AG1-471 Final System Impact Study (Retool 2) Report

v2.00 released 2026-05-14 11:57

Up Church-Wayne County 69 kV

32.4 MW Capacity / 54.0 MW Energy

Introduction

This Final System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 314 for New Service Requests (projects) in Transition Cycle 1 (TC1). The Project Developer/Eligible Customer (developer) is Barrelhead Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is East Kentucky Power Cooperative, Inc..

Preface

The Final System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Final System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 5, Final Agreement Negotiation Phase, the purpose of the Final Agreement Negotiation Phase is to:

  1. Negotiate, execute and enter into the applicable final interconnection related service agreement found in Tariff, Part IX;
  2. Conduct any remaining analyses or updated analyses based on New Service Requests withdrawn during Decision Point III (DP3); and
  3. Adjust the security obligation based on New Service Requests withdrawn during Decision Point III and/or during the Final Agreement Negotiation Phase.
Retool 1:

In accordance with PJM Tariff Part VII.D 314 B(1)(a), Final Agreement Negotiation Phase:

  • PJM will perform a retool (Retool 1) after the conclusion of DP3 considering only the projects moving on in the Final Agreement Negotiation Phase (Removes DP3 withdrawals).
  • The Final System Impact Study reflecting results from the retooled analysis (Retool 1) will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • PJM will provide updated final electronic agreements to Project Developers and Eligible Customers in the Cycle reflecting updates from the Final System Impact Study after Retool 1 including the adjusted Security requirements.

The AG1-471 Final System Impact Study (Retool 1) Report is available for download here.

Retool 2 (if needed):

If particular New Service Requests do not sign their final agreements after receiving the updated information after Retool 1, there may be the need to run a second retool (Retool 2) to identify if any network upgrades are no longer necessary:

  • PJM will perform Retool 2 (if necessary) considering only the removal of projects from the model which chose not to execute their agreements after Retool 1.
  • The updated Final System Impact Study reflecting results from Retool 2 will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  • If there are any adjustments to the agreements required after Retool 2, the necessary network upgrade or Security changes will be handled via the scope change process post-GIA.

General

The Project Developer has proposed a Solar generating facility located in the East Kentucky Power Cooperative, Inc. zone — Wayne County, Kentucky. The installed facilities will have a total capability of 54.0 MW with 32.4 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG1-471
Project Name:
Up Church-Wayne County 69 kV
Project Developer Name:
Barrelhead Solar, LLC
State:
Kentucky
County:
Wayne
Transmission Owner:
East Kentucky Power Cooperative, Inc.
MFO:
54.0
MWE:
54.0
MWC:
32.4
Fuel Type:
Solar
Basecase Study Year:
2027

Physical Interconnection Facility Study

Received

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG1-471 will interconnect on the East Kentucky Power Cooperative, Inc. transmission system tapping the Upchurch to Wayne County 69 kV line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II. Facilities Studies are available for download on PJM.com (see General Section for document links). The Interconnected Transmission Owner has performed a Facilities Study for the required System Reliability Network Upgrades in Phase III (see System Reinforcement Section for document links).

Based on the Final SIS results, the AG1-471 project has the following allocation of costs for interconnection. The Security amount required after the Final SIS and revised agreements is also shown below.

Cost Summary
DescriptionCost Allocated to AG1-471Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$718,000$718,000
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$7,050,000$7,050,000
Network Upgrades$6,137,000$6,137,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0
AFS - Non-PJM Violations$0 **$0 **
Total$13,905,000$13,905,000

* Contributes to calculation for Security. See Security Requirement Section of this report for additional detail.

