E
Adder
44.82117647058823538.098
944582AF1-123 E
Adder
44.6637.961
923832AB2-022 E
Adder
0.53882352941176470.458
935112AD1-144 E
Adder
0.42235294117647060.359
3138533PONTONDP
Adder
0.360.306
946282AF1-292 E
Adder
0.47058823529411770.4
944012AF1-069 E
Adder
2.02941176470588271.725
925865AC1-065 E
Adder
7.73058823529411756.571
927042AC1-191 E
Adder
2.55411764705882362.171
316233AE1-074 C
50/50
3.7333.733
3147133PAMPLIN
Adder
0.54941176470588240.467
966622AG1-532 E
Adder
0.42588235294117650.362
935162AD1-151 E
Adder
5.9847058823529415.087
943461AF1-017 C
Adder
0.64470588235294120.548
316311AC2-079 C
Adder
2.71999999999999982.312
932596AC2-079 E
Adder
4.4376470588235293.772
920692AA2-178 E
Adder
1.78588235294117651.518
917122Z2-027 E
Adder
0.58470588235294120.497
3146326AYDLETT TAP
Adder
0.58823529411764710.5
938532AE1-072 E
Adder
3.9729411764705883.377
940551AE2-041 C
Adder
3.25058823529411762.763
957832AF2-077 E
Adder
0.63529411764705890.54
3150731STONECA
Adder
4.1494117647058823.527
924302AB2-077 E O1
Adder
0.62117647058823530.528
935161AD1-151 C
Adder
8.9764705882352947.63
900672V4-068 E
Adder
0.157647058823529420.134
3145393UNCAMP
Adder
2.72117647058823582.313
938531AE1-072 C
Adder
7.6223529411764716.479
932046AC2-012 E
Adder
5.7529411764705884.89
958161AF2-110 C
Adder
0.61529411764705890.523
926785AC1-164_E
Adder
8.8941176470588247.56
316336AC2-165 C
50/50
13.55213.552
934622AD1-088 E
Adder
2.08470588235294141.772
934612AD1-087 E
Adder
1.55882352941176471.325
316084AB2-161 E
Adder
2.8764705882352942.445
940641AE2-051 C
Adder
7.0152941176470595.963
943471AF1-018 C
Adder
3.25058823529411762.763
933502AC2-165 E
50/50
10.19910.199
940432AE2-027 E
Adder
5.3129411764705894.516
3137643SOCKMAN
Adder
0.317647058823529450.27
939411AE1-173 C
Adder
37.3388235294117631.738
934012AD1-025 E
Adder
5.44117647058823554.625
913392Y1-086 E
Adder
0.9552941176470590.812
939612AE1-191 E
Adder
2.6082352941176472.217
957602AF2-054 E
Adder
0.63529411764705890.54
3138116ELKO L286
Adder
0.76588235294117660.651
927041AC1-191 C
Adder
5.1282352941176474.359
938821AE1-108 C
Adder
8.4270588235294127.163
925612AC1-036 E
Adder
0.435294117647058830.37
924312AB2-078 E O1
Adder
0.62117647058823530.528
940541AE2-040 C
Adder
1.35764705882352941.154
940481AE2-033 C
Adder
7.6223529411764716.479
940482AE2-033 E
Adder
5.13882352941176554.368
923263AB1-132 E OP
Adder
2.70941176470588242.303
961611AG1-000B C
Adder
8.1152941176470596.898
316303AF2-085
50/50
7.0277.027
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.08118.081
G-007PJM->LTFIMP_G-007
CMTX_NF
2.112.11
CPLELTFEXP_CPLE->PJM
CLTF
4.6984.698
SIGELTFEXP_SIGE->PJM
CLTF
0.1370.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.7270.727
MECLTFEXP_MEC->PJM
CLTF
2.1322.132
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.2422.242
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.29711.297
NYPJM->LTFIMP_NY
CLTF
0.9630.963
TVALTFEXP_TVA->PJM
CLTF
2.952.95
O66PJM->LTFIMP_O-066
CMTX_NF
13.41813.418
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.62940.629
WECLTFEXP_WEC->PJM
CLTF
0.3730.373
LAGNLTFEXP_LAGN->PJM
CLTF
3.6953.695

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.58 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:678.86
MW Contribution:5.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316405AF2-144 C
50/50
0.370.37
941011AE2-092 C
50/50
17.02117.021
961792AG1-021 E
50/50
1.7281.728
937482AD2-202 E
Adder
0.59882352941176480.509
918492AA1-063AE OP
Adder
1.62117647058823521.378
938552AE1-074 E
Adder
0.58705882352941170.499
938562AE1-075 E
50/50
1.3151.315
932763AC2-100 E
Adder
1.14117647058823520.97
964242AG1-285 E
50/50
6.6676.667
964792AG1-342 E
50/50
1.4521.452
924162AB2-060 E OP
50/50
3.1523.152
313527AB2-043 C
50/50
0.3710.371
940451AE2-029 C
Adder
-2.101176470588235-1.786
959311AF2-222 C
50/50
16.12516.125
925785AC1-054 E
Adder
1.72941176470588241.47
3145723EMPORIA
Adder
0.183529411764705890.156
923573AB1-173 E OP
Adder
1.38235294117647081.175
919692AA2-053 E OP
Adder
1.70470588235294131.449
946302AF1-294 E
50/50
3.5313.531
943902AF1-058 E
Adder
0.69411764705882350.59
924322AB2-079 E O1
50/50
0.9480.948
957481AF2-042 C
Adder
29.74705882352941425.285
316088AB2-174 E
Adder
2.76235294117647052.348
923994AB2-040_E
Adder
2.5917647058823532.203
316313AB2-026 C
50/50
0.4750.475
3151921BEARGRDN G2
50/50
12.47412.474
942462AE2-259 E
50/50
9.1529.152
964791AG1-342 C
50/50
2.1782.178
316239AB2-077 C O1
50/50
0.2320.232
959312AF2-222 E
50/50
10.80310.803
3147223TWITTYS
50/50
0.8950.895
924022AB2-043 E O1
50/50
3.7383.738
924516AB2-100 E1
Adder
1.08941176470588250.926
966621AG1-532 C
Adder
0.60117647058823530.511
940642AE2-051 E
Adder
4.0647058823529413.455
924032AB2-045 E
50/50
2.7232.723
961791AG1-021 C
50/50
2.0282.028
936261AD2-033 C
50/50
11.6911.69
962562AG1-105 E
50/50
3.7423.742
963041AG1-153 C
Adder
2.1717647058823531.846
960081AF2-299 C
Adder
0.80117647058823540.681
944011AF1-069 C
Adder
4.8258823529411774.102
3150831SPRUNCA
Adder
3.4141176470588242.902
3150841SPRUNCB
Adder
3.4141176470588242.902
316258AE1-075 C
50/50
0.4360.436
923862AB2-026 E
50/50
1.5431.543
941012AE2-092 E
50/50
11.34711.347
958211AF2-115 C
50/50
2.5362.536
936262AD2-033 E
50/50
7.7937.793
923852AB2-025 E
Adder
0.41764705882352940.355
941032AE2-094 E
Adder
6.615294117647065.623
941031AE2-094 C
Adder
14.76941176470588212.554
939412AE1-173 E
Adder
20.8635294117647117.734
958212AF2-115 E
50/50
2.162.16
3144293JTRSVLE
50/50
0.4650.465
316034AC1-036 C
50/50
0.220.22
964241AG1-285 C
50/50
1010
962561AG1-105 C
50/50
5.6135.613
963042AG1-153 E
Adder
3.25764705882352962.769
946281AF1-292 C
Adder
0.66352941176470580.564
960082AF2-299 E
Adder
0.53411764705882360.454
316233AE1-074 C
Adder
1.16470588235294130.99
958132AF2-107 E
50/50
1.9941.994
3147133PAMPLIN
50/50
1.1881.188
927264AC1-222 E
Adder
2.12235294117647081.804
966622AG1-532 E
Adder
0.401176470588235360.341
958131AF2-107 C
50/50
3.6383.638
316322AB2-045 C
50/50
0.6050.605
924302AB2-077 E O1
50/50
0.9480.948
316238AB2-078 C O1
50/50
0.2320.232
316336AC2-165 C
50/50
14.4814.48
3151931BEARGRDN S1
50/50
16.13716.137
927255AC1-221 E
Adder
1.70000000000000021.445
316237AB2-079 C O1
50/50
0.2320.232
934622AD1-088 E
50/50
3.073.07
934612AD1-087 E
Adder
2.04705882352941161.74
940641AE2-051 C
Adder
6.0976470588235295.183
958502AF2-144 E
50/50
1.5161.516
938822AE1-108 E
50/50
11.96911.969
942461AE2-259 C
50/50
13.72813.728
946301AF1-294 C
50/50
4.174.17
935172AD1-152 E
Adder
2.9870588235294122.539
934621AD1-088 C
50/50
6.3766.376
957482AF2-042 E
Adder
19.8305882352941216.856
924517AB2-100 E2
Adder
1.08941176470588250.926
933502AC2-165 E
50/50
10.89810.898
3151911BEARGRDN G1
50/50
12.47412.474
3137643SOCKMAN
Adder
0.296470588235294150.252
939411AE1-173 C
Adder
31.29411764705882626.6
3138533PONTONDP
50/50
0.7510.751
316131AB2-060 C
50/50
1.0911.091
946282AF1-292 E
Adder
0.44235294117647060.376
944012AF1-069 E
Adder
1.87411764705882341.593
938821AE1-108 C
50/50
25.08525.085
925612AC1-036 E
50/50
0.8080.808
926274AC1-105 E
Adder
1.54705882352941181.315
924312AB2-078 E O1
50/50
0.9480.948
940541AE2-040 C
Adder
1.03294117647058830.878
940481AE2-033 C
Adder
5.8647058823529424.985
940482AE2-033 E
Adder
3.9541176470588243.361
316303AF2-085
50/50
2.082.08
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.2992.299
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9570.957
CPLELTFEXP_CPLE->PJM
CLTF
4.0634.063
SIGELTFEXP_SIGE->PJM
CLTF
0.030.03
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.1180.118
MECLTFEXP_MEC->PJM
CLTF
0.5720.572
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9351.935
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.6554.655
NYPJM->LTFIMP_NY
CLTF
0.4910.491
TVALTFEXP_TVA->PJM
CLTF
1.461.46
O66PJM->LTFIMP_O-066
CMTX_NF
6.1316.131
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.59331.593
WECLTFEXP_WEC->PJM
CLTF
0.0570.057
LAGNLTFEXP_LAGN->PJM
CLTF
1.8911.891

