AG2-029 Phase I Study Report

v1.00 released 2025-10-29 20:49

Forest G. Hipple-Collingwood 345 kV

39.0 MW Capacity / 300.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Southern Pike Solar LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the American Electric Power zone — Noble County, Indiana. The installed facilities will have a total capability of 300.0 MW with 39.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-029
Project Name:
Forest G. Hipple-Collingwood 345 kV
Project Developer Name:
Southern Pike Solar LLC
State:
Indiana
County:
Noble
Transmission Owner:
American Electric Power
MFO:
300.0
MWE:
300.0
MWC:
39.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-029 will interconnect on the American Electric Power transmission system by tapping the Forest G. Hipple - Dunton Lake 345 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-029 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-029Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$31,735,000$31,735,000
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$114,010,999$114,010,999
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$145,745,999$145,745,999

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-029

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-029 Project due at DP1
ABA - B
AG2-029$14,574,600$1,200,000$13,374,600

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will construct a new breaker and a half station, initially populated with 3 breakers and operated as a ring bus as well as the associated facilities required to support the interconnection.$31,735,000 $31,735,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 30 to 36 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Remote end work required on a Facility owned by a non-PJM Transmission Owner:

 

Please note that your project interconnects directly to an AEP (PJM Transmission Owner) facility which shares a tie line with NIPSCO (non-PJM Transmission Owner). The Transmission Owner Scope of Work above outlines the interconnection facilities required on the AEP facilities. Your project will also require upgrades at the remote end NIPSCO facility.  It is your responsibility to engage with NIPSCO regarding the upgrade work required to accommodate this interconnection.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-029 was evaluated as a 300.0 MW (39.0 MW Capacity) injection in the AEP area.

AG2-029 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 300.0 MW (300.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC120.65 %3792.0B4574.964.21
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC120.64 %3792.0B4574.634.21
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC139.36 %3792.0B5284.614.08
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC139.32 %3792.0B5282.914.08
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-024_SRT-A
BreakerAC132.75 %3729.0B4950.2731.85
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-025_SRT-A
BreakerAC131.94 %3729.0B4919.9331.76
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-015_SRT-A
BreakerAC131.63 %3729.0B4908.4731.75
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-014_SRT-A
BreakerAC131.63 %3729.0B4908.4731.75
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC130.62 %3729.0B4870.984.79
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.23 %3729.0B4856.2632.39
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.1 %3729.0B4627.64.62
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-008B_SRT-SL
BreakerAC168.3 %1683.0B2832.5218.32
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-013_SRT-SL
BreakerAC146.58 %1683.0B2466.9918.98
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-014_SRT-A
BreakerAC146.58 %1683.0B2466.9718.98
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-009_SRT-A
BreakerAC146.4 %1683.0B2463.9918.96
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-602_SRT-A
SingleAC142.52 %1683.0B2398.592.87
GD2ATSI
02BEAVER-02CARLIL 345.0 kV Ckt 1 line
ATSI_P7-1_OEC-345-002_SRT-A
TowerAC109.31 %1745.0B1907.4514.08
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-901_SRT-SL
BreakerAC113.76 %1720.0B1956.713.03
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-007A_SRT-SL
BreakerAC104.78 %1878.0B1967.8213.03
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-031_SRT-A
BreakerAC100.84 %1878.0B1893.7212.95
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-002_SRT-A
BreakerAC174.17 %1878.0B3270.9318.11
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-003_SRT-SL
BreakerAC104.76 %1878.0B1967.4813.11
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-028_SRT-A
BreakerAC101.37 %1878.0B1903.6513.01
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-005_SRT-A
BreakerAC149.08 %1892.0B2820.5916.5
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-006_SRT-SL
BreakerAC146.41 %1892.0B2770.1216.63
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010A_SRT-SL
BreakerAC144.5 %1892.0B2733.8816.63
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC136.86 %1892.0B2589.312.51
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC136.39 %1892.0B2580.582.51
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-F1_SRT-A
BreakerAC155.03 %1646.0B2551.8416.14
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-12_SRT-A
BreakerAC155.03 %1646.0B2551.8416.14
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010B1_SRT-SL
BreakerAC153.46 %1646.0B2525.9415.94
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010B2_SRT-SL
BreakerAC153.46 %1646.0B2525.9415.94
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-3_SRT-A
BreakerAC151.55 %1646.0B2494.5716.05
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-810_SRT-A
SingleAC136.64 %1646.0B2249.012.41
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC128.94 %1646.0B2122.342.39
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-005_SRT-A
BreakerAC146.75 %1878.0B2755.8916.89
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-006_SRT-SL
BreakerAC144.08 %1878.0B2705.7417.12
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010A_SRT-SL
BreakerAC142.21 %1878.0B2670.7617.04
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC136.05 %1878.0B2554.952.57
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC135.68 %1878.0B2548.092.58
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-007_SRT-SL
BreakerAC137.87 %1878.0B2589.1918.73
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-004_SRT-A
BreakerAC118.2 %1878.0B2219.819.39
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-005_SRT-SL
BreakerAC118.2 %1878.0B2219.7319.39
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-006_SRT-SL
BreakerAC118.2 %1878.0B2219.7319.39
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-601_SRT-A
SingleAC113.99 %1878.0B2140.732.93
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-021_SRT-A-1
TowerAC109.02 %1878.0B2047.4316.71
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC132.08 %1737.0B2294.2536.41
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC127.28 %1737.0B2210.8336.79
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC125.14 %1737.0B2173.6435.82
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC121.78 %1737.0B2115.35.56
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC102.67 %1737.0B1783.4130.65
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC117.99 %1302.0B1536.2315.43
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC110.86 %1302.0B1443.4516.06
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC103.45 %1302.0B1346.9213.82
GD2AEP
05FLTLCK-05GAVIN_RF 765.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC103.34 %4349.0B4494.0840.66
GD2AEP
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC101.83 %1301.0B1324.8115.72
GD2AEP
05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC106.88 %4571.0B4885.665.59
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC124.65 %1409.0B1756.3514.51
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC124.16 %1409.0B1749.3614.48
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC124.05 %1409.0B1747.9114.48
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC112.44 %1409.0B1584.2714.42
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC112.42 %1409.0B1584.0514.42
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7216_05VASSEL 765_B1_SRT-A
BreakerAC102.74 %1409.0B1447.5414.24
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#709_546_SRT-A
SingleAC118.09 %3039.0B3588.672.9
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC127.46 %2826.0B3601.922.9
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-024_SRT-A
BreakerAC134.01 %3792.0B5081.5231.85
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-025_SRT-A
BreakerAC133.21 %3792.0B5051.231.76
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-015_SRT-A
BreakerAC132.9 %3792.0B5039.6931.75
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-014_SRT-A
BreakerAC132.9 %3792.0B5039.6931.75
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.92 %3792.0B5002.284.79
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC131.49 %3792.0B4985.9832.39
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.38 %3792.0B4754.334.62
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC124.95 %4142.0B5175.3936.88
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC120.6 %4142.0B4995.0937.39
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC120.39 %4142.0B4986.3737.28
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC120.3 %4142.0B4982.8237.23
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.76 %4142.0B4919.185.63
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC132.07 %2246.0B2966.3335.52
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC128.1 %2246.0B2877.1135.91
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC126.64 %2246.0B2844.2434.94
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC120.12 %2246.0B2697.985.43
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC109.44 %2246.0B2457.9629.77
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC105.16 %2246.0B2361.8929.68
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC135.19 %4142.0B5599.5637.15
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC132.22 %4142.0B5476.6537.43
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC132.17 %4142.0B5474.4937.39
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC132.15 %4142.0B5473.5537.38
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.8 %4142.0B5417.865.65
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P4_#706_05GAVIN 765_C1_SRT-A
BreakerAC116.53 %4142.0B4826.4843.34
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC114.0 %4142.0B4722.066.55
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC108.04 %4142.0B4474.9132.26
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC107.84 %4142.0B4466.8934.05
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC104.56 %4142.0B4331.0831.9
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT5_SRT-SL
BusAC103.79 %4142.0B4298.8631.91
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Base Case
SingleAC100.2 %4142.0A4150.444.83
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC134.69 %4571.0B6156.8737.21
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC132.13 %4571.0B6039.5637.45
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC132.1 %4571.0B6038.2937.43
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC132.09 %4571.0B6037.7337.43
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.64 %4571.0B5971.435.66
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC116.18 %4571.0B5310.776.73
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Base Case
SingleAC114.73 %4047.0A4643.024.84
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P7-1_#10944___SRT-A
TowerAC111.6 %4571.0B5101.332.37
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC109.99 %4571.0B5027.5133.99
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC107.3 %4571.0B4904.4731.97
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P2-2_WP-500-DRT5_SRT-SL
BusAC106.58 %4571.0B4871.6831.99
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC134.71 %4571.0B6157.3837.21
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC132.15 %4571.0B6040.6737.45
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC132.12 %4571.0B6039.437.43
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC132.11 %4571.0B6038.8537.43
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.66 %4571.0B5972.545.66
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC116.43 %4571.0B5322.016.73
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Base Case
SingleAC114.86 %4047.0A4648.254.84
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC111.67 %4571.0B5104.5232.37
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC110.09 %4571.0B5032.3233.99
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC107.38 %4571.0B4908.3331.97
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT5_SRT-SL
BusAC106.67 %4571.0B4875.8931.99
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC166.87 %4142.0B6911.862.69
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC154.24 %4142.0B6388.4762.78
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC153.33 %4142.0B6350.8458.98
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC151.73 %4142.0B6284.859.12
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC145.65 %4142.0B6032.938.94
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#2995_05E LIMA 345_M_SRT-A
BreakerAC145.3 %4142.0B6018.3661.23
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P7-1_#11010___SRT-A
TowerAC141.23 %4142.0B5849.9360.64
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#6463_16757_SRT-A
SingleAC140.14 %4142.0B5804.669.25
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P7-1_#17567_SRT-SL
TowerAC140.03 %4142.0B5799.957.56
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
BusAC135.98 %4142.0B5632.1955.42
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A
BusAC135.75 %4142.0B5622.5755.45
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Base Case
SingleAC130.5 %4047.0A5281.198.07
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC142.73 %1868.0B2666.2635.76
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC137.89 %1868.0B2575.836.14
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC136.15 %1868.0B2543.2835.17
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC132.35 %1868.0B2472.275.46
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC115.52 %1868.0B2158.030.01
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC110.54 %1868.0B2064.9729.92
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7443_05DUMONT 765_A_SRT-A
BreakerAC116.16 %3097.0B3597.5549.52
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7442_05SORENS 765_K2_SRT-A
BreakerAC116.09 %3097.0B3595.3149.4
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7444_05DUMONT 765_A2_SRT-A
BreakerAC115.9 %3097.0B3589.5649.56
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P1-2_#7442_200545_SRT-A
SingleAC111.07 %3097.0B3439.747.47
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC125.19 %5523.0B6914.1262.69
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC115.15 %5523.0B6359.9162.78
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC114.88 %5523.0B6345.0358.98
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC113.61 %5523.0B6274.5659.12
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC109.05 %5523.0B6022.778.94
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P4_#2995_05E LIMA 345_M_SRT-A
BreakerAC108.54 %5523.0B5994.8861.23
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P7-1_#11010___SRT-A
TowerAC105.44 %5523.0B5823.6860.64
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#6463_16757_SRT-A
SingleAC104.68 %5523.0B5781.39.25
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P7-1_#17567_SRT-SL
TowerAC104.6 %5523.0B5777.1857.56
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
BusAC101.5 %5523.0B5605.7955.42
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A
BusAC101.3 %5523.0B5594.7855.45
GD2AEP
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC113.98 %6066.0B6914.1262.69
GD2AEP
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC105.32 %6066.0B6388.4762.78
GD2AEP
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC104.7 %6066.0B6350.8458.98
GD2AEP
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC103.61 %6066.0B6284.859.12
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
BusAC128.08 %2317.0B2967.7116.05
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
BreakerAC128.08 %2317.0B2967.5516.05
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC118.23 %2317.0B2739.42.15
GD2ATSI/METC
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-034T_SRT-A
BreakerAC108.58 %1793.0B1946.8115.55
GD2ATSI/METC
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-033T_SRT-A
BreakerAC108.35 %1793.0B1942.6515.29
GD2ATSI/ITCT
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-023T_SRT-SL
BreakerAC117.29 %1660.0B1946.9416.4
GD2ATSI/ITCT
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-022T_SRT-A
BreakerAC117.16 %1660.0B1944.8516.4
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-009_SRT-SL
BreakerAC165.39 %1499.0B2479.1515.9
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-12_SRT-A
BreakerAC145.45 %1798.0B2615.2616.09
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-F1_SRT-A
BreakerAC145.45 %1798.0B2615.2616.09
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-3_SRT-A
BreakerAC142.16 %1798.0B2556.0115.99
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010B1_SRT-SL
BreakerAC141.11 %1798.0B2537.1815.88
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-810_SRT-A
SingleAC123.08 %1798.0B2212.912.4
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC117.76 %1798.0B2117.362.38
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC150.17 %1868.0B2805.1435.76
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC145.37 %1868.0B2715.5236.14
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC143.67 %1868.0B2683.7335.17
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC138.82 %1868.0B2593.185.46
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC122.96 %1868.0B2296.8430.01
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC117.83 %1868.0B2201.0129.92
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P7-1_#11067___SRT-A
TowerAC104.58 %1868.0B1953.5629.71
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P7-1_#11068___SRT-A
TowerAC103.67 %1868.0B1936.629.46
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC101.68 %1868.0B1899.3928.45
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P2-2_#11848_05HAVILND2 69.0_2_SRT-A
BusAC100.29 %1868.0B1873.4928.71

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.96
MW Contribution:4.21
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270053AF1-130 C
Solar/Wind Harmer
1.432
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.63
MW Contribution:4.21
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270053AF1-130 C
Solar/Wind Harmer
1.432
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.36 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5284.61
MW Contribution:4.08
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.32 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5282.91
MW Contribution:4.08
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.75 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4950.27
MW Contribution:31.85
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270459AD2-067 GEN
Solar/Wind Harmer
10.252
961821AG1-024 GEN
Solar/Wind Harmer
10.408
270054AF2-122 C O1
Solar/Wind Harmer
3.995
972239AH1-704 GEN
Adder
2.671
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270156DARBY CT1
Adder
10.432
270157DARBY CT2
Adder
10.407
270158DARBY CT3
Adder
10.24
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270302AB2-170 GEN
Solar/Wind Harmer
9.566
270317AD1-130_GEN
Solar/Wind Harmer
3.667
270269AC2-059
Solar/Wind Harmer
10.62
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
958581AF2-149 GEN
Solar/Wind Harmer
4.732
970179AG2-119 GEN
Solar/Wind Harmer
8.844
970879AG2-548 GEN
Solar/Wind Harmer
4.736
253372AE2-315 SEC3
Adder
2.071
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
253349AC2-067 GEN
Solar/Wind Harmer
5.421
253400AC2-068 GEN
Solar/Wind Harmer
2.18
957201AF2-014 GEN
Solar/Wind Harmer
4.91
270435AC2-044 GEN
Solar/Wind Harmer
2.165
965051AG1-369 GEN
Solar/Wind Harmer
5.38
965041AG1-368 GEN
Solar/Wind Harmer
10.749
247607V1-011 GEN
Solar/Wind Harmer
4.249
24729505KEY G4
Adder
6.948
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971567AH1-282 GEN
Solar/Wind Harmer
16.053
966831AG1-554 GEN
Solar/Wind Harmer
1.28
270119AB2-067 GEN1
50/50
7.1
270120AB2-067 GEN2
50/50
7.1
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
970077AG2-063 GEN
Solar/Wind Harmer
6.25
270224U2-072_GEN2
Solar/Wind Harmer
2.287
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
270518AE2-148 GEN
Solar/Wind Harmer
13.911
253378AE2-206_GEN
Solar/Wind Harmer
4.016
276820AF1-078_GEN
Solar/Wind Harmer
1.784
972159AH1-661 GEN
Adder
1.111
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
970879AG2-548 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
970611AG2-400 GEN
Solar/Wind Harmer
10.775
971231AH1-075 GEN
Solar/Wind Harmer
0.862
270007AE1-245 C
Solar/Wind Harmer
6.374
942801AE2-298 GEN
Solar/Wind Harmer
1.626
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
960971AF2-388 GEN
Solar/Wind Harmer
11.659
942221AE2-234 GEN
Solar/Wind Harmer
0.781
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.634
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270071AF1-092 GEN
Solar/Wind Harmer
16.048
971985AH1-537 GEN
Solar/Wind Harmer
19.051
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270024AE2-089 GEN
Solar/Wind Harmer
5.004
965101AG1-375 GEN
Solar/Wind Harmer
10.653
270367AC2-061_GEN
Solar/Wind Harmer
3.388
24318805MLG1
50/50
10.158
23559001PLEAS1
50/50
6.365
270051AF1-062 GEN
50/50
11.843
270475AD2-096_GEN
50/50
7.165
970153AG2-106 GEN
Solar/Wind Harmer
17.953
961921AG1-034 GEN
Solar/Wind Harmer
15.612
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
942051AE2-217 GEN
Solar/Wind Harmer
21.08
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253338AC1-165 GEN
Solar/Wind Harmer
1.243
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.692
270273AD2-016 GEN
Solar/Wind Harmer
3.037
972173AH1-669 GEN
Solar/Wind Harmer
5.679
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
957541AF2-048 GEN
Solar/Wind Harmer
1.724
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
971191AH1-055 GEN
Solar/Wind Harmer
23.759
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270191TR4_S_V150
Solar/Wind Harmer
3.232
270247TR4_N_V136
Solar/Wind Harmer
0.916
959331AF2-224 GEN
Solar/Wind Harmer
10.775
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
270588AE1-091_GEN
Solar/Wind Harmer
11.804
944531AF1-118 GEN
Solar/Wind Harmer
37.541
270043AE2-236 GEN
Solar/Wind Harmer
5.893
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
25196608WSDLE5
Adder
9.114
962031AG1-047 GEN
Solar/Wind Harmer
3.214
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
25194608D.CRK4
Adder
1.747
270222AC2-111 GEN
Solar/Wind Harmer
8.657
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270044AE2-322 C
Solar/Wind Harmer
1.394
270404AC1-167 GEN
Solar/Wind Harmer
1.161
24642205MAYFLWER
Adder
0.667
25196008MFTGT1
Adder
1.411
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
274753CRETE EC ;3U
Adder
8.515
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
24728705AND G3
Adder
8.251
24728505AND G1
Adder
3.945
274826FISK ;BP
Adder
11.256
274800UNIV PARK;3U
Adder
5.993
972038AH1-567 GEN2
Adder
0.375
972228AH1-698 GEN2
Adder
3.807
274676JOLIET 29;8U
Adder
30.322
274729ELWOOD EC;1P
Adder
16.844
274730ELWOOD EC;6P
Adder
16.844
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238118U2-030_1
Solar/Wind Helper
0.344
238127S14_GEN_2
Solar/Wind Helper
0.832
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237080AD1-060 GEN
Solar/Wind Helper
0.343
237038AE2-054 C
Solar/Wind Helper
0.273
235062AE1-101 C1
Solar/Wind Helper
1.665
23779801AA1-109
Solar/Wind Helper
0.194
237048AF1-022 C
Solar/Wind Helper
0.179
223401AF1-299 GEN
Solar/Wind Helper
0.369
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.078
233930AB2-032 GEN
Solar/Wind Helper
0.382
233915AB1-141 GEN
Solar/Wind Helper
0.504
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.149
230434AG1-499 GEN
Solar/Wind Helper
0.231
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.577
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
202652Y1-033 WT C
Solar/Wind Helper
0.5
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
270166AC1-044 GEN3
50/50
7.1
23559101PLEAS2
50/50
6.365
962761AG1-125 GEN
Solar/Wind Harmer
41.173
970149AG2-104 GEN
Solar/Wind Harmer
50.849
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
253343AC1-166 GEN
Solar/Wind Harmer
1.243
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270462AD2-086
Solar/Wind Harmer
7.958
971995AH1-542 GEN
Solar/Wind Harmer
12.515
270263AC1-001 GEN
Solar/Wind Harmer
1.179
25326309TAIT D
Adder
1.2
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
927014AC1-188 GEN
Solar/Wind Harmer
1.729
241813AF1-122_GEN
Solar/Wind Harmer
6.978
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965421AG1-410 GEN
Solar/Wind Harmer
32.464
960001AF2-291 GEN
Solar/Wind Harmer
3.264
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
965011AG1-365 GEN
Solar/Wind Harmer
10.775
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
958861AF2-177 GEN
Solar/Wind Harmer
11.644
247536S-71 GEN
Solar/Wind Harmer
4.305
25194608D.CRK4
Adder
1.747
945371AF1-202 GEN
Solar/Wind Harmer
7.414
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
25196808ZIMRHP
Adder
80.055
24639705ELKHART HY
Adder
0.162
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274754CRETE EC ;4U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274801UNIV PARK;4U
Adder
5.993
274676JOLIET 29;8U
Adder
31.445
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
274745AC1-111 GEN9
Adder
5.705
970091AG2-072 GEN
Adder
78.03
316095T157 G97
Solar/Wind Helper
1.508
23583801GRNGAP
Solar/Wind Helper
5.618
238185AF2-356 C
Solar/Wind Helper
2.662
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
23562501BACKB
Solar/Wind Helper
1.017
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.498
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.347
223402AF1-300 C
Solar/Wind Helper
0.369
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233982AB2-133 GEN
Solar/Wind Helper
0.359
233994AC2-023 GEN
Solar/Wind Helper
0.965
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.359
230430AE1-229_GEN
Solar/Wind Helper
3.385
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
24728905RICHG2
Adder
3.981
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
274803UNIV PARK;6U
Adder
5.997
972259AH1-714 GEN
Adder
19.596
274674JOLIET 9 ;6U
Adder
15.776
274696ROCKY RD ;4P
Adder
11.59
274695ROCKY RD ;2P
Adder
11.323
274693ROCKY RD ;1P
Adder
11.211
274697ROCKY RD ;3P
Adder
3.076
23585401KL_K28_T16
Solar/Wind Helper
1.493
238120AE2-309 GEN
Solar/Wind Helper
0.528
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.72
20390526W1-045 C
Solar/Wind Helper
0.351
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.509
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
233970AC1-092 C
Solar/Wind Helper
0.351
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.327
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
203955AF1-039 C O1
Solar/Wind Helper
0.33
970321AG2-212 GEN
Solar/Wind Harmer
4.981
971673AH1-337 GEN
Solar/Wind Harmer
4.893
971029AG2-637 GEN
Solar/Wind Harmer
15.954
252524AE2-267 GEN
Solar/Wind Harmer
1.677
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
25196508WSDLE4
Adder
9.021
270543AE2-219 C
Solar/Wind Harmer
5.445
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
270297AD1-101 GEN
Solar/Wind Harmer
2.953
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274775LINCOLN ;6U
Adder
8.715
274776LINCOLN ;7U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274811UNIV PK N;7U
Adder
5.162
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274735ELWOOD EC;4P
Adder
16.844
274728ELWOOD EC;5P
Adder
16.844
972203AH1-686 GEN
Adder
2.356
274746AC1-111 G10
Adder
5.705
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.832
238152AF2-075_GEN
Solar/Wind Helper
0.709
238208AF1-136 C
Solar/Wind Helper
0.221
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.655
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
23750501ELLIOTTS
Solar/Wind Helper
0.644
959381AF2-229 GEN
Solar/Wind Helper
0.359
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.511
205932AD2-116_GEN
Solar/Wind Helper
0.511
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.508
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
MECLTFEXP_MEC->PJM
CLTF
15.978
SIGELTFEXP_SIGE->PJM
CLTF
0.507
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
TVALTFEXP_TVA->PJM
CLTF
7.337
CPLELTFEXP_CPLE->PJM
CLTF
0.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
NYPJM->LTFIMP_NY
CLTF
4.819
LGEELTFEXP_LGEE->PJM
CLTF
6.781
WECLTFEXP_WEC->PJM
CLTF
3.842
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.94 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4919.93
MW Contribution:31.76
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.115
23559001PLEAS1
50/50
6.183
270051AF1-062 GEN
50/50
11.828
270475AD2-096_GEN
50/50
7.148
970153AG2-106 GEN
Solar/Wind Harmer
17.883
961921AG1-034 GEN
Solar/Wind Harmer
15.599
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
942051AE2-217 GEN
Solar/Wind Harmer
21.044
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.241
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.032
972173AH1-669 GEN
Solar/Wind Harmer
5.669
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
970065AG2-057 GEN
Solar/Wind Harmer
1.09
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
971191AH1-055 GEN
Solar/Wind Harmer
23.693
270377AD1-106 GEN
Solar/Wind Harmer
6.649
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270191TR4_S_V150
Solar/Wind Harmer
3.224
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.746
965021AG1-366 GEN
Solar/Wind Harmer
2.499
958091AF2-103 GEN
Solar/Wind Harmer
0.173
270166AC1-044 GEN3
50/50
7.072
23559101PLEAS2
50/50
6.183
962761AG1-125 GEN
Solar/Wind Harmer
41.012
970149AG2-104 GEN
Solar/Wind Harmer
50.65
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.241
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.502
270263AC1-001 GEN
Solar/Wind Harmer
1.177
25326309TAIT D
Adder
1.197
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
241813AF1-122_GEN
Solar/Wind Harmer
6.974
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.386
960001AF2-291 GEN
Solar/Wind Harmer
3.255
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.746
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
958861AF2-177 GEN
Solar/Wind Harmer
11.61
247536S-71 GEN
Solar/Wind Harmer
4.293
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.392
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
25196808ZIMRHP
Adder
79.831
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274754CRETE EC ;4U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274801UNIV PARK;4U
Adder
5.975
274676JOLIET 29;8U
Adder
31.348
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
274745AC1-111 GEN9
Adder
5.687
970091AG2-072 GEN
Adder
77.755
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.606
238185AF2-356 C
Solar/Wind Helper
2.651
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
23562501BACKB
Solar/Wind Helper
1.01
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.728
270588AE1-091_GEN
Solar/Wind Harmer
11.789
944531AF1-118 GEN
Solar/Wind Harmer
37.432
270043AE2-236 GEN
Solar/Wind Harmer
5.876
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
25196608WSDLE5
Adder
9.089
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.632
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270044AE2-322 C
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
274753CRETE EC ;3U
Adder
8.489
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
24728705AND G3
Adder
8.226
274802UNIV PARK;5U
Adder
5.978
24728505AND G1
Adder
3.933
274826FISK ;BP
Adder
11.221
274800UNIV PARK;3U
Adder
5.975
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.796
274676JOLIET 29;8U
Adder
30.228
274729ELWOOD EC;1P
Adder
16.792
274730ELWOOD EC;6P
Adder
16.792
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238118U2-030_1
Solar/Wind Helper
0.342
238127S14_GEN_2
Solar/Wind Helper
0.829
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.178
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
232434Z2-077 GEN
Solar/Wind Helper
0.127
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.06
207445AB1-138_GEN
Solar/Wind Helper
0.104
270119AB2-067 GEN1
50/50
7.072
270120AB2-067 GEN2
50/50
7.072
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
970077AG2-063 GEN
Solar/Wind Harmer
6.239
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972269AH1-719 GEN
Adder
2.575
972159AH1-661 GEN
Adder
1.116
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
971201AH1-060 GEN
Solar/Wind Harmer
2.179
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
960971AF2-388 GEN
Solar/Wind Harmer
11.625
942221AE2-234 GEN
Solar/Wind Harmer
0.779
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.605
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194408D.CRK1
Adder
8.014
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
24728905RICHG2
Adder
3.969
274770LINCOLN ;1U
Adder
8.688
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
274803UNIV PARK;6U
Adder
5.978
972259AH1-714 GEN
Adder
19.535
274674JOLIET 9 ;6U
Adder
15.727
274696ROCKY RD ;4P
Adder
11.554
274695ROCKY RD ;2P
Adder
11.287
274693ROCKY RD ;1P
Adder
11.176
274697ROCKY RD ;3P
Adder
3.066
23585401KL_K28_T16
Solar/Wind Helper
1.485
238120AE2-309 GEN
Solar/Wind Helper
0.526
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
962771AG1-126 GEN
Solar/Wind Harmer
41.012
972239AH1-704 GEN
Adder
2.683
270459AD2-067 GEN
Solar/Wind Harmer
10.243
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
945631AF1-228 GEN
Solar/Wind Harmer
5.461
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
270158DARBY CT3
Adder
10.225
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.66
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.736
970179AG2-119 GEN
Solar/Wind Harmer
8.837
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.728
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
253349AC2-067 GEN
Solar/Wind Harmer
5.408
253400AC2-068 GEN
Solar/Wind Harmer
2.175
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.366
965041AG1-368 GEN
Solar/Wind Harmer
10.722
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
966831AG1-554 GEN
Solar/Wind Harmer
1.279
971989AH1-539 GEN
Solar/Wind Harmer
13.833
24729505KEY G4
Adder
6.928
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270071AF1-092 GEN
Solar/Wind Harmer
16.001
971985AH1-537 GEN
Solar/Wind Harmer
18.998
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.99
270367AC2-061_GEN
Solar/Wind Harmer
3.379
965101AG1-375 GEN
Solar/Wind Harmer
10.622
971673AH1-337 GEN
Solar/Wind Harmer
4.88
252524AE2-267 GEN
Solar/Wind Harmer
1.673
971029AG2-637 GEN
Solar/Wind Harmer
15.909
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
25196508WSDLE4
Adder
8.996
270543AE2-219 C
Solar/Wind Harmer
5.43
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.688
274776LINCOLN ;7U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274811UNIV PK N;7U
Adder
5.147
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
274735ELWOOD EC;4P
Adder
16.792
274728ELWOOD EC;5P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274746AC1-111 G10
Adder
5.687
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.829
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.651
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.64
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
233990AG1-397 GEN
Solar/Wind Helper
0.03
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.501
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.728
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
209116AE2-175 GEN
Solar/Wind Helper
1.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
MECLTFEXP_MEC->PJM
CLTF
15.925
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
TVALTFEXP_TVA->PJM
CLTF
7.306
CPLELTFEXP_CPLE->PJM
CLTF
0.632
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.759
WECLTFEXP_WEC->PJM
CLTF
3.83
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:31.75
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:31.75
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.62 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4870.98
MW Contribution:4.79
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.23 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4856.26
MW Contribution:32.39
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
270119AB2-067 GEN1
50/50
7.033
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.1 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4627.6
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-008B_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-008B_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:168.3 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2832.52
MW Contribution:18.32
Bus #Bus NameTypeMW Contribution
972211AH1-690 GEN
50/50
441.807
23888502TROY G1
50/50
1.502
23888602TROY G2
50/50
1.502
970817AG2-515 GEN
Solar/Wind Harmer
14.047
945411AF1-206 GEN
Solar/Wind Harmer
8.225
945641AF1-229 GEN
Solar/Wind Harmer
3.751
270499AE1-146 GEN
Solar/Wind Harmer
2.271
971549AH1-272 GEN
Solar/Wind Harmer
14.989
270297AD1-101 GEN
Solar/Wind Harmer
1.998
944161AF1-084 GEN
Solar/Wind Harmer
1.473
957201AF2-014 GEN
Solar/Wind Harmer
2.92
270435AC2-044 GEN
Solar/Wind Harmer
1.288
247607V1-011 GEN
Solar/Wind Harmer
2.525
971771AH1-392 GEN
Solar/Wind Harmer
5.464
965041AG1-368 GEN
Solar/Wind Harmer
6.053
965051AG1-369 GEN
Solar/Wind Harmer
3.001
23929302BS-PKR
50/50
2.743
241832AE2-181_GEN
Solar/Wind Harmer
1.964
958321AF2-126 GEN
Solar/Wind Harmer
1.44
23906502RICHG2&3
Adder
1.317
270541AE2-072 C
Solar/Wind Harmer
4.336
270575GUS2 35KV
Solar/Wind Harmer
9.524
970217AG2-149 GEN
Solar/Wind Harmer
24.156
247604X1-042
Adder
0.294
270044AE2-322 C
Solar/Wind Harmer
0.914
270404AC1-167 GEN
Solar/Wind Harmer
0.761
24441205WTRV SLR C
Solar/Wind Harmer
0.093
270258AD1-119 GEN
Solar/Wind Harmer
1.873
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
945111AF1-176 GEN
Solar/Wind Harmer
3.628
958091AF2-103 GEN
Solar/Wind Harmer
0.103
270588AE1-091_GEN
Solar/Wind Harmer
7.012
24642205MAYFLWER
Adder
0.396
247643Z2-116 C
Solar/Wind Harmer
0.043
970031AG2-029 GEN
Solar/Wind Harmer
18.318
270191TR4_S_V150
Solar/Wind Harmer
1.803
270247TR4_N_V136
Solar/Wind Harmer
0.511
959331AF2-224 GEN
Solar/Wind Harmer
5.881
965021AG1-366 GEN
Solar/Wind Harmer
1.368
270485AE1-090_GEN
Solar/Wind Harmer
0.345
970349AG2-230 GEN
Solar/Wind Harmer
8.492
270043AE2-236 GEN
Solar/Wind Harmer
3.088
270535AF1-215 GEN1
Solar/Wind Harmer
2.437
942871AE2-306 GEN
Solar/Wind Harmer
0.48
270391AF1-285 GEN3
Solar/Wind Harmer
0.246
972231SS25-0005
Solar/Wind Harmer
5.018
972181SS23-001
Solar/Wind Harmer
3.136
274752CRETE EC ;2U
Adder
2.584
274753CRETE EC ;3U
Adder
2.584
964401AG1-302 GEN
Solar/Wind Harmer
4.779
274724RIVER EC ;11
Adder
9.288
959141AF2-205 GEN
Solar/Wind Harmer
3.132
274802UNIV PARK;5U
Adder
3.011
274826FISK ;BP
Adder
5.644
274800UNIV PARK;3U
Adder
3.001
972038AH1-567 GEN2
Adder
0.188
276772AC2-154 GEN
Solar/Wind Harmer
1.433
276806AD2-047 C O1
Solar/Wind Harmer
5.498
970941AG2-585 GEN
Solar/Wind Harmer
6.424
274772LINCOLN ;3U
Adder
3.184
972228AH1-698 GEN2
Adder
1.898
274676JOLIET 29;8U
Adder
15.079
276897AD1-100 C
Solar/Wind Harmer
14.775
939351AE1-166 GEN
Solar/Wind Harmer
3.019
276893AG1-478 C
Solar/Wind Harmer
0.213
274729ELWOOD EC;1P
Adder
8.363
274730ELWOOD EC;6P
Adder
8.363
274734ELWOOD EC;8P
Adder
8.363
274736ELWOOD EC;9P
Adder
8.363
970707AG2-453 GEN
Solar/Wind Harmer
14.243
970513AG2-328 GEN
Solar/Wind Harmer
9.047
970517AG2-330 GEN
Solar/Wind Harmer
8.206
966831AG1-554 GEN
Solar/Wind Harmer
0.715
971989AH1-539 GEN
Solar/Wind Harmer
7.733
971769AH1-391 GEN
Solar/Wind Harmer
5.922
270302AB2-170 GEN
Solar/Wind Harmer
4.775
270317AD1-130_GEN
Solar/Wind Harmer
1.83
960681AF2-359 GEN
Solar/Wind Harmer
2.151
971347AH1-153 GEN
Solar/Wind Harmer
8.492
963791AG1-232 GEN
Solar/Wind Harmer
7.348
971567AH1-282 GEN
Solar/Wind Harmer
8.122
270536AF1-215 GEN2
Solar/Wind Harmer
2.437
270578AF1-285 GEN2
Solar/Wind Harmer
0.246
274814UNIV PK N;0U
Adder
2.638
274807UNIV PK N;3U
Adder
2.632
274805UNIV PK N;1U
Adder
2.621
274811UNIV PK N;7U
Adder
2.615
270071AF1-092 GEN
Solar/Wind Harmer
7.832
958391AF2-133 GEN
Solar/Wind Harmer
4.734
972037AH1-567 GEN1
Adder
0.095
274827FISK ;RP
Adder
4
960591AF2-350 GEN
Solar/Wind Harmer
5.139
274775LINCOLN ;6U
Adder
3.184
274776LINCOLN ;7U
Adder
3.184
274777LINCOLN ;8U
Adder
3.184
972227AH1-698 GEN1
Adder
1.336
274687WILL CNTY;4U
Adder
14.272
274687WILL CNTY;4U
Adder
14.272
274675JOLIET 29;7U
Adder
15.638
274675JOLIET 29;7U
Adder
15.08
274731ELWOOD EC;2P
Adder
8.363
274733ELWOOD EC;3P
Adder
8.363
274735ELWOOD EC;4P
Adder
8.363
274728ELWOOD EC;5P
Adder
8.363
970833AG2-524 GEN
Solar/Wind Harmer
4.42
970833AG2-524 GEN
Solar/Wind Harmer
2.056
274746AC1-111 G10
Adder
2.812
274744AC1-111 GEN8
Adder
2.812
274823ROCKFORD ;21
Adder
9.526
24729505KEY G4
Adder
3.155
241886AC2-103 GEN2
Solar/Wind Helper
6.897
241982AE2-343 S C
Solar/Wind Helper
0.125
254304AE2-114 C
Solar/Wind Helper
0.119
203846AF2-130 C
Solar/Wind Helper
0.261
241997AF1-093 GEN
Solar/Wind Helper
0.138
203804AE2-113_GEN
Solar/Wind Helper
0.91
24189902OREGON_CT2
50/50
4.092
23856402BAYSG1
50/50
1.558
23888702TROY G3
50/50
1.502
972253AH1-711 GEN
50/50
45.886
23920202STRYCT
50/50
1.896
241808AF1-120 C
Solar/Wind Harmer
1.228
241858AF1-205_GEN
Solar/Wind Harmer
5.333
241840AF1-064_GEN
Solar/Wind Harmer
1.343
972301AH1-735 GEN
Adder
6.599
23906402RICHG1
Adder
1.32
23906502RICHG2&3
Adder
1.317
270361_3
Solar/Wind Harmer
8.085
960841AF2-375 GEN
Solar/Wind Harmer
3.588
970515AG2-329 GEN
Solar/Wind Harmer
10.955
944231AF1-091 GEN
Solar/Wind Harmer
2.656
247522W1-056 GEN
Solar/Wind Harmer
1.562
270449AD2-020 GEN
Solar/Wind Harmer
1.841
943021AE2-325 GEN
Solar/Wind Harmer
2.392
246936BC-WTG1
Solar/Wind Harmer
2.519
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
945111AF1-176 GEN
Solar/Wind Harmer
11.446
270505AE1-170 C O1
Solar/Wind Harmer
9.623
965421AG1-410 GEN
Solar/Wind Harmer
19.155
24639705ELKHART HY
Adder
0.095
24695305TIMB G C
Solar/Wind Harmer
3.406
270063AE2-323 C
Solar/Wind Harmer
1.345
247521TR3_G114
Solar/Wind Harmer
2.021
270246TR4_N_V150
Solar/Wind Harmer
0.511
965011AG1-365 GEN
Solar/Wind Harmer
5.881
270462AD2-086
Solar/Wind Harmer
3.972
970373AG2-245 GEN
Solar/Wind Harmer
11.492
270055AF2-134 C O1
Solar/Wind Harmer
1.624
270223U2-072_GEN1
Solar/Wind Harmer
1.047
270578AF1-285 GEN2
Solar/Wind Harmer
0.64
270391AF1-285 GEN3
Solar/Wind Harmer
0.64
274751CRETE EC ;1U
Adder
2.584
274754CRETE EC ;4U
Adder
2.584
958381AF2-132 GEN
Solar/Wind Harmer
4.779
964861AG1-349 GEN
Solar/Wind Harmer
4.133
971917AH1-482 GEN
Solar/Wind Harmer
4.769
274723RIVER EC ;12
Adder
9.4
274812UNIV PK N;8U
Adder
2.615
276164X3-005 C
Solar/Wind Harmer
0.365
274801UNIV PARK;4U
Adder
3.001
276776AD2-060 GEN
Solar/Wind Harmer
0.217
972207SS24-0001
Solar/Wind Harmer
11.322
274773LINCOLN ;4U
Adder
3.184
274774LINCOLN ;5U
Adder
3.184
940581AE2-045 GEN
Solar/Wind Harmer
5.238
971605AH1-302 GEN
Solar/Wind Harmer
4.479
274676JOLIET 29;8U
Adder
15.638
941551AE2-152 GEN
Solar/Wind Harmer
2.309
274732ELWOOD EC;7P
Adder
8.363
274674JOLIET 9 ;6U
Adder
7.833
970245AG2-165 GEN
Solar/Wind Harmer
9.047
274871GR RIDGE ;2U
Solar/Wind Harmer
3.89
274745AC1-111 GEN9
Adder
2.812
276691AA1-018 GEN1
Solar/Wind Harmer
0.234
274682WAUKEGAN ;7U
Adder
8.98
274828WAUKEGAN ;BP
Adder
5.514
274822ROCKFORD ;11
Adder
9.595
972235AH1-702 GEN1
Adder
1.23
274761LEE CO EC;2U
Adder
4.495
274766LEE CO EC;7U
Adder
4.442
241885AC2-103 GEN1
Solar/Wind Helper
6.897
241807AE2-176_GEN
Solar/Wind Helper
1.674
961971AG1-040 GEN
Solar/Wind Helper
0.353
203835AF1-098 GEN
Solar/Wind Helper
1.392
203860AG1-193 C
Solar/Wind Helper
0.157
241966AE1-183 GEN
Solar/Wind Helper
0.138
254303AC2-168 GEN
Solar/Wind Helper
0.08
203954AE2-126 C
Solar/Wind Helper
0.229
24190002OREGON_ST1
50/50
5.505
24189802OREGON_CT1
50/50
4.176
23888802TROY G4
50/50
1.502
241996AE2-282_GEN
Solar/Wind Harmer
2.202
971677AH1-339 GEN
Solar/Wind Harmer
6.538
961051AF2-396 GEN
Solar/Wind Harmer
10.337
961051AF2-396 GEN
Solar/Wind Harmer
4.808
246938BC-WTG3
Solar/Wind Harmer
2.563
246937BC-WTG2
Solar/Wind Harmer
2.519
960981AF2-389 GEN
Solar/Wind Harmer
0.966
957891AF2-083 GEN
Solar/Wind Harmer
2.156
270007AE1-245 C
Solar/Wind Harmer
3.789
942801AE2-298 GEN
Solar/Wind Harmer
0.957
247620Y3-023
Adder
0.286
270216AD2-079_GEN
Solar/Wind Harmer
0.373
270526AF1-158 GEN
Solar/Wind Harmer
2.704
24441505OLIV SLR
Solar/Wind Harmer
0.079
970611AG2-400 GEN
Solar/Wind Harmer
5.881
965681AG1-436 GEN
Solar/Wind Harmer
7.117
965791AG1-447 GEN
Solar/Wind Harmer
3.641
270224U2-072_GEN2
Solar/Wind Harmer
1.047
270227U2-072_GEN3
Solar/Wind Harmer
1.047
270228U2-072_GEN4
Solar/Wind Harmer
1.047
270231U2-072_GEN5
Solar/Wind Harmer
1.047
274808UNIV PK N;4U
Adder
2.604
274803UNIV PARK;6U
Adder
3.011
274888KELLY CRK;1U
Solar/Wind Harmer
3.034
274887GEN-1.85
Solar/Wind Harmer
2.739
276843GEN-1.7
Solar/Wind Harmer
0.295
958011AF2-095 GEN
Solar/Wind Harmer
7.401
274770LINCOLN ;1U
Adder
3.184
274771LINCOLN ;2U
Adder
3.184
972259AH1-714 GEN
Adder
9.731
274674JOLIET 9 ;6U
Adder
7.833
970321AG2-212 GEN
Solar/Wind Harmer
9.047
274847GR RIDGE ;BU
Solar/Wind Harmer
2.559
958481AF2-142 GEN
Solar/Wind Harmer
7.542
274861TOP CROP ;1U
Solar/Wind Harmer
3.046
274862TOP CROP ;2U
Solar/Wind Harmer
2.544
942221AE2-234 GEN
Solar/Wind Harmer
0.367
274696ROCKY RD ;4P
Adder
5.693
274695ROCKY RD ;2P
Adder
5.562
274693ROCKY RD ;1P
Adder
5.507
274697ROCKY RD ;3P
Adder
1.511
274683WAUKEGAN ;8U
Adder
10.52
274683WAUKEGAN ;8U
Adder
8.868
274764LEE CO EC;5U
Adder
4.506
274765LEE CO EC;6U
Adder
4.506
274762LEE CO EC;3U
Adder
4.495
274763LEE CO EC;4U
Adder
4.453
972267AH1-718 GEN
Adder
1.998
247621Y3-024
Adder
0.11
25326509SID D
Adder
0.587
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.263
203979AG1-198 GEN
Solar/Wind Helper
0.205
241967AE2-285_GEN
Solar/Wind Helper
0.358
241801AE1-079 GEN
Solar/Wind Helper
0.139
241985AE1-237 GEN
Solar/Wind Helper
0.139
962101AG1-054 GEN
Solar/Wind Helper
0.345
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.117
971573AH1-285 GEN
Solar/Wind Harmer
0.202
943121AE2-341 GEN
Solar/Wind Harmer
7.543
943591AF1-030 GEN
Solar/Wind Harmer
5.029
276694AA1-018 GEN2
Solar/Wind Harmer
3.173
274682WAUKEGAN ;7U
Adder
8.98
972236AH1-702 GEN2
Adder
1.07
274760LEE CO EC;1U
Adder
4.495
274767LEE CO EC;8U
Adder
4.442
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.342
959441AF2-235 GEN
Solar/Wind Helper
0.155
254305AE2-115 C
Solar/Wind Helper
0.119
20334926Z1-069 C
Solar/Wind Helper
0.677
991182J1586 G
External Queue
28.11846351623535
990527J1329
External Queue
2.0234405994415283
990142J1224
External Queue
14.791350364685059
991177J1571 G
External Queue
15.792752265930176
CBM West 1LTFEXP_CBM-W1->PJM
CBM
109.741
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.094
MECLTFEXP_MEC->PJM
CLTF
7.274
SIGELTFEXP_SIGE->PJM
CLTF
0.188
LAGNLTFEXP_LAGN->PJM
CLTF
5.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.753
TVALTFEXP_TVA->PJM
CLTF
2.558
CPLELTFEXP_CPLE->PJM
CLTF
0.497
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.66
NYPJM->LTFIMP_NY
CLTF
2.102
LGEELTFEXP_LGEE->PJM
CLTF
2.253
WECLTFEXP_WEC->PJM
CLTF
1.864
AG2-052LTFEXP_AG2-052->PJM
LTF
0.12
AH1-155LTFEXP_AH1-155->PJM
LTF
0.18

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-013_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.58 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2466.99
MW Contribution:18.98
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
5.547
24189802OREGON_CT1
50/50
4.208
23888802TROY G4
50/50
1.536
241996AE2-282_GEN
Solar/Wind Harmer
2.235
971677AH1-339 GEN
Solar/Wind Harmer
6.71
961051AF2-396 GEN
Solar/Wind Harmer
10.688
961051AF2-396 GEN
Solar/Wind Harmer
4.971
246938BC-WTG3
Solar/Wind Harmer
2.651
246937BC-WTG2
Solar/Wind Harmer
2.606
960981AF2-389 GEN
Solar/Wind Harmer
1
957891AF2-083 GEN
Solar/Wind Harmer
2.231
270007AE1-245 C
Solar/Wind Harmer
3.918
942801AE2-298 GEN
Solar/Wind Harmer
0.99
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.386
270526AF1-158 GEN
Solar/Wind Harmer
2.804
24441505OLIV SLR
Solar/Wind Harmer
0.082
970611AG2-400 GEN
Solar/Wind Harmer
6.101
965681AG1-436 GEN
Solar/Wind Harmer
7.392
965791AG1-447 GEN
Solar/Wind Harmer
3.782
270224U2-072_GEN2
Solar/Wind Harmer
1.091
270227U2-072_GEN3
Solar/Wind Harmer
1.091
270228U2-072_GEN4
Solar/Wind Harmer
1.091
270231U2-072_GEN5
Solar/Wind Harmer
1.091
274808UNIV PK N;4U
Adder
2.713
274803UNIV PARK;6U
Adder
3.139
274888KELLY CRK;1U
Solar/Wind Harmer
3.164
274887GEN-1.85
Solar/Wind Harmer
2.856
276843GEN-1.7
Solar/Wind Harmer
0.307
958011AF2-095 GEN
Solar/Wind Harmer
7.717
274770LINCOLN ;1U
Adder
3.32
274771LINCOLN ;2U
Adder
3.32
972259AH1-714 GEN
Adder
10.15
274674JOLIET 9 ;6U
Adder
8.171
970321AG2-212 GEN
Solar/Wind Harmer
9.439
274847GR RIDGE ;BU
Solar/Wind Harmer
2.67
958481AF2-142 GEN
Solar/Wind Harmer
7.871
274861TOP CROP ;1U
Solar/Wind Harmer
3.179
274862TOP CROP ;2U
Solar/Wind Harmer
2.655
942221AE2-234 GEN
Solar/Wind Harmer
0.383
274696ROCKY RD ;4P
Adder
5.943
274695ROCKY RD ;2P
Adder
5.806
274693ROCKY RD ;1P
Adder
5.749
274697ROCKY RD ;3P
Adder
1.577
274683WAUKEGAN ;8U
Adder
10.982
274683WAUKEGAN ;8U
Adder
9.257
274764LEE CO EC;5U
Adder
4.71
274765LEE CO EC;6U
Adder
4.71
274762LEE CO EC;3U
Adder
4.699
274763LEE CO EC;4U
Adder
4.655
972267AH1-718 GEN
Adder
2.09
247621Y3-024
Adder
0.116
25326509SID D
Adder
0.615
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.199
241967AE2-285_GEN
Solar/Wind Helper
0.345
241801AE1-079 GEN
Solar/Wind Helper
0.134
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.112
971573AH1-285 GEN
Solar/Wind Harmer
0.21
972211AH1-690 GEN
50/50
445.145
23888502TROY G1
50/50
1.536
23888602TROY G2
50/50
1.536
970817AG2-515 GEN
Solar/Wind Harmer
14.306
945411AF1-206 GEN
Solar/Wind Harmer
8.348
945641AF1-229 GEN
Solar/Wind Harmer
3.836
270499AE1-146 GEN
Solar/Wind Harmer
2.323
971549AH1-272 GEN
Solar/Wind Harmer
15.402
270297AD1-101 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
1.521
957201AF2-014 GEN
Solar/Wind Harmer
3.021
270435AC2-044 GEN
Solar/Wind Harmer
1.332
247607V1-011 GEN
Solar/Wind Harmer
2.612
971771AH1-392 GEN
Solar/Wind Harmer
5.663
965041AG1-368 GEN
Solar/Wind Harmer
6.272
965051AG1-369 GEN
Solar/Wind Harmer
3.11
966831AG1-554 GEN
Solar/Wind Harmer
0.741
971989AH1-539 GEN
Solar/Wind Harmer
8.012
971769AH1-391 GEN
Solar/Wind Harmer
6.143
270302AB2-170 GEN
Solar/Wind Harmer
4.96
270317AD1-130_GEN
Solar/Wind Harmer
1.901
960681AF2-359 GEN
Solar/Wind Harmer
2.234
971347AH1-153 GEN
Solar/Wind Harmer
8.822
963791AG1-232 GEN
Solar/Wind Harmer
7.644
971567AH1-282 GEN
Solar/Wind Harmer
8.457
270536AF1-215 GEN2
Solar/Wind Harmer
2.537
270578AF1-285 GEN2
Solar/Wind Harmer
0.257
274814UNIV PK N;0U
Adder
2.749
274807UNIV PK N;3U
Adder
2.743
274805UNIV PK N;1U
Adder
2.731
274811UNIV PK N;7U
Adder
2.725
270071AF1-092 GEN
Solar/Wind Harmer
8.161
958391AF2-133 GEN
Solar/Wind Harmer
4.933
972037AH1-567 GEN1
Adder
0.099
274827FISK ;RP
Adder
4.17
960591AF2-350 GEN
Solar/Wind Harmer
5.359
274775LINCOLN ;6U
Adder
3.32
274776LINCOLN ;7U
Adder
3.32
274777LINCOLN ;8U
Adder
3.32
972227AH1-698 GEN1
Adder
1.394
274687WILL CNTY;4U
Adder
14.885
274687WILL CNTY;4U
Adder
14.885
274675JOLIET 29;7U
Adder
16.311
274675JOLIET 29;7U
Adder
15.729
274731ELWOOD EC;2P
Adder
8.724
274733ELWOOD EC;3P
Adder
8.724
274735ELWOOD EC;4P
Adder
8.724
274728ELWOOD EC;5P
Adder
8.724
970833AG2-524 GEN
Solar/Wind Harmer
4.611
970833AG2-524 GEN
Solar/Wind Harmer
2.145
274746AC1-111 G10
Adder
2.935
274744AC1-111 GEN8
Adder
2.935
274823ROCKFORD ;21
Adder
9.953
24729505KEY G4
Adder
3.297
241886AC2-103 GEN2
Solar/Wind Helper
6.853
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.87
24189902OREGON_CT2
50/50
4.123
23856402BAYSG1
50/50
1.571
23888702TROY G3
50/50
1.536
972253AH1-711 GEN
50/50
46.925
23920202STRYCT
50/50
1.926
241808AF1-120 C
Solar/Wind Harmer
1.246
241858AF1-205_GEN
Solar/Wind Harmer
5.409
241840AF1-064_GEN
Solar/Wind Harmer
1.361
972301AH1-735 GEN
Adder
6.723
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.342
270361_3
Solar/Wind Harmer
8.261
960841AF2-375 GEN
Solar/Wind Harmer
3.668
970515AG2-329 GEN
Solar/Wind Harmer
11.285
944231AF1-091 GEN
Solar/Wind Harmer
2.737
247522W1-056 GEN
Solar/Wind Harmer
1.61
270449AD2-020 GEN
Solar/Wind Harmer
1.903
943021AE2-325 GEN
Solar/Wind Harmer
2.473
246936BC-WTG1
Solar/Wind Harmer
2.606
270489AE1-102 GEN1
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
11.84
270505AE1-170 C O1
Solar/Wind Harmer
9.954
965421AG1-410 GEN
Solar/Wind Harmer
19.819
24639705ELKHART HY
Adder
0.099
24695305TIMB G C
Solar/Wind Harmer
3.527
270063AE2-323 C
Solar/Wind Harmer
1.394
247521TR3_G114
Solar/Wind Harmer
2.094
270246TR4_N_V150
Solar/Wind Harmer
0.53
965011AG1-365 GEN
Solar/Wind Harmer
6.101
270462AD2-086
Solar/Wind Harmer
4.126
970373AG2-245 GEN
Solar/Wind Harmer
11.954
270055AF2-134 C O1
Solar/Wind Harmer
1.691
270223U2-072_GEN1
Solar/Wind Harmer
1.091
270578AF1-285 GEN2
Solar/Wind Harmer
0.667
270391AF1-285 GEN3
Solar/Wind Harmer
0.667
274751CRETE EC ;1U
Adder
2.692
274754CRETE EC ;4U
Adder
2.692
958381AF2-132 GEN
Solar/Wind Harmer
4.978
964861AG1-349 GEN
Solar/Wind Harmer
4.305
971917AH1-482 GEN
Solar/Wind Harmer
4.968
274723RIVER EC ;12
Adder
9.794
274812UNIV PK N;8U
Adder
2.725
276164X3-005 C
Solar/Wind Harmer
0.381
274801UNIV PARK;4U
Adder
3.129
276776AD2-060 GEN
Solar/Wind Harmer
0.227
972207SS24-0001
Solar/Wind Harmer
11.806
274773LINCOLN ;4U
Adder
3.32
274774LINCOLN ;5U
Adder
3.32
940581AE2-045 GEN
Solar/Wind Harmer
5.461
971605AH1-302 GEN
Solar/Wind Harmer
4.67
274676JOLIET 29;8U
Adder
16.311
941551AE2-152 GEN
Solar/Wind Harmer
2.408
274732ELWOOD EC;7P
Adder
8.724
274674JOLIET 9 ;6U
Adder
8.171
970245AG2-165 GEN
Solar/Wind Harmer
9.439
274871GR RIDGE ;2U
Solar/Wind Harmer
4.059
274745AC1-111 GEN9
Adder
2.935
276691AA1-018 GEN1
Solar/Wind Harmer
0.244
274682WAUKEGAN ;7U
Adder
9.374
274828WAUKEGAN ;BP
Adder
5.756
274822ROCKFORD ;11
Adder
10.025
972235AH1-702 GEN1
Adder
1.285
274761LEE CO EC;2U
Adder
4.699
274766LEE CO EC;7U
Adder
4.644
24728605AND G2
Adder
1.664
241885AC2-103 GEN1
Solar/Wind Helper
6.853
241807AE2-176_GEN
Solar/Wind Helper
1.649
961971AG1-040 GEN
Solar/Wind Helper
0.343
203835AF1-098 GEN
Solar/Wind Helper
1.35
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
23929302BS-PKR
50/50
2.766
241832AE2-181_GEN
Solar/Wind Harmer
1.995
958321AF2-126 GEN
Solar/Wind Harmer
1.459
23906502RICHG2&3
Adder
1.342
270541AE2-072 C
Solar/Wind Harmer
4.431
270575GUS2 35KV
Solar/Wind Harmer
9.732
970217AG2-149 GEN
Solar/Wind Harmer
24.885
247604X1-042
Adder
0.304
270044AE2-322 C
Solar/Wind Harmer
0.942
270404AC1-167 GEN
Solar/Wind Harmer
0.785
24441205WTRV SLR C
Solar/Wind Harmer
0.096
270258AD1-119 GEN
Solar/Wind Harmer
1.934
270491AE1-102 GEN2
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
3.753
958091AF2-103 GEN
Solar/Wind Harmer
0.107
270588AE1-091_GEN
Solar/Wind Harmer
7.25
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0.044
970031AG2-029 GEN
Solar/Wind Harmer
18.979
270191TR4_S_V150
Solar/Wind Harmer
1.869
270247TR4_N_V136
Solar/Wind Harmer
0.53
959331AF2-224 GEN
Solar/Wind Harmer
6.101
965021AG1-366 GEN
Solar/Wind Harmer
1.419
270485AE1-090_GEN
Solar/Wind Harmer
0.359
970349AG2-230 GEN
Solar/Wind Harmer
8.822
270043AE2-236 GEN
Solar/Wind Harmer
3.209
270535AF1-215 GEN1
Solar/Wind Harmer
2.537
942871AE2-306 GEN
Solar/Wind Harmer
0.5
270391AF1-285 GEN3
Solar/Wind Harmer
0.257
972231SS25-0005
Solar/Wind Harmer
5.226
972181SS23-001
Solar/Wind Harmer
3.267
274752CRETE EC ;2U
Adder
2.692
274753CRETE EC ;3U
Adder
2.692
964401AG1-302 GEN
Solar/Wind Harmer
4.978
274724RIVER EC ;11
Adder
9.677
959141AF2-205 GEN
Solar/Wind Harmer
3.265
274802UNIV PARK;5U
Adder
3.139
274826FISK ;BP
Adder
5.884
274800UNIV PARK;3U
Adder
3.129
972038AH1-567 GEN2
Adder
0.196
276772AC2-154 GEN
Solar/Wind Harmer
1.494
276806AD2-047 C O1
Solar/Wind Harmer
5.733
970941AG2-585 GEN
Solar/Wind Harmer
6.698
274772LINCOLN ;3U
Adder
3.32
972228AH1-698 GEN2
Adder
1.979
274676JOLIET 29;8U
Adder
15.729
276897AD1-100 C
Solar/Wind Harmer
15.411
939351AE1-166 GEN
Solar/Wind Harmer
3.149
276893AG1-478 C
Solar/Wind Harmer
0.222
274729ELWOOD EC;1P
Adder
8.724
274730ELWOOD EC;6P
Adder
8.724
274734ELWOOD EC;8P
Adder
8.724
274736ELWOOD EC;9P
Adder
8.724
970707AG2-453 GEN
Solar/Wind Harmer
14.858
970513AG2-328 GEN
Solar/Wind Harmer
9.439
970517AG2-330 GEN
Solar/Wind Harmer
8.561
943121AE2-341 GEN
Solar/Wind Harmer
7.872
943591AF1-030 GEN
Solar/Wind Harmer
5.248
276694AA1-018 GEN2
Solar/Wind Harmer
3.311
274682WAUKEGAN ;7U
Adder
9.374
972236AH1-702 GEN2
Adder
1.118
274760LEE CO EC;1U
Adder
4.699
274767LEE CO EC;8U
Adder
4.644
24728705AND G3
Adder
3.481
24728505AND G1
Adder
1.664
962511AG1-100 GEN
Solar/Wind Helper
0.351
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
991182J1586 G
External Queue
28.164417266845703
990527J1329
External Queue
2.0267114639282227
990142J1224
External Queue
14.81525993347168
991177J1571 G
External Queue
15.818673133850098
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.978
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.921
MECLTFEXP_MEC->PJM
CLTF
7.642
SIGELTFEXP_SIGE->PJM
CLTF
0.2
LAGNLTFEXP_LAGN->PJM
CLTF
6.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.404
TVALTFEXP_TVA->PJM
CLTF
2.778
CPLELTFEXP_CPLE->PJM
CLTF
0.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.597
NYPJM->LTFIMP_NY
CLTF
1.967
LGEELTFEXP_LGEE->PJM
CLTF
2.403
WECLTFEXP_WEC->PJM
CLTF
1.948
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.188

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-014_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.58 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2466.97
MW Contribution:18.98
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
5.547
24189802OREGON_CT1
50/50
4.208
23888802TROY G4
50/50
1.536
241996AE2-282_GEN
Solar/Wind Harmer
2.235
971677AH1-339 GEN
Solar/Wind Harmer
6.71
961051AF2-396 GEN
Solar/Wind Harmer
10.687
961051AF2-396 GEN
Solar/Wind Harmer
4.971
246938BC-WTG3
Solar/Wind Harmer
2.651
246937BC-WTG2
Solar/Wind Harmer
2.606
960981AF2-389 GEN
Solar/Wind Harmer
1
957891AF2-083 GEN
Solar/Wind Harmer
2.231
270007AE1-245 C
Solar/Wind Harmer
3.918
942801AE2-298 GEN
Solar/Wind Harmer
0.99
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.386
270526AF1-158 GEN
Solar/Wind Harmer
2.804
24441505OLIV SLR
Solar/Wind Harmer
0.082
970611AG2-400 GEN
Solar/Wind Harmer
6.101
965681AG1-436 GEN
Solar/Wind Harmer
7.392
965791AG1-447 GEN
Solar/Wind Harmer
3.782
270224U2-072_GEN2
Solar/Wind Harmer
1.091
270227U2-072_GEN3
Solar/Wind Harmer
1.091
270228U2-072_GEN4
Solar/Wind Harmer
1.091
270231U2-072_GEN5
Solar/Wind Harmer
1.091
274808UNIV PK N;4U
Adder
2.713
274803UNIV PARK;6U
Adder
3.139
274888KELLY CRK;1U
Solar/Wind Harmer
3.164
274887GEN-1.85
Solar/Wind Harmer
2.856
276843GEN-1.7
Solar/Wind Harmer
0.307
958011AF2-095 GEN
Solar/Wind Harmer
7.717
274770LINCOLN ;1U
Adder
3.32
274771LINCOLN ;2U
Adder
3.32
972259AH1-714 GEN
Adder
10.15
274674JOLIET 9 ;6U
Adder
8.171
970321AG2-212 GEN
Solar/Wind Harmer
9.439
274847GR RIDGE ;BU
Solar/Wind Harmer
2.67
958481AF2-142 GEN
Solar/Wind Harmer
7.871
274861TOP CROP ;1U
Solar/Wind Harmer
3.179
274862TOP CROP ;2U
Solar/Wind Harmer
2.655
942221AE2-234 GEN
Solar/Wind Harmer
0.383
274696ROCKY RD ;4P
Adder
5.943
274695ROCKY RD ;2P
Adder
5.806
274693ROCKY RD ;1P
Adder
5.749
274697ROCKY RD ;3P
Adder
1.577
274683WAUKEGAN ;8U
Adder
10.982
274683WAUKEGAN ;8U
Adder
9.257
274764LEE CO EC;5U
Adder
4.71
274765LEE CO EC;6U
Adder
4.71
274762LEE CO EC;3U
Adder
4.699
274763LEE CO EC;4U
Adder
4.655
972267AH1-718 GEN
Adder
2.09
247621Y3-024
Adder
0.116
25326509SID D
Adder
0.615
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.199
241967AE2-285_GEN
Solar/Wind Helper
0.345
241801AE1-079 GEN
Solar/Wind Helper
0.134
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.112
971573AH1-285 GEN
Solar/Wind Harmer
0.21
972211AH1-690 GEN
50/50
445.147
23888502TROY G1
50/50
1.536
23888602TROY G2
50/50
1.536
970817AG2-515 GEN
Solar/Wind Harmer
14.306
945411AF1-206 GEN
Solar/Wind Harmer
8.348
945641AF1-229 GEN
Solar/Wind Harmer
3.836
270499AE1-146 GEN
Solar/Wind Harmer
2.323
971549AH1-272 GEN
Solar/Wind Harmer
15.402
270297AD1-101 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
1.521
957201AF2-014 GEN
Solar/Wind Harmer
3.02
270435AC2-044 GEN
Solar/Wind Harmer
1.332
247607V1-011 GEN
Solar/Wind Harmer
2.612
971771AH1-392 GEN
Solar/Wind Harmer
5.663
965041AG1-368 GEN
Solar/Wind Harmer
6.272
965051AG1-369 GEN
Solar/Wind Harmer
3.11
966831AG1-554 GEN
Solar/Wind Harmer
0.741
971989AH1-539 GEN
Solar/Wind Harmer
8.012
971769AH1-391 GEN
Solar/Wind Harmer
6.143
270302AB2-170 GEN
Solar/Wind Harmer
4.96
270317AD1-130_GEN
Solar/Wind Harmer
1.901
960681AF2-359 GEN
Solar/Wind Harmer
2.234
971347AH1-153 GEN
Solar/Wind Harmer
8.822
963791AG1-232 GEN
Solar/Wind Harmer
7.644
971567AH1-282 GEN
Solar/Wind Harmer
8.457
270536AF1-215 GEN2
Solar/Wind Harmer
2.537
270578AF1-285 GEN2
Solar/Wind Harmer
0.257
274814UNIV PK N;0U
Adder
2.749
274807UNIV PK N;3U
Adder
2.743
274805UNIV PK N;1U
Adder
2.731
274811UNIV PK N;7U
Adder
2.725
270071AF1-092 GEN
Solar/Wind Harmer
8.161
958391AF2-133 GEN
Solar/Wind Harmer
4.933
972037AH1-567 GEN1
Adder
0.099
274827FISK ;RP
Adder
4.17
960591AF2-350 GEN
Solar/Wind Harmer
5.359
274775LINCOLN ;6U
Adder
3.32
274776LINCOLN ;7U
Adder
3.32
274777LINCOLN ;8U
Adder
3.32
972227AH1-698 GEN1
Adder
1.394
274687WILL CNTY;4U
Adder
14.885
274687WILL CNTY;4U
Adder
14.885
274675JOLIET 29;7U
Adder
16.311
274675JOLIET 29;7U
Adder
15.729
274731ELWOOD EC;2P
Adder
8.724
274733ELWOOD EC;3P
Adder
8.724
274735ELWOOD EC;4P
Adder
8.724
274728ELWOOD EC;5P
Adder
8.724
970833AG2-524 GEN
Solar/Wind Harmer
4.611
970833AG2-524 GEN
Solar/Wind Harmer
2.145
274746AC1-111 G10
Adder
2.935
274744AC1-111 GEN8
Adder
2.935
274823ROCKFORD ;21
Adder
9.952
24729505KEY G4
Adder
3.297
241886AC2-103 GEN2
Solar/Wind Helper
6.853
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.87
24189902OREGON_CT2
50/50
4.123
23856402BAYSG1
50/50
1.571
23888702TROY G3
50/50
1.536
972253AH1-711 GEN
50/50
46.923
23920202STRYCT
50/50
1.926
241808AF1-120 C
Solar/Wind Harmer
1.246
241858AF1-205_GEN
Solar/Wind Harmer
5.409
241840AF1-064_GEN
Solar/Wind Harmer
1.361
972301AH1-735 GEN
Adder
6.723
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.342
270361_3
Solar/Wind Harmer
8.261
960841AF2-375 GEN
Solar/Wind Harmer
3.668
970515AG2-329 GEN
Solar/Wind Harmer
11.285
944231AF1-091 GEN
Solar/Wind Harmer
2.737
247522W1-056 GEN
Solar/Wind Harmer
1.61
270449AD2-020 GEN
Solar/Wind Harmer
1.903
943021AE2-325 GEN
Solar/Wind Harmer
2.473
246936BC-WTG1
Solar/Wind Harmer
2.606
270489AE1-102 GEN1
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
11.84
270505AE1-170 C O1
Solar/Wind Harmer
9.954
965421AG1-410 GEN
Solar/Wind Harmer
19.819
24639705ELKHART HY
Adder
0.099
24695305TIMB G C
Solar/Wind Harmer
3.527
270063AE2-323 C
Solar/Wind Harmer
1.394
247521TR3_G114
Solar/Wind Harmer
2.094
270246TR4_N_V150
Solar/Wind Harmer
0.53
965011AG1-365 GEN
Solar/Wind Harmer
6.101
270462AD2-086
Solar/Wind Harmer
4.126
970373AG2-245 GEN
Solar/Wind Harmer
11.954
270055AF2-134 C O1
Solar/Wind Harmer
1.691
270223U2-072_GEN1
Solar/Wind Harmer
1.091
270578AF1-285 GEN2
Solar/Wind Harmer
0.667
270391AF1-285 GEN3
Solar/Wind Harmer
0.667
274751CRETE EC ;1U
Adder
2.692
274754CRETE EC ;4U
Adder
2.692
958381AF2-132 GEN
Solar/Wind Harmer
4.978
964861AG1-349 GEN
Solar/Wind Harmer
4.305
971917AH1-482 GEN
Solar/Wind Harmer
4.968
274723RIVER EC ;12
Adder
9.794
274812UNIV PK N;8U
Adder
2.725
276164X3-005 C
Solar/Wind Harmer
0.381
274801UNIV PARK;4U
Adder
3.129
276776AD2-060 GEN
Solar/Wind Harmer
0.227
972207SS24-0001
Solar/Wind Harmer
11.806
274773LINCOLN ;4U
Adder
3.32
274774LINCOLN ;5U
Adder
3.32
940581AE2-045 GEN
Solar/Wind Harmer
5.461
971605AH1-302 GEN
Solar/Wind Harmer
4.67
274676JOLIET 29;8U
Adder
16.311
941551AE2-152 GEN
Solar/Wind Harmer
2.408
274732ELWOOD EC;7P
Adder
8.724
274674JOLIET 9 ;6U
Adder
8.171
970245AG2-165 GEN
Solar/Wind Harmer
9.439
274871GR RIDGE ;2U
Solar/Wind Harmer
4.059
274745AC1-111 GEN9
Adder
2.935
276691AA1-018 GEN1
Solar/Wind Harmer
0.244
274682WAUKEGAN ;7U
Adder
9.374
274828WAUKEGAN ;BP
Adder
5.756
274822ROCKFORD ;11
Adder
10.025
972235AH1-702 GEN1
Adder
1.285
274761LEE CO EC;2U
Adder
4.699
274766LEE CO EC;7U
Adder
4.644
24728605AND G2
Adder
1.664
241885AC2-103 GEN1
Solar/Wind Helper
6.853
241807AE2-176_GEN
Solar/Wind Helper
1.649
961971AG1-040 GEN
Solar/Wind Helper
0.343
203835AF1-098 GEN
Solar/Wind Helper
1.35
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
23929302BS-PKR
50/50
2.766
241832AE2-181_GEN
Solar/Wind Harmer
1.995
958321AF2-126 GEN
Solar/Wind Harmer
1.459
23906502RICHG2&3
Adder
1.342
270541AE2-072 C
Solar/Wind Harmer
4.431
270575GUS2 35KV
Solar/Wind Harmer
9.732
970217AG2-149 GEN
Solar/Wind Harmer
24.885
247604X1-042
Adder
0.304
270044AE2-322 C
Solar/Wind Harmer
0.942
270404AC1-167 GEN
Solar/Wind Harmer
0.785
24441205WTRV SLR C
Solar/Wind Harmer
0.096
270258AD1-119 GEN
Solar/Wind Harmer
1.934
270491AE1-102 GEN2
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
3.753
958091AF2-103 GEN
Solar/Wind Harmer
0.107
270588AE1-091_GEN
Solar/Wind Harmer
7.25
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0.044
970031AG2-029 GEN
Solar/Wind Harmer
18.979
270191TR4_S_V150
Solar/Wind Harmer
1.869
270247TR4_N_V136
Solar/Wind Harmer
0.53
959331AF2-224 GEN
Solar/Wind Harmer
6.101
965021AG1-366 GEN
Solar/Wind Harmer
1.419
270485AE1-090_GEN
Solar/Wind Harmer
0.359
970349AG2-230 GEN
Solar/Wind Harmer
8.822
270043AE2-236 GEN
Solar/Wind Harmer
3.209
270535AF1-215 GEN1
Solar/Wind Harmer
2.537
942871AE2-306 GEN
Solar/Wind Harmer
0.5
270391AF1-285 GEN3
Solar/Wind Harmer
0.257
972231SS25-0005
Solar/Wind Harmer
5.226
972181SS23-001
Solar/Wind Harmer
3.267
274752CRETE EC ;2U
Adder
2.692
274753CRETE EC ;3U
Adder
2.692
964401AG1-302 GEN
Solar/Wind Harmer
4.978
274724RIVER EC ;11
Adder
9.677
959141AF2-205 GEN
Solar/Wind Harmer
3.265
274802UNIV PARK;5U
Adder
3.139
274826FISK ;BP
Adder
5.884
274800UNIV PARK;3U
Adder
3.129
972038AH1-567 GEN2
Adder
0.196
276772AC2-154 GEN
Solar/Wind Harmer
1.494
276806AD2-047 C O1
Solar/Wind Harmer
5.733
970941AG2-585 GEN
Solar/Wind Harmer
6.698
274772LINCOLN ;3U
Adder
3.32
972228AH1-698 GEN2
Adder
1.979
274676JOLIET 29;8U
Adder
15.728
276897AD1-100 C
Solar/Wind Harmer
15.411
939351AE1-166 GEN
Solar/Wind Harmer
3.149
276893AG1-478 C
Solar/Wind Harmer
0.222
274729ELWOOD EC;1P
Adder
8.724
274730ELWOOD EC;6P
Adder
8.724
274734ELWOOD EC;8P
Adder
8.724
274736ELWOOD EC;9P
Adder
8.724
970707AG2-453 GEN
Solar/Wind Harmer
14.858
970513AG2-328 GEN
Solar/Wind Harmer
9.439
970517AG2-330 GEN
Solar/Wind Harmer
8.561
943121AE2-341 GEN
Solar/Wind Harmer
7.872
943591AF1-030 GEN
Solar/Wind Harmer
5.248
276694AA1-018 GEN2
Solar/Wind Harmer
3.311
274682WAUKEGAN ;7U
Adder
9.374
972236AH1-702 GEN2
Adder
1.118
274760LEE CO EC;1U
Adder
4.699
274767LEE CO EC;8U
Adder
4.644
24728705AND G3
Adder
3.481
24728505AND G1
Adder
1.664
962511AG1-100 GEN
Solar/Wind Helper
0.351
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
991182J1586 G
External Queue
28.164098739624023
990527J1329
External Queue
2.026688814163208
990142J1224
External Queue
14.815095901489258
991177J1571 G
External Queue
15.818490982055664
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.92
MECLTFEXP_MEC->PJM
CLTF
7.642
SIGELTFEXP_SIGE->PJM
CLTF
0.2
LAGNLTFEXP_LAGN->PJM
CLTF
6.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.404
TVALTFEXP_TVA->PJM
CLTF
2.778
CPLELTFEXP_CPLE->PJM
CLTF
0.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.596
NYPJM->LTFIMP_NY
CLTF
1.967
LGEELTFEXP_LGEE->PJM
CLTF
2.403
WECLTFEXP_WEC->PJM
CLTF
1.948
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.188

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-009_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-009_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.4 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2463.99
MW Contribution:18.96
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
4.125
23856402BAYSG1
50/50
1.577
23888702TROY G3
50/50
1.526
972253AH1-711 GEN
50/50
46.611
23920202STRYCT
50/50
1.928
241808AF1-120 C
Solar/Wind Harmer
1.247
241858AF1-205_GEN
Solar/Wind Harmer
5.419
241840AF1-064_GEN
Solar/Wind Harmer
1.367
972301AH1-735 GEN
Adder
6.727
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.343
270361_3
Solar/Wind Harmer
8.271
960841AF2-375 GEN
Solar/Wind Harmer
3.672
970515AG2-329 GEN
Solar/Wind Harmer
11.264
944231AF1-091 GEN
Solar/Wind Harmer
2.736
247522W1-056 GEN
Solar/Wind Harmer
1.61
270449AD2-020 GEN
Solar/Wind Harmer
1.901
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
2.603
270489AE1-102 GEN1
Solar/Wind Harmer
0.865
945111AF1-176 GEN
Solar/Wind Harmer
11.826
270505AE1-170 C O1
Solar/Wind Harmer
9.942
965421AG1-410 GEN
Solar/Wind Harmer
19.794
24639705ELKHART HY
Adder
0.098
24695305TIMB G C
Solar/Wind Harmer
3.523
270063AE2-323 C
Solar/Wind Harmer
1.392
247521TR3_G114
Solar/Wind Harmer
2.092
270246TR4_N_V150
Solar/Wind Harmer
0.529
24190002OREGON_ST1
50/50
5.55
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.526
241996AE2-282_GEN
Solar/Wind Harmer
2.237
971677AH1-339 GEN
Solar/Wind Harmer
6.708
961051AF2-396 GEN
Solar/Wind Harmer
10.675
961051AF2-396 GEN
Solar/Wind Harmer
4.965
246938BC-WTG3
Solar/Wind Harmer
2.648
246937BC-WTG2
Solar/Wind Harmer
2.603
960981AF2-389 GEN
Solar/Wind Harmer
0.999
957891AF2-083 GEN
Solar/Wind Harmer
2.228
270007AE1-245 C
Solar/Wind Harmer
3.915
942801AE2-298 GEN
Solar/Wind Harmer
0.989
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.386
270526AF1-158 GEN
Solar/Wind Harmer
2.801
24441505OLIV SLR
Solar/Wind Harmer
0.082
970611AG2-400 GEN
Solar/Wind Harmer
6.095
965681AG1-436 GEN
Solar/Wind Harmer
7.384
965791AG1-447 GEN
Solar/Wind Harmer
3.778
270224U2-072_GEN2
Solar/Wind Harmer
1.089
270227U2-072_GEN3
Solar/Wind Harmer
1.089
270228U2-072_GEN4
Solar/Wind Harmer
1.089
270231U2-072_GEN5
Solar/Wind Harmer
1.089
274808UNIV PK N;4U
Adder
2.71
274803UNIV PARK;6U
Adder
3.135
274888KELLY CRK;1U
Solar/Wind Harmer
3.16
274887GEN-1.85
Solar/Wind Harmer
2.853
972211AH1-690 GEN
50/50
445.374
23888502TROY G1
50/50
1.526
23888602TROY G2
50/50
1.526
970817AG2-515 GEN
Solar/Wind Harmer
14.26
945411AF1-206 GEN
Solar/Wind Harmer
8.353
945641AF1-229 GEN
Solar/Wind Harmer
3.828
270499AE1-146 GEN
Solar/Wind Harmer
2.325
971549AH1-272 GEN
Solar/Wind Harmer
15.383
270297AD1-101 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
1.52
957201AF2-014 GEN
Solar/Wind Harmer
3.017
270435AC2-044 GEN
Solar/Wind Harmer
1.33
247607V1-011 GEN
Solar/Wind Harmer
2.61
971771AH1-392 GEN
Solar/Wind Harmer
5.656
965011AG1-365 GEN
Solar/Wind Harmer
6.095
270462AD2-086
Solar/Wind Harmer
4.12
970373AG2-245 GEN
Solar/Wind Harmer
11.94
270055AF2-134 C O1
Solar/Wind Harmer
1.689
270223U2-072_GEN1
Solar/Wind Harmer
1.089
270578AF1-285 GEN2
Solar/Wind Harmer
0.666
270391AF1-285 GEN3
Solar/Wind Harmer
0.666
274751CRETE EC ;1U
Adder
2.689
274754CRETE EC ;4U
Adder
2.689
958381AF2-132 GEN
Solar/Wind Harmer
4.972
964861AG1-349 GEN
Solar/Wind Harmer
4.3
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.782
23929302BS-PKR
50/50
2.775
241832AE2-181_GEN
Solar/Wind Harmer
1.996
958321AF2-126 GEN
Solar/Wind Harmer
1.466
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
4.433
270575GUS2 35KV
Solar/Wind Harmer
9.743
970217AG2-149 GEN
Solar/Wind Harmer
24.838
247604X1-042
Adder
0.303
270044AE2-322 C
Solar/Wind Harmer
0.942
270404AC1-167 GEN
Solar/Wind Harmer
0.784
24441205WTRV SLR C
Solar/Wind Harmer
0.096
270258AD1-119 GEN
Solar/Wind Harmer
1.933
270491AE1-102 GEN2
Solar/Wind Harmer
0.865
945111AF1-176 GEN
Solar/Wind Harmer
3.748
958091AF2-103 GEN
Solar/Wind Harmer
0.107
270588AE1-091_GEN
Solar/Wind Harmer
7.246
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0.044
970031AG2-029 GEN
Solar/Wind Harmer
18.957
270191TR4_S_V150
Solar/Wind Harmer
1.867
270247TR4_N_V136
Solar/Wind Harmer
0.529
959331AF2-224 GEN
Solar/Wind Harmer
6.095
965021AG1-366 GEN
Solar/Wind Harmer
1.417
270485AE1-090_GEN
Solar/Wind Harmer
0.358
970349AG2-230 GEN
Solar/Wind Harmer
8.811
270043AE2-236 GEN
Solar/Wind Harmer
3.205
270535AF1-215 GEN1
Solar/Wind Harmer
2.534
942871AE2-306 GEN
Solar/Wind Harmer
0.5
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
972231SS25-0005
Solar/Wind Harmer
5.22
972181SS23-001
Solar/Wind Harmer
3.263
274752CRETE EC ;2U
Adder
2.689
274753CRETE EC ;3U
Adder
2.689
964401AG1-302 GEN
Solar/Wind Harmer
4.972
274724RIVER EC ;11
Adder
9.666
959141AF2-205 GEN
Solar/Wind Harmer
3.261
274802UNIV PARK;5U
Adder
3.135
274826FISK ;BP
Adder
5.877
274800UNIV PARK;3U
Adder
3.125
972038AH1-567 GEN2
Adder
0.196
276772AC2-154 GEN
Solar/Wind Harmer
1.493
276806AD2-047 C O1
Solar/Wind Harmer
5.726
970941AG2-585 GEN
Solar/Wind Harmer
6.69
274772LINCOLN ;3U
Adder
3.317
972228AH1-698 GEN2
Adder
1.977
274676JOLIET 29;8U
Adder
15.71
276897AD1-100 C
Solar/Wind Harmer
15.393
939351AE1-166 GEN
Solar/Wind Harmer
3.145
276893AG1-478 C
Solar/Wind Harmer
0.221
274730ELWOOD EC;6P
Adder
8.714
274734ELWOOD EC;8P
Adder
8.714
274736ELWOOD EC;9P
Adder
8.714
274729ELWOOD EC;1P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
14.84
970513AG2-328 GEN
Solar/Wind Harmer
9.428
970517AG2-330 GEN
Solar/Wind Harmer
8.551
943121AE2-341 GEN
Solar/Wind Harmer
7.863
943591AF1-030 GEN
Solar/Wind Harmer
5.242
276694AA1-018 GEN2
Solar/Wind Harmer
3.307
274682WAUKEGAN ;7U
Adder
9.363
972236AH1-702 GEN2
Adder
1.116
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
4.638
24728705AND G3
Adder
3.477
24728505AND G1
Adder
1.662
962511AG1-100 GEN
Solar/Wind Helper
0.35
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
276843GEN-1.7
Solar/Wind Harmer
0.307
958011AF2-095 GEN
Solar/Wind Harmer
7.707
274770LINCOLN ;1U
Adder
3.317
274771LINCOLN ;2U
Adder
3.317
972259AH1-714 GEN
Adder
10.138
274674JOLIET 9 ;6U
Adder
8.161
970321AG2-212 GEN
Solar/Wind Harmer
9.428
274847GR RIDGE ;BU
Solar/Wind Harmer
2.667
958481AF2-142 GEN
Solar/Wind Harmer
7.862
274861TOP CROP ;1U
Solar/Wind Harmer
3.176
274862TOP CROP ;2U
Solar/Wind Harmer
2.652
942221AE2-234 GEN
Solar/Wind Harmer
0.383
274696ROCKY RD ;4P
Adder
5.936
274695ROCKY RD ;2P
Adder
5.799
274693ROCKY RD ;1P
Adder
5.742
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.969
274683WAUKEGAN ;8U
Adder
9.246
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
972267AH1-718 GEN
Adder
2.087
247621Y3-024
Adder
0.115
25326509SID D
Adder
0.615
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.198
241801AE1-079 GEN
Solar/Wind Helper
0.134
241967AE2-285_GEN
Solar/Wind Helper
0.345
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
971573AH1-285 GEN
Solar/Wind Harmer
0.21
274812UNIV PK N;8U
Adder
2.722
276164X3-005 C
Solar/Wind Harmer
0.38
274801UNIV PARK;4U
Adder
3.125
276776AD2-060 GEN
Solar/Wind Harmer
0.226
972207SS24-0001
Solar/Wind Harmer
11.792
274773LINCOLN ;4U
Adder
3.317
274774LINCOLN ;5U
Adder
3.317
940581AE2-045 GEN
Solar/Wind Harmer
5.455
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.292
941551AE2-152 GEN
Solar/Wind Harmer
2.406
274732ELWOOD EC;7P
Adder
8.714
274674JOLIET 9 ;6U
Adder
8.161
970245AG2-165 GEN
Solar/Wind Harmer
9.428
274871GR RIDGE ;2U
Solar/Wind Harmer
4.054
274745AC1-111 GEN9
Adder
2.931
276691AA1-018 GEN1
Solar/Wind Harmer
0.244
274682WAUKEGAN ;7U
Adder
9.363
274828WAUKEGAN ;BP
Adder
5.75
274822ROCKFORD ;11
Adder
10.013
972235AH1-702 GEN1
Adder
1.284
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24728605AND G2
Adder
1.662
241885AC2-103 GEN1
Solar/Wind Helper
6.849
241807AE2-176_GEN
Solar/Wind Helper
1.64
961971AG1-040 GEN
Solar/Wind Helper
0.342
203835AF1-098 GEN
Solar/Wind Helper
1.348
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
965041AG1-368 GEN
Solar/Wind Harmer
6.266
965051AG1-369 GEN
Solar/Wind Harmer
3.107
966831AG1-554 GEN
Solar/Wind Harmer
0.741
971989AH1-539 GEN
Solar/Wind Harmer
8.008
971769AH1-391 GEN
Solar/Wind Harmer
6.135
270302AB2-170 GEN
Solar/Wind Harmer
4.953
270317AD1-130_GEN
Solar/Wind Harmer
1.899
960681AF2-359 GEN
Solar/Wind Harmer
2.232
971347AH1-153 GEN
Solar/Wind Harmer
8.811
963791AG1-232 GEN
Solar/Wind Harmer
7.636
971567AH1-282 GEN
Solar/Wind Harmer
8.442
270536AF1-215 GEN2
Solar/Wind Harmer
2.534
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274805UNIV PK N;1U
Adder
2.728
274811UNIV PK N;7U
Adder
2.722
270071AF1-092 GEN
Solar/Wind Harmer
8.152
958391AF2-133 GEN
Solar/Wind Harmer
4.927
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
960591AF2-350 GEN
Solar/Wind Harmer
5.352
274775LINCOLN ;6U
Adder
3.317
274776LINCOLN ;7U
Adder
3.317
274777LINCOLN ;8U
Adder
3.317
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.867
274687WILL CNTY;4U
Adder
14.867
274675JOLIET 29;7U
Adder
16.292
274675JOLIET 29;7U
Adder
15.71
274728ELWOOD EC;5P
Adder
8.714
274731ELWOOD EC;2P
Adder
8.713
274733ELWOOD EC;3P
Adder
8.713
274735ELWOOD EC;4P
Adder
8.713
970833AG2-524 GEN
Solar/Wind Harmer
4.606
970833AG2-524 GEN
Solar/Wind Harmer
2.142
274746AC1-111 G10
Adder
2.931
274744AC1-111 GEN8
Adder
2.931
274823ROCKFORD ;21
Adder
9.941
24729505KEY G4
Adder
3.294
241886AC2-103 GEN2
Solar/Wind Helper
6.849
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.869
991182J1586 G
External Queue
28.11846351623535
990527J1329
External Queue
2.0234405994415283
990142J1224
External Queue
14.791350364685059
991177J1571 G
External Queue
15.792752265930176
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.633
SIGELTFEXP_SIGE->PJM
CLTF
0.2
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.4
TVALTFEXP_TVA->PJM
CLTF
2.775
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.539
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.946
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-602_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-602_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.52 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2398.59
MW Contribution:2.87
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
4.125
23856402BAYSG1
50/50
1.577
23888702TROY G3
50/50
1.526
972253AH1-711 GEN
50/50
46.611
23920202STRYCT
50/50
1.928
241808AF1-120 C
Solar/Wind Harmer
0.003
241858AF1-205_GEN
Solar/Wind Harmer
3.78
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.727
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.343
270361_3
Solar/Wind Harmer
4.521
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
970515AG2-329 GEN
Solar/Wind Harmer
14.08
944231AF1-091 GEN
Solar/Wind Harmer
1.351
247522W1-056 GEN
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
0.188
270489AE1-102 GEN1
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
8.251
270505AE1-170 C O1
Solar/Wind Harmer
4.856
965421AG1-410 GEN
Solar/Wind Harmer
13.81
24639705ELKHART HY
Adder
0.098
24695305TIMB G C
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.004
247521TR3_G114
Solar/Wind Harmer
0.158
270246TR4_N_V150
Solar/Wind Harmer
0.028
965011AG1-365 GEN
Solar/Wind Harmer
4.252
270462AD2-086
Solar/Wind Harmer
0.009
970373AG2-245 GEN
Solar/Wind Harmer
8.33
270055AF2-134 C O1
Solar/Wind Harmer
0.003
270223U2-072_GEN1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
4.532
274754CRETE EC ;4U
Adder
4.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.782
274812UNIV PK N;8U
Adder
2.722
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.125
276776AD2-060 GEN
Solar/Wind Harmer
0.39
274773LINCOLN ;4U
Adder
4.515
274774LINCOLN ;5U
Adder
4.515
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.292
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.714
274674JOLIET 9 ;6U
Adder
8.161
970245AG2-165 GEN
Solar/Wind Harmer
1.596
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.931
276691AA1-018 GEN1
Solar/Wind Harmer
0.443
274682WAUKEGAN ;7U
Adder
9.363
274828WAUKEGAN ;BP
Adder
5.75
276901AD2-066 C O1
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
2.703
962781AG1-127 GEN
Solar/Wind Harmer
3.433
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.887
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.064
957471AF2-041 GEN
Solar/Wind Harmer
10.7
959081AF2-199 GEN
Solar/Wind Harmer
3.567
971067AG2-660 GEN
Solar/Wind Harmer
1.189
274822ROCKFORD ;11
Adder
10.013
972235AH1-702 GEN1
Adder
1.284
970569AG2-363 GEN
Solar/Wind Harmer
10.66
970819AG2-516 GEN
Solar/Wind Harmer
4.256
971475AH1-234 GEN
Solar/Wind Harmer
1.718
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.858
965651AG1-433 GEN
Solar/Wind Harmer
1.012
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
1.482
963741AG1-226 GEN
Solar/Wind Harmer
7.999
972175AH1-670 GEN
Solar/Wind Harmer
2.788
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.435
274880W4-005 GEN4
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
2.212
963831AG1-236 GEN
Solar/Wind Harmer
1.29
247536S-71 GEN
Solar/Wind Harmer
0.132
276615X2-022 GEN
Solar/Wind Harmer
0.034
276903AD2-071 C
Solar/Wind Harmer
3.649
970825AG2-519 GEN
Solar/Wind Harmer
1.153
270005AE1-210 C O1
Solar/Wind Harmer
0.7
241885AC2-103 GEN1
Solar/Wind Helper
6.849
241807AE2-176_GEN
Solar/Wind Helper
1.64
961971AG1-040 GEN
Solar/Wind Helper
0.342
203835AF1-098 GEN
Solar/Wind Helper
1.348
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
965031AG1-367 GEN
Solar/Wind Harmer
0.798
23929302BS-PKR
50/50
2.775
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.136
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.521
970217AG2-149 GEN
Solar/Wind Harmer
4.693
247604X1-042
Adder
0.303
270404AC1-167 GEN
Solar/Wind Harmer
0.002
24441205WTRV SLR C
Solar/Wind Harmer
0
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
3.748
270588AE1-091_GEN
Solar/Wind Harmer
3.595
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.866
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.028
959331AF2-224 GEN
Solar/Wind Harmer
2.976
965021AG1-366 GEN
Solar/Wind Harmer
1.417
270485AE1-090_GEN
Solar/Wind Harmer
0.001
970349AG2-230 GEN
Solar/Wind Harmer
6.147
270043AE2-236 GEN
Solar/Wind Harmer
2.609
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
274752CRETE EC ;2U
Adder
4.532
274753CRETE EC ;3U
Adder
4.532
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
9.666
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
3.135
274826FISK ;BP
Adder
5.877
274800UNIV PARK;3U
Adder
3.125
972038AH1-567 GEN2
Adder
0.196
276806AD2-047 C O1
Solar/Wind Harmer
2.116
970941AG2-585 GEN
Solar/Wind Harmer
4.668
274772LINCOLN ;3U
Adder
4.515
972228AH1-698 GEN2
Adder
1.977
274676JOLIET 29;8U
Adder
15.71
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.147
274730ELWOOD EC;6P
Adder
8.714
274734ELWOOD EC;8P
Adder
8.714
274736ELWOOD EC;9P
Adder
8.714
274729ELWOOD EC;1P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
12.079
970513AG2-328 GEN
Solar/Wind Harmer
1.596
970517AG2-330 GEN
Solar/Wind Harmer
9.577
943121AE2-341 GEN
Solar/Wind Harmer
6.132
943591AF1-030 GEN
Solar/Wind Harmer
4.078
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
9.363
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.132
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.599
971617AH1-308 GEN
Solar/Wind Harmer
2.996
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.382
274855GSG-6 ;RU
Solar/Wind Harmer
0.131
274850MENDOTA H;RU
Solar/Wind Harmer
0.042
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.064
944531AF1-118 GEN
Solar/Wind Harmer
16.023
959091AF2-200 GEN
Solar/Wind Harmer
7.133
972236AH1-702 GEN2
Adder
1.116
970571AG2-364 GEN
Solar/Wind Harmer
7.107
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
1.086
276157O29GEN1
Solar/Wind Harmer
0.565
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
942111AE2-223 GEN
Solar/Wind Harmer
1.128
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.299
959611AF2-252 GEN
Solar/Wind Harmer
1.144
965931AG1-462 GEN
Solar/Wind Harmer
8.719
24190002OREGON_ST1
50/50
5.55
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.526
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.659
970621AG2-405 GEN
Solar/Wind Harmer
0.944
970623AG2-406 GEN
Solar/Wind Harmer
0.885
961051AF2-396 GEN
Solar/Wind Harmer
9.384
961051AF2-396 GEN
Solar/Wind Harmer
6.256
246938BC-WTG3
Solar/Wind Harmer
0.168
246937BC-WTG2
Solar/Wind Harmer
0.188
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
4.252
970627AG2-408 GEN
Solar/Wind Harmer
1.276
965681AG1-436 GEN
Solar/Wind Harmer
5.151
965791AG1-447 GEN
Solar/Wind Harmer
3.778
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.71
274803UNIV PARK;6U
Adder
3.135
274888KELLY CRK;1U
Solar/Wind Harmer
0.219
274887GEN-1.85
Solar/Wind Harmer
0.098
276843GEN-1.7
Solar/Wind Harmer
0.121
958011AF2-095 GEN
Solar/Wind Harmer
5.377
274770LINCOLN ;1U
Adder
4.515
274771LINCOLN ;2U
Adder
4.515
972259AH1-714 GEN
Adder
10.138
274674JOLIET 9 ;6U
Adder
8.161
970321AG2-212 GEN
Solar/Wind Harmer
1.596
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.485
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.495
942221AE2-234 GEN
Solar/Wind Harmer
0.018
971573AH1-285 GEN
Solar/Wind Harmer
0.679
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
5.936
274695ROCKY RD ;2P
Adder
5.799
274693ROCKY RD ;1P
Adder
5.742
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.969
274683WAUKEGAN ;8U
Adder
9.246
958491AF2-143 GEN
Solar/Wind Harmer
5.438
962691AG1-118 GEN
Solar/Wind Harmer
10.84
274879MINONK ;1U
Solar/Wind Harmer
0.152
970921AG2-575 GEN
Solar/Wind Harmer
3.608
970921AG2-575 GEN
Solar/Wind Harmer
1.203
942991AE2-321 GEN
Solar/Wind Harmer
4.013
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.161
971335AH1-147 GEN
Solar/Wind Harmer
7.161
971341AH1-150 GEN
Solar/Wind Harmer
7.133
971343AH1-151 GEN
Solar/Wind Harmer
7.133
274856ECOGROVE ;U1
Solar/Wind Harmer
0.084
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.999
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.397
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.137
276646AC1-214 GEN2
Solar/Wind Harmer
0.137
276741O09 GEN1
Solar/Wind Harmer
0.124
276708O09 GEN2
Solar/Wind Harmer
0.124
276782AC1-033 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.231
960971AF2-388 GEN
Solar/Wind Harmer
2.024
960611AF2-352 GEN
Solar/Wind Harmer
1.144
970241AG2-163 GEN
Solar/Wind Harmer
1.972
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
3.085
270031AE2-169
Solar/Wind Harmer
1.851
964611AG1-324 GEN
Solar/Wind Harmer
0.251
971613AH1-306 GEN
Solar/Wind Harmer
1.593
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971231AH1-075 GEN
Solar/Wind Harmer
0.377
960441AF2-335 GEN
Solar/Wind Harmer
3.255
970825AG2-519 GEN
Solar/Wind Harmer
3.6
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.198
241801AE1-079 GEN
Solar/Wind Helper
0.134
241967AE2-285_GEN
Solar/Wind Helper
0.345
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.066
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.368
970291AG2-192 GEN
Solar/Wind Harmer
0.334
276686W4-005 GEN3
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.121
971993AH1-541 GEN
Solar/Wind Harmer
1.533
270377AD1-106 GEN
Solar/Wind Harmer
1.25
276621W2-048 GEN
Solar/Wind Harmer
0.166
276838X2-022 GEN2
Solar/Wind Harmer
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.103
958821AF2-173 GEN
Solar/Wind Harmer
4.521
270004AE1-209 GEN
Solar/Wind Harmer
0.7
962511AG1-100 GEN
Solar/Wind Helper
0.35
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
972211AH1-690 GEN
50/50
445.374
23888502TROY G1
50/50
1.526
23888602TROY G2
50/50
1.526
970817AG2-515 GEN
Solar/Wind Harmer
9.949
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
971549AH1-272 GEN
Solar/Wind Harmer
11.98
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.588
971619AH1-309 GEN
Solar/Wind Harmer
2.081
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
4.385
965041AG1-368 GEN
Solar/Wind Harmer
4.372
965051AG1-369 GEN
Solar/Wind Harmer
2.168
971989AH1-539 GEN
Solar/Wind Harmer
1.862
971769AH1-391 GEN
Solar/Wind Harmer
4.78
270302AB2-170 GEN
Solar/Wind Harmer
0.003
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.58
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
6.147
963791AG1-232 GEN
Solar/Wind Harmer
5.327
971567AH1-282 GEN
Solar/Wind Harmer
5.89
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274805UNIV PK N;1U
Adder
2.728
274811UNIV PK N;7U
Adder
2.722
270071AF1-092 GEN
Solar/Wind Harmer
7.267
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
960591AF2-350 GEN
Solar/Wind Harmer
3.734
274775LINCOLN ;6U
Adder
4.515
274776LINCOLN ;7U
Adder
4.515
274777LINCOLN ;8U
Adder
4.515
971611AH1-305 GEN
Solar/Wind Harmer
2.222
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.867
274687WILL CNTY;4U
Adder
14.867
274675JOLIET 29;7U
Adder
16.292
274675JOLIET 29;7U
Adder
15.71
274728ELWOOD EC;5P
Adder
8.714
274731ELWOOD EC;2P
Adder
8.713
274733ELWOOD EC;3P
Adder
8.713
274735ELWOOD EC;4P
Adder
8.713
970833AG2-524 GEN
Solar/Wind Harmer
4.049
970833AG2-524 GEN
Solar/Wind Harmer
2.699
274746AC1-111 G10
Adder
2.931
274744AC1-111 GEN8
Adder
2.931
276868AE1-113 GEN
Solar/Wind Harmer
0.724
276882AE2-255 GEN
Solar/Wind Harmer
0.422
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.004
971177AH1-047 GEN
Solar/Wind Harmer
2.216
971411AH1-196 GEN
Solar/Wind Harmer
5.375
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.396
971171AH1-044 GEN
Solar/Wind Harmer
7.133
274823ROCKFORD ;21
Adder
9.941
926823AC1-168 GEN
Solar/Wind Harmer
0.603
970169AG2-114 GEN
Solar/Wind Harmer
3.546
276612AE2-035 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.294
971681AH1-341 GEN
Solar/Wind Harmer
5.682
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.056
957751AF2-069 GEN
Solar/Wind Harmer
0.115
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.644
941731AE2-173 GEN
Solar/Wind Harmer
2.892
963841AG1-237 GEN
Solar/Wind Harmer
1.492
946321AF1-296 GEN
Solar/Wind Harmer
1.922
965101AG1-375 GEN
Solar/Wind Harmer
3.421
971609AH1-304 GEN
Solar/Wind Harmer
0.55
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.635
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.121
276848AB2-070 GEN3
Solar/Wind Harmer
0.12
270594AE1-207 GEN
Solar/Wind Harmer
3.716
970115AG2-085 GEN
Solar/Wind Harmer
1.302
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
6.849
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.869
991182J1586 G
External Queue
28.11846351623535
990527J1329
External Queue
2.0234405994415283
990142J1224
External Queue
14.791350364685059
991177J1571 G
External Queue
15.792752265930176
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.633
SIGELTFEXP_SIGE->PJM
CLTF
0.2
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.4
TVALTFEXP_TVA->PJM
CLTF
2.775
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.539
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.946
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187

Details for 02BEAVER-02CARLIL 345.0 kV Ckt 1 line l/o ATSI_P7-1_OEC-345-002_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02CARLIL 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_OEC-345-002_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.31 %
Rating:1745.0 MVA
Rating Type:B
MVA to Mitigate:1907.45
MW Contribution:14.08
Bus #Bus NameTypeMW Contribution
957071AF2-004 GEN
50/50
12.095
23917502WLORG-6
50/50
0.764
23857102WLORG-A
50/50
9.096
23929302BS-PKR
50/50
2.106
241832AE2-181_GEN
Solar/Wind Harmer
1.75
958321AF2-126 GEN
Solar/Wind Harmer
1.366
23906502RICHG2&3
Adder
1.187
270575GUS2 35KV
Solar/Wind Harmer
10.039
270541AE2-072 C
Solar/Wind Harmer
3.99
970217AG2-149 GEN
Solar/Wind Harmer
22.552
270588AE1-091_GEN
Solar/Wind Harmer
6.591
270044AE2-322 C
Solar/Wind Harmer
0.769
270404AC1-167 GEN
Solar/Wind Harmer
0.641
270258AD1-119 GEN
Solar/Wind Harmer
1.565
961961AG1-039 GEN
Solar/Wind Harmer
1.583
958091AF2-103 GEN
Solar/Wind Harmer
0.086
247604X1-042
Adder
0.22
270491AE1-102 GEN2
Solar/Wind Harmer
0.679
24441205WTRV SLR C
Solar/Wind Harmer
0.07
270377AD1-106 GEN
Solar/Wind Harmer
3.082
270191TR4_S_V150
Solar/Wind Harmer
1.46
270247TR4_N_V136
Solar/Wind Harmer
0.414
945111AF1-176 GEN
Solar/Wind Harmer
2.737
270485AE1-090_GEN
Solar/Wind Harmer
0.287
23867002DVBSG1
50/50
10.407
972211AH1-690 GEN
50/50
238.133
241886AC2-103 GEN2
Solar/Wind Harmer
14.419
24191202EL_AA1-006
Adder
0.297
970817AG2-515 GEN
Solar/Wind Harmer
13.044
945411AF1-206 GEN
Solar/Wind Harmer
7.213
270499AE1-146 GEN
Solar/Wind Harmer
2.343
945641AF1-229 GEN
Solar/Wind Harmer
3.229
970159AG2-109 GEN
Solar/Wind Harmer
3.418
270297AD1-101 GEN
Solar/Wind Harmer
1.75
971549AH1-272 GEN
Solar/Wind Harmer
11.155
966831AG1-554 GEN
Solar/Wind Harmer
0.704
971989AH1-539 GEN
Solar/Wind Harmer
7.613
971567AH1-282 GEN
Solar/Wind Harmer
8.024
247607V1-011 GEN
Solar/Wind Harmer
2.098
957201AF2-014 GEN
Solar/Wind Harmer
2.368
270435AC2-044 GEN
Solar/Wind Harmer
1.044
944161AF1-084 GEN
Solar/Wind Harmer
1.106
965041AG1-368 GEN
Solar/Wind Harmer
4.881
965051AG1-369 GEN
Solar/Wind Harmer
2.43
270302AB2-170 GEN
Solar/Wind Harmer
3.966
270317AD1-130_GEN
Solar/Wind Harmer
1.52
971219AH1-069 GEN
Solar/Wind Harmer
0.796
971771AH1-392 GEN
Solar/Wind Harmer
4.129
971769AH1-391 GEN
Solar/Wind Harmer
4.471
270578AF1-285 GEN2
Solar/Wind Harmer
0.204
970179AG2-119 GEN
Solar/Wind Harmer
3.495
963791AG1-232 GEN
Solar/Wind Harmer
5.807
960681AF2-359 GEN
Solar/Wind Harmer
1.625
241982AE2-343 S C
Solar/Wind Helper
0.109
254304AE2-114 C
Solar/Wind Helper
0.104
241997AF1-093 GEN
Solar/Wind Helper
0.121
24642205MAYFLWER
Adder
0.299
970031AG2-029 GEN
Solar/Wind Harmer
14.083
247643Z2-116 C
Solar/Wind Harmer
0.032
959331AF2-224 GEN
Solar/Wind Harmer
4.645
965021AG1-366 GEN
Solar/Wind Harmer
1.08
970065AG2-057 GEN
Solar/Wind Harmer
0.459
942871AE2-306 GEN
Solar/Wind Harmer
0.398
270391AF1-285 GEN3
Solar/Wind Harmer
0.204
270043AE2-236 GEN
Solar/Wind Harmer
2.394
962511AG1-100 GEN
Solar/Wind Helper
0.255
203830AF1-094 GEN
Solar/Wind Helper
0.245
254305AE2-115 C
Solar/Wind Helper
0.104
959441AF2-235 GEN
Solar/Wind Helper
0.115
23917402WLORG-5
50/50
1.527
23917102WLORG-2
50/50
1.505
966321AG1-501 GEN
50/50
1.834
957111AF2-005 GEN
50/50
1.467
24189902OREGON_CT2
50/50
2.208
23856402BAYSG1
50/50
1.196
241885AC2-103 GEN1
Solar/Wind Harmer
14.419
241807AE2-176_GEN
Solar/Wind Harmer
6.057
972253AH1-711 GEN
Adder
43.699
241858AF1-205_GEN
Solar/Wind Harmer
4.928
241808AF1-120 C
Solar/Wind Harmer
1.077
23920202STRYCT
Adder
1.608
241840AF1-064_GEN
Solar/Wind Harmer
1.274
972301AH1-735 GEN
Adder
5.944
23906402RICHG1
Adder
1.189
23906502RICHG2&3
Adder
1.187
270361_3
Solar/Wind Harmer
8.521
960841AF2-375 GEN
Solar/Wind Harmer
3.749
270428AC2-015 C
Solar/Wind Harmer
4.415
247522W1-056 GEN
Solar/Wind Harmer
1.589
970515AG2-329 GEN
Solar/Wind Harmer
10.227
970905AG2-564 GEN
Solar/Wind Harmer
3.497
944231AF1-091 GEN
Solar/Wind Harmer
2.19
241847AF2-150_GEN
Solar/Wind Harmer
2.294
246936BC-WTG1
Solar/Wind Harmer
2.043
270489AE1-102 GEN1
Solar/Wind Harmer
0.679
965421AG1-410 GEN
Solar/Wind Harmer
15.499
24695305TIMB G C
Solar/Wind Harmer
2.781
270449AD2-020 GEN
Solar/Wind Harmer
1.385
943021AE2-325 GEN
Solar/Wind Harmer
1.799
247521TR3_G114
Solar/Wind Harmer
1.636
270246TR4_N_V150
Solar/Wind Harmer
0.414
945111AF1-176 GEN
Solar/Wind Harmer
8.634
270505AE1-170 C O1
Solar/Wind Harmer
7.249
270462AD2-086
Solar/Wind Harmer
3.299
24639705ELKHART HY
Adder
0.072
270063AE2-323 C
Solar/Wind Harmer
1.038
971221AH1-070 GEN
Solar/Wind Harmer
0.796
965011AG1-365 GEN
Solar/Wind Harmer
4.645
241813AF1-122_GEN
Solar/Wind Harmer
2.935
270223U2-072_GEN1
Solar/Wind Harmer
0.868
270578AF1-285 GEN2
Solar/Wind Harmer
0.531
270391AF1-285 GEN3
Solar/Wind Harmer
0.531
961971AG1-040 GEN
Solar/Wind Helper
0.251
203835AF1-098 GEN
Solar/Wind Helper
0.992
241966AE1-183 GEN
Solar/Wind Helper
0.121
203860AG1-193 C
Solar/Wind Helper
0.116
254303AC2-168 GEN
Solar/Wind Helper
0.071
23917202WLORG-3
50/50
1.553
23917302WLORG-4
50/50
1.519
966311AG1-500 GEN
50/50
141.29
23857202WLORG-B
50/50
9.372
24190002OREGON_ST1
50/50
2.971
24189802OREGON_CT1
50/50
2.254
241996AE2-282_GEN
Solar/Wind Harmer
1.931
971677AH1-339 GEN
Solar/Wind Harmer
6.773
270007AE1-245 C
Solar/Wind Harmer
3.147
942801AE2-298 GEN
Solar/Wind Harmer
0.797
246938BC-WTG3
Solar/Wind Harmer
2.078
246937BC-WTG2
Solar/Wind Harmer
2.043
971231AH1-075 GEN
Solar/Wind Harmer
0.399
961051AF2-396 GEN
Solar/Wind Harmer
7.783
961051AF2-396 GEN
Solar/Wind Harmer
3.62
960981AF2-389 GEN
Solar/Wind Harmer
0.728
957891AF2-083 GEN
Solar/Wind Harmer
1.625
247620Y3-023
Adder
0.218
270216AD2-079_GEN
Solar/Wind Harmer
0.283
970611AG2-400 GEN
Solar/Wind Harmer
4.645
971201AH1-060 GEN
Solar/Wind Harmer
0.917
270526AF1-158 GEN
Solar/Wind Harmer
2.042
24441505OLIV SLR
Solar/Wind Harmer
0.06
270224U2-072_GEN2
Solar/Wind Harmer
0.868
270227U2-072_GEN3
Solar/Wind Harmer
0.868
270228U2-072_GEN4
Solar/Wind Harmer
0.868
270231U2-072_GEN5
Solar/Wind Harmer
0.868
241960AC2-195 GEN
Solar/Wind Harmer
1.215
965681AG1-436 GEN
Solar/Wind Harmer
5.376
965791AG1-447 GEN
Solar/Wind Harmer
2.75
203947AF1-006 C
Solar/Wind Helper
0.283
241967AE2-285_GEN
Solar/Wind Helper
0.314
241801AE1-079 GEN
Solar/Wind Helper
0.122
203980AG1-197 GEN
Solar/Wind Helper
0.188
241985AE1-237 GEN
Solar/Wind Helper
0.122
203979AG1-198 GEN
Solar/Wind Helper
0.147
962101AG1-054 GEN
Solar/Wind Helper
0.304
990527J1329
External Queue
1.536989450454712
990142J1224
External Queue
11.235392570495605
991177J1571 G
External Queue
13.065269470214844
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.4
MECLTFEXP_MEC->PJM
CLTF
5.472
SIGELTFEXP_SIGE->PJM
CLTF
0.142
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.536
TVALTFEXP_TVA->PJM
CLTF
1.857
CPLELTFEXP_CPLE->PJM
CLTF
0.14
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.236
NYPJM->LTFIMP_NY
CLTF
1.797
LGEELTFEXP_LGEE->PJM
CLTF
1.709
WECLTFEXP_WEC->PJM
CLTF
1.408
AG2-052LTFEXP_AG2-052->PJM
LTF
0.091
AH1-155LTFEXP_AH1-155->PJM
LTF
0.136

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-901_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-901_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.76 %
Rating:1720.0 MVA
Rating Type:B
MVA to Mitigate:1956.7
MW Contribution:13.03
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
9.149
972211AH1-690 GEN
50/50
209.151
241886AC2-103 GEN2
Solar/Wind Harmer
12.757
970817AG2-515 GEN
Solar/Wind Harmer
11.458
24191202EL_AA1-006
Adder
0.247
945411AF1-206 GEN
Solar/Wind Harmer
6.338
270499AE1-146 GEN
Solar/Wind Harmer
2.056
945641AF1-229 GEN
Solar/Wind Harmer
2.848
970159AG2-109 GEN
Solar/Wind Harmer
2.554
270297AD1-101 GEN
Solar/Wind Harmer
1.58
971549AH1-272 GEN
Solar/Wind Harmer
10.147
966831AG1-554 GEN
Solar/Wind Harmer
0.634
971989AH1-539 GEN
Solar/Wind Harmer
6.852
247607V1-011 GEN
Solar/Wind Harmer
1.919
971567AH1-282 GEN
Solar/Wind Harmer
7.189
957201AF2-014 GEN
Solar/Wind Harmer
2.171
270435AC2-044 GEN
Solar/Wind Harmer
0.957
944161AF1-084 GEN
Solar/Wind Harmer
1.019
965041AG1-368 GEN
Solar/Wind Harmer
4.498
965051AG1-369 GEN
Solar/Wind Harmer
2.239
270302AB2-170 GEN
Solar/Wind Harmer
3.666
270317AD1-130_GEN
Solar/Wind Harmer
1.405
203846AF2-130 C
Solar/Wind Helper
0.272
203804AE2-113_GEN
Solar/Wind Helper
0.933
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
241997AF1-093 GEN
Solar/Wind Helper
0.118
23917202WLORG-3
50/50
1.38
23917302WLORG-4
50/50
1.349
966311AG1-500 GEN
50/50
125.486
24190002OREGON_ST1
50/50
2.61
24189802OREGON_CT1
50/50
1.98
241996AE2-282_GEN
Solar/Wind Harmer
1.697
23857202WLORG-B
Adder
4.429
971677AH1-339 GEN
Solar/Wind Harmer
5.947
270007AE1-245 C
Solar/Wind Harmer
2.879
942801AE2-298 GEN
Solar/Wind Harmer
0.729
246938BC-WTG3
Solar/Wind Harmer
1.905
246937BC-WTG2
Solar/Wind Harmer
1.873
961051AF2-396 GEN
Solar/Wind Harmer
7.181
961051AF2-396 GEN
Solar/Wind Harmer
3.34
971231AH1-075 GEN
Solar/Wind Harmer
0.362
960981AF2-389 GEN
Solar/Wind Harmer
0.673
957891AF2-083 GEN
Solar/Wind Harmer
1.501
247620Y3-023
Adder
0.202
270216AD2-079_GEN
Solar/Wind Harmer
0.262
970611AG2-400 GEN
Solar/Wind Harmer
4.301
203947AF1-006 C
Solar/Wind Helper
0.458
203980AG1-197 GEN
Solar/Wind Helper
0.296
203979AG1-198 GEN
Solar/Wind Helper
0.229
241967AE2-285_GEN
Solar/Wind Helper
0.308
241801AE1-079 GEN
Solar/Wind Helper
0.12
241985AE1-237 GEN
Solar/Wind Helper
0.119
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.295
23917402WLORG-5
50/50
1.356
23917102WLORG-2
50/50
1.337
24189902OREGON_CT2
50/50
1.94
23856402BAYSG1
50/50
1.043
241885AC2-103 GEN1
Solar/Wind Harmer
12.757
241807AE2-176_GEN
Solar/Wind Harmer
5.062
972253AH1-711 GEN
Adder
38.383
241858AF1-205_GEN
Solar/Wind Harmer
4.326
241808AF1-120 C
Solar/Wind Harmer
0.946
23920202STRYCT
Adder
1.415
241840AF1-064_GEN
Solar/Wind Harmer
1.119
972301AH1-735 GEN
Adder
5.258
23906402RICHG1
Adder
1.052
23906502RICHG2&3
Adder
1.05
270361_3
Solar/Wind Harmer
7.454
960841AF2-375 GEN
Solar/Wind Harmer
3.283
966321AG1-501 GEN
Adder
0.867
957111AF2-005 GEN
Adder
0.693
270428AC2-015 C
Solar/Wind Harmer
3.75
247522W1-056 GEN
Solar/Wind Harmer
1.41
970515AG2-329 GEN
Solar/Wind Harmer
9.037
970905AG2-564 GEN
Solar/Wind Harmer
2.954
944231AF1-091 GEN
Solar/Wind Harmer
1.993
241847AF2-150_GEN
Solar/Wind Harmer
1.989
246936BC-WTG1
Solar/Wind Harmer
1.873
270489AE1-102 GEN1
Solar/Wind Harmer
0.622
965421AG1-410 GEN
Solar/Wind Harmer
14.219
24695305TIMB G C
Solar/Wind Harmer
2.555
270449AD2-020 GEN
Solar/Wind Harmer
1.277
943021AE2-325 GEN
Solar/Wind Harmer
1.659
247521TR3_G114
Solar/Wind Harmer
1.508
270246TR4_N_V150
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
7.974
270505AE1-170 C O1
Solar/Wind Harmer
6.696
270462AD2-086
Solar/Wind Harmer
3.05
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.96
965011AG1-365 GEN
Solar/Wind Harmer
4.301
961971AG1-040 GEN
Solar/Wind Helper
0.397
203835AF1-098 GEN
Solar/Wind Helper
1.566
203860AG1-193 C
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.118
203954AE2-126 C
Solar/Wind Helper
0.23
254303AC2-168 GEN
Solar/Wind Helper
0.068
957071AF2-004 GEN
50/50
10.742
23929302BS-PKR
50/50
1.836
241832AE2-181_GEN
Solar/Wind Harmer
1.539
958321AF2-126 GEN
Solar/Wind Harmer
1.2
23906502RICHG2&3
Adder
1.05
270575GUS2 35KV
Solar/Wind Harmer
8.781
23857102WLORG-A
Adder
4.299
270541AE2-072 C
Solar/Wind Harmer
3.537
970217AG2-149 GEN
Solar/Wind Harmer
19.929
270588AE1-091_GEN
Solar/Wind Harmer
5.941
270044AE2-322 C
Solar/Wind Harmer
0.699
270404AC1-167 GEN
Solar/Wind Harmer
0.582
270258AD1-119 GEN
Solar/Wind Harmer
1.426
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.202
961961AG1-039 GEN
Solar/Wind Harmer
1.372
270491AE1-102 GEN2
Solar/Wind Harmer
0.622
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.793
270191TR4_S_V150
Solar/Wind Harmer
1.345
270247TR4_N_V136
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
2.527
270485AE1-090_GEN
Solar/Wind Harmer
0.265
24642205MAYFLWER
Adder
0.277
970031AG2-029 GEN
Solar/Wind Harmer
13.034
247643Z2-116 C
Solar/Wind Harmer
0.03
959331AF2-224 GEN
Solar/Wind Harmer
4.301
965021AG1-366 GEN
Solar/Wind Harmer
1
962511AG1-100 GEN
Solar/Wind Helper
0.409
203830AF1-094 GEN
Solar/Wind Helper
0.382
959441AF2-235 GEN
Solar/Wind Helper
0.168
20334926Z1-069 C
Solar/Wind Helper
0.688
254305AE2-115 C
Solar/Wind Helper
0.102
990527J1329
External Queue
1.3126888275146484
990142J1224
External Queue
9.595755577087402
991177J1571 G
External Queue
11.149422645568848
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.464
MECLTFEXP_MEC->PJM
CLTF
5.219
SIGELTFEXP_SIGE->PJM
CLTF
0.139
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.004
TVALTFEXP_TVA->PJM
CLTF
1.884
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.563
NYPJM->LTFIMP_NY
CLTF
1.974
LGEELTFEXP_LGEE->PJM
CLTF
1.688
WECLTFEXP_WEC->PJM
CLTF
1.329
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-007A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-007A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1967.82
MW Contribution:13.03
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.431
23917102WLORG-2
50/50
1.41
24189902OREGON_CT2
50/50
1.967
241885AC2-103 GEN1
Solar/Wind Harmer
13.312
241807AE2-176_GEN
Solar/Wind Harmer
4.79
972253AH1-711 GEN
Adder
38.846
23917202WLORG-3
50/50
1.455
23917302WLORG-4
50/50
1.423
966311AG1-500 GEN
50/50
132.376
24190002OREGON_ST1
50/50
2.646
24189802OREGON_CT1
50/50
2.007
241996AE2-282_GEN
Solar/Wind Harmer
1.708
971677AH1-339 GEN
Solar/Wind Harmer
5.827
270007AE1-245 C
Solar/Wind Harmer
2.868
957071AF2-004 GEN
50/50
11.332
23929302BS-PKR
Adder
1.735
241832AE2-181_GEN
Solar/Wind Harmer
1.549
958321AF2-126 GEN
Solar/Wind Harmer
1.204
23906502RICHG2&3
Adder
1.054
270575GUS2 35KV
Solar/Wind Harmer
8.659
270541AE2-072 C
Solar/Wind Harmer
3.532
970217AG2-149 GEN
Solar/Wind Harmer
19.363
270588AE1-091_GEN
Solar/Wind Harmer
5.847
270044AE2-322 C
Solar/Wind Harmer
0.698
270404AC1-167 GEN
Solar/Wind Harmer
0.581
270258AD1-119 GEN
Solar/Wind Harmer
1.423
247604X1-042
Adder
0.202
958091AF2-103 GEN
Solar/Wind Harmer
0.078
270491AE1-102 GEN2
Solar/Wind Harmer
0.62
24441205WTRV SLR C
Solar/Wind Harmer
0.064
945111AF1-176 GEN
Solar/Wind Harmer
2.531
270191TR4_S_V150
Solar/Wind Harmer
1.341
270247TR4_N_V136
Solar/Wind Harmer
0.38
961961AG1-039 GEN
Solar/Wind Harmer
1.258
24642205MAYFLWER
Adder
0.277
270377AD1-106 GEN
Solar/Wind Harmer
2.69
270485AE1-090_GEN
Solar/Wind Harmer
0.263
970031AG2-029 GEN
Solar/Wind Harmer
13.034
247643Z2-116 C
Solar/Wind Harmer
0.03
962511AG1-100 GEN
Solar/Wind Helper
0.406
203830AF1-094 GEN
Solar/Wind Helper
0.379
959441AF2-235 GEN
Solar/Wind Helper
0.167
20334926Z1-069 C
Solar/Wind Helper
0.684
254305AE2-115 C
Solar/Wind Helper
0.101
241858AF1-205_GEN
Solar/Wind Harmer
4.354
241808AF1-120 C
Solar/Wind Harmer
0.952
23920202STRYCT
Adder
1.423
241840AF1-064_GEN
Solar/Wind Harmer
1.123
972301AH1-735 GEN
Adder
5.278
23906402RICHG1
Adder
1.056
23906502RICHG2&3
Adder
1.054
270361_3
Solar/Wind Harmer
7.35
960841AF2-375 GEN
Solar/Wind Harmer
3.239
270428AC2-015 C
Solar/Wind Harmer
3.47
247522W1-056 GEN
Solar/Wind Harmer
1.38
970515AG2-329 GEN
Solar/Wind Harmer
8.781
970905AG2-564 GEN
Solar/Wind Harmer
2.663
944231AF1-091 GEN
Solar/Wind Harmer
1.994
246936BC-WTG1
Solar/Wind Harmer
1.867
270489AE1-102 GEN1
Solar/Wind Harmer
0.62
965421AG1-410 GEN
Solar/Wind Harmer
14.177
24695305TIMB G C
Solar/Wind Harmer
2.547
270449AD2-020 GEN
Solar/Wind Harmer
1.279
943021AE2-325 GEN
Solar/Wind Harmer
1.662
945111AF1-176 GEN
Solar/Wind Harmer
7.986
247521TR3_G114
Solar/Wind Harmer
1.503
270246TR4_N_V150
Solar/Wind Harmer
0.38
270505AE1-170 C O1
Solar/Wind Harmer
6.706
241847AF2-150_GEN
Solar/Wind Harmer
1.823
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.96
270462AD2-086
Solar/Wind Harmer
3.029
961971AG1-040 GEN
Solar/Wind Helper
0.395
203835AF1-098 GEN
Solar/Wind Helper
1.556
203860AG1-193 C
Solar/Wind Helper
0.17
241966AE1-183 GEN
Solar/Wind Helper
0.117
203954AE2-126 C
Solar/Wind Helper
0.228
254303AC2-168 GEN
Solar/Wind Helper
0.067
23867002DVBSG1
50/50
9.378
972211AH1-690 GEN
50/50
212.091
241886AC2-103 GEN2
Solar/Wind Harmer
13.312
970817AG2-515 GEN
Solar/Wind Harmer
11.575
945411AF1-206 GEN
Solar/Wind Harmer
6.379
24191202EL_AA1-006
Adder
0.223
270499AE1-146 GEN
Solar/Wind Harmer
2.029
945641AF1-229 GEN
Solar/Wind Harmer
2.819
270297AD1-101 GEN
Solar/Wind Harmer
1.573
971549AH1-272 GEN
Solar/Wind Harmer
10.193
966831AG1-554 GEN
Solar/Wind Harmer
0.62
971989AH1-539 GEN
Solar/Wind Harmer
6.706
247607V1-011 GEN
Solar/Wind Harmer
1.912
957201AF2-014 GEN
Solar/Wind Harmer
2.164
270435AC2-044 GEN
Solar/Wind Harmer
0.954
944161AF1-084 GEN
Solar/Wind Harmer
1.021
971567AH1-282 GEN
Solar/Wind Harmer
6.891
970159AG2-109 GEN
Solar/Wind Harmer
1.835
965041AG1-368 GEN
Solar/Wind Harmer
4.486
965051AG1-369 GEN
Solar/Wind Harmer
2.232
270302AB2-170 GEN
Solar/Wind Harmer
3.641
270317AD1-130_GEN
Solar/Wind Harmer
1.396
203846AF2-130 C
Solar/Wind Helper
0.27
203804AE2-113_GEN
Solar/Wind Helper
0.928
241982AE2-343 S C
Solar/Wind Helper
0.106
254304AE2-114 C
Solar/Wind Helper
0.101
241997AF1-093 GEN
Solar/Wind Helper
0.117
942801AE2-298 GEN
Solar/Wind Harmer
0.727
246938BC-WTG3
Solar/Wind Harmer
1.899
246937BC-WTG2
Solar/Wind Harmer
1.867
961051AF2-396 GEN
Solar/Wind Harmer
7.193
961051AF2-396 GEN
Solar/Wind Harmer
3.346
960981AF2-389 GEN
Solar/Wind Harmer
0.674
957891AF2-083 GEN
Solar/Wind Harmer
1.504
247620Y3-023
Adder
0.202
971231AH1-075 GEN
Solar/Wind Harmer
0.349
270216AD2-079_GEN
Solar/Wind Harmer
0.262
203947AF1-006 C
Solar/Wind Helper
0.455
203980AG1-197 GEN
Solar/Wind Helper
0.294
203979AG1-198 GEN
Solar/Wind Helper
0.227
241801AE1-079 GEN
Solar/Wind Helper
0.119
241967AE2-285_GEN
Solar/Wind Helper
0.305
241985AE1-237 GEN
Solar/Wind Helper
0.118
946381AF1-302 GEN
Solar/Wind Helper
0.109
238217AF1-153 C O1
Solar/Wind Helper
0.117
962101AG1-054 GEN
Solar/Wind Helper
0.293
990527J1329
External Queue
1.333598017692566
990142J1224
External Queue
9.748601913452148
991177J1571 G
External Queue
11.313738822937012
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.887
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.407
MECLTFEXP_MEC->PJM
CLTF
5.205
SIGELTFEXP_SIGE->PJM
CLTF
0.138
LAGNLTFEXP_LAGN->PJM
CLTF
4.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.967
TVALTFEXP_TVA->PJM
CLTF
1.87
CPLELTFEXP_CPLE->PJM
CLTF
0.326
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.394
NYPJM->LTFIMP_NY
CLTF
1.964
LGEELTFEXP_LGEE->PJM
CLTF
1.675
WECLTFEXP_WEC->PJM
CLTF
1.327
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-031_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-031_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.84 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1893.72
MW Contribution:12.95
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.318
23917102WLORG-2
50/50
1.299
24189902OREGON_CT2
50/50
1.916
23856402BAYSG1
50/50
1.035
241885AC2-103 GEN1
Solar/Wind Harmer
12.452
241807AE2-176_GEN
Solar/Wind Harmer
5.144
972253AH1-711 GEN
Adder
37.939
241858AF1-205_GEN
Solar/Wind Harmer
4.286
241808AF1-120 C
Solar/Wind Harmer
0.937
23920202STRYCT
Adder
1.402
241840AF1-064_GEN
Solar/Wind Harmer
1.11
966321AG1-501 GEN
Adder
1.036
957111AF2-005 GEN
Adder
0.829
972301AH1-735 GEN
Adder
5.214
23906402RICHG1
Adder
1.043
23906502RICHG2&3
Adder
1.042
270361_3
Solar/Wind Harmer
7.442
960841AF2-375 GEN
Solar/Wind Harmer
3.277
270428AC2-015 C
Solar/Wind Harmer
3.83
247522W1-056 GEN
Solar/Wind Harmer
1.411
970515AG2-329 GEN
Solar/Wind Harmer
9.065
970905AG2-564 GEN
Solar/Wind Harmer
3.041
944231AF1-091 GEN
Solar/Wind Harmer
1.98
241847AF2-150_GEN
Solar/Wind Harmer
2.034
246936BC-WTG1
Solar/Wind Harmer
1.863
270489AE1-102 GEN1
Solar/Wind Harmer
0.619
965421AG1-410 GEN
Solar/Wind Harmer
14.14
24695305TIMB G C
Solar/Wind Harmer
2.541
270449AD2-020 GEN
Solar/Wind Harmer
1.268
943021AE2-325 GEN
Solar/Wind Harmer
1.647
247521TR3_G114
Solar/Wind Harmer
1.5
270246TR4_N_V150
Solar/Wind Harmer
0.379
945111AF1-176 GEN
Solar/Wind Harmer
7.917
270505AE1-170 C O1
Solar/Wind Harmer
6.647
270462AD2-086
Solar/Wind Harmer
3.037
24639705ELKHART HY
Adder
0.066
270063AE2-323 C
Solar/Wind Harmer
0.954
961971AG1-040 GEN
Solar/Wind Helper
0.397
203835AF1-098 GEN
Solar/Wind Helper
1.564
203860AG1-193 C
Solar/Wind Helper
0.171
241966AE1-183 GEN
Solar/Wind Helper
0.118
203954AE2-126 C
Solar/Wind Helper
0.229
254303AC2-168 GEN
Solar/Wind Helper
0.068
957071AF2-004 GEN
50/50
10.437
23929302BS-PKR
50/50
1.821
241832AE2-181_GEN
Solar/Wind Harmer
1.524
958321AF2-126 GEN
Solar/Wind Harmer
1.19
23857102WLORG-A
Adder
5.14
23906502RICHG2&3
Adder
1.042
270575GUS2 35KV
Solar/Wind Harmer
8.767
270541AE2-072 C
Solar/Wind Harmer
3.515
970217AG2-149 GEN
Solar/Wind Harmer
19.989
270588AE1-091_GEN
Solar/Wind Harmer
5.936
270044AE2-322 C
Solar/Wind Harmer
0.695
270404AC1-167 GEN
Solar/Wind Harmer
0.579
270258AD1-119 GEN
Solar/Wind Harmer
1.418
961961AG1-039 GEN
Solar/Wind Harmer
1.403
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.2
270491AE1-102 GEN2
Solar/Wind Harmer
0.619
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.813
270191TR4_S_V150
Solar/Wind Harmer
1.338
270247TR4_N_V136
Solar/Wind Harmer
0.379
945111AF1-176 GEN
Solar/Wind Harmer
2.509
270485AE1-090_GEN
Solar/Wind Harmer
0.264
24642205MAYFLWER
Adder
0.275
970031AG2-029 GEN
Solar/Wind Harmer
12.948
962511AG1-100 GEN
Solar/Wind Helper
0.408
203830AF1-094 GEN
Solar/Wind Helper
0.381
959441AF2-235 GEN
Solar/Wind Helper
0.168
20334926Z1-069 C
Solar/Wind Helper
0.686
254305AE2-115 C
Solar/Wind Helper
0.102
23867002DVBSG1
50/50
8.998
972211AH1-690 GEN
50/50
206.563
24191202EL_AA1-006
50/50
0.275
241886AC2-103 GEN2
Solar/Wind Harmer
12.452
970817AG2-515 GEN
Solar/Wind Harmer
11.334
945411AF1-206 GEN
Solar/Wind Harmer
6.279
270499AE1-146 GEN
Solar/Wind Harmer
2.052
945641AF1-229 GEN
Solar/Wind Harmer
2.838
970159AG2-109 GEN
Solar/Wind Harmer
2.868
270297AD1-101 GEN
Solar/Wind Harmer
1.572
971549AH1-272 GEN
Solar/Wind Harmer
10.061
966831AG1-554 GEN
Solar/Wind Harmer
0.634
971989AH1-539 GEN
Solar/Wind Harmer
6.861
971567AH1-282 GEN
Solar/Wind Harmer
7.246
247607V1-011 GEN
Solar/Wind Harmer
1.909
957201AF2-014 GEN
Solar/Wind Harmer
2.159
270435AC2-044 GEN
Solar/Wind Harmer
0.952
944161AF1-084 GEN
Solar/Wind Harmer
1.011
965041AG1-368 GEN
Solar/Wind Harmer
4.473
965051AG1-369 GEN
Solar/Wind Harmer
2.227
270302AB2-170 GEN
Solar/Wind Harmer
3.651
270317AD1-130_GEN
Solar/Wind Harmer
1.4
203846AF2-130 C
Solar/Wind Helper
0.271
203804AE2-113_GEN
Solar/Wind Helper
0.931
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
241997AF1-093 GEN
Solar/Wind Helper
0.118
23917202WLORG-3
50/50
1.34
23917302WLORG-4
50/50
1.311
966311AG1-500 GEN
50/50
121.92
24190002OREGON_ST1
50/50
2.577
24189802OREGON_CT1
50/50
1.955
241996AE2-282_GEN
Solar/Wind Harmer
1.681
23857202WLORG-B
Adder
5.296
971677AH1-339 GEN
Solar/Wind Harmer
5.951
270007AE1-245 C
Solar/Wind Harmer
2.864
942801AE2-298 GEN
Solar/Wind Harmer
0.726
246938BC-WTG3
Solar/Wind Harmer
1.895
246937BC-WTG2
Solar/Wind Harmer
1.863
971231AH1-075 GEN
Solar/Wind Harmer
0.364
961051AF2-396 GEN
Solar/Wind Harmer
7.128
961051AF2-396 GEN
Solar/Wind Harmer
3.316
960981AF2-389 GEN
Solar/Wind Harmer
0.668
957891AF2-083 GEN
Solar/Wind Harmer
1.491
247620Y3-023
Adder
0.2
203947AF1-006 C
Solar/Wind Helper
0.458
203980AG1-197 GEN
Solar/Wind Helper
0.295
203979AG1-198 GEN
Solar/Wind Helper
0.229
241801AE1-079 GEN
Solar/Wind Helper
0.119
241967AE2-285_GEN
Solar/Wind Helper
0.307
241985AE1-237 GEN
Solar/Wind Helper
0.119
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.117
962101AG1-054 GEN
Solar/Wind Helper
0.294
990527J1329
External Queue
1.2952468395233154
990142J1224
External Queue
9.468253135681152
991177J1571 G
External Queue
11.006390571594238
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.973
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.443
MECLTFEXP_MEC->PJM
CLTF
5.19
SIGELTFEXP_SIGE->PJM
CLTF
0.138
LAGNLTFEXP_LAGN->PJM
CLTF
4.096
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.011
TVALTFEXP_TVA->PJM
CLTF
1.879
CPLELTFEXP_CPLE->PJM
CLTF
0.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.428
NYPJM->LTFIMP_NY
CLTF
1.967
LGEELTFEXP_LGEE->PJM
CLTF
1.683
WECLTFEXP_WEC->PJM
CLTF
1.321
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.127

