AG1-153 Final System Impact Study (Retool 1) Report

v1.00 released 2025-12-08 18:22

Heritage 500 kV

30.0 MW Capacity / 75.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia), and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the TC1 projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.
Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of TC1 projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Brunswick County, Virginia. The installed facilities will have a total capability of 75.0 MW with 30.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG1-153
Project Name:
Heritage 500 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
State:
Virginia
County:
Brunswick
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
75.0
MWE:
75.0
MWC:
30.0
Battery Storage Specification:
300.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2027

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG1-153 will interconnect on the Dominion transmission system as direct connect at Heritage 500 kV Substation.

 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AG1-153 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AG1-153Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$4,822,863$4,822,863
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$1,958,524$1,958,524
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$1,759,557$1,759,557
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$8,540,944$8,540,944

* Contributes to calculation for Security. See Security Section of this report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AG1-153

Security has been calculated for the AG1-153 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AG1-153
Project(s): AG1-153
Final Agreement Security (A): $8,540,944
Portion of Costs Already Paid (B): $641,287
Revised Net Security (C): A − B = $7,899,657
Security on Hand with PJM (D): $7,734,646
Additional Security Due at Agreement Execution (E): C − D = $165,011
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

The New Service Request Project will interconnect with the Dominion transmission system via a direct connect to the Heritage 500 kV Sub. The required work for the interconnection of the New Service Request Project to the Dominion Transmission System is detailed in the following tables.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n8316

Expansion of Existing Heritage 500 kV Substation

$875,457$738,668$270,404$73,995$1,958,524$1,958,524
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Transmission Owner Interconnection Facilities, including one (1) new 500 kV engineered steel 3-pole structure is to be installed outside the fence of the interconnection substation, to terminate the Project Developer’s generator lead line, and line conductor from the backbone structure to the bus position in the switchyard of the interconnection substation.

$3,362,312$838,141$553,656$68,754$4,822,863$4,822,863

Based on the scope of work for the Interconnection Facilities, it is expected to take 62 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

 

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG1-153 was evaluated as a 75.0 MW (30.0 MW Capacity) injection in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC110.49 %1204.0C1330.349.94
GD1DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC108.7 %1204.0C1308.789.94
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC142.63 %812.0C1158.145.82
GD1DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC133.85 %663.64B888.272.02
GD1DVP
6POE-6TYLER1 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC104.13 %541.0C563.345.48
GD1DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC113.54 %1056.8C1199.8611.7
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC106.16 %3940.0C4182.7424.49
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC104.22 %3940.0C4106.1223.45
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H1T567_SRT-A
BreakerAC103.44 %3940.0C4075.5524.51
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
SingleAC100.39 %1058.16B1062.253.67
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
TowerAC108.98 %3940.0C4293.9822.88
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC104.85 %3940.0C4130.9822.74
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S_SENS
BreakerAC102.96 %3940.0C4056.7621.88
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S_SENS
SingleAC102.07 %3220.44B3287.018.59
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC102.59 %3144.0C3225.3217.14
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC102.48 %3144.0C3221.9716.91
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC102.48 %3144.0C3221.9716.91
GD1DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC102.48 %3144.0C3221.8116.91

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.49 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1330.34
MW Contribution:9.94
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.67 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1404.76
MW Contribution:9.8
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
918492AA1-063AE OP
Adder
2.40470588235294122.044
962571AG1-106 C
50/50
2.0442.044
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
927146AC1-208 E
Adder
2.45294117647058842.085
934622AD1-088 E
Adder
2.72588235294117662.317
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
316087AB2-174 C
50/50
0.9180.918
962572AG1-106 E
50/50
0.8940.894
926214AC1-099 E
Adder
0.70941176470588230.603
932632AC2-084 E
Adder
1.89764705882352951.613
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
964792AG1-342 E
Adder
1.34588235294117631.144
932763AC2-100 E
Adder
1.3917647058823531.183
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934521AD1-076 C
Adder
4.7823529411764714.065
934511AD1-075 C
Adder
3.2917647058823532.798
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
940541AE2-040 C
50/50
3.3223.322
940481AE2-033 C
50/50
18.24118.241
940482AE2-033 E
50/50
12.29712.297
923263AB1-132 E OP
50/50
4.64.6
3151411GASTONB
50/50
2.2972.297
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
3152441Z1-086 ST
50/50
13.14613.146
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
926274AC1-105 E
Adder
1.50823529411764711.282
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151041BRUNSWICKG3
50/50
5.8715.871
3151021BRUNSWICKG1
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
3151051BRUNSWICKS1
50/50
12.19612.196
963042AG1-153 E
50/50
5.9665.966
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
963041AG1-153 C
50/50
3.9773.977
957862AF2-080 E
Adder
1.84352941176470591.567
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
316315AB2-025 C
50/50
0.4720.472
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
957861AF2-080 C
Adder
4.1588235294117653.535
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
936172AD2-023 E
Adder
1.21058823529411751.029
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961942AG1-037 E
Adder
0.167058823529411760.142
961941AG1-037 C
Adder
0.251764705882352950.214
3151391GASTONA
50/50
2.2972.297
3151381ROSEMG2
50/50
0.7050.705
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934332AD1-057 E
Adder
1.21529411764705891.033
934331AD1-057 C
Adder
2.33411764705882341.984
934321AD1-056 C
Adder
4.1835294117647063.556
934322AD1-056 E
Adder
2.26941176470588251.929
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.7 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1308.78
MW Contribution:9.94
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.88 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1383.11
MW Contribution:9.8
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940492AE2-034 E
Adder
1.07647058823529430.915
934522AD1-076 E
Adder
2.43764705882352972.072
943172AE2-346 E
Adder
0.30117647058823530.256
918492AA1-063AE OP
Adder
2.40470588235294122.044
962571AG1-106 C
50/50
2.0442.044
917332KELFORD E
Adder
0.87529411764705890.744
925122AB2-169 E
Adder
2.5788235294117652.192
316274AC1-208 C
Adder
5.5235294117647074.695
917342Z2-044 E
Adder
0.36117647058823530.307
937482AD2-202 E
Adder
0.64705882352941180.55
3151311EDGECMA
Adder
9.4070588235294137.996
961792AG1-021 E
Adder
0.71411764705882350.607
3145946PLYMOUTH TP
Adder
0.123529411764705890.105
933982AD1-022 E
Adder
1.9647058823529411.67
927146AC1-208 E
Adder
2.45294117647058842.085
934622AD1-088 E
Adder
2.72588235294117662.317
934612AD1-087 E
Adder
2.20941176470588241.878
927255AC1-221 E
Adder
2.0517647058823531.744
316087AB2-174 C
50/50
0.9180.918
920692AA2-178 E
Adder
1.43529411764705881.22
966622AG1-532 E
50/50
0.7790.779
922923AB1-081 E OP
Adder
2.24941176470588241.912
3147133PAMPLIN
Adder
0.454117647058823570.386
927264AC1-222 E
Adder
2.16588235294117661.841
3145393UNCAMP
Adder
2.10941176470588231.793
933981AD1-022 C
Adder
3.6082352941176473.067
900672V4-068 E
Adder
0.172941176470588240.147
3151261ROARAP2
50/50
0.9170.917
3147043LAWRENC
50/50
0.2360.236
3152411Z1-086 GT1
50/50
7.5527.552
924302AB2-077 E O1
Adder
0.7917647058823530.673
934512AD1-075 E
Adder
1.67647058823529421.425
934502AD1-074 E
Adder
6.7035294117647065.698
924516AB2-100 E1
50/50
2.6782.678
918512AA1-065 E OP
Adder
2.60941176470588232.218
966621AG1-532 C
50/50
1.1691.169
918532AA1-067 E
Adder
0.367058823529411770.312
924022AB2-043 E O1
Adder
3.07764705882352942.616
3147223TWITTYS
Adder
0.52235294117647060.444
959312AF2-222 E
Adder
6.0152941176470595.113
926024AC1-080 E
Adder
0.454117647058823570.386
936161AD2-022 C
Adder
3.8235294117647063.25
962572AG1-106 E
50/50
0.8940.894
926214AC1-099 E
Adder
0.70941176470588230.603
932632AC2-084 E
Adder
1.89764705882352951.613
964242AG1-285 E
Adder
5.0011764705882364.251
924162AB2-060 E OP
Adder
2.522.142
964792AG1-342 E
Adder
1.34588235294117631.144
932763AC2-100 E
Adder
1.3917647058823531.183
939411AE1-173 C
Adder
49.7729411764705942.307
3137643SOCKMAN
50/50
0.5020.502
3151031BRUNSWICKG2
50/50
5.8715.871
919710AA2-057 E
Adder
2.3988235294117652.039
944641AF1-129 C
Adder
-87.83529411764705-74.66
316240AF1-291 C
Adder
-1.56-1.326
920042AA2-088 E OP
Adder
4.9317647058823534.192
934521AD1-076 C
Adder
4.7823529411764714.065
934511AD1-075 C
Adder
3.2917647058823532.798
3145723EMPORIA
50/50
0.3510.351
316011AB1-132 C OP
50/50
1.7541.754
923573AB1-173 E OP
50/50
2.4772.477
919692AA2-053 E OP
Adder
2.6788235294117652.277
925785AC1-054 E
Adder
2.1505882352941181.828
316263AC1-034 C
Adder
4.00705882352941253.406
959311AF2-222 C
Adder
8.9788235294117647.632
940541AE2-040 C
50/50
3.3223.322
940481AE2-033 C
50/50
18.24118.241
940482AE2-033 E
50/50
12.29712.297
923263AB1-132 E OP
50/50
4.64.6
3151411GASTONB
50/50
2.2972.297
316181AB2-040 GEN
50/50
0.9590.959
3151281ROARAP4
50/50
0.8680.868
3152441Z1-086 ST
50/50
13.14613.146
3152431Z1-086 GT3
50/50
7.5497.549
3152421Z1-086 GT2
50/50
7.5497.549
925612AC1-036 E
Adder
0.47058823529411770.4
924312AB2-078 E O1
Adder
0.7917647058823530.673
926274AC1-105 E
Adder
1.50823529411764711.282
3143316POE
Adder
0.51176470588235290.435
316365AB2-100 C1
50/50
0.8890.889
926206AC1-098 E
Adder
2.14705882352941171.825
3151041BRUNSWICKG3
50/50
5.8715.871
3151021BRUNSWICKG1
50/50
5.8715.871
942462AE2-259 E
Adder
2.62.21
964791AG1-342 C
Adder
2.0188235294117651.716
925997AC1-075 E
Adder
1.36941176470588231.164
316141AB2-099 E
Adder
0.125882352941176470.107
316088AB2-174 E
50/50
5.0815.081
313506AB1-173 C OP
50/50
0.8520.852
923994AB2-040_E
50/50
4.6454.645
3151361ROSEMG1
50/50
1.5051.505
957481AF2-042 C
50/50
34.00834.008
961672AG1-007 E
Adder
0.30352941176470590.258
924322AB2-079 E O1
Adder
0.7917647058823530.673
946302AF1-294 E
Adder
1.46000000000000021.241
943902AF1-058 E
Adder
0.71411764705882350.607
942001AE2-212 C
Adder
-3.7917647058823527-3.223
934501AD1-074 C
Adder
13.16823529411764711.193
924517AB2-100 E2
50/50
2.6782.678
3151371ROSEMS1
50/50
0.9320.932
957482AF2-042 E
50/50
22.67222.672
961671AG1-007 C
Adder
0.53647058823529410.456
934621AD1-088 C
Adder
5.6611764705882364.812
946301AF1-294 C
Adder
1.7247058823529411.466
942461AE2-259 C
Adder
3.8988235294117653.314
935172AD1-152 E
Adder
3.25058823529411762.763
936162AD2-022 E
Adder
2.29411764705882341.95
3145413WATKINS
Adder
0.265882352941176460.226
960081AF2-299 C
50/50
1.5581.558
926072AC1-086 E
50/50
7.1937.193
944011AF1-069 C
50/50
9.4749.474
963041AG1-153 C
50/50
3.9773.977
957862AF2-080 E
Adder
1.84352941176470591.567
936261AD2-033 C
Adder
7.0082352941176475.957
961791AG1-021 C
Adder
0.83882352941176460.713
962562AG1-105 E
Adder
3.39764705882352922.888
936171AD2-023 C
Adder
2.23058823529411751.896
316315AB2-025 C
50/50
0.4720.472
946282AF1-292 E
50/50
0.860.86
944012AF1-069 E
50/50
3.683.68
957861AF2-080 C
Adder
4.1588235294117653.535
917512Z2-088 E OP1
Adder
2.742.329
3138533PONTONDP
Adder
0.310588235294117660.264
316023AB2-100 C2
50/50
0.8890.889
960082AF2-299 E
50/50
1.0391.039
946281AF1-292 C
50/50
1.291.29
926071AC1-086 C
50/50
15.80515.805
3151051BRUNSWICKS1
50/50
12.19612.196
963042AG1-153 E
50/50
5.9665.966
927021AC1-189 C
Adder
4.5788235294117653.892
964241AG1-285 C
Adder
7.502352941176476.377
924152AB2-059 E OP
Adder
3.18705882352941172.709
958212AF2-115 E
Adder
0.89294117647058820.759
962561AG1-105 C
Adder
5.0952941176470594.331
936172AD2-023 E
Adder
1.21058823529411751.029
923852AB2-025 E
50/50
1.3441.344
939412AE1-173 E
Adder
33.1823529411764728.205
961942AG1-037 E
Adder
0.167058823529411760.142
961941AG1-037 C
Adder
0.251764705882352950.214
3151391GASTONA
50/50
2.2972.297
3151381ROSEMG2
50/50
0.7050.705
941032AE2-094 E
50/50
12.98612.986
941031AE2-094 C
50/50
28.99528.995
934332AD1-057 E
Adder
1.21529411764705891.033
934331AD1-057 C
Adder
2.33411764705882341.984
934321AD1-056 C
Adder
4.1835294117647063.556
934322AD1-056 E
Adder
2.26941176470588251.929
927022AC1-189 E
Adder
2.28117647058823541.939
925595AC1-034 E
Adder
3.0235294117647062.57
936262AD2-033 E
Adder
4.6729411764705883.972
958211AF2-115 C
Adder
1.04823529411764720.891
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.1273.127
CBM South 2LTFEXP_CBM-S2->PJM
CBM
53.66253.662
CPLELTFEXP_CPLE->PJM
CLTF
6.566.56
TVALTFEXP_TVA->PJM
CLTF
3.2723.272
O66PJM->LTFIMP_O-066
CMTX_NF
8.4068.406
NYPJM->LTFIMP_NY
CLTF
0.6070.607
LGEELTFEXP_LGEE->PJM
CLTF
0.6710.671
WECLTFEXP_WEC->PJM
CLTF
0.3580.358
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.44517.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.17912.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1542.154
LAGNLTFEXP_LAGN->PJM
CLTF
4.1864.186
G-007PJM->LTFIMP_G-007
CMTX_NF
1.3211.321
SIGELTFEXP_SIGE->PJM
CLTF
0.1320.132

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.63 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1158.14
MW Contribution:5.82
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.2 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1065.31
MW Contribution:5.76
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961611AG1-000B C
Adder
7.286.188
940541AE2-040 C
50/50
1.7731.773
940481AE2-033 C
50/50
9.8069.806
940482AE2-033 E
50/50
6.6116.611
923263AB1-132 E OP
Adder
2.8364705882352942.411
3150771HOPHCF1
50/50
1.6821.682
940431AE2-027 C
Adder
5.5282352941176474.699
942002AE2-212 E
50/50
1.5921.592
316132AB2-190 C
50/50
2.4992.499
944581AF1-123 C
Adder
13.82941176470588311.755
939191AE1-149 C
50/50
7.6817.681
3143316POE
50/50
1.2311.231
901082W1-029 E
Adder
10.5541176470588248.971
926206AC1-098 E
Adder
1.4682352941176471.248
964791AG1-342 C
Adder
1.1482352941176470.976
3150651CHESTF6
50/50
25.13725.137
946262AF1-291 E
50/50
1.8721.872
934576AD1-082 E
50/50
2.7072.707
944602AF1-125 E
Adder
31.17176470588235326.496
3145506HICKORY
Adder
0.6682352941176470.568
943612AF1-032 E
Adder
0.30705882352941180.261
957871AF2-081 C
Adder
3.10588235294117652.64
940492AE2-034 E
Adder
1.08941176470588250.926
934522AD1-076 E
Adder
2.2623529411764711.923
943172AE2-346 E
Adder
0.238823529411764740.203
918492AA1-063AE OP
Adder
1.7070588235294121.451
962571AG1-106 C
Adder
1.26117647058823531.072
917332KELFORD E
Adder
0.65058823529411770.553
925122AB2-169 E
Adder
2.1235294117647061.805
316274AC1-208 C
Adder
3.6705882352941183.12
917342Z2-044 E
Adder
0.235294117647058850.2
937482AD2-202 E
Adder
0.36941176470588240.314
3151311EDGECMA
Adder
6.0682352941176485.158
316084AB2-161 E
50/50
3.3973.397
316083AB2-161 C
50/50
0.340.34
3145946PLYMOUTH TP
Adder
0.116470588235294130.099
933982AD1-022 E
Adder
1.75647058823529421.493
927146AC1-208 E
Adder
1.62941176470588231.385
934622AD1-088 E
Adder
1.53176470588235311.302
934612AD1-087 E
Adder
1.26235294117647071.073
944641AF1-129 C
50/50
138.059138.059
316240AF1-291 C
50/50
2.8082.808
924814AB2-134 E
Adder
6.8941176470588245.86
316381AD1-082 C
50/50
0.7750.775
942342AE2-247 E
Adder
0.96470588235294120.82
919152AA1-139 E1
Adder
1.27058823529411781.08
920042AA2-088 E OP
Adder
4.2552941176470593.617
934521AD1-076 C
Adder
4.443.774
934511AD1-075 C
Adder
3.0564705882352942.598
3145723EMPORIA
Adder
0.205882352941176460.175
923573AB1-173 E OP
Adder
1.50588235294117641.28
919692AA2-053 E OP
Adder
1.7835294117647061.516
925785AC1-054 E
Adder
1.32352941176470581.125
316263AC1-034 C
Adder
2.5882352941176472.2
3150761HOPPOLC
50/50
1.0581.058
3145256KINGFORK
Adder
0.33882352941176470.288
925522AC1-027 E
Adder
0.380.323
941102AE2-104 E
Adder
1.98470588235294131.687
957872AF2-081 E
Adder
1.33058823529411761.131
962572AG1-106 E
Adder
0.55176470588235290.469
926214AC1-099 E
Adder
0.484705882352941150.412
932632AC2-084 E
Adder
1.2988235294117651.104
964242AG1-285 E
Adder
2.7964705882352942.377
924162AB2-060 E OP
Adder
1.41882352941176461.206
964792AG1-342 E
Adder
0.76588235294117660.651
925332AB2-190 E
50/50
4.8614.861
927226AC1-216 E
Adder
4.2082352941176473.577
936666AD2-085 E
Adder
2.62823529411764722.234
941591AE2-156 C
Adder
5.6635294117647064.814
944591AF1-124 C
Adder
13.87882352941176711.797
944601AF1-125 C
Adder
13.61647058823529511.574
938771AE1-103 C
Adder
1.1282352941176470.959
3145413WATKINS
Adder
0.271764705882352960.231
960081AF2-299 C
Adder
0.90588235294117650.77
926072AC1-086 E
Adder
4.4364705882352943.771
944011AF1-069 C
Adder
5.5494117647058824.717
963041AG1-153 C
Adder
2.32823529411764741.979
957862AF2-080 E
Adder
1.29176470588235311.098
962562AG1-105 E
Adder
1.93058823529411771.641
3150791HOPHCF3
50/50
1.6821.682
926662AC1-147 E
Adder
0.420.357
916192Z1-068 E
Adder
0.58588235294117650.498
957492AF2-043 E
Adder
0.4717647058823530.401
923852AB2-025 E
50/50
0.7170.717
939412AE1-173 E
Adder
23.37764705882352719.871
961942AG1-037 E
Adder
0.132941176470588230.113
961941AG1-037 C
Adder
0.198823529411764730.169
941032AE2-094 E
Adder
7.6070588235294126.466
941031AE2-094 C
Adder
16.9847058823529414.437
934332AD1-057 E
Adder
0.76705882352941180.652
934331AD1-057 C
Adder
1.47294117647058821.252
934321AD1-056 C
Adder
2.642.244
934322AD1-056 E
Adder
1.4317647058823531.217
927022AC1-189 E
Adder
1.59882352941176481.359
935162AD1-151 E
50/50
6.1926.192
943461AF1-017 C
Adder
0.6317647058823530.537
932596AC2-079 E
Adder
4.2658823529411763.626
316311AC2-079 C
Adder
2.61529411764705882.223
938532AE1-072 E
Adder
2.8635294117647062.434
3146326AYDLETT TAP
Adder
0.424705882352941160.361
917122Z2-027 E
Adder
0.435294117647058830.37
920692AA2-178 E
Adder
1.45294117647058841.235
966622AG1-532 E
Adder
0.452941176470588240.385
922923AB1-081 E OP
Adder
1.45294117647058841.235
3150731STONECA
50/50
4.7614.761
935161AD1-151 C
50/50
9.2889.288
932046AC2-012 E
Adder
4.1552941176470593.532
958161AF2-110 C
Adder
0.50941176470588230.433
938531AE1-072 C
Adder
5.49411764705882364.67
3145393UNCAMP
Adder
2.362.006
933981AD1-022 C
Adder
3.22705882352941182.743
900672V4-068 E
Adder
0.14235294117647060.121
924302AB2-077 E O1
Adder
0.448235294117647070.381
942341AE2-247 C
Adder
0.69882352941176470.594
943462AF1-017 E
Adder
1.03058823529411760.876
958162AF2-110 E
Adder
0.81058823529411760.689
919153AA1-139 E2
Adder
1.27058823529411781.08
934512AD1-075 E
Adder
1.5552941176470591.322
934502AD1-074 E
Adder
6.222352941176475.289
924516AB2-100 E1
Adder
1.5282352941176471.299
918512AA1-065 E OP
Adder
2.12470588235294141.806
966621AG1-532 C
Adder
0.67999999999999990.578
918532AA1-067 E
Adder
0.269411764705882350.229
924022AB2-043 E O1
Adder
1.73764705882352951.477
940432AE2-027 E
Adder
3.68588235294117663.133
934012AD1-025 E
Adder
5.4482352941176474.631
913392Y1-086 E
Adder
0.70470588235294120.599
939411AE1-173 C
Adder
35.0670588235294129.807
3137643SOCKMAN
Adder
0.315294117647058840.268
919710AA2-057 E
Adder
1.58117647058823541.344
924312AB2-078 E O1
Adder
0.448235294117647070.381
926274AC1-105 E
Adder
0.860.731
941101AE2-104 C
Adder
1.2482352941176471.061
316141AB2-099 E
Adder
0.098823529411764710.084
316088AB2-174 E
Adder
3.04352941176470632.587
923994AB2-040_E
Adder
2.8235294117647062.4
957481AF2-042 C
Adder
19.4705882352941216.55
961672AG1-007 E
Adder
0.204705882352941150.174
924322AB2-079 E O1
Adder
0.448235294117647070.381
3150781HOPHCF2
50/50
1.6821.682
942001AE2-212 C
50/50
2.3882.388
939192AE1-149 E
50/50
5.125.12
939312AE1-162 E
Adder
0.54941176470588240.467
934065AD1-033 E
Adder
1.53411764705882361.304
937226AE2-253 E
Adder
1.80588235294117651.535
934501AD1-074 C
Adder
12.22470588235294110.391
924517AB2-100 E2
Adder
1.5282352941176471.299
957482AF2-042 E
Adder
12.9811.033
961671AG1-007 C
Adder
0.36235294117647060.308
934621AD1-088 C
Adder
3.18117647058823572.704
935172AD1-152 E
Adder
1.86235294117647051.583
3150801HOPHCF4
50/50
2.5532.553
316349AD2-085 C
Adder
1.61058823529411771.369
935112AD1-144 E
Adder
0.315294117647058840.268
944582AF1-123 E
Adder
31.66823529411764726.918
944592AF1-124 E
Adder
31.78352941176470427.016
923832AB2-022 E
Adder
0.397647058823529460.338
938772AE1-103 E
Adder
1.55882352941176471.325
916042Z1-036 E
Adder
9.7517647058823538.289
960082AF2-299 E
Adder
0.60352941176470590.513
946281AF1-292 C
Adder
0.74941176470588230.637
926071AC1-086 C
Adder
9.7470588235294138.285
963042AG1-153 E
Adder
3.4917647058823532.968
927021AC1-189 C
Adder
3.2094117647058832.728
964241AG1-285 C
Adder
4.1952941176470593.566
924152AB2-059 E OP
Adder
2.0588235294117651.75
962561AG1-105 C
Adder
2.89529411764705862.461
316315AB2-025 C
50/50
0.2520.252
946282AF1-292 E
Adder
0.50.425
944012AF1-069 E
Adder
2.1552941176470591.832
957861AF2-080 C
Adder
2.9152941176470592.478
917512Z2-088 E OP1
Adder
1.88000000000000011.598
925595AC1-034 E
Adder
1.95294117647058821.66
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.8981.898
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.93631.936
CPLELTFEXP_CPLE->PJM
CLTF
3.9843.984
TVALTFEXP_TVA->PJM
CLTF
1.811.81
O66PJM->LTFIMP_O-066
CMTX_NF
6.2766.276
NYPJM->LTFIMP_NY
CLTF
0.4640.464
LGEELTFEXP_LGEE->PJM
CLTF
0.3190.319
WECLTFEXP_WEC->PJM
CLTF
0.1690.169
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.0758.075
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.5166.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.081.08
LAGNLTFEXP_LAGN->PJM
CLTF
2.3232.323
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9850.985
SIGELTFEXP_SIGE->PJM
CLTF
0.0650.065

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.85 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:888.27
MW Contribution:2.02
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.9 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:921.81
MW Contribution:1.99
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316083AB2-161 C
80/20
0.340.34
940641AE2-051 C
80/20
6.3516.351
316336AC2-165 C
Adder
-2.925882352941177-2.487
3150651CHESTF6
80/20
25.04225.042
957871AF2-081 C
Adder
3.42823529411764752.914
3151151S HAMPT1
80/20
0.5930.593
962571AG1-106 C
80/20
1.2051.205
316274AC1-208 C
Adder
3.50823529411764762.982
3151311EDGECMA
Adder
5.7282352941176474.869
3151211GRAVEL5
80/20
1.1271.127
943461AF1-017 C
80/20
0.6470.647
316311AC2-079 C
80/20
2.6862.686
3151171GRAVELC
80/20
0.3880.388
942341AE2-247 C
80/20
0.7150.715
966621AG1-532 C
80/20
0.6420.642
3150761HOPPOLC
80/20
1.0681.068
933291AC2-141 C
Adder
9.0470588235294127.69
316087AB2-174 C
80/20
0.5210.521
939411AE1-173 C
80/20
32.73632.736
3137643SOCKMAN
80/20
0.30.3
3151031BRUNSWICKG2
80/20
2.9812.981
3150731STONECA
80/20
4.8074.807
935161AD1-151 C
80/20
9.5159.515
3151221GRAVEL6
80/20
1.141.14
3151201GRAVEL4
80/20
1.1421.142
958161AF2-110 C
80/20
0.5350.535
938531AE1-072 C
Adder
6.04588235294117655.139
933981AD1-022 C
Adder
3.26941176470588252.779
3151261ROARAP2
80/20
0.5670.567
3147043LAWRENC
80/20
0.1270.127
3152411Z1-086 GT1
80/20
3.8333.833
961611AG1-000B C
80/20
7.6267.626
316236AE1-162 C
80/20
0.1440.144
940541AE2-040 C
80/20
1.6761.676
940481AE2-033 C
80/20
9.2759.275
3151411GASTONB
80/20
1.3541.354
316181AB2-040 GEN
80/20
0.5530.553
3156063AA2-053SOLA
80/20
0.6110.611
3151281ROARAP4
80/20
0.5360.536
316033AB2-134 GEN
80/20
1.1791.179
934011AD1-025 C
80/20
1.4591.459
939191AE1-149 C
80/20
7.67.6
316365AB2-100 C1
80/20
0.4810.481
3151041BRUNSWICKG3
80/20
2.9812.981
3151021BRUNSWICKG1
80/20
2.9812.981
3152441Z1-086 ST
80/20
6.6736.673
3152431Z1-086 GT3
80/20
3.8323.832
3152421Z1-086 GT2
80/20
3.8323.832
3150771HOPHCF1
80/20
1.6981.698
940431AE2-027 C
80/20
5.4285.428
316132AB2-190 C
80/20
2.552.55
944581AF1-123 C
Adder
15.41882352941176613.106
941101AE2-104 C
80/20
1.3111.311
3156083AA2-088SOLA
80/20
0.4240.424
313506AB1-173 C OP
80/20
0.4910.491
3151361ROSEMG1
80/20
0.8890.889
957481AF2-042 C
Adder
16.9176470588235314.38
944641AF1-129 C
80/20
137.537137.537
316240AF1-291 C
80/20
2.7922.792
3151191GRAVEL3
80/20
1.1271.127
316381AD1-082 C
80/20
0.7760.776
934521AD1-076 C
Adder
4.5247058823529423.846
934511AD1-075 C
Adder
3.1141176470588232.647
316011AB1-132 C OP
80/20
1.0341.034
316263AC1-034 C
Adder
2.44235294117647062.076
3150781HOPHCF2
80/20
1.6981.698
942001AE2-212 C
80/20
2.3582.358
3151161SURRY 1
80/20
11.09811.098
934501AD1-074 C
Adder
12.4576470588235310.589
3156073AA1-063SOLA
80/20
0.570.57
3151371ROSEMS1
80/20
0.5510.551
961671AG1-007 C
Adder
0.34588235294117650.294
941591AE2-156 C
Adder
6.2764705882352945.335
944591AF1-124 C
Adder
15.47294117647058813.152
944601AF1-125 C
Adder
15.18117647058823612.904
938771AE1-103 C
80/20
1.1561.156
960081AF2-299 C
80/20
0.8560.856
944011AF1-069 C
80/20
4.8054.805
963041AG1-153 C
Adder
2.0188235294117651.716
316315AB2-025 C
80/20
0.2380.238
957861AF2-080 C
Adder
2.8035294117647062.383
3150801HOPHCF4
80/20
2.5782.578
316349AD2-085 C
80/20
1.6511.651
316023AB2-100 C2
80/20
0.4810.481
946281AF1-292 C
80/20
0.7080.708
926071AC1-086 C
80/20
9.3179.317
3151051BRUNSWICKS1
80/20
6.1926.192
927021AC1-189 C
Adder
3.0858823529411772.623
3150791HOPHCF3
80/20
1.6981.698
316369AC1-216 C
80/20
0.90.9
961941AG1-037 C
Adder
0.196470588235294150.167
3151391GASTONA
80/20
1.3541.354
3151381ROSEMG2
80/20
0.4160.416
941031AE2-094 C
80/20
14.70614.706
934331AD1-057 C
Adder
1.39882352941176481.189
934321AD1-056 C
Adder
2.50705882352941162.131
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7131.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.64628.646
CPLELTFEXP_CPLE->PJM
CLTF
3.5953.595
TVALTFEXP_TVA->PJM
CLTF
1.6011.601
NYPJM->LTFIMP_NY
CLTF
0.4310.431
LGEELTFEXP_LGEE->PJM
CLTF
0.2740.274
WECLTFEXP_WEC->PJM
CLTF
0.1450.145
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.8996.899
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.7315.731
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
0.9380.938
LAGNLTFEXP_LAGN->PJM
CLTF
2.0572.057
SIGELTFEXP_SIGE->PJM
CLTF
0.0560.056

Details for 6POE-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6POE-6TYLER1 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.13 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:563.34
MW Contribution:5.48
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6POE-6TYLER1 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:588.85
MW Contribution:5.39
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934576AD1-082 E
50/50
3.6773.677
943172AE2-346 E
Adder
0.191764705882352950.163
918492AA1-063AE OP
Adder
1.49058823529411751.267
962571AG1-106 C
Adder
1.15882352941176480.985
917332KELFORD E
Adder
0.53411764705882360.454
316274AC1-208 C
Adder
3.23411764705882382.749
917342Z2-044 E
Adder
0.209411764705882350.178
937482AD2-202 E
Adder
0.35647058823529410.303
3151311EDGECMA
Adder
5.4047058823529424.594
316084AB2-161 E
50/50
4.6154.615
316083AB2-161 C
50/50
0.4620.462
927146AC1-208 E
Adder
1.43647058823529421.221
934622AD1-088 E
Adder
1.5035294117647061.278
934612AD1-087 E
Adder
1.21882352941176491.036
962572AG1-106 E
Adder
0.50705882352941180.431
926214AC1-099 E
Adder
0.420.357
932632AC2-084 E
Adder
1.12235294117647060.954
964242AG1-285 E
Adder
2.76470588235294162.35
924162AB2-060 E OP
Adder
1.39764705882352951.188
964792AG1-342 E
Adder
0.74588235294117660.634
943461AF1-017 C
Adder
0.66588235294117650.566
932596AC2-079 E
Adder
4.3541176470588243.701
316311AC2-079 C
Adder
2.6682352941176472.268
966622AG1-532 E
Adder
0.434117647058823550.369
922923AB1-081 E OP
Adder
1.2952941176470591.101
3145393UNCAMP
Adder
1.841.564
900672V4-068 E
Adder
0.116470588235294130.099
924302AB2-077 E O1
Adder
0.440.374
942341AE2-247 C
Adder
0.73647058823529410.626
943462AF1-017 E
Adder
1.08705882352941190.924
924516AB2-100 E1
Adder
1.4764705882352941.255
966621AG1-532 C
Adder
0.65058823529411770.553
924022AB2-043 E O1
Adder
1.7070588235294121.451
3147223TWITTYS
Adder
0.288235294117647030.245
939191AE1-149 C
50/50
11.48911.489
3143316POE
50/50
2.8062.806
926206AC1-098 E
Adder
1.26941176470588221.079
964791AG1-342 C
Adder
1.11882352941176480.951
939411AE1-173 C
Adder
28.66352941176470624.364
3137643SOCKMAN
Adder
0.289411764705882370.246
919710AA2-057 E
Adder
1.39647058823529411.187
944641AF1-129 C
Adder
-70.29176470588236-59.748
316240AF1-291 C
Adder
-2.144705882352941-1.823
316381AD1-082 C
50/50
1.0531.053
942342AE2-247 E
Adder
1.01647058823529420.864
920042AA2-088 E OP
Adder
3.4941176470588242.97
3145723EMPORIA
Adder
0.196470588235294150.167
923573AB1-173 E OP
Adder
1.40588235294117661.195
919692AA2-053 E OP
Adder
1.57764705882352941.341
925785AC1-054 E
Adder
1.22941176470588221.045
316263AC1-034 C
Adder
2.30588235294117631.96
940541AE2-040 C
50/50
1.7881.788
940481AE2-033 C
50/50
9.8449.844
940482AE2-033 E
50/50
6.6366.636
923263AB1-132 E OP
Adder
2.60588235294117652.215
925612AC1-036 E
Adder
0.260.221
924312AB2-078 E O1
Adder
0.440.374
926274AC1-105 E
Adder
0.83529411764705890.71
316141AB2-099 E
Adder
0.080.068
316088AB2-174 E
Adder
2.8647058823529412.435
923994AB2-040_E
Adder
2.63529411764705922.24
957481AF2-042 C
Adder
18.75411764705882315.941
961672AG1-007 E
Adder
0.17764705882352940.151
924322AB2-079 E O1
Adder
0.440.374
939192AE1-149 E
50/50
7.667.66
924517AB2-100 E2
Adder
1.4764705882352941.255
957482AF2-042 E
Adder
12.50352941176470610.628
961671AG1-007 C
Adder
0.31294117647058830.266
934621AD1-088 C
Adder
3.12235294117647082.654
935172AD1-152 E
Adder
1.7964705882352941.527
936666AD2-085 E
Adder
2.77176470588235272.356
938771AE1-103 C
Adder
0.87058823529411770.74
3145413WATKINS
Adder
0.215294117647058830.183
960081AF2-299 C
Adder
0.86705882352941180.737
926072AC1-086 E
Adder
4.0752941176470593.464
944011AF1-069 C
Adder
5.2117647058823534.43
963041AG1-153 C
Adder
2.1905882352941181.862
957862AF2-080 E
Adder
1.08823529411764720.925
962562AG1-105 E
Adder
1.8835294117647061.601
316315AB2-025 C
50/50
0.2540.254
946282AF1-292 E
Adder
0.47882352941176470.407
944012AF1-069 E
Adder
2.02470588235294141.721
957861AF2-080 C
Adder
2.4564705882352942.088
917512Z2-088 E OP1
Adder
1.60588235294117651.365
316349AD2-085 C
Adder
1.69882352941176461.444
938772AE1-103 E
Adder
1.20117647058823531.021
960082AF2-299 E
Adder
0.57764705882352940.491
946281AF1-292 C
Adder
0.71764705882352940.61
926071AC1-086 C
Adder
8.9552941176470597.612
963042AG1-153 E
Adder
3.28588235294117672.793
927021AC1-189 C
Adder
2.7035294117647062.298
964241AG1-285 C
Adder
4.1470588235294123.525
924152AB2-059 E OP
Adder
1.83411764705882341.559
962561AG1-105 C
Adder
2.82588235294117672.402
923852AB2-025 E
50/50
0.7230.723
939412AE1-173 E
Adder
19.10941176470588216.243
961942AG1-037 E
Adder
0.105882352941176470.09
961941AG1-037 C
Adder
0.158823529411764720.135
941032AE2-094 E
Adder
7.1447058823529426.073
941031AE2-094 C
Adder
15.95176470588235213.559
934332AD1-057 E
Adder
0.69411764705882350.59
934331AD1-057 C
Adder
1.3317647058823531.132
934321AD1-056 C
Adder
2.3882352941176472.03
934322AD1-056 E
Adder
1.2952941176470591.101
927022AC1-189 E
Adder
1.34705882352941191.145
925595AC1-034 E
Adder
1.74000000000000021.479
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.7591.759
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.05430.054
CPLELTFEXP_CPLE->PJM
CLTF
3.6893.689
TVALTFEXP_TVA->PJM
CLTF
1.8151.815
O66PJM->LTFIMP_O-066
CMTX_NF
4.8534.853
NYPJM->LTFIMP_NY
CLTF
0.3510.351
LGEELTFEXP_LGEE->PJM
CLTF
0.3660.366
WECLTFEXP_WEC->PJM
CLTF
0.1950.195
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.5019.501
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.7336.733
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.1821.182
LAGNLTFEXP_LAGN->PJM
CLTF
2.3242.324
G-007PJM->LTFIMP_G-007
CMTX_NF
0.7620.762
SIGELTFEXP_SIGE->PJM
CLTF
0.0720.072

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.54 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1199.86
MW Contribution:11.7
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.15 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1216.94
MW Contribution:11.66
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3151041BRUNSWICKG3
50/50
6.916.91
3151021BRUNSWICKG1
50/50
6.916.91
942462AE2-259 E
Adder
2.21764705882352951.885
964791AG1-342 C
Adder
1.43529411764705881.22
933292AC2-141 E
Adder
6.3529411764705895.4
944602AF1-125 E
Adder
38.536470588235332.756
3145506HICKORY
Adder
0.80470588235294130.684
957871AF2-081 C
Adder
3.47411764705882352.953
937482AD2-202 E
50/50
0.6470.647
961792AG1-021 E
Adder
0.50117647058823530.426
940641AE2-051 C
50/50
14.85114.851
934622AD1-088 E
50/50
2.6942.694
934611AD1-087 C
50/50
0.7660.766
934612AD1-087 E
50/50
2.212.21
927255AC1-221 E
Adder
1.70117647058823531.446
944641AF1-129 C
Adder
-99.89764705882352-84.913
316240AF1-291 C
Adder
-2.2705882352941176-1.93
919152AA1-139 E1
Adder
1.42117647058823531.208
3145723EMPORIA
Adder
-0.3270588235294118-0.278
959311AF2-222 C
Adder
7.2776470588235296.186
925522AC1-027 E
Adder
0.430588235294117660.366
933291AC2-141 C
Adder
14.88235294117647112.65
926755AC1-161 E
Adder
6.3529411764705895.4
957872AF2-081 E
Adder
1.48941176470588241.266
964242AG1-285 E
Adder
3.99647058823529383.397
924162AB2-060 E OP
Adder
1.4435294117647061.227
964792AG1-342 E
Adder
0.95647058823529410.813
932763AC2-100 E
Adder
1.14235294117647060.971
938532AE1-072 E
Adder
3.1047058823529412.639
3146326AYDLETT TAP
Adder
0.455294117647058850.387
3147133PAMPLIN
Adder
0.377647058823529450.321
927264AC1-222 E
Adder
1.781.513
932046AC2-012 E
Adder
4.4317647058823533.767
938531AE1-072 C
Adder
5.95529411764705955.062
3152411Z1-086 GT1
50/50
8.9758.975
924302AB2-077 E O1
Adder
0.45058823529411770.383
919153AA1-139 E2
Adder
1.42117647058823531.208
940642AE2-051 E
50/50
9.9019.901
966621AG1-532 C
Adder
-1.14-0.969
924022AB2-043 E O1
Adder
1.75058823529411781.488
3147223TWITTYS
Adder
0.42235294117647060.359
959312AF2-222 E
Adder
4.8764705882352944.145
913392Y1-086 E
Adder
0.66235294117647060.563
939411AE1-173 C
50/50
67.01167.011
3137643SOCKMAN
Adder
-0.34352941176470586-0.292
3151031BRUNSWICKG2
50/50
6.916.91
937481AD2-202 C
50/50
0.2220.222
3152441Z1-086 ST
50/50
15.62315.623
3152431Z1-086 GT3
50/50
8.9718.971
3152421Z1-086 GT2
50/50
8.9718.971
925612AC1-036 E
Adder
0.381176470588235340.324
924312AB2-078 E O1
Adder
0.45058823529411770.383
926274AC1-105 E
Adder
1.15529411764705880.982
944581AF1-123 C
Adder
17.0976470588235314.533
957481AF2-042 C
50/50
35.70935.709
924322AB2-079 E O1
Adder
0.45058823529411770.383
946302AF1-294 E
Adder
1.02352941176470580.87
943902AF1-058 E
Adder
0.58823529411764710.5
942001AE2-212 C
Adder
-2.8705882352941177-2.44
934065AD1-033 E
Adder
1.87294117647058831.592
937226AE2-253 E
Adder
2.081.768
957482AF2-042 E
50/50
23.80623.806
934621AD1-088 C
50/50
5.5965.596
946301AF1-294 C
Adder
1.2082352941176471.027
942461AE2-259 C
Adder
3.32588235294117632.827
935172AD1-152 E
Adder
3.1047058823529412.639
944012AF1-069 E
50/50
4.4634.463
944582AF1-123 E
Adder
39.15058823529411633.278
944592AF1-124 E
Adder
39.2929411764705933.399
923832AB2-022 E
Adder
0.374117647058823550.318
946281AF1-292 C
Adder
-1.2576470588235293-1.069
3151051BRUNSWICKS1
50/50
14.35614.356
963042AG1-153 E
50/50
7.0227.022
3151531CLOVER1
50/50
7.797.79
964241AG1-285 C
Adder
5.9952941176470595.096
941591AE2-156 C
Adder
6.1035294117647065.188
944591AF1-124 C
Adder
17.15764705882352814.584
944601AF1-125 C
Adder
16.8341176470588214.309
944011AF1-069 C
50/50
11.48911.489
963041AG1-153 C
50/50
4.6824.682
3151541CLOVER2
50/50
7.7177.717
936261AD2-033 C
Adder
4.3352941176470593.685
961791AG1-021 C
Adder
0.58823529411764710.5
962562AG1-105 E
Adder
2.3352941176470591.985
3138533PONTONDP
Adder
0.217647058823529420.185
958212AF2-115 E
Adder
0.62588235294117660.532
962561AG1-105 C
Adder
3.50352941176470622.978
926662AC1-147 E
Adder
0.448235294117647070.381
916192Z1-068 E
Adder
0.6682352941176470.568
939412AE1-173 E
50/50
44.67444.674
941032AE2-094 E
50/50
15.74915.749
941031AE2-094 C
50/50
35.16335.163
934331AD1-057 C
Adder
-1.1952941176470588-1.016
934321AD1-056 C
Adder
-2.142352941176471-1.821
936262AD2-033 E
Adder
2.89058823529411772.457
958211AF2-115 C
Adder
0.73529411764705890.625
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9681.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.24536.245
CPLELTFEXP_CPLE->PJM
CLTF
4.1284.128
TVALTFEXP_TVA->PJM
CLTF
2.2832.283
O66PJM->LTFIMP_O-066
CMTX_NF
6.1826.182
NYPJM->LTFIMP_NY
CLTF
0.4470.447
LGEELTFEXP_LGEE->PJM
CLTF
0.4670.467
WECLTFEXP_WEC->PJM
CLTF
0.2490.249
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.10812.108
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.4868.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.4991.499
LAGNLTFEXP_LAGN->PJM
CLTF
2.9182.918
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9710.971
SIGELTFEXP_SIGE->PJM
CLTF
0.0920.092

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.16 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4182.74
MW Contribution:24.49
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.7 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4637.48
MW Contribution:24.49
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
939191AE1-149 C
Adder
13.15411764705882411.181
3143316POE
Adder
1.71764705882352931.46
901082W1-029 E
Adder
48.63529411764706441.34
926206AC1-098 E
Adder
5.25647058823529444.468
3151041BRUNSWICKG3
50/50
14.45714.457
3151021BRUNSWICKG1
50/50
14.45714.457
964791AG1-342 C
Adder
4.7858823529411764.068
934576AD1-082 E
Adder
5.7482352941176484.886
916191Z1-068 C
50/50
0.0680.068
933292AC2-141 E
50/50
20.76320.763
316294AC1-161 C
50/50
7.9487.948
944602AF1-125 E
50/50
159.152159.152
3145506HICKORY
50/50
3.3883.388
943612AF1-032 E
Adder
1.40823529411764731.197
957871AF2-081 C
50/50
15.47915.479
940492AE2-034 E
Adder
4.6305882352941183.936
934522AD1-076 E
Adder
9.3011764705882357.906
943172AE2-346 E
Adder
0.88941176470588230.756
918492AA1-063AE OP
Adder
5.9423529411764715.051
962571AG1-106 C
Adder
3.9364705882352943.346
917332KELFORD E
Adder
2.39764705882352922.038
925122AB2-169 E
Adder
8.4305882352941197.166
316274AC1-208 C
Adder
12.93882352941176410.998
917342Z2-044 E
Adder
0.84705882352941180.72
937482AD2-202 E
Adder
1.57764705882352941.341
3151311EDGECMA
Adder
21.84705882352941218.57
932046AC2-012 E
50/50
20.04320.043
958161AF2-110 C
Adder
2.04352941176470631.737
316017AA1-139 ULT1
50/50
1.6761.676
938531AE1-072 C
50/50
27.18327.183
3145393UNCAMP
Adder
9.0117647058823537.66
933981AD1-022 C
Adder
13.02235294117647211.069
900672V4-068 E
Adder
0.52352941176470590.445
316084AB2-161 E
Adder
7.2141176470588236.132
3145946PLYMOUTH TP
Adder
0.48235294117647060.41
933982AD1-022 E
Adder
7.0894117647058836.026
940641AE2-051 C
50/50
31.3831.38
927146AC1-208 E
Adder
5.74470588235294164.883
934622AD1-088 E
Adder
6.6576470588235295.659
934612AD1-087 E
Adder
5.3905882352941184.582
942342AE2-247 E
Adder
2.92470588235294172.486
316036AC1-147 C
50/50
0.5640.564
919152AA1-139 E1
50/50
6.336.33
316018AA1-139 ULT2
50/50
1.6761.676
920042AA2-088 E OP
Adder
15.59882352941176513.259
934521AD1-076 C
Adder
18.24823529411764515.511
934511AD1-075 C
Adder
12.56117647058823510.677
3145723EMPORIA
Adder
0.62470588235294120.531
923573AB1-173 E OP
Adder
4.7517647058823534.039
919692AA2-053 E OP
Adder
6.1282352941176475.209
925785AC1-054 E
Adder
4.8741176470588234.143
316263AC1-034 C
Adder
9.344705882352947.943
959311AF2-222 C
Adder
21.718.445
3150921YORKTN3
Adder
152.65647058823532129.758
3145256KINGFORK
Adder
1.48823529411764691.265
925522AC1-027 E
50/50
1.8771.877
933291AC2-141 C
50/50
48.6448.64
926755AC1-161 E
50/50
20.76320.763
941102AE2-104 E
Adder
7.966.766
957872AF2-081 E
50/50
6.6346.634
962572AG1-106 E
Adder
1.72235294117647061.464
926214AC1-099 E
Adder
1.73647058823529421.476
932632AC2-084 E
Adder
4.6458823529411763.949
964242AG1-285 E
Adder
11.97764705882352810.181
924162AB2-060 E OP
Adder
5.8752941176470594.994
964792AG1-342 E
Adder
3.1905882352941182.712
943461AF1-017 C
Adder
1.91529411764705881.628
932596AC2-079 E
Adder
13.36941176470588411.364
316311AC2-079 C
Adder
8.1941176470588236.965
938532AE1-072 E
50/50
14.1714.17
3146326AYDLETT TAP
50/50
2.0962.096
917122Z2-027 E
Adder
2.061.751
920692AA2-178 E
Adder
6.1741176470588245.248
966622AG1-532 E
Adder
1.35411764705882361.151
922923AB1-081 E OP
Adder
5.2458823529411764.459
3152411Z1-086 GT1
50/50
18.60518.605
924302AB2-077 E O1
Adder
1.84705882352941191.57
942341AE2-247 C
Adder
2.11764705882352941.8
943462AF1-017 E
Adder
3.12588235294117662.657
958162AF2-110 E
Adder
3.24941176470588242.762
316388AE2-253 GEN
50/50
3.0473.047
919153AA1-139 E2
50/50
6.336.33
934512AD1-075 E
Adder
6.3941176470588235.435
934502AD1-074 E
Adder
25.5776470588235321.741
924516AB2-100 E1
Adder
4.23058823529411753.596
918512AA1-065 E OP
Adder
8.1470588235294116.925
940642AE2-051 E
50/50
20.9220.92
966621AG1-532 C
Adder
2.0317647058823531.727
918532AA1-067 E
Adder
1.02823529411764710.874
924022AB2-043 E O1
Adder
7.1670588235294126.092
3147223TWITTYS
Adder
1.2588235294117651.07
959312AF2-222 E
Adder
2.9682352941176472.523
913392Y1-086 E
50/50
3.383.38
939411AE1-173 C
50/50
158.79158.79
3137643SOCKMAN
Adder
1.03058823529411760.876
3151031BRUNSWICKG2
50/50
14.45714.457
919710AA2-057 E
Adder
5.6458823529411774.799
961611AG1-000B C
Adder
19.52941176470588416.6
316375AC2-012 C
50/50
2.0662.066
313526AB2-022 C
50/50
0.5790.579
940541AE2-040 C
Adder
4.263.621
940481AE2-033 C
Adder
23.97176470588235420.376
940482AE2-033 E
Adder
16.1613.736
923263AB1-132 E OP
Adder
8.8564705882352937.528
3152441Z1-086 ST
50/50
32.38732.387
3152431Z1-086 GT3
50/50
18.59718.597
3152421Z1-086 GT2
50/50
18.59718.597
925612AC1-036 E
Adder
1.13647058823529410.966
924312AB2-078 E O1
Adder
1.84705882352941191.57
926274AC1-105 E
Adder
3.63.06
3150981CHESPKA
50/50
0.6670.667
316185AD1-033 C
50/50
1.9111.911
944581AF1-123 C
50/50
70.6170.61
941101AE2-104 C
Adder
5.00705882352941254.256
316320Y1-086 C
50/50
0.3390.339
316141AB2-099 E
Adder
0.370588235294117660.315
316088AB2-174 E
Adder
9.4435294117647068.027
923994AB2-040_E
Adder
8.9094117647058837.573
957481AF2-042 C
50/50
83.22783.227
961672AG1-007 E
Adder
0.75529411764705890.642
924322AB2-079 E O1
Adder
1.84705882352941191.57
939192AE1-149 E
Adder
8.7694117647058827.454
939312AE1-162 E
Adder
1.95882352941176491.665
3150991CHESPKB
50/50
1.1051.105
934065AD1-033 E
50/50
7.7977.797
937226AE2-253 E
50/50
9.0629.062
934501AD1-074 C
Adder
50.2447058823529442.708
924517AB2-100 E2
Adder
4.23058823529411753.596
957482AF2-042 E
50/50
55.48555.485
961671AG1-007 C
Adder
1.33294117647058831.133
934621AD1-088 C
Adder
13.82823529411764711.754
935172AD1-152 E
Adder
7.9105882352941186.724
3151101ELIZAR3
50/50
4.9744.974
316315AB2-025 C
50/50
0.6050.605
946282AF1-292 E
Adder
1.49529411764705871.271
944012AF1-069 E
50/50
9.0749.074
957861AF2-080 C
Adder
10.917647058823539.28
917512Z2-088 E OP1
Adder
6.9717647058823535.926
316349AD2-085 C
Adder
4.8858823529411764.153
935112AD1-144 E
Adder
1.38117647058823521.174
3151091ELIZAR2
50/50
4.8274.827
944582AF1-123 E
50/50
161.69161.69
944592AF1-124 E
50/50
162.275162.275
923832AB2-022 E
50/50
1.9081.908
938772AE1-103 E
Adder
6.0023529411764715.102
916042Z1-036 E
Adder
43.3141176470588236.817
960082AF2-299 E
Adder
1.80588235294117651.535
946281AF1-292 C
Adder
2.24235294117647041.906
926071AC1-086 C
Adder
30.4329411764705925.868
3151051BRUNSWICKS1
50/50
30.03530.035
963042AG1-153 E
50/50
14.69214.692
927021AC1-189 C
Adder
12.02000000000000110.217
964241AG1-285 C
Adder
17.9658823529411815.271
924152AB2-059 E OP
Adder
7.4317647058823546.317
962561AG1-105 C
Adder
12.04705882352941210.24
936666AD2-085 E
Adder
7.9705882352941196.775
941591AE2-156 C
50/50
27.4127.41
3151081ELIZAR1
50/50
4.9124.912
316316AC1-027 C
50/50
0.4870.487
944591AF1-124 C
50/50
70.86170.861
944601AF1-125 C
50/50
69.52369.523
938771AE1-103 C
Adder
4.3470588235294113.695
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.70823529411764732.302
926072AC1-086 E
Adder
13.85058823529411711.773
944011AF1-069 C
50/50
23.35723.357
963041AG1-153 C
50/50
9.7959.795
957862AF2-080 E
Adder
4.844.114
962562AG1-105 E
Adder
8.0317647058823526.827
926662AC1-147 E
50/50
2.0262.026
916192Z1-068 E
50/50
2.92.9
957492AF2-043 E
Adder
2.16705882352941171.842
923852AB2-025 E
50/50
1.7231.723
939412AE1-173 E
50/50
105.86105.86
961942AG1-037 E
Adder
0.494117647058823550.42
961941AG1-037 C
Adder
0.74117647058823530.63
941032AE2-094 E
50/50
32.01732.017
941031AE2-094 C
50/50
71.48571.485
934332AD1-057 E
Adder
2.5917647058823532.203
934331AD1-057 C
Adder
4.9764705882352954.23
934321AD1-056 C
Adder
8.927.582
934322AD1-056 E
Adder
4.8388235294117664.113
927022AC1-189 E
Adder
5.9882352941176475.09
925595AC1-034 E
Adder
7.0494117647058835.992
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6337.633
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.923129.923
CPLELTFEXP_CPLE->PJM
CLTF
16.01716.017
TVALTFEXP_TVA->PJM
CLTF
7.5637.563
O66PJM->LTFIMP_O-066
CMTX_NF
29.52729.527
NYPJM->LTFIMP_NY
CLTF
2.172.17
LGEELTFEXP_LGEE->PJM
CLTF
1.3891.389
WECLTFEXP_WEC->PJM
CLTF
0.7290.729
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.88834.888
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.38927.389
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.6044.604
LAGNLTFEXP_LAGN->PJM
CLTF
9.689.68
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6364.636
SIGELTFEXP_SIGE->PJM
CLTF
0.2790.279

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.22 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4106.12
MW Contribution:23.45
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316084AB2-161 E
Adder
6.8258823529411765.802
3145946PLYMOUTH TP
Adder
0.44705882352941180.38
933982AD1-022 E
Adder
6.582352941176475.595
940641AE2-051 C
50/50
29.73129.731
927146AC1-208 E
Adder
5.44117647058823554.625
934622AD1-088 E
Adder
6.4094117647058835.448
934611AD1-087 C
50/50
1.7961.796
934612AD1-087 E
50/50
5.1825.182
934576AD1-082 E
Adder
5.4388235294117654.623
916191Z1-068 C
50/50
0.0610.061
933292AC2-141 E
50/50
18.61818.618
316294AC1-161 C
50/50
7.1277.127
944602AF1-125 E
50/50
144.526144.526
3145506HICKORY
50/50
3.0783.078
943612AF1-032 E
Adder
1.28470588235294141.092
957871AF2-081 C
50/50
14.0814.08
940492AE2-034 E
Adder
4.2752941176470593.634
934522AD1-076 E
Adder
8.6200000000000017.327
943172AE2-346 E
Adder
0.8317647058823530.707
918492AA1-063AE OP
Adder
5.6035294117647064.763
962571AG1-106 C
Adder
3.73764705882352953.177
917332KELFORD E
Adder
2.25058823529411761.913
925122AB2-169 E
Adder
7.8694117647058836.689
316274AC1-208 C
Adder
12.25411764705882510.416
917342Z2-044 E
Adder
0.80352941176470590.683
937482AD2-202 E
50/50
1.5171.517
3151311EDGECMA
Adder
20.7705882352941217.655
942341AE2-247 C
Adder
1.9647058823529411.67
943462AF1-017 E
Adder
2.90117647058823552.466
958162AF2-110 E
Adder
2.98235294117647072.535
316388AE2-253 GEN
50/50
2.7712.771
919153AA1-139 E2
50/50
5.7585.758
934512AD1-075 E
Adder
5.9258823529411765.037
934502AD1-074 E
Adder
23.70588235294117420.15
924516AB2-100 E1
Adder
4.042352941176473.436
918512AA1-065 E OP
Adder
7.6023529411764716.462
940642AE2-051 E
50/50
19.82119.821
966621AG1-532 C
Adder
1.94000000000000021.649
918532AA1-067 E
Adder
0.96823529411764710.823
924022AB2-043 E O1
Adder
6.95.865
3147223TWITTYS
Adder
1.21764705882352931.035
959312AF2-222 E
Adder
14.06705882352941311.957
3150921YORKTN3
Adder
46.1517647058823539.229
3145256KINGFORK
Adder
1.35529411764705881.152
925522AC1-027 E
50/50
1.7051.705
933291AC2-141 C
50/50
43.61643.616
926755AC1-161 E
50/50
18.61818.618
941102AE2-104 E
Adder
7.3058823529411766.21
957872AF2-081 E
50/50
6.0346.034
962572AG1-106 E
Adder
1.63529411764705881.39
926214AC1-099 E
Adder
1.64117647058823551.395
932632AC2-084 E
Adder
4.3905882352941183.732
964242AG1-285 E
Adder
11.549.809
924162AB2-060 E OP
Adder
5.6588235294117644.81
964792AG1-342 E
Adder
3.07411764705882362.613
913392Y1-086 E
Adder
3.08235294117647072.62
939411AE1-173 C
50/50
149.153149.153
3137643SOCKMAN
Adder
0.97882352941176460.832
3151031BRUNSWICKG2
50/50
13.84313.843
919710AA2-057 E
Adder
5.3541176470588244.551
937481AD2-202 C
50/50
0.5210.521
932046AC2-012 E
50/50
18.21618.216
958161AF2-110 C
Adder
1.8752941176470591.594
316017AA1-139 ULT1
50/50
1.5241.524
938531AE1-072 C
50/50
24.73924.739
3145393UNCAMP
Adder
8.3505882352941197.098
933981AD1-022 C
Adder
12.09058823529411710.277
900672V4-068 E
Adder
0.490588235294117660.417
3152411Z1-086 GT1
50/50
17.81217.812
924302AB2-077 E O1
Adder
1.77764705882352941.511
943461AF1-017 C
Adder
1.77764705882352941.511
932596AC2-079 E
Adder
12.38941176470588310.531
316311AC2-079 C
Adder
7.5929411764705886.454
938532AE1-072 E
50/50
12.89612.896
3146326AYDLETT TAP
50/50
1.9081.908
917122Z2-027 E
Adder
1.88117647058823521.599
920692AA2-178 E
Adder
5.74.845
966622AG1-532 E
Adder
1.29294117647058831.099
922923AB1-081 E OP
Adder
4.9882352941176474.24
939191AE1-149 C
Adder
12.63647058823529410.741
3143316POE
Adder
1.67647058823529421.425
901082W1-029 E
Adder
44.4776470588235337.806
926206AC1-098 E
Adder
4.9670588235294124.222
3151041BRUNSWICKG3
50/50
13.84313.843
3151021BRUNSWICKG1
50/50
13.84313.843
964791AG1-342 C
Adder
4.6105882352941173.919
961611AG1-000B C
Adder
18.02352941176470615.32
316375AC2-012 C
50/50
1.8781.878
940541AE2-040 C
50/50
4.0974.097
940481AE2-033 C
50/50
23.03323.033
940482AE2-033 E
50/50
15.52815.528
923263AB1-132 E OP
Adder
8.4105882352941177.149
3152441Z1-086 ST
50/50
31.00731.007
3152431Z1-086 GT3
50/50
17.80517.805
3152421Z1-086 GT2
50/50
17.80517.805
925612AC1-036 E
Adder
1.09882352941176480.934
924312AB2-078 E O1
Adder
1.77764705882352941.511
926274AC1-105 E
Adder
3.4682352941176472.948
942342AE2-247 E
Adder
2.71411764705882372.307
919152AA1-139 E1
50/50
5.7585.758
316018AA1-139 ULT2
50/50
1.5241.524
920042AA2-088 E OP
Adder
14.57411764705882412.388
934521AD1-076 C
Adder
16.9129411764705914.376
934511AD1-075 C
Adder
11.6423529411764739.896
3145723EMPORIA
Adder
0.59647058823529410.507
923573AB1-173 E OP
Adder
4.5223529411764713.844
919692AA2-053 E OP
Adder
5.797647058823534.928
925785AC1-054 E
Adder
4.65176470588235353.954
316263AC1-034 C
Adder
8.8847058823529417.552
959311AF2-222 C
Adder
20.9952941176470617.846
316185AD1-033 C
50/50
1.7361.736
944581AF1-123 C
50/50
64.12164.121
941101AE2-104 C
Adder
4.5952941176470593.906
316141AB2-099 E
Adder
0.347058823529411750.295
316088AB2-174 E
Adder
8.997647058823537.648
923994AB2-040_E
Adder
8.487.208
957481AF2-042 C
50/50
79.94679.946
961672AG1-007 E
Adder
0.71529411764705890.608
924322AB2-079 E O1
Adder
1.77764705882352941.511
943902AF1-058 E
Adder
1.65647058823529411.408
939192AE1-149 E
Adder
8.424705882352947.161
939312AE1-162 E
Adder
1.79058823529411781.522
934065AD1-033 E
50/50
7.0817.081
937226AE2-253 E
50/50
8.2398.239
934501AD1-074 C
Adder
46.5682352941176539.583
924517AB2-100 E2
Adder
4.042352941176473.436
957482AF2-042 E
50/50
53.29753.297
961671AG1-007 C
Adder
1.26235294117647071.073
934621AD1-088 C
Adder
13.31176470588235211.315
935172AD1-152 E
Adder
7.6094117647058826.468
3151101ELIZAR3
50/50
4.5194.519
316315AB2-025 C
50/50
0.5820.582
946282AF1-292 E
Adder
1.4270588235294121.213
944012AF1-069 E
50/50
8.6848.684
957861AF2-080 C
Adder
10.3094117647058838.763
917512Z2-088 E OP1
Adder
6.5941176470588245.605
316349AD2-085 C
Adder
4.5341176470588243.854
935112AD1-144 E
Adder
1.2588235294117651.07
3151091ELIZAR2
50/50
4.3864.386
944582AF1-123 E
50/50
146.831146.831
944592AF1-124 E
50/50
147.363147.363
923832AB2-022 E
Adder
1.74000000000000021.479
938772AE1-103 E
Adder
5.5529411764705884.72
916042Z1-036 E
Adder
39.78705882352941433.819
960082AF2-299 E
Adder
1.7247058823529411.466
946281AF1-292 C
Adder
2.14117647058823521.82
926071AC1-086 C
Adder
28.90117647058823624.566
3151051BRUNSWICKS1
50/50
28.75928.759
963042AG1-153 E
50/50
14.06814.068
927021AC1-189 C
Adder
11.3505882352941179.648
3151531CLOVER1
50/50
18.24618.246
964241AG1-285 C
Adder
17.3105882352941214.714
924152AB2-059 E OP
Adder
7.0658823529411776.006
962561AG1-105 C
Adder
11.6047058823529429.864
936666AD2-085 E
Adder
7.397647058823536.288
941591AE2-156 C
50/50
24.9124.91
3151081ELIZAR1
50/50
4.4634.463
316316AC1-027 C
50/50
0.4430.443
944591AF1-124 C
50/50
64.34964.349
944601AF1-125 C
50/50
63.13463.134
938771AE1-103 C
Adder
4.0211764705882363.418
3145413WATKINS
Adder
0.94941176470588240.807
960081AF2-299 C
Adder
2.58705882352941162.199
926072AC1-086 E
Adder
13.15411764705882411.181
944011AF1-069 C
50/50
22.35322.353
963041AG1-153 C
50/50
9.3799.379
957862AF2-080 E
Adder
4.5705882352941173.885
3151541CLOVER2
50/50
18.07618.076
936261AD2-033 C
Adder
15.9952941176470613.596
962562AG1-105 E
Adder
7.7364705882352946.576
926662AC1-147 E
Adder
1.84117647058823521.565
916192Z1-068 E
50/50
2.6352.635
957492AF2-043 E
Adder
1.97647058823529421.68
923852AB2-025 E
50/50
1.6571.657
939412AE1-173 E
50/50
99.43599.435
961942AG1-037 E
Adder
0.462352941176470630.393
961941AG1-037 C
Adder
0.69294117647058820.589
941032AE2-094 E
50/50
30.64130.641
941031AE2-094 C
50/50
68.41468.414
934332AD1-057 E
Adder
2.46235294117647062.093
934331AD1-057 C
Adder
4.72941176470588154.02
934321AD1-056 C
Adder
8.477647058823537.206
934322AD1-056 E
Adder
4.59882352941176453.909
927022AC1-189 E
Adder
5.6541176470588244.806
925595AC1-034 E
Adder
6.702352941176475.697
936262AD2-033 E
Adder
10.6635294117647069.064
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.3487.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
126.03126.03
CPLELTFEXP_CPLE->PJM
CLTF
15.41515.415
TVALTFEXP_TVA->PJM
CLTF
7.567.56
O66PJM->LTFIMP_O-066
CMTX_NF
30.16830.168
NYPJM->LTFIMP_NY
CLTF
2.22.2
LGEELTFEXP_LGEE->PJM
CLTF
1.4681.468
WECLTFEXP_WEC->PJM
CLTF
0.7690.769
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.99436.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.67827.678
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.7584.758
LAGNLTFEXP_LAGN->PJM
CLTF
9.6549.654
G-007PJM->LTFIMP_G-007
CMTX_NF
4.7394.739
SIGELTFEXP_SIGE->PJM
CLTF
0.2910.291

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T567_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.44 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4075.55
MW Contribution:24.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934576AD1-082 E
Adder
5.5282352941176474.699
916191Z1-068 C
50/50
0.0690.069
933292AC2-141 E
50/50
21.46921.469
316294AC1-161 C
50/50
8.2198.219
944602AF1-125 E
50/50
161.991161.991
3145506HICKORY
50/50
3.4483.448
943612AF1-032 E
Adder
1.42235294117647081.209
957871AF2-081 C
50/50
15.73315.733
940492AE2-034 E
Adder
4.663.961
934522AD1-076 E
Adder
9.3411764705882367.94
943172AE2-346 E
Adder
0.88823529411764710.755
918492AA1-063AE OP
Adder
5.9070588235294125.021
962571AG1-106 C
Adder
3.8952941176470593.311
917332KELFORD E
Adder
2.39058823529411772.032
925122AB2-169 E
Adder
8.4411764705882367.175
316274AC1-208 C
Adder
12.85294117647058910.925
917342Z2-044 E
Adder
0.84117647058823530.715
937482AD2-202 E
Adder
1.56941176470588251.334
3151311EDGECMA
Adder
21.6952941176470618.441
316084AB2-161 E
Adder
6.937647058823535.897
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
933982AD1-022 E
Adder
7.11294117647058856.046
940641AE2-051 C
50/50
31.61831.618
927146AC1-208 E
Adder
5.7070588235294124.851
934622AD1-088 E
Adder
6.6058823529411775.615
934612AD1-087 E
Adder
5.3611764705882364.557
3150921YORKTN3
Adder
148.4764705882353126.205
3145256KINGFORK
Adder
1.49058823529411751.267
925522AC1-027 E
50/50
1.9061.906
933291AC2-141 C
50/50
50.29350.293
926755AC1-161 E
50/50
21.46921.469
941102AE2-104 E
Adder
7.99294117647058756.794
957872AF2-081 E
50/50
6.7436.743
962572AG1-106 E
Adder
1.7035294117647061.448
926214AC1-099 E
Adder
1.72705882352941181.468
932632AC2-084 E
Adder
4.623.927
964242AG1-285 E
Adder
11.85176470588235310.074
924162AB2-060 E OP
Adder
5.8058823529411764.935
964792AG1-342 E
Adder
3.1588235294117652.685
943461AF1-017 C
Adder
1.89411764705882371.61
932596AC2-079 E
Adder
13.2447058823529411.258
316311AC2-079 C
Adder
8.117647058823536.9
938532AE1-072 E
50/50
14.39614.396
3146326AYDLETT TAP
50/50
2.1292.129
917122Z2-027 E
Adder
2.08705882352941161.774
920692AA2-178 E
Adder
6.2129411764705885.281
966622AG1-532 E
Adder
1.3352941176470591.135
922923AB1-081 E OP
Adder
5.2094117647058834.428
932046AC2-012 E
50/50
20.31420.314
958161AF2-110 C
Adder
2.0517647058823531.744
316017AA1-139 ULT1
50/50
1.7031.703
938531AE1-072 C
50/50
27.61527.615
3145393UNCAMP
Adder
9.017647058823537.665
933981AD1-022 C
Adder
13.06588235294117711.106
900672V4-068 E
Adder
0.52235294117647060.444
3152411Z1-086 GT1
50/50
18.63118.631
924302AB2-077 E O1
Adder
1.82588235294117651.552
942341AE2-247 C
Adder
2.09411764705882361.78
943462AF1-017 E
Adder
3.09058823529411742.627
958162AF2-110 E
Adder
3.2635294117647062.774
316388AE2-253 GEN
50/50
3.0993.099
919153AA1-139 E2
50/50
6.4346.434
934512AD1-075 E
Adder
6.422352941176475.459
934502AD1-074 E
Adder
25.6882352941176521.835
924516AB2-100 E1
Adder
4.1635294117647063.539
918512AA1-065 E OP
Adder
8.1494117647058816.927
940642AE2-051 E
50/50
21.07921.079
966621AG1-532 C
Adder
2.00352941176470621.703
918532AA1-067 E
Adder
1.02588235294117650.872
924022AB2-043 E O1
Adder
7.0847058823529416.022
3147223TWITTYS
Adder
1.241.054
959312AF2-222 E
Adder
14.30117647058823712.156
3143316POE
Adder
1.61411764705882371.372
913392Y1-086 E
Adder
3.42705882352941152.913
939411AE1-173 C
50/50
160.299160.299
3137643SOCKMAN
Adder
1.02117647058823540.868
3151031BRUNSWICKG2
50/50
14.47314.473
919710AA2-057 E
Adder
5.6082352941176474.767
942342AE2-247 E
Adder
2.89058823529411772.457
919152AA1-139 E1
50/50
6.4346.434
316018AA1-139 ULT2
50/50
1.7031.703
961611AG1-000B C
Adder
5.04.25
3152331SURRY 2
50/50
39.09439.094
316375AC2-012 C
50/50
2.0942.094
940541AE2-040 C
Adder
4.16470588235294153.54
940481AE2-033 C
Adder
23.45176470588235419.934
940482AE2-033 E
Adder
15.81058823529411813.439
923263AB1-132 E OP
Adder
8.7635294117647067.449
3152441Z1-086 ST
50/50
32.43232.432
3152431Z1-086 GT3
50/50
18.62318.623
3152421Z1-086 GT2
50/50
18.62318.623
925612AC1-036 E
Adder
1.11882352941176480.951
924312AB2-078 E O1
Adder
1.82588235294117651.552
926274AC1-105 E
Adder
3.5647058823529413.03
901082W1-029 E
Adder
49.1811764705882441.804
926206AC1-098 E
Adder
5.2270588235294114.443
3151041BRUNSWICKG3
50/50
14.47314.473
3151021BRUNSWICKG1
50/50
14.47314.473
964791AG1-342 C
Adder
4.737647058823534.027
316185AD1-033 C
50/50
1.9451.945
944581AF1-123 C
50/50
71.8771.87
941101AE2-104 C
Adder
5.0270588235294114.273
316141AB2-099 E
Adder
0.36941176470588240.314
316088AB2-174 E
Adder
9.3282352941176477.929
923994AB2-040_E
Adder
8.8082352941176477.487
957481AF2-042 C
Adder
82.8776470588235370.446
961672AG1-007 E
Adder
0.7517647058823530.639
924322AB2-079 E O1
Adder
1.82588235294117651.552
943902AF1-058 E
Adder
1.70235294117647061.447
920042AA2-088 E OP
Adder
15.5623529411764713.228
934521AD1-076 C
Adder
18.32705882352941315.578
934511AD1-075 C
Adder
12.6152941176470610.723
3145723EMPORIA
Adder
0.61647058823529410.524
923573AB1-173 E OP
Adder
4.6976470588235293.993
919692AA2-053 E OP
Adder
6.08588235294117655.173
925785AC1-054 E
Adder
4.8317647058823534.107
316263AC1-034 C
Adder
9.287.888
959311AF2-222 C
Adder
21.34470588235294418.143
939312AE1-162 E
Adder
1.93058823529411771.641
3150991CHESPKB
50/50
1.121.12
934065AD1-033 E
50/50
7.9347.934
937226AE2-253 E
50/50
9.2149.214
934501AD1-074 C
Adder
50.4623529411764742.893
924517AB2-100 E2
Adder
4.1635294117647063.539
957482AF2-042 E
Adder
55.2517647058823546.964
961671AG1-007 C
Adder
1.32588235294117651.127
934621AD1-088 C
Adder
13.7211.662
935172AD1-152 E
Adder
7.8611764705882366.682
936666AD2-085 E
Adder
7.8811764705882356.699
941591AE2-156 C
50/50
27.78727.787
3151081ELIZAR1
50/50
4.9824.982
316316AC1-027 C
50/50
0.4950.495
944591AF1-124 C
50/50
72.12672.126
944601AF1-125 C
50/50
70.76370.763
938771AE1-103 C
Adder
4.3517647058823533.699
3145413WATKINS
Adder
1.02235294117647070.869
960081AF2-299 C
Adder
2.6705882352941182.27
926072AC1-086 E
Adder
13.70588235294117811.65
944011AF1-069 C
50/50
23.40523.405
963041AG1-153 C
50/50
9.8059.805
957862AF2-080 E
Adder
4.8211764705882354.098
962562AG1-105 E
Adder
7.9482352941176486.756
3151101ELIZAR3
50/50
5.0455.045
946282AF1-292 E
Adder
1.47411764705882351.253
944012AF1-069 E
50/50
9.0929.092
957861AF2-080 C
Adder
10.8752941176470599.244
917512Z2-088 E OP1
Adder
6.9388235294117645.898
316349AD2-085 C
Adder
4.8305882352941174.106
935112AD1-144 E
Adder
1.3835294117647061.176
3151091ELIZAR2
50/50
4.8964.896
944582AF1-123 E
50/50
164.574164.574
944592AF1-124 E
50/50
165.171165.171
923832AB2-022 E
Adder
1.93411764705882351.644
938772AE1-103 E
Adder
6.0094117647058825.108
916042Z1-036 E
Adder
43.71058823529412537.154
960082AF2-299 E
Adder
1.78117647058823541.514
946281AF1-292 C
Adder
2.21058823529411751.879
926071AC1-086 C
Adder
30.1129411764705925.596
3151051BRUNSWICKS1
50/50
30.06830.068
963042AG1-153 E
50/50
14.70814.708
927021AC1-189 C
Adder
11.97411764705882410.178
964241AG1-285 C
Adder
17.77647058823529515.11
924152AB2-059 E OP
Adder
7.3811764705882366.274
962561AG1-105 C
Adder
11.92235294117647210.134
926662AC1-147 E
Adder
2.05411764705882361.746
916192Z1-068 E
50/50
2.9452.945
957492AF2-043 E
Adder
2.18823529411764731.86
923852AB2-025 E
Adder
1.6847058823529411.432
939412AE1-173 E
50/50
106.866106.866
961942AG1-037 E
Adder
0.49294117647058820.419
961941AG1-037 C
Adder
0.740.629
941032AE2-094 E
50/50
32.08232.082
941031AE2-094 C
50/50
71.63171.631
934332AD1-057 E
Adder
2.56941176470588272.184
934331AD1-057 C
Adder
4.9341176470588244.194
934321AD1-056 C
Adder
8.844705882352947.518
934322AD1-056 E
Adder
4.797647058823534.078
927022AC1-189 E
Adder
5.9647058823529415.07
925595AC1-034 E
Adder
7.0011764705882355.951
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.5637.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
128.067128.067
CPLELTFEXP_CPLE->PJM
CLTF
15.87115.871
TVALTFEXP_TVA->PJM
CLTF
7.2977.297
O66PJM->LTFIMP_O-066
CMTX_NF
27.12727.127
NYPJM->LTFIMP_NY
CLTF
2.0052.005
LGEELTFEXP_LGEE->PJM
CLTF
1.2871.287
WECLTFEXP_WEC->PJM
CLTF
0.6770.677
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.34332.343
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.24226.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.3444.344
LAGNLTFEXP_LAGN->PJM
CLTF
9.3599.359
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2584.258
SIGELTFEXP_SIGE->PJM
CLTF
0.2610.261