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.49 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4212.31
MW Contribution:13.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936591AD2-074 C
Adder
5.9258823529411765.037
3150461FOUR RIVERD
50/50
3.4763.476
3150651CHESTF6
Adder
20.5870588235294117.499
946262AF1-291 E
Adder
1.58588235294117651.348
934576AD1-082 E
Adder
4.7623529411764714.048
933292AC2-141 E
Adder
14.03647058823529311.931
940492AE2-034 E
Adder
3.1905882352941182.712
944602AF1-125 E
Adder
110.2776470588235393.736
957871AF2-081 C
Adder
10.6988235294117659.094
3145506HICKORY
Adder
2.34000000000000031.989
943612AF1-032 E
Adder
0.99058823529411770.842
3130536PAPERMILL
Adder
7.1317647058823546.062
939602AE1-190 E
Adder
1.5282352941176471.299
936592AD2-074 E
Adder
9.6694117647058818.219
944631AF1-128 C
Adder
43.9294117647058937.34
315052AA1-145 CT2
50/50
5.6165.616
3150471FOUR RIVERE
50/50
3.4763.476
938552AE1-074 E
Adder
1.35529411764705881.152
3150411LDYSMT5
50/50
5.4185.418
316160AE1-175 E
Adder
1.30705882352941181.111
933291AC2-141 C
Adder
32.8811764705882427.949
926755AC1-161 E
Adder
14.03647058823529311.931
957872AF2-081 E
Adder
4.5847058823529413.897
925522AC1-027 E
Adder
1.31058823529411781.114
941102AE2-104 E
Adder
5.6988235294117654.844
3145256KINGFORK
Adder
1.09411764705882360.93
3150921YORKTN3
Adder
130.66235294117647111.063
939246AE1-155 E
Adder
9.2517647058823537.864
316004AC1-112 C
50/50
0.3640.364
3142296MT RD221
50/50
0.1350.135
944641AF1-129 C
Adder
113.0705882352941296.11
316240AF1-291 C
Adder
2.37882352941176432.022
924814AB2-134 E
Adder
13.88352941176470711.801
920042AA2-088 E OP
Adder
10.782352941176479.165
942342AE2-247 E
Adder
2.2129411764705881.881
919152AA1-139 E1
Adder
4.3752941176470593.719
943742AF1-042 E
Adder
5.05882352941176454.3
962862AG1-135 E
Adder
4.3023529411764713.657
966662AG1-536 E
Adder
7.686.528
3150401LDYSMT4
50/50
5.4015.401
942002AE2-212 E
Adder
1.57294117647058831.337
940431AE2-027 C
Adder
14.21058823529411812.079
944581AF1-123 C
Adder
48.9258823529411841.587
941101AE2-104 C
Adder
3.58470588235294143.047
934392AD1-063 E
Adder
1.1517647058823530.979
958261AF2-120 C
Adder
6.6447058823529415.648
3143316POE
Adder
1.4635294117647061.244
939191AE1-149 C
Adder
11.6529411764705889.905
901082W1-029 E
Adder
33.8176470588235328.745
934146AD1-041 E
Adder
3.8211764705882363.248
957601AF2-054 C
Adder
2.2717647058823531.931
963612AG1-210 E
Adder
1.04352941176470580.887
926412AC1-112 E
50/50
1.2521.252
3150441FOUR RIVERB
50/50
3.5273.527
3152261N ANNA2
50/50
40.26240.262
940642AE2-051 E
Adder
11.4905882352941179.767
934502AD1-074 E
Adder
8.9670588235294127.622
943462AF1-017 E
Adder
2.36588235294117682.011
942341AE2-247 C
Adder
1.60235294117647081.362
919153AA1-139 E2
Adder
4.3752941176470593.719
958162AF2-110 E
Adder
2.3270588235294121.978
964212AG1-282 E
Adder
1.4117647058823531.2
3150601CHESTF5
Adder
70.2058823529411759.675
3150431FOUR RIVERA
50/50
3.5273.527
966881AG1-559 C
50/50
2.7662.766
925332AB2-190 E
Adder
8.8811764705882377.549
963041AG1-153 C
Adder
5.3364705882352944.536
944011AF1-069 C
Adder
12.49058823529411910.617
927226AC1-216 E
Adder
8.4752941176470587.204
3145413WATKINS
Adder
0.71529411764705890.608
936666AD2-085 E
Adder
6.03294117647058855.128
962962AG1-145 E
Adder
1.5835294117647061.346
938771AE1-103 C
Adder
3.06470588235294142.605
944591AF1-124 C
Adder
49.141.735
944601AF1-125 C
Adder
48.17294117647059440.947
941591AE2-156 C
Adder
19.3216.422
964211AG1-282 C
Adder
2.11764705882352941.8
316076AC2-137 E
Adder
1.47529411764705891.254
966872AG1-558 E
Adder
1.341.139
966871AG1-558 C
Adder
2.662.261
3150831SPRUNCA
Adder
10.0964705882352958.582
3150841SPRUNCB
Adder
10.0964705882352958.582
3150391LDYSMT3
50/50
5.3915.391
316045AC1-158 C2
50/50
7.3677.367
316044AC1-158 C1
50/50
7.3677.367
923852AB2-025 E
Adder
1.16941176470588240.994
941032AE2-094 E
Adder
17.12117647058823514.553
941031AE2-094 C
Adder
38.2270588235294232.493
939412AE1-173 E
Adder
61.3576470588235452.154
916192Z1-068 E
Adder
2.0235294117647061.72
926662AC1-147 E
Adder
1.42941176470588241.215
957492AF2-043 E
Adder
1.52352941176470581.295
923842AB2-024 E
Adder
1.92941176470588241.64
316157AD2-030 E
Adder
1.27411764705882361.083
316169AC1-164 GEN
Adder
44.39529411764705537.736
930122AB1-027 E
50/50
1.5391.539
966882AG1-559 E
50/50
1.3931.393
939261AE1-157 C
50/50
16.15516.155
963042AG1-153 E
Adder
8.0047058823529426.804
316349AD2-085 C
Adder
3.6976470588235293.143
938772AE1-103 E
Adder
4.2317647058823533.597
916042Z1-036 E
Adder
29.97176470588235425.476
944592AF1-124 E
Adder
112.4411764705882595.575
944582AF1-123 E
Adder
112.0352941176470795.23
923832AB2-022 E
Adder
1.32117647058823541.123
935112AD1-144 E
Adder
1.0152941176470590.863
961952AG1-038 E
Adder
4.7329411764705884.023
961951AG1-038 C
Adder
3.42705882352941152.913
939262AE1-157 E
50/50
8.7638.763
944012AF1-069 E
Adder
4.8517647058823534.124
927042AC1-191 E
Adder
5.3188235294117654.521
316233AE1-074 C
Adder
2.69176470588235262.288
3150381LDYSMT2
50/50
5.2525.252
926739AC1-158 E1
50/50
19.2719.27
935162AD1-151 E
Adder
11.82117647058823610.048
943461AF1-017 C
Adder
1.44941176470588241.232
316311AC2-079 C
Adder
6.1564705882352945.233
932596AC2-079 E
Adder
10.0458823529411768.539
920692AA2-178 E
Adder
4.2541176470588233.616
917122Z2-027 E
Adder
1.4282352941176471.214
3146326AYDLETT TAP
Adder
1.44941176470588241.232
938532AE1-072 E
Adder
9.7976470588235298.328
940551AE2-041 C
Adder
7.67764705882352956.526
957832AF2-077 E
Adder
1.54588235294117651.314
3150701DARBY 4
50/50
2.8532.853
3142366NRTHEST
50/50
0.2060.206
315051AA1-145 CT1
50/50
5.6195.619
3150481FOUR RIVERF
50/50
4.2454.245
3150731STONECA
Adder
7.6200000000000016.477
935161AD1-151 C
Adder
17.7317647058823515.072
3145393UNCAMP
Adder
6.3329411764705885.383
938531AE1-072 C
Adder
18.79411764705882215.975
932046AC2-012 E
Adder
14.1412.019
958161AF2-110 C
Adder
1.46235294117647091.243
926785AC1-164_E
Adder
19.94588235294117616.954
926004AC1-076_E
Adder
4.277647058823533.636
316084AB2-161 E
Adder
5.9764705882352945.08
940641AE2-051 C
Adder
17.23529411764705814.65
3145946PLYMOUTH TP
Adder
0.33176470588235290.282
943471AF1-018 C
Adder
7.67764705882352956.526
943741AF1-042 C
Adder
3.10117647058823562.636
962861AG1-135 C
Adder
6.4529411764705885.485
3141813NORNECK
Adder
0.92588235294117650.787
3152251N ANNA1
50/50
40.24640.246
942001AE2-212 C
Adder
2.35882352941176482.005
939192AE1-149 E
Adder
7.7682352941176476.603
934501AD1-074 C
Adder
34.51411764705882529.337
937226AE2-253 E
Adder
6.265.321
934065AD1-033 E
Adder
5.3894117647058834.581
939312AE1-162 E
Adder
1.5552941176470591.322
958262AF2-120 E
Adder
4.4294117647058833.765
966661AG1-536 C
Adder
5.7152941176470584.858
316078AC2-138 E
Adder
0.97411764705882350.828
316312AB1-027 C
50/50
0.5850.585
3150451FOUR RIVERC
50/50
4.314.31
940432AE2-027 E
Adder
9.4729411764705888.052
939411AE1-173 C
Adder
92.0364705882352978.231
934012AD1-025 E
Adder
10.9729411764705889.327
913392Y1-086 E
Adder
2.34117647058823541.99
939612AE1-191 E
Adder
6.1141176470588245.197
957602AF2-054 E
Adder
1.51411764705882361.287
963611AG1-210 C
Adder
0.69529411764705880.591
3138116ELKO L286
Adder
1.53882352941176471.308
927041AC1-191 C
Adder
10.6788235294117659.077
3150371LDYSMT1
50/50
5.1855.185
926740AC1-158 E2
50/50
19.2719.27
940541AE2-040 C
Adder
2.89058823529411772.457
940481AE2-033 C
Adder
16.25647058823529513.818
940482AE2-033 E
Adder
10.969.316
925865AC1-065 E
Adder
17.8870588235294115.204
961611AG1-000B C
Adder
17.4070588235294114.796
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.37922.379
NYPJM->LTFIMP_NY
CLTF
2.722.72
TVALTFEXP_TVA->PJM
CLTF
6.1246.124
O66PJM->LTFIMP_O-066
CMTX_NF
36.64136.641
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.48890.488
WECLTFEXP_WEC->PJM
CLTF
0.640.64
LAGNLTFEXP_LAGN->PJM
CLTF
7.6467.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.3021.302
MECLTFEXP_MEC->PJM
CLTF
3.9143.914
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0355.035
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.06830.068
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7495.749
CPLELTFEXP_CPLE->PJM
CLTF
10.55810.558
SIGELTFEXP_SIGE->PJM
CLTF
0.2490.249

