AF2-120 Phase III Study Report

v1.00 released 2025-09-18 16:43

Garner-Northern Neck 115 kV

37.2 MW Capacity / 62.0 MW Energy

Introduction

This Phase III System Impact Study Report (PH3) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 312 for New Service Requests (projects) in Transition Cycle 1. The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (Dominion Virginia Power).

Preface

New Service Requests meeting the requirements of Tariff, Part VII, Subpart D, Decision Point II, were included in the Phase III System Impact Study. The Phase III System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase III System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.7, PJM takes the following actions during the Phase III System Impact Study:
  1. PJM will retool load flow, short circuit and stability results based on decisions made by Project Developers or Eligible Customers during Decision Point II.
  2. PJM will coordinate with Affected System Operators to conduct any studies required to determine the final impact of a New Service Request on any Affected System and will include the final Affected System Study results in the Phase III System Impact Study, if available from the Affected System.
  3. The Phase III System Impact Study Results will be publicly available on PJM’s website; Project Developers and Eligible Customers must obtain the results from the website.
  4. PJM will tender draft final agreements to Project Developers or Eligible Customers.
The Transmission Owner takes the following actions during the Phase III System Impact Study:
  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase III System Impact Study phase will be for the System Reliability Network Upgrades. The Facilities Study requirements are outlined in Attachment C of PJM Manual 14H. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7).

Decision Point III Requirements

At the close of Phase III System Impact Study, PJM will initiate Decision Point III (DP3). During DP3, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 313.A. Additional information on these elements is available in PJM Manual 14H sections 4.8, 6, and 7.

As stated in PJM Tariff, Part VII, Subpart D, section 313.C, New Service Requests may not be changed or modified in any way for any reason during Decision Point III. A New Service Request must be withdrawn and resubmitted in a subsequent Cycle to the extent a Project Developer or Eligible Customer wants to make any changes to such New Service Request at this point in the Cycle process.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP3 with cumulative Readiness Deposits forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 313.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point III, the Network Upgrade cost from Phase II to Phase III must:

  1. Increase overall by 35% or more
  2. Increases by more than $25,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase, Decision Point I, and Decision Point II (RD1, and RD2 and RD3, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP3 Adverse Eligibility = DP3 Adverse Cost Alloc DP2 Adverse Cost Alloc > 1.35 AND ( DP3 Adverse Cost Alloc - DP2 Adverse Cost Alloc ) Project Size > $25,000 per MW
DP3 Adverse Eligibility = $39,584,227 $38,774,644 = 1.02 AND ( $39,584,227 - $38,774,644 ) 62.0 = $13,058 per MW

General

The Project Developer has proposed a Solar generating facility located in the Virginia Electric and Power Company (Dominion Virginia Power) zone — Richmond County, Virginia. The installed facilities will have a total capability of 62.0 MW with 37.2 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AF2-120
Project Name:
Garner-Northern Neck 115 kV
Project Developer Name:
Virginia Electric and Power Company
State:
Virginia
County:
Richmond
Transmission Owner:
Virginia Electric and Power Company (Dominion Virginia Power)
MFO:
62.0
MWE:
62.0
MWC:
37.2
Fuel Type:
Solar
Basecase Study Year:
2027

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AF2-120 will interconnect on the Dominion transmission system via a direct connection to the new substation constructed for the AE1-155 project (Moon Corner) located between Garner and Northern Neck 115 kV substations, sharing interconnection facilities with AG1-536.

 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase III SIS, the interconnected Transmission Owner has performed a facilities study for the required System Reliability Network Upgrades. The Facilities Studies for the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades were performed by the Transmission Owner in Phase II and are available for download on PJM.com (see General Section for document links).

Based on the Phase III SIS results, the AF2-120 project has the following allocation of costs for interconnection. The Security amount required at DP3 is also shown below.

Cost Summary
Description Cost Allocated to AF2-120 Cost Subject to Security
Transmission Owner Interconnection Facilities (TOIF) $1,219,290 $1,219,290
Other Scope $0 $0
Option to Build Oversight $0 $0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades $0 $0
Network Upgrades $1,219,184 $1,219,184
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL) $34,436,117 $34,436,117
Transient Stability $3,851,263 $3,851,263
Short Circuit $77,663 $77,663
Transmission Owner Analysis
SubRegional $0 $0
Distribution $0 $0
Affected System Study Reinforcements
AFS - PJM Violatons $0 $0
AFS - Non-PJM Violations $0 $0
Total $40,803,516 $40,803,516

* Contributes to calculation for Security. See Security Section of this report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Security Requirement

Per Tariff Part VII, Subpart D, section 313 (Decision Point III) A.1.a and PJM Manual 14H, section 8.6.1, Project Developers and Eligible Customers are required to provide Security in a form acceptable to PJM at Decision Point III which runs concurrently with the projects' Final Agreement Negotiation Phase. Security may be in the form of cash, letter of credit, or other form of Security acceptable to PJM (see PJM M14H, Section 6.4).

Security is calculated for a New Service Request based on the Network Upgrade costs allocated pursuant to the Phase III System Impact Study results.

Note 1: "Network Upgrades" referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Security Due for AF2-120/AG1-536

Security has been calculated for the AF2-120/AG1-536 project(s) based on the Phase III System Impact Study results and is shown in the table below. This Security must be provided at Decision Point III through either a wire transfer or letter of credit or other form of Security deemed acceptable by PJM per Manual 14H, Section 6.4.

Security Due for AF2-120/AG1-536
Project(s): AF2-120/AG1-536
Final Agreement Security (A): $85,831,295
Portion of Costs Already Paid (B): $3,055,600
Net Security Due at DP3: A − B = $82,775,695
Note: Failure to provide an acceptable form of Security by the end of Decision Point III will result in withdrawal and termination of the New Service Request.

Transmission Owner Scope of Work

The New Service Request Project will interconnect with the Dominion transmission system via a direct connect to the Moon Corner Substation along the Garner-Northern Neck 115 kV Line. The required work for the interconnection of the New Service Request Project to the Dominion Transmission System is detailed in the following tables.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Network Upgrades
RTEP ID Description Direct Indirect Total Cost ($USD) Allocated Cost ($USD)
Labor Materials Labor Materials
n8218

Expansion of Existing Moon Corner Substation

$1,400,804 $846,686 $120,017 $70,861 $2,438,368 $1,219,184 (See Note 1)
Transmission Owner Interconnection Facilities
RTEP ID Description Direct Indirect Total Cost ($USD) Allocated Cost ($USD)
Labor Materials Labor Materials
(Pending)

The installation of two new backbone structures and line conductor at the existing Moon Corner Substation.

$1,757,687 $475,788 $168,899 $36,205 $2,438,579 $1,219,290 (See Note 1)

Based on the scope of work for the Interconnection Facilities, it is expected to take 43 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase 2 of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

 

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here. Refer to AF2-120 Physical Interconnection Facilities Study for additional requirements found in the General Section of the report.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards and in the Physical Interconnection Facilities Study.

Summer Peak Analysis

The New Service Request was evaluated as a 62.0 MW (37.2 MW Capacity) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential summer peak period network impacts were as follows:

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The full energy output of Generation Interconnection Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).

The following flowgates remain after considering the topology reinforcements required by the cycle.

Area Facility Description Contingency Name Contingency Type DC|AC Final Cycle Loading Rating (MVA) Rating Type MVA to Mitigate MW Contribution Details
DVP 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
314218 to 314908 ckt 1
DVP_P4-2: H2T557_SRT-S
CONTINGENCY 'DVP_P4-2: H2T557_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Breaker AC 134.11 % 1065.0 C 1428.3 9.99
DVP 6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 1 transformer
314196 to 314911 ckt 1
DVP_P4-2: H2T574_SRT-S_SENS
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
END
Breaker AC 117.45 % 1031.0 C 1210.88 7.91
DVP 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
314181 to 314182 ckt 2
DVP_P1-3: 6NORNECK-TX#4_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#4_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
END
Single AC 123.6 % 177.38 B 219.24 24.61
DVP 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
314181 to 314182 ckt 1
DVP_P1-3: 6NORNECK-TX#6_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#6_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
Single AC 117.36 % 179.92 B 211.15 23.63
DVP 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
314181 to 314182 ckt 2
DVP_P1-2: LN 65_SRT-SW-A
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-A'
 OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1   /*3OCRAN       115.0 - 3LANCAST     115.0
 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1   /*3OCRAN       115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1   /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1   /*3LANCAST     115.0 - 3LANCA_1     115.0
 OPEN BRANCH FROM BUS 962970 TO BUS 314178 CKT 1   /*AG1-146 TP   115.0 - 3LANCAST     115.0
 OPEN BUS 313813                                   /*3OCRAN       115.0
 OPEN BUS 314178                                   /*3LANCAST     115.0
 OPEN BUS 314191                                   /*3WHIT STONE  115.0
 OPEN BUS 314400                                   /*3LANCA_1     115.0
END
Single AC 106.27 % 177.38 B 188.51 20.3

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
314218 to 314908 ckt 1
Contingency Name:
DVP_P4-2: H2T557_SRT-S
CONTINGENCY 'DVP_P4-2: H2T557_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: Breaker
DC|AC: AC
Final Cycle Loading: 134.11 %
Rating: 1065.0 MVA
Rating Type: C
MVA to Mitigate: 1428.3 MVA
MW Contribution: 9.99 MW
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area: DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
314218 to 314908 ckt 1
Contingency Name:
DVP_P4-2: H2T557_SRT-S
CONTINGENCY 'DVP_P4-2: H2T557_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: Breaker
DC|AC: AC
Final Cycle Loading: 168.67 %
Rating: 1065.0 MVA
Rating Type: C
MVA to Mitigate: 1796.38 MVA
MW Contribution: 11.42 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961941 AG1-037 C Adder 0.36 MW 0.3 MW
961942 AG1-037 E Adder 0.24 MW 0.2 MW
962331 AG1-082 C Adder 1.43 MW 1.22 MW
962332 AG1-082 E Adder 0.95 MW 0.81 MW
965291 AG1-394 C Adder 0.62 MW 0.53 MW
965292 AG1-394 E Adder 1.14 MW 0.97 MW
966621 AG1-532 C Adder 0.95 MW 0.81 MW
966622 AG1-532 E Adder 0.63 MW 0.54 MW
314541 3WATKINS Adder 0.52 MW 0.44 MW
314572 3EMPORIA Adder 0.29 MW 0.25 MW
918492 AA1-063AE OP Adder 2.83 MW 2.41 MW
920042 AA2-088 E OP Adder 7.72 MW 6.56 MW
934521 AD1-076 C Adder 8.86 MW 7.53 MW
934522 AD1-076 E Adder 4.51 MW 3.84 MW
943172 AE2-346 E Adder 0.43 MW 0.36 MW
960081 AF2-299 C Adder 1.27 MW 1.08 MW
960082 AF2-299 E Adder 0.84 MW 0.72 MW
316141 AB2-099 E Adder 0.18 MW 0.15 MW
900672 V4-068 E Adder 0.26 MW 0.22 MW
940492 AE2-034 E Adder 2.28 MW 1.94 MW
946281 AF1-292 C Adder 1.05 MW 0.89 MW
946282 AF1-292 E Adder 0.7 MW 0.59 MW
957521 AF2-046 C Adder 10.16 MW 8.64 MW
957522 AF2-046 E Adder 5.14 MW 4.37 MW
314539 3UNCAMP Adder 4.63 MW 3.94 MW
916042 Z1-036 E Adder 21.64 MW 18.4 MW
938771 AE1-103 C Adder 2.25 MW 1.91 MW
938772 AE1-103 E Adder 3.11 MW 2.64 MW
314229 6MT RD221 50/50 0.18 MW 0.18 MW
314236 6NRTHEST 50/50 0.24 MW 0.24 MW
314331 6POE Adder 1.25 MW 1.06 MW
314507 3THOMPSN Adder 1.62 MW 1.38 MW
314525 6KINGFORK Adder 0.83 MW 0.71 MW
314550 6HICKORY Adder 1.72 MW 1.46 MW
315050 1FOURRIVERG 50/50 6.28 MW 6.28 MW
315060 1CHESTF5 Adder 70.53 MW 59.95 MW
315065 1CHESTF6 Adder 21.43 MW 18.22 MW
315067 1DARBY 1 50/50 3.25 MW 3.25 MW
315068 1DARBY 2 50/50 3.26 MW 3.26 MW
315069 1DARBY 3 50/50 3.27 MW 3.27 MW
315070 1DARBY 4 50/50 3.27 MW 3.27 MW
315073 1STONECA Adder 7.28 MW 6.19 MW
315083 1SPRUNCA Adder 10.11 MW 8.6 MW
315084 1SPRUNCB Adder 10.11 MW 8.6 MW
315092 1YORKTN3 Adder 118.93 MW 101.09 MW
925865 AC1-065 E Adder 16.6 MW 14.11 MW
926412 AC1-112 E 50/50 1.51 MW 1.51 MW
926472 AC1-118 E Adder 0.95 MW 0.81 MW
926662 AC1-147 E Adder 1.06 MW 0.9 MW
926755 AC1-161 E Adder 10.1 MW 8.59 MW
927226 AC1-216 E Adder 7.54 MW 6.41 MW
934392 AD1-063 E Adder 1.07 MW 0.91 MW
934781 AD1-105 C 50/50 1.55 MW 1.55 MW
934782 AD1-105 E 50/50 6.42 MW 6.42 MW
935112 AD1-144 E Adder 0.77 MW 0.66 MW
936582 AD2-073 E Adder 0.99 MW 0.84 MW
936591 AD2-074 C Adder 5.36 MW 4.55 MW
936592 AD2-074 E Adder 8.74 MW 7.43 MW
942341 AE2-247 C Adder 1.25 MW 1.06 MW
942342 AE2-247 E Adder 1.73 MW 1.47 MW
943461 AF1-017 C Adder 1.13 MW 0.96 MW
943462 AF1-017 E Adder 1.84 MW 1.57 MW
943612 AF1-032 E Adder 0.73 MW 0.62 MW
943741 AF1-042 C Adder 2.8 MW 2.38 MW
943742 AF1-042 E Adder 4.57 MW 3.89 MW
944491 AF1-114 C Adder 4.88 MW 4.14 MW
944492 AF1-114 E Adder 6.73 MW 5.72 MW
961951 AG1-038 C Adder 3.1 MW 2.63 MW
961952 AG1-038 E Adder 4.28 MW 3.64 MW
966661 AG1-536 C Adder 5.15 MW 4.38 MW
966662 AG1-536 E Adder 6.93 MW 5.89 MW
966871 AG1-558 C 50/50 3.55 MW 3.55 MW
966872 AG1-558 E 50/50 1.79 MW 1.79 MW
966881 AG1-559 C Adder 2.03 MW 1.73 MW
966882 AG1-559 E Adder 1.02 MW 0.87 MW
315260 1GOSPORTA Adder 1.71 MW 1.45 MW
315261 1GOSPORTB Adder 2.18 MW 1.86 MW
315262 1GOSPORTC Adder 1.85 MW 1.58 MW
316076 AC2-137 E Adder 1.54 MW 1.31 MW
316078 AC2-138 E Adder 0.89 MW 0.76 MW
316157 AD2-030 E Adder 1.16 MW 0.99 MW
913392 Y1-086 E Adder 1.71 MW 1.46 MW
916192 Z1-068 E Adder 1.5 MW 1.27 MW
923832 AB2-022 E Adder 0.97 MW 0.82 MW
923842 AB2-024 E Adder 1.81 MW 1.54 MW
923852 AB2-025 E Adder 0.86 MW 0.73 MW
930122 AB1-027 E 50/50 1.86 MW 1.86 MW
938552 AE1-074 E Adder 1.21 MW 1.03 MW
939312 AE1-162 E Adder 1.24 MW 1.06 MW
946262 AF1-291 E Adder 1.54 MW 1.31 MW
957411 AF2-035 C Adder 7.34 MW 6.24 MW
957412 AF2-035 E Adder 3.67 MW 3.12 MW
957492 AF2-043 E Adder 1.13 MW 0.96 MW
957601 AF2-054 C Adder 2.07 MW 1.76 MW
957602 AF2-054 E Adder 1.38 MW 1.17 MW
962861 AG1-135 C Adder 5.82 MW 4.95 MW
962862 AG1-135 E Adder 3.88 MW 3.3 MW
962962 AG1-145 E Adder 1.39 MW 1.18 MW
962971 AG1-146 C Adder 2.98 MW 2.53 MW
962972 AG1-146 E Adder 1.99 MW 1.69 MW
962981 AG1-147 C Adder 6.95 MW 5.91 MW
962982 AG1-147 E Adder 4.64 MW 3.94 MW
963611 AG1-210 C Adder 0.64 MW 0.54 MW
963612 AG1-210 E Adder 0.96 MW 0.81 MW
964211 AG1-282 C Adder 1.95 MW 1.66 MW
964212 AG1-282 E Adder 1.3 MW 1.1 MW
901082 W1-029 E Adder 24.7 MW 21.0 MW
917122 Z2-027 E Adder 1.04 MW 0.89 MW
925332 AB2-190 E Adder 8.13 MW 6.91 MW
925522 AC1-027 E Adder 0.97 MW 0.82 MW
942001 AE2-212 C Adder 2.19 MW 1.86 MW
942002 AE2-212 E Adder 1.46 MW 1.24 MW
957832 AF2-077 E Adder 1.33 MW 1.13 MW
957871 AF2-081 C Adder 7.85 MW 6.67 MW
957872 AF2-081 E Adder 3.36 MW 2.86 MW
957971 AF2-091 C Adder 1.66 MW 1.41 MW
957972 AF2-091 E Adder 2.29 MW 1.95 MW
958161 AF2-110 C Adder 1.1 MW 0.93 MW
958162 AF2-110 E Adder 1.74 MW 1.48 MW
313811 6ELKO L286 Adder 1.61 MW 1.37 MW
314181 3NORNECK Adder 0.85 MW 0.72 MW
933291 AC2-141 C Adder 23.67 MW 20.12 MW
933292 AC2-141 E Adder 10.1 MW 8.59 MW
939411 AE1-173 C Adder 60.71 MW 51.6 MW
939412 AE1-173 E Adder 40.47 MW 34.4 MW
934012 AD1-025 E Adder 9.76 MW 8.29 MW
927041 AC1-191 C 50/50 14.26 MW 14.26 MW
927042 AC1-191 E 50/50 7.11 MW 7.11 MW
933981 AD1-022 C Adder 6.3 MW 5.35 MW
933982 AD1-022 E Adder 3.43 MW 2.92 MW
961681 AG1-008 C Adder 10.16 MW 8.64 MW
961682 AG1-008 E Adder 5.14 MW 4.37 MW
313053 6PAPERMILL Adder 6.68 MW 5.68 MW
314594 6PLYMOUTH TP Adder 0.23 MW 0.2 MW
314632 6AYDLETT TAP Adder 1.06 MW 0.9 MW
316004 AC1-112 C 50/50 0.44 MW 0.44 MW
316160 AE1-175 E Adder 1.14 MW 0.97 MW
316169 AC1-164 GEN Adder 43.81 MW 37.24 MW
316233 AE1-074 C Adder 2.4 MW 2.04 MW
316240 AF1-291 C Adder 2.32 MW 1.97 MW
316312 AB1-027 C 50/50 0.71 MW 0.71 MW
917332 KELFORD E Adder 1.16 MW 0.99 MW
924516 AB2-100 E1 Adder 2.03 MW 1.73 MW
924517 AB2-100 E2 Adder 2.03 MW 1.73 MW
926206 AC1-098 E Adder 1.88 MW 1.6 MW
926785 AC1-164_E Adder 19.68 MW 16.73 MW
934065 AD1-033 E Adder 3.96 MW 3.37 MW
937226 AE2-253 E Adder 4.59 MW 3.9 MW
939612 AE1-191 E Adder 5.63 MW 4.78 MW
315051 AA1-145 CT1 50/50 6.56 MW 6.56 MW
315052 AA1-145 CT2 50/50 6.56 MW 6.56 MW
939246 AE1-155 E Adder 8.34 MW 7.09 MW
918512 AA1-065 E OP Adder 3.9 MW 3.32 MW
919153 AA1-139 E2 Adder 3.21 MW 2.73 MW
919152 AA1-139 E1 Adder 3.21 MW 2.73 MW
920692 AA2-178 E Adder 3.04 MW 2.58 MW
924814 AB2-134 E Adder 12.34 MW 10.49 MW
316084 AB2-161 E Adder 4.94 MW 4.2 MW
316088 AB2-174 E Adder 4.41 MW 3.75 MW
932046 AC2-012 E Adder 10.52 MW 8.94 MW
316311 AC2-079 C Adder 4.78 MW 4.06 MW
932596 AC2-079 E Adder 7.8 MW 6.63 MW
934146 AD1-041 E Adder 3.52 MW 2.99 MW
934576 AD1-082 E Adder 3.94 MW 3.35 MW
316349 AD2-085 C Adder 2.88 MW 2.45 MW
936666 AD2-085 E Adder 4.7 MW 4.0 MW
961611 AG1-000B C Adder 14.77 MW 12.55 MW
941591 AE2-156 C Adder 14.37 MW 12.21 MW
944581 AF1-123 C Adder 35.81 MW 30.43 MW
944582 AF1-123 E Adder 81.99 MW 69.69 MW
944591 AF1-124 C Adder 35.93 MW 30.54 MW
944592 AF1-124 E Adder 82.29 MW 69.95 MW
944601 AF1-125 C Adder 35.26 MW 29.97 MW
944602 AF1-125 E Adder 80.71 MW 68.6 MW
944631 AF1-128 C Adder 44.13 MW 37.51 MW
958261 AF2-120 C Adder 5.99 MW 5.09 MW
958262 AF2-120 E Adder 3.99 MW 3.4 MW
965281 AG1-393 C Adder 2.22 MW 1.89 MW
965282 AG1-393 E Adder 1.48 MW 1.26 MW
934501 AD1-074 C Adder 24.38 MW 20.73 MW
934502 AD1-074 E Adder 12.41 MW 10.55 MW
934511 AD1-075 C Adder 6.1 MW 5.18 MW
934512 AD1-075 E Adder 3.1 MW 2.64 MW
935161 AD1-151 C Adder 16.02 MW 13.61 MW
935162 AD1-151 E Adder 10.68 MW 9.08 MW
938531 AE1-072 C Adder 13.78 MW 11.71 MW
938532 AE1-072 E Adder 7.18 MW 6.11 MW
939191 AE1-149 C Adder 10.01 MW 8.51 MW
939192 AE1-149 E Adder 6.67 MW 5.67 MW
939261 AE1-157 C Adder 9.71 MW 8.26 MW
939262 AE1-157 E Adder 5.27 MW 4.48 MW
939602 AE1-190 E Adder 1.41 MW 1.2 MW
940431 AE2-027 C Adder 13.54 MW 11.51 MW
940432 AE2-027 E Adder 9.03 MW 7.67 MW
940481 AE2-033 C Adder 11.92 MW 10.13 MW
940482 AE2-033 E Adder 8.03 MW 6.83 MW
940541 AE2-040 C Adder 2.13 MW 1.81 MW
940551 AE2-041 C Adder 7.13 MW 6.06 MW
940641 AE2-051 C Adder 10.94 MW 9.3 MW
940642 AE2-051 E Adder 7.29 MW 6.2 MW
941101 AE2-104 C Adder 2.68 MW 2.28 MW
941102 AE2-104 E Adder 4.27 MW 3.63 MW
943471 AF1-018 C Adder 7.13 MW 6.06 MW
944641 AF1-129 C Adder 111.79 MW 95.02 MW
315043 1FOUR RIVERA 50/50 4.12 MW 4.12 MW
315044 1FOUR RIVERB 50/50 4.12 MW 4.12 MW
315045 1FOUR RIVERC 50/50 5.03 MW 5.03 MW
315046 1FOUR RIVERD 50/50 4.06 MW 4.06 MW
315047 1FOUR RIVERE 50/50 4.06 MW 4.06 MW
315048 1FOUR RIVERF 50/50 4.96 MW 4.96 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 4.44 MW 4.44 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 41.67 MW 41.67 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.59 MW 1.59 MW
NY PJM->LTFIMP_NY CLTF 0.81 MW 0.81 MW
CPLE LTFEXP_CPLE->PJM CLTF 5.58 MW 5.58 MW
TVA LTFEXP_TVA->PJM CLTF 1.58 MW 1.58 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.05 MW 0.05 MW
MEC LTFEXP_MEC->PJM CLTF 0.3 MW 0.3 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.13 MW 0.13 MW
LAGN LTFEXP_LAGN->PJM CLTF 2.09 MW 2.09 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.01 MW 0.01 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 10.18 MW 10.18 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 2.65 MW 2.65 MW

Details for 6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T574_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 1 transformer
314196 to 314911 ckt 1
Contingency Name:
DVP_P4-2: H2T574_SRT-S_SENS
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 313483 CKT 1 /*8LADYSMITH   500.0 - 8KRAKEN      500.0
END
Contingency Type: Breaker
DC|AC: AC
Final Cycle Loading: 117.45 %
Rating: 1031.0 MVA
Rating Type: C
MVA to Mitigate: 1210.88 MVA
MW Contribution: 7.91 MW
Impact of Topology Modeling:
Addition
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314229 6MT RD221 50/50 0.11 MW 0.11 MW
314331 6POE Adder 0.71 MW 0.61 MW
314507 3THOMPSN Adder 0.97 MW 0.82 MW
314525 6KINGFORK Adder 0.5 MW 0.42 MW
315033 1BIRCHWDA Adder 33.1 MW 28.14 MW
315039 1LDYSMT3 50/50 10.19 MW 10.19 MW
315040 1LDYSMT4 50/50 10.21 MW 10.21 MW
315041 1LDYSMT5 50/50 10.24 MW 10.24 MW
315050 1FOURRIVERG 50/50 4.57 MW 4.57 MW
315060 1CHESTF5 Adder 42.49 MW 36.12 MW
315065 1CHESTF6 Adder 12.43 MW 10.56 MW
315073 1STONECA Adder 4.31 MW 3.67 MW
315083 1SPRUNCA Adder 5.78 MW 4.91 MW
315084 1SPRUNCB Adder 5.78 MW 4.91 MW
315092 1YORKTN3 Adder 74.34 MW 63.19 MW
925865 AC1-065 E Adder 11.21 MW 9.53 MW
926412 AC1-112 E Adder 0.9 MW 0.77 MW
926472 AC1-118 E Adder 0.93 MW 0.79 MW
926662 AC1-147 E Adder 0.63 MW 0.54 MW
927226 AC1-216 E Adder 4.49 MW 3.82 MW
934392 AD1-063 E Adder 0.72 MW 0.61 MW
934781 AD1-105 C 50/50 1.18 MW 1.18 MW
934782 AD1-105 E 50/50 4.88 MW 4.88 MW
935112 AD1-144 E Adder 0.46 MW 0.39 MW
936582 AD2-073 E Adder 0.88 MW 0.75 MW
936591 AD2-074 C Adder 4.1 MW 3.49 MW
936592 AD2-074 E Adder 6.7 MW 5.69 MW
942341 AE2-247 C Adder 0.74 MW 0.63 MW
942342 AE2-247 E Adder 1.02 MW 0.87 MW
943461 AF1-017 C Adder 0.67 MW 0.57 MW
943462 AF1-017 E Adder 1.09 MW 0.93 MW
943741 AF1-042 C Adder 2.15 MW 1.82 MW
943742 AF1-042 E Adder 3.5 MW 2.98 MW
944491 AF1-114 C Adder 6.13 MW 5.21 MW
944492 AF1-114 E Adder 8.47 MW 7.2 MW
961951 AG1-038 C Adder 2.37 MW 2.02 MW
961952 AG1-038 E Adder 3.28 MW 2.79 MW
966661 AG1-536 C Adder 4.08 MW 3.47 MW
966662 AG1-536 E Adder 5.48 MW 4.66 MW
966871 AG1-558 C Adder 2.17 MW 1.84 MW
966872 AG1-558 E Adder 1.09 MW 0.93 MW
966881 AG1-559 C 50/50 4.18 MW 4.18 MW
966882 AG1-559 E 50/50 2.11 MW 2.11 MW
315260 1GOSPORTA Adder 1.02 MW 0.87 MW
315261 1GOSPORTB Adder 1.3 MW 1.11 MW
315262 1GOSPORTC Adder 1.11 MW 0.94 MW
316076 AC2-137 E Adder 0.95 MW 0.8 MW
316078 AC2-138 E Adder 0.72 MW 0.61 MW
316157 AD2-030 E Adder 0.8 MW 0.68 MW
916192 Z1-068 E Adder 0.89 MW 0.76 MW
923842 AB2-024 E Adder 1.22 MW 1.03 MW
930122 AB1-027 E Adder 1.11 MW 0.94 MW
938552 AE1-074 E Adder 0.67 MW 0.57 MW
939312 AE1-162 E Adder 0.74 MW 0.63 MW
946262 AF1-291 E Adder 0.89 MW 0.76 MW
957411 AF2-035 C 50/50 15.1 MW 15.1 MW
957412 AF2-035 E 50/50 7.55 MW 7.55 MW
957601 AF2-054 C Adder 1.42 MW 1.21 MW
957602 AF2-054 E Adder 0.95 MW 0.81 MW
962861 AG1-135 C Adder 4.58 MW 3.89 MW
962862 AG1-135 E Adder 3.05 MW 2.59 MW
962962 AG1-145 E Adder 0.87 MW 0.74 MW
962971 AG1-146 C Adder 2.24 MW 1.9 MW
962972 AG1-146 E Adder 1.49 MW 1.27 MW
962981 AG1-147 C Adder 5.23 MW 4.44 MW
962982 AG1-147 E Adder 3.48 MW 2.96 MW
963051 AG1-154 C 50/50 7.8 MW 7.8 MW
963052 AG1-154 E 50/50 11.71 MW 11.71 MW
963611 AG1-210 C Adder 0.52 MW 0.44 MW
963612 AG1-210 E Adder 0.77 MW 0.66 MW
964211 AG1-282 C Adder 1.54 MW 1.31 MW
964212 AG1-282 E Adder 1.03 MW 0.88 MW
925332 AB2-190 E Adder 4.83 MW 4.11 MW
925522 AC1-027 E Adder 0.58 MW 0.49 MW
942001 AE2-212 C Adder 1.26 MW 1.07 MW
942002 AE2-212 E Adder 0.84 MW 0.71 MW
957832 AF2-077 E Adder 0.88 MW 0.74 MW
957971 AF2-091 C Adder 2.08 MW 1.77 MW
957972 AF2-091 E Adder 2.88 MW 2.45 MW
313811 6ELKO L286 Adder 0.99 MW 0.84 MW
314181 3NORNECK Adder 0.69 MW 0.58 MW
934012 AD1-025 E Adder 5.82 MW 4.94 MW
927041 AC1-191 C Adder 8.7 MW 7.39 MW
927042 AC1-191 E Adder 4.33 MW 3.68 MW
313053 6PAPERMILL Adder 4.49 MW 3.81 MW
316160 AE1-175 E Adder 0.72 MW 0.61 MW
316169 AC1-164 GEN Adder 27.54 MW 23.41 MW
316233 AE1-074 C Adder 1.32 MW 1.12 MW
316240 AF1-291 C Adder 1.34 MW 1.14 MW
926785 AC1-164_E Adder 12.37 MW 10.52 MW
939612 AE1-191 E Adder 3.83 MW 3.26 MW
315037 1LDYSMT1 50/50 9.8 MW 9.8 MW
315038 1LDYSMT2 50/50 9.93 MW 9.93 MW
315051 AA1-145 CT1 50/50 6.08 MW 6.08 MW
315052 AA1-145 CT2 50/50 6.08 MW 6.08 MW
939246 AE1-155 E Adder 6.61 MW 5.62 MW
924814 AB2-134 E Adder 7.36 MW 6.26 MW
316084 AB2-161 E Adder 2.89 MW 2.46 MW
932046 AC2-012 E Adder 6.28 MW 5.33 MW
316311 AC2-079 C Adder 2.82 MW 2.4 MW
932596 AC2-079 E Adder 4.6 MW 3.91 MW
934146 AD1-041 E Adder 2.39 MW 2.04 MW
934576 AD1-082 E Adder 2.3 MW 1.96 MW
316349 AD2-085 C Adder 1.7 MW 1.45 MW
936666 AD2-085 E Adder 2.78 MW 2.36 MW
961611 AG1-000B C Adder 8.85 MW 7.52 MW
941591 AE2-156 C Adder 8.57 MW 7.28 MW
944631 AF1-128 C Adder 26.59 MW 22.6 MW
958261 AF2-120 C Adder 4.74 MW 4.03 MW
958262 AF2-120 E Adder 3.16 MW 2.69 MW
965281 AG1-393 C Adder 1.3 MW 1.1 MW
965282 AG1-393 E Adder 0.86 MW 0.73 MW
935161 AD1-151 C Adder 9.54 MW 8.11 MW
935162 AD1-151 E Adder 6.36 MW 5.4 MW
939191 AE1-149 C Adder 5.82 MW 4.95 MW
939192 AE1-149 E Adder 3.88 MW 3.3 MW
939261 AE1-157 C 50/50 26.64 MW 26.64 MW
939262 AE1-157 E 50/50 14.45 MW 14.45 MW
939602 AE1-190 E Adder 0.96 MW 0.81 MW
940431 AE2-027 C Adder 7.91 MW 6.72 MW
940432 AE2-027 E Adder 5.27 MW 4.48 MW
940551 AE2-041 C Adder 4.82 MW 4.1 MW
943471 AF1-018 C Adder 4.82 MW 4.1 MW
944641 AF1-129 C Adder 64.82 MW 55.1 MW
957191 AF2-013 C Adder 15.56 MW 13.23 MW
315043 1FOUR RIVERA 50/50 3.82 MW 3.82 MW
315044 1FOUR RIVERB 50/50 3.82 MW 3.82 MW
315045 1FOUR RIVERC 50/50 4.67 MW 4.67 MW
315046 1FOUR RIVERD 50/50 3.76 MW 3.76 MW
315047 1FOUR RIVERE 50/50 3.76 MW 3.76 MW
315048 1FOUR RIVERF 50/50 4.6 MW 4.6 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 3.79 MW 3.79 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 4.8 MW 4.8 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 27.23 MW 27.23 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.94 MW 1.94 MW
NY PJM->LTFIMP_NY CLTF 0.92 MW 0.92 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.19 MW 0.19 MW
WEC LTFEXP_WEC->PJM CLTF 0.09 MW 0.09 MW
CPLE LTFEXP_CPLE->PJM CLTF 3.42 MW 3.42 MW
TVA LTFEXP_TVA->PJM CLTF 1.44 MW 1.44 MW
MEC LTFEXP_MEC->PJM CLTF 0.68 MW 0.68 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.83 MW 1.83 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.04 MW 0.04 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 12.37 MW 12.37 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 1.63 MW 1.63 MW

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6NORNECK-TX#4_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
314181 to 314182 ckt 2
Contingency Name:
DVP_P1-3: 6NORNECK-TX#4_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#4_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 123.6 %
Rating: 177.38 MVA
Rating Type: B
MVA to Mitigate: 219.24 MVA
MW Contribution: 24.61 MW
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area: DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
314181 to 314182 ckt 2
Contingency Name:
DVP_P1-3: 6NORNECK-TX#4_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#4_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 111.81 %
Rating: 177.38 MVA
Rating Type: B
MVA to Mitigate: 198.33 MVA
MW Contribution: 21.84 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314184 3SHACKLE 80/20 0.32 MW 0.32 MW
315034 1NORNECKC1 80/20 2.99 MW 2.99 MW
315035 1NORNECKC2 80/20 2.89 MW 2.89 MW
936591 AD2-074 C 80/20 17.86 MW 17.86 MW
943741 AF1-042 C 80/20 9.35 MW 9.35 MW
961951 AG1-038 C 80/20 10.33 MW 10.33 MW
966661 AG1-536 C 80/20 21.17 MW 21.17 MW
316077 AC2-138 C 80/20 1.01 MW 1.01 MW
316156 AD2-030 C 80/20 0.37 MW 0.37 MW
957601 AF2-054 C 80/20 2.05 MW 2.05 MW
962861 AG1-135 C 80/20 22.84 MW 22.84 MW
962971 AG1-146 C 80/20 8.63 MW 8.63 MW
962981 AG1-147 C 80/20 20.14 MW 20.14 MW
963611 AG1-210 C 80/20 2.94 MW 2.94 MW
957831 AF2-077 C 80/20 0.16 MW 0.16 MW
316059 AD1-063 C 80/20 0.11 MW 0.11 MW
939611 AE1-191 C 80/20 1.05 MW 1.05 MW
316201 AC1-065 C 80/20 0.99 MW 0.99 MW
316404 AE1-155 C 80/20 8.35 MW 8.35 MW
316280 AD1-041 C 80/20 0.67 MW 0.67 MW
958261 AF2-120 C 80/20 24.61 MW 24.61 MW
939601 AE1-190 C 80/20 0.26 MW 0.26 MW
940551 AE2-041 C 80/20 2.97 MW 2.97 MW
943471 AF1-018 C 80/20 2.97 MW 2.97 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 0.5 MW 0.5 MW
NY PJM->LTFIMP_NY CLTF 0.06 MW 0.06 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.03 MW 0.03 MW
CPLE LTFEXP_CPLE->PJM CLTF 0.08 MW 0.08 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.08 MW 0.08 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.03 MW 0.03 MW

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6NORNECK-TX#6_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
314181 to 314182 ckt 1
Contingency Name:
DVP_P1-3: 6NORNECK-TX#6_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#6_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 117.36 %
Rating: 179.92 MVA
Rating Type: B
MVA to Mitigate: 211.15 MVA
MW Contribution: 23.63 MW
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area: DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
314181 to 314182 ckt 1
Contingency Name:
DVP_P1-3: 6NORNECK-TX#6_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#6_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 108.05 %
Rating: 179.92 MVA
Rating Type: B
MVA to Mitigate: 194.4 MVA
MW Contribution: 21.07 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314184 3SHACKLE 80/20 0.31 MW 0.31 MW
315034 1NORNECKC1 80/20 2.88 MW 2.88 MW
315035 1NORNECKC2 80/20 2.77 MW 2.77 MW
936591 AD2-074 C 80/20 17.15 MW 17.15 MW
943741 AF1-042 C 80/20 8.97 MW 8.97 MW
961951 AG1-038 C 80/20 9.92 MW 9.92 MW
966661 AG1-536 C 80/20 20.33 MW 20.33 MW
316077 AC2-138 C 80/20 0.97 MW 0.97 MW
316156 AD2-030 C 80/20 0.35 MW 0.35 MW
957601 AF2-054 C 80/20 1.97 MW 1.97 MW
962861 AG1-135 C 80/20 21.94 MW 21.94 MW
962971 AG1-146 C 80/20 8.29 MW 8.29 MW
962981 AG1-147 C 80/20 19.35 MW 19.35 MW
963611 AG1-210 C 80/20 2.83 MW 2.83 MW
957831 AF2-077 C 80/20 0.15 MW 0.15 MW
316059 AD1-063 C 80/20 0.1 MW 0.1 MW
939611 AE1-191 C 80/20 1.01 MW 1.01 MW
316201 AC1-065 C 80/20 0.95 MW 0.95 MW
316404 AE1-155 C 80/20 8.02 MW 8.02 MW
316280 AD1-041 C 80/20 0.64 MW 0.64 MW
958261 AF2-120 C 80/20 23.63 MW 23.63 MW
939601 AE1-190 C 80/20 0.25 MW 0.25 MW
940551 AE2-041 C 80/20 2.85 MW 2.85 MW
943471 AF1-018 C 80/20 2.85 MW 2.85 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 0.48 MW 0.48 MW
NY PJM->LTFIMP_NY CLTF 0.06 MW 0.06 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.02 MW 0.02 MW
CPLE LTFEXP_CPLE->PJM CLTF 0.08 MW 0.08 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.07 MW 0.07 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.06 MW 0.06 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.03 MW 0.03 MW

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 65_SRT-SW-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
314181 to 314182 ckt 2
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-A
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-A'
 OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1   /*3OCRAN       115.0 - 3LANCAST     115.0
 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1   /*3OCRAN       115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1   /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1   /*3LANCAST     115.0 - 3LANCA_1     115.0
 OPEN BRANCH FROM BUS 962970 TO BUS 314178 CKT 1   /*AG1-146 TP   115.0 - 3LANCAST     115.0
 OPEN BUS 313813                                   /*3OCRAN       115.0
 OPEN BUS 314178                                   /*3LANCAST     115.0
 OPEN BUS 314191                                   /*3WHIT STONE  115.0
 OPEN BUS 314400                                   /*3LANCA_1     115.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 106.27 %
Rating: 177.38 MVA
Rating Type: B
MVA to Mitigate: 188.51 MVA
MW Contribution: 20.3 MW
Impact of Topology Modeling:
Increase
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
315034 1NORNECKC1 80/20 2.22 MW 2.22 MW
315035 1NORNECKC2 80/20 2.14 MW 2.14 MW
936591 AD2-074 C 80/20 17.83 MW 17.83 MW
943741 AF1-042 C 80/20 9.33 MW 9.33 MW
961951 AG1-038 C 80/20 10.31 MW 10.31 MW
966661 AG1-536 C 80/20 17.46 MW 17.46 MW
316077 AC2-138 C 80/20 0.75 MW 0.75 MW
962861 AG1-135 C 80/20 19.64 MW 19.64 MW
962971 AG1-146 C 80/20 9.82 MW 9.82 MW
962981 AG1-147 C 80/20 22.92 MW 22.92 MW
963611 AG1-210 C 80/20 2.18 MW 2.18 MW
316404 AE1-155 C 80/20 6.89 MW 6.89 MW
958261 AF2-120 C 80/20 20.3 MW 20.3 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

Area Facility Description Contingency Name Contingency Type DC|AC Final Cycle Loading Rating (MVA) Rating Type MVA to Mitigate MW Contribution Details
DVP AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
316399 to 314181 ckt 1
DVP_P1-2: LN 65_SRT-SW-A
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-A'
 OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1   /*3OCRAN       115.0 - 3LANCAST     115.0
 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1   /*3OCRAN       115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1   /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1   /*3LANCAST     115.0 - 3LANCA_1     115.0
 OPEN BRANCH FROM BUS 962970 TO BUS 314178 CKT 1   /*AG1-146 TP   115.0 - 3LANCAST     115.0
 OPEN BUS 313813                                   /*3OCRAN       115.0
 OPEN BUS 314178                                   /*3LANCAST     115.0
 OPEN BUS 314191                                   /*3WHIT STONE  115.0
 OPEN BUS 314400                                   /*3LANCA_1     115.0
END
Single AC 147.57 % 203.98 B 301.01 37.19
DVP AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
962970 to 314178 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Single AC 144.85 % 203.98 B 295.47 37.19
DVP 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
314934 to 314916 ckt 1
DVP_P1-2: LN 552_SRT-S
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
Single AC 122.77 % 3220.44 B 3953.87 6.41
DVP 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
314934 to 314916 ckt 1
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Single AC 122.25 % 3220.44 B 3936.83 6.31
DVP AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
316399 to 314181 ckt 1
DVP_P1-2: LN 1021_SRT-A
CONTINGENCY 'DVP_P1-2: LN 1021_SRT-A'
 OPEN BRANCH FROM BUS 313842 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_1 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313843 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_2 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 313900 CKT Z1   /*3RAPPAHNCK   115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 1    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 2    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 314174 CKT 1    /*3GREYSPT     115.0 - 3HARMONY     115.0
 OPEN BUS 313842                                    /*3RAPPAHNCK_1 115.0
 OPEN BUS 313843                                    /*3RAPPAHNCK_2 115.0
 OPEN BUS 313886                                    /*3GREYSPT     115.0
 OPEN BUS 313900                                    /*3RAPP TR     115.0
END
Single AC 118.66 % 203.98 B 242.05 37.19
DVP 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
314918 to 314934 ckt 1
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Single AC 117.57 % 3220.44 B 3786.34 6.55
DVP AD2-074 TP-AG1-146 TP 115.0 kV Ckt 1 line
936590 to 962970 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Single AC 116.08 % 203.98 B 236.78 37.19
DVP 3LANCAST-3OCRAN 115.0 kV Ckt 1 line
314178 to 313813 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Single AC 115.13 % 219.96 B 253.24 37.19
DVP 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
314918 to 314934 ckt 1
DVP_P1-2: LN 552_SRT-S
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
Single AC 114.74 % 3220.44 B 3695.07 6.42
DVP 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1
DVP_P1-2: LN 576_SRT-A
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
Single AC 113.8 % 4070.2 B 4632.05 9.55
DVP 3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
313813 to 314191 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Single AC 110.06 % 219.96 B 242.08 37.19
DVP 6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1
DVP_P1-2: LN 574_SRT-S
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
Single AC 104.18 % 548.02 B 570.92 7.82
DVP 6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1
DVP_P1-2: LN 574_SRT-S
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
Single AC 104.13 % 548.02 B 570.64 7.82
DVP 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
314911 to 314922 ckt 1
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Single AC 102.06 % 3220.44 B 3286.74 5.22
DVP 6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1
DVP_P1-2: LN 2090_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2090_SRT-A'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1   /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1   /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1   /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BUS 313837                                   /*6SUMMIT      230.0
 OPEN BUS 314138                                   /*6MINE RD     230.0
END
Single AC 101.54 % 548.02 B 556.48 7.21
DVP 6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1
DVP_P1-2: LN 2090_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2090_SRT-A'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1   /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1   /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1   /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BUS 313837                                   /*6SUMMIT      230.0
 OPEN BUS 314138                                   /*6MINE RD     230.0
END
Single AC 101.48 % 548.02 B 556.11 7.21
DVP 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
314911 to 314922 ckt 1
DVP_P1-2: LN 552_SRT-S
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
Single AC 101.34 % 3220.44 B 3263.68 5.2
DVP 6FREDBRG-6CRANES 230.0 kV Ckt 1 line
314137 to 314134 ckt 1
DVP_P1-2: LN 9296_SRT-A
CONTINGENCY 'DVP_P1-2: LN 9296_SRT-A'
 OPEN BRANCH FROM BUS 314137 TO BUS 314145 CKT 1   /*6FREDBRG     230.0 - 6AQUI_HARB_B 230.0
END
Single AC 101.19 % 984.18 B 995.92 4.75
DVP 6FREDBRG-6CRANES 230.0 kV Ckt 1 line
314137 to 314134 ckt 1
DVP_P1-2: LN 2119_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2119_SRT-A'
 OPEN BRANCH FROM BUS 314140 TO BUS 314145 CKT 1   /*6GARSVL      230.0 - 6AQUI_HARB_B 230.0
END
Single AC 101.17 % 984.18 B 995.73 4.75
DVP 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1
DVP_P1-2: LN 563_SRT-S-1
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
Single AC 100.88 % 4070.2 B 4105.97 8.1
DVP AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
316399 to 314181 ckt 1
DVP_P4-2: 65T1021_SRT-A
CONTINGENCY 'DVP_P4-2: 65T1021_SRT-A'
 OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1    /*3OCRAN       115.0 - 3LANCAST     115.0
 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1    /*3OCRAN       115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313842 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_1 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313843 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_2 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 313900 CKT Z1   /*3RAPPAHNCK   115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1    /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 314174 CKT 1    /*3GREYSPT     115.0 - 3HARMONY     115.0
 OPEN BRANCH FROM BUS 313900 TO BUS 313886 CKT 1    /*3RAPP TR     115.0 - 3GREYSPT     115.0
 OPEN BRANCH FROM BUS 313900 TO BUS 313886 CKT 2    /*3RAPP TR     115.0 - 3GREYSPT     115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1    /*3LANCAST     115.0 - 3LANCA_1     115.0
 OPEN BRANCH FROM BUS 962970 TO BUS 314178 CKT 1    /*AG1-146 TP   115.0 - 3LANCAST     115.0
 OPEN BUS 313813                                    /*3OCRAN       115.0
 OPEN BUS 313842                                    /*3RAPPAHNCK_1 115.0
 OPEN BUS 313843                                    /*3RAPPAHNCK_2 115.0
 OPEN BUS 313886                                    /*3GREYSPT     115.0
 OPEN BUS 314178                                    /*3LANCAST     115.0
 OPEN BUS 314191                                    /*3WHIT STONE  115.0
 OPEN BUS 314400                                    /*3LANCA_1     115.0
END
Breaker AC 233.75 % 249.0 C 582.03 61.98
DVP 6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1
DVP_P4-2: 574T581_SRT-S
CONTINGENCY 'DVP_P4-2: 574T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
END
Breaker AC 104.31 % 671.0 C 699.94 13.04
DVP 6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1
DVP_P4-2: 574T581_SRT-S
CONTINGENCY 'DVP_P4-2: 574T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
END
Breaker AC 104.28 % 671.0 C 699.73 13.04
DVP 6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1
DVP_P4-2: H1T574_SRT-S
CONTINGENCY 'DVP_P4-2: H1T574_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
END
Breaker AC 104.24 % 671.0 C 699.42 13.03
DVP 6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1
DVP_P4-2: H1T574_SRT-S
CONTINGENCY 'DVP_P4-2: H1T574_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
END
Breaker AC 104.2 % 671.0 C 699.18 13.03
DVP 3WAN 89-3WHITEMARSH 115.0 kV Ckt 1 line
313284 to 313828 ckt 1
DVP_P7-1: LN 2016-85_SRT-A-2
CONTINGENCY 'DVP_P7-1: LN 2016-85_SRT-A-2'
 OPEN BRANCH FROM BUS 313053 TO BUS 314189 CKT 1   /*6PAPERMILL   230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1   /*3HARMONY     115.0 - 6HARMONY     230.0
 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1   /*6HARMONY     230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314184 TO BUS 314188 CKT 1   /*3SHACKLE     115.0 - 3WEST PT     115.0
 OPEN BRANCH FROM BUS 314184 TO BUS 316275 CKT 1   /*3SHACKLE     115.0 - AD1-041 TAP  115.0
 OPEN BRANCH FROM BUS 314188 TO BUS 314387 CKT 1   /*3WEST PT     115.0 - 3LANEXA      115.0
 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1   /*6PAPERMIL TP 230.0 - 6CORRCTN     230.0
 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1   /*6CORRCTN     230.0 - 6LANEXA      230.0
 OPEN BUS 313053                                   /*6PAPERMILL   230.0
 OPEN BUS 313846                                   /*6HARMONY_1   230.0
 OPEN BUS 314176                                   /*6HARMONY     230.0
 OPEN BUS 314184                                   /*3SHACKLE     115.0
 OPEN BUS 314188                                   /*3WEST PT     115.0
 OPEN BUS 314189                                   /*6PAPERMIL TP 230.0
 OPEN BUS 314375                                   /*6CORRCTN     230.0
END
Tower AC 114.88 % 208.0 C 238.95 15.44
DVP 3WHITEMARSH-3HAYES89 115.0 kV Ckt 1 line
313828 to 314177 ckt 1
DVP_P7-1: LN 2016-85_SRT-A-2
CONTINGENCY 'DVP_P7-1: LN 2016-85_SRT-A-2'
 OPEN BRANCH FROM BUS 313053 TO BUS 314189 CKT 1   /*6PAPERMILL   230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1   /*3HARMONY     115.0 - 6HARMONY     230.0
 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1   /*6HARMONY     230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314184 TO BUS 314188 CKT 1   /*3SHACKLE     115.0 - 3WEST PT     115.0
 OPEN BRANCH FROM BUS 314184 TO BUS 316275 CKT 1   /*3SHACKLE     115.0 - AD1-041 TAP  115.0
 OPEN BRANCH FROM BUS 314188 TO BUS 314387 CKT 1   /*3WEST PT     115.0 - 3LANEXA      115.0
 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1   /*6PAPERMIL TP 230.0 - 6CORRCTN     230.0
 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1   /*6CORRCTN     230.0 - 6LANEXA      230.0
 OPEN BUS 313053                                   /*6PAPERMILL   230.0
 OPEN BUS 313846                                   /*6HARMONY_1   230.0
 OPEN BUS 314176                                   /*6HARMONY     230.0
 OPEN BUS 314184                                   /*3SHACKLE     115.0
 OPEN BUS 314188                                   /*3WEST PT     115.0
 OPEN BUS 314189                                   /*6PAPERMIL TP 230.0
 OPEN BUS 314375                                   /*6CORRCTN     230.0
END
Tower AC 111.93 % 208.0 C 232.81 15.43
DVP 8OX-8CLIFTON 500.0 kV Ckt 1 line
314919 to 314904 ckt 1
DVP_P7-1: LN 2101-569_SRT-S
CONTINGENCY 'DVP_P7-1: LN 2101-569_SRT-S'
 OPEN BRANCH FROM BUS 313712 TO BUS 313716 CKT 1                /*6VINTHIL TP  230.0 - 6VINTHIL DP  230.0
 OPEN BRANCH FROM BUS 313712 TO BUS 314119 CKT 1                /*6VINTHIL TP  230.0 - 6NOKESVL     230.0
 OPEN BRANCH FROM BUS 313712 TO BUS 314125 CKT 1                /*6VINTHIL TP  230.0 - 6VINTHIL     230.0
 OPEN BRANCH FROM BUS 314119 TO BUS 314130 CKT 1                /*6NOKESVL     230.0 - 6BRISTER     230.0
 OPEN BRANCH FROM BUS 314913 TO BUS 314916 CKT 1                /*8LOUDOUN     500.0 - 8MORRSVL     500.0
 OPEN BUS 313712                                                /*6VINTHIL TP  230.0
 OPEN BUS 313716                                                /*6VINTHIL DP  230.0
 OPEN BUS 314119                                                /*6NOKESVL     230.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
Tower AC 105.67 % 3144.0 C 3322.12 7.88

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
316399 to 314181 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-A
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-A'
 OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1   /*3OCRAN       115.0 - 3LANCAST     115.0
 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1   /*3OCRAN       115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1   /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1   /*3LANCAST     115.0 - 3LANCA_1     115.0
 OPEN BRANCH FROM BUS 962970 TO BUS 314178 CKT 1   /*AG1-146 TP   115.0 - 3LANCAST     115.0
 OPEN BUS 313813                                   /*3OCRAN       115.0
 OPEN BUS 314178                                   /*3LANCAST     115.0
 OPEN BUS 314191                                   /*3WHIT STONE  115.0
 OPEN BUS 314400                                   /*3LANCA_1     115.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 147.57 %
Rating: 203.98 MVA
Rating Type: B
MVA to Mitigate: 301.01 MVA
MW Contribution: 37.19 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 80/20 32.67 MW 32.67 MW
943741 AF1-042 C 80/20 17.09 MW 17.09 MW
961951 AG1-038 C 80/20 18.89 MW 18.89 MW
966661 AG1-536 C 80/20 31.99 MW 31.99 MW
962861 AG1-135 C 80/20 35.99 MW 35.99 MW
962971 AG1-146 C 80/20 17.99 MW 17.99 MW
962981 AG1-147 C 80/20 41.98 MW 41.98 MW
316404 AE1-155 C 80/20 12.57 MW 12.57 MW
958261 AF2-120 C 80/20 37.19 MW 37.19 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
962970 to 314178 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 144.85 %
Rating: 203.98 MVA
Rating Type: B
MVA to Mitigate: 295.47 MVA
MW Contribution: 37.19 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 80/20 32.67 MW 32.67 MW
943741 AF1-042 C 80/20 17.09 MW 17.09 MW
961951 AG1-038 C 80/20 18.89 MW 18.89 MW
966661 AG1-536 C 80/20 31.99 MW 31.99 MW
962861 AG1-135 C 80/20 35.99 MW 35.99 MW
962971 AG1-146 C 80/20 17.99 MW 17.99 MW
962981 AG1-147 C 80/20 41.98 MW 41.98 MW
316404 AE1-155 C 80/20 12.57 MW 12.57 MW
958261 AF2-120 C 80/20 37.19 MW 37.19 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
314934 to 314916 ckt 1
Contingency Name:
DVP_P1-2: LN 552_SRT-S
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 122.77 %
Rating: 3220.44 MVA
Rating Type: B
MVA to Mitigate: 3953.87 MVA
MW Contribution: 6.41 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961671 AG1-007 C Adder 0.93 MW 0.79 MW
961791 AG1-021 C Adder 1.7 MW 1.45 MW
961941 AG1-037 C Adder 0.53 MW 0.45 MW
962331 AG1-082 C Adder 2.11 MW 1.79 MW
963041 AG1-153 C Adder 5.77 MW 4.9 MW
963171 AG1-166 C Adder 0.95 MW 0.8 MW
963181 AG1-167 C Adder 0.71 MW 0.6 MW
963191 AG1-168 C Adder 0.71 MW 0.6 MW
964791 AG1-342 C Adder 3.32 MW 2.83 MW
966801 AG1-551 C Adder 2.15 MW 1.82 MW
966811 AG1-552 C Adder 2.1 MW 1.78 MW
965291 AG1-394 C Adder 0.9 MW 0.76 MW
966621 AG1-532 C Adder 1.44 MW 1.22 MW
313853 3PONTONDP Adder 0.63 MW 0.54 MW
934521 AD1-076 C Adder 12.97 MW 11.02 MW
944011 AF1-069 C 80/20 13.52 MW 13.52 MW
959311 AF2-222 C Adder 15.87 MW 13.49 MW
960081 AF2-299 C Adder 1.92 MW 1.63 MW
938371 AE1-056 C Adder 6.1 MW 5.18 MW
939181 AE1-148 C Adder 8.68 MW 7.38 MW
941031 AE2-094 C 80/20 41.39 MW 41.39 MW
946281 AF1-292 C Adder 1.58 MW 1.35 MW
946301 AF1-294 C Adder 3.5 MW 2.98 MW
957481 AF2-042 C Adder 53.68 MW 45.62 MW
957521 AF2-046 C Adder 14.87 MW 12.64 MW
957861 AF2-080 C Adder 7.65 MW 6.5 MW
958211 AF2-115 C Adder 2.13 MW 1.81 MW
938771 AE1-103 C Adder 3.16 MW 2.69 MW
314236 6NRTHEST 80/20 0.2 MW 0.2 MW
314309 6IRON208 80/20 0.48 MW 0.48 MW
314507 3THOMPSN Adder 2.23 MW 1.9 MW
315060 1CHESTF5 Adder 69.01 MW 58.66 MW
315065 1CHESTF6 80/20 21.77 MW 21.77 MW
315073 1STONECA 80/20 7.61 MW 7.61 MW
315076 1HOPPOLC 80/20 1.69 MW 1.69 MW
315077 1HOPHCF1 80/20 2.68 MW 2.68 MW
315078 1HOPHCF2 80/20 2.68 MW 2.68 MW
315079 1HOPHCF3 80/20 2.68 MW 2.68 MW
315080 1HOPHCF4 80/20 4.07 MW 4.07 MW
315083 1SPRUNCA 80/20 10.22 MW 10.22 MW
315084 1SPRUNCB 80/20 10.22 MW 10.22 MW
315092 1YORKTN3 Adder 144.43 MW 122.76 MW
936591 AD2-074 C Adder 5.73 MW 4.87 MW
942341 AE2-247 C Adder 1.64 MW 1.4 MW
943461 AF1-017 C Adder 1.49 MW 1.26 MW
943741 AF1-042 C Adder 3.0 MW 2.55 MW
961951 AG1-038 C Adder 3.31 MW 2.82 MW
966661 AG1-536 C Adder 5.51 MW 4.68 MW
966871 AG1-558 C Adder 2.51 MW 2.13 MW
966881 AG1-559 C Adder 2.4 MW 2.04 MW
315099 1CHESPKB 80/20 0.8 MW 0.8 MW
315108 1ELIZAR1 80/20 3.53 MW 3.53 MW
315109 1ELIZAR2 80/20 3.47 MW 3.47 MW
315110 1ELIZAR3 80/20 3.57 MW 3.57 MW
315225 1N ANNA1 80/20 55.33 MW 55.33 MW
315226 1N ANNA2 80/20 55.35 MW 55.35 MW
315233 1SURRY 2 80/20 27.3 MW 27.3 MW
315260 1GOSPORTA Adder 2.36 MW 2.0 MW
315261 1GOSPORTB Adder 3.01 MW 2.56 MW
315262 1GOSPORTC Adder 2.55 MW 2.17 MW
957411 AF2-035 C Adder 8.65 MW 7.35 MW
957601 AF2-054 C Adder 2.21 MW 1.88 MW
962861 AG1-135 C Adder 6.23 MW 5.29 MW
962971 AG1-146 C Adder 3.19 MW 2.71 MW
962981 AG1-147 C Adder 7.44 MW 6.32 MW
963051 AG1-154 C Adder 3.44 MW 2.92 MW
963611 AG1-210 C Adder 0.67 MW 0.57 MW
964211 AG1-282 C Adder 2.03 MW 1.73 MW
942001 AE2-212 C 80/20 2.4 MW 2.4 MW
957871 AF2-081 C Adder 10.98 MW 9.34 MW
958161 AF2-110 C Adder 1.5 MW 1.28 MW
926071 AC1-086 C Adder 21.52 MW 18.29 MW
927021 AC1-189 C Adder 8.42 MW 7.16 MW
936261 AD2-033 C Adder 12.42 MW 10.55 MW
933291 AC2-141 C 80/20 33.68 MW 33.68 MW
934621 AD1-088 C Adder 12.5 MW 10.63 MW
939411 AE1-173 C 80/20 97.69 MW 97.69 MW
927041 AC1-191 C Adder 10.08 MW 8.57 MW
933981 AD1-022 C Adder 9.25 MW 7.87 MW
961681 AG1-008 C Adder 14.87 MW 12.64 MW
962571 AG1-106 C Adder 2.78 MW 2.37 MW
316164 AC1-076_C 80/20 0.99 MW 0.99 MW
316169 AC1-164 GEN Adder 42.79 MW 36.37 MW
316192 AB2-158 C 80/20 2.12 MW 2.12 MW
316233 AE1-074 C 80/20 2.82 MW 2.82 MW
316240 AF1-291 C 80/20 2.4 MW 2.4 MW
316274 AC1-208 C Adder 9.1 MW 7.73 MW
316294 AC1-161 C 80/20 5.48 MW 5.48 MW
316336 AC2-165 C Adder 10.13 MW 8.61 MW
316044 AC1-158 C1 80/20 14.96 MW 14.96 MW
316045 AC1-158 C2 80/20 14.96 MW 14.96 MW
316375 AC2-012 C 80/20 1.49 MW 1.49 MW
316311 AC2-079 C Adder 6.32 MW 5.37 MW
316349 AD2-085 C Adder 3.79 MW 3.22 MW
961611 AG1-000B C Adder 17.56 MW 14.93 MW
941591 AE2-156 C 80/20 19.8 MW 19.8 MW
944581 AF1-123 C 80/20 50.24 MW 50.24 MW
944591 AF1-124 C 80/20 50.42 MW 50.42 MW
944601 AF1-125 C 80/20 49.47 MW 49.47 MW
944631 AF1-128 C Adder 43.18 MW 36.7 MW
958261 AF2-120 C Adder 6.41 MW 5.45 MW
962491 AG1-098 C Adder 11.2 MW 9.52 MW
962561 AG1-105 C Adder 8.36 MW 7.11 MW
964241 AG1-285 C Adder 11.99 MW 10.19 MW
965281 AG1-393 C 80/20 2.39 MW 2.39 MW
313764 3SOCKMAN Adder 0.73 MW 0.62 MW
934321 AD1-056 C Adder 6.26 MW 5.32 MW
934331 AD1-057 C Adder 3.49 MW 2.97 MW
934501 AD1-074 C Adder 35.71 MW 30.35 MW
934511 AD1-075 C Adder 8.93 MW 7.59 MW
935161 AD1-151 C Adder 17.8 MW 15.13 MW
938531 AE1-072 C Adder 19.3 MW 16.41 MW
939191 AE1-149 C 80/20 11.91 MW 11.91 MW
939261 AE1-157 C Adder 13.78 MW 11.71 MW
940431 AE2-027 C 80/20 14.32 MW 14.32 MW
940481 AE2-033 C Adder 17.09 MW 14.53 MW
940541 AE2-040 C Adder 3.04 MW 2.58 MW
940551 AE2-041 C Adder 7.46 MW 6.34 MW
940641 AE2-051 C 80/20 18.5 MW 18.5 MW
941101 AE2-104 C Adder 3.68 MW 3.13 MW
942461 AE2-259 C Adder 9.36 MW 7.96 MW
943471 AF1-018 C Adder 7.46 MW 6.34 MW
944641 AF1-129 C 80/20 113.54 MW 113.54 MW
315085 1SPRUNCC 80/20 0.18 MW 0.18 MW
315086 1SPRUNCD 80/20 0.18 MW 0.18 MW
316303 AF2-085 80/20 4.37 MW 4.37 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 27.62 MW 27.62 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 22.07 MW 22.07 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 94.18 MW 94.18 MW
NY PJM->LTFIMP_NY CLTF 2.81 MW 2.81 MW
LGEE LTFEXP_LGEE->PJM CLTF 1.22 MW 1.22 MW
WEC LTFEXP_WEC->PJM CLTF 0.59 MW 0.59 MW
CPLE LTFEXP_CPLE->PJM CLTF 11.09 MW 11.09 MW
TVA LTFEXP_TVA->PJM CLTF 6.14 MW 6.14 MW
MEC LTFEXP_MEC->PJM CLTF 3.74 MW 3.74 MW
LAGN LTFEXP_LAGN->PJM CLTF 7.67 MW 7.67 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.24 MW 0.24 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 5.29 MW 5.29 MW