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-002_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-002_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.17 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:3270.93
MW Contribution:18.11
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.92
23917102WLORG-2
50/50
1.892
24189902OREGON_CT2
50/50
2.76
23856402BAYSG1
50/50
1.489
957071AF2-004 GEN
50/50
15.205
23929302BS-PKR
50/50
2.62
23857102WLORG-A
Adder
8.207
241832AE2-181_GEN
Solar/Wind Harmer
2.188
958321AF2-126 GEN
Solar/Wind Harmer
1.707
23906502RICHG2&3
Adder
1.489
270575GUS2 35KV
Solar/Wind Harmer
12.516
270541AE2-072 C
Solar/Wind Harmer
5.011
970217AG2-149 GEN
Solar/Wind Harmer
28.273
270588AE1-091_GEN
Solar/Wind Harmer
8.353
270044AE2-322 C
Solar/Wind Harmer
0.979
270404AC1-167 GEN
Solar/Wind Harmer
0.816
270258AD1-119 GEN
Solar/Wind Harmer
1.996
961961AG1-039 GEN
Solar/Wind Harmer
1.964
958091AF2-103 GEN
Solar/Wind Harmer
0.109
247604X1-042
Adder
0.282
270491AE1-102 GEN2
Solar/Wind Harmer
0.868
24441205WTRV SLR C
Solar/Wind Harmer
0.089
270377AD1-106 GEN
Solar/Wind Harmer
3.918
270191TR4_S_V150
Solar/Wind Harmer
1.873
270247TR4_N_V136
Solar/Wind Harmer
0.531
945111AF1-176 GEN
Solar/Wind Harmer
3.515
270485AE1-090_GEN
Solar/Wind Harmer
0.369
24642205MAYFLWER
Adder
0.384
970031AG2-029 GEN
Solar/Wind Harmer
18.113
247643Z2-116 C
Solar/Wind Harmer
0.042
959331AF2-224 GEN
Solar/Wind Harmer
5.975
965021AG1-366 GEN
Solar/Wind Harmer
1.39
970065AG2-057 GEN
Solar/Wind Harmer
0.575
942871AE2-306 GEN
Solar/Wind Harmer
0.514
270391AF1-285 GEN3
Solar/Wind Harmer
0.264
270043AE2-236 GEN
Solar/Wind Harmer
3.089
23867002DVBSG1
50/50
13.011
972211AH1-690 GEN
50/50
297.552
241886AC2-103 GEN2
Solar/Wind Harmer
18.089
24191202EL_AA1-006
Adder
0.36
970817AG2-515 GEN
Solar/Wind Harmer
16.3
945411AF1-206 GEN
Solar/Wind Harmer
9.015
270499AE1-146 GEN
Solar/Wind Harmer
2.926
945641AF1-229 GEN
Solar/Wind Harmer
4.044
970159AG2-109 GEN
Solar/Wind Harmer
3.924
270297AD1-101 GEN
Solar/Wind Harmer
2.22
971549AH1-272 GEN
Solar/Wind Harmer
14.209
966831AG1-554 GEN
Solar/Wind Harmer
0.892
971989AH1-539 GEN
Solar/Wind Harmer
9.641
247607V1-011 GEN
Solar/Wind Harmer
2.681
971567AH1-282 GEN
Solar/Wind Harmer
10.136
957201AF2-014 GEN
Solar/Wind Harmer
3.029
270435AC2-044 GEN
Solar/Wind Harmer
1.336
944161AF1-084 GEN
Solar/Wind Harmer
1.419
965041AG1-368 GEN
Solar/Wind Harmer
6.263
965051AG1-369 GEN
Solar/Wind Harmer
3.117
270302AB2-170 GEN
Solar/Wind Harmer
5.097
270317AD1-130_GEN
Solar/Wind Harmer
1.954
971771AH1-392 GEN
Solar/Wind Harmer
5.317
971769AH1-391 GEN
Solar/Wind Harmer
5.763
270578AF1-285 GEN2
Solar/Wind Harmer
0.264
960681AF2-359 GEN
Solar/Wind Harmer
2.098
963791AG1-232 GEN
Solar/Wind Harmer
7.497
971347AH1-153 GEN
Solar/Wind Harmer
8.3
970179AG2-119 GEN
Solar/Wind Harmer
4.411
971219AH1-069 GEN
Solar/Wind Harmer
0.907
270536AF1-215 GEN2
Solar/Wind Harmer
2.387
270071AF1-092 GEN
Solar/Wind Harmer
7.858
958391AF2-133 GEN
Solar/Wind Harmer
4.646
274814UNIV PK N;0U
Adder
2.586
274807UNIV PK N;3U
Adder
2.581
274805UNIV PK N;1U
Adder
2.569
274811UNIV PK N;7U
Adder
2.564
972037AH1-567 GEN1
Adder
0.093
274827FISK ;RP
Adder
3.924
960591AF2-350 GEN
Solar/Wind Harmer
5.042
274775LINCOLN ;6U
Adder
3.125
274776LINCOLN ;7U
Adder
3.125
274777LINCOLN ;8U
Adder
3.125
270024AE2-089 GEN
Solar/Wind Harmer
2.366
972227AH1-698 GEN1
Adder
1.311
274687WILL CNTY;4U
Adder
14.004
274687WILL CNTY;4U
Adder
14.004
274675JOLIET 29;7U
Adder
15.345
274675JOLIET 29;7U
Adder
14.797
274731ELWOOD EC;2P
Adder
8.208
274733ELWOOD EC;3P
Adder
8.208
274735ELWOOD EC;4P
Adder
8.208
274728ELWOOD EC;5P
Adder
8.208
274746AC1-111 G10
Adder
2.761
274744AC1-111 GEN8
Adder
2.761
24729505KEY G4
Adder
3.179
274823ROCKFORD ;21
Adder
9.356
203846AF2-130 C
Solar/Wind Helper
0.325
241982AE2-343 S C
Solar/Wind Helper
0.145
254304AE2-114 C
Solar/Wind Helper
0.138
241997AF1-093 GEN
Solar/Wind Helper
0.16
203804AE2-113_GEN
Solar/Wind Helper
1.128
203855AF2-088 C
Solar/Wind Helper
0.087
20090526Q36
Solar/Wind Helper
0.548
203993AD2-133_GEN1
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.29
20092526R32
Solar/Wind Helper
0.563
203961AE2-224 GEN
Solar/Wind Helper
1.164
941231AE2-117 GEN
Solar/Wind Helper
0.227
970833AG2-524 GEN
Solar/Wind Harmer
1.943
970833AG2-524 GEN
Solar/Wind Harmer
0.904
970349AG2-230 GEN
Solar/Wind Harmer
8.3
270535AF1-215 GEN1
Solar/Wind Harmer
2.387
972231SS25-0005
Solar/Wind Harmer
4.917
972181SS23-001
Solar/Wind Harmer
3.073
274752CRETE EC ;2U
Adder
2.532
274753CRETE EC ;3U
Adder
2.532
964401AG1-302 GEN
Solar/Wind Harmer
4.687
274724RIVER EC ;11
Adder
9.105
959141AF2-205 GEN
Solar/Wind Harmer
3.076
274802UNIV PARK;5U
Adder
2.953
274826FISK ;BP
Adder
5.536
274800UNIV PARK;3U
Adder
2.944
972038AH1-567 GEN2
Adder
0.184
276772AC2-154 GEN
Solar/Wind Harmer
1.406
276806AD2-047 C O1
Solar/Wind Harmer
5.394
970941AG2-585 GEN
Solar/Wind Harmer
6.303
274772LINCOLN ;3U
Adder
3.125
971617AH1-308 GEN
Solar/Wind Harmer
2.93
972228AH1-698 GEN2
Adder
1.862
274676JOLIET 29;8U
Adder
14.797
276897AD1-100 C
Solar/Wind Harmer
14.503
939351AE1-166 GEN
Solar/Wind Harmer
2.963
276893AG1-478 C
Solar/Wind Harmer
0.209
970707AG2-453 GEN
Solar/Wind Harmer
13.981
274729ELWOOD EC;1P
Adder
8.208
274730ELWOOD EC;6P
Adder
8.208
274734ELWOOD EC;8P
Adder
8.208
274736ELWOOD EC;9P
Adder
8.208
970513AG2-328 GEN
Solar/Wind Harmer
8.906
970517AG2-330 GEN
Solar/Wind Harmer
8.078
274682WAUKEGAN ;7U
Adder
8.816
972236AH1-702 GEN2
Adder
1.051
274760LEE CO EC;1U
Adder
4.416
962511AG1-100 GEN
Solar/Wind Helper
0.462
203830AF1-094 GEN
Solar/Wind Helper
0.435
959441AF2-235 GEN
Solar/Wind Helper
0.196
254305AE2-115 C
Solar/Wind Helper
0.138
20334926Z1-069 C
Solar/Wind Helper
0.837
203854AF2-039 C
Solar/Wind Helper
0.18
203818AF1-086 GEN
Solar/Wind Helper
0.912
238202AE2-262_GEN
Solar/Wind Helper
0.528
941421AE2-139 GEN
Solar/Wind Helper
1.203
235058AG1-386 C
Solar/Wind Helper
0.205
200917MEHOOPANY_G
Solar/Wind Helper
1.091
241885AC2-103 GEN1
Solar/Wind Harmer
18.089
241807AE2-176_GEN
Solar/Wind Harmer
7.368
972253AH1-711 GEN
Adder
54.605
241858AF1-205_GEN
Solar/Wind Harmer
6.156
966321AG1-501 GEN
Adder
1.655
957111AF2-005 GEN
Adder
1.324
241808AF1-120 C
Solar/Wind Harmer
1.346
23920202STRYCT
Adder
2.011
241840AF1-064_GEN
Solar/Wind Harmer
1.592
972301AH1-735 GEN
Adder
7.456
23906402RICHG1
Adder
1.491
23906502RICHG2&3
Adder
1.489
270361_3
Solar/Wind Harmer
10.624
960841AF2-375 GEN
Solar/Wind Harmer
4.677
270428AC2-015 C
Solar/Wind Harmer
5.418
247522W1-056 GEN
Solar/Wind Harmer
1.996
970515AG2-329 GEN
Solar/Wind Harmer
12.822
970905AG2-564 GEN
Solar/Wind Harmer
4.278
944231AF1-091 GEN
Solar/Wind Harmer
2.791
241847AF2-150_GEN
Solar/Wind Harmer
2.847
246936BC-WTG1
Solar/Wind Harmer
2.614
270489AE1-102 GEN1
Solar/Wind Harmer
0.868
965421AG1-410 GEN
Solar/Wind Harmer
19.836
24695305TIMB G C
Solar/Wind Harmer
3.562
270449AD2-020 GEN
Solar/Wind Harmer
1.777
943021AE2-325 GEN
Solar/Wind Harmer
2.309
247521TR3_G114
Solar/Wind Harmer
2.099
270246TR4_N_V150
Solar/Wind Harmer
0.531
945111AF1-176 GEN
Solar/Wind Harmer
11.092
270505AE1-170 C O1
Solar/Wind Harmer
9.313
270462AD2-086
Solar/Wind Harmer
4.24
24639705ELKHART HY
Adder
0.093
270063AE2-323 C
Solar/Wind Harmer
1.334
965011AG1-365 GEN
Solar/Wind Harmer
5.975
241813AF1-122_GEN
Solar/Wind Harmer
3.682
270223U2-072_GEN1
Solar/Wind Harmer
1.12
270578AF1-285 GEN2
Solar/Wind Harmer
0.685
270391AF1-285 GEN3
Solar/Wind Harmer
0.685
970373AG2-245 GEN
Solar/Wind Harmer
11.24
971221AH1-070 GEN
Solar/Wind Harmer
0.907
270055AF2-134 C O1
Solar/Wind Harmer
1.591
274751CRETE EC ;1U
Adder
2.532
274754CRETE EC ;4U
Adder
2.532
958381AF2-132 GEN
Solar/Wind Harmer
4.687
964861AG1-349 GEN
Solar/Wind Harmer
4.054
971917AH1-482 GEN
Solar/Wind Harmer
4.678
274723RIVER EC ;12
Adder
9.215
274812UNIV PK N;8U
Adder
2.564
276164X3-005 C
Solar/Wind Harmer
0.358
274801UNIV PARK;4U
Adder
2.944
940581AE2-045 GEN
Solar/Wind Harmer
5.147
971605AH1-302 GEN
Solar/Wind Harmer
4.401
276776AD2-060 GEN
Solar/Wind Harmer
0.213
972207SS24-0001
Solar/Wind Harmer
11.112
274773LINCOLN ;4U
Adder
3.125
274774LINCOLN ;5U
Adder
3.125
274676JOLIET 29;8U
Adder
15.345
941551AE2-152 GEN
Solar/Wind Harmer
2.266
274732ELWOOD EC;7P
Adder
8.208
274674JOLIET 9 ;6U
Adder
7.687
970245AG2-165 GEN
Solar/Wind Harmer
8.906
274745AC1-111 GEN9
Adder
2.761
274682WAUKEGAN ;7U
Adder
8.816
274828WAUKEGAN ;BP
Adder
5.414
274822ROCKFORD ;11
Adder
9.424
972235AH1-702 GEN1
Adder
1.208
274761LEE CO EC;2U
Adder
2.885
961971AG1-040 GEN
Solar/Wind Helper
0.451
203835AF1-098 GEN
Solar/Wind Helper
1.778
203860AG1-193 C
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.16
254303AC2-168 GEN
Solar/Wind Helper
0.093
203954AE2-126 C
Solar/Wind Helper
0.282
959471AF2-238 GEN
Solar/Wind Helper
0.26
238206AE2-263_GEN
Solar/Wind Helper
0.502
20094526CT_V3-030
Solar/Wind Helper
0.243
20088826HIGHLAND
Solar/Wind Helper
0.435
964201AG1-281 GEN
Solar/Wind Helper
0.234
964391AG1-301 GEN
Solar/Wind Helper
0.226
23917202WLORG-3
50/50
1.953
23917302WLORG-4
50/50
1.91
966311AG1-500 GEN
50/50
177.624
24190002OREGON_ST1
50/50
3.713
24189802OREGON_CT1
50/50
2.816
23857202WLORG-B
Adder
8.455
241996AE2-282_GEN
Solar/Wind Harmer
2.414
971677AH1-339 GEN
Solar/Wind Harmer
8.462
270007AE1-245 C
Solar/Wind Harmer
4.022
942801AE2-298 GEN
Solar/Wind Harmer
1.019
246938BC-WTG3
Solar/Wind Harmer
2.659
246937BC-WTG2
Solar/Wind Harmer
2.614
971231AH1-075 GEN
Solar/Wind Harmer
0.508
961051AF2-396 GEN
Solar/Wind Harmer
9.992
961051AF2-396 GEN
Solar/Wind Harmer
4.648
960981AF2-389 GEN
Solar/Wind Harmer
0.936
957891AF2-083 GEN
Solar/Wind Harmer
2.088
247620Y3-023
Adder
0.281
270216AD2-079_GEN
Solar/Wind Harmer
0.363
970611AG2-400 GEN
Solar/Wind Harmer
5.975
270526AF1-158 GEN
Solar/Wind Harmer
2.631
24441505OLIV SLR
Solar/Wind Harmer
0.077
971201AH1-060 GEN
Solar/Wind Harmer
1.151
270224U2-072_GEN2
Solar/Wind Harmer
1.12
270227U2-072_GEN3
Solar/Wind Harmer
1.12
270228U2-072_GEN4
Solar/Wind Harmer
1.12
270231U2-072_GEN5
Solar/Wind Harmer
1.12
965681AG1-436 GEN
Solar/Wind Harmer
6.942
965791AG1-447 GEN
Solar/Wind Harmer
3.552
241960AC2-195 GEN
Solar/Wind Harmer
1.533
274808UNIV PK N;4U
Adder
2.553
942221AE2-234 GEN
Solar/Wind Harmer
0.373
274803UNIV PARK;6U
Adder
2.953
274888KELLY CRK;1U
Solar/Wind Harmer
2.977
274887GEN-1.85
Solar/Wind Harmer
2.688
276843GEN-1.7
Solar/Wind Harmer
0.289
958011AF2-095 GEN
Solar/Wind Harmer
7.261
274770LINCOLN ;1U
Adder
3.125
274771LINCOLN ;2U
Adder
3.125
972259AH1-714 GEN
Adder
9.55
274674JOLIET 9 ;6U
Adder
7.687
970321AG2-212 GEN
Solar/Wind Harmer
8.906
274696ROCKY RD ;4P
Adder
5.589
274695ROCKY RD ;2P
Adder
5.46
274693ROCKY RD ;1P
Adder
5.407
274697ROCKY RD ;3P
Adder
1.483
274683WAUKEGAN ;8U
Adder
10.328
274683WAUKEGAN ;8U
Adder
8.706
25326509SID D
Adder
0.633
274764LEE CO EC;5U
Adder
4.426
274765LEE CO EC;6U
Adder
4.426
203947AF1-006 C
Solar/Wind Helper
0.516
203980AG1-197 GEN
Solar/Wind Helper
0.336
203979AG1-198 GEN
Solar/Wind Helper
0.261
241967AE2-285_GEN
Solar/Wind Helper
0.417
241801AE1-079 GEN
Solar/Wind Helper
0.162
241985AE1-237 GEN
Solar/Wind Helper
0.162
962101AG1-054 GEN
Solar/Wind Helper
0.402
946381AF1-302 GEN
Solar/Wind Helper
0.136
238217AF1-153 C O1
Solar/Wind Helper
0.144
20398826ARMNA MT
Solar/Wind Helper
0.849
203853AF1-134 C O1
Solar/Wind Helper
0.264
203952AE2-129 C
Solar/Wind Helper
0.257
203946AE2-131 C
Solar/Wind Helper
0.258
946071AF1-272 GEN
Solar/Wind Helper
1.356
203940AF1-140 C
Solar/Wind Helper
0.192
20084626FORWARD
Solar/Wind Helper
0.17
20088626ARWF_N39
Solar/Wind Helper
0.584
20303426NA_O38_P22
Solar/Wind Helper
0.479
20088926STNY CRK
Solar/Wind Helper
0.38
20083426SW_E13_K22
Solar/Wind Helper
0.025
991182J1586 G
External Queue
25.886547088623047
990527J1329
External Queue
1.891624927520752
990142J1224
External Queue
13.827776908874512
991177J1571 G
External Queue
16.072763442993164
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.376
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.995
MECLTFEXP_MEC->PJM
CLTF
7.157
SIGELTFEXP_SIGE->PJM
CLTF
0.189
LAGNLTFEXP_LAGN->PJM
CLTF
5.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.427
TVALTFEXP_TVA->PJM
CLTF
2.517
CPLELTFEXP_CPLE->PJM
CLTF
0.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.143
NYPJM->LTFIMP_NY
CLTF
2.552
LGEELTFEXP_LGEE->PJM
CLTF
2.281
WECLTFEXP_WEC->PJM
CLTF
1.831
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.177

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-003_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-003_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.76 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1967.48
MW Contribution:13.11
Bus #Bus NameTypeMW Contribution
23917202WLORG-3
50/50
1.387
23917302WLORG-4
50/50
1.357
966311AG1-500 GEN
50/50
126.182
24190002OREGON_ST1
50/50
2.624
24189802OREGON_CT1
50/50
1.991
241996AE2-282_GEN
Solar/Wind Harmer
1.706
23857202WLORG-B
Adder
4.453
971677AH1-339 GEN
Solar/Wind Harmer
5.98
270007AE1-245 C
Solar/Wind Harmer
2.895
942801AE2-298 GEN
Solar/Wind Harmer
0.734
246938BC-WTG3
Solar/Wind Harmer
1.916
246937BC-WTG2
Solar/Wind Harmer
1.883
961051AF2-396 GEN
Solar/Wind Harmer
7.22
961051AF2-396 GEN
Solar/Wind Harmer
3.358
971231AH1-075 GEN
Solar/Wind Harmer
0.364
960981AF2-389 GEN
Solar/Wind Harmer
0.677
957891AF2-083 GEN
Solar/Wind Harmer
1.51
247620Y3-023
Adder
0.203
270216AD2-079_GEN
Solar/Wind Harmer
0.263
970611AG2-400 GEN
Solar/Wind Harmer
4.324
203947AF1-006 C
Solar/Wind Helper
0.461
203980AG1-197 GEN
Solar/Wind Helper
0.297
203979AG1-198 GEN
Solar/Wind Helper
0.23
241967AE2-285_GEN
Solar/Wind Helper
0.309
241801AE1-079 GEN
Solar/Wind Helper
0.12
241985AE1-237 GEN
Solar/Wind Helper
0.12
946381AF1-302 GEN
Solar/Wind Helper
0.111
238217AF1-153 C O1
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.297
957071AF2-004 GEN
50/50
10.802
23929302BS-PKR
50/50
1.846
241832AE2-181_GEN
Solar/Wind Harmer
1.547
958321AF2-126 GEN
Solar/Wind Harmer
1.207
23906502RICHG2&3
Adder
1.056
270575GUS2 35KV
Solar/Wind Harmer
8.83
23857102WLORG-A
Adder
4.322
270541AE2-072 C
Solar/Wind Harmer
3.557
970217AG2-149 GEN
Solar/Wind Harmer
20.039
270588AE1-091_GEN
Solar/Wind Harmer
5.974
270044AE2-322 C
Solar/Wind Harmer
0.703
270404AC1-167 GEN
Solar/Wind Harmer
0.585
270258AD1-119 GEN
Solar/Wind Harmer
1.434
958091AF2-103 GEN
Solar/Wind Harmer
0.079
247604X1-042
Adder
0.203
961961AG1-039 GEN
Solar/Wind Harmer
1.38
270491AE1-102 GEN2
Solar/Wind Harmer
0.626
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.809
270191TR4_S_V150
Solar/Wind Harmer
1.353
270247TR4_N_V136
Solar/Wind Harmer
0.384
945111AF1-176 GEN
Solar/Wind Harmer
2.541
270485AE1-090_GEN
Solar/Wind Harmer
0.267
24642205MAYFLWER
Adder
0.278
970031AG2-029 GEN
Solar/Wind Harmer
13.106
247643Z2-116 C
Solar/Wind Harmer
0.03
959331AF2-224 GEN
Solar/Wind Harmer
4.324
965021AG1-366 GEN
Solar/Wind Harmer
1.006
962511AG1-100 GEN
Solar/Wind Helper
0.411
203830AF1-094 GEN
Solar/Wind Helper
0.384
959441AF2-235 GEN
Solar/Wind Helper
0.169
20334926Z1-069 C
Solar/Wind Helper
0.692
254305AE2-115 C
Solar/Wind Helper
0.103
23867002DVBSG1
50/50
9.2
972211AH1-690 GEN
50/50
210.311
241886AC2-103 GEN2
Solar/Wind Harmer
12.828
970817AG2-515 GEN
Solar/Wind Harmer
11.522
24191202EL_AA1-006
Adder
0.249
945411AF1-206 GEN
Solar/Wind Harmer
6.374
270499AE1-146 GEN
Solar/Wind Harmer
2.067
945641AF1-229 GEN
Solar/Wind Harmer
2.863
970159AG2-109 GEN
Solar/Wind Harmer
2.569
270297AD1-101 GEN
Solar/Wind Harmer
1.589
971549AH1-272 GEN
Solar/Wind Harmer
10.203
966831AG1-554 GEN
Solar/Wind Harmer
0.637
971989AH1-539 GEN
Solar/Wind Harmer
6.89
247607V1-011 GEN
Solar/Wind Harmer
1.93
971567AH1-282 GEN
Solar/Wind Harmer
7.229
957201AF2-014 GEN
Solar/Wind Harmer
2.183
270435AC2-044 GEN
Solar/Wind Harmer
0.963
944161AF1-084 GEN
Solar/Wind Harmer
1.025
965041AG1-368 GEN
Solar/Wind Harmer
4.523
965051AG1-369 GEN
Solar/Wind Harmer
2.252
270302AB2-170 GEN
Solar/Wind Harmer
3.686
270317AD1-130_GEN
Solar/Wind Harmer
1.413
203846AF2-130 C
Solar/Wind Helper
0.273
203804AE2-113_GEN
Solar/Wind Helper
0.939
241982AE2-343 S C
Solar/Wind Helper
0.108
254304AE2-114 C
Solar/Wind Helper
0.103
241997AF1-093 GEN
Solar/Wind Helper
0.119
23917402WLORG-5
50/50
1.364
23917102WLORG-2
50/50
1.344
24189902OREGON_CT2
50/50
1.95
23856402BAYSG1
50/50
1.049
241885AC2-103 GEN1
Solar/Wind Harmer
12.828
241807AE2-176_GEN
Solar/Wind Harmer
5.09
972253AH1-711 GEN
Adder
38.596
241858AF1-205_GEN
Solar/Wind Harmer
4.35
241808AF1-120 C
Solar/Wind Harmer
0.951
23920202STRYCT
Adder
1.423
241840AF1-064_GEN
Solar/Wind Harmer
1.126
972301AH1-735 GEN
Adder
5.287
23906402RICHG1
Adder
1.057
23906502RICHG2&3
Adder
1.056
270361_3
Solar/Wind Harmer
7.495
960841AF2-375 GEN
Solar/Wind Harmer
3.301
966321AG1-501 GEN
Adder
0.871
957111AF2-005 GEN
Adder
0.697
270428AC2-015 C
Solar/Wind Harmer
3.771
247522W1-056 GEN
Solar/Wind Harmer
1.418
970515AG2-329 GEN
Solar/Wind Harmer
9.087
970905AG2-564 GEN
Solar/Wind Harmer
2.97
944231AF1-091 GEN
Solar/Wind Harmer
2.004
241847AF2-150_GEN
Solar/Wind Harmer
2
246936BC-WTG1
Solar/Wind Harmer
1.883
270489AE1-102 GEN1
Solar/Wind Harmer
0.626
965421AG1-410 GEN
Solar/Wind Harmer
14.298
24695305TIMB G C
Solar/Wind Harmer
2.569
270449AD2-020 GEN
Solar/Wind Harmer
1.284
943021AE2-325 GEN
Solar/Wind Harmer
1.668
247521TR3_G114
Solar/Wind Harmer
1.516
270246TR4_N_V150
Solar/Wind Harmer
0.384
945111AF1-176 GEN
Solar/Wind Harmer
8.018
270505AE1-170 C O1
Solar/Wind Harmer
6.733
270462AD2-086
Solar/Wind Harmer
3.066
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.965
965011AG1-365 GEN
Solar/Wind Harmer
4.324
961971AG1-040 GEN
Solar/Wind Helper
0.4
203835AF1-098 GEN
Solar/Wind Helper
1.575
203860AG1-193 C
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.119
203954AE2-126 C
Solar/Wind Helper
0.231
254303AC2-168 GEN
Solar/Wind Helper
0.068
990527J1329
External Queue
1.3199658393859863
990142J1224
External Queue
9.648950576782227
991177J1571 G
External Queue
11.211230278015137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.978
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.506
MECLTFEXP_MEC->PJM
CLTF
5.248
SIGELTFEXP_SIGE->PJM
CLTF
0.14
LAGNLTFEXP_LAGN->PJM
CLTF
4.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.016
TVALTFEXP_TVA->PJM
CLTF
1.895
CPLELTFEXP_CPLE->PJM
CLTF
0.34
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.744
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
1.697
WECLTFEXP_WEC->PJM
CLTF
1.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.086
AH1-155LTFEXP_AH1-155->PJM
LTF
0.129

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-028_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.37 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1903.65
MW Contribution:13.01
Bus #Bus NameTypeMW Contribution
957071AF2-004 GEN
50/50
10.49
23929302BS-PKR
50/50
1.83
241832AE2-181_GEN
Solar/Wind Harmer
1.532
958321AF2-126 GEN
Solar/Wind Harmer
1.196
23857102WLORG-A
Adder
5.166
23906502RICHG2&3
Adder
1.047
270575GUS2 35KV
Solar/Wind Harmer
8.812
270541AE2-072 C
Solar/Wind Harmer
3.533
970217AG2-149 GEN
Solar/Wind Harmer
20.092
270588AE1-091_GEN
Solar/Wind Harmer
5.966
270044AE2-322 C
Solar/Wind Harmer
0.698
270404AC1-167 GEN
Solar/Wind Harmer
0.582
270258AD1-119 GEN
Solar/Wind Harmer
1.425
961961AG1-039 GEN
Solar/Wind Harmer
1.41
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.201
270491AE1-102 GEN2
Solar/Wind Harmer
0.622
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.828
270191TR4_S_V150
Solar/Wind Harmer
1.345
270247TR4_N_V136
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
2.522
270485AE1-090_GEN
Solar/Wind Harmer
0.265
24642205MAYFLWER
Adder
0.276
970031AG2-029 GEN
Solar/Wind Harmer
13.014
247643Z2-116 C
Solar/Wind Harmer
0.03
23917402WLORG-5
50/50
1.325
23917102WLORG-2
50/50
1.305
24189902OREGON_CT2
50/50
1.926
23856402BAYSG1
50/50
1.04
241885AC2-103 GEN1
Solar/Wind Harmer
12.516
241807AE2-176_GEN
Solar/Wind Harmer
5.17
972253AH1-711 GEN
Adder
38.133
241858AF1-205_GEN
Solar/Wind Harmer
4.307
241808AF1-120 C
Solar/Wind Harmer
0.942
23920202STRYCT
Adder
1.409
241840AF1-064_GEN
Solar/Wind Harmer
1.116
966321AG1-501 GEN
Adder
1.042
957111AF2-005 GEN
Adder
0.833
972301AH1-735 GEN
Adder
5.24
23906402RICHG1
Adder
1.048
23906502RICHG2&3
Adder
1.047
270361_3
Solar/Wind Harmer
7.48
960841AF2-375 GEN
Solar/Wind Harmer
3.294
270428AC2-015 C
Solar/Wind Harmer
3.85
247522W1-056 GEN
Solar/Wind Harmer
1.419
970515AG2-329 GEN
Solar/Wind Harmer
9.111
970905AG2-564 GEN
Solar/Wind Harmer
3.056
944231AF1-091 GEN
Solar/Wind Harmer
1.99
241847AF2-150_GEN
Solar/Wind Harmer
2.044
246936BC-WTG1
Solar/Wind Harmer
1.872
270489AE1-102 GEN1
Solar/Wind Harmer
0.622
965421AG1-410 GEN
Solar/Wind Harmer
14.212
24695305TIMB G C
Solar/Wind Harmer
2.554
270449AD2-020 GEN
Solar/Wind Harmer
1.274
943021AE2-325 GEN
Solar/Wind Harmer
1.655
247521TR3_G114
Solar/Wind Harmer
1.507
270246TR4_N_V150
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
7.958
270505AE1-170 C O1
Solar/Wind Harmer
6.681
270462AD2-086
Solar/Wind Harmer
3.053
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.958
961971AG1-040 GEN
Solar/Wind Helper
0.399
203835AF1-098 GEN
Solar/Wind Helper
1.572
203860AG1-193 C
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.118
203954AE2-126 C
Solar/Wind Helper
0.231
254303AC2-168 GEN
Solar/Wind Helper
0.068
962511AG1-100 GEN
Solar/Wind Helper
0.41
203830AF1-094 GEN
Solar/Wind Helper
0.383
959441AF2-235 GEN
Solar/Wind Helper
0.169
20334926Z1-069 C
Solar/Wind Helper
0.69
254305AE2-115 C
Solar/Wind Helper
0.102
23917202WLORG-3
50/50
1.347
23917302WLORG-4
50/50
1.318
966311AG1-500 GEN
50/50
122.544
24190002OREGON_ST1
50/50
2.591
24189802OREGON_CT1
50/50
1.965
241996AE2-282_GEN
Solar/Wind Harmer
1.69
23857202WLORG-B
Adder
5.323
971677AH1-339 GEN
Solar/Wind Harmer
5.982
270007AE1-245 C
Solar/Wind Harmer
2.879
942801AE2-298 GEN
Solar/Wind Harmer
0.729
246938BC-WTG3
Solar/Wind Harmer
1.904
246937BC-WTG2
Solar/Wind Harmer
1.872
971231AH1-075 GEN
Solar/Wind Harmer
0.366
961051AF2-396 GEN
Solar/Wind Harmer
7.165
961051AF2-396 GEN
Solar/Wind Harmer
3.333
960981AF2-389 GEN
Solar/Wind Harmer
0.672
957891AF2-083 GEN
Solar/Wind Harmer
1.498
247620Y3-023
Adder
0.202
23867002DVBSG1
50/50
9.044
972211AH1-690 GEN
50/50
207.621
24191202EL_AA1-006
50/50
0.277
241886AC2-103 GEN2
Solar/Wind Harmer
12.516
970817AG2-515 GEN
Solar/Wind Harmer
11.392
945411AF1-206 GEN
Solar/Wind Harmer
6.311
270499AE1-146 GEN
Solar/Wind Harmer
2.062
945641AF1-229 GEN
Solar/Wind Harmer
2.852
970159AG2-109 GEN
Solar/Wind Harmer
2.883
270297AD1-101 GEN
Solar/Wind Harmer
1.58
971549AH1-272 GEN
Solar/Wind Harmer
10.113
966831AG1-554 GEN
Solar/Wind Harmer
0.638
971989AH1-539 GEN
Solar/Wind Harmer
6.896
971567AH1-282 GEN
Solar/Wind Harmer
7.283
247607V1-011 GEN
Solar/Wind Harmer
1.919
957201AF2-014 GEN
Solar/Wind Harmer
2.17
270435AC2-044 GEN
Solar/Wind Harmer
0.957
944161AF1-084 GEN
Solar/Wind Harmer
1.017
965041AG1-368 GEN
Solar/Wind Harmer
4.496
965051AG1-369 GEN
Solar/Wind Harmer
2.238
270302AB2-170 GEN
Solar/Wind Harmer
3.67
270317AD1-130_GEN
Solar/Wind Harmer
1.407
203846AF2-130 C
Solar/Wind Helper
0.273
203804AE2-113_GEN
Solar/Wind Helper
0.936
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
241997AF1-093 GEN
Solar/Wind Helper
0.118
270216AD2-079_GEN
Solar/Wind Harmer
0.261
203947AF1-006 C
Solar/Wind Helper
0.46
203980AG1-197 GEN
Solar/Wind Helper
0.297
203979AG1-198 GEN
Solar/Wind Helper
0.23
241967AE2-285_GEN
Solar/Wind Helper
0.308
241801AE1-079 GEN
Solar/Wind Helper
0.12
241985AE1-237 GEN
Solar/Wind Helper
0.12
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.296
990527J1329
External Queue
1.3018794059753418
990142J1224
External Queue
9.516737937927246
991177J1571 G
External Queue
11.062751770019531
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.481
MECLTFEXP_MEC->PJM
CLTF
5.217
SIGELTFEXP_SIGE->PJM
CLTF
0.139
LAGNLTFEXP_LAGN->PJM
CLTF
4.117
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
1.889
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.594
NYPJM->LTFIMP_NY
CLTF
1.977
LGEELTFEXP_LGEE->PJM
CLTF
1.691
WECLTFEXP_WEC->PJM
CLTF
1.328
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-005_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-005_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.08 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2820.59
MW Contribution:16.5
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
15.541
972211AH1-690 GEN
50/50
306.568
23888502TROY G1
50/50
1.9
23888602TROY G2
50/50
1.9
241886AC2-103 GEN2
Solar/Wind Harmer
15.652
970817AG2-515 GEN
Solar/Wind Harmer
15.768
945411AF1-206 GEN
Solar/Wind Harmer
8.154
945641AF1-229 GEN
Solar/Wind Harmer
3.506
270499AE1-146 GEN
Solar/Wind Harmer
2.087
971549AH1-272 GEN
Solar/Wind Harmer
13.415
270297AD1-101 GEN
Solar/Wind Harmer
1.871
944161AF1-084 GEN
Solar/Wind Harmer
1.317
957201AF2-014 GEN
Solar/Wind Harmer
2.676
270435AC2-044 GEN
Solar/Wind Harmer
1.18
247607V1-011 GEN
Solar/Wind Harmer
2.325
965041AG1-368 GEN
Solar/Wind Harmer
5.531
965051AG1-369 GEN
Solar/Wind Harmer
2.742
966831AG1-554 GEN
Solar/Wind Harmer
0.652
971989AH1-539 GEN
Solar/Wind Harmer
7.048
971771AH1-392 GEN
Solar/Wind Harmer
4.891
971769AH1-391 GEN
Solar/Wind Harmer
5.295
270302AB2-170 GEN
Solar/Wind Harmer
4.384
270317AD1-130_GEN
Solar/Wind Harmer
1.681
960681AF2-359 GEN
Solar/Wind Harmer
1.922
971347AH1-153 GEN
Solar/Wind Harmer
7.592
971567AH1-282 GEN
Solar/Wind Harmer
7.444
963791AG1-232 GEN
Solar/Wind Harmer
6.663
270578AF1-285 GEN2
Solar/Wind Harmer
0.225
270536AF1-215 GEN2
Solar/Wind Harmer
2.176
270071AF1-092 GEN
Solar/Wind Harmer
7.051
274814UNIV PK N;0U
Adder
2.355
274807UNIV PK N;3U
Adder
2.35
274805UNIV PK N;1U
Adder
2.34
274811UNIV PK N;7U
Adder
2.335
958391AF2-133 GEN
Solar/Wind Harmer
4.226
972037AH1-567 GEN1
Adder
0.084
274827FISK ;RP
Adder
3.57
960591AF2-350 GEN
Solar/Wind Harmer
4.586
274775LINCOLN ;6U
Adder
2.842
274776LINCOLN ;7U
Adder
2.842
274777LINCOLN ;8U
Adder
2.842
972227AH1-698 GEN1
Adder
1.192
274687WILL CNTY;4U
Adder
12.733
274687WILL CNTY;4U
Adder
12.733
274675JOLIET 29;7U
Adder
13.952
274675JOLIET 29;7U
Adder
13.453
274731ELWOOD EC;2P
Adder
7.461
274733ELWOOD EC;3P
Adder
7.461
274735ELWOOD EC;4P
Adder
7.461
274728ELWOOD EC;5P
Adder
7.461
970833AG2-524 GEN
Solar/Wind Harmer
3.942
970833AG2-524 GEN
Solar/Wind Harmer
1.834
274746AC1-111 G10
Adder
2.508
274744AC1-111 GEN8
Adder
2.508
24729505KEY G4
Adder
2.834
274823ROCKFORD ;21
Adder
8.489
241982AE2-343 S C
Solar/Wind Helper
0.119
254304AE2-114 C
Solar/Wind Helper
0.114
24190002OREGON_ST1
50/50
3.824
24189802OREGON_CT1
50/50
2.901
23888802TROY G4
50/50
1.9
241996AE2-282_GEN
Solar/Wind Harmer
2.183
971677AH1-339 GEN
Solar/Wind Harmer
5.955
246938BC-WTG3
Solar/Wind Harmer
2.348
246937BC-WTG2
Solar/Wind Harmer
2.308
270007AE1-245 C
Solar/Wind Harmer
3.488
942801AE2-298 GEN
Solar/Wind Harmer
0.883
961051AF2-396 GEN
Solar/Wind Harmer
9.249
961051AF2-396 GEN
Solar/Wind Harmer
4.302
960981AF2-389 GEN
Solar/Wind Harmer
0.865
957891AF2-083 GEN
Solar/Wind Harmer
1.929
247620Y3-023
Adder
0.257
270216AD2-079_GEN
Solar/Wind Harmer
0.334
970611AG2-400 GEN
Solar/Wind Harmer
5.341
270526AF1-158 GEN
Solar/Wind Harmer
2.418
24441505OLIV SLR
Solar/Wind Harmer
0.071
965681AG1-436 GEN
Solar/Wind Harmer
6.36
965791AG1-447 GEN
Solar/Wind Harmer
3.254
270224U2-072_GEN2
Solar/Wind Harmer
0.959
270227U2-072_GEN3
Solar/Wind Harmer
0.959
270228U2-072_GEN4
Solar/Wind Harmer
0.959
270231U2-072_GEN5
Solar/Wind Harmer
0.959
274808UNIV PK N;4U
Adder
2.324
274803UNIV PARK;6U
Adder
2.687
274888KELLY CRK;1U
Solar/Wind Harmer
2.708
274887GEN-1.85
Solar/Wind Harmer
2.444
276843GEN-1.7
Solar/Wind Harmer
0.263
958011AF2-095 GEN
Solar/Wind Harmer
6.604
274770LINCOLN ;1U
Adder
2.842
274771LINCOLN ;2U
Adder
2.842
972259AH1-714 GEN
Adder
8.682
274674JOLIET 9 ;6U
Adder
6.988
942221AE2-234 GEN
Solar/Wind Harmer
0.331
970321AG2-212 GEN
Solar/Wind Harmer
8.074
274847GR RIDGE ;BU
Solar/Wind Harmer
2.283
274696ROCKY RD ;4P
Adder
5.076
274695ROCKY RD ;2P
Adder
4.959
274693ROCKY RD ;1P
Adder
4.91
274697ROCKY RD ;3P
Adder
1.347
274683WAUKEGAN ;8U
Adder
9.38
274683WAUKEGAN ;8U
Adder
7.907
274764LEE CO EC;5U
Adder
4.014
274765LEE CO EC;6U
Adder
4.014
274762LEE CO EC;3U
Adder
4.005
274763LEE CO EC;4U
Adder
3.967
203947AF1-006 C
Solar/Wind Helper
0.382
203980AG1-197 GEN
Solar/Wind Helper
0.25
203979AG1-198 GEN
Solar/Wind Helper
0.195
241967AE2-285_GEN
Solar/Wind Helper
0.343
241801AE1-079 GEN
Solar/Wind Helper
0.133
241985AE1-237 GEN
Solar/Wind Helper
0.133
962101AG1-054 GEN
Solar/Wind Helper
0.331
946381AF1-302 GEN
Solar/Wind Helper
0.106
238217AF1-153 C O1
Solar/Wind Helper
0.113
958481AF2-142 GEN
Solar/Wind Harmer
6.617
24189902OREGON_CT2
50/50
2.842
23888702TROY G3
50/50
1.9
972253AH1-711 GEN
50/50
58.047
23856402BAYSG1
50/50
1.206
23920202STRYCT
50/50
1.925
241885AC2-103 GEN1
Solar/Wind Harmer
15.652
241858AF1-205_GEN
Solar/Wind Harmer
5.546
241808AF1-120 C
Solar/Wind Harmer
1.217
241840AF1-064_GEN
Solar/Wind Harmer
1.355
972301AH1-735 GEN
Adder
6.637
23906402RICHG1
Adder
1.327
23906502RICHG2&3
Adder
1.324
270361_3
Solar/Wind Harmer
7.399
960841AF2-375 GEN
Solar/Wind Harmer
3.289
970515AG2-329 GEN
Solar/Wind Harmer
10.155
944231AF1-091 GEN
Solar/Wind Harmer
2.497
247522W1-056 GEN
Solar/Wind Harmer
1.426
246936BC-WTG1
Solar/Wind Harmer
2.308
270489AE1-102 GEN1
Solar/Wind Harmer
0.767
270449AD2-020 GEN
Solar/Wind Harmer
1.647
943021AE2-325 GEN
Solar/Wind Harmer
2.14
965421AG1-410 GEN
Solar/Wind Harmer
17.537
945111AF1-176 GEN
Solar/Wind Harmer
10.248
270505AE1-170 C O1
Solar/Wind Harmer
8.61
24695305TIMB G C
Solar/Wind Harmer
3.122
24639705ELKHART HY
Adder
0.085
270063AE2-323 C
Solar/Wind Harmer
1.215
247521TR3_G114
Solar/Wind Harmer
1.846
270246TR4_N_V150
Solar/Wind Harmer
0.467
965011AG1-365 GEN
Solar/Wind Harmer
5.341
270462AD2-086
Solar/Wind Harmer
3.647
970373AG2-245 GEN
Solar/Wind Harmer
10.266
270223U2-072_GEN1
Solar/Wind Harmer
0.959
270578AF1-285 GEN2
Solar/Wind Harmer
0.586
270391AF1-285 GEN3
Solar/Wind Harmer
0.586
270055AF2-134 C O1
Solar/Wind Harmer
1.451
274751CRETE EC ;1U
Adder
2.308
274754CRETE EC ;4U
Adder
2.308
958381AF2-132 GEN
Solar/Wind Harmer
4.267
964861AG1-349 GEN
Solar/Wind Harmer
3.69
971917AH1-482 GEN
Solar/Wind Harmer
4.258
274723RIVER EC ;12
Adder
8.392
274812UNIV PK N;8U
Adder
2.335
276164X3-005 C
Solar/Wind Harmer
0.326
274801UNIV PARK;4U
Adder
2.678
276776AD2-060 GEN
Solar/Wind Harmer
0.194
940581AE2-045 GEN
Solar/Wind Harmer
4.675
972207SS24-0001
Solar/Wind Harmer
10.104
274773LINCOLN ;4U
Adder
2.842
274774LINCOLN ;5U
Adder
2.842
971605AH1-302 GEN
Solar/Wind Harmer
3.998
274676JOLIET 29;8U
Adder
13.952
941551AE2-152 GEN
Solar/Wind Harmer
2.06
274732ELWOOD EC;7P
Adder
7.461
274674JOLIET 9 ;6U
Adder
6.988
970245AG2-165 GEN
Solar/Wind Harmer
8.074
274871GR RIDGE ;2U
Solar/Wind Harmer
3.47
274745AC1-111 GEN9
Adder
2.508
276691AA1-018 GEN1
Solar/Wind Harmer
0.209
274682WAUKEGAN ;7U
Adder
8.008
274828WAUKEGAN ;BP
Adder
4.917
274822ROCKFORD ;11
Adder
8.551
203846AF2-130 C
Solar/Wind Helper
0.25
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.874
972235AH1-702 GEN1
Adder
1.096
274761LEE CO EC;2U
Adder
4.005
274766LEE CO EC;7U
Adder
3.958
241807AE2-176_GEN
Solar/Wind Helper
2.243
961971AG1-040 GEN
Solar/Wind Helper
0.336
203835AF1-098 GEN
Solar/Wind Helper
1.324
203860AG1-193 C
Solar/Wind Helper
0.15
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
203954AE2-126 C
Solar/Wind Helper
0.22
23929302BS-PKR
50/50
2.123
241832AE2-181_GEN
Solar/Wind Harmer
1.981
958321AF2-126 GEN
Solar/Wind Harmer
1.453
23906502RICHG2&3
Adder
1.324
270541AE2-072 C
Solar/Wind Harmer
4.225
270575GUS2 35KV
Solar/Wind Harmer
8.717
970217AG2-149 GEN
Solar/Wind Harmer
22.392
270044AE2-322 C
Solar/Wind Harmer
0.856
270404AC1-167 GEN
Solar/Wind Harmer
0.713
247604X1-042
Adder
0.263
270258AD1-119 GEN
Solar/Wind Harmer
1.747
24441205WTRV SLR C
Solar/Wind Harmer
0.083
270491AE1-102 GEN2
Solar/Wind Harmer
0.767
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270588AE1-091_GEN
Solar/Wind Harmer
6.43
945111AF1-176 GEN
Solar/Wind Harmer
3.248
24642205MAYFLWER
Adder
0.355
247643Z2-116 C
Solar/Wind Harmer
0.038
970031AG2-029 GEN
Solar/Wind Harmer
16.505
270191TR4_S_V150
Solar/Wind Harmer
1.647
270247TR4_N_V136
Solar/Wind Harmer
0.467
959331AF2-224 GEN
Solar/Wind Harmer
5.341
965021AG1-366 GEN
Solar/Wind Harmer
1.242
270485AE1-090_GEN
Solar/Wind Harmer
0.317
270043AE2-236 GEN
Solar/Wind Harmer
2.786
970349AG2-230 GEN
Solar/Wind Harmer
7.592
942871AE2-306 GEN
Solar/Wind Harmer
0.44
270391AF1-285 GEN3
Solar/Wind Harmer
0.225
270535AF1-215 GEN1
Solar/Wind Harmer
2.176
972231SS25-0005
Solar/Wind Harmer
4.48
972181SS23-001
Solar/Wind Harmer
2.8
274752CRETE EC ;2U
Adder
2.308
274753CRETE EC ;3U
Adder
2.308
964401AG1-302 GEN
Solar/Wind Harmer
4.267
274724RIVER EC ;11
Adder
8.292
959141AF2-205 GEN
Solar/Wind Harmer
2.796
274802UNIV PARK;5U
Adder
2.687
274826FISK ;BP
Adder
5.037
274800UNIV PARK;3U
Adder
2.678
972038AH1-567 GEN2
Adder
0.168
276772AC2-154 GEN
Solar/Wind Harmer
1.279
276806AD2-047 C O1
Solar/Wind Harmer
4.906
970941AG2-585 GEN
Solar/Wind Harmer
5.733
274772LINCOLN ;3U
Adder
2.842
972228AH1-698 GEN2
Adder
1.694
274676JOLIET 29;8U
Adder
13.453
276897AD1-100 C
Solar/Wind Harmer
13.182
939351AE1-166 GEN
Solar/Wind Harmer
2.693
276893AG1-478 C
Solar/Wind Harmer
0.19
274729ELWOOD EC;1P
Adder
7.461
274730ELWOOD EC;6P
Adder
7.461
274734ELWOOD EC;8P
Adder
7.461
274736ELWOOD EC;9P
Adder
7.461
970707AG2-453 GEN
Solar/Wind Harmer
12.707
970513AG2-328 GEN
Solar/Wind Harmer
8.074
970517AG2-330 GEN
Solar/Wind Harmer
7.323
943121AE2-341 GEN
Solar/Wind Harmer
6.728
943591AF1-030 GEN
Solar/Wind Harmer
4.485
276694AA1-018 GEN2
Solar/Wind Harmer
2.83
274682WAUKEGAN ;7U
Adder
8.008
972236AH1-702 GEN2
Adder
0.953
274760LEE CO EC;1U
Adder
4.005
274767LEE CO EC;8U
Adder
3.958
962511AG1-100 GEN
Solar/Wind Helper
0.343
203830AF1-094 GEN
Solar/Wind Helper
0.325
959441AF2-235 GEN
Solar/Wind Helper
0.148
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.651
991182J1586 G
External Queue
26.137367248535156
990527J1329
External Queue
1.9070898294448853
990142J1224
External Queue
13.940826416015625
991177J1571 G
External Queue
15.847536087036133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.867
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.771
MECLTFEXP_MEC->PJM
CLTF
6.458
SIGELTFEXP_SIGE->PJM
CLTF
0.166
LAGNLTFEXP_LAGN->PJM
CLTF
4.896
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.089
TVALTFEXP_TVA->PJM
CLTF
2.214
CPLELTFEXP_CPLE->PJM
CLTF
0.293
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.259
NYPJM->LTFIMP_NY
CLTF
2.051
LGEELTFEXP_LGEE->PJM
CLTF
1.986
WECLTFEXP_WEC->PJM
CLTF
1.661
AG2-052LTFEXP_AG2-052->PJM
LTF
0.107
AH1-155LTFEXP_AH1-155->PJM
LTF
0.161

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-006_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.41 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2770.12
MW Contribution:16.63
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
15.56
972211AH1-690 GEN
50/50
307.318
23888502TROY G1
50/50
1.906
23888602TROY G2
50/50
1.906
241886AC2-103 GEN2
Solar/Wind Harmer
15.671
970817AG2-515 GEN
Solar/Wind Harmer
15.816
945411AF1-206 GEN
Solar/Wind Harmer
8.184
945641AF1-229 GEN
Solar/Wind Harmer
3.527
270499AE1-146 GEN
Solar/Wind Harmer
2.102
971549AH1-272 GEN
Solar/Wind Harmer
13.494
270297AD1-101 GEN
Solar/Wind Harmer
1.884
944161AF1-084 GEN
Solar/Wind Harmer
1.326
957201AF2-014 GEN
Solar/Wind Harmer
2.696
270435AC2-044 GEN
Solar/Wind Harmer
1.189
247607V1-011 GEN
Solar/Wind Harmer
2.343
965041AG1-368 GEN
Solar/Wind Harmer
5.574
965051AG1-369 GEN
Solar/Wind Harmer
2.764
966831AG1-554 GEN
Solar/Wind Harmer
0.658
971989AH1-539 GEN
Solar/Wind Harmer
7.12
971771AH1-392 GEN
Solar/Wind Harmer
4.928
971769AH1-391 GEN
Solar/Wind Harmer
5.337
270302AB2-170 GEN
Solar/Wind Harmer
4.422
270317AD1-130_GEN
Solar/Wind Harmer
1.695
960681AF2-359 GEN
Solar/Wind Harmer
1.938
971347AH1-153 GEN
Solar/Wind Harmer
7.655
971567AH1-282 GEN
Solar/Wind Harmer
7.54
963791AG1-232 GEN
Solar/Wind Harmer
6.721
270578AF1-285 GEN2
Solar/Wind Harmer
0.228
270536AF1-215 GEN2
Solar/Wind Harmer
2.195
270071AF1-092 GEN
Solar/Wind Harmer
7.114
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274805UNIV PK N;1U
Adder
2.36
274811UNIV PK N;7U
Adder
2.355
958391AF2-133 GEN
Solar/Wind Harmer
4.264
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.602
960591AF2-350 GEN
Solar/Wind Harmer
4.627
274775LINCOLN ;6U
Adder
2.867
274776LINCOLN ;7U
Adder
2.867
274777LINCOLN ;8U
Adder
2.867
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.848
274687WILL CNTY;4U
Adder
12.848
274675JOLIET 29;7U
Adder
14.077
274675JOLIET 29;7U
Adder
13.575
274731ELWOOD EC;2P
Adder
7.528
274733ELWOOD EC;3P
Adder
7.528
274735ELWOOD EC;4P
Adder
7.528
274728ELWOOD EC;5P
Adder
7.529
970833AG2-524 GEN
Solar/Wind Harmer
3.978
970833AG2-524 GEN
Solar/Wind Harmer
1.85
274746AC1-111 G10
Adder
2.531
274744AC1-111 GEN8
Adder
2.531
24729505KEY G4
Adder
2.861
274823ROCKFORD ;21
Adder
8.568
241982AE2-343 S C
Solar/Wind Helper
0.119
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.249
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.87
24189902OREGON_CT2
50/50
2.849
23888702TROY G3
50/50
1.906
972253AH1-711 GEN
50/50
58.205
23856402BAYSG1
50/50
1.211
23920202STRYCT
50/50
1.932
241885AC2-103 GEN1
Solar/Wind Harmer
15.671
241858AF1-205_GEN
Solar/Wind Harmer
5.566
241808AF1-120 C
Solar/Wind Harmer
1.222
241840AF1-064_GEN
Solar/Wind Harmer
1.361
972301AH1-735 GEN
Adder
6.666
23906402RICHG1
Adder
1.333
23906502RICHG2&3
Adder
1.33
270361_3
Solar/Wind Harmer
7.454
960841AF2-375 GEN
Solar/Wind Harmer
3.314
970515AG2-329 GEN
Solar/Wind Harmer
10.249
944231AF1-091 GEN
Solar/Wind Harmer
2.514
247522W1-056 GEN
Solar/Wind Harmer
1.44
246936BC-WTG1
Solar/Wind Harmer
2.326
270489AE1-102 GEN1
Solar/Wind Harmer
0.773
270449AD2-020 GEN
Solar/Wind Harmer
1.659
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
17.671
945111AF1-176 GEN
Solar/Wind Harmer
10.323
270505AE1-170 C O1
Solar/Wind Harmer
8.673
24695305TIMB G C
Solar/Wind Harmer
3.146
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
1.224
247521TR3_G114
Solar/Wind Harmer
1.861
270246TR4_N_V150
Solar/Wind Harmer
0.471
965011AG1-365 GEN
Solar/Wind Harmer
5.384
270462AD2-086
Solar/Wind Harmer
3.678
970373AG2-245 GEN
Solar/Wind Harmer
10.352
270223U2-072_GEN1
Solar/Wind Harmer
0.967
270578AF1-285 GEN2
Solar/Wind Harmer
0.592
270391AF1-285 GEN3
Solar/Wind Harmer
0.592
270055AF2-134 C O1
Solar/Wind Harmer
1.463
274751CRETE EC ;1U
Adder
2.328
274754CRETE EC ;4U
Adder
2.328
958381AF2-132 GEN
Solar/Wind Harmer
4.304
964861AG1-349 GEN
Solar/Wind Harmer
3.722
971917AH1-482 GEN
Solar/Wind Harmer
4.295
274723RIVER EC ;12
Adder
8.466
274812UNIV PK N;8U
Adder
2.355
276164X3-005 C
Solar/Wind Harmer
0.329
274801UNIV PARK;4U
Adder
2.702
276776AD2-060 GEN
Solar/Wind Harmer
0.196
940581AE2-045 GEN
Solar/Wind Harmer
4.717
972207SS24-0001
Solar/Wind Harmer
10.194
274773LINCOLN ;4U
Adder
2.867
274774LINCOLN ;5U
Adder
2.867
971605AH1-302 GEN
Solar/Wind Harmer
4.034
274676JOLIET 29;8U
Adder
14.077
941551AE2-152 GEN
Solar/Wind Harmer
2.079
274732ELWOOD EC;7P
Adder
7.529
274674JOLIET 9 ;6U
Adder
7.051
970245AG2-165 GEN
Solar/Wind Harmer
8.148
274871GR RIDGE ;2U
Solar/Wind Harmer
3.502
274745AC1-111 GEN9
Adder
2.531
276691AA1-018 GEN1
Solar/Wind Harmer
0.211
274682WAUKEGAN ;7U
Adder
8.081
274828WAUKEGAN ;BP
Adder
4.962
274822ROCKFORD ;11
Adder
8.631
972235AH1-702 GEN1
Adder
1.107
274761LEE CO EC;2U
Adder
4.043
274766LEE CO EC;7U
Adder
3.995
241807AE2-176_GEN
Solar/Wind Helper
2.224
961971AG1-040 GEN
Solar/Wind Helper
0.335
203835AF1-098 GEN
Solar/Wind Helper
1.322
203860AG1-193 C
Solar/Wind Helper
0.15
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
23929302BS-PKR
50/50
2.132
241832AE2-181_GEN
Solar/Wind Harmer
1.988
958321AF2-126 GEN
Solar/Wind Harmer
1.459
23906502RICHG2&3
Adder
1.33
270541AE2-072 C
Solar/Wind Harmer
4.248
270575GUS2 35KV
Solar/Wind Harmer
8.782
970217AG2-149 GEN
Solar/Wind Harmer
22.6
270044AE2-322 C
Solar/Wind Harmer
0.862
270404AC1-167 GEN
Solar/Wind Harmer
0.718
247604X1-042
Adder
0.265
270258AD1-119 GEN
Solar/Wind Harmer
1.76
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.773
958091AF2-103 GEN
Solar/Wind Harmer
0.096
270588AE1-091_GEN
Solar/Wind Harmer
6.489
945111AF1-176 GEN
Solar/Wind Harmer
3.272
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0.039
970031AG2-029 GEN
Solar/Wind Harmer
16.631
270191TR4_S_V150
Solar/Wind Harmer
1.66
270247TR4_N_V136
Solar/Wind Harmer
0.471
959331AF2-224 GEN
Solar/Wind Harmer
5.384
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270485AE1-090_GEN
Solar/Wind Harmer
0.32
270043AE2-236 GEN
Solar/Wind Harmer
2.809
970349AG2-230 GEN
Solar/Wind Harmer
7.655
942871AE2-306 GEN
Solar/Wind Harmer
0.444
270391AF1-285 GEN3
Solar/Wind Harmer
0.228
270535AF1-215 GEN1
Solar/Wind Harmer
2.195
972231SS25-0005
Solar/Wind Harmer
4.519
972181SS23-001
Solar/Wind Harmer
2.825
274752CRETE EC ;2U
Adder
2.328
274753CRETE EC ;3U
Adder
2.328
964401AG1-302 GEN
Solar/Wind Harmer
4.304
274724RIVER EC ;11
Adder
8.365
959141AF2-205 GEN
Solar/Wind Harmer
2.821
274802UNIV PARK;5U
Adder
2.711
274826FISK ;BP
Adder
5.082
274800UNIV PARK;3U
Adder
2.702
972038AH1-567 GEN2
Adder
0.169
276772AC2-154 GEN
Solar/Wind Harmer
1.29
276806AD2-047 C O1
Solar/Wind Harmer
4.95
970941AG2-585 GEN
Solar/Wind Harmer
5.784
274772LINCOLN ;3U
Adder
2.867
972228AH1-698 GEN2
Adder
1.709
274676JOLIET 29;8U
Adder
13.575
276897AD1-100 C
Solar/Wind Harmer
13.3
939351AE1-166 GEN
Solar/Wind Harmer
2.718
276893AG1-478 C
Solar/Wind Harmer
0.191
274729ELWOOD EC;1P
Adder
7.528
274730ELWOOD EC;6P
Adder
7.529
274734ELWOOD EC;8P
Adder
7.529
274736ELWOOD EC;9P
Adder
7.529
970707AG2-453 GEN
Solar/Wind Harmer
12.822
970513AG2-328 GEN
Solar/Wind Harmer
8.148
970517AG2-330 GEN
Solar/Wind Harmer
7.39
943121AE2-341 GEN
Solar/Wind Harmer
6.789
943591AF1-030 GEN
Solar/Wind Harmer
4.526
276694AA1-018 GEN2
Solar/Wind Harmer
2.856
274682WAUKEGAN ;7U
Adder
8.081
972236AH1-702 GEN2
Adder
0.962
274760LEE CO EC;1U
Adder
4.043
274767LEE CO EC;8U
Adder
3.995
962511AG1-100 GEN
Solar/Wind Helper
0.343
203830AF1-094 GEN
Solar/Wind Helper
0.325
959441AF2-235 GEN
Solar/Wind Helper
0.148
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.648
24190002OREGON_ST1
50/50
3.833
24189802OREGON_CT1
50/50
2.908
23888802TROY G4
50/50
1.906
241996AE2-282_GEN
Solar/Wind Harmer
2.191
971677AH1-339 GEN
Solar/Wind Harmer
6.006
246938BC-WTG3
Solar/Wind Harmer
2.366
246937BC-WTG2
Solar/Wind Harmer
2.326
270007AE1-245 C
Solar/Wind Harmer
3.514
942801AE2-298 GEN
Solar/Wind Harmer
0.89
961051AF2-396 GEN
Solar/Wind Harmer
9.316
961051AF2-396 GEN
Solar/Wind Harmer
4.333
960981AF2-389 GEN
Solar/Wind Harmer
0.871
957891AF2-083 GEN
Solar/Wind Harmer
1.944
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.337
970611AG2-400 GEN
Solar/Wind Harmer
5.384
270526AF1-158 GEN
Solar/Wind Harmer
2.437
24441505OLIV SLR
Solar/Wind Harmer
0.071
965681AG1-436 GEN
Solar/Wind Harmer
6.412
965791AG1-447 GEN
Solar/Wind Harmer
3.281
270224U2-072_GEN2
Solar/Wind Harmer
0.967
270227U2-072_GEN3
Solar/Wind Harmer
0.967
270228U2-072_GEN4
Solar/Wind Harmer
0.967
270231U2-072_GEN5
Solar/Wind Harmer
0.967
274808UNIV PK N;4U
Adder
2.345
274803UNIV PARK;6U
Adder
2.711
274888KELLY CRK;1U
Solar/Wind Harmer
2.732
274887GEN-1.85
Solar/Wind Harmer
2.466
276843GEN-1.7
Solar/Wind Harmer
0.265
958011AF2-095 GEN
Solar/Wind Harmer
6.663
274770LINCOLN ;1U
Adder
2.867
274771LINCOLN ;2U
Adder
2.867
972259AH1-714 GEN
Adder
8.76
274674JOLIET 9 ;6U
Adder
7.051
942221AE2-234 GEN
Solar/Wind Harmer
0.334
970321AG2-212 GEN
Solar/Wind Harmer
8.148
274847GR RIDGE ;BU
Solar/Wind Harmer
2.304
274695ROCKY RD ;2P
Adder
5.005
274693ROCKY RD ;1P
Adder
4.956
274697ROCKY RD ;3P
Adder
1.36
274696ROCKY RD ;4P
Adder
5.123
274683WAUKEGAN ;8U
Adder
9.466
274683WAUKEGAN ;8U
Adder
7.98
274764LEE CO EC;5U
Adder
4.052
274765LEE CO EC;6U
Adder
4.052
274762LEE CO EC;3U
Adder
4.043
274763LEE CO EC;4U
Adder
4.004
972267AH1-718 GEN
Adder
1.797
203947AF1-006 C
Solar/Wind Helper
0.382
203980AG1-197 GEN
Solar/Wind Helper
0.25
203979AG1-198 GEN
Solar/Wind Helper
0.195
241967AE2-285_GEN
Solar/Wind Helper
0.342
241801AE1-079 GEN
Solar/Wind Helper
0.133
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.33
946381AF1-302 GEN
Solar/Wind Helper
0.106
238217AF1-153 C O1
Solar/Wind Helper
0.112
958481AF2-142 GEN
Solar/Wind Harmer
6.677
991182J1586 G
External Queue
26.15285873413086
990527J1329
External Queue
1.9081761837005615
990142J1224
External Queue
13.94876766204834
991177J1571 G
External Queue
15.857954978942871
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.917
MECLTFEXP_MEC->PJM
CLTF
6.526
SIGELTFEXP_SIGE->PJM
CLTF
0.169
LAGNLTFEXP_LAGN->PJM
CLTF
4.973
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.195
TVALTFEXP_TVA->PJM
CLTF
2.252
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.785
NYPJM->LTFIMP_NY
CLTF
2.036
LGEELTFEXP_LGEE->PJM
CLTF
2.013
WECLTFEXP_WEC->PJM
CLTF
1.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.5 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2733.88
MW Contribution:16.63
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.833
24189802OREGON_CT1
50/50
2.907
23888802TROY G4
50/50
1.905
241996AE2-282_GEN
Solar/Wind Harmer
2.19
971677AH1-339 GEN
Solar/Wind Harmer
5.988
246938BC-WTG3
Solar/Wind Harmer
2.365
246937BC-WTG2
Solar/Wind Harmer
2.325
270007AE1-245 C
Solar/Wind Harmer
3.513
942801AE2-298 GEN
Solar/Wind Harmer
0.889
961051AF2-396 GEN
Solar/Wind Harmer
9.316
961051AF2-396 GEN
Solar/Wind Harmer
4.333
960981AF2-389 GEN
Solar/Wind Harmer
0.871
957891AF2-083 GEN
Solar/Wind Harmer
1.944
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.337
970611AG2-400 GEN
Solar/Wind Harmer
5.383
270526AF1-158 GEN
Solar/Wind Harmer
2.438
24441505OLIV SLR
Solar/Wind Harmer
0.071
965681AG1-436 GEN
Solar/Wind Harmer
6.413
965791AG1-447 GEN
Solar/Wind Harmer
3.281
270224U2-072_GEN2
Solar/Wind Harmer
0.967
270227U2-072_GEN3
Solar/Wind Harmer
0.967
270228U2-072_GEN4
Solar/Wind Harmer
0.967
270231U2-072_GEN5
Solar/Wind Harmer
0.967
274808UNIV PK N;4U
Adder
2.345
274803UNIV PARK;6U
Adder
2.712
274888KELLY CRK;1U
Solar/Wind Harmer
2.733
274887GEN-1.85
Solar/Wind Harmer
2.467
276843GEN-1.7
Solar/Wind Harmer
0.265
958011AF2-095 GEN
Solar/Wind Harmer
6.665
274770LINCOLN ;1U
Adder
2.868
274771LINCOLN ;2U
Adder
2.868
972259AH1-714 GEN
Adder
8.763
274674JOLIET 9 ;6U
Adder
7.053
942221AE2-234 GEN
Solar/Wind Harmer
0.334
970321AG2-212 GEN
Solar/Wind Harmer
8.15
274847GR RIDGE ;BU
Solar/Wind Harmer
2.304
958481AF2-142 GEN
Solar/Wind Harmer
6.79
274861TOP CROP ;1U
Solar/Wind Harmer
2.743
274862TOP CROP ;2U
Solar/Wind Harmer
2.29
274696ROCKY RD ;4P
Adder
5.124
274695ROCKY RD ;2P
Adder
5.006
274693ROCKY RD ;1P
Adder
4.957
274697ROCKY RD ;3P
Adder
1.36
274683WAUKEGAN ;8U
Adder
9.469
274683WAUKEGAN ;8U
Adder
7.982
274764LEE CO EC;5U
Adder
4.053
274765LEE CO EC;6U
Adder
4.053
274762LEE CO EC;3U
Adder
4.044
274763LEE CO EC;4U
Adder
4.006
972267AH1-718 GEN
Adder
1.798
203947AF1-006 C
Solar/Wind Helper
0.38
203980AG1-197 GEN
Solar/Wind Helper
0.249
203979AG1-198 GEN
Solar/Wind Helper
0.194
241967AE2-285_GEN
Solar/Wind Helper
0.34
241801AE1-079 GEN
Solar/Wind Helper
0.132
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.328
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
945421AF1-207 GEN
Solar/Wind Harmer
0.181
23867002DVBSG1
50/50
15.565
972211AH1-690 GEN
50/50
307.274
23888502TROY G1
50/50
1.905
23888602TROY G2
50/50
1.905
970817AG2-515 GEN
Solar/Wind Harmer
15.811
945411AF1-206 GEN
Solar/Wind Harmer
8.18
945641AF1-229 GEN
Solar/Wind Harmer
3.521
270499AE1-146 GEN
Solar/Wind Harmer
2.097
971549AH1-272 GEN
Solar/Wind Harmer
13.494
270297AD1-101 GEN
Solar/Wind Harmer
1.883
944161AF1-084 GEN
Solar/Wind Harmer
1.326
957201AF2-014 GEN
Solar/Wind Harmer
2.695
270435AC2-044 GEN
Solar/Wind Harmer
1.188
247607V1-011 GEN
Solar/Wind Harmer
2.341
965041AG1-368 GEN
Solar/Wind Harmer
5.573
965051AG1-369 GEN
Solar/Wind Harmer
2.763
966831AG1-554 GEN
Solar/Wind Harmer
0.657
971989AH1-539 GEN
Solar/Wind Harmer
7.103
971771AH1-392 GEN
Solar/Wind Harmer
4.929
971769AH1-391 GEN
Solar/Wind Harmer
5.338
270302AB2-170 GEN
Solar/Wind Harmer
4.419
270317AD1-130_GEN
Solar/Wind Harmer
1.694
960681AF2-359 GEN
Solar/Wind Harmer
1.938
971347AH1-153 GEN
Solar/Wind Harmer
7.656
971567AH1-282 GEN
Solar/Wind Harmer
7.507
963791AG1-232 GEN
Solar/Wind Harmer
6.72
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
270536AF1-215 GEN2
Solar/Wind Harmer
2.195
270071AF1-092 GEN
Solar/Wind Harmer
7.115
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274805UNIV PK N;1U
Adder
2.361
274811UNIV PK N;7U
Adder
2.356
958391AF2-133 GEN
Solar/Wind Harmer
4.265
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.602
960591AF2-350 GEN
Solar/Wind Harmer
4.628
274775LINCOLN ;6U
Adder
2.868
274776LINCOLN ;7U
Adder
2.868
274777LINCOLN ;8U
Adder
2.868
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.851
274687WILL CNTY;4U
Adder
12.851
274675JOLIET 29;7U
Adder
14.081
274675JOLIET 29;7U
Adder
13.578
274731ELWOOD EC;2P
Adder
7.53
274733ELWOOD EC;3P
Adder
7.53
274735ELWOOD EC;4P
Adder
7.53
274728ELWOOD EC;5P
Adder
7.531
970833AG2-524 GEN
Solar/Wind Harmer
3.979
970833AG2-524 GEN
Solar/Wind Harmer
1.851
274746AC1-111 G10
Adder
2.532
274744AC1-111 GEN8
Adder
2.532
24729505KEY G4
Adder
2.862
274823ROCKFORD ;21
Adder
8.571
241886AC2-103 GEN2
Solar/Wind Helper
3.958
241982AE2-343 S C
Solar/Wind Helper
0.118
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.866
24189902OREGON_CT2
50/50
2.849
23888702TROY G3
50/50
1.905
972253AH1-711 GEN
50/50
58.19
23856402BAYSG1
50/50
1.21
23920202STRYCT
50/50
1.931
241858AF1-205_GEN
Solar/Wind Harmer
5.563
241808AF1-120 C
Solar/Wind Harmer
1.221
241840AF1-064_GEN
Solar/Wind Harmer
1.36
972301AH1-735 GEN
Adder
6.662
23906402RICHG1
Adder
1.332
23906502RICHG2&3
Adder
1.329
270361_3
Solar/Wind Harmer
7.436
960841AF2-375 GEN
Solar/Wind Harmer
3.306
970515AG2-329 GEN
Solar/Wind Harmer
10.216
944231AF1-091 GEN
Solar/Wind Harmer
2.513
247522W1-056 GEN
Solar/Wind Harmer
1.436
246936BC-WTG1
Solar/Wind Harmer
2.325
270489AE1-102 GEN1
Solar/Wind Harmer
0.772
270449AD2-020 GEN
Solar/Wind Harmer
1.659
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
17.664
945111AF1-176 GEN
Solar/Wind Harmer
10.323
270505AE1-170 C O1
Solar/Wind Harmer
8.673
24695305TIMB G C
Solar/Wind Harmer
3.145
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
1.224
247521TR3_G114
Solar/Wind Harmer
1.86
270246TR4_N_V150
Solar/Wind Harmer
0.471
965011AG1-365 GEN
Solar/Wind Harmer
5.383
270462AD2-086
Solar/Wind Harmer
3.676
970373AG2-245 GEN
Solar/Wind Harmer
10.354
270223U2-072_GEN1
Solar/Wind Harmer
0.967
270578AF1-285 GEN2
Solar/Wind Harmer
0.591
270391AF1-285 GEN3
Solar/Wind Harmer
0.591
270055AF2-134 C O1
Solar/Wind Harmer
1.463
274751CRETE EC ;1U
Adder
2.328
274754CRETE EC ;4U
Adder
2.328
958381AF2-132 GEN
Solar/Wind Harmer
4.305
964861AG1-349 GEN
Solar/Wind Harmer
3.723
971917AH1-482 GEN
Solar/Wind Harmer
4.296
274723RIVER EC ;12
Adder
8.468
274812UNIV PK N;8U
Adder
2.356
276164X3-005 C
Solar/Wind Harmer
0.329
274801UNIV PARK;4U
Adder
2.703
276776AD2-060 GEN
Solar/Wind Harmer
0.196
940581AE2-045 GEN
Solar/Wind Harmer
4.718
972207SS24-0001
Solar/Wind Harmer
10.197
274773LINCOLN ;4U
Adder
2.868
274774LINCOLN ;5U
Adder
2.868
971605AH1-302 GEN
Solar/Wind Harmer
4.035
274676JOLIET 29;8U
Adder
14.081
941551AE2-152 GEN
Solar/Wind Harmer
2.079
274732ELWOOD EC;7P
Adder
7.531
274674JOLIET 9 ;6U
Adder
7.053
970245AG2-165 GEN
Solar/Wind Harmer
8.15
274871GR RIDGE ;2U
Solar/Wind Harmer
3.503
274745AC1-111 GEN9
Adder
2.532
276691AA1-018 GEN1
Solar/Wind Harmer
0.211
274682WAUKEGAN ;7U
Adder
8.083
274828WAUKEGAN ;BP
Adder
4.964
274822ROCKFORD ;11
Adder
8.634
972235AH1-702 GEN1
Adder
1.107
274761LEE CO EC;2U
Adder
4.044
274766LEE CO EC;7U
Adder
3.996
241885AC2-103 GEN1
Solar/Wind Helper
3.958
241807AE2-176_GEN
Solar/Wind Helper
2.236
961971AG1-040 GEN
Solar/Wind Helper
0.334
203835AF1-098 GEN
Solar/Wind Helper
1.316
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
23929302BS-PKR
50/50
2.13
241832AE2-181_GEN
Solar/Wind Harmer
1.987
958321AF2-126 GEN
Solar/Wind Harmer
1.458
23906502RICHG2&3
Adder
1.329
270541AE2-072 C
Solar/Wind Harmer
4.244
270575GUS2 35KV
Solar/Wind Harmer
8.76
970217AG2-149 GEN
Solar/Wind Harmer
22.527
270044AE2-322 C
Solar/Wind Harmer
0.862
270404AC1-167 GEN
Solar/Wind Harmer
0.718
247604X1-042
Adder
0.265
270258AD1-119 GEN
Solar/Wind Harmer
1.759
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.772
958091AF2-103 GEN
Solar/Wind Harmer
0.096
270588AE1-091_GEN
Solar/Wind Harmer
6.477
945111AF1-176 GEN
Solar/Wind Harmer
3.272
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0.039
970031AG2-029 GEN
Solar/Wind Harmer
16.631
270191TR4_S_V150
Solar/Wind Harmer
1.66
270247TR4_N_V136
Solar/Wind Harmer
0.471
959331AF2-224 GEN
Solar/Wind Harmer
5.383
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270485AE1-090_GEN
Solar/Wind Harmer
0.32
270043AE2-236 GEN
Solar/Wind Harmer
2.809
970349AG2-230 GEN
Solar/Wind Harmer
7.656
942871AE2-306 GEN
Solar/Wind Harmer
0.444
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
270535AF1-215 GEN1
Solar/Wind Harmer
2.195
972231SS25-0005
Solar/Wind Harmer
4.52
972181SS23-001
Solar/Wind Harmer
2.825
274752CRETE EC ;2U
Adder
2.328
274753CRETE EC ;3U
Adder
2.328
964401AG1-302 GEN
Solar/Wind Harmer
4.305
274724RIVER EC ;11
Adder
8.367
959141AF2-205 GEN
Solar/Wind Harmer
2.822
274802UNIV PARK;5U
Adder
2.712
274826FISK ;BP
Adder
5.083
274800UNIV PARK;3U
Adder
2.703
972038AH1-567 GEN2
Adder
0.169
276772AC2-154 GEN
Solar/Wind Harmer
1.291
276806AD2-047 C O1
Solar/Wind Harmer
4.951
970941AG2-585 GEN
Solar/Wind Harmer
5.785
274772LINCOLN ;3U
Adder
2.868
972228AH1-698 GEN2
Adder
1.709
274676JOLIET 29;8U
Adder
13.578
276897AD1-100 C
Solar/Wind Harmer
13.304
939351AE1-166 GEN
Solar/Wind Harmer
2.718
276893AG1-478 C
Solar/Wind Harmer
0.191
274729ELWOOD EC;1P
Adder
7.53
274730ELWOOD EC;6P
Adder
7.531
274734ELWOOD EC;8P
Adder
7.531
274736ELWOOD EC;9P
Adder
7.531
970707AG2-453 GEN
Solar/Wind Harmer
12.825
970513AG2-328 GEN
Solar/Wind Harmer
8.15
970517AG2-330 GEN
Solar/Wind Harmer
7.392
943121AE2-341 GEN
Solar/Wind Harmer
6.791
943591AF1-030 GEN
Solar/Wind Harmer
4.527
276694AA1-018 GEN2
Solar/Wind Harmer
2.856
274682WAUKEGAN ;7U
Adder
8.083
972236AH1-702 GEN2
Adder
0.963
274760LEE CO EC;1U
Adder
4.044
274767LEE CO EC;8U
Adder
3.996
962511AG1-100 GEN
Solar/Wind Helper
0.341
203830AF1-094 GEN
Solar/Wind Helper
0.323
959441AF2-235 GEN
Solar/Wind Helper
0.147
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.645
991182J1586 G
External Queue
26.137367248535156
990527J1329
External Queue
1.9070898294448853
990142J1224
External Queue
13.940826416015625
991177J1571 G
External Queue
15.847536087036133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.932
MECLTFEXP_MEC->PJM
CLTF
6.529
SIGELTFEXP_SIGE->PJM
CLTF
0.169
LAGNLTFEXP_LAGN->PJM
CLTF
4.982
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.217
TVALTFEXP_TVA->PJM
CLTF
2.257
CPLELTFEXP_CPLE->PJM
CLTF
0.339
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.829
NYPJM->LTFIMP_NY
CLTF
2.024
LGEELTFEXP_LGEE->PJM
CLTF
2.015
WECLTFEXP_WEC->PJM
CLTF
1.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.86 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2589.31
MW Contribution:2.51
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.847
23888702TROY G3
50/50
1.904
972253AH1-711 GEN
50/50
58.156
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.93
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
3.878
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.656
23906402RICHG1
Adder
1.331
23906502RICHG2&3
Adder
1.328
270361_3
Solar/Wind Harmer
4.06
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.751
944231AF1-091 GEN
Solar/Wind Harmer
1.239
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.168
270489AE1-102 GEN1
Solar/Wind Harmer
0.538
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.152
965421AG1-410 GEN
Solar/Wind Harmer
12.302
945111AF1-176 GEN
Solar/Wind Harmer
7.189
270505AE1-170 C O1
Solar/Wind Harmer
4.228
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
0.003
247521TR3_G114
Solar/Wind Harmer
0.14
270246TR4_N_V150
Solar/Wind Harmer
0.025
24190002OREGON_ST1
50/50
3.831
24189802OREGON_CT1
50/50
2.906
23888802TROY G4
50/50
1.904
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.588
970621AG2-405 GEN
Solar/Wind Harmer
0.863
970623AG2-406 GEN
Solar/Wind Harmer
0.804
246938BC-WTG3
Solar/Wind Harmer
0.15
246937BC-WTG2
Solar/Wind Harmer
0.168
270007AE1-245 C
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
8.176
961051AF2-396 GEN
Solar/Wind Harmer
5.45
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.749
970627AG2-408 GEN
Solar/Wind Harmer
1.125
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.465
965791AG1-447 GEN
Solar/Wind Harmer
3.275
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.34
274803UNIV PARK;6U
Adder
2.706
274888KELLY CRK;1U
Solar/Wind Harmer
0.189
274887GEN-1.85
Solar/Wind Harmer
0.085
276843GEN-1.7
Solar/Wind Harmer
0.104
958011AF2-095 GEN
Solar/Wind Harmer
4.64
274770LINCOLN ;1U
Adder
3.895
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.129
23906502RICHG2&3
Adder
1.328
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.06
970217AG2-149 GEN
Solar/Wind Harmer
4.25
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.264
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.538
270588AE1-091_GEN
Solar/Wind Harmer
3.207
945111AF1-176 GEN
Solar/Wind Harmer
3.266
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.509
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.025
959331AF2-224 GEN
Solar/Wind Harmer
2.624
965021AG1-366 GEN
Solar/Wind Harmer
1.25
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.282
970349AG2-230 GEN
Solar/Wind Harmer
5.331
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.916
274753CRETE EC ;3U
Adder
3.916
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.349
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.706
274826FISK ;BP
Adder
5.072
274800UNIV PARK;3U
Adder
2.697
23867002DVBSG1
50/50
15.559
972211AH1-690 GEN
50/50
307.104
23888502TROY G1
50/50
1.904
23888602TROY G2
50/50
1.904
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
11.024
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.026
971549AH1-272 GEN
Solar/Wind Harmer
10.494
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.524
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.812
965041AG1-368 GEN
Solar/Wind Harmer
3.881
965051AG1-369 GEN
Solar/Wind Harmer
1.924
971989AH1-539 GEN
Solar/Wind Harmer
1.649
971771AH1-392 GEN
Solar/Wind Harmer
3.814
971769AH1-391 GEN
Solar/Wind Harmer
4.151
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.517
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.331
971567AH1-282 GEN
Solar/Wind Harmer
5.227
965011AG1-365 GEN
Solar/Wind Harmer
3.749
270462AD2-086
Solar/Wind Harmer
0.008
970373AG2-245 GEN
Solar/Wind Harmer
7.209
270223U2-072_GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
3.916
274754CRETE EC ;4U
Adder
3.916
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.287
274723RIVER EC ;12
Adder
8.45
274812UNIV PK N;8U
Adder
2.351
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.697
276776AD2-060 GEN
Solar/Wind Harmer
0.336
274773LINCOLN ;4U
Adder
3.895
274774LINCOLN ;5U
Adder
3.895
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.026
274676JOLIET 29;8U
Adder
14.05
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.514
274674JOLIET 9 ;6U
Adder
7.038
970245AG2-165 GEN
Solar/Wind Harmer
1.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.526
276691AA1-018 GEN1
Solar/Wind Harmer
0.382
274682WAUKEGAN ;7U
Adder
8.065
274828WAUKEGAN ;BP
Adder
4.952
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.328
962781AG1-127 GEN
Solar/Wind Harmer
2.956
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.624
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.055
957471AF2-041 GEN
Solar/Wind Harmer
9.206
959081AF2-199 GEN
Solar/Wind Harmer
3.069
971067AG2-660 GEN
Solar/Wind Harmer
1.023
274822ROCKFORD ;11
Adder
8.614
972235AH1-702 GEN1
Adder
1.104
970569AG2-363 GEN
Solar/Wind Harmer
9.17
970819AG2-516 GEN
Solar/Wind Harmer
3.66
971475AH1-234 GEN
Solar/Wind Harmer
1.477
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.035
274766LEE CO EC;7U
Adder
2.419
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
241807AE2-176_GEN
Solar/Wind Helper
2.238
274771LINCOLN ;2U
Adder
3.895
972259AH1-714 GEN
Adder
8.743
274674JOLIET 9 ;6U
Adder
7.038
942221AE2-234 GEN
Solar/Wind Harmer
0.016
970321AG2-212 GEN
Solar/Wind Harmer
1.377
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.726
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.426
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.585
274696ROCKY RD ;4P
Adder
5.113
274695ROCKY RD ;2P
Adder
4.995
274693ROCKY RD ;1P
Adder
4.946
274697ROCKY RD ;3P
Adder
1.357
274683WAUKEGAN ;8U
Adder
9.448
274683WAUKEGAN ;8U
Adder
7.964
958491AF2-143 GEN
Solar/Wind Harmer
4.684
962691AG1-118 GEN
Solar/Wind Harmer
9.334
274879MINONK ;1U
Solar/Wind Harmer
0.131
970921AG2-575 GEN
Solar/Wind Harmer
3.106
970921AG2-575 GEN
Solar/Wind Harmer
1.035
942991AE2-321 GEN
Solar/Wind Harmer
3.454
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.163
971335AH1-147 GEN
Solar/Wind Harmer
6.163
971341AH1-150 GEN
Solar/Wind Harmer
6.137
971343AH1-151 GEN
Solar/Wind Harmer
6.137
274856ECOGROVE ;U1
Solar/Wind Harmer
0.072
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.719
274764LEE CO EC;5U
Adder
4.044
274765LEE CO EC;6U
Adder
4.044
274762LEE CO EC;3U
Adder
4.035
274763LEE CO EC;4U
Adder
3.996
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.342
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
276741O09 GEN1
Solar/Wind Harmer
0.107
276708O09 GEN2
Solar/Wind Harmer
0.107
203947AF1-006 C
Solar/Wind Helper
0.381
203980AG1-197 GEN
Solar/Wind Helper
0.249
203979AG1-198 GEN
Solar/Wind Helper
0.194
241967AE2-285_GEN
Solar/Wind Helper
0.341
241801AE1-079 GEN
Solar/Wind Helper
0.133
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.329
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.112
972038AH1-567 GEN2
Adder
0.169
276806AD2-047 C O1
Solar/Wind Harmer
1.826
970941AG2-585 GEN
Solar/Wind Harmer
4.027
274772LINCOLN ;3U
Adder
3.895
972228AH1-698 GEN2
Adder
1.705
274676JOLIET 29;8U
Adder
13.548
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.126
274729ELWOOD EC;1P
Adder
7.514
274730ELWOOD EC;6P
Adder
7.514
274734ELWOOD EC;8P
Adder
7.514
274736ELWOOD EC;9P
Adder
7.514
970707AG2-453 GEN
Solar/Wind Harmer
10.416
970513AG2-328 GEN
Solar/Wind Harmer
1.377
970517AG2-330 GEN
Solar/Wind Harmer
8.26
943121AE2-341 GEN
Solar/Wind Harmer
5.284
943591AF1-030 GEN
Solar/Wind Harmer
3.514
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.61
274682WAUKEGAN ;7U
Adder
8.065
276805AD2-038 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
13.898
274872LEEDK;1U
Solar/Wind Harmer
0.114
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.1
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
0.113
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
959091AF2-200 GEN
Solar/Wind Harmer
6.137
972236AH1-702 GEN2
Adder
0.96
970571AG2-364 GEN
Solar/Wind Harmer
6.113
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.035
276157O29GEN1
Solar/Wind Harmer
0.485
962511AG1-100 GEN
Solar/Wind Helper
0.342
203830AF1-094 GEN
Solar/Wind Helper
0.324
959441AF2-235 GEN
Solar/Wind Helper
0.147
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.646
961971AG1-040 GEN
Solar/Wind Helper
0.334
203835AF1-098 GEN
Solar/Wind Helper
1.318
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
963791AG1-232 GEN
Solar/Wind Harmer
4.679
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.329
274814UNIV PK N;0U
Adder
2.371
274807UNIV PK N;3U
Adder
2.366
274805UNIV PK N;1U
Adder
2.356
274811UNIV PK N;7U
Adder
2.351
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.595
960591AF2-350 GEN
Solar/Wind Harmer
3.222
274775LINCOLN ;6U
Adder
3.895
274776LINCOLN ;7U
Adder
3.895
274777LINCOLN ;8U
Adder
3.895
971611AH1-305 GEN
Solar/Wind Harmer
1.917
972227AH1-698 GEN1
Adder
1.201
274687WILL CNTY;4U
Adder
12.823
274687WILL CNTY;4U
Adder
12.823
274675JOLIET 29;7U
Adder
14.05
274675JOLIET 29;7U
Adder
13.548
274731ELWOOD EC;2P
Adder
7.514
274733ELWOOD EC;3P
Adder
7.514
274735ELWOOD EC;4P
Adder
7.514
274728ELWOOD EC;5P
Adder
7.514
970833AG2-524 GEN
Solar/Wind Harmer
3.49
970833AG2-524 GEN
Solar/Wind Harmer
2.327
274746AC1-111 G10
Adder
2.526
274744AC1-111 GEN8
Adder
2.526
270024AE2-089 GEN
Solar/Wind Harmer
0.003
276868AE1-113 GEN
Solar/Wind Harmer
0.623
276882AE2-255 GEN
Solar/Wind Harmer
0.363
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.907
971411AH1-196 GEN
Solar/Wind Harmer
4.626
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.202
24729505KEY G4
Adder
2.855
971171AH1-044 GEN
Solar/Wind Harmer
6.137
274823ROCKFORD ;21
Adder
8.551
926823AC1-168 GEN
Solar/Wind Harmer
0.519
970169AG2-114 GEN
Solar/Wind Harmer
3.05
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
4.885
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.766
957751AF2-069 GEN
Solar/Wind Harmer
0.099
241982AE2-343 S C
Solar/Wind Helper
0.119
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.868
991182J1586 G
External Queue
26.137367248535156
990527J1329
External Queue
1.9070898294448853
990142J1224
External Queue
13.940826416015625
991177J1571 G
External Queue
15.847536087036133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.893
MECLTFEXP_MEC->PJM
CLTF
6.512
SIGELTFEXP_SIGE->PJM
CLTF
0.168
LAGNLTFEXP_LAGN->PJM
CLTF
4.961
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.186
TVALTFEXP_TVA->PJM
CLTF
2.246
CPLELTFEXP_CPLE->PJM
CLTF
0.328
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.692
NYPJM->LTFIMP_NY
CLTF
2.031
LGEELTFEXP_LGEE->PJM
CLTF
2.008
WECLTFEXP_WEC->PJM
CLTF
1.673
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.39 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2580.58
MW Contribution:2.51
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.849
23888702TROY G3
50/50
1.905
972253AH1-711 GEN
50/50
58.19
23856402BAYSG1
50/50
1.21
23920202STRYCT
50/50
1.931
241858AF1-205_GEN
Solar/Wind Harmer
3.881
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.662
23906402RICHG1
Adder
1.332
23906502RICHG2&3
Adder
1.329
270361_3
Solar/Wind Harmer
4.064
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.77
944231AF1-091 GEN
Solar/Wind Harmer
1.241
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.168
270489AE1-102 GEN1
Solar/Wind Harmer
0.539
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
12.324
945111AF1-176 GEN
Solar/Wind Harmer
7.202
270505AE1-170 C O1
Solar/Wind Harmer
4.236
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
0.003
247521TR3_G114
Solar/Wind Harmer
0.141
270246TR4_N_V150
Solar/Wind Harmer
0.025
965011AG1-365 GEN
Solar/Wind Harmer
3.756
270462AD2-086
Solar/Wind Harmer
0.008
970373AG2-245 GEN
Solar/Wind Harmer
7.224
270223U2-072_GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
3.925
274754CRETE EC ;4U
Adder
3.925
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.296
274723RIVER EC ;12
Adder
8.468
274812UNIV PK N;8U
Adder
2.356
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.703
276776AD2-060 GEN
Solar/Wind Harmer
0.337
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
274773LINCOLN ;4U
Adder
3.904
274774LINCOLN ;5U
Adder
3.904
971605AH1-302 GEN
Solar/Wind Harmer
4.035
274676JOLIET 29;8U
Adder
14.081
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.531
274674JOLIET 9 ;6U
Adder
7.053
970245AG2-165 GEN
Solar/Wind Harmer
1.38
24190002OREGON_ST1
50/50
3.833
24189802OREGON_CT1
50/50
2.907
23888802TROY G4
50/50
1.905
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.588
970621AG2-405 GEN
Solar/Wind Harmer
0.864
970623AG2-406 GEN
Solar/Wind Harmer
0.806
246938BC-WTG3
Solar/Wind Harmer
0.15
246937BC-WTG2
Solar/Wind Harmer
0.168
23929302BS-PKR
50/50
2.13
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.13
23906502RICHG2&3
Adder
1.329
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.064
970217AG2-149 GEN
Solar/Wind Harmer
4.257
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.265
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.539
270588AE1-091_GEN
Solar/Wind Harmer
3.213
945111AF1-176 GEN
Solar/Wind Harmer
3.272
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.514
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.025
959331AF2-224 GEN
Solar/Wind Harmer
2.629
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.287
970349AG2-230 GEN
Solar/Wind Harmer
5.341
270007AE1-245 C
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
8.19
961051AF2-396 GEN
Solar/Wind Harmer
5.46
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.756
970627AG2-408 GEN
Solar/Wind Harmer
1.127
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.474
965791AG1-447 GEN
Solar/Wind Harmer
3.281
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.345
274803UNIV PARK;6U
Adder
2.712
274888KELLY CRK;1U
Solar/Wind Harmer
0.19
274887GEN-1.85
Solar/Wind Harmer
0.085
276843GEN-1.7
Solar/Wind Harmer
0.105
958011AF2-095 GEN
Solar/Wind Harmer
4.65
274770LINCOLN ;1U
Adder
3.904
274771LINCOLN ;2U
Adder
3.904
972259AH1-714 GEN
Adder
8.763
274674JOLIET 9 ;6U
Adder
7.053
942221AE2-234 GEN
Solar/Wind Harmer
0.016
970321AG2-212 GEN
Solar/Wind Harmer
1.38
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.737
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.925
274753CRETE EC ;3U
Adder
3.925
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.367
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.712
274826FISK ;BP
Adder
5.083
274800UNIV PARK;3U
Adder
2.703
972038AH1-567 GEN2
Adder
0.169
276806AD2-047 C O1
Solar/Wind Harmer
1.83
970941AG2-585 GEN
Solar/Wind Harmer
4.036
274772LINCOLN ;3U
Adder
3.904
972228AH1-698 GEN2
Adder
1.709
274676JOLIET 29;8U
Adder
13.578
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.127
274729ELWOOD EC;1P
Adder
7.53
274730ELWOOD EC;6P
Adder
7.531
274734ELWOOD EC;8P
Adder
7.531
274736ELWOOD EC;9P
Adder
7.531
970707AG2-453 GEN
Solar/Wind Harmer
10.439
970513AG2-328 GEN
Solar/Wind Harmer
1.38
970517AG2-330 GEN
Solar/Wind Harmer
8.279
943121AE2-341 GEN
Solar/Wind Harmer
5.296
943591AF1-030 GEN
Solar/Wind Harmer
3.522
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.616
23867002DVBSG1
50/50
15.565
972211AH1-690 GEN
50/50
307.274
23888502TROY G1
50/50
1.905
23888602TROY G2
50/50
1.905
970817AG2-515 GEN
Solar/Wind Harmer
11.031
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.026
971549AH1-272 GEN
Solar/Wind Harmer
10.508
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.525
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.815
965041AG1-368 GEN
Solar/Wind Harmer
3.888
965051AG1-369 GEN
Solar/Wind Harmer
1.928
971989AH1-539 GEN
Solar/Wind Harmer
1.652
971771AH1-392 GEN
Solar/Wind Harmer
3.821
971769AH1-391 GEN
Solar/Wind Harmer
4.158
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.518
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.341
971567AH1-282 GEN
Solar/Wind Harmer
5.238
963791AG1-232 GEN
Solar/Wind Harmer
4.689
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.342
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274805UNIV PK N;1U
Adder
2.361
274811UNIV PK N;7U
Adder
2.356
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.602
960591AF2-350 GEN
Solar/Wind Harmer
3.229
274775LINCOLN ;6U
Adder
3.904
274776LINCOLN ;7U
Adder
3.904
274777LINCOLN ;8U
Adder
3.904
971611AH1-305 GEN
Solar/Wind Harmer
1.922
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.851
274687WILL CNTY;4U
Adder
12.851
274675JOLIET 29;7U
Adder
14.081
274675JOLIET 29;7U
Adder
13.578
274731ELWOOD EC;2P
Adder
7.53
274733ELWOOD EC;3P
Adder
7.53
274862TOP CROP ;2U
Solar/Wind Harmer
0.427
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.586
274696ROCKY RD ;4P
Adder
5.124
274695ROCKY RD ;2P
Adder
5.006
274693ROCKY RD ;1P
Adder
4.957
274697ROCKY RD ;3P
Adder
1.36
274683WAUKEGAN ;8U
Adder
9.469
274683WAUKEGAN ;8U
Adder
7.982
958491AF2-143 GEN
Solar/Wind Harmer
4.695
962691AG1-118 GEN
Solar/Wind Harmer
9.356
274879MINONK ;1U
Solar/Wind Harmer
0.131
970921AG2-575 GEN
Solar/Wind Harmer
3.113
970921AG2-575 GEN
Solar/Wind Harmer
1.038
942991AE2-321 GEN
Solar/Wind Harmer
3.462
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.177
971335AH1-147 GEN
Solar/Wind Harmer
6.177
971341AH1-150 GEN
Solar/Wind Harmer
6.151
971343AH1-151 GEN
Solar/Wind Harmer
6.151
274856ECOGROVE ;U1
Solar/Wind Harmer
0.072
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.723
274764LEE CO EC;5U
Adder
4.053
274765LEE CO EC;6U
Adder
4.053
274762LEE CO EC;3U
Adder
4.044
274763LEE CO EC;4U
Adder
4.006
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.342
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
276741O09 GEN1
Solar/Wind Harmer
0.107
276708O09 GEN2
Solar/Wind Harmer
0.107
276782AC1-033 GEN
Solar/Wind Harmer
0
203947AF1-006 C
Solar/Wind Helper
0.38
203980AG1-197 GEN
Solar/Wind Helper
0.249
203979AG1-198 GEN
Solar/Wind Helper
0.194
241967AE2-285_GEN
Solar/Wind Helper
0.34
241801AE1-079 GEN
Solar/Wind Helper
0.132
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.328
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
274735ELWOOD EC;4P
Adder
7.53
274728ELWOOD EC;5P
Adder
7.531
970833AG2-524 GEN
Solar/Wind Harmer
3.498
970833AG2-524 GEN
Solar/Wind Harmer
2.332
274746AC1-111 G10
Adder
2.532
274744AC1-111 GEN8
Adder
2.532
270024AE2-089 GEN
Solar/Wind Harmer
0.003
276868AE1-113 GEN
Solar/Wind Harmer
0.625
276882AE2-255 GEN
Solar/Wind Harmer
0.364
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.911
971411AH1-196 GEN
Solar/Wind Harmer
4.636
274682WAUKEGAN ;7U
Adder
8.083
276805AD2-038 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
13.93
274872LEEDK;1U
Solar/Wind Harmer
0.114
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.107
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.113
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
959091AF2-200 GEN
Solar/Wind Harmer
6.151
970571AG2-364 GEN
Solar/Wind Harmer
6.128
972236AH1-702 GEN2
Adder
0.963
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.044
276157O29GEN1
Solar/Wind Harmer
0.487
962511AG1-100 GEN
Solar/Wind Helper
0.341
203830AF1-094 GEN
Solar/Wind Helper
0.323
959441AF2-235 GEN
Solar/Wind Helper
0.147
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.645
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.532
276691AA1-018 GEN1
Solar/Wind Harmer
0.383
274682WAUKEGAN ;7U
Adder
8.083
274828WAUKEGAN ;BP
Adder
4.964
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.333
962781AG1-127 GEN
Solar/Wind Harmer
2.963
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.628
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.055
957471AF2-041 GEN
Solar/Wind Harmer
9.227
959081AF2-199 GEN
Solar/Wind Harmer
3.076
971067AG2-660 GEN
Solar/Wind Harmer
1.025
274822ROCKFORD ;11
Adder
8.634
970569AG2-363 GEN
Solar/Wind Harmer
9.191
972235AH1-702 GEN1
Adder
1.107
970819AG2-516 GEN
Solar/Wind Harmer
3.668
971475AH1-234 GEN
Solar/Wind Harmer
1.481
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.044
274766LEE CO EC;7U
Adder
2.424
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
3.958
241807AE2-176_GEN
Solar/Wind Helper
2.236
961971AG1-040 GEN
Solar/Wind Helper
0.334
203835AF1-098 GEN
Solar/Wind Helper
1.316
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.204
24729505KEY G4
Adder
2.862
971171AH1-044 GEN
Solar/Wind Harmer
6.151
274823ROCKFORD ;21
Adder
8.571
926823AC1-168 GEN
Solar/Wind Harmer
0.52
970169AG2-114 GEN
Solar/Wind Harmer
3.057
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
4.897
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.771
957751AF2-069 GEN
Solar/Wind Harmer
0.099
241886AC2-103 GEN2
Solar/Wind Helper
3.958
241982AE2-343 S C
Solar/Wind Helper
0.118
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.866
991182J1586 G
External Queue
26.137367248535156
990527J1329
External Queue
1.9070898294448853
990142J1224
External Queue
13.940826416015625
991177J1571 G
External Queue
15.847536087036133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.932
MECLTFEXP_MEC->PJM
CLTF
6.529
SIGELTFEXP_SIGE->PJM
CLTF
0.169
LAGNLTFEXP_LAGN->PJM
CLTF
4.982
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.217
TVALTFEXP_TVA->PJM
CLTF
2.257
CPLELTFEXP_CPLE->PJM
CLTF
0.339
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.829
NYPJM->LTFIMP_NY
CLTF
2.024
LGEELTFEXP_LGEE->PJM
CLTF
2.015
WECLTFEXP_WEC->PJM
CLTF
1.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-F1_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.03 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2551.84
MW Contribution:16.14
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
14.157
972211AH1-690 GEN
50/50
290.294
23888502TROY G1
50/50
1.813
23888602TROY G2
50/50
1.813
970817AG2-515 GEN
Solar/Wind Harmer
15.206
945411AF1-206 GEN
Solar/Wind Harmer
8.026
945641AF1-229 GEN
Solar/Wind Harmer
3.439
270499AE1-146 GEN
Solar/Wind Harmer
2.201
971549AH1-272 GEN
Solar/Wind Harmer
13.004
270297AD1-101 GEN
Solar/Wind Harmer
1.871
247607V1-011 GEN
Solar/Wind Harmer
2.303
957201AF2-014 GEN
Solar/Wind Harmer
2.636
270435AC2-044 GEN
Solar/Wind Harmer
1.162
944161AF1-084 GEN
Solar/Wind Harmer
1.282
966831AG1-554 GEN
Solar/Wind Harmer
0.674
971989AH1-539 GEN
Solar/Wind Harmer
7.284
965041AG1-368 GEN
Solar/Wind Harmer
5.453
965051AG1-369 GEN
Solar/Wind Harmer
2.706
971771AH1-392 GEN
Solar/Wind Harmer
4.773
270302AB2-170 GEN
Solar/Wind Harmer
4.342
270317AD1-130_GEN
Solar/Wind Harmer
1.665
971769AH1-391 GEN
Solar/Wind Harmer
5.17
971567AH1-282 GEN
Solar/Wind Harmer
7.463
960681AF2-359 GEN
Solar/Wind Harmer
1.878
971347AH1-153 GEN
Solar/Wind Harmer
7.421
963791AG1-232 GEN
Solar/Wind Harmer
6.559
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.129
270071AF1-092 GEN
Solar/Wind Harmer
6.925
274814UNIV PK N;0U
Adder
2.305
274807UNIV PK N;3U
Adder
2.3
274805UNIV PK N;1U
Adder
2.29
274811UNIV PK N;7U
Adder
2.285
958391AF2-133 GEN
Solar/Wind Harmer
4.138
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.495
960591AF2-350 GEN
Solar/Wind Harmer
4.49
274775LINCOLN ;6U
Adder
2.783
274776LINCOLN ;7U
Adder
2.783
274777LINCOLN ;8U
Adder
2.783
972227AH1-698 GEN1
Adder
1.168
274687WILL CNTY;4U
Adder
12.469
274687WILL CNTY;4U
Adder
12.469
274675JOLIET 29;7U
Adder
13.662
274675JOLIET 29;7U
Adder
13.175
274728ELWOOD EC;5P
Adder
7.307
274731ELWOOD EC;2P
Adder
7.307
274733ELWOOD EC;3P
Adder
7.307
274735ELWOOD EC;4P
Adder
7.307
970833AG2-524 GEN
Solar/Wind Harmer
3.861
970833AG2-524 GEN
Solar/Wind Harmer
1.796
274746AC1-111 G10
Adder
2.457
274744AC1-111 GEN8
Adder
2.457
270024AE2-089 GEN
Solar/Wind Harmer
2.062
241886AC2-103 GEN2
Solar/Wind Helper
9.152
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.243
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.851
24190002OREGON_ST1
50/50
3.621
24189802OREGON_CT1
50/50
2.747
23888802TROY G4
50/50
1.813
241996AE2-282_GEN
Solar/Wind Harmer
2.149
971677AH1-339 GEN
Solar/Wind Harmer
6.251
270007AE1-245 C
Solar/Wind Harmer
3.456
246938BC-WTG3
Solar/Wind Harmer
2.313
246937BC-WTG2
Solar/Wind Harmer
2.274
942801AE2-298 GEN
Solar/Wind Harmer
0.875
961051AF2-396 GEN
Solar/Wind Harmer
9.012
961051AF2-396 GEN
Solar/Wind Harmer
4.192
960981AF2-389 GEN
Solar/Wind Harmer
0.843
957891AF2-083 GEN
Solar/Wind Harmer
1.881
247620Y3-023
Adder
0.251
270216AD2-079_GEN
Solar/Wind Harmer
0.326
970611AG2-400 GEN
Solar/Wind Harmer
5.249
270526AF1-158 GEN
Solar/Wind Harmer
2.361
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.214
965791AG1-447 GEN
Solar/Wind Harmer
3.179
270224U2-072_GEN2
Solar/Wind Harmer
0.951
270227U2-072_GEN3
Solar/Wind Harmer
0.951
270228U2-072_GEN4
Solar/Wind Harmer
0.951
270231U2-072_GEN5
Solar/Wind Harmer
0.951
274808UNIV PK N;4U
Adder
2.275
274803UNIV PARK;6U
Adder
2.631
274888KELLY CRK;1U
Solar/Wind Harmer
2.651
274887GEN-1.85
Solar/Wind Harmer
2.393
276843GEN-1.7
Solar/Wind Harmer
0.258
958011AF2-095 GEN
Solar/Wind Harmer
6.466
274770LINCOLN ;1U
Adder
2.783
274771LINCOLN ;2U
Adder
2.783
972259AH1-714 GEN
Adder
8.502
942221AE2-234 GEN
Solar/Wind Harmer
0.326
274674JOLIET 9 ;6U
Adder
6.844
970321AG2-212 GEN
Solar/Wind Harmer
7.911
274847GR RIDGE ;BU
Solar/Wind Harmer
2.236
958481AF2-142 GEN
Solar/Wind Harmer
6.589
274696ROCKY RD ;4P
Adder
4.973
274695ROCKY RD ;2P
Adder
4.858
274693ROCKY RD ;1P
Adder
4.81
274697ROCKY RD ;3P
Adder
1.32
274683WAUKEGAN ;8U
Adder
9.189
274683WAUKEGAN ;8U
Adder
7.746
203947AF1-006 C
Solar/Wind Helper
0.374
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241801AE1-079 GEN
Solar/Wind Helper
0.13
241967AE2-285_GEN
Solar/Wind Helper
0.334
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.322
946381AF1-302 GEN
Solar/Wind Helper
0.103
274861TOP CROP ;1U
Solar/Wind Harmer
0.243
274862TOP CROP ;2U
Solar/Wind Harmer
0.203
24189902OREGON_CT2
50/50
2.691
23888702TROY G3
50/50
1.813
972253AH1-711 GEN
50/50
55.392
23856402BAYSG1
50/50
1.233
23920202STRYCT
50/50
1.896
241858AF1-205_GEN
Solar/Wind Harmer
5.467
241808AF1-120 C
Solar/Wind Harmer
1.198
241840AF1-064_GEN
Solar/Wind Harmer
1.359
972301AH1-735 GEN
Adder
6.555
23906402RICHG1
Adder
1.311
23906502RICHG2&3
Adder
1.308
270361_3
Solar/Wind Harmer
7.869
960841AF2-375 GEN
Solar/Wind Harmer
3.486
970515AG2-329 GEN
Solar/Wind Harmer
10.065
247522W1-056 GEN
Solar/Wind Harmer
1.487
944231AF1-091 GEN
Solar/Wind Harmer
2.457
246936BC-WTG1
Solar/Wind Harmer
2.274
270489AE1-102 GEN1
Solar/Wind Harmer
0.755
965421AG1-410 GEN
Solar/Wind Harmer
17.272
270449AD2-020 GEN
Solar/Wind Harmer
1.604
943021AE2-325 GEN
Solar/Wind Harmer
2.085
24695305TIMB G C
Solar/Wind Harmer
3.084
945111AF1-176 GEN
Solar/Wind Harmer
9.989
270505AE1-170 C O1
Solar/Wind Harmer
8.391
24639705ELKHART HY
Adder
0.083
247521TR3_G114
Solar/Wind Harmer
1.822
270246TR4_N_V150
Solar/Wind Harmer
0.461
270063AE2-323 C
Solar/Wind Harmer
1.189
965011AG1-365 GEN
Solar/Wind Harmer
5.249
270462AD2-086
Solar/Wind Harmer
3.612
270223U2-072_GEN1
Solar/Wind Harmer
0.951
270578AF1-285 GEN2
Solar/Wind Harmer
0.581
270391AF1-285 GEN3
Solar/Wind Harmer
0.581
970373AG2-245 GEN
Solar/Wind Harmer
10.039
270055AF2-134 C O1
Solar/Wind Harmer
1.419
274751CRETE EC ;1U
Adder
2.258
274754CRETE EC ;4U
Adder
2.258
958381AF2-132 GEN
Solar/Wind Harmer
4.176
964861AG1-349 GEN
Solar/Wind Harmer
3.612
971917AH1-482 GEN
Solar/Wind Harmer
4.168
274723RIVER EC ;12
Adder
8.214
274812UNIV PK N;8U
Adder
2.285
276164X3-005 C
Solar/Wind Harmer
0.319
274801UNIV PARK;4U
Adder
2.622
276776AD2-060 GEN
Solar/Wind Harmer
0.19
940581AE2-045 GEN
Solar/Wind Harmer
4.579
971605AH1-302 GEN
Solar/Wind Harmer
3.915
972207SS24-0001
Solar/Wind Harmer
9.894
274773LINCOLN ;4U
Adder
2.783
274774LINCOLN ;5U
Adder
2.783
274676JOLIET 29;8U
Adder
13.662
941551AE2-152 GEN
Solar/Wind Harmer
2.017
274732ELWOOD EC;7P
Adder
7.307
274674JOLIET 9 ;6U
Adder
6.844
970245AG2-165 GEN
Solar/Wind Harmer
7.911
274871GR RIDGE ;2U
Solar/Wind Harmer
3.399
274745AC1-111 GEN9
Adder
2.457
276691AA1-018 GEN1
Solar/Wind Harmer
0.205
274682WAUKEGAN ;7U
Adder
7.844
274828WAUKEGAN ;BP
Adder
4.817
241885AC2-103 GEN1
Solar/Wind Helper
9.152
961971AG1-040 GEN
Solar/Wind Helper
0.328
203835AF1-098 GEN
Solar/Wind Helper
1.294
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.075
23929302BS-PKR
50/50
2.169
241832AE2-181_GEN
Solar/Wind Harmer
1.949
958321AF2-126 GEN
Solar/Wind Harmer
1.457
23906502RICHG2&3
Adder
1.308
270541AE2-072 C
Solar/Wind Harmer
4.233
270575GUS2 35KV
Solar/Wind Harmer
9.271
970217AG2-149 GEN
Solar/Wind Harmer
22.195
270044AE2-322 C
Solar/Wind Harmer
0.848
270404AC1-167 GEN
Solar/Wind Harmer
0.706
270258AD1-119 GEN
Solar/Wind Harmer
1.728
247604X1-042
Adder
0.256
24441205WTRV SLR C
Solar/Wind Harmer
0.081
270588AE1-091_GEN
Solar/Wind Harmer
6.56
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.755
945111AF1-176 GEN
Solar/Wind Harmer
3.166
24642205MAYFLWER
Adder
0.346
270191TR4_S_V150
Solar/Wind Harmer
1.626
270247TR4_N_V136
Solar/Wind Harmer
0.461
970031AG2-029 GEN
Solar/Wind Harmer
16.144
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.249
965021AG1-366 GEN
Solar/Wind Harmer
1.221
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270043AE2-236 GEN
Solar/Wind Harmer
2.733
970349AG2-230 GEN
Solar/Wind Harmer
7.421
942871AE2-306 GEN
Solar/Wind Harmer
0.436
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270535AF1-215 GEN1
Solar/Wind Harmer
2.129
972231SS25-0005
Solar/Wind Harmer
4.384
972181SS23-001
Solar/Wind Harmer
2.74
274752CRETE EC ;2U
Adder
2.258
274753CRETE EC ;3U
Adder
2.258
964401AG1-302 GEN
Solar/Wind Harmer
4.176
274724RIVER EC ;11
Adder
8.116
959141AF2-205 GEN
Solar/Wind Harmer
2.738
274802UNIV PARK;5U
Adder
2.631
274826FISK ;BP
Adder
4.931
274800UNIV PARK;3U
Adder
2.622
972038AH1-567 GEN2
Adder
0.164
276772AC2-154 GEN
Solar/Wind Harmer
1.252
276806AD2-047 C O1
Solar/Wind Harmer
4.804
970941AG2-585 GEN
Solar/Wind Harmer
5.613
274772LINCOLN ;3U
Adder
2.783
972228AH1-698 GEN2
Adder
1.658
274676JOLIET 29;8U
Adder
13.174
276897AD1-100 C
Solar/Wind Harmer
12.909
939351AE1-166 GEN
Solar/Wind Harmer
2.638
276893AG1-478 C
Solar/Wind Harmer
0.186
274730ELWOOD EC;6P
Adder
7.307
274734ELWOOD EC;8P
Adder
7.307
274736ELWOOD EC;9P
Adder
7.307
970707AG2-453 GEN
Solar/Wind Harmer
12.445
274729ELWOOD EC;1P
Adder
7.307
970513AG2-328 GEN
Solar/Wind Harmer
7.911
970517AG2-330 GEN
Solar/Wind Harmer
7.175
971617AH1-308 GEN
Solar/Wind Harmer
2.555
943121AE2-341 GEN
Solar/Wind Harmer
6.59
943591AF1-030 GEN
Solar/Wind Harmer
4.393
276694AA1-018 GEN2
Solar/Wind Harmer
2.772
274682WAUKEGAN ;7U
Adder
7.844
962511AG1-100 GEN
Solar/Wind Helper
0.336
203830AF1-094 GEN
Solar/Wind Helper
0.318
959441AF2-235 GEN
Solar/Wind Helper
0.144
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.633
991182J1586 G
External Queue
24.90056610107422
990527J1329
External Queue
1.8186211585998535
990142J1224
External Queue
13.294119834899902
991177J1571 G
External Queue
15.212156295776367
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.92
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.716
MECLTFEXP_MEC->PJM
CLTF
6.343
SIGELTFEXP_SIGE->PJM
CLTF
0.165
LAGNLTFEXP_LAGN->PJM
CLTF
4.854
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.172
TVALTFEXP_TVA->PJM
CLTF
2.201
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.784
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
1.969
WECLTFEXP_WEC->PJM
CLTF
1.628
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-12_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-12_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.03 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2551.84
MW Contribution:16.14
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.691
23888702TROY G3
50/50
1.813
972253AH1-711 GEN
50/50
55.392
23856402BAYSG1
50/50
1.233
23920202STRYCT
50/50
1.896
241858AF1-205_GEN
Solar/Wind Harmer
5.467
241808AF1-120 C
Solar/Wind Harmer
1.198
241840AF1-064_GEN
Solar/Wind Harmer
1.359
972301AH1-735 GEN
Adder
6.555
23906402RICHG1
Adder
1.311
23906502RICHG2&3
Adder
1.308
270361_3
Solar/Wind Harmer
7.869
960841AF2-375 GEN
Solar/Wind Harmer
3.486
970515AG2-329 GEN
Solar/Wind Harmer
10.065
247522W1-056 GEN
Solar/Wind Harmer
1.487
944231AF1-091 GEN
Solar/Wind Harmer
2.457
246936BC-WTG1
Solar/Wind Harmer
2.274
270489AE1-102 GEN1
Solar/Wind Harmer
0.755
965421AG1-410 GEN
Solar/Wind Harmer
17.272
270449AD2-020 GEN
Solar/Wind Harmer
1.604
943021AE2-325 GEN
Solar/Wind Harmer
2.085
24695305TIMB G C
Solar/Wind Harmer
3.084
945111AF1-176 GEN
Solar/Wind Harmer
9.989
270505AE1-170 C O1
Solar/Wind Harmer
8.391
24639705ELKHART HY
Adder
0.083
247521TR3_G114
Solar/Wind Harmer
1.822
270246TR4_N_V150
Solar/Wind Harmer
0.461
270063AE2-323 C
Solar/Wind Harmer
1.189
965011AG1-365 GEN
Solar/Wind Harmer
5.249
270462AD2-086
Solar/Wind Harmer
3.612
270223U2-072_GEN1
Solar/Wind Harmer
0.951
270578AF1-285 GEN2
Solar/Wind Harmer
0.581
270391AF1-285 GEN3
Solar/Wind Harmer
0.581
970373AG2-245 GEN
Solar/Wind Harmer
10.039
270055AF2-134 C O1
Solar/Wind Harmer
1.419
274751CRETE EC ;1U
Adder
2.258
274754CRETE EC ;4U
Adder
2.258
958381AF2-132 GEN
Solar/Wind Harmer
4.176
964861AG1-349 GEN
Solar/Wind Harmer
3.612
971917AH1-482 GEN
Solar/Wind Harmer
4.168
274723RIVER EC ;12
Adder
8.214
274812UNIV PK N;8U
Adder
2.285
276164X3-005 C
Solar/Wind Harmer
0.319
274801UNIV PARK;4U
Adder
2.622
276776AD2-060 GEN
Solar/Wind Harmer
0.19
940581AE2-045 GEN
Solar/Wind Harmer
4.579
971605AH1-302 GEN
Solar/Wind Harmer
3.915
972207SS24-0001
Solar/Wind Harmer
9.894
274773LINCOLN ;4U
Adder
2.783
274774LINCOLN ;5U
Adder
2.783
274676JOLIET 29;8U
Adder
13.662
941551AE2-152 GEN
Solar/Wind Harmer
2.017
274732ELWOOD EC;7P
Adder
7.307
274674JOLIET 9 ;6U
Adder
6.844
970245AG2-165 GEN
Solar/Wind Harmer
7.911
274871GR RIDGE ;2U
Solar/Wind Harmer
3.399
274745AC1-111 GEN9
Adder
2.457
276691AA1-018 GEN1
Solar/Wind Harmer
0.205
274682WAUKEGAN ;7U
Adder
7.844
274828WAUKEGAN ;BP
Adder
4.817
241885AC2-103 GEN1
Solar/Wind Helper
9.152
961971AG1-040 GEN
Solar/Wind Helper
0.328
203835AF1-098 GEN
Solar/Wind Helper
1.294
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.075
23929302BS-PKR
50/50
2.169
241832AE2-181_GEN
Solar/Wind Harmer
1.949
958321AF2-126 GEN
Solar/Wind Harmer
1.457
23906502RICHG2&3
Adder
1.308
270541AE2-072 C
Solar/Wind Harmer
4.233
270575GUS2 35KV
Solar/Wind Harmer
9.271
970217AG2-149 GEN
Solar/Wind Harmer
22.195
270044AE2-322 C
Solar/Wind Harmer
0.848
270404AC1-167 GEN
Solar/Wind Harmer
0.706
270258AD1-119 GEN
Solar/Wind Harmer
1.728
247604X1-042
Adder
0.256
24441205WTRV SLR C
Solar/Wind Harmer
0.081
270588AE1-091_GEN
Solar/Wind Harmer
6.56
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.755
945111AF1-176 GEN
Solar/Wind Harmer
3.166
24642205MAYFLWER
Adder
0.346
270191TR4_S_V150
Solar/Wind Harmer
1.626
270247TR4_N_V136
Solar/Wind Harmer
0.461
970031AG2-029 GEN
Solar/Wind Harmer
16.144
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.249
965021AG1-366 GEN
Solar/Wind Harmer
1.221
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270043AE2-236 GEN
Solar/Wind Harmer
2.733
970349AG2-230 GEN
Solar/Wind Harmer
7.421
942871AE2-306 GEN
Solar/Wind Harmer
0.436
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270535AF1-215 GEN1
Solar/Wind Harmer
2.129
972231SS25-0005
Solar/Wind Harmer
4.384
972181SS23-001
Solar/Wind Harmer
2.74
274752CRETE EC ;2U
Adder
2.258
274753CRETE EC ;3U
Adder
2.258
964401AG1-302 GEN
Solar/Wind Harmer
4.176
274724RIVER EC ;11
Adder
8.116
959141AF2-205 GEN
Solar/Wind Harmer
2.738
274802UNIV PARK;5U
Adder
2.631
274826FISK ;BP
Adder
4.931
274800UNIV PARK;3U
Adder
2.622
972038AH1-567 GEN2
Adder
0.164
276772AC2-154 GEN
Solar/Wind Harmer
1.252
276806AD2-047 C O1
Solar/Wind Harmer
4.804
970941AG2-585 GEN
Solar/Wind Harmer
5.613
274772LINCOLN ;3U
Adder
2.783
972228AH1-698 GEN2
Adder
1.658
274676JOLIET 29;8U
Adder
13.174
276897AD1-100 C
Solar/Wind Harmer
12.909
939351AE1-166 GEN
Solar/Wind Harmer
2.638
276893AG1-478 C
Solar/Wind Harmer
0.186
274730ELWOOD EC;6P
Adder
7.307
274734ELWOOD EC;8P
Adder
7.307
274736ELWOOD EC;9P
Adder
7.307
970707AG2-453 GEN
Solar/Wind Harmer
12.445
274729ELWOOD EC;1P
Adder
7.307
970513AG2-328 GEN
Solar/Wind Harmer
7.911
970517AG2-330 GEN
Solar/Wind Harmer
7.175
971617AH1-308 GEN
Solar/Wind Harmer
2.555
943121AE2-341 GEN
Solar/Wind Harmer
6.59
943591AF1-030 GEN
Solar/Wind Harmer
4.393
276694AA1-018 GEN2
Solar/Wind Harmer
2.772
274682WAUKEGAN ;7U
Adder
7.844
962511AG1-100 GEN
Solar/Wind Helper
0.336
203830AF1-094 GEN
Solar/Wind Helper
0.318
959441AF2-235 GEN
Solar/Wind Helper
0.144
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.633
23867002DVBSG1
50/50
14.157
972211AH1-690 GEN
50/50
290.294
23888502TROY G1
50/50
1.813
23888602TROY G2
50/50
1.813
970817AG2-515 GEN
Solar/Wind Harmer
15.206
945411AF1-206 GEN
Solar/Wind Harmer
8.026
945641AF1-229 GEN
Solar/Wind Harmer
3.439
270499AE1-146 GEN
Solar/Wind Harmer
2.201
971549AH1-272 GEN
Solar/Wind Harmer
13.004
270297AD1-101 GEN
Solar/Wind Harmer
1.871
247607V1-011 GEN
Solar/Wind Harmer
2.303
957201AF2-014 GEN
Solar/Wind Harmer
2.636
270435AC2-044 GEN
Solar/Wind Harmer
1.162
944161AF1-084 GEN
Solar/Wind Harmer
1.282
966831AG1-554 GEN
Solar/Wind Harmer
0.674
971989AH1-539 GEN
Solar/Wind Harmer
7.284
965041AG1-368 GEN
Solar/Wind Harmer
5.453
965051AG1-369 GEN
Solar/Wind Harmer
2.706
971771AH1-392 GEN
Solar/Wind Harmer
4.773
270302AB2-170 GEN
Solar/Wind Harmer
4.342
270317AD1-130_GEN
Solar/Wind Harmer
1.665
971769AH1-391 GEN
Solar/Wind Harmer
5.17
971567AH1-282 GEN
Solar/Wind Harmer
7.463
960681AF2-359 GEN
Solar/Wind Harmer
1.878
971347AH1-153 GEN
Solar/Wind Harmer
7.421
963791AG1-232 GEN
Solar/Wind Harmer
6.559
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.129
270071AF1-092 GEN
Solar/Wind Harmer
6.925
274814UNIV PK N;0U
Adder
2.305
274807UNIV PK N;3U
Adder
2.3
274805UNIV PK N;1U
Adder
2.29
274811UNIV PK N;7U
Adder
2.285
958391AF2-133 GEN
Solar/Wind Harmer
4.138
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.495
960591AF2-350 GEN
Solar/Wind Harmer
4.49
274775LINCOLN ;6U
Adder
2.783
274776LINCOLN ;7U
Adder
2.783
274777LINCOLN ;8U
Adder
2.783
972227AH1-698 GEN1
Adder
1.168
274687WILL CNTY;4U
Adder
12.469
274687WILL CNTY;4U
Adder
12.469
274675JOLIET 29;7U
Adder
13.662
274675JOLIET 29;7U
Adder
13.175
274728ELWOOD EC;5P
Adder
7.307
274731ELWOOD EC;2P
Adder
7.307
274733ELWOOD EC;3P
Adder
7.307
274735ELWOOD EC;4P
Adder
7.307
970833AG2-524 GEN
Solar/Wind Harmer
3.861
970833AG2-524 GEN
Solar/Wind Harmer
1.796
274746AC1-111 G10
Adder
2.457
274744AC1-111 GEN8
Adder
2.457
270024AE2-089 GEN
Solar/Wind Harmer
2.062
241886AC2-103 GEN2
Solar/Wind Helper
9.152
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.243
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.851
24190002OREGON_ST1
50/50
3.621
24189802OREGON_CT1
50/50
2.747
23888802TROY G4
50/50
1.813
241996AE2-282_GEN
Solar/Wind Harmer
2.149
971677AH1-339 GEN
Solar/Wind Harmer
6.251
270007AE1-245 C
Solar/Wind Harmer
3.456
246938BC-WTG3
Solar/Wind Harmer
2.313
246937BC-WTG2
Solar/Wind Harmer
2.274
942801AE2-298 GEN
Solar/Wind Harmer
0.875
961051AF2-396 GEN
Solar/Wind Harmer
9.012
961051AF2-396 GEN
Solar/Wind Harmer
4.192
960981AF2-389 GEN
Solar/Wind Harmer
0.843
957891AF2-083 GEN
Solar/Wind Harmer
1.881
247620Y3-023
Adder
0.251
270216AD2-079_GEN
Solar/Wind Harmer
0.326
970611AG2-400 GEN
Solar/Wind Harmer
5.249
270526AF1-158 GEN
Solar/Wind Harmer
2.361
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.214
965791AG1-447 GEN
Solar/Wind Harmer
3.179
270224U2-072_GEN2
Solar/Wind Harmer
0.951
270227U2-072_GEN3
Solar/Wind Harmer
0.951
270228U2-072_GEN4
Solar/Wind Harmer
0.951
270231U2-072_GEN5
Solar/Wind Harmer
0.951
274808UNIV PK N;4U
Adder
2.275
274803UNIV PARK;6U
Adder
2.631
274888KELLY CRK;1U
Solar/Wind Harmer
2.651
274887GEN-1.85
Solar/Wind Harmer
2.393
276843GEN-1.7
Solar/Wind Harmer
0.258
958011AF2-095 GEN
Solar/Wind Harmer
6.466
274770LINCOLN ;1U
Adder
2.783
274771LINCOLN ;2U
Adder
2.783
972259AH1-714 GEN
Adder
8.502
942221AE2-234 GEN
Solar/Wind Harmer
0.326
274674JOLIET 9 ;6U
Adder
6.844
970321AG2-212 GEN
Solar/Wind Harmer
7.911
274847GR RIDGE ;BU
Solar/Wind Harmer
2.236
958481AF2-142 GEN
Solar/Wind Harmer
6.589
274696ROCKY RD ;4P
Adder
4.973
274695ROCKY RD ;2P
Adder
4.858
274693ROCKY RD ;1P
Adder
4.81
274697ROCKY RD ;3P
Adder
1.32
274683WAUKEGAN ;8U
Adder
9.189
274683WAUKEGAN ;8U
Adder
7.746
203947AF1-006 C
Solar/Wind Helper
0.374
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241801AE1-079 GEN
Solar/Wind Helper
0.13
241967AE2-285_GEN
Solar/Wind Helper
0.334
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.322
946381AF1-302 GEN
Solar/Wind Helper
0.103
274861TOP CROP ;1U
Solar/Wind Harmer
0.243
274862TOP CROP ;2U
Solar/Wind Harmer
0.203
991182J1586 G
External Queue
24.90056610107422
990527J1329
External Queue
1.8186211585998535
990142J1224
External Queue
13.294119834899902
991177J1571 G
External Queue
15.212156295776367
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.92
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.716
MECLTFEXP_MEC->PJM
CLTF
6.343
SIGELTFEXP_SIGE->PJM
CLTF
0.165
LAGNLTFEXP_LAGN->PJM
CLTF
4.854
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.172
TVALTFEXP_TVA->PJM
CLTF
2.201
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.784
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
1.969
WECLTFEXP_WEC->PJM
CLTF
1.628
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010B1_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010B1_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.46 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2525.94
MW Contribution:15.94
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.668
23888702TROY G3
50/50
1.796
972253AH1-711 GEN
50/50
54.848
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.869
241858AF1-205_GEN
Solar/Wind Harmer
5.389
241808AF1-120 C
Solar/Wind Harmer
1.181
241840AF1-064_GEN
Solar/Wind Harmer
1.337
972301AH1-735 GEN
Adder
6.461
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.289
270361_3
Solar/Wind Harmer
7.682
960841AF2-375 GEN
Solar/Wind Harmer
3.405
970515AG2-329 GEN
Solar/Wind Harmer
9.92
247522W1-056 GEN
Solar/Wind Harmer
1.456
944231AF1-091 GEN
Solar/Wind Harmer
2.424
246936BC-WTG1
Solar/Wind Harmer
2.243
270489AE1-102 GEN1
Solar/Wind Harmer
0.745
965421AG1-410 GEN
Solar/Wind Harmer
17.04
270449AD2-020 GEN
Solar/Wind Harmer
1.585
943021AE2-325 GEN
Solar/Wind Harmer
2.06
945111AF1-176 GEN
Solar/Wind Harmer
9.87
270505AE1-170 C O1
Solar/Wind Harmer
8.291
24695305TIMB G C
Solar/Wind Harmer
3.042
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
1.797
270246TR4_N_V150
Solar/Wind Harmer
0.455
270063AE2-323 C
Solar/Wind Harmer
1.174
965011AG1-365 GEN
Solar/Wind Harmer
5.181
270462AD2-086
Solar/Wind Harmer
3.561
270223U2-072_GEN1
Solar/Wind Harmer
0.937
270578AF1-285 GEN2
Solar/Wind Harmer
0.573
270391AF1-285 GEN3
Solar/Wind Harmer
0.573
970373AG2-245 GEN
Solar/Wind Harmer
9.916
270055AF2-134 C O1
Solar/Wind Harmer
1.402
274751CRETE EC ;1U
Adder
2.23
274754CRETE EC ;4U
Adder
2.23
958381AF2-132 GEN
Solar/Wind Harmer
4.125
964861AG1-349 GEN
Solar/Wind Harmer
3.567
971917AH1-482 GEN
Solar/Wind Harmer
4.117
274723RIVER EC ;12
Adder
8.113
274812UNIV PK N;8U
Adder
2.257
276164X3-005 C
Solar/Wind Harmer
0.315
274801UNIV PARK;4U
Adder
2.59
276776AD2-060 GEN
Solar/Wind Harmer
0.188
940581AE2-045 GEN
Solar/Wind Harmer
4.522
971605AH1-302 GEN
Solar/Wind Harmer
3.867
972207SS24-0001
Solar/Wind Harmer
9.772
274773LINCOLN ;4U
Adder
2.748
274774LINCOLN ;5U
Adder
2.748
274676JOLIET 29;8U
Adder
13.494
941551AE2-152 GEN
Solar/Wind Harmer
1.993
274732ELWOOD EC;7P
Adder
7.217
274674JOLIET 9 ;6U
Adder
6.759
970245AG2-165 GEN
Solar/Wind Harmer
7.813
274871GR RIDGE ;2U
Solar/Wind Harmer
3.357
274745AC1-111 GEN9
Adder
2.426
276691AA1-018 GEN1
Solar/Wind Harmer
0.202
274682WAUKEGAN ;7U
Adder
7.748
274828WAUKEGAN ;BP
Adder
4.757
241885AC2-103 GEN1
Solar/Wind Helper
9.126
961971AG1-040 GEN
Solar/Wind Helper
0.324
203835AF1-098 GEN
Solar/Wind Helper
1.276
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.764
254303AC2-168 GEN
Solar/Wind Helper
0.074
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
1.922
958321AF2-126 GEN
Solar/Wind Harmer
1.433
23906502RICHG2&3
Adder
1.289
270541AE2-072 C
Solar/Wind Harmer
4.165
270575GUS2 35KV
Solar/Wind Harmer
9.05
970217AG2-149 GEN
Solar/Wind Harmer
21.874
270044AE2-322 C
Solar/Wind Harmer
0.836
270404AC1-167 GEN
Solar/Wind Harmer
0.696
270258AD1-119 GEN
Solar/Wind Harmer
1.704
247604X1-042
Adder
0.253
24441205WTRV SLR C
Solar/Wind Harmer
0.08
270588AE1-091_GEN
Solar/Wind Harmer
6.441
958091AF2-103 GEN
Solar/Wind Harmer
0.093
270491AE1-102 GEN2
Solar/Wind Harmer
0.745
945111AF1-176 GEN
Solar/Wind Harmer
3.128
24642205MAYFLWER
Adder
0.342
270191TR4_S_V150
Solar/Wind Harmer
1.604
270247TR4_N_V136
Solar/Wind Harmer
0.455
247643Z2-116 C
Solar/Wind Harmer
0.037
970031AG2-029 GEN
Solar/Wind Harmer
15.944
959331AF2-224 GEN
Solar/Wind Harmer
5.181
965021AG1-366 GEN
Solar/Wind Harmer
1.205
270485AE1-090_GEN
Solar/Wind Harmer
0.31
270043AE2-236 GEN
Solar/Wind Harmer
2.698
970349AG2-230 GEN
Solar/Wind Harmer
7.33
942871AE2-306 GEN
Solar/Wind Harmer
0.43
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
2.103
972231SS25-0005
Solar/Wind Harmer
4.331
972181SS23-001
Solar/Wind Harmer
2.707
274752CRETE EC ;2U
Adder
2.23
274753CRETE EC ;3U
Adder
2.23
964401AG1-302 GEN
Solar/Wind Harmer
4.125
274724RIVER EC ;11
Adder
8.016
959141AF2-205 GEN
Solar/Wind Harmer
2.704
274802UNIV PARK;5U
Adder
2.599
274826FISK ;BP
Adder
4.871
274800UNIV PARK;3U
Adder
2.59
972038AH1-567 GEN2
Adder
0.162
276772AC2-154 GEN
Solar/Wind Harmer
1.237
276806AD2-047 C O1
Solar/Wind Harmer
4.745
970941AG2-585 GEN
Solar/Wind Harmer
5.544
274772LINCOLN ;3U
Adder
2.748
972228AH1-698 GEN2
Adder
1.638
274676JOLIET 29;8U
Adder
13.012
276897AD1-100 C
Solar/Wind Harmer
12.75
939351AE1-166 GEN
Solar/Wind Harmer
2.605
276893AG1-478 C
Solar/Wind Harmer
0.183
274729ELWOOD EC;1P
Adder
7.217
274730ELWOOD EC;6P
Adder
7.217
274734ELWOOD EC;8P
Adder
7.217
274736ELWOOD EC;9P
Adder
7.217
970707AG2-453 GEN
Solar/Wind Harmer
12.291
970513AG2-328 GEN
Solar/Wind Harmer
7.813
970517AG2-330 GEN
Solar/Wind Harmer
7.086
943121AE2-341 GEN
Solar/Wind Harmer
6.509
943591AF1-030 GEN
Solar/Wind Harmer
4.339
23867002DVBSG1
50/50
14.11
972211AH1-690 GEN
50/50
287.754
23888502TROY G1
50/50
1.796
23888602TROY G2
50/50
1.796
970817AG2-515 GEN
Solar/Wind Harmer
15.035
945411AF1-206 GEN
Solar/Wind Harmer
7.914
945641AF1-229 GEN
Solar/Wind Harmer
3.393
270499AE1-146 GEN
Solar/Wind Harmer
2.151
971549AH1-272 GEN
Solar/Wind Harmer
12.855
270297AD1-101 GEN
Solar/Wind Harmer
1.842
247607V1-011 GEN
Solar/Wind Harmer
2.271
944161AF1-084 GEN
Solar/Wind Harmer
1.267
957201AF2-014 GEN
Solar/Wind Harmer
2.6
270435AC2-044 GEN
Solar/Wind Harmer
1.147
966831AG1-554 GEN
Solar/Wind Harmer
0.66
971989AH1-539 GEN
Solar/Wind Harmer
7.141
965041AG1-368 GEN
Solar/Wind Harmer
5.38
965051AG1-369 GEN
Solar/Wind Harmer
2.669
971771AH1-392 GEN
Solar/Wind Harmer
4.715
270302AB2-170 GEN
Solar/Wind Harmer
4.281
270317AD1-130_GEN
Solar/Wind Harmer
1.641
971769AH1-391 GEN
Solar/Wind Harmer
5.107
960681AF2-359 GEN
Solar/Wind Harmer
1.855
971567AH1-282 GEN
Solar/Wind Harmer
7.347
971347AH1-153 GEN
Solar/Wind Harmer
7.33
963791AG1-232 GEN
Solar/Wind Harmer
6.473
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
2.103
270071AF1-092 GEN
Solar/Wind Harmer
6.837
274814UNIV PK N;0U
Adder
2.277
274807UNIV PK N;3U
Adder
2.272
274805UNIV PK N;1U
Adder
2.262
274811UNIV PK N;7U
Adder
2.257
958391AF2-133 GEN
Solar/Wind Harmer
4.087
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.452
960591AF2-350 GEN
Solar/Wind Harmer
4.435
274775LINCOLN ;6U
Adder
2.748
274776LINCOLN ;7U
Adder
2.748
274777LINCOLN ;8U
Adder
2.748
972227AH1-698 GEN1
Adder
1.153
274687WILL CNTY;4U
Adder
12.315
274687WILL CNTY;4U
Adder
12.315
274675JOLIET 29;7U
Adder
13.494
274675JOLIET 29;7U
Adder
13.012
274731ELWOOD EC;2P
Adder
7.217
274733ELWOOD EC;3P
Adder
7.217
274735ELWOOD EC;4P
Adder
7.217
274728ELWOOD EC;5P
Adder
7.217
970833AG2-524 GEN
Solar/Wind Harmer
3.814
970833AG2-524 GEN
Solar/Wind Harmer
1.774
274746AC1-111 G10
Adder
2.426
274744AC1-111 GEN8
Adder
2.426
241886AC2-103 GEN2
Solar/Wind Helper
9.126
241982AE2-343 S C
Solar/Wind Helper
0.114
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.24
241997AF1-093 GEN
Solar/Wind Helper
0.126
203804AE2-113_GEN
Solar/Wind Helper
0.838
270024AE2-089 GEN
Solar/Wind Harmer
0.078
276694AA1-018 GEN2
Solar/Wind Harmer
2.738
274682WAUKEGAN ;7U
Adder
7.748
962511AG1-100 GEN
Solar/Wind Helper
0.331
203830AF1-094 GEN
Solar/Wind Helper
0.313
959441AF2-235 GEN
Solar/Wind Helper
0.142
254305AE2-115 C
Solar/Wind Helper
0.109
971617AH1-308 GEN
Solar/Wind Harmer
0.096
24190002OREGON_ST1
50/50
3.59
24189802OREGON_CT1
50/50
2.723
23888802TROY G4
50/50
1.796
241996AE2-282_GEN
Solar/Wind Harmer
2.119
971677AH1-339 GEN
Solar/Wind Harmer
6.113
270007AE1-245 C
Solar/Wind Harmer
3.406
246938BC-WTG3
Solar/Wind Harmer
2.282
246937BC-WTG2
Solar/Wind Harmer
2.243
942801AE2-298 GEN
Solar/Wind Harmer
0.863
961051AF2-396 GEN
Solar/Wind Harmer
8.904
961051AF2-396 GEN
Solar/Wind Harmer
4.142
960981AF2-389 GEN
Solar/Wind Harmer
0.833
957891AF2-083 GEN
Solar/Wind Harmer
1.858
247620Y3-023
Adder
0.248
270216AD2-079_GEN
Solar/Wind Harmer
0.322
970611AG2-400 GEN
Solar/Wind Harmer
5.181
270526AF1-158 GEN
Solar/Wind Harmer
2.332
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.139
965791AG1-447 GEN
Solar/Wind Harmer
3.141
270224U2-072_GEN2
Solar/Wind Harmer
0.937
270227U2-072_GEN3
Solar/Wind Harmer
0.937
270228U2-072_GEN4
Solar/Wind Harmer
0.937
270231U2-072_GEN5
Solar/Wind Harmer
0.937
274808UNIV PK N;4U
Adder
2.247
274803UNIV PARK;6U
Adder
2.599
274888KELLY CRK;1U
Solar/Wind Harmer
2.618
274887GEN-1.85
Solar/Wind Harmer
2.364
276843GEN-1.7
Solar/Wind Harmer
0.254
958011AF2-095 GEN
Solar/Wind Harmer
6.387
274770LINCOLN ;1U
Adder
2.748
274771LINCOLN ;2U
Adder
2.748
972259AH1-714 GEN
Adder
8.397
942221AE2-234 GEN
Solar/Wind Harmer
0.322
274674JOLIET 9 ;6U
Adder
6.759
970321AG2-212 GEN
Solar/Wind Harmer
7.813
274847GR RIDGE ;BU
Solar/Wind Harmer
2.208
958481AF2-142 GEN
Solar/Wind Harmer
6.507
274861TOP CROP ;1U
Solar/Wind Harmer
2.629
274862TOP CROP ;2U
Solar/Wind Harmer
2.195
274696ROCKY RD ;4P
Adder
4.912
274695ROCKY RD ;2P
Adder
4.798
274693ROCKY RD ;1P
Adder
4.751
274697ROCKY RD ;3P
Adder
1.303
274683WAUKEGAN ;8U
Adder
9.076
274683WAUKEGAN ;8U
Adder
7.65
203947AF1-006 C
Solar/Wind Helper
0.369
203980AG1-197 GEN
Solar/Wind Helper
0.241
203979AG1-198 GEN
Solar/Wind Helper
0.188
241801AE1-079 GEN
Solar/Wind Helper
0.128
241967AE2-285_GEN
Solar/Wind Helper
0.329
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.317
991182J1586 G
External Queue
24.65229034423828
990527J1329
External Queue
1.8002409934997559
990142J1224
External Queue
13.159761428833008
991177J1571 G
External Queue
15.044508934020996
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.603
MECLTFEXP_MEC->PJM
CLTF
6.264
SIGELTFEXP_SIGE->PJM
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
4.792
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
TVALTFEXP_TVA->PJM
CLTF
2.173
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.291
NYPJM->LTFIMP_NY
CLTF
1.957
LGEELTFEXP_LGEE->PJM
CLTF
1.943
WECLTFEXP_WEC->PJM
CLTF
1.608
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010B2_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010B2_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.46 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2525.94
MW Contribution:15.94
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.668
23888702TROY G3
50/50
1.796
972253AH1-711 GEN
50/50
54.848
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.869
241858AF1-205_GEN
Solar/Wind Harmer
5.389
241808AF1-120 C
Solar/Wind Harmer
1.181
241840AF1-064_GEN
Solar/Wind Harmer
1.337
972301AH1-735 GEN
Adder
6.461
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.289
270361_3
Solar/Wind Harmer
7.682
960841AF2-375 GEN
Solar/Wind Harmer
3.405
970515AG2-329 GEN
Solar/Wind Harmer
9.92
247522W1-056 GEN
Solar/Wind Harmer
1.456
944231AF1-091 GEN
Solar/Wind Harmer
2.424
246936BC-WTG1
Solar/Wind Harmer
2.243
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
1.922
958321AF2-126 GEN
Solar/Wind Harmer
1.433
23906502RICHG2&3
Adder
1.289
270541AE2-072 C
Solar/Wind Harmer
4.165
270575GUS2 35KV
Solar/Wind Harmer
9.05
970217AG2-149 GEN
Solar/Wind Harmer
21.874
270044AE2-322 C
Solar/Wind Harmer
0.836
270404AC1-167 GEN
Solar/Wind Harmer
0.696
270258AD1-119 GEN
Solar/Wind Harmer
1.704
247604X1-042
Adder
0.253
24441205WTRV SLR C
Solar/Wind Harmer
0.08
270588AE1-091_GEN
Solar/Wind Harmer
6.441
958091AF2-103 GEN
Solar/Wind Harmer
0.093
270491AE1-102 GEN2
Solar/Wind Harmer
0.745
945111AF1-176 GEN
Solar/Wind Harmer
3.128
24642205MAYFLWER
Adder
0.342
270191TR4_S_V150
Solar/Wind Harmer
1.604
270247TR4_N_V136
Solar/Wind Harmer
0.455
247643Z2-116 C
Solar/Wind Harmer
0.037
970031AG2-029 GEN
Solar/Wind Harmer
15.944
959331AF2-224 GEN
Solar/Wind Harmer
5.181
965021AG1-366 GEN
Solar/Wind Harmer
1.205
270485AE1-090_GEN
Solar/Wind Harmer
0.31
270043AE2-236 GEN
Solar/Wind Harmer
2.698
970349AG2-230 GEN
Solar/Wind Harmer
7.33
23867002DVBSG1
50/50
14.11
972211AH1-690 GEN
50/50
287.754
23888502TROY G1
50/50
1.796
23888602TROY G2
50/50
1.796
970817AG2-515 GEN
Solar/Wind Harmer
15.035
945411AF1-206 GEN
Solar/Wind Harmer
7.914
945641AF1-229 GEN
Solar/Wind Harmer
3.393
270499AE1-146 GEN
Solar/Wind Harmer
2.151
971549AH1-272 GEN
Solar/Wind Harmer
12.855
270297AD1-101 GEN
Solar/Wind Harmer
1.842
247607V1-011 GEN
Solar/Wind Harmer
2.271
944161AF1-084 GEN
Solar/Wind Harmer
1.267
957201AF2-014 GEN
Solar/Wind Harmer
2.6
270435AC2-044 GEN
Solar/Wind Harmer
1.147
966831AG1-554 GEN
Solar/Wind Harmer
0.66
971989AH1-539 GEN
Solar/Wind Harmer
7.141
965041AG1-368 GEN
Solar/Wind Harmer
5.38
965051AG1-369 GEN
Solar/Wind Harmer
2.669
971771AH1-392 GEN
Solar/Wind Harmer
4.715
270302AB2-170 GEN
Solar/Wind Harmer
4.281
270317AD1-130_GEN
Solar/Wind Harmer
1.641
971769AH1-391 GEN
Solar/Wind Harmer
5.107
960681AF2-359 GEN
Solar/Wind Harmer
1.855
971567AH1-282 GEN
Solar/Wind Harmer
7.347
971347AH1-153 GEN
Solar/Wind Harmer
7.33
963791AG1-232 GEN
Solar/Wind Harmer
6.473
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
2.103
270071AF1-092 GEN
Solar/Wind Harmer
6.837
274814UNIV PK N;0U
Adder
2.277
274807UNIV PK N;3U
Adder
2.272
274805UNIV PK N;1U
Adder
2.262
274811UNIV PK N;7U
Adder
2.257
958391AF2-133 GEN
Solar/Wind Harmer
4.087
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.452
960591AF2-350 GEN
Solar/Wind Harmer
4.435
274775LINCOLN ;6U
Adder
2.748
274776LINCOLN ;7U
Adder
2.748
274777LINCOLN ;8U
Adder
2.748
972227AH1-698 GEN1
Adder
1.153
274687WILL CNTY;4U
Adder
12.315
274687WILL CNTY;4U
Adder
12.315
274675JOLIET 29;7U
Adder
13.494
274675JOLIET 29;7U
Adder
13.012
274731ELWOOD EC;2P
Adder
7.217
274733ELWOOD EC;3P
Adder
7.217
274735ELWOOD EC;4P
Adder
7.217
274728ELWOOD EC;5P
Adder
7.217
970833AG2-524 GEN
Solar/Wind Harmer
3.814
970833AG2-524 GEN
Solar/Wind Harmer
1.774
274746AC1-111 G10
Adder
2.426
274744AC1-111 GEN8
Adder
2.426
241886AC2-103 GEN2
Solar/Wind Helper
9.126
241982AE2-343 S C
Solar/Wind Helper
0.114
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.24
241997AF1-093 GEN
Solar/Wind Helper
0.126
203804AE2-113_GEN
Solar/Wind Helper
0.838
270024AE2-089 GEN
Solar/Wind Harmer
0.078
270489AE1-102 GEN1
Solar/Wind Harmer
0.745
965421AG1-410 GEN
Solar/Wind Harmer
17.04
270449AD2-020 GEN
Solar/Wind Harmer
1.585
943021AE2-325 GEN
Solar/Wind Harmer
2.06
945111AF1-176 GEN
Solar/Wind Harmer
9.87
270505AE1-170 C O1
Solar/Wind Harmer
8.291
24695305TIMB G C
Solar/Wind Harmer
3.042
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
1.797
270246TR4_N_V150
Solar/Wind Harmer
0.455
270063AE2-323 C
Solar/Wind Harmer
1.174
965011AG1-365 GEN
Solar/Wind Harmer
5.181
270462AD2-086
Solar/Wind Harmer
3.561
270223U2-072_GEN1
Solar/Wind Harmer
0.937
270578AF1-285 GEN2
Solar/Wind Harmer
0.573
270391AF1-285 GEN3
Solar/Wind Harmer
0.573
970373AG2-245 GEN
Solar/Wind Harmer
9.916
270055AF2-134 C O1
Solar/Wind Harmer
1.402
274751CRETE EC ;1U
Adder
2.23
274754CRETE EC ;4U
Adder
2.23
958381AF2-132 GEN
Solar/Wind Harmer
4.125
964861AG1-349 GEN
Solar/Wind Harmer
3.567
971917AH1-482 GEN
Solar/Wind Harmer
4.117
274723RIVER EC ;12
Adder
8.113
274812UNIV PK N;8U
Adder
2.257
276164X3-005 C
Solar/Wind Harmer
0.315
274801UNIV PARK;4U
Adder
2.59
276776AD2-060 GEN
Solar/Wind Harmer
0.188
940581AE2-045 GEN
Solar/Wind Harmer
4.522
971605AH1-302 GEN
Solar/Wind Harmer
3.867
972207SS24-0001
Solar/Wind Harmer
9.772
274773LINCOLN ;4U
Adder
2.748
274774LINCOLN ;5U
Adder
2.748
274676JOLIET 29;8U
Adder
13.494
941551AE2-152 GEN
Solar/Wind Harmer
1.993
274732ELWOOD EC;7P
Adder
7.217
274674JOLIET 9 ;6U
Adder
6.759
970245AG2-165 GEN
Solar/Wind Harmer
7.813
274871GR RIDGE ;2U
Solar/Wind Harmer
3.357
274745AC1-111 GEN9
Adder
2.426
276691AA1-018 GEN1
Solar/Wind Harmer
0.202
274682WAUKEGAN ;7U
Adder
7.748
274828WAUKEGAN ;BP
Adder
4.757
241885AC2-103 GEN1
Solar/Wind Helper
9.126
961971AG1-040 GEN
Solar/Wind Helper
0.324
203835AF1-098 GEN
Solar/Wind Helper
1.276
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.764
254303AC2-168 GEN
Solar/Wind Helper
0.074
24190002OREGON_ST1
50/50
3.59
24189802OREGON_CT1
50/50
2.723
23888802TROY G4
50/50
1.796
241996AE2-282_GEN
Solar/Wind Harmer
2.119
971677AH1-339 GEN
Solar/Wind Harmer
6.113
270007AE1-245 C
Solar/Wind Harmer
3.406
246938BC-WTG3
Solar/Wind Harmer
2.282
246937BC-WTG2
Solar/Wind Harmer
2.243
942801AE2-298 GEN
Solar/Wind Harmer
0.863
961051AF2-396 GEN
Solar/Wind Harmer
8.904
961051AF2-396 GEN
Solar/Wind Harmer
4.142
960981AF2-389 GEN
Solar/Wind Harmer
0.833
957891AF2-083 GEN
Solar/Wind Harmer
1.858
247620Y3-023
Adder
0.248
270216AD2-079_GEN
Solar/Wind Harmer
0.322
970611AG2-400 GEN
Solar/Wind Harmer
5.181
270526AF1-158 GEN
Solar/Wind Harmer
2.332
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.139
965791AG1-447 GEN
Solar/Wind Harmer
3.141
270224U2-072_GEN2
Solar/Wind Harmer
0.937
270227U2-072_GEN3
Solar/Wind Harmer
0.937
270228U2-072_GEN4
Solar/Wind Harmer
0.937
270231U2-072_GEN5
Solar/Wind Harmer
0.937
274808UNIV PK N;4U
Adder
2.247
274803UNIV PARK;6U
Adder
2.599
274888KELLY CRK;1U
Solar/Wind Harmer
2.618
274887GEN-1.85
Solar/Wind Harmer
2.364
276843GEN-1.7
Solar/Wind Harmer
0.254
958011AF2-095 GEN
Solar/Wind Harmer
6.387
274770LINCOLN ;1U
Adder
2.748
274771LINCOLN ;2U
Adder
2.748
972259AH1-714 GEN
Adder
8.397
942221AE2-234 GEN
Solar/Wind Harmer
0.322
274674JOLIET 9 ;6U
Adder
6.759
970321AG2-212 GEN
Solar/Wind Harmer
7.813
274847GR RIDGE ;BU
Solar/Wind Harmer
2.208
958481AF2-142 GEN
Solar/Wind Harmer
6.507
274861TOP CROP ;1U
Solar/Wind Harmer
2.629
274862TOP CROP ;2U
Solar/Wind Harmer
2.195
274696ROCKY RD ;4P
Adder
4.912
274695ROCKY RD ;2P
Adder
4.798
274693ROCKY RD ;1P
Adder
4.751
274697ROCKY RD ;3P
Adder
1.303
274683WAUKEGAN ;8U
Adder
9.076
274683WAUKEGAN ;8U
Adder
7.65
203947AF1-006 C
Solar/Wind Helper
0.369
203980AG1-197 GEN
Solar/Wind Helper
0.241
203979AG1-198 GEN
Solar/Wind Helper
0.188
241801AE1-079 GEN
Solar/Wind Helper
0.128
241967AE2-285_GEN
Solar/Wind Helper
0.329
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.317
942871AE2-306 GEN
Solar/Wind Harmer
0.43
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
2.103
972231SS25-0005
Solar/Wind Harmer
4.331
972181SS23-001
Solar/Wind Harmer
2.707
274752CRETE EC ;2U
Adder
2.23
274753CRETE EC ;3U
Adder
2.23
964401AG1-302 GEN
Solar/Wind Harmer
4.125
274724RIVER EC ;11
Adder
8.016
959141AF2-205 GEN
Solar/Wind Harmer
2.704
274802UNIV PARK;5U
Adder
2.599
274826FISK ;BP
Adder
4.871
274800UNIV PARK;3U
Adder
2.59
972038AH1-567 GEN2
Adder
0.162
276772AC2-154 GEN
Solar/Wind Harmer
1.237
276806AD2-047 C O1
Solar/Wind Harmer
4.745
970941AG2-585 GEN
Solar/Wind Harmer
5.544
274772LINCOLN ;3U
Adder
2.748
972228AH1-698 GEN2
Adder
1.638
274676JOLIET 29;8U
Adder
13.012
276897AD1-100 C
Solar/Wind Harmer
12.75
939351AE1-166 GEN
Solar/Wind Harmer
2.605
276893AG1-478 C
Solar/Wind Harmer
0.183
274729ELWOOD EC;1P
Adder
7.217
274730ELWOOD EC;6P
Adder
7.217
274734ELWOOD EC;8P
Adder
7.217
274736ELWOOD EC;9P
Adder
7.217
970707AG2-453 GEN
Solar/Wind Harmer
12.291
970513AG2-328 GEN
Solar/Wind Harmer
7.813
970517AG2-330 GEN
Solar/Wind Harmer
7.086
943121AE2-341 GEN
Solar/Wind Harmer
6.509
943591AF1-030 GEN
Solar/Wind Harmer
4.339
276694AA1-018 GEN2
Solar/Wind Harmer
2.738
274682WAUKEGAN ;7U
Adder
7.748
962511AG1-100 GEN
Solar/Wind Helper
0.331
203830AF1-094 GEN
Solar/Wind Helper
0.313
959441AF2-235 GEN
Solar/Wind Helper
0.142
254305AE2-115 C
Solar/Wind Helper
0.109
971617AH1-308 GEN
Solar/Wind Harmer
0.096
991182J1586 G
External Queue
24.65229034423828
990527J1329
External Queue
1.8002409934997559
990142J1224
External Queue
13.159761428833008
991177J1571 G
External Queue
15.044508934020996
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.603
MECLTFEXP_MEC->PJM
CLTF
6.264
SIGELTFEXP_SIGE->PJM
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
4.792
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
TVALTFEXP_TVA->PJM
CLTF
2.173
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.291
NYPJM->LTFIMP_NY
CLTF
1.957
LGEELTFEXP_LGEE->PJM
CLTF
1.943
WECLTFEXP_WEC->PJM
CLTF
1.608
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-3_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.55 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2494.57
MW Contribution:16.05
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.599
23888702TROY G3
50/50
1.766
972253AH1-711 GEN
50/50
53.942
23856402BAYSG1
50/50
1.288
23920202STRYCT
50/50
1.908
241858AF1-205_GEN
Solar/Wind Harmer
5.509
241808AF1-120 C
Solar/Wind Harmer
1.205
241840AF1-064_GEN
Solar/Wind Harmer
1.394
972301AH1-735 GEN
Adder
6.613
23906402RICHG1
Adder
1.323
23906502RICHG2&3
Adder
1.32
270361_3
Solar/Wind Harmer
8.519
960841AF2-375 GEN
Solar/Wind Harmer
3.762
241807AE2-176_GEN
Solar/Wind Harmer
2.793
247522W1-056 GEN
Solar/Wind Harmer
1.578
970515AG2-329 GEN
Solar/Wind Harmer
10.167
944231AF1-091 GEN
Solar/Wind Harmer
2.462
246936BC-WTG1
Solar/Wind Harmer
2.279
270489AE1-102 GEN1
Solar/Wind Harmer
0.757
965421AG1-410 GEN
Solar/Wind Harmer
17.306
270449AD2-020 GEN
Solar/Wind Harmer
1.589
943021AE2-325 GEN
Solar/Wind Harmer
2.064
270428AC2-015 C
Solar/Wind Harmer
3.1
24695305TIMB G C
Solar/Wind Harmer
3.1
945111AF1-176 GEN
Solar/Wind Harmer
9.898
270505AE1-170 C O1
Solar/Wind Harmer
8.313
247521TR3_G114
Solar/Wind Harmer
1.829
270246TR4_N_V150
Solar/Wind Harmer
0.463
24639705ELKHART HY
Adder
0.083
270063AE2-323 C
Solar/Wind Harmer
1.182
965011AG1-365 GEN
Solar/Wind Harmer
5.243
270462AD2-086
Solar/Wind Harmer
3.638
270223U2-072_GEN1
Solar/Wind Harmer
0.958
270578AF1-285 GEN2
Solar/Wind Harmer
0.586
270391AF1-285 GEN3
Solar/Wind Harmer
0.586
970373AG2-245 GEN
Solar/Wind Harmer
9.966
270055AF2-134 C O1
Solar/Wind Harmer
1.409
274751CRETE EC ;1U
Adder
2.243
274754CRETE EC ;4U
Adder
2.243
958381AF2-132 GEN
Solar/Wind Harmer
4.148
964861AG1-349 GEN
Solar/Wind Harmer
3.588
971917AH1-482 GEN
Solar/Wind Harmer
4.14
274723RIVER EC ;12
Adder
8.158
274812UNIV PK N;8U
Adder
2.27
276164X3-005 C
Solar/Wind Harmer
0.317
274801UNIV PARK;4U
Adder
2.605
940581AE2-045 GEN
Solar/Wind Harmer
4.55
276776AD2-060 GEN
Solar/Wind Harmer
0.189
971605AH1-302 GEN
Solar/Wind Harmer
3.891
972207SS24-0001
Solar/Wind Harmer
9.829
274773LINCOLN ;4U
Adder
2.764
274774LINCOLN ;5U
Adder
2.764
274676JOLIET 29;8U
Adder
13.573
941551AE2-152 GEN
Solar/Wind Harmer
2.004
274732ELWOOD EC;7P
Adder
7.259
274674JOLIET 9 ;6U
Adder
6.799
970245AG2-165 GEN
Solar/Wind Harmer
7.863
274871GR RIDGE ;2U
Solar/Wind Harmer
3.377
970905AG2-564 GEN
Solar/Wind Harmer
2.194
274745AC1-111 GEN9
Adder
2.441
274682WAUKEGAN ;7U
Adder
7.794
274828WAUKEGAN ;BP
Adder
4.786
241885AC2-103 GEN1
Solar/Wind Helper
9.447
961971AG1-040 GEN
Solar/Wind Helper
0.332
203835AF1-098 GEN
Solar/Wind Helper
1.307
203860AG1-193 C
Solar/Wind Helper
0.148
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
276691AA1-018 GEN1
Solar/Wind Harmer
0.047
23867002DVBSG1
50/50
13.074
972211AH1-690 GEN
50/50
280.319
23888502TROY G1
50/50
1.766
23888602TROY G2
50/50
1.766
970817AG2-515 GEN
Solar/Wind Harmer
14.976
945411AF1-206 GEN
Solar/Wind Harmer
8.075
945641AF1-229 GEN
Solar/Wind Harmer
3.442
270499AE1-146 GEN
Solar/Wind Harmer
2.365
971549AH1-272 GEN
Solar/Wind Harmer
12.831
270297AD1-101 GEN
Solar/Wind Harmer
1.906
966831AG1-554 GEN
Solar/Wind Harmer
0.708
971989AH1-539 GEN
Solar/Wind Harmer
7.656
247607V1-011 GEN
Solar/Wind Harmer
2.323
957201AF2-014 GEN
Solar/Wind Harmer
2.642
270435AC2-044 GEN
Solar/Wind Harmer
1.165
944161AF1-084 GEN
Solar/Wind Harmer
1.269
965041AG1-368 GEN
Solar/Wind Harmer
5.468
965051AG1-369 GEN
Solar/Wind Harmer
2.716
971771AH1-392 GEN
Solar/Wind Harmer
4.733
270302AB2-170 GEN
Solar/Wind Harmer
4.373
270317AD1-130_GEN
Solar/Wind Harmer
1.676
971769AH1-391 GEN
Solar/Wind Harmer
5.127
971567AH1-282 GEN
Solar/Wind Harmer
7.606
960681AF2-359 GEN
Solar/Wind Harmer
1.863
971347AH1-153 GEN
Solar/Wind Harmer
7.365
963791AG1-232 GEN
Solar/Wind Harmer
6.558
270578AF1-285 GEN2
Solar/Wind Harmer
0.225
270536AF1-215 GEN2
Solar/Wind Harmer
2.114
270071AF1-092 GEN
Solar/Wind Harmer
6.904
958391AF2-133 GEN
Solar/Wind Harmer
4.11
274814UNIV PK N;0U
Adder
2.289
274807UNIV PK N;3U
Adder
2.285
274805UNIV PK N;1U
Adder
2.275
274811UNIV PK N;7U
Adder
2.27
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.472
960591AF2-350 GEN
Solar/Wind Harmer
4.461
274775LINCOLN ;6U
Adder
2.764
274776LINCOLN ;7U
Adder
2.764
274777LINCOLN ;8U
Adder
2.764
972227AH1-698 GEN1
Adder
1.16
274687WILL CNTY;4U
Adder
12.387
274687WILL CNTY;4U
Adder
12.387
274675JOLIET 29;7U
Adder
13.573
274675JOLIET 29;7U
Adder
13.089
274731ELWOOD EC;2P
Adder
7.259
274733ELWOOD EC;3P
Adder
7.259
274735ELWOOD EC;4P
Adder
7.259
274728ELWOOD EC;5P
Adder
7.259
270024AE2-089 GEN
Solar/Wind Harmer
2.063
970833AG2-524 GEN
Solar/Wind Harmer
3.836
970833AG2-524 GEN
Solar/Wind Harmer
1.784
274746AC1-111 G10
Adder
2.441
274744AC1-111 GEN8
Adder
2.441
241886AC2-103 GEN2
Solar/Wind Helper
9.447
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.246
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.858
23929302BS-PKR
50/50
2.267
241832AE2-181_GEN
Solar/Wind Harmer
1.96
958321AF2-126 GEN
Solar/Wind Harmer
1.494
23906502RICHG2&3
Adder
1.32
270575GUS2 35KV
Solar/Wind Harmer
10.036
270541AE2-072 C
Solar/Wind Harmer
4.33
970217AG2-149 GEN
Solar/Wind Harmer
22.419
270044AE2-322 C
Solar/Wind Harmer
0.854
270404AC1-167 GEN
Solar/Wind Harmer
0.711
270258AD1-119 GEN
Solar/Wind Harmer
1.74
270588AE1-091_GEN
Solar/Wind Harmer
6.813
247604X1-042
Adder
0.253
24441205WTRV SLR C
Solar/Wind Harmer
0.08
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270491AE1-102 GEN2
Solar/Wind Harmer
0.757
945111AF1-176 GEN
Solar/Wind Harmer
3.137
270191TR4_S_V150
Solar/Wind Harmer
1.632
270247TR4_N_V136
Solar/Wind Harmer
0.463
24642205MAYFLWER
Adder
0.343
970031AG2-029 GEN
Solar/Wind Harmer
16.05
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.243
965021AG1-366 GEN
Solar/Wind Harmer
1.219
270485AE1-090_GEN
Solar/Wind Harmer
0.316
270043AE2-236 GEN
Solar/Wind Harmer
2.723
970349AG2-230 GEN
Solar/Wind Harmer
7.365
942871AE2-306 GEN
Solar/Wind Harmer
0.439
270391AF1-285 GEN3
Solar/Wind Harmer
0.225
270377AD1-106 GEN
Solar/Wind Harmer
2.883
270535AF1-215 GEN1
Solar/Wind Harmer
2.114
972231SS25-0005
Solar/Wind Harmer
4.354
972181SS23-001
Solar/Wind Harmer
2.721
274752CRETE EC ;2U
Adder
2.243
274753CRETE EC ;3U
Adder
2.243
964401AG1-302 GEN
Solar/Wind Harmer
4.148
274724RIVER EC ;11
Adder
8.061
959141AF2-205 GEN
Solar/Wind Harmer
2.72
274802UNIV PARK;5U
Adder
2.613
274826FISK ;BP
Adder
4.899
274800UNIV PARK;3U
Adder
2.605
972038AH1-567 GEN2
Adder
0.163
276772AC2-154 GEN
Solar/Wind Harmer
1.244
276806AD2-047 C O1
Solar/Wind Harmer
4.772
970941AG2-585 GEN
Solar/Wind Harmer
5.576
274772LINCOLN ;3U
Adder
2.764
972228AH1-698 GEN2
Adder
1.647
274676JOLIET 29;8U
Adder
13.089
276897AD1-100 C
Solar/Wind Harmer
12.825
939351AE1-166 GEN
Solar/Wind Harmer
2.621
276893AG1-478 C
Solar/Wind Harmer
0.185
274729ELWOOD EC;1P
Adder
7.259
274730ELWOOD EC;6P
Adder
7.259
274734ELWOOD EC;8P
Adder
7.259
274736ELWOOD EC;9P
Adder
7.259
970707AG2-453 GEN
Solar/Wind Harmer
12.364
970513AG2-328 GEN
Solar/Wind Harmer
7.863
970517AG2-330 GEN
Solar/Wind Harmer
7.132
971617AH1-308 GEN
Solar/Wind Harmer
2.555
943121AE2-341 GEN
Solar/Wind Harmer
6.548
943591AF1-030 GEN
Solar/Wind Harmer
4.365
274682WAUKEGAN ;7U
Adder
7.794
962511AG1-100 GEN
Solar/Wind Helper
0.339
203830AF1-094 GEN
Solar/Wind Helper
0.321
959441AF2-235 GEN
Solar/Wind Helper
0.146
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.639
276694AA1-018 GEN2
Solar/Wind Harmer
0.632
24190002OREGON_ST1
50/50
3.497
24189802OREGON_CT1
50/50
2.653
23888802TROY G4
50/50
1.766
241996AE2-282_GEN
Solar/Wind Harmer
2.162
971677AH1-339 GEN
Solar/Wind Harmer
6.682
270007AE1-245 C
Solar/Wind Harmer
3.485
942801AE2-298 GEN
Solar/Wind Harmer
0.882
246938BC-WTG3
Solar/Wind Harmer
2.318
246937BC-WTG2
Solar/Wind Harmer
2.279
961051AF2-396 GEN
Solar/Wind Harmer
8.926
961051AF2-396 GEN
Solar/Wind Harmer
4.152
960981AF2-389 GEN
Solar/Wind Harmer
0.835
957891AF2-083 GEN
Solar/Wind Harmer
1.863
247620Y3-023
Adder
0.25
270216AD2-079_GEN
Solar/Wind Harmer
0.324
970611AG2-400 GEN
Solar/Wind Harmer
5.243
270526AF1-158 GEN
Solar/Wind Harmer
2.341
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.166
965791AG1-447 GEN
Solar/Wind Harmer
3.155
270224U2-072_GEN2
Solar/Wind Harmer
0.958
270227U2-072_GEN3
Solar/Wind Harmer
0.958
270228U2-072_GEN4
Solar/Wind Harmer
0.958
270231U2-072_GEN5
Solar/Wind Harmer
0.958
971231AH1-075 GEN
Solar/Wind Harmer
0.374
274808UNIV PK N;4U
Adder
2.26
274803UNIV PARK;6U
Adder
2.613
274888KELLY CRK;1U
Solar/Wind Harmer
2.634
274887GEN-1.85
Solar/Wind Harmer
2.378
276843GEN-1.7
Solar/Wind Harmer
0.256
958011AF2-095 GEN
Solar/Wind Harmer
6.424
274770LINCOLN ;1U
Adder
2.764
274771LINCOLN ;2U
Adder
2.764
942221AE2-234 GEN
Solar/Wind Harmer
0.326
972259AH1-714 GEN
Adder
8.447
274674JOLIET 9 ;6U
Adder
6.799
970321AG2-212 GEN
Solar/Wind Harmer
7.863
274847GR RIDGE ;BU
Solar/Wind Harmer
2.221
274696ROCKY RD ;4P
Adder
4.941
274695ROCKY RD ;2P
Adder
4.827
274693ROCKY RD ;1P
Adder
4.78
274697ROCKY RD ;3P
Adder
1.311
274683WAUKEGAN ;8U
Adder
9.13
274683WAUKEGAN ;8U
Adder
7.697
203947AF1-006 C
Solar/Wind Helper
0.378
203980AG1-197 GEN
Solar/Wind Helper
0.247
203979AG1-198 GEN
Solar/Wind Helper
0.193
241967AE2-285_GEN
Solar/Wind Helper
0.336
241801AE1-079 GEN
Solar/Wind Helper
0.131
241985AE1-237 GEN
Solar/Wind Helper
0.13
962101AG1-054 GEN
Solar/Wind Helper
0.324
946381AF1-302 GEN
Solar/Wind Helper
0.104
238217AF1-153 C O1
Solar/Wind Helper
0.11
991182J1586 G
External Queue
24.279396057128906
990527J1329
External Queue
1.7751743793487549
990142J1224
External Queue
12.976524353027344
991177J1571 G
External Queue
14.956707954406738
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.607
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.701
MECLTFEXP_MEC->PJM
CLTF
6.308
SIGELTFEXP_SIGE->PJM
CLTF
0.164
LAGNLTFEXP_LAGN->PJM
CLTF
4.838
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.167
TVALTFEXP_TVA->PJM
CLTF
2.196
CPLELTFEXP_CPLE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.653
NYPJM->LTFIMP_NY
CLTF
2
LGEELTFEXP_LGEE->PJM
CLTF
1.969
WECLTFEXP_WEC->PJM
CLTF
1.618
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.156