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.09 %
Rating:2442.12 MVA
Rating Type:A
MVA to Mitigate:2541.99
MW Contribution:12.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936591AD2-074 C
Adder
7.2670588235294116.177
316274AC1-208 C
Adder
8.6647058823529427.365
934576AD1-082 E
Adder
4.80941176470588254.088
918492AA1-063AE OP
Adder
4.17764705882352953.551
917332KELFORD E
Adder
1.74000000000000021.479
925122AB2-169 E
Adder
6.3976470588235295.438
943172AE2-346 E
Adder
0.66705882352941170.567
934522AD1-076 E
Adder
7.48117647058823556.359
933292AC2-141 E
50/50
20.21420.214
940492AE2-034 E
Adder
3.8317647058823533.257
944602AF1-125 E
50/50
147.882147.882
957871AF2-081 C
50/50
14.02714.027
3145506HICKORY
50/50
3.0893.089
943612AF1-032 E
Adder
1.2764705882352941.085
3130536PAPERMILL
50/50
9.1469.146
939602AE1-190 E
Adder
1.9247058823529411.636
936592AD2-074 E
Adder
11.85764705882353110.079
944631AF1-128 C
Adder
41.73529411764706535.475
926214AC1-099 E
Adder
1.18705882352941171.009
932632AC2-084 E
Adder
3.17764705882352952.701
316160AE1-175 E
50/50
1.8321.832
933291AC2-141 C
50/50
47.35447.354
926755AC1-161 E
50/50
20.21420.214
957872AF2-081 E
50/50
6.0126.012
316018AA1-139 ULT2
50/50
1.5131.513
925522AC1-027 E
50/50
1.7291.729
941102AE2-104 E
Adder
7.0717647058823536.011
3145256KINGFORK
50/50
1.4051.405
3150921YORKTN3
50/50
185.501185.501
939246AE1-155 E
Adder
11.1941176470588259.515
3145723EMPORIA
Adder
0.39411764705882360.335
923573AB1-173 E OP
Adder
3.06235294117647072.603
919692AA2-053 E OP
Adder
4.1705882352941183.545
924814AB2-134 E
Adder
14.67647058823529312.475
920042AA2-088 E OP
Adder
11.93294117647058910.143
934521AD1-076 C
Adder
14.67647058823529312.475
934511AD1-075 C
Adder
10.102352941176478.587
942342AE2-247 E
Adder
2.54235294117647072.161
919152AA1-139 E1
50/50
5.7365.736
316036AC1-147 C
50/50
0.5220.522
943741AF1-042 C
Adder
3.8023529411764713.232
962861AG1-135 C
Adder
7.8329411764705896.658
3141813NORNECK
Adder
1.09294117647058830.929
939192AE1-149 E
Adder
7.1047058823529416.039
924517AB2-100 E2
Adder
2.6788235294117652.277
934501AD1-074 C
Adder
40.41176470588235534.35
937226AE2-253 E
50/50
8.238.23
934065AD1-033 E
50/50
7.137.13
939312AE1-162 E
Adder
1.9235294117647061.635
943742AF1-042 E
Adder
6.20470588235294155.274
962862AG1-135 E
Adder
5.2211764705882354.438
966662AG1-536 E
Adder
9.2917647058823527.898
940431AE2-027 C
Adder
10.9364705882352939.296
316088AB2-174 E
Adder
6.03294117647058855.128
923994AB2-040_E
Adder
5.7423529411764714.881
316141AB2-099 E
Adder
0.27764705882352940.236
316294AC1-161 C
50/50
7.7117.711
944581AF1-123 C
50/50
65.6165.61
316185AD1-033 C
50/50
1.7411.741
916191Z1-068 C
50/50
0.0620.062
941101AE2-104 C
Adder
4.4482352941176473.781
934392AD1-063 E
50/50
1.4751.475
958261AF2-120 C
Adder
8.0388235294117656.833
3143316POE
Adder
1.19294117647058821.014
939191AE1-149 C
Adder
10.6576470588235289.059
926206AC1-098 E
Adder
3.5952941176470593.056
316382AG1-145 C
50/50
0.5420.542
901082W1-029 E
Adder
43.0176470588235336.565
3150981CHESPKA
50/50
0.6170.617
934146AD1-041 E
Adder
4.8129411764705894.091
957601AF2-054 C
Adder
2.92.465
963612AG1-210 E
Adder
1.23058823529411781.046
924516AB2-100 E1
Adder
2.6788235294117652.277
966621AG1-532 C
Adder
1.27294117647058851.082
940642AE2-051 E
Adder
11.79999999999999910.03
918532AA1-067 E
Adder
0.72588235294117650.617
918512AA1-065 E OP
Adder
6.2364705882352955.301
934502AD1-074 E
Adder
20.57176470588235517.486
934512AD1-075 E
Adder
5.1435294117647064.372
943462AF1-017 E
Adder
2.71882352941176462.311
942341AE2-247 C
Adder
1.84117647058823521.565
316159AE1-175 C
50/50
0.6010.601
919153AA1-139 E2
50/50
5.7365.736
316388AE2-253 GEN
50/50
2.7582.758
958162AF2-110 E
Adder
2.8870588235294122.454
964212AG1-282 E
Adder
1.6847058823529411.432
3150601CHESTF5
Adder
66.756.695
925332AB2-190 E
Adder
8.8411764705882367.515
963041AG1-153 C
Adder
4.884.148
960081AF2-299 C
Adder
1.69647058823529421.442
944011AF1-069 C
Adder
11.532941176470599.803
926072AC1-086 E
Adder
9.1682352941176477.793
927226AC1-216 E
Adder
8.9599999999999997.616
3145413WATKINS
Adder
0.82235294117647050.699
936666AD2-085 E
Adder
6.9317647058823545.892
962962AG1-145 E
50/50
2.2212.221
938771AE1-103 C
Adder
3.62470588235294143.081
944591AF1-124 C
50/50
65.84465.844
944601AF1-125 C
50/50
64.664.6
3151101ELIZAR3
50/50
4.6014.601
941591AE2-156 C
50/50
25.46125.461
964211AG1-282 C
Adder
2.5270588235294122.148
316076AC2-137 E
Adder
1.53647058823529431.306
923852AB2-025 E
Adder
1.040.884
941032AE2-094 E
Adder
15.80941176470588313.438
941031AE2-094 C
Adder
35.2988235294117730.004
934321AD1-056 C
Adder
2.15411764705882371.831
927022AC1-189 E
Adder
4.1023529411764713.487
939412AE1-173 E
Adder
67.656470588235357.508
961942AG1-037 E
Adder
0.370588235294117660.315
961941AG1-037 C
Adder
0.55529411764705880.472
916192Z1-068 E
50/50
2.672.67
3151081ELIZAR1
50/50
4.5444.544
926662AC1-147 E
50/50
1.8821.882
957492AF2-043 E
Adder
1.9635294117647061.669
923842AB2-024 E
50/50
2.4762.476
316157AD2-030 E
Adder
1.6270588235294121.383
316169AC1-164 GEN
50/50
57.50657.506
963042AG1-153 E
Adder
7.3188235294117656.221
946281AF1-292 C
Adder
1.40470588235294121.194
960082AF2-299 E
Adder
1.13058823529411770.961
926071AC1-086 C
Adder
20.14470588235294517.123
927021AC1-189 C
Adder
8.235294117647067
316349AD2-085 C
Adder
4.2482352941176483.611
938772AE1-103 E
Adder
5.00588235294117644.255
916042Z1-036 E
Adder
37.13529411764706431.565
944592AF1-124 E
50/50
150.785150.785
944582AF1-123 E
50/50
150.24150.24
923832AB2-022 E
Adder
1.7070588235294121.451
3151091ELIZAR2
50/50
4.4644.464
935112AD1-144 E
50/50
1.3041.304
316314AB2-024 C
50/50
0.4030.403
961952AG1-038 E
Adder
5.8035294117647064.933
961951AG1-038 C
Adder
4.20352941176470553.573
936582AD2-073 E
Adder
1.23176470588235291.047
946282AF1-292 E
Adder
0.93647058823529420.796
944012AF1-069 E
Adder
4.47999999999999953.808
917512Z2-088 E OP1
Adder
4.702352941176473.997
316316AC1-027 C
50/50
0.4470.447
3144216WINCHST
50/50
0.20.2
925865AC1-065 E
Adder
22.29058823529411618.947
966622AG1-532 E
Adder
0.84823529411764710.721
935162AD1-151 E
Adder
12.10588235294117610.29
943461AF1-017 C
Adder
1.66588235294117641.416
316311AC2-079 C
Adder
7.1458823529411766.074
932596AC2-079 E
Adder
11.6588235294117669.91
920692AA2-178 E
Adder
5.1082352941176474.342
3152331SURRY 2
50/50
43.89143.891
917122Z2-027 E
Adder
1.83411764705882341.559
3146326AYDLETT TAP
50/50
1.8931.893
938532AE1-072 E
50/50
12.8112.81
940551AE2-041 C
Adder
9.8305882352941178.356
957832AF2-077 E
50/50
2.0912.091
3150731STONECA
Adder
6.8694117647058835.839
935161AD1-151 C
Adder
18.1615.436
900672V4-068 E
Adder
0.395294117647058850.336
933981AD1-022 C
Adder
10.3435294117647068.792
3145393UNCAMP
Adder
7.4105882352941186.299
938531AE1-072 C
50/50
24.57324.573
932046AC2-012 E
50/50
18.61318.613
958161AF2-110 C
Adder
1.81529411764705871.543
926472AC1-118 E
Adder
1.13411764705882350.964
926785AC1-164_E
50/50
25.83625.836
927146AC1-208 E
Adder
3.8470588235294123.27
316084AB2-161 E
Adder
6.0352941176470595.13
940641AE2-051 C
Adder
17.715.045
933982AD1-022 E
Adder
5.6317647058823534.787
3145946PLYMOUTH TP
Adder
0.38941176470588240.331
316017AA1-139 ULT1
50/50
1.5131.513
943471AF1-018 C
Adder
9.8305882352941178.356
958262AF2-120 E
Adder
5.3588235294117644.555
966661AG1-536 C
Adder
6.91529411764705955.878
316078AC2-138 E
Adder
1.1482352941176470.976
940432AE2-027 E
Adder
7.2905882352941186.197
919710AA2-057 E
Adder
3.71882352941176463.161
3137643SOCKMAN
Adder
0.6764705882352940.575
939411AE1-173 C
Adder
101.4858823529411986.263
934012AD1-025 E
Adder
11.69.86
913392Y1-086 E
Adder
3.0235294117647062.57
3150991CHESPKB
50/50
1.0231.023
939612AE1-191 E
Adder
7.76.545
957602AF2-054 E
Adder
1.93294117647058841.643
963611AG1-210 C
Adder
0.820.697
3138116ELKO L286
Adder
1.60117647058823541.361
940541AE2-040 C
Adder
2.5717647058823532.186
940481AE2-033 C
Adder
14.5623529411764712.378
940482AE2-033 E
Adder
9.817647058823538.345
923263AB1-132 E OP
Adder
5.86235294117647054.983
316375AC2-012 C
50/50
1.9131.913
961611AG1-000B C
Adder
20.0529411764705917.045
316072AD1-144 C
50/50
0.3890.389
316059AD1-063 C
50/50
0.360.36
957831AF2-077 C
50/50
0.4830.483
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.05913.059
G-007PJM->LTFIMP_G-007
CMTX_NF
2.7242.724
CPLELTFEXP_CPLE->PJM
CLTF
8.9638.963
SIGELTFEXP_SIGE->PJM
CLTF
0.1170.117
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.5530.553
MECLTFEXP_MEC->PJM
CLTF
1.9921.992
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.274.27
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.06213.062
NYPJM->LTFIMP_NY
CLTF
1.3121.312
TVALTFEXP_TVA->PJM
CLTF
3.7783.778
O66PJM->LTFIMP_O-066
CMTX_NF
17.37617.376
CBM South 2LTFEXP_CBM-S2->PJM
CBM
70.8670.86
WECLTFEXP_WEC->PJM
CLTF
0.2830.283
LAGNLTFEXP_LAGN->PJM
CLTF
4.854.85

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.53 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4213.9
MW Contribution:13.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
936591AD2-074 C
Adder
6.0611764705882365.152
3150461FOUR RIVERD
50/50
3.5573.557
3150651CHESTF6
Adder
20.99647058823529717.847
946262AF1-291 E
Adder
1.61764705882352941.375
934576AD1-082 E
Adder
4.8541176470588244.126
934522AD1-076 E
Adder
6.5094117647058835.533
933292AC2-141 E
Adder
14.30941176470588312.163
940492AE2-034 E
Adder
3.25176470588235272.764
944602AF1-125 E
Adder
112.412941176470695.551
957871AF2-081 C
Adder
10.904705882352949.269
3145506HICKORY
Adder
2.38470588235294122.027
943612AF1-032 E
Adder
1.00941176470588250.858
3130536PAPERMILL
Adder
7.2870588235294126.194
939602AE1-190 E
Adder
1.56117647058823541.327
936592AD2-074 E
Adder
9.8894117647058838.406
944631AF1-128 C
Adder
44.8294117647058838.105
315052AA1-145 CT2
50/50
5.7475.747
3150471FOUR RIVERE
50/50
3.5573.557
934782AD1-105 E
Adder
2.9682352941176472.523
938552AE1-074 E
Adder
1.38000000000000011.173
3150411LDYSMT5
50/50
5.5725.572
316160AE1-175 E
Adder
1.33411764705882341.134
933291AC2-141 C
Adder
33.5211764705882428.493
926755AC1-161 E
Adder
14.30941176470588312.163
957872AF2-081 E
Adder
4.6741176470588233.973
925522AC1-027 E
Adder
1.3364705882352941.136
941102AE2-104 E
Adder
5.80941176470588254.938
3145256KINGFORK
Adder
1.11529411764705880.948
3150921YORKTN3
Adder
133.3164705882353113.319
939246AE1-155 E
Adder
9.4658823529411768.046
316004AC1-112 C
50/50
0.3720.372
3142296MT RD221
50/50
0.1380.138
944641AF1-129 C
Adder
115.3152941176470698.018
316240AF1-291 C
Adder
2.42588235294117642.062
924814AB2-134 E
Adder
14.1612.036
920042AA2-088 E OP
Adder
10.9811764705882359.334
934521AD1-076 C
Adder
12.77058823529411810.855
934511AD1-075 C
Adder
8.7917647058823527.473
942342AE2-247 E
Adder
2.2552941176470591.917
919152AA1-139 E1
Adder
4.463.791
943741AF1-042 C
Adder
3.1717647058823532.696
943742AF1-042 E
Adder
5.1741176470588234.398
962862AG1-135 E
Adder
4.40117647058823553.741
966662AG1-536 E
Adder
7.857647058823536.679
3150401LDYSMT4
50/50
5.5555.555
942002AE2-212 E
Adder
1.60352941176470591.363
940431AE2-027 C
Adder
14.49176470588235312.318
944581AF1-123 C
Adder
49.87411764705882442.393
941101AE2-104 C
Adder
3.65411764705882373.106
934392AD1-063 E
Adder
1.17647058823529421
958261AF2-120 C
Adder
6.7976470588235295.778
3143316POE
Adder
1.4917647058823531.268
939191AE1-149 C
Adder
11.8810.098
901082W1-029 E
Adder
34.4682352941176529.298
934146AD1-041 E
Adder
3.9035294117647063.318
957601AF2-054 C
Adder
2.321.972
963612AG1-210 E
Adder
1.06823529411764720.908
926412AC1-112 E
50/50
1.2791.279
3150441FOUR RIVERB
50/50
3.613.61
3152261N ANNA2
50/50
40.89340.893
924516AB2-100 E1
Adder
2.91411764705882352.477
940642AE2-051 E
Adder
11.7000000000000019.945
934502AD1-074 E
Adder
17.90117647058823615.216
934512AD1-075 E
Adder
4.4752941176470593.804
943462AF1-017 E
Adder
2.4117647058823532.05
942341AE2-247 C
Adder
1.63294117647058811.388
919153AA1-139 E2
Adder
4.463.791
958162AF2-110 E
Adder
2.3717647058823532.016
964212AG1-282 E
Adder
1.44470588235294131.228
3150601CHESTF5
Adder
71.6458823529411960.899
3150431FOUR RIVERA
50/50
3.613.61
966881AG1-559 C
50/50
2.8382.838
925332AB2-190 E
Adder
9.057647058823537.699
963041AG1-153 C
Adder
5.4305882352941184.616
944011AF1-069 C
Adder
12.71176470588235210.805
927226AC1-216 E
Adder
8.6447058823529417.348
3145413WATKINS
Adder
0.72823529411764710.619
936666AD2-085 E
Adder
6.1494117647058835.227
962962AG1-145 E
Adder
1.61647058823529431.374
938771AE1-103 C
Adder
3.12235294117647082.654
944591AF1-124 C
Adder
50.0517647058823542.544
944601AF1-125 C
Adder
49.1058823529411841.74
941591AE2-156 C
Adder
19.6952941176470616.741
964211AG1-282 C
Adder
2.16705882352941171.842
316076AC2-137 E
Adder
1.50588235294117641.28
966872AG1-558 E
Adder
1.36941176470588231.164
966871AG1-558 C
Adder
2.71882352941176462.311
3150831SPRUNCA
Adder
10.2905882352941188.747
3150841SPRUNCB
Adder
10.2905882352941188.747
3150391LDYSMT3
50/50
5.5445.544
923852AB2-025 E
Adder
1.19058823529411771.012
941032AE2-094 E
Adder
17.42588235294117614.812
941031AE2-094 C
Adder
38.9070588235294133.071
939412AE1-173 E
Adder
62.4952941176470653.121
916192Z1-068 E
Adder
2.0635294117647061.754
926662AC1-147 E
Adder
1.45764705882352951.239
957492AF2-043 E
Adder
1.55294117647058831.32
923842AB2-024 E
Adder
1.97176470588235291.676
316157AD2-030 E
Adder
1.30235294117647071.107
316169AC1-164 GEN
Adder
45.3376470588235338.537
930122AB1-027 E
50/50
1.5721.572
966882AG1-559 E
50/50
1.431.43
939261AE1-157 C
50/50
16.59116.591
963042AG1-153 E
Adder
8.1447058823529416.923
316349AD2-085 C
Adder
3.7682352941176473.203
938772AE1-103 E
Adder
4.3117647058823533.665
916042Z1-036 E
Adder
30.54352941176470525.962
944592AF1-124 E
Adder
114.6297.427
944582AF1-123 E
Adder
114.2058823529411997.075
923832AB2-022 E
Adder
1.34705882352941191.145
935112AD1-144 E
Adder
1.0352941176470590.88
961952AG1-038 E
Adder
4.8411764705882364.115
961951AG1-038 C
Adder
3.50588235294117642.98
939262AE1-157 E
50/50
8.9998.999
944012AF1-069 E
Adder
4.9388235294117654.198
925865AC1-065 E
Adder
18.27411764705882315.533
927042AC1-191 E
Adder
5.4376470588235294.622
316233AE1-074 C
Adder
2.73882352941176472.328
3150381LDYSMT2
50/50
5.4025.402
935162AD1-151 E
Adder
12.0576470588235310.249
943461AF1-017 C
Adder
1.47764705882352951.256
316311AC2-079 C
Adder
6.2752941176470595.334
932596AC2-079 E
Adder
10.2388235294117648.703
920692AA2-178 E
Adder
4.3352941176470593.685
917122Z2-027 E
Adder
1.4552941176470591.237
3146326AYDLETT TAP
Adder
1.47764705882352951.256
938532AE1-072 E
Adder
9.9870588235294138.489
940551AE2-041 C
Adder
7.8435294117647066.667
957832AF2-077 E
Adder
1.57882352941176471.342
3150701DARBY 4
50/50
2.9132.913
3142366NRTHEST
50/50
0.2110.211
315051AA1-145 CT1
50/50
5.755.75
3150481FOUR RIVERF
50/50
4.3444.344
3150731STONECA
Adder
7.7717647058823536.606
935161AD1-151 C
Adder
18.08588235294117715.373
3145393UNCAMP
Adder
6.4517647058823535.484
938531AE1-072 C
Adder
19.15764705882352816.284
932046AC2-012 E
Adder
14.41411764705882512.252
958161AF2-110 C
Adder
1.49058823529411751.267
926785AC1-164_E
Adder
20.36941176470588417.314
316084AB2-161 E
Adder
6.0929411764705895.179
940641AE2-051 C
Adder
17.55058823529411814.918
3145946PLYMOUTH TP
Adder
0.33764705882352940.287
943471AF1-018 C
Adder
7.8435294117647066.667
962861AG1-135 C
Adder
6.6023529411764715.612
3141813NORNECK
Adder
0.94823529411764720.806
3152251N ANNA1
50/50
40.87840.878
942001AE2-212 C
Adder
2.40588235294117642.045
939192AE1-149 E
Adder
7.9200000000000016.732
924517AB2-100 E2
Adder
2.91411764705882352.477
934501AD1-074 C
Adder
35.1647058823529429.89
937226AE2-253 E
Adder
6.3811764705882365.424
934065AD1-033 E
Adder
5.49411764705882364.67
939312AE1-162 E
Adder
1.58588235294117651.348
958262AF2-120 E
Adder
4.53176470588235253.852
966661AG1-536 C
Adder
5.8482352941176474.971
316078AC2-138 E
Adder
0.99647058823529410.847
316312AB1-027 C
50/50
0.5970.597
3150451FOUR RIVERC
50/50
4.414.41
940432AE2-027 E
Adder
9.6611764705882348.212
939411AE1-173 C
Adder
93.7423529411764679.681
934012AD1-025 E
Adder
11.1917647058823539.513
913392Y1-086 E
Adder
2.38588235294117632.028
939612AE1-191 E
Adder
6.2458823529411775.309
957602AF2-054 E
Adder
1.54705882352941181.315
963611AG1-210 C
Adder
0.7117647058823530.605
3138116ELKO L286
Adder
1.57058823529411761.335
927041AC1-191 C
Adder
10.915294117647069.278
3150371LDYSMT1
50/50
5.3335.333
940541AE2-040 C
Adder
2.94352941176470572.502
940481AE2-033 C
Adder
16.55647058823529614.073
940482AE2-033 E
Adder
11.1611764705882369.487
961611AG1-000B C
Adder
17.75176470588235515.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.18992.189
WECLTFEXP_WEC->PJM
CLTF
0.6690.669
LAGNLTFEXP_LAGN->PJM
CLTF
7.8427.842
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.04923.049
NYPJM->LTFIMP_NY
CLTF
2.6672.667
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
O66PJM->LTFIMP_O-066
CMTX_NF
35.97435.974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.55931.559
G-007PJM->LTFIMP_G-007
CMTX_NF
5.6455.645
CPLELTFEXP_CPLE->PJM
CLTF
10.74810.748
SIGELTFEXP_SIGE->PJM
CLTF
0.2590.259
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.3551.355
MECLTFEXP_MEC->PJM
CLTF
4.0634.063
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1265.126

