AG1-447 Final System Impact Study (Retool 1) Report

v1.00 released 2025-12-08 18:22

Olive-University Park 345 kV

55.0 MW Capacity / 55.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is RWE Solar Development, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is AEP Indiana Michigan Transmission Company, Inc..

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the TC1 projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.
Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of TC1 projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the AEP Indiana Michigan Transmission Company, Inc. zone — LaPorte County, Indiana. This project is an increase to the developer’s AF2-359/AG1-436 project(s), which will share the same Point of Interconnection. The AG1-447 project is a 55.0 MW uprate (55.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 305.0 MW with 205.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG1-447
Project Name:
Olive-University Park 345 kV
Project Developer Name:
RWE Solar Development, LLC
State:
Indiana
County:
LaPorte
Transmission Owner:
AEP Indiana Michigan Transmission Company, Inc.
MFO:
305.0
MWE:
55.0
MWC:
55.0
Battery Storage Specification:
220.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2027

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG1-447 will interconnect on the AEP Indiana Michigan Transmission Company, Inc. transmission system as an uprate to AF2-359 tapping the Olive to University Park 345 kV line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AG1-447 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AG1-447Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$138,247$138,247
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$60,764$60,764
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$291,870$0
Total$490,881$199,011

* Contributes to calculation for Security. See Security Section of this report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF2-359/AG1-436/AG1-447

Security has been calculated for the AF2-359/AG1-436/AG1-447 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF2-359/AG1-436/AG1-447
Project(s): AF2-359/AG1-436/AG1-447
Final Agreement Security (A): $3,007,904
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $3,007,904
Security on Hand with PJM (D): $3,007,904
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

AG1-447 will interconnect with the AEP transmission system as an uprate to a previous interconnection at the Olive - University Park 345 kV Station. The estimates provided in this report are preliminary in nature, as they were determined without the benefit of detailed engineering studies. Final estimates will require an on-site review and coordination to determine final construction requirements.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9567.0

Proposed AF2-359 345 kV Station: Review and revise the protective relay settings at the AF2-359 proposed 345 kV Station to account for the additional generation of AG1-436. o Settings will need to be revised for each generation project (AG1-436 & AG1-447) unless they share an in-service date.

$36,901$7,080$14,081$2,702$60,764$30,382 (See Note 1)
n9566.0

Proposed AF2-359 345 kV Station: Review and revise the protective relay settings at the AF2-359 proposed 345 kV Station to account for the additional generation of AG1-447. o Settings will need to be revised for each generation project (AG1-436 & AG1-447) unless they share an in-service date.

$36,901$7,080$14,081$2,702$60,764$30,382 (See Note 1)
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

AG1-436 Transmission Owner Interconnection Facilities. • IMTCo will procure one (1) metering panel with three (3) primary meters and two (2) ethernet switches to be installed by the Project Developer in the AG1-436 and AG1-447 Project Developer's collector stations. • IMTCo will procure one (1) connected grid router ("CGR") to be installed by the Project Developer in the Project Developer's originating project collector station (AF2-359).

$106,608$51,442$23,199$12,553$193,802$96,901 (See Note 1)
(Pending)

AG1-447 Transmission Owner Interconnection Facilities. • IMTCo will procure one (1) metering panel with three (3) primary meters and two (2) ethernet switches to be installed by the Project Developer in the AG1-436 and AG1-447 Project Developer's collector stations. • IMTCo will procure one (1) CGR to be installed by the Project Developer in the Project Developer's originating project collector station (AF2-359).

$48,465$21,971$8,433$3,823$82,692$41,346 (See Note 1)

Based on the scope of work for the Interconnection Facilities, it is expected to take 4 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

The minimum and maximum schedules reflect the amount of time (in months) that AEP projects their portion of the construction project scope elapsing from the time of agreement assuming commercial operation of the preceding project has been achieved. The minimum schedule assumes that the Transmission Owners only scope of work is review and revision of relay settings at the interconnection station. The maximum schedule assumes the need for additional work being required at the interconnection station.  Any material ordering or construction work done prior to Engineering and Procurement or Generation Interconnection Agreements is done solely at the Project Developers risk. There is a potential that any work done or materials ordered prior to agreements and the ensuing detailed engineering processes does not meet AEP specifications, resulting in rejection of the completed work.

Transmission Owner Analysis

No Transmission Owner impacts identified.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG1-447 was evaluated as a 55.0 MW (55.0 MW Capacity) injection in the AEP area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP
05DUMONT-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC111.6 %4142.0B4622.3212.78
GD1AEP
05DUMONT-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC100.33 %4142.0B4155.8111.54
GD1AEP
05SORENS-05MARYSV 765.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC102.72 %4142.0B4254.8513.88
GD1ATSI/METC
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-022T_SRT-A-1_SENS
TowerAC111.87 %1793.0B2005.864.81

Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.6 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4622.32
MW Contribution:12.78
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.12 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4643.96
MW Contribution:13.1
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
4.9294117647058834.19
962781AG1-127 C
Adder
12.98470588235294311.037
962782AG1-127 E
Adder
8.6411764705882357.345
965681AG1-436 C
Adder
17.43176470588235514.817
965682AG1-436 E
Adder
11.6211764705882359.878
966091AG1-478 C
Adder
3.71294117647058863.156
966092AG1-478 E
Adder
0.93411764705882360.794
966441AG1-513 C
Adder
0.93411764705882360.794
966442AG1-513 E
Adder
1.40117647058823551.191
24796705OLIV SLR E
Adder
0.56117647058823530.477
290021O50 E
Adder
35.73058823529411430.371
290051GSG-6; E
Adder
19.6129411764705916.671
295109WESTBROOK E
Adder
10.5011764705882368.926
295111SUBLETTE E
Adder
5.1047058823529424.339
910542X3-005 E
Adder
1.32588235294117651.127
918052AA1-018 E OP
Adder
29.625.16
933911AD1-013 C
Adder
3.45176470588235332.934
933912AD1-013 E
Adder
5.5141176470588244.687
934721AD1-100 C
50/50
5.4585.458
934722AD1-100 E
50/50
165.829165.829
937002AD2-134 E
Adder
18.96352941176470716.119
958481AF2-142 C
Adder
20.41411764705882317.352
958482AF2-142 E
Adder
13.60941176470588211.568
958491AF2-143 C
Adder
20.1317647058823517.112
958492AF2-143 E
Adder
13.42117647058823411.408
959351AF2-226 C
Adder
4.5435294117647063.862
959352AF2-226 E
Adder
6.8141176470588245.792
960281AF2-319 C
Adder
4.5435294117647063.862
960282AF2-319 E
Adder
6.8141176470588245.792
960582AF2-349 E
Adder
67.176470588235357.1
960681AF2-359 C
Adder
17.43176470588235514.817
960682AF2-359 E
Adder
11.6211764705882359.878
960751AF2-366 C
Adder
12.94823529411764811.006
960752AF2-366 E
Adder
8.6317647058823527.337
24344105CKG2
50/50
60.20560.205
274660LASCO STA;1U
50/50
44.08644.086
274661LASCO STA;2U
50/50
44.22744.227
274675JOLIET 29;7U
Adder
129.0741176470588109.713
274676JOLIET 29;8U
Adder
129.0705882352941109.71
274682WAUKEGAN ;7U
Adder
75.2058823529411763.925
274683WAUKEGAN ;8U
Adder
81.1376470588235368.967
274687WILL CNTY;4U
Adder
119.63882352941177101.693
274771LINCOLN ;2U
50/50
3.1483.148
274772LINCOLN ;3U
50/50
3.1483.148
274773LINCOLN ;4U
50/50
3.1483.148
274774LINCOLN ;5U
50/50
3.1483.148
274775LINCOLN ;6U
50/50
3.1483.148
274776LINCOLN ;7U
50/50
3.1483.148
274777LINCOLN ;8U
50/50
3.1483.148
274788SE CHICAG;5U
Adder
8.7305882352941187.421
274789SE CHICAG;6U
Adder
8.7305882352941187.421
274790SE CHICAG;7U
Adder
8.7305882352941187.421
274791SE CHICAG;8U
Adder
8.7305882352941187.421
274792SE CHICAG;9U
Adder
8.722352941176477.414
274793SE CHICAG;0U
Adder
8.722352941176477.414
274794SE CHICAG;1U
Adder
8.722352941176477.414
274795SE CHICAG;2U
Adder
8.722352941176477.414
276591L-013 2
Adder
6.7270588235294125.718
293061N-015 E
Adder
28.1705882352941223.945
293644O22 E1
Adder
26.09999999999999822.185
293645O22 E2
Adder
29.89294117647058625.409
294392P-010 E
Adder
35.776470588235330.41
933411AC2-154 C
Adder
4.4858823529411773.813
933412AC2-154 E
Adder
7.3188235294117656.221
957331AF2-027 C
Adder
4.55882352941176453.875
957332AF2-027 E
Adder
6.8388235294117655.813
957471AF2-041 C
Adder
31.69882352941176526.944
274674JOLIET 9 ;6U
Adder
65.8517647058823555.974
274890CAYUG;1U E
Adder
26.69411764705882522.69
274891CAYUG;2U E
Adder
26.69411764705882522.69
938851AE1-113 C
Adder
14.73882352941176612.528
938852AE1-113 E
Adder
52.2552941176470644.417
934101AD2-000 1
Adder
10.767058823529419.152
934111AD2-000 2
Adder
10.7964705882352949.177
270100AB1-080 CT1
50/50
9.0469.046
270101AB1-080 CT2
50/50
9.0469.046
270102AB1-080 ST
50/50
9.7879.787
274708KENDALL ;3C
50/50
7.1797.179
274709KENDALL ;3S
50/50
4.7494.749
274710KENDALL ;4C
50/50
7.1017.101
274711KENDALL ;4S
50/50
4.7494.749
275149KELLYCK ;1E
Adder
33.05176470588235628.094
293519PILOT HIL;1E
Adder
33.05176470588235628.094
290108LEEDK;1U E
Adder
44.7835294117647138.066
916221Z1-073 E
Adder
13.82117647058823511.748
936292AD2-038 E
Adder
27.6482352941176523.501
936371AD2-047 C
Adder
8.0270588235294126.823
936372AD2-047 E
Adder
39.1894117647058833.311
936461AD2-060 C
Adder
4.7211764705882354.013
936511AD2-066 C
Adder
15.63294117647058813.288
936512AD2-066 E
Adder
10.422352941176478.859
942421AE2-255 C
Adder
5.5823529411764714.745
942422AE2-255 E
Adder
16.7482352941176514.236
942651AE2-281 C
Adder
1.56588235294117651.331
942652AE2-281 E
Adder
9.6188235294117658.176
943121AE2-341 C
Adder
23.57411764705882420.038
943122AE2-341 E
Adder
11.5764705882352949.84
943591AF1-030 C
Adder
15.67647058823529313.325
943592AF1-030 E
Adder
7.75647058823529446.593
960591AF2-350 C
Adder
14.1647058823529412.04
960592AF2-350 E
Adder
9.4435294117647068.027
961501AF2-441 C
Adder
18.91647058823529516.079
961502AF2-441 E
Adder
28.3752941176470624.119
939321AE1-163 C
Adder
10.9611764705882359.317
939322AE1-163 E
Adder
67.3294117647058857.23
939351AE1-166 C
50/50
18.47818.478
939352AE1-166 E
50/50
17.05717.057
939401AE1-172 C
Adder
10.182352941176478.655
939402AE1-172 E
Adder
47.6717647058823540.521
946671AF1-331 C
Adder
4.4823529411764713.81
962691AG1-118 C
Adder
41.05764705882353434.899
962692AG1-118 E
Adder
27.37176470588235223.266
941551AE2-152 C
50/50
21.32121.321
941552AE2-152 E
50/50
14.21414.214
957371AF2-031 C
Adder
1.8882352941176471.605
957372AF2-031 E
Adder
2.83294117647058832.408
958011AF2-095 C
Adder
20.3976470588235317.338
958012AF2-095 E
Adder
13.59882352941176411.559
965791AG1-447 C
Adder
12.78352941176470610.866
274770LINCOLN ;1U
50/50
3.1483.148
920272AA2-123 E
Adder
5.30941176470588254.513
276170Z1-108 E
Adder
5.3764705882352954.57
276675AE2-062 E
Adder
0.275294117647058860.234
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
2.162.16
CBM West 1LTFEXP_CBM-W1->PJM
CBM
268.722268.722
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.75157.751
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
5.9085.908
NYPJM->LTFIMP_NY
CLTF
3.0993.099
LGEELTFEXP_LGEE->PJM
CLTF
1.2131.213
WECLTFEXP_WEC->PJM
CLTF
7.2467.246
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.4271.427
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.7140.714
TVALTFEXP_TVA->PJM
CLTF
5.7885.788
MECLTFEXP_MEC->PJM
CLTF
27.4427.44
LAGNLTFEXP_LAGN->PJM
CLTF
10.83410.834
SIGELTFEXP_SIGE->PJM
CLTF
0.7480.748
O66PJM->LTFIMP_O-066
CMTX_NF
37.87737.877

Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.33 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4155.81
MW Contribution:11.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.97 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4182.04
MW Contribution:11.82
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
4.4705882352941183.8
962781AG1-127 C
Adder
11.7810.013
962782AG1-127 E
Adder
7.8388235294117666.663
965681AG1-436 C
Adder
15.73176470588235413.372
965682AG1-436 E
Adder
10.4870588235294118.914
966091AG1-478 C
Adder
3.3647058823529412.86
966092AG1-478 E
Adder
0.84705882352941180.72
966441AG1-513 C
Adder
0.84705882352941180.72
966442AG1-513 E
Adder
1.27058823529411781.08
24796705OLIV SLR E
Adder
0.50470588235294120.429
290021O50 E
Adder
32.3317647058823527.482
290051GSG-6; E
Adder
17.78705882352941415.119
295109WESTBROOK E
Adder
9.522352941176478.094
295111SUBLETTE E
Adder
4.6294117647058833.935
910542X3-005 E
Adder
1.20117647058823531.021
918052AA1-018 E OP
Adder
26.79411764705882222.775
933911AD1-013 C
Adder
3.1305882352941182.661
933912AD1-013 E
Adder
5.04.25
934721AD1-100 C
50/50
4.9494.949
934722AD1-100 E
50/50
150.352150.352
937002AD2-134 E
Adder
17.1976470588235314.618
958481AF2-142 C
Adder
18.47882352941176615.707
958482AF2-142 E
Adder
12.31882352941176410.471
958491AF2-143 C
Adder
18.21411764705882415.482
958492AF2-143 E
Adder
12.1423529411764710.321
959351AF2-226 C
Adder
4.11294117647058853.496
959352AF2-226 E
Adder
6.1694117647058825.244
960281AF2-319 C
Adder
4.11294117647058853.496
960282AF2-319 E
Adder
6.1694117647058825.244
960582AF2-349 E
Adder
60.9223529411764751.784
960681AF2-359 C
Adder
15.73176470588235413.372
960682AF2-359 E
Adder
10.4870588235294118.914
960751AF2-366 C
Adder
11.747058823529419.985
960752AF2-366 E
Adder
7.8305882352941176.656
24344105CKG2
50/50
55.59555.595
274660LASCO STA;1U
50/50
40.01740.017
274661LASCO STA;2U
50/50
40.14440.144
274675JOLIET 29;7U
Adder
117.0552941176470799.497
274676JOLIET 29;8U
Adder
117.0517647058823699.494
274682WAUKEGAN ;7U
Adder
68.2257.987
274683WAUKEGAN ;8U
Adder
73.6000000000000162.56
274687WILL CNTY;4U
Adder
108.4752941176470592.204
274771LINCOLN ;2U
50/50
2.8662.866
274772LINCOLN ;3U
50/50
2.8662.866
274773LINCOLN ;4U
50/50
2.8662.866
274774LINCOLN ;5U
50/50
2.8662.866
274775LINCOLN ;6U
50/50
2.8662.866
274776LINCOLN ;7U
50/50
2.8662.866
274777LINCOLN ;8U
50/50
2.8662.866
274788SE CHICAG;5U
Adder
7.9058823529411776.72
274789SE CHICAG;6U
Adder
7.9058823529411776.72
274790SE CHICAG;7U
Adder
7.9058823529411776.72
274791SE CHICAG;8U
Adder
7.9058823529411776.72
274792SE CHICAG;9U
Adder
7.8964705882352946.712
274793SE CHICAG;0U
Adder
7.8964705882352946.712
274794SE CHICAG;1U
Adder
7.8964705882352946.712
274795SE CHICAG;2U
Adder
7.8964705882352946.712
276591L-013 2
Adder
6.1047058823529415.189
293061N-015 E
Adder
25.55058823529411821.718
293644O22 E1
Adder
23.6270588235294120.083
293645O22 E2
Adder
27.06117647058823323.002
294392P-010 E
Adder
32.44823529411764427.581
933411AC2-154 C
Adder
4.0658823529411773.456
933412AC2-154 E
Adder
6.6329411764705885.638
957331AF2-027 C
Adder
4.1352941176470593.515
957332AF2-027 E
Adder
6.20352941176470555.273
957471AF2-041 C
Adder
36.2482352941176530.811
957472AF2-041 E
Adder
0.407058823529411750.346
274674JOLIET 9 ;6U
Adder
59.7105882352941250.754
938851AE1-113 C
Adder
13.33647058823529511.336
938852AE1-113 E
Adder
47.2858823529411740.193
934101AD2-000 1
Adder
9.7588235294117668.295
934111AD2-000 2
Adder
9.7858823529411768.318
270100AB1-080 CT1
50/50
8.1638.163
270101AB1-080 CT2
50/50
8.1638.163
270102AB1-080 ST
50/50
8.8338.833
274708KENDALL ;3C
50/50
6.5186.518
274709KENDALL ;3S
50/50
4.3114.311
274710KENDALL ;4C
50/50
6.4476.447
274711KENDALL ;4S
50/50
4.3114.311
275149KELLYCK ;1E
Adder
29.9576470588235325.464
293519PILOT HIL;1E
Adder
29.9576470588235325.464
290108LEEDK;1U E
Adder
40.62588235294117634.532
916221Z1-073 E
Adder
12.53411764705882410.654
936292AD2-038 E
Adder
25.01411764705882521.262
936371AD2-047 C
Adder
7.2752941176470596.184
936372AD2-047 E
Adder
35.5211764705882430.193
936461AD2-060 C
Adder
4.283.638
936511AD2-066 C
Adder
14.14470588235294112.023
936512AD2-066 E
Adder
9.4294117647058838.015
942421AE2-255 C
Adder
5.0517647058823534.294
942422AE2-255 E
Adder
15.1552941176470612.882
942651AE2-281 C
Adder
1.41647058823529411.204
942652AE2-281 E
Adder
8.7023529411764717.397
943121AE2-341 C
Adder
21.4047058823529418.194
943122AE2-341 E
Adder
10.5105882352941178.934
943591AF1-030 C
Adder
14.23411764705882412.099
943592AF1-030 E
Adder
7.042352941176475.986
959091AF2-200 C
Adder
24.1647058823529420.54
960591AF2-350 C
Adder
12.83882352941176610.913
960592AF2-350 E
Adder
8.5588235294117647.275
961501AF2-441 C
Adder
17.1376470588235314.567
961502AF2-441 E
Adder
25.7070588235294121.851
939321AE1-163 C
Adder
9.9164705882352958.429
939322AE1-163 E
Adder
60.916470588235351.779
939351AE1-166 C
50/50
16.75316.753
939352AE1-166 E
50/50
15.46515.465
939401AE1-172 C
Adder
9.2000000000000017.82
939402AE1-172 E
Adder
43.0741176470588336.613
946671AF1-331 C
Adder
4.0647058823529413.455
962691AG1-118 C
Adder
37.2494117647058831.662
962692AG1-118 E
Adder
24.8329411764705921.108
941551AE2-152 C
50/50
19.33119.331
941552AE2-152 E
50/50
12.88712.887
957371AF2-031 C
Adder
1.71058823529411771.454
957372AF2-031 E
Adder
2.56470588235294142.18
958011AF2-095 C
Adder
18.48823529411764715.715
958012AF2-095 E
Adder
12.32588235294117710.477
965791AG1-447 C
Adder
11.5364705882352939.806
274770LINCOLN ;1U
50/50
2.8662.866
920272AA2-123 E
Adder
4.8164705882352954.094
276170Z1-108 E
Adder
4.877647058823534.146
276675AE2-062 E
Adder
0.249411764705882360.212
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.8261.826
CBM West 1LTFEXP_CBM-W1->PJM
CBM
243.013243.013
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.43653.436
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
5.4955.495
NYPJM->LTFIMP_NY
CLTF
2.8932.893
LGEELTFEXP_LGEE->PJM
CLTF
3.0323.032
WECLTFEXP_WEC->PJM
CLTF
6.5716.571
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.1751.175
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5610.561
TVALTFEXP_TVA->PJM
CLTF
5.8945.894
MECLTFEXP_MEC->PJM
CLTF
24.86724.867
LAGNLTFEXP_LAGN->PJM
CLTF
10.36210.362
SIGELTFEXP_SIGE->PJM
CLTF
0.7770.777
O66PJM->LTFIMP_O-066
CMTX_NF
35.23735.237

Details for 05SORENS-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SORENS-05MARYSV 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.72 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4254.85
MW Contribution:13.88
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05MARYSV 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.54 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4288.77
MW Contribution:14.39
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
24335305OLIVE
50/50
0.2120.212
965681AG1-436 C
Adder
18.9305882352941216.091
965682AG1-436 E
Adder
12.62117647058823510.728
966091AG1-478 C
Adder
3.88000000000000033.298
966092AG1-478 E
Adder
0.97647058823529410.83
966441AG1-513 C
Adder
0.96823529411764710.823
966442AG1-513 E
Adder
1.45294117647058841.235
24642205MAYFLWER
50/50
0.2440.244
24643105BUCHANAN
50/50
0.0840.084
247643Z2-116 C
50/50
0.0550.055
24796605WTRV SLR E
Adder
0.57647058823529410.49
24796705OLIV SLR E
50/50
0.6480.648
247969Z2-116 E
50/50
0.3340.334
910542X3-005 E
Adder
1.39411764705882371.185
918052AA1-018 E OP
Adder
31.17294117647058726.497
934722AD1-100 E
Adder
172.2376470588235146.402
943001AE2-323 C
Adder
16.5152941176470614.038
943002AE2-323 E
Adder
8.097647058823536.883
943021AE2-325 C
50/50
7.9467.946
943022AE2-325 E
50/50
5.2975.297
944161AF1-084 C
Adder
13.66941176470588311.619
944162AF1-084 E
Adder
7.80823529411764656.637
944961AF1-161 C
50/50
6.3426.342
958481AF2-142 C
Adder
21.49882352941176618.274
958482AF2-142 E
Adder
14.3329411764705912.183
959351AF2-226 C
Adder
4.7847058823529424.067
959352AF2-226 E
Adder
7.17647058823529356.1
960281AF2-319 C
Adder
4.7847058823529424.067
960282AF2-319 E
Adder
7.17647058823529356.1
960681AF2-359 C
Adder
18.9305882352941216.091
960682AF2-359 E
Adder
12.62117647058823510.728
24307105BERRINSP G
50/50
0.1370.137
24344005CKG1
50/50
43.40443.404
24344105CKG2
50/50
55.8555.85
24441505OLIV SLR C
50/50
0.1060.106
270142AA2-116_CT1
50/50
15.92315.923
270143AA2-116_CT2
50/50
15.92315.923
270144AA2-116_ST
50/50
14.10214.102
274675JOLIET 29;7U
Adder
134.57764705882354114.391
274676JOLIET 29;8U
Adder
134.5764705882353114.39
274682WAUKEGAN ;7U
Adder
78.4505882352941366.683
274683WAUKEGAN ;8U
Adder
84.6588235294117671.96
274687WILL CNTY;4U
Adder
124.97176470588235106.226
274771LINCOLN ;2U
50/50
3.1893.189
274772LINCOLN ;3U
50/50
3.1893.189
274773LINCOLN ;4U
50/50
3.1893.189
274776LINCOLN ;7U
50/50
3.1893.189
274777LINCOLN ;8U
50/50
3.1893.189
274788SE CHICAG;5U
Adder
9.2541176470588237.866
274789SE CHICAG;6U
Adder
9.2541176470588237.866
274790SE CHICAG;7U
Adder
9.2541176470588237.866
274791SE CHICAG;8U
Adder
9.2541176470588237.866
274792SE CHICAG;9U
Adder
9.2541176470588237.866
274793SE CHICAG;0U
Adder
9.2541176470588237.866
274794SE CHICAG;1U
Adder
9.2541176470588237.866
274795SE CHICAG;2U
Adder
9.2541176470588237.866
276591L-013 2
Adder
6.9894117647058825.941
293061N-015 E
Adder
29.2470588235294124.86
293644O22 E1
Adder
27.48823529411764723.365
293645O22 E2
Adder
31.48352941176470726.761
294392P-010 E
Adder
37.143529411764731.572
933411AC2-154 C
Adder
4.6870588235294123.984
933412AC2-154 E
Adder
7.6482352941176476.501
274674JOLIET 9 ;6U
Adder
68.6729411764705958.372
934101AD2-000 1
Adder
11.2117647058823529.53
934111AD2-000 2
Adder
11.2741176470588259.583
24335205NTRDAM
50/50
2.4332.433
24641605TWIN BRNCH
50/50
0.0710.071
24647605NILES
50/50
0.0550.055
24647705NILES
50/50
0.0550.055
270100AB1-080 CT1
50/50
9.9719.971
270101AB1-080 CT2
50/50
9.9719.971
270102AB1-080 ST
50/50
10.78910.789
270216AD2-079_C O1
50/50
0.5020.502
275149KELLYCK ;1E
Adder
34.53882352941176529.358
293519PILOT HIL;1E
Adder
34.53882352941176529.358
936632AD2-079 E O1
50/50
2.0472.047
936141AD2-020 C
50/50
15.70315.703
936371AD2-047 C
Adder
8.3882352941176477.13
936372AD2-047 E
Adder
40.95294117647059634.81
936461AD2-060 C
Adder
4.9341176470588244.194
942241AE2-236 C
Adder
9.7541176470588238.291
942242AE2-236 E
Adder
4.183.553
943121AE2-341 C
Adder
24.38470588235294320.727
943122AE2-341 E
Adder
11.97411764705882410.178
943591AF1-030 C
Adder
16.21647058823529613.784
943592AF1-030 E
Adder
8.0235294117647066.82
944241AF1-092 C
Adder
28.98705882352941324.639
944242AF1-092 E
Adder
8.822352941176477.499
944931AF1-158 C
50/50
3.7133.713
944932AF1-158 E
50/50
15.54815.548
945111AF1-176 C
50/50
39.50439.504
945112AF1-176 E
50/50
36.6236.62
945421AF1-207 C
Adder
8.1811764705882366.954
945422AF1-207 E
Adder
35.13176470588235429.862
945502AF1-215 E
Adder
30.13647058823529425.616
959141AF2-205 C
Adder
29.48588235294117525.063
959142AF2-205 E
Adder
19.65764705882352816.709
960591AF2-350 C
Adder
14.80235294117647312.582
960592AF2-350 E
Adder
9.8682352941176488.388
961051AF2-396 C
50/50
50.74150.741
961501AF2-441 C
Adder
19.95058823529411616.958
961502AF2-441 E
Adder
29.9258823529411825.437
939351AE1-166 C
Adder
19.19176470588235316.313
939352AE1-166 E
Adder
17.7152941176470615.058
939391AE1-170 C
50/50
16.1416.14
939392AE1-170 E
50/50
22.28822.288
939402AE1-172 E
Adder
25.43999999999999821.624
940581AE2-045 C
Adder
20.59882352941176717.509
940582AE2-045 E
Adder
28.28352941176470724.041
962601AG1-109 C
50/50
6.3426.342
964401AG1-302 C
Adder
44.7047058823529537.999
964402AG1-302 E
Adder
29.80235294117647325.332
936142AD2-020 E
50/50
9.6669.666
941551AE2-152 C
Adder
22.1447058823529418.823
941552AE2-152 E
Adder
14.76352941176470612.549
957371AF2-031 C
Adder
2.01.7
957372AF2-031 E
Adder
3.02.55
957841AF2-078 C
Adder
28.8752941176470624.544
957842AF2-078 E
Adder
19.25058823529411716.363
957891AF2-083 C
50/50
25.55625.556
957892AF2-083 E
50/50
12.77812.778
958011AF2-095 C
Adder
21.31529411764705618.118
958012AF2-095 E
Adder
14.21058823529411812.079
958381AF2-132 C
Adder
44.7047058823529537.999
958382AF2-132 E
Adder
29.80235294117647325.332
958391AF2-133 C
Adder
44.3929411764705937.734
958392AF2-133 E
Adder
29.59529411764705725.156
958402AF2-134 E
Adder
10.0458823529411768.539
964861AG1-349 C
Adder
38.6632.861
964862AG1-349 E
Adder
25.7729411764705921.907
965791AG1-447 C
Adder
13.88235294117647111.8
274770LINCOLN ;1U
50/50
3.1893.189
276675AE2-062 E
Adder
0.287058823529411760.244
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
2.3872.387
CBM West 1LTFEXP_CBM-W1->PJM
CBM
319.618319.618
CBM West 2LTFEXP_CBM-W2->PJM
CBM
75.36775.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
6.9886.988
NYPJM->LTFIMP_NY
CLTF
3.633.63
LGEELTFEXP_LGEE->PJM
CLTF
3.8433.843
WECLTFEXP_WEC->PJM
CLTF
7.6087.608
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.531.53
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.7280.728
TVALTFEXP_TVA->PJM
CLTF
8.198.19
MECLTFEXP_MEC->PJM
CLTF
30.0930.09
LAGNLTFEXP_LAGN->PJM
CLTF
13.77113.771
SIGELTFEXP_SIGE->PJM
CLTF
1.2341.234
O66PJM->LTFIMP_O-066
CMTX_NF
44.79244.792