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.39 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1062.25
MW Contribution:3.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.68 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1086.53
MW Contribution:3.61
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
940641AE2-051 C
80/20
11.53811.538
316336AC2-165 C
Adder
-10.758823529411764-9.145
934611AD1-087 C
80/20
0.6230.623
3151611KERR 4
80/20
0.4940.494
916191Z1-068 C
80/20
0.0180.018
316294AC1-161 C
80/20
2.1972.197
957871AF2-081 C
80/20
4.1964.196
962571AG1-106 C
80/20
1.1691.169
932631AC2-084 C
80/20
0.4330.433
316274AC1-208 C
80/20
3.8963.896
3151311EDGECMA
Adder
6.8129411764705895.791
3151601KERR 3
80/20
0.4940.494
3151581KERR 1
80/20
0.1760.176
941011AE2-092 C
Adder
-4.452941176470588-3.785
942341AE2-247 C
Adder
0.50235294117647060.427
316246AF1-032 C
80/20
0.1150.115
316388AE2-253 GEN
80/20
0.8260.826
966621AG1-532 C
80/20
0.6010.601
936161AD2-022 C
Adder
3.0882352941176472.625
933291AC2-141 C
80/20
13.44213.442
316305AF2-043 C
80/20
0.1410.141
316087AB2-174 C
80/20
0.5050.505
3151591KERR 2
80/20
0.4940.494
3156116Z1-036WIND
80/20
0.2750.275
939411AE1-173 C
80/20
55.12655.126
3152921DOMTR78
80/20
0.5790.579
316140AB2-099 C
80/20
0.0410.041
3137643SOCKMAN
80/20
0.3050.305
316212AC1-099 C
80/20
0.1360.136
3151031BRUNSWICKG2
80/20
5.4215.421
937481AD2-202 C
80/20
0.1810.181
3151641KERR 7
80/20
0.4940.494
958161AF2-110 C
Adder
0.53058823529411770.451
316017AA1-139 ULT1
80/20
0.4540.454
938531AE1-072 C
80/20
7.3717.371
315614AA2-178 C
80/20
0.6580.658
933981AD1-022 C
80/20
3.6993.699
3151261ROARAP2
80/20
0.5930.593
3147043LAWRENC
80/20
0.130.13
3152411Z1-086 GT1
80/20
7.0067.006
3151621KERR 5
80/20
0.4940.494
943461AF1-017 C
Adder
0.454117647058823570.386
316311AC2-079 C
Adder
1.9682352941176471.673
3156056W1-029WIND
80/20
0.3220.322
316375AC2-012 C
80/20
0.5420.542
313526AB2-022 C
80/20
0.1570.157
940541AE2-040 C
80/20
1.2541.254
940481AE2-033 C
80/20
7.0627.062
3151411GASTONB
80/20
1.3141.314
316181AB2-040 GEN
80/20
0.5450.545
316174AB2-169_C
80/20
0.4470.447
3156063AA2-053SOLA
80/20
0.6450.645
316365AB2-100 C1
80/20
0.4150.415
316318V4-068 C
80/20
0.0340.034
316210AC1-098 C
80/20
0.4070.407
3151041BRUNSWICKG3
80/20
5.4215.421
3151021BRUNSWICKG1
80/20
5.4215.421
935171AD1-152 C
80/20
0.6380.638
964791AG1-342 C
Adder
1.48470588235294131.262
3151281ROARAP4
80/20
0.5610.561
3152441Z1-086 ST
80/20
12.19612.196
3152431Z1-086 GT3
80/20
7.0037.003
3152421Z1-086 GT2
80/20
7.0037.003
938821AE1-108 C
Adder
-4.716470588235294-4.009
3150981CHESPKA
80/20
0.1750.175
316185AD1-033 C
80/20
0.5160.516
944581AF1-123 C
80/20
19.1219.12
941101AE2-104 C
Adder
1.31.105
316320Y1-086 C
80/20
0.0920.092
3156083AA2-088SOLA
80/20
0.4390.439
313506AB1-173 C OP
80/20
0.4830.483
316036AC1-147 C
80/20
0.1480.148
316018AA1-139 ULT2
80/20
0.4540.454
934521AD1-076 C
80/20
5.1645.164
934511AD1-075 C
80/20
3.5543.554
316011AB1-132 C OP
80/20
1.0031.003
316263AC1-034 C
Adder
2.91411764705882352.477
959311AF2-222 C
Adder
5.57411764705882454.738
3151361ROSEMG1
80/20
0.8780.878
957481AF2-042 C
80/20
28.34128.341
3150991CHESPKB
80/20
0.290.29
316321Z2-027 C
80/20
0.1520.152
940491AE2-034 C
80/20
0.4850.485
934501AD1-074 C
80/20
14.21814.218
3156021HOLLOMANSOL
80/20
0.7790.779
3156073AA1-063SOLA
80/20
0.5950.595
3151371ROSEMS1
80/20
0.5440.544
961671AG1-007 C
Adder
0.410588235294117640.349
934621AD1-088 C
80/20
4.3624.362
3151101ELIZAR3
80/20
1.3121.312
316315AB2-025 C
80/20
0.1780.178
316129AC1-054 C
80/20
0.5240.524
957861AF2-080 C
Adder
3.3247058823529412.826
316349AD2-085 C
Adder
1.15882352941176480.985
3151091ELIZAR2
80/20
1.2731.273
316023AB2-100 C2
80/20
0.4150.415
946281AF1-292 C
80/20
0.6630.663
926071AC1-086 C
80/20
9.0389.038
316317KELFORD C
80/20
0.1530.153
3151051BRUNSWICKS1
80/20
11.26211.262
927021AC1-189 C
Adder
3.66117647058823573.112
3151531CLOVER1
80/20
6.3346.334
964241AG1-285 C
80/20
5.3655.365
962561AG1-105 C
Adder
3.70941176470588243.153
941591AE2-156 C
80/20
7.2027.202
3151081ELIZAR1
80/20
1.2951.295
316316AC1-027 C
80/20
0.130.13
944591AF1-124 C
80/20
19.18819.188
944601AF1-125 C
80/20
18.82618.826
938771AE1-103 C
Adder
1.16941176470588240.994
960081AF2-299 C
80/20
0.8010.801
944011AF1-069 C
80/20
8.8768.876
963041AG1-153 C
80/20
3.6733.673
3151541CLOVER2
80/20
6.2756.275
3151631KERR 6
80/20
0.4940.494
936261AD2-033 C
Adder
4.2364705882352943.601
936171AD2-023 C
Adder
1.80117647058823521.531
943171AE2-346 C
80/20
0.0950.095
961941AG1-037 C
80/20
0.2130.213
3151391GASTONA
80/20
1.3141.314
3151381ROSEMG2
80/20
0.4110.411
941031AE2-094 C
80/20
27.16527.165
934331AD1-057 C
Adder
1.52117647058823541.293
934321AD1-056 C
Adder
2.72588235294117662.317
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
NYPJM->LTFIMP_NY
CLTF
0.5140.514
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
WECLTFEXP_WEC->PJM
CLTF
0.2390.239
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.98 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4293.98
MW Contribution:22.88
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316084AB2-161 E
Adder
8.717647058823537.41
3145946PLYMOUTH TP
Adder
0.50.425
933982AD1-022 E
Adder
7.3576470588235296.254
940641AE2-051 C
50/50
29.19229.192
316336AC2-165 C
Adder
14.85411764705882312.626
934622AD1-088 E
Adder
6.9164705882352945.879
934612AD1-087 E
Adder
5.42823529411764754.614
3150651CHESTF6
Adder
27.96823529411764823.773
946262AF1-291 E
Adder
2.17647058823529441.85
934576AD1-082 E
Adder
6.9458823529411775.904
916191Z1-068 C
50/50
0.070.07
933292AC2-141 E
50/50
20.7620.76
316294AC1-161 C
50/50
7.9477.947
944602AF1-125 E
50/50
163.5163.5
3145506HICKORY
50/50
3.4833.483
943612AF1-032 E
Adder
1.4682352941176471.248
957871AF2-081 C
Adder
15.93294117647058713.543
940492AE2-034 E
Adder
4.84.08
934522AD1-076 E
Adder
9.6458823529411778.199
918492AA1-063AE OP
Adder
6.2388235294117655.303
962571AG1-106 C
Adder
3.9470588235294123.355
937482AD2-202 E
Adder
1.58941176470588231.351
935162AD1-151 E
Adder
16.1505882352941213.728
316233AE1-074 C
50/50
4.1784.178
943461AF1-017 C
Adder
2.1352941176470591.815
932596AC2-079 E
Adder
14.80823529411764712.587
316311AC2-079 C
Adder
9.0764705882352947.715
938532AE1-072 E
Adder
14.59294117647058912.404
3146326AYDLETT TAP
Adder
2.161.836
917122Z2-027 E
Adder
2.12941176470588231.81
920692AA2-178 E
Adder
6.45.44
966622AG1-532 E
Adder
1.43647058823529421.221
942341AE2-247 C
Adder
2.362.006
943462AF1-017 E
Adder
3.48470588235294132.962
958162AF2-110 E
Adder
3.4494117647058822.932
919153AA1-139 E2
Adder
6.5152941176470595.538
934512AD1-075 E
Adder
6.6317647058823535.637
934502AD1-074 E
Adder
26.5247058823529422.546
924516AB2-100 E1
Adder
4.4917647058823533.818
940642AE2-051 E
50/50
19.46119.461
966621AG1-532 C
Adder
2.15411764705882371.831
938552AE1-074 E
50/50
2.1052.105
3150921YORKTN3
Adder
175.7670588235294149.402
3145256KINGFORK
Adder
1.5952941176470591.356
925522AC1-027 E
50/50
1.9431.943
933291AC2-141 C
50/50
48.63248.632
926755AC1-161 E
50/50
20.7620.76
941102AE2-104 E
Adder
8.4494117647058827.182
957872AF2-081 E
Adder
6.8282352941176485.804
938562AE1-075 E
Adder
1.64117647058823551.395
940432AE2-027 E
Adder
13.04588235294117711.089
934012AD1-025 E
Adder
15.07294117647058812.812
913392Y1-086 E
Adder
3.48941176470588272.966
939411AE1-173 C
50/50
151.032151.032
933502AC2-165 E
Adder
11.189.503
3151031BRUNSWICKG2
50/50
13.50613.506
3150731STONECA
Adder
10.1976470588235298.668
935161AD1-151 C
Adder
24.22470588235294320.591
932046AC2-012 E
50/50
20.89320.893
958161AF2-110 C
Adder
2.16823529411764731.843
938531AE1-072 C
Adder
27.99411764705882523.795
3145393UNCAMP
Adder
9.5200000000000018.092
933981AD1-022 C
Adder
13.5152941176470611.488
900672V4-068 E
Adder
0.54941176470588240.467
3152411Z1-086 GT1
50/50
17.32817.328
939191AE1-149 C
Adder
16.88000000000000314.348
3143316POE
50/50
2.1752.175
901082W1-029 E
Adder
50.41764705882352642.855
3151041BRUNSWICKG3
50/50
13.50613.506
3151021BRUNSWICKG1
50/50
13.50613.506
961611AG1-000B C
Adder
24.2858823529411820.643
316375AC2-012 C
50/50
2.1542.154
940541AE2-040 C
50/50
4.5764.576
940481AE2-033 C
50/50
25.70925.709
940482AE2-033 E
50/50
17.33217.332
923263AB1-132 E OP
Adder
9.3023529411764717.907
3152441Z1-086 ST
50/50
30.16330.163
3152431Z1-086 GT3
50/50
17.32117.321
3152421Z1-086 GT2
50/50
17.32117.321
944641AF1-129 C
Adder
153.60588235294117130.565
316240AF1-291 C
Adder
3.2635294117647062.774
924814AB2-134 E
Adder
19.07058823529411716.21
942342AE2-247 E
Adder
3.262.771
919152AA1-139 E1
Adder
6.5152941176470595.538
920042AA2-088 E OP
Adder
16.40941176470588313.948
934521AD1-076 C
Adder
18.92352941176470816.085
934511AD1-075 C
Adder
13.02705882352941211.073
3145723EMPORIA
Adder
0.66117647058823540.562
923573AB1-173 E OP
Adder
5.0141176470588234.262
940431AE2-027 C
Adder
19.56823529411764516.633
942002AE2-212 E
Adder
2.23058823529411751.896
316185AD1-033 C
50/50
1.9651.965
944581AF1-123 C
50/50
72.53972.539
941101AE2-104 C
Adder
5.3141176470588244.517
316088AB2-174 E
Adder
9.988.483
923994AB2-040_E
Adder
9.4011764705882357.991
957481AF2-042 C
Adder
82.7976470588235370.378
942001AE2-212 C
Adder
3.34588235294117632.844
939192AE1-149 E
Adder
11.2529411764705879.565
939312AE1-162 E
Adder
2.22705882352941181.893
934065AD1-033 E
50/50
8.0198.019
937226AE2-253 E
Adder
9.322352941176477.924
934501AD1-074 C
Adder
52.1070588235294144.291
958502AF2-144 E
Adder
1.89058823529411771.607
924517AB2-100 E2
Adder
4.4917647058823533.818
957482AF2-042 E
Adder
55.1988235294117646.919
934621AD1-088 C
Adder
14.36470588235294312.21
925332AB2-190 E
Adder
12.07529411764705810.264
927226AC1-216 E
Adder
11.6423529411764739.896
936666AD2-085 E
Adder
8.8858823529411777.553
3151101ELIZAR3
50/50
5.1725.172
316315AB2-025 C
50/50
0.650.65
946282AF1-292 E
Adder
1.58588235294117651.348
944012AF1-069 E
50/50
8.3958.395
316349AD2-085 C
Adder
5.4458823529411764.629
935112AD1-144 E
Adder
1.48117647058823531.259
3151091ELIZAR2
50/50
5.0195.019
944582AF1-123 E
50/50
166.107166.107
944592AF1-124 E
50/50
166.709166.709
923832AB2-022 E
Adder
1.96941176470588241.674
938772AE1-103 E
Adder
6.3458823529411775.394
916042Z1-036 E
Adder
44.8811764705882438.149
960082AF2-299 E
Adder
1.91529411764705881.628
946281AF1-292 C
Adder
2.37764705882352922.021
926071AC1-086 C
Adder
31.96588235294117627.171
3151051BRUNSWICKS1
50/50
28.05828.058
963042AG1-153 E
50/50
13.72513.725
941591AE2-156 C
50/50
28.55328.553
3151081ELIZAR1
50/50
5.1085.108
316316AC1-027 C
50/50
0.5040.504
944591AF1-124 C
50/50
72.79772.797
944601AF1-125 C
50/50
71.42271.422
938771AE1-103 C
Adder
4.5952941176470593.906
3145413WATKINS
Adder
1.07882352941176470.917
960081AF2-299 C
Adder
2.87294117647058832.442
926072AC1-086 E
Adder
14.54823529411764812.366
944011AF1-069 C
50/50
21.6121.61
963041AG1-153 C
50/50
9.159.15
3150841SPRUNCB
Adder
14.05529411764705811.947
3150831SPRUNCA
Adder
14.05529411764705811.947
926662AC1-147 E
Adder
2.1117647058823531.795
916192Z1-068 E
50/50
3.0013.001
957492AF2-043 E
Adder
2.25882352941176471.92
923852AB2-025 E
50/50
1.8511.851
939412AE1-173 E
50/50
100.688100.688
923862AB2-026 E
Adder
1.9247058823529411.636
941032AE2-094 E
50/50
29.62229.622
941031AE2-094 C
50/50
66.13866.138
316303AF2-085
50/50
6.8996.899
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6737.673
CBM South 2LTFEXP_CBM-S2->PJM
CBM
132.286132.286
CPLELTFEXP_CPLE->PJM
CLTF
16.09616.096
TVALTFEXP_TVA->PJM
CLTF
8.1488.148
O66PJM->LTFIMP_O-066
CMTX_NF
37.46537.465
NYPJM->LTFIMP_NY
CLTF
2.7212.721
LGEELTFEXP_LGEE->PJM
CLTF
1.6421.642
WECLTFEXP_WEC->PJM
CLTF
0.8540.854
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.00241.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.98729.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.2215.221
LAGNLTFEXP_LAGN->PJM
CLTF
10.36610.366
G-007PJM->LTFIMP_G-007
CMTX_NF
5.8875.887
SIGELTFEXP_SIGE->PJM
CLTF
0.3220.322

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.85 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4130.98
MW Contribution:22.74
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.17 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4734.56
MW Contribution:23.03
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
939191AE1-149 C
Adder
16.1694117647058813.744
3143316POE
Adder
2.0705882352941181.76
946262AF1-291 E
Adder
2.00235294117647071.702
934576AD1-082 E
Adder
6.7411764705882365.73
916191Z1-068 C
50/50
0.0710.071
933292AC2-141 E
50/50
21.18321.183
316294AC1-161 C
50/50
8.1098.109
944602AF1-125 E
50/50
165.126165.126
3145506HICKORY
50/50
3.5173.517
943612AF1-032 E
Adder
1.4764705882352941.255
957871AF2-081 C
Adder
16.07411764705882413.663
940492AE2-034 E
Adder
4.8023529411764714.082
934522AD1-076 E
Adder
9.6317647058823528.187
943172AE2-346 E
Adder
0.92117647058823540.783
918492AA1-063AE OP
Adder
6.1705882352941185.245
962571AG1-106 C
Adder
4.07176470588235253.461
917332KELFORD E
Adder
2.4741176470588242.103
925122AB2-169 E
Adder
8.6764705882352937.375
937482AD2-202 E
Adder
1.5682352941176471.333
316084AB2-161 E
Adder
8.467.191
3145946PLYMOUTH TP
Adder
0.50.425
933982AD1-022 E
Adder
7.346.239
940641AE2-051 C
50/50
29.19929.199
934622AD1-088 E
Adder
6.8105882352941185.789
934612AD1-087 E
Adder
5.3588235294117644.555
944641AF1-129 C
Adder
128.6564705882353109.358
316240AF1-291 C
Adder
3.0047058823529412.554
924814AB2-134 E
Adder
18.37647058823529315.62
942342AE2-247 E
Adder
3.22235294117647042.739
938552AE1-074 E
50/50
1.9361.936
316160AE1-175 E
Adder
1.67529411764705881.424
3150921YORKTN3
Adder
176.88117647058823150.349
3145256KINGFORK
Adder
1.61.36
925522AC1-027 E
50/50
1.961.96
933291AC2-141 C
50/50
49.62549.625
926755AC1-161 E
50/50
21.18321.183
941102AE2-104 E
Adder
8.4505882352941187.183
957872AF2-081 E
Adder
6.88823529411764755.855
938562AE1-075 E
Adder
1.53176470588235311.302
962572AG1-106 E
Adder
1.78117647058823541.514
964242AG1-285 E
Adder
12.5610.676
925332AB2-190 E
Adder
11.5164705882352939.789
927226AC1-216 E
Adder
11.2188235294117659.536
935162AD1-151 E
Adder
15.4776470588235313.156
316233AE1-074 C
50/50
3.8433.843
943461AF1-017 C
Adder
2.1105882352941181.794
932596AC2-079 E
Adder
14.6612.461
316311AC2-079 C
Adder
8.9858823529411777.638
938532AE1-072 E
Adder
14.7176470588235312.51
3146326AYDLETT TAP
Adder
2.17764705882352951.851
917122Z2-027 E
Adder
2.1435294117647061.822
920692AA2-178 E
Adder
6.4035294117647065.443
966622AG1-532 E
Adder
1.41058823529411771.199
3150731STONECA
Adder
9.5694117647058838.134
935161AD1-151 C
Adder
23.2152941176470619.733
932046AC2-012 E
50/50
21.04921.049
958161AF2-110 C
Adder
2.16941176470588241.844
938531AE1-072 C
Adder
28.2329411764705923.998
3145393UNCAMP
Adder
9.4858823529411778.063
933981AD1-022 C
Adder
13.48352941176470711.461
900672V4-068 E
Adder
0.54588235294117650.464
3152411Z1-086 GT1
50/50
17.23317.233
942341AE2-247 C
Adder
2.33294117647058831.983
943462AF1-017 E
Adder
3.44470588235294132.928
958162AF2-110 E
Adder
3.45058823529411772.933
316388AE2-253 GEN
50/50
3.1643.164
919153AA1-139 E2
Adder
6.57294117647058855.587
934512AD1-075 E
Adder
6.622352941176475.629
934502AD1-074 E
Adder
26.48705882352941322.514
924516AB2-100 E1
Adder
4.4035294117647063.743
918512AA1-065 E OP
Adder
8.4305882352941197.166
940642AE2-051 E
50/50
19.46619.466
966621AG1-532 C
Adder
2.11529411764705881.798
901082W1-029 E
Adder
50.6800000000000143.078
3151041BRUNSWICKG3
50/50
13.42713.427
3151021BRUNSWICKG1
50/50
13.42713.427
940432AE2-027 E
Adder
12.12235294117647110.304
934012AD1-025 E
Adder
14.52470588235294212.346
913392Y1-086 E
Adder
3.51411764705882362.987
939411AE1-173 C
50/50
151.38151.38
3137643SOCKMAN
Adder
1.06823529411764720.908
3151031BRUNSWICKG2
50/50
13.42713.427
919152AA1-139 E1
Adder
6.57294117647058855.587
920042AA2-088 E OP
Adder
16.29647058823529413.852
934521AD1-076 C
Adder
18.8976470588235316.063
934511AD1-075 C
Adder
13.00823529411764811.057
3145723EMPORIA
Adder
0.65058823529411770.553
923573AB1-173 E OP
Adder
4.9341176470588244.194
919692AA2-053 E OP
Adder
6.3423529411764715.391
961611AG1-000B C
Adder
23.7620.196
316375AC2-012 C
50/50
2.172.17
940541AE2-040 C
Adder
4.4623529411764713.793
940481AE2-033 C
Adder
25.0882352941176521.325
940482AE2-033 E
Adder
16.9129411764705914.376
923263AB1-132 E OP
Adder
9.162352941176477.788
3152441Z1-086 ST
50/50
29.99929.999
3152431Z1-086 GT3
50/50
17.22617.226
3152421Z1-086 GT2
50/50
17.22617.226
940431AE2-027 C
Adder
18.18352941176470615.456
942002AE2-212 E
Adder
2.0811764705882351.769
316185AD1-033 C
50/50
1.9851.985
944581AF1-123 C
50/50
73.26173.261
941101AE2-104 C
Adder
5.3152941176470594.518
316141AB2-099 E
Adder
0.38352941176470590.326
316088AB2-174 E
Adder
9.8129411764705888.341
923994AB2-040_E
Adder
9.2505882352941197.863
957481AF2-042 C
Adder
81.8317647058823669.557
942001AE2-212 C
Adder
3.1211764705882352.653
939192AE1-149 E
Adder
10.7800000000000019.163
939312AE1-162 E
Adder
2.21058823529411751.879
934065AD1-033 E
50/50
8.0978.097
937226AE2-253 E
50/50
9.4079.407
934501AD1-074 C
Adder
52.03294117647059444.228
958502AF2-144 E
Adder
1.76470588235294111.5
924517AB2-100 E2
Adder
4.4035294117647063.743
957482AF2-042 E
Adder
54.5552941176470646.372
934621AD1-088 C
Adder
14.14588235294117512.024
316349AD2-085 C
Adder
5.3835294117647054.576
935112AD1-144 E
Adder
1.48470588235294131.262
3151091ELIZAR2
50/50
5.0595.059
944582AF1-123 E
50/50
167.759167.759
944592AF1-124 E
50/50
168.367168.367
923832AB2-022 E
Adder
1.98352941176470581.686
938772AE1-103 E
Adder
6.3270588235294125.378
916042Z1-036 E
Adder
45.0211764705882438.268
960082AF2-299 E
Adder
1.88000000000000011.598
946281AF1-292 C
Adder
2.33411764705882341.984
926071AC1-086 C
Adder
31.48235294117647226.76
3151051BRUNSWICKS1
50/50
27.89527.895
963042AG1-153 E
50/50
13.64513.645
964241AG1-285 C
Adder
18.8416.014
962962AG1-145 E
Adder
2.0305882352941181.726
936666AD2-085 E
Adder
8.7835294117647067.466
941591AE2-156 C
50/50
28.7728.77
3151081ELIZAR1
50/50
5.1485.148
316316AC1-027 C
50/50
0.5090.509
944591AF1-124 C
50/50
73.52173.521
944601AF1-125 C
50/50
72.13372.133
938771AE1-103 C
Adder
4.582352941176473.895
3145413WATKINS
Adder
1.07411764705882360.913
960081AF2-299 C
Adder
2.822.397
926072AC1-086 E
Adder
14.32823529411764712.179
944011AF1-069 C
50/50
21.50921.509
963041AG1-153 C
50/50
9.0979.097
3151101ELIZAR3
50/50
5.2135.213
946282AF1-292 E
Adder
1.5564705882352941.323
944012AF1-069 E
50/50
8.3568.356
3150841SPRUNCB
Adder
12.67882352941176410.777
3150831SPRUNCA
Adder
12.67882352941176410.777
926662AC1-147 E
Adder
2.12823529411764721.809
916192Z1-068 E
50/50
3.0273.027
957492AF2-043 E
Adder
2.2717647058823531.931
923852AB2-025 E
Adder
1.80470588235294121.534
939412AE1-173 E
50/50
100.92100.92
923862AB2-026 E
Adder
1.7964705882352941.527
961942AG1-037 E
Adder
0.51176470588235290.435
961941AG1-037 C
Adder
0.76823529411764710.653
941032AE2-094 E
50/50
29.48329.483
941031AE2-094 C
50/50
65.82865.828
316303AF2-085
50/50
6.4766.476
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.547.54
CBM South 2LTFEXP_CBM-S2->PJM
CBM
129.173129.173
CPLELTFEXP_CPLE->PJM
CLTF
15.81915.819
TVALTFEXP_TVA->PJM
CLTF
7.767.76
O66PJM->LTFIMP_O-066
CMTX_NF
34.77734.777
NYPJM->LTFIMP_NY
CLTF
2.5392.539
LGEELTFEXP_LGEE->PJM
CLTF
1.4991.499
WECLTFEXP_WEC->PJM
CLTF
0.780.78
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.34537.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.31928.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8474.847
LAGNLTFEXP_LAGN->PJM
CLTF
9.8929.892
G-007PJM->LTFIMP_G-007
CMTX_NF
5.4635.463
SIGELTFEXP_SIGE->PJM
CLTF
0.2970.297

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.96 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4056.76
MW Contribution:21.88
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
Adder
25.5882352941176521.75
946262AF1-291 E
Adder
1.99529411764705891.696
934576AD1-082 E
Adder
6.4764705882352945.505
916191Z1-068 C
50/50
0.0660.066
933292AC2-141 E
50/50
19.5219.52
316294AC1-161 C
50/50
7.4737.473
944602AF1-125 E
50/50
153.669153.669
3145506HICKORY
50/50
3.2743.274
943612AF1-032 E
Adder
1.38000000000000011.173
957871AF2-081 C
Adder
14.97647058823529412.73
316084AB2-161 E
Adder
8.1282352941176486.909
3145946PLYMOUTH TP
Adder
0.47058823529411770.4
933982AD1-022 E
Adder
6.9329411764705885.893
940641AE2-051 C
50/50
27.86227.862
316336AC2-165 C
Adder
14.02588235294117811.922
934622AD1-088 E
Adder
6.5941176470588245.605
934612AD1-087 E
Adder
5.17764705882352954.401
935162AD1-151 E
Adder
14.89411764705882412.66
316233AE1-074 C
50/50
3.8973.897
943461AF1-017 C
Adder
2.01.7
932596AC2-079 E
Adder
13.86941176470588211.789
316311AC2-079 C
Adder
8.5011764705882367.226
940492AE2-034 E
Adder
4.5188235294117653.841
934522AD1-076 E
Adder
9.0858823529411777.723
918492AA1-063AE OP
Adder
5.8905882352941185.007
962571AG1-106 C
Adder
3.90588235294117643.32
937482AD2-202 E
Adder
1.5152941176470591.288
938532AE1-072 E
Adder
13.7176470588235311.66
3146326AYDLETT TAP
Adder
2.02941176470588271.725
917122Z2-027 E
Adder
2.00235294117647071.702
920692AA2-178 E
Adder
6.0258823529411775.122
966622AG1-532 E
Adder
1.35764705882352941.154
942341AE2-247 C
Adder
2.21058823529411751.879
943462AF1-017 E
Adder
3.2623529411764712.773
958162AF2-110 E
Adder
3.2376470588235292.752
919153AA1-139 E2
Adder
6.1235294117647065.205
934512AD1-075 E
Adder
6.2470588235294125.31
934502AD1-074 E
Adder
24.98705882352941321.239
924516AB2-100 E1
Adder
4.2411764705882353.605
940642AE2-051 E
50/50
18.57518.575
966621AG1-532 C
Adder
2.03647058823529431.731
938552AE1-074 E
50/50
1.9631.963
3150921YORKTN3
Adder
163.19176470588235138.713
3145256KINGFORK
Adder
1.49529411764705871.271
925522AC1-027 E
50/50
1.8261.826
933291AC2-141 C
50/50
45.72845.728
926755AC1-161 E
50/50
19.5219.52
941102AE2-104 E
Adder
7.9317647058823536.742
957872AF2-081 E
Adder
6.4188235294117665.456
938562AE1-075 E
Adder
1.55058823529411781.318
962572AG1-106 E
Adder
1.7082352941176471.452
940432AE2-027 E
Adder
11.99411764705882410.195
934012AD1-025 E
Adder
13.92352941176470811.835
913392Y1-086 E
Adder
3.282.788
939411AE1-173 C
50/50
143.648143.648
933502AC2-165 E
Adder
10.5564705882352968.973
3137643SOCKMAN
Adder
1.02470588235294110.871
3151031BRUNSWICKG2
50/50
12.91612.916
935161AD1-151 C
Adder
22.3418.989
932046AC2-012 E
50/50
19.61519.615
958161AF2-110 C
Adder
2.03529411764705871.73
938531AE1-072 C
Adder
26.31411764705882622.367
3145393UNCAMP
Adder
8.9552941176470597.612
933981AD1-022 C
Adder
12.73411764705882410.824
900672V4-068 E
Adder
0.51764705882352950.44
3152411Z1-086 GT1
50/50
16.57316.573
961611AG1-000B C
Adder
22.53529411764706219.155
316375AC2-012 C
50/50
2.0222.022
940541AE2-040 C
50/50
4.3194.319
940481AE2-033 C
50/50
24.26824.268
940482AE2-033 E
50/50
16.3616.36
923263AB1-132 E OP
Adder
8.7870588235294127.469
3152441Z1-086 ST
50/50
28.8528.85
3152431Z1-086 GT3
50/50
16.56616.566
3152421Z1-086 GT2
50/50
16.56616.566
939191AE1-149 C
Adder
15.69529411764705913.341
3143316POE
50/50
2.0282.028
901082W1-029 E
Adder
47.440.29
3151041BRUNSWICKG3
50/50
12.91612.916
3151021BRUNSWICKG1
50/50
12.91612.916
940431AE2-027 C
Adder
17.9905882352941215.292
942002AE2-212 E
Adder
2.0588235294117651.75
316185AD1-033 C
50/50
1.8471.847
944581AF1-123 C
50/50
68.17868.178
941101AE2-104 C
Adder
4.9894117647058824.241
316088AB2-174 E
Adder
9.4352941176470598.02
923994AB2-040_E
Adder
8.8870588235294117.554
957481AF2-042 C
Adder
79.0188235294117667.166
944641AF1-129 C
Adder
140.53529411764706119.455
316240AF1-291 C
Adder
2.99294117647058842.544
924814AB2-134 E
Adder
17.61647058823529514.974
942342AE2-247 E
Adder
3.0517647058823532.594
919152AA1-139 E1
Adder
6.1235294117647065.205
920042AA2-088 E OP
Adder
15.46470588235294113.145
934521AD1-076 C
Adder
17.82705882352941315.153
934511AD1-075 C
Adder
12.27176470588235310.431
3145723EMPORIA
Adder
0.62588235294117660.532
923573AB1-173 E OP
Adder
4.744.029
942001AE2-212 C
Adder
3.08941176470588232.626
939192AE1-149 E
Adder
10.4635294117647078.894
939312AE1-162 E
Adder
2.07764705882352941.766
934065AD1-033 E
50/50
7.5367.536
937226AE2-253 E
Adder
8.7623529411764727.448
934501AD1-074 C
Adder
49.0858823529411841.723
958502AF2-144 E
Adder
1.78705882352941181.519
924517AB2-100 E2
Adder
4.2411764705882353.605
957482AF2-042 E
Adder
52.67882352941176544.777
934621AD1-088 C
Adder
13.69411764705882511.64
925332AB2-190 E
Adder
11.1200000000000019.452
927226AC1-216 E
Adder
10.7541176470588239.141
936666AD2-085 E
Adder
8.327.072
3151101ELIZAR3
50/50
4.8574.857
316315AB2-025 C
50/50
0.6130.613
946282AF1-292 E
Adder
1.49882352941176471.274
944012AF1-069 E
50/50
8.0328.032
316349AD2-085 C
Adder
5.09882352941176454.334
935112AD1-144 E
Adder
1.3882352941176471.18
3151091ELIZAR2
50/50
4.7134.713
944582AF1-123 E
50/50
156.119156.119
944592AF1-124 E
50/50
156.684156.684
923832AB2-022 E
Adder
1.8517647058823531.574
938772AE1-103 E
Adder
5.9670588235294125.072
916042Z1-036 E
Adder
42.2247058823529435.891
960082AF2-299 E
Adder
1.81058823529411761.539
946281AF1-292 C
Adder
2.24823529411764731.911
926071AC1-086 C
Adder
30.19411764705882525.665
3151051BRUNSWICKS1
50/50
26.83226.832
963042AG1-153 E
50/50
13.12513.125
964241AG1-285 C
Adder
6.4458823529411775.479
941591AE2-156 C
50/50
26.80726.807
3151081ELIZAR1
50/50
4.7964.796
316316AC1-027 C
50/50
0.4740.474
944591AF1-124 C
50/50
68.4268.42
944601AF1-125 C
50/50
67.12767.127
938771AE1-103 C
Adder
4.3211764705882353.673
3145413WATKINS
Adder
1.0152941176470590.863
960081AF2-299 C
Adder
2.7152941176470592.308
926072AC1-086 E
Adder
13.7423529411764711.681
944011AF1-069 C
50/50
20.67620.676
963041AG1-153 C
50/50
8.758.75
3150841SPRUNCB
Adder
12.87647058823529510.945
3150831SPRUNCA
Adder
12.87647058823529510.945
926662AC1-147 E
Adder
1.98235294117647071.685
916192Z1-068 E
50/50
2.8192.819
957492AF2-043 E
Adder
2.12235294117647081.804
923852AB2-025 E
50/50
1.7471.747
939412AE1-173 E
50/50
95.76595.765
923862AB2-026 E
Adder
1.81882352941176471.546
941032AE2-094 E
50/50
28.34228.342
941031AE2-094 C
50/50
63.2863.28
316303AF2-085
50/50
6.5326.532
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.2837.283
CBM South 2LTFEXP_CBM-S2->PJM
CBM
125.379125.379
CPLELTFEXP_CPLE->PJM
CLTF
15.2815.28
TVALTFEXP_TVA->PJM
CLTF
7.6637.663
O66PJM->LTFIMP_O-066
CMTX_NF
35.08335.083
NYPJM->LTFIMP_NY
CLTF
2.5532.553
LGEELTFEXP_LGEE->PJM
CLTF
1.5241.524
WECLTFEXP_WEC->PJM
CLTF
0.7920.792
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.98737.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.12228.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8684.868
LAGNLTFEXP_LAGN->PJM
CLTF
9.7559.755
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5125.512
SIGELTFEXP_SIGE->PJM
CLTF
0.30.3

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.07 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3287.01
MW Contribution:8.59
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
943471AF1-018 C
Adder
7.9588235294117656.765
316083AB2-161 C
80/20
0.7870.787
316072AD1-144 C
80/20
0.4020.402
940641AE2-051 C
80/20
27.30727.307
316336AC2-165 C
Adder
13.69411764705882511.64
934611AD1-087 C
80/20
1.761.76
3150651CHESTF6
Adder
24.50588235294117520.83
916191Z1-068 C
80/20
0.0640.064
316294AC1-161 C
80/20
7.267.26
957871AF2-081 C
80/20
14.54714.547
936591AD2-074 C
Adder
5.7647058823529424.9
3151151S HAMPT1
80/20
2.1352.135
316313AB2-026 C
80/20
0.5480.548
962571AG1-106 C
Adder
3.80823529411764743.237
316274AC1-208 C
Adder
12.4023529411764710.542
3151311EDGECMA
Adder
20.74352941176470817.632
316233AE1-074 C
80/20
3.7763.776
940551AE2-041 C
Adder
7.9588235294117656.765
3151211GRAVEL5
80/20
3.4433.443
943461AF1-017 C
80/20
1.9381.938
316311AC2-079 C
80/20
8.2428.242
3156056W1-029WIND
80/20
1.1231.123
942341AE2-247 C
80/20
2.1432.143
316246AF1-032 C
80/20
0.4130.413
316388AE2-253 GEN
80/20
2.8622.862
966621AG1-532 C
Adder
1.9870588235294121.689
944631AF1-128 C
Adder
48.040.8
3150921YORKTN3
Adder
157.0388235294118133.483
933291AC2-141 C
80/20
44.42644.426
316305AF2-043 C
80/20
0.5050.505
3150851SPRUNCC
80/20
0.2220.222
3156116Z1-036WIND
80/20
0.9440.944
939411AE1-173 C
80/20
140.502140.502
3137643SOCKMAN
Adder
1.00.85
3151031BRUNSWICKG2
80/20
12.67612.676
937481AD2-202 C
80/20
0.5110.511
3150731STONECA
Adder
8.9505882352941187.608
935161AD1-151 C
Adder
21.46588235294117618.246
3151221GRAVEL6
80/20
3.4833.483
3151201GRAVEL4
80/20
3.4873.487
958161AF2-110 C
80/20
1.9761.976
316017AA1-139 ULT1
80/20
1.5751.575
938531AE1-072 C
80/20
25.56125.561
933981AD1-022 C
Adder
12.39411764705882410.535
3152411Z1-086 GT1
80/20
16.26716.267
939191AE1-149 C
80/20
15.16215.162
957601AF2-054 C
Adder
2.37764705882352922.021
316365AB2-100 C1
80/20
1.3721.372
3151041BRUNSWICKG3
80/20
12.67612.676
3151021BRUNSWICKG1
80/20
12.67612.676
964791AG1-342 C
Adder
4.6788235294117653.977
961611AG1-000B C
Adder
21.72352941176470518.465
316236AE1-162 C
80/20
0.4930.493
3152331SURRY 2
80/20
34.47834.478
316375AC2-012 C
80/20
1.9631.963
313526AB2-022 C
80/20
0.5460.546
940541AE2-040 C
80/20
4.2084.208
940481AE2-033 C
80/20
23.64823.648
3152441Z1-086 ST
80/20
28.31628.316
3152431Z1-086 GT3
80/20
16.2616.26
3152421Z1-086 GT2
80/20
16.2616.26
3150861SPRUNCD
80/20
0.2220.222
940431AE2-027 C
Adder
17.26588235294117614.676
3150981CHESPKA
80/20
0.6340.634
316185AD1-033 C
80/20
1.7941.794
944581AF1-123 C
80/20
66.2266.22
941101AE2-104 C
80/20
4.8434.843
316320Y1-086 C
80/20
0.3190.319
944641AF1-129 C
Adder
134.59058823529412114.402
316240AF1-291 C
Adder
2.86941176470588262.439
316381AD1-082 C
80/20
1.7951.795
316036AC1-147 C
80/20
0.5360.536
316018AA1-139 ULT2
80/20
1.5751.575
934521AD1-076 C
Adder
17.34705882352941214.745
934511AD1-075 C
Adder
11.94117647058823610.15
316263AC1-034 C
Adder
8.8741176470588247.543
959311AF2-222 C
Adder
23.07176470588235519.611
316405AF2-144 C
80/20
0.4280.428
957481AF2-042 C
80/20
77.49977.499
942001AE2-212 C
80/20
2.9732.973
3151161SURRY 1
80/20
33.88933.889
3150991CHESPKB
80/20
1.051.05
316321Z2-027 C
80/20
0.5270.527
943741AF1-042 C
Adder
3.01647058823529422.564
934501AD1-074 C
Adder
47.763529411764740.599
961671AG1-007 C
Adder
1.26588235294117671.076
934621AD1-088 C
80/20
13.42613.426
946301AF1-294 C
Adder
4.8470588235294124.12
942461AE2-259 C
Adder
12.70588235294117810.8
3150601CHESTF5
Adder
76.7117647058823665.205
941591AE2-156 C
80/20
26.02126.021
3151081ELIZAR1
80/20
4.6564.656
316316AC1-027 C
80/20
0.460.46
944591AF1-124 C
80/20
66.45566.455
944601AF1-125 C
80/20
65.265.2
938771AE1-103 C
80/20
4.24.2
960081AF2-299 C
Adder
2.64941176470588242.252
944011AF1-069 C
80/20
20.29620.296
963041AG1-153 C
80/20
8.5888.588
3151541CLOVER2
80/20
17.71117.711
936261AD2-033 C
Adder
17.57529411764705814.939
961791AG1-021 C
Adder
2.35764705882352972.004
3151101ELIZAR3
80/20
4.7154.715
316315AB2-025 C
80/20
0.5980.598
961951AG1-038 C
Adder
3.3341176470588242.834
957861AF2-080 C
Adder
10.3623529411764718.808
3138533PONTONDP
Adder
0.87294117647058820.742
316169AC1-164 GEN
Adder
44.9588235294117738.215
316349AD2-085 C
80/20
4.9434.943
3151091ELIZAR2
80/20
4.5754.575
316258AE1-075 C
80/20
0.5030.503
316023AB2-100 C2
80/20
1.3721.372
946281AF1-292 C
Adder
2.19294117647058861.864
926071AC1-086 C
Adder
29.4425.024
3151051BRUNSWICKS1
80/20
26.33426.334
927021AC1-189 C
Adder
11.4094117647058839.698
3151531CLOVER1
80/20
17.87817.878
964241AG1-285 C
Adder
17.89058823529411815.207
962561AG1-105 C
Adder
11.8176470588235310.045
3150841SPRUNCB
80/20
12.34712.347
3150831SPRUNCA
80/20
12.34712.347
961941AG1-037 C
Adder
0.71058823529411760.604
941031AE2-094 C
80/20
62.11762.117
934331AD1-057 C
Adder
4.7623529411764714.048
934321AD1-056 C
Adder
8.5376470588235297.257
958211AF2-115 C
Adder
2.94705882352941152.505
316303AF2-085
80/20
6.3826.382
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1347.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.889122.889
CPLELTFEXP_CPLE->PJM
CLTF
14.96614.966
TVALTFEXP_TVA->PJM
CLTF
7.5327.532
NYPJM->LTFIMP_NY
CLTF
2.4692.469
LGEELTFEXP_LGEE->PJM
CLTF
1.5071.507
WECLTFEXP_WEC->PJM
CLTF
0.7840.784
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.6437.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.68227.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.8064.806
LAGNLTFEXP_LAGN->PJM
CLTF
9.5879.587
SIGELTFEXP_SIGE->PJM
CLTF
0.2960.296

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.59 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3225.32
MW Contribution:17.14
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.29 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3436.04
MW Contribution:17.13
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
939191AE1-149 C
Adder
8.8411764705882367.515
934576AD1-082 E
Adder
4.4847058823529413.812
916191Z1-068 C
50/50
0.0720.072
933292AC2-141 E
50/50
24.4824.48
316294AC1-161 C
50/50
9.3719.371
944602AF1-125 E
50/50
171.025171.025
3145506HICKORY
50/50
3.633.63
943612AF1-032 E
50/50
1.4511.451
957871AF2-081 C
50/50
16.44116.441
940492AE2-034 E
50/50
4.4344.434
934522AD1-076 E
Adder
8.667.361
943172AE2-346 E
Adder
0.76823529411764710.653
918492AA1-063AE OP
Adder
4.80941176470588254.088
962571AG1-106 C
Adder
2.94588235294117642.504
917332KELFORD E
Adder
2.01647058823529421.714
925122AB2-169 E
Adder
7.4694117647058836.349
316274AC1-208 C
Adder
10.168.636
917342Z2-044 E
Adder
0.65529411764705890.557
937482AD2-202 E
Adder
1.1129411764705880.946
3151311EDGECMA
Adder
16.76352941176470814.249
316084AB2-161 E
Adder
5.6282352941176474.784
316072AD1-144 C
50/50
0.4210.421
3145946PLYMOUTH TP
Adder
0.451764705882352960.384
933982AD1-022 E
Adder
6.5129411764705885.536
940641AE2-051 C
50/50
24.20324.203
927146AC1-208 E
Adder
4.5117647058823533.835
934622AD1-088 E
Adder
4.70470588235294153.999
934612AD1-087 E
Adder
3.80117647058823543.231
927255AC1-221 E
Adder
3.5270588235294122.998
924814AB2-134 E
Adder
11.1823529411764729.505
942342AE2-247 E
Adder
2.6752941176470592.274
316036AC1-147 C
50/50
0.60.6
919152AA1-139 E1
50/50
6.7236.723
316018AA1-139 ULT2
50/50
1.781.78
920042AA2-088 E OP
Adder
13.60117647058823611.561
934521AD1-076 C
Adder
16.99176470588235314.443
934511AD1-075 C
Adder
11.6964705882352959.942
3145723EMPORIA
Adder
0.44705882352941180.38
923573AB1-173 E OP
Adder
3.50352941176470622.978
919692AA2-053 E OP
Adder
4.8294117647058834.105
925785AC1-054 E
Adder
3.63176470588235353.087
316160AE1-175 E
Adder
1.12470588235294120.956
3150921YORKTN3
50/50
162.48162.48
3145256KINGFORK
50/50
1.5181.518
925522AC1-027 E
50/50
2.0032.003
933291AC2-141 C
50/50
57.34757.347
926755AC1-161 E
50/50
24.4824.48
941102AE2-104 E
50/50
7.8957.895
316305AF2-043 C
50/50
0.5470.547
957872AF2-081 E
50/50
7.0467.046
962572AG1-106 E
Adder
1.28941176470588251.096
926214AC1-099 E
Adder
1.38941176470588231.181
932632AC2-084 E
Adder
3.71882352941176463.161
964242AG1-285 E
Adder
8.5011764705882367.226
924162AB2-060 E OP
Adder
4.1870588235294123.559
964792AG1-342 E
Adder
2.2623529411764711.923
957832AF2-077 E
Adder
1.38000000000000011.173
943461AF1-017 C
Adder
1.75294117647058821.49
932596AC2-079 E
Adder
12.36705882352941210.512
316311AC2-079 C
Adder
7.586.443
938532AE1-072 E
50/50
14.99614.996
3146326AYDLETT TAP
50/50
2.2162.216
917122Z2-027 E
50/50
2.1312.131
3156056W1-029WIND
50/50
1.211.21
920692AA2-178 E
50/50
5.9125.912
966622AG1-532 E
Adder
0.95882352941176460.815
922923AB1-081 E OP
Adder
4.0270588235294123.423
932046AC2-012 E
50/50
21.31821.318
958161AF2-110 C
50/50
2.0262.026
316017AA1-139 ULT1
50/50
1.781.78
938531AE1-072 C
50/50
28.76728.767
3145393UNCAMP
Adder
8.367.106
315614AA2-178 C
50/50
2.2542.254
933981AD1-022 C
Adder
11.96352941176470710.169
900672V4-068 E
Adder
0.452941176470588240.385
924302AB2-077 E O1
Adder
1.3164705882352941.119
942341AE2-247 C
Adder
1.93764705882352951.647
943462AF1-017 E
Adder
2.86000000000000032.431
958162AF2-110 E
50/50
3.2233.223
316246AF1-032 C
50/50
0.4470.447
316388AE2-253 GEN
50/50
3.2483.248
919153AA1-139 E2
50/50
6.7236.723
934512AD1-075 E
Adder
5.95411764705882355.061
934502AD1-074 E
Adder
23.81647058823529420.244
924516AB2-100 E1
Adder
2.92235294117647062.484
918512AA1-065 E OP
Adder
7.1905882352941186.112
940642AE2-051 E
50/50
16.13516.135
966621AG1-532 C
Adder
1.43882352941176481.223
918532AA1-067 E
Adder
0.85764705882352940.729
924022AB2-043 E O1
Adder
5.1070588235294124.341
3147223TWITTYS
Adder
0.89647058823529410.762
959312AF2-222 E
Adder
10.3552941176470598.802
901082W1-029 E
50/50
49.64949.649
926206AC1-098 E
Adder
4.2070588235294123.576
964791AG1-342 C
Adder
3.39411764705882352.885
934012AD1-025 E
Adder
8.837647058823537.512
913392Y1-086 E
50/50
3.5213.521
3156116Z1-036WIND
50/50
0.9890.989
939411AE1-173 C
50/50
132.376132.376
3137643SOCKMAN
Adder
0.77882352941176480.662
919710AA2-057 E
Adder
4.43.74
316263AC1-034 C
Adder
7.1729411764705896.097
959311AF2-222 C
Adder
15.45647058823529513.138
961611AG1-000B C
Adder
17.5717647058823514.936
316236AE1-162 C
50/50
0.4750.475
3152331SURRY 2
50/50
52.22852.228
316375AC2-012 C
50/50
2.1982.198
313526AB2-022 C
50/50
0.6030.603
940541AE2-040 C
Adder
2.6435294117647062.247
940481AE2-033 C
Adder
15.09058823529411912.827
940482AE2-033 E
Adder
10.1729411764705898.647
923263AB1-132 E OP
Adder
6.6282352941176485.634
925612AC1-036 E
Adder
0.80823529411764720.687
924312AB2-078 E O1
Adder
1.3164705882352941.119
926274AC1-105 E
Adder
2.5482352941176472.166
3150981CHESPKA
50/50
0.7090.709
316185AD1-033 C
50/50
2.0522.052
944581AF1-123 C
50/50
75.87875.878
941101AE2-104 C
50/50
4.9664.966
316320Y1-086 C
50/50
0.3530.353
316141AB2-099 E
Adder
0.320.272
316088AB2-174 E
Adder
6.877647058823535.846
923994AB2-040_E
Adder
6.5694117647058825.584
957481AF2-042 C
Adder
58.59176470588235549.803
961672AG1-007 E
Adder
0.59882352941176480.509
924322AB2-079 E O1
Adder
1.3164705882352941.119
943902AF1-058 E
Adder
1.21411764705882351.032
939192AE1-149 E
Adder
4.0364705882352953.431
939312AE1-162 E
50/50
1.9371.937
3150991CHESPKB
50/50
1.1761.176
934065AD1-033 E
50/50
8.3718.371
937226AE2-253 E
50/50
9.6579.657
316321Z2-027 C
50/50
0.5770.577
940491AE2-034 C
50/50
1.6591.659
934501AD1-074 C
Adder
46.7858823529411839.768
924517AB2-100 E2
Adder
2.92235294117647062.484
957482AF2-042 E
Adder
39.0611764705882433.202
961671AG1-007 C
Adder
1.05647058823529430.898
934621AD1-088 C
Adder
9.7717647058823538.306
935172AD1-152 E
Adder
5.5847058823529414.747
927226AC1-216 E
Adder
6.8258823529411765.802
962962AG1-145 E
Adder
1.36235294117647051.158
936666AD2-085 E
Adder
7.2929411764705886.199
941591AE2-156 C
50/50
29.1829.18
3151081ELIZAR1
50/50
5.2375.237
316316AC1-027 C
50/50
0.520.52
944591AF1-124 C
50/50
76.14876.148
944601AF1-125 C
50/50
74.70974.709
938771AE1-103 C
50/50
4.0814.081
3145413WATKINS
Adder
0.93058823529411770.791
960081AF2-299 C
Adder
1.91882352941176481.631
926072AC1-086 E
Adder
10.3658823529411768.811
944011AF1-069 C
50/50
16.3216.32
963041AG1-153 C
Adder
6.8564705882352955.828
957862AF2-080 E
Adder
3.9294117647058823.34
936261AD2-033 C
Adder
11.82117647058823610.048
962562AG1-105 E
Adder
5.74.845
3151101ELIZAR3
50/50
5.3035.303
946282AF1-292 E
Adder
1.05882352941176470.9
944012AF1-069 E
50/50
6.346.34
957861AF2-080 C
Adder
8.8647058823529427.535
917512Z2-088 E OP1
Adder
5.58588235294117654.748
3144216WINCHST
50/50
0.1770.177
316349AD2-085 C
Adder
4.4694117647058833.799
935112AD1-144 E
50/50
1.4091.409
3151091ELIZAR2
50/50
5.1465.146
944582AF1-123 E
50/50
173.752173.752
944592AF1-124 E
50/50
174.381174.381
923832AB2-022 E
50/50
1.9881.988
938772AE1-103 E
50/50
5.6365.636
916042Z1-036 E
50/50
42.96342.963
960082AF2-299 E
Adder
1.27882352941176471.087
946281AF1-292 C
Adder
1.58823529411764721.35
926071AC1-086 C
Adder
22.77647058823529519.36
963042AG1-153 E
Adder
10.2835294117647068.741
927021AC1-189 C
Adder
9.768.296
964241AG1-285 C
Adder
12.75176470588235310.839
924152AB2-059 E OP
Adder
5.70470588235294154.849
962561AG1-105 C
Adder
8.5494117647058847.267
926662AC1-147 E
50/50
2.1552.155
916192Z1-068 E
50/50
3.0983.098
957492AF2-043 E
50/50
2.2332.233
923852AB2-025 E
Adder
1.06941176470588250.909
939412AE1-173 E
50/50
88.25188.251
961942AG1-037 E
Adder
0.427058823529411770.363
961941AG1-037 C
Adder
0.640.544
941032AE2-094 E
50/50
22.37122.371
941031AE2-094 C
50/50
49.94849.948
934332AD1-057 E
Adder
1.96588235294117661.671
934331AD1-057 C
Adder
3.7752941176470593.209
934321AD1-056 C
Adder
6.7670588235294115.752
934322AD1-056 E
Adder
3.6705882352941183.12
927022AC1-189 E
Adder
4.86235294117647054.133
925595AC1-034 E
Adder
5.4105882352941184.599
936262AD2-033 E
Adder
7.8811764705882356.699
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.515.51
CBM South 2LTFEXP_CBM-S2->PJM
CBM
91.70491.704
CPLELTFEXP_CPLE->PJM
CLTF
11.56611.566
TVALTFEXP_TVA->PJM
CLTF
4.9264.926
O66PJM->LTFIMP_O-066
CMTX_NF
19.32919.329
NYPJM->LTFIMP_NY
CLTF
1.4491.449
LGEELTFEXP_LGEE->PJM
CLTF
0.760.76
WECLTFEXP_WEC->PJM
CLTF
0.3980.398
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.74418.744
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.28317.283
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.712.71
LAGNLTFEXP_LAGN->PJM
CLTF
6.3446.344
G-007PJM->LTFIMP_G-007
CMTX_NF
3.0313.031
SIGELTFEXP_SIGE->PJM
CLTF
0.160.16

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.97
MW Contribution:16.91
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.97
MW Contribution:16.91
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3221.81
MW Contribution:16.91
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.28 %
Rating:3144.0 MVA
Rating Type:C
MVA to Mitigate:3435.8
MW Contribution:16.98
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934576AD1-082 E
Adder
4.8152941176470594.093
916191Z1-068 C
50/50
0.0730.073
933292AC2-141 E
50/50
24.52424.524
316294AC1-161 C
50/50
9.3889.388
944602AF1-125 E
50/50
172.13172.13
3145506HICKORY
50/50
3.6553.655
943612AF1-032 E
50/50
1.4671.467
957871AF2-081 C
50/50
16.56416.564
940492AE2-034 E
50/50
4.514.51
934522AD1-076 E
Adder
8.832941176470597.508
943172AE2-346 E
Adder
0.79058823529411770.672
918492AA1-063AE OP
Adder
5.04.25
962571AG1-106 C
Adder
3.1282352941176472.659
917332KELFORD E
Adder
2.081.768
925122AB2-169 E
Adder
7.6341176470588236.489
316274AC1-208 C
Adder
10.5388235294117658.958
917342Z2-044 E
Adder
0.6764705882352940.575
937482AD2-202 E
Adder
1.11058823529411770.944
3151311EDGECMA
Adder
17.2952941176470614.701
316084AB2-161 E
Adder
6.0435294117647055.137
316072AD1-144 C
50/50
0.4270.427
3145946PLYMOUTH TP
Adder
0.460.391
933982AD1-022 E
Adder
6.6541176470588245.656
940641AE2-051 C
50/50
23.90723.907
927146AC1-208 E
Adder
4.6800000000000013.978
934622AD1-088 E
Adder
4.7082352941176474.002
934612AD1-087 E
Adder
3.79294117647058873.224
935162AD1-151 E
Adder
9.3141176470588247.917
957832AF2-077 E
Adder
1.4235294117647061.21
943461AF1-017 C
Adder
1.81411764705882361.542
932596AC2-079 E
Adder
12.76823529411764610.853
316311AC2-079 C
Adder
7.8258823529411776.652
938532AE1-072 E
50/50
15.11415.114
3146326AYDLETT TAP
50/50
2.2332.233
917122Z2-027 E
50/50
2.1522.152
3156056W1-029WIND
50/50
1.2241.224
920692AA2-178 E
50/50
6.0146.014
966622AG1-532 E
Adder
1.03058823529411760.876
922923AB1-081 E OP
Adder
4.1529411764705883.53
935161AD1-151 C
Adder
13.97176470588235211.876
932046AC2-012 E
50/50
21.49421.494
958161AF2-110 C
50/50
2.0612.061
316017AA1-139 ULT1
50/50
1.7931.793
938531AE1-072 C
50/50
28.99428.994
3145393UNCAMP
Adder
8.5611764705882367.277
315614AA2-178 C
50/50
2.2932.293
942341AE2-247 C
Adder
2.00470588235294131.704
943462AF1-017 E
Adder
2.962.516
958162AF2-110 E
50/50
3.2793.279
316246AF1-032 C
50/50
0.4520.452
316388AE2-253 GEN
50/50
3.2713.271
919153AA1-139 E2
50/50
6.7746.774
934512AD1-075 E
Adder
6.07294117647058855.162
934502AD1-074 E
Adder
24.29058823529411620.647
924516AB2-100 E1
Adder
3.19529411764705932.716
918512AA1-065 E OP
Adder
7.3847058823529416.277
940642AE2-051 E
50/50
15.93815.938
966621AG1-532 C
Adder
1.54588235294117651.314
918532AA1-067 E
Adder
0.87882352941176480.747
924022AB2-043 E O1
Adder
5.1847058823529414.407
3147223TWITTYS
Adder
0.90823529411764710.772
959312AF2-222 E
Adder
10.5035294117647088.928
316160AE1-175 E
Adder
1.160.986
3150921YORKTN3
50/50
165.39165.39
3145256KINGFORK
50/50
1.5391.539
925522AC1-027 E
50/50
2.0192.019
933291AC2-141 C
50/50
57.45157.451
926755AC1-161 E
50/50
24.52424.524
941102AE2-104 E
50/50
8.0328.032
316305AF2-043 C
50/50
0.5530.553
957872AF2-081 E
50/50
7.0997.099
962572AG1-106 E
Adder
1.36823529411764721.163
926214AC1-099 E
Adder
1.43882352941176481.223
932632AC2-084 E
Adder
3.8494117647058823.272
964242AG1-285 E
Adder
8.5717647058823537.286
924162AB2-060 E OP
Adder
4.2517647058823533.614
964792AG1-342 E
Adder
2.2835294117647061.941
934012AD1-025 E
Adder
9.3823529411764717.975
913392Y1-086 E
50/50
3.5543.554
3156116Z1-036WIND
50/50
1.0021.002
939411AE1-173 C
50/50
131.454131.454
3137643SOCKMAN
Adder
0.820.697
919710AA2-057 E
Adder
4.5505882352941183.868
924814AB2-134 E
Adder
11.87058823529411810.09
942342AE2-247 E
Adder
2.76823529411764732.353
316036AC1-147 C
50/50
0.6050.605
919152AA1-139 E1
50/50
6.7746.774
316018AA1-139 ULT2
50/50
1.7931.793
920042AA2-088 E OP
Adder
14.01647058823529311.914
934521AD1-076 C
Adder
17.32941176470588514.73
934511AD1-075 C
Adder
11.92941176470588310.14
3145723EMPORIA
Adder
0.47882352941176470.407
923573AB1-173 E OP
Adder
3.7152941176470593.158
919692AA2-053 E OP
Adder
5.035294117647064.28
933981AD1-022 C
Adder
12.2223529411764710.389
900672V4-068 E
Adder
0.46705882352941180.397
924302AB2-077 E O1
Adder
1.3364705882352941.136
961611AG1-000B C
Adder
18.24117647058823615.505
316236AE1-162 C
50/50
0.4850.485
3152331SURRY 2
50/50
52.46452.464
316375AC2-012 C
50/50
2.2162.216
313526AB2-022 C
50/50
0.6090.609
940541AE2-040 C
Adder
3.02117647058823562.568
940481AE2-033 C
Adder
17.1423529411764714.571
940482AE2-033 E
Adder
11.5564705882352949.823
923263AB1-132 E OP
Adder
7.045.984
925612AC1-036 E
Adder
0.81882352941176460.696
924312AB2-078 E O1
Adder
1.3364705882352941.136
926274AC1-105 E
Adder
2.56470588235294142.18
939191AE1-149 C
Adder
9.8705882352941188.39
901082W1-029 E
50/50
50.20950.209
926206AC1-098 E
Adder
4.3541176470588243.701
964791AG1-342 C
Adder
3.42470588235294132.911
3150981CHESPKA
50/50
0.7150.715
316185AD1-033 C
50/50
2.0652.065
944581AF1-123 C
50/50
76.36876.368
941101AE2-104 C
50/50
5.0525.052
316320Y1-086 C
50/50
0.3560.356
316141AB2-099 E
Adder
0.32941176470588240.28
316088AB2-174 E
Adder
7.3223529411764716.224
923994AB2-040_E
Adder
6.96705882352941155.922
957481AF2-042 C
Adder
58.3200000000000149.572
961672AG1-007 E
Adder
0.61647058823529410.524
924322AB2-079 E O1
Adder
1.3364705882352941.136
925785AC1-054 E
Adder
3.7423529411764713.181
316263AC1-034 C
Adder
7.3964705882352946.287
959311AF2-222 C
Adder
15.67647058823529313.325
939192AE1-149 E
Adder
6.585.593
939312AE1-162 E
50/50
1.9771.977
3150991CHESPKB
50/50
1.1851.185
934065AD1-033 E
50/50
8.4268.426
937226AE2-253 E
50/50
9.7279.727
316321Z2-027 C
50/50
0.5830.583
940491AE2-034 C
50/50
1.6871.687
934501AD1-074 C
Adder
47.7164705882352940.559
924517AB2-100 E2
Adder
3.19529411764705932.716
957482AF2-042 E
Adder
38.8833.048
961671AG1-007 C
Adder
1.08705882352941190.924
934621AD1-088 C
Adder
9.7788235294117638.312
935172AD1-152 E
Adder
5.5800000000000014.743
927226AC1-216 E
Adder
7.2470588235294126.16
962962AG1-145 E
Adder
1.40705882352941171.196
936666AD2-085 E
Adder
7.5470588235294126.415
941591AE2-156 C
50/50
29.41729.417
3151081ELIZAR1
50/50
5.2795.279
316316AC1-027 C
50/50
0.5240.524
944591AF1-124 C
50/50
76.6476.64
944601AF1-125 C
50/50
75.19275.192
938771AE1-103 C
50/50
4.1744.174
3145413WATKINS
Adder
0.9552941176470590.812
960081AF2-299 C
Adder
2.061.751
926072AC1-086 E
Adder
11.0094117647058839.358
944011AF1-069 C
Adder
16.07529411764705813.664
963041AG1-153 C
Adder
6.7647058823529415.75
957862AF2-080 E
Adder
4.0352941176470593.43
936261AD2-033 C
Adder
10.6341176470588249.039
962562AG1-105 E
Adder
5.75647058823529444.893
3151101ELIZAR3
50/50
5.3455.345
946282AF1-292 E
Adder
1.13647058823529410.966
944012AF1-069 E
Adder
6.24470588235294165.308
957861AF2-080 C
Adder
9.1035294117647067.738
917512Z2-088 E OP1
Adder
5.7423529411764714.881
3144216WINCHST
50/50
0.180.18
316349AD2-085 C
Adder
4.6258823529411773.932
935112AD1-144 E
50/50
1.4291.429
3151091ELIZAR2
50/50
5.1875.187
944582AF1-123 E
50/50
174.875174.875
944592AF1-124 E
50/50
175.508175.508
923832AB2-022 E
50/50
2.0062.006
938772AE1-103 E
50/50
5.7645.764
916042Z1-036 E
50/50
43.55943.559
960082AF2-299 E
Adder
1.37411764705882341.168
946281AF1-292 C
Adder
1.70588235294117641.45
926071AC1-086 C
Adder
24.18941176470588420.561
963042AG1-153 E
Adder
10.1470588235294118.625
927021AC1-189 C
Adder
10.0235294117647068.52
964241AG1-285 C
Adder
12.8576470588235310.929
924152AB2-059 E OP
Adder
5.8823529411764715
962561AG1-105 C
Adder
8.6352941176470587.34
926662AC1-147 E
50/50
2.1732.173
916192Z1-068 E
50/50
3.1213.121
957492AF2-043 E
50/50
2.2562.256
923852AB2-025 E
Adder
1.22235294117647041.039
939412AE1-173 E
50/50
87.63687.636
961942AG1-037 E
Adder
0.43882352941176470.373
961941AG1-037 C
Adder
0.65882352941176480.56
941032AE2-094 E
Adder
22.03411764705882418.729
941031AE2-094 C
Adder
49.1976470588235341.818
934332AD1-057 E
Adder
2.05294117647058851.745
934331AD1-057 C
Adder
3.94352941176470573.352
934321AD1-056 C
Adder
7.0682352941176476.008
934322AD1-056 E
Adder
3.83411764705882343.259
927022AC1-189 E
Adder
4.9929411764705884.244
925595AC1-034 E
Adder
5.5800000000000014.743
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.5515.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.27192.271
CPLELTFEXP_CPLE->PJM
CLTF
11.65111.651
TVALTFEXP_TVA->PJM
CLTF
4.9574.957
O66PJM->LTFIMP_O-066
CMTX_NF
19.78919.789
NYPJM->LTFIMP_NY
CLTF
1.4831.483
LGEELTFEXP_LGEE->PJM
CLTF
0.7650.765
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.83618.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.38817.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7262.726
LAGNLTFEXP_LAGN->PJM
CLTF
6.3836.383
G-007PJM->LTFIMP_G-007
CMTX_NF
3.1033.103
SIGELTFEXP_SIGE->PJM
CLTF
0.1610.161
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P7-1: ELMONT-LADYSMITH_500_230_SRT-A'
 OPEN BRANCH FROM BUS 314218 TO BUS 314196 CKT 1   /*6ELMONT      230.0 - 6LADYSMITH   230.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1   /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T567_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314903 CKT 1 /*8ELMONT      500.0 - 8CHCKAHM     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314911 CKT 1 /*8NO ANNA     500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
314282 to 314285 ckt 1
314285 to 314316 ckt 1
314287 to 314276 ckt 1
314331 to 314263 ckt 1
314902 to 314282 ckt 2
314902 to 314914 ckt 1
314914 to 314322 ckt 1
314914 to 314918 ckt 1
314924 to 314903 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC100.89 %984.18B992.943.04
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC113.38 %3940.0C4467.222.93
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.8 %3220.44B3342.689.14
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: 563T576_SRT-S
BreakerAC104.31 %3637.0C3793.6919.16
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC111.92 %4070.2B4555.568.3
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC111.48 %5011.0C5586.2820.75
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
SingleAC101.04 %4070.2B4112.57.02
GD1DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: 545T552_SRT-S
BreakerAC107.93 %3940.0C4252.5711.21
GD1DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC100.32 %3220.44B3230.794.27
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC119.82 %3220.44B3858.598.78
GD1DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC117.79 %3940.0C4641.1122.09
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC111.38 %3220.44B3586.785.14
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
SingleAC111.09 %3220.44B3577.615.39
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC110.41 %3940.0C4350.1713.4
GD1DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T594_SRT-S
BreakerAC106.75 %3940.0C4205.8112.87
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC116.97 %3220.44B3767.035.7
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC114.22 %3220.44B3678.495.89
GD1DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC111.99 %3940.0C4412.3614.79
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC106.7 %4070.2B4342.9717.25
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC102.59 %4070.2B4175.6217.25
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC121.18 %3220.44B3902.625.54
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC120.07 %3220.44B3866.795.76
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T575_SRT-A
BreakerAC117.55 %3940.0C4631.3214.45
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC104.04 %4070.2B4234.717.1

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.89 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:992.94
MW Contribution:3.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
80/20
13.23613.236
961671AG1-007 C
80/20
0.4820.482
940491AE2-034 C
80/20
0.4170.417
316359AB2-059 C OP
80/20
0.8920.892
316283AC2-100 C
80/20
0.510.51
946301AF1-294 C
Adder
1.3164705882352941.119
934621AD1-088 C
80/20
4.424.42
942001AE2-212 C
Adder
-3.9329411764705884-3.343
3151261ROARAP2
80/20
0.8190.819
3152411Z1-086 GT1
80/20
5.755.75
3152421Z1-086 GT2
80/20
5.7485.748
932631AC2-084 C
80/20
0.5330.533
316274AC1-208 C
80/20
4.9624.962
962571AG1-106 C
80/20
1.851.85
3151311EDGECMA
80/20
8.3398.339
315614AA2-178 C
80/20
0.5670.567
3151411GASTONB
80/20
2.0712.071
316181AB2-040 GEN
80/20
0.8530.853
3147043LAWRENC
80/20
0.2030.203
940481AE2-033 C
80/20
16.46516.465
940541AE2-040 C
80/20
2.9992.999
3152441Z1-086 ST
80/20
10.00810.008
3152661PLYWOOD A
80/20
0.5410.541
316005AA1-067 C
80/20
0.1280.128
316210AC1-098 C
80/20
0.50.5
316318V4-068 C
80/20
0.0370.037
313506AB1-173 C OP
80/20
0.7570.757
966621AG1-532 C
80/20
1.041.04
3151601KERR 3
80/20
0.5540.554
3151581KERR 1
80/20
0.1980.198
935171AD1-152 C
80/20
0.620.62
3151021BRUNSWICKG1
80/20
4.4774.477
3151041BRUNSWICKG3
80/20
4.4774.477
316365AB2-100 C1
80/20
0.7990.799
3156083AA2-088SOLA
80/20
0.4670.467
316003AC1-222 C
80/20
0.4260.426
957481AF2-042 C
80/20
26.38726.387
943171AE2-346 C
80/20
0.1050.105
961941AG1-037 C
80/20
0.2370.237
3151391GASTONA
80/20
2.0712.071
934321AD1-056 C
80/20
3.7443.744
934331AD1-057 C
80/20
2.0892.089
958211AF2-115 C
Adder
0.80.68
3151531CLOVER1
80/20
6.056.05
941031AE2-094 C
80/20
22.06822.068
316140AB2-099 C
80/20
0.0450.045
3152921DOMTR78
80/20
0.5570.557
316319Z2-044 C
80/20
0.1130.113
3151641KERR 7
80/20
0.5540.554
313527AB2-043 C
80/20
0.2380.238
3151361ROSEMG1
80/20
1.3551.355
316327AA2-057 C
80/20
0.7010.701
3151151S HAMPT1
80/20
0.570.57
316239AB2-077 C O1
80/20
0.1510.151
964791AG1-342 C
80/20
1.5971.597
3156011CONETOE2SOL
80/20
0.6290.629
3151611KERR 4
80/20
0.5540.554
3151621KERR 5
80/20
0.5540.554
316237AB2-079 C O1
80/20
0.1510.151
316222AC1-221 C
80/20
0.6320.632
934611AD1-087 C
80/20
0.5960.596
3152431Z1-086 GT3
80/20
5.7485.748
940641AE2-051 C
80/20
9.0359.035
933981AD1-022 C
80/20
3.5783.578
316174AB2-169_C
80/20
0.4490.449
3156063AA2-053SOLA
80/20
0.860.86
3151281ROARAP4
80/20
0.7750.775
316049AB1-081 C OP
80/20
0.7570.757
316238AB2-078 C O1
80/20
0.1510.151
934521AD1-076 C
80/20
4.8074.807
934511AD1-075 C
80/20
3.3093.309
316212AC1-099 C
80/20
0.1680.168
316263AC1-034 C
80/20
3.5493.549
3156073AA1-063SOLA
80/20
0.7530.753
316087AB2-174 C
80/20
0.8150.815
3151591KERR 2
80/20
0.5540.554
959311AF2-222 C
80/20
6.6486.648
937481AD2-202 C
80/20
0.1730.173
3151031BRUNSWICKG2
80/20
4.4774.477
316240AF1-291 C
Adder
-1.6611764705882353-1.412
944641AF1-129 C
Adder
-92.12117647058824-78.303
927021AC1-189 C
80/20
4.1534.153
926071AC1-086 C
80/20
14.30114.301
946281AF1-292 C
80/20
1.1471.147
964241AG1-285 C
80/20
5.5515.551
962561AG1-105 C
80/20
4.0224.022
3151381ROSEMG2
80/20
0.6340.634
960081AF2-299 C
80/20
1.3861.386
936261AD2-033 C
80/20
5.4245.424
316248AF1-058 C
80/20
0.140.14
961791AG1-021 C
Adder
0.640.544
938771AE1-103 C
Adder
0.96705882352941170.822
963041AG1-153 C
80/20
3.0443.044
3151051BRUNSWICKS1
80/20
9.3029.302
944011AF1-069 C
80/20
7.217.21
316317KELFORD C
80/20
0.1760.176
957861AF2-080 C
80/20
3.7723.772
316023AB2-100 C2
80/20
0.7990.799
316129AC1-054 C
80/20
0.6480.648
3151631KERR 6
80/20
0.5540.554
316315AB2-025 C
80/20
0.4250.425
3156021HOLLOMANSOL
80/20
0.830.83
316011AB1-132 C OP
80/20
1.5811.581
3151371ROSEMS1
80/20
0.8390.839
3137643SOCKMAN
80/20
0.4490.449
939411AE1-173 C
80/20
41.75841.758
316131AB2-060 C
80/20
0.680.68
3138533PONTONDP
Adder
0.237647058823529430.202
3151541CLOVER2
80/20
5.9935.993
316034AC1-036 C
80/20
0.0950.095
316118AC1-105 C
80/20
0.4080.408
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.6422.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.16446.164
CPLELTFEXP_CPLE->PJM
CLTF
5.5395.539
TVALTFEXP_TVA->PJM
CLTF
3.0473.047
NYPJM->LTFIMP_NY
CLTF
0.5840.584
LGEELTFEXP_LGEE->PJM
CLTF
0.6950.695
WECLTFEXP_WEC->PJM
CLTF
0.3670.367
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.95317.953
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.57311.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.1342.134
LAGNLTFEXP_LAGN->PJM
CLTF
3.8673.867
SIGELTFEXP_SIGE->PJM
CLTF
0.1330.133