Details for 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 568_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 568_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.01 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3639.35
MW Contribution:8.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
926615AC1-143 E
50/50
3.1393.139
3150651CHESTF6
Adder
11.80470588235294310.034
946262AF1-291 E
Adder
0.91058823529411770.774
934576AD1-082 E
Adder
2.76823529411764732.353
933292AC2-141 E
Adder
8.1494117647058816.927
944602AF1-125 E
Adder
64.2011764705882454.571
957871AF2-081 C
Adder
6.2388235294117655.303
3145506HICKORY
Adder
1.36235294117647051.158
943612AF1-032 E
Adder
0.57764705882352940.491
3130536PAPERMILL
Adder
3.9835294117647063.386
939602AE1-190 E
Adder
0.85529411764705890.727
944631AF1-128 C
Adder
24.86705882352941221.137
938552AE1-074 E
Adder
0.79529411764705890.676
934862AD1-115 E
50/50
5.1585.158
938562AE1-075 E
Adder
0.65058823529411770.553
316160AE1-175 E
Adder
0.74117647058823530.63
933291AC2-141 C
Adder
19.09176470588235516.228
926755AC1-161 E
Adder
8.1494117647058816.927
957872AF2-081 E
Adder
2.67411764705882372.273
925522AC1-027 E
Adder
0.76235294117647070.648
941102AE2-104 E
Adder
3.32823529411764742.829
3145256KINGFORK
Adder
0.63529411764705890.54
3150921YORKTN3
Adder
74.6435294117647263.447
963032AG1-152 E
50/50
9.9779.977
926502AC1-121 E
50/50
1.0641.064
944641AF1-129 C
Adder
64.8341176470588355.109
316240AF1-291 C
Adder
1.36588235294117651.161
924814AB2-134 E
Adder
7.9717647058823536.776
942342AE2-247 E
Adder
1.28941176470588251.096
919152AA1-139 E1
Adder
2.5505882352941182.168
958502AF2-144 E
Adder
0.74941176470588230.637
3152251N ANNA1
50/50
25.66925.669
316192AB2-158 C
50/50
1.5911.591
942001AE2-212 C
Adder
1.36235294117647051.158
939192AE1-149 E
Adder
4.5070588235294123.831
937226AE2-253 E
Adder
3.64941176470588243.102
934065AD1-033 E
Adder
3.1388235294117652.668
939312AE1-162 E
Adder
0.90.765
3150301M RUN C
50/50
4.5794.579
3150281M RUN A
50/50
4.5814.581
3151801S ANNAS2
50/50
0.8990.899
942002AE2-212 E
Adder
0.90823529411764710.772
940431AE2-027 C
Adder
8.1647058823529426.94
944581AF1-123 C
Adder
28.48352941176470724.211
941101AE2-104 C
Adder
2.0929411764705881.779
934392AD1-063 E
Adder
0.64352941176470590.547
316164AC1-076_C
50/50
0.6630.663
316006AB2-029 C
50/50
0.2070.207
939221AE1-153 C
50/50
14.35714.357
3143316POE
Adder
0.8517647058823530.724
939191AE1-149 C
Adder
6.7600000000000015.746
901082W1-029 E
Adder
19.80352941176470316.833
934146AD1-041 E
Adder
2.13764705882352951.817
926412AC1-112 E
Adder
0.69529411764705880.591
934861AD1-115 C
50/50
3.1623.162
3152261N ANNA2
50/50
25.67925.679
940642AE2-051 E
Adder
6.837647058823535.812
943462AF1-017 E
Adder
1.37882352941176461.172
942341AE2-247 C
Adder
0.93411764705882360.794
919153AA1-139 E2
Adder
2.5505882352941182.168
958162AF2-110 E
Adder
1.35882352941176481.155
3150601CHESTF5
Adder
39.7423529411764733.781
316170AC1-121 C
50/50
2.262.26
925332AB2-190 E
Adder
5.0905882352941184.327
963041AG1-153 C
Adder
3.22823529411764732.744
944011AF1-069 C
Adder
7.5129411764705896.386
927226AC1-216 E
Adder
4.8670588235294114.137
936666AD2-085 E
Adder
3.51647058823529422.989
962962AG1-145 E
Adder
0.89764705882352950.763
938771AE1-103 C
Adder
1.80588235294117651.535
944591AF1-124 C
Adder
28.58470588235294224.297
944601AF1-125 C
Adder
28.04470588235294323.838
941591AE2-156 C
Adder
11.2364705882352949.551
316076AC2-137 E
Adder
0.82705882352941170.703
966872AG1-558 E
Adder
0.73647058823529410.626
966871AG1-558 C
Adder
1.46235294117647091.243
3150831SPRUNCA
Adder
5.8117647058823544.94
3150841SPRUNCB
Adder
5.8117647058823544.94
316411AF1-147_GEN1
Adder
-4.0458823529411765-3.439
923862AB2-026 E
Adder
0.76235294117647070.648
316045AC1-158 C2
50/50
5.6365.636
316044AC1-158 C1
50/50
5.6365.636
3151791S ANNAG2
50/50
1.751.75
3151781S ANNAS1
50/50
0.8990.899
3151771S ANNAG1
50/50
1.751.75
923852AB2-025 E
Adder
0.69411764705882350.59
941032AE2-094 E
Adder
10.297647058823538.753
941031AE2-094 C
Adder
22.99176470588235319.543
939412AE1-173 E
Adder
36.316470588235330.869
916192Z1-068 E
Adder
1.17764705882352931.001
926662AC1-147 E
Adder
0.8317647058823530.707
957492AF2-043 E
Adder
0.88823529411764710.755
923842AB2-024 E
Adder
1.07764705882352940.916
316169AC1-164 GEN
Adder
24.84352941176470621.117
930122AB1-027 E
Adder
0.85411764705882350.726
316415AF1-147_GEN2
Adder
-4.0458823529411765-3.439
923892AB2-029 E
50/50
2.0392.039
939222AE1-153 E
50/50
9.5719.571
925022AB2-158 E
50/50
4.2284.228
963042AG1-153 E
Adder
4.842352941176474.116
316349AD2-085 C
Adder
2.1552941176470591.832
938772AE1-103 E
Adder
2.49294117647058842.119
916042Z1-036 E
Adder
17.63882352941176614.993
944592AF1-124 E
Adder
65.4611764705882455.642
944582AF1-123 E
Adder
65.2247058823529555.441
923832AB2-022 E
Adder
0.7717647058823530.656
935112AD1-144 E
Adder
0.59058823529411760.502
316267AC1-143 C
50/50
6.8796.879
316257AC1-043 C
50/50
6.3236.323
316254AC1-120 C
50/50
6.5816.581
944012AF1-069 E
Adder
2.9188235294117652.481
925865AC1-065 E
Adder
10.0070588235294128.506
927042AC1-191 E
Adder
2.9258823529411772.487
316233AE1-074 C
Adder
1.57882352941176471.342
3150241REMNGT4
50/50
4.1084.108
926739AC1-158 E1
50/50
14.74214.742
966002AG1-469 E
50/50
0.7050.705
935162AD1-151 E
Adder
6.7811764705882355.764
943461AF1-017 C
Adder
0.84470588235294120.718
316311AC2-079 C
Adder
3.58941176470588273.051
932596AC2-079 E
Adder
5.8564705882352944.978
917122Z2-027 E
Adder
0.83529411764705890.71
3146326AYDLETT TAP
Adder
0.84588235294117640.719
938532AE1-072 E
Adder
5.7152941176470584.858
940551AE2-041 C
Adder
4.2894117647058823.646
957832AF2-077 E
Adder
0.87411764705882360.743
3150211REMNGT1
50/50
4.0534.053
3150231REMNGT3
50/50
4.6034.603
963031AG1-152 C
50/50
6.6516.651
926486AC1-120 E
50/50
3.393.39
3150731STONECA
Adder
4.3564705882352943.703
935161AD1-151 C
Adder
10.1717647058823558.646
3145393UNCAMP
Adder
3.73882352941176473.178
938531AE1-072 C
Adder
10.9647058823529419.32
932046AC2-012 E
Adder
8.2235294117647076.99
958161AF2-110 C
Adder
0.85411764705882350.726
926785AC1-164_E
Adder
11.1611764705882369.487
926004AC1-076_E
50/50
3.7993.799
316336AC2-165 C
Adder
6.1258823529411775.207
316084AB2-161 E
Adder
3.47411764705882352.953
940641AE2-051 C
Adder
10.2564705882352948.718
943471AF1-018 C
Adder
4.2894117647058823.646
3150291M RUN B
50/50
4.5454.545
933502AC2-165 E
Adder
4.6105882352941173.919
940432AE2-027 E
Adder
5.4435294117647064.627
939411AE1-173 C
Adder
54.4741176470588246.303
934012AD1-025 E
Adder
6.3011764705882355.356
913392Y1-086 E
Adder
1.36823529411764721.163
939612AE1-191 E
Adder
3.422.907
3138116ELKO L286
Adder
0.86235294117647050.733
927041AC1-191 C
Adder
5.8741176470588244.993
3150221REMNGT2
50/50
4.0914.091
925672AC1-043 E
50/50
10.31710.317
926740AC1-158 E2
50/50
14.74214.742
966001AG1-469 C
50/50
1.4091.409
940541AE2-040 C
Adder
1.71529411764705891.458
940481AE2-033 C
Adder
9.6588235294117668.21
940482AE2-033 E
Adder
6.5117647058823535.535
961611AG1-000B C
Adder
10.0211764705882368.518
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.68919.689
NYPJM->LTFIMP_NY
CLTF
2.5742.574
TVALTFEXP_TVA->PJM
CLTF
4.9884.988
O66PJM->LTFIMP_O-066
CMTX_NF
36.63136.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
61.60961.609
WECLTFEXP_WEC->PJM
CLTF
0.710.71
LAGNLTFEXP_LAGN->PJM
CLTF
6.216.21
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
1.3821.382
MECLTFEXP_MEC->PJM
CLTF
3.9063.906
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.2763.276
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.58334.583
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7675.767
CPLELTFEXP_CPLE->PJM
CLTF
6.8626.862
SIGELTFEXP_SIGE->PJM
CLTF
0.2540.254