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
314934 to 314916 ckt 1
Contingency Name:
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 122.25 %
Rating: 3220.44 MVA
Rating Type: B
MVA to Mitigate: 3936.83 MVA
MW Contribution: 6.31 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961671 AG1-007 C Adder 0.92 MW 0.78 MW
961791 AG1-021 C Adder 1.67 MW 1.42 MW
961941 AG1-037 C Adder 0.52 MW 0.44 MW
962331 AG1-082 C Adder 2.07 MW 1.76 MW
963041 AG1-153 C Adder 5.68 MW 4.83 MW
963171 AG1-166 C Adder 0.93 MW 0.79 MW
963181 AG1-167 C Adder 0.7 MW 0.59 MW
963191 AG1-168 C Adder 0.7 MW 0.59 MW
964791 AG1-342 C Adder 3.27 MW 2.78 MW
966801 AG1-551 C Adder 2.11 MW 1.8 MW
966811 AG1-552 C Adder 2.07 MW 1.76 MW
965291 AG1-394 C Adder 0.88 MW 0.75 MW
966621 AG1-532 C Adder 1.41 MW 1.2 MW
313853 3PONTONDP Adder 0.62 MW 0.53 MW
315131 1EDGECMA Adder 14.99 MW 12.74 MW
934521 AD1-076 C Adder 12.77 MW 10.85 MW
944011 AF1-069 C 80/20 13.32 MW 13.32 MW
959311 AF2-222 C Adder 15.61 MW 13.27 MW
960081 AF2-299 C Adder 1.88 MW 1.6 MW
938371 AE1-056 C Adder 5.99 MW 5.09 MW
939181 AE1-148 C Adder 8.54 MW 7.26 MW
941031 AE2-094 C 80/20 40.77 MW 40.77 MW
946281 AF1-292 C Adder 1.56 MW 1.33 MW
946301 AF1-294 C Adder 3.44 MW 2.92 MW
957481 AF2-042 C Adder 52.84 MW 44.91 MW
957521 AF2-046 C Adder 14.64 MW 12.45 MW
957861 AF2-080 C Adder 7.53 MW 6.4 MW
958211 AF2-115 C Adder 2.09 MW 1.78 MW
938771 AE1-103 C Adder 3.11 MW 2.65 MW
314236 6NRTHEST 80/20 0.2 MW 0.2 MW
314309 6IRON208 80/20 0.48 MW 0.48 MW
314507 3THOMPSN Adder 2.2 MW 1.87 MW
315060 1CHESTF5 Adder 67.92 MW 57.73 MW
315065 1CHESTF6 80/20 21.43 MW 21.43 MW
315073 1STONECA 80/20 7.49 MW 7.49 MW
315076 1HOPPOLC 80/20 1.66 MW 1.66 MW
315077 1HOPHCF1 80/20 2.64 MW 2.64 MW
315078 1HOPHCF2 80/20 2.64 MW 2.64 MW
315079 1HOPHCF3 80/20 2.64 MW 2.64 MW
315080 1HOPHCF4 80/20 4.0 MW 4.0 MW
315083 1SPRUNCA 80/20 10.06 MW 10.06 MW
315084 1SPRUNCB 80/20 10.06 MW 10.06 MW
315092 1YORKTN3 Adder 142.16 MW 120.84 MW
936591 AD2-074 C Adder 5.64 MW 4.79 MW
942341 AE2-247 C Adder 1.62 MW 1.38 MW
943461 AF1-017 C Adder 1.46 MW 1.24 MW
943741 AF1-042 C Adder 2.95 MW 2.51 MW
961951 AG1-038 C Adder 3.26 MW 2.77 MW
966661 AG1-536 C Adder 5.42 MW 4.61 MW
966871 AG1-558 C Adder 2.47 MW 2.1 MW
966881 AG1-559 C Adder 2.36 MW 2.0 MW
315099 1CHESPKB 80/20 0.78 MW 0.78 MW
315108 1ELIZAR1 80/20 3.47 MW 3.47 MW
315109 1ELIZAR2 80/20 3.41 MW 3.41 MW
315110 1ELIZAR3 80/20 3.52 MW 3.52 MW
315225 1N ANNA1 80/20 54.68 MW 54.68 MW
315226 1N ANNA2 80/20 54.7 MW 54.7 MW
315233 1SURRY 2 80/20 26.88 MW 26.88 MW
315260 1GOSPORTA Adder 2.32 MW 1.97 MW
315261 1GOSPORTB Adder 2.96 MW 2.52 MW
315262 1GOSPORTC Adder 2.51 MW 2.14 MW
957411 AF2-035 C Adder 8.51 MW 7.23 MW
957601 AF2-054 C Adder 2.18 MW 1.85 MW
962861 AG1-135 C Adder 6.13 MW 5.21 MW
962971 AG1-146 C Adder 3.14 MW 2.67 MW
962981 AG1-147 C Adder 7.32 MW 6.22 MW
963051 AG1-154 C Adder 3.38 MW 2.87 MW
963611 AG1-210 C Adder 0.66 MW 0.56 MW
964211 AG1-282 C Adder 2.0 MW 1.7 MW
942001 AE2-212 C 80/20 2.36 MW 2.36 MW
957871 AF2-081 C Adder 10.82 MW 9.19 MW
958161 AF2-110 C Adder 1.48 MW 1.26 MW
926071 AC1-086 C Adder 21.18 MW 18.01 MW
927021 AC1-189 C Adder 8.29 MW 7.05 MW
936261 AD2-033 C Adder 12.21 MW 10.38 MW
933291 AC2-141 C 80/20 33.16 MW 33.16 MW
934621 AD1-088 C Adder 12.3 MW 10.46 MW
939411 AE1-173 C 80/20 96.21 MW 96.21 MW
927041 AC1-191 C Adder 9.92 MW 8.43 MW
933981 AD1-022 C Adder 9.11 MW 7.74 MW
961681 AG1-008 C Adder 14.64 MW 12.45 MW
962571 AG1-106 C Adder 2.74 MW 2.33 MW
316169 AC1-164 GEN Adder 42.1 MW 35.79 MW
316192 AB2-158 C 80/20 2.05 MW 2.05 MW
316233 AE1-074 C 80/20 2.78 MW 2.78 MW
316240 AF1-291 C 80/20 2.36 MW 2.36 MW
316263 AC1-034 C Adder 6.41 MW 5.45 MW
316274 AC1-208 C Adder 8.95 MW 7.61 MW
316294 AC1-161 C 80/20 5.4 MW 5.4 MW
316336 AC2-165 C Adder 9.95 MW 8.46 MW
316044 AC1-158 C1 80/20 14.85 MW 14.85 MW
316045 AC1-158 C2 80/20 14.85 MW 14.85 MW
316375 AC2-012 C 80/20 1.47 MW 1.47 MW
316311 AC2-079 C Adder 6.22 MW 5.29 MW
316349 AD2-085 C Adder 3.73 MW 3.17 MW
961611 AG1-000B C Adder 17.29 MW 14.7 MW
941591 AE2-156 C 80/20 19.5 MW 19.5 MW
944581 AF1-123 C 80/20 49.47 MW 49.47 MW
944591 AF1-124 C 80/20 49.64 MW 49.64 MW
944601 AF1-125 C 80/20 48.7 MW 48.7 MW
944631 AF1-128 C Adder 42.5 MW 36.12 MW
958261 AF2-120 C Adder 6.31 MW 5.36 MW
962491 AG1-098 C Adder 11.02 MW 9.37 MW
962561 AG1-105 C Adder 8.23 MW 7.0 MW
964241 AG1-285 C Adder 11.79 MW 10.02 MW
965281 AG1-393 C 80/20 2.35 MW 2.35 MW
313764 3SOCKMAN Adder 0.72 MW 0.61 MW
934321 AD1-056 C Adder 6.16 MW 5.23 MW
934331 AD1-057 C Adder 3.44 MW 2.92 MW
934501 AD1-074 C Adder 35.16 MW 29.88 MW
934511 AD1-075 C Adder 8.79 MW 7.47 MW
935161 AD1-151 C Adder 17.52 MW 14.89 MW
938531 AE1-072 C Adder 19.0 MW 16.15 MW
939191 AE1-149 C 80/20 11.72 MW 11.72 MW
939261 AE1-157 C Adder 13.55 MW 11.52 MW
940431 AE2-027 C 80/20 14.1 MW 14.1 MW
940481 AE2-033 C Adder 16.83 MW 14.3 MW
940541 AE2-040 C Adder 2.99 MW 2.54 MW
940551 AE2-041 C Adder 7.34 MW 6.24 MW
940641 AE2-051 C 80/20 18.22 MW 18.22 MW
941101 AE2-104 C Adder 3.62 MW 3.08 MW
942461 AE2-259 C Adder 9.19 MW 7.81 MW
943471 AF1-018 C Adder 7.34 MW 6.24 MW
944641 AF1-129 C 80/20 111.76 MW 111.76 MW
315085 1SPRUNCC 80/20 0.18 MW 0.18 MW
315086 1SPRUNCD 80/20 0.18 MW 0.18 MW
316303 AF2-085 80/20 4.3 MW 4.3 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 27.01 MW 27.01 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 21.65 MW 21.65 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 92.62 MW 92.62 MW
NY PJM->LTFIMP_NY CLTF 2.75 MW 2.75 MW
LGEE LTFEXP_LGEE->PJM CLTF 1.2 MW 1.2 MW
WEC LTFEXP_WEC->PJM CLTF 0.58 MW 0.58 MW
CPLE LTFEXP_CPLE->PJM CLTF 10.91 MW 10.91 MW
TVA LTFEXP_TVA->PJM CLTF 6.02 MW 6.02 MW
MEC LTFEXP_MEC->PJM CLTF 3.67 MW 3.67 MW
LAGN LTFEXP_LAGN->PJM CLTF 7.54 MW 7.54 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.23 MW 0.23 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 5.2 MW 5.2 MW

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1021_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
316399 to 314181 ckt 1
Contingency Name:
DVP_P1-2: LN 1021_SRT-A
CONTINGENCY 'DVP_P1-2: LN 1021_SRT-A'
 OPEN BRANCH FROM BUS 313842 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_1 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313843 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_2 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 313900 CKT Z1   /*3RAPPAHNCK   115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 1    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 2    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 314174 CKT 1    /*3GREYSPT     115.0 - 3HARMONY     115.0
 OPEN BUS 313842                                    /*3RAPPAHNCK_1 115.0
 OPEN BUS 313843                                    /*3RAPPAHNCK_2 115.0
 OPEN BUS 313886                                    /*3GREYSPT     115.0
 OPEN BUS 313900                                    /*3RAPP TR     115.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 118.66 %
Rating: 203.98 MVA
Rating Type: B
MVA to Mitigate: 242.05 MVA
MW Contribution: 37.19 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 80/20 32.67 MW 32.67 MW
943741 AF1-042 C 80/20 17.09 MW 17.09 MW
961951 AG1-038 C 80/20 18.89 MW 18.89 MW
966661 AG1-536 C 80/20 31.99 MW 31.99 MW
962861 AG1-135 C 80/20 35.99 MW 35.99 MW
962971 AG1-146 C 80/20 17.99 MW 17.99 MW
962981 AG1-147 C 80/20 41.98 MW 41.98 MW
316404 AE1-155 C 80/20 12.57 MW 12.57 MW
958261 AF2-120 C 80/20 37.19 MW 37.19 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
314918 to 314934 ckt 1
Contingency Name:
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 117.57 %
Rating: 3220.44 MVA
Rating Type: B
MVA to Mitigate: 3786.34 MVA
MW Contribution: 6.55 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961671 AG1-007 C Adder 0.95 MW 0.81 MW
961791 AG1-021 C Adder 1.72 MW 1.46 MW
961941 AG1-037 C Adder 0.54 MW 0.46 MW
962331 AG1-082 C Adder 2.15 MW 1.83 MW
963041 AG1-153 C Adder 5.89 MW 5.0 MW
963171 AG1-166 C Adder 0.96 MW 0.81 MW
963181 AG1-167 C Adder 0.72 MW 0.61 MW
963191 AG1-168 C Adder 0.72 MW 0.61 MW
964791 AG1-342 C Adder 3.38 MW 2.88 MW
966801 AG1-551 C Adder 2.19 MW 1.86 MW
966811 AG1-552 C Adder 2.14 MW 1.82 MW
965291 AG1-394 C Adder 0.92 MW 0.78 MW
966621 AG1-532 C Adder 1.46 MW 1.25 MW
313853 3PONTONDP Adder 0.64 MW 0.54 MW
315131 1EDGECMA Adder 15.56 MW 13.23 MW
934521 AD1-076 C Adder 13.24 MW 11.26 MW
944011 AF1-069 C 80/20 13.81 MW 13.81 MW
959311 AF2-222 C Adder 16.08 MW 13.66 MW
960081 AF2-299 C Adder 1.95 MW 1.66 MW
938371 AE1-056 C Adder 6.16 MW 5.23 MW
939181 AE1-148 C Adder 8.84 MW 7.51 MW
941031 AE2-094 C 80/20 42.26 MW 42.26 MW
946281 AF1-292 C Adder 1.62 MW 1.38 MW
946301 AF1-294 C Adder 3.54 MW 3.01 MW
957481 AF2-042 C Adder 54.68 MW 46.48 MW
957521 AF2-046 C Adder 15.19 MW 12.91 MW
957861 AF2-080 C Adder 7.82 MW 6.64 MW
958211 AF2-115 C Adder 2.15 MW 1.83 MW
938771 AE1-103 C Adder 3.23 MW 2.74 MW
314236 6NRTHEST 80/20 0.2 MW 0.2 MW
314309 6IRON208 80/20 0.49 MW 0.49 MW
314507 3THOMPSN Adder 2.28 MW 1.94 MW
315060 1CHESTF5 Adder 70.44 MW 59.87 MW
315065 1CHESTF6 80/20 22.22 MW 22.22 MW
315073 1STONECA 80/20 7.77 MW 7.77 MW
315076 1HOPPOLC 80/20 1.72 MW 1.72 MW
315077 1HOPHCF1 80/20 2.73 MW 2.73 MW
315078 1HOPHCF2 80/20 2.73 MW 2.73 MW
315079 1HOPHCF3 80/20 2.73 MW 2.73 MW
315080 1HOPHCF4 80/20 4.15 MW 4.15 MW
315083 1SPRUNCA 80/20 10.43 MW 10.43 MW
315084 1SPRUNCB 80/20 10.43 MW 10.43 MW
315092 1YORKTN3 Adder 147.47 MW 125.35 MW
934861 AD1-115 C Adder -3.06 MW -2.6 MW
936591 AD2-074 C Adder 5.86 MW 4.98 MW
942341 AE2-247 C Adder 1.68 MW 1.43 MW
943461 AF1-017 C Adder 1.52 MW 1.29 MW
943741 AF1-042 C Adder 3.06 MW 2.6 MW
961951 AG1-038 C Adder 3.39 MW 2.88 MW
966661 AG1-536 C Adder 5.64 MW 4.79 MW
966871 AG1-558 C Adder 2.56 MW 2.18 MW
966881 AG1-559 C Adder 2.45 MW 2.08 MW
315099 1CHESPKB 80/20 0.81 MW 0.81 MW
315108 1ELIZAR1 80/20 3.6 MW 3.6 MW
315109 1ELIZAR2 80/20 3.54 MW 3.54 MW
315110 1ELIZAR3 80/20 3.65 MW 3.65 MW
315225 1N ANNA1 80/20 56.71 MW 56.71 MW
315226 1N ANNA2 80/20 56.73 MW 56.73 MW
315233 1SURRY 2 80/20 27.88 MW 27.88 MW
315260 1GOSPORTA Adder 2.4 MW 2.04 MW
315261 1GOSPORTB Adder 3.07 MW 2.61 MW
315262 1GOSPORTC Adder 2.61 MW 2.22 MW
957411 AF2-035 C Adder 8.85 MW 7.52 MW
957601 AF2-054 C Adder 2.26 MW 1.92 MW
962861 AG1-135 C Adder 6.37 MW 5.41 MW
962971 AG1-146 C Adder 3.26 MW 2.77 MW
962981 AG1-147 C Adder 7.6 MW 6.46 MW
963051 AG1-154 C Adder 3.52 MW 2.99 MW
963611 AG1-210 C Adder 0.68 MW 0.58 MW
964211 AG1-282 C Adder 2.08 MW 1.77 MW
942001 AE2-212 C 80/20 2.45 MW 2.45 MW
957871 AF2-081 C Adder 11.22 MW 9.53 MW
958161 AF2-110 C Adder 1.53 MW 1.3 MW
926071 AC1-086 C Adder 21.97 MW 18.68 MW
927021 AC1-189 C Adder 8.6 MW 7.31 MW
936261 AD2-033 C Adder 12.59 MW 10.7 MW
933291 AC2-141 C 80/20 34.38 MW 34.38 MW
934621 AD1-088 C Adder 12.72 MW 10.81 MW
939411 AE1-173 C 80/20 99.75 MW 99.75 MW
927041 AC1-191 C Adder 10.29 MW 8.75 MW
933981 AD1-022 C Adder 9.45 MW 8.03 MW
961681 AG1-008 C Adder 15.19 MW 12.91 MW
962571 AG1-106 C Adder 2.84 MW 2.42 MW
316169 AC1-164 GEN Adder 43.68 MW 37.13 MW
316233 AE1-074 C 80/20 2.88 MW 2.88 MW
316240 AF1-291 C 80/20 2.44 MW 2.44 MW
316254 AC1-120 C Adder -6.38 MW -5.42 MW
316257 AC1-043 C Adder -6.12 MW -5.2 MW
316263 AC1-034 C Adder 6.66 MW 5.66 MW
316274 AC1-208 C Adder 9.29 MW 7.89 MW
316294 AC1-161 C 80/20 5.6 MW 5.6 MW
316336 AC2-165 C Adder 10.2 MW 8.67 MW
316375 AC2-012 C 80/20 1.52 MW 1.52 MW
316311 AC2-079 C Adder 6.45 MW 5.48 MW
316349 AD2-085 C Adder 3.87 MW 3.29 MW
961611 AG1-000B C Adder 17.93 MW 15.24 MW
941591 AE2-156 C 80/20 20.22 MW 20.22 MW
944581 AF1-123 C 80/20 51.3 MW 51.3 MW
944591 AF1-124 C 80/20 51.48 MW 51.48 MW
944601 AF1-125 C 80/20 50.51 MW 50.51 MW
944631 AF1-128 C Adder 44.08 MW 37.46 MW
958261 AF2-120 C Adder 6.55 MW 5.57 MW
962491 AG1-098 C Adder 11.39 MW 9.68 MW
962561 AG1-105 C Adder 8.51 MW 7.23 MW
964241 AG1-285 C Adder 12.17 MW 10.35 MW
965281 AG1-393 C 80/20 2.44 MW 2.44 MW
313764 3SOCKMAN Adder 0.74 MW 0.63 MW
934321 AD1-056 C Adder 6.39 MW 5.43 MW
934331 AD1-057 C Adder 3.56 MW 3.03 MW
934501 AD1-074 C Adder 36.47 MW 31.0 MW
934511 AD1-075 C Adder 9.12 MW 7.75 MW
935161 AD1-151 C Adder 18.17 MW 15.44 MW
938531 AE1-072 C Adder 19.71 MW 16.75 MW
939191 AE1-149 C 80/20 12.16 MW 12.16 MW
939261 AE1-157 C Adder 14.11 MW 11.99 MW
940431 AE2-027 C 80/20 14.62 MW 14.62 MW
940481 AE2-033 C Adder 17.45 MW 14.83 MW
940541 AE2-040 C Adder 3.1 MW 2.64 MW
940551 AE2-041 C Adder 7.62 MW 6.47 MW
940641 AE2-051 C 80/20 18.89 MW 18.89 MW
941101 AE2-104 C Adder 3.76 MW 3.19 MW
942461 AE2-259 C Adder 9.42 MW 8.01 MW
943471 AF1-018 C Adder 7.62 MW 6.47 MW
944641 AF1-129 C 80/20 115.89 MW 115.89 MW
315085 1SPRUNCC 80/20 0.19 MW 0.19 MW
315086 1SPRUNCD 80/20 0.19 MW 0.19 MW
316303 AF2-085 80/20 4.45 MW 4.45 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 30.69 MW 30.69 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 23.32 MW 23.32 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 96.7 MW 96.7 MW
NY PJM->LTFIMP_NY CLTF 2.7 MW 2.7 MW
LGEE LTFEXP_LGEE->PJM CLTF 1.33 MW 1.33 MW
WEC LTFEXP_WEC->PJM CLTF 0.65 MW 0.65 MW
CPLE LTFEXP_CPLE->PJM CLTF 11.35 MW 11.35 MW
TVA LTFEXP_TVA->PJM CLTF 6.41 MW 6.41 MW
MEC LTFEXP_MEC->PJM CLTF 4.04 MW 4.04 MW
LAGN LTFEXP_LAGN->PJM CLTF 8.02 MW 8.02 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.26 MW 0.26 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 5.41 MW 5.41 MW

Details for AD2-074 TP-AG1-146 TP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
AD2-074 TP-AG1-146 TP 115.0 kV Ckt 1 line
936590 to 962970 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 116.08 %
Rating: 203.98 MVA
Rating Type: B
MVA to Mitigate: 236.78 MVA
MW Contribution: 37.19 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 80/20 32.67 MW 32.67 MW
943741 AF1-042 C 80/20 17.09 MW 17.09 MW
961951 AG1-038 C 80/20 18.89 MW 18.89 MW
966661 AG1-536 C 80/20 31.99 MW 31.99 MW
962861 AG1-135 C 80/20 35.99 MW 35.99 MW
316404 AE1-155 C 80/20 12.57 MW 12.57 MW
958261 AF2-120 C 80/20 37.19 MW 37.19 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for 3LANCAST-3OCRAN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
314178 to 313813 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 115.13 %
Rating: 219.96 MVA
Rating Type: B
MVA to Mitigate: 253.24 MVA
MW Contribution: 37.19 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 80/20 32.67 MW 32.67 MW
943741 AF1-042 C 80/20 17.09 MW 17.09 MW
961951 AG1-038 C 80/20 18.89 MW 18.89 MW
966661 AG1-536 C 80/20 31.99 MW 31.99 MW
962861 AG1-135 C 80/20 35.99 MW 35.99 MW
962971 AG1-146 C 80/20 17.99 MW 17.99 MW
962981 AG1-147 C 80/20 41.98 MW 41.98 MW
316404 AE1-155 C 80/20 12.57 MW 12.57 MW
958261 AF2-120 C 80/20 37.19 MW 37.19 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
314918 to 314934 ckt 1
Contingency Name:
DVP_P1-2: LN 552_SRT-S
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 114.74 %
Rating: 3220.44 MVA
Rating Type: B
MVA to Mitigate: 3695.07 MVA
MW Contribution: 6.42 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961671 AG1-007 C Adder 0.94 MW 0.8 MW
961791 AG1-021 C Adder 1.7 MW 1.44 MW
961941 AG1-037 C Adder 0.53 MW 0.45 MW
962331 AG1-082 C Adder 2.12 MW 1.8 MW
963041 AG1-153 C Adder 5.8 MW 4.93 MW
963171 AG1-166 C Adder 0.94 MW 0.8 MW
963181 AG1-167 C Adder 0.71 MW 0.6 MW
963191 AG1-168 C Adder 0.71 MW 0.6 MW
964791 AG1-342 C Adder 3.34 MW 2.83 MW
966801 AG1-551 C Adder 2.16 MW 1.83 MW
966811 AG1-552 C Adder 2.11 MW 1.79 MW
965291 AG1-394 C Adder 0.9 MW 0.77 MW
966621 AG1-532 C Adder 1.44 MW 1.23 MW
313853 3PONTONDP Adder 0.63 MW 0.54 MW
315131 1EDGECMA Adder 15.32 MW 13.02 MW
934521 AD1-076 C Adder 13.03 MW 11.07 MW
944011 AF1-069 C 80/20 13.61 MW 13.61 MW
959311 AF2-222 C Adder 15.86 MW 13.48 MW
960081 AF2-299 C Adder 1.92 MW 1.64 MW
938371 AE1-056 C Adder 6.08 MW 5.17 MW
939181 AE1-148 C Adder 8.71 MW 7.41 MW
941031 AE2-094 C 80/20 41.66 MW 41.66 MW
946281 AF1-292 C Adder 1.59 MW 1.35 MW
946301 AF1-294 C Adder 3.49 MW 2.97 MW
957481 AF2-042 C Adder 53.92 MW 45.83 MW
957521 AF2-046 C Adder 14.94 MW 12.7 MW
957861 AF2-080 C Adder 7.69 MW 6.54 MW
958211 AF2-115 C Adder 2.12 MW 1.8 MW
938771 AE1-103 C Adder 3.17 MW 2.7 MW
314309 6IRON208 80/20 0.48 MW 0.48 MW
314507 3THOMPSN Adder 2.24 MW 1.9 MW
315060 1CHESTF5 Adder 69.07 MW 58.71 MW
315065 1CHESTF6 80/20 21.82 MW 21.82 MW
315073 1STONECA Adder 7.62 MW 6.48 MW
315083 1SPRUNCA 80/20 10.24 MW 10.24 MW
315084 1SPRUNCB 80/20 10.24 MW 10.24 MW
315092 1YORKTN3 Adder 144.72 MW 123.01 MW
936591 AD2-074 C Adder 5.74 MW 4.88 MW
942341 AE2-247 C Adder 1.65 MW 1.4 MW
943461 AF1-017 C Adder 1.49 MW 1.27 MW
943741 AF1-042 C Adder 3.0 MW 2.55 MW
961951 AG1-038 C Adder 3.32 MW 2.82 MW
966661 AG1-536 C Adder 5.52 MW 4.69 MW
966871 AG1-558 C Adder 2.51 MW 2.13 MW
966881 AG1-559 C Adder 2.38 MW 2.03 MW
315098 1CHESPKA 80/20 0.48 MW 0.48 MW
315099 1CHESPKB 80/20 0.8 MW 0.8 MW
315108 1ELIZAR1 80/20 3.54 MW 3.54 MW
315109 1ELIZAR2 80/20 3.48 MW 3.48 MW
315110 1ELIZAR3 80/20 3.58 MW 3.58 MW
315225 1N ANNA1 80/20 56.45 MW 56.45 MW
315226 1N ANNA2 80/20 56.47 MW 56.47 MW
315233 1SURRY 2 80/20 27.37 MW 27.37 MW
315260 1GOSPORTA Adder 2.36 MW 2.01 MW
315261 1GOSPORTB 80/20 3.02 MW 3.02 MW
315262 1GOSPORTC 80/20 2.56 MW 2.56 MW
957411 AF2-035 C Adder 8.61 MW 7.32 MW
957601 AF2-054 C Adder 2.22 MW 1.88 MW
962861 AG1-135 C Adder 6.23 MW 5.3 MW
962971 AG1-146 C Adder 3.19 MW 2.71 MW
962981 AG1-147 C Adder 7.45 MW 6.33 MW
963051 AG1-154 C Adder 3.41 MW 2.9 MW
963611 AG1-210 C Adder 0.67 MW 0.57 MW
964211 AG1-282 C Adder 2.04 MW 1.73 MW
942001 AE2-212 C 80/20 2.4 MW 2.4 MW
957871 AF2-081 C Adder 11.02 MW 9.37 MW
958161 AF2-110 C Adder 1.51 MW 1.28 MW
926071 AC1-086 C Adder 21.62 MW 18.38 MW
927021 AC1-189 C Adder 8.47 MW 7.2 MW
936261 AD2-033 C Adder 12.42 MW 10.55 MW
933291 AC2-141 C 80/20 33.8 MW 33.8 MW
934621 AD1-088 C Adder 12.54 MW 10.66 MW
939411 AE1-173 C 80/20 98.23 MW 98.23 MW
927041 AC1-191 C Adder 10.07 MW 8.56 MW
933981 AD1-022 C Adder 9.3 MW 7.9 MW
961681 AG1-008 C Adder 14.94 MW 12.7 MW
962571 AG1-106 C Adder 2.8 MW 2.38 MW
316036 AC1-147 C 80/20 0.41 MW 0.41 MW
316169 AC1-164 GEN Adder 42.78 MW 36.37 MW
316233 AE1-074 C 80/20 2.83 MW 2.83 MW
316240 AF1-291 C 80/20 2.4 MW 2.4 MW
316263 AC1-034 C Adder 6.55 MW 5.57 MW
316274 AC1-208 C Adder 9.14 MW 7.77 MW
316294 AC1-161 C 80/20 5.5 MW 5.5 MW
316336 AC2-165 C Adder 10.08 MW 8.56 MW
316375 AC2-012 C 80/20 1.49 MW 1.49 MW
316311 AC2-079 C Adder 6.34 MW 5.39 MW
316349 AD2-085 C Adder 3.81 MW 3.23 MW
961611 AG1-000B C Adder 17.61 MW 14.97 MW
941591 AE2-156 C 80/20 19.87 MW 19.87 MW
944581 AF1-123 C 80/20 50.42 MW 50.42 MW
944591 AF1-124 C 80/20 50.6 MW 50.6 MW
944601 AF1-125 C 80/20 49.65 MW 49.65 MW
944631 AF1-128 C Adder 43.22 MW 36.73 MW
958261 AF2-120 C Adder 6.42 MW 5.45 MW
962491 AG1-098 C Adder 11.24 MW 9.55 MW
962561 AG1-105 C Adder 8.39 MW 7.13 MW
964241 AG1-285 C Adder 12.0 MW 10.2 MW
965281 AG1-393 C 80/20 2.4 MW 2.4 MW
313764 3SOCKMAN Adder 0.73 MW 0.62 MW
934321 AD1-056 C Adder 6.29 MW 5.35 MW
934331 AD1-057 C Adder 3.51 MW 2.98 MW
934501 AD1-074 C Adder 35.87 MW 30.49 MW
934511 AD1-075 C Adder 8.97 MW 7.62 MW
935161 AD1-151 C Adder 17.84 MW 15.16 MW
938531 AE1-072 C Adder 19.37 MW 16.47 MW
939191 AE1-149 C 80/20 11.95 MW 11.95 MW
939261 AE1-157 C Adder 13.7 MW 11.64 MW
940431 AE2-027 C 80/20 14.36 MW 14.36 MW
940481 AE2-033 C Adder 17.17 MW 14.6 MW
940541 AE2-040 C Adder 3.05 MW 2.6 MW
940551 AE2-041 C Adder 7.46 MW 6.34 MW
940641 AE2-051 C 80/20 18.61 MW 18.61 MW
941101 AE2-104 C Adder 3.7 MW 3.14 MW
942461 AE2-259 C Adder 9.31 MW 7.91 MW
943471 AF1-018 C Adder 7.46 MW 6.34 MW
944641 AF1-129 C 80/20 113.77 MW 113.77 MW
315085 1SPRUNCC 80/20 0.18 MW 0.18 MW
315086 1SPRUNCD 80/20 0.18 MW 0.18 MW
316303 AF2-085 80/20 4.39 MW 4.39 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 30.2 MW 30.2 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 22.96 MW 22.96 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 95.26 MW 95.26 MW
NY PJM->LTFIMP_NY CLTF 2.66 MW 2.66 MW
LGEE LTFEXP_LGEE->PJM CLTF 1.31 MW 1.31 MW
WEC LTFEXP_WEC->PJM CLTF 0.64 MW 0.64 MW
CPLE LTFEXP_CPLE->PJM CLTF 11.19 MW 11.19 MW
TVA LTFEXP_TVA->PJM CLTF 6.32 MW 6.32 MW
MEC LTFEXP_MEC->PJM CLTF 3.97 MW 3.97 MW
LAGN LTFEXP_LAGN->PJM CLTF 7.9 MW 7.9 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.25 MW 0.25 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 5.33 MW 5.33 MW

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1
Contingency Name:
DVP_P1-2: LN 576_SRT-A
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 113.8 %
Rating: 4070.2 MVA
Rating Type: B
MVA to Mitigate: 4632.05 MVA
MW Contribution: 9.55 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961671 AG1-007 C Adder 1.45 MW 1.23 MW
961941 AG1-037 C Adder 0.82 MW 0.7 MW
962331 AG1-082 C Adder 3.29 MW 2.79 MW
963041 AG1-153 C Adder 8.3 MW 7.06 MW
966801 AG1-551 C Adder 3.36 MW 2.86 MW
966811 AG1-552 C Adder 3.22 MW 2.73 MW
965291 AG1-394 C Adder 1.4 MW 1.19 MW
966621 AG1-532 C Adder 2.18 MW 1.85 MW
934521 AD1-076 C Adder 20.42 MW 17.36 MW
944011 AF1-069 C Adder 19.36 MW 16.46 MW
960081 AF2-299 C Adder 2.9 MW 2.47 MW
939181 AE1-148 C Adder 12.96 MW 11.02 MW
941031 AE2-094 C Adder 59.26 MW 50.37 MW
946281 AF1-292 C Adder 2.4 MW 2.04 MW
957481 AF2-042 C Adder 77.81 MW 66.14 MW
957521 AF2-046 C Adder 23.18 MW 19.71 MW
957861 AF2-080 C Adder 11.93 MW 10.14 MW
938771 AE1-103 C Adder 4.98 MW 4.23 MW
314229 6MT RD221 80/20 0.22 MW 0.22 MW
314236 6NRTHEST 80/20 0.33 MW 0.33 MW
314309 6IRON208 80/20 0.79 MW 0.79 MW
314421 6WINCHST 80/20 0.24 MW 0.24 MW
314507 3THOMPSN Adder 3.57 MW 3.03 MW
315060 1CHESTF5 80/20 114.01 MW 114.01 MW
315061 1CHESTG7 80/20 6.93 MW 6.93 MW
315062 1CHESTS7 80/20 3.18 MW 3.18 MW
315063 1CHESTG8 80/20 6.82 MW 6.82 MW
315064 1CHESTS8 80/20 3.51 MW 3.51 MW
315065 1CHESTF6 Adder 34.49 MW 29.32 MW
315067 1DARBY 1 80/20 4.57 MW 4.57 MW
315068 1DARBY 2 80/20 4.58 MW 4.58 MW
315069 1DARBY 3 80/20 4.59 MW 4.59 MW
315070 1DARBY 4 80/20 4.6 MW 4.6 MW
315073 1STONECA 80/20 12.28 MW 12.28 MW
315076 1HOPPOLC 80/20 2.72 MW 2.72 MW
315077 1HOPHCF1 80/20 4.32 MW 4.32 MW
315078 1HOPHCF2 80/20 4.32 MW 4.32 MW
315079 1HOPHCF3 80/20 4.32 MW 4.32 MW
315080 1HOPHCF4 80/20 6.56 MW 6.56 MW
315083 1SPRUNCA Adder 15.79 MW 13.42 MW
315084 1SPRUNCB Adder 15.79 MW 13.42 MW
315092 1YORKTN3 80/20 239.44 MW 239.44 MW
936591 AD2-074 C Adder 8.71 MW 7.4 MW
942341 AE2-247 C Adder 2.6 MW 2.21 MW
943461 AF1-017 C Adder 2.35 MW 2.0 MW
943741 AF1-042 C Adder 4.56 MW 3.87 MW
961951 AG1-038 C Adder 5.04 MW 4.28 MW
966661 AG1-536 C Adder 8.21 MW 6.98 MW
966871 AG1-558 C Adder 4.08 MW 3.47 MW
315116 1SURRY 1 80/20 43.8 MW 43.8 MW
315119 1GRAVEL3 80/20 4.45 MW 4.45 MW
315120 1GRAVEL4 80/20 4.51 MW 4.51 MW
315122 1GRAVEL6 80/20 4.5 MW 4.5 MW
315233 1SURRY 2 80/20 45.83 MW 45.83 MW
315260 1GOSPORTA Adder 3.76 MW 3.2 MW
315261 1GOSPORTB Adder 4.81 MW 4.09 MW
315262 1GOSPORTC Adder 4.08 MW 3.47 MW
316075 AC2-137 C 80/20 0.69 MW 0.69 MW
316132 AB2-190 C 80/20 7.37 MW 7.37 MW
957601 AF2-054 C Adder 3.56 MW 3.03 MW
962861 AG1-135 C Adder 9.32 MW 7.92 MW
962971 AG1-146 C Adder 4.9 MW 4.16 MW
962981 AG1-147 C Adder 11.43 MW 9.72 MW
963611 AG1-210 C Adder 0.96 MW 0.81 MW
964211 AG1-282 C Adder 2.98 MW 2.54 MW
942001 AE2-212 C Adder 3.74 MW 3.18 MW
957871 AF2-081 C Adder 17.52 MW 14.89 MW
958161 AF2-110 C Adder 2.38 MW 2.03 MW
926071 AC1-086 C Adder 32.98 MW 28.04 MW
927021 AC1-189 C Adder 13.13 MW 11.16 MW
933291 AC2-141 C 80/20 54.36 MW 54.36 MW
934621 AD1-088 C Adder 18.12 MW 15.4 MW
939411 AE1-173 C Adder 145.79 MW 123.92 MW
934011 AD1-025 C 80/20 4.61 MW 4.61 MW
927041 AC1-191 C Adder 16.4 MW 13.94 MW
933981 AD1-022 C Adder 14.55 MW 12.37 MW
961681 AG1-008 C Adder 23.18 MW 19.71 MW
962571 AG1-106 C Adder 4.27 MW 3.63 MW
316004 AC1-112 C 80/20 0.6 MW 0.6 MW
316159 AE1-175 C 80/20 0.71 MW 0.71 MW
316169 AC1-164 GEN 80/20 73.92 MW 73.92 MW
316233 AE1-074 C Adder 4.09 MW 3.48 MW
316240 AF1-291 C Adder 3.78 MW 3.21 MW
316274 AC1-208 C Adder 14.05 MW 11.94 MW
316294 AC1-161 C 80/20 8.85 MW 8.85 MW
316312 AB1-027 C 80/20 0.96 MW 0.96 MW
316336 AC2-165 C Adder 13.93 MW 11.84 MW
316369 AC1-216 C 80/20 2.85 MW 2.85 MW
316382 AG1-145 C 80/20 0.64 MW 0.64 MW
316033 AB2-134 GEN 80/20 3.73 MW 3.73 MW
316311 AC2-079 C Adder 9.99 MW 8.49 MW
316349 AD2-085 C Adder 5.99 MW 5.09 MW
961611 AG1-000B C 80/20 28.36 MW 28.36 MW
941591 AE2-156 C Adder 31.66 MW 26.91 MW
944581 AF1-123 C Adder 80.24 MW 68.2 MW
944591 AF1-124 C Adder 80.52 MW 68.44 MW
944601 AF1-125 C Adder 79.0 MW 67.15 MW
944631 AF1-128 C 80/20 71.34 MW 71.34 MW
958261 AF2-120 C Adder 9.55 MW 8.12 MW
962491 AG1-098 C Adder 16.22 MW 13.79 MW
965281 AG1-393 C Adder 3.76 MW 3.19 MW
313764 3SOCKMAN Adder 1.11 MW 0.95 MW
934321 AD1-056 C Adder 9.66 MW 8.21 MW
934331 AD1-057 C Adder 5.39 MW 4.58 MW
934501 AD1-074 C Adder 56.23 MW 47.8 MW
934511 AD1-075 C Adder 14.06 MW 11.95 MW
935161 AD1-151 C 80/20 28.73 MW 28.73 MW
938531 AE1-072 C Adder 30.78 MW 26.16 MW
939191 AE1-149 C Adder 18.61 MW 15.82 MW
940431 AE2-027 C Adder 22.59 MW 19.2 MW
940481 AE2-033 C Adder 25.65 MW 21.8 MW
940541 AE2-040 C Adder 4.56 MW 3.87 MW
940551 AE2-041 C Adder 12.16 MW 10.34 MW
940641 AE2-051 C Adder 26.98 MW 22.94 MW
941101 AE2-104 C Adder 5.84 MW 4.97 MW
943471 AF1-018 C Adder 12.16 MW 10.34 MW
944641 AF1-129 C Adder 179.89 MW 152.91 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 84.24 MW 84.24 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 48.64 MW 48.64 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 156.7 MW 156.7 MW
NY PJM->LTFIMP_NY CLTF 4.13 MW 4.13 MW
LGEE LTFEXP_LGEE->PJM CLTF 3.35 MW 3.35 MW
WEC LTFEXP_WEC->PJM CLTF 1.73 MW 1.73 MW
CPLE LTFEXP_CPLE->PJM CLTF 17.61 MW 17.61 MW
TVA LTFEXP_TVA->PJM CLTF 12.4 MW 12.4 MW
MEC LTFEXP_MEC->PJM CLTF 9.56 MW 9.56 MW
LAGN LTFEXP_LAGN->PJM CLTF 15.45 MW 15.45 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.62 MW 0.62 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 8.41 MW 8.41 MW

Details for 3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
313813 to 314191 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 110.06 %
Rating: 219.96 MVA
Rating Type: B
MVA to Mitigate: 242.08 MVA
MW Contribution: 37.19 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 80/20 32.67 MW 32.67 MW
943741 AF1-042 C 80/20 17.09 MW 17.09 MW
961951 AG1-038 C 80/20 18.89 MW 18.89 MW
966661 AG1-536 C 80/20 31.99 MW 31.99 MW
962861 AG1-135 C 80/20 35.99 MW 35.99 MW
962971 AG1-146 C 80/20 17.99 MW 17.99 MW
962981 AG1-147 C 80/20 41.98 MW 41.98 MW
316404 AE1-155 C 80/20 12.57 MW 12.57 MW
958261 AF2-120 C 80/20 37.19 MW 37.19 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1
Contingency Name:
DVP_P1-2: LN 574_SRT-S
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 104.18 %
Rating: 548.02 MVA
Rating Type: B
MVA to Mitigate: 570.92 MVA
MW Contribution: 7.82 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 80/20 1.01 MW 1.01 MW
314184 3SHACKLE 80/20 0.35 MW 0.35 MW
315033 1BIRCHWDA 80/20 157.92 MW 157.92 MW
315034 1NORNECKC1 80/20 0.99 MW 0.99 MW
315035 1NORNECKC2 80/20 0.95 MW 0.95 MW
936591 AD2-074 C 80/20 6.23 MW 6.23 MW
943741 AF1-042 C 80/20 3.26 MW 3.26 MW
944491 AF1-114 C 80/20 21.14 MW 21.14 MW
961951 AG1-038 C 80/20 3.6 MW 3.6 MW
966661 AG1-536 C 80/20 6.73 MW 6.73 MW
316077 AC2-138 C 80/20 0.33 MW 0.33 MW
316156 AD2-030 C 80/20 0.27 MW 0.27 MW
957601 AF2-054 C 80/20 1.51 MW 1.51 MW
962861 AG1-135 C 80/20 7.4 MW 7.4 MW
962971 AG1-146 C 80/20 3.23 MW 3.23 MW
962981 AG1-147 C 80/20 7.53 MW 7.53 MW
963611 AG1-210 C 80/20 0.98 MW 0.98 MW
964211 AG1-282 C 80/20 2.74 MW 2.74 MW
957831 AF2-077 C 80/20 0.17 MW 0.17 MW
957971 AF2-091 C 80/20 7.19 MW 7.19 MW
316059 AD1-063 C 80/20 0.17 MW 0.17 MW
316314 AB2-024 C 80/20 0.19 MW 0.19 MW
939611 AE1-191 C 80/20 0.94 MW 0.94 MW
316201 AC1-065 C 80/20 1.08 MW 1.08 MW
316223 AC1-118 C 80/20 0.78 MW 0.78 MW
316337 AD2-073 C 80/20 0.65 MW 0.65 MW
316404 AE1-155 C 80/20 2.64 MW 2.64 MW
316280 AD1-041 C 80/20 0.59 MW 0.59 MW
958261 AF2-120 C 80/20 7.82 MW 7.82 MW
939601 AE1-190 C 80/20 0.23 MW 0.23 MW
940551 AE2-041 C 80/20 4.78 MW 4.78 MW
943471 AF1-018 C 80/20 4.78 MW 4.78 MW
957191 AF2-013 C 80/20 65.45 MW 65.45 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 8.18 MW 8.18 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 5.01 MW 5.01 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 17.51 MW 17.51 MW
NY PJM->LTFIMP_NY CLTF 0.5 MW 0.5 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.33 MW 0.33 MW
WEC LTFEXP_WEC->PJM CLTF 0.17 MW 0.17 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.02 MW 2.02 MW
TVA LTFEXP_TVA->PJM CLTF 1.3 MW 1.3 MW
MEC LTFEXP_MEC->PJM CLTF 0.96 MW 0.96 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.63 MW 1.63 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.06 MW 0.06 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.96 MW 0.96 MW

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1
Contingency Name:
DVP_P1-2: LN 574_SRT-S
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 104.13 %
Rating: 548.02 MVA
Rating Type: B
MVA to Mitigate: 570.64 MVA
MW Contribution: 7.82 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 80/20 1.01 MW 1.01 MW
314184 3SHACKLE 80/20 0.35 MW 0.35 MW
315033 1BIRCHWDA 80/20 157.92 MW 157.92 MW
315034 1NORNECKC1 80/20 0.99 MW 0.99 MW
315035 1NORNECKC2 80/20 0.95 MW 0.95 MW
936591 AD2-074 C 80/20 6.23 MW 6.23 MW
943741 AF1-042 C 80/20 3.26 MW 3.26 MW
944491 AF1-114 C 80/20 21.14 MW 21.14 MW
961951 AG1-038 C 80/20 3.6 MW 3.6 MW
966661 AG1-536 C 80/20 6.73 MW 6.73 MW
316077 AC2-138 C 80/20 0.33 MW 0.33 MW
316156 AD2-030 C 80/20 0.27 MW 0.27 MW
957601 AF2-054 C 80/20 1.51 MW 1.51 MW
962861 AG1-135 C 80/20 7.4 MW 7.4 MW
962971 AG1-146 C 80/20 3.23 MW 3.23 MW
962981 AG1-147 C 80/20 7.53 MW 7.53 MW
963611 AG1-210 C 80/20 0.98 MW 0.98 MW
964211 AG1-282 C 80/20 2.74 MW 2.74 MW
957831 AF2-077 C 80/20 0.17 MW 0.17 MW
957971 AF2-091 C 80/20 7.19 MW 7.19 MW
316059 AD1-063 C 80/20 0.17 MW 0.17 MW
316314 AB2-024 C 80/20 0.19 MW 0.19 MW
939611 AE1-191 C 80/20 0.94 MW 0.94 MW
316201 AC1-065 C 80/20 1.08 MW 1.08 MW
316223 AC1-118 C 80/20 0.78 MW 0.78 MW
316337 AD2-073 C 80/20 0.65 MW 0.65 MW
316404 AE1-155 C 80/20 2.64 MW 2.64 MW
316280 AD1-041 C 80/20 0.59 MW 0.59 MW
958261 AF2-120 C 80/20 7.82 MW 7.82 MW
939601 AE1-190 C 80/20 0.23 MW 0.23 MW
940551 AE2-041 C 80/20 4.78 MW 4.78 MW
943471 AF1-018 C 80/20 4.78 MW 4.78 MW
957191 AF2-013 C 80/20 65.45 MW 65.45 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 8.18 MW 8.18 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 5.01 MW 5.01 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 17.51 MW 17.51 MW
NY PJM->LTFIMP_NY CLTF 0.5 MW 0.5 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.33 MW 0.33 MW
WEC LTFEXP_WEC->PJM CLTF 0.17 MW 0.17 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.02 MW 2.02 MW
TVA LTFEXP_TVA->PJM CLTF 1.3 MW 1.3 MW
MEC LTFEXP_MEC->PJM CLTF 0.96 MW 0.96 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.63 MW 1.63 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.06 MW 0.06 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.96 MW 0.96 MW

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
314911 to 314922 ckt 1
Contingency Name:
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 102.06 %
Rating: 3220.44 MVA
Rating Type: B
MVA to Mitigate: 3286.74 MVA
MW Contribution: 5.22 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961941 AG1-037 C Adder 0.42 MW 0.35 MW
962331 AG1-082 C Adder 1.66 MW 1.41 MW
963041 AG1-153 C Adder 4.27 MW 3.63 MW
966811 AG1-552 C Adder 1.64 MW 1.4 MW
965291 AG1-394 C Adder 0.71 MW 0.6 MW
966621 AG1-532 C Adder 1.12 MW 0.95 MW
934521 AD1-076 C Adder 10.28 MW 8.73 MW
944011 AF1-069 C Adder 9.93 MW 8.44 MW
960081 AF2-299 C Adder 1.49 MW 1.27 MW
941031 AE2-094 C Adder 30.4 MW 25.84 MW
946281 AF1-292 C Adder 1.23 MW 1.05 MW
957481 AF2-042 C Adder 40.42 MW 34.35 MW
957521 AF2-046 C Adder 11.73 MW 9.97 MW
938771 AE1-103 C Adder 2.5 MW 2.13 MW
314229 6MT RD221 80/20 0.11 MW 0.11 MW
314236 6NRTHEST 80/20 0.17 MW 0.17 MW
314309 6IRON208 80/20 0.4 MW 0.4 MW
314507 3THOMPSN Adder 1.77 MW 1.51 MW
315039 1LDYSMT3 80/20 4.42 MW 4.42 MW
315040 1LDYSMT4 80/20 4.43 MW 4.43 MW
315041 1LDYSMT5 80/20 4.44 MW 4.44 MW
315060 1CHESTF5 80/20 57.85 MW 57.85 MW
315061 1CHESTG7 80/20 3.52 MW 3.52 MW
315062 1CHESTS7 80/20 1.61 MW 1.61 MW
315063 1CHESTG8 80/20 3.46 MW 3.46 MW
315064 1CHESTS8 80/20 1.78 MW 1.78 MW
315065 1CHESTF6 Adder 17.75 MW 15.09 MW
315067 1DARBY 1 80/20 2.35 MW 2.35 MW
315068 1DARBY 2 80/20 2.35 MW 2.35 MW
315069 1DARBY 3 80/20 2.36 MW 2.36 MW
315070 1DARBY 4 80/20 2.37 MW 2.37 MW
315073 1STONECA Adder 6.25 MW 5.31 MW
315083 1SPRUNCA Adder 8.22 MW 6.99 MW
315084 1SPRUNCB Adder 8.22 MW 6.99 MW
315092 1YORKTN3 Adder 118.69 MW 100.89 MW
936591 AD2-074 C Adder 4.69 MW 3.99 MW
942341 AE2-247 C Adder 1.31 MW 1.11 MW
943461 AF1-017 C Adder 1.18 MW 1.0 MW
943741 AF1-042 C Adder 2.45 MW 2.09 MW
961951 AG1-038 C Adder 2.71 MW 2.31 MW
966661 AG1-536 C Adder 4.49 MW 3.82 MW
966871 AG1-558 C 80/20 2.2 MW 2.2 MW
966881 AG1-559 C 80/20 2.29 MW 2.29 MW
315225 1N ANNA1 80/20 26.09 MW 26.09 MW
315226 1N ANNA2 80/20 26.09 MW 26.09 MW
315260 1GOSPORTA Adder 1.87 MW 1.59 MW
315261 1GOSPORTB Adder 2.39 MW 2.03 MW
315262 1GOSPORTC Adder 2.03 MW 1.73 MW
316075 AC2-137 C 80/20 0.35 MW 0.35 MW
957411 AF2-035 C 80/20 8.26 MW 8.26 MW
957601 AF2-054 C Adder 1.84 MW 1.56 MW
962861 AG1-135 C Adder 5.08 MW 4.32 MW
962971 AG1-146 C Adder 2.62 MW 2.23 MW
962981 AG1-147 C Adder 6.11 MW 5.19 MW
963051 AG1-154 C 80/20 3.4 MW 3.4 MW
963611 AG1-210 C Adder 0.54 MW 0.46 MW
964211 AG1-282 C Adder 1.65 MW 1.41 MW
942001 AE2-212 C Adder 1.92 MW 1.63 MW
957871 AF2-081 C Adder 8.72 MW 7.41 MW
958161 AF2-110 C Adder 1.19 MW 1.01 MW
926071 AC1-086 C Adder 16.84 MW 14.31 MW
933291 AC2-141 C Adder 26.79 MW 22.77 MW
939411 AE1-173 C Adder 73.68 MW 62.63 MW
927041 AC1-191 C 80/20 8.82 MW 8.82 MW
933981 AD1-022 C Adder 7.33 MW 6.23 MW
961681 AG1-008 C Adder 11.73 MW 9.97 MW
962571 AG1-106 C Adder 2.18 MW 1.85 MW
316004 AC1-112 C 80/20 0.3 MW 0.3 MW
316169 AC1-164 GEN 80/20 36.81 MW 36.81 MW
316233 AE1-074 C Adder 2.16 MW 1.83 MW
316240 AF1-291 C Adder 1.94 MW 1.65 MW
316312 AB1-027 C 80/20 0.49 MW 0.49 MW
316336 AC2-165 C Adder 7.75 MW 6.59 MW
315037 1LDYSMT1 80/20 4.25 MW 4.25 MW
315038 1LDYSMT2 80/20 4.3 MW 4.3 MW
315051 AA1-145 CT1 80/20 4.7 MW 4.7 MW
315052 AA1-145 CT2 80/20 4.7 MW 4.7 MW
316311 AC2-079 C Adder 5.02 MW 4.26 MW
316349 AD2-085 C Adder 3.01 MW 2.56 MW
961611 AG1-000B C Adder 14.24 MW 12.1 MW
941591 AE2-156 C Adder 15.74 MW 13.38 MW
944581 AF1-123 C Adder 39.82 MW 33.85 MW
944591 AF1-124 C Adder 39.96 MW 33.97 MW
944601 AF1-125 C Adder 39.21 MW 33.33 MW
944631 AF1-128 C 80/20 36.2 MW 36.2 MW
958261 AF2-120 C Adder 5.22 MW 4.44 MW
965281 AG1-393 C Adder 1.93 MW 1.64 MW
313764 3SOCKMAN Adder 0.57 MW 0.48 MW
934501 AD1-074 C Adder 28.29 MW 24.05 MW
934511 AD1-075 C Adder 7.07 MW 6.01 MW
935161 AD1-151 C Adder 14.52 MW 12.34 MW
938531 AE1-072 C Adder 15.31 MW 13.02 MW
939191 AE1-149 C Adder 9.48 MW 8.06 MW
939261 AE1-157 C 80/20 13.32 MW 13.32 MW
940431 AE2-027 C Adder 11.6 MW 9.86 MW
940481 AE2-033 C Adder 13.14 MW 11.17 MW
940541 AE2-040 C Adder 2.33 MW 1.98 MW
940551 AE2-041 C Adder 6.24 MW 5.3 MW
940641 AE2-051 C Adder 13.72 MW 11.66 MW
941101 AE2-104 C Adder 2.92 MW 2.48 MW
943471 AF1-018 C Adder 6.24 MW 5.3 MW
944641 AF1-129 C Adder 92.56 MW 78.67 MW
315043 1FOUR RIVERA 80/20 2.95 MW 2.95 MW
315044 1FOUR RIVERB 80/20 2.95 MW 2.95 MW
315045 1FOUR RIVERC 80/20 3.61 MW 3.61 MW
315046 1FOUR RIVERD 80/20 2.91 MW 2.91 MW
315047 1FOUR RIVERE 80/20 2.91 MW 2.91 MW
315048 1FOUR RIVERF 80/20 3.55 MW 3.55 MW
315085 1SPRUNCC 80/20 0.15 MW 0.15 MW
315086 1SPRUNCD 80/20 0.15 MW 0.15 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 45.84 MW 45.84 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 25.97 MW 25.97 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 81.52 MW 81.52 MW
NY PJM->LTFIMP_NY CLTF 2.83 MW 2.83 MW
LGEE LTFEXP_LGEE->PJM CLTF 1.82 MW 1.82 MW
WEC LTFEXP_WEC->PJM CLTF 0.94 MW 0.94 MW
CPLE LTFEXP_CPLE->PJM CLTF 9.11 MW 9.11 MW
TVA LTFEXP_TVA->PJM CLTF 6.57 MW 6.57 MW
MEC LTFEXP_MEC->PJM CLTF 5.16 MW 5.16 MW
LAGN LTFEXP_LAGN->PJM CLTF 8.19 MW 8.19 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.34 MW 0.34 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 4.35 MW 4.35 MW

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1
Contingency Name:
DVP_P1-2: LN 2090_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2090_SRT-A'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1   /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1   /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1   /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BUS 313837                                   /*6SUMMIT      230.0
 OPEN BUS 314138                                   /*6MINE RD     230.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 101.54 %
Rating: 548.02 MVA
Rating Type: B
MVA to Mitigate: 556.48 MVA
MW Contribution: 7.21 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 80/20 0.95 MW 0.95 MW
314184 3SHACKLE 80/20 0.31 MW 0.31 MW
315033 1BIRCHWDA 80/20 150.03 MW 150.03 MW
315034 1NORNECKC1 80/20 0.92 MW 0.92 MW
315035 1NORNECKC2 80/20 0.89 MW 0.89 MW
936591 AD2-074 C 80/20 5.72 MW 5.72 MW
943741 AF1-042 C 80/20 2.99 MW 2.99 MW
944491 AF1-114 C 80/20 19.96 MW 19.96 MW
961951 AG1-038 C 80/20 3.31 MW 3.31 MW
966661 AG1-536 C 80/20 6.2 MW 6.2 MW
316077 AC2-138 C 80/20 0.31 MW 0.31 MW
316156 AD2-030 C 80/20 0.24 MW 0.24 MW
957601 AF2-054 C 80/20 1.36 MW 1.36 MW
962861 AG1-135 C 80/20 6.82 MW 6.82 MW
962971 AG1-146 C 80/20 2.95 MW 2.95 MW
962981 AG1-147 C 80/20 6.89 MW 6.89 MW
963611 AG1-210 C 80/20 0.91 MW 0.91 MW
964211 AG1-282 C 80/20 2.53 MW 2.53 MW
957831 AF2-077 C 80/20 0.15 MW 0.15 MW
957971 AF2-091 C 80/20 6.79 MW 6.79 MW
316059 AD1-063 C 80/20 0.16 MW 0.16 MW
316314 AB2-024 C 80/20 0.17 MW 0.17 MW
939611 AE1-191 C 80/20 0.84 MW 0.84 MW
316201 AC1-065 C 80/20 0.96 MW 0.96 MW
316223 AC1-118 C 80/20 0.73 MW 0.73 MW
316337 AD2-073 C 80/20 0.61 MW 0.61 MW
316404 AE1-155 C 80/20 2.44 MW 2.44 MW
316280 AD1-041 C 80/20 0.53 MW 0.53 MW
958261 AF2-120 C 80/20 7.21 MW 7.21 MW
939601 AE1-190 C 80/20 0.21 MW 0.21 MW
940551 AE2-041 C 80/20 4.26 MW 4.26 MW
943471 AF1-018 C 80/20 4.26 MW 4.26 MW
957191 AF2-013 C 80/20 62.05 MW 62.05 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 5.86 MW 5.86 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 3.8 MW 3.8 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 14.18 MW 14.18 MW
NY PJM->LTFIMP_NY CLTF 0.42 MW 0.42 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.24 MW 0.24 MW
WEC LTFEXP_WEC->PJM CLTF 0.12 MW 0.12 MW
CPLE LTFEXP_CPLE->PJM CLTF 1.66 MW 1.66 MW
TVA LTFEXP_TVA->PJM CLTF 1.0 MW 1.0 MW
MEC LTFEXP_MEC->PJM CLTF 0.7 MW 0.7 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.26 MW 1.26 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.04 MW 0.04 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.79 MW 0.79 MW

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1
Contingency Name:
DVP_P1-2: LN 2090_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2090_SRT-A'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1   /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1   /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1   /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BUS 313837                                   /*6SUMMIT      230.0
 OPEN BUS 314138                                   /*6MINE RD     230.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 101.48 %
Rating: 548.02 MVA
Rating Type: B
MVA to Mitigate: 556.11 MVA
MW Contribution: 7.21 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 80/20 0.95 MW 0.95 MW
314184 3SHACKLE 80/20 0.31 MW 0.31 MW
315033 1BIRCHWDA 80/20 150.03 MW 150.03 MW
315034 1NORNECKC1 80/20 0.92 MW 0.92 MW
315035 1NORNECKC2 80/20 0.89 MW 0.89 MW
936591 AD2-074 C 80/20 5.72 MW 5.72 MW
943741 AF1-042 C 80/20 2.99 MW 2.99 MW
944491 AF1-114 C 80/20 19.96 MW 19.96 MW
961951 AG1-038 C 80/20 3.31 MW 3.31 MW
966661 AG1-536 C 80/20 6.2 MW 6.2 MW
316077 AC2-138 C 80/20 0.31 MW 0.31 MW
316156 AD2-030 C 80/20 0.24 MW 0.24 MW
957601 AF2-054 C 80/20 1.36 MW 1.36 MW
962861 AG1-135 C 80/20 6.82 MW 6.82 MW
962971 AG1-146 C 80/20 2.95 MW 2.95 MW
962981 AG1-147 C 80/20 6.89 MW 6.89 MW
963611 AG1-210 C 80/20 0.91 MW 0.91 MW
964211 AG1-282 C 80/20 2.53 MW 2.53 MW
957831 AF2-077 C 80/20 0.15 MW 0.15 MW
957971 AF2-091 C 80/20 6.79 MW 6.79 MW
316059 AD1-063 C 80/20 0.16 MW 0.16 MW
316314 AB2-024 C 80/20 0.17 MW 0.17 MW
939611 AE1-191 C 80/20 0.84 MW 0.84 MW
316201 AC1-065 C 80/20 0.96 MW 0.96 MW
316223 AC1-118 C 80/20 0.73 MW 0.73 MW
316337 AD2-073 C 80/20 0.61 MW 0.61 MW
316404 AE1-155 C 80/20 2.44 MW 2.44 MW
316280 AD1-041 C 80/20 0.53 MW 0.53 MW
958261 AF2-120 C 80/20 7.21 MW 7.21 MW
939601 AE1-190 C 80/20 0.21 MW 0.21 MW
940551 AE2-041 C 80/20 4.26 MW 4.26 MW
943471 AF1-018 C 80/20 4.26 MW 4.26 MW
957191 AF2-013 C 80/20 62.05 MW 62.05 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 5.86 MW 5.86 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 3.8 MW 3.8 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 14.18 MW 14.18 MW
NY PJM->LTFIMP_NY CLTF 0.42 MW 0.42 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.24 MW 0.24 MW
WEC LTFEXP_WEC->PJM CLTF 0.12 MW 0.12 MW
CPLE LTFEXP_CPLE->PJM CLTF 1.66 MW 1.66 MW
TVA LTFEXP_TVA->PJM CLTF 1.0 MW 1.0 MW
MEC LTFEXP_MEC->PJM CLTF 0.7 MW 0.7 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.26 MW 1.26 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.04 MW 0.04 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.79 MW 0.79 MW

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
314911 to 314922 ckt 1
Contingency Name:
DVP_P1-2: LN 552_SRT-S
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 101.34 %
Rating: 3220.44 MVA
Rating Type: B
MVA to Mitigate: 3263.68 MVA
MW Contribution: 5.2 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961941 AG1-037 C Adder 0.42 MW 0.35 MW
962331 AG1-082 C Adder 1.66 MW 1.41 MW
963041 AG1-153 C Adder 4.26 MW 3.62 MW
966811 AG1-552 C Adder 1.64 MW 1.4 MW
965291 AG1-394 C Adder 0.71 MW 0.6 MW
966621 AG1-532 C Adder 1.11 MW 0.95 MW
934521 AD1-076 C Adder 10.25 MW 8.71 MW
944011 AF1-069 C Adder 9.92 MW 8.43 MW
960081 AF2-299 C Adder 1.49 MW 1.26 MW
941031 AE2-094 C Adder 30.35 MW 25.8 MW
946281 AF1-292 C Adder 1.23 MW 1.04 MW
957481 AF2-042 C Adder 40.37 MW 34.31 MW
957521 AF2-046 C Adder 11.71 MW 9.95 MW
938771 AE1-103 C Adder 2.5 MW 2.12 MW
314229 6MT RD221 80/20 0.11 MW 0.11 MW
314236 6NRTHEST 80/20 0.17 MW 0.17 MW
314309 6IRON208 80/20 0.4 MW 0.4 MW
314507 3THOMPSN Adder 1.77 MW 1.5 MW
315039 1LDYSMT3 80/20 4.38 MW 4.38 MW
315040 1LDYSMT4 80/20 4.39 MW 4.39 MW
315041 1LDYSMT5 80/20 4.41 MW 4.41 MW
315060 1CHESTF5 80/20 57.63 MW 57.63 MW
315061 1CHESTG7 80/20 3.5 MW 3.5 MW
315062 1CHESTS7 80/20 1.61 MW 1.61 MW
315063 1CHESTG8 80/20 3.45 MW 3.45 MW
315064 1CHESTS8 80/20 1.77 MW 1.77 MW
315065 1CHESTF6 Adder 17.69 MW 15.03 MW
315067 1DARBY 1 80/20 2.34 MW 2.34 MW
315068 1DARBY 2 80/20 2.35 MW 2.35 MW
315069 1DARBY 3 80/20 2.35 MW 2.35 MW
315070 1DARBY 4 80/20 2.36 MW 2.36 MW
315073 1STONECA Adder 6.23 MW 5.29 MW
315083 1SPRUNCA Adder 8.2 MW 6.97 MW
315084 1SPRUNCB Adder 8.2 MW 6.97 MW
315092 1YORKTN3 Adder 118.27 MW 100.53 MW
936591 AD2-074 C Adder 4.67 MW 3.97 MW
942341 AE2-247 C Adder 1.3 MW 1.11 MW
943461 AF1-017 C Adder 1.18 MW 1.0 MW
943741 AF1-042 C Adder 2.44 MW 2.08 MW
961951 AG1-038 C Adder 2.7 MW 2.29 MW
966661 AG1-536 C Adder 4.47 MW 3.8 MW
966871 AG1-558 C 80/20 2.19 MW 2.19 MW
966881 AG1-559 C 80/20 2.27 MW 2.27 MW
315225 1N ANNA1 80/20 26.19 MW 26.19 MW
315226 1N ANNA2 80/20 26.2 MW 26.2 MW
315260 1GOSPORTA Adder 1.87 MW 1.59 MW
315261 1GOSPORTB Adder 2.38 MW 2.03 MW
315262 1GOSPORTC Adder 2.02 MW 1.72 MW
316075 AC2-137 C 80/20 0.34 MW 0.34 MW
957411 AF2-035 C 80/20 8.21 MW 8.21 MW
957601 AF2-054 C Adder 1.83 MW 1.55 MW
962861 AG1-135 C Adder 5.06 MW 4.3 MW
962971 AG1-146 C Adder 2.6 MW 2.21 MW
962981 AG1-147 C Adder 6.08 MW 5.17 MW
963051 AG1-154 C 80/20 3.37 MW 3.37 MW
964211 AG1-282 C Adder 1.65 MW 1.4 MW
942001 AE2-212 C Adder 1.92 MW 1.63 MW
957871 AF2-081 C Adder 8.69 MW 7.39 MW
958161 AF2-110 C Adder 1.19 MW 1.01 MW
926071 AC1-086 C Adder 16.8 MW 14.28 MW
933291 AC2-141 C Adder 26.71 MW 22.7 MW
939411 AE1-173 C Adder 73.52 MW 62.49 MW
927041 AC1-191 C 80/20 8.78 MW 8.78 MW
933981 AD1-022 C Adder 7.31 MW 6.21 MW
961681 AG1-008 C Adder 11.71 MW 9.95 MW
962571 AG1-106 C Adder 2.17 MW 1.85 MW
316004 AC1-112 C 80/20 0.3 MW 0.3 MW
316169 AC1-164 GEN 80/20 36.66 MW 36.66 MW
316233 AE1-074 C Adder 2.15 MW 1.83 MW
316240 AF1-291 C Adder 1.94 MW 1.65 MW
316312 AB1-027 C 80/20 0.49 MW 0.49 MW
316336 AC2-165 C Adder 7.76 MW 6.59 MW
315037 1LDYSMT1 80/20 4.21 MW 4.21 MW
315038 1LDYSMT2 80/20 4.27 MW 4.27 MW
315051 AA1-145 CT1 80/20 4.68 MW 4.68 MW
315052 AA1-145 CT2 80/20 4.67 MW 4.67 MW
316311 AC2-079 C Adder 5.0 MW 4.25 MW
316349 AD2-085 C Adder 3.0 MW 2.55 MW
961611 AG1-000B C Adder 14.19 MW 12.06 MW
941591 AE2-156 C Adder 15.69 MW 13.34 MW
944581 AF1-123 C Adder 39.7 MW 33.75 MW
944591 AF1-124 C Adder 39.85 MW 33.87 MW
944601 AF1-125 C Adder 39.09 MW 33.23 MW
944631 AF1-128 C 80/20 36.06 MW 36.06 MW
958261 AF2-120 C Adder 5.2 MW 4.42 MW
965281 AG1-393 C Adder 1.92 MW 1.63 MW
313764 3SOCKMAN Adder 0.57 MW 0.48 MW
934501 AD1-074 C Adder 28.22 MW 23.99 MW
934511 AD1-075 C Adder 7.06 MW 6.0 MW
935161 AD1-151 C Adder 14.47 MW 12.3 MW
938531 AE1-072 C Adder 15.27 MW 12.98 MW
939191 AE1-149 C Adder 9.45 MW 8.04 MW
939261 AE1-157 C 80/20 13.23 MW 13.23 MW
940431 AE2-027 C Adder 11.56 MW 9.83 MW
940481 AE2-033 C Adder 13.11 MW 11.14 MW
940541 AE2-040 C Adder 2.33 MW 1.98 MW
940551 AE2-041 C Adder 6.21 MW 5.28 MW
940641 AE2-051 C Adder 13.69 MW 11.64 MW
941101 AE2-104 C Adder 2.91 MW 2.48 MW
943471 AF1-018 C Adder 6.21 MW 5.28 MW
944641 AF1-129 C Adder 92.24 MW 78.41 MW
315043 1FOUR RIVERA 80/20 2.94 MW 2.94 MW
315044 1FOUR RIVERB 80/20 2.94 MW 2.94 MW
315045 1FOUR RIVERC 80/20 3.59 MW 3.59 MW
315046 1FOUR RIVERD 80/20 2.89 MW 2.89 MW
315047 1FOUR RIVERE 80/20 2.89 MW 2.89 MW
315048 1FOUR RIVERF 80/20 3.53 MW 3.53 MW
315085 1SPRUNCC 80/20 0.15 MW 0.15 MW
315086 1SPRUNCD 80/20 0.15 MW 0.15 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 45.83 MW 45.83 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 25.95 MW 25.95 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 81.42 MW 81.42 MW
NY PJM->LTFIMP_NY CLTF 2.83 MW 2.83 MW
LGEE LTFEXP_LGEE->PJM CLTF 1.82 MW 1.82 MW
WEC LTFEXP_WEC->PJM CLTF 0.94 MW 0.94 MW
CPLE LTFEXP_CPLE->PJM CLTF 9.1 MW 9.1 MW
TVA LTFEXP_TVA->PJM CLTF 6.57 MW 6.57 MW
MEC LTFEXP_MEC->PJM CLTF 5.16 MW 5.16 MW
LAGN LTFEXP_LAGN->PJM CLTF 8.18 MW 8.18 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.34 MW 0.34 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 4.34 MW 4.34 MW