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-810_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-810_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.64 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2249.01
MW Contribution:2.41
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.668
23888702TROY G3
50/50
1.796
972253AH1-711 GEN
50/50
54.848
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.869
241858AF1-205_GEN
Solar/Wind Harmer
3.76
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.461
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.289
270361_3
Solar/Wind Harmer
4.199
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.4
247522W1-056 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.197
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.52
965421AG1-410 GEN
Solar/Wind Harmer
11.889
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.06
945111AF1-176 GEN
Solar/Wind Harmer
6.886
270505AE1-170 C O1
Solar/Wind Harmer
4.049
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
0.136
270246TR4_N_V150
Solar/Wind Harmer
0.024
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.614
270462AD2-086
Solar/Wind Harmer
0.007
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.918
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
3.76
274754CRETE EC ;4U
Adder
3.76
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.117
274723RIVER EC ;12
Adder
8.113
274812UNIV PK N;8U
Adder
2.257
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.59
276776AD2-060 GEN
Solar/Wind Harmer
0.323
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.867
274773LINCOLN ;4U
Adder
3.741
274774LINCOLN ;5U
Adder
3.741
274676JOLIET 29;8U
Adder
13.494
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.217
274674JOLIET 9 ;6U
Adder
6.759
970245AG2-165 GEN
Solar/Wind Harmer
1.323
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.426
276691AA1-018 GEN1
Solar/Wind Harmer
0.367
274682WAUKEGAN ;7U
Adder
7.748
274828WAUKEGAN ;BP
Adder
4.757
241885AC2-103 GEN1
Solar/Wind Helper
9.126
961971AG1-040 GEN
Solar/Wind Helper
0.324
203835AF1-098 GEN
Solar/Wind Helper
1.276
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.764
254303AC2-168 GEN
Solar/Wind Helper
0.074
24190002OREGON_ST1
50/50
3.59
24189802OREGON_CT1
50/50
2.723
23888802TROY G4
50/50
1.796
241996AE2-282_GEN
Solar/Wind Harmer
0.005
971677AH1-339 GEN
Solar/Wind Harmer
0.601
970621AG2-405 GEN
Solar/Wind Harmer
0.845
970623AG2-406 GEN
Solar/Wind Harmer
0.78
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.162
961051AF2-396 GEN
Solar/Wind Harmer
7.827
961051AF2-396 GEN
Solar/Wind Harmer
5.218
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.248
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.614
970627AG2-408 GEN
Solar/Wind Harmer
1.084
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.283
965791AG1-447 GEN
Solar/Wind Harmer
3.141
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.247
274803UNIV PARK;6U
Adder
2.599
274888KELLY CRK;1U
Solar/Wind Harmer
0.182
274887GEN-1.85
Solar/Wind Harmer
0.081
276843GEN-1.7
Solar/Wind Harmer
0.1
958011AF2-095 GEN
Solar/Wind Harmer
4.456
274770LINCOLN ;1U
Adder
3.741
274771LINCOLN ;2U
Adder
3.741
972259AH1-714 GEN
Adder
8.397
942221AE2-234 GEN
Solar/Wind Harmer
0.015
274674JOLIET 9 ;6U
Adder
6.759
970321AG2-212 GEN
Solar/Wind Harmer
1.323
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.54
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.409
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.562
274696ROCKY RD ;4P
Adder
4.912
274695ROCKY RD ;2P
Adder
4.798
274693ROCKY RD ;1P
Adder
4.751
274697ROCKY RD ;3P
Adder
1.303
274683WAUKEGAN ;8U
Adder
9.076
274683WAUKEGAN ;8U
Adder
7.65
203947AF1-006 C
Solar/Wind Helper
0.369
203980AG1-197 GEN
Solar/Wind Helper
0.241
203979AG1-198 GEN
Solar/Wind Helper
0.188
241801AE1-079 GEN
Solar/Wind Helper
0.128
241967AE2-285_GEN
Solar/Wind Helper
0.329
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.317
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.111
23906502RICHG2&3
Adder
1.289
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.199
970217AG2-149 GEN
Solar/Wind Harmer
4.133
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.253
24441205WTRV SLR C
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
3.195
270491AE1-102 GEN2
Solar/Wind Harmer
0.52
945111AF1-176 GEN
Solar/Wind Harmer
3.128
24642205MAYFLWER
Adder
0.342
270191TR4_S_V150
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.024
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.41
959331AF2-224 GEN
Solar/Wind Harmer
2.53
965021AG1-366 GEN
Solar/Wind Harmer
1.205
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.196
970349AG2-230 GEN
Solar/Wind Harmer
5.114
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.76
274753CRETE EC ;3U
Adder
3.76
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.016
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.599
274826FISK ;BP
Adder
4.871
274800UNIV PARK;3U
Adder
2.59
972038AH1-567 GEN2
Adder
0.162
276806AD2-047 C O1
Solar/Wind Harmer
1.753
970941AG2-585 GEN
Solar/Wind Harmer
3.868
274772LINCOLN ;3U
Adder
3.741
972228AH1-698 GEN2
Adder
1.638
274676JOLIET 29;8U
Adder
13.012
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.217
274730ELWOOD EC;6P
Adder
7.217
274734ELWOOD EC;8P
Adder
7.217
274736ELWOOD EC;9P
Adder
7.217
970707AG2-453 GEN
Solar/Wind Harmer
10.005
970513AG2-328 GEN
Solar/Wind Harmer
1.323
970517AG2-330 GEN
Solar/Wind Harmer
7.937
943121AE2-341 GEN
Solar/Wind Harmer
5.076
943591AF1-030 GEN
Solar/Wind Harmer
3.375
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.521
274682WAUKEGAN ;7U
Adder
7.748
962511AG1-100 GEN
Solar/Wind Helper
0.331
203830AF1-094 GEN
Solar/Wind Helper
0.313
959441AF2-235 GEN
Solar/Wind Helper
0.142
254305AE2-115 C
Solar/Wind Helper
0.109
23867002DVBSG1
50/50
14.11
972211AH1-690 GEN
50/50
287.754
23888502TROY G1
50/50
1.796
23888602TROY G2
50/50
1.796
970817AG2-515 GEN
Solar/Wind Harmer
10.489
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.027
971549AH1-272 GEN
Solar/Wind Harmer
10.011
270297AD1-101 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.507
971619AH1-309 GEN
Solar/Wind Harmer
1.735
971989AH1-539 GEN
Solar/Wind Harmer
1.661
965041AG1-368 GEN
Solar/Wind Harmer
3.753
965051AG1-369 GEN
Solar/Wind Harmer
1.862
971771AH1-392 GEN
Solar/Wind Harmer
3.655
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.502
971769AH1-391 GEN
Solar/Wind Harmer
3.979
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971567AH1-282 GEN
Solar/Wind Harmer
5.126
971347AH1-153 GEN
Solar/Wind Harmer
5.114
963791AG1-232 GEN
Solar/Wind Harmer
4.516
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.095
274814UNIV PK N;0U
Adder
2.277
274807UNIV PK N;3U
Adder
2.272
274805UNIV PK N;1U
Adder
2.262
274811UNIV PK N;7U
Adder
2.257
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.452
960591AF2-350 GEN
Solar/Wind Harmer
3.094
971611AH1-305 GEN
Solar/Wind Harmer
1.842
274775LINCOLN ;6U
Adder
3.741
274776LINCOLN ;7U
Adder
3.741
274777LINCOLN ;8U
Adder
3.741
972227AH1-698 GEN1
Adder
1.153
274687WILL CNTY;4U
Adder
12.315
274687WILL CNTY;4U
Adder
12.315
274675JOLIET 29;7U
Adder
13.494
274675JOLIET 29;7U
Adder
13.012
274731ELWOOD EC;2P
Adder
7.217
274733ELWOOD EC;3P
Adder
7.217
274735ELWOOD EC;4P
Adder
7.217
274728ELWOOD EC;5P
Adder
7.217
970833AG2-524 GEN
Solar/Wind Harmer
3.353
970833AG2-524 GEN
Solar/Wind Harmer
2.235
274746AC1-111 G10
Adder
2.426
274744AC1-111 GEN8
Adder
2.426
270024AE2-089 GEN
Solar/Wind Harmer
0.003
241886AC2-103 GEN2
Solar/Wind Helper
9.126
241982AE2-343 S C
Solar/Wind Helper
0.114
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.24
241997AF1-093 GEN
Solar/Wind Helper
0.126
203804AE2-113_GEN
Solar/Wind Helper
0.838
991182J1586 G
External Queue
24.65229034423828
990527J1329
External Queue
1.8002409934997559
990142J1224
External Queue
13.159761428833008
991177J1571 G
External Queue
15.044508934020996
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.603
MECLTFEXP_MEC->PJM
CLTF
6.264
SIGELTFEXP_SIGE->PJM
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
4.792
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
TVALTFEXP_TVA->PJM
CLTF
2.173
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.291
NYPJM->LTFIMP_NY
CLTF
1.957
LGEELTFEXP_LGEE->PJM
CLTF
1.943
WECLTFEXP_WEC->PJM
CLTF
1.608
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.94 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2122.34
MW Contribution:2.39
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.254
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.148
23906502RICHG2&3
Adder
1.306
270575GUS2 35KV
Solar/Wind Harmer
4.656
270541AE2-072 C
Solar/Wind Harmer
0.008
970217AG2-149 GEN
Solar/Wind Harmer
4.19
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270588AE1-091_GEN
Solar/Wind Harmer
3.358
247604X1-042
Adder
0.249
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.522
945111AF1-176 GEN
Solar/Wind Harmer
3.093
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.024
24642205MAYFLWER
Adder
0.338
970031AG2-029 GEN
Solar/Wind Harmer
2.393
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.528
965021AG1-366 GEN
Solar/Wind Harmer
1.204
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.187
970349AG2-230 GEN
Solar/Wind Harmer
5.067
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
270377AD1-106 GEN
Solar/Wind Harmer
1.238
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.728
274753CRETE EC ;3U
Adder
3.728
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
7.95
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.577
274826FISK ;BP
Adder
4.831
274800UNIV PARK;3U
Adder
2.569
972038AH1-567 GEN2
Adder
0.161
276806AD2-047 C O1
Solar/Wind Harmer
1.739
970941AG2-585 GEN
Solar/Wind Harmer
3.837
274772LINCOLN ;3U
Adder
3.711
972228AH1-698 GEN2
Adder
1.625
274676JOLIET 29;8U
Adder
12.909
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.12
970707AG2-453 GEN
Solar/Wind Harmer
9.926
274729ELWOOD EC;1P
Adder
7.16
274730ELWOOD EC;6P
Adder
7.16
274734ELWOOD EC;8P
Adder
7.16
274736ELWOOD EC;9P
Adder
7.16
970513AG2-328 GEN
Solar/Wind Harmer
1.313
970517AG2-330 GEN
Solar/Wind Harmer
7.878
971617AH1-308 GEN
Solar/Wind Harmer
2.523
943121AE2-341 GEN
Solar/Wind Harmer
5.036
943591AF1-030 GEN
Solar/Wind Harmer
3.349
276694AA1-018 GEN2
Solar/Wind Harmer
0
962511AG1-100 GEN
Solar/Wind Helper
0.335
203830AF1-094 GEN
Solar/Wind Helper
0.317
959441AF2-235 GEN
Solar/Wind Helper
0.144
254305AE2-115 C
Solar/Wind Helper
0.11
20334926Z1-069 C
Solar/Wind Helper
0.632
24189902OREGON_CT2
50/50
2.551
23888702TROY G3
50/50
1.736
972253AH1-711 GEN
50/50
53.019
23856402BAYSG1
50/50
1.281
23920202STRYCT
50/50
1.886
241858AF1-205_GEN
Solar/Wind Harmer
3.799
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.539
23906402RICHG1
Adder
1.308
23906502RICHG2&3
Adder
1.306
270361_3
Solar/Wind Harmer
4.656
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
241807AE2-176_GEN
Solar/Wind Harmer
0.004
247522W1-056 GEN
Solar/Wind Harmer
0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.569
944231AF1-091 GEN
Solar/Wind Harmer
1.201
270428AC2-015 C
Solar/Wind Harmer
0.002
246936BC-WTG1
Solar/Wind Harmer
0.163
270489AE1-102 GEN1
Solar/Wind Harmer
0.522
965421AG1-410 GEN
Solar/Wind Harmer
11.925
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.035
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.808
270505AE1-170 C O1
Solar/Wind Harmer
4.002
247521TR3_G114
Solar/Wind Harmer
0.137
270246TR4_N_V150
Solar/Wind Harmer
0.024
24639705ELKHART HY
Adder
0.082
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.611
270462AD2-086
Solar/Wind Harmer
0.008
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.857
270055AF2-134 C O1
Solar/Wind Harmer
0.002
970905AG2-564 GEN
Solar/Wind Harmer
1.733
274751CRETE EC ;1U
Adder
3.728
274754CRETE EC ;4U
Adder
3.728
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.083
274723RIVER EC ;12
Adder
8.046
274812UNIV PK N;8U
Adder
2.238
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.569
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.837
276776AD2-060 GEN
Solar/Wind Harmer
0.32
274773LINCOLN ;4U
Adder
3.711
274774LINCOLN ;5U
Adder
3.711
274676JOLIET 29;8U
Adder
13.387
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.16
274674JOLIET 9 ;6U
Adder
6.706
970245AG2-165 GEN
Solar/Wind Harmer
1.313
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.408
276691AA1-018 GEN1
Solar/Wind Harmer
0.364
241885AC2-103 GEN1
Solar/Wind Helper
9.503
961971AG1-040 GEN
Solar/Wind Helper
0.328
203835AF1-098 GEN
Solar/Wind Helper
1.293
203860AG1-193 C
Solar/Wind Helper
0.146
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.074
24190002OREGON_ST1
50/50
3.432
24189802OREGON_CT1
50/50
2.603
23888802TROY G4
50/50
1.736
241996AE2-282_GEN
Solar/Wind Harmer
0.005
971677AH1-339 GEN
Solar/Wind Harmer
0.655
970621AG2-405 GEN
Solar/Wind Harmer
0.866
970623AG2-406 GEN
Solar/Wind Harmer
0.788
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.163
961051AF2-396 GEN
Solar/Wind Harmer
7.735
961051AF2-396 GEN
Solar/Wind Harmer
5.157
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.246
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.611
970627AG2-408 GEN
Solar/Wind Harmer
1.083
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.242
965791AG1-447 GEN
Solar/Wind Harmer
3.111
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.374
274808UNIV PK N;4U
Adder
2.229
274803UNIV PARK;6U
Adder
2.577
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
274887GEN-1.85
Solar/Wind Harmer
0.081
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.42
274770LINCOLN ;1U
Adder
3.711
274771LINCOLN ;2U
Adder
3.711
942221AE2-234 GEN
Solar/Wind Harmer
0.015
972259AH1-714 GEN
Adder
8.331
274674JOLIET 9 ;6U
Adder
6.706
970321AG2-212 GEN
Solar/Wind Harmer
1.313
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.505
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.406
203947AF1-006 C
Solar/Wind Helper
0.374
203980AG1-197 GEN
Solar/Wind Helper
0.244
203979AG1-198 GEN
Solar/Wind Helper
0.19
241967AE2-285_GEN
Solar/Wind Helper
0.332
241801AE1-079 GEN
Solar/Wind Helper
0.129
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.321
946381AF1-302 GEN
Solar/Wind Helper
0.103
23867002DVBSG1
50/50
12.729
972211AH1-690 GEN
50/50
275.118
23888502TROY G1
50/50
1.736
23888602TROY G2
50/50
1.736
970817AG2-515 GEN
Solar/Wind Harmer
10.289
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
9.844
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
1.772
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.508
971619AH1-309 GEN
Solar/Wind Harmer
1.715
965041AG1-368 GEN
Solar/Wind Harmer
3.769
965051AG1-369 GEN
Solar/Wind Harmer
1.872
971771AH1-392 GEN
Solar/Wind Harmer
3.617
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.506
24191202EL_AA1-006
Adder
0.112
971769AH1-391 GEN
Solar/Wind Harmer
3.938
971567AH1-282 GEN
Solar/Wind Harmer
5.256
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.067
963791AG1-232 GEN
Solar/Wind Harmer
4.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.074
274814UNIV PK N;0U
Adder
2.258
274807UNIV PK N;3U
Adder
2.253
274805UNIV PK N;1U
Adder
2.243
274811UNIV PK N;7U
Adder
2.238
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.424
971611AH1-305 GEN
Solar/Wind Harmer
1.828
960591AF2-350 GEN
Solar/Wind Harmer
3.069
274775LINCOLN ;6U
Adder
3.711
274776LINCOLN ;7U
Adder
3.711
274777LINCOLN ;8U
Adder
3.711
972227AH1-698 GEN1
Adder
1.144
274687WILL CNTY;4U
Adder
12.217
274687WILL CNTY;4U
Adder
12.217
274675JOLIET 29;7U
Adder
13.387
274675JOLIET 29;7U
Adder
12.909
274731ELWOOD EC;2P
Adder
7.16
274733ELWOOD EC;3P
Adder
7.16
274735ELWOOD EC;4P
Adder
7.16
274728ELWOOD EC;5P
Adder
7.16
270024AE2-089 GEN
Solar/Wind Harmer
0.003
970833AG2-524 GEN
Solar/Wind Harmer
3.326
970833AG2-524 GEN
Solar/Wind Harmer
2.217
274746AC1-111 G10
Adder
2.408
274744AC1-111 GEN8
Adder
2.408
241886AC2-103 GEN2
Solar/Wind Helper
9.503
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.11
203846AF2-130 C
Solar/Wind Helper
0.243
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.848
991182J1586 G
External Queue
23.868927001953125
990527J1329
External Queue
1.745489239692688
990142J1224
External Queue
12.759525299072266
991177J1571 G
External Queue
14.724894523620605
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.231
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.589
MECLTFEXP_MEC->PJM
CLTF
6.223
SIGELTFEXP_SIGE->PJM
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
4.775
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.139
TVALTFEXP_TVA->PJM
CLTF
2.168
CPLELTFEXP_CPLE->PJM
CLTF
0.326
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.144
NYPJM->LTFIMP_NY
CLTF
1.977
LGEELTFEXP_LGEE->PJM
CLTF
1.944
WECLTFEXP_WEC->PJM
CLTF
1.596
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-005_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-005_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.75 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2755.89
MW Contribution:16.89
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
12.801
972211AH1-690 GEN
50/50
288.187
23888502TROY G1
50/50
1.831
23888602TROY G2
50/50
1.831
23860102FRMENG 1
50/50
1.729
23860202FRMENG 2
50/50
1.729
24191202EL_AA1-006
50/50
0.333
241886AC2-103 GEN2
Solar/Wind Harmer
12.859
970817AG2-515 GEN
Solar/Wind Harmer
15.71
945411AF1-206 GEN
Solar/Wind Harmer
8.65
270499AE1-146 GEN
Solar/Wind Harmer
2.686
945641AF1-229 GEN
Solar/Wind Harmer
3.662
270297AD1-101 GEN
Solar/Wind Harmer
2.06
971549AH1-272 GEN
Solar/Wind Harmer
13.433
966831AG1-554 GEN
Solar/Wind Harmer
0.787
24189902OREGON_CT2
50/50
2.672
23856402BAYSG1
50/50
1.43
23888702TROY G3
50/50
1.831
972253AH1-711 GEN
50/50
55.942
23860302FRMENG 3
50/50
3.53
23920202STRYCT
50/50
2.045
241885AC2-103 GEN1
Solar/Wind Harmer
12.859
241807AE2-176_GEN
Solar/Wind Harmer
7.277
241858AF1-205_GEN
Solar/Wind Harmer
5.91
241808AF1-120 C
Solar/Wind Harmer
1.291
241840AF1-064_GEN
Solar/Wind Harmer
1.52
972301AH1-735 GEN
Adder
7.097
23906402RICHG1
Adder
1.419
23906502RICHG2&3
Adder
1.417
270361_3
Solar/Wind Harmer
9.742
960841AF2-375 GEN
Solar/Wind Harmer
4.291
247522W1-056 GEN
Solar/Wind Harmer
1.77
270428AC2-015 C
Solar/Wind Harmer
4.143
970515AG2-329 GEN
Solar/Wind Harmer
10.896
944231AF1-091 GEN
Solar/Wind Harmer
2.617
246936BC-WTG1
Solar/Wind Harmer
2.42
270489AE1-102 GEN1
Solar/Wind Harmer
0.804
965421AG1-410 GEN
Solar/Wind Harmer
18.372
24695305TIMB G C
Solar/Wind Harmer
3.301
270449AD2-020 GEN
Solar/Wind Harmer
1.666
943021AE2-325 GEN
Solar/Wind Harmer
2.165
970905AG2-564 GEN
Solar/Wind Harmer
2.943
945111AF1-176 GEN
Solar/Wind Harmer
10.388
270505AE1-170 C O1
Solar/Wind Harmer
8.723
247521TR3_G114
Solar/Wind Harmer
1.944
270246TR4_N_V150
Solar/Wind Harmer
0.492
24639705ELKHART HY
Adder
0.087
270063AE2-323 C
Solar/Wind Harmer
1.245
270462AD2-086
Solar/Wind Harmer
3.878
965011AG1-365 GEN
Solar/Wind Harmer
5.544
270223U2-072_GEN1
Solar/Wind Harmer
1.021
270578AF1-285 GEN2
Solar/Wind Harmer
0.624
270391AF1-285 GEN3
Solar/Wind Harmer
0.624
970373AG2-245 GEN
Solar/Wind Harmer
10.463
270055AF2-134 C O1
Solar/Wind Harmer
1.48
274751CRETE EC ;1U
Adder
2.355
274754CRETE EC ;4U
Adder
2.355
958381AF2-132 GEN
Solar/Wind Harmer
4.356
964861AG1-349 GEN
Solar/Wind Harmer
3.767
971917AH1-482 GEN
Solar/Wind Harmer
4.347
274723RIVER EC ;12
Adder
8.566
274812UNIV PK N;8U
Adder
2.383
276164X3-005 C
Solar/Wind Harmer
0.333
241847AF2-150_GEN
Solar/Wind Harmer
1.954
274801UNIV PARK;4U
Adder
2.735
940581AE2-045 GEN
Solar/Wind Harmer
4.778
971605AH1-302 GEN
Solar/Wind Harmer
4.086
276776AD2-060 GEN
Solar/Wind Harmer
0.198
972207SS24-0001
Solar/Wind Harmer
10.32
274773LINCOLN ;4U
Adder
2.903
274774LINCOLN ;5U
Adder
2.903
274676JOLIET 29;8U
Adder
14.25
941551AE2-152 GEN
Solar/Wind Harmer
2.104
274732ELWOOD EC;7P
Adder
7.621
274674JOLIET 9 ;6U
Adder
7.138
970245AG2-165 GEN
Solar/Wind Harmer
8.259
274871GR RIDGE ;2U
Solar/Wind Harmer
3.545
274745AC1-111 GEN9
Adder
2.563
274682WAUKEGAN ;7U
Adder
8.182
274828WAUKEGAN ;BP
Adder
5.024
274822ROCKFORD ;11
Adder
8.741
972235AH1-702 GEN1
Adder
1.121
274761LEE CO EC;2U
Adder
4.095
274766LEE CO EC;7U
Adder
4.047
961971AG1-040 GEN
Solar/Wind Helper
0.361
203835AF1-098 GEN
Solar/Wind Helper
1.422
203860AG1-193 C
Solar/Wind Helper
0.161
241966AE1-183 GEN
Solar/Wind Helper
0.14
254303AC2-168 GEN
Solar/Wind Helper
0.082
203954AE2-126 C
Solar/Wind Helper
0.235
24190002OREGON_ST1
50/50
3.596
24189802OREGON_CT1
50/50
2.727
23888802TROY G4
50/50
1.831
241996AE2-282_GEN
Solar/Wind Harmer
2.316
971677AH1-339 GEN
Solar/Wind Harmer
7.553
270007AE1-245 C
Solar/Wind Harmer
3.723
942801AE2-298 GEN
Solar/Wind Harmer
0.943
246938BC-WTG3
Solar/Wind Harmer
2.462
246937BC-WTG2
Solar/Wind Harmer
2.42
961051AF2-396 GEN
Solar/Wind Harmer
9.365
961051AF2-396 GEN
Solar/Wind Harmer
4.356
960981AF2-389 GEN
Solar/Wind Harmer
0.877
957891AF2-083 GEN
Solar/Wind Harmer
1.955
247620Y3-023
Adder
0.262
270216AD2-079_GEN
Solar/Wind Harmer
0.34
970611AG2-400 GEN
Solar/Wind Harmer
5.544
270526AF1-158 GEN
Solar/Wind Harmer
2.458
24441505OLIV SLR
Solar/Wind Harmer
0.072
971231AH1-075 GEN
Solar/Wind Harmer
0.425
965681AG1-436 GEN
Solar/Wind Harmer
6.472
965791AG1-447 GEN
Solar/Wind Harmer
3.311
270224U2-072_GEN2
Solar/Wind Harmer
1.021
270227U2-072_GEN3
Solar/Wind Harmer
1.021
270228U2-072_GEN4
Solar/Wind Harmer
1.021
270231U2-072_GEN5
Solar/Wind Harmer
1.021
274808UNIV PK N;4U
Adder
2.372
274803UNIV PARK;6U
Adder
2.744
942221AE2-234 GEN
Solar/Wind Harmer
0.344
274888KELLY CRK;1U
Solar/Wind Harmer
2.765
274887GEN-1.85
Solar/Wind Harmer
2.496
276843GEN-1.7
Solar/Wind Harmer
0.269
958011AF2-095 GEN
Solar/Wind Harmer
6.744
274770LINCOLN ;1U
Adder
2.903
274771LINCOLN ;2U
Adder
2.903
972259AH1-714 GEN
Adder
8.868
274674JOLIET 9 ;6U
Adder
7.138
970321AG2-212 GEN
Solar/Wind Harmer
8.259
274847GR RIDGE ;BU
Solar/Wind Harmer
2.332
274696ROCKY RD ;4P
Adder
5.187
274695ROCKY RD ;2P
Adder
5.068
274693ROCKY RD ;1P
Adder
5.018
274697ROCKY RD ;3P
Adder
1.377
274683WAUKEGAN ;8U
Adder
9.585
274683WAUKEGAN ;8U
Adder
8.08
274764LEE CO EC;5U
Adder
4.104
274765LEE CO EC;6U
Adder
4.104
274762LEE CO EC;3U
Adder
4.095
274763LEE CO EC;4U
Adder
4.056
972267AH1-718 GEN
Adder
1.82
25326509SID D
Adder
0.57
203947AF1-006 C
Solar/Wind Helper
0.411
203980AG1-197 GEN
Solar/Wind Helper
0.269
203979AG1-198 GEN
Solar/Wind Helper
0.209
241967AE2-285_GEN
Solar/Wind Helper
0.365
241801AE1-079 GEN
Solar/Wind Helper
0.142
241985AE1-237 GEN
Solar/Wind Helper
0.142
962101AG1-054 GEN
Solar/Wind Helper
0.353
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.12
20398826ARMNA MT
Solar/Wind Helper
0.712
203853AF1-134 C O1
Solar/Wind Helper
0.222
971989AH1-539 GEN
Solar/Wind Harmer
8.505
247607V1-011 GEN
Solar/Wind Harmer
2.482
957201AF2-014 GEN
Solar/Wind Harmer
2.805
270435AC2-044 GEN
Solar/Wind Harmer
1.237
944161AF1-084 GEN
Solar/Wind Harmer
1.331
965041AG1-368 GEN
Solar/Wind Harmer
5.807
965051AG1-369 GEN
Solar/Wind Harmer
2.887
270302AB2-170 GEN
Solar/Wind Harmer
4.661
270317AD1-130_GEN
Solar/Wind Harmer
1.787
971771AH1-392 GEN
Solar/Wind Harmer
4.969
971567AH1-282 GEN
Solar/Wind Harmer
8.2
971769AH1-391 GEN
Solar/Wind Harmer
5.381
960681AF2-359 GEN
Solar/Wind Harmer
1.956
270578AF1-285 GEN2
Solar/Wind Harmer
0.24
971347AH1-153 GEN
Solar/Wind Harmer
7.734
963791AG1-232 GEN
Solar/Wind Harmer
6.936
270536AF1-215 GEN2
Solar/Wind Harmer
2.22
270071AF1-092 GEN
Solar/Wind Harmer
7.277
958391AF2-133 GEN
Solar/Wind Harmer
4.316
274814UNIV PK N;0U
Adder
2.404
274807UNIV PK N;3U
Adder
2.399
274805UNIV PK N;1U
Adder
2.388
274811UNIV PK N;7U
Adder
2.383
972037AH1-567 GEN1
Adder
0.086
274827FISK ;RP
Adder
3.645
960591AF2-350 GEN
Solar/Wind Harmer
4.683
274775LINCOLN ;6U
Adder
2.903
274776LINCOLN ;7U
Adder
2.903
274777LINCOLN ;8U
Adder
2.903
972227AH1-698 GEN1
Adder
1.218
274687WILL CNTY;4U
Adder
13.005
274687WILL CNTY;4U
Adder
13.005
270024AE2-089 GEN
Solar/Wind Harmer
2.18
274675JOLIET 29;7U
Adder
14.25
274675JOLIET 29;7U
Adder
13.741
274731ELWOOD EC;2P
Adder
7.621
274733ELWOOD EC;3P
Adder
7.621
274735ELWOOD EC;4P
Adder
7.621
274728ELWOOD EC;5P
Adder
7.621
970833AG2-524 GEN
Solar/Wind Harmer
4.028
970833AG2-524 GEN
Solar/Wind Harmer
1.873
274746AC1-111 G10
Adder
2.563
274744AC1-111 GEN8
Adder
2.563
24729505KEY G4
Adder
2.933
274823ROCKFORD ;21
Adder
8.678
241982AE2-343 S C
Solar/Wind Helper
0.127
254304AE2-114 C
Solar/Wind Helper
0.121
203846AF2-130 C
Solar/Wind Helper
0.267
241997AF1-093 GEN
Solar/Wind Helper
0.14
203804AE2-113_GEN
Solar/Wind Helper
0.935
203855AF2-088 C
Solar/Wind Helper
0.073
23929302BS-PKR
50/50
2.517
241832AE2-181_GEN
Solar/Wind Harmer
2.098
958321AF2-126 GEN
Solar/Wind Harmer
1.63
23906502RICHG2&3
Adder
1.417
270575GUS2 35KV
Solar/Wind Harmer
11.477
270541AE2-072 C
Solar/Wind Harmer
4.706
970217AG2-149 GEN
Solar/Wind Harmer
24.027
270044AE2-322 C
Solar/Wind Harmer
0.913
270404AC1-167 GEN
Solar/Wind Harmer
0.76
270588AE1-091_GEN
Solar/Wind Harmer
7.489
270258AD1-119 GEN
Solar/Wind Harmer
1.858
247604X1-042
Adder
0.265
958091AF2-103 GEN
Solar/Wind Harmer
0.101
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.804
945111AF1-176 GEN
Solar/Wind Harmer
3.292
270191TR4_S_V150
Solar/Wind Harmer
1.734
270247TR4_N_V136
Solar/Wind Harmer
0.492
24642205MAYFLWER
Adder
0.36
970031AG2-029 GEN
Solar/Wind Harmer
16.895
247643Z2-116 C
Solar/Wind Harmer
0.039
270485AE1-090_GEN
Solar/Wind Harmer
0.337
959331AF2-224 GEN
Solar/Wind Harmer
5.544
965021AG1-366 GEN
Solar/Wind Harmer
1.289
270377AD1-106 GEN
Solar/Wind Harmer
3.284
270043AE2-236 GEN
Solar/Wind Harmer
2.87
942871AE2-306 GEN
Solar/Wind Harmer
0.468
270391AF1-285 GEN3
Solar/Wind Harmer
0.24
970349AG2-230 GEN
Solar/Wind Harmer
7.734
270535AF1-215 GEN1
Solar/Wind Harmer
2.22
972231SS25-0005
Solar/Wind Harmer
4.572
972181SS23-001
Solar/Wind Harmer
2.857
274752CRETE EC ;2U
Adder
2.355
274753CRETE EC ;3U
Adder
2.355
964401AG1-302 GEN
Solar/Wind Harmer
4.356
274724RIVER EC ;11
Adder
8.463
959141AF2-205 GEN
Solar/Wind Harmer
2.857
274802UNIV PARK;5U
Adder
2.744
961961AG1-039 GEN
Solar/Wind Harmer
1.348
274826FISK ;BP
Adder
5.143
274800UNIV PARK;3U
Adder
2.735
972038AH1-567 GEN2
Adder
0.171
276772AC2-154 GEN
Solar/Wind Harmer
1.306
276806AD2-047 C O1
Solar/Wind Harmer
5.01
970941AG2-585 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
2.903
972228AH1-698 GEN2
Adder
1.73
274676JOLIET 29;8U
Adder
13.741
971617AH1-308 GEN
Solar/Wind Harmer
2.7
276897AD1-100 C
Solar/Wind Harmer
13.466
939351AE1-166 GEN
Solar/Wind Harmer
2.751
276893AG1-478 C
Solar/Wind Harmer
0.194
274729ELWOOD EC;1P
Adder
7.621
274730ELWOOD EC;6P
Adder
7.621
274734ELWOOD EC;8P
Adder
7.621
274736ELWOOD EC;9P
Adder
7.621
970707AG2-453 GEN
Solar/Wind Harmer
12.981
970513AG2-328 GEN
Solar/Wind Harmer
8.259
970517AG2-330 GEN
Solar/Wind Harmer
7.49
274682WAUKEGAN ;7U
Adder
8.182
972236AH1-702 GEN2
Adder
0.975
274760LEE CO EC;1U
Adder
4.095
274767LEE CO EC;8U
Adder
4.047
962511AG1-100 GEN
Solar/Wind Helper
0.369
203830AF1-094 GEN
Solar/Wind Helper
0.349
959441AF2-235 GEN
Solar/Wind Helper
0.159
254305AE2-115 C
Solar/Wind Helper
0.121
20334926Z1-069 C
Solar/Wind Helper
0.696
203854AF2-039 C
Solar/Wind Helper
0.151
203818AF1-086 GEN
Solar/Wind Helper
0.772
943121AE2-341 GEN
Solar/Wind Harmer
2.136
943591AF1-030 GEN
Solar/Wind Harmer
1.424
991182J1586 G
External Queue
25.292837142944336
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
991177J1571 G
External Queue
15.714932441711426
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.745
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.083
MECLTFEXP_MEC->PJM
CLTF
6.617
SIGELTFEXP_SIGE->PJM
CLTF
0.172
LAGNLTFEXP_LAGN->PJM
CLTF
5.047
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.15
TVALTFEXP_TVA->PJM
CLTF
2.288
CPLELTFEXP_CPLE->PJM
CLTF
0.293
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.459
NYPJM->LTFIMP_NY
CLTF
2.188
LGEELTFEXP_LGEE->PJM
CLTF
2.068
WECLTFEXP_WEC->PJM
CLTF
1.698
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.164

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-006_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.08 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2705.74
MW Contribution:17.12
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.686
23856402BAYSG1
50/50
1.441
23888702TROY G3
50/50
1.842
972253AH1-711 GEN
50/50
56.254
23860302FRMENG 3
50/50
3.59
23920202STRYCT
50/50
2.06
241885AC2-103 GEN1
Solar/Wind Harmer
12.88
241807AE2-176_GEN
Solar/Wind Harmer
7.419
241858AF1-205_GEN
Solar/Wind Harmer
5.953
241808AF1-120 C
Solar/Wind Harmer
1.301
241840AF1-064_GEN
Solar/Wind Harmer
1.533
972301AH1-735 GEN
Adder
7.158
23906402RICHG1
Adder
1.432
23906502RICHG2&3
Adder
1.43
270361_3
Solar/Wind Harmer
9.878
960841AF2-375 GEN
Solar/Wind Harmer
4.35
247522W1-056 GEN
Solar/Wind Harmer
1.802
270428AC2-015 C
Solar/Wind Harmer
4.301
970515AG2-329 GEN
Solar/Wind Harmer
11.13
944231AF1-091 GEN
Solar/Wind Harmer
2.648
246936BC-WTG1
Solar/Wind Harmer
2.454
270489AE1-102 GEN1
Solar/Wind Harmer
0.815
965421AG1-410 GEN
Solar/Wind Harmer
18.626
970905AG2-564 GEN
Solar/Wind Harmer
3.098
24695305TIMB G C
Solar/Wind Harmer
3.347
270449AD2-020 GEN
Solar/Wind Harmer
1.687
943021AE2-325 GEN
Solar/Wind Harmer
2.193
945111AF1-176 GEN
Solar/Wind Harmer
10.521
270505AE1-170 C O1
Solar/Wind Harmer
8.835
247521TR3_G114
Solar/Wind Harmer
1.972
270246TR4_N_V150
Solar/Wind Harmer
0.499
24639705ELKHART HY
Adder
0.088
270063AE2-323 C
Solar/Wind Harmer
1.262
270462AD2-086
Solar/Wind Harmer
3.938
965011AG1-365 GEN
Solar/Wind Harmer
5.623
270223U2-072_GEN1
Solar/Wind Harmer
1.038
270578AF1-285 GEN2
Solar/Wind Harmer
0.635
270391AF1-285 GEN3
Solar/Wind Harmer
0.635
23929302BS-PKR
50/50
2.537
241832AE2-181_GEN
Solar/Wind Harmer
2.114
958321AF2-126 GEN
Solar/Wind Harmer
1.643
23906502RICHG2&3
Adder
1.43
270575GUS2 35KV
Solar/Wind Harmer
11.637
270541AE2-072 C
Solar/Wind Harmer
4.757
970217AG2-149 GEN
Solar/Wind Harmer
24.543
270044AE2-322 C
Solar/Wind Harmer
0.925
270404AC1-167 GEN
Solar/Wind Harmer
0.77
270588AE1-091_GEN
Solar/Wind Harmer
7.618
270258AD1-119 GEN
Solar/Wind Harmer
1.882
247604X1-042
Adder
0.268
958091AF2-103 GEN
Solar/Wind Harmer
0.103
24441205WTRV SLR C
Solar/Wind Harmer
0.085
270491AE1-102 GEN2
Solar/Wind Harmer
0.815
945111AF1-176 GEN
Solar/Wind Harmer
3.334
270191TR4_S_V150
Solar/Wind Harmer
1.759
270247TR4_N_V136
Solar/Wind Harmer
0.499
24642205MAYFLWER
Adder
0.364
970031AG2-029 GEN
Solar/Wind Harmer
17.123
247643Z2-116 C
Solar/Wind Harmer
0.04
270485AE1-090_GEN
Solar/Wind Harmer
0.342
959331AF2-224 GEN
Solar/Wind Harmer
5.623
965021AG1-366 GEN
Solar/Wind Harmer
1.308
270377AD1-106 GEN
Solar/Wind Harmer
3.371
270043AE2-236 GEN
Solar/Wind Harmer
2.911
942871AE2-306 GEN
Solar/Wind Harmer
0.476
270391AF1-285 GEN3
Solar/Wind Harmer
0.244
970349AG2-230 GEN
Solar/Wind Harmer
7.843
270535AF1-215 GEN1
Solar/Wind Harmer
2.253
961961AG1-039 GEN
Solar/Wind Harmer
1.415
972231SS25-0005
Solar/Wind Harmer
4.639
972181SS23-001
Solar/Wind Harmer
2.9
274752CRETE EC ;2U
Adder
2.389
274753CRETE EC ;3U
Adder
2.389
964401AG1-302 GEN
Solar/Wind Harmer
4.421
274724RIVER EC ;11
Adder
8.59
959141AF2-205 GEN
Solar/Wind Harmer
2.9
274802UNIV PARK;5U
Adder
2.785
274826FISK ;BP
Adder
5.221
274800UNIV PARK;3U
Adder
2.776
972038AH1-567 GEN2
Adder
0.174
276772AC2-154 GEN
Solar/Wind Harmer
1.326
276806AD2-047 C O1
Solar/Wind Harmer
5.086
970941AG2-585 GEN
Solar/Wind Harmer
5.943
274772LINCOLN ;3U
Adder
2.947
972228AH1-698 GEN2
Adder
1.756
971617AH1-308 GEN
Solar/Wind Harmer
2.744
274676JOLIET 29;8U
Adder
13.951
276897AD1-100 C
Solar/Wind Harmer
13.671
939351AE1-166 GEN
Solar/Wind Harmer
2.793
276893AG1-478 C
Solar/Wind Harmer
0.197
970707AG2-453 GEN
Solar/Wind Harmer
13.179
274729ELWOOD EC;1P
Adder
7.738
274730ELWOOD EC;6P
Adder
7.738
274734ELWOOD EC;8P
Adder
7.738
274736ELWOOD EC;9P
Adder
7.738
970513AG2-328 GEN
Solar/Wind Harmer
8.386
970517AG2-330 GEN
Solar/Wind Harmer
7.606
274682WAUKEGAN ;7U
Adder
8.309
972236AH1-702 GEN2
Adder
0.99
274760LEE CO EC;1U
Adder
4.16
274767LEE CO EC;8U
Adder
4.111
962511AG1-100 GEN
Solar/Wind Helper
0.371
203830AF1-094 GEN
Solar/Wind Helper
0.351
959441AF2-235 GEN
Solar/Wind Helper
0.159
254305AE2-115 C
Solar/Wind Helper
0.121
20334926Z1-069 C
Solar/Wind Helper
0.698
203854AF2-039 C
Solar/Wind Helper
0.151
203818AF1-086 GEN
Solar/Wind Helper
0.773
24190002OREGON_ST1
50/50
3.613
24189802OREGON_CT1
50/50
2.741
23888802TROY G4
50/50
1.842
241996AE2-282_GEN
Solar/Wind Harmer
2.333
971677AH1-339 GEN
Solar/Wind Harmer
7.68
270007AE1-245 C
Solar/Wind Harmer
3.775
942801AE2-298 GEN
Solar/Wind Harmer
0.956
246938BC-WTG3
Solar/Wind Harmer
2.496
246937BC-WTG2
Solar/Wind Harmer
2.454
961051AF2-396 GEN
Solar/Wind Harmer
9.484
961051AF2-396 GEN
Solar/Wind Harmer
4.411
960981AF2-389 GEN
Solar/Wind Harmer
0.888
957891AF2-083 GEN
Solar/Wind Harmer
1.981
247620Y3-023
Adder
0.266
270216AD2-079_GEN
Solar/Wind Harmer
0.344
970611AG2-400 GEN
Solar/Wind Harmer
5.623
270526AF1-158 GEN
Solar/Wind Harmer
2.491
971231AH1-075 GEN
Solar/Wind Harmer
0.437
24441505OLIV SLR
Solar/Wind Harmer
0.073
965681AG1-436 GEN
Solar/Wind Harmer
6.563
965791AG1-447 GEN
Solar/Wind Harmer
3.358
270224U2-072_GEN2
Solar/Wind Harmer
1.038
270227U2-072_GEN3
Solar/Wind Harmer
1.038
270228U2-072_GEN4
Solar/Wind Harmer
1.038
270231U2-072_GEN5
Solar/Wind Harmer
1.038
274808UNIV PK N;4U
Adder
2.408
274803UNIV PARK;6U
Adder
2.785
942221AE2-234 GEN
Solar/Wind Harmer
0.349
274888KELLY CRK;1U
Solar/Wind Harmer
2.807
274887GEN-1.85
Solar/Wind Harmer
2.534
276843GEN-1.7
Solar/Wind Harmer
0.273
958011AF2-095 GEN
Solar/Wind Harmer
6.846
274770LINCOLN ;1U
Adder
2.947
274771LINCOLN ;2U
Adder
2.947
972259AH1-714 GEN
Adder
9.004
274674JOLIET 9 ;6U
Adder
7.247
970321AG2-212 GEN
Solar/Wind Harmer
8.386
274847GR RIDGE ;BU
Solar/Wind Harmer
2.368
274696ROCKY RD ;4P
Adder
5.267
274695ROCKY RD ;2P
Adder
5.146
274693ROCKY RD ;1P
Adder
5.095
274697ROCKY RD ;3P
Adder
1.398
274683WAUKEGAN ;8U
Adder
9.733
274683WAUKEGAN ;8U
Adder
8.205
274764LEE CO EC;5U
Adder
4.169
274765LEE CO EC;6U
Adder
4.169
274762LEE CO EC;3U
Adder
4.16
274763LEE CO EC;4U
Adder
4.12
972267AH1-718 GEN
Adder
1.849
25326509SID D
Adder
0.581
247621Y3-024
Adder
0.105
203947AF1-006 C
Solar/Wind Helper
0.413
203980AG1-197 GEN
Solar/Wind Helper
0.27
203979AG1-198 GEN
Solar/Wind Helper
0.21
241967AE2-285_GEN
Solar/Wind Helper
0.366
241801AE1-079 GEN
Solar/Wind Helper
0.143
241985AE1-237 GEN
Solar/Wind Helper
0.142
962101AG1-054 GEN
Solar/Wind Helper
0.354
946381AF1-302 GEN
Solar/Wind Helper
0.114
238217AF1-153 C O1
Solar/Wind Helper
0.12
20398826ARMNA MT
Solar/Wind Helper
0.713
203853AF1-134 C O1
Solar/Wind Helper
0.223
23867002DVBSG1
50/50
12.822
972211AH1-690 GEN
50/50
289.616
23888502TROY G1
50/50
1.842
23888602TROY G2
50/50
1.842
23860102FRMENG 1
50/50
1.758
23860202FRMENG 2
50/50
1.758
24191202EL_AA1-006
50/50
0.345
241886AC2-103 GEN2
Solar/Wind Harmer
12.88
970817AG2-515 GEN
Solar/Wind Harmer
15.806
945411AF1-206 GEN
Solar/Wind Harmer
8.713
270499AE1-146 GEN
Solar/Wind Harmer
2.723
945641AF1-229 GEN
Solar/Wind Harmer
3.712
270297AD1-101 GEN
Solar/Wind Harmer
2.086
971549AH1-272 GEN
Solar/Wind Harmer
13.576
966831AG1-554 GEN
Solar/Wind Harmer
0.802
971989AH1-539 GEN
Solar/Wind Harmer
8.669
247607V1-011 GEN
Solar/Wind Harmer
2.516
957201AF2-014 GEN
Solar/Wind Harmer
2.844
270435AC2-044 GEN
Solar/Wind Harmer
1.254
944161AF1-084 GEN
Solar/Wind Harmer
1.348
965041AG1-368 GEN
Solar/Wind Harmer
5.889
965051AG1-369 GEN
Solar/Wind Harmer
2.928
270302AB2-170 GEN
Solar/Wind Harmer
4.734
270317AD1-130_GEN
Solar/Wind Harmer
1.815
971567AH1-282 GEN
Solar/Wind Harmer
8.435
971771AH1-392 GEN
Solar/Wind Harmer
5.035
971769AH1-391 GEN
Solar/Wind Harmer
5.455
960681AF2-359 GEN
Solar/Wind Harmer
1.984
270578AF1-285 GEN2
Solar/Wind Harmer
0.244
971347AH1-153 GEN
Solar/Wind Harmer
7.843
963791AG1-232 GEN
Solar/Wind Harmer
7.04
270536AF1-215 GEN2
Solar/Wind Harmer
2.253
270071AF1-092 GEN
Solar/Wind Harmer
7.388
958391AF2-133 GEN
Solar/Wind Harmer
4.381
274814UNIV PK N;0U
Adder
2.44
274807UNIV PK N;3U
Adder
2.434
274805UNIV PK N;1U
Adder
2.424
274811UNIV PK N;7U
Adder
2.419
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.7
960591AF2-350 GEN
Solar/Wind Harmer
4.754
274775LINCOLN ;6U
Adder
2.947
274776LINCOLN ;7U
Adder
2.947
274777LINCOLN ;8U
Adder
2.947
972227AH1-698 GEN1
Adder
1.236
274687WILL CNTY;4U
Adder
13.203
274687WILL CNTY;4U
Adder
13.203
270024AE2-089 GEN
Solar/Wind Harmer
2.215
274675JOLIET 29;7U
Adder
14.468
274675JOLIET 29;7U
Adder
13.951
274731ELWOOD EC;2P
Adder
7.738
274733ELWOOD EC;3P
Adder
7.738
274735ELWOOD EC;4P
Adder
7.738
274728ELWOOD EC;5P
Adder
7.738
970833AG2-524 GEN
Solar/Wind Harmer
4.089
970833AG2-524 GEN
Solar/Wind Harmer
1.902
274746AC1-111 G10
Adder
2.602
274744AC1-111 GEN8
Adder
2.602
24729505KEY G4
Adder
2.98
274823ROCKFORD ;21
Adder
8.814
241982AE2-343 S C
Solar/Wind Helper
0.127
254304AE2-114 C
Solar/Wind Helper
0.121
203846AF2-130 C
Solar/Wind Helper
0.268
241997AF1-093 GEN
Solar/Wind Helper
0.141
203804AE2-113_GEN
Solar/Wind Helper
0.937
203855AF2-088 C
Solar/Wind Helper
0.073
970373AG2-245 GEN
Solar/Wind Harmer
10.614
270055AF2-134 C O1
Solar/Wind Harmer
1.502
241847AF2-150_GEN
Solar/Wind Harmer
2.052
274751CRETE EC ;1U
Adder
2.389
274754CRETE EC ;4U
Adder
2.389
958381AF2-132 GEN
Solar/Wind Harmer
4.421
964861AG1-349 GEN
Solar/Wind Harmer
3.823
971917AH1-482 GEN
Solar/Wind Harmer
4.412
274723RIVER EC ;12
Adder
8.693
274812UNIV PK N;8U
Adder
2.419
276164X3-005 C
Solar/Wind Harmer
0.338
274801UNIV PARK;4U
Adder
2.776
940581AE2-045 GEN
Solar/Wind Harmer
4.851
971605AH1-302 GEN
Solar/Wind Harmer
4.148
276776AD2-060 GEN
Solar/Wind Harmer
0.201
972207SS24-0001
Solar/Wind Harmer
10.477
274773LINCOLN ;4U
Adder
2.947
274774LINCOLN ;5U
Adder
2.947
274676JOLIET 29;8U
Adder
14.467
941551AE2-152 GEN
Solar/Wind Harmer
2.137
274732ELWOOD EC;7P
Adder
7.738
274674JOLIET 9 ;6U
Adder
7.247
970245AG2-165 GEN
Solar/Wind Harmer
8.386
274871GR RIDGE ;2U
Solar/Wind Harmer
3.6
274745AC1-111 GEN9
Adder
2.602
274682WAUKEGAN ;7U
Adder
8.309
274828WAUKEGAN ;BP
Adder
5.102
274822ROCKFORD ;11
Adder
8.879
972235AH1-702 GEN1
Adder
1.138
274761LEE CO EC;2U
Adder
4.16
274766LEE CO EC;7U
Adder
4.111
961971AG1-040 GEN
Solar/Wind Helper
0.363
203835AF1-098 GEN
Solar/Wind Helper
1.429
203860AG1-193 C
Solar/Wind Helper
0.162
241966AE1-183 GEN
Solar/Wind Helper
0.141
254303AC2-168 GEN
Solar/Wind Helper
0.082
203954AE2-126 C
Solar/Wind Helper
0.236
943121AE2-341 GEN
Solar/Wind Harmer
2.169
943591AF1-030 GEN
Solar/Wind Harmer
1.446
991182J1586 G
External Queue
25.351587295532227
990527J1329
External Queue
1.8554641008377075
990142J1224
External Queue
13.56344223022461
991177J1571 G
External Queue
15.754436492919922
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.822
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.312
MECLTFEXP_MEC->PJM
CLTF
6.73
SIGELTFEXP_SIGE->PJM
CLTF
0.176
LAGNLTFEXP_LAGN->PJM
CLTF
5.168
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.294
TVALTFEXP_TVA->PJM
CLTF
2.348
CPLELTFEXP_CPLE->PJM
CLTF
0.34
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.311
NYPJM->LTFIMP_NY
CLTF
2.183
LGEELTFEXP_LGEE->PJM
CLTF
2.114
WECLTFEXP_WEC->PJM
CLTF
1.725
AG2-052LTFEXP_AG2-052->PJM
LTF
0.111
AH1-155LTFEXP_AH1-155->PJM
LTF
0.167

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.21 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2670.76
MW Contribution:17.04
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.605
24189802OREGON_CT1
50/50
2.735
24189902OREGON_CT2
50/50
2.68
23856402BAYSG1
50/50
1.434
23888702TROY G3
50/50
1.837
972253AH1-711 GEN
50/50
56.101
23860302FRMENG 3
50/50
3.54
23920202STRYCT
50/50
2.052
241807AE2-176_GEN
Solar/Wind Harmer
7.294
241858AF1-205_GEN
Solar/Wind Harmer
5.929
241808AF1-120 C
Solar/Wind Harmer
1.295
241840AF1-064_GEN
Solar/Wind Harmer
1.525
972301AH1-735 GEN
Adder
7.125
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270361_3
Solar/Wind Harmer
9.783
960841AF2-375 GEN
Solar/Wind Harmer
4.309
247522W1-056 GEN
Solar/Wind Harmer
1.78
270428AC2-015 C
Solar/Wind Harmer
4.168
970515AG2-329 GEN
Solar/Wind Harmer
10.964
944231AF1-091 GEN
Solar/Wind Harmer
2.634
246936BC-WTG1
Solar/Wind Harmer
2.439
270489AE1-102 GEN1
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.512
24695305TIMB G C
Solar/Wind Harmer
3.326
270449AD2-020 GEN
Solar/Wind Harmer
1.68
943021AE2-325 GEN
Solar/Wind Harmer
2.182
970905AG2-564 GEN
Solar/Wind Harmer
2.966
945111AF1-176 GEN
Solar/Wind Harmer
10.472
270505AE1-170 C O1
Solar/Wind Harmer
8.793
247521TR3_G114
Solar/Wind Harmer
1.96
270246TR4_N_V150
Solar/Wind Harmer
0.496
24639705ELKHART HY
Adder
0.088
270063AE2-323 C
Solar/Wind Harmer
1.255
270462AD2-086
Solar/Wind Harmer
3.91
965011AG1-365 GEN
Solar/Wind Harmer
5.591
270223U2-072_GEN1
Solar/Wind Harmer
1.03
270578AF1-285 GEN2
Solar/Wind Harmer
0.63
270391AF1-285 GEN3
Solar/Wind Harmer
0.63
970373AG2-245 GEN
Solar/Wind Harmer
10.561
270055AF2-134 C O1
Solar/Wind Harmer
1.494
274751CRETE EC ;1U
Adder
2.377
274754CRETE EC ;4U
Adder
2.377
958381AF2-132 GEN
Solar/Wind Harmer
4.398
964861AG1-349 GEN
Solar/Wind Harmer
3.804
971917AH1-482 GEN
Solar/Wind Harmer
4.39
274723RIVER EC ;12
Adder
8.649
274812UNIV PK N;8U
Adder
2.406
276164X3-005 C
Solar/Wind Harmer
0.336
241847AF2-150_GEN
Solar/Wind Harmer
1.974
274801UNIV PARK;4U
Adder
2.762
940581AE2-045 GEN
Solar/Wind Harmer
4.826
971605AH1-302 GEN
Solar/Wind Harmer
4.126
276776AD2-060 GEN
Solar/Wind Harmer
0.2
972207SS24-0001
Solar/Wind Harmer
10.423
274773LINCOLN ;4U
Adder
2.932
274774LINCOLN ;5U
Adder
2.932
274676JOLIET 29;8U
Adder
14.394
941551AE2-152 GEN
Solar/Wind Harmer
2.126
274732ELWOOD EC;7P
Adder
7.698
274674JOLIET 9 ;6U
Adder
7.21
970245AG2-165 GEN
Solar/Wind Harmer
8.342
274871GR RIDGE ;2U
Solar/Wind Harmer
3.581
274745AC1-111 GEN9
Adder
2.589
274682WAUKEGAN ;7U
Adder
8.266
274828WAUKEGAN ;BP
Adder
5.076
274822ROCKFORD ;11
Adder
8.833
972235AH1-702 GEN1
Adder
1.133
274761LEE CO EC;2U
Adder
4.138
274766LEE CO EC;7U
Adder
4.089
241885AC2-103 GEN1
Solar/Wind Helper
4.614
961971AG1-040 GEN
Solar/Wind Helper
0.358
203835AF1-098 GEN
Solar/Wind Helper
1.412
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.233
23888802TROY G4
50/50
1.837
241996AE2-282_GEN
Solar/Wind Harmer
2.323
971677AH1-339 GEN
Solar/Wind Harmer
7.59
270007AE1-245 C
Solar/Wind Harmer
3.751
942801AE2-298 GEN
Solar/Wind Harmer
0.95
246938BC-WTG3
Solar/Wind Harmer
2.481
246937BC-WTG2
Solar/Wind Harmer
2.439
961051AF2-396 GEN
Solar/Wind Harmer
9.439
961051AF2-396 GEN
Solar/Wind Harmer
4.39
960981AF2-389 GEN
Solar/Wind Harmer
0.884
957891AF2-083 GEN
Solar/Wind Harmer
1.971
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.343
970611AG2-400 GEN
Solar/Wind Harmer
5.591
270526AF1-158 GEN
Solar/Wind Harmer
2.479
24441505OLIV SLR
Solar/Wind Harmer
0.073
971231AH1-075 GEN
Solar/Wind Harmer
0.429
965681AG1-436 GEN
Solar/Wind Harmer
6.531
965791AG1-447 GEN
Solar/Wind Harmer
3.341
270224U2-072_GEN2
Solar/Wind Harmer
1.03
270227U2-072_GEN3
Solar/Wind Harmer
1.03
270228U2-072_GEN4
Solar/Wind Harmer
1.03
270231U2-072_GEN5
Solar/Wind Harmer
1.03
274808UNIV PK N;4U
Adder
2.396
274803UNIV PARK;6U
Adder
2.771
942221AE2-234 GEN
Solar/Wind Harmer
0.347
274888KELLY CRK;1U
Solar/Wind Harmer
2.793
274887GEN-1.85
Solar/Wind Harmer
2.521
276843GEN-1.7
Solar/Wind Harmer
0.271
958011AF2-095 GEN
Solar/Wind Harmer
6.812
274770LINCOLN ;1U
Adder
2.932
274771LINCOLN ;2U
Adder
2.932
972259AH1-714 GEN
Adder
8.958
274674JOLIET 9 ;6U
Adder
7.21
970321AG2-212 GEN
Solar/Wind Harmer
8.342
274847GR RIDGE ;BU
Solar/Wind Harmer
2.356
274696ROCKY RD ;4P
Adder
5.24
274695ROCKY RD ;2P
Adder
5.12
274693ROCKY RD ;1P
Adder
5.069
274697ROCKY RD ;3P
Adder
1.391
274683WAUKEGAN ;8U
Adder
9.683
274683WAUKEGAN ;8U
Adder
8.163
274764LEE CO EC;5U
Adder
4.148
274765LEE CO EC;6U
Adder
4.148
274762LEE CO EC;3U
Adder
4.138
274763LEE CO EC;4U
Adder
4.099
972267AH1-718 GEN
Adder
1.84
25326509SID D
Adder
0.576
247621Y3-024
Adder
0.105
203947AF1-006 C
Solar/Wind Helper
0.408
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.362
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.14
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.112
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.704
23867002DVBSG1
50/50
12.828
972211AH1-690 GEN
50/50
288.97
23888502TROY G1
50/50
1.837
23888602TROY G2
50/50
1.837
23860102FRMENG 1
50/50
1.734
23860202FRMENG 2
50/50
1.734
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
15.756
945411AF1-206 GEN
Solar/Wind Harmer
8.678
270499AE1-146 GEN
Solar/Wind Harmer
2.698
945641AF1-229 GEN
Solar/Wind Harmer
3.679
270297AD1-101 GEN
Solar/Wind Harmer
2.073
971549AH1-272 GEN
Solar/Wind Harmer
13.52
966831AG1-554 GEN
Solar/Wind Harmer
0.792
971989AH1-539 GEN
Solar/Wind Harmer
8.566
247607V1-011 GEN
Solar/Wind Harmer
2.5
957201AF2-014 GEN
Solar/Wind Harmer
2.826
270435AC2-044 GEN
Solar/Wind Harmer
1.246
944161AF1-084 GEN
Solar/Wind Harmer
1.342
965041AG1-368 GEN
Solar/Wind Harmer
5.854
965051AG1-369 GEN
Solar/Wind Harmer
2.91
270302AB2-170 GEN
Solar/Wind Harmer
4.7
270317AD1-130_GEN
Solar/Wind Harmer
1.802
971771AH1-392 GEN
Solar/Wind Harmer
5.011
971567AH1-282 GEN
Solar/Wind Harmer
8.27
971769AH1-391 GEN
Solar/Wind Harmer
5.428
960681AF2-359 GEN
Solar/Wind Harmer
1.974
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
7.804
963791AG1-232 GEN
Solar/Wind Harmer
7
270536AF1-215 GEN2
Solar/Wind Harmer
2.241
270071AF1-092 GEN
Solar/Wind Harmer
7.347
958391AF2-133 GEN
Solar/Wind Harmer
4.359
23929302BS-PKR
50/50
2.524
241832AE2-181_GEN
Solar/Wind Harmer
2.105
958321AF2-126 GEN
Solar/Wind Harmer
1.635
23906502RICHG2&3
Adder
1.423
270575GUS2 35KV
Solar/Wind Harmer
11.525
270541AE2-072 C
Solar/Wind Harmer
4.728
970217AG2-149 GEN
Solar/Wind Harmer
24.176
270044AE2-322 C
Solar/Wind Harmer
0.919
270404AC1-167 GEN
Solar/Wind Harmer
0.766
270588AE1-091_GEN
Solar/Wind Harmer
7.54
270258AD1-119 GEN
Solar/Wind Harmer
1.871
247604X1-042
Adder
0.267
958091AF2-103 GEN
Solar/Wind Harmer
0.102
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.81
945111AF1-176 GEN
Solar/Wind Harmer
3.319
270191TR4_S_V150
Solar/Wind Harmer
1.748
270247TR4_N_V136
Solar/Wind Harmer
0.496
24642205MAYFLWER
Adder
0.363
970031AG2-029 GEN
Solar/Wind Harmer
17.036
247643Z2-116 C
Solar/Wind Harmer
0.039
270485AE1-090_GEN
Solar/Wind Harmer
0.34
959331AF2-224 GEN
Solar/Wind Harmer
5.591
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270377AD1-106 GEN
Solar/Wind Harmer
3.313
270043AE2-236 GEN
Solar/Wind Harmer
2.896
942871AE2-306 GEN
Solar/Wind Harmer
0.472
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
7.804
270535AF1-215 GEN1
Solar/Wind Harmer
2.241
972231SS25-0005
Solar/Wind Harmer
4.616
972181SS23-001
Solar/Wind Harmer
2.885
274752CRETE EC ;2U
Adder
2.377
274753CRETE EC ;3U
Adder
2.377
964401AG1-302 GEN
Solar/Wind Harmer
4.398
274724RIVER EC ;11
Adder
8.546
959141AF2-205 GEN
Solar/Wind Harmer
2.885
274802UNIV PARK;5U
Adder
2.771
961961AG1-039 GEN
Solar/Wind Harmer
1.361
274826FISK ;BP
Adder
5.194
274800UNIV PARK;3U
Adder
2.762
972038AH1-567 GEN2
Adder
0.173
276772AC2-154 GEN
Solar/Wind Harmer
1.319
276806AD2-047 C O1
Solar/Wind Harmer
5.06
970941AG2-585 GEN
Solar/Wind Harmer
5.913
274772LINCOLN ;3U
Adder
2.932
972228AH1-698 GEN2
Adder
1.747
274676JOLIET 29;8U
Adder
13.879
971617AH1-308 GEN
Solar/Wind Harmer
2.727
276897AD1-100 C
Solar/Wind Harmer
13.601
939351AE1-166 GEN
Solar/Wind Harmer
2.779
276893AG1-478 C
Solar/Wind Harmer
0.196
970707AG2-453 GEN
Solar/Wind Harmer
13.112
274729ELWOOD EC;1P
Adder
7.698
274730ELWOOD EC;6P
Adder
7.698
274734ELWOOD EC;8P
Adder
7.698
274736ELWOOD EC;9P
Adder
7.698
970513AG2-328 GEN
Solar/Wind Harmer
8.342
970517AG2-330 GEN
Solar/Wind Harmer
7.566
274682WAUKEGAN ;7U
Adder
8.266
972236AH1-702 GEN2
Adder
0.985
274760LEE CO EC;1U
Adder
4.138
274767LEE CO EC;8U
Adder
4.089
962511AG1-100 GEN
Solar/Wind Helper
0.366
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.157
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.689
203854AF2-039 C
Solar/Wind Helper
0.149
943121AE2-341 GEN
Solar/Wind Harmer
5.427
943591AF1-030 GEN
Solar/Wind Harmer
3.618
274814UNIV PK N;0U
Adder
2.427
274807UNIV PK N;3U
Adder
2.422
274805UNIV PK N;1U
Adder
2.412
274811UNIV PK N;7U
Adder
2.406
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.681
960591AF2-350 GEN
Solar/Wind Harmer
4.73
274775LINCOLN ;6U
Adder
2.932
274776LINCOLN ;7U
Adder
2.932
274777LINCOLN ;8U
Adder
2.932
972227AH1-698 GEN1
Adder
1.23
274687WILL CNTY;4U
Adder
13.136
274687WILL CNTY;4U
Adder
13.136
270024AE2-089 GEN
Solar/Wind Harmer
2.202
274675JOLIET 29;7U
Adder
14.394
274675JOLIET 29;7U
Adder
13.88
274731ELWOOD EC;2P
Adder
7.698
274733ELWOOD EC;3P
Adder
7.698
274735ELWOOD EC;4P
Adder
7.698
274728ELWOOD EC;5P
Adder
7.698
970833AG2-524 GEN
Solar/Wind Harmer
4.069
970833AG2-524 GEN
Solar/Wind Harmer
1.892
274746AC1-111 G10
Adder
2.589
274744AC1-111 GEN8
Adder
2.589
24729505KEY G4
Adder
2.963
274823ROCKFORD ;21
Adder
8.769
241886AC2-103 GEN2
Solar/Wind Helper
4.614
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.926
203855AF2-088 C
Solar/Wind Helper
0.072
991182J1586 G
External Queue
25.292837142944336
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
991177J1571 G
External Queue
15.714932441711426
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.429
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.261
MECLTFEXP_MEC->PJM
CLTF
6.695
SIGELTFEXP_SIGE->PJM
CLTF
0.175
LAGNLTFEXP_LAGN->PJM
CLTF
5.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.292
TVALTFEXP_TVA->PJM
CLTF
2.336
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.091
NYPJM->LTFIMP_NY
CLTF
2.158
LGEELTFEXP_LGEE->PJM
CLTF
2.101
WECLTFEXP_WEC->PJM
CLTF
1.716
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.05 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2554.95
MW Contribution:2.57
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.678
23856402BAYSG1
50/50
1.433
23888702TROY G3
50/50
1.836
972253AH1-711 GEN
50/50
56.068
23860302FRMENG 3
50/50
3.538
23920202STRYCT
50/50
2.05
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241858AF1-205_GEN
Solar/Wind Harmer
4.134
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
7.119
23906402RICHG1
Adder
1.424
23906502RICHG2&3
Adder
1.422
270361_3
Solar/Wind Harmer
5.343
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
270428AC2-015 C
Solar/Wind Harmer
0.003
970515AG2-329 GEN
Solar/Wind Harmer
13.687
944231AF1-091 GEN
Solar/Wind Harmer
1.299
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.564
965421AG1-410 GEN
Solar/Wind Harmer
12.895
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.179
970905AG2-564 GEN
Solar/Wind Harmer
2.266
945111AF1-176 GEN
Solar/Wind Harmer
7.294
270505AE1-170 C O1
Solar/Wind Harmer
4.287
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.087
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
3.894
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.354
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4
274754CRETE EC ;4U
Adder
4
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.381
274723RIVER EC ;12
Adder
8.632
274812UNIV PK N;8U
Adder
2.401
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.756
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.118
276776AD2-060 GEN
Solar/Wind Harmer
0.344
274773LINCOLN ;4U
Adder
3.982
274774LINCOLN ;5U
Adder
3.982
274676JOLIET 29;8U
Adder
14.364
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.682
274674JOLIET 9 ;6U
Adder
7.195
970245AG2-165 GEN
Solar/Wind Harmer
1.409
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.583
276691AA1-018 GEN1
Solar/Wind Harmer
0.39
274682WAUKEGAN ;7U
Adder
8.249
274828WAUKEGAN ;BP
Adder
5.065
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.382
962781AG1-127 GEN
Solar/Wind Harmer
3.024
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.662
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.057
957471AF2-041 GEN
Solar/Wind Harmer
9.419
959081AF2-199 GEN
Solar/Wind Harmer
3.14
971067AG2-660 GEN
Solar/Wind Harmer
1.047
274822ROCKFORD ;11
Adder
8.814
970569AG2-363 GEN
Solar/Wind Harmer
9.385
972235AH1-702 GEN1
Adder
1.13
970819AG2-516 GEN
Solar/Wind Harmer
3.745
971475AH1-234 GEN
Solar/Wind Harmer
1.512
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.129
274766LEE CO EC;7U
Adder
0.439
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
0.908
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.328
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.276
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.359
203835AF1-098 GEN
Solar/Wind Helper
1.414
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.234
24190002OREGON_ST1
50/50
3.603
24189802OREGON_CT1
50/50
2.733
23888802TROY G4
50/50
1.836
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.745
970621AG2-405 GEN
Solar/Wind Harmer
0.95
970623AG2-406 GEN
Solar/Wind Harmer
0.856
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.157
246937BC-WTG2
Solar/Wind Harmer
0.176
961051AF2-396 GEN
Solar/Wind Harmer
8.284
961051AF2-396 GEN
Solar/Wind Harmer
5.523
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.894
970627AG2-408 GEN
Solar/Wind Harmer
1.168
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.428
965681AG1-436 GEN
Solar/Wind Harmer
4.548
965791AG1-447 GEN
Solar/Wind Harmer
3.335
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.391
274803UNIV PARK;6U
Adder
2.765
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.193
274887GEN-1.85
Solar/Wind Harmer
0.087
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.742
274770LINCOLN ;1U
Adder
3.982
274771LINCOLN ;2U
Adder
3.982
972259AH1-714 GEN
Adder
8.939
274674JOLIET 9 ;6U
Adder
7.195
970321AG2-212 GEN
Solar/Wind Harmer
1.409
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.833
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.436
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.598
274696ROCKY RD ;4P
Adder
5.229
274695ROCKY RD ;2P
Adder
5.109
23929302BS-PKR
50/50
2.523
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.267
23906502RICHG2&3
Adder
1.422
270575GUS2 35KV
Solar/Wind Harmer
5.343
270541AE2-072 C
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
4.562
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
3.735
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.266
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.564
945111AF1-176 GEN
Solar/Wind Harmer
3.313
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.026
24642205MAYFLWER
Adder
0.362
970031AG2-029 GEN
Solar/Wind Harmer
2.571
247643Z2-116 C
Solar/Wind Harmer
0
270485AE1-090_GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
2.726
965021AG1-366 GEN
Solar/Wind Harmer
1.298
270377AD1-106 GEN
Solar/Wind Harmer
1.42
270043AE2-236 GEN
Solar/Wind Harmer
2.353
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.434
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
4
274753CRETE EC ;3U
Adder
4
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
8.529
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.765
274826FISK ;BP
Adder
5.184
274800UNIV PARK;3U
Adder
2.756
972038AH1-567 GEN2
Adder
0.173
276806AD2-047 C O1
Solar/Wind Harmer
1.866
970941AG2-585 GEN
Solar/Wind Harmer
4.117
274772LINCOLN ;3U
Adder
3.982
972228AH1-698 GEN2
Adder
1.743
274676JOLIET 29;8U
Adder
13.851
971617AH1-308 GEN
Solar/Wind Harmer
2.722
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.129
274729ELWOOD EC;1P
Adder
7.682
274730ELWOOD EC;6P
Adder
7.682
274734ELWOOD EC;8P
Adder
7.682
274736ELWOOD EC;9P
Adder
7.682
970707AG2-453 GEN
Solar/Wind Harmer
10.65
23867002DVBSG1
50/50
12.822
972211AH1-690 GEN
50/50
288.807
23888502TROY G1
50/50
1.836
23888602TROY G2
50/50
1.836
23860102FRMENG 1
50/50
1.733
23860202FRMENG 2
50/50
1.733
24191202EL_AA1-006
50/50
0.334
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
10.986
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
10.515
971989AH1-539 GEN
Solar/Wind Harmer
1.989
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.55
971619AH1-309 GEN
Solar/Wind Harmer
1.837
965041AG1-368 GEN
Solar/Wind Harmer
4.077
965051AG1-369 GEN
Solar/Wind Harmer
2.027
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.55
971771AH1-392 GEN
Solar/Wind Harmer
3.877
971567AH1-282 GEN
Solar/Wind Harmer
5.76
971769AH1-391 GEN
Solar/Wind Harmer
4.221
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
5.434
963791AG1-232 GEN
Solar/Wind Harmer
4.874
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.537
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
2.422
274807UNIV PK N;3U
Adder
2.417
274805UNIV PK N;1U
Adder
2.407
274811UNIV PK N;7U
Adder
2.401
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.674
971611AH1-305 GEN
Solar/Wind Harmer
1.961
960591AF2-350 GEN
Solar/Wind Harmer
3.293
274775LINCOLN ;6U
Adder
3.982
274776LINCOLN ;7U
Adder
3.982
274777LINCOLN ;8U
Adder
3.982
972227AH1-698 GEN1
Adder
1.228
274687WILL CNTY;4U
Adder
13.109
274687WILL CNTY;4U
Adder
13.109
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274675JOLIET 29;7U
Adder
14.364
274675JOLIET 29;7U
Adder
13.851
274731ELWOOD EC;2P
Adder
7.682
274733ELWOOD EC;3P
Adder
7.682
274735ELWOOD EC;4P
Adder
7.682
274728ELWOOD EC;5P
Adder
7.682
970833AG2-524 GEN
Solar/Wind Harmer
3.569
970833AG2-524 GEN
Solar/Wind Harmer
2.379
274746AC1-111 G10
Adder
2.583
274744AC1-111 GEN8
Adder
2.583
24729505KEY G4
Adder
2.957
276868AE1-113 GEN
Solar/Wind Harmer
0.638
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.951
971411AH1-196 GEN
Solar/Wind Harmer
4.733
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.229
971171AH1-044 GEN
Solar/Wind Harmer
6.279
274823ROCKFORD ;21
Adder
8.75
970169AG2-114 GEN
Solar/Wind Harmer
3.123
970513AG2-328 GEN
Solar/Wind Harmer
1.409
970517AG2-330 GEN
Solar/Wind Harmer
8.456
943121AE2-341 GEN
Solar/Wind Harmer
5.404
943591AF1-030 GEN
Solar/Wind Harmer
3.594
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.389
274682WAUKEGAN ;7U
Adder
8.249
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.176
274872LEEDK;1U
Solar/Wind Harmer
0.116
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
959091AF2-200 GEN
Solar/Wind Harmer
6.279
970571AG2-364 GEN
Solar/Wind Harmer
6.257
972236AH1-702 GEN2
Adder
0.983
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.129
276157O29GEN1
Solar/Wind Harmer
0.497
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
942111AE2-223 GEN
Solar/Wind Harmer
0.993
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.58
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.061
959611AF2-252 GEN
Solar/Wind Harmer
1.007
965931AG1-462 GEN
Solar/Wind Harmer
7.661
247642Z2-115 C
Solar/Wind Harmer
0.001
962511AG1-100 GEN
Solar/Wind Helper
0.367
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.158
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.691
203854AF2-039 C
Solar/Wind Helper
0.15
274693ROCKY RD ;1P
Adder
5.059
274697ROCKY RD ;3P
Adder
1.388
274683WAUKEGAN ;8U
Adder
9.663
274683WAUKEGAN ;8U
Adder
8.145
958491AF2-143 GEN
Solar/Wind Harmer
4.791
962691AG1-118 GEN
Solar/Wind Harmer
9.548
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.177
970921AG2-575 GEN
Solar/Wind Harmer
1.059
942991AE2-321 GEN
Solar/Wind Harmer
3.534
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.305
971335AH1-147 GEN
Solar/Wind Harmer
6.305
971341AH1-150 GEN
Solar/Wind Harmer
6.279
971343AH1-151 GEN
Solar/Wind Harmer
6.279
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.759
274764LEE CO EC;5U
Adder
4.139
274765LEE CO EC;6U
Adder
4.139
274762LEE CO EC;3U
Adder
4.129
274763LEE CO EC;4U
Adder
4.09
966841AG1-555 GEN
Solar/Wind Harmer
0.35
944541AF1-119 GEN
Solar/Wind Harmer
0.207
276603SUBLETTE C
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
1.815
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276741O09 GEN1
Solar/Wind Harmer
0.109
276708O09 GEN2
Solar/Wind Harmer
0.109
276782AC1-033 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.305
960611AF2-352 GEN
Solar/Wind Harmer
1.007
270599AE1-208 GEN
Solar/Wind Harmer
2.766
270031AE2-169
Solar/Wind Harmer
1.66
203947AF1-006 C
Solar/Wind Helper
0.409
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.363
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.141
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.706
203853AF1-134 C O1
Solar/Wind Helper
0.221
926823AC1-168 GEN
Solar/Wind Harmer
0.531
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.808
957751AF2-069 GEN
Solar/Wind Harmer
0.102
965101AG1-375 GEN
Solar/Wind Harmer
3.066
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.207
941731AE2-173 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.315
971609AH1-304 GEN
Solar/Wind Harmer
0.493
946321AF1-296 GEN
Solar/Wind Harmer
1.689
945581AF1-223 GEN
Solar/Wind Harmer
0
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.266
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.928
203855AF2-088 C
Solar/Wind Helper
0.072
991182J1586 G
External Queue
25.292837142944336
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
991177J1571 G
External Queue
15.714932441711426
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.287
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.224
MECLTFEXP_MEC->PJM
CLTF
6.679
SIGELTFEXP_SIGE->PJM
CLTF
0.174
LAGNLTFEXP_LAGN->PJM
CLTF
5.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.262
TVALTFEXP_TVA->PJM
CLTF
2.326
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.959
NYPJM->LTFIMP_NY
CLTF
2.164
LGEELTFEXP_LGEE->PJM
CLTF
2.094
WECLTFEXP_WEC->PJM
CLTF
1.712
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.68 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2548.09
MW Contribution:2.58
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.68
23856402BAYSG1
50/50
1.434
23888702TROY G3
50/50
1.837
972253AH1-711 GEN
50/50
56.101
23860302FRMENG 3
50/50
3.54
23920202STRYCT
50/50
2.052
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241858AF1-205_GEN
Solar/Wind Harmer
4.136
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
7.125
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270361_3
Solar/Wind Harmer
5.347
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
270428AC2-015 C
Solar/Wind Harmer
0.003
970515AG2-329 GEN
Solar/Wind Harmer
13.704
944231AF1-091 GEN
Solar/Wind Harmer
1.301
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.565
965421AG1-410 GEN
Solar/Wind Harmer
12.915
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.182
970905AG2-564 GEN
Solar/Wind Harmer
2.27
945111AF1-176 GEN
Solar/Wind Harmer
7.306
270505AE1-170 C O1
Solar/Wind Harmer
4.294
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.088
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
3.901
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.368
270055AF2-134 C O1
Solar/Wind Harmer
0.003
23929302BS-PKR
50/50
2.524
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.268
23906502RICHG2&3
Adder
1.423
270575GUS2 35KV
Solar/Wind Harmer
5.347
270541AE2-072 C
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
4.568
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
3.741
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.267
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.565
945111AF1-176 GEN
Solar/Wind Harmer
3.319
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.026
24642205MAYFLWER
Adder
0.363
970031AG2-029 GEN
Solar/Wind Harmer
2.575
247643Z2-116 C
Solar/Wind Harmer
0
270485AE1-090_GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
2.73
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270377AD1-106 GEN
Solar/Wind Harmer
1.422
270043AE2-236 GEN
Solar/Wind Harmer
2.357
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.444
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
4.008
274753CRETE EC ;3U
Adder
4.008
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
8.546
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.771
274826FISK ;BP
Adder
5.194
274800UNIV PARK;3U
Adder
2.762
972038AH1-567 GEN2
Adder
0.173
276806AD2-047 C O1
Solar/Wind Harmer
1.87
970941AG2-585 GEN
Solar/Wind Harmer
4.125
274772LINCOLN ;3U
Adder
3.991
972228AH1-698 GEN2
Adder
1.747
274676JOLIET 29;8U
Adder
13.879
971617AH1-308 GEN
Solar/Wind Harmer
2.727
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.13
24190002OREGON_ST1
50/50
3.605
24189802OREGON_CT1
50/50
2.735
23888802TROY G4
50/50
1.837
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.746
970621AG2-405 GEN
Solar/Wind Harmer
0.951
970623AG2-406 GEN
Solar/Wind Harmer
0.857
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.158
246937BC-WTG2
Solar/Wind Harmer
0.176
961051AF2-396 GEN
Solar/Wind Harmer
8.298
961051AF2-396 GEN
Solar/Wind Harmer
5.532
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.901
970627AG2-408 GEN
Solar/Wind Harmer
1.17
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.429
965681AG1-436 GEN
Solar/Wind Harmer
4.556
965791AG1-447 GEN
Solar/Wind Harmer
3.341
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.396
274803UNIV PARK;6U
Adder
2.771
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.194
274887GEN-1.85
Solar/Wind Harmer
0.087
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.752
23867002DVBSG1
50/50
12.828
972211AH1-690 GEN
50/50
288.97
23888502TROY G1
50/50
1.837
23888602TROY G2
50/50
1.837
23860102FRMENG 1
50/50
1.734
23860202FRMENG 2
50/50
1.734
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
10.993
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
10.529
971989AH1-539 GEN
Solar/Wind Harmer
1.992
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.551
971619AH1-309 GEN
Solar/Wind Harmer
1.84
965041AG1-368 GEN
Solar/Wind Harmer
4.084
965051AG1-369 GEN
Solar/Wind Harmer
2.03
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.551
971771AH1-392 GEN
Solar/Wind Harmer
3.884
971567AH1-282 GEN
Solar/Wind Harmer
5.77
971769AH1-391 GEN
Solar/Wind Harmer
4.229
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
5.444
963791AG1-232 GEN
Solar/Wind Harmer
4.883
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.55
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
2.427
274807UNIV PK N;3U
Adder
2.422
274805UNIV PK N;1U
Adder
2.412
274811UNIV PK N;7U
Adder
2.406
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.681
971611AH1-305 GEN
Solar/Wind Harmer
1.965
960591AF2-350 GEN
Solar/Wind Harmer
3.3
274775LINCOLN ;6U
Adder
3.991
274776LINCOLN ;7U
Adder
3.991
274777LINCOLN ;8U
Adder
3.991
972227AH1-698 GEN1
Adder
1.23
274687WILL CNTY;4U
Adder
13.136
274687WILL CNTY;4U
Adder
13.136
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274675JOLIET 29;7U
Adder
14.394
274675JOLIET 29;7U
Adder
13.88
274731ELWOOD EC;2P
Adder
7.698
274733ELWOOD EC;3P
Adder
7.698
274735ELWOOD EC;4P
Adder
7.698
274728ELWOOD EC;5P
Adder
7.698
970833AG2-524 GEN
Solar/Wind Harmer
3.577
970833AG2-524 GEN
Solar/Wind Harmer
2.384
274746AC1-111 G10
Adder
2.589
274744AC1-111 GEN8
Adder
2.589
24729505KEY G4
Adder
2.963
276868AE1-113 GEN
Solar/Wind Harmer
0.639
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.955
971411AH1-196 GEN
Solar/Wind Harmer
4.743
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.232
971171AH1-044 GEN
Solar/Wind Harmer
6.293
274823ROCKFORD ;21
Adder
8.769
970169AG2-114 GEN
Solar/Wind Harmer
3.129
926823AC1-168 GEN
Solar/Wind Harmer
0.532
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.011
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.812
957751AF2-069 GEN
Solar/Wind Harmer
0.102
965101AG1-375 GEN
Solar/Wind Harmer
3.072
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.214
941731AE2-173 GEN
Solar/Wind Harmer
2.551
963841AG1-237 GEN
Solar/Wind Harmer
1.318
971609AH1-304 GEN
Solar/Wind Harmer
0.494
946321AF1-296 GEN
Solar/Wind Harmer
1.693
945581AF1-223 GEN
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
4.614
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.926
203855AF2-088 C
Solar/Wind Helper
0.072
274770LINCOLN ;1U
Adder
3.991
274771LINCOLN ;2U
Adder
3.991
972259AH1-714 GEN
Adder
8.958
274674JOLIET 9 ;6U
Adder
7.21
970321AG2-212 GEN
Solar/Wind Harmer
1.412
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.844
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.437
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.6
274696ROCKY RD ;4P
Adder
5.24
274695ROCKY RD ;2P
Adder
5.12
274693ROCKY RD ;1P
Adder
5.069
274697ROCKY RD ;3P
Adder
1.391
274683WAUKEGAN ;8U
Adder
9.683
274683WAUKEGAN ;8U
Adder
8.163
958491AF2-143 GEN
Solar/Wind Harmer
4.801
962691AG1-118 GEN
Solar/Wind Harmer
9.569
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.184
970921AG2-575 GEN
Solar/Wind Harmer
1.061
942991AE2-321 GEN
Solar/Wind Harmer
3.541
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.319
971335AH1-147 GEN
Solar/Wind Harmer
6.319
971341AH1-150 GEN
Solar/Wind Harmer
6.293
971343AH1-151 GEN
Solar/Wind Harmer
6.293
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.763
274764LEE CO EC;5U
Adder
4.148
274765LEE CO EC;6U
Adder
4.148
274762LEE CO EC;3U
Adder
4.138
274763LEE CO EC;4U
Adder
4.099
966841AG1-555 GEN
Solar/Wind Harmer
0.351
944541AF1-119 GEN
Solar/Wind Harmer
0.208
276603SUBLETTE C
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
1.819
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276741O09 GEN1
Solar/Wind Harmer
0.11
276708O09 GEN2
Solar/Wind Harmer
0.11
276782AC1-033 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.308
960611AF2-352 GEN
Solar/Wind Harmer
1.009
270599AE1-208 GEN
Solar/Wind Harmer
2.772
270031AE2-169
Solar/Wind Harmer
1.663
203947AF1-006 C
Solar/Wind Helper
0.408
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.362
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.14
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.112
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.704
274751CRETE EC ;1U
Adder
4.008
274754CRETE EC ;4U
Adder
4.008
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.39
274723RIVER EC ;12
Adder
8.649
274812UNIV PK N;8U
Adder
2.406
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.762
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.126
276776AD2-060 GEN
Solar/Wind Harmer
0.345
274773LINCOLN ;4U
Adder
3.991
274774LINCOLN ;5U
Adder
3.991
274676JOLIET 29;8U
Adder
14.394
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.698
274674JOLIET 9 ;6U
Adder
7.21
970245AG2-165 GEN
Solar/Wind Harmer
1.412
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.589
276691AA1-018 GEN1
Solar/Wind Harmer
0.391
274682WAUKEGAN ;7U
Adder
8.266
274828WAUKEGAN ;BP
Adder
5.076
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.387
962781AG1-127 GEN
Solar/Wind Harmer
3.03
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.665
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.057
957471AF2-041 GEN
Solar/Wind Harmer
9.44
959081AF2-199 GEN
Solar/Wind Harmer
3.147
971067AG2-660 GEN
Solar/Wind Harmer
1.049
274822ROCKFORD ;11
Adder
8.833
970569AG2-363 GEN
Solar/Wind Harmer
9.405
972235AH1-702 GEN1
Adder
1.133
970819AG2-516 GEN
Solar/Wind Harmer
3.753
971475AH1-234 GEN
Solar/Wind Harmer
1.515
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.138
274766LEE CO EC;7U
Adder
0.44
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
0.909
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.331
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.286
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
4.614
961971AG1-040 GEN
Solar/Wind Helper
0.358
203835AF1-098 GEN
Solar/Wind Helper
1.412
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.233
970707AG2-453 GEN
Solar/Wind Harmer
10.672
274729ELWOOD EC;1P
Adder
7.698
274730ELWOOD EC;6P
Adder
7.698
274734ELWOOD EC;8P
Adder
7.698
274736ELWOOD EC;9P
Adder
7.698
970513AG2-328 GEN
Solar/Wind Harmer
1.412
970517AG2-330 GEN
Solar/Wind Harmer
8.474
943121AE2-341 GEN
Solar/Wind Harmer
5.415
943591AF1-030 GEN
Solar/Wind Harmer
3.601
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.419
274682WAUKEGAN ;7U
Adder
8.266
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.183
274872LEEDK;1U
Solar/Wind Harmer
0.117
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
959091AF2-200 GEN
Solar/Wind Harmer
6.293
970571AG2-364 GEN
Solar/Wind Harmer
6.27
972236AH1-702 GEN2
Adder
0.985
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.138
276157O29GEN1
Solar/Wind Harmer
0.498
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
942111AE2-223 GEN
Solar/Wind Harmer
0.995
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.59
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.081
959611AF2-252 GEN
Solar/Wind Harmer
1.009
965931AG1-462 GEN
Solar/Wind Harmer
7.678
247642Z2-115 C
Solar/Wind Harmer
0.001
962511AG1-100 GEN
Solar/Wind Helper
0.366
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.157
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.689
203854AF2-039 C
Solar/Wind Helper
0.149
991182J1586 G
External Queue
25.292837142944336
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
991177J1571 G
External Queue
15.714932441711426
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.429
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.261
MECLTFEXP_MEC->PJM
CLTF
6.695
SIGELTFEXP_SIGE->PJM
CLTF
0.175
LAGNLTFEXP_LAGN->PJM
CLTF
5.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.292
TVALTFEXP_TVA->PJM
CLTF
2.336
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.091
NYPJM->LTFIMP_NY
CLTF
2.158
LGEELTFEXP_LGEE->PJM
CLTF
2.101
WECLTFEXP_WEC->PJM
CLTF
1.716
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-007_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-007_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.87 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2589.19
MW Contribution:18.73
Bus #Bus NameTypeMW Contribution
23906502RICHG2&3
50/50
1.719
241832AE2-181_GEN
Solar/Wind Harmer
2.411
958321AF2-126 GEN
Solar/Wind Harmer
1.797
23929302BS-PKR
Adder
1.928
270541AE2-072 C
Solar/Wind Harmer
5.113
270575GUS2 35KV
Solar/Wind Harmer
10.488
970217AG2-149 GEN
Solar/Wind Harmer
26.038
270044AE2-322 C
Solar/Wind Harmer
1.007
270404AC1-167 GEN
Solar/Wind Harmer
0.839
270258AD1-119 GEN
Solar/Wind Harmer
2.048
247604X1-042
Adder
0.293
270588AE1-091_GEN
Solar/Wind Harmer
7.623
24441205WTRV SLR C
Solar/Wind Harmer
0.093
958091AF2-103 GEN
Solar/Wind Harmer
0.111
270491AE1-102 GEN2
Solar/Wind Harmer
0.885
945111AF1-176 GEN
Solar/Wind Harmer
3.646
270191TR4_S_V150
Solar/Wind Harmer
1.906
270247TR4_N_V136
Solar/Wind Harmer
0.54
24642205MAYFLWER
Adder
0.399
970031AG2-029 GEN
Solar/Wind Harmer
18.728
247643Z2-116 C
Solar/Wind Harmer
0.043
959331AF2-224 GEN
Solar/Wind Harmer
6.135
965021AG1-366 GEN
Solar/Wind Harmer
1.427
270485AE1-090_GEN
Solar/Wind Harmer
0.37
270043AE2-236 GEN
Solar/Wind Harmer
3.186
970349AG2-230 GEN
Solar/Wind Harmer
8.587
942871AE2-306 GEN
Solar/Wind Harmer
0.515
270391AF1-285 GEN3
Solar/Wind Harmer
0.264
270535AF1-215 GEN1
Solar/Wind Harmer
2.468
972231SS25-0005
Solar/Wind Harmer
5.086
972181SS23-001
Solar/Wind Harmer
3.179
274752CRETE EC ;2U
Adder
2.62
274753CRETE EC ;3U
Adder
2.62
964401AG1-302 GEN
Solar/Wind Harmer
4.846
274724RIVER EC ;11
Adder
9.418
959141AF2-205 GEN
Solar/Wind Harmer
3.179
274802UNIV PARK;5U
Adder
3.055
274826FISK ;BP
Adder
5.726
274800UNIV PARK;3U
Adder
3.045
972038AH1-567 GEN2
Adder
0.191
276772AC2-154 GEN
Solar/Wind Harmer
1.454
276806AD2-047 C O1
Solar/Wind Harmer
5.578
970941AG2-585 GEN
Solar/Wind Harmer
6.518
274772LINCOLN ;3U
Adder
3.232
972228AH1-698 GEN2
Adder
1.926
274676JOLIET 29;8U
Adder
15.304
276897AD1-100 C
Solar/Wind Harmer
14.996
939351AE1-166 GEN
Solar/Wind Harmer
3.064
276893AG1-478 C
Solar/Wind Harmer
0.216
274729ELWOOD EC;1P
Adder
8.488
274730ELWOOD EC;6P
Adder
8.488
274734ELWOOD EC;8P
Adder
8.488
274736ELWOOD EC;9P
Adder
8.488
970707AG2-453 GEN
Solar/Wind Harmer
14.457
971617AH1-308 GEN
Solar/Wind Harmer
2.998
970513AG2-328 GEN
Solar/Wind Harmer
9.194
970517AG2-330 GEN
Solar/Wind Harmer
8.339
943121AE2-341 GEN
Solar/Wind Harmer
7.659
943591AF1-030 GEN
Solar/Wind Harmer
5.106
276694AA1-018 GEN2
Solar/Wind Harmer
3.221
23888802TROY G4
50/50
2.619
24190002OREGON_ST1
50/50
2.882
24189802OREGON_CT1
50/50
2.186
241996AE2-282_GEN
Solar/Wind Harmer
2.622
971677AH1-339 GEN
Solar/Wind Harmer
7.096
270007AE1-245 C
Solar/Wind Harmer
4.06
942801AE2-298 GEN
Solar/Wind Harmer
1.031
246938BC-WTG3
Solar/Wind Harmer
2.71
246937BC-WTG2
Solar/Wind Harmer
2.664
961051AF2-396 GEN
Solar/Wind Harmer
10.367
961051AF2-396 GEN
Solar/Wind Harmer
4.822
960981AF2-389 GEN
Solar/Wind Harmer
0.971
957891AF2-083 GEN
Solar/Wind Harmer
2.166
247620Y3-023
Adder
0.291
270216AD2-079_GEN
Solar/Wind Harmer
0.377
970611AG2-400 GEN
Solar/Wind Harmer
6.135
270526AF1-158 GEN
Solar/Wind Harmer
2.726
24441505OLIV SLR
Solar/Wind Harmer
0.08
274682WAUKEGAN ;7U
Adder
9.118
972236AH1-702 GEN2
Adder
1.087
274760LEE CO EC;1U
Adder
4.569
274767LEE CO EC;8U
Adder
4.515
962511AG1-100 GEN
Solar/Wind Helper
0.372
203830AF1-094 GEN
Solar/Wind Helper
0.352
959441AF2-235 GEN
Solar/Wind Helper
0.159
254305AE2-115 C
Solar/Wind Helper
0.122
20334926Z1-069 C
Solar/Wind Helper
0.694
203854AF2-039 C
Solar/Wind Helper
0.15
23888502TROY G1
50/50
2.619
23888602TROY G2
50/50
2.619
972211AH1-690 GEN
50/50
230.612
23906902RICHG6
50/50
1.023
23906702RICHG4
50/50
1.02
23906802RICHG5
50/50
0.745
970817AG2-515 GEN
Solar/Wind Harmer
20.387
945411AF1-206 GEN
Solar/Wind Harmer
9.795
945641AF1-229 GEN
Solar/Wind Harmer
4.031
270499AE1-146 GEN
Solar/Wind Harmer
2.505
971549AH1-272 GEN
Solar/Wind Harmer
14.838
270297AD1-101 GEN
Solar/Wind Harmer
2.213
247607V1-011 GEN
Solar/Wind Harmer
2.706
957201AF2-014 GEN
Solar/Wind Harmer
3.088
270435AC2-044 GEN
Solar/Wind Harmer
1.362
944161AF1-084 GEN
Solar/Wind Harmer
1.473
966831AG1-554 GEN
Solar/Wind Harmer
0.779
971989AH1-539 GEN
Solar/Wind Harmer
8.419
965041AG1-368 GEN
Solar/Wind Harmer
6.392
965051AG1-369 GEN
Solar/Wind Harmer
3.172
971771AH1-392 GEN
Solar/Wind Harmer
5.509
270302AB2-170 GEN
Solar/Wind Harmer
5.12
270317AD1-130_GEN
Solar/Wind Harmer
1.963
971769AH1-391 GEN
Solar/Wind Harmer
5.97
971567AH1-282 GEN
Solar/Wind Harmer
8.782
960681AF2-359 GEN
Solar/Wind Harmer
2.172
971347AH1-153 GEN
Solar/Wind Harmer
8.587
963791AG1-232 GEN
Solar/Wind Harmer
7.686
270578AF1-285 GEN2
Solar/Wind Harmer
0.264
270536AF1-215 GEN2
Solar/Wind Harmer
2.468
270071AF1-092 GEN
Solar/Wind Harmer
8.09
274814UNIV PK N;0U
Adder
2.675
274807UNIV PK N;3U
Adder
2.669
274805UNIV PK N;1U
Adder
2.658
274811UNIV PK N;7U
Adder
2.652
958391AF2-133 GEN
Solar/Wind Harmer
4.803
972037AH1-567 GEN1
Adder
0.096
274827FISK ;RP
Adder
4.058
960591AF2-350 GEN
Solar/Wind Harmer
5.215
274775LINCOLN ;6U
Adder
3.232
274776LINCOLN ;7U
Adder
3.232
274777LINCOLN ;8U
Adder
3.232
972227AH1-698 GEN1
Adder
1.356
274687WILL CNTY;4U
Adder
14.483
274687WILL CNTY;4U
Adder
14.483
274675JOLIET 29;7U
Adder
15.87
274675JOLIET 29;7U
Adder
15.304
274731ELWOOD EC;2P
Adder
8.488
274733ELWOOD EC;3P
Adder
8.488
274735ELWOOD EC;4P
Adder
8.488
274728ELWOOD EC;5P
Adder
8.488
270024AE2-089 GEN
Solar/Wind Harmer
2.42
970833AG2-524 GEN
Solar/Wind Harmer
4.486
970833AG2-524 GEN
Solar/Wind Harmer
2.087
274746AC1-111 G10
Adder
2.855
274744AC1-111 GEN8
Adder
2.855
24729505KEY G4
Adder
3.263
274823ROCKFORD ;21
Adder
9.678
241886AC2-103 GEN2
Solar/Wind Helper
7.132
241982AE2-343 S C
Solar/Wind Helper
0.128
254304AE2-114 C
Solar/Wind Helper
0.122
203846AF2-130 C
Solar/Wind Helper
0.268
241997AF1-093 GEN
Solar/Wind Helper
0.141
203804AE2-113_GEN
Solar/Wind Helper
0.933
203855AF2-088 C
Solar/Wind Helper
0.072
965681AG1-436 GEN
Solar/Wind Harmer
7.186
965791AG1-447 GEN
Solar/Wind Harmer
3.677
270224U2-072_GEN2
Solar/Wind Harmer
1.122
270227U2-072_GEN3
Solar/Wind Harmer
1.122
270228U2-072_GEN4
Solar/Wind Harmer
1.122
270231U2-072_GEN5
Solar/Wind Harmer
1.122
274808UNIV PK N;4U
Adder
2.64
274803UNIV PARK;6U
Adder
3.055
942221AE2-234 GEN
Solar/Wind Harmer
0.382
274888KELLY CRK;1U
Solar/Wind Harmer
3.079
274887GEN-1.85
Solar/Wind Harmer
2.779
276843GEN-1.7
Solar/Wind Harmer
0.299
958011AF2-095 GEN
Solar/Wind Harmer
7.509
274770LINCOLN ;1U
Adder
3.232
274771LINCOLN ;2U
Adder
3.232
972259AH1-714 GEN
Adder
9.876
274674JOLIET 9 ;6U
Adder
7.95
970321AG2-212 GEN
Solar/Wind Harmer
9.194
274847GR RIDGE ;BU
Solar/Wind Harmer
2.598
958481AF2-142 GEN
Solar/Wind Harmer
7.657
274696ROCKY RD ;4P
Adder
5.781
274695ROCKY RD ;2P
Adder
5.647
274693ROCKY RD ;1P
Adder
5.592
274697ROCKY RD ;3P
Adder
1.534
274683WAUKEGAN ;8U
Adder
10.682
274683WAUKEGAN ;8U
Adder
9.004
274764LEE CO EC;5U
Adder
4.579
274765LEE CO EC;6U
Adder
4.579
274762LEE CO EC;3U
Adder
4.569
274763LEE CO EC;4U
Adder
4.525
972267AH1-718 GEN
Adder
2.031
247621Y3-024
Adder
0.115
25326509SID D
Adder
0.626
203947AF1-006 C
Solar/Wind Helper
0.414
203980AG1-197 GEN
Solar/Wind Helper
0.271
203979AG1-198 GEN
Solar/Wind Helper
0.211
241967AE2-285_GEN
Solar/Wind Helper
0.368
241801AE1-079 GEN
Solar/Wind Helper
0.143
241985AE1-237 GEN
Solar/Wind Helper
0.143
962101AG1-054 GEN
Solar/Wind Helper
0.354
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.12
20398826ARMNA MT
Solar/Wind Helper
0.707
203853AF1-134 C O1
Solar/Wind Helper
0.221
274861TOP CROP ;1U
Solar/Wind Harmer
0.282
274862TOP CROP ;2U
Solar/Wind Harmer
0.236
23888702TROY G3
50/50
2.619
972253AH1-711 GEN
50/50
79.996
23920202STRYCT
50/50
2.358
24189902OREGON_CT2
50/50
2.142
972301AH1-735 GEN
50/50
8.615
23906402RICHG1
50/50
1.723
23906502RICHG2&3
50/50
1.719
241858AF1-205_GEN
Solar/Wind Harmer
6.914
241808AF1-120 C
Solar/Wind Harmer
1.462
241840AF1-064_GEN
Solar/Wind Harmer
1.676
270361_3
Solar/Wind Harmer
8.902
960841AF2-375 GEN
Solar/Wind Harmer
3.954
970515AG2-329 GEN
Solar/Wind Harmer
11.808
944231AF1-091 GEN
Solar/Wind Harmer
2.931
247522W1-056 GEN
Solar/Wind Harmer
1.705
246936BC-WTG1
Solar/Wind Harmer
2.664
270489AE1-102 GEN1
Solar/Wind Harmer
0.885
965421AG1-410 GEN
Solar/Wind Harmer
20.233
270449AD2-020 GEN
Solar/Wind Harmer
1.844
943021AE2-325 GEN
Solar/Wind Harmer
2.397
24695305TIMB G C
Solar/Wind Harmer
3.619
945111AF1-176 GEN
Solar/Wind Harmer
11.504
270505AE1-170 C O1
Solar/Wind Harmer
9.66
247521TR3_G114
Solar/Wind Harmer
2.136
270246TR4_N_V150
Solar/Wind Harmer
0.54
24639705ELKHART HY
Adder
0.096
270063AE2-323 C
Solar/Wind Harmer
1.381
965011AG1-365 GEN
Solar/Wind Harmer
6.135
270462AD2-086
Solar/Wind Harmer
4.259
270223U2-072_GEN1
Solar/Wind Harmer
1.122
270578AF1-285 GEN2
Solar/Wind Harmer
0.686
270391AF1-285 GEN3
Solar/Wind Harmer
0.686
970373AG2-245 GEN
Solar/Wind Harmer
11.628
270055AF2-134 C O1
Solar/Wind Harmer
1.645
274751CRETE EC ;1U
Adder
2.62
274754CRETE EC ;4U
Adder
2.62
958381AF2-132 GEN
Solar/Wind Harmer
4.846
964861AG1-349 GEN
Solar/Wind Harmer
4.191
971917AH1-482 GEN
Solar/Wind Harmer
4.836
274723RIVER EC ;12
Adder
9.531
274812UNIV PK N;8U
Adder
2.652
276164X3-005 C
Solar/Wind Harmer
0.371
274801UNIV PARK;4U
Adder
3.045
940581AE2-045 GEN
Solar/Wind Harmer
5.319
971605AH1-302 GEN
Solar/Wind Harmer
4.548
276776AD2-060 GEN
Solar/Wind Harmer
0.22
972207SS24-0001
Solar/Wind Harmer
11.49
274773LINCOLN ;4U
Adder
3.232
274774LINCOLN ;5U
Adder
3.232
274676JOLIET 29;8U
Adder
15.87
941551AE2-152 GEN
Solar/Wind Harmer
2.344
274732ELWOOD EC;7P
Adder
8.488
274674JOLIET 9 ;6U
Adder
7.95
970245AG2-165 GEN
Solar/Wind Harmer
9.194
274871GR RIDGE ;2U
Solar/Wind Harmer
3.949
274745AC1-111 GEN9
Adder
2.855
276691AA1-018 GEN1
Solar/Wind Harmer
0.238
274682WAUKEGAN ;7U
Adder
9.118
274828WAUKEGAN ;BP
Adder
5.599
274822ROCKFORD ;11
Adder
9.749
972235AH1-702 GEN1
Adder
1.25
274761LEE CO EC;2U
Adder
4.569
274766LEE CO EC;7U
Adder
4.515
241885AC2-103 GEN1
Solar/Wind Helper
7.132
241807AE2-176_GEN
Solar/Wind Helper
1.736
961971AG1-040 GEN
Solar/Wind Helper
0.363
203835AF1-098 GEN
Solar/Wind Helper
1.432
203860AG1-193 C
Solar/Wind Helper
0.162
241966AE1-183 GEN
Solar/Wind Helper
0.141
254303AC2-168 GEN
Solar/Wind Helper
0.082
203954AE2-126 C
Solar/Wind Helper
0.234
991182J1586 G
External Queue
28.404245376586914
990527J1329
External Queue
2.100800037384033
990142J1224
External Queue
15.35684871673584
991177J1571 G
External Queue
18.513126373291016
CBM West 1LTFEXP_CBM-W1->PJM
CBM
103.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.444
MECLTFEXP_MEC->PJM
CLTF
7.414
SIGELTFEXP_SIGE->PJM
CLTF
0.194
LAGNLTFEXP_LAGN->PJM
CLTF
5.797
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.925
TVALTFEXP_TVA->PJM
CLTF
2.645
CPLELTFEXP_CPLE->PJM
CLTF
0.546
CBM West 2LTFEXP_CBM-W2->PJM
CBM
45.898
NYPJM->LTFIMP_NY
CLTF
2.147
LGEELTFEXP_LGEE->PJM
CLTF
2.336
WECLTFEXP_WEC->PJM
CLTF
1.894
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-004_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.2 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2219.8
MW Contribution:19.39
Bus #Bus NameTypeMW Contribution
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
2.658
971677AH1-339 GEN
Solar/Wind Harmer
7.272
270007AE1-245 C
Solar/Wind Harmer
4.19
942801AE2-298 GEN
Solar/Wind Harmer
1.064
246938BC-WTG3
Solar/Wind Harmer
2.798
246937BC-WTG2
Solar/Wind Harmer
2.75
961051AF2-396 GEN
Solar/Wind Harmer
10.715
961051AF2-396 GEN
Solar/Wind Harmer
4.984
960981AF2-389 GEN
Solar/Wind Harmer
1.004
957891AF2-083 GEN
Solar/Wind Harmer
2.24
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.39
970611AG2-400 GEN
Solar/Wind Harmer
6.354
270526AF1-158 GEN
Solar/Wind Harmer
2.826
24441505OLIV SLR
Solar/Wind Harmer
0.083
965681AG1-436 GEN
Solar/Wind Harmer
7.46
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
1.166
270227U2-072_GEN3
Solar/Wind Harmer
1.166
270228U2-072_GEN4
Solar/Wind Harmer
1.166
270231U2-072_GEN5
Solar/Wind Harmer
1.166
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.398
274888KELLY CRK;1U
Solar/Wind Harmer
3.208
274887GEN-1.85
Solar/Wind Harmer
2.896
276843GEN-1.7
Solar/Wind Harmer
0.312
958011AF2-095 GEN
Solar/Wind Harmer
7.825
274770LINCOLN ;1U
Adder
3.367
274771LINCOLN ;2U
Adder
3.367
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
9.586
274847GR RIDGE ;BU
Solar/Wind Harmer
2.709
958481AF2-142 GEN
Solar/Wind Harmer
7.986
274696ROCKY RD ;4P
Adder
6.031
274695ROCKY RD ;2P
Adder
5.892
274693ROCKY RD ;1P
Adder
5.834
274697ROCKY RD ;3P
Adder
1.6
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.773
274763LEE CO EC;4U
Adder
4.728
972267AH1-718 GEN
Adder
2.123
247621Y3-024
Adder
0.12
25326509SID D
Adder
0.655
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241801AE1-079 GEN
Solar/Wind Helper
0.138
241967AE2-285_GEN
Solar/Wind Helper
0.354
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
274861TOP CROP ;1U
Solar/Wind Harmer
0.294
274862TOP CROP ;2U
Solar/Wind Harmer
0.246
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.74
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.177
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
7.001
241808AF1-120 C
Solar/Wind Harmer
1.482
241840AF1-064_GEN
Solar/Wind Harmer
1.7
270361_3
Solar/Wind Harmer
9.093
960841AF2-375 GEN
Solar/Wind Harmer
4.04
970515AG2-329 GEN
Solar/Wind Harmer
12.127
944231AF1-091 GEN
Solar/Wind Harmer
3.014
247522W1-056 GEN
Solar/Wind Harmer
1.754
246936BC-WTG1
Solar/Wind Harmer
2.75
270489AE1-102 GEN1
Solar/Wind Harmer
0.914
965421AG1-410 GEN
Solar/Wind Harmer
20.891
270449AD2-020 GEN
Solar/Wind Harmer
1.906
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
3.74
945111AF1-176 GEN
Solar/Wind Harmer
11.896
270505AE1-170 C O1
Solar/Wind Harmer
9.989
247521TR3_G114
Solar/Wind Harmer
2.21
270246TR4_N_V150
Solar/Wind Harmer
0.559
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
1.43
965011AG1-365 GEN
Solar/Wind Harmer
6.354
270462AD2-086
Solar/Wind Harmer
4.412
270223U2-072_GEN1
Solar/Wind Harmer
1.166
270578AF1-285 GEN2
Solar/Wind Harmer
0.713
270391AF1-285 GEN3
Solar/Wind Harmer
0.713
970373AG2-245 GEN
Solar/Wind Harmer
12.089
270055AF2-134 C O1
Solar/Wind Harmer
1.712
274751CRETE EC ;1U
Adder
2.727
274754CRETE EC ;4U
Adder
2.727
958381AF2-132 GEN
Solar/Wind Harmer
5.045
964861AG1-349 GEN
Solar/Wind Harmer
4.363
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0.386
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
5.542
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.23
972207SS24-0001
Solar/Wind Harmer
11.973
274773LINCOLN ;4U
Adder
3.367
274774LINCOLN ;5U
Adder
3.367
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
2.443
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
9.586
274871GR RIDGE ;2U
Solar/Wind Harmer
4.118
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.248
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.842
274822ROCKFORD ;11
Adder
10.179
972235AH1-702 GEN1
Adder
1.305
274761LEE CO EC;2U
Adder
4.773
274766LEE CO EC;7U
Adder
4.716
24728605AND G2
Adder
1.715
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.702
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
2.443
958321AF2-126 GEN
Solar/Wind Harmer
1.823
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
5.213
270575GUS2 35KV
Solar/Wind Harmer
10.713
970217AG2-149 GEN
Solar/Wind Harmer
26.741
270044AE2-322 C
Solar/Wind Harmer
1.036
270404AC1-167 GEN
Solar/Wind Harmer
0.862
270258AD1-119 GEN
Solar/Wind Harmer
2.11
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
7.864
24441205WTRV SLR C
Solar/Wind Harmer
0.096
958091AF2-103 GEN
Solar/Wind Harmer
0.114
270491AE1-102 GEN2
Solar/Wind Harmer
0.914
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
1.971
270247TR4_N_V136
Solar/Wind Harmer
0.559
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
19.386
247643Z2-116 C
Solar/Wind Harmer
0.045
959331AF2-224 GEN
Solar/Wind Harmer
6.354
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.384
270043AE2-236 GEN
Solar/Wind Harmer
3.307
970349AG2-230 GEN
Solar/Wind Harmer
8.916
942871AE2-306 GEN
Solar/Wind Harmer
0.535
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
2.568
972231SS25-0005
Solar/Wind Harmer
5.294
972181SS23-001
Solar/Wind Harmer
3.309
274752CRETE EC ;2U
Adder
2.727
274753CRETE EC ;3U
Adder
2.727
964401AG1-302 GEN
Solar/Wind Harmer
5.045
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
3.312
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276772AC2-154 GEN
Solar/Wind Harmer
1.515
276806AD2-047 C O1
Solar/Wind Harmer
5.813
970941AG2-585 GEN
Solar/Wind Harmer
6.792
274772LINCOLN ;3U
Adder
3.367
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
15.633
939351AE1-166 GEN
Solar/Wind Harmer
3.194
276893AG1-478 C
Solar/Wind Harmer
0.225
274729ELWOOD EC;1P
Adder
8.849
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
15.071
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
9.586
970517AG2-330 GEN
Solar/Wind Harmer
8.694
943121AE2-341 GEN
Solar/Wind Harmer
7.988
943591AF1-030 GEN
Solar/Wind Harmer
5.325
276694AA1-018 GEN2
Solar/Wind Harmer
3.36
274682WAUKEGAN ;7U
Adder
9.512
972236AH1-702 GEN2
Adder
1.135
274760LEE CO EC;1U
Adder
4.773
274767LEE CO EC;8U
Adder
4.716
24728705AND G3
Adder
3.588
24728505AND G1
Adder
1.715
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.319
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
20.605
945411AF1-206 GEN
Solar/Wind Harmer
9.926
945641AF1-229 GEN
Solar/Wind Harmer
4.111
270499AE1-146 GEN
Solar/Wind Harmer
2.56
971549AH1-272 GEN
Solar/Wind Harmer
15.244
270297AD1-101 GEN
Solar/Wind Harmer
2.274
247607V1-011 GEN
Solar/Wind Harmer
2.793
957201AF2-014 GEN
Solar/Wind Harmer
3.188
270435AC2-044 GEN
Solar/Wind Harmer
1.406
944161AF1-084 GEN
Solar/Wind Harmer
1.521
966831AG1-554 GEN
Solar/Wind Harmer
0.805
971989AH1-539 GEN
Solar/Wind Harmer
8.703
965041AG1-368 GEN
Solar/Wind Harmer
6.611
965051AG1-369 GEN
Solar/Wind Harmer
3.281
971771AH1-392 GEN
Solar/Wind Harmer
5.707
270302AB2-170 GEN
Solar/Wind Harmer
5.304
270317AD1-130_GEN
Solar/Wind Harmer
2.033
971769AH1-391 GEN
Solar/Wind Harmer
6.189
971567AH1-282 GEN
Solar/Wind Harmer
9.111
960681AF2-359 GEN
Solar/Wind Harmer
2.255
971347AH1-153 GEN
Solar/Wind Harmer
8.916
963791AG1-232 GEN
Solar/Wind Harmer
7.982
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
2.568
270071AF1-092 GEN
Solar/Wind Harmer
8.419
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
5.002
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
960591AF2-350 GEN
Solar/Wind Harmer
5.434
274775LINCOLN ;6U
Adder
3.367
274776LINCOLN ;7U
Adder
3.367
274777LINCOLN ;8U
Adder
3.367
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.096
274687WILL CNTY;4U
Adder
15.096
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.849
274733ELWOOD EC;3P
Adder
8.849
274735ELWOOD EC;4P
Adder
8.849
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
2.523
970833AG2-524 GEN
Solar/Wind Harmer
4.678
970833AG2-524 GEN
Solar/Wind Harmer
2.176
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
24729505KEY G4
Adder
3.405
274823ROCKFORD ;21
Adder
10.105
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
944201AF1-088_MTX
Adder
0.5
991182J1586 G
External Queue
28.40474510192871
990527J1329
External Queue
2.100818634033203
990142J1224
External Queue
15.356985092163086
991177J1571 G
External Queue
18.512771606445312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.194
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.861
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.488
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-005_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-005_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.2 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2219.73
MW Contribution:19.39
Bus #Bus NameTypeMW Contribution
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
2.658
971677AH1-339 GEN
Solar/Wind Harmer
7.271
270007AE1-245 C
Solar/Wind Harmer
4.19
942801AE2-298 GEN
Solar/Wind Harmer
1.064
246938BC-WTG3
Solar/Wind Harmer
2.798
246937BC-WTG2
Solar/Wind Harmer
2.75
961051AF2-396 GEN
Solar/Wind Harmer
10.715
961051AF2-396 GEN
Solar/Wind Harmer
4.984
960981AF2-389 GEN
Solar/Wind Harmer
1.004
957891AF2-083 GEN
Solar/Wind Harmer
2.24
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.39
970611AG2-400 GEN
Solar/Wind Harmer
6.354
270526AF1-158 GEN
Solar/Wind Harmer
2.826
24441505OLIV SLR
Solar/Wind Harmer
0.083
965681AG1-436 GEN
Solar/Wind Harmer
7.46
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
1.166
270227U2-072_GEN3
Solar/Wind Harmer
1.166
270228U2-072_GEN4
Solar/Wind Harmer
1.166
270231U2-072_GEN5
Solar/Wind Harmer
1.166
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.398
274888KELLY CRK;1U
Solar/Wind Harmer
3.208
274887GEN-1.85
Solar/Wind Harmer
2.896
276843GEN-1.7
Solar/Wind Harmer
0.312
958011AF2-095 GEN
Solar/Wind Harmer
7.825
274770LINCOLN ;1U
Adder
3.367
274771LINCOLN ;2U
Adder
3.367
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
9.586
274847GR RIDGE ;BU
Solar/Wind Harmer
2.709
958481AF2-142 GEN
Solar/Wind Harmer
7.986
274695ROCKY RD ;2P
Adder
5.891
274693ROCKY RD ;1P
Adder
5.833
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
972267AH1-718 GEN
Adder
2.123
247621Y3-024
Adder
0.12
25326509SID D
Adder
0.655
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
274861TOP CROP ;1U
Solar/Wind Harmer
0.294
274862TOP CROP ;2U
Solar/Wind Harmer
0.246
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.176
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
7.002
241808AF1-120 C
Solar/Wind Harmer
1.482
241840AF1-064_GEN
Solar/Wind Harmer
1.7
270361_3
Solar/Wind Harmer
9.093
960841AF2-375 GEN
Solar/Wind Harmer
4.04
970515AG2-329 GEN
Solar/Wind Harmer
12.126
944231AF1-091 GEN
Solar/Wind Harmer
3.014
247522W1-056 GEN
Solar/Wind Harmer
1.754
246936BC-WTG1
Solar/Wind Harmer
2.75
270489AE1-102 GEN1
Solar/Wind Harmer
0.914
965421AG1-410 GEN
Solar/Wind Harmer
20.891
270449AD2-020 GEN
Solar/Wind Harmer
1.906
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
3.74
945111AF1-176 GEN
Solar/Wind Harmer
11.896
270505AE1-170 C O1
Solar/Wind Harmer
9.988
247521TR3_G114
Solar/Wind Harmer
2.21
270246TR4_N_V150
Solar/Wind Harmer
0.559
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
1.43
965011AG1-365 GEN
Solar/Wind Harmer
6.354
270462AD2-086
Solar/Wind Harmer
4.412
270223U2-072_GEN1
Solar/Wind Harmer
1.166
270578AF1-285 GEN2
Solar/Wind Harmer
0.713
270391AF1-285 GEN3
Solar/Wind Harmer
0.713
970373AG2-245 GEN
Solar/Wind Harmer
12.088
270055AF2-134 C O1
Solar/Wind Harmer
1.712
274751CRETE EC ;1U
Adder
2.727
274754CRETE EC ;4U
Adder
2.727
958381AF2-132 GEN
Solar/Wind Harmer
5.044
964861AG1-349 GEN
Solar/Wind Harmer
4.363
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0.386
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
5.542
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.23
972207SS24-0001
Solar/Wind Harmer
11.973
274773LINCOLN ;4U
Adder
3.367
274774LINCOLN ;5U
Adder
3.367
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
2.443
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
9.586
274871GR RIDGE ;2U
Solar/Wind Harmer
4.118
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.248
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
274822ROCKFORD ;11
Adder
10.179
972235AH1-702 GEN1
Adder
1.305
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.716
24728605AND G2
Adder
1.715
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.701
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
2.444
958321AF2-126 GEN
Solar/Wind Harmer
1.823
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
5.213
270575GUS2 35KV
Solar/Wind Harmer
10.713
970217AG2-149 GEN
Solar/Wind Harmer
26.74
270044AE2-322 C
Solar/Wind Harmer
1.036
270404AC1-167 GEN
Solar/Wind Harmer
0.862
270258AD1-119 GEN
Solar/Wind Harmer
2.11
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
7.864
24441205WTRV SLR C
Solar/Wind Harmer
0.096
958091AF2-103 GEN
Solar/Wind Harmer
0.114
270491AE1-102 GEN2
Solar/Wind Harmer
0.914
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
1.971
270247TR4_N_V136
Solar/Wind Harmer
0.559
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
19.386
247643Z2-116 C
Solar/Wind Harmer
0.045
959331AF2-224 GEN
Solar/Wind Harmer
6.354
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.384
270043AE2-236 GEN
Solar/Wind Harmer
3.307
970349AG2-230 GEN
Solar/Wind Harmer
8.916
942871AE2-306 GEN
Solar/Wind Harmer
0.535
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
2.568
972231SS25-0005
Solar/Wind Harmer
5.294
972181SS23-001
Solar/Wind Harmer
3.309
274752CRETE EC ;2U
Adder
2.727
274753CRETE EC ;3U
Adder
2.727
964401AG1-302 GEN
Solar/Wind Harmer
5.044
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
3.312
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276772AC2-154 GEN
Solar/Wind Harmer
1.515
276806AD2-047 C O1
Solar/Wind Harmer
5.813
970941AG2-585 GEN
Solar/Wind Harmer
6.792
274772LINCOLN ;3U
Adder
3.367
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
15.632
939351AE1-166 GEN
Solar/Wind Harmer
3.194
276893AG1-478 C
Solar/Wind Harmer
0.225
274729ELWOOD EC;1P
Adder
8.848
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
15.071
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
9.586
970517AG2-330 GEN
Solar/Wind Harmer
8.694
943121AE2-341 GEN
Solar/Wind Harmer
7.988
943591AF1-030 GEN
Solar/Wind Harmer
5.325
276694AA1-018 GEN2
Solar/Wind Harmer
3.36
274682WAUKEGAN ;7U
Adder
9.512
972236AH1-702 GEN2
Adder
1.135
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
4.716
24728705AND G3
Adder
3.588
24728505AND G1
Adder
1.715
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.282
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
20.606
945411AF1-206 GEN
Solar/Wind Harmer
9.927
945641AF1-229 GEN
Solar/Wind Harmer
4.111
270499AE1-146 GEN
Solar/Wind Harmer
2.56
971549AH1-272 GEN
Solar/Wind Harmer
15.243
270297AD1-101 GEN
Solar/Wind Harmer
2.274
247607V1-011 GEN
Solar/Wind Harmer
2.793
957201AF2-014 GEN
Solar/Wind Harmer
3.188
270435AC2-044 GEN
Solar/Wind Harmer
1.406
944161AF1-084 GEN
Solar/Wind Harmer
1.521
966831AG1-554 GEN
Solar/Wind Harmer
0.805
971989AH1-539 GEN
Solar/Wind Harmer
8.703
965041AG1-368 GEN
Solar/Wind Harmer
6.611
965051AG1-369 GEN
Solar/Wind Harmer
3.281
971771AH1-392 GEN
Solar/Wind Harmer
5.706
270302AB2-170 GEN
Solar/Wind Harmer
5.304
270317AD1-130_GEN
Solar/Wind Harmer
2.033
971769AH1-391 GEN
Solar/Wind Harmer
6.189
971567AH1-282 GEN
Solar/Wind Harmer
9.111
960681AF2-359 GEN
Solar/Wind Harmer
2.255
971347AH1-153 GEN
Solar/Wind Harmer
8.916
963791AG1-232 GEN
Solar/Wind Harmer
7.982
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
2.568
270071AF1-092 GEN
Solar/Wind Harmer
8.419
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
5.002
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
960591AF2-350 GEN
Solar/Wind Harmer
5.434
274775LINCOLN ;6U
Adder
3.367
274776LINCOLN ;7U
Adder
3.367
274777LINCOLN ;8U
Adder
3.367
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274735ELWOOD EC;4P
Adder
8.848
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
2.523
970833AG2-524 GEN
Solar/Wind Harmer
4.678
970833AG2-524 GEN
Solar/Wind Harmer
2.176
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
24729505KEY G4
Adder
3.405
274823ROCKFORD ;21
Adder
10.105
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
944201AF1-088_MTX
Adder
0.5
991182J1586 G
External Queue
28.404245376586914
990527J1329
External Queue
2.100800037384033
990142J1224
External Queue
15.35684871673584
991177J1571 G
External Queue
18.513126373291016
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-006_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.2 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2219.73
MW Contribution:19.39
Bus #Bus NameTypeMW Contribution
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
2.658
971677AH1-339 GEN
Solar/Wind Harmer
7.271
270007AE1-245 C
Solar/Wind Harmer
4.19
942801AE2-298 GEN
Solar/Wind Harmer
1.064
246938BC-WTG3
Solar/Wind Harmer
2.798
246937BC-WTG2
Solar/Wind Harmer
2.75
961051AF2-396 GEN
Solar/Wind Harmer
10.715
961051AF2-396 GEN
Solar/Wind Harmer
4.984
960981AF2-389 GEN
Solar/Wind Harmer
1.004
957891AF2-083 GEN
Solar/Wind Harmer
2.24
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.39
970611AG2-400 GEN
Solar/Wind Harmer
6.354
270526AF1-158 GEN
Solar/Wind Harmer
2.826
24441505OLIV SLR
Solar/Wind Harmer
0.083
965681AG1-436 GEN
Solar/Wind Harmer
7.46
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
1.166
270227U2-072_GEN3
Solar/Wind Harmer
1.166
270228U2-072_GEN4
Solar/Wind Harmer
1.166
270231U2-072_GEN5
Solar/Wind Harmer
1.166
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.398
274888KELLY CRK;1U
Solar/Wind Harmer
3.208
274887GEN-1.85
Solar/Wind Harmer
2.896
276843GEN-1.7
Solar/Wind Harmer
0.312
958011AF2-095 GEN
Solar/Wind Harmer
7.825
274770LINCOLN ;1U
Adder
3.367
274771LINCOLN ;2U
Adder
3.367
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
9.586
274847GR RIDGE ;BU
Solar/Wind Harmer
2.709
958481AF2-142 GEN
Solar/Wind Harmer
7.986
274695ROCKY RD ;2P
Adder
5.891
274693ROCKY RD ;1P
Adder
5.833
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
972267AH1-718 GEN
Adder
2.123
247621Y3-024
Adder
0.12
25326509SID D
Adder
0.655
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
274861TOP CROP ;1U
Solar/Wind Harmer
0.294
274862TOP CROP ;2U
Solar/Wind Harmer
0.246
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.176
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
7.002
241808AF1-120 C
Solar/Wind Harmer
1.482
241840AF1-064_GEN
Solar/Wind Harmer
1.7
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
2.444
958321AF2-126 GEN
Solar/Wind Harmer
1.823
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
5.213
270575GUS2 35KV
Solar/Wind Harmer
10.713
970217AG2-149 GEN
Solar/Wind Harmer
26.74
270044AE2-322 C
Solar/Wind Harmer
1.036
270404AC1-167 GEN
Solar/Wind Harmer
0.862
270258AD1-119 GEN
Solar/Wind Harmer
2.11
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
7.864
24441205WTRV SLR C
Solar/Wind Harmer
0.096
958091AF2-103 GEN
Solar/Wind Harmer
0.114
270491AE1-102 GEN2
Solar/Wind Harmer
0.914
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
1.971
270247TR4_N_V136
Solar/Wind Harmer
0.559
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
19.386
247643Z2-116 C
Solar/Wind Harmer
0.045
959331AF2-224 GEN
Solar/Wind Harmer
6.354
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.384
270043AE2-236 GEN
Solar/Wind Harmer
3.307
970349AG2-230 GEN
Solar/Wind Harmer
8.916
942871AE2-306 GEN
Solar/Wind Harmer
0.535
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
2.568
972231SS25-0005
Solar/Wind Harmer
5.294
972181SS23-001
Solar/Wind Harmer
3.309
274752CRETE EC ;2U
Adder
2.727
274753CRETE EC ;3U
Adder
2.727
964401AG1-302 GEN
Solar/Wind Harmer
5.044
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
3.312
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276772AC2-154 GEN
Solar/Wind Harmer
1.515
276806AD2-047 C O1
Solar/Wind Harmer
5.813
970941AG2-585 GEN
Solar/Wind Harmer
6.792
274772LINCOLN ;3U
Adder
3.367
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
15.632
939351AE1-166 GEN
Solar/Wind Harmer
3.194
276893AG1-478 C
Solar/Wind Harmer
0.225
274729ELWOOD EC;1P
Adder
8.848
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
15.071
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
9.586
970517AG2-330 GEN
Solar/Wind Harmer
8.694
943121AE2-341 GEN
Solar/Wind Harmer
7.988
943591AF1-030 GEN
Solar/Wind Harmer
5.325
276694AA1-018 GEN2
Solar/Wind Harmer
3.36
274682WAUKEGAN ;7U
Adder
9.512
972236AH1-702 GEN2
Adder
1.135
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
4.716
24728705AND G3
Adder
3.588
24728505AND G1
Adder
1.715
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
270361_3
Solar/Wind Harmer
9.093
960841AF2-375 GEN
Solar/Wind Harmer
4.04
970515AG2-329 GEN
Solar/Wind Harmer
12.126
944231AF1-091 GEN
Solar/Wind Harmer
3.014
247522W1-056 GEN
Solar/Wind Harmer
1.754
246936BC-WTG1
Solar/Wind Harmer
2.75
270489AE1-102 GEN1
Solar/Wind Harmer
0.914
965421AG1-410 GEN
Solar/Wind Harmer
20.891
270449AD2-020 GEN
Solar/Wind Harmer
1.906
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
3.74
945111AF1-176 GEN
Solar/Wind Harmer
11.896
270505AE1-170 C O1
Solar/Wind Harmer
9.988
247521TR3_G114
Solar/Wind Harmer
2.21
270246TR4_N_V150
Solar/Wind Harmer
0.559
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
1.43
965011AG1-365 GEN
Solar/Wind Harmer
6.354
270462AD2-086
Solar/Wind Harmer
4.412
270223U2-072_GEN1
Solar/Wind Harmer
1.166
270578AF1-285 GEN2
Solar/Wind Harmer
0.713
270391AF1-285 GEN3
Solar/Wind Harmer
0.713
970373AG2-245 GEN
Solar/Wind Harmer
12.088
270055AF2-134 C O1
Solar/Wind Harmer
1.712
274751CRETE EC ;1U
Adder
2.727
274754CRETE EC ;4U
Adder
2.727
958381AF2-132 GEN
Solar/Wind Harmer
5.044
964861AG1-349 GEN
Solar/Wind Harmer
4.363
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0.386
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
5.542
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.23
972207SS24-0001
Solar/Wind Harmer
11.973
274773LINCOLN ;4U
Adder
3.367
274774LINCOLN ;5U
Adder
3.367
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
2.443
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
9.586
274871GR RIDGE ;2U
Solar/Wind Harmer
4.118
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.248
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
274822ROCKFORD ;11
Adder
10.179
972235AH1-702 GEN1
Adder
1.305
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.716
24728605AND G2
Adder
1.715
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.701
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.282
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
20.606
945411AF1-206 GEN
Solar/Wind Harmer
9.927
945641AF1-229 GEN
Solar/Wind Harmer
4.111
270499AE1-146 GEN
Solar/Wind Harmer
2.56
971549AH1-272 GEN
Solar/Wind Harmer
15.243
270297AD1-101 GEN
Solar/Wind Harmer
2.274
247607V1-011 GEN
Solar/Wind Harmer
2.793
957201AF2-014 GEN
Solar/Wind Harmer
3.188
270435AC2-044 GEN
Solar/Wind Harmer
1.406
944161AF1-084 GEN
Solar/Wind Harmer
1.521
966831AG1-554 GEN
Solar/Wind Harmer
0.805
971989AH1-539 GEN
Solar/Wind Harmer
8.703
965041AG1-368 GEN
Solar/Wind Harmer
6.611
965051AG1-369 GEN
Solar/Wind Harmer
3.281
971771AH1-392 GEN
Solar/Wind Harmer
5.706
270302AB2-170 GEN
Solar/Wind Harmer
5.304
270317AD1-130_GEN
Solar/Wind Harmer
2.033
971769AH1-391 GEN
Solar/Wind Harmer
6.189
971567AH1-282 GEN
Solar/Wind Harmer
9.111
960681AF2-359 GEN
Solar/Wind Harmer
2.255
971347AH1-153 GEN
Solar/Wind Harmer
8.916
963791AG1-232 GEN
Solar/Wind Harmer
7.982
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
2.568
270071AF1-092 GEN
Solar/Wind Harmer
8.419
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
5.002
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
960591AF2-350 GEN
Solar/Wind Harmer
5.434
274775LINCOLN ;6U
Adder
3.367
274776LINCOLN ;7U
Adder
3.367
274777LINCOLN ;8U
Adder
3.367
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274735ELWOOD EC;4P
Adder
8.848
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
2.523
970833AG2-524 GEN
Solar/Wind Harmer
4.678
970833AG2-524 GEN
Solar/Wind Harmer
2.176
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
24729505KEY G4
Adder
3.405
274823ROCKFORD ;21
Adder
10.105
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
944201AF1-088_MTX
Adder
0.5
991182J1586 G
External Queue
28.404245376586914
990527J1329
External Queue
2.100800037384033
990142J1224
External Queue
15.35684871673584
991177J1571 G
External Queue
18.513126373291016
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-601_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-601_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.99 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2140.73
MW Contribution:2.93
Bus #Bus NameTypeMW Contribution
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.413
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
0.01
270575GUS2 35KV
Solar/Wind Harmer
4.971
970217AG2-149 GEN
Solar/Wind Harmer
5.053
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
3.901
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.637
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.03
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
2.93
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
3.103
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.692
970349AG2-230 GEN
Solar/Wind Harmer
6.22
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
274752CRETE EC ;2U
Adder
4.596
274753CRETE EC ;3U
Adder
4.596
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276806AD2-047 C O1
Solar/Wind Harmer
2.148
970941AG2-585 GEN
Solar/Wind Harmer
4.739
274772LINCOLN ;3U
Adder
4.584
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.149
274729ELWOOD EC;1P
Adder
8.848
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
12.267
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
1.623
970517AG2-330 GEN
Solar/Wind Harmer
9.737
943121AE2-341 GEN
Solar/Wind Harmer
6.229
943591AF1-030 GEN
Solar/Wind Harmer
4.142
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
16.565
274682WAUKEGAN ;7U
Adder
9.512
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.663
274872LEEDK;1U
Solar/Wind Harmer
0.134
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.388
274855GSG-6 ;RU
Solar/Wind Harmer
0.133
274850MENDOTA H;RU
Solar/Wind Harmer
0.043
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.065
959091AF2-200 GEN
Solar/Wind Harmer
7.251
970571AG2-364 GEN
Solar/Wind Harmer
7.226
972236AH1-702 GEN2
Adder
1.135
270377AD1-106 GEN
Solar/Wind Harmer
1.364
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
0.229
276157O29GEN1
Solar/Wind Harmer
0.575
274878BISHOP HL;2U
Solar/Wind Harmer
0.119
942111AE2-223 GEN
Solar/Wind Harmer
1.148
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.278
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.488
959611AF2-252 GEN
Solar/Wind Harmer
1.165
965931AG1-462 GEN
Solar/Wind Harmer
8.873
247642Z2-115 C
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
0.379
970291AG2-192 GEN
Solar/Wind Harmer
0.345
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.563
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
946031AF1-268 GEN
Solar/Wind Harmer
3.219
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.189
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
958821AF2-173 GEN
Solar/Wind Harmer
1.049
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.176
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
4.885
241808AF1-120 C
Solar/Wind Harmer
0.004
241840AF1-064_GEN
Solar/Wind Harmer
0.005
270361_3
Solar/Wind Harmer
4.971
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
970515AG2-329 GEN
Solar/Wind Harmer
15.158
944231AF1-091 GEN
Solar/Wind Harmer
1.488
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.199
270489AE1-102 GEN1
Solar/Wind Harmer
0.637
965421AG1-410 GEN
Solar/Wind Harmer
14.575
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
8.299
270505AE1-170 C O1
Solar/Wind Harmer
4.878
247521TR3_G114
Solar/Wind Harmer
0.167
270246TR4_N_V150
Solar/Wind Harmer
0.03
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
0.004
965011AG1-365 GEN
Solar/Wind Harmer
4.433
270462AD2-086
Solar/Wind Harmer
0.009
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
8.434
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4.596
274754CRETE EC ;4U
Adder
4.596
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.396
274773LINCOLN ;4U
Adder
4.584
274774LINCOLN ;5U
Adder
4.584
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
1.623
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
276901AD2-066 C O1
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
2.747
962781AG1-127 GEN
Solar/Wind Harmer
3.489
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.918
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.065
957471AF2-041 GEN
Solar/Wind Harmer
10.876
959081AF2-199 GEN
Solar/Wind Harmer
3.625
971067AG2-660 GEN
Solar/Wind Harmer
1.208
274822ROCKFORD ;11
Adder
10.179
970569AG2-363 GEN
Solar/Wind Harmer
10.839
972235AH1-702 GEN1
Adder
1.305
970819AG2-516 GEN
Solar/Wind Harmer
4.326
971475AH1-234 GEN
Solar/Wind Harmer
1.747
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.716
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.047
276158O29GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.119
958861AF2-177 GEN
Solar/Wind Harmer
1.533
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.946
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
8.165
970291AG2-192 GEN
Solar/Wind Harmer
0.448
972175AH1-670 GEN
Solar/Wind Harmer
2.841
247536S-71 GEN
Solar/Wind Harmer
0.138
270032AE2-172
Solar/Wind Harmer
2.283
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.315
276903AD2-071 C
Solar/Wind Harmer
3.766
970825AG2-519 GEN
Solar/Wind Harmer
1.195
276615X2-022 GEN
Solar/Wind Harmer
0.035
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.701
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
0.007
971677AH1-339 GEN
Solar/Wind Harmer
0.714
970621AG2-405 GEN
Solar/Wind Harmer
1.043
970623AG2-406 GEN
Solar/Wind Harmer
0.966
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.178
246937BC-WTG2
Solar/Wind Harmer
0.199
961051AF2-396 GEN
Solar/Wind Harmer
9.419
961051AF2-396 GEN
Solar/Wind Harmer
6.28
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
4.433
970627AG2-408 GEN
Solar/Wind Harmer
1.33
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
5.205
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.019
274888KELLY CRK;1U
Solar/Wind Harmer
0.223
274887GEN-1.85
Solar/Wind Harmer
0.1
276843GEN-1.7
Solar/Wind Harmer
0.123
958011AF2-095 GEN
Solar/Wind Harmer
5.459
274770LINCOLN ;1U
Adder
4.584
274771LINCOLN ;2U
Adder
4.584
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
1.623
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.572
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.503
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.69
274695ROCKY RD ;2P
Adder
5.891
274693ROCKY RD ;1P
Adder
5.833
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
958491AF2-143 GEN
Solar/Wind Harmer
5.526
962691AG1-118 GEN
Solar/Wind Harmer
11.015
274879MINONK ;1U
Solar/Wind Harmer
0.155
970921AG2-575 GEN
Solar/Wind Harmer
3.666
970921AG2-575 GEN
Solar/Wind Harmer
1.222
942991AE2-321 GEN
Solar/Wind Harmer
4.078
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.279
971335AH1-147 GEN
Solar/Wind Harmer
7.279
971341AH1-150 GEN
Solar/Wind Harmer
7.251
971343AH1-151 GEN
Solar/Wind Harmer
7.251
274856ECOGROVE ;U1
Solar/Wind Harmer
0.085
276611AD2-172 GEN
Solar/Wind Harmer
0.001
971231AH1-075 GEN
Solar/Wind Harmer
0.412
938861AE1-114 GEN
Solar/Wind Harmer
2.033
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
966841AG1-555 GEN
Solar/Wind Harmer
0.405
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.239
960971AF2-388 GEN
Solar/Wind Harmer
2.094
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.14
276646AC1-214 GEN2
Solar/Wind Harmer
0.14
276741O09 GEN1
Solar/Wind Harmer
0.127
276708O09 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.165
964611AG1-324 GEN
Solar/Wind Harmer
0.262
270599AE1-208 GEN
Solar/Wind Harmer
3.195
270031AE2-169
Solar/Wind Harmer
1.917
970241AG2-163 GEN
Solar/Wind Harmer
2.013
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.487
971613AH1-306 GEN
Solar/Wind Harmer
1.644
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
3.372
970825AG2-519 GEN
Solar/Wind Harmer
3.73
970883AG2-550 GEN
Solar/Wind Harmer
3.346
970885AG2-551 GEN
Solar/Wind Harmer
1.115
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.282
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
14.376
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.032
971549AH1-272 GEN
Solar/Wind Harmer
11.871
270297AD1-101 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.621
971989AH1-539 GEN
Solar/Wind Harmer
2.024
971619AH1-309 GEN
Solar/Wind Harmer
2.091
965041AG1-368 GEN
Solar/Wind Harmer
4.612
965051AG1-369 GEN
Solar/Wind Harmer
2.289
971771AH1-392 GEN
Solar/Wind Harmer
4.424
270302AB2-170 GEN
Solar/Wind Harmer
0.003
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.621
971769AH1-391 GEN
Solar/Wind Harmer
4.822
971567AH1-282 GEN
Solar/Wind Harmer
6.357
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
6.22
963791AG1-232 GEN
Solar/Wind Harmer
5.569
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
270071AF1-092 GEN
Solar/Wind Harmer
7.505
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
971611AH1-305 GEN
Solar/Wind Harmer
2.257
960591AF2-350 GEN
Solar/Wind Harmer
3.791
274775LINCOLN ;6U
Adder
4.584
274776LINCOLN ;7U
Adder
4.584
274777LINCOLN ;8U
Adder
4.584
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274735ELWOOD EC;4P
Adder
8.848
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
0.004
970833AG2-524 GEN
Solar/Wind Harmer
4.112
970833AG2-524 GEN
Solar/Wind Harmer
2.741
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
276868AE1-113 GEN
Solar/Wind Harmer
0.736
276882AE2-255 GEN
Solar/Wind Harmer
0.429
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
3.405
971177AH1-047 GEN
Solar/Wind Harmer
2.252
971411AH1-196 GEN
Solar/Wind Harmer
5.463
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.419
971171AH1-044 GEN
Solar/Wind Harmer
7.251
274823ROCKFORD ;21
Adder
10.105
926823AC1-168 GEN
Solar/Wind Harmer
0.613
970169AG2-114 GEN
Solar/Wind Harmer
3.606
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.777
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.09
957751AF2-069 GEN
Solar/Wind Harmer
0.117
965101AG1-375 GEN
Solar/Wind Harmer
3.538
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.709
941731AE2-173 GEN
Solar/Wind Harmer
2.944
963841AG1-237 GEN
Solar/Wind Harmer
1.521
946321AF1-296 GEN
Solar/Wind Harmer
1.955
971609AH1-304 GEN
Solar/Wind Harmer
0.569
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.655
270594AE1-207 GEN
Solar/Wind Harmer
3.835
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.123
970115AG2-085 GEN
Solar/Wind Harmer
1.349
270543AE2-219 C
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
991182J1586 G
External Queue
28.404245376586914
990527J1329
External Queue
2.100800037384033
990142J1224
External Queue
15.35684871673584
991177J1571 G
External Queue
18.513126373291016
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-021_SRT-A-1