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.38 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4467.2
MW Contribution:22.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
45.3647058823529438.56
961671AG1-007 C
Adder
1.25411764705882361.066
920692AA2-178 E
Adder
5.5388235294117654.708
922923AB1-081 E OP
Adder
4.9682352941176474.223
966622AG1-532 E
Adder
1.24941176470588241.062
917122Z2-027 E
Adder
1.81294117647058831.541
3146326AYDLETT TAP
50/50
1.8341.834
938532AE1-072 E
50/50
12.39212.392
927264AC1-222 E
Adder
5.0905882352941184.327
3152411Z1-086 GT1
50/50
17.34217.342
3152421Z1-086 GT2
50/50
17.33717.337
943461AF1-017 C
Adder
1.71411764705882371.457
316311AC2-079 C
Adder
7.3223529411764716.224
932596AC2-079 E
Adder
11.94588235294117610.154
943172AE2-346 E
Adder
0.81176470588235290.69
917332KELFORD E
Adder
2.2035294117647061.873
925122AB2-169 E
Adder
7.7223529411764716.564
934522AD1-076 E
Adder
8.397647058823537.138
940492AE2-034 E
Adder
4.1541176470588243.531
316274AC1-208 C
Adder
12.05058823529411810.243
962571AG1-106 C
Adder
3.6529411764705883.105
917342Z2-044 E
Adder
0.79764705882352950.678
3151311EDGECMA
Adder
20.6976470588235317.593
918492AA1-063AE OP
Adder
5.4552941176470594.637
957871AF2-081 C
50/50
13.52313.523
937482AD2-202 E
50/50
1.5031.503
3145506HICKORY
50/50
2.9532.953
933292AC2-141 E
50/50
18.00718.007
934576AD1-082 E
Adder
5.2247058823529414.441
944602AF1-125 E
50/50
140.592140.592
943612AF1-032 E
Adder
1.24117647058823531.055
918512AA1-065 E OP
Adder
7.42823529411764756.314
918532AA1-067 E
Adder
0.95764705882352940.814
934502AD1-074 E
Adder
23.0929411764705919.629
934512AD1-075 E
Adder
5.7729411764705894.907
924516AB2-100 E1
Adder
3.9282352941176473.339
966621AG1-532 C
Adder
1.87411764705882341.593
919153AA1-139 E2
50/50
5.535.53
316388AE2-253 GEN
50/50
2.652.65
924022AB2-043 E O1
Adder
6.3552941176470595.402
3151021BRUNSWICKG1
50/50
13.49313.493
3151041BRUNSWICKG3
50/50
13.49313.493
940642AE2-051 E
50/50
19.2519.25
942341AE2-247 C
Adder
1.89411764705882371.61
943462AF1-017 E
Adder
2.7964705882352942.377
958162AF2-110 E
Adder
2.8811764705882352.449
923263AB1-132 E OP
Adder
8.217647058823536.985
940481AE2-033 C
50/50
22.31122.311
940482AE2-033 E
50/50
15.04115.041
940541AE2-040 C
50/50
3.9673.967
924312AB2-078 E O1
Adder
1.6447058823529411.398
926274AC1-105 E
Adder
3.4082352941176472.897
3152441Z1-086 ST
50/50
30.18730.187
316375AC2-012 C
50/50
1.8031.803
316141AB2-099 E
Adder
0.33882352941176470.288
961672AG1-007 E
Adder
0.71058823529411760.604
923994AB2-040_E
Adder
8.2247058823529416.991
316088AB2-174 E
Adder
8.7141176470588247.407
924322AB2-079 E O1
Adder
1.6447058823529411.398
943902AF1-058 E
Adder
1.65529411764705881.407
957481AF2-042 C
50/50
79.02379.023
316294AC1-161 C
50/50
6.8696.869
944581AF1-123 C
50/50
62.37662.376
934521AD1-076 C
Adder
16.4752941176470614.004
934511AD1-075 C
Adder
11.3411764705882369.64
919692AA2-053 E OP
Adder
5.65176470588235354.804
316263AC1-034 C
Adder
8.8505882352941177.523
923573AB1-173 E OP
Adder
4.3858823529411773.728
3145723EMPORIA
Adder
0.57647058823529410.49
920042AA2-088 E OP
Adder
14.1647058823529412.04
925785AC1-054 E
Adder
4.5188235294117653.841
919152AA1-139 E1
50/50
5.535.53
926206AC1-098 E
Adder
4.8835294117647064.151
964791AG1-342 C
Adder
4.4517647058823523.784
901082W1-029 E
Adder
42.9564705882352936.513
3143316POE
Adder
1.6082352941176471.367
939191AE1-149 C
Adder
12.10588235294117610.29
933982AD1-022 E
Adder
6.417647058823535.455
3145946PLYMOUTH TP
Adder
0.435294117647058830.37
927146AC1-208 E
Adder
5.3517647058823544.549
316017AA1-139 ULT1
50/50
1.4591.459
927255AC1-221 E
Adder
4.84941176470588254.122
934612AD1-087 E
50/50
5.1365.136
934611AD1-087 C
50/50
1.7741.774
934622AD1-088 E
50/50
6.3856.385
3152431Z1-086 GT3
50/50
17.33717.337
940641AE2-051 C
50/50
28.87528.875
316084AB2-161 E
Adder
6.5576470588235295.574
933981AD1-022 C
Adder
11.78823529411764610.02
900672V4-068 E
Adder
0.47764705882352950.406
938531AE1-072 C
50/50
23.77123.771
924302AB2-077 E O1
Adder
1.6447058823529411.398
3145393UNCAMP
Adder
8.0941176470588236.88
932046AC2-012 E
50/50
17.5517.55
958161AF2-110 C
Adder
1.8117647058823531.54
926214AC1-099 E
Adder
1.61294117647058831.371
932632AC2-084 E
Adder
4.3164705882352943.669
962572AG1-106 E
Adder
1.59764705882352961.358
957872AF2-081 E
50/50
5.7955.795
316018AA1-139 ULT2
50/50
1.4591.459
924162AB2-060 E OP
Adder
5.2141176470588244.432
964242AG1-285 E
Adder
9.9188235294117648.431
964792AG1-342 E
Adder
2.9682352941176472.523
932763AC2-100 E
Adder
3.2952941176470592.801
926755AC1-161 E
50/50
18.00718.007
933291AC2-141 C
50/50
42.18342.183
3150921YORKTN3
Adder
106.1988235294117790.269
925522AC1-027 E
50/50
1.641.64
941102AE2-104 E
Adder
7.0576470588235295.999
3145256KINGFORK
Adder
1.30823529411764721.112
937481AD2-202 C
50/50
0.5150.515
3151031BRUNSWICKG2
50/50
13.49313.493
942342AE2-247 E
Adder
2.61647058823529432.224
927021AC1-189 C
Adder
11.2564705882352949.568
926071AC1-086 C
Adder
28.2376470588235324.002
924152AB2-059 E OP
Adder
7.0388235294117655.983
946281AF1-292 C
Adder
2.0682352941176471.758
960082AF2-299 E
Adder
1.66588235294117641.416
916042Z1-036 E
Adder
38.52941176470588432.75
923832AB2-022 E
Adder
1.67529411764705881.424
964241AG1-285 C
Adder
14.8776470588235312.646
962561AG1-105 C
Adder
11.1211764705882359.453
938772AE1-103 E
Adder
5.3788235294117654.572
963042AG1-153 E
50/50
13.7613.76
944592AF1-124 E
50/50
143.351143.351
944582AF1-123 E
50/50
142.834142.834
3151091ELIZAR2
50/50
4.2124.212
316349AD2-085 C
Adder
4.3705882352941173.715
935112AD1-144 E
Adder
1.21411764705882351.032
957862AF2-080 E
Adder
4.53176470588235253.852
926072AC1-086 E
Adder
12.85176470588235310.924
960081AF2-299 C
Adder
2.4988235294117652.124
3145413WATKINS
Adder
0.92117647058823540.783
962562AG1-105 E
Adder
7.41411764705882356.302
938771AE1-103 C
Adder
3.8941176470588243.31
963041AG1-153 C
50/50
9.1739.173
3151051BRUNSWICKS1
50/50
28.03428.034
944011AF1-069 C
50/50
21.78821.788
944591AF1-124 C
50/50
62.59862.598
944601AF1-125 C
50/50
61.41561.415
3151101ELIZAR3
50/50
4.3424.342
941591AE2-156 C
50/50
24.00724.007
936666AD2-085 E
Adder
7.1317647058823546.062
961942AG1-037 E
Adder
0.451764705882352960.384
961941AG1-037 C
Adder
0.6764705882352940.575
927022AC1-189 E
Adder
5.6070588235294124.766
934322AD1-056 E
Adder
4.5447058823529413.863
934332AD1-057 E
Adder
2.43411764705882352.069
934321AD1-056 C
Adder
8.3788235294117657.122
934331AD1-057 C
Adder
4.6741176470588233.973
925595AC1-034 E
Adder
6.6764705882352945.675
923852AB2-025 E
50/50
1.6041.604
3151531CLOVER1
50/50
18.02218.022
941031AE2-094 C
50/50
66.68466.684
941032AE2-094 E
50/50
29.86629.866
939412AE1-173 E
50/50
96.49596.495
3151081ELIZAR1
50/50
4.2884.288
926662AC1-147 E
Adder
1.77411764705882361.508
916192Z1-068 E
50/50
2.5342.534
957492AF2-043 E
Adder
1.9105882352941181.624
957861AF2-080 C
Adder
10.2235294117647058.69
919710AA2-057 E
Adder
5.2964705882352944.502
3137643SOCKMAN
Adder
0.95176470588235310.809
913392Y1-086 E
Adder
2.9682352941176472.523
939411AE1-173 C
50/50
144.742144.742
316185AD1-033 C
50/50
1.6591.659
916191Z1-068 C
50/50
0.0590.059
941101AE2-104 C
Adder
4.4388235294117653.773
924517AB2-100 E2
Adder
3.9282352941176473.339
937226AE2-253 E
50/50
7.9097.909
935172AD1-152 E
Adder
7.5717647058823536.436
934621AD1-088 C
50/50
13.2613.26
957482AF2-042 E
50/50
52.68252.682
939192AE1-149 E
Adder
8.0705882352941176.86
939312AE1-162 E
Adder
1.72117647058823551.463
934065AD1-033 E
50/50
6.7926.792
917512Z2-088 E OP1
Adder
6.54705882352941255.565
946282AF1-292 E
Adder
1.37882352941176461.172
316315AB2-025 C
50/50
0.5620.562
3151541CLOVER2
50/50
17.85317.853
944012AF1-069 E
50/50
8.4648.464
316316AC1-027 C
50/50
0.4240.424
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.6257.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
136.078136.078
CPLELTFEXP_CPLE->PJM
CLTF
15.98515.985
TVALTFEXP_TVA->PJM
CLTF
9.3529.352
O66PJM->LTFIMP_O-066
CMTX_NF
36.00236.002
NYPJM->LTFIMP_NY
CLTF
2.5842.584
LGEELTFEXP_LGEE->PJM
CLTF
2.1892.189
WECLTFEXP_WEC->PJM
CLTF
1.1371.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.25255.252
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.53435.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.5866.586
LAGNLTFEXP_LAGN->PJM
CLTF
11.79711.797
G-007PJM->LTFIMP_G-007
CMTX_NF
5.665.66
SIGELTFEXP_SIGE->PJM
CLTF
0.4160.416

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.8 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3342.68
MW Contribution:9.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
80/20
45.0845.08
961671AG1-007 C
Adder
1.2482352941176471.061
940491AE2-034 C
80/20
1.5381.538
3156116Z1-036WIND
80/20
0.8770.877
946301AF1-294 C
Adder
3.75411764705882333.191
934621AD1-088 C
80/20
13.20613.206
942001AE2-212 C
Adder
2.11411764705882371.797
934521AD1-076 C
80/20
16.37216.372
934511AD1-075 C
80/20
11.2711.27
316212AC1-099 C
80/20
0.4180.418
316263AC1-034 C
Adder
8.8035294117647057.483
3156073AA1-063SOLA
80/20
1.8611.861
316087AB2-174 C
80/20
1.561.56
316321Z2-027 C
80/20
0.4860.486
959311AF2-222 C
Adder
18.28823529411764815.545
937481AD2-202 C
80/20
0.5130.513
3151031BRUNSWICKG2
80/20
13.44613.446
316036AC1-147 C
80/20
0.4890.489
316305AF2-043 C
80/20
0.4630.463
3151261ROARAP2
80/20
1.8341.834
3156056W1-029WIND
80/20
1.0361.036
3152411Z1-086 GT1
80/20
17.28117.281
3152421Z1-086 GT2
80/20
17.27717.277
943461AF1-017 C
80/20
1.7011.701
316311AC2-079 C
80/20
7.2667.266
932631AC2-084 C
80/20
1.3311.331
316274AC1-208 C
80/20
11.98411.984
962571AG1-106 C
80/20
3.6323.632
3151311EDGECMA
Adder
20.58941176470588317.501
957871AF2-081 C
80/20
13.4313.43
315614AA2-178 C
80/20
2.0912.091
3151411GASTONB
80/20
4.0664.066
316181AB2-040 GEN
80/20
1.6831.683
3147043LAWRENC
80/20
0.3980.398
940481AE2-033 C
80/20
22.18122.181
940541AE2-040 C
80/20
3.9443.944
3152441Z1-086 ST
80/20
30.08130.081
961611AG1-000B C
Adder
17.0670588235294114.507
316375AC2-012 C
80/20
1.7911.791
316072AD1-144 C
80/20
0.3590.359
316210AC1-098 C
80/20
1.251.25
316318V4-068 C
80/20
0.1070.107
313506AB1-173 C OP
80/20
1.4941.494
966621AG1-532 C
80/20
1.8631.863
316320Y1-086 C
80/20
0.2940.294
316388AE2-253 GEN
80/20
2.6322.632
936161AD2-022 C
Adder
9.455294117647068.037
935171AD1-152 C
80/20
1.8271.827
3151021BRUNSWICKG1
80/20
13.44613.446
3151041BRUNSWICKG3
80/20
13.44613.446
942341AE2-247 C
80/20
1.881.88
316246AF1-032 C
80/20
0.3780.378
316365AB2-100 C1
80/20
1.2911.291
3156083AA2-088SOLA
80/20
1.4051.405
957481AF2-042 C
80/20
78.71578.715
940431AE2-027 C
Adder
11.395294117647069.686
316294AC1-161 C
80/20
6.8246.824
944581AF1-123 C
80/20
61.95761.957
316185AD1-033 C
80/20
1.6481.648
916191Z1-068 C
80/20
0.0580.058
941101AE2-104 C
80/20
4.4074.407
943171AE2-346 C
80/20
0.2980.298
961941AG1-037 C
80/20
0.6730.673
3151391GASTONA
80/20
4.0664.066
934321AD1-056 C
Adder
8.332941176470597.083
934331AD1-057 C
Adder
4.6482352941176473.951
958211AF2-115 C
Adder
2.28235294117647051.94
3151531CLOVER1
80/20
17.9517.95
941031AE2-094 C
80/20
66.45566.455
3151081ELIZAR1
80/20
4.2584.258
316140AB2-099 C
80/20
0.1280.128
3152921DOMTR78
80/20
1.8181.818
316018AA1-139 ULT2
80/20
1.4491.449
933291AC2-141 C
80/20
41.90441.904
3150921YORKTN3
Adder
127.84235294117647108.666
3151361ROSEMG1
80/20
2.7122.712
3151151S HAMPT1
80/20
1.9741.974
964791AG1-342 C
Adder
4.4317647058823533.767
939191AE1-149 C
Adder
11.99058823529411710.192
3150981CHESPKA
80/20
0.5780.578
313526AB2-022 C
80/20
0.5040.504
316017AA1-139 ULT1
80/20
1.4491.449
934611AD1-087 C
80/20
1.7671.767
3152431Z1-086 GT3
80/20
17.27717.277
940641AE2-051 C
80/20
28.76428.764
3152331SURRY 2
80/20
30.82730.827
933981AD1-022 C
80/20
11.71411.714
316174AB2-169_C
80/20
1.3931.393
3156063AA2-053SOLA
80/20
1.9981.998
3151281ROARAP4
80/20
1.7351.735
938531AE1-072 C
80/20
23.60823.608
935161AD1-151 C
Adder
15.27058823529411812.98
958161AF2-110 C
80/20
1.7981.798
927021AC1-189 C
Adder
11.1952941176470599.516
926071AC1-086 C
80/20
28.07728.077
946281AF1-292 C
80/20
2.0562.056
964241AG1-285 C
Adder
14.80352941176470712.583
962561AG1-105 C
Adder
11.0694117647058839.409
3151091ELIZAR2
80/20
4.1834.183
316349AD2-085 C
80/20
4.3374.337
3151381ROSEMG2
80/20
1.271.27
960081AF2-299 C
80/20
2.4842.484
936171AD2-023 C
Adder
5.5152941176470584.688
936261AD2-033 C
Adder
14.72470588235294112.516
961791AG1-021 C
Adder
1.82588235294117651.552
938771AE1-103 C
80/20
3.8693.869
963041AG1-153 C
80/20
9.1419.141
3151051BRUNSWICKS1
80/20
27.93627.936
944011AF1-069 C
80/20
21.71321.713
944591AF1-124 C
80/20
62.17762.177
944601AF1-125 C
80/20
61.00261.002
3151101ELIZAR3
80/20
4.3114.311
941591AE2-156 C
80/20
23.83823.838
316317KELFORD C
80/20
0.4760.476
957861AF2-080 C
Adder
10.167058823529418.642
316023AB2-100 C2
80/20
1.2911.291
316129AC1-054 C
80/20
1.5891.589
316315AB2-025 C
80/20
0.5580.558
3138533PONTONDP
Adder
0.6764705882352940.575
3151541CLOVER2
80/20
17.78217.782
316316AC1-027 C
80/20
0.4210.421
3156021HOLLOMANSOL
80/20
2.4482.448
316011AB1-132 C OP
80/20
3.1053.105
3151371ROSEMS1
80/20
1.681.68
3137643SOCKMAN
80/20
0.9470.947
939411AE1-173 C
80/20
144.1144.1
3150991CHESPKB
80/20
0.9580.958
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.597.59
CBM South 2LTFEXP_CBM-S2->PJM
CBM
135.46135.46
CPLELTFEXP_CPLE->PJM
CLTF
15.91315.913
TVALTFEXP_TVA->PJM
CLTF
9.319.31
NYPJM->LTFIMP_NY
CLTF
2.5592.559
LGEELTFEXP_LGEE->PJM
CLTF
2.182.18
WECLTFEXP_WEC->PJM
CLTF
1.1331.133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.0655.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.38335.383
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
6.566.56
LAGNLTFEXP_LAGN->PJM
CLTF
11.74411.744
SIGELTFEXP_SIGE->PJM
CLTF
0.4150.415

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 563T576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.31 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:3793.69
MW Contribution:19.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
920692AA2-178 E
Adder
6.7435294117647065.732
917122Z2-027 E
50/50
2.3642.364
3146326AYDLETT TAP
50/50
2.4292.429
938532AE1-072 E
50/50
16.42416.424
3156056W1-029WIND
50/50
1.351.35
940551AE2-041 C
Adder
11.3211764705882359.623
935162AD1-151 E
Adder
15.29411764705882413
957832AF2-077 E
50/50
2.4692.469
943461AF1-017 C
Adder
2.17764705882352951.851
901082W1-029 E
50/50
55.655.6
958261AF2-120 C
Adder
9.1988235294117657.819
939191AE1-149 C
Adder
14.42941176470588312.265
934146AD1-041 E
Adder
5.5776470588235294.741
957601AF2-054 C
Adder
3.36117647058823542.857
316382AG1-145 C
50/50
0.6360.636
3150981CHESPKA
50/50
0.7870.787
943172AE2-346 E
Adder
0.90941176470588240.773
917332KELFORD E
Adder
2.42.04
925122AB2-169 E
Adder
8.6941176470588237.39
934522AD1-076 E
Adder
9.9670588235294128.472
940492AE2-034 E
Adder
5.057647058823534.299
962571AG1-106 C
Adder
3.71294117647058863.156
918492AA1-063AE OP
Adder
5.82352941176470654.95
957871AF2-081 C
50/50
17.9717.97
3145506HICKORY
50/50
3.9493.949
936591AD2-074 C
Adder
8.3435294117647067.092
3130536PAPERMILL
Adder
10.4988235294117648.924
939602AE1-190 E
Adder
2.23058823529411751.896
933292AC2-141 E
50/50
25.37725.377
934576AD1-082 E
Adder
6.4070588235294125.446
944602AF1-125 E
50/50
188.725188.725
943612AF1-032 E
50/50
1.6391.639
933981AD1-022 C
Adder
13.8411.764
900672V4-068 E
Adder
0.53882352941176470.458
938531AE1-072 C
50/50
31.50731.507
3145393UNCAMP
Adder
9.815294117647068.343
935161AD1-151 C
Adder
22.94117647058823619.5
932046AC2-012 E
50/50
23.72823.728
958161AF2-110 C
50/50
2.3482.348
933982AD1-022 E
Adder
7.5341176470588246.404
3145946PLYMOUTH TP
Adder
0.51882352941176470.441
313526AB2-022 C
50/50
0.6650.665
316017AA1-139 ULT1
50/50
1.9391.939
940641AE2-051 C
50/50
26.37426.374
926785AC1-164_E
50/50
29.20829.208
943471AF1-018 C
Adder
11.3211764705882359.623
3152331SURRY 2
50/50
52.5452.54
316084AB2-161 E
Adder
8.0411764705882356.835
316236AE1-162 C
50/50
0.5940.594
934521AD1-076 C
Adder
19.5552941176470616.622
934511AD1-075 C
Adder
13.46117647058823511.442
919692AA2-053 E OP
Adder
5.8800000000000014.998
923573AB1-173 E OP
Adder
4.3988235294117643.739
3145723EMPORIA
Adder
0.57058823529411760.485
920042AA2-088 E OP
Adder
16.1705882352941213.745
316321Z2-027 C
50/50
0.6380.638
919152AA1-139 E1
50/50
7.3487.348
939246AE1-155 E
Adder
12.80941176470588310.888
924814AB2-134 E
Adder
18.51882352941176515.741
316036AC1-147 C
50/50
0.6650.665
942342AE2-247 E
Adder
3.3247058823529412.826
316305AF2-043 C
50/50
0.6160.616
962572AG1-106 E
Adder
1.62470588235294121.381
957872AF2-081 E
50/50
7.7017.701
316018AA1-139 ULT2
50/50
1.9391.939
944631AF1-128 C
Adder
50.1435294117647142.622
936592AD2-074 E
Adder
13.61411764705882311.572
316160AE1-175 E
50/50
2.1482.148
926755AC1-161 E
50/50
25.37725.377
933291AC2-141 C
50/50
59.4559.45
3150921YORKTN3
50/50
222.183222.183
925522AC1-027 E
50/50
2.2062.206
941102AE2-104 E
50/50
9.159.15
3145256KINGFORK
50/50
1.7881.788
926072AC1-086 E
Adder
13.06352941176470511.104
960081AF2-299 C
Adder
2.12235294117647081.804
3145413WATKINS
Adder
1.09647058823529430.932
938771AE1-103 C
Adder
4.7799999999999994.063
963041AG1-153 C
Adder
7.662352941176476.513
944011AF1-069 C
Adder
18.13647058823529415.416
3150601CHESTF5
Adder
80.1388235294117768.118
964212AG1-282 E
Adder
1.91529411764705881.628
925332AB2-190 E
Adder
11.1811764705882369.504
962962AG1-145 E
50/50
2.6032.603
927226AC1-216 E
Adder
11.3047058823529419.609
944591AF1-124 C
50/50
84.02984.029
944601AF1-125 C
50/50
82.44182.441
3151101ELIZAR3
50/50
5.8665.866
941591AE2-156 C
50/50
32.45632.456
936666AD2-085 E
Adder
9.0611764705882357.702
961942AG1-037 E
Adder
0.50470588235294120.429
961941AG1-037 C
Adder
0.75764705882352950.644
316311AC2-079 C
Adder
9.3282352941176477.929
932596AC2-079 E
Adder
15.21999999999999912.937
918512AA1-065 E OP
Adder
8.4494117647058827.182
934502AD1-074 E
Adder
27.4094117647058823.298
934512AD1-075 E
Adder
6.8529411764705895.825
924516AB2-100 E1
Adder
3.87764705882352923.296
316320Y1-086 C
50/50
0.3880.388
919153AA1-139 E2
50/50
7.3487.348
316388AE2-253 GEN
50/50
3.5313.531
940642AE2-051 E
50/50
17.58317.583
963612AG1-210 E
Adder
1.39882352941176481.189
316159AE1-175 C
50/50
0.7040.704
942341AE2-247 C
Adder
2.40705882352941152.046
943462AF1-017 E
Adder
3.55294117647058853.02
958162AF2-110 E
50/50
3.7353.735
316246AF1-032 C
50/50
0.5030.503
3137643SOCKMAN
Adder
0.96588235294117640.821
913392Y1-086 E
50/50
3.893.89
316078AC2-138 E
Adder
1.30588235294117671.11
958262AF2-120 E
Adder
6.1329411764705885.213
966661AG1-536 C
Adder
7.9129411764705886.726
939612AE1-191 E
Adder
8.9247058823529427.586
957602AF2-054 E
Adder
2.24117647058823531.905
939411AE1-173 C
50/50
144.69144.69
934012AD1-025 E
Adder
14.63647058823529612.441
3151161SURRY 1
50/50
40.01440.014
3150991CHESPKB
50/50
1.3041.304
923263AB1-132 E OP
Adder
8.3529411764705897.1
940481AE2-033 C
Adder
21.4117647058823518.2
940482AE2-033 E
Adder
14.43529411764705912.27
940541AE2-040 C
Adder
3.79058823529411763.222
3138116ELKO L286
Adder
1.84941176470588251.572
963611AG1-210 C
Adder
0.93294117647058830.793
957831AF2-077 C
50/50
0.570.57
961611AG1-000B C
Adder
25.22588235294117721.442
316375AC2-012 C
50/50
2.4382.438
316072AD1-144 C
50/50
0.4940.494
316141AB2-099 E
Adder
0.37882352941176470.322
923994AB2-040_E
Adder
8.2482352941176477.011
316088AB2-174 E
Adder
8.6929411764705897.389
966662AG1-536 E
Adder
10.6329411764705889.038
962862AG1-135 E
Adder
5.985.083
943742AF1-042 E
Adder
7.1235294117647056.055
934392AD1-063 E
Adder
1.69764705882352951.443
316294AC1-161 C
50/50
9.6819.681
944581AF1-123 C
50/50
83.73183.731
316185AD1-033 C
50/50
2.2242.224
916191Z1-068 C
50/50
0.0790.079
941101AE2-104 C
50/50
5.7555.755
934501AD1-074 C
Adder
53.8447058823529445.768
924517AB2-100 E2
Adder
3.87764705882352923.296
3156116Z1-036WIND
50/50
1.1111.111
937226AE2-253 E
50/50
10.53510.535
3141813NORNECK
Adder
1.24235294117647071.056
962861AG1-135 C
Adder
8.9694117647058827.624
939192AE1-149 E
Adder
9.628.177
943741AF1-042 C
Adder
4.3658823529411773.711
939312AE1-162 E
50/50
2.4312.431
934065AD1-033 E
50/50
9.1079.107
944012AF1-069 E
Adder
7.04588235294117655.989
961952AG1-038 E
Adder
6.66352941176470555.664
961951AG1-038 C
Adder
4.8258823529411774.102
925865AC1-065 E
Adder
25.8294117647058821.955
3144216WINCHST
50/50
0.2410.241
316316AC1-027 C
50/50
0.5710.571
926071AC1-086 C
Adder
28.7023529411764724.397
916042Z1-036 E
50/50
48.46248.462
923832AB2-022 E
50/50
2.1962.196
938772AE1-103 E
Adder
6.6011764705882355.611
963042AG1-153 E
Adder
11.4941176470588249.77
316169AC1-164 GEN
50/50
65.01265.012
944592AF1-124 E
50/50
192.429192.429
944582AF1-123 E
50/50
191.735191.735
3151091ELIZAR2
50/50
5.6915.691
316349AD2-085 C
Adder
5.5541176470588244.721
935112AD1-144 E
50/50
1.661.66
923852AB2-025 E
Adder
1.53294117647058831.303
941031AE2-094 C
Adder
55.5058823529411847.18
941032AE2-094 E
Adder
24.8621.131
316076AC2-137 E
Adder
1.77294117647058821.507
964211AG1-282 C
Adder
2.87176470588235282.441
923842AB2-024 E
Adder
2.84000000000000032.414
316157AD2-030 E
Adder
1.88588235294117661.603
939412AE1-173 E
50/50
96.4696.46
3151081ELIZAR1
50/50
5.7935.793
926662AC1-147 E
50/50
2.3992.399
916192Z1-068 E
50/50
3.4083.408
957492AF2-043 E
50/50
2.5222.522
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.5566.556
CBM South 2LTFEXP_CBM-S2->PJM
CBM
111.34111.34
CPLELTFEXP_CPLE->PJM
CLTF
13.75813.758
TVALTFEXP_TVA->PJM
CLTF
6.4816.481
O66PJM->LTFIMP_O-066
CMTX_NF
27.4327.43
NYPJM->LTFIMP_NY
CLTF
2.0382.038
LGEELTFEXP_LGEE->PJM
CLTF
1.1621.162
WECLTFEXP_WEC->PJM
CLTF
0.5990.599
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.41628.416
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.24623.246
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.853.85
LAGNLTFEXP_LAGN->PJM
CLTF
8.2678.267
G-007PJM->LTFIMP_G-007
CMTX_NF
4.3044.304
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.92 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4555.56
MW Contribution:8.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
56.2176470588235347.785
961671AG1-007 C
Adder
1.44941176470588241.232
934621AD1-088 C
Adder
13.69294117647058911.639
942001AE2-212 C
Adder
3.73882352941176473.178
3150671DARBY 1
80/20
4.574.57
3150641CHESTS8
80/20
3.5113.511
962861AG1-135 C
Adder
9.3188235294117667.921
943741AF1-042 C
Adder
4.5552941176470593.872
934521AD1-076 C
Adder
20.41647058823529517.354
934511AD1-075 C
Adder
14.05411764705882411.946
316263AC1-034 C
Adder
10.102352941176478.587
316240AF1-291 C
Adder
3.78000000000000023.213
944641AF1-129 C
Adder
179.8423529411765152.866
3142296MT RD221
80/20
0.2170.217
316004AC1-112 C
80/20
0.5960.596
3150781HOPHCF2
80/20
4.324.32
3150761HOPPOLC
80/20
2.7172.717
316233AE1-074 C
Adder
4.08588235294117653.473
3150691DARBY 3
80/20
4.5924.592
940551AE2-041 C
Adder
12.16117647058823610.337
943461AF1-017 C
Adder
2.34941176470588251.997
316311AC2-079 C
Adder
9.984705882352948.487
316274AC1-208 C
Adder
14.04588235294117711.939
962571AG1-106 C
Adder
4.2647058823529413.625
3151311EDGECMA
Adder
23.6270588235294120.083
957871AF2-081 C
Adder
17.51647058823529314.889
3150651CHESTF6
Adder
32.7447058823529427.833
936591AD2-074 C
Adder
8.7058823529411787.4
316033AB2-134 GEN
80/20
3.7293.729
934011AD1-025 C
80/20
4.6114.611
940481AE2-033 C
Adder
25.6411764705882421.795
940541AE2-040 C
Adder
4.5529411764705883.87
927041AC1-191 C
Adder
16.39529411764705813.936
963611AG1-210 C
Adder
0.95764705882352940.814
961611AG1-000B C
80/20
28.34928.349
966621AG1-532 C
Adder
2.1752941176470591.849
3150771HOPHCF1
80/20
4.324.32
316159AE1-175 C
80/20
0.7120.712
942341AE2-247 C
Adder
2.5964705882352942.207
957481AF2-042 C
Adder
77.7682352941176466.103
940431AE2-027 C
Adder
22.58000000000000219.193
3150681DARBY 2
80/20
4.5764.576
316294AC1-161 C
80/20
8.8498.849
944581AF1-123 C
Adder
80.2141176470588368.182
941101AE2-104 C
Adder
5.8423529411764714.966
316336AC2-165 C
Adder
13.90823529411764711.822
940641AE2-051 C
Adder
26.97529411764705622.929
943471AF1-018 C
Adder
12.16117647058823610.337
3152331SURRY 2
80/20
45.81645.816
3151201GRAVEL4
80/20
4.5054.505
3151221GRAVEL6
80/20
4.54.5
3143096IRON208
80/20
0.7870.787
958261AF2-120 C
Adder
9.5447058823529418.113
939191AE1-149 C
Adder
18.60588235294117615.815
957601AF2-054 C
Adder
3.56235294117647073.028
316132AB2-190 C
80/20
7.3677.367
316382AG1-145 C
80/20
0.6420.642
961941AG1-037 C
Adder
0.82117647058823530.698
934321AD1-056 C
Adder
9.6541176470588248.206
934331AD1-057 C
Adder
5.3847058823529414.577
941031AE2-094 C
Adder
59.24117647058823650.355
3150831SPRUNCA
Adder
15.78000000000000113.413
3150841SPRUNCB
Adder
15.78000000000000113.413
966871AG1-558 C
Adder
4.0835294117647063.471
316075AC2-137 C
80/20
0.6870.687
964211AG1-282 C
Adder
2.9811764705882352.534
3150801HOPHCF4
80/20
6.5586.558
316369AC1-216 C
80/20
2.8462.846
944631AF1-128 C
80/20
71.31971.319
933291AC2-141 C
80/20
54.34454.344
3150921YORKTN3
80/20
215.99215.99
3151191GRAVEL3
80/20
4.4484.448
933981AD1-022 C
Adder
14.54588235294117712.364
938531AE1-072 C
Adder
30.76823529411764526.153
3142366NRTHEST
80/20
0.330.33
3150701DARBY 4
80/20
4.5974.597
3150731STONECA
80/20
12.27512.275
935161AD1-151 C
80/20
28.71928.719
958161AF2-110 C
Adder
2.38352941176470572.026
927021AC1-189 C
Adder
13.13058823529411811.161
926071AC1-086 C
Adder
32.9752941176470628.029
946281AF1-292 C
Adder
2.40117647058823552.041
964241AG1-285 C
Adder
17.71058823529411815.054
316169AC1-164 GEN
80/20
73.90473.904
316349AD2-085 C
Adder
5.9917647058823535.093
960081AF2-299 C
Adder
2.92.465
936261AD2-033 C
Adder
18.25529411764705815.517
938771AE1-103 C
Adder
4.9788235294117654.232
963041AG1-153 C
Adder
8.3011764705882357.056
944011AF1-069 C
Adder
19.35647058823529316.453
3150621CHESTS7
80/20
3.1823.182
3150601CHESTF5
80/20
113.981113.981
944591AF1-124 C
Adder
80.4988235294117868.424
944601AF1-125 C
Adder
78.9788235294117767.132
941591AE2-156 C
Adder
31.64823529411764726.901
957861AF2-080 C
Adder
11.92588235294117810.137
3150631CHESTG8
80/20
6.826.82
3150611CHESTG7
80/20
6.936.93
3150791HOPHCF3
80/20
4.324.32
961951AG1-038 C
Adder
5.035294117647064.28
3144216WINCHST
80/20
0.2370.237
3137643SOCKMAN
Adder
1.1117647058823530.945
316312AB1-027 C
80/20
0.9570.957
966661AG1-536 C
Adder
8.2105882352941186.979
939411AE1-173 C
Adder
145.74235294117648123.881
3151161SURRY 1
80/20
43.78743.787
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4058.405
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.686156.686
CPLELTFEXP_CPLE->PJM
CLTF
17.60717.607
TVALTFEXP_TVA->PJM
CLTF
12.412.4
NYPJM->LTFIMP_NY
CLTF
4.1344.134
LGEELTFEXP_LGEE->PJM
CLTF
3.3563.356
WECLTFEXP_WEC->PJM
CLTF
1.7261.726
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.27284.272
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.64648.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5619.561
LAGNLTFEXP_LAGN->PJM
CLTF
15.45715.457
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.48 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5586.28
MW Contribution:20.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
920692AA2-178 E
Adder
6.9352941176470585.895
966622AG1-532 E
Adder
1.45058823529411771.233
917122Z2-027 E
Adder
2.3352941176470591.985
3146326AYDLETT TAP
Adder
2.3717647058823532.016
938532AE1-072 E
Adder
16.0329411764705913.628
316233AE1-074 C
Adder
4.08588235294117653.473
927042AC1-191 E
Adder
8.1611764705882366.937
943172AE2-346 E
Adder
0.98588235294117640.838
917332KELFORD E
Adder
2.63882352941176462.243
925122AB2-169 E
Adder
9.3470588235294127.945
934522AD1-076 E
Adder
10.4035294117647078.843
940492AE2-034 E
Adder
5.2011764705882364.421
962571AG1-106 C
Adder
4.2647058823529413.625
918492AA1-063AE OP
Adder
6.5082352941176485.532
957871AF2-081 C
Adder
17.5105882352941214.884
3145506HICKORY
Adder
3.83058823529411763.256
946262AF1-291 E
Adder
2.5188235294117652.141
3150691DARBY 3
50/50
4.5894.589
940551AE2-041 C
Adder
12.15411764705882410.331
935162AD1-151 E
Adder
19.1376470588235316.267
957832AF2-077 E
Adder
2.49294117647058842.119
943461AF1-017 C
Adder
2.34941176470588251.997
316311AC2-079 C
Adder
9.9811764705882358.484
932596AC2-079 E
Adder
16.2847058823529413.842
3150651CHESTF6
Adder
32.7305882352941227.821
936591AD2-074 C
Adder
8.77.395
3130536PAPERMILL
Adder
11.342352941176479.641
939602AE1-190 E
Adder
2.40470588235294122.044
933292AC2-141 E
Adder
23.1894117647058819.711
934576AD1-082 E
Adder
7.6470588235294126.5
944602AF1-125 E
Adder
180.73058823529414153.621
918512AA1-065 E OP
Adder
9.0517647058823547.694
934502AD1-074 E
Adder
28.60941176470588624.318
934512AD1-075 E
Adder
7.1529411764705896.08
924516AB2-100 E1
Adder
4.5505882352941183.868
966621AG1-532 C
Adder
2.1752941176470591.849
919153AA1-139 E2
Adder
7.166.086
940642AE2-051 E
Adder
17.97882352941176615.282
926412AC1-112 E
50/50
2.0462.046
316159AE1-175 C
50/50
0.7110.711
923263AB1-132 E OP
Adder
9.595294117647068.156
940481AE2-033 C
Adder
25.63411764705882621.789
940482AE2-033 E
Adder
17.28117647058823514.689
940541AE2-040 C
Adder
4.5517647058823533.869
927041AC1-191 C
Adder
16.38352941176470513.926
3138116ELKO L286
50/50
2.5282.528
961611AG1-000B C
Adder
28.33647058823529424.086
901082W1-029 E
Adder
55.2529411764705946.965
3143316POE
Adder
2.31058823529411761.964
939191AE1-149 C
Adder
18.59882352941176415.809
934146AD1-041 E
Adder
6.0129411764705885.111
957601AF2-054 C
Adder
3.56117647058823563.027
316382AG1-145 C
50/50
0.6420.642
943612AF1-032 E
Adder
1.61764705882352941.375
933982AD1-022 E
Adder
7.9164705882352956.729
3145946PLYMOUTH TP
Adder
0.540.459
940641AE2-051 C
Adder
26.96705882352941322.922
926785AC1-164_E
50/50
33.18433.184
943471AF1-018 C
Adder
12.15411764705882410.331
3152331SURRY 2
50/50
45.79645.796
316084AB2-161 E
Adder
9.597647058823538.158
933981AD1-022 C
Adder
14.54117647058823512.36
900672V4-068 E
Adder
0.58235294117647060.495
938531AE1-072 C
Adder
30.75647058823529526.143
3145393UNCAMP
Adder
10.2788235294117658.737
3142366NRTHEST
50/50
0.330.33
3150701DARBY 4
50/50
4.5944.594
3150731STONECA
Adder
12.26941176470588210.429
935161AD1-151 C
Adder
28.70588235294117424.4
932046AC2-012 E
Adder
23.15176470588235319.679
958161AF2-110 C
Adder
2.38352941176470572.026
962572AG1-106 E
Adder
1.86588235294117651.586
957872AF2-081 E
Adder
7.50470588235294046.379
938552AE1-074 E
Adder
2.05764705882352941.749
944631AF1-128 C
50/50
71.28371.283
936592AD2-074 E
Adder
14.19411764705882312.065
316160AE1-175 E
50/50
2.1682.168
926755AC1-161 E
Adder
23.1894117647058819.711
933291AC2-141 C
Adder
54.3223529411764746.174
3150921YORKTN3
Adder
215.8894117647059183.506
925522AC1-027 E
Adder
2.14588235294117661.824
941102AE2-104 E
Adder
9.2858823529411767.893
3145256KINGFORK
Adder
1.78823529411764711.52
934521AD1-076 C
Adder
20.41176470588235517.35
934511AD1-075 C
Adder
14.05058823529411811.943
919692AA2-053 E OP
Adder
6.6552941176470595.657
923573AB1-173 E OP
Adder
5.11176470588235254.345
3145723EMPORIA
Adder
0.66941176470588230.569
920042AA2-088 E OP
Adder
17.4414.824
919152AA1-139 E1
Adder
7.166.086
316240AF1-291 C
Adder
3.7788235294117653.212
944641AF1-129 C
Adder
179.7623529411765152.798
3142296MT RD221
50/50
0.2170.217
316004AC1-112 C
50/50
0.5960.596
924814AB2-134 E
Adder
22.5082352941176519.132
942342AE2-247 E
Adder
3.58470588235294143.047
926071AC1-086 C
Adder
32.9682352941176528.023
946281AF1-292 C
Adder
2.40117647058823552.041
960082AF2-299 E
Adder
1.93294117647058841.643
916042Z1-036 E
Adder
48.916470588235341.579
923832AB2-022 E
Adder
2.16117647058823531.837
938772AE1-103 E
Adder
6.8741176470588235.843
963042AG1-153 E
Adder
12.44941176470588410.582
930122AB1-027 E
50/50
2.5162.516
316169AC1-164 GEN
50/50
73.86273.862
944592AF1-124 E
Adder
184.2764705882353156.635
926072AC1-086 E
Adder
15.0047058823529412.754
960081AF2-299 C
Adder
2.92.465
3145413WATKINS
Adder
1.15882352941176480.985
938771AE1-103 C
Adder
4.9776470588235294.231
963041AG1-153 C
Adder
8.37.055
944011AF1-069 C
Adder
19.35294117647058716.45
3150621CHESTS7
50/50
3.183.18
3150601CHESTF5
50/50
113.923113.923
925332AB2-190 E
Adder
14.35882352941176512.205
962962AG1-145 E
50/50
2.6282.628
927226AC1-216 E
Adder
13.74117647058823411.68
944591AF1-124 C
Adder
80.4682352941176568.398
944601AF1-125 C
Adder
78.9482352941176467.106
941591AE2-156 C
Adder
31.63647058823529426.891
936666AD2-085 E
Adder
9.7729411764705898.307
961942AG1-037 E
Adder
0.54705882352941180.465
961941AG1-037 C
Adder
0.82117647058823530.698
923852AB2-025 E
Adder
1.84117647058823521.565
941031AE2-094 C
Adder
59.2294117647058850.345
941032AE2-094 E
Adder
26.52705882352941222.548
3150831SPRUNCA
Adder
15.77411764705882313.408
3150841SPRUNCB
Adder
15.77411764705882313.408
966872AG1-558 E
Adder
2.0552941176470591.747
966871AG1-558 C
Adder
4.083.468
316076AC2-137 E
50/50
2.4242.424
316075AC2-137 C
50/50
0.6870.687
923842AB2-024 E
Adder
3.07294117647058852.612
316157AD2-030 E
Adder
1.99764705882352931.698
939412AE1-173 E
Adder
97.132941176470682.563
926662AC1-147 E
Adder
2.34000000000000031.989
916192Z1-068 E
Adder
3.3141176470588242.817
957492AF2-043 E
Adder
2.48941176470588272.116
942341AE2-247 C
Adder
2.5964705882352942.207
943462AF1-017 E
Adder
3.8317647058823533.257
958162AF2-110 E
Adder
3.79058823529411763.222
3137643SOCKMAN
Adder
1.1117647058823530.945
913392Y1-086 E
Adder
3.8282352941176473.254
940432AE2-027 E
Adder
15.04705882352941212.79
316312AB1-027 C
50/50
0.9560.956
939612AE1-191 E
Adder
9.628.177
957602AF2-054 E
Adder
2.37411764705882342.018
939411AE1-173 C
Adder
145.69882352941175123.844
934012AD1-025 E
Adder
17.78941176470588215.121
316141AB2-099 E
Adder
0.410588235294117640.349
923994AB2-040_E
Adder
9.5835294117647068.146
316088AB2-174 E
Adder
10.1435294117647078.622
957481AF2-042 C
Adder
64.6541176470588354.956
942002AE2-212 E
Adder
2.49058823529411782.117
940431AE2-027 C
Adder
22.57058823529411719.185
3150681DARBY 2
50/50
4.5734.573
943742AF1-042 E
Adder
7.42705882352941156.313
934392AD1-063 E
Adder
1.8235294117647061.55
944581AF1-123 C
Adder
80.1835294117647168.156
941101AE2-104 C
Adder
5.8411764705882354.965
934501AD1-074 C
Adder
56.2023529411764747.772
924517AB2-100 E2
Adder
4.5505882352941183.868
937226AE2-253 E
Adder
10.2482352941176478.711
942001AE2-212 C
Adder
3.73647058823529443.176
3150671DARBY 1
50/50
4.5674.567
3150641CHESTS8
50/50
3.5093.509
939192AE1-149 E
Adder
12.39882352941176410.539
943741AF1-042 C
Adder
4.5517647058823533.869
939312AE1-162 E
Adder
2.54117647058823562.16
934065AD1-033 E
Adder
8.8270588235294137.503
946282AF1-292 E
Adder
1.61.36
944012AF1-069 E
Adder
7.5176470588235296.39
3150631CHESTG8
50/50
6.8166.816
3150611CHESTG7
50/50
6.9276.927
961952AG1-038 E
Adder
6.9482352941176475.906
961951AG1-038 C
Adder
5.0317647058823534.277
925865AC1-065 E
Adder
28.22117647058823723.988
944582AF1-123 E
Adder
183.61176470588234156.07
316349AD2-085 C
Adder
5.9894117647058835.091
935112AD1-144 E
Adder
1.66000000000000011.411
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.4068.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
156.721156.721
CPLELTFEXP_CPLE->PJM
CLTF
17.60917.609
TVALTFEXP_TVA->PJM
CLTF
12.40612.406
O66PJM->LTFIMP_O-066
CMTX_NF
58.60758.607
NYPJM->LTFIMP_NY
CLTF
4.1384.138
LGEELTFEXP_LGEE->PJM
CLTF
3.3583.358
WECLTFEXP_WEC->PJM
CLTF
1.7271.727
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.33484.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.67448.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
9.5679.567
LAGNLTFEXP_LAGN->PJM
CLTF
15.46415.464
G-007PJM->LTFIMP_G-007
CMTX_NF
9.2239.223
SIGELTFEXP_SIGE->PJM
CLTF
0.620.62

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4112.5
MW Contribution:7.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
48.0341176470588340.829
961671AG1-007 C
Adder
1.22941176470588221.045
934621AD1-088 C
Adder
11.2658823529411789.576
942001AE2-212 C
Adder
3.01764705882352932.565
3150641CHESTS8
80/20
2.8432.843
962861AG1-135 C
Adder
7.9105882352941186.724
943741AF1-042 C
Adder
3.87058823529411773.29
940551AE2-041 C
Adder
10.3670588235294128.812
943461AF1-017 C
Adder
1.99058823529411751.692
316311AC2-079 C
Adder
8.4682352941176487.198
316274AC1-208 C
Adder
11.86588235294117810.086
962571AG1-106 C
Adder
3.5905882352941183.052
3151311EDGECMA
Adder
20.00352941176470617.003
957871AF2-081 C
80/20
15.09215.092
3150651CHESTF6
Adder
26.14823529411764722.226
936591AD2-074 C
Adder
7.3964705882352946.287
316033AB2-134 GEN
80/20
3.0983.098
934011AD1-025 C
80/20
3.8313.831
940481AE2-033 C
Adder
21.37647058823529618.17
940541AE2-040 C
Adder
3.7941176470588243.225
927041AC1-191 C
Adder
13.58823529411764911.55
963611AG1-210 C
Adder
0.81058823529411760.689
957831AF2-077 C
80/20
0.4940.494
961611AG1-000B C
80/20
23.84623.846
316375AC2-012 C
80/20
2.0492.049
316072AD1-144 C
80/20
0.4250.425
966621AG1-532 C
Adder
1.81764705882352941.545
316320Y1-086 C
80/20
0.3290.329
316388AE2-253 GEN
80/20
2.9612.961
316159AE1-175 C
80/20
0.6130.613
942341AE2-247 C
Adder
2.21.87
316246AF1-032 C
80/20
0.4270.427
957481AF2-042 C
Adder
64.7188235294117655.011
3152191CUNINGD
80/20
17.70617.706
940431AE2-027 C
Adder
18.18117647058823715.454
316294AC1-161 C
80/20
7.7077.707
944581AF1-123 C
80/20
69.29269.292
316185AD1-033 C
80/20
1.8591.859
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
55
961941AG1-037 C
Adder
0.69764705882352940.593
934321AD1-056 C
Adder
8.1541176470588246.931
934331AD1-057 C
Adder
4.5482352941176483.866
941031AE2-094 C
Adder
50.196470588235342.667
3150831SPRUNCA
Adder
10.6141176470588259.022
3150841SPRUNCB
Adder
10.6141176470588259.022
966871AG1-558 C
Adder
3.3847058823529412.877
316075AC2-137 C
80/20
0.5730.573
964211AG1-282 C
Adder
2.5270588235294122.148
316369AC1-216 C
80/20
2.3642.364
3151081ELIZAR1
80/20
4.8584.858
934521AD1-076 C
Adder
17.4447058823529414.828
934511AD1-075 C
Adder
12.00823529411764810.207
316263AC1-034 C
Adder
8.5517647058823547.269
316321Z2-027 C
80/20
0.5420.542
316240AF1-291 C
Adder
3.02705882352941162.573
316018AA1-139 ULT2
80/20
1.6281.628
3152181CUNINGC
80/20
7.9167.916
944631AF1-128 C
80/20
57.75157.751
933291AC2-141 C
80/20
47.32947.329
3150921YORKTN3
80/20
186.63186.63
3151191GRAVEL3
80/20
3.7583.758
958261AF2-120 C
Adder
8.16.885
939191AE1-149 C
Adder
15.33294117647058713.033
957601AF2-054 C
Adder
3.03647058823529432.581
316382AG1-145 C
80/20
0.5540.554
3151171GRAVELC
80/20
1.2921.292
3150981CHESPKA
80/20
0.6610.661
313526AB2-022 C
80/20
0.5630.563
316017AA1-139 ULT1
80/20
1.6281.628
940641AE2-051 C
Adder
23.00823529411764719.557
943471AF1-018 C
Adder
10.3670588235294128.812
3152331SURRY 2
80/20
40.26840.268
3151201GRAVEL4
80/20
3.8063.806
3151211GRAVEL5
80/20
3.7583.758
3151221GRAVEL6
80/20
3.8023.802
316236AE1-162 C
80/20
0.5280.528
933981AD1-022 C
Adder
12.41647058823529510.554
938531AE1-072 C
80/20
26.50226.502
3150731STONECA
Adder
9.9858823529411778.488
935161AD1-151 C
80/20
23.75423.754
958161AF2-110 C
80/20
2.042.04
944641AF1-129 C
Adder
143.61529411764707122.073
3142296MT RD221
80/20
0.180.18
316004AC1-112 C
80/20
0.5060.506
316036AC1-147 C
80/20
0.5590.559
316305AF2-043 C
80/20
0.5230.523
927021AC1-189 C
Adder
11.1482352941176499.476
926071AC1-086 C
Adder
27.76352941176470823.599
946281AF1-292 C
Adder
2.00588235294117641.705
316169AC1-164 GEN
80/20
63.00863.008
3151091ELIZAR2
80/20
4.7734.773
316349AD2-085 C
Adder
5.0752941176470594.314
960081AF2-299 C
Adder
2.4235294117647062.06
938771AE1-103 C
Adder
4.2458823529411773.609
963041AG1-153 C
Adder
7.0223529411764725.969
944011AF1-069 C
Adder
16.40117647058823613.941
3150621CHESTS7
80/20
2.5762.576
3150601CHESTF5
80/20
92.29692.296
944591AF1-124 C
80/20
69.53869.538
944601AF1-125 C
80/20
68.22568.225
3151101ELIZAR3
80/20
4.9194.919
941591AE2-156 C
80/20
27.25627.256
957861AF2-080 C
Adder
10.1247058823529418.606
3152161CUNINGA
80/20
7.9167.916
3152171CUNINGB
80/20
7.9167.916
3150631CHESTG8
80/20
5.5225.522
3150611CHESTG7
80/20
5.6125.612
961951AG1-038 C
Adder
4.277647058823533.636
3144216WINCHST
80/20
0.2040.204
316316AC1-027 C
80/20
0.4790.479
3137643SOCKMAN
Adder
0.93411764705882360.794
316312AB1-027 C
80/20
0.8120.812
966661AG1-536 C
Adder
6.96705882352941155.922
939411AE1-173 C
Adder
124.68470588235294105.982
3151161SURRY 1
80/20
36.99336.993
3150991CHESPKB
80/20
1.0961.096
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.1467.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
133.887133.887
CPLELTFEXP_CPLE->PJM
CLTF
14.96914.969
TVALTFEXP_TVA->PJM
CLTF
10.74810.748
NYPJM->LTFIMP_NY
CLTF
3.5973.597
LGEELTFEXP_LGEE->PJM
CLTF
2.952.95
WECLTFEXP_WEC->PJM
CLTF
1.5171.517
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.17274.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.32542.325
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.3698.369
LAGNLTFEXP_LAGN->PJM
CLTF
13.38813.388
SIGELTFEXP_SIGE->PJM
CLTF
0.5440.544

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.93 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4252.57
MW Contribution:11.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
920692AA2-178 E
Adder
3.6352941176470593.09
966622AG1-532 E
Adder
0.780.663
917122Z2-027 E
Adder
1.21294117647058821.031
3146326AYDLETT TAP
Adder
1.22941176470588221.045
938532AE1-072 E
Adder
8.3117647058823547.065
316233AE1-074 C
Adder
2.25058823529411761.913
927042AC1-191 E
Adder
4.4917647058823533.818
3150691DARBY 3
50/50
2.4352.435
940551AE2-041 C
Adder
6.3964705882352955.437
935162AD1-151 E
Adder
10.0317647058823528.527
957832AF2-077 E
Adder
1.29764705882352941.103
943461AF1-017 C
Adder
1.22941176470588221.045
316311AC2-079 C
Adder
5.2200000000000014.437
932596AC2-079 E
Adder
8.517647058823537.24
940481AE2-033 C
Adder
13.74117647058823411.68
940482AE2-033 E
Adder
9.2635294117647067.874
940541AE2-040 C
Adder
2.442.074
901082W1-029 E
Adder
28.74235294117647424.431
3143316POE
Adder
1.23411764705882351.049
939191AE1-149 C
Adder
9.8564705882352958.378
934146AD1-041 E
Adder
3.17647058823529442.7
957601AF2-054 C
Adder
1.8835294117647061.601
943172AE2-346 E
Adder
0.52235294117647060.444
934522AD1-076 E
Adder
5.4705882352941194.65
940492AE2-034 E
Adder
2.72588235294117662.317
918492AA1-063AE OP
Adder
3.47058823529411782.95
957871AF2-081 C
Adder
9.0741176470588247.713
3145506HICKORY
Adder
1.98352941176470581.686
946262AF1-291 E
Adder
1.34470588235294121.143
3150651CHESTF6
Adder
17.46352941176470714.844
3150461FOUR RIVERD
50/50
2.9592.959
3150441FOUR RIVERB
50/50
3.0033.003
936591AD2-074 C
Adder
4.7717647058823534.056
3130536PAPERMILL
Adder
5.95411764705882355.061
939602AE1-190 E
Adder
1.27058823529411781.08
933292AC2-141 E
Adder
11.89764705882352810.113
934576AD1-082 E
Adder
4.0317647058823533.427
944602AF1-125 E
Adder
93.4294117647058979.415
943612AF1-032 E
Adder
0.840.714
933982AD1-022 E
Adder
4.1682352941176483.543
3145946PLYMOUTH TP
Adder
0.283529411764705860.241
316336AC2-165 C
Adder
8.2082352941176486.977
3150481FOUR RIVERF
50/50
3.6143.614
940641AE2-051 C
Adder
14.38235294117647112.225
926785AC1-164_E
Adder
17.0152941176470614.463
933981AD1-022 C
Adder
7.6564705882352946.508
900672V4-068 E
Adder
0.308235294117647050.262
938531AE1-072 C
Adder
15.94470588235294213.553
3145393UNCAMP
Adder
5.3964705882352944.587
315051AA1-145 CT1
50/50
4.7834.783
3142366NRTHEST
50/50
0.1760.176
3150701DARBY 4
50/50
2.4382.438
3150731STONECA
Adder
6.46823529411764755.498
935161AD1-151 C
Adder
15.04823529411764812.791
932046AC2-012 E
Adder
11.9823529411764710.185
958161AF2-110 C
Adder
1.24117647058823531.055
943471AF1-018 C
Adder
6.3964705882352955.437
316084AB2-161 E
Adder
5.06000000000000054.301
957872AF2-081 E
Adder
3.88941176470588263.306
938562AE1-075 E
Adder
0.87764705882352940.746
3152251N ANNA1
50/50
28.6128.61
938552AE1-074 E
Adder
1.13294117647058810.963
934521AD1-076 C
Adder
10.7329411764705889.123
934511AD1-075 C
Adder
7.38823529411764756.28
3145723EMPORIA
Adder
0.360.306
920042AA2-088 E OP
Adder
9.2247058823529417.841
919152AA1-139 E1
Adder
3.71058823529411753.154
316240AF1-291 C
Adder
2.01647058823529421.714
944641AF1-129 C
Adder
95.9141176470588381.527
3150451FOUR RIVERC
50/50
3.6693.669
3142296MT RD221
50/50
0.1170.117
316004AC1-112 C
50/50
0.3130.313
924814AB2-134 E
Adder
11.78117647058823510.014
942342AE2-247 E
Adder
1.87647058823529411.595
3150471FOUR RIVERE
50/50
2.9592.959
315052AA1-145 CT2
50/50
4.7814.781
944631AF1-128 C
Adder
37.3682352941176531.763
936592AD2-074 E
Adder
7.7847058823529426.617
316160AE1-175 E
Adder
1.11058823529411770.944
926755AC1-161 E
Adder
11.89764705882352810.113
933291AC2-141 C
Adder
27.87176470588235223.691
3150921YORKTN3
Adder
110.8188235294117694.196
925522AC1-027 E
Adder
1.11058823529411770.944
941102AE2-104 E
Adder
4.8364705882352944.111
3145256KINGFORK
Adder
0.92823529411764720.789
960081AF2-299 C
Adder
1.56117647058823541.327
3145413WATKINS
Adder
0.60941176470588240.518
938771AE1-103 C
Adder
2.60941176470588232.218
963041AG1-153 C
Adder
4.4858823529411773.813
944011AF1-069 C
Adder
10.437647058823538.872
966881AG1-559 C
50/50
2.2942.294
3150601CHESTF5
Adder
59.7211764705882350.763
925332AB2-190 E
Adder
7.537647058823536.407
962962AG1-145 E
Adder
1.34588235294117631.144
927226AC1-216 E
Adder
7.19176470588235356.113
944591AF1-124 C
Adder
41.5988235294117735.359
944601AF1-125 C
Adder
40.81294117647059534.691
941591AE2-156 C
Adder
16.3729411764705913.917
936666AD2-085 E
Adder
5.11411764705882454.347
961942AG1-037 E
Adder
0.290588235294117650.247
961941AG1-037 C
Adder
0.435294117647058830.37
923852AB2-025 E
Adder
0.98705882352941180.839
923862AB2-026 E
Adder
1.02941176470588250.875
941031AE2-094 C
Adder
31.94588235294117627.154
941032AE2-094 E
Adder
14.3082352941176512.162
3150831SPRUNCA
Adder
8.5294117647058827.25
3150841SPRUNCB
Adder
8.5294117647058827.25
966872AG1-558 E
Adder
1.1317647058823530.962
966871AG1-558 C
Adder
2.24588235294117671.909
316076AC2-137 E
50/50
1.2591.259
316075AC2-137 C
50/50
0.3570.357
923842AB2-024 E
Adder
1.61176470588235321.37
316157AD2-030 E
Adder
1.05647058823529430.898
939412AE1-173 E
Adder
51.40235294117647443.692
926662AC1-147 E
Adder
1.2117647058823531.03
916192Z1-068 E
Adder
1.71529411764705891.458
957492AF2-043 E
Adder
1.29176470588235311.098
918512AA1-065 E OP
Adder
4.7847058823529424.067
934502AD1-074 E
Adder
15.04470588235294112.788
934512AD1-075 E
Adder
3.76117647058823533.197
924516AB2-100 E1
Adder
2.4388235294117652.073
966621AG1-532 C
Adder
1.17058823529411770.995
919153AA1-139 E2
Adder
3.71058823529411753.154
226704AOCX4-046 E
Adder
-2.8423529411764705-2.416
3152261N ANNA2
50/50
28.62228.622
940642AE2-051 E
Adder
9.5882352941176498.15
926412AC1-112 E
50/50
1.0751.075
942341AE2-247 C
Adder
1.35882352941176481.155
943462AF1-017 E
Adder
2.00588235294117641.705
958162AF2-110 E
Adder
1.97411764705882351.678
913392Y1-086 E
Adder
1.9870588235294121.689
933502AC2-165 E
Adder
6.177647058823535.251
940432AE2-027 E
Adder
8.0188235294117656.816
316312AB1-027 C
50/50
0.5020.502
939612AE1-191 E
Adder
5.0823529411764714.32
957602AF2-054 E
Adder
1.2552941176470591.067
939411AE1-173 C
Adder
77.103529411764765.538
934012AD1-025 E
Adder
9.3117647058823547.915
927041AC1-191 C
Adder
9.0164705882352937.664
3138116ELKO L286
50/50
1.3131.313
961611AG1-000B C
Adder
14.76705882352941212.552
316141AB2-099 E
Adder
0.217647058823529420.185
923994AB2-040_E
Adder
1.6270588235294121.383
316088AB2-174 E
Adder
5.4517647058823534.634
942002AE2-212 E
Adder
1.33058823529411761.131
940431AE2-027 C
Adder
12.02823529411764810.224
3150681DARBY 2
50/50
2.4262.426
962862AG1-135 E
Adder
3.43764705882352972.922
943742AF1-042 E
Adder
4.07294117647058853.462
934392AD1-063 E
Adder
0.960.816
944581AF1-123 C
Adder
41.45176470588235435.234
941101AE2-104 C
Adder
3.04235294117647072.586
934501AD1-074 C
Adder
29.5529411764705925.12
924517AB2-100 E2
Adder
2.4388235294117652.073
937226AE2-253 E
Adder
5.30941176470588254.513
226896D-009
Adder
-1.4576470588235295-1.239
958502AF2-144 E
Adder
1.0117647058823530.86
942001AE2-212 C
Adder
1.99647058823529421.697
3150671DARBY 1
50/50
2.4232.423
962861AG1-135 C
Adder
5.1564705882352944.383
939192AE1-149 E
Adder
6.5717647058823535.586
943741AF1-042 C
Adder
2.4964705882352942.122
939312AE1-162 E
Adder
1.31882352941176471.121
934065AD1-033 E
Adder
4.5682352941176473.883
946282AF1-292 E
Adder
0.86117647058823530.732
944012AF1-069 E
Adder
4.0552941176470593.447
939262AE1-157 E
Adder
7.2070588235294136.126
3150431FOUR RIVERA
50/50
3.0033.003
961952AG1-038 E
Adder
3.81058823529411763.239
961951AG1-038 C
Adder
2.7588235294117652.345
925865AC1-065 E
Adder
14.8929411764705912.659
946281AF1-292 C
Adder
1.29176470588235311.098
960082AF2-299 E
Adder
1.040.884
916042Z1-036 E
Adder
25.53647058823529321.706
923832AB2-022 E
Adder
1.12235294117647060.954
938772AE1-103 E
Adder
3.60352941176470633.063
963042AG1-153 E
Adder
6.7294117647058825.72
939261AE1-157 C
Adder
13.28588235294117611.293
966882AG1-559 E
50/50
1.1551.155
930122AB1-027 E
50/50
1.3221.322
316169AC1-164 GEN
Adder
37.8729411764705932.192
944592AF1-124 E
Adder
95.2635294117647180.974
944582AF1-123 E
Adder
94.9280.682
316349AD2-085 C
Adder
3.13411764705882372.664
935112AD1-144 E
Adder
0.86117647058823530.732
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.6074.607
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.84786.847
CPLELTFEXP_CPLE->PJM
CLTF
9.659.65
TVALTFEXP_TVA->PJM
CLTF
7.1437.143
O66PJM->LTFIMP_O-066
CMTX_NF
44.79944.799
NYPJM->LTFIMP_NY
CLTF
3.113.11
LGEELTFEXP_LGEE->PJM
CLTF
2.0262.026
WECLTFEXP_WEC->PJM
CLTF
1.0481.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.34851.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.44428.444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.7125.712
LAGNLTFEXP_LAGN->PJM
CLTF
8.98.9
G-007PJM->LTFIMP_G-007
CMTX_NF
7.0597.059
SIGELTFEXP_SIGE->PJM
CLTF
0.3720.372

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.32 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3230.79
MW Contribution:4.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
28.28352941176470724.041
934621AD1-088 C
Adder
7.1611764705882356.087
942001AE2-212 C
Adder
1.92117647058823531.633
3150671DARBY 1
80/20
2.3512.351
3150641CHESTS8
80/20
1.7811.781
962861AG1-135 C
Adder
5.0788235294117654.317
943741AF1-042 C
Adder
2.45411764705882352.086
3150381LDYSMT2
80/20
4.3034.303
316233AE1-074 C
Adder
2.1552941176470591.832
3150691DARBY 3
80/20
2.3622.362
940551AE2-041 C
Adder
6.2364705882352955.301
943461AF1-017 C
Adder
1.18117647058823531.004
316311AC2-079 C
Adder
5.0141176470588234.262
962571AG1-106 C
Adder
2.17764705882352951.851
957871AF2-081 C
Adder
8.7129411764705887.406
3150651CHESTF6
Adder
16.84705882352941214.32
3150461FOUR RIVERD
80/20
2.9092.909
3150441FOUR RIVERB
80/20
2.9522.952
3150861SPRUNCD
80/20
0.1470.147
936591AD2-074 C
Adder
4.6894117647058823.986
966621AG1-532 C
Adder
1.1164705882352940.949
3152261N ANNA2
80/20
26.0926.09
942341AE2-247 C
Adder
1.30470588235294121.109
940481AE2-033 C
Adder
13.13529411764705811.165
940541AE2-040 C
Adder
2.33294117647058831.983
3150371LDYSMT1
80/20
4.2494.249
927041AC1-191 C
80/20
8.8178.817
963611AG1-210 C
Adder
0.53882352941176470.458
961611AG1-000B C
Adder
14.23176470588235412.097
957481AF2-042 C
Adder
40.39647058823529634.337
3150401LDYSMT4
80/20
4.4254.425
940431AE2-027 C
Adder
11.5988235294117659.859
3150681DARBY 2
80/20
2.3542.354
944581AF1-123 C
Adder
39.80941176470588533.838
941101AE2-104 C
Adder
2.92000000000000042.482
934521AD1-076 C
Adder
10.2717647058823538.731
934511AD1-075 C
Adder
7.0705882352941176.01
3150411LDYSMT5
80/20
4.4394.439
316240AF1-291 C
Adder
1.94470588235294131.653
944641AF1-129 C
Adder
92.5282352941176578.649
3150451FOUR RIVERC
80/20
3.6073.607
3142296MT RD221
80/20
0.1140.114
316004AC1-112 C
80/20
0.3050.305
3152251N ANNA1
80/20
26.07926.079
3150471FOUR RIVERE
80/20
2.9092.909
315052AA1-145 CT2
80/20
4.74.7
3143096IRON208
80/20
0.4040.404
958261AF2-120 C
Adder
5.2200000000000014.437
939191AE1-149 C
Adder
9.4788235294117668.057
957601AF2-054 C
Adder
1.83764705882352961.562
316336AC2-165 C
Adder
7.7411764705882356.58
3150481FOUR RIVERF
80/20
3.5533.553
940641AE2-051 C
Adder
13.71529411764705811.658
943471AF1-018 C
Adder
6.2364705882352955.301
933981AD1-022 C
Adder
7.3258823529411776.227
938531AE1-072 C
Adder
15.30823529411764713.012
315051AA1-145 CT1
80/20
4.7034.703
3142366NRTHEST
80/20
0.1710.171
3150701DARBY 4
80/20
2.3652.365
3150731STONECA
Adder
6.2458823529411775.309
935161AD1-151 C
Adder
14.5176470588235312.34
958161AF2-110 C
Adder
1.19176470588235281.013
3150851SPRUNCC
80/20
0.1470.147
944631AF1-128 C
80/20
36.1936.19
933291AC2-141 C
Adder
26.7822.763
3150921YORKTN3
Adder
107.0694117647058991.009
926071AC1-086 C
Adder
16.83294117647058714.308
946281AF1-292 C
Adder
1.23176470588235291.047
939261AE1-157 C
80/20
13.3213.32
316169AC1-164 GEN
80/20
36.80636.806
316349AD2-085 C
Adder
3.0105882352941182.559
960081AF2-299 C
Adder
1.48823529411764691.265
938771AE1-103 C
Adder
2.5011764705882352.126
963041AG1-153 C
Adder
4.2658823529411763.626
944011AF1-069 C
Adder
9.9305882352941198.441
966881AG1-559 C
80/20
2.2882.288
3150621CHESTS7
80/20
1.6141.614
3150601CHESTF5
80/20
57.83757.837
944591AF1-124 C
Adder
39.9505882352941233.958
944601AF1-125 C
Adder
39.1964705882352933.317
941591AE2-156 C
Adder
15.7305882352941213.371
961941AG1-037 C
Adder
0.41529411764705880.353
941031AE2-094 C
Adder
30.39411764705882425.835
3150391LDYSMT3
80/20
4.4174.417
3150831SPRUNCA
80/20
8.2198.219
3150841SPRUNCB
Adder
8.2188235294117656.986
966871AG1-558 C
80/20
2.1962.196
316075AC2-137 C
80/20
0.3470.347
964211AG1-282 C
Adder
1.65294117647058841.405
3150431FOUR RIVERA
80/20
2.9522.952
3150631CHESTG8
80/20
3.4613.461
3150611CHESTG7
80/20
3.5173.517
961951AG1-038 C
Adder
2.7117647058823532.305
3137643SOCKMAN
Adder
0.56941176470588240.484
316312AB1-027 C
80/20
0.4890.489
966661AG1-536 C
Adder
4.4905882352941183.817
939411AE1-173 C
Adder
73.6611764705882562.612
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.3484.348
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.51781.517
CPLELTFEXP_CPLE->PJM
CLTF
9.1099.109
TVALTFEXP_TVA->PJM
CLTF
6.5746.574
NYPJM->LTFIMP_NY
CLTF
2.8322.832
LGEELTFEXP_LGEE->PJM
CLTF
1.8211.821
WECLTFEXP_WEC->PJM
CLTF
0.9380.938
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.86545.865
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.97725.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
5.1595.159
LAGNLTFEXP_LAGN->PJM
CLTF
8.1928.192
SIGELTFEXP_SIGE->PJM
CLTF
0.3350.335

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.82 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3858.59
MW Contribution:8.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
50.0317647058823542.527
961671AG1-007 C
Adder
1.34941176470588231.147
3156116Z1-036WIND
80/20
0.9810.981
946301AF1-294 C
Adder
4.9423529411764714.201
942461AE2-259 C
Adder
12.99058823529411711.042
934621AD1-088 C
80/20
14.01914.019
942001AE2-212 C
80/20
3.1513.151
934521AD1-076 C
Adder
18.1705882352941215.445
934511AD1-075 C
Adder
12.50823529411764710.632
316263AC1-034 C
Adder
9.488.058
316321Z2-027 C
80/20
0.5460.546
959311AF2-222 C
Adder
22.66470588235294419.265
3151031BRUNSWICKG2
80/20
12.91412.914
316240AF1-291 C
Adder
3.0682352941176472.608
944641AF1-129 C
Adder
144.29529411764705122.651
316036AC1-147 C
80/20
0.5540.554
316305AF2-043 C
80/20
0.5240.524
3156056W1-029WIND
80/20
1.1641.164
3152411Z1-086 GT1
80/20
16.54216.542
3152421Z1-086 GT2
80/20
16.53816.538
316233AE1-074 C
80/20
3.9163.916
940551AE2-041 C
Adder
8.4917647058823537.218
943461AF1-017 C
80/20
2.0242.024
316311AC2-079 C
80/20
8.6058.605
316274AC1-208 C
Adder
13.08588235294117711.123
962571AG1-106 C
Adder
3.98941176470588273.391
3151311EDGECMA
Adder
22.1658823529411818.841
957871AF2-081 C
80/20
15.07515.075
316405AF2-144 C
80/20
0.4360.436
3150651CHESTF6
Adder
26.27176470588235422.331
3150861SPRUNCD
80/20
0.2360.236
940481AE2-033 C
80/20
24.49624.496
940541AE2-040 C
80/20
4.3564.356
3152441Z1-086 ST
80/20
28.79528.795
961611AG1-000B C
Adder
22.90588235294117719.47
316375AC2-012 C
80/20
2.0322.032
316072AD1-144 C
80/20
0.4180.418
966621AG1-532 C
Adder
2.06235294117647071.753
316320Y1-086 C
80/20
0.330.33
316388AE2-253 GEN
80/20
2.9552.955
3151021BRUNSWICKG1
80/20
12.91412.914
3151041BRUNSWICKG3
80/20
12.91412.914
942341AE2-247 C
80/20
2.2382.238
316246AF1-032 C
80/20
0.4280.428
316365AB2-100 C1
80/20
1.4231.423
957481AF2-042 C
80/20
80.37380.373
940431AE2-027 C
Adder
18.39647058823529615.637
316294AC1-161 C
80/20
7.5057.505
944581AF1-123 C
80/20
68.97668.976
316185AD1-033 C
80/20
1.8511.851
916191Z1-068 C
80/20
0.0660.066
941101AE2-104 C
80/20
5.0455.045
313526AB2-022 C
80/20
0.5650.565
316017AA1-139 ULT1
80/20
1.6261.626
3152431Z1-086 GT3
80/20
16.53816.538
316336AC2-165 C
Adder
14.04941176470588411.942
940641AE2-051 C
80/20
27.74527.745
943471AF1-018 C
Adder
8.4917647058823537.218
3152331SURRY 2
80/20
35.95635.956
3151201GRAVEL4
80/20
3.6573.657
3151211GRAVEL5
80/20
3.6113.611
3151221GRAVEL6
80/20
3.6533.653
316236AE1-162 C
80/20
0.5140.514
964791AG1-342 C
Adder
4.884.148
316313AB2-026 C
80/20
0.5590.559
939191AE1-149 C
80/20
15.94215.942
957601AF2-054 C
Adder
2.53058823529411742.151
3150981CHESPKA
80/20
0.6560.656
961941AG1-037 C
Adder
0.74470588235294120.633
934321AD1-056 C
Adder
9.0458823529411777.689
934331AD1-057 C
Adder
5.04588235294117654.289
958211AF2-115 C
Adder
3.0058823529411772.555
3151531CLOVER1
80/20
18.57418.574
316258AE1-075 C
80/20
0.5130.513
941031AE2-094 C
80/20
63.15563.155
3150831SPRUNCA
80/20
13.15813.158
3150841SPRUNCB
80/20
13.15813.158
3151081ELIZAR1
80/20
4.824.82
316018AA1-139 ULT2
80/20
1.6261.626
3150851SPRUNCC
80/20
0.2360.236
944631AF1-128 C
Adder
51.9752941176470644.179
933291AC2-141 C
80/20
46.08646.086
3150921YORKTN3
Adder
165.5670588235294140.732
3151191GRAVEL3
80/20
3.6113.611
933981AD1-022 C
Adder
12.98823529411764711.04
938531AE1-072 C
80/20
26.49826.498
3150731STONECA
Adder
9.5788235294117648.142
935161AD1-151 C
Adder
22.80117647058823519.381
316083AB2-161 C
80/20
0.8230.823
958161AF2-110 C
80/20
2.0582.058
927021AC1-189 C
Adder
12.14117647058823710.32
926071AC1-086 C
Adder
30.83882352941176626.213
946281AF1-292 C
Adder
2.2752941176470591.934
964241AG1-285 C
Adder
17.31176470588235414.715
962561AG1-105 C
Adder
12.25882352941176610.42
316169AC1-164 GEN
Adder
49.0282352941176541.674
3151091ELIZAR2
80/20
4.7354.735
316349AD2-085 C
80/20
5.1625.162
960081AF2-299 C
Adder
2.74941176470588242.337
936261AD2-033 C
Adder
17.81058823529411615.139
961791AG1-021 C
Adder
2.40470588235294122.044
938771AE1-103 C
80/20
4.3814.381
963041AG1-153 C
80/20
8.7798.779
3151051BRUNSWICKS1
80/20
26.8326.83
944011AF1-069 C
80/20
20.63520.635
3150601CHESTF5
Adder
83.0647058823529570.605
944591AF1-124 C
80/20
69.22169.221
944601AF1-125 C
80/20
67.91467.914
3151101ELIZAR3
80/20
4.8814.881
941591AE2-156 C
80/20
27.03327.033
957861AF2-080 C
Adder
11.0270588235294129.373
316023AB2-100 C2
80/20
1.4231.423
316315AB2-025 C
80/20
0.6170.617
3138533PONTONDP
Adder
0.89058823529411770.757
3151541CLOVER2
80/20
18.418.4
316316AC1-027 C
80/20
0.4760.476
3137643SOCKMAN
Adder
1.04352941176470580.887
939411AE1-173 C
80/20
143.49143.49
316381AD1-082 C
80/20
1.8751.875
3151161SURRY 1
80/20
35.54335.543
3150991CHESPKB
80/20
1.0871.087
316303AF2-085
80/20
6.4786.478
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.9747.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
144.491144.491
CPLELTFEXP_CPLE->PJM
CLTF
16.71416.714
TVALTFEXP_TVA->PJM
CLTF
10.46710.467
NYPJM->LTFIMP_NY
CLTF
3.1863.186
LGEELTFEXP_LGEE->PJM
CLTF
2.5932.593
WECLTFEXP_WEC->PJM
CLTF
1.3381.338
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.12565.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.22440.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6237.623
LAGNLTFEXP_LAGN->PJM
CLTF
13.13513.135
SIGELTFEXP_SIGE->PJM
CLTF
0.4870.487