Details for 18MOROCCO-02ALLEN 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-022T_SRT-A-1_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:ATSI/METC
Facility Description:
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-022T_SRT-A-1_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.87 %
Rating:1793.0 MVA
Rating Type:B
MVA to Mitigate:2005.86
MW Contribution:4.81
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
24335305OLIVE
50/50
0.0820.082
965681AG1-436 C
Adder
6.5623529411764715.578
965682AG1-436 E
Adder
4.3752941176470593.719
24639705ELKHART HY
50/50
0.0320.032
24642205MAYFLWER
50/50
0.1020.102
24643105BUCHANAN
50/50
0.0350.035
24752805COVRT1
50/50
5.4595.459
24752905COVRT2
50/50
5.4595.459
24753005COVRT3
50/50
5.4595.459
24753105COVRT4
50/50
3.2833.283
24753205COVRT5
50/50
3.2593.259
24753305COVRT6
50/50
2.6732.673
247620Y3-023
50/50
0.0770.077
247643Z2-116 C
50/50
0.0220.022
24796605WTRV SLR E
50/50
0.290.29
24796705OLIV SLR E
50/50
0.2510.251
247969Z2-116 E
50/50
0.1370.137
943001AE2-323 C
Adder
5.824.947
943002AE2-323 E
Adder
2.8541176470588242.426
943021AE2-325 C
50/50
3.6953.695
943022AE2-325 E
50/50
2.4632.463
944161AF1-084 C
50/50
6.5136.513
944162AF1-084 E
50/50
3.723.72
944961AF1-161 C
50/50
2.952.95
945641AF1-229 C
Adder
-8.618823529411765-7.326
960681AF2-359 C
Adder
6.5623529411764715.578
960682AF2-359 E
Adder
4.3752941176470593.719
960841AF2-375 C
Adder
-9.301176470588235-7.906
24307105BERRINSP G
50/50
0.0630.063
24344005CKG1
50/50
18.67318.673
24441205WTRV SLR C
50/50
0.0470.047
24441505OLIV SLR C
50/50
0.0410.041
270142AA2-116_CT1
50/50
6.8386.838
270143AA2-116_CT2
50/50
6.8386.838
270144AA2-116_ST
50/50
6.0566.056
274788SE CHICAG;5U
Adder
3.09058823529411742.627
274789SE CHICAG;6U
Adder
3.09058823529411742.627
274790SE CHICAG;7U
Adder
3.09058823529411742.627
274791SE CHICAG;8U
Adder
3.09058823529411742.627
274792SE CHICAG;9U
Adder
3.09411764705882362.63
274793SE CHICAG;0U
Adder
3.09411764705882362.63
274794SE CHICAG;1U
Adder
3.09411764705882362.63
274795SE CHICAG;2U
Adder
3.09411764705882362.63
941781AE2-181 C
Adder
-7.374117647058823-6.268
24335205NTRDAM
50/50
0.9730.973
24641605TWIN BRNCH
50/50
0.0290.029
24647605NILES
50/50
0.0230.023
24647705NILES
50/50
0.0230.023
24653605MOTTVILLE
50/50
0.0090.009
247604X1-042
50/50
0.0810.081
270216AD2-079_C O1
50/50
0.2080.208
936632AD2-079 E O1
50/50
0.8480.848
936141AD2-020 C
50/50
7.3037.303
944931AF1-158 C
50/50
1.451.45
944932AF1-158 E
50/50
6.0726.072
945111AF1-176 C
50/50
17.81417.814
945112AF1-176 E
50/50
16.51416.514
945502AF1-215 E
Adder
10.5917647058823539.003
959141AF2-205 C
Adder
10.1647058823529428.64
959142AF2-205 E
Adder
6.7764705882352945.76
961051AF2-396 C
50/50
23.33323.333
939391AE1-170 C
50/50
7.1597.159
939392AE1-170 E
50/50
9.8869.886
940581AE2-045 C
Adder
7.0670588235294116.007
940582AE2-045 E
Adder
9.7035294117647068.248
962601AG1-109 C
50/50
2.952.95
964401AG1-302 C
Adder
15.55882352941176413.225
964402AG1-302 E
Adder
10.3729411764705888.817
936142AD2-020 E
50/50
4.4954.495
957371AF2-031 C
Adder
0.66705882352941170.567
957372AF2-031 E
Adder
1.00117647058823530.851
957891AF2-083 C
50/50
11.29411.294
957892AF2-083 E
50/50
5.6475.647
958381AF2-132 C
Adder
15.55882352941176413.225
958382AF2-132 E
Adder
10.3729411764705888.817
958391AF2-133 C
Adder
15.35529411764705913.052
958392AF2-133 E
Adder
10.2364705882352968.701
958402AF2-134 E
Adder
3.5305882352941183.001
964861AG1-349 C
Adder
13.4294117647058811.415
964862AG1-349 E
Adder
8.9529411764705887.61
965791AG1-447 C
Adder
4.8117647058823534.09
939161AE1-146 C
Adder
-9.078823529411764-7.717
943961AF1-064 C
Adder
-7.631764705882353-6.487
991182J1586 G
External Queue
63.33609008789062563.336090087890625
990527J1329 G
External Queue
5.52491998672485355.5249199867248535
955182J996 G
External Queue
27.58028030395507827.580280303955078
990142J1224 G
External Queue
46.72817993164062546.728179931640625
990152J1226
External Queue
85.5240020751953185.52400207519531
991177J1571 G
External Queue
66.2298431396484466.22984313964844
991227J1663 G
External Queue
17.13986778259277317.139867782592773
955782J1062 G
External Queue
59.26379013061523459.263790130615234
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.2120.212
CBM West 1LTFEXP_CBM-W1->PJM
CBM
233.141233.141
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.95127.951
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.2539.253
G-007PJM->LTFIMP_G-007
CMTX_NF
2.2922.292
NYPJM->LTFIMP_NY
CLTF
1.4091.409
LGEELTFEXP_LGEE->PJM
CLTF
1.9271.927
WECLTFEXP_WEC->PJM
CLTF
2.4822.482
CPLELTFEXP_CPLE->PJM
CLTF
0.4250.425
TVALTFEXP_TVA->PJM
CLTF
4.1424.142
MECLTFEXP_MEC->PJM
CLTF
10.07210.072
LAGNLTFEXP_LAGN->PJM
CLTF
6.0326.032
SIGELTFEXP_SIGE->PJM
CLTF
0.4440.444
O66PJM->LTFIMP_O-066
CMTX_NF
14.78614.786
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT Z1   /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1    /*05HANG R     765.0 - 05JEFRSO     765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1   /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1   /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1   /*05HANG R     765.0 - 05JEFRSO     765.0
 REMOVE UNIT 1A FROM BUS 247245                    /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                    /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                    /*05HRKG1S      18.0
 REMOVE UNIT 2 FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2A FROM BUS 247248                    /*05HRKG2A      18.0
 REMOVE UNIT 2S FROM BUS 247250                    /*05HRKG2S      18.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-022T_SRT-A-1_SENS'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 264594 CKT 1   /*02LEMOYN     345.0 - 19LULU       345.0
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
END
243206 to 246999 ckt 1
246999 to 242928 ckt 1
256583 to 238530 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP
05DUMONT-05SORENS 765.0 kV Ckt 1 line
AEP_P7-1_#11046___SRT-A
TowerAC100.52 %4142.0B4163.6412.24
GD1AEP
05OLIVE-05NEW CARLI1 138.0 kV Ckt 1 line
AEP_P4_#9247_05OLIVE 138_R1_SRT-SL
BreakerAC113.25 %337.0B381.652.83
GD1ATSI/METC
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-022T_SRT-A-1
TowerAC111.24 %1793.0B1994.515.05
GD1ATSI/METC
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-022T_SRT-A-2
TowerAC108.8 %1793.0B1950.815.05
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC148.85 %971.0B1445.3546.75
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC148.76 %971.0B1444.4446.9
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC148.76 %971.0B1444.4446.9

Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P7-1_#11046___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11046___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.52 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4163.64
MW Contribution:12.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
4.4117647058823533.75
962781AG1-127 C
Adder
11.6764705882352959.925
962782AG1-127 E
Adder
7.77058823529411856.605
965681AG1-436 C
50/50
16.69316.693
965682AG1-436 E
50/50
11.12911.129
966091AG1-478 C
Adder
3.35058823529411762.848
966092AG1-478 E
Adder
0.84235294117647050.716
966441AG1-513 C
Adder
0.84235294117647050.716
966442AG1-513 E
Adder
1.26235294117647071.073
24796705OLIV SLR E
Adder
0.52823529411764710.449
290021O50 E
Adder
31.95647058823529527.163
290051GSG-6; E
Adder
17.55176470588235614.919
295109WESTBROOK E
Adder
9.3964705882352947.987
295111SUBLETTE E
Adder
4.5682352941176473.883
910542X3-005 E
Adder
1.20352941176470571.023
918052AA1-018 E OP
Adder
26.60117647058823622.611
933911AD1-013 C
Adder
3.08941176470588232.626
933912AD1-013 E
Adder
4.9341176470588244.194
934722AD1-100 E
Adder
149.50823529411764127.082
937002AD2-134 E
Adder
16.9705882352941214.425
958481AF2-142 C
Adder
18.34588235294117515.594
958482AF2-142 E
Adder
12.2305882352941210.396
958491AF2-143 C
Adder
18.03411764705882415.329
958492AF2-143 E
Adder
12.0223529411764710.219
959351AF2-226 C
Adder
4.0788235294117653.467
959352AF2-226 E
Adder
6.117647058823535.2
960281AF2-319 C
Adder
4.0788235294117653.467
960282AF2-319 E
Adder
6.117647058823535.2
960582AF2-349 E
Adder
60.28705882352941451.244
960681AF2-359 C
50/50
16.69316.693
960682AF2-359 E
50/50
11.12911.129
960751AF2-366 C
Adder
11.6435294117647079.897
960752AF2-366 E
Adder
7.7623529411764716.598
24344005CKG1
50/50
36.32536.325
24344105CKG2
50/50
55.71455.714
274660LASCO STA;1U
50/50
39.69139.691
274661LASCO STA;2U
50/50
39.8239.82
274675JOLIET 29;7U
Adder
116.6376470588235399.142
274676JOLIET 29;8U
Adder
116.6341176470588299.139
274682WAUKEGAN ;7U
Adder
67.7223529411764757.564
274683WAUKEGAN ;8U
Adder
73.0517647058823662.094
274687WILL CNTY;4U
Adder
108.1341176470588391.914
274771LINCOLN ;2U
50/50
2.8472.847
274772LINCOLN ;3U
50/50
2.8472.847
274773LINCOLN ;4U
50/50
2.8472.847
274774LINCOLN ;5U
50/50
2.8472.847
274775LINCOLN ;6U
50/50
2.8472.847
274776LINCOLN ;7U
50/50
2.8472.847
274777LINCOLN ;8U
50/50
2.8472.847
274788SE CHICAG;5U
Adder
7.93999999999999956.749
274789SE CHICAG;6U
Adder
7.93999999999999956.749
274790SE CHICAG;7U
Adder
7.93999999999999956.749
274791SE CHICAG;8U
Adder
7.93999999999999956.749
274792SE CHICAG;9U
Adder
7.9305882352941186.741
274793SE CHICAG;0U
Adder
7.9305882352941186.741
274794SE CHICAG;1U
Adder
7.9305882352941186.741
274795SE CHICAG;2U
Adder
7.9305882352941186.741
276591L-013 2
Adder
6.0611764705882365.152
293061N-015 E
Adder
25.37882352941176521.572
293644O22 E1
Adder
23.4329411764705919.918
293645O22 E2
Adder
26.8376470588235322.812
294392P-010 E
Adder
32.2305882352941227.396
933411AC2-154 C
Adder
4.0564705882352943.448
933412AC2-154 E
Adder
6.6188235294117655.626
957331AF2-027 C
Adder
4.1035294117647063.488
957332AF2-027 E
Adder
6.1552941176470595.232
957471AF2-041 C
Adder
35.81882352941176630.446
957472AF2-041 E
Adder
16.55176470588235614.069
274674JOLIET 9 ;6U
Adder
59.4611764705882450.542
938851AE1-113 C
Adder
13.18235294117647211.205
938852AE1-113 E
Adder
46.73529411764706539.725
934101AD2-000 1
Adder
9.6658823529411778.216
934111AD2-000 2
Adder
9.7294117647058828.27
270100AB1-080 CT1
50/50
8.4898.489
270101AB1-080 CT2
50/50
8.4898.489
270102AB1-080 ST
50/50
9.1849.184
275149KELLYCK ;1E
Adder
29.89176470588235525.408
293519PILOT HIL;1E
Adder
29.89176470588235525.408
290108LEEDK;1U E
Adder
40.1234.102
916221Z1-073 E
Adder
12.36823529411764810.513
936292AD2-038 E
Adder
24.7670588235294121.052
936371AD2-047 C
Adder
7.2600000000000016.171
936372AD2-047 E
Adder
35.4435294117647130.127
936461AD2-060 C
Adder
4.2705882352941183.63
936511AD2-066 C
Adder
13.97882352941176411.882
936512AD2-066 E
Adder
9.3188235294117667.921
942421AE2-255 C
Adder
4.9929411764705884.244
942422AE2-255 E
Adder
14.97882352941176412.732
942651AE2-281 C
Adder
1.40235294117647061.192
942652AE2-281 E
Adder
8.6164705882352957.324
943121AE2-341 C
Adder
21.2623529411764718.073
943122AE2-341 E
Adder
10.4411764705882368.875
943591AF1-030 C
Adder
14.1412.019
943592AF1-030 E
Adder
6.9952941176470595.946
944932AF1-158 E
Adder
12.53176470588235210.652
959091AF2-200 C
Adder
23.87882352941176520.297
960591AF2-350 C
Adder
12.81058823529411810.889
960592AF2-350 E
Adder
8.5411764705882357.26
961501AF2-441 C
Adder
17.18352941176470614.606
961502AF2-441 E
Adder
25.77529411764705721.909
939321AE1-163 C
Adder
9.8188235294117648.346
939322AE1-163 E
Adder
60.3141176470588351.267
939351AE1-166 C
Adder
16.6614.161
939352AE1-166 E
Adder
15.37764705882352913.071
939401AE1-172 C
Adder
9.0694117647058817.709
939402AE1-172 E
Adder
42.46235294117647636.093
946671AF1-331 C
Adder
4.0117647058823533.41
962691AG1-118 C
Adder
36.9352941176470631.395
962692AG1-118 E
Adder
24.62352941176470720.93
941551AE2-152 C
Adder
19.2223529411764716.339
941552AE2-152 E
Adder
12.8152941176470610.893
957371AF2-031 C
Adder
1.71647058823529421.459
957372AF2-031 E
Adder
2.5752941176470592.189
958011AF2-095 C
Adder
18.44823529411764815.681
958012AF2-095 E
Adder
12.29882352941176610.454
965791AG1-447 C
50/50
12.24212.242
274770LINCOLN ;1U
50/50
2.8472.847
920272AA2-123 E
Adder
4.76941176470588254.054
276170Z1-108 E
Adder
4.837647058823534.112
276675AE2-062 E
Adder
0.249411764705882360.212
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
1.4661.466
CBM West 1LTFEXP_CBM-W1->PJM
CBM
235.985235.985
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.62846.628
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
5.225.22
NYPJM->LTFIMP_NY
CLTF
2.7622.762
LGEELTFEXP_LGEE->PJM
CLTF
1.661.66
WECLTFEXP_WEC->PJM
CLTF
6.4986.498
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.9160.916
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.4090.409
TVALTFEXP_TVA->PJM
CLTF
5.1695.169
MECLTFEXP_MEC->PJM
CLTF
23.96923.969
LAGNLTFEXP_LAGN->PJM
CLTF
9.4439.443
SIGELTFEXP_SIGE->PJM
CLTF
0.560.56
O66PJM->LTFIMP_O-066
CMTX_NF
33.48333.483

Details for 05OLIVE-05NEW CARLI1 138.0 kV Ckt 1 line l/o AEP_P4_#9247_05OLIVE 138_R1_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05OLIVE-05NEW CARLI1 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9247_05OLIVE 138_R1_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.25 %
Rating:337.0 MVA
Rating Type:B
MVA to Mitigate:381.65
MW Contribution:2.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
24335305OLIVE
50/50
0.2590.259
965681AG1-436 C
Adder
3.8576470588235293.279
965682AG1-436 E
Adder
2.5717647058823532.186
24796705OLIV SLR E
50/50
0.7950.795
960681AF2-359 C
Adder
3.8576470588235293.279
960682AF2-359 E
Adder
2.5717647058823532.186
24441505OLIV SLR C
50/50
0.1290.129
944931AF1-158 C
50/50
3.563.56
944932AF1-158 E
50/50
14.95914.959
965791AG1-447 C
Adder
2.8294117647058822.405
990647J1355
External Queue
-11.762874603271484-11.762874603271484
990662J1358
External Queue
-25.98584747314453-25.98584747314453
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0390.039
LTFEXP_AC1-056LTFEXP_AC1-056->LTFIMP_AC1-056
CLTF
0.3630.363
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.1850.185
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.6650.665
G-007ALTFEXP_G-007A->PJM
CMTX
0.3370.337
VTFLTFEXP_VFT->PJM
CMTX
0.9080.908
LGEELTFEXP_LGEE->PJM
CLTF
0.0770.077
COTTONWOODPJM->LTFIMP_COTTONWOOD
CLTF
0.3750.375
CPLELTFEXP_CPLE->PJM
CLTF
0.0810.081
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.6970.697
SIGELTFEXP_SIGE->PJM
CLTF
0.0060.006
MDUPJM->LTFIMP_MDU
CLTF
0.0830.083