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-021_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.02 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2047.43
MW Contribution:16.71
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
2.569
23888602TROY G2
50/50
2.569
972211AH1-690 GEN
50/50
211.679
23906902RICHG6
50/50
0.775
23906702RICHG4
50/50
0.773
23906502RICHG2&3
50/50
1.301
241832AE2-181_GEN
Solar/Wind Harmer
1.668
958321AF2-126 GEN
Solar/Wind Harmer
1.231
270541AE2-072 C
Solar/Wind Harmer
4.058
270575GUS2 35KV
Solar/Wind Harmer
8.824
970217AG2-149 GEN
Solar/Wind Harmer
24.659
270044AE2-322 C
Solar/Wind Harmer
0.857
270404AC1-167 GEN
Solar/Wind Harmer
0.713
270258AD1-119 GEN
Solar/Wind Harmer
1.762
247604X1-042
Adder
0.26
270491AE1-102 GEN2
Solar/Wind Harmer
0.803
270588AE1-091_GEN
Solar/Wind Harmer
6.773
24441205WTRV SLR C
Solar/Wind Harmer
0.082
958091AF2-103 GEN
Solar/Wind Harmer
0.098
945111AF1-176 GEN
Solar/Wind Harmer
3.248
270191TR4_S_V150
Solar/Wind Harmer
1.699
270247TR4_N_V136
Solar/Wind Harmer
0.482
270485AE1-090_GEN
Solar/Wind Harmer
0.342
24642205MAYFLWER
Adder
0.356
970031AG2-029 GEN
Solar/Wind Harmer
16.707
247643Z2-116 C
Solar/Wind Harmer
0.039
23906802RICHG5
50/50
0.564
970817AG2-515 GEN
Solar/Wind Harmer
17.825
945411AF1-206 GEN
Solar/Wind Harmer
6.384
945641AF1-229 GEN
Solar/Wind Harmer
3.799
270499AE1-146 GEN
Solar/Wind Harmer
2.114
971549AH1-272 GEN
Solar/Wind Harmer
13.108
270297AD1-101 GEN
Solar/Wind Harmer
1.882
957201AF2-014 GEN
Solar/Wind Harmer
2.802
270435AC2-044 GEN
Solar/Wind Harmer
1.235
247607V1-011 GEN
Solar/Wind Harmer
2.395
944161AF1-084 GEN
Solar/Wind Harmer
1.31
966831AG1-554 GEN
Solar/Wind Harmer
0.689
971989AH1-539 GEN
Solar/Wind Harmer
7.445
965041AG1-368 GEN
Solar/Wind Harmer
5.685
965051AG1-369 GEN
Solar/Wind Harmer
2.828
270302AB2-170 GEN
Solar/Wind Harmer
4.729
270317AD1-130_GEN
Solar/Wind Harmer
1.813
971567AH1-282 GEN
Solar/Wind Harmer
8.37
971771AH1-392 GEN
Solar/Wind Harmer
4.919
971769AH1-391 GEN
Solar/Wind Harmer
5.338
270578AF1-285 GEN2
Solar/Wind Harmer
0.244
960681AF2-359 GEN
Solar/Wind Harmer
1.946
971347AH1-153 GEN
Solar/Wind Harmer
7.697
963791AG1-232 GEN
Solar/Wind Harmer
6.886
270536AF1-215 GEN2
Solar/Wind Harmer
2.218
270071AF1-092 GEN
Solar/Wind Harmer
7.266
274814UNIV PK N;0U
Adder
2.407
274807UNIV PK N;3U
Adder
2.402
274805UNIV PK N;1U
Adder
2.392
274811UNIV PK N;7U
Adder
2.386
958391AF2-133 GEN
Solar/Wind Harmer
4.322
972037AH1-567 GEN1
Adder
0.086
274827FISK ;RP
Adder
3.654
960591AF2-350 GEN
Solar/Wind Harmer
4.697
274775LINCOLN ;6U
Adder
2.911
274776LINCOLN ;7U
Adder
2.911
274777LINCOLN ;8U
Adder
2.911
972227AH1-698 GEN1
Adder
1.222
274687WILL CNTY;4U
Adder
13.048
274687WILL CNTY;4U
Adder
13.048
274675JOLIET 29;7U
Adder
14.3
274675JOLIET 29;7U
Adder
13.789
274728ELWOOD EC;5P
Adder
7.649
274731ELWOOD EC;2P
Adder
7.649
274733ELWOOD EC;3P
Adder
7.649
274735ELWOOD EC;4P
Adder
7.649
270024AE2-089 GEN
Solar/Wind Harmer
2.183
970833AG2-524 GEN
Solar/Wind Harmer
4.044
970833AG2-524 GEN
Solar/Wind Harmer
1.881
274746AC1-111 G10
Adder
2.574
274744AC1-111 GEN8
Adder
2.574
24729505KEY G4
Adder
2.948
274823ROCKFORD ;21
Adder
8.739
241886AC2-103 GEN2
Solar/Wind Helper
5.94
241982AE2-343 S C
Solar/Wind Helper
0.106
254304AE2-114 C
Solar/Wind Helper
0.101
203846AF2-130 C
Solar/Wind Helper
0.222
241997AF1-093 GEN
Solar/Wind Helper
0.117
23888702TROY G3
50/50
2.569
972253AH1-711 GEN
50/50
78.462
24189902OREGON_CT2
50/50
1.966
23920202STRYCT
50/50
1.673
972301AH1-735 GEN
50/50
6.522
23906402RICHG1
50/50
1.304
23906502RICHG2&3
50/50
1.301
241858AF1-205_GEN
Solar/Wind Harmer
5.012
241808AF1-120 C
Solar/Wind Harmer
0.953
241840AF1-064_GEN
Solar/Wind Harmer
1.148
270361_3
Solar/Wind Harmer
7.49
960841AF2-375 GEN
Solar/Wind Harmer
3.331
970515AG2-329 GEN
Solar/Wind Harmer
11.182
247522W1-056 GEN
Solar/Wind Harmer
1.488
944231AF1-091 GEN
Solar/Wind Harmer
2.464
246936BC-WTG1
Solar/Wind Harmer
2.417
270489AE1-102 GEN1
Solar/Wind Harmer
0.803
965421AG1-410 GEN
Solar/Wind Harmer
18.338
270449AD2-020 GEN
Solar/Wind Harmer
1.642
943021AE2-325 GEN
Solar/Wind Harmer
2.133
24695305TIMB G C
Solar/Wind Harmer
3.212
945111AF1-176 GEN
Solar/Wind Harmer
10.248
270505AE1-170 C O1
Solar/Wind Harmer
8.607
247521TR3_G114
Solar/Wind Harmer
1.904
270246TR4_N_V150
Solar/Wind Harmer
0.482
270462AD2-086
Solar/Wind Harmer
3.934
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
1.226
965011AG1-365 GEN
Solar/Wind Harmer
5.502
270223U2-072_GEN1
Solar/Wind Harmer
1.039
270578AF1-285 GEN2
Solar/Wind Harmer
0.635
270391AF1-285 GEN3
Solar/Wind Harmer
0.635
970373AG2-245 GEN
Solar/Wind Harmer
10.44
270055AF2-134 C O1
Solar/Wind Harmer
1.479
274751CRETE EC ;1U
Adder
2.356
274754CRETE EC ;4U
Adder
2.356
958381AF2-132 GEN
Solar/Wind Harmer
4.359
964861AG1-349 GEN
Solar/Wind Harmer
3.77
971917AH1-482 GEN
Solar/Wind Harmer
4.351
274723RIVER EC ;12
Adder
8.575
274812UNIV PK N;8U
Adder
2.386
276164X3-005 C
Solar/Wind Harmer
0.334
274801UNIV PARK;4U
Adder
2.742
940581AE2-045 GEN
Solar/Wind Harmer
4.791
971605AH1-302 GEN
Solar/Wind Harmer
4.097
276776AD2-060 GEN
Solar/Wind Harmer
0.199
972207SS24-0001
Solar/Wind Harmer
10.349
274773LINCOLN ;4U
Adder
2.911
274774LINCOLN ;5U
Adder
2.911
274676JOLIET 29;8U
Adder
14.3
941551AE2-152 GEN
Solar/Wind Harmer
2.112
274732ELWOOD EC;7P
Adder
7.649
274674JOLIET 9 ;6U
Adder
7.164
970245AG2-165 GEN
Solar/Wind Harmer
8.289
274871GR RIDGE ;2U
Solar/Wind Harmer
3.56
274745AC1-111 GEN9
Adder
2.574
276691AA1-018 GEN1
Solar/Wind Harmer
0.214
274682WAUKEGAN ;7U
Adder
8.225
274828WAUKEGAN ;BP
Adder
5.051
274822ROCKFORD ;11
Adder
8.803
972235AH1-702 GEN1
Adder
1.129
274761LEE CO EC;2U
Adder
4.128
274766LEE CO EC;7U
Adder
4.079
241885AC2-103 GEN1
Solar/Wind Helper
5.94
241807AE2-176_GEN
Solar/Wind Helper
1.896
961971AG1-040 GEN
Solar/Wind Helper
0.304
203835AF1-098 GEN
Solar/Wind Helper
1.197
203860AG1-193 C
Solar/Wind Helper
0.135
241966AE1-183 GEN
Solar/Wind Helper
0.117
254303AC2-168 GEN
Solar/Wind Helper
0.068
23888802TROY G4
50/50
2.569
24190002OREGON_ST1
50/50
2.645
24189802OREGON_CT1
50/50
2.007
241996AE2-282_GEN
Solar/Wind Harmer
1.709
971677AH1-339 GEN
Solar/Wind Harmer
6.229
246938BC-WTG3
Solar/Wind Harmer
2.459
246937BC-WTG2
Solar/Wind Harmer
2.417
270007AE1-245 C
Solar/Wind Harmer
3.593
942801AE2-298 GEN
Solar/Wind Harmer
0.907
961051AF2-396 GEN
Solar/Wind Harmer
9.231
961051AF2-396 GEN
Solar/Wind Harmer
4.293
960981AF2-389 GEN
Solar/Wind Harmer
0.865
957891AF2-083 GEN
Solar/Wind Harmer
1.93
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.336
970611AG2-400 GEN
Solar/Wind Harmer
5.502
270526AF1-158 GEN
Solar/Wind Harmer
2.437
24441505OLIV SLR
Solar/Wind Harmer
0.072
270224U2-072_GEN2
Solar/Wind Harmer
1.039
270227U2-072_GEN3
Solar/Wind Harmer
1.039
270228U2-072_GEN4
Solar/Wind Harmer
1.039
270231U2-072_GEN5
Solar/Wind Harmer
1.039
965681AG1-436 GEN
Solar/Wind Harmer
6.439
965791AG1-447 GEN
Solar/Wind Harmer
3.294
274808UNIV PK N;4U
Adder
2.376
274803UNIV PARK;6U
Adder
2.75
274888KELLY CRK;1U
Solar/Wind Harmer
2.773
274887GEN-1.85
Solar/Wind Harmer
2.503
276843GEN-1.7
Solar/Wind Harmer
0.269
942221AE2-234 GEN
Solar/Wind Harmer
0.344
958011AF2-095 GEN
Solar/Wind Harmer
6.763
274770LINCOLN ;1U
Adder
2.911
274771LINCOLN ;2U
Adder
2.911
972259AH1-714 GEN
Adder
8.899
274674JOLIET 9 ;6U
Adder
7.164
970321AG2-212 GEN
Solar/Wind Harmer
8.289
274847GR RIDGE ;BU
Solar/Wind Harmer
2.342
958481AF2-142 GEN
Solar/Wind Harmer
6.904
274696ROCKY RD ;4P
Adder
5.214
274695ROCKY RD ;2P
Adder
5.094
274693ROCKY RD ;1P
Adder
5.044
274697ROCKY RD ;3P
Adder
1.384
274683WAUKEGAN ;8U
Adder
9.635
274683WAUKEGAN ;8U
Adder
8.122
274764LEE CO EC;5U
Adder
4.138
274765LEE CO EC;6U
Adder
4.138
274762LEE CO EC;3U
Adder
4.128
274763LEE CO EC;4U
Adder
4.089
972267AH1-718 GEN
Adder
1.836
25326509SID D
Adder
0.577
247621Y3-024
Adder
0.104
203947AF1-006 C
Solar/Wind Helper
0.347
203980AG1-197 GEN
Solar/Wind Helper
0.226
203979AG1-198 GEN
Solar/Wind Helper
0.176
241967AE2-285_GEN
Solar/Wind Helper
0.305
241801AE1-079 GEN
Solar/Wind Helper
0.119
241985AE1-237 GEN
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.293
274861TOP CROP ;1U
Solar/Wind Harmer
0.254
274862TOP CROP ;2U
Solar/Wind Harmer
0.213
959331AF2-224 GEN
Solar/Wind Harmer
5.502
965021AG1-366 GEN
Solar/Wind Harmer
1.28
942871AE2-306 GEN
Solar/Wind Harmer
0.477
270391AF1-285 GEN3
Solar/Wind Harmer
0.244
270043AE2-236 GEN
Solar/Wind Harmer
2.848
970349AG2-230 GEN
Solar/Wind Harmer
7.697
270535AF1-215 GEN1
Solar/Wind Harmer
2.218
972231SS25-0005
Solar/Wind Harmer
4.574
972181SS23-001
Solar/Wind Harmer
2.859
274752CRETE EC ;2U
Adder
2.356
274753CRETE EC ;3U
Adder
2.356
964401AG1-302 GEN
Solar/Wind Harmer
4.359
274724RIVER EC ;11
Adder
8.473
959141AF2-205 GEN
Solar/Wind Harmer
2.862
274802UNIV PARK;5U
Adder
2.75
274826FISK ;BP
Adder
5.156
274800UNIV PARK;3U
Adder
2.742
972038AH1-567 GEN2
Adder
0.172
276772AC2-154 GEN
Solar/Wind Harmer
1.31
276806AD2-047 C O1
Solar/Wind Harmer
5.024
970941AG2-585 GEN
Solar/Wind Harmer
5.871
274772LINCOLN ;3U
Adder
2.911
972228AH1-698 GEN2
Adder
1.735
274676JOLIET 29;8U
Adder
13.789
276897AD1-100 C
Solar/Wind Harmer
13.513
939351AE1-166 GEN
Solar/Wind Harmer
2.761
276893AG1-478 C
Solar/Wind Harmer
0.194
274730ELWOOD EC;6P
Adder
7.649
274734ELWOOD EC;8P
Adder
7.649
274736ELWOOD EC;9P
Adder
7.649
970707AG2-453 GEN
Solar/Wind Harmer
13.028
274729ELWOOD EC;1P
Adder
7.649
971617AH1-308 GEN
Solar/Wind Harmer
2.704
970513AG2-328 GEN
Solar/Wind Harmer
8.289
970517AG2-330 GEN
Solar/Wind Harmer
7.518
943121AE2-341 GEN
Solar/Wind Harmer
6.906
943591AF1-030 GEN
Solar/Wind Harmer
4.604
276694AA1-018 GEN2
Solar/Wind Harmer
2.905
274682WAUKEGAN ;7U
Adder
8.225
972236AH1-702 GEN2
Adder
0.982
274760LEE CO EC;1U
Adder
4.128
274767LEE CO EC;8U
Adder
4.079
962511AG1-100 GEN
Solar/Wind Helper
0.311
203830AF1-094 GEN
Solar/Wind Helper
0.294
959441AF2-235 GEN
Solar/Wind Helper
0.133
254305AE2-115 C
Solar/Wind Helper
0.101
991182J1586 G
External Queue
24.285308837890625
990527J1329
External Queue
1.7516577243804932
990142J1224
External Queue
12.804616928100586
991177J1571 G
External Queue
14.387535095214844
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.185
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.846
MECLTFEXP_MEC->PJM
CLTF
6.742
SIGELTFEXP_SIGE->PJM
CLTF
0.179
LAGNLTFEXP_LAGN->PJM
CLTF
5.44
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.193
TVALTFEXP_TVA->PJM
CLTF
2.504
CPLELTFEXP_CPLE->PJM
CLTF
0.714
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.488
NYPJM->LTFIMP_NY
CLTF
1.719
LGEELTFEXP_LGEE->PJM
CLTF
2.17
WECLTFEXP_WEC->PJM
CLTF
1.711
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.164

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.08 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2294.25
MW Contribution:36.41
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.416
24729505KEY G4
50/50
6.81
24653605MOTTVILLE
50/50
0.004
963791AG1-232 GEN
Solar/Wind Harmer
16.715
965041AG1-368 GEN
Solar/Wind Harmer
12.09
270071AF1-092 GEN
Solar/Wind Harmer
16.314
965051AG1-369 GEN
Solar/Wind Harmer
5.144
958711AF2-162 GEN
Solar/Wind Harmer
0.921
270024AE2-089 GEN
Solar/Wind Harmer
4.207
965101AG1-375 GEN
Solar/Wind Harmer
8.843
971771AH1-392 GEN
Solar/Wind Harmer
7.653
971347AH1-153 GEN
Solar/Wind Harmer
12.648
945581AF1-223 GEN
Solar/Wind Harmer
3.786
971769AH1-391 GEN
Solar/Wind Harmer
8.193
944161AF1-084 GEN
Solar/Wind Harmer
1.8
960681AF2-359 GEN
Solar/Wind Harmer
3.035
274814UNIV PK N;0U
Adder
3.859
274807UNIV PK N;3U
Adder
3.851
274805UNIV PK N;1U
Adder
3.834
274811UNIV PK N;7U
Adder
3.826
270536AF1-215 GEN2
Solar/Wind Harmer
3.466
274775LINCOLN ;6U
Adder
4.718
274776LINCOLN ;7U
Adder
4.718
274777LINCOLN ;8U
Adder
4.718
972037AH1-567 GEN1
Adder
0.138
274827FISK ;RP
Adder
5.862
960591AF2-350 GEN
Solar/Wind Harmer
7.533
972227AH1-698 GEN1
Adder
1.959
274687WILL CNTY;4U
Adder
20.885
274687WILL CNTY;4U
Adder
20.885
958391AF2-133 GEN
Solar/Wind Harmer
6.77
274675JOLIET 29;7U
Adder
22.884
274675JOLIET 29;7U
Adder
22.066
274728ELWOOD EC;5P
Adder
12.229
274731ELWOOD EC;2P
Adder
12.229
274733ELWOOD EC;3P
Adder
12.229
274735ELWOOD EC;4P
Adder
12.229
970833AG2-524 GEN
Solar/Wind Harmer
6.467
970833AG2-524 GEN
Solar/Wind Harmer
3.008
274746AC1-111 G10
Adder
4.111
274744AC1-111 GEN8
Adder
4.111
965461AG1-414 GEN
Solar/Wind Harmer
1.643
970289AG2-191 GEN
Solar/Wind Harmer
1.377
276868AE1-113 GEN
Solar/Wind Harmer
7.267
276882AE2-255 GEN
Solar/Wind Harmer
2.423
270594AE1-207 GEN
Solar/Wind Harmer
10.53
971177AH1-047 GEN
Solar/Wind Harmer
4.195
274823ROCKFORD ;21
Adder
13.762
957201AF2-014 GEN
Solar/Wind Helper
8.626
270317AD1-130_GEN
Solar/Wind Helper
4.234
966831AG1-554 GEN
Solar/Wind Helper
0.892
270284AF1-227 GEN1
Solar/Wind Helper
2.01
270286AF1-227 GEN2
Solar/Wind Helper
0.737
270287AF1-227 GEN3
Solar/Wind Helper
0.737
270499AE1-146 GEN
Solar/Wind Helper
1.982
945641AF1-229 GEN
Solar/Wind Helper
0.956
971411AH1-196 GEN
Solar/Wind Harmer
5.712
970583AG2-370 GEN
50/50
2.812
960851AF2-376 GEN
50/50
2.102
24641605TWIN BRNCH
50/50
0.016
959331AF2-224 GEN
Solar/Wind Harmer
19.764
965021AG1-366 GEN
Solar/Wind Harmer
4.596
970031AG2-029 GEN
Solar/Wind Harmer
36.406
270043AE2-236 GEN
Solar/Wind Harmer
6.429
270191TR4_S_V150
Solar/Wind Harmer
3.09
270247TR4_N_V136
Solar/Wind Harmer
0.876
944531AF1-118 GEN
Solar/Wind Harmer
35.621
971617AH1-308 GEN
Solar/Wind Harmer
5.211
247643Z2-116 C
Solar/Wind Harmer
0.062
945111AF1-176 GEN
Solar/Wind Harmer
4.869
970349AG2-230 GEN
Solar/Wind Harmer
12.648
24642205MAYFLWER
Adder
0.532
24441205WTRV SLR C
Solar/Wind Harmer
0.106
970513AG2-328 GEN
Solar/Wind Harmer
13.899
970517AG2-330 GEN
Solar/Wind Harmer
12.606
972231SS25-0005
Solar/Wind Harmer
7.33
972181SS23-001
Solar/Wind Harmer
4.582
274752CRETE EC ;2U
Adder
3.775
274753CRETE EC ;3U
Adder
3.775
274724RIVER EC ;11
Adder
13.63
270535AF1-215 GEN1
Solar/Wind Harmer
3.466
247604X1-042
Adder
0.317
274772LINCOLN ;3U
Adder
4.718
274802UNIV PARK;5U
Adder
4.409
274826FISK ;BP
Adder
8.271
274800UNIV PARK;3U
Adder
4.397
972038AH1-567 GEN2
Adder
0.275
276772AC2-154 GEN
Solar/Wind Harmer
2.101
276806AD2-047 C O1
Solar/Wind Harmer
8.058
970941AG2-585 GEN
Solar/Wind Harmer
9.416
964401AG1-302 GEN
Solar/Wind Harmer
6.822
972228AH1-698 GEN2
Adder
2.782
970707AG2-453 GEN
Solar/Wind Harmer
20.967
276897AD1-100 C
Solar/Wind Harmer
21.65
939351AE1-166 GEN
Solar/Wind Harmer
4.424
274676JOLIET 29;8U
Adder
22.066
276893AG1-478 C
Solar/Wind Harmer
0.311
274730ELWOOD EC;6P
Adder
12.229
274734ELWOOD EC;8P
Adder
12.229
274736ELWOOD EC;9P
Adder
12.229
274729ELWOOD EC;1P
Adder
12.229
959141AF2-205 GEN
Solar/Wind Harmer
4.486
943121AE2-341 GEN
Solar/Wind Harmer
11.036
943591AF1-030 GEN
Solar/Wind Harmer
7.358
247642Z2-115 C
Solar/Wind Harmer
0.047
276694AA1-018 GEN2
Solar/Wind Harmer
4.613
274682WAUKEGAN ;7U
Adder
13.074
970289AG2-191 GEN
Solar/Wind Harmer
0.556
970291AG2-192 GEN
Solar/Wind Harmer
0.506
276805AD2-038 GEN
Solar/Wind Harmer
3.705
958821AF2-173 GEN
Solar/Wind Harmer
10.069
270004AE1-209 GEN
Solar/Wind Harmer
3.931
274872LEEDK;1U
Solar/Wind Harmer
0.184
972236AH1-702 GEN2
Adder
1.545
274760LEE CO EC;1U
Adder
6.463
274767LEE CO EC;8U
Adder
6.387
24728705AND G3
Adder
4.402
24728505AND G1
Adder
2.105
270485AE1-090_GEN
Solar/Wind Helper
0.333
942871AE2-306 GEN
Solar/Wind Helper
0.459
270541AE2-072 C
Solar/Wind Helper
0.95
970615AG2-402 GEN
50/50
4.596
24729405KEY G3
50/50
0.372
24729305KEY G2
50/50
0.365
24729205KEY G1
50/50
0.364
247620Y3-023
50/50
0.468
970611AG2-400 GEN
Solar/Wind Harmer
19.764
942221AE2-234 GEN
Solar/Wind Harmer
0.72
944541AF1-119 GEN
Solar/Wind Harmer
3.812
960971AF2-388 GEN
Solar/Wind Harmer
9.948
270216AD2-079_GEN
Solar/Wind Harmer
0.542
960981AF2-389 GEN
Solar/Wind Harmer
1.28
957891AF2-083 GEN
Solar/Wind Harmer
2.854
961051AF2-396 GEN
Solar/Wind Harmer
13.326
961051AF2-396 GEN
Solar/Wind Harmer
6.198
270526AF1-158 GEN
Solar/Wind Harmer
3.75
24441505OLIV SLR
Solar/Wind Harmer
0.11
965681AG1-436 GEN
Solar/Wind Harmer
10.041
965791AG1-447 GEN
Solar/Wind Harmer
5.137
270599AE1-208 GEN
Solar/Wind Harmer
6.461
270031AE2-169
Solar/Wind Harmer
6.461
970321AG2-212 GEN
Solar/Wind Harmer
13.899
274808UNIV PK N;4U
Adder
3.809
274770LINCOLN ;1U
Adder
4.718
274771LINCOLN ;2U
Adder
4.718
274803UNIV PARK;6U
Adder
4.409
274888KELLY CRK;1U
Solar/Wind Harmer
4.447
274887GEN-1.85
Solar/Wind Harmer
4.015
276843GEN-1.7
Solar/Wind Harmer
0.432
958011AF2-095 GEN
Solar/Wind Harmer
10.847
972259AH1-714 GEN
Adder
14.289
274674JOLIET 9 ;6U
Adder
11.46
274847GR RIDGE ;BU
Solar/Wind Harmer
3.744
971573AH1-285 GEN
Solar/Wind Harmer
6.295
958481AF2-142 GEN
Solar/Wind Harmer
10.965
274861TOP CROP ;1U
Solar/Wind Harmer
4.428
274862TOP CROP ;2U
Solar/Wind Harmer
3.697
274696ROCKY RD ;4P
Adder
8.294
274695ROCKY RD ;2P
Adder
8.103
274693ROCKY RD ;1P
Adder
8.023
274697ROCKY RD ;3P
Adder
2.201
274683WAUKEGAN ;8U
Adder
15.31
274683WAUKEGAN ;8U
Adder
12.906
945421AF1-207 GEN
Solar/Wind Harmer
10.147
957841AF2-078 GEN
Solar/Wind Harmer
4.367
962691AG1-118 GEN
Solar/Wind Harmer
21.67
958491AF2-143 GEN
Solar/Wind Harmer
10.834
970921AG2-575 GEN
Solar/Wind Harmer
7.206
970921AG2-575 GEN
Solar/Wind Harmer
1.676
274879MINONK ;1U
Solar/Wind Harmer
4.845
942991AE2-321 GEN
Solar/Wind Harmer
7.162
274764LEE CO EC;5U
Adder
6.478
274765LEE CO EC;6U
Adder
6.478
274762LEE CO EC;3U
Adder
6.463
274763LEE CO EC;4U
Adder
6.402
972267AH1-718 GEN
Adder
2.865
247621Y3-024
Adder
0.162
246938BC-WTG3
Solar/Wind Helper
11.1
246937BC-WTG2
Solar/Wind Helper
10.912
270224U2-072_GEN2
Solar/Wind Helper
0.903
270227U2-072_GEN3
Solar/Wind Helper
0.903
270228U2-072_GEN4
Solar/Wind Helper
0.903
270231U2-072_GEN5
Solar/Wind Helper
0.903
270471AD2-092_GEN
Solar/Wind Helper
0.949
253378AE2-206_GEN
Solar/Wind Helper
0.705
276820AF1-078_GEN
Solar/Wind Helper
0.329
241960AC2-195 GEN
Solar/Wind Helper
0.731
960861AF2-377 GEN
50/50
2.397
970521AG2-332 GEN
50/50
10.933
24639705ELKHART HY
50/50
0.151
965011AG1-365 GEN
Solar/Wind Harmer
19.764
270063AE2-323 C
Solar/Wind Harmer
2.365
247521TR3_G114
Solar/Wind Harmer
3.464
270246TR4_N_V150
Solar/Wind Harmer
0.876
944231AF1-091 GEN
Solar/Wind Harmer
3.77
965651AG1-433 GEN
Solar/Wind Harmer
4.974
24695305TIMB G C
Solar/Wind Harmer
4.975
958861AF2-177 GEN
Solar/Wind Harmer
9.665
945111AF1-176 GEN
Solar/Wind Harmer
15.363
270505AE1-170 C O1
Solar/Wind Harmer
12.602
945371AF1-202 GEN
Solar/Wind Harmer
5.825
270449AD2-020 GEN
Solar/Wind Harmer
2.318
943021AE2-325 GEN
Solar/Wind Harmer
3.011
970245AG2-165 GEN
Solar/Wind Harmer
13.899
970373AG2-245 GEN
Solar/Wind Harmer
16.282
274751CRETE EC ;1U
Adder
3.775
274754CRETE EC ;4U
Adder
3.775
274723RIVER EC ;12
Adder
13.797
274812UNIV PK N;8U
Adder
3.826
276164X3-005 C
Solar/Wind Harmer
0.536
270055AF2-134 C O1
Solar/Wind Harmer
2.311
972207SS24-0001
Solar/Wind Harmer
16.774
274773LINCOLN ;4U
Adder
4.718
274774LINCOLN ;5U
Adder
4.718
274801UNIV PARK;4U
Adder
4.397
276776AD2-060 GEN
Solar/Wind Harmer
0.318
958381AF2-132 GEN
Solar/Wind Harmer
6.822
964861AG1-349 GEN
Solar/Wind Harmer
5.901
971917AH1-482 GEN
Solar/Wind Harmer
6.81
941551AE2-152 GEN
Solar/Wind Harmer
3.384
274676JOLIET 29;8U
Adder
22.883
274674JOLIET 9 ;6U
Adder
11.46
274732ELWOOD EC;7P
Adder
12.229
274871GR RIDGE ;2U
Solar/Wind Harmer
5.692
940581AE2-045 GEN
Solar/Wind Harmer
7.515
971605AH1-302 GEN
Solar/Wind Harmer
6.426
274745AC1-111 GEN9
Adder
4.111
276691AA1-018 GEN1
Solar/Wind Harmer
0.34
274682WAUKEGAN ;7U
Adder
13.074
274828WAUKEGAN ;BP
Adder
8.025
970291AG2-192 GEN
Solar/Wind Harmer
0.942
960751AF2-366 GEN
Solar/Wind Harmer
2.068
962781AG1-127 GEN
Solar/Wind Harmer
6.853
939401AE1-172 GEN
Solar/Wind Harmer
10.037
276901AD2-066 C O1
Solar/Wind Harmer
2.53
270005AE1-210 C O1
Solar/Wind Harmer
3.931
965031AG1-367 GEN
Solar/Wind Harmer
7.192
274872LEEDK;1U
Solar/Wind Harmer
5.906
270032AE2-172
Solar/Wind Harmer
3.332
971997AH1-543 GEN
Solar/Wind Harmer
11.263
274822ROCKFORD ;11
Adder
13.863
972235AH1-702 GEN1
Adder
1.776
274761LEE CO EC;2U
Adder
6.463
274766LEE CO EC;7U
Adder
6.387
24728605AND G2
Adder
2.105
246936BC-WTG1
Solar/Wind Helper
10.912
270462AD2-086
Solar/Wind Helper
3.823
270223U2-072_GEN1
Solar/Wind Helper
0.903
270578AF1-285 GEN2
Solar/Wind Helper
0.612
270391AF1-285 GEN3
Solar/Wind Helper
0.612
247522W1-056 GEN
Solar/Wind Helper
1.188
960841AF2-375 GEN
Solar/Wind Helper
1.193
270349AD2-093_GEN
Solar/Wind Helper
0.949
944201AF1-088_MTX
Adder
57.685
957141AF2-008_MTX
Adder
28.842
990497J1323
External Queue
1.5705512762069702
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.871
MECLTFEXP_MEC->PJM
CLTF
9.992
SIGELTFEXP_SIGE->PJM
CLTF
0.208
LAGNLTFEXP_LAGN->PJM
CLTF
6.288
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.588
TVALTFEXP_TVA->PJM
CLTF
2.587
CPLELTFEXP_CPLE->PJM
CLTF
0.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.368
NYPJM->LTFIMP_NY
CLTF
1.141
LGEELTFEXP_LGEE->PJM
CLTF
1.935
WECLTFEXP_WEC->PJM
CLTF
2.689
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.28 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2210.83
MW Contribution:36.79
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.521
24729505KEY G4
50/50
6.883
24653605MOTTVILLE
50/50
0.004
270144AC1-141 ST1_
50/50
1.82
963791AG1-232 GEN
Solar/Wind Harmer
16.926
965041AG1-368 GEN
Solar/Wind Harmer
12.293
270071AF1-092 GEN
Solar/Wind Harmer
16.475
965051AG1-369 GEN
Solar/Wind Harmer
5.256
958711AF2-162 GEN
Solar/Wind Harmer
0.931
270024AE2-089 GEN
Solar/Wind Harmer
4.271
965101AG1-375 GEN
Solar/Wind Harmer
8.942
971771AH1-392 GEN
Solar/Wind Harmer
7.737
971347AH1-153 GEN
Solar/Wind Harmer
12.776
945581AF1-223 GEN
Solar/Wind Harmer
3.83
971769AH1-391 GEN
Solar/Wind Harmer
8.28
944161AF1-084 GEN
Solar/Wind Harmer
1.822
960681AF2-359 GEN
Solar/Wind Harmer
3.065
274814UNIV PK N;0U
Adder
3.891
274807UNIV PK N;3U
Adder
3.883
274805UNIV PK N;1U
Adder
3.866
274811UNIV PK N;7U
Adder
3.858
270536AF1-215 GEN2
Solar/Wind Harmer
3.496
274775LINCOLN ;6U
Adder
4.756
274776LINCOLN ;7U
Adder
4.756
274777LINCOLN ;8U
Adder
4.756
972037AH1-567 GEN1
Adder
0.14
274827FISK ;RP
Adder
5.909
960591AF2-350 GEN
Solar/Wind Harmer
7.593
972227AH1-698 GEN1
Adder
1.975
274687WILL CNTY;4U
Adder
21.05
274687WILL CNTY;4U
Adder
21.05
958391AF2-133 GEN
Solar/Wind Harmer
6.825
274675JOLIET 29;7U
Adder
23.063
274675JOLIET 29;7U
Adder
22.239
274731ELWOOD EC;2P
Adder
12.325
274733ELWOOD EC;3P
Adder
12.325
274735ELWOOD EC;4P
Adder
12.325
274728ELWOOD EC;5P
Adder
12.325
970833AG2-524 GEN
Solar/Wind Harmer
6.517
970833AG2-524 GEN
Solar/Wind Harmer
3.031
274746AC1-111 G10
Adder
4.142
274744AC1-111 GEN8
Adder
4.142
965461AG1-414 GEN
Solar/Wind Harmer
1.661
970289AG2-191 GEN
Solar/Wind Harmer
1.391
270594AE1-207 GEN
Solar/Wind Harmer
10.648
276868AE1-113 GEN
Solar/Wind Harmer
7.319
276882AE2-255 GEN
Solar/Wind Harmer
2.44
971177AH1-047 GEN
Solar/Wind Harmer
4.224
274823ROCKFORD ;21
Adder
13.855
957201AF2-014 GEN
Solar/Wind Helper
8.571
270317AD1-130_GEN
Solar/Wind Helper
4.044
966831AG1-554 GEN
Solar/Wind Helper
0.856
270284AF1-227 GEN1
Solar/Wind Helper
1.824
270286AF1-227 GEN2
Solar/Wind Helper
0.669
270287AF1-227 GEN3
Solar/Wind Helper
0.669
270499AE1-146 GEN
Solar/Wind Helper
1.895
945641AF1-229 GEN
Solar/Wind Helper
0.904
971411AH1-196 GEN
Solar/Wind Harmer
5.751
970583AG2-370 GEN
50/50
2.859
960851AF2-376 GEN
50/50
2.155
24641605TWIN BRNCH
50/50
0.016
270142AC1-141 CT1_
50/50
2.055
959331AF2-224 GEN
Solar/Wind Harmer
19.942
965021AG1-366 GEN
Solar/Wind Harmer
4.638
970031AG2-029 GEN
Solar/Wind Harmer
36.788
270043AE2-236 GEN
Solar/Wind Harmer
6.497
270191TR4_S_V150
Solar/Wind Harmer
3.157
270247TR4_N_V136
Solar/Wind Harmer
0.895
944531AF1-118 GEN
Solar/Wind Harmer
36.002
971617AH1-308 GEN
Solar/Wind Harmer
5.291
247643Z2-116 C
Solar/Wind Harmer
0.063
945111AF1-176 GEN
Solar/Wind Harmer
4.927
970349AG2-230 GEN
Solar/Wind Harmer
12.776
24642205MAYFLWER
Adder
0.538
24441205WTRV SLR C
Solar/Wind Harmer
0.107
970513AG2-328 GEN
Solar/Wind Harmer
14.009
970517AG2-330 GEN
Solar/Wind Harmer
12.706
972231SS25-0005
Solar/Wind Harmer
7.393
972181SS23-001
Solar/Wind Harmer
4.621
274752CRETE EC ;2U
Adder
3.808
274753CRETE EC ;3U
Adder
3.808
274724RIVER EC ;11
Adder
13.745
247604X1-042
Adder
0.322
270535AF1-215 GEN1
Solar/Wind Harmer
3.496
274772LINCOLN ;3U
Adder
4.756
274802UNIV PARK;5U
Adder
4.445
274826FISK ;BP
Adder
8.338
274800UNIV PARK;3U
Adder
4.433
972038AH1-567 GEN2
Adder
0.277
276772AC2-154 GEN
Solar/Wind Harmer
2.118
276806AD2-047 C O1
Solar/Wind Harmer
8.123
970941AG2-585 GEN
Solar/Wind Harmer
9.492
964401AG1-302 GEN
Solar/Wind Harmer
6.878
972228AH1-698 GEN2
Adder
2.805
970707AG2-453 GEN
Solar/Wind Harmer
21.132
276897AD1-100 C
Solar/Wind Harmer
21.821
939351AE1-166 GEN
Solar/Wind Harmer
4.459
274676JOLIET 29;8U
Adder
22.239
276893AG1-478 C
Solar/Wind Harmer
0.313
274729ELWOOD EC;1P
Adder
12.325
274730ELWOOD EC;6P
Adder
12.325
274734ELWOOD EC;8P
Adder
12.325
274736ELWOOD EC;9P
Adder
12.325
959141AF2-205 GEN
Solar/Wind Harmer
4.522
943121AE2-341 GEN
Solar/Wind Harmer
11.12
943591AF1-030 GEN
Solar/Wind Harmer
7.413
247642Z2-115 C
Solar/Wind Harmer
0.047
276694AA1-018 GEN2
Solar/Wind Harmer
4.648
274682WAUKEGAN ;7U
Adder
13.17
970289AG2-191 GEN
Solar/Wind Harmer
0.562
970291AG2-192 GEN
Solar/Wind Harmer
0.511
958821AF2-173 GEN
Solar/Wind Harmer
10.193
270004AE1-209 GEN
Solar/Wind Harmer
3.979
276805AD2-038 GEN
Solar/Wind Harmer
3.732
274872LEEDK;1U
Solar/Wind Harmer
0.185
972236AH1-702 GEN2
Adder
1.555
274760LEE CO EC;1U
Adder
6.505
274767LEE CO EC;8U
Adder
6.428
24728705AND G3
Adder
4.445
24728505AND G1
Adder
2.125
270485AE1-090_GEN
Solar/Wind Helper
0.318
942871AE2-306 GEN
Solar/Wind Helper
0.434
270541AE2-072 C
Solar/Wind Helper
0.891
970615AG2-402 GEN
50/50
4.638
24729405KEY G3
50/50
0.376
24729305KEY G2
50/50
0.369
24729205KEY G1
50/50
0.368
247620Y3-023
50/50
0.473
970611AG2-400 GEN
Solar/Wind Harmer
19.942
942221AE2-234 GEN
Solar/Wind Harmer
0.73
944541AF1-119 GEN
Solar/Wind Harmer
3.855
960971AF2-388 GEN
Solar/Wind Harmer
10.059
270216AD2-079_GEN
Solar/Wind Harmer
0.548
960981AF2-389 GEN
Solar/Wind Harmer
1.295
957891AF2-083 GEN
Solar/Wind Harmer
2.888
961051AF2-396 GEN
Solar/Wind Harmer
13.49
961051AF2-396 GEN
Solar/Wind Harmer
6.274
270526AF1-158 GEN
Solar/Wind Harmer
3.79
24441505OLIV SLR
Solar/Wind Harmer
0.111
965681AG1-436 GEN
Solar/Wind Harmer
10.141
965791AG1-447 GEN
Solar/Wind Harmer
5.189
270599AE1-208 GEN
Solar/Wind Harmer
6.539
270031AE2-169
Solar/Wind Harmer
6.539
970321AG2-212 GEN
Solar/Wind Harmer
14.009
274808UNIV PK N;4U
Adder
3.841
274770LINCOLN ;1U
Adder
4.756
274771LINCOLN ;2U
Adder
4.756
274803UNIV PARK;6U
Adder
4.445
274888KELLY CRK;1U
Solar/Wind Harmer
4.483
274887GEN-1.85
Solar/Wind Harmer
4.047
276843GEN-1.7
Solar/Wind Harmer
0.435
958011AF2-095 GEN
Solar/Wind Harmer
10.934
972259AH1-714 GEN
Adder
14.402
274674JOLIET 9 ;6U
Adder
11.55
274847GR RIDGE ;BU
Solar/Wind Harmer
3.773
971573AH1-285 GEN
Solar/Wind Harmer
6.342
958481AF2-142 GEN
Solar/Wind Harmer
11.047
274861TOP CROP ;1U
Solar/Wind Harmer
4.461
274862TOP CROP ;2U
Solar/Wind Harmer
3.725
274695ROCKY RD ;2P
Adder
8.163
274693ROCKY RD ;1P
Adder
8.082
274697ROCKY RD ;3P
Adder
2.217
274696ROCKY RD ;4P
Adder
8.355
274683WAUKEGAN ;8U
Adder
15.422
274683WAUKEGAN ;8U
Adder
13
945421AF1-207 GEN
Solar/Wind Harmer
10.221
957841AF2-078 GEN
Solar/Wind Harmer
4.398
962691AG1-118 GEN
Solar/Wind Harmer
21.826
958491AF2-143 GEN
Solar/Wind Harmer
10.913
970921AG2-575 GEN
Solar/Wind Harmer
7.258
970921AG2-575 GEN
Solar/Wind Harmer
1.688
274879MINONK ;1U
Solar/Wind Harmer
4.88
942991AE2-321 GEN
Solar/Wind Harmer
7.212
274764LEE CO EC;5U
Adder
6.52
274765LEE CO EC;6U
Adder
6.52
274762LEE CO EC;3U
Adder
6.505
274763LEE CO EC;4U
Adder
6.443
972267AH1-718 GEN
Adder
2.883
247621Y3-024
Adder
0.165
246938BC-WTG3
Solar/Wind Helper
11.029
246937BC-WTG2
Solar/Wind Helper
10.843
270224U2-072_GEN2
Solar/Wind Helper
0.855
270227U2-072_GEN3
Solar/Wind Helper
0.855
270228U2-072_GEN4
Solar/Wind Helper
0.855
270231U2-072_GEN5
Solar/Wind Helper
0.855
270471AD2-092_GEN
Solar/Wind Helper
0.817
253378AE2-206_GEN
Solar/Wind Helper
0.657
276820AF1-078_GEN
Solar/Wind Helper
0.307
241960AC2-195 GEN
Solar/Wind Helper
0.657
960861AF2-377 GEN
50/50
2.449
970521AG2-332 GEN
50/50
11.057
24639705ELKHART HY
50/50
0.153
270143AC1-141 CT2_
50/50
2.055
965011AG1-365 GEN
Solar/Wind Harmer
19.942
270063AE2-323 C
Solar/Wind Harmer
2.392
247521TR3_G114
Solar/Wind Harmer
3.539
270246TR4_N_V150
Solar/Wind Harmer
0.895
944231AF1-091 GEN
Solar/Wind Harmer
3.837
24695305TIMB G C
Solar/Wind Harmer
5.099
965651AG1-433 GEN
Solar/Wind Harmer
5.029
958861AF2-177 GEN
Solar/Wind Harmer
9.774
945111AF1-176 GEN
Solar/Wind Harmer
15.546
270505AE1-170 C O1
Solar/Wind Harmer
12.753
945371AF1-202 GEN
Solar/Wind Harmer
5.892
270449AD2-020 GEN
Solar/Wind Harmer
2.346
943021AE2-325 GEN
Solar/Wind Harmer
3.049
970245AG2-165 GEN
Solar/Wind Harmer
14.009
970373AG2-245 GEN
Solar/Wind Harmer
16.431
274751CRETE EC ;1U
Adder
3.808
274754CRETE EC ;4U
Adder
3.808
274723RIVER EC ;12
Adder
13.914
274812UNIV PK N;8U
Adder
3.858
276164X3-005 C
Solar/Wind Harmer
0.541
270055AF2-134 C O1
Solar/Wind Harmer
2.331
972207SS24-0001
Solar/Wind Harmer
16.91
274773LINCOLN ;4U
Adder
4.756
274774LINCOLN ;5U
Adder
4.756
274801UNIV PARK;4U
Adder
4.433
276776AD2-060 GEN
Solar/Wind Harmer
0.321
958381AF2-132 GEN
Solar/Wind Harmer
6.878
964861AG1-349 GEN
Solar/Wind Harmer
5.95
971917AH1-482 GEN
Solar/Wind Harmer
6.867
941551AE2-152 GEN
Solar/Wind Harmer
3.41
274676JOLIET 29;8U
Adder
23.063
274674JOLIET 9 ;6U
Adder
11.55
274732ELWOOD EC;7P
Adder
12.325
274871GR RIDGE ;2U
Solar/Wind Harmer
5.736
940581AE2-045 GEN
Solar/Wind Harmer
7.574
971605AH1-302 GEN
Solar/Wind Harmer
6.476
274745AC1-111 GEN9
Adder
4.142
276691AA1-018 GEN1
Solar/Wind Harmer
0.343
274682WAUKEGAN ;7U
Adder
13.17
970291AG2-192 GEN
Solar/Wind Harmer
0.952
274828WAUKEGAN ;BP
Adder
8.084
270005AE1-210 C O1
Solar/Wind Harmer
3.979
965031AG1-367 GEN
Solar/Wind Harmer
7.281
960751AF2-366 GEN
Solar/Wind Harmer
2.082
962781AG1-127 GEN
Solar/Wind Harmer
6.902
939401AE1-172 GEN
Solar/Wind Harmer
10.111
276901AD2-066 C O1
Solar/Wind Harmer
2.548
270032AE2-172
Solar/Wind Harmer
3.37
274872LEEDK;1U
Solar/Wind Harmer
5.948
971997AH1-543 GEN
Solar/Wind Harmer
11.343
274822ROCKFORD ;11
Adder
13.956
972235AH1-702 GEN1
Adder
1.788
274761LEE CO EC;2U
Adder
6.505
274766LEE CO EC;7U
Adder
6.428
24728605AND G2
Adder
2.125
246936BC-WTG1
Solar/Wind Helper
10.843
270462AD2-086
Solar/Wind Helper
3.651
270223U2-072_GEN1
Solar/Wind Helper
0.855
270578AF1-285 GEN2
Solar/Wind Helper
0.579
270391AF1-285 GEN3
Solar/Wind Helper
0.579
247522W1-056 GEN
Solar/Wind Helper
1.138
960841AF2-375 GEN
Solar/Wind Helper
1.139
270349AD2-093_GEN
Solar/Wind Helper
0.817
944201AF1-088_MTX
Adder
57.673
957141AF2-008_MTX
Adder
28.836
990497J1323
External Queue
1.5914489030838013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.466
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.567
MECLTFEXP_MEC->PJM
CLTF
10.019
SIGELTFEXP_SIGE->PJM
CLTF
0.208
LAGNLTFEXP_LAGN->PJM
CLTF
6.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.094
TVALTFEXP_TVA->PJM
CLTF
2.49
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.858
NYPJM->LTFIMP_NY
CLTF
1.126
LGEELTFEXP_LGEE->PJM
CLTF
1.931
WECLTFEXP_WEC->PJM
CLTF
2.707
AG2-052LTFEXP_AG2-052->PJM
LTF
0.175
AH1-155LTFEXP_AH1-155->PJM
LTF
0.263

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.14 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2173.64
MW Contribution:35.82
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
2.34
970521AG2-332 GEN
50/50
10.717
24639705ELKHART HY
50/50
0.148
965011AG1-365 GEN
Solar/Wind Harmer
19.54
270063AE2-323 C
Solar/Wind Harmer
2.322
247521TR3_G114
Solar/Wind Harmer
3.382
270246TR4_N_V150
Solar/Wind Harmer
0.855
944231AF1-091 GEN
Solar/Wind Harmer
3.694
965651AG1-433 GEN
Solar/Wind Harmer
4.874
24695305TIMB G C
Solar/Wind Harmer
4.842
958861AF2-177 GEN
Solar/Wind Harmer
9.465
945111AF1-176 GEN
Solar/Wind Harmer
15.039
270505AE1-170 C O1
Solar/Wind Harmer
12.331
945371AF1-202 GEN
Solar/Wind Harmer
5.699
270449AD2-020 GEN
Solar/Wind Harmer
2.267
943021AE2-325 GEN
Solar/Wind Harmer
2.946
970245AG2-165 GEN
Solar/Wind Harmer
13.574
970373AG2-245 GEN
Solar/Wind Harmer
15.903
274751CRETE EC ;1U
Adder
3.688
274754CRETE EC ;4U
Adder
3.688
274723RIVER EC ;12
Adder
13.475
274812UNIV PK N;8U
Adder
3.736
276164X3-005 C
Solar/Wind Harmer
0.524
270055AF2-134 C O1
Solar/Wind Harmer
2.256
972207SS24-0001
Solar/Wind Harmer
16.378
274773LINCOLN ;4U
Adder
4.607
274774LINCOLN ;5U
Adder
4.607
274801UNIV PARK;4U
Adder
4.293
276776AD2-060 GEN
Solar/Wind Harmer
0.311
958381AF2-132 GEN
Solar/Wind Harmer
6.658
964861AG1-349 GEN
Solar/Wind Harmer
5.76
971917AH1-482 GEN
Solar/Wind Harmer
6.646
941551AE2-152 GEN
Solar/Wind Harmer
3.302
274676JOLIET 29;8U
Adder
22.335
274674JOLIET 9 ;6U
Adder
11.185
274732ELWOOD EC;7P
Adder
11.936
274871GR RIDGE ;2U
Solar/Wind Harmer
5.555
940581AE2-045 GEN
Solar/Wind Harmer
7.331
971605AH1-302 GEN
Solar/Wind Harmer
6.269
274745AC1-111 GEN9
Adder
4.011
276691AA1-018 GEN1
Solar/Wind Harmer
0.332
274682WAUKEGAN ;7U
Adder
12.754
274828WAUKEGAN ;BP
Adder
7.829
970291AG2-192 GEN
Solar/Wind Harmer
0.919
960751AF2-366 GEN
Solar/Wind Harmer
2.017
962781AG1-127 GEN
Solar/Wind Harmer
6.684
939401AE1-172 GEN
Solar/Wind Harmer
9.789
276901AD2-066 C O1
Solar/Wind Harmer
2.467
270005AE1-210 C O1
Solar/Wind Harmer
3.834
965031AG1-367 GEN
Solar/Wind Harmer
7.016
274872LEEDK;1U
Solar/Wind Harmer
5.76
270032AE2-172
Solar/Wind Harmer
3.249
971997AH1-543 GEN
Solar/Wind Harmer
10.984
274822ROCKFORD ;11
Adder
13.515
972235AH1-702 GEN1
Adder
1.732
274761LEE CO EC;2U
Adder
6.299
274766LEE CO EC;7U
Adder
6.225
24728605AND G2
Adder
2.04
246936BC-WTG1
Solar/Wind Helper
10.981
270462AD2-086
Solar/Wind Helper
3.987
270223U2-072_GEN1
Solar/Wind Helper
0.949
270578AF1-285 GEN2
Solar/Wind Helper
0.643
970583AG2-370 GEN
50/50
2.757
960851AF2-376 GEN
50/50
2.046
24641605TWIN BRNCH
50/50
0.015
959331AF2-224 GEN
Solar/Wind Harmer
19.54
965021AG1-366 GEN
Solar/Wind Harmer
4.544
970031AG2-029 GEN
Solar/Wind Harmer
35.817
270043AE2-236 GEN
Solar/Wind Harmer
6.32
270191TR4_S_V150
Solar/Wind Harmer
3.017
270247TR4_N_V136
Solar/Wind Harmer
0.855
944531AF1-118 GEN
Solar/Wind Harmer
34.962
971617AH1-308 GEN
Solar/Wind Harmer
5.098
247643Z2-116 C
Solar/Wind Harmer
0.061
945111AF1-176 GEN
Solar/Wind Harmer
4.766
970349AG2-230 GEN
Solar/Wind Harmer
12.375
24642205MAYFLWER
Adder
0.52
24441205WTRV SLR C
Solar/Wind Harmer
0.103
970513AG2-328 GEN
Solar/Wind Harmer
13.574
970517AG2-330 GEN
Solar/Wind Harmer
12.311
972231SS25-0005
Solar/Wind Harmer
7.16
972181SS23-001
Solar/Wind Harmer
4.475
274752CRETE EC ;2U
Adder
3.688
274753CRETE EC ;3U
Adder
3.688
274724RIVER EC ;11
Adder
13.312
270535AF1-215 GEN1
Solar/Wind Harmer
3.384
247604X1-042
Adder
0.31
274772LINCOLN ;3U
Adder
4.607
274802UNIV PARK;5U
Adder
4.305
274826FISK ;BP
Adder
8.075
274800UNIV PARK;3U
Adder
4.293
972038AH1-567 GEN2
Adder
0.269
276772AC2-154 GEN
Solar/Wind Harmer
2.051
276806AD2-047 C O1
Solar/Wind Harmer
7.867
970941AG2-585 GEN
Solar/Wind Harmer
9.192
964401AG1-302 GEN
Solar/Wind Harmer
6.658
972228AH1-698 GEN2
Adder
2.716
970707AG2-453 GEN
Solar/Wind Harmer
20.466
276897AD1-100 C
Solar/Wind Harmer
21.131
939351AE1-166 GEN
Solar/Wind Harmer
4.318
274676JOLIET 29;8U
Adder
21.538
276893AG1-478 C
Solar/Wind Harmer
0.303
274729ELWOOD EC;1P
Adder
11.935
274730ELWOOD EC;6P
Adder
11.936
274734ELWOOD EC;8P
Adder
11.936
274736ELWOOD EC;9P
Adder
11.936
959141AF2-205 GEN
Solar/Wind Harmer
4.377
943121AE2-341 GEN
Solar/Wind Harmer
10.769
943591AF1-030 GEN
Solar/Wind Harmer
7.179
247642Z2-115 C
Solar/Wind Harmer
0.046
276694AA1-018 GEN2
Solar/Wind Harmer
4.501
274682WAUKEGAN ;7U
Adder
12.754
970289AG2-191 GEN
Solar/Wind Harmer
0.542
970291AG2-192 GEN
Solar/Wind Harmer
0.493
276805AD2-038 GEN
Solar/Wind Harmer
3.614
958821AF2-173 GEN
Solar/Wind Harmer
9.822
270004AE1-209 GEN
Solar/Wind Harmer
3.834
274872LEEDK;1U
Solar/Wind Harmer
0.179
972236AH1-702 GEN2
Adder
1.506
274760LEE CO EC;1U
Adder
6.299
274767LEE CO EC;8U
Adder
6.225
24728705AND G3
Adder
4.266
24728505AND G1
Adder
2.04
270485AE1-090_GEN
Solar/Wind Helper
0.347
942871AE2-306 GEN
Solar/Wind Helper
0.482
270541AE2-072 C
Solar/Wind Helper
0.989
270391AF1-285 GEN3
Solar/Wind Helper
0.643
247522W1-056 GEN
Solar/Wind Helper
1.213
960841AF2-375 GEN
Solar/Wind Helper
1.218
270349AD2-093_GEN
Solar/Wind Helper
1.087
971599AH1-298 GEN
50/50
10.246
24729505KEY G4
50/50
6.681
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
16.434
965041AG1-368 GEN
Solar/Wind Harmer
11.857
270071AF1-092 GEN
Solar/Wind Harmer
16.023
965051AG1-369 GEN
Solar/Wind Harmer
5.022
958711AF2-162 GEN
Solar/Wind Harmer
0.902
270024AE2-089 GEN
Solar/Wind Harmer
4.115
965101AG1-375 GEN
Solar/Wind Harmer
8.66
971771AH1-392 GEN
Solar/Wind Harmer
7.489
971347AH1-153 GEN
Solar/Wind Harmer
12.375
945581AF1-223 GEN
Solar/Wind Harmer
3.704
971769AH1-391 GEN
Solar/Wind Harmer
8.012
944161AF1-084 GEN
Solar/Wind Harmer
1.76
960681AF2-359 GEN
Solar/Wind Harmer
2.967
274814UNIV PK N;0U
Adder
3.769
274807UNIV PK N;3U
Adder
3.76
274805UNIV PK N;1U
Adder
3.744
274811UNIV PK N;7U
Adder
3.736
270536AF1-215 GEN2
Solar/Wind Harmer
3.384
274775LINCOLN ;6U
Adder
4.607
274776LINCOLN ;7U
Adder
4.607
274777LINCOLN ;8U
Adder
4.607
972037AH1-567 GEN1
Adder
0.135
274827FISK ;RP
Adder
5.723
960591AF2-350 GEN
Solar/Wind Harmer
7.354
972227AH1-698 GEN1
Adder
1.912
274687WILL CNTY;4U
Adder
20.386
274687WILL CNTY;4U
Adder
20.386
958391AF2-133 GEN
Solar/Wind Harmer
6.607
274675JOLIET 29;7U
Adder
22.336
274675JOLIET 29;7U
Adder
21.538
274731ELWOOD EC;2P
Adder
11.935
274733ELWOOD EC;3P
Adder
11.935
274735ELWOOD EC;4P
Adder
11.935
274728ELWOOD EC;5P
Adder
11.936
970833AG2-524 GEN
Solar/Wind Harmer
6.311
970833AG2-524 GEN
Solar/Wind Harmer
2.935
274746AC1-111 G10
Adder
4.011
274744AC1-111 GEN8
Adder
4.011
965461AG1-414 GEN
Solar/Wind Harmer
1.602
970289AG2-191 GEN
Solar/Wind Harmer
1.343
276868AE1-113 GEN
Solar/Wind Harmer
7.087
276882AE2-255 GEN
Solar/Wind Harmer
2.363
270594AE1-207 GEN
Solar/Wind Harmer
10.267
971177AH1-047 GEN
Solar/Wind Harmer
4.091
274823ROCKFORD ;21
Adder
13.417
957201AF2-014 GEN
Solar/Wind Helper
8.681
270317AD1-130_GEN
Solar/Wind Helper
4.417
966831AG1-554 GEN
Solar/Wind Helper
0.909
270284AF1-227 GEN1
Solar/Wind Helper
2.199
270286AF1-227 GEN2
Solar/Wind Helper
0.806
270287AF1-227 GEN3
Solar/Wind Helper
0.806
270499AE1-146 GEN
Solar/Wind Helper
2.027
945641AF1-229 GEN
Solar/Wind Helper
0.968
971411AH1-196 GEN
Solar/Wind Harmer
5.57
970615AG2-402 GEN
50/50
4.544
24729405KEY G3
50/50
0.365
24729305KEY G2
50/50
0.359
24729205KEY G1
50/50
0.357
247620Y3-023
50/50
0.459
970611AG2-400 GEN
Solar/Wind Harmer
19.54
942221AE2-234 GEN
Solar/Wind Harmer
0.706
944541AF1-119 GEN
Solar/Wind Harmer
3.735
960971AF2-388 GEN
Solar/Wind Harmer
9.747
270216AD2-079_GEN
Solar/Wind Harmer
0.531
960981AF2-389 GEN
Solar/Wind Harmer
1.253
957891AF2-083 GEN
Solar/Wind Harmer
2.793
961051AF2-396 GEN
Solar/Wind Harmer
13.04
961051AF2-396 GEN
Solar/Wind Harmer
6.065
270526AF1-158 GEN
Solar/Wind Harmer
3.668
24441505OLIV SLR
Solar/Wind Harmer
0.107
965681AG1-436 GEN
Solar/Wind Harmer
9.816
965791AG1-447 GEN
Solar/Wind Harmer
5.022
270599AE1-208 GEN
Solar/Wind Harmer
6.313
270031AE2-169
Solar/Wind Harmer
6.313
970321AG2-212 GEN
Solar/Wind Harmer
13.574
274808UNIV PK N;4U
Adder
3.72
274770LINCOLN ;1U
Adder
4.607
274771LINCOLN ;2U
Adder
4.607
274803UNIV PARK;6U
Adder
4.305
274888KELLY CRK;1U
Solar/Wind Harmer
4.342
274887GEN-1.85
Solar/Wind Harmer
3.92
276843GEN-1.7
Solar/Wind Harmer
0.422
958011AF2-095 GEN
Solar/Wind Harmer
10.589
972259AH1-714 GEN
Adder
13.948
274674JOLIET 9 ;6U
Adder
11.185
274847GR RIDGE ;BU
Solar/Wind Harmer
3.654
971573AH1-285 GEN
Solar/Wind Harmer
6.142
958481AF2-142 GEN
Solar/Wind Harmer
10.698
274861TOP CROP ;1U
Solar/Wind Harmer
4.32
274862TOP CROP ;2U
Solar/Wind Harmer
3.607
274695ROCKY RD ;2P
Adder
7.905
274693ROCKY RD ;1P
Adder
7.827
274697ROCKY RD ;3P
Adder
2.147
274696ROCKY RD ;4P
Adder
8.091
274683WAUKEGAN ;8U
Adder
14.936
274683WAUKEGAN ;8U
Adder
12.59
962691AG1-118 GEN
Solar/Wind Harmer
21.137
958491AF2-143 GEN
Solar/Wind Harmer
10.567
945421AF1-207 GEN
Solar/Wind Harmer
9.894
957841AF2-078 GEN
Solar/Wind Harmer
4.258
970921AG2-575 GEN
Solar/Wind Harmer
7.029
970921AG2-575 GEN
Solar/Wind Harmer
1.635
274879MINONK ;1U
Solar/Wind Harmer
4.725
942991AE2-321 GEN
Solar/Wind Harmer
6.984
274764LEE CO EC;5U
Adder
6.314
274765LEE CO EC;6U
Adder
6.314
274762LEE CO EC;3U
Adder
6.299
274763LEE CO EC;4U
Adder
6.24
972267AH1-718 GEN
Adder
2.792
247621Y3-024
Adder
0.157
246938BC-WTG3
Solar/Wind Helper
11.17
246937BC-WTG2
Solar/Wind Helper
10.981
270224U2-072_GEN2
Solar/Wind Helper
0.949
270227U2-072_GEN3
Solar/Wind Helper
0.949
270228U2-072_GEN4
Solar/Wind Helper
0.949
270231U2-072_GEN5
Solar/Wind Helper
0.949
270471AD2-092_GEN
Solar/Wind Helper
1.087
253378AE2-206_GEN
Solar/Wind Helper
0.738
276820AF1-078_GEN
Solar/Wind Helper
0.345
241960AC2-195 GEN
Solar/Wind Helper
0.737
944201AF1-088_MTX
Adder
55.652
957141AF2-008_MTX
Adder
27.826
990497J1323
External Queue
1.5632063150405884
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.962
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.281
MECLTFEXP_MEC->PJM
CLTF
9.703
SIGELTFEXP_SIGE->PJM
CLTF
0.2
LAGNLTFEXP_LAGN->PJM
CLTF
5.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.252
TVALTFEXP_TVA->PJM
CLTF
2.43
CPLELTFEXP_CPLE->PJM
CLTF
0.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.193
NYPJM->LTFIMP_NY
CLTF
1.069
LGEELTFEXP_LGEE->PJM
CLTF
1.827
WECLTFEXP_WEC->PJM
CLTF
2.621
AG2-052LTFEXP_AG2-052->PJM
LTF
0.169
AH1-155LTFEXP_AH1-155->PJM
LTF
0.254

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.78 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2115.3
MW Contribution:5.56
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.638
24729405KEY G3
50/50
0.376
24729305KEY G2
50/50
0.369
24729205KEY G1
50/50
0.368
247620Y3-023
50/50
0.473
270102X2-052 ST
50/50
1.304
270100X2-052 CT1
50/50
1.202
270101X2-052 CT2
50/50
1.202
970611AG2-400 GEN
Solar/Wind Harmer
13.913
970627AG2-408 GEN
Solar/Wind Harmer
4.174
942221AE2-234 GEN
Solar/Wind Harmer
0.035
944541AF1-119 GEN
Solar/Wind Harmer
0.43
960971AF2-388 GEN
Solar/Wind Harmer
3.767
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.858
961051AF2-396 GEN
Solar/Wind Harmer
7.905
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
7.075
965791AG1-447 GEN
Solar/Wind Harmer
5.189
270599AE1-208 GEN
Solar/Wind Harmer
5.131
270031AE2-169
Solar/Wind Harmer
3.079
970321AG2-212 GEN
Solar/Wind Harmer
2.372
274808UNIV PK N;4U
Adder
3.841
274770LINCOLN ;1U
Adder
6.474
274771LINCOLN ;2U
Adder
6.474
274803UNIV PARK;6U
Adder
4.445
274888KELLY CRK;1U
Solar/Wind Harmer
0.311
274887GEN-1.85
Solar/Wind Harmer
0.139
276843GEN-1.7
Solar/Wind Harmer
0.171
958011AF2-095 GEN
Solar/Wind Harmer
7.629
972259AH1-714 GEN
Adder
14.402
274674JOLIET 9 ;6U
Adder
11.55
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.959
958481AF2-142 GEN
Solar/Wind Harmer
7.707
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.695
274695ROCKY RD ;2P
Adder
8.163
274693ROCKY RD ;1P
Adder
8.082
274697ROCKY RD ;3P
Adder
2.217
274696ROCKY RD ;4P
Adder
8.355
274683WAUKEGAN ;8U
Adder
15.422
274683WAUKEGAN ;8U
Adder
13
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
15.227
958491AF2-143 GEN
Solar/Wind Harmer
7.614
970921AG2-575 GEN
Solar/Wind Harmer
5.064
970921AG2-575 GEN
Solar/Wind Harmer
1.688
971613AH1-306 GEN
Solar/Wind Harmer
2.426
274879MINONK ;1U
Solar/Wind Harmer
0.213
942991AE2-321 GEN
Solar/Wind Harmer
5.619
971333AH1-146 GEN
Solar/Wind Harmer
10.011
971335AH1-147 GEN
Solar/Wind Harmer
10.011
960441AF2-335 GEN
Solar/Wind Harmer
4.991
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.953
971343AH1-151 GEN
Solar/Wind Harmer
9.953
970825AG2-519 GEN
Solar/Wind Harmer
5.49
274856ECOGROVE ;U1
Solar/Wind Harmer
0.116
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.774
274764LEE CO EC;5U
Adder
6.52
274765LEE CO EC;6U
Adder
6.52
274762LEE CO EC;3U
Adder
6.505
274763LEE CO EC;4U
Adder
6.443
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.365
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.883
276741O09 GEN1
Solar/Wind Harmer
0.172
276708O09 GEN2
Solar/Wind Harmer
0.172
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
970583AG2-370 GEN
50/50
2.859
960851AF2-376 GEN
50/50
2.155
24641605TWIN BRNCH
50/50
0.016
270142AC1-141 CT1_
50/50
2.055
24642205MAYFLWER
50/50
0.571
944961AF1-161 GEN
50/50
2.434
962601AG1-109 GEN
50/50
2.434
24344005CKG1
50/50
5.289
959331AF2-224 GEN
Solar/Wind Harmer
9.739
965021AG1-366 GEN
Solar/Wind Harmer
4.638
970031AG2-029 GEN
Solar/Wind Harmer
5.561
270043AE2-236 GEN
Solar/Wind Harmer
5.288
960861AF2-377 GEN
50/50
2.449
970521AG2-332 GEN
50/50
11.057
24639705ELKHART HY
50/50
0.153
270143AC1-141 CT2_
50/50
2.055
24344105CKG2
50/50
6.288
24307105BERRINSP G
50/50
0.018
965011AG1-365 GEN
Solar/Wind Harmer
13.913
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.268
270246TR4_N_V150
Solar/Wind Harmer
0.047
944231AF1-091 GEN
Solar/Wind Harmer
1.894
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.883
958861AF2-177 GEN
Solar/Wind Harmer
2.703
945111AF1-176 GEN
Solar/Wind Harmer
10.846
270505AE1-170 C O1
Solar/Wind Harmer
6.228
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.049
970245AG2-165 GEN
Solar/Wind Harmer
2.372
970373AG2-245 GEN
Solar/Wind Harmer
11.463
274751CRETE EC ;1U
Adder
6.419
274754CRETE EC ;4U
Adder
6.419
274723RIVER EC ;12
Adder
13.914
274812UNIV PK N;8U
Adder
3.858
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.474
274774LINCOLN ;5U
Adder
6.474
274801UNIV PARK;4U
Adder
4.433
276776AD2-060 GEN
Solar/Wind Harmer
0.553
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.867
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
23.063
274674JOLIET 9 ;6U
Adder
11.55
274732ELWOOD EC;7P
Adder
12.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.476
274745AC1-111 GEN9
Adder
4.142
276691AA1-018 GEN1
Solar/Wind Harmer
0.622
274682WAUKEGAN ;7U
Adder
13.17
970291AG2-192 GEN
Solar/Wind Harmer
0.664
274828WAUKEGAN ;BP
Adder
8.084
270005AE1-210 C O1
Solar/Wind Harmer
1.101
965031AG1-367 GEN
Solar/Wind Harmer
5.08
962781AG1-127 GEN
Solar/Wind Harmer
4.819
939401AE1-172 GEN
Solar/Wind Harmer
3.786
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.37
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.638
276861AD2-134 GEN
Solar/Wind Harmer
0.09
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.929
959081AF2-199 GEN
Solar/Wind Harmer
4.976
971067AG2-660 GEN
Solar/Wind Harmer
1.659
274822ROCKFORD ;11
Adder
13.956
970825AG2-519 GEN
Solar/Wind Harmer
1.759
972235AH1-702 GEN1
Adder
1.788
970819AG2-516 GEN
Solar/Wind Harmer
5.921
970569AG2-363 GEN
Solar/Wind Harmer
14.789
971475AH1-234 GEN
Solar/Wind Harmer
2.388
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.505
274766LEE CO EC;7U
Adder
6.428
276903AD2-071 C
Solar/Wind Harmer
5.417
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.161
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
6.647
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.748
963741AG1-226 GEN
Solar/Wind Harmer
10.683
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.3
247536S-71 GEN
Solar/Wind Harmer
0.179
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.713
276615X2-022 GEN
Solar/Wind Harmer
0.046
965911AG1-460 GEN
Solar/Wind Harmer
0.838
24728605AND G2
Adder
2.125
970773AG2-487 GEN
Solar/Wind Harmer
0.635
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
2.323
246936BC-WTG1
Solar/Wind Helper
10.843
270462AD2-086
Solar/Wind Helper
3.651
270223U2-072_GEN1
Solar/Wind Helper
0.855
270578AF1-285 GEN2
Solar/Wind Helper
0.579
270391AF1-285 GEN3
Solar/Wind Helper
0.579
247522W1-056 GEN
Solar/Wind Helper
1.138
960841AF2-375 GEN
Solar/Wind Helper
1.139
270349AD2-093_GEN
Solar/Wind Helper
0.817
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
944531AF1-118 GEN
Solar/Wind Harmer
32.162
971617AH1-308 GEN
Solar/Wind Harmer
5.291
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.927
970349AG2-230 GEN
Solar/Wind Harmer
8.913
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.372
970517AG2-330 GEN
Solar/Wind Harmer
14.231
274752CRETE EC ;2U
Adder
6.419
274753CRETE EC ;3U
Adder
6.419
274724RIVER EC ;11
Adder
13.745
247604X1-042
Adder
0.322
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.474
274802UNIV PARK;5U
Adder
4.445
274826FISK ;BP
Adder
8.338
274800UNIV PARK;3U
Adder
4.433
972038AH1-567 GEN2
Adder
0.277
276806AD2-047 C O1
Solar/Wind Harmer
3.002
970941AG2-585 GEN
Solar/Wind Harmer
6.622
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.805
970707AG2-453 GEN
Solar/Wind Harmer
17.2
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.239
276893AG1-478 C
Solar/Wind Harmer
0.207
274729ELWOOD EC;1P
Adder
12.325
274730ELWOOD EC;6P
Adder
12.325
274734ELWOOD EC;8P
Adder
12.325
274736ELWOOD EC;9P
Adder
12.325
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.672
943591AF1-030 GEN
Solar/Wind Harmer
5.767
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
13.17
970289AG2-191 GEN
Solar/Wind Harmer
0.562
970291AG2-192 GEN
Solar/Wind Harmer
0.511
958821AF2-173 GEN
Solar/Wind Harmer
7.111
270004AE1-209 GEN
Solar/Wind Harmer
1.101
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.185
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.534
274855GSG-6 ;RU
Solar/Wind Harmer
0.184
274850MENDOTA H;RU
Solar/Wind Harmer
0.059
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.09
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.985
959091AF2-200 GEN
Solar/Wind Harmer
9.953
972236AH1-702 GEN2
Adder
1.555
970571AG2-364 GEN
Solar/Wind Harmer
9.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.505
274767LEE CO EC;8U
Adder
6.428
946031AF1-268 GEN
Solar/Wind Harmer
4.635
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.294
276157O29GEN1
Solar/Wind Harmer
0.779
274878BISHOP HL;2U
Solar/Wind Harmer
0.161
942111AE2-223 GEN
Solar/Wind Harmer
1.543
965931AG1-462 GEN
Solar/Wind Harmer
11.906
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
14.002
959611AF2-252 GEN
Solar/Wind Harmer
1.556
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.161
971993AH1-541 GEN
Solar/Wind Harmer
2.041
276621W2-048 GEN
Solar/Wind Harmer
0.219
276838X2-022 GEN2
Solar/Wind Harmer
0.245
942481AE2-261 GEN
Solar/Wind Harmer
12.535
970193AG2-126 GEN
Solar/Wind Harmer
6.087
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.445
24728505AND G1
Adder
2.125
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.9
970519AG2-331 GEN
Solar/Wind Harmer
8.446
970699AG2-449 GEN
Solar/Wind Harmer
0.812
270485AE1-090_GEN
Solar/Wind Helper
0.318
942871AE2-306 GEN
Solar/Wind Helper
0.434
270541AE2-072 C
Solar/Wind Helper
0.891
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.189
276646AC1-214 GEN2
Solar/Wind Harmer
0.189
966841AG1-555 GEN
Solar/Wind Harmer
0.542
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.165
960611AF2-352 GEN
Solar/Wind Harmer
1.556
970241AG2-163 GEN
Solar/Wind Harmer
2.633
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.003
276916AD2-100_GEN
Solar/Wind Harmer
8.729
276911AD2-131_GEN
Solar/Wind Harmer
0.575
970883AG2-550 GEN
Solar/Wind Harmer
4.063
970885AG2-551 GEN
Solar/Wind Harmer
1.354
945391AF1-204 GEN
Solar/Wind Harmer
4.312
970623AG2-406 GEN
Solar/Wind Harmer
0.709
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.538
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.812
246938BC-WTG3
Solar/Wind Helper
11.029
246937BC-WTG2
Solar/Wind Helper
10.843
270224U2-072_GEN2
Solar/Wind Helper
0.855
270227U2-072_GEN3
Solar/Wind Helper
0.855
270228U2-072_GEN4
Solar/Wind Helper
0.855
270231U2-072_GEN5
Solar/Wind Helper
0.855
270471AD2-092_GEN
Solar/Wind Helper
0.817
253378AE2-206_GEN
Solar/Wind Helper
0.657
276820AF1-078_GEN
Solar/Wind Helper
0.307
241960AC2-195 GEN
Solar/Wind Helper
0.657
971599AH1-298 GEN
50/50
10.521
24729505KEY G4
50/50
6.883
24653605MOTTVILLE
50/50
0.004
270144AC1-141 ST1_
50/50
1.82
24643105BUCHANAN
50/50
0.011
963791AG1-232 GEN
Solar/Wind Harmer
11.809
965041AG1-368 GEN
Solar/Wind Harmer
8.577
270071AF1-092 GEN
Solar/Wind Harmer
14.687
965051AG1-369 GEN
Solar/Wind Harmer
3.667
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.239
971771AH1-392 GEN
Solar/Wind Harmer
5.998
971347AH1-153 GEN
Solar/Wind Harmer
8.913
971619AH1-309 GEN
Solar/Wind Harmer
2.669
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.451
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.914
274814UNIV PK N;0U
Adder
3.891
274807UNIV PK N;3U
Adder
3.883
274805UNIV PK N;1U
Adder
3.866
274811UNIV PK N;7U
Adder
3.858
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.474
274776LINCOLN ;7U
Adder
6.474
274777LINCOLN ;8U
Adder
6.474
972037AH1-567 GEN1
Adder
0.14
274827FISK ;RP
Adder
5.909
960591AF2-350 GEN
Solar/Wind Harmer
5.298
972227AH1-698 GEN1
Adder
1.975
274687WILL CNTY;4U
Adder
21.05
274687WILL CNTY;4U
Adder
21.05
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
23.063
274675JOLIET 29;7U
Adder
22.239
274731ELWOOD EC;2P
Adder
12.325
274733ELWOOD EC;3P
Adder
12.325
274735ELWOOD EC;4P
Adder
12.325
274728ELWOOD EC;5P
Adder
12.325
970833AG2-524 GEN
Solar/Wind Harmer
5.728
970833AG2-524 GEN
Solar/Wind Harmer
3.819
971611AH1-305 GEN
Solar/Wind Harmer
3.084
274746AC1-111 G10
Adder
4.142
274744AC1-111 GEN8
Adder
4.142
970289AG2-191 GEN
Solar/Wind Harmer
0.971
270594AE1-207 GEN
Solar/Wind Harmer
5.661
276868AE1-113 GEN
Solar/Wind Harmer
1.012
276882AE2-255 GEN
Solar/Wind Harmer
0.59
971177AH1-047 GEN
Solar/Wind Harmer
3.102
971411AH1-196 GEN
Solar/Wind Harmer
7.515
971675AH1-338 GEN
Solar/Wind Harmer
1.952
970115AG2-085 GEN
Solar/Wind Harmer
1.996
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.953
274823ROCKFORD ;21
Adder
13.855
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.837
970169AG2-114 GEN
Solar/Wind Harmer
4.915
971681AH1-341 GEN
Solar/Wind Harmer
7.885
971549AH1-272 GEN
Solar/Wind Harmer
10.103
961011AF2-392 GEN
Solar/Wind Harmer
2.842
957751AF2-069 GEN
Solar/Wind Harmer
0.159
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.986
941731AE2-173 GEN
Solar/Wind Harmer
3.957
946321AF1-296 GEN
Solar/Wind Harmer
2.629
963841AG1-237 GEN
Solar/Wind Harmer
2.014
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.161
276848AB2-070 GEN3
Solar/Wind Harmer
0.16
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.367
971029AG2-637 GEN
Solar/Wind Harmer
5.468
971673AH1-337 GEN
Solar/Wind Harmer
2.273
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.571
270317AD1-130_GEN
Solar/Wind Helper
4.044
966831AG1-554 GEN
Solar/Wind Helper
0.856
270284AF1-227 GEN1
Solar/Wind Helper
1.824
270286AF1-227 GEN2
Solar/Wind Helper
0.669
270287AF1-227 GEN3
Solar/Wind Helper
0.669
270499AE1-146 GEN
Solar/Wind Helper
1.895
945641AF1-229 GEN
Solar/Wind Helper
0.904
944201AF1-088_MTX
Adder
57.673
957141AF2-008_MTX
Adder
8.943
990497J1323
External Queue
1.5914489030838013
990792J1392
External Queue
5.474584102630615
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.466
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.567
MECLTFEXP_MEC->PJM
CLTF
10.019
SIGELTFEXP_SIGE->PJM
CLTF
0.208
LAGNLTFEXP_LAGN->PJM
CLTF
6.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.094
TVALTFEXP_TVA->PJM
CLTF
2.49
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.858
NYPJM->LTFIMP_NY
CLTF
1.126
LGEELTFEXP_LGEE->PJM
CLTF
1.931
WECLTFEXP_WEC->PJM
CLTF
2.707
AG2-052LTFEXP_AG2-052->PJM
LTF
0.175
AH1-155LTFEXP_AH1-155->PJM
LTF
0.263

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.67 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:1783.41
MW Contribution:30.65
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.148
970611AG2-400 GEN
Solar/Wind Harmer
17.837
942221AE2-234 GEN
Solar/Wind Harmer
0.599
247620Y3-023
Adder
0.353
944541AF1-119 GEN
Solar/Wind Harmer
3.09
960971AF2-388 GEN
Solar/Wind Harmer
8.065
270216AD2-079_GEN
Solar/Wind Harmer
0.425
960981AF2-389 GEN
Solar/Wind Harmer
0.991
957891AF2-083 GEN
Solar/Wind Harmer
2.208
961051AF2-396 GEN
Solar/Wind Harmer
10.299
961051AF2-396 GEN
Solar/Wind Harmer
4.79
270599AE1-208 GEN
Solar/Wind Harmer
5.221
270031AE2-169
Solar/Wind Harmer
5.221
270526AF1-158 GEN
Solar/Wind Harmer
2.885
24441505OLIV SLR
Solar/Wind Harmer
0.084
965681AG1-436 GEN
Solar/Wind Harmer
7.678
965791AG1-447 GEN
Solar/Wind Harmer
3.928
274808UNIV PK N;4U
Adder
2.917
970321AG2-212 GEN
Solar/Wind Harmer
10.422
274770LINCOLN ;1U
Adder
3.589
274771LINCOLN ;2U
Adder
3.589
274803UNIV PARK;6U
Adder
3.373
274888KELLY CRK;1U
Solar/Wind Harmer
3.399
274887GEN-1.85
Solar/Wind Harmer
3.069
276843GEN-1.7
Solar/Wind Harmer
0.33
958011AF2-095 GEN
Solar/Wind Harmer
8.291
972259AH1-714 GEN
Adder
10.903
274674JOLIET 9 ;6U
Adder
8.758
274847GR RIDGE ;BU
Solar/Wind Harmer
2.859
960441AF2-335 GEN
Solar/Wind Harmer
5.647
945421AF1-207 GEN
Solar/Wind Harmer
7.883
957841AF2-078 GEN
Solar/Wind Harmer
3.392
970825AG2-519 GEN
Solar/Wind Harmer
5.907
958481AF2-142 GEN
Solar/Wind Harmer
8.393
274861TOP CROP ;1U
Solar/Wind Harmer
3.389
274862TOP CROP ;2U
Solar/Wind Harmer
2.83
971573AH1-285 GEN
Solar/Wind Harmer
4.808
274695ROCKY RD ;2P
Adder
6.194
274693ROCKY RD ;1P
Adder
6.133
274697ROCKY RD ;3P
Adder
1.683
274696ROCKY RD ;4P
Adder
6.34
274683WAUKEGAN ;8U
Adder
11.709
274683WAUKEGAN ;8U
Adder
9.87
958491AF2-143 GEN
Solar/Wind Harmer
8.297
962691AG1-118 GEN
Solar/Wind Harmer
16.569
970921AG2-575 GEN
Solar/Wind Harmer
5.511
970921AG2-575 GEN
Solar/Wind Harmer
1.282
247621Y3-024
Adder
0.129
274764LEE CO EC;5U
Adder
4.967
274765LEE CO EC;6U
Adder
4.967
274762LEE CO EC;3U
Adder
4.955
274763LEE CO EC;4U
Adder
4.908
972267AH1-718 GEN
Adder
2.198
246938BC-WTG3
Solar/Wind Helper
11.498
246937BC-WTG2
Solar/Wind Helper
11.304
270224U2-072_GEN2
Solar/Wind Helper
1
270227U2-072_GEN3
Solar/Wind Helper
1
270228U2-072_GEN4
Solar/Wind Helper
1
270231U2-072_GEN5
Solar/Wind Helper
1
270471AD2-092_GEN
Solar/Wind Helper
1.159
253378AE2-206_GEN
Solar/Wind Helper
0.808
276820AF1-078_GEN
Solar/Wind Helper
0.377
241960AC2-195 GEN
Solar/Wind Helper
0.795
970583AG2-370 GEN
50/50
2.398
959331AF2-224 GEN
Solar/Wind Harmer
17.837
965021AG1-366 GEN
Solar/Wind Harmer
4.148
970031AG2-029 GEN
Solar/Wind Harmer
30.654
270043AE2-236 GEN
Solar/Wind Harmer
5.317
270191TR4_S_V150
Solar/Wind Harmer
2.574
270247TR4_N_V136
Solar/Wind Harmer
0.73
944531AF1-118 GEN
Solar/Wind Harmer
29.028
971617AH1-308 GEN
Solar/Wind Harmer
4.328
247643Z2-116 C
Solar/Wind Harmer
0.049
945111AF1-176 GEN
Solar/Wind Harmer
3.787
24642205MAYFLWER
Adder
0.41
970349AG2-230 GEN
Solar/Wind Harmer
9.616
24441205WTRV SLR C
Solar/Wind Harmer
0.08
972231SS25-0005
Solar/Wind Harmer
5.619
972181SS23-001
Solar/Wind Harmer
3.512
274752CRETE EC ;2U
Adder
2.894
274753CRETE EC ;3U
Adder
2.894
274724RIVER EC ;11
Adder
10.434
270535AF1-215 GEN1
Solar/Wind Harmer
2.67
970513AG2-328 GEN
Solar/Wind Harmer
10.422
970517AG2-330 GEN
Solar/Wind Harmer
9.453
247642Z2-115 C
Solar/Wind Harmer
0.037
964401AG1-302 GEN
Solar/Wind Harmer
5.266
274772LINCOLN ;3U
Adder
3.589
274802UNIV PARK;5U
Adder
3.373
274826FISK ;BP
Adder
6.325
274800UNIV PARK;3U
Adder
3.362
972038AH1-567 GEN2
Adder
0.21
276772AC2-154 GEN
Solar/Wind Harmer
1.606
276806AD2-047 C O1
Solar/Wind Harmer
6.159
970941AG2-585 GEN
Solar/Wind Harmer
7.197
970289AG2-191 GEN
Solar/Wind Harmer
0.442
970291AG2-192 GEN
Solar/Wind Harmer
0.402
958821AF2-173 GEN
Solar/Wind Harmer
8.055
270004AE1-209 GEN
Solar/Wind Harmer
3.144
247604X1-042
Adder
0.24
959141AF2-205 GEN
Solar/Wind Harmer
3.471
972228AH1-698 GEN2
Adder
2.125
970707AG2-453 GEN
Solar/Wind Harmer
15.979
274676JOLIET 29;8U
Adder
16.864
276897AD1-100 C
Solar/Wind Harmer
16.531
971599AH1-298 GEN
50/50
8.505
963791AG1-232 GEN
Solar/Wind Harmer
14.396
965041AG1-368 GEN
Solar/Wind Harmer
10.31
270071AF1-092 GEN
Solar/Wind Harmer
13.399
965051AG1-369 GEN
Solar/Wind Harmer
4.285
24729505KEY G4
Adder
5.223
270024AE2-089 GEN
Solar/Wind Harmer
3.494
958711AF2-162 GEN
Solar/Wind Harmer
0.746
965101AG1-375 GEN
Solar/Wind Harmer
7.158
945581AF1-223 GEN
Solar/Wind Harmer
3.056
971771AH1-392 GEN
Solar/Wind Harmer
5.92
971347AH1-153 GEN
Solar/Wind Harmer
9.616
971769AH1-391 GEN
Solar/Wind Harmer
6.293
944161AF1-084 GEN
Solar/Wind Harmer
1.381
960681AF2-359 GEN
Solar/Wind Harmer
2.321
270536AF1-215 GEN2
Solar/Wind Harmer
2.67
274814UNIV PK N;0U
Adder
2.955
274807UNIV PK N;3U
Adder
2.949
274805UNIV PK N;1U
Adder
2.936
274811UNIV PK N;7U
Adder
2.929
274775LINCOLN ;6U
Adder
3.589
274776LINCOLN ;7U
Adder
3.589
274777LINCOLN ;8U
Adder
3.589
972037AH1-567 GEN1
Adder
0.106
274827FISK ;RP
Adder
4.483
958391AF2-133 GEN
Solar/Wind Harmer
5.233
960591AF2-350 GEN
Solar/Wind Harmer
5.758
965461AG1-414 GEN
Solar/Wind Harmer
1.305
970289AG2-191 GEN
Solar/Wind Harmer
1.094
972227AH1-698 GEN1
Adder
1.497
274687WILL CNTY;4U
Adder
15.965
274687WILL CNTY;4U
Adder
15.965
274675JOLIET 29;7U
Adder
17.489
274675JOLIET 29;7U
Adder
16.864
270594AE1-207 GEN
Solar/Wind Harmer
8.37
274731ELWOOD EC;2P
Adder
9.347
274733ELWOOD EC;3P
Adder
9.347
274735ELWOOD EC;4P
Adder
9.347
274728ELWOOD EC;5P
Adder
9.347
970833AG2-524 GEN
Solar/Wind Harmer
4.939
970833AG2-524 GEN
Solar/Wind Harmer
2.297
970115AG2-085 GEN
Solar/Wind Harmer
2.259
274746AC1-111 G10
Adder
3.14
274744AC1-111 GEN8
Adder
3.14
24690905MDL-1G C
Solar/Wind Harmer
4.428
270180AB1-006 GEN1
Solar/Wind Harmer
3.967
946581AF1-322 GEN
Solar/Wind Harmer
5.643
24691005MDL-2G C
Solar/Wind Harmer
2.04
24697605MDL-3G C
Solar/Wind Harmer
2.033
24697905MDL-4G C
Solar/Wind Harmer
1.266
270181AB1-006 GEN2
Solar/Wind Harmer
0.394
939351AE1-166 GEN
Solar/Wind Harmer
3.378
276893AG1-478 C
Solar/Wind Harmer
0.238
274729ELWOOD EC;1P
Adder
9.347
274730ELWOOD EC;6P
Adder
9.347
274734ELWOOD EC;8P
Adder
9.347
274736ELWOOD EC;9P
Adder
9.347
943121AE2-341 GEN
Solar/Wind Harmer
8.426
943591AF1-030 GEN
Solar/Wind Harmer
5.617
276694AA1-018 GEN2
Solar/Wind Harmer
3.531
274682WAUKEGAN ;7U
Adder
9.998
276805AD2-038 GEN
Solar/Wind Harmer
2.837
24755605MDL-5G
Solar/Wind Harmer
1.33
970781AG2-491 GEN
Solar/Wind Harmer
5.515
972236AH1-702 GEN2
Adder
1.183
274760LEE CO EC;1U
Adder
4.955
274767LEE CO EC;8U
Adder
4.897
24728705AND G3
Adder
3.454
24728505AND G1
Adder
1.652
270485AE1-090_GEN
Solar/Wind Helper
0.365
942871AE2-306 GEN
Solar/Wind Helper
0.508
270541AE2-072 C
Solar/Wind Helper
1.161
274823ROCKFORD ;21
Adder
10.54
957201AF2-014 GEN
Solar/Wind Helper
8.936
270317AD1-130_GEN
Solar/Wind Helper
4.645
966831AG1-554 GEN
Solar/Wind Helper
0.97
270284AF1-227 GEN1
Solar/Wind Helper
2.329
270286AF1-227 GEN2
Solar/Wind Helper
0.854
270287AF1-227 GEN3
Solar/Wind Helper
0.854
270499AE1-146 GEN
Solar/Wind Helper
2.213
945641AF1-229 GEN
Solar/Wind Helper
1.058
253383AE2-342_GEN
Solar/Wind Helper
0.382
965011AG1-365 GEN
Solar/Wind Harmer
17.837
270063AE2-323 C
Solar/Wind Harmer
1.939
247521TR3_G114
Solar/Wind Harmer
2.886
270246TR4_N_V150
Solar/Wind Harmer
0.73
944231AF1-091 GEN
Solar/Wind Harmer
3.11
965651AG1-433 GEN
Solar/Wind Harmer
4.032
24639705ELKHART HY
Adder
0.113
24695305TIMB G C
Solar/Wind Harmer
4.043
958861AF2-177 GEN
Solar/Wind Harmer
7.824
945371AF1-202 GEN
Solar/Wind Harmer
4.701
945111AF1-176 GEN
Solar/Wind Harmer
11.949
270505AE1-170 C O1
Solar/Wind Harmer
9.724
270449AD2-020 GEN
Solar/Wind Harmer
1.784
943021AE2-325 GEN
Solar/Wind Harmer
2.318
970373AG2-245 GEN
Solar/Wind Harmer
12.513
274751CRETE EC ;1U
Adder
2.894
274754CRETE EC ;4U
Adder
2.894
274723RIVER EC ;12
Adder
10.564
270055AF2-134 C O1
Solar/Wind Harmer
1.78
274812UNIV PK N;8U
Adder
2.929
276164X3-005 C
Solar/Wind Harmer
0.41
970245AG2-165 GEN
Solar/Wind Harmer
10.422
958381AF2-132 GEN
Solar/Wind Harmer
5.266
964861AG1-349 GEN
Solar/Wind Harmer
4.557
971917AH1-482 GEN
Solar/Wind Harmer
5.259
972207SS24-0001
Solar/Wind Harmer
12.76
274773LINCOLN ;4U
Adder
3.589
274774LINCOLN ;5U
Adder
3.589
274801UNIV PARK;4U
Adder
3.362
276776AD2-060 GEN
Solar/Wind Harmer
0.243
970291AG2-192 GEN
Solar/Wind Harmer
0.748
270005AE1-210 C O1
Solar/Wind Harmer
3.144
965031AG1-367 GEN
Solar/Wind Harmer
5.754
940581AE2-045 GEN
Solar/Wind Harmer
5.82
971605AH1-302 GEN
Solar/Wind Harmer
4.977
274676JOLIET 29;8U
Adder
17.489
941551AE2-152 GEN
Solar/Wind Harmer
2.583
270032AE2-172
Solar/Wind Harmer
2.649
274674JOLIET 9 ;6U
Adder
8.758
274732ELWOOD EC;7P
Adder
9.347
274871GR RIDGE ;2U
Solar/Wind Harmer
4.347
274745AC1-111 GEN9
Adder
3.14
970825AG2-519 GEN
Solar/Wind Harmer
1.318
276691AA1-018 GEN1
Solar/Wind Harmer
0.26
274682WAUKEGAN ;7U
Adder
9.998
274828WAUKEGAN ;BP
Adder
6.138
24791305MDL-5G
Solar/Wind Harmer
1.33
276901AD2-066 C O1
Solar/Wind Harmer
1.936
960751AF2-366 GEN
Solar/Wind Harmer
1.581
962781AG1-127 GEN
Solar/Wind Harmer
5.241
274822ROCKFORD ;11
Adder
10.617
972235AH1-702 GEN1
Adder
1.361
274761LEE CO EC;2U
Adder
4.955
274766LEE CO EC;7U
Adder
4.897
24728605AND G2
Adder
1.652
246936BC-WTG1
Solar/Wind Helper
11.304
270462AD2-086
Solar/Wind Helper
4.193
270223U2-072_GEN1
Solar/Wind Helper
1
270578AF1-285 GEN2
Solar/Wind Helper
0.677
270391AF1-285 GEN3
Solar/Wind Helper
0.677
247522W1-056 GEN
Solar/Wind Helper
1.306
960841AF2-375 GEN
Solar/Wind Helper
1.333
270349AD2-093_GEN
Solar/Wind Helper
1.159
241840AF1-064_GEN
Solar/Wind Helper
0.463
939401AE1-172 GEN
Solar/Wind Harmer
2.574
990497J1323
External Queue
1.411980390548706
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.937
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.28
MECLTFEXP_MEC->PJM
CLTF
7.744
SIGELTFEXP_SIGE->PJM
CLTF
0.164
LAGNLTFEXP_LAGN->PJM
CLTF
5.219
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.272
TVALTFEXP_TVA->PJM
CLTF
2.209
CPLELTFEXP_CPLE->PJM
CLTF
0.473
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.821
NYPJM->LTFIMP_NY
CLTF
0.846
LGEELTFEXP_LGEE->PJM
CLTF
1.5
WECLTFEXP_WEC->PJM
CLTF
2.06
AG2-052LTFEXP_AG2-052->PJM
LTF
0.134
AH1-155LTFEXP_AH1-155->PJM
LTF
0.201