Details for 8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.31 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4286.27
MW Contribution:42.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961792AG1-021 E
Adder
1.96705882352941171.672
3152661PLYWOOD A
50/50
2.0932.093
937482AD2-202 E
50/50
2.4072.407
3151021BRUNSWICKG1
50/50
25.15825.158
932763AC2-100 E
50/50
4.6734.673
964242AG1-285 E
50/50
11.38411.384
964792AG1-342 E
50/50
3.8443.844
924162AB2-060 E OP
50/50
5.8965.896
313527AB2-043 C
50/50
0.7110.711
3151641KERR 7
50/50
1.6151.615
3151031BRUNSWICKG2
50/50
25.15825.158
933291AC2-141 C
Adder
-32.203529411764706-27.373
944641AF1-129 C
Adder
-90.49176470588236-76.918
316240AF1-291 C
Adder
-1.9317647058823528-1.642
940082AE1-250 E
Adder
8.5741176470588247.288
942751AE2-291 C
Adder
12.11176470588235310.295
316205AC1-080 C
50/50
0.4520.452
316123AC1-075 C
50/50
1.3531.353
959311AF2-222 C
50/50
22.05622.056
937481AD2-202 C
50/50
0.8240.824
3151591KERR 2
50/50
1.6151.615
925785AC1-054 E
Adder
2.96470588235294132.52
942001AE2-212 C
Adder
-2.010588235294118-1.709
942461AE2-259 C
Adder
12.19882352941176510.369
936162AD2-022 E
Adder
7.29529411764705856.201
946301AF1-294 C
Adder
4.7458823529411774.034
316283AC2-100 C
50/50
2.1162.116
935172AD1-152 E
50/50
11.76211.762
934621AD1-088 C
50/50
21.36821.368
957482AF2-042 E
50/50
86.59186.591
24401205PINNACLE
Adder
1.6670588235294121.417
946302AF1-294 E
Adder
4.01882352941176453.416
316003AC1-222 C
50/50
1.7441.744
943902AF1-058 E
50/50
2.342.34
924322AB2-079 E O1
50/50
1.8631.863
957481AF2-042 C
50/50
129.887129.887
940081AE1-250 C
Adder
12.86117647058823510.932
942462AE2-259 E
Adder
8.1329411764705886.913
925997AC1-075 E
50/50
4.7084.708
964791AG1-342 C
50/50
5.7665.766
316239AB2-077 C O1
50/50
0.4550.455
3151041BRUNSWICKG3
50/50
25.15825.158
957601AF2-054 C
Adder
-1.8-1.53
926024AC1-080 E
50/50
1.5621.562
936161AD2-022 C
Adder
12.15882352941176610.335
959312AF2-222 E
50/50
14.77814.778
3147223TWITTYS
50/50
1.2661.266
924022AB2-043 E O1
50/50
7.1597.159
935171AD1-152 C
50/50
2.8492.849
3151601KERR 3
50/50
1.6151.615
3151581KERR 1
50/50
0.5770.577
936171AD2-023 C
Adder
7.0929411764705886.029
961791AG1-021 C
Adder
2.30941176470588251.963
936261AD2-033 C
50/50
17.43217.432
316248AF1-058 C
50/50
0.5710.571
962562AG1-105 E
50/50
9.4059.405
3151531CLOVER1
50/50
28.86828.868
963041AG1-153 C
50/50
17.10317.103
964211AG1-282 C
Adder
-1.7011764705882353-1.446
958211AF2-115 C
Adder
2.88588235294117632.453
936262AD2-033 E
50/50
11.62211.622
3151051BRUNSWICKS1
50/50
52.26552.265
936172AD2-023 E
Adder
3.8505882352941183.273
958212AF2-115 E
Adder
2.45882352941176442.09
316034AC1-036 C
50/50
0.3110.311
316118AC1-105 C
50/50
1.5721.572
964241AG1-285 C
50/50
17.07617.076
962561AG1-105 C
50/50
14.10814.108
3151541CLOVER2
50/50
28.59928.599
963042AG1-153 E
50/50
25.65425.654
3138533PONTONDP
Adder
0.85529411764705890.727
316131AB2-060 C
50/50
2.042.04
3151631KERR 6
50/50
1.6151.615
3147133PAMPLIN
Adder
1.261.071
927264AC1-222 E
50/50
7.1497.149
3152411Z1-086 GT1
50/50
33.47433.474
3152441Z1-086 ST
50/50
58.26658.266
942752AE2-291 E
Adder
8.0741176470588246.863
924302AB2-077 E O1
50/50
1.8631.863
316238AB2-078 C O1
50/50
0.4550.455
3152421Z1-086 GT2
50/50
33.46533.465
938531AE1-072 C
Adder
-16.01294117647059-13.611
316222AC1-221 C
50/50
2.6372.637
927255AC1-221 E
50/50
6.9166.916
316237AB2-079 C O1
50/50
0.4550.455
934622AD1-088 E
50/50
10.28810.288
934611AD1-087 C
50/50
2.842.84
934612AD1-087 E
50/50
8.2238.223
3151621KERR 5
50/50
1.6151.615
3151611KERR 4
50/50
1.6151.615
940641AE2-051 C
Adder
-21.040000000000003-17.884
925612AC1-036 E
50/50
1.1421.142
926274AC1-105 E
50/50
4.6164.616
924312AB2-078 E O1
50/50
1.8631.863
3152431Z1-086 GT3
50/50
33.46533.465
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
WECLTFEXP_WEC->PJM
CLTF
1.451.45
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
NYPJM->LTFIMP_NY
CLTF
2.1082.108
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
O66PJM->LTFIMP_O-066
CMTX_NF
29.75629.756
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6814.681
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.94 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3379.54
MW Contribution:10.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150861SPRUNCD
50/50
0.1320.132
3150651CHESTF6
Adder
14.8105882352941212.589
946262AF1-291 E
Adder
1.14588235294117660.974
3151021BRUNSWICKG1
50/50
6.3966.396
934576AD1-082 E
Adder
3.5411764705882353.01
933292AC2-141 E
50/50
10.44910.449
944602AF1-125 E
50/50
82.45882.458
957871AF2-081 C
Adder
7.9988235294117666.799
3145506HICKORY
Adder
1.7482352941176471.486
943612AF1-032 E
Adder
0.740.629
944631AF1-128 C
Adder
30.4447058823529425.878
3150851SPRUNCC
50/50
0.1320.132
938552AE1-074 E
50/50
1.0491.049
938562AE1-075 E
Adder
0.82470588235294120.701
3151031BRUNSWICKG2
50/50
6.3966.396
316160AE1-175 E
Adder
0.90941176470588240.773
933291AC2-141 C
50/50
24.47824.478
926755AC1-161 E
50/50
10.44910.449
957872AF2-081 E
Adder
3.42823529411764752.914
925522AC1-027 E
Adder
0.97764705882352940.831
941102AE2-104 E
Adder
4.2623529411764713.623
3145256KINGFORK
Adder
0.81058823529411760.689
3150921YORKTN3
Adder
92.9023529411764778.967
944641AF1-129 C
Adder
81.343529411764769.142
316240AF1-291 C
Adder
1.721.462
924814AB2-134 E
Adder
10.004705882352948.504
942342AE2-247 E
Adder
1.65176470588235281.404
919152AA1-139 E1
Adder
3.27058823529411762.78
958502AF2-144 E
Adder
0.95058823529411770.808
3152251N ANNA1
50/50
47.55247.552
316192AB2-158 C
50/50
1.8381.838
942001AE2-212 C
50/50
1.7341.734
939192AE1-149 E
50/50
5.7625.762
924517AB2-100 E2
Adder
2.21882352941176461.886
937226AE2-253 E
Adder
4.6788235294117653.977
934065AD1-033 E
Adder
4.0258823529411773.422
939312AE1-162 E
Adder
1.14235294117647060.971
942002AE2-212 E
50/50
1.1561.156
940431AE2-027 C
Adder
10.2917647058823528.748
957481AF2-042 C
Adder
12.04117647058823510.235
316294AC1-161 C
50/50
3.9863.986
944581AF1-123 C
50/50
36.58436.584
941101AE2-104 C
Adder
2.68117647058823532.279
316164AC1-076_C
50/50
0.8170.817
3143316POE
50/50
1.1011.101
939191AE1-149 C
50/50
8.6438.643
3151041BRUNSWICKG3
50/50
6.3966.396
901082W1-029 E
Adder
25.35058823529411521.548
3152261N ANNA2
50/50
47.5747.57
924516AB2-100 E1
Adder
2.21882352941176461.886
940642AE2-051 E
50/50
9.2539.253
943462AF1-017 E
Adder
1.76470588235294111.5
942341AE2-247 C
Adder
1.19529411764705881.016
919153AA1-139 E2
Adder
3.27058823529411762.78
958162AF2-110 E
Adder
1.74000000000000021.479
3150601CHESTF5
Adder
48.65647058823529441.358
925332AB2-190 E
Adder
6.3717647058823535.416
963041AG1-153 C
50/50
4.3484.348
944011AF1-069 C
50/50
10.20810.208
927226AC1-216 E
Adder
6.1082352941176475.192
3145413WATKINS
Adder
0.54117647058823540.46
936666AD2-085 E
Adder
4.5011764705882353.826
962962AG1-145 E
Adder
1.10235294117647080.937
938771AE1-103 C
Adder
2.30941176470588251.963
944591AF1-124 C
50/50
36.71436.714
944601AF1-125 C
50/50
36.02136.021
3151101ELIZAR3
50/50
2.5992.599
941591AE2-156 C
Adder
14.39882352941176612.239
316076AC2-137 E
Adder
0.99176470588235290.843
3150831SPRUNCA
50/50
7.377.37
3150841SPRUNCB
50/50
7.377.37
923862AB2-026 E
Adder
0.96705882352941170.822
316045AC1-158 C2
50/50
14.72914.729
316044AC1-158 C1
50/50
14.72914.729
923852AB2-025 E
Adder
0.90941176470588240.773
3151051BRUNSWICKS1
50/50
13.28713.287
941032AE2-094 E
50/50
13.99213.992
941031AE2-094 C
50/50
31.24231.242
939412AE1-173 E
50/50
48.51748.517
916192Z1-068 E
Adder
1.51058823529411781.284
3151081ELIZAR1
50/50
2.5662.566
926662AC1-147 E
Adder
1.06470588235294120.905
957492AF2-043 E
Adder
1.13882352941176480.968
316169AC1-164 GEN
Adder
29.7105882352941225.254
925022AB2-158 E
50/50
4.8864.886
963042AG1-153 E
50/50
6.5226.522
316349AD2-085 C
Adder
2.7588235294117652.345
938772AE1-103 E
Adder
3.18941176470588242.711
916042Z1-036 E
Adder
22.54588235294117719.164
944592AF1-124 E
50/50
84.07784.077
944582AF1-123 E
50/50
83.77383.773
923832AB2-022 E
Adder
0.98941176470588230.841
3151091ELIZAR2
50/50
2.5212.521
935112AD1-144 E
Adder
0.75294117647058820.64
944012AF1-069 E
50/50
3.9663.966
316233AE1-074 C
50/50
2.0822.082
926739AC1-158 E1
50/50
38.52538.525
3152411Z1-086 GT1
50/50
8.198.19
3152441Z1-086 ST
50/50
14.25614.256
935162AD1-151 E
Adder
8.4988235294117667.224
943461AF1-017 C
Adder
1.08235294117647070.92
316311AC2-079 C
Adder
4.5952941176470593.906
932596AC2-079 E
Adder
7.497647058823536.373
917122Z2-027 E
Adder
1.06941176470588250.909
3146326AYDLETT TAP
Adder
1.08470588235294120.922
938532AE1-072 E
Adder
7.3270588235294126.228
957832AF2-077 E
Adder
1.07764705882352940.916
3150731STONECA
Adder
5.4305882352941184.616
3152421Z1-086 GT2
50/50
8.1888.188
935161AD1-151 C
Adder
12.74823529411764710.836
3145393UNCAMP
Adder
4.7823529411764714.065
938531AE1-072 C
Adder
14.05529411764705811.947
932046AC2-012 E
Adder
10.5364705882352958.956
958161AF2-110 C
Adder
1.09411764705882360.93
926785AC1-164_E
Adder
13.34823529411764811.346
926004AC1-076_E
50/50
4.684.68
316084AB2-161 E
Adder
4.4435294117647063.777
940641AE2-051 C
50/50
13.8813.88
940432AE2-027 E
Adder
6.8611764705882355.832
939411AE1-173 C
50/50
72.77672.776
934012AD1-025 E
Adder
7.9070588235294126.721
913392Y1-086 E
Adder
1.75294117647058821.49
3138116ELKO L286
Adder
1.03411764705882360.879
926740AC1-158 E2
50/50
38.52538.525
940541AE2-040 C
Adder
2.24941176470588241.912
940481AE2-033 C
Adder
12.64705882352941110.75
940482AE2-033 E
Adder
8.5258823529411767.247
3152431Z1-086 GT3
50/50
8.1888.188
961611AG1-000B C
Adder
12.62823529411764810.734
316303AF2-085
50/50
3.2933.293
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
LGEELTFEXP_LGEE->PJM
CLTF
0.8310.831
MECLTFEXP_MEC->PJM
CLTF
2.5882.588
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.9113.911
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.47618.476
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2794.279
CPLELTFEXP_CPLE->PJM
CLTF
8.2058.205
SIGELTFEXP_SIGE->PJM
CLTF
0.1630.163
CBM South 2LTFEXP_CBM-S2->PJM
CBM
69.2669.26
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
LAGNLTFEXP_LAGN->PJM
CLTF
5.5035.503
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.62115.621
NYPJM->LTFIMP_NY
CLTF
2.0512.051
TVALTFEXP_TVA->PJM
CLTF
4.3954.395
O66PJM->LTFIMP_O-066
CMTX_NF
27.29527.295
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 568_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1                /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
313373 to 314765 ckt 1
313707 to 313373 ckt 1
314322 to 314914 ckt 1
314765 to 314749 ckt 1
314905 to 314900 ckt 1
314903 to 314908 ckt 1
314911 to 314905 ckt 1
314916 to 314913 ckt 1
314940 to 941030 ckt 1
314934 to 314916 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AG1-153 was evaluated as a 75.0 MW injection and 75.0 MW withdrawal in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC113.52 %678.68B770.464.4
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC106.87 %678.68B725.295.34
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC113.06 %678.68B767.34.4
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC106.41 %678.68B722.165.34