Details for 18MOROCCO-02ALLEN 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-022T_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI/METC
Facility Description:
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-022T_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.24 %
Rating:1793.0 MVA
Rating Type:B
MVA to Mitigate:1994.51
MW Contribution:5.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
965681AG1-436 C
Adder
6.8894117647058835.856
965682AG1-436 E
Adder
4.5929411764705883.904
24639705ELKHART HY
50/50
0.0310.031
24642205MAYFLWER
50/50
0.0990.099
24643105BUCHANAN
50/50
0.0340.034
24752805COVRT1
50/50
5.2795.279
24752905COVRT2
50/50
5.2795.279
24753005COVRT3
50/50
5.2795.279
24753105COVRT4
50/50
3.1753.175
24753205COVRT5
50/50
3.1513.151
24753305COVRT6
50/50
2.5822.582
247620Y3-023
50/50
0.0740.074
247643Z2-116 C
50/50
0.0220.022
24796605WTRV SLR E
50/50
0.2820.282
24796705OLIV SLR E
Adder
0.243529411764705880.207
247969Z2-116 E
50/50
0.1330.133
943001AE2-323 C
Adder
5.6729411764705884.822
943002AE2-323 E
Adder
2.78117647058823542.364
943021AE2-325 C
50/50
3.5913.591
943022AE2-325 E
50/50
2.3942.394
944161AF1-084 C
50/50
6.3286.328
944162AF1-084 E
50/50
3.6143.614
944961AF1-161 C
50/50
2.8662.866
945641AF1-229 C
Adder
-8.249411764705883-7.012
960681AF2-359 C
Adder
6.8894117647058835.856
960682AF2-359 E
Adder
4.5929411764705883.904
960841AF2-375 C
Adder
-8.9-7.565
24307105BERRINSP G
50/50
0.0610.061
24344005CKG1
50/50
18.08718.087
24441205WTRV SLR C
50/50
0.0460.046
270142AA2-116_CT1
50/50
6.6246.624
270143AA2-116_CT2
50/50
6.6246.624
270144AA2-116_ST
50/50
5.8665.866
274788SE CHICAG;5U
Adder
3.01764705882352932.565
274789SE CHICAG;6U
Adder
3.01764705882352932.565
274790SE CHICAG;7U
Adder
3.01764705882352932.565
274791SE CHICAG;8U
Adder
3.01764705882352932.565
274792SE CHICAG;9U
Adder
3.02235294117647072.569
274793SE CHICAG;0U
Adder
3.02235294117647072.569
274794SE CHICAG;1U
Adder
3.02235294117647072.569
274795SE CHICAG;2U
Adder
3.02235294117647072.569
941781AE2-181 C
Adder
-7.069411764705883-6.009
24335205NTRDAM
50/50
0.9430.943
24641605TWIN BRNCH
50/50
0.0280.028
24647605NILES
50/50
0.0220.022
24647705NILES
50/50
0.0220.022
24653605MOTTVILLE
50/50
0.0090.009
247604X1-042
50/50
0.0780.078
270216AD2-079_C O1
50/50
0.2010.201
936632AD2-079 E O1
50/50
0.8250.825
936141AD2-020 C
50/50
7.0977.097
944932AF1-158 E
Adder
5.9082352941176485.022
945111AF1-176 C
50/50
17.31417.314
945112AF1-176 E
50/50
16.0516.05
945502AF1-215 E
Adder
10.3188235294117668.771
959141AF2-205 C
Adder
9.912941176470598.426
959142AF2-205 E
Adder
6.6082352941176475.617
961051AF2-396 C
50/50
22.67522.675
939391AE1-170 C
50/50
6.9596.959
939392AE1-170 E
50/50
9.6099.609
940581AE2-045 C
Adder
6.8929411764705895.859
940582AE2-045 E
Adder
9.4647058823529418.045
962601AG1-109 C
50/50
2.8662.866
964401AG1-302 C
Adder
15.16588235294117712.891
964402AG1-302 E
Adder
10.1105882352941178.594
936142AD2-020 E
50/50
4.3684.368
957371AF2-031 C
Adder
0.6517647058823530.554
957372AF2-031 E
Adder
0.97764705882352940.831
957891AF2-083 C
50/50
10.97810.978
957892AF2-083 E
50/50
5.4895.489
958381AF2-132 C
Adder
15.16588235294117712.891
958382AF2-132 E
Adder
10.1105882352941178.594
958391AF2-133 C
Adder
14.97058823529411812.725
958392AF2-133 E
Adder
9.9811764705882358.484
958402AF2-134 E
Adder
3.442.924
964861AG1-349 C
Adder
13.09058823529411911.127
964862AG1-349 E
Adder
8.7270588235294117.418
965791AG1-447 C
Adder
5.0517647058823534.294
939161AE1-146 C
Adder
-8.681176470588236-7.379
943961AF1-064 C
Adder
-7.32-6.222
991182J1586 G
External Queue
60.0508537292480560.05085372924805
990527J1329 G
External Queue
5.49665594100952155.4966559410095215
955182J996 G
External Queue
28.6180343627929728.61803436279297
990142J1224 G
External Queue
46.4891281127929746.48912811279297
990152J1226
External Queue
89.7095184326171989.70951843261719
991177J1571 G
External Queue
68.5579071044921968.55790710449219
991227J1663 G
External Queue
16.31785583496093816.317855834960938
955782J1062 G
External Queue
43.4495162963867243.44951629638672
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.2470.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
229.18229.18
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.68127.681
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.13610.136
G-007PJM->LTFIMP_G-007
CMTX_NF
2.3062.306
NYPJM->LTFIMP_NY
CLTF
1.41.4
LGEELTFEXP_LGEE->PJM
CLTF
1.9231.923
WECLTFEXP_WEC->PJM
CLTF
2.4232.423
CPLELTFEXP_CPLE->PJM
CLTF
0.4980.498
TVALTFEXP_TVA->PJM
CLTF
4.1694.169
MECLTFEXP_MEC->PJM
CLTF
9.8669.866
LAGNLTFEXP_LAGN->PJM
CLTF
6.0236.023
SIGELTFEXP_SIGE->PJM
CLTF
0.440.44
O66PJM->LTFIMP_O-066
CMTX_NF
14.86514.865

Details for 18MOROCCO-02ALLEN 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-022T_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI/METC
Facility Description:
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-022T_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.8 %
Rating:1793.0 MVA
Rating Type:B
MVA to Mitigate:1950.81
MW Contribution:5.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
965681AG1-436 C
Adder
6.8894117647058835.856
965682AG1-436 E
Adder
4.5929411764705883.904
24639705ELKHART HY
50/50
0.0310.031
24642205MAYFLWER
50/50
0.0990.099
24643105BUCHANAN
50/50
0.0340.034
24752805COVRT1
50/50
5.2795.279
24752905COVRT2
50/50
5.2795.279
24753005COVRT3
50/50
5.2795.279
24753105COVRT4
50/50
3.1753.175
24753205COVRT5
50/50
3.1513.151
24753305COVRT6
50/50
2.5822.582
247620Y3-023
50/50
0.0740.074
247643Z2-116 C
50/50
0.0220.022
24796605WTRV SLR E
50/50
0.2820.282
24796705OLIV SLR E
Adder
0.243529411764705880.207
247969Z2-116 E
50/50
0.1330.133
943001AE2-323 C
Adder
5.6729411764705884.822
943002AE2-323 E
Adder
2.78117647058823542.364
943021AE2-325 C
50/50
3.5913.591
943022AE2-325 E
50/50
2.3942.394
944161AF1-084 C
50/50
6.3286.328
944162AF1-084 E
50/50
3.6143.614
944961AF1-161 C
50/50
2.8662.866
945641AF1-229 C
Adder
-8.249411764705883-7.012
960681AF2-359 C
Adder
6.8894117647058835.856
960682AF2-359 E
Adder
4.5929411764705883.904
960841AF2-375 C
Adder
-8.9-7.565
24307105BERRINSP G
50/50
0.0610.061
24344005CKG1
50/50
18.08718.087
24441205WTRV SLR C
50/50
0.0460.046
270142AA2-116_CT1
50/50
6.6246.624
270143AA2-116_CT2
50/50
6.6246.624
270144AA2-116_ST
50/50
5.8665.866
274788SE CHICAG;5U
Adder
3.01764705882352932.565
274789SE CHICAG;6U
Adder
3.01764705882352932.565
274790SE CHICAG;7U
Adder
3.01764705882352932.565
274791SE CHICAG;8U
Adder
3.01764705882352932.565
274792SE CHICAG;9U
Adder
3.02235294117647072.569
274793SE CHICAG;0U
Adder
3.02235294117647072.569
274794SE CHICAG;1U
Adder
3.02235294117647072.569
274795SE CHICAG;2U
Adder
3.02235294117647072.569
941781AE2-181 C
Adder
-7.069411764705883-6.009
24335205NTRDAM
50/50
0.9430.943
24641605TWIN BRNCH
50/50
0.0280.028
24647605NILES
50/50
0.0220.022
24647705NILES
50/50
0.0220.022
24653605MOTTVILLE
50/50
0.0090.009
247604X1-042
50/50
0.0780.078
270216AD2-079_C O1
50/50
0.2010.201
936632AD2-079 E O1
50/50
0.8250.825
936141AD2-020 C
50/50
7.0977.097
944932AF1-158 E
Adder
5.9082352941176485.022
945111AF1-176 C
50/50
17.31417.314
945112AF1-176 E
50/50
16.0516.05
945502AF1-215 E
Adder
10.3188235294117668.771
959141AF2-205 C
Adder
9.912941176470598.426
959142AF2-205 E
Adder
6.6082352941176475.617
961051AF2-396 C
50/50
22.67522.675
939391AE1-170 C
50/50
6.9596.959
939392AE1-170 E
50/50
9.6099.609
940581AE2-045 C
Adder
6.8929411764705895.859
940582AE2-045 E
Adder
9.4647058823529418.045
962601AG1-109 C
50/50
2.8662.866
964401AG1-302 C
Adder
15.16588235294117712.891
964402AG1-302 E
Adder
10.1105882352941178.594
936142AD2-020 E
50/50
4.3684.368
957371AF2-031 C
Adder
0.6517647058823530.554
957372AF2-031 E
Adder
0.97764705882352940.831
957891AF2-083 C
50/50
10.97810.978
957892AF2-083 E
50/50
5.4895.489
958381AF2-132 C
Adder
15.16588235294117712.891
958382AF2-132 E
Adder
10.1105882352941178.594
958391AF2-133 C
Adder
14.97058823529411812.725
958392AF2-133 E
Adder
9.9811764705882358.484
958402AF2-134 E
Adder
3.442.924
964861AG1-349 C
Adder
13.09058823529411911.127
964862AG1-349 E
Adder
8.7270588235294117.418
965791AG1-447 C
Adder
5.0517647058823534.294
939161AE1-146 C
Adder
-8.681176470588236-7.379
943961AF1-064 C
Adder
-7.32-6.222
991182J1586 G
External Queue
60.0508537292480560.05085372924805
990527J1329 G
External Queue
5.49665594100952155.4966559410095215
955182J996 G
External Queue
28.6180343627929728.61803436279297
990142J1224 G
External Queue
46.4891281127929746.48912811279297
990152J1226
External Queue
89.7095184326171989.70951843261719
991177J1571 G
External Queue
68.5579071044921968.55790710449219
991227J1663 G
External Queue
16.31785583496093816.317855834960938
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.2470.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
229.18229.18
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.68127.681
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.13610.136
G-007PJM->LTFIMP_G-007
CMTX_NF
2.3062.306
NYPJM->LTFIMP_NY
CLTF
1.41.4
LGEELTFEXP_LGEE->PJM
CLTF
1.9231.923
WECLTFEXP_WEC->PJM
CLTF
2.4232.423
CPLELTFEXP_CPLE->PJM
CLTF
0.4980.498
TVALTFEXP_TVA->PJM
CLTF
4.1694.169
MECLTFEXP_MEC->PJM
CLTF
9.8669.866
LAGNLTFEXP_LAGN->PJM
CLTF
6.0236.023
SIGELTFEXP_SIGE->PJM
CLTF
0.440.44
O66PJM->LTFIMP_O-066
CMTX_NF
14.86514.865

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.85 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1445.35
MW Contribution:46.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.21411764705882331.882
962012AG1-044 E
Adder
0.0529411764705882350.045
962781AG1-127 C
Adder
5.8976470588235295.013
962782AG1-127 E
Adder
3.92470588235294133.336
965681AG1-436 C
50/50
63.75263.752
965682AG1-436 E
50/50
42.50142.501
966091AG1-478 C
Adder
1.7552941176470591.492
966092AG1-478 E
Adder
0.44117647058823530.375
966441AG1-513 C
Adder
0.430588235294117660.366
966442AG1-513 E
Adder
0.64470588235294120.548
290021O50 E
Adder
16.24352941176470813.807
290051GSG-6; E
Adder
8.8082352941176477.487
295109WESTBROOK E
Adder
4.7152941176470594.008
295111SUBLETTE E
Adder
2.29294117647058831.949
910542X3-005 E
Adder
0.53058823529411770.451
918052AA1-018 E OP
Adder
14.7952941176470612.576
933911AD1-013 C
Adder
1.55058823529411781.318
933912AD1-013 E
Adder
2.47764705882352932.106
934722AD1-100 E
Adder
76.1635294117647164.739
937002AD2-134 E
Adder
8.5164705882352937.239
937312AD2-172 E
Adder
2.84588235294117682.419
958481AF2-142 C
Adder
10.2035294117647068.673
958482AF2-142 E
Adder
6.8023529411764715.782
958491AF2-143 C
Adder
9.748.279
958492AF2-143 E
Adder
6.4929411764705885.519
958912AF2-182 E
Adder
28.6258823529411824.332
959081AF2-199 C
Adder
5.9858823529411775.088
959082AF2-199 E
Adder
2.99294117647058842.544
959351AF2-226 C
Adder
2.0105882352941181.709
959352AF2-226 E
Adder
3.01647058823529422.564
960281AF2-319 C
Adder
2.0105882352941181.709
960282AF2-319 E
Adder
3.01647058823529422.564
960582AF2-349 E
Adder
30.4847058823529425.912
960681AF2-359 C
50/50
63.75263.752
960682AF2-359 E
50/50
42.50142.501
960751AF2-366 C
Adder
5.8811764705882354.999
960752AF2-366 E
Adder
3.92117647058823553.333
274675JOLIET 29;7U
Adder
61.79058823529411652.522
274676JOLIET 29;8U
Adder
61.7682352941176552.503
274682WAUKEGAN ;7U
Adder
34.8235294117647129.6
274683WAUKEGAN ;8U
Adder
37.5458823529411831.914
274687WILL CNTY;4U
Adder
55.58000000000000547.243
274859EASYR;U1 E
Adder
10.0658823529411758.556
274860EASYR;U2 E
Adder
10.0658823529411758.556
276591L-013 2
Adder
3.09411764705882362.63
293061N-015 E
Adder
13.10117647058823411.136
293644O22 E1
Adder
11.5517647058823549.819
293645O22 E2
Adder
13.2305882352941211.246
293715O-029 E
Adder
8.1494117647058816.927
293716O-029 E
Adder
4.46823529411764753.798
293717O-029 E
Adder
4.1070588235294123.491
294392P-010 E
Adder
16.63882352941176614.143
294763P-046 E
Adder
7.9094117647058826.723
933411AC2-154 C
Adder
2.10235294117647081.787
933412AC2-154 E
Adder
3.42941176470588262.915
939061AE1-134 2
Adder
1.14705882352941170.975
940502AE2-035 E
Adder
2.84588235294117682.419
957331AF2-027 C
Adder
2.1047058823529411.789
957332AF2-027 E
Adder
3.15764705882352952.684
957471AF2-041 C
Adder
17.9576470588235315.264
957472AF2-041 E
Adder
8.9788235294117647.632
274674JOLIET 9 ;6U
Adder
31.0329411764705926.378
274890CAYUG;1U E
Adder
11.395294117647069.686
274891CAYUG;2U E
Adder
11.395294117647069.686
938851AE1-113 C
Adder
6.75.695
938852AE1-113 E
Adder
23.75647058823529520.193
934101AD2-000 1
Adder
4.8788235294117654.147
934111AD2-000 2
Adder
5.0470588235294124.29
275149KELLYCK ;1E
Adder
15.48823529411764713.165
293516O-009 E
Adder
15.7576470588235313.394
293519PILOT HIL;1E
Adder
15.48823529411764713.165
290108LEEDK;1U E
Adder
20.2152941176470617.183
916221Z1-073 E
Adder
6.2070588235294125.276
274805UNIV PK N;1U
50/50
1.9031.903
274807UNIV PK N;3U
50/50
1.9151.915
274808UNIV PK N;4U
50/50
1.9071.907
926821AC1-168 C
Adder
0.95764705882352940.814
926822AC1-168 E
Adder
6.4258823529411765.462
936292AD2-038 E
Adder
13.37529411764705911.369
936371AD2-047 C
Adder
3.76235294117647053.198
936372AD2-047 E
Adder
18.36705882352941215.612
936461AD2-060 C
Adder
2.2129411764705881.881
936511AD2-066 C
Adder
7.1305882352941186.061
936512AD2-066 E
Adder
4.7541176470588244.041
942421AE2-255 C
Adder
2.53764705882352942.157
942422AE2-255 E
Adder
7.61411764705882456.472
942651AE2-281 C
Adder
0.75764705882352950.644
942652AE2-281 E
Adder
4.6529411764705893.955
943121AE2-341 C
Adder
10.7729411764705899.157
943122AE2-341 E
Adder
5.2905882352941184.497
943591AF1-030 C
Adder
7.1635294117647066.089
943592AF1-030 E
Adder
3.54470588235294143.013
959091AF2-200 C
Adder
11.97176470588235410.176
959092AF2-200 E
Adder
7.98117647058823556.784
960591AF2-350 C
Adder
6.637647058823535.642
960592AF2-350 E
Adder
4.4247058823529413.761
938861AE1-114 C
Adder
3.2964705882352942.802
938862AE1-114 E
Adder
11.244705882352949.558
939321AE1-163 C
Adder
5.302352941176474.507
939322AE1-163 E
Adder
32.5729411764705927.687
939351AE1-166 C
Adder
8.4870588235294137.214
939352AE1-166 E
Adder
7.8341176470588236.659
939401AE1-172 C
Adder
4.4505882352941173.783
939402AE1-172 E
Adder
20.8352941176470617.71
946152AF1-280 E
Adder
19.08352941176470816.221
946671AF1-331 C
Adder
2.01411764705882361.712
962691AG1-118 C
Adder
18.6752941176470615.874
962692AG1-118 E
Adder
12.45058823529411810.583
941551AE2-152 C
Adder
9.7929411764705888.324
941552AE2-152 E
Adder
6.5282352941176485.549
958011AF2-095 C
Adder
9.557647058823538.124
958012AF2-095 E
Adder
6.3717647058823535.416
965791AG1-447 C
50/50
46.75146.751
274810UNIV PK N;6U
50/50
1.9071.907
274811UNIV PK N;7U
50/50
1.9151.915
274812UNIV PK N;8U
50/50
1.8991.899
274813UNIV PK N;9U
50/50
1.8991.899
274814UNIV PK N;0U
50/50
1.8911.891
274815UNIV PK N;XU
50/50
1.9031.903
274816UNIV PK N;YU
50/50
1.9151.915
920272AA2-123 E
Adder
2.4188235294117652.056
276170Z1-108 E
Adder
2.4670588235294122.097
276626AG1-044 E
Adder
0.061176470588235290.052
276675AE2-062 E
Adder
0.134117647058823540.114
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6070.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.23368.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.47412.474
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7291.729
NYPJM->LTFIMP_NY
CLTF
0.9310.931
WECLTFEXP_WEC->PJM
CLTF
3.2883.288
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4090.409
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.210.21
TVALTFEXP_TVA->PJM
CLTF
1.1671.167
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.4090.409
MECLTFEXP_MEC->PJM
CLTF
10.92410.924
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.1721.172
LAGNLTFEXP_LAGN->PJM
CLTF
2.992.99
SIGELTFEXP_SIGE->PJM
CLTF
0.0150.015
O66PJM->LTFIMP_O-066
CMTX_NF
11.09411.094