Details for 6FREDBRG-6CRANES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9296_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
6FREDBRG-6CRANES 230.0 kV Ckt 1 line
314137 to 314134 ckt 1
Contingency Name:
DVP_P1-2: LN 9296_SRT-A
CONTINGENCY 'DVP_P1-2: LN 9296_SRT-A'
 OPEN BRANCH FROM BUS 314137 TO BUS 314145 CKT 1   /*6FREDBRG     230.0 - 6AQUI_HARB_B 230.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 101.19 %
Rating: 984.18 MVA
Rating Type: B
MVA to Mitigate: 995.92 MVA
MW Contribution: 4.75 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 80/20 0.48 MW 0.48 MW
314184 3SHACKLE 80/20 0.26 MW 0.26 MW
315033 1BIRCHWDA 80/20 75.26 MW 75.26 MW
315034 1NORNECKC1 80/20 0.58 MW 0.58 MW
315035 1NORNECKC2 80/20 0.56 MW 0.56 MW
315039 1LDYSMT3 80/20 4.37 MW 4.37 MW
315040 1LDYSMT4 80/20 4.38 MW 4.38 MW
315041 1LDYSMT5 80/20 4.39 MW 4.39 MW
315050 1FOURRIVERG 80/20 4.18 MW 4.18 MW
315060 1CHESTF5 Adder 22.44 MW 19.08 MW
315092 1YORKTN3 Adder 45.52 MW 38.7 MW
934781 AD1-105 C 80/20 1.18 MW 1.18 MW
936591 AD2-074 C 80/20 3.9 MW 3.9 MW
943741 AF1-042 C 80/20 2.04 MW 2.04 MW
944491 AF1-114 C 80/20 10.64 MW 10.64 MW
961951 AG1-038 C 80/20 2.25 MW 2.25 MW
966661 AG1-536 C 80/20 4.09 MW 4.09 MW
966871 AG1-558 C 80/20 1.16 MW 1.16 MW
966881 AG1-559 C 80/20 1.77 MW 1.77 MW
316077 AC2-138 C 80/20 0.2 MW 0.2 MW
316156 AD2-030 C 80/20 0.2 MW 0.2 MW
957411 AF2-035 C 80/20 6.37 MW 6.37 MW
957601 AF2-054 C 80/20 1.09 MW 1.09 MW
962861 AG1-135 C 80/20 4.53 MW 4.53 MW
962971 AG1-146 C 80/20 2.06 MW 2.06 MW
962981 AG1-147 C 80/20 4.8 MW 4.8 MW
963051 AG1-154 C 80/20 3.36 MW 3.36 MW
963611 AG1-210 C 80/20 0.57 MW 0.57 MW
964211 AG1-282 C 80/20 1.63 MW 1.63 MW
957971 AF2-091 C 80/20 3.62 MW 3.62 MW
927041 AC1-191 C 80/20 4.66 MW 4.66 MW
316059 AD1-063 C 80/20 0.13 MW 0.13 MW
316169 AC1-164 GEN Adder 15.3 MW 13.0 MW
316314 AB2-024 C 80/20 0.14 MW 0.14 MW
939611 AE1-191 C 80/20 0.69 MW 0.69 MW
315037 1LDYSMT1 80/20 4.2 MW 4.2 MW
315038 1LDYSMT2 80/20 4.26 MW 4.26 MW
315051 AA1-145 CT1 80/20 2.46 MW 2.46 MW
315052 AA1-145 CT2 80/20 2.46 MW 2.46 MW
316201 AC1-065 C 80/20 0.81 MW 0.81 MW
316223 AC1-118 C 80/20 0.41 MW 0.41 MW
316337 AD2-073 C 80/20 0.36 MW 0.36 MW
316404 AE1-155 C 80/20 1.61 MW 1.61 MW
316280 AD1-041 C 80/20 0.44 MW 0.44 MW
944631 AF1-128 C Adder 14.04 MW 11.94 MW
958261 AF2-120 C 80/20 4.75 MW 4.75 MW
939261 AE1-157 C 80/20 11.33 MW 11.33 MW
939601 AE1-190 C 80/20 0.17 MW 0.17 MW
940551 AE2-041 C 80/20 3.55 MW 3.55 MW
943471 AF1-018 C 80/20 3.55 MW 3.55 MW
957191 AF2-013 C 80/20 31.8 MW 31.8 MW
315043 1FOUR RIVERA 80/20 1.54 MW 1.54 MW
315044 1FOUR RIVERB 80/20 1.54 MW 1.54 MW
315045 1FOUR RIVERC 80/20 1.89 MW 1.89 MW
315046 1FOUR RIVERD 80/20 1.52 MW 1.52 MW
315047 1FOUR RIVERE 80/20 1.52 MW 1.52 MW
315048 1FOUR RIVERF 80/20 1.86 MW 1.86 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 10.28 MW 10.28 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 6.48 MW 6.48 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 23.07 MW 23.07 MW
NY PJM->LTFIMP_NY CLTF 0.8 MW 0.8 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.42 MW 0.42 MW
WEC LTFEXP_WEC->PJM CLTF 0.21 MW 0.21 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.65 MW 2.65 MW
TVA LTFEXP_TVA->PJM CLTF 1.7 MW 1.7 MW
MEC LTFEXP_MEC->PJM CLTF 1.22 MW 1.22 MW
LAGN LTFEXP_LAGN->PJM CLTF 2.12 MW 2.12 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.08 MW 0.08 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 1.27 MW 1.27 MW

Details for 6FREDBRG-6CRANES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2119_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
6FREDBRG-6CRANES 230.0 kV Ckt 1 line
314137 to 314134 ckt 1
Contingency Name:
DVP_P1-2: LN 2119_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2119_SRT-A'
 OPEN BRANCH FROM BUS 314140 TO BUS 314145 CKT 1   /*6GARSVL      230.0 - 6AQUI_HARB_B 230.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 101.17 %
Rating: 984.18 MVA
Rating Type: B
MVA to Mitigate: 995.73 MVA
MW Contribution: 4.75 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 80/20 0.48 MW 0.48 MW
314184 3SHACKLE 80/20 0.26 MW 0.26 MW
315033 1BIRCHWDA 80/20 75.26 MW 75.26 MW
315034 1NORNECKC1 80/20 0.58 MW 0.58 MW
315035 1NORNECKC2 80/20 0.56 MW 0.56 MW
315039 1LDYSMT3 80/20 4.37 MW 4.37 MW
315040 1LDYSMT4 80/20 4.38 MW 4.38 MW
315041 1LDYSMT5 80/20 4.39 MW 4.39 MW
315050 1FOURRIVERG 80/20 4.18 MW 4.18 MW
315060 1CHESTF5 Adder 22.44 MW 19.08 MW
315092 1YORKTN3 Adder 45.52 MW 38.7 MW
934781 AD1-105 C 80/20 1.18 MW 1.18 MW
936591 AD2-074 C 80/20 3.9 MW 3.9 MW
943741 AF1-042 C 80/20 2.04 MW 2.04 MW
944491 AF1-114 C 80/20 10.64 MW 10.64 MW
961951 AG1-038 C 80/20 2.25 MW 2.25 MW
966661 AG1-536 C 80/20 4.09 MW 4.09 MW
966871 AG1-558 C 80/20 1.16 MW 1.16 MW
966881 AG1-559 C 80/20 1.77 MW 1.77 MW
316077 AC2-138 C 80/20 0.2 MW 0.2 MW
316156 AD2-030 C 80/20 0.2 MW 0.2 MW
957411 AF2-035 C 80/20 6.37 MW 6.37 MW
957601 AF2-054 C 80/20 1.09 MW 1.09 MW
962861 AG1-135 C 80/20 4.53 MW 4.53 MW
962971 AG1-146 C 80/20 2.06 MW 2.06 MW
962981 AG1-147 C 80/20 4.8 MW 4.8 MW
963051 AG1-154 C 80/20 3.36 MW 3.36 MW
963611 AG1-210 C 80/20 0.57 MW 0.57 MW
964211 AG1-282 C 80/20 1.63 MW 1.63 MW
957971 AF2-091 C 80/20 3.62 MW 3.62 MW
927041 AC1-191 C 80/20 4.66 MW 4.66 MW
316059 AD1-063 C 80/20 0.13 MW 0.13 MW
316169 AC1-164 GEN Adder 15.3 MW 13.0 MW
316314 AB2-024 C 80/20 0.14 MW 0.14 MW
939611 AE1-191 C 80/20 0.69 MW 0.69 MW
315037 1LDYSMT1 80/20 4.2 MW 4.2 MW
315038 1LDYSMT2 80/20 4.26 MW 4.26 MW
315051 AA1-145 CT1 80/20 2.46 MW 2.46 MW
315052 AA1-145 CT2 80/20 2.46 MW 2.46 MW
316201 AC1-065 C 80/20 0.81 MW 0.81 MW
316223 AC1-118 C 80/20 0.41 MW 0.41 MW
316337 AD2-073 C 80/20 0.36 MW 0.36 MW
316404 AE1-155 C 80/20 1.61 MW 1.61 MW
316280 AD1-041 C 80/20 0.44 MW 0.44 MW
944631 AF1-128 C Adder 14.04 MW 11.94 MW
958261 AF2-120 C 80/20 4.75 MW 4.75 MW
939261 AE1-157 C 80/20 11.33 MW 11.33 MW
939601 AE1-190 C 80/20 0.17 MW 0.17 MW
940551 AE2-041 C 80/20 3.55 MW 3.55 MW
943471 AF1-018 C 80/20 3.55 MW 3.55 MW
957191 AF2-013 C 80/20 31.8 MW 31.8 MW
315043 1FOUR RIVERA 80/20 1.54 MW 1.54 MW
315044 1FOUR RIVERB 80/20 1.54 MW 1.54 MW
315045 1FOUR RIVERC 80/20 1.89 MW 1.89 MW
315046 1FOUR RIVERD 80/20 1.52 MW 1.52 MW
315047 1FOUR RIVERE 80/20 1.52 MW 1.52 MW
315048 1FOUR RIVERF 80/20 1.86 MW 1.86 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 10.28 MW 10.28 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 6.48 MW 6.48 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 23.07 MW 23.07 MW
NY PJM->LTFIMP_NY CLTF 0.8 MW 0.8 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.42 MW 0.42 MW
WEC LTFEXP_WEC->PJM CLTF 0.21 MW 0.21 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.65 MW 2.65 MW
TVA LTFEXP_TVA->PJM CLTF 1.7 MW 1.7 MW
MEC LTFEXP_MEC->PJM CLTF 1.22 MW 1.22 MW
LAGN LTFEXP_LAGN->PJM CLTF 2.12 MW 2.12 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.08 MW 0.08 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 1.27 MW 1.27 MW

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1
Contingency Name:
DVP_P1-2: LN 563_SRT-S-1
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA       500.0 - AE2-051 TP   500.0
END
Contingency Type: Single
DC|AC: AC
Final Cycle Loading: 100.88 %
Rating: 4070.2 MVA
Rating Type: B
MVA to Mitigate: 4105.97 MVA
MW Contribution: 8.1 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961671 AG1-007 C Adder 1.23 MW 1.04 MW
961941 AG1-037 C Adder 0.7 MW 0.59 MW
962331 AG1-082 C Adder 2.79 MW 2.37 MW
963041 AG1-153 C Adder 7.02 MW 5.97 MW
966801 AG1-551 C Adder 2.86 MW 2.43 MW
966811 AG1-552 C Adder 2.71 MW 2.3 MW
965291 AG1-394 C Adder 1.19 MW 1.01 MW
966621 AG1-532 C Adder 1.82 MW 1.54 MW
934521 AD1-076 C Adder 17.45 MW 14.83 MW
944011 AF1-069 C Adder 16.4 MW 13.94 MW
960081 AF2-299 C Adder 2.42 MW 2.06 MW
941031 AE2-094 C Adder 50.2 MW 42.67 MW
946281 AF1-292 C Adder 2.01 MW 1.71 MW
957481 AF2-042 C Adder 64.72 MW 55.02 MW
957521 AF2-046 C Adder 19.67 MW 16.72 MW
957861 AF2-080 C Adder 10.13 MW 8.61 MW
938771 AE1-103 C Adder 4.25 MW 3.61 MW
314229 6MT RD221 80/20 0.18 MW 0.18 MW
314421 6WINCHST 80/20 0.2 MW 0.2 MW
314507 3THOMPSN 80/20 3.07 MW 3.07 MW
315060 1CHESTF5 Adder 92.3 MW 78.45 MW
315065 1CHESTF6 Adder 27.54 MW 23.41 MW
315073 1STONECA Adder 9.99 MW 8.49 MW
315083 1SPRUNCA Adder 10.61 MW 9.02 MW
315084 1SPRUNCB Adder 10.61 MW 9.02 MW
315092 1YORKTN3 80/20 206.84 MW 206.84 MW
936591 AD2-074 C Adder 7.4 MW 6.29 MW
942341 AE2-247 C Adder 2.2 MW 1.87 MW
943461 AF1-017 C Adder 1.99 MW 1.69 MW
943741 AF1-042 C Adder 3.87 MW 3.29 MW
961951 AG1-038 C Adder 4.28 MW 3.64 MW
966661 AG1-536 C Adder 6.97 MW 5.92 MW
966871 AG1-558 C Adder 3.38 MW 2.88 MW
315098 1CHESPKA 80/20 0.66 MW 0.66 MW
315099 1CHESPKB 80/20 1.1 MW 1.1 MW
315108 1ELIZAR1 80/20 4.86 MW 4.86 MW
315109 1ELIZAR2 80/20 4.77 MW 4.77 MW
315110 1ELIZAR3 80/20 4.92 MW 4.92 MW
315116 1SURRY 1 80/20 36.99 MW 36.99 MW
315120 1GRAVEL4 80/20 3.81 MW 3.81 MW
315122 1GRAVEL6 80/20 3.8 MW 3.8 MW
315216 1CUNINGA 80/20 7.92 MW 7.92 MW
315217 1CUNINGB 80/20 7.92 MW 7.92 MW
315218 1CUNINGC 80/20 7.92 MW 7.92 MW
315219 1CUNINGD 80/20 17.71 MW 17.71 MW
315233 1SURRY 2 80/20 40.27 MW 40.27 MW
315260 1GOSPORTA 80/20 3.24 MW 3.24 MW
315261 1GOSPORTB 80/20 4.14 MW 4.14 MW
315262 1GOSPORTC 80/20 3.51 MW 3.51 MW
316075 AC2-137 C 80/20 0.57 MW 0.57 MW
957601 AF2-054 C Adder 3.04 MW 2.58 MW
962861 AG1-135 C Adder 7.91 MW 6.72 MW
962971 AG1-146 C Adder 4.16 MW 3.54 MW
962981 AG1-147 C Adder 9.72 MW 8.26 MW
963611 AG1-210 C Adder 0.81 MW 0.69 MW
964211 AG1-282 C Adder 2.53 MW 2.15 MW
942001 AE2-212 C Adder 3.02 MW 2.56 MW
957871 AF2-081 C 80/20 15.09 MW 15.09 MW
958161 AF2-110 C Adder 2.04 MW 1.73 MW
926071 AC1-086 C Adder 27.76 MW 23.6 MW
927021 AC1-189 C Adder 11.15 MW 9.48 MW
933291 AC2-141 C 80/20 47.33 MW 47.33 MW
934621 AD1-088 C Adder 14.9 MW 12.66 MW
939411 AE1-173 C Adder 124.69 MW 105.99 MW
916191 Z1-068 C 80/20 0.07 MW 0.07 MW
927041 AC1-191 C Adder 13.59 MW 11.55 MW
933981 AD1-022 C Adder 12.42 MW 10.55 MW
961681 AG1-008 C Adder 19.67 MW 16.72 MW
962571 AG1-106 C Adder 3.59 MW 3.05 MW
316004 AC1-112 C 80/20 0.51 MW 0.51 MW
316036 AC1-147 C 80/20 0.56 MW 0.56 MW
316159 AE1-175 C 80/20 0.61 MW 0.61 MW
316169 AC1-164 GEN 80/20 63.01 MW 63.01 MW
316185 AD1-033 C 80/20 1.86 MW 1.86 MW
316236 AE1-162 C 80/20 0.53 MW 0.53 MW
316240 AF1-291 C Adder 3.03 MW 2.57 MW
316274 AC1-208 C Adder 11.87 MW 10.09 MW
316294 AC1-161 C 80/20 7.71 MW 7.71 MW
316312 AB1-027 C 80/20 0.81 MW 0.81 MW
316316 AC1-027 C 80/20 0.48 MW 0.48 MW
316382 AG1-145 C 80/20 0.55 MW 0.55 MW
316017 AA1-139 ULT1 80/20 1.63 MW 1.63 MW
316018 AA1-139 ULT2 80/20 1.63 MW 1.63 MW
316375 AC2-012 C 80/20 2.05 MW 2.05 MW
316311 AC2-079 C Adder 8.47 MW 7.2 MW
316349 AD2-085 C Adder 5.08 MW 4.31 MW
316388 AE2-253 GEN 80/20 2.96 MW 2.96 MW
961611 AG1-000B C Adder 23.85 MW 20.27 MW
941591 AE2-156 C 80/20 27.26 MW 27.26 MW
944581 AF1-123 C 80/20 69.3 MW 69.3 MW
944591 AF1-124 C 80/20 69.54 MW 69.54 MW
944601 AF1-125 C 80/20 68.23 MW 68.23 MW
944631 AF1-128 C Adder 57.75 MW 49.09 MW
958261 AF2-120 C Adder 8.1 MW 6.88 MW
962491 AG1-098 C Adder 13.31 MW 11.31 MW
965281 AG1-393 C Adder 3.03 MW 2.58 MW
313764 3SOCKMAN Adder 0.93 MW 0.79 MW
934321 AD1-056 C Adder 8.15 MW 6.93 MW
934331 AD1-057 C Adder 4.55 MW 3.87 MW
934501 AD1-074 C Adder 48.04 MW 40.83 MW
934511 AD1-075 C Adder 12.01 MW 10.21 MW
935161 AD1-151 C Adder 23.76 MW 20.19 MW
938531 AE1-072 C Adder 26.5 MW 22.53 MW
939191 AE1-149 C Adder 15.33 MW 13.03 MW
940431 AE2-027 C Adder 18.18 MW 15.46 MW
940481 AE2-033 C Adder 21.38 MW 18.17 MW
940541 AE2-040 C Adder 3.79 MW 3.23 MW
940551 AE2-041 C Adder 10.37 MW 8.81 MW
940641 AE2-051 C Adder 23.01 MW 19.56 MW
941101 AE2-104 C Adder 5.0 MW 4.25 MW
943471 AF1-018 C Adder 10.37 MW 8.81 MW
944641 AF1-129 C Adder 143.62 MW 122.08 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 74.17 MW 74.17 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 42.32 MW 42.32 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 133.89 MW 133.89 MW
NY PJM->LTFIMP_NY CLTF 3.6 MW 3.6 MW
LGEE LTFEXP_LGEE->PJM CLTF 2.95 MW 2.95 MW
WEC LTFEXP_WEC->PJM CLTF 1.52 MW 1.52 MW
CPLE LTFEXP_CPLE->PJM CLTF 14.97 MW 14.97 MW
TVA LTFEXP_TVA->PJM CLTF 10.75 MW 10.75 MW
MEC LTFEXP_MEC->PJM CLTF 8.37 MW 8.37 MW
LAGN LTFEXP_LAGN->PJM CLTF 13.39 MW 13.39 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.54 MW 0.54 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 7.15 MW 7.15 MW

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P4-2: 65T1021_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
316399 to 314181 ckt 1
Contingency Name:
DVP_P4-2: 65T1021_SRT-A
CONTINGENCY 'DVP_P4-2: 65T1021_SRT-A'
 OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1    /*3OCRAN       115.0 - 3LANCAST     115.0
 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1    /*3OCRAN       115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313842 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_1 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313843 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_2 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 313900 CKT Z1   /*3RAPPAHNCK   115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1    /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 314174 CKT 1    /*3GREYSPT     115.0 - 3HARMONY     115.0
 OPEN BRANCH FROM BUS 313900 TO BUS 313886 CKT 1    /*3RAPP TR     115.0 - 3GREYSPT     115.0
 OPEN BRANCH FROM BUS 313900 TO BUS 313886 CKT 2    /*3RAPP TR     115.0 - 3GREYSPT     115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1    /*3LANCAST     115.0 - 3LANCA_1     115.0
 OPEN BRANCH FROM BUS 962970 TO BUS 314178 CKT 1    /*AG1-146 TP   115.0 - 3LANCAST     115.0
 OPEN BUS 313813                                    /*3OCRAN       115.0
 OPEN BUS 313842                                    /*3RAPPAHNCK_1 115.0
 OPEN BUS 313843                                    /*3RAPPAHNCK_2 115.0
 OPEN BUS 313886                                    /*3GREYSPT     115.0
 OPEN BUS 314178                                    /*3LANCAST     115.0
 OPEN BUS 314191                                    /*3WHIT STONE  115.0
 OPEN BUS 314400                                    /*3LANCA_1     115.0
END
Contingency Type: Breaker
DC|AC: AC
Final Cycle Loading: 233.75 %
Rating: 249.0 MVA
Rating Type: C
MVA to Mitigate: 582.03 MVA
MW Contribution: 61.98 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 50/50 32.67 MW 32.67 MW
936592 AD2-074 E 50/50 53.3 MW 53.3 MW
943741 AF1-042 C 50/50 17.09 MW 17.09 MW
943742 AF1-042 E 50/50 27.89 MW 27.89 MW
961951 AG1-038 C 50/50 18.89 MW 18.89 MW
961952 AG1-038 E 50/50 26.09 MW 26.09 MW
966661 AG1-536 C 50/50 31.99 MW 31.99 MW
966662 AG1-536 E 50/50 42.98 MW 42.98 MW
962861 AG1-135 C 50/50 35.99 MW 35.99 MW
962862 AG1-135 E 50/50 23.99 MW 23.99 MW
962971 AG1-146 C 50/50 17.99 MW 17.99 MW
962972 AG1-146 E 50/50 11.99 MW 11.99 MW
962981 AG1-147 C 50/50 41.98 MW 41.98 MW
962982 AG1-147 E 50/50 27.99 MW 27.99 MW
316404 AE1-155 C 50/50 12.57 MW 12.57 MW
939246 AE1-155 E 50/50 51.78 MW 51.78 MW
958261 AF2-120 C 50/50 37.19 MW 37.19 MW
958262 AF2-120 E 50/50 24.79 MW 24.79 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.04 MW 0.04 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.27 MW 0.27 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1
Contingency Name:
DVP_P4-2: 574T581_SRT-S
CONTINGENCY 'DVP_P4-2: 574T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
END
Contingency Type: Breaker
DC|AC: AC
Final Cycle Loading: 104.31 %
Rating: 671.0 MVA
Rating Type: C
MVA to Mitigate: 699.94 MVA
MW Contribution: 13.04 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 50/50 1.01 MW 1.01 MW
315033 1BIRCHWDA 50/50 157.93 MW 157.93 MW
315034 1NORNECKC1 50/50 0.99 MW 0.99 MW
315035 1NORNECKC2 50/50 0.96 MW 0.96 MW
925865 AC1-065 E 50/50 11.06 MW 11.06 MW
926472 AC1-118 E 50/50 2.46 MW 2.46 MW
934392 AD1-063 E 50/50 0.72 MW 0.72 MW
936582 AD2-073 E 50/50 1.99 MW 1.99 MW
936591 AD2-074 C 50/50 6.23 MW 6.23 MW
936592 AD2-074 E 50/50 10.17 MW 10.17 MW
943741 AF1-042 C 50/50 3.26 MW 3.26 MW
943742 AF1-042 E 50/50 5.32 MW 5.32 MW
944491 AF1-114 C 50/50 21.14 MW 21.14 MW
944492 AF1-114 E 50/50 29.2 MW 29.2 MW
961951 AG1-038 C 50/50 3.6 MW 3.6 MW
961952 AG1-038 E 50/50 4.98 MW 4.98 MW
966661 AG1-536 C 50/50 6.73 MW 6.73 MW
966662 AG1-536 E 50/50 9.04 MW 9.04 MW
316077 AC2-138 C 50/50 0.33 MW 0.33 MW
316078 AC2-138 E 50/50 1.37 MW 1.37 MW
316156 AD2-030 C 50/50 0.27 MW 0.27 MW
316157 AD2-030 E 50/50 0.85 MW 0.85 MW
923842 AB2-024 E Adder 1.15 MW 0.98 MW
957601 AF2-054 C 50/50 1.51 MW 1.51 MW
957602 AF2-054 E 50/50 1.01 MW 1.01 MW
962861 AG1-135 C 50/50 7.4 MW 7.4 MW
962862 AG1-135 E 50/50 4.94 MW 4.94 MW
962971 AG1-146 C 50/50 3.23 MW 3.23 MW
962972 AG1-146 E 50/50 2.15 MW 2.15 MW
962981 AG1-147 C 50/50 7.53 MW 7.53 MW
962982 AG1-147 E 50/50 5.02 MW 5.02 MW
963611 AG1-210 C 50/50 0.98 MW 0.98 MW
963612 AG1-210 E 50/50 1.47 MW 1.47 MW
964211 AG1-282 C 50/50 2.74 MW 2.74 MW
964212 AG1-282 E 50/50 1.82 MW 1.82 MW
957832 AF2-077 E Adder 0.75 MW 0.64 MW
957971 AF2-091 C 50/50 7.19 MW 7.19 MW
957972 AF2-091 E 50/50 9.93 MW 9.93 MW
314181 3NORNECK 50/50 1.3 MW 1.3 MW
313053 6PAPERMILL Adder 4.29 MW 3.65 MW
316059 AD1-063 C 50/50 0.17 MW 0.17 MW
939611 AE1-191 C 50/50 0.94 MW 0.94 MW
939612 AE1-191 E 50/50 3.91 MW 3.91 MW
316201 AC1-065 C 50/50 1.08 MW 1.08 MW
316223 AC1-118 C 50/50 0.78 MW 0.78 MW
316337 AD2-073 C 50/50 0.65 MW 0.65 MW
316404 AE1-155 C 50/50 2.64 MW 2.64 MW
939246 AE1-155 E 50/50 10.89 MW 10.89 MW
316280 AD1-041 C 50/50 0.59 MW 0.59 MW
934146 AD1-041 E 50/50 2.44 MW 2.44 MW
958261 AF2-120 C 50/50 7.82 MW 7.82 MW
958262 AF2-120 E 50/50 5.21 MW 5.21 MW
939601 AE1-190 C 50/50 0.23 MW 0.23 MW
939602 AE1-190 E 50/50 0.98 MW 0.98 MW
940551 AE2-041 C 50/50 4.78 MW 4.78 MW
943471 AF1-018 C 50/50 4.78 MW 4.78 MW
957191 AF2-013 C 50/50 65.46 MW 65.46 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 8.19 MW 8.19 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 5.02 MW 5.02 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 17.53 MW 17.53 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.11 MW 1.11 MW
NY PJM->LTFIMP_NY CLTF 0.5 MW 0.5 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.33 MW 0.33 MW
WEC LTFEXP_WEC->PJM CLTF 0.17 MW 0.17 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.02 MW 2.02 MW
TVA LTFEXP_TVA->PJM CLTF 1.3 MW 1.3 MW
MEC LTFEXP_MEC->PJM CLTF 0.96 MW 0.96 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.63 MW 1.63 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.06 MW 0.06 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 7.07 MW 7.07 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.96 MW 0.96 MW

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1
Contingency Name:
DVP_P4-2: 574T581_SRT-S
CONTINGENCY 'DVP_P4-2: 574T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
END
Contingency Type: Breaker
DC|AC: AC
Final Cycle Loading: 104.28 %
Rating: 671.0 MVA
Rating Type: C
MVA to Mitigate: 699.73 MVA
MW Contribution: 13.04 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 50/50 1.01 MW 1.01 MW
315033 1BIRCHWDA 50/50 157.93 MW 157.93 MW
315034 1NORNECKC1 50/50 0.99 MW 0.99 MW
315035 1NORNECKC2 50/50 0.96 MW 0.96 MW
925865 AC1-065 E 50/50 11.06 MW 11.06 MW
926472 AC1-118 E 50/50 2.46 MW 2.46 MW
934392 AD1-063 E 50/50 0.72 MW 0.72 MW
936582 AD2-073 E 50/50 1.99 MW 1.99 MW
936591 AD2-074 C 50/50 6.23 MW 6.23 MW
936592 AD2-074 E 50/50 10.17 MW 10.17 MW
943741 AF1-042 C 50/50 3.26 MW 3.26 MW
943742 AF1-042 E 50/50 5.32 MW 5.32 MW
944491 AF1-114 C 50/50 21.14 MW 21.14 MW
944492 AF1-114 E 50/50 29.2 MW 29.2 MW
961951 AG1-038 C 50/50 3.6 MW 3.6 MW
961952 AG1-038 E 50/50 4.98 MW 4.98 MW
966661 AG1-536 C 50/50 6.73 MW 6.73 MW
966662 AG1-536 E 50/50 9.04 MW 9.04 MW
316077 AC2-138 C 50/50 0.33 MW 0.33 MW
316078 AC2-138 E 50/50 1.37 MW 1.37 MW
316156 AD2-030 C 50/50 0.27 MW 0.27 MW
316157 AD2-030 E 50/50 0.85 MW 0.85 MW
923842 AB2-024 E Adder 1.15 MW 0.98 MW
957601 AF2-054 C 50/50 1.51 MW 1.51 MW
957602 AF2-054 E 50/50 1.01 MW 1.01 MW
962861 AG1-135 C 50/50 7.4 MW 7.4 MW
962862 AG1-135 E 50/50 4.94 MW 4.94 MW
962971 AG1-146 C 50/50 3.23 MW 3.23 MW
962972 AG1-146 E 50/50 2.15 MW 2.15 MW
962981 AG1-147 C 50/50 7.53 MW 7.53 MW
962982 AG1-147 E 50/50 5.02 MW 5.02 MW
963611 AG1-210 C 50/50 0.98 MW 0.98 MW
963612 AG1-210 E 50/50 1.47 MW 1.47 MW
964211 AG1-282 C 50/50 2.74 MW 2.74 MW
964212 AG1-282 E 50/50 1.82 MW 1.82 MW
957832 AF2-077 E Adder 0.75 MW 0.64 MW
957971 AF2-091 C 50/50 7.19 MW 7.19 MW
957972 AF2-091 E 50/50 9.93 MW 9.93 MW
314181 3NORNECK 50/50 1.3 MW 1.3 MW
313053 6PAPERMILL Adder 4.29 MW 3.65 MW
316059 AD1-063 C 50/50 0.17 MW 0.17 MW
939611 AE1-191 C 50/50 0.94 MW 0.94 MW
939612 AE1-191 E 50/50 3.91 MW 3.91 MW
316201 AC1-065 C 50/50 1.08 MW 1.08 MW
316223 AC1-118 C 50/50 0.78 MW 0.78 MW
316337 AD2-073 C 50/50 0.65 MW 0.65 MW
316404 AE1-155 C 50/50 2.64 MW 2.64 MW
939246 AE1-155 E 50/50 10.89 MW 10.89 MW
316280 AD1-041 C 50/50 0.59 MW 0.59 MW
934146 AD1-041 E 50/50 2.44 MW 2.44 MW
958261 AF2-120 C 50/50 7.82 MW 7.82 MW
958262 AF2-120 E 50/50 5.21 MW 5.21 MW
939601 AE1-190 C 50/50 0.23 MW 0.23 MW
939602 AE1-190 E 50/50 0.98 MW 0.98 MW
940551 AE2-041 C 50/50 4.78 MW 4.78 MW
943471 AF1-018 C 50/50 4.78 MW 4.78 MW
957191 AF2-013 C 50/50 65.46 MW 65.46 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 8.19 MW 8.19 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 5.02 MW 5.02 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 17.53 MW 17.53 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.11 MW 1.11 MW
NY PJM->LTFIMP_NY CLTF 0.5 MW 0.5 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.33 MW 0.33 MW
WEC LTFEXP_WEC->PJM CLTF 0.17 MW 0.17 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.02 MW 2.02 MW
TVA LTFEXP_TVA->PJM CLTF 1.3 MW 1.3 MW
MEC LTFEXP_MEC->PJM CLTF 0.96 MW 0.96 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.63 MW 1.63 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.06 MW 0.06 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 7.07 MW 7.07 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.96 MW 0.96 MW

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1
Contingency Name:
DVP_P4-2: H1T574_SRT-S
CONTINGENCY 'DVP_P4-2: H1T574_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
END
Contingency Type: Breaker
DC|AC: AC
Final Cycle Loading: 104.24 %
Rating: 671.0 MVA
Rating Type: C
MVA to Mitigate: 699.42 MVA
MW Contribution: 13.03 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 50/50 1.01 MW 1.01 MW
315033 1BIRCHWDA 50/50 157.9 MW 157.9 MW
315034 1NORNECKC1 50/50 0.99 MW 0.99 MW
315035 1NORNECKC2 50/50 0.95 MW 0.95 MW
925865 AC1-065 E 50/50 11.04 MW 11.04 MW
926472 AC1-118 E 50/50 2.46 MW 2.46 MW
934392 AD1-063 E 50/50 0.72 MW 0.72 MW
936582 AD2-073 E 50/50 1.99 MW 1.99 MW
936591 AD2-074 C 50/50 6.23 MW 6.23 MW
936592 AD2-074 E 50/50 10.16 MW 10.16 MW
943741 AF1-042 C 50/50 3.26 MW 3.26 MW
943742 AF1-042 E 50/50 5.32 MW 5.32 MW
944491 AF1-114 C 50/50 21.14 MW 21.14 MW
944492 AF1-114 E 50/50 29.19 MW 29.19 MW
961951 AG1-038 C 50/50 3.6 MW 3.6 MW
961952 AG1-038 E 50/50 4.97 MW 4.97 MW
966661 AG1-536 C 50/50 6.72 MW 6.72 MW
966662 AG1-536 E 50/50 9.04 MW 9.04 MW
316077 AC2-138 C 50/50 0.33 MW 0.33 MW
316078 AC2-138 E 50/50 1.37 MW 1.37 MW
316156 AD2-030 C 50/50 0.27 MW 0.27 MW
316157 AD2-030 E 50/50 0.85 MW 0.85 MW
923842 AB2-024 E Adder 1.15 MW 0.98 MW
957601 AF2-054 C 50/50 1.51 MW 1.51 MW
957602 AF2-054 E 50/50 1.01 MW 1.01 MW
962861 AG1-135 C 50/50 7.4 MW 7.4 MW
962862 AG1-135 E 50/50 4.93 MW 4.93 MW
962971 AG1-146 C 50/50 3.23 MW 3.23 MW
962972 AG1-146 E 50/50 2.15 MW 2.15 MW
962981 AG1-147 C 50/50 7.53 MW 7.53 MW
962982 AG1-147 E 50/50 5.02 MW 5.02 MW
963611 AG1-210 C 50/50 0.98 MW 0.98 MW
963612 AG1-210 E 50/50 1.47 MW 1.47 MW
964211 AG1-282 C 50/50 2.73 MW 2.73 MW
964212 AG1-282 E 50/50 1.82 MW 1.82 MW
957832 AF2-077 E Adder 0.75 MW 0.64 MW
957971 AF2-091 C 50/50 7.19 MW 7.19 MW
957972 AF2-091 E 50/50 9.93 MW 9.93 MW
314181 3NORNECK 50/50 1.3 MW 1.3 MW
313053 6PAPERMILL Adder 4.28 MW 3.64 MW
316059 AD1-063 C 50/50 0.17 MW 0.17 MW
939611 AE1-191 C 50/50 0.94 MW 0.94 MW
939612 AE1-191 E 50/50 3.9 MW 3.9 MW
316201 AC1-065 C 50/50 1.08 MW 1.08 MW
316223 AC1-118 C 50/50 0.78 MW 0.78 MW
316337 AD2-073 C 50/50 0.65 MW 0.65 MW
316404 AE1-155 C 50/50 2.64 MW 2.64 MW
939246 AE1-155 E 50/50 10.89 MW 10.89 MW
316280 AD1-041 C 50/50 0.59 MW 0.59 MW
934146 AD1-041 E 50/50 2.44 MW 2.44 MW
958261 AF2-120 C 50/50 7.82 MW 7.82 MW
958262 AF2-120 E 50/50 5.21 MW 5.21 MW
939601 AE1-190 C 50/50 0.23 MW 0.23 MW
939602 AE1-190 E 50/50 0.98 MW 0.98 MW
940551 AE2-041 C 50/50 4.77 MW 4.77 MW
943471 AF1-018 C 50/50 4.77 MW 4.77 MW
957191 AF2-013 C 50/50 65.44 MW 65.44 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 8.2 MW 8.2 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 5.02 MW 5.02 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 17.51 MW 17.51 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.11 MW 1.11 MW
NY PJM->LTFIMP_NY CLTF 0.5 MW 0.5 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.33 MW 0.33 MW
WEC LTFEXP_WEC->PJM CLTF 0.17 MW 0.17 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.02 MW 2.02 MW
TVA LTFEXP_TVA->PJM CLTF 1.3 MW 1.3 MW
MEC LTFEXP_MEC->PJM CLTF 0.96 MW 0.96 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.63 MW 1.63 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.06 MW 0.06 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 7.06 MW 7.06 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.96 MW 0.96 MW

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1
Contingency Name:
DVP_P4-2: H1T574_SRT-S
CONTINGENCY 'DVP_P4-2: H1T574_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
END
Contingency Type: Breaker
DC|AC: AC
Final Cycle Loading: 104.2 %
Rating: 671.0 MVA
Rating Type: C
MVA to Mitigate: 699.18 MVA
MW Contribution: 13.03 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 50/50 1.01 MW 1.01 MW
315033 1BIRCHWDA 50/50 157.9 MW 157.9 MW
315034 1NORNECKC1 50/50 0.99 MW 0.99 MW
315035 1NORNECKC2 50/50 0.95 MW 0.95 MW
925865 AC1-065 E 50/50 11.04 MW 11.04 MW
926472 AC1-118 E 50/50 2.46 MW 2.46 MW
934392 AD1-063 E 50/50 0.72 MW 0.72 MW
936582 AD2-073 E 50/50 1.99 MW 1.99 MW
936591 AD2-074 C 50/50 6.23 MW 6.23 MW
936592 AD2-074 E 50/50 10.16 MW 10.16 MW
943741 AF1-042 C 50/50 3.26 MW 3.26 MW
943742 AF1-042 E 50/50 5.32 MW 5.32 MW
944491 AF1-114 C 50/50 21.14 MW 21.14 MW
944492 AF1-114 E 50/50 29.19 MW 29.19 MW
961951 AG1-038 C 50/50 3.6 MW 3.6 MW
961952 AG1-038 E 50/50 4.97 MW 4.97 MW
966661 AG1-536 C 50/50 6.72 MW 6.72 MW
966662 AG1-536 E 50/50 9.04 MW 9.04 MW
316077 AC2-138 C 50/50 0.33 MW 0.33 MW
316078 AC2-138 E 50/50 1.37 MW 1.37 MW
316156 AD2-030 C 50/50 0.27 MW 0.27 MW
316157 AD2-030 E 50/50 0.85 MW 0.85 MW
923842 AB2-024 E Adder 1.15 MW 0.98 MW
957601 AF2-054 C 50/50 1.51 MW 1.51 MW
957602 AF2-054 E 50/50 1.01 MW 1.01 MW
962861 AG1-135 C 50/50 7.4 MW 7.4 MW
962862 AG1-135 E 50/50 4.93 MW 4.93 MW
962971 AG1-146 C 50/50 3.23 MW 3.23 MW
962972 AG1-146 E 50/50 2.15 MW 2.15 MW
962981 AG1-147 C 50/50 7.53 MW 7.53 MW
962982 AG1-147 E 50/50 5.02 MW 5.02 MW
963611 AG1-210 C 50/50 0.98 MW 0.98 MW
963612 AG1-210 E 50/50 1.47 MW 1.47 MW
964211 AG1-282 C 50/50 2.73 MW 2.73 MW
964212 AG1-282 E 50/50 1.82 MW 1.82 MW
957832 AF2-077 E Adder 0.75 MW 0.64 MW
957971 AF2-091 C 50/50 7.19 MW 7.19 MW
957972 AF2-091 E 50/50 9.93 MW 9.93 MW
314181 3NORNECK 50/50 1.3 MW 1.3 MW
313053 6PAPERMILL Adder 4.28 MW 3.64 MW
316059 AD1-063 C 50/50 0.17 MW 0.17 MW
939611 AE1-191 C 50/50 0.94 MW 0.94 MW
939612 AE1-191 E 50/50 3.9 MW 3.9 MW
316201 AC1-065 C 50/50 1.08 MW 1.08 MW
316223 AC1-118 C 50/50 0.78 MW 0.78 MW
316337 AD2-073 C 50/50 0.65 MW 0.65 MW
316404 AE1-155 C 50/50 2.64 MW 2.64 MW
939246 AE1-155 E 50/50 10.89 MW 10.89 MW
316280 AD1-041 C 50/50 0.59 MW 0.59 MW
934146 AD1-041 E 50/50 2.44 MW 2.44 MW
958261 AF2-120 C 50/50 7.82 MW 7.82 MW
958262 AF2-120 E 50/50 5.21 MW 5.21 MW
939601 AE1-190 C 50/50 0.23 MW 0.23 MW
939602 AE1-190 E 50/50 0.98 MW 0.98 MW
940551 AE2-041 C 50/50 4.77 MW 4.77 MW
943471 AF1-018 C 50/50 4.77 MW 4.77 MW
957191 AF2-013 C 50/50 65.44 MW 65.44 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 8.2 MW 8.2 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 5.02 MW 5.02 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 17.51 MW 17.51 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.11 MW 1.11 MW
NY PJM->LTFIMP_NY CLTF 0.5 MW 0.5 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.33 MW 0.33 MW
WEC LTFEXP_WEC->PJM CLTF 0.17 MW 0.17 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.02 MW 2.02 MW
TVA LTFEXP_TVA->PJM CLTF 1.3 MW 1.3 MW
MEC LTFEXP_MEC->PJM CLTF 0.96 MW 0.96 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.63 MW 1.63 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.06 MW 0.06 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 7.06 MW 7.06 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.96 MW 0.96 MW

Details for 3WAN 89-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2016-85_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
3WAN 89-3WHITEMARSH 115.0 kV Ckt 1 line
313284 to 313828 ckt 1
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-2
CONTINGENCY 'DVP_P7-1: LN 2016-85_SRT-A-2'
 OPEN BRANCH FROM BUS 313053 TO BUS 314189 CKT 1   /*6PAPERMILL   230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1   /*3HARMONY     115.0 - 6HARMONY     230.0
 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1   /*6HARMONY     230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314184 TO BUS 314188 CKT 1   /*3SHACKLE     115.0 - 3WEST PT     115.0
 OPEN BRANCH FROM BUS 314184 TO BUS 316275 CKT 1   /*3SHACKLE     115.0 - AD1-041 TAP  115.0
 OPEN BRANCH FROM BUS 314188 TO BUS 314387 CKT 1   /*3WEST PT     115.0 - 3LANEXA      115.0
 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1   /*6PAPERMIL TP 230.0 - 6CORRCTN     230.0
 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1   /*6CORRCTN     230.0 - 6LANEXA      230.0
 OPEN BUS 313053                                   /*6PAPERMILL   230.0
 OPEN BUS 313846                                   /*6HARMONY_1   230.0
 OPEN BUS 314176                                   /*6HARMONY     230.0
 OPEN BUS 314184                                   /*3SHACKLE     115.0
 OPEN BUS 314188                                   /*3WEST PT     115.0
 OPEN BUS 314189                                   /*6PAPERMIL TP 230.0
 OPEN BUS 314375                                   /*6CORRCTN     230.0
END
Contingency Type: Tower
DC|AC: AC
Final Cycle Loading: 114.88 %
Rating: 208.0 MVA
Rating Type: C
MVA to Mitigate: 238.95 MVA
MW Contribution: 15.44 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
315034 1NORNECKC1 50/50 0.48 MW 0.48 MW
315035 1NORNECKC2 50/50 0.47 MW 0.47 MW
936591 AD2-074 C 50/50 10.56 MW 10.56 MW
936592 AD2-074 E 50/50 17.24 MW 17.24 MW
943741 AF1-042 C 50/50 5.53 MW 5.53 MW
943742 AF1-042 E 50/50 9.02 MW 9.02 MW
961951 AG1-038 C 50/50 6.11 MW 6.11 MW
961952 AG1-038 E 50/50 8.44 MW 8.44 MW
966661 AG1-536 C 50/50 7.97 MW 7.97 MW
966662 AG1-536 E 50/50 10.71 MW 10.71 MW
316077 AC2-138 C 50/50 0.16 MW 0.16 MW
316078 AC2-138 E 50/50 0.67 MW 0.67 MW
316156 AD2-030 C 50/50 1.21 MW 1.21 MW
316157 AD2-030 E 50/50 3.79 MW 3.79 MW
957601 AF2-054 C 50/50 6.75 MW 6.75 MW
957602 AF2-054 E 50/50 4.5 MW 4.5 MW
962861 AG1-135 C 50/50 9.59 MW 9.59 MW
962862 AG1-135 E 50/50 6.39 MW 6.39 MW
962971 AG1-146 C 50/50 6.6 MW 6.6 MW
962972 AG1-146 E 50/50 4.4 MW 4.4 MW
962981 AG1-147 C 50/50 15.39 MW 15.39 MW
962982 AG1-147 E 50/50 10.26 MW 10.26 MW
963611 AG1-210 C 50/50 0.48 MW 0.48 MW
963612 AG1-210 E 50/50 0.71 MW 0.71 MW
314181 3NORNECK 50/50 0.63 MW 0.63 MW
939611 AE1-191 C 50/50 4.34 MW 4.34 MW
939612 AE1-191 E 50/50 18.09 MW 18.09 MW
316404 AE1-155 C 50/50 3.13 MW 3.13 MW
939246 AE1-155 E 50/50 12.89 MW 12.89 MW
316280 AD1-041 C 50/50 2.75 MW 2.75 MW
934146 AD1-041 E 50/50 11.31 MW 11.31 MW
958261 AF2-120 C 50/50 9.26 MW 9.26 MW
958262 AF2-120 E 50/50 6.17 MW 6.17 MW
939601 AE1-190 C 50/50 1.08 MW 1.08 MW
939602 AE1-190 E 50/50 4.52 MW 4.52 MW
CBM North LTFEXP_CBM-N->PJM CBM 0.02 MW 0.02 MW
G-007A LTFEXP_G-007A->PJM CMTX 0.06 MW 0.06 MW
VTF LTFEXP_VFT->PJM CMTX 0.15 MW 0.15 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.24 MW 0.24 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.12 MW 0.12 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.06 MW 0.06 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.23 MW 0.23 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.04 MW 0.04 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.14 MW 0.14 MW
MDU PJM->LTFIMP_MDU CLTF 0.01 MW 0.01 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.08 MW 0.08 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.18 MW 0.18 MW

Details for 3WHITEMARSH-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2016-85_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
3WHITEMARSH-3HAYES89 115.0 kV Ckt 1 line
313828 to 314177 ckt 1
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-2
CONTINGENCY 'DVP_P7-1: LN 2016-85_SRT-A-2'
 OPEN BRANCH FROM BUS 313053 TO BUS 314189 CKT 1   /*6PAPERMILL   230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1   /*3HARMONY     115.0 - 6HARMONY     230.0
 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1   /*6HARMONY     230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314184 TO BUS 314188 CKT 1   /*3SHACKLE     115.0 - 3WEST PT     115.0
 OPEN BRANCH FROM BUS 314184 TO BUS 316275 CKT 1   /*3SHACKLE     115.0 - AD1-041 TAP  115.0
 OPEN BRANCH FROM BUS 314188 TO BUS 314387 CKT 1   /*3WEST PT     115.0 - 3LANEXA      115.0
 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1   /*6PAPERMIL TP 230.0 - 6CORRCTN     230.0
 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1   /*6CORRCTN     230.0 - 6LANEXA      230.0
 OPEN BUS 313053                                   /*6PAPERMILL   230.0
 OPEN BUS 313846                                   /*6HARMONY_1   230.0
 OPEN BUS 314176                                   /*6HARMONY     230.0
 OPEN BUS 314184                                   /*3SHACKLE     115.0
 OPEN BUS 314188                                   /*3WEST PT     115.0
 OPEN BUS 314189                                   /*6PAPERMIL TP 230.0
 OPEN BUS 314375                                   /*6CORRCTN     230.0
END
Contingency Type: Tower
DC|AC: AC
Final Cycle Loading: 111.93 %
Rating: 208.0 MVA
Rating Type: C
MVA to Mitigate: 232.81 MVA
MW Contribution: 15.43 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
315034 1NORNECKC1 50/50 0.48 MW 0.48 MW
315035 1NORNECKC2 50/50 0.47 MW 0.47 MW
936591 AD2-074 C 50/50 10.56 MW 10.56 MW
936592 AD2-074 E 50/50 17.23 MW 17.23 MW
943741 AF1-042 C 50/50 5.53 MW 5.53 MW
943742 AF1-042 E 50/50 9.02 MW 9.02 MW
961951 AG1-038 C 50/50 6.11 MW 6.11 MW
961952 AG1-038 E 50/50 8.44 MW 8.44 MW
966661 AG1-536 C 50/50 7.96 MW 7.96 MW
966662 AG1-536 E 50/50 10.7 MW 10.7 MW
316077 AC2-138 C 50/50 0.16 MW 0.16 MW
316078 AC2-138 E 50/50 0.67 MW 0.67 MW
316156 AD2-030 C 50/50 1.21 MW 1.21 MW
316157 AD2-030 E 50/50 3.79 MW 3.79 MW
957601 AF2-054 C 50/50 6.75 MW 6.75 MW
957602 AF2-054 E 50/50 4.5 MW 4.5 MW
962861 AG1-135 C 50/50 9.59 MW 9.59 MW
962862 AG1-135 E 50/50 6.39 MW 6.39 MW
962971 AG1-146 C 50/50 6.59 MW 6.59 MW
962972 AG1-146 E 50/50 4.4 MW 4.4 MW
962981 AG1-147 C 50/50 15.39 MW 15.39 MW
962982 AG1-147 E 50/50 10.26 MW 10.26 MW
963611 AG1-210 C 50/50 0.48 MW 0.48 MW
963612 AG1-210 E 50/50 0.71 MW 0.71 MW
957831 AF2-077 C 50/50 1.44 MW 1.44 MW
957832 AF2-077 E 50/50 6.25 MW 6.25 MW
314181 3NORNECK 50/50 0.63 MW 0.63 MW
939611 AE1-191 C 50/50 4.34 MW 4.34 MW
939612 AE1-191 E 50/50 18.09 MW 18.09 MW
316404 AE1-155 C 50/50 3.13 MW 3.13 MW
939246 AE1-155 E 50/50 12.89 MW 12.89 MW
316280 AD1-041 C 50/50 2.75 MW 2.75 MW
934146 AD1-041 E 50/50 11.31 MW 11.31 MW
958261 AF2-120 C 50/50 9.26 MW 9.26 MW
958262 AF2-120 E 50/50 6.17 MW 6.17 MW
939601 AE1-190 C 50/50 1.08 MW 1.08 MW
939602 AE1-190 E 50/50 4.52 MW 4.52 MW
CBM North LTFEXP_CBM-N->PJM CBM 0.01 MW 0.01 MW
G-007A LTFEXP_G-007A->PJM CMTX 0.04 MW 0.04 MW
VTF LTFEXP_VFT->PJM CMTX 0.11 MW 0.11 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.25 MW 0.25 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.13 MW 0.13 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.07 MW 0.07 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.25 MW 0.25 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.05 MW 0.05 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.15 MW 0.15 MW
MDU PJM->LTFIMP_MDU CLTF 0.01 MW 0.01 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.09 MW 0.09 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.18 MW 0.18 MW

Details for 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
8OX-8CLIFTON 500.0 kV Ckt 1 line
314919 to 314904 ckt 1
Contingency Name:
DVP_P7-1: LN 2101-569_SRT-S
CONTINGENCY 'DVP_P7-1: LN 2101-569_SRT-S'
 OPEN BRANCH FROM BUS 313712 TO BUS 313716 CKT 1                /*6VINTHIL TP  230.0 - 6VINTHIL DP  230.0
 OPEN BRANCH FROM BUS 313712 TO BUS 314119 CKT 1                /*6VINTHIL TP  230.0 - 6NOKESVL     230.0
 OPEN BRANCH FROM BUS 313712 TO BUS 314125 CKT 1                /*6VINTHIL TP  230.0 - 6VINTHIL     230.0
 OPEN BRANCH FROM BUS 314119 TO BUS 314130 CKT 1                /*6NOKESVL     230.0 - 6BRISTER     230.0
 OPEN BRANCH FROM BUS 314913 TO BUS 314916 CKT 1                /*8LOUDOUN     500.0 - 8MORRSVL     500.0
 OPEN BUS 313712                                                /*6VINTHIL TP  230.0
 OPEN BUS 313716                                                /*6VINTHIL DP  230.0
 OPEN BUS 314119                                                /*6NOKESVL     230.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
Contingency Type: Tower
DC|AC: AC
Final Cycle Loading: 105.67 %
Rating: 3144.0 MVA
Rating Type: C
MVA to Mitigate: 3322.12 MVA
MW Contribution: 7.88 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314331 6POE Adder 0.89 MW 0.76 MW
314507 3THOMPSN Adder 1.32 MW 1.12 MW
314525 6KINGFORK Adder 0.67 MW 0.57 MW
314550 6HICKORY Adder 1.42 MW 1.21 MW
315007 1POSSM 5 Adder 93.74 MW 79.68 MW
315008 1POSSM6A 50/50 3.71 MW 3.71 MW
315009 1POSSM6B 50/50 3.71 MW 3.71 MW
315010 1POSSM6S 50/50 5.78 MW 5.78 MW
315018 1POSSMC2 50/50 0.82 MW 0.82 MW
315033 1BIRCHWDA Adder 28.44 MW 24.18 MW
315039 1LDYSMT3 50/50 3.92 MW 3.92 MW
315040 1LDYSMT4 50/50 3.93 MW 3.93 MW
315041 1LDYSMT5 50/50 3.94 MW 3.94 MW
315060 1CHESTF5 Adder 43.4 MW 36.89 MW
315065 1CHESTF6 Adder 13.28 MW 11.29 MW
315073 1STONECA Adder 4.68 MW 3.98 MW
315083 1SPRUNCA Adder 6.19 MW 5.26 MW
315084 1SPRUNCB Adder 6.19 MW 5.26 MW
315092 1YORKTN3 Adder 89.33 MW 75.93 MW
925865 AC1-065 E Adder 11.66 MW 9.91 MW
926412 AC1-112 E Adder 0.78 MW 0.66 MW
926472 AC1-118 E Adder 0.89 MW 0.76 MW
926662 AC1-147 E Adder 0.87 MW 0.74 MW
926755 AC1-161 E Adder 8.49 MW 7.22 MW
927226 AC1-216 E Adder 5.19 MW 4.41 MW
934392 AD1-063 E Adder 0.75 MW 0.64 MW
934782 AD1-105 E Adder 3.92 MW 3.33 MW
935112 AD1-144 E Adder 0.62 MW 0.53 MW
936582 AD2-073 E Adder 0.86 MW 0.73 MW
936591 AD2-074 C Adder 4.14 MW 3.52 MW
936592 AD2-074 E Adder 6.75 MW 5.74 MW
942341 AE2-247 C Adder 0.97 MW 0.83 MW
942342 AE2-247 E Adder 1.34 MW 1.14 MW
943461 AF1-017 C Adder 0.88 MW 0.75 MW
943462 AF1-017 E Adder 1.44 MW 1.22 MW
943612 AF1-032 E Adder 0.6 MW 0.51 MW
943741 AF1-042 C Adder 2.17 MW 1.84 MW
943742 AF1-042 E Adder 3.53 MW 3.0 MW
944491 AF1-114 C Adder 5.64 MW 4.79 MW
944492 AF1-114 E Adder 7.78 MW 6.62 MW
961951 AG1-038 C Adder 2.39 MW 2.03 MW
961952 AG1-038 E Adder 3.3 MW 2.81 MW
966661 AG1-536 C Adder 4.07 MW 3.46 MW
966662 AG1-536 E Adder 5.47 MW 4.65 MW
966871 AG1-558 C Adder 1.71 MW 1.46 MW
966872 AG1-558 E Adder 0.86 MW 0.73 MW
966881 AG1-559 C 50/50 1.9 MW 1.9 MW
966882 AG1-559 E 50/50 0.96 MW 0.96 MW
315225 1N ANNA1 50/50 23.22 MW 23.22 MW
315226 1N ANNA2 50/50 23.23 MW 23.23 MW
315260 1GOSPORTA Adder 1.39 MW 1.19 MW
315261 1GOSPORTB Adder 1.78 MW 1.51 MW
315262 1GOSPORTC Adder 1.51 MW 1.28 MW
316076 AC2-137 E Adder 0.92 MW 0.78 MW
316078 AC2-138 E Adder 0.72 MW 0.61 MW
316157 AD2-030 E Adder 0.84 MW 0.71 MW
916192 Z1-068 E Adder 1.23 MW 1.04 MW
923842 AB2-024 E Adder 1.25 MW 1.06 MW
925022 AB2-158 E Adder 3.34 MW 2.84 MW
930122 AB1-027 E Adder 0.95 MW 0.81 MW
938552 AE1-074 E Adder 0.83 MW 0.7 MW
939312 AE1-162 E Adder 0.95 MW 0.81 MW
946262 AF1-291 E Adder 0.97 MW 0.82 MW
957411 AF2-035 C 50/50 6.87 MW 6.87 MW
957412 AF2-035 E 50/50 3.43 MW 3.43 MW
957492 AF2-043 E Adder 0.92 MW 0.79 MW
957601 AF2-054 C Adder 1.49 MW 1.27 MW
957602 AF2-054 E Adder 0.99 MW 0.84 MW
962861 AG1-135 C Adder 4.57 MW 3.89 MW
962862 AG1-135 E Adder 3.05 MW 2.59 MW
962962 AG1-145 E Adder 0.98 MW 0.83 MW
962971 AG1-146 C Adder 2.27 MW 1.93 MW
962972 AG1-146 E Adder 1.52 MW 1.29 MW
962981 AG1-147 C Adder 5.31 MW 4.51 MW
962982 AG1-147 E Adder 3.54 MW 3.01 MW
963051 AG1-154 C 50/50 3.01 MW 3.01 MW
963052 AG1-154 E 50/50 4.52 MW 4.52 MW
963611 AG1-210 C Adder 0.51 MW 0.44 MW
963612 AG1-210 E Adder 0.77 MW 0.65 MW
964211 AG1-282 C Adder 1.53 MW 1.3 MW
964212 AG1-282 E Adder 1.02 MW 0.87 MW
925332 AB2-190 E Adder 5.45 MW 4.63 MW
925522 AC1-027 E Adder 0.8 MW 0.68 MW
942001 AE2-212 C Adder 1.44 MW 1.23 MW
942002 AE2-212 E Adder 0.96 MW 0.82 MW
957832 AF2-077 E Adder 0.98 MW 0.83 MW
957871 AF2-081 C Adder 6.48 MW 5.51 MW
957872 AF2-081 E Adder 2.78 MW 2.36 MW
957971 AF2-091 C Adder 1.92 MW 1.63 MW
957972 AF2-091 E Adder 2.65 MW 2.25 MW
313811 6ELKO L286 Adder 0.96 MW 0.81 MW
314181 3NORNECK Adder 0.68 MW 0.58 MW
933291 AC2-141 C Adder 19.9 MW 16.91 MW
933292 AC2-141 E Adder 8.49 MW 7.22 MW
939411 AE1-173 C Adder 55.53 MW 47.2 MW
939412 AE1-173 E Adder 37.02 MW 31.46 MW
934012 AD1-025 E Adder 6.72 MW 5.71 MW
927041 AC1-191 C Adder 6.88 MW 5.85 MW
927042 AC1-191 E Adder 3.43 MW 2.92 MW
313053 6PAPERMILL Adder 4.63 MW 3.94 MW
314632 6AYDLETT TAP Adder 0.88 MW 0.75 MW
316160 AE1-175 E Adder 0.81 MW 0.69 MW
316169 AC1-164 GEN Adder 27.66 MW 23.52 MW
316170 AC1-121 C Adder 1.59 MW 1.35 MW
316233 AE1-074 C Adder 1.64 MW 1.4 MW
316240 AF1-291 C Adder 1.46 MW 1.24 MW
316254 AC1-120 C Adder 4.62 MW 3.93 MW
926785 AC1-164_E Adder 12.43 MW 10.56 MW
934065 AD1-033 E Adder 3.27 MW 2.78 MW
937226 AE2-253 E Adder 3.8 MW 3.23 MW
939612 AE1-191 E Adder 4.0 MW 3.4 MW
926004 AC1-076_E Adder 2.94 MW 2.5 MW
926486 AC1-120 E Adder 2.38 MW 2.02 MW
926502 AC1-121 E Adder 0.75 MW 0.64 MW
315037 1LDYSMT1 50/50 3.77 MW 3.77 MW
315038 1LDYSMT2 50/50 3.82 MW 3.82 MW
316411 AF1-147_GEN1 Adder -5.71 MW -4.85 MW
316415 AF1-147_GEN2 Adder -5.71 MW -4.85 MW
939246 AE1-155 E Adder 6.59 MW 5.6 MW
919153 AA1-139 E2 Adder 2.65 MW 2.25 MW
919152 AA1-139 E1 Adder 2.65 MW 2.25 MW
924814 AB2-134 E Adder 8.51 MW 7.23 MW
316084 AB2-161 E Adder 3.64 MW 3.09 MW
316044 AC1-158 C1 50/50 4.24 MW 4.24 MW
316045 AC1-158 C2 50/50 4.24 MW 4.24 MW
926739 AC1-158 E1 50/50 11.09 MW 11.09 MW
926740 AC1-158 E2 50/50 11.09 MW 11.09 MW
932046 AC2-012 E Adder 8.58 MW 7.29 MW
316311 AC2-079 C Adder 3.74 MW 3.18 MW
932596 AC2-079 E Adder 6.1 MW 5.19 MW
934146 AD1-041 E Adder 2.5 MW 2.12 MW
934576 AD1-082 E Adder 2.9 MW 2.46 MW
316349 AD2-085 C Adder 2.25 MW 1.91 MW
936666 AD2-085 E Adder 3.67 MW 3.12 MW
961611 AG1-000B C Adder 10.65 MW 9.05 MW
941591 AE2-156 C Adder 11.72 MW 9.96 MW
944581 AF1-123 C Adder 29.65 MW 25.2 MW
944582 AF1-123 E Adder 67.89 MW 57.7 MW
944591 AF1-124 C Adder 29.75 MW 25.29 MW
944592 AF1-124 E Adder 68.13 MW 57.91 MW
944601 AF1-125 C Adder 29.19 MW 24.81 MW
944602 AF1-125 E Adder 66.82 MW 56.8 MW
944631 AF1-128 C Adder 27.16 MW 23.09 MW
958261 AF2-120 C Adder 4.73 MW 4.02 MW
958262 AF2-120 E Adder 3.15 MW 2.68 MW
965281 AG1-393 C Adder 1.45 MW 1.23 MW
965282 AG1-393 E Adder 0.97 MW 0.82 MW
935161 AD1-151 C Adder 10.87 MW 9.24 MW
935162 AD1-151 E Adder 7.25 MW 6.16 MW
938531 AE1-072 C Adder 11.39 MW 9.68 MW
938532 AE1-072 E Adder 5.94 MW 5.05 MW
939191 AE1-149 C Adder 7.11 MW 6.04 MW
939192 AE1-149 E Adder 4.74 MW 4.03 MW
939261 AE1-157 C 50/50 11.35 MW 11.35 MW
939262 AE1-157 E 50/50 6.16 MW 6.16 MW
939602 AE1-190 E Adder 1.0 MW 0.85 MW
940431 AE2-027 C Adder 8.73 MW 7.42 MW
940432 AE2-027 E Adder 5.82 MW 4.94 MW
940551 AE2-041 C Adder 5.0 MW 4.25 MW
940641 AE2-051 C Adder 10.38 MW 8.82 MW
940642 AE2-051 E Adder 0.7 MW 0.6 MW
943471 AF1-018 C Adder 5.0 MW 4.25 MW
944641 AF1-129 C Adder 69.28 MW 58.88 MW
957191 AF2-013 C Adder 13.77 MW 11.7 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 9.03 MW 9.03 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 10.51 MW 10.51 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 52.11 MW 52.11 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 3.97 MW 3.97 MW
NY PJM->LTFIMP_NY CLTF 1.96 MW 1.96 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.48 MW 0.48 MW
WEC LTFEXP_WEC->PJM CLTF 0.21 MW 0.21 MW
CPLE LTFEXP_CPLE->PJM CLTF 6.21 MW 6.21 MW
TVA LTFEXP_TVA->PJM CLTF 3.12 MW 3.12 MW
MEC LTFEXP_MEC->PJM CLTF 1.56 MW 1.56 MW
LAGN LTFEXP_LAGN->PJM CLTF 3.88 MW 3.88 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.1 MW 0.1 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 25.38 MW 25.38 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 2.96 MW 2.96 MW

Summer Potential Congestion due to Local Energy Deliverability

PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.

Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.

The following flowgates remain after considering the topology reinforcements required by the cycle.