** This value reflects the results at the time of the report posting and it is subject to change. AFS – Non-PJM Violations are not subject to Security. For latest AFS – Non-PJM Violations, please refer to the latest Affected System Study Report for your project.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 314 (Final Agreement Negotiation Phase) A.1 and PJM Manual 14H, Section 5, if a Transition Cycle 1 New Service Request is withdrawn during Decision Point III and/or the Final Agreement Negotiation Phase, PJM shall remove the New Service Request from the Cycle and adjust the Security obligations of other New Service Requests based on the withdrawal. The Final System Impact Study results will reflect the updated Security amount for this project. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Final System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AG1-471

Security has been calculated for the AG1-471 project(s) based on the Final System Impact Study results and is shown in the table below. This Security must be provided at Final SIS through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AG1-471
Project(s): AG1-471
Final Agreement Security (A): $13,905,000
Portion of Costs Already Paid (B): $0
Revised Net Security (C): A − B = $13,905,000
Security on Hand with PJM (D): $13,905,000
Additional Security Due at Agreement Execution (E): C − D = $0
Note:

In accordance with Tariff, Part VII, Subpart D, section 314(B)(4)(a) (Final Agreement Negotiation Phase) failure to provide any required adjustments to Security within the 15 Business Day period will result in the New Service Request project being terminated and withdrawn.

Please see the cover letter for more details on Letter of Credit/Wire details to satisfy the additional Security requirement.

If no additional Security is required, please coordinate with your assigned Project Manager to initiate any refunds of Security reductions.

Transmission Owner Scope of Work

EKPC will construct a 69 kV Main and Transfer switching station and a new 69 kV loop-in tap from the EKPC Wayne County-Upchurch 69 kV line to accommodate the direct connection of the PD’s substation facilities to the EKPC transmission system.  EKPC will also construct a 69 kV disconnect switch structure which will be the POI interface.

EKPC will also complete the required network upgrades at existing EKPC substations, which are system protection changes necessary at the Wayne County and Summer Shade substations to accommodate the addition of this new facility, and installation of OPGW on the existing 69 kV line sections from the new Massingale Road switching station to the Wayne County and Summer Shade substations in order to provide necessary communications infrastructure for EKPC.  

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Scope
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9513.0

Revise Relay Settings at Summer Shade Sub.

$55,000$1,000$6,000$1,000$63,000$63,000
n9512.0

Revise Relay Settings at Wayne County Sub.

$55,000$1,000$6,000$1,000$63,000$63,000
n9511.0

Loop existing Upchurch Tap - Wayne County 69 kV line into new interconnection switching station.

$254,000$244,000$50,000$6,000$554,000$554,000
n9510.0

Install new overhead optical ground wire (OPGW) on the existing Wayne County - Massingale Road and Massingale Road - Summer Shade 69 kV line sections for a total of 44.2 miles.

$3,510,000$1,401,000$491,000$55,000$5,457,000$5,457,000
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
n9514.0

Massingale Road Substation: Construct new 69 kV switching station.

$2,987,000$3,359,000$634,000$70,000$7,050,000$7,050,000
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

One (1) 69 kV generator lead line to include, but not be limited to, installation of a 69 kV line monopole dead-end structure and foundation, a 3-pole disconnect switch mounted to the monopole, line conductor from the dead-end structure to the bus position in the switchyard, and two (2) 48-strand fiber optic cables.

$378,000$268,000$65,000$7,000$718,000$718,000

Based on the scope of work for the Interconnection Facilities, it is expected to take 25 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

EKPC anticipates that it will take 25 months after the signing of the Generator Interconnection Agreement and the project kickoff call is subsequently held to complete the physical interconnection projects.  This assumes no delays due to permitting or environmental issues, and that all necessary outages can be taken as needed to maintain this schedule.