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.52 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:770.46
MW Contribution:4.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.06 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:814.81
MW Contribution:4.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.0258.025
3150651CHESTF6
80/20
3.3173.317
3150831SPRUNCA
80/20
1.4311.431
3150841SPRUNCB
80/20
1.4311.431
3156056W1-029WIND
80/20
0.5460.546
3156116Z1-036WIND
80/20
0.9860.986
901082W1-029 E
80/20
3.6623.662
916042Z1-036 E
80/20
6.626.62
916192Z1-068 E
80/20
0.2130.213
941032AE2-094 E
80/20
11.86611.866
944012AF1-069 E
80/20
3.8773.877
961942AG1-037 E
80/20
0.0860.086
963041AG1-153 C
80/20
1.7621.762
963042AG1-153 E
80/20
2.6422.642
916191Z1-068 C
80/20
0.030.03
961611AG1-000B C
80/20
1.5261.526
940541AE2-040 C
80/20
0.8680.868
941591AE2-156 C
80/20
5.0815.081
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
80/20
10.29210.292
944582AF1-123 E
80/20
23.56823.568
944591AF1-124 C
80/20
10.32910.329
944592AF1-124 E
80/20
23.65323.653
944601AF1-125 C
80/20
10.13310.133
944602AF1-125 E
80/20
23.19823.198
944631AF1-128 C
80/20
20.96620.966
944641AF1-129 C
80/20
30.36730.367
961612AG1-000B E
80/20
2.2892.289
316303AF2-085
80/20
1.8321.832
958502AF2-144 E
Adder
2.8294117647058822.405
943573AF1-028 BT
80/20
15.77615.776

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.87 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:725.29
MW Contribution:5.34
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.49 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:777.05
MW Contribution:5.55
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.4243.424
3150831SPRUNCA
80/20
1.4991.499
3150841SPRUNCB
80/20
1.4991.499
3151311EDGECMA
80/20
2.4292.429
3156056W1-029WIND
80/20
0.6050.605
3156116Z1-036WIND
80/20
1.11.1
901082W1-029 E
80/20
4.0534.053
916042Z1-036 E
80/20
7.3857.385
916192Z1-068 E
80/20
0.2340.234
941032AE2-094 E
80/20
14.50614.506
944012AF1-069 E
80/20
4.744.74
961942AG1-037 E
80/20
0.0980.098
963041AG1-153 C
80/20
2.1352.135
963042AG1-153 E
80/20
3.2023.202
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5981.598
940541AE2-040 C
80/20
1.0031.003
941591AE2-156 C
80/20
5.5525.552
943571AF1-028 C
Adder
-12.025882352941176-10.222
944581AF1-123 C
80/20
11.29511.295
944582AF1-123 E
80/20
25.86425.864
944591AF1-124 C
80/20
11.33511.335
944592AF1-124 E
80/20
25.95725.957
944601AF1-125 C
80/20
11.12111.121
944602AF1-125 E
80/20
25.45825.458
944641AF1-129 C
80/20
31.34631.346
961602AG1-000A E
80/20
1.8891.889
961612AG1-000B E
80/20
2.3972.397
316303AF2-085
80/20
2.1022.102
958502AF2-144 E
Adder
3.01882352941176452.566
943573AF1-028 BT
80/20
12.02612.026

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.06 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:767.3
MW Contribution:4.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.58 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:811.58
MW Contribution:4.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.0258.025
3150651CHESTF6
80/20
3.3173.317
3150831SPRUNCA
80/20
1.4311.431
3150841SPRUNCB
80/20
1.4311.431
3156056W1-029WIND
80/20
0.5460.546
3156116Z1-036WIND
80/20
0.9860.986
901082W1-029 E
80/20
3.6623.662
916042Z1-036 E
80/20
6.626.62
916192Z1-068 E
80/20
0.2130.213
941032AE2-094 E
80/20
11.86611.866
944012AF1-069 E
80/20
3.8773.877
961942AG1-037 E
80/20
0.0860.086
963041AG1-153 C
80/20
1.7621.762
963042AG1-153 E
80/20
2.6422.642
916191Z1-068 C
80/20
0.030.03
961611AG1-000B C
80/20
1.5261.526
940541AE2-040 C
80/20
0.8680.868
941591AE2-156 C
80/20
5.0815.081
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
80/20
10.29210.292
944582AF1-123 E
80/20
23.56823.568
944591AF1-124 C
80/20
10.32910.329
944592AF1-124 E
80/20
23.65323.653
944601AF1-125 C
80/20
10.13310.133
944602AF1-125 E
80/20
23.19823.198
944631AF1-128 C
80/20
20.96620.966
944641AF1-129 C
80/20
30.36730.367
961612AG1-000B E
80/20
2.2892.289
316303AF2-085
80/20
1.8321.832
958502AF2-144 E
Adder
2.8294117647058822.405
943573AF1-028 BT
80/20
15.77615.776

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.41 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:722.16
MW Contribution:5.34
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.03 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:773.88
MW Contribution:5.55
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.4243.424
3150831SPRUNCA
80/20
1.4991.499
3150841SPRUNCB
80/20
1.4991.499
3151311EDGECMA
80/20
2.4292.429
3156056W1-029WIND
80/20
0.6050.605
3156116Z1-036WIND
80/20
1.11.1
901082W1-029 E
80/20
4.0534.053
916042Z1-036 E
80/20
7.3857.385
916192Z1-068 E
80/20
0.2340.234
941032AE2-094 E
80/20
14.50614.506
944012AF1-069 E
80/20
4.744.74
961942AG1-037 E
80/20
0.0980.098
963041AG1-153 C
80/20
2.1352.135
963042AG1-153 E
80/20
3.2023.202
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5981.598
940541AE2-040 C
80/20
1.0031.003
941591AE2-156 C
80/20
5.5525.552
943571AF1-028 C
Adder
-12.025882352941176-10.222
944581AF1-123 C
80/20
11.29511.295
944582AF1-123 E
80/20
25.86425.864
944591AF1-124 C
80/20
11.33511.335
944592AF1-124 E
80/20
25.95725.957
944601AF1-125 C
80/20
11.12111.121
944602AF1-125 E
80/20
25.45825.458
944641AF1-129 C
80/20
31.34631.346
961602AG1-000A E
80/20
1.8891.889
961612AG1-000B E
80/20
2.3972.397
316303AF2-085
80/20
2.1022.102
958502AF2-144 E
Adder
3.01882352941176452.566
943573AF1-028 BT
80/20
12.02612.026
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC110.03 %661.76B728.154.39
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC101.32 %661.76B670.55.17
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC111.3 %661.76B736.514.39
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC102.58 %661.76B678.835.17
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC108.36 %661.76B717.074.39

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.03 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:728.15
MW Contribution:4.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.398.39
3150651CHESTF6
80/20
3.4453.445
3150831SPRUNCA
80/20
1.4641.464
3150841SPRUNCB
80/20
1.4641.464
3156056W1-029WIND
80/20
0.5590.559
3156116Z1-036WIND
80/20
1.0071.007
901082W1-029 E
80/20
3.7483.748
916042Z1-036 E
80/20
6.7636.763
916192Z1-068 E
80/20
0.2190.219
941032AE2-094 E
80/20
11.9111.91
944012AF1-069 E
80/20
3.8913.891
961942AG1-037 E
80/20
0.0870.087
963041AG1-153 C
80/20
1.7571.757
963042AG1-153 E
80/20
2.6362.636
916191Z1-068 C
80/20
0.0310.031
961611AG1-000B C
80/20
1.5771.577
940541AE2-040 C
80/20
0.8830.883
941591AE2-156 C
80/20
5.2155.215
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
80/20
10.55910.559
944582AF1-123 E
80/20
24.1824.18
944591AF1-124 C
80/20
10.59710.597
944592AF1-124 E
80/20
24.26824.268
944601AF1-125 C
80/20
10.39710.397
944602AF1-125 E
80/20
23.823.8
944631AF1-128 C
80/20
21.92121.921
944641AF1-129 C
80/20
31.53431.534
961612AG1-000B E
80/20
2.3662.366
316303AF2-085
80/20
1.8091.809
958502AF2-144 E
Adder
2.68235294117647042.28
943573AF1-028 BT
80/20
15.50215.502

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.32 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:670.5
MW Contribution:5.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.3773.377
3150831SPRUNCA
80/20
1.4651.465
3150841SPRUNCB
80/20
1.4651.465
3151311EDGECMA
80/20
2.4182.418
3156056W1-029WIND
80/20
0.5910.591
3156116Z1-036WIND
80/20
1.0781.078
901082W1-029 E
80/20
3.9623.962
916042Z1-036 E
80/20
7.2357.235
916192Z1-068 E
80/20
0.2280.228
941032AE2-094 E
80/20
14.06514.065
944012AF1-069 E
80/20
4.5964.596
961942AG1-037 E
80/20
0.0970.097
963041AG1-153 C
80/20
2.072.07
963042AG1-153 E
80/20
3.1043.104
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5651.565
940541AE2-040 C
80/20
0.9830.983
941591AE2-156 C
80/20
5.4145.414
943571AF1-028 C
Adder
-11.711764705882354-9.955
944581AF1-123 C
80/20
11.01711.017
944582AF1-123 E
80/20
25.22825.228
944591AF1-124 C
80/20
11.05611.056
944592AF1-124 E
80/20
25.3225.32
944601AF1-125 C
80/20
10.84810.848
944602AF1-125 E
80/20
24.83224.832
944641AF1-129 C
80/20
30.90830.908
961602AG1-000A E
80/20
1.8811.881
961612AG1-000B E
80/20
2.3482.348
316303AF2-085
80/20
2.0152.015
958502AF2-144 E
Adder
2.84235294117647052.416
943573AF1-028 BT
80/20
11.71211.712

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.3 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:736.51
MW Contribution:4.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.398.39
3150651CHESTF6
80/20
3.4453.445
3150831SPRUNCA
80/20
1.4641.464
3150841SPRUNCB
80/20
1.4641.464
3156056W1-029WIND
80/20
0.5590.559
3156116Z1-036WIND
80/20
1.0071.007
901082W1-029 E
80/20
3.7483.748
916042Z1-036 E
80/20
6.7636.763
916192Z1-068 E
80/20
0.2190.219
941032AE2-094 E
80/20
11.9111.91
944012AF1-069 E
80/20
3.8913.891
961942AG1-037 E
80/20
0.0870.087
963041AG1-153 C
80/20
1.7571.757
963042AG1-153 E
80/20
2.6362.636
916191Z1-068 C
80/20
0.0310.031
961611AG1-000B C
80/20
1.5771.577
940541AE2-040 C
80/20
0.8830.883
941591AE2-156 C
80/20
5.2155.215
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
80/20
10.55910.559
944582AF1-123 E
80/20
24.1824.18
944591AF1-124 C
80/20
10.59710.597
944592AF1-124 E
80/20
24.26824.268
944601AF1-125 C
80/20
10.39710.397
944602AF1-125 E
80/20
23.823.8
944631AF1-128 C
80/20
21.92121.921
944641AF1-129 C
80/20
31.53431.534
961612AG1-000B E
80/20
2.3662.366
316303AF2-085
80/20
1.8091.809
958502AF2-144 E
Adder
2.68235294117647042.28
943573AF1-028 BT
80/20
15.50215.502

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.58 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:678.83
MW Contribution:5.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.3773.377
3150831SPRUNCA
80/20
1.4651.465
3150841SPRUNCB
80/20
1.4651.465
3151311EDGECMA
80/20
2.4182.418
3156056W1-029WIND
80/20
0.5910.591
3156116Z1-036WIND
80/20
1.0781.078
901082W1-029 E
80/20
3.9623.962
916042Z1-036 E
80/20
7.2357.235
916192Z1-068 E
80/20
0.2280.228
941032AE2-094 E
80/20
14.06514.065
944012AF1-069 E
80/20
4.5964.596
961942AG1-037 E
80/20
0.0970.097
963041AG1-153 C
80/20
2.072.07
963042AG1-153 E
80/20
3.1043.104
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5651.565
940541AE2-040 C
80/20
0.9830.983
941591AE2-156 C
80/20
5.4145.414
943571AF1-028 C
Adder
-11.711764705882354-9.955
944581AF1-123 C
80/20
11.01711.017
944582AF1-123 E
80/20
25.22825.228
944591AF1-124 C
80/20
11.05611.056
944592AF1-124 E
80/20
25.3225.32
944601AF1-125 C
80/20
10.84810.848
944602AF1-125 E
80/20
24.83224.832
944641AF1-129 C
80/20
30.90830.908
961602AG1-000A E
80/20
1.8811.881
961612AG1-000B E
80/20
2.3482.348
316303AF2-085
80/20
2.0152.015
958502AF2-144 E
Adder
2.84235294117647052.416
943573AF1-028 BT
80/20
11.71211.712