Area Facility Description Contingency Name Contingency Type DC|AC Final Cycle Loading Rating (MVA) Rating Type MVA to Mitigate MW Contribution Details
DVP 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
314181 to 314182 ckt 2
DVP_P1-3: 6NORNECK-TX#4_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#4_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
END
OP AC 238.23 % 177.38 B 422.58 41.01
DVP 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
314181 to 314182 ckt 1
DVP_P1-3: 6NORNECK-TX#6_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#6_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
OP AC 230.73 % 179.92 B 415.12 39.39
DVP AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
962970 to 314178 ckt 1
DVP_P1-3: 6NORNECK-TX#6_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#6_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
OP AC 131.88 % 203.98 B 269.0 22.57
DVP 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
314218 to 314908 ckt 2
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
OP AC 109.7 % 879.84 B 965.14 6.75
DVP 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
314214 to 314903 ckt 1
DVP_P1-2: LN 567_SRT-A
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
OP AC 123.73 % 934.92 B 1156.78 11.64
DVP AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
962970 to 314178 ckt 1
Base Case OP AC 105.86 % 203.98 A 215.94 16.78
DVP AD2-074 TP-AG1-146 TP 115.0 kV Ckt 1 line
936590 to 962970 ckt 1
DVP_P1-2: LN 2083_SRT-S
CONTINGENCY 'DVP_P1-2: LN 2083_SRT-S'
 OPEN BRANCH FROM BUS 314132 TO BUS 314163 CKT 1                /*6BIRCHWD     230.0 - 6FINES       230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314163 CKT 1                /*6FREDBRG     230.0 - 6FINES       230.0
 OPEN BUS 314163                                                /*6FINES       230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314137 TO BUS 314138 CKT 1 /*6FREDBRG     230.0 - 6MINE RD     230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314137 TO BUS 314138 CKT 1 /*6FREDBRG     230.0 - 6MINE RD     230.0
END
OP AC 107.09 % 203.98 B 218.45 17.96
DVP 6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1
DVP_P1-2: LN 2090_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2090_SRT-A'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1   /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1   /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1   /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BUS 313837                                   /*6SUMMIT      230.0
 OPEN BUS 314138                                   /*6MINE RD     230.0
END
OP AC 115.57 % 548.02 B 633.37 12.88
DVP 6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1
DVP_P1-2: LN 2090_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2090_SRT-A'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1   /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1   /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1   /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BUS 313837                                   /*6SUMMIT      230.0
 OPEN BUS 314138                                   /*6MINE RD     230.0
END
OP AC 115.51 % 548.02 B 633.03 12.88
DVP 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
OP AC 110.9 % 2858.0 B 3169.45 11.4
DVP 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
314181 to 314182 ckt 2
Base Case OP AC 145.8 % 170.05 A 247.94 24.67
DVP 6CHESTF A-6IRON208 230.0 kV Ckt 1 line
314286 to 314309 ckt 1
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
OP AC 122.25 % 663.64 B 811.33 4.53
DVP 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
314181 to 314182 ckt 1
Base Case OP AC 125.3 % 171.17 A 214.47 20.51
DVP 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
314236 to 314218 ckt 1
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
OP AC 122.86 % 678.68 B 833.8 5.25
DVP 3LANCAST-3OCRAN 115.0 kV Ckt 1 line
314178 to 313813 ckt 1
DVP_P1-3: 6NORNECK-TX#6_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#6_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
OP AC 103.22 % 219.96 B 227.05 22.57
DVP 6IRON208-6SOUWEST 230.0 kV Ckt 1 line
314309 to 314338 ckt 1
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
OP AC 113.21 % 663.64 B 751.33 4.53
DVP 6FREDBRG-6CRANES 230.0 kV Ckt 1 line
314137 to 314134 ckt 1
DVP_P1-2: LN 9296_SRT-A
CONTINGENCY 'DVP_P1-2: LN 9296_SRT-A'
 OPEN BRANCH FROM BUS 314137 TO BUS 314145 CKT 1   /*6FREDBRG     230.0 - 6AQUI_HARB_B 230.0
END
OP AC 104.79 % 984.18 B 1031.34 8.3
DVP 6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1
Base Case OP AC 101.18 % 548.02 A 554.48 13.28
DVP 6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1
Base Case OP AC 101.12 % 548.02 A 554.15 13.28
DVP 6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line
314145 to 314140 ckt 1
DVP_P1-2: LN 2157_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2157_SRT-A'
 OPEN BRANCH FROM BUS 314134 TO BUS 314137 CKT 1   /*6CRANES      230.0 - 6FREDBRG     230.0
END
OP AC 101.96 % 898.64 B 916.21 7.6
DVP 8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
314911 to 313483 ckt 1
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
OP AC 114.52 % 3220.44 B 3688.11 12.32

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6NORNECK-TX#4_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
314181 to 314182 ckt 2
Contingency Name:
DVP_P1-3: 6NORNECK-TX#4_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#4_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 238.23 %
Rating: 177.38 MVA
Rating Type: B
MVA to Mitigate: 422.58 MVA
MW Contribution: 41.01 MW
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area: DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
314181 to 314182 ckt 2
Contingency Name:
DVP_P1-3: 6NORNECK-TX#4_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#4_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 216.82 %
Rating: 177.38 MVA
Rating Type: B
MVA to Mitigate: 384.6 MVA
MW Contribution: 36.41 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314184 3SHACKLE 50/50 0.32 MW 0.32 MW
315034 1NORNECKC1 50/50 2.99 MW 2.99 MW
315035 1NORNECKC2 50/50 2.89 MW 2.89 MW
925865 AC1-065 E 50/50 10.15 MW 10.15 MW
936591 AD2-074 C 50/50 17.86 MW 17.86 MW
936592 AD2-074 E 50/50 29.14 MW 29.14 MW
943741 AF1-042 C 50/50 9.35 MW 9.35 MW
943742 AF1-042 E 50/50 15.25 MW 15.25 MW
961951 AG1-038 C 50/50 10.33 MW 10.33 MW
961952 AG1-038 E 50/50 14.26 MW 14.26 MW
966661 AG1-536 C 50/50 21.17 MW 21.17 MW
966662 AG1-536 E 50/50 28.45 MW 28.45 MW
316077 AC2-138 C 50/50 1.01 MW 1.01 MW
316078 AC2-138 E 50/50 4.12 MW 4.12 MW
316156 AD2-030 C 50/50 0.37 MW 0.37 MW
316157 AD2-030 E 50/50 1.15 MW 1.15 MW
957601 AF2-054 C 50/50 2.05 MW 2.05 MW
957602 AF2-054 E 50/50 1.37 MW 1.37 MW
962861 AG1-135 C 50/50 22.84 MW 22.84 MW
962862 AG1-135 E 50/50 15.23 MW 15.23 MW
962971 AG1-146 C 50/50 8.63 MW 8.63 MW
962972 AG1-146 E 50/50 5.76 MW 5.76 MW
962981 AG1-147 C 50/50 20.14 MW 20.14 MW
962982 AG1-147 E 50/50 13.43 MW 13.43 MW
963611 AG1-210 C 50/50 2.94 MW 2.94 MW
963612 AG1-210 E 50/50 4.42 MW 4.42 MW
314181 3NORNECK 50/50 3.92 MW 3.92 MW
939611 AE1-191 C 50/50 1.05 MW 1.05 MW
939612 AE1-191 E 50/50 4.36 MW 4.36 MW
316201 AC1-065 C 50/50 0.99 MW 0.99 MW
316404 AE1-155 C 50/50 8.35 MW 8.35 MW
939246 AE1-155 E 50/50 34.27 MW 34.27 MW
316280 AD1-041 C 50/50 0.67 MW 0.67 MW
934146 AD1-041 E 50/50 2.72 MW 2.72 MW
958261 AF2-120 C 50/50 24.61 MW 24.61 MW
958262 AF2-120 E 50/50 16.41 MW 16.41 MW
939601 AE1-190 C 50/50 0.26 MW 0.26 MW
939602 AE1-190 E 50/50 1.09 MW 1.09 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 0.5 MW 0.5 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.12 MW 0.12 MW
NY PJM->LTFIMP_NY CLTF 0.06 MW 0.06 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.03 MW 0.03 MW
CPLE LTFEXP_CPLE->PJM CLTF 0.08 MW 0.08 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.08 MW 0.08 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.75 MW 0.75 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.03 MW 0.03 MW

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6NORNECK-TX#6_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
314181 to 314182 ckt 1
Contingency Name:
DVP_P1-3: 6NORNECK-TX#6_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#6_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 230.73 %
Rating: 179.92 MVA
Rating Type: B
MVA to Mitigate: 415.12 MVA
MW Contribution: 39.39 MW
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area: DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
314181 to 314182 ckt 1
Contingency Name:
DVP_P1-3: 6NORNECK-TX#6_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#6_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 213.06 %
Rating: 179.92 MVA
Rating Type: B
MVA to Mitigate: 383.34 MVA
MW Contribution: 35.12 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314184 3SHACKLE 50/50 0.31 MW 0.31 MW
315034 1NORNECKC1 50/50 2.88 MW 2.88 MW
315035 1NORNECKC2 50/50 2.77 MW 2.77 MW
925865 AC1-065 E 50/50 9.74 MW 9.74 MW
936591 AD2-074 C 50/50 17.15 MW 17.15 MW
936592 AD2-074 E 50/50 27.98 MW 27.98 MW
943741 AF1-042 C 50/50 8.97 MW 8.97 MW
943742 AF1-042 E 50/50 14.64 MW 14.64 MW
961951 AG1-038 C 50/50 9.92 MW 9.92 MW
961952 AG1-038 E 50/50 13.7 MW 13.7 MW
966661 AG1-536 C 50/50 20.33 MW 20.33 MW
966662 AG1-536 E 50/50 27.32 MW 27.32 MW
316077 AC2-138 C 50/50 0.97 MW 0.97 MW
316078 AC2-138 E 50/50 3.96 MW 3.96 MW
316156 AD2-030 C 50/50 0.35 MW 0.35 MW
316157 AD2-030 E 50/50 1.11 MW 1.11 MW
957601 AF2-054 C 50/50 1.97 MW 1.97 MW
957602 AF2-054 E 50/50 1.31 MW 1.31 MW
962861 AG1-135 C 50/50 21.94 MW 21.94 MW
962862 AG1-135 E 50/50 14.63 MW 14.63 MW
962971 AG1-146 C 50/50 8.29 MW 8.29 MW
962972 AG1-146 E 50/50 5.53 MW 5.53 MW
962981 AG1-147 C 50/50 19.35 MW 19.35 MW
962982 AG1-147 E 50/50 12.9 MW 12.9 MW
963611 AG1-210 C 50/50 2.83 MW 2.83 MW
963612 AG1-210 E 50/50 4.24 MW 4.24 MW
314181 3NORNECK 50/50 3.77 MW 3.77 MW
939611 AE1-191 C 50/50 1.01 MW 1.01 MW
939612 AE1-191 E 50/50 4.19 MW 4.19 MW
316201 AC1-065 C 50/50 0.95 MW 0.95 MW
316404 AE1-155 C 50/50 8.02 MW 8.02 MW
939246 AE1-155 E 50/50 32.91 MW 32.91 MW
316280 AD1-041 C 50/50 0.64 MW 0.64 MW
934146 AD1-041 E 50/50 2.62 MW 2.62 MW
958261 AF2-120 C 50/50 23.63 MW 23.63 MW
958262 AF2-120 E 50/50 15.76 MW 15.76 MW
939601 AE1-190 C 50/50 0.25 MW 0.25 MW
939602 AE1-190 E 50/50 1.05 MW 1.05 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 0.48 MW 0.48 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.11 MW 0.11 MW
NY PJM->LTFIMP_NY CLTF 0.06 MW 0.06 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.02 MW 0.02 MW
CPLE LTFEXP_CPLE->PJM CLTF 0.08 MW 0.08 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.07 MW 0.07 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.06 MW 0.06 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.72 MW 0.72 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.03 MW 0.03 MW

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P1-3: 6NORNECK-TX#6_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
962970 to 314178 ckt 1
Contingency Name:
DVP_P1-3: 6NORNECK-TX#6_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#6_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 131.88 %
Rating: 203.98 MVA
Rating Type: B
MVA to Mitigate: 269.0 MVA
MW Contribution: 22.57 MW
Impact of Topology Modeling:
Decrease
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
315034 1NORNECKC1 50/50 1.19 MW 1.19 MW
315035 1NORNECKC2 50/50 1.15 MW 1.15 MW
936591 AD2-074 C 50/50 15.51 MW 15.51 MW
936592 AD2-074 E 50/50 25.3 MW 25.3 MW
943741 AF1-042 C 50/50 8.11 MW 8.11 MW
943742 AF1-042 E 50/50 13.24 MW 13.24 MW
961951 AG1-038 C 50/50 8.97 MW 8.97 MW
961952 AG1-038 E 50/50 12.38 MW 12.38 MW
966661 AG1-536 C 50/50 11.65 MW 11.65 MW
966662 AG1-536 E 50/50 15.65 MW 15.65 MW
316077 AC2-138 C 50/50 0.4 MW 0.4 MW
316078 AC2-138 E 50/50 1.64 MW 1.64 MW
957601 AF2-054 C Adder -1.98 MW -1.68 MW
962861 AG1-135 C 50/50 14.04 MW 14.04 MW
962862 AG1-135 E 50/50 9.36 MW 9.36 MW
962971 AG1-146 C 50/50 9.7 MW 9.7 MW
962972 AG1-146 E 50/50 6.46 MW 6.46 MW
962981 AG1-147 C 50/50 22.62 MW 22.62 MW
962982 AG1-147 E 50/50 15.08 MW 15.08 MW
963611 AG1-210 C 50/50 1.17 MW 1.17 MW
963612 AG1-210 E 50/50 1.75 MW 1.75 MW
314181 3NORNECK 50/50 1.56 MW 1.56 MW
316404 AE1-155 C 50/50 4.59 MW 4.59 MW
939246 AE1-155 E 50/50 18.85 MW 18.85 MW
958261 AF2-120 C 50/50 13.54 MW 13.54 MW
958262 AF2-120 E 50/50 9.03 MW 9.03 MW
CBM North LTFEXP_CBM-N->PJM CBM 0.04 MW 0.04 MW
G-007A LTFEXP_G-007A->PJM CMTX 0.09 MW 0.09 MW
VTF LTFEXP_VFT->PJM CMTX 0.24 MW 0.24 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.12 MW 0.12 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.08 MW 0.08 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.04 MW 0.04 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.11 MW 0.11 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.06 MW 0.06 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.11 MW 0.11 MW

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
314218 to 314908 ckt 2
Contingency Name:
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 109.7 %
Rating: 879.84 MVA
Rating Type: B
MVA to Mitigate: 965.14 MVA
MW Contribution: 6.75 MW
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area: DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
314218 to 314908 ckt 2
Contingency Name:
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 133.9 %
Rating: 879.84 MVA
Rating Type: B
MVA to Mitigate: 1178.08 MVA
MW Contribution: 7.48 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961941 AG1-037 C Adder 0.24 MW 0.21 MW
961942 AG1-037 E Adder 0.16 MW 0.14 MW
962331 AG1-082 C Adder 0.97 MW 0.82 MW
962332 AG1-082 E Adder 0.64 MW 0.55 MW
965291 AG1-394 C Adder 0.42 MW 0.35 MW
965292 AG1-394 E Adder 0.77 MW 0.65 MW
966621 AG1-532 C Adder 0.64 MW 0.55 MW
966622 AG1-532 E Adder 0.43 MW 0.36 MW
314541 3WATKINS Adder 0.35 MW 0.3 MW
314572 3EMPORIA Adder 0.2 MW 0.17 MW
918492 AA1-063AE OP Adder 1.91 MW 1.63 MW
920042 AA2-088 E OP Adder 5.22 MW 4.44 MW
934521 AD1-076 C Adder 5.99 MW 5.09 MW
934522 AD1-076 E Adder 3.05 MW 2.6 MW
943172 AE2-346 E Adder 0.29 MW 0.25 MW
960081 AF2-299 C Adder 0.86 MW 0.73 MW
960082 AF2-299 E Adder 0.57 MW 0.48 MW
316141 AB2-099 E Adder 0.12 MW 0.1 MW
900672 V4-068 E Adder 0.17 MW 0.15 MW
940492 AE2-034 E Adder 1.54 MW 1.31 MW
946281 AF1-292 C Adder 0.71 MW 0.6 MW
946282 AF1-292 E Adder 0.47 MW 0.4 MW
957521 AF2-046 C Adder 6.87 MW 5.84 MW
957522 AF2-046 E Adder 3.47 MW 2.95 MW
314539 3UNCAMP Adder 3.13 MW 2.66 MW
916042 Z1-036 E Adder 14.64 MW 12.44 MW
938771 AE1-103 C Adder 1.52 MW 1.29 MW
938772 AE1-103 E Adder 2.1 MW 1.79 MW
314229 6MT RD221 50/50 0.12 MW 0.12 MW
314236 6NRTHEST 50/50 0.16 MW 0.16 MW
314331 6POE Adder 0.84 MW 0.72 MW
314507 3THOMPSN Adder 1.1 MW 0.93 MW
314525 6KINGFORK Adder 0.56 MW 0.48 MW
314550 6HICKORY Adder 1.16 MW 0.99 MW
315050 1FOURRIVERG 50/50 4.25 MW 4.25 MW
315060 1CHESTF5 Adder 47.7 MW 40.54 MW
315065 1CHESTF6 Adder 14.5 MW 12.32 MW
315067 1DARBY 1 50/50 2.2 MW 2.2 MW
315068 1DARBY 2 50/50 2.2 MW 2.2 MW
315069 1DARBY 3 50/50 2.21 MW 2.21 MW
315070 1DARBY 4 50/50 2.21 MW 2.21 MW
315073 1STONECA Adder 4.92 MW 4.19 MW
315083 1SPRUNCA Adder 6.84 MW 5.81 MW
315084 1SPRUNCB Adder 6.84 MW 5.81 MW
315092 1YORKTN3 Adder 80.43 MW 68.36 MW
925865 AC1-065 E Adder 11.22 MW 9.54 MW
926412 AC1-112 E 50/50 1.02 MW 1.02 MW
926472 AC1-118 E Adder 0.64 MW 0.55 MW
926662 AC1-147 E Adder 0.72 MW 0.61 MW
926755 AC1-161 E Adder 6.83 MW 5.81 MW
927226 AC1-216 E Adder 5.1 MW 4.33 MW
934392 AD1-063 E Adder 0.72 MW 0.61 MW
934781 AD1-105 C 50/50 1.05 MW 1.05 MW
934782 AD1-105 E 50/50 4.34 MW 4.34 MW
935112 AD1-144 E Adder 0.52 MW 0.44 MW
936582 AD2-073 E Adder 0.67 MW 0.57 MW
936591 AD2-074 C Adder 3.62 MW 3.08 MW
936592 AD2-074 E Adder 5.91 MW 5.02 MW
942341 AE2-247 C Adder 0.85 MW 0.72 MW
942342 AE2-247 E Adder 1.17 MW 0.99 MW
943461 AF1-017 C Adder 0.76 MW 0.65 MW
943462 AF1-017 E Adder 1.25 MW 1.06 MW
943612 AF1-032 E Adder 0.5 MW 0.42 MW
943741 AF1-042 C Adder 1.9 MW 1.61 MW
943742 AF1-042 E Adder 3.09 MW 2.63 MW
944491 AF1-114 C Adder 3.3 MW 2.8 MW
944492 AF1-114 E Adder 4.55 MW 3.87 MW
961951 AG1-038 C Adder 2.1 MW 1.78 MW
961952 AG1-038 E Adder 2.89 MW 2.46 MW
966661 AG1-536 C Adder 3.49 MW 2.96 MW
966662 AG1-536 E Adder 4.68 MW 3.98 MW
966871 AG1-558 C 50/50 2.4 MW 2.4 MW
966872 AG1-558 E 50/50 1.21 MW 1.21 MW
966881 AG1-559 C Adder 1.38 MW 1.17 MW
966882 AG1-559 E Adder 0.69 MW 0.59 MW
315260 1GOSPORTA Adder 1.16 MW 0.98 MW
315261 1GOSPORTB Adder 1.48 MW 1.25 MW
315262 1GOSPORTC Adder 1.25 MW 1.07 MW
316076 AC2-137 E Adder 1.04 MW 0.89 MW
316078 AC2-138 E Adder 0.6 MW 0.51 MW
316157 AD2-030 E Adder 0.78 MW 0.67 MW
913392 Y1-086 E Adder 1.16 MW 0.98 MW
916192 Z1-068 E Adder 1.01 MW 0.86 MW
923832 AB2-022 E Adder 0.65 MW 0.56 MW
923842 AB2-024 E Adder 1.22 MW 1.04 MW
923852 AB2-025 E Adder 0.58 MW 0.49 MW
930122 AB1-027 E 50/50 1.25 MW 1.25 MW
938552 AE1-074 E Adder 0.82 MW 0.69 MW
939312 AE1-162 E Adder 0.84 MW 0.71 MW
946262 AF1-291 E Adder 1.04 MW 0.89 MW
957411 AF2-035 C Adder 4.96 MW 4.22 MW
957412 AF2-035 E Adder 2.48 MW 2.11 MW
957492 AF2-043 E Adder 0.76 MW 0.65 MW
957601 AF2-054 C Adder 1.4 MW 1.19 MW
957602 AF2-054 E Adder 0.93 MW 0.79 MW
962861 AG1-135 C Adder 3.94 MW 3.35 MW
962862 AG1-135 E Adder 2.62 MW 2.23 MW
962962 AG1-145 E Adder 0.94 MW 0.8 MW
962971 AG1-146 C Adder 2.02 MW 1.71 MW
962972 AG1-146 E Adder 1.34 MW 1.14 MW
962981 AG1-147 C Adder 4.7 MW 4.0 MW
962982 AG1-147 E Adder 3.14 MW 2.67 MW
963611 AG1-210 C Adder 0.43 MW 0.37 MW
963612 AG1-210 E Adder 0.65 MW 0.55 MW
964211 AG1-282 C Adder 1.32 MW 1.12 MW
964212 AG1-282 E Adder 0.88 MW 0.75 MW
901082 W1-029 E Adder 16.71 MW 14.2 MW
917122 Z2-027 E Adder 0.71 MW 0.6 MW
925332 AB2-190 E Adder 5.5 MW 4.67 MW
925522 AC1-027 E Adder 0.66 MW 0.56 MW
942001 AE2-212 C Adder 1.48 MW 1.26 MW
942002 AE2-212 E Adder 0.99 MW 0.84 MW
957832 AF2-077 E Adder 0.9 MW 0.77 MW
957871 AF2-081 C Adder 5.31 MW 4.51 MW
957872 AF2-081 E Adder 2.27 MW 1.93 MW
957971 AF2-091 C Adder 1.12 MW 0.95 MW
957972 AF2-091 E Adder 1.55 MW 1.32 MW
958161 AF2-110 C Adder 0.74 MW 0.63 MW
958162 AF2-110 E Adder 1.18 MW 1.0 MW
313811 6ELKO L286 Adder 1.09 MW 0.93 MW
314181 3NORNECK Adder 0.57 MW 0.49 MW
933291 AC2-141 C Adder 16.01 MW 13.61 MW
933292 AC2-141 E Adder 6.83 MW 5.81 MW
939411 AE1-173 C Adder 41.06 MW 34.9 MW
939412 AE1-173 E Adder 27.37 MW 23.27 MW
934012 AD1-025 E Adder 6.6 MW 5.61 MW
927041 AC1-191 C 50/50 9.65 MW 9.65 MW
927042 AC1-191 E 50/50 4.8 MW 4.8 MW
933981 AD1-022 C Adder 4.26 MW 3.62 MW
933982 AD1-022 E Adder 2.32 MW 1.97 MW
961681 AG1-008 C Adder 6.87 MW 5.84 MW
961682 AG1-008 E Adder 3.47 MW 2.95 MW
313053 6PAPERMILL Adder 4.52 MW 3.84 MW
314594 6PLYMOUTH TP Adder 0.16 MW 0.14 MW
314632 6AYDLETT TAP Adder 0.72 MW 0.61 MW
316004 AC1-112 C 50/50 0.3 MW 0.3 MW
316160 AE1-175 E Adder 0.77 MW 0.66 MW
316169 AC1-164 GEN Adder 29.63 MW 25.18 MW
316233 AE1-074 C Adder 1.62 MW 1.38 MW
316240 AF1-291 C Adder 1.57 MW 1.33 MW
316312 AB1-027 C 50/50 0.48 MW 0.48 MW
917332 KELFORD E Adder 0.79 MW 0.67 MW
924516 AB2-100 E1 Adder 1.38 MW 1.17 MW
924517 AB2-100 E2 Adder 1.38 MW 1.17 MW
926206 AC1-098 E Adder 1.27 MW 1.08 MW
926785 AC1-164_E Adder 13.31 MW 11.31 MW
934065 AD1-033 E Adder 2.68 MW 2.28 MW
937226 AE2-253 E Adder 3.11 MW 2.64 MW
939612 AE1-191 E Adder 3.81 MW 3.23 MW
315051 AA1-145 CT1 50/50 4.44 MW 4.44 MW
315052 AA1-145 CT2 50/50 4.43 MW 4.43 MW
939246 AE1-155 E Adder 5.64 MW 4.8 MW
918512 AA1-065 E OP Adder 2.64 MW 2.24 MW
919153 AA1-139 E2 Adder 2.17 MW 1.84 MW
919152 AA1-139 E1 Adder 2.17 MW 1.84 MW
920692 AA2-178 E Adder 2.05 MW 1.75 MW
924814 AB2-134 E Adder 8.35 MW 7.1 MW
316084 AB2-161 E Adder 3.34 MW 2.84 MW
316088 AB2-174 E Adder 2.98 MW 2.53 MW
932046 AC2-012 E Adder 7.12 MW 6.05 MW
316311 AC2-079 C Adder 3.23 MW 2.75 MW
932596 AC2-079 E Adder 5.27 MW 4.48 MW
934146 AD1-041 E Adder 2.38 MW 2.02 MW
934576 AD1-082 E Adder 2.66 MW 2.26 MW
316349 AD2-085 C Adder 1.95 MW 1.66 MW
936666 AD2-085 E Adder 3.18 MW 2.71 MW
961611 AG1-000B C Adder 9.99 MW 8.49 MW
941591 AE2-156 C Adder 9.72 MW 8.26 MW
944581 AF1-123 C Adder 24.22 MW 20.58 MW
944582 AF1-123 E Adder 55.45 MW 47.13 MW
944591 AF1-124 C Adder 24.3 MW 20.66 MW
944592 AF1-124 E Adder 55.65 MW 47.3 MW
944601 AF1-125 C Adder 23.84 MW 20.27 MW
944602 AF1-125 E Adder 54.58 MW 46.39 MW
944631 AF1-128 C Adder 29.85 MW 25.37 MW
958261 AF2-120 C Adder 4.05 MW 3.44 MW
958262 AF2-120 E Adder 2.7 MW 2.3 MW
965281 AG1-393 C Adder 1.5 MW 1.28 MW
965282 AG1-393 E Adder 1.0 MW 0.85 MW
934501 AD1-074 C Adder 16.49 MW 14.02 MW
934502 AD1-074 E Adder 8.39 MW 7.13 MW
934511 AD1-075 C Adder 4.12 MW 3.5 MW
934512 AD1-075 E Adder 2.1 MW 1.78 MW
935161 AD1-151 C Adder 10.83 MW 9.21 MW
935162 AD1-151 E Adder 7.22 MW 6.14 MW
938531 AE1-072 C Adder 9.32 MW 7.92 MW
938532 AE1-072 E Adder 4.86 MW 4.13 MW
939191 AE1-149 C Adder 6.77 MW 5.75 MW
939192 AE1-149 E Adder 4.51 MW 3.84 MW
939261 AE1-157 C Adder 6.57 MW 5.58 MW
939262 AE1-157 E Adder 3.56 MW 3.03 MW
939602 AE1-190 E Adder 0.95 MW 0.81 MW
940431 AE2-027 C Adder 9.16 MW 7.78 MW
940432 AE2-027 E Adder 6.1 MW 5.19 MW
940481 AE2-033 C Adder 8.06 MW 6.85 MW
940482 AE2-033 E Adder 5.43 MW 4.62 MW
940541 AE2-040 C Adder 1.44 MW 1.22 MW
940551 AE2-041 C Adder 4.82 MW 4.1 MW
940641 AE2-051 C Adder 7.4 MW 6.29 MW
940642 AE2-051 E Adder 4.93 MW 4.19 MW
941101 AE2-104 C Adder 1.82 MW 1.54 MW
941102 AE2-104 E Adder 2.89 MW 2.45 MW
943471 AF1-018 C Adder 4.82 MW 4.1 MW
944641 AF1-129 C Adder 75.6 MW 64.26 MW
315043 1FOUR RIVERA 50/50 2.79 MW 2.79 MW
315044 1FOUR RIVERB 50/50 2.79 MW 2.79 MW
315045 1FOUR RIVERC 50/50 3.4 MW 3.4 MW
315046 1FOUR RIVERD 50/50 2.75 MW 2.75 MW
315047 1FOUR RIVERE 50/50 2.75 MW 2.75 MW
315048 1FOUR RIVERF 50/50 3.35 MW 3.35 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 3.0 MW 3.0 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 28.18 MW 28.18 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.08 MW 1.08 MW
NY PJM->LTFIMP_NY CLTF 0.55 MW 0.55 MW
CPLE LTFEXP_CPLE->PJM CLTF 3.77 MW 3.77 MW
TVA LTFEXP_TVA->PJM CLTF 1.07 MW 1.07 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.04 MW 0.04 MW
MEC LTFEXP_MEC->PJM CLTF 0.21 MW 0.21 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.09 MW 0.09 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.41 MW 1.41 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.01 MW 0.01 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 6.89 MW 6.89 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 1.79 MW 1.79 MW

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 567_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
314214 to 314903 ckt 1
Contingency Name:
DVP_P1-2: LN 567_SRT-A
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 123.73 %
Rating: 934.92 MVA
Rating Type: B
MVA to Mitigate: 1156.78 MVA
MW Contribution: 11.64 MW
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area: DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
314214 to 314903 ckt 1
Contingency Name:
DVP_P1-2: LN 567_SRT-A
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 128.41 %
Rating: 934.92 MVA
Rating Type: B
MVA to Mitigate: 1200.49 MVA
MW Contribution: 11.79 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961941 AG1-037 C Adder 0.26 MW 0.22 MW
961942 AG1-037 E Adder 0.17 MW 0.14 MW
962331 AG1-082 C Adder 1.02 MW 0.87 MW
962332 AG1-082 E Adder 0.68 MW 0.58 MW
965291 AG1-394 C Adder 0.44 MW 0.37 MW
965292 AG1-394 E Adder 0.81 MW 0.69 MW
314541 3WATKINS Adder 0.38 MW 0.32 MW
918492 AA1-063AE OP Adder 1.96 MW 1.67 MW
919692 AA2-053 E OP Adder 1.97 MW 1.67 MW
920042 AA2-088 E OP Adder 5.49 MW 4.67 MW
927146 AC1-208 E Adder 1.95 MW 1.66 MW
934521 AD1-076 C Adder 6.46 MW 5.49 MW
934522 AD1-076 E Adder 3.29 MW 2.8 MW
943172 AE2-346 E Adder 0.31 MW 0.26 MW
316141 AB2-099 E Adder 0.13 MW 0.11 MW
900672 V4-068 E Adder 0.18 MW 0.15 MW
917342 Z2-044 E Adder 0.3 MW 0.26 MW
940492 AE2-034 E Adder 1.68 MW 1.42 MW
957521 AF2-046 C Adder 7.23 MW 6.14 MW
957522 AF2-046 E Adder 3.65 MW 3.1 MW
314539 3UNCAMP Adder 3.37 MW 2.86 MW
916042 Z1-036 E Adder 16.11 MW 13.69 MW
938771 AE1-103 C Adder 1.64 MW 1.4 MW
938772 AE1-103 E Adder 2.27 MW 1.93 MW
314184 3SHACKLE 50/50 0.6 MW 0.6 MW
314331 6POE Adder 0.72 MW 0.61 MW
314507 3THOMPSN Adder 1.23 MW 1.04 MW
314525 6KINGFORK Adder 0.65 MW 0.55 MW
314550 6HICKORY Adder 1.3 MW 1.1 MW
315060 1CHESTF5 Adder 61.61 MW 52.37 MW
315065 1CHESTF6 Adder 11.1 MW 9.43 MW
315073 1STONECA Adder 5.14 MW 4.37 MW
315083 1SPRUNCA Adder 4.63 MW 3.94 MW
315084 1SPRUNCB Adder 4.63 MW 3.94 MW
315092 1YORKTN3 Adder 112.31 MW 95.46 MW
925865 AC1-065 E 50/50 18.88 MW 18.88 MW
926412 AC1-112 E Adder 0.95 MW 0.81 MW
926472 AC1-118 E Adder 1.07 MW 0.91 MW
926662 AC1-147 E Adder 0.81 MW 0.69 MW
926755 AC1-161 E Adder 7.68 MW 6.53 MW
927226 AC1-216 E Adder 5.58 MW 4.74 MW
934392 AD1-063 E 50/50 1.28 MW 1.28 MW
935112 AD1-144 E Adder 0.6 MW 0.51 MW
936582 AD2-073 E Adder 1.15 MW 0.97 MW
936591 AD2-074 C 50/50 6.21 MW 6.21 MW
936592 AD2-074 E 50/50 10.14 MW 10.14 MW
942341 AE2-247 C Adder 0.89 MW 0.75 MW
942342 AE2-247 E Adder 1.22 MW 1.04 MW
943461 AF1-017 C Adder 0.8 MW 0.68 MW
943462 AF1-017 E Adder 1.31 MW 1.11 MW
943612 AF1-032 E Adder 0.56 MW 0.47 MW
943741 AF1-042 C 50/50 3.25 MW 3.25 MW
943742 AF1-042 E 50/50 5.3 MW 5.3 MW
944491 AF1-114 C Adder 5.07 MW 4.31 MW
944492 AF1-114 E Adder 7.0 MW 5.95 MW
961951 AG1-038 C 50/50 3.59 MW 3.59 MW
961952 AG1-038 E 50/50 4.96 MW 4.96 MW
966661 AG1-536 C 50/50 6.01 MW 6.01 MW
966662 AG1-536 E 50/50 8.07 MW 8.07 MW
315260 1GOSPORTA Adder 1.3 MW 1.1 MW
315261 1GOSPORTB Adder 1.66 MW 1.41 MW
315262 1GOSPORTC Adder 1.41 MW 1.2 MW
316075 AC2-137 C 50/50 0.45 MW 0.45 MW
316076 AC2-137 E 50/50 1.58 MW 1.58 MW
316078 AC2-138 E Adder 1.04 MW 0.89 MW
316156 AD2-030 C 50/50 0.42 MW 0.42 MW
316157 AD2-030 E 50/50 1.33 MW 1.33 MW
913392 Y1-086 E Adder 1.29 MW 1.1 MW
916192 Z1-068 E Adder 1.13 MW 0.96 MW
923832 AB2-022 E Adder 0.73 MW 0.62 MW
923842 AB2-024 E 50/50 2.23 MW 2.23 MW
923852 AB2-025 E Adder 0.54 MW 0.46 MW
930122 AB1-027 E Adder 1.17 MW 0.99 MW
939312 AE1-162 E Adder 0.96 MW 0.81 MW
946262 AF1-291 E Adder 0.81 MW 0.69 MW
957492 AF2-043 E Adder 0.86 MW 0.73 MW
957601 AF2-054 C 50/50 2.37 MW 2.37 MW
957602 AF2-054 E 50/50 1.58 MW 1.58 MW
962861 AG1-135 C 50/50 6.78 MW 6.78 MW
962862 AG1-135 E 50/50 4.52 MW 4.52 MW
962962 AG1-145 E 50/50 1.53 MW 1.53 MW
962971 AG1-146 C 50/50 3.45 MW 3.45 MW
962972 AG1-146 E 50/50 2.3 MW 2.3 MW
962981 AG1-147 C 50/50 8.05 MW 8.05 MW
962982 AG1-147 E 50/50 5.36 MW 5.36 MW
963611 AG1-210 C Adder 0.74 MW 0.63 MW
963612 AG1-210 E Adder 1.12 MW 0.95 MW
964211 AG1-282 C 50/50 2.32 MW 2.32 MW
964212 AG1-282 E 50/50 1.55 MW 1.55 MW
901082 W1-029 E Adder 18.56 MW 15.78 MW
917122 Z2-027 E Adder 0.78 MW 0.67 MW
925332 AB2-190 E Adder 5.9 MW 5.02 MW
925522 AC1-027 E Adder 0.74 MW 0.62 MW
942001 AE2-212 C Adder 1.19 MW 1.01 MW
942002 AE2-212 E Adder 0.79 MW 0.67 MW
957832 AF2-077 E Adder 1.39 MW 1.18 MW
957871 AF2-081 C Adder 5.93 MW 5.04 MW
957872 AF2-081 E Adder 2.54 MW 2.16 MW
957971 AF2-091 C Adder 1.72 MW 1.46 MW
957972 AF2-091 E Adder 2.38 MW 2.02 MW
958161 AF2-110 C Adder 0.81 MW 0.69 MW
958162 AF2-110 E Adder 1.29 MW 1.1 MW
313811 6ELKO L286 50/50 1.65 MW 1.65 MW
314181 3NORNECK Adder 0.99 MW 0.84 MW
933291 AC2-141 C Adder 18.0 MW 15.3 MW
933292 AC2-141 E Adder 7.68 MW 6.53 MW
939411 AE1-173 C Adder 42.86 MW 36.43 MW
939412 AE1-173 E Adder 28.57 MW 24.29 MW
934012 AD1-025 E Adder 7.22 MW 6.14 MW
933981 AD1-022 C Adder 4.58 MW 3.89 MW
933982 AD1-022 E Adder 2.49 MW 2.12 MW
961681 AG1-008 C Adder 7.23 MW 6.14 MW
961682 AG1-008 E Adder 3.65 MW 3.1 MW
313053 6PAPERMILL 50/50 8.16 MW 8.16 MW
314594 6PLYMOUTH TP Adder 0.17 MW 0.15 MW
314632 6AYDLETT TAP Adder 0.8 MW 0.68 MW
316059 AD1-063 C 50/50 0.31 MW 0.31 MW
316159 AE1-175 C 50/50 0.42 MW 0.42 MW
316160 AE1-175 E 50/50 1.27 MW 1.27 MW
316169 AC1-164 GEN 50/50 59.58 MW 59.58 MW
316240 AF1-291 C Adder 1.21 MW 1.03 MW
316274 AC1-208 C Adder 4.4 MW 3.74 MW
316314 AB2-024 C 50/50 0.36 MW 0.36 MW
316382 AG1-145 C 50/50 0.38 MW 0.38 MW
917332 KELFORD E Adder 0.82 MW 0.7 MW
924516 AB2-100 E1 Adder 1.32 MW 1.12 MW
924517 AB2-100 E2 Adder 1.32 MW 1.12 MW
926206 AC1-098 E Adder 1.8 MW 1.53 MW
926214 AC1-099 E Adder 0.6 MW 0.51 MW
926785 AC1-164_E 50/50 26.77 MW 26.77 MW
934065 AD1-033 E Adder 3.0 MW 2.55 MW
937226 AE2-253 E Adder 3.47 MW 2.95 MW
939611 AE1-191 C 50/50 1.54 MW 1.54 MW
939612 AE1-191 E 50/50 6.42 MW 6.42 MW
316201 AC1-065 C 50/50 1.85 MW 1.85 MW
316404 AE1-155 C 50/50 2.37 MW 2.37 MW
939246 AE1-155 E 50/50 9.72 MW 9.72 MW
918512 AA1-065 E OP Adder 2.8 MW 2.38 MW
919153 AA1-139 E2 Adder 2.42 MW 2.06 MW
919152 AA1-139 E1 Adder 2.42 MW 2.06 MW
919710 AA2-057 E Adder 1.98 MW 1.69 MW
920692 AA2-178 E Adder 2.23 MW 1.9 MW
924814 AB2-134 E Adder 9.14 MW 7.77 MW
316084 AB2-161 E Adder 3.28 MW 2.79 MW
925122 AB2-169 E Adder 2.83 MW 2.4 MW
932046 AC2-012 E Adder 7.98 MW 6.79 MW
316311 AC2-079 C Adder 3.41 MW 2.9 MW
932596 AC2-079 E Adder 5.56 MW 4.73 MW
316280 AD1-041 C 50/50 0.98 MW 0.98 MW
934146 AD1-041 E 50/50 4.01 MW 4.01 MW
934576 AD1-082 E Adder 2.62 MW 2.22 MW
316349 AD2-085 C Adder 2.05 MW 1.74 MW
936666 AD2-085 E Adder 3.34 MW 2.84 MW
961611 AG1-000B C Adder 11.28 MW 9.59 MW
941591 AE2-156 C Adder 10.9 MW 9.27 MW
944581 AF1-123 C Adder 27.1 MW 23.03 MW
944582 AF1-123 E Adder 62.05 MW 52.74 MW
944591 AF1-124 C Adder 27.19 MW 23.11 MW
944592 AF1-124 E Adder 62.27 MW 52.93 MW
944601 AF1-125 C Adder 26.68 MW 22.68 MW
944602 AF1-125 E Adder 61.08 MW 51.91 MW
944631 AF1-128 C Adder 38.55 MW 32.77 MW
958261 AF2-120 C 50/50 6.98 MW 6.98 MW
958262 AF2-120 E 50/50 4.66 MW 4.66 MW
965281 AG1-393 C Adder 1.32 MW 1.12 MW
965282 AG1-393 E Adder 0.88 MW 0.75 MW
932632 AC2-084 E Adder 1.59 MW 1.35 MW
934501 AD1-074 C Adder 17.79 MW 15.12 MW
934502 AD1-074 E Adder 9.06 MW 7.7 MW
934511 AD1-075 C Adder 4.45 MW 3.78 MW
934512 AD1-075 E Adder 2.26 MW 1.93 MW
935161 AD1-151 C Adder 11.73 MW 9.97 MW
935162 AD1-151 E Adder 7.82 MW 6.65 MW
938531 AE1-072 C Adder 10.4 MW 8.84 MW
938532 AE1-072 E Adder 5.42 MW 4.61 MW
939191 AE1-149 C Adder 6.37 MW 5.41 MW
939192 AE1-149 E Adder 4.24 MW 3.61 MW
939601 AE1-190 C 50/50 0.38 MW 0.38 MW
939602 AE1-190 E 50/50 1.6 MW 1.6 MW
940431 AE2-027 C Adder 8.04 MW 6.83 MW
940432 AE2-027 E Adder 5.36 MW 4.56 MW
940481 AE2-033 C Adder 7.46 MW 6.34 MW
940482 AE2-033 E Adder 5.03 MW 4.28 MW
940541 AE2-040 C Adder 1.33 MW 1.13 MW
940551 AE2-041 C 50/50 8.53 MW 8.53 MW
940641 AE2-051 C Adder 7.5 MW 6.38 MW
940642 AE2-051 E Adder 5.0 MW 4.25 MW
941101 AE2-104 C Adder 1.99 MW 1.69 MW
941102 AE2-104 E Adder 3.17 MW 2.69 MW
943471 AF1-018 C 50/50 8.53 MW 8.53 MW
944641 AF1-129 C Adder 57.89 MW 49.2 MW
957191 AF2-013 C Adder 8.09 MW 6.87 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 1.13 MW 1.13 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 3.92 MW 3.92 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 29.25 MW 29.25 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.13 MW 1.13 MW
NY PJM->LTFIMP_NY CLTF 0.56 MW 0.56 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.07 MW 0.07 MW
WEC LTFEXP_WEC->PJM CLTF 0.03 MW 0.03 MW
CPLE LTFEXP_CPLE->PJM CLTF 3.85 MW 3.85 MW
TVA LTFEXP_TVA->PJM CLTF 1.27 MW 1.27 MW
MEC LTFEXP_MEC->PJM CLTF 0.43 MW 0.43 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.66 MW 1.66 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.02 MW 0.02 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 7.22 MW 7.22 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 1.83 MW 1.83 MW

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
962970 to 314178 ckt 1
Contingency Name:
Base Case
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 105.86 %
Rating: 203.98 MVA
Rating Type: A
MVA to Mitigate: 215.94 MVA
MW Contribution: 16.78 MW
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area: DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
962970 to 314178 ckt 1
Contingency Name:
Base Case
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 126.9 %
Rating: 203.98 MVA
Rating Type: A
MVA to Mitigate: 258.84 MVA
MW Contribution: 22.31 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
315034 1NORNECKC1 50/50 0.77 MW 0.77 MW
315035 1NORNECKC2 50/50 0.74 MW 0.74 MW
926472 AC1-118 E Adder 0.39 MW 0.33 MW
936582 AD2-073 E Adder 0.42 MW 0.35 MW
936591 AD2-074 C 50/50 12.98 MW 12.98 MW
936592 AD2-074 E 50/50 21.19 MW 21.19 MW
943741 AF1-042 C 50/50 6.79 MW 6.79 MW
943742 AF1-042 E 50/50 11.09 MW 11.09 MW
961951 AG1-038 C 50/50 7.51 MW 7.51 MW
961952 AG1-038 E 50/50 10.37 MW 10.37 MW
966661 AG1-536 C 50/50 8.66 MW 8.66 MW
966662 AG1-536 E 50/50 11.64 MW 11.64 MW
316077 AC2-138 C 50/50 0.26 MW 0.26 MW
316078 AC2-138 E 50/50 1.06 MW 1.06 MW
957601 AF2-054 C Adder -2.27 MW -1.93 MW
962861 AG1-135 C 50/50 10.81 MW 10.81 MW
962862 AG1-135 E 50/50 7.21 MW 7.21 MW
962971 AG1-146 C 50/50 8.48 MW 8.48 MW
962972 AG1-146 E 50/50 5.65 MW 5.65 MW
962981 AG1-147 C 50/50 19.78 MW 19.78 MW
962982 AG1-147 E 50/50 13.19 MW 13.19 MW
963611 AG1-210 C 50/50 0.76 MW 0.76 MW
963612 AG1-210 E 50/50 1.13 MW 1.13 MW
314181 3NORNECK 50/50 1.0 MW 1.0 MW
316404 AE1-155 C 50/50 3.42 MW 3.42 MW
939246 AE1-155 E 50/50 14.02 MW 14.02 MW
958261 AF2-120 C 50/50 10.07 MW 10.07 MW
958262 AF2-120 E 50/50 6.71 MW 6.71 MW
CBM North LTFEXP_CBM-N->PJM CBM 0.06 MW 0.06 MW
G-007A LTFEXP_G-007A->PJM CMTX 0.13 MW 0.13 MW
VTF LTFEXP_VFT->PJM CMTX 0.34 MW 0.34 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.12 MW 0.12 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.08 MW 0.08 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.04 MW 0.04 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.01 MW 0.01 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.05 MW 0.05 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.03 MW 0.03 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.12 MW 0.12 MW

Details for AD2-074 TP-AG1-146 TP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2083_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
AD2-074 TP-AG1-146 TP 115.0 kV Ckt 1 line
936590 to 962970 ckt 1
Contingency Name:
DVP_P1-2: LN 2083_SRT-S
CONTINGENCY 'DVP_P1-2: LN 2083_SRT-S'
 OPEN BRANCH FROM BUS 314132 TO BUS 314163 CKT 1                /*6BIRCHWD     230.0 - 6FINES       230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314163 CKT 1                /*6FREDBRG     230.0 - 6FINES       230.0
 OPEN BUS 314163                                                /*6FINES       230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314137 TO BUS 314138 CKT 1 /*6FREDBRG     230.0 - 6MINE RD     230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314137 TO BUS 314138 CKT 1 /*6FREDBRG     230.0 - 6MINE RD     230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 107.09 %
Rating: 203.98 MVA
Rating Type: B
MVA to Mitigate: 218.45 MVA
MW Contribution: 17.96 MW
Impact of Topology Modeling:
Decrease
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
315033 1BIRCHWDA Adder 17.98 MW 15.28 MW
315034 1NORNECKC1 50/50 0.85 MW 0.85 MW
315035 1NORNECKC2 50/50 0.82 MW 0.82 MW
926472 AC1-118 E Adder 0.6 MW 0.51 MW
936582 AD2-073 E Adder 0.59 MW 0.5 MW
936591 AD2-074 C 50/50 13.54 MW 13.54 MW
936592 AD2-074 E 50/50 22.09 MW 22.09 MW
943741 AF1-042 C 50/50 7.08 MW 7.08 MW
943742 AF1-042 E 50/50 11.56 MW 11.56 MW
944491 AF1-114 C Adder 3.73 MW 3.17 MW
944492 AF1-114 E Adder 5.15 MW 4.38 MW
961951 AG1-038 C 50/50 7.83 MW 7.83 MW
961952 AG1-038 E 50/50 10.81 MW 10.81 MW
966661 AG1-536 C 50/50 9.27 MW 9.27 MW
966662 AG1-536 E 50/50 12.46 MW 12.46 MW
316077 AC2-138 C 50/50 0.29 MW 0.29 MW
316078 AC2-138 E 50/50 1.17 MW 1.17 MW
957601 AF2-054 C Adder -2.14 MW -1.82 MW
962861 AG1-135 C 50/50 11.48 MW 11.48 MW
962862 AG1-135 E 50/50 7.65 MW 7.65 MW
963611 AG1-210 C 50/50 0.84 MW 0.84 MW
963612 AG1-210 E 50/50 1.25 MW 1.25 MW
964211 AG1-282 C Adder 0.84 MW 0.71 MW
964212 AG1-282 E Adder 0.56 MW 0.47 MW
957971 AF2-091 C Adder 1.27 MW 1.08 MW
957972 AF2-091 E Adder 1.75 MW 1.49 MW
314181 3NORNECK 50/50 1.11 MW 1.11 MW
316404 AE1-155 C 50/50 3.65 MW 3.65 MW
939246 AE1-155 E 50/50 15.0 MW 15.0 MW
958261 AF2-120 C 50/50 10.78 MW 10.78 MW
958262 AF2-120 E 50/50 7.18 MW 7.18 MW
957191 AF2-013 C Adder 8.89 MW 7.55 MW
CBM North LTFEXP_CBM-N->PJM CBM 0.0 MW 0.0 MW
G-007A LTFEXP_G-007A->PJM CMTX 0.01 MW 0.01 MW
VTF LTFEXP_VFT->PJM CMTX 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.04 MW 0.04 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.03 MW 0.03 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.01 MW 0.01 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.02 MW 0.02 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.01 MW 0.01 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1
Contingency Name:
DVP_P1-2: LN 2090_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2090_SRT-A'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1   /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1   /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1   /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BUS 313837                                   /*6SUMMIT      230.0
 OPEN BUS 314138                                   /*6MINE RD     230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 115.57 %
Rating: 548.02 MVA
Rating Type: B
MVA to Mitigate: 633.37 MVA
MW Contribution: 12.88 MW
Impact of Topology Modeling:
Decrease
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 50/50 0.96 MW 0.96 MW
315033 1BIRCHWDA 50/50 150.18 MW 150.18 MW
315034 1NORNECKC1 50/50 0.9 MW 0.9 MW
315035 1NORNECKC2 50/50 0.87 MW 0.87 MW
925865 AC1-065 E 50/50 9.96 MW 9.96 MW
926472 AC1-118 E 50/50 2.3 MW 2.3 MW
934392 AD1-063 E Adder 0.64 MW 0.54 MW
936582 AD2-073 E 50/50 1.84 MW 1.84 MW
936591 AD2-074 C 50/50 6.09 MW 6.09 MW
936592 AD2-074 E 50/50 9.93 MW 9.93 MW
943741 AF1-042 C 50/50 3.19 MW 3.19 MW
943742 AF1-042 E 50/50 5.2 MW 5.2 MW
944491 AF1-114 C 50/50 19.93 MW 19.93 MW
944492 AF1-114 E 50/50 27.52 MW 27.52 MW
961951 AG1-038 C 50/50 3.52 MW 3.52 MW
961952 AG1-038 E 50/50 4.86 MW 4.86 MW
966661 AG1-536 C 50/50 6.65 MW 6.65 MW
966662 AG1-536 E 50/50 8.93 MW 8.93 MW
316077 AC2-138 C 50/50 0.3 MW 0.3 MW
316078 AC2-138 E 50/50 1.24 MW 1.24 MW
316156 AD2-030 C 50/50 0.25 MW 0.25 MW
316157 AD2-030 E 50/50 0.78 MW 0.78 MW
923842 AB2-024 E Adder 1.01 MW 0.86 MW
957601 AF2-054 C 50/50 1.39 MW 1.39 MW
957602 AF2-054 E 50/50 0.93 MW 0.93 MW
962861 AG1-135 C 50/50 7.3 MW 7.3 MW
962862 AG1-135 E 50/50 4.87 MW 4.87 MW
962971 AG1-146 C 50/50 3.13 MW 3.13 MW
962972 AG1-146 E 50/50 2.08 MW 2.08 MW
962981 AG1-147 C 50/50 7.3 MW 7.3 MW
962982 AG1-147 E 50/50 4.87 MW 4.87 MW
963611 AG1-210 C 50/50 0.89 MW 0.89 MW
963612 AG1-210 E 50/50 1.33 MW 1.33 MW
964211 AG1-282 C 50/50 2.5 MW 2.5 MW
964212 AG1-282 E 50/50 1.67 MW 1.67 MW
957832 AF2-077 E Adder 0.66 MW 0.56 MW
957971 AF2-091 C 50/50 6.78 MW 6.78 MW
957972 AF2-091 E 50/50 9.36 MW 9.36 MW
314181 3NORNECK 50/50 1.18 MW 1.18 MW
313053 6PAPERMILL Adder 3.78 MW 3.21 MW
939611 AE1-191 C 50/50 0.85 MW 0.85 MW
939612 AE1-191 E 50/50 3.55 MW 3.55 MW
316201 AC1-065 C 50/50 0.97 MW 0.97 MW
316223 AC1-118 C 50/50 0.73 MW 0.73 MW
316337 AD2-073 C 50/50 0.61 MW 0.61 MW
316404 AE1-155 C 50/50 2.62 MW 2.62 MW
939246 AE1-155 E 50/50 10.76 MW 10.76 MW
316280 AD1-041 C 50/50 0.54 MW 0.54 MW
934146 AD1-041 E 50/50 2.22 MW 2.22 MW
958261 AF2-120 C 50/50 7.73 MW 7.73 MW
958262 AF2-120 E 50/50 5.15 MW 5.15 MW
939601 AE1-190 C 50/50 0.21 MW 0.21 MW
939602 AE1-190 E 50/50 0.89 MW 0.89 MW
940551 AE2-041 C Adder 4.27 MW 3.63 MW
943471 AF1-018 C Adder 4.27 MW 3.63 MW
957191 AF2-013 C 50/50 62.05 MW 62.05 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 3.79 MW 3.79 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 2.79 MW 2.79 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 12.13 MW 12.13 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.77 MW 0.77 MW
NY PJM->LTFIMP_NY CLTF 0.35 MW 0.35 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.15 MW 0.15 MW
WEC LTFEXP_WEC->PJM CLTF 0.08 MW 0.08 MW
CPLE LTFEXP_CPLE->PJM CLTF 1.47 MW 1.47 MW
TVA LTFEXP_TVA->PJM CLTF 0.76 MW 0.76 MW
MEC LTFEXP_MEC->PJM CLTF 0.49 MW 0.49 MW
LAGN LTFEXP_LAGN->PJM CLTF 0.96 MW 0.96 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.03 MW 0.03 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 4.89 MW 4.89 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.7 MW 0.7 MW

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1
Contingency Name:
DVP_P1-2: LN 2090_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2090_SRT-A'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1   /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1   /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1   /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BUS 313837                                   /*6SUMMIT      230.0
 OPEN BUS 314138                                   /*6MINE RD     230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 115.51 %
Rating: 548.02 MVA
Rating Type: B
MVA to Mitigate: 633.03 MVA
MW Contribution: 12.88 MW
Impact of Topology Modeling:
Decrease
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 50/50 0.96 MW 0.96 MW
315033 1BIRCHWDA 50/50 150.18 MW 150.18 MW
315034 1NORNECKC1 50/50 0.9 MW 0.9 MW
315035 1NORNECKC2 50/50 0.87 MW 0.87 MW
925865 AC1-065 E 50/50 9.96 MW 9.96 MW
926472 AC1-118 E 50/50 2.3 MW 2.3 MW
934392 AD1-063 E Adder 0.64 MW 0.54 MW
936582 AD2-073 E 50/50 1.84 MW 1.84 MW
936591 AD2-074 C 50/50 6.09 MW 6.09 MW
936592 AD2-074 E 50/50 9.93 MW 9.93 MW
943741 AF1-042 C 50/50 3.19 MW 3.19 MW
943742 AF1-042 E 50/50 5.2 MW 5.2 MW
944491 AF1-114 C 50/50 19.93 MW 19.93 MW
944492 AF1-114 E 50/50 27.52 MW 27.52 MW
961951 AG1-038 C 50/50 3.52 MW 3.52 MW
961952 AG1-038 E 50/50 4.86 MW 4.86 MW
966661 AG1-536 C 50/50 6.65 MW 6.65 MW
966662 AG1-536 E 50/50 8.93 MW 8.93 MW
316077 AC2-138 C 50/50 0.3 MW 0.3 MW
316078 AC2-138 E 50/50 1.24 MW 1.24 MW
316156 AD2-030 C 50/50 0.25 MW 0.25 MW
316157 AD2-030 E 50/50 0.78 MW 0.78 MW
923842 AB2-024 E Adder 1.01 MW 0.86 MW
957601 AF2-054 C 50/50 1.39 MW 1.39 MW
957602 AF2-054 E 50/50 0.93 MW 0.93 MW
962861 AG1-135 C 50/50 7.3 MW 7.3 MW
962862 AG1-135 E 50/50 4.87 MW 4.87 MW
962971 AG1-146 C 50/50 3.13 MW 3.13 MW
962972 AG1-146 E 50/50 2.08 MW 2.08 MW
962981 AG1-147 C 50/50 7.3 MW 7.3 MW
962982 AG1-147 E 50/50 4.87 MW 4.87 MW
963611 AG1-210 C 50/50 0.89 MW 0.89 MW
963612 AG1-210 E 50/50 1.33 MW 1.33 MW
964211 AG1-282 C 50/50 2.5 MW 2.5 MW
964212 AG1-282 E 50/50 1.67 MW 1.67 MW
957832 AF2-077 E Adder 0.66 MW 0.56 MW
957971 AF2-091 C 50/50 6.78 MW 6.78 MW
957972 AF2-091 E 50/50 9.36 MW 9.36 MW
314181 3NORNECK 50/50 1.18 MW 1.18 MW
313053 6PAPERMILL Adder 3.78 MW 3.21 MW
939611 AE1-191 C 50/50 0.85 MW 0.85 MW
939612 AE1-191 E 50/50 3.55 MW 3.55 MW
316201 AC1-065 C 50/50 0.97 MW 0.97 MW
316223 AC1-118 C 50/50 0.73 MW 0.73 MW
316337 AD2-073 C 50/50 0.61 MW 0.61 MW
316404 AE1-155 C 50/50 2.62 MW 2.62 MW
939246 AE1-155 E 50/50 10.76 MW 10.76 MW
316280 AD1-041 C 50/50 0.54 MW 0.54 MW
934146 AD1-041 E 50/50 2.22 MW 2.22 MW
958261 AF2-120 C 50/50 7.73 MW 7.73 MW
958262 AF2-120 E 50/50 5.15 MW 5.15 MW
939601 AE1-190 C 50/50 0.21 MW 0.21 MW
939602 AE1-190 E 50/50 0.89 MW 0.89 MW
940551 AE2-041 C Adder 4.27 MW 3.63 MW
943471 AF1-018 C Adder 4.27 MW 3.63 MW
957191 AF2-013 C 50/50 62.05 MW 62.05 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 3.79 MW 3.79 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 2.79 MW 2.79 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 12.13 MW 12.13 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.77 MW 0.77 MW
NY PJM->LTFIMP_NY CLTF 0.35 MW 0.35 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.15 MW 0.15 MW
WEC LTFEXP_WEC->PJM CLTF 0.08 MW 0.08 MW
CPLE LTFEXP_CPLE->PJM CLTF 1.47 MW 1.47 MW
TVA LTFEXP_TVA->PJM CLTF 0.76 MW 0.76 MW
MEC LTFEXP_MEC->PJM CLTF 0.49 MW 0.49 MW
LAGN LTFEXP_LAGN->PJM CLTF 0.96 MW 0.96 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.03 MW 0.03 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 4.89 MW 4.89 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.7 MW 0.7 MW

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1
Contingency Name:
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 110.9 %
Rating: 2858.0 MVA
Rating Type: B
MVA to Mitigate: 3169.45 MVA
MW Contribution: 11.4 MW
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area: DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1
Contingency Name:
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 122.47 %
Rating: 2858.0 MVA
Rating Type: B
MVA to Mitigate: 3500.12 MVA
MW Contribution: 11.05 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961941 AG1-037 C Adder 0.46 MW 0.4 MW
961942 AG1-037 E Adder 0.31 MW 0.26 MW
962331 AG1-082 C Adder 1.86 MW 1.58 MW
962332 AG1-082 E Adder 1.24 MW 1.05 MW
965291 AG1-394 C Adder 0.8 MW 0.68 MW
965292 AG1-394 E Adder 1.47 MW 1.25 MW
314541 3WATKINS Adder 0.67 MW 0.57 MW
918492 AA1-063AE OP Adder 3.61 MW 3.07 MW
920042 AA2-088 E OP Adder 9.96 MW 8.46 MW
934521 AD1-076 C Adder 11.74 MW 9.97 MW
934522 AD1-076 E Adder 5.98 MW 5.08 MW
943172 AE2-346 E Adder 0.56 MW 0.47 MW
316141 AB2-099 E Adder 0.23 MW 0.2 MW
900672 V4-068 E Adder 0.33 MW 0.28 MW
917342 Z2-044 E Adder 0.56 MW 0.47 MW
940492 AE2-034 E Adder 3.03 MW 2.57 MW
957521 AF2-046 C Adder 13.16 MW 11.19 MW
957522 AF2-046 E Adder 6.65 MW 5.65 MW
314539 3UNCAMP Adder 6.02 MW 5.12 MW
916042 Z1-036 E Adder 28.94 MW 24.6 MW
938771 AE1-103 C Adder 2.93 MW 2.49 MW
938772 AE1-103 E Adder 4.04 MW 3.44 MW
314229 6MT RD221 50/50 0.15 MW 0.15 MW
314236 6NRTHEST 50/50 0.22 MW 0.22 MW
314331 6POE Adder 1.31 MW 1.12 MW
314507 3THOMPSN Adder 2.18 MW 1.85 MW
314525 6KINGFORK Adder 1.1 MW 0.94 MW
314550 6HICKORY Adder 2.34 MW 1.99 MW
315060 1CHESTF5 50/50 76.84 MW 76.84 MW
315061 1CHESTG7 50/50 4.69 MW 4.69 MW
315062 1CHESTS7 50/50 2.15 MW 2.15 MW
315063 1CHESTG8 50/50 4.61 MW 4.61 MW
315064 1CHESTS8 50/50 2.38 MW 2.38 MW
315065 1CHESTF6 Adder 21.27 MW 18.08 MW
315067 1DARBY 1 50/50 3.12 MW 3.12 MW
315068 1DARBY 2 50/50 3.13 MW 3.13 MW
315069 1DARBY 3 50/50 3.14 MW 3.14 MW
315070 1DARBY 4 50/50 3.14 MW 3.14 MW
315073 1STONECA Adder 7.85 MW 6.67 MW
315083 1SPRUNCA Adder 9.35 MW 7.95 MW
315084 1SPRUNCB Adder 9.35 MW 7.95 MW
315092 1YORKTN3 Adder 160.64 MW 136.54 MW
925865 AC1-065 E Adder 20.0 MW 17.0 MW
926412 AC1-112 E 50/50 1.48 MW 1.48 MW
926662 AC1-147 E Adder 1.43 MW 1.22 MW
926755 AC1-161 E Adder 14.38 MW 12.23 MW
927226 AC1-216 E Adder 8.74 MW 7.43 MW
934392 AD1-063 E Adder 1.3 MW 1.11 MW
934782 AD1-105 E Adder 4.71 MW 4.01 MW
935112 AD1-144 E Adder 1.02 MW 0.87 MW
936582 AD2-073 E Adder 1.06 MW 0.9 MW
936591 AD2-074 C Adder 6.22 MW 5.29 MW
936592 AD2-074 E Adder 10.14 MW 8.62 MW
942341 AE2-247 C Adder 1.56 MW 1.32 MW
942342 AE2-247 E Adder 2.15 MW 1.83 MW
943461 AF1-017 C Adder 1.41 MW 1.2 MW
943462 AF1-017 E Adder 2.3 MW 1.95 MW
943612 AF1-032 E Adder 0.98 MW 0.83 MW
943741 AF1-042 C Adder 3.25 MW 2.77 MW
943742 AF1-042 E Adder 5.31 MW 4.51 MW
961951 AG1-038 C Adder 3.6 MW 3.06 MW
961952 AG1-038 E Adder 4.97 MW 4.22 MW
966661 AG1-536 C Adder 5.88 MW 5.0 MW
966662 AG1-536 E Adder 7.91 MW 6.72 MW
966871 AG1-558 C Adder 2.9 MW 2.46 MW
966872 AG1-558 E Adder 1.46 MW 1.24 MW
315216 1CUNINGA 50/50 7.76 MW 7.76 MW
315217 1CUNINGB 50/50 7.76 MW 7.76 MW
315218 1CUNINGC 50/50 7.76 MW 7.76 MW
315219 1CUNINGD 50/50 17.35 MW 17.35 MW
315233 1SURRY 2 50/50 30.59 MW 30.59 MW
315260 1GOSPORTA Adder 2.3 MW 1.96 MW
315261 1GOSPORTB Adder 2.94 MW 2.5 MW
315262 1GOSPORTC Adder 2.5 MW 2.12 MW
316075 AC2-137 C 50/50 0.49 MW 0.49 MW
316076 AC2-137 E 50/50 1.73 MW 1.73 MW
316078 AC2-138 E Adder 1.01 MW 0.85 MW
316157 AD2-030 E Adder 1.41 MW 1.2 MW
913392 Y1-086 E Adder 2.31 MW 1.96 MW
916192 Z1-068 E Adder 2.02 MW 1.72 MW
923832 AB2-022 E Adder 1.3 MW 1.11 MW
923842 AB2-024 E 50/50 2.21 MW 2.21 MW
923852 AB2-025 E Adder 0.97 MW 0.83 MW
930122 AB1-027 E 50/50 1.82 MW 1.82 MW
938552 AE1-074 E Adder 1.06 MW 0.9 MW
939312 AE1-162 E Adder 1.59 MW 1.35 MW
946262 AF1-291 E Adder 1.54 MW 1.31 MW
957492 AF2-043 E Adder 1.51 MW 1.28 MW
957601 AF2-054 C Adder 2.52 MW 2.14 MW
957602 AF2-054 E Adder 1.68 MW 1.43 MW
962861 AG1-135 C Adder 6.67 MW 5.67 MW
962862 AG1-135 E Adder 4.45 MW 3.78 MW
962962 AG1-145 E 50/50 1.82 MW 1.82 MW
962971 AG1-146 C Adder 3.49 MW 2.97 MW
962972 AG1-146 E Adder 2.33 MW 1.98 MW
962981 AG1-147 C Adder 8.15 MW 6.92 MW
962982 AG1-147 E Adder 5.43 MW 4.62 MW
963611 AG1-210 C Adder 0.72 MW 0.61 MW
963612 AG1-210 E Adder 1.08 MW 0.92 MW
964211 AG1-282 C Adder 2.22 MW 1.89 MW
964212 AG1-282 E Adder 1.48 MW 1.26 MW
901082 W1-029 E Adder 33.14 MW 28.17 MW
917122 Z2-027 E Adder 1.41 MW 1.2 MW
925332 AB2-190 E Adder 9.15 MW 7.78 MW
925522 AC1-027 E Adder 1.31 MW 1.11 MW
942001 AE2-212 C Adder 2.22 MW 1.89 MW
942002 AE2-212 E Adder 1.48 MW 1.26 MW
957832 AF2-077 E Adder 1.72 MW 1.46 MW
957871 AF2-081 C Adder 10.64 MW 9.04 MW
957872 AF2-081 E Adder 4.56 MW 3.88 MW
958161 AF2-110 C Adder 1.43 MW 1.22 MW
958162 AF2-110 E Adder 2.28 MW 1.94 MW
313811 6ELKO L286 50/50 1.8 MW 1.8 MW
314181 3NORNECK Adder 0.96 MW 0.81 MW
933291 AC2-141 C Adder 33.69 MW 28.64 MW
933292 AC2-141 E Adder 14.38 MW 12.23 MW
939411 AE1-173 C Adder 76.23 MW 64.8 MW
939412 AE1-173 E Adder 50.82 MW 43.2 MW
934012 AD1-025 E Adder 11.31 MW 9.62 MW
927041 AC1-191 C Adder 11.63 MW 9.88 MW
927042 AC1-191 E Adder 5.79 MW 4.92 MW
933981 AD1-022 C Adder 8.32 MW 7.07 MW
933982 AD1-022 E Adder 4.53 MW 3.85 MW
961681 AG1-008 C Adder 13.16 MW 11.19 MW
961682 AG1-008 E Adder 6.65 MW 5.65 MW
313053 6PAPERMILL 50/50 8.16 MW 8.16 MW
314594 6PLYMOUTH TP Adder 0.31 MW 0.26 MW
314632 6AYDLETT TAP Adder 1.44 MW 1.22 MW
316004 AC1-112 C 50/50 0.43 MW 0.43 MW
316159 AE1-175 C 50/50 0.5 MW 0.5 MW
316160 AE1-175 E 50/50 1.51 MW 1.51 MW
316169 AC1-164 GEN 50/50 53.91 MW 53.91 MW
316233 AE1-074 C Adder 2.11 MW 1.79 MW
316240 AF1-291 C Adder 2.31 MW 1.97 MW
316312 AB1-027 C 50/50 0.69 MW 0.69 MW
316314 AB2-024 C 50/50 0.36 MW 0.36 MW
316382 AG1-145 C 50/50 0.45 MW 0.45 MW
917332 KELFORD E Adder 1.51 MW 1.28 MW
924516 AB2-100 E1 Adder 1.64 MW 1.39 MW
926206 AC1-098 E Adder 3.32 MW 2.82 MW
926214 AC1-099 E Adder 1.1 MW 0.93 MW
926785 AC1-164_E 50/50 24.22 MW 24.22 MW
934065 AD1-033 E Adder 5.39 MW 4.58 MW
937226 AE2-253 E Adder 6.24 MW 5.3 MW
939612 AE1-191 E Adder 6.81 MW 5.79 MW
939246 AE1-155 E Adder 9.52 MW 8.1 MW
918512 AA1-065 E OP Adder 5.11 MW 4.34 MW
919153 AA1-139 E2 Adder 4.35 MW 3.7 MW
919152 AA1-139 E1 Adder 4.35 MW 3.7 MW
919710 AA2-057 E Adder 3.66 MW 3.11 MW
920692 AA2-178 E Adder 4.04 MW 3.43 MW
924814 AB2-134 E Adder 14.31 MW 12.17 MW
316084 AB2-161 E Adder 5.72 MW 4.86 MW
925122 AB2-169 E Adder 5.21 MW 4.43 MW
932046 AC2-012 E Adder 14.16 MW 12.04 MW
316311 AC2-079 C Adder 5.98 MW 5.09 MW
932596 AC2-079 E Adder 9.76 MW 8.3 MW
934146 AD1-041 E Adder 4.26 MW 3.62 MW
934576 AD1-082 E Adder 4.55 MW 3.87 MW
316349 AD2-085 C Adder 3.59 MW 3.05 MW
936666 AD2-085 E Adder 5.86 MW 4.98 MW
961611 AG1-000B C Adder 17.95 MW 15.26 MW
941591 AE2-156 C Adder 19.35 MW 16.45 MW
944581 AF1-123 C Adder 48.7 MW 41.39 MW
944582 AF1-123 E Adder 111.51 MW 94.78 MW
944591 AF1-124 C Adder 48.87 MW 41.54 MW
944592 AF1-124 E Adder 111.92 MW 95.13 MW
944601 AF1-125 C Adder 47.95 MW 40.76 MW
944602 AF1-125 E Adder 109.76 MW 93.3 MW
944631 AF1-128 C Adder 48.08 MW 40.87 MW
958261 AF2-120 C Adder 6.84 MW 5.81 MW
958262 AF2-120 E Adder 4.56 MW 3.88 MW
965281 AG1-393 C Adder 2.28 MW 1.94 MW
965282 AG1-393 E Adder 1.52 MW 1.29 MW
932632 AC2-084 E Adder 2.94 MW 2.5 MW
934501 AD1-074 C Adder 32.31 MW 27.47 MW
934502 AD1-074 E Adder 16.45 MW 13.98 MW
934511 AD1-075 C Adder 8.08 MW 6.87 MW
934512 AD1-075 E Adder 4.11 MW 3.5 MW
935161 AD1-151 C Adder 18.28 MW 15.54 MW
935162 AD1-151 E Adder 12.19 MW 10.36 MW
938531 AE1-072 C Adder 18.67 MW 15.87 MW
938532 AE1-072 E Adder 9.73 MW 8.27 MW
939191 AE1-149 C Adder 11.03 MW 9.37 MW
939192 AE1-149 E Adder 7.35 MW 6.25 MW
939602 AE1-190 E Adder 1.7 MW 1.45 MW
940431 AE2-027 C Adder 13.84 MW 11.76 MW
940432 AE2-027 E Adder 9.22 MW 7.84 MW
940481 AE2-033 C Adder 13.54 MW 11.51 MW
940482 AE2-033 E Adder 9.13 MW 7.76 MW
940541 AE2-040 C Adder 2.4 MW 2.04 MW
940551 AE2-041 C Adder 8.7 MW 7.39 MW
940641 AE2-051 C Adder 13.3 MW 11.31 MW
940642 AE2-051 E Adder 8.87 MW 7.54 MW
941101 AE2-104 C Adder 3.51 MW 2.99 MW
941102 AE2-104 E Adder 5.59 MW 4.75 MW
943471 AF1-018 C Adder 8.7 MW 7.39 MW
944641 AF1-129 C Adder 110.92 MW 94.28 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 32.18 MW 32.18 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 19.78 MW 19.78 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 70.82 MW 70.82 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 4.73 MW 4.73 MW
NY PJM->LTFIMP_NY CLTF 2.13 MW 2.13 MW
LGEE LTFEXP_LGEE->PJM CLTF 1.28 MW 1.28 MW
WEC LTFEXP_WEC->PJM CLTF 0.66 MW 0.66 MW
CPLE LTFEXP_CPLE->PJM CLTF 8.27 MW 8.27 MW
TVA LTFEXP_TVA->PJM CLTF 5.13 MW 5.13 MW
MEC LTFEXP_MEC->PJM CLTF 3.76 MW 3.76 MW
LAGN LTFEXP_LAGN->PJM CLTF 6.44 MW 6.44 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.24 MW 0.24 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 30.03 MW 30.03 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 3.94 MW 3.94 MW