Transmission Owner Analysis

No Transmission Owner impacts identified.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. EKPC interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG1-471 was evaluated as a 52.2 MW (32.4 MW Capacity) injection in the EKPC area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD1EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A
TowerAC100.5 %105.0B105.527.48
GD1EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC106.47 %277.0B294.9310.55
GD1EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC106.47 %277.0B294.9310.55
GD1EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC106.14 %277.0B294.0210.57
GD1EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC106.14 %277.0B294.0210.57

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.5 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:105.52
MW Contribution:7.48
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:99.43 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:104.4
MW Contribution:7.47
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
964901AG1-354 C
Adder
7.2682352941176476.178
964902AG1-354 E
Adder
4.8458823529411764.119
943701AF1-038 C
50/50
8.4088.408
943702AF1-038 E
50/50
5.6055.605
943821AF1-050 C
Adder
2.9811764705882352.534
943822AF1-050 E
Adder
1.9870588235294121.689
945382AF1-203 E
Adder
0.72235294117647060.614
3429001COOPER1 G
50/50
5.115.11
3429031COOPER2 G
50/50
9.9119.911
939132AE1-143 E
Adder
3.12588235294117662.657
940832AE2-071 E
Adder
1.26470588235294111.075
339206AE1-143 C
Adder
6.3070588235294115.361
944151AF1-083 C
Adder
2.92470588235294172.486
944152AF1-083 E
Adder
1.94941176470588241.657
964781AG1-341 C
Adder
5.0411764705882364.285
964782AG1-341 E
Adder
3.36117647058823542.857
966021AG1-471 C
50/50
4.6414.641
966022AG1-471 E
50/50
2.8362.836
950011AG9-010
External Queue
8.6052598953247078.605259895324707
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0380.038
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.1073.107
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.5913.591
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.6741.674
G-007PJM->LTFIMP_G-007
CMTX_NF
0.0890.089
NYPJM->LTFIMP_NY
CLTF
0.0470.047
WECLTFEXP_WEC->PJM
CLTF
0.0660.066
CPLELTFEXP_CPLE->PJM
CLTF
0.0810.081
TVALTFEXP_TVA->PJM
CLTF
1.2851.285
MECLTFEXP_MEC->PJM
CLTF
0.5590.559
LAGNLTFEXP_LAGN->PJM
CLTF
1.211.21
SIGELTFEXP_SIGE->PJM
CLTF
0.0430.043
O66PJM->LTFIMP_O-066
CMTX_NF
0.5690.569

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.47 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:294.93
MW Contribution:10.55
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.98 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:293.57
MW Contribution:10.55
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
964901AG1-354 C
50/50
10.68810.688
964902AG1-354 E
50/50
7.1257.125
943701AF1-038 C
50/50
6.6266.626
943702AF1-038 E
50/50
4.4184.418
943821AF1-050 C
50/50
4.4474.447
943822AF1-050 E
50/50
2.9652.965
945381AF1-203 C
50/50
0.2290.229
945382AF1-203 E
50/50
0.9620.962
3424422W GLASGOW
50/50
0.0170.017
3429001COOPER1 G
50/50
10.51510.515
3429031COOPER2 G
50/50
20.45820.458
3429451LAUREL 1G
50/50
6.3646.364
939132AE1-143 E
50/50
4.8744.874
940831AE2-071 C
50/50
0.4040.404
940832AE2-071 E
50/50
1.6841.684
339206AE1-143 C
50/50
9.8339.833
944151AF1-083 C
50/50
4.4674.467
944152AF1-083 E
50/50
2.9782.978
964781AG1-341 C
50/50
7.3317.331
964782AG1-341 E
50/50
4.8884.888
966021AG1-471 C
50/50
6.5516.551
966022AG1-471 E
50/50
4.0034.003
950011AG9-010
External Queue
13.441103935241713.4411039352417
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0540.054
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.6133.613
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.1215.121
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.5362.536
G-007PJM->LTFIMP_G-007
CMTX_NF
0.1730.173
NYPJM->LTFIMP_NY
CLTF
0.0920.092
WECLTFEXP_WEC->PJM
CLTF
0.0780.078
CPLELTFEXP_CPLE->PJM
CLTF
0.1160.116
TVALTFEXP_TVA->PJM
CLTF
1.921.92
MECLTFEXP_MEC->PJM
CLTF
0.750.75
LAGNLTFEXP_LAGN->PJM
CLTF
1.7841.784
SIGELTFEXP_SIGE->PJM
CLTF
0.0560.056
O66PJM->LTFIMP_O-066
CMTX_NF
1.1091.109