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.36 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:717.07
MW Contribution:4.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.398.39
3150651CHESTF6
80/20
3.4453.445
3150831SPRUNCA
80/20
1.4641.464
3150841SPRUNCB
80/20
1.4641.464
3156056W1-029WIND
80/20
0.5590.559
3156116Z1-036WIND
80/20
1.0071.007
901082W1-029 E
80/20
3.7483.748
916042Z1-036 E
80/20
6.7636.763
916192Z1-068 E
80/20
0.2190.219
941032AE2-094 E
80/20
11.9111.91
944012AF1-069 E
80/20
3.8913.891
961942AG1-037 E
80/20
0.0870.087
963041AG1-153 C
80/20
1.7571.757
963042AG1-153 E
80/20
2.6362.636
916191Z1-068 C
80/20
0.0310.031
961611AG1-000B C
80/20
1.5771.577
940541AE2-040 C
80/20
0.8830.883
941591AE2-156 C
80/20
5.2155.215
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
80/20
10.55910.559
944582AF1-123 E
80/20
24.1824.18
944591AF1-124 C
80/20
10.59710.597
944592AF1-124 E
80/20
24.26824.268
944601AF1-125 C
80/20
10.39710.397
944602AF1-125 E
80/20
23.823.8
944631AF1-128 C
80/20
21.92121.921
944641AF1-129 C
80/20
31.53431.534
961612AG1-000B E
80/20
2.3662.366
316303AF2-085
80/20
1.8091.809
958502AF2-144 E
Adder
2.68235294117647042.28
943573AF1-028 BT
80/20
15.50215.502
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
313373 to 314765 ckt 1
313707 to 313373 ckt 1
314765 to 314749 ckt 1

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC108.48 %678.68B736.224.4
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC108.04 %678.68B733.224.4

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.48 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:736.22
MW Contribution:4.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.77 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:772.11
MW Contribution:4.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.0247058823529426.821
3150651CHESTF6
Adder
3.3176470588235292.82
3150831SPRUNCA
Adder
1.43058823529411771.216
3150841SPRUNCB
Adder
1.43058823529411771.216
3156116Z1-036WIND
Adder
0.98588235294117640.838
916042Z1-036 E
Adder
6.625.627
941032AE2-094 E
Adder
11.86588235294117810.086
944012AF1-069 E
Adder
3.87764705882352923.296
961942AG1-037 E
Adder
0.085882352941176470.073
963041AG1-153 C
Adder
1.76117647058823561.497
963042AG1-153 E
Adder
2.6423529411764712.246
961611AG1-000B C
Adder
1.52588235294117651.297
940541AE2-040 C
Adder
0.86823529411764710.738
941591AE2-156 C
Adder
5.0811764705882354.319
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
Adder
10.2917647058823528.748
944582AF1-123 E
Adder
23.5682352941176520.033
944591AF1-124 C
Adder
10.3282352941176478.779
944592AF1-124 E
Adder
23.65294117647058820.105
944601AF1-125 C
Adder
10.1341176470588248.614
944602AF1-125 E
Adder
23.1976470588235319.718
944631AF1-128 C
Adder
20.9658823529411817.821
944641AF1-129 C
Adder
30.36705882352941525.812
961612AG1-000B E
Adder
2.28823529411764741.945
316303AF2-085
Adder
2.1552941176470591.832
958502AF2-144 E
Adder
2.8294117647058822.405

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.04 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:733.22
MW Contribution:4.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.32 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:769.11
MW Contribution:4.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.0247058823529426.821
3150651CHESTF6
Adder
3.3176470588235292.82
3150831SPRUNCA
Adder
1.43058823529411771.216
3150841SPRUNCB
Adder
1.43058823529411771.216
3156116Z1-036WIND
Adder
0.98588235294117640.838
916042Z1-036 E
Adder
6.625.627
941032AE2-094 E
Adder
11.86588235294117810.086
944012AF1-069 E
Adder
3.87764705882352923.296
961942AG1-037 E
Adder
0.085882352941176470.073
963041AG1-153 C
Adder
1.76117647058823561.497
963042AG1-153 E
Adder
2.6423529411764712.246
961611AG1-000B C
Adder
1.52588235294117651.297
940541AE2-040 C
Adder
0.86823529411764710.738
941591AE2-156 C
Adder
5.0811764705882354.319
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
Adder
10.2917647058823528.748
944582AF1-123 E
Adder
23.5682352941176520.033
944591AF1-124 C
Adder
10.3282352941176478.779
944592AF1-124 E
Adder
23.65294117647058820.105
944601AF1-125 C
Adder
10.1341176470588248.614
944602AF1-125 E
Adder
23.1976470588235319.718
944631AF1-128 C
Adder
20.9658823529411817.821
944641AF1-129 C
Adder
30.36705882352941525.812
961612AG1-000B E
Adder
2.28823529411764741.945
316303AF2-085
Adder
2.1552941176470591.832
958502AF2-144 E
Adder
2.8294117647058822.405
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC103.72 %661.76B686.414.39
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC105.01 %661.76B694.914.39
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC102.08 %661.76B675.514.39

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.72 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:686.41
MW Contribution:4.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.3894117647058837.131
3150651CHESTF6
Adder
3.44470588235294132.928
3150831SPRUNCA
Adder
1.46470588235294131.245
3150841SPRUNCB
Adder
1.46470588235294131.245
3156116Z1-036WIND
Adder
1.00705882352941180.856
916042Z1-036 E
Adder
6.7623529411764715.748
941032AE2-094 E
Adder
11.90941176470588110.123
944012AF1-069 E
Adder
3.8917647058823533.308
961942AG1-037 E
Adder
0.087058823529411760.074
963041AG1-153 C
Adder
1.75764705882352961.494
963042AG1-153 E
Adder
2.63647058823529432.241
961611AG1-000B C
Adder
1.57764705882352941.341
940541AE2-040 C
Adder
0.88352941176470590.751
941591AE2-156 C
Adder
5.2152941176470584.433
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
Adder
10.568.976
944582AF1-123 E
Adder
24.18000000000000320.553
944591AF1-124 C
Adder
10.5964705882352939.007
944592AF1-124 E
Adder
24.2670588235294120.627
944601AF1-125 C
Adder
10.3964705882352948.837
944602AF1-125 E
Adder
23.820.23
944631AF1-128 C
Adder
21.92117647058823618.633
944641AF1-129 C
Adder
31.5341176470588226.804
961612AG1-000B E
Adder
2.36588235294117682.011
316303AF2-085
Adder
2.12823529411764721.809
958502AF2-144 E
Adder
2.68235294117647042.28

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.01 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:694.91
MW Contribution:4.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.3894117647058837.131
3150651CHESTF6
Adder
3.44470588235294132.928
3150831SPRUNCA
Adder
1.46470588235294131.245
3150841SPRUNCB
Adder
1.46470588235294131.245
3156116Z1-036WIND
Adder
1.00705882352941180.856
916042Z1-036 E
Adder
6.7623529411764715.748
941032AE2-094 E
Adder
11.90941176470588110.123
944012AF1-069 E
Adder
3.8917647058823533.308
961942AG1-037 E
Adder
0.087058823529411760.074
963041AG1-153 C
Adder
1.75764705882352961.494
963042AG1-153 E
Adder
2.63647058823529432.241
961611AG1-000B C
Adder
1.57764705882352941.341
940541AE2-040 C
Adder
0.88352941176470590.751
941591AE2-156 C
Adder
5.2152941176470584.433
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
Adder
10.568.976
944582AF1-123 E
Adder
24.18000000000000320.553
944591AF1-124 C
Adder
10.5964705882352939.007
944592AF1-124 E
Adder
24.2670588235294120.627
944601AF1-125 C
Adder
10.3964705882352948.837
944602AF1-125 E
Adder
23.820.23
944631AF1-128 C
Adder
21.92117647058823618.633
944641AF1-129 C
Adder
31.5341176470588226.804
961612AG1-000B E
Adder
2.36588235294117682.011
316303AF2-085
Adder
2.12823529411764721.809
958502AF2-144 E
Adder
2.68235294117647042.28

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:675.51
MW Contribution:4.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.3894117647058837.131
3150651CHESTF6
Adder
3.44470588235294132.928
3150831SPRUNCA
Adder
1.46470588235294131.245
3150841SPRUNCB
Adder
1.46470588235294131.245
3156116Z1-036WIND
Adder
1.00705882352941180.856
916042Z1-036 E
Adder
6.7623529411764715.748
941032AE2-094 E
Adder
11.90941176470588110.123
944012AF1-069 E
Adder
3.8917647058823533.308
961942AG1-037 E
Adder
0.087058823529411760.074
963041AG1-153 C
Adder
1.75764705882352961.494
963042AG1-153 E
Adder
2.63647058823529432.241
961611AG1-000B C
Adder
1.57764705882352941.341
940541AE2-040 C
Adder
0.88352941176470590.751
941591AE2-156 C
Adder
5.2152941176470584.433
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
Adder
10.568.976
944582AF1-123 E
Adder
24.18000000000000320.553
944591AF1-124 C
Adder
10.5964705882352939.007
944592AF1-124 E
Adder
24.2670588235294120.627
944601AF1-125 C
Adder
10.3964705882352948.837
944602AF1-125 E
Adder
23.820.23
944631AF1-128 C
Adder
21.92117647058823618.633
944641AF1-129 C
Adder
31.5341176470588226.804
961612AG1-000B E
Adder
2.36588235294117682.011
316303AF2-085
Adder
2.12823529411764721.809
958502AF2-144 E
Adder
2.68235294117647042.28
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
313373 to 314765 ckt 1
313707 to 313373 ckt 1
314765 to 314749 ckt 1

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 1 Cluster 47 are listed in Table 1 below. This report will cover the TC1 Phase 3 dynamic analysis of Cluster 47 projects.

 

Table 1: Transition Cycle 1 Cluster 47 Projects

Cluster

Project

Fuel Type

Transmission Owner

MFO (MW)

MWE (MW)

MWC (MW)

Point of Interconnection

47

AG1-153

Battery

Dominion

75

75

30

Heritage 500 kV

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 47 projects will meet the dynamics requirements of the NERC, Dominion Energy, and PJM reliability standards.

 

The load flow case finalized for Phase 2 was used as a starting point and was updated based on latest Cluster 47 data, Dominion Energy recommended transmission changes and withdrawn generation. Projects in vicinity of Cluster 47 have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer. The dynamic models for Cluster 42 projects were updated based on the latest DP2 data and include any tuning adjustments recommended during Phase 2.

 

Cluster 47 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. 97 contingencies were studied, each with a 30 second simulation time period. The studied contingencies included:

 

  • Steady-state operation (30 seconds)
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults with delayed clearing at remote end
  • Three-phase faults with loss of multiple-circuit tower line.

 

The contingencies were updated based on topology changes due to any Dominion Energy recommended transmission changes or generation withdrawals.

 

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all of the fault contingencies tested on the RTEP 2027 summer peak case:

 

 

AG1-153 queue project did not meet the power factor 0.95 lagging measured at the high side of the transformer and it is deficient by 3.85 MVAR. AG1-153 queue project met the 0.95 leading power factor requirements.

 

The result of the analysis for Cluster 47 projects met all evaluation criteria for all the contingencies. No mitigation was required. There were minor reactive drift from AG1-153 that could be tuned by developer to improve performance.

 

AE1-173:

AE1-173, a nearby generator tripped for under voltage protection for voltages under 0.64 p.u for 0.31 seconds. The unit rode through all contingencies when pickup time was increased to 0.4375 seconds. The generator owner should be contacted to confirm if the revised setting is within plants capability and/or tune the model’s recovery.

 

AB2-169:

AB2-169, nearby generator, tripped for over voltage protection for voltages over 1.25 p.u. for 0.0 seconds. The unit rode through all contingencies when pickup time was increased to 0.0125 seconds.  The generator owner should be contacted to confirm if the revised setting is within plants capability and/or tune the model’s recovery.

Reactive Power Analysis

The reactive power capability of AG1-153 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-065Earleys 230kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-088Boykins-Handsome 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB1-173Brink-Trego 115kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-100Clubhouse-Lakeview 230kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVEngineering & Procurement
AC1-036Twittys Creek 34.5kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-080Perth-Hickory Grove 115kVIn Service
AC1-086Thelma 230kVUnder Construction
AC1-098Dawson-South Justice 115kVIn Service
AC1-099Dawson-South Justice 115kVIn Service
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-216Hopewell-Surry 230kVIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVUnder Construction
AC2-084Dawson-South Justice 115kVIn Service
AC2-100Halifax-Person 230kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-149Disputanta-Poe 115 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE2-027Harrowgate-Locks 115kVSuspended
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVIn Service
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVWithdrawn
AE2-156Yadkin 115 kVEngineering & Procurement
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-247Myrtle-Windsor 115 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-346Ahoskie 34.5 kVIn Service
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-028Endless Caverns 115 kVPartially in Service - Under Construction
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-123Harper 230 kVUnder Construction
AF1-124Harper 230 kVPartially in Service - Under Construction
AF1-125Harper 230 kVUnder Construction
AF1-128Chesterfield 230 kVUnder Construction
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVUnder Construction
AF1-294Jetersville-Ponton 115 kVEngineering & Procurement
AF2-042Clover-Rawlings 500 kVEngineering & Procurement
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-081Moyock 230 kVEngineering & Procurement
AF2-085Midlothian 34.5 kVIn Service
AF2-110Suffolk 115 kVWithdrawn
AF2-115Jetersville-Ponton 115 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVEngineering & Procurement
AF2-299Fields 34.5 kVEngineering & Procurement
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-021Jetersville-Ponton 115 kVEngineering & Procurement
AG1-037Ahoskie 34.5 kVWithdrawn
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVUnder Construction
AG1-135Garner-Lancaster 115 kVUnder Construction
AG1-145Lightfoot 34.5 kVIn Service
AG1-285Chase City-Central 115 kVEngineering & Procurement
AG1-342Dryburg 115 kVEngineering & Procurement
AG1-532Fields 34.5 kVUnder Construction
V4-068Murphy's 34.5kVIn Service
W1-029Winfall 230kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z1-068Birdneck 34.5kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-088Tarboro-Everetts 230kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In coordination with other Affected System Operators, PJM has determined that the Affected System Operator for this project that requires an Affected System Study. For the latest Affected System Study results pertaining this project, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM lists any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG1-153 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn9378.0Replace existing 230/500 kV Carson transformer #1 with (4)-480 MVA single phase transformers.Cost Allocated$1,759,557
Dominionb4000.315Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.Contingent$0N/A
Dominionb4000.316At Poe substation, uprate all Line #2003 terminal equipment, line leads, and bus to be rated to 4000A.Contingent$0N/A
Dominionb4000.317At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.Contingent$0N/A
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Non-Contingent$0N/A
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Non-Contingent$0N/A
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Non-Contingent$0N/A
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Non-Contingent$0N/A
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Non-Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Non-Contingent$0N/A
Dominionb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Non-Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Non-Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Non-Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Non-Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Non-Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Non-Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationNon-Contingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Non-Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Non-Contingent$0N/A
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Non-Contingent$0N/A
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Non-Contingent$0N/A
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Non-Contingent$0N/A
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Non-Contingent$0N/A
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Non-Contingent$0N/A
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Non-Contingent$0N/A
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Non-Contingent$0N/A
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Non-Contingent$0N/A
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Non-Contingent$0N/A
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Non-Contingent$0N/A
Dominionn8492.1Two Breaker Additions at Fentress Substation.Non-Contingent$0N/A
Grand Total:$1,759,557