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
314181 to 314182 ckt 2
Contingency Name:
Base Case
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 145.8 %
Rating: 170.05 MVA
Rating Type: A
MVA to Mitigate: 247.94 MVA
MW Contribution: 24.67 MW
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area: DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
314181 to 314182 ckt 2
Contingency Name:
Base Case
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 121.97 %
Rating: 170.05 MVA
Rating Type: A
MVA to Mitigate: 207.41 MVA
MW Contribution: 21.65 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
315034 1NORNECKC1 50/50 1.8 MW 1.8 MW
315035 1NORNECKC2 50/50 1.74 MW 1.74 MW
925865 AC1-065 E Adder 6.1 MW 5.19 MW
936591 AD2-074 C 50/50 10.74 MW 10.74 MW
936592 AD2-074 E 50/50 17.53 MW 17.53 MW
943741 AF1-042 C 50/50 5.62 MW 5.62 MW
943742 AF1-042 E 50/50 9.17 MW 9.17 MW
961951 AG1-038 C 50/50 6.21 MW 6.21 MW
961952 AG1-038 E 50/50 8.58 MW 8.58 MW
966661 AG1-536 C 50/50 12.73 MW 12.73 MW
966662 AG1-536 E 50/50 17.11 MW 17.11 MW
316077 AC2-138 C 50/50 0.61 MW 0.61 MW
316078 AC2-138 E 50/50 2.48 MW 2.48 MW
316156 AD2-030 C 50/50 0.22 MW 0.22 MW
316157 AD2-030 E 50/50 0.69 MW 0.69 MW
957601 AF2-054 C 50/50 1.23 MW 1.23 MW
957602 AF2-054 E 50/50 0.82 MW 0.82 MW
962861 AG1-135 C 50/50 13.74 MW 13.74 MW
962862 AG1-135 E 50/50 9.16 MW 9.16 MW
962971 AG1-146 C 50/50 5.19 MW 5.19 MW
962972 AG1-146 E 50/50 3.46 MW 3.46 MW
962981 AG1-147 C 50/50 12.12 MW 12.12 MW
962982 AG1-147 E 50/50 8.08 MW 8.08 MW
963611 AG1-210 C 50/50 1.77 MW 1.77 MW
963612 AG1-210 E 50/50 2.66 MW 2.66 MW
314181 3NORNECK 50/50 2.36 MW 2.36 MW
939612 AE1-191 E Adder 2.62 MW 2.23 MW
316404 AE1-155 C 50/50 5.02 MW 5.02 MW
939246 AE1-155 E 50/50 20.61 MW 20.61 MW
934146 AD1-041 E Adder 1.64 MW 1.39 MW
958261 AF2-120 C 50/50 14.8 MW 14.8 MW
958262 AF2-120 E 50/50 9.87 MW 9.87 MW
939602 AE1-190 E Adder 0.66 MW 0.56 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 0.3 MW 0.3 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.07 MW 0.07 MW
NY PJM->LTFIMP_NY CLTF 0.04 MW 0.04 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.01 MW 0.01 MW
CPLE LTFEXP_CPLE->PJM CLTF 0.05 MW 0.05 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.05 MW 0.05 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.01 MW 0.01 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.04 MW 0.04 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.45 MW 0.45 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.02 MW 0.02 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.02 MW 0.02 MW

Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
314286 to 314309 ckt 1
Contingency Name:
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 122.25 %
Rating: 663.64 MVA
Rating Type: B
MVA to Mitigate: 811.33 MVA
MW Contribution: 4.53 MW
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area: DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
314286 to 314309 ckt 1
Contingency Name:
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 120.34 %
Rating: 663.64 MVA
Rating Type: B
MVA to Mitigate: 798.65 MVA
MW Contribution: 4.5 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314539 3UNCAMP Adder 1.77 MW 1.51 MW
916042 Z1-036 E Adder 8.51 MW 7.23 MW
938771 AE1-103 C Adder 0.87 MW 0.74 MW
938772 AE1-103 E Adder 1.2 MW 1.02 MW
314507 3THOMPSN Adder 0.68 MW 0.58 MW
314525 6KINGFORK Adder 0.36 MW 0.3 MW
314550 6HICKORY Adder 0.7 MW 0.59 MW
315060 1CHESTF5 50/50 79.72 MW 79.72 MW
315061 1CHESTG7 50/50 4.86 MW 4.86 MW
315062 1CHESTS7 50/50 2.23 MW 2.23 MW
315063 1CHESTG8 50/50 4.79 MW 4.79 MW
315064 1CHESTS8 50/50 2.46 MW 2.46 MW
315073 1STONECA 50/50 4.67 MW 4.67 MW
315076 1HOPPOLC 50/50 1.04 MW 1.04 MW
315077 1HOPHCF1 50/50 1.65 MW 1.65 MW
315078 1HOPHCF2 50/50 1.65 MW 1.65 MW
315079 1HOPHCF3 50/50 1.65 MW 1.65 MW
315080 1HOPHCF4 50/50 2.5 MW 2.5 MW
315092 1YORKTN3 Adder 54.33 MW 46.18 MW
925865 AC1-065 E Adder 7.58 MW 6.44 MW
926472 AC1-118 E Adder 0.4 MW 0.34 MW
926662 AC1-147 E Adder 0.45 MW 0.38 MW
926755 AC1-161 E Adder 3.95 MW 3.36 MW
927226 AC1-216 E 50/50 4.35 MW 4.35 MW
934392 AD1-063 E Adder 0.51 MW 0.43 MW
935112 AD1-144 E Adder 0.33 MW 0.28 MW
936582 AD2-073 E Adder 0.44 MW 0.37 MW
936591 AD2-074 C Adder 2.44 MW 2.08 MW
936592 AD2-074 E Adder 3.99 MW 3.39 MW
942341 AE2-247 C Adder 0.5 MW 0.42 MW
942342 AE2-247 E Adder 0.68 MW 0.58 MW
943461 AF1-017 C Adder 0.45 MW 0.38 MW
943462 AF1-017 E Adder 0.73 MW 0.62 MW
943612 AF1-032 E Adder 0.3 MW 0.25 MW
943741 AF1-042 C Adder 1.28 MW 1.09 MW
943742 AF1-042 E Adder 2.09 MW 1.77 MW
961951 AG1-038 C Adder 1.41 MW 1.2 MW
961952 AG1-038 E Adder 1.95 MW 1.66 MW
966661 AG1-536 C Adder 2.34 MW 1.99 MW
966662 AG1-536 E Adder 3.14 MW 2.67 MW
315260 1GOSPORTA Adder 0.72 MW 0.61 MW
315261 1GOSPORTB Adder 0.92 MW 0.78 MW
315262 1GOSPORTC Adder 0.78 MW 0.66 MW
316076 AC2-137 E Adder 0.53 MW 0.45 MW
316078 AC2-138 E Adder 0.4 MW 0.34 MW
316132 AB2-190 C 50/50 2.52 MW 2.52 MW
316157 AD2-030 E Adder 0.54 MW 0.46 MW
913392 Y1-086 E Adder 0.69 MW 0.59 MW
916192 Z1-068 E Adder 0.62 MW 0.53 MW
923832 AB2-022 E Adder 0.39 MW 0.33 MW
923842 AB2-024 E Adder 0.87 MW 0.74 MW
939312 AE1-162 E Adder 0.6 MW 0.51 MW
957492 AF2-043 E Adder 0.46 MW 0.39 MW
957601 AF2-054 C Adder 0.96 MW 0.81 MW
957602 AF2-054 E Adder 0.64 MW 0.54 MW
962861 AG1-135 C Adder 2.65 MW 2.25 MW
962862 AG1-135 E Adder 1.76 MW 1.5 MW
962962 AG1-145 E Adder 0.66 MW 0.56 MW
962971 AG1-146 C Adder 1.36 MW 1.16 MW
962972 AG1-146 E Adder 0.91 MW 0.77 MW
962981 AG1-147 C Adder 3.18 MW 2.71 MW
962982 AG1-147 E Adder 2.12 MW 1.8 MW
963611 AG1-210 C Adder 0.29 MW 0.24 MW
963612 AG1-210 E Adder 0.43 MW 0.37 MW
964211 AG1-282 C Adder 0.89 MW 0.76 MW
964212 AG1-282 E Adder 0.6 MW 0.51 MW
901082 W1-029 E Adder 9.91 MW 8.42 MW
917122 Z2-027 E Adder 0.42 MW 0.36 MW
925332 AB2-190 E 50/50 4.91 MW 4.91 MW
925522 AC1-027 E Adder 0.4 MW 0.34 MW
957832 AF2-077 E Adder 0.61 MW 0.52 MW
957871 AF2-081 C Adder 3.18 MW 2.71 MW
957872 AF2-081 E Adder 1.36 MW 1.16 MW
958161 AF2-110 C Adder 0.44 MW 0.38 MW
958162 AF2-110 E Adder 0.7 MW 0.6 MW
313811 6ELKO L286 Adder 0.55 MW 0.47 MW
314181 3NORNECK Adder 0.38 MW 0.33 MW
933291 AC2-141 C Adder 9.25 MW 7.86 MW
933292 AC2-141 E Adder 3.95 MW 3.36 MW
934011 AD1-025 C 50/50 1.46 MW 1.46 MW
934012 AD1-025 E 50/50 5.63 MW 5.63 MW
313053 6PAPERMILL Adder 3.2 MW 2.72 MW
314632 6AYDLETT TAP Adder 0.43 MW 0.37 MW
316160 AE1-175 E Adder 0.54 MW 0.46 MW
316169 AC1-164 GEN 50/50 22.39 MW 22.39 MW
316369 AC1-216 C 50/50 0.9 MW 0.9 MW
926785 AC1-164_E 50/50 10.06 MW 10.06 MW
934065 AD1-033 E Adder 1.62 MW 1.38 MW
937226 AE2-253 E Adder 1.87 MW 1.59 MW
939612 AE1-191 E Adder 2.59 MW 2.2 MW
939246 AE1-155 E Adder 3.79 MW 3.22 MW
919153 AA1-139 E2 Adder 1.3 MW 1.11 MW
919152 AA1-139 E1 Adder 1.3 MW 1.11 MW
316033 AB2-134 GEN 50/50 1.18 MW 1.18 MW
924814 AB2-134 E 50/50 7.12 MW 7.12 MW
316084 AB2-161 E Adder 1.92 MW 1.63 MW
932046 AC2-012 E Adder 4.42 MW 3.75 MW
316311 AC2-079 C Adder 1.9 MW 1.61 MW
932596 AC2-079 E Adder 3.1 MW 2.63 MW
934146 AD1-041 E Adder 1.62 MW 1.37 MW
934576 AD1-082 E Adder 1.53 MW 1.3 MW
316349 AD2-085 C Adder 1.14 MW 0.97 MW
936666 AD2-085 E Adder 1.87 MW 1.59 MW
961611 AG1-000B C Adder 7.87 MW 6.69 MW
941591 AE2-156 C Adder 6.02 MW 5.12 MW
944581 AF1-123 C Adder 14.58 MW 12.39 MW
944582 AF1-123 E Adder 33.39 MW 28.38 MW
944591 AF1-124 C Adder 14.63 MW 12.44 MW
944592 AF1-124 E Adder 33.51 MW 28.48 MW
944601 AF1-125 C Adder 14.36 MW 12.2 MW
944602 AF1-125 E Adder 32.86 MW 27.93 MW
944631 AF1-128 C 50/50 49.88 MW 49.88 MW
958261 AF2-120 C Adder 2.72 MW 2.31 MW
958262 AF2-120 E Adder 1.81 MW 1.54 MW
965281 AG1-393 C Adder 0.66 MW 0.56 MW
965282 AG1-393 E Adder 0.44 MW 0.38 MW
935161 AD1-151 C 50/50 9.47 MW 9.47 MW
935162 AD1-151 E 50/50 6.31 MW 6.31 MW
938531 AE1-072 C Adder 5.58 MW 4.75 MW
938532 AE1-072 E Adder 2.91 MW 2.47 MW
939191 AE1-149 C Adder 3.84 MW 3.26 MW
939192 AE1-149 E Adder 2.56 MW 2.17 MW
939602 AE1-190 E Adder 0.65 MW 0.55 MW
940431 AE2-027 C Adder 3.98 MW 3.38 MW
940432 AE2-027 E Adder 2.65 MW 2.25 MW
940551 AE2-041 C Adder 3.38 MW 2.88 MW
941101 AE2-104 C Adder 1.08 MW 0.92 MW
941102 AE2-104 E Adder 1.72 MW 1.46 MW
943471 AF1-018 C Adder 3.38 MW 2.88 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 0.5 MW 0.5 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 1.74 MW 1.74 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 12.92 MW 12.92 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.57 MW 0.57 MW
NY PJM->LTFIMP_NY CLTF 0.28 MW 0.28 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.03 MW 0.03 MW
WEC LTFEXP_WEC->PJM CLTF 0.01 MW 0.01 MW
CPLE LTFEXP_CPLE->PJM CLTF 1.71 MW 1.71 MW
TVA LTFEXP_TVA->PJM CLTF 0.56 MW 0.56 MW
MEC LTFEXP_MEC->PJM CLTF 0.19 MW 0.19 MW
LAGN LTFEXP_LAGN->PJM CLTF 0.73 MW 0.73 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.01 MW 0.01 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 3.65 MW 3.65 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.81 MW 0.81 MW

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
314181 to 314182 ckt 1
Contingency Name:
Base Case
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 125.3 %
Rating: 171.17 MVA
Rating Type: A
MVA to Mitigate: 214.47 MVA
MW Contribution: 20.51 MW
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area: DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
314181 to 314182 ckt 1
Contingency Name:
Base Case
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 119.12 %
Rating: 171.17 MVA
Rating Type: A
MVA to Mitigate: 203.9 MVA
MW Contribution: 18.0 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
315034 1NORNECKC1 50/50 1.5 MW 1.5 MW
315035 1NORNECKC2 50/50 1.44 MW 1.44 MW
925865 AC1-065 E Adder 5.07 MW 4.31 MW
936591 AD2-074 C 50/50 8.93 MW 8.93 MW
936592 AD2-074 E 50/50 14.57 MW 14.57 MW
943741 AF1-042 C 50/50 4.67 MW 4.67 MW
943742 AF1-042 E 50/50 7.62 MW 7.62 MW
961951 AG1-038 C 50/50 5.16 MW 5.16 MW
961952 AG1-038 E 50/50 7.13 MW 7.13 MW
966661 AG1-536 C 50/50 10.58 MW 10.58 MW
966662 AG1-536 E 50/50 14.22 MW 14.22 MW
316077 AC2-138 C 50/50 0.51 MW 0.51 MW
316078 AC2-138 E 50/50 2.06 MW 2.06 MW
316157 AD2-030 E Adder 0.58 MW 0.49 MW
957601 AF2-054 C Adder 1.03 MW 0.87 MW
957602 AF2-054 E Adder 0.68 MW 0.58 MW
962861 AG1-135 C 50/50 11.42 MW 11.42 MW
962862 AG1-135 E 50/50 7.62 MW 7.62 MW
962971 AG1-146 C 50/50 4.32 MW 4.32 MW
962972 AG1-146 E 50/50 2.88 MW 2.88 MW
962981 AG1-147 C 50/50 10.07 MW 10.07 MW
962982 AG1-147 E 50/50 6.71 MW 6.71 MW
963611 AG1-210 C 50/50 1.47 MW 1.47 MW
963612 AG1-210 E 50/50 2.21 MW 2.21 MW
314181 3NORNECK 50/50 1.96 MW 1.96 MW
939612 AE1-191 E Adder 2.18 MW 1.85 MW
316404 AE1-155 C 50/50 4.17 MW 4.17 MW
939246 AE1-155 E 50/50 17.13 MW 17.13 MW
934146 AD1-041 E Adder 1.36 MW 1.16 MW
958261 AF2-120 C 50/50 12.3 MW 12.3 MW
958262 AF2-120 E 50/50 8.2 MW 8.2 MW
939602 AE1-190 E Adder 0.54 MW 0.46 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 0.25 MW 0.25 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.06 MW 0.06 MW
NY PJM->LTFIMP_NY CLTF 0.03 MW 0.03 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.01 MW 0.01 MW
CPLE LTFEXP_CPLE->PJM CLTF 0.04 MW 0.04 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.04 MW 0.04 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.01 MW 0.01 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.03 MW 0.03 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.38 MW 0.38 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.02 MW 0.02 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.02 MW 0.02 MW

Details for 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
314236 to 314218 ckt 1
Contingency Name:
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 122.86 %
Rating: 678.68 MVA
Rating Type: B
MVA to Mitigate: 833.8 MVA
MW Contribution: 5.25 MW
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area: DVP
Facility Description:
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
314236 to 314218 ckt 1
Contingency Name:
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 116.62 %
Rating: 678.68 MVA
Rating Type: B
MVA to Mitigate: 791.44 MVA
MW Contribution: 5.06 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961941 AG1-037 C Adder 0.2 MW 0.17 MW
961942 AG1-037 E Adder 0.13 MW 0.11 MW
962331 AG1-082 C Adder 0.78 MW 0.67 MW
962332 AG1-082 E Adder 0.52 MW 0.44 MW
965291 AG1-394 C Adder 0.34 MW 0.29 MW
965292 AG1-394 E Adder 0.62 MW 0.53 MW
314541 3WATKINS Adder 0.28 MW 0.24 MW
918492 AA1-063AE OP Adder 1.55 MW 1.32 MW
920042 AA2-088 E OP Adder 4.23 MW 3.59 MW
934521 AD1-076 C Adder 4.85 MW 4.12 MW
934522 AD1-076 E Adder 2.47 MW 2.1 MW
943172 AE2-346 E Adder 0.24 MW 0.2 MW
316141 AB2-099 E Adder 0.1 MW 0.08 MW
900672 V4-068 E Adder 0.14 MW 0.12 MW
940492 AE2-034 E Adder 1.25 MW 1.06 MW
957521 AF2-046 C Adder 5.57 MW 4.73 MW
957522 AF2-046 E Adder 2.81 MW 2.39 MW
314539 3UNCAMP Adder 2.53 MW 2.15 MW
916042 Z1-036 E Adder 11.83 MW 10.05 MW
938771 AE1-103 C Adder 1.23 MW 1.05 MW
938772 AE1-103 E Adder 1.7 MW 1.45 MW
314236 6NRTHEST 50/50 0.41 MW 0.41 MW
314331 6POE Adder 0.69 MW 0.59 MW
314507 3THOMPSN Adder 0.88 MW 0.75 MW
314525 6KINGFORK Adder 0.45 MW 0.39 MW
314550 6HICKORY Adder 0.94 MW 0.8 MW
315060 1CHESTF5 Adder 33.53 MW 28.5 MW
315065 1CHESTF6 Adder 12.06 MW 10.25 MW
315067 1DARBY 1 50/50 5.13 MW 5.13 MW
315068 1DARBY 2 50/50 5.14 MW 5.14 MW
315069 1DARBY 3 50/50 5.16 MW 5.16 MW
315070 1DARBY 4 50/50 5.17 MW 5.17 MW
315073 1STONECA Adder 3.82 MW 3.25 MW
315083 1SPRUNCA 50/50 10.71 MW 10.71 MW
315084 1SPRUNCB 50/50 10.71 MW 10.71 MW
315092 1YORKTN3 Adder 65.96 MW 56.06 MW
925865 AC1-065 E Adder 9.35 MW 7.95 MW
926472 AC1-118 E Adder 0.45 MW 0.38 MW
926662 AC1-147 E Adder 0.58 MW 0.49 MW
926755 AC1-161 E Adder 5.53 MW 4.7 MW
927226 AC1-216 E Adder 4.01 MW 3.41 MW
934392 AD1-063 E Adder 0.6 MW 0.51 MW
935112 AD1-144 E Adder 0.42 MW 0.36 MW
936582 AD2-073 E Adder 0.49 MW 0.42 MW
936591 AD2-074 C Adder 2.86 MW 2.43 MW
936592 AD2-074 E Adder 4.66 MW 3.96 MW
942341 AE2-247 C Adder 0.68 MW 0.58 MW
942342 AE2-247 E Adder 0.95 MW 0.8 MW
943461 AF1-017 C Adder 0.62 MW 0.53 MW
943462 AF1-017 E Adder 1.01 MW 0.86 MW
943612 AF1-032 E Adder 0.4 MW 0.34 MW
943741 AF1-042 C Adder 1.49 MW 1.27 MW
943742 AF1-042 E Adder 2.44 MW 2.07 MW
961951 AG1-038 C Adder 1.65 MW 1.4 MW
961952 AG1-038 E Adder 2.28 MW 1.94 MW
966661 AG1-536 C Adder 2.71 MW 2.3 MW
966662 AG1-536 E Adder 3.64 MW 3.1 MW
315260 1GOSPORTA Adder 0.93 MW 0.79 MW
315261 1GOSPORTB Adder 1.19 MW 1.01 MW
315262 1GOSPORTC Adder 1.01 MW 0.86 MW
316075 AC2-137 C 50/50 0.44 MW 0.44 MW
316076 AC2-137 E 50/50 1.54 MW 1.54 MW
316078 AC2-138 E Adder 0.46 MW 0.4 MW
316157 AD2-030 E Adder 0.64 MW 0.55 MW
913392 Y1-086 E Adder 0.93 MW 0.79 MW
916192 Z1-068 E Adder 0.82 MW 0.69 MW
923832 AB2-022 E Adder 0.53 MW 0.45 MW
923842 AB2-024 E Adder 1.02 MW 0.87 MW
923852 AB2-025 E Adder 0.47 MW 0.4 MW
939312 AE1-162 E Adder 0.67 MW 0.57 MW
946262 AF1-291 E Adder 0.87 MW 0.74 MW
957492 AF2-043 E Adder 0.62 MW 0.52 MW
957601 AF2-054 C Adder 1.15 MW 0.98 MW
957602 AF2-054 E Adder 0.77 MW 0.65 MW
962861 AG1-135 C Adder 3.07 MW 2.61 MW
962862 AG1-135 E Adder 2.05 MW 1.74 MW
962962 AG1-145 E Adder 0.78 MW 0.67 MW
962971 AG1-146 C Adder 1.6 MW 1.36 MW
962972 AG1-146 E Adder 1.07 MW 0.91 MW
962981 AG1-147 C Adder 3.74 MW 3.18 MW
962982 AG1-147 E Adder 2.49 MW 2.12 MW
963611 AG1-210 C Adder 0.33 MW 0.28 MW
963612 AG1-210 E Adder 0.5 MW 0.42 MW
964211 AG1-282 C Adder 1.03 MW 0.87 MW
964212 AG1-282 E Adder 0.68 MW 0.58 MW
901082 W1-029 E Adder 13.49 MW 11.46 MW
917122 Z2-027 E Adder 0.57 MW 0.48 MW
925332 AB2-190 E Adder 4.3 MW 3.66 MW
925522 AC1-027 E Adder 0.53 MW 0.45 MW
942001 AE2-212 C Adder 1.23 MW 1.05 MW
942002 AE2-212 E Adder 0.82 MW 0.7 MW
957832 AF2-077 E Adder 0.74 MW 0.63 MW
957871 AF2-081 C Adder 4.28 MW 3.64 MW
957872 AF2-081 E Adder 1.83 MW 1.56 MW
958161 AF2-110 C Adder 0.6 MW 0.51 MW
958162 AF2-110 E Adder 0.95 MW 0.81 MW
313811 6ELKO L286 50/50 1.6 MW 1.6 MW
314181 3NORNECK Adder 0.44 MW 0.38 MW
933291 AC2-141 C Adder 12.95 MW 11.01 MW
933292 AC2-141 E Adder 5.53 MW 4.7 MW
939411 AE1-173 C Adder 32.71 MW 27.8 MW
939412 AE1-173 E Adder 21.8 MW 18.53 MW
934012 AD1-025 E Adder 5.19 MW 4.41 MW
933981 AD1-022 C Adder 3.45 MW 2.93 MW
933982 AD1-022 E Adder 1.88 MW 1.6 MW
961681 AG1-008 C Adder 5.57 MW 4.73 MW
961682 AG1-008 E Adder 2.81 MW 2.39 MW
313053 6PAPERMILL Adder 3.76 MW 3.19 MW
314594 6PLYMOUTH TP Adder 0.13 MW 0.11 MW
314632 6AYDLETT TAP Adder 0.58 MW 0.49 MW
316160 AE1-175 E Adder 0.65 MW 0.55 MW
316169 AC1-164 GEN 50/50 25.4 MW 25.4 MW
316240 AF1-291 C Adder 1.3 MW 1.11 MW
917332 KELFORD E Adder 0.64 MW 0.54 MW
924516 AB2-100 E1 Adder 1.12 MW 0.95 MW
924517 AB2-100 E2 Adder 1.12 MW 0.95 MW
926785 AC1-164_E 50/50 11.41 MW 11.41 MW
934065 AD1-033 E Adder 2.16 MW 1.84 MW
937226 AE2-253 E Adder 2.51 MW 2.13 MW
939612 AE1-191 E Adder 3.15 MW 2.68 MW
939246 AE1-155 E Adder 4.39 MW 3.73 MW
918512 AA1-065 E OP Adder 2.14 MW 1.82 MW
919153 AA1-139 E2 Adder 1.75 MW 1.49 MW
919152 AA1-139 E1 Adder 1.75 MW 1.49 MW
920692 AA2-178 E Adder 1.66 MW 1.41 MW
924814 AB2-134 E Adder 6.56 MW 5.58 MW
316084 AB2-161 E Adder 2.72 MW 2.31 MW
932046 AC2-012 E Adder 5.73 MW 4.87 MW
316311 AC2-079 C Adder 2.62 MW 2.22 MW
932596 AC2-079 E Adder 4.27 MW 3.63 MW
934146 AD1-041 E Adder 1.97 MW 1.67 MW
934576 AD1-082 E Adder 2.17 MW 1.84 MW
316349 AD2-085 C Adder 1.58 MW 1.34 MW
936666 AD2-085 E Adder 2.58 MW 2.19 MW
961611 AG1-000B C Adder 7.93 MW 6.74 MW
941591 AE2-156 C Adder 7.82 MW 6.65 MW
944581 AF1-123 C Adder 19.52 MW 16.59 MW
944582 AF1-123 E Adder 44.7 MW 37.99 MW
944591 AF1-124 C Adder 19.59 MW 16.65 MW
944592 AF1-124 E Adder 44.86 MW 38.13 MW
944601 AF1-125 C Adder 19.22 MW 16.34 MW
944602 AF1-125 E Adder 44.0 MW 37.4 MW
944631 AF1-128 C Adder 20.98 MW 17.83 MW
958261 AF2-120 C Adder 3.15 MW 2.68 MW
958262 AF2-120 E Adder 2.1 MW 1.79 MW
965281 AG1-393 C Adder 1.31 MW 1.11 MW
965282 AG1-393 E Adder 0.87 MW 0.74 MW
934501 AD1-074 C Adder 13.36 MW 11.35 MW
934502 AD1-074 E Adder 6.8 MW 5.78 MW
934511 AD1-075 C Adder 3.34 MW 2.84 MW
934512 AD1-075 E Adder 1.7 MW 1.45 MW
935161 AD1-151 C Adder 8.49 MW 7.22 MW
935162 AD1-151 E Adder 5.66 MW 4.81 MW
938531 AE1-072 C Adder 7.52 MW 6.39 MW
938532 AE1-072 E Adder 3.92 MW 3.33 MW
939191 AE1-149 C Adder 5.52 MW 4.69 MW
939192 AE1-149 E Adder 3.68 MW 3.13 MW
939602 AE1-190 E Adder 0.79 MW 0.67 MW
940431 AE2-027 C Adder 8.06 MW 6.85 MW
940432 AE2-027 E Adder 5.37 MW 4.57 MW
940481 AE2-033 C Adder 6.55 MW 5.57 MW
940482 AE2-033 E Adder 4.42 MW 3.75 MW
940541 AE2-040 C Adder 1.17 MW 0.99 MW
940551 AE2-041 C Adder 3.99 MW 3.4 MW
940641 AE2-051 C Adder 5.86 MW 4.99 MW
940642 AE2-051 E Adder 3.91 MW 3.32 MW
941101 AE2-104 C Adder 1.47 MW 1.25 MW
941102 AE2-104 E Adder 2.33 MW 1.98 MW
943471 AF1-018 C Adder 3.99 MW 3.4 MW
944641 AF1-129 C Adder 62.91 MW 53.48 MW
315085 1SPRUNCC 50/50 0.19 MW 0.19 MW
315086 1SPRUNCD 50/50 0.19 MW 0.19 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 3.49 MW 3.49 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 4.16 MW 4.16 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 24.69 MW 24.69 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.96 MW 0.96 MW
NY PJM->LTFIMP_NY CLTF 0.47 MW 0.47 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.15 MW 0.15 MW
WEC LTFEXP_WEC->PJM CLTF 0.08 MW 0.08 MW
CPLE LTFEXP_CPLE->PJM CLTF 3.17 MW 3.17 MW
TVA LTFEXP_TVA->PJM CLTF 1.23 MW 1.23 MW
MEC LTFEXP_MEC->PJM CLTF 0.59 MW 0.59 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.59 MW 1.59 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.03 MW 0.03 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 6.14 MW 6.14 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 1.51 MW 1.51 MW

Details for 3LANCAST-3OCRAN 115.0 kV Ckt 1 line l/o DVP_P1-3: 6NORNECK-TX#6_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
314178 to 313813 ckt 1
Contingency Name:
DVP_P1-3: 6NORNECK-TX#6_SRT-A
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#6_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 103.22 %
Rating: 219.96 MVA
Rating Type: B
MVA to Mitigate: 227.05 MVA
MW Contribution: 22.57 MW
Impact of Topology Modeling:
Decrease
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
315034 1NORNECKC1 50/50 1.19 MW 1.19 MW
315035 1NORNECKC2 50/50 1.15 MW 1.15 MW
936591 AD2-074 C 50/50 15.51 MW 15.51 MW
936592 AD2-074 E 50/50 25.3 MW 25.3 MW
943741 AF1-042 C 50/50 8.11 MW 8.11 MW
943742 AF1-042 E 50/50 13.24 MW 13.24 MW
961951 AG1-038 C 50/50 8.97 MW 8.97 MW
961952 AG1-038 E 50/50 12.38 MW 12.38 MW
966661 AG1-536 C 50/50 11.65 MW 11.65 MW
966662 AG1-536 E 50/50 15.65 MW 15.65 MW
316077 AC2-138 C 50/50 0.4 MW 0.4 MW
316078 AC2-138 E 50/50 1.64 MW 1.64 MW
957601 AF2-054 C Adder -1.98 MW -1.68 MW
962861 AG1-135 C 50/50 14.04 MW 14.04 MW
962862 AG1-135 E 50/50 9.36 MW 9.36 MW
962971 AG1-146 C 50/50 9.7 MW 9.7 MW
962972 AG1-146 E 50/50 6.46 MW 6.46 MW
962981 AG1-147 C 50/50 22.62 MW 22.62 MW
962982 AG1-147 E 50/50 15.08 MW 15.08 MW
963611 AG1-210 C 50/50 1.17 MW 1.17 MW
963612 AG1-210 E 50/50 1.75 MW 1.75 MW
314181 3NORNECK 50/50 1.56 MW 1.56 MW
316404 AE1-155 C 50/50 4.59 MW 4.59 MW
939246 AE1-155 E 50/50 18.85 MW 18.85 MW
958261 AF2-120 C 50/50 13.54 MW 13.54 MW
958262 AF2-120 E 50/50 9.03 MW 9.03 MW
CBM North LTFEXP_CBM-N->PJM CBM 0.04 MW 0.04 MW
G-007A LTFEXP_G-007A->PJM CMTX 0.09 MW 0.09 MW
VTF LTFEXP_VFT->PJM CMTX 0.24 MW 0.24 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.12 MW 0.12 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.08 MW 0.08 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.04 MW 0.04 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.11 MW 0.11 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.06 MW 0.06 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.11 MW 0.11 MW

Details for 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
314309 to 314338 ckt 1
Contingency Name:
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 113.21 %
Rating: 663.64 MVA
Rating Type: B
MVA to Mitigate: 751.33 MVA
MW Contribution: 4.53 MW
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area: DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
314309 to 314338 ckt 1
Contingency Name:
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 112.58 %
Rating: 663.64 MVA
Rating Type: B
MVA to Mitigate: 747.13 MVA
MW Contribution: 4.5 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314539 3UNCAMP Adder 1.77 MW 1.5 MW
916042 Z1-036 E Adder 8.5 MW 7.22 MW
938771 AE1-103 C Adder 0.87 MW 0.74 MW
938772 AE1-103 E Adder 1.2 MW 1.02 MW
314309 6IRON208 50/50 1.15 MW 1.15 MW
314507 3THOMPSN Adder 0.68 MW 0.58 MW
314525 6KINGFORK Adder 0.36 MW 0.3 MW
314550 6HICKORY Adder 0.7 MW 0.59 MW
315060 1CHESTF5 50/50 79.69 MW 79.69 MW
315061 1CHESTG7 50/50 4.86 MW 4.86 MW
315062 1CHESTS7 50/50 2.23 MW 2.23 MW
315063 1CHESTG8 50/50 4.79 MW 4.79 MW
315064 1CHESTS8 50/50 2.46 MW 2.46 MW
315073 1STONECA Adder 4.67 MW 3.97 MW
315077 1HOPHCF1 50/50 1.65 MW 1.65 MW
315078 1HOPHCF2 50/50 1.65 MW 1.65 MW
315079 1HOPHCF3 50/50 1.65 MW 1.65 MW
315080 1HOPHCF4 50/50 2.5 MW 2.5 MW
315092 1YORKTN3 Adder 54.27 MW 46.13 MW
925865 AC1-065 E Adder 7.57 MW 6.43 MW
926472 AC1-118 E Adder 0.4 MW 0.34 MW
926662 AC1-147 E Adder 0.45 MW 0.38 MW
926755 AC1-161 E Adder 3.94 MW 3.35 MW
927226 AC1-216 E Adder 4.34 MW 3.69 MW
934392 AD1-063 E Adder 0.51 MW 0.43 MW
935112 AD1-144 E Adder 0.33 MW 0.28 MW
936582 AD2-073 E Adder 0.44 MW 0.37 MW
936591 AD2-074 C Adder 2.44 MW 2.08 MW
936592 AD2-074 E Adder 3.98 MW 3.39 MW
942341 AE2-247 C Adder 0.5 MW 0.42 MW
942342 AE2-247 E Adder 0.68 MW 0.58 MW
943461 AF1-017 C Adder 0.45 MW 0.38 MW
943462 AF1-017 E Adder 0.73 MW 0.62 MW
943612 AF1-032 E Adder 0.3 MW 0.25 MW
943741 AF1-042 C Adder 1.28 MW 1.09 MW
943742 AF1-042 E Adder 2.08 MW 1.77 MW
961951 AG1-038 C Adder 1.41 MW 1.2 MW
961952 AG1-038 E Adder 1.95 MW 1.66 MW
966661 AG1-536 C Adder 2.34 MW 1.99 MW
966662 AG1-536 E Adder 3.14 MW 2.67 MW
315260 1GOSPORTA Adder 0.72 MW 0.61 MW
315261 1GOSPORTB Adder 0.92 MW 0.78 MW
315262 1GOSPORTC Adder 0.78 MW 0.66 MW
316076 AC2-137 E Adder 0.53 MW 0.45 MW
316078 AC2-138 E Adder 0.4 MW 0.34 MW
316157 AD2-030 E Adder 0.54 MW 0.46 MW
913392 Y1-086 E Adder 0.69 MW 0.59 MW
916192 Z1-068 E Adder 0.62 MW 0.53 MW
923832 AB2-022 E Adder 0.39 MW 0.33 MW
923842 AB2-024 E Adder 0.87 MW 0.74 MW
939312 AE1-162 E Adder 0.6 MW 0.51 MW
957492 AF2-043 E Adder 0.46 MW 0.39 MW
957601 AF2-054 C Adder 0.96 MW 0.81 MW
957602 AF2-054 E Adder 0.64 MW 0.54 MW
962861 AG1-135 C Adder 2.64 MW 2.25 MW
962862 AG1-135 E Adder 1.76 MW 1.5 MW
962962 AG1-145 E Adder 0.66 MW 0.56 MW
962971 AG1-146 C Adder 1.36 MW 1.16 MW
962972 AG1-146 E Adder 0.91 MW 0.77 MW
962981 AG1-147 C Adder 3.18 MW 2.7 MW
962982 AG1-147 E Adder 2.12 MW 1.8 MW
963611 AG1-210 C Adder 0.29 MW 0.24 MW
963612 AG1-210 E Adder 0.43 MW 0.37 MW
964211 AG1-282 C Adder 0.89 MW 0.76 MW
964212 AG1-282 E Adder 0.6 MW 0.51 MW
901082 W1-029 E Adder 9.9 MW 8.41 MW
917122 Z2-027 E Adder 0.42 MW 0.36 MW
925332 AB2-190 E Adder 4.9 MW 4.17 MW
925522 AC1-027 E Adder 0.4 MW 0.34 MW
957832 AF2-077 E Adder 0.61 MW 0.52 MW
957871 AF2-081 C Adder 3.18 MW 2.7 MW
957872 AF2-081 E Adder 1.36 MW 1.16 MW
958161 AF2-110 C Adder 0.44 MW 0.38 MW
958162 AF2-110 E Adder 0.7 MW 0.6 MW
313811 6ELKO L286 Adder 0.55 MW 0.47 MW
314181 3NORNECK Adder 0.38 MW 0.33 MW
933291 AC2-141 C Adder 9.24 MW 7.85 MW
933292 AC2-141 E Adder 3.94 MW 3.35 MW
934012 AD1-025 E Adder 5.62 MW 4.78 MW
313053 6PAPERMILL Adder 3.2 MW 2.72 MW
314632 6AYDLETT TAP Adder 0.43 MW 0.36 MW
316160 AE1-175 E Adder 0.54 MW 0.46 MW
316169 AC1-164 GEN Adder 22.37 MW 19.02 MW
926785 AC1-164_E Adder 10.05 MW 8.54 MW
934065 AD1-033 E Adder 1.62 MW 1.37 MW
937226 AE2-253 E Adder 1.86 MW 1.58 MW
939612 AE1-191 E Adder 2.58 MW 2.2 MW
939246 AE1-155 E Adder 3.78 MW 3.22 MW
919153 AA1-139 E2 Adder 1.3 MW 1.1 MW
919152 AA1-139 E1 Adder 1.3 MW 1.1 MW
924814 AB2-134 E Adder 7.12 MW 6.05 MW
316084 AB2-161 E Adder 1.92 MW 1.63 MW
932046 AC2-012 E Adder 4.41 MW 3.75 MW
316311 AC2-079 C Adder 1.9 MW 1.61 MW
932596 AC2-079 E Adder 3.09 MW 2.63 MW
934146 AD1-041 E Adder 1.61 MW 1.37 MW
934576 AD1-082 E Adder 1.53 MW 1.3 MW
316349 AD2-085 C Adder 1.14 MW 0.97 MW
936666 AD2-085 E Adder 1.86 MW 1.58 MW
961611 AG1-000B C Adder 7.86 MW 6.68 MW
941591 AE2-156 C Adder 6.02 MW 5.11 MW
944581 AF1-123 C Adder 14.56 MW 12.38 MW
944582 AF1-123 E Adder 33.34 MW 28.34 MW
944591 AF1-124 C Adder 14.61 MW 12.42 MW
944592 AF1-124 E Adder 33.46 MW 28.44 MW
944601 AF1-125 C Adder 14.34 MW 12.19 MW
944602 AF1-125 E Adder 32.82 MW 27.9 MW
944631 AF1-128 C 50/50 49.87 MW 49.87 MW
958261 AF2-120 C Adder 2.72 MW 2.31 MW
958262 AF2-120 E Adder 1.81 MW 1.54 MW
965281 AG1-393 C Adder 0.66 MW 0.56 MW
965282 AG1-393 E Adder 0.44 MW 0.38 MW
935161 AD1-151 C Adder 9.46 MW 8.04 MW
935162 AD1-151 E Adder 6.31 MW 5.36 MW
938531 AE1-072 C Adder 5.57 MW 4.74 MW
938532 AE1-072 E Adder 2.91 MW 2.47 MW
939191 AE1-149 C Adder 3.83 MW 3.26 MW
939192 AE1-149 E Adder 2.55 MW 2.17 MW
939602 AE1-190 E Adder 0.65 MW 0.55 MW
940431 AE2-027 C Adder 3.97 MW 3.38 MW
940432 AE2-027 E Adder 2.65 MW 2.25 MW
940551 AE2-041 C Adder 3.38 MW 2.87 MW
941101 AE2-104 C Adder 1.08 MW 0.92 MW
941102 AE2-104 E Adder 1.72 MW 1.46 MW
943471 AF1-018 C Adder 3.38 MW 2.87 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 0.37 MW 0.37 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 1.69 MW 1.69 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 12.84 MW 12.84 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.58 MW 0.58 MW
NY PJM->LTFIMP_NY CLTF 0.29 MW 0.29 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.03 MW 0.03 MW
WEC LTFEXP_WEC->PJM CLTF 0.01 MW 0.01 MW
CPLE LTFEXP_CPLE->PJM CLTF 1.7 MW 1.7 MW
TVA LTFEXP_TVA->PJM CLTF 0.55 MW 0.55 MW
MEC LTFEXP_MEC->PJM CLTF 0.18 MW 0.18 MW
LAGN LTFEXP_LAGN->PJM CLTF 0.72 MW 0.72 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.01 MW 0.01 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 3.7 MW 3.7 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.81 MW 0.81 MW

Details for 6FREDBRG-6CRANES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9296_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
6FREDBRG-6CRANES 230.0 kV Ckt 1 line
314137 to 314134 ckt 1
Contingency Name:
DVP_P1-2: LN 9296_SRT-A
CONTINGENCY 'DVP_P1-2: LN 9296_SRT-A'
 OPEN BRANCH FROM BUS 314137 TO BUS 314145 CKT 1   /*6FREDBRG     230.0 - 6AQUI_HARB_B 230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 104.79 %
Rating: 984.18 MVA
Rating Type: B
MVA to Mitigate: 1031.34 MVA
MW Contribution: 8.3 MW
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area: DVP
Facility Description:
6FREDBRG-6CRANES 230.0 kV Ckt 1 line
314137 to 314134 ckt 1
Contingency Name:
DVP_P1-2: LN 9296_SRT-A
CONTINGENCY 'DVP_P1-2: LN 9296_SRT-A'
 OPEN BRANCH FROM BUS 314137 TO BUS 314145 CKT 1   /*6FREDBRG     230.0 - 6AQUI_HARB_B 230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 109.82 %
Rating: 984.18 MVA
Rating Type: B
MVA to Mitigate: 1080.87 MVA
MW Contribution: 7.92 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 50/50 0.48 MW 0.48 MW
315033 1BIRCHWDA 50/50 74.58 MW 74.58 MW
315039 1LDYSMT3 50/50 4.16 MW 4.16 MW
315040 1LDYSMT4 50/50 4.17 MW 4.17 MW
315041 1LDYSMT5 50/50 4.18 MW 4.18 MW
315050 1FOURRIVERG 50/50 4.23 MW 4.23 MW
315060 1CHESTF5 Adder 22.67 MW 19.27 MW
315065 1CHESTF6 Adder 6.42 MW 5.46 MW
315073 1STONECA Adder 2.31 MW 1.97 MW
315083 1SPRUNCA Adder 2.96 MW 2.52 MW
315084 1SPRUNCB Adder 2.96 MW 2.52 MW
315092 1YORKTN3 Adder 45.2 MW 38.42 MW
925865 AC1-065 E Adder 8.36 MW 7.1 MW
926412 AC1-112 E Adder 0.42 MW 0.36 MW
926472 AC1-118 E 50/50 1.3 MW 1.3 MW
934392 AD1-063 E Adder 0.54 MW 0.46 MW
934781 AD1-105 C 50/50 1.19 MW 1.19 MW
934782 AD1-105 E 50/50 4.92 MW 4.92 MW
936582 AD2-073 E 50/50 1.09 MW 1.09 MW
936591 AD2-074 C Adder 4.06 MW 3.45 MW
936592 AD2-074 E Adder 6.63 MW 5.63 MW
943741 AF1-042 C Adder 2.13 MW 1.81 MW
943742 AF1-042 E Adder 3.47 MW 2.95 MW
944491 AF1-114 C 50/50 10.55 MW 10.55 MW
944492 AF1-114 E 50/50 14.56 MW 14.56 MW
961951 AG1-038 C Adder 2.35 MW 2.0 MW
961952 AG1-038 E Adder 3.24 MW 2.76 MW
966661 AG1-536 C Adder 4.28 MW 3.64 MW
966662 AG1-536 E Adder 5.76 MW 4.89 MW
966871 AG1-558 C Adder 1.19 MW 1.01 MW
966872 AG1-558 E Adder 0.6 MW 0.51 MW
966881 AG1-559 C Adder 1.71 MW 1.45 MW
966882 AG1-559 E Adder 0.86 MW 0.73 MW
316076 AC2-137 E Adder 0.5 MW 0.42 MW
316078 AC2-138 E Adder 0.78 MW 0.67 MW
316157 AD2-030 E Adder 0.62 MW 0.53 MW
923842 AB2-024 E Adder 0.87 MW 0.74 MW
930122 AB1-027 E Adder 0.52 MW 0.44 MW
957411 AF2-035 C Adder 6.16 MW 5.24 MW
957412 AF2-035 E Adder 3.08 MW 2.62 MW
957601 AF2-054 C Adder 1.11 MW 0.95 MW
957602 AF2-054 E Adder 0.74 MW 0.63 MW
962861 AG1-135 C Adder 4.74 MW 4.03 MW
962862 AG1-135 E Adder 3.16 MW 2.69 MW
962962 AG1-145 E Adder 0.51 MW 0.43 MW
962971 AG1-146 C Adder 2.14 MW 1.82 MW
962972 AG1-146 E Adder 1.42 MW 1.21 MW
962981 AG1-147 C Adder 4.99 MW 4.24 MW
962982 AG1-147 E Adder 3.32 MW 2.83 MW
963051 AG1-154 C 50/50 3.19 MW 3.19 MW
963052 AG1-154 E 50/50 4.78 MW 4.78 MW
963611 AG1-210 C Adder 0.56 MW 0.48 MW
963612 AG1-210 E Adder 0.84 MW 0.71 MW
964211 AG1-282 C Adder 1.61 MW 1.37 MW
964212 AG1-282 E Adder 1.08 MW 0.91 MW
957832 AF2-077 E Adder 0.61 MW 0.52 MW
957971 AF2-091 C 50/50 3.59 MW 3.59 MW
957972 AF2-091 E 50/50 4.95 MW 4.95 MW
313811 6ELKO L286 Adder 0.52 MW 0.44 MW
314181 3NORNECK Adder 0.75 MW 0.63 MW
927041 AC1-191 C Adder 4.79 MW 4.08 MW
927042 AC1-191 E Adder 2.39 MW 2.03 MW
313053 6PAPERMILL Adder 3.24 MW 2.76 MW
316160 AE1-175 E Adder 0.42 MW 0.36 MW
316169 AC1-164 GEN Adder 15.39 MW 13.08 MW
926785 AC1-164_E Adder 6.92 MW 5.88 MW
939612 AE1-191 E Adder 2.92 MW 2.48 MW
315037 1LDYSMT1 50/50 4.0 MW 4.0 MW
315038 1LDYSMT2 50/50 4.05 MW 4.05 MW
316223 AC1-118 C 50/50 0.41 MW 0.41 MW
316337 AD2-073 C 50/50 0.36 MW 0.36 MW
939246 AE1-155 E Adder 6.94 MW 5.89 MW
934146 AD1-041 E Adder 1.82 MW 1.55 MW
944631 AF1-128 C Adder 14.19 MW 12.06 MW
958261 AF2-120 C Adder 4.98 MW 4.23 MW
958262 AF2-120 E Adder 3.32 MW 2.82 MW
939261 AE1-157 C Adder 10.87 MW 9.24 MW
939262 AE1-157 E Adder 5.9 MW 5.01 MW
939602 AE1-190 E Adder 0.73 MW 0.62 MW
940431 AE2-027 C Adder 4.27 MW 3.63 MW
940432 AE2-027 E Adder 2.85 MW 2.42 MW
940551 AE2-041 C Adder 3.58 MW 3.04 MW
943471 AF1-018 C Adder 3.58 MW 3.04 MW
944641 AF1-129 C Adder 33.51 MW 28.48 MW
957191 AF2-013 C 50/50 31.52 MW 31.52 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 7.53 MW 7.53 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 5.13 MW 5.13 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 20.46 MW 20.46 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.56 MW 1.56 MW
NY PJM->LTFIMP_NY CLTF 0.71 MW 0.71 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.31 MW 0.31 MW
WEC LTFEXP_WEC->PJM CLTF 0.16 MW 0.16 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.44 MW 2.44 MW
TVA LTFEXP_TVA->PJM CLTF 1.37 MW 1.37 MW
MEC LTFEXP_MEC->PJM CLTF 0.93 MW 0.93 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.73 MW 1.73 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.06 MW 0.06 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 9.89 MW 9.89 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 1.16 MW 1.16 MW

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1
Contingency Name:
Base Case
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 101.18 %
Rating: 548.02 MVA
Rating Type: A
MVA to Mitigate: 554.48 MVA
MW Contribution: 13.28 MW
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area: DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1
Contingency Name:
Base Case
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 107.25 %
Rating: 548.02 MVA
Rating Type: A
MVA to Mitigate: 587.74 MVA
MW Contribution: 12.37 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 50/50 1.01 MW 1.01 MW
315033 1BIRCHWDA 50/50 158.67 MW 158.67 MW
315034 1NORNECKC1 50/50 0.93 MW 0.93 MW
315035 1NORNECKC2 50/50 0.9 MW 0.9 MW
925865 AC1-065 E 50/50 9.94 MW 9.94 MW
926472 AC1-118 E 50/50 2.4 MW 2.4 MW
934392 AD1-063 E Adder 0.64 MW 0.54 MW
936582 AD2-073 E 50/50 1.92 MW 1.92 MW
936591 AD2-074 C 50/50 6.25 MW 6.25 MW
936592 AD2-074 E 50/50 10.2 MW 10.2 MW
943741 AF1-042 C 50/50 3.27 MW 3.27 MW
943742 AF1-042 E 50/50 5.34 MW 5.34 MW
944491 AF1-114 C 50/50 20.94 MW 20.94 MW
944492 AF1-114 E 50/50 28.92 MW 28.92 MW
961951 AG1-038 C 50/50 3.62 MW 3.62 MW
961952 AG1-038 E 50/50 4.99 MW 4.99 MW
966661 AG1-536 C 50/50 6.86 MW 6.86 MW
966662 AG1-536 E 50/50 9.21 MW 9.21 MW
316077 AC2-138 C 50/50 0.31 MW 0.31 MW
316078 AC2-138 E 50/50 1.28 MW 1.28 MW
316156 AD2-030 C 50/50 0.25 MW 0.25 MW
316157 AD2-030 E 50/50 0.78 MW 0.78 MW
923842 AB2-024 E Adder 1.0 MW 0.85 MW
957601 AF2-054 C 50/50 1.39 MW 1.39 MW
957602 AF2-054 E 50/50 0.93 MW 0.93 MW
962861 AG1-135 C 50/50 7.52 MW 7.52 MW
962862 AG1-135 E 50/50 5.01 MW 5.01 MW
962971 AG1-146 C 50/50 3.2 MW 3.2 MW
962972 AG1-146 E 50/50 2.14 MW 2.14 MW
962981 AG1-147 C 50/50 7.48 MW 7.48 MW
962982 AG1-147 E 50/50 4.98 MW 4.98 MW
963611 AG1-210 C 50/50 0.92 MW 0.92 MW
963612 AG1-210 E 50/50 1.37 MW 1.37 MW
964211 AG1-282 C 50/50 2.58 MW 2.58 MW
964212 AG1-282 E 50/50 1.72 MW 1.72 MW
957832 AF2-077 E Adder 0.65 MW 0.55 MW
957971 AF2-091 C 50/50 7.12 MW 7.12 MW
957972 AF2-091 E 50/50 9.83 MW 9.83 MW
314181 3NORNECK 50/50 1.22 MW 1.22 MW
313053 6PAPERMILL Adder 3.76 MW 3.19 MW
939611 AE1-191 C 50/50 0.85 MW 0.85 MW
939612 AE1-191 E 50/50 3.55 MW 3.55 MW
316201 AC1-065 C 50/50 0.97 MW 0.97 MW
316223 AC1-118 C 50/50 0.76 MW 0.76 MW
316337 AD2-073 C 50/50 0.63 MW 0.63 MW
316404 AE1-155 C 50/50 2.7 MW 2.7 MW
939246 AE1-155 E 50/50 11.1 MW 11.1 MW
316280 AD1-041 C 50/50 0.54 MW 0.54 MW
934146 AD1-041 E 50/50 2.22 MW 2.22 MW
958261 AF2-120 C 50/50 7.97 MW 7.97 MW
958262 AF2-120 E 50/50 5.31 MW 5.31 MW
939601 AE1-190 C 50/50 0.21 MW 0.21 MW
939602 AE1-190 E 50/50 0.89 MW 0.89 MW
940551 AE2-041 C Adder 4.26 MW 3.62 MW
943471 AF1-018 C Adder 4.26 MW 3.62 MW
957191 AF2-013 C 50/50 65.43 MW 65.43 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 2.93 MW 2.93 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 2.25 MW 2.25 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 10.22 MW 10.22 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.6 MW 0.6 MW
NY PJM->LTFIMP_NY CLTF 0.28 MW 0.28 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.12 MW 0.12 MW
WEC LTFEXP_WEC->PJM CLTF 0.06 MW 0.06 MW
CPLE LTFEXP_CPLE->PJM CLTF 1.25 MW 1.25 MW
TVA LTFEXP_TVA->PJM CLTF 0.62 MW 0.62 MW
MEC LTFEXP_MEC->PJM CLTF 0.38 MW 0.38 MW
LAGN LTFEXP_LAGN->PJM CLTF 0.79 MW 0.79 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.02 MW 0.02 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 3.81 MW 3.81 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.6 MW 0.6 MW

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1
Contingency Name:
Base Case
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 101.12 %
Rating: 548.02 MVA
Rating Type: A
MVA to Mitigate: 554.15 MVA
MW Contribution: 13.28 MW
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area: DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1
Contingency Name:
Base Case
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 107.19 %
Rating: 548.02 MVA
Rating Type: A
MVA to Mitigate: 587.44 MVA
MW Contribution: 12.37 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 50/50 1.01 MW 1.01 MW
315033 1BIRCHWDA 50/50 158.67 MW 158.67 MW
315034 1NORNECKC1 50/50 0.93 MW 0.93 MW
315035 1NORNECKC2 50/50 0.9 MW 0.9 MW
925865 AC1-065 E 50/50 9.94 MW 9.94 MW
926472 AC1-118 E 50/50 2.4 MW 2.4 MW
934392 AD1-063 E Adder 0.64 MW 0.54 MW
936582 AD2-073 E 50/50 1.92 MW 1.92 MW
936591 AD2-074 C 50/50 6.25 MW 6.25 MW
936592 AD2-074 E 50/50 10.2 MW 10.2 MW
943741 AF1-042 C 50/50 3.27 MW 3.27 MW
943742 AF1-042 E 50/50 5.34 MW 5.34 MW
944491 AF1-114 C 50/50 20.94 MW 20.94 MW
944492 AF1-114 E 50/50 28.92 MW 28.92 MW
961951 AG1-038 C 50/50 3.62 MW 3.62 MW
961952 AG1-038 E 50/50 4.99 MW 4.99 MW
966661 AG1-536 C 50/50 6.86 MW 6.86 MW
966662 AG1-536 E 50/50 9.21 MW 9.21 MW
316077 AC2-138 C 50/50 0.31 MW 0.31 MW
316078 AC2-138 E 50/50 1.28 MW 1.28 MW
316156 AD2-030 C 50/50 0.25 MW 0.25 MW
316157 AD2-030 E 50/50 0.78 MW 0.78 MW
923842 AB2-024 E Adder 1.0 MW 0.85 MW
957601 AF2-054 C 50/50 1.39 MW 1.39 MW
957602 AF2-054 E 50/50 0.93 MW 0.93 MW
962861 AG1-135 C 50/50 7.52 MW 7.52 MW
962862 AG1-135 E 50/50 5.01 MW 5.01 MW
962971 AG1-146 C 50/50 3.2 MW 3.2 MW
962972 AG1-146 E 50/50 2.14 MW 2.14 MW
962981 AG1-147 C 50/50 7.48 MW 7.48 MW
962982 AG1-147 E 50/50 4.98 MW 4.98 MW
963611 AG1-210 C 50/50 0.92 MW 0.92 MW
963612 AG1-210 E 50/50 1.37 MW 1.37 MW
964211 AG1-282 C 50/50 2.58 MW 2.58 MW
964212 AG1-282 E 50/50 1.72 MW 1.72 MW
957832 AF2-077 E Adder 0.65 MW 0.55 MW
957971 AF2-091 C 50/50 7.12 MW 7.12 MW
957972 AF2-091 E 50/50 9.83 MW 9.83 MW
314181 3NORNECK 50/50 1.22 MW 1.22 MW
313053 6PAPERMILL Adder 3.76 MW 3.19 MW
939611 AE1-191 C 50/50 0.85 MW 0.85 MW
939612 AE1-191 E 50/50 3.55 MW 3.55 MW
316201 AC1-065 C 50/50 0.97 MW 0.97 MW
316223 AC1-118 C 50/50 0.76 MW 0.76 MW
316337 AD2-073 C 50/50 0.63 MW 0.63 MW
316404 AE1-155 C 50/50 2.7 MW 2.7 MW
939246 AE1-155 E 50/50 11.1 MW 11.1 MW
316280 AD1-041 C 50/50 0.54 MW 0.54 MW
934146 AD1-041 E 50/50 2.22 MW 2.22 MW
958261 AF2-120 C 50/50 7.97 MW 7.97 MW
958262 AF2-120 E 50/50 5.31 MW 5.31 MW
939601 AE1-190 C 50/50 0.21 MW 0.21 MW
939602 AE1-190 E 50/50 0.89 MW 0.89 MW
940551 AE2-041 C Adder 4.26 MW 3.62 MW
943471 AF1-018 C Adder 4.26 MW 3.62 MW
957191 AF2-013 C 50/50 65.43 MW 65.43 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 2.93 MW 2.93 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 2.25 MW 2.25 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 10.22 MW 10.22 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.6 MW 0.6 MW
NY PJM->LTFIMP_NY CLTF 0.28 MW 0.28 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.12 MW 0.12 MW
WEC LTFEXP_WEC->PJM CLTF 0.06 MW 0.06 MW
CPLE LTFEXP_CPLE->PJM CLTF 1.25 MW 1.25 MW
TVA LTFEXP_TVA->PJM CLTF 0.62 MW 0.62 MW
MEC LTFEXP_MEC->PJM CLTF 0.38 MW 0.38 MW
LAGN LTFEXP_LAGN->PJM CLTF 0.79 MW 0.79 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.02 MW 0.02 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 3.81 MW 3.81 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.6 MW 0.6 MW

Details for 6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2157_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line
314145 to 314140 ckt 1
Contingency Name:
DVP_P1-2: LN 2157_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2157_SRT-A'
 OPEN BRANCH FROM BUS 314134 TO BUS 314137 CKT 1   /*6CRANES      230.0 - 6FREDBRG     230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 101.96 %
Rating: 898.64 MVA
Rating Type: B
MVA to Mitigate: 916.21 MVA
MW Contribution: 7.6 MW
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area: DVP
Facility Description:
6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line
314145 to 314140 ckt 1
Contingency Name:
DVP_P1-2: LN 2157_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2157_SRT-A'
 OPEN BRANCH FROM BUS 314134 TO BUS 314137 CKT 1   /*6CRANES      230.0 - 6FREDBRG     230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 107.13 %
Rating: 898.64 MVA
Rating Type: B
MVA to Mitigate: 962.74 MVA
MW Contribution: 7.25 MW
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 50/50 0.44 MW 0.44 MW
315033 1BIRCHWDA 50/50 68.25 MW 68.25 MW
315039 1LDYSMT3 50/50 3.81 MW 3.81 MW
315040 1LDYSMT4 50/50 3.81 MW 3.81 MW
315041 1LDYSMT5 50/50 3.83 MW 3.83 MW
315050 1FOURRIVERG 50/50 3.87 MW 3.87 MW
315060 1CHESTF5 Adder 20.75 MW 17.63 MW
315065 1CHESTF6 Adder 5.88 MW 5.0 MW
315073 1STONECA Adder 2.12 MW 1.8 MW
315083 1SPRUNCA Adder 2.71 MW 2.31 MW
315084 1SPRUNCB Adder 2.71 MW 2.31 MW
315092 1YORKTN3 Adder 41.37 MW 35.16 MW
925865 AC1-065 E Adder 7.65 MW 6.5 MW
926412 AC1-112 E Adder 0.39 MW 0.33 MW
926472 AC1-118 E 50/50 1.19 MW 1.19 MW
934392 AD1-063 E Adder 0.49 MW 0.42 MW
934781 AD1-105 C 50/50 1.09 MW 1.09 MW
934782 AD1-105 E 50/50 4.51 MW 4.51 MW
936582 AD2-073 E 50/50 1.0 MW 1.0 MW
936591 AD2-074 C Adder 3.72 MW 3.16 MW
936592 AD2-074 E Adder 6.07 MW 5.16 MW
943741 AF1-042 C Adder 1.94 MW 1.65 MW
943742 AF1-042 E Adder 3.17 MW 2.7 MW
944491 AF1-114 C 50/50 9.65 MW 9.65 MW
944492 AF1-114 E 50/50 13.33 MW 13.33 MW
961951 AG1-038 C Adder 2.15 MW 1.83 MW
961952 AG1-038 E Adder 2.97 MW 2.52 MW
966661 AG1-536 C Adder 3.92 MW 3.33 MW
966662 AG1-536 E Adder 5.27 MW 4.48 MW
966871 AG1-558 C Adder 1.09 MW 0.93 MW
966872 AG1-558 E Adder 0.55 MW 0.47 MW
966881 AG1-559 C Adder 1.56 MW 1.33 MW
966882 AG1-559 E Adder 0.79 MW 0.67 MW
316076 AC2-137 E Adder 0.46 MW 0.39 MW
316078 AC2-138 E Adder 0.72 MW 0.61 MW
316157 AD2-030 E Adder 0.57 MW 0.49 MW
923842 AB2-024 E Adder 0.8 MW 0.68 MW
930122 AB1-027 E Adder 0.48 MW 0.41 MW
957411 AF2-035 C Adder 5.64 MW 4.79 MW
957412 AF2-035 E Adder 2.82 MW 2.4 MW
957601 AF2-054 C Adder 1.02 MW 0.86 MW
957602 AF2-054 E Adder 0.68 MW 0.58 MW
962861 AG1-135 C Adder 4.34 MW 3.69 MW
962862 AG1-135 E Adder 2.89 MW 2.46 MW
962962 AG1-145 E Adder 0.47 MW 0.4 MW
962971 AG1-146 C Adder 1.96 MW 1.66 MW
962972 AG1-146 E Adder 1.3 MW 1.11 MW
962981 AG1-147 C Adder 4.56 MW 3.88 MW
962982 AG1-147 E Adder 3.04 MW 2.59 MW
963051 AG1-154 C 50/50 2.92 MW 2.92 MW
963052 AG1-154 E 50/50 4.37 MW 4.37 MW
963611 AG1-210 C Adder 0.51 MW 0.44 MW
963612 AG1-210 E Adder 0.77 MW 0.65 MW
964211 AG1-282 C Adder 1.48 MW 1.25 MW
964212 AG1-282 E Adder 0.98 MW 0.84 MW
957832 AF2-077 E Adder 0.56 MW 0.48 MW
957971 AF2-091 C 50/50 3.28 MW 3.28 MW
957972 AF2-091 E 50/50 4.53 MW 4.53 MW
313811 6ELKO L286 Adder 0.48 MW 0.41 MW
314181 3NORNECK Adder 0.68 MW 0.58 MW
927041 AC1-191 C Adder 4.39 MW 3.73 MW
927042 AC1-191 E Adder 2.18 MW 1.86 MW
313053 6PAPERMILL Adder 2.97 MW 2.52 MW
316160 AE1-175 E Adder 0.39 MW 0.33 MW
316169 AC1-164 GEN Adder 14.08 MW 11.97 MW
926785 AC1-164_E Adder 6.33 MW 5.38 MW
939612 AE1-191 E Adder 2.67 MW 2.27 MW
315037 1LDYSMT1 50/50 3.66 MW 3.66 MW
315038 1LDYSMT2 50/50 3.71 MW 3.71 MW
316223 AC1-118 C 50/50 0.38 MW 0.38 MW
316337 AD2-073 C 50/50 0.33 MW 0.33 MW
939246 AE1-155 E Adder 6.35 MW 5.39 MW
934146 AD1-041 E Adder 1.67 MW 1.42 MW
944631 AF1-128 C Adder 12.98 MW 11.03 MW
958261 AF2-120 C Adder 4.56 MW 3.87 MW
958262 AF2-120 E Adder 3.04 MW 2.58 MW
939261 AE1-157 C Adder 9.95 MW 8.45 MW
939262 AE1-157 E Adder 5.4 MW 4.59 MW
939602 AE1-190 E Adder 0.67 MW 0.57 MW
940431 AE2-027 C Adder 3.91 MW 3.32 MW
940432 AE2-027 E Adder 2.61 MW 2.21 MW
940551 AE2-041 C Adder 3.27 MW 2.78 MW
943471 AF1-018 C Adder 3.27 MW 2.78 MW
944641 AF1-129 C Adder 30.66 MW 26.06 MW
957191 AF2-013 C 50/50 28.84 MW 28.84 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 6.89 MW 6.89 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 4.69 MW 4.69 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 18.73 MW 18.73 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.43 MW 1.43 MW
NY PJM->LTFIMP_NY CLTF 0.65 MW 0.65 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.28 MW 0.28 MW
WEC LTFEXP_WEC->PJM CLTF 0.14 MW 0.14 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.23 MW 2.23 MW
TVA LTFEXP_TVA->PJM CLTF 1.25 MW 1.25 MW
MEC LTFEXP_MEC->PJM CLTF 0.85 MW 0.85 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.58 MW 1.58 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.05 MW 0.05 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 9.05 MW 9.05 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 1.06 MW 1.06 MW