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.79 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4641.11
MW Contribution:22.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
50.5435294117647142.962
924517AB2-100 E2
Adder
4.3447058823529413.693
937226AE2-253 E
Adder
8.9129411764705877.576
934621AD1-088 C
Adder
14.11647058823529511.999
957482AF2-042 E
Adder
53.94941176470588645.857
958502AF2-144 E
Adder
1.81.53
942001AE2-212 C
Adder
3.19647058823529442.717
939192AE1-149 E
Adder
10.7658823529411769.151
939312AE1-162 E
Adder
2.13058823529411741.811
934065AD1-033 E
50/50
7.6627.662
920692AA2-178 E
Adder
6.19058823529411755.262
966622AG1-532 E
Adder
1.3870588235294121.179
917122Z2-027 E
Adder
2.04352941176470631.737
3146326AYDLETT TAP
Adder
2.06705882352941161.757
938532AE1-072 E
Adder
13.96470588235294111.87
3152411Z1-086 GT1
50/50
16.65116.651
3152421Z1-086 GT2
50/50
16.64616.646
316233AE1-074 C
50/50
3.9613.961
935162AD1-151 E
Adder
15.43176470588235513.117
943461AF1-017 C
Adder
2.0482352941176471.741
316311AC2-079 C
Adder
8.7047058823529427.399
932596AC2-079 E
Adder
14.20352941176470712.073
943172AE2-346 E
Adder
0.90235294117647060.767
934522AD1-076 E
Adder
9.3564705882352957.953
940492AE2-034 E
Adder
4.6423529411764713.946
962571AG1-106 C
Adder
4.0258823529411773.422
918492AA1-063AE OP
Adder
6.065.151
957871AF2-081 C
Adder
15.24000000000000212.954
937482AD2-202 E
Adder
1.561.326
3145506HICKORY
50/50
3.3283.328
946262AF1-291 E
Adder
2.07764705882352941.766
3150651CHESTF6
Adder
26.6976470588235322.693
933292AC2-141 E
50/50
19.88619.886
934576AD1-082 E
Adder
6.6517647058823535.654
944602AF1-125 E
50/50
157.162157.162
943612AF1-032 E
Adder
1.40941176470588241.198
918512AA1-065 E OP
Adder
8.2458823529411777.009
934502AD1-074 E
Adder
25.72941176470588321.87
934512AD1-075 E
Adder
6.4317647058823535.467
924516AB2-100 E1
Adder
4.3447058823529413.693
966621AG1-532 C
Adder
2.0811764705882351.769
919153AA1-139 E2
Adder
6.2317647058823535.297
3151021BRUNSWICKG1
50/50
12.99912.999
3151041BRUNSWICKG3
50/50
12.99912.999
940642AE2-051 E
50/50
18.62918.629
942341AE2-247 C
Adder
2.2635294117647061.924
943462AF1-017 E
Adder
3.34117647058823542.84
958162AF2-110 E
Adder
3.31058823529411762.814
923263AB1-132 E OP
Adder
9.0588235294117647.7
940481AE2-033 C
50/50
24.72924.729
940482AE2-033 E
50/50
16.67116.671
940541AE2-040 C
50/50
4.3984.398
3152441Z1-086 ST
50/50
28.98428.984
961611AG1-000B C
Adder
23.2270588235294119.743
316375AC2-012 C
50/50
2.0552.055
316141AB2-099 E
Adder
0.37647058823529410.32
923994AB2-040_E
Adder
9.1117647058823537.745
316088AB2-174 E
Adder
9.6611764705882348.212
957481AF2-042 C
Adder
80.9247058823529468.786
942002AE2-212 E
Adder
2.13058823529411741.811
940431AE2-027 C
Adder
18.6823529411764715.88
316294AC1-161 C
50/50
7.5867.586
944581AF1-123 C
50/50
69.72769.727
316185AD1-033 C
50/50
1.8711.871
916191Z1-068 C
50/50
0.0670.067
941101AE2-104 C
Adder
5.1011764705882364.336
934521AD1-076 C
Adder
18.35647058823529315.603
934511AD1-075 C
Adder
12.6352941176470610.74
919692AA2-053 E OP
Adder
6.2482352941176475.311
923573AB1-173 E OP
Adder
4.8588235294117644.13
3145723EMPORIA
Adder
0.640.544
920042AA2-088 E OP
Adder
15.88941176470588313.506
919152AA1-139 E1
Adder
6.2317647058823535.297
3151031BRUNSWICKG2
50/50
12.99912.999
316240AF1-291 C
Adder
3.11647058823529432.649
944641AF1-129 C
Adder
146.62823529411764124.634
924814AB2-134 E
Adder
18.2270588235294115.493
942342AE2-247 E
Adder
3.12588235294117662.657
901082W1-029 E
Adder
48.43294117647058541.168
3143316POE
50/50
2.082.08
939191AE1-149 C
Adder
16.1494117647058813.727
933982AD1-022 E
Adder
7.1423529411764716.071
3145946PLYMOUTH TP
Adder
0.484705882352941150.412
934612AD1-087 E
Adder
5.3305882352941174.531
934622AD1-088 E
Adder
6.79647058823529455.777
3152431Z1-086 GT3
50/50
16.64616.646
316336AC2-165 C
Adder
5.537647058823534.707
940641AE2-051 C
50/50
27.94427.944
316084AB2-161 E
Adder
8.3482352941176477.096
933981AD1-022 C
Adder
13.12117647058823711.153
900672V4-068 E
Adder
0.53294117647058830.453
938531AE1-072 C
Adder
26.78823529411764822.77
3145393UNCAMP
Adder
9.1811764705882367.804
3150731STONECA
Adder
9.735294117647068.275
935161AD1-151 C
Adder
23.14823529411764719.676
932046AC2-012 E
50/50
20.00120.001
958161AF2-110 C
Adder
2.0811764705882351.769
962572AG1-106 E
Adder
1.76117647058823561.497
957872AF2-081 E
Adder
6.53176470588235255.552
938562AE1-075 E
Adder
1.56235294117647071.328
938552AE1-074 E
50/50
1.9951.995
926755AC1-161 E
50/50
19.88619.886
933291AC2-141 C
50/50
46.58646.586
3150921YORKTN3
Adder
168.0623529411765142.853
925522AC1-027 E
50/50
1.8591.859
941102AE2-104 E
Adder
8.1105882352941186.894
3145256KINGFORK
Adder
1.52941176470588251.3
926071AC1-086 C
Adder
31.12823529411764826.459
946281AF1-292 C
Adder
2.2964705882352941.952
960082AF2-299 E
Adder
1.84941176470588251.572
916042Z1-036 E
Adder
43.2517647058823636.764
923832AB2-022 E
Adder
1.8882352941176471.605
938772AE1-103 E
Adder
6.115294117647065.198
963042AG1-153 E
50/50
13.25613.256
944592AF1-124 E
50/50
160.246160.246
944582AF1-123 E
50/50
159.668159.668
3151091ELIZAR2
50/50
4.7894.789
316349AD2-085 C
Adder
5.2223529411764714.439
935112AD1-144 E
Adder
1.42000000000000021.207
926072AC1-086 E
Adder
14.16705882352941312.042
960081AF2-299 C
Adder
2.7741176470588242.358
3145413WATKINS
Adder
1.04117647058823540.885
938771AE1-103 C
Adder
4.4282352941176473.764
963041AG1-153 C
50/50
8.8378.837
3151051BRUNSWICKS1
50/50
27.00627.006
944011AF1-069 C
50/50
20.76920.769
925332AB2-190 E
Adder
11.5352941176470599.805
927226AC1-216 E
Adder
11.1270588235294129.458
944591AF1-124 C
50/50
69.97569.975
944601AF1-125 C
50/50
68.65368.653
3151101ELIZAR3
50/50
4.9354.935
941591AE2-156 C
50/50
27.33727.337
936666AD2-085 E
Adder
8.5211764705882367.243
961942AG1-037 E
Adder
0.50117647058823530.426
961941AG1-037 C
Adder
0.7517647058823530.639
923852AB2-025 E
50/50
1.7791.779
923862AB2-026 E
Adder
1.8317647058823531.557
941031AE2-094 C
50/50
63.56663.566
941032AE2-094 E
50/50
28.4728.47
3150831SPRUNCA
Adder
13.36352941176470611.359
3150841SPRUNCB
Adder
13.36352941176470611.359
939412AE1-173 E
50/50
96.42796.427
3151081ELIZAR1
50/50
4.8744.874
926662AC1-147 E
Adder
2.02235294117647071.719
916192Z1-068 E
50/50
2.8712.871
957492AF2-043 E
Adder
2.16705882352941171.842
946282AF1-292 E
Adder
1.53058823529411761.301
316315AB2-025 C
50/50
0.6230.623
944012AF1-069 E
50/50
8.0688.068
316316AC1-027 C
50/50
0.4810.481
3137643SOCKMAN
Adder
1.05294117647058830.895
913392Y1-086 E
Adder
3.3447058823529412.843
940432AE2-027 E
Adder
12.45529411764705910.587
939411AE1-173 C
50/50
144.64144.64
934012AD1-025 E
Adder
14.40588235294117712.245
316303AF2-085
50/50
6.5316.531
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
8.0368.036
CBM South 2LTFEXP_CBM-S2->PJM
CBM
145.599145.599
CPLELTFEXP_CPLE->PJM
CLTF
16.84316.843
TVALTFEXP_TVA->PJM
CLTF
10.54210.542
O66PJM->LTFIMP_O-066
CMTX_NF
45.24145.241
NYPJM->LTFIMP_NY
CLTF
3.2313.231
LGEELTFEXP_LGEE->PJM
CLTF
2.6092.609
WECLTFEXP_WEC->PJM
CLTF
1.3461.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.46965.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.49440.494
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
7.6697.669
LAGNLTFEXP_LAGN->PJM
CLTF
13.22813.228
G-007PJM->LTFIMP_G-007
CMTX_NF
7.1157.115
SIGELTFEXP_SIGE->PJM
CLTF
0.490.49

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.38 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3586.78
MW Contribution:5.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
24.38588235294117720.728
961671AG1-007 C
Adder
0.69647058823529410.592
946301AF1-294 C
80/20
2.9542.954
942461AE2-259 C
80/20
7.9867.986
934621AD1-088 C
80/20
8.2538.253
208901BRIS G2
80/20
-2.846-2.846
316192AB2-158 C
80/20
4.3254.325
942001AE2-212 C
Adder
1.40235294117647061.192
934521AD1-076 C
Adder
8.8564705882352937.528
934511AD1-075 C
Adder
6.0964705882352945.182
316087AB2-174 C
80/20
0.9080.908
959311AF2-222 C
80/20
13.30313.303
937481AD2-202 C
80/20
0.3090.309
3151031BRUNSWICKG2
80/20
7.5567.556
3152411Z1-086 GT1
80/20
9.6939.693
3152421Z1-086 GT2
80/20
9.699.69
316233AE1-074 C
80/20
2.0672.067
943461AF1-017 C
Adder
0.94000000000000010.799
316311AC2-079 C
Adder
3.99647058823529383.397
316274AC1-208 C
Adder
6.785.763
962571AG1-106 C
Adder
2.0682352941176471.758
957871AF2-081 C
Adder
7.0094117647058835.958
316405AF2-144 C
80/20
0.2720.272
3147043LAWRENC
80/20
0.240.24
940481AE2-033 C
80/20
12.91312.913
940541AE2-040 C
80/20
2.2982.298
3152441Z1-086 ST
80/20
16.87216.872
966001AG1-469 C
80/20
2.3822.382
966621AG1-532 C
80/20
1.0911.091
935171AD1-152 C
80/20
1.0991.099
3151021BRUNSWICKG1
80/20
7.5567.556
3151041BRUNSWICKG3
80/20
7.5567.556
934861AD1-115 C
80/20
3.3063.306
3152261N ANNA2
80/20
103.964103.964
942341AE2-247 C
Adder
1.03882352941176470.883
316365AB2-100 C1
80/20
0.7450.745
957481AF2-042 C
80/20
47.06247.062
3151801S ANNAS2
80/20
1.6761.676
944581AF1-123 C
Adder
32.0470588235294127.24
941101AE2-104 C
Adder
2.35411764705882342.001
316237AB2-079 C O1
80/20
0.2590.259
934611AD1-087 C
80/20
1.0661.066
3152431Z1-086 GT3
80/20
9.699.69
316336AC2-165 C
80/20
8.8748.874
940641AE2-051 C
80/20
15.75815.758
961941AG1-037 C
Adder
0.37294117647058830.317
934321AD1-056 C
Adder
4.7070588235294134.001
934331AD1-057 C
Adder
2.6258823529411772.232
958211AF2-115 C
80/20
1.7961.796
3151531CLOVER1
80/20
10.82910.829
208900BRIS G1
80/20
-2.405-2.405
3151761LOISA E
80/20
6.8276.827
3151771S ANNAG1
80/20
3.2623.262
3151791S ANNAG2
80/20
3.2623.262
3151781S ANNAS1
80/20
1.6761.676
316258AE1-075 C
80/20
0.320.32
941031AE2-094 C
80/20
37.11337.113
313527AB2-043 C
80/20
0.4090.409
3152251N ANNA1
80/20
103.92103.92
933291AC2-141 C
Adder
21.0423529411764717.886
316239AB2-077 C O1
80/20
0.2590.259
964791AG1-342 C
Adder
2.77294117647058872.357
3151731LOISA B
80/20
3.3493.349
3151751LOISA D
80/20
3.3493.349
316313AB2-026 C
80/20
0.3480.348
316164AC1-076_C
80/20
1.0891.089
939191AE1-149 C
Adder
7.2929411764705886.199
933981AD1-022 C
Adder
6.3599999999999995.406
938531AE1-072 C
Adder
12.33529411764705810.485
316238AB2-078 C O1
80/20
0.2590.259
958161AF2-110 C
Adder
0.96117647058823530.817
927021AC1-189 C
Adder
6.225.287
926071AC1-086 C
Adder
15.98823529411764713.59
946281AF1-292 C
80/20
1.2041.204
964241AG1-285 C
80/20
9.9749.974
962561AG1-105 C
Adder
6.9729411764705885.927
316034AC1-036 C
80/20
0.1860.186
3144293JTRSVLE
80/20
0.3290.329
316044AC1-158 C1
80/20
18.51718.517
316349AD2-085 C
Adder
2.3964705882352942.037
960081AF2-299 C
80/20
1.4551.455
936261AD2-033 C
80/20
10.37510.375
961791AG1-021 C
80/20
1.4371.437
938771AE1-103 C
Adder
2.10235294117647081.787
963041AG1-153 C
80/20
5.1375.137
3151051BRUNSWICKS1
80/20
15.69915.699
316170AC1-121 C
80/20
2.952.95
944011AF1-069 C
80/20
12.12612.126
316045AC1-158 C2
80/20
18.51718.517
944591AF1-124 C
Adder
32.1611764705882427.337
944601AF1-125 C
Adder
31.55411764705882826.821
941591AE2-156 C
Adder
12.43294117647058910.568
957861AF2-080 C
Adder
5.6494117647058824.802
316023AB2-100 C2
80/20
0.7450.745
316315AB2-025 C
80/20
0.3250.325
316131AB2-060 C
80/20
1.1781.178
3138533PONTONDP
80/20
0.5320.532
3151541CLOVER2
80/20
10.72710.727
316257AC1-043 C
80/20
6.6126.612
316254AC1-120 C
80/20
8.5918.591
3137643SOCKMAN
Adder
0.54588235294117650.464
3151741LOISA C
80/20
3.3493.349
3151721LOISA A
80/20
3.3313.331
939411AE1-173 C
80/20
78.11378.113
316303AF2-085
80/20
3.8763.876
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2194.219
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.82173.821
CPLELTFEXP_CPLE->PJM
CLTF
8.8538.853
TVALTFEXP_TVA->PJM
CLTF
4.5224.522
NYPJM->LTFIMP_NY
CLTF
2.292.29
LGEELTFEXP_LGEE->PJM
CLTF
0.8350.835
WECLTFEXP_WEC->PJM
CLTF
0.4130.413
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.20919.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.12316.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6672.667
LAGNLTFEXP_LAGN->PJM
CLTF
5.7055.705
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.09 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3577.61
MW Contribution:5.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
25.86823529411764621.988
961671AG1-007 C
Adder
0.73647058823529410.626
946301AF1-294 C
80/20
3.0833.083
942461AE2-259 C
Adder
8.3117647058823547.065
934621AD1-088 C
80/20
8.6418.641
208901BRIS G2
80/20
-2.857-2.857
316192AB2-158 C
80/20
4.2764.276
942001AE2-212 C
Adder
1.49882352941176471.274
934521AD1-076 C
Adder
9.3952941176470587.986
934511AD1-075 C
Adder
6.46705882352941155.497
316263AC1-034 C
Adder
5.2270588235294114.443
316087AB2-174 C
80/20
0.9580.958
959311AF2-222 C
80/20
13.90913.909
937481AD2-202 C
80/20
0.3240.324
3151031BRUNSWICKG2
80/20
7.9247.924
3152411Z1-086 GT1
80/20
10.16410.164
3152421Z1-086 GT2
80/20
10.16110.161
316233AE1-074 C
80/20
2.1822.182
943461AF1-017 C
Adder
1.00.85
316311AC2-079 C
Adder
4.2541176470588233.616
316274AC1-208 C
Adder
7.1635294117647066.089
962571AG1-106 C
Adder
2.1847058823529411.857
3151311EDGECMA
Adder
12.21411764705882410.382
957871AF2-081 C
Adder
7.4588235294117656.34
316405AF2-144 C
80/20
0.2830.283
3150651CHESTF6
Adder
11.5976470588235319.858
316181AB2-040 GEN
80/20
1.0311.031
3147043LAWRENC
80/20
0.2530.253
940481AE2-033 C
80/20
13.63113.631
940541AE2-040 C
80/20
2.4262.426
313506AB1-173 C OP
80/20
0.9150.915
966621AG1-532 C
80/20
1.1511.151
935171AD1-152 C
80/20
1.1531.153
3151021BRUNSWICKG1
80/20
7.9247.924
3151041BRUNSWICKG3
80/20
7.9247.924
3152261N ANNA2
80/20
106.999106.999
942341AE2-247 C
Adder
1.10588235294117650.94
316365AB2-100 C1
80/20
0.7870.787
3152441Z1-086 ST
80/20
17.69217.692
966001AG1-469 C
80/20
1.9821.982
961611AG1-000B C
Adder
10.3129411764705888.766
316237AB2-079 C O1
80/20
0.2720.272
934611AD1-087 C
80/20
1.1171.117
3152431Z1-086 GT3
80/20
10.16110.161
316336AC2-165 C
80/20
9.2269.226
940641AE2-051 C
80/20
16.55416.554
957481AF2-042 C
80/20
49.31549.315
3151801S ANNAS2
80/20
1.5631.563
940431AE2-027 C
Adder
8.3129411764705887.066
944581AF1-123 C
Adder
34.0988235294117728.984
941101AE2-104 C
Adder
2.50470588235294132.129
316239AB2-077 C O1
80/20
0.2720.272
964791AG1-342 C
Adder
2.9105882352941182.474
3151731LOISA B
80/20
3.0953.095
961941AG1-037 C
Adder
0.39411764705882360.335
934321AD1-056 C
Adder
4.9729411764705894.227
934331AD1-057 C
Adder
2.7741176470588242.358
958211AF2-115 C
80/20
1.8751.875
3151531CLOVER1
80/20
11.34911.349
316240AF1-291 C
Adder
1.37882352941176461.172
944641AF1-129 C
Adder
63.6988235294117654.144
313527AB2-043 C
80/20
0.4290.429
3152251N ANNA1
80/20
106.954106.954
933291AC2-141 C
Adder
22.41294117647058619.051
3151751LOISA D
80/20
3.0953.095
316313AB2-026 C
80/20
0.3630.363
939191AE1-149 C
Adder
7.7752941176470596.609
933981AD1-022 C
Adder
6.7447058823529415.733
938531AE1-072 C
Adder
13.12352941176470511.155
316238AB2-078 C O1
80/20
0.2720.272
958161AF2-110 C
Adder
1.02235294117647070.869
927021AC1-189 C
Adder
6.5788235294117645.592
926071AC1-086 C
Adder
16.8929411764705914.359
946281AF1-292 C
80/20
1.2711.271
964241AG1-285 C
80/20
10.44910.449
962561AG1-105 C
Adder
7.3152941176470596.218
316034AC1-036 C
80/20
0.1950.195
3144293JTRSVLE
80/20
0.3440.344
316349AD2-085 C
Adder
2.5505882352941182.168
960081AF2-299 C
80/20
1.5351.535
936261AD2-033 C
80/20
10.85610.856
961791AG1-021 C
80/20
1.51.5
938771AE1-103 C
Adder
2.2329411764705881.898
963041AG1-153 C
80/20
5.3875.387
3151051BRUNSWICKS1
80/20
16.46316.463
944011AF1-069 C
80/20
12.71412.714
944591AF1-124 C
Adder
34.2229.087
944601AF1-125 C
Adder
33.5741176470588328.538
941591AE2-156 C
Adder
13.23882352941176611.253
208900BRIS G1
80/20
-2.414-2.414
3151761LOISA E
80/20
6.316.31
3151771S ANNAG1
80/20
3.0413.041
3151791S ANNAG2
80/20
3.0413.041
3151781S ANNAS1
80/20
1.5631.563
316258AE1-075 C
80/20
0.3330.333
941031AE2-094 C
80/20
38.91138.911
3150831SPRUNCA
Adder
6.1623529411764715.238
3150841SPRUNCB
Adder
6.1623529411764715.238
957861AF2-080 C
Adder
5.9741176470588245.078
316023AB2-100 C2
80/20
0.7870.787
316315AB2-025 C
80/20
0.3440.344
316131AB2-060 C
80/20
1.2351.235
3138533PONTONDP
80/20
0.5550.555
3151541CLOVER2
80/20
11.24311.243
3137643SOCKMAN
Adder
0.57647058823529410.49
3151741LOISA C
80/20
3.0953.095
3151721LOISA A
80/20
3.0793.079
939411AE1-173 C
80/20
82.26382.263
316303AF2-085
80/20
4.064.06
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4574.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
78.26878.268
CPLELTFEXP_CPLE->PJM
CLTF
9.3529.352
TVALTFEXP_TVA->PJM
CLTF
4.8954.895
NYPJM->LTFIMP_NY
CLTF
2.2912.291
LGEELTFEXP_LGEE->PJM
CLTF
0.9480.948
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.24822.248
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.65817.658
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.9882.988
LAGNLTFEXP_LAGN->PJM
CLTF
6.1746.174
SIGELTFEXP_SIGE->PJM
CLTF
0.1860.186

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.41 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4350.17
MW Contribution:13.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
920692AA2-178 E
Adder
3.1141176470588232.647
922923AB1-081 E OP
Adder
2.9105882352941182.474
923263AB1-132 E OP
Adder
4.8811764705882354.149
940481AE2-033 C
Adder
13.54823529411764811.516
940482AE2-033 E
Adder
9.1341176470588247.764
940541AE2-040 C
Adder
2.4117647058823532.05
924312AB2-078 E O1
Adder
1.10588235294117650.94
925612AC1-036 E
Adder
0.7117647058823530.605
926274AC1-105 E
Adder
2.1788235294117651.852
966001AG1-469 C
50/50
2.0062.006
926740AC1-158 E2
50/50
51.18251.182
316141AB2-099 E
Adder
0.195294117647058840.166
961672AG1-007 E
Adder
0.414117647058823530.352
923994AB2-040_E
Adder
4.9741176470588234.228
316088AB2-174 E
Adder
5.2858823529411774.493
924322AB2-079 E O1
Adder
1.10588235294117650.94
943902AF1-058 E
Adder
1.04352941176470580.887
946302AF1-294 E
Adder
2.59294117647058852.204
957481AF2-042 C
Adder
49.0341176470588341.679
3151801S ANNAS2
50/50
1.5681.568
942002AE2-212 E
Adder
0.99176470588235290.843
944581AF1-123 C
Adder
33.8670588235294128.787
941101AE2-104 C
Adder
2.48705882352941152.114
926206AC1-098 E
Adder
2.86705882352941142.437
964791AG1-342 C
Adder
2.88941176470588262.456
901082W1-029 E
Adder
23.76705882352941420.202
942462AE2-259 E
Adder
5.5047058823529414.679
3151731LOISA B
50/50
3.1063.106
3151751LOISA D
50/50
3.1063.106
3143316POE
Adder
1.04235294117647070.886
939191AE1-149 C
Adder
7.7200000000000016.562
943172AE2-346 E
Adder
0.46941176470588240.399
917332KELFORD E
Adder
1.281.088
925122AB2-169 E
Adder
4.4105882352941183.749
934522AD1-076 E
Adder
4.7541176470588244.041
940492AE2-034 E
Adder
2.3364705882352941.986
316274AC1-208 C
Adder
7.1094117647058826.043
962571AG1-106 C
Adder
2.16941176470588241.844
917342Z2-044 E
Adder
0.46823529411764710.398
3151311EDGECMA
Adder
12.11411764705882510.297
918492AA1-063AE OP
Adder
3.22705882352941182.743
957871AF2-081 C
Adder
7.4070588235294126.296
961792AG1-021 E
Adder
1.26941176470588221.079
937482AD2-202 E
Adder
0.94117647058823540.8
3145506HICKORY
Adder
1.61411764705882371.372
933292AC2-141 E
Adder
9.502352941176478.077
934576AD1-082 E
Adder
3.19882352941176462.719
944602AF1-125 E
Adder
76.3341176470588364.884
943612AF1-032 E
Adder
0.68470588235294120.582
933982AD1-022 E
Adder
3.6447058823529413.098
3145946PLYMOUTH TP
Adder
0.245882352941176470.209
927146AC1-208 E
Adder
3.1564705882352942.683
927255AC1-221 E
Adder
2.9588235294117652.515
934612AD1-087 E
Adder
3.2152941176470592.733
934622AD1-088 E
Adder
4.1364705882352943.516
316336AC2-165 C
Adder
9.177647058823537.801
940641AE2-051 C
50/50
16.47216.472
316084AB2-161 E
Adder
4.0141176470588233.412
933981AD1-022 C
Adder
6.6952941176470595.691
900672V4-068 E
Adder
0.276470588235294130.235
938531AE1-072 C
Adder
13.03294117647058811.078
924302AB2-077 E O1
Adder
1.10588235294117650.94
3145393UNCAMP
Adder
4.622352941176473.929
932046AC2-012 E
Adder
9.6164705882352938.174
926214AC1-099 E
Adder
0.94705882352941180.805
932632AC2-084 E
Adder
2.53411764705882362.154
962572AG1-106 E
Adder
0.94941176470588240.807
957872AF2-081 E
Adder
3.17411764705882372.698
924162AB2-060 E OP
Adder
3.54470588235294143.013
964242AG1-285 E
Adder
6.9188235294117655.881
964792AG1-342 E
Adder
1.92588235294117661.637
932763AC2-100 E
Adder
2.00588235294117641.705
938562AE1-075 E
Adder
1.00.85
3152251N ANNA1
50/50
106.841106.841
938552AE1-074 E
Adder
1.09294117647058830.929
926755AC1-161 E
Adder
9.502352941176478.077
933291AC2-141 C
Adder
22.2618.921
925522AC1-027 E
Adder
0.89764705882352950.763
941102AE2-104 E
Adder
3.9541176470588243.361
3145256KINGFORK
Adder
0.72352941176470590.615
934521AD1-076 C
Adder
9.3258823529411777.927
934511AD1-075 C
Adder
6.425.457
919692AA2-053 E OP
Adder
3.36117647058823542.857
316263AC1-034 C
Adder
5.1835294117647064.406
923573AB1-173 E OP
Adder
2.6529411764705882.255
3145723EMPORIA
Adder
0.350588235294117640.298
920042AA2-088 E OP
Adder
8.226.987
925785AC1-054 E
Adder
2.79764705882352962.378
919152AA1-139 E1
Adder
3.02941176470588272.575
959311AF2-222 C
Adder
13.8152941176470611.743
942342AE2-247 E
Adder
1.5164705882352941.289
957862AF2-080 E
Adder
2.6270588235294122.233
926072AC1-086 E
Adder
7.6341176470588236.489
960081AF2-299 C
Adder
1.52470588235294141.296
3145413WATKINS
Adder
0.52941176470588240.45
936261AD2-033 C
Adder
10.782352941176479.165
962562AG1-105 E
Adder
4.842352941176474.116
961791AG1-021 C
Adder
1.48941176470588241.266
938771AE1-103 C
Adder
2.21764705882352951.885
924032AB2-045 E
Adder
1.08588235294117650.923
963041AG1-153 C
Adder
5.3588235294117644.555
944011AF1-069 C
50/50
12.65212.652
316045AC1-158 C2
50/50
19.56819.568
944591AF1-124 C
Adder
33.9870588235294128.889
944601AF1-125 C
Adder
33.3447058823529428.343
941591AE2-156 C
Adder
13.14823529411764711.176
936666AD2-085 E
Adder
4.1329411764705883.513
961942AG1-037 E
Adder
0.26117647058823530.222
961941AG1-037 C
Adder
0.391764705882352960.333
927022AC1-189 E
Adder
3.25058823529411762.763
934322AD1-056 E
Adder
2.6764705882352942.275
934332AD1-057 E
Adder
1.43411764705882371.219
934321AD1-056 C
Adder
4.9352941176470594.195
934331AD1-057 C
Adder
2.75294117647058822.34
925595AC1-034 E
Adder
3.91058823529411773.324
923852AB2-025 E
Adder
0.97529411764705880.829
936262AD2-033 E
Adder
7.1882352941176476.11
958211AF2-115 C
Adder
1.86235294117647051.583
208900BRIS G1
50/50
-2.489-2.489
3151761LOISA E
50/50
6.3326.332
3151771S ANNAG1
50/50
3.0513.051
3151791S ANNAG2
50/50
3.0513.051
3151781S ANNAS1
50/50
1.5681.568
923862AB2-026 E
Adder
1.17294117647058820.997
941031AE2-094 C
50/50
38.72138.721
941032AE2-094 E
50/50
17.34217.342
3150831SPRUNCA
Adder
6.117647058823535.2
3150841SPRUNCB
Adder
6.117647058823535.2
939412AE1-173 E
Adder
54.5505882352941246.368
926662AC1-147 E
Adder
0.97176470588235290.826
916192Z1-068 E
Adder
1.38588235294117631.178
957492AF2-043 E
Adder
1.05294117647058830.895
966622AG1-532 E
Adder
0.76235294117647070.648
917122Z2-027 E
Adder
1.00.85
3146326AYDLETT TAP
Adder
1.00588235294117640.855
938532AE1-072 E
Adder
6.7941176470588245.775
927264AC1-222 E
Adder
3.20470588235294152.724
3147133PAMPLIN
Adder
0.82352941176470580.7
966002AG1-469 E
50/50
1.0031.003
926739AC1-158 E1
50/50
51.18251.182
316233AE1-074 C
Adder
2.17058823529411751.845
943461AF1-017 C
Adder
0.99294117647058820.844
316311AC2-079 C
Adder
4.2247058823529413.591
932596AC2-079 E
Adder
6.8929411764705895.859
918512AA1-065 E OP
Adder
4.2588235294117653.62
918532AA1-067 E
Adder
0.55176470588235290.469
934502AD1-074 E
Adder
13.07176470588235311.111
934512AD1-075 E
Adder
3.26823529411764732.778
924516AB2-100 E1
Adder
2.36470588235294082.01
966621AG1-532 C
Adder
1.1435294117647060.972
919153AA1-139 E2
Adder
3.02941176470588272.575
924022AB2-043 E O1
Adder
4.2929411764705883.649
3147223TWITTYS
Adder
0.78941176470588240.671
959312AF2-222 E
Adder
9.2564705882352957.868
3152261N ANNA2
50/50
106.886106.886
940642AE2-051 E
50/50
10.98110.981
958161AF2-110 C
Adder
1.0152941176470590.863
942341AE2-247 C
Adder
1.09764705882352940.933
943462AF1-017 E
Adder
1.621.377
958162AF2-110 E
Adder
1.61411764705882371.372
919710AA2-057 E
Adder
3.1117647058823532.645
3137643SOCKMAN
Adder
0.57294117647058830.487
913392Y1-086 E
Adder
1.63411764705882371.389
933502AC2-165 E
Adder
6.9070588235294135.871
3151741LOISA C
50/50
3.1063.106
3151721LOISA A
50/50
3.093.09
939411AE1-173 C
Adder
81.8247058823529469.551
934501AD1-074 C
Adder
25.6821.828
961671AG1-007 C
Adder
0.73058823529411760.621
924517AB2-100 E2
Adder
2.36470588235294082.01
937226AE2-253 E
Adder
4.3282352941176473.679
946301AF1-294 C
Adder
3.06235294117647072.603
935172AD1-152 E
Adder
4.7270588235294114.018
942461AE2-259 C
Adder
8.257647058823537.019
934621AD1-088 C
Adder
8.5905882352941177.302
957482AF2-042 E
Adder
32.6894117647058927.786
208901BRIS G2
50/50
-2.946-2.946
958502AF2-144 E
Adder
1.15294117647058810.98
316192AB2-158 C
50/50
4.2784.278
942001AE2-212 C
Adder
1.48705882352941181.264
939192AE1-149 E
Adder
5.1470588235294124.375
939312AE1-162 E
Adder
0.97647058823529410.83
934065AD1-033 E
Adder
3.70941176470588243.153
957861AF2-080 C
Adder
5.9270588235294125.038
917512Z2-088 E OP1
Adder
3.8047058823529413.234
946282AF1-292 E
Adder
0.84117647058823530.715
3138533PONTONDP
Adder
0.55176470588235290.469
944012AF1-069 E
50/50
4.9154.915
927021AC1-189 C
Adder
6.5247058823529425.546
926071AC1-086 C
Adder
16.77411764705882314.258
924152AB2-059 E OP
Adder
4.122352941176473.504
946281AF1-292 C
Adder
1.26235294117647071.073
960082AF2-299 E
Adder
1.01647058823529420.864
916042Z1-036 E
Adder
21.48117647058823518.259
923832AB2-022 E
Adder
0.92235294117647060.784
964241AG1-285 C
Adder
10.3776470588235298.821
962561AG1-105 C
Adder
7.2635294117647076.174
958212AF2-115 E
Adder
1.58588235294117651.348
938772AE1-103 E
Adder
3.0611764705882352.602
963042AG1-153 E
Adder
8.0388235294117656.833
925022AB2-158 E
50/50
11.37311.373
316044AC1-158 C1
50/50
19.56819.568
944592AF1-124 E
Adder
77.8317647058823566.157
944582AF1-123 E
Adder
77.5517647058823565.919
316349AD2-085 C
Adder
2.53294117647058852.153
935112AD1-144 E
Adder
0.67176470588235290.571
316303AF2-085
50/50
4.0434.043
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.4084.408
CBM South 2LTFEXP_CBM-S2->PJM
CBM
77.11777.117
CPLELTFEXP_CPLE->PJM
CLTF
9.2519.251
TVALTFEXP_TVA->PJM
CLTF
4.7224.722
O66PJM->LTFIMP_O-066
CMTX_NF
32.20632.206
NYPJM->LTFIMP_NY
CLTF
2.3732.373
LGEELTFEXP_LGEE->PJM
CLTF
0.8720.872
WECLTFEXP_WEC->PJM
CLTF
0.4310.431
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.05120.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.83616.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.7842.784
LAGNLTFEXP_LAGN->PJM
CLTF
5.9595.959
G-007PJM->LTFIMP_G-007
CMTX_NF
5.0575.057
SIGELTFEXP_SIGE->PJM
CLTF
0.1730.173

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.75 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4205.81
MW Contribution:12.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
923263AB1-132 E OP
Adder
4.66470588235294153.965
940481AE2-033 C
Adder
12.94470588235294211.003
940482AE2-033 E
Adder
8.7270588235294117.418
940541AE2-040 C
Adder
2.3035294117647061.958
924312AB2-078 E O1
Adder
1.06588235294117650.906
925612AC1-036 E
Adder
0.68823529411764710.585
926274AC1-105 E
Adder
2.09764705882352941.783
966001AG1-469 C
50/50
2.4612.461
925672AC1-043 E
50/50
11.48611.486
926740AC1-158 E2
50/50
48.49548.495
316141AB2-099 E
Adder
0.187058823529411780.159
923994AB2-040_E
Adder
4.7588235294117654.045
316088AB2-174 E
Adder
5.0564705882352944.298
924322AB2-079 E O1
Adder
1.06588235294117650.906
943902AF1-058 E
Adder
1.00470588235294110.854
946302AF1-294 E
Adder
2.51294117647058852.136
957481AF2-042 C
Adder
47.1905882352941240.112
3151801S ANNAS2
50/50
1.7251.725
942002AE2-212 E
Adder
0.93764705882352950.797
944581AF1-123 C
Adder
32.1329411764705927.313
941101AE2-104 C
Adder
2.362.006
926206AC1-098 E
Adder
2.742.329
964791AG1-342 C
Adder
2.7823529411764712.365
901082W1-029 E
Adder
22.56941176470588319.184
942462AE2-259 E
Adder
5.3529411764705884.55
3151731LOISA B
50/50
3.4533.453
3151751LOISA D
50/50
3.4533.453
3143316POE
Adder
0.99058823529411770.842
316164AC1-076_C
50/50
1.1111.111
939191AE1-149 C
Adder
7.3129411764705896.216
943172AE2-346 E
Adder
0.448235294117647070.381
917332KELFORD E
Adder
1.22235294117647041.039
925122AB2-169 E
Adder
4.2058823529411773.575
934522AD1-076 E
Adder
4.5258823529411773.847
940492AE2-034 E
Adder
2.2223529411764711.889
316274AC1-208 C
Adder
6.7976470588235295.778
962571AG1-106 C
Adder
2.07294117647058851.762
917342Z2-044 E
Adder
0.448235294117647070.381
918492AA1-063AE OP
Adder
3.08235294117647072.62
957871AF2-081 C
Adder
7.0282352941176475.974
961792AG1-021 E
Adder
1.22941176470588221.045
937482AD2-202 E
Adder
0.90588235294117650.77
3145506HICKORY
Adder
1.53058823529411761.301
933292AC2-141 E
Adder
9.0070588235294127.656
934576AD1-082 E
Adder
3.0317647058823532.577
944602AF1-125 E
Adder
72.4247058823529461.561
943612AF1-032 E
Adder
0.64941176470588250.552
933982AD1-022 E
Adder
3.47058823529411782.95
3145946PLYMOUTH TP
Adder
0.234117647058823540.199
927146AC1-208 E
Adder
3.01882352941176452.566
927255AC1-221 E
Adder
2.84470588235294162.418
934612AD1-087 E
Adder
3.09529411764705882.631
934622AD1-088 E
Adder
3.98588235294117643.388
316336AC2-165 C
Adder
8.9188235294117667.581
926004AC1-076_E
50/50
6.3656.365
940641AE2-051 C
50/50
15.79315.793
316084AB2-161 E
Adder
3.8047058823529413.234
926214AC1-099 E
Adder
0.90470588235294120.769
932632AC2-084 E
Adder
2.4211764705882352.058
962572AG1-106 E
Adder
0.90705882352941180.771
934521AD1-076 C
Adder
8.8788235294117657.547
934511AD1-075 C
Adder
6.1117647058823535.195
919692AA2-053 E OP
Adder
3.2129411764705882.731
923573AB1-173 E OP
Adder
2.53764705882352942.157
3145723EMPORIA
Adder
0.33529411764705880.285
920042AA2-088 E OP
Adder
7.8352941176470596.66
925785AC1-054 E
Adder
2.6835294117647062.281
919152AA1-139 E1
Adder
2.8741176470588242.443
959311AF2-222 C
Adder
13.3576470588235311.354
926502AC1-121 E
50/50
1.4471.447
942342AE2-247 E
Adder
1.43764705882352951.222
957872AF2-081 E
Adder
3.0117647058823532.56
924162AB2-060 E OP
Adder
3.4164705882352942.904
964242AG1-285 E
Adder
6.6741176470588245.673
964792AG1-342 E
Adder
1.85529411764705881.577
932763AC2-100 E
Adder
1.9282352941176471.639
934862AD1-115 E
50/50
5.7435.743
938562AE1-075 E
Adder
0.96941176470588230.824
3152251N ANNA1
50/50
104.031104.031
938552AE1-074 E
Adder
1.04470588235294120.888
926755AC1-161 E
Adder
9.0070588235294127.656
933291AC2-141 C
Adder
21.09882352941176717.934
925522AC1-027 E
Adder
0.85058823529411760.723
941102AE2-104 E
Adder
3.75294117647058823.19
3145256KINGFORK
Adder
0.68588235294117650.583
957862AF2-080 E
Adder
2.5105882352941182.134
926072AC1-086 E
Adder
7.29529411764705856.201
960081AF2-299 C
Adder
1.45882352941176461.24
3145413WATKINS
Adder
0.50352941176470590.428
936261AD2-033 C
Adder
10.415294117647068.853
962562AG1-105 E
Adder
4.6635294117647063.964
961791AG1-021 C
Adder
1.4435294117647061.227
938771AE1-103 C
Adder
2.1082352941176471.792
924032AB2-045 E
Adder
1.06588235294117650.906
963041AG1-153 C
Adder
5.1482352941176474.376
316170AC1-121 C
50/50
3.0753.075
944011AF1-069 C
50/50
12.15212.152
316045AC1-158 C2
50/50
18.54118.541
944591AF1-124 C
Adder
32.24705882352941427.41
944601AF1-125 C
Adder
31.6376470588235326.892
941591AE2-156 C
Adder
12.46588235294117710.596
936666AD2-085 E
Adder
3.923.332
961942AG1-037 E
Adder
0.249411764705882360.212
961941AG1-037 C
Adder
0.37294117647058830.317
927022AC1-189 E
Adder
3.10588235294117652.64
934322AD1-056 E
Adder
2.562.176
934332AD1-057 E
Adder
1.37058823529411771.165
934321AD1-056 C
Adder
4.7188235294117654.011
934331AD1-057 C
Adder
2.6329411764705882.238
923852AB2-025 E
Adder
0.9317647058823530.792
936262AD2-033 E
Adder
6.9435294117647075.902
958211AF2-115 C
Adder
1.80470588235294121.534
208900BRIS G1
50/50
-2.42-2.42
3151761LOISA E
50/50
7.047.04
3151771S ANNAG1
50/50
3.3573.357
3151791S ANNAG2
50/50
3.3573.357
3151781S ANNAS1
50/50
1.7251.725
923862AB2-026 E
Adder
1.13764705882352950.967
941031AE2-094 C
50/50
37.19337.193
941032AE2-094 E
50/50
16.65816.658
939412AE1-173 E
Adder
52.19411764705882544.365
926662AC1-147 E
Adder
0.92117647058823540.783
916192Z1-068 E
Adder
1.31411764705882361.117
957492AF2-043 E
Adder
0.99882352941176470.849
920692AA2-178 E
Adder
2.9635294117647062.519
966622AG1-532 E
Adder
0.72941176470588230.62
917122Z2-027 E
Adder
0.94941176470588240.807
3146326AYDLETT TAP
Adder
0.95411764705882360.811
938532AE1-072 E
Adder
6.4470588235294135.48
927264AC1-222 E
Adder
3.0847058823529412.622
3147133PAMPLIN
Adder
0.79882352941176480.679
966002AG1-469 E
50/50
1.231.23
926739AC1-158 E1
50/50
48.49548.495
316233AE1-074 C
Adder
2.07294117647058851.762
943461AF1-017 C
Adder
0.94235294117647060.801
316311AC2-079 C
Adder
4.00705882352941253.406
932596AC2-079 E
Adder
6.5388235294117655.558
933981AD1-022 C
Adder
6.3764705882352955.42
900672V4-068 E
Adder
0.26352941176470590.224
938531AE1-072 C
Adder
12.36823529411764810.513
924302AB2-077 E O1
Adder
1.06588235294117650.906
3145393UNCAMP
Adder
4.3976470588235293.738
926486AC1-120 E
50/50
4.6124.612
932046AC2-012 E
Adder
9.1176470588235297.75
958161AF2-110 C
Adder
0.96352941176470590.819
918512AA1-065 E OP
Adder
4.06000000000000053.451
918532AA1-067 E
Adder
0.52705882352941180.448
934502AD1-074 E
Adder
12.44588235294117810.579
934512AD1-075 E
Adder
3.1117647058823532.645
924516AB2-100 E1
Adder
2.26000000000000021.921
966621AG1-532 C
Adder
1.09411764705882360.93
919153AA1-139 E2
Adder
2.8741176470588242.443
924022AB2-043 E O1
Adder
4.1364705882352943.516
3147223TWITTYS
Adder
0.76235294117647070.648
959312AF2-222 E
Adder
8.9494117647058827.607
934861AD1-115 C
50/50
3.523.52
3152261N ANNA2
50/50
104.075104.075
940642AE2-051 E
50/50
10.52910.529
942341AE2-247 C
Adder
1.04117647058823540.885
943462AF1-017 E
Adder
1.53764705882352941.307
958162AF2-110 E
Adder
1.53176470588235311.302
919710AA2-057 E
Adder
2.97647058823529382.53
3137643SOCKMAN
Adder
0.54705882352941180.465
913392Y1-086 E
Adder
1.5517647058823531.319
933502AC2-165 E
Adder
6.7129411764705895.706
3151741LOISA C
50/50
3.4533.453
3151721LOISA A
50/50
3.4353.435
939411AE1-173 C
Adder
78.2905882352941166.547
934501AD1-074 C
Adder
24.44941176470588220.782
924517AB2-100 E2
Adder
2.26000000000000021.921
937226AE2-253 E
Adder
4.1070588235294123.491
946301AF1-294 C
Adder
2.96705882352941152.522
935172AD1-152 E
Adder
4.5494117647058833.867
942461AE2-259 C
Adder
8.0294117647058826.825
934621AD1-088 C
Adder
8.277647058823537.036
957482AF2-042 E
Adder
31.4626.741
208901BRIS G2
50/50
-2.864-2.864
958502AF2-144 E
Adder
1.11764705882352940.95
316192AB2-158 C
50/50
4.384.38
942001AE2-212 C
Adder
1.40588235294117661.195
939192AE1-149 E
Adder
4.87529411764705944.144
934065AD1-033 E
Adder
3.5188235294117652.991
957861AF2-080 C
Adder
5.6635294117647064.814
946282AF1-292 E
Adder
0.80470588235294130.684
3138533PONTONDP
Adder
0.53411764705882360.454
316257AC1-043 C
50/50
7.047.04
316254AC1-120 C
50/50
8.9538.953
927021AC1-189 C
Adder
6.2352941176470595.3
926071AC1-086 C
Adder
16.0282352941176513.624
946281AF1-292 C
Adder
1.2082352941176471.027
960082AF2-299 E
Adder
0.97294117647058820.827
916042Z1-036 E
Adder
20.41647058823529517.354
923832AB2-022 E
Adder
0.87529411764705890.744
964241AG1-285 C
Adder
10.0105882352941198.509
962561AG1-105 C
Adder
6.9952941176470595.946
958212AF2-115 E
Adder
1.53764705882352941.307
938772AE1-103 E
Adder
2.91176470588235332.475
963042AG1-153 E
Adder
7.7235294117647076.565
925022AB2-158 E
50/50
11.64111.641
316044AC1-158 C1
50/50
18.54118.541
944592AF1-124 E
Adder
73.8458823529411762.769
944582AF1-123 E
Adder
73.5862.543
316349AD2-085 C
Adder
2.40235294117647062.042
935112AD1-144 E
Adder
0.63647058823529420.541
944012AF1-069 E
50/50
4.7214.721
316303AF2-085
50/50
3.8863.886
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.2284.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
73.97573.975
CPLELTFEXP_CPLE->PJM
CLTF
8.8738.873
TVALTFEXP_TVA->PJM
CLTF
4.5234.523
O66PJM->LTFIMP_O-066
CMTX_NF
31.31531.315
NYPJM->LTFIMP_NY
CLTF
2.3072.307
LGEELTFEXP_LGEE->PJM
CLTF
0.8310.831
WECLTFEXP_WEC->PJM
CLTF
0.410.41
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.05119.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.10316.103
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
2.6562.656
LAGNLTFEXP_LAGN->PJM
CLTF
5.7065.706
G-007PJM->LTFIMP_G-007
CMTX_NF
4.9174.917
SIGELTFEXP_SIGE->PJM
CLTF
0.1650.165

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.97 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3767.03
MW Contribution:5.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
30.18352941176470625.656
961671AG1-007 C
Adder
0.82941176470588230.705
946301AF1-294 C
Adder
3.3141176470588242.817
942461AE2-259 C
Adder
8.8929411764705887.559
934621AD1-088 C
80/20
9.29.2
208901BRIS G2
80/20
-3.03-3.03
316192AB2-158 C
80/20
3.5593.559
942001AE2-212 C
Adder
1.8635294117647061.584
934521AD1-076 C
Adder
10.9623529411764719.318
934511AD1-075 C
Adder
7.54588235294117656.414
316263AC1-034 C
Adder
5.8505882352941184.973
316087AB2-174 C
80/20
1.0751.075
316321Z2-027 C
80/20
0.3250.325
959311AF2-222 C
Adder
14.9976470588235312.748
937481AD2-202 C
80/20
0.3460.346
3151031BRUNSWICKG2
80/20
8.3898.389
316240AF1-291 C
Adder
1.78117647058823541.514
944641AF1-129 C
Adder
83.2882352941176570.795
316036AC1-147 C
80/20
0.3280.328
316305AF2-043 C
80/20
0.3110.311
3156056W1-029WIND
80/20
0.6930.693
3152411Z1-086 GT1
80/20
10.75310.753
3152421Z1-086 GT2
80/20
10.7510.75
316233AE1-074 C
80/20
2.4792.479
943461AF1-017 C
80/20
1.2041.204
316311AC2-079 C
80/20
5.125.12
316274AC1-208 C
Adder
8.077647058823536.866
962571AG1-106 C
Adder
2.4670588235294122.097
3151311EDGECMA
Adder
13.67647058823529511.625
957871AF2-081 C
80/20
8.9458.945
316405AF2-144 C
80/20
0.30.3
3150651CHESTF6
Adder
15.16470588235294212.89
3150861SPRUNCD
80/20
0.140.14
316181AB2-040 GEN
80/20
1.1581.158
3147043LAWRENC
80/20
0.2810.281
940481AE2-033 C
80/20
15.30215.302
940541AE2-040 C
80/20
2.7232.723
3152441Z1-086 ST
80/20
18.71718.717
966001AG1-469 C
Adder
1.43764705882352951.222
961611AG1-000B C
Adder
13.19882352941176511.219
316375AC2-012 C
80/20
1.2021.202
316072AD1-144 C
80/20
0.2460.246
313506AB1-173 C OP
80/20
1.0281.028
966621AG1-532 C
80/20
1.2891.289
316320Y1-086 C
80/20
0.1960.196
316388AE2-253 GEN
80/20
1.7531.753
935171AD1-152 C
80/20
1.2331.233
3151021BRUNSWICKG1
80/20
8.3898.389
3151041BRUNSWICKG3
80/20
8.3898.389
3152261N ANNA2
80/20
92.75992.759
942341AE2-247 C
80/20
1.3311.331
316246AF1-032 C
80/20
0.2540.254
316365AB2-100 C1
80/20
0.8850.885
957481AF2-042 C
80/20
52.44752.447
3151801S ANNAS2
80/20
1.2181.218
940431AE2-027 C
Adder
10.6976470588235299.093
316294AC1-161 C
80/20
4.4154.415
944581AF1-123 C
80/20
40.90340.903
316185AD1-033 C
80/20
1.0971.097
916191Z1-068 C
80/20
0.0390.039
941101AE2-104 C
80/20
3.0013.001
313526AB2-022 C
80/20
0.3360.336
316017AA1-139 ULT1
80/20
0.9650.965
934611AD1-087 C
80/20
1.1911.191
3152431Z1-086 GT3
80/20
10.7510.75
316336AC2-165 C
80/20
9.7879.787
940641AE2-051 C
80/20
17.817.8
964791AG1-342 C
Adder
3.14588235294117662.674
3151731LOISA B
80/20
2.3872.387
3151751LOISA D
80/20
2.3872.387
316313AB2-026 C
80/20
0.3850.385
939191AE1-149 C
80/20
9.4869.486
3150981CHESPKA
80/20
0.3880.388
961941AG1-037 C
Adder
0.454117647058823570.386
934321AD1-056 C
Adder
5.5882352941176484.75
934331AD1-057 C
Adder
3.11764705882352942.65
958211AF2-115 C
Adder
2.0152941176470591.713
3151531CLOVER1
80/20
12.09912.099
208900BRIS G1
80/20
-2.561-2.561
3151761LOISA E
80/20
4.8664.866
3151771S ANNAG1
80/20
2.372.37
3151791S ANNAG2
80/20
2.372.37
3151781S ANNAS1
80/20
1.2181.218
316258AE1-075 C
80/20
0.3530.353
941031AE2-094 C
80/20
41.10641.106
3150831SPRUNCA
Adder
7.7905882352941186.622
3150841SPRUNCB
Adder
7.7905882352941186.622
3151081ELIZAR1
80/20
2.8512.851
316018AA1-139 ULT2
80/20
0.9650.965
3152251N ANNA1
80/20
92.7292.72
3150851SPRUNCC
80/20
0.140.14
944631AF1-128 C
Adder
28.33882352941176624.088
933291AC2-141 C
80/20
27.11427.114
3150921YORKTN3
Adder
92.4352941176470578.57
933981AD1-022 C
Adder
7.84941176470588256.672
938531AE1-072 C
80/20
15.7315.73
3150731STONECA
Adder
5.4352941176470594.62
935161AD1-151 C
Adder
13.03882352941176511.083
316083AB2-161 C
80/20
0.4890.489
958161AF2-110 C
80/20
1.2251.225
927021AC1-189 C
Adder
7.4435294117647066.327
926071AC1-086 C
Adder
19.07647058823529616.215
946281AF1-292 C
80/20
1.4231.423
964241AG1-285 C
Adder
11.3035294117647079.608
962561AG1-105 C
Adder
7.9117647058823526.725
3151091ELIZAR2
80/20
2.8012.801
316349AD2-085 C
80/20
3.0713.071
960081AF2-299 C
80/20
1.7191.719
936261AD2-033 C
Adder
11.7211764705882359.963
961791AG1-021 C
Adder
1.61176470588235321.37
938771AE1-103 C
80/20
2.6332.633
963041AG1-153 C
80/20
5.7035.703
3151051BRUNSWICKS1
80/20
17.42917.429
944011AF1-069 C
80/20
13.43113.431
3150601CHESTF5
Adder
45.29058823529411638.497
944591AF1-124 C
80/20
41.04941.049
944601AF1-125 C
80/20
40.27340.273
3151101ELIZAR3
80/20
2.8872.887
941591AE2-156 C
80/20
15.98415.984
957861AF2-080 C
Adder
6.7600000000000015.746
316023AB2-100 C2
80/20
0.8850.885
316315AB2-025 C
80/20
0.3860.386
3138533PONTONDP
Adder
0.59764705882352940.508
3151541CLOVER2
80/20
11.98611.986
316316AC1-027 C
80/20
0.2820.282
3137643SOCKMAN
Adder
0.64823529411764710.551
3151741LOISA C
80/20
2.3872.387
3151721LOISA A
80/20
2.3742.374
939411AE1-173 C
80/20
90.4790.47
316381AD1-082 C
80/20
1.1161.116
3150991CHESPKB
80/20
0.6430.643
316303AF2-085
80/20
4.3034.303
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.8954.895
CBM South 2LTFEXP_CBM-S2->PJM
CBM
86.42786.427
CPLELTFEXP_CPLE->PJM
CLTF
10.2710.27
TVALTFEXP_TVA->PJM
CLTF
5.5015.501
NYPJM->LTFIMP_NY
CLTF
2.4542.454
LGEELTFEXP_LGEE->PJM
CLTF
1.0841.084
WECLTFEXP_WEC->PJM
CLTF
0.5370.537
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.18225.182
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.8619.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.3753.375
LAGNLTFEXP_LAGN->PJM
CLTF
6.9186.918
SIGELTFEXP_SIGE->PJM
CLTF
0.2110.211

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.22 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3678.49
MW Contribution:5.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
36.4552941176470630.987
961671AG1-007 C
Adder
0.95176470588235310.809
946301AF1-294 C
Adder
3.5305882352941183.001
942461AE2-259 C
Adder
9.4035294117647077.993
934621AD1-088 C
Adder
9.6105882352941188.169
942001AE2-212 C
80/20
2.4472.447
962861AG1-135 C
Adder
6.3647058823529425.41
943741AF1-042 C
Adder
3.06352941176470632.604
934521AD1-076 C
Adder
13.2411.254
934511AD1-075 C
Adder
9.1141176470588237.747
316263AC1-034 C
Adder
6.6529411764705895.655
959311AF2-222 C
Adder
16.0552941176470613.647
316240AF1-291 C
80/20
2.4442.444
944641AF1-129 C
80/20
115.84115.84
3150781HOPHCF2
80/20
2.7332.733
3150761HOPPOLC
80/20
1.7191.719
316233AE1-074 C
80/20
2.8742.874
940551AE2-041 C
Adder
7.6152941176470596.473
943461AF1-017 C
Adder
1.51764705882352961.29
316311AC2-079 C
Adder
6.4458823529411775.479
316274AC1-208 C
Adder
9.2835294117647067.891
962571AG1-106 C
Adder
2.84117647058823542.415
3151311EDGECMA
Adder
15.55647058823529613.223
957871AF2-081 C
Adder
11.2117647058823529.53
3150651CHESTF6
80/20
21.09121.091
3150861SPRUNCD
80/20
0.1870.187
936591AD2-074 C
Adder
5.8552941176470594.977
940481AE2-033 C
Adder
17.43882352941176714.823
940541AE2-040 C
Adder
3.10117647058823562.636
927041AC1-191 C
Adder
10.2870588235294128.744
963611AG1-210 C
Adder
0.68235294117647060.58
961611AG1-000B C
Adder
17.92352941176470415.235
316375AC2-012 C
80/20
1.521.52
966621AG1-532 C
Adder
1.46470588235294131.245
934861AD1-115 C
Adder
-3.06-2.601
3152261N ANNA2
80/20
56.72156.721
3150771HOPHCF1
80/20
2.7332.733
942341AE2-247 C
Adder
1.67764705882352931.426
957481AF2-042 C
Adder
54.6470588235294146.45
940431AE2-027 C
80/20
14.61614.616
316294AC1-161 C
80/20
5.5975.597
944581AF1-123 C
80/20
51.27751.277
941101AE2-104 C
Adder
3.75764705882352963.194
316336AC2-165 C
Adder
10.1788235294117648.652
940641AE2-051 C
80/20
18.8818.88
943471AF1-018 C
Adder
7.6152941176470596.473
3152331SURRY 2
80/20
27.86527.865
964791AG1-342 C
Adder
3.38000000000000032.873
961941AG1-037 C
Adder
0.53764705882352950.457
934321AD1-056 C
Adder
6.3870588235294125.429
934331AD1-057 C
Adder
3.5635294117647063.029
958211AF2-115 C
Adder
2.14705882352941171.825
941031AE2-094 C
80/20
42.24742.247
3150831SPRUNCA
80/20
10.42510.425
3150841SPRUNCB
80/20
10.42510.425
966871AG1-558 C
Adder
2.56235294117647072.178
964211AG1-282 C
Adder
2.07882352941176451.767
3150801HOPHCF4
80/20
4.1494.149
3151081ELIZAR1
80/20
3.6013.601
3152251N ANNA1
80/20
56.69756.697
3150851SPRUNCC
80/20
0.1870.187
944631AF1-128 C
Adder
44.0564705882352937.448
933291AC2-141 C
80/20
34.37234.372
3150921YORKTN3
Adder
133.0105882352941113.059
3143096IRON208
80/20
0.4940.494
958261AF2-120 C
Adder
6.5505882352941175.568
939191AE1-149 C
80/20
12.15312.153
957601AF2-054 C
Adder
2.26000000000000021.921
933981AD1-022 C
Adder
9.4470588235294128.03
938531AE1-072 C
Adder
19.70000000000000316.745
3142366NRTHEST
80/20
0.2040.204
3150731STONECA
80/20
7.7657.765
935161AD1-151 C
Adder
18.16235294117647215.438
958161AF2-110 C
Adder
1.53294117647058831.303
927021AC1-189 C
Adder
8.6023529411764727.312
926071AC1-086 C
Adder
21.9611764705882418.667
946281AF1-292 C
Adder
1.61647058823529431.374
964241AG1-285 C
Adder
12.1610.336
962561AG1-105 C
Adder
8.5058823529411767.23
939261AE1-157 C
Adder
14.10235294117647211.987
316169AC1-164 GEN
Adder
43.66588235294117537.116
3151091ELIZAR2
80/20
3.5383.538
316349AD2-085 C
Adder
3.87058823529411773.29
960081AF2-299 C
Adder
1.95294117647058821.66
936261AD2-033 C
Adder
12.57294117647058810.687
961791AG1-021 C
Adder
1.71764705882352931.46
938771AE1-103 C
Adder
3.22705882352941182.743
963041AG1-153 C
Adder
5.8858823529411765.003
944011AF1-069 C
80/20
13.80413.804
966881AG1-559 C
Adder
2.45176470588235332.084
3150601CHESTF5
Adder
70.4105882352941159.849
944591AF1-124 C
80/20
51.4651.46
944601AF1-125 C
80/20
50.48850.488
3151101ELIZAR3
80/20
3.6473.647
941591AE2-156 C
80/20
20.20920.209
957861AF2-080 C
Adder
7.8129411764705896.641
3138533PONTONDP
Adder
0.63647058823529420.541
316257AC1-043 C
Adder
-6.121176470588236-5.203
316254AC1-120 C
Adder
-6.376470588235295-5.42
3150791HOPHCF3
80/20
2.7332.733
961951AG1-038 C
Adder
3.3858823529411772.878
3137643SOCKMAN
Adder
0.74235294117647070.631
966661AG1-536 C
Adder
5.6341176470588234.789
939411AE1-173 C
80/20
99.71499.714
3150991CHESPKB
80/20
0.8130.813
316303AF2-085
80/20
4.4474.447
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.4135.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69496.694
CPLELTFEXP_CPLE->PJM
CLTF
11.35211.352
TVALTFEXP_TVA->PJM
CLTF
6.4156.415
NYPJM->LTFIMP_NY
CLTF
2.72.7
LGEELTFEXP_LGEE->PJM
CLTF
1.331.33
WECLTFEXP_WEC->PJM
CLTF
0.6540.654
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.72830.728
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.33523.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
4.0414.041
LAGNLTFEXP_LAGN->PJM
CLTF
8.0268.026
SIGELTFEXP_SIGE->PJM
CLTF
0.2560.256

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.99 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4412.36
MW Contribution:14.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
31.6952941176470626.941
924517AB2-100 E2
Adder
2.82.38
937226AE2-253 E
Adder
5.5047058823529414.679
946301AF1-294 C
Adder
3.45529411764705862.937
935172AD1-152 E
Adder
5.2941176470588234.5
942461AE2-259 C
Adder
9.2705882352941187.88
934621AD1-088 C
Adder
9.5599999999999998.126
957482AF2-042 E
Adder
36.31529411764705630.868
208901BRIS G2
50/50
-3.245-3.245
958502AF2-144 E
Adder
1.2764705882352941.085
316192AB2-158 C
50/50
3.5873.587
942001AE2-212 C
Adder
1.96941176470588241.674
939192AE1-149 E
Adder
6.6670588235294125.667
939312AE1-162 E
Adder
1.29647058823529431.102
934065AD1-033 E
Adder
4.7282352941176474.019
920692AA2-178 E
Adder
3.86941176470588263.289
966622AG1-532 E
Adder
0.89882352941176480.764
917122Z2-027 E
Adder
1.26588235294117671.076
3146326AYDLETT TAP
Adder
1.27764705882352961.086
938532AE1-072 E
Adder
8.6305882352941187.336
3147133PAMPLIN
Adder
0.92823529411764720.789
3152411Z1-086 GT1
50/50
11.14911.149
3152421Z1-086 GT2
50/50
11.14611.146
966002AG1-469 E
Adder
0.73058823529411760.621
316233AE1-074 C
50/50
2.5912.591
935162AD1-151 E
Adder
0.93764705882352950.797
943461AF1-017 C
Adder
1.26823529411764711.078
316311AC2-079 C
Adder
5.3905882352941184.582
932596AC2-079 E
Adder
8.7952941176470587.476
923263AB1-132 E OP
Adder
5.80941176470588254.938
940481AE2-033 C
Adder
15.98588235294117513.588
940482AE2-033 E
Adder
10.777647058823539.161
940541AE2-040 C
Adder
2.84470588235294162.418
924312AB2-078 E O1
Adder
1.25764705882352931.069
925612AC1-036 E
Adder
0.80588235294117660.685
3152441Z1-086 ST
50/50
19.40819.408
966001AG1-469 C
Adder
1.46235294117647091.243
943172AE2-346 E
Adder
0.5717647058823530.486
917332KELFORD E
Adder
1.54588235294117651.314
934522AD1-076 E
Adder
5.8670588235294124.987
940492AE2-034 E
Adder
2.90235294117647062.467
961611AG1-000B C
Adder
13.98823529411764911.89
316141AB2-099 E
Adder
0.237647058823529430.202
923994AB2-040_E
Adder
5.8811764705882354.999
316088AB2-174 E
Adder
6.242352941176475.306
924322AB2-079 E O1
Adder
1.25764705882352931.069
946302AF1-294 E
Adder
2.9258823529411772.487
957481AF2-042 C
Adder
54.4729411764705946.302
3151801S ANNAS2
50/50
1.2331.233
942002AE2-212 E
Adder
1.31294117647058851.116
940431AE2-027 C
Adder
11.3411764705882369.64
944581AF1-123 C
Adder
43.0529411764705936.595
941101AE2-104 C
Adder
3.1588235294117652.685
901082W1-029 E
Adder
30.02588235294117425.522
942462AE2-259 E
Adder
6.1800000000000015.253
3151731LOISA B
50/50
2.4192.419
3151751LOISA D
50/50
2.4192.419
3143316POE
Adder
1.30941176470588231.113
939191AE1-149 C
Adder
10.0011764705882348.501
962571AG1-106 C
Adder
2.58235294117647032.195
918492AA1-063AE OP
Adder
3.87294117647058833.292
957871AF2-081 C
Adder
9.4164705882352948.004
961792AG1-021 E
Adder
1.4317647058823531.217
937482AD2-202 E
Adder
1.04941176470588250.892
3145506HICKORY
Adder
2.05411764705882361.746
946262AF1-291 E
Adder
1.261.071
3150651CHESTF6
Adder
16.10470588235294213.689
933292AC2-141 E
Adder
12.19411764705882510.365
934576AD1-082 E
Adder
4.1188235294117653.501
944602AF1-125 E
Adder
97.0388235294117782.483
943612AF1-032 E
Adder
0.87058823529411770.74
933982AD1-022 E
Adder
4.4858823529411773.813
3145946PLYMOUTH TP
Adder
0.30352941176470590.258
934612AD1-087 E
Adder
3.5835294117647063.046
934622AD1-088 E
Adder
4.6035294117647063.913
3152431Z1-086 GT3
50/50
11.14611.146
316336AC2-165 C
Adder
10.1788235294117648.652
940641AE2-051 C
50/50
18.48718.487
316084AB2-161 E
Adder
5.1694117647058834.394
933981AD1-022 C
Adder
8.247.004
900672V4-068 E
Adder
0.33764705882352940.287
938531AE1-072 C
Adder
16.55647058823529614.073
924302AB2-077 E O1
Adder
1.25764705882352931.069
3145393UNCAMP
Adder
5.7482352941176484.886
935161AD1-151 C
Adder
13.84941176470588311.772
932046AC2-012 E
Adder
12.31647058823529410.469
958161AF2-110 C
Adder
1.28941176470588251.096
962572AG1-106 E
Adder
1.12941176470588230.96
957872AF2-081 E
Adder
4.0352941176470593.43
924162AB2-060 E OP
Adder
4.0294117647058823.425
964242AG1-285 E
Adder
7.8564705882352946.678
938562AE1-075 E
Adder
1.1082352941176470.942
3152251N ANNA1
50/50
93.18793.187
938552AE1-074 E
50/50
1.3051.305
926755AC1-161 E
Adder
12.19411764705882510.365
933291AC2-141 C
Adder
28.56588235294117724.281
925522AC1-027 E
Adder
1.14588235294117660.974
941102AE2-104 E
Adder
5.0223529411764714.269
3145256KINGFORK
Adder
0.93882352941176480.798
934521AD1-076 C
Adder
11.5105882352941199.784
934511AD1-075 C
Adder
7.9235294117647066.735
919692AA2-053 E OP
Adder
4.00705882352941253.406
923573AB1-173 E OP
Adder
3.1364705882352942.666
3145723EMPORIA
Adder
0.414117647058823530.352
920042AA2-088 E OP
Adder
10.0447058823529418.538
925785AC1-054 E
Adder
3.24941176470588242.762
919152AA1-139 E1
Adder
3.8505882352941183.273
959311AF2-222 C
Adder
15.63529411764705813.29
3151031BRUNSWICKG2
50/50
8.78.7
316240AF1-291 C
Adder
1.88941176470588261.606
944641AF1-129 C
Adder
88.4505882352941375.183
924814AB2-134 E
Adder
10.9235294117647069.285
942342AE2-247 E
Adder
1.93529411764705881.645
961942AG1-037 E
Adder
0.317647058823529450.27
961941AG1-037 C
Adder
0.476470588235294150.405
923852AB2-025 E
Adder
1.15058823529411770.978
936262AD2-033 E
Adder
8.1458823529411776.924
958211AF2-115 C
Adder
2.1011764705882351.786
3151761LOISA E
50/50
4.9314.931
3151771S ANNAG1
50/50
2.42.4
3151791S ANNAG2
50/50
2.42.4
3151781S ANNAS1
50/50
1.2331.233
923862AB2-026 E
Adder
1.31.105
941031AE2-094 C
50/50
42.60742.607
941032AE2-094 E
50/50
19.08319.083
3150831SPRUNCA
Adder
8.2435294117647067.007
3150841SPRUNCB
Adder
8.2435294117647067.007
939412AE1-173 E
50/50
62.82462.824
926072AC1-086 E
Adder
9.0847058823529427.722
960081AF2-299 C
Adder
1.7964705882352941.527
3145413WATKINS
Adder
0.65411764705882360.556
936261AD2-033 C
Adder
12.2210.387
961791AG1-021 C
Adder
1.68117647058823551.429
938771AE1-103 C
Adder
2.7670588235294122.352
963041AG1-153 C
50/50
5.9155.915
3151051BRUNSWICKS1
50/50
18.07518.075
944011AF1-069 C
50/50
13.92113.921
927226AC1-216 E
Adder
6.6694117647058825.669
944591AF1-124 C
Adder
43.2058823529411836.725
944601AF1-125 C
Adder
42.3894117647058836.031
941591AE2-156 C
Adder
16.83647058823529414.311
936666AD2-085 E
Adder
5.2764705882352954.485
926662AC1-147 E
Adder
1.24470588235294131.058
916192Z1-068 E
Adder
1.77058823529411761.505
957492AF2-043 E
Adder
1.341.139
918512AA1-065 E OP
Adder
5.2011764705882364.421
934502AD1-074 E
Adder
16.13411764705882613.714
934512AD1-075 E
Adder
4.0341176470588243.429
924516AB2-100 E1
Adder
2.82.38
966621AG1-532 C
Adder
1.34705882352941191.145
919153AA1-139 E2
Adder
3.8505882352941183.273
924022AB2-043 E O1
Adder
4.8811764705882354.149
3147223TWITTYS
Adder
0.89294117647058820.759
959312AF2-222 E
Adder
10.4764705882352948.905
3151021BRUNSWICKG1
50/50
8.78.7
3151041BRUNSWICKG3
50/50
8.78.7
3152261N ANNA2
50/50
93.22693.226
940642AE2-051 E
50/50
12.32512.325
942341AE2-247 C
Adder
1.40235294117647061.192
943462AF1-017 E
Adder
2.06941176470588231.759
958162AF2-110 E
Adder
2.0505882352941181.743
3137643SOCKMAN
Adder
0.67882352941176470.577
913392Y1-086 E
Adder
2.0705882352941181.76
933502AC2-165 E
Adder
7.6611764705882356.512
940432AE2-027 E
Adder
7.5611764705882356.427
939411AE1-173 C
50/50
94.23794.237
934012AD1-025 E
Adder
8.6341176470588247.339
946282AF1-292 E
Adder
0.99176470588235290.843
3138533PONTONDP
Adder
0.62235294117647070.529
944012AF1-069 E
50/50
5.4085.408
926071AC1-086 C
Adder
19.96117647058823516.967
946281AF1-292 C
Adder
1.48705882352941181.264
960082AF2-299 E
Adder
1.19764705882352951.018
916042Z1-036 E
Adder
26.91882352941176422.881
923832AB2-022 E
Adder
1.1682352941176470.993
964241AG1-285 C
Adder
11.78352941176470610.016
958212AF2-115 E
Adder
1.78941176470588231.521
938772AE1-103 E
Adder
3.8211764705882363.248
963042AG1-153 E
50/50
8.8728.872
925022AB2-158 E
50/50
9.5359.535
944592AF1-124 E
Adder
98.9435294117647184.102
944582AF1-123 E
Adder
98.5858823529411883.798
316349AD2-085 C
Adder
3.23411764705882382.749
935112AD1-144 E
Adder
0.8717647058823530.741
316303AF2-085
50/50
4.464.46
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1255.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.8190.81
CPLELTFEXP_CPLE->PJM
CLTF
10.7510.75
TVALTFEXP_TVA->PJM
CLTF
5.8785.878
O66PJM->LTFIMP_O-066
CMTX_NF
35.46935.469
NYPJM->LTFIMP_NY
CLTF
2.6122.612
LGEELTFEXP_LGEE->PJM
CLTF
1.1951.195
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.02528.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.37921.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.6863.686
LAGNLTFEXP_LAGN->PJM
CLTF
7.3867.386
G-007PJM->LTFIMP_G-007
CMTX_NF
5.5685.568
SIGELTFEXP_SIGE->PJM
CLTF
0.2320.232