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.76 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1444.44
MW Contribution:46.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.22941176470588241.895
962012AG1-044 E
Adder
0.0529411764705882350.045
962781AG1-127 C
Adder
5.94117647058823555.05
962782AG1-127 E
Adder
3.9541176470588243.361
965681AG1-436 C
50/50
63.94963.949
965682AG1-436 E
50/50
42.63342.633
966091AG1-478 C
Adder
1.76941176470588251.504
966092AG1-478 E
Adder
0.44470588235294120.378
966441AG1-513 C
Adder
0.434117647058823550.369
966442AG1-513 E
Adder
0.65058823529411770.553
290021O50 E
Adder
16.3552941176470613.902
290051GSG-6; E
Adder
8.8682352941176487.538
295109WESTBROOK E
Adder
4.7482352941176474.036
295111SUBLETTE E
Adder
2.3082352941176471.962
910542X3-005 E
Adder
0.53764705882352950.457
918052AA1-018 E OP
Adder
14.9023529411764712.667
933911AD1-013 C
Adder
1.56117647058823541.327
933912AD1-013 E
Adder
2.49411764705882362.12
934722AD1-100 E
Adder
76.7823529411764765.265
937002AD2-134 E
Adder
8.5752941176470587.289
937312AD2-172 E
Adder
2.8647058823529412.435
958481AF2-142 C
Adder
10.2776470588235318.736
958482AF2-142 E
Adder
6.8517647058823535.824
958491AF2-143 C
Adder
9.8058823529411778.335
958492AF2-143 E
Adder
6.537647058823535.557
958912AF2-182 E
Adder
28.79647058823529424.477
959081AF2-199 C
Adder
6.0258823529411775.122
959082AF2-199 E
Adder
3.01294117647058852.561
959351AF2-226 C
Adder
2.0270588235294121.723
959352AF2-226 E
Adder
3.0411764705882352.585
960281AF2-319 C
Adder
2.0270588235294121.723
960282AF2-319 E
Adder
3.0411764705882352.585
960582AF2-349 E
Adder
30.726.095
960681AF2-359 C
50/50
63.94963.949
960682AF2-359 E
50/50
42.63342.633
960751AF2-366 C
Adder
5.9247058823529415.036
960752AF2-366 E
Adder
3.94941176470588263.357
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274676JOLIET 29;8U
Adder
62.29647058823529452.952
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
274687WILL CNTY;4U
Adder
56.08235294117647447.67
274859EASYR;U1 E
Adder
10.1270588235294138.608
274860EASYR;U2 E
Adder
10.1270588235294138.608
276591L-013 2
Adder
3.11882352941176462.651
293061N-015 E
Adder
13.20352941176470711.223
293644O22 E1
Adder
11.6458823529411759.899
293645O22 E2
Adder
13.33882352941176411.338
293715O-029 E
Adder
8.1929411764705896.964
293716O-029 E
Adder
4.4917647058823533.818
293717O-029 E
Adder
4.1282352941176473.509
294392P-010 E
Adder
16.76941176470588214.254
294763P-046 E
Adder
7.9611764705882366.767
933411AC2-154 C
Adder
2.1211764705882351.803
933412AC2-154 E
Adder
3.46117647058823552.942
939061AE1-134 2
Adder
1.15294117647058810.98
940502AE2-035 E
Adder
2.8647058823529412.435
957331AF2-027 C
Adder
2.1211764705882351.803
957332AF2-027 E
Adder
3.1823529411764712.705
957471AF2-041 C
Adder
18.07882352941176815.367
957472AF2-041 E
Adder
9.0400000000000017.684
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
274890CAYUG;1U E
Adder
11.4552941176470599.737
274891CAYUG;2U E
Adder
11.4552941176470599.737
938851AE1-113 C
Adder
6.7458823529411775.734
938852AE1-113 E
Adder
23.91882352941176420.331
934101AD2-000 1
Adder
4.91411764705882354.177
934111AD2-000 2
Adder
5.0882352941176484.325
275149KELLYCK ;1E
Adder
15.63058823529411813.286
293516O-009 E
Adder
15.8423529411764713.466
293519PILOT HIL;1E
Adder
15.63058823529411813.286
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
274805UNIV PK N;1U
50/50
1.9131.913
274807UNIV PK N;3U
50/50
1.9251.925
274808UNIV PK N;4U
50/50
1.9171.917
926821AC1-168 C
Adder
0.96235294117647050.818
926822AC1-168 E
Adder
6.4588235294117655.49
936292AD2-038 E
Adder
13.46705882352941211.447
936371AD2-047 C
Adder
3.7964705882352943.227
936372AD2-047 E
Adder
18.53411764705882415.754
936461AD2-060 C
Adder
2.2329411764705881.898
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
942421AE2-255 C
Adder
2.5552941176470592.172
942422AE2-255 E
Adder
7.6658823529411776.516
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
943121AE2-341 C
Adder
10.8588235294117659.23
943122AE2-341 E
Adder
5.3317647058823534.532
943591AF1-030 C
Adder
7.2211764705882366.138
943592AF1-030 E
Adder
3.5729411764705883.037
959091AF2-200 C
Adder
12.05294117647058810.245
959092AF2-200 E
Adder
8.0352941176470596.83
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
938861AE1-114 C
Adder
3.3164705882352942.819
938862AE1-114 E
Adder
11.315294117647069.618
939321AE1-163 C
Adder
5.3388235294117654.538
939322AE1-163 E
Adder
32.7952941176470627.876
939351AE1-166 C
Adder
8.555294117647067.272
939352AE1-166 E
Adder
7.897647058823536.713
939401AE1-172 C
Adder
4.4776470588235293.806
939402AE1-172 E
Adder
20.9647058823529417.82
946152AF1-280 E
Adder
19.1976470588235316.318
946671AF1-331 C
Adder
2.0282352941176471.724
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
941551AE2-152 C
Adder
9.8717647058823528.391
941552AE2-152 E
Adder
6.5811764705882365.594
958011AF2-095 C
Adder
9.6458823529411778.199
958012AF2-095 E
Adder
6.4305882352941185.466
965791AG1-447 C
50/50
46.89646.896
274810UNIV PK N;6U
50/50
1.9171.917
274811UNIV PK N;7U
50/50
1.9251.925
274812UNIV PK N;8U
50/50
1.9091.909
274813UNIV PK N;9U
50/50
1.9091.909
274814UNIV PK N;0U
50/50
1.9011.901
274815UNIV PK N;XU
50/50
1.9131.913
274816UNIV PK N;YU
50/50
1.9251.925
920272AA2-123 E
Adder
2.4364705882352942.071
276170Z1-108 E
Adder
2.48588235294117642.113
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.76 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1444.44
MW Contribution:46.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
272363ESS H440 ; R
Adder
2.22941176470588241.895
962012AG1-044 E
Adder
0.0529411764705882350.045
962781AG1-127 C
Adder
5.94117647058823555.05
962782AG1-127 E
Adder
3.9541176470588243.361
965681AG1-436 C
50/50
63.94963.949
965682AG1-436 E
50/50
42.63342.633
966091AG1-478 C
Adder
1.76941176470588251.504
966092AG1-478 E
Adder
0.44470588235294120.378
966441AG1-513 C
Adder
0.434117647058823550.369
966442AG1-513 E
Adder
0.65058823529411770.553
290021O50 E
Adder
16.3552941176470613.902
290051GSG-6; E
Adder
8.8682352941176487.538
295109WESTBROOK E
Adder
4.7482352941176474.036
295111SUBLETTE E
Adder
2.3082352941176471.962
910542X3-005 E
Adder
0.53764705882352950.457
918052AA1-018 E OP
Adder
14.9023529411764712.667
933911AD1-013 C
Adder
1.56117647058823541.327
933912AD1-013 E
Adder
2.49411764705882362.12
934722AD1-100 E
Adder
76.7823529411764765.265
937002AD2-134 E
Adder
8.5752941176470587.289
937312AD2-172 E
Adder
2.8647058823529412.435
958481AF2-142 C
Adder
10.2776470588235318.736
958482AF2-142 E
Adder
6.8517647058823535.824
958491AF2-143 C
Adder
9.8058823529411778.335
958492AF2-143 E
Adder
6.537647058823535.557
958912AF2-182 E
Adder
28.79647058823529424.477
959081AF2-199 C
Adder
6.0258823529411775.122
959082AF2-199 E
Adder
3.01294117647058852.561
959351AF2-226 C
Adder
2.0270588235294121.723
959352AF2-226 E
Adder
3.0411764705882352.585
960281AF2-319 C
Adder
2.0270588235294121.723
960282AF2-319 E
Adder
3.0411764705882352.585
960582AF2-349 E
Adder
30.726.095
960681AF2-359 C
50/50
63.94963.949
960682AF2-359 E
50/50
42.63342.633
960751AF2-366 C
Adder
5.9247058823529415.036
960752AF2-366 E
Adder
3.94941176470588263.357
274675JOLIET 29;7U
Adder
62.3188235294117652.971
274676JOLIET 29;8U
Adder
62.29647058823529452.952
274682WAUKEGAN ;7U
Adder
35.0952941176470629.831
274683WAUKEGAN ;8U
Adder
37.83647058823529432.161
274687WILL CNTY;4U
Adder
56.08235294117647447.67
274859EASYR;U1 E
Adder
10.1270588235294138.608
274860EASYR;U2 E
Adder
10.1270588235294138.608
276591L-013 2
Adder
3.11882352941176462.651
293061N-015 E
Adder
13.20352941176470711.223
293644O22 E1
Adder
11.6458823529411759.899
293645O22 E2
Adder
13.33882352941176411.338
293715O-029 E
Adder
8.1929411764705896.964
293716O-029 E
Adder
4.4917647058823533.818
293717O-029 E
Adder
4.1282352941176473.509
294392P-010 E
Adder
16.76941176470588214.254
294763P-046 E
Adder
7.9611764705882366.767
933411AC2-154 C
Adder
2.1211764705882351.803
933412AC2-154 E
Adder
3.46117647058823552.942
939061AE1-134 2
Adder
1.15294117647058810.98
940502AE2-035 E
Adder
2.8647058823529412.435
957331AF2-027 C
Adder
2.1211764705882351.803
957332AF2-027 E
Adder
3.1823529411764712.705
957471AF2-041 C
Adder
18.07882352941176815.367
957472AF2-041 E
Adder
9.0400000000000017.684
274674JOLIET 9 ;6U
Adder
31.29764705882353226.603
274890CAYUG;1U E
Adder
11.4552941176470599.737
274891CAYUG;2U E
Adder
11.4552941176470599.737
938851AE1-113 C
Adder
6.7458823529411775.734
938852AE1-113 E
Adder
23.91882352941176420.331
934101AD2-000 1
Adder
4.91411764705882354.177
934111AD2-000 2
Adder
5.0882352941176484.325
275149KELLYCK ;1E
Adder
15.63058823529411813.286
293516O-009 E
Adder
15.8423529411764713.466
293519PILOT HIL;1E
Adder
15.63058823529411813.286
290108LEEDK;1U E
Adder
20.36117647058823417.307
916221Z1-073 E
Adder
6.2494117647058835.312
274805UNIV PK N;1U
50/50
1.9131.913
274807UNIV PK N;3U
50/50
1.9251.925
274808UNIV PK N;4U
50/50
1.9171.917
926821AC1-168 C
Adder
0.96235294117647050.818
926822AC1-168 E
Adder
6.4588235294117655.49
936292AD2-038 E
Adder
13.46705882352941211.447
936371AD2-047 C
Adder
3.7964705882352943.227
936372AD2-047 E
Adder
18.53411764705882415.754
936461AD2-060 C
Adder
2.2329411764705881.898
936511AD2-066 C
Adder
7.17882352941176556.102
936512AD2-066 E
Adder
4.7858823529411764.068
942421AE2-255 C
Adder
2.5552941176470592.172
942422AE2-255 E
Adder
7.6658823529411776.516
942651AE2-281 C
Adder
0.76235294117647070.648
942652AE2-281 E
Adder
4.6847058823529423.982
943121AE2-341 C
Adder
10.8588235294117659.23
943122AE2-341 E
Adder
5.3317647058823534.532
943591AF1-030 C
Adder
7.2211764705882366.138
943592AF1-030 E
Adder
3.5729411764705883.037
959091AF2-200 C
Adder
12.05294117647058810.245
959092AF2-200 E
Adder
8.0352941176470596.83
960591AF2-350 C
Adder
6.6988235294117655.694
960592AF2-350 E
Adder
4.4658823529411763.796
938861AE1-114 C
Adder
3.3164705882352942.819
938862AE1-114 E
Adder
11.315294117647069.618
939321AE1-163 C
Adder
5.3388235294117654.538
939322AE1-163 E
Adder
32.7952941176470627.876
939351AE1-166 C
Adder
8.555294117647067.272
939352AE1-166 E
Adder
7.897647058823536.713
939401AE1-172 C
Adder
4.4776470588235293.806
939402AE1-172 E
Adder
20.9658823529411817.821
946152AF1-280 E
Adder
19.1976470588235316.318
946671AF1-331 C
Adder
2.0282352941176471.724
962691AG1-118 C
Adder
18.81411764705882615.992
962692AG1-118 E
Adder
12.54235294117647110.661
941551AE2-152 C
Adder
9.8717647058823528.391
941552AE2-152 E
Adder
6.5811764705882365.594
958011AF2-095 C
Adder
9.6458823529411778.199
958012AF2-095 E
Adder
6.4305882352941185.466
965791AG1-447 C
50/50
46.89646.896
274810UNIV PK N;6U
50/50
1.9171.917
274811UNIV PK N;7U
50/50
1.9251.925
274812UNIV PK N;8U
50/50
1.9091.909
274813UNIV PK N;9U
50/50
1.9091.909
274814UNIV PK N;0U
50/50
1.9011.901
274815UNIV PK N;XU
50/50
1.9131.913
274816UNIV PK N;YU
50/50
1.9251.925
920272AA2-123 E
Adder
2.4364705882352942.071
276170Z1-108 E
Adder
2.48588235294117642.113
276626AG1-044 E
Adder
0.062352941176470590.053
276675AE2-062 E
Adder
0.135294117647058840.115
LTFEXP_AC1-131LTFEXP_AC1-131->LTFIMP_AC1-131
CLTF
0.6510.651
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.52969.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.78511.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
G-007PJM->LTFIMP_G-007
CMTX_NF
1.7371.737
NYPJM->LTFIMP_NY
CLTF
0.9330.933
WECLTFEXP_WEC->PJM
CLTF
3.3113.311
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4450.445
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.2340.234
TVALTFEXP_TVA->PJM
CLTF
1.0321.032
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5250.525
MECLTFEXP_MEC->PJM
CLTF
10.92110.921
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.5241.524
LAGNLTFEXP_LAGN->PJM
CLTF
2.8452.845
O66PJM->LTFIMP_O-066
CMTX_NF
11.14211.142
CONTINGENCY 'AEP_P7-1_#11046___SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 246955 CKT 1   /*05DUMONT     345.0 - 05OLIVE_BP   345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243234 CKT 1   /*05MERIDN     345.0 - 05TWIN B     345.0
 OPEN BRANCH FROM BUS 243232 TO BUS 246955 CKT 1   /*05SORENS     345.0 - 05OLIVE_BP   345.0
END
CONTINGENCY 'AEP_P4_#9247_05OLIVE 138_R1_SRT-SL'
 OPEN BRANCH FROM BUS 243297 TO BUS 243352 CKT 1                /*05GERMAN     138.0 - 05NTRDAM     138.0
 OPEN BRANCH FROM BUS 243297 TO BUS 243353 CKT 1                /*05GERMAN     138.0 - 05OLIVE      138.0
 OPEN BRANCH FROM BUS 243353 TO BUS 244173 CKT 1                /*05OLIVE      138.0 - 05SILVER LAK 138.0
 REMOVE LOAD D5 FROM BUS 243353                                 /*05OLIVE      138.0
 SET POSTCONTRATING 337 BRANCH FROM BUS 243353 TO BUS 244930 CKT 1 /*05OLIVE      138.0 - 05NEW CARLI1 138.0
 SET PRECONTRATING 287 BRANCH FROM BUS 243353 TO BUS 244930 CKT 1 /*05OLIVE      138.0 - 05NEW CARLI1 138.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-022T_SRT-A-1'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 955780 CKT 1   /*02LEMOYN     345.0 - J1062 POI    345.0
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-022T_SRT-A-2'
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
 DISCONNECT BRANCH FROM BUS 264599 TO BUS 955780 CKT 1   /*19MAJTC      345.0 - J1062 POI    345.0
END
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243207 CKT 1   /*05DUMONT     765.0 - 05GRNTWN     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
243206 to 246999 ckt 1
243353 to 244930 ckt 1
256583 to 238530 ckt 1
960680 to 243229 ckt 1