Details for 8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area: DVP
Facility Description:
8LADYSMITH-8KRAKEN 500.0 kV Ckt 1 line
314911 to 313483 ckt 1
Contingency Name:
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 114.52 %
Rating: 3220.44 MVA
Rating Type: B
MVA to Mitigate: 3688.11 MVA
MW Contribution: 12.32 MW
Impact of Topology Modeling:
Addition
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
961941 AG1-037 C Adder 0.49 MW 0.42 MW
961942 AG1-037 E Adder 0.33 MW 0.28 MW
962331 AG1-082 C Adder 1.97 MW 1.67 MW
962332 AG1-082 E Adder 1.31 MW 1.11 MW
965291 AG1-394 C Adder 0.84 MW 0.72 MW
965292 AG1-394 E Adder 1.55 MW 1.32 MW
314541 3WATKINS Adder 0.7 MW 0.6 MW
920042 AA2-088 E OP Adder 10.51 MW 8.93 MW
934521 AD1-076 C Adder 12.18 MW 10.35 MW
934522 AD1-076 E Adder 6.21 MW 5.28 MW
943172 AE2-346 E Adder 0.59 MW 0.5 MW
316141 AB2-099 E Adder 0.25 MW 0.21 MW
900672 V4-068 E Adder 0.35 MW 0.3 MW
940492 AE2-034 E Adder 3.12 MW 2.65 MW
941031 AE2-094 C Adder 16.13 MW 13.71 MW
957521 AF2-046 C Adder 13.91 MW 11.83 MW
957522 AF2-046 E Adder 7.03 MW 5.98 MW
314539 3UNCAMP Adder 6.24 MW 5.31 MW
916042 Z1-036 E Adder 29.54 MW 25.11 MW
938771 AE1-103 C Adder 3.03 MW 2.57 MW
938772 AE1-103 E Adder 4.18 MW 3.55 MW
314229 6MT RD221 50/50 0.16 MW 0.16 MW
314236 6NRTHEST 50/50 0.23 MW 0.23 MW
314331 6POE Adder 1.46 MW 1.24 MW
314507 3THOMPSN Adder 2.18 MW 1.86 MW
314525 6KINGFORK Adder 1.1 MW 0.94 MW
314550 6HICKORY Adder 2.34 MW 1.99 MW
315039 1LDYSMT3 50/50 7.22 MW 7.22 MW
315040 1LDYSMT4 50/50 7.24 MW 7.24 MW
315041 1LDYSMT5 50/50 7.26 MW 7.26 MW
315060 1CHESTF5 Adder 77.5 MW 65.88 MW
315065 1CHESTF6 Adder 22.98 MW 19.54 MW
315070 1DARBY 4 50/50 3.26 MW 3.26 MW
315073 1STONECA Adder 8.14 MW 6.92 MW
315083 1SPRUNCA Adder 10.58 MW 8.99 MW
315084 1SPRUNCB Adder 10.58 MW 8.99 MW
315092 1YORKTN3 Adder 153.85 MW 130.77 MW
925865 AC1-065 E Adder 19.89 MW 16.91 MW
926412 AC1-112 E 50/50 1.48 MW 1.48 MW
926472 AC1-118 E Adder 1.22 MW 1.03 MW
926662 AC1-147 E Adder 1.43 MW 1.22 MW
926755 AC1-161 E Adder 14.08 MW 11.97 MW
927226 AC1-216 E Adder 8.91 MW 7.58 MW
934392 AD1-063 E Adder 1.29 MW 1.09 MW
934782 AD1-105 E Adder 6.11 MW 5.2 MW
935112 AD1-144 E Adder 1.03 MW 0.87 MW
936582 AD2-073 E Adder 1.24 MW 1.06 MW
936591 AD2-074 C Adder 6.59 MW 5.6 MW
936592 AD2-074 E Adder 10.75 MW 9.13 MW
942341 AE2-247 C Adder 1.61 MW 1.37 MW
942342 AE2-247 E Adder 2.22 MW 1.89 MW
943461 AF1-017 C Adder 1.45 MW 1.24 MW
943462 AF1-017 E Adder 2.37 MW 2.02 MW
943612 AF1-032 E Adder 0.99 MW 0.84 MW
943741 AF1-042 C Adder 3.45 MW 2.93 MW
943742 AF1-042 E Adder 5.62 MW 4.78 MW
961951 AG1-038 C Adder 3.81 MW 3.24 MW
961952 AG1-038 E Adder 5.26 MW 4.47 MW
966661 AG1-536 C Adder 6.36 MW 5.41 MW
966662 AG1-536 E Adder 8.55 MW 7.26 MW
966871 AG1-558 C 50/50 3.19 MW 3.19 MW
966872 AG1-558 E 50/50 1.6 MW 1.6 MW
966881 AG1-559 C 50/50 3.58 MW 3.58 MW
966882 AG1-559 E 50/50 1.8 MW 1.8 MW
315260 1GOSPORTA Adder 2.3 MW 1.96 MW
315261 1GOSPORTB Adder 2.94 MW 2.5 MW
315262 1GOSPORTC Adder 2.5 MW 2.12 MW
316076 AC2-137 E Adder 1.68 MW 1.43 MW
316078 AC2-138 E Adder 1.1 MW 0.94 MW
316157 AD2-030 E Adder 1.41 MW 1.2 MW
913392 Y1-086 E Adder 2.33 MW 1.98 MW
916192 Z1-068 E Adder 2.03 MW 1.72 MW
923832 AB2-022 E Adder 1.32 MW 1.12 MW
923842 AB2-024 E Adder 2.17 MW 1.84 MW
923852 AB2-025 E Adder 1.11 MW 0.94 MW
930122 AB1-027 E 50/50 1.82 MW 1.82 MW
938552 AE1-074 E Adder 1.32 MW 1.12 MW
939312 AE1-162 E Adder 1.59 MW 1.35 MW
946262 AF1-291 E Adder 1.67 MW 1.42 MW
957411 AF2-035 C 50/50 12.93 MW 12.93 MW
957412 AF2-035 E 50/50 6.47 MW 6.47 MW
957492 AF2-043 E Adder 1.52 MW 1.29 MW
957601 AF2-054 C Adder 2.52 MW 2.14 MW
957602 AF2-054 E Adder 1.68 MW 1.43 MW
962861 AG1-135 C Adder 7.18 MW 6.1 MW
962862 AG1-135 E Adder 4.79 MW 4.07 MW
962962 AG1-145 E Adder 1.73 MW 1.47 MW
962971 AG1-146 C Adder 3.66 MW 3.11 MW
962972 AG1-146 E Adder 2.44 MW 2.07 MW
962981 AG1-147 C Adder 8.53 MW 7.25 MW
962982 AG1-147 E Adder 5.69 MW 4.84 MW
963051 AG1-154 C 50/50 5.53 MW 5.53 MW
963052 AG1-154 E 50/50 8.3 MW 8.3 MW
963611 AG1-210 C Adder 0.79 MW 0.67 MW
963612 AG1-210 E Adder 1.18 MW 1.0 MW
964211 AG1-282 C Adder 2.4 MW 2.04 MW
964212 AG1-282 E Adder 1.6 MW 1.36 MW
901082 W1-029 E Adder 33.57 MW 28.53 MW
917122 Z2-027 E Adder 1.42 MW 1.21 MW
925332 AB2-190 E Adder 9.4 MW 7.99 MW
925522 AC1-027 E Adder 1.31 MW 1.12 MW
942001 AE2-212 C Adder 2.43 MW 2.07 MW
942002 AE2-212 E Adder 1.62 MW 1.38 MW
957832 AF2-077 E Adder 1.68 MW 1.42 MW
957871 AF2-081 C Adder 10.68 MW 9.08 MW
957872 AF2-081 E Adder 4.58 MW 3.89 MW
958161 AF2-110 C Adder 1.46 MW 1.24 MW
958162 AF2-110 E Adder 2.32 MW 1.97 MW
313811 6ELKO L286 Adder 1.75 MW 1.49 MW
314181 3NORNECK Adder 1.05 MW 0.89 MW
933291 AC2-141 C Adder 32.98 MW 28.04 MW
933292 AC2-141 E Adder 14.08 MW 11.97 MW
939411 AE1-173 C Adder 85.03 MW 72.28 MW
939412 AE1-173 E Adder 56.69 MW 48.19 MW
934012 AD1-025 E Adder 11.54 MW 9.81 MW
927041 AC1-191 C 50/50 12.79 MW 12.79 MW
927042 AC1-191 E 50/50 6.37 MW 6.37 MW
933981 AD1-022 C Adder 8.66 MW 7.37 MW
933982 AD1-022 E Adder 4.72 MW 4.01 MW
961681 AG1-008 C Adder 13.91 MW 11.83 MW
961682 AG1-008 E Adder 7.03 MW 5.98 MW
313053 6PAPERMILL Adder 8.0 MW 6.8 MW
314594 6PLYMOUTH TP Adder 0.32 MW 0.27 MW
314632 6AYDLETT TAP Adder 1.45 MW 1.23 MW
316004 AC1-112 C 50/50 0.43 MW 0.43 MW
316160 AE1-175 E Adder 1.42 MW 1.21 MW
316169 AC1-164 GEN Adder 50.64 MW 43.04 MW
316233 AE1-074 C Adder 2.62 MW 2.23 MW
316240 AF1-291 C Adder 2.51 MW 2.13 MW
316312 AB1-027 C 50/50 0.69 MW 0.69 MW
924516 AB2-100 E1 Adder 2.7 MW 2.3 MW
924517 AB2-100 E2 Adder 2.7 MW 2.3 MW
926785 AC1-164_E Adder 22.75 MW 19.34 MW
934065 AD1-033 E Adder 5.39 MW 4.58 MW
937226 AE2-253 E Adder 6.25 MW 5.32 MW
939612 AE1-191 E Adder 6.79 MW 5.77 MW
315037 1LDYSMT1 50/50 6.95 MW 6.95 MW
315038 1LDYSMT2 50/50 7.04 MW 7.04 MW
315051 AA1-145 CT1 50/50 7.04 MW 7.04 MW
315052 AA1-145 CT2 50/50 7.04 MW 7.04 MW
939246 AE1-155 E Adder 10.29 MW 8.75 MW
918512 AA1-065 E OP Adder 5.37 MW 4.57 MW
919153 AA1-139 E2 Adder 4.37 MW 3.71 MW
919152 AA1-139 E1 Adder 4.37 MW 3.71 MW
920692 AA2-178 E Adder 4.16 MW 3.54 MW
924814 AB2-134 E Adder 14.6 MW 12.41 MW
316084 AB2-161 E Adder 6.04 MW 5.13 MW
932046 AC2-012 E Adder 14.18 MW 12.06 MW
316311 AC2-079 C Adder 6.17 MW 5.25 MW
932596 AC2-079 E Adder 10.07 MW 8.56 MW
934146 AD1-041 E Adder 4.24 MW 3.61 MW
934576 AD1-082 E Adder 4.81 MW 4.09 MW
316349 AD2-085 C Adder 3.71 MW 3.15 MW
936666 AD2-085 E Adder 6.05 MW 5.14 MW
961611 AG1-000B C Adder 18.12 MW 15.4 MW
941591 AE2-156 C Adder 19.38 MW 16.47 MW
944581 AF1-123 C Adder 48.76 MW 41.44 MW
944582 AF1-123 E Adder 111.64 MW 94.9 MW
944591 AF1-124 C Adder 48.93 MW 41.59 MW
944592 AF1-124 E Adder 112.05 MW 95.24 MW
944601 AF1-125 C Adder 48.0 MW 40.8 MW
944602 AF1-125 E Adder 109.89 MW 93.41 MW
944631 AF1-128 C Adder 48.49 MW 41.22 MW
958261 AF2-120 C Adder 7.39 MW 6.28 MW
958262 AF2-120 E Adder 4.93 MW 4.19 MW
965281 AG1-393 C Adder 2.47 MW 2.1 MW
965282 AG1-393 E Adder 1.64 MW 1.4 MW
934501 AD1-074 C Adder 33.53 MW 28.5 MW
934502 AD1-074 E Adder 17.07 MW 14.51 MW
934511 AD1-075 C Adder 8.38 MW 7.12 MW
934512 AD1-075 E Adder 4.27 MW 3.63 MW
935161 AD1-151 C Adder 18.71 MW 15.91 MW
935162 AD1-151 E Adder 12.48 MW 10.6 MW
938531 AE1-072 C Adder 18.76 MW 15.94 MW
938532 AE1-072 E Adder 9.78 MW 8.31 MW
939191 AE1-149 C Adder 11.83 MW 10.06 MW
939192 AE1-149 E Adder 7.89 MW 6.71 MW
939261 AE1-157 C 50/50 21.17 MW 21.17 MW
939262 AE1-157 E 50/50 11.48 MW 11.48 MW
939602 AE1-190 E Adder 1.7 MW 1.44 MW
940431 AE2-027 C Adder 14.92 MW 12.68 MW
940432 AE2-027 E Adder 9.94 MW 8.45 MW
940481 AE2-033 C Adder 15.38 MW 13.07 MW
940482 AE2-033 E Adder 10.37 MW 8.81 MW
940541 AE2-040 C Adder 2.73 MW 2.32 MW
940551 AE2-041 C Adder 8.58 MW 7.29 MW
940641 AE2-051 C Adder 15.49 MW 13.17 MW
940642 AE2-051 E Adder 10.33 MW 8.78 MW
941101 AE2-104 C Adder 3.58 MW 3.04 MW
941102 AE2-104 E Adder 5.69 MW 4.83 MW
943471 AF1-018 C Adder 8.58 MW 7.29 MW
944641 AF1-129 C Adder 119.87 MW 101.89 MW
315043 1FOUR RIVERA 50/50 4.42 MW 4.42 MW
315044 1FOUR RIVERB 50/50 4.42 MW 4.42 MW
315045 1FOUR RIVERC 50/50 5.4 MW 5.4 MW
315046 1FOUR RIVERD 50/50 4.36 MW 4.36 MW
315047 1FOUR RIVERE 50/50 4.36 MW 4.36 MW
315048 1FOUR RIVERF 50/50 5.32 MW 5.32 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 24.61 MW 24.61 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 17.81 MW 17.81 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 75.41 MW 75.41 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 5.3 MW 5.3 MW
NY PJM->LTFIMP_NY CLTF 2.43 MW 2.43 MW
LGEE LTFEXP_LGEE->PJM CLTF 1.01 MW 1.01 MW
WEC LTFEXP_WEC->PJM CLTF 0.52 MW 0.52 MW
CPLE LTFEXP_CPLE->PJM CLTF 9.08 MW 9.08 MW
TVA LTFEXP_TVA->PJM CLTF 4.83 MW 4.83 MW
MEC LTFEXP_MEC->PJM CLTF 3.13 MW 3.13 MW
LAGN LTFEXP_LAGN->PJM CLTF 6.1 MW 6.1 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.2 MW 0.2 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 33.72 MW 33.72 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 4.33 MW 4.33 MW

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

Area Facility Description Contingency Name Contingency Type DC|AC Final Cycle Loading Rating (MVA) Rating Type MVA to Mitigate MW Contribution Details
DVP 3LANCAST-3OCRAN 115.0 kV Ckt 1 line
314178 to 313813 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
OP AC 257.66 % 219.96 B 566.74 61.98
DVP 3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
313813 to 314191 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
OP AC 252.11 % 219.96 B 554.54 61.98
DVP 3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line
314191 to 313870 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
OP AC 173.14 % 315.84 B 546.84 61.98
DVP AD2-074 TP-AG1-146 TP 115.0 kV Ckt 1 line
936590 to 962970 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
OP AC 241.94 % 203.98 B 493.51 61.98
DVP 3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
313900 to 313886 ckt 2
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
OP AC 206.29 % 132.54 B 273.41 30.99
DVP 3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
313900 to 313886 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
OP AC 206.29 % 132.54 B 273.41 30.99
DVP 3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
313886 to 314174 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
OP AC 201.3 % 269.78 B 543.05 61.98
DVP AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
316399 to 314181 ckt 1
Base Case OP AC 182.2 % 203.98 A 371.65 39.67
DVP 3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer
314174 to 314176 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
OP DC 158.71 % 224.38 B 356.11 29.74
DVP AG1-135 TP-AD2-074 TP 115.0 kV Ckt 1 line
962860 to 936590 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
OP AC 153.07 % 203.98 B 312.22 61.98
DVP AE1-155 TAP-3GARNER 115.0 kV Ckt 1 line
316399 to 314173 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
OP AC 129.26 % 203.98 B 263.66 61.98
DVP 3WEST PT-3LANEXA 115.0 kV Ckt 1 line
314188 to 314387 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
OP AC 125.29 % 224.66 B 281.49 15.26
DVP 3GARNER-AG1-135 TP 115.0 kV Ckt 1 line
314173 to 962860 ckt 1
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
OP AC 123.78 % 203.98 B 252.49 61.98
DVP 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
314911 to 314922 ckt 1
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
OP AC 117.95 % 3220.44 B 3798.63 8.7
DVP AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
957190 to 314131 ckt 1
DVP_P1-2: LN 574_SRT-S
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
OP AC 104.84 % 559.3 B 586.36 13.04
DVP AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
944490 to 313810 ckt 1
DVP_P1-2: LN 574_SRT-S
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
OP AC 104.24 % 571.52 B 595.77 13.04
DVP 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
314911 to 314905 ckt 1
DVP_P1-2: LN 573_SRT-A
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
OP AC 103.76 % 4070.2 B 4223.17 11.33
DVP 8CHANCE-8BRISTER 500.0 kV Ckt 1 line
314905 to 314900 ckt 1
DVP_P1-2: LN 594_SRT-S
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
OP AC 103.7 % 4070.2 B 4220.84 11.08
DVP 6CRANES-6STAFORD 230.0 kV Ckt 1 line
314134 to 314142 ckt 1
DVP_P1-2: LN 9296_SRT-A
CONTINGENCY 'DVP_P1-2: LN 9296_SRT-A'
 OPEN BRANCH FROM BUS 314137 TO BUS 314145 CKT 1   /*6FREDBRG     230.0 - 6AQUI_HARB_B 230.0
END
OP AC 102.1 % 984.18 B 1004.88 7.92
DVP 6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line
314140 to 314144 ckt 1
DVP_P1-2: LN 2157_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2157_SRT-A'
 OPEN BRANCH FROM BUS 314134 TO BUS 314137 CKT 1   /*6CRANES      230.0 - 6FREDBRG     230.0
END
OP AC 101.4 % 898.64 B 911.24 7.25
DVP AD2-074 TP-AG1-146 TP 115.0 kV Ckt 1 line
936590 to 962970 ckt 1
Base Case OP AC 101.16 % 203.98 A 206.35 22.31
DVP 6DAHLGREN-AF2-013 TP 230.0 kV Ckt 1 line
313810 to 957190 ckt 1
DVP_P1-2: LN 574_SRT-S
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
OP AC 101.1 % 559.3 B 565.44 13.04

Details for 3LANCAST-3OCRAN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
314178 to 313813 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 257.66 %
Rating: 219.96 MVA
Rating Type: B
MVA to Mitigate: 566.74 MVA
MW Contribution: 61.98 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 50/50 32.67 MW 32.67 MW
936592 AD2-074 E 50/50 53.3 MW 53.3 MW
943741 AF1-042 C 50/50 17.09 MW 17.09 MW
943742 AF1-042 E 50/50 27.89 MW 27.89 MW
961951 AG1-038 C 50/50 18.89 MW 18.89 MW
961952 AG1-038 E 50/50 26.09 MW 26.09 MW
966661 AG1-536 C 50/50 31.99 MW 31.99 MW
966662 AG1-536 E 50/50 42.98 MW 42.98 MW
962861 AG1-135 C 50/50 35.99 MW 35.99 MW
962862 AG1-135 E 50/50 23.99 MW 23.99 MW
962971 AG1-146 C 50/50 17.99 MW 17.99 MW
962972 AG1-146 E 50/50 11.99 MW 11.99 MW
962981 AG1-147 C 50/50 41.98 MW 41.98 MW
962982 AG1-147 E 50/50 27.99 MW 27.99 MW
316404 AE1-155 C 50/50 12.57 MW 12.57 MW
939246 AE1-155 E 50/50 51.78 MW 51.78 MW
958261 AF2-120 C 50/50 37.19 MW 37.19 MW
958262 AF2-120 E 50/50 24.79 MW 24.79 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.04 MW 0.04 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.27 MW 0.27 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for 3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
313813 to 314191 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 252.11 %
Rating: 219.96 MVA
Rating Type: B
MVA to Mitigate: 554.54 MVA
MW Contribution: 61.98 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 50/50 32.67 MW 32.67 MW
936592 AD2-074 E 50/50 53.3 MW 53.3 MW
943741 AF1-042 C 50/50 17.09 MW 17.09 MW
943742 AF1-042 E 50/50 27.89 MW 27.89 MW
961951 AG1-038 C 50/50 18.89 MW 18.89 MW
961952 AG1-038 E 50/50 26.09 MW 26.09 MW
966661 AG1-536 C 50/50 31.99 MW 31.99 MW
966662 AG1-536 E 50/50 42.98 MW 42.98 MW
962861 AG1-135 C 50/50 35.99 MW 35.99 MW
962862 AG1-135 E 50/50 23.99 MW 23.99 MW
962971 AG1-146 C 50/50 17.99 MW 17.99 MW
962972 AG1-146 E 50/50 11.99 MW 11.99 MW
962981 AG1-147 C 50/50 41.98 MW 41.98 MW
962982 AG1-147 E 50/50 27.99 MW 27.99 MW
316404 AE1-155 C 50/50 12.57 MW 12.57 MW
939246 AE1-155 E 50/50 51.78 MW 51.78 MW
958261 AF2-120 C 50/50 37.19 MW 37.19 MW
958262 AF2-120 E 50/50 24.79 MW 24.79 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.04 MW 0.04 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.27 MW 0.27 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for 3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line
314191 to 313870 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 173.14 %
Rating: 315.84 MVA
Rating Type: B
MVA to Mitigate: 546.84 MVA
MW Contribution: 61.98 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 50/50 32.67 MW 32.67 MW
936592 AD2-074 E 50/50 53.3 MW 53.3 MW
943741 AF1-042 C 50/50 17.09 MW 17.09 MW
943742 AF1-042 E 50/50 27.89 MW 27.89 MW
961951 AG1-038 C 50/50 18.89 MW 18.89 MW
961952 AG1-038 E 50/50 26.09 MW 26.09 MW
966661 AG1-536 C 50/50 31.99 MW 31.99 MW
966662 AG1-536 E 50/50 42.98 MW 42.98 MW
962861 AG1-135 C 50/50 35.99 MW 35.99 MW
962862 AG1-135 E 50/50 23.99 MW 23.99 MW
962971 AG1-146 C 50/50 17.99 MW 17.99 MW
962972 AG1-146 E 50/50 11.99 MW 11.99 MW
962981 AG1-147 C 50/50 41.98 MW 41.98 MW
962982 AG1-147 E 50/50 27.99 MW 27.99 MW
316404 AE1-155 C 50/50 12.57 MW 12.57 MW
939246 AE1-155 E 50/50 51.78 MW 51.78 MW
958261 AF2-120 C 50/50 37.19 MW 37.19 MW
958262 AF2-120 E 50/50 24.79 MW 24.79 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.04 MW 0.04 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.27 MW 0.27 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for AD2-074 TP-AG1-146 TP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
AD2-074 TP-AG1-146 TP 115.0 kV Ckt 1 line
936590 to 962970 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 241.94 %
Rating: 203.98 MVA
Rating Type: B
MVA to Mitigate: 493.51 MVA
MW Contribution: 61.98 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 50/50 32.67 MW 32.67 MW
936592 AD2-074 E 50/50 53.3 MW 53.3 MW
943741 AF1-042 C 50/50 17.09 MW 17.09 MW
943742 AF1-042 E 50/50 27.89 MW 27.89 MW
961951 AG1-038 C 50/50 18.89 MW 18.89 MW
961952 AG1-038 E 50/50 26.09 MW 26.09 MW
966661 AG1-536 C 50/50 31.99 MW 31.99 MW
966662 AG1-536 E 50/50 42.98 MW 42.98 MW
962861 AG1-135 C 50/50 35.99 MW 35.99 MW
962862 AG1-135 E 50/50 23.99 MW 23.99 MW
316404 AE1-155 C 50/50 12.57 MW 12.57 MW
939246 AE1-155 E 50/50 51.78 MW 51.78 MW
958261 AF2-120 C 50/50 37.19 MW 37.19 MW
958262 AF2-120 E 50/50 24.79 MW 24.79 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.04 MW 0.04 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.27 MW 0.27 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
313900 to 313886 ckt 2
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 206.29 %
Rating: 132.54 MVA
Rating Type: B
MVA to Mitigate: 273.41 MVA
MW Contribution: 30.99 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 50/50 16.33 MW 16.33 MW
936592 AD2-074 E 50/50 26.65 MW 26.65 MW
943741 AF1-042 C 50/50 8.55 MW 8.55 MW
943742 AF1-042 E 50/50 13.94 MW 13.94 MW
961951 AG1-038 C 50/50 9.45 MW 9.45 MW
961952 AG1-038 E 50/50 13.04 MW 13.04 MW
966661 AG1-536 C 50/50 15.99 MW 15.99 MW
966662 AG1-536 E 50/50 21.49 MW 21.49 MW
962861 AG1-135 C 50/50 17.99 MW 17.99 MW
962862 AG1-135 E 50/50 11.99 MW 11.99 MW
962971 AG1-146 C 50/50 9.0 MW 9.0 MW
962972 AG1-146 E 50/50 6.0 MW 6.0 MW
962981 AG1-147 C 50/50 20.99 MW 20.99 MW
962982 AG1-147 E 50/50 13.99 MW 13.99 MW
316404 AE1-155 C 50/50 6.29 MW 6.29 MW
939246 AE1-155 E 50/50 25.89 MW 25.89 MW
958261 AF2-120 C 50/50 18.59 MW 18.59 MW
958262 AF2-120 E 50/50 12.39 MW 12.39 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.02 MW 0.02 MW
NY PJM->LTFIMP_NY CLTF 0.01 MW 0.01 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.04 MW 0.04 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.01 MW 0.01 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.05 MW 0.05 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.01 MW 0.01 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.03 MW 0.03 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.13 MW 0.13 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.02 MW 0.02 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.01 MW 0.01 MW

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
313900 to 313886 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 206.29 %
Rating: 132.54 MVA
Rating Type: B
MVA to Mitigate: 273.41 MVA
MW Contribution: 30.99 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 50/50 16.33 MW 16.33 MW
936592 AD2-074 E 50/50 26.65 MW 26.65 MW
943741 AF1-042 C 50/50 8.55 MW 8.55 MW
943742 AF1-042 E 50/50 13.94 MW 13.94 MW
961951 AG1-038 C 50/50 9.45 MW 9.45 MW
961952 AG1-038 E 50/50 13.04 MW 13.04 MW
966661 AG1-536 C 50/50 15.99 MW 15.99 MW
966662 AG1-536 E 50/50 21.49 MW 21.49 MW
962861 AG1-135 C 50/50 17.99 MW 17.99 MW
962862 AG1-135 E 50/50 11.99 MW 11.99 MW
962971 AG1-146 C 50/50 9.0 MW 9.0 MW
962972 AG1-146 E 50/50 6.0 MW 6.0 MW
962981 AG1-147 C 50/50 20.99 MW 20.99 MW
962982 AG1-147 E 50/50 13.99 MW 13.99 MW
316404 AE1-155 C 50/50 6.29 MW 6.29 MW
939246 AE1-155 E 50/50 25.89 MW 25.89 MW
958261 AF2-120 C 50/50 18.59 MW 18.59 MW
958262 AF2-120 E 50/50 12.39 MW 12.39 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.02 MW 0.02 MW
NY PJM->LTFIMP_NY CLTF 0.01 MW 0.01 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.04 MW 0.04 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.01 MW 0.01 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.05 MW 0.05 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.01 MW 0.01 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.03 MW 0.03 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.13 MW 0.13 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.02 MW 0.02 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.01 MW 0.01 MW

Details for 3GREYSPT-3HARMONY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
313886 to 314174 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 201.3 %
Rating: 269.78 MVA
Rating Type: B
MVA to Mitigate: 543.05 MVA
MW Contribution: 61.98 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
936591 AD2-074 C 50/50 32.67 MW 32.67 MW
936592 AD2-074 E 50/50 53.3 MW 53.3 MW
943741 AF1-042 C 50/50 17.09 MW 17.09 MW
943742 AF1-042 E 50/50 27.89 MW 27.89 MW
961951 AG1-038 C 50/50 18.89 MW 18.89 MW
961952 AG1-038 E 50/50 26.09 MW 26.09 MW
966661 AG1-536 C 50/50 31.99 MW 31.99 MW
966662 AG1-536 E 50/50 42.98 MW 42.98 MW
962861 AG1-135 C 50/50 35.99 MW 35.99 MW
962862 AG1-135 E 50/50 23.99 MW 23.99 MW
962971 AG1-146 C 50/50 17.99 MW 17.99 MW
962972 AG1-146 E 50/50 11.99 MW 11.99 MW
962981 AG1-147 C 50/50 41.98 MW 41.98 MW
962982 AG1-147 E 50/50 27.99 MW 27.99 MW
316404 AE1-155 C 50/50 12.57 MW 12.57 MW
939246 AE1-155 E 50/50 51.78 MW 51.78 MW
958261 AF2-120 C 50/50 37.19 MW 37.19 MW
958262 AF2-120 E 50/50 24.79 MW 24.79 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.04 MW 0.04 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.27 MW 0.27 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
316399 to 314181 ckt 1
Contingency Name:
Base Case
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 182.2 %
Rating: 203.98 MVA
Rating Type: A
MVA to Mitigate: 371.65 MVA
MW Contribution: 39.67 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314184 3SHACKLE 50/50 0.31 MW 0.31 MW
925865 AC1-065 E 50/50 9.85 MW 9.85 MW
934392 AD1-063 E Adder 0.43 MW 0.37 MW
936591 AD2-074 C 50/50 17.28 MW 17.28 MW
936592 AD2-074 E 50/50 28.19 MW 28.19 MW
943741 AF1-042 C 50/50 9.04 MW 9.04 MW
943742 AF1-042 E 50/50 14.75 MW 14.75 MW
961951 AG1-038 C 50/50 9.99 MW 9.99 MW
961952 AG1-038 E 50/50 13.8 MW 13.8 MW
966661 AG1-536 C 50/50 20.48 MW 20.48 MW
966662 AG1-536 E 50/50 27.51 MW 27.51 MW
316156 AD2-030 C 50/50 0.35 MW 0.35 MW
316157 AD2-030 E 50/50 1.12 MW 1.12 MW
957601 AF2-054 C 50/50 1.99 MW 1.99 MW
957602 AF2-054 E 50/50 1.32 MW 1.32 MW
962861 AG1-135 C 50/50 22.1 MW 22.1 MW
962862 AG1-135 E 50/50 14.73 MW 14.73 MW
962971 AG1-146 C 50/50 8.35 MW 8.35 MW
962972 AG1-146 E 50/50 5.57 MW 5.57 MW
962981 AG1-147 C 50/50 19.49 MW 19.49 MW
962982 AG1-147 E 50/50 12.99 MW 12.99 MW
957832 AF2-077 E Adder 0.68 MW 0.58 MW
939611 AE1-191 C 50/50 1.01 MW 1.01 MW
939612 AE1-191 E 50/50 4.22 MW 4.22 MW
316201 AC1-065 C 50/50 0.96 MW 0.96 MW
316404 AE1-155 C 50/50 8.05 MW 8.05 MW
939246 AE1-155 E 50/50 33.14 MW 33.14 MW
316280 AD1-041 C 50/50 0.64 MW 0.64 MW
934146 AD1-041 E 50/50 2.64 MW 2.64 MW
958261 AF2-120 C 50/50 23.8 MW 23.8 MW
958262 AF2-120 E 50/50 15.87 MW 15.87 MW
939601 AE1-190 C 50/50 0.25 MW 0.25 MW
939602 AE1-190 E 50/50 1.06 MW 1.06 MW
940551 AE2-041 C Adder 2.88 MW 2.45 MW
943471 AF1-018 C Adder 2.88 MW 2.45 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 0.11 MW 0.11 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 0.92 MW 0.92 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.1 MW 0.1 MW
NY PJM->LTFIMP_NY CLTF 0.05 MW 0.05 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.0 MW 0.0 MW
CPLE LTFEXP_CPLE->PJM CLTF 0.12 MW 0.12 MW
TVA LTFEXP_TVA->PJM CLTF 0.04 MW 0.04 MW
MEC LTFEXP_MEC->PJM CLTF 0.01 MW 0.01 MW
LAGN LTFEXP_LAGN->PJM CLTF 0.05 MW 0.05 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.0 MW 0.0 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.63 MW 0.63 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.06 MW 0.06 MW

Details for 3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer
314174 to 314176 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: OP
DC|AC: DC
Final Cycle Loading: 158.71 %
Rating: 224.38 MVA
Rating Type: B
MVA to Mitigate: 356.11 MVA
MW Contribution: 29.74 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314184 3SHACKLE 50/50 0.88 MW 0.88 MW
925865 AC1-065 E 50/50 27.71 MW 27.71 MW
936591 AD2-074 C 50/50 15.68 MW 15.68 MW
936592 AD2-074 E 50/50 25.57 MW 25.57 MW
943741 AF1-042 C 50/50 8.2 MW 8.2 MW
943742 AF1-042 E 50/50 13.38 MW 13.38 MW
961951 AG1-038 C 50/50 9.06 MW 9.06 MW
961952 AG1-038 E 50/50 12.52 MW 12.52 MW
966661 AG1-536 C 50/50 15.35 MW 15.35 MW
966662 AG1-536 E 50/50 20.62 MW 20.62 MW
316156 AD2-030 C 50/50 1.02 MW 1.02 MW
316157 AD2-030 E 50/50 3.21 MW 3.21 MW
957601 AF2-054 C 50/50 5.73 MW 5.73 MW
957602 AF2-054 E 50/50 3.82 MW 3.82 MW
962861 AG1-135 C 50/50 17.27 MW 17.27 MW
962862 AG1-135 E 50/50 11.51 MW 11.51 MW
962971 AG1-146 C 50/50 8.63 MW 8.63 MW
962972 AG1-146 E 50/50 5.76 MW 5.76 MW
962981 AG1-147 C 50/50 20.14 MW 20.14 MW
962982 AG1-147 E 50/50 13.43 MW 13.43 MW
957831 AF2-077 C 50/50 0.44 MW 0.44 MW
957832 AF2-077 E 50/50 1.91 MW 1.91 MW
939611 AE1-191 C 50/50 2.89 MW 2.89 MW
939612 AE1-191 E 50/50 12.04 MW 12.04 MW
316201 AC1-065 C 50/50 2.7 MW 2.7 MW
316404 AE1-155 C 50/50 6.03 MW 6.03 MW
939246 AE1-155 E 50/50 24.85 MW 24.85 MW
316280 AD1-041 C 50/50 1.83 MW 1.83 MW
934146 AD1-041 E 50/50 7.53 MW 7.53 MW
958261 AF2-120 C 50/50 17.84 MW 17.84 MW
958262 AF2-120 E 50/50 11.89 MW 11.89 MW
939601 AE1-190 C 50/50 0.72 MW 0.72 MW
939602 AE1-190 E 50/50 3.01 MW 3.01 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 0.54 MW 0.54 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.1 MW 0.1 MW
NY PJM->LTFIMP_NY CLTF 0.05 MW 0.05 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.01 MW 0.01 MW
CPLE LTFEXP_CPLE->PJM CLTF 0.08 MW 0.08 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.06 MW 0.06 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.05 MW 0.05 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.62 MW 0.62 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.03 MW 0.03 MW

Details for AG1-135 TP-AD2-074 TP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
AG1-135 TP-AD2-074 TP 115.0 kV Ckt 1 line
962860 to 936590 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 153.07 %
Rating: 203.98 MVA
Rating Type: B
MVA to Mitigate: 312.22 MVA
MW Contribution: 61.98 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
966661 AG1-536 C 50/50 31.99 MW 31.99 MW
966662 AG1-536 E 50/50 42.98 MW 42.98 MW
962861 AG1-135 C 50/50 35.99 MW 35.99 MW
962862 AG1-135 E 50/50 23.99 MW 23.99 MW
316404 AE1-155 C 50/50 12.57 MW 12.57 MW
939246 AE1-155 E 50/50 51.78 MW 51.78 MW
958261 AF2-120 C 50/50 37.19 MW 37.19 MW
958262 AF2-120 E 50/50 24.79 MW 24.79 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.04 MW 0.04 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.27 MW 0.27 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for AE1-155 TAP-3GARNER 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
AE1-155 TAP-3GARNER 115.0 kV Ckt 1 line
316399 to 314173 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 129.26 %
Rating: 203.98 MVA
Rating Type: B
MVA to Mitigate: 263.66 MVA
MW Contribution: 61.98 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
966661 AG1-536 C 50/50 31.99 MW 31.99 MW
966662 AG1-536 E 50/50 42.98 MW 42.98 MW
316404 AE1-155 C 50/50 12.57 MW 12.57 MW
939246 AE1-155 E 50/50 51.78 MW 51.78 MW
958261 AF2-120 C 50/50 37.19 MW 37.19 MW
958262 AF2-120 E 50/50 24.79 MW 24.79 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.04 MW 0.04 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.27 MW 0.27 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for 3WEST PT-3LANEXA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
3WEST PT-3LANEXA 115.0 kV Ckt 1 line
314188 to 314387 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 125.29 %
Rating: 224.66 MVA
Rating Type: B
MVA to Mitigate: 281.49 MVA
MW Contribution: 15.26 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314184 3SHACKLE 50/50 1.55 MW 1.55 MW
925865 AC1-065 E 50/50 48.66 MW 48.66 MW
934392 AD1-063 E 50/50 0.62 MW 0.62 MW
936591 AD2-074 C 50/50 8.04 MW 8.04 MW
936592 AD2-074 E 50/50 13.13 MW 13.13 MW
943741 AF1-042 C 50/50 4.21 MW 4.21 MW
943742 AF1-042 E 50/50 6.87 MW 6.87 MW
961951 AG1-038 C 50/50 4.65 MW 4.65 MW
961952 AG1-038 E 50/50 6.42 MW 6.42 MW
966661 AG1-536 C 50/50 7.88 MW 7.88 MW
966662 AG1-536 E 50/50 10.59 MW 10.59 MW
316156 AD2-030 C 50/50 0.53 MW 0.53 MW
316157 AD2-030 E 50/50 1.65 MW 1.65 MW
957601 AF2-054 C 50/50 2.94 MW 2.94 MW
957602 AF2-054 E 50/50 1.96 MW 1.96 MW
962861 AG1-135 C 50/50 8.86 MW 8.86 MW
962862 AG1-135 E 50/50 5.91 MW 5.91 MW
962971 AG1-146 C 50/50 4.43 MW 4.43 MW
962972 AG1-146 E 50/50 2.95 MW 2.95 MW
962981 AG1-147 C 50/50 10.34 MW 10.34 MW
962982 AG1-147 E 50/50 6.89 MW 6.89 MW
957831 AF2-077 C 50/50 0.23 MW 0.23 MW
957832 AF2-077 E 50/50 0.99 MW 0.99 MW
316059 AD1-063 C 50/50 0.15 MW 0.15 MW
939611 AE1-191 C 50/50 3.08 MW 3.08 MW
939612 AE1-191 E 50/50 12.86 MW 12.86 MW
316201 AC1-065 C 50/50 4.74 MW 4.74 MW
316404 AE1-155 C 50/50 3.1 MW 3.1 MW
939246 AE1-155 E 50/50 12.75 MW 12.75 MW
316280 AD1-041 C 50/50 1.96 MW 1.96 MW
934146 AD1-041 E 50/50 8.04 MW 8.04 MW
958261 AF2-120 C 50/50 9.16 MW 9.16 MW
958262 AF2-120 E 50/50 6.11 MW 6.11 MW
939601 AE1-190 C 50/50 0.77 MW 0.77 MW
939602 AE1-190 E 50/50 3.21 MW 3.21 MW
940551 AE2-041 C 50/50 4.14 MW 4.14 MW
943471 AF1-018 C 50/50 4.14 MW 4.14 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.07 MW 0.07 MW
NY PJM->LTFIMP_NY CLTF 0.04 MW 0.04 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.07 MW 0.07 MW
CPLE LTFEXP_CPLE->PJM CLTF 0.01 MW 0.01 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.0 MW 0.0 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.46 MW 0.46 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW

Details for 3GARNER-AG1-135 TP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-SW-E


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
3GARNER-AG1-135 TP 115.0 kV Ckt 1 line
314173 to 962860 ckt 1
Contingency Name:
DVP_P1-2: LN 65_SRT-SW-E
CONTINGENCY 'DVP_P1-2: LN 65_SRT-SW-E'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 123.78 %
Rating: 203.98 MVA
Rating Type: B
MVA to Mitigate: 252.49 MVA
MW Contribution: 61.98 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
966661 AG1-536 C 50/50 31.99 MW 31.99 MW
966662 AG1-536 E 50/50 42.98 MW 42.98 MW
316404 AE1-155 C 50/50 12.57 MW 12.57 MW
939246 AE1-155 E 50/50 51.78 MW 51.78 MW
958261 AF2-120 C 50/50 37.19 MW 37.19 MW
958262 AF2-120 E 50/50 24.79 MW 24.79 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 0.04 MW 0.04 MW
NY PJM->LTFIMP_NY CLTF 0.02 MW 0.02 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.08 MW 0.08 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.02 MW 0.02 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.01 MW 0.01 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.1 MW 0.1 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 0.27 MW 0.27 MW
MDU PJM->LTFIMP_MDU CLTF 0.0 MW 0.0 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.03 MW 0.03 MW

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
314911 to 314922 ckt 1
Contingency Name:
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 117.95 %
Rating: 3220.44 MVA
Rating Type: B
MVA to Mitigate: 3798.63 MVA
MW Contribution: 8.7 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
963041 AG1-153 C Adder 4.27 MW 3.63 MW
963042 AG1-153 E Adder 6.4 MW 5.44 MW
965291 AG1-394 C Adder 0.71 MW 0.6 MW
965292 AG1-394 E Adder 1.3 MW 1.11 MW
314541 3WATKINS Adder 0.58 MW 0.5 MW
920042 AA2-088 E OP Adder 8.83 MW 7.5 MW
934521 AD1-076 C Adder 10.28 MW 8.73 MW
934522 AD1-076 E Adder 5.24 MW 4.45 MW
944011 AF1-069 C Adder 9.93 MW 8.44 MW
944012 AF1-069 E Adder 3.86 MW 3.28 MW
900672 V4-068 E Adder 0.3 MW 0.25 MW
940492 AE2-034 E Adder 2.61 MW 2.22 MW
941031 AE2-094 C Adder 30.4 MW 25.84 MW
941032 AE2-094 E Adder 13.62 MW 11.57 MW
957521 AF2-046 C Adder 4.0 MW 3.4 MW
314539 3UNCAMP Adder 5.17 MW 4.4 MW
916042 Z1-036 E Adder 24.49 MW 20.82 MW
938771 AE1-103 C Adder 2.5 MW 2.13 MW
938772 AE1-103 E Adder 3.46 MW 2.94 MW
314229 6MT RD221 50/50 0.11 MW 0.11 MW
314236 6NRTHEST 50/50 0.17 MW 0.17 MW
314331 6POE Adder 1.19 MW 1.01 MW
314507 3THOMPSN Adder 1.77 MW 1.51 MW
314525 6KINGFORK Adder 0.89 MW 0.76 MW
314550 6HICKORY Adder 1.91 MW 1.62 MW
315039 1LDYSMT3 50/50 4.42 MW 4.42 MW
315040 1LDYSMT4 50/50 4.43 MW 4.43 MW
315041 1LDYSMT5 50/50 4.44 MW 4.44 MW
315060 1CHESTF5 Adder 57.85 MW 49.17 MW
315065 1CHESTF6 Adder 17.75 MW 15.09 MW
315070 1DARBY 4 50/50 2.37 MW 2.37 MW
315073 1STONECA Adder 6.25 MW 5.31 MW
315083 1SPRUNCA Adder 8.22 MW 6.99 MW
315084 1SPRUNCB Adder 8.22 MW 6.99 MW
315092 1YORKTN3 Adder 118.69 MW 100.89 MW
925865 AC1-065 E Adder 14.52 MW 12.34 MW
926412 AC1-112 E 50/50 1.05 MW 1.05 MW
926662 AC1-147 E Adder 1.16 MW 0.99 MW
926755 AC1-161 E Adder 11.44 MW 9.72 MW
927226 AC1-216 E Adder 6.94 MW 5.9 MW
934392 AD1-063 E Adder 0.94 MW 0.8 MW
935112 AD1-144 E Adder 0.83 MW 0.7 MW
936591 AD2-074 C Adder 4.69 MW 3.99 MW
936592 AD2-074 E Adder 7.65 MW 6.51 MW
942341 AE2-247 C Adder 1.31 MW 1.11 MW
942342 AE2-247 E Adder 1.8 MW 1.53 MW
943461 AF1-017 C Adder 1.18 MW 1.0 MW
943462 AF1-017 E Adder 1.93 MW 1.64 MW
943612 AF1-032 E Adder 0.81 MW 0.69 MW
943741 AF1-042 C Adder 2.45 MW 2.09 MW
943742 AF1-042 E Adder 4.0 MW 3.4 MW
958502 AF2-144 E Adder 0.96 MW 0.81 MW
961951 AG1-038 C Adder 2.71 MW 2.31 MW
961952 AG1-038 E Adder 3.75 MW 3.19 MW
966661 AG1-536 C Adder 4.49 MW 3.82 MW
966662 AG1-536 E Adder 6.04 MW 5.13 MW
966871 AG1-558 C Adder 2.2 MW 1.87 MW
966872 AG1-558 E Adder 1.11 MW 0.94 MW
966881 AG1-559 C 50/50 2.29 MW 2.29 MW
966882 AG1-559 E 50/50 1.15 MW 1.15 MW
315260 1GOSPORTA Adder 1.87 MW 1.59 MW
315261 1GOSPORTB Adder 2.39 MW 2.03 MW
315262 1GOSPORTC Adder 2.03 MW 1.73 MW
316076 AC2-137 E Adder 1.22 MW 1.04 MW
316157 AD2-030 E Adder 1.03 MW 0.88 MW
913392 Y1-086 E Adder 1.91 MW 1.62 MW
916192 Z1-068 E Adder 1.65 MW 1.4 MW
923832 AB2-022 E Adder 1.08 MW 0.92 MW
923842 AB2-024 E Adder 1.57 MW 1.34 MW
923852 AB2-025 E Adder 0.94 MW 0.8 MW
923862 AB2-026 E Adder 0.97 MW 0.83 MW
930122 AB1-027 E 50/50 1.29 MW 1.29 MW
938552 AE1-074 E Adder 1.09 MW 0.92 MW
938562 AE1-075 E Adder 0.83 MW 0.71 MW
939312 AE1-162 E Adder 1.27 MW 1.08 MW
946262 AF1-291 E Adder 1.3 MW 1.1 MW
957411 AF2-035 C 50/50 8.26 MW 8.26 MW
957412 AF2-035 E 50/50 4.13 MW 4.13 MW
957492 AF2-043 E Adder 1.24 MW 1.05 MW
957601 AF2-054 C Adder 1.84 MW 1.56 MW
957602 AF2-054 E Adder 1.22 MW 1.04 MW
962861 AG1-135 C Adder 5.08 MW 4.32 MW
962862 AG1-135 E Adder 3.39 MW 2.88 MW
962962 AG1-145 E Adder 1.3 MW 1.11 MW
962971 AG1-146 C Adder 2.62 MW 2.23 MW
962972 AG1-146 E Adder 1.74 MW 1.48 MW
962981 AG1-147 C Adder 6.11 MW 5.19 MW
962982 AG1-147 E Adder 4.07 MW 3.46 MW
963051 AG1-154 C 50/50 3.4 MW 3.4 MW
963052 AG1-154 E 50/50 5.09 MW 5.09 MW
901082 W1-029 E Adder 27.59 MW 23.45 MW
917122 Z2-027 E Adder 1.16 MW 0.99 MW
925332 AB2-190 E Adder 7.28 MW 6.18 MW
925522 AC1-027 E Adder 1.07 MW 0.91 MW
942001 AE2-212 C Adder 1.92 MW 1.63 MW
942002 AE2-212 E Adder 1.28 MW 1.09 MW
957832 AF2-077 E Adder 1.26 MW 1.07 MW
957871 AF2-081 C Adder 8.72 MW 7.41 MW
957872 AF2-081 E Adder 3.74 MW 3.17 MW
958161 AF2-110 C Adder 1.19 MW 1.01 MW
958162 AF2-110 E Adder 1.9 MW 1.61 MW
313811 6ELKO L286 Adder 1.28 MW 1.08 MW
933291 AC2-141 C Adder 26.79 MW 22.77 MW
933292 AC2-141 E Adder 11.44 MW 9.72 MW
939411 AE1-173 C Adder 73.68 MW 62.63 MW
939412 AE1-173 E Adder 49.12 MW 41.75 MW
934012 AD1-025 E Adder 8.98 MW 7.64 MW
927041 AC1-191 C Adder 8.82 MW 7.5 MW
927042 AC1-191 E Adder 4.39 MW 3.73 MW
933981 AD1-022 C Adder 7.33 MW 6.23 MW
933982 AD1-022 E Adder 3.99 MW 3.39 MW
313053 6PAPERMILL Adder 5.81 MW 4.93 MW
314594 6PLYMOUTH TP Adder 0.27 MW 0.23 MW
314632 6AYDLETT TAP Adder 1.18 MW 1.0 MW
316004 AC1-112 C 50/50 0.3 MW 0.3 MW
316160 AE1-175 E Adder 1.08 MW 0.91 MW
316169 AC1-164 GEN Adder 36.82 MW 31.29 MW
316233 AE1-074 C Adder 2.16 MW 1.83 MW
316240 AF1-291 C Adder 1.94 MW 1.65 MW
316312 AB1-027 C 50/50 0.49 MW 0.49 MW
924516 AB2-100 E1 Adder 2.33 MW 1.98 MW
924517 AB2-100 E2 Adder 2.33 MW 1.98 MW
926785 AC1-164_E Adder 16.54 MW 14.06 MW
934065 AD1-033 E Adder 4.39 MW 3.73 MW
937226 AE2-253 E Adder 5.1 MW 4.33 MW
939612 AE1-191 E Adder 4.96 MW 4.21 MW
315037 1LDYSMT1 50/50 4.25 MW 4.25 MW
315038 1LDYSMT2 50/50 4.3 MW 4.3 MW
315051 AA1-145 CT1 50/50 4.7 MW 4.7 MW
315052 AA1-145 CT2 50/50 4.7 MW 4.7 MW
939246 AE1-155 E Adder 7.27 MW 6.18 MW
919153 AA1-139 E2 Adder 3.56 MW 3.03 MW
919152 AA1-139 E1 Adder 3.56 MW 3.03 MW
920692 AA2-178 E Adder 3.48 MW 2.96 MW
924814 AB2-134 E Adder 11.37 MW 9.66 MW
316084 AB2-161 E Adder 4.87 MW 4.14 MW
932046 AC2-012 E Adder 11.52 MW 9.79 MW
316311 AC2-079 C Adder 5.02 MW 4.26 MW
932596 AC2-079 E Adder 8.18 MW 6.96 MW
934146 AD1-041 E Adder 3.1 MW 2.63 MW
934576 AD1-082 E Adder 3.88 MW 3.29 MW
316349 AD2-085 C Adder 3.01 MW 2.56 MW
936666 AD2-085 E Adder 4.91 MW 4.18 MW
961611 AG1-000B C Adder 14.24 MW 12.1 MW
941591 AE2-156 C Adder 15.74 MW 13.38 MW
944581 AF1-123 C Adder 39.82 MW 33.85 MW
944582 AF1-123 E Adder 91.18 MW 77.51 MW
944591 AF1-124 C Adder 39.96 MW 33.97 MW
944592 AF1-124 E Adder 91.52 MW 77.79 MW
944601 AF1-125 C Adder 39.21 MW 33.33 MW
944602 AF1-125 E Adder 89.75 MW 76.29 MW
944631 AF1-128 C Adder 36.2 MW 30.77 MW
958261 AF2-120 C Adder 5.22 MW 4.44 MW
958262 AF2-120 E Adder 3.48 MW 2.96 MW
965281 AG1-393 C Adder 1.93 MW 1.64 MW
965282 AG1-393 E Adder 1.29 MW 1.09 MW
934501 AD1-074 C Adder 28.29 MW 24.05 MW
934502 AD1-074 E Adder 14.4 MW 12.24 MW
934511 AD1-075 C Adder 7.07 MW 6.01 MW
934512 AD1-075 E Adder 3.6 MW 3.06 MW
935161 AD1-151 C Adder 14.52 MW 12.34 MW
935162 AD1-151 E Adder 9.68 MW 8.23 MW
938531 AE1-072 C Adder 15.31 MW 13.02 MW
938532 AE1-072 E Adder 7.98 MW 6.79 MW
939191 AE1-149 C Adder 9.48 MW 8.06 MW
939192 AE1-149 E Adder 6.32 MW 5.37 MW
939261 AE1-157 C 50/50 13.32 MW 13.32 MW
939262 AE1-157 E 50/50 7.23 MW 7.23 MW
939602 AE1-190 E Adder 1.24 MW 1.05 MW
940431 AE2-027 C Adder 11.6 MW 9.86 MW
940432 AE2-027 E Adder 7.74 MW 6.58 MW
940481 AE2-033 C Adder 13.14 MW 11.17 MW
940482 AE2-033 E Adder 8.86 MW 7.53 MW
940541 AE2-040 C Adder 2.33 MW 1.98 MW
940551 AE2-041 C Adder 6.24 MW 5.3 MW
940641 AE2-051 C Adder 13.72 MW 11.66 MW
940642 AE2-051 E Adder 9.15 MW 7.78 MW
941101 AE2-104 C Adder 2.92 MW 2.48 MW
941102 AE2-104 E Adder 4.64 MW 3.95 MW
943471 AF1-018 C Adder 6.24 MW 5.3 MW
944641 AF1-129 C Adder 92.56 MW 78.67 MW
315043 1FOUR RIVERA 50/50 2.95 MW 2.95 MW
315044 1FOUR RIVERB 50/50 2.95 MW 2.95 MW
315045 1FOUR RIVERC 50/50 3.61 MW 3.61 MW
315046 1FOUR RIVERD 50/50 2.91 MW 2.91 MW
315047 1FOUR RIVERE 50/50 2.91 MW 2.91 MW
315048 1FOUR RIVERF 50/50 3.55 MW 3.55 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 45.84 MW 45.84 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 25.97 MW 25.97 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 81.52 MW 81.52 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 6.39 MW 6.39 MW
NY PJM->LTFIMP_NY CLTF 2.83 MW 2.83 MW
LGEE LTFEXP_LGEE->PJM CLTF 1.82 MW 1.82 MW
WEC LTFEXP_WEC->PJM CLTF 0.94 MW 0.94 MW
CPLE LTFEXP_CPLE->PJM CLTF 9.11 MW 9.11 MW
TVA LTFEXP_TVA->PJM CLTF 6.57 MW 6.57 MW
MEC LTFEXP_MEC->PJM CLTF 5.16 MW 5.16 MW
LAGN LTFEXP_LAGN->PJM CLTF 8.19 MW 8.19 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.34 MW 0.34 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 40.55 MW 40.55 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 4.35 MW 4.35 MW

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
957190 to 314131 ckt 1
Contingency Name:
DVP_P1-2: LN 574_SRT-S
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 104.84 %
Rating: 559.3 MVA
Rating Type: B
MVA to Mitigate: 586.36 MVA
MW Contribution: 13.04 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
315034 1NORNECKC1 50/50 0.99 MW 0.99 MW
315035 1NORNECKC2 50/50 0.95 MW 0.95 MW
925865 AC1-065 E 50/50 11.05 MW 11.05 MW
926472 AC1-118 E 50/50 2.46 MW 2.46 MW
934392 AD1-063 E 50/50 0.72 MW 0.72 MW
936582 AD2-073 E 50/50 1.99 MW 1.99 MW
936591 AD2-074 C 50/50 6.23 MW 6.23 MW
936592 AD2-074 E 50/50 10.17 MW 10.17 MW
943741 AF1-042 C 50/50 3.26 MW 3.26 MW
943742 AF1-042 E 50/50 5.32 MW 5.32 MW
944491 AF1-114 C 50/50 21.14 MW 21.14 MW
944492 AF1-114 E 50/50 29.2 MW 29.2 MW
961951 AG1-038 C 50/50 3.6 MW 3.6 MW
961952 AG1-038 E 50/50 4.98 MW 4.98 MW
966661 AG1-536 C 50/50 6.73 MW 6.73 MW
966662 AG1-536 E 50/50 9.04 MW 9.04 MW
316077 AC2-138 C 50/50 0.33 MW 0.33 MW
316078 AC2-138 E 50/50 1.37 MW 1.37 MW
316156 AD2-030 C 50/50 0.27 MW 0.27 MW
316157 AD2-030 E 50/50 0.85 MW 0.85 MW
923842 AB2-024 E Adder 1.15 MW 0.98 MW
957601 AF2-054 C 50/50 1.51 MW 1.51 MW
957602 AF2-054 E 50/50 1.01 MW 1.01 MW
962861 AG1-135 C 50/50 7.4 MW 7.4 MW
962862 AG1-135 E 50/50 4.94 MW 4.94 MW
962971 AG1-146 C 50/50 3.23 MW 3.23 MW
962972 AG1-146 E 50/50 2.15 MW 2.15 MW
962981 AG1-147 C 50/50 7.53 MW 7.53 MW
962982 AG1-147 E 50/50 5.02 MW 5.02 MW
963611 AG1-210 C 50/50 0.98 MW 0.98 MW
963612 AG1-210 E 50/50 1.47 MW 1.47 MW
964211 AG1-282 C 50/50 2.74 MW 2.74 MW
964212 AG1-282 E 50/50 1.82 MW 1.82 MW
957832 AF2-077 E Adder 0.75 MW 0.64 MW
957971 AF2-091 C 50/50 7.19 MW 7.19 MW
957972 AF2-091 E 50/50 9.93 MW 9.93 MW
314181 3NORNECK 50/50 1.3 MW 1.3 MW
313053 6PAPERMILL Adder 4.29 MW 3.64 MW
316059 AD1-063 C 50/50 0.17 MW 0.17 MW
316169 AC1-164 GEN Adder 15.66 MW 13.31 MW
926785 AC1-164_E Adder 7.04 MW 5.98 MW
939611 AE1-191 C 50/50 0.94 MW 0.94 MW
939612 AE1-191 E 50/50 3.91 MW 3.91 MW
316201 AC1-065 C 50/50 1.08 MW 1.08 MW
316223 AC1-118 C 50/50 0.78 MW 0.78 MW
316337 AD2-073 C 50/50 0.65 MW 0.65 MW
316404 AE1-155 C 50/50 2.64 MW 2.64 MW
939246 AE1-155 E 50/50 10.89 MW 10.89 MW
316280 AD1-041 C 50/50 0.59 MW 0.59 MW
934146 AD1-041 E 50/50 2.44 MW 2.44 MW
958261 AF2-120 C 50/50 7.82 MW 7.82 MW
958262 AF2-120 E 50/50 5.21 MW 5.21 MW
939601 AE1-190 C 50/50 0.23 MW 0.23 MW
939602 AE1-190 E 50/50 0.98 MW 0.98 MW
940551 AE2-041 C 50/50 4.78 MW 4.78 MW
943471 AF1-018 C 50/50 4.78 MW 4.78 MW
957191 AF2-013 C 50/50 65.45 MW 65.45 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 8.26 MW 8.26 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 5.04 MW 5.04 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 17.55 MW 17.55 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.1 MW 1.1 MW
NY PJM->LTFIMP_NY CLTF 0.5 MW 0.5 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.33 MW 0.33 MW
WEC LTFEXP_WEC->PJM CLTF 0.17 MW 0.17 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.02 MW 2.02 MW
TVA LTFEXP_TVA->PJM CLTF 1.31 MW 1.31 MW
MEC LTFEXP_MEC->PJM CLTF 0.96 MW 0.96 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.64 MW 1.64 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.06 MW 0.06 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 7.02 MW 7.02 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.96 MW 0.96 MW

Details for AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
944490 to 313810 ckt 1
Contingency Name:
DVP_P1-2: LN 574_SRT-S
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 104.24 %
Rating: 571.52 MVA
Rating Type: B
MVA to Mitigate: 595.77 MVA
MW Contribution: 13.04 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
315034 1NORNECKC1 50/50 0.99 MW 0.99 MW
315035 1NORNECKC2 50/50 0.95 MW 0.95 MW
315092 1YORKTN3 Adder 46.63 MW 39.63 MW
925865 AC1-065 E 50/50 11.05 MW 11.05 MW
926472 AC1-118 E 50/50 2.46 MW 2.46 MW
934392 AD1-063 E 50/50 0.72 MW 0.72 MW
936582 AD2-073 E 50/50 1.99 MW 1.99 MW
936591 AD2-074 C 50/50 6.23 MW 6.23 MW
936592 AD2-074 E 50/50 10.17 MW 10.17 MW
943741 AF1-042 C 50/50 3.26 MW 3.26 MW
943742 AF1-042 E 50/50 5.32 MW 5.32 MW
944491 AF1-114 C 50/50 21.14 MW 21.14 MW
944492 AF1-114 E 50/50 29.2 MW 29.2 MW
961951 AG1-038 C 50/50 3.6 MW 3.6 MW
961952 AG1-038 E 50/50 4.98 MW 4.98 MW
966661 AG1-536 C 50/50 6.73 MW 6.73 MW
966662 AG1-536 E 50/50 9.04 MW 9.04 MW
316076 AC2-137 E Adder 0.46 MW 0.39 MW
316077 AC2-138 C 50/50 0.33 MW 0.33 MW
316078 AC2-138 E 50/50 1.37 MW 1.37 MW
316156 AD2-030 C 50/50 0.27 MW 0.27 MW
316157 AD2-030 E 50/50 0.85 MW 0.85 MW
923842 AB2-024 E Adder 1.15 MW 0.98 MW
957601 AF2-054 C 50/50 1.51 MW 1.51 MW
957602 AF2-054 E 50/50 1.01 MW 1.01 MW
962861 AG1-135 C 50/50 7.4 MW 7.4 MW
962862 AG1-135 E 50/50 4.94 MW 4.94 MW
962962 AG1-145 E Adder 0.53 MW 0.45 MW
962971 AG1-146 C 50/50 3.23 MW 3.23 MW
962972 AG1-146 E 50/50 2.15 MW 2.15 MW
962981 AG1-147 C 50/50 7.53 MW 7.53 MW
962982 AG1-147 E 50/50 5.02 MW 5.02 MW
963611 AG1-210 C 50/50 0.98 MW 0.98 MW
963612 AG1-210 E 50/50 1.47 MW 1.47 MW
964211 AG1-282 C 50/50 2.74 MW 2.74 MW
964212 AG1-282 E 50/50 1.82 MW 1.82 MW
957832 AF2-077 E Adder 0.75 MW 0.64 MW
957971 AF2-091 C 50/50 7.19 MW 7.19 MW
957972 AF2-091 E 50/50 9.93 MW 9.93 MW
313811 6ELKO L286 Adder 0.48 MW 0.41 MW
314181 3NORNECK 50/50 1.3 MW 1.3 MW
313053 6PAPERMILL Adder 4.29 MW 3.64 MW
316059 AD1-063 C 50/50 0.17 MW 0.17 MW
316160 AE1-175 E Adder 0.44 MW 0.37 MW
316169 AC1-164 GEN Adder 15.66 MW 13.31 MW
926785 AC1-164_E Adder 7.04 MW 5.98 MW
939611 AE1-191 C 50/50 0.94 MW 0.94 MW
939612 AE1-191 E 50/50 3.91 MW 3.91 MW
316201 AC1-065 C 50/50 1.08 MW 1.08 MW
316223 AC1-118 C 50/50 0.78 MW 0.78 MW
316337 AD2-073 C 50/50 0.65 MW 0.65 MW
316404 AE1-155 C 50/50 2.64 MW 2.64 MW
939246 AE1-155 E 50/50 10.89 MW 10.89 MW
316280 AD1-041 C 50/50 0.59 MW 0.59 MW
934146 AD1-041 E 50/50 2.44 MW 2.44 MW
958261 AF2-120 C 50/50 7.82 MW 7.82 MW
958262 AF2-120 E 50/50 5.21 MW 5.21 MW
939601 AE1-190 C 50/50 0.23 MW 0.23 MW
939602 AE1-190 E 50/50 0.98 MW 0.98 MW
940551 AE2-041 C 50/50 4.78 MW 4.78 MW
943471 AF1-018 C 50/50 4.78 MW 4.78 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 8.26 MW 8.26 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 5.04 MW 5.04 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 17.55 MW 17.55 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.1 MW 1.1 MW
NY PJM->LTFIMP_NY CLTF 0.5 MW 0.5 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.33 MW 0.33 MW
WEC LTFEXP_WEC->PJM CLTF 0.17 MW 0.17 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.02 MW 2.02 MW
TVA LTFEXP_TVA->PJM CLTF 1.31 MW 1.31 MW
MEC LTFEXP_MEC->PJM CLTF 0.96 MW 0.96 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.64 MW 1.64 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.06 MW 0.06 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 7.02 MW 7.02 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.96 MW 0.96 MW