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.47 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:294.93
MW Contribution:10.55
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.97 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:293.54
MW Contribution:10.55
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
964901AG1-354 C
50/50
10.68810.688
964902AG1-354 E
50/50
7.1257.125
943701AF1-038 C
50/50
6.6266.626
943702AF1-038 E
50/50
4.4184.418
943821AF1-050 C
50/50
4.4474.447
943822AF1-050 E
50/50
2.9652.965
945381AF1-203 C
50/50
0.2290.229
945382AF1-203 E
50/50
0.9620.962
3424422W GLASGOW
50/50
0.0170.017
3429001COOPER1 G
50/50
10.51510.515
3429031COOPER2 G
50/50
20.45820.458
3429451LAUREL 1G
50/50
6.3646.364
939132AE1-143 E
50/50
4.8744.874
940831AE2-071 C
50/50
0.4040.404
940832AE2-071 E
50/50
1.6841.684
339206AE1-143 C
50/50
9.8339.833
944151AF1-083 C
50/50
4.4674.467
944152AF1-083 E
50/50
2.9782.978
964781AG1-341 C
50/50
7.3317.331
964782AG1-341 E
50/50
4.8884.888
966021AG1-471 C
50/50
6.5516.551
966022AG1-471 E
50/50
4.0034.003
950011AG9-010
External Queue
13.44110488891601613.441104888916016
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0540.054
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.6133.613
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.1215.121
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.5362.536
G-007PJM->LTFIMP_G-007
CMTX_NF
0.1730.173
NYPJM->LTFIMP_NY
CLTF
0.0920.092
WECLTFEXP_WEC->PJM
CLTF
0.0780.078
CPLELTFEXP_CPLE->PJM
CLTF
0.1160.116
TVALTFEXP_TVA->PJM
CLTF
1.921.92
MECLTFEXP_MEC->PJM
CLTF
0.750.75
LAGNLTFEXP_LAGN->PJM
CLTF
1.7841.784
SIGELTFEXP_SIGE->PJM
CLTF
0.0560.056
O66PJM->LTFIMP_O-066
CMTX_NF
1.1091.109

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.14 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:294.02
MW Contribution:10.57
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.65 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:292.65
MW Contribution:10.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
964901AG1-354 C
50/50
10.70410.704
964902AG1-354 E
50/50
7.1367.136
943701AF1-038 C
50/50
6.6396.639
943702AF1-038 E
50/50
4.4264.426
943821AF1-050 C
50/50
4.4544.454
943822AF1-050 E
50/50
2.9692.969
945381AF1-203 C
50/50
0.2290.229
945382AF1-203 E
50/50
0.9640.964
3424422W GLASGOW
50/50
0.0170.017
3429001COOPER1 G
50/50
10.52410.524
3429031COOPER2 G
50/50
20.47420.474
3429451LAUREL 1G
50/50
6.3696.369
939132AE1-143 E
50/50
4.884.88
940831AE2-071 C
50/50
0.4050.405
940832AE2-071 E
50/50
1.6871.687
339206AE1-143 C
50/50
9.8469.846
944151AF1-083 C
50/50
4.4734.473
944152AF1-083 E
50/50
2.9822.982
964781AG1-341 C
50/50
7.3437.343
964782AG1-341 E
50/50
4.8954.895
966021AG1-471 C
50/50
6.5616.561
966022AG1-471 E
50/50
4.014.01
950011AG9-010
External Queue
13.46012592315673813.460125923156738
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0560.056
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.6283.628
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.1495.149
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.5792.579
G-007PJM->LTFIMP_G-007
CMTX_NF
0.1730.173
NYPJM->LTFIMP_NY
CLTF
0.0920.092
WECLTFEXP_WEC->PJM
CLTF
0.0790.079
CPLELTFEXP_CPLE->PJM
CLTF
0.1190.119
TVALTFEXP_TVA->PJM
CLTF
1.931.93
MECLTFEXP_MEC->PJM
CLTF
0.7540.754
LAGNLTFEXP_LAGN->PJM
CLTF
1.7951.795
SIGELTFEXP_SIGE->PJM
CLTF
0.0560.056
O66PJM->LTFIMP_O-066
CMTX_NF
1.1081.108