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AG1-447 was evaluated as a 55.0 MW injection and 55.0 MW withdrawal in the AEP area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC124.77 %971.0B1211.5646.68
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC124.6 %971.0B1209.946.68
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC110.59 %971.0B1073.8146.68
GD1AEP/CE
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC110.59 %971.0B1073.846.68
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC121.46 %970.0STE1178.148.32
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC121.2 %970.0STE1175.668.32
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC107.66 %970.0STE1044.288.32
GD1CE
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC107.66 %970.0STE1044.268.32

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.77 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1211.56
MW Contribution:46.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.730.73
274848CAMPGROVE;RU
80/20
0.2780.278
274849CRESCENT ;1U
80/20
0.2120.212
274850MENDOTA H;RU
80/20
0.3520.352
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274856ECOGROVE ;U1
80/20
0.4620.462
274857BIG SKY ;U1
80/20
0.3530.353
274858BIG SKY ;U2
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274860EASYR;U2 E
80/20
2.4372.437
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
274864CAYUGA RI;2U
80/20
0.5160.516
274871GR RIDGE ;2U
80/20
0.2720.272
274872LEE DEKAL;1U
80/20
0.9950.995
274877BISHOP HL;1U
80/20
0.4330.433
274878BISHOP HL;2U
80/20
0.4330.433
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274887PILOT HIL;1U
80/20
0.9460.946
274888KELLY CRK;1U
80/20
0.9460.946
276156O-029 C
80/20
0.2490.249
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
276615W2-048 GEN
80/20
0.8910.891
276621X2-022 GEN
80/20
2.5362.536
290021O50 E
80/20
3.9653.965
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
293061N-015 E
80/20
3.1963.196
293644O22 E1
80/20
2.822.82
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293716O-029 E
80/20
1.081.08
293717O-029 E
80/20
0.9930.993
293771O-035 E
80/20
1.3921.392
294392P-010 E
80/20
4.0594.059
294401BSHIL;1U E
80/20
1.7331.733
294410BSHIL;2U E
80/20
1.7331.733
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
295111SUBLETTE E
80/20
0.5570.557
917502Z2-087 E
80/20
3.3333.333
918052AA1-018 E OP
80/20
3.6223.622
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
934721AD1-100 C
80/20
3.8223.822
934722AD1-100 E
80/20
59.4559.45
937001AD2-134 C
80/20
0.8290.829
937002AD2-134 E
80/20
3.3123.312
942111AE2-223 C
80/20
1.1951.195
942112AE2-223 E
80/20
7.9997.999
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959351AF2-226 C
80/20
1.9641.964
959352AF2-226 E
80/20
2.9452.945
959611AF2-252 C
80/20
1.4511.451
959612AF2-252 E
80/20
2.1762.176
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
962012AG1-044 E
80/20
0.0450.045
966091AG1-478 C
80/20
0.4310.431
966092AG1-478 E
80/20
0.6470.647
966441AG1-513 C
80/20
0.4190.419
966442AG1-513 E
80/20
0.6290.629
274674JOLIET 9 ;6U
80/20
13.64413.644
274675JOLIET 29;7U
80/20
36.25136.251
274676JOLIET 29;8U
80/20
36.23736.237
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274687WILL CNTY;4U
80/20
32.59232.592
274890CAYUG;1U E
80/20
2.7522.752
274891CAYUG;2U E
80/20
2.7522.752
925771AC1-053 C
80/20
0.590.59
925772AC1-053 E
80/20
3.953.95
938851AE1-113 C
80/20
5.2345.234
938852AE1-113 E
80/20
18.55518.555
939401AE1-172 C
80/20
3.453.45
939402AE1-172 E
80/20
16.15416.154
942651AE2-281 C
80/20
0.5930.593
942652AE2-281 E
80/20
3.6423.642
270681BRIGHTSTK; R
80/20
0.4980.498
270839OTTER CRK; R
80/20
0.5410.541
274881WALNUT RG;1U
80/20
0.9520.952
275149KELLYCK ;1E
80/20
3.7863.786
276174W4-005 E
80/20
3.7663.766
276602WESTBROOK C
80/20
0.1730.173
276603SUBLETTE C
80/20
0.0780.078
276626AG1-044 E
80/20
0.0510.051
276627AG1-044 BAT
80/20
0.0090.009
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
276655AB2-047 C1
80/20
0.3110.311
276656AB2-047 C2
80/20
0.3110.311
276668AB2-070 C
80/20
0.3750.375
276675AE2-062 E
80/20
0.1120.112
293516O-009 E
80/20
3.8093.809
293519PILOT HIL;1E
80/20
3.7863.786
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
924048AB2-047 E1
80/20
2.0672.067
924049AB2-047 E2
80/20
2.0992.099
924266AB2-070 E
80/20
2.272.27
926821AC1-168 C
80/20
0.7420.742
926822AC1-168 E
80/20
4.9814.981
927208AC1-214 E1
80/20
0.660.66
927209AC1-214 E2
80/20
0.660.66
935141AD1-148 C
80/20
0.7970.797
936371AD2-047 C
80/20
2.9422.942
936372AD2-047 E
80/20
14.36514.365
938861AE1-114 C
80/20
2.5552.555
938862AE1-114 E
80/20
8.7168.716
939321AE1-163 C
80/20
4.1514.151
939322AE1-163 E
80/20
25.49625.496
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
946321AF1-296 C
80/20
2.2942.294
946322AF1-296 E
80/20
10.73910.739
957371AF2-031 C
80/20
0.6360.636
957372AF2-031 E
80/20
0.9540.954
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
961502AF2-441 E
80/20
10.40210.402
965331AG1-398 C
80/20
0.1690.169
965791AG1-447 C
80/20
46.67646.676
990901L-005 E
80/20
2.5642.564
276170Z1-108 E
80/20
2.0422.042
920272AA2-123 E
80/20
22
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.6 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1209.9
MW Contribution:46.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.730.73
274848CAMPGROVE;RU
80/20
0.2780.278
274849CRESCENT ;1U
80/20
0.2120.212
274850MENDOTA H;RU
80/20
0.3520.352
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274856ECOGROVE ;U1
80/20
0.4620.462
274857BIG SKY ;U1
80/20
0.3530.353
274858BIG SKY ;U2
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274860EASYR;U2 E
80/20
2.4372.437
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
274864CAYUGA RI;2U
80/20
0.5160.516
274871GR RIDGE ;2U
80/20
0.2720.272
274872LEE DEKAL;1U
80/20
0.9950.995
274877BISHOP HL;1U
80/20
0.4330.433
274878BISHOP HL;2U
80/20
0.4330.433
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274887PILOT HIL;1U
80/20
0.9460.946
274888KELLY CRK;1U
80/20
0.9460.946
276156O-029 C
80/20
0.2490.249
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
276615W2-048 GEN
80/20
0.8910.891
276621X2-022 GEN
80/20
2.5362.536
290021O50 E
80/20
3.9653.965
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
293061N-015 E
80/20
3.1963.196
293644O22 E1
80/20
2.822.82
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293716O-029 E
80/20
1.081.08
293717O-029 E
80/20
0.9930.993
293771O-035 E
80/20
1.3921.392
294392P-010 E
80/20
4.0594.059
294401BSHIL;1U E
80/20
1.7331.733
294410BSHIL;2U E
80/20
1.7331.733
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
295111SUBLETTE E
80/20
0.5570.557
917502Z2-087 E
80/20
3.3333.333
918052AA1-018 E OP
80/20
3.6223.622
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
934721AD1-100 C
80/20
3.8223.822
934722AD1-100 E
80/20
59.4559.45
937001AD2-134 C
80/20
0.8290.829
937002AD2-134 E
80/20
3.3123.312
942111AE2-223 C
80/20
1.1951.195
942112AE2-223 E
80/20
7.9997.999
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959351AF2-226 C
80/20
1.9641.964
959352AF2-226 E
80/20
2.9452.945
959611AF2-252 C
80/20
1.4511.451
959612AF2-252 E
80/20
2.1762.176
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
962012AG1-044 E
80/20
0.0450.045
966091AG1-478 C
80/20
0.4310.431
966092AG1-478 E
80/20
0.6470.647
966441AG1-513 C
80/20
0.4190.419
966442AG1-513 E
80/20
0.6290.629
274674JOLIET 9 ;6U
80/20
13.64413.644
274675JOLIET 29;7U
80/20
36.25136.251
274676JOLIET 29;8U
80/20
36.23736.237
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274687WILL CNTY;4U
80/20
32.59232.592
274890CAYUG;1U E
80/20
2.7522.752
274891CAYUG;2U E
80/20
2.7522.752
925771AC1-053 C
80/20
0.590.59
925772AC1-053 E
80/20
3.953.95
938851AE1-113 C
80/20
5.2345.234
938852AE1-113 E
80/20
18.55518.555
939401AE1-172 C
80/20
3.453.45
939402AE1-172 E
80/20
16.15416.154
942651AE2-281 C
80/20
0.5930.593
942652AE2-281 E
80/20
3.6423.642
270681BRIGHTSTK; R
80/20
0.4980.498
270839OTTER CRK; R
80/20
0.5410.541
274881WALNUT RG;1U
80/20
0.9520.952
275149KELLYCK ;1E
80/20
3.7863.786
276174W4-005 E
80/20
3.7663.766
276602WESTBROOK C
80/20
0.1730.173
276603SUBLETTE C
80/20
0.0780.078
276626AG1-044 E
80/20
0.0510.051
276627AG1-044 BAT
80/20
0.0090.009
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
276655AB2-047 C1
80/20
0.3110.311
276656AB2-047 C2
80/20
0.3110.311
276668AB2-070 C
80/20
0.3750.375
276675AE2-062 E
80/20
0.1120.112
293516O-009 E
80/20
3.8093.809
293519PILOT HIL;1E
80/20
3.7863.786
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
924048AB2-047 E1
80/20
2.0672.067
924049AB2-047 E2
80/20
2.0992.099
924266AB2-070 E
80/20
2.272.27
926821AC1-168 C
80/20
0.7420.742
926822AC1-168 E
80/20
4.9814.981
927208AC1-214 E1
80/20
0.660.66
927209AC1-214 E2
80/20
0.660.66
935141AD1-148 C
80/20
0.7970.797
936371AD2-047 C
80/20
2.9422.942
936372AD2-047 E
80/20
14.36514.365
938861AE1-114 C
80/20
2.5552.555
938862AE1-114 E
80/20
8.7168.716
939321AE1-163 C
80/20
4.1514.151
939322AE1-163 E
80/20
25.49625.496
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
946321AF1-296 C
80/20
2.2942.294
946322AF1-296 E
80/20
10.73910.739
957371AF2-031 C
80/20
0.6360.636
957372AF2-031 E
80/20
0.9540.954
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
961502AF2-441 E
80/20
10.40210.402
965331AG1-398 C
80/20
0.1690.169
965791AG1-447 C
80/20
46.67646.676
990901L-005 E
80/20
2.5642.564
276170Z1-108 E
80/20
2.0422.042
920272AA2-123 E
80/20
22
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.59 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1073.81
MW Contribution:46.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.730.73
274871GR RIDGE ;2U
50/50
0.2720.272
274887PILOT HIL;1U
50/50
0.9460.946
274888KELLY CRK;1U
50/50
0.9460.946
293061N-015 E
50/50
3.1963.196
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
934721AD1-100 C
50/50
3.8213.821
934722AD1-100 E
50/50
59.44459.444
942111AE2-223 C
Adder
1.19529411764705881.016
942112AE2-223 E
Adder
7.9988235294117666.799
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959351AF2-226 C
Adder
1.9635294117647061.669
959352AF2-226 E
Adder
2.94588235294117642.504
959611AF2-252 C
Adder
1.45058823529411771.233
959612AF2-252 E
Adder
2.17647058823529441.85
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
962012AG1-044 E
Adder
0.044705882352941180.038
966091AG1-478 C
50/50
0.4310.431
966092AG1-478 E
50/50
0.6470.647
966441AG1-513 C
50/50
0.420.42
966442AG1-513 E
50/50
0.6290.629
274674JOLIET 9 ;6U
50/50
13.64513.645
274675JOLIET 29;7U
50/50
36.25136.251
274676JOLIET 29;8U
50/50
36.23736.237
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
274687WILL CNTY;4U
50/50
32.59532.595
938851AE1-113 C
Adder
5.2341176470588244.449
938852AE1-113 E
Adder
18.5576470588235315.774
939401AE1-172 C
Adder
3.45058823529411772.933
939402AE1-172 E
Adder
16.15411764705882513.731
942651AE2-281 C
50/50
0.5930.593
942652AE2-281 E
50/50
3.6423.642
270839OTTER CRK; R
50/50
0.5410.541
275149KELLYCK ;1E
50/50
3.7853.785
276626AG1-044 E
Adder
0.050588235294117640.043
276627AG1-044 BAT
Adder
0.0094117647058823540.008
276675AE2-062 E
50/50
0.1120.112
293519PILOT HIL;1E
50/50
3.7853.785
926821AC1-168 C
Adder
0.74235294117647070.631
926822AC1-168 E
Adder
4.98117647058823554.234
936371AD2-047 C
50/50
2.9422.942
936372AD2-047 E
50/50
14.36514.365
938861AE1-114 C
Adder
2.5552941176470592.172
938862AE1-114 E
Adder
8.717647058823537.41
939321AE1-163 C
50/50
4.1514.151
939322AE1-163 E
50/50
25.49625.496
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
946321AF1-296 C
Adder
2.29411764705882341.95
946322AF1-296 E
Adder
10.749.129
957371AF2-031 C
Adder
0.63647058823529420.541
957372AF2-031 E
Adder
0.95411764705882360.811
961501AF2-441 C
Adder
6.9341176470588245.894
961502AF2-441 E
Adder
10.48.84
965791AG1-447 C
50/50
46.67546.675
276170Z1-108 E
50/50
2.0432.043
920272AA2-123 E
Adder
2.35294117647058832
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
990947J1432 G
External Queue
12.502512.5025
991302J1755
External Queue
8.07698.0769

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.59 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1073.8
MW Contribution:46.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.730.73
274871GR RIDGE ;2U
50/50
0.2720.272
274887PILOT HIL;1U
50/50
0.9460.946
274888KELLY CRK;1U
50/50
0.9460.946
293061N-015 E
50/50
3.1963.196
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
934721AD1-100 C
50/50
3.8213.821
934722AD1-100 E
50/50
59.44459.444
942111AE2-223 C
Adder
1.19529411764705881.016
942112AE2-223 E
Adder
7.9988235294117666.799
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959351AF2-226 C
Adder
1.9635294117647061.669
959352AF2-226 E
Adder
2.94588235294117642.504
959611AF2-252 C
Adder
1.45058823529411771.233
959612AF2-252 E
Adder
2.17647058823529441.85
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
962012AG1-044 E
Adder
0.044705882352941180.038
966091AG1-478 C
50/50
0.4310.431
966092AG1-478 E
50/50
0.6470.647
966441AG1-513 C
50/50
0.420.42
966442AG1-513 E
50/50
0.6290.629
274674JOLIET 9 ;6U
50/50
13.64513.645
274675JOLIET 29;7U
50/50
36.25136.251
274676JOLIET 29;8U
50/50
36.23736.237
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
274687WILL CNTY;4U
50/50
32.59532.595
938851AE1-113 C
Adder
5.2341176470588244.449
938852AE1-113 E
Adder
18.5576470588235315.774
939401AE1-172 C
Adder
3.45058823529411772.933
939402AE1-172 E
Adder
16.15411764705882513.731
942651AE2-281 C
50/50
0.5930.593
942652AE2-281 E
50/50
3.6423.642
270839OTTER CRK; R
50/50
0.5410.541
275149KELLYCK ;1E
50/50
3.7853.785
276626AG1-044 E
Adder
0.050588235294117640.043
276627AG1-044 BAT
Adder
0.0094117647058823540.008
276675AE2-062 E
50/50
0.1120.112
293519PILOT HIL;1E
50/50
3.7853.785
926821AC1-168 C
Adder
0.74235294117647070.631
926822AC1-168 E
Adder
4.98117647058823554.234
936371AD2-047 C
50/50
2.9422.942
936372AD2-047 E
50/50
14.36514.365
938861AE1-114 C
Adder
2.5552941176470592.172
938862AE1-114 E
Adder
8.717647058823537.41
939321AE1-163 C
50/50
4.1514.151
939322AE1-163 E
50/50
25.49625.496
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
946321AF1-296 C
Adder
2.29411764705882341.95
946322AF1-296 E
Adder
10.749.129
957371AF2-031 C
Adder
0.63647058823529420.541
957372AF2-031 E
Adder
0.95411764705882360.811
961501AF2-441 C
Adder
6.9341176470588245.894
961502AF2-441 E
Adder
10.48.84
965791AG1-447 C
50/50
46.67546.675
276170Z1-108 E
50/50
2.0432.043
920272AA2-123 E
Adder
2.35294117647058832
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
990947J1432 G
External Queue
12.502512.5025
991302J1755
External Queue
8.07698.0769