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
314911 to 314905 ckt 1
Contingency Name:
DVP_P1-2: LN 573_SRT-A
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 103.76 %
Rating: 4070.2 MVA
Rating Type: B
MVA to Mitigate: 4223.17 MVA
MW Contribution: 11.33 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
963041 AG1-153 C Adder 5.43 MW 4.62 MW
963042 AG1-153 E Adder 8.15 MW 6.93 MW
314541 3WATKINS Adder 0.73 MW 0.62 MW
920042 AA2-088 E OP Adder 10.98 MW 9.34 MW
944011 AF1-069 C Adder 12.72 MW 10.81 MW
944012 AF1-069 E Adder 4.94 MW 4.2 MW
940492 AE2-034 E Adder 3.25 MW 2.77 MW
941031 AE2-094 C Adder 38.92 MW 33.08 MW
941032 AE2-094 E Adder 17.43 MW 14.82 MW
314539 3UNCAMP Adder 6.45 MW 5.49 MW
916042 Z1-036 E Adder 30.55 MW 25.97 MW
938771 AE1-103 C Adder 3.12 MW 2.65 MW
938772 AE1-103 E Adder 4.31 MW 3.67 MW
314229 6MT RD221 50/50 0.14 MW 0.14 MW
314236 6NRTHEST 50/50 0.21 MW 0.21 MW
314331 6POE Adder 1.49 MW 1.27 MW
314507 3THOMPSN Adder 2.22 MW 1.89 MW
314525 6KINGFORK Adder 1.12 MW 0.95 MW
314550 6HICKORY Adder 2.39 MW 2.03 MW
315039 1LDYSMT3 50/50 5.54 MW 5.54 MW
315040 1LDYSMT4 50/50 5.56 MW 5.56 MW
315041 1LDYSMT5 50/50 5.57 MW 5.57 MW
315060 1CHESTF5 Adder 71.67 MW 60.92 MW
315065 1CHESTF6 Adder 22.12 MW 18.8 MW
315070 1DARBY 4 50/50 2.91 MW 2.91 MW
315073 1STONECA Adder 7.78 MW 6.61 MW
315083 1SPRUNCA Adder 10.3 MW 8.75 MW
315084 1SPRUNCB Adder 10.3 MW 8.75 MW
315092 1YORKTN3 Adder 147.8 MW 125.63 MW
925865 AC1-065 E Adder 18.28 MW 15.54 MW
926412 AC1-112 E 50/50 1.28 MW 1.28 MW
926662 AC1-147 E Adder 1.46 MW 1.24 MW
926755 AC1-161 E Adder 14.31 MW 12.17 MW
927226 AC1-216 E Adder 8.65 MW 7.35 MW
934392 AD1-063 E Adder 1.18 MW 1.0 MW
935112 AD1-144 E Adder 1.04 MW 0.88 MW
936591 AD2-074 C Adder 6.06 MW 5.15 MW
936592 AD2-074 E Adder 9.89 MW 8.41 MW
942341 AE2-247 C Adder 1.63 MW 1.39 MW
942342 AE2-247 E Adder 2.26 MW 1.92 MW
943461 AF1-017 C Adder 1.48 MW 1.26 MW
943462 AF1-017 E Adder 2.41 MW 2.05 MW
943612 AF1-032 E Adder 1.01 MW 0.86 MW
943741 AF1-042 C Adder 3.17 MW 2.7 MW
943742 AF1-042 E Adder 5.18 MW 4.4 MW
961951 AG1-038 C Adder 3.51 MW 2.98 MW
961952 AG1-038 E Adder 4.84 MW 4.12 MW
966661 AG1-536 C Adder 5.85 MW 4.97 MW
966662 AG1-536 E Adder 7.86 MW 6.68 MW
966871 AG1-558 C Adder 2.72 MW 2.31 MW
966872 AG1-558 E Adder 1.37 MW 1.16 MW
966881 AG1-559 C 50/50 2.84 MW 2.84 MW
966882 AG1-559 E 50/50 1.43 MW 1.43 MW
315225 1N ANNA1 50/50 40.89 MW 40.89 MW
315226 1N ANNA2 50/50 40.9 MW 40.9 MW
315260 1GOSPORTA Adder 2.34 MW 1.99 MW
315261 1GOSPORTB Adder 2.99 MW 2.54 MW
315262 1GOSPORTC Adder 2.54 MW 2.16 MW
316076 AC2-137 E Adder 1.51 MW 1.28 MW
316078 AC2-138 E Adder 1.0 MW 0.85 MW
316157 AD2-030 E Adder 1.3 MW 1.11 MW
913392 Y1-086 E Adder 2.39 MW 2.03 MW
916192 Z1-068 E Adder 2.06 MW 1.75 MW
923832 AB2-022 E Adder 1.35 MW 1.15 MW
923842 AB2-024 E Adder 1.97 MW 1.68 MW
923852 AB2-025 E Adder 1.19 MW 1.01 MW
930122 AB1-027 E 50/50 1.57 MW 1.57 MW
938552 AE1-074 E Adder 1.38 MW 1.17 MW
939312 AE1-162 E Adder 1.59 MW 1.35 MW
946262 AF1-291 E Adder 1.62 MW 1.38 MW
957411 AF2-035 C 50/50 10.24 MW 10.24 MW
957412 AF2-035 E 50/50 5.12 MW 5.12 MW
957492 AF2-043 E Adder 1.55 MW 1.32 MW
957601 AF2-054 C Adder 2.32 MW 1.97 MW
957602 AF2-054 E Adder 1.55 MW 1.31 MW
962861 AG1-135 C Adder 6.6 MW 5.61 MW
962862 AG1-135 E Adder 4.4 MW 3.74 MW
962962 AG1-145 E Adder 1.62 MW 1.37 MW
962971 AG1-146 C Adder 3.37 MW 2.86 MW
962972 AG1-146 E Adder 2.25 MW 1.91 MW
962981 AG1-147 C Adder 7.86 MW 6.68 MW
962982 AG1-147 E Adder 5.24 MW 4.45 MW
963051 AG1-154 C 50/50 4.26 MW 4.26 MW
963052 AG1-154 E 50/50 6.39 MW 6.39 MW
963611 AG1-210 C Adder 0.71 MW 0.6 MW
963612 AG1-210 E Adder 1.07 MW 0.91 MW
964211 AG1-282 C Adder 2.17 MW 1.84 MW
964212 AG1-282 E Adder 1.44 MW 1.23 MW
901082 W1-029 E Adder 34.48 MW 29.31 MW
917122 Z2-027 E Adder 1.46 MW 1.24 MW
925332 AB2-190 E Adder 9.06 MW 7.7 MW
925522 AC1-027 E Adder 1.34 MW 1.14 MW
942001 AE2-212 C Adder 2.41 MW 2.04 MW
942002 AE2-212 E Adder 1.6 MW 1.36 MW
957832 AF2-077 E Adder 1.58 MW 1.34 MW
957871 AF2-081 C Adder 10.91 MW 9.27 MW
957872 AF2-081 E Adder 4.68 MW 3.97 MW
958161 AF2-110 C Adder 1.49 MW 1.27 MW
958162 AF2-110 E Adder 2.37 MW 2.02 MW
313811 6ELKO L286 Adder 1.57 MW 1.34 MW
314181 3NORNECK Adder 0.95 MW 0.81 MW
933291 AC2-141 C Adder 33.53 MW 28.5 MW
933292 AC2-141 E Adder 14.31 MW 12.17 MW
939411 AE1-173 C Adder 93.78 MW 79.71 MW
939412 AE1-173 E Adder 62.52 MW 53.14 MW
934012 AD1-025 E Adder 11.2 MW 9.52 MW
927041 AC1-191 C Adder 10.92 MW 9.28 MW
927042 AC1-191 E Adder 5.44 MW 4.62 MW
313053 6PAPERMILL Adder 7.29 MW 6.2 MW
314594 6PLYMOUTH TP Adder 0.34 MW 0.29 MW
314632 6AYDLETT TAP Adder 1.48 MW 1.26 MW
316004 AC1-112 C 50/50 0.37 MW 0.37 MW
316160 AE1-175 E Adder 1.33 MW 1.13 MW
316169 AC1-164 GEN Adder 45.35 MW 38.55 MW
316233 AE1-074 C Adder 2.74 MW 2.33 MW
316240 AF1-291 C Adder 2.43 MW 2.06 MW
316312 AB1-027 C 50/50 0.6 MW 0.6 MW
926785 AC1-164_E Adder 20.38 MW 17.32 MW
934065 AD1-033 E Adder 5.5 MW 4.67 MW
937226 AE2-253 E Adder 6.38 MW 5.43 MW
939612 AE1-191 E Adder 6.25 MW 5.31 MW
315037 1LDYSMT1 50/50 5.33 MW 5.33 MW
315038 1LDYSMT2 50/50 5.4 MW 5.4 MW
315051 AA1-145 CT1 50/50 5.75 MW 5.75 MW
315052 AA1-145 CT2 50/50 5.75 MW 5.75 MW
939246 AE1-155 E Adder 9.47 MW 8.05 MW
919153 AA1-139 E2 Adder 4.46 MW 3.79 MW
919152 AA1-139 E1 Adder 4.46 MW 3.79 MW
920692 AA2-178 E Adder 4.34 MW 3.69 MW
924814 AB2-134 E Adder 14.16 MW 12.04 MW
316084 AB2-161 E Adder 6.1 MW 5.18 MW
932046 AC2-012 E Adder 14.42 MW 12.26 MW
316311 AC2-079 C Adder 6.28 MW 5.34 MW
932596 AC2-079 E Adder 10.24 MW 8.71 MW
934146 AD1-041 E Adder 3.91 MW 3.32 MW
934576 AD1-082 E Adder 4.86 MW 4.13 MW
316349 AD2-085 C Adder 3.77 MW 3.21 MW
936666 AD2-085 E Adder 6.15 MW 5.23 MW
961611 AG1-000B C Adder 17.76 MW 15.09 MW
941591 AE2-156 C Adder 19.7 MW 16.75 MW
944581 AF1-123 C Adder 49.89 MW 42.41 MW
944582 AF1-123 E Adder 114.24 MW 97.11 MW
944591 AF1-124 C Adder 50.07 MW 42.56 MW
944592 AF1-124 E Adder 114.66 MW 97.46 MW
944601 AF1-125 C Adder 49.12 MW 41.75 MW
944602 AF1-125 E Adder 112.45 MW 95.58 MW
944631 AF1-128 C Adder 44.85 MW 38.12 MW
958261 AF2-120 C Adder 6.8 MW 5.78 MW
958262 AF2-120 E Adder 4.53 MW 3.85 MW
965281 AG1-393 C Adder 2.41 MW 2.05 MW
965282 AG1-393 E Adder 1.61 MW 1.37 MW
934501 AD1-074 C Adder 25.02 MW 21.27 MW
935161 AD1-151 C Adder 18.09 MW 15.38 MW
935162 AD1-151 E Adder 12.06 MW 10.25 MW
938531 AE1-072 C Adder 19.16 MW 16.29 MW
938532 AE1-072 E Adder 9.99 MW 8.49 MW
939191 AE1-149 C Adder 11.88 MW 10.1 MW
939192 AE1-149 E Adder 7.92 MW 6.73 MW
939261 AE1-157 C 50/50 16.59 MW 16.59 MW
939262 AE1-157 E 50/50 9.0 MW 9.0 MW
939602 AE1-190 E Adder 1.56 MW 1.33 MW
940431 AE2-027 C Adder 14.5 MW 12.32 MW
940432 AE2-027 E Adder 9.66 MW 8.21 MW
940481 AE2-033 C Adder 16.56 MW 14.08 MW
940482 AE2-033 E Adder 11.17 MW 9.49 MW
940541 AE2-040 C Adder 2.94 MW 2.5 MW
940551 AE2-041 C Adder 7.85 MW 6.67 MW
940641 AE2-051 C Adder 17.56 MW 14.92 MW
940642 AE2-051 E Adder 11.7 MW 9.95 MW
941101 AE2-104 C Adder 3.66 MW 3.11 MW
941102 AE2-104 E Adder 5.81 MW 4.94 MW
943471 AF1-018 C Adder 7.85 MW 6.67 MW
944641 AF1-129 C Adder 115.36 MW 98.05 MW
315043 1FOUR RIVERA 50/50 3.61 MW 3.61 MW
315044 1FOUR RIVERB 50/50 3.61 MW 3.61 MW
315045 1FOUR RIVERC 50/50 4.41 MW 4.41 MW
315046 1FOUR RIVERD 50/50 3.56 MW 3.56 MW
315047 1FOUR RIVERE 50/50 3.56 MW 3.56 MW
315048 1FOUR RIVERF 50/50 4.34 MW 4.34 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 31.53 MW 31.53 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 23.04 MW 23.04 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 92.19 MW 92.19 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 5.64 MW 5.64 MW
NY PJM->LTFIMP_NY CLTF 2.67 MW 2.67 MW
LGEE LTFEXP_LGEE->PJM CLTF 1.35 MW 1.35 MW
WEC LTFEXP_WEC->PJM CLTF 0.67 MW 0.67 MW
CPLE LTFEXP_CPLE->PJM CLTF 10.75 MW 10.75 MW
TVA LTFEXP_TVA->PJM CLTF 6.28 MW 6.28 MW
MEC LTFEXP_MEC->PJM CLTF 4.06 MW 4.06 MW
LAGN LTFEXP_LAGN->PJM CLTF 7.84 MW 7.84 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.26 MW 0.26 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 35.97 MW 35.97 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 5.13 MW 5.13 MW

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
314905 to 314900 ckt 1
Contingency Name:
DVP_P1-2: LN 594_SRT-S
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 103.7 %
Rating: 4070.2 MVA
Rating Type: B
MVA to Mitigate: 4220.84 MVA
MW Contribution: 11.08 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
963041 AG1-153 C Adder 5.34 MW 4.54 MW
963042 AG1-153 E Adder 8.01 MW 6.81 MW
314541 3WATKINS Adder 0.72 MW 0.61 MW
944011 AF1-069 C Adder 12.5 MW 10.62 MW
944012 AF1-069 E Adder 4.85 MW 4.13 MW
941031 AE2-094 C Adder 38.24 MW 32.51 MW
941032 AE2-094 E Adder 17.13 MW 14.56 MW
314539 3UNCAMP Adder 6.34 MW 5.38 MW
916042 Z1-036 E Adder 29.98 MW 25.48 MW
938771 AE1-103 C Adder 3.07 MW 2.61 MW
938772 AE1-103 E Adder 4.23 MW 3.6 MW
314229 6MT RD221 50/50 0.14 MW 0.14 MW
314236 6NRTHEST 50/50 0.21 MW 0.21 MW
314331 6POE Adder 1.46 MW 1.24 MW
314507 3THOMPSN Adder 2.18 MW 1.85 MW
314525 6KINGFORK Adder 1.09 MW 0.93 MW
314550 6HICKORY Adder 2.34 MW 1.99 MW
315039 1LDYSMT3 50/50 5.39 MW 5.39 MW
315040 1LDYSMT4 50/50 5.4 MW 5.4 MW
315041 1LDYSMT5 50/50 5.42 MW 5.42 MW
315060 1CHESTF5 Adder 70.23 MW 59.7 MW
315065 1CHESTF6 Adder 21.69 MW 18.43 MW
315070 1DARBY 4 50/50 2.85 MW 2.85 MW
315073 1STONECA Adder 7.62 MW 6.48 MW
315083 1SPRUNCA Adder 10.1 MW 8.59 MW
315084 1SPRUNCB Adder 10.1 MW 8.59 MW
315092 1YORKTN3 Adder 144.86 MW 123.13 MW
925865 AC1-065 E Adder 17.89 MW 15.21 MW
926412 AC1-112 E 50/50 1.25 MW 1.25 MW
926662 AC1-147 E Adder 1.43 MW 1.22 MW
926755 AC1-161 E Adder 14.04 MW 11.94 MW
927226 AC1-216 E Adder 8.48 MW 7.21 MW
934392 AD1-063 E Adder 1.15 MW 0.98 MW
935112 AD1-144 E Adder 1.02 MW 0.86 MW
936591 AD2-074 C Adder 5.93 MW 5.04 MW
936592 AD2-074 E Adder 9.67 MW 8.22 MW
942341 AE2-247 C Adder 1.6 MW 1.36 MW
942342 AE2-247 E Adder 2.21 MW 1.88 MW
943461 AF1-017 C Adder 1.45 MW 1.23 MW
943462 AF1-017 E Adder 2.37 MW 2.01 MW
943612 AF1-032 E Adder 0.99 MW 0.84 MW
943741 AF1-042 C Adder 3.1 MW 2.64 MW
943742 AF1-042 E Adder 5.06 MW 4.3 MW
961951 AG1-038 C Adder 3.43 MW 2.91 MW
961952 AG1-038 E Adder 4.73 MW 4.02 MW
966661 AG1-536 C Adder 5.72 MW 4.86 MW
966662 AG1-536 E Adder 7.68 MW 6.53 MW
966871 AG1-558 C Adder 2.66 MW 2.26 MW
966872 AG1-558 E Adder 1.34 MW 1.14 MW
966881 AG1-559 C 50/50 2.77 MW 2.77 MW
966882 AG1-559 E 50/50 1.39 MW 1.39 MW
315225 1N ANNA1 50/50 40.26 MW 40.26 MW
315226 1N ANNA2 50/50 40.27 MW 40.27 MW
315260 1GOSPORTA Adder 2.3 MW 1.95 MW
315261 1GOSPORTB Adder 2.94 MW 2.5 MW
315262 1GOSPORTC Adder 2.49 MW 2.12 MW
316076 AC2-137 E Adder 1.48 MW 1.25 MW
316157 AD2-030 E Adder 1.28 MW 1.08 MW
913392 Y1-086 E Adder 2.34 MW 1.99 MW
916192 Z1-068 E Adder 2.02 MW 1.72 MW
923832 AB2-022 E Adder 1.32 MW 1.12 MW
923842 AB2-024 E Adder 1.93 MW 1.64 MW
923852 AB2-025 E Adder 1.17 MW 0.99 MW
930122 AB1-027 E 50/50 1.54 MW 1.54 MW
938552 AE1-074 E Adder 1.36 MW 1.15 MW
939312 AE1-162 E Adder 1.56 MW 1.32 MW
946262 AF1-291 E Adder 1.59 MW 1.35 MW
957411 AF2-035 C 50/50 9.98 MW 9.98 MW
957412 AF2-035 E 50/50 4.99 MW 4.99 MW
957492 AF2-043 E Adder 1.52 MW 1.29 MW
957601 AF2-054 C Adder 2.27 MW 1.93 MW
957602 AF2-054 E Adder 1.51 MW 1.29 MW
962861 AG1-135 C Adder 6.46 MW 5.49 MW
962862 AG1-135 E Adder 4.3 MW 3.66 MW
962962 AG1-145 E Adder 1.58 MW 1.35 MW
962971 AG1-146 C Adder 3.29 MW 2.8 MW
962972 AG1-146 E Adder 2.2 MW 1.87 MW
962981 AG1-147 C Adder 7.69 MW 6.53 MW
962982 AG1-147 E Adder 5.12 MW 4.36 MW
963051 AG1-154 C 50/50 4.14 MW 4.14 MW
963052 AG1-154 E 50/50 6.22 MW 6.22 MW
901082 W1-029 E Adder 33.83 MW 28.75 MW
917122 Z2-027 E Adder 1.43 MW 1.21 MW
925332 AB2-190 E Adder 8.88 MW 7.55 MW
925522 AC1-027 E Adder 1.31 MW 1.11 MW
942001 AE2-212 C Adder 2.36 MW 2.01 MW
942002 AE2-212 E Adder 1.57 MW 1.34 MW
957832 AF2-077 E Adder 1.55 MW 1.31 MW
957871 AF2-081 C Adder 10.7 MW 9.1 MW
957872 AF2-081 E Adder 4.59 MW 3.9 MW
958161 AF2-110 C Adder 1.46 MW 1.24 MW
958162 AF2-110 E Adder 2.33 MW 1.98 MW
313811 6ELKO L286 Adder 1.54 MW 1.31 MW
933291 AC2-141 C Adder 32.89 MW 27.96 MW
933292 AC2-141 E Adder 14.04 MW 11.94 MW
939411 AE1-173 C Adder 92.07 MW 78.26 MW
939412 AE1-173 E Adder 61.38 MW 52.17 MW
934012 AD1-025 E Adder 10.98 MW 9.33 MW
927041 AC1-191 C Adder 10.68 MW 9.08 MW
927042 AC1-191 E Adder 5.32 MW 4.52 MW
313053 6PAPERMILL Adder 7.13 MW 6.06 MW
314632 6AYDLETT TAP Adder 1.45 MW 1.23 MW
316004 AC1-112 C 50/50 0.36 MW 0.36 MW
316160 AE1-175 E Adder 1.31 MW 1.11 MW
316169 AC1-164 GEN Adder 44.41 MW 37.75 MW
316233 AE1-074 C Adder 2.69 MW 2.29 MW
316240 AF1-291 C Adder 2.38 MW 2.02 MW
316312 AB1-027 C 50/50 0.58 MW 0.58 MW
926785 AC1-164_E Adder 19.95 MW 16.96 MW
934065 AD1-033 E Adder 5.39 MW 4.58 MW
937226 AE2-253 E Adder 6.26 MW 5.32 MW
939612 AE1-191 E Adder 6.12 MW 5.2 MW
926004 AC1-076_E Adder 4.28 MW 3.64 MW
315037 1LDYSMT1 50/50 5.19 MW 5.19 MW
315038 1LDYSMT2 50/50 5.25 MW 5.25 MW
315051 AA1-145 CT1 50/50 5.62 MW 5.62 MW
315052 AA1-145 CT2 50/50 5.62 MW 5.62 MW
939246 AE1-155 E Adder 9.26 MW 7.87 MW
919153 AA1-139 E2 Adder 4.38 MW 3.72 MW
919152 AA1-139 E1 Adder 4.38 MW 3.72 MW
920692 AA2-178 E Adder 0.86 MW 0.73 MW
924814 AB2-134 E Adder 13.89 MW 11.8 MW
316084 AB2-161 E Adder 5.98 MW 5.08 MW
316044 AC1-158 C1 50/50 7.37 MW 7.37 MW
316045 AC1-158 C2 50/50 7.37 MW 7.37 MW
926739 AC1-158 E1 50/50 19.27 MW 19.27 MW
926740 AC1-158 E2 50/50 19.27 MW 19.27 MW
932046 AC2-012 E Adder 14.14 MW 12.02 MW
316311 AC2-079 C Adder 6.16 MW 5.24 MW
932596 AC2-079 E Adder 10.05 MW 8.54 MW
934146 AD1-041 E Adder 3.82 MW 3.25 MW
934576 AD1-082 E Adder 4.76 MW 4.05 MW
316349 AD2-085 C Adder 3.7 MW 3.14 MW
936666 AD2-085 E Adder 6.03 MW 5.13 MW
961611 AG1-000B C Adder 17.41 MW 14.8 MW
941591 AE2-156 C Adder 19.33 MW 16.43 MW
944581 AF1-123 C Adder 48.94 MW 41.6 MW
944582 AF1-123 E Adder 112.08 MW 95.26 MW
944591 AF1-124 C Adder 49.12 MW 41.75 MW
944592 AF1-124 E Adder 112.48 MW 95.61 MW
944601 AF1-125 C Adder 48.19 MW 40.96 MW
944602 AF1-125 E Adder 110.32 MW 93.77 MW
944631 AF1-128 C Adder 43.94 MW 37.35 MW
958261 AF2-120 C Adder 6.65 MW 5.65 MW
958262 AF2-120 E Adder 4.43 MW 3.77 MW
965281 AG1-393 C Adder 2.36 MW 2.01 MW
965282 AG1-393 E Adder 1.58 MW 1.34 MW
935161 AD1-151 C Adder 17.74 MW 15.08 MW
935162 AD1-151 E Adder 11.83 MW 10.05 MW
938531 AE1-072 C Adder 18.8 MW 15.98 MW
938532 AE1-072 E Adder 9.8 MW 8.33 MW
939191 AE1-149 C Adder 11.66 MW 9.91 MW
939192 AE1-149 E Adder 7.77 MW 6.61 MW
939261 AE1-157 C 50/50 16.16 MW 16.16 MW
939262 AE1-157 E 50/50 8.77 MW 8.77 MW
939602 AE1-190 E Adder 1.53 MW 1.3 MW
940431 AE2-027 C Adder 14.22 MW 12.08 MW
940432 AE2-027 E Adder 9.48 MW 8.05 MW
940481 AE2-033 C Adder 16.26 MW 13.82 MW
940482 AE2-033 E Adder 10.96 MW 9.32 MW
940541 AE2-040 C Adder 2.89 MW 2.46 MW
940551 AE2-041 C Adder 7.68 MW 6.53 MW
940641 AE2-051 C Adder 17.24 MW 14.66 MW
940642 AE2-051 E Adder 11.5 MW 9.77 MW
941101 AE2-104 C Adder 3.59 MW 3.05 MW
941102 AE2-104 E Adder 5.7 MW 4.85 MW
943471 AF1-018 C Adder 7.68 MW 6.53 MW
944641 AF1-129 C Adder 113.11 MW 96.15 MW
315043 1FOUR RIVERA 50/50 3.53 MW 3.53 MW
315044 1FOUR RIVERB 50/50 3.53 MW 3.53 MW
315045 1FOUR RIVERC 50/50 4.31 MW 4.31 MW
315046 1FOUR RIVERD 50/50 3.48 MW 3.48 MW
315047 1FOUR RIVERE 50/50 3.48 MW 3.48 MW
315048 1FOUR RIVERF 50/50 4.25 MW 4.25 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 30.04 MW 30.04 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 22.37 MW 22.37 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 90.49 MW 90.49 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 5.75 MW 5.75 MW
NY PJM->LTFIMP_NY CLTF 2.72 MW 2.72 MW
LGEE LTFEXP_LGEE->PJM CLTF 1.3 MW 1.3 MW
WEC LTFEXP_WEC->PJM CLTF 0.64 MW 0.64 MW
CPLE LTFEXP_CPLE->PJM CLTF 10.56 MW 10.56 MW
TVA LTFEXP_TVA->PJM CLTF 6.12 MW 6.12 MW
MEC LTFEXP_MEC->PJM CLTF 3.91 MW 3.91 MW
LAGN LTFEXP_LAGN->PJM CLTF 7.64 MW 7.64 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.25 MW 0.25 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 36.64 MW 36.64 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 5.04 MW 5.04 MW

Details for 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9296_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
6CRANES-6STAFORD 230.0 kV Ckt 1 line
314134 to 314142 ckt 1
Contingency Name:
DVP_P1-2: LN 9296_SRT-A
CONTINGENCY 'DVP_P1-2: LN 9296_SRT-A'
 OPEN BRANCH FROM BUS 314137 TO BUS 314145 CKT 1   /*6FREDBRG     230.0 - 6AQUI_HARB_B 230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 102.1 %
Rating: 984.18 MVA
Rating Type: B
MVA to Mitigate: 1004.88 MVA
MW Contribution: 7.92 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 50/50 0.48 MW 0.48 MW
315033 1BIRCHWDA 50/50 75.26 MW 75.26 MW
315039 1LDYSMT3 50/50 4.37 MW 4.37 MW
315040 1LDYSMT4 50/50 4.38 MW 4.38 MW
315041 1LDYSMT5 50/50 4.39 MW 4.39 MW
315050 1FOURRIVERG 50/50 4.18 MW 4.18 MW
315060 1CHESTF5 Adder 22.44 MW 19.07 MW
315092 1YORKTN3 Adder 45.52 MW 38.69 MW
925865 AC1-065 E Adder 8.26 MW 7.02 MW
926412 AC1-112 E Adder 0.41 MW 0.35 MW
926472 AC1-118 E 50/50 1.31 MW 1.31 MW
934392 AD1-063 E Adder 0.53 MW 0.45 MW
934781 AD1-105 C 50/50 1.18 MW 1.18 MW
934782 AD1-105 E 50/50 4.89 MW 4.89 MW
936582 AD2-073 E 50/50 1.1 MW 1.1 MW
936591 AD2-074 C Adder 3.9 MW 3.31 MW
936592 AD2-074 E Adder 6.36 MW 5.4 MW
943741 AF1-042 C Adder 2.04 MW 1.73 MW
943742 AF1-042 E Adder 3.33 MW 2.83 MW
944491 AF1-114 C 50/50 10.64 MW 10.64 MW
944492 AF1-114 E 50/50 14.7 MW 14.7 MW
961951 AG1-038 C Adder 2.25 MW 1.92 MW
961952 AG1-038 E Adder 3.11 MW 2.65 MW
966661 AG1-536 C Adder 4.09 MW 3.47 MW
966662 AG1-536 E Adder 5.49 MW 4.67 MW
966871 AG1-558 C Adder 1.16 MW 0.99 MW
966872 AG1-558 E Adder 0.58 MW 0.5 MW
966881 AG1-559 C Adder 1.77 MW 1.5 MW
966882 AG1-559 E Adder 0.89 MW 0.76 MW
316076 AC2-137 E Adder 0.49 MW 0.42 MW
316078 AC2-138 E Adder 0.8 MW 0.68 MW
316157 AD2-030 E Adder 0.61 MW 0.52 MW
923842 AB2-024 E Adder 0.87 MW 0.74 MW
930122 AB1-027 E Adder 0.51 MW 0.43 MW
957411 AF2-035 C Adder 6.37 MW 5.42 MW
957412 AF2-035 E Adder 3.19 MW 2.71 MW
957601 AF2-054 C Adder 1.09 MW 0.93 MW
957602 AF2-054 E Adder 0.73 MW 0.62 MW
962861 AG1-135 C Adder 4.52 MW 3.85 MW
962862 AG1-135 E Adder 3.02 MW 2.56 MW
962962 AG1-145 E Adder 0.51 MW 0.44 MW
962971 AG1-146 C Adder 2.06 MW 1.75 MW
962972 AG1-146 E Adder 1.37 MW 1.17 MW
962981 AG1-147 C Adder 4.8 MW 4.08 MW
962982 AG1-147 E Adder 3.2 MW 2.72 MW
963051 AG1-154 C 50/50 3.36 MW 3.36 MW
963052 AG1-154 E 50/50 5.04 MW 5.04 MW
963611 AG1-210 C Adder 0.57 MW 0.48 MW
963612 AG1-210 E Adder 0.86 MW 0.73 MW
964211 AG1-282 C Adder 1.63 MW 1.38 MW
964212 AG1-282 E Adder 1.08 MW 0.92 MW
957832 AF2-077 E Adder 0.61 MW 0.52 MW
957971 AF2-091 C 50/50 3.62 MW 3.62 MW
957972 AF2-091 E 50/50 5.0 MW 5.0 MW
313811 6ELKO L286 Adder 0.52 MW 0.44 MW
314181 3NORNECK Adder 0.76 MW 0.65 MW
927041 AC1-191 C Adder 4.66 MW 3.96 MW
927042 AC1-191 E Adder 2.32 MW 1.97 MW
313053 6PAPERMILL Adder 3.24 MW 2.75 MW
316160 AE1-175 E Adder 0.42 MW 0.36 MW
316169 AC1-164 GEN Adder 15.3 MW 13.0 MW
926785 AC1-164_E Adder 6.87 MW 5.84 MW
939612 AE1-191 E Adder 2.88 MW 2.44 MW
315037 1LDYSMT1 50/50 4.2 MW 4.2 MW
315038 1LDYSMT2 50/50 4.26 MW 4.26 MW
316223 AC1-118 C 50/50 0.41 MW 0.41 MW
316337 AD2-073 C 50/50 0.36 MW 0.36 MW
939246 AE1-155 E Adder 6.61 MW 5.62 MW
934146 AD1-041 E Adder 1.8 MW 1.53 MW
944631 AF1-128 C Adder 14.04 MW 11.93 MW
958261 AF2-120 C Adder 4.75 MW 4.04 MW
958262 AF2-120 E Adder 3.17 MW 2.69 MW
939261 AE1-157 C 50/50 11.33 MW 11.33 MW
939262 AE1-157 E 50/50 6.15 MW 6.15 MW
939602 AE1-190 E Adder 0.72 MW 0.61 MW
940551 AE2-041 C Adder 3.55 MW 3.02 MW
943471 AF1-018 C Adder 3.55 MW 3.02 MW
957191 AF2-013 C 50/50 31.8 MW 31.8 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 10.27 MW 10.27 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 6.47 MW 6.47 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 23.06 MW 23.06 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.77 MW 1.77 MW
NY PJM->LTFIMP_NY CLTF 0.8 MW 0.8 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.42 MW 0.42 MW
WEC LTFEXP_WEC->PJM CLTF 0.21 MW 0.21 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.65 MW 2.65 MW
TVA LTFEXP_TVA->PJM CLTF 1.69 MW 1.69 MW
MEC LTFEXP_MEC->PJM CLTF 1.22 MW 1.22 MW
LAGN LTFEXP_LAGN->PJM CLTF 2.12 MW 2.12 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.08 MW 0.08 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 11.26 MW 11.26 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 1.27 MW 1.27 MW

Details for 6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2157_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line
314140 to 314144 ckt 1
Contingency Name:
DVP_P1-2: LN 2157_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2157_SRT-A'
 OPEN BRANCH FROM BUS 314134 TO BUS 314137 CKT 1   /*6CRANES      230.0 - 6FREDBRG     230.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 101.4 %
Rating: 898.64 MVA
Rating Type: B
MVA to Mitigate: 911.24 MVA
MW Contribution: 7.25 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
314131 6ARNOLDS 50/50 0.44 MW 0.44 MW
315033 1BIRCHWDA 50/50 68.94 MW 68.94 MW
315039 1LDYSMT3 50/50 4.0 MW 4.0 MW
315040 1LDYSMT4 50/50 4.01 MW 4.01 MW
315041 1LDYSMT5 50/50 4.02 MW 4.02 MW
315050 1FOURRIVERG 50/50 3.83 MW 3.83 MW
315060 1CHESTF5 Adder 20.56 MW 17.47 MW
315092 1YORKTN3 Adder 41.7 MW 35.44 MW
925865 AC1-065 E Adder 7.57 MW 6.43 MW
926412 AC1-112 E Adder 0.38 MW 0.32 MW
926472 AC1-118 E 50/50 1.2 MW 1.2 MW
934392 AD1-063 E Adder 0.49 MW 0.41 MW
934781 AD1-105 C 50/50 1.08 MW 1.08 MW
934782 AD1-105 E 50/50 4.48 MW 4.48 MW
936582 AD2-073 E 50/50 1.01 MW 1.01 MW
936591 AD2-074 C Adder 3.57 MW 3.03 MW
936592 AD2-074 E Adder 5.82 MW 4.95 MW
943741 AF1-042 C Adder 1.87 MW 1.59 MW
943742 AF1-042 E Adder 3.05 MW 2.59 MW
944491 AF1-114 C 50/50 9.75 MW 9.75 MW
944492 AF1-114 E 50/50 13.46 MW 13.46 MW
961951 AG1-038 C Adder 2.06 MW 1.75 MW
961952 AG1-038 E Adder 2.85 MW 2.42 MW
966661 AG1-536 C Adder 3.74 MW 3.18 MW
966662 AG1-536 E Adder 5.03 MW 4.28 MW
966871 AG1-558 C Adder 1.06 MW 0.9 MW
966872 AG1-558 E Adder 0.54 MW 0.46 MW
966881 AG1-559 C Adder 1.62 MW 1.38 MW
966882 AG1-559 E Adder 0.82 MW 0.69 MW
316076 AC2-137 E Adder 0.45 MW 0.38 MW
316078 AC2-138 E Adder 0.73 MW 0.62 MW
316157 AD2-030 E Adder 0.56 MW 0.48 MW
923842 AB2-024 E Adder 0.8 MW 0.68 MW
930122 AB1-027 E Adder 0.47 MW 0.4 MW
957411 AF2-035 C Adder 5.84 MW 4.96 MW
957412 AF2-035 E Adder 2.92 MW 2.48 MW
957601 AF2-054 C Adder 1.0 MW 0.85 MW
957602 AF2-054 E Adder 0.67 MW 0.57 MW
962861 AG1-135 C Adder 4.14 MW 3.52 MW
962862 AG1-135 E Adder 2.76 MW 2.35 MW
962962 AG1-145 E Adder 0.47 MW 0.4 MW
962971 AG1-146 C Adder 1.88 MW 1.6 MW
962972 AG1-146 E Adder 1.26 MW 1.07 MW
962981 AG1-147 C Adder 4.4 MW 3.74 MW
962982 AG1-147 E Adder 2.93 MW 2.49 MW
963051 AG1-154 C 50/50 3.08 MW 3.08 MW
963052 AG1-154 E 50/50 4.61 MW 4.61 MW
963611 AG1-210 C Adder 0.52 MW 0.44 MW
963612 AG1-210 E Adder 0.78 MW 0.67 MW
964211 AG1-282 C Adder 1.49 MW 1.27 MW
964212 AG1-282 E Adder 0.99 MW 0.84 MW
957832 AF2-077 E Adder 0.56 MW 0.47 MW
957971 AF2-091 C 50/50 3.31 MW 3.31 MW
957972 AF2-091 E 50/50 4.58 MW 4.58 MW
313811 6ELKO L286 Adder 0.47 MW 0.4 MW
314181 3NORNECK Adder 0.7 MW 0.59 MW
927041 AC1-191 C Adder 4.27 MW 3.63 MW
927042 AC1-191 E Adder 2.13 MW 1.81 MW
313053 6PAPERMILL Adder 2.96 MW 2.52 MW
316160 AE1-175 E Adder 0.39 MW 0.33 MW
316169 AC1-164 GEN Adder 14.01 MW 11.91 MW
926785 AC1-164_E Adder 6.3 MW 5.35 MW
939612 AE1-191 E Adder 2.64 MW 2.24 MW
315037 1LDYSMT1 50/50 3.85 MW 3.85 MW
315038 1LDYSMT2 50/50 3.9 MW 3.9 MW
316223 AC1-118 C 50/50 0.38 MW 0.38 MW
316337 AD2-073 C 50/50 0.33 MW 0.33 MW
939246 AE1-155 E Adder 6.06 MW 5.15 MW
934146 AD1-041 E Adder 1.65 MW 1.4 MW
944631 AF1-128 C Adder 12.86 MW 10.93 MW
958261 AF2-120 C Adder 4.35 MW 3.7 MW
958262 AF2-120 E Adder 2.9 MW 2.46 MW
939261 AE1-157 C 50/50 10.38 MW 10.38 MW
939262 AE1-157 E 50/50 5.63 MW 5.63 MW
939602 AE1-190 E Adder 0.66 MW 0.56 MW
940551 AE2-041 C Adder 3.25 MW 2.77 MW
943471 AF1-018 C Adder 3.25 MW 2.77 MW
957191 AF2-013 C 50/50 29.13 MW 29.13 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 9.41 MW 9.41 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 5.93 MW 5.93 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 21.13 MW 21.13 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.62 MW 1.62 MW
NY PJM->LTFIMP_NY CLTF 0.74 MW 0.74 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.38 MW 0.38 MW
WEC LTFEXP_WEC->PJM CLTF 0.2 MW 0.2 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.43 MW 2.43 MW
TVA LTFEXP_TVA->PJM CLTF 1.55 MW 1.55 MW
MEC LTFEXP_MEC->PJM CLTF 1.12 MW 1.12 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.94 MW 1.94 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.07 MW 0.07 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 10.31 MW 10.31 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 1.16 MW 1.16 MW

Details for AD2-074 TP-AG1-146 TP 115.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
AD2-074 TP-AG1-146 TP 115.0 kV Ckt 1 line
936590 to 962970 ckt 1
Contingency Name:
Base Case
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 101.16 %
Rating: 203.98 MVA
Rating Type: A
MVA to Mitigate: 206.35 MVA
MW Contribution: 22.31 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
315034 1NORNECKC1 50/50 0.67 MW 0.67 MW
315035 1NORNECKC2 50/50 0.65 MW 0.65 MW
936582 AD2-073 E Adder 0.36 MW 0.31 MW
936591 AD2-074 C 50/50 15.39 MW 15.39 MW
936592 AD2-074 E 50/50 25.11 MW 25.11 MW
943741 AF1-042 C 50/50 8.05 MW 8.05 MW
943742 AF1-042 E 50/50 13.14 MW 13.14 MW
961951 AG1-038 C 50/50 8.9 MW 8.9 MW
961952 AG1-038 E 50/50 12.29 MW 12.29 MW
966661 AG1-536 C 50/50 11.51 MW 11.51 MW
966662 AG1-536 E 50/50 15.47 MW 15.47 MW
316077 AC2-138 C 50/50 0.23 MW 0.23 MW
316078 AC2-138 E 50/50 0.93 MW 0.93 MW
957601 AF2-054 C Adder -1.99 MW -1.69 MW
962861 AG1-135 C 50/50 13.89 MW 13.89 MW
962862 AG1-135 E 50/50 9.26 MW 9.26 MW
963611 AG1-210 C 50/50 0.66 MW 0.66 MW
963612 AG1-210 E 50/50 0.99 MW 0.99 MW
314181 3NORNECK 50/50 0.88 MW 0.88 MW
316404 AE1-155 C 50/50 4.53 MW 4.53 MW
939246 AE1-155 E 50/50 18.64 MW 18.64 MW
958261 AF2-120 C 50/50 13.38 MW 13.38 MW
958262 AF2-120 E 50/50 8.92 MW 8.92 MW
CBM North LTFEXP_CBM-N->PJM CBM 0.06 MW 0.06 MW
G-007A LTFEXP_G-007A->PJM CMTX 0.13 MW 0.13 MW
VTF LTFEXP_VFT->PJM CMTX 0.35 MW 0.35 MW
COTTONWOOD PJM->LTFIMP_COTTONWOOD CLTF 0.14 MW 0.14 MW
HAMLET PJM->LTFIMP_HAMLET CLTF 0.09 MW 0.09 MW
CATAWBA PJM->LTFIMP_CATAWBA CLTF 0.04 MW 0.04 MW
PRAIRIE PJM->LTFIMP_PRAIRIE CLTF 0.13 MW 0.13 MW
TRIMBLE PJM->LTFIMP_TRIMBLE CLTF 0.02 MW 0.02 MW
BlueGrass PJM->LTFIMP_BlueG CLTF 0.07 MW 0.07 MW
MDU PJM->LTFIMP_MDU CLTF 0.01 MW 0.01 MW
LTFEXP_AC1-056 LTFEXP_AC1-056->LTFIMP_AC1-056 CLTF 0.04 MW 0.04 MW
LTFEXP_AC1-131 LTFEXP_AC1-131->LTFIMP_AC1-131 CLTF 0.12 MW 0.12 MW

Details for 6DAHLGREN-AF2-013 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area: DVP
Facility Description:
6DAHLGREN-AF2-013 TP 230.0 kV Ckt 1 line
313810 to 957190 ckt 1
Contingency Name:
DVP_P1-2: LN 574_SRT-S
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
Contingency Type: OP
DC|AC: AC
Final Cycle Loading: 101.1 %
Rating: 559.3 MVA
Rating Type: B
MVA to Mitigate: 565.44 MVA
MW Contribution: 13.04 MW
Impact of Topology Modeling:
Elimination
Bus # Bus Name Type Full MW Contribution GenDeliv MW Contribution
315034 1NORNECKC1 50/50 0.99 MW 0.99 MW
315035 1NORNECKC2 50/50 0.95 MW 0.95 MW
315092 1YORKTN3 Adder 46.63 MW 39.63 MW
925865 AC1-065 E 50/50 11.05 MW 11.05 MW
926472 AC1-118 E 50/50 2.46 MW 2.46 MW
934392 AD1-063 E 50/50 0.72 MW 0.72 MW
936582 AD2-073 E 50/50 1.99 MW 1.99 MW
936591 AD2-074 C 50/50 6.23 MW 6.23 MW
936592 AD2-074 E 50/50 10.17 MW 10.17 MW
943741 AF1-042 C 50/50 3.26 MW 3.26 MW
943742 AF1-042 E 50/50 5.32 MW 5.32 MW
944491 AF1-114 C 50/50 21.14 MW 21.14 MW
944492 AF1-114 E 50/50 29.2 MW 29.2 MW
961951 AG1-038 C 50/50 3.6 MW 3.6 MW
961952 AG1-038 E 50/50 4.98 MW 4.98 MW
966661 AG1-536 C 50/50 6.73 MW 6.73 MW
966662 AG1-536 E 50/50 9.04 MW 9.04 MW
316076 AC2-137 E Adder 0.46 MW 0.39 MW
316077 AC2-138 C 50/50 0.33 MW 0.33 MW
316078 AC2-138 E 50/50 1.37 MW 1.37 MW
316156 AD2-030 C 50/50 0.27 MW 0.27 MW
316157 AD2-030 E 50/50 0.85 MW 0.85 MW
923842 AB2-024 E Adder 1.15 MW 0.98 MW
957601 AF2-054 C 50/50 1.51 MW 1.51 MW
957602 AF2-054 E 50/50 1.01 MW 1.01 MW
962861 AG1-135 C 50/50 7.4 MW 7.4 MW
962862 AG1-135 E 50/50 4.94 MW 4.94 MW
962962 AG1-145 E Adder 0.53 MW 0.45 MW
962971 AG1-146 C 50/50 3.23 MW 3.23 MW
962972 AG1-146 E 50/50 2.15 MW 2.15 MW
962981 AG1-147 C 50/50 7.53 MW 7.53 MW
962982 AG1-147 E 50/50 5.02 MW 5.02 MW
963611 AG1-210 C 50/50 0.98 MW 0.98 MW
963612 AG1-210 E 50/50 1.47 MW 1.47 MW
964211 AG1-282 C 50/50 2.74 MW 2.74 MW
964212 AG1-282 E 50/50 1.82 MW 1.82 MW
957832 AF2-077 E Adder 0.75 MW 0.64 MW
957971 AF2-091 C 50/50 7.19 MW 7.19 MW
957972 AF2-091 E 50/50 9.93 MW 9.93 MW
313811 6ELKO L286 Adder 0.48 MW 0.41 MW
314181 3NORNECK 50/50 1.3 MW 1.3 MW
313053 6PAPERMILL Adder 4.29 MW 3.64 MW
316059 AD1-063 C 50/50 0.17 MW 0.17 MW
316160 AE1-175 E Adder 0.44 MW 0.37 MW
316169 AC1-164 GEN Adder 15.66 MW 13.31 MW
926785 AC1-164_E Adder 7.04 MW 5.98 MW
939611 AE1-191 C 50/50 0.94 MW 0.94 MW
939612 AE1-191 E 50/50 3.91 MW 3.91 MW
316201 AC1-065 C 50/50 1.08 MW 1.08 MW
316223 AC1-118 C 50/50 0.78 MW 0.78 MW
316337 AD2-073 C 50/50 0.65 MW 0.65 MW
316404 AE1-155 C 50/50 2.64 MW 2.64 MW
939246 AE1-155 E 50/50 10.89 MW 10.89 MW
316280 AD1-041 C 50/50 0.59 MW 0.59 MW
934146 AD1-041 E 50/50 2.44 MW 2.44 MW
958261 AF2-120 C 50/50 7.82 MW 7.82 MW
958262 AF2-120 E 50/50 5.21 MW 5.21 MW
939601 AE1-190 C 50/50 0.23 MW 0.23 MW
939602 AE1-190 E 50/50 0.98 MW 0.98 MW
940551 AE2-041 C 50/50 4.78 MW 4.78 MW
943471 AF1-018 C 50/50 4.78 MW 4.78 MW
CBM West 1 LTFEXP_CBM-W1->PJM CBM 8.26 MW 8.26 MW
CBM West 2 LTFEXP_CBM-W2->PJM CBM 5.04 MW 5.04 MW
CBM South 1 LTFEXP_CBM-S1->PJM CBM 0.0 MW 0.0 MW
CBM South 2 LTFEXP_CBM-S2->PJM CBM 17.55 MW 17.55 MW
G-007 PJM->LTFIMP_G-007 CMTX_NF 1.1 MW 1.1 MW
NY PJM->LTFIMP_NY CLTF 0.5 MW 0.5 MW
LGEE LTFEXP_LGEE->PJM CLTF 0.33 MW 0.33 MW
WEC LTFEXP_WEC->PJM CLTF 0.17 MW 0.17 MW
CPLE LTFEXP_CPLE->PJM CLTF 2.02 MW 2.02 MW
TVA LTFEXP_TVA->PJM CLTF 1.31 MW 1.31 MW
MEC LTFEXP_MEC->PJM CLTF 0.96 MW 0.96 MW
LAGN LTFEXP_LAGN->PJM CLTF 1.64 MW 1.64 MW
SIGE LTFEXP_SIGE->PJM CLTF 0.06 MW 0.06 MW
O66 PJM->LTFIMP_O-066 CMTX_NF 7.02 MW 7.02 MW
LTFEXP_AA2-074 LTFEXP_AA2-074->LTFIMP_AA2-074 CLTF 0.96 MW 0.96 MW

Winter Peak Analysis

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Winter Potential Congestion due to Local Energy Deliverability

PJM will start performing Winter Peak analysis in Transition Cycle 2.

Light Load Analysis

Light Load Analysis is Not Required.

Light Load Potential Congestion due to Local Energy Deliverability

Light Load Analysis is Not Required.

Short Circuit Analysis

The Phase III Short circuit analysis was conducted for the following two study scenarios:

 

  • Scenario 1 - TC1 Project Impacts;
  • Scenario 2 - TC1 Topology-Changing Upgrade Impacts;

 

The starting TC1 Phase III short circuit case is an updated Phase II case that accounted for the DPII outcomes (project changes & withdrawals) and other pre-TC1 changes. The starting Phase III case was utilized for the Scenario 1 studies to determine the impact of TC1 projects without modeling any topology-changing upgrades required for TC1. To conduct the Scenario 2 studies, the required topology-changing upgrades from the latest Load Flow & Stability studies were incorporated into the Scenario 1 case and utilized for the Scenario 2 studies to determine the impact of the topology-changing upgrades on the short circuit results from Scenario 1. The result is detailed in the following table:

 

 Short Circuit Analysis

 

 

 

 

 

 

 

Bus Name

Breaker

Interrupting Capability (Amps)

Duty Percent TC1 Phase 3 - Scenario 2 Topology Upgrades (%)

Duty Percent TC1 Phase 3 - Scenario 2 No Topology Upgrades (%)

Duty Percent Difference (%)

Reinforcement

Projected In Service Date (ISD)

BRAMBLETON 230.kV

20102

63000

103.66%

95.89%

7.76%

b3800.405

1/8/2031

BRAMBLETON 230.kV

20602

63000

105.40%

97.28%

8.12%

b3800.405

1/8/2031

BRAMBLETON 230.kV

204502

63000

105.03%

97.32%

7.72%

b3800.405

1/8/2031

BRAMBLETON 230.kV

209402

63000

105.07%

97.35%

7.72%

b3800.405

1/8/2031

BRAMBLETON 230.kV

217202

63000

103.17%

95.89%

7.28%

b4000.103

1/8/2031

BRAMBLETON 230.kV

218302

63000

109.45%

101.02%

8.43%

b3689.2

3/31/2027

BRAMBLETON 230.kV

201T2045

63000

105.03%

97.32%

7.72%

b3800.405

1/8/2031

BRAMBLETON 230.kV

206T2094

63000

105.40%

97.35%

8.05%

b3800.405

1/8/2031

BRAMBLETON 230.kV

2172T2183

63000

107.20%

99.03%

8.17%

b4000.103

1/8/2031

BRAMBLETON 230.kV

H302

63000

109.45%

101.02%

8.43%

b3689.2

3/31/2027

BRAMBLETON 230.kV

H402

63000

109.45%

101.02%

8.43%

b3689.2

3/31/2027

BRAMBLETON 230.kV

L102

63000

103.17%

95.89%

7.28%

b4000.103

6/1/2028

BRAMBLETON 230.kV

SC102

63000

109.45%

101.02%

8.43%

b3689.2

3/31/2027

CARSON 230.kV

23872

40000

100.25%

98.16%

2.09%

b4000.108

6/12/2029

CARSON 230.kV

200272

40000

100.40%

98.51%

1.88%

b3854.1

6/1/2025

GAINESVILLE 230.kV

216192

40000

126.89%

104.16%

22.73%

b3800.406

3/15/2030

IDYLWOOD 230.kV

20212

40000

103.71%

100.35%

3.35%

b1696

12/30/2026

IDYLWOOD 230.kV

20712

40000

101.95%

98.56%

3.39%

b1696

12/30/2026

LADYSMITH 500.kV

568T575

40000

103.90%

88.38%

15.52%

b4000.354

11/14/2029

LADYSMITH 500.kV

574T581

40000

112.03%

87.44%

24.59%

b4000.115

11/27/2031

LADYSMITH S1 230.kV

GT172

40000

101.24%

94.15%

7.09%

b4000.114

7/18/2030

LADYSMITH S1 230.kV

GT272

40000

101.24%

94.15%

7.09%

b4000.114

7/18/2030

LADYSMITH S1 230.kV

GT372

40000

101.04%

93.94%

7.10%

b4000.114

7/18/2030

LADYSMITH S1 230.kV

GT472

40000

101.04%

93.94%

7.10%

b4000.114

7/18/2030

LADYSMITH S1 230.kV

GT572

40000

101.03%

93.93%

7.10%

b4000.114

7/18/2030

LADYSMITH S1 230.kV

SX1272

40000

105.46%

98.43%

7.04%

b3853.1

6/1/2025

LADYSMITH S1 230.kV

SX3472

40000

105.46%

98.43%

7.04%

b3853.1

6/1/2025

LOUDOUN 230.kV

200852

63000

103.92%

95.27%

8.65%

b3800.334

10/5/2031

LOUDOUN 230.kV

203052

63000

102.57%

95.02%

7.56%

b3800.334

10/5/2031

LOUDOUN 230.kV

204552

63000

101.56%

93.15%

8.41%

b3800.407

10/5/2031

LOUDOUN 230.kV

211752

63000

107.05%

98.13%

8.92%

b3800.235

10/5/2031

LOUDOUN 230.kV

212352

63000

107.59%

98.67%

8.92%

b3800.235

10/5/2031

LOUDOUN 230.kV

214052

63000

104.61%

96.50%

8.11%

b3800.334

10/5/2031

LOUDOUN 230.kV

217352

63000

101.82%

93.34%

8.47%

b3800.407

10/5/2031

LOUDOUN 230.kV

2008T2045

63000

103.92%

95.27%

8.65%

b3800.235

10/5/2031

LOUDOUN 230.kV

2030T2117

63000

107.05%

98.13%

8.92%

b3800.235

10/5/2031

LOUDOUN 230.kV

2094T2140

63000

104.61%

96.50%

8.11%

b3800.334

10/5/2031

LOUDOUN 230.kV

2123T2173

63000

107.59%

98.67%

8.92%

b3800.235

10/5/2031

LOUDOUN CAP 230.kV

SC352

50000

100.12%

93.62%

6.50%

b4000.119

10/31/2030

NORTH ANNA 500.kV

57502

40000

113.86%

95.53%

18.33%

b4000.128

10/13/2032

NORTH ANNA 500.kV

G102-1

40000

113.86%

95.53%

18.33%

b4000.128

10/13/2032

NORTH ANNA 500.kV

G102-2

40000

113.48%

95.12%

18.36%

b4000.128

10/13/2032

NORTH ANNA 500.kV

G202

40000

113.86%

95.53%

18.33%

b4000.128

10/13/2032

NORTH ANNA 500.kV

G2T575

40000

106.24%

87.81%

18.44%

b4000.128

10/13/2032

NORTH ANNA 500.kV

XT573

40000

113.86%

95.53%

18.33%

b4000.128

10/13/2032

OX 230.kV

22042

63000

100.37%

96.12%

4.24%

b3800.408

4/21/1931

OX 230.kV

220T2063

63000

100.37%

96.12%

4.24%

b3800.408

4/21/1931

OX 500.kV

56142

40000

105.23%

98.27%

6.96%

b3800.335

12/15/1931

OX 500.kV

H1T539

40000

104.44%

97.54%

6.90%

b3800.236

1/5/2029

OX 500.kV

H2T539

40000

104.44%

97.54%

6.90%

b3800.236

1/5/2029

OX L142 230.kV

L142

50000

108.05%

103.82%

4.22%

s2609.6

12/15/2030

PLEASANTVIEW 230.kV

L3T203

50000

108.44%

103.89%

4.56%

s2609.9

12/15/2030

PLEASANTVIEW 230.kV

L3T2180

50000

108.44%

103.89%

4.56%

s2609.9

12/15/2030

REMINGTON CT 230.kV

211462

40000

102.56%

95.98%

6.58%

b4000.134

1/9/2031

REMINGTON S1 230.kV

GT162

40000

101.45%

95.39%

6.06%

b4000.134

1/9/2031

REMINGTON S1 230.kV

GT262

40000

101.45%

95.39%

6.06%

b4000.134

1/9/2031

REMINGTON S2 230.kV

GT362

40000

101.45%

95.39%

6.06%

b4000.134

1/9/2031

REMINGTON S2 230.kV

GT462

40000

101.45%

95.39%

6.06%

b4000.134

1/9/2031

YADKIN 2&4 230.kV

210512

40000

101.22%

99.46%

1.76%

n6588

12/1/2028

 

 

Stability Analysis

Analysis Complete - Issues Found

Executive Summary for Dynamic Stability Analysis using PSSE

New Service Requests (projects) in PJM Transition Cycle 1 Cluster 32 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 32 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 32 projects will meet the dynamics requirements of the NERC, Dominion Energy, and PJM reliability standards.

 

 Table 1: Transition Cycle 1 Cluster 32 Projects

Cluster

Project

Fuel Type

Transmission Owner

MFO

(MW)

MWE

(MW)

MWC

(MW)

Point of Interconnection

32

AF2-120

Solar

Dominion

62

62

37.2

Garner – Northern Neck 115 kV

AG1-135

Solar

Dominion

60

60

36

Garner – Lancaster

115 kV

AG1-146

Solar

Dominion

30

30

18

Garner – Lancaster

115 kV

AG1-147

Solar

Dominion

100

70

42

Garner – Lancaster

115 kV

AG1-536

Battery

Dominion

75

75

32

Garner – Northern Neck 115 kV

 

The load flow case finalized for Phase 2 was used as a starting point and was updated based on latest Cluster 32 data, Dominion Energy recommended transmission changes and withdrawn generation. Projects in vicinity of Cluster 32 have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer. The dynamic models for Cluster 32 projects were updated based on the latest DP2 data and include any tuning adjustments recommended during Phase 2.

 

Cluster 32 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. 116 contingencies were studied, each with a 30 second simulation time period. The studied contingencies included:

 

  • Steady-state operation (30 seconds)
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults with delayed clearing at remote end
  • Single-phase faults with loss of multiple-circuit tower line.

 

The contingencies were updated based on topology changes due to any Dominion Energy recommended transmission changes or generation withdrawals.

 

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

Instability was observed for certain contingencies resulting in the outage of the Northern Neck and AE1-155 Tap 115 kV line. The instability was mitigated by adding in a second 115 kV line from Northern Neck to AE1-155 Tap (Moon Corner). This new line would require additional breakers at Moon Corner and Northern Neck Both lines should not share a common breaker such that a breaker failure or stuck breaker could take out both Northern Neck – AE1-155 115 kV lines. Both lines should not share a common tower or structure such that a tower or structure failure could take out both lines.

 

A load flow analysis network update that reconductors the Northern Neck to Rappahannock 115 kV was considered and was not required to meet the evaluation criteria for the CL32 Stability Analysis.

 

With the addition of the second 115 kV line from Northern Neck to AE1-155 Tap, the study found that the following generators protection trips occurred. The relay pick-up settings were increased to allow the generators to ride through and should be confirmed with the generator owner.

 

  • AE2-041 tripped for voltages below 0.65 p.u. for more than 0.35 seconds and the relay pick-up time was increased to 0.4334 seconds to able to ride through the faults.
  • AF1-018 tripped for voltages below 0.65 p.u. for more than 0.35 seconds and the relay pick-up time was increased to 0.4334 seconds to able to ride through the faults.
  • AG1-038 tripped for voltages above 1.20 p.u. for more than 0.045 seconds and the relay pick-up time was increased to 0.0501 seconds to able to ride through the faults.

 

Reactive power for AF1-114 and AF2-091 does not appear to settle within the 30 seconds simulation for some contingencies. This did not violate any criteria nor create instability. AF1-114 and AF2-091 currently utilize a 4% voltage reactive droop. If a faster reactive power settling is desired in the future, then the model can be tuned to improve the reactive recovery later.

 

With the new 115 kV transmission line mitigation identified above, the results of the contingencies tested on the RTEP 2027 summer peak case found:

 

  • Cluster 32 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  • The system with Cluster 32 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for inter area modes and 4% for local modes.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities

 

No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

Executive Summary for Dynamic Stability Analysis using PSCAD/EMT

 

Model Quality Testing Report

 

PSCAD model for Queue project AF2-120, AG1-135, AG1-146/147 and AG1-536 was developed and tested individually to ensure the model was in compliance with the PJM requirements. Test summary and result of test been summarized below in table 2. it is confirmed that PSCAD model was set up properly and satisfied the PJM requirement.

 

Table 2. MQT Result for each project

 

Test

Status

Flat Start Test 

Pass 

Voltage Step-Down 

Pass 

Voltage Step-Up 

Pass 

Frequency Step-Down, No Headroom

Pass 

Frequency Step-Down, Headroom

Pass 

Frequency Step-Up, Headroom 

Pass 

HVRT Leading

Pass 

HVRT Lagging

Pass 

LVRT Leading

Pass 

LVRT Lagging

Pass 

System Strength Test 

Pass 

Voltage Ride Through

Pass 

Phase Angle Step-Down 

Pass 

Phase Angle Step-Up 

Pass 

 

Weak Grid Assessment

 

This Weak Grid Assessment evaluates five projects from PJM Transition Cycle 1 (TC1) Cluster 32 for risk of voltage instability due to weak grid conditions in an EMT simulation environment.  The five projects, AF2-120, AG1-135, AG1-146, AG1-147, and AG1-536, were identified in the Cluster Study as having risk of undamped oscillations in multiple contingency cases, indicating system instability after dynamic simulation analysis in PSS/E. A network upgrade, a new second 115 kV transmission line from Northern Neck to AE1-155 Tap, was recommended along with evaluation using detailed models in an EMT simulation.

This assessment, completed by INS Engineering, aims to evaluate the risk of weak grid instability and verify the effectiveness of the recommended network upgrade in EMT simulation.  A summary description of each project is listed below:

 

 

Table 3. Summary Description of TC1 Cluster 32 Projects

 

 

 

 

Project Name

Project Type

Project Size (MW)

POI

POI Bus Number

AF2-120 Cerulean Solar

PV

62

Garner – Northern Neck 115 kV

939240

AG1-135 Moon Corner

PV

60

Garner – Lancaster

115 kV

962860

AG1-146/AG1-147 Merry Point 1 and 2 Solar

PV

100

Garner – Lancaster

115 kV

962970

AG1-536 Mulberry

BESS

75

Garner – Northern Neck 115 kV

939240

 

First, the individual project PSCAD models were evaluated for data consistency and model performance as part of the standard Model Quality Tests process, model updates being made where needed.  INS confirmed that the PSCAD models were set up properly and satisfied the requirements of PJM. After satisfactory configuration and performance of the individual project models were obtained, the models were integrated into a translated reduced network in PSCAD to create an overall detailed system model. 

 

A representative contingency case from the Cluster Study, considered effectively the worst case in terms of risk for weak grid instability, was then simulated in the PSCAD detailed system model. For Cluster 32, the following contingency case was chosen.

 

  • Fault ID P1.03: Fault at AE1-155 Tap 115 kV on AE1-155 Tap – Northern Neck 115 kV circuit #1059. Fault cleared with loss of Northen Neck 115/34.5 kV Transformer #1

 

Simulation results in PSCAD are summarized below.  In Case 1a with the PSCAD detailed system model, weak grid oscillations and unstable recovery are observed without the network upgrade. With the network upgrade added in Case 1b, stable recovery is observed due to sufficient grid strength. These results are consistent with the results in the Cluster Study.

 

Table 4. Summary of cases tested in PSCAD system study

 

 

 

Case ID

Fault Description

Cluster Study Result [1]

PSCAD Study Result

Case 1a

P1.03, without network upgrade

Unstable

Unstable

Case 1b

P1.03, with network upgrade

Stable

Stable

Case 2a

P1.03, without network upgrade, modified PPC tuning

-

Stable*

* Details in Appendix B. Although a stable response was observed in this case, a detailed tuning evaluation over multiple operating conditions would be needed to verify robustness of the modified tuning.

 

As a potential alternative solution, PPC parameter were tuned to be more appropriate for weak grid conditions and this configuration was evaluated in base case P1.03, without the network upgrade – Case 2a. A stable response was observed in Case 2a, however, a detailed tuning evaluation over multiple operating conditions would be needed to verify robustness of this modified tuning.  As such, the modified tuning results in Appendix B should be considered for information only.

Based on the simulation results described above, the results of this assessment show stable recovery in the worst-case contingency when the network upgrade is included.  These results support the conclusion from the Cluster Study that the proposed network upgrade mitigates potential weak grid instability issues.