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4342.97
MW Contribution:17.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316359AB2-059 C OP
80/20
1.1351.135
316283AC2-100 C
80/20
2.3262.326
946301AF1-294 C
80/20
5.4265.426
316197AC1-042 C
80/20
0.3460.346
942461AE2-259 C
80/20
14.02314.023
934621AD1-088 C
80/20
24.38424.384
942001AE2-212 C
Adder
-2.1176470588235294-1.8
316263AC1-034 C
80/20
4.5164.516
3151591KERR 2
80/20
1.8191.819
959311AF2-222 C
80/20
25.13225.132
316205AC1-080 C
80/20
0.5050.505
316123AC1-075 C
80/20
1.5121.512
942751AE2-291 C
80/20
13.51213.512
24684705SMG5
80/20
1.2291.229
3151561HALLBR1
80/20
1.2391.239
937481AD2-202 C
80/20
0.9380.938
3151031BRUNSWICKG2
80/20
25.36825.368
316240AF1-291 C
Adder
-2.031764705882353-1.727
944641AF1-129 C
Adder
-95.19529411764705-80.916
3152411Z1-086 GT1
80/20
32.08832.088
3152421Z1-086 GT2
80/20
32.07932.079
3151311EDGECMA
80/20
10.35810.358
3152661PLYWOOD A
80/20
2.3542.354
24684405SMG2
80/20
3.2353.235
24728405LEESVG
80/20
0.9740.974
3152441Z1-086 ST
80/20
55.85455.854
3151601KERR 3
80/20
1.8191.819
3151581KERR 1
80/20
0.650.65
936161AD2-022 C
80/20
12.80112.801
270197AC1-083 C
80/20
0.9970.997
24684605SMG4
80/20
3.2353.235
935171AD1-152 C
80/20
3.2243.224
3151021BRUNSWICKG1
80/20
25.36825.368
3151041BRUNSWICKG3
80/20
25.36825.368
316003AC1-222 C
80/20
1.9581.958
957481AF2-042 C
80/20
148.174148.174
3151611KERR 4
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
316237AB2-079 C O1
80/20
0.5160.516
316222AC1-221 C
80/20
2.9052.905
958211AF2-115 C
80/20
3.33.3
3151531CLOVER1
80/20
32.84832.848
941031AE2-094 C
80/20
119.094119.094
964211AG1-282 C
Adder
-1.7882352941176471-1.52
3151641KERR 7
80/20
1.8191.819
313527AB2-043 C
80/20
0.8060.806
933291AC2-141 C
Adder
-33.98823529411765-28.89
316239AB2-077 C O1
80/20
0.5160.516
964791AG1-342 C
80/20
6.5026.502
940081AE1-250 C
80/20
13.65313.653
957601AF2-054 C
Adder
-1.8941176470588237-1.61
934611AD1-087 C
80/20
3.2323.232
3152431Z1-086 GT3
80/20
32.07932.079
940641AE2-051 C
Adder
-22.240000000000002-18.904
316049AB1-081 C OP
80/20
0.9630.963
938531AE1-072 C
Adder
-16.896470588235296-14.362
316238AB2-078 C O1
80/20
0.5160.516
316322AB2-045 C
80/20
0.2670.267
964241AG1-285 C
80/20
19.39519.395
962561AG1-105 C
80/20
15.92115.921
316034AC1-036 C
80/20
0.3540.354
316118AC1-105 C
80/20
1.7691.769
943811AF1-049 C
80/20
9.4269.426
3144293JTRSVLE
80/20
0.6050.605
938741AE1-100 C
80/20
0.7290.729
941671AE2-166 C
80/20
5.7085.708
942671AE2-283 C
80/20
3.7323.732
316217AC1-145 C
80/20
0.4120.412
936171AD2-023 C
80/20
7.4677.467
936261AD2-033 C
80/20
19.83719.837
316248AF1-058 C
80/20
0.6420.642
961791AG1-021 C
80/20
2.642.64
941801AE2-185 C
80/20
4.7984.798
963041AG1-153 C
80/20
17.24617.246
3151051BRUNSWICKS1
80/20
52.70552.705
944011AF1-069 C
80/20
38.91238.912
316129AC1-054 C
80/20
1.1861.186
3151631KERR 6
80/20
1.8191.819
316131AB2-060 C
80/20
2.3152.315
3138533PONTONDP
80/20
0.9780.978
941431AE2-140 C
80/20
14.14314.143
24684305SMG1
80/20
1.1751.175
3151541CLOVER2
80/20
32.5432.54
940601AE2-047 C
80/20
4.254.25
24684505SMG3
80/20
1.9881.988
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.59 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4175.62
MW Contribution:17.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316359AB2-059 C OP
80/20
1.1351.135
316283AC2-100 C
80/20
2.3262.326
946301AF1-294 C
80/20
5.4265.426
316197AC1-042 C
80/20
0.3460.346
942461AE2-259 C
80/20
14.02314.023
934621AD1-088 C
80/20
24.38424.384
942001AE2-212 C
Adder
-2.1176470588235294-1.8
3152411Z1-086 GT1
80/20
32.08832.088
3152421Z1-086 GT2
80/20
32.07932.079
3151311EDGECMA
80/20
10.35810.358
3152661PLYWOOD A
80/20
2.3542.354
24684405SMG2
80/20
3.2353.235
3151601KERR 3
80/20
1.8191.819
3151581KERR 1
80/20
0.650.65
936161AD2-022 C
80/20
12.80112.801
270197AC1-083 C
80/20
0.9970.997
24684605SMG4
80/20
3.2353.235
935171AD1-152 C
80/20
3.2243.224
3151021BRUNSWICKG1
80/20
25.36825.368
3151041BRUNSWICKG3
80/20
25.36825.368
24728405LEESVG
80/20
0.9740.974
3152441Z1-086 ST
80/20
55.85455.854
3151611KERR 4
80/20
1.8191.819
3151621KERR 5
80/20
1.8191.819
316237AB2-079 C O1
80/20
0.5160.516
316222AC1-221 C
80/20
2.9052.905
316003AC1-222 C
80/20
1.9581.958
957481AF2-042 C
80/20
148.174148.174
316263AC1-034 C
80/20
4.5164.516
3151591KERR 2
80/20
1.8191.819
959311AF2-222 C
80/20
25.13225.132
316205AC1-080 C
80/20
0.5050.505
316123AC1-075 C
80/20
1.5121.512
942751AE2-291 C
80/20
13.51213.512
24684705SMG5
80/20
1.2291.229
3151561HALLBR1
80/20
1.2391.239
937481AD2-202 C
80/20
0.9380.938
3151031BRUNSWICKG2
80/20
25.36825.368
316240AF1-291 C
Adder
-2.031764705882353-1.727
944641AF1-129 C
Adder
-95.19529411764705-80.916
3151641KERR 7
80/20
1.8191.819
313527AB2-043 C
80/20
0.8060.806
933291AC2-141 C
Adder
-33.98823529411765-28.89
316239AB2-077 C O1
80/20
0.5160.516
964791AG1-342 C
80/20
6.5026.502
940081AE1-250 C
80/20
13.65313.653
957601AF2-054 C
Adder
-1.8941176470588237-1.61
934611AD1-087 C
80/20
3.2323.232
3152431Z1-086 GT3
80/20
32.07932.079
940641AE2-051 C
Adder
-22.240000000000002-18.904
316049AB1-081 C OP
80/20
0.9630.963
938531AE1-072 C
Adder
-16.896470588235296-14.362
316238AB2-078 C O1
80/20
0.5160.516
316322AB2-045 C
80/20
0.2670.267
964241AG1-285 C
80/20
19.39519.395
962561AG1-105 C
80/20
15.92115.921
316034AC1-036 C
80/20
0.3540.354
316118AC1-105 C
80/20
1.7691.769
943811AF1-049 C
80/20
9.4269.426
3144293JTRSVLE
80/20
0.6050.605
938741AE1-100 C
80/20
0.7290.729
941671AE2-166 C
80/20
5.7085.708
942671AE2-283 C
80/20
3.7323.732
316217AC1-145 C
80/20
0.4120.412
936171AD2-023 C
80/20
7.4677.467
936261AD2-033 C
80/20
19.83719.837
316248AF1-058 C
80/20
0.6420.642
961791AG1-021 C
80/20
2.642.64
941801AE2-185 C
80/20
4.7984.798
963041AG1-153 C
80/20
17.24617.246
3151051BRUNSWICKS1
80/20
52.70552.705
958211AF2-115 C
80/20
3.33.3
3151531CLOVER1
80/20
32.84832.848
964211AG1-282 C
Adder
-1.7882352941176471-1.52
316129AC1-054 C
80/20
1.1861.186
3151631KERR 6
80/20
1.8191.819
316131AB2-060 C
80/20
2.3152.315
3138533PONTONDP
80/20
0.9780.978
941431AE2-140 C
80/20
14.14314.143
24684305SMG1
80/20
1.1751.175
3151541CLOVER2
80/20
32.5432.54
940601AE2-047 C
80/20
4.254.25
24684505SMG3
80/20
1.9881.988
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.6199.619
CBM South 2LTFEXP_CBM-S2->PJM
CBM
177.277177.277
CPLELTFEXP_CPLE->PJM
CLTF
20.16220.162
TVALTFEXP_TVA->PJM
CLTF
12.22612.226
NYPJM->LTFIMP_NY
CLTF
2.1882.188
LGEELTFEXP_LGEE->PJM
CLTF
2.8852.885
WECLTFEXP_WEC->PJM
CLTF
1.5251.525
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.77474.774
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.81246.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.7578.757
LAGNLTFEXP_LAGN->PJM
CLTF
15.4915.49
SIGELTFEXP_SIGE->PJM
CLTF
0.550.55

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.18 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3902.62
MW Contribution:5.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
29.40470588235294324.994
961671AG1-007 C
Adder
0.80588235294117660.685
946301AF1-294 C
Adder
3.2458823529411762.759
942461AE2-259 C
Adder
8.7329411764705887.423
934621AD1-088 C
80/20
8.9588.958
208901BRIS G2
80/20
-3.11-3.11
316192AB2-158 C
80/20
3.6253.625
942001AE2-212 C
Adder
1.82117647058823541.548
934521AD1-076 C
Adder
10.6788235294117659.077
934511AD1-075 C
Adder
7.3517647058823536.249
316263AC1-034 C
Adder
5.6858823529411774.833
316087AB2-174 C
80/20
1.0461.046
316321Z2-027 C
80/20
0.3170.317
959311AF2-222 C
Adder
14.6623529411764712.463
937481AD2-202 C
80/20
0.3360.336
3151031BRUNSWICKG2
80/20
8.1438.143
316240AF1-291 C
Adder
1.7435294117647061.482
944641AF1-129 C
Adder
81.5517647058823669.319
316036AC1-147 C
80/20
0.320.32
316305AF2-043 C
80/20
0.3030.303
3156056W1-029WIND
80/20
0.6760.676
3152411Z1-086 GT1
80/20
10.43710.437
3152421Z1-086 GT2
80/20
10.43410.434
316233AE1-074 C
80/20
2.4172.417
943461AF1-017 C
80/20
1.1751.175
316311AC2-079 C
80/20
4.9964.996
316274AC1-208 C
Adder
7.857647058823536.679
962571AG1-106 C
Adder
2.40117647058823552.041
3151311EDGECMA
Adder
13.28823529411764811.295
957871AF2-081 C
80/20
8.7288.728
316405AF2-144 C
80/20
0.2940.294
3150651CHESTF6
Adder
14.84823529411764812.621
3150861SPRUNCD
80/20
0.1370.137
3147043LAWRENC
80/20
0.2730.273
940481AE2-033 C
80/20
14.89114.891
940541AE2-040 C
80/20
2.652.65
3152441Z1-086 ST
80/20
18.16818.168
966001AG1-469 C
80/20
1.9591.959
961611AG1-000B C
Adder
12.91058823529411910.974
316375AC2-012 C
80/20
1.1731.173
966621AG1-532 C
80/20
1.2551.255
316320Y1-086 C
80/20
0.1920.192
316388AE2-253 GEN
80/20
1.711.71
935171AD1-152 C
80/20
1.1991.199
3151021BRUNSWICKG1
80/20
8.1438.143
3151041BRUNSWICKG3
80/20
8.1438.143
934861AD1-115 C
Adder
2.8482352941176472.421
3152261N ANNA2
80/20
89.07389.073
942341AE2-247 C
80/20
1.2991.299
316246AF1-032 C
80/20
0.2480.248
316365AB2-100 C1
80/20
0.8620.862
957481AF2-042 C
80/20
51.00351.003
3151801S ANNAS2
80/20
1.3621.362
940431AE2-027 C
Adder
10.4682352941176488.898
316294AC1-161 C
80/20
4.314.31
944581AF1-123 C
80/20
39.90939.909
316185AD1-033 C
80/20
1.071.07
916191Z1-068 C
80/20
0.0380.038
941101AE2-104 C
80/20
2.9282.928
313526AB2-022 C
80/20
0.3280.328
316017AA1-139 ULT1
80/20
0.9420.942
934611AD1-087 C
80/20
1.1591.159
3152431Z1-086 GT3
80/20
10.43410.434
316336AC2-165 C
80/20
9.6099.609
940641AE2-051 C
80/20
17.2917.29
964791AG1-342 C
Adder
3.06352941176470632.604
3151731LOISA B
80/20
2.7082.708
3151751LOISA D
80/20
2.7082.708
316313AB2-026 C
80/20
0.3770.377
316164AC1-076_C
80/20
1.1141.114
939191AE1-149 C
80/20
9.2629.262
3150981CHESPKA
80/20
0.3780.378
961941AG1-037 C
Adder
0.44235294117647060.376
934321AD1-056 C
Adder
5.4329411764705894.618
934331AD1-057 C
Adder
3.0305882352941182.576
958211AF2-115 C
Adder
1.97411764705882351.678
3151531CLOVER1
80/20
11.76811.768
208900BRIS G1
80/20
-2.628-2.628
3151761LOISA E
80/20
5.5225.522
3151771S ANNAG1
80/20
2.6512.651
3151791S ANNAG2
80/20
2.6512.651
3151781S ANNAS1
80/20
1.3621.362
316258AE1-075 C
80/20
0.3460.346
941031AE2-094 C
80/20
39.89839.898
3150831SPRUNCA
Adder
7.6235294117647066.48
3150841SPRUNCB
Adder
7.6235294117647066.48
3151081ELIZAR1
80/20
2.7822.782
316018AA1-139 ULT2
80/20
0.9420.942
3152251N ANNA1
80/20
89.03589.035
3150851SPRUNCC
80/20
0.1370.137
933291AC2-141 C
80/20
26.46526.465
3150921YORKTN3
Adder
90.5694117647058876.984
933981AD1-022 C
Adder
7.6458823529411766.499
938531AE1-072 C
80/20
15.34615.346
3150731STONECA
Adder
5.3258823529411774.527
935161AD1-151 C
Adder
12.7647058823529410.85
316083AB2-161 C
80/20
0.4780.478
958161AF2-110 C
80/20
1.1951.195
927021AC1-189 C
Adder
7.2364705882352946.151
926071AC1-086 C
Adder
18.5623529411764715.778
946281AF1-292 C
80/20
1.3851.385
964241AG1-285 C
Adder
11.0294117647058829.375
962561AG1-105 C
Adder
7.70470588235294156.549
316044AC1-158 C1
80/20
19.41919.419
3151091ELIZAR2
80/20
2.7332.733
316349AD2-085 C
80/20
2.9972.997
960081AF2-299 C
80/20
1.6731.673
936261AD2-033 C
Adder
11.4505882352941189.733
961791AG1-021 C
Adder
1.57882352941176471.342
938771AE1-103 C
80/20
2.5672.567
963041AG1-153 C
80/20
5.5365.536
3151051BRUNSWICKS1
80/20
16.91816.918
316170AC1-121 C
80/20
2.7242.724
944011AF1-069 C
80/20
13.03613.036
316045AC1-158 C2
80/20
19.41919.419
944591AF1-124 C
80/20
40.05140.051
944601AF1-125 C
80/20
39.29539.295
3151101ELIZAR3
80/20
2.8172.817
941591AE2-156 C
80/20
15.615.6
957861AF2-080 C
Adder
6.57294117647058855.587
316023AB2-100 C2
80/20
0.8620.862
316315AB2-025 C
80/20
0.3750.375
3138533PONTONDP
Adder
0.58470588235294120.497
3151541CLOVER2
80/20
11.65811.658
316257AC1-043 C
Adder
5.697647058823534.843
316254AC1-120 C
80/20
7.9327.932
316316AC1-027 C
80/20
0.2750.275
3137643SOCKMAN
Adder
0.6317647058823530.537
3151741LOISA C
80/20
2.7082.708
3151721LOISA A
80/20
2.6942.694
939411AE1-173 C
80/20
87.96287.962
316381AD1-082 C
80/20
1.0891.089
3150991CHESPKB
80/20
0.6270.627
316303AF2-085
80/20
4.1844.184
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.744.74
CBM South 2LTFEXP_CBM-S2->PJM
CBM
83.40383.403
CPLELTFEXP_CPLE->PJM
CLTF
9.9459.945
TVALTFEXP_TVA->PJM
CLTF
5.1955.195
NYPJM->LTFIMP_NY
CLTF
2.5322.532
LGEELTFEXP_LGEE->PJM
CLTF
0.9710.971
WECLTFEXP_WEC->PJM
CLTF
0.4740.474
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.96121.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.49718.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.0623.062
LAGNLTFEXP_LAGN->PJM
CLTF
6.5316.531
SIGELTFEXP_SIGE->PJM
CLTF
0.1910.191

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.07 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3866.79
MW Contribution:5.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
35.6976470588235330.343
961671AG1-007 C
Adder
0.9317647058823530.792
946301AF1-294 C
Adder
3.4941176470588242.97
942461AE2-259 C
Adder
9.347.939
934621AD1-088 C
Adder
9.4482352941176488.031
316192AB2-158 C
80/20
2.1182.118
942001AE2-212 C
80/20
2.3972.397
962861AG1-135 C
Adder
6.222352941176475.289
943741AF1-042 C
Adder
2.9964705882352942.547
934521AD1-076 C
Adder
12.96470588235294111.02
934511AD1-075 C
Adder
8.9247058823529427.586
316263AC1-034 C
Adder
6.5105882352941185.534
959311AF2-222 C
Adder
15.85294117647058913.475
316240AF1-291 C
80/20
2.3942.394
944641AF1-129 C
80/20
113.49113.49
3150781HOPHCF2
80/20
2.6772.677
3150761HOPPOLC
80/20
1.6841.684
316233AE1-074 C
80/20
2.8192.819
940551AE2-041 C
Adder
7.4541176470588246.336
943461AF1-017 C
Adder
1.48588235294117641.263
316311AC2-079 C
Adder
6.3129411764705885.366
316274AC1-208 C
Adder
9.0917647058823537.728
962571AG1-106 C
Adder
2.7823529411764712.365
3151311EDGECMA
Adder
15.22352941176470512.94
957871AF2-081 C
Adder
10.989.333
3150651CHESTF6
80/20
20.66420.664
3150861SPRUNCD
80/20
0.1830.183
936591AD2-074 C
Adder
5.7258823529411764.867
940481AE2-033 C
Adder
17.08117647058823614.519
940541AE2-040 C
Adder
3.03764705882352942.582
927041AC1-191 C
Adder
10.0729411764705888.562
963611AG1-210 C
Adder
0.66705882352941170.567
961611AG1-000B C
Adder
17.55647058823529614.923
316375AC2-012 C
80/20
1.4881.488
966621AG1-532 C
Adder
1.43529411764705881.22
3152261N ANNA2
80/20
55.34655.346
3150771HOPHCF1
80/20
2.6772.677
942341AE2-247 C
Adder
1.64235294117647061.396
957481AF2-042 C
Adder
53.64117647058823545.595
940431AE2-027 C
80/20
14.31814.318
316294AC1-161 C
80/20
5.4825.482
944581AF1-123 C
80/20
50.22150.221
941101AE2-104 C
Adder
3.683.128
316336AC2-165 C
Adder
10.1094117647058828.593
940641AE2-051 C
80/20
18.48818.488
943471AF1-018 C
Adder
7.4541176470588246.336
3152331SURRY 2
80/20
27.29427.294
964791AG1-342 C
Adder
3.32117647058823542.823
316164AC1-076_C
80/20
0.9930.993
3143096IRON208
80/20
0.4840.484
958261AF2-120 C
Adder
6.4035294117647065.443
939191AE1-149 C
80/20
11.90511.905
957601AF2-054 C
Adder
2.2117647058823531.88
961941AG1-037 C
Adder
0.52705882352941180.448
934321AD1-056 C
Adder
6.2529411764705895.315
934331AD1-057 C
Adder
3.4882352941176472.965
958211AF2-115 C
Adder
2.12470588235294141.806
941031AE2-094 C
80/20
41.37341.373
3150831SPRUNCA
80/20
10.21910.219
3150841SPRUNCB
80/20
10.21910.219
966871AG1-558 C
Adder
2.50941176470588222.133
964211AG1-282 C
Adder
2.0317647058823531.727
3150801HOPHCF4
80/20
4.0644.064
3151081ELIZAR1
80/20
3.5273.527
3152251N ANNA1
80/20
55.32355.323
3150851SPRUNCC
80/20
0.1830.183
944631AF1-128 C
Adder
43.1623529411764736.688
933291AC2-141 C
80/20
33.66433.664
3150921YORKTN3
Adder
130.26705882352942110.727
933981AD1-022 C
Adder
9.2505882352941197.863
938531AE1-072 C
Adder
19.2929411764705916.399
3142366NRTHEST
80/20
0.20.2
3150731STONECA
80/20
7.6067.606
935161AD1-151 C
Adder
17.79176470588235415.123
958161AF2-110 C
Adder
1.50117647058823531.276
927021AC1-189 C
Adder
8.4188235294117647.156
926071AC1-086 C
Adder
21.50823529411764718.282
946281AF1-292 C
Adder
1.58470588235294121.347
964241AG1-285 C
Adder
11.97764705882352810.181
962561AG1-105 C
Adder
8.3588235294117657.105
316044AC1-158 C1
80/20
14.96214.962
939261AE1-157 C
Adder
13.77647058823529511.71
316169AC1-164 GEN
Adder
42.77176470588235436.356
3151091ELIZAR2
80/20
3.4653.465
316349AD2-085 C
Adder
3.79058823529411763.222
960081AF2-299 C
Adder
1.91411764705882351.627
936261AD2-033 C
Adder
12.4023529411764710.542
961791AG1-021 C
Adder
1.70000000000000021.445
938771AE1-103 C
Adder
3.162.686
963041AG1-153 C
Adder
5.7647058823529424.9
944011AF1-069 C
80/20
13.51813.518
316045AC1-158 C2
80/20
14.96214.962
966881AG1-559 C
Adder
2.3964705882352942.037
3150601CHESTF5
Adder
68.9811764705882458.634
944591AF1-124 C
80/20
50.39950.399
944601AF1-125 C
80/20
49.44749.447
3151101ELIZAR3
80/20
3.5723.572
941591AE2-156 C
80/20
19.79319.793
957861AF2-080 C
Adder
7.6458823529411766.499
3138533PONTONDP
Adder
0.62941176470588240.535
3150791HOPHCF3
80/20
2.6772.677
961951AG1-038 C
Adder
3.3117647058823532.815
3137643SOCKMAN
Adder
0.72705882352941180.618
966661AG1-536 C
Adder
5.5082352941176484.682
939411AE1-173 C
80/20
97.64897.648
3150991CHESPKB
80/20
0.7960.796
316303AF2-085
80/20
4.3634.363
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.2865.286
CBM South 2LTFEXP_CBM-S2->PJM
CBM
94.17394.173
CPLELTFEXP_CPLE->PJM
CLTF
11.08811.088
TVALTFEXP_TVA->PJM
CLTF
6.1396.139
NYPJM->LTFIMP_NY
CLTF
2.8062.806
LGEELTFEXP_LGEE->PJM
CLTF
1.2221.222
WECLTFEXP_WEC->PJM
CLTF
0.5950.595
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.65727.657
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.08222.082
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.7473.747
LAGNLTFEXP_LAGN->PJM
CLTF
7.6777.677
SIGELTFEXP_SIGE->PJM
CLTF
0.2370.237

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T575_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.55 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4631.32
MW Contribution:14.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
934501AD1-074 C
Adder
31.13882352941176626.468
924517AB2-100 E2
Adder
2.74588235294117672.334
937226AE2-253 E
Adder
5.4188235294117654.606
946301AF1-294 C
Adder
3.4070588235294122.896
935172AD1-152 E
Adder
5.1847058823529414.407
942461AE2-259 C
Adder
9.1658823529411777.791
934621AD1-088 C
Adder
9.3717647058823547.966
957482AF2-042 E
Adder
35.55176470588235630.219
208901BRIS G2
50/50
-3.356-3.356
958502AF2-144 E
Adder
1.2588235294117651.07
316192AB2-158 C
50/50
3.6573.657
942001AE2-212 C
Adder
1.94235294117647061.651
939192AE1-149 E
Adder
6.5694117647058825.584
939312AE1-162 E
Adder
1.27764705882352961.086
934065AD1-033 E
Adder
4.6541176470588243.956
920692AA2-178 E
Adder
3.8023529411764713.232
966622AG1-532 E
Adder
0.88117647058823530.749
917122Z2-027 E
Adder
1.24470588235294131.058
3146326AYDLETT TAP
Adder
1.25764705882352931.069
938532AE1-072 E
Adder
8.4941176470588247.22
3147133PAMPLIN
Adder
0.91529411764705890.778
966002AG1-469 E
50/50
0.9930.993
926739AC1-158 E1
50/50
50.96750.967
316233AE1-074 C
Adder
2.5458823529411772.164
935162AD1-151 E
Adder
9.1294117647058827.76
943461AF1-017 C
Adder
1.2482352941176471.061
316311AC2-079 C
Adder
5.3070588235294124.511
932596AC2-079 E
Adder
8.6588235294117667.36
923263AB1-132 E OP
Adder
5.697647058823534.843
940481AE2-033 C
Adder
15.6752941176470613.324
940482AE2-033 E
Adder
10.5670588235294118.982
940541AE2-040 C
Adder
2.78823529411764742.37
924312AB2-078 E O1
Adder
1.23529411764705891.05
925612AC1-036 E
Adder
0.79294117647058830.674
966001AG1-469 C
50/50
1.9871.987
925672AC1-043 E
Adder
9.4635294117647078.044
926740AC1-158 E2
50/50
50.96750.967
961611AG1-000B C
Adder
13.8152941176470611.743
943172AE2-346 E
Adder
0.56117647058823530.477
917332KELFORD E
Adder
1.51764705882352961.29
925122AB2-169 E
Adder
5.2764705882352954.485
934522AD1-076 E
Adder
5.7635294117647064.899
940492AE2-034 E
Adder
2.85176470588235282.424
316274AC1-208 C
Adder
8.2905882352941187.047
962571AG1-106 C
Adder
2.53176470588235342.152
918492AA1-063AE OP
Adder
3.80117647058823543.231
957871AF2-081 C
Adder
9.2670588235294127.877
961792AG1-021 E
Adder
1.4117647058823531.2
937482AD2-202 E
Adder
1.02705882352941180.873
3145506HICKORY
Adder
2.02235294117647071.719
946262AF1-291 E
Adder
1.24470588235294131.058
3150651CHESTF6
Adder
15.92588235294117813.537
933292AC2-141 E
Adder
12.0070588235294110.206
934576AD1-082 E
Adder
4.0564705882352943.448
944602AF1-125 E
Adder
95.5082352941176581.182
943612AF1-032 E
Adder
0.85764705882352940.729
918512AA1-065 E OP
Adder
5.1070588235294124.341
934502AD1-074 E
Adder
15.85176470588235313.474
934512AD1-075 E
Adder
3.96235294117647063.368
924516AB2-100 E1
Adder
2.74588235294117672.334
966621AG1-532 C
Adder
1.32117647058823541.123
919153AA1-139 E2
Adder
3.78941176470588253.221
924022AB2-043 E O1
Adder
4.7941176470588244.075
3147223TWITTYS
Adder
0.87882352941176480.747
959312AF2-222 E
Adder
10.3129411764705888.766
934861AD1-115 C
Adder
2.92.465
3152261N ANNA2
50/50
89.60989.609
316141AB2-099 E
Adder
0.234117647058823540.199
923994AB2-040_E
Adder
5.76941176470588254.904
316088AB2-174 E
Adder
6.1235294117647065.205
924322AB2-079 E O1
Adder
1.23529411764705891.05
946302AF1-294 E
Adder
2.88470588235294122.452
957481AF2-042 C
Adder
53.3270588235294245.328
3151801S ANNAS2
50/50
1.381.38
942002AE2-212 E
Adder
1.2952941176470591.101
940431AE2-027 C
Adder
11.2058823529411789.525
944581AF1-123 C
Adder
42.37411764705882436.018
941101AE2-104 C
Adder
3.10941176470588232.643
961942AG1-037 E
Adder
0.311764705882352940.265
961941AG1-037 C
Adder
0.46705882352941180.397
923852AB2-025 E
Adder
1.1282352941176470.959
936262AD2-033 E
Adder
8.0141176470588256.812
926206AC1-098 E
Adder
3.35647058823529452.853
901082W1-029 E
Adder
29.54000000000000325.109
942462AE2-259 E
Adder
6.1105882352941175.194
3151731LOISA B
50/50
2.7452.745
3151751LOISA D
50/50
2.7452.745
3143316POE
Adder
1.28823529411764711.095
316164AC1-076_C
50/50
1.1311.131
939191AE1-149 C
Adder
9.8529411764705898.375
933982AD1-022 E
Adder
4.4070588235294123.746
3145946PLYMOUTH TP
Adder
0.29882352941176470.254
927146AC1-208 E
Adder
1.16941176470588240.994
934612AD1-087 E
Adder
3.50941176470588272.983
934622AD1-088 E
Adder
4.5117647058823533.835
316336AC2-165 C
Adder
10.0588235294117668.55
926004AC1-076_E
50/50
6.486.48
940641AE2-051 C
50/50
18.07818.078
316084AB2-161 E
Adder
5.0917647058823544.328
933981AD1-022 C
Adder
8.0941176470588236.88
900672V4-068 E
Adder
0.33058823529411770.281
938531AE1-072 C
Adder
16.29411764705882213.85
924302AB2-077 E O1
Adder
1.23529411764705891.05
3145393UNCAMP
Adder
5.65176470588235354.804
926486AC1-120 E
50/50
4.1534.153
935161AD1-151 C
Adder
13.69411764705882511.64
932046AC2-012 E
Adder
12.12705882352941210.308
958161AF2-110 C
Adder
1.26823529411764711.078
926214AC1-099 E
Adder
1.1082352941176470.942
932632AC2-084 E
Adder
2.96705882352941152.522
962572AG1-106 E
Adder
1.1082352941176470.942
957872AF2-081 E
Adder
3.9717647058823533.376
924162AB2-060 E OP
Adder
3.95764705882352933.364
964242AG1-285 E
Adder
7.7211764705882356.563
934862AD1-115 E
Adder
4.73176470588235354.022
938562AE1-075 E
Adder
1.0917647058823530.928
3152251N ANNA1
50/50
89.57189.571
938552AE1-074 E
Adder
1.28235294117647071.09
926755AC1-161 E
Adder
12.0070588235294110.206
933291AC2-141 C
Adder
28.12941176470588223.91
925522AC1-027 E
Adder
1.1282352941176470.959
941102AE2-104 E
Adder
4.9423529411764714.201
3145256KINGFORK
Adder
0.92470588235294130.786
934521AD1-076 C
Adder
11.3094117647058829.613
934511AD1-075 C
Adder
7.7847058823529426.617
919692AA2-053 E OP
Adder
3.93176470588235333.342
923573AB1-173 E OP
Adder
3.07647058823529432.615
3145723EMPORIA
Adder
0.405882352941176470.345
920042AA2-088 E OP
Adder
9.8670588235294128.387
925785AC1-054 E
Adder
3.18705882352941172.709
919152AA1-139 E1
Adder
3.78941176470588253.221
959311AF2-222 C
Adder
15.39294117647058813.084
926502AC1-121 E
50/50
1.3031.303
316240AF1-291 C
Adder
1.86705882352941191.587
944641AF1-129 C
Adder
87.4717647058823574.351
924814AB2-134 E
Adder
10.7988235294117659.179
942342AE2-247 E
Adder
1.90588235294117661.62
958211AF2-115 C
Adder
2.0717647058823531.761
208900BRIS G1
50/50
-2.836-2.836
3151761LOISA E
50/50
5.5965.596
3151771S ANNAG1
50/50
2.6852.685
3151791S ANNAG2
50/50
2.6852.685
3151781S ANNAS1
50/50
1.381.38
923862AB2-026 E
Adder
1.28117647058823541.089
941031AE2-094 C
50/50
41.61841.618
941032AE2-094 E
50/50
18.6418.64
3150831SPRUNCA
Adder
8.1435294117647056.922
3150841SPRUNCB
Adder
8.1435294117647056.922
939412AE1-173 E
Adder
61.5211764705882452.293
926662AC1-147 E
Adder
1.22588235294117661.042
916192Z1-068 E
Adder
1.74235294117647071.481
957492AF2-043 E
Adder
1.31882352941176471.121
926072AC1-086 E
Adder
8.9094117647058837.573
960081AF2-299 C
Adder
1.76235294117647071.498
3145413WATKINS
Adder
0.64235294117647070.546
936261AD2-033 C
Adder
12.02117647058823610.218
962562AG1-105 E
Adder
5.3929411764705884.584
961791AG1-021 C
Adder
1.65764705882352951.409
938771AE1-103 C
Adder
2.72117647058823582.313
963041AG1-153 C
Adder
5.7788235294117654.912
316170AC1-121 C
50/50
2.7692.769
944011AF1-069 C
50/50
13.59813.598
316045AC1-158 C2
50/50
19.48619.486
925332AB2-190 E
Adder
6.8164705882352945.794
927226AC1-216 E
Adder
6.5917647058823535.603
944591AF1-124 C
Adder
42.5247058823529436.146
944601AF1-125 C
Adder
41.7211764705882435.463
941591AE2-156 C
Adder
16.57647058823529614.09
936666AD2-085 E
Adder
5.195294117647064.416
940642AE2-051 E
50/50
12.05212.052
942341AE2-247 C
Adder
1.38000000000000011.173
943462AF1-017 E
Adder
2.03764705882352941.732
958162AF2-110 E
Adder
2.01764705882352931.715
3137643SOCKMAN
Adder
0.66588235294117650.566
913392Y1-086 E
Adder
2.03647058823529431.731
933502AC2-165 E
Adder
7.5705882352941176.435
3151741LOISA C
50/50
2.7452.745
3151721LOISA A
50/50
2.7312.731
940432AE2-027 E
Adder
7.4705882352941186.35
939411AE1-173 C
Adder
92.2811764705882478.439
934012AD1-025 E
Adder
8.5352941176470597.255
946282AF1-292 E
Adder
0.97294117647058820.827
3138533PONTONDP
Adder
0.61411764705882350.522
316257AC1-043 C
Adder
5.84.93
316254AC1-120 C
50/50
8.0618.061
944012AF1-069 E
50/50
5.2835.283
926071AC1-086 C
Adder
19.57647058823529616.64
946281AF1-292 C
Adder
1.45882352941176461.24
960082AF2-299 E
Adder
1.17529411764705880.999
916042Z1-036 E
Adder
26.4694117647058822.499
923832AB2-022 E
Adder
1.14941176470588240.977
964241AG1-285 C
Adder
11.5811764705882349.844
962561AG1-105 C
Adder
8.0894117647058836.876
958212AF2-115 E
Adder
1.76470588235294111.5
938772AE1-103 E
Adder
3.75764705882352963.194
963042AG1-153 E
Adder
8.6682352941176477.368
925022AB2-158 E
50/50
9.7219.721
316044AC1-158 C1
50/50
19.48619.486
944592AF1-124 E
Adder
97.3823529411764882.775
944582AF1-123 E
Adder
97.0317647058823782.477
316349AD2-085 C
Adder
3.1835294117647062.706
935112AD1-144 E
Adder
0.85764705882352940.729
316303AF2-085
50/50
4.3644.364
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0035.003
CBM South 2LTFEXP_CBM-S2->PJM
CBM
88.42988.429
CPLELTFEXP_CPLE->PJM
CLTF
10.49610.496
TVALTFEXP_TVA->PJM
CLTF
5.6275.627
O66PJM->LTFIMP_O-066
CMTX_NF
36.7236.72
NYPJM->LTFIMP_NY
CLTF
2.7142.714
LGEELTFEXP_LGEE->PJM
CLTF
1.0981.098
WECLTFEXP_WEC->PJM
CLTF
0.5410.541
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.22125.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.23820.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
3.4183.418
LAGNLTFEXP_LAGN->PJM
CLTF
7.0687.068
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7645.764
SIGELTFEXP_SIGE->PJM
CLTF
0.2140.214

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4234.7
MW Contribution:17.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
316359AB2-059 C OP
80/20
1.0881.088
316283AC2-100 C
80/20
2.1162.116
946301AF1-294 C
80/20
4.7464.746
316197AC1-042 C
80/20
0.3150.315
942461AE2-259 C
80/20
12.19912.199
934621AD1-088 C
80/20
21.36821.368
942001AE2-212 C
Adder
-2.010588235294118-1.709
3152411Z1-086 GT1
80/20
33.47333.473
3152421Z1-086 GT2
80/20
33.46433.464
3152661PLYWOOD A
80/20
2.0932.093
24684405SMG2
80/20
3.0033.003
3151601KERR 3
80/20
1.6151.615
3151581KERR 1
80/20
0.5770.577
936161AD2-022 C
80/20
12.15912.159
270197AC1-083 C
80/20
0.9340.934
24684605SMG4
80/20
3.0033.003
935171AD1-152 C
80/20
2.8492.849
3151021BRUNSWICKG1
80/20
25.15625.156
3151041BRUNSWICKG3
80/20
25.15625.156
24728405LEESVG
80/20
0.8940.894
3152441Z1-086 ST
80/20
58.26658.266
3151611KERR 4
80/20
1.6151.615
3151621KERR 5
80/20
1.6151.615
316237AB2-079 C O1
80/20
0.4550.455
316222AC1-221 C
80/20
2.6372.637
934611AD1-087 C
80/20
2.842.84
3152431Z1-086 GT3
80/20
33.46433.464
940641AE2-051 C
Adder
-21.040000000000003-17.884
316003AC1-222 C
80/20
1.7441.744
957481AF2-042 C
80/20
129.887129.887
316263AC1-034 C
80/20
4.3284.328
3151591KERR 2
80/20
1.6151.615
959311AF2-222 C
80/20
22.05622.056
316205AC1-080 C
80/20
0.4520.452
316123AC1-075 C
80/20
1.3531.353
942751AE2-291 C
80/20
12.11212.112
24684705SMG5
80/20
1.1411.141
3151561HALLBR1
80/20
1.1241.124
937481AD2-202 C
80/20
0.8240.824
3151031BRUNSWICKG2
80/20
25.15625.156
316240AF1-291 C
Adder
-1.9317647058823528-1.642
944641AF1-129 C
Adder
-90.49176470588236-76.918
3151641KERR 7
80/20
1.6151.615
313527AB2-043 C
80/20
0.7110.711
933291AC2-141 C
Adder
-32.203529411764706-27.373
316239AB2-077 C O1
80/20
0.4550.455
964791AG1-342 C
80/20
5.7665.766
940081AE1-250 C
80/20
12.86112.861
957601AF2-054 C
Adder
-1.8-1.53
316049AB1-081 C OP
80/20
0.9230.923
938531AE1-072 C
Adder
-16.01294117647059-13.611
316238AB2-078 C O1
80/20
0.4550.455
316322AB2-045 C
80/20
0.2270.227
964241AG1-285 C
80/20
17.07617.076
962561AG1-105 C
80/20
14.10814.108
316034AC1-036 C
80/20
0.3110.311
316118AC1-105 C
80/20
1.5721.572
943811AF1-049 C
80/20
8.9298.929
3144293JTRSVLE
80/20
0.5290.529
938741AE1-100 C
80/20
0.690.69
941671AE2-166 C
80/20
5.45.4
942671AE2-283 C
80/20
3.3963.396
316217AC1-145 C
80/20
0.3750.375
936171AD2-023 C
80/20
7.0937.093
936261AD2-033 C
80/20
17.43217.432
316248AF1-058 C
80/20
0.5710.571
961791AG1-021 C
80/20
2.3092.309
941801AE2-185 C
80/20
4.3664.366
963041AG1-153 C
80/20
17.10317.103
3151051BRUNSWICKS1
80/20
52.26552.265
944011AF1-069 C
80/20
45.1645.16
958211AF2-115 C
80/20
2.8862.886
3151531CLOVER1
80/20
28.86928.869
941031AE2-094 C
80/20
138.215138.215
964211AG1-282 C
Adder
-1.7011764705882353-1.446
316129AC1-054 C
80/20
1.0481.048
3151631KERR 6
80/20
1.6151.615
316131AB2-060 C
80/20
2.042.04
3138533PONTONDP
80/20
0.8550.855
941431AE2-140 C
80/20
13.39313.393
24684305SMG1
80/20
1.0911.091
3151541CLOVER2
80/20
28.59828.598
940601AE2-047 C
80/20
4.0274.027
24684505SMG3
80/20
1.8451.845
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
NYPJM->LTFIMP_NY
CLTF
2.1082.108
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
WECLTFEXP_WEC->PJM
CLTF
1.451.45
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: 545T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1                /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314063 TO BUS 314916 CKT 1                /*6MORRSVL     230.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 568T575_SRT-A'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1   /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1   /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 314940 TO BUS 941030 CKT 1   /*8ROGERS RD   500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314282 to 314285 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 314922 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314936 to 314902 ckt 1
314934 to 314916 ckt 1
941030 to 314902 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC101.12 %678.68B686.285.61
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC100.08 %678.68B679.215.61
GD1DVP
6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC100.11 %984.18B985.294.87
GD1DVP
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.74 %984.18B1020.964.87
GD1DVP
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC103.68 %984.18B1020.424.87
GD1DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
OPAC104.12 %3220.44A3352.9920.8
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC136.21 %2442.12B3326.417.93
GD1DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC115.81 %4070.2B4713.5919.2
GD1DVP
8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
DVP_P1-2: LN N ANNA-KRAKEN_SRT-A
OPAC107.4 %3220.44B3458.6510.85
GD1DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-A
OPAC126.88 %1058.16B1342.559.18
GD1DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
OPAC108.69 %4070.2B4423.7243.41
GD1DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S-1
OPAC106.42 %2442.12B2598.9316.38
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
OPAC105.3 %3220.44B3390.9712.01
GD1DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.93 %4070.2B4311.7143.01

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:101.12 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:686.28
MW Contribution:5.61
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.88 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:732.13
MW Contribution:5.83
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.1112.111
961792AG1-021 E
50/50
1.7981.798
963041AG1-153 C
Adder
2.2447058823529411.908
963042AG1-153 E
Adder
3.3670588235294122.862
964791AG1-342 C
Adder
2.18117647058823531.854
964792AG1-342 E
Adder
1.45411764705882351.236
966621AG1-532 C
Adder
0.61058823529411770.519
966622AG1-532 E
Adder
0.407058823529411750.346
3138533PONTONDP
50/50
0.7820.782
3144293JTRSVLE
50/50
0.4860.486
3145723EMPORIA
Adder
0.187058823529411780.159
3147133PAMPLIN
50/50
1.231.23
918492AA1-063AE OP
Adder
1.64941176470588241.402
919692AA2-053 E OP
Adder
1.73294117647058841.473
925785AC1-054 E
Adder
1.7588235294117651.495
926274AC1-105 E
Adder
1.55058823529411781.318
943902AF1-058 E
Adder
0.69647058823529410.592
944011AF1-069 C
Adder
4.9870588235294124.239
944012AF1-069 E
Adder
1.93764705882352951.647
959311AF2-222 C
50/50
16.21416.214
959312AF2-222 E
50/50
10.86410.864
960081AF2-299 C
Adder
0.81294117647058820.691
960082AF2-299 E
Adder
0.54235294117647060.461
316131AB2-060 C
50/50
1.0971.097
923573AB1-173 E OP
Adder
1.4035294117647061.193
924162AB2-060 E OP
50/50
3.163.16
924302AB2-077 E O1
50/50
0.9490.949
924312AB2-078 E O1
50/50
0.9490.949
924322AB2-079 E O1
50/50
0.9490.949
925612AC1-036 E
50/50
0.8090.809
941031AE2-094 C
Adder
15.26470588235294212.975
941032AE2-094 E
Adder
6.83647058823529455.811
946281AF1-292 C
Adder
0.67294117647058820.572
946282AF1-292 E
Adder
0.44941176470588240.382
946301AF1-294 C
50/50
4.3394.339
946302AF1-294 E
50/50
3.6743.674
957481AF2-042 C
Adder
31.1270588235294126.458
957482AF2-042 E
Adder
20.7517647058823517.639
958211AF2-115 C
50/50
2.6382.638
958212AF2-115 E
50/50
2.2482.248
940451AE2-029 C
Adder
-2.1529411764705886-1.83
924032AB2-045 E
50/50
2.9052.905
933502AC2-165 E
50/50
11.611.6
3150831SPRUNCA
Adder
3.52.975
3150841SPRUNCB
Adder
3.52.975
958502AF2-144 E
50/50
1.611.61
3151911BEARGRDN G1
50/50
13.38913.389
3151921BEARGRDN G2
50/50
13.38913.389
923852AB2-025 E
Adder
0.428235294117647050.364
923862AB2-026 E
50/50
1.6391.639
938552AE1-074 E
Adder
0.60823529411764710.517
938562AE1-075 E
50/50
1.3971.397
3147223TWITTYS
50/50
0.8960.896
936261AD2-033 C
50/50
11.9511.95
936262AD2-033 E
50/50
7.9677.967
934621AD1-088 C
50/50
6.7356.735
934622AD1-088 E
50/50
3.2433.243
939411AE1-173 C
Adder
32.29058823529411627.447
939412AE1-173 E
Adder
21.52705882352941218.298
3151931BEARGRDN S1
50/50
17.32117.321
316034AC1-036 C
50/50
0.2210.221
316233AE1-074 C
Adder
1.20705882352941171.026
316237AB2-079 C O1
50/50
0.2330.233
316238AB2-078 C O1
50/50
0.2330.233
316239AB2-077 C O1
50/50
0.2330.233
316258AE1-075 C
50/50
0.4640.464
316313AB2-026 C
50/50
0.5060.506
316322AB2-045 C
50/50
0.6480.648
316336AC2-165 C
50/50
15.41215.412
316405AF2-144 C
50/50
0.3950.395
924516AB2-100 E1
Adder
1.11058823529411770.944
924517AB2-100 E2
Adder
1.11058823529411770.944
927255AC1-221 E
Adder
1.72235294117647061.464
927264AC1-222 E
Adder
2.09764705882352941.783
932763AC2-100 E
Adder
1.15411764705882350.981
923994AB2-040_E
Adder
2.6317647058823532.237
313527AB2-043 C
50/50
0.3720.372
924022AB2-043 E O1
50/50
3.7383.738
316088AB2-174 E
Adder
2.8035294117647062.383
962561AG1-105 C
Adder
5.6211764705882354.778
962562AG1-105 E
Adder
3.74705882352941183.185
964241AG1-285 C
50/50
9.7319.731
964242AG1-285 E
50/50
6.4876.487
3137643SOCKMAN
Adder
0.30117647058823530.256
934612AD1-087 E
Adder
2.13647058823529431.816
935172AD1-152 E
Adder
3.09058823529411742.627
937482AD2-202 E
Adder
0.62470588235294120.531
938821AE1-108 C
Adder
7.7941176470588236.625
938822AE1-108 E
Adder
3.71882352941176463.161
940481AE2-033 C
Adder
6.05.1
940482AE2-033 E
Adder
4.0447058823529413.438
940541AE2-040 C
Adder
1.05764705882352940.899
940641AE2-051 C
Adder
6.297647058823535.353
940642AE2-051 E
Adder
4.1988235294117653.569
942461AE2-259 C
50/50
14.43514.435
942462AE2-259 E
50/50
9.6239.623
316303AF2-085
50/50
2.1712.171
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9041.904
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.3713.371
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.16230.162
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8220.822
NYPJM->LTFIMP_NY
CLTF
0.4340.434
CPLELTFEXP_CPLE->PJM
CLTF
4.0014.001
TVALTFEXP_TVA->PJM
CLTF
1.171.17
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0190.019
MECLTFEXP_MEC->PJM
CLTF
0.2690.269
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0350.035
LAGNLTFEXP_LAGN->PJM
CLTF
1.5461.546
SIGELTFEXP_SIGE->PJM
CLTF
0.010.01
O66PJM->LTFIMP_O-066
CMTX_NF
5.2725.272

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.08 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:679.21
MW Contribution:5.61
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.82 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:724.99
MW Contribution:5.83
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.1112.111
961792AG1-021 E
50/50
1.7981.798
963041AG1-153 C
Adder
2.2447058823529411.908
963042AG1-153 E
Adder
3.3670588235294122.862
964791AG1-342 C
Adder
2.18117647058823531.854
964792AG1-342 E
Adder
1.45411764705882351.236
966621AG1-532 C
Adder
0.61058823529411770.519
966622AG1-532 E
Adder
0.407058823529411750.346
3138533PONTONDP
50/50
0.7820.782
3144293JTRSVLE
50/50
0.4860.486
3145723EMPORIA
Adder
0.187058823529411780.159
3147133PAMPLIN
50/50
1.231.23
918492AA1-063AE OP
Adder
1.64941176470588241.402
919692AA2-053 E OP
Adder
1.73294117647058841.473
925785AC1-054 E
Adder
1.7588235294117651.495
926274AC1-105 E
Adder
1.55058823529411781.318
943902AF1-058 E
Adder
0.69647058823529410.592
944011AF1-069 C
Adder
4.9870588235294124.239
944012AF1-069 E
Adder
1.93764705882352951.647
959311AF2-222 C
50/50
16.21416.214
959312AF2-222 E
50/50
10.86410.864
960081AF2-299 C
Adder
0.81294117647058820.691
960082AF2-299 E
Adder
0.54235294117647060.461
316131AB2-060 C
50/50
1.0971.097
923573AB1-173 E OP
Adder
1.4035294117647061.193
924162AB2-060 E OP
50/50
3.163.16
924302AB2-077 E O1
50/50
0.9490.949
924312AB2-078 E O1
50/50
0.9490.949
924322AB2-079 E O1
50/50
0.9490.949
925612AC1-036 E
50/50
0.8090.809
941031AE2-094 C
Adder
15.26470588235294212.975
941032AE2-094 E
Adder
6.83647058823529455.811
946281AF1-292 C
Adder
0.67294117647058820.572
946282AF1-292 E
Adder
0.44941176470588240.382
946301AF1-294 C
50/50
4.3394.339
946302AF1-294 E
50/50
3.6743.674
957481AF2-042 C
Adder
31.1270588235294126.458
957482AF2-042 E
Adder
20.7517647058823517.639
958211AF2-115 C
50/50
2.6382.638
958212AF2-115 E
50/50
2.2482.248
940451AE2-029 C
Adder
-2.1529411764705886-1.83
924032AB2-045 E
50/50
2.9052.905
933502AC2-165 E
50/50
11.611.6
3150831SPRUNCA
Adder
3.52.975
3150841SPRUNCB
Adder
3.52.975
958502AF2-144 E
50/50
1.611.61
3151911BEARGRDN G1
50/50
13.38913.389
3151921BEARGRDN G2
50/50
13.38913.389
923852AB2-025 E
Adder
0.428235294117647050.364
923862AB2-026 E
50/50
1.6391.639
938552AE1-074 E
Adder
0.60823529411764710.517
938562AE1-075 E
50/50
1.3971.397
3147223TWITTYS
50/50
0.8960.896
936261AD2-033 C
50/50
11.9511.95
936262AD2-033 E
50/50
7.9677.967
934621AD1-088 C
50/50
6.7356.735
934622AD1-088 E
50/50
3.2433.243
939411AE1-173 C
Adder
32.29058823529411627.447
939412AE1-173 E
Adder
21.52705882352941218.298
3151931BEARGRDN S1
50/50
17.32117.321
316034AC1-036 C
50/50
0.2210.221
316233AE1-074 C
Adder
1.20705882352941171.026
316237AB2-079 C O1
50/50
0.2330.233
316238AB2-078 C O1
50/50
0.2330.233
316239AB2-077 C O1
50/50
0.2330.233
316258AE1-075 C
50/50
0.4640.464
316313AB2-026 C
50/50
0.5060.506
316322AB2-045 C
50/50
0.6480.648
316336AC2-165 C
50/50
15.41215.412
316405AF2-144 C
50/50
0.3950.395
924516AB2-100 E1
Adder
1.11058823529411770.944
924517AB2-100 E2
Adder
1.11058823529411770.944
927255AC1-221 E
Adder
1.72235294117647061.464
927264AC1-222 E
Adder
2.09764705882352941.783
932763AC2-100 E
Adder
1.15411764705882350.981
923994AB2-040_E
Adder
2.6317647058823532.237
313527AB2-043 C
50/50
0.3720.372
924022AB2-043 E O1
50/50
3.7383.738
316088AB2-174 E
Adder
2.8035294117647062.383
962561AG1-105 C
Adder
5.6211764705882354.778
962562AG1-105 E
Adder
3.74705882352941183.185
964241AG1-285 C
50/50
9.7319.731
964242AG1-285 E
50/50
6.4876.487
3137643SOCKMAN
Adder
0.30117647058823530.256
934612AD1-087 E
Adder
2.13647058823529431.816
935172AD1-152 E
Adder
3.09058823529411742.627
937482AD2-202 E
Adder
0.62470588235294120.531
938821AE1-108 C
Adder
7.7941176470588236.625
938822AE1-108 E
Adder
3.71882352941176463.161
940481AE2-033 C
Adder
6.05.1
940482AE2-033 E
Adder
4.0447058823529413.438
940541AE2-040 C
Adder
1.05764705882352940.899
940641AE2-051 C
Adder
6.297647058823535.353
940642AE2-051 E
Adder
4.1988235294117653.569
942461AE2-259 C
50/50
14.43514.435
942462AE2-259 E
50/50
9.6239.623
316303AF2-085
50/50
2.1712.171
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9041.904
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.3713.371
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.16230.162
G-007PJM->LTFIMP_G-007
CMTX_NF
0.8220.822
NYPJM->LTFIMP_NY
CLTF
0.4340.434
CPLELTFEXP_CPLE->PJM
CLTF
4.0014.001
TVALTFEXP_TVA->PJM
CLTF
1.171.17
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.0190.019
MECLTFEXP_MEC->PJM
CLTF
0.2690.269
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.0350.035
LAGNLTFEXP_LAGN->PJM
CLTF
1.5461.546
SIGELTFEXP_SIGE->PJM
CLTF
0.010.01
O66PJM->LTFIMP_O-066
CMTX_NF
5.2725.272

Details for 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.11 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:985.29
MW Contribution:4.87
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:96.98 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:954.41
MW Contribution:4.65
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.332941176470588240.283
961672AG1-007 E
Adder
0.188235294117647060.16
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
963041AG1-153 C
Adder
1.9482352941176471.656
963042AG1-153 E
Adder
2.92235294117647062.484
966621AG1-532 C
Adder
0.61294117647058830.521
966622AG1-532 E
Adder
0.408235294117647030.347
3145413WATKINS
Adder
0.26470588235294120.225
3145723EMPORIA
Adder
0.185882352941176470.158
3151311EDGECMA
Adder
5.5117647058823534.685
918492AA1-063AE OP
Adder
1.59411764705882361.355
918532AA1-067 E
Adder
0.251764705882352950.214
919692AA2-053 E OP
Adder
1.64941176470588241.402
920042AA2-088 E OP
Adder
4.0811764705882353.469
925785AC1-054 E
Adder
1.2082352941176471.027
927146AC1-208 E
Adder
1.51.275
934521AD1-076 C
Adder
4.377647058823533.721
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
944011AF1-069 C
Adder
4.6141176470588243.922
944012AF1-069 E
Adder
1.7917647058823531.523
960081AF2-299 C
Adder
0.81647058823529410.694
960082AF2-299 E
Adder
0.54470588235294130.463
316141AB2-099 E
Adder
0.095294117647058830.081
900672V4-068 E
Adder
0.136470588235294120.116
917342Z2-044 E
Adder
0.215294117647058830.183
922923AB1-081 E OP
Adder
1.321.122
923263AB1-132 E OP
Adder
2.582.193
923573AB1-173 E OP
Adder
1.36823529411764721.163
924162AB2-060 E OP
Adder
1.3117647058823531.115
924302AB2-077 E O1
Adder
0.41176470588235290.35
924312AB2-078 E O1
Adder
0.41176470588235290.35
924322AB2-079 E O1
Adder
0.41176470588235290.35
940492AE2-034 E
Adder
1.09058823529411760.927
941031AE2-094 C
Adder
14.12000000000000112.002
941032AE2-094 E
Adder
6.3247058823529425.376
946281AF1-292 C
Adder
0.67529411764705880.574
946282AF1-292 E
Adder
0.45058823529411770.383
957481AF2-042 C
Adder
17.0152941176470614.463
957482AF2-042 E
Adder
11.3435294117647069.642
957861AF2-080 C
Adder
2.7023529411764712.297
957862AF2-080 E
Adder
1.19764705882352951.018
3145393UNCAMP
Adder
2.3247058823529411.976
916042Z1-036 E
Adder
9.9682352941176488.473
938771AE1-103 C
Adder
1.11764705882352940.95
938772AE1-103 E
Adder
1.5435294117647061.312
3143316POE
50/50
1.0861.086
3145256KINGFORK
Adder
0.357647058823529430.304
3145506HICKORY
Adder
0.72352941176470590.615
3150651CHESTF6
50/50
21.89721.897
3150731STONECA
50/50
4.5124.512
3150761HOPPOLC
50/50
1.0021.002
3150771HOPHCF1
50/50
1.5941.594
3150781HOPHCF2
50/50
1.5941.594
3150791HOPHCF3
50/50
1.5941.594
3150801HOPHCF4
50/50
2.4192.419
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
926662AC1-147 E
Adder
0.452941176470588240.385
926755AC1-161 E
Adder
3.78588235294117673.218
927226AC1-216 E
Adder
4.122352941176473.504
935112AD1-144 E
Adder
0.33176470588235290.282
942341AE2-247 C
Adder
0.68470588235294120.582
942342AE2-247 E
Adder
0.94470588235294130.803
943461AF1-017 C
Adder
0.61882352941176480.526
943462AF1-017 E
Adder
1.00941176470588250.858
943612AF1-032 E
Adder
0.320.272
316132AB2-190 C
50/50
2.4122.412
913392Y1-086 E
Adder
0.74470588235294120.633
916192Z1-068 E
Adder
0.63294117647058830.538
923832AB2-022 E
Adder
0.421176470588235260.358
923852AB2-025 E
Adder
0.6317647058823530.537
939312AE1-162 E
Adder
0.5717647058823530.486
946262AF1-291 E
50/50
1.6321.632
957492AF2-043 E
Adder
0.49294117647058820.419
901082W1-029 E
Adder
10.9870588235294139.339
917122Z2-027 E
Adder
0.457647058823529460.389
925332AB2-190 E
50/50
4.6914.691
925522AC1-027 E
Adder
0.410588235294117640.349
942001AE2-212 C
50/50
2.1112.111
942002AE2-212 E
50/50
1.4081.408
957871AF2-081 C
Adder
3.34117647058823542.84
957872AF2-081 E
Adder
1.4317647058823531.217
958161AF2-110 C
Adder
0.51764705882352950.44
958162AF2-110 E
Adder
0.82470588235294120.701
917512Z2-088 E OP1
Adder
1.73411764705882351.474
926071AC1-086 C
Adder
8.8647058823529427.535
926072AC1-086 E
Adder
4.0352941176470593.43
927021AC1-189 C
Adder
2.97529411764705862.529
927022AC1-189 E
Adder
1.48235294117647071.26
933291AC2-141 C
Adder
8.8694117647058827.539
933292AC2-141 E
Adder
3.78588235294117673.218
934621AD1-088 C
Adder
2.86941176470588262.439
934622AD1-088 E
Adder
1.38117647058823521.174
939411AE1-173 C
Adder
31.5352941176470626.805
939412AE1-173 E
Adder
21.0235294117647117.87
934012AD1-025 E
Adder
5.3364705882352944.536
933981AD1-022 C
Adder
3.162.686
933982AD1-022 E
Adder
1.721.462
962572AG1-106 E
Adder
0.50117647058823530.426
962571AG1-106 C
Adder
1.14705882352941170.975
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
3146326AYDLETT TAP
Adder
0.455294117647058850.387
316240AF1-291 C
50/50
2.4482.448
316263AC1-034 C
Adder
2.3517647058823531.999
316274AC1-208 C
Adder
3.3788235294117652.872
917332KELFORD E
Adder
0.61411764705882350.522
924516AB2-100 E1
Adder
1.36823529411764721.163
924517AB2-100 E2
Adder
1.36823529411764721.163
925595AC1-034 E
Adder
1.77411764705882361.508
926206AC1-098 E
Adder
1.35999999999999991.156
926214AC1-099 E
Adder
0.44941176470588240.382
934065AD1-033 E
Adder
1.6670588235294121.417
937226AE2-253 E
Adder
1.9482352941176471.656
918512AA1-065 E OP
Adder
2.04235294117647071.736
919153AA1-139 E2
Adder
1.36588235294117651.161
919152AA1-139 E1
Adder
1.36588235294117651.161
919710AA2-057 E
Adder
1.44823529411764731.231
920692AA2-178 E
Adder
1.4552941176470591.237
923994AB2-040_E
Adder
2.56588235294117652.181
924022AB2-043 E O1
Adder
1.60117647058823541.361
924152AB2-059 E OP
Adder
1.87058823529411791.59
924814AB2-134 E
Adder
6.7529411764705885.74
316083AB2-161 C
50/50
0.3210.321
316084AB2-161 E
50/50
3.213.21
925122AB2-169 E
Adder
2.04352941176470631.737
316088AB2-174 E
Adder
2.7588235294117652.345
932046AC2-012 E
Adder
4.4823529411764713.81
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
316381AD1-082 C
50/50
0.7330.733
934576AD1-082 E
50/50
2.5582.558
316349AD2-085 C
Adder
1.57882352941176471.342
936666AD2-085 E
Adder
2.5752941176470592.189
961611AG1-000B C
Adder
7.342352941176476.241
941591AE2-156 C
Adder
6.1141176470588245.197
944581AF1-123 C
Adder
15.03411764705882412.779
944582AF1-123 E
Adder
34.4258823529411829.262
944591AF1-124 C
Adder
15.08705882352941312.824
944592AF1-124 E
Adder
34.55058823529411429.368
944601AF1-125 C
Adder
14.80235294117647312.582
944602AF1-125 E
Adder
33.8847058823529428.802
964241AG1-285 C
Adder
3.85882352941176483.28
964242AG1-285 E
Adder
2.5717647058823532.186
3137643SOCKMAN
Adder
0.288235294117647030.245
932632AC2-084 E
Adder
1.20235294117647061.022
934321AD1-056 C
Adder
2.3988235294117652.039
934322AD1-056 E
Adder
1.30117647058823541.106
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934501AD1-074 C
Adder
12.05529411764705810.247
934502AD1-074 E
Adder
6.1364705882352945.216
934511AD1-075 C
Adder
3.01411764705882362.562
934512AD1-075 E
Adder
1.53411764705882361.304
934612AD1-087 E
Adder
1.1117647058823530.945
935161AD1-151 C
50/50
9.0229.022
935162AD1-151 E
50/50
6.0156.015
935172AD1-152 E
Adder
1.6435294117647061.397
937482AD2-202 E
Adder
0.32588235294117650.277
938531AE1-072 C
Adder
5.8905882352941185.007
938532AE1-072 E
Adder
3.07058823529411742.61
939191AE1-149 C
50/50
7.1377.137
939192AE1-149 E
50/50
4.7584.758
940431AE2-027 C
Adder
7.0447058823529425.988
940432AE2-027 E
Adder
4.6964705882352943.992
940481AE2-033 C
Adder
8.6517647058823537.354
940482AE2-033 E
Adder
5.8329411764705884.958
940541AE2-040 C
Adder
1.56117647058823541.327
940641AE2-051 C
Adder
6.0952941176470595.181
940642AE2-051 E
Adder
4.0635294117647063.454
941101AE2-104 C
Adder
1.26941176470588221.079
941102AE2-104 E
Adder
2.0188235294117651.716
944641AF1-129 C
50/50
120.262120.262
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883

Details for 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.74 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1020.96
MW Contribution:4.87
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.61 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:990.18
MW Contribution:4.65
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.332941176470588240.283
961672AG1-007 E
Adder
0.188235294117647060.16
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
963041AG1-153 C
Adder
1.9482352941176471.656
963042AG1-153 E
Adder
2.92235294117647062.484
966621AG1-532 C
Adder
0.61294117647058830.521
966622AG1-532 E
Adder
0.408235294117647030.347
3145413WATKINS
Adder
0.26470588235294120.225
3145723EMPORIA
Adder
0.185882352941176470.158
3151311EDGECMA
Adder
5.5117647058823534.685
918492AA1-063AE OP
Adder
1.59411764705882361.355
918532AA1-067 E
Adder
0.251764705882352950.214
919692AA2-053 E OP
Adder
1.64941176470588241.402
920042AA2-088 E OP
Adder
4.0811764705882353.469
925785AC1-054 E
Adder
1.2082352941176471.027
927146AC1-208 E
Adder
1.51.275
934521AD1-076 C
Adder
4.377647058823533.721
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
944011AF1-069 C
Adder
4.6141176470588243.922
944012AF1-069 E
Adder
1.7917647058823531.523
960081AF2-299 C
Adder
0.81647058823529410.694
960082AF2-299 E
Adder
0.54470588235294130.463
316141AB2-099 E
Adder
0.095294117647058830.081
900672V4-068 E
Adder
0.136470588235294120.116
917342Z2-044 E
Adder
0.215294117647058830.183
922923AB1-081 E OP
Adder
1.321.122
923263AB1-132 E OP
Adder
2.582.193
923573AB1-173 E OP
Adder
1.36823529411764721.163
924162AB2-060 E OP
Adder
1.3117647058823531.115
924302AB2-077 E O1
Adder
0.41176470588235290.35
924312AB2-078 E O1
Adder
0.41176470588235290.35
924322AB2-079 E O1
Adder
0.41176470588235290.35
940492AE2-034 E
Adder
1.09058823529411760.927
941031AE2-094 C
Adder
14.12000000000000112.002
941032AE2-094 E
Adder
6.3247058823529425.376
946281AF1-292 C
Adder
0.67529411764705880.574
946282AF1-292 E
Adder
0.45058823529411770.383
957481AF2-042 C
Adder
17.0152941176470614.463
957482AF2-042 E
Adder
11.3435294117647069.642
957861AF2-080 C
Adder
2.7023529411764712.297
957862AF2-080 E
Adder
1.19764705882352951.018
3145393UNCAMP
Adder
2.3247058823529411.976
916042Z1-036 E
Adder
9.9682352941176488.473
938771AE1-103 C
Adder
1.11764705882352940.95
938772AE1-103 E
Adder
1.5435294117647061.312
3143316POE
50/50
1.0861.086
3145256KINGFORK
Adder
0.357647058823529430.304
3145506HICKORY
Adder
0.72352941176470590.615
3150651CHESTF6
50/50
21.89721.897
3150731STONECA
50/50
4.5124.512
3150761HOPPOLC
50/50
1.0021.002
3150771HOPHCF1
50/50
1.5941.594
3150781HOPHCF2
50/50
1.5941.594
3150791HOPHCF3
50/50
1.5941.594
3150801HOPHCF4
50/50
2.4192.419
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
926662AC1-147 E
Adder
0.452941176470588240.385
926755AC1-161 E
Adder
3.78588235294117673.218
927226AC1-216 E
Adder
4.122352941176473.504
935112AD1-144 E
Adder
0.33176470588235290.282
942341AE2-247 C
Adder
0.68470588235294120.582
942342AE2-247 E
Adder
0.94470588235294130.803
943461AF1-017 C
Adder
0.61882352941176480.526
943462AF1-017 E
Adder
1.00941176470588250.858
943612AF1-032 E
Adder
0.320.272
316132AB2-190 C
50/50
2.4122.412
913392Y1-086 E
Adder
0.74470588235294120.633
916192Z1-068 E
Adder
0.63294117647058830.538
923832AB2-022 E
Adder
0.421176470588235260.358
923852AB2-025 E
Adder
0.6317647058823530.537
939312AE1-162 E
Adder
0.5717647058823530.486
946262AF1-291 E
50/50
1.6321.632
957492AF2-043 E
Adder
0.49294117647058820.419
901082W1-029 E
Adder
10.9870588235294139.339
917122Z2-027 E
Adder
0.457647058823529460.389
925332AB2-190 E
50/50
4.6914.691
925522AC1-027 E
Adder
0.410588235294117640.349
942001AE2-212 C
50/50
2.1112.111
942002AE2-212 E
50/50
1.4081.408
957871AF2-081 C
Adder
3.34117647058823542.84
957872AF2-081 E
Adder
1.4317647058823531.217
958161AF2-110 C
Adder
0.51764705882352950.44
958162AF2-110 E
Adder
0.82470588235294120.701
917512Z2-088 E OP1
Adder
1.73411764705882351.474
926071AC1-086 C
Adder
8.8647058823529427.535
926072AC1-086 E
Adder
4.0352941176470593.43
927021AC1-189 C
Adder
2.97529411764705862.529
927022AC1-189 E
Adder
1.48235294117647071.26
933291AC2-141 C
Adder
8.8694117647058827.539
933292AC2-141 E
Adder
3.78588235294117673.218
934621AD1-088 C
Adder
2.86941176470588262.439
934622AD1-088 E
Adder
1.38117647058823521.174
939411AE1-173 C
Adder
31.5352941176470626.805
939412AE1-173 E
Adder
21.0235294117647117.87
934012AD1-025 E
Adder
5.3364705882352944.536
933981AD1-022 C
Adder
3.162.686
933982AD1-022 E
Adder
1.721.462
962572AG1-106 E
Adder
0.50117647058823530.426
962571AG1-106 C
Adder
1.14705882352941170.975
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
3146326AYDLETT TAP
Adder
0.455294117647058850.387
316240AF1-291 C
50/50
2.4482.448
316263AC1-034 C
Adder
2.3517647058823531.999
316274AC1-208 C
Adder
3.3788235294117652.872
917332KELFORD E
Adder
0.61411764705882350.522
924516AB2-100 E1
Adder
1.36823529411764721.163
924517AB2-100 E2
Adder
1.36823529411764721.163
925595AC1-034 E
Adder
1.77411764705882361.508
926206AC1-098 E
Adder
1.35999999999999991.156
926214AC1-099 E
Adder
0.44941176470588240.382
934065AD1-033 E
Adder
1.6670588235294121.417
937226AE2-253 E
Adder
1.9482352941176471.656
918512AA1-065 E OP
Adder
2.04235294117647071.736
919153AA1-139 E2
Adder
1.36588235294117651.161
919152AA1-139 E1
Adder
1.36588235294117651.161
919710AA2-057 E
Adder
1.44823529411764731.231
920692AA2-178 E
Adder
1.4552941176470591.237
923994AB2-040_E
Adder
2.56588235294117652.181
924022AB2-043 E O1
Adder
1.60117647058823541.361
924152AB2-059 E OP
Adder
1.87058823529411791.59
924814AB2-134 E
Adder
6.7529411764705885.74
316083AB2-161 C
50/50
0.3210.321
316084AB2-161 E
50/50
3.213.21
925122AB2-169 E
Adder
2.04352941176470631.737
316088AB2-174 E
Adder
2.7588235294117652.345
932046AC2-012 E
Adder
4.4823529411764713.81
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
316381AD1-082 C
50/50
0.7330.733
934576AD1-082 E
50/50
2.5582.558
316349AD2-085 C
Adder
1.57882352941176471.342
936666AD2-085 E
Adder
2.5752941176470592.189
961611AG1-000B C
Adder
7.342352941176476.241
941591AE2-156 C
Adder
6.1141176470588245.197
944581AF1-123 C
Adder
15.03411764705882412.779
944582AF1-123 E
Adder
34.4258823529411829.262
944591AF1-124 C
Adder
15.08705882352941312.824
944592AF1-124 E
Adder
34.55058823529411429.368
944601AF1-125 C
Adder
14.80235294117647312.582
944602AF1-125 E
Adder
33.8847058823529428.802
964241AG1-285 C
Adder
3.85882352941176483.28
964242AG1-285 E
Adder
2.5717647058823532.186
3137643SOCKMAN
Adder
0.288235294117647030.245
932632AC2-084 E
Adder
1.20235294117647061.022
934321AD1-056 C
Adder
2.3988235294117652.039
934322AD1-056 E
Adder
1.30117647058823541.106
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934501AD1-074 C
Adder
12.05529411764705810.247
934502AD1-074 E
Adder
6.1364705882352945.216
934511AD1-075 C
Adder
3.01411764705882362.562
934512AD1-075 E
Adder
1.53411764705882361.304
934612AD1-087 E
Adder
1.1117647058823530.945
935161AD1-151 C
50/50
9.0229.022
935162AD1-151 E
50/50
6.0156.015
935172AD1-152 E
Adder
1.6435294117647061.397
937482AD2-202 E
Adder
0.32588235294117650.277
938531AE1-072 C
Adder
5.8905882352941185.007
938532AE1-072 E
Adder
3.07058823529411742.61
939191AE1-149 C
50/50
7.1377.137
939192AE1-149 E
50/50
4.7584.758
940431AE2-027 C
Adder
7.0447058823529425.988
940432AE2-027 E
Adder
4.6964705882352943.992
940481AE2-033 C
Adder
8.6517647058823537.354
940482AE2-033 E
Adder
5.8329411764705884.958
940541AE2-040 C
Adder
1.56117647058823541.327
940641AE2-051 C
Adder
6.0952941176470595.181
940642AE2-051 E
Adder
4.0635294117647063.454
941101AE2-104 C
Adder
1.26941176470588221.079
941102AE2-104 E
Adder
2.0188235294117651.716
944641AF1-129 C
50/50
120.262120.262
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883