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.46 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1178.14
MW Contribution:8.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.730.73
274848CAMPGROVE;RU
80/20
0.2780.278
274849CRESCENT ;1U
80/20
0.2120.212
274850MENDOTA H;RU
80/20
0.3520.352
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274856ECOGROVE ;U1
80/20
0.4620.462
274857BIG SKY ;U1
80/20
0.3530.353
274858BIG SKY ;U2
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274860EASYR;U2 E
80/20
2.4372.437
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
274864CAYUGA RI;2U
80/20
0.5160.516
274871GR RIDGE ;2U
80/20
0.2720.272
274872LEE DEKAL;1U
80/20
0.9950.995
274877BISHOP HL;1U
80/20
0.4330.433
274878BISHOP HL;2U
80/20
0.4330.433
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274887PILOT HIL;1U
80/20
0.9460.946
274888KELLY CRK;1U
80/20
0.9460.946
276156O-029 C
80/20
0.2490.249
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
276615W2-048 GEN
80/20
0.8910.891
276621X2-022 GEN
80/20
2.5362.536
290021O50 E
80/20
3.9653.965
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
293061N-015 E
80/20
3.1963.196
293644O22 E1
80/20
2.822.82
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293716O-029 E
80/20
1.081.08
293717O-029 E
80/20
0.9930.993
293771O-035 E
80/20
1.3921.392
294392P-010 E
80/20
4.0594.059
294401BSHIL;1U E
80/20
1.7331.733
294410BSHIL;2U E
80/20
1.7331.733
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
295111SUBLETTE E
80/20
0.5570.557
917502Z2-087 E
80/20
3.3333.333
918052AA1-018 E OP
80/20
3.6223.622
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
934721AD1-100 C
80/20
3.8223.822
934722AD1-100 E
80/20
59.4559.45
937001AD2-134 C
80/20
0.8290.829
937002AD2-134 E
80/20
3.3123.312
942111AE2-223 C
80/20
1.1951.195
942112AE2-223 E
80/20
7.9997.999
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959351AF2-226 C
80/20
1.9641.964
959352AF2-226 E
80/20
2.9452.945
959611AF2-252 C
80/20
1.4511.451
959612AF2-252 E
80/20
2.1762.176
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
962012AG1-044 E
80/20
0.0450.045
966091AG1-478 C
80/20
0.4310.431
966092AG1-478 E
80/20
0.6470.647
966441AG1-513 C
80/20
0.4190.419
966442AG1-513 E
80/20
0.6290.629
274674JOLIET 9 ;6U
80/20
13.64413.644
274675JOLIET 29;7U
80/20
36.25136.251
274676JOLIET 29;8U
80/20
36.23736.237
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274687WILL CNTY;4U
80/20
32.59232.592
274890CAYUG;1U E
80/20
2.7522.752
274891CAYUG;2U E
80/20
2.7522.752
925771AC1-053 C
80/20
0.590.59
925772AC1-053 E
80/20
3.953.95
938851AE1-113 C
80/20
5.2345.234
938852AE1-113 E
80/20
18.55518.555
939401AE1-172 C
80/20
3.453.45
939402AE1-172 E
80/20
16.15416.154
942651AE2-281 C
80/20
0.5930.593
942652AE2-281 E
80/20
3.6423.642
270681BRIGHTSTK; R
80/20
0.4980.498
270839OTTER CRK; R
80/20
0.5410.541
274881WALNUT RG;1U
80/20
0.9520.952
275149KELLYCK ;1E
80/20
3.7863.786
276174W4-005 E
80/20
3.7663.766
276602WESTBROOK C
80/20
0.1730.173
276603SUBLETTE C
80/20
0.0780.078
276626AG1-044 E
80/20
0.0510.051
276627AG1-044 BAT
80/20
0.0090.009
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
276655AB2-047 C1
80/20
0.3110.311
276656AB2-047 C2
80/20
0.3110.311
276668AB2-070 C
80/20
0.3750.375
276675AE2-062 E
80/20
0.1120.112
293516O-009 E
80/20
3.8093.809
293519PILOT HIL;1E
80/20
3.7863.786
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
924048AB2-047 E1
80/20
2.0672.067
924049AB2-047 E2
80/20
2.0992.099
924266AB2-070 E
80/20
2.272.27
926821AC1-168 C
80/20
0.7420.742
926822AC1-168 E
80/20
4.9814.981
927208AC1-214 E1
80/20
0.660.66
927209AC1-214 E2
80/20
0.660.66
935141AD1-148 C
80/20
0.7970.797
936371AD2-047 C
80/20
2.9422.942
936372AD2-047 E
80/20
14.36514.365
938861AE1-114 C
80/20
2.5552.555
938862AE1-114 E
80/20
8.7168.716
939321AE1-163 C
80/20
4.1514.151
939322AE1-163 E
80/20
25.49625.496
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
946321AF1-296 C
80/20
2.2942.294
946322AF1-296 E
80/20
10.73910.739
957371AF2-031 C
80/20
0.6360.636
957372AF2-031 E
80/20
0.9540.954
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
961502AF2-441 E
80/20
10.40210.402
965331AG1-398 C
80/20
0.1690.169
990901L-005 E
80/20
2.5642.564
276170Z1-108 E
80/20
2.0422.042
920272AA2-123 E
80/20
22
965793AG1-447 BT
80/20
8.3248.324
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.2 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1175.66
MW Contribution:8.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
80/20
0.730.73
274848CAMPGROVE;RU
80/20
0.2780.278
274849CRESCENT ;1U
80/20
0.2120.212
274850MENDOTA H;RU
80/20
0.3520.352
274851PROVIDENC;RU
80/20
0.2250.225
274853TWINGROVE;U1
80/20
0.6310.631
274854TWINGROVE;U2
80/20
0.6490.649
274855GSG-6 ;RU
80/20
0.5350.535
274856ECOGROVE ;U1
80/20
0.4620.462
274857BIG SKY ;U1
80/20
0.3530.353
274858BIG SKY ;U2
80/20
0.3530.353
274859EASYR;U1 E
80/20
2.4372.437
274860EASYR;U2 E
80/20
2.4372.437
274861TOP CROP ;1U
80/20
0.4520.452
274862TOP CROP ;2U
80/20
0.8620.862
274863CAYUGA RI;1U
80/20
0.5160.516
274864CAYUGA RI;2U
80/20
0.5160.516
274871GR RIDGE ;2U
80/20
0.2720.272
274872LEE DEKAL;1U
80/20
0.9950.995
274877BISHOP HL;1U
80/20
0.4330.433
274878BISHOP HL;2U
80/20
0.4330.433
274879MINONK ;1U
80/20
0.9910.991
274880RADFORD R;1U
80/20
0.6590.659
274887PILOT HIL;1U
80/20
0.9460.946
274888KELLY CRK;1U
80/20
0.9460.946
276156O-029 C
80/20
0.2490.249
276157O-029 C
80/20
0.4490.449
276158O-029 C
80/20
0.4490.449
276615W2-048 GEN
80/20
0.8910.891
276621X2-022 GEN
80/20
2.5362.536
290021O50 E
80/20
3.9653.965
290051GSG-6; E
80/20
2.1392.139
290108LEEDK;1U E
80/20
4.9144.914
290261S-027 E
80/20
2.962.96
290265S-028 E
80/20
2.9422.942
293061N-015 E
80/20
3.1963.196
293644O22 E1
80/20
2.822.82
293645O22 E2
80/20
3.233.23
293715O-029 E
80/20
1.971.97
293716O-029 E
80/20
1.081.08
293717O-029 E
80/20
0.9930.993
293771O-035 E
80/20
1.3921.392
294392P-010 E
80/20
4.0594.059
294401BSHIL;1U E
80/20
1.7331.733
294410BSHIL;2U E
80/20
1.7331.733
294763P-046 E
80/20
1.9171.917
295109WESTBROOK E
80/20
1.1451.145
295111SUBLETTE E
80/20
0.5570.557
917502Z2-087 E
80/20
3.3333.333
918052AA1-018 E OP
80/20
3.6223.622
925581AC1-033 C
80/20
0.4550.455
925582AC1-033 E
80/20
3.0433.043
934721AD1-100 C
80/20
3.8223.822
934722AD1-100 E
80/20
59.4559.45
937001AD2-134 C
80/20
0.8290.829
937002AD2-134 E
80/20
3.3123.312
942111AE2-223 C
80/20
1.1951.195
942112AE2-223 E
80/20
7.9997.999
957331AF2-027 C
80/20
2.0512.051
957332AF2-027 E
80/20
3.0763.076
959351AF2-226 C
80/20
1.9641.964
959352AF2-226 E
80/20
2.9452.945
959611AF2-252 C
80/20
1.4511.451
959612AF2-252 E
80/20
2.1762.176
960281AF2-319 C
80/20
1.9641.964
960282AF2-319 E
80/20
2.9452.945
960611AF2-352 C
80/20
1.4511.451
960612AF2-352 E
80/20
2.1762.176
962012AG1-044 E
80/20
0.0450.045
966091AG1-478 C
80/20
0.4310.431
966092AG1-478 E
80/20
0.6470.647
966441AG1-513 C
80/20
0.4190.419
966442AG1-513 E
80/20
0.6290.629
274674JOLIET 9 ;6U
80/20
13.64413.644
274675JOLIET 29;7U
80/20
36.25136.251
274676JOLIET 29;8U
80/20
36.23736.237
274682WAUKEGAN ;7U
80/20
15.27215.272
274683WAUKEGAN ;8U
80/20
16.46316.463
274687WILL CNTY;4U
80/20
32.59232.592
274890CAYUG;1U E
80/20
2.7522.752
274891CAYUG;2U E
80/20
2.7522.752
925771AC1-053 C
80/20
0.590.59
925772AC1-053 E
80/20
3.953.95
938851AE1-113 C
80/20
5.2345.234
938852AE1-113 E
80/20
18.55518.555
939401AE1-172 C
80/20
3.453.45
939402AE1-172 E
80/20
16.15416.154
942651AE2-281 C
80/20
0.5930.593
942652AE2-281 E
80/20
3.6423.642
270681BRIGHTSTK; R
80/20
0.4980.498
270839OTTER CRK; R
80/20
0.5410.541
274881WALNUT RG;1U
80/20
0.9520.952
275149KELLYCK ;1E
80/20
3.7863.786
276174W4-005 E
80/20
3.7663.766
276602WESTBROOK C
80/20
0.1730.173
276603SUBLETTE C
80/20
0.0780.078
276626AG1-044 E
80/20
0.0510.051
276627AG1-044 BAT
80/20
0.0090.009
276645AC1-214 C1
80/20
0.1860.186
276646AC1-214 C2
80/20
0.1860.186
276655AB2-047 C1
80/20
0.3110.311
276656AB2-047 C2
80/20
0.3110.311
276668AB2-070 C
80/20
0.3750.375
276675AE2-062 E
80/20
0.1120.112
293516O-009 E
80/20
3.8093.809
293519PILOT HIL;1E
80/20
3.7863.786
916212CRESCENT ;1U
80/20
0.9780.978
916221Z1-073 E
80/20
1.5071.507
924048AB2-047 E1
80/20
2.0672.067
924049AB2-047 E2
80/20
2.0992.099
924266AB2-070 E
80/20
2.272.27
926821AC1-168 C
80/20
0.7420.742
926822AC1-168 E
80/20
4.9814.981
927208AC1-214 E1
80/20
0.660.66
927209AC1-214 E2
80/20
0.660.66
935141AD1-148 C
80/20
0.7970.797
936371AD2-047 C
80/20
2.9422.942
936372AD2-047 E
80/20
14.36514.365
938861AE1-114 C
80/20
2.5552.555
938862AE1-114 E
80/20
8.7168.716
939321AE1-163 C
80/20
4.1514.151
939322AE1-163 E
80/20
25.49625.496
942421AE2-255 C
80/20
1.9821.982
942422AE2-255 E
80/20
5.9475.947
946321AF1-296 C
80/20
2.2942.294
946322AF1-296 E
80/20
10.73910.739
957371AF2-031 C
80/20
0.6360.636
957372AF2-031 E
80/20
0.9540.954
960261AF2-317 C
80/20
0.3440.344
961501AF2-441 C
80/20
6.9346.934
961502AF2-441 E
80/20
10.40210.402
965331AG1-398 C
80/20
0.1690.169
990901L-005 E
80/20
2.5642.564
276170Z1-108 E
80/20
2.0422.042
920272AA2-123 E
80/20
22
965793AG1-447 BT
80/20
8.3248.324
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
991302J1755
External Queue
8.07698.0769

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.66 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1044.28
MW Contribution:8.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.730.73
274871GR RIDGE ;2U
50/50
0.2720.272
274887PILOT HIL;1U
50/50
0.9460.946
274888KELLY CRK;1U
50/50
0.9460.946
293061N-015 E
50/50
3.1963.196
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
934721AD1-100 C
50/50
3.8213.821
934722AD1-100 E
50/50
59.44459.444
942111AE2-223 C
Adder
1.19529411764705881.016
942112AE2-223 E
Adder
7.9988235294117666.799
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959351AF2-226 C
Adder
1.9635294117647061.669
959352AF2-226 E
Adder
2.94588235294117642.504
959611AF2-252 C
Adder
1.45058823529411771.233
959612AF2-252 E
Adder
2.17647058823529441.85
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
962012AG1-044 E
Adder
0.044705882352941180.038
966091AG1-478 C
50/50
0.4310.431
966092AG1-478 E
50/50
0.6470.647
966441AG1-513 C
50/50
0.420.42
966442AG1-513 E
50/50
0.6290.629
274674JOLIET 9 ;6U
50/50
13.64513.645
274675JOLIET 29;7U
50/50
36.25136.251
274676JOLIET 29;8U
50/50
36.23736.237
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
274687WILL CNTY;4U
50/50
32.59532.595
938851AE1-113 C
Adder
5.2341176470588244.449
938852AE1-113 E
Adder
18.5576470588235315.774
939401AE1-172 C
Adder
3.45058823529411772.933
939402AE1-172 E
Adder
16.15411764705882513.731
942651AE2-281 C
50/50
0.5930.593
942652AE2-281 E
50/50
3.6423.642
270839OTTER CRK; R
50/50
0.5410.541
275149KELLYCK ;1E
50/50
3.7853.785
276626AG1-044 E
Adder
0.050588235294117640.043
276627AG1-044 BAT
Adder
0.0094117647058823540.008
276675AE2-062 E
50/50
0.1120.112
293519PILOT HIL;1E
50/50
3.7853.785
926821AC1-168 C
Adder
0.74235294117647070.631
926822AC1-168 E
Adder
4.98117647058823554.234
936371AD2-047 C
50/50
2.9422.942
936372AD2-047 E
50/50
14.36514.365
938861AE1-114 C
Adder
2.5552941176470592.172
938862AE1-114 E
Adder
8.717647058823537.41
939321AE1-163 C
50/50
4.1514.151
939322AE1-163 E
50/50
25.49625.496
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
946321AF1-296 C
Adder
2.29411764705882341.95
946322AF1-296 E
Adder
10.749.129
957371AF2-031 C
Adder
0.63647058823529420.541
957372AF2-031 E
Adder
0.95411764705882360.811
961501AF2-441 C
Adder
6.9341176470588245.894
961502AF2-441 E
Adder
10.48.84
276170Z1-108 E
50/50
2.0432.043
920272AA2-123 E
50/50
22
965793AG1-447 BT
50/50
8.3258.325
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
990947J1432 G
External Queue
12.502512.5025
991302J1755
External Queue
8.07698.0769