Reactive Power Analysis

AF2-120 met the 0.95 lagging and leading power factor requirements measured at the high side of the main transformer.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project ID Project Name Status
AA1-063A Carolina–Seaboard 115kV In Service
AA1-065 Earleys 230kV In Service
AA1-139 Hickory-Shawboro 230kV In Service
AA1-145 Four Rivers 230kV In Service
AA2-088 Boykins-Handsome 115kV In Service
AA2-178 Mackeys 230kV In Service
AB1-027 Old Church 34.5 KV In Service
AB2-022 Elizabeth City 34.5kV In Service
AB2-024 Correctional 34.5kV In Service
AB2-025 Sapony 34.5kV In Service
AB2-099 Ahoskie 34.5kV In Service
AB2-100 Clubhouse-Lakeview 230kV In Service
AB2-134 Hopewell-Surry 230kV In Service
AB2-161 Waverly #2 DP 115kV In Service
AB2-174 Emporia-Trego 115kV In Service
AB2-190 Hopewell-Surry 230kV In Service
AC1-027 Pendleton 34.5kV In Service
AC1-065 Harmony Village-Shackleford 115kV Under Construction
AC1-098 Dawson-South Justice 115kV Under Construction
AC1-112 Old Church 34.5kV In Service
AC1-118 Westmoreland 34.5kV In Service
AC1-147 Grassfield 34.5kV In Service
AC1-161 Septa 500kV In Service
AC1-164 Chickahominy 230kV Partially in Service - Under Construction
AC1-191 Elmont 115kV Engineering & Procurement
AC1-216 Hopewell-Surry 230kV In Service
AC2-012 Grassfield-Great Bridge 115kV In Service
AC2-079 Ivor-Oak Ridge 115kV Suspended
AC2-137 Elko 34.5kV In Service
AC2-138 Northern Neck 34.5kV In Service
AC2-141 Septa 500kV Engineering & Procurement
AD1-022 Cashie-Trowbridge 230 kV Engineering & Procurement
AD1-025 Hopewell-Surry 230 kV Under Construction
AD1-033 Fentress-Landstown 230 kV In Service
AD1-041 Harmony Village-Shackleford 115 kV In Service
AD1-063 Harmony Village 34.5 kV In Service
AD1-074 Trowbridge 230 kV Engineering & Procurement
AD1-075 Trowbridge 230 kV Engineering & Procurement
AD1-076 Trowbridge 230 kV Engineering & Procurement
AD1-082 Bakers Pond-Ivor 115kV In Service
AD1-105 Kings Dominion DP 115 kV Under Construction
AD1-144 Kings Fork 34.5 kV In Service
AD1-151 Hopewell-Surry 230 kV Suspended
AD2-030 Wan 34.5 kV In Service
AD2-073 Sanders DP 230 kV In Service
AD2-074 Garner DP-Lancaster 115 kV Engineering & Procurement
AD2-085 Myrtle-Windsor DP 115kV Engineering & Procurement
AE1-072 Shawboro-Sligo 230 kV Engineering & Procurement
AE1-074 Winterpock 34.5 kV Under Construction
AE1-103 Holland-Union Camp 115 kV Under Construction
AE1-149 Disputanta-Poe 115 kV Suspended
AE1-155 Garner-Northern Neck 115 kV In Service
AE1-157 Ladysmith CT-St. Johns 230 kV Suspended
AE1-162 Smithfield 34.5 kV In Service
AE1-173 Carson-Suffolk 500 kV Under Construction
AE1-175 Light Foot 34.5 kV In Service
AE1-190 Harmony Village-Shackleford 115 kV Partially in Service - Under Construction
AE1-191 Harmony Village-Shackleford 115 kV Partially in Service - Under Construction
AE2-027 Harrowgate-Locks 115kV Suspended
AE2-033 Clubhouse-Sapony 230 kV Suspended
AE2-034 Mackeys 230 kV Partially in Service - Under Construction
AE2-040 Sapony 34.5 kV Under Construction
AE2-041 Harmony Village 230 kV Engineering & Procurement
AE2-051 Carson-Septa 500 kV Engineering & Procurement
AE2-104 Suffolk 115 kV Suspended
AE2-156 Yadkin 115 kV Active
AE2-212 Harrowgate 34 kV Engineering & Procurement
AE2-247 Myrtle-Windsor 115 kV Engineering & Procurement
AE2-253 Hickory-Moyock 230 kV In Service
AE2-346 Ahoskie 34.5 kV In Service
AF1-017 Myrtle-Windsor 115 kV Engineering & Procurement
AF1-018 Harmony Village 230 kV Engineering & Procurement
AF1-032 Suffolk 34.5 kV In Service
AF1-042 Garner DP-Lancaster 115 kV Engineering & Procurement
AF1-114 Oak Grove-Dahlgren 230 kV Engineering & Procurement
AF1-123 Oceana 230 kV Active
AF1-124 Oceana 230 kV Active
AF1-125 Oceana 230 kV Active
AF1-128 Chesterfield 230 kV Active
AF1-129 Chesterfield 230 kV Engineering & Procurement
AF1-291 Tyler 34.5 kV Engineering & Procurement
AF1-292 Fields 34.5kV Engineering & Procurement
AF2-013 Arnold's Corner-Dahlgren 230 kV Engineering & Procurement
AF2-035 St. Johns 115 kV Active
AF2-043 Suffolk 34.5 kV In Service
AF2-046 Tunis-Mapleton 115 kV Active
AF2-054 Wan 34.5 kV In Service
AF2-077 White Marsh 34.5 kV In Service
AF2-081 Moyock 230 kV Active
AF2-091 Oak Grove-Dahlgren 230 kV Engineering & Procurement
AF2-110 Suffolk 115 kV Suspended
AF2-299 Fields 34.5 kV Active
AG1-008 Tunis-Mapleton 115 kV Active
AG1-037 Ahoskie 34.5 kV Engineering & Procurement
AG1-038 Garner DP-Lancaster 115 kV Engineering & Procurement
AG1-082 Ahoskie 34.5 kV Active
AG1-135 Garner-Lancaster 115 kV Active
AG1-145 Lightfoot 34.5 kV In Service
AG1-146 Garner DP-Lancaster 115 kV Active
AG1-147 Garner DP-Lancaster 115 kV Active
AG1-154 Ladysmith CT 230 kV Active
AG1-210 Northern Neck 34.5 kV Engineering & Procurement
AG1-282 Dunnsville 34.5 kV Engineering & Procurement
AG1-393 Fort Pickett DP 34.5 kV Active
AG1-394 Boykins 34.5 kV Active
AG1-532 Fields 34.5 kV Engineering & Procurement
AG1-536 Garner-Northern Neck 115 kV Active
AG1-558 Buckner 34.5 kV Engineering & Procurement
AG1-559 Caroline Pines 22 kV Engineering & Procurement
V4-068 Murphy's 34.5kV In Service
W1-029 Winfall 230kV In Service
Y1-086 Morgans Corner In Service
Z1-036 WinFall-Chowan 230kV In Service
Z1-068 Birdneck 34.5kV In Service
Z2-027 Pasquotank 34.5kV In Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO) No Impact
New York Independent System Operator (NYISO) No Impact
Tennessee Valley Authority (TVA) No Impact
Louisville Gas & Electric (LG&E) No Impact
Duke Energy Carolinas (DUKE) No Impact
Duke Energy Progress – East (CPLE) No Impact
Duke Energy Progress – West (CPLW) No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 312.A.1.b and as outlined in PJM Manual 14H, Section 13, in Phase III of the Cycle, PJM coordinates with the Affected System Operators to conduct any studies required to determine the impact of the New Service Request on any Affected System and will include the Affected System Study results in Phase III System Impact Study, if available from the Affected System Operator.

If your project required an Affected System Study, the results are shown below from the Affected System Operator.

For more details, please refer to your Affected System Study report by the Affected System Operator. If the Affected System Operator identified the need for a system reinforcement on their system due to their planning criteria, Project Developer must follow the Affected System Operator Tariff for construction of the network upgrade. PJM will list any required network upgrades identified by the Affected System Operator in the PJM Project Developer’s GIA under Schedule F.

Affected System network upgrade costs are included in the Adverse Study Impact calculation for DP3. See the Adverse Test Eligibility section of this Phase III SIS report.

Midcontinent Independent System Operator, Inc. (MISO) Not required
New York Independent System Operator (NYISO) Not required
Tennessee Valley Authority (TVA) Not required
Louisville Gas & Electric (LG&E) Not required
Duke Energy Carolinas (DUKE) Not required
Duke Energy Progress – East (CPLE) Not required
Duke Energy Progress – West (CPLW) Not required

System Reinforcements

Based on the Phase III analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AF2-120 System Reinforcements:
TO RTEP ID Title Category Allocated Cost ($USD) Facilities Study
Dominion n9651.0 Wreck and rebuild 10.05 miles of 115kV transmission line 1059 between Northern Neck and Moon Corner with (1) 768.2 ACSS/TW (20/7) "MAUMEE" conductor and replace line lead at Moon Corner. Cost Allocated $5,944,669
Dominion n9138.0 Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work. Cost Allocated $5,003,236
Dominion n9250.0 Construct a new 22.59 mile line between Carson and Rawlings Substations. Cost Allocated $4,895,086
Dominion n9380.0 Replace existing Ladysmith 230/500 kV transformer 1 with four (4) 480 MVA single phase transformers. Cost Allocated $4,123,504
Dominion n9630.0 Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers. Cost Allocated $4,027,998
Dominion n8492 Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line. Cost Allocated $3,609,464
Dominion n9267.0 Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner. Cost Allocated $2,058,830
Dominion n7549 Replace Northern Neck 115/230 kV transformer #4 with a 224 MVA (260/271/295 MVA). Cost Allocated $1,850,537
Dominion n7553 Replace Northern Neck 115/230 kV transformer #6 with a 224 MVA (260/271/295 MVA). Cost Allocated $1,829,790
Dominion n9259.0 Install two 230 kV gas insulated switchgear ("GIS") bus ties for the Coastal Virginia Offshore Wind ("CVOW") project. Cost Allocated $1,139,261
Dominion n7541 Add a third 224 MVA 230/115 kV transformer at Earleys Substation and supporting equipment. Cost Allocated $1,025,559
Dominion n8492.1 Two Breaker Additions at Fentress Substation. Cost Allocated $897,990
Dominion n9207.0 Replace 6ELMONT 230 kV to 8ELMONT 500 kV circuit 1 with larger transformer (3-480 MVA single phase transformer). Cost Allocated $834,462
Dominion n8492.2 Expand Yadkin Substation to accommodate the new 500 kV line. Cost Allocated $729,667
Dominion n9652.0 Replace Wave Trap at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner Cost Allocated $222,485
Dominion n9653.0 Replace Line Switch at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner Cost Allocated $94,842
Dominion n6588 Replace 230 kV breaker 210512 at Yadkin 230 kV with a 63 kA breaker. Cost Allocated $77,663
Dominion b4000.357 Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat. Contingent $0 N/A
Dominion b4000.356 Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section). Contingent $0 N/A
Dominion b4000.355 Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section). Contingent $0 N/A
Dominion b4000.352 Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point. Contingent $0 N/A
Dominion b4000.351 Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken. Contingent $0 N/A
Dominion b4000.350 Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken. Contingent $0 N/A
Dominion b4000.349 Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken. Contingent $0 N/A
Dominion b4000.348 Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. Contingent $0 N/A
Dominion b4000.346 Cut-in 500kV line from Kraken substation into Yeat substation Contingent $0 N/A
Dominion b4000.345 Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA. Contingent $0 N/A
Dominion b4000.344 Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA. Contingent $0 N/A
Dominion b4000.342 Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill. Contingent $0 N/A
Dominion b4000.341 Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site. Contingent $0 N/A
Dominion b4000.325 Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA. Contingent $0 N/A
Dominion b3689.2 Replace 230 kV breakers SC102, H302, H402 and 218302 at Brambleton substation with 80 kA Contingent $0 N/A
Dominion b4000.103 Brambleton Sub 230kV - replace 63kA breakers 217202, 2172T2183, L102, L202 with 80kA Contingent $0 N/A
Dominion b3800.405 Replace Brambleton 230 kV breakers 20102, 20602, 204502, 209402, 201T2045, 206T2094 with breakers rated 80 kA. Contingent $0 N/A
Dominion b3854.1 Replace over duty Carson 230kV circuit breakers 200272 and 24972-3 with an interrupting rating of 63 kA Contingent $0 N/A
Dominion b4000.108 Carson Sub 230kV - replace 40kA breaker 23872 with 63kA Contingent $0 N/A
Dominion b4000.326 At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith. Contingent $0 N/A
Dominion b4000.327 Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme. Contingent $0 N/A
Dominion b3800.406 Replace Gainesville 230 kV breaker 216192 with a breaker rated 80 kA. Contingent $0 N/A
Dominion b4000.115 Ladysmith Sub 500kV - replace 40kA breaker 574T581 with 63kA Contingent $0 N/A
Dominion b4000.354 Ladysmith substation breakers replacement: 574T575 and 568T581 Contingent $0 N/A
Dominion b3853.1 Replace over duty Ladysmith CT 230kV circuit breakers SX1272 and SX3472 with an interrupting rating of 63 kA Contingent $0 N/A
Dominion b4000.114 Ladysmith S1 Sub 230kV - replace 40kA breakers 25672, 209072, 256T2090, GT172, GT272, GT372, GT472, GT572 with 63kA Contingent $0 N/A
Dominion b3800.235 Replace 5 overdutied 230kV breakers at Loudoun substation with 80kA breakers Contingent $0 N/A
Dominion b3800.334 Replace four (4) overdutied 230 kV breakers at Loudoun Substation with 80 kA breakers. Contingent $0 N/A
Dominion b3800.407 Replace Loudoun 230 kV breakers 204552 and 217352 with breakers rated 80 kA. Contingent $0 N/A
Dominion b4000.119 Loudoun Cap Substation 230kV - replace 50 kA breaker SC352 with 63 kA. Contingent $0 N/A
Dominion b4000.128 North Anna Substation 500 kV - replace 40 kA breakers 57502, G102-1, G102-2, G202, G2T575, and XT573 with 63 kA. Contingent $0 N/A
Dominion b3800.408 Replace Ox 230 kV breakers 22042, 24342, 24842, 220T2063, 243T2097, 248T2013, and H342 with breakers rated 80 kA. Contingent $0 N/A
Dominion s2609.6 Upgrade two (2) 230 kV breakers 201342 and L142 from 50 kA to 63 kA at Ox Substation due to an insufficient breaker duty rating with the expansion in place. Contingent $0 N/A
Dominion s2609.9 Upgrade 230 kV Pleasant View breakers L3T203 and L3T2180 from 50 kA to 80 kA. Contingent $0 N/A
Dominion b4000.134 Remington Substation 230 kV - replace 40 kA and 50 kA breakers 211462, GT162, GT262, GT362, GT462, 2077T2086, 208662, H962, and H9T299 with 63 kA. Contingent $0 N/A
Dominion b1696 Install a breaker and a half scheme with a minimum of eight 230 kV breakers for five existing lines at Idylwood 230 kV: 20212 and 20712 Contingent $0 N/A
Dominion b3800.236 Replace 2 overdutied 500kV breakers at Ox Substation with 63kA breakers. Contingent $0 N/A
Dominion s3047.2 Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation. Contingent $0 N/A
Dominion b3800.312 Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. Contingent $0 N/A
Dominion b3800.313 Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW. Contingent $0 N/A
Dominion b3800.356 Build a new 500 kV line from Vint Hill to Wishing Star. Contingent $0 N/A
Dominion b3800.357 Build a new 500 kV line from Morrisville to Vint Hill. Contingent $0 N/A
Dominion b3800.354 Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590. Contingent $0 N/A
Dominion b3800.335 Replace 1 overdutied 500kV breaker at Ox Substation with a 63kA breaker Contingent $0 N/A
Grand Total: $38,365,043

PJM evaluated the impact of topology changing reinforcements to mitigate the impacts driven by New Service Requests. PJM determined which reinforcements were eliminated as a result of modeling the topology changing reinforcements. PJM then grouped the topology changing and eliminated reinforcements by region and computed a discount factor to apply to reinforcements to reduce the cost of all these reinforcements down to the cost of contstructing only the topology changing reinforcements. For additional details, please click the icon below

Regional Topology Upgrade Conversion

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Discounted Total Cost ($USD)
$18,687,686
Allocated Cost ($USD)
$3,851,263
Time Estimate
45 to 46 Months

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Facility Contingency
3NORNECK-AE1-155 TAP 115.0 kV Ckt 1 line (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 122.0 MW 20.6% $3,851,263
AG1-135 120.0 MW 20.3% $3,788,117
AG1-146 60.0 MW 10.1% $1,894,058
AG1-147 140.0 MW 23.6% $4,419,259
AG1-536 150.0 MW 25.3% $4,734,988
System Reinforcement: n9267.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9267.0 / TC1-PH2-DOM-067
Title
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner.
Description
Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner substations with single (1) 768.2 ACSS/TW “Maumee” at 250 degrees C. This new line will be on separate transmission towers from the existing Northern Neck and Moon Corner line 1059. Station expansion is required at Northern Neck and Moon Corner to accommodate the new line.
Total Cost ($USD)
$45,730,074
Allocated Cost ($USD)
$2,058,830
Time Estimate
45 to 46 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
Project Percent Allocation Allocated Cost ($USD)
AE1-148 0.5656 % $258,644
AE2-185 0.0346 % $15,813
AE2-187 0.0300 % $13,704
AE2-283 0.0305 % $13,968
AE2-291 0.5378 % $245,950
AF1-123 10.2087 % $4,668,467
AF1-124 10.2455 % $4,685,295
AF1-125 10.0507 % $4,596,198
AF1-294 0.4085 % $186,804
AF2-035 0.2624 % $120,013
AF2-042 28.1786 % $12,886,086
AF2-046 2.8849 % $1,319,269
AF2-115 0.2488 % $113,776
AF2-120 4.5021 % $2,058,830
AF2-222 3.8795 % $1,774,085
AF2-297 0.7165 % $327,665
AG1-008 2.8849 % $1,319,269
AG1-021 0.1990 % $91,024
AG1-082 0.1873 % $85,638
AG1-098 1.6029 % $733,002
AG1-105 0.6819 % $311,830
AG1-124 1.0619 % $485,606
AG1-135 4.4165 % $2,019,652
AG1-146 2.1236 % $971,126
AG1-147 4.9550 % $2,265,905
AG1-154 0.1382 % $63,208
AG1-166 0.1304 % $59,625
AG1-167 0.0978 % $44,721
AG1-168 0.0978 % $44,721
AG1-285 2.7978 % $1,279,453
AG1-342 0.0630 % $28,810
AG1-494 0.8172 % $373,725
AG1-536 4.9600 % $2,268,192

System Reinforcement: n6588
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
n6588 / TC1-PH2-DOM-034
Title
Replace 230 kV breaker 210512 at Yadkin 230 kV with a 63 kA breaker.
Description
Replace 230kV breaker 210512 at Yadkin 230 kV with a 63 kA breaker.
Total Cost ($USD)
$1,725,040
Discounted Total Cost ($USD)
$1,725,040
Allocated Cost ($USD)
$77,663
Time Estimate
Dec 01 2028

Contributor

Cost Allocation
Project Percent Allocation Allocated Cost ($USD)
AE1-148 0.57% $9,757
AE2-185 0.03% $597
AE2-187 0.03% $518
AE2-283 0.03% $526
AE2-291 0.54% $9,277
AF1-123 10.21% $176,104
AF1-124 10.25% $176,739
AF1-125 10.05% $173,379
AF1-294 0.41% $7,047
AF2-035 0.26% $4,527
AF2-042 28.18% $486,093
AF2-046 2.88% $49,766
AF2-115 0.25% $4,292
AF2-120 4.50% $77,663
AF2-222 3.88% $66,923
AF2-297 0.72% $12,360
AG1-008 2.88% $49,766
AG1-021 0.20% $3,433
AG1-082 0.19% $3,231
AG1-098 1.60% $27,651
AG1-105 0.68% $11,763
AG1-124 1.06% $18,318
AG1-135 4.42% $76,186
AG1-146 2.12% $36,633
AG1-147 4.96% $85,476
AG1-154 0.14% $2,384
AG1-166 0.13% $2,249
AG1-167 0.10% $1,687
AG1-168 0.10% $1,687
AG1-285 2.80% $48,263
AG1-342 0.06% $1,087
AG1-494 0.82% $14,097
AG1-536 4.96% $85,562

System Reinforcement: n7576
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7576 / dom-281
Title
Rebuild 7.91 miles of 230 kV Line 2083 from Birchwood to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor 250 degrees C.
Description
Rebuild 7.91 miles of 230 kV Line 2083 from Birchwood to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor 250 degrees C.
Total Cost ($USD)
$35,735,843
Discounted Total Cost ($USD)
$14,603,524
Allocated Cost ($USD)
$3,222,678
Time Estimate
43 to 44 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

Facility Contingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 line (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
13.0 MW 22.1% $3,222,678
AG1-135 12.3 MW 20.9% $3,050,630
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
5.4 MW 9.1% $1,329,660
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
12.6 MW 21.2% $3,102,294
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
15.8 MW 26.7% $3,898,261

System Reinforcement: n9222.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9222.0 / TC1-PH2-DOM-036
Title
Wreck and Rebuild 6.95 miles of 115 kV Line 89 from White Marsh to Hayes with (1) 768 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C. Replace Line Lead at Hayes.
Description
Wreck and Rebuild 6.95 miles of 115 kV Line 89 from White Marsh to Hayes with (1) 768 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C. Replace Line Lead at Hayes.
Total Cost ($USD)
$42,356,870
Discounted Total Cost ($USD)
$17,309,219
Allocated Cost ($USD)
$3,080,189
Time Estimate
43 to 44 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

Facility Contingency
3WHITEMARSH-3HAYES89 115.0 kV Ckt 1 line (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
15.4 MW 17.8% $3,080,189
AG1-135 16.0 MW 18.4% $3,189,376
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
11.0 MW 12.7% $2,194,118
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
25.6 MW 29.6% $5,119,609
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
18.7 MW 21.5% $3,725,929

System Reinforcement: n7575
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7575 / dom-286
Title
Rebuild 6.46 mi miles of 2-545.6 ACAR (15/7) 90 MOT 230 kV Line 2083 from Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C.
Description
Rebuild 6.46 mi miles of 2-545.6 ACAR (15/7) 90 MOT 230 kV Line 2083 from Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C.
Total Cost ($USD)
$33,559,690
Discounted Total Cost ($USD)
$13,714,234
Allocated Cost ($USD)
$3,026,431
Time Estimate
43 to 44 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

Facility Contingency
6FREDBRG-6FINES 230.0 kV Ckt 1 line (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
13.0 MW 22.1% $3,026,431
AG1-135 12.3 MW 20.9% $2,864,861
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
5.4 MW 9.1% $1,248,690
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
12.6 MW 21.2% $2,913,378
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
15.8 MW 26.7% $3,660,874

System Reinforcement: n9148.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9148.0 / TC1-PH1-DOM-013
Title
Wreck and rebuild 5.63 miles of 115 kV line between Wan and White Marsh with (1) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C.
Description
Wreck and rebuild 5.63 miles of 115 kV line between Wan and White Marsh with (1) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C.
Total Cost ($USD)
$37,993,385
Discounted Total Cost ($USD)
$15,526,073
Allocated Cost ($USD)
$2,762,955
Time Estimate
43 to 44 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

Facility Contingency
3WAN 89-3WHITEMARSH 115.0 kV Ckt 1 line (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
15.4 MW 17.8% $2,762,955
AG1-135 16.0 MW 18.4% $2,860,872
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
11.0 MW 12.7% $1,967,990
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
25.7 MW 29.6% $4,592,037
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
18.7 MW 21.5% $3,342,218

System Reinforcement: n9218.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9218.0 / TC1-PH2-DOM-030
Title
Reconductor 6.01 miles of 115 kV Line 65 from AG1-146 Tap to Lancaster with (1) 768.2 ACSS/TW (20/70 "Maumee" conductor @ 250 degrees C.
Description
Reconductor 6.01 miles of 115 kV Line 65 from AG1-146 Tap to Lancaster with (1) 768.2 ACSS/TW (20/70 "Maumee" conductor @ 250 degrees C.
Total Cost ($USD)
$27,984,346
Discounted Total Cost ($USD)
$11,435,859
Allocated Cost ($USD)
$2,575,135
Time Estimate
43 to 44 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

Facility Contingency
3LANCAST-AG1-146 TP 115.0 kV Ckt 1 line (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
37.2 MW 22.5% $2,575,135
AG1-135 36.0 MW 21.8% $2,492,102
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
18.0 MW 10.9% $1,246,051
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
42.0 MW 25.4% $2,907,406
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
32.0 MW 19.4% $2,215,164

System Reinforcement: n9651.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9651.0 / TC1-PH2-DOM-009
Title
Wreck and rebuild 10.05 miles of 115kV transmission line 1059 between Northern Neck and Moon Corner with (1) 768.2 ACSS/TW (20/7) "MAUMEE" conductor and replace line lead at Moon Corner.
Description
Wreck and rebuild 10.05 miles of Line 1059 between Northern Neck and Moon Corner with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C and replace line lead at Moon Corner (AE1-155).
Total Cost ($USD)
$28,476,954
Discounted Total Cost ($USD)
$28,476,954
Allocated Cost ($USD)
$5,944,669
Time Estimate
Mar 31 2029

Contributor

Facility Contingency
3NORNECK-AE1-155 TAP 115.0 kV Ckt 1 line (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
62.0 MW 20.9% $5,944,669
AG1-135 60.0 MW 20.2% $5,752,924
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
30.0 MW 10.1% $2,876,462
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
70.0 MW 23.6% $6,711,745
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
75.0 MW 25.3% $7,191,155

System Reinforcement: n7556
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7556 / dom-461
Title
Reconductor 3.53 miles of 115 kV Line 65 from AD2-074 Tap to AG1-146 Tap with (1) 768.2 ACSS/TW (20/70) "Maumee" conductor @ 250 degrees C
Description
Reconductor 3.53 miles of 115 kV Line 65 from AD2-074 Tap to AG1-146 Tap with (1) 768.2 ACSS/TW (20/70) "Maumee" conductor @ 250 degrees C
Total Cost ($USD)
$16,493,251
Discounted Total Cost ($USD)
$6,740,000
Allocated Cost ($USD)
$2,383,336
Time Estimate
43 to 44 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

Facility Contingency
AD2-074 TAP-AG1-146 TAP 115.0 kV Ckt 1 line (Any)
AD2-074 TP-AG1-146 TP 115.0 kV Ckt 1 line (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
37.2 MW 35.4% $2,383,336
AG1-135 36.0 MW 34.2% $2,306,488
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
32.0 MW 30.4% $2,050,176

System Reinforcement: n9380.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9380.0 / TC1-PH3-DOM-012
Title
Replace existing Ladysmith 230/500 kV transformer 1 with four (4) 480 MVA single phase transformers.
Description
Replace existing Ladysmith 230/500 kV transformer 1 with four (4) 480 MVA single phase transformers.
Total Cost ($USD)
$37,587,605
Discounted Total Cost ($USD)
$37,587,605
Allocated Cost ($USD)
$4,123,504
Time Estimate
Dec 31 2029

Contributor

Facility Contingency
6LADYSMITH-8LADYSMITH 230.0/500.0 kV Ckt 1 transformer (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-035 22.7 MW 31.4% $11,814,141
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
7.9 MW 11.0% $4,123,504
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
3.7 MW 5.2% $1,945,994
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
8.7 MW 12.1% $4,541,173
AG1-154 19.5 MW 27.1% $10,174,751
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
9.6 MW 13.3% $4,988,042

System Reinforcement: n7685
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7685 / dom-283
Title
Rebuild 4.56 miles of 230 kV Line 2157 from Fredericksburg to Cranes Corner with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 C and replace Line Lead at Cranes Corner.
Description
Rebuild 4.56 miles of 230 kV Line 2157 from Fredericksburg to Cranes Corner with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 C and replace Line Lead at Cranes Corner.
Total Cost ($USD)
$15,674,813
Discounted Total Cost ($USD)
$6,405,544
Allocated Cost ($USD)
$1,015,938
Time Estimate
43 to 44 Months

Aggregate ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

Facility Contingency
6CRANES-6FREDBRG 230.0 kV Ckt 1 line (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-035 6.4 MW 21.3% $1,363,282
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
4.8 MW 15.9% $1,015,938
AG1-135 4.5 MW 15.1% $967,815
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
2.1 MW 6.9% $439,955
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
4.8 MW 16.0% $1,026,632
AG1-154 3.4 MW 11.2% $718,001
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
4.1 MW 13.6% $873,921

System Reinforcement: n9212.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9212.0 / TC1-PH2-DOM-023
Title
Reconductor 3.01 mi of the 115 kV line 65 from Lancaster to Ocran with 768.2 ACSS 250 C.
Description
Reconductor 3.01 mi of 115 kV line 65 from Lancaster to Ocran with (1) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C.
Total Cost ($USD)
$9,591,162
Discounted Total Cost ($USD)
$3,919,447
Allocated Cost ($USD)
$882,584
Time Estimate
42 to 43 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

Facility Contingency
3OCRAN-3LANCAST 115.0 kV Ckt 1 line (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
37.2 MW 22.5% $882,584
AG1-135 36.0 MW 21.8% $854,126
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
18.0 MW 10.9% $427,063
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
42.0 MW 25.4% $996,464
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
32.0 MW 19.4% $759,210

System Reinforcement: n7549
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7549 / dom-428
Title
Replace Northern Neck 115/230 kV transformer #4 with a 224 MVA (260/271/295 MVA).
Description
Replace Northern Neck 115/230 kV transformer #4 with a 224 MVA (260/271/295 MVA).
Total Cost ($USD)
$7,324,554
Discounted Total Cost ($USD)
$7,324,554
Allocated Cost ($USD)
$1,850,537
Time Estimate
59 to 60 Months

Contributor

Facility Contingency
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
23.6 MW 25.3% $1,850,537
AG1-135 21.9 MW 23.5% $1,717,897
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
8.3 MW 8.9% $649,262
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
19.3 MW 20.7% $1,514,944
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
20.3 MW 21.7% $1,591,913

System Reinforcement: n7553
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7553 / dom-427
Title
Replace Northern Neck 115/230 kV transformer #6 with a 224 MVA (260/271/295 MVA).
Description
Replace Northern Neck 115/230 kV transformer #6 with a 224 MVA (260/271/295 MVA).
Total Cost ($USD)
$7,242,347
Discounted Total Cost ($USD)
$7,242,347
Allocated Cost ($USD)
$1,829,790
Time Estimate
59 to 60 Months

Contributor

Facility Contingency
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
24.6 MW 25.3% $1,829,790
AG1-135 22.8 MW 23.5% $1,698,623
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
8.6 MW 8.9% $642,003
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
20.1 MW 20.7% $1,497,932
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
21.2 MW 21.7% $1,574,000

System Reinforcement: n8305
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8305 / dom-471
Title
Reconductor 1.33 Miles of 115kV transmission line 65 from Ocran to Whitestone
Description
Reconductor 1.33 miles of 115 kV Line 65 from Ocran to Whitestone with (1) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C. Upgrade 1534 ACRA 42/19 MOT 75 line leads at Whitestone and Ocran.
Total Cost ($USD)
$6,374,460
Discounted Total Cost ($USD)
$2,604,936
Allocated Cost ($USD)
$586,581
Time Estimate
42 to 43 Months

ContributorEliminated

Note: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle. However, this project is receiving cost allocation based on its MW contribution to this eliminated reinforcement to fund the topology reinforcements which together alleviated the need for this reinforcement. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

Since this project contributed to a violation with a reinforcement that was eliminated by the topology changing reinforcements, this project is contingent on all of the topology changing reinforcements within the region in which the eliminated reinforcement belongs.

Facility Contingency
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
37.2 MW 22.5% $586,581
AG1-135 36.0 MW 21.8% $567,668
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
18.0 MW 10.9% $283,834
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
42.0 MW 25.4% $662,268
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
32.0 MW 19.4% $504,585

System Reinforcement: n9207.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9207.0 / TC1-PH2-DOM-018
Title
Replace 6ELMONT 230 kV to 8ELMONT 500 kV circuit 1 with larger transformer (3-480 MVA single phase transformer).
Description
Replace 6ELMONT 230 KV to 8ELMONT 500 kV ckt 1 with Larger XFRM. (3-480 MVA Single Phase XFRM).
Total Cost ($USD)
$38,254,469
Discounted Total Cost ($USD)
$38,254,469
Allocated Cost ($USD)
$834,462
Time Estimate
59 to 60 Months

Contributor

Facility Contingency
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AE2-156 14.4 MW 3.1% $1,200,552
AF1-123 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
117.8 MW 25.7% $9,843,658
AF1-124 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
118.2 MW 25.8% $9,879,089
AF1-125 ⧉ CVOW Harpers 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF1-123, AF1-124, AF1-125
116.0 MW 25.3% $9,689,986
AF2-035 11.0 MW 2.4% $919,947
AF2-046 ⧉ AF2-046 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-046, AG1-008
15.3 MW 3.3% $1,278,517
AF2-081 11.2 MW 2.4% $936,743
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
10.0 MW 2.2% $834,462
AG1-008 ⧉ AF2-046 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-046, AG1-008
15.3 MW 3.3% $1,278,517
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
5.0 MW 1.1% $415,058
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
11.6 MW 2.5% $968,497
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
12.1 MW 2.6% $1,009,443

System Reinforcement: n9652.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9652.0 / TC1-PH2-DOM-010
Title
Replace Wave Trap at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner
Description
Replace Wave Trap at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner
Total Cost ($USD)
$1,065,776
Discounted Total Cost ($USD)
$1,065,776
Allocated Cost ($USD)
$222,485
Time Estimate
Mar 01 2027

Contributor

Facility Contingency
3NORNECK-AE1-155 TAP 115.0 kV Ckt 1 line (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
62.0 MW 20.9% $222,485
AG1-135 60.0 MW 20.2% $215,308
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
30.0 MW 10.1% $107,654
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
70.0 MW 23.6% $251,193
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
75.0 MW 25.3% $269,136

System Reinforcement: n9653.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9653.0 / TC1-PH2-DOM-011
Title
Replace Line Switch at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner
Description
Replace Line Switch at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner
Total Cost ($USD)
$454,326
Discounted Total Cost ($USD)
$454,326
Allocated Cost ($USD)
$94,842
Time Estimate
Mar 01 2027

Contributor

Facility Contingency
3NORNECK-AE1-155 TAP 115.0 kV Ckt 1 line (Any)
Cost Allocation
Project MW Impact Percent Allocation Allocated Cost ($USD)
AF2-120 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
62.0 MW 20.9% $94,842
AG1-135 60.0 MW 20.2% $91,783
AG1-146 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
30.0 MW 10.1% $45,892
AG1-147 ⧉ AG1-146 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG1-146, AG1-147
70.0 MW 23.6% $107,080
AG1-536 ⧉ AE1-155 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AF2-120, AG1-536
75.0 MW 25.3% $114,729

System Reinforcement: n6161
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6161 / dom-039
Title
Replace 500 kV circuit breaker H1T561 at Clifton with a higher rated device (Clifton - Ox).
Description
Replace 500 kV circuit breaker H1T561 at Clifton with a higher rated device (Clifton - Ox).
Total Cost ($USD)
$2,634,901
Discounted Total Cost ($USD)
$2,634,901
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-120 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-120 could receive cost allocation. Although AF2-120 may not presently have cost responsibility for this upgrade, AF2-120 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

Facility Contingency
8CLIFTON-8OX 500.0 kV Ckt 1 line (Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AF2-120 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-120 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

Facility Contingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line (Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line (Any)
System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-120 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-120 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

Facility Contingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line (Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line (Any)
System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-120 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-120 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

Facility Contingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line (Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line (Any)
System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-120 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-120 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

Facility Contingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line (Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line (Any)
System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-120 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-120 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

Facility Contingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line (Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line (Any)
System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AF2-120 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-120 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

Facility Contingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line (Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line (Any)
System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AF2-120 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-120 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

Facility Contingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line (Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line (Any)
System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-120 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-120 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

Facility Contingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line (Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line (Any)
System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AF2-120 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-120 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

Facility Contingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line (Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line (Any)
System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030
Cost Alloc Type
Contingent

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not ContingentTopology Changing

Note 1: AF2-120 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-120 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

Facility Contingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line (Any)
System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not ContingentTopology Changing

Note 1: AF2-120 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-120 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

Facility Contingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line (Any)
System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029
Cost Alloc Type
Contingent

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not ContingentTopology Changing

Note 1: AF2-120 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AF2-120 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

Facility Contingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line (Any)
System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029
Cost Alloc Type
Contingent

System Reinforcement: n9246.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9246.0 / TC1-PH2-DOM-040
Title
Wreck and rebuild 18.75 miles of Line 594 btwn Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work to achieve new rating of 4356/4356/5009 MVA.
Description
Wreck and rebuild 18.75 miles of Line 594 between Morrisville and Spotsylvania with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$128,018,212
Discounted Total Cost ($USD)
$128,018,212
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-120 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-120 could receive cost allocation. Although AF2-120 may not presently have cost responsibility for this upgrade, AF2-120 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

Facility Contingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line (Any)

System Reinforcement: n9247.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9247.0 / TC1-PH2-DOM-041
Title
Wreck and rebuild 14.02 miles of Line 573 btwn Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and assoc substation work to achieve new rating of 4356/4356/5009 MVA.
Description
Wreck and rebuild 14.02 miles of Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA
Total Cost ($USD)
$99,636,684
Discounted Total Cost ($USD)
$99,636,684
Allocated Cost ($USD)
$0
Time Estimate
48 Months

Potential Aggregate ContributorEliminated

Note 1: Based on PJM cost allocation criteria, AF2-120 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AF2-120 could receive cost allocation. Although AF2-120 may not presently have cost responsibility for this upgrade, AF2-120 is a potential Aggregate Pool Contributor.

Note 2: The topology changing reinforcements listed in the Cycle executive summary report eliminated the need for this reinforcement and it is no longer required by the Cycle.

Facility Contingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line (Any)

System Reinforcement: n9138.0

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Allocated Cost ($USD)
$5,003,236
Time Estimate
60 to 61 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
Project Percent Allocation Allocated Cost ($USD)
AE1-148 0.5656 % $628,553
AE2-185 0.0346 % $38,451
AE2-187 0.0300 % $33,339
AE2-283 0.0305 % $33,895
AE2-291 0.5378 % $597,659
AF1-123 10.2087 % $11,344,958
AF1-124 10.2455 % $11,385,854
AF1-125 10.0507 % $11,169,372
AF1-294 0.4085 % $453,967
AF2-035 0.2624 % $291,606
AF2-042 28.1786 % $31,314,960
AF2-046 2.8849 % $3,205,998
AF2-115 0.2488 % $276,492
AF2-120 4.5021 % $5,003,197
AF2-222 3.8795 % $4,311,300
AF2-297 0.7165 % $796,249
AG1-008 2.8849 % $3,205,998
AG1-021 0.1990 % $221,149
AG1-082 0.1873 % $208,147
AG1-098 1.6029 % $1,781,307
AG1-105 0.6819 % $757,797
AG1-124 1.0619 % $1,180,093
AG1-135 4.4165 % $4,908,069
AG1-146 2.1236 % $2,359,963
AG1-147 4.9550 % $5,506,506
AG1-154 0.1382 % $153,582
AG1-166 0.1304 % $144,914
AG1-167 0.0978 % $108,685
AG1-168 0.0978 % $108,685
AG1-285 2.7978 % $3,109,203
AG1-342 0.0630 % $70,012
AG1-494 0.8172 % $908,157
AG1-536 4.9600 % $5,512,062

System Reinforcement: n9250.0

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Allocated Cost ($USD)
$4,895,086
Time Estimate
60 to 61 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
Project Percent Allocation Allocated Cost ($USD)
AE1-148 0.5656 % $614,966
AE2-185 0.0346 % $37,620
AE2-187 0.0300 % $32,618
AE2-283 0.0305 % $33,162
AE2-291 0.5378 % $584,740
AF1-123 10.2087 % $11,099,724
AF1-124 10.2455 % $11,139,736
AF1-125 10.0507 % $10,927,934
AF1-294 0.4085 % $444,154
AF2-035 0.2624 % $285,302
AF2-042 28.1786 % $30,638,052
AF2-046 2.8849 % $3,136,697
AF2-115 0.2488 % $270,515
AF2-120 4.5021 % $4,895,047
AF2-222 3.8795 % $4,218,106
AF2-297 0.7165 % $779,037
AG1-008 2.8849 % $3,136,697
AG1-021 0.1990 % $216,369
AG1-082 0.1873 % $203,648
AG1-098 1.6029 % $1,742,802
AG1-105 0.6819 % $741,417
AG1-124 1.0619 % $1,154,584
AG1-135 4.4165 % $4,801,976
AG1-146 2.1236 % $2,308,950
AG1-147 4.9550 % $5,387,477
AG1-154 0.1382 % $150,262
AG1-166 0.1304 % $141,781
AG1-167 0.0978 % $106,336
AG1-168 0.0978 % $106,336
AG1-285 2.7978 % $3,041,994
AG1-342 0.0630 % $68,499
AG1-494 0.8172 % $888,526
AG1-536 4.9600 % $5,392,913

System Reinforcement: n9630.0

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$89,468,616
Allocated Cost ($USD)
$4,027,998
Time Estimate
Dec 31 2029
Cost Alloc Type
Cost Allocated
Cost Allocation
Project Percent Allocation Allocated Cost ($USD)
AE1-148 0.5656 % $506,034
AE2-185 0.0346 % $30,956
AE2-187 0.0300 % $26,841
AE2-283 0.0305 % $27,288
AE2-291 0.5378 % $481,162
AF1-123 10.2087 % $9,133,583
AF1-124 10.2455 % $9,166,507
AF1-125 10.0507 % $8,992,222
AF1-294 0.4085 % $365,479
AF2-035 0.2624 % $234,766
AF2-042 28.1786 % $25,211,003
AF2-046 2.8849 % $2,581,080
AF2-115 0.2488 % $222,598
AF2-120 4.5021 % $4,027,967
AF2-222 3.8795 % $3,470,935
AF2-297 0.7165 % $641,043
AG1-008 2.8849 % $2,581,080
AG1-021 0.1990 % $178,043
AG1-082 0.1873 % $167,575
AG1-098 1.6029 % $1,434,092
AG1-105 0.6819 % $610,086
AG1-124 1.0619 % $950,067
AG1-135 4.4165 % $3,951,381
AG1-146 2.1236 % $1,899,956
AG1-147 4.9550 % $4,433,170
AG1-154 0.1382 % $123,646
AG1-166 0.1304 % $116,667
AG1-167 0.0978 % $87,500
AG1-168 0.0978 % $87,500
AG1-285 2.7978 % $2,503,153
AG1-342 0.0630 % $56,365
AG1-494 0.8172 % $731,138
AG1-536 4.9600 % $4,437,643

System Reinforcement: n8492

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492
Title
Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line.
Description
Wreck and rebuild one (1) overhead 500kV transmission line that will start at the existing Fentress 500 kV Substation and terminate at the existing Yadkin 500 kV Substation, located approximately 13.5 miles away.
Total Cost ($USD)
$80,172,278
Allocated Cost ($USD)
$3,609,464
Time Estimate
26 to 27 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
Project Percent Allocation Allocated Cost ($USD)
AE1-148 0.5656 % $453,454
AE2-185 0.0346 % $27,740
AE2-187 0.0300 % $24,052
AE2-283 0.0305 % $24,453
AE2-291 0.5378 % $431,167
AF1-123 10.2087 % $8,184,547
AF1-124 10.2455 % $8,214,051
AF1-125 10.0507 % $8,057,875
AF1-294 0.4085 % $327,504
AF2-035 0.2624 % $210,372
AF2-042 28.1786 % $22,591,426
AF2-046 2.8849 % $2,312,890
AF2-115 0.2488 % $199,469
AF2-120 4.5021 % $3,609,436
AF2-222 3.8795 % $3,110,284
AF2-297 0.7165 % $574,434
AG1-008 2.8849 % $2,312,890
AG1-021 0.1990 % $159,543
AG1-082 0.1873 % $150,163
AG1-098 1.6029 % $1,285,081
AG1-105 0.6819 % $546,695
AG1-124 1.0619 % $851,349
AG1-135 4.4165 % $3,540,809
AG1-146 2.1236 % $1,702,538
AG1-147 4.9550 % $3,972,536
AG1-154 0.1382 % $110,798
AG1-166 0.1304 % $104,545
AG1-167 0.0978 % $78,408
AG1-168 0.0978 % $78,408
AG1-285 2.7978 % $2,243,060
AG1-342 0.0630 % $50,509
AG1-494 0.8172 % $655,168
AG1-536 4.9600 % $3,976,545

System Reinforcement: n9259.0

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n9259.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9259.0
Title
Install two 230 kV gas insulated switchgear ("GIS") bus ties for the Coastal Virginia Offshore Wind ("CVOW") project.
Description
Install two 230 kV gas insulated switchgear ("GIS") bus ties for the Coastal Virginia Offshore Wind ("CVOW") project.
Total Cost ($USD)
$25,304,902
Allocated Cost ($USD)
$1,139,261
Time Estimate
38 to 39 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
Project Percent Allocation Allocated Cost ($USD)
AE1-148 0.5656 % $143,125
AE2-185 0.0346 % $8,755
AE2-187 0.0300 % $7,591
AE2-283 0.0305 % $7,718
AE2-291 0.5378 % $136,090
AF1-123 10.2087 % $2,583,302
AF1-124 10.2455 % $2,592,614
AF1-125 10.0507 % $2,543,320
AF1-294 0.4085 % $103,371
AF2-035 0.2624 % $66,400
AF2-042 28.1786 % $7,130,567
AF2-046 2.8849 % $730,021
AF2-115 0.2488 % $62,959
AF2-120 4.5021 % $1,139,252
AF2-222 3.8795 % $981,704
AF2-297 0.7165 % $181,310
AG1-008 2.8849 % $730,021
AG1-021 0.1990 % $50,357
AG1-082 0.1873 % $47,396
AG1-098 1.6029 % $405,612
AG1-105 0.6819 % $172,554
AG1-124 1.0619 % $268,713
AG1-135 4.4165 % $1,117,591
AG1-146 2.1236 % $537,375
AG1-147 4.9550 % $1,253,858
AG1-154 0.1382 % $34,971
AG1-166 0.1304 % $32,998
AG1-167 0.0978 % $24,748
AG1-168 0.0978 % $24,748
AG1-285 2.7978 % $707,981
AG1-342 0.0630 % $15,942
AG1-494 0.8172 % $206,792
AG1-536 4.9600 % $1,255,123

System Reinforcement: n7541

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n7541
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7541 / dom-016
Title
Add a third 224 MVA 230/115 kV transformer at Earleys Substation and supporting equipment.
Description
Add a third 224 MVA 230/115 kV transformer at Earleys Substation and supporting equipment.
Total Cost ($USD)
$22,779,395
Allocated Cost ($USD)
$1,025,559
Time Estimate
Dec 31 2029
Cost Alloc Type
Cost Allocated
Cost Allocation
Project Percent Allocation Allocated Cost ($USD)
AE1-148 0.5656 % $128,840
AE2-185 0.0346 % $7,882
AE2-187 0.0300 % $6,834
AE2-283 0.0305 % $6,948
AE2-291 0.5378 % $122,508
AF1-123 10.2087 % $2,325,480
AF1-124 10.2455 % $2,333,863
AF1-125 10.0507 % $2,289,489
AF1-294 0.4085 % $93,054
AF2-035 0.2624 % $59,773
AF2-042 28.1786 % $6,418,915
AF2-046 2.8849 % $657,163
AF2-115 0.2488 % $56,675
AF2-120 4.5021 % $1,025,551
AF2-222 3.8795 % $883,727
AF2-297 0.7165 % $163,214
AG1-008 2.8849 % $657,163
AG1-021 0.1990 % $45,331
AG1-082 0.1873 % $42,666
AG1-098 1.6029 % $365,131
AG1-105 0.6819 % $155,333
AG1-124 1.0619 % $241,894
AG1-135 4.4165 % $1,006,052
AG1-146 2.1236 % $483,743
AG1-147 4.9550 % $1,128,719
AG1-154 0.1382 % $31,481
AG1-166 0.1304 % $29,704
AG1-167 0.0978 % $22,278
AG1-168 0.0978 % $22,278
AG1-285 2.7978 % $637,322
AG1-342 0.0630 % $14,351
AG1-494 0.8172 % $186,153
AG1-536 4.9600 % $1,129,858

System Reinforcement: n8492.1

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.1
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.1
Title
Two Breaker Additions at Fentress Substation.
Description
Install Two 5000 amp GIS Breakers at Fentress Substation to connect the new 500 kV line 5005.
Total Cost ($USD)
$19,945,879
Allocated Cost ($USD)
$897,990
Time Estimate
30 to 36 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
Project Percent Allocation Allocated Cost ($USD)
AE1-148 0.5656 % $112,814
AE2-185 0.0346 % $6,901
AE2-187 0.0300 % $5,984
AE2-283 0.0305 % $6,083
AE2-291 0.5378 % $107,269
AF1-123 10.2087 % $2,036,215
AF1-124 10.2455 % $2,043,555
AF1-125 10.0507 % $2,004,700
AF1-294 0.4085 % $81,479
AF2-035 0.2624 % $52,338
AF2-042 28.1786 % $5,620,469
AF2-046 2.8849 % $575,419
AF2-115 0.2488 % $49,625
AF2-120 4.5021 % $897,983
AF2-222 3.8795 % $773,800
AF2-297 0.7165 % $142,912
AG1-008 2.8849 % $575,419
AG1-021 0.1990 % $39,692
AG1-082 0.1873 % $37,359
AG1-098 1.6029 % $319,712
AG1-105 0.6819 % $136,011
AG1-124 1.0619 % $211,805
AG1-135 4.4165 % $880,910
AG1-146 2.1236 % $423,571
AG1-147 4.9550 % $988,318
AG1-154 0.1382 % $27,565
AG1-166 0.1304 % $26,009
AG1-167 0.0978 % $19,507
AG1-168 0.0978 % $19,507
AG1-285 2.7978 % $558,046
AG1-342 0.0630 % $12,566
AG1-494 0.8172 % $162,998
AG1-536 4.9600 % $989,316

System Reinforcement: n8492.2

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: n8492.2
Type
Stability
TO
Dominion
RTEP ID / TO ID
n8492.2
Title
Expand Yadkin Substation to accommodate the new 500 kV line.
Description
Expansion of yadkins 500 kV switchyard to accommodate the new 500 kV line which includes addition of 5000 amp GIS breakers and relocation of the existing suffolk -yadkin 500 kV line#565
Total Cost ($USD)
$16,207,123
Allocated Cost ($USD)
$729,667
Time Estimate
15 to 16 Months
Cost Alloc Type
Cost Allocated
Cost Allocation
Project Percent Allocation Allocated Cost ($USD)
AE1-148 0.5656 % $91,667
AE2-185 0.0346 % $5,608
AE2-187 0.0300 % $4,862
AE2-283 0.0305 % $4,943
AE2-291 0.5378 % $87,162
AF1-123 10.2087 % $1,654,537
AF1-124 10.2455 % $1,660,501
AF1-125 10.0507 % $1,628,929
AF1-294 0.4085 % $66,206
AF2-035 0.2624 % $42,527
AF2-042 28.1786 % $4,566,940
AF2-046 2.8849 % $467,559
AF2-115 0.2488 % $40,323
AF2-120 4.5021 % $729,661
AF2-222 3.8795 % $628,755
AF2-297 0.7165 % $116,124
AG1-008 2.8849 % $467,559
AG1-021 0.1990 % $32,252
AG1-082 0.1873 % $30,356
AG1-098 1.6029 % $259,784
AG1-105 0.6819 % $110,516
AG1-124 1.0619 % $172,103
AG1-135 4.4165 % $715,788
AG1-146 2.1236 % $344,174
AG1-147 4.9550 % $803,063
AG1-154 0.1382 % $22,398
AG1-166 0.1304 % $21,134
AG1-167 0.0978 % $15,851
AG1-168 0.0978 % $15,851
AG1-285 2.7978 % $453,443
AG1-342 0.0630 % $10,210
AG1-494 0.8172 % $132,445
AG1-536 4.9600 % $803,873

System Reinforcement: b4000.356

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.355

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.342

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.341

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3689.2

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3689.2
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b3689.2
Title
Replace 230 kV breakers SC102, H302, H402 and 218302 at Brambleton substation with 80 kA
Description
Replace 230 kV breakers SC102, H302, H402 and 218302 at Brambleton substation with 4000A 80 kA breakers and associated equipment including breaker leads as necessary to address breaker duty issues identified in short circuit analysis.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.103

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.103
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b4000.103
Title
Brambleton Sub 230kV - replace 63kA breakers 217202, 2172T2183, L102, L202 with 80kA
Description
Brambleton Sub 230kV - replace 63kA breakers 217202, 2172T2183, L102, L202 with 80kA
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.405

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.405
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b3800.405
Title
Replace Brambleton 230 kV breakers 20102, 20602, 204502, 209402, 201T2045, 206T2094 with breakers rated 80 kA.
Description
Replace Brambleton 230 kV breakers 20102, 20602, 204502, 209402, 201T2045, 206T2094 with breakers rated 80 kA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3854.1

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3854.1
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b3854.1
Title
Replace over duty Carson 230kV circuit breakers 200272 and 24972-3 with an interrupting rating of 63 kA
Description
Replace over duty Carson 230kV circuit breakers 200272 and 24972-3 with an interrupting rating of 63 kA
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.108

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.108
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b4000.108
Title
Carson Sub 230kV - replace 40kA breaker 23872 with 63kA
Description
Carson Sub 230kV - replace 40kA breaker 23872 with 63kA
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.406

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.406
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b3800.406
Title
Replace Gainesville 230 kV breaker 216192 with a breaker rated 80 kA.
Description
Replace Gainesville 230 kV breaker 216192 with a breaker rated 80 kA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.115

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.115
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b4000.115
Title
Ladysmith Sub 500kV - replace 40kA breaker 574T581 with 63kA
Description
Ladysmith Sub 500kV - replace 40kA breaker 574T581 with 63kA
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.354

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.354
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b4000.354
Title
Ladysmith substation breakers replacement: 574T575 and 568T581
Description
Expand Ladysmith substation to a add redundant circuit breakers to the middle breakers on both 500kV strings (574T575 and 568T581). The equipment including switches 57518, 57515, H115 will be replaced with 5000A equipment.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3853.1

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3853.1
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b3853.1 / (Pending)
Title
Replace over duty Ladysmith CT 230kV circuit breakers SX1272 and SX3472 with an interrupting rating of 63 kA
Description
Replace over duty Ladysmith CT 230kV circuit breakers SX1272 and SX3472 with an interrupting rating of 63 kA
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.114

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.114
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b4000.114
Title
Ladysmith S1 Sub 230kV - replace 40kA breakers 25672, 209072, 256T2090, GT172, GT272, GT372, GT472, GT572 with 63kA
Description
Ladysmith S1 Sub 230kV - replace 40kA breakers 25672, 209072, 256T2090, GT172, GT272, GT372, GT472, GT572 with 63kA
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.235

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.235
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b3800.235
Title
Replace 5 overdutied 230kV breakers at Loudoun substation with 80kA breakers
Description
Replace 5 overdutied 230kV breakers at Loudoun substation with 80kA breakers: 212352, 2123T2173, 2030T2117, 211752, and 2008T2045
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.334

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.334
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b3800.334
Title
Replace four (4) overdutied 230 kV breakers at Loudoun Substation with 80 kA breakers.
Description
Replace 4 overdutied 230kV breakers at Loudoun Substation with 80kA breakers: 2094T2140, 214052, 200852 and 203052.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.407

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.407
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b3800.407
Title
Replace Loudoun 230 kV breakers 204552 and 217352 with breakers rated 80 kA.
Description
Replace Loudoun 230 kV breakers 204552, 217352 with breakers rated 80 kA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.119

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.119
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b4000.119
Title
Loudoun Cap Substation 230kV - replace 50 kA breaker SC352 with 63 kA.
Description
Loudoun Cap Sub 230kV - replace 50kA breaker SC352 with 63kA
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.128

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.128
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b4000.128
Title
North Anna Substation 500 kV - replace 40 kA breakers 57502, G102-1, G102-2, G202, G2T575, and XT573 with 63 kA.
Description
North Anna Sub 500kV - replace 40kA breakers 57502, G102-1, G102-2, G202, G2T575, XT573 with 63kA
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.408

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.408
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b3800.408
Title
Replace Ox 230 kV breakers 22042, 24342, 24842, 220T2063, 243T2097, 248T2013, and H342 with breakers rated 80 kA.
Description
Replace Ox 230 kV breakers 22042, 24342, 24842, 220T2063, 243T2097, 248T2013, H342 with breakers rated 80 kA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: s2609.6

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s2609.6
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
s2609.6
Title
Upgrade two (2) 230 kV breakers 201342 and L142 from 50 kA to 63 kA at Ox Substation due to an insufficient breaker duty rating with the expansion in place.
Description
Upgrade (2) 230 kV breakers 201342 & L142 from 50kA to 63kA at Ox Substation due to an insufficient breaker duty rating with the expansion in place.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: s2609.9

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s2609.9
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
s2609.9
Title
Upgrade 230 kV Pleasant View breakers L3T203 and L3T2180 from 50 kA to 80 kA.
Description
Upgrade 230kV Pleasant View breakers L3T203 and L3T2180 from 50kA to 80kA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b4000.134

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b4000.134
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b4000.134
Title
Remington Substation 230 kV - replace 40 kA and 50 kA breakers 211462, GT162, GT262, GT362, GT462, 2077T2086, 208662, H962, and H9T299 with 63 kA.
Description
Remington Sub 230kV - replace 40kA and 50kA breakers 211462, GT162, GT262, GT362, GT462, 2077T2086, 208662, H962, H9T299 with 63kA
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b1696

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b1696
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b1696
Title
Install a breaker and a half scheme with a minimum of eight 230 kV breakers for five existing lines at Idylwood 230 kV: 20212 and 20712
Description
Install a breaker and a half scheme with a minimum of eight 230 kV breakers for five existing lines at Idylwood 230 kV: 20212 and 20712
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.236

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.236
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b3800.236
Title
Replace 2 overdutied 500kV breakers at Ox Substation with 63kA breakers.
Description
Replace 2 overdutied 500kV breakers at Ox Substation with 63kA breakers: H1T539 and H2T539
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: s3047.2

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: s3047.2
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3047.2
Title
Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation.
Description
Install (2) 1400 MVA 500-230 kV transformers and associated 500 kV and 230 kV equipment (breakers, switches, leads) at Vint Hill Substation to supply the area with a 500 kV source Cut and loop 500 kV line #535 Loudoun – Meadowbrook and #569 Loudoun - Morrisville as the 500 kV sources into the proposed 500 kV ring bus Vint Hill Substation will be expanded to the north of the existing site to accommodate the 500 kV ring required for the addition of the new transformers Existing terminations for 230 kV line #2174 Wheeler – Vint Hill, line #2101 Bristers – Vint Hill, and line #2163 Liberty – Vint Hill will be rearranged to terminate into the expanded Vint Hill Substation 230 kV line #2114 Remington CT – Rollins Ford will also be cut and looped into the expanded Vint Hill Substation due to spatial constraints along the existing right-of-way.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.312

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.312
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.312
Title
Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way.
Description
Rebuild 500kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. New conductor to have a summer rating of 4357 MVA.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.313

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.313
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.313
Title
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Description
Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.356

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.356
Title
Build a new 500 kV line from Vint Hill to Wishing Star.
Description
Build a new 500kV line from Vint Hill to Wishing Star. The line will be supported on single circuit monopoles. New conductor to have a summer rating of 4357 MVA. Line length is approximately 16.59 miles
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.357

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.357
Title
Build a new 500 kV line from Morrisville to Vint Hill.
Description
Build a new 500kV line from Morrisville to Vint Hill. New conductor to have a summer rating of 4357 MVA. Line length is approximately 19.71 miles.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.354

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.354
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.354
Title
Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590.
Description
Install terminal equipment at Wishing Star substation to support a 5000A line to Vint Hill. Update relay settings for 500kV Lines #546 and #590.
Cost Information
Cost Alloc Type
Contingent

System Reinforcement: b3800.335

AF2-120 did not load into this reinforcement directly however this project contributed to an topology or eliminated upgrade and therefore this project is responsible for relevant regional upgrades.

System Reinforcement: b3800.335
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b3800.335
Title
Replace 1 overdutied 500kV breaker at Ox Substation with a 63kA breaker
Description
Replace 1 overdutied 500kV breaker at Ox Substation with a 63kA breaker: 56142
Cost Information
Cost Alloc Type
Contingent

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AF2-120


AF2-120 Contributions into Topology or Eliminated Reinforcements:
Type TO RTEP ID / TO ID Title Topo or Elim MW Impact Percent Allocation Category Allocated Cost ($USD)
Stability Dominion n9267.0 / TC1-PH2-DOM-067 Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner. Topology 122.0 MW 20.6% Cost Allocated $3,851,263
Load Flow Dominion n7576 / dom-281 Rebuild 7.91 miles of 230 kV Line 2083 from Birchwood to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor 250 degrees C. Eliminated 13.0 MW 22.1% Cost Allocated $3,222,678
Load Flow Dominion n9222.0 / TC1-PH2-DOM-036 Wreck and Rebuild 6.95 miles of 115 kV Line 89 from White Marsh to Hayes with (1) 768 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C. Replace Line Lead at Hayes. Eliminated 15.4 MW 17.8% Cost Allocated $3,080,189
Load Flow Dominion n7575 / dom-286 Rebuild 6.46 mi miles of 2-545.6 ACAR (15/7) 90 MOT 230 kV Line 2083 from Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C. Eliminated 13.0 MW 22.1% Cost Allocated $3,026,431
Load Flow Dominion n9148.0 / TC1-PH1-DOM-013 Wreck and rebuild 5.63 miles of 115 kV line between Wan and White Marsh with (1) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C. Eliminated 15.4 MW 17.8% Cost Allocated $2,762,955
Load Flow Dominion n9218.0 / TC1-PH2-DOM-030 Reconductor 6.01 miles of 115 kV Line 65 from AG1-146 Tap to Lancaster with (1) 768.2 ACSS/TW (20/70 "Maumee" conductor @ 250 degrees C. Eliminated 37.2 MW 22.5% Cost Allocated $2,575,135
Load Flow Dominion n7556 / dom-461 Reconductor 3.53 miles of 115 kV Line 65 from AD2-074 Tap to AG1-146 Tap with (1) 768.2 ACSS/TW (20/70) "Maumee" conductor @ 250 degrees C Eliminated 37.2 MW 35.4% Cost Allocated $2,383,336
Load Flow Dominion n7685 / dom-283 Rebuild 4.56 miles of 230 kV Line 2157 from Fredericksburg to Cranes Corner with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 C and replace Line Lead at Cranes Corner. Eliminated 4.8 MW 15.9% Cost Allocated $1,015,938
Load Flow Dominion n9212.0 / TC1-PH2-DOM-023 Reconductor 3.01 mi of the 115 kV line 65 from Lancaster to Ocran with 768.2 ACSS 250 C. Eliminated 37.2 MW 22.5% Cost Allocated $882,584
Load Flow Dominion n8305 / dom-471 Reconductor 1.33 Miles of 115kV transmission line 65 from Ocran to Whitestone Eliminated 37.2 MW 22.5% Cost Allocated $586,581
Contributions into Topology or Eliminated Reinforcement Total: $23,387,090
AF2-120 Contingent Region Topology Upgrades:
TO RTEP ID Title Category Allocated Cost ($USD)
Dominion n9138.0 Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work. Cost Allocated $5,003,236
Dominion n9250.0 Construct a new 22.59 mile line between Carson and Rawlings Substations. Cost Allocated $4,895,086
Dominion n9630.0 Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers. Cost Allocated $4,027,998
Dominion n8492 Wreck and rebuild the existing Yadkin to Fentress 500 kV Line #588 to share the right of way with the new Yadkin to Fentress #5005 line. Cost Allocated $3,609,464
Dominion n9267.0 Construct new 10.21 mile 115 kV line between Northern Neck and Moon Corner. Cost Allocated $2,058,830
Dominion n9259.0 Install two 230 kV gas insulated switchgear ("GIS") bus ties for the Coastal Virginia Offshore Wind ("CVOW") project. Cost Allocated $1,139,261
Dominion n7541 Add a third 224 MVA 230/115 kV transformer at Earleys Substation and supporting equipment. Cost Allocated $1,025,559
Dominion n8492.1 Two Breaker Additions at Fentress Substation. Cost Allocated $897,990
Dominion n8492.2 Expand Yadkin Substation to accommodate the new 500 kV line. Cost Allocated $729,667
Dominion b4000.357 Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat. Contingent $0
Dominion b4000.356 Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section). Contingent $0
Dominion b4000.355 Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section). Contingent $0
Dominion b4000.352 Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point. Contingent $0
Dominion b4000.351 Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken. Contingent $0
Dominion b4000.350 Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken. Contingent $0
Dominion b4000.349 Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken. Contingent $0
Dominion b4000.348 Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. Contingent $0
Dominion b4000.346 Cut-in 500kV line from Kraken substation into Yeat substation Contingent $0
Dominion b4000.345 Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA. Contingent $0
Dominion b4000.344 Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA. Contingent $0
Dominion b4000.342 Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill. Contingent $0
Dominion b4000.341 Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site. Contingent $0
Dominion b4000.325 Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA. Contingent $0
Dominion b3689.2 Replace 230 kV breakers SC102, H302, H402 and 218302 at Brambleton substation with 80 kA Contingent $0
Dominion b4000.103 Brambleton Sub 230kV - replace 63kA breakers 217202, 2172T2183, L102, L202 with 80kA Contingent $0
Dominion b3800.405 Replace Brambleton 230 kV breakers 20102, 20602, 204502, 209402, 201T2045, 206T2094 with breakers rated 80 kA. Contingent $0
Dominion b3854.1 Replace over duty Carson 230kV circuit breakers 200272 and 24972-3 with an interrupting rating of 63 kA Contingent $0
Dominion b4000.108 Carson Sub 230kV - replace 40kA breaker 23872 with 63kA Contingent $0
Dominion b4000.326 At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith. Contingent $0
Dominion b4000.327 Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme. Contingent $0
Dominion b3800.406 Replace Gainesville 230 kV breaker 216192 with a breaker rated 80 kA. Contingent $0
Dominion b4000.115 Ladysmith Sub 500kV - replace 40kA breaker 574T581 with 63kA Contingent $0
Dominion b4000.354 Ladysmith substation breakers replacement: 574T575 and 568T581 Contingent $0
Dominion b3853.1 Replace over duty Ladysmith CT 230kV circuit breakers SX1272 and SX3472 with an interrupting rating of 63 kA Contingent $0
Dominion b4000.114 Ladysmith S1 Sub 230kV - replace 40kA breakers 25672, 209072, 256T2090, GT172, GT272, GT372, GT472, GT572 with 63kA Contingent $0
Dominion b3800.235 Replace 5 overdutied 230kV breakers at Loudoun substation with 80kA breakers Contingent $0
Dominion b3800.334 Replace four (4) overdutied 230 kV breakers at Loudoun Substation with 80 kA breakers. Contingent $0
Dominion b3800.407 Replace Loudoun 230 kV breakers 204552 and 217352 with breakers rated 80 kA. Contingent $0
Dominion b4000.119 Loudoun Cap Substation 230kV - replace 50 kA breaker SC352 with 63 kA. Contingent $0
Dominion b4000.128 North Anna Substation 500 kV - replace 40 kA breakers 57502, G102-1, G102-2, G202, G2T575, and XT573 with 63 kA. Contingent $0
Dominion b3800.408 Replace Ox 230 kV breakers 22042, 24342, 24842, 220T2063, 243T2097, 248T2013, and H342 with breakers rated 80 kA. Contingent $0
Dominion s2609.6 Upgrade two (2) 230 kV breakers 201342 and L142 from 50 kA to 63 kA at Ox Substation due to an insufficient breaker duty rating with the expansion in place. Contingent $0
Dominion s2609.9 Upgrade 230 kV Pleasant View breakers L3T203 and L3T2180 from 50 kA to 80 kA. Contingent $0
Dominion b4000.134 Remington Substation 230 kV - replace 40 kA and 50 kA breakers 211462, GT162, GT262, GT362, GT462, 2077T2086, 208662, H962, and H9T299 with 63 kA. Contingent $0
Dominion b1696 Install a breaker and a half scheme with a minimum of eight 230 kV breakers for five existing lines at Idylwood 230 kV: 20212 and 20712 Contingent $0
Dominion b3800.236 Replace 2 overdutied 500kV breakers at Ox Substation with 63kA breakers. Contingent $0
Dominion s3047.2 Install two (2) 1400 MVA 500-230 kV transformers at Vint Hill Substation and loop 500 kV line #535 and #569 into the proposed 500 kV ring bus at Vint Hill Substation. Contingent $0
Dominion b3800.312 Rebuild 500 kV Line #569 Loudoun - Morrisville to accommodate the new 500 kV line in the existing right-of-way. Contingent $0
Dominion b3800.313 Rebuild approximately 10.29 miles line segment of Line #535 (Meadow Brook to Loudoun) to accommodate the new 500 kV line in the existing ROW. Contingent $0
Dominion b3800.356 Build a new 500 kV line from Vint Hill to Wishing Star. Contingent $0
Dominion b3800.357 Build a new 500 kV line from Morrisville to Vint Hill. Contingent $0
Dominion b3800.354 Install terminal equipment at Wishing Star Substation to support a 5000A line to Vint Hill. Update relay settings for 500 kV Lines #546 and #590. Contingent $0
Dominion b3800.335 Replace 1 overdutied 500kV breaker at Ox Substation with a 63kA breaker Contingent $0
Region Topology Upgrade Total: $23,387,091

Attachments

AF2-120 One Line Diagram

AF2-120 One Line Diagram.jpg

[1]Winter load flow analysis will be performed starting in Transition Cycle 2.