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.99 %
Rating:1302.0 MVA
Rating Type:B
MVA to Mitigate:1536.23
MW Contribution:15.43
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
22.116
270224U2-072_GEN2
Solar/Wind Harmer
8.675
270227U2-072_GEN3
Solar/Wind Harmer
8.675
270228U2-072_GEN4
Solar/Wind Harmer
8.675
270231U2-072_GEN5
Solar/Wind Harmer
8.675
246938BC-WTG3
Solar/Wind Harmer
4.471
246937BC-WTG2
Solar/Wind Harmer
4.395
270007AE1-245 C
Solar/Wind Harmer
4.993
942801AE2-298 GEN
Solar/Wind Harmer
1.179
970611AG2-400 GEN
Solar/Wind Harmer
6.922
971677AH1-339 GEN
Solar/Wind Harmer
5.222
241996AE2-282_GEN
Solar/Wind Harmer
0.963
247620Y3-023
Adder
0.211
971231AH1-075 GEN
Solar/Wind Harmer
0.352
942221AE2-234 GEN
Solar/Wind Harmer
0.32
270216AD2-079_GEN
Solar/Wind Harmer
0.262
270471AD2-092_GEN
Solar/Wind Helper
1.798
946101AF1-275 GEN
Solar/Wind Helper
0.318
965431AG1-411 GEN
50/50
12.58
24727105RPMNG2
50/50
0.95
942871AE2-306 GEN
Solar/Wind Harmer
3.979
270391AF1-285 GEN3
Solar/Wind Harmer
2.041
270485AE1-090_GEN
Solar/Wind Harmer
2.304
270491AE1-102 GEN2
Solar/Wind Harmer
1.46
270588AE1-091_GEN
Solar/Wind Harmer
10.946
270541AE2-072 C
Solar/Wind Harmer
3.904
958091AF2-103 GEN
Solar/Wind Harmer
0.136
270575GUS2 35KV
Solar/Wind Harmer
7.614
270258AD1-119 GEN
Solar/Wind Harmer
2.055
270044AE2-322 C
Solar/Wind Harmer
0.958
270404AC1-167 GEN
Solar/Wind Harmer
0.797
270191TR4_S_V150
Solar/Wind Harmer
2.148
270247TR4_N_V136
Solar/Wind Harmer
0.609
959331AF2-224 GEN
Solar/Wind Harmer
6.922
965021AG1-366 GEN
Solar/Wind Harmer
1.61
23906502RICHG2&3
Adder
0.822
958321AF2-126 GEN
Solar/Wind Harmer
0.806
241832AE2-181_GEN
Solar/Wind Harmer
0.902
23929302BS-PKR
Adder
0.782
970031AG2-029 GEN
Solar/Wind Harmer
15.427
270043AE2-236 GEN
Solar/Wind Harmer
2.738
270377AD1-106 GEN
Solar/Wind Harmer
2.718
945111AF1-176 GEN
Solar/Wind Harmer
2.442
247643Z2-116 C
Solar/Wind Harmer
0.03
971617AH1-308 GEN
Solar/Wind Harmer
2.507
24727005RPMNG1
50/50
0.947
270223U2-072_GEN1
Solar/Wind Harmer
8.675
270578AF1-285 GEN2
Solar/Wind Harmer
5.305
270391AF1-285 GEN3
Solar/Wind Harmer
5.305
270462AD2-086
Solar/Wind Harmer
26.506
246936BC-WTG1
Solar/Wind Harmer
4.395
270489AE1-102 GEN1
Solar/Wind Harmer
1.46
965421AG1-410 GEN
Solar/Wind Harmer
32.457
247522W1-056 GEN
Solar/Wind Harmer
1.843
960841AF2-375 GEN
Solar/Wind Harmer
3.015
24695305TIMB G C
Solar/Wind Harmer
4.219
270361_3
Solar/Wind Harmer
6.463
247521TR3_G114
Solar/Wind Harmer
2.408
270246TR4_N_V150
Solar/Wind Harmer
0.609
965011AG1-365 GEN
Solar/Wind Harmer
6.922
23906502RICHG2&3
Adder
0.822
972301AH1-735 GEN
Adder
4.089
23906402RICHG1
Adder
0.818
241840AF1-064_GEN
Solar/Wind Harmer
0.752
23920202STRYCT
Adder
0.86
944231AF1-091 GEN
Solar/Wind Harmer
2.303
241808AF1-120 C
Solar/Wind Harmer
0.537
241858AF1-205_GEN
Solar/Wind Harmer
2.383
972253AH1-711 GEN
Adder
18.549
270063AE2-323 C
Solar/Wind Harmer
1.091
24639705ELKHART HY
Adder
0.068
945111AF1-176 GEN
Solar/Wind Harmer
7.706
270349AD2-093_GEN
Solar/Wind Helper
1.798
270036AE2-216 BAT
50/50
24.327
24727205RPMNG3
50/50
0.942
270284AF1-227 GEN1
Solar/Wind Harmer
35.4
270286AF1-227 GEN2
Solar/Wind Harmer
13.096
270287AF1-227 GEN3
Solar/Wind Harmer
13.096
270578AF1-285 GEN2
Solar/Wind Harmer
2.041
270302AB2-170 GEN
Solar/Wind Harmer
31.863
270317AD1-130_GEN
Solar/Wind Harmer
12.215
957201AF2-014 GEN
Solar/Wind Harmer
5.094
270435AC2-044 GEN
Solar/Wind Harmer
2.246
270297AD1-101 GEN
Solar/Wind Harmer
2.352
247607V1-011 GEN
Solar/Wind Harmer
3.327
966831AG1-554 GEN
Solar/Wind Harmer
0.997
971989AH1-539 GEN
Solar/Wind Harmer
10.779
270499AE1-146 GEN
Solar/Wind Harmer
2.04
965051AG1-369 GEN
Solar/Wind Harmer
3.576
965041AG1-368 GEN
Solar/Wind Harmer
7.155
945411AF1-206 GEN
Solar/Wind Harmer
3.599
970817AG2-515 GEN
Solar/Wind Harmer
5.709
972211AH1-690 GEN
Adder
87.557
963791AG1-232 GEN
Solar/Wind Harmer
7.374
945641AF1-229 GEN
Solar/Wind Harmer
1.909
270071AF1-092 GEN
Solar/Wind Harmer
6.82
971549AH1-272 GEN
Solar/Wind Harmer
8.28
270024AE2-089 GEN
Solar/Wind Harmer
2.024
270520AE2-214 GEN
Solar/Wind Helper
2.538
270054AF2-122 C O1
Solar/Wind Helper
0.659
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.204
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.052
MECLTFEXP_MEC->PJM
CLTF
4.384
SIGELTFEXP_SIGE->PJM
CLTF
0.085
LAGNLTFEXP_LAGN->PJM
CLTF
2.114
TVALTFEXP_TVA->PJM
CLTF
0.753
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.723
NYPJM->LTFIMP_NY
CLTF
0.798
LGEELTFEXP_LGEE->PJM
CLTF
0.744
WECLTFEXP_WEC->PJM
CLTF
1.222
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.369
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.86 %
Rating:1302.0 MVA
Rating Type:B
MVA to Mitigate:1443.45
MW Contribution:16.06
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
24.946
24727205RPMNG3
50/50
0.982
270284AF1-227 GEN1
Solar/Wind Harmer
36.123
270286AF1-227 GEN2
Solar/Wind Harmer
13.364
270287AF1-227 GEN3
Solar/Wind Harmer
13.364
270578AF1-285 GEN2
Solar/Wind Harmer
2.089
270302AB2-170 GEN
Solar/Wind Harmer
32.674
270317AD1-130_GEN
Solar/Wind Harmer
12.526
957201AF2-014 GEN
Solar/Wind Harmer
5.307
270435AC2-044 GEN
Solar/Wind Harmer
2.34
966831AG1-554 GEN
Solar/Wind Harmer
1.072
971989AH1-539 GEN
Solar/Wind Harmer
11.594
270297AD1-101 GEN
Solar/Wind Harmer
2.489
247607V1-011 GEN
Solar/Wind Harmer
3.496
270499AE1-146 GEN
Solar/Wind Harmer
2.176
965051AG1-369 GEN
Solar/Wind Harmer
3.76
965041AG1-368 GEN
Solar/Wind Harmer
7.49
945411AF1-206 GEN
Solar/Wind Harmer
3.846
970817AG2-515 GEN
Solar/Wind Harmer
6.123
972211AH1-690 GEN
Adder
94.166
945641AF1-229 GEN
Solar/Wind Harmer
2.109
963791AG1-232 GEN
Solar/Wind Harmer
7.721
270071AF1-092 GEN
Solar/Wind Harmer
7.086
971549AH1-272 GEN
Solar/Wind Harmer
8.654
270024AE2-089 GEN
Solar/Wind Harmer
2.13
944161AF1-084 GEN
Solar/Wind Harmer
0.983
971771AH1-392 GEN
Solar/Wind Harmer
3.88
270466AD2-091
50/50
22.679
270224U2-072_GEN2
Solar/Wind Harmer
8.881
270227U2-072_GEN3
Solar/Wind Harmer
8.881
270228U2-072_GEN4
Solar/Wind Harmer
8.881
270231U2-072_GEN5
Solar/Wind Harmer
8.881
246938BC-WTG3
Solar/Wind Harmer
4.658
246937BC-WTG2
Solar/Wind Harmer
4.579
270007AE1-245 C
Solar/Wind Harmer
5.246
942801AE2-298 GEN
Solar/Wind Harmer
1.244
970611AG2-400 GEN
Solar/Wind Harmer
7.215
971677AH1-339 GEN
Solar/Wind Harmer
5.666
241996AE2-282_GEN
Solar/Wind Harmer
1.03
971231AH1-075 GEN
Solar/Wind Harmer
0.402
247620Y3-023
Adder
0.219
942221AE2-234 GEN
Solar/Wind Harmer
0.335
270216AD2-079_GEN
Solar/Wind Harmer
0.272
961051AF2-396 GEN
Solar/Wind Harmer
7.083
961051AF2-396 GEN
Solar/Wind Harmer
3.295
960981AF2-389 GEN
Solar/Wind Harmer
0.67
957891AF2-083 GEN
Solar/Wind Harmer
1.495
270471AD2-092_GEN
Solar/Wind Helper
1.579
24727005RPMNG1
50/50
0.986
270223U2-072_GEN1
Solar/Wind Harmer
8.881
270578AF1-285 GEN2
Solar/Wind Harmer
5.431
270391AF1-285 GEN3
Solar/Wind Harmer
5.431
270462AD2-086
Solar/Wind Harmer
27.18
246936BC-WTG1
Solar/Wind Harmer
4.579
270489AE1-102 GEN1
Solar/Wind Harmer
1.521
965421AG1-410 GEN
Solar/Wind Harmer
33.814
247522W1-056 GEN
Solar/Wind Harmer
1.977
960841AF2-375 GEN
Solar/Wind Harmer
3.224
24695305TIMB G C
Solar/Wind Harmer
4.424
270361_3
Solar/Wind Harmer
6.922
247521TR3_G114
Solar/Wind Harmer
2.532
270246TR4_N_V150
Solar/Wind Harmer
0.641
23906502RICHG2&3
Adder
0.873
965011AG1-365 GEN
Solar/Wind Harmer
7.215
972301AH1-735 GEN
Adder
4.34
23906402RICHG1
Adder
0.868
241840AF1-064_GEN
Solar/Wind Harmer
0.802
23920202STRYCT
Adder
0.918
944231AF1-091 GEN
Solar/Wind Harmer
2.414
241808AF1-120 C
Solar/Wind Harmer
0.574
241858AF1-205_GEN
Solar/Wind Harmer
2.55
972253AH1-711 GEN
Adder
19.928
270063AE2-323 C
Solar/Wind Harmer
1.135
965431AG1-411 GEN
50/50
13.106
24727105RPMNG2
50/50
0.99
942871AE2-306 GEN
Solar/Wind Harmer
4.074
270391AF1-285 GEN3
Solar/Wind Harmer
2.089
270485AE1-090_GEN
Solar/Wind Harmer
2.363
270491AE1-102 GEN2
Solar/Wind Harmer
1.521
270588AE1-091_GEN
Solar/Wind Harmer
11.649
270541AE2-072 C
Solar/Wind Harmer
4.133
958091AF2-103 GEN
Solar/Wind Harmer
0.143
270575GUS2 35KV
Solar/Wind Harmer
8.155
270258AD1-119 GEN
Solar/Wind Harmer
2.165
270044AE2-322 C
Solar/Wind Harmer
1.008
270404AC1-167 GEN
Solar/Wind Harmer
0.84
270191TR4_S_V150
Solar/Wind Harmer
2.259
270247TR4_N_V136
Solar/Wind Harmer
0.641
23906502RICHG2&3
Adder
0.873
959331AF2-224 GEN
Solar/Wind Harmer
7.215
965021AG1-366 GEN
Solar/Wind Harmer
1.678
958321AF2-126 GEN
Solar/Wind Harmer
0.86
241832AE2-181_GEN
Solar/Wind Harmer
0.964
23929302BS-PKR
Adder
0.842
970031AG2-029 GEN
Solar/Wind Harmer
16.057
270043AE2-236 GEN
Solar/Wind Harmer
2.85
270377AD1-106 GEN
Solar/Wind Harmer
3.103
971617AH1-308 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
2.538
247643Z2-116 C
Solar/Wind Harmer
0.031
247604X1-042
Adder
0.185
24441205WTRV SLR C
Solar/Wind Harmer
0.06
944531AF1-118 GEN
Solar/Wind Harmer
15.258
24642205MAYFLWER
Adder
0.276
24639705ELKHART HY
Adder
0.071
945111AF1-176 GEN
Solar/Wind Harmer
8.008
270449AD2-020 GEN
Solar/Wind Harmer
1.247
943021AE2-325 GEN
Solar/Wind Harmer
1.62
270505AE1-170 C O1
Solar/Wind Harmer
6.636
270428AC2-015 C
Solar/Wind Harmer
2.363
270349AD2-093_GEN
Solar/Wind Helper
1.579
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.293
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.552
MECLTFEXP_MEC->PJM
CLTF
4.428
SIGELTFEXP_SIGE->PJM
CLTF
0.085
LAGNLTFEXP_LAGN->PJM
CLTF
1.858
TVALTFEXP_TVA->PJM
CLTF
0.593
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.885
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.774
LGEELTFEXP_LGEE->PJM
CLTF
0.737
WECLTFEXP_WEC->PJM
CLTF
1.252
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.545
AG2-052LTFEXP_AG2-052->PJM
LTF
0.082
AH1-155LTFEXP_AH1-155->PJM
LTF
0.124

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.45 %
Rating:1302.0 MVA
Rating Type:B
MVA to Mitigate:1346.92
MW Contribution:13.82
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
21.135
270224U2-072_GEN2
Solar/Wind Harmer
8.311
270227U2-072_GEN3
Solar/Wind Harmer
8.311
270228U2-072_GEN4
Solar/Wind Harmer
8.311
270231U2-072_GEN5
Solar/Wind Harmer
8.311
246938BC-WTG3
Solar/Wind Harmer
4.133
246937BC-WTG2
Solar/Wind Harmer
4.063
270007AE1-245 C
Solar/Wind Harmer
4.541
942801AE2-298 GEN
Solar/Wind Harmer
1.064
970611AG2-400 GEN
Solar/Wind Harmer
6.286
971677AH1-339 GEN
Solar/Wind Harmer
4.825
241996AE2-282_GEN
Solar/Wind Harmer
0.89
270471AD2-092_GEN
Solar/Wind Helper
2.202
946101AF1-275 GEN
Solar/Wind Helper
0.321
965431AG1-411 GEN
50/50
11.618
24727105RPMNG2
50/50
0.875
942871AE2-306 GEN
Solar/Wind Harmer
3.812
270391AF1-285 GEN3
Solar/Wind Harmer
1.955
270485AE1-090_GEN
Solar/Wind Harmer
2.202
270491AE1-102 GEN2
Solar/Wind Harmer
1.35
270588AE1-091_GEN
Solar/Wind Harmer
10.088
270541AE2-072 C
Solar/Wind Harmer
3.595
958091AF2-103 GEN
Solar/Wind Harmer
0.124
270575GUS2 35KV
Solar/Wind Harmer
7.051
270258AD1-119 GEN
Solar/Wind Harmer
1.859
270044AE2-322 C
Solar/Wind Harmer
0.868
270404AC1-167 GEN
Solar/Wind Harmer
0.723
270191TR4_S_V150
Solar/Wind Harmer
1.934
270247TR4_N_V136
Solar/Wind Harmer
0.549
959331AF2-224 GEN
Solar/Wind Harmer
6.286
965021AG1-366 GEN
Solar/Wind Harmer
1.462
23906502RICHG2&3
Adder
0.756
958321AF2-126 GEN
Solar/Wind Harmer
0.744
241832AE2-181_GEN
Solar/Wind Harmer
0.833
23929302BS-PKR
Adder
0.727
970031AG2-029 GEN
Solar/Wind Harmer
13.816
270043AE2-236 GEN
Solar/Wind Harmer
2.443
241974AD2-163_GEN2
Solar/Wind Helper
0.822
270036AE2-216 BAT
50/50
23.248
24727205RPMNG3
50/50
0.868
270284AF1-227 GEN1
Solar/Wind Harmer
34.078
270286AF1-227 GEN2
Solar/Wind Harmer
12.607
270287AF1-227 GEN3
Solar/Wind Harmer
12.607
270578AF1-285 GEN2
Solar/Wind Harmer
1.955
270302AB2-170 GEN
Solar/Wind Harmer
30.45
270317AD1-130_GEN
Solar/Wind Harmer
11.673
957201AF2-014 GEN
Solar/Wind Harmer
4.709
270435AC2-044 GEN
Solar/Wind Harmer
2.077
966831AG1-554 GEN
Solar/Wind Harmer
0.919
971989AH1-539 GEN
Solar/Wind Harmer
9.938
270297AD1-101 GEN
Solar/Wind Harmer
2.134
247607V1-011 GEN
Solar/Wind Harmer
3.026
270499AE1-146 GEN
Solar/Wind Harmer
1.886
965041AG1-368 GEN
Solar/Wind Harmer
6.484
965051AG1-369 GEN
Solar/Wind Harmer
3.22
945411AF1-206 GEN
Solar/Wind Harmer
3.324
970817AG2-515 GEN
Solar/Wind Harmer
5.288
972211AH1-690 GEN
Adder
81.324
963791AG1-232 GEN
Solar/Wind Harmer
6.585
945641AF1-229 GEN
Solar/Wind Harmer
1.758
270520AE2-214 GEN
Solar/Wind Helper
2.563
241973AD2-163_GEN1
Solar/Wind Helper
0.822
24727005RPMNG1
50/50
0.872
270223U2-072_GEN1
Solar/Wind Harmer
8.311
270578AF1-285 GEN2
Solar/Wind Harmer
5.083
270391AF1-285 GEN3
Solar/Wind Harmer
5.083
270462AD2-086
Solar/Wind Harmer
25.33
246936BC-WTG1
Solar/Wind Harmer
4.063
270489AE1-102 GEN1
Solar/Wind Harmer
1.35
965421AG1-410 GEN
Solar/Wind Harmer
29.973
247522W1-056 GEN
Solar/Wind Harmer
1.7
960841AF2-375 GEN
Solar/Wind Harmer
2.791
24695305TIMB G C
Solar/Wind Harmer
3.83
270361_3
Solar/Wind Harmer
5.985
247521TR3_G114
Solar/Wind Harmer
2.168
270246TR4_N_V150
Solar/Wind Harmer
0.549
965011AG1-365 GEN
Solar/Wind Harmer
6.286
23906502RICHG2&3
Adder
0.756
972301AH1-735 GEN
Adder
3.758
23906402RICHG1
Adder
0.752
241840AF1-064_GEN
Solar/Wind Harmer
0.694
23920202STRYCT
Adder
0.794
944231AF1-091 GEN
Solar/Wind Harmer
2.084
241808AF1-120 C
Solar/Wind Harmer
0.496
241858AF1-205_GEN
Solar/Wind Harmer
2.204
972253AH1-711 GEN
Adder
17.22
270063AE2-323 C
Solar/Wind Harmer
0.974
270349AD2-093_GEN
Solar/Wind Helper
2.202
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.891
MECLTFEXP_MEC->PJM
CLTF
3.699
SIGELTFEXP_SIGE->PJM
CLTF
0.065
LAGNLTFEXP_LAGN->PJM
CLTF
1.493
TVALTFEXP_TVA->PJM
CLTF
0.456
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.042
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.642
LGEELTFEXP_LGEE->PJM
CLTF
0.496
WECLTFEXP_WEC->PJM
CLTF
1.055
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.448
AG2-052LTFEXP_AG2-052->PJM
LTF
0.069
AH1-155LTFEXP_AH1-155->PJM
LTF
0.104

Details for 05FLTLCK-05GAVIN_RF 765.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05FLTLCK-05GAVIN_RF 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.34 %
Rating:4349.0 MVA
Rating Type:B
MVA to Mitigate:4494.08
MW Contribution:40.66
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.201
270100X2-052 CT1
50/50
2.028
270101X2-052 CT2
50/50
2.028
247620Y3-023
50/50
0.669
970615AG2-402 GEN
50/50
3.074
970321AG2-212 GEN
Solar/Wind Harmer
25.325
270216AD2-079_GEN
Solar/Wind Harmer
0.841
957891AF2-083 GEN
Solar/Wind Harmer
4.643
960981AF2-389 GEN
Solar/Wind Harmer
2.08
270526AF1-158 GEN
Solar/Wind Harmer
6.237
24441505OLIV SLR
Solar/Wind Harmer
0.183
961051AF2-396 GEN
Solar/Wind Harmer
21.727
961051AF2-396 GEN
Solar/Wind Harmer
10.106
965681AG1-436 GEN
Solar/Wind Harmer
17.064
965791AG1-447 GEN
Solar/Wind Harmer
8.731
970611AG2-400 GEN
Solar/Wind Harmer
13.218
274770LINCOLN ;1U
Adder
8.163
274771LINCOLN ;2U
Adder
8.163
274808UNIV PK N;4U
Adder
6.434
274803UNIV PARK;6U
Adder
7.474
972259AH1-714 GEN
Adder
24.421
274888KELLY CRK;1U
Solar/Wind Harmer
7.557
274887GEN-1.85
Solar/Wind Harmer
6.822
276843GEN-1.7
Solar/Wind Harmer
0.734
958011AF2-095 GEN
Solar/Wind Harmer
18.431
274674JOLIET 9 ;6U
Adder
19.473
274847GR RIDGE ;BU
Solar/Wind Harmer
6.376
971573AH1-285 GEN
Solar/Wind Harmer
10.712
274696ROCKY RD ;4P
Adder
14.064
274695ROCKY RD ;2P
Adder
13.74
274693ROCKY RD ;1P
Adder
13.605
274697ROCKY RD ;3P
Adder
3.732
958481AF2-142 GEN
Solar/Wind Harmer
18.503
274861TOP CROP ;1U
Solar/Wind Harmer
7.47
274862TOP CROP ;2U
Solar/Wind Harmer
6.238
274683WAUKEGAN ;8U
Adder
25.914
274683WAUKEGAN ;8U
Adder
21.844
962691AG1-118 GEN
Solar/Wind Harmer
36.699
970921AG2-575 GEN
Solar/Wind Harmer
12.196
970921AG2-575 GEN
Solar/Wind Harmer
2.836
944541AF1-119 GEN
Solar/Wind Harmer
5.094
960971AF2-388 GEN
Solar/Wind Harmer
13.293
958491AF2-143 GEN
Solar/Wind Harmer
18.234
942991AE2-321 GEN
Solar/Wind Harmer
12.086
274879MINONK ;1U
Solar/Wind Harmer
8.155
274764LEE CO EC;5U
Adder
10.839
274765LEE CO EC;6U
Adder
10.839
274762LEE CO EC;3U
Adder
10.813
274763LEE CO EC;4U
Adder
10.711
972267AH1-718 GEN
Adder
4.78
247621Y3-024
Adder
0.217
971333AH1-146 GEN
Solar/Wind Harmer
8.998
971335AH1-147 GEN
Solar/Wind Harmer
8.998
24722005FLATG5
50/50
8.432
24721905FLATG4
50/50
154.591
270142AC1-141 CT1_
50/50
3.334
24344005CKG1
50/50
9.104
24641605TWIN BRNCH
50/50
0.024
24642205MAYFLWER
50/50
0.927
944961AF1-161 GEN
50/50
3.972
962601AG1-109 GEN
50/50
3.972
247604X1-042
50/50
0.589
970153AG2-106 GEN
Solar/Wind Harmer
75.966
970349AG2-230 GEN
Solar/Wind Harmer
22.036
270043AE2-236 GEN
Solar/Wind Harmer
7.928
970513AG2-328 GEN
Solar/Wind Harmer
25.325
970517AG2-330 GEN
Solar/Wind Harmer
22.969
247643Z2-116 C
Solar/Wind Harmer
0.097
945111AF1-176 GEN
Solar/Wind Harmer
7.764
970031AG2-029 GEN
Solar/Wind Harmer
40.661
24441205WTRV SLR C
Solar/Wind Harmer
0.181
944531AF1-118 GEN
Solar/Wind Harmer
46.957
959331AF2-224 GEN
Solar/Wind Harmer
13.218
965021AG1-366 GEN
Solar/Wind Harmer
3.074
274772LINCOLN ;3U
Adder
8.163
274724RIVER EC ;11
Adder
23.052
972231SS25-0005
Solar/Wind Harmer
12.334
24721605FLATG1
50/50
8.432
971599AH1-298 GEN
50/50
13.812
270144AC1-141 ST1_
50/50
2.953
24653605MOTTVILLE
50/50
0.005
24643105BUCHANAN
50/50
0.018
962771AG1-126 GEN
Solar/Wind Harmer
174.214
971347AH1-153 GEN
Solar/Wind Harmer
22.036
270071AF1-092 GEN
Solar/Wind Harmer
20.801
971771AH1-392 GEN
Solar/Wind Harmer
12.478
971769AH1-391 GEN
Solar/Wind Harmer
13.692
960681AF2-359 GEN
Solar/Wind Harmer
5.157
944161AF1-084 GEN
Solar/Wind Harmer
3.004
274775LINCOLN ;6U
Adder
8.163
274776LINCOLN ;7U
Adder
8.163
274777LINCOLN ;8U
Adder
8.163
24729505KEY G4
Adder
8.488
274814UNIV PK N;0U
Adder
6.519
972181SS23-001
Solar/Wind Harmer
7.709
274752CRETE EC ;2U
Adder
6.353
274753CRETE EC ;3U
Adder
6.353
970707AG2-453 GEN
Solar/Wind Harmer
36.006
274802UNIV PARK;5U
Adder
7.474
274826FISK ;BP
Adder
14.031
276772AC2-154 GEN
Solar/Wind Harmer
3.569
276806AD2-047 C O1
Solar/Wind Harmer
13.693
970941AG2-585 GEN
Solar/Wind Harmer
16
274800UNIV PARK;3U
Adder
7.462
972038AH1-567 GEN2
Adder
0.467
972228AH1-698 GEN2
Adder
4.737
276897AD1-100 C
Solar/Wind Harmer
36.905
939351AE1-166 GEN
Solar/Wind Harmer
7.541
274676JOLIET 29;8U
Adder
37.492
274729ELWOOD EC;1P
Adder
20.768
274730ELWOOD EC;6P
Adder
20.768
274734ELWOOD EC;8P
Adder
20.768
274736ELWOOD EC;9P
Adder
20.768
276893AG1-478 C
Solar/Wind Harmer
0.527
270535AF1-215 GEN1
Solar/Wind Harmer
5.712
943121AE2-341 GEN
Solar/Wind Harmer
18.813
943591AF1-030 GEN
Solar/Wind Harmer
12.542
276694AA1-018 GEN2
Solar/Wind Harmer
7.785
274682WAUKEGAN ;7U
Adder
22.136
964401AG1-302 GEN
Solar/Wind Harmer
11.14
274872LEEDK;1U
Solar/Wind Harmer
0.311
276805AD2-038 GEN
Solar/Wind Harmer
6.236
276799AD1-013 GEN
Solar/Wind Harmer
2.659
946671AF1-331 GEN
Solar/Wind Harmer
0.503
959141AF2-205 GEN
Solar/Wind Harmer
7.265
274855GSG-6 ;RU
Solar/Wind Harmer
4.438
274850MENDOTA H;RU
Solar/Wind Harmer
3.086
276602WESTBROOK C
Solar/Wind Harmer
2.554
276863AD2-134 GEN
Solar/Wind Harmer
2.146
972236AH1-702 GEN2
Adder
2.595
274760LEE CO EC;1U
Adder
10.813
274767LEE CO EC;8U
Adder
10.686
274807UNIV PK N;3U
Adder
6.505
274805UNIV PK N;1U
Adder
6.477
274811UNIV PK N;7U
Adder
6.463
972037AH1-567 GEN1
Adder
0.235
274827FISK ;RP
Adder
9.944
960591AF2-350 GEN
Solar/Wind Harmer
12.8
972227AH1-698 GEN1
Adder
3.335
274687WILL CNTY;4U
Adder
35.465
274687WILL CNTY;4U
Adder
35.465
274675JOLIET 29;7U
Adder
38.882
274675JOLIET 29;7U
Adder
37.493
971549AH1-272 GEN
Solar/Wind Harmer
23.441
274731ELWOOD EC;2P
Adder
20.768
274733ELWOOD EC;3P
Adder
20.768
274735ELWOOD EC;4P
Adder
20.768
274728ELWOOD EC;5P
Adder
20.768
970833AG2-524 GEN
Solar/Wind Harmer
11.011
970833AG2-524 GEN
Solar/Wind Harmer
5.121
270536AF1-215 GEN2
Solar/Wind Harmer
5.712
274746AC1-111 G10
Adder
6.996
274744AC1-111 GEN8
Adder
6.996
958711AF2-162 GEN
Solar/Wind Harmer
1.23
958391AF2-133 GEN
Solar/Wind Harmer
11.003
276868AE1-113 GEN
Solar/Wind Harmer
12.231
276882AE2-255 GEN
Solar/Wind Harmer
4.077
971177AH1-047 GEN
Solar/Wind Harmer
7.079
971411AH1-196 GEN
Solar/Wind Harmer
18.031
971675AH1-338 GEN
Solar/Wind Harmer
21.635
274823ROCKFORD ;21
Adder
23.136
24721805FLATG3
50/50
8.432
24721705FLATG2
50/50
154.591
24344105CKG2
50/50
11.53
270143AC1-141 CT2_
50/50
3.334
24639705ELKHART HY
50/50
0.224
970521AG2-332 GEN
50/50
15.95
24307105BERRINSP G
50/50
0.03
962761AG1-125 GEN
Solar/Wind Harmer
174.214
970149AG2-104 GEN
Solar/Wind Harmer
215.155
970155AG2-107 GEN
Solar/Wind Harmer
75.966
970245AG2-165 GEN
Solar/Wind Harmer
25.325
270505AE1-170 C O1
Solar/Wind Harmer
20.687
945111AF1-176 GEN
Solar/Wind Harmer
24.498
270063AE2-323 C
Solar/Wind Harmer
3.019
270449AD2-020 GEN
Solar/Wind Harmer
3.83
943021AE2-325 GEN
Solar/Wind Harmer
4.976
965011AG1-365 GEN
Solar/Wind Harmer
13.218
972207SS24-0001
Solar/Wind Harmer
29.024
274773LINCOLN ;4U
Adder
8.163
274774LINCOLN ;5U
Adder
8.163
274723RIVER EC ;12
Adder
23.321
274751CRETE EC ;1U
Adder
6.353
274754CRETE EC ;4U
Adder
6.353
276164X3-005 C
Solar/Wind Harmer
0.91
970373AG2-245 GEN
Solar/Wind Harmer
27.1
274812UNIV PK N;8U
Adder
6.463
276776AD2-060 GEN
Solar/Wind Harmer
0.541
274801UNIV PARK;4U
Adder
7.462
941551AE2-152 GEN
Solar/Wind Harmer
5.768
274676JOLIET 29;8U
Adder
38.881
274674JOLIET 9 ;6U
Adder
19.473
274732ELWOOD EC;7P
Adder
20.768
274871GR RIDGE ;2U
Solar/Wind Harmer
9.692
270055AF2-134 C O1
Solar/Wind Harmer
3.807
274745AC1-111 GEN9
Adder
6.996
276691AA1-018 GEN1
Solar/Wind Harmer
0.574
274682WAUKEGAN ;7U
Adder
22.136
274828WAUKEGAN ;BP
Adder
13.584
958381AF2-132 GEN
Solar/Wind Harmer
11.14
964861AG1-349 GEN
Solar/Wind Harmer
9.628
971917AH1-482 GEN
Solar/Wind Harmer
11.111
960751AF2-366 GEN
Solar/Wind Harmer
3.499
962781AG1-127 GEN
Solar/Wind Harmer
11.598
939401AE1-172 GEN
Solar/Wind Harmer
16.958
274872LEEDK;1U
Solar/Wind Harmer
9.989
965651AG1-433 GEN
Solar/Wind Harmer
6.647
276901AD2-066 C O1
Solar/Wind Harmer
4.262
971997AH1-543 GEN
Solar/Wind Harmer
18.988
276861AD2-134 GEN
Solar/Wind Harmer
2.146
274822ROCKFORD ;11
Adder
23.305
972235AH1-702 GEN1
Adder
2.984
274761LEE CO EC;2U
Adder
10.813
274766LEE CO EC;7U
Adder
10.686
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.936
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.15
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.3
MECLTFEXP_MEC->PJM
CLTF
15.891
SIGELTFEXP_SIGE->PJM
CLTF
0.293
LAGNLTFEXP_LAGN->PJM
CLTF
6.748
TVALTFEXP_TVA->PJM
CLTF
2.171
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
70.171
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
2.159
LGEELTFEXP_LGEE->PJM
CLTF
2.657
WECLTFEXP_WEC->PJM
CLTF
4.511
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.689
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428

Details for 05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.83 %
Rating:1301.0 MVA
Rating Type:B
MVA to Mitigate:1324.81
MW Contribution:15.72
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
12.696
24727105RPMNG2
50/50
0.96
942871AE2-306 GEN
Solar/Wind Harmer
3.988
270391AF1-285 GEN3
Solar/Wind Harmer
2.045
270485AE1-090_GEN
Solar/Wind Harmer
2.31
270491AE1-102 GEN2
Solar/Wind Harmer
1.473
270588AE1-091_GEN
Solar/Wind Harmer
11.055
270541AE2-072 C
Solar/Wind Harmer
3.949
958091AF2-103 GEN
Solar/Wind Harmer
0.137
270575GUS2 35KV
Solar/Wind Harmer
7.716
270258AD1-119 GEN
Solar/Wind Harmer
2.083
270044AE2-322 C
Solar/Wind Harmer
0.971
270404AC1-167 GEN
Solar/Wind Harmer
0.808
270191TR4_S_V150
Solar/Wind Harmer
2.178
270247TR4_N_V136
Solar/Wind Harmer
0.618
959331AF2-224 GEN
Solar/Wind Harmer
7.021
965021AG1-366 GEN
Solar/Wind Harmer
1.633
23906502RICHG2&3
Adder
0.834
958321AF2-126 GEN
Solar/Wind Harmer
0.818
241832AE2-181_GEN
Solar/Wind Harmer
0.917
23929302BS-PKR
Adder
0.797
970031AG2-029 GEN
Solar/Wind Harmer
15.724
270043AE2-236 GEN
Solar/Wind Harmer
2.792
270377AD1-106 GEN
Solar/Wind Harmer
2.779
945111AF1-176 GEN
Solar/Wind Harmer
2.498
247643Z2-116 C
Solar/Wind Harmer
0.031
971617AH1-308 GEN
Solar/Wind Harmer
2.565
247604X1-042
Adder
0.182
24441205WTRV SLR C
Solar/Wind Harmer
0.059
24727005RPMNG1
50/50
0.956
270223U2-072_GEN1
Solar/Wind Harmer
8.695
270578AF1-285 GEN2
Solar/Wind Harmer
5.317
270391AF1-285 GEN3
Solar/Wind Harmer
5.317
270462AD2-086
Solar/Wind Harmer
26.575
246936BC-WTG1
Solar/Wind Harmer
4.434
270489AE1-102 GEN1
Solar/Wind Harmer
1.473
965421AG1-410 GEN
Solar/Wind Harmer
32.755
247522W1-056 GEN
Solar/Wind Harmer
1.866
960841AF2-375 GEN
Solar/Wind Harmer
3.054
24695305TIMB G C
Solar/Wind Harmer
4.274
270361_3
Solar/Wind Harmer
6.549
247521TR3_G114
Solar/Wind Harmer
2.441
270246TR4_N_V150
Solar/Wind Harmer
0.618
965011AG1-365 GEN
Solar/Wind Harmer
7.021
23906502RICHG2&3
Adder
0.834
972301AH1-735 GEN
Adder
4.148
23906402RICHG1
Adder
0.83
241840AF1-064_GEN
Solar/Wind Harmer
0.763
23920202STRYCT
Adder
0.874
944231AF1-091 GEN
Solar/Wind Harmer
2.34
241808AF1-120 C
Solar/Wind Harmer
0.546
241858AF1-205_GEN
Solar/Wind Harmer
2.423
972253AH1-711 GEN
Adder
18.867
270063AE2-323 C
Solar/Wind Harmer
1.113
24639705ELKHART HY
Adder
0.07
945111AF1-176 GEN
Solar/Wind Harmer
7.883
270449AD2-020 GEN
Solar/Wind Harmer
1.227
943021AE2-325 GEN
Solar/Wind Harmer
1.594
270505AE1-170 C O1
Solar/Wind Harmer
6.536
270349AD2-093_GEN
Solar/Wind Helper
1.782
270036AE2-216 BAT
50/50
24.391
24727205RPMNG3
50/50
0.952
270578AF1-285 GEN2
Solar/Wind Harmer
2.045
270302AB2-170 GEN
Solar/Wind Harmer
31.946
270317AD1-130_GEN
Solar/Wind Harmer
12.246
957201AF2-014 GEN
Solar/Wind Harmer
5.139
270435AC2-044 GEN
Solar/Wind Harmer
2.266
270297AD1-101 GEN
Solar/Wind Harmer
2.38
247607V1-011 GEN
Solar/Wind Harmer
3.367
966831AG1-554 GEN
Solar/Wind Harmer
1.009
971989AH1-539 GEN
Solar/Wind Harmer
10.907
270499AE1-146 GEN
Solar/Wind Harmer
2.064
965051AG1-369 GEN
Solar/Wind Harmer
3.625
965041AG1-368 GEN
Solar/Wind Harmer
7.254
945411AF1-206 GEN
Solar/Wind Harmer
3.658
970817AG2-515 GEN
Solar/Wind Harmer
5.808
972211AH1-690 GEN
Adder
89.121
963791AG1-232 GEN
Solar/Wind Harmer
7.507
945641AF1-229 GEN
Solar/Wind Harmer
1.945
270071AF1-092 GEN
Solar/Wind Harmer
6.969
971549AH1-272 GEN
Solar/Wind Harmer
8.464
270024AE2-089 GEN
Solar/Wind Harmer
2.07
944161AF1-084 GEN
Solar/Wind Harmer
0.967
270284AF1-227 GEN1
Solar/Wind Helper
5.57
270286AF1-227 GEN2
Solar/Wind Helper
2.043
270287AF1-227 GEN3
Solar/Wind Helper
2.043
270520AE2-214 GEN
Solar/Wind Helper
2.488
270054AF2-122 C O1
Solar/Wind Helper
0.645
270466AD2-091
50/50
22.173
270224U2-072_GEN2
Solar/Wind Harmer
8.695
270227U2-072_GEN3
Solar/Wind Harmer
8.695
270228U2-072_GEN4
Solar/Wind Harmer
8.695
270231U2-072_GEN5
Solar/Wind Harmer
8.695
246938BC-WTG3
Solar/Wind Harmer
4.511
246937BC-WTG2
Solar/Wind Harmer
4.434
270007AE1-245 C
Solar/Wind Harmer
5.052
942801AE2-298 GEN
Solar/Wind Harmer
1.194
970611AG2-400 GEN
Solar/Wind Harmer
7.021
971677AH1-339 GEN
Solar/Wind Harmer
5.301
241996AE2-282_GEN
Solar/Wind Harmer
0.979
247620Y3-023
Adder
0.215
971231AH1-075 GEN
Solar/Wind Harmer
0.36
942221AE2-234 GEN
Solar/Wind Harmer
0.327
270216AD2-079_GEN
Solar/Wind Harmer
0.268
961051AF2-396 GEN
Solar/Wind Harmer
6.972
961051AF2-396 GEN
Solar/Wind Harmer
3.243
960981AF2-389 GEN
Solar/Wind Harmer
0.66
957891AF2-083 GEN
Solar/Wind Harmer
1.473
270471AD2-092_GEN
Solar/Wind Helper
1.782
946101AF1-275 GEN
Solar/Wind Helper
0.312
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.43
MECLTFEXP_MEC->PJM
CLTF
4.551
SIGELTFEXP_SIGE->PJM
CLTF
0.09
LAGNLTFEXP_LAGN->PJM
CLTF
2.316
TVALTFEXP_TVA->PJM
CLTF
0.854
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.063
NYPJM->LTFIMP_NY
CLTF
0.734
LGEELTFEXP_LGEE->PJM
CLTF
0.812
WECLTFEXP_WEC->PJM
CLTF
1.26
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.302
AG2-052LTFEXP_AG2-052->PJM
LTF
0.082
AH1-155LTFEXP_AH1-155->PJM
LTF
0.124

Details for 05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.88 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4885.66
MW Contribution:5.59
Bus #Bus NameTypeMW Contribution
24344305RKG2
50/50
10.006
270406AB1-088 CT1
50/50
3.172
970243AG2-164 GEN
Solar/Wind Harmer
10.48
970519AG2-331 GEN
Solar/Wind Harmer
46.579
970699AG2-449 GEN
Solar/Wind Harmer
4.479
970513AG2-328 GEN
Solar/Wind Harmer
4.889
970517AG2-330 GEN
Solar/Wind Harmer
29.332
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
11.21
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
964401AG1-302 GEN
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
16.013
270535AF1-215 GEN1
Solar/Wind Harmer
0.013
970349AG2-230 GEN
Solar/Wind Harmer
14.79
274772LINCOLN ;3U
Adder
11.903
942111AE2-223 GEN
Solar/Wind Harmer
3.184
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247642Z2-115 C
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
11.551
274753CRETE EC ;3U
Adder
11.551
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
29.335
959611AF2-252 GEN
Solar/Wind Harmer
3.259
274724RIVER EC ;11
Adder
24.801
972228AH1-698 GEN2
Adder
5.187
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.513
276806AD2-047 C O1
Solar/Wind Harmer
5.533
970941AG2-585 GEN
Solar/Wind Harmer
12.205
276668AB2-070 GEN1
Solar/Wind Harmer
0.356
970707AG2-453 GEN
Solar/Wind Harmer
31.865
274802UNIV PARK;5U
Adder
8.15
274800UNIV PARK;3U
Adder
8.146
972038AH1-567 GEN2
Adder
0.51
274826FISK ;BP
Adder
15.289
274729ELWOOD EC;1P
Adder
22.909
274730ELWOOD EC;6P
Adder
22.908
274734ELWOOD EC;8P
Adder
22.908
274736ELWOOD EC;9P
Adder
22.908
276893AG1-478 C
Solar/Wind Harmer
0.385
276621W2-048 GEN
Solar/Wind Harmer
0.49
276838X2-022 GEN2
Solar/Wind Harmer
0.547
274676JOLIET 29;8U
Adder
41.178
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
943121AE2-341 GEN
Solar/Wind Harmer
16.19
943591AF1-030 GEN
Solar/Wind Harmer
10.767
942481AE2-261 GEN
Solar/Wind Harmer
28.852
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274682WAUKEGAN ;7U
Adder
24.679
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
19.097
274872LEEDK;1U
Solar/Wind Harmer
0.35
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.013
274855GSG-6 ;RU
Solar/Wind Harmer
0.348
274850MENDOTA H;RU
Solar/Wind Harmer
0.112
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.17
959091AF2-200 GEN
Solar/Wind Harmer
18.922
970289AG2-191 GEN
Solar/Wind Harmer
1.04
970291AG2-192 GEN
Solar/Wind Harmer
0.945
274878BISHOP HL;2U
Solar/Wind Harmer
0.317
972236AH1-702 GEN2
Adder
2.96
24642205MAYFLWER
Adder
0.856
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
276157O29GEN1
Solar/Wind Harmer
1.512
970091AG2-072 GEN
50/50
198.882
270407AB1-088 ST1
50/50
3.172
970333AG2-219 GEN
Solar/Wind Harmer
12.809
270445AC2-157 GEN2
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
4.889
24791305MDL-5G
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
963741AG1-226 GEN
Solar/Wind Harmer
26.02
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
942601AE2-276 GEN
50/50
10.552
970239AG2-162 GEN
Solar/Wind Harmer
4.479
270444AC2-157 GEN1
Solar/Wind Harmer
0.006
971587AH1-292 GEN
Solar/Wind Harmer
9.286
970321AG2-212 GEN
Solar/Wind Harmer
4.889
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
966841AG1-555 GEN
Solar/Wind Harmer
1.266
970241AG2-163 GEN
Solar/Wind Harmer
6.413
945391AF1-204 GEN
Solar/Wind Harmer
11.343
965681AG1-436 GEN
Solar/Wind Harmer
12.338
965791AG1-447 GEN
Solar/Wind Harmer
9.048
274770LINCOLN ;1U
Adder
11.903
274771LINCOLN ;2U
Adder
11.903
960611AF2-352 GEN
Solar/Wind Harmer
3.259
274808UNIV PK N;4U
Adder
6.98
274888KELLY CRK;1U
Solar/Wind Harmer
0.573
274887GEN-1.85
Solar/Wind Harmer
0.257
276843GEN-1.7
Solar/Wind Harmer
0.316
958011AF2-095 GEN
Solar/Wind Harmer
14.061
972259AH1-714 GEN
Adder
26.685
274803UNIV PARK;6U
Adder
8.15
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
274674JOLIET 9 ;6U
Adder
21.442
24441505OLIV SLR
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.489
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.307
276916AD2-100_GEN
Solar/Wind Harmer
20.263
276911AD2-131_GEN
Solar/Wind Harmer
1.335
971573AH1-285 GEN
Solar/Wind Harmer
1.794
958491AF2-143 GEN
Solar/Wind Harmer
14.439
270526AF1-158 GEN
Solar/Wind Harmer
0.012
274879MINONK ;1U
Solar/Wind Harmer
0.405
274696ROCKY RD ;4P
Adder
15.67
274695ROCKY RD ;2P
Adder
15.309
274693ROCKY RD ;1P
Adder
15.158
274697ROCKY RD ;3P
Adder
4.159
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274683WAUKEGAN ;8U
Adder
28.915
274683WAUKEGAN ;8U
Adder
24.374
962691AG1-118 GEN
Solar/Wind Harmer
28.676
970921AG2-575 GEN
Solar/Wind Harmer
9.546
970921AG2-575 GEN
Solar/Wind Harmer
3.182
942991AE2-321 GEN
Solar/Wind Harmer
10.614
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.373
276646AC1-214 GEN2
Solar/Wind Harmer
0.373
971333AH1-146 GEN
Solar/Wind Harmer
18.962
971335AH1-147 GEN
Solar/Wind Harmer
18.962
971341AH1-150 GEN
Solar/Wind Harmer
18.922
971343AH1-151 GEN
Solar/Wind Harmer
18.922
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.222
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
5.315
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
12.51
274765LEE CO EC;6U
Adder
9.439
276741O09 GEN1
Solar/Wind Harmer
0.333
276708O09 GEN2
Solar/Wind Harmer
0.333
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
18.41
961051AF2-396 GEN
Solar/Wind Harmer
12.273
971613AH1-306 GEN
Solar/Wind Harmer
4.367
944541AF1-119 GEN
Solar/Wind Harmer
0.549
960971AF2-388 GEN
Solar/Wind Harmer
4.806
270599AE1-208 GEN
Solar/Wind Harmer
7.51
270031AE2-169
Solar/Wind Harmer
4.506
960441AF2-335 GEN
Solar/Wind Harmer
8.073
970825AG2-519 GEN
Solar/Wind Harmer
8.886
942221AE2-234 GEN
Solar/Wind Harmer
0.04
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
971605AH1-302 GEN
Solar/Wind Harmer
13.725
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
13.986
958381AF2-132 GEN
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.008
970373AG2-245 GEN
Solar/Wind Harmer
21.781
274773LINCOLN ;4U
Adder
11.903
274774LINCOLN ;5U
Adder
11.903
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
13.718
939401AE1-172 GEN
Solar/Wind Harmer
7.325
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274751CRETE EC ;1U
Adder
11.551
274754CRETE EC ;4U
Adder
11.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
8.079
274723RIVER EC ;12
Adder
25.097
274880W4-005 GEN4
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.01
276776AD2-060 GEN
Solar/Wind Harmer
1.019
274801UNIV PARK;4U
Adder
8.146
963831AG1-236 GEN
Solar/Wind Harmer
3.802
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
22.908
276615X2-022 GEN
Solar/Wind Harmer
0.102
274674JOLIET 9 ;6U
Adder
21.442
274676JOLIET 29;8U
Adder
42.703
276691AA1-018 GEN1
Solar/Wind Harmer
1.17
274745AC1-111 GEN9
Adder
7.736
965911AG1-460 GEN
Solar/Wind Harmer
1.93
276901AD2-066 C O1
Solar/Wind Harmer
0.01
971997AH1-543 GEN
Solar/Wind Harmer
5.053
274682WAUKEGAN ;7U
Adder
24.679
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274828WAUKEGAN ;BP
Adder
15.157
970569AG2-363 GEN
Solar/Wind Harmer
28.645
962781AG1-127 GEN
Solar/Wind Harmer
9.085
274872LEEDK;1U
Solar/Wind Harmer
0.006
276861AD2-134 GEN
Solar/Wind Harmer
0.17
957471AF2-041 GEN
Solar/Wind Harmer
28.383
959081AF2-199 GEN
Solar/Wind Harmer
9.461
971067AG2-660 GEN
Solar/Wind Harmer
3.154
970291AG2-192 GEN
Solar/Wind Harmer
1.229
274877BISHOP HL;1U
Solar/Wind Harmer
0.317
274822ROCKFORD ;11
Adder
26.534
972235AH1-702 GEN1
Adder
3.404
970819AG2-516 GEN
Solar/Wind Harmer
11.285
971475AH1-234 GEN
Solar/Wind Harmer
4.553
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
276158O29GEN2
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
9.741
945111AF1-176 GEN
Solar/Wind Harmer
16.452
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.8
270032AE2-172
Solar/Wind Harmer
6.065
276903AD2-071 C
Solar/Wind Harmer
10.136
270063AE2-323 C
Solar/Wind Harmer
0.007
965651AG1-433 GEN
Solar/Wind Harmer
2.403
958861AF2-177 GEN
Solar/Wind Harmer
3.539
945371AF1-202 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
2.846
270005AE1-210 C O1
Solar/Wind Harmer
1.734
965031AG1-367 GEN
Solar/Wind Harmer
8.001
970773AG2-487 GEN
Solar/Wind Harmer
1.37
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.665
965011AG1-365 GEN
Solar/Wind Harmer
7.456
247536S-71 GEN
Solar/Wind Harmer
0.284
944231AF1-091 GEN
Solar/Wind Harmer
1.864
971565AH1-281 GEN
Solar/Wind Harmer
1.306
247521TR3_G114
Solar/Wind Harmer
0.234
270246TR4_N_V150
Solar/Wind Harmer
0.041
24695305TIMB G C
Solar/Wind Harmer
0.002
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
7.473
965931AG1-462 GEN
Solar/Wind Harmer
23.338
24441205WTRV SLR C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
5.542
970031AG2-029 GEN
Solar/Wind Harmer
5.595
944531AF1-118 GEN
Solar/Wind Harmer
37.201
958821AF2-173 GEN
Solar/Wind Harmer
11.202
270004AE1-209 GEN
Solar/Wind Harmer
1.734
946031AF1-268 GEN
Solar/Wind Harmer
7.423
270356AE2-297 GEN
Solar/Wind Harmer
0.01
270437AC2-090 C
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.219
965021AG1-366 GEN
Solar/Wind Harmer
2.485
971617AH1-308 GEN
Solar/Wind Harmer
6.14
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.942
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24344205RKG1
50/50
10.236
24344205RKG1
50/50
10.215
24344305RKG2
50/50
10.196
270393AB1-087 CT1
50/50
3.172
270394AB1-087 ST1
50/50
3.172
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.805
971611AH1-305 GEN
Solar/Wind Harmer
6.537
958391AF2-133 GEN
Solar/Wind Harmer
0.002
270536AF1-215 GEN2
Solar/Wind Harmer
0.013
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971347AH1-153 GEN
Solar/Wind Harmer
14.79
274775LINCOLN ;6U
Adder
11.903
274776LINCOLN ;7U
Adder
11.903
274777LINCOLN ;8U
Adder
11.903
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.288
941731AE2-173 GEN
Solar/Wind Harmer
8.165
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
970169AG2-114 GEN
Solar/Wind Harmer
9.776
972227AH1-698 GEN1
Adder
3.652
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
7.072
274807UNIV PK N;3U
Adder
7.056
274805UNIV PK N;1U
Adder
7.026
274811UNIV PK N;7U
Adder
7.01
960591AF2-350 GEN
Solar/Wind Harmer
9.764
276849AB2-070 GEN2
Solar/Wind Harmer
0.356
276848AB2-070 GEN3
Solar/Wind Harmer
0.354
972037AH1-567 GEN1
Adder
0.256
274827FISK ;RP
Adder
10.835
970833AG2-524 GEN
Solar/Wind Harmer
10.702
970833AG2-524 GEN
Solar/Wind Harmer
7.134
274731ELWOOD EC;2P
Adder
22.909
274733ELWOOD EC;3P
Adder
22.909
274735ELWOOD EC;4P
Adder
22.909
274728ELWOOD EC;5P
Adder
22.908
274687WILL CNTY;4U
Adder
38.91
274687WILL CNTY;4U
Adder
38.91
274675JOLIET 29;7U
Adder
42.703
274675JOLIET 29;7U
Adder
41.178
971769AH1-391 GEN
Solar/Wind Harmer
10.786
274746AC1-111 G10
Adder
7.736
274744AC1-111 GEN8
Adder
7.736
944221AF1-090 GEN
Solar/Wind Harmer
5.66
276868AE1-113 GEN
Solar/Wind Harmer
1.928
276882AE2-255 GEN
Solar/Wind Harmer
1.124
926823AC1-168 GEN
Solar/Wind Harmer
1.627
971177AH1-047 GEN
Solar/Wind Harmer
5.86
971675AH1-338 GEN
Solar/Wind Harmer
3.702
957751AF2-069 GEN
Solar/Wind Harmer
0.313
971771AH1-392 GEN
Solar/Wind Harmer
9.483
971411AH1-196 GEN
Solar/Wind Harmer
14.224
971171AH1-044 GEN
Solar/Wind Harmer
18.922
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
1.796
274823ROCKFORD ;21
Adder
26.341
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
15.111
961011AF2-392 GEN
Solar/Wind Harmer
5.479
971619AH1-309 GEN
Solar/Wind Harmer
4.175
270071AF1-092 GEN
Solar/Wind Harmer
17.687
946321AF1-296 GEN
Solar/Wind Harmer
5.141
270594AE1-207 GEN
Solar/Wind Harmer
10.19
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
17.277
971609AH1-304 GEN
Solar/Wind Harmer
1.338
965101AG1-375 GEN
Solar/Wind Harmer
8.167
945581AF1-223 GEN
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.229
270240V3-007_GEN2
Solar/Wind Harmer
0.002
963791AG1-232 GEN
Solar/Wind Harmer
10.035
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270543AE2-219 C
Solar/Wind Harmer
0.004
965041AG1-368 GEN
Solar/Wind Harmer
6.799
971029AG2-637 GEN
Solar/Wind Harmer
9.99
971673AH1-337 GEN
Solar/Wind Harmer
4.275
965051AG1-369 GEN
Solar/Wind Harmer
3.198
970455AG2-298 GEN
Solar/Wind Harmer
4.116
970611AG2-400 GEN
Solar/Wind Harmer
7.456
970627AG2-408 GEN
Solar/Wind Harmer
2.237
270383AD1-128 GEN
Solar/Wind Harmer
0.005
964611AG1-324 GEN
Solar/Wind Harmer
0.555
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970883AG2-550 GEN
Solar/Wind Harmer
6.873
970885AG2-551 GEN
Solar/Wind Harmer
2.291
964571AG1-320 GEN
Solar/Wind Harmer
6.134
970235AG2-159 GEN
Solar/Wind Harmer
3.809
970235AG2-159 GEN
Solar/Wind Harmer
2.185
970653AG2-424 GEN
Solar/Wind Harmer
2.907
970653AG2-424 GEN
Solar/Wind Harmer
1.506
944201AF1-088_MTX
50/50
211.042
957141AF2-008_MTX
50/50
105.521
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
162.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.289
MECLTFEXP_MEC->PJM
CLTF
20.301
SIGELTFEXP_SIGE->PJM
CLTF
0.641
LAGNLTFEXP_LAGN->PJM
CLTF
11.815
TVALTFEXP_TVA->PJM
CLTF
4.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
121.55
NYPJM->LTFIMP_NY
CLTF
2.584
LGEELTFEXP_LGEE->PJM
CLTF
8.153
WECLTFEXP_WEC->PJM
CLTF
5.142
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.945
AG2-052LTFEXP_AG2-052->PJM
LTF
0.335
AH1-155LTFEXP_AH1-155->PJM
LTF
0.503

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.65 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1756.35
MW Contribution:14.51
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
7.813
942871AE2-306 GEN
Solar/Wind Harmer
0.907
270391AF1-285 GEN3
Solar/Wind Harmer
0.465
241974AD2-163_GEN2
Solar/Wind Harmer
1.957
270485AE1-090_GEN
Solar/Wind Harmer
0.566
942051AE2-217 GEN
Solar/Wind Harmer
13.984
970065AG2-057 GEN
Solar/Wind Harmer
0.767
970605AG2-385 GEN
Solar/Wind Harmer
3.836
241955AC1-078 GEN
Solar/Wind Harmer
5.001
970153AG2-106 GEN
Solar/Wind Harmer
9.124
270491AE1-102 GEN2
Solar/Wind Harmer
0.782
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.663
270247TR4_N_V136
Solar/Wind Harmer
0.472
270349AD2-093_GEN
Solar/Wind Harmer
4.882
971995AH1-542 GEN
Solar/Wind Harmer
11.801
270223U2-072_GEN1
Solar/Wind Harmer
1.977
270578AF1-285 GEN2
Solar/Wind Harmer
1.209
270391AF1-285 GEN3
Solar/Wind Harmer
1.209
270462AD2-086
Solar/Wind Harmer
6.507
241813AF1-122_GEN
Solar/Wind Harmer
4.908
970593AG2-378 GEN
Solar/Wind Harmer
1.421
962761AG1-125 GEN
Solar/Wind Harmer
20.924
970149AG2-104 GEN
Solar/Wind Harmer
25.841
970155AG2-107 GEN
Solar/Wind Harmer
9.124
246936BC-WTG1
Solar/Wind Harmer
2.355
270489AE1-102 GEN1
Solar/Wind Harmer
0.782
965421AG1-410 GEN
Solar/Wind Harmer
17.855
247521TR3_G114
Solar/Wind Harmer
1.865
270246TR4_N_V150
Solar/Wind Harmer
0.472
24695305TIMB G C
Solar/Wind Harmer
3.018
965011AG1-365 GEN
Solar/Wind Harmer
5.315
270159DARBY CT4
Adder
4.615
944231AF1-091 GEN
Solar/Wind Harmer
1.845
253343AC1-166 GEN
Solar/Wind Harmer
0.526
253325AC1-069 GEN
Solar/Wind Harmer
0.507
960071AF2-298 GEN
Solar/Wind Harmer
2.404
25326309TAIT D
Adder
0.526
270063AE2-323 C
Solar/Wind Harmer
1.058
965651AG1-433 GEN
Solar/Wind Harmer
2.549
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
958861AF2-177 GEN
Solar/Wind Harmer
5.061
247536S-71 GEN
Solar/Wind Harmer
1.868
945111AF1-176 GEN
Solar/Wind Harmer
8.176
270505AE1-170 C O1
Solar/Wind Harmer
6.853
945371AF1-202 GEN
Solar/Wind Harmer
3.186
270449AD2-020 GEN
Solar/Wind Harmer
1.276
943021AE2-325 GEN
Solar/Wind Harmer
1.657
970245AG2-165 GEN
Solar/Wind Harmer
8.061
970825AG2-519 GEN
Solar/Wind Harmer
1.042
270005AE1-210 C O1
Solar/Wind Harmer
2.413
965031AG1-367 GEN
Solar/Wind Harmer
4.414
970373AG2-245 GEN
Solar/Wind Harmer
9.267
274751CRETE EC ;1U
Adder
3.613
274754CRETE EC ;4U
Adder
3.613
274773LINCOLN ;4U
Adder
3.698
274774LINCOLN ;5U
Adder
3.698
274723RIVER EC ;12
Adder
7.85
274812UNIV PK N;8U
Adder
2.185
274801UNIV PARK;4U
Adder
2.53
274676JOLIET 29;8U
Adder
13.243
274674JOLIET 9 ;6U
Adder
6.64
274732ELWOOD EC;7P
Adder
7.088
270258AD1-119 GEN
Solar/Wind Harmer
1.498
959331AF2-224 GEN
Solar/Wind Harmer
5.315
965021AG1-366 GEN
Solar/Wind Harmer
1.236
270044AE2-322 C
Solar/Wind Harmer
0.691
270404AC1-167 GEN
Solar/Wind Harmer
0.576
270588AE1-091_GEN
Solar/Wind Harmer
5.503
270043AE2-236 GEN
Solar/Wind Harmer
2.714
253338AC1-165 GEN
Solar/Wind Harmer
0.526
253333AC1-068 GEN
Solar/Wind Harmer
0.507
970031AG2-029 GEN
Solar/Wind Harmer
14.514
971617AH1-308 GEN
Solar/Wind Harmer
2.796
944531AF1-118 GEN
Solar/Wind Harmer
16.819
270541AE2-072 C
Solar/Wind Harmer
2.163
962031AG1-047 GEN
Solar/Wind Harmer
1.413
957741AF2-068 GEN
Solar/Wind Harmer
7.01
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
970349AG2-230 GEN
Solar/Wind Harmer
6.938
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.591
24642205MAYFLWER
Adder
0.29
970513AG2-328 GEN
Solar/Wind Harmer
8.061
970517AG2-330 GEN
Solar/Wind Harmer
7.311
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.187
946031AF1-268 GEN
Solar/Wind Harmer
3.715
958821AF2-173 GEN
Solar/Wind Harmer
6.18
270004AE1-209 GEN
Solar/Wind Harmer
2.413
274752CRETE EC ;2U
Adder
3.613
274753CRETE EC ;3U
Adder
3.613
274772LINCOLN ;3U
Adder
3.698
274724RIVER EC ;11
Adder
7.758
274802UNIV PARK;5U
Adder
2.533
274826FISK ;BP
Adder
4.755
274800UNIV PARK;3U
Adder
2.53
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.606
274676JOLIET 29;8U
Adder
12.77
274729ELWOOD EC;1P
Adder
7.088
274730ELWOOD EC;6P
Adder
7.088
274734ELWOOD EC;8P
Adder
7.088
274736ELWOOD EC;9P
Adder
7.088
270466AD2-091
50/50
5.429
270471AD2-092_GEN
Solar/Wind Harmer
4.882
938701AE1-092 GEN
Solar/Wind Harmer
21.983
964601AG1-323 GEN
Solar/Wind Harmer
3.2
964601AG1-323 GEN
Solar/Wind Harmer
1.488
270224U2-072_GEN2
Solar/Wind Harmer
1.977
270227U2-072_GEN3
Solar/Wind Harmer
1.977
270228U2-072_GEN4
Solar/Wind Harmer
1.977
270231U2-072_GEN5
Solar/Wind Harmer
1.977
946101AF1-275 GEN
Solar/Wind Harmer
1.348
241960AC2-195 GEN
Solar/Wind Harmer
2.362
971201AH1-060 GEN
Solar/Wind Harmer
1.534
970077AG2-063 GEN
Solar/Wind Harmer
3.836
253378AE2-206_GEN
Solar/Wind Harmer
2.399
276820AF1-078_GEN
Solar/Wind Harmer
1.066
25326509SID D
Adder
0.833
246938BC-WTG3
Solar/Wind Harmer
2.396
246937BC-WTG2
Solar/Wind Harmer
2.355
270007AE1-245 C
Solar/Wind Harmer
3.344
942801AE2-298 GEN
Solar/Wind Harmer
0.852
970611AG2-400 GEN
Solar/Wind Harmer
5.315
270518AE2-148 GEN
Solar/Wind Harmer
6.282
942861AE2-305 GEN
Solar/Wind Harmer
3.928
25326109MON D
Adder
0.653
25322209TAIT E
Adder
4.68
25322209TAIT E
Adder
4.575
942221AE2-234 GEN
Solar/Wind Harmer
0.35
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.402
944541AF1-119 GEN
Solar/Wind Harmer
1.954
960971AF2-388 GEN
Solar/Wind Harmer
5.098
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.929
964611AG1-324 GEN
Solar/Wind Harmer
0.546
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.28
960981AF2-389 GEN
Solar/Wind Harmer
0.691
957891AF2-083 GEN
Solar/Wind Harmer
1.542
970883AG2-550 GEN
Solar/Wind Harmer
4.568
970885AG2-551 GEN
Solar/Wind Harmer
1.062
961051AF2-396 GEN
Solar/Wind Harmer
7.242
961051AF2-396 GEN
Solar/Wind Harmer
3.368
270526AF1-158 GEN
Solar/Wind Harmer
2.06
24441505OLIV SLR
Solar/Wind Harmer
0.061
970321AG2-212 GEN
Solar/Wind Harmer
8.061
270599AE1-208 GEN
Solar/Wind Harmer
3.679
270031AE2-169
Solar/Wind Harmer
3.679
965681AG1-436 GEN
Solar/Wind Harmer
5.624
965791AG1-447 GEN
Solar/Wind Harmer
2.877
970825AG2-519 GEN
Solar/Wind Harmer
4.672
960441AF2-335 GEN
Solar/Wind Harmer
4.424
274770LINCOLN ;1U
Adder
3.698
274771LINCOLN ;2U
Adder
3.698
274808UNIV PK N;4U
Adder
2.176
274803UNIV PARK;6U
Adder
2.533
972259AH1-714 GEN
Adder
8.267
274674JOLIET 9 ;6U
Adder
6.64
270036AE2-216 BAT
50/50
5.972
270284AF1-227 GEN1
Solar/Wind Harmer
6.854
270286AF1-227 GEN2
Solar/Wind Harmer
2.536
270287AF1-227 GEN3
Solar/Wind Harmer
2.536
270578AF1-285 GEN2
Solar/Wind Harmer
0.465
241973AD2-163_GEN1
Solar/Wind Harmer
1.957
270302AB2-170 GEN
Solar/Wind Harmer
7.822
270317AD1-130_GEN
Solar/Wind Harmer
2.998
270520AE2-214 GEN
Solar/Wind Harmer
5.402
970179AG2-119 GEN
Solar/Wind Harmer
6.794
962771AG1-126 GEN
Solar/Wind Harmer
20.924
957201AF2-014 GEN
Solar/Wind Harmer
2.73
270435AC2-044 GEN
Solar/Wind Harmer
1.204
241972AD1-140 GEN
Solar/Wind Harmer
2.573
247607V1-011 GEN
Solar/Wind Harmer
2.229
965051AG1-369 GEN
Solar/Wind Harmer
2.769
270297AD1-101 GEN
Solar/Wind Harmer
1.544
965041AG1-368 GEN
Solar/Wind Harmer
5.379
945631AF1-228 GEN
Solar/Wind Harmer
2.515
270156DARBY CT1
Adder
4.69
270157DARBY CT2
Adder
4.678
270158DARBY CT3
Adder
4.603
943861AF1-054 GEN
Solar/Wind Harmer
1.939
943851AF1-053 GEN
Solar/Wind Harmer
0.937
963791AG1-232 GEN
Solar/Wind Harmer
6.797
270071AF1-092 GEN
Solar/Wind Harmer
7.236
270024AE2-089 GEN
Solar/Wind Harmer
2.257
24729505KEY G4
Adder
3.093
253349AC2-067 GEN
Solar/Wind Harmer
2.35
253400AC2-068 GEN
Solar/Wind Harmer
0.945
961761AG1-017 GEN
Solar/Wind Harmer
0.2
958711AF2-162 GEN
Solar/Wind Harmer
0.472
25306009OHH W.
Adder
1.34
253372AE2-315 SEC3
Adder
0.879
253372AE2-315 SEC3
Adder
0.879
965101AG1-375 GEN
Solar/Wind Harmer
4.631
971347AH1-153 GEN
Solar/Wind Harmer
6.938
971771AH1-392 GEN
Solar/Wind Harmer
4.117
270543AE2-219 C
Solar/Wind Harmer
2.339
945581AF1-223 GEN
Solar/Wind Harmer
2.071
944161AF1-084 GEN
Solar/Wind Harmer
1.002
971769AH1-391 GEN
Solar/Wind Harmer
4.525
971029AG2-637 GEN
Solar/Wind Harmer
6.782
971673AH1-337 GEN
Solar/Wind Harmer
2.073
253383AE2-342_GEN
Solar/Wind Harmer
0.399
960681AF2-359 GEN
Solar/Wind Harmer
1.7
970115AG2-085 GEN
Solar/Wind Harmer
1.77
274775LINCOLN ;6U
Adder
3.698
274776LINCOLN ;7U
Adder
3.698
274777LINCOLN ;8U
Adder
3.698
274814UNIV PK N;0U
Adder
2.205
274807UNIV PK N;3U
Adder
2.2
274805UNIV PK N;1U
Adder
2.19
274811UNIV PK N;7U
Adder
2.185
972037AH1-567 GEN1
Adder
0.08
274827FISK ;RP
Adder
3.37
972227AH1-698 GEN1
Adder
1.131
274687WILL CNTY;4U
Adder
12.072
274687WILL CNTY;4U
Adder
12.072
274675JOLIET 29;7U
Adder
13.243
274675JOLIET 29;7U
Adder
12.77
274731ELWOOD EC;2P
Adder
7.088
274733ELWOOD EC;3P
Adder
7.088
274735ELWOOD EC;4P
Adder
7.088
274728ELWOOD EC;5P
Adder
7.088
270054AF2-122 C O1
Solar/Wind Helper
0.823
971549AH1-272 GEN
Solar/Wind Harmer
6.331
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.507
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.587
MECLTFEXP_MEC->PJM
CLTF
6.34
SIGELTFEXP_SIGE->PJM
CLTF
0.182
LAGNLTFEXP_LAGN->PJM
CLTF
5.126
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.351
TVALTFEXP_TVA->PJM
CLTF
2.378
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.92
NYPJM->LTFIMP_NY
CLTF
1.307
LGEELTFEXP_LGEE->PJM
CLTF
2.299
WECLTFEXP_WEC->PJM
CLTF
1.593
AG2-052LTFEXP_AG2-052->PJM
LTF
0.101
AH1-155LTFEXP_AH1-155->PJM
LTF
0.151

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.16 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1749.36
MW Contribution:14.48
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
5.416
270471AD2-092_GEN
Solar/Wind Harmer
4.871
938701AE1-092 GEN
Solar/Wind Harmer
21.927
964601AG1-323 GEN
Solar/Wind Harmer
3.191
964601AG1-323 GEN
Solar/Wind Harmer
1.484
270224U2-072_GEN2
Solar/Wind Harmer
1.972
270227U2-072_GEN3
Solar/Wind Harmer
1.972
270228U2-072_GEN4
Solar/Wind Harmer
1.972
270231U2-072_GEN5
Solar/Wind Harmer
1.972
946101AF1-275 GEN
Solar/Wind Harmer
1.344
241960AC2-195 GEN
Solar/Wind Harmer
2.356
971201AH1-060 GEN
Solar/Wind Harmer
1.53
970077AG2-063 GEN
Solar/Wind Harmer
3.824
253378AE2-206_GEN
Solar/Wind Harmer
2.393
276820AF1-078_GEN
Solar/Wind Harmer
1.063
25326509SID D
Adder
0.831
246938BC-WTG3
Solar/Wind Harmer
2.391
246937BC-WTG2
Solar/Wind Harmer
2.35
270007AE1-245 C
Solar/Wind Harmer
3.337
942801AE2-298 GEN
Solar/Wind Harmer
0.85
970611AG2-400 GEN
Solar/Wind Harmer
5.303
270518AE2-148 GEN
Solar/Wind Harmer
6.27
942861AE2-305 GEN
Solar/Wind Harmer
3.903
25326109MON D
Adder
0.652
25322209TAIT E
Adder
4.67
25322209TAIT E
Adder
4.565
942221AE2-234 GEN
Solar/Wind Harmer
0.35
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.397
944541AF1-119 GEN
Solar/Wind Harmer
1.949
960971AF2-388 GEN
Solar/Wind Harmer
5.087
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.927
964611AG1-324 GEN
Solar/Wind Harmer
0.545
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.279
960981AF2-389 GEN
Solar/Wind Harmer
0.69
957891AF2-083 GEN
Solar/Wind Harmer
1.539
970883AG2-550 GEN
Solar/Wind Harmer
4.558
970885AG2-551 GEN
Solar/Wind Harmer
1.06
961051AF2-396 GEN
Solar/Wind Harmer
7.227
961051AF2-396 GEN
Solar/Wind Harmer
3.361
270526AF1-158 GEN
Solar/Wind Harmer
2.056
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.044
270599AE1-208 GEN
Solar/Wind Harmer
3.671
270031AE2-169
Solar/Wind Harmer
3.671
965681AG1-436 GEN
Solar/Wind Harmer
5.612
965791AG1-447 GEN
Solar/Wind Harmer
2.871
970825AG2-519 GEN
Solar/Wind Harmer
4.662
960441AF2-335 GEN
Solar/Wind Harmer
4.415
274770LINCOLN ;1U
Adder
3.69
274771LINCOLN ;2U
Adder
3.69
274808UNIV PK N;4U
Adder
2.171
274803UNIV PARK;6U
Adder
2.528
972259AH1-714 GEN
Adder
8.249
274674JOLIET 9 ;6U
Adder
6.626
270036AE2-216 BAT
50/50
5.958
270284AF1-227 GEN1
Solar/Wind Harmer
6.838
270286AF1-227 GEN2
Solar/Wind Harmer
2.53
270287AF1-227 GEN3
Solar/Wind Harmer
2.53
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.951
270302AB2-170 GEN
Solar/Wind Harmer
7.804
270317AD1-130_GEN
Solar/Wind Harmer
2.992
270520AE2-214 GEN
Solar/Wind Harmer
5.387
970179AG2-119 GEN
Solar/Wind Harmer
6.779
962771AG1-126 GEN
Solar/Wind Harmer
20.876
957201AF2-014 GEN
Solar/Wind Harmer
2.724
270435AC2-044 GEN
Solar/Wind Harmer
1.201
241972AD1-140 GEN
Solar/Wind Harmer
2.566
270349AD2-093_GEN
Solar/Wind Harmer
4.871
971995AH1-542 GEN
Solar/Wind Harmer
11.773
270223U2-072_GEN1
Solar/Wind Harmer
1.972
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270462AD2-086
Solar/Wind Harmer
6.492
241813AF1-122_GEN
Solar/Wind Harmer
4.897
970593AG2-378 GEN
Solar/Wind Harmer
1.416
962761AG1-125 GEN
Solar/Wind Harmer
20.876
970149AG2-104 GEN
Solar/Wind Harmer
25.782
970155AG2-107 GEN
Solar/Wind Harmer
9.103
246936BC-WTG1
Solar/Wind Harmer
2.35
270489AE1-102 GEN1
Solar/Wind Harmer
0.781
965421AG1-410 GEN
Solar/Wind Harmer
17.815
247521TR3_G114
Solar/Wind Harmer
1.86
270246TR4_N_V150
Solar/Wind Harmer
0.471
24695305TIMB G C
Solar/Wind Harmer
3.012
965011AG1-365 GEN
Solar/Wind Harmer
5.303
270159DARBY CT4
Adder
4.607
944231AF1-091 GEN
Solar/Wind Harmer
1.841
253343AC1-166 GEN
Solar/Wind Harmer
0.525
253325AC1-069 GEN
Solar/Wind Harmer
0.506
960071AF2-298 GEN
Solar/Wind Harmer
2.398
25326309TAIT D
Adder
0.525
270063AE2-323 C
Solar/Wind Harmer
1.055
965651AG1-433 GEN
Solar/Wind Harmer
2.544
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
958861AF2-177 GEN
Solar/Wind Harmer
5.05
247536S-71 GEN
Solar/Wind Harmer
1.864
945111AF1-176 GEN
Solar/Wind Harmer
8.158
270505AE1-170 C O1
Solar/Wind Harmer
6.839
945371AF1-202 GEN
Solar/Wind Harmer
3.179
270449AD2-020 GEN
Solar/Wind Harmer
1.273
943021AE2-325 GEN
Solar/Wind Harmer
1.654
970245AG2-165 GEN
Solar/Wind Harmer
8.044
970825AG2-519 GEN
Solar/Wind Harmer
1.04
270005AE1-210 C O1
Solar/Wind Harmer
2.407
965031AG1-367 GEN
Solar/Wind Harmer
4.405
970373AG2-245 GEN
Solar/Wind Harmer
9.248
274751CRETE EC ;1U
Adder
3.605
274754CRETE EC ;4U
Adder
3.605
274773LINCOLN ;4U
Adder
3.69
274774LINCOLN ;5U
Adder
3.69
274723RIVER EC ;12
Adder
7.833
274812UNIV PK N;8U
Adder
2.181
274801UNIV PARK;4U
Adder
2.525
274676JOLIET 29;8U
Adder
13.215
274674JOLIET 9 ;6U
Adder
6.626
274732ELWOOD EC;7P
Adder
7.073
270475AD2-096_GEN
50/50
7.794
942871AE2-306 GEN
Solar/Wind Harmer
0.905
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
241974AD2-163_GEN2
Solar/Wind Harmer
1.951
270485AE1-090_GEN
Solar/Wind Harmer
0.564
942051AE2-217 GEN
Solar/Wind Harmer
13.946
970065AG2-057 GEN
Solar/Wind Harmer
0.765
970605AG2-385 GEN
Solar/Wind Harmer
3.824
241955AC1-078 GEN
Solar/Wind Harmer
4.991
970153AG2-106 GEN
Solar/Wind Harmer
9.103
270491AE1-102 GEN2
Solar/Wind Harmer
0.781
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.66
270247TR4_N_V136
Solar/Wind Harmer
0.471
270258AD1-119 GEN
Solar/Wind Harmer
1.494
959331AF2-224 GEN
Solar/Wind Harmer
5.303
965021AG1-366 GEN
Solar/Wind Harmer
1.233
270044AE2-322 C
Solar/Wind Harmer
0.69
270404AC1-167 GEN
Solar/Wind Harmer
0.574
270588AE1-091_GEN
Solar/Wind Harmer
5.492
270043AE2-236 GEN
Solar/Wind Harmer
2.708
253338AC1-165 GEN
Solar/Wind Harmer
0.525
253333AC1-068 GEN
Solar/Wind Harmer
0.506
970031AG2-029 GEN
Solar/Wind Harmer
14.483
971617AH1-308 GEN
Solar/Wind Harmer
2.79
944531AF1-118 GEN
Solar/Wind Harmer
16.782
270541AE2-072 C
Solar/Wind Harmer
2.158
962031AG1-047 GEN
Solar/Wind Harmer
1.409
957741AF2-068 GEN
Solar/Wind Harmer
6.995
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
970349AG2-230 GEN
Solar/Wind Harmer
6.923
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.586
24642205MAYFLWER
Adder
0.289
970513AG2-328 GEN
Solar/Wind Harmer
8.044
970517AG2-330 GEN
Solar/Wind Harmer
7.296
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.186
946031AF1-268 GEN
Solar/Wind Harmer
3.707
958821AF2-173 GEN
Solar/Wind Harmer
6.167
270004AE1-209 GEN
Solar/Wind Harmer
2.407
274752CRETE EC ;2U
Adder
3.605
274753CRETE EC ;3U
Adder
3.605
274772LINCOLN ;3U
Adder
3.69
274724RIVER EC ;11
Adder
7.742
274802UNIV PARK;5U
Adder
2.528
274826FISK ;BP
Adder
4.745
274800UNIV PARK;3U
Adder
2.525
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.603
274676JOLIET 29;8U
Adder
12.743
274729ELWOOD EC;1P
Adder
7.072
274730ELWOOD EC;6P
Adder
7.073
274734ELWOOD EC;8P
Adder
7.073
274736ELWOOD EC;9P
Adder
7.073
247607V1-011 GEN
Solar/Wind Harmer
2.224
965051AG1-369 GEN
Solar/Wind Harmer
2.763
270297AD1-101 GEN
Solar/Wind Harmer
1.54
965041AG1-368 GEN
Solar/Wind Harmer
5.367
945631AF1-228 GEN
Solar/Wind Harmer
2.511
270156DARBY CT1
Adder
4.681
270157DARBY CT2
Adder
4.67
270158DARBY CT3
Adder
4.595
963791AG1-232 GEN
Solar/Wind Harmer
6.783
943861AF1-054 GEN
Solar/Wind Harmer
1.926
943851AF1-053 GEN
Solar/Wind Harmer
0.931
270071AF1-092 GEN
Solar/Wind Harmer
7.22
270024AE2-089 GEN
Solar/Wind Harmer
2.252
24729505KEY G4
Adder
3.086
253349AC2-067 GEN
Solar/Wind Harmer
2.345
253400AC2-068 GEN
Solar/Wind Harmer
0.943
961761AG1-017 GEN
Solar/Wind Harmer
0.2
958711AF2-162 GEN
Solar/Wind Harmer
0.471
25306009OHH W.
Adder
1.337
253372AE2-315 SEC3
Adder
0.877
253372AE2-315 SEC3
Adder
0.877
965101AG1-375 GEN
Solar/Wind Harmer
4.621
971347AH1-153 GEN
Solar/Wind Harmer
6.923
971771AH1-392 GEN
Solar/Wind Harmer
4.108
270543AE2-219 C
Solar/Wind Harmer
2.334
945581AF1-223 GEN
Solar/Wind Harmer
2.066
944161AF1-084 GEN
Solar/Wind Harmer
1
971769AH1-391 GEN
Solar/Wind Harmer
4.515
971029AG2-637 GEN
Solar/Wind Harmer
6.767
971673AH1-337 GEN
Solar/Wind Harmer
2.069
960681AF2-359 GEN
Solar/Wind Harmer
1.696
253383AE2-342_GEN
Solar/Wind Harmer
0.396
970115AG2-085 GEN
Solar/Wind Harmer
1.766
274775LINCOLN ;6U
Adder
3.69
274776LINCOLN ;7U
Adder
3.69
274777LINCOLN ;8U
Adder
3.69
274814UNIV PK N;0U
Adder
2.2
274807UNIV PK N;3U
Adder
2.195
274805UNIV PK N;1U
Adder
2.186
274811UNIV PK N;7U
Adder
2.181
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.363
972227AH1-698 GEN1
Adder
1.129
274687WILL CNTY;4U
Adder
12.046
274687WILL CNTY;4U
Adder
12.046
274675JOLIET 29;7U
Adder
13.215
274675JOLIET 29;7U
Adder
12.743
274731ELWOOD EC;2P
Adder
7.072
274733ELWOOD EC;3P
Adder
7.072
274735ELWOOD EC;4P
Adder
7.072
274728ELWOOD EC;5P
Adder
7.073
270054AF2-122 C O1
Solar/Wind Helper
0.817
971549AH1-272 GEN
Solar/Wind Harmer
6.317
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.568
MECLTFEXP_MEC->PJM
CLTF
6.327
SIGELTFEXP_SIGE->PJM
CLTF
0.182
LAGNLTFEXP_LAGN->PJM
CLTF
5.116
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.348
TVALTFEXP_TVA->PJM
CLTF
2.374
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.837
NYPJM->LTFIMP_NY
CLTF
1.305
LGEELTFEXP_LGEE->PJM
CLTF
2.295
WECLTFEXP_WEC->PJM
CLTF
1.59
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.151

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.05 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1747.91
MW Contribution:14.48
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
5.413
270471AD2-092_GEN
Solar/Wind Harmer
4.868
938701AE1-092 GEN
Solar/Wind Harmer
21.914
964601AG1-323 GEN
Solar/Wind Harmer
3.189
964601AG1-323 GEN
Solar/Wind Harmer
1.483
270224U2-072_GEN2
Solar/Wind Harmer
1.971
270227U2-072_GEN3
Solar/Wind Harmer
1.971
270228U2-072_GEN4
Solar/Wind Harmer
1.971
270231U2-072_GEN5
Solar/Wind Harmer
1.971
946101AF1-275 GEN
Solar/Wind Harmer
1.343
241960AC2-195 GEN
Solar/Wind Harmer
2.355
270349AD2-093_GEN
Solar/Wind Harmer
4.868
971995AH1-542 GEN
Solar/Wind Harmer
11.766
270223U2-072_GEN1
Solar/Wind Harmer
1.971
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270462AD2-086
Solar/Wind Harmer
6.488
241813AF1-122_GEN
Solar/Wind Harmer
4.895
970593AG2-378 GEN
Solar/Wind Harmer
1.415
962761AG1-125 GEN
Solar/Wind Harmer
20.865
970149AG2-104 GEN
Solar/Wind Harmer
25.768
970155AG2-107 GEN
Solar/Wind Harmer
9.098
246936BC-WTG1
Solar/Wind Harmer
2.349
270489AE1-102 GEN1
Solar/Wind Harmer
0.78
965421AG1-410 GEN
Solar/Wind Harmer
17.806
247521TR3_G114
Solar/Wind Harmer
1.86
270246TR4_N_V150
Solar/Wind Harmer
0.47
24695305TIMB G C
Solar/Wind Harmer
3.01
965011AG1-365 GEN
Solar/Wind Harmer
5.301
270159DARBY CT4
Adder
4.605
944231AF1-091 GEN
Solar/Wind Harmer
1.84
253343AC1-166 GEN
Solar/Wind Harmer
0.525
253325AC1-069 GEN
Solar/Wind Harmer
0.506
960071AF2-298 GEN
Solar/Wind Harmer
2.397
25326309TAIT D
Adder
0.525
270063AE2-323 C
Solar/Wind Harmer
1.055
965651AG1-433 GEN
Solar/Wind Harmer
2.542
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
958861AF2-177 GEN
Solar/Wind Harmer
5.048
247536S-71 GEN
Solar/Wind Harmer
1.863
945111AF1-176 GEN
Solar/Wind Harmer
8.154
270505AE1-170 C O1
Solar/Wind Harmer
6.835
945371AF1-202 GEN
Solar/Wind Harmer
3.177
270449AD2-020 GEN
Solar/Wind Harmer
1.272
943021AE2-325 GEN
Solar/Wind Harmer
1.653
970245AG2-165 GEN
Solar/Wind Harmer
8.04
970825AG2-519 GEN
Solar/Wind Harmer
1.04
270005AE1-210 C O1
Solar/Wind Harmer
2.406
965031AG1-367 GEN
Solar/Wind Harmer
4.403
970373AG2-245 GEN
Solar/Wind Harmer
9.243
274751CRETE EC ;1U
Adder
3.603
274754CRETE EC ;4U
Adder
3.603
274773LINCOLN ;4U
Adder
3.688
274774LINCOLN ;5U
Adder
3.688
274723RIVER EC ;12
Adder
7.829
274812UNIV PK N;8U
Adder
2.18
274801UNIV PARK;4U
Adder
2.524
274676JOLIET 29;8U
Adder
13.208
274674JOLIET 9 ;6U
Adder
6.622
274732ELWOOD EC;7P
Adder
7.069
270475AD2-096_GEN
50/50
7.79
942871AE2-306 GEN
Solar/Wind Harmer
0.904
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
241974AD2-163_GEN2
Solar/Wind Harmer
1.95
270485AE1-090_GEN
Solar/Wind Harmer
0.564
942051AE2-217 GEN
Solar/Wind Harmer
13.937
970065AG2-057 GEN
Solar/Wind Harmer
0.765
970605AG2-385 GEN
Solar/Wind Harmer
3.821
241955AC1-078 GEN
Solar/Wind Harmer
4.989
970153AG2-106 GEN
Solar/Wind Harmer
9.098
270491AE1-102 GEN2
Solar/Wind Harmer
0.78
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.659
270247TR4_N_V136
Solar/Wind Harmer
0.47
270258AD1-119 GEN
Solar/Wind Harmer
1.494
959331AF2-224 GEN
Solar/Wind Harmer
5.301
965021AG1-366 GEN
Solar/Wind Harmer
1.233
270044AE2-322 C
Solar/Wind Harmer
0.689
270404AC1-167 GEN
Solar/Wind Harmer
0.574
270588AE1-091_GEN
Solar/Wind Harmer
5.49
270043AE2-236 GEN
Solar/Wind Harmer
2.707
253338AC1-165 GEN
Solar/Wind Harmer
0.525
253333AC1-068 GEN
Solar/Wind Harmer
0.506
970031AG2-029 GEN
Solar/Wind Harmer
14.476
971617AH1-308 GEN
Solar/Wind Harmer
2.788
944531AF1-118 GEN
Solar/Wind Harmer
16.774
270541AE2-072 C
Solar/Wind Harmer
2.157
962031AG1-047 GEN
Solar/Wind Harmer
1.409
957741AF2-068 GEN
Solar/Wind Harmer
6.991
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
970349AG2-230 GEN
Solar/Wind Harmer
6.92
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.584
24642205MAYFLWER
Adder
0.289
970513AG2-328 GEN
Solar/Wind Harmer
8.04
970517AG2-330 GEN
Solar/Wind Harmer
7.292
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.186
946031AF1-268 GEN
Solar/Wind Harmer
3.705
958821AF2-173 GEN
Solar/Wind Harmer
6.164
270004AE1-209 GEN
Solar/Wind Harmer
2.406
274752CRETE EC ;2U
Adder
3.603
274753CRETE EC ;3U
Adder
3.603
274772LINCOLN ;3U
Adder
3.688
274724RIVER EC ;11
Adder
7.738
274802UNIV PARK;5U
Adder
2.527
270036AE2-216 BAT
50/50
5.955
270284AF1-227 GEN1
Solar/Wind Harmer
6.834
270286AF1-227 GEN2
Solar/Wind Harmer
2.528
270287AF1-227 GEN3
Solar/Wind Harmer
2.528
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.95
270302AB2-170 GEN
Solar/Wind Harmer
7.799
270317AD1-130_GEN
Solar/Wind Harmer
2.99
270520AE2-214 GEN
Solar/Wind Harmer
5.383
970179AG2-119 GEN
Solar/Wind Harmer
6.775
962771AG1-126 GEN
Solar/Wind Harmer
20.865
957201AF2-014 GEN
Solar/Wind Harmer
2.722
270435AC2-044 GEN
Solar/Wind Harmer
1.201
241972AD1-140 GEN
Solar/Wind Harmer
2.565
247607V1-011 GEN
Solar/Wind Harmer
2.223
965051AG1-369 GEN
Solar/Wind Harmer
2.761
270297AD1-101 GEN
Solar/Wind Harmer
1.539
965041AG1-368 GEN
Solar/Wind Harmer
5.365
945631AF1-228 GEN
Solar/Wind Harmer
2.51
270156DARBY CT1
Adder
4.68
270157DARBY CT2
Adder
4.668
270158DARBY CT3
Adder
4.594
963791AG1-232 GEN
Solar/Wind Harmer
6.779
943861AF1-054 GEN
Solar/Wind Harmer
1.923
943851AF1-053 GEN
Solar/Wind Harmer
0.929
270071AF1-092 GEN
Solar/Wind Harmer
7.217
270024AE2-089 GEN
Solar/Wind Harmer
2.251
24729505KEY G4
Adder
3.085
253349AC2-067 GEN
Solar/Wind Harmer
2.344
253400AC2-068 GEN
Solar/Wind Harmer
0.943
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.471
25306009OHH W.
Adder
1.337
253372AE2-315 SEC3
Adder
0.876
253372AE2-315 SEC3
Adder
0.876
965101AG1-375 GEN
Solar/Wind Harmer
4.618
971347AH1-153 GEN
Solar/Wind Harmer
6.92
971771AH1-392 GEN
Solar/Wind Harmer
4.106
270543AE2-219 C
Solar/Wind Harmer
2.333
945581AF1-223 GEN
Solar/Wind Harmer
2.065
944161AF1-084 GEN
Solar/Wind Harmer
1
971769AH1-391 GEN
Solar/Wind Harmer
4.513
971029AG2-637 GEN
Solar/Wind Harmer
6.764
971673AH1-337 GEN
Solar/Wind Harmer
2.068
960681AF2-359 GEN
Solar/Wind Harmer
1.695
253383AE2-342_GEN
Solar/Wind Harmer
0.395
970115AG2-085 GEN
Solar/Wind Harmer
1.765
274826FISK ;BP
Adder
4.742
274800UNIV PARK;3U
Adder
2.524
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.602
274676JOLIET 29;8U
Adder
12.736
274729ELWOOD EC;1P
Adder
7.069
274730ELWOOD EC;6P
Adder
7.069
274734ELWOOD EC;8P
Adder
7.069
274736ELWOOD EC;9P
Adder
7.069
971201AH1-060 GEN
Solar/Wind Harmer
1.53
970077AG2-063 GEN
Solar/Wind Harmer
3.821
253378AE2-206_GEN
Solar/Wind Harmer
2.391
276820AF1-078_GEN
Solar/Wind Harmer
1.062
25326509SID D
Adder
0.831
246938BC-WTG3
Solar/Wind Harmer
2.389
246937BC-WTG2
Solar/Wind Harmer
2.349
270007AE1-245 C
Solar/Wind Harmer
3.335
942801AE2-298 GEN
Solar/Wind Harmer
0.849
970611AG2-400 GEN
Solar/Wind Harmer
5.301
270518AE2-148 GEN
Solar/Wind Harmer
6.267
942861AE2-305 GEN
Solar/Wind Harmer
3.897
25326109MON D
Adder
0.651
25322209TAIT E
Adder
4.667
25322209TAIT E
Adder
4.562
942221AE2-234 GEN
Solar/Wind Harmer
0.349
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.396
944541AF1-119 GEN
Solar/Wind Harmer
1.948
960971AF2-388 GEN
Solar/Wind Harmer
5.085
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.926
964611AG1-324 GEN
Solar/Wind Harmer
0.545
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.279
957891AF2-083 GEN
Solar/Wind Harmer
1.538
960981AF2-389 GEN
Solar/Wind Harmer
0.689
970883AG2-550 GEN
Solar/Wind Harmer
4.556
970885AG2-551 GEN
Solar/Wind Harmer
1.06
961051AF2-396 GEN
Solar/Wind Harmer
7.223
961051AF2-396 GEN
Solar/Wind Harmer
3.36
270526AF1-158 GEN
Solar/Wind Harmer
2.055
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.04
270599AE1-208 GEN
Solar/Wind Harmer
3.669
270031AE2-169
Solar/Wind Harmer
3.669
965681AG1-436 GEN
Solar/Wind Harmer
5.609
965791AG1-447 GEN
Solar/Wind Harmer
2.87
970825AG2-519 GEN
Solar/Wind Harmer
4.659
960441AF2-335 GEN
Solar/Wind Harmer
4.412
274770LINCOLN ;1U
Adder
3.688
274771LINCOLN ;2U
Adder
3.688
274808UNIV PK N;4U
Adder
2.17
274803UNIV PARK;6U
Adder
2.527
972259AH1-714 GEN
Adder
8.245
274674JOLIET 9 ;6U
Adder
6.622
274775LINCOLN ;6U
Adder
3.688
274776LINCOLN ;7U
Adder
3.688
274777LINCOLN ;8U
Adder
3.688
274814UNIV PK N;0U
Adder
2.199
274807UNIV PK N;3U
Adder
2.194
274805UNIV PK N;1U
Adder
2.185
274811UNIV PK N;7U
Adder
2.18
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.361
972227AH1-698 GEN1
Adder
1.128
274687WILL CNTY;4U
Adder
12.041
274687WILL CNTY;4U
Adder
12.041
274675JOLIET 29;7U
Adder
13.208
274675JOLIET 29;7U
Adder
12.736
274731ELWOOD EC;2P
Adder
7.069
274733ELWOOD EC;3P
Adder
7.069
274735ELWOOD EC;4P
Adder
7.069
274728ELWOOD EC;5P
Adder
7.069
270054AF2-122 C O1
Solar/Wind Helper
0.816
971549AH1-272 GEN
Solar/Wind Harmer
6.314
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.361
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.564
MECLTFEXP_MEC->PJM
CLTF
6.323
SIGELTFEXP_SIGE->PJM
CLTF
0.181
LAGNLTFEXP_LAGN->PJM
CLTF
5.114
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.347
TVALTFEXP_TVA->PJM
CLTF
2.373
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.818
NYPJM->LTFIMP_NY
CLTF
1.304
LGEELTFEXP_LGEE->PJM
CLTF
2.294
WECLTFEXP_WEC->PJM
CLTF
1.589
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.44 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1584.27
MW Contribution:14.42
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
7.755
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
241974AD2-163_GEN2
Solar/Wind Harmer
1.939
270485AE1-090_GEN
Solar/Wind Harmer
0.562
942051AE2-217 GEN
Solar/Wind Harmer
13.864
970065AG2-057 GEN
Solar/Wind Harmer
0.762
970605AG2-385 GEN
Solar/Wind Harmer
3.797
241955AC1-078 GEN
Solar/Wind Harmer
4.97
970153AG2-106 GEN
Solar/Wind Harmer
9.059
270491AE1-102 GEN2
Solar/Wind Harmer
0.777
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.652
270247TR4_N_V136
Solar/Wind Harmer
0.468
270258AD1-119 GEN
Solar/Wind Harmer
1.487
959331AF2-224 GEN
Solar/Wind Harmer
5.279
965021AG1-366 GEN
Solar/Wind Harmer
1.228
270044AE2-322 C
Solar/Wind Harmer
0.687
270404AC1-167 GEN
Solar/Wind Harmer
0.572
270588AE1-091_GEN
Solar/Wind Harmer
5.47
270043AE2-236 GEN
Solar/Wind Harmer
2.696
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Harmer
0.505
970031AG2-029 GEN
Solar/Wind Harmer
14.416
971617AH1-308 GEN
Solar/Wind Harmer
2.777
944531AF1-118 GEN
Solar/Wind Harmer
16.706
270541AE2-072 C
Solar/Wind Harmer
2.148
962031AG1-047 GEN
Solar/Wind Harmer
1.403
957741AF2-068 GEN
Solar/Wind Harmer
6.963
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
970349AG2-230 GEN
Solar/Wind Harmer
6.892
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.574
24642205MAYFLWER
Adder
0.288
970513AG2-328 GEN
Solar/Wind Harmer
8.007
970517AG2-330 GEN
Solar/Wind Harmer
7.263
24441205WTRV SLR C
Solar/Wind Harmer
0.06
247604X1-042
Adder
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.69
958821AF2-173 GEN
Solar/Wind Harmer
6.139
270004AE1-209 GEN
Solar/Wind Harmer
2.397
274752CRETE EC ;2U
Adder
3.589
274753CRETE EC ;3U
Adder
3.589
274772LINCOLN ;3U
Adder
3.673
274724RIVER EC ;11
Adder
7.706
274802UNIV PARK;5U
Adder
2.517
274826FISK ;BP
Adder
4.723
274800UNIV PARK;3U
Adder
2.514
972038AH1-567 GEN2
Adder
0.157
972228AH1-698 GEN2
Adder
1.596
270349AD2-093_GEN
Solar/Wind Harmer
4.846
971995AH1-542 GEN
Solar/Wind Harmer
11.714
270223U2-072_GEN1
Solar/Wind Harmer
1.963
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270462AD2-086
Solar/Wind Harmer
6.46
241813AF1-122_GEN
Solar/Wind Harmer
4.874
970593AG2-378 GEN
Solar/Wind Harmer
1.406
962761AG1-125 GEN
Solar/Wind Harmer
20.775
970149AG2-104 GEN
Solar/Wind Harmer
25.657
970155AG2-107 GEN
Solar/Wind Harmer
9.059
246936BC-WTG1
Solar/Wind Harmer
2.339
270489AE1-102 GEN1
Solar/Wind Harmer
0.777
965421AG1-410 GEN
Solar/Wind Harmer
17.731
247521TR3_G114
Solar/Wind Harmer
1.852
270246TR4_N_V150
Solar/Wind Harmer
0.468
24695305TIMB G C
Solar/Wind Harmer
2.998
965011AG1-365 GEN
Solar/Wind Harmer
5.279
270159DARBY CT4
Adder
4.59
944231AF1-091 GEN
Solar/Wind Harmer
1.832
253343AC1-166 GEN
Solar/Wind Harmer
0.523
253325AC1-069 GEN
Solar/Wind Harmer
0.505
960071AF2-298 GEN
Solar/Wind Harmer
2.387
25326309TAIT D
Adder
0.523
270063AE2-323 C
Solar/Wind Harmer
1.051
965651AG1-433 GEN
Solar/Wind Harmer
2.532
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
958861AF2-177 GEN
Solar/Wind Harmer
5.028
247536S-71 GEN
Solar/Wind Harmer
1.856
945111AF1-176 GEN
Solar/Wind Harmer
8.121
270505AE1-170 C O1
Solar/Wind Harmer
6.807
945371AF1-202 GEN
Solar/Wind Harmer
3.165
270449AD2-020 GEN
Solar/Wind Harmer
1.267
943021AE2-325 GEN
Solar/Wind Harmer
1.646
970245AG2-165 GEN
Solar/Wind Harmer
8.007
970825AG2-519 GEN
Solar/Wind Harmer
1.035
270005AE1-210 C O1
Solar/Wind Harmer
2.397
965031AG1-367 GEN
Solar/Wind Harmer
4.385
970373AG2-245 GEN
Solar/Wind Harmer
9.206
274751CRETE EC ;1U
Adder
3.589
274754CRETE EC ;4U
Adder
3.589
274773LINCOLN ;4U
Adder
3.673
274774LINCOLN ;5U
Adder
3.673
274723RIVER EC ;12
Adder
7.798
274812UNIV PK N;8U
Adder
2.171
274801UNIV PARK;4U
Adder
2.514
270036AE2-216 BAT
50/50
5.929
270284AF1-227 GEN1
Solar/Wind Harmer
6.804
270286AF1-227 GEN2
Solar/Wind Harmer
2.517
270287AF1-227 GEN3
Solar/Wind Harmer
2.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.939
270302AB2-170 GEN
Solar/Wind Harmer
7.765
270317AD1-130_GEN
Solar/Wind Harmer
2.977
270520AE2-214 GEN
Solar/Wind Harmer
5.355
970179AG2-119 GEN
Solar/Wind Harmer
6.746
962771AG1-126 GEN
Solar/Wind Harmer
20.775
957201AF2-014 GEN
Solar/Wind Harmer
2.711
270435AC2-044 GEN
Solar/Wind Harmer
1.195
241972AD1-140 GEN
Solar/Wind Harmer
2.551
247607V1-011 GEN
Solar/Wind Harmer
2.214
965051AG1-369 GEN
Solar/Wind Harmer
2.75
270297AD1-101 GEN
Solar/Wind Harmer
1.533
965041AG1-368 GEN
Solar/Wind Harmer
5.342
945631AF1-228 GEN
Solar/Wind Harmer
2.501
270156DARBY CT1
Adder
4.664
270157DARBY CT2
Adder
4.653
270158DARBY CT3
Adder
4.578
963791AG1-232 GEN
Solar/Wind Harmer
6.751
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
270071AF1-092 GEN
Solar/Wind Harmer
7.187
270024AE2-089 GEN
Solar/Wind Harmer
2.242
24729505KEY G4
Adder
3.072
253349AC2-067 GEN
Solar/Wind Harmer
2.334
253400AC2-068 GEN
Solar/Wind Harmer
0.939
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.469
25306009OHH W.
Adder
1.331
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
965101AG1-375 GEN
Solar/Wind Harmer
4.6
971347AH1-153 GEN
Solar/Wind Harmer
6.892
971771AH1-392 GEN
Solar/Wind Harmer
4.09
270543AE2-219 C
Solar/Wind Harmer
2.323
945581AF1-223 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
0.996
971769AH1-391 GEN
Solar/Wind Harmer
4.495
971029AG2-637 GEN
Solar/Wind Harmer
6.737
971673AH1-337 GEN
Solar/Wind Harmer
2.06
960681AF2-359 GEN
Solar/Wind Harmer
1.688
970115AG2-085 GEN
Solar/Wind Harmer
1.758
253383AE2-342_GEN
Solar/Wind Harmer
0.388
274775LINCOLN ;6U
Adder
3.673
274776LINCOLN ;7U
Adder
3.673
274777LINCOLN ;8U
Adder
3.673
274814UNIV PK N;0U
Adder
2.19
274807UNIV PK N;3U
Adder
2.185
274805UNIV PK N;1U
Adder
2.176
274811UNIV PK N;7U
Adder
2.171
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.347
972227AH1-698 GEN1
Adder
1.124
270054AF2-122 C O1
Solar/Wind Helper
0.806
971549AH1-272 GEN
Solar/Wind Harmer
6.289
270466AD2-091
50/50
5.39
270471AD2-092_GEN
Solar/Wind Harmer
4.846
938701AE1-092 GEN
Solar/Wind Harmer
21.808
964601AG1-323 GEN
Solar/Wind Harmer
3.173
964601AG1-323 GEN
Solar/Wind Harmer
1.476
270224U2-072_GEN2
Solar/Wind Harmer
1.963
270227U2-072_GEN3
Solar/Wind Harmer
1.963
270228U2-072_GEN4
Solar/Wind Harmer
1.963
270231U2-072_GEN5
Solar/Wind Harmer
1.963
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.345
971201AH1-060 GEN
Solar/Wind Harmer
1.523
970077AG2-063 GEN
Solar/Wind Harmer
3.797
253378AE2-206_GEN
Solar/Wind Harmer
2.379
276820AF1-078_GEN
Solar/Wind Harmer
1.057
25326509SID D
Adder
0.827
246938BC-WTG3
Solar/Wind Harmer
2.379
246937BC-WTG2
Solar/Wind Harmer
2.339
270007AE1-245 C
Solar/Wind Harmer
3.321
942801AE2-298 GEN
Solar/Wind Harmer
0.846
970611AG2-400 GEN
Solar/Wind Harmer
5.279
270518AE2-148 GEN
Solar/Wind Harmer
6.245
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.648
25322209TAIT E
Adder
4.647
25322209TAIT E
Adder
4.543
942221AE2-234 GEN
Solar/Wind Harmer
0.348
247620Y3-023
Adder
0.214
270201AC2-176 GEN
Solar/Wind Harmer
2.386
944541AF1-119 GEN
Solar/Wind Harmer
1.941
960971AF2-388 GEN
Solar/Wind Harmer
5.064
247621Y3-024
Adder
0.111
253370AE2-315 SEC1
Adder
0.923
964611AG1-324 GEN
Solar/Wind Harmer
0.542
964611AG1-324 GEN
Solar/Wind Harmer
0.241
270216AD2-079_GEN
Solar/Wind Harmer
0.278
960981AF2-389 GEN
Solar/Wind Harmer
0.686
957891AF2-083 GEN
Solar/Wind Harmer
1.532
970883AG2-550 GEN
Solar/Wind Harmer
4.537
970885AG2-551 GEN
Solar/Wind Harmer
1.055
961051AF2-396 GEN
Solar/Wind Harmer
7.194
961051AF2-396 GEN
Solar/Wind Harmer
3.346
270526AF1-158 GEN
Solar/Wind Harmer
2.047
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.007
270599AE1-208 GEN
Solar/Wind Harmer
3.654
270031AE2-169
Solar/Wind Harmer
3.654
965681AG1-436 GEN
Solar/Wind Harmer
5.586
965791AG1-447 GEN
Solar/Wind Harmer
2.858
970825AG2-519 GEN
Solar/Wind Harmer
4.641
960441AF2-335 GEN
Solar/Wind Harmer
4.395
274770LINCOLN ;1U
Adder
3.673
274771LINCOLN ;2U
Adder
3.673
274808UNIV PK N;4U
Adder
2.161
274803UNIV PARK;6U
Adder
2.517
972259AH1-714 GEN
Adder
8.212
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.529
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181
LAGNLTFEXP_LAGN->PJM
CLTF
5.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.339
TVALTFEXP_TVA->PJM
CLTF
2.364
CPLELTFEXP_CPLE->PJM
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.662
NYPJM->LTFIMP_NY
CLTF
1.299
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.42 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1584.05
MW Contribution:14.42
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
5.39
270471AD2-092_GEN
Solar/Wind Harmer
4.846
938701AE1-092 GEN
Solar/Wind Harmer
21.808
964601AG1-323 GEN
Solar/Wind Harmer
3.173
964601AG1-323 GEN
Solar/Wind Harmer
1.476
270224U2-072_GEN2
Solar/Wind Harmer
1.963
270349AD2-093_GEN
Solar/Wind Harmer
4.846
971995AH1-542 GEN
Solar/Wind Harmer
11.714
270223U2-072_GEN1
Solar/Wind Harmer
1.963
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270475AD2-096_GEN
50/50
7.755
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
241974AD2-163_GEN2
Solar/Wind Harmer
1.939
270485AE1-090_GEN
Solar/Wind Harmer
0.562
942051AE2-217 GEN
Solar/Wind Harmer
13.864
970065AG2-057 GEN
Solar/Wind Harmer
0.762
970605AG2-385 GEN
Solar/Wind Harmer
3.797
241955AC1-078 GEN
Solar/Wind Harmer
4.97
970153AG2-106 GEN
Solar/Wind Harmer
9.059
270491AE1-102 GEN2
Solar/Wind Harmer
0.777
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.652
270247TR4_N_V136
Solar/Wind Harmer
0.468
270258AD1-119 GEN
Solar/Wind Harmer
1.487
959331AF2-224 GEN
Solar/Wind Harmer
5.279
965021AG1-366 GEN
Solar/Wind Harmer
1.228
270044AE2-322 C
Solar/Wind Harmer
0.687
270404AC1-167 GEN
Solar/Wind Harmer
0.572
270588AE1-091_GEN
Solar/Wind Harmer
5.47
270043AE2-236 GEN
Solar/Wind Harmer
2.696
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Harmer
0.505
970031AG2-029 GEN
Solar/Wind Harmer
14.416
971617AH1-308 GEN
Solar/Wind Harmer
2.777
944531AF1-118 GEN
Solar/Wind Harmer
16.706
270541AE2-072 C
Solar/Wind Harmer
2.148
962031AG1-047 GEN
Solar/Wind Harmer
1.403
957741AF2-068 GEN
Solar/Wind Harmer
6.963
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
970349AG2-230 GEN
Solar/Wind Harmer
6.892
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.574
24642205MAYFLWER
Adder
0.288
970513AG2-328 GEN
Solar/Wind Harmer
8.007
970517AG2-330 GEN
Solar/Wind Harmer
7.263
24441205WTRV SLR C
Solar/Wind Harmer
0.06
247604X1-042
Adder
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.69
958821AF2-173 GEN
Solar/Wind Harmer
6.139
270004AE1-209 GEN
Solar/Wind Harmer
2.397
274752CRETE EC ;2U
Adder
3.589
274753CRETE EC ;3U
Adder
3.589
274772LINCOLN ;3U
Adder
3.673
274724RIVER EC ;11
Adder
7.706
274802UNIV PARK;5U
Adder
2.517
274826FISK ;BP
Adder
4.723
274800UNIV PARK;3U
Adder
2.514
972038AH1-567 GEN2
Adder
0.157
972228AH1-698 GEN2
Adder
1.596
270036AE2-216 BAT
50/50
5.929
270284AF1-227 GEN1
Solar/Wind Harmer
6.804
270286AF1-227 GEN2
Solar/Wind Harmer
2.517
270287AF1-227 GEN3
Solar/Wind Harmer
2.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.939
270227U2-072_GEN3
Solar/Wind Harmer
1.963
270228U2-072_GEN4
Solar/Wind Harmer
1.963
270231U2-072_GEN5
Solar/Wind Harmer
1.963
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.345
971201AH1-060 GEN
Solar/Wind Harmer
1.523
970077AG2-063 GEN
Solar/Wind Harmer
3.797
253378AE2-206_GEN
Solar/Wind Harmer
2.379
276820AF1-078_GEN
Solar/Wind Harmer
1.057
25326509SID D
Adder
0.827
246938BC-WTG3
Solar/Wind Harmer
2.379
246937BC-WTG2
Solar/Wind Harmer
2.339
270007AE1-245 C
Solar/Wind Harmer
3.321
942801AE2-298 GEN
Solar/Wind Harmer
0.846
970611AG2-400 GEN
Solar/Wind Harmer
5.279
270518AE2-148 GEN
Solar/Wind Harmer
6.245
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.648
25322209TAIT E
Adder
4.647
25322209TAIT E
Adder
4.543
942221AE2-234 GEN
Solar/Wind Harmer
0.348
247620Y3-023
Adder
0.214
270201AC2-176 GEN
Solar/Wind Harmer
2.386
944541AF1-119 GEN
Solar/Wind Harmer
1.941
960971AF2-388 GEN
Solar/Wind Harmer
5.064
247621Y3-024
Adder
0.111
253370AE2-315 SEC1
Adder
0.923
964611AG1-324 GEN
Solar/Wind Harmer
0.542
964611AG1-324 GEN
Solar/Wind Harmer
0.241
270216AD2-079_GEN
Solar/Wind Harmer
0.278
960981AF2-389 GEN
Solar/Wind Harmer
0.686
957891AF2-083 GEN
Solar/Wind Harmer
1.532
970883AG2-550 GEN
Solar/Wind Harmer
4.537
970885AG2-551 GEN
Solar/Wind Harmer
1.055
961051AF2-396 GEN
Solar/Wind Harmer
7.194
961051AF2-396 GEN
Solar/Wind Harmer
3.346
270526AF1-158 GEN
Solar/Wind Harmer
2.047
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.007
270599AE1-208 GEN
Solar/Wind Harmer
3.654
270031AE2-169
Solar/Wind Harmer
3.654
965681AG1-436 GEN
Solar/Wind Harmer
5.586
965791AG1-447 GEN
Solar/Wind Harmer
2.858
970825AG2-519 GEN
Solar/Wind Harmer
4.641
960441AF2-335 GEN
Solar/Wind Harmer
4.395
274770LINCOLN ;1U
Adder
3.673
274771LINCOLN ;2U
Adder
3.673
274808UNIV PK N;4U
Adder
2.161
274803UNIV PARK;6U
Adder
2.517
972259AH1-714 GEN
Adder
8.212
270302AB2-170 GEN
Solar/Wind Harmer
7.765
270317AD1-130_GEN
Solar/Wind Harmer
2.977
270520AE2-214 GEN
Solar/Wind Harmer
5.355
970179AG2-119 GEN
Solar/Wind Harmer
6.746
962771AG1-126 GEN
Solar/Wind Harmer
20.775
957201AF2-014 GEN
Solar/Wind Harmer
2.711
270435AC2-044 GEN
Solar/Wind Harmer
1.195
241972AD1-140 GEN
Solar/Wind Harmer
2.551
247607V1-011 GEN
Solar/Wind Harmer
2.214
965051AG1-369 GEN
Solar/Wind Harmer
2.75
270297AD1-101 GEN
Solar/Wind Harmer
1.533
965041AG1-368 GEN
Solar/Wind Harmer
5.342
945631AF1-228 GEN
Solar/Wind Harmer
2.501
270156DARBY CT1
Adder
4.664
270157DARBY CT2
Adder
4.653
270158DARBY CT3
Adder
4.578
963791AG1-232 GEN
Solar/Wind Harmer
6.751
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
270071AF1-092 GEN
Solar/Wind Harmer
7.187
270024AE2-089 GEN
Solar/Wind Harmer
2.242
24729505KEY G4
Adder
3.072
253349AC2-067 GEN
Solar/Wind Harmer
2.334
253400AC2-068 GEN
Solar/Wind Harmer
0.939
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.469
25306009OHH W.
Adder
1.331
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
965101AG1-375 GEN
Solar/Wind Harmer
4.6
971347AH1-153 GEN
Solar/Wind Harmer
6.892
971771AH1-392 GEN
Solar/Wind Harmer
4.09
270543AE2-219 C
Solar/Wind Harmer
2.323
945581AF1-223 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
0.996
971769AH1-391 GEN
Solar/Wind Harmer
4.495
971029AG2-637 GEN
Solar/Wind Harmer
6.737
971673AH1-337 GEN
Solar/Wind Harmer
2.06
960681AF2-359 GEN
Solar/Wind Harmer
1.688
970115AG2-085 GEN
Solar/Wind Harmer
1.758
253383AE2-342_GEN
Solar/Wind Harmer
0.388
274775LINCOLN ;6U
Adder
3.673
274776LINCOLN ;7U
Adder
3.673
274777LINCOLN ;8U
Adder
3.673
274814UNIV PK N;0U
Adder
2.19
274807UNIV PK N;3U
Adder
2.185
274805UNIV PK N;1U
Adder
2.176
274811UNIV PK N;7U
Adder
2.171
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.347
972227AH1-698 GEN1
Adder
1.124
270054AF2-122 C O1
Solar/Wind Helper
0.806
971549AH1-272 GEN
Solar/Wind Harmer
6.289
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270462AD2-086
Solar/Wind Harmer
6.46
241813AF1-122_GEN
Solar/Wind Harmer
4.874
970593AG2-378 GEN
Solar/Wind Harmer
1.406
962761AG1-125 GEN
Solar/Wind Harmer
20.775
970149AG2-104 GEN
Solar/Wind Harmer
25.657
970155AG2-107 GEN
Solar/Wind Harmer
9.059
246936BC-WTG1
Solar/Wind Harmer
2.339
270489AE1-102 GEN1
Solar/Wind Harmer
0.777
965421AG1-410 GEN
Solar/Wind Harmer
17.731
247521TR3_G114
Solar/Wind Harmer
1.852
270246TR4_N_V150
Solar/Wind Harmer
0.468
24695305TIMB G C
Solar/Wind Harmer
2.998
965011AG1-365 GEN
Solar/Wind Harmer
5.279
270159DARBY CT4
Adder
4.59
944231AF1-091 GEN
Solar/Wind Harmer
1.832
253343AC1-166 GEN
Solar/Wind Harmer
0.523
253325AC1-069 GEN
Solar/Wind Harmer
0.505
960071AF2-298 GEN
Solar/Wind Harmer
2.387
25326309TAIT D
Adder
0.523
270063AE2-323 C
Solar/Wind Harmer
1.051
965651AG1-433 GEN
Solar/Wind Harmer
2.532
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
958861AF2-177 GEN
Solar/Wind Harmer
5.028
247536S-71 GEN
Solar/Wind Harmer
1.856
945111AF1-176 GEN
Solar/Wind Harmer
8.121
270505AE1-170 C O1
Solar/Wind Harmer
6.807
945371AF1-202 GEN
Solar/Wind Harmer
3.165
270449AD2-020 GEN
Solar/Wind Harmer
1.267
943021AE2-325 GEN
Solar/Wind Harmer
1.646
970245AG2-165 GEN
Solar/Wind Harmer
8.007
970825AG2-519 GEN
Solar/Wind Harmer
1.035
270005AE1-210 C O1
Solar/Wind Harmer
2.397
965031AG1-367 GEN
Solar/Wind Harmer
4.385
970373AG2-245 GEN
Solar/Wind Harmer
9.206
274751CRETE EC ;1U
Adder
3.589
274754CRETE EC ;4U
Adder
3.589
274773LINCOLN ;4U
Adder
3.673
274774LINCOLN ;5U
Adder
3.673
274723RIVER EC ;12
Adder
7.798
274812UNIV PK N;8U
Adder
2.171
274801UNIV PARK;4U
Adder
2.514
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.529
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181
LAGNLTFEXP_LAGN->PJM
CLTF
5.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.339
TVALTFEXP_TVA->PJM
CLTF
2.364
CPLELTFEXP_CPLE->PJM
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.662
NYPJM->LTFIMP_NY
CLTF
1.299
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7216_05VASSEL 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7216_05VASSEL 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.74 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1447.54
MW Contribution:14.24
Bus #Bus NameTypeMW Contribution
270349AD2-093_GEN
Solar/Wind Harmer
4.839
971995AH1-542 GEN
Solar/Wind Harmer
11.797
270223U2-072_GEN1
Solar/Wind Harmer
1.959
270578AF1-285 GEN2
Solar/Wind Harmer
1.198
270391AF1-285 GEN3
Solar/Wind Harmer
1.198
270462AD2-086
Solar/Wind Harmer
6.448
241813AF1-122_GEN
Solar/Wind Harmer
4.917
970593AG2-378 GEN
Solar/Wind Harmer
1.423
962761AG1-125 GEN
Solar/Wind Harmer
20.13
970149AG2-104 GEN
Solar/Wind Harmer
24.861
970155AG2-107 GEN
Solar/Wind Harmer
8.778
246936BC-WTG1
Solar/Wind Harmer
2.324
270475AD2-096_GEN
50/50
7.743
942871AE2-306 GEN
Solar/Wind Harmer
0.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.461
241974AD2-163_GEN2
Solar/Wind Harmer
1.957
270485AE1-090_GEN
Solar/Wind Harmer
0.561
942051AE2-217 GEN
Solar/Wind Harmer
14.042
970065AG2-057 GEN
Solar/Wind Harmer
0.768
970605AG2-385 GEN
Solar/Wind Harmer
3.843
241955AC1-078 GEN
Solar/Wind Harmer
5.062
970153AG2-106 GEN
Solar/Wind Harmer
8.778
270491AE1-102 GEN2
Solar/Wind Harmer
0.772
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.639
270247TR4_N_V136
Solar/Wind Harmer
0.465
270258AD1-119 GEN
Solar/Wind Harmer
1.477
959331AF2-224 GEN
Solar/Wind Harmer
5.222
965021AG1-366 GEN
Solar/Wind Harmer
1.214
270044AE2-322 C
Solar/Wind Harmer
0.682
270404AC1-167 GEN
Solar/Wind Harmer
0.568
270588AE1-091_GEN
Solar/Wind Harmer
5.477
253338AC1-165 GEN
Solar/Wind Harmer
0.533
253333AC1-068 GEN
Solar/Wind Harmer
0.514
270043AE2-236 GEN
Solar/Wind Harmer
2.66
970031AG2-029 GEN
Solar/Wind Harmer
14.237
971617AH1-308 GEN
Solar/Wind Harmer
2.754
270541AE2-072 C
Solar/Wind Harmer
2.143
944531AF1-118 GEN
Solar/Wind Harmer
16.503
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.928
253371AE2-315 SEC2
Adder
0.878
962031AG1-047 GEN
Solar/Wind Harmer
1.393
957741AF2-068 GEN
Solar/Wind Harmer
6.912
970349AG2-230 GEN
Solar/Wind Harmer
6.79
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.539
24642205MAYFLWER
Adder
0.284
970513AG2-328 GEN
Solar/Wind Harmer
7.888
970517AG2-330 GEN
Solar/Wind Harmer
7.154
24441205WTRV SLR C
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.659
247604X1-042
Adder
0.183
958821AF2-173 GEN
Solar/Wind Harmer
6.084
270004AE1-209 GEN
Solar/Wind Harmer
2.375
270489AE1-102 GEN1
Solar/Wind Harmer
0.772
965421AG1-410 GEN
Solar/Wind Harmer
17.611
247521TR3_G114
Solar/Wind Harmer
1.837
270246TR4_N_V150
Solar/Wind Harmer
0.465
24695305TIMB G C
Solar/Wind Harmer
2.974
270159DARBY CT4
Adder
4.69
965011AG1-365 GEN
Solar/Wind Harmer
5.222
253343AC1-166 GEN
Solar/Wind Harmer
0.533
253325AC1-069 GEN
Solar/Wind Harmer
0.514
944231AF1-091 GEN
Solar/Wind Harmer
1.814
960071AF2-298 GEN
Solar/Wind Harmer
2.399
25326309TAIT D
Adder
0.526
270063AE2-323 C
Solar/Wind Harmer
1.037
253370AE2-315 SEC1
Adder
0.928
253371AE2-315 SEC2
Adder
0.878
965651AG1-433 GEN
Solar/Wind Harmer
2.504
247536S-71 GEN
Solar/Wind Harmer
1.844
958861AF2-177 GEN
Solar/Wind Harmer
4.973
24639705ELKHART HY
Adder
0.07
945111AF1-176 GEN
Solar/Wind Harmer
8.011
945371AF1-202 GEN
Solar/Wind Harmer
3.132
270505AE1-170 C O1
Solar/Wind Harmer
6.714
270449AD2-020 GEN
Solar/Wind Harmer
1.25
943021AE2-325 GEN
Solar/Wind Harmer
1.624
970245AG2-165 GEN
Solar/Wind Harmer
7.888
970825AG2-519 GEN
Solar/Wind Harmer
1.026
270005AE1-210 C O1
Solar/Wind Harmer
2.375
965031AG1-367 GEN
Solar/Wind Harmer
4.346
970373AG2-245 GEN
Solar/Wind Harmer
9.08
270032AE2-172
Solar/Wind Harmer
0.861
270466AD2-091
50/50
5.38
270471AD2-092_GEN
Solar/Wind Harmer
4.839
938701AE1-092 GEN
Solar/Wind Harmer
21.937
964601AG1-323 GEN
Solar/Wind Harmer
3.19
964601AG1-323 GEN
Solar/Wind Harmer
1.484
270224U2-072_GEN2
Solar/Wind Harmer
1.959
270227U2-072_GEN3
Solar/Wind Harmer
1.959
270228U2-072_GEN4
Solar/Wind Harmer
1.959
270231U2-072_GEN5
Solar/Wind Harmer
1.959
946101AF1-275 GEN
Solar/Wind Harmer
1.359
241960AC2-195 GEN
Solar/Wind Harmer
2.364
971201AH1-060 GEN
Solar/Wind Harmer
1.536
970077AG2-063 GEN
Solar/Wind Harmer
3.843
253378AE2-206_GEN
Solar/Wind Harmer
2.386
276820AF1-078_GEN
Solar/Wind Harmer
1.06
25326509SID D
Adder
0.829
246938BC-WTG3
Solar/Wind Harmer
2.364
246937BC-WTG2
Solar/Wind Harmer
2.324
270007AE1-245 C
Solar/Wind Harmer
3.3
942801AE2-298 GEN
Solar/Wind Harmer
0.841
270518AE2-148 GEN
Solar/Wind Harmer
6.356
970611AG2-400 GEN
Solar/Wind Harmer
5.222
942861AE2-305 GEN
Solar/Wind Harmer
3.921
25326109MON D
Adder
0.653
25322209TAIT E
Adder
4.675
25322209TAIT E
Adder
4.57
942221AE2-234 GEN
Solar/Wind Harmer
0.344
253370AE2-315 SEC1
Adder
0.928
270201AC2-176 GEN
Solar/Wind Harmer
2.369
944541AF1-119 GEN
Solar/Wind Harmer
1.919
960971AF2-388 GEN
Solar/Wind Harmer
5.008
247620Y3-023
Adder
0.211
247621Y3-024
Adder
0.11
964611AG1-324 GEN
Solar/Wind Harmer
0.538
964611AG1-324 GEN
Solar/Wind Harmer
0.239
270216AD2-079_GEN
Solar/Wind Harmer
0.274
970883AG2-550 GEN
Solar/Wind Harmer
4.511
970885AG2-551 GEN
Solar/Wind Harmer
1.049
960981AF2-389 GEN
Solar/Wind Harmer
0.677
957891AF2-083 GEN
Solar/Wind Harmer
1.511
961051AF2-396 GEN
Solar/Wind Harmer
7.096
961051AF2-396 GEN
Solar/Wind Harmer
3.301
270526AF1-158 GEN
Solar/Wind Harmer
2.018
270599AE1-208 GEN
Solar/Wind Harmer
3.619
270031AE2-169
Solar/Wind Harmer
3.619
24441505OLIV SLR
Solar/Wind Harmer
0.059
970321AG2-212 GEN
Solar/Wind Harmer
7.888
965681AG1-436 GEN
Solar/Wind Harmer
5.508
965791AG1-447 GEN
Solar/Wind Harmer
2.818
970825AG2-519 GEN
Solar/Wind Harmer
4.6
960441AF2-335 GEN
Solar/Wind Harmer
4.356
270383AD1-128 GEN
Solar/Wind Harmer
2.637
270036AE2-216 BAT
50/50
5.918
270284AF1-227 GEN1
Solar/Wind Harmer
6.793
270286AF1-227 GEN2
Solar/Wind Harmer
2.513
270287AF1-227 GEN3
Solar/Wind Harmer
2.513
270578AF1-285 GEN2
Solar/Wind Harmer
0.461
241973AD2-163_GEN1
Solar/Wind Harmer
1.957
270302AB2-170 GEN
Solar/Wind Harmer
7.752
270317AD1-130_GEN
Solar/Wind Harmer
2.972
270520AE2-214 GEN
Solar/Wind Harmer
5.445
970179AG2-119 GEN
Solar/Wind Harmer
6.8
962771AG1-126 GEN
Solar/Wind Harmer
20.13
957201AF2-014 GEN
Solar/Wind Harmer
2.694
270435AC2-044 GEN
Solar/Wind Harmer
1.188
241972AD1-140 GEN
Solar/Wind Harmer
2.576
247607V1-011 GEN
Solar/Wind Harmer
2.2
270297AD1-101 GEN
Solar/Wind Harmer
1.527
965051AG1-369 GEN
Solar/Wind Harmer
2.727
945631AF1-228 GEN
Solar/Wind Harmer
2.554
270156DARBY CT1
Adder
4.766
270157DARBY CT2
Adder
4.755
270158DARBY CT3
Adder
4.679
965041AG1-368 GEN
Solar/Wind Harmer
5.294
943861AF1-054 GEN
Solar/Wind Harmer
1.935
943851AF1-053 GEN
Solar/Wind Harmer
0.935
963791AG1-232 GEN
Solar/Wind Harmer
6.686
270024AE2-089 GEN
Solar/Wind Harmer
2.223
270071AF1-092 GEN
Solar/Wind Harmer
7.094
253349AC2-067 GEN
Solar/Wind Harmer
2.343
253400AC2-068 GEN
Solar/Wind Harmer
0.942
24729505KEY G4
Adder
3.036
25306009OHH W.
Adder
1.338
253372AE2-315 SEC3
Adder
0.878
253372AE2-315 SEC3
Adder
0.878
961761AG1-017 GEN
Solar/Wind Harmer
0.197
958711AF2-162 GEN
Solar/Wind Harmer
0.464
965101AG1-375 GEN
Solar/Wind Harmer
4.55
971347AH1-153 GEN
Solar/Wind Harmer
6.79
270543AE2-219 C
Solar/Wind Harmer
2.31
945581AF1-223 GEN
Solar/Wind Harmer
2.036
971771AH1-392 GEN
Solar/Wind Harmer
4.033
253383AE2-342_GEN
Solar/Wind Harmer
0.396
971029AG2-637 GEN
Solar/Wind Harmer
6.703
971673AH1-337 GEN
Solar/Wind Harmer
2.05
944161AF1-084 GEN
Solar/Wind Harmer
0.982
971769AH1-391 GEN
Solar/Wind Harmer
4.432
960681AF2-359 GEN
Solar/Wind Harmer
1.665
970115AG2-085 GEN
Solar/Wind Harmer
1.742
270054AF2-122 C O1
Solar/Wind Helper
0.786
270594AE1-207 GEN
Solar/Wind Harmer
2.721
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.444
MECLTFEXP_MEC->PJM
CLTF
6.218
SIGELTFEXP_SIGE->PJM
CLTF
0.179
LAGNLTFEXP_LAGN->PJM
CLTF
5.039
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.304
TVALTFEXP_TVA->PJM
CLTF
2.34
CPLELTFEXP_CPLE->PJM
CLTF
0.34
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.234
NYPJM->LTFIMP_NY
CLTF
1.287
LGEELTFEXP_LGEE->PJM
CLTF
2.274
WECLTFEXP_WEC->PJM
CLTF
1.561
AG2-052LTFEXP_AG2-052->PJM
LTF
0.099
AH1-155LTFEXP_AH1-155->PJM
LTF
0.148