Details for 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.68 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1020.42
MW Contribution:4.87
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:100.56 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:989.69
MW Contribution:4.65
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.332941176470588240.283
961672AG1-007 E
Adder
0.188235294117647060.16
961941AG1-037 C
Adder
0.189411764705882360.161
961942AG1-037 E
Adder
0.125882352941176470.107
963041AG1-153 C
Adder
1.9482352941176471.656
963042AG1-153 E
Adder
2.92235294117647062.484
966621AG1-532 C
Adder
0.61294117647058830.521
966622AG1-532 E
Adder
0.408235294117647030.347
3145413WATKINS
Adder
0.26470588235294120.225
3145723EMPORIA
Adder
0.185882352941176470.158
3151311EDGECMA
Adder
5.5117647058823534.685
918492AA1-063AE OP
Adder
1.59411764705882361.355
918532AA1-067 E
Adder
0.251764705882352950.214
919692AA2-053 E OP
Adder
1.64941176470588241.402
920042AA2-088 E OP
Adder
4.0811764705882353.469
925785AC1-054 E
Adder
1.2082352941176471.027
927146AC1-208 E
Adder
1.51.275
934521AD1-076 C
Adder
4.377647058823533.721
934522AD1-076 E
Adder
2.2317647058823531.897
943172AE2-346 E
Adder
0.227058823529411790.193
944011AF1-069 C
Adder
4.6141176470588243.922
944012AF1-069 E
Adder
1.7917647058823531.523
960081AF2-299 C
Adder
0.81647058823529410.694
960082AF2-299 E
Adder
0.54470588235294130.463
316141AB2-099 E
Adder
0.095294117647058830.081
900672V4-068 E
Adder
0.136470588235294120.116
917342Z2-044 E
Adder
0.215294117647058830.183
922923AB1-081 E OP
Adder
1.321.122
923263AB1-132 E OP
Adder
2.582.193
923573AB1-173 E OP
Adder
1.36823529411764721.163
924162AB2-060 E OP
Adder
1.3117647058823531.115
924302AB2-077 E O1
Adder
0.41176470588235290.35
924312AB2-078 E O1
Adder
0.41176470588235290.35
924322AB2-079 E O1
Adder
0.41176470588235290.35
940492AE2-034 E
Adder
1.09058823529411760.927
941031AE2-094 C
Adder
14.12000000000000112.002
941032AE2-094 E
Adder
6.3247058823529425.376
946281AF1-292 C
Adder
0.67529411764705880.574
946282AF1-292 E
Adder
0.45058823529411770.383
957481AF2-042 C
Adder
17.0152941176470614.463
957482AF2-042 E
Adder
11.3435294117647069.642
957861AF2-080 C
Adder
2.7023529411764712.297
957862AF2-080 E
Adder
1.19764705882352951.018
3145393UNCAMP
Adder
2.3247058823529411.976
916042Z1-036 E
Adder
9.9682352941176488.473
938771AE1-103 C
Adder
1.11764705882352940.95
938772AE1-103 E
Adder
1.5435294117647061.312
3143316POE
50/50
1.0861.086
3145256KINGFORK
Adder
0.357647058823529430.304
3145506HICKORY
Adder
0.72352941176470590.615
3150651CHESTF6
50/50
21.89721.897
3150731STONECA
50/50
4.5124.512
3150761HOPPOLC
50/50
1.0021.002
3150771HOPHCF1
50/50
1.5941.594
3150781HOPHCF2
50/50
1.5941.594
3150791HOPHCF3
50/50
1.5941.594
3150801HOPHCF4
50/50
2.4192.419
3150831SPRUNCA
Adder
2.6776470588235292.276
3150841SPRUNCB
Adder
2.6776470588235292.276
926662AC1-147 E
Adder
0.452941176470588240.385
926755AC1-161 E
Adder
3.78588235294117673.218
927226AC1-216 E
Adder
4.122352941176473.504
935112AD1-144 E
Adder
0.33176470588235290.282
942341AE2-247 C
Adder
0.68470588235294120.582
942342AE2-247 E
Adder
0.94470588235294130.803
943461AF1-017 C
Adder
0.61882352941176480.526
943462AF1-017 E
Adder
1.00941176470588250.858
943612AF1-032 E
Adder
0.320.272
316132AB2-190 C
50/50
2.4122.412
913392Y1-086 E
Adder
0.74470588235294120.633
916192Z1-068 E
Adder
0.63294117647058830.538
923832AB2-022 E
Adder
0.421176470588235260.358
923852AB2-025 E
Adder
0.6317647058823530.537
939312AE1-162 E
Adder
0.5717647058823530.486
946262AF1-291 E
50/50
1.6321.632
957492AF2-043 E
Adder
0.49294117647058820.419
901082W1-029 E
Adder
10.9870588235294139.339
917122Z2-027 E
Adder
0.457647058823529460.389
925332AB2-190 E
50/50
4.6914.691
925522AC1-027 E
Adder
0.410588235294117640.349
942001AE2-212 C
50/50
2.1112.111
942002AE2-212 E
50/50
1.4081.408
957871AF2-081 C
Adder
3.34117647058823542.84
957872AF2-081 E
Adder
1.4317647058823531.217
958161AF2-110 C
Adder
0.51764705882352950.44
958162AF2-110 E
Adder
0.82470588235294120.701
917512Z2-088 E OP1
Adder
1.73411764705882351.474
926071AC1-086 C
Adder
8.8647058823529427.535
926072AC1-086 E
Adder
4.0352941176470593.43
927021AC1-189 C
Adder
2.97529411764705862.529
927022AC1-189 E
Adder
1.48235294117647071.26
933291AC2-141 C
Adder
8.8694117647058827.539
933292AC2-141 E
Adder
3.78588235294117673.218
934621AD1-088 C
Adder
2.86941176470588262.439
934622AD1-088 E
Adder
1.38117647058823521.174
939411AE1-173 C
Adder
31.5352941176470626.805
939412AE1-173 E
Adder
21.0235294117647117.87
934012AD1-025 E
Adder
5.3364705882352944.536
933981AD1-022 C
Adder
3.162.686
933982AD1-022 E
Adder
1.721.462
962572AG1-106 E
Adder
0.50117647058823530.426
962571AG1-106 C
Adder
1.14705882352941170.975
3145946PLYMOUTH TP
Adder
0.115294117647058820.098
3146326AYDLETT TAP
Adder
0.455294117647058850.387
316240AF1-291 C
50/50
2.4482.448
316263AC1-034 C
Adder
2.3517647058823531.999
316274AC1-208 C
Adder
3.3788235294117652.872
917332KELFORD E
Adder
0.61411764705882350.522
924516AB2-100 E1
Adder
1.36823529411764721.163
924517AB2-100 E2
Adder
1.36823529411764721.163
925595AC1-034 E
Adder
1.77411764705882361.508
926206AC1-098 E
Adder
1.35999999999999991.156
926214AC1-099 E
Adder
0.44941176470588240.382
934065AD1-033 E
Adder
1.6670588235294121.417
937226AE2-253 E
Adder
1.9482352941176471.656
918512AA1-065 E OP
Adder
2.04235294117647071.736
919153AA1-139 E2
Adder
1.36588235294117651.161
919152AA1-139 E1
Adder
1.36588235294117651.161
919710AA2-057 E
Adder
1.44823529411764731.231
920692AA2-178 E
Adder
1.4552941176470591.237
923994AB2-040_E
Adder
2.56588235294117652.181
924022AB2-043 E O1
Adder
1.60117647058823541.361
924152AB2-059 E OP
Adder
1.87058823529411791.59
924814AB2-134 E
Adder
6.7529411764705885.74
316083AB2-161 C
50/50
0.3210.321
316084AB2-161 E
50/50
3.213.21
925122AB2-169 E
Adder
2.04352941176470631.737
316088AB2-174 E
Adder
2.7588235294117652.345
932046AC2-012 E
Adder
4.4823529411764713.81
316311AC2-079 C
Adder
2.5717647058823532.186
932596AC2-079 E
Adder
4.1964705882352953.567
316381AD1-082 C
50/50
0.7330.733
934576AD1-082 E
50/50
2.5582.558
316349AD2-085 C
Adder
1.57882352941176471.342
936666AD2-085 E
Adder
2.5752941176470592.189
961611AG1-000B C
Adder
7.342352941176476.241
941591AE2-156 C
Adder
6.1141176470588245.197
944581AF1-123 C
Adder
15.03411764705882412.779
944582AF1-123 E
Adder
34.4258823529411829.262
944591AF1-124 C
Adder
15.08705882352941312.824
944592AF1-124 E
Adder
34.55058823529411429.368
944601AF1-125 C
Adder
14.80235294117647312.582
944602AF1-125 E
Adder
33.8847058823529428.802
964241AG1-285 C
Adder
3.85882352941176483.28
964242AG1-285 E
Adder
2.5717647058823532.186
3137643SOCKMAN
Adder
0.288235294117647030.245
932632AC2-084 E
Adder
1.20235294117647061.022
934321AD1-056 C
Adder
2.3988235294117652.039
934322AD1-056 E
Adder
1.30117647058823541.106
934331AD1-057 C
Adder
1.33882352941176451.138
934332AD1-057 E
Adder
0.69647058823529410.592
934501AD1-074 C
Adder
12.05529411764705810.247
934502AD1-074 E
Adder
6.1364705882352945.216
934511AD1-075 C
Adder
3.01411764705882362.562
934512AD1-075 E
Adder
1.53411764705882361.304
934612AD1-087 E
Adder
1.1117647058823530.945
935161AD1-151 C
50/50
9.0229.022
935162AD1-151 E
50/50
6.0156.015
935172AD1-152 E
Adder
1.6435294117647061.397
937482AD2-202 E
Adder
0.32588235294117650.277
938531AE1-072 C
Adder
5.8905882352941185.007
938532AE1-072 E
Adder
3.07058823529411742.61
939191AE1-149 C
50/50
7.1377.137
939192AE1-149 E
50/50
4.7584.758
940431AE2-027 C
Adder
7.0447058823529425.988
940432AE2-027 E
Adder
4.6964705882352943.992
940481AE2-033 C
Adder
8.6517647058823537.354
940482AE2-033 E
Adder
5.8329411764705884.958
940541AE2-040 C
Adder
1.56117647058823541.327
940641AE2-051 C
Adder
6.0952941176470595.181
940642AE2-051 E
Adder
4.0635294117647063.454
941101AE2-104 C
Adder
1.26941176470588221.079
941102AE2-104 E
Adder
2.0188235294117651.716
944641AF1-129 C
50/50
120.262120.262
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.6671.667
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.6896.689
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.585.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.89227.892
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9230.923
NYPJM->LTFIMP_NY
CLTF
0.4360.436
LGEELTFEXP_LGEE->PJM
CLTF
0.2670.267
WECLTFEXP_WEC->PJM
CLTF
0.140.14
CPLELTFEXP_CPLE->PJM
CLTF
3.4983.498
TVALTFEXP_TVA->PJM
CLTF
1.561.56
MECLTFEXP_MEC->PJM
CLTF
0.9120.912
LAGNLTFEXP_LAGN->PJM
CLTF
2.0042.004
SIGELTFEXP_SIGE->PJM
CLTF
0.0550.055
O66PJM->LTFIMP_O-066
CMTX_NF
5.8835.883

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.12 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3352.99
MW Contribution:20.8
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3492.91
MW Contribution:20.39
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
1.05882352941176470.9
961672AG1-007 E
Adder
0.60.51
961791AG1-021 C
Adder
1.63058823529411771.386
961792AG1-021 E
Adder
1.38941176470588231.181
961941AG1-037 C
Adder
0.5717647058823530.486
961942AG1-037 E
Adder
0.381176470588235340.324
963041AG1-153 C
50/50
8.3218.321
963042AG1-153 E
50/50
12.48112.481
964791AG1-342 C
Adder
3.96470588235294133.37
964792AG1-342 E
Adder
2.6435294117647062.247
966621AG1-532 C
50/50
1.6281.628
966622AG1-532 E
50/50
1.0851.085
3138533PONTONDP
Adder
0.60352941176470590.513
3145413WATKINS
Adder
0.7717647058823530.656
3145723EMPORIA
50/50
0.50.5
3147133PAMPLIN
Adder
0.89882352941176480.764
3151311EDGECMA
Adder
17.50705882352941214.881
3151531CLOVER1
50/50
15.90515.905
3151541CLOVER2
50/50
15.75715.757
918492AA1-063AE OP
Adder
4.65058823529411753.953
918532AA1-067 E
Adder
0.80588235294117660.685
919692AA2-053 E OP
Adder
4.8352941176470594.11
920042AA2-088 E OP
Adder
11.94941176470588210.157
925785AC1-054 E
Adder
3.94000000000000043.349
926274AC1-105 E
Adder
2.9882352941176472.54
927146AC1-208 E
Adder
4.5541176470588243.871
934521AD1-076 C
Adder
13.81176470588235411.74
934522AD1-076 E
Adder
7.045.984
943172AE2-346 E
Adder
0.68588235294117650.583
943902AF1-058 E
Adder
1.42941176470588241.215
944011AF1-069 C
50/50
19.88619.886
944012AF1-069 E
50/50
7.7257.725
959311AF2-222 C
Adder
17.79058823529411615.122
959312AF2-222 E
Adder
11.9210.132
960081AF2-299 C
50/50
2.1712.171
960082AF2-299 E
50/50
1.4471.447
316141AB2-099 E
Adder
0.28588235294117650.243
900672V4-068 E
Adder
0.402352941176470640.342
917342Z2-044 E
Adder
0.6764705882352940.575
922923AB1-081 E OP
Adder
4.20470588235294153.574
923263AB1-132 E OP
Adder
7.0270588235294125.973
923573AB1-173 E OP
Adder
3.78941176470588253.221
924162AB2-060 E OP
Adder
4.8364705882352944.111
924302AB2-077 E O1
Adder
1.52117647058823541.293
924312AB2-078 E O1
Adder
1.52117647058823541.293
924322AB2-079 E O1
Adder
1.52117647058823541.293
925612AC1-036 E
Adder
0.93294117647058830.793
940492AE2-034 E
Adder
3.4764705882352942.955
941031AE2-094 C
50/50
60.86460.864
941032AE2-094 E
50/50
27.25927.259
946281AF1-292 C
50/50
1.7971.797
946282AF1-292 E
50/50
1.1981.198
946301AF1-294 C
Adder
3.3517647058823532.849
946302AF1-294 E
Adder
2.83882352941176472.413
957481AF2-042 C
50/50
69.9469.94
957482AF2-042 E
50/50
46.62746.627
957861AF2-080 C
Adder
8.6200000000000017.327
957862AF2-080 E
Adder
3.8211764705882363.248
958211AF2-115 C
Adder
2.03764705882352941.732
958212AF2-115 E
Adder
1.73647058823529421.476
3145393UNCAMP
Adder
6.7635294117647065.749
916042Z1-036 E
Adder
32.1705882352941227.345
938771AE1-103 C
Adder
3.24823529411764732.761
938772AE1-103 E
Adder
4.4858823529411773.813
313526AB2-022 C
50/50
0.4240.424
3143316POE
Adder
1.30823529411764721.112
3145256KINGFORK
Adder
1.06588235294117650.906
3145506HICKORY
50/50
2.4672.467
926662AC1-147 E
Adder
1.46588235294117641.246
926755AC1-161 E
50/50
14.89414.894
935112AD1-144 E
Adder
0.98941176470588230.841
942341AE2-247 C
Adder
1.54941176470588231.317
942342AE2-247 E
Adder
2.141.819
943461AF1-017 C
Adder
1.40235294117647061.192
943462AF1-017 E
Adder
2.2870588235294121.944
943612AF1-032 E
Adder
1.02823529411764710.874
3151021BRUNSWICKG1
50/50
12.28212.282
3151031BRUNSWICKG2
50/50
12.28212.282
3151041BRUNSWICKG3
50/50
12.28212.282
3151051BRUNSWICKS1
50/50
25.51625.516
3151081ELIZAR1
50/50
3.5563.556
3151091ELIZAR2
50/50
3.4953.495
3151101ELIZAR3
50/50
3.6013.601
3152411Z1-086 GT1
50/50
15.81615.816
3152421Z1-086 GT2
50/50
15.81115.811
3152431Z1-086 GT3
50/50
15.81115.811
3152441Z1-086 ST
50/50
27.53327.533
913392Y1-086 E
50/50
2.4762.476
916192Z1-068 E
50/50
2.1052.105
923832AB2-022 E
50/50
1.3981.398
923852AB2-025 E
50/50
1.3891.389
939312AE1-162 E
Adder
1.37058823529411771.165
957492AF2-043 E
Adder
1.58117647058823541.344
901082W1-029 E
Adder
35.7705882352941230.405
917122Z2-027 E
50/50
1.5121.512
925522AC1-027 E
50/50
1.3621.362
957871AF2-081 C
50/50
11.29311.293
957872AF2-081 E
50/50
4.844.84
958161AF2-110 C
Adder
1.49647058823529421.272
958162AF2-110 E
Adder
2.38000000000000032.023
3147223TWITTYS
Adder
1.03411764705882360.879
917512Z2-088 E OP1
Adder
5.5247058823529414.696
926071AC1-086 C
Adder
24.1447058823529420.523
926072AC1-086 E
Adder
10.9894117647058819.341
927021AC1-189 C
Adder
9.4905882352941178.067
927022AC1-189 E
Adder
4.7282352941176474.019
936261AD2-033 C
Adder
13.51176470588235311.485
936262AD2-033 E
Adder
9.0082352941176477.657
933291AC2-141 C
50/50
34.8934.89
933292AC2-141 E
50/50
14.89414.894
934621AD1-088 C
50/50
11.53711.537
934622AD1-088 E
50/50
5.5555.555
939411AE1-173 C
50/50
128.665128.665
939412AE1-173 E
50/50
85.77785.777
916191Z1-068 C
50/50
0.0490.049
933981AD1-022 C
Adder
9.8917647058823528.408
933982AD1-022 E
Adder
5.3847058823529414.577
962572AG1-106 E
Adder
1.36588235294117651.161
962571AG1-106 C
Adder
3.1235294117647062.655
3145946PLYMOUTH TP
Adder
0.364705882352941160.31
3146326AYDLETT TAP
50/50
1.5311.531
316023AB2-100 C2
50/50
1.1231.123
316185AD1-033 C
50/50
1.391.39
316263AC1-034 C
Adder
7.4894117647058826.366
316274AC1-208 C
Adder
10.255294117647068.717
316294AC1-161 C
50/50
5.7015.701
316315AB2-025 C
50/50
0.4880.488
316316AC1-027 C
50/50
0.3530.353
316320Y1-086 C
50/50
0.2480.248
316321Z2-027 C
50/50
0.410.41
316365AB2-100 C1
50/50
1.1231.123
917332KELFORD E
Adder
1.8635294117647061.584
924516AB2-100 E1
50/50
3.3843.384
924517AB2-100 E2
50/50
3.3843.384
925595AC1-034 E
Adder
5.65058823529411754.803
926206AC1-098 E
Adder
4.1470588235294123.525
926214AC1-099 E
Adder
1.36941176470588231.164
927255AC1-221 E
Adder
4.1411764705882363.52
927264AC1-222 E
Adder
4.3282352941176473.679
932763AC2-100 E
Adder
2.80941176470588252.388
934065AD1-033 E
50/50
5.6715.671
937226AE2-253 E
50/50
6.6066.606
918512AA1-065 E OP
Adder
6.2505882352941175.313
316017AA1-139 ULT1
50/50
1.2231.223
316018AA1-139 ULT2
50/50
1.2231.223
919153AA1-139 E2
50/50
4.6184.618
919152AA1-139 E1
50/50
4.6184.618
919710AA2-057 E
Adder
4.49411764705882363.82
920692AA2-178 E
Adder
4.6352941176470593.94
923994AB2-040_E
Adder
7.1047058823529416.039
924022AB2-043 E O1
Adder
5.9035294117647065.018
924152AB2-059 E OP
Adder
5.9564705882352945.063
316084AB2-161 E
Adder
5.26941176470588254.479
925122AB2-169 E
Adder
6.4858823529411775.513
316087AB2-174 C
50/50
1.3621.362
316088AB2-174 E
50/50
7.5427.542
316375AC2-012 C
50/50
1.4951.495
932046AC2-012 E
50/50
14.50114.501
316311AC2-079 C
Adder
5.9964705882352955.097
932596AC2-079 E
Adder
9.7835294117647078.316
934576AD1-082 E
Adder
4.1988235294117653.569
316349AD2-085 C
Adder
3.5752941176470593.039
936666AD2-085 E
Adder
5.8329411764705884.958
316388AE2-253 GEN
50/50
2.2212.221
961611AG1-000B C
Adder
5.824.947
941591AE2-156 C
50/50
19.83519.835
944581AF1-123 C
50/50
51.37451.374
944582AF1-123 E
50/50
117.641117.641
944591AF1-124 C
50/50
51.55751.557
944592AF1-124 E
50/50
118.067118.067
944601AF1-125 C
50/50
50.58350.583
944602AF1-125 E
50/50
115.795115.795
962561AG1-105 C
Adder
9.9705882352941188.475
962562AG1-105 E
Adder
6.6470588235294125.65
964241AG1-285 C
50/50
14.87614.876
964242AG1-285 E
50/50
9.9189.918
3137643SOCKMAN
Adder
0.81882352941176460.696
932632AC2-084 E
Adder
3.66588235294117663.116
934321AD1-056 C
Adder
7.126.052
934322AD1-056 E
Adder
3.86117647058823543.282
934331AD1-057 C
Adder
3.9717647058823533.376
934332AD1-057 E
Adder
2.0682352941176471.758
934501AD1-074 C
Adder
38.0305882352941232.326
934502AD1-074 E
Adder
19.3616.456
934511AD1-075 C
Adder
9.507058823529418.081
934512AD1-075 E
Adder
4.844.114
934611AD1-087 C
50/50
1.5661.566
934612AD1-087 E
50/50
4.5174.517
935171AD1-152 C
50/50
1.6091.609
935172AD1-152 E
50/50
6.6176.617
937481AD2-202 C
50/50
0.4540.454
937482AD2-202 E
50/50
1.3221.322
938531AE1-072 C
50/50
19.84719.847
938532AE1-072 E
50/50
10.34610.346
939191AE1-149 C
Adder
9.5941176470588238.155
939192AE1-149 E
Adder
6.3964705882352955.437
940481AE2-033 C
50/50
19.30519.305
940482AE2-033 E
50/50
13.01513.015
940541AE2-040 C
50/50
3.4343.434
940641AE2-051 C
50/50
26.11526.115
940642AE2-051 E
50/50
17.4117.41
941101AE2-104 C
Adder
3.66705882352941173.117
941102AE2-104 E
Adder
5.8305882352941184.956
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
6.3016.301
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.47229.472
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.8122.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
107.493107.493
G-007PJM->LTFIMP_G-007
CMTX_NF
3.5513.551
NYPJM->LTFIMP_NY
CLTF
1.6611.661
LGEELTFEXP_LGEE->PJM
CLTF
1.1651.165
WECLTFEXP_WEC->PJM
CLTF
0.6140.614
CPLELTFEXP_CPLE->PJM
CLTF
13.22113.221
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
MECLTFEXP_MEC->PJM
CLTF
3.8563.856
LAGNLTFEXP_LAGN->PJM
CLTF
8.048.04
SIGELTFEXP_SIGE->PJM
CLTF
0.2340.234
O66PJM->LTFIMP_O-066
CMTX_NF
22.61622.616

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:136.21 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3326.4
MW Contribution:17.93
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:145.97 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3564.84
MW Contribution:18.09
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.71294117647058820.606
961942AG1-037 E
Adder
0.475294117647058870.404
963041AG1-153 C
Adder
7.1717647058823536.096
963042AG1-153 E
Adder
10.757647058823539.144
966621AG1-532 C
Adder
1.72705882352941181.468
966622AG1-532 E
Adder
1.1517647058823530.979
3145413WATKINS
Adder
1.03764705882352940.882
3145723EMPORIA
Adder
0.53411764705882360.454
918492AA1-063AE OP
Adder
5.464705882352944.645
918532AA1-067 E
Adder
0.94588235294117650.804
919692AA2-053 E OP
Adder
5.50588235294117644.68
920042AA2-088 E OP
Adder
15.25058823529411712.963
934521AD1-076 C
Adder
18.52705882352941215.748
934522AD1-076 E
Adder
9.4435294117647068.027
943172AE2-346 E
Adder
0.85647058823529410.728
944011AF1-069 C
Adder
17.03647058823529314.481
944012AF1-069 E
Adder
6.6188235294117655.626
960081AF2-299 C
Adder
2.3023529411764711.957
960082AF2-299 E
Adder
1.53529411764705871.305
316141AB2-099 E
Adder
0.35647058823529410.303
900672V4-068 E
Adder
0.50705882352941180.431
923263AB1-132 E OP
Adder
7.79647058823529456.627
923573AB1-173 E OP
Adder
4.1152941176470593.498
940492AE2-034 E
Adder
4.8058823529411764.085
941031AE2-094 C
Adder
52.14117647058823544.32
941032AE2-094 E
Adder
23.3529411764705919.85
946281AF1-292 C
Adder
1.90588235294117661.62
946282AF1-292 E
Adder
1.27058823529411781.08
3145393UNCAMP
Adder
9.2964705882352947.902
916042Z1-036 E
50/50
46.21946.219
938771AE1-103 C
Adder
4.5305882352941173.851
938772AE1-103 E
Adder
6.257647058823535.319
313526AB2-022 C
50/50
0.640.64
3144216WINCHST
50/50
0.2310.231
3145256KINGFORK
50/50
1.7041.704
3145506HICKORY
50/50
3.8083.808
3150601CHESTF5
Adder
72.936470588235361.996
3150921YORKTN3
50/50
212.818212.818
925865AC1-065 E
Adder
24.48470588235294420.812
926662AC1-147 E
50/50
2.2972.297
926755AC1-161 E
50/50
24.37824.378
927226AC1-216 E
Adder
10.5317647058823528.952
934392AD1-063 E
Adder
1.61529411764705881.373
935112AD1-144 E
50/50
1.5821.582
936591AD2-074 C
Adder
7.8788235294117656.697
936592AD2-074 E
Adder
12.85529411764705910.927
942341AE2-247 C
Adder
2.2741176470588241.933
942342AE2-247 E
Adder
3.142.669
943461AF1-017 C
Adder
2.05764705882352941.749
943462AF1-017 E
Adder
3.35647058823529452.853
943612AF1-032 E
50/50
1.5651.565
943741AF1-042 C
Adder
4.122352941176473.504
943742AF1-042 E
Adder
6.7258823529411765.717
961951AG1-038 C
Adder
4.5564705882352943.873
961952AG1-038 E
Adder
6.2929411764705885.349
966661AG1-536 C
Adder
7.4564705882352956.338
966662AG1-536 E
Adder
10.0188235294117658.516
3150981CHESPKA
50/50
0.7560.756
3150991CHESPKB
50/50
1.2531.253
3151081ELIZAR1
50/50
5.5655.565
3151091ELIZAR2
50/50
5.4685.468
3151101ELIZAR3
50/50
5.6365.636
3151161SURRY 1
50/50
37.92137.921
3152331SURRY 2
50/50
50.93450.934
3156056W1-029WIND
50/50
1.2961.296
3156116Z1-036WIND
50/50
1.0631.063
316076AC2-137 E
Adder
1.64117647058823551.395
316078AC2-138 E
Adder
1.26470588235294111.075
316157AD2-030 E
Adder
1.7917647058823531.523
913392Y1-086 E
50/50
3.7343.734
916192Z1-068 E
50/50
3.2743.274
923832AB2-022 E
50/50
2.1082.108
923842AB2-024 E
Adder
2.7035294117647062.298
923852AB2-025 E
Adder
1.42470588235294131.211
939312AE1-162 E
50/50
2.3092.309
957492AF2-043 E
50/50
2.4072.407
957601AF2-054 C
Adder
3.1929411764705882.714
957602AF2-054 E
Adder
2.12823529411764721.809
962861AG1-135 C
Adder
8.4564705882352957.188
962862AG1-135 E
Adder
5.63764705882352954.792
962962AG1-145 E
50/50
2.4882.488
963611AG1-210 C
Adder
0.90352941176470590.768
963612AG1-210 E
Adder
1.35529411764705881.152
964211AG1-282 C
Adder
2.76588235294117672.351
964212AG1-282 E
Adder
1.84352941176470591.567
901082W1-029 E
50/50
53.16253.162
917122Z2-027 E
50/50
2.2672.267
925332AB2-190 E
Adder
10.335294117647068.785
925522AC1-027 E
50/50
2.1192.119
957831AF2-077 C
50/50
0.5460.546
957832AF2-077 E
50/50
2.3562.356
957871AF2-081 C
50/50
17.30217.302
957872AF2-081 E
50/50
7.4157.415
958161AF2-110 C
50/50
2.2342.234
958162AF2-110 E
50/50
3.5543.554
3138116ELKO L286
Adder
1.71058823529411771.454
3141813NORNECK
Adder
1.20352941176470571.023
926071AC1-086 C
Adder
26.78823529411764822.77
926072AC1-086 E
Adder
12.19176470588235310.363
933291AC2-141 C
50/50
57.10857.108
933292AC2-141 E
50/50
24.37824.378
939411AE1-173 C
50/50
137.269137.269
939412AE1-173 E
50/50
91.51291.512
934012AD1-025 E
Adder
13.63529411764705811.59
916191Z1-068 C
50/50
0.0760.076
933981AD1-022 C
Adder
13.0952941176470611.131
933982AD1-022 E
Adder
7.1294117647058826.06
962572AG1-106 E
Adder
1.5164705882352941.289
962571AG1-106 C
Adder
3.4647058823529412.945
3130536PAPERMILL
Adder
9.9929411764705888.494
3145946PLYMOUTH TP
Adder
0.491764705882352940.418
3146326AYDLETT TAP
50/50
2.3362.336
316036AC1-147 C
50/50
0.6390.639
316072AD1-144 C
50/50
0.4730.473
316159AE1-175 C
50/50
0.6760.676
316160AE1-175 E
50/50
2.0532.053
316169AC1-164 GEN
50/50
61.5761.57
316185AD1-033 C
50/50
2.1522.152
316236AE1-162 C
50/50
0.5660.566
316246AF1-032 C
50/50
0.4820.482
316294AC1-161 C
50/50
9.3329.332
316305AF2-043 C
50/50
0.590.59
316316AC1-027 C
50/50
0.550.55
316320Y1-086 C
50/50
0.3740.374
316321Z2-027 C
50/50
0.6140.614
316382AG1-145 C
50/50
0.610.61
917332KELFORD E
Adder
2.25294117647058821.915
924516AB2-100 E1
Adder
3.61411764705882373.072
924517AB2-100 E2
Adder
3.61411764705882373.072
926206AC1-098 E
Adder
4.72941176470588154.02
926214AC1-099 E
Adder
1.56235294117647071.328
926785AC1-164_E
50/50
27.66227.662
934065AD1-033 E
50/50
8.788.78
937226AE2-253 E
50/50
10.1510.15
939612AE1-191 E
Adder
8.4670588235294127.197
939246AE1-155 E
Adder
12.06941176470588310.259
918512AA1-065 E OP
Adder
7.9635294117647066.769
316017AA1-139 ULT1
50/50
1.8731.873
316018AA1-139 ULT2
50/50
1.8731.873
919153AA1-139 E2
50/50
7.0757.075
919152AA1-139 E1
50/50
7.0757.075
920692AA2-178 E
Adder
6.4070588235294125.446
923994AB2-040_E
Adder
7.7152941176470586.558
924814AB2-134 E
Adder
17.2517647058823514.664
316084AB2-161 E
Adder
7.497647058823536.373
925122AB2-169 E
Adder
8.1847058823529426.957
316088AB2-174 E
Adder
8.1305882352941186.911
316375AC2-012 C
50/50
2.3432.343
932046AC2-012 E
50/50
22.72422.724
316311AC2-079 C
Adder
8.827.497
932596AC2-079 E
Adder
14.39058823529411812.232
934146AD1-041 E
Adder
5.2917647058823534.498
934576AD1-082 E
Adder
5.9741176470588245.078
316349AD2-085 C
Adder
5.2458823529411764.459
936666AD2-085 E
Adder
8.5588235294117647.275
316388AE2-253 GEN
50/50
3.4133.413
961611AG1-000B C
Adder
23.74470588235294220.183
941591AE2-156 C
50/50
31.07431.074
944581AF1-123 C
50/50
79.48679.486
944582AF1-123 E
50/50
182.015182.015
944591AF1-124 C
50/50
79.76979.769
944592AF1-124 E
50/50
182.674182.674
944601AF1-125 C
50/50
78.26278.262
944602AF1-125 E
50/50
179.158179.158
944631AF1-128 C
Adder
26.26705882352941422.327
958261AF2-120 C
Adder
8.6682352941176477.368
958262AF2-120 E
Adder
5.7788235294117654.912
3137643SOCKMAN
Adder
0.90352941176470590.768
932632AC2-084 E
Adder
4.183.553
934501AD1-074 C
Adder
51.01411764705882543.362
934502AD1-074 E
Adder
25.96941176470588522.074
934511AD1-075 C
Adder
12.75411764705882310.841
934512AD1-075 E
Adder
6.4917647058823525.518
935161AD1-151 C
Adder
21.28588235294117618.093
935162AD1-151 E
Adder
14.19058823529411712.062
938531AE1-072 C
50/50
30.31830.318
938532AE1-072 E
50/50
15.80515.805
939191AE1-149 C
Adder
13.30705882352941111.311
939192AE1-149 E
Adder
8.8705882352941187.54
939602AE1-190 E
Adder
2.1164705882352941.799
940481AE2-033 C
Adder
19.89882352941176816.914
940482AE2-033 E
Adder
13.4152941176470611.403
940541AE2-040 C
Adder
3.5223529411764712.994
940551AE2-041 C
Adder
10.7682352941176489.153
940641AE2-051 C
50/50
24.9624.96
940642AE2-051 E
50/50
16.6416.64
941101AE2-104 C
50/50
5.4755.475
941102AE2-104 E
50/50
8.7058.705
943471AF1-018 C
Adder
10.7682352941176489.153
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.8765.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.55415.554
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.85316.853
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
96.69696.696
G-007PJM->LTFIMP_G-007
CMTX_NF
3.3653.365
NYPJM->LTFIMP_NY
CLTF
1.6271.627
LGEELTFEXP_LGEE->PJM
CLTF
0.6520.652
WECLTFEXP_WEC->PJM
CLTF
0.3380.338
CPLELTFEXP_CPLE->PJM
CLTF
12.33712.337
TVALTFEXP_TVA->PJM
CLTF
4.9324.932
MECLTFEXP_MEC->PJM
CLTF
2.4842.484
LAGNLTFEXP_LAGN->PJM
CLTF
6.3726.372
SIGELTFEXP_SIGE->PJM
CLTF
0.1430.143
O66PJM->LTFIMP_O-066
CMTX_NF
21.46821.468

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4713.59
MW Contribution:19.2
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:137.17 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5582.91
MW Contribution:20.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.76117647058823530.647
961942AG1-037 E
Adder
0.50705882352941180.431
963041AG1-153 C
Adder
7.67882352941176556.527
963042AG1-153 E
Adder
11.517647058823539.79
966621AG1-532 C
Adder
2.00705882352941161.706
966622AG1-532 E
Adder
1.33882352941176451.138
3145413WATKINS
Adder
1.08705882352941190.924
3145723EMPORIA
Adder
0.61764705882352940.525
918492AA1-063AE OP
Adder
6.0129411764705885.111
920042AA2-088 E OP
Adder
16.25647058823529513.818
934521AD1-076 C
Adder
19.0647058823529416.205
934522AD1-076 E
Adder
9.7164705882352948.259
943172AE2-346 E
Adder
0.91294117647058830.776
944011AF1-069 C
Adder
18.02352941176470615.32
944012AF1-069 E
Adder
7.0023529411764715.952
960081AF2-299 C
Adder
2.6764705882352942.275
960082AF2-299 E
Adder
1.78470588235294111.517
316141AB2-099 E
Adder
0.380.323
900672V4-068 E
Adder
0.54235294117647060.461
923573AB1-173 E OP
Adder
4.7082352941176474.002
940492AE2-034 E
Adder
4.8823529411764714.15
941031AE2-094 C
Adder
55.1635294117647146.889
941032AE2-094 E
Adder
24.70588235294117821
946281AF1-292 C
Adder
2.2152941176470591.883
946282AF1-292 E
Adder
1.47764705882352951.256
3145393UNCAMP
Adder
9.664705882352948.215
916042Z1-036 E
Adder
46.2035294117647139.273
938771AE1-103 C
Adder
4.6882352941176473.985
938772AE1-103 E
Adder
6.4741176470588245.503
3143316POE
Adder
2.15411764705882371.831
3144216WINCHST
50/50
0.2290.229
3145256KINGFORK
Adder
1.70470588235294131.449
3145506HICKORY
Adder
3.66705882352941173.117
3150601CHESTF5
50/50
107.532107.532
3150611CHESTG7
50/50
6.5626.562
3150621CHESTS7
50/50
3.0123.012
3150631CHESTG8
50/50
6.4576.457
3150641CHESTS8
50/50
3.3243.324
3150651CHESTF6
Adder
30.4035294117647125.843
3150681DARBY 2
50/50
4.2574.257
3150691DARBY 3
50/50
4.2724.272
3150701DARBY 4
50/50
4.2774.277
3150731STONECA
Adder
11.5258823529411789.797
3150831SPRUNCA
Adder
14.5823529411764712.395
3150841SPRUNCB
Adder
14.5823529411764712.395
3150921YORKTN3
50/50
208.205208.205
925865AC1-065 E
Adder
27.3976470588235323.288
926412AC1-112 E
50/50
1.9031.903
926662AC1-147 E
Adder
2.2364705882352941.901
926755AC1-161 E
50/50
22.27722.277
927226AC1-216 E
Adder
12.9976470588235311.048
934392AD1-063 E
Adder
1.77411764705882361.508
935112AD1-144 E
Adder
1.58235294117647051.345
936591AD2-074 C
Adder
8.5505882352941187.268
936592AD2-074 E
Adder
13.95176470588235211.859
942341AE2-247 C
Adder
2.4552941176470592.087
942342AE2-247 E
Adder
3.39176470588235322.883
943461AF1-017 C
Adder
2.2223529411764711.889
943462AF1-017 E
Adder
3.62470588235294143.081
943612AF1-032 E
Adder
1.54117647058823541.31
943741AF1-042 C
Adder
4.4741176470588243.803
943742AF1-042 E
Adder
7.3000000000000016.205
961951AG1-038 C
Adder
4.9458823529411764.204
961952AG1-038 E
Adder
6.8294117647058825.805
966661AG1-536 C
Adder
8.0929411764705876.879
966662AG1-536 E
Adder
10.8741176470588249.243
966871AG1-558 C
Adder
3.73647058823529443.176
966872AG1-558 E
Adder
1.88235294117647081.6
3152331SURRY 2
50/50
44.51344.513
316075AC2-137 C
50/50
0.6540.654
316076AC2-137 E
50/50
2.32.3
316078AC2-138 E
Adder
1.37294117647058831.167
316157AD2-030 E
Adder
1.94470588235294131.653
913392Y1-086 E
Adder
3.6470588235294123.1
916192Z1-068 E
Adder
3.16941176470588242.694
923832AB2-022 E
Adder
2.0588235294117651.75
923842AB2-024 E
Adder
2.99058823529411732.542
923852AB2-025 E
Adder
1.7117647058823531.455
930122AB1-027 E
50/50
2.342.34
938552AE1-074 E
Adder
1.90000000000000011.615
939312AE1-162 E
Adder
2.4211764705882352.058
946262AF1-291 E
Adder
2.34117647058823541.99
957492AF2-043 E
Adder
2.37058823529411772.015
957601AF2-054 C
Adder
3.4647058823529412.945
957602AF2-054 E
Adder
2.31058823529411761.964
962861AG1-135 C
Adder
9.177647058823537.801
962862AG1-135 E
Adder
6.1188235294117645.201
962962AG1-145 E
50/50
2.5352.535
963611AG1-210 C
Adder
0.980.833
963612AG1-210 E
Adder
1.47058823529411781.25
964211AG1-282 C
Adder
3.02000000000000052.567
964212AG1-282 E
Adder
2.01294117647058851.711
901082W1-029 E
Adder
52.4682352941176544.598
917122Z2-027 E
Adder
2.22117647058823531.888
925332AB2-190 E
Adder
13.54588235294117611.514
925522AC1-027 E
Adder
2.05294117647058851.745
942001AE2-212 C
Adder
3.4764705882352942.955
942002AE2-212 E
Adder
2.31764705882352961.97
957832AF2-077 E
Adder
2.41411764705882352.052
957871AF2-081 C
Adder
16.73529411764705814.225
957872AF2-081 E
Adder
7.1717647058823536.096
958161AF2-110 C
Adder
2.2623529411764711.923
958162AF2-110 E
Adder
3.5988235294117653.059
3138116ELKO L286
50/50
2.3992.399
3141813NORNECK
Adder
1.30588235294117671.11
926071AC1-086 C
Adder
8.492941176470597.219
933291AC2-141 C
50/50
52.18752.187
933292AC2-141 E
50/50
22.27722.277
939411AE1-173 C
Adder
137.65882352941176117.01
939412AE1-173 E
Adder
91.772941176470678.007
934012AD1-025 E
Adder
16.82705882352941314.303
927041AC1-191 C
Adder
15.00352941176470612.753
927042AC1-191 E
Adder
7.4741176470588236.353
933981AD1-022 C
Adder
13.55882352941176611.525
933982AD1-022 E
Adder
7.3811764705882366.274
3130536PAPERMILL
Adder
11.0400000000000019.384
3145946PLYMOUTH TP
Adder
0.50470588235294120.429
3146326AYDLETT TAP
Adder
2.26588235294117621.926
316004AC1-112 C
50/50
0.5560.556
316159AE1-175 C
50/50
0.6890.689
316160AE1-175 E
50/50
2.0922.092
316169AC1-164 GEN
50/50
71.02671.026
316233AE1-074 C
Adder
3.7705882352941183.205
316240AF1-291 C
Adder
3.5117647058823532.985
316294AC1-161 C
50/50
8.5288.528
316312AB1-027 C
50/50
0.8920.892
316382AG1-145 C
50/50
0.6220.622
917332KELFORD E
Adder
2.43058823529411772.066
924516AB2-100 E1
Adder
4.20352941176470553.573
924517AB2-100 E2
Adder
4.20352941176470553.573
926785AC1-164_E
50/50
31.9131.91
934065AD1-033 E
Adder
8.4505882352941187.183
937226AE2-253 E
Adder
9.88.33
939612AE1-191 E
Adder
9.3494117647058837.947
939246AE1-155 E
Adder
13.111.135
918512AA1-065 E OP
Adder
8.397647058823537.138
919153AA1-139 E2
Adder
6.8435294117647065.817
919152AA1-139 E1
Adder
6.8435294117647065.817
920692AA2-178 E
Adder
6.5094117647058835.533
923994AB2-040_E
Adder
8.8282352941176477.504
924814AB2-134 E
Adder
21.28941176470588218.096
316084AB2-161 E
Adder
9.0294117647058827.675
925122AB2-169 E
Adder
8.6200000000000017.327
316088AB2-174 E
Adder
9.3494117647058837.947
932046AC2-012 E
Adder
22.12352941176470718.805
316311AC2-079 C
Adder
9.4458823529411768.029
932596AC2-079 E
Adder
15.41176470588235313.1
934146AD1-041 E
Adder
5.8435294117647054.967
934576AD1-082 E
Adder
7.1941176470588246.115
316349AD2-085 C
Adder
5.6658823529411774.816
936666AD2-085 E
Adder
9.244705882352947.858
961611AG1-000B C
Adder
26.9129411764705922.876
941591AE2-156 C
Adder
30.2317647058823525.697
944581AF1-123 C
Adder
76.4247058823529464.961
944582AF1-123 E
Adder
175.0035294117647148.753
944591AF1-124 C
Adder
76.6964705882352965.192
944592AF1-124 E
Adder
175.63764705882355149.292
944601AF1-125 C
Adder
75.2470588235294163.96
944602AF1-125 E
Adder
172.25764705882355146.419
944631AF1-128 C
50/50
67.28467.284
958261AF2-120 C
Adder
9.4070588235294137.996
958262AF2-120 E
Adder
6.2717647058823545.331
934501AD1-074 C
Adder
52.4929411764705944.619
934502AD1-074 E
Adder
26.72117647058823722.713
934511AD1-075 C
Adder
13.12352941176470511.155
934512AD1-075 E
Adder
6.685.678
935161AD1-151 C
Adder
27.11411764705882623.047
935162AD1-151 E
Adder
18.0752941176470615.364
938531AE1-072 C
Adder
29.3776470588235324.971
938532AE1-072 E
Adder
15.31411764705882413.017
939191AE1-149 C
Adder
17.43176470588235514.817
939192AE1-149 E
Adder
11.6211764705882359.878
939602AE1-190 E
Adder
2.33764705882352961.987
940431AE2-027 C
Adder
21.05411764705882417.896
940432AE2-027 E
Adder
14.03647058823529311.931
940481AE2-033 C
Adder
23.8117647058823520.24
940482AE2-033 E
Adder
16.0529411764705913.645
940541AE2-040 C
Adder
4.2317647058823533.597
940551AE2-041 C
Adder
11.82823529411764710.054
940641AE2-051 C
Adder
25.38941176470588321.581
940642AE2-051 E
Adder
16.92588235294117614.387
941101AE2-104 C
Adder
5.5447058823529414.713
941102AE2-104 E
Adder
8.815294117647067.493
943471AF1-018 C
Adder
11.82823529411764710.054
944641AF1-129 C
Adder
166.98352941176472141.936
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
7.017.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.3345.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.55730.557
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
122.912122.912
G-007PJM->LTFIMP_G-007
CMTX_NF
6.8256.825
NYPJM->LTFIMP_NY
CLTF
3.1153.115
LGEELTFEXP_LGEE->PJM
CLTF
1.8191.819
WECLTFEXP_WEC->PJM
CLTF
0.9390.939
CPLELTFEXP_CPLE->PJM
CLTF
14.714.7
TVALTFEXP_TVA->PJM
CLTF
8.1358.135
MECLTFEXP_MEC->PJM
CLTF
5.5435.543
LAGNLTFEXP_LAGN->PJM
CLTF
10.28110.281
SIGELTFEXP_SIGE->PJM
CLTF
0.3490.349
O66PJM->LTFIMP_O-066
CMTX_NF
43.443.4

Details for 8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN N ANNA-KRAKEN_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN N ANNA-KRAKEN_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:107.4 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3458.65
MW Contribution:10.85
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.42235294117647060.359
961942AG1-037 E
Adder
0.28117647058823530.239
963041AG1-153 C
Adder
4.3411764705882353.69
963042AG1-153 E
Adder
6.5117647058823535.535
966621AG1-532 C
Adder
1.13529411764705880.965
966622AG1-532 E
Adder
0.75647058823529410.643
3145413WATKINS
Adder
0.59882352941176480.509
3145723EMPORIA
Adder
0.349411764705882370.297
918492AA1-063AE OP
Adder
3.35882352941176482.855
920042AA2-088 E OP
Adder
8.9988235294117667.649
934521AD1-076 C
Adder
10.4682352941176488.898
934522AD1-076 E
Adder
5.3364705882352944.536
943172AE2-346 E
Adder
0.50588235294117640.43
944011AF1-069 C
Adder
10.1705882352941178.645
944012AF1-069 E
Adder
3.95058823529411773.358
960081AF2-299 C
Adder
1.51411764705882361.287
960082AF2-299 E
Adder
1.00941176470588250.858
316141AB2-099 E
Adder
0.210588235294117630.179
900672V4-068 E
Adder
0.30.255
923573AB1-173 E OP
Adder
2.65529411764705922.257
940492AE2-034 E
Adder
2.6705882352941182.27
941031AE2-094 C
Adder
31.1258823529411826.457
941032AE2-094 E
Adder
13.94000000000000111.849
946281AF1-292 C
Adder
1.25294117647058821.065
946282AF1-292 E
Adder
0.83529411764705890.71
3145393UNCAMP
Adder
5.30941176470588254.513
916042Z1-036 E
Adder
25.1621.386
938771AE1-103 C
Adder
2.5717647058823532.186
938772AE1-103 E
Adder
3.55058823529411743.018
933502AC2-165 E
Adder
5.9823529411764715.085
3142296MT RD221
50/50
0.1210.121
3142366NRTHEST
50/50
0.1810.181
3143316POE
Adder
1.23411764705882351.049
3145256KINGFORK
Adder
0.92470588235294130.786
3145506HICKORY
Adder
1.97647058823529421.68
3150391LDYSMT3
50/50
4.7014.701
3150401LDYSMT4
50/50
4.7094.709
3150411LDYSMT5
50/50
4.7244.724
3150601CHESTF5
Adder
60.84352941176470651.717
3150651CHESTF6
Adder
17.66352941176470615.014
3150691DARBY 3
50/50
2.5052.505
3150701DARBY 4
50/50
2.5082.508
3150731STONECA
Adder
6.54705882352941255.565
3150831SPRUNCA
Adder
8.6470588235294117.35
3150841SPRUNCB
Adder
8.6470588235294117.35
3150921YORKTN3
Adder
111.7541176470588294.991
925865AC1-065 E
Adder
15.30588235294117713.01
926412AC1-112 E
50/50
1.1081.108
926662AC1-147 E
Adder
1.20705882352941171.026
926755AC1-161 E
Adder
11.85176470588235310.074
927226AC1-216 E
Adder
7.2470588235294126.16
934392AD1-063 E
Adder
0.98705882352941180.839
934782AD1-105 E
Adder
4.277647058823533.636
935112AD1-144 E
Adder
0.85882352941176470.73
936591AD2-074 C
Adder
4.9494117647058824.207
936592AD2-074 E
Adder
8.0764705882352946.865
942341AE2-247 C
Adder
1.3517647058823531.149
942342AE2-247 E
Adder
1.86705882352941191.587
943461AF1-017 C
Adder
1.2235294117647061.04
943462AF1-017 E
Adder
1.99647058823529421.697
943612AF1-032 E
Adder
0.83411764705882350.709
943741AF1-042 C
Adder
2.5905882352941182.202
943742AF1-042 E
Adder
4.2258823529411773.592
958502AF2-144 E
Adder
0.98588235294117640.838
961951AG1-038 C
Adder
2.86235294117647052.433
961952AG1-038 E
Adder
3.95294117647058843.36
966661AG1-536 C
Adder
4.742352941176474.031
966662AG1-536 E
Adder
6.3717647058823535.416
966871AG1-558 C
Adder
2.34588235294117631.994
966872AG1-558 E
Adder
1.18235294117647041.005
966881AG1-559 C
50/50
2.4312.431
966882AG1-559 E
50/50
1.2241.224
316076AC2-137 E
Adder
1.28941176470588251.096
316078AC2-138 E
Adder
0.81411764705882350.692
316157AD2-030 E
Adder
1.08588235294117650.923
913392Y1-086 E
Adder
1.97294117647058841.677
916192Z1-068 E
Adder
1.70941176470588241.453
923832AB2-022 E
Adder
1.11411764705882340.947
923842AB2-024 E
Adder
1.66000000000000011.411
923852AB2-025 E
Adder
0.97058823529411760.825
923862AB2-026 E
Adder
1.00352941176470580.853
930122AB1-027 E
50/50
1.3631.363
938552AE1-074 E
Adder
1.14117647058823520.97
938562AE1-075 E
Adder
0.85529411764705890.727
939312AE1-162 E
Adder
1.321.122
946262AF1-291 E
Adder
1.35764705882352941.154
957492AF2-043 E
Adder
1.28352941176470581.091
957601AF2-054 C
Adder
1.93529411764705881.645
957602AF2-054 E
Adder
1.29058823529411761.097
962861AG1-135 C
Adder
5.36235294117647054.558
962862AG1-135 E
Adder
3.5752941176470593.039
962962AG1-145 E
Adder
1.36470588235294121.16
963611AG1-210 C
Adder
0.58117647058823530.494
963612AG1-210 E
Adder
0.8717647058823530.741
964211AG1-282 C
Adder
1.77411764705882361.508
964212AG1-282 E
Adder
1.1835294117647061.006
901082W1-029 E
Adder
28.4624.191
917122Z2-027 E
Adder
1.20352941176470571.023
925332AB2-190 E
Adder
7.6082352941176476.467
925522AC1-027 E
Adder
1.10705882352941170.941
942001AE2-212 C
Adder
2.0082352941176471.707
942002AE2-212 E
Adder
1.33882352941176451.138
957832AF2-077 E
Adder
1.321.122
957871AF2-081 C
Adder
9.0294117647058827.675
957872AF2-081 E
Adder
3.86941176470588263.289
958161AF2-110 C
Adder
1.23176470588235291.047
958162AF2-110 E
Adder
1.961.666
3138116ELKO L286
Adder
1.34470588235294121.143
3141813NORNECK
Adder
0.77411764705882360.658
926071AC1-086 C
Adder
4.4847058823529413.812
933291AC2-141 C
Adder
27.76352941176470823.599
933292AC2-141 E
Adder
11.85176470588235310.074
939411AE1-173 C
Adder
76.0247058823529364.621
939412AE1-173 E
Adder
50.6835294117647143.081
934012AD1-025 E
Adder
9.3823529411764717.975
927041AC1-191 C
Adder
9.428.007
927042AC1-191 E
Adder
4.6929411764705893.989
933981AD1-022 C
Adder
7.457647058823536.339
933982AD1-022 E
Adder
4.06000000000000053.451
3130536PAPERMILL
Adder
6.1294117647058835.21
3145946PLYMOUTH TP
Adder
0.276470588235294130.235
3146326AYDLETT TAP
Adder
1.2235294117647061.04
316004AC1-112 C
50/50
0.3240.324
316160AE1-175 E
Adder
1.12588235294117660.957
316169AC1-164 GEN
Adder
38.76588235294117632.951
316233AE1-074 C
Adder
2.2647058823529411.925
316240AF1-291 C
Adder
2.03764705882352941.732
316312AB1-027 C
50/50
0.520.52
316336AC2-165 C
Adder
7.9482352941176486.756
924516AB2-100 E1
Adder
2.37411764705882342.018
924517AB2-100 E2
Adder
2.37411764705882342.018
926785AC1-164_E
Adder
17.41647058823529514.804
934065AD1-033 E
Adder
4.5529411764705883.87
937226AE2-253 E
Adder
5.2858823529411774.493
939612AE1-191 E
Adder
5.2223529411764714.439
3150371LDYSMT1
50/50
4.5224.522
3150381LDYSMT2
50/50
4.584.58
315051AA1-145 CT1
50/50
5.025.02
315052AA1-145 CT2
50/50
5.0185.018
939246AE1-155 E
Adder
7.6764705882352946.525
918512AA1-065 E OP
Adder
4.6411764705882353.945
919153AA1-139 E2
Adder
3.6929411764705883.139
919152AA1-139 E1
Adder
3.6929411764705883.139
920692AA2-178 E
Adder
3.56117647058823563.027
923994AB2-040_E
Adder
4.9776470588235294.231
924814AB2-134 E
Adder
11.87058823529411810.09
316084AB2-161 E
Adder
5.0552941176470584.297
316088AB2-174 E
Adder
5.2764705882352954.485
932046AC2-012 E
Adder
11.9410.149
316311AC2-079 C
Adder
5.1941176470588244.415
932596AC2-079 E
Adder
8.4741176470588247.203
934146AD1-041 E
Adder
3.2635294117647062.774
934576AD1-082 E
Adder
4.0270588235294123.423
316349AD2-085 C
Adder
3.122.652
936666AD2-085 E
Adder
5.0894117647058824.326
961611AG1-000B C
Adder
14.83882352941176412.613
941591AE2-156 C
Adder
16.31294117647058813.866
944581AF1-123 C
Adder
41.16941176470588534.994
944582AF1-123 E
Adder
94.272941176470680.132
944591AF1-124 C
Adder
41.3152941176470635.118
944592AF1-124 E
Adder
94.6141176470588280.422
944601AF1-125 C
Adder
40.53529411764705534.455
944602AF1-125 E
Adder
92.7929411764705978.874
944631AF1-128 C
Adder
38.0705882352941232.36
958261AF2-120 C
Adder
5.5129411764705884.686
958262AF2-120 E
Adder
3.67529411764705933.124
934501AD1-074 C
Adder
28.82588235294117524.502
934502AD1-074 E
Adder
14.67411764705882512.473
934511AD1-075 C
Adder
7.2058823529411776.125
934512AD1-075 E
Adder
3.6682352941176473.118
935161AD1-151 C
Adder
15.17647058823529512.9
935162AD1-151 E
Adder
10.1176470588235298.6
938531AE1-072 C
Adder
15.85882352941176513.48
938532AE1-072 E
Adder
8.2670588235294127.027
939191AE1-149 C
Adder
9.8705882352941188.39
939192AE1-149 E
Adder
6.585.593
939261AE1-157 C
50/50
14.14114.141
939262AE1-157 E
50/50
7.677.67
939602AE1-190 E
Adder
1.30588235294117671.11
940431AE2-027 C
Adder
12.14705882352941110.325
940432AE2-027 E
Adder
8.097647058823536.883
940481AE2-033 C
Adder
13.50235294117647211.477
940482AE2-033 E
Adder
9.1023529411764727.737
940541AE2-040 C
Adder
2.40117647058823552.041
940551AE2-041 C
Adder
6.585.593
940641AE2-051 C
Adder
14.1412.019
940642AE2-051 E
Adder
9.4270588235294128.013
941101AE2-104 C
Adder
3.02000000000000052.567
941102AE2-104 E
Adder
4.8011764705882364.081
943471AF1-018 C
Adder
6.585.593
944641AF1-129 C
Adder
97.016470588235382.464
3150431FOUR RIVERA
50/50
3.1513.151
3150441FOUR RIVERB
50/50
3.1513.151
3150451FOUR RIVERC
50/50
3.853.85
3150461FOUR RIVERD
50/50
3.1063.106
3150471FOUR RIVERE
50/50
3.1063.106
3150481FOUR RIVERF
50/50
3.7933.793
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.0244.024
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.37329.373
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.83518.835
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
71.47471.474
G-007PJM->LTFIMP_G-007
CMTX_NF
5.3775.377
NYPJM->LTFIMP_NY
CLTF
2.4112.411
LGEELTFEXP_LGEE->PJM
CLTF
1.1741.174
WECLTFEXP_WEC->PJM
CLTF
0.6070.607
CPLELTFEXP_CPLE->PJM
CLTF
8.4398.439
TVALTFEXP_TVA->PJM
CLTF
4.9434.943
MECLTFEXP_MEC->PJM
CLTF
3.5063.506
LAGNLTFEXP_LAGN->PJM
CLTF
6.236.23
SIGELTFEXP_SIGE->PJM
CLTF
0.2230.223
O66PJM->LTFIMP_O-066
CMTX_NF
34.15334.153

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:126.88 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1342.55
MW Contribution:9.18
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:127.67 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1350.99
MW Contribution:9.02
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.410588235294117640.349
961672AG1-007 E
Adder
0.232941176470588260.198
961941AG1-037 C
Adder
0.212941176470588240.181
961942AG1-037 E
Adder
0.14235294117647060.121
963041AG1-153 C
50/50
3.6733.673
963042AG1-153 E
50/50
5.5095.509
964791AG1-342 C
Adder
1.48470588235294131.262
964792AG1-342 E
Adder
0.99058823529411770.842
966621AG1-532 C
Adder
0.60117647058823530.511
966622AG1-532 E
Adder
0.40.34
3145413WATKINS
Adder
0.279999999999999970.238
3145723EMPORIA
Adder
0.18470588235294120.157
3151311EDGECMA
Adder
6.8129411764705895.791
918492AA1-063AE OP
Adder
1.72705882352941181.468
918532AA1-067 E
Adder
0.30941176470588240.263
919692AA2-053 E OP
Adder
1.80705882352941181.536
920042AA2-088 E OP
Adder
4.3847058823529413.727
925785AC1-054 E
Adder
1.47764705882352951.256
926274AC1-105 E
Adder
1.13764705882352950.967
927146AC1-208 E
Adder
1.72941176470588241.47
934521AD1-076 C
Adder
5.1635294117647064.389
934522AD1-076 E
Adder
2.6317647058823532.237
943172AE2-346 E
Adder
0.255294117647058840.217
943902AF1-058 E
Adder
0.55294117647058830.47
944011AF1-069 C
50/50
8.8768.876
944012AF1-069 E
50/50
3.4483.448
959311AF2-222 C
Adder
5.57411764705882454.738
959312AF2-222 E
Adder
3.73411764705882383.174
960081AF2-299 C
Adder
0.80117647058823540.681
960082AF2-299 E
Adder
0.53411764705882360.454
316141AB2-099 E
Adder
0.107058823529411760.091
900672V4-068 E
Adder
0.149411764705882360.127
917342Z2-044 E
Adder
0.26117647058823530.222
922923AB1-081 E OP
Adder
1.63529411764705881.39
923263AB1-132 E OP
Adder
2.6305882352941182.236
923573AB1-173 E OP
Adder
1.40588235294117661.195
924162AB2-060 E OP
Adder
1.71764705882352931.46
924302AB2-077 E O1
Adder
0.54823529411764720.466
924312AB2-078 E O1
Adder
0.54823529411764720.466
924322AB2-079 E O1
Adder
0.54823529411764720.466
925612AC1-036 E
Adder
0.30.255
940492AE2-034 E
Adder
1.2952941176470591.101
941011AE2-092 C
Adder
-4.452941176470588-3.785
941031AE2-094 C
50/50
27.16527.165
941032AE2-094 E
50/50
12.16712.167
946281AF1-292 C
Adder
0.66352941176470580.564
946282AF1-292 E
Adder
0.44235294117647060.376
957481AF2-042 C
Adder
28.3424.089
957482AF2-042 E
Adder
18.89411764705882416.06
957861AF2-080 C
Adder
3.3247058823529412.826
957862AF2-080 E
Adder
1.47411764705882351.253
3145393UNCAMP
Adder
2.44352941176470572.077
916042Z1-036 E
Adder
11.93411764705882510.144
938771AE1-103 C
Adder
1.16941176470588240.994
938772AE1-103 E
Adder
1.61529411764705881.373
3145256KINGFORK
Adder
0.367058823529411770.312
3145506HICKORY
Adder
0.91764705882352950.78
926662AC1-147 E
Adder
0.53176470588235290.452
926755AC1-161 E
Adder
5.7376470588235294.877
935112AD1-144 E
Adder
0.339999999999999970.289
942341AE2-247 C
Adder
0.50235294117647060.427
942342AE2-247 E
Adder
0.69411764705882350.59
943461AF1-017 C
Adder
0.454117647058823570.386
943462AF1-017 E
Adder
0.74117647058823530.63
943612AF1-032 E
Adder
0.374117647058823550.318
3151021BRUNSWICKG1
50/50
5.4215.421
3151031BRUNSWICKG2
50/50
5.4215.421
3151041BRUNSWICKG3
50/50
5.4215.421
3151051BRUNSWICKS1
50/50
11.26311.263
3152411Z1-086 GT1
50/50
7.0067.006
3152421Z1-086 GT2
50/50
7.0037.003
3152431Z1-086 GT3
50/50
7.0037.003
3152441Z1-086 ST
50/50
12.19612.196
913392Y1-086 E
Adder
0.91764705882352950.78
916192Z1-068 E
Adder
0.77294117647058820.657
923832AB2-022 E
Adder
0.51764705882352950.44
923852AB2-025 E
Adder
0.50705882352941180.431
939312AE1-162 E
Adder
0.41294117647058820.351
957492AF2-043 E
Adder
0.57529411764705880.489
901082W1-029 E
Adder
13.19764705882352911.218
917122Z2-027 E
Adder
0.55999999999999990.476
925522AC1-027 E
Adder
0.50.425
957871AF2-081 C
Adder
4.1964705882352953.567
957872AF2-081 E
Adder
1.79882352941176471.529
958161AF2-110 C
Adder
0.53058823529411770.451
958162AF2-110 E
Adder
0.84352941176470590.717
3147223TWITTYS
Adder
0.332941176470588240.283
917512Z2-088 E OP1
Adder
2.1352941176470591.815
926071AC1-086 C
Adder
9.037647058823537.682
926072AC1-086 E
Adder
4.11294117647058853.496
927021AC1-189 C
Adder
3.66117647058823573.112
927022AC1-189 E
Adder
1.8235294117647061.55
936261AD2-033 C
Adder
4.2364705882352943.601
936262AD2-033 E
Adder
2.8247058823529412.401
933291AC2-141 C
Adder
13.44235294117647211.426
933292AC2-141 E
Adder
5.7376470588235294.877
934621AD1-088 C
Adder
4.3611764705882353.707
934622AD1-088 E
Adder
2.11.785
939411AE1-173 C
50/50
55.12655.126
939412AE1-173 E
50/50
36.75136.751
933981AD1-022 C
Adder
3.73.145
933982AD1-022 E
Adder
2.01411764705882361.712
962572AG1-106 E
Adder
0.51176470588235290.435
962571AG1-106 C
Adder
1.16941176470588240.994
3145946PLYMOUTH TP
Adder
0.136470588235294120.116
3146326AYDLETT TAP
Adder
0.56823529411764710.483
316263AC1-034 C
Adder
2.91411764705882352.477
316274AC1-208 C
Adder
3.8952941176470593.311
316336AC2-165 C
Adder
-10.758823529411764-9.145
917332KELFORD E
Adder
0.70117647058823530.596
924516AB2-100 E1
Adder
1.25176470588235311.064
924517AB2-100 E2
Adder
1.25176470588235311.064
925595AC1-034 E
Adder
2.19764705882352951.868
926206AC1-098 E
Adder
1.57411764705882361.338
926214AC1-099 E
Adder
0.520.442
927255AC1-221 E
Adder
1.65176470588235281.404
927264AC1-222 E
Adder
1.66470588235294131.415
932763AC2-100 E
Adder
1.12117647058823520.953
934065AD1-033 E
Adder
2.10705882352941171.791
937226AE2-253 E
Adder
2.4552941176470592.087
918512AA1-065 E OP
Adder
2.34000000000000031.989
919153AA1-139 E2
Adder
1.71529411764705891.458
919152AA1-139 E1
Adder
1.71529411764705891.458
919710AA2-057 E
Adder
1.72588235294117661.467
920692AA2-178 E
Adder
1.72705882352941181.468
923994AB2-040_E
Adder
2.63647058823529432.241
924022AB2-043 E O1
Adder
2.11764705882352941.8
924152AB2-059 E OP
Adder
2.31764705882352961.97
925122AB2-169 E
Adder
2.4564705882352942.088
316088AB2-174 E
Adder
2.7941176470588242.375
932046AC2-012 E
Adder
5.2588235294117654.47
316311AC2-079 C
Adder
1.9682352941176471.673
932596AC2-079 E
Adder
3.2117647058823532.73
316349AD2-085 C
Adder
1.15882352941176480.985
936666AD2-085 E
Adder
1.89058823529411771.607
941591AE2-156 C
Adder
7.202352941176476.122
944581AF1-123 C
Adder
19.11999999999999716.252
944582AF1-123 E
Adder
43.7823529411764837.215
944591AF1-124 C
Adder
19.18823529411764616.31
944592AF1-124 E
Adder
43.9411764705882437.35
944601AF1-125 C
Adder
18.82588235294117516.002
944602AF1-125 E
Adder
43.0952941176470636.631
962561AG1-105 C
Adder
3.70941176470588243.153
962562AG1-105 E
Adder
2.4729411764705882.102
964241AG1-285 C
Adder
5.3647058823529414.56
964242AG1-285 E
Adder
3.57647058823529433.04
3137643SOCKMAN
Adder
0.30470588235294120.259
932632AC2-084 E
Adder
1.3917647058823531.183
934321AD1-056 C
Adder
2.72588235294117662.317
934322AD1-056 E
Adder
1.47882352941176461.257
934331AD1-057 C
Adder
1.52117647058823541.293
934332AD1-057 E
Adder
0.7917647058823530.673
934501AD1-074 C
Adder
14.2176470588235312.085
934502AD1-074 E
Adder
7.237647058823536.152
934511AD1-075 C
Adder
3.55411764705882363.021
934512AD1-075 E
Adder
1.80941176470588251.538
934612AD1-087 E
Adder
1.79882352941176471.529
935172AD1-152 E
Adder
2.6258823529411772.232
936161AD2-022 C
Adder
3.0882352941176472.625
936162AD2-022 E
Adder
1.85294117647058831.575
936171AD2-023 C
Adder
1.80117647058823521.531
936172AD2-023 E
Adder
0.97764705882352940.831
937482AD2-202 E
Adder
0.52588235294117650.447
938531AE1-072 C
Adder
7.3705882352941176.265
938532AE1-072 E
Adder
3.84235294117647053.266
938821AE1-108 C
Adder
-4.716470588235294-4.009
940481AE2-033 C
Adder
7.0611764705882366.002
940482AE2-033 E
Adder
4.7611764705882354.047
940541AE2-040 C
Adder
1.25411764705882361.066
940641AE2-051 C
50/50
11.53811.538
940642AE2-051 E
50/50
7.6927.692
941101AE2-104 C
Adder
1.31.105
941102AE2-104 E
Adder
2.06588235294117651.756
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.5712.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.53211.532
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.0379.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.69643.696
G-007PJM->LTFIMP_G-007
CMTX_NF
1.0921.092
NYPJM->LTFIMP_NY
CLTF
0.5140.514
LGEELTFEXP_LGEE->PJM
CLTF
0.4480.448
WECLTFEXP_WEC->PJM
CLTF
0.2390.239
CPLELTFEXP_CPLE->PJM
CLTF
5.3965.396
TVALTFEXP_TVA->PJM
CLTF
2.4942.494
MECLTFEXP_MEC->PJM
CLTF
1.5141.514
LAGNLTFEXP_LAGN->PJM
CLTF
3.2073.207
SIGELTFEXP_SIGE->PJM
CLTF
0.0910.091
O66PJM->LTFIMP_O-066
CMTX_NF
6.9576.957

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.69 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4423.72
MW Contribution:43.41
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:114.82 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4673.36
MW Contribution:43.12
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
3.08941176470588232.626
961792AG1-021 E
Adder
2.6317647058823532.237
963041AG1-153 C
50/50
17.36617.366
963042AG1-153 E
50/50
26.04926.049
964791AG1-342 C
50/50
7.2097.209
964792AG1-342 E
50/50
4.8064.806
3138533PONTONDP
Adder
1.14470588235294120.973
3147133PAMPLIN
50/50
1.8091.809
3151531CLOVER1
50/50
32.82932.829
3151541CLOVER2
50/50
32.52432.524
3151581KERR 1
50/50
0.7110.711
3151591KERR 2
50/50
1.991.99
3151601KERR 3
50/50
1.991.99
3151611KERR 4
50/50
1.991.99
3151621KERR 5
50/50
1.991.99
925785AC1-054 E
Adder
3.75647058823529443.193
926274AC1-105 E
50/50
5.5465.546
942751AE2-291 C
Adder
13.03294117647058811.078
942752AE2-291 E
Adder
8.6882352941176467.385
943902AF1-058 E
50/50
2.7082.708
944011AF1-069 C
50/50
39.18539.185
944012AF1-069 E
50/50
15.22215.222
959311AF2-222 C
50/50
34.76234.762
959312AF2-222 E
50/50
23.29123.291
24401205PINNACLE
Adder
1.62588235294117631.382
3151631KERR 6
50/50
1.991.99
3151641KERR 7
50/50
1.991.99
3152661PLYWOOD A
50/50
2.4812.481
316118AC1-105 C
50/50
1.8951.895
316131AB2-060 C
50/50
2.8942.894
924162AB2-060 E OP
50/50
8.3338.333
924302AB2-077 E O1
50/50
2.6052.605
924312AB2-078 E O1
50/50
2.6052.605
924322AB2-079 E O1
50/50
2.6052.605
925612AC1-036 E
50/50
1.8171.817
941031AE2-094 C
50/50
119.928119.928
941032AE2-094 E
50/50
53.71353.713
946301AF1-294 C
Adder
6.3505882352941185.398
946302AF1-294 E
Adder
5.377647058823534.571
957481AF2-042 C
50/50
147.496147.496
957482AF2-042 E
50/50
98.33198.331
958211AF2-115 C
Adder
3.86117647058823543.282
958212AF2-115 E
Adder
3.2894117647058822.796
924032AB2-045 E
Adder
1.26941176470588221.079
3151021BRUNSWICKG1
50/50
25.63425.634
3151031BRUNSWICKG2
50/50
25.63425.634
3151041BRUNSWICKG3
50/50
25.63425.634
3151051BRUNSWICKS1
50/50
53.25453.254
3152411Z1-086 GT1
50/50
32.42432.424
3152421Z1-086 GT2
50/50
32.41332.413
3152431Z1-086 GT3
50/50
32.41332.413
3152441Z1-086 ST
50/50
56.44456.444
957601AF2-054 C
Adder
-1.72-1.462
942001AE2-212 C
Adder
-1.9541176470588235-1.661
3147223TWITTYS
50/50
2.0152.015
936261AD2-033 C
50/50
24.11624.116
936262AD2-033 E
50/50
16.07816.078
933291AC2-141 C
Adder
-31.96117647058824-27.167
934621AD1-088 C
50/50
23.87723.877
934622AD1-088 E
50/50
11.49611.496
316003AC1-222 C
50/50
2.0082.008
316034AC1-036 C
50/50
0.4960.496
316222AC1-221 C
50/50
2.9122.912
316237AB2-079 C O1
50/50
0.6390.639
316238AB2-078 C O1
50/50
0.6390.639
316239AB2-077 C O1
50/50
0.6390.639
316240AF1-291 C
Adder
-1.863529411764706-1.584
316248AF1-058 C
50/50
0.6640.664
316283AC2-100 C
50/50
2.3312.331
927255AC1-221 E
50/50
7.6147.614
927264AC1-222 E
50/50
8.2018.201
932763AC2-100 E
50/50
5.1295.129
313527AB2-043 C
50/50
1.011.01
924022AB2-043 E O1
50/50
10.1410.14
925997AC1-075 E
Adder
5.1705882352941174.395
926024AC1-080 E
Adder
1.71529411764705891.458
962561AG1-105 C
50/50
17.96517.965
962562AG1-105 E
50/50
11.97711.977
964241AG1-285 C
50/50
28.57228.572
964242AG1-285 E
50/50
19.04819.048
934611AD1-087 C
50/50
3.233.23
934612AD1-087 E
50/50
9.3199.319
935171AD1-152 C
50/50
3.2363.236
935172AD1-152 E
50/50
13.31413.314
936161AD2-022 C
Adder
12.41176470588235310.55
936162AD2-022 E
Adder
7.4470588235294126.33
936171AD2-023 C
Adder
7.246.154
936172AD2-023 E
Adder
3.9305882352941183.341
937481AD2-202 C
50/50
0.9370.937
937482AD2-202 E
50/50
2.7272.727
938531AE1-072 C
Adder
-16.06705882352941-13.657
940641AE2-051 C
Adder
-21.288235294117648-18.095
942461AE2-259 C
Adder
16.0152941176470613.613
942462AE2-259 E
Adder
10.6764705882352939.075
944641AF1-129 C
Adder
-87.13882352941177-74.068
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.4399.439
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.04159.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.12440.124
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
169.426169.426
G-007PJM->LTFIMP_G-007
CMTX_NF
4.1284.128
NYPJM->LTFIMP_NY
CLTF
1.8831.883
LGEELTFEXP_LGEE->PJM
CLTF
2.2642.264
WECLTFEXP_WEC->PJM
CLTF
1.2081.208
CPLELTFEXP_CPLE->PJM
CLTF
19.79519.795
TVALTFEXP_TVA->PJM
CLTF
10.7110.71
MECLTFEXP_MEC->PJM
CLTF
7.1897.189
LAGNLTFEXP_LAGN->PJM
CLTF
13.6813.68
SIGELTFEXP_SIGE->PJM
CLTF
0.4430.443
O66PJM->LTFIMP_O-066
CMTX_NF
26.2626.26