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.14 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:294.02
MW Contribution:10.57
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.66 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:292.69
MW Contribution:10.57
Bus #Bus NameTypeFull MW ContributionGenDeliv MW Contribution
964901AG1-354 C
50/50
10.70410.704
964902AG1-354 E
50/50
7.1367.136
943701AF1-038 C
50/50
6.6396.639
943702AF1-038 E
50/50
4.4264.426
943821AF1-050 C
50/50
4.4544.454
943822AF1-050 E
50/50
2.9692.969
945381AF1-203 C
50/50
0.2290.229
945382AF1-203 E
50/50
0.9640.964
3424422W GLASGOW
50/50
0.0170.017
3429001COOPER1 G
50/50
10.52410.524
3429031COOPER2 G
50/50
20.47420.474
3429451LAUREL 1G
50/50
6.3696.369
939132AE1-143 E
50/50
4.884.88
940831AE2-071 C
50/50
0.4050.405
940832AE2-071 E
50/50
1.6871.687
339206AE1-143 C
50/50
9.8469.846
944151AF1-083 C
50/50
4.4734.473
944152AF1-083 E
50/50
2.9822.982
964781AG1-341 C
50/50
7.3437.343
964782AG1-341 E
50/50
4.8954.895
966021AG1-471 C
50/50
6.5616.561
966022AG1-471 E
50/50
4.014.01
950011AG9-010
External Queue
13.46012592315673813.460125923156738
LTFEXP_AA2-074LTFEXP_AA2-074->LTFIMP_AA2-074
CLTF
0.0560.056
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.6283.628
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.1495.149
CBM South 1LTFEXP_CBM-S1->PJM
CBM
00
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.5792.579
G-007PJM->LTFIMP_G-007
CMTX_NF
0.1730.173
NYPJM->LTFIMP_NY
CLTF
0.0920.092
WECLTFEXP_WEC->PJM
CLTF
0.0790.079
CPLELTFEXP_CPLE->PJM
CLTF
0.1190.119
TVALTFEXP_TVA->PJM
CLTF
1.931.93
MECLTFEXP_MEC->PJM
CLTF
0.7540.754
LAGNLTFEXP_LAGN->PJM
CLTF
1.7951.795
SIGELTFEXP_SIGE->PJM
CLTF
0.0560.056
O66PJM->LTFIMP_O-066
CMTX_NF
1.1081.108
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 342718 TO BUS 342757 CKT 1   /*5COOPER2     161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P7-1_LAURL 161 DBL_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
 OPEN BUS 342754                                   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1014_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P2-2_LAUREL CO 161_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
342287 to 324531 ckt 1
342718 to 324141 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

The New Service Request AG1-471 was evaluated as a 54.0 MW injection in the EKPC area.

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Based on PJM’s Short Circuit Analysis, this project did not contribute >1% fault duty to previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests (projects) in PJM Transition Cycle 1, Cluster 25 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 25 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 25 projects will meet the dynamics requirements of the NERC, EKPC and PJM reliability standards.

 

The load flow scenario for the analysis was based on the RTEP 2027 summer peak load case, modified to include applicable projects. Cluster 25 projects have been dispatched online at maximum power output, and voltage schedules set to achieve near unity power factor at the high side of the main transformer.

 

       Cluster 25 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 133 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

       a)       Steady-state operation (20 second run);

       b)       Three-phase faults with normal clearing time;

       c)       Single-phase bus faults with normal clearing time;

       d)       Single-phase faults with stuck breaker;

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure;

       f)       Single-phase faults with loss of multiple-circuit tower line.