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.09 %
Rating:3039.0 MVA
Rating Type:B
MVA to Mitigate:3588.67
MW Contribution:2.9
Bus #Bus NameTypeMW Contribution
970091AG2-072 GEN
50/50
218.455
270407AB1-088 ST1
50/50
2.508
970023AG2-014 GEN
50/50
2.686
970783AG2-492 GEN
50/50
2.686
24344105CKG2
50/50
6.851
970333AG2-219 GEN
Solar/Wind Harmer
14.81
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970245AG2-165 GEN
Solar/Wind Harmer
3.606
24791305MDL-5G
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.756
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.732
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
963741AG1-226 GEN
Solar/Wind Harmer
17.046
970373AG2-245 GEN
Solar/Wind Harmer
14.55
274773LINCOLN ;4U
Adder
7.237
274774LINCOLN ;5U
Adder
7.237
274751CRETE EC ;1U
Adder
7.047
274754CRETE EC ;4U
Adder
7.047
274723RIVER EC ;12
Adder
15.25
274812UNIV PK N;8U
Adder
4.257
276164X3-005 C
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.616
274801UNIV PARK;4U
Adder
4.918
939401AE1-172 GEN
Solar/Wind Harmer
4.373
274732ELWOOD EC;7P
Adder
13.765
274674JOLIET 9 ;6U
Adder
12.881
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
25.663
274745AC1-111 GEN9
Adder
4.62
276691AA1-018 GEN1
Solar/Wind Harmer
0.697
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.048
276901AD2-066 C O1
Solar/Wind Harmer
0.006
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
2.988
274682WAUKEGAN ;7U
Adder
14.638
274828WAUKEGAN ;BP
Adder
8.984
972175AH1-670 GEN
Solar/Wind Harmer
4.678
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
5.364
274872LEEDK;1U
Solar/Wind Harmer
0.003
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.181
970569AG2-363 GEN
Solar/Wind Harmer
16.771
276861AD2-134 GEN
Solar/Wind Harmer
0.1
270505AE1-170 C O1
Solar/Wind Harmer
5.832
276615X2-022 GEN
Solar/Wind Harmer
0.058
957471AF2-041 GEN
Solar/Wind Harmer
16.603
959081AF2-199 GEN
Solar/Wind Harmer
5.534
971067AG2-660 GEN
Solar/Wind Harmer
1.845
274822ROCKFORD ;11
Adder
1.007
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.872
945111AF1-176 GEN
Solar/Wind Harmer
9.771
970819AG2-516 GEN
Solar/Wind Harmer
6.568
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
971475AH1-234 GEN
Solar/Wind Harmer
2.645
965911AG1-460 GEN
Solar/Wind Harmer
1.09
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
24344305RKG2
50/50
10.991
270406AB1-088 CT1
50/50
2.508
970243AG2-164 GEN
Solar/Wind Harmer
12.117
970519AG2-331 GEN
Solar/Wind Harmer
53.854
970699AG2-449 GEN
Solar/Wind Harmer
5.178
970513AG2-328 GEN
Solar/Wind Harmer
3.606
970517AG2-330 GEN
Solar/Wind Harmer
21.635
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.058
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
970193AG2-126 GEN
Solar/Wind Harmer
9.211
970349AG2-230 GEN
Solar/Wind Harmer
9.104
274772LINCOLN ;3U
Adder
7.237
274752CRETE EC ;2U
Adder
7.047
274753CRETE EC ;3U
Adder
7.047
274724RIVER EC ;11
Adder
15.065
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
3.132
276806AD2-047 C O1
Solar/Wind Harmer
3.342
970941AG2-585 GEN
Solar/Wind Harmer
7.373
274802UNIV PARK;5U
Adder
4.928
274800UNIV PARK;3U
Adder
4.918
972038AH1-567 GEN2
Adder
0.308
274826FISK ;BP
Adder
9.234
970707AG2-453 GEN
Solar/Wind Harmer
19.213
274729ELWOOD EC;1P
Adder
13.765
274730ELWOOD EC;6P
Adder
13.765
274734ELWOOD EC;8P
Adder
13.765
274736ELWOOD EC;9P
Adder
13.765
276893AG1-478 C
Solar/Wind Harmer
0.231
274676JOLIET 29;8U
Adder
24.747
943121AE2-341 GEN
Solar/Wind Harmer
9.668
943591AF1-030 GEN
Solar/Wind Harmer
6.429
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
1.868
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
17.118
959611AF2-252 GEN
Solar/Wind Harmer
1.902
274682WAUKEGAN ;7U
Adder
14.638
24642205MAYFLWER
Adder
0.516
276889AE2-281 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.206
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.595
276668AB2-070 GEN1
Solar/Wind Harmer
0.205
970571AG2-364 GEN
Solar/Wind Harmer
11.181
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.595
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.066
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.1
276621W2-048 GEN
Solar/Wind Harmer
0.28
276838X2-022 GEN2
Solar/Wind Harmer
0.313
959091AF2-200 GEN
Solar/Wind Harmer
11.069
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.439
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
942481AE2-261 GEN
Solar/Wind Harmer
16.292
24441205WTRV SLR C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.872
965931AG1-462 GEN
Solar/Wind Harmer
13.177
247642Z2-115 C
Solar/Wind Harmer
0.002
970031AG2-029 GEN
Solar/Wind Harmer
2.905
270043AE2-236 GEN
Solar/Wind Harmer
2.56
970289AG2-191 GEN
Solar/Wind Harmer
0.413
970291AG2-192 GEN
Solar/Wind Harmer
0.376
959331AF2-224 GEN
Solar/Wind Harmer
2.131
965021AG1-366 GEN
Solar/Wind Harmer
1.015
252510AF1-249 C
Solar/Wind Helper
0.376
253406AD2-031_GEN
Solar/Wind Helper
0.712
253415AE1-040 GEN
Solar/Wind Helper
0.483
339250AF1-203 GEN
Solar/Wind Helper
0.118
253338AC1-165 GEN
Solar/Wind Helper
0.467
253333AC1-068 GEN
Solar/Wind Helper
0.484
276158O29GEN2
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.004
970291AG2-192 GEN
Solar/Wind Harmer
0.488
965011AG1-365 GEN
Solar/Wind Harmer
3.044
944231AF1-091 GEN
Solar/Wind Harmer
0.807
252507AC2-088 GEN
Solar/Wind Helper
1.471
339216AC1-074 GEN
Solar/Wind Helper
1.461
943111AE2-339 GEN
Solar/Wind Helper
0.643
339241AF1-083 GEN
Solar/Wind Helper
0.405
253343AC1-166 GEN
Solar/Wind Helper
0.467
253325AC1-069 GEN
Solar/Wind Helper
0.484
942601AE2-276 GEN
50/50
8.344
270102X2-052 ST
50/50
1.424
270100X2-052 CT1
50/50
1.312
270101X2-052 CT2
50/50
1.312
970239AG2-162 GEN
Solar/Wind Harmer
5.178
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.343
970321AG2-212 GEN
Solar/Wind Harmer
3.606
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
966841AG1-555 GEN
Solar/Wind Harmer
0.888
970241AG2-163 GEN
Solar/Wind Harmer
4.202
965681AG1-436 GEN
Solar/Wind Harmer
7.741
965791AG1-447 GEN
Solar/Wind Harmer
5.677
945391AF1-204 GEN
Solar/Wind Harmer
6.524
274770LINCOLN ;1U
Adder
7.237
274771LINCOLN ;2U
Adder
7.237
24441505OLIV SLR
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.239
270526AF1-158 GEN
Solar/Wind Harmer
0.007
274888KELLY CRK;1U
Solar/Wind Harmer
0.346
274887GEN-1.85
Solar/Wind Harmer
0.155
276843GEN-1.7
Solar/Wind Harmer
0.191
958011AF2-095 GEN
Solar/Wind Harmer
8.493
274803UNIV PARK;6U
Adder
4.928
24344205RKG1
50/50
11.244
24344205RKG1
50/50
11.22
24344305RKG2
50/50
11.199
270393AB1-087 CT1
50/50
2.508
270394AB1-087 ST1
50/50
2.508
970541AG2-344 GEN
50/50
10.209
970539AG2-343 GEN
50/50
9.364
970543AG2-345 GEN
50/50
4.682
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.647
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.256
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
9.104
274775LINCOLN ;6U
Adder
7.237
274776LINCOLN ;7U
Adder
7.237
274777LINCOLN ;8U
Adder
7.237
971769AH1-391 GEN
Solar/Wind Harmer
6.648
274814UNIV PK N;0U
Adder
4.294
274807UNIV PK N;3U
Adder
4.285
274805UNIV PK N;1U
Adder
4.266
274811UNIV PK N;7U
Adder
4.257
972227AH1-698 GEN1
Adder
2.206
960591AF2-350 GEN
Solar/Wind Harmer
5.898
972037AH1-567 GEN1
Adder
0.155
274827FISK ;RP
Adder
6.544
274687WILL CNTY;4U
Adder
23.403
274687WILL CNTY;4U
Adder
23.403
274731ELWOOD EC;2P
Adder
13.765
274733ELWOOD EC;3P
Adder
13.765
274735ELWOOD EC;4P
Adder
13.765
274728ELWOOD EC;5P
Adder
13.765
970833AG2-524 GEN
Solar/Wind Harmer
6.424
970833AG2-524 GEN
Solar/Wind Harmer
4.282
274675JOLIET 29;7U
Adder
25.664
274675JOLIET 29;7U
Adder
24.747
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
5.784
274746AC1-111 G10
Adder
4.62
274744AC1-111 GEN8
Adder
4.62
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.036
941731AE2-173 GEN
Solar/Wind Harmer
4.79
971771AH1-392 GEN
Solar/Wind Harmer
5.725
276868AE1-113 GEN
Solar/Wind Harmer
1.14
276882AE2-255 GEN
Solar/Wind Harmer
0.664
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.205
276848AB2-070 GEN3
Solar/Wind Harmer
0.204
926823AC1-168 GEN
Solar/Wind Harmer
0.954
971177AH1-047 GEN
Solar/Wind Harmer
3.447
971675AH1-338 GEN
Solar/Wind Harmer
2.173
971411AH1-196 GEN
Solar/Wind Harmer
8.347
971619AH1-309 GEN
Solar/Wind Harmer
2.5
971171AH1-044 GEN
Solar/Wind Harmer
11.069
274823ROCKFORD ;21
Adder
15.377
957751AF2-069 GEN
Solar/Wind Harmer
0.182
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
8.765
944221AF1-090 GEN
Solar/Wind Harmer
3.172
961011AF2-392 GEN
Solar/Wind Harmer
3.16
946321AF1-296 GEN
Solar/Wind Harmer
2.912
971549AH1-272 GEN
Solar/Wind Harmer
10.16
270071AF1-092 GEN
Solar/Wind Harmer
8.874
970289AG2-191 GEN
Solar/Wind Harmer
0.714
252524AE2-267 GEN
Solar/Wind Helper
0.465
339243AC2-075 GEN1
Solar/Wind Helper
0.336
339211AE2-254 GEN
Solar/Wind Helper
0.447
270367AC2-061_GEN
Solar/Wind Helper
1.692
270340AC2-060 GEN
Solar/Wind Helper
1.094
241972AD1-140 GEN
Solar/Wind Helper
2.07
972259AH1-714 GEN
Adder
16.092
274674JOLIET 9 ;6U
Adder
12.881
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
958481AF2-142 GEN
Solar/Wind Harmer
8.633
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.778
971573AH1-285 GEN
Solar/Wind Harmer
1.068
958491AF2-143 GEN
Solar/Wind Harmer
8.559
960611AF2-352 GEN
Solar/Wind Harmer
1.902
274695ROCKY RD ;2P
Adder
9.087
274693ROCKY RD ;1P
Adder
8.997
274697ROCKY RD ;3P
Adder
2.468
274696ROCKY RD ;4P
Adder
9.301
274879MINONK ;1U
Solar/Wind Harmer
0.24
274683WAUKEGAN ;8U
Adder
17.139
274683WAUKEGAN ;8U
Adder
14.447
962691AG1-118 GEN
Solar/Wind Harmer
16.954
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
970921AG2-575 GEN
Solar/Wind Harmer
5.636
970921AG2-575 GEN
Solar/Wind Harmer
1.879
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.244
971333AH1-146 GEN
Solar/Wind Harmer
11.124
971335AH1-147 GEN
Solar/Wind Harmer
11.124
957891AF2-083 GEN
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
11.069
971343AH1-151 GEN
Solar/Wind Harmer
11.069
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.216
276646AC1-214 GEN2
Solar/Wind Harmer
0.216
961051AF2-396 GEN
Solar/Wind Harmer
10.985
961051AF2-396 GEN
Solar/Wind Harmer
7.324
270216AD2-079_GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.129
276611AD2-172 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276916AD2-100_GEN
Solar/Wind Harmer
11.423
276911AD2-131_GEN
Solar/Wind Harmer
0.752
938861AE1-114 GEN
Solar/Wind Harmer
3.082
276603SUBLETTE C
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.192
276708O09 GEN2
Solar/Wind Harmer
0.192
970611AG2-400 GEN
Solar/Wind Harmer
3.044
970627AG2-408 GEN
Solar/Wind Harmer
0.913
252509AD1-136 GEN
Solar/Wind Helper
0.21
339221AD2-048_GEN
Solar/Wind Helper
1.206
25183208HLCRTG
Solar/Wind Helper
2.027
270186AC1-089 GEN
Solar/Wind Helper
0.821
253394AE2-221_GEN
Solar/Wind Helper
1.236
253398AE2-221_GEN2
Solar/Wind Helper
1.236
962581AG1-107 GEN
Solar/Wind Helper
0.907
961491AF2-440 GEN
Solar/Wind Helper
0.037
339236AF1-050_GEN
Solar/Wind Helper
0.406
339231AF1-038_GEN
Solar/Wind Helper
0.396
339255AE2-071 GEN
Solar/Wind Helper
0.206
270518AE2-148 GEN
Solar/Wind Helper
5.626
944201AF1-088_MTX
50/50
166.885
957141AF2-008_MTX
50/50
83.443
955142J992
External Queue
11.408185005187988
990742J1381
External Queue
17.5482177734375
950011AG9-010
External Queue
6.204055309295654
991082J1475 G
External Queue
6.161812782287598
991312J1772
External Queue
12.355378150939941
991112J1481
External Queue
17.5482177734375
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.745
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.126
MECLTFEXP_MEC->PJM
CLTF
10.584
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.981
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.615
LAGNLTFEXP_LAGN->PJM
CLTF
2.246
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.176
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
1.043
WECLTFEXP_WEC->PJM
CLTF
2.99
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.226
AG2-052LTFEXP_AG2-052->PJM
LTF
0.2
AH1-155LTFEXP_AH1-155->PJM
LTF
0.301

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.46 %
Rating:2826.0 MVA
Rating Type:B
MVA to Mitigate:3601.92
MW Contribution:2.9
Bus #Bus NameTypeMW Contribution
942601AE2-276 GEN
50/50
8.344
270102X2-052 ST
50/50
1.424
270100X2-052 CT1
50/50
1.312
270101X2-052 CT2
50/50
1.312
970239AG2-162 GEN
Solar/Wind Harmer
5.178
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.343
970321AG2-212 GEN
Solar/Wind Harmer
3.606
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
966841AG1-555 GEN
Solar/Wind Harmer
0.888
970241AG2-163 GEN
Solar/Wind Harmer
4.202
965681AG1-436 GEN
Solar/Wind Harmer
7.741
965791AG1-447 GEN
Solar/Wind Harmer
5.677
945391AF1-204 GEN
Solar/Wind Harmer
6.524
274770LINCOLN ;1U
Adder
7.237
274771LINCOLN ;2U
Adder
7.237
24441505OLIV SLR
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.239
270526AF1-158 GEN
Solar/Wind Harmer
0.007
274888KELLY CRK;1U
Solar/Wind Harmer
0.346
274887GEN-1.85
Solar/Wind Harmer
0.155
276843GEN-1.7
Solar/Wind Harmer
0.191
958011AF2-095 GEN
Solar/Wind Harmer
8.493
274803UNIV PARK;6U
Adder
4.928
972259AH1-714 GEN
Adder
16.092
274674JOLIET 9 ;6U
Adder
12.881
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
958481AF2-142 GEN
Solar/Wind Harmer
8.633
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.778
971573AH1-285 GEN
Solar/Wind Harmer
1.068
958491AF2-143 GEN
Solar/Wind Harmer
8.559
960611AF2-352 GEN
Solar/Wind Harmer
1.902
274695ROCKY RD ;2P
Adder
9.087
274693ROCKY RD ;1P
Adder
8.997
274697ROCKY RD ;3P
Adder
2.468
274696ROCKY RD ;4P
Adder
9.301
274879MINONK ;1U
Solar/Wind Harmer
0.24
274683WAUKEGAN ;8U
Adder
17.139
274683WAUKEGAN ;8U
Adder
14.447
962691AG1-118 GEN
Solar/Wind Harmer
16.954
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
970921AG2-575 GEN
Solar/Wind Harmer
5.636
970921AG2-575 GEN
Solar/Wind Harmer
1.879
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.244
971333AH1-146 GEN
Solar/Wind Harmer
11.124
971335AH1-147 GEN
Solar/Wind Harmer
11.124
957891AF2-083 GEN
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
11.069
971343AH1-151 GEN
Solar/Wind Harmer
11.069
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.216
276646AC1-214 GEN2
Solar/Wind Harmer
0.216
961051AF2-396 GEN
Solar/Wind Harmer
10.985
961051AF2-396 GEN
Solar/Wind Harmer
7.324
270216AD2-079_GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.129
276611AD2-172 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0.001
24344305RKG2
50/50
10.991
270406AB1-088 CT1
50/50
2.508
970243AG2-164 GEN
Solar/Wind Harmer
12.117
970519AG2-331 GEN
Solar/Wind Harmer
53.854
970699AG2-449 GEN
Solar/Wind Harmer
5.178
970513AG2-328 GEN
Solar/Wind Harmer
3.606
970517AG2-330 GEN
Solar/Wind Harmer
21.635
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.058
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
970193AG2-126 GEN
Solar/Wind Harmer
9.211
970349AG2-230 GEN
Solar/Wind Harmer
9.104
274772LINCOLN ;3U
Adder
7.237
274752CRETE EC ;2U
Adder
7.047
274753CRETE EC ;3U
Adder
7.047
274724RIVER EC ;11
Adder
15.065
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
3.132
276806AD2-047 C O1
Solar/Wind Harmer
3.342
970941AG2-585 GEN
Solar/Wind Harmer
7.373
274802UNIV PARK;5U
Adder
4.928
274800UNIV PARK;3U
Adder
4.918
972038AH1-567 GEN2
Adder
0.308
274826FISK ;BP
Adder
9.234
970707AG2-453 GEN
Solar/Wind Harmer
19.213
274729ELWOOD EC;1P
Adder
13.765
274730ELWOOD EC;6P
Adder
13.765
274734ELWOOD EC;8P
Adder
13.765
274736ELWOOD EC;9P
Adder
13.765
276893AG1-478 C
Solar/Wind Harmer
0.231
274676JOLIET 29;8U
Adder
24.747
276916AD2-100_GEN
Solar/Wind Harmer
11.423
276911AD2-131_GEN
Solar/Wind Harmer
0.752
938861AE1-114 GEN
Solar/Wind Harmer
3.082
276603SUBLETTE C
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.192
276708O09 GEN2
Solar/Wind Harmer
0.192
970611AG2-400 GEN
Solar/Wind Harmer
3.044
970627AG2-408 GEN
Solar/Wind Harmer
0.913
252509AD1-136 GEN
Solar/Wind Helper
0.21
339221AD2-048_GEN
Solar/Wind Helper
1.206
25183208HLCRTG
Solar/Wind Helper
2.027
270186AC1-089 GEN
Solar/Wind Helper
0.821
253394AE2-221_GEN
Solar/Wind Helper
1.236
253398AE2-221_GEN2
Solar/Wind Helper
1.236
962581AG1-107 GEN
Solar/Wind Helper
0.907
961491AF2-440 GEN
Solar/Wind Helper
0.037
339236AF1-050_GEN
Solar/Wind Helper
0.406
339231AF1-038_GEN
Solar/Wind Helper
0.396
339255AE2-071 GEN
Solar/Wind Helper
0.206
270518AE2-148 GEN
Solar/Wind Helper
5.626
943121AE2-341 GEN
Solar/Wind Harmer
9.668
943591AF1-030 GEN
Solar/Wind Harmer
6.429
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
1.868
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
17.118
959611AF2-252 GEN
Solar/Wind Harmer
1.902
274682WAUKEGAN ;7U
Adder
14.638
24642205MAYFLWER
Adder
0.516
276889AE2-281 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.206
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.595
276668AB2-070 GEN1
Solar/Wind Harmer
0.205
970571AG2-364 GEN
Solar/Wind Harmer
11.181
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.595
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.066
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.1
276621W2-048 GEN
Solar/Wind Harmer
0.28
276838X2-022 GEN2
Solar/Wind Harmer
0.313
959091AF2-200 GEN
Solar/Wind Harmer
11.069
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.439
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
942481AE2-261 GEN
Solar/Wind Harmer
16.292
24441205WTRV SLR C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.872
965931AG1-462 GEN
Solar/Wind Harmer
13.177
247642Z2-115 C
Solar/Wind Harmer
0.002
970031AG2-029 GEN
Solar/Wind Harmer
2.905
270043AE2-236 GEN
Solar/Wind Harmer
2.56
970289AG2-191 GEN
Solar/Wind Harmer
0.413
970291AG2-192 GEN
Solar/Wind Harmer
0.376
959331AF2-224 GEN
Solar/Wind Harmer
2.131
965021AG1-366 GEN
Solar/Wind Harmer
1.015
252510AF1-249 C
Solar/Wind Helper
0.376
253406AD2-031_GEN
Solar/Wind Helper
0.712
253415AE1-040 GEN
Solar/Wind Helper
0.483
339250AF1-203 GEN
Solar/Wind Helper
0.118
253338AC1-165 GEN
Solar/Wind Helper
0.467
253333AC1-068 GEN
Solar/Wind Helper
0.484
970091AG2-072 GEN
50/50
218.455
270407AB1-088 ST1
50/50
2.508
970023AG2-014 GEN
50/50
2.686
970783AG2-492 GEN
50/50
2.686
24344105CKG2
50/50
6.851
970333AG2-219 GEN
Solar/Wind Harmer
14.81
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970245AG2-165 GEN
Solar/Wind Harmer
3.606
24791305MDL-5G
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.756
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.732
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
963741AG1-226 GEN
Solar/Wind Harmer
17.046
970373AG2-245 GEN
Solar/Wind Harmer
14.55
274773LINCOLN ;4U
Adder
7.237
274774LINCOLN ;5U
Adder
7.237
274751CRETE EC ;1U
Adder
7.047
274754CRETE EC ;4U
Adder
7.047
274723RIVER EC ;12
Adder
15.25
274812UNIV PK N;8U
Adder
4.257
276164X3-005 C
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.616
274801UNIV PARK;4U
Adder
4.918
939401AE1-172 GEN
Solar/Wind Harmer
4.373
274732ELWOOD EC;7P
Adder
13.765
274674JOLIET 9 ;6U
Adder
12.881
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
25.663
274745AC1-111 GEN9
Adder
4.62
276691AA1-018 GEN1
Solar/Wind Harmer
0.697
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.048
276901AD2-066 C O1
Solar/Wind Harmer
0.006
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
2.988
274682WAUKEGAN ;7U
Adder
14.638
274828WAUKEGAN ;BP
Adder
8.984
972175AH1-670 GEN
Solar/Wind Harmer
4.678
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
5.364
274872LEEDK;1U
Solar/Wind Harmer
0.003
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.181
970569AG2-363 GEN
Solar/Wind Harmer
16.771
276861AD2-134 GEN
Solar/Wind Harmer
0.1
270505AE1-170 C O1
Solar/Wind Harmer
5.832
276615X2-022 GEN
Solar/Wind Harmer
0.058
957471AF2-041 GEN
Solar/Wind Harmer
16.603
959081AF2-199 GEN
Solar/Wind Harmer
5.534
971067AG2-660 GEN
Solar/Wind Harmer
1.845
274822ROCKFORD ;11
Adder
1.007
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.872
945111AF1-176 GEN
Solar/Wind Harmer
9.771
970819AG2-516 GEN
Solar/Wind Harmer
6.568
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
971475AH1-234 GEN
Solar/Wind Harmer
2.645
965911AG1-460 GEN
Solar/Wind Harmer
1.09
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.004
970291AG2-192 GEN
Solar/Wind Harmer
0.488
965011AG1-365 GEN
Solar/Wind Harmer
3.044
944231AF1-091 GEN
Solar/Wind Harmer
0.807
252507AC2-088 GEN
Solar/Wind Helper
1.471
339216AC1-074 GEN
Solar/Wind Helper
1.461
943111AE2-339 GEN
Solar/Wind Helper
0.643
339241AF1-083 GEN
Solar/Wind Helper
0.405
253343AC1-166 GEN
Solar/Wind Helper
0.467
253325AC1-069 GEN
Solar/Wind Helper
0.484
24344205RKG1
50/50
11.244
24344205RKG1
50/50
11.22
24344305RKG2
50/50
11.199
270393AB1-087 CT1
50/50
2.508
270394AB1-087 ST1
50/50
2.508
970541AG2-344 GEN
50/50
10.209
970539AG2-343 GEN
50/50
9.364
970543AG2-345 GEN
50/50
4.682
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.647
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.256
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
9.104
274775LINCOLN ;6U
Adder
7.237
274776LINCOLN ;7U
Adder
7.237
274777LINCOLN ;8U
Adder
7.237
971769AH1-391 GEN
Solar/Wind Harmer
6.648
274814UNIV PK N;0U
Adder
4.294
274807UNIV PK N;3U
Adder
4.285
274805UNIV PK N;1U
Adder
4.266
274811UNIV PK N;7U
Adder
4.257
972227AH1-698 GEN1
Adder
2.206
960591AF2-350 GEN
Solar/Wind Harmer
5.898
972037AH1-567 GEN1
Adder
0.155
274827FISK ;RP
Adder
6.544
274687WILL CNTY;4U
Adder
23.403
274687WILL CNTY;4U
Adder
23.403
274731ELWOOD EC;2P
Adder
13.765
274733ELWOOD EC;3P
Adder
13.765
274735ELWOOD EC;4P
Adder
13.765
274728ELWOOD EC;5P
Adder
13.765
970833AG2-524 GEN
Solar/Wind Harmer
6.424
970833AG2-524 GEN
Solar/Wind Harmer
4.282
274675JOLIET 29;7U
Adder
25.664
274675JOLIET 29;7U
Adder
24.747
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
5.784
274746AC1-111 G10
Adder
4.62
274744AC1-111 GEN8
Adder
4.62
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.036
941731AE2-173 GEN
Solar/Wind Harmer
4.79
971771AH1-392 GEN
Solar/Wind Harmer
5.725
276868AE1-113 GEN
Solar/Wind Harmer
1.14
276882AE2-255 GEN
Solar/Wind Harmer
0.664
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.205
276848AB2-070 GEN3
Solar/Wind Harmer
0.204
926823AC1-168 GEN
Solar/Wind Harmer
0.954
971177AH1-047 GEN
Solar/Wind Harmer
3.447
971675AH1-338 GEN
Solar/Wind Harmer
2.173
971411AH1-196 GEN
Solar/Wind Harmer
8.347
971619AH1-309 GEN
Solar/Wind Harmer
2.5
971171AH1-044 GEN
Solar/Wind Harmer
11.069
274823ROCKFORD ;21
Adder
15.377
957751AF2-069 GEN
Solar/Wind Harmer
0.182
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
8.765
944221AF1-090 GEN
Solar/Wind Harmer
3.172
961011AF2-392 GEN
Solar/Wind Harmer
3.16
946321AF1-296 GEN
Solar/Wind Harmer
2.912
971549AH1-272 GEN
Solar/Wind Harmer
10.16
270071AF1-092 GEN
Solar/Wind Harmer
8.874
970289AG2-191 GEN
Solar/Wind Harmer
0.714
252524AE2-267 GEN
Solar/Wind Helper
0.465
339243AC2-075 GEN1
Solar/Wind Helper
0.336
339211AE2-254 GEN
Solar/Wind Helper
0.447
270367AC2-061_GEN
Solar/Wind Helper
1.692
270340AC2-060 GEN
Solar/Wind Helper
1.094
241972AD1-140 GEN
Solar/Wind Helper
2.07
944201AF1-088_MTX
50/50
166.885
957141AF2-008_MTX
50/50
83.443
955142J992
External Queue
11.408185005187988
990742J1381
External Queue
17.5482177734375
950011AG9-010
External Queue
6.204055309295654
991082J1475 G
External Queue
6.161812782287598
991312J1772
External Queue
12.355378150939941
991112J1481
External Queue
17.5482177734375
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.745
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.126
MECLTFEXP_MEC->PJM
CLTF
10.584
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.981
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.615
LAGNLTFEXP_LAGN->PJM
CLTF
2.246
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.176
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
1.043
WECLTFEXP_WEC->PJM
CLTF
2.99
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.226
AG2-052LTFEXP_AG2-052->PJM
LTF
0.2
AH1-155LTFEXP_AH1-155->PJM
LTF
0.301

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5081.52
MW Contribution:31.85
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.1
270120AB2-067 GEN2
50/50
7.1
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
970077AG2-063 GEN
Solar/Wind Harmer
6.25
270224U2-072_GEN2
Solar/Wind Harmer
2.287
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
270518AE2-148 GEN
Solar/Wind Harmer
13.911
253378AE2-206_GEN
Solar/Wind Harmer
4.016
276820AF1-078_GEN
Solar/Wind Harmer
1.784
972159AH1-661 GEN
Adder
1.111
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
970879AG2-548 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
970611AG2-400 GEN
Solar/Wind Harmer
10.775
971231AH1-075 GEN
Solar/Wind Harmer
0.862
270007AE1-245 C
Solar/Wind Harmer
6.374
942801AE2-298 GEN
Solar/Wind Harmer
1.626
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
960971AF2-388 GEN
Solar/Wind Harmer
11.659
942221AE2-234 GEN
Solar/Wind Harmer
0.781
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.634
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
24728905RICHG2
Adder
3.981
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
274803UNIV PARK;6U
Adder
5.997
972259AH1-714 GEN
Adder
19.596
274674JOLIET 9 ;6U
Adder
15.776
274696ROCKY RD ;4P
Adder
11.59
274695ROCKY RD ;2P
Adder
11.323
274693ROCKY RD ;1P
Adder
11.211
274697ROCKY RD ;3P
Adder
3.076
23585401KL_K28_T16
Solar/Wind Helper
1.493
238120AE2-309 GEN
Solar/Wind Helper
0.528
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.72
20390526W1-045 C
Solar/Wind Helper
0.351
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.509
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270459AD2-067 GEN
Solar/Wind Harmer
10.252
961821AG1-024 GEN
Solar/Wind Harmer
10.408
270054AF2-122 C O1
Solar/Wind Harmer
3.995
972239AH1-704 GEN
Adder
2.671
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270156DARBY CT1
Adder
10.432
270157DARBY CT2
Adder
10.407
270158DARBY CT3
Adder
10.24
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270302AB2-170 GEN
Solar/Wind Harmer
9.566
270317AD1-130_GEN
Solar/Wind Harmer
3.667
270269AC2-059
Solar/Wind Harmer
10.62
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
958581AF2-149 GEN
Solar/Wind Harmer
4.732
970179AG2-119 GEN
Solar/Wind Harmer
8.844
970879AG2-548 GEN
Solar/Wind Harmer
4.736
253372AE2-315 SEC3
Adder
2.071
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
253349AC2-067 GEN
Solar/Wind Harmer
5.421
253400AC2-068 GEN
Solar/Wind Harmer
2.18
957201AF2-014 GEN
Solar/Wind Harmer
4.91
270435AC2-044 GEN
Solar/Wind Harmer
2.165
965051AG1-369 GEN
Solar/Wind Harmer
5.38
965041AG1-368 GEN
Solar/Wind Harmer
10.749
247607V1-011 GEN
Solar/Wind Harmer
4.249
24729505KEY G4
Adder
6.948
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971567AH1-282 GEN
Solar/Wind Harmer
16.053
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270071AF1-092 GEN
Solar/Wind Harmer
16.048
971985AH1-537 GEN
Solar/Wind Harmer
19.051
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270024AE2-089 GEN
Solar/Wind Harmer
5.004
965101AG1-375 GEN
Solar/Wind Harmer
10.653
270367AC2-061_GEN
Solar/Wind Harmer
3.388
971673AH1-337 GEN
Solar/Wind Harmer
4.893
971029AG2-637 GEN
Solar/Wind Harmer
15.954
252524AE2-267 GEN
Solar/Wind Harmer
1.677
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
25196508WSDLE4
Adder
9.021
270543AE2-219 C
Solar/Wind Harmer
5.445
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
270297AD1-101 GEN
Solar/Wind Harmer
2.953
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274775LINCOLN ;6U
Adder
8.715
274776LINCOLN ;7U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274811UNIV PK N;7U
Adder
5.162
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274735ELWOOD EC;4P
Adder
16.844
274728ELWOOD EC;5P
Adder
16.844
270166AC1-044 GEN3
50/50
7.1
23559101PLEAS2
50/50
6.365
962761AG1-125 GEN
Solar/Wind Harmer
41.173
970149AG2-104 GEN
Solar/Wind Harmer
50.849
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
253343AC1-166 GEN
Solar/Wind Harmer
1.243
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270462AD2-086
Solar/Wind Harmer
7.958
971995AH1-542 GEN
Solar/Wind Harmer
12.515
270263AC1-001 GEN
Solar/Wind Harmer
1.179
25326309TAIT D
Adder
1.2
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
927014AC1-188 GEN
Solar/Wind Harmer
1.729
241813AF1-122_GEN
Solar/Wind Harmer
6.978
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965421AG1-410 GEN
Solar/Wind Harmer
32.464
960001AF2-291 GEN
Solar/Wind Harmer
3.264
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
972203AH1-686 GEN
Adder
2.356
274746AC1-111 G10
Adder
5.705
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.832
238152AF2-075_GEN
Solar/Wind Helper
0.709
238208AF1-136 C
Solar/Wind Helper
0.221
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.655
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
23750501ELLIOTTS
Solar/Wind Helper
0.644
959381AF2-229 GEN
Solar/Wind Helper
0.359
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.511
205932AD2-116_GEN
Solar/Wind Helper
0.511
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.508
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.786
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
965011AG1-365 GEN
Solar/Wind Harmer
10.775
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
958861AF2-177 GEN
Solar/Wind Harmer
11.644
247536S-71 GEN
Solar/Wind Harmer
4.305
25194608D.CRK4
Adder
1.747
945371AF1-202 GEN
Solar/Wind Harmer
7.414
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
25196808ZIMRHP
Adder
80.055
24639705ELKHART HY
Adder
0.162
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274754CRETE EC ;4U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274801UNIV PARK;4U
Adder
5.993
274676JOLIET 29;8U
Adder
31.445
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
274745AC1-111 GEN9
Adder
5.705
970091AG2-072 GEN
Adder
78.03
316095T157 G97
Solar/Wind Helper
1.508
23583801GRNGAP
Solar/Wind Helper
5.618
238185AF2-356 C
Solar/Wind Helper
2.662
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
23562501BACKB
Solar/Wind Helper
1.017
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.498
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.347
223402AF1-300 C
Solar/Wind Helper
0.369
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233982AB2-133 GEN
Solar/Wind Helper
0.359
233994AC2-023 GEN
Solar/Wind Helper
0.965
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.359
230430AE1-229_GEN
Solar/Wind Helper
3.385
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
24318805MLG1
50/50
10.158
23559001PLEAS1
50/50
6.365
270051AF1-062 GEN
50/50
11.843
270475AD2-096_GEN
50/50
7.165
970153AG2-106 GEN
Solar/Wind Harmer
17.953
961921AG1-034 GEN
Solar/Wind Harmer
15.612
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
942051AE2-217 GEN
Solar/Wind Harmer
21.08
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253338AC1-165 GEN
Solar/Wind Harmer
1.243
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.692
270273AD2-016 GEN
Solar/Wind Harmer
3.037
972173AH1-669 GEN
Solar/Wind Harmer
5.679
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
957541AF2-048 GEN
Solar/Wind Harmer
1.724
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
971191AH1-055 GEN
Solar/Wind Harmer
23.759
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270191TR4_S_V150
Solar/Wind Harmer
3.232
270247TR4_N_V136
Solar/Wind Harmer
0.916
959331AF2-224 GEN
Solar/Wind Harmer
10.775
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
270588AE1-091_GEN
Solar/Wind Harmer
11.804
944531AF1-118 GEN
Solar/Wind Harmer
37.541
270043AE2-236 GEN
Solar/Wind Harmer
5.893
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
25196608WSDLE5
Adder
9.114
962031AG1-047 GEN
Solar/Wind Harmer
3.214
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
25194608D.CRK4
Adder
1.747
270222AC2-111 GEN
Solar/Wind Harmer
8.657
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270044AE2-322 C
Solar/Wind Harmer
1.394
270404AC1-167 GEN
Solar/Wind Harmer
1.161
24642205MAYFLWER
Adder
0.667
25196008MFTGT1
Adder
1.411
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
274753CRETE EC ;3U
Adder
8.515
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
24728705AND G3
Adder
8.251
24728505AND G1
Adder
3.945
274826FISK ;BP
Adder
11.256
274800UNIV PARK;3U
Adder
5.993
972038AH1-567 GEN2
Adder
0.375
972228AH1-698 GEN2
Adder
3.807
274676JOLIET 29;8U
Adder
30.322
274729ELWOOD EC;1P
Adder
16.844
274730ELWOOD EC;6P
Adder
16.844
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238118U2-030_1
Solar/Wind Helper
0.344
238127S14_GEN_2
Solar/Wind Helper
0.832
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237080AD1-060 GEN
Solar/Wind Helper
0.343
237038AE2-054 C
Solar/Wind Helper
0.273
235062AE1-101 C1
Solar/Wind Helper
1.665
23779801AA1-109
Solar/Wind Helper
0.194
237048AF1-022 C
Solar/Wind Helper
0.179
223401AF1-299 GEN
Solar/Wind Helper
0.369
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.078
233930AB2-032 GEN
Solar/Wind Helper
0.382
233915AB1-141 GEN
Solar/Wind Helper
0.504
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.149
230434AG1-499 GEN
Solar/Wind Helper
0.231
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.577
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
202652Y1-033 WT C
Solar/Wind Helper
0.5
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
233970AC1-092 C
Solar/Wind Helper
0.351
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.327
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
203955AF1-039 C O1
Solar/Wind Helper
0.33
970321AG2-212 GEN
Solar/Wind Harmer
4.981
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
MECLTFEXP_MEC->PJM
CLTF
15.978
SIGELTFEXP_SIGE->PJM
CLTF
0.507
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
TVALTFEXP_TVA->PJM
CLTF
7.337
CPLELTFEXP_CPLE->PJM
CLTF
0.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
NYPJM->LTFIMP_NY
CLTF
4.819
LGEELTFEXP_LGEE->PJM
CLTF
6.781
WECLTFEXP_WEC->PJM
CLTF
3.842
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.21 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.2
MW Contribution:31.76
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
41.012
972239AH1-704 GEN
Adder
2.683
270459AD2-067 GEN
Solar/Wind Harmer
10.243
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
945631AF1-228 GEN
Solar/Wind Harmer
5.461
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
270158DARBY CT3
Adder
10.225
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.66
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.736
970179AG2-119 GEN
Solar/Wind Harmer
8.837
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.728
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
253349AC2-067 GEN
Solar/Wind Harmer
5.408
253400AC2-068 GEN
Solar/Wind Harmer
2.175
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.366
965041AG1-368 GEN
Solar/Wind Harmer
10.722
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
966831AG1-554 GEN
Solar/Wind Harmer
1.279
971989AH1-539 GEN
Solar/Wind Harmer
13.833
24729505KEY G4
Adder
6.928
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270071AF1-092 GEN
Solar/Wind Harmer
16.001
971985AH1-537 GEN
Solar/Wind Harmer
18.998
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.99
270367AC2-061_GEN
Solar/Wind Harmer
3.379
965101AG1-375 GEN
Solar/Wind Harmer
10.622
270166AC1-044 GEN3
50/50
7.072
23559101PLEAS2
50/50
6.183
962761AG1-125 GEN
Solar/Wind Harmer
41.012
970149AG2-104 GEN
Solar/Wind Harmer
50.65
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.241
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
24318805MLG1
50/50
10.115
23559001PLEAS1
50/50
6.183
270051AF1-062 GEN
50/50
11.828
270475AD2-096_GEN
50/50
7.148
970153AG2-106 GEN
Solar/Wind Harmer
17.883
961921AG1-034 GEN
Solar/Wind Harmer
15.599
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
942051AE2-217 GEN
Solar/Wind Harmer
21.044
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.241
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.032
972173AH1-669 GEN
Solar/Wind Harmer
5.669
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
970065AG2-057 GEN
Solar/Wind Harmer
1.09
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
971191AH1-055 GEN
Solar/Wind Harmer
23.693
270119AB2-067 GEN1
50/50
7.072
270120AB2-067 GEN2
50/50
7.072
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
970077AG2-063 GEN
Solar/Wind Harmer
6.239
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972269AH1-719 GEN
Adder
2.575
972159AH1-661 GEN
Adder
1.116
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
971201AH1-060 GEN
Solar/Wind Harmer
2.179
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
960971AF2-388 GEN
Solar/Wind Harmer
11.625
942221AE2-234 GEN
Solar/Wind Harmer
0.779
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.605
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194408D.CRK1
Adder
8.014
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
24728905RICHG2
Adder
3.969
274770LINCOLN ;1U
Adder
8.688
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
274803UNIV PARK;6U
Adder
5.978
972259AH1-714 GEN
Adder
19.535
274674JOLIET 9 ;6U
Adder
15.727
274696ROCKY RD ;4P
Adder
11.554
274695ROCKY RD ;2P
Adder
11.287
274693ROCKY RD ;1P
Adder
11.176
274697ROCKY RD ;3P
Adder
3.066
23585401KL_K28_T16
Solar/Wind Helper
1.485
238120AE2-309 GEN
Solar/Wind Helper
0.526
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
971995AH1-542 GEN
Solar/Wind Harmer
12.502
270263AC1-001 GEN
Solar/Wind Harmer
1.177
25326309TAIT D
Adder
1.197
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
241813AF1-122_GEN
Solar/Wind Harmer
6.974
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.386
960001AF2-291 GEN
Solar/Wind Harmer
3.255
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.746
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
958861AF2-177 GEN
Solar/Wind Harmer
11.61
247536S-71 GEN
Solar/Wind Harmer
4.293
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.392
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
25196808ZIMRHP
Adder
79.831
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274754CRETE EC ;4U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274801UNIV PARK;4U
Adder
5.975
274676JOLIET 29;8U
Adder
31.348
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
274745AC1-111 GEN9
Adder
5.687
970091AG2-072 GEN
Adder
77.755
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.606
238185AF2-356 C
Solar/Wind Helper
2.651
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
971673AH1-337 GEN
Solar/Wind Harmer
4.88
252524AE2-267 GEN
Solar/Wind Harmer
1.673
971029AG2-637 GEN
Solar/Wind Harmer
15.909
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
25196508WSDLE4
Adder
8.996
270543AE2-219 C
Solar/Wind Harmer
5.43
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.688
274776LINCOLN ;7U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274811UNIV PK N;7U
Adder
5.147
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
274735ELWOOD EC;4P
Adder
16.792
274728ELWOOD EC;5P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274746AC1-111 G10
Adder
5.687
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.829
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.651
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.64
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
270377AD1-106 GEN
Solar/Wind Harmer
6.649
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270191TR4_S_V150
Solar/Wind Harmer
3.224
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.746
965021AG1-366 GEN
Solar/Wind Harmer
2.499
958091AF2-103 GEN
Solar/Wind Harmer
0.173
270588AE1-091_GEN
Solar/Wind Harmer
11.789
944531AF1-118 GEN
Solar/Wind Harmer
37.432
270043AE2-236 GEN
Solar/Wind Harmer
5.876
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
25196608WSDLE5
Adder
9.089
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.632
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270044AE2-322 C
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
274753CRETE EC ;3U
Adder
8.489
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
24728705AND G3
Adder
8.226
274802UNIV PARK;5U
Adder
5.978
24728505AND G1
Adder
3.933
274826FISK ;BP
Adder
11.221
274800UNIV PARK;3U
Adder
5.975
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.796
274676JOLIET 29;8U
Adder
30.228
274729ELWOOD EC;1P
Adder
16.792
274730ELWOOD EC;6P
Adder
16.792
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238118U2-030_1
Solar/Wind Helper
0.342
238127S14_GEN_2
Solar/Wind Helper
0.829
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.178
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
232434Z2-077 GEN
Solar/Wind Helper
0.127
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.06
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
23562501BACKB
Solar/Wind Helper
1.01
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.728
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.728
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
233990AG1-397 GEN
Solar/Wind Helper
0.03
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.501
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
MECLTFEXP_MEC->PJM
CLTF
15.925
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
TVALTFEXP_TVA->PJM
CLTF
7.306
CPLELTFEXP_CPLE->PJM
CLTF
0.632
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.759
WECLTFEXP_WEC->PJM
CLTF
3.83
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:31.75
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:31.75
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.92 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5002.28
MW Contribution:4.79
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.49 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4985.98
MW Contribution:32.39
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
270119AB2-067 GEN1
50/50
7.033
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4754.33
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.95 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5175.39
MW Contribution:36.88
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
16.969
270475AD2-096_GEN
50/50
10
970153AG2-106 GEN
Solar/Wind Harmer
25.994
961921AG1-034 GEN
Solar/Wind Harmer
20.196
241955AC1-078 GEN
Solar/Wind Harmer
11.082
241974AD2-163_GEN2
Solar/Wind Harmer
2.945
942051AE2-217 GEN
Solar/Wind Harmer
26.379
942871AE2-306 GEN
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.673
970605AG2-385 GEN
Solar/Wind Harmer
7.746
270485AE1-090_GEN
Solar/Wind Harmer
0.845
253338AC1-165 GEN
Solar/Wind Harmer
1.495
253333AC1-068 GEN
Solar/Wind Harmer
1.442
960801AF2-371 GEN
Solar/Wind Harmer
3.362
964871AG1-351 GEN
Solar/Wind Harmer
2.322
270273AD2-016 GEN
Solar/Wind Harmer
3.416
944531AF1-118 GEN
Solar/Wind Harmer
44.619
972173AH1-669 GEN
Solar/Wind Harmer
6.355
270043AE2-236 GEN
Solar/Wind Harmer
6.955
959331AF2-224 GEN
Solar/Wind Harmer
12.615
965021AG1-366 GEN
Solar/Wind Harmer
2.934
253303V4-073 C
Solar/Wind Harmer
0.146
253370AE2-315 SEC1
Adder
2.522
253371AE2-315 SEC2
Adder
2.385
970513AG2-328 GEN
Solar/Wind Harmer
22.419
970517AG2-330 GEN
Solar/Wind Harmer
20.333
253415AE1-040 GEN
Solar/Wind Harmer
1.412
970349AG2-230 GEN
Solar/Wind Harmer
18.681
270191TR4_S_V150
Solar/Wind Harmer
3.726
270247TR4_N_V136
Solar/Wind Harmer
1.057
24721905FLATG4
Adder
25.137
971617AH1-308 GEN
Solar/Wind Harmer
7.196
270491AE1-102 GEN2
Solar/Wind Harmer
1.608
962031AG1-047 GEN
Solar/Wind Harmer
3.725
957741AF2-068 GEN
Solar/Wind Harmer
18.489
970031AG2-029 GEN
Solar/Wind Harmer
36.885
958821AF2-173 GEN
Solar/Wind Harmer
17.206
270004AE1-209 GEN
Solar/Wind Harmer
6.717
946031AF1-268 GEN
Solar/Wind Harmer
10.188
253406AD2-031_GEN
Solar/Wind Harmer
1.568
970289AG2-191 GEN
Solar/Wind Harmer
0.938
970291AG2-192 GEN
Solar/Wind Harmer
0.853
247642Z2-115 C
Solar/Wind Harmer
0.078
270437AC2-090 C
Solar/Wind Harmer
6.819
247643Z2-116 C
Solar/Wind Harmer
0.085
274772LINCOLN ;3U
Adder
10.257
274724RIVER EC ;11
Adder
21.436
274752CRETE EC ;2U
Adder
9.969
274753CRETE EC ;3U
Adder
9.969
24642205MAYFLWER
Adder
0.769
274802UNIV PARK;5U
Adder
7.033
972228AH1-698 GEN2
Adder
4.468
274826FISK ;BP
Adder
13.204
274800UNIV PARK;3U
Adder
7.031
972038AH1-567 GEN2
Adder
0.44
274676JOLIET 29;8U
Adder
35.583
274729ELWOOD EC;1P
Adder
19.763
274730ELWOOD EC;6P
Adder
19.763
274734ELWOOD EC;8P
Adder
19.763
274736ELWOOD EC;9P
Adder
19.763
274682WAUKEGAN ;7U
Adder
21.437
25196608WSDLE5
Adder
10.207
25194608D.CRK4
Adder
1.955
24728705AND G3
Adder
9.473
24728505AND G1
Adder
4.529
972236AH1-702 GEN2
Adder
2.586
235058AG1-386 C
Solar/Wind Helper
0.458
237048AF1-022 C
Solar/Wind Helper
0.178
254305AE2-115 C
Solar/Wind Helper
0.216
237043AE2-125 C
Solar/Wind Helper
0.174
964991AG1-363 GEN
Solar/Wind Helper
3.62
202652Y1-033 WT C
Solar/Wind Helper
0.532
20089126CSLMN_L13
Solar/Wind Helper
0.564
20089026BF_G21_K23
Solar/Wind Helper
0.447
23750701CROSSCHOOL
Solar/Wind Helper
1.136
203818AF1-086 GEN
Solar/Wind Helper
1.615
238118U2-030_1
Solar/Wind Helper
0.272
238127S14_GEN_2
Solar/Wind Helper
0.648
203854AF2-039 C
Solar/Wind Helper
0.304
20334926Z1-069 C
Solar/Wind Helper
1.285
238202AE2-262_GEN
Solar/Wind Helper
0.914
959441AF2-235 GEN
Solar/Wind Helper
0.223
941421AE2-139 GEN
Solar/Wind Helper
2.214
253316AC1-085 GEN3
Solar/Wind Harmer
9.161
253433AC1-085 GEN1
Solar/Wind Harmer
5.815
270166AC1-044 GEN3
50/50
18.357
270159DARBY CT4
50/50
13.387
962761AG1-125 GEN
Solar/Wind Harmer
59.614
970149AG2-104 GEN
Solar/Wind Harmer
73.623
970155AG2-107 GEN
Solar/Wind Harmer
25.994
270349AD2-093_GEN
Solar/Wind Harmer
6.249
270223U2-072_GEN1
Solar/Wind Harmer
2.862
270578AF1-285 GEN2
Solar/Wind Harmer
1.75
270391AF1-285 GEN3
Solar/Wind Harmer
1.75
970593AG2-378 GEN
Solar/Wind Harmer
2.869
270462AD2-086
Solar/Wind Harmer
9.72
253343AC1-166 GEN
Solar/Wind Harmer
1.495
253325AC1-069 GEN
Solar/Wind Harmer
1.442
25326309TAIT D
Adder
1.387
960071AF2-298 GEN
Solar/Wind Harmer
6.296
965011AG1-365 GEN
Solar/Wind Harmer
12.615
253370AE2-315 SEC1
Adder
2.522
253371AE2-315 SEC2
Adder
2.385
965651AG1-433 GEN
Solar/Wind Harmer
6.877
970245AG2-165 GEN
Solar/Wind Harmer
22.419
958861AF2-177 GEN
Solar/Wind Harmer
13.71
971995AH1-542 GEN
Solar/Wind Harmer
13.79
945371AF1-202 GEN
Solar/Wind Harmer
8.699
247521TR3_G114
Solar/Wind Harmer
4.176
270246TR4_N_V150
Solar/Wind Harmer
1.057
24721705FLATG2
Adder
25.137
965421AG1-410 GEN
Solar/Wind Harmer
37.184
246936BC-WTG1
Solar/Wind Harmer
4.841
270489AE1-102 GEN1
Solar/Wind Harmer
1.608
247536S-71 GEN
Solar/Wind Harmer
4.98
270005AE1-210 C O1
Solar/Wind Harmer
6.717
965031AG1-367 GEN
Solar/Wind Harmer
12.29
270063AE2-323 C
Solar/Wind Harmer
2.705
24695305TIMB G C
Solar/Wind Harmer
6.75
970825AG2-519 GEN
Solar/Wind Harmer
2.886
270263AC1-001 GEN
Solar/Wind Harmer
1.282
270032AE2-172
Solar/Wind Harmer
5.689
970291AG2-192 GEN
Solar/Wind Harmer
1.589
942081AE2-220 GEN
Solar/Wind Harmer
7.808
270239V3-007_GEN1
Solar/Wind Harmer
2.102
24639705ELKHART HY
Adder
0.187
274773LINCOLN ;4U
Adder
10.257
274774LINCOLN ;5U
Adder
10.257
274723RIVER EC ;12
Adder
21.689
274751CRETE EC ;1U
Adder
9.969
274754CRETE EC ;4U
Adder
9.969
274812UNIV PK N;8U
Adder
6.05
274801UNIV PARK;4U
Adder
7.031
274676JOLIET 29;8U
Adder
36.901
274674JOLIET 9 ;6U
Adder
18.512
274732ELWOOD EC;7P
Adder
19.763
274745AC1-111 GEN9
Adder
6.698
274682WAUKEGAN ;7U
Adder
21.437
274828WAUKEGAN ;BP
Adder
13.169
25194608D.CRK4
Adder
1.955
24728605AND G2
Adder
4.529
274822ROCKFORD ;11
Adder
23.174
972235AH1-702 GEN1
Adder
2.974
25196808ZIMRHP
Adder
57.753
254303AC2-168 GEN
Solar/Wind Helper
0.156
237046AF1-021 C
Solar/Wind Helper
0.468
241966AE1-183 GEN
Solar/Wind Helper
0.251
238185AF2-356 C
Solar/Wind Helper
2.051
20089226LOOKOUT
Solar/Wind Helper
0.549
20088826HIGHLAND
Solar/Wind Helper
0.858
20094526CT_V3-030
Solar/Wind Helper
0.452
235054AD2-180 GEN
Solar/Wind Helper
1.586
964201AG1-281 GEN
Solar/Wind Helper
0.463
238117U2-030
Solar/Wind Helper
0.272
235531U2-073 GEN
Solar/Wind Helper
2.578
964391AG1-301 GEN
Solar/Wind Helper
0.452
203954AE2-126 C
Solar/Wind Helper
0.449
23751201ROTHROCK
Solar/Wind Helper
0.661
238206AE2-263_GEN
Solar/Wind Helper
0.87
959471AF2-238 GEN
Solar/Wind Helper
0.445
203860AG1-193 C
Solar/Wind Helper
0.222
23562501BACKB
Solar/Wind Helper
0.804
253432AC1-085 GEN2
Solar/Wind Harmer
0.293
270156DARBY CT1
50/50
13.604
270157DARBY CT2
50/50
13.571
270158DARBY CT3
50/50
13.354
270036AE2-216 BAT
50/50
8.921
962771AG1-126 GEN
Solar/Wind Harmer
59.614
270284AF1-227 GEN1
Solar/Wind Harmer
9.137
270286AF1-227 GEN2
Solar/Wind Harmer
3.38
270287AF1-227 GEN3
Solar/Wind Harmer
3.38
270459AD2-067 GEN
Solar/Wind Harmer
13.262
961821AG1-024 GEN
Solar/Wind Harmer
13.464
270520AE2-214 GEN
Solar/Wind Harmer
9.4
270054AF2-122 C O1
Solar/Wind Harmer
5.025
253383AE2-342_GEN
Solar/Wind Harmer
1.352
241973AD2-163_GEN1
Solar/Wind Harmer
2.945
943861AF1-054 GEN
Solar/Wind Harmer
5.682
943851AF1-053 GEN
Solar/Wind Harmer
2.746
270578AF1-285 GEN2
Solar/Wind Harmer
0.673
945631AF1-228 GEN
Solar/Wind Harmer
6.732
270302AB2-170 GEN
Solar/Wind Harmer
11.684
270317AD1-130_GEN
Solar/Wind Harmer
4.479
241972AD1-140 GEN
Solar/Wind Harmer
6.007
970689AG2-444 GEN
Solar/Wind Harmer
21.667
270432AC2-029 GEN
Solar/Wind Harmer
9.275
270269AC2-059
Solar/Wind Harmer
11.946
24729505KEY G4
Adder
8.242
270071AF1-092 GEN
Solar/Wind Harmer
18.992
253372AE2-315 SEC3
Adder
2.385
253372AE2-315 SEC3
Adder
2.385
958711AF2-162 GEN
Solar/Wind Harmer
1.273
965101AG1-375 GEN
Solar/Wind Harmer
12.544
25306009OHH W.
Adder
3.614
253349AC2-067 GEN
Solar/Wind Harmer
6.244
253400AC2-068 GEN
Solar/Wind Harmer
2.511
945581AF1-223 GEN
Solar/Wind Harmer
5.655
963791AG1-232 GEN
Solar/Wind Harmer
16.817
971347AH1-153 GEN
Solar/Wind Harmer
18.681
965051AG1-369 GEN
Solar/Wind Harmer
6.202
965041AG1-368 GEN
Solar/Wind Harmer
12.384
270024AE2-089 GEN
Solar/Wind Harmer
5.81
957201AF2-014 GEN
Solar/Wind Harmer
5.611
270435AC2-044 GEN
Solar/Wind Harmer
2.474
270340AC2-060 GEN
Solar/Wind Harmer
3.749
961761AG1-017 GEN
Solar/Wind Harmer
0.528
270119AB2-067 GEN1
50/50
18.357
270120AB2-067 GEN2
50/50
18.357
270160DARBY CT5
50/50
0.729
270161DARBY CT6
50/50
0.719
270466AD2-091
50/50
8.11
270471AD2-092_GEN
Solar/Wind Harmer
6.249
946101AF1-275 GEN
Solar/Wind Harmer
2.346
942861AE2-305 GEN
Solar/Wind Harmer
11.513
270224U2-072_GEN2
Solar/Wind Harmer
2.862
270227U2-072_GEN3
Solar/Wind Harmer
2.862
270228U2-072_GEN4
Solar/Wind Harmer
2.862
270231U2-072_GEN5
Solar/Wind Harmer
2.862
970077AG2-063 GEN
Solar/Wind Harmer
7.746
270518AE2-148 GEN
Solar/Wind Harmer
16.865
964601AG1-323 GEN
Solar/Wind Harmer
4.402
964601AG1-323 GEN
Solar/Wind Harmer
2.047
938701AE1-092 GEN
Solar/Wind Harmer
28.355
253378AE2-206_GEN
Solar/Wind Harmer
4.74
276820AF1-078_GEN
Solar/Wind Harmer
2.106
25326509SID D
Adder
1.698
25326109MON D
Adder
1.683
25322209TAIT E
Adder
12.344
25322209TAIT E
Adder
12.066
970611AG2-400 GEN
Solar/Wind Harmer
12.615
253370AE2-315 SEC1
Adder
2.522
944541AF1-119 GEN
Solar/Wind Harmer
5.27
960971AF2-388 GEN
Solar/Wind Harmer
13.754
970321AG2-212 GEN
Solar/Wind Harmer
22.419
942221AE2-234 GEN
Solar/Wind Harmer
0.913
246938BC-WTG3
Solar/Wind Harmer
4.925
246937BC-WTG2
Solar/Wind Harmer
4.841
270599AE1-208 GEN
Solar/Wind Harmer
10.052
270031AE2-169
Solar/Wind Harmer
10.052
253394AE2-221_GEN
Solar/Wind Harmer
5.603
253398AE2-221_GEN2
Solar/Wind Harmer
5.603
270201AC2-176 GEN
Solar/Wind Harmer
6.336
964611AG1-324 GEN
Solar/Wind Harmer
1.452
964611AG1-324 GEN
Solar/Wind Harmer
0.644
247621Y3-024
Adder
0.297
970883AG2-550 GEN
Solar/Wind Harmer
12.281
970885AG2-551 GEN
Solar/Wind Harmer
2.856
970825AG2-519 GEN
Solar/Wind Harmer
12.934
960441AF2-335 GEN
Solar/Wind Harmer
12.253
270383AD1-128 GEN
Solar/Wind Harmer
7.465
24379505HDWTR1G C
Solar/Wind Harmer
9.658
270209AC1-174_GEN
Solar/Wind Harmer
6.816
926881AC1-175 GEN
Solar/Wind Harmer
6.816
965681AG1-436 GEN
Solar/Wind Harmer
15.255
965791AG1-447 GEN
Solar/Wind Harmer
7.805
270216AD2-079_GEN
Solar/Wind Harmer
0.738
247620Y3-023
Adder
0.56
274770LINCOLN ;1U
Adder
10.257
274771LINCOLN ;2U
Adder
10.257
274808UNIV PK N;4U
Adder
6.023
972259AH1-714 GEN
Adder
23.016
274803UNIV PARK;6U
Adder
7.033
24728805RICHG1
Adder
4.555
24728905RICHG2
Adder
4.555
274674JOLIET 9 ;6U
Adder
18.512
274696ROCKY RD ;4P
Adder
13.603
274695ROCKY RD ;2P
Adder
13.289
274693ROCKY RD ;1P
Adder
13.158
274697ROCKY RD ;3P
Adder
3.61
274683WAUKEGAN ;8U
Adder
25.124
274683WAUKEGAN ;8U
Adder
21.178
25194408D.CRK1
Adder
8.991
25194508D.CRK3
Adder
1.681
23652301WDPWR_K20
Solar/Wind Helper
0.139
241967AE2-285_GEN
Solar/Wind Helper
0.629
241801AE1-079 GEN
Solar/Wind Helper
0.245
241985AE1-237 GEN
Solar/Wind Helper
0.245
962101AG1-054 GEN
Solar/Wind Helper
0.639
946071AF1-272 GEN
Solar/Wind Helper
2.599
23585401KL_K28_T16
Solar/Wind Helper
1.182
203955AF1-039 C O1
Solar/Wind Helper
0.351
944781AF1-143 GEN
Solar/Wind Helper
2.342
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.34
20088926STNY CRK
Solar/Wind Helper
0.78
203940AF1-140 C
Solar/Wind Helper
0.378
20088626ARWF_N39
Solar/Wind Helper
1.161
20303426NA_O38_P22
Solar/Wind Helper
0.952
946381AF1-302 GEN
Solar/Wind Helper
0.212
203853AF1-134 C O1
Solar/Wind Helper
0.457
203952AE2-129 C
Solar/Wind Helper
0.453
203946AE2-131 C
Solar/Wind Helper
0.454
238120AE2-309 GEN
Solar/Wind Helper
0.406
238217AF1-153 C O1
Solar/Wind Helper
0.226
20398826ARMNA MT
Solar/Wind Helper
1.425
253317AC1-085 GEN4
Solar/Wind Harmer
9.161
270543AE2-219 C
Solar/Wind Harmer
6.289
971029AG2-637 GEN
Solar/Wind Harmer
18.391
971673AH1-337 GEN
Solar/Wind Harmer
5.637
970115AG2-085 GEN
Solar/Wind Harmer
4.901
270594AE1-207 GEN
Solar/Wind Harmer
17.978
965461AG1-414 GEN
Solar/Wind Harmer
2.772
970289AG2-191 GEN
Solar/Wind Harmer
2.322
270240V3-007_GEN2
Solar/Wind Harmer
7.556
960681AF2-359 GEN
Solar/Wind Harmer
4.61
971771AH1-392 GEN
Solar/Wind Harmer
10.956
274775LINCOLN ;6U
Adder
10.257
274776LINCOLN ;7U
Adder
10.257
274777LINCOLN ;8U
Adder
10.257
274814UNIV PK N;0U
Adder
6.103
274807UNIV PK N;3U
Adder
6.089
274805UNIV PK N;1U
Adder
6.063
274811UNIV PK N;7U
Adder
6.05
972227AH1-698 GEN1
Adder
3.146
972037AH1-567 GEN1
Adder
0.221
274827FISK ;RP
Adder
9.358
274687WILL CNTY;4U
Adder
33.62
274687WILL CNTY;4U
Adder
33.62
274675JOLIET 29;7U
Adder
36.901
274675JOLIET 29;7U
Adder
35.583
274731ELWOOD EC;2P
Adder
19.763
274733ELWOOD EC;3P
Adder
19.763
274735ELWOOD EC;4P
Adder
19.763
274728ELWOOD EC;5P
Adder
19.763
274746AC1-111 G10
Adder
6.698
274744AC1-111 GEN8
Adder
6.698
25196408WSDLE3
Adder
10.507
25196308WSDLE2
Adder
10.416
25196208WSDLE1
Adder
10.39
25196708WSDLE6
Adder
10.364
25196508WSDLE4
Adder
10.103
274823ROCKFORD ;21
Adder
23.006
254304AE2-114 C
Solar/Wind Helper
0.216
241982AE2-343 S C
Solar/Wind Helper
0.22
241997AF1-093 GEN
Solar/Wind Helper
0.251
23750501ELLIOTTS
Solar/Wind Helper
0.617
20092526R32
Solar/Wind Helper
1.112
203961AE2-224 GEN
Solar/Wind Helper
2.307
20091526CHSTN_FL
Solar/Wind Helper
0.557
20090526Q36
Solar/Wind Helper
0.998
203993AD2-133_GEN1
Solar/Wind Helper
0.998
203846AF2-130 C
Solar/Wind Helper
0.431
238126S14_GEN_1
Solar/Wind Helper
0.648
941231AE2-117 GEN
Solar/Wind Helper
0.453
203855AF2-088 C
Solar/Wind Helper
0.146
203804AE2-113_GEN
Solar/Wind Helper
1.661
CBM West 1LTFEXP_CBM-W1->PJM
CBM
154.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.973
MECLTFEXP_MEC->PJM
CLTF
18.683
SIGELTFEXP_SIGE->PJM
CLTF
0.577
LAGNLTFEXP_LAGN->PJM
CLTF
17.654
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.421
TVALTFEXP_TVA->PJM
CLTF
8.605
CPLELTFEXP_CPLE->PJM
CLTF
2.579
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.191
NYPJM->LTFIMP_NY
CLTF
5.405
LGEELTFEXP_LGEE->PJM
CLTF
7.595
WECLTFEXP_WEC->PJM
CLTF
4.506
AG2-052LTFEXP_AG2-052->PJM
LTF
0.28
AH1-155LTFEXP_AH1-155->PJM
LTF
0.42

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.6 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4995.09
MW Contribution:37.39
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
18.415
270159DARBY CT4
50/50
13.555
962761AG1-125 GEN
Solar/Wind Harmer
60.17
970149AG2-104 GEN
Solar/Wind Harmer
74.31
970155AG2-107 GEN
Solar/Wind Harmer
26.237
270349AD2-093_GEN
Solar/Wind Harmer
6.312
270223U2-072_GEN1
Solar/Wind Harmer
2.896
270051AF1-062 GEN
50/50
17.137
270475AD2-096_GEN
50/50
10.101
970153AG2-106 GEN
Solar/Wind Harmer
26.237
961921AG1-034 GEN
Solar/Wind Harmer
20.428
241955AC1-078 GEN
Solar/Wind Harmer
11.216
241974AD2-163_GEN2
Solar/Wind Harmer
2.98
942051AE2-217 GEN
Solar/Wind Harmer
26.699
942871AE2-306 GEN
Solar/Wind Harmer
1.328
270391AF1-285 GEN3
Solar/Wind Harmer
0.681
970605AG2-385 GEN
Solar/Wind Harmer
7.841
270485AE1-090_GEN
Solar/Wind Harmer
0.855
253338AC1-165 GEN
Solar/Wind Harmer
1.515
253333AC1-068 GEN
Solar/Wind Harmer
1.461
960801AF2-371 GEN
Solar/Wind Harmer
3.409
964871AG1-351 GEN
Solar/Wind Harmer
2.354
270273AD2-016 GEN
Solar/Wind Harmer
3.465
944531AF1-118 GEN
Solar/Wind Harmer
45.213
972173AH1-669 GEN
Solar/Wind Harmer
6.446
270043AE2-236 GEN
Solar/Wind Harmer
7.048
959331AF2-224 GEN
Solar/Wind Harmer
12.784
965021AG1-366 GEN
Solar/Wind Harmer
2.973
253303V4-073 C
Solar/Wind Harmer
0.148
253370AE2-315 SEC1
Adder
2.557
253371AE2-315 SEC2
Adder
2.418
970513AG2-328 GEN
Solar/Wind Harmer
22.72
970517AG2-330 GEN
Solar/Wind Harmer
20.606
253415AE1-040 GEN
Solar/Wind Harmer
1.432
970349AG2-230 GEN
Solar/Wind Harmer
18.933
270191TR4_S_V150
Solar/Wind Harmer
3.777
270247TR4_N_V136
Solar/Wind Harmer
1.071
24721905FLATG4
Adder
25.49
971617AH1-308 GEN
Solar/Wind Harmer
7.295
270491AE1-102 GEN2
Solar/Wind Harmer
1.63
962031AG1-047 GEN
Solar/Wind Harmer
3.777
957741AF2-068 GEN
Solar/Wind Harmer
18.744
970031AG2-029 GEN
Solar/Wind Harmer
37.389
958821AF2-173 GEN
Solar/Wind Harmer
17.445
270004AE1-209 GEN
Solar/Wind Harmer
6.81
946031AF1-268 GEN
Solar/Wind Harmer
10.33
253406AD2-031_GEN
Solar/Wind Harmer
1.591
970289AG2-191 GEN
Solar/Wind Harmer
0.951
970291AG2-192 GEN
Solar/Wind Harmer
0.865
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.914
247643Z2-116 C
Solar/Wind Harmer
0.086
253316AC1-085 GEN3
Solar/Wind Harmer
10.337
253433AC1-085 GEN1
Solar/Wind Harmer
6.562
274772LINCOLN ;3U
Adder
10.399
274724RIVER EC ;11
Adder
21.733
274752CRETE EC ;2U
Adder
10.107
274753CRETE EC ;3U
Adder
10.107
24642205MAYFLWER
Adder
0.779
274802UNIV PARK;5U
Adder
7.13
972228AH1-698 GEN2
Adder
4.53
274826FISK ;BP
Adder
13.387
274800UNIV PARK;3U
Adder
7.128
972038AH1-567 GEN2
Adder
0.446
274676JOLIET 29;8U
Adder
36.078
274729ELWOOD EC;1P
Adder
20.037
274730ELWOOD EC;6P
Adder
20.037
274734ELWOOD EC;8P
Adder
20.037
274736ELWOOD EC;9P
Adder
20.037
274682WAUKEGAN ;7U
Adder
21.737
25196608WSDLE5
Adder
10.356
25194608D.CRK4
Adder
1.983
24728705AND G3
Adder
9.609
24728505AND G1
Adder
4.594
972236AH1-702 GEN2
Adder
2.622
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.177
254305AE2-115 C
Solar/Wind Helper
0.213
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.598
202652Y1-033 WT C
Solar/Wind Helper
0.528
23750701CROSSCHOOL
Solar/Wind Helper
1.128
20089126CSLMN_L13
Solar/Wind Helper
0.559
20089026BF_G21_K23
Solar/Wind Helper
0.443
203818AF1-086 GEN
Solar/Wind Helper
1.599
238118U2-030_1
Solar/Wind Helper
0.27
238127S14_GEN_2
Solar/Wind Helper
0.644
203854AF2-039 C
Solar/Wind Helper
0.301
20334926Z1-069 C
Solar/Wind Helper
1.271
238202AE2-262_GEN
Solar/Wind Helper
0.905
959441AF2-235 GEN
Solar/Wind Helper
0.22
946181AF1-283 GEN
Solar/Wind Harmer
8.323
270119AB2-067 GEN1
50/50
18.415
270120AB2-067 GEN2
50/50
18.415
270160DARBY CT5
50/50
0.738
270161DARBY CT6
50/50
0.728
270466AD2-091
50/50
8.21
270471AD2-092_GEN
Solar/Wind Harmer
6.312
946101AF1-275 GEN
Solar/Wind Harmer
2.373
270156DARBY CT1
50/50
13.775
270157DARBY CT2
50/50
13.741
270158DARBY CT3
50/50
13.521
270036AE2-216 BAT
50/50
9.031
962771AG1-126 GEN
Solar/Wind Harmer
60.17
270284AF1-227 GEN1
Solar/Wind Harmer
9.235
270286AF1-227 GEN2
Solar/Wind Harmer
3.417
270287AF1-227 GEN3
Solar/Wind Harmer
3.417
270459AD2-067 GEN
Solar/Wind Harmer
13.414
961821AG1-024 GEN
Solar/Wind Harmer
13.619
270520AE2-214 GEN
Solar/Wind Harmer
9.509
270054AF2-122 C O1
Solar/Wind Harmer
5.085
253383AE2-342_GEN
Solar/Wind Harmer
1.367
241973AD2-163_GEN1
Solar/Wind Harmer
2.98
943861AF1-054 GEN
Solar/Wind Harmer
5.751
943851AF1-053 GEN
Solar/Wind Harmer
2.779
270578AF1-285 GEN2
Solar/Wind Harmer
0.681
945631AF1-228 GEN
Solar/Wind Harmer
6.816
270302AB2-170 GEN
Solar/Wind Harmer
11.828
270317AD1-130_GEN
Solar/Wind Harmer
4.534
241972AD1-140 GEN
Solar/Wind Harmer
6.086
970689AG2-444 GEN
Solar/Wind Harmer
21.964
270432AC2-029 GEN
Solar/Wind Harmer
9.402
270269AC2-059
Solar/Wind Harmer
12.116
24729505KEY G4
Adder
8.352
270071AF1-092 GEN
Solar/Wind Harmer
19.246
253372AE2-315 SEC3
Adder
2.418
253372AE2-315 SEC3
Adder
2.418
958711AF2-162 GEN
Solar/Wind Harmer
1.29
25306009OHH W.
Adder
3.664
965101AG1-375 GEN
Solar/Wind Harmer
12.713
253349AC2-067 GEN
Solar/Wind Harmer
6.33
253400AC2-068 GEN
Solar/Wind Harmer
2.546
945581AF1-223 GEN
Solar/Wind Harmer
5.732
963791AG1-232 GEN
Solar/Wind Harmer
17.046
971347AH1-153 GEN
Solar/Wind Harmer
18.933
965051AG1-369 GEN
Solar/Wind Harmer
6.287
965041AG1-368 GEN
Solar/Wind Harmer
12.553
270024AE2-089 GEN
Solar/Wind Harmer
5.889
270340AC2-060 GEN
Solar/Wind Harmer
3.803
957201AF2-014 GEN
Solar/Wind Harmer
5.688
270435AC2-044 GEN
Solar/Wind Harmer
2.508
961761AG1-017 GEN
Solar/Wind Harmer
0.535
270543AE2-219 C
Solar/Wind Harmer
6.376
971029AG2-637 GEN
Solar/Wind Harmer
18.648
971673AH1-337 GEN
Solar/Wind Harmer
5.716
970115AG2-085 GEN
Solar/Wind Harmer
4.969
270594AE1-207 GEN
Solar/Wind Harmer
18.228
965461AG1-414 GEN
Solar/Wind Harmer
2.81
970289AG2-191 GEN
Solar/Wind Harmer
2.355
270240V3-007_GEN2
Solar/Wind Harmer
7.662
960681AF2-359 GEN
Solar/Wind Harmer
4.674
274775LINCOLN ;6U
Adder
10.399
274776LINCOLN ;7U
Adder
10.399
274777LINCOLN ;8U
Adder
10.399
274814UNIV PK N;0U
Adder
6.187
274807UNIV PK N;3U
Adder
6.174
274805UNIV PK N;1U
Adder
6.147
274811UNIV PK N;7U
Adder
6.133
972037AH1-567 GEN1
Adder
0.224
972227AH1-698 GEN1
Adder
3.19
274827FISK ;RP
Adder
9.488
274687WILL CNTY;4U
Adder
34.087
274687WILL CNTY;4U
Adder
34.087
274675JOLIET 29;7U
Adder
37.414
274675JOLIET 29;7U
Adder
36.078
274731ELWOOD EC;2P
Adder
20.037
274733ELWOOD EC;3P
Adder
20.037
274735ELWOOD EC;4P
Adder
20.037
274728ELWOOD EC;5P
Adder
20.037
274746AC1-111 G10
Adder
6.792
274744AC1-111 GEN8
Adder
6.792
25196408WSDLE3
Adder
10.661
25196308WSDLE2
Adder
10.568
25196208WSDLE1
Adder
10.541
25196708WSDLE6
Adder
10.515
25196508WSDLE4
Adder
10.25
274823ROCKFORD ;21
Adder
23.331
254304AE2-114 C
Solar/Wind Helper
0.213
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.613
20092526R32
Solar/Wind Helper
1.102
203961AE2-224 GEN
Solar/Wind Helper
2.286
20091526CHSTN_FL
Solar/Wind Helper
0.552
20090526Q36
Solar/Wind Helper
0.989
203993AD2-133_GEN1
Solar/Wind Helper
0.989
203846AF2-130 C
Solar/Wind Helper
0.426
238126S14_GEN_1
Solar/Wind Helper
0.644
941231AE2-117 GEN
Solar/Wind Helper
0.449
203855AF2-088 C
Solar/Wind Helper
0.145
203804AE2-113_GEN
Solar/Wind Helper
1.643
942861AE2-305 GEN
Solar/Wind Harmer
11.65
270224U2-072_GEN2
Solar/Wind Harmer
2.896
270227U2-072_GEN3
Solar/Wind Harmer
2.896
270228U2-072_GEN4
Solar/Wind Harmer
2.896
270231U2-072_GEN5
Solar/Wind Harmer
2.896
970077AG2-063 GEN
Solar/Wind Harmer
7.841
270518AE2-148 GEN
Solar/Wind Harmer
17.081
964601AG1-323 GEN
Solar/Wind Harmer
4.458
964601AG1-323 GEN
Solar/Wind Harmer
2.073
938701AE1-092 GEN
Solar/Wind Harmer
28.718
253378AE2-206_GEN
Solar/Wind Harmer
4.802
276820AF1-078_GEN
Solar/Wind Harmer
2.133
25326509SID D
Adder
1.721
25326109MON D
Adder
1.706
25322209TAIT E
Adder
12.514
25322209TAIT E
Adder
12.233
970611AG2-400 GEN
Solar/Wind Harmer
12.784
253370AE2-315 SEC1
Adder
2.557
944541AF1-119 GEN
Solar/Wind Harmer
5.341
960971AF2-388 GEN
Solar/Wind Harmer
13.939
970321AG2-212 GEN
Solar/Wind Harmer
22.72
942221AE2-234 GEN
Solar/Wind Harmer
0.925
246938BC-WTG3
Solar/Wind Harmer
4.992
246937BC-WTG2
Solar/Wind Harmer
4.907
253394AE2-221_GEN
Solar/Wind Harmer
5.683
253398AE2-221_GEN2
Solar/Wind Harmer
5.683
270599AE1-208 GEN
Solar/Wind Harmer
10.191
270031AE2-169
Solar/Wind Harmer
10.191
270201AC2-176 GEN
Solar/Wind Harmer
6.424
964611AG1-324 GEN
Solar/Wind Harmer
1.472
964611AG1-324 GEN
Solar/Wind Harmer
0.653
247621Y3-024
Adder
0.301
970883AG2-550 GEN
Solar/Wind Harmer
12.452
970885AG2-551 GEN
Solar/Wind Harmer
2.896
970825AG2-519 GEN
Solar/Wind Harmer
13.114
960441AF2-335 GEN
Solar/Wind Harmer
12.423
270383AD1-128 GEN
Solar/Wind Harmer
7.569
24379505HDWTR1G C
Solar/Wind Harmer
9.793
270209AC1-174_GEN
Solar/Wind Harmer
6.911
926881AC1-175 GEN
Solar/Wind Harmer
6.911
965681AG1-436 GEN
Solar/Wind Harmer
15.464
965791AG1-447 GEN
Solar/Wind Harmer
7.912
270216AD2-079_GEN
Solar/Wind Harmer
0.748
253317AC1-085 GEN4
Solar/Wind Harmer
10.337
247620Y3-023
Adder
0.568
274770LINCOLN ;1U
Adder
10.399
274771LINCOLN ;2U
Adder
10.399
274808UNIV PK N;4U
Adder
6.107
972259AH1-714 GEN
Adder
23.335
274803UNIV PARK;6U
Adder
7.13
24728805RICHG1
Adder
4.62
24728905RICHG2
Adder
4.62
274674JOLIET 9 ;6U
Adder
18.77
274696ROCKY RD ;4P
Adder
13.793
274695ROCKY RD ;2P
Adder
13.475
274693ROCKY RD ;1P
Adder
13.342
274697ROCKY RD ;3P
Adder
3.661
274683WAUKEGAN ;8U
Adder
25.476
274683WAUKEGAN ;8U
Adder
21.475
25194408D.CRK1
Adder
9.122
25194508D.CRK3
Adder
1.705
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.575
23585401KL_K28_T16
Solar/Wind Helper
1.173
203955AF1-039 C O1
Solar/Wind Helper
0.348
944781AF1-143 GEN
Solar/Wind Helper
2.322
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.337
20088926STNY CRK
Solar/Wind Helper
0.773
203940AF1-140 C
Solar/Wind Helper
0.375
20088626ARWF_N39
Solar/Wind Helper
1.151
20303426NA_O38_P22
Solar/Wind Helper
0.944
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.453
238120AE2-309 GEN
Solar/Wind Helper
0.403
203952AE2-129 C
Solar/Wind Helper
0.449
203946AE2-131 C
Solar/Wind Helper
0.45
238217AF1-153 C O1
Solar/Wind Helper
0.224
20398826ARMNA MT
Solar/Wind Helper
1.411
270578AF1-285 GEN2
Solar/Wind Harmer
1.771
270391AF1-285 GEN3
Solar/Wind Harmer
1.771
970593AG2-378 GEN
Solar/Wind Harmer
2.904
270462AD2-086
Solar/Wind Harmer
9.839
253343AC1-166 GEN
Solar/Wind Harmer
1.515
253325AC1-069 GEN
Solar/Wind Harmer
1.461
25326309TAIT D
Adder
1.406
960071AF2-298 GEN
Solar/Wind Harmer
6.383
965011AG1-365 GEN
Solar/Wind Harmer
12.784
253370AE2-315 SEC1
Adder
2.557
253371AE2-315 SEC2
Adder
2.418
965651AG1-433 GEN
Solar/Wind Harmer
6.97
970245AG2-165 GEN
Solar/Wind Harmer
22.72
958861AF2-177 GEN
Solar/Wind Harmer
13.896
971995AH1-542 GEN
Solar/Wind Harmer
13.983
945371AF1-202 GEN
Solar/Wind Harmer
8.818
247521TR3_G114
Solar/Wind Harmer
4.233
270246TR4_N_V150
Solar/Wind Harmer
1.071
24721705FLATG2
Adder
25.49
965421AG1-410 GEN
Solar/Wind Harmer
37.691
246936BC-WTG1
Solar/Wind Harmer
4.907
270489AE1-102 GEN1
Solar/Wind Harmer
1.63
247536S-71 GEN
Solar/Wind Harmer
5.049
270005AE1-210 C O1
Solar/Wind Harmer
6.81
965031AG1-367 GEN
Solar/Wind Harmer
12.46
270063AE2-323 C
Solar/Wind Harmer
2.742
24695305TIMB G C
Solar/Wind Harmer
6.843
970825AG2-519 GEN
Solar/Wind Harmer
2.926
270263AC1-001 GEN
Solar/Wind Harmer
1.301
270032AE2-172
Solar/Wind Harmer
5.768
970291AG2-192 GEN
Solar/Wind Harmer
1.611
942081AE2-220 GEN
Solar/Wind Harmer
7.917
270239V3-007_GEN1
Solar/Wind Harmer
2.131
253432AC1-085 GEN2
Solar/Wind Harmer
0.33
24639705ELKHART HY
Adder
0.189
274773LINCOLN ;4U
Adder
10.399
274774LINCOLN ;5U
Adder
10.399
274723RIVER EC ;12
Adder
21.989
274751CRETE EC ;1U
Adder
10.107
274754CRETE EC ;4U
Adder
10.107
274812UNIV PK N;8U
Adder
6.133
274801UNIV PARK;4U
Adder
7.128
274676JOLIET 29;8U
Adder
37.414
274674JOLIET 9 ;6U
Adder
18.77
274732ELWOOD EC;7P
Adder
20.037
274745AC1-111 GEN9
Adder
6.792
274682WAUKEGAN ;7U
Adder
21.737
274828WAUKEGAN ;BP
Adder
13.354
25194608D.CRK4
Adder
1.983
24728605AND G2
Adder
4.594
274822ROCKFORD ;11
Adder
23.501
972235AH1-702 GEN1
Adder
3.016
25196808ZIMRHP
Adder
58.606
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.465
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.036
20089226LOOKOUT
Solar/Wind Helper
0.545
20088826HIGHLAND
Solar/Wind Helper
0.85
20094526CT_V3-030
Solar/Wind Helper
0.448
235054AD2-180 GEN
Solar/Wind Helper
1.575
964201AG1-281 GEN
Solar/Wind Helper
0.458
238117U2-030
Solar/Wind Helper
0.27
235531U2-073 GEN
Solar/Wind Helper
2.559
964391AG1-301 GEN
Solar/Wind Helper
0.448
203954AE2-126 C
Solar/Wind Helper
0.445
23751201ROTHROCK
Solar/Wind Helper
0.656
238206AE2-263_GEN
Solar/Wind Helper
0.861
959471AF2-238 GEN
Solar/Wind Helper
0.441
CBM West 1LTFEXP_CBM-W1->PJM
CBM
156.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.576
MECLTFEXP_MEC->PJM
CLTF
18.96
SIGELTFEXP_SIGE->PJM
CLTF
0.586
LAGNLTFEXP_LAGN->PJM
CLTF
17.971
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.828
TVALTFEXP_TVA->PJM
CLTF
8.763
CPLELTFEXP_CPLE->PJM
CLTF
2.716
CBM West 2LTFEXP_CBM-W2->PJM
CBM
134.362
NYPJM->LTFIMP_NY
CLTF
5.354
LGEELTFEXP_LGEE->PJM
CLTF
7.711
WECLTFEXP_WEC->PJM
CLTF
4.569
AG2-052LTFEXP_AG2-052->PJM
LTF
0.284
AH1-155LTFEXP_AH1-155->PJM
LTF
0.426

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.39 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4986.37
MW Contribution:37.28
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
17.095
270475AD2-096_GEN
50/50
10.077
970153AG2-106 GEN
Solar/Wind Harmer
26.181
961921AG1-034 GEN
Solar/Wind Harmer
20.368
241955AC1-078 GEN
Solar/Wind Harmer
11.182
241974AD2-163_GEN2
Solar/Wind Harmer
2.972
942051AE2-217 GEN
Solar/Wind Harmer
26.62
942871AE2-306 GEN
Solar/Wind Harmer
1.325
270391AF1-285 GEN3
Solar/Wind Harmer
0.679
970605AG2-385 GEN
Solar/Wind Harmer
7.818
270485AE1-090_GEN
Solar/Wind Harmer
0.853
253338AC1-165 GEN
Solar/Wind Harmer
1.51
253333AC1-068 GEN
Solar/Wind Harmer
1.456
960801AF2-371 GEN
Solar/Wind Harmer
3.397
964871AG1-351 GEN
Solar/Wind Harmer
2.345
270273AD2-016 GEN
Solar/Wind Harmer
3.452
944531AF1-118 GEN
Solar/Wind Harmer
45.079
972173AH1-669 GEN
Solar/Wind Harmer
6.423
270043AE2-236 GEN
Solar/Wind Harmer
7.027
959331AF2-224 GEN
Solar/Wind Harmer
12.746
965021AG1-366 GEN
Solar/Wind Harmer
2.964
253303V4-073 C
Solar/Wind Harmer
0.147
253370AE2-315 SEC1
Adder
2.549
253371AE2-315 SEC2
Adder
2.411
970513AG2-328 GEN
Solar/Wind Harmer
22.653
970517AG2-330 GEN
Solar/Wind Harmer
20.546
253415AE1-040 GEN
Solar/Wind Harmer
1.427
970349AG2-230 GEN
Solar/Wind Harmer
18.878
270191TR4_S_V150
Solar/Wind Harmer
3.765
270247TR4_N_V136
Solar/Wind Harmer
1.068
24721905FLATG4
Adder
25.406
971617AH1-308 GEN
Solar/Wind Harmer
7.273
270491AE1-102 GEN2
Solar/Wind Harmer
1.625
962031AG1-047 GEN
Solar/Wind Harmer
3.765
957741AF2-068 GEN
Solar/Wind Harmer
18.686
970031AG2-029 GEN
Solar/Wind Harmer
37.277
958821AF2-173 GEN
Solar/Wind Harmer
17.391
270004AE1-209 GEN
Solar/Wind Harmer
6.789
946031AF1-268 GEN
Solar/Wind Harmer
10.298
253406AD2-031_GEN
Solar/Wind Harmer
1.585
970289AG2-191 GEN
Solar/Wind Harmer
0.948
970291AG2-192 GEN
Solar/Wind Harmer
0.862
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.893
247643Z2-116 C
Solar/Wind Harmer
0.086
274772LINCOLN ;3U
Adder
10.368
274724RIVER EC ;11
Adder
21.668
274752CRETE EC ;2U
Adder
10.077
274753CRETE EC ;3U
Adder
10.077
24642205MAYFLWER
Adder
0.777
274802UNIV PARK;5U
Adder
7.109
972228AH1-698 GEN2
Adder
4.517
274826FISK ;BP
Adder
13.347
274800UNIV PARK;3U
Adder
7.107
972038AH1-567 GEN2
Adder
0.445
274676JOLIET 29;8U
Adder
35.969
274729ELWOOD EC;1P
Adder
19.977
274730ELWOOD EC;6P
Adder
19.977
274734ELWOOD EC;8P
Adder
19.977
274736ELWOOD EC;9P
Adder
19.977
274682WAUKEGAN ;7U
Adder
21.671
25196608WSDLE5
Adder
10.321
25194608D.CRK4
Adder
1.976
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.58
972236AH1-702 GEN2
Adder
2.615
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.213
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.583
202652Y1-033 WT C
Solar/Wind Helper
0.526
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089026BF_G21_K23
Solar/Wind Helper
0.442
23750701CROSSCHOOL
Solar/Wind Helper
1.124
203818AF1-086 GEN
Solar/Wind Helper
1.596
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.641
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.269
238202AE2-262_GEN
Solar/Wind Helper
0.903
253316AC1-085 GEN3
Solar/Wind Harmer
9.261
253433AC1-085 GEN1
Solar/Wind Harmer
5.879
270156DARBY CT1
50/50
13.732
270157DARBY CT2
50/50
13.698
270158DARBY CT3
50/50
13.479
270036AE2-216 BAT
50/50
9.005
962771AG1-126 GEN
Solar/Wind Harmer
60.041
270284AF1-227 GEN1
Solar/Wind Harmer
9.212
270286AF1-227 GEN2
Solar/Wind Harmer
3.408
270287AF1-227 GEN3
Solar/Wind Harmer
3.408
270459AD2-067 GEN
Solar/Wind Harmer
13.375
961821AG1-024 GEN
Solar/Wind Harmer
13.579
270520AE2-214 GEN
Solar/Wind Harmer
9.481
270054AF2-122 C O1
Solar/Wind Harmer
5.069
253383AE2-342_GEN
Solar/Wind Harmer
1.364
241973AD2-163_GEN1
Solar/Wind Harmer
2.972
943861AF1-054 GEN
Solar/Wind Harmer
5.734
943851AF1-053 GEN
Solar/Wind Harmer
2.771
270578AF1-285 GEN2
Solar/Wind Harmer
0.679
945631AF1-228 GEN
Solar/Wind Harmer
6.795
270302AB2-170 GEN
Solar/Wind Harmer
11.795
270317AD1-130_GEN
Solar/Wind Harmer
4.522
241972AD1-140 GEN
Solar/Wind Harmer
6.067
970689AG2-444 GEN
Solar/Wind Harmer
21.887
270432AC2-029 GEN
Solar/Wind Harmer
9.37
270269AC2-059
Solar/Wind Harmer
12.072
24729505KEY G4
Adder
8.327
270071AF1-092 GEN
Solar/Wind Harmer
19.189
253372AE2-315 SEC3
Adder
2.411
253372AE2-315 SEC3
Adder
2.411
958711AF2-162 GEN
Solar/Wind Harmer
1.286
965101AG1-375 GEN
Solar/Wind Harmer
12.675
25306009OHH W.
Adder
3.652
253349AC2-067 GEN
Solar/Wind Harmer
6.31
253400AC2-068 GEN
Solar/Wind Harmer
2.537
945581AF1-223 GEN
Solar/Wind Harmer
5.714
963791AG1-232 GEN
Solar/Wind Harmer
16.994
971347AH1-153 GEN
Solar/Wind Harmer
18.878
965051AG1-369 GEN
Solar/Wind Harmer
6.268
965041AG1-368 GEN
Solar/Wind Harmer
12.515
270024AE2-089 GEN
Solar/Wind Harmer
5.871
957201AF2-014 GEN
Solar/Wind Harmer
5.67
270435AC2-044 GEN
Solar/Wind Harmer
2.5
270340AC2-060 GEN
Solar/Wind Harmer
3.789
961761AG1-017 GEN
Solar/Wind Harmer
0.533
270543AE2-219 C
Solar/Wind Harmer
6.356
971029AG2-637 GEN
Solar/Wind Harmer
18.589
971673AH1-337 GEN
Solar/Wind Harmer
5.698
970115AG2-085 GEN
Solar/Wind Harmer
4.954
270594AE1-207 GEN
Solar/Wind Harmer
18.171
965461AG1-414 GEN
Solar/Wind Harmer
2.801
970289AG2-191 GEN
Solar/Wind Harmer
2.347
270240V3-007_GEN2
Solar/Wind Harmer
7.638
960681AF2-359 GEN
Solar/Wind Harmer
4.66
971771AH1-392 GEN
Solar/Wind Harmer
11.073
274775LINCOLN ;6U
Adder
10.368
274776LINCOLN ;7U
Adder
10.368
274777LINCOLN ;8U
Adder
10.368
274814UNIV PK N;0U
Adder
6.169
274807UNIV PK N;3U
Adder
6.155
274805UNIV PK N;1U
Adder
6.128
274811UNIV PK N;7U
Adder
6.115
972227AH1-698 GEN1
Adder
3.18
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.459
274687WILL CNTY;4U
Adder
33.985
274687WILL CNTY;4U
Adder
33.985
274675JOLIET 29;7U
Adder
37.302
274675JOLIET 29;7U
Adder
35.969
274731ELWOOD EC;2P
Adder
19.977
274733ELWOOD EC;3P
Adder
19.977
274735ELWOOD EC;4P
Adder
19.977
274728ELWOOD EC;5P
Adder
19.977
274746AC1-111 G10
Adder
6.771
274744AC1-111 GEN8
Adder
6.771
25196408WSDLE3
Adder
10.624
25196308WSDLE2
Adder
10.532
25196208WSDLE1
Adder
10.505
25196708WSDLE6
Adder
10.479
25196508WSDLE4
Adder
10.215
274823ROCKFORD ;21
Adder
23.26
254304AE2-114 C
Solar/Wind Helper
0.213
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.611
20092526R32
Solar/Wind Helper
1.1
203961AE2-224 GEN
Solar/Wind Helper
2.28
20091526CHSTN_FL
Solar/Wind Helper
0.551
20090526Q36
Solar/Wind Helper
0.986
203993AD2-133_GEN1
Solar/Wind Helper
0.986
203846AF2-130 C
Solar/Wind Helper
0.426
238126S14_GEN_1
Solar/Wind Helper
0.641
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.145
203804AE2-113_GEN
Solar/Wind Helper
1.64
270119AB2-067 GEN1
50/50
18.405
270120AB2-067 GEN2
50/50
18.405
270160DARBY CT5
50/50
0.736
270161DARBY CT6
50/50
0.726
270466AD2-091
50/50
8.187
270471AD2-092_GEN
Solar/Wind Harmer
6.297
946101AF1-275 GEN
Solar/Wind Harmer
2.366
942861AE2-305 GEN
Solar/Wind Harmer
11.617
270224U2-072_GEN2
Solar/Wind Harmer
2.888
270227U2-072_GEN3
Solar/Wind Harmer
2.888
270228U2-072_GEN4
Solar/Wind Harmer
2.888
270231U2-072_GEN5
Solar/Wind Harmer
2.888
970077AG2-063 GEN
Solar/Wind Harmer
7.818
270518AE2-148 GEN
Solar/Wind Harmer
17.027
964601AG1-323 GEN
Solar/Wind Harmer
4.444
964601AG1-323 GEN
Solar/Wind Harmer
2.067
938701AE1-092 GEN
Solar/Wind Harmer
28.63
253378AE2-206_GEN
Solar/Wind Harmer
4.787
276820AF1-078_GEN
Solar/Wind Harmer
2.127
25326509SID D
Adder
1.715
25326109MON D
Adder
1.7
25322209TAIT E
Adder
12.473
25322209TAIT E
Adder
12.193
970611AG2-400 GEN
Solar/Wind Harmer
12.746
253370AE2-315 SEC1
Adder
2.549
944541AF1-119 GEN
Solar/Wind Harmer
5.325
960971AF2-388 GEN
Solar/Wind Harmer
13.897
970321AG2-212 GEN
Solar/Wind Harmer
22.653
942221AE2-234 GEN
Solar/Wind Harmer
0.922
246938BC-WTG3
Solar/Wind Harmer
4.977
246937BC-WTG2
Solar/Wind Harmer
4.892
253394AE2-221_GEN
Solar/Wind Harmer
5.664
253398AE2-221_GEN2
Solar/Wind Harmer
5.664
270599AE1-208 GEN
Solar/Wind Harmer
10.159
270031AE2-169
Solar/Wind Harmer
10.159
270201AC2-176 GEN
Solar/Wind Harmer
6.404
964611AG1-324 GEN
Solar/Wind Harmer
1.468
964611AG1-324 GEN
Solar/Wind Harmer
0.651
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
12.413
970885AG2-551 GEN
Solar/Wind Harmer
2.887
970825AG2-519 GEN
Solar/Wind Harmer
13.073
960441AF2-335 GEN
Solar/Wind Harmer
12.384
270383AD1-128 GEN
Solar/Wind Harmer
7.545
24379505HDWTR1G C
Solar/Wind Harmer
9.762
270209AC1-174_GEN
Solar/Wind Harmer
6.889
926881AC1-175 GEN
Solar/Wind Harmer
6.889
965681AG1-436 GEN
Solar/Wind Harmer
15.418
965791AG1-447 GEN
Solar/Wind Harmer
7.888
270216AD2-079_GEN
Solar/Wind Harmer
0.746
247620Y3-023
Adder
0.566
274770LINCOLN ;1U
Adder
10.368
274771LINCOLN ;2U
Adder
10.368
274808UNIV PK N;4U
Adder
6.088
972259AH1-714 GEN
Adder
23.265
274803UNIV PARK;6U
Adder
7.109
24728805RICHG1
Adder
4.605
24728905RICHG2
Adder
4.605
274674JOLIET 9 ;6U
Adder
18.713
274696ROCKY RD ;4P
Adder
13.751
274695ROCKY RD ;2P
Adder
13.434
274693ROCKY RD ;1P
Adder
13.302
274697ROCKY RD ;3P
Adder
3.649
274683WAUKEGAN ;8U
Adder
25.399
274683WAUKEGAN ;8U
Adder
21.41
25194408D.CRK1
Adder
9.091
25194508D.CRK3
Adder
1.7
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.569
23585401KL_K28_T16
Solar/Wind Helper
1.169
203955AF1-039 C O1
Solar/Wind Helper
0.347
944781AF1-143 GEN
Solar/Wind Helper
2.315
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.771
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.148
20303426NA_O38_P22
Solar/Wind Helper
0.941
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.448
203946AE2-131 C
Solar/Wind Helper
0.449
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.408
253317AC1-085 GEN4
Solar/Wind Harmer
9.261
270166AC1-044 GEN3
50/50
18.405
270159DARBY CT4
50/50
13.513
962761AG1-125 GEN
Solar/Wind Harmer
60.041
970149AG2-104 GEN
Solar/Wind Harmer
74.151
970155AG2-107 GEN
Solar/Wind Harmer
26.181
270349AD2-093_GEN
Solar/Wind Harmer
6.297
270223U2-072_GEN1
Solar/Wind Harmer
2.888
270578AF1-285 GEN2
Solar/Wind Harmer
1.766
270391AF1-285 GEN3
Solar/Wind Harmer
1.766
970593AG2-378 GEN
Solar/Wind Harmer
2.895
270462AD2-086
Solar/Wind Harmer
9.812
253343AC1-166 GEN
Solar/Wind Harmer
1.51
253325AC1-069 GEN
Solar/Wind Harmer
1.456
25326309TAIT D
Adder
1.402
960071AF2-298 GEN
Solar/Wind Harmer
6.362
965011AG1-365 GEN
Solar/Wind Harmer
12.746
253370AE2-315 SEC1
Adder
2.549
253371AE2-315 SEC2
Adder
2.411
965651AG1-433 GEN
Solar/Wind Harmer
6.949
970245AG2-165 GEN
Solar/Wind Harmer
22.653
958861AF2-177 GEN
Solar/Wind Harmer
13.854
971995AH1-542 GEN
Solar/Wind Harmer
13.936
945371AF1-202 GEN
Solar/Wind Harmer
8.791
247521TR3_G114
Solar/Wind Harmer
4.221
270246TR4_N_V150
Solar/Wind Harmer
1.068
24721705FLATG2
Adder
25.406
965421AG1-410 GEN
Solar/Wind Harmer
37.577
246936BC-WTG1
Solar/Wind Harmer
4.892
270489AE1-102 GEN1
Solar/Wind Harmer
1.625
247536S-71 GEN
Solar/Wind Harmer
5.033
270005AE1-210 C O1
Solar/Wind Harmer
6.789
965031AG1-367 GEN
Solar/Wind Harmer
12.422
270063AE2-323 C
Solar/Wind Harmer
2.733
24695305TIMB G C
Solar/Wind Harmer
6.822
970825AG2-519 GEN
Solar/Wind Harmer
2.917
270263AC1-001 GEN
Solar/Wind Harmer
1.296
270032AE2-172
Solar/Wind Harmer
5.75
970291AG2-192 GEN
Solar/Wind Harmer
1.606
942081AE2-220 GEN
Solar/Wind Harmer
7.893
270239V3-007_GEN1
Solar/Wind Harmer
2.124
24639705ELKHART HY
Adder
0.189
274773LINCOLN ;4U
Adder
10.368
274774LINCOLN ;5U
Adder
10.368
274723RIVER EC ;12
Adder
21.923
274751CRETE EC ;1U
Adder
10.077
274754CRETE EC ;4U
Adder
10.077
274812UNIV PK N;8U
Adder
6.115
274801UNIV PARK;4U
Adder
7.107
274676JOLIET 29;8U
Adder
37.301
274674JOLIET 9 ;6U
Adder
18.713
274732ELWOOD EC;7P
Adder
19.977
274745AC1-111 GEN9
Adder
6.771
274682WAUKEGAN ;7U
Adder
21.671
274828WAUKEGAN ;BP
Adder
13.314
25194608D.CRK4
Adder
1.976
24728605AND G2
Adder
4.58
274822ROCKFORD ;11
Adder
23.43
972235AH1-702 GEN1
Adder
3.007
25196808ZIMRHP
Adder
58.404
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.464
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.029
20089226LOOKOUT
Solar/Wind Helper
0.543
20088826HIGHLAND
Solar/Wind Helper
0.848
20094526CT_V3-030
Solar/Wind Helper
0.447
235054AD2-180 GEN
Solar/Wind Helper
1.569
964201AG1-281 GEN
Solar/Wind Helper
0.457
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.549
964391AG1-301 GEN
Solar/Wind Helper
0.447
203954AE2-126 C
Solar/Wind Helper
0.444
23751201ROTHROCK
Solar/Wind Helper
0.653
238206AE2-263_GEN
Solar/Wind Helper
0.859
253432AC1-085 GEN2
Solar/Wind Harmer
0.296
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.46
MECLTFEXP_MEC->PJM
CLTF
18.901
SIGELTFEXP_SIGE->PJM
CLTF
0.584
LAGNLTFEXP_LAGN->PJM
CLTF
17.912
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.787
TVALTFEXP_TVA->PJM
CLTF
8.734
CPLELTFEXP_CPLE->PJM
CLTF
2.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.928
NYPJM->LTFIMP_NY
CLTF
5.339
LGEELTFEXP_LGEE->PJM
CLTF
7.685
WECLTFEXP_WEC->PJM
CLTF
4.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.425

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.3 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4982.82
MW Contribution:37.23
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
17.076
270475AD2-096_GEN
50/50
10.066
970153AG2-106 GEN
Solar/Wind Harmer
26.156
961921AG1-034 GEN
Solar/Wind Harmer
20.342
241955AC1-078 GEN
Solar/Wind Harmer
11.167
241974AD2-163_GEN2
Solar/Wind Harmer
2.968
942051AE2-217 GEN
Solar/Wind Harmer
26.585
942871AE2-306 GEN
Solar/Wind Harmer
1.323
270391AF1-285 GEN3
Solar/Wind Harmer
0.678
970605AG2-385 GEN
Solar/Wind Harmer
7.807
270485AE1-090_GEN
Solar/Wind Harmer
0.852
253338AC1-165 GEN
Solar/Wind Harmer
1.508
253333AC1-068 GEN
Solar/Wind Harmer
1.454
960801AF2-371 GEN
Solar/Wind Harmer
3.391
964871AG1-351 GEN
Solar/Wind Harmer
2.342
270273AD2-016 GEN
Solar/Wind Harmer
3.447
944531AF1-118 GEN
Solar/Wind Harmer
45.02
270156DARBY CT1
50/50
13.713
270157DARBY CT2
50/50
13.679
270158DARBY CT3
50/50
13.461
270036AE2-216 BAT
50/50
8.994
962771AG1-126 GEN
Solar/Wind Harmer
59.984
270284AF1-227 GEN1
Solar/Wind Harmer
9.201
270286AF1-227 GEN2
Solar/Wind Harmer
3.404
270287AF1-227 GEN3
Solar/Wind Harmer
3.404
270459AD2-067 GEN
Solar/Wind Harmer
13.358
961821AG1-024 GEN
Solar/Wind Harmer
13.561
270520AE2-214 GEN
Solar/Wind Harmer
9.469
270054AF2-122 C O1
Solar/Wind Harmer
5.062
253383AE2-342_GEN
Solar/Wind Harmer
1.362
241973AD2-163_GEN1
Solar/Wind Harmer
2.968
943861AF1-054 GEN
Solar/Wind Harmer
5.727
943851AF1-053 GEN
Solar/Wind Harmer
2.767
270578AF1-285 GEN2
Solar/Wind Harmer
0.678
945631AF1-228 GEN
Solar/Wind Harmer
6.786
270302AB2-170 GEN
Solar/Wind Harmer
11.78
270317AD1-130_GEN
Solar/Wind Harmer
4.516
241972AD1-140 GEN
Solar/Wind Harmer
6.058
970689AG2-444 GEN
Solar/Wind Harmer
21.853
270432AC2-029 GEN
Solar/Wind Harmer
9.355
270269AC2-059
Solar/Wind Harmer
12.053
24729505KEY G4
Adder
8.316
270071AF1-092 GEN
Solar/Wind Harmer
19.164
253372AE2-315 SEC3
Adder
2.407
253372AE2-315 SEC3
Adder
2.407
958711AF2-162 GEN
Solar/Wind Harmer
1.285
965101AG1-375 GEN
Solar/Wind Harmer
12.658
25306009OHH W.
Adder
3.647
253349AC2-067 GEN
Solar/Wind Harmer
6.301
253400AC2-068 GEN
Solar/Wind Harmer
2.534
945581AF1-223 GEN
Solar/Wind Harmer
5.707
963791AG1-232 GEN
Solar/Wind Harmer
16.971
971347AH1-153 GEN
Solar/Wind Harmer
18.853
965051AG1-369 GEN
Solar/Wind Harmer
6.259
965041AG1-368 GEN
Solar/Wind Harmer
12.498
270024AE2-089 GEN
Solar/Wind Harmer
5.863
957201AF2-014 GEN
Solar/Wind Harmer
5.663
270435AC2-044 GEN
Solar/Wind Harmer
2.497
270340AC2-060 GEN
Solar/Wind Harmer
3.783
961761AG1-017 GEN
Solar/Wind Harmer
0.532
270543AE2-219 C
Solar/Wind Harmer
6.347
971029AG2-637 GEN
Solar/Wind Harmer
18.562
971673AH1-337 GEN
Solar/Wind Harmer
5.69
970115AG2-085 GEN
Solar/Wind Harmer
4.947
270594AE1-207 GEN
Solar/Wind Harmer
18.147
965461AG1-414 GEN
Solar/Wind Harmer
2.797
970289AG2-191 GEN
Solar/Wind Harmer
2.344
270240V3-007_GEN2
Solar/Wind Harmer
7.627
960681AF2-359 GEN
Solar/Wind Harmer
4.654
971771AH1-392 GEN
Solar/Wind Harmer
11.059
274775LINCOLN ;6U
Adder
10.354
274776LINCOLN ;7U
Adder
10.354
274777LINCOLN ;8U
Adder
10.354
274814UNIV PK N;0U
Adder
6.16
274807UNIV PK N;3U
Adder
6.147
274805UNIV PK N;1U
Adder
6.12
274811UNIV PK N;7U
Adder
6.107
972227AH1-698 GEN1
Adder
3.176
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.447
274687WILL CNTY;4U
Adder
33.939
274687WILL CNTY;4U
Adder
33.939
274675JOLIET 29;7U
Adder
37.252
274675JOLIET 29;7U
Adder
35.922
274731ELWOOD EC;2P
Adder
19.951
274733ELWOOD EC;3P
Adder
19.951
274735ELWOOD EC;4P
Adder
19.951
274728ELWOOD EC;5P
Adder
19.951
274746AC1-111 G10
Adder
6.762
274744AC1-111 GEN8
Adder
6.762
25196408WSDLE3
Adder
10.608
25196308WSDLE2
Adder
10.516
25196208WSDLE1
Adder
10.49
25196708WSDLE6
Adder
10.463
25196508WSDLE4
Adder
10.2
274823ROCKFORD ;21
Adder
23.229
254304AE2-114 C
Solar/Wind Helper
0.214
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.61
20092526R32
Solar/Wind Helper
1.098
203961AE2-224 GEN
Solar/Wind Helper
2.278
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.985
203993AD2-133_GEN1
Solar/Wind Helper
0.985
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.144
203804AE2-113_GEN
Solar/Wind Helper
1.639
972173AH1-669 GEN
Solar/Wind Harmer
6.413
270043AE2-236 GEN
Solar/Wind Harmer
7.018
959331AF2-224 GEN
Solar/Wind Harmer
12.73
965021AG1-366 GEN
Solar/Wind Harmer
2.96
253303V4-073 C
Solar/Wind Harmer
0.147
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
970513AG2-328 GEN
Solar/Wind Harmer
22.623
970517AG2-330 GEN
Solar/Wind Harmer
20.519
253415AE1-040 GEN
Solar/Wind Harmer
1.424
970349AG2-230 GEN
Solar/Wind Harmer
18.853
270191TR4_S_V150
Solar/Wind Harmer
3.76
270247TR4_N_V136
Solar/Wind Harmer
1.066
24721905FLATG4
Adder
25.369
971617AH1-308 GEN
Solar/Wind Harmer
7.263
270491AE1-102 GEN2
Solar/Wind Harmer
1.623
962031AG1-047 GEN
Solar/Wind Harmer
3.76
957741AF2-068 GEN
Solar/Wind Harmer
18.66
970031AG2-029 GEN
Solar/Wind Harmer
37.228
958821AF2-173 GEN
Solar/Wind Harmer
17.367
270004AE1-209 GEN
Solar/Wind Harmer
6.779
946031AF1-268 GEN
Solar/Wind Harmer
10.283
253406AD2-031_GEN
Solar/Wind Harmer
1.583
970289AG2-191 GEN
Solar/Wind Harmer
0.947
970291AG2-192 GEN
Solar/Wind Harmer
0.861
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.883
247643Z2-116 C
Solar/Wind Harmer
0.086
274772LINCOLN ;3U
Adder
10.354
274724RIVER EC ;11
Adder
21.639
274752CRETE EC ;2U
Adder
10.063
274753CRETE EC ;3U
Adder
10.063
24642205MAYFLWER
Adder
0.776
274802UNIV PARK;5U
Adder
7.1
972228AH1-698 GEN2
Adder
4.511
274826FISK ;BP
Adder
13.329
274800UNIV PARK;3U
Adder
7.097
972038AH1-567 GEN2
Adder
0.444
274676JOLIET 29;8U
Adder
35.922
274729ELWOOD EC;1P
Adder
19.951
274730ELWOOD EC;6P
Adder
19.951
274734ELWOOD EC;8P
Adder
19.951
274736ELWOOD EC;9P
Adder
19.951
274682WAUKEGAN ;7U
Adder
21.642
25196608WSDLE5
Adder
10.305
25194608D.CRK4
Adder
1.973
24728705AND G3
Adder
9.564
24728505AND G1
Adder
4.573
972236AH1-702 GEN2
Adder
2.611
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.214
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.577
202652Y1-033 WT C
Solar/Wind Helper
0.525
20089126CSLMN_L13
Solar/Wind Helper
0.557
20089026BF_G21_K23
Solar/Wind Helper
0.441
23750701CROSSCHOOL
Solar/Wind Helper
1.122
203818AF1-086 GEN
Solar/Wind Helper
1.594
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.64
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.268
238202AE2-262_GEN
Solar/Wind Helper
0.902
253316AC1-085 GEN3
Solar/Wind Harmer
9.247
253433AC1-085 GEN1
Solar/Wind Harmer
5.87
270119AB2-067 GEN1
50/50
18.401
270120AB2-067 GEN2
50/50
18.401
270160DARBY CT5
50/50
0.735
270161DARBY CT6
50/50
0.725
270466AD2-091
50/50
8.176
270471AD2-092_GEN
Solar/Wind Harmer
6.29
946101AF1-275 GEN
Solar/Wind Harmer
2.363
942861AE2-305 GEN
Solar/Wind Harmer
11.602
270224U2-072_GEN2
Solar/Wind Harmer
2.884
270227U2-072_GEN3
Solar/Wind Harmer
2.884
270228U2-072_GEN4
Solar/Wind Harmer
2.884
270231U2-072_GEN5
Solar/Wind Harmer
2.884
970077AG2-063 GEN
Solar/Wind Harmer
7.807
270518AE2-148 GEN
Solar/Wind Harmer
17.003
964601AG1-323 GEN
Solar/Wind Harmer
4.438
964601AG1-323 GEN
Solar/Wind Harmer
2.064
938701AE1-092 GEN
Solar/Wind Harmer
28.592
253378AE2-206_GEN
Solar/Wind Harmer
4.781
276820AF1-078_GEN
Solar/Wind Harmer
2.124
25326509SID D
Adder
1.713
25326109MON D
Adder
1.698
25322209TAIT E
Adder
12.455
25322209TAIT E
Adder
12.175
970611AG2-400 GEN
Solar/Wind Harmer
12.73
253370AE2-315 SEC1
Adder
2.545
944541AF1-119 GEN
Solar/Wind Harmer
5.318
960971AF2-388 GEN
Solar/Wind Harmer
13.879
970321AG2-212 GEN
Solar/Wind Harmer
22.623
942221AE2-234 GEN
Solar/Wind Harmer
0.921
246938BC-WTG3
Solar/Wind Harmer
4.97
246937BC-WTG2
Solar/Wind Harmer
4.886
270599AE1-208 GEN
Solar/Wind Harmer
10.145
270031AE2-169
Solar/Wind Harmer
10.145
253394AE2-221_GEN
Solar/Wind Harmer
5.655
253398AE2-221_GEN2
Solar/Wind Harmer
5.655
270201AC2-176 GEN
Solar/Wind Harmer
6.395
964611AG1-324 GEN
Solar/Wind Harmer
1.466
964611AG1-324 GEN
Solar/Wind Harmer
0.65
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
12.396
970885AG2-551 GEN
Solar/Wind Harmer
2.883
970825AG2-519 GEN
Solar/Wind Harmer
13.055
960441AF2-335 GEN
Solar/Wind Harmer
12.367
270383AD1-128 GEN
Solar/Wind Harmer
7.535
24379505HDWTR1G C
Solar/Wind Harmer
9.748
270209AC1-174_GEN
Solar/Wind Harmer
6.88
926881AC1-175 GEN
Solar/Wind Harmer
6.88
965681AG1-436 GEN
Solar/Wind Harmer
15.398
965791AG1-447 GEN
Solar/Wind Harmer
7.878
270216AD2-079_GEN
Solar/Wind Harmer
0.745
247620Y3-023
Adder
0.565
274770LINCOLN ;1U
Adder
10.354
274771LINCOLN ;2U
Adder
10.354
274808UNIV PK N;4U
Adder
6.08
972259AH1-714 GEN
Adder
23.234
274803UNIV PARK;6U
Adder
7.1
24728805RICHG1
Adder
4.598
24728905RICHG2
Adder
4.598
274674JOLIET 9 ;6U
Adder
18.689
274696ROCKY RD ;4P
Adder
13.733
274695ROCKY RD ;2P
Adder
13.416
274693ROCKY RD ;1P
Adder
13.284
274697ROCKY RD ;3P
Adder
3.645
274683WAUKEGAN ;8U
Adder
25.365
274683WAUKEGAN ;8U
Adder
21.381
25194408D.CRK1
Adder
9.077
25194508D.CRK3
Adder
1.697
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.567
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.346
944781AF1-143 GEN
Solar/Wind Helper
2.312
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.147
20303426NA_O38_P22
Solar/Wind Helper
0.94
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.447
203946AE2-131 C
Solar/Wind Helper
0.448
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.407
253317AC1-085 GEN4
Solar/Wind Harmer
9.247
270166AC1-044 GEN3
50/50
18.401
270159DARBY CT4
50/50
13.494
962761AG1-125 GEN
Solar/Wind Harmer
59.984
970149AG2-104 GEN
Solar/Wind Harmer
74.081
970155AG2-107 GEN
Solar/Wind Harmer
26.156
270349AD2-093_GEN
Solar/Wind Harmer
6.29
270223U2-072_GEN1
Solar/Wind Harmer
2.884
270578AF1-285 GEN2
Solar/Wind Harmer
1.764
270391AF1-285 GEN3
Solar/Wind Harmer
1.764
970593AG2-378 GEN
Solar/Wind Harmer
2.892
270462AD2-086
Solar/Wind Harmer
9.8
253343AC1-166 GEN
Solar/Wind Harmer
1.508
253325AC1-069 GEN
Solar/Wind Harmer
1.454
25326309TAIT D
Adder
1.4
960071AF2-298 GEN
Solar/Wind Harmer
6.353
965011AG1-365 GEN
Solar/Wind Harmer
12.73
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
965651AG1-433 GEN
Solar/Wind Harmer
6.939
970245AG2-165 GEN
Solar/Wind Harmer
22.623
958861AF2-177 GEN
Solar/Wind Harmer
13.835
971995AH1-542 GEN
Solar/Wind Harmer
13.916
945371AF1-202 GEN
Solar/Wind Harmer
8.779
247521TR3_G114
Solar/Wind Harmer
4.215
270246TR4_N_V150
Solar/Wind Harmer
1.066
24721705FLATG2
Adder
25.369
965421AG1-410 GEN
Solar/Wind Harmer
37.527
246936BC-WTG1
Solar/Wind Harmer
4.886
270489AE1-102 GEN1
Solar/Wind Harmer
1.623
247536S-71 GEN
Solar/Wind Harmer
5.026
270005AE1-210 C O1
Solar/Wind Harmer
6.779
965031AG1-367 GEN
Solar/Wind Harmer
12.405
270063AE2-323 C
Solar/Wind Harmer
2.73
24695305TIMB G C
Solar/Wind Harmer
6.813
970825AG2-519 GEN
Solar/Wind Harmer
2.913
270263AC1-001 GEN
Solar/Wind Harmer
1.294
270032AE2-172
Solar/Wind Harmer
5.743
970291AG2-192 GEN
Solar/Wind Harmer
1.604
942081AE2-220 GEN
Solar/Wind Harmer
7.882
270239V3-007_GEN1
Solar/Wind Harmer
2.121
24639705ELKHART HY
Adder
0.188
274773LINCOLN ;4U
Adder
10.354
274774LINCOLN ;5U
Adder
10.354
274723RIVER EC ;12
Adder
21.894
274751CRETE EC ;1U
Adder
10.063
274754CRETE EC ;4U
Adder
10.063
274812UNIV PK N;8U
Adder
6.107
274801UNIV PARK;4U
Adder
7.097
274676JOLIET 29;8U
Adder
37.252
274674JOLIET 9 ;6U
Adder
18.689
274732ELWOOD EC;7P
Adder
19.951
274745AC1-111 GEN9
Adder
6.762
274682WAUKEGAN ;7U
Adder
21.642
274828WAUKEGAN ;BP
Adder
13.296
25194608D.CRK4
Adder
1.973
24728605AND G2
Adder
4.573
274822ROCKFORD ;11
Adder
23.399
972235AH1-702 GEN1
Adder
3.003
25196808ZIMRHP
Adder
58.315
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.463
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.025
20089226LOOKOUT
Solar/Wind Helper
0.542
20088826HIGHLAND
Solar/Wind Helper
0.847
20094526CT_V3-030
Solar/Wind Helper
0.446
235054AD2-180 GEN
Solar/Wind Helper
1.566
964201AG1-281 GEN
Solar/Wind Helper
0.457
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.545
964391AG1-301 GEN
Solar/Wind Helper
0.446
203954AE2-126 C
Solar/Wind Helper
0.443
23751201ROTHROCK
Solar/Wind Helper
0.652
238206AE2-263_GEN
Solar/Wind Helper
0.858
253432AC1-085 GEN2
Solar/Wind Harmer
0.296
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.409
MECLTFEXP_MEC->PJM
CLTF
18.875
SIGELTFEXP_SIGE->PJM
CLTF
0.583
LAGNLTFEXP_LAGN->PJM
CLTF
17.886
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.768
TVALTFEXP_TVA->PJM
CLTF
8.721
CPLELTFEXP_CPLE->PJM
CLTF
2.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.737
NYPJM->LTFIMP_NY
CLTF
5.332
LGEELTFEXP_LGEE->PJM
CLTF
7.674
WECLTFEXP_WEC->PJM
CLTF
4.549
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.424

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.76 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4919.18
MW Contribution:5.63
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
17.076
270475AD2-096_GEN
50/50
10.066
970153AG2-106 GEN
Solar/Wind Harmer
32.303
961921AG1-034 GEN
Solar/Wind Harmer
9.935
241955AC1-078 GEN
Solar/Wind Harmer
0.009
241974AD2-163_GEN2
Solar/Wind Harmer
0.008
942051AE2-217 GEN
Solar/Wind Harmer
18.548
270391AF1-285 GEN3
Solar/Wind Harmer
0.678
970605AG2-385 GEN
Solar/Wind Harmer
6.136
270485AE1-090_GEN
Solar/Wind Harmer
0.001
253338AC1-165 GEN
Solar/Wind Harmer
0.004
253333AC1-068 GEN
Solar/Wind Harmer
0.015
270273AD2-016 GEN
Solar/Wind Harmer
0.935
944531AF1-118 GEN
Solar/Wind Harmer
40.219
972173AH1-669 GEN
Solar/Wind Harmer
4.474
270043AE2-236 GEN
Solar/Wind Harmer
5.712
959331AF2-224 GEN
Solar/Wind Harmer
6.217
965021AG1-366 GEN
Solar/Wind Harmer
2.96
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
970513AG2-328 GEN
Solar/Wind Harmer
3.83
970517AG2-330 GEN
Solar/Wind Harmer
22.981
970191AG2-125 GEN
Solar/Wind Harmer
2.269
253415AE1-040 GEN
Solar/Wind Harmer
0.004
970349AG2-230 GEN
Solar/Wind Harmer
13.153
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.056
24721905FLATG4
Adder
25.369
971617AH1-308 GEN
Solar/Wind Harmer
7.263
270491AE1-102 GEN2
Solar/Wind Harmer
1.132
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.019
970031AG2-029 GEN
Solar/Wind Harmer
5.627
958821AF2-173 GEN
Solar/Wind Harmer
12.116
270004AE1-209 GEN
Solar/Wind Harmer
1.875
946031AF1-268 GEN
Solar/Wind Harmer
8.226
253406AD2-031_GEN
Solar/Wind Harmer
0.643
970289AG2-191 GEN
Solar/Wind Harmer
0.947
970291AG2-192 GEN
Solar/Wind Harmer
0.861
247642Z2-115 C
Solar/Wind Harmer
0.004
270437AC2-090 C
Solar/Wind Harmer
0.004
247643Z2-116 C
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.138
274772LINCOLN ;3U
Adder
10.354
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.32
274724RIVER EC ;11
Adder
21.639
274752CRETE EC ;2U
Adder
10.063
274753CRETE EC ;3U
Adder
10.063
24642205MAYFLWER
Adder
0.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970707AG2-453 GEN
Solar/Wind Harmer
27.781
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276806AD2-047 C O1
Solar/Wind Harmer
4.815
970941AG2-585 GEN
Solar/Wind Harmer
10.621
274802UNIV PARK;5U
Adder
7.1
972228AH1-698 GEN2
Adder
4.511
274826FISK ;BP
Adder
13.329
274800UNIV PARK;3U
Adder
7.097
972038AH1-567 GEN2
Adder
0.444
276897AD1-100 C
Solar/Wind Harmer
0.011
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.882
274676JOLIET 29;8U
Adder
35.922
274729ELWOOD EC;1P
Adder
19.951
274730ELWOOD EC;6P
Adder
19.951
274734ELWOOD EC;8P
Adder
19.951
274736ELWOOD EC;9P
Adder
19.951
276893AG1-478 C
Solar/Wind Harmer
0.336
943121AE2-341 GEN
Solar/Wind Harmer
14.16
943591AF1-030 GEN
Solar/Wind Harmer
9.416
270356AE2-297 GEN
Solar/Wind Harmer
0.011
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.438
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
21.642
25196608WSDLE5
Adder
10.305
270166AC1-044 GEN3
50/50
18.401
270159DARBY CT4
50/50
13.494
962761AG1-125 GEN
Solar/Wind Harmer
50.586
970149AG2-104 GEN
Solar/Wind Harmer
54.635
970155AG2-107 GEN
Solar/Wind Harmer
32.303
270349AD2-093_GEN
Solar/Wind Harmer
0.009
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970593AG2-378 GEN
Solar/Wind Harmer
2.27
270462AD2-086
Solar/Wind Harmer
0.021
253343AC1-166 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.015
25326309TAIT D
Adder
1.4
960071AF2-298 GEN
Solar/Wind Harmer
4.426
965011AG1-365 GEN
Solar/Wind Harmer
8.881
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
965651AG1-433 GEN
Solar/Wind Harmer
2.599
970245AG2-165 GEN
Solar/Wind Harmer
3.83
958861AF2-177 GEN
Solar/Wind Harmer
3.827
971995AH1-542 GEN
Solar/Wind Harmer
3.236
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.319
270246TR4_N_V150
Solar/Wind Harmer
0.056
24721705FLATG2
Adder
25.369
965421AG1-410 GEN
Solar/Wind Harmer
26.181
246936BC-WTG1
Solar/Wind Harmer
0.353
270489AE1-102 GEN1
Solar/Wind Harmer
1.132
247536S-71 GEN
Solar/Wind Harmer
0.349
270005AE1-210 C O1
Solar/Wind Harmer
1.875
965031AG1-367 GEN
Solar/Wind Harmer
8.654
270063AE2-323 C
Solar/Wind Harmer
0.007
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
3.064
270263AC1-001 GEN
Solar/Wind Harmer
0.865
270032AE2-172
Solar/Wind Harmer
5.743
970291AG2-192 GEN
Solar/Wind Harmer
1.119
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.306
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.568
24639705ELKHART HY
Adder
0.188
276903AD2-071 C
Solar/Wind Harmer
9.56
274773LINCOLN ;4U
Adder
10.354
274774LINCOLN ;5U
Adder
10.354
970373AG2-245 GEN
Solar/Wind Harmer
17.958
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274723RIVER EC ;12
Adder
21.894
274751CRETE EC ;1U
Adder
10.063
274754CRETE EC ;4U
Adder
10.063
276164X3-005 C
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.064
274812UNIV PK N;8U
Adder
6.107
276776AD2-060 GEN
Solar/Wind Harmer
0.887
274801UNIV PARK;4U
Adder
7.097
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
15.149
270505AE1-170 C O1
Solar/Wind Harmer
8.915
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274676JOLIET 29;8U
Adder
37.252
274674JOLIET 9 ;6U
Adder
18.689
274732ELWOOD EC;7P
Adder
19.951
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.492
274745AC1-111 GEN9
Adder
6.762
24791305MDL-5G
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.404
939401AE1-172 GEN
Solar/Wind Harmer
6.298
276691AA1-018 GEN1
Solar/Wind Harmer
1.02
274682WAUKEGAN ;7U
Adder
21.642
270119AB2-067 GEN1
50/50
18.401
270120AB2-067 GEN2
50/50
18.401
270160DARBY CT5
50/50
0.735
270161DARBY CT6
50/50
0.725
270466AD2-091
50/50
8.176
270471AD2-092_GEN
Solar/Wind Harmer
0.009
942861AE2-305 GEN
Solar/Wind Harmer
8.094
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
970077AG2-063 GEN
Solar/Wind Harmer
5.8
270518AE2-148 GEN
Solar/Wind Harmer
0.847
964601AG1-323 GEN
Solar/Wind Harmer
3.902
964601AG1-323 GEN
Solar/Wind Harmer
2.601
938701AE1-092 GEN
Solar/Wind Harmer
15.513
971655AH1-328 GEN
Solar/Wind Harmer
3.428
253378AE2-206_GEN
Solar/Wind Harmer
0.005
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
4.005
25326509SID D
Adder
1.713
25326109MON D
Adder
1.698
25322209TAIT E
Adder
12.455
25322209TAIT E
Adder
12.175
970611AG2-400 GEN
Solar/Wind Harmer
8.881
970627AG2-408 GEN
Solar/Wind Harmer
2.664
253370AE2-315 SEC1
Adder
2.545
944541AF1-119 GEN
Solar/Wind Harmer
0.594
960971AF2-388 GEN
Solar/Wind Harmer
5.197
970321AG2-212 GEN
Solar/Wind Harmer
3.83
942221AE2-234 GEN
Solar/Wind Harmer
0.044
246938BC-WTG3
Solar/Wind Harmer
0.316
246937BC-WTG2
Solar/Wind Harmer
0.353
270599AE1-208 GEN
Solar/Wind Harmer
7.961
270031AE2-169
Solar/Wind Harmer
4.777
253394AE2-221_GEN
Solar/Wind Harmer
0.011
253398AE2-221_GEN2
Solar/Wind Harmer
0.011
270201AC2-176 GEN
Solar/Wind Harmer
0.002
964611AG1-324 GEN
Solar/Wind Harmer
0.65
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
8.648
970885AG2-551 GEN
Solar/Wind Harmer
2.883
970825AG2-519 GEN
Solar/Wind Harmer
9.566
960441AF2-335 GEN
Solar/Wind Harmer
8.628
971613AH1-306 GEN
Solar/Wind Harmer
4.135
270383AD1-128 GEN
Solar/Wind Harmer
0.005
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
10.743
965791AG1-447 GEN
Solar/Wind Harmer
7.878
270216AD2-079_GEN
Solar/Wind Harmer
0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
247620Y3-023
Adder
0.565
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
10.354
274771LINCOLN ;2U
Adder
10.354
270007AE1-245 C
Solar/Wind Harmer
0.002
274808UNIV PK N;4U
Adder
6.08
274888KELLY CRK;1U
Solar/Wind Harmer
0.499
274887GEN-1.85
Solar/Wind Harmer
0.224
276843GEN-1.7
Solar/Wind Harmer
0.275
972259AH1-714 GEN
Adder
23.234
958011AF2-095 GEN
Solar/Wind Harmer
12.235
274803UNIV PARK;6U
Adder
7.1
957891AF2-083 GEN
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
4.598
24728905RICHG2
Adder
4.598
274674JOLIET 9 ;6U
Adder
18.689
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
961051AF2-396 GEN
Solar/Wind Harmer
16.913
961051AF2-396 GEN
Solar/Wind Harmer
11.276
971573AH1-285 GEN
Solar/Wind Harmer
1.571
958481AF2-142 GEN
Solar/Wind Harmer
12.626
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.139
274696ROCKY RD ;4P
Adder
13.733
274695ROCKY RD ;2P
Adder
13.416
274693ROCKY RD ;1P
Adder
13.284
274697ROCKY RD ;3P
Adder
3.645
274683WAUKEGAN ;8U
Adder
25.365
274683WAUKEGAN ;8U
Adder
21.381
25183208HLCRTG
Solar/Wind Harmer
0.013
958491AF2-143 GEN
Solar/Wind Harmer
12.583
962691AG1-118 GEN
Solar/Wind Harmer
25.162
966841AG1-555 GEN
Solar/Wind Harmer
0.948
970921AG2-575 GEN
Solar/Wind Harmer
8.38
970921AG2-575 GEN
Solar/Wind Harmer
2.793
274879MINONK ;1U
Solar/Wind Harmer
0.353
25194408D.CRK1
Adder
9.077
25194508D.CRK3
Adder
1.697
252519AF1-045_GEN
Solar/Wind Harmer
7.283
252516AE2-318_GEN
Solar/Wind Harmer
6.46
270156DARBY CT1
50/50
13.713
270157DARBY CT2
50/50
13.679
270158DARBY CT3
50/50
13.461
270036AE2-216 BAT
50/50
8.994
962771AG1-126 GEN
Solar/Wind Harmer
50.586
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
6.623
270520AE2-214 GEN
Solar/Wind Harmer
0.017
270054AF2-122 C O1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.004
241973AD2-163_GEN1
Solar/Wind Harmer
0.008
943861AF1-054 GEN
Solar/Wind Harmer
3.995
943851AF1-053 GEN
Solar/Wind Harmer
2.767
270578AF1-285 GEN2
Solar/Wind Harmer
0.678
945631AF1-228 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.014
971653AH1-327 GEN
Solar/Wind Harmer
1.38
241972AD1-140 GEN
Solar/Wind Harmer
1.032
970689AG2-444 GEN
Solar/Wind Harmer
19.097
270432AC2-029 GEN
Solar/Wind Harmer
4.134
270269AC2-059
Solar/Wind Harmer
0.005
24729505KEY G4
Adder
8.316
270071AF1-092 GEN
Solar/Wind Harmer
17.084
253372AE2-315 SEC3
Adder
2.407
253372AE2-315 SEC3
Adder
2.407
965101AG1-375 GEN
Solar/Wind Harmer
8.831
25306009OHH W.
Adder
3.647
253349AC2-067 GEN
Solar/Wind Harmer
2.778
253400AC2-068 GEN
Solar/Wind Harmer
1.117
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
11.841
971347AH1-153 GEN
Solar/Wind Harmer
13.153
965051AG1-369 GEN
Solar/Wind Harmer
4.367
965041AG1-368 GEN
Solar/Wind Harmer
8.719
276805AD2-038 GEN
Solar/Wind Harmer
0.002
25194608D.CRK4
Adder
1.973
274872LEEDK;1U
Solar/Wind Harmer
0.307
252510AF1-249 C
Solar/Wind Harmer
0.065
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.891
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.306
274850MENDOTA H;RU
Solar/Wind Harmer
0.098
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.15
959091AF2-200 GEN
Solar/Wind Harmer
16.66
24441205WTRV SLR C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
16.64
24728705AND G3
Adder
9.564
24728505AND G1
Adder
4.573
270258AD1-119 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
2.611
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.214
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.577
202652Y1-033 WT C
Solar/Wind Helper
0.525
20089126CSLMN_L13
Solar/Wind Helper
0.557
20089026BF_G21_K23
Solar/Wind Helper
0.441
23750701CROSSCHOOL
Solar/Wind Helper
1.122
203818AF1-086 GEN
Solar/Wind Helper
1.594
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.64
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.268
238202AE2-262_GEN
Solar/Wind Helper
0.902
274828WAUKEGAN ;BP
Adder
13.296
276901AD2-066 C O1
Solar/Wind Harmer
0.008
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
962781AG1-127 GEN
Solar/Wind Harmer
7.975
971997AH1-543 GEN
Solar/Wind Harmer
4.396
25194608D.CRK4
Adder
1.973
274872LEEDK;1U
Solar/Wind Harmer
0.005
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.15
957471AF2-041 GEN
Solar/Wind Harmer
24.989
959081AF2-199 GEN
Solar/Wind Harmer
8.33
971067AG2-660 GEN
Solar/Wind Harmer
2.777
970569AG2-363 GEN
Solar/Wind Harmer
24.96
24728605AND G2
Adder
4.573
274822ROCKFORD ;11
Adder
23.399
972235AH1-702 GEN1
Adder
3.003
963741AG1-226 GEN
Solar/Wind Harmer
19.652
25196808ZIMRHP
Adder
58.315
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.463
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.025
20089226LOOKOUT
Solar/Wind Helper
0.542
20088826HIGHLAND
Solar/Wind Helper
0.847
20094526CT_V3-030
Solar/Wind Helper
0.446
235054AD2-180 GEN
Solar/Wind Helper
1.566
964201AG1-281 GEN
Solar/Wind Helper
0.457
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.545
964391AG1-301 GEN
Solar/Wind Helper
0.446
203954AE2-126 C
Solar/Wind Helper
0.443
23751201ROTHROCK
Solar/Wind Helper
0.652
238206AE2-263_GEN
Solar/Wind Helper
0.858
970819AG2-516 GEN
Solar/Wind Harmer
7.858
270024AE2-089 GEN
Solar/Wind Harmer
0.009
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.103
270340AC2-060 GEN
Solar/Wind Harmer
0.01
971609AH1-304 GEN
Solar/Wind Harmer
1.419
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
12.951
971673AH1-337 GEN
Solar/Wind Harmer
5.609
970115AG2-085 GEN
Solar/Wind Harmer
3.451
270594AE1-207 GEN
Solar/Wind Harmer
9.648
970289AG2-191 GEN
Solar/Wind Harmer
1.635
270240V3-007_GEN2
Solar/Wind Harmer
0.003
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.573
971769AH1-391 GEN
Solar/Wind Harmer
9.561
274775LINCOLN ;6U
Adder
10.354
274776LINCOLN ;7U
Adder
10.354
274777LINCOLN ;8U
Adder
10.354
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
247607V1-011 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
6.16
274807UNIV PK N;3U
Adder
6.147
274805UNIV PK N;1U
Adder
6.12
274811UNIV PK N;7U
Adder
6.107
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
8.497
972227AH1-698 GEN1
Adder
3.176
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.447
971619AH1-309 GEN
Solar/Wind Harmer
3.821
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274687WILL CNTY;4U
Adder
33.939
274687WILL CNTY;4U
Adder
33.939
274675JOLIET 29;7U
Adder
37.252
274675JOLIET 29;7U
Adder
35.922
274731ELWOOD EC;2P
Adder
19.951
274733ELWOOD EC;3P
Adder
19.951
274735ELWOOD EC;4P
Adder
19.951
274728ELWOOD EC;5P
Adder
19.951
970833AG2-524 GEN
Solar/Wind Harmer
9.313
970833AG2-524 GEN
Solar/Wind Harmer
6.209
274746AC1-111 G10
Adder
6.762
274744AC1-111 GEN8
Adder
6.762
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.608
25196308WSDLE2
Adder
10.516
25196208WSDLE1
Adder
10.49
25196708WSDLE6
Adder
10.463
25196508WSDLE4
Adder
10.2
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.681
276882AE2-255 GEN
Solar/Wind Harmer
0.979
970169AG2-114 GEN
Solar/Wind Harmer
8.358
971177AH1-047 GEN
Solar/Wind Harmer
5.154
971675AH1-338 GEN
Solar/Wind Harmer
3.256
971411AH1-196 GEN
Solar/Wind Harmer
12.519
963841AG1-237 GEN
Solar/Wind Harmer
3.615
971171AH1-044 GEN
Solar/Wind Harmer
16.66
926823AC1-168 GEN
Solar/Wind Harmer
1.415
274823ROCKFORD ;21
Adder
23.229
254304AE2-114 C
Solar/Wind Helper
0.214
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.61
20092526R32
Solar/Wind Helper
1.098
203961AE2-224 GEN
Solar/Wind Helper
2.278
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.985
203993AD2-133_GEN1
Solar/Wind Helper
0.985
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.144
203804AE2-113_GEN
Solar/Wind Helper
1.639
942991AE2-321 GEN
Solar/Wind Harmer
9.334
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
16.689
971335AH1-147 GEN
Solar/Wind Harmer
16.689
971341AH1-150 GEN
Solar/Wind Harmer
16.66
971343AH1-151 GEN
Solar/Wind Harmer
16.66
970623AG2-406 GEN
Solar/Wind Harmer
1.522
970241AG2-163 GEN
Solar/Wind Harmer
4.844
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.567
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.346
944781AF1-143 GEN
Solar/Wind Helper
2.312
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.147
20303426NA_O38_P22
Solar/Wind Helper
0.94
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.447
203946AE2-131 C
Solar/Wind Helper
0.448
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.407
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.409
MECLTFEXP_MEC->PJM
CLTF
18.875
SIGELTFEXP_SIGE->PJM
CLTF
0.583
LAGNLTFEXP_LAGN->PJM
CLTF
17.886
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.768
TVALTFEXP_TVA->PJM
CLTF
8.721
CPLELTFEXP_CPLE->PJM
CLTF
2.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.737
NYPJM->LTFIMP_NY
CLTF
5.332
LGEELTFEXP_LGEE->PJM
CLTF
7.674
WECLTFEXP_WEC->PJM
CLTF
4.549
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.424