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.42 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2598.93
MW Contribution:16.38
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.96 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2758.53
MW Contribution:16.33
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961671AG1-007 C
Adder
0.73882352941176480.628
961672AG1-007 E
Adder
0.41882352941176470.356
961791AG1-021 C
Adder
1.33058823529411761.131
961792AG1-021 E
Adder
1.13294117647058810.963
961941AG1-037 C
Adder
0.367058823529411770.312
961942AG1-037 E
Adder
0.244705882352941160.208
963041AG1-153 C
50/50
6.556.55
963042AG1-153 E
50/50
9.8259.825
964791AG1-342 C
Adder
3.09882352941176452.634
964792AG1-342 E
Adder
2.06588235294117651.756
966621AG1-532 C
Adder
1.15411764705882350.981
966622AG1-532 E
Adder
0.76941176470588240.654
3138533PONTONDP
Adder
0.49294117647058820.419
3145413WATKINS
Adder
0.451764705882352960.384
3145723EMPORIA
Adder
0.352941176470588260.3
3147133PAMPLIN
Adder
0.740.629
3151311EDGECMA
Adder
12.4152941176470610.553
3151531CLOVER1
50/50
12.55212.552
3151541CLOVER2
50/50
12.43612.436
918492AA1-063AE OP
Adder
3.0882352941176472.625
918532AA1-067 E
Adder
0.54705882352941180.465
919692AA2-053 E OP
Adder
3.30000000000000032.805
920042AA2-088 E OP
Adder
7.3835294117647066.276
925785AC1-054 E
Adder
2.882.448
926274AC1-105 E
Adder
2.3364705882352941.986
927146AC1-208 E
Adder
3.14470588235294152.673
934521AD1-076 C
Adder
9.1176470588235297.75
934522AD1-076 E
Adder
4.6470588235294123.95
943172AE2-346 E
Adder
0.440.374
943902AF1-058 E
Adder
1.11882352941176480.951
944011AF1-069 C
50/50
15.67315.673
944012AF1-069 E
50/50
6.0886.088
959311AF2-222 C
Adder
14.27882352941176512.137
959312AF2-222 E
Adder
9.5670588235294118.132
960081AF2-299 C
Adder
1.541.309
960082AF2-299 E
Adder
1.02588235294117650.872
316141AB2-099 E
Adder
0.183529411764705890.156
900672V4-068 E
Adder
0.254117647058823560.216
917342Z2-044 E
Adder
0.475294117647058870.404
922923AB1-081 E OP
Adder
2.9811764705882352.534
923263AB1-132 E OP
Adder
4.8517647058823534.124
923573AB1-173 E OP
Adder
2.65411764705882322.256
924162AB2-060 E OP
Adder
3.78117647058823543.214
924302AB2-077 E O1
Adder
1.18705882352941171.009
924312AB2-078 E O1
Adder
1.18705882352941171.009
924322AB2-079 E O1
Adder
1.18705882352941171.009
925612AC1-036 E
Adder
0.74705882352941180.635
940492AE2-034 E
Adder
2.3152941176470591.968
941031AE2-094 C
50/50
47.96747.967
941032AE2-094 E
50/50
21.48321.483
946281AF1-292 C
Adder
1.27411764705882361.083
946282AF1-292 E
Adder
0.84941176470588230.722
946301AF1-294 C
Adder
2.73529411764705932.325
946302AF1-294 E
Adder
2.3164705882352941.969
957481AF2-042 C
50/50
55.26355.263
957482AF2-042 E
50/50
36.84236.842
957861AF2-080 C
Adder
5.9388235294117655.048
957862AF2-080 E
Adder
2.6329411764705882.238
958211AF2-115 C
Adder
1.6635294117647061.414
958212AF2-115 E
Adder
1.41647058823529411.204
3145393UNCAMP
Adder
3.8517647058823533.274
916042Z1-036 E
Adder
21.67647058823529718.425
938771AE1-103 C
Adder
1.81647058823529431.544
938772AE1-103 E
Adder
2.50941176470588222.133
3143316POE
Adder
0.80823529411764720.687
3145506HICKORY
50/50
2.1612.161
926662AC1-147 E
Adder
1.23058823529411781.046
926755AC1-161 E
50/50
37.13537.135
3151021BRUNSWICKG1
50/50
9.6689.668
3151031BRUNSWICKG2
50/50
9.6689.668
3151041BRUNSWICKG3
50/50
9.6689.668
3151051BRUNSWICKS1
50/50
20.08620.086
3151081ELIZAR1
50/50
3.033.03
3151091ELIZAR2
50/50
2.9782.978
3151101ELIZAR3
50/50
3.0693.069
3152411Z1-086 GT1
50/50
12.45512.455
3152421Z1-086 GT2
50/50
12.4512.45
3152431Z1-086 GT3
50/50
12.4512.45
3152441Z1-086 ST
50/50
21.68121.681
913392Y1-086 E
Adder
1.8917647058823531.608
916192Z1-068 E
50/50
1.7941.794
923832AB2-022 E
Adder
1.06823529411764720.908
923852AB2-025 E
Adder
0.98588235294117640.838
957601AF2-054 C
Adder
-1.2505882352941176-1.063
901082W1-029 E
Adder
23.54352941176470520.012
917122Z2-027 E
Adder
1.1117647058823530.945
925522AC1-027 E
50/50
1.1581.158
957871AF2-081 C
50/50
9.4939.493
957872AF2-081 E
50/50
4.0684.068
3147223TWITTYS
Adder
0.82823529411764710.704
917512Z2-088 E OP1
Adder
3.83294117647058833.258
926071AC1-086 C
Adder
16.6705882352941214.17
926072AC1-086 E
Adder
7.5870588235294126.449
927021AC1-189 C
Adder
6.5388235294117655.558
927022AC1-189 E
Adder
3.25764705882352962.769
936261AD2-033 C
Adder
10.7294117647058829.12
936262AD2-033 E
Adder
7.1529411764705896.08
933291AC2-141 C
50/50
86.99486.994
933292AC2-141 E
50/50
37.13537.135
934621AD1-088 C
50/50
9.1619.161
934622AD1-088 E
50/50
4.4114.411
939411AE1-173 C
50/50
86.92186.921
939412AE1-173 E
50/50
57.94757.947
916191Z1-068 C
50/50
0.0420.042
933981AD1-022 C
Adder
6.4741176470588245.503
933982AD1-022 E
Adder
3.52470588235294142.996
962572AG1-106 E
Adder
0.9435294117647060.802
962571AG1-106 C
Adder
2.1564705882352941.833
3145946PLYMOUTH TP
Adder
0.24117647058823530.205
3146326AYDLETT TAP
Adder
1.25647058823529421.068
316185AD1-033 C
50/50
1.2261.226
316263AC1-034 C
Adder
5.31058823529411854.514
316274AC1-208 C
Adder
7.0835294117647066.021
316294AC1-161 C
50/50
14.21614.216
316316AC1-027 C
50/50
0.3010.301
917332KELFORD E
Adder
1.2282352941176471.044
924516AB2-100 E1
Adder
2.3717647058823532.016
924517AB2-100 E2
Adder
2.3717647058823532.016
925595AC1-034 E
Adder
4.00588235294117643.405
926206AC1-098 E
Adder
2.8317647058823532.407
926214AC1-099 E
Adder
0.93529411764705890.795
927255AC1-221 E
Adder
3.2152941176470592.733
927264AC1-222 E
Adder
3.3870588235294122.879
932763AC2-100 E
Adder
2.1788235294117651.852
934065AD1-033 E
50/50
5.0045.004
937226AE2-253 E
50/50
5.6435.643
918512AA1-065 E OP
Adder
3.98941176470588273.391
316017AA1-139 ULT1
50/50
1.0281.028
316018AA1-139 ULT2
50/50
1.0281.028
919153AA1-139 E2
50/50
3.8823.882
919152AA1-139 E1
50/50
3.8823.882
919710AA2-057 E
Adder
3.1364705882352942.666
920692AA2-178 E
Adder
3.0870588235294122.624
923994AB2-040_E
Adder
4.9776470588235294.231
924022AB2-043 E O1
Adder
4.6082352941176473.917
924152AB2-059 E OP
Adder
4.2235294117647063.59
925122AB2-169 E
Adder
4.3388235294117653.688
316088AB2-174 E
Adder
5.3035294117647064.508
316375AC2-012 C
50/50
1.2551.255
932046AC2-012 E
50/50
12.1712.17
316388AE2-253 GEN
50/50
1.8981.898
941591AE2-156 C
50/50
16.7516.75
944581AF1-123 C
50/50
45.64445.644
944582AF1-123 E
50/50
104.52104.52
944591AF1-124 C
50/50
45.80645.806
944592AF1-124 E
50/50
104.898104.898
944601AF1-125 C
50/50
44.94144.941
944602AF1-125 E
50/50
102.879102.879
962561AG1-105 C
Adder
7.7917647058823536.623
962562AG1-105 E
Adder
5.1941176470588244.415
964241AG1-285 C
Adder
11.7588235294117649.995
964242AG1-285 E
Adder
7.846.664
3137643SOCKMAN
Adder
0.56941176470588240.484
932632AC2-084 E
Adder
2.50352941176470622.128
934321AD1-056 C
Adder
4.99411764705882364.245
934322AD1-056 E
Adder
2.70941176470588242.303
934331AD1-057 C
Adder
2.78588235294117632.368
934332AD1-057 E
Adder
1.45058823529411771.233
934501AD1-074 C
Adder
25.10470588235294221.339
934502AD1-074 E
Adder
12.7810.863
934511AD1-075 C
Adder
6.2764705882352945.335
934512AD1-075 E
Adder
3.19529411764705932.716
934611AD1-087 C
50/50
1.2361.236
934612AD1-087 E
50/50
3.5653.565
935172AD1-152 E
Adder
5.2058823529411774.425
937481AD2-202 C
50/50
0.3590.359
937482AD2-202 E
50/50
1.0431.043
938531AE1-072 C
50/50
16.39816.398
938532AE1-072 E
50/50
8.5488.548
940481AE2-033 C
Adder
13.6776470588235311.626
940482AE2-033 E
Adder
9.2211764705882357.838
940541AE2-040 C
Adder
2.4364705882352942.071
940641AE2-051 C
50/50
26.4726.47
940642AE2-051 E
50/50
17.64717.647
942461AE2-259 C
Adder
6.5341176470588245.554
942462AE2-259 E
Adder
4.3564705882352943.703
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.7574.757
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.52724.527
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.91517.915
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
81.65881.658
G-007PJM->LTFIMP_G-007
CMTX_NF
2.1242.124
NYPJM->LTFIMP_NY
CLTF
0.9860.986
LGEELTFEXP_LGEE->PJM
CLTF
0.950.95
WECLTFEXP_WEC->PJM
CLTF
0.5060.506
CPLELTFEXP_CPLE->PJM
CLTF
9.989.98
TVALTFEXP_TVA->PJM
CLTF
4.8674.867
MECLTFEXP_MEC->PJM
CLTF
3.1033.103
LAGNLTFEXP_LAGN->PJM
CLTF
6.2356.235
SIGELTFEXP_SIGE->PJM
CLTF
0.1890.189
O66PJM->LTFIMP_O-066
CMTX_NF
13.52713.527

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.3 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3390.97
MW Contribution:12.01
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:138.84 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4471.41
MW Contribution:14.41
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
963041AG1-153 C
Adder
4.8047058823529414.084
963042AG1-153 E
Adder
7.2070588235294136.126
3145413WATKINS
Adder
0.62117647058823530.528
920042AA2-088 E OP
Adder
9.3552941176470597.952
934521AD1-076 C
Adder
10.8305882352941179.206
944011AF1-069 C
Adder
11.3364705882352949.636
944012AF1-069 E
Adder
4.4035294117647063.743
940492AE2-034 E
Adder
2.7635294117647062.349
941031AE2-094 C
Adder
34.69411764705882529.49
941032AE2-094 E
Adder
15.53882352941176513.208
3145393UNCAMP
Adder
5.5035294117647064.678
916042Z1-036 E
Adder
26.0235294117647122.12
938771AE1-103 C
Adder
2.66470588235294152.265
938772AE1-103 E
Adder
3.67882352941176463.127
3143316POE
Adder
1.28352941176470581.091
3145256KINGFORK
Adder
0.94941176470588240.807
3145506HICKORY
Adder
2.04352941176470631.737
3150601CHESTF5
Adder
59.5223529411764750.594
3150651CHESTF6
Adder
17.73411764705882415.074
3150731STONECA
Adder
6.53294117647058855.553
3150831SPRUNCA
50/50
8.7958.795
3150841SPRUNCB
50/50
8.7958.795
3150921YORKTN3
Adder
111.6988235294117794.944
925865AC1-065 E
Adder
15.09882352941176512.834
926412AC1-112 E
Adder
1.03294117647058830.878
926662AC1-147 E
Adder
1.24588235294117641.059
926755AC1-161 E
Adder
12.22823529411764710.394
927226AC1-216 E
Adder
7.2941176470588246.2
934392AD1-063 E
Adder
0.97058823529411760.825
935112AD1-144 E
Adder
0.88235294117647060.75
936591AD2-074 C
Adder
4.9882352941176474.24
936592AD2-074 E
Adder
8.1388235294117656.918
942341AE2-247 C
Adder
1.39529411764705881.186
942342AE2-247 E
Adder
1.92705882352941171.638
943461AF1-017 C
Adder
1.26235294117647071.073
943462AF1-017 E
Adder
2.061.751
943612AF1-032 E
Adder
0.86235294117647050.733
943741AF1-042 C
Adder
2.61058823529411742.219
943742AF1-042 E
Adder
4.2588235294117653.62
958502AF2-144 E
Adder
1.07058823529411760.91
961951AG1-038 C
Adder
2.88470588235294122.452
961952AG1-038 E
Adder
3.98470588235294133.387
966661AG1-536 C
Adder
4.8058823529411764.085
966662AG1-536 E
Adder
6.4588235294117655.49
966871AG1-558 C
Adder
2.1964705882352941.867
966872AG1-558 E
Adder
1.10705882352941170.941
966881AG1-559 C
Adder
2.14941176470588241.827
966882AG1-559 E
Adder
1.08235294117647070.92
3152251N ANNA1
50/50
47.25147.251
3152261N ANNA2
50/50
47.2747.27
316076AC2-137 E
Adder
1.23411764705882351.049
316157AD2-030 E
Adder
1.07647058823529430.915
913392Y1-086 E
Adder
2.041.734
916192Z1-068 E
Adder
1.76588235294117651.501
923832AB2-022 E
Adder
1.1517647058823530.979
923842AB2-024 E
Adder
1.62470588235294121.381
923852AB2-025 E
Adder
1.0352941176470590.88
923862AB2-026 E
Adder
1.08941176470588250.926
925022AB2-158 E
50/50
5.0315.031
930122AB1-027 E
Adder
1.27058823529411781.08
938552AE1-074 E
50/50
1.2191.219
938562AE1-075 E
Adder
0.92941176470588240.79
939312AE1-162 E
Adder
1.3482352941176471.146
946262AF1-291 E
Adder
1.36823529411764721.163
957492AF2-043 E
Adder
1.32705882352941161.128
957601AF2-054 C
Adder
1.91764705882352931.63
957602AF2-054 E
Adder
1.27882352941176471.087
962861AG1-135 C
Adder
5.42823529411764754.614
962862AG1-135 E
Adder
3.6188235294117653.076
962962AG1-145 E
Adder
1.34235294117647071.141
901082W1-029 E
Adder
29.42941176470588325.015
917122Z2-027 E
Adder
1.24470588235294131.058
925332AB2-190 E
Adder
7.6305882352941186.486
925522AC1-027 E
Adder
1.1435294117647060.972
942001AE2-212 C
Adder
2.0505882352941181.743
942002AE2-212 E
Adder
1.36705882352941171.162
957832AF2-077 E
Adder
1.31411764705882361.117
957871AF2-081 C
Adder
9.347.939
957872AF2-081 E
Adder
4.0035294117647063.403
958161AF2-110 C
Adder
1.27411764705882361.083
958162AF2-110 E
Adder
2.02588235294117651.722
3138116ELKO L286
Adder
1.28705882352941181.094
933291AC2-141 C
Adder
28.64705882352941324.35
933292AC2-141 E
Adder
12.22823529411764710.394
939411AE1-173 C
50/50
82.56982.569
939412AE1-173 E
50/50
55.04655.046
934012AD1-025 E
Adder
9.442352941176478.026
927041AC1-191 C
Adder
8.827.497
927042AC1-191 E
Adder
4.3941176470588243.735
3130536PAPERMILL
Adder
6.0070588235294125.106
3145946PLYMOUTH TP
Adder
0.287058823529411760.244
3146326AYDLETT TAP
Adder
1.26470588235294111.075
316160AE1-175 E
Adder
1.10705882352941170.941
316164AC1-076_C
50/50
1.0121.012
316169AC1-164 GEN
Adder
37.0447058823529431.488
316170AC1-121 C
Adder
2.1788235294117651.852
316192AB2-158 C
50/50
1.8991.899
316233AE1-074 C
50/50
2.4192.419
316240AF1-291 C
Adder
2.05294117647058851.745
316254AC1-120 C
Adder
6.3435294117647065.392
924516AB2-100 E1
Adder
2.50705882352941162.131
924517AB2-100 E2
Adder
2.50705882352941162.131
926785AC1-164_E
Adder
16.64352941176470714.147
934065AD1-033 E
Adder
4.7094117647058834.003
937226AE2-253 E
Adder
5.4670588235294124.647
939612AE1-191 E
Adder
5.162352941176474.388
926004AC1-076_E
50/50
5.7785.778
926486AC1-120 E
Adder
3.26823529411764732.778
926502AC1-121 E
Adder
1.02470588235294110.871
939246AE1-155 E
Adder
7.7800000000000016.613
919153AA1-139 E2
Adder
3.823.247
919152AA1-139 E1
Adder
3.823.247
920692AA2-178 E
Adder
3.6835294117647063.131
924814AB2-134 E
Adder
11.94705882352941210.155
316084AB2-161 E
Adder
5.2058823529411774.425
316044AC1-158 C1
50/50
15.00715.007
316045AC1-158 C2
50/50
15.00715.007
926739AC1-158 E1
50/50
39.12239.122
926740AC1-158 E2
50/50
39.12239.122
932046AC2-012 E
Adder
12.32588235294117710.477
316311AC2-079 C
Adder
5.3611764705882364.557
932596AC2-079 E
Adder
8.7482352941176477.436
934146AD1-041 E
Adder
3.22588235294117662.742
934576AD1-082 E
Adder
4.1482352941176473.526
316349AD2-085 C
Adder
3.222.737
936666AD2-085 E
Adder
5.2529411764705884.465
961611AG1-000B C
Adder
15.01294117647058712.761
941591AE2-156 C
Adder
16.84235294117647214.316
944581AF1-123 C
Adder
42.58941176470588636.201
944582AF1-123 E
Adder
97.5247058823529582.896
944591AF1-124 C
Adder
42.74117647058823636.33
944592AF1-124 E
Adder
97.8776470588235383.196
944601AF1-125 C
Adder
41.9329411764705935.643
944602AF1-125 E
Adder
95.9941176470588381.595
944631AF1-128 C
Adder
37.24352941176470531.657
958261AF2-120 C
Adder
5.5870588235294124.749
958262AF2-120 E
Adder
3.7247058823529413.166
934501AD1-074 C
Adder
29.82235294117647225.349
934502AD1-074 E
Adder
15.18117647058823612.904
934511AD1-075 C
Adder
3.1717647058823532.696
935161AD1-151 C
Adder
15.24705882352941312.96
935162AD1-151 E
Adder
10.1647058823529428.64
938531AE1-072 C
Adder
16.40352941176470513.943
938532AE1-072 E
Adder
8.5517647058823547.269
939191AE1-149 C
Adder
10.152941176470598.63
939192AE1-149 E
Adder
6.7682352941176475.753
939261AE1-157 C
Adder
12.43411764705882510.569
939262AE1-157 E
Adder
6.7447058823529415.733
939602AE1-190 E
Adder
1.29058823529411761.097
940431AE2-027 C
Adder
12.27647058823529510.435
940432AE2-027 E
Adder
8.1835294117647066.956
940481AE2-033 C
Adder
14.37882352941176512.222
940482AE2-033 E
Adder
9.6941176470588258.24
940541AE2-040 C
Adder
2.562.176
940551AE2-041 C
Adder
6.4717647058823545.501
940641AE2-051 C
50/50
15.61115.611
940642AE2-051 E
50/50
10.40710.407
941101AE2-104 C
Adder
3.1211764705882352.653
941102AE2-104 E
Adder
4.9623529411764714.218
943471AF1-018 C
Adder
6.4717647058823545.501
944641AF1-129 C
Adder
97.3976470588235282.788
3150851SPRUNCC
50/50
0.1580.158
3150861SPRUNCD
50/50
0.1580.158
316303AF2-085
50/50
3.7313.731
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.9713.971
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.2045.204
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.39910.399
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
66.04366.043
G-007PJM->LTFIMP_G-007
CMTX_NF
3.9253.925
NYPJM->LTFIMP_NY
CLTF
1.9221.922
LGEELTFEXP_LGEE->PJM
CLTF
0.310.31
WECLTFEXP_WEC->PJM
CLTF
0.1350.135
CPLELTFEXP_CPLE->PJM
CLTF
8.348.34
TVALTFEXP_TVA->PJM
CLTF
3.2553.255
MECLTFEXP_MEC->PJM
CLTF
1.3051.305
LAGNLTFEXP_LAGN->PJM
CLTF
4.1614.161
SIGELTFEXP_SIGE->PJM
CLTF
0.0740.074
O66PJM->LTFIMP_O-066
CMTX_NF
25.06225.062

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.93 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4311.71
MW Contribution:43.01
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:112.26 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4569.37
MW Contribution:42.76
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
2.68823529411764732.285
961792AG1-021 E
Adder
2.28941176470588251.946
963041AG1-153 C
50/50
17.20617.206
963042AG1-153 E
50/50
25.80825.808
964791AG1-342 C
50/50
6.3476.347
964792AG1-342 E
50/50
4.2324.232
3138533PONTONDP
Adder
0.99529411764705880.846
3147133PAMPLIN
50/50
1.5711.571
3151531CLOVER1
50/50
28.70828.708
3151541CLOVER2
50/50
28.44128.441
3151581KERR 1
50/50
0.6270.627
3151591KERR 2
50/50
1.7561.756
3151601KERR 3
50/50
1.7561.756
3151611KERR 4
50/50
1.7561.756
3151621KERR 5
50/50
1.7561.756
925785AC1-054 E
Adder
3.30235294117647052.807
926274AC1-105 E
50/50
4.8944.894
942751AE2-291 C
Adder
11.5670588235294139.832
942752AE2-291 E
Adder
7.7105882352941186.554
943902AF1-058 E
50/50
2.3942.394
944011AF1-069 C
50/50
45.64245.642
944012AF1-069 E
50/50
17.73117.731
959311AF2-222 C
50/50
30.29330.293
959312AF2-222 E
50/50
20.29620.296
24401205PINNACLE
Adder
1.53647058823529431.306
3151631KERR 6
50/50
1.7561.756
3151641KERR 7
50/50
1.7561.756
3152661PLYWOOD A
50/50
2.1912.191
316118AC1-105 C
50/50
1.6721.672
316131AB2-060 C
50/50
2.5322.532
924162AB2-060 E OP
50/50
7.2927.292
924302AB2-077 E O1
50/50
2.2822.282
924312AB2-078 E O1
50/50
2.2822.282
924322AB2-079 E O1
50/50
2.2822.282
925612AC1-036 E
50/50
1.5841.584
941031AE2-094 C
50/50
139.691139.691
941032AE2-094 E
50/50
62.56462.564
946301AF1-294 C
Adder
5.5247058823529414.696
946302AF1-294 E
Adder
4.6788235294117653.977
957481AF2-042 C
50/50
128.648128.648
957482AF2-042 E
50/50
85.76685.766
958211AF2-115 C
Adder
3.362.856
958212AF2-115 E
Adder
2.86235294117647052.433
3151021BRUNSWICKG1
50/50
25.39725.397
3151031BRUNSWICKG2
50/50
25.39725.397
3151041BRUNSWICKG3
50/50
25.39725.397
3151051BRUNSWICKS1
50/50
52.76252.762
3152411Z1-086 GT1
50/50
33.84633.846
3152421Z1-086 GT2
50/50
33.83433.834
3152431Z1-086 GT3
50/50
33.83433.834
3152441Z1-086 ST
50/50
58.91958.919
957601AF2-054 C
Adder
-1.6305882352941177-1.386
942001AE2-212 C
Adder
-1.851764705882353-1.574
3147223TWITTYS
50/50
1.7561.756
936261AD2-033 C
50/50
21.05721.057
936262AD2-033 E
50/50
14.03814.038
933291AC2-141 C
Adder
-30.18235294117647-25.655
934621AD1-088 C
50/50
20.82320.823
934622AD1-088 E
50/50
10.02610.026
316003AC1-222 C
50/50
1.7761.776
316034AC1-036 C
50/50
0.4320.432
316222AC1-221 C
50/50
2.632.63
316237AB2-079 C O1
50/50
0.5590.559
316238AB2-078 C O1
50/50
0.5590.559
316239AB2-077 C O1
50/50
0.5590.559
316240AF1-291 C
Adder
-1.7670588235294118-1.502
316248AF1-058 C
50/50
0.5870.587
316283AC2-100 C
50/50
2.112.11
927255AC1-221 E
50/50
6.8776.877
927264AC1-222 E
50/50
7.2547.254
932763AC2-100 E
50/50
4.6444.644
313527AB2-043 C
50/50
0.8840.884
924022AB2-043 E O1
50/50
8.8758.875
925997AC1-075 E
Adder
4.5835294117647063.896
926024AC1-080 E
Adder
1.52117647058823541.293
962561AG1-105 C
50/50
15.80415.804
962562AG1-105 E
50/50
10.53610.536
964241AG1-285 C
50/50
24.94424.944
964242AG1-285 E
50/50
16.62916.629
934611AD1-087 C
50/50
2.8252.825
934612AD1-087 E
50/50
8.158.15
935171AD1-152 C
50/50
2.8452.845
935172AD1-152 E
50/50
11.70511.705
936161AD2-022 C
Adder
11.7541176470588239.991
936162AD2-022 E
Adder
7.0529411764705895.995
936171AD2-023 C
Adder
6.8564705882352955.828
936172AD2-023 E
Adder
3.7223529411764713.164
937481AD2-202 C
50/50
0.820.82
937482AD2-202 E
50/50
2.3852.385
938531AE1-072 C
Adder
-15.17764705882353-12.901
940641AE2-051 C
Adder
-20.06823529411765-17.058
942461AE2-259 C
Adder
13.86823529411764811.788
942462AE2-259 E
Adder
9.2458823529411777.859
944641AF1-129 C
Adder
-82.61058823529412-70.219
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.0719.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5656
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.3338.33
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
162.815162.815
G-007PJM->LTFIMP_G-007
CMTX_NF
3.9723.972
NYPJM->LTFIMP_NY
CLTF
1.8141.814
LGEELTFEXP_LGEE->PJM
CLTF
2.1482.148
WECLTFEXP_WEC->PJM
CLTF
1.1471.147
CPLELTFEXP_CPLE->PJM
CLTF
19.02319.023
TVALTFEXP_TVA->PJM
CLTF
10.24910.249
MECLTFEXP_MEC->PJM
CLTF
6.8436.843
LAGNLTFEXP_LAGN->PJM
CLTF
13.09813.098
SIGELTFEXP_SIGE->PJM
CLTF
0.4210.421
O66PJM->LTFIMP_O-066
CMTX_NF
25.2725.27
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN N ANNA-KRAKEN_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 313483 CKT 1   /*8NO ANNA     500.0 - 8KRAKEN      500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314225 to 314227 ckt 1
314287 to 314260 ckt 1
314260 to 314225 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 313483 ckt 1
314914 to 314322 ckt 1
314936 to 314902 ckt 1
314923 to 314924 ckt 1
314934 to 314916 ckt 1
941030 to 314902 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC106.19 %661.76B702.745.43
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC108.87 %661.76B720.455.43
GD1DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S-1
OPAC111.78 %1058.16B1182.785.66
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
OPAC102.58 %661.76B678.865.43
GD1DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
OPAC103.49 %4070.2B4212.3113.34
GD1DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Base Case
OPAC104.11 %2442.12A2542.4612.2
GD1DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-A
OPAC103.53 %4070.2B4213.913.57
GD1DVP
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
DVP_P1-2: LN 568_SRT-S
OPAC113.01 %3220.44B3639.358.07
GD1DVP
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
OPAC105.31 %4070.2B4286.2642.76
GD1DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Base Case
OPAC104.94 %3220.44A3379.5410.87

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:106.19 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:702.74
MW Contribution:5.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.0282.028
961792AG1-021 E
50/50
1.7281.728
963041AG1-153 C
Adder
2.1717647058823531.846
963042AG1-153 E
Adder
3.25764705882352962.769
964791AG1-342 C
50/50
2.1782.178
964792AG1-342 E
50/50
1.4521.452
966621AG1-532 C
Adder
0.60117647058823530.511
966622AG1-532 E
Adder
0.401176470588235360.341
3138533PONTONDP
50/50
0.7510.751
3144293JTRSVLE
50/50
0.4650.465
3145723EMPORIA
Adder
0.183529411764705890.156
3147133PAMPLIN
50/50
1.1881.188
918492AA1-063AE OP
Adder
1.62117647058823521.378
919692AA2-053 E OP
Adder
1.70470588235294131.449
925785AC1-054 E
Adder
1.72941176470588241.47
926274AC1-105 E
Adder
1.54705882352941181.315
943902AF1-058 E
Adder
0.69411764705882350.59
944011AF1-069 C
Adder
4.8258823529411774.102
944012AF1-069 E
Adder
1.87411764705882341.593
959311AF2-222 C
50/50
16.12516.125
959312AF2-222 E
50/50
10.80310.803
960081AF2-299 C
Adder
0.80117647058823540.681
960082AF2-299 E
Adder
0.53411764705882360.454
316131AB2-060 C
50/50
1.0911.091
923573AB1-173 E OP
Adder
1.38235294117647081.175
924162AB2-060 E OP
50/50
3.1523.152
924302AB2-077 E O1
50/50
0.9480.948
924312AB2-078 E O1
50/50
0.9480.948
924322AB2-079 E O1
50/50
0.9480.948
925612AC1-036 E
50/50
0.8080.808
941011AE2-092 C
50/50
17.02117.021
941012AE2-092 E
50/50
11.34711.347
941031AE2-094 C
Adder
14.76941176470588212.554
941032AE2-094 E
Adder
6.615294117647065.623
946281AF1-292 C
Adder
0.66352941176470580.564
946282AF1-292 E
Adder
0.44235294117647060.376
946301AF1-294 C
50/50
4.174.17
946302AF1-294 E
50/50
3.5313.531
957481AF2-042 C
Adder
29.74705882352941425.285
957482AF2-042 E
Adder
19.8305882352941216.856
958131AF2-107 C
50/50
3.6383.638
958132AF2-107 E
50/50
1.9941.994
958211AF2-115 C
50/50
2.5362.536
958212AF2-115 E
50/50
2.162.16
940451AE2-029 C
Adder
-2.101176470588235-1.786
924032AB2-045 E
50/50
2.7232.723
933502AC2-165 E
50/50
10.89810.898
3150831SPRUNCA
Adder
3.4141176470588242.902
3150841SPRUNCB
Adder
3.4141176470588242.902
958502AF2-144 E
50/50
1.5161.516
3151911BEARGRDN G1
50/50
12.47412.474
3151921BEARGRDN G2
50/50
12.47412.474
923852AB2-025 E
Adder
0.41764705882352940.355
923862AB2-026 E
50/50
1.5431.543
938552AE1-074 E
Adder
0.58705882352941170.499
938562AE1-075 E
50/50
1.3151.315
3147223TWITTYS
50/50
0.8950.895
936261AD2-033 C
50/50
11.6911.69
936262AD2-033 E
50/50
7.7937.793
934621AD1-088 C
50/50
6.3766.376
934622AD1-088 E
50/50
3.073.07
939411AE1-173 C
Adder
31.29411764705882626.6
939412AE1-173 E
Adder
20.8635294117647117.734
3151931BEARGRDN S1
50/50
16.13716.137
316034AC1-036 C
50/50
0.220.22
316233AE1-074 C
Adder
1.16470588235294130.99
316237AB2-079 C O1
50/50
0.2320.232
316238AB2-078 C O1
50/50
0.2320.232
316239AB2-077 C O1
50/50
0.2320.232
316258AE1-075 C
50/50
0.4360.436
316313AB2-026 C
50/50
0.4750.475
316322AB2-045 C
50/50
0.6050.605
316336AC2-165 C
50/50
14.4814.48
316405AF2-144 C
50/50
0.370.37
924516AB2-100 E1
Adder
1.08941176470588250.926
924517AB2-100 E2
Adder
1.08941176470588250.926
927255AC1-221 E
Adder
1.70000000000000021.445
927264AC1-222 E
Adder
2.12235294117647081.804
932763AC2-100 E
Adder
1.14117647058823520.97
923994AB2-040_E
Adder
2.5917647058823532.203
313527AB2-043 C
50/50
0.3710.371
924022AB2-043 E O1
50/50
3.7383.738
316088AB2-174 E
Adder
2.76235294117647052.348
962561AG1-105 C
50/50
5.6135.613
962562AG1-105 E
50/50
3.7423.742
964241AG1-285 C
50/50
1010
964242AG1-285 E
50/50
6.6676.667
3137643SOCKMAN
Adder
0.296470588235294150.252
934612AD1-087 E
Adder
2.04705882352941161.74
935172AD1-152 E
Adder
2.9870588235294122.539
937482AD2-202 E
Adder
0.59882352941176480.509
938821AE1-108 C
50/50
25.08525.085
938822AE1-108 E
50/50
11.96911.969
940481AE2-033 C
Adder
5.8647058823529424.985
940482AE2-033 E
Adder
3.9541176470588243.361
940541AE2-040 C
Adder
1.03294117647058830.878
940641AE2-051 C
Adder
6.0976470588235295.183
940642AE2-051 E
Adder
4.0647058823529413.455
942461AE2-259 C
50/50
13.72813.728
942462AE2-259 E
50/50
9.1529.152
316303AF2-085
50/50
2.082.08
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9351.935
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.2992.299
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.6554.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.59331.593
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9570.957
NYPJM->LTFIMP_NY
CLTF
0.4910.491
LGEELTFEXP_LGEE->PJM
CLTF
0.1180.118
WECLTFEXP_WEC->PJM
CLTF
0.0570.057
CPLELTFEXP_CPLE->PJM
CLTF
4.0634.063
TVALTFEXP_TVA->PJM
CLTF
1.461.46
MECLTFEXP_MEC->PJM
CLTF
0.5720.572
LAGNLTFEXP_LAGN->PJM
CLTF
1.8911.891
SIGELTFEXP_SIGE->PJM
CLTF
0.030.03
O66PJM->LTFIMP_O-066
CMTX_NF
6.1316.131

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.87 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:720.45
MW Contribution:5.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.0282.028
961792AG1-021 E
50/50
1.7281.728
963041AG1-153 C
Adder
2.1717647058823531.846
963042AG1-153 E
Adder
3.25764705882352962.769
964791AG1-342 C
50/50
2.1782.178
964792AG1-342 E
50/50
1.4521.452
966621AG1-532 C
Adder
0.60117647058823530.511
966622AG1-532 E
Adder
0.401176470588235360.341
3138533PONTONDP
50/50
0.7510.751
3144293JTRSVLE
50/50
0.4650.465
3145723EMPORIA
Adder
0.183529411764705890.156
3147133PAMPLIN
50/50
1.1881.188
918492AA1-063AE OP
Adder
1.62117647058823521.378
919692AA2-053 E OP
Adder
1.70470588235294131.449
925785AC1-054 E
Adder
1.72941176470588241.47
926274AC1-105 E
Adder
1.54705882352941181.315
943902AF1-058 E
Adder
0.69411764705882350.59
944011AF1-069 C
Adder
4.8258823529411774.102
944012AF1-069 E
Adder
1.87411764705882341.593
959311AF2-222 C
50/50
16.12516.125
959312AF2-222 E
50/50
10.80310.803
960081AF2-299 C
Adder
0.80117647058823540.681
960082AF2-299 E
Adder
0.53411764705882360.454
316131AB2-060 C
50/50
1.0911.091
923573AB1-173 E OP
Adder
1.38235294117647081.175
924162AB2-060 E OP
50/50
3.1523.152
924302AB2-077 E O1
50/50
0.9480.948
924312AB2-078 E O1
50/50
0.9480.948
924322AB2-079 E O1
50/50
0.9480.948
925612AC1-036 E
50/50
0.8080.808
941011AE2-092 C
50/50
17.02117.021
941012AE2-092 E
50/50
11.34711.347
941031AE2-094 C
Adder
14.76941176470588212.554
941032AE2-094 E
Adder
6.615294117647065.623
946281AF1-292 C
Adder
0.66352941176470580.564
946282AF1-292 E
Adder
0.44235294117647060.376
946301AF1-294 C
50/50
4.174.17
946302AF1-294 E
50/50
3.5313.531
957481AF2-042 C
Adder
29.74705882352941425.285
957482AF2-042 E
Adder
19.8305882352941216.856
958131AF2-107 C
50/50
3.6383.638
958132AF2-107 E
50/50
1.9941.994
958211AF2-115 C
50/50
2.5362.536
958212AF2-115 E
50/50
2.162.16
940451AE2-029 C
Adder
-2.101176470588235-1.786
924032AB2-045 E
50/50
2.7232.723
933502AC2-165 E
50/50
10.89810.898
3150831SPRUNCA
Adder
3.4141176470588242.902
3150841SPRUNCB
Adder
3.4141176470588242.902
958502AF2-144 E
50/50
1.5161.516
3151911BEARGRDN G1
50/50
12.47412.474
3151921BEARGRDN G2
50/50
12.47412.474
923852AB2-025 E
Adder
0.41764705882352940.355
923862AB2-026 E
50/50
1.5431.543
938552AE1-074 E
Adder
0.58705882352941170.499
938562AE1-075 E
50/50
1.3151.315
3147223TWITTYS
50/50
0.8950.895
936261AD2-033 C
50/50
11.6911.69
936262AD2-033 E
50/50
7.7937.793
934621AD1-088 C
50/50
6.3766.376
934622AD1-088 E
50/50
3.073.07
939411AE1-173 C
Adder
31.29411764705882626.6
939412AE1-173 E
Adder
20.8635294117647117.734
3151931BEARGRDN S1
50/50
16.13716.137
316034AC1-036 C
50/50
0.220.22
316233AE1-074 C
Adder
1.16470588235294130.99
316237AB2-079 C O1
50/50
0.2320.232
316238AB2-078 C O1
50/50
0.2320.232
316239AB2-077 C O1
50/50
0.2320.232
316258AE1-075 C
50/50
0.4360.436
316313AB2-026 C
50/50
0.4750.475
316322AB2-045 C
50/50
0.6050.605
316336AC2-165 C
50/50
14.4814.48
316405AF2-144 C
50/50
0.370.37
924516AB2-100 E1
Adder
1.08941176470588250.926
924517AB2-100 E2
Adder
1.08941176470588250.926
927255AC1-221 E
Adder
1.70000000000000021.445
927264AC1-222 E
Adder
2.12235294117647081.804
932763AC2-100 E
Adder
1.14117647058823520.97
923994AB2-040_E
Adder
2.5917647058823532.203
313527AB2-043 C
50/50
0.3710.371
924022AB2-043 E O1
50/50
3.7383.738
316088AB2-174 E
Adder
2.76235294117647052.348
962561AG1-105 C
50/50
5.6135.613
962562AG1-105 E
50/50
3.7423.742
964241AG1-285 C
50/50
1010
964242AG1-285 E
50/50
6.6676.667
3137643SOCKMAN
Adder
0.296470588235294150.252
934612AD1-087 E
Adder
2.04705882352941161.74
935172AD1-152 E
Adder
2.9870588235294122.539
937482AD2-202 E
Adder
0.59882352941176480.509
938821AE1-108 C
50/50
25.08525.085
938822AE1-108 E
50/50
11.96911.969
940481AE2-033 C
Adder
5.8647058823529424.985
940482AE2-033 E
Adder
3.9541176470588243.361
940541AE2-040 C
Adder
1.03294117647058830.878
940641AE2-051 C
Adder
6.0976470588235295.183
940642AE2-051 E
Adder
4.0647058823529413.455
942461AE2-259 C
50/50
13.72813.728
942462AE2-259 E
50/50
9.1529.152
316303AF2-085
50/50
2.082.08
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9351.935
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.2992.299
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.6554.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.59331.593
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9570.957
NYPJM->LTFIMP_NY
CLTF
0.4910.491
LGEELTFEXP_LGEE->PJM
CLTF
0.1180.118
WECLTFEXP_WEC->PJM
CLTF
0.0570.057
CPLELTFEXP_CPLE->PJM
CLTF
4.0634.063
TVALTFEXP_TVA->PJM
CLTF
1.461.46
MECLTFEXP_MEC->PJM
CLTF
0.5720.572
LAGNLTFEXP_LAGN->PJM
CLTF
1.8911.891
SIGELTFEXP_SIGE->PJM
CLTF
0.030.03
O66PJM->LTFIMP_O-066
CMTX_NF
6.1316.131

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:111.78 %
Rating:1058.16 MVA
Rating Type:B
MVA to Mitigate:1182.78
MW Contribution:5.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
0.97294117647058820.827
961792AG1-021 E
Adder
0.82823529411764710.704
963041AG1-153 C
Adder
2.2623529411764711.923
963042AG1-153 E
Adder
3.39411764705882352.885
966621AG1-532 C
Adder
0.63882352941176480.543
966622AG1-532 E
Adder
0.42588235294117650.362
3138533PONTONDP
Adder
0.360.306
3145413WATKINS
Adder
0.30941176470588240.263
3145723EMPORIA
Adder
0.196470588235294150.167
3147133PAMPLIN
Adder
0.54941176470588240.467
918492AA1-063AE OP
Adder
1.8117647058823531.54
919692AA2-053 E OP
Adder
1.86823529411764721.588
920042AA2-088 E OP
Adder
4.724.012
944011AF1-069 C
Adder
5.2235294117647074.44
944012AF1-069 E
Adder
2.02941176470588271.725
959311AF2-222 C
Adder
8.5341176470588237.254
959312AF2-222 E
Adder
5.71764705882352954.86
960081AF2-299 C
Adder
0.8517647058823530.724
960082AF2-299 E
Adder
0.56823529411764710.483
900672V4-068 E
Adder
0.157647058823529420.134
923263AB1-132 E OP
Adder
2.70941176470588242.303
923573AB1-173 E OP
Adder
1.47764705882352951.256
924162AB2-060 E OP
Adder
2.0117647058823531.71
924302AB2-077 E O1
Adder
0.62117647058823530.528
924312AB2-078 E O1
Adder
0.62117647058823530.528
924322AB2-079 E O1
Adder
0.62117647058823530.528
925612AC1-036 E
Adder
0.435294117647058830.37
940492AE2-034 E
Adder
1.33882352941176451.138
941011AE2-092 C
Adder
6.9470588235294125.905
941012AE2-092 E
Adder
4.6305882352941183.936
941031AE2-094 C
Adder
15.98588235294117513.588
941032AE2-094 E
Adder
7.166.086
946281AF1-292 C
Adder
0.70588235294117650.6
946282AF1-292 E
Adder
0.47058823529411770.4
946301AF1-294 C
Adder
1.99882352941176491.699
946302AF1-294 E
Adder
1.69294117647058841.439
957481AF2-042 C
Adder
23.21647058823529619.734
957482AF2-042 E
Adder
15.4776470588235313.156
958211AF2-115 C
Adder
1.21529411764705891.033
958212AF2-115 E
Adder
1.0352941176470590.88
3145393UNCAMP
Adder
2.72117647058823582.313
916042Z1-036 E
Adder
12.43647058823529310.571
938771AE1-103 C
Adder
1.3117647058823531.115
938772AE1-103 E
Adder
1.8117647058823531.54
924032AB2-045 E
Adder
0.94941176470588240.807
933502AC2-165 E
50/50
10.19910.199
3143096IRON208
50/50
0.330.33
3143316POE
Adder
0.75647058823529410.643
3145256KINGFORK
Adder
0.455294117647058850.387
3145506HICKORY
Adder
0.94470588235294130.803
3150601CHESTF5
Adder
39.4470588235294233.53
3150651CHESTF6
Adder
11.96588235294117610.171
3150731STONECA
Adder
4.1494117647058823.527
3150831SPRUNCA
50/50
9.4469.446
3150841SPRUNCB
50/50
9.4469.446
3150921YORKTN3
Adder
52.8152941176470644.893
925865AC1-065 E
Adder
7.73058823529411756.571
926412AC1-112 E
Adder
0.56470588235294120.48
926662AC1-147 E
Adder
0.58117647058823530.494
926755AC1-161 E
Adder
0.59529411764705890.506
927226AC1-216 E
Adder
4.20352941176470553.573
934392AD1-063 E
Adder
0.487058823529411770.414
935112AD1-144 E
Adder
0.42235294117647060.359
942341AE2-247 C
Adder
0.71294117647058820.606
942342AE2-247 E
Adder
0.98470588235294120.837
943461AF1-017 C
Adder
0.64470588235294120.548
943462AF1-017 E
Adder
1.0517647058823530.894
943612AF1-032 E
Adder
0.405882352941176470.345
958502AF2-144 E
50/50
1.7771.777
966871AG1-558 C
Adder
1.27764705882352961.086
966872AG1-558 E
Adder
0.64352941176470590.547
316076AC2-137 E
Adder
0.73529411764705890.625
316157AD2-030 E
Adder
0.53411764705882360.454
913392Y1-086 E
Adder
0.9552941176470590.812
916192Z1-068 E
Adder
0.820.697
923832AB2-022 E
Adder
0.53882352941176470.458
923842AB2-024 E
Adder
0.82235294117647050.699
923852AB2-025 E
Adder
0.54941176470588240.467
923862AB2-026 E
50/50
1.8081.808
930122AB1-027 E
Adder
0.69529411764705880.591
938552AE1-074 E
50/50
1.8811.881
938562AE1-075 E
50/50
1.5421.542
939312AE1-162 E
Adder
0.67999999999999990.578
946262AF1-291 E
Adder
0.91058823529411770.774
957492AF2-043 E
Adder
0.62470588235294120.531
957601AF2-054 C
Adder
0.95294117647058830.81
957602AF2-054 E
Adder
0.63529411764705890.54
962962AG1-145 E
Adder
0.65529411764705890.557
901082W1-029 E
Adder
13.8976470588235311.813
917122Z2-027 E
Adder
0.58470588235294120.497
925332AB2-190 E
Adder
4.5752941176470593.889
925522AC1-027 E
Adder
0.53176470588235290.452
942001AE2-212 C
Adder
1.3035294117647061.108
942002AE2-212 E
Adder
0.86941176470588230.739
957832AF2-077 E
Adder
0.63529411764705890.54
957871AF2-081 C
Adder
4.3329411764705883.683
957872AF2-081 E
Adder
1.85647058823529431.578
958161AF2-110 C
Adder
0.61529411764705890.523
958162AF2-110 E
Adder
0.97882352941176460.832
3138116ELKO L286
Adder
0.76588235294117660.651
3147223TWITTYS
Adder
0.48235294117647060.41
926071AC1-086 C
Adder
9.3082352941176477.912
926072AC1-086 E
Adder
4.2364705882352943.601
936261AD2-033 C
Adder
6.5000000000000015.525
936262AD2-033 E
Adder
4.3329411764705883.683
933291AC2-141 C
Adder
12.51176470588235310.635
934621AD1-088 C
Adder
4.3294117647058833.68
934622AD1-088 E
Adder
2.08470588235294141.772
939411AE1-173 C
Adder
37.3388235294117631.738
939412AE1-173 E
Adder
24.89294117647058621.159
934012AD1-025 E
Adder
5.44117647058823554.625
927041AC1-191 C
Adder
5.1282352941176474.359
927042AC1-191 E
Adder
2.55411764705882362.171
962572AG1-106 E
Adder
0.52705882352941180.448
962571AG1-106 C
Adder
1.20352941176470571.023
3130536PAPERMILL
Adder
3.0341176470588242.579
3146326AYDLETT TAP
Adder
0.58823529411764710.5
316160AE1-175 E
Adder
0.54117647058823540.46
316169AC1-164 GEN
Adder
19.79647058823529816.827
316233AE1-074 C
50/50
3.7333.733
316240AF1-291 C
Adder
1.36588235294117651.161
316258AE1-075 C
50/50
0.5110.511
316313AB2-026 C
50/50
0.5570.557
316336AC2-165 C
50/50
13.55213.552
316405AF2-144 C
50/50
0.4340.434
924516AB2-100 E1
Adder
1.32117647058823541.123
924517AB2-100 E2
Adder
1.32117647058823541.123
926785AC1-164_E
Adder
8.8941176470588247.56
934065AD1-033 E
Adder
2.1752941176470591.849
937226AE2-253 E
Adder
2.53176470588235342.152
939612AE1-191 E
Adder
2.6082352941176472.217
919153AA1-139 E2
Adder
1.7717647058823531.506
919152AA1-139 E1
Adder
1.7717647058823531.506
920692AA2-178 E
Adder
1.78588235294117651.518
923994AB2-040_E
Adder
2.76941176470588252.354
924022AB2-043 E O1
Adder
2.4235294117647062.06
924814AB2-134 E
Adder
6.8847058823529425.852
316084AB2-161 E
Adder
2.8764705882352942.445
316088AB2-174 E
Adder
2.94705882352941152.505
932046AC2-012 E
Adder
5.7529411764705884.89
316311AC2-079 C
Adder
2.71999999999999982.312
932596AC2-079 E
Adder
4.4376470588235293.772
934146AD1-041 E
Adder
1.63058823529411771.386
934576AD1-082 E
Adder
2.2917647058823531.948
316349AD2-085 C
Adder
1.6447058823529411.398
936666AD2-085 E
Adder
2.6835294117647062.281
961611AG1-000B C
Adder
8.1152941176470596.898
941591AE2-156 C
Adder
7.8529411764705886.675
944581AF1-123 C
Adder
19.50352941176470616.578
944582AF1-123 E
Adder
44.6637.961
944591AF1-124 C
Adder
19.5717647058823516.636
944592AF1-124 E
Adder
44.82117647058823538.098
944601AF1-125 C
Adder
19.2023529411764716.322
944602AF1-125 E
Adder
43.9588235294117737.365
944631AF1-128 C
Adder
24.6823529411764720.98
964241AG1-285 C
Adder
6.0305882352941185.126
964242AG1-285 E
Adder
4.0211764705882363.418
3137643SOCKMAN
Adder
0.317647058823529450.27
934612AD1-087 E
Adder
1.55882352941176471.325
935161AD1-151 C
Adder
8.9764705882352947.63
935162AD1-151 E
Adder
5.9847058823529415.087
937482AD2-202 E
Adder
0.456470588235294130.388
938531AE1-072 C
Adder
7.6223529411764716.479
938532AE1-072 E
Adder
3.9729411764705883.377
938821AE1-108 C
Adder
8.4270588235294127.163
938822AE1-108 E
Adder
4.0211764705882363.418
939191AE1-149 C
Adder
5.8976470588235295.013
939192AE1-149 E
Adder
3.93176470588235333.342
939602AE1-190 E
Adder
0.6517647058823530.554
940431AE2-027 C
Adder
7.9682352941176476.773
940432AE2-027 E
Adder
5.3129411764705894.516
940481AE2-033 C
Adder
7.6223529411764716.479
940482AE2-033 E
Adder
5.13882352941176554.368
940541AE2-040 C
Adder
1.35764705882352941.154
940551AE2-041 C
Adder
3.25058823529411762.763
940641AE2-051 C
Adder
7.0152941176470595.963
940642AE2-051 E
Adder
4.67764705882352953.976
941101AE2-104 C
Adder
1.50823529411764711.282
941102AE2-104 E
Adder
2.39764705882352922.038
942461AE2-259 C
Adder
5.83647058823529454.961
942462AE2-259 E
Adder
3.8917647058823533.308
943471AF1-018 C
Adder
3.25058823529411762.763
944641AF1-129 C
Adder
65.7211764705882355.863
3150851SPRUNCC
50/50
0.1690.169
3150861SPRUNCD
50/50
0.1690.169
316303AF2-085
50/50
7.0277.027
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
2.2422.242
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.08118.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.29711.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.62940.629
G-007PJM->LTFIMP_G-007
CMTX_NF
2.112.11
NYPJM->LTFIMP_NY
CLTF
0.9630.963
LGEELTFEXP_LGEE->PJM
CLTF
0.7270.727
WECLTFEXP_WEC->PJM
CLTF
0.3730.373
CPLELTFEXP_CPLE->PJM
CLTF
4.6984.698
TVALTFEXP_TVA->PJM
CLTF
2.952.95
MECLTFEXP_MEC->PJM
CLTF
2.1322.132
LAGNLTFEXP_LAGN->PJM
CLTF
3.6953.695
SIGELTFEXP_SIGE->PJM
CLTF
0.1370.137
O66PJM->LTFIMP_O-066
CMTX_NF
13.41813.418

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.58 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:678.86
MW Contribution:5.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
50/50
2.0282.028
961792AG1-021 E
50/50
1.7281.728
963041AG1-153 C
Adder
2.1717647058823531.846
963042AG1-153 E
Adder
3.25764705882352962.769
964791AG1-342 C
50/50
2.1782.178
964792AG1-342 E
50/50
1.4521.452
966621AG1-532 C
Adder
0.60117647058823530.511
966622AG1-532 E
Adder
0.401176470588235360.341
3138533PONTONDP
50/50
0.7510.751
3144293JTRSVLE
50/50
0.4650.465
3145723EMPORIA
Adder
0.183529411764705890.156
3147133PAMPLIN
50/50
1.1881.188
918492AA1-063AE OP
Adder
1.62117647058823521.378
919692AA2-053 E OP
Adder
1.70470588235294131.449
925785AC1-054 E
Adder
1.72941176470588241.47
926274AC1-105 E
Adder
1.54705882352941181.315
943902AF1-058 E
Adder
0.69411764705882350.59
944011AF1-069 C
Adder
4.8258823529411774.102
944012AF1-069 E
Adder
1.87411764705882341.593
959311AF2-222 C
50/50
16.12516.125
959312AF2-222 E
50/50
10.80310.803
960081AF2-299 C
Adder
0.80117647058823540.681
960082AF2-299 E
Adder
0.53411764705882360.454
316131AB2-060 C
50/50
1.0911.091
923573AB1-173 E OP
Adder
1.38235294117647081.175
924162AB2-060 E OP
50/50
3.1523.152
924302AB2-077 E O1
50/50
0.9480.948
924312AB2-078 E O1
50/50
0.9480.948
924322AB2-079 E O1
50/50
0.9480.948
925612AC1-036 E
50/50
0.8080.808
941011AE2-092 C
50/50
17.02117.021
941012AE2-092 E
50/50
11.34711.347
941031AE2-094 C
Adder
14.76941176470588212.554
941032AE2-094 E
Adder
6.615294117647065.623
946281AF1-292 C
Adder
0.66352941176470580.564
946282AF1-292 E
Adder
0.44235294117647060.376
946301AF1-294 C
50/50
4.174.17
946302AF1-294 E
50/50
3.5313.531
957481AF2-042 C
Adder
29.74705882352941425.285
957482AF2-042 E
Adder
19.8305882352941216.856
958131AF2-107 C
50/50
3.6383.638
958132AF2-107 E
50/50
1.9941.994
958211AF2-115 C
50/50
2.5362.536
958212AF2-115 E
50/50
2.162.16
940451AE2-029 C
Adder
-2.101176470588235-1.786
924032AB2-045 E
50/50
2.7232.723
933502AC2-165 E
50/50
10.89810.898
3150831SPRUNCA
Adder
3.4141176470588242.902
3150841SPRUNCB
Adder
3.4141176470588242.902
958502AF2-144 E
50/50
1.5161.516
3151911BEARGRDN G1
50/50
12.47412.474
3151921BEARGRDN G2
50/50
12.47412.474
923852AB2-025 E
Adder
0.41764705882352940.355
923862AB2-026 E
50/50
1.5431.543
938552AE1-074 E
Adder
0.58705882352941170.499
938562AE1-075 E
50/50
1.3151.315
3147223TWITTYS
50/50
0.8950.895
936261AD2-033 C
50/50
11.6911.69
936262AD2-033 E
50/50
7.7937.793
934621AD1-088 C
50/50
6.3766.376
934622AD1-088 E
50/50
3.073.07
939411AE1-173 C
Adder
31.29411764705882626.6
939412AE1-173 E
Adder
20.8635294117647117.734
3151931BEARGRDN S1
50/50
16.13716.137
316034AC1-036 C
50/50
0.220.22
316233AE1-074 C
Adder
1.16470588235294130.99
316237AB2-079 C O1
50/50
0.2320.232
316238AB2-078 C O1
50/50
0.2320.232
316239AB2-077 C O1
50/50
0.2320.232
316258AE1-075 C
50/50
0.4360.436
316313AB2-026 C
50/50
0.4750.475
316322AB2-045 C
50/50
0.6050.605
316336AC2-165 C
50/50
14.4814.48
316405AF2-144 C
50/50
0.370.37
924516AB2-100 E1
Adder
1.08941176470588250.926
924517AB2-100 E2
Adder
1.08941176470588250.926
927255AC1-221 E
Adder
1.70000000000000021.445
927264AC1-222 E
Adder
2.12235294117647081.804
932763AC2-100 E
Adder
1.14117647058823520.97
923994AB2-040_E
Adder
2.5917647058823532.203
313527AB2-043 C
50/50
0.3710.371
924022AB2-043 E O1
50/50
3.7383.738
316088AB2-174 E
Adder
2.76235294117647052.348
962561AG1-105 C
50/50
5.6135.613
962562AG1-105 E
50/50
3.7423.742
964241AG1-285 C
50/50
1010
964242AG1-285 E
50/50
6.6676.667
3137643SOCKMAN
Adder
0.296470588235294150.252
934612AD1-087 E
Adder
2.04705882352941161.74
935172AD1-152 E
Adder
2.9870588235294122.539
937482AD2-202 E
Adder
0.59882352941176480.509
938821AE1-108 C
50/50
25.08525.085
938822AE1-108 E
50/50
11.96911.969
940481AE2-033 C
Adder
5.8647058823529424.985
940482AE2-033 E
Adder
3.9541176470588243.361
940541AE2-040 C
Adder
1.03294117647058830.878
940641AE2-051 C
Adder
6.0976470588235295.183
940642AE2-051 E
Adder
4.0647058823529413.455
942461AE2-259 C
50/50
13.72813.728
942462AE2-259 E
50/50
9.1529.152
316303AF2-085
50/50
2.082.08
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
1.9351.935
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.2992.299
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.6554.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.59331.593
G-007PJM->LTFIMP_G-007
CMTX_NF
0.9570.957
NYPJM->LTFIMP_NY
CLTF
0.4910.491
LGEELTFEXP_LGEE->PJM
CLTF
0.1180.118
WECLTFEXP_WEC->PJM
CLTF
0.0570.057
CPLELTFEXP_CPLE->PJM
CLTF
4.0634.063
TVALTFEXP_TVA->PJM
CLTF
1.461.46
MECLTFEXP_MEC->PJM
CLTF
0.5720.572
LAGNLTFEXP_LAGN->PJM
CLTF
1.8911.891
SIGELTFEXP_SIGE->PJM
CLTF
0.030.03
O66PJM->LTFIMP_O-066
CMTX_NF
6.1316.131

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.49 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4212.31
MW Contribution:13.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
963041AG1-153 C
Adder
5.3364705882352944.536
963042AG1-153 E
Adder
8.0047058823529426.804
3145413WATKINS
Adder
0.71529411764705890.608
920042AA2-088 E OP
Adder
10.782352941176479.165
944011AF1-069 C
Adder
12.49058823529411910.617
944012AF1-069 E
Adder
4.8517647058823534.124
940492AE2-034 E
Adder
3.1905882352941182.712
941031AE2-094 C
Adder
38.2270588235294232.493
941032AE2-094 E
Adder
17.12117647058823514.553
3145393UNCAMP
Adder
6.3329411764705885.383
916042Z1-036 E
Adder
29.97176470588235425.476
938771AE1-103 C
Adder
3.06470588235294142.605
938772AE1-103 E
Adder
4.2317647058823533.597
3142296MT RD221
50/50
0.1350.135
3142366NRTHEST
50/50
0.2060.206
3143316POE
Adder
1.4635294117647061.244
3145256KINGFORK
Adder
1.09411764705882360.93
3145506HICKORY
Adder
2.34000000000000031.989
3150391LDYSMT3
50/50
5.3915.391
3150401LDYSMT4
50/50
5.4015.401
3150411LDYSMT5
50/50
5.4185.418
3150601CHESTF5
Adder
70.2058823529411759.675
3150651CHESTF6
Adder
20.5870588235294117.499
3150701DARBY 4
50/50
2.8532.853
3150731STONECA
Adder
7.6200000000000016.477
3150831SPRUNCA
Adder
10.0964705882352958.582
3150841SPRUNCB
Adder
10.0964705882352958.582
3150921YORKTN3
Adder
130.66235294117647111.063
925865AC1-065 E
Adder
17.8870588235294115.204
926412AC1-112 E
50/50
1.2521.252
926662AC1-147 E
Adder
1.42941176470588241.215
926755AC1-161 E
Adder
14.03647058823529311.931
927226AC1-216 E
Adder
8.4752941176470587.204
934392AD1-063 E
Adder
1.1517647058823530.979
935112AD1-144 E
Adder
1.0152941176470590.863
936591AD2-074 C
Adder
5.9258823529411765.037
936592AD2-074 E
Adder
9.6694117647058818.219
942341AE2-247 C
Adder
1.60235294117647081.362
942342AE2-247 E
Adder
2.2129411764705881.881
943461AF1-017 C
Adder
1.44941176470588241.232
943462AF1-017 E
Adder
2.36588235294117682.011
943612AF1-032 E
Adder
0.99058823529411770.842
943741AF1-042 C
Adder
3.10117647058823562.636
943742AF1-042 E
Adder
5.05882352941176454.3
961951AG1-038 C
Adder
3.42705882352941152.913
961952AG1-038 E
Adder
4.7329411764705884.023
966661AG1-536 C
Adder
5.7152941176470584.858
966662AG1-536 E
Adder
7.686.528
966871AG1-558 C
Adder
2.662.261
966872AG1-558 E
Adder
1.341.139
966881AG1-559 C
50/50
2.7662.766
966882AG1-559 E
50/50
1.3931.393
3152251N ANNA1
50/50
40.24640.246
3152261N ANNA2
50/50
40.26240.262
316076AC2-137 E
Adder
1.47529411764705891.254
316078AC2-138 E
Adder
0.97411764705882350.828
316157AD2-030 E
Adder
1.27411764705882361.083
913392Y1-086 E
Adder
2.34117647058823541.99
916192Z1-068 E
Adder
2.0235294117647061.72
923832AB2-022 E
Adder
1.32117647058823541.123
923842AB2-024 E
Adder
1.92941176470588241.64
923852AB2-025 E
Adder
1.16941176470588240.994
930122AB1-027 E
50/50
1.5391.539
938552AE1-074 E
Adder
1.35529411764705881.152
939312AE1-162 E
Adder
1.5552941176470591.322
946262AF1-291 E
Adder
1.58588235294117651.348
957492AF2-043 E
Adder
1.52352941176470581.295
957601AF2-054 C
Adder
2.2717647058823531.931
957602AF2-054 E
Adder
1.51411764705882361.287
962861AG1-135 C
Adder
6.4529411764705885.485
962862AG1-135 E
Adder
4.3023529411764713.657
962962AG1-145 E
Adder
1.5835294117647061.346
963611AG1-210 C
Adder
0.69529411764705880.591
963612AG1-210 E
Adder
1.04352941176470580.887
964211AG1-282 C
Adder
2.11764705882352941.8
964212AG1-282 E
Adder
1.4117647058823531.2
901082W1-029 E
Adder
33.8176470588235328.745
917122Z2-027 E
Adder
1.4282352941176471.214
925332AB2-190 E
Adder
8.8811764705882377.549
925522AC1-027 E
Adder
1.31058823529411781.114
942001AE2-212 C
Adder
2.35882352941176482.005
942002AE2-212 E
Adder
1.57294117647058831.337
957832AF2-077 E
Adder
1.54588235294117651.314
957871AF2-081 C
Adder
10.6988235294117659.094
957872AF2-081 E
Adder
4.5847058823529413.897
958161AF2-110 C
Adder
1.46235294117647091.243
958162AF2-110 E
Adder
2.3270588235294121.978
3138116ELKO L286
Adder
1.53882352941176471.308
3141813NORNECK
Adder
0.92588235294117650.787
933291AC2-141 C
Adder
32.8811764705882427.949
933292AC2-141 E
Adder
14.03647058823529311.931
939411AE1-173 C
Adder
92.0364705882352978.231
939412AE1-173 E
Adder
61.3576470588235452.154
934012AD1-025 E
Adder
10.9729411764705889.327
927041AC1-191 C
Adder
10.6788235294117659.077
927042AC1-191 E
Adder
5.3188235294117654.521
3130536PAPERMILL
Adder
7.1317647058823546.062
3145946PLYMOUTH TP
Adder
0.33176470588235290.282
3146326AYDLETT TAP
Adder
1.44941176470588241.232
316004AC1-112 C
50/50
0.3640.364
316160AE1-175 E
Adder
1.30705882352941181.111
316169AC1-164 GEN
Adder
44.39529411764705537.736
316233AE1-074 C
Adder
2.69176470588235262.288
316240AF1-291 C
Adder
2.37882352941176432.022
316312AB1-027 C
50/50
0.5850.585
926785AC1-164_E
Adder
19.94588235294117616.954
934065AD1-033 E
Adder
5.3894117647058834.581
937226AE2-253 E
Adder
6.265.321
939612AE1-191 E
Adder
6.1141176470588245.197
926004AC1-076_E
Adder
4.277647058823533.636
3150371LDYSMT1
50/50
5.1855.185
3150381LDYSMT2
50/50
5.2525.252
315051AA1-145 CT1
50/50
5.6195.619
315052AA1-145 CT2
50/50
5.6165.616
939246AE1-155 E
Adder
9.2517647058823537.864
919153AA1-139 E2
Adder
4.3752941176470593.719
919152AA1-139 E1
Adder
4.3752941176470593.719
920692AA2-178 E
Adder
4.2541176470588233.616
924814AB2-134 E
Adder
13.88352941176470711.801
316084AB2-161 E
Adder
5.9764705882352945.08
316044AC1-158 C1
50/50
7.3677.367
316045AC1-158 C2
50/50
7.3677.367
926739AC1-158 E1
50/50
19.2719.27
926740AC1-158 E2
50/50
19.2719.27
932046AC2-012 E
Adder
14.1412.019
316311AC2-079 C
Adder
6.1564705882352945.233
932596AC2-079 E
Adder
10.0458823529411768.539
934146AD1-041 E
Adder
3.8211764705882363.248
934576AD1-082 E
Adder
4.7623529411764714.048
316349AD2-085 C
Adder
3.6976470588235293.143
936666AD2-085 E
Adder
6.03294117647058855.128
961611AG1-000B C
Adder
17.4070588235294114.796
941591AE2-156 C
Adder
19.3216.422
944581AF1-123 C
Adder
48.9258823529411841.587
944582AF1-123 E
Adder
112.0352941176470795.23
944591AF1-124 C
Adder
49.141.735
944592AF1-124 E
Adder
112.4411764705882595.575
944601AF1-125 C
Adder
48.17294117647059440.947
944602AF1-125 E
Adder
110.2776470588235393.736
944631AF1-128 C
Adder
43.9294117647058937.34
958261AF2-120 C
Adder
6.6447058823529415.648
958262AF2-120 E
Adder
4.4294117647058833.765
934501AD1-074 C
Adder
34.51411764705882529.337
934502AD1-074 E
Adder
8.9670588235294127.622
935161AD1-151 C
Adder
17.7317647058823515.072
935162AD1-151 E
Adder
11.82117647058823610.048
938531AE1-072 C
Adder
18.79411764705882215.975
938532AE1-072 E
Adder
9.7976470588235298.328
939191AE1-149 C
Adder
11.6529411764705889.905
939192AE1-149 E
Adder
7.7682352941176476.603
939261AE1-157 C
50/50
16.15516.155
939262AE1-157 E
50/50
8.7638.763
939602AE1-190 E
Adder
1.5282352941176471.299
940431AE2-027 C
Adder
14.21058823529411812.079
940432AE2-027 E
Adder
9.4729411764705888.052
940481AE2-033 C
Adder
16.25647058823529513.818
940482AE2-033 E
Adder
10.969.316
940541AE2-040 C
Adder
2.89058823529411772.457
940551AE2-041 C
Adder
7.67764705882352956.526
940641AE2-051 C
Adder
17.23529411764705814.65
940642AE2-051 E
Adder
11.4905882352941179.767
941101AE2-104 C
Adder
3.58470588235294143.047
941102AE2-104 E
Adder
5.6988235294117654.844
943471AF1-018 C
Adder
7.67764705882352956.526
944641AF1-129 C
Adder
113.0705882352941296.11
3150431FOUR RIVERA
50/50
3.5273.527
3150441FOUR RIVERB
50/50
3.5273.527
3150451FOUR RIVERC
50/50
4.314.31
3150461FOUR RIVERD
50/50
3.4763.476
3150471FOUR RIVERE
50/50
3.4763.476
3150481FOUR RIVERF
50/50
4.2454.245
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.0355.035
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.06830.068
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.37922.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
90.48890.488
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7495.749
NYPJM->LTFIMP_NY
CLTF
2.722.72
LGEELTFEXP_LGEE->PJM
CLTF
1.3021.302
WECLTFEXP_WEC->PJM
CLTF
0.640.64
CPLELTFEXP_CPLE->PJM
CLTF
10.55810.558
TVALTFEXP_TVA->PJM
CLTF
6.1246.124
MECLTFEXP_MEC->PJM
CLTF
3.9143.914
LAGNLTFEXP_LAGN->PJM
CLTF
7.6467.646
SIGELTFEXP_SIGE->PJM
CLTF
0.2490.249
O66PJM->LTFIMP_O-066
CMTX_NF
36.64136.641

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.11 %
Rating:2442.12 MVA
Rating Type:A
MVA to Mitigate:2542.46
MW Contribution:12.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961941AG1-037 C
Adder
0.55529411764705880.472
961942AG1-037 E
Adder
0.370588235294117660.315
963041AG1-153 C
Adder
4.884.148
963042AG1-153 E
Adder
7.3188235294117656.221
966621AG1-532 C
Adder
1.27294117647058851.082
966622AG1-532 E
Adder
0.84823529411764710.721
3145413WATKINS
Adder
0.82235294117647050.699
3145723EMPORIA
Adder
0.39411764705882360.335
918492AA1-063AE OP
Adder
4.17764705882352953.551
918532AA1-067 E
Adder
0.72588235294117650.617
919692AA2-053 E OP
Adder
4.1705882352941183.545
920042AA2-088 E OP
Adder
11.93294117647058910.143
927146AC1-208 E
Adder
3.8470588235294123.27
934521AD1-076 C
Adder
14.67647058823529312.475
934522AD1-076 E
Adder
7.48117647058823556.359
943172AE2-346 E
Adder
0.66705882352941170.567
944011AF1-069 C
Adder
11.532941176470599.803
944012AF1-069 E
Adder
4.47999999999999953.808
960081AF2-299 C
Adder
1.69647058823529421.442
960082AF2-299 E
Adder
1.13058823529411770.961
316141AB2-099 E
Adder
0.27764705882352940.236
900672V4-068 E
Adder
0.395294117647058850.336
923263AB1-132 E OP
Adder
5.86235294117647054.983
923573AB1-173 E OP
Adder
3.06235294117647072.603
940492AE2-034 E
Adder
3.8317647058823533.257
941031AE2-094 C
Adder
35.2988235294117730.004
941032AE2-094 E
Adder
15.80941176470588313.438
946281AF1-292 C
Adder
1.40470588235294121.194
946282AF1-292 E
Adder
0.93647058823529420.796
957861AF2-080 C
Adder
7.47999999999999956.358
957862AF2-080 E
Adder
3.3152941176470592.818
3145393UNCAMP
Adder
7.4105882352941186.299
916042Z1-036 E
Adder
37.13529411764706431.565
938771AE1-103 C
Adder
3.62470588235294143.081
938772AE1-103 E
Adder
5.00588235294117644.255
3143316POE
Adder
1.19294117647058821.014
3144216WINCHST
50/50
0.20.2
3145256KINGFORK
50/50
1.4051.405
3145506HICKORY
50/50
3.0893.089
3150601CHESTF5
Adder
66.756.695
3150731STONECA
Adder
6.8694117647058835.839
3150921YORKTN3
50/50
185.501185.501
925865AC1-065 E
Adder
22.29058823529411618.947
926472AC1-118 E
Adder
1.13411764705882350.964
926662AC1-147 E
50/50
1.8821.882
926755AC1-161 E
50/50
20.21420.214
927226AC1-216 E
Adder
8.9599999999999997.616
934392AD1-063 E
50/50
1.4751.475
935112AD1-144 E
50/50
1.3041.304
936582AD2-073 E
Adder
1.23176470588235291.047
936591AD2-074 C
Adder
7.2670588235294116.177
936592AD2-074 E
Adder
11.85764705882353110.079
942341AE2-247 C
Adder
1.84117647058823521.565
942342AE2-247 E
Adder
2.54235294117647072.161
943461AF1-017 C
Adder
1.66588235294117641.416
943462AF1-017 E
Adder
2.71882352941176462.311
943612AF1-032 E
Adder
1.2764705882352941.085
943741AF1-042 C
Adder
3.8023529411764713.232
943742AF1-042 E
Adder
6.20470588235294155.274
961951AG1-038 C
Adder
4.20352941176470553.573
961952AG1-038 E
Adder
5.8035294117647064.933
966661AG1-536 C
Adder
6.91529411764705955.878
966662AG1-536 E
Adder
9.2917647058823527.898
3150981CHESPKA
50/50
0.6170.617
3150991CHESPKB
50/50
1.0231.023
3151081ELIZAR1
50/50
4.5444.544
3151091ELIZAR2
50/50
4.4644.464
3151101ELIZAR3
50/50
4.6014.601
3152331SURRY 2
50/50
43.89143.891
316076AC2-137 E
Adder
1.53647058823529431.306
316078AC2-138 E
Adder
1.1482352941176470.976
316157AD2-030 E
Adder
1.6270588235294121.383
913392Y1-086 E
Adder
3.0235294117647062.57
916192Z1-068 E
50/50
2.672.67
923832AB2-022 E
Adder
1.7070588235294121.451
923842AB2-024 E
50/50
2.4762.476
923852AB2-025 E
Adder
1.040.884
939312AE1-162 E
Adder
1.9235294117647061.635
957492AF2-043 E
Adder
1.9635294117647061.669
957601AF2-054 C
Adder
2.92.465
957602AF2-054 E
Adder
1.93294117647058841.643
962861AG1-135 C
Adder
7.8329411764705896.658
962862AG1-135 E
Adder
5.2211764705882354.438
962962AG1-145 E
50/50
2.2212.221
963611AG1-210 C
Adder
0.820.697
963612AG1-210 E
Adder
1.23058823529411781.046
964211AG1-282 C
Adder
2.5270588235294122.148
964212AG1-282 E
Adder
1.6847058823529411.432
901082W1-029 E
Adder
43.0176470588235336.565
917122Z2-027 E
Adder
1.83411764705882341.559
925332AB2-190 E
Adder
8.8411764705882367.515
925522AC1-027 E
50/50
1.7291.729
957831AF2-077 C
50/50
0.4830.483
957832AF2-077 E
50/50
2.0912.091
957871AF2-081 C
50/50
14.02714.027
957872AF2-081 E
50/50
6.0126.012
958161AF2-110 C
Adder
1.81529411764705871.543
958162AF2-110 E
Adder
2.8870588235294122.454
3138116ELKO L286
Adder
1.60117647058823541.361
3141813NORNECK
Adder
1.09294117647058830.929
926071AC1-086 C
Adder
20.14470588235294517.123
926072AC1-086 E
Adder
9.1682352941176477.793
927021AC1-189 C
Adder
8.235294117647067
927022AC1-189 E
Adder
4.1023529411764713.487
933291AC2-141 C
50/50
47.35447.354
933292AC2-141 E
50/50
20.21420.214
939411AE1-173 C
Adder
101.4858823529411986.263
939412AE1-173 E
Adder
67.656470588235357.508
934012AD1-025 E
Adder
11.69.86
916191Z1-068 C
50/50
0.0620.062
933981AD1-022 C
Adder
10.3435294117647068.792
933982AD1-022 E
Adder
5.6317647058823534.787
962572AG1-106 E
Adder
1.140.969
962571AG1-106 C
Adder
2.60588235294117652.215
3130536PAPERMILL
50/50
9.1469.146
3145946PLYMOUTH TP
Adder
0.38941176470588240.331
3146326AYDLETT TAP
50/50
1.8931.893
316036AC1-147 C
50/50
0.5220.522
316059AD1-063 C
50/50
0.360.36
316072AD1-144 C
50/50
0.3890.389
316159AE1-175 C
50/50
0.6010.601
316160AE1-175 E
50/50
1.8321.832
316169AC1-164 GEN
50/50
57.50657.506
316185AD1-033 C
50/50
1.7411.741
316274AC1-208 C
Adder
8.6647058823529427.365
316294AC1-161 C
50/50
7.7117.711
316314AB2-024 C
50/50
0.4030.403
316316AC1-027 C
50/50
0.4470.447
316382AG1-145 C
50/50
0.5420.542
917332KELFORD E
Adder
1.74000000000000021.479
924516AB2-100 E1
Adder
2.6788235294117652.277
924517AB2-100 E2
Adder
2.6788235294117652.277
926206AC1-098 E
Adder
3.5952941176470593.056
926214AC1-099 E
Adder
1.18705882352941171.009
926785AC1-164_E
50/50
25.83625.836
934065AD1-033 E
50/50
7.137.13
937226AE2-253 E
50/50
8.238.23
939612AE1-191 E
Adder
7.76.545
939246AE1-155 E
Adder
11.1941176470588259.515
918512AA1-065 E OP
Adder
6.2364705882352955.301
316017AA1-139 ULT1
50/50
1.5131.513
316018AA1-139 ULT2
50/50
1.5131.513
919153AA1-139 E2
50/50
5.7365.736
919152AA1-139 E1
50/50
5.7365.736
920692AA2-178 E
Adder
5.1082352941176474.342
923994AB2-040_E
Adder
5.7423529411764714.881
924814AB2-134 E
Adder
14.67647058823529312.475
316084AB2-161 E
Adder
6.0352941176470595.13
925122AB2-169 E
Adder
6.3976470588235295.438
316088AB2-174 E
Adder
6.03294117647058855.128
316375AC2-012 C
50/50
1.9131.913
932046AC2-012 E
50/50
18.61318.613
316311AC2-079 C
Adder
7.1458823529411766.074
932596AC2-079 E
Adder
11.6588235294117669.91
934146AD1-041 E
Adder
4.8129411764705894.091
934576AD1-082 E
Adder
4.80941176470588254.088
316349AD2-085 C
Adder
4.2482352941176483.611
936666AD2-085 E
Adder
6.9317647058823545.892
316388AE2-253 GEN
50/50
2.7582.758
961611AG1-000B C
Adder
20.0529411764705917.045
941591AE2-156 C
50/50
25.46125.461
944581AF1-123 C
50/50
65.6165.61
944582AF1-123 E
50/50
150.24150.24
944591AF1-124 C
50/50
65.84465.844
944592AF1-124 E
50/50
150.785150.785
944601AF1-125 C
50/50
64.664.6
944602AF1-125 E
50/50
147.882147.882
944631AF1-128 C
Adder
41.73529411764706535.475
958261AF2-120 C
Adder
8.0388235294117656.833
958262AF2-120 E
Adder
5.3588235294117644.555
3137643SOCKMAN
Adder
0.6764705882352940.575
932632AC2-084 E
Adder
3.17764705882352952.701
934501AD1-074 C
Adder
40.41176470588235534.35
934502AD1-074 E
Adder
20.57176470588235517.486
934511AD1-075 C
Adder
10.102352941176478.587
934512AD1-075 E
Adder
5.1435294117647064.372
935161AD1-151 C
Adder
18.1615.436
935162AD1-151 E
Adder
12.10588235294117610.29
938531AE1-072 C
50/50
24.57324.573
938532AE1-072 E
50/50
12.8112.81
939191AE1-149 C
Adder
10.6576470588235289.059
939192AE1-149 E
Adder
7.1047058823529416.039
939602AE1-190 E
Adder
1.9247058823529411.636
940431AE2-027 C
Adder
10.9364705882352939.296
940432AE2-027 E
Adder
3.88235294117647063.3
940481AE2-033 C
Adder
14.5623529411764712.378
940482AE2-033 E
Adder
9.817647058823538.345
940541AE2-040 C
Adder
2.5717647058823532.186
940551AE2-041 C
Adder
9.8305882352941178.356
940641AE2-051 C
Adder
17.715.045
940642AE2-051 E
Adder
11.79999999999999910.03
941101AE2-104 C
Adder
4.4482352941176473.781
941102AE2-104 E
Adder
7.0717647058823536.011
943471AF1-018 C
Adder
9.8305882352941178.356
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
4.274.27
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.05913.059
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.06213.062
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
70.8670.86
G-007PJM->LTFIMP_G-007
CMTX_NF
2.7242.724
NYPJM->LTFIMP_NY
CLTF
1.3121.312
LGEELTFEXP_LGEE->PJM
CLTF
0.5530.553
WECLTFEXP_WEC->PJM
CLTF
0.2830.283
CPLELTFEXP_CPLE->PJM
CLTF
8.9638.963
TVALTFEXP_TVA->PJM
CLTF
3.7783.778
MECLTFEXP_MEC->PJM
CLTF
1.9921.992
LAGNLTFEXP_LAGN->PJM
CLTF
4.854.85
SIGELTFEXP_SIGE->PJM
CLTF
0.1170.117
O66PJM->LTFIMP_O-066
CMTX_NF
17.37617.376