 

No relevant high speed reclosing (HSR) contingencies were identified for this study.

 

For all simulations, the Cluster 25 projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all of the fault contingencies tested on the 2027 peak load case:

       a)       Cluster 25 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 25 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3%.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

AG1-354 and AG1-471 meet the 0.95 leading and lagging PF requirement.

 

AG1-471 generator unit remained at High Voltage Ride Through mode for several  contingencies. As a result, the AG1-471 generator terminal voltage remained at approximately 1.12 pu after fault recovery which exceeds the range of 0.95 pu – 1.05 pu. This issue caused the voltage relay stage set to 1.1 pu for 10 seconds to pick up and trip AG1-471 generating unit. Modifying CON(J+1): Vup to 1.16 pu of the REECA1 model resolved the issue of AG1-471 getting stuck in HVRT mode and resolved the tripping of the unit. The AG1-471 developer confirmed the proposed settings .

 

No mitigations were found to be required.

 

Table 1: TC1 Cluster 25 Projects

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

25

AG1-354

Solar

EKPC

150.0

150.0

90.0

Summershade - Green County 161 kV

AG1-471

Solar

EKPC

54.0

54.0

32.4

Up Church-Wayne County 69 kV

 

 

Reactive Power Analysis

The reactive power capability of AG1-471 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AE1-143Marion County 161 kVUnder Construction
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AF1-038Sewellton Jct-Webbs Crossroads 69 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AG1-341Summer Shade 161 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVEngineering & Procurement

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)Identified Impacts
AG1-471 System Reinforcements:
TOTrans Owner IDTitleCategoryAllocated Cost ($USD)
LGEELGEE_TC1_15519Invalid - P7 contingency 69kV not monitored by LGEEInformational$0
LGEELGEE_TC1_15524Load shedding of 10% PC load is allowed for P7 contingencyInformational$0
LGEENoneLoad shedding of 10% PC load is allowed for P2 contingencyInformational$0
LGEELGEE_TC1_15523Load shedding of 10% PC load is allowed for P4 contingencyInformational$0
Grand Total:$0

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15519
Title
Invalid - P7 contingency 69kV not monitored by LGEE
Description
Invalid - P7 contingency 69kV not monitored by LGEE EKPC emergency rating is 143 MVA on the Somerset KU - Ferguston 69kV line.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15524
Title
Load shedding of 10% PC load is allowed for P7 contingency
Description
Load shedding of 10% PC load is allowed for P7 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending)
Title
Load shedding of 10% PC load is allowed for P2 contingency
Description
Load shedding of 10% PC load is allowed for P2 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15523
Title
Load shedding of 10% PC load is allowed for P4 contingency
Description
Load shedding of 10% PC load is allowed for P4 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In coordination with other Affected System Operators, PJM has determined that the Affected System Operator for this project that requires an Affected System Study. For the latest Affected System Study results pertaining this project, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM lists any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)No Impact
Note: Please communicate with the Affected System Operator regarding the status of the Affected System Study for your project.
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Final System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc1-r0004a
Title
EKPC emergency rating is 143 MVA.
Description
EKPC emergency rating is 143 MVA. LG&E: SE rating is 105 MVA.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A143.0 MVA
(All)B143.0 MVA
(All)C143.0 MVA

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc1-r0012a
Title
LGE/KU is limiting this facility. EKPC emergency rating is 298 MVA.
Description
LGE/KU is limiting this facility (LGEE Summer 219/277 MVA & winter 335/335 MVA Rate A/Rate B). EKPC emergency rating is 298 MVA. LGEE AFS for TC1 has determined they will not require an reinforcement and thus EKPC existing 298 MVA Rate B is adequate as LGEE is the limiting element of the line.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA267.0 MVA
SUMB298.0 MVA
SUMC298.0 MVA


Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG1-471


AG1-471 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AG1-471 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG1-471 One Line Diagram

AG1-471 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.