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.07 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2966.33
MW Contribution:35.52
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
44.998
24727105RPMNG2
50/50
3.288
970583AG2-370 GEN
50/50
2.743
270491AE1-102 GEN2
Solar/Wind Harmer
5.296
959331AF2-224 GEN
Solar/Wind Harmer
19.471
965021AG1-366 GEN
Solar/Wind Harmer
4.528
970031AG2-029 GEN
Solar/Wind Harmer
35.525
270043AE2-236 GEN
Solar/Wind Harmer
6.267
270191TR4_S_V150
Solar/Wind Harmer
3.002
270247TR4_N_V136
Solar/Wind Harmer
0.851
944531AF1-118 GEN
Solar/Wind Harmer
34.594
971617AH1-308 GEN
Solar/Wind Harmer
5.041
247643Z2-116 C
Solar/Wind Harmer
0.06
945111AF1-176 GEN
Solar/Wind Harmer
4.703
970349AG2-230 GEN
Solar/Wind Harmer
12.208
24642205MAYFLWER
Adder
0.513
24441205WTRV SLR C
Solar/Wind Harmer
0.102
970513AG2-328 GEN
Solar/Wind Harmer
13.375
970517AG2-330 GEN
Solar/Wind Harmer
12.131
972231SS25-0005
Solar/Wind Harmer
7.052
972181SS23-001
Solar/Wind Harmer
4.407
274752CRETE EC ;2U
Adder
3.632
274753CRETE EC ;3U
Adder
3.632
274724RIVER EC ;11
Adder
13.111
270535AF1-215 GEN1
Solar/Wind Harmer
3.333
247604X1-042
Adder
0.305
274772LINCOLN ;3U
Adder
4.536
274802UNIV PARK;5U
Adder
4.238
274826FISK ;BP
Adder
7.95
274800UNIV PARK;3U
Adder
4.226
972038AH1-567 GEN2
Adder
0.265
276772AC2-154 GEN
Solar/Wind Harmer
2.019
276806AD2-047 C O1
Solar/Wind Harmer
7.744
970941AG2-585 GEN
Solar/Wind Harmer
9.049
964401AG1-302 GEN
Solar/Wind Harmer
6.555
972228AH1-698 GEN2
Adder
2.674
970707AG2-453 GEN
Solar/Wind Harmer
20.145
276897AD1-100 C
Solar/Wind Harmer
20.799
939351AE1-166 GEN
Solar/Wind Harmer
4.25
274676JOLIET 29;8U
Adder
21.198
276893AG1-478 C
Solar/Wind Harmer
0.299
274730ELWOOD EC;6P
Adder
11.747
274734ELWOOD EC;8P
Adder
11.747
274736ELWOOD EC;9P
Adder
11.747
274729ELWOOD EC;1P
Adder
11.747
959141AF2-205 GEN
Solar/Wind Harmer
4.309
943121AE2-341 GEN
Solar/Wind Harmer
10.596
943591AF1-030 GEN
Solar/Wind Harmer
7.064
247642Z2-115 C
Solar/Wind Harmer
0.045
276694AA1-018 GEN2
Solar/Wind Harmer
4.428
274682WAUKEGAN ;7U
Adder
12.546
970289AG2-191 GEN
Solar/Wind Harmer
0.534
970291AG2-192 GEN
Solar/Wind Harmer
0.485
276805AD2-038 GEN
Solar/Wind Harmer
3.555
958821AF2-173 GEN
Solar/Wind Harmer
9.658
270004AE1-209 GEN
Solar/Wind Harmer
3.77
274872LEEDK;1U
Solar/Wind Harmer
0.176
972236AH1-702 GEN2
Adder
1.48
274760LEE CO EC;1U
Adder
6.19
274767LEE CO EC;8U
Adder
6.117
24728705AND G3
Adder
4.167
24728505AND G1
Adder
1.992
270485AE1-090_GEN
Solar/Wind Helper
0.34
942871AE2-306 GEN
Solar/Wind Helper
0.47
270541AE2-072 C
Solar/Wind Helper
1.006
24727005RPMNG1
50/50
3.277
960861AF2-377 GEN
50/50
2.329
970521AG2-332 GEN
50/50
10.591
24639705ELKHART HY
50/50
0.146
246936BC-WTG1
Solar/Wind Harmer
15.94
270489AE1-102 GEN1
Solar/Wind Harmer
5.296
965421AG1-410 GEN
Solar/Wind Harmer
116.095
965011AG1-365 GEN
Solar/Wind Harmer
19.471
270063AE2-323 C
Solar/Wind Harmer
2.3
247521TR3_G114
Solar/Wind Harmer
3.365
270246TR4_N_V150
Solar/Wind Harmer
0.851
944231AF1-091 GEN
Solar/Wind Harmer
3.659
965651AG1-433 GEN
Solar/Wind Harmer
4.814
24695305TIMB G C
Solar/Wind Harmer
4.813
958861AF2-177 GEN
Solar/Wind Harmer
9.344
945111AF1-176 GEN
Solar/Wind Harmer
14.839
270505AE1-170 C O1
Solar/Wind Harmer
12.162
945371AF1-202 GEN
Solar/Wind Harmer
5.62
270449AD2-020 GEN
Solar/Wind Harmer
2.235
943021AE2-325 GEN
Solar/Wind Harmer
2.904
970245AG2-165 GEN
Solar/Wind Harmer
13.375
970373AG2-245 GEN
Solar/Wind Harmer
15.666
274751CRETE EC ;1U
Adder
3.632
274754CRETE EC ;4U
Adder
3.632
274723RIVER EC ;12
Adder
13.271
274812UNIV PK N;8U
Adder
3.679
276164X3-005 C
Solar/Wind Harmer
0.516
270055AF2-134 C O1
Solar/Wind Harmer
2.222
972207SS24-0001
Solar/Wind Harmer
16.127
274773LINCOLN ;4U
Adder
4.536
274774LINCOLN ;5U
Adder
4.536
274801UNIV PARK;4U
Adder
4.226
276776AD2-060 GEN
Solar/Wind Harmer
0.306
958381AF2-132 GEN
Solar/Wind Harmer
6.555
964861AG1-349 GEN
Solar/Wind Harmer
5.671
971917AH1-482 GEN
Solar/Wind Harmer
6.544
941551AE2-152 GEN
Solar/Wind Harmer
3.25
274676JOLIET 29;8U
Adder
21.983
274674JOLIET 9 ;6U
Adder
11.008
274732ELWOOD EC;7P
Adder
11.747
274871GR RIDGE ;2U
Solar/Wind Harmer
5.466
940581AE2-045 GEN
Solar/Wind Harmer
7.216
971605AH1-302 GEN
Solar/Wind Harmer
6.17
274745AC1-111 GEN9
Adder
3.947
276691AA1-018 GEN1
Solar/Wind Harmer
0.327
274682WAUKEGAN ;7U
Adder
12.546
274828WAUKEGAN ;BP
Adder
7.701
970291AG2-192 GEN
Solar/Wind Harmer
0.904
960751AF2-366 GEN
Solar/Wind Harmer
1.983
962781AG1-127 GEN
Solar/Wind Harmer
6.574
939401AE1-172 GEN
Solar/Wind Harmer
9.628
276901AD2-066 C O1
Solar/Wind Harmer
2.426
270005AE1-210 C O1
Solar/Wind Harmer
3.77
965031AG1-367 GEN
Solar/Wind Harmer
6.899
274872LEEDK;1U
Solar/Wind Harmer
5.665
274822ROCKFORD ;11
Adder
13.287
972235AH1-702 GEN1
Adder
1.702
274761LEE CO EC;2U
Adder
6.19
274766LEE CO EC;7U
Adder
6.117
24728605AND G2
Adder
1.992
270462AD2-086
Solar/Wind Helper
3.909
270223U2-072_GEN1
Solar/Wind Helper
0.925
270578AF1-285 GEN2
Solar/Wind Helper
0.627
270391AF1-285 GEN3
Solar/Wind Helper
0.627
247522W1-056 GEN
Solar/Wind Helper
1.229
960841AF2-375 GEN
Solar/Wind Helper
1.241
270349AD2-093_GEN
Solar/Wind Helper
0.994
270032AE2-172
Solar/Wind Harmer
1.324
970615AG2-402 GEN
50/50
4.528
24729405KEY G3
50/50
0.361
24729305KEY G2
50/50
0.355
24729205KEY G1
50/50
0.353
247620Y3-023
50/50
0.454
246938BC-WTG3
Solar/Wind Harmer
16.215
246937BC-WTG2
Solar/Wind Harmer
15.94
970611AG2-400 GEN
Solar/Wind Harmer
19.471
942221AE2-234 GEN
Solar/Wind Harmer
0.699
944541AF1-119 GEN
Solar/Wind Harmer
3.689
960971AF2-388 GEN
Solar/Wind Harmer
9.627
270216AD2-079_GEN
Solar/Wind Harmer
0.524
960981AF2-389 GEN
Solar/Wind Harmer
1.236
957891AF2-083 GEN
Solar/Wind Harmer
2.755
961051AF2-396 GEN
Solar/Wind Harmer
12.861
961051AF2-396 GEN
Solar/Wind Harmer
5.982
270526AF1-158 GEN
Solar/Wind Harmer
3.617
24441505OLIV SLR
Solar/Wind Harmer
0.106
965681AG1-436 GEN
Solar/Wind Harmer
9.675
965791AG1-447 GEN
Solar/Wind Harmer
4.95
270599AE1-208 GEN
Solar/Wind Harmer
6.221
270031AE2-169
Solar/Wind Harmer
6.221
970321AG2-212 GEN
Solar/Wind Harmer
13.375
274808UNIV PK N;4U
Adder
3.663
274770LINCOLN ;1U
Adder
4.536
274771LINCOLN ;2U
Adder
4.536
274803UNIV PARK;6U
Adder
4.238
274888KELLY CRK;1U
Solar/Wind Harmer
4.274
274887GEN-1.85
Solar/Wind Harmer
3.859
276843GEN-1.7
Solar/Wind Harmer
0.415
958011AF2-095 GEN
Solar/Wind Harmer
10.425
972259AH1-714 GEN
Adder
13.729
274674JOLIET 9 ;6U
Adder
11.008
274847GR RIDGE ;BU
Solar/Wind Harmer
3.596
971573AH1-285 GEN
Solar/Wind Harmer
6.043
958481AF2-142 GEN
Solar/Wind Harmer
10.525
274861TOP CROP ;1U
Solar/Wind Harmer
4.25
274862TOP CROP ;2U
Solar/Wind Harmer
3.549
274696ROCKY RD ;4P
Adder
7.96
274695ROCKY RD ;2P
Adder
7.776
274693ROCKY RD ;1P
Adder
7.7
274697ROCKY RD ;3P
Adder
2.112
274683WAUKEGAN ;8U
Adder
14.692
274683WAUKEGAN ;8U
Adder
12.385
945421AF1-207 GEN
Solar/Wind Harmer
9.735
957841AF2-078 GEN
Solar/Wind Harmer
4.189
962691AG1-118 GEN
Solar/Wind Harmer
20.79
958491AF2-143 GEN
Solar/Wind Harmer
10.394
970921AG2-575 GEN
Solar/Wind Harmer
6.913
970921AG2-575 GEN
Solar/Wind Harmer
1.608
274879MINONK ;1U
Solar/Wind Harmer
4.647
274764LEE CO EC;5U
Adder
6.205
274765LEE CO EC;6U
Adder
6.205
274762LEE CO EC;3U
Adder
6.19
274763LEE CO EC;4U
Adder
6.132
972267AH1-718 GEN
Adder
2.743
247621Y3-024
Adder
0.155
270224U2-072_GEN2
Solar/Wind Helper
0.925
270227U2-072_GEN3
Solar/Wind Helper
0.925
270228U2-072_GEN4
Solar/Wind Helper
0.925
270231U2-072_GEN5
Solar/Wind Helper
0.925
270471AD2-092_GEN
Solar/Wind Helper
0.994
253378AE2-206_GEN
Solar/Wind Helper
0.741
276820AF1-078_GEN
Solar/Wind Helper
0.346
241960AC2-195 GEN
Solar/Wind Helper
0.775
24727205RPMNG3
50/50
3.261
971599AH1-298 GEN
50/50
10.16
24729505KEY G4
50/50
6.608
24653605MOTTVILLE
50/50
0.003
957201AF2-014 GEN
Solar/Wind Harmer
18.475
270435AC2-044 GEN
Solar/Wind Harmer
8.147
963791AG1-232 GEN
Solar/Wind Harmer
16.319
965041AG1-368 GEN
Solar/Wind Harmer
11.796
270071AF1-092 GEN
Solar/Wind Harmer
15.874
965051AG1-369 GEN
Solar/Wind Harmer
4.998
958711AF2-162 GEN
Solar/Wind Harmer
0.891
270024AE2-089 GEN
Solar/Wind Harmer
4.069
965101AG1-375 GEN
Solar/Wind Harmer
8.549
971771AH1-392 GEN
Solar/Wind Harmer
7.388
971347AH1-153 GEN
Solar/Wind Harmer
12.208
945581AF1-223 GEN
Solar/Wind Harmer
3.653
971769AH1-391 GEN
Solar/Wind Harmer
7.899
944161AF1-084 GEN
Solar/Wind Harmer
1.735
960681AF2-359 GEN
Solar/Wind Harmer
2.924
274814UNIV PK N;0U
Adder
3.711
274807UNIV PK N;3U
Adder
3.703
274805UNIV PK N;1U
Adder
3.687
274811UNIV PK N;7U
Adder
3.679
270536AF1-215 GEN2
Solar/Wind Harmer
3.333
274775LINCOLN ;6U
Adder
4.536
274776LINCOLN ;7U
Adder
4.536
274777LINCOLN ;8U
Adder
4.536
972037AH1-567 GEN1
Adder
0.133
274827FISK ;RP
Adder
5.634
960591AF2-350 GEN
Solar/Wind Harmer
7.239
972227AH1-698 GEN1
Adder
1.883
274687WILL CNTY;4U
Adder
20.065
274687WILL CNTY;4U
Adder
20.065
958391AF2-133 GEN
Solar/Wind Harmer
6.504
274675JOLIET 29;7U
Adder
21.983
274675JOLIET 29;7U
Adder
21.198
274728ELWOOD EC;5P
Adder
11.747
274731ELWOOD EC;2P
Adder
11.747
274733ELWOOD EC;3P
Adder
11.747
274735ELWOOD EC;4P
Adder
11.747
970833AG2-524 GEN
Solar/Wind Harmer
6.21
970833AG2-524 GEN
Solar/Wind Harmer
2.889
274746AC1-111 G10
Adder
3.947
274744AC1-111 GEN8
Adder
3.947
965461AG1-414 GEN
Solar/Wind Harmer
1.577
970289AG2-191 GEN
Solar/Wind Harmer
1.321
276868AE1-113 GEN
Solar/Wind Harmer
6.97
276882AE2-255 GEN
Solar/Wind Harmer
2.324
274823ROCKFORD ;21
Adder
13.19
270317AD1-130_GEN
Solar/Wind Helper
4.329
966831AG1-554 GEN
Solar/Wind Helper
0.92
270284AF1-227 GEN1
Solar/Wind Helper
2.08
270286AF1-227 GEN2
Solar/Wind Helper
0.763
270287AF1-227 GEN3
Solar/Wind Helper
0.763
270499AE1-146 GEN
Solar/Wind Helper
2.06
945641AF1-229 GEN
Solar/Wind Helper
1.001
253383AE2-342_GEN
Solar/Wind Helper
0.367
270594AE1-207 GEN
Solar/Wind Harmer
4.183
944201AF1-088_MTX
Adder
54.272
957141AF2-008_MTX
Adder
27.136
990497J1323
External Queue
1.5705512762069702
CBM West 1LTFEXP_CBM-W1->PJM
CBM
67.038
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.752
MECLTFEXP_MEC->PJM
CLTF
9.498
SIGELTFEXP_SIGE->PJM
CLTF
0.193
LAGNLTFEXP_LAGN->PJM
CLTF
5.691
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.698
TVALTFEXP_TVA->PJM
CLTF
2.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.402
NYPJM->LTFIMP_NY
CLTF
1.33
LGEELTFEXP_LGEE->PJM
CLTF
1.732
WECLTFEXP_WEC->PJM
CLTF
2.577
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.001
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.1 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2877.11
MW Contribution:35.91
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
3.285
971599AH1-298 GEN
50/50
10.265
24729505KEY G4
50/50
6.681
957201AF2-014 GEN
Solar/Wind Harmer
18.604
270435AC2-044 GEN
Solar/Wind Harmer
8.204
963791AG1-232 GEN
Solar/Wind Harmer
16.53
965041AG1-368 GEN
Solar/Wind Harmer
12
270071AF1-092 GEN
Solar/Wind Harmer
16.035
965051AG1-369 GEN
Solar/Wind Harmer
5.109
958711AF2-162 GEN
Solar/Wind Harmer
0.901
270024AE2-089 GEN
Solar/Wind Harmer
4.134
965101AG1-375 GEN
Solar/Wind Harmer
8.649
971771AH1-392 GEN
Solar/Wind Harmer
7.473
971347AH1-153 GEN
Solar/Wind Harmer
12.336
945581AF1-223 GEN
Solar/Wind Harmer
3.697
971769AH1-391 GEN
Solar/Wind Harmer
7.986
944161AF1-084 GEN
Solar/Wind Harmer
1.758
960681AF2-359 GEN
Solar/Wind Harmer
2.954
274814UNIV PK N;0U
Adder
3.743
274807UNIV PK N;3U
Adder
3.735
274805UNIV PK N;1U
Adder
3.719
274811UNIV PK N;7U
Adder
3.711
270536AF1-215 GEN2
Solar/Wind Harmer
3.363
274775LINCOLN ;6U
Adder
4.574
274776LINCOLN ;7U
Adder
4.574
274777LINCOLN ;8U
Adder
4.574
972037AH1-567 GEN1
Adder
0.134
274827FISK ;RP
Adder
5.682
960591AF2-350 GEN
Solar/Wind Harmer
7.3
972227AH1-698 GEN1
Adder
1.898
274687WILL CNTY;4U
Adder
20.23
274687WILL CNTY;4U
Adder
20.23
958391AF2-133 GEN
Solar/Wind Harmer
6.559
274675JOLIET 29;7U
Adder
22.163
274675JOLIET 29;7U
Adder
21.371
274731ELWOOD EC;2P
Adder
11.842
274733ELWOOD EC;3P
Adder
11.842
274735ELWOOD EC;4P
Adder
11.842
274728ELWOOD EC;5P
Adder
11.843
970833AG2-524 GEN
Solar/Wind Harmer
6.26
970833AG2-524 GEN
Solar/Wind Harmer
2.912
274746AC1-111 G10
Adder
3.978
274744AC1-111 GEN8
Adder
3.978
965461AG1-414 GEN
Solar/Wind Harmer
1.594
970289AG2-191 GEN
Solar/Wind Harmer
1.336
270594AE1-207 GEN
Solar/Wind Harmer
10.216
274823ROCKFORD ;21
Adder
13.283
270317AD1-130_GEN
Solar/Wind Helper
4.139
966831AG1-554 GEN
Solar/Wind Helper
0.884
270284AF1-227 GEN1
Solar/Wind Helper
1.894
270286AF1-227 GEN2
Solar/Wind Helper
0.695
270287AF1-227 GEN3
Solar/Wind Helper
0.695
270499AE1-146 GEN
Solar/Wind Helper
1.973
945641AF1-229 GEN
Solar/Wind Helper
0.949
276868AE1-113 GEN
Solar/Wind Harmer
4.636
276882AE2-255 GEN
Solar/Wind Harmer
1.545
965431AG1-411 GEN
50/50
45.318
24727105RPMNG2
50/50
3.312
970583AG2-370 GEN
50/50
2.791
270491AE1-102 GEN2
Solar/Wind Harmer
5.333
959331AF2-224 GEN
Solar/Wind Harmer
19.649
965021AG1-366 GEN
Solar/Wind Harmer
4.57
970031AG2-029 GEN
Solar/Wind Harmer
35.908
270043AE2-236 GEN
Solar/Wind Harmer
6.335
270191TR4_S_V150
Solar/Wind Harmer
3.069
270247TR4_N_V136
Solar/Wind Harmer
0.87
944531AF1-118 GEN
Solar/Wind Harmer
34.974
971617AH1-308 GEN
Solar/Wind Harmer
5.12
247643Z2-116 C
Solar/Wind Harmer
0.061
945111AF1-176 GEN
Solar/Wind Harmer
4.761
970349AG2-230 GEN
Solar/Wind Harmer
12.336
24642205MAYFLWER
Adder
0.519
24441205WTRV SLR C
Solar/Wind Harmer
0.103
970513AG2-328 GEN
Solar/Wind Harmer
13.485
970517AG2-330 GEN
Solar/Wind Harmer
12.231
972231SS25-0005
Solar/Wind Harmer
7.115
972181SS23-001
Solar/Wind Harmer
4.447
274752CRETE EC ;2U
Adder
3.664
274753CRETE EC ;3U
Adder
3.664
274724RIVER EC ;11
Adder
13.226
247604X1-042
Adder
0.309
270535AF1-215 GEN1
Solar/Wind Harmer
3.363
274772LINCOLN ;3U
Adder
4.574
274802UNIV PARK;5U
Adder
4.274
274826FISK ;BP
Adder
8.017
274800UNIV PARK;3U
Adder
4.262
972038AH1-567 GEN2
Adder
0.267
276772AC2-154 GEN
Solar/Wind Harmer
2.036
276806AD2-047 C O1
Solar/Wind Harmer
7.809
970941AG2-585 GEN
Solar/Wind Harmer
9.125
964401AG1-302 GEN
Solar/Wind Harmer
6.612
972228AH1-698 GEN2
Adder
2.696
970707AG2-453 GEN
Solar/Wind Harmer
20.31
276897AD1-100 C
Solar/Wind Harmer
20.969
939351AE1-166 GEN
Solar/Wind Harmer
4.285
274676JOLIET 29;8U
Adder
21.371
276893AG1-478 C
Solar/Wind Harmer
0.301
274729ELWOOD EC;1P
Adder
11.842
274730ELWOOD EC;6P
Adder
11.843
274734ELWOOD EC;8P
Adder
11.843
274736ELWOOD EC;9P
Adder
11.843
959141AF2-205 GEN
Solar/Wind Harmer
4.345
943121AE2-341 GEN
Solar/Wind Harmer
10.679
943591AF1-030 GEN
Solar/Wind Harmer
7.12
247642Z2-115 C
Solar/Wind Harmer
0.046
276694AA1-018 GEN2
Solar/Wind Harmer
4.462
274682WAUKEGAN ;7U
Adder
12.642
970289AG2-191 GEN
Solar/Wind Harmer
0.539
970291AG2-192 GEN
Solar/Wind Harmer
0.49
958821AF2-173 GEN
Solar/Wind Harmer
9.782
270004AE1-209 GEN
Solar/Wind Harmer
3.819
276805AD2-038 GEN
Solar/Wind Harmer
3.582
274872LEEDK;1U
Solar/Wind Harmer
0.178
972236AH1-702 GEN2
Adder
1.491
274760LEE CO EC;1U
Adder
6.232
274767LEE CO EC;8U
Adder
6.158
24728705AND G3
Adder
4.21
24728505AND G1
Adder
2.013
270485AE1-090_GEN
Solar/Wind Helper
0.325
942871AE2-306 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.947
970615AG2-402 GEN
50/50
4.57
24729405KEY G3
50/50
0.365
24729305KEY G2
50/50
0.359
24729205KEY G1
50/50
0.357
247620Y3-023
50/50
0.459
246938BC-WTG3
Solar/Wind Harmer
16.329
246937BC-WTG2
Solar/Wind Harmer
16.052
970611AG2-400 GEN
Solar/Wind Harmer
19.649
942221AE2-234 GEN
Solar/Wind Harmer
0.708
944541AF1-119 GEN
Solar/Wind Harmer
3.732
960971AF2-388 GEN
Solar/Wind Harmer
9.738
270216AD2-079_GEN
Solar/Wind Harmer
0.53
960981AF2-389 GEN
Solar/Wind Harmer
1.251
957891AF2-083 GEN
Solar/Wind Harmer
2.789
961051AF2-396 GEN
Solar/Wind Harmer
13.024
961051AF2-396 GEN
Solar/Wind Harmer
6.058
270526AF1-158 GEN
Solar/Wind Harmer
3.657
24441505OLIV SLR
Solar/Wind Harmer
0.107
965681AG1-436 GEN
Solar/Wind Harmer
9.775
965791AG1-447 GEN
Solar/Wind Harmer
5.001
270599AE1-208 GEN
Solar/Wind Harmer
6.3
270031AE2-169
Solar/Wind Harmer
6.3
970321AG2-212 GEN
Solar/Wind Harmer
13.485
274808UNIV PK N;4U
Adder
3.694
274770LINCOLN ;1U
Adder
4.574
274771LINCOLN ;2U
Adder
4.574
274803UNIV PARK;6U
Adder
4.274
274888KELLY CRK;1U
Solar/Wind Harmer
4.31
274887GEN-1.85
Solar/Wind Harmer
3.891
276843GEN-1.7
Solar/Wind Harmer
0.419
958011AF2-095 GEN
Solar/Wind Harmer
10.512
972259AH1-714 GEN
Adder
13.842
274674JOLIET 9 ;6U
Adder
11.098
274847GR RIDGE ;BU
Solar/Wind Harmer
3.625
971573AH1-285 GEN
Solar/Wind Harmer
6.09
958481AF2-142 GEN
Solar/Wind Harmer
10.607
274861TOP CROP ;1U
Solar/Wind Harmer
4.283
274862TOP CROP ;2U
Solar/Wind Harmer
3.577
274696ROCKY RD ;4P
Adder
8.021
274695ROCKY RD ;2P
Adder
7.836
274693ROCKY RD ;1P
Adder
7.759
274697ROCKY RD ;3P
Adder
2.129
274683WAUKEGAN ;8U
Adder
14.804
274683WAUKEGAN ;8U
Adder
12.479
945421AF1-207 GEN
Solar/Wind Harmer
9.808
957841AF2-078 GEN
Solar/Wind Harmer
4.221
962691AG1-118 GEN
Solar/Wind Harmer
20.945
958491AF2-143 GEN
Solar/Wind Harmer
10.473
970921AG2-575 GEN
Solar/Wind Harmer
6.964
970921AG2-575 GEN
Solar/Wind Harmer
1.62
274764LEE CO EC;5U
Adder
6.246
274765LEE CO EC;6U
Adder
6.246
274762LEE CO EC;3U
Adder
6.232
274763LEE CO EC;4U
Adder
6.173
972267AH1-718 GEN
Adder
2.761
247621Y3-024
Adder
0.158
270224U2-072_GEN2
Solar/Wind Helper
0.877
270227U2-072_GEN3
Solar/Wind Helper
0.877
270228U2-072_GEN4
Solar/Wind Helper
0.877
270231U2-072_GEN5
Solar/Wind Helper
0.877
270471AD2-092_GEN
Solar/Wind Helper
0.862
253378AE2-206_GEN
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.324
241960AC2-195 GEN
Solar/Wind Helper
0.702
24727005RPMNG1
50/50
3.301
960861AF2-377 GEN
50/50
2.381
970521AG2-332 GEN
50/50
10.716
24639705ELKHART HY
50/50
0.148
246936BC-WTG1
Solar/Wind Harmer
16.052
270489AE1-102 GEN1
Solar/Wind Harmer
5.333
965421AG1-410 GEN
Solar/Wind Harmer
116.919
965011AG1-365 GEN
Solar/Wind Harmer
19.649
270063AE2-323 C
Solar/Wind Harmer
2.327
247521TR3_G114
Solar/Wind Harmer
3.44
270246TR4_N_V150
Solar/Wind Harmer
0.87
944231AF1-091 GEN
Solar/Wind Harmer
3.727
24695305TIMB G C
Solar/Wind Harmer
4.938
965651AG1-433 GEN
Solar/Wind Harmer
4.869
958861AF2-177 GEN
Solar/Wind Harmer
9.453
945111AF1-176 GEN
Solar/Wind Harmer
15.023
270505AE1-170 C O1
Solar/Wind Harmer
12.313
945371AF1-202 GEN
Solar/Wind Harmer
5.687
270449AD2-020 GEN
Solar/Wind Harmer
2.264
943021AE2-325 GEN
Solar/Wind Harmer
2.942
970245AG2-165 GEN
Solar/Wind Harmer
13.485
970373AG2-245 GEN
Solar/Wind Harmer
15.815
274751CRETE EC ;1U
Adder
3.664
274754CRETE EC ;4U
Adder
3.664
274723RIVER EC ;12
Adder
13.388
274812UNIV PK N;8U
Adder
3.711
276164X3-005 C
Solar/Wind Harmer
0.52
270055AF2-134 C O1
Solar/Wind Harmer
2.242
972207SS24-0001
Solar/Wind Harmer
16.263
274773LINCOLN ;4U
Adder
4.574
274774LINCOLN ;5U
Adder
4.574
274801UNIV PARK;4U
Adder
4.262
276776AD2-060 GEN
Solar/Wind Harmer
0.309
958381AF2-132 GEN
Solar/Wind Harmer
6.612
964861AG1-349 GEN
Solar/Wind Harmer
5.72
971917AH1-482 GEN
Solar/Wind Harmer
6.6
941551AE2-152 GEN
Solar/Wind Harmer
3.277
274676JOLIET 29;8U
Adder
22.162
274674JOLIET 9 ;6U
Adder
11.098
274732ELWOOD EC;7P
Adder
11.843
274871GR RIDGE ;2U
Solar/Wind Harmer
5.51
940581AE2-045 GEN
Solar/Wind Harmer
7.274
971605AH1-302 GEN
Solar/Wind Harmer
6.22
274745AC1-111 GEN9
Adder
3.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.329
274682WAUKEGAN ;7U
Adder
12.642
970291AG2-192 GEN
Solar/Wind Harmer
0.914
274828WAUKEGAN ;BP
Adder
7.76
270005AE1-210 C O1
Solar/Wind Harmer
3.819
965031AG1-367 GEN
Solar/Wind Harmer
6.987
960751AF2-366 GEN
Solar/Wind Harmer
1.998
962781AG1-127 GEN
Solar/Wind Harmer
6.623
939401AE1-172 GEN
Solar/Wind Harmer
9.702
276901AD2-066 C O1
Solar/Wind Harmer
2.445
270032AE2-172
Solar/Wind Harmer
3.233
274872LEEDK;1U
Solar/Wind Harmer
5.707
274822ROCKFORD ;11
Adder
13.38
972235AH1-702 GEN1
Adder
1.714
274761LEE CO EC;2U
Adder
6.232
274766LEE CO EC;7U
Adder
6.158
24728605AND G2
Adder
2.013
270462AD2-086
Solar/Wind Helper
3.736
270223U2-072_GEN1
Solar/Wind Helper
0.877
270578AF1-285 GEN2
Solar/Wind Helper
0.594
270391AF1-285 GEN3
Solar/Wind Helper
0.594
247522W1-056 GEN
Solar/Wind Helper
1.179
960841AF2-375 GEN
Solar/Wind Helper
1.188
270349AD2-093_GEN
Solar/Wind Helper
0.862
944201AF1-088_MTX
Adder
54.26
957141AF2-008_MTX
Adder
27.13
990497J1323
External Queue
1.5914489030838013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.448
MECLTFEXP_MEC->PJM
CLTF
9.525
SIGELTFEXP_SIGE->PJM
CLTF
0.193
LAGNLTFEXP_LAGN->PJM
CLTF
5.535
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.203
TVALTFEXP_TVA->PJM
CLTF
2.191
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.893
NYPJM->LTFIMP_NY
CLTF
1.315
LGEELTFEXP_LGEE->PJM
CLTF
1.728
WECLTFEXP_WEC->PJM
CLTF
2.594
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.108
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.64 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2844.24
MW Contribution:34.94
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
3.236
971599AH1-298 GEN
50/50
9.99
24729505KEY G4
50/50
6.479
24653605MOTTVILLE
50/50
0.003
957201AF2-014 GEN
Solar/Wind Harmer
18.345
270435AC2-044 GEN
Solar/Wind Harmer
8.09
963791AG1-232 GEN
Solar/Wind Harmer
16.038
965041AG1-368 GEN
Solar/Wind Harmer
11.564
270071AF1-092 GEN
Solar/Wind Harmer
15.583
965051AG1-369 GEN
Solar/Wind Harmer
4.875
958711AF2-162 GEN
Solar/Wind Harmer
0.872
270024AE2-089 GEN
Solar/Wind Harmer
3.978
965101AG1-375 GEN
Solar/Wind Harmer
8.366
971771AH1-392 GEN
Solar/Wind Harmer
7.225
971347AH1-153 GEN
Solar/Wind Harmer
11.935
945581AF1-223 GEN
Solar/Wind Harmer
3.571
971769AH1-391 GEN
Solar/Wind Harmer
7.719
944161AF1-084 GEN
Solar/Wind Harmer
1.695
960681AF2-359 GEN
Solar/Wind Harmer
2.856
274814UNIV PK N;0U
Adder
3.62
274807UNIV PK N;3U
Adder
3.613
970615AG2-402 GEN
50/50
4.476
24729405KEY G3
50/50
0.354
24727005RPMNG1
50/50
3.251
960861AF2-377 GEN
50/50
2.272
970521AG2-332 GEN
50/50
10.376
24639705ELKHART HY
50/50
0.143
246936BC-WTG1
Solar/Wind Harmer
15.829
270489AE1-102 GEN1
Solar/Wind Harmer
5.258
965421AG1-410 GEN
Solar/Wind Harmer
115.255
965011AG1-365 GEN
Solar/Wind Harmer
19.246
270063AE2-323 C
Solar/Wind Harmer
2.257
247521TR3_G114
Solar/Wind Harmer
3.283
270246TR4_N_V150
Solar/Wind Harmer
0.831
944231AF1-091 GEN
Solar/Wind Harmer
3.584
965651AG1-433 GEN
Solar/Wind Harmer
4.713
24695305TIMB G C
Solar/Wind Harmer
4.68
958861AF2-177 GEN
Solar/Wind Harmer
9.145
945111AF1-176 GEN
Solar/Wind Harmer
14.516
270505AE1-170 C O1
Solar/Wind Harmer
11.891
965431AG1-411 GEN
50/50
44.673
24727105RPMNG2
50/50
3.263
970583AG2-370 GEN
50/50
2.689
270491AE1-102 GEN2
Solar/Wind Harmer
5.258
959331AF2-224 GEN
Solar/Wind Harmer
19.246
965021AG1-366 GEN
Solar/Wind Harmer
4.476
970031AG2-029 GEN
Solar/Wind Harmer
34.937
270043AE2-236 GEN
Solar/Wind Harmer
6.159
270191TR4_S_V150
Solar/Wind Harmer
2.929
270247TR4_N_V136
Solar/Wind Harmer
0.831
944531AF1-118 GEN
Solar/Wind Harmer
33.935
971617AH1-308 GEN
Solar/Wind Harmer
4.927
247643Z2-116 C
Solar/Wind Harmer
0.059
945111AF1-176 GEN
Solar/Wind Harmer
4.6
970349AG2-230 GEN
Solar/Wind Harmer
11.935
24642205MAYFLWER
Adder
0.502
24441205WTRV SLR C
Solar/Wind Harmer
0.099
970513AG2-328 GEN
Solar/Wind Harmer
13.05
970517AG2-330 GEN
Solar/Wind Harmer
11.836
972231SS25-0005
Solar/Wind Harmer
6.881
972181SS23-001
Solar/Wind Harmer
4.301
274752CRETE EC ;2U
Adder
3.544
274753CRETE EC ;3U
Adder
3.544
274724RIVER EC ;11
Adder
12.793
270535AF1-215 GEN1
Solar/Wind Harmer
3.251
247604X1-042
Adder
0.298
274772LINCOLN ;3U
Adder
4.425
274802UNIV PARK;5U
Adder
4.134
274826FISK ;BP
Adder
7.754
274800UNIV PARK;3U
Adder
4.122
972038AH1-567 GEN2
Adder
0.258
276772AC2-154 GEN
Solar/Wind Harmer
1.969
276806AD2-047 C O1
Solar/Wind Harmer
7.553
970941AG2-585 GEN
Solar/Wind Harmer
8.825
964401AG1-302 GEN
Solar/Wind Harmer
6.392
972228AH1-698 GEN2
Adder
2.607
970707AG2-453 GEN
Solar/Wind Harmer
19.645
276897AD1-100 C
Solar/Wind Harmer
20.28
939351AE1-166 GEN
Solar/Wind Harmer
4.144
274676JOLIET 29;8U
Adder
20.669
276893AG1-478 C
Solar/Wind Harmer
0.291
274729ELWOOD EC;1P
Adder
11.453
274730ELWOOD EC;6P
Adder
11.453
274734ELWOOD EC;8P
Adder
11.453
274736ELWOOD EC;9P
Adder
11.453
959141AF2-205 GEN
Solar/Wind Harmer
4.2
943121AE2-341 GEN
Solar/Wind Harmer
10.329
943591AF1-030 GEN
Solar/Wind Harmer
6.886
247642Z2-115 C
Solar/Wind Harmer
0.044
276694AA1-018 GEN2
Solar/Wind Harmer
4.315
274682WAUKEGAN ;7U
Adder
12.227
970289AG2-191 GEN
Solar/Wind Harmer
0.52
24729305KEY G2
50/50
0.348
24729205KEY G1
50/50
0.346
247620Y3-023
50/50
0.445
246938BC-WTG3
Solar/Wind Harmer
16.102
246937BC-WTG2
Solar/Wind Harmer
15.829
970611AG2-400 GEN
Solar/Wind Harmer
19.246
942221AE2-234 GEN
Solar/Wind Harmer
0.685
944541AF1-119 GEN
Solar/Wind Harmer
3.612
960971AF2-388 GEN
Solar/Wind Harmer
9.426
270216AD2-079_GEN
Solar/Wind Harmer
0.513
960981AF2-389 GEN
Solar/Wind Harmer
1.208
957891AF2-083 GEN
Solar/Wind Harmer
2.694
961051AF2-396 GEN
Solar/Wind Harmer
12.574
961051AF2-396 GEN
Solar/Wind Harmer
5.849
270526AF1-158 GEN
Solar/Wind Harmer
3.535
24441505OLIV SLR
Solar/Wind Harmer
0.103
965681AG1-436 GEN
Solar/Wind Harmer
9.449
965791AG1-447 GEN
Solar/Wind Harmer
4.834
270599AE1-208 GEN
Solar/Wind Harmer
6.074
270031AE2-169
Solar/Wind Harmer
6.074
970321AG2-212 GEN
Solar/Wind Harmer
13.05
274808UNIV PK N;4U
Adder
3.573
274770LINCOLN ;1U
Adder
4.425
274771LINCOLN ;2U
Adder
4.425
274803UNIV PARK;6U
Adder
4.134
274888KELLY CRK;1U
Solar/Wind Harmer
4.168
274887GEN-1.85
Solar/Wind Harmer
3.763
276843GEN-1.7
Solar/Wind Harmer
0.405
958011AF2-095 GEN
Solar/Wind Harmer
10.167
945371AF1-202 GEN
Solar/Wind Harmer
5.494
270449AD2-020 GEN
Solar/Wind Harmer
2.185
943021AE2-325 GEN
Solar/Wind Harmer
2.839
970245AG2-165 GEN
Solar/Wind Harmer
13.05
970373AG2-245 GEN
Solar/Wind Harmer
15.287
274751CRETE EC ;1U
Adder
3.544
274754CRETE EC ;4U
Adder
3.544
274723RIVER EC ;12
Adder
12.95
274812UNIV PK N;8U
Adder
3.589
276164X3-005 C
Solar/Wind Harmer
0.503
270055AF2-134 C O1
Solar/Wind Harmer
2.167
972207SS24-0001
Solar/Wind Harmer
15.732
274773LINCOLN ;4U
Adder
4.425
274774LINCOLN ;5U
Adder
4.425
274801UNIV PARK;4U
Adder
4.122
276776AD2-060 GEN
Solar/Wind Harmer
0.299
958381AF2-132 GEN
Solar/Wind Harmer
6.392
964861AG1-349 GEN
Solar/Wind Harmer
5.529
971917AH1-482 GEN
Solar/Wind Harmer
6.38
941551AE2-152 GEN
Solar/Wind Harmer
3.169
274676JOLIET 29;8U
Adder
21.435
274674JOLIET 9 ;6U
Adder
10.733
274732ELWOOD EC;7P
Adder
11.453
274871GR RIDGE ;2U
Solar/Wind Harmer
5.329
940581AE2-045 GEN
Solar/Wind Harmer
7.032
971605AH1-302 GEN
Solar/Wind Harmer
6.013
274745AC1-111 GEN9
Adder
3.847
276691AA1-018 GEN1
Solar/Wind Harmer
0.318
274682WAUKEGAN ;7U
Adder
12.227
274828WAUKEGAN ;BP
Adder
7.505
970291AG2-192 GEN
Solar/Wind Harmer
0.881
960751AF2-366 GEN
Solar/Wind Harmer
1.932
962781AG1-127 GEN
Solar/Wind Harmer
6.405
939401AE1-172 GEN
Solar/Wind Harmer
9.38
276901AD2-066 C O1
Solar/Wind Harmer
2.364
270005AE1-210 C O1
Solar/Wind Harmer
3.674
965031AG1-367 GEN
Solar/Wind Harmer
6.723
274872LEEDK;1U
Solar/Wind Harmer
5.519
274822ROCKFORD ;11
Adder
12.939
972235AH1-702 GEN1
Adder
1.658
274761LEE CO EC;2U
Adder
6.026
274766LEE CO EC;7U
Adder
5.955
24728605AND G2
Adder
1.927
270462AD2-086
Solar/Wind Helper
4.073
270223U2-072_GEN1
Solar/Wind Helper
0.972
270578AF1-285 GEN2
Solar/Wind Helper
0.658
270391AF1-285 GEN3
Solar/Wind Helper
0.658
247522W1-056 GEN
Solar/Wind Helper
1.253
960841AF2-375 GEN
Solar/Wind Helper
1.267
270349AD2-093_GEN
Solar/Wind Helper
1.132
270032AE2-172
Solar/Wind Harmer
1.289
970291AG2-192 GEN
Solar/Wind Harmer
0.473
276805AD2-038 GEN
Solar/Wind Harmer
3.463
958821AF2-173 GEN
Solar/Wind Harmer
9.412
270004AE1-209 GEN
Solar/Wind Harmer
3.674
274872LEEDK;1U
Solar/Wind Harmer
0.172
972236AH1-702 GEN2
Adder
1.441
274760LEE CO EC;1U
Adder
6.026
274767LEE CO EC;8U
Adder
5.955
24728705AND G3
Adder
4.031
24728505AND G1
Adder
1.927
270485AE1-090_GEN
Solar/Wind Helper
0.355
942871AE2-306 GEN
Solar/Wind Helper
0.494
270541AE2-072 C
Solar/Wind Helper
1.045
274805UNIV PK N;1U
Adder
3.597
274811UNIV PK N;7U
Adder
3.589
270536AF1-215 GEN2
Solar/Wind Harmer
3.251
274775LINCOLN ;6U
Adder
4.425
274776LINCOLN ;7U
Adder
4.425
274777LINCOLN ;8U
Adder
4.425
972037AH1-567 GEN1
Adder
0.13
274827FISK ;RP
Adder
5.495
960591AF2-350 GEN
Solar/Wind Harmer
7.06
972227AH1-698 GEN1
Adder
1.836
274687WILL CNTY;4U
Adder
19.566
274687WILL CNTY;4U
Adder
19.566
958391AF2-133 GEN
Solar/Wind Harmer
6.34
274675JOLIET 29;7U
Adder
21.435
274675JOLIET 29;7U
Adder
20.67
274731ELWOOD EC;2P
Adder
11.453
274733ELWOOD EC;3P
Adder
11.453
274735ELWOOD EC;4P
Adder
11.453
274728ELWOOD EC;5P
Adder
11.453
970833AG2-524 GEN
Solar/Wind Harmer
6.055
970833AG2-524 GEN
Solar/Wind Harmer
2.816
274746AC1-111 G10
Adder
3.847
274744AC1-111 GEN8
Adder
3.847
965461AG1-414 GEN
Solar/Wind Harmer
1.536
970289AG2-191 GEN
Solar/Wind Harmer
1.287
276868AE1-113 GEN
Solar/Wind Harmer
6.79
276882AE2-255 GEN
Solar/Wind Harmer
2.264
274823ROCKFORD ;21
Adder
12.846
270317AD1-130_GEN
Solar/Wind Helper
4.512
966831AG1-554 GEN
Solar/Wind Helper
0.937
270284AF1-227 GEN1
Solar/Wind Helper
2.269
270286AF1-227 GEN2
Solar/Wind Helper
0.832
270287AF1-227 GEN3
Solar/Wind Helper
0.832
270499AE1-146 GEN
Solar/Wind Helper
2.104
945641AF1-229 GEN
Solar/Wind Helper
1.013
253383AE2-342_GEN
Solar/Wind Helper
0.371
270594AE1-207 GEN
Solar/Wind Harmer
4.074
972259AH1-714 GEN
Adder
13.388
274674JOLIET 9 ;6U
Adder
10.733
274847GR RIDGE ;BU
Solar/Wind Harmer
3.505
971573AH1-285 GEN
Solar/Wind Harmer
5.89
958481AF2-142 GEN
Solar/Wind Harmer
10.258
274861TOP CROP ;1U
Solar/Wind Harmer
4.142
274862TOP CROP ;2U
Solar/Wind Harmer
3.459
274696ROCKY RD ;4P
Adder
7.757
274695ROCKY RD ;2P
Adder
7.578
274693ROCKY RD ;1P
Adder
7.504
274697ROCKY RD ;3P
Adder
2.059
274683WAUKEGAN ;8U
Adder
14.317
274683WAUKEGAN ;8U
Adder
12.069
962691AG1-118 GEN
Solar/Wind Harmer
20.257
958491AF2-143 GEN
Solar/Wind Harmer
10.127
945421AF1-207 GEN
Solar/Wind Harmer
9.481
957841AF2-078 GEN
Solar/Wind Harmer
4.08
970921AG2-575 GEN
Solar/Wind Harmer
6.735
970921AG2-575 GEN
Solar/Wind Harmer
1.566
274879MINONK ;1U
Solar/Wind Harmer
4.527
274764LEE CO EC;5U
Adder
6.04
274765LEE CO EC;6U
Adder
6.04
274762LEE CO EC;3U
Adder
6.026
274763LEE CO EC;4U
Adder
5.969
972267AH1-718 GEN
Adder
2.67
247621Y3-024
Adder
0.15
270224U2-072_GEN2
Solar/Wind Helper
0.972
270227U2-072_GEN3
Solar/Wind Helper
0.972
270228U2-072_GEN4
Solar/Wind Helper
0.972
270231U2-072_GEN5
Solar/Wind Helper
0.972
270471AD2-092_GEN
Solar/Wind Helper
1.132
253378AE2-206_GEN
Solar/Wind Helper
0.774
276820AF1-078_GEN
Solar/Wind Helper
0.362
241960AC2-195 GEN
Solar/Wind Helper
0.782
944201AF1-088_MTX
Adder
52.239
957141AF2-008_MTX
Adder
26.12
990497J1323
External Queue
1.5632063150405884
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.666
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.161
MECLTFEXP_MEC->PJM
CLTF
9.209
SIGELTFEXP_SIGE->PJM
CLTF
0.184
LAGNLTFEXP_LAGN->PJM
CLTF
5.377
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.361
TVALTFEXP_TVA->PJM
CLTF
2.131
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.228
NYPJM->LTFIMP_NY
CLTF
1.258
LGEELTFEXP_LGEE->PJM
CLTF
1.624
WECLTFEXP_WEC->PJM
CLTF
2.509
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.066
AG2-052LTFEXP_AG2-052->PJM
LTF
0.163
AH1-155LTFEXP_AH1-155->PJM
LTF
0.244

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.12 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2697.98
MW Contribution:5.43
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.301
960861AF2-377 GEN
50/50
2.381
970521AG2-332 GEN
50/50
10.716
24639705ELKHART HY
50/50
0.148
246936BC-WTG1
Solar/Wind Harmer
1.161
270489AE1-102 GEN1
Solar/Wind Harmer
3.72
965421AG1-410 GEN
Solar/Wind Harmer
81.572
965011AG1-365 GEN
Solar/Wind Harmer
13.709
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.26
270246TR4_N_V150
Solar/Wind Harmer
0.046
965431AG1-411 GEN
50/50
45.318
24727105RPMNG2
50/50
3.312
970583AG2-370 GEN
50/50
2.791
270491AE1-102 GEN2
Solar/Wind Harmer
3.72
959331AF2-224 GEN
Solar/Wind Harmer
9.596
965021AG1-366 GEN
Solar/Wind Harmer
4.57
970031AG2-029 GEN
Solar/Wind Harmer
5.428
270043AE2-236 GEN
Solar/Wind Harmer
5.157
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.245
971617AH1-308 GEN
Solar/Wind Harmer
5.12
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.761
970349AG2-230 GEN
Solar/Wind Harmer
8.606
24642205MAYFLWER
Adder
0.519
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.283
970517AG2-330 GEN
Solar/Wind Harmer
13.699
274752CRETE EC ;2U
Adder
6.177
274753CRETE EC ;3U
Adder
6.177
274724RIVER EC ;11
Adder
13.226
247604X1-042
Adder
0.309
270535AF1-215 GEN1
Solar/Wind Harmer
0.006
274772LINCOLN ;3U
Adder
6.227
274802UNIV PARK;5U
Adder
4.274
274826FISK ;BP
Adder
8.017
274800UNIV PARK;3U
Adder
4.262
972038AH1-567 GEN2
Adder
0.267
276806AD2-047 C O1
Solar/Wind Harmer
2.886
970941AG2-585 GEN
Solar/Wind Harmer
6.366
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.696
970707AG2-453 GEN
Solar/Wind Harmer
16.532
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.371
276893AG1-478 C
Solar/Wind Harmer
0.199
274729ELWOOD EC;1P
Adder
11.842
274730ELWOOD EC;6P
Adder
11.843
274734ELWOOD EC;8P
Adder
11.843
274736ELWOOD EC;9P
Adder
11.843
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.328
943591AF1-030 GEN
Solar/Wind Harmer
5.538
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.642
970289AG2-191 GEN
Solar/Wind Harmer
0.539
970291AG2-192 GEN
Solar/Wind Harmer
0.49
958821AF2-173 GEN
Solar/Wind Harmer
6.825
270004AE1-209 GEN
Solar/Wind Harmer
1.056
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.178
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
0.176
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.086
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.78
959091AF2-200 GEN
Solar/Wind Harmer
9.543
972236AH1-702 GEN2
Adder
1.491
970571AG2-364 GEN
Solar/Wind Harmer
9.45
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.232
274767LEE CO EC;8U
Adder
6.158
946031AF1-268 GEN
Solar/Wind Harmer
4.44
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
6.987
276157O29GEN1
Solar/Wind Harmer
0.746
274878BISHOP HL;2U
Solar/Wind Harmer
0.154
942111AE2-223 GEN
Solar/Wind Harmer
1.477
965931AG1-462 GEN
Solar/Wind Harmer
11.384
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.388
959611AF2-252 GEN
Solar/Wind Harmer
1.488
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.154
971993AH1-541 GEN
Solar/Wind Harmer
1.946
276621W2-048 GEN
Solar/Wind Harmer
0.209
276838X2-022 GEN2
Solar/Wind Harmer
0.233
942481AE2-261 GEN
Solar/Wind Harmer
11.923
970193AG2-126 GEN
Solar/Wind Harmer
5.78
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.21
24728505AND G1
Adder
2.013
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.781
970519AG2-331 GEN
Solar/Wind Harmer
7.913
970699AG2-449 GEN
Solar/Wind Harmer
0.761
270485AE1-090_GEN
Solar/Wind Helper
0.325
942871AE2-306 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.947
944231AF1-091 GEN
Solar/Wind Harmer
1.84
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.823
958861AF2-177 GEN
Solar/Wind Harmer
2.615
945111AF1-176 GEN
Solar/Wind Harmer
10.481
270505AE1-170 C O1
Solar/Wind Harmer
6.013
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.942
970245AG2-165 GEN
Solar/Wind Harmer
2.283
970373AG2-245 GEN
Solar/Wind Harmer
11.033
274751CRETE EC ;1U
Adder
6.177
274754CRETE EC ;4U
Adder
6.177
274723RIVER EC ;12
Adder
13.388
274812UNIV PK N;8U
Adder
3.711
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.227
274774LINCOLN ;5U
Adder
6.227
274801UNIV PARK;4U
Adder
4.262
276776AD2-060 GEN
Solar/Wind Harmer
0.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.6
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.162
274674JOLIET 9 ;6U
Adder
11.098
274732ELWOOD EC;7P
Adder
11.843
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.22
274745AC1-111 GEN9
Adder
3.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.598
274682WAUKEGAN ;7U
Adder
12.642
970291AG2-192 GEN
Solar/Wind Harmer
0.638
274828WAUKEGAN ;BP
Adder
7.76
270005AE1-210 C O1
Solar/Wind Harmer
1.056
965031AG1-367 GEN
Solar/Wind Harmer
4.875
962781AG1-127 GEN
Solar/Wind Harmer
4.624
939401AE1-172 GEN
Solar/Wind Harmer
3.633
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.233
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.531
276861AD2-134 GEN
Solar/Wind Harmer
0.086
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.315
959081AF2-199 GEN
Solar/Wind Harmer
4.772
971067AG2-660 GEN
Solar/Wind Harmer
1.591
274822ROCKFORD ;11
Adder
13.38
970825AG2-519 GEN
Solar/Wind Harmer
1.686
972235AH1-702 GEN1
Adder
1.714
970819AG2-516 GEN
Solar/Wind Harmer
5.675
970569AG2-363 GEN
Solar/Wind Harmer
14.175
971475AH1-234 GEN
Solar/Wind Harmer
2.289
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.232
274766LEE CO EC;7U
Adder
6.158
276903AD2-071 C
Solar/Wind Harmer
5.188
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.154
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.361
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.579
963741AG1-226 GEN
Solar/Wind Harmer
10.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.15
247536S-71 GEN
Solar/Wind Harmer
0.171
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.633
276615X2-022 GEN
Solar/Wind Harmer
0.043
965911AG1-460 GEN
Solar/Wind Harmer
0.798
24728605AND G2
Adder
2.013
970773AG2-487 GEN
Solar/Wind Harmer
0.599
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.176
270462AD2-086
Solar/Wind Helper
3.736
270223U2-072_GEN1
Solar/Wind Helper
0.877
270578AF1-285 GEN2
Solar/Wind Helper
0.594
270391AF1-285 GEN3
Solar/Wind Helper
0.594
247522W1-056 GEN
Solar/Wind Helper
1.179
960841AF2-375 GEN
Solar/Wind Helper
1.188
270349AD2-093_GEN
Solar/Wind Helper
0.862
970615AG2-402 GEN
50/50
4.57
24729405KEY G3
50/50
0.365
24729305KEY G2
50/50
0.359
24729205KEY G1
50/50
0.357
247620Y3-023
50/50
0.459
246938BC-WTG3
Solar/Wind Harmer
1.037
246937BC-WTG2
Solar/Wind Harmer
1.161
970611AG2-400 GEN
Solar/Wind Harmer
13.709
970627AG2-408 GEN
Solar/Wind Harmer
4.113
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.416
960971AF2-388 GEN
Solar/Wind Harmer
3.647
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.449
961051AF2-396 GEN
Solar/Wind Harmer
7.632
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.819
965791AG1-447 GEN
Solar/Wind Harmer
5.001
270599AE1-208 GEN
Solar/Wind Harmer
4.943
270031AE2-169
Solar/Wind Harmer
2.966
970321AG2-212 GEN
Solar/Wind Harmer
2.283
274808UNIV PK N;4U
Adder
3.694
274770LINCOLN ;1U
Adder
6.227
274771LINCOLN ;2U
Adder
6.227
274803UNIV PARK;6U
Adder
4.274
274888KELLY CRK;1U
Solar/Wind Harmer
0.299
274887GEN-1.85
Solar/Wind Harmer
0.134
276843GEN-1.7
Solar/Wind Harmer
0.165
958011AF2-095 GEN
Solar/Wind Harmer
7.334
972259AH1-714 GEN
Adder
13.842
274674JOLIET 9 ;6U
Adder
11.098
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.921
958481AF2-142 GEN
Solar/Wind Harmer
7.4
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.667
274696ROCKY RD ;4P
Adder
8.021
274695ROCKY RD ;2P
Adder
7.836
274693ROCKY RD ;1P
Adder
7.759
274697ROCKY RD ;3P
Adder
2.129
274683WAUKEGAN ;8U
Adder
14.804
274683WAUKEGAN ;8U
Adder
12.479
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.613
958491AF2-143 GEN
Solar/Wind Harmer
7.306
970921AG2-575 GEN
Solar/Wind Harmer
4.859
970921AG2-575 GEN
Solar/Wind Harmer
1.62
971613AH1-306 GEN
Solar/Wind Harmer
2.328
274879MINONK ;1U
Solar/Wind Harmer
0.204
942991AE2-321 GEN
Solar/Wind Harmer
5.39
971333AH1-146 GEN
Solar/Wind Harmer
9.601
971335AH1-147 GEN
Solar/Wind Harmer
9.601
960441AF2-335 GEN
Solar/Wind Harmer
4.786
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.543
971343AH1-151 GEN
Solar/Wind Harmer
9.543
970825AG2-519 GEN
Solar/Wind Harmer
5.263
274856ECOGROVE ;U1
Solar/Wind Harmer
0.111
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.658
274764LEE CO EC;5U
Adder
6.246
274765LEE CO EC;6U
Adder
6.246
274762LEE CO EC;3U
Adder
6.232
274763LEE CO EC;4U
Adder
6.173
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.349
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.761
276741O09 GEN1
Solar/Wind Harmer
0.164
276708O09 GEN2
Solar/Wind Harmer
0.164
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.181
276646AC1-214 GEN2
Solar/Wind Harmer
0.181
966841AG1-555 GEN
Solar/Wind Harmer
0.519
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.158
960611AF2-352 GEN
Solar/Wind Harmer
1.488
970241AG2-163 GEN
Solar/Wind Harmer
2.514
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.299
276911AD2-131_GEN
Solar/Wind Harmer
0.547
970883AG2-550 GEN
Solar/Wind Harmer
3.858
970885AG2-551 GEN
Solar/Wind Harmer
1.286
945391AF1-204 GEN
Solar/Wind Harmer
4.094
970623AG2-406 GEN
Solar/Wind Harmer
0.671
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.387
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.761
270224U2-072_GEN2
Solar/Wind Helper
0.877
270227U2-072_GEN3
Solar/Wind Helper
0.877
270228U2-072_GEN4
Solar/Wind Helper
0.877
270231U2-072_GEN5
Solar/Wind Helper
0.877
270471AD2-092_GEN
Solar/Wind Helper
0.862
253378AE2-206_GEN
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.324
241960AC2-195 GEN
Solar/Wind Helper
0.702
24727205RPMNG3
50/50
3.285
971599AH1-298 GEN
50/50
10.265
24729505KEY G4
50/50
6.681
957201AF2-014 GEN
Solar/Wind Harmer
0.002
270435AC2-044 GEN
Solar/Wind Harmer
3.625
963791AG1-232 GEN
Solar/Wind Harmer
11.533
965041AG1-368 GEN
Solar/Wind Harmer
8.372
270071AF1-092 GEN
Solar/Wind Harmer
14.295
965051AG1-369 GEN
Solar/Wind Harmer
3.565
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.034
971771AH1-392 GEN
Solar/Wind Harmer
5.793
971347AH1-153 GEN
Solar/Wind Harmer
8.606
971619AH1-309 GEN
Solar/Wind Harmer
2.577
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.222
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.881
274814UNIV PK N;0U
Adder
3.743
274807UNIV PK N;3U
Adder
3.735
274805UNIV PK N;1U
Adder
3.719
274811UNIV PK N;7U
Adder
3.711
270536AF1-215 GEN2
Solar/Wind Harmer
0.006
274775LINCOLN ;6U
Adder
6.227
274776LINCOLN ;7U
Adder
6.227
274777LINCOLN ;8U
Adder
6.227
972037AH1-567 GEN1
Adder
0.134
274827FISK ;RP
Adder
5.682
960591AF2-350 GEN
Solar/Wind Harmer
5.093
972227AH1-698 GEN1
Adder
1.898
274687WILL CNTY;4U
Adder
20.23
274687WILL CNTY;4U
Adder
20.23
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.163
274675JOLIET 29;7U
Adder
21.371
274731ELWOOD EC;2P
Adder
11.842
274733ELWOOD EC;3P
Adder
11.842
274735ELWOOD EC;4P
Adder
11.842
274728ELWOOD EC;5P
Adder
11.843
970833AG2-524 GEN
Solar/Wind Harmer
5.503
970833AG2-524 GEN
Solar/Wind Harmer
3.669
971611AH1-305 GEN
Solar/Wind Harmer
2.963
274746AC1-111 G10
Adder
3.978
274744AC1-111 GEN8
Adder
3.978
970289AG2-191 GEN
Solar/Wind Harmer
0.932
270594AE1-207 GEN
Solar/Wind Harmer
5.432
276868AE1-113 GEN
Solar/Wind Harmer
0.971
276882AE2-255 GEN
Solar/Wind Harmer
0.566
971177AH1-047 GEN
Solar/Wind Harmer
2.975
971411AH1-196 GEN
Solar/Wind Harmer
7.208
971675AH1-338 GEN
Solar/Wind Harmer
1.873
970115AG2-085 GEN
Solar/Wind Harmer
1.915
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.543
274823ROCKFORD ;21
Adder
13.283
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.802
970169AG2-114 GEN
Solar/Wind Harmer
4.71
971681AH1-341 GEN
Solar/Wind Harmer
7.556
971549AH1-272 GEN
Solar/Wind Harmer
9.681
961011AF2-392 GEN
Solar/Wind Harmer
2.722
957751AF2-069 GEN
Solar/Wind Harmer
0.152
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.771
941731AE2-173 GEN
Solar/Wind Harmer
3.786
946321AF1-296 GEN
Solar/Wind Harmer
2.514
963841AG1-237 GEN
Solar/Wind Harmer
1.925
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.154
276848AB2-070 GEN3
Solar/Wind Harmer
0.153
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.247
971029AG2-637 GEN
Solar/Wind Harmer
5.161
971673AH1-337 GEN
Solar/Wind Harmer
2.14
247607V1-011 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Helper
4.139
966831AG1-554 GEN
Solar/Wind Helper
0.884
270284AF1-227 GEN1
Solar/Wind Helper
1.894
270286AF1-227 GEN2
Solar/Wind Helper
0.695
270287AF1-227 GEN3
Solar/Wind Helper
0.695
270499AE1-146 GEN
Solar/Wind Helper
1.973
945641AF1-229 GEN
Solar/Wind Helper
0.949
944201AF1-088_MTX
Adder
54.26
957141AF2-008_MTX
Adder
17.407
990497J1323
External Queue
1.5914489030838013
990792J1392
External Queue
5.474584102630615
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.448
MECLTFEXP_MEC->PJM
CLTF
9.525
SIGELTFEXP_SIGE->PJM
CLTF
0.193
LAGNLTFEXP_LAGN->PJM
CLTF
5.535
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.203
TVALTFEXP_TVA->PJM
CLTF
2.191
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.893
NYPJM->LTFIMP_NY
CLTF
1.315
LGEELTFEXP_LGEE->PJM
CLTF
1.728
WECLTFEXP_WEC->PJM
CLTF
2.594
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.108
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.44 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2457.96
MW Contribution:29.77
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.115
246936BC-WTG1
Solar/Wind Harmer
15.308
270489AE1-102 GEN1
Solar/Wind Harmer
5.086
965421AG1-410 GEN
Solar/Wind Harmer
111.161
965011AG1-365 GEN
Solar/Wind Harmer
17.544
270063AE2-323 C
Solar/Wind Harmer
1.875
247521TR3_G114
Solar/Wind Harmer
2.787
270246TR4_N_V150
Solar/Wind Harmer
0.705
944231AF1-091 GEN
Solar/Wind Harmer
3
965651AG1-433 GEN
Solar/Wind Harmer
3.872
24639705ELKHART HY
Adder
0.108
24695305TIMB G C
Solar/Wind Harmer
3.882
958861AF2-177 GEN
Solar/Wind Harmer
7.503
945371AF1-202 GEN
Solar/Wind Harmer
4.496
945111AF1-176 GEN
Solar/Wind Harmer
11.426
270505AE1-170 C O1
Solar/Wind Harmer
9.283
270449AD2-020 GEN
Solar/Wind Harmer
1.702
943021AE2-325 GEN
Solar/Wind Harmer
2.211
970373AG2-245 GEN
Solar/Wind Harmer
11.897
274751CRETE EC ;1U
Adder
2.751
274754CRETE EC ;4U
Adder
2.751
274723RIVER EC ;12
Adder
10.038
270055AF2-134 C O1
Solar/Wind Harmer
1.691
274812UNIV PK N;8U
Adder
2.782
276164X3-005 C
Solar/Wind Harmer
0.39
970245AG2-165 GEN
Solar/Wind Harmer
9.898
958381AF2-132 GEN
Solar/Wind Harmer
5
964861AG1-349 GEN
Solar/Wind Harmer
4.326
971917AH1-482 GEN
Solar/Wind Harmer
4.993
972207SS24-0001
Solar/Wind Harmer
12.113
274773LINCOLN ;4U
Adder
3.407
274774LINCOLN ;5U
Adder
3.407
274801UNIV PARK;4U
Adder
3.191
276776AD2-060 GEN
Solar/Wind Harmer
0.231
970291AG2-192 GEN
Solar/Wind Harmer
0.71
270005AE1-210 C O1
Solar/Wind Harmer
2.984
965031AG1-367 GEN
Solar/Wind Harmer
5.46
940581AE2-045 GEN
Solar/Wind Harmer
5.521
970615AG2-402 GEN
50/50
4.08
246938BC-WTG3
Solar/Wind Harmer
15.573
246937BC-WTG2
Solar/Wind Harmer
15.308
970611AG2-400 GEN
Solar/Wind Harmer
17.544
942221AE2-234 GEN
Solar/Wind Harmer
0.577
247620Y3-023
Adder
0.339
944541AF1-119 GEN
Solar/Wind Harmer
2.967
960971AF2-388 GEN
Solar/Wind Harmer
7.744
270216AD2-079_GEN
Solar/Wind Harmer
0.407
960981AF2-389 GEN
Solar/Wind Harmer
0.946
957891AF2-083 GEN
Solar/Wind Harmer
2.109
961051AF2-396 GEN
Solar/Wind Harmer
9.834
961051AF2-396 GEN
Solar/Wind Harmer
4.574
270599AE1-208 GEN
Solar/Wind Harmer
4.982
270031AE2-169
Solar/Wind Harmer
4.982
270526AF1-158 GEN
Solar/Wind Harmer
2.751
24441505OLIV SLR
Solar/Wind Harmer
0.08
965681AG1-436 GEN
Solar/Wind Harmer
7.311
965791AG1-447 GEN
Solar/Wind Harmer
3.741
274808UNIV PK N;4U
Adder
2.77
970321AG2-212 GEN
Solar/Wind Harmer
9.898
274770LINCOLN ;1U
Adder
3.407
274771LINCOLN ;2U
Adder
3.407
274803UNIV PARK;6U
Adder
3.202
274888KELLY CRK;1U
Solar/Wind Harmer
3.226
274887GEN-1.85
Solar/Wind Harmer
2.912
276843GEN-1.7
Solar/Wind Harmer
0.313
958011AF2-095 GEN
Solar/Wind Harmer
7.868
972259AH1-714 GEN
Adder
10.344
274674JOLIET 9 ;6U
Adder
8.306
274847GR RIDGE ;BU
Solar/Wind Harmer
2.711
960441AF2-335 GEN
Solar/Wind Harmer
5.354
945421AF1-207 GEN
Solar/Wind Harmer
7.47
957841AF2-078 GEN
Solar/Wind Harmer
3.215
970825AG2-519 GEN
Solar/Wind Harmer
5.598
958481AF2-142 GEN
Solar/Wind Harmer
7.952
274861TOP CROP ;1U
Solar/Wind Harmer
3.211
274862TOP CROP ;2U
Solar/Wind Harmer
2.682
971573AH1-285 GEN
Solar/Wind Harmer
4.556
274696ROCKY RD ;4P
Adder
6.006
274695ROCKY RD ;2P
Adder
5.867
274693ROCKY RD ;1P
Adder
5.81
274697ROCKY RD ;3P
Adder
1.594
274683WAUKEGAN ;8U
Adder
11.09
274683WAUKEGAN ;8U
Adder
9.349
958491AF2-143 GEN
Solar/Wind Harmer
7.857
962691AG1-118 GEN
Solar/Wind Harmer
15.688
247621Y3-024
Adder
0.122
274764LEE CO EC;5U
Adder
4.693
274765LEE CO EC;6U
Adder
4.693
274762LEE CO EC;3U
Adder
4.682
274763LEE CO EC;4U
Adder
4.638
972267AH1-718 GEN
Adder
2.076
270224U2-072_GEN2
Solar/Wind Helper
1.022
270227U2-072_GEN3
Solar/Wind Helper
1.022
270228U2-072_GEN4
Solar/Wind Helper
1.022
270231U2-072_GEN5
Solar/Wind Helper
1.022
270471AD2-092_GEN
Solar/Wind Helper
1.204
253378AE2-206_GEN
Solar/Wind Helper
0.844
276820AF1-078_GEN
Solar/Wind Helper
0.395
241960AC2-195 GEN
Solar/Wind Helper
0.84
965431AG1-411 GEN
50/50
43.085
24727105RPMNG2
50/50
3.126
970583AG2-370 GEN
50/50
2.329
270491AE1-102 GEN2
Solar/Wind Harmer
5.086
959331AF2-224 GEN
Solar/Wind Harmer
17.544
965021AG1-366 GEN
Solar/Wind Harmer
4.08
970031AG2-029 GEN
Solar/Wind Harmer
29.774
270043AE2-236 GEN
Solar/Wind Harmer
5.156
270191TR4_S_V150
Solar/Wind Harmer
2.486
270247TR4_N_V136
Solar/Wind Harmer
0.705
944531AF1-118 GEN
Solar/Wind Harmer
28.001
971617AH1-308 GEN
Solar/Wind Harmer
4.158
247643Z2-116 C
Solar/Wind Harmer
0.047
945111AF1-176 GEN
Solar/Wind Harmer
3.621
24642205MAYFLWER
Adder
0.392
970349AG2-230 GEN
Solar/Wind Harmer
9.176
24441205WTRV SLR C
Solar/Wind Harmer
0.076
972231SS25-0005
Solar/Wind Harmer
5.341
972181SS23-001
Solar/Wind Harmer
3.338
274752CRETE EC ;2U
Adder
2.751
274753CRETE EC ;3U
Adder
2.751
274724RIVER EC ;11
Adder
9.915
270535AF1-215 GEN1
Solar/Wind Harmer
2.537
970513AG2-328 GEN
Solar/Wind Harmer
9.898
970517AG2-330 GEN
Solar/Wind Harmer
8.977
247642Z2-115 C
Solar/Wind Harmer
0.035
964401AG1-302 GEN
Solar/Wind Harmer
5
274772LINCOLN ;3U
Adder
3.407
274802UNIV PARK;5U
Adder
3.202
274826FISK ;BP
Adder
6.004
274800UNIV PARK;3U
Adder
3.191
972038AH1-567 GEN2
Adder
0.2
276772AC2-154 GEN
Solar/Wind Harmer
1.524
276806AD2-047 C O1
Solar/Wind Harmer
5.845
970941AG2-585 GEN
Solar/Wind Harmer
6.83
970289AG2-191 GEN
Solar/Wind Harmer
0.419
970291AG2-192 GEN
Solar/Wind Harmer
0.381
958821AF2-173 GEN
Solar/Wind Harmer
7.644
270004AE1-209 GEN
Solar/Wind Harmer
2.984
247604X1-042
Adder
0.227
959141AF2-205 GEN
Solar/Wind Harmer
3.293
972228AH1-698 GEN2
Adder
2.017
970707AG2-453 GEN
Solar/Wind Harmer
15.157
274676JOLIET 29;8U
Adder
15.996
276897AD1-100 C
Solar/Wind Harmer
15.679
939351AE1-166 GEN
Solar/Wind Harmer
3.204
276893AG1-478 C
Solar/Wind Harmer
0.225
274730ELWOOD EC;6P
Adder
8.865
274734ELWOOD EC;8P
Adder
8.865
274736ELWOOD EC;9P
Adder
8.865
274729ELWOOD EC;1P
Adder
8.864
943121AE2-341 GEN
Solar/Wind Harmer
7.985
943591AF1-030 GEN
Solar/Wind Harmer
5.324
276694AA1-018 GEN2
Solar/Wind Harmer
3.346
274682WAUKEGAN ;7U
Adder
9.47
276805AD2-038 GEN
Solar/Wind Harmer
2.687
972236AH1-702 GEN2
Adder
1.119
274760LEE CO EC;1U
Adder
4.682
274767LEE CO EC;8U
Adder
4.627
270485AE1-090_GEN
Solar/Wind Helper
0.372
942871AE2-306 GEN
Solar/Wind Helper
0.519
270541AE2-072 C
Solar/Wind Helper
1.217
971605AH1-302 GEN
Solar/Wind Harmer
4.721
274676JOLIET 29;8U
Adder
16.588
941551AE2-152 GEN
Solar/Wind Harmer
2.45
270032AE2-172
Solar/Wind Harmer
2.512
274674JOLIET 9 ;6U
Adder
8.306
274732ELWOOD EC;7P
Adder
8.865
274871GR RIDGE ;2U
Solar/Wind Harmer
4.121
274745AC1-111 GEN9
Adder
2.976
970825AG2-519 GEN
Solar/Wind Harmer
1.249
276691AA1-018 GEN1
Solar/Wind Harmer
0.247
274682WAUKEGAN ;7U
Adder
9.47
274828WAUKEGAN ;BP
Adder
5.813
274822ROCKFORD ;11
Adder
10.041
972235AH1-702 GEN1
Adder
1.287
274761LEE CO EC;2U
Adder
4.682
274766LEE CO EC;7U
Adder
4.627
270462AD2-086
Solar/Wind Helper
4.279
270223U2-072_GEN1
Solar/Wind Helper
1.022
270578AF1-285 GEN2
Solar/Wind Helper
0.692
270391AF1-285 GEN3
Solar/Wind Helper
0.692
247522W1-056 GEN
Solar/Wind Helper
1.347
960841AF2-375 GEN
Solar/Wind Helper
1.381
270349AD2-093_GEN
Solar/Wind Helper
1.204
241840AF1-064_GEN
Solar/Wind Helper
0.493
241807AE2-176_GEN
Solar/Wind Helper
0.713
24727205RPMNG3
50/50
3.1
971599AH1-298 GEN
50/50
8.249
957201AF2-014 GEN
Solar/Wind Harmer
17.743
270435AC2-044 GEN
Solar/Wind Harmer
7.824
963791AG1-232 GEN
Solar/Wind Harmer
14
965041AG1-368 GEN
Solar/Wind Harmer
10.016
270071AF1-092 GEN
Solar/Wind Harmer
12.959
965051AG1-369 GEN
Solar/Wind Harmer
4.139
24729505KEY G4
Adder
5.032
270024AE2-089 GEN
Solar/Wind Harmer
3.357
958711AF2-162 GEN
Solar/Wind Harmer
0.717
965101AG1-375 GEN
Solar/Wind Harmer
6.864
945581AF1-223 GEN
Solar/Wind Harmer
2.922
971771AH1-392 GEN
Solar/Wind Harmer
5.656
971347AH1-153 GEN
Solar/Wind Harmer
9.176
971769AH1-391 GEN
Solar/Wind Harmer
6
944161AF1-084 GEN
Solar/Wind Harmer
1.316
960681AF2-359 GEN
Solar/Wind Harmer
2.21
270536AF1-215 GEN2
Solar/Wind Harmer
2.537
274814UNIV PK N;0U
Adder
2.807
274807UNIV PK N;3U
Adder
2.801
274805UNIV PK N;1U
Adder
2.788
274811UNIV PK N;7U
Adder
2.782
274775LINCOLN ;6U
Adder
3.407
274776LINCOLN ;7U
Adder
3.407
274777LINCOLN ;8U
Adder
3.407
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.255
958391AF2-133 GEN
Solar/Wind Harmer
4.967
960591AF2-350 GEN
Solar/Wind Harmer
5.464
965461AG1-414 GEN
Solar/Wind Harmer
1.238
970289AG2-191 GEN
Solar/Wind Harmer
1.038
972227AH1-698 GEN1
Adder
1.42
274687WILL CNTY;4U
Adder
15.145
274687WILL CNTY;4U
Adder
15.145
274675JOLIET 29;7U
Adder
16.588
274675JOLIET 29;7U
Adder
15.996
270594AE1-207 GEN
Solar/Wind Harmer
7.938
274728ELWOOD EC;5P
Adder
8.865
274731ELWOOD EC;2P
Adder
8.864
274733ELWOOD EC;3P
Adder
8.864
274735ELWOOD EC;4P
Adder
8.864
970833AG2-524 GEN
Solar/Wind Harmer
4.682
970833AG2-524 GEN
Solar/Wind Harmer
2.178
970115AG2-085 GEN
Solar/Wind Harmer
2.141
274746AC1-111 G10
Adder
2.976
274744AC1-111 GEN8
Adder
2.976
24690905MDL-1G C
Solar/Wind Harmer
4.193
270180AB1-006 GEN1
Solar/Wind Harmer
3.756
946581AF1-322 GEN
Solar/Wind Harmer
5.343
274823ROCKFORD ;21
Adder
9.968
270317AD1-130_GEN
Solar/Wind Helper
4.74
966831AG1-554 GEN
Solar/Wind Helper
0.998
270284AF1-227 GEN1
Solar/Wind Helper
2.4
270286AF1-227 GEN2
Solar/Wind Helper
0.88
270287AF1-227 GEN3
Solar/Wind Helper
0.88
270499AE1-146 GEN
Solar/Wind Helper
2.29
945641AF1-229 GEN
Solar/Wind Helper
1.103
253383AE2-342_GEN
Solar/Wind Helper
0.406
24691005MDL-2G C
Solar/Wind Harmer
1.875
24697605MDL-3G C
Solar/Wind Harmer
1.869
990497J1323
External Queue
1.411980390548706
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.641
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.161
MECLTFEXP_MEC->PJM
CLTF
7.249
SIGELTFEXP_SIGE->PJM
CLTF
0.148
LAGNLTFEXP_LAGN->PJM
CLTF
4.622
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.381
TVALTFEXP_TVA->PJM
CLTF
1.911
CPLELTFEXP_CPLE->PJM
CLTF
0.15
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.856
NYPJM->LTFIMP_NY
CLTF
1.035
LGEELTFEXP_LGEE->PJM
CLTF
1.297
WECLTFEXP_WEC->PJM
CLTF
1.948
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.16 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2361.89
MW Contribution:29.68
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.09
246938BC-WTG3
Solar/Wind Harmer
15.841
246937BC-WTG2
Solar/Wind Harmer
15.572
970611AG2-400 GEN
Solar/Wind Harmer
17.588
942221AE2-234 GEN
Solar/Wind Harmer
0.574
965431AG1-411 GEN
50/50
43.799
24727105RPMNG2
50/50
3.172
970583AG2-370 GEN
50/50
2.382
270491AE1-102 GEN2
Solar/Wind Harmer
5.173
959331AF2-224 GEN
Solar/Wind Harmer
17.588
965021AG1-366 GEN
Solar/Wind Harmer
4.09
970031AG2-029 GEN
Solar/Wind Harmer
29.683
270043AE2-236 GEN
Solar/Wind Harmer
5.059
270191TR4_S_V150
Solar/Wind Harmer
2.589
270247TR4_N_V136
Solar/Wind Harmer
0.734
944531AF1-118 GEN
Solar/Wind Harmer
26.974
971617AH1-308 GEN
Solar/Wind Harmer
4.191
247643Z2-116 C
Solar/Wind Harmer
0.046
945111AF1-176 GEN
Solar/Wind Harmer
3.597
24642205MAYFLWER
Adder
0.389
970349AG2-230 GEN
Solar/Wind Harmer
8.976
270535AF1-215 GEN1
Solar/Wind Harmer
2.615
964401AG1-302 GEN
Solar/Wind Harmer
5.2
959141AF2-205 GEN
Solar/Wind Harmer
3.453
247642Z2-115 C
Solar/Wind Harmer
0.037
24441205WTRV SLR C
Solar/Wind Harmer
0.076
970513AG2-328 GEN
Solar/Wind Harmer
10.07
970517AG2-330 GEN
Solar/Wind Harmer
9.134
972231SS25-0005
Solar/Wind Harmer
5.32
972181SS23-001
Solar/Wind Harmer
3.325
274752CRETE EC ;2U
Adder
2.74
274753CRETE EC ;3U
Adder
2.74
970289AG2-191 GEN
Solar/Wind Harmer
0.43
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24755605MDL-5G
Solar/Wind Harmer
1.348
970781AG2-491 GEN
Solar/Wind Harmer
5.588
274724RIVER EC ;11
Adder
9.858
247620Y3-023
Adder
0.338
944541AF1-119 GEN
Solar/Wind Harmer
2.87
960971AF2-388 GEN
Solar/Wind Harmer
7.489
270216AD2-079_GEN
Solar/Wind Harmer
0.404
960981AF2-389 GEN
Solar/Wind Harmer
0.939
957891AF2-083 GEN
Solar/Wind Harmer
2.093
961051AF2-396 GEN
Solar/Wind Harmer
9.771
961051AF2-396 GEN
Solar/Wind Harmer
4.545
270599AE1-208 GEN
Solar/Wind Harmer
4.921
270031AE2-169
Solar/Wind Harmer
4.921
270526AF1-158 GEN
Solar/Wind Harmer
2.734
24441505OLIV SLR
Solar/Wind Harmer
0.08
965681AG1-436 GEN
Solar/Wind Harmer
7.281
965791AG1-447 GEN
Solar/Wind Harmer
3.725
945421AF1-207 GEN
Solar/Wind Harmer
7.967
957841AF2-078 GEN
Solar/Wind Harmer
3.428
970321AG2-212 GEN
Solar/Wind Harmer
10.07
274808UNIV PK N;4U
Adder
2.758
274803UNIV PARK;6U
Adder
3.186
274770LINCOLN ;1U
Adder
3.374
274771LINCOLN ;2U
Adder
3.374
274888KELLY CRK;1U
Solar/Wind Harmer
3.21
274887GEN-1.85
Solar/Wind Harmer
2.898
276843GEN-1.7
Solar/Wind Harmer
0.312
958011AF2-095 GEN
Solar/Wind Harmer
7.829
966841AG1-555 GEN
Solar/Wind Harmer
1.357
972259AH1-714 GEN
Adder
10.279
274674JOLIET 9 ;6U
Adder
8.265
970239AG2-162 GEN
Solar/Wind Harmer
5.862
274847GR RIDGE ;BU
Solar/Wind Harmer
2.698
274696ROCKY RD ;4P
Adder
5.974
274695ROCKY RD ;2P
Adder
5.836
274693ROCKY RD ;1P
Adder
5.779
274697ROCKY RD ;3P
Adder
1.585
274683WAUKEGAN ;8U
Adder
11.034
274683WAUKEGAN ;8U
Adder
9.301
247621Y3-024
Adder
0.124
274764LEE CO EC;5U
Adder
4.679
274765LEE CO EC;6U
Adder
4.679
274762LEE CO EC;3U
Adder
4.668
274763LEE CO EC;4U
Adder
4.624
972267AH1-718 GEN
Adder
2.071
270224U2-072_GEN2
Solar/Wind Helper
0.826
270227U2-072_GEN3
Solar/Wind Helper
0.826
270228U2-072_GEN4
Solar/Wind Helper
0.826
270231U2-072_GEN5
Solar/Wind Helper
0.826
253378AE2-206_GEN
Solar/Wind Helper
0.682
276820AF1-078_GEN
Solar/Wind Helper
0.319
274802UNIV PARK;5U
Adder
3.186
274826FISK ;BP
Adder
5.972
247604X1-042
Adder
0.227
274800UNIV PARK;3U
Adder
3.175
972038AH1-567 GEN2
Adder
0.199
274772LINCOLN ;3U
Adder
3.374
276772AC2-154 GEN
Solar/Wind Harmer
1.516
276806AD2-047 C O1
Solar/Wind Harmer
5.816
970941AG2-585 GEN
Solar/Wind Harmer
6.796
972228AH1-698 GEN2
Adder
2.007
276897AD1-100 C
Solar/Wind Harmer
15.614
939351AE1-166 GEN
Solar/Wind Harmer
3.19
274676JOLIET 29;8U
Adder
15.911
276893AG1-478 C
Solar/Wind Harmer
0.224
970707AG2-453 GEN
Solar/Wind Harmer
15.038
274729ELWOOD EC;1P
Adder
8.824
274730ELWOOD EC;6P
Adder
8.825
274734ELWOOD EC;8P
Adder
8.825
274736ELWOOD EC;9P
Adder
8.825
970243AG2-164 GEN
Solar/Wind Harmer
13.763
970519AG2-331 GEN
Solar/Wind Harmer
9.247
970699AG2-449 GEN
Solar/Wind Harmer
6.117
958821AF2-173 GEN
Solar/Wind Harmer
7.467
270004AE1-209 GEN
Solar/Wind Harmer
2.915
274682WAUKEGAN ;7U
Adder
9.422
972236AH1-702 GEN2
Adder
1.114
274760LEE CO EC;1U
Adder
4.668
274767LEE CO EC;8U
Adder
4.613
270485AE1-090_GEN
Solar/Wind Helper
0.312
942871AE2-306 GEN
Solar/Wind Helper
0.42
270541AE2-072 C
Solar/Wind Helper
1.043
24727205RPMNG3
50/50
3.146
971599AH1-298 GEN
50/50
7.919
957201AF2-014 GEN
Solar/Wind Harmer
18.048
270435AC2-044 GEN
Solar/Wind Harmer
7.959
963791AG1-232 GEN
Solar/Wind Harmer
14.071
965041AG1-368 GEN
Solar/Wind Harmer
10.243
965051AG1-369 GEN
Solar/Wind Harmer
4.31
270071AF1-092 GEN
Solar/Wind Harmer
12.825
24729505KEY G4
Adder
4.853
270024AE2-089 GEN
Solar/Wind Harmer
3.384
958711AF2-162 GEN
Solar/Wind Harmer
0.693
965101AG1-375 GEN
Solar/Wind Harmer
6.646
945581AF1-223 GEN
Solar/Wind Harmer
2.836
971771AH1-392 GEN
Solar/Wind Harmer
5.607
971347AH1-153 GEN
Solar/Wind Harmer
8.976
971769AH1-391 GEN
Solar/Wind Harmer
5.966
944161AF1-084 GEN
Solar/Wind Harmer
1.309
960681AF2-359 GEN
Solar/Wind Harmer
2.201
270536AF1-215 GEN2
Solar/Wind Harmer
2.615
958391AF2-133 GEN
Solar/Wind Harmer
5.189
965461AG1-414 GEN
Solar/Wind Harmer
1.269
970289AG2-191 GEN
Solar/Wind Harmer
1.063
24690905MDL-1G C
Solar/Wind Harmer
4.487
270180AB1-006 GEN1
Solar/Wind Harmer
4.019
946581AF1-322 GEN
Solar/Wind Harmer
5.718
24691005MDL-2G C
Solar/Wind Harmer
2.067
24697605MDL-3G C
Solar/Wind Harmer
2.06
24697905MDL-4G C
Solar/Wind Harmer
1.283
270181AB1-006 GEN2
Solar/Wind Harmer
0.4
274814UNIV PK N;0U
Adder
2.794
274807UNIV PK N;3U
Adder
2.788
274805UNIV PK N;1U
Adder
2.776
274811UNIV PK N;7U
Adder
2.77
270594AE1-207 GEN
Solar/Wind Harmer
8.07
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.232
274775LINCOLN ;6U
Adder
3.374
274776LINCOLN ;7U
Adder
3.374
274777LINCOLN ;8U
Adder
3.374
960591AF2-350 GEN
Solar/Wind Harmer
5.437
972227AH1-698 GEN1
Adder
1.413
24386205FR-12G C
Solar/Wind Harmer
2.318
24386405FR-21G C
Solar/Wind Harmer
2.326
24386605FR-22G C
Solar/Wind Harmer
2.326
24387005FR-3G C
Solar/Wind Harmer
2.14
274687WILL CNTY;4U
Adder
15.065
274687WILL CNTY;4U
Adder
15.065
274675JOLIET 29;7U
Adder
16.5
274675JOLIET 29;7U
Adder
15.911
274731ELWOOD EC;2P
Adder
8.824
274733ELWOOD EC;3P
Adder
8.824
274735ELWOOD EC;4P
Adder
8.824
274728ELWOOD EC;5P
Adder
8.825
970833AG2-524 GEN
Solar/Wind Harmer
4.66
970833AG2-524 GEN
Solar/Wind Harmer
2.168
274746AC1-111 G10
Adder
2.958
274744AC1-111 GEN8
Adder
2.958
274823ROCKFORD ;21
Adder
9.927
270317AD1-130_GEN
Solar/Wind Helper
3.975
966831AG1-554 GEN
Solar/Wind Helper
0.878
270499AE1-146 GEN
Solar/Wind Helper
2.015
270284AF1-227 GEN1
Solar/Wind Helper
1.598
270286AF1-227 GEN2
Solar/Wind Helper
0.586
270287AF1-227 GEN3
Solar/Wind Helper
0.586
945641AF1-229 GEN
Solar/Wind Helper
0.942
24727005RPMNG1
50/50
3.161
960861AF2-377 GEN
50/50
2.009
246936BC-WTG1
Solar/Wind Harmer
15.572
270489AE1-102 GEN1
Solar/Wind Harmer
5.173
965421AG1-410 GEN
Solar/Wind Harmer
113.002
965011AG1-365 GEN
Solar/Wind Harmer
17.588
247521TR3_G114
Solar/Wind Harmer
2.902
270246TR4_N_V150
Solar/Wind Harmer
0.734
270063AE2-323 C
Solar/Wind Harmer
1.864
944231AF1-091 GEN
Solar/Wind Harmer
3.053
24695305TIMB G C
Solar/Wind Harmer
4.082
24639705ELKHART HY
Adder
0.108
965651AG1-433 GEN
Solar/Wind Harmer
3.744
958861AF2-177 GEN
Solar/Wind Harmer
7.264
945111AF1-176 GEN
Solar/Wind Harmer
11.349
945371AF1-202 GEN
Solar/Wind Harmer
4.363
270505AE1-170 C O1
Solar/Wind Harmer
9.21
270449AD2-020 GEN
Solar/Wind Harmer
1.691
943021AE2-325 GEN
Solar/Wind Harmer
2.198
970373AG2-245 GEN
Solar/Wind Harmer
12.138
270055AF2-134 C O1
Solar/Wind Harmer
1.743
958381AF2-132 GEN
Solar/Wind Harmer
5.2
964861AG1-349 GEN
Solar/Wind Harmer
4.503
971917AH1-482 GEN
Solar/Wind Harmer
5.197
940581AE2-045 GEN
Solar/Wind Harmer
5.815
971605AH1-302 GEN
Solar/Wind Harmer
4.972
970245AG2-165 GEN
Solar/Wind Harmer
10.07
274751CRETE EC ;1U
Adder
2.74
274754CRETE EC ;4U
Adder
2.74
970291AG2-192 GEN
Solar/Wind Harmer
0.728
24791305MDL-5G
Solar/Wind Harmer
1.348
274723RIVER EC ;12
Adder
9.982
274812UNIV PK N;8U
Adder
2.77
276164X3-005 C
Solar/Wind Harmer
0.387
270032AE2-172
Solar/Wind Harmer
2.554
274801UNIV PARK;4U
Adder
3.175
972207SS24-0001
Solar/Wind Harmer
11.996
274773LINCOLN ;4U
Adder
3.374
274774LINCOLN ;5U
Adder
3.374
276776AD2-060 GEN
Solar/Wind Harmer
0.23
24385905FR-11G C
Solar/Wind Harmer
4.495
24387305FR-4G C
Solar/Wind Harmer
2.748
941551AE2-152 GEN
Solar/Wind Harmer
2.44
274676JOLIET 29;8U
Adder
16.5
274732ELWOOD EC;7P
Adder
8.825
274674JOLIET 9 ;6U
Adder
8.265
970333AG2-219 GEN
Solar/Wind Harmer
16.822
274871GR RIDGE ;2U
Solar/Wind Harmer
4.102
270005AE1-210 C O1
Solar/Wind Harmer
2.915
274745AC1-111 GEN9
Adder
2.958
274682WAUKEGAN ;7U
Adder
9.422
274828WAUKEGAN ;BP
Adder
5.784
274822ROCKFORD ;11
Adder
10
972235AH1-702 GEN1
Adder
1.282
274761LEE CO EC;2U
Adder
4.668
274766LEE CO EC;7U
Adder
4.613
970091AG2-072 GEN
Adder
37.434
270462AD2-086
Solar/Wind Helper
3.588
270223U2-072_GEN1
Solar/Wind Helper
0.826
270578AF1-285 GEN2
Solar/Wind Helper
0.559
270391AF1-285 GEN3
Solar/Wind Helper
0.559
247522W1-056 GEN
Solar/Wind Helper
1.183
960841AF2-375 GEN
Solar/Wind Helper
1.212
965031AG1-367 GEN
Solar/Wind Harmer
3.001
944201AF1-088_MTX
Adder
51.989
957141AF2-008_MTX
Adder
9.293
990497J1323
External Queue
1.3854676485061646
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.017
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.009
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.025
MECLTFEXP_MEC->PJM
CLTF
7.23
SIGELTFEXP_SIGE->PJM
CLTF
0.147
LAGNLTFEXP_LAGN->PJM
CLTF
4.179
TVALTFEXP_TVA->PJM
CLTF
1.622
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.017
NYPJM->LTFIMP_NY
CLTF
0.995
LGEELTFEXP_LGEE->PJM
CLTF
1.047
WECLTFEXP_WEC->PJM
CLTF
1.939
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.127
AG2-052LTFEXP_AG2-052->PJM
LTF
0.129
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.19 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5599.56
MW Contribution:37.15
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.03
270100X2-052 CT1
50/50
1.87
270101X2-052 CT2
50/50
1.87
970321AG2-212 GEN
Solar/Wind Harmer
23.63
965681AG1-436 GEN
Solar/Wind Harmer
15.817
965791AG1-447 GEN
Solar/Wind Harmer
8.092
274770LINCOLN ;1U
Adder
7.811
274771LINCOLN ;2U
Adder
7.811
270526AF1-158 GEN
Solar/Wind Harmer
5.718
24441505OLIV SLR
Solar/Wind Harmer
0.169
270216AD2-079_GEN
Solar/Wind Harmer
0.761
274808UNIV PK N;4U
Adder
6.203
957891AF2-083 GEN
Solar/Wind Harmer
4.193
972259AH1-714 GEN
Adder
23.715
960981AF2-389 GEN
Solar/Wind Harmer
1.879
247620Y3-023
Adder
0.572
274803UNIV PARK;6U
Adder
7.24
274888KELLY CRK;1U
Solar/Wind Harmer
7.331
274887GEN-1.85
Solar/Wind Harmer
6.619
276843GEN-1.7
Solar/Wind Harmer
0.712
958011AF2-095 GEN
Solar/Wind Harmer
17.882
274674JOLIET 9 ;6U
Adder
19.027
961051AF2-396 GEN
Solar/Wind Harmer
19.603
961051AF2-396 GEN
Solar/Wind Harmer
9.118
274847GR RIDGE ;BU
Solar/Wind Harmer
6.245
971573AH1-285 GEN
Solar/Wind Harmer
10.565
970611AG2-400 GEN
Solar/Wind Harmer
12.268
274696ROCKY RD ;4P
Adder
13.939
274695ROCKY RD ;2P
Adder
13.618
274693ROCKY RD ;1P
Adder
13.484
274697ROCKY RD ;3P
Adder
3.699
958481AF2-142 GEN
Solar/Wind Harmer
18.335
274861TOP CROP ;1U
Solar/Wind Harmer
7.405
274862TOP CROP ;2U
Solar/Wind Harmer
6.183
274683WAUKEGAN ;8U
Adder
25.73
274683WAUKEGAN ;8U
Adder
21.689
962691AG1-118 GEN
Solar/Wind Harmer
36.56
970921AG2-575 GEN
Solar/Wind Harmer
12.17
970921AG2-575 GEN
Solar/Wind Harmer
2.83
958491AF2-143 GEN
Solar/Wind Harmer
18.224
274879MINONK ;1U
Solar/Wind Harmer
8.18
942991AE2-321 GEN
Solar/Wind Harmer
12.121
971333AH1-146 GEN
Solar/Wind Harmer
24.178
971335AH1-147 GEN
Solar/Wind Harmer
24.178
274764LEE CO EC;5U
Adder
11.118
274765LEE CO EC;6U
Adder
11.118
274762LEE CO EC;3U
Adder
11.092
274763LEE CO EC;4U
Adder
10.988
972267AH1-718 GEN
Adder
4.939
247621Y3-024
Adder
0.249
24721605FLATG1
50/50
1.712
971599AH1-298 GEN
50/50
11.939
962771AG1-126 GEN
Solar/Wind Harmer
88.009
971347AH1-153 GEN
Solar/Wind Harmer
19.74
270071AF1-092 GEN
Solar/Wind Harmer
19.263
960681AF2-359 GEN
Solar/Wind Harmer
4.78
274775LINCOLN ;6U
Adder
7.811
274776LINCOLN ;7U
Adder
7.811
274777LINCOLN ;8U
Adder
7.811
971771AH1-392 GEN
Solar/Wind Harmer
11.34
971769AH1-391 GEN
Solar/Wind Harmer
12.581
24729505KEY G4
Adder
8.072
274814UNIV PK N;0U
Adder
6.285
274807UNIV PK N;3U
Adder
6.271
274805UNIV PK N;1U
Adder
6.244
274811UNIV PK N;7U
Adder
6.23
274827FISK ;RP
Adder
9.635
972037AH1-567 GEN1
Adder
0.227
960591AF2-350 GEN
Solar/Wind Harmer
12.418
972227AH1-698 GEN1
Adder
3.239
274687WILL CNTY;4U
Adder
34.573
274687WILL CNTY;4U
Adder
34.573
274675JOLIET 29;7U
Adder
37.943
274675JOLIET 29;7U
Adder
36.588
274731ELWOOD EC;2P
Adder
20.304
274733ELWOOD EC;3P
Adder
20.304
274735ELWOOD EC;4P
Adder
20.304
274728ELWOOD EC;5P
Adder
20.304
970833AG2-524 GEN
Solar/Wind Harmer
10.782
970833AG2-524 GEN
Solar/Wind Harmer
5.015
274746AC1-111 G10
Adder
6.879
274744AC1-111 GEN8
Adder
6.879
270536AF1-215 GEN2
Solar/Wind Harmer
5.59
944161AF1-084 GEN
Solar/Wind Harmer
2.707
958391AF2-133 GEN
Solar/Wind Harmer
11.03
276868AE1-113 GEN
Solar/Wind Harmer
12.269
276882AE2-255 GEN
Solar/Wind Harmer
4.09
971177AH1-047 GEN
Solar/Wind Harmer
7.102
971675AH1-338 GEN
Solar/Wind Harmer
21.77
971411AH1-196 GEN
Solar/Wind Harmer
18.14
274863CRW1-WTG
Solar/Wind Harmer
6.746
274864CRW2-WTG
Solar/Wind Harmer
6.746
274823ROCKFORD ;21
Adder
23.439
24721805FLATG3
50/50
1.712
24721705FLATG2
50/50
31.388
24344105CKG2
50/50
10.173
962761AG1-125 GEN
Solar/Wind Harmer
88.009
970149AG2-104 GEN
Solar/Wind Harmer
108.691
970155AG2-107 GEN
Solar/Wind Harmer
38.376
970245AG2-165 GEN
Solar/Wind Harmer
23.63
972207SS24-0001
Solar/Wind Harmer
27.773
274773LINCOLN ;4U
Adder
7.811
274774LINCOLN ;5U
Adder
7.811
274723RIVER EC ;12
Adder
22.373
24639705ELKHART HY
Adder
0.192
276164X3-005 C
Solar/Wind Harmer
0.876
274751CRETE EC ;1U
Adder
6.093
274754CRETE EC ;4U
Adder
6.093
274812UNIV PK N;8U
Adder
6.23
270063AE2-323 C
Solar/Wind Harmer
2.741
270505AE1-170 C O1
Solar/Wind Harmer
18.655
276776AD2-060 GEN
Solar/Wind Harmer
0.525
274801UNIV PARK;4U
Adder
7.237
970373AG2-245 GEN
Solar/Wind Harmer
26.061
945111AF1-176 GEN
Solar/Wind Harmer
22.129
941551AE2-152 GEN
Solar/Wind Harmer
5.622
274676JOLIET 29;8U
Adder
37.943
274674JOLIET 9 ;6U
Adder
19.027
274732ELWOOD EC;7P
Adder
20.304
274871GR RIDGE ;2U
Solar/Wind Harmer
9.495
270449AD2-020 GEN
Solar/Wind Harmer
3.453
943021AE2-325 GEN
Solar/Wind Harmer
4.486
274745AC1-111 GEN9
Adder
6.879
270055AF2-134 C O1
Solar/Wind Harmer
3.726
965011AG1-365 GEN
Solar/Wind Harmer
12.268
276691AA1-018 GEN1
Solar/Wind Harmer
0.569
274682WAUKEGAN ;7U
Adder
21.959
274828WAUKEGAN ;BP
Adder
13.487
24722005FLATG5
50/50
1.712
24721905FLATG4
50/50
31.388
970153AG2-106 GEN
Solar/Wind Harmer
38.376
970513AG2-328 GEN
Solar/Wind Harmer
23.63
970517AG2-330 GEN
Solar/Wind Harmer
21.432
970349AG2-230 GEN
Solar/Wind Harmer
19.74
270043AE2-236 GEN
Solar/Wind Harmer
7.114
274772LINCOLN ;3U
Adder
7.811
944531AF1-118 GEN
Solar/Wind Harmer
44.088
247643Z2-116 C
Solar/Wind Harmer
0.088
274724RIVER EC ;11
Adder
22.115
24642205MAYFLWER
Adder
0.793
972231SS25-0005
Solar/Wind Harmer
11.831
972181SS23-001
Solar/Wind Harmer
7.394
274752CRETE EC ;2U
Adder
6.093
274753CRETE EC ;3U
Adder
6.093
970707AG2-453 GEN
Solar/Wind Harmer
34.896
274826FISK ;BP
Adder
13.595
274802UNIV PARK;5U
Adder
7.24
276772AC2-154 GEN
Solar/Wind Harmer
3.463
276806AD2-047 C O1
Solar/Wind Harmer
13.284
970941AG2-585 GEN
Solar/Wind Harmer
15.522
972228AH1-698 GEN2
Adder
4.599
274800UNIV PARK;3U
Adder
7.237
972038AH1-567 GEN2
Adder
0.453
945111AF1-176 GEN
Solar/Wind Harmer
7.013
276897AD1-100 C
Solar/Wind Harmer
35.973
939351AE1-166 GEN
Solar/Wind Harmer
7.35
970031AG2-029 GEN
Solar/Wind Harmer
37.15
274676JOLIET 29;8U
Adder
36.588
274729ELWOOD EC;1P
Adder
20.304
274730ELWOOD EC;6P
Adder
20.304
274734ELWOOD EC;8P
Adder
20.304
274736ELWOOD EC;9P
Adder
20.304
276893AG1-478 C
Solar/Wind Harmer
0.516
943121AE2-341 GEN
Solar/Wind Harmer
18.483
943591AF1-030 GEN
Solar/Wind Harmer
12.322
270535AF1-215 GEN1
Solar/Wind Harmer
5.59
959331AF2-224 GEN
Solar/Wind Harmer
12.268
965021AG1-366 GEN
Solar/Wind Harmer
2.853
276694AA1-018 GEN2
Solar/Wind Harmer
7.714
274682WAUKEGAN ;7U
Adder
21.959
964401AG1-302 GEN
Solar/Wind Harmer
11.074
274872LEEDK;1U
Solar/Wind Harmer
0.311
276805AD2-038 GEN
Solar/Wind Harmer
6.233
959141AF2-205 GEN
Solar/Wind Harmer
7.329
24441205WTRV SLR C
Solar/Wind Harmer
0.163
276799AD1-013 GEN
Solar/Wind Harmer
2.674
946671AF1-331 GEN
Solar/Wind Harmer
0.506
274855GSG-6 ;RU
Solar/Wind Harmer
4.467
274850MENDOTA H;RU
Solar/Wind Harmer
3.106
276602WESTBROOK C
Solar/Wind Harmer
2.571
276863AD2-134 GEN
Solar/Wind Harmer
2.16
972236AH1-702 GEN2
Adder
2.633
247604X1-042
Adder
0.499
274760LEE CO EC;1U
Adder
11.092
274767LEE CO EC;8U
Adder
10.962
24728705AND G3
Adder
5.203
958381AF2-132 GEN
Solar/Wind Harmer
11.074
964861AG1-349 GEN
Solar/Wind Harmer
9.588
971917AH1-482 GEN
Solar/Wind Harmer
11.064
939401AE1-172 GEN
Solar/Wind Harmer
16.965
960751AF2-366 GEN
Solar/Wind Harmer
3.492
962781AG1-127 GEN
Solar/Wind Harmer
11.574
274872LEEDK;1U
Solar/Wind Harmer
9.985
276901AD2-066 C O1
Solar/Wind Harmer
4.267
971997AH1-543 GEN
Solar/Wind Harmer
19.076
276861AD2-134 GEN
Solar/Wind Harmer
2.16
274822ROCKFORD ;11
Adder
23.61
972235AH1-702 GEN1
Adder
3.028
274761LEE CO EC;2U
Adder
11.092
274766LEE CO EC;7U
Adder
10.962
940581AE2-045 GEN
Solar/Wind Harmer
2.548
971605AH1-302 GEN
Solar/Wind Harmer
2.178
944201AF1-088_MTX
Adder
120.897
957141AF2-008_MTX
Adder
60.448
CBM West 1LTFEXP_CBM-W1->PJM
CBM
147.549
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.127
MECLTFEXP_MEC->PJM
CLTF
18.475
SIGELTFEXP_SIGE->PJM
CLTF
0.494
LAGNLTFEXP_LAGN->PJM
CLTF
16.558
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.028
TVALTFEXP_TVA->PJM
CLTF
7.884
CPLELTFEXP_CPLE->PJM
CLTF
3.179
CBM West 2LTFEXP_CBM-W2->PJM
CBM
122.482
NYPJM->LTFIMP_NY
CLTF
3.943
LGEELTFEXP_LGEE->PJM
CLTF
5.944
WECLTFEXP_WEC->PJM
CLTF
4.587
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.425

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.22 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5476.65
MW Contribution:37.43
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.723
24721905FLATG4
50/50
31.59
970153AG2-106 GEN
Solar/Wind Harmer
38.507
970513AG2-328 GEN
Solar/Wind Harmer
23.794
970517AG2-330 GEN
Solar/Wind Harmer
21.581
970349AG2-230 GEN
Solar/Wind Harmer
19.878
270043AE2-236 GEN
Solar/Wind Harmer
7.165
274772LINCOLN ;3U
Adder
7.868
944531AF1-118 GEN
Solar/Wind Harmer
44.412
247643Z2-116 C
Solar/Wind Harmer
0.088
274724RIVER EC ;11
Adder
22.277
24642205MAYFLWER
Adder
0.799
972231SS25-0005
Solar/Wind Harmer
11.918
972181SS23-001
Solar/Wind Harmer
7.449
274752CRETE EC ;2U
Adder
6.138
274753CRETE EC ;3U
Adder
6.138
970707AG2-453 GEN
Solar/Wind Harmer
35.152
274826FISK ;BP
Adder
13.696
274802UNIV PARK;5U
Adder
7.293
972228AH1-698 GEN2
Adder
4.633
276772AC2-154 GEN
Solar/Wind Harmer
3.489
276806AD2-047 C O1
Solar/Wind Harmer
13.382
970941AG2-585 GEN
Solar/Wind Harmer
15.637
274800UNIV PARK;3U
Adder
7.291
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.065
276897AD1-100 C
Solar/Wind Harmer
36.239
939351AE1-166 GEN
Solar/Wind Harmer
7.405
970031AG2-029 GEN
Solar/Wind Harmer
37.426
274676JOLIET 29;8U
Adder
36.859
274729ELWOOD EC;1P
Adder
20.454
274730ELWOOD EC;6P
Adder
20.454
274734ELWOOD EC;8P
Adder
20.454
274736ELWOOD EC;9P
Adder
20.454
276893AG1-478 C
Solar/Wind Harmer
0.52
943121AE2-341 GEN
Solar/Wind Harmer
18.62
943591AF1-030 GEN
Solar/Wind Harmer
12.414
270535AF1-215 GEN1
Solar/Wind Harmer
5.632
959331AF2-224 GEN
Solar/Wind Harmer
12.36
965021AG1-366 GEN
Solar/Wind Harmer
2.874
276694AA1-018 GEN2
Solar/Wind Harmer
7.772
274682WAUKEGAN ;7U
Adder
22.124
964401AG1-302 GEN
Solar/Wind Harmer
11.158
274872LEEDK;1U
Solar/Wind Harmer
0.313
276805AD2-038 GEN
Solar/Wind Harmer
6.28
959141AF2-205 GEN
Solar/Wind Harmer
7.384
24441205WTRV SLR C
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
2.695
24721805FLATG3
50/50
1.723
24721705FLATG2
50/50
31.59
24344105CKG2
50/50
10.242
962761AG1-125 GEN
Solar/Wind Harmer
88.31
970149AG2-104 GEN
Solar/Wind Harmer
109.063
970155AG2-107 GEN
Solar/Wind Harmer
38.507
970245AG2-165 GEN
Solar/Wind Harmer
23.794
972207SS24-0001
Solar/Wind Harmer
27.975
274773LINCOLN ;4U
Adder
7.868
274774LINCOLN ;5U
Adder
7.868
274723RIVER EC ;12
Adder
22.538
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0.882
274751CRETE EC ;1U
Adder
6.138
274754CRETE EC ;4U
Adder
6.138
274812UNIV PK N;8U
Adder
6.276
270063AE2-323 C
Solar/Wind Harmer
2.761
270505AE1-170 C O1
Solar/Wind Harmer
18.792
276776AD2-060 GEN
Solar/Wind Harmer
0.529
274801UNIV PARK;4U
Adder
7.291
970373AG2-245 GEN
Solar/Wind Harmer
26.254
945111AF1-176 GEN
Solar/Wind Harmer
22.293
941551AE2-152 GEN
Solar/Wind Harmer
5.664
274676JOLIET 29;8U
Adder
38.224
274674JOLIET 9 ;6U
Adder
19.168
274732ELWOOD EC;7P
Adder
20.454
274871GR RIDGE ;2U
Solar/Wind Harmer
9.565
270449AD2-020 GEN
Solar/Wind Harmer
3.478
943021AE2-325 GEN
Solar/Wind Harmer
4.52
274745AC1-111 GEN9
Adder
6.931
270055AF2-134 C O1
Solar/Wind Harmer
3.754
965011AG1-365 GEN
Solar/Wind Harmer
12.36
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274682WAUKEGAN ;7U
Adder
22.124
274828WAUKEGAN ;BP
Adder
13.588
958381AF2-132 GEN
Solar/Wind Harmer
11.158
964861AG1-349 GEN
Solar/Wind Harmer
9.66
971917AH1-482 GEN
Solar/Wind Harmer
11.148
939401AE1-172 GEN
Solar/Wind Harmer
17.093
960751AF2-366 GEN
Solar/Wind Harmer
3.518
962781AG1-127 GEN
Solar/Wind Harmer
11.661
274872LEEDK;1U
Solar/Wind Harmer
10.06
276901AD2-066 C O1
Solar/Wind Harmer
4.299
971997AH1-543 GEN
Solar/Wind Harmer
19.22
276861AD2-134 GEN
Solar/Wind Harmer
2.176
274822ROCKFORD ;11
Adder
23.79
972235AH1-702 GEN1
Adder
3.052
274761LEE CO EC;2U
Adder
11.177
274766LEE CO EC;7U
Adder
11.046
946671AF1-331 GEN
Solar/Wind Harmer
0.51
274855GSG-6 ;RU
Solar/Wind Harmer
4.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.129
276602WESTBROOK C
Solar/Wind Harmer
2.591
276863AD2-134 GEN
Solar/Wind Harmer
2.176
972236AH1-702 GEN2
Adder
2.653
247604X1-042
Adder
0.503
274760LEE CO EC;1U
Adder
11.177
274767LEE CO EC;8U
Adder
11.046
24728705AND G3
Adder
5.25
940581AE2-045 GEN
Solar/Wind Harmer
2.567
971605AH1-302 GEN
Solar/Wind Harmer
2.195
270102X2-052 ST
50/50
2.044
270100X2-052 CT1
50/50
1.884
270101X2-052 CT2
50/50
1.884
970321AG2-212 GEN
Solar/Wind Harmer
23.794
965681AG1-436 GEN
Solar/Wind Harmer
15.932
965791AG1-447 GEN
Solar/Wind Harmer
8.151
274770LINCOLN ;1U
Adder
7.868
274771LINCOLN ;2U
Adder
7.868
270526AF1-158 GEN
Solar/Wind Harmer
5.76
24441505OLIV SLR
Solar/Wind Harmer
0.17
270216AD2-079_GEN
Solar/Wind Harmer
0.767
274808UNIV PK N;4U
Adder
6.249
957891AF2-083 GEN
Solar/Wind Harmer
4.224
972259AH1-714 GEN
Adder
23.89
960981AF2-389 GEN
Solar/Wind Harmer
1.893
247620Y3-023
Adder
0.576
274803UNIV PARK;6U
Adder
7.293
274888KELLY CRK;1U
Solar/Wind Harmer
7.386
274887GEN-1.85
Solar/Wind Harmer
6.668
276843GEN-1.7
Solar/Wind Harmer
0.717
958011AF2-095 GEN
Solar/Wind Harmer
18.014
274674JOLIET 9 ;6U
Adder
19.168
961051AF2-396 GEN
Solar/Wind Harmer
19.749
961051AF2-396 GEN
Solar/Wind Harmer
9.185
274847GR RIDGE ;BU
Solar/Wind Harmer
6.292
971573AH1-285 GEN
Solar/Wind Harmer
10.643
970611AG2-400 GEN
Solar/Wind Harmer
12.36
274695ROCKY RD ;2P
Adder
13.72
274693ROCKY RD ;1P
Adder
13.585
274697ROCKY RD ;3P
Adder
3.727
274696ROCKY RD ;4P
Adder
14.044
958481AF2-142 GEN
Solar/Wind Harmer
18.473
274861TOP CROP ;1U
Solar/Wind Harmer
7.461
274862TOP CROP ;2U
Solar/Wind Harmer
6.23
274683WAUKEGAN ;8U
Adder
25.923
274683WAUKEGAN ;8U
Adder
21.852
962691AG1-118 GEN
Solar/Wind Harmer
36.835
970921AG2-575 GEN
Solar/Wind Harmer
12.262
970921AG2-575 GEN
Solar/Wind Harmer
2.852
958491AF2-143 GEN
Solar/Wind Harmer
18.361
274879MINONK ;1U
Solar/Wind Harmer
8.242
942991AE2-321 GEN
Solar/Wind Harmer
12.213
971333AH1-146 GEN
Solar/Wind Harmer
24.361
971335AH1-147 GEN
Solar/Wind Harmer
24.361
274764LEE CO EC;5U
Adder
11.204
274765LEE CO EC;6U
Adder
11.204
274762LEE CO EC;3U
Adder
11.177
274763LEE CO EC;4U
Adder
11.072
972267AH1-718 GEN
Adder
4.977
247621Y3-024
Adder
0.251
24721605FLATG1
50/50
1.723
971599AH1-298 GEN
50/50
12.019
962771AG1-126 GEN
Solar/Wind Harmer
88.31
971347AH1-153 GEN
Solar/Wind Harmer
19.878
270071AF1-092 GEN
Solar/Wind Harmer
19.402
960681AF2-359 GEN
Solar/Wind Harmer
4.815
274775LINCOLN ;6U
Adder
7.868
274776LINCOLN ;7U
Adder
7.868
274777LINCOLN ;8U
Adder
7.868
971771AH1-392 GEN
Solar/Wind Harmer
11.423
971769AH1-391 GEN
Solar/Wind Harmer
12.673
24729505KEY G4
Adder
8.132
274814UNIV PK N;0U
Adder
6.331
274807UNIV PK N;3U
Adder
6.318
274805UNIV PK N;1U
Adder
6.29
274811UNIV PK N;7U
Adder
6.276
274827FISK ;RP
Adder
9.706
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
12.509
972227AH1-698 GEN1
Adder
3.263
274687WILL CNTY;4U
Adder
34.83
274687WILL CNTY;4U
Adder
34.83
274675JOLIET 29;7U
Adder
38.225
274675JOLIET 29;7U
Adder
36.86
274731ELWOOD EC;2P
Adder
20.454
274733ELWOOD EC;3P
Adder
20.454
274735ELWOOD EC;4P
Adder
20.454
274728ELWOOD EC;5P
Adder
20.454
970833AG2-524 GEN
Solar/Wind Harmer
10.862
970833AG2-524 GEN
Solar/Wind Harmer
5.052
274746AC1-111 G10
Adder
6.931
274744AC1-111 GEN8
Adder
6.931
270536AF1-215 GEN2
Solar/Wind Harmer
5.632
944161AF1-084 GEN
Solar/Wind Harmer
2.727
958391AF2-133 GEN
Solar/Wind Harmer
11.114
276868AE1-113 GEN
Solar/Wind Harmer
12.361
276882AE2-255 GEN
Solar/Wind Harmer
4.121
971177AH1-047 GEN
Solar/Wind Harmer
7.155
971675AH1-338 GEN
Solar/Wind Harmer
21.935
971411AH1-196 GEN
Solar/Wind Harmer
18.277
274863CRW1-WTG
Solar/Wind Harmer
6.797
274864CRW2-WTG
Solar/Wind Harmer
6.797
274823ROCKFORD ;21
Adder
23.617
944201AF1-088_MTX
Adder
121.966
957141AF2-008_MTX
Adder
60.983
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.884
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.467
MECLTFEXP_MEC->PJM
CLTF
18.629
SIGELTFEXP_SIGE->PJM
CLTF
0.499
LAGNLTFEXP_LAGN->PJM
CLTF
16.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.278
TVALTFEXP_TVA->PJM
CLTF
7.974
CPLELTFEXP_CPLE->PJM
CLTF
3.266
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.696
NYPJM->LTFIMP_NY
CLTF
3.9
LGEELTFEXP_LGEE->PJM
CLTF
6.008
WECLTFEXP_WEC->PJM
CLTF
4.622
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.17 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5474.49
MW Contribution:37.39
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.722
24721905FLATG4
50/50
31.565
970153AG2-106 GEN
Solar/Wind Harmer
38.491
970513AG2-328 GEN
Solar/Wind Harmer
23.775
24721805FLATG3
50/50
1.722
24721705FLATG2
50/50
31.565
24344105CKG2
50/50
10.234
962761AG1-125 GEN
Solar/Wind Harmer
88.274
970149AG2-104 GEN
Solar/Wind Harmer
109.018
970155AG2-107 GEN
Solar/Wind Harmer
38.491
970245AG2-165 GEN
Solar/Wind Harmer
23.775
972207SS24-0001
Solar/Wind Harmer
27.952
274773LINCOLN ;4U
Adder
7.862
274774LINCOLN ;5U
Adder
7.862
274723RIVER EC ;12
Adder
22.519
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0.882
274751CRETE EC ;1U
Adder
6.133
274754CRETE EC ;4U
Adder
6.133
274812UNIV PK N;8U
Adder
6.271
270063AE2-323 C
Solar/Wind Harmer
2.759
270505AE1-170 C O1
Solar/Wind Harmer
18.777
276776AD2-060 GEN
Solar/Wind Harmer
0.528
274801UNIV PARK;4U
Adder
7.284
970373AG2-245 GEN
Solar/Wind Harmer
26.232
945111AF1-176 GEN
Solar/Wind Harmer
22.274
941551AE2-152 GEN
Solar/Wind Harmer
5.659
274676JOLIET 29;8U
Adder
38.193
274674JOLIET 9 ;6U
Adder
19.152
274732ELWOOD EC;7P
Adder
20.437
274871GR RIDGE ;2U
Solar/Wind Harmer
9.557
270449AD2-020 GEN
Solar/Wind Harmer
3.475
943021AE2-325 GEN
Solar/Wind Harmer
4.516
274745AC1-111 GEN9
Adder
6.925
270055AF2-134 C O1
Solar/Wind Harmer
3.751
965011AG1-365 GEN
Solar/Wind Harmer
12.349
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274682WAUKEGAN ;7U
Adder
22.105
274828WAUKEGAN ;BP
Adder
13.577
958381AF2-132 GEN
Solar/Wind Harmer
11.148
964861AG1-349 GEN
Solar/Wind Harmer
9.652
971917AH1-482 GEN
Solar/Wind Harmer
11.138
939401AE1-172 GEN
Solar/Wind Harmer
17.078
960751AF2-366 GEN
Solar/Wind Harmer
3.515
962781AG1-127 GEN
Solar/Wind Harmer
11.651
274872LEEDK;1U
Solar/Wind Harmer
10.051
276901AD2-066 C O1
Solar/Wind Harmer
4.296
971997AH1-543 GEN
Solar/Wind Harmer
19.204
276861AD2-134 GEN
Solar/Wind Harmer
2.175
274822ROCKFORD ;11
Adder
23.77
972235AH1-702 GEN1
Adder
3.049
274761LEE CO EC;2U
Adder
11.168
274766LEE CO EC;7U
Adder
11.036
940581AE2-045 GEN
Solar/Wind Harmer
2.565
971605AH1-302 GEN
Solar/Wind Harmer
2.193
970517AG2-330 GEN
Solar/Wind Harmer
21.564
970349AG2-230 GEN
Solar/Wind Harmer
19.862
270043AE2-236 GEN
Solar/Wind Harmer
7.159
274772LINCOLN ;3U
Adder
7.862
944531AF1-118 GEN
Solar/Wind Harmer
44.374
247643Z2-116 C
Solar/Wind Harmer
0.088
274724RIVER EC ;11
Adder
22.259
24642205MAYFLWER
Adder
0.798
972231SS25-0005
Solar/Wind Harmer
11.908
972181SS23-001
Solar/Wind Harmer
7.442
274752CRETE EC ;2U
Adder
6.133
274753CRETE EC ;3U
Adder
6.133
970707AG2-453 GEN
Solar/Wind Harmer
35.123
274826FISK ;BP
Adder
13.684
274802UNIV PARK;5U
Adder
7.287
972228AH1-698 GEN2
Adder
4.63
276772AC2-154 GEN
Solar/Wind Harmer
3.486
276806AD2-047 C O1
Solar/Wind Harmer
13.371
970941AG2-585 GEN
Solar/Wind Harmer
15.624
274800UNIV PARK;3U
Adder
7.284
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.059
276897AD1-100 C
Solar/Wind Harmer
36.209
939351AE1-166 GEN
Solar/Wind Harmer
7.399
970031AG2-029 GEN
Solar/Wind Harmer
37.394
274676JOLIET 29;8U
Adder
36.829
274729ELWOOD EC;1P
Adder
20.437
274730ELWOOD EC;6P
Adder
20.437
274734ELWOOD EC;8P
Adder
20.437
274736ELWOOD EC;9P
Adder
20.437
276893AG1-478 C
Solar/Wind Harmer
0.519
943121AE2-341 GEN
Solar/Wind Harmer
18.605
943591AF1-030 GEN
Solar/Wind Harmer
12.403
270535AF1-215 GEN1
Solar/Wind Harmer
5.627
959331AF2-224 GEN
Solar/Wind Harmer
12.349
965021AG1-366 GEN
Solar/Wind Harmer
2.872
276694AA1-018 GEN2
Solar/Wind Harmer
7.765
274682WAUKEGAN ;7U
Adder
22.105
964401AG1-302 GEN
Solar/Wind Harmer
11.148
274872LEEDK;1U
Solar/Wind Harmer
0.313
276805AD2-038 GEN
Solar/Wind Harmer
6.274
959141AF2-205 GEN
Solar/Wind Harmer
7.378
24441205WTRV SLR C
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
2.692
946671AF1-331 GEN
Solar/Wind Harmer
0.51
274855GSG-6 ;RU
Solar/Wind Harmer
4.497
24721605FLATG1
50/50
1.722
971599AH1-298 GEN
50/50
12.01
962771AG1-126 GEN
Solar/Wind Harmer
88.274
971347AH1-153 GEN
Solar/Wind Harmer
19.862
270071AF1-092 GEN
Solar/Wind Harmer
19.385
960681AF2-359 GEN
Solar/Wind Harmer
4.811
274775LINCOLN ;6U
Adder
7.862
274776LINCOLN ;7U
Adder
7.862
274777LINCOLN ;8U
Adder
7.862
971771AH1-392 GEN
Solar/Wind Harmer
11.413
971769AH1-391 GEN
Solar/Wind Harmer
12.662
24729505KEY G4
Adder
8.125
274814UNIV PK N;0U
Adder
6.326
274807UNIV PK N;3U
Adder
6.312
274805UNIV PK N;1U
Adder
6.285
274811UNIV PK N;7U
Adder
6.271
274827FISK ;RP
Adder
9.698
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
12.499
972227AH1-698 GEN1
Adder
3.26
274687WILL CNTY;4U
Adder
34.801
274687WILL CNTY;4U
Adder
34.801
274675JOLIET 29;7U
Adder
38.193
274675JOLIET 29;7U
Adder
36.829
274731ELWOOD EC;2P
Adder
20.437
274733ELWOOD EC;3P
Adder
20.437
274735ELWOOD EC;4P
Adder
20.437
274728ELWOOD EC;5P
Adder
20.437
970833AG2-524 GEN
Solar/Wind Harmer
10.853
970833AG2-524 GEN
Solar/Wind Harmer
5.048
274746AC1-111 G10
Adder
6.925
274744AC1-111 GEN8
Adder
6.925
270536AF1-215 GEN2
Solar/Wind Harmer
5.627
944161AF1-084 GEN
Solar/Wind Harmer
2.725
958391AF2-133 GEN
Solar/Wind Harmer
11.104
276868AE1-113 GEN
Solar/Wind Harmer
12.351
276882AE2-255 GEN
Solar/Wind Harmer
4.117
971177AH1-047 GEN
Solar/Wind Harmer
7.149
971675AH1-338 GEN
Solar/Wind Harmer
21.917
971411AH1-196 GEN
Solar/Wind Harmer
18.262
274863CRW1-WTG
Solar/Wind Harmer
6.791
274864CRW2-WTG
Solar/Wind Harmer
6.791
274823ROCKFORD ;21
Adder
23.597
270102X2-052 ST
50/50
2.043
270100X2-052 CT1
50/50
1.882
270101X2-052 CT2
50/50
1.882
970321AG2-212 GEN
Solar/Wind Harmer
23.775
965681AG1-436 GEN
Solar/Wind Harmer
15.919
965791AG1-447 GEN
Solar/Wind Harmer
8.144
274770LINCOLN ;1U
Adder
7.862
274771LINCOLN ;2U
Adder
7.862
270526AF1-158 GEN
Solar/Wind Harmer
5.755
24441505OLIV SLR
Solar/Wind Harmer
0.17
270216AD2-079_GEN
Solar/Wind Harmer
0.766
274808UNIV PK N;4U
Adder
6.244
957891AF2-083 GEN
Solar/Wind Harmer
4.22
972259AH1-714 GEN
Adder
23.87
960981AF2-389 GEN
Solar/Wind Harmer
1.891
247620Y3-023
Adder
0.576
274803UNIV PARK;6U
Adder
7.287
274888KELLY CRK;1U
Solar/Wind Harmer
7.379
274887GEN-1.85
Solar/Wind Harmer
6.662
276843GEN-1.7
Solar/Wind Harmer
0.717
958011AF2-095 GEN
Solar/Wind Harmer
17.999
274674JOLIET 9 ;6U
Adder
19.152
961051AF2-396 GEN
Solar/Wind Harmer
19.732
961051AF2-396 GEN
Solar/Wind Harmer
9.178
274847GR RIDGE ;BU
Solar/Wind Harmer
6.287
971573AH1-285 GEN
Solar/Wind Harmer
10.635
970611AG2-400 GEN
Solar/Wind Harmer
12.349
274695ROCKY RD ;2P
Adder
13.709
274693ROCKY RD ;1P
Adder
13.574
274697ROCKY RD ;3P
Adder
3.724
274696ROCKY RD ;4P
Adder
14.032
958481AF2-142 GEN
Solar/Wind Harmer
18.457
274861TOP CROP ;1U
Solar/Wind Harmer
7.454
274862TOP CROP ;2U
Solar/Wind Harmer
6.225
274683WAUKEGAN ;8U
Adder
25.901
274683WAUKEGAN ;8U
Adder
21.834
962691AG1-118 GEN
Solar/Wind Harmer
36.804
970921AG2-575 GEN
Solar/Wind Harmer
12.252
970921AG2-575 GEN
Solar/Wind Harmer
2.849
958491AF2-143 GEN
Solar/Wind Harmer
18.346
274879MINONK ;1U
Solar/Wind Harmer
8.235
942991AE2-321 GEN
Solar/Wind Harmer
12.203
971333AH1-146 GEN
Solar/Wind Harmer
24.34
971335AH1-147 GEN
Solar/Wind Harmer
24.34
274764LEE CO EC;5U
Adder
11.194
274765LEE CO EC;6U
Adder
11.194
274762LEE CO EC;3U
Adder
11.168
274763LEE CO EC;4U
Adder
11.063
972267AH1-718 GEN
Adder
4.973
247621Y3-024
Adder
0.251
274850MENDOTA H;RU
Solar/Wind Harmer
3.127
276602WESTBROOK C
Solar/Wind Harmer
2.588
276863AD2-134 GEN
Solar/Wind Harmer
2.175
972236AH1-702 GEN2
Adder
2.651
247604X1-042
Adder
0.502
274760LEE CO EC;1U
Adder
11.168
274767LEE CO EC;8U
Adder
11.036
24728705AND G3
Adder
5.245
944201AF1-088_MTX
Adder
121.843
957141AF2-008_MTX
Adder
60.922
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.738
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.434
MECLTFEXP_MEC->PJM
CLTF
18.612
SIGELTFEXP_SIGE->PJM
CLTF
0.498
LAGNLTFEXP_LAGN->PJM
CLTF
16.721
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.266
TVALTFEXP_TVA->PJM
CLTF
7.965
CPLELTFEXP_CPLE->PJM
CLTF
3.264
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.573
NYPJM->LTFIMP_NY
CLTF
3.896
LGEELTFEXP_LGEE->PJM
CLTF
6
WECLTFEXP_WEC->PJM
CLTF
4.618
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.15 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5473.55
MW Contribution:37.38
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.721
24721705FLATG2
50/50
31.554
24344105CKG2
50/50
10.231
962761AG1-125 GEN
Solar/Wind Harmer
88.258
970149AG2-104 GEN
Solar/Wind Harmer
108.998
970155AG2-107 GEN
Solar/Wind Harmer
38.484
970245AG2-165 GEN
Solar/Wind Harmer
23.767
972207SS24-0001
Solar/Wind Harmer
27.942
274773LINCOLN ;4U
Adder
7.859
274774LINCOLN ;5U
Adder
7.859
274723RIVER EC ;12
Adder
22.511
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0.881
274751CRETE EC ;1U
Adder
6.131
274754CRETE EC ;4U
Adder
6.131
274812UNIV PK N;8U
Adder
6.269
24721605FLATG1
50/50
1.721
971599AH1-298 GEN
50/50
12.006
962771AG1-126 GEN
Solar/Wind Harmer
88.258
971347AH1-153 GEN
Solar/Wind Harmer
19.855
270071AF1-092 GEN
Solar/Wind Harmer
19.378
960681AF2-359 GEN
Solar/Wind Harmer
4.809
274775LINCOLN ;6U
Adder
7.859
274776LINCOLN ;7U
Adder
7.859
274777LINCOLN ;8U
Adder
7.859
971771AH1-392 GEN
Solar/Wind Harmer
11.409
971769AH1-391 GEN
Solar/Wind Harmer
12.658
24729505KEY G4
Adder
8.122
274814UNIV PK N;0U
Adder
6.324
274807UNIV PK N;3U
Adder
6.31
274805UNIV PK N;1U
Adder
6.283
274811UNIV PK N;7U
Adder
6.269
274827FISK ;RP
Adder
9.695
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
12.495
972227AH1-698 GEN1
Adder
3.259
274687WILL CNTY;4U
Adder
34.788
274687WILL CNTY;4U
Adder
34.788
274675JOLIET 29;7U
Adder
38.179
274675JOLIET 29;7U
Adder
36.815
274731ELWOOD EC;2P
Adder
20.43
274733ELWOOD EC;3P
Adder
20.43
274735ELWOOD EC;4P
Adder
20.43
274728ELWOOD EC;5P
Adder
20.43
970833AG2-524 GEN
Solar/Wind Harmer
10.849
970833AG2-524 GEN
Solar/Wind Harmer
5.046
274746AC1-111 G10
Adder
6.922
274744AC1-111 GEN8
Adder
6.922
270536AF1-215 GEN2
Solar/Wind Harmer
5.625
944161AF1-084 GEN
Solar/Wind Harmer
2.724
958391AF2-133 GEN
Solar/Wind Harmer
11.1
276868AE1-113 GEN
Solar/Wind Harmer
12.346
276882AE2-255 GEN
Solar/Wind Harmer
4.116
971177AH1-047 GEN
Solar/Wind Harmer
7.147
971675AH1-338 GEN
Solar/Wind Harmer
21.909
971411AH1-196 GEN
Solar/Wind Harmer
18.255
274863CRW1-WTG
Solar/Wind Harmer
6.789
274864CRW2-WTG
Solar/Wind Harmer
6.789
274823ROCKFORD ;21
Adder
23.589
270102X2-052 ST
50/50
2.042
270100X2-052 CT1
50/50
1.881
270101X2-052 CT2
50/50
1.881
970321AG2-212 GEN
Solar/Wind Harmer
23.767
965681AG1-436 GEN
Solar/Wind Harmer
15.913
965791AG1-447 GEN
Solar/Wind Harmer
8.141
274770LINCOLN ;1U
Adder
7.859
274771LINCOLN ;2U
Adder
7.859
270526AF1-158 GEN
Solar/Wind Harmer
5.753
24441505OLIV SLR
Solar/Wind Harmer
0.17
270216AD2-079_GEN
Solar/Wind Harmer
0.766
274808UNIV PK N;4U
Adder
6.241
957891AF2-083 GEN
Solar/Wind Harmer
4.219
972259AH1-714 GEN
Adder
23.861
960981AF2-389 GEN
Solar/Wind Harmer
1.89
247620Y3-023
Adder
0.576
274803UNIV PARK;6U
Adder
7.284
274888KELLY CRK;1U
Solar/Wind Harmer
7.377
274887GEN-1.85
Solar/Wind Harmer
6.66
276843GEN-1.7
Solar/Wind Harmer
0.717
958011AF2-095 GEN
Solar/Wind Harmer
17.992
274674JOLIET 9 ;6U
Adder
19.145
961051AF2-396 GEN
Solar/Wind Harmer
19.725
961051AF2-396 GEN
Solar/Wind Harmer
9.174
274847GR RIDGE ;BU
Solar/Wind Harmer
6.284
971573AH1-285 GEN
Solar/Wind Harmer
10.631
970611AG2-400 GEN
Solar/Wind Harmer
12.344
274695ROCKY RD ;2P
Adder
13.703
274693ROCKY RD ;1P
Adder
13.569
274697ROCKY RD ;3P
Adder
3.723
274696ROCKY RD ;4P
Adder
14.027
958481AF2-142 GEN
Solar/Wind Harmer
18.451
274861TOP CROP ;1U
Solar/Wind Harmer
7.451
274862TOP CROP ;2U
Solar/Wind Harmer
6.222
274683WAUKEGAN ;8U
Adder
25.892
274683WAUKEGAN ;8U
Adder
21.826
962691AG1-118 GEN
Solar/Wind Harmer
36.79
970921AG2-575 GEN
Solar/Wind Harmer
12.247
970921AG2-575 GEN
Solar/Wind Harmer
2.848
24722005FLATG5
50/50
1.721
24721905FLATG4
50/50
31.554
970153AG2-106 GEN
Solar/Wind Harmer
38.484
970513AG2-328 GEN
Solar/Wind Harmer
23.767
970517AG2-330 GEN
Solar/Wind Harmer
21.556
970349AG2-230 GEN
Solar/Wind Harmer
19.855
270043AE2-236 GEN
Solar/Wind Harmer
7.157
274772LINCOLN ;3U
Adder
7.859
944531AF1-118 GEN
Solar/Wind Harmer
44.357
247643Z2-116 C
Solar/Wind Harmer
0.088
274724RIVER EC ;11
Adder
22.251
24642205MAYFLWER
Adder
0.798
972231SS25-0005
Solar/Wind Harmer
11.904
972181SS23-001
Solar/Wind Harmer
7.44
274752CRETE EC ;2U
Adder
6.131
274753CRETE EC ;3U
Adder
6.131
970707AG2-453 GEN
Solar/Wind Harmer
35.11
274826FISK ;BP
Adder
13.679
274802UNIV PARK;5U
Adder
7.284
276772AC2-154 GEN
Solar/Wind Harmer
3.484
276806AD2-047 C O1
Solar/Wind Harmer
13.366
970941AG2-585 GEN
Solar/Wind Harmer
15.618
972228AH1-698 GEN2
Adder
4.628
274800UNIV PARK;3U
Adder
7.282
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.057
276897AD1-100 C
Solar/Wind Harmer
36.196
939351AE1-166 GEN
Solar/Wind Harmer
7.396
970031AG2-029 GEN
Solar/Wind Harmer
37.38
274676JOLIET 29;8U
Adder
36.815
274729ELWOOD EC;1P
Adder
20.43
274730ELWOOD EC;6P
Adder
20.43
274734ELWOOD EC;8P
Adder
20.43
274736ELWOOD EC;9P
Adder
20.43
276893AG1-478 C
Solar/Wind Harmer
0.519
943121AE2-341 GEN
Solar/Wind Harmer
18.598
943591AF1-030 GEN
Solar/Wind Harmer
12.399
270535AF1-215 GEN1
Solar/Wind Harmer
5.625
959331AF2-224 GEN
Solar/Wind Harmer
12.344
965021AG1-366 GEN
Solar/Wind Harmer
2.871
276694AA1-018 GEN2
Solar/Wind Harmer
7.762
274682WAUKEGAN ;7U
Adder
22.097
964401AG1-302 GEN
Solar/Wind Harmer
11.144
274872LEEDK;1U
Solar/Wind Harmer
0.313
276805AD2-038 GEN
Solar/Wind Harmer
6.272
959141AF2-205 GEN
Solar/Wind Harmer
7.375
24441205WTRV SLR C
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
2.691
946671AF1-331 GEN
Solar/Wind Harmer
0.51
274855GSG-6 ;RU
Solar/Wind Harmer
4.495
274850MENDOTA H;RU
Solar/Wind Harmer
3.126
276602WESTBROOK C
Solar/Wind Harmer
2.587
276863AD2-134 GEN
Solar/Wind Harmer
2.174
972236AH1-702 GEN2
Adder
2.65
247604X1-042
Adder
0.502
274760LEE CO EC;1U
Adder
11.164
274767LEE CO EC;8U
Adder
11.032
24728705AND G3
Adder
5.242
958491AF2-143 GEN
Solar/Wind Harmer
18.339
274879MINONK ;1U
Solar/Wind Harmer
8.232
942991AE2-321 GEN
Solar/Wind Harmer
12.198
971333AH1-146 GEN
Solar/Wind Harmer
24.331
971335AH1-147 GEN
Solar/Wind Harmer
24.331
274764LEE CO EC;5U
Adder
11.19
274765LEE CO EC;6U
Adder
11.19
274762LEE CO EC;3U
Adder
11.164
274763LEE CO EC;4U
Adder
11.058
972267AH1-718 GEN
Adder
4.971
247621Y3-024
Adder
0.251
270063AE2-323 C
Solar/Wind Harmer
2.758
270505AE1-170 C O1
Solar/Wind Harmer
18.77
276776AD2-060 GEN
Solar/Wind Harmer
0.528
274801UNIV PARK;4U
Adder
7.282
970373AG2-245 GEN
Solar/Wind Harmer
26.222
945111AF1-176 GEN
Solar/Wind Harmer
22.266
941551AE2-152 GEN
Solar/Wind Harmer
5.657
274676JOLIET 29;8U
Adder
38.179
274674JOLIET 9 ;6U
Adder
19.145
274732ELWOOD EC;7P
Adder
20.43
274871GR RIDGE ;2U
Solar/Wind Harmer
9.554
270449AD2-020 GEN
Solar/Wind Harmer
3.474
943021AE2-325 GEN
Solar/Wind Harmer
4.514
274745AC1-111 GEN9
Adder
6.922
270055AF2-134 C O1
Solar/Wind Harmer
3.749
965011AG1-365 GEN
Solar/Wind Harmer
12.344
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274682WAUKEGAN ;7U
Adder
22.097
274828WAUKEGAN ;BP
Adder
13.572
958381AF2-132 GEN
Solar/Wind Harmer
11.144
964861AG1-349 GEN
Solar/Wind Harmer
9.648
971917AH1-482 GEN
Solar/Wind Harmer
11.134
939401AE1-172 GEN
Solar/Wind Harmer
17.072
960751AF2-366 GEN
Solar/Wind Harmer
3.514
962781AG1-127 GEN
Solar/Wind Harmer
11.647
274872LEEDK;1U
Solar/Wind Harmer
10.048
276901AD2-066 C O1
Solar/Wind Harmer
4.294
971997AH1-543 GEN
Solar/Wind Harmer
19.196
276861AD2-134 GEN
Solar/Wind Harmer
2.174
274822ROCKFORD ;11
Adder
23.761
972235AH1-702 GEN1
Adder
3.048
274761LEE CO EC;2U
Adder
11.164
274766LEE CO EC;7U
Adder
11.032
940581AE2-045 GEN
Solar/Wind Harmer
2.564
971605AH1-302 GEN
Solar/Wind Harmer
2.192
944201AF1-088_MTX
Adder
121.789
957141AF2-008_MTX
Adder
60.895
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.42
MECLTFEXP_MEC->PJM
CLTF
18.605
SIGELTFEXP_SIGE->PJM
CLTF
0.498
LAGNLTFEXP_LAGN->PJM
CLTF
16.714
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.261
TVALTFEXP_TVA->PJM
CLTF
7.962
CPLELTFEXP_CPLE->PJM
CLTF
3.263
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.519
NYPJM->LTFIMP_NY
CLTF
3.894
LGEELTFEXP_LGEE->PJM
CLTF
5.997
WECLTFEXP_WEC->PJM
CLTF
4.617
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.427