Details for UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.66 %
Rating:970.0 MVA
Rating Type:STE
MVA to Mitigate:1044.26
MW Contribution:8.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
274847GR RIDGE ;BU
50/50
0.730.73
274871GR RIDGE ;2U
50/50
0.2720.272
274887PILOT HIL;1U
50/50
0.9460.946
274888KELLY CRK;1U
50/50
0.9460.946
293061N-015 E
50/50
3.1963.196
294392P-010 E
50/50
4.064.06
918052AA1-018 E OP
50/50
3.6223.622
934721AD1-100 C
50/50
3.8213.821
934722AD1-100 E
50/50
59.44459.444
942111AE2-223 C
Adder
1.19529411764705881.016
942112AE2-223 E
Adder
7.9988235294117666.799
957331AF2-027 C
50/50
2.0512.051
957332AF2-027 E
50/50
3.0763.076
959351AF2-226 C
Adder
1.9635294117647061.669
959352AF2-226 E
Adder
2.94588235294117642.504
959611AF2-252 C
Adder
1.45058823529411771.233
959612AF2-252 E
Adder
2.17647058823529441.85
960281AF2-319 C
Adder
1.9635294117647061.669
960282AF2-319 E
Adder
2.94588235294117642.504
960611AF2-352 C
Adder
1.45058823529411771.233
960612AF2-352 E
Adder
2.17647058823529441.85
962012AG1-044 E
Adder
0.044705882352941180.038
966091AG1-478 C
50/50
0.4310.431
966092AG1-478 E
50/50
0.6470.647
966441AG1-513 C
50/50
0.420.42
966442AG1-513 E
50/50
0.6290.629
274674JOLIET 9 ;6U
50/50
13.64513.645
274675JOLIET 29;7U
50/50
36.25136.251
274676JOLIET 29;8U
50/50
36.23736.237
274682WAUKEGAN ;7U
50/50
15.27415.274
274683WAUKEGAN ;8U
50/50
16.46616.466
274687WILL CNTY;4U
50/50
32.59532.595
938851AE1-113 C
Adder
5.2341176470588244.449
938852AE1-113 E
Adder
18.5576470588235315.774
939401AE1-172 C
Adder
3.45058823529411772.933
939402AE1-172 E
Adder
16.15411764705882513.731
942651AE2-281 C
50/50
0.5930.593
942652AE2-281 E
50/50
3.6423.642
270839OTTER CRK; R
50/50
0.5410.541
275149KELLYCK ;1E
50/50
3.7853.785
276626AG1-044 E
Adder
0.050588235294117640.043
276627AG1-044 BAT
Adder
0.0094117647058823540.008
276675AE2-062 E
50/50
0.1120.112
293519PILOT HIL;1E
50/50
3.7853.785
926821AC1-168 C
Adder
0.74235294117647070.631
926822AC1-168 E
Adder
4.98117647058823554.234
936371AD2-047 C
50/50
2.9422.942
936372AD2-047 E
50/50
14.36514.365
938861AE1-114 C
Adder
2.5552941176470592.172
938862AE1-114 E
Adder
8.717647058823537.41
939321AE1-163 C
50/50
4.1514.151
939322AE1-163 E
50/50
25.49625.496
942421AE2-255 C
Adder
1.98235294117647071.685
942422AE2-255 E
Adder
5.9482352941176475.056
946321AF1-296 C
Adder
2.29411764705882341.95
946322AF1-296 E
Adder
10.749.129
957371AF2-031 C
Adder
0.63647058823529420.541
957372AF2-031 E
Adder
0.95411764705882360.811
961501AF2-441 C
Adder
6.9341176470588245.894
961502AF2-441 E
Adder
10.48.84
276170Z1-108 E
50/50
2.0432.043
920272AA2-123 E
50/50
22
965793AG1-447 BT
50/50
8.3258.325
990052J1200
External Queue
0.35320.3532
990512J1326 G
External Queue
4.43924.4392
990947J1432 G
External Queue
12.502512.5025
991302J1755
External Queue
8.07698.0769
CONTINGENCY '765-L11215__-S_SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
END
CONTINGENCY 'AEP_P1-2_#695_1681_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1   /*05DUMONT     765.0 - WILTON   ;   765.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1   /*WILTON   ;   765.0 - 05DUMONT     765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
960680 to 243229 ckt 1
274804 to 960680 ckt 1

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests (AG1-436, and AG1-447) in PJM Transition Cycle 1, Cluster 58 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 58 projects.

 

This analysis is effectively a screening study to determine whether the addition of the cluster 58 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

The load flow scenario for the analysis was based on the RTEP 2027 summer peak load case, modified to include applicable projects. Cluster 58 projects have been dispatched online at maximum power output, with 1.0 voltage at the terminal bus.

 

Cluster 58 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 56 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

       a)       Steady-state operation (20 second run),

       a)       Three-phase faults with normal clearing time; (and with unsuccessful high-speed reclosing),

       b)       Single-phase bus faults with normal clearing time,

       c)       Single-phase faults with stuck breaker,

       d)       Three-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing).

 

There are no delayed (Zone 2) clearing faults due to dual primary relays being employed in the AEP 345 kV transmission system.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all of the fault contingencies tested on the 2027 peak load case:

       a)       Cluster 58 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 58 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

AG1-447 and AG1-436 meet the 0.95 leading and lagging PF requirement.

 

AG1-436 GEN exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. This issue was mitigated by increasing Kc value in REPCA1 dynamic model from 0 to 0.1. This change has been confirmed by the developer and included in the latest data submission.

 

AG1-447 GEN exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. ETERM of AG1-447 GEN went outside the range of 0.95 pu ~1.05 pu in post fault for several contingencies. These issues were mitigated by changing VCFlag from 1 to 0, increasing Kc from 0 to 0.08, and Ki from 0.5 to 3.5 in the REPCA1 model. These changes have been confirmed by the developer in correspondence.

 

The IPCMD and IQCMD states in the REGCA1 model of AG1-447 GEN, and AG1-436 GEN showed erratic behavior for some contingencies in which these generators have been disconnected as part of the contingency event. Since the machine is disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

No mitigations were found to be required.

 

Table 1: TC1 Cluster 58 Projects

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

58

AG1-436

Solar

AEP

125

125

75

Olive-University Park 345 kV

AG1-447

Battery

AEP

55

55

55

Olive-University Park 345 kV

 

 

Reactive Power Analysis

The reactive power capability of AG1-447 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA2-116Cook-East Elkhart 345kVIn Service
AA2-123Marengo 34kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-080Dumont-Olive 345kVIn Service
AB1-087Sullivan 345kV #1Under Construction
AB1-088Sullivan 345kV #2Engineering & Procurement
AC1-168Kewanee-StreatorSuspended
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD2-020Valley 138 kVEngineering & Procurement
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-079Capitol Ave 34.5kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-205McLean 345 kVEngineering & Procurement
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-062Romeoville 12 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-181Snyder 69kVPartially in Service - Under Construction
AE2-223McLean 345 kVActive
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-276Sullivan 345kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-323Twin Branch-Guardian 138 kVPartially in Service - Under Construction
AE2-325Valley 138 kVActive
AE2-341Sandwich-Plano 138 kVActive
AF1-030Sandwich-Plano 138 kVActive
AF1-064Weston 69 kVUnder Construction
AF1-084Hartford-Almena 69 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVActive
AF1-176Corey 138 kVActive
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-027Zion Energy Center 345 kVEngineering & Procurement
AF2-031CalumetEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-095Davis Creek 138 kVActive
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-226Katydid Road 345 kVActive
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-319Katydid Road 345 kVActive
AF2-349SILVER LAKE- CHERRY VALLEY 345 KVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-396Stinger 138 kVActive
AF2-441Burnham 138kVActive
AG1-109Valley 138 kVActive
AG1-118Sugar Grove-Waterman 138kVActive
AG1-127Crego Rd 138 kVActive
AG1-226Dequine-Eugene 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-513Aurora 138 kVSuspended
AG1-555Dequine 345 kVEngineering & Procurement
X1-042WatervlietIn Service
X3-005Wildwood 12kVIn Service
Y1-054Rochelle 138kVIn Service
Y3-023Country Side 12kVIn Service
Z1-073Mendota HillsIn Service
Z1-108McHenry 34kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)Identified Impacts
AG1-447 System Reinforcements:
TOTrans Owner IDTitleCategoryAllocated Cost ($USD)
METCMETC_TC1_16078Perform sag mitigation on Allen Junction - Morocco 345kV line. New ratings will be 1861/2124 MVA.Informational$0
ITCTITCT_TC1_13866MTEP24#25223 - Lulu Sub. Construct the Lulu switching station. Cut in the Lemoyne-Maple and Milan-Monroe-Morocco lines into the new station (Projected ISD 6/11/2027)Informational$0
Grand Total:$0

System Reinforcement
Type
Load Flow
TO
METC
RTEP ID / TO ID
(Pending) / METC_TC1_16078
Title
Perform sag mitigation on Allen Junction - Morocco 345kV line. New ratings will be 1861/2124 MVA.
Description
Perform sag mitigation on Allen Junction - Morocco 345kV line. New ratings will be 1861/2124 MVA.
Total Cost ($USD)
$625,000
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-447 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-447 could receive cost allocation. Although AG1-447 may not presently have cost responsibility for this upgrade, AG1-447 is a potential Aggregate Pool Contributor.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B2124.0 MVA

System Reinforcement
Type
Load Flow
TO
ITCT
RTEP ID / TO ID
(Pending) / ITCT_TC1_13866
Title
MTEP24#25223 - Lulu Sub. Construct the Lulu switching station. Cut in the Lemoyne-Maple and Milan-Monroe-Morocco lines into the new station (Projected ISD 6/11/2027)
Description
Construct the Lulu switching station. Cut in the Lemoyne-Maple and Milan-Monroe-Morocco lines into the new station. This project is a DPP 2020 Network Upgrade associated with the J1516, J1525, J1526, J1527, J1550, J1553, J1557, J1571, J1586, J1587, J1603, J1614, J1635, J1658, J1659, J1663, and J1664 projects. Projected In-Service 6/1/2027
Total Cost ($USD)
$29,916,928
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-447 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-447 could receive cost allocation. Although AG1-447 may not presently have cost responsibility for this upgrade, AG1-447 is a potential Aggregate Pool Contributor.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 312.A.1.b and as outlined in PJM Manual 14H, Section 13, in Phase III of the Cycle, PJM coordinates with the Affected System Operators to conduct any studies required to determine the impact of the New Service Request on any Affected System and will include the Affected System Study results in Phase III System Impact Study, if available from the Affected System Operator.

If your project required an Affected System Study, the results are shown below from the Affected System Operator.

For more details, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM will list any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO) Identified Impacts
Note: Please communicate with the Affected System Operator regarding the status of the Affected System Study for your project.
Impacted FacilityTransmission OwnerReinforcementCostCost Allocated to AG1-447Scenarios
  • Wvrich 69.0 - Rochester TP 69.0 CKT 1
DEI DEI: Rebuild 1 mile of Wvrich - Rochester TP 69 kV
DEI: Rebuild 1 mile of 69kV with 477ACSR/VR2 @
100/120C the ratings assume that NIPSCO terminal
upgrades would not limit our T-Line rating. $1.5M
NIPSCO: Rebuild line, NIPSCO owns 0.037 miles of
0.9 mile line. NIPSCO portion included in Argos to
Rochester tap mitigation/cost.
$1,500,000$21,130
  • NIPSCO LPC
  • Wvrich 69.0 - Rochester TP 69.0 CKT 1
NIPS NIPSCO: Rebuild line (.3miles)Wvrich - Rochester TP 69 kV
DEI: Rebuild 1 mile of 69kV with 477ACSR/VR2 @
100/120C the ratings assume that NIPSCO terminal
upgrades would not limit our T-Line rating. $1.5M
NIPSCO: Rebuild line, NIPSCO owns 0.037 miles of
0.9 mile line. NIPSCO portion included in Argos to
Rochester tap mitigation/cost.
$0$0
  • NIPSCO LPC
  • Argos 69.0 - Plymouth 69.0 CKT 1
NIPS Rebuild Argos - Plymouth 69 kV line
Rebuild line, approx 10 miles
$12,654,948$173,003
  • NIPSCO LPC
  • Argos 69.0 - Rochester TP 69.0 CKT 1
NIPS Rebuild Argos - Rochester TP 69 kV
Rebuild line, approx 3.2 miles
$4,049,583$57,045
  • NIPSCO LPC
  • CAP BANK 230.0 - Gallagher 230.0 CKT 0
DEI Install 144 MVAR cap bank at Gallagher sub.
Install 144 MVAR cap bank at Gallagher sub.
$3,000,000$16,713
  • MISO Voltage
  • CAP BANK 138.0 - Shoals 138.0 CKT 0
DEI Install 28.8 MVAR cap bank at Shoals sub
Install 28.8 MVAR cap bank at Shoals sub
$3,000,000$12,658
  • MISO Voltage
  • CAP BANK 138.0 - Avon East 138.0 CKT 0
DEI Install 28.8 MVAR cap bank at Avon East sub
Install 28.8 MVAR cap bank at Avon East sub
$3,000,000$11,321
  • MISO Voltage
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Final System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG1-447 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
ComEdb3775.1Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV lineContingent$0N/A
ComEdb3775.4Rebuild 345 kV double circuit extending from Crete to E. Frankfort.Contingent$0N/A
Grand Total:$0

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9322.0
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
n9322.0 / TE-AG1-S-0012a
Title
Replace Four (4) disconnect switches, four (4) breaker leads, and one (1) meter, and reconductor two (2) transmission line drops on the Morocco 345 kV line terminal at Allen Junction.
Description
Replace (4) disconnect switches at Allen Junction Replace (4) breaker leads at Allen Junction Reconductor (2) TL Drops at Allen Junction Replace (1) meter at Allen Junction New FE Ratings 1868 / 2249 / 2586 MVA SN/SE/SLD
Total Cost ($USD)
$1,408,997
Discounted Total Cost ($USD)
$1,408,997
Allocated Cost ($USD)
$0
Time Estimate
38 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG1-447 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG1-447 could receive cost allocation. Although AG1-447 may not presently have cost responsibility for this upgrade, AG1-447 is a potential Aggregate Pool Contributor.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1868.0 MVA
(All)B2249.0 MVA
(All)C2586.0 MVA

System Reinforcement: s3442.26
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s3442.26
Title
Dumont 765 kV: Replace 3000 A circuit breaker at Dumont
Description
Dumont 765 kV: Replace 3000 A circuit breaker at Dumont to address a generation deliverability violation on the Dumont – Sorenson 765 kV branch related to the new customer interconnections in the area. Projected in service date 3/5/2027
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AG1-447 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG1-447 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-05SORENS 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4558.0 MVA
(All)B5001.0 MVA

System Reinforcement: n3985
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n3985 / AEPO0036a
Title
Upgrade three Marysville Wavetraps ( 3000A)
Description
Replace 3 Marysville 765 kV wave traps. Costs updated to $705,368 from Facility Study
Total Cost ($USD)
$900,000
Discounted Total Cost ($USD)
$900,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 24 Months

Not Contingent

Note: AG1-447 contributes to the loading of an overloaded facility that is being mitigated by a network upgrade that was securitized by a prior Queue/Cycle. AG1-447 is not contingent on this network upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05SORENS 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5075.0 MVA
(All)B5075.0 MVA

System Reinforcement: b3775.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.1
Title
Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line
Description
Outside of the Green Acres substation, swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line to the University Park N-Olive 345 kV line to create a University Park N-Green Acres-Olive and St. John-Olive 345 kV lines.
Cost Information
Time Estimate
Mar 30 2027

Contingent

Note: Although AG1-447 may not presently have cost responsibility for this upgrade, AG1-447 may need this upgrade in-service to be deliverable to the PJM system. If AG1-447 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05OLIVE-05NEW CARLI1 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05OLIVE-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A9999.0 MVA
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A9999.0 MVA

System Reinforcement: b3775.10
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3775.10
Title
Perform sag study mitigation work on Olive – University Park
Description
Perform a sag study on the Olive – University Park 345kV line to increase the operating temperature to 225 F. Remediation work includes two tower replacements on the line.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AG1-447 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG1-447 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
UNIV PK N;RP-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1679.0 MVA
(All)B2058.0 MVA

System Reinforcement: b3775.4
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.4 / CE_B3775.4
Title
Rebuild 345 kV double circuit extending from Crete to E. Frankfort.
Description
Part of b3775 baseline. Rebuild 12.7 miles of 345 kV double circuit extending from Crete to E. Frankfort with twin bundled 1277 ACAR conductor.
Cost Information
Time Estimate
Dec 01 2026

Contingent

Note: Although AG1-447 may not presently have cost responsibility for this upgrade, AG1-447 may need this upgrade in-service to be deliverable to the PJM system. If AG1-447 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
(Any)765-L11215__-S_SRT-A
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG1-447


AG1-447 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AG1-447 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG1-447 One Line Diagram

AG1-447 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.