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-A
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.53 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4213.9
MW Contribution:13.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
963041AG1-153 C
Adder
5.4305882352941184.616
963042AG1-153 E
Adder
8.1447058823529416.923
3145413WATKINS
Adder
0.72823529411764710.619
920042AA2-088 E OP
Adder
10.9811764705882359.334
934521AD1-076 C
Adder
12.77058823529411810.855
934522AD1-076 E
Adder
6.5094117647058835.533
944011AF1-069 C
Adder
12.71176470588235210.805
944012AF1-069 E
Adder
4.9388235294117654.198
940492AE2-034 E
Adder
3.25176470588235272.764
941031AE2-094 C
Adder
38.9070588235294133.071
941032AE2-094 E
Adder
17.42588235294117614.812
3145393UNCAMP
Adder
6.4517647058823535.484
916042Z1-036 E
Adder
30.54352941176470525.962
938771AE1-103 C
Adder
3.12235294117647082.654
938772AE1-103 E
Adder
4.3117647058823533.665
3142296MT RD221
50/50
0.1380.138
3142366NRTHEST
50/50
0.2110.211
3143316POE
Adder
1.4917647058823531.268
3145256KINGFORK
Adder
1.11529411764705880.948
3145506HICKORY
Adder
2.38470588235294122.027
3150391LDYSMT3
50/50
5.5445.544
3150401LDYSMT4
50/50
5.5555.555
3150411LDYSMT5
50/50
5.5725.572
3150601CHESTF5
Adder
71.6458823529411960.899
3150651CHESTF6
Adder
20.99647058823529717.847
3150701DARBY 4
50/50
2.9132.913
3150731STONECA
Adder
7.7717647058823536.606
3150831SPRUNCA
Adder
10.2905882352941188.747
3150841SPRUNCB
Adder
10.2905882352941188.747
3150921YORKTN3
Adder
133.3164705882353113.319
925865AC1-065 E
Adder
18.27411764705882315.533
926412AC1-112 E
50/50
1.2791.279
926662AC1-147 E
Adder
1.45764705882352951.239
926755AC1-161 E
Adder
14.30941176470588312.163
927226AC1-216 E
Adder
8.6447058823529417.348
934392AD1-063 E
Adder
1.17647058823529421
934782AD1-105 E
Adder
2.9682352941176472.523
935112AD1-144 E
Adder
1.0352941176470590.88
936591AD2-074 C
Adder
6.0611764705882365.152
936592AD2-074 E
Adder
9.8894117647058838.406
942341AE2-247 C
Adder
1.63294117647058811.388
942342AE2-247 E
Adder
2.2552941176470591.917
943461AF1-017 C
Adder
1.47764705882352951.256
943462AF1-017 E
Adder
2.4117647058823532.05
943612AF1-032 E
Adder
1.00941176470588250.858
943741AF1-042 C
Adder
3.1717647058823532.696
943742AF1-042 E
Adder
5.1741176470588234.398
961951AG1-038 C
Adder
3.50588235294117642.98
961952AG1-038 E
Adder
4.8411764705882364.115
966661AG1-536 C
Adder
5.8482352941176474.971
966662AG1-536 E
Adder
7.857647058823536.679
966871AG1-558 C
Adder
2.71882352941176462.311
966872AG1-558 E
Adder
1.36941176470588231.164
966881AG1-559 C
50/50
2.8382.838
966882AG1-559 E
50/50
1.431.43
3152251N ANNA1
50/50
40.87840.878
3152261N ANNA2
50/50
40.89340.893
316076AC2-137 E
Adder
1.50588235294117641.28
316078AC2-138 E
Adder
0.99647058823529410.847
316157AD2-030 E
Adder
1.30235294117647071.107
913392Y1-086 E
Adder
2.38588235294117632.028
916192Z1-068 E
Adder
2.0635294117647061.754
923832AB2-022 E
Adder
1.34705882352941191.145
923842AB2-024 E
Adder
1.97176470588235291.676
923852AB2-025 E
Adder
1.19058823529411771.012
930122AB1-027 E
50/50
1.5721.572
938552AE1-074 E
Adder
1.38000000000000011.173
939312AE1-162 E
Adder
1.58588235294117651.348
946262AF1-291 E
Adder
1.61764705882352941.375
957492AF2-043 E
Adder
1.55294117647058831.32
957601AF2-054 C
Adder
2.321.972
957602AF2-054 E
Adder
1.54705882352941181.315
962861AG1-135 C
Adder
6.6023529411764715.612
962862AG1-135 E
Adder
4.40117647058823553.741
962962AG1-145 E
Adder
1.61647058823529431.374
963611AG1-210 C
Adder
0.7117647058823530.605
963612AG1-210 E
Adder
1.06823529411764720.908
964211AG1-282 C
Adder
2.16705882352941171.842
964212AG1-282 E
Adder
1.44470588235294131.228
901082W1-029 E
Adder
34.4682352941176529.298
917122Z2-027 E
Adder
1.4552941176470591.237
925332AB2-190 E
Adder
9.057647058823537.699
925522AC1-027 E
Adder
1.3364705882352941.136
942001AE2-212 C
Adder
2.40588235294117642.045
942002AE2-212 E
Adder
1.60352941176470591.363
957832AF2-077 E
Adder
1.57882352941176471.342
957871AF2-081 C
Adder
10.904705882352949.269
957872AF2-081 E
Adder
4.6741176470588233.973
958161AF2-110 C
Adder
1.49058823529411751.267
958162AF2-110 E
Adder
2.3717647058823532.016
3138116ELKO L286
Adder
1.57058823529411761.335
3141813NORNECK
Adder
0.94823529411764720.806
933291AC2-141 C
Adder
33.5211764705882428.493
933292AC2-141 E
Adder
14.30941176470588312.163
939411AE1-173 C
Adder
93.7423529411764679.681
939412AE1-173 E
Adder
62.4952941176470653.121
934012AD1-025 E
Adder
11.1917647058823539.513
927041AC1-191 C
Adder
10.915294117647069.278
927042AC1-191 E
Adder
5.4376470588235294.622
3130536PAPERMILL
Adder
7.2870588235294126.194
3145946PLYMOUTH TP
Adder
0.33764705882352940.287
3146326AYDLETT TAP
Adder
1.47764705882352951.256
316004AC1-112 C
50/50
0.3720.372
316160AE1-175 E
Adder
1.33411764705882341.134
316169AC1-164 GEN
Adder
45.3376470588235338.537
316233AE1-074 C
Adder
2.73882352941176472.328
316240AF1-291 C
Adder
2.42588235294117642.062
316312AB1-027 C
50/50
0.5970.597
924516AB2-100 E1
Adder
2.91411764705882352.477
924517AB2-100 E2
Adder
2.91411764705882352.477
926785AC1-164_E
Adder
20.36941176470588417.314
934065AD1-033 E
Adder
5.49411764705882364.67
937226AE2-253 E
Adder
6.3811764705882365.424
939612AE1-191 E
Adder
6.2458823529411775.309
3150371LDYSMT1
50/50
5.3335.333
3150381LDYSMT2
50/50
5.4025.402
315051AA1-145 CT1
50/50
5.755.75
315052AA1-145 CT2
50/50
5.7475.747
939246AE1-155 E
Adder
9.4658823529411768.046
919153AA1-139 E2
Adder
4.463.791
919152AA1-139 E1
Adder
4.463.791
920692AA2-178 E
Adder
4.3352941176470593.685
924814AB2-134 E
Adder
14.1612.036
316084AB2-161 E
Adder
6.0929411764705895.179
932046AC2-012 E
Adder
14.41411764705882512.252
316311AC2-079 C
Adder
6.2752941176470595.334
932596AC2-079 E
Adder
10.2388235294117648.703
934146AD1-041 E
Adder
3.9035294117647063.318
934576AD1-082 E
Adder
4.8541176470588244.126
316349AD2-085 C
Adder
3.7682352941176473.203
936666AD2-085 E
Adder
6.1494117647058835.227
961611AG1-000B C
Adder
17.75176470588235515.089
941591AE2-156 C
Adder
19.6952941176470616.741
944581AF1-123 C
Adder
49.87411764705882442.393
944582AF1-123 E
Adder
114.2058823529411997.075
944591AF1-124 C
Adder
50.0517647058823542.544
944592AF1-124 E
Adder
114.6297.427
944601AF1-125 C
Adder
49.1058823529411841.74
944602AF1-125 E
Adder
112.412941176470695.551
944631AF1-128 C
Adder
44.8294117647058838.105
958261AF2-120 C
Adder
6.7976470588235295.778
958262AF2-120 E
Adder
4.53176470588235253.852
934501AD1-074 C
Adder
35.1647058823529429.89
934502AD1-074 E
Adder
17.90117647058823615.216
934511AD1-075 C
Adder
8.7917647058823527.473
934512AD1-075 E
Adder
4.4752941176470593.804
935161AD1-151 C
Adder
18.08588235294117715.373
935162AD1-151 E
Adder
12.0576470588235310.249
938531AE1-072 C
Adder
19.15764705882352816.284
938532AE1-072 E
Adder
9.9870588235294138.489
939191AE1-149 C
Adder
11.8810.098
939192AE1-149 E
Adder
7.9200000000000016.732
939261AE1-157 C
50/50
16.59116.591
939262AE1-157 E
50/50
8.9998.999
939602AE1-190 E
Adder
1.56117647058823541.327
940431AE2-027 C
Adder
14.49176470588235312.318
940432AE2-027 E
Adder
9.6611764705882348.212
940481AE2-033 C
Adder
16.55647058823529614.073
940482AE2-033 E
Adder
11.1611764705882369.487
940541AE2-040 C
Adder
2.94352941176470572.502
940551AE2-041 C
Adder
7.8435294117647066.667
940641AE2-051 C
Adder
17.55058823529411814.918
940642AE2-051 E
Adder
11.7000000000000019.945
941101AE2-104 C
Adder
3.65411764705882373.106
941102AE2-104 E
Adder
5.80941176470588254.938
943471AF1-018 C
Adder
7.8435294117647066.667
944641AF1-129 C
Adder
115.3152941176470698.018
3150431FOUR RIVERA
50/50
3.613.61
3150441FOUR RIVERB
50/50
3.613.61
3150451FOUR RIVERC
50/50
4.414.41
3150461FOUR RIVERD
50/50
3.5573.557
3150471FOUR RIVERE
50/50
3.5573.557
3150481FOUR RIVERF
50/50
4.3444.344
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
5.1265.126
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.55931.559
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.04923.049
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
92.18992.189
G-007PJM->LTFIMP_G-007
CMTX_NF
5.6455.645
NYPJM->LTFIMP_NY
CLTF
2.6672.667
LGEELTFEXP_LGEE->PJM
CLTF
1.3551.355
WECLTFEXP_WEC->PJM
CLTF
0.6690.669
CPLELTFEXP_CPLE->PJM
CLTF
10.74810.748
TVALTFEXP_TVA->PJM
CLTF
6.2796.279
MECLTFEXP_MEC->PJM
CLTF
4.0634.063
LAGNLTFEXP_LAGN->PJM
CLTF
7.8427.842
SIGELTFEXP_SIGE->PJM
CLTF
0.2590.259
O66PJM->LTFIMP_O-066
CMTX_NF
35.97435.974

Details for 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 568_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 568_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.01 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3639.35
MW Contribution:8.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
963041AG1-153 C
Adder
3.22823529411764732.744
963042AG1-153 E
Adder
4.842352941176474.116
944011AF1-069 C
Adder
7.5129411764705896.386
944012AF1-069 E
Adder
2.9188235294117652.481
941031AE2-094 C
Adder
22.99176470588235319.543
941032AE2-094 E
Adder
10.297647058823538.753
3145393UNCAMP
Adder
3.73882352941176473.178
916042Z1-036 E
Adder
17.63882352941176614.993
938771AE1-103 C
Adder
1.80588235294117651.535
938772AE1-103 E
Adder
2.49294117647058842.119
933502AC2-165 E
Adder
4.6105882352941173.919
3143316POE
Adder
0.8517647058823530.724
3145256KINGFORK
Adder
0.63529411764705890.54
3145506HICKORY
Adder
1.36235294117647051.158
3150211REMNGT1
50/50
4.0534.053
3150221REMNGT2
50/50
4.0914.091
3150231REMNGT3
50/50
4.6034.603
3150241REMNGT4
50/50
4.1084.108
3150281M RUN A
50/50
4.5814.581
3150291M RUN B
50/50
4.5454.545
3150301M RUN C
50/50
4.5794.579
3150601CHESTF5
Adder
39.7423529411764733.781
3150651CHESTF6
Adder
11.80470588235294310.034
3150731STONECA
Adder
4.3564705882352943.703
3150831SPRUNCA
Adder
5.8117647058823544.94
3150841SPRUNCB
Adder
5.8117647058823544.94
3150921YORKTN3
Adder
74.6435294117647263.447
925865AC1-065 E
Adder
10.0070588235294128.506
926412AC1-112 E
Adder
0.69529411764705880.591
926662AC1-147 E
Adder
0.8317647058823530.707
926755AC1-161 E
Adder
8.1494117647058816.927
927226AC1-216 E
Adder
4.8670588235294114.137
934392AD1-063 E
Adder
0.64352941176470590.547
934861AD1-115 C
50/50
3.1623.162
934862AD1-115 E
50/50
5.1585.158
935112AD1-144 E
Adder
0.59058823529411760.502
942341AE2-247 C
Adder
0.93411764705882360.794
942342AE2-247 E
Adder
1.28941176470588251.096
943461AF1-017 C
Adder
0.84470588235294120.718
943462AF1-017 E
Adder
1.37882352941176461.172
943612AF1-032 E
Adder
0.57764705882352940.491
958502AF2-144 E
Adder
0.74941176470588230.637
966871AG1-558 C
Adder
1.46235294117647091.243
966872AG1-558 E
Adder
0.73647058823529410.626
3151771S ANNAG1
50/50
1.751.75
3151781S ANNAS1
50/50
0.8990.899
3151791S ANNAG2
50/50
1.751.75
3151801S ANNAS2
50/50
0.8990.899
3152251N ANNA1
50/50
25.66925.669
3152261N ANNA2
50/50
25.67925.679
316076AC2-137 E
Adder
0.82705882352941170.703
913392Y1-086 E
Adder
1.36823529411764721.163
916192Z1-068 E
Adder
1.17764705882352931.001
923832AB2-022 E
Adder
0.7717647058823530.656
923842AB2-024 E
Adder
1.07764705882352940.916
923852AB2-025 E
Adder
0.69411764705882350.59
923862AB2-026 E
Adder
0.76235294117647070.648
925022AB2-158 E
50/50
4.2284.228
930122AB1-027 E
Adder
0.85411764705882350.726
938552AE1-074 E
Adder
0.79529411764705890.676
938562AE1-075 E
Adder
0.65058823529411770.553
939312AE1-162 E
Adder
0.90.765
946262AF1-291 E
Adder
0.91058823529411770.774
957492AF2-043 E
Adder
0.88823529411764710.755
962962AG1-145 E
Adder
0.89764705882352950.763
963031AG1-152 C
50/50
6.6516.651
963032AG1-152 E
50/50
9.9779.977
966001AG1-469 C
50/50
1.4091.409
966002AG1-469 E
50/50
0.7050.705
901082W1-029 E
Adder
19.80352941176470316.833
917122Z2-027 E
Adder
0.83529411764705890.71
925332AB2-190 E
Adder
5.0905882352941184.327
925522AC1-027 E
Adder
0.76235294117647070.648
925672AC1-043 E
50/50
10.31710.317
942001AE2-212 C
Adder
1.36235294117647051.158
942002AE2-212 E
Adder
0.90823529411764710.772
957832AF2-077 E
Adder
0.87411764705882360.743
957871AF2-081 C
Adder
6.2388235294117655.303
957872AF2-081 E
Adder
2.67411764705882372.273
958161AF2-110 C
Adder
0.85411764705882350.726
958162AF2-110 E
Adder
1.35882352941176481.155
3138116ELKO L286
Adder
0.86235294117647050.733
933291AC2-141 C
Adder
19.09176470588235516.228
933292AC2-141 E
Adder
8.1494117647058816.927
939411AE1-173 C
Adder
54.4741176470588246.303
939412AE1-173 E
Adder
36.316470588235330.869
923892AB2-029 E
50/50
2.0392.039
934012AD1-025 E
Adder
6.3011764705882355.356
927041AC1-191 C
Adder
5.8741176470588244.993
927042AC1-191 E
Adder
2.9258823529411772.487
3130536PAPERMILL
Adder
3.9835294117647063.386
3146326AYDLETT TAP
Adder
0.84588235294117640.719
316160AE1-175 E
Adder
0.74117647058823530.63
316164AC1-076_C
50/50
0.6630.663
316169AC1-164 GEN
Adder
24.84352941176470621.117
316170AC1-121 C
50/50
2.262.26
316192AB2-158 C
50/50
1.5911.591
316233AE1-074 C
Adder
1.57882352941176471.342
316240AF1-291 C
Adder
1.36588235294117651.161
316254AC1-120 C
50/50
6.5816.581
316257AC1-043 C
50/50
6.3236.323
316336AC2-165 C
Adder
6.1258823529411775.207
926785AC1-164_E
Adder
11.1611764705882369.487
934065AD1-033 E
Adder
3.1388235294117652.668
937226AE2-253 E
Adder
3.64941176470588243.102
939612AE1-191 E
Adder
3.422.907
926004AC1-076_E
50/50
3.7993.799
926486AC1-120 E
50/50
3.393.39
926502AC1-121 E
50/50
1.0641.064
926615AC1-143 E
50/50
3.1393.139
316006AB2-029 C
50/50
0.2070.207
316267AC1-143 C
50/50
6.8796.879
316411AF1-147_GEN1
Adder
-4.0458823529411765-3.439
316415AF1-147_GEN2
Adder
-4.0458823529411765-3.439
919153AA1-139 E2
Adder
2.5505882352941182.168
919152AA1-139 E1
Adder
2.5505882352941182.168
924814AB2-134 E
Adder
7.9717647058823536.776
316084AB2-161 E
Adder
3.47411764705882352.953
316044AC1-158 C1
50/50
5.6365.636
316045AC1-158 C2
50/50
5.6365.636
926739AC1-158 E1
50/50
14.74214.742
926740AC1-158 E2
50/50
14.74214.742
932046AC2-012 E
Adder
8.2235294117647076.99
316311AC2-079 C
Adder
3.58941176470588273.051
932596AC2-079 E
Adder
5.8564705882352944.978
934146AD1-041 E
Adder
2.13764705882352951.817
934576AD1-082 E
Adder
2.76823529411764732.353
316349AD2-085 C
Adder
2.1552941176470591.832
936666AD2-085 E
Adder
3.51647058823529422.989
961611AG1-000B C
Adder
10.0211764705882368.518
941591AE2-156 C
Adder
11.2364705882352949.551
944581AF1-123 C
Adder
28.48352941176470724.211
944582AF1-123 E
Adder
65.2247058823529555.441
944591AF1-124 C
Adder
28.58470588235294224.297
944592AF1-124 E
Adder
65.4611764705882455.642
944601AF1-125 C
Adder
28.04470588235294323.838
944602AF1-125 E
Adder
64.2011764705882454.571
944631AF1-128 C
Adder
24.86705882352941221.137
935161AD1-151 C
Adder
10.1717647058823558.646
935162AD1-151 E
Adder
6.7811764705882355.764
938531AE1-072 C
Adder
10.9647058823529419.32
938532AE1-072 E
Adder
5.7152941176470584.858
939191AE1-149 C
Adder
6.7600000000000015.746
939192AE1-149 E
Adder
4.5070588235294123.831
939221AE1-153 C
50/50
14.35714.357
939222AE1-153 E
50/50
9.5719.571
939602AE1-190 E
Adder
0.85529411764705890.727
940431AE2-027 C
Adder
8.1647058823529426.94
940432AE2-027 E
Adder
5.4435294117647064.627
940481AE2-033 C
Adder
9.6588235294117668.21
940482AE2-033 E
Adder
6.5117647058823535.535
940541AE2-040 C
Adder
1.71529411764705891.458
940551AE2-041 C
Adder
4.2894117647058823.646
940641AE2-051 C
Adder
10.2564705882352948.718
940642AE2-051 E
Adder
6.837647058823535.812
941101AE2-104 C
Adder
2.0929411764705881.779
941102AE2-104 E
Adder
3.32823529411764742.829
943471AF1-018 C
Adder
4.2894117647058823.646
944641AF1-129 C
Adder
64.8341176470588355.109
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.2763.276
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.58334.583
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.68919.689
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
61.60961.609
G-007PJM->LTFIMP_G-007
CMTX_NF
5.7675.767
NYPJM->LTFIMP_NY
CLTF
2.5742.574
LGEELTFEXP_LGEE->PJM
CLTF
1.3821.382
WECLTFEXP_WEC->PJM
CLTF
0.710.71
CPLELTFEXP_CPLE->PJM
CLTF
6.8626.862
TVALTFEXP_TVA->PJM
CLTF
4.9884.988
MECLTFEXP_MEC->PJM
CLTF
3.9063.906
LAGNLTFEXP_LAGN->PJM
CLTF
6.216.21
SIGELTFEXP_SIGE->PJM
CLTF
0.2540.254
O66PJM->LTFIMP_O-066
CMTX_NF
36.63136.631

Details for 8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.31 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4286.26
MW Contribution:42.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
961791AG1-021 C
Adder
2.30941176470588251.963
961792AG1-021 E
Adder
1.96705882352941171.672
963041AG1-153 C
50/50
17.10317.103
963042AG1-153 E
50/50
25.65425.654
964791AG1-342 C
50/50
5.7665.766
964792AG1-342 E
50/50
3.8443.844
3138533PONTONDP
Adder
0.85529411764705890.727
3147133PAMPLIN
Adder
1.261.071
3151531CLOVER1
50/50
28.86828.868
3151541CLOVER2
50/50
28.59928.599
3151581KERR 1
50/50
0.5770.577
3151591KERR 2
50/50
1.6151.615
3151601KERR 3
50/50
1.6151.615
3151611KERR 4
50/50
1.6151.615
3151621KERR 5
50/50
1.6151.615
925785AC1-054 E
Adder
2.96470588235294132.52
926274AC1-105 E
50/50
4.6164.616
942751AE2-291 C
Adder
12.11176470588235310.295
942752AE2-291 E
Adder
8.0741176470588246.863
943902AF1-058 E
50/50
2.342.34
959311AF2-222 C
50/50
22.05622.056
959312AF2-222 E
50/50
14.77814.778
24401205PINNACLE
Adder
1.6670588235294121.417
3151631KERR 6
50/50
1.6151.615
3151641KERR 7
50/50
1.6151.615
3152661PLYWOOD A
50/50
2.0932.093
316118AC1-105 C
50/50
1.5721.572
316131AB2-060 C
50/50
2.042.04
924162AB2-060 E OP
50/50
5.8965.896
924302AB2-077 E O1
50/50
1.8631.863
924312AB2-078 E O1
50/50
1.8631.863
924322AB2-079 E O1
50/50
1.8631.863
925612AC1-036 E
50/50
1.1421.142
940081AE1-250 C
Adder
12.86117647058823510.932
940082AE1-250 E
Adder
8.5741176470588247.288
946301AF1-294 C
Adder
4.7458823529411774.034
946302AF1-294 E
Adder
4.01882352941176453.416
957481AF2-042 C
50/50
129.887129.887
957482AF2-042 E
50/50
86.59186.591
958211AF2-115 C
Adder
2.88588235294117632.453
958212AF2-115 E
Adder
2.45882352941176442.09
3151021BRUNSWICKG1
50/50
25.15825.158
3151031BRUNSWICKG2
50/50
25.15825.158
3151041BRUNSWICKG3
50/50
25.15825.158
3151051BRUNSWICKS1
50/50
52.26552.265
3152411Z1-086 GT1
50/50
33.47433.474
3152421Z1-086 GT2
50/50
33.46533.465
3152431Z1-086 GT3
50/50
33.46533.465
3152441Z1-086 ST
50/50
58.26658.266
957601AF2-054 C
Adder
-1.8-1.53
964211AG1-282 C
Adder
-1.7011764705882353-1.446
942001AE2-212 C
Adder
-2.010588235294118-1.709
3147223TWITTYS
50/50
1.2661.266
936261AD2-033 C
50/50
17.43217.432
936262AD2-033 E
50/50
11.62211.622
933291AC2-141 C
Adder
-32.203529411764706-27.373
934621AD1-088 C
50/50
21.36821.368
934622AD1-088 E
50/50
10.28810.288
316003AC1-222 C
50/50
1.7441.744
316034AC1-036 C
50/50
0.3110.311
316222AC1-221 C
50/50
2.6372.637
316237AB2-079 C O1
50/50
0.4550.455
316238AB2-078 C O1
50/50
0.4550.455
316239AB2-077 C O1
50/50
0.4550.455
316240AF1-291 C
Adder
-1.9317647058823528-1.642
316248AF1-058 C
50/50
0.5710.571
316283AC2-100 C
50/50
2.1162.116
927255AC1-221 E
50/50
6.9166.916
927264AC1-222 E
50/50
7.1497.149
932763AC2-100 E
50/50
4.6734.673
313527AB2-043 C
50/50
0.7110.711
924022AB2-043 E O1
50/50
7.1597.159
316123AC1-075 C
50/50
1.3531.353
925997AC1-075 E
50/50
4.7084.708
316205AC1-080 C
50/50
0.4520.452
926024AC1-080 E
50/50
1.5621.562
962561AG1-105 C
50/50
14.10814.108
962562AG1-105 E
50/50
9.4059.405
964241AG1-285 C
50/50
17.07617.076
964242AG1-285 E
50/50
11.38411.384
934611AD1-087 C
50/50
2.842.84
934612AD1-087 E
50/50
8.2238.223
935171AD1-152 C
50/50
2.8492.849
935172AD1-152 E
50/50
11.76211.762
936161AD2-022 C
Adder
12.15882352941176610.335
936162AD2-022 E
Adder
7.29529411764705856.201
936171AD2-023 C
Adder
7.0929411764705886.029
936172AD2-023 E
Adder
3.8505882352941183.273
937481AD2-202 C
50/50
0.8240.824
937482AD2-202 E
50/50
2.4072.407
938531AE1-072 C
Adder
-16.01294117647059-13.611
940641AE2-051 C
Adder
-21.040000000000003-17.884
942461AE2-259 C
Adder
12.19882352941176510.369
942462AE2-259 E
Adder
8.1329411764705886.913
944641AF1-129 C
Adder
-90.49176470588236-76.918
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
9.2639.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.06671.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.76444.764
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
170.641170.641
G-007PJM->LTFIMP_G-007
CMTX_NF
4.6814.681
NYPJM->LTFIMP_NY
CLTF
2.1082.108
LGEELTFEXP_LGEE->PJM
CLTF
2.7422.742
WECLTFEXP_WEC->PJM
CLTF
1.451.45
CPLELTFEXP_CPLE->PJM
CLTF
19.41719.417
TVALTFEXP_TVA->PJM
CLTF
11.71211.712
MECLTFEXP_MEC->PJM
CLTF
8.3488.348
LAGNLTFEXP_LAGN->PJM
CLTF
14.84614.846
SIGELTFEXP_SIGE->PJM
CLTF
0.5240.524
O66PJM->LTFIMP_O-066
CMTX_NF
29.75629.756

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:104.94 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3379.54
MW Contribution:10.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
963041AG1-153 C
50/50
4.3484.348
963042AG1-153 E
50/50
6.5226.522
3145413WATKINS
Adder
0.54117647058823540.46
944011AF1-069 C
50/50
10.20810.208
944012AF1-069 E
50/50
3.9663.966
941031AE2-094 C
50/50
31.24231.242
941032AE2-094 E
50/50
13.99213.992
957481AF2-042 C
Adder
12.04117647058823510.235
3145393UNCAMP
Adder
4.7823529411764714.065
916042Z1-036 E
Adder
22.54588235294117719.164
938771AE1-103 C
Adder
2.30941176470588251.963
938772AE1-103 E
Adder
3.18941176470588242.711
3143316POE
50/50
1.1011.101
3145256KINGFORK
Adder
0.81058823529411760.689
3145506HICKORY
Adder
1.7482352941176471.486
3150601CHESTF5
Adder
48.65647058823529441.358
3150651CHESTF6
Adder
14.8105882352941212.589
3150731STONECA
Adder
5.4305882352941184.616
3150831SPRUNCA
50/50
7.377.37
3150841SPRUNCB
50/50
7.377.37
3150921YORKTN3
Adder
92.9023529411764778.967
926662AC1-147 E
Adder
1.06470588235294120.905
926755AC1-161 E
50/50
10.44910.449
927226AC1-216 E
Adder
6.1082352941176475.192
935112AD1-144 E
Adder
0.75294117647058820.64
942341AE2-247 C
Adder
1.19529411764705881.016
942342AE2-247 E
Adder
1.65176470588235281.404
943461AF1-017 C
Adder
1.08235294117647070.92
943462AF1-017 E
Adder
1.76470588235294111.5
943612AF1-032 E
Adder
0.740.629
958502AF2-144 E
Adder
0.95058823529411770.808
3151021BRUNSWICKG1
50/50
6.3966.396
3151031BRUNSWICKG2
50/50
6.3966.396
3151041BRUNSWICKG3
50/50
6.3966.396
3151051BRUNSWICKS1
50/50
13.28713.287
3151081ELIZAR1
50/50
2.5662.566
3151091ELIZAR2
50/50
2.5212.521
3151101ELIZAR3
50/50
2.5992.599
3152251N ANNA1
50/50
47.55247.552
3152261N ANNA2
50/50
47.5747.57
3152411Z1-086 GT1
50/50
8.198.19
3152421Z1-086 GT2
50/50
8.1888.188
3152431Z1-086 GT3
50/50
8.1888.188
3152441Z1-086 ST
50/50
14.25614.256
316076AC2-137 E
Adder
0.99176470588235290.843
913392Y1-086 E
Adder
1.75294117647058821.49
916192Z1-068 E
Adder
1.51058823529411781.284
923832AB2-022 E
Adder
0.98941176470588230.841
923852AB2-025 E
Adder
0.90941176470588240.773
923862AB2-026 E
Adder
0.96705882352941170.822
925022AB2-158 E
50/50
4.8864.886
938552AE1-074 E
50/50
1.0491.049
938562AE1-075 E
Adder
0.82470588235294120.701
939312AE1-162 E
Adder
1.14235294117647060.971
946262AF1-291 E
Adder
1.14588235294117660.974
957492AF2-043 E
Adder
1.13882352941176480.968
962962AG1-145 E
Adder
1.10235294117647080.937
901082W1-029 E
Adder
25.35058823529411521.548
917122Z2-027 E
Adder
1.06941176470588250.909
925332AB2-190 E
Adder
6.3717647058823535.416
925522AC1-027 E
Adder
0.97764705882352940.831
942001AE2-212 C
50/50
1.7341.734
942002AE2-212 E
50/50
1.1561.156
957832AF2-077 E
Adder
1.07764705882352940.916
957871AF2-081 C
Adder
7.9988235294117666.799
957872AF2-081 E
Adder
3.42823529411764752.914
958161AF2-110 C
Adder
1.09411764705882360.93
958162AF2-110 E
Adder
1.74000000000000021.479
3138116ELKO L286
Adder
1.03411764705882360.879
933291AC2-141 C
50/50
24.47824.478
933292AC2-141 E
50/50
10.44910.449
939411AE1-173 C
50/50
72.77672.776
939412AE1-173 E
50/50
48.51748.517
934012AD1-025 E
Adder
7.9070588235294126.721
3146326AYDLETT TAP
Adder
1.08470588235294120.922
316160AE1-175 E
Adder
0.90941176470588240.773
316164AC1-076_C
50/50
0.8170.817
316169AC1-164 GEN
Adder
29.7105882352941225.254
316192AB2-158 C
50/50
1.8381.838
316233AE1-074 C
50/50
2.0822.082
316240AF1-291 C
Adder
1.721.462
316294AC1-161 C
50/50
3.9863.986
924516AB2-100 E1
Adder
2.21882352941176461.886
924517AB2-100 E2
Adder
2.21882352941176461.886
926785AC1-164_E
Adder
13.34823529411764811.346
934065AD1-033 E
Adder
4.0258823529411773.422
937226AE2-253 E
Adder
4.6788235294117653.977
926004AC1-076_E
50/50
4.684.68
919153AA1-139 E2
Adder
3.27058823529411762.78
919152AA1-139 E1
Adder
3.27058823529411762.78
924814AB2-134 E
Adder
10.004705882352948.504
316084AB2-161 E
Adder
4.4435294117647063.777
316044AC1-158 C1
50/50
14.72914.729
316045AC1-158 C2
50/50
14.72914.729
926739AC1-158 E1
50/50
38.52538.525
926740AC1-158 E2
50/50
38.52538.525
932046AC2-012 E
Adder
10.5364705882352958.956
316311AC2-079 C
Adder
4.5952941176470593.906
932596AC2-079 E
Adder
7.497647058823536.373
934576AD1-082 E
Adder
3.5411764705882353.01
316349AD2-085 C
Adder
2.7588235294117652.345
936666AD2-085 E
Adder
4.5011764705882353.826
961611AG1-000B C
Adder
12.62823529411764810.734
941591AE2-156 C
Adder
14.39882352941176612.239
944581AF1-123 C
50/50
36.58436.584
944582AF1-123 E
50/50
83.77383.773
944591AF1-124 C
50/50
36.71436.714
944592AF1-124 E
50/50
84.07784.077
944601AF1-125 C
50/50
36.02136.021
944602AF1-125 E
50/50
82.45882.458
944631AF1-128 C
Adder
30.4447058823529425.878
935161AD1-151 C
Adder
12.74823529411764710.836
935162AD1-151 E
Adder
8.4988235294117667.224
938531AE1-072 C
Adder
14.05529411764705811.947
938532AE1-072 E
Adder
7.3270588235294126.228
939191AE1-149 C
50/50
8.6438.643
939192AE1-149 E
50/50
5.7625.762
940431AE2-027 C
Adder
10.2917647058823528.748
940432AE2-027 E
Adder
6.8611764705882355.832
940481AE2-033 C
Adder
12.64705882352941110.75
940482AE2-033 E
Adder
8.5258823529411767.247
940541AE2-040 C
Adder
2.24941176470588241.912
940641AE2-051 C
50/50
13.8813.88
940642AE2-051 E
50/50
9.2539.253
941101AE2-104 C
Adder
2.68117647058823532.279
941102AE2-104 E
Adder
4.2623529411764713.623
944641AF1-129 C
Adder
81.343529411764769.142
3150851SPRUNCC
50/50
0.1320.132
3150861SPRUNCD
50/50
0.1320.132
316303AF2-085
50/50
3.2933.293
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
3.9113.911
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.47618.476
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.62115.621
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
69.2669.26
G-007PJM->LTFIMP_G-007
CMTX_NF
4.2794.279
NYPJM->LTFIMP_NY
CLTF
2.0512.051
LGEELTFEXP_LGEE->PJM
CLTF
0.8310.831
WECLTFEXP_WEC->PJM
CLTF
0.4010.401
CPLELTFEXP_CPLE->PJM
CLTF
8.2058.205
TVALTFEXP_TVA->PJM
CLTF
4.3954.395
MECLTFEXP_MEC->PJM
CLTF
2.5882.588
LAGNLTFEXP_LAGN->PJM
CLTF
5.5035.503
SIGELTFEXP_SIGE->PJM
CLTF
0.1630.163
O66PJM->LTFIMP_O-066
CMTX_NF
27.29527.295
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 568_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1                /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
313373 to 314765 ckt 1
313707 to 313373 ckt 1
314322 to 314914 ckt 1
314765 to 314749 ckt 1
314905 to 314900 ckt 1
314903 to 314908 ckt 1
314911 to 314905 ckt 1
314916 to 314913 ckt 1
314940 to 941030 ckt 1
314934 to 314916 ckt 1

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AG1-153 was evaluated as a 75.0 MW injection and 75.0 MW withdrawal in the Dominion area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC113.52 %678.68B770.464.4
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC106.87 %678.68B725.295.34
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC113.06 %678.68B767.34.4
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC106.41 %678.68B722.165.34

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.52 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:770.46
MW Contribution:4.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.06 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:814.82
MW Contribution:4.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.0258.025
3150651CHESTF6
80/20
3.3173.317
3150831SPRUNCA
80/20
1.4311.431
3150841SPRUNCB
80/20
1.4311.431
3156056W1-029WIND
80/20
0.5460.546
3156116Z1-036WIND
80/20
0.9860.986
901082W1-029 E
80/20
3.6623.662
916042Z1-036 E
80/20
6.626.62
916192Z1-068 E
80/20
0.2130.213
941032AE2-094 E
80/20
11.86611.866
944012AF1-069 E
80/20
3.8773.877
961942AG1-037 E
80/20
0.0860.086
963041AG1-153 C
80/20
1.7621.762
963042AG1-153 E
80/20
2.6422.642
916191Z1-068 C
80/20
0.030.03
961611AG1-000B C
80/20
1.5261.526
940541AE2-040 C
80/20
0.8680.868
941591AE2-156 C
80/20
5.0815.081
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
80/20
10.29210.292
944582AF1-123 E
80/20
23.56823.568
944591AF1-124 C
80/20
10.32910.329
944592AF1-124 E
80/20
23.65323.653
944601AF1-125 C
80/20
10.13310.133
944602AF1-125 E
80/20
23.19823.198
944631AF1-128 C
80/20
20.96620.966
944641AF1-129 C
80/20
30.36730.367
961612AG1-000B E
80/20
2.2892.289
316303AF2-085
80/20
1.8321.832
958502AF2-144 E
Adder
2.8294117647058822.405
943573AF1-028 BT
80/20
15.77615.776

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.87 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:725.29
MW Contribution:5.34
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.5 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:777.06
MW Contribution:5.55
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.4243.424
3150831SPRUNCA
80/20
1.4991.499
3150841SPRUNCB
80/20
1.4991.499
3151311EDGECMA
80/20
2.4292.429
3156056W1-029WIND
80/20
0.6050.605
3156116Z1-036WIND
80/20
1.11.1
901082W1-029 E
80/20
4.0534.053
916042Z1-036 E
80/20
7.3857.385
916192Z1-068 E
80/20
0.2340.234
941032AE2-094 E
80/20
14.50614.506
944012AF1-069 E
80/20
4.744.74
961942AG1-037 E
80/20
0.0980.098
963041AG1-153 C
80/20
2.1352.135
963042AG1-153 E
80/20
3.2023.202
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5981.598
940541AE2-040 C
80/20
1.0031.003
941591AE2-156 C
80/20
5.5525.552
943571AF1-028 C
Adder
-12.025882352941176-10.222
944581AF1-123 C
80/20
11.29511.295
944582AF1-123 E
80/20
25.86425.864
944591AF1-124 C
80/20
11.33511.335
944592AF1-124 E
80/20
25.95725.957
944601AF1-125 C
80/20
11.12111.121
944602AF1-125 E
80/20
25.45825.458
944641AF1-129 C
80/20
31.34631.346
961602AG1-000A E
80/20
1.8891.889
961612AG1-000B E
80/20
2.3972.397
316303AF2-085
80/20
2.1022.102
958502AF2-144 E
Adder
3.01882352941176452.566
943573AF1-028 BT
80/20
12.02612.026

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.06 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:767.3
MW Contribution:4.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.58 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:811.59
MW Contribution:4.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.0258.025
3150651CHESTF6
80/20
3.3173.317
3150831SPRUNCA
80/20
1.4311.431
3150841SPRUNCB
80/20
1.4311.431
3156056W1-029WIND
80/20
0.5460.546
3156116Z1-036WIND
80/20
0.9860.986
901082W1-029 E
80/20
3.6623.662
916042Z1-036 E
80/20
6.626.62
916192Z1-068 E
80/20
0.2130.213
941032AE2-094 E
80/20
11.86611.866
944012AF1-069 E
80/20
3.8773.877
961942AG1-037 E
80/20
0.0860.086
963041AG1-153 C
80/20
1.7621.762
963042AG1-153 E
80/20
2.6422.642
916191Z1-068 C
80/20
0.030.03
961611AG1-000B C
80/20
1.5261.526
940541AE2-040 C
80/20
0.8680.868
941591AE2-156 C
80/20
5.0815.081
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
80/20
10.29210.292
944582AF1-123 E
80/20
23.56823.568
944591AF1-124 C
80/20
10.32910.329
944592AF1-124 E
80/20
23.65323.653
944601AF1-125 C
80/20
10.13310.133
944602AF1-125 E
80/20
23.19823.198
944631AF1-128 C
80/20
20.96620.966
944641AF1-129 C
80/20
30.36730.367
961612AG1-000B E
80/20
2.2892.289
316303AF2-085
80/20
1.8321.832
958502AF2-144 E
Adder
2.8294117647058822.405
943573AF1-028 BT
80/20
15.77615.776

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.41 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:722.16
MW Contribution:5.34
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.03 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:773.89
MW Contribution:5.55
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.4243.424
3150831SPRUNCA
80/20
1.4991.499
3150841SPRUNCB
80/20
1.4991.499
3151311EDGECMA
80/20
2.4292.429
3156056W1-029WIND
80/20
0.6050.605
3156116Z1-036WIND
80/20
1.11.1
901082W1-029 E
80/20
4.0534.053
916042Z1-036 E
80/20
7.3857.385
916192Z1-068 E
80/20
0.2340.234
941032AE2-094 E
80/20
14.50614.506
944012AF1-069 E
80/20
4.744.74
961942AG1-037 E
80/20
0.0980.098
963041AG1-153 C
80/20
2.1352.135
963042AG1-153 E
80/20
3.2023.202
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5981.598
940541AE2-040 C
80/20
1.0031.003
941591AE2-156 C
80/20
5.5525.552
943571AF1-028 C
Adder
-12.025882352941176-10.222
944581AF1-123 C
80/20
11.29511.295
944582AF1-123 E
80/20
25.86425.864
944591AF1-124 C
80/20
11.33511.335
944592AF1-124 E
80/20
25.95725.957
944601AF1-125 C
80/20
11.12111.121
944602AF1-125 E
80/20
25.45825.458
944641AF1-129 C
80/20
31.34631.346
961602AG1-000A E
80/20
1.8891.889
961612AG1-000B E
80/20
2.3972.397
316303AF2-085
80/20
2.1022.102
958502AF2-144 E
Adder
3.01882352941176452.566
943573AF1-028 BT
80/20
12.02612.026
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC110.03 %661.76B728.154.39
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC101.32 %661.76B670.55.17
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC111.3 %661.76B736.514.39
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-A
SingleAC102.58 %661.76B678.835.17
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC108.36 %661.76B717.074.39

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.03 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:728.15
MW Contribution:4.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.398.39
3150651CHESTF6
80/20
3.4453.445
3150831SPRUNCA
80/20
1.4641.464
3150841SPRUNCB
80/20
1.4641.464
3156056W1-029WIND
80/20
0.5590.559
3156116Z1-036WIND
80/20
1.0071.007
901082W1-029 E
80/20
3.7483.748
916042Z1-036 E
80/20
6.7636.763
916192Z1-068 E
80/20
0.2190.219
941032AE2-094 E
80/20
11.9111.91
944012AF1-069 E
80/20
3.8913.891
961942AG1-037 E
80/20
0.0870.087
963041AG1-153 C
80/20
1.7571.757
963042AG1-153 E
80/20
2.6362.636
916191Z1-068 C
80/20
0.0310.031
961611AG1-000B C
80/20
1.5771.577
940541AE2-040 C
80/20
0.8830.883
941591AE2-156 C
80/20
5.2155.215
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
80/20
10.55910.559
944582AF1-123 E
80/20
24.1824.18
944591AF1-124 C
80/20
10.59710.597
944592AF1-124 E
80/20
24.26824.268
944601AF1-125 C
80/20
10.39710.397
944602AF1-125 E
80/20
23.823.8
944631AF1-128 C
80/20
21.92121.921
944641AF1-129 C
80/20
31.53431.534
961612AG1-000B E
80/20
2.3662.366
316303AF2-085
80/20
1.8091.809
958502AF2-144 E
Adder
2.68235294117647042.28
943573AF1-028 BT
80/20
15.50215.502

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.32 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:670.5
MW Contribution:5.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.3773.377
3150831SPRUNCA
80/20
1.4651.465
3150841SPRUNCB
80/20
1.4651.465
3151311EDGECMA
80/20
2.4182.418
3156056W1-029WIND
80/20
0.5910.591
3156116Z1-036WIND
80/20
1.0781.078
901082W1-029 E
80/20
3.9623.962
916042Z1-036 E
80/20
7.2357.235
916192Z1-068 E
80/20
0.2280.228
941032AE2-094 E
80/20
14.06514.065
944012AF1-069 E
80/20
4.5964.596
961942AG1-037 E
80/20
0.0970.097
963041AG1-153 C
80/20
2.072.07
963042AG1-153 E
80/20
3.1043.104
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5651.565
940541AE2-040 C
80/20
0.9830.983
941591AE2-156 C
80/20
5.4145.414
943571AF1-028 C
Adder
-11.711764705882354-9.955
944581AF1-123 C
80/20
11.01711.017
944582AF1-123 E
80/20
25.22825.228
944591AF1-124 C
80/20
11.05611.056
944592AF1-124 E
80/20
25.3225.32
944601AF1-125 C
80/20
10.84810.848
944602AF1-125 E
80/20
24.83224.832
944641AF1-129 C
80/20
30.90830.908
961602AG1-000A E
80/20
1.8811.881
961612AG1-000B E
80/20
2.3482.348
316303AF2-085
80/20
2.0152.015
958502AF2-144 E
Adder
2.84235294117647052.416
943573AF1-028 BT
80/20
11.71211.712

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.3 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:736.51
MW Contribution:4.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.398.39
3150651CHESTF6
80/20
3.4453.445
3150831SPRUNCA
80/20
1.4641.464
3150841SPRUNCB
80/20
1.4641.464
3156056W1-029WIND
80/20
0.5590.559
3156116Z1-036WIND
80/20
1.0071.007
901082W1-029 E
80/20
3.7483.748
916042Z1-036 E
80/20
6.7636.763
916192Z1-068 E
80/20
0.2190.219
941032AE2-094 E
80/20
11.9111.91
944012AF1-069 E
80/20
3.8913.891
961942AG1-037 E
80/20
0.0870.087
963041AG1-153 C
80/20
1.7571.757
963042AG1-153 E
80/20
2.6362.636
916191Z1-068 C
80/20
0.0310.031
961611AG1-000B C
80/20
1.5771.577
940541AE2-040 C
80/20
0.8830.883
941591AE2-156 C
80/20
5.2155.215
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
80/20
10.55910.559
944582AF1-123 E
80/20
24.1824.18
944591AF1-124 C
80/20
10.59710.597
944592AF1-124 E
80/20
24.26824.268
944601AF1-125 C
80/20
10.39710.397
944602AF1-125 E
80/20
23.823.8
944631AF1-128 C
80/20
21.92121.921
944641AF1-129 C
80/20
31.53431.534
961612AG1-000B E
80/20
2.3662.366
316303AF2-085
80/20
1.8091.809
958502AF2-144 E
Adder
2.68235294117647042.28
943573AF1-028 BT
80/20
15.50215.502

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.58 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:678.83
MW Contribution:5.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150651CHESTF6
80/20
3.3773.377
3150831SPRUNCA
80/20
1.4651.465
3150841SPRUNCB
80/20
1.4651.465
3151311EDGECMA
80/20
2.4182.418
3156056W1-029WIND
80/20
0.5910.591
3156116Z1-036WIND
80/20
1.0781.078
901082W1-029 E
80/20
3.9623.962
916042Z1-036 E
80/20
7.2357.235
916192Z1-068 E
80/20
0.2280.228
941032AE2-094 E
80/20
14.06514.065
944012AF1-069 E
80/20
4.5964.596
961942AG1-037 E
80/20
0.0970.097
963041AG1-153 C
80/20
2.072.07
963042AG1-153 E
80/20
3.1043.104
916191Z1-068 C
80/20
0.0330.033
961611AG1-000B C
80/20
1.5651.565
940541AE2-040 C
80/20
0.9830.983
941591AE2-156 C
80/20
5.4145.414
943571AF1-028 C
Adder
-11.711764705882354-9.955
944581AF1-123 C
80/20
11.01711.017
944582AF1-123 E
80/20
25.22825.228
944591AF1-124 C
80/20
11.05611.056
944592AF1-124 E
80/20
25.3225.32
944601AF1-125 C
80/20
10.84810.848
944602AF1-125 E
80/20
24.83224.832
944641AF1-129 C
80/20
30.90830.908
961602AG1-000A E
80/20
1.8811.881
961612AG1-000B E
80/20
2.3482.348
316303AF2-085
80/20
2.0152.015
958502AF2-144 E
Adder
2.84235294117647052.416
943573AF1-028 BT
80/20
11.71211.712

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.36 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:717.07
MW Contribution:4.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
80/20
8.398.39
3150651CHESTF6
80/20
3.4453.445
3150831SPRUNCA
80/20
1.4641.464
3150841SPRUNCB
80/20
1.4641.464
3156056W1-029WIND
80/20
0.5590.559
3156116Z1-036WIND
80/20
1.0071.007
901082W1-029 E
80/20
3.7483.748
916042Z1-036 E
80/20
6.7636.763
916192Z1-068 E
80/20
0.2190.219
941032AE2-094 E
80/20
11.9111.91
944012AF1-069 E
80/20
3.8913.891
961942AG1-037 E
80/20
0.0870.087
963041AG1-153 C
80/20
1.7571.757
963042AG1-153 E
80/20
2.6362.636
916191Z1-068 C
80/20
0.0310.031
961611AG1-000B C
80/20
1.5771.577
940541AE2-040 C
80/20
0.8830.883
941591AE2-156 C
80/20
5.2155.215
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
80/20
10.55910.559
944582AF1-123 E
80/20
24.1824.18
944591AF1-124 C
80/20
10.59710.597
944592AF1-124 E
80/20
24.26824.268
944601AF1-125 C
80/20
10.39710.397
944602AF1-125 E
80/20
23.823.8
944631AF1-128 C
80/20
21.92121.921
944641AF1-129 C
80/20
31.53431.534
961612AG1-000B E
80/20
2.3662.366
316303AF2-085
80/20
1.8091.809
958502AF2-144 E
Adder
2.68235294117647042.28
943573AF1-028 BT
80/20
15.50215.502
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
313373 to 314765 ckt 1
313707 to 313373 ckt 1
314765 to 314749 ckt 1

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC108.48 %678.68B736.224.4
GD1DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC108.04 %678.68B733.224.4

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.48 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:736.22
MW Contribution:4.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.77 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:772.11
MW Contribution:4.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.0247058823529426.821
3150651CHESTF6
Adder
3.3176470588235292.82
3150831SPRUNCA
Adder
1.43058823529411771.216
3150841SPRUNCB
Adder
1.43058823529411771.216
3156116Z1-036WIND
Adder
0.98588235294117640.838
916042Z1-036 E
Adder
6.625.627
941032AE2-094 E
Adder
11.86588235294117810.086
944012AF1-069 E
Adder
3.87764705882352923.296
961942AG1-037 E
Adder
0.085882352941176470.073
963041AG1-153 C
Adder
1.76117647058823561.497
963042AG1-153 E
Adder
2.6423529411764712.246
961611AG1-000B C
Adder
1.52588235294117651.297
940541AE2-040 C
Adder
0.86823529411764710.738
941591AE2-156 C
Adder
5.0811764705882354.319
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
Adder
10.2917647058823528.748
944582AF1-123 E
Adder
23.5682352941176520.033
944591AF1-124 C
Adder
10.3282352941176478.779
944592AF1-124 E
Adder
23.65294117647058820.105
944601AF1-125 C
Adder
10.1341176470588248.614
944602AF1-125 E
Adder
23.1976470588235319.718
944631AF1-128 C
Adder
20.9658823529411817.821
944641AF1-129 C
Adder
30.36705882352941525.812
961612AG1-000B E
Adder
2.28823529411764741.945
316303AF2-085
Adder
2.1552941176470591.832
958502AF2-144 E
Adder
2.8294117647058822.405

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:108.04 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:733.22
MW Contribution:4.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:113.32 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:769.11
MW Contribution:4.75
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.0247058823529426.821
3150651CHESTF6
Adder
3.3176470588235292.82
3150831SPRUNCA
Adder
1.43058823529411771.216
3150841SPRUNCB
Adder
1.43058823529411771.216
3156116Z1-036WIND
Adder
0.98588235294117640.838
916042Z1-036 E
Adder
6.625.627
941032AE2-094 E
Adder
11.86588235294117810.086
944012AF1-069 E
Adder
3.87764705882352923.296
961942AG1-037 E
Adder
0.085882352941176470.073
963041AG1-153 C
Adder
1.76117647058823561.497
963042AG1-153 E
Adder
2.6423529411764712.246
961611AG1-000B C
Adder
1.52588235294117651.297
940541AE2-040 C
Adder
0.86823529411764710.738
941591AE2-156 C
Adder
5.0811764705882354.319
943571AF1-028 C
Adder
-15.776470588235295-13.41
944581AF1-123 C
Adder
10.2917647058823528.748
944582AF1-123 E
Adder
23.5682352941176520.033
944591AF1-124 C
Adder
10.3282352941176478.779
944592AF1-124 E
Adder
23.65294117647058820.105
944601AF1-125 C
Adder
10.1341176470588248.614
944602AF1-125 E
Adder
23.1976470588235319.718
944631AF1-128 C
Adder
20.9658823529411817.821
944641AF1-129 C
Adder
30.36705882352941525.812
961612AG1-000B E
Adder
2.28823529411764741.945
316303AF2-085
Adder
2.1552941176470591.832
958502AF2-144 E
Adder
2.8294117647058822.405
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1DVP
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC103.72 %661.76B686.414.39
GD1DVP
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC105.01 %661.76B694.914.39
GD1DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
OPAC102.08 %661.76B675.514.39

Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:103.72 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:686.41
MW Contribution:4.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.3894117647058837.131
3150651CHESTF6
Adder
3.44470588235294132.928
3150831SPRUNCA
Adder
1.46470588235294131.245
3150841SPRUNCB
Adder
1.46470588235294131.245
3156116Z1-036WIND
Adder
1.00705882352941180.856
916042Z1-036 E
Adder
6.7623529411764715.748
941032AE2-094 E
Adder
11.90941176470588110.123
944012AF1-069 E
Adder
3.8917647058823533.308
961942AG1-037 E
Adder
0.087058823529411760.074
963041AG1-153 C
Adder
1.75764705882352961.494
963042AG1-153 E
Adder
2.63647058823529432.241
961611AG1-000B C
Adder
1.57764705882352941.341
940541AE2-040 C
Adder
0.88352941176470590.751
941591AE2-156 C
Adder
5.2152941176470584.433
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
Adder
10.568.976
944582AF1-123 E
Adder
24.18000000000000320.553
944591AF1-124 C
Adder
10.5964705882352939.007
944592AF1-124 E
Adder
24.2670588235294120.627
944601AF1-125 C
Adder
10.3964705882352948.837
944602AF1-125 E
Adder
23.820.23
944631AF1-128 C
Adder
21.92117647058823618.633
944641AF1-129 C
Adder
31.5341176470588226.804
961612AG1-000B E
Adder
2.36588235294117682.011
316303AF2-085
Adder
2.12823529411764721.809
958502AF2-144 E
Adder
2.68235294117647042.28

Details for 6FORK UNION-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6CUNNING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:105.01 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:694.91
MW Contribution:4.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.3894117647058837.131
3150651CHESTF6
Adder
3.44470588235294132.928
3150831SPRUNCA
Adder
1.46470588235294131.245
3150841SPRUNCB
Adder
1.46470588235294131.245
3156116Z1-036WIND
Adder
1.00705882352941180.856
916042Z1-036 E
Adder
6.7623529411764715.748
941032AE2-094 E
Adder
11.90941176470588110.123
944012AF1-069 E
Adder
3.8917647058823533.308
961942AG1-037 E
Adder
0.087058823529411760.074
963041AG1-153 C
Adder
1.75764705882352961.494
963042AG1-153 E
Adder
2.63647058823529432.241
961611AG1-000B C
Adder
1.57764705882352941.341
940541AE2-040 C
Adder
0.88352941176470590.751
941591AE2-156 C
Adder
5.2152941176470584.433
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
Adder
10.568.976
944582AF1-123 E
Adder
24.18000000000000320.553
944591AF1-124 C
Adder
10.5964705882352939.007
944592AF1-124 E
Adder
24.2670588235294120.627
944601AF1-125 C
Adder
10.3964705882352948.837
944602AF1-125 E
Adder
23.820.23
944631AF1-128 C
Adder
21.92117647058823618.633
944641AF1-129 C
Adder
31.5341176470588226.804
961612AG1-000B E
Adder
2.36588235294117682.011
316303AF2-085
Adder
2.12823529411764721.809
958502AF2-144 E
Adder
2.68235294117647042.28

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:OP
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:675.51
MW Contribution:4.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
3150601CHESTF5
Adder
8.3894117647058837.131
3150651CHESTF6
Adder
3.44470588235294132.928
3150831SPRUNCA
Adder
1.46470588235294131.245
3150841SPRUNCB
Adder
1.46470588235294131.245
3156116Z1-036WIND
Adder
1.00705882352941180.856
916042Z1-036 E
Adder
6.7623529411764715.748
941032AE2-094 E
Adder
11.90941176470588110.123
944012AF1-069 E
Adder
3.8917647058823533.308
961942AG1-037 E
Adder
0.087058823529411760.074
963041AG1-153 C
Adder
1.75764705882352961.494
963042AG1-153 E
Adder
2.63647058823529432.241
961611AG1-000B C
Adder
1.57764705882352941.341
940541AE2-040 C
Adder
0.88352941176470590.751
941591AE2-156 C
Adder
5.2152941176470584.433
943571AF1-028 C
Adder
-15.50235294117647-13.177
944581AF1-123 C
Adder
10.568.976
944582AF1-123 E
Adder
24.18000000000000320.553
944591AF1-124 C
Adder
10.5964705882352939.007
944592AF1-124 E
Adder
24.2670588235294120.627
944601AF1-125 C
Adder
10.3964705882352948.837
944602AF1-125 E
Adder
23.820.23
944631AF1-128 C
Adder
21.92117647058823618.633
944641AF1-129 C
Adder
31.5341176470588226.804
961612AG1-000B E
Adder
2.36588235294117682.011
316303AF2-085
Adder
2.12823529411764721.809
958502AF2-144 E
Adder
2.68235294117647042.28
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
313373 to 314765 ckt 1
313707 to 313373 ckt 1
314765 to 314749 ckt 1

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 1 Cluster 47 are listed in Table 1 below. This report will cover the TC1 Phase 3 dynamic analysis of Cluster 47 projects.

 

Table 1: Transition Cycle 1 Cluster 47 Projects

Cluster

Project

Fuel Type

Transmission Owner

MFO (MW)

MWE (MW)

MWC (MW)

Point of Interconnection

47

AG1-153

Battery

Dominion

75

75

30

Heritage 500 kV

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 47 projects will meet the dynamics requirements of the NERC, Dominion Energy, and PJM reliability standards.

 

The load flow case finalized for Phase 2 was used as a starting point and was updated based on latest Cluster 47 data, Dominion Energy recommended transmission changes and withdrawn generation. Projects in vicinity of Cluster 47 have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer. The dynamic models for Cluster 42 projects were updated based on the latest DP2 data and include any tuning adjustments recommended during Phase 2.

 

Cluster 47 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. 97 contingencies were studied, each with a 30 second simulation time period. The studied contingencies included:

 

  • Steady-state operation (30 seconds)
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults with delayed clearing at remote end
  • Three-phase faults with loss of multiple-circuit tower line.

 

The contingencies were updated based on topology changes due to any Dominion Energy recommended transmission changes or generation withdrawals.

 

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all of the fault contingencies tested on the RTEP 2027 summer peak case:

 

 

AG1-153 queue project did not meet the power factor 0.95 lagging measured at the high side of the transformer and it is deficient by 3.85 MVAR. AG1-153 queue project met the 0.95 leading power factor requirements.

 

The result of the analysis for Cluster 47 projects met all evaluation criteria for all the contingencies. No mitigation was required. There were minor reactive drift from AG1-153 that could be tuned by developer to improve performance.

 

AE1-173:

AE1-173, a nearby generator tripped for under voltage protection for voltages under 0.64 p.u for 0.31 seconds. The unit rode through all contingencies when pickup time was increased to 0.4375 seconds. The generator owner should be contacted to confirm if the revised setting is within plants capability and/or tune the model’s recovery.

 

AB2-169:

AB2-169, nearby generator, tripped for over voltage protection for voltages over 1.25 p.u. for 0.0 seconds. The unit rode through all contingencies when pickup time was increased to 0.0125 seconds.  The generator owner should be contacted to confirm if the revised setting is within plants capability and/or tune the model’s recovery.

Reactive Power Analysis

The reactive power capability of AG1-153 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-065Earleys 230kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-088Boykins-Handsome 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB1-173Brink-Trego 115kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-100Clubhouse-Lakeview 230kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-080Perth-Hickory Grove 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-216Hopewell-Surry 230kVIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-084Dawson-South Justice 115kVPartially in Service - Under Construction
AC2-100Halifax-Person 230kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVPartially in Service - Under Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-149Disputanta-Poe 115 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-247Myrtle-Windsor 115 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-346Ahoskie 34.5 kVIn Service
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-028Endless Caverns 115 kVUnder Construction
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-299Fields 34.5 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
V4-068Murphy's 34.5kVIn Service
W1-029Winfall 230kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z1-068Birdneck 34.5kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-088Tarboro-Everetts 230kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 312.A.1.b and as outlined in PJM Manual 14H, Section 13, in Phase III of the Cycle, PJM coordinates with the Affected System Operators to conduct any studies required to determine the impact of the New Service Request on any Affected System and will include the Affected System Study results in Phase III System Impact Study, if available from the Affected System Operator.

If your project required an Affected System Study, the results are shown below from the Affected System Operator.

For more details, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM will list any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG1-153 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn9378.0Replace existing 230/500 kV Carson transformer 2 with (4)-480 MVA single phase transformers.Cost Allocated$1,759,557
Dominionb4000.315Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.Contingent$0N/A
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Non-Contingent$0N/A
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Non-Contingent$0N/A
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Non-Contingent$0N/A
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Non-Contingent$0N/A
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Non-Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Non-Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Non-Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Non-Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Non-Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Non-Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationNon-Contingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0N/A
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Non-Contingent$0N/A
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Non-Contingent$0N/A
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Non-Contingent$0N/A
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Non-Contingent$0N/A
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Non-Contingent$0N/A
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Non-Contingent$0N/A
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Non-Contingent$0N/A
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Non-Contingent$0N/A
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Non-Contingent$0N/A
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Non-Contingent$0N/A
Dominionn8492.1Two Breaker Additions at Fentress Substation.Non-Contingent$0N/A
Grand Total:$1,759,557

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9378.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9378.0 / TC1-PH3-DOM-010
Title
Replace existing 230/500 kV Carson transformer 2 with (4)-480 MVA single phase transformers.
Description
Replace Existing 230/500 kV Carson transformer 2 with (4)-480 MVA Single Phase transformers.
Total Cost ($USD)
$37,801,301
Discounted Total Cost ($USD)
$37,801,301
Allocated Cost ($USD)
$1,759,557
Time Estimate
Dec 31 2029

Contributor

FacilityContingency
6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
LLA2016.0 MVA
LLB2083.0 MVA
LLC2239.0 MVA
SUMA1707.0 MVA
SUMB1758.0 MVA
SUMC1873.0 MVA
WINA2196.0 MVA
WINB2228.0 MVA
WINC2308.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.2 MW22.4%$8,456,365
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
56.5 MW22.5%$8,486,733
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
55.4 MW22.0%$8,324,368
AF2-04259.5 MW23.7%$8,947,219
AF2-22212.2 MW4.8%$1,827,058
AG1-15311.7 MW4.7%$1,759,557

System Reinforcement: n9112.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9112.0 / TC1-PH2-DOM-063
Title
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Description
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Total Cost ($USD)
$87,030,447
Discounted Total Cost ($USD)
$87,030,447
Allocated Cost ($USD)
$0
Time Estimate
46 to 47 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A797.0 MVA
(All)B797.0 MVA
(All)C1115.0 MVA

System Reinforcement: n9265.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9265.0 / TC1-PH2-DOM-064
Title
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Description
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Total Cost ($USD)
$396,021
Discounted Total Cost ($USD)
$396,021
Allocated Cost ($USD)
$0
Time Estimate
14 to 15 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A876.0 MVA
(All)B956.0 MVA
(All)C1163.0 MVA

System Reinforcement: n9681.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9681.0
Title
Upgrade 1.04 Miles of 230kV transmission line 249 from 249/86 to 249/93
Description
Reconductor 1.04 miles of 2*636 ACSR 24/7 MOT 150 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" MOT 250 on 230 kV line 249 between Carson and Chaparral
Total Cost ($USD)
$3,042,004
Discounted Total Cost ($USD)
$3,042,004
Allocated Cost ($USD)
$0
Time Estimate
20 to 21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1442.0 MVA
LLB1540.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1493.0 MVA
WINB1587.0 MVA
WINC1631.0 MVA

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1047.0 MVA
(All)B1047.0 MVA
(All)C1204.0 MVA
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / dom-369
Title
ELIM FOR TC1: Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C and replace line lead at Mt. Eagle.
Description
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C and replace line lead at Mt. Eagle.
Total Cost ($USD)
$36,802,018
Discounted Total Cost ($USD)
$36,802,018
Allocated Cost ($USD)
$0
Time Estimate
43 to 44 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A781.0 MVA
(All)B796.0 MVA
(All)C909.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-008
Title
ELIMINATED FOR TC1: Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Description
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Total Cost ($USD)
$29,539,973
Discounted Total Cost ($USD)
$29,539,973
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
6CUNNING-6FORK UNION 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1046.0 MVA
(All)B1046.0 MVA
(All)C1203.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / dom-490
Title
ELIMINATED FOR TC1: Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.
Description
Uograde 3.78 miles of transmission line 2028 between Mt. Eagle and Grape Vine with (2) 768.2 ACSS/TW (20/7) "MAUMEE". The segment runs from Mt Eagle to structure 2080/73.
Total Cost ($USD)
$13,360,242
Discounted Total Cost ($USD)
$13,360,242
Allocated Cost ($USD)
$0
Time Estimate
43 to 44 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A721.0 MVA
(All)B721.0 MVA
(All)C829.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH3-DOM-006
Title
ELIM FOR TC1: Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.
Description
Rebuild a 2.73 mile segment of 230kV line 2028 between Mt. Eagle and Grape Vinew with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @250 degrees C.
Total Cost ($USD)
$8,415,380
Discounted Total Cost ($USD)
$8,415,380
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1174.0 MVA
(All)B1302.0 MVA
(All)C1360.0 MVA

System Reinforcement: n9199.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9199.0 / TC1-PH2-DOM-004
Title
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Description
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Total Cost ($USD)
$7,947,612
Discounted Total Cost ($USD)
$7,947,612
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA956.0 MVA
LLB1011.0 MVA
LLC1091.0 MVA
SUMA782.0 MVA
SUMB870.0 MVA
SUMC910.0 MVA
WINA979.0 MVA
WINB1043.0 MVA
WINC1115.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA956.0 MVA
LLB1011.0 MVA
LLC1091.0 MVA
SUMA782.0 MVA
SUMB870.0 MVA
SUMC910.0 MVA
WINA979.0 MVA
WINB1043.0 MVA
WINC1115.0 MVA

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Discounted Total Cost ($USD)
$37,836,293
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not ContingentTopology Changing

Note 1: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.315
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.315
Title
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Description
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Apr 22 2030

Contingent

Note: Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 may need this upgrade in-service to be deliverable to the PJM system. If AG1-153 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Discounted Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b3692
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3692
Title
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.
Description
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy with current 500 kV standards construction practices to achieve a summer rating of 4330 MVA. Projected ISD: 06/01/2026
Cost Information
Time Estimate
Jun 01 2026

Not Contingent

Note: AG1-153 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-153 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4330.0 MVA
(All)B4330.0 MVA
(All)C5011.0 MVA

System Reinforcement: n9264.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9264.0 / TC1-PH1-DOM-080
Title
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Description
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Total Cost ($USD)
$582,006
Discounted Total Cost ($USD)
$582,006
Allocated Cost ($USD)
$0
Time Estimate
12 to 13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2650.0 MVA
(All)B2831.0 MVA
(All)C3663.0 MVA

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Discounted Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
ELIM TC1: Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Discounted Total Cost ($USD)
$111,130,292
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
ELIM TC1: Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Discounted Total Cost ($USD)
$108,728,086
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
No new ratings for this Flowgate.
8ROGERS RD-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-040
Title
ELIM TC1: Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) Dipper at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 18.75 miles of Line 594 between Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$128,018,212
Discounted Total Cost ($USD)
$128,018,212
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n9247.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9247.0 / TC1-PH2-DOM-041
Title
ELIM TC1: Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work (new rating: 4356/4356/5009 MVA)
Description
Wreck and rebuild 14.02 miles of Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA
Total Cost ($USD)
$99,636,684
Discounted Total Cost ($USD)
$99,636,684
Allocated Cost ($USD)
$0
Time Estimate
48 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AG1-153 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-153 could receive cost allocation. Although AG1-153 may not presently have cost responsibility for this upgrade, AG1-153 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4356.0 MVA
(All)B4356.0 MVA
(All)C5009.0 MVA

System Reinforcement: n8492.2

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Allocated Cost ($USD)
$0
Time Estimate
15 to 16 Months
Cost Alloc Type
Non-Contingent

System Reinforcement: n9259.0

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.
Total Cost ($USD)
$25,304,902
Allocated Cost ($USD)
$0
Time Estimate
38 to 39 Months
Cost Alloc Type
Non-Contingent

System Reinforcement: n9267.0

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months
Cost Alloc Type
Non-Contingent

System Reinforcement: n9630.0

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029
Cost Alloc Type
Non-Contingent

System Reinforcement: b4000.325

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: s3047.2

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s3047.2
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3047.2
Title
Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.
Description
Install (2) 1400 MVA 500-230 kV transformers and associated 500 kV and 230 kV equipment (breakers, switches, leads) at Vint Hill Substation to supply the area with a 500 kV source Cut and loop 500 kV line #535 Loudoun – Meadowbrook and #569 Loudoun - Morrisville as the 500 kV sources into the proposed 500 kV ring bus Vint Hill Substation will be expanded to the north of the existing site to accommodate the 500 kV ring required for the addition of the new transformers Existing terminations for 230 kV line #2174 Wheeler – Vint Hill, line #2101 Bristers – Vint Hill, and line #2163 Liberty – Vint Hill will be rearranged to terminate into the expanded Vint Hill Substation 230 kV line #2114 Remington CT – Rollins Ford will also be cut and looped into the expanded Vint Hill Substation due to spatial constraints along the existing right-of-way.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.312

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.313

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.313
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.313
Title
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Description
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.356

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.356
Title
Build a new 500 kV line from Vint Hill to Wishing Star.
Description
Build a new 500kV line from Vint Hill to Wishing Star. The line will be supported on single circuit monopoles. New conductor to have a summer rating of 4357 MVA. Line length is approximately 16.59 miles
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.357

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.357
Title
Build a new 500 kV line from Morrisville to Vint Hill.
Description
Build a new 500kV line from Morrisville to Vint Hill. New conductor to have a summer rating of 4357 MVA. Line length is approximately 19.71 miles.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: b3800.354

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.354
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.354
Title
Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.
Description
Install terminal equipment at Wishing Star substation to support a 5000A line to Vint Hill. Update relay settings for 500kV Lines #546 and #590.
Cost Information
Cost Alloc Type
Non-Contingent

System Reinforcement: n8492

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Allocated Cost ($USD)
$0
Time Estimate
26 to 27 Months
Cost Alloc Type
Non-Contingent

System Reinforcement: n8492.1

AG1-153 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months
Cost Alloc Type
Non-Contingent

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG1-153


AG1-153 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AG1-153 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Dominionn8492.2Expand Yadkin Substation to accommodate the new 500 kV line.Non-Contingent$0
Dominionn9259.0Install two 230 kV gas insulated switchgear ("GIS") bus ties at the Fentress 230 kV substation.Non-Contingent$0
Dominionn9267.0Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.Non-Contingent$0
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Non-Contingent$0
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Non-Contingent$0
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.Non-Contingent$0
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.Non-Contingent$0
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.Non-Contingent$0
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.Non-Contingent$0
Dominionb4000.348Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Non-Contingent$0
Dominionb4000.346Cut-in 500kV line from Kraken substation into Yeat substationNon-Contingent$0
Dominionb4000.345Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.Non-Contingent$0
Dominionb4000.325Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.Non-Contingent$0
Dominionb4000.326At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.Non-Contingent$0
Dominionb4000.327Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.Non-Contingent$0
Dominions3047.2Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.Non-Contingent$0
Dominionb3800.312Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.Non-Contingent$0
Dominionb3800.313Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.Non-Contingent$0
Dominionb3800.356Build a new 500 kV line from Vint Hill to Wishing Star.Non-Contingent$0
Dominionb3800.357Build a new 500 kV line from Morrisville to Vint Hill.Non-Contingent$0
Dominionb3800.354Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.Non-Contingent$0
Dominionn8492Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.Non-Contingent$0
Dominionn8492.1Two Breaker Additions at Fentress Substation.Non-Contingent$0
Region Topology Upgrade Total:$0

Attachments

AG1-153 One Line Diagram

AG1-153 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.