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9378.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9378.0 / TC1-PH3-DOM-010
Title
Replace existing 230/500 kV Carson transformer #1 with (4)-480 MVA single phase transformers.
Description
Replace Existing 230/500 kV Carson transformer #1 with (4)-480 MVA Single Phase transformers. 6CARSON - 8CARSON ckt 2 represents tranformer #1.
Total Cost ($USD)
$37,801,301
Discounted Total Cost ($USD)
$37,801,301
Allocated Cost ($USD)
$1,759,557
Time Estimate
Mar 29 2029

Contributor

FacilityContingency
6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
LLA2016.0 MVA
LLB2083.0 MVA
LLC2239.0 MVA
SUMA1707.0 MVA
SUMB1758.0 MVA
SUMC1873.0 MVA
WINA2196.0 MVA
WINB2228.0 MVA
WINC2308.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.2 MW22.4%$8,456,365
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.5 MW22.5%$8,486,733
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
55.4 MW22.0%$8,324,368
AF2-04259.5 MW23.7%$8,947,219
AF2-22212.2 MW4.8%$1,827,058
AG1-15311.7 MW4.7%$1,759,557

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4030.1
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.1
Title
Chesterfield-Basin 230 kV rebuild: Wreck and rebuild approximately 12.5 miles of Chesterfield-Basin 230 kV line.
Description
Chesterfield-Basin 230 kV rebuild: Wreck and rebuild approximately 12.5 miles of Chesterfield-Basin 230 kV line.
Cost Information
Time Estimate
Jun 01 2030

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1572.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.3
Title
Basin 230 kV substation scope: Replace all terminal equipment, line leads and bus at Basin 230 kV substation to be rated to 4000A.
Description
Basin 230 kV substation scope: Replace all terminal equipment, line leads and bus at Basin 230 kV substation to be rated to 4000A.
Cost Information
Time Estimate
Jun 01 2030

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1572.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.4
Title
Chesterfield 230 kV substation scope: Install a new 230 kV, 80 kA 4000A circuit breaker at Chesterfield 230 kV substation.
Description
Chesterfield 230 kV substation scope: Install a new 230 kV, 80 kA 4000A circuit breaker at Chesterfield 230 kV substation.
Cost Information
Time Estimate
Jun 01 2030

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1572.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: n9681.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9681.0
Title
Upgrade 1.04 Miles of 230kV transmission line 249 from 249/86 to 249/93
Description
Reconductor 1.04 miles of 2*636 ACSR 24/7 MOT 150 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" MOT 250 on 230 kV line 249 between Carson and Chaparral
Total Cost ($USD)
$3,042,004
Discounted Total Cost ($USD)
$3,042,004
Allocated Cost ($USD)
$0
Time Estimate
20 to 21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1442.0 MVA
LLB1540.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1493.0 MVA
WINB1587.0 MVA
WINC1631.0 MVA

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1047.0 MVA
(All)B1047.0 MVA
(All)C1204.0 MVA
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA

System Reinforcement: b4030.9
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.9
Title
Charlottesville-Fork Union 230 kV rebuild: Wreck and rebuild ~24 miles of Charlottesville-Fork Union 230 kV line.New Reinforcement
Description
Charlottesville-Fork Union 230 kV rebuild: Wreck and rebuild ~24 miles of Charlottesville-Fork Union 230 kV line.
Cost Information
Time Estimate
Jun 01 2030

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6CUNNING-6FORK UNION 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.15
Title
Upgrade disconnect switches at Mt. Eagle tap 230 kV substation to 4000A.
Description
Mt. Eagle tap 230 kV substation scope: Upgrade disconnect switches at Mt. Eagle tap 230 kV substation to 4000A.
Cost Information
Time Estimate
Jun 01 2030

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.11
Title
Replace all terminal equipment at Charlottesville 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Description
Charlottesville 230 kV substation scope: Replace all terminal equipment at Charlottesville 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC16480.0 MVA

System Reinforcement: b4030.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.12
Title
Replace all terminal equipment at Fork Union 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Description
Fork Union 230 kV substation scope: Replace all terminal equipment at Fork Union 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CUNNING-6FORK UNION 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.10
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.10
Title
Fork Union-Bremo 230 kV rebuild: Wreck and Rebuild approximately 1.74 miles of Fork Union-Bremo 230 kV line.
Description
Fork Union-Bremo 230 kV rebuild: Wreck and Rebuild approximately 1.74 miles of Fork Union-Bremo 230 kV line.
Cost Information
Time Estimate
Jun 01 2030

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB16480.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.13
Title
Replace all terminal equipment at Fork Union 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Description
Fork Union 230 kV substation scope: Replace all terminal equipment at Fork Union 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.14
Title
Replace all terminal equipment at Bremo 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Description
Bremo 230 kV substation scope: Replace all terminal equipment at Bremo 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Discounted Total Cost ($USD)
$37,836,293
Allocated Cost ($USD)
$0
Time Estimate
Oct 01 2029

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA

System Reinforcement: b4000.315
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.315
Title
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Description
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Apr 22 2030

Contingent

Note: Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 may need this upgrade in-service to be deliverable to the PJM system. If AG1-153 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA

System Reinforcement: b4000.316
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.316
Title
At Poe substation, uprate all Line #2003 terminal equipment, line leads, and bus to be rated to 4000A.
Description
At Poe substation, uprate all Line #2003 terminal equipment, line leads, and bus to be rated to 4000A.
Cost Information
Time Estimate
Apr 22 2030

Contingent

Note: Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 may need this upgrade in-service to be deliverable to the PJM system. If AG1-153 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA

System Reinforcement: b4000.317
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.317
Title
At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.
Description
At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.
Cost Information
Time Estimate
Apr 22 2030

Contingent

Note: Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 may need this upgrade in-service to be deliverable to the PJM system. If AG1-153 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA

System Reinforcement: b4053.18
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.18
Title
Rebuild approximately 37.4 miles of 500 kV line No. 563 from Carson-Midlothian.
Description
Rebuild approximately 37.4 miles of 500 kV line No. 563 from Carson-Midlothian. The proposed structures to be installed are mainly 500/230 kV double-circuit V-string suspension towers. The 230 kV circuit position will be vacant at the completion of this project but serves to accommodate a future 230 kV line.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4053.19
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.19
Title
Uprate 500 kV line No. 563 associated terminal equipment at Carson to 5000A standards.
Description
Uprate 500 kV line No. 563 associated terminal equipment at Carson to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4053.20
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.20
Title
Uprate 500 kV line No. 563 associated terminal equipment at Midlothian to 5000A standards.
Description
Uprate 500 kV line No. 563 associated terminal equipment at Midlothian to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4357.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA5155.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b3692
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3692
Title
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.
Description
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy with current 500 kV standards construction practices to achieve a summer rating of 4330 MVA. Projected ISD: 06/01/2026
Cost Information
Time Estimate
Jun 01 2026

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4330.0 MVA
(All)B4330.0 MVA
(All)C5011.0 MVA

System Reinforcement: b4053.21
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.21
Title
Uprate 500 kV line No. 567 associated terminal equipment at Chickahominy to 5000A standards.
Description
Uprate 500 kV line No. 567 associated terminal equipment at Chickahominy to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3322.0 MVA
(All)B3425.0 MVA
(All)C3939.0 MVA
WINA4191.0 MVA
WINB4376.0 MVA
WINC5032.0 MVA

System Reinforcement: b4053.22
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.22
Title
Uprate 500 kV line No. 567 associated terminal equipment at Surry to 5000A standards.
Description
Uprate 500 kV line No. 567 associated terminal equipment at Surry to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3322.0 MVA
(All)B3425.0 MVA
(All)C3939.0 MVA
WINA4191.0 MVA
WINB4376.0 MVA
WINC5032.0 MVA

System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
ELIM TC1: Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Discounted Total Cost ($USD)
$111,130,292
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
ELIM TC1: Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Discounted Total Cost ($USD)
$108,728,086
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b4053.27
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.27
Title
Upgrade/install 6000A equipment at Midlothian substation to support the new conductor termination from Vontay.
Description
Upgrade/install 6000A equipment at Midlothian substation to support the new conductor termination from Vontay.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.6
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.6
Title
Rebuild 20 miles of 500 kV line No. 576 from North Anna substation to Vontay substation using 6000A conductor.
Description
Rebuild 20 miles of 500 kV line No. 576 from North Anna substation to Vontay substation using 6000A conductor.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.7
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.7
Title
Upgrade/install 6000A equipment at North Anna substation to support the new conductor termination.
Description
Upgrade/install 6000A equipment at North Anna substation to support the new conductor termination.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement: b4053.26
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.26
Title
Rebuild 20 miles of 500 kV line No. 576 from Vontay substation to Midlothian substation using 6000A conductor.
Description
Rebuild 20 miles of 500 kV line No. 576 from Vontay substation to Midlothian substation using 6000A conductor.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5109.0 MVA
(All)B5268.0 MVA
(All)C6057.0 MVA
WINA5691.0 MVA
WINB5867.0 MVA
WINC6748.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-040
Title
ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 18.75 miles of Line 594 between Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$128,018,212
Discounted Total Cost ($USD)
$128,018,212
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9247.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9247.0 / TC1-PH2-DOM-041
Title
ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 14.02 miles of Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA
Total Cost ($USD)
$99,636,684
Discounted Total Cost ($USD)
$99,636,684
Allocated Cost ($USD)
$0
Time Estimate
48 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n8492.2

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2026
Cost Alloc Type
Non-Contingent

System Reinforcement: n9259.0

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Allocated Cost ($USD)
$0
Time Estimate
Jan 01 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: n9267.0

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months
Cost Alloc Type
Non-Contingent

System Reinforcement: n9630.0

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.356

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.355

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.325

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.326

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.327

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: s3047.2

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s3047.2
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3047.2
Title
Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.
Description
Install (2) 1400 MVA 500-230 kV transformers and associated 500 kV and 230 kV equipment (breakers, switches, leads) at Vint Hill Substation to supply the area with a 500 kV source Cut and loop 500 kV line #535 Loudoun – Meadowbrook and #569 Loudoun - Morrisville as the 500 kV sources into the proposed 500 kV ring bus Vint Hill Substation will be expanded to the north of the existing site to accommodate the 500 kV ring required for the addition of the new transformers Existing terminations for 230 kV line #2174 Wheeler – Vint Hill, line #2101 Bristers – Vint Hill, and line #2163 Liberty – Vint Hill will be rearranged to terminate into the expanded Vint Hill Substation 230 kV line #2114 Remington CT – Rollins Ford will also be cut and looped into the expanded Vint Hill Substation due to spatial constraints along the existing right-of-way.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.312

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.313

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.313
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.313
Title
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Description
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.356

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.356
Title
Build a new 500 kV line from Vint Hill to Wishing Star.
Description
Build a new 500kV line from Vint Hill to Wishing Star. The line will be supported on single circuit monopoles. New conductor to have a summer rating of 4357 MVA. Line length is approximately 16.59 miles
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.357

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.357
Title
Build a new 500 kV line from Morrisville to Vint Hill.
Description
Build a new 500kV line from Morrisville to Vint Hill. New conductor to have a summer rating of 4357 MVA. Line length is approximately 19.71 miles.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.354

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.354
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.354
Title
Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.
Description
Install terminal equipment at Wishing Star substation to support a 5000A line to Vint Hill. Update relay settings for 500kV Lines #546 and #590.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: n8492

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2026
Cost Alloc Type
Non-Contingent

System Reinforcement: n8492.1

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2026
Cost Alloc Type
Non-Contingent

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG1-153


AG1-153 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AG1-153 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Non-Contingent$0
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Non-Contingent$0
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Non-Contingent$0
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Non-Contingent$0
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Non-Contingent$0
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Non-Contingent$0
Dominionb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Non-Contingent$0
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Non-Contingent$0
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Non-Contingent$0
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Non-Contingent$0
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Non-Contingent$0
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Non-Contingent$0
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationNon-Contingent$0
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Non-Contingent$0
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Non-Contingent$0
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Non-Contingent$0
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Non-Contingent$0
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Non-Contingent$0
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Non-Contingent$0
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Non-Contingent$0
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Non-Contingent$0
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Non-Contingent$0
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Non-Contingent$0
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Non-Contingent$0
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Non-Contingent$0
Dominionn8492.1Two Breaker Additions at Fentress Substation.Non-Contingent$0
Region Topology Upgrade Total:$0

Attachments

AG1-153 One Line Diagram

AG1-153 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.