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.8 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5417.86
MW Contribution:5.65
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.042
270100X2-052 CT1
50/50
1.881
270101X2-052 CT2
50/50
1.881
970321AG2-212 GEN
Solar/Wind Harmer
4.024
965681AG1-436 GEN
Solar/Wind Harmer
11.102
965791AG1-447 GEN
Solar/Wind Harmer
8.141
274770LINCOLN ;1U
Adder
10.698
274771LINCOLN ;2U
Adder
10.698
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.241
957891AF2-083 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
23.861
247620Y3-023
Adder
0.576
274803UNIV PARK;6U
Adder
7.284
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
274887GEN-1.85
Solar/Wind Harmer
0.23
276843GEN-1.7
Solar/Wind Harmer
0.282
958011AF2-095 GEN
Solar/Wind Harmer
12.553
274674JOLIET 9 ;6U
Adder
19.145
961051AF2-396 GEN
Solar/Wind Harmer
17.339
961051AF2-396 GEN
Solar/Wind Harmer
11.56
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.607
970611AG2-400 GEN
Solar/Wind Harmer
8.612
970627AG2-408 GEN
Solar/Wind Harmer
2.584
274695ROCKY RD ;2P
Adder
13.703
274693ROCKY RD ;1P
Adder
13.569
274697ROCKY RD ;3P
Adder
3.723
274696ROCKY RD ;4P
Adder
14.027
958481AF2-142 GEN
Solar/Wind Harmer
12.872
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.161
274683WAUKEGAN ;8U
Adder
25.892
274683WAUKEGAN ;8U
Adder
21.826
962691AG1-118 GEN
Solar/Wind Harmer
25.667
970921AG2-575 GEN
Solar/Wind Harmer
8.545
970921AG2-575 GEN
Solar/Wind Harmer
2.848
958491AF2-143 GEN
Solar/Wind Harmer
12.795
274879MINONK ;1U
Solar/Wind Harmer
0.359
942991AE2-321 GEN
Solar/Wind Harmer
9.503
971333AH1-146 GEN
Solar/Wind Harmer
16.975
971335AH1-147 GEN
Solar/Wind Harmer
16.975
971341AH1-150 GEN
Solar/Wind Harmer
16.925
971343AH1-151 GEN
Solar/Wind Harmer
16.925
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.565
960971AF2-388 GEN
Solar/Wind Harmer
4.95
274856ECOGROVE ;U1
Solar/Wind Harmer
0.198
276611AD2-172 GEN
Solar/Wind Harmer
0.002
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.753
274764LEE CO EC;5U
Adder
11.19
274765LEE CO EC;6U
Adder
11.19
274762LEE CO EC;3U
Adder
11.164
274763LEE CO EC;4U
Adder
11.058
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
4.971
276741O09 GEN1
Solar/Wind Harmer
0.296
276708O09 GEN2
Solar/Wind Harmer
0.296
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.006
960611AF2-352 GEN
Solar/Wind Harmer
2.732
966841AG1-555 GEN
Solar/Wind Harmer
0.926
942221AE2-234 GEN
Solar/Wind Harmer
0.041
970241AG2-163 GEN
Solar/Wind Harmer
4.649
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
7.244
270031AE2-169
Solar/Wind Harmer
4.346
971613AH1-306 GEN
Solar/Wind Harmer
3.777
276916AD2-100_GEN
Solar/Wind Harmer
16.273
276911AD2-131_GEN
Solar/Wind Harmer
1.072
960441AF2-335 GEN
Solar/Wind Harmer
7.639
945391AF1-204 GEN
Solar/Wind Harmer
8.098
970825AG2-519 GEN
Solar/Wind Harmer
8.443
970239AG2-162 GEN
Solar/Wind Harmer
0.651
24722005FLATG5
50/50
1.721
24721905FLATG4
50/50
31.554
970153AG2-106 GEN
Solar/Wind Harmer
47.528
970513AG2-328 GEN
Solar/Wind Harmer
4.024
970517AG2-330 GEN
Solar/Wind Harmer
24.143
970349AG2-230 GEN
Solar/Wind Harmer
13.852
270043AE2-236 GEN
Solar/Wind Harmer
5.825
274772LINCOLN ;3U
Adder
10.698
944531AF1-118 GEN
Solar/Wind Harmer
39.627
247643Z2-116 C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
22.251
24642205MAYFLWER
Adder
0.798
274752CRETE EC ;2U
Adder
10.335
274753CRETE EC ;3U
Adder
10.335
970707AG2-453 GEN
Solar/Wind Harmer
28.578
274826FISK ;BP
Adder
13.679
274802UNIV PARK;5U
Adder
7.284
276806AD2-047 C O1
Solar/Wind Harmer
4.94
970941AG2-585 GEN
Solar/Wind Harmer
10.896
972228AH1-698 GEN2
Adder
4.628
274800UNIV PARK;3U
Adder
7.282
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.057
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.65
274676JOLIET 29;8U
Adder
36.815
274729ELWOOD EC;1P
Adder
20.43
274730ELWOOD EC;6P
Adder
20.43
274734ELWOOD EC;8P
Adder
20.43
274736ELWOOD EC;9P
Adder
20.43
276893AG1-478 C
Solar/Wind Harmer
0.344
943121AE2-341 GEN
Solar/Wind Harmer
14.504
943591AF1-030 GEN
Solar/Wind Harmer
9.645
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
959331AF2-224 GEN
Solar/Wind Harmer
6.029
965021AG1-366 GEN
Solar/Wind Harmer
2.871
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.097
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.313
276805AD2-038 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.906
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959091AF2-200 GEN
Solar/Wind Harmer
16.925
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.65
247604X1-042
Adder
0.502
970571AG2-364 GEN
Solar/Wind Harmer
16.817
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.164
274767LEE CO EC;8U
Adder
11.032
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.324
276157O29GEN1
Solar/Wind Harmer
1.345
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
942111AE2-223 GEN
Solar/Wind Harmer
2.687
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.591
959611AF2-252 GEN
Solar/Wind Harmer
2.732
965931AG1-462 GEN
Solar/Wind Harmer
20.863
247642Z2-115 C
Solar/Wind Harmer
0.003
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.685
276668AB2-070 GEN1
Solar/Wind Harmer
0.291
970289AG2-191 GEN
Solar/Wind Harmer
0.875
970291AG2-192 GEN
Solar/Wind Harmer
0.796
276621W2-048 GEN
Solar/Wind Harmer
0.399
276838X2-022 GEN2
Solar/Wind Harmer
0.445
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.051
942481AE2-261 GEN
Solar/Wind Harmer
23.26
958821AF2-173 GEN
Solar/Wind Harmer
10.805
270004AE1-209 GEN
Solar/Wind Harmer
1.672
971617AH1-308 GEN
Solar/Wind Harmer
6.396
970193AG2-126 GEN
Solar/Wind Harmer
11.433
946031AF1-268 GEN
Solar/Wind Harmer
7.175
970243AG2-164 GEN
Solar/Wind Harmer
1.523
970519AG2-331 GEN
Solar/Wind Harmer
6.77
970699AG2-449 GEN
Solar/Wind Harmer
0.651
24721805FLATG3
50/50
1.721
24721705FLATG2
50/50
31.554
24344105CKG2
50/50
10.231
962761AG1-125 GEN
Solar/Wind Harmer
74.429
970149AG2-104 GEN
Solar/Wind Harmer
80.386
970155AG2-107 GEN
Solar/Wind Harmer
47.528
970245AG2-165 GEN
Solar/Wind Harmer
4.024
274773LINCOLN ;4U
Adder
10.698
274774LINCOLN ;5U
Adder
10.698
274723RIVER EC ;12
Adder
22.511
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.335
274754CRETE EC ;4U
Adder
10.335
274812UNIV PK N;8U
Adder
6.269
270063AE2-323 C
Solar/Wind Harmer
0.007
270505AE1-170 C O1
Solar/Wind Harmer
9.167
276776AD2-060 GEN
Solar/Wind Harmer
0.91
274801UNIV PARK;4U
Adder
7.282
970373AG2-245 GEN
Solar/Wind Harmer
18.295
945111AF1-176 GEN
Solar/Wind Harmer
15.535
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
38.179
274674JOLIET 9 ;6U
Adder
19.145
274732ELWOOD EC;7P
Adder
20.43
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.514
274745AC1-111 GEN9
Adder
6.922
270055AF2-134 C O1
Solar/Wind Harmer
0.007
965011AG1-365 GEN
Solar/Wind Harmer
8.612
276691AA1-018 GEN1
Solar/Wind Harmer
1.04
274682WAUKEGAN ;7U
Adder
22.097
274828WAUKEGAN ;BP
Adder
13.572
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.134
939401AE1-172 GEN
Solar/Wind Harmer
6.393
962781AG1-127 GEN
Solar/Wind Harmer
8.132
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
971997AH1-543 GEN
Solar/Wind Harmer
4.464
276861AD2-134 GEN
Solar/Wind Harmer
0.152
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.6
957471AF2-041 GEN
Solar/Wind Harmer
25.388
959081AF2-199 GEN
Solar/Wind Harmer
8.463
971067AG2-660 GEN
Solar/Wind Harmer
2.821
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
23.761
965651AG1-433 GEN
Solar/Wind Harmer
2.475
972235AH1-702 GEN1
Adder
3.048
970819AG2-516 GEN
Solar/Wind Harmer
10.106
970569AG2-363 GEN
Solar/Wind Harmer
25.226
971475AH1-234 GEN
Solar/Wind Harmer
4.081
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.164
274766LEE CO EC;7U
Adder
11.032
958861AF2-177 GEN
Solar/Wind Harmer
3.614
24791305MDL-5G
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
270349AD2-093_GEN
Solar/Wind Harmer
0.006
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.575
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
945371AF1-202 GEN
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
6.679
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
18.86
970291AG2-192 GEN
Solar/Wind Harmer
1.034
963831AG1-236 GEN
Solar/Wind Harmer
3.102
276615X2-022 GEN
Solar/Wind Harmer
0.083
270032AE2-172
Solar/Wind Harmer
5.246
247521TR3_G114
Solar/Wind Harmer
0.286
270246TR4_N_V150
Solar/Wind Harmer
0.051
965911AG1-460 GEN
Solar/Wind Harmer
1.556
276903AD2-071 C
Solar/Wind Harmer
8.661
270005AE1-210 C O1
Solar/Wind Harmer
1.672
965031AG1-367 GEN
Solar/Wind Harmer
7.718
944231AF1-091 GEN
Solar/Wind Harmer
2.052
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
2.704
970333AG2-219 GEN
Solar/Wind Harmer
1.862
24721605FLATG1
50/50
1.721
971599AH1-298 GEN
50/50
12.006
962771AG1-126 GEN
Solar/Wind Harmer
74.429
971347AH1-153 GEN
Solar/Wind Harmer
13.852
270071AF1-092 GEN
Solar/Wind Harmer
17.275
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
10.698
274776LINCOLN ;7U
Adder
10.698
274777LINCOLN ;8U
Adder
10.698
971771AH1-392 GEN
Solar/Wind Harmer
8.844
971769AH1-391 GEN
Solar/Wind Harmer
9.861
24729505KEY G4
Adder
8.122
274814UNIV PK N;0U
Adder
6.324
274807UNIV PK N;3U
Adder
6.31
274805UNIV PK N;1U
Adder
6.283
274811UNIV PK N;7U
Adder
6.269
971619AH1-309 GEN
Solar/Wind Harmer
3.929
274827FISK ;RP
Adder
9.695
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
8.717
972227AH1-698 GEN1
Adder
3.259
274687WILL CNTY;4U
Adder
34.788
274687WILL CNTY;4U
Adder
34.788
274675JOLIET 29;7U
Adder
38.179
274675JOLIET 29;7U
Adder
36.815
274731ELWOOD EC;2P
Adder
20.43
274733ELWOOD EC;3P
Adder
20.43
274735ELWOOD EC;4P
Adder
20.43
274728ELWOOD EC;5P
Adder
20.43
970833AG2-524 GEN
Solar/Wind Harmer
9.537
970833AG2-524 GEN
Solar/Wind Harmer
6.358
274746AC1-111 G10
Adder
6.922
274744AC1-111 GEN8
Adder
6.922
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.708
276882AE2-255 GEN
Solar/Wind Harmer
0.995
971177AH1-047 GEN
Solar/Wind Harmer
5.247
971675AH1-338 GEN
Solar/Wind Harmer
3.312
971411AH1-196 GEN
Solar/Wind Harmer
12.736
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.049
971171AH1-044 GEN
Solar/Wind Harmer
16.925
274823ROCKFORD ;21
Adder
23.589
970169AG2-114 GEN
Solar/Wind Harmer
8.416
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.43
971681AH1-341 GEN
Solar/Wind Harmer
13.508
961011AF2-392 GEN
Solar/Wind Harmer
4.894
965101AG1-375 GEN
Solar/Wind Harmer
8.339
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
957751AF2-069 GEN
Solar/Wind Harmer
0.274
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.681
941731AE2-173 GEN
Solar/Wind Harmer
6.89
946321AF1-296 GEN
Solar/Wind Harmer
4.595
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.958
963841AG1-237 GEN
Solar/Wind Harmer
3.497
965041AG1-368 GEN
Solar/Wind Harmer
8.037
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.291
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
970289AG2-191 GEN
Solar/Wind Harmer
1.512
971549AH1-272 GEN
Solar/Wind Harmer
16.344
971609AH1-304 GEN
Solar/Wind Harmer
1.291
270594AE1-207 GEN
Solar/Wind Harmer
8.813
965051AG1-369 GEN
Solar/Wind Harmer
3.913
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270024AE2-089 GEN
Solar/Wind Harmer
0.008
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.485
970115AG2-085 GEN
Solar/Wind Harmer
3.056
944201AF1-088_MTX
Adder
121.789
957141AF2-008_MTX
Adder
33.652
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.42
MECLTFEXP_MEC->PJM
CLTF
18.605
SIGELTFEXP_SIGE->PJM
CLTF
0.498
LAGNLTFEXP_LAGN->PJM
CLTF
16.714
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.261
TVALTFEXP_TVA->PJM
CLTF
7.962
CPLELTFEXP_CPLE->PJM
CLTF
3.263
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.519
NYPJM->LTFIMP_NY
CLTF
3.894
LGEELTFEXP_LGEE->PJM
CLTF
5.997
WECLTFEXP_WEC->PJM
CLTF
4.617
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.427

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P4_#706_05GAVIN 765_C1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#706_05GAVIN 765_C1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.53 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4826.48
MW Contribution:43.34
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
4.694
24721905FLATG4
50/50
86.059
270475AD2-096_GEN
50/50
10.488
270142AC1-141 CT1_
50/50
3.444
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.376
24642205MAYFLWER
50/50
0.961
944961AF1-161 GEN
50/50
4.122
962601AG1-109 GEN
50/50
4.122
970153AG2-106 GEN
Solar/Wind Harmer
56.644
270043AE2-236 GEN
Solar/Wind Harmer
8.306
970349AG2-230 GEN
Solar/Wind Harmer
22.443
959331AF2-224 GEN
Solar/Wind Harmer
14.786
965021AG1-366 GEN
Solar/Wind Harmer
3.439
942871AE2-306 GEN
Solar/Wind Harmer
1.331
270391AF1-285 GEN3
Solar/Wind Harmer
0.683
970513AG2-328 GEN
Solar/Wind Harmer
26.004
970517AG2-330 GEN
Solar/Wind Harmer
23.585
970031AG2-029 GEN
Solar/Wind Harmer
43.335
247643Z2-116 C
Solar/Wind Harmer
0.101
944531AF1-118 GEN
Solar/Wind Harmer
49.96
945111AF1-176 GEN
Solar/Wind Harmer
8.066
270485AE1-090_GEN
Solar/Wind Harmer
0.85
24441205WTRV SLR C
Solar/Wind Harmer
0.189
247604X1-042
Adder
0.578
274772LINCOLN ;3U
Adder
8.527
270191TR4_S_V150
Solar/Wind Harmer
4.119
270247TR4_N_V136
Solar/Wind Harmer
1.168
274724RIVER EC ;11
Adder
24.177
972231SS25-0005
Solar/Wind Harmer
12.946
972181SS23-001
Solar/Wind Harmer
8.091
274752CRETE EC ;2U
Adder
6.668
274753CRETE EC ;3U
Adder
6.668
970707AG2-453 GEN
Solar/Wind Harmer
37.832
274802UNIV PARK;5U
Adder
7.866
274826FISK ;BP
Adder
14.766
276772AC2-154 GEN
Solar/Wind Harmer
3.758
276806AD2-047 C O1
Solar/Wind Harmer
14.415
970941AG2-585 GEN
Solar/Wind Harmer
16.843
274800UNIV PARK;3U
Adder
7.856
972038AH1-567 GEN2
Adder
0.492
972228AH1-698 GEN2
Adder
4.987
270491AE1-102 GEN2
Solar/Wind Harmer
1.748
276897AD1-100 C
Solar/Wind Harmer
38.911
939351AE1-166 GEN
Solar/Wind Harmer
7.95
274676JOLIET 29;8U
Adder
39.557
270535AF1-215 GEN1
Solar/Wind Harmer
6.069
274729ELWOOD EC;1P
Adder
21.93
274730ELWOOD EC;6P
Adder
21.93
274734ELWOOD EC;8P
Adder
21.93
274736ELWOOD EC;9P
Adder
21.93
276893AG1-478 C
Solar/Wind Harmer
0.557
943121AE2-341 GEN
Solar/Wind Harmer
19.89
943591AF1-030 GEN
Solar/Wind Harmer
13.26
964401AG1-302 GEN
Solar/Wind Harmer
11.919
276694AA1-018 GEN2
Solar/Wind Harmer
8.271
274682WAUKEGAN ;7U
Adder
23.511
972236AH1-702 GEN2
Adder
2.783
274760LEE CO EC;1U
Adder
11.654
274767LEE CO EC;8U
Adder
11.517
24728705AND G3
Adder
7.997
24728505AND G1
Adder
3.824
24721605FLATG1
50/50
4.694
971599AH1-298 GEN
50/50
14.063
270144AC1-141 ST1_
50/50
3.051
24653605MOTTVILLE
50/50
0.005
24643105BUCHANAN
50/50
0.018
270036AE2-216 BAT
50/50
8.975
962771AG1-126 GEN
Solar/Wind Harmer
129.902
270284AF1-227 GEN1
Solar/Wind Harmer
9.474
270286AF1-227 GEN2
Solar/Wind Harmer
3.505
270287AF1-227 GEN3
Solar/Wind Harmer
3.505
971347AH1-153 GEN
Solar/Wind Harmer
22.443
270578AF1-285 GEN2
Solar/Wind Harmer
0.683
270071AF1-092 GEN
Solar/Wind Harmer
21.965
971771AH1-392 GEN
Solar/Wind Harmer
12.923
971769AH1-391 GEN
Solar/Wind Harmer
14.204
960681AF2-359 GEN
Solar/Wind Harmer
5.35
944161AF1-084 GEN
Solar/Wind Harmer
3.119
270302AB2-170 GEN
Solar/Wind Harmer
11.755
270317AD1-130_GEN
Solar/Wind Harmer
4.507
24729505KEY G4
Adder
9.092
965041AG1-368 GEN
Solar/Wind Harmer
13.959
274775LINCOLN ;6U
Adder
8.527
274776LINCOLN ;7U
Adder
8.527
274777LINCOLN ;8U
Adder
8.527
965051AG1-369 GEN
Solar/Wind Harmer
6.856
274814UNIV PK N;0U
Adder
6.852
274807UNIV PK N;3U
Adder
6.837
274805UNIV PK N;1U
Adder
6.807
274811UNIV PK N;7U
Adder
6.792
972037AH1-567 GEN1
Adder
0.247
274827FISK ;RP
Adder
10.465
960591AF2-350 GEN
Solar/Wind Harmer
13.475
972227AH1-698 GEN1
Adder
3.512
957201AF2-014 GEN
Solar/Wind Harmer
6.1
270435AC2-044 GEN
Solar/Wind Harmer
2.69
963791AG1-232 GEN
Solar/Wind Harmer
18.134
274687WILL CNTY;4U
Adder
37.406
274687WILL CNTY;4U
Adder
37.406
274675JOLIET 29;7U
Adder
41.022
274675JOLIET 29;7U
Adder
39.557
270536AF1-215 GEN2
Solar/Wind Harmer
6.069
274731ELWOOD EC;2P
Adder
21.93
274733ELWOOD EC;3P
Adder
21.93
274735ELWOOD EC;4P
Adder
21.93
274728ELWOOD EC;5P
Adder
21.93
970833AG2-524 GEN
Solar/Wind Harmer
11.63
970833AG2-524 GEN
Solar/Wind Harmer
5.409
971549AH1-272 GEN
Solar/Wind Harmer
24.604
958711AF2-162 GEN
Solar/Wind Harmer
1.345
274746AC1-111 G10
Adder
7.401
274744AC1-111 GEN8
Adder
7.401
965101AG1-375 GEN
Solar/Wind Harmer
13.06
958391AF2-133 GEN
Solar/Wind Harmer
11.816
274823ROCKFORD ;21
Adder
24.797
970615AG2-402 GEN
50/50
3.439
247620Y3-023
50/50
0.701
270102X2-052 ST
50/50
2.279
270100X2-052 CT1
50/50
2.1
270101X2-052 CT2
50/50
2.1
270471AD2-092_GEN
Solar/Wind Harmer
6.554
970611AG2-400 GEN
Solar/Wind Harmer
14.786
270224U2-072_GEN2
Solar/Wind Harmer
2.903
270227U2-072_GEN3
Solar/Wind Harmer
2.903
270228U2-072_GEN4
Solar/Wind Harmer
2.903
270231U2-072_GEN5
Solar/Wind Harmer
2.903
970321AG2-212 GEN
Solar/Wind Harmer
26.004
270216AD2-079_GEN
Solar/Wind Harmer
0.873
957891AF2-083 GEN
Solar/Wind Harmer
4.815
960981AF2-389 GEN
Solar/Wind Harmer
2.158
270526AF1-158 GEN
Solar/Wind Harmer
6.468
961051AF2-396 GEN
Solar/Wind Harmer
22.558
961051AF2-396 GEN
Solar/Wind Harmer
10.492
24441505OLIV SLR
Solar/Wind Harmer
0.19
965681AG1-436 GEN
Solar/Wind Harmer
17.703
965791AG1-447 GEN
Solar/Wind Harmer
9.057
274770LINCOLN ;1U
Adder
8.527
274771LINCOLN ;2U
Adder
8.527
274808UNIV PK N;4U
Adder
6.763
274803UNIV PARK;6U
Adder
7.866
274888KELLY CRK;1U
Solar/Wind Harmer
7.955
274887GEN-1.85
Solar/Wind Harmer
7.182
276843GEN-1.7
Solar/Wind Harmer
0.773
958011AF2-095 GEN
Solar/Wind Harmer
19.404
972259AH1-714 GEN
Adder
25.697
246938BC-WTG3
Solar/Wind Harmer
5.354
246937BC-WTG2
Solar/Wind Harmer
5.263
274674JOLIET 9 ;6U
Adder
20.555
274847GR RIDGE ;BU
Solar/Wind Harmer
6.735
944541AF1-119 GEN
Solar/Wind Harmer
5.569
960971AF2-388 GEN
Solar/Wind Harmer
14.532
971573AH1-285 GEN
Solar/Wind Harmer
11.345
958481AF2-142 GEN
Solar/Wind Harmer
19.659
274696ROCKY RD ;4P
Adder
14.93
274695ROCKY RD ;2P
Adder
14.586
274693ROCKY RD ;1P
Adder
14.442
274697ROCKY RD ;3P
Adder
3.962
274861TOP CROP ;1U
Solar/Wind Harmer
7.938
274862TOP CROP ;2U
Solar/Wind Harmer
6.628
274683WAUKEGAN ;8U
Adder
27.535
274683WAUKEGAN ;8U
Adder
23.211
962691AG1-118 GEN
Solar/Wind Harmer
39.042
942221AE2-234 GEN
Solar/Wind Harmer
0.953
274764LEE CO EC;5U
Adder
11.682
274765LEE CO EC;6U
Adder
11.682
274762LEE CO EC;3U
Adder
11.654
274763LEE CO EC;4U
Adder
11.544
972267AH1-718 GEN
Adder
5.169
247621Y3-024
Adder
0.268
970921AG2-575 GEN
Solar/Wind Harmer
11.763
970921AG2-575 GEN
Solar/Wind Harmer
2.735
24721805FLATG3
50/50
4.694
24721705FLATG2
50/50
86.059
24344105CKG2
50/50
11.607
270143AC1-141 CT2_
50/50
3.444
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.668
24307105BERRINSP G
50/50
0.031
962761AG1-125 GEN
Solar/Wind Harmer
129.902
970149AG2-104 GEN
Solar/Wind Harmer
160.43
970155AG2-107 GEN
Solar/Wind Harmer
56.644
270349AD2-093_GEN
Solar/Wind Harmer
6.554
965011AG1-365 GEN
Solar/Wind Harmer
14.786
270223U2-072_GEN1
Solar/Wind Harmer
2.903
270578AF1-285 GEN2
Solar/Wind Harmer
1.775
270391AF1-285 GEN3
Solar/Wind Harmer
1.775
970245AG2-165 GEN
Solar/Wind Harmer
26.004
270063AE2-323 C
Solar/Wind Harmer
3.194
270505AE1-170 C O1
Solar/Wind Harmer
21.434
945111AF1-176 GEN
Solar/Wind Harmer
25.451
270449AD2-020 GEN
Solar/Wind Harmer
3.975
943021AE2-325 GEN
Solar/Wind Harmer
5.164
270462AD2-086
Solar/Wind Harmer
9.779
972207SS24-0001
Solar/Wind Harmer
30.317
274773LINCOLN ;4U
Adder
8.527
274774LINCOLN ;5U
Adder
8.527
247521TR3_G114
Solar/Wind Harmer
4.617
270246TR4_N_V150
Solar/Wind Harmer
1.168
274723RIVER EC ;12
Adder
24.46
274751CRETE EC ;1U
Adder
6.668
274754CRETE EC ;4U
Adder
6.668
970373AG2-245 GEN
Solar/Wind Harmer
28.573
276164X3-005 C
Solar/Wind Harmer
0.955
965421AG1-410 GEN
Solar/Wind Harmer
40.731
274812UNIV PK N;8U
Adder
6.792
24695305TIMB G C
Solar/Wind Harmer
7.439
276776AD2-060 GEN
Solar/Wind Harmer
0.57
274801UNIV PARK;4U
Adder
7.856
246936BC-WTG1
Solar/Wind Harmer
5.263
270489AE1-102 GEN1
Solar/Wind Harmer
1.748
941551AE2-152 GEN
Solar/Wind Harmer
6.081
944231AF1-091 GEN
Solar/Wind Harmer
5.048
274676JOLIET 29;8U
Adder
41.022
270055AF2-134 C O1
Solar/Wind Harmer
4.045
274674JOLIET 9 ;6U
Adder
20.555
274732ELWOOD EC;7P
Adder
21.93
274871GR RIDGE ;2U
Solar/Wind Harmer
10.239
965651AG1-433 GEN
Solar/Wind Harmer
7.266
274745AC1-111 GEN9
Adder
7.401
958381AF2-132 GEN
Solar/Wind Harmer
11.919
964861AG1-349 GEN
Solar/Wind Harmer
10.309
971917AH1-482 GEN
Solar/Wind Harmer
11.896
276691AA1-018 GEN1
Solar/Wind Harmer
0.61
274682WAUKEGAN ;7U
Adder
23.511
274828WAUKEGAN ;BP
Adder
14.433
958861AF2-177 GEN
Solar/Wind Harmer
14.275
274822ROCKFORD ;11
Adder
24.978
972235AH1-702 GEN1
Adder
3.201
274761LEE CO EC;2U
Adder
11.654
274766LEE CO EC;7U
Adder
11.517
24728605AND G2
Adder
3.824
960751AF2-366 GEN
Solar/Wind Harmer
3.375
962781AG1-127 GEN
Solar/Wind Harmer
11.186
944201AF1-088_MTX
Adder
108.034
957141AF2-008_MTX
Adder
1.852
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.302
MECLTFEXP_MEC->PJM
CLTF
18.121
SIGELTFEXP_SIGE->PJM
CLTF
0.416
LAGNLTFEXP_LAGN->PJM
CLTF
11.481
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.982
TVALTFEXP_TVA->PJM
CLTF
4.813
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.823
NYPJM->LTFIMP_NY
CLTF
3.072
LGEELTFEXP_LGEE->PJM
CLTF
4.553
WECLTFEXP_WEC->PJM
CLTF
4.843
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4722.06
MW Contribution:6.55
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
4.694
971599AH1-298 GEN
50/50
14.063
270144AC1-141 ST1_
50/50
3.051
24653605MOTTVILLE
50/50
0.005
24643105BUCHANAN
50/50
0.018
270036AE2-216 BAT
50/50
8.975
962771AG1-126 GEN
Solar/Wind Harmer
109.549
270284AF1-227 GEN1
Solar/Wind Harmer
0.015
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
15.658
270578AF1-285 GEN2
Solar/Wind Harmer
0.683
270071AF1-092 GEN
Solar/Wind Harmer
19.582
971771AH1-392 GEN
Solar/Wind Harmer
10.018
971619AH1-309 GEN
Solar/Wind Harmer
4.486
971769AH1-391 GEN
Solar/Wind Harmer
11.066
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.014
971653AH1-327 GEN
Solar/Wind Harmer
1.377
24729505KEY G4
Adder
9.092
965041AG1-368 GEN
Solar/Wind Harmer
9.739
274775LINCOLN ;6U
Adder
11.607
274776LINCOLN ;7U
Adder
11.607
274777LINCOLN ;8U
Adder
11.607
965051AG1-369 GEN
Solar/Wind Harmer
4.783
274814UNIV PK N;0U
Adder
6.852
274807UNIV PK N;3U
Adder
6.837
274805UNIV PK N;1U
Adder
6.807
274811UNIV PK N;7U
Adder
6.792
972037AH1-567 GEN1
Adder
0.247
274827FISK ;RP
Adder
10.465
960591AF2-350 GEN
Solar/Wind Harmer
9.401
972227AH1-698 GEN1
Adder
3.512
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.189
963791AG1-232 GEN
Solar/Wind Harmer
12.652
274687WILL CNTY;4U
Adder
37.406
274687WILL CNTY;4U
Adder
37.406
274675JOLIET 29;7U
Adder
41.022
274675JOLIET 29;7U
Adder
39.557
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
274731ELWOOD EC;2P
Adder
21.93
274733ELWOOD EC;3P
Adder
21.93
274735ELWOOD EC;4P
Adder
21.93
274728ELWOOD EC;5P
Adder
21.93
970833AG2-524 GEN
Solar/Wind Harmer
10.224
970833AG2-524 GEN
Solar/Wind Harmer
6.816
971549AH1-272 GEN
Solar/Wind Harmer
19.16
274746AC1-111 G10
Adder
7.401
274744AC1-111 GEN8
Adder
7.401
965101AG1-375 GEN
Solar/Wind Harmer
9.112
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.807
276882AE2-255 GEN
Solar/Wind Harmer
1.053
971177AH1-047 GEN
Solar/Wind Harmer
5.547
247607V1-011 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.442
971675AH1-338 GEN
Solar/Wind Harmer
3.495
971611AH1-305 GEN
Solar/Wind Harmer
5.332
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
17.815
274823ROCKFORD ;21
Adder
24.797
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.498
970169AG2-114 GEN
Solar/Wind Harmer
8.81
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
14.125
961011AF2-392 GEN
Solar/Wind Harmer
5.094
957751AF2-069 GEN
Solar/Wind Harmer
0.285
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.957
941731AE2-173 GEN
Solar/Wind Harmer
7.108
270024AE2-089 GEN
Solar/Wind Harmer
0.009
946321AF1-296 GEN
Solar/Wind Harmer
4.721
971609AH1-304 GEN
Solar/Wind Harmer
1.376
24386205FR-12G C
Solar/Wind Harmer
0.001
970615AG2-402 GEN
50/50
3.439
247620Y3-023
50/50
0.701
270102X2-052 ST
50/50
2.279
270100X2-052 CT1
50/50
2.1
270101X2-052 CT2
50/50
2.1
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.316
970627AG2-408 GEN
Solar/Wind Harmer
3.095
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
970321AG2-212 GEN
Solar/Wind Harmer
4.403
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.012
961051AF2-396 GEN
Solar/Wind Harmer
19.83
961051AF2-396 GEN
Solar/Wind Harmer
13.22
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
12.351
965791AG1-447 GEN
Solar/Wind Harmer
9.057
274770LINCOLN ;1U
Adder
11.607
274771LINCOLN ;2U
Adder
11.607
274808UNIV PK N;4U
Adder
6.763
274803UNIV PARK;6U
Adder
7.866
274888KELLY CRK;1U
Solar/Wind Harmer
0.552
274887GEN-1.85
Solar/Wind Harmer
0.248
276843GEN-1.7
Solar/Wind Harmer
0.304
958011AF2-095 GEN
Solar/Wind Harmer
13.537
972259AH1-714 GEN
Adder
25.697
246938BC-WTG3
Solar/Wind Harmer
0.34
246937BC-WTG2
Solar/Wind Harmer
0.381
274674JOLIET 9 ;6U
Adder
20.555
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
944541AF1-119 GEN
Solar/Wind Harmer
0.622
960971AF2-388 GEN
Solar/Wind Harmer
5.442
971573AH1-285 GEN
Solar/Wind Harmer
1.715
958481AF2-142 GEN
Solar/Wind Harmer
13.715
274696ROCKY RD ;4P
Adder
14.93
274695ROCKY RD ;2P
Adder
14.586
274693ROCKY RD ;1P
Adder
14.442
274697ROCKY RD ;3P
Adder
3.962
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.237
274683WAUKEGAN ;8U
Adder
27.535
274683WAUKEGAN ;8U
Adder
23.211
962691AG1-118 GEN
Solar/Wind Harmer
27.238
942221AE2-234 GEN
Solar/Wind Harmer
0.045
970921AG2-575 GEN
Solar/Wind Harmer
9.059
970921AG2-575 GEN
Solar/Wind Harmer
3.02
958491AF2-143 GEN
Solar/Wind Harmer
13.566
274879MINONK ;1U
Solar/Wind Harmer
0.38
942991AE2-321 GEN
Solar/Wind Harmer
10.048
270007AE1-245 C
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
17.91
971335AH1-147 GEN
Solar/Wind Harmer
17.91
971341AH1-150 GEN
Solar/Wind Harmer
17.815
971343AH1-151 GEN
Solar/Wind Harmer
17.815
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.621
274856ECOGROVE ;U1
Solar/Wind Harmer
0.208
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.97
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
274764LEE CO EC;5U
Adder
11.682
274765LEE CO EC;6U
Adder
11.682
274762LEE CO EC;3U
Adder
11.654
274763LEE CO EC;4U
Adder
11.544
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.169
276741O09 GEN1
Solar/Wind Harmer
0.308
276708O09 GEN2
Solar/Wind Harmer
0.308
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
7.723
270031AE2-169
Solar/Wind Harmer
4.634
960611AF2-352 GEN
Solar/Wind Harmer
2.799
966841AG1-555 GEN
Solar/Wind Harmer
0.944
971613AH1-306 GEN
Solar/Wind Harmer
3.936
960441AF2-335 GEN
Solar/Wind Harmer
7.977
970241AG2-163 GEN
Solar/Wind Harmer
4.643
970825AG2-519 GEN
Solar/Wind Harmer
8.815
970621AG2-405 GEN
Solar/Wind Harmer
1.453
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.595
247621Y3-024
Adder
0.268
276916AD2-100_GEN
Solar/Wind Harmer
12.804
276911AD2-131_GEN
Solar/Wind Harmer
0.843
24721805FLATG3
50/50
4.694
24721705FLATG2
50/50
86.059
24344105CKG2
50/50
11.607
270143AC1-141 CT2_
50/50
3.444
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.668
24307105BERRINSP G
50/50
0.031
962761AG1-125 GEN
Solar/Wind Harmer
109.549
970149AG2-104 GEN
Solar/Wind Harmer
118.317
970155AG2-107 GEN
Solar/Wind Harmer
69.955
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.316
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
4.403
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.468
945111AF1-176 GEN
Solar/Wind Harmer
17.757
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.164
270462AD2-086
Solar/Wind Harmer
0.02
274773LINCOLN ;4U
Adder
11.607
274774LINCOLN ;5U
Adder
11.607
247521TR3_G114
Solar/Wind Harmer
0.349
270246TR4_N_V150
Solar/Wind Harmer
0.062
274723RIVER EC ;12
Adder
24.46
274751CRETE EC ;1U
Adder
11.24
274754CRETE EC ;4U
Adder
11.24
970373AG2-245 GEN
Solar/Wind Harmer
19.935
276164X3-005 C
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
28.417
274812UNIV PK N;8U
Adder
6.792
24695305TIMB G C
Solar/Wind Harmer
0.002
276776AD2-060 GEN
Solar/Wind Harmer
0.981
274801UNIV PARK;4U
Adder
7.856
246936BC-WTG1
Solar/Wind Harmer
0.381
270489AE1-102 GEN1
Solar/Wind Harmer
1.22
941551AE2-152 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
2.492
274676JOLIET 29;8U
Adder
41.022
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274674JOLIET 9 ;6U
Adder
20.555
274732ELWOOD EC;7P
Adder
21.93
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.721
274745AC1-111 GEN9
Adder
7.401
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.896
276691AA1-018 GEN1
Solar/Wind Harmer
1.108
274682WAUKEGAN ;7U
Adder
23.511
274828WAUKEGAN ;BP
Adder
14.433
958861AF2-177 GEN
Solar/Wind Harmer
3.948
962781AG1-127 GEN
Solar/Wind Harmer
8.621
939401AE1-172 GEN
Solar/Wind Harmer
6.775
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.718
276861AD2-134 GEN
Solar/Wind Harmer
0.161
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.195
957471AF2-041 GEN
Solar/Wind Harmer
26.723
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
1.575
270594AE1-207 GEN
Solar/Wind Harmer
9.184
963841AG1-237 GEN
Solar/Wind Harmer
3.53
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.191
276849AB2-070 GEN2
Solar/Wind Harmer
0.291
276848AB2-070 GEN3
Solar/Wind Harmer
0.29
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
24722005FLATG5
50/50
4.694
24721905FLATG4
50/50
86.059
270475AD2-096_GEN
50/50
10.488
270142AC1-141 CT1_
50/50
3.444
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.376
24642205MAYFLWER
50/50
0.961
944961AF1-161 GEN
50/50
4.122
962601AG1-109 GEN
50/50
4.122
970153AG2-106 GEN
Solar/Wind Harmer
69.955
270043AE2-236 GEN
Solar/Wind Harmer
6.761
970349AG2-230 GEN
Solar/Wind Harmer
15.658
959331AF2-224 GEN
Solar/Wind Harmer
7.221
965021AG1-366 GEN
Solar/Wind Harmer
3.439
270391AF1-285 GEN3
Solar/Wind Harmer
0.683
970513AG2-328 GEN
Solar/Wind Harmer
4.403
970517AG2-330 GEN
Solar/Wind Harmer
26.415
970031AG2-029 GEN
Solar/Wind Harmer
6.551
247643Z2-116 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
44.632
945111AF1-176 GEN
Solar/Wind Harmer
8.066
270485AE1-090_GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.578
274772LINCOLN ;3U
Adder
11.607
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
274724RIVER EC ;11
Adder
24.177
274752CRETE EC ;2U
Adder
11.24
274753CRETE EC ;3U
Adder
11.24
970707AG2-453 GEN
Solar/Wind Harmer
30.794
274802UNIV PARK;5U
Adder
7.866
959081AF2-199 GEN
Solar/Wind Harmer
8.908
971067AG2-660 GEN
Solar/Wind Harmer
2.969
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
24.978
972235AH1-702 GEN1
Adder
3.201
970819AG2-516 GEN
Solar/Wind Harmer
10.6
970569AG2-363 GEN
Solar/Wind Harmer
26.435
971475AH1-234 GEN
Solar/Wind Harmer
4.275
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.654
274766LEE CO EC;7U
Adder
11.517
276158O29GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.289
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.942
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
970291AG2-192 GEN
Solar/Wind Harmer
1.078
270032AE2-172
Solar/Wind Harmer
5.467
972175AH1-670 GEN
Solar/Wind Harmer
6.757
270005AE1-210 C O1
Solar/Wind Harmer
1.747
965031AG1-367 GEN
Solar/Wind Harmer
8.064
276903AD2-071 C
Solar/Wind Harmer
8.911
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
18.836
970825AG2-519 GEN
Solar/Wind Harmer
2.823
963831AG1-236 GEN
Solar/Wind Harmer
3.095
276615X2-022 GEN
Solar/Wind Harmer
0.082
965911AG1-460 GEN
Solar/Wind Harmer
1.521
247536S-71 GEN
Solar/Wind Harmer
0.305
24728605AND G2
Adder
3.824
274826FISK ;BP
Adder
14.766
276806AD2-047 C O1
Solar/Wind Harmer
5.327
970941AG2-585 GEN
Solar/Wind Harmer
11.751
274800UNIV PARK;3U
Adder
7.856
972038AH1-567 GEN2
Adder
0.492
972228AH1-698 GEN2
Adder
4.987
270491AE1-102 GEN2
Solar/Wind Harmer
1.22
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
39.557
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
274729ELWOOD EC;1P
Adder
21.93
274730ELWOOD EC;6P
Adder
21.93
274734ELWOOD EC;8P
Adder
21.93
274736ELWOOD EC;9P
Adder
21.93
276893AG1-478 C
Solar/Wind Harmer
0.369
943121AE2-341 GEN
Solar/Wind Harmer
15.511
943591AF1-030 GEN
Solar/Wind Harmer
10.315
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
23.511
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.331
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.956
274855GSG-6 ;RU
Solar/Wind Harmer
0.329
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.161
959091AF2-200 GEN
Solar/Wind Harmer
17.815
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.783
270258AD1-119 GEN
Solar/Wind Harmer
0.002
970571AG2-364 GEN
Solar/Wind Harmer
17.623
270404AC1-167 GEN
Solar/Wind Harmer
0.004
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.654
274767LEE CO EC;8U
Adder
11.517
276157O29GEN1
Solar/Wind Harmer
1.397
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.621
274878BISHOP HL;2U
Solar/Wind Harmer
0.289
942111AE2-223 GEN
Solar/Wind Harmer
2.772
971617AH1-308 GEN
Solar/Wind Harmer
7.081
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.189
959611AF2-252 GEN
Solar/Wind Harmer
2.799
965931AG1-462 GEN
Solar/Wind Harmer
21.385
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.912
970291AG2-192 GEN
Solar/Wind Harmer
0.829
958821AF2-173 GEN
Solar/Wind Harmer
11.29
270004AE1-209 GEN
Solar/Wind Harmer
1.747
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.686
276668AB2-070 GEN1
Solar/Wind Harmer
0.291
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.901
946031AF1-268 GEN
Solar/Wind Harmer
7.527
276621W2-048 GEN
Solar/Wind Harmer
0.396
276838X2-022 GEN2
Solar/Wind Harmer
0.442
942481AE2-261 GEN
Solar/Wind Harmer
22.745
24728705AND G3
Adder
7.997
24728505AND G1
Adder
3.824
944201AF1-088_MTX
Adder
80.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.302
MECLTFEXP_MEC->PJM
CLTF
18.121
SIGELTFEXP_SIGE->PJM
CLTF
0.416
LAGNLTFEXP_LAGN->PJM
CLTF
11.481
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.982
TVALTFEXP_TVA->PJM
CLTF
4.813
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.823
NYPJM->LTFIMP_NY
CLTF
3.072
LGEELTFEXP_LGEE->PJM
CLTF
4.553
WECLTFEXP_WEC->PJM
CLTF
4.843
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.04 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4474.91
MW Contribution:32.26
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.493
270144AC1-141 ST1_
50/50
2.307
274775LINCOLN ;6U
50/50
7.103
274776LINCOLN ;7U
50/50
7.103
274777LINCOLN ;8U
50/50
7.103
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
81.099
971347AH1-153 GEN
Solar/Wind Harmer
17.162
270071AF1-092 GEN
Solar/Wind Harmer
16.665
971771AH1-392 GEN
Solar/Wind Harmer
9.826
960681AF2-359 GEN
Solar/Wind Harmer
4.124
971769AH1-391 GEN
Solar/Wind Harmer
10.874
24729505KEY G4
Adder
6.929
274814UNIV PK N;0U
Adder
5.377
274807UNIV PK N;3U
Adder
5.366
274805UNIV PK N;1U
Adder
5.342
274811UNIV PK N;7U
Adder
5.331
944161AF1-084 GEN
Solar/Wind Harmer
2.348
274827FISK ;RP
Adder
8.235
972037AH1-567 GEN1
Adder
0.194
960591AF2-350 GEN
Solar/Wind Harmer
10.611
972227AH1-698 GEN1
Adder
2.767
274687WILL CNTY;4U
Adder
29.513
274687WILL CNTY;4U
Adder
29.513
274675JOLIET 29;7U
Adder
32.383
274675JOLIET 29;7U
Adder
31.226
274731ELWOOD EC;2P
Adder
17.321
274733ELWOOD EC;3P
Adder
17.321
274735ELWOOD EC;4P
Adder
17.321
274728ELWOOD EC;5P
Adder
17.321
970833AG2-524 GEN
Solar/Wind Harmer
9.195
970833AG2-524 GEN
Solar/Wind Harmer
4.277
274746AC1-111 G10
Adder
5.862
274744AC1-111 GEN8
Adder
5.862
270536AF1-215 GEN2
Solar/Wind Harmer
4.766
958391AF2-133 GEN
Solar/Wind Harmer
9.357
276868AE1-113 GEN
Solar/Wind Harmer
10.411
276882AE2-255 GEN
Solar/Wind Harmer
3.471
971177AH1-047 GEN
Solar/Wind Harmer
6.027
971675AH1-338 GEN
Solar/Wind Harmer
18.464
971411AH1-196 GEN
Solar/Wind Harmer
15.386
274823ROCKFORD ;21
Adder
19.853
270054AF2-122 C O1
Solar/Wind Helper
1.254
274863CRW1-WTG
Solar/Wind Harmer
3.998
274864CRW2-WTG
Solar/Wind Harmer
3.998
24344105CKG2
50/50
8.873
270143AC1-141 CT2_
50/50
2.604
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.559
274773LINCOLN ;4U
50/50
7.103
274774LINCOLN ;5U
50/50
7.103
962761AG1-125 GEN
Solar/Wind Harmer
81.099
970149AG2-104 GEN
Solar/Wind Harmer
100.157
970155AG2-107 GEN
Solar/Wind Harmer
35.363
970245AG2-165 GEN
Solar/Wind Harmer
20.356
270063AE2-323 C
Solar/Wind Harmer
2.382
972207SS24-0001
Solar/Wind Harmer
23.8
270505AE1-170 C O1
Solar/Wind Harmer
16.187
945111AF1-176 GEN
Solar/Wind Harmer
19.199
274723RIVER EC ;12
Adder
19.163
965011AG1-365 GEN
Solar/Wind Harmer
10.695
270449AD2-020 GEN
Solar/Wind Harmer
2.996
943021AE2-325 GEN
Solar/Wind Harmer
3.892
274751CRETE EC ;1U
Adder
5.219
274754CRETE EC ;4U
Adder
5.219
276164X3-005 C
Solar/Wind Harmer
0.75
274812UNIV PK N;8U
Adder
5.331
970373AG2-245 GEN
Solar/Wind Harmer
22.301
276776AD2-060 GEN
Solar/Wind Harmer
0.449
274801UNIV PARK;4U
Adder
6.184
941551AE2-152 GEN
Solar/Wind Harmer
4.799
274676JOLIET 29;8U
Adder
32.382
274674JOLIET 9 ;6U
Adder
16.234
274732ELWOOD EC;7P
Adder
17.321
274871GR RIDGE ;2U
Solar/Wind Harmer
8.096
274745AC1-111 GEN9
Adder
5.862
270055AF2-134 C O1
Solar/Wind Harmer
3.177
270349AD2-093_GEN
Solar/Wind Harmer
3.79
276691AA1-018 GEN1
Solar/Wind Harmer
0.484
274682WAUKEGAN ;7U
Adder
18.678
274828WAUKEGAN ;BP
Adder
11.47
958381AF2-132 GEN
Solar/Wind Harmer
9.41
964861AG1-349 GEN
Solar/Wind Harmer
8.144
971917AH1-482 GEN
Solar/Wind Harmer
9.398
960751AF2-366 GEN
Solar/Wind Harmer
2.967
962781AG1-127 GEN
Solar/Wind Harmer
9.833
939401AE1-172 GEN
Solar/Wind Harmer
14.402
274872LEEDK;1U
Solar/Wind Harmer
8.48
276901AD2-066 C O1
Solar/Wind Harmer
3.622
971997AH1-543 GEN
Solar/Wind Harmer
16.182
276861AD2-134 GEN
Solar/Wind Harmer
1.832
274822ROCKFORD ;11
Adder
19.998
972235AH1-702 GEN1
Adder
2.564
274761LEE CO EC;2U
Adder
9.372
274766LEE CO EC;7U
Adder
9.261
24721705FLATG2
Adder
19.591
270102X2-052 ST
50/50
1.753
270100X2-052 CT1
50/50
1.615
270101X2-052 CT2
50/50
1.615
274770LINCOLN ;1U
50/50
7.103
274771LINCOLN ;2U
50/50
7.103
247620Y3-023
50/50
0.527
970321AG2-212 GEN
Solar/Wind Harmer
20.356
965681AG1-436 GEN
Solar/Wind Harmer
13.644
965791AG1-447 GEN
Solar/Wind Harmer
6.981
270216AD2-079_GEN
Solar/Wind Harmer
0.661
270526AF1-158 GEN
Solar/Wind Harmer
4.945
24441505OLIV SLR
Solar/Wind Harmer
0.146
957891AF2-083 GEN
Solar/Wind Harmer
3.638
960981AF2-389 GEN
Solar/Wind Harmer
1.63
961051AF2-396 GEN
Solar/Wind Harmer
17.007
961051AF2-396 GEN
Solar/Wind Harmer
7.91
970611AG2-400 GEN
Solar/Wind Harmer
10.695
274808UNIV PK N;4U
Adder
5.307
972259AH1-714 GEN
Adder
20.26
274803UNIV PARK;6U
Adder
6.188
274888KELLY CRK;1U
Solar/Wind Harmer
6.264
274887GEN-1.85
Solar/Wind Harmer
5.656
276843GEN-1.7
Solar/Wind Harmer
0.609
958011AF2-095 GEN
Solar/Wind Harmer
15.279
274674JOLIET 9 ;6U
Adder
16.234
274847GR RIDGE ;BU
Solar/Wind Harmer
5.326
971573AH1-285 GEN
Solar/Wind Harmer
8.997
270471AD2-092_GEN
Solar/Wind Harmer
3.79
274696ROCKY RD ;4P
Adder
11.859
274695ROCKY RD ;2P
Adder
11.585
274693ROCKY RD ;1P
Adder
11.471
274697ROCKY RD ;3P
Adder
3.147
958481AF2-142 GEN
Solar/Wind Harmer
15.598
274861TOP CROP ;1U
Solar/Wind Harmer
6.299
274862TOP CROP ;2U
Solar/Wind Harmer
5.26
274683WAUKEGAN ;8U
Adder
21.882
274683WAUKEGAN ;8U
Adder
18.445
962691AG1-118 GEN
Solar/Wind Harmer
31.071
970921AG2-575 GEN
Solar/Wind Harmer
10.34
970921AG2-575 GEN
Solar/Wind Harmer
2.405
958491AF2-143 GEN
Solar/Wind Harmer
15.476
942991AE2-321 GEN
Solar/Wind Harmer
10.288
274879MINONK ;1U
Solar/Wind Harmer
6.941
971333AH1-146 GEN
Solar/Wind Harmer
20.505
971335AH1-147 GEN
Solar/Wind Harmer
20.505
274764LEE CO EC;5U
Adder
9.394
274765LEE CO EC;6U
Adder
9.394
274762LEE CO EC;3U
Adder
9.372
274763LEE CO EC;4U
Adder
9.283
972267AH1-718 GEN
Adder
4.167
270142AC1-141 CT1_
50/50
2.604
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.093
24642205MAYFLWER
50/50
0.729
274772LINCOLN ;3U
50/50
7.103
970153AG2-106 GEN
Solar/Wind Harmer
35.363
970349AG2-230 GEN
Solar/Wind Harmer
17.162
970513AG2-328 GEN
Solar/Wind Harmer
20.356
970517AG2-330 GEN
Solar/Wind Harmer
18.462
270043AE2-236 GEN
Solar/Wind Harmer
6.202
247643Z2-116 C
Solar/Wind Harmer
0.076
944531AF1-118 GEN
Solar/Wind Harmer
37.964
945111AF1-176 GEN
Solar/Wind Harmer
6.085
970031AG2-029 GEN
Solar/Wind Harmer
32.264
274724RIVER EC ;11
Adder
18.942
959331AF2-224 GEN
Solar/Wind Harmer
10.695
965021AG1-366 GEN
Solar/Wind Harmer
2.487
972231SS25-0005
Solar/Wind Harmer
10.133
972181SS23-001
Solar/Wind Harmer
6.333
274752CRETE EC ;2U
Adder
5.219
274753CRETE EC ;3U
Adder
5.219
970707AG2-453 GEN
Solar/Wind Harmer
29.824
274826FISK ;BP
Adder
11.62
274802UNIV PARK;5U
Adder
6.188
276772AC2-154 GEN
Solar/Wind Harmer
2.959
276806AD2-047 C O1
Solar/Wind Harmer
11.351
970941AG2-585 GEN
Solar/Wind Harmer
13.263
274800UNIV PARK;3U
Adder
6.184
972228AH1-698 GEN2
Adder
3.929
972038AH1-567 GEN2
Adder
0.387
276897AD1-100 C
Solar/Wind Harmer
30.707
939351AE1-166 GEN
Solar/Wind Harmer
6.274
274676JOLIET 29;8U
Adder
31.226
274729ELWOOD EC;1P
Adder
17.321
274730ELWOOD EC;6P
Adder
17.321
274734ELWOOD EC;8P
Adder
17.321
274736ELWOOD EC;9P
Adder
17.321
276893AG1-478 C
Solar/Wind Harmer
0.44
943121AE2-341 GEN
Solar/Wind Harmer
15.753
943591AF1-030 GEN
Solar/Wind Harmer
10.502
24441205WTRV SLR C
Solar/Wind Harmer
0.142
270535AF1-215 GEN1
Solar/Wind Harmer
4.766
276694AA1-018 GEN2
Solar/Wind Harmer
6.562
274682WAUKEGAN ;7U
Adder
18.678
247604X1-042
Adder
0.433
964401AG1-302 GEN
Solar/Wind Harmer
9.41
274872LEEDK;1U
Solar/Wind Harmer
0.264
276805AD2-038 GEN
Solar/Wind Harmer
5.293
959141AF2-205 GEN
Solar/Wind Harmer
6.209
276799AD1-013 GEN
Solar/Wind Harmer
2.268
946671AF1-331 GEN
Solar/Wind Harmer
0.43
274855GSG-6 ;RU
Solar/Wind Harmer
3.788
274850MENDOTA H;RU
Solar/Wind Harmer
2.634
276602WESTBROOK C
Solar/Wind Harmer
2.18
276863AD2-134 GEN
Solar/Wind Harmer
1.832
972236AH1-702 GEN2
Adder
2.23
274760LEE CO EC;1U
Adder
9.372
274767LEE CO EC;8U
Adder
9.261
24721905FLATG4
Adder
19.591
CBM West 1LTFEXP_CBM-W1->PJM
CBM
124.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.057
MECLTFEXP_MEC->PJM
CLTF
15.25
SIGELTFEXP_SIGE->PJM
CLTF
0.383
LAGNLTFEXP_LAGN->PJM
CLTF
12.443
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.1
TVALTFEXP_TVA->PJM
CLTF
5.746
CPLELTFEXP_CPLE->PJM
CLTF
1.819
CBM West 2LTFEXP_CBM-W2->PJM
CBM
95.132
NYPJM->LTFIMP_NY
CLTF
2.909
LGEELTFEXP_LGEE->PJM
CLTF
4.431
WECLTFEXP_WEC->PJM
CLTF
3.883
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.84 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4466.89
MW Contribution:34.05
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
9.236
270143AC1-141 CT2_
50/50
2.745
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.241
24307105BERRINSP G
50/50
0.025
962761AG1-125 GEN
Solar/Wind Harmer
81.683
970149AG2-104 GEN
Solar/Wind Harmer
100.878
970155AG2-107 GEN
Solar/Wind Harmer
35.618
970245AG2-165 GEN
Solar/Wind Harmer
21.006
270063AE2-323 C
Solar/Wind Harmer
2.513
270142AC1-141 CT1_
50/50
2.745
24641605TWIN BRNCH
50/50
0.02
24344005CKG1
50/50
7.486
24642205MAYFLWER
50/50
0.768
944961AF1-161 GEN
50/50
3.289
962601AG1-109 GEN
50/50
3.289
970153AG2-106 GEN
Solar/Wind Harmer
35.618
970349AG2-230 GEN
Solar/Wind Harmer
17.891
270043AE2-236 GEN
Solar/Wind Harmer
6.493
970513AG2-328 GEN
Solar/Wind Harmer
21.006
970517AG2-330 GEN
Solar/Wind Harmer
19.052
247643Z2-116 C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
6.428
970031AG2-029 GEN
Solar/Wind Harmer
34.05
959331AF2-224 GEN
Solar/Wind Harmer
11.324
965021AG1-366 GEN
Solar/Wind Harmer
2.634
944531AF1-118 GEN
Solar/Wind Harmer
39.305
274772LINCOLN ;3U
Adder
6.925
24441205WTRV SLR C
Solar/Wind Harmer
0.151
247604X1-042
Adder
0.462
274724RIVER EC ;11
Adder
19.633
972231SS25-0005
Solar/Wind Harmer
10.51
972181SS23-001
Solar/Wind Harmer
6.569
274752CRETE EC ;2U
Adder
5.413
274753CRETE EC ;3U
Adder
5.413
970707AG2-453 GEN
Solar/Wind Harmer
30.834
274802UNIV PARK;5U
Adder
6.406
274826FISK ;BP
Adder
12.027
276772AC2-154 GEN
Solar/Wind Harmer
3.062
276806AD2-047 C O1
Solar/Wind Harmer
11.745
970941AG2-585 GEN
Solar/Wind Harmer
13.724
274800UNIV PARK;3U
Adder
6.4
972038AH1-567 GEN2
Adder
0.401
972228AH1-698 GEN2
Adder
4.065
276897AD1-100 C
Solar/Wind Harmer
31.748
939351AE1-166 GEN
Solar/Wind Harmer
6.487
274676JOLIET 29;8U
Adder
32.29
274729ELWOOD EC;1P
Adder
17.909
274730ELWOOD EC;6P
Adder
17.909
274734ELWOOD EC;8P
Adder
17.909
274736ELWOOD EC;9P
Adder
17.909
276893AG1-478 C
Solar/Wind Harmer
0.455
270535AF1-215 GEN1
Solar/Wind Harmer
4.946
943121AE2-341 GEN
Solar/Wind Harmer
16.272
943591AF1-030 GEN
Solar/Wind Harmer
10.848
964401AG1-302 GEN
Solar/Wind Harmer
9.751
276694AA1-018 GEN2
Solar/Wind Harmer
6.779
274682WAUKEGAN ;7U
Adder
19.286
274872LEEDK;1U
Solar/Wind Harmer
0.273
276805AD2-038 GEN
Solar/Wind Harmer
5.464
959141AF2-205 GEN
Solar/Wind Harmer
6.424
276799AD1-013 GEN
Solar/Wind Harmer
2.339
946671AF1-331 GEN
Solar/Wind Harmer
0.443
274855GSG-6 ;RU
Solar/Wind Harmer
3.907
274850MENDOTA H;RU
Solar/Wind Harmer
2.716
270505AE1-170 C O1
Solar/Wind Harmer
17.093
945111AF1-176 GEN
Solar/Wind Harmer
20.281
965011AG1-365 GEN
Solar/Wind Harmer
11.324
270449AD2-020 GEN
Solar/Wind Harmer
3.171
943021AE2-325 GEN
Solar/Wind Harmer
4.12
972207SS24-0001
Solar/Wind Harmer
24.622
274773LINCOLN ;4U
Adder
6.925
274774LINCOLN ;5U
Adder
6.925
270349AD2-093_GEN
Solar/Wind Harmer
4.046
274723RIVER EC ;12
Adder
19.863
274751CRETE EC ;1U
Adder
5.413
274754CRETE EC ;4U
Adder
5.413
276164X3-005 C
Solar/Wind Harmer
0.776
970373AG2-245 GEN
Solar/Wind Harmer
23.188
274812UNIV PK N;8U
Adder
5.523
276776AD2-060 GEN
Solar/Wind Harmer
0.464
274801UNIV PARK;4U
Adder
6.4
941551AE2-152 GEN
Solar/Wind Harmer
4.962
274676JOLIET 29;8U
Adder
33.486
274674JOLIET 9 ;6U
Adder
16.785
274732ELWOOD EC;7P
Adder
17.909
270102X2-052 ST
50/50
1.83
270100X2-052 CT1
50/50
1.686
270101X2-052 CT2
50/50
1.686
247620Y3-023
50/50
0.556
970615AG2-402 GEN
50/50
2.634
970321AG2-212 GEN
Solar/Wind Harmer
21.006
270216AD2-079_GEN
Solar/Wind Harmer
0.695
270526AF1-158 GEN
Solar/Wind Harmer
5.182
965681AG1-436 GEN
Solar/Wind Harmer
14.237
965791AG1-447 GEN
Solar/Wind Harmer
7.284
24441505OLIV SLR
Solar/Wind Harmer
0.153
957891AF2-083 GEN
Solar/Wind Harmer
3.84
960981AF2-389 GEN
Solar/Wind Harmer
1.721
961051AF2-396 GEN
Solar/Wind Harmer
17.989
961051AF2-396 GEN
Solar/Wind Harmer
8.367
970611AG2-400 GEN
Solar/Wind Harmer
11.324
274770LINCOLN ;1U
Adder
6.925
274771LINCOLN ;2U
Adder
6.925
270471AD2-092_GEN
Solar/Wind Harmer
4.046
274808UNIV PK N;4U
Adder
5.499
274803UNIV PARK;6U
Adder
6.406
972259AH1-714 GEN
Adder
20.95
274888KELLY CRK;1U
Solar/Wind Harmer
6.482
274887GEN-1.85
Solar/Wind Harmer
5.852
276843GEN-1.7
Solar/Wind Harmer
0.63
958011AF2-095 GEN
Solar/Wind Harmer
15.81
274674JOLIET 9 ;6U
Adder
16.785
274847GR RIDGE ;BU
Solar/Wind Harmer
5.504
971573AH1-285 GEN
Solar/Wind Harmer
9.291
274695ROCKY RD ;2P
Adder
11.962
274693ROCKY RD ;1P
Adder
11.844
274697ROCKY RD ;3P
Adder
3.25
274696ROCKY RD ;4P
Adder
12.244
958481AF2-142 GEN
Solar/Wind Harmer
16.113
274861TOP CROP ;1U
Solar/Wind Harmer
6.507
274862TOP CROP ;2U
Solar/Wind Harmer
5.433
274683WAUKEGAN ;8U
Adder
22.593
274683WAUKEGAN ;8U
Adder
19.044
962691AG1-118 GEN
Solar/Wind Harmer
32.066
970921AG2-575 GEN
Solar/Wind Harmer
10.67
970921AG2-575 GEN
Solar/Wind Harmer
2.481
958491AF2-143 GEN
Solar/Wind Harmer
15.976
274879MINONK ;1U
Solar/Wind Harmer
7.163
942991AE2-321 GEN
Solar/Wind Harmer
10.613
274764LEE CO EC;5U
Adder
9.675
274765LEE CO EC;6U
Adder
9.675
274762LEE CO EC;3U
Adder
9.652
274763LEE CO EC;4U
Adder
9.561
972267AH1-718 GEN
Adder
4.289
247621Y3-024
Adder
0.213
971333AH1-146 GEN
Solar/Wind Harmer
10.211
971335AH1-147 GEN
Solar/Wind Harmer
10.211
276602WESTBROOK C
Solar/Wind Harmer
2.249
276863AD2-134 GEN
Solar/Wind Harmer
1.889
972236AH1-702 GEN2
Adder
2.298
274760LEE CO EC;1U
Adder
9.652
274767LEE CO EC;8U
Adder
9.538
24721905FLATG4
Adder
18.408
270055AF2-134 C O1
Solar/Wind Harmer
3.297
274871GR RIDGE ;2U
Solar/Wind Harmer
8.367
274745AC1-111 GEN9
Adder
6.056
958381AF2-132 GEN
Solar/Wind Harmer
9.751
276691AA1-018 GEN1
Solar/Wind Harmer
0.5
964861AG1-349 GEN
Solar/Wind Harmer
8.438
971917AH1-482 GEN
Solar/Wind Harmer
9.737
274682WAUKEGAN ;7U
Adder
19.286
274828WAUKEGAN ;BP
Adder
11.843
960751AF2-366 GEN
Solar/Wind Harmer
3.061
962781AG1-127 GEN
Solar/Wind Harmer
10.147
939401AE1-172 GEN
Solar/Wind Harmer
14.86
274872LEEDK;1U
Solar/Wind Harmer
8.749
276901AD2-066 C O1
Solar/Wind Harmer
3.738
971997AH1-543 GEN
Solar/Wind Harmer
16.692
276861AD2-134 GEN
Solar/Wind Harmer
1.889
274822ROCKFORD ;11
Adder
20.615
972235AH1-702 GEN1
Adder
2.643
274761LEE CO EC;2U
Adder
9.652
274766LEE CO EC;7U
Adder
9.538
24721705FLATG2
Adder
18.408
971599AH1-298 GEN
50/50
10.933
270144AC1-141 ST1_
50/50
2.431
24653605MOTTVILLE
50/50
0.004
24643105BUCHANAN
50/50
0.015
962771AG1-126 GEN
Solar/Wind Harmer
81.683
971347AH1-153 GEN
Solar/Wind Harmer
17.891
270071AF1-092 GEN
Solar/Wind Harmer
17.328
971771AH1-392 GEN
Solar/Wind Harmer
10.32
960681AF2-359 GEN
Solar/Wind Harmer
4.303
971769AH1-391 GEN
Solar/Wind Harmer
11.39
944161AF1-084 GEN
Solar/Wind Harmer
2.49
274775LINCOLN ;6U
Adder
6.925
274776LINCOLN ;7U
Adder
6.925
274777LINCOLN ;8U
Adder
6.925
24729505KEY G4
Adder
7.169
274814UNIV PK N;0U
Adder
5.572
274807UNIV PK N;3U
Adder
5.56
274805UNIV PK N;1U
Adder
5.536
274811UNIV PK N;7U
Adder
5.523
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.524
960591AF2-350 GEN
Solar/Wind Harmer
10.979
972227AH1-698 GEN1
Adder
2.862
274687WILL CNTY;4U
Adder
30.524
274687WILL CNTY;4U
Adder
30.524
274675JOLIET 29;7U
Adder
33.487
274675JOLIET 29;7U
Adder
32.291
274731ELWOOD EC;2P
Adder
17.909
274733ELWOOD EC;3P
Adder
17.909
274735ELWOOD EC;4P
Adder
17.909
274728ELWOOD EC;5P
Adder
17.909
270536AF1-215 GEN2
Solar/Wind Harmer
4.946
970833AG2-524 GEN
Solar/Wind Harmer
9.503
970833AG2-524 GEN
Solar/Wind Harmer
4.42
274746AC1-111 G10
Adder
6.056
274744AC1-111 GEN8
Adder
6.056
958391AF2-133 GEN
Solar/Wind Harmer
9.687
971549AH1-272 GEN
Solar/Wind Harmer
19.683
276868AE1-113 GEN
Solar/Wind Harmer
10.743
276882AE2-255 GEN
Solar/Wind Harmer
3.581
971177AH1-047 GEN
Solar/Wind Harmer
6.217
965041AG1-368 GEN
Solar/Wind Harmer
10.597
971675AH1-338 GEN
Solar/Wind Harmer
19.042
971411AH1-196 GEN
Solar/Wind Harmer
15.869
274823ROCKFORD ;21
Adder
20.465
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.664
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.379
MECLTFEXP_MEC->PJM
CLTF
15.566
SIGELTFEXP_SIGE->PJM
CLTF
0.382
LAGNLTFEXP_LAGN->PJM
CLTF
12.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.026
TVALTFEXP_TVA->PJM
CLTF
5.551
CPLELTFEXP_CPLE->PJM
CLTF
1.446
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.727
NYPJM->LTFIMP_NY
CLTF
2.961
LGEELTFEXP_LGEE->PJM
CLTF
4.354
WECLTFEXP_WEC->PJM
CLTF
4.001
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.374

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.56 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4331.08
MW Contribution:31.9
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
8.741
270143AC1-141 CT2_
50/50
2.57
24639705ELKHART HY
50/50
0.174
970521AG2-332 GEN
50/50
12.397
962761AG1-125 GEN
Solar/Wind Harmer
80.816
970149AG2-104 GEN
Solar/Wind Harmer
99.808
970155AG2-107 GEN
Solar/Wind Harmer
35.24
970245AG2-165 GEN
Solar/Wind Harmer
19.945
270349AD2-093_GEN
Solar/Wind Harmer
3.906
270063AE2-323 C
Solar/Wind Harmer
2.355
270505AE1-170 C O1
Solar/Wind Harmer
15.976
965011AG1-365 GEN
Solar/Wind Harmer
10.627
945111AF1-176 GEN
Solar/Wind Harmer
18.951
972207SS24-0001
Solar/Wind Harmer
23.296
274773LINCOLN ;4U
Adder
6.552
274774LINCOLN ;5U
Adder
6.552
270449AD2-020 GEN
Solar/Wind Harmer
2.958
943021AE2-325 GEN
Solar/Wind Harmer
3.843
274723RIVER EC ;12
Adder
18.763
274751CRETE EC ;1U
Adder
5.111
274754CRETE EC ;4U
Adder
5.111
276164X3-005 C
Solar/Wind Harmer
0.734
274812UNIV PK N;8U
Adder
5.217
970373AG2-245 GEN
Solar/Wind Harmer
21.845
276776AD2-060 GEN
Solar/Wind Harmer
0.439
274801UNIV PARK;4U
Adder
6.049
941551AE2-152 GEN
Solar/Wind Harmer
4.691
274676JOLIET 29;8U
Adder
31.655
274674JOLIET 9 ;6U
Adder
15.867
274732ELWOOD EC;7P
Adder
16.929
274871GR RIDGE ;2U
Solar/Wind Harmer
7.911
270055AF2-134 C O1
Solar/Wind Harmer
3.107
274745AC1-111 GEN9
Adder
5.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.473
274682WAUKEGAN ;7U
Adder
18.234
274828WAUKEGAN ;BP
Adder
11.196
270142AC1-141 CT1_
50/50
2.57
24641605TWIN BRNCH
50/50
0.019
270475AD2-096_GEN
50/50
6.25
24344005CKG1
50/50
6.999
24642205MAYFLWER
50/50
0.719
970153AG2-106 GEN
Solar/Wind Harmer
35.24
970349AG2-230 GEN
Solar/Wind Harmer
16.9
970513AG2-328 GEN
Solar/Wind Harmer
19.945
970517AG2-330 GEN
Solar/Wind Harmer
18.09
270043AE2-236 GEN
Solar/Wind Harmer
6.129
247643Z2-116 C
Solar/Wind Harmer
0.075
944531AF1-118 GEN
Solar/Wind Harmer
37.271
970031AG2-029 GEN
Solar/Wind Harmer
31.903
959331AF2-224 GEN
Solar/Wind Harmer
10.627
965021AG1-366 GEN
Solar/Wind Harmer
2.471
945111AF1-176 GEN
Solar/Wind Harmer
6.006
274772LINCOLN ;3U
Adder
6.552
274724RIVER EC ;11
Adder
18.546
972231SS25-0005
Solar/Wind Harmer
9.923
972181SS23-001
Solar/Wind Harmer
6.202
274752CRETE EC ;2U
Adder
5.111
274753CRETE EC ;3U
Adder
5.111
970707AG2-453 GEN
Solar/Wind Harmer
29.165
274802UNIV PARK;5U
Adder
6.053
274826FISK ;BP
Adder
11.367
276772AC2-154 GEN
Solar/Wind Harmer
2.894
276806AD2-047 C O1
Solar/Wind Harmer
11.101
970941AG2-585 GEN
Solar/Wind Harmer
12.972
274800UNIV PARK;3U
Adder
6.049
972038AH1-567 GEN2
Adder
0.379
972228AH1-698 GEN2
Adder
3.843
24441205WTRV SLR C
Solar/Wind Harmer
0.14
276897AD1-100 C
Solar/Wind Harmer
30.017
939351AE1-166 GEN
Solar/Wind Harmer
6.133
274676JOLIET 29;8U
Adder
30.524
274729ELWOOD EC;1P
Adder
16.929
274730ELWOOD EC;6P
Adder
16.929
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
276893AG1-478 C
Solar/Wind Harmer
0.43
247604X1-042
Adder
0.428
943121AE2-341 GEN
Solar/Wind Harmer
15.389
943591AF1-030 GEN
Solar/Wind Harmer
10.259
270535AF1-215 GEN1
Solar/Wind Harmer
4.661
276694AA1-018 GEN2
Solar/Wind Harmer
6.407
274682WAUKEGAN ;7U
Adder
18.234
964401AG1-302 GEN
Solar/Wind Harmer
9.192
274872LEEDK;1U
Solar/Wind Harmer
0.258
276805AD2-038 GEN
Solar/Wind Harmer
5.164
959141AF2-205 GEN
Solar/Wind Harmer
6.057
276799AD1-013 GEN
Solar/Wind Harmer
2.212
946671AF1-331 GEN
Solar/Wind Harmer
0.419
274855GSG-6 ;RU
Solar/Wind Harmer
3.694
274850MENDOTA H;RU
Solar/Wind Harmer
2.568
276602WESTBROOK C
Solar/Wind Harmer
2.126
276863AD2-134 GEN
Solar/Wind Harmer
1.786
972236AH1-702 GEN2
Adder
2.173
274760LEE CO EC;1U
Adder
9.125
274767LEE CO EC;8U
Adder
9.017
24721905FLATG4
Adder
18.071
958381AF2-132 GEN
Solar/Wind Harmer
9.192
964861AG1-349 GEN
Solar/Wind Harmer
7.954
971917AH1-482 GEN
Solar/Wind Harmer
9.179
960751AF2-366 GEN
Solar/Wind Harmer
2.894
962781AG1-127 GEN
Solar/Wind Harmer
9.594
939401AE1-172 GEN
Solar/Wind Harmer
14.049
274872LEEDK;1U
Solar/Wind Harmer
8.273
276901AD2-066 C O1
Solar/Wind Harmer
3.534
971997AH1-543 GEN
Solar/Wind Harmer
15.781
276861AD2-134 GEN
Solar/Wind Harmer
1.786
274822ROCKFORD ;11
Adder
19.489
972235AH1-702 GEN1
Adder
2.499
274761LEE CO EC;2U
Adder
9.125
274766LEE CO EC;7U
Adder
9.017
24721705FLATG2
Adder
18.071
971599AH1-298 GEN
50/50
10.378
270144AC1-141 ST1_
50/50
2.276
24653605MOTTVILLE
50/50
0.004
24643105BUCHANAN
50/50
0.014
962771AG1-126 GEN
Solar/Wind Harmer
80.816
971347AH1-153 GEN
Solar/Wind Harmer
16.9
270071AF1-092 GEN
Solar/Wind Harmer
16.402
971771AH1-392 GEN
Solar/Wind Harmer
9.684
960681AF2-359 GEN
Solar/Wind Harmer
4.052
971769AH1-391 GEN
Solar/Wind Harmer
10.7
274775LINCOLN ;6U
Adder
6.552
274776LINCOLN ;7U
Adder
6.552
274777LINCOLN ;8U
Adder
6.552
944161AF1-084 GEN
Solar/Wind Harmer
2.319
24729505KEY G4
Adder
6.795
274814UNIV PK N;0U
Adder
5.263
274807UNIV PK N;3U
Adder
5.252
274805UNIV PK N;1U
Adder
5.229
274811UNIV PK N;7U
Adder
5.217
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.056
960591AF2-350 GEN
Solar/Wind Harmer
10.377
972227AH1-698 GEN1
Adder
2.706
274687WILL CNTY;4U
Adder
28.853
274687WILL CNTY;4U
Adder
28.853
274675JOLIET 29;7U
Adder
31.655
274675JOLIET 29;7U
Adder
30.525
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
274735ELWOOD EC;4P
Adder
16.929
274728ELWOOD EC;5P
Adder
16.929
970833AG2-524 GEN
Solar/Wind Harmer
8.985
970833AG2-524 GEN
Solar/Wind Harmer
4.179
270536AF1-215 GEN2
Solar/Wind Harmer
4.661
274746AC1-111 G10
Adder
5.726
274744AC1-111 GEN8
Adder
5.726
958391AF2-133 GEN
Solar/Wind Harmer
9.133
276868AE1-113 GEN
Solar/Wind Harmer
10.155
276882AE2-255 GEN
Solar/Wind Harmer
3.385
971177AH1-047 GEN
Solar/Wind Harmer
5.878
270284AF1-227 GEN1
Solar/Wind Harmer
5.666
270286AF1-227 GEN2
Solar/Wind Harmer
2.096
270287AF1-227 GEN3
Solar/Wind Harmer
2.096
971675AH1-338 GEN
Solar/Wind Harmer
18.004
971411AH1-196 GEN
Solar/Wind Harmer
15.003
274823ROCKFORD ;21
Adder
19.348
270102X2-052 ST
50/50
1.723
270100X2-052 CT1
50/50
1.588
270101X2-052 CT2
50/50
1.588
247620Y3-023
50/50
0.52
970615AG2-402 GEN
50/50
2.471
970321AG2-212 GEN
Solar/Wind Harmer
19.945
270216AD2-079_GEN
Solar/Wind Harmer
0.652
270471AD2-092_GEN
Solar/Wind Harmer
3.906
965681AG1-436 GEN
Solar/Wind Harmer
13.408
965791AG1-447 GEN
Solar/Wind Harmer
6.86
270526AF1-158 GEN
Solar/Wind Harmer
4.867
24441505OLIV SLR
Solar/Wind Harmer
0.143
957891AF2-083 GEN
Solar/Wind Harmer
3.59
960981AF2-389 GEN
Solar/Wind Harmer
1.609
970611AG2-400 GEN
Solar/Wind Harmer
10.627
961051AF2-396 GEN
Solar/Wind Harmer
16.791
961051AF2-396 GEN
Solar/Wind Harmer
7.81
274770LINCOLN ;1U
Adder
6.552
274771LINCOLN ;2U
Adder
6.552
274808UNIV PK N;4U
Adder
5.195
972259AH1-714 GEN
Adder
19.81
274803UNIV PARK;6U
Adder
6.053
274888KELLY CRK;1U
Solar/Wind Harmer
6.127
274887GEN-1.85
Solar/Wind Harmer
5.531
276843GEN-1.7
Solar/Wind Harmer
0.595
958011AF2-095 GEN
Solar/Wind Harmer
14.944
274674JOLIET 9 ;6U
Adder
15.867
274847GR RIDGE ;BU
Solar/Wind Harmer
5.204
971573AH1-285 GEN
Solar/Wind Harmer
8.786
274696ROCKY RD ;4P
Adder
11.577
274695ROCKY RD ;2P
Adder
11.31
274693ROCKY RD ;1P
Adder
11.199
274697ROCKY RD ;3P
Adder
3.072
958481AF2-142 GEN
Solar/Wind Harmer
15.23
274861TOP CROP ;1U
Solar/Wind Harmer
6.15
274862TOP CROP ;2U
Solar/Wind Harmer
5.135
274683WAUKEGAN ;8U
Adder
21.36
274683WAUKEGAN ;8U
Adder
18.005
962691AG1-118 GEN
Solar/Wind Harmer
30.32
970921AG2-575 GEN
Solar/Wind Harmer
10.088
970921AG2-575 GEN
Solar/Wind Harmer
2.346
958491AF2-143 GEN
Solar/Wind Harmer
15.1
942991AE2-321 GEN
Solar/Wind Harmer
10.034
274879MINONK ;1U
Solar/Wind Harmer
6.77
274764LEE CO EC;5U
Adder
9.146
274765LEE CO EC;6U
Adder
9.146
274762LEE CO EC;3U
Adder
9.125
274763LEE CO EC;4U
Adder
9.039
972267AH1-718 GEN
Adder
4.055
971333AH1-146 GEN
Solar/Wind Harmer
18.98
971335AH1-147 GEN
Solar/Wind Harmer
18.98
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.32
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.167
MECLTFEXP_MEC->PJM
CLTF
14.71
SIGELTFEXP_SIGE->PJM
CLTF
0.36
LAGNLTFEXP_LAGN->PJM
CLTF
11.516
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.671
TVALTFEXP_TVA->PJM
CLTF
5.244
CPLELTFEXP_CPLE->PJM
CLTF
1.375
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.414
NYPJM->LTFIMP_NY
CLTF
2.724
LGEELTFEXP_LGEE->PJM
CLTF
4.084
WECLTFEXP_WEC->PJM
CLTF
3.783
AG2-052LTFEXP_AG2-052->PJM
LTF
0.235
AH1-155LTFEXP_AH1-155->PJM
LTF
0.353

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT5_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT5_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.79 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4298.86
MW Contribution:31.91
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.571
24641605TWIN BRNCH
50/50
0.019
270475AD2-096_GEN
50/50
6.252
24344005CKG1
50/50
7.002
24642205MAYFLWER
50/50
0.719
970153AG2-106 GEN
Solar/Wind Harmer
35.245
970349AG2-230 GEN
Solar/Wind Harmer
16.906
970513AG2-328 GEN
Solar/Wind Harmer
19.953
970517AG2-330 GEN
Solar/Wind Harmer
18.097
270043AE2-236 GEN
Solar/Wind Harmer
6.131
247643Z2-116 C
Solar/Wind Harmer
0.075
944531AF1-118 GEN
Solar/Wind Harmer
37.285
970031AG2-029 GEN
Solar/Wind Harmer
31.915
959331AF2-224 GEN
Solar/Wind Harmer
10.631
965021AG1-366 GEN
Solar/Wind Harmer
2.472
945111AF1-176 GEN
Solar/Wind Harmer
6.009
274772LINCOLN ;3U
Adder
6.555
274724RIVER EC ;11
Adder
18.553
972231SS25-0005
Solar/Wind Harmer
9.927
972181SS23-001
Solar/Wind Harmer
6.205
274752CRETE EC ;2U
Adder
5.113
274753CRETE EC ;3U
Adder
5.113
970707AG2-453 GEN
Solar/Wind Harmer
29.177
274826FISK ;BP
Adder
11.371
274802UNIV PARK;5U
Adder
6.056
276772AC2-154 GEN
Solar/Wind Harmer
2.895
276806AD2-047 C O1
Solar/Wind Harmer
11.106
970941AG2-585 GEN
Solar/Wind Harmer
12.977
274800UNIV PARK;3U
Adder
6.051
972038AH1-567 GEN2
Adder
0.379
972228AH1-698 GEN2
Adder
3.844
24441205WTRV SLR C
Solar/Wind Harmer
0.14
276897AD1-100 C
Solar/Wind Harmer
30.029
939351AE1-166 GEN
Solar/Wind Harmer
6.136
274676JOLIET 29;8U
Adder
30.536
24344105CKG2
50/50
8.745
270143AC1-141 CT2_
50/50
2.571
24639705ELKHART HY
50/50
0.174
970521AG2-332 GEN
50/50
12.401
962761AG1-125 GEN
Solar/Wind Harmer
80.829
970149AG2-104 GEN
Solar/Wind Harmer
99.824
970155AG2-107 GEN
Solar/Wind Harmer
35.245
970245AG2-165 GEN
Solar/Wind Harmer
19.953
270349AD2-093_GEN
Solar/Wind Harmer
3.907
270063AE2-323 C
Solar/Wind Harmer
2.356
270505AE1-170 C O1
Solar/Wind Harmer
15.982
965011AG1-365 GEN
Solar/Wind Harmer
10.631
945111AF1-176 GEN
Solar/Wind Harmer
18.959
972207SS24-0001
Solar/Wind Harmer
23.305
274773LINCOLN ;4U
Adder
6.555
274774LINCOLN ;5U
Adder
6.555
270449AD2-020 GEN
Solar/Wind Harmer
2.959
943021AE2-325 GEN
Solar/Wind Harmer
3.845
274723RIVER EC ;12
Adder
18.77
274751CRETE EC ;1U
Adder
5.113
274754CRETE EC ;4U
Adder
5.113
276164X3-005 C
Solar/Wind Harmer
0.734
274812UNIV PK N;8U
Adder
5.219
970373AG2-245 GEN
Solar/Wind Harmer
21.854
276776AD2-060 GEN
Solar/Wind Harmer
0.439
274801UNIV PARK;4U
Adder
6.051
941551AE2-152 GEN
Solar/Wind Harmer
4.693
274676JOLIET 29;8U
Adder
31.667
274674JOLIET 9 ;6U
Adder
15.873
274732ELWOOD EC;7P
Adder
16.936
274871GR RIDGE ;2U
Solar/Wind Harmer
7.915
270055AF2-134 C O1
Solar/Wind Harmer
3.108
274745AC1-111 GEN9
Adder
5.728
276691AA1-018 GEN1
Solar/Wind Harmer
0.473
274682WAUKEGAN ;7U
Adder
18.241
274828WAUKEGAN ;BP
Adder
11.201
958381AF2-132 GEN
Solar/Wind Harmer
9.196
964861AG1-349 GEN
Solar/Wind Harmer
7.957
971917AH1-482 GEN
Solar/Wind Harmer
9.183
960751AF2-366 GEN
Solar/Wind Harmer
2.896
962781AG1-127 GEN
Solar/Wind Harmer
9.598
939401AE1-172 GEN
Solar/Wind Harmer
14.055
274872LEEDK;1U
Solar/Wind Harmer
8.276
276901AD2-066 C O1
Solar/Wind Harmer
3.535
971997AH1-543 GEN
Solar/Wind Harmer
15.787
276861AD2-134 GEN
Solar/Wind Harmer
1.787
274822ROCKFORD ;11
Adder
19.497
972235AH1-702 GEN1
Adder
2.5
274761LEE CO EC;2U
Adder
9.128
274766LEE CO EC;7U
Adder
9.021
24721705FLATG2
Adder
18.079
274729ELWOOD EC;1P
Adder
16.936
274730ELWOOD EC;6P
Adder
16.936
274734ELWOOD EC;8P
Adder
16.936
274736ELWOOD EC;9P
Adder
16.936
276893AG1-478 C
Solar/Wind Harmer
0.43
247604X1-042
Adder
0.428
270535AF1-215 GEN1
Solar/Wind Harmer
4.663
943121AE2-341 GEN
Solar/Wind Harmer
15.395
943591AF1-030 GEN
Solar/Wind Harmer
10.263
276694AA1-018 GEN2
Solar/Wind Harmer
6.41
274682WAUKEGAN ;7U
Adder
18.241
964401AG1-302 GEN
Solar/Wind Harmer
9.196
274872LEEDK;1U
Solar/Wind Harmer
0.258
276805AD2-038 GEN
Solar/Wind Harmer
5.166
959141AF2-205 GEN
Solar/Wind Harmer
6.06
276799AD1-013 GEN
Solar/Wind Harmer
2.213
946671AF1-331 GEN
Solar/Wind Harmer
0.419
274855GSG-6 ;RU
Solar/Wind Harmer
3.695
274850MENDOTA H;RU
Solar/Wind Harmer
2.569
276602WESTBROOK C
Solar/Wind Harmer
2.127
276863AD2-134 GEN
Solar/Wind Harmer
1.787
972236AH1-702 GEN2
Adder
2.174
274760LEE CO EC;1U
Adder
9.128
274767LEE CO EC;8U
Adder
9.021
24721905FLATG4
Adder
18.079
270102X2-052 ST
50/50
1.724
270100X2-052 CT1
50/50
1.588
270101X2-052 CT2
50/50
1.588
247620Y3-023
50/50
0.52
970615AG2-402 GEN
50/50
2.472
970321AG2-212 GEN
Solar/Wind Harmer
19.953
270216AD2-079_GEN
Solar/Wind Harmer
0.652
270471AD2-092_GEN
Solar/Wind Harmer
3.907
965681AG1-436 GEN
Solar/Wind Harmer
13.413
965791AG1-447 GEN
Solar/Wind Harmer
6.862
270526AF1-158 GEN
Solar/Wind Harmer
4.869
24441505OLIV SLR
Solar/Wind Harmer
0.143
957891AF2-083 GEN
Solar/Wind Harmer
3.591
960981AF2-389 GEN
Solar/Wind Harmer
1.609
970611AG2-400 GEN
Solar/Wind Harmer
10.631
961051AF2-396 GEN
Solar/Wind Harmer
16.797
961051AF2-396 GEN
Solar/Wind Harmer
7.813
274770LINCOLN ;1U
Adder
6.555
274771LINCOLN ;2U
Adder
6.555
274808UNIV PK N;4U
Adder
5.197
972259AH1-714 GEN
Adder
19.818
274803UNIV PARK;6U
Adder
6.056
274888KELLY CRK;1U
Solar/Wind Harmer
6.129
274887GEN-1.85
Solar/Wind Harmer
5.534
276843GEN-1.7
Solar/Wind Harmer
0.595
958011AF2-095 GEN
Solar/Wind Harmer
14.949
274674JOLIET 9 ;6U
Adder
15.873
274847GR RIDGE ;BU
Solar/Wind Harmer
5.206
971573AH1-285 GEN
Solar/Wind Harmer
8.79
274695ROCKY RD ;2P
Adder
11.315
274693ROCKY RD ;1P
Adder
11.203
274697ROCKY RD ;3P
Adder
3.074
274696ROCKY RD ;4P
Adder
11.582
958481AF2-142 GEN
Solar/Wind Harmer
15.236
274861TOP CROP ;1U
Solar/Wind Harmer
6.152
274862TOP CROP ;2U
Solar/Wind Harmer
5.137
274683WAUKEGAN ;8U
Adder
21.368
274683WAUKEGAN ;8U
Adder
18.013
962691AG1-118 GEN
Solar/Wind Harmer
30.332
970921AG2-575 GEN
Solar/Wind Harmer
10.092
970921AG2-575 GEN
Solar/Wind Harmer
2.347
958491AF2-143 GEN
Solar/Wind Harmer
15.106
942991AE2-321 GEN
Solar/Wind Harmer
10.038
274879MINONK ;1U
Solar/Wind Harmer
6.773
274764LEE CO EC;5U
Adder
9.15
274765LEE CO EC;6U
Adder
9.15
274762LEE CO EC;3U
Adder
9.128
274763LEE CO EC;4U
Adder
9.042
972267AH1-718 GEN
Adder
4.057
971333AH1-146 GEN
Solar/Wind Harmer
18.988
971335AH1-147 GEN
Solar/Wind Harmer
18.988
971599AH1-298 GEN
50/50
10.381
270144AC1-141 ST1_
50/50
2.277
24653605MOTTVILLE
50/50
0.004
24643105BUCHANAN
50/50
0.014
962771AG1-126 GEN
Solar/Wind Harmer
80.829
971347AH1-153 GEN
Solar/Wind Harmer
16.906
270071AF1-092 GEN
Solar/Wind Harmer
16.409
971771AH1-392 GEN
Solar/Wind Harmer
9.687
960681AF2-359 GEN
Solar/Wind Harmer
4.054
971769AH1-391 GEN
Solar/Wind Harmer
10.704
274775LINCOLN ;6U
Adder
6.555
274776LINCOLN ;7U
Adder
6.555
274777LINCOLN ;8U
Adder
6.555
944161AF1-084 GEN
Solar/Wind Harmer
2.32
24729505KEY G4
Adder
6.798
274814UNIV PK N;0U
Adder
5.265
274807UNIV PK N;3U
Adder
5.254
274805UNIV PK N;1U
Adder
5.231
274811UNIV PK N;7U
Adder
5.219
274827FISK ;RP
Adder
8.059
972037AH1-567 GEN1
Adder
0.19
960591AF2-350 GEN
Solar/Wind Harmer
10.382
972227AH1-698 GEN1
Adder
2.707
274687WILL CNTY;4U
Adder
28.864
274687WILL CNTY;4U
Adder
28.864
274675JOLIET 29;7U
Adder
31.668
274675JOLIET 29;7U
Adder
30.537
274731ELWOOD EC;2P
Adder
16.936
274733ELWOOD EC;3P
Adder
16.936
274735ELWOOD EC;4P
Adder
16.936
274728ELWOOD EC;5P
Adder
16.936
970833AG2-524 GEN
Solar/Wind Harmer
8.989
970833AG2-524 GEN
Solar/Wind Harmer
4.181
270536AF1-215 GEN2
Solar/Wind Harmer
4.663
274746AC1-111 G10
Adder
5.728
274744AC1-111 GEN8
Adder
5.728
958391AF2-133 GEN
Solar/Wind Harmer
9.137
276868AE1-113 GEN
Solar/Wind Harmer
10.159
276882AE2-255 GEN
Solar/Wind Harmer
3.386
971177AH1-047 GEN
Solar/Wind Harmer
5.881
270284AF1-227 GEN1
Solar/Wind Harmer
5.668
270286AF1-227 GEN2
Solar/Wind Harmer
2.097
270287AF1-227 GEN3
Solar/Wind Harmer
2.097
971675AH1-338 GEN
Solar/Wind Harmer
18.012
971411AH1-196 GEN
Solar/Wind Harmer
15.009
274823ROCKFORD ;21
Adder
19.356
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.38
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.182
MECLTFEXP_MEC->PJM
CLTF
14.717
SIGELTFEXP_SIGE->PJM
CLTF
0.36
LAGNLTFEXP_LAGN->PJM
CLTF
11.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.683
TVALTFEXP_TVA->PJM
CLTF
5.248
CPLELTFEXP_CPLE->PJM
CLTF
1.38
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.47
NYPJM->LTFIMP_NY
CLTF
2.721
LGEELTFEXP_LGEE->PJM
CLTF
4.087
WECLTFEXP_WEC->PJM
CLTF
3.784
AG2-052LTFEXP_AG2-052->PJM
LTF
0.235
AH1-155LTFEXP_AH1-155->PJM
LTF
0.353

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.2 %
Rating:4142.0 MVA
Rating Type:A
MVA to Mitigate:4150.44
MW Contribution:4.83
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
8.761
270143AC1-141 CT2_
50/50
2.576
24639705ELKHART HY
50/50
0.174
970521AG2-332 GEN
50/50
12.426
962761AG1-125 GEN
Solar/Wind Harmer
68.224
970149AG2-104 GEN
Solar/Wind Harmer
73.684
970155AG2-107 GEN
Solar/Wind Harmer
43.566
970245AG2-165 GEN
Solar/Wind Harmer
3.385
270349AD2-093_GEN
Solar/Wind Harmer
0.006
270063AE2-323 C
Solar/Wind Harmer
0.006
270505AE1-170 C O1
Solar/Wind Harmer
7.821
965011AG1-365 GEN
Solar/Wind Harmer
7.432
945111AF1-176 GEN
Solar/Wind Harmer
13.254
274773LINCOLN ;4U
Adder
8.941
274774LINCOLN ;5U
Adder
8.941
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.852
274723RIVER EC ;12
Adder
18.809
274751CRETE EC ;1U
Adder
8.637
274754CRETE EC ;4U
Adder
8.637
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.23
970373AG2-245 GEN
Solar/Wind Harmer
15.278
276776AD2-060 GEN
Solar/Wind Harmer
0.758
274801UNIV PARK;4U
Adder
6.064
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.733
274674JOLIET 9 ;6U
Adder
15.907
274732ELWOOD EC;7P
Adder
16.972
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
270142AC1-141 CT1_
50/50
2.576
24641605TWIN BRNCH
50/50
0.019
270475AD2-096_GEN
50/50
6.265
24344005CKG1
50/50
7.016
24642205MAYFLWER
50/50
0.721
970153AG2-106 GEN
Solar/Wind Harmer
43.566
970349AG2-230 GEN
Solar/Wind Harmer
11.817
970513AG2-328 GEN
Solar/Wind Harmer
3.385
970517AG2-330 GEN
Solar/Wind Harmer
20.307
270043AE2-236 GEN
Solar/Wind Harmer
5
247643Z2-116 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
33.376
970031AG2-029 GEN
Solar/Wind Harmer
4.834
959331AF2-224 GEN
Solar/Wind Harmer
5.202
965021AG1-366 GEN
Solar/Wind Harmer
2.477
945111AF1-176 GEN
Solar/Wind Harmer
6.021
274772LINCOLN ;3U
Adder
8.941
274724RIVER EC ;11
Adder
18.592
274752CRETE EC ;2U
Adder
8.637
274753CRETE EC ;3U
Adder
8.637
970707AG2-453 GEN
Solar/Wind Harmer
23.798
274826FISK ;BP
Adder
11.395
274802UNIV PARK;5U
Adder
6.068
276806AD2-047 C O1
Solar/Wind Harmer
4.113
970941AG2-585 GEN
Solar/Wind Harmer
9.072
274800UNIV PARK;3U
Adder
6.064
972038AH1-567 GEN2
Adder
0.38
972228AH1-698 GEN2
Adder
3.852
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.6
274729ELWOOD EC;1P
Adder
16.971
274730ELWOOD EC;6P
Adder
16.972
274734ELWOOD EC;8P
Adder
16.972
274736ELWOOD EC;9P
Adder
16.972
276893AG1-478 C
Solar/Wind Harmer
0.285
247604X1-042
Adder
0.429
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
12.031
943591AF1-030 GEN
Solar/Wind Harmer
8
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.28
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.258
276805AD2-038 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.747
274745AC1-111 GEN9
Adder
5.741
276691AA1-018 GEN1
Solar/Wind Harmer
0.86
274682WAUKEGAN ;7U
Adder
18.28
274828WAUKEGAN ;BP
Adder
11.225
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.202
962781AG1-127 GEN
Solar/Wind Harmer
6.715
939401AE1-172 GEN
Solar/Wind Harmer
5.274
274872LEEDK;1U
Solar/Wind Harmer
0.004
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.679
276861AD2-134 GEN
Solar/Wind Harmer
0.125
965651AG1-433 GEN
Solar/Wind Harmer
2.05
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.708
957471AF2-041 GEN
Solar/Wind Harmer
20.89
959081AF2-199 GEN
Solar/Wind Harmer
6.963
971067AG2-660 GEN
Solar/Wind Harmer
2.321
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.54
972235AH1-702 GEN1
Adder
2.505
970819AG2-516 GEN
Solar/Wind Harmer
8.301
971475AH1-234 GEN
Solar/Wind Harmer
3.35
970569AG2-363 GEN
Solar/Wind Harmer
20.699
958861AF2-177 GEN
Solar/Wind Harmer
2.981
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.148
274766LEE CO EC;7U
Adder
9.041
276158O29GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.227
247521TR3_G114
Solar/Wind Harmer
0.245
270246TR4_N_V150
Solar/Wind Harmer
0.043
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.414
945371AF1-202 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.771
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24695305TIMB G C
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
5.377
965421AG1-410 GEN
Solar/Wind Harmer
19.447
970291AG2-192 GEN
Solar/Wind Harmer
0.832
274880W4-005 GEN4
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.259
270489AE1-102 GEN1
Solar/Wind Harmer
0.83
963831AG1-236 GEN
Solar/Wind Harmer
2.479
963741AG1-226 GEN
Solar/Wind Harmer
15.028
270032AE2-172
Solar/Wind Harmer
4.213
276615X2-022 GEN
Solar/Wind Harmer
0.066
24721705FLATG2
Adder
18.123
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
6.907
270005AE1-210 C O1
Solar/Wind Harmer
1.338
965031AG1-367 GEN
Solar/Wind Harmer
6.174
965911AG1-460 GEN
Solar/Wind Harmer
1.231
970825AG2-519 GEN
Solar/Wind Harmer
2.158
274855GSG-6 ;RU
Solar/Wind Harmer
0.257
274850MENDOTA H;RU
Solar/Wind Harmer
0.082
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.125
959091AF2-200 GEN
Solar/Wind Harmer
13.927
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.178
970571AG2-364 GEN
Solar/Wind Harmer
13.8
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.148
274767LEE CO EC;8U
Adder
9.041
276157O29GEN1
Solar/Wind Harmer
1.1
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.767
274878BISHOP HL;2U
Solar/Wind Harmer
0.227
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.043
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.944
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.925
959611AF2-252 GEN
Solar/Wind Harmer
2.214
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.704
970291AG2-192 GEN
Solar/Wind Harmer
0.64
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.949
270491AE1-102 GEN2
Solar/Wind Harmer
0.83
276668AB2-070 GEN1
Solar/Wind Harmer
0.233
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
971617AH1-308 GEN
Solar/Wind Harmer
5.233
24721905FLATG4
Adder
18.123
270391AF1-285 GEN3
Solar/Wind Harmer
0.412
958821AF2-173 GEN
Solar/Wind Harmer
8.644
270004AE1-209 GEN
Solar/Wind Harmer
1.338
942481AE2-261 GEN
Solar/Wind Harmer
18.406
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270404AC1-167 GEN
Solar/Wind Harmer
0.003
946031AF1-268 GEN
Solar/Wind Harmer
5.724
971599AH1-298 GEN
50/50
10.4
270144AC1-141 ST1_
50/50
2.281
24653605MOTTVILLE
50/50
0.004
24643105BUCHANAN
50/50
0.014
962771AG1-126 GEN
Solar/Wind Harmer
68.224
971347AH1-153 GEN
Solar/Wind Harmer
11.817
270071AF1-092 GEN
Solar/Wind Harmer
14.657
971771AH1-392 GEN
Solar/Wind Harmer
7.525
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.356
971619AH1-309 GEN
Solar/Wind Harmer
3.352
274775LINCOLN ;6U
Adder
8.941
274776LINCOLN ;7U
Adder
8.941
274777LINCOLN ;8U
Adder
8.941
24729505KEY G4
Adder
6.812
274814UNIV PK N;0U
Adder
5.276
274807UNIV PK N;3U
Adder
5.265
274805UNIV PK N;1U
Adder
5.242
274811UNIV PK N;7U
Adder
5.23
274827FISK ;RP
Adder
8.075
972037AH1-567 GEN1
Adder
0.19
960591AF2-350 GEN
Solar/Wind Harmer
7.258
972227AH1-698 GEN1
Adder
2.712
274687WILL CNTY;4U
Adder
28.924
274687WILL CNTY;4U
Adder
28.924
274675JOLIET 29;7U
Adder
31.734
274675JOLIET 29;7U
Adder
30.6
274731ELWOOD EC;2P
Adder
16.971
274733ELWOOD EC;3P
Adder
16.971
274735ELWOOD EC;4P
Adder
16.971
274728ELWOOD EC;5P
Adder
16.972
970833AG2-524 GEN
Solar/Wind Harmer
7.918
970833AG2-524 GEN
Solar/Wind Harmer
5.279
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
274746AC1-111 G10
Adder
5.741
274744AC1-111 GEN8
Adder
5.741
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.408
276882AE2-255 GEN
Solar/Wind Harmer
0.821
971177AH1-047 GEN
Solar/Wind Harmer
4.327
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971675AH1-338 GEN
Solar/Wind Harmer
2.729
971411AH1-196 GEN
Solar/Wind Harmer
10.494
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971611AH1-305 GEN
Solar/Wind Harmer
4.147
971171AH1-044 GEN
Solar/Wind Harmer
13.927
274823ROCKFORD ;21
Adder
19.398
276612AE2-035 GEN
Solar/Wind Harmer
0.002
965041AG1-368 GEN
Solar/Wind Harmer
6.907
926823AC1-168 GEN
Solar/Wind Harmer
1.173
970169AG2-114 GEN
Solar/Wind Harmer
6.898
971681AH1-341 GEN
Solar/Wind Harmer
11.079
965101AG1-375 GEN
Solar/Wind Harmer
6.878
963791AG1-232 GEN
Solar/Wind Harmer
9.223
961011AF2-392 GEN
Solar/Wind Harmer
4.004
957751AF2-069 GEN
Solar/Wind Harmer
0.224
971549AH1-272 GEN
Solar/Wind Harmer
14.025
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
3.359
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.736
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.803
970289AG2-191 GEN
Solar/Wind Harmer
1.217
971609AH1-304 GEN
Solar/Wind Harmer
1.046
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.808
276849AB2-070 GEN2
Solar/Wind Harmer
0.233
276848AB2-070 GEN3
Solar/Wind Harmer
0.232
270594AE1-207 GEN
Solar/Wind Harmer
7.078
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270578AF1-285 GEN2
Solar/Wind Harmer
0.412
247607V1-011 GEN
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.44
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270102X2-052 ST
50/50
1.727
270100X2-052 CT1
50/50
1.592
270101X2-052 CT2
50/50
1.592
247620Y3-023
50/50
0.521
970615AG2-402 GEN
50/50
2.477
970321AG2-212 GEN
Solar/Wind Harmer
3.385
270216AD2-079_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.006
965681AG1-436 GEN
Solar/Wind Harmer
9.376
965791AG1-447 GEN
Solar/Wind Harmer
6.876
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
7.432
970627AG2-408 GEN
Solar/Wind Harmer
2.23
961051AF2-396 GEN
Solar/Wind Harmer
14.796
961051AF2-396 GEN
Solar/Wind Harmer
9.864
274770LINCOLN ;1U
Adder
8.941
274771LINCOLN ;2U
Adder
8.941
274808UNIV PK N;4U
Adder
5.207
972259AH1-714 GEN
Adder
19.859
274803UNIV PARK;6U
Adder
6.068
274888KELLY CRK;1U
Solar/Wind Harmer
0.426
274887GEN-1.85
Solar/Wind Harmer
0.191
276843GEN-1.7
Solar/Wind Harmer
0.235
958011AF2-095 GEN
Solar/Wind Harmer
10.451
274674JOLIET 9 ;6U
Adder
15.907
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.332
274695ROCKY RD ;2P
Adder
11.339
274693ROCKY RD ;1P
Adder
11.227
274697ROCKY RD ;3P
Adder
3.08
274696ROCKY RD ;4P
Adder
11.606
958481AF2-142 GEN
Solar/Wind Harmer
10.652
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.96
274683WAUKEGAN ;8U
Adder
21.414
274683WAUKEGAN ;8U
Adder
18.051
962691AG1-118 GEN
Solar/Wind Harmer
21.207
970921AG2-575 GEN
Solar/Wind Harmer
7.056
970921AG2-575 GEN
Solar/Wind Harmer
2.352
958491AF2-143 GEN
Solar/Wind Harmer
10.561
942991AE2-321 GEN
Solar/Wind Harmer
7.837
274879MINONK ;1U
Solar/Wind Harmer
0.296
971333AH1-146 GEN
Solar/Wind Harmer
13.985
971335AH1-147 GEN
Solar/Wind Harmer
13.985
944541AF1-119 GEN
Solar/Wind Harmer
0.468
960971AF2-388 GEN
Solar/Wind Harmer
4.1
971341AH1-150 GEN
Solar/Wind Harmer
13.927
971343AH1-151 GEN
Solar/Wind Harmer
13.927
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.163
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.898
274764LEE CO EC;5U
Adder
9.17
274765LEE CO EC;6U
Adder
9.17
274762LEE CO EC;3U
Adder
9.148
274763LEE CO EC;4U
Adder
9.062
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.066
276741O09 GEN1
Solar/Wind Harmer
0.242
276708O09 GEN2
Solar/Wind Harmer
0.242
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.267
276646AC1-214 GEN2
Solar/Wind Harmer
0.267
276782AC1-033 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.034
960611AF2-352 GEN
Solar/Wind Harmer
2.214
966841AG1-555 GEN
Solar/Wind Harmer
0.746
270599AE1-208 GEN
Solar/Wind Harmer
5.869
270031AE2-169
Solar/Wind Harmer
3.522
246938BC-WTG3
Solar/Wind Harmer
0.231
246937BC-WTG2
Solar/Wind Harmer
0.259
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.704
971613AH1-306 GEN
Solar/Wind Harmer
3.033
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
12.852
276911AD2-131_GEN
Solar/Wind Harmer
0.847
960441AF2-335 GEN
Solar/Wind Harmer
6.101
970623AG2-406 GEN
Solar/Wind Harmer
1.115
970825AG2-519 GEN
Solar/Wind Harmer
6.738
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.695
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.264
MECLTFEXP_MEC->PJM
CLTF
14.753
SIGELTFEXP_SIGE->PJM
CLTF
0.361
LAGNLTFEXP_LAGN->PJM
CLTF
11.568
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.749
TVALTFEXP_TVA->PJM
CLTF
5.27
CPLELTFEXP_CPLE->PJM
CLTF
1.403
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.76
NYPJM->LTFIMP_NY
CLTF
2.707
LGEELTFEXP_LGEE->PJM
CLTF
4.102
WECLTFEXP_WEC->PJM
CLTF
3.793
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.353

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.69 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6156.87
MW Contribution:37.21
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.786
24721905FLATG4
50/50
32.751
970153AG2-106 GEN
Solar/Wind Harmer
41.667
970513AG2-328 GEN
Solar/Wind Harmer
23.936
970517AG2-330 GEN
Solar/Wind Harmer
21.709
970349AG2-230 GEN
Solar/Wind Harmer
20.011
270043AE2-236 GEN
Solar/Wind Harmer
7.153
274772LINCOLN ;3U
Adder
7.877
247643Z2-116 C
Solar/Wind Harmer
0.088
24642205MAYFLWER
Adder
0.8
274724RIVER EC ;11
Adder
22.273
970707AG2-453 GEN
Solar/Wind Harmer
35.145
972231SS25-0005
Solar/Wind Harmer
11.912
972181SS23-001
Solar/Wind Harmer
7.445
274752CRETE EC ;2U
Adder
6.135
274753CRETE EC ;3U
Adder
6.135
944531AF1-118 GEN
Solar/Wind Harmer
43.883
274826FISK ;BP
Adder
13.685
274802UNIV PARK;5U
Adder
7.287
276772AC2-154 GEN
Solar/Wind Harmer
3.485
276806AD2-047 C O1
Solar/Wind Harmer
13.37
970941AG2-585 GEN
Solar/Wind Harmer
15.623
972228AH1-698 GEN2
Adder
4.629
274800UNIV PARK;3U
Adder
7.284
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.064
276897AD1-100 C
Solar/Wind Harmer
36.195
939351AE1-166 GEN
Solar/Wind Harmer
7.396
274676JOLIET 29;8U
Adder
36.814
274729ELWOOD EC;1P
Adder
20.424
274730ELWOOD EC;6P
Adder
20.425
274734ELWOOD EC;8P
Adder
20.425
274736ELWOOD EC;9P
Adder
20.425
276893AG1-478 C
Solar/Wind Harmer
0.519
970031AG2-029 GEN
Solar/Wind Harmer
37.211
943121AE2-341 GEN
Solar/Wind Harmer
18.593
943591AF1-030 GEN
Solar/Wind Harmer
12.395
270535AF1-215 GEN1
Solar/Wind Harmer
5.608
276694AA1-018 GEN2
Solar/Wind Harmer
7.75
274682WAUKEGAN ;7U
Adder
22.07
964401AG1-302 GEN
Solar/Wind Harmer
11.095
274872LEEDK;1U
Solar/Wind Harmer
0.312
276805AD2-038 GEN
Solar/Wind Harmer
6.257
959331AF2-224 GEN
Solar/Wind Harmer
12.175
965021AG1-366 GEN
Solar/Wind Harmer
2.831
24441205WTRV SLR C
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
2.685
946671AF1-331 GEN
Solar/Wind Harmer
0.508
274855GSG-6 ;RU
Solar/Wind Harmer
4.484
274850MENDOTA H;RU
Solar/Wind Harmer
3.118
276602WESTBROOK C
Solar/Wind Harmer
2.581
276863AD2-134 GEN
Solar/Wind Harmer
2.169
959141AF2-205 GEN
Solar/Wind Harmer
7.332
972236AH1-702 GEN2
Adder
2.642
247604X1-042
Adder
0.502
274760LEE CO EC;1U
Adder
11.12
274767LEE CO EC;8U
Adder
10.989
959091AF2-200 GEN
Solar/Wind Harmer
0.774
24721805FLATG3
50/50
1.786
24721705FLATG2
50/50
32.751
24344105CKG2
50/50
10.346
962761AG1-125 GEN
Solar/Wind Harmer
95.557
970149AG2-104 GEN
Solar/Wind Harmer
118.013
970155AG2-107 GEN
Solar/Wind Harmer
41.667
970245AG2-165 GEN
Solar/Wind Harmer
23.936
972207SS24-0001
Solar/Wind Harmer
28.005
274773LINCOLN ;4U
Adder
7.877
274774LINCOLN ;5U
Adder
7.877
274723RIVER EC ;12
Adder
22.533
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0.882
274751CRETE EC ;1U
Adder
6.135
274754CRETE EC ;4U
Adder
6.135
270505AE1-170 C O1
Solar/Wind Harmer
18.802
274812UNIV PK N;8U
Adder
6.272
276776AD2-060 GEN
Solar/Wind Harmer
0.528
274801UNIV PARK;4U
Adder
7.284
945111AF1-176 GEN
Solar/Wind Harmer
22.288
270063AE2-323 C
Solar/Wind Harmer
2.75
941551AE2-152 GEN
Solar/Wind Harmer
5.657
970373AG2-245 GEN
Solar/Wind Harmer
26.192
274676JOLIET 29;8U
Adder
38.177
274674JOLIET 9 ;6U
Adder
19.142
274732ELWOOD EC;7P
Adder
20.425
274871GR RIDGE ;2U
Solar/Wind Harmer
9.551
270449AD2-020 GEN
Solar/Wind Harmer
3.477
943021AE2-325 GEN
Solar/Wind Harmer
4.518
274745AC1-111 GEN9
Adder
6.919
270055AF2-134 C O1
Solar/Wind Harmer
3.738
276691AA1-018 GEN1
Solar/Wind Harmer
0.572
274682WAUKEGAN ;7U
Adder
22.07
274828WAUKEGAN ;BP
Adder
13.555
958381AF2-132 GEN
Solar/Wind Harmer
11.095
960751AF2-366 GEN
Solar/Wind Harmer
3.508
962781AG1-127 GEN
Solar/Wind Harmer
11.628
964861AG1-349 GEN
Solar/Wind Harmer
9.604
971917AH1-482 GEN
Solar/Wind Harmer
11.083
939401AE1-172 GEN
Solar/Wind Harmer
17.025
274872LEEDK;1U
Solar/Wind Harmer
10.03
276901AD2-066 C O1
Solar/Wind Harmer
4.283
965011AG1-365 GEN
Solar/Wind Harmer
12.175
971997AH1-543 GEN
Solar/Wind Harmer
19.145
276861AD2-134 GEN
Solar/Wind Harmer
2.169
274822ROCKFORD ;11
Adder
23.693
972235AH1-702 GEN1
Adder
3.039
274761LEE CO EC;2U
Adder
11.12
274766LEE CO EC;7U
Adder
10.989
970091AG2-072 GEN
Adder
5.216
957471AF2-041 GEN
Solar/Wind Harmer
1.161
959081AF2-199 GEN
Solar/Wind Harmer
0.387
971067AG2-660 GEN
Solar/Wind Harmer
0.09
270102X2-052 ST
50/50
2.048
270100X2-052 CT1
50/50
1.887
270101X2-052 CT2
50/50
1.887
970321AG2-212 GEN
Solar/Wind Harmer
23.936
965681AG1-436 GEN
Solar/Wind Harmer
15.956
965791AG1-447 GEN
Solar/Wind Harmer
8.164
274770LINCOLN ;1U
Adder
7.877
274771LINCOLN ;2U
Adder
7.877
270526AF1-158 GEN
Solar/Wind Harmer
5.766
24441505OLIV SLR
Solar/Wind Harmer
0.17
270216AD2-079_GEN
Solar/Wind Harmer
0.767
957891AF2-083 GEN
Solar/Wind Harmer
4.225
960981AF2-389 GEN
Solar/Wind Harmer
1.893
274808UNIV PK N;4U
Adder
6.245
972259AH1-714 GEN
Adder
23.874
274803UNIV PARK;6U
Adder
7.287
274888KELLY CRK;1U
Solar/Wind Harmer
7.379
274887GEN-1.85
Solar/Wind Harmer
6.662
276843GEN-1.7
Solar/Wind Harmer
0.717
958011AF2-095 GEN
Solar/Wind Harmer
17.998
247620Y3-023
Adder
0.575
961051AF2-396 GEN
Solar/Wind Harmer
19.743
961051AF2-396 GEN
Solar/Wind Harmer
9.183
274674JOLIET 9 ;6U
Adder
19.142
274847GR RIDGE ;BU
Solar/Wind Harmer
6.282
971573AH1-285 GEN
Solar/Wind Harmer
10.624
274695ROCKY RD ;2P
Adder
13.688
274693ROCKY RD ;1P
Adder
13.554
274697ROCKY RD ;3P
Adder
3.718
274696ROCKY RD ;4P
Adder
14.011
958481AF2-142 GEN
Solar/Wind Harmer
18.422
24721605FLATG1
50/50
1.786
971599AH1-298 GEN
50/50
12.095
962771AG1-126 GEN
Solar/Wind Harmer
95.557
971347AH1-153 GEN
Solar/Wind Harmer
20.011
270071AF1-092 GEN
Solar/Wind Harmer
19.32
960681AF2-359 GEN
Solar/Wind Harmer
4.823
971771AH1-392 GEN
Solar/Wind Harmer
11.437
274775LINCOLN ;6U
Adder
7.877
274776LINCOLN ;7U
Adder
7.877
274777LINCOLN ;8U
Adder
7.877
971769AH1-391 GEN
Solar/Wind Harmer
12.687
274814UNIV PK N;0U
Adder
6.327
274807UNIV PK N;3U
Adder
6.313
274805UNIV PK N;1U
Adder
6.286
274811UNIV PK N;7U
Adder
6.272
274827FISK ;RP
Adder
9.699
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
12.498
972227AH1-698 GEN1
Adder
3.26
274687WILL CNTY;4U
Adder
34.788
274687WILL CNTY;4U
Adder
34.788
274675JOLIET 29;7U
Adder
38.178
274675JOLIET 29;7U
Adder
36.814
274731ELWOOD EC;2P
Adder
20.424
274733ELWOOD EC;3P
Adder
20.424
274735ELWOOD EC;4P
Adder
20.424
274728ELWOOD EC;5P
Adder
20.425
970833AG2-524 GEN
Solar/Wind Harmer
10.846
970833AG2-524 GEN
Solar/Wind Harmer
5.045
274746AC1-111 G10
Adder
6.919
274744AC1-111 GEN8
Adder
6.919
24729505KEY G4
Adder
8.014
270536AF1-215 GEN2
Solar/Wind Harmer
5.608
944161AF1-084 GEN
Solar/Wind Harmer
2.725
958391AF2-133 GEN
Solar/Wind Harmer
11.042
971177AH1-047 GEN
Solar/Wind Harmer
7.132
276868AE1-113 GEN
Solar/Wind Harmer
12.314
276882AE2-255 GEN
Solar/Wind Harmer
4.105
971675AH1-338 GEN
Solar/Wind Harmer
21.857
971411AH1-196 GEN
Solar/Wind Harmer
18.212
274863CRW1-WTG
Solar/Wind Harmer
6.762
274864CRW2-WTG
Solar/Wind Harmer
6.762
274823ROCKFORD ;21
Adder
23.521
270054AF2-122 C O1
Solar/Wind Helper
1.549
971171AH1-044 GEN
Solar/Wind Harmer
0.774
274861TOP CROP ;1U
Solar/Wind Harmer
7.44
274862TOP CROP ;2U
Solar/Wind Harmer
6.212
274683WAUKEGAN ;8U
Adder
25.859
274683WAUKEGAN ;8U
Adder
21.798
962691AG1-118 GEN
Solar/Wind Harmer
36.735
970921AG2-575 GEN
Solar/Wind Harmer
12.227
970921AG2-575 GEN
Solar/Wind Harmer
2.844
958491AF2-143 GEN
Solar/Wind Harmer
18.296
970611AG2-400 GEN
Solar/Wind Harmer
12.175
942991AE2-321 GEN
Solar/Wind Harmer
12.173
274879MINONK ;1U
Solar/Wind Harmer
8.21
971333AH1-146 GEN
Solar/Wind Harmer
24.274
971335AH1-147 GEN
Solar/Wind Harmer
24.274
274764LEE CO EC;5U
Adder
11.146
274765LEE CO EC;6U
Adder
11.146
274762LEE CO EC;3U
Adder
11.12
274763LEE CO EC;4U
Adder
11.015
972267AH1-718 GEN
Adder
4.949
971341AH1-150 GEN
Solar/Wind Harmer
0.774
971343AH1-151 GEN
Solar/Wind Harmer
0.774
944201AF1-088_MTX
Adder
117.628
957141AF2-008_MTX
Adder
58.814
CBM West 1LTFEXP_CBM-W1->PJM
CBM
145.765
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.894
MECLTFEXP_MEC->PJM
CLTF
18.376
SIGELTFEXP_SIGE->PJM
CLTF
0.47
LAGNLTFEXP_LAGN->PJM
CLTF
16.151
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.809
TVALTFEXP_TVA->PJM
CLTF
7.633
CPLELTFEXP_CPLE->PJM
CLTF
3.161
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.296
NYPJM->LTFIMP_NY
CLTF
3.802
LGEELTFEXP_LGEE->PJM
CLTF
5.477
WECLTFEXP_WEC->PJM
CLTF
4.602
AG2-052LTFEXP_AG2-052->PJM
LTF
0.284
AH1-155LTFEXP_AH1-155->PJM
LTF
0.425

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.13 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6039.56
MW Contribution:37.45
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.796
24721905FLATG4
50/50
32.926
970153AG2-106 GEN
Solar/Wind Harmer
41.782
970513AG2-328 GEN
Solar/Wind Harmer
24.08
970517AG2-330 GEN
Solar/Wind Harmer
21.84
970349AG2-230 GEN
Solar/Wind Harmer
20.131
270043AE2-236 GEN
Solar/Wind Harmer
7.197
274772LINCOLN ;3U
Adder
7.927
247643Z2-116 C
Solar/Wind Harmer
0.089
24642205MAYFLWER
Adder
0.805
274724RIVER EC ;11
Adder
22.416
970707AG2-453 GEN
Solar/Wind Harmer
35.371
972231SS25-0005
Solar/Wind Harmer
11.989
972181SS23-001
Solar/Wind Harmer
7.493
274752CRETE EC ;2U
Adder
6.174
274753CRETE EC ;3U
Adder
6.174
944531AF1-118 GEN
Solar/Wind Harmer
44.166
274826FISK ;BP
Adder
13.773
274802UNIV PARK;5U
Adder
7.334
276772AC2-154 GEN
Solar/Wind Harmer
3.508
276806AD2-047 C O1
Solar/Wind Harmer
13.456
970941AG2-585 GEN
Solar/Wind Harmer
15.724
972228AH1-698 GEN2
Adder
4.659
274800UNIV PARK;3U
Adder
7.331
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.109
276897AD1-100 C
Solar/Wind Harmer
36.429
939351AE1-166 GEN
Solar/Wind Harmer
7.443
274676JOLIET 29;8U
Adder
37.052
274729ELWOOD EC;1P
Adder
20.557
274730ELWOOD EC;6P
Adder
20.557
274734ELWOOD EC;8P
Adder
20.557
274736ELWOOD EC;9P
Adder
20.557
276893AG1-478 C
Solar/Wind Harmer
0.522
970031AG2-029 GEN
Solar/Wind Harmer
37.453
943121AE2-341 GEN
Solar/Wind Harmer
18.714
943591AF1-030 GEN
Solar/Wind Harmer
12.476
270535AF1-215 GEN1
Solar/Wind Harmer
5.645
276694AA1-018 GEN2
Solar/Wind Harmer
7.801
274682WAUKEGAN ;7U
Adder
22.214
964401AG1-302 GEN
Solar/Wind Harmer
11.168
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
6.299
959331AF2-224 GEN
Solar/Wind Harmer
12.256
965021AG1-366 GEN
Solar/Wind Harmer
2.85
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276799AD1-013 GEN
Solar/Wind Harmer
2.703
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
4.514
274850MENDOTA H;RU
Solar/Wind Harmer
3.139
276602WESTBROOK C
Solar/Wind Harmer
2.598
276863AD2-134 GEN
Solar/Wind Harmer
2.183
959141AF2-205 GEN
Solar/Wind Harmer
7.381
972236AH1-702 GEN2
Adder
2.66
247604X1-042
Adder
0.505
274760LEE CO EC;1U
Adder
11.195
274767LEE CO EC;8U
Adder
11.063
959091AF2-200 GEN
Solar/Wind Harmer
0.779
24721805FLATG3
50/50
1.796
24721705FLATG2
50/50
32.926
24344105CKG2
50/50
10.407
962761AG1-125 GEN
Solar/Wind Harmer
95.82
970149AG2-104 GEN
Solar/Wind Harmer
118.338
970155AG2-107 GEN
Solar/Wind Harmer
41.782
970245AG2-165 GEN
Solar/Wind Harmer
24.08
972207SS24-0001
Solar/Wind Harmer
28.182
274773LINCOLN ;4U
Adder
7.927
274774LINCOLN ;5U
Adder
7.927
274723RIVER EC ;12
Adder
22.677
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0.888
274751CRETE EC ;1U
Adder
6.174
274754CRETE EC ;4U
Adder
6.174
270505AE1-170 C O1
Solar/Wind Harmer
18.922
274812UNIV PK N;8U
Adder
6.313
276776AD2-060 GEN
Solar/Wind Harmer
0.532
274801UNIV PARK;4U
Adder
7.331
945111AF1-176 GEN
Solar/Wind Harmer
22.432
270063AE2-323 C
Solar/Wind Harmer
2.768
941551AE2-152 GEN
Solar/Wind Harmer
5.693
970373AG2-245 GEN
Solar/Wind Harmer
26.361
274676JOLIET 29;8U
Adder
38.424
274674JOLIET 9 ;6U
Adder
19.265
274732ELWOOD EC;7P
Adder
20.557
274871GR RIDGE ;2U
Solar/Wind Harmer
9.612
270449AD2-020 GEN
Solar/Wind Harmer
3.5
943021AE2-325 GEN
Solar/Wind Harmer
4.548
274745AC1-111 GEN9
Adder
6.964
270055AF2-134 C O1
Solar/Wind Harmer
3.763
276691AA1-018 GEN1
Solar/Wind Harmer
0.576
274682WAUKEGAN ;7U
Adder
22.214
274828WAUKEGAN ;BP
Adder
13.643
958381AF2-132 GEN
Solar/Wind Harmer
11.168
960751AF2-366 GEN
Solar/Wind Harmer
3.531
962781AG1-127 GEN
Solar/Wind Harmer
11.704
964861AG1-349 GEN
Solar/Wind Harmer
9.667
971917AH1-482 GEN
Solar/Wind Harmer
11.156
939401AE1-172 GEN
Solar/Wind Harmer
17.137
274872LEEDK;1U
Solar/Wind Harmer
10.096
276901AD2-066 C O1
Solar/Wind Harmer
4.312
965011AG1-365 GEN
Solar/Wind Harmer
12.256
971997AH1-543 GEN
Solar/Wind Harmer
19.271
276861AD2-134 GEN
Solar/Wind Harmer
2.183
274822ROCKFORD ;11
Adder
23.85
972235AH1-702 GEN1
Adder
3.059
274761LEE CO EC;2U
Adder
11.195
274766LEE CO EC;7U
Adder
11.063
970091AG2-072 GEN
Adder
5.259
957471AF2-041 GEN
Solar/Wind Harmer
1.169
959081AF2-199 GEN
Solar/Wind Harmer
0.39
971067AG2-660 GEN
Solar/Wind Harmer
0.091
270102X2-052 ST
50/50
2.061
270100X2-052 CT1
50/50
1.899
270101X2-052 CT2
50/50
1.899
970321AG2-212 GEN
Solar/Wind Harmer
24.08
965681AG1-436 GEN
Solar/Wind Harmer
16.057
965791AG1-447 GEN
Solar/Wind Harmer
8.215
274770LINCOLN ;1U
Adder
7.927
274771LINCOLN ;2U
Adder
7.927
270526AF1-158 GEN
Solar/Wind Harmer
5.803
24441505OLIV SLR
Solar/Wind Harmer
0.171
270216AD2-079_GEN
Solar/Wind Harmer
0.772
957891AF2-083 GEN
Solar/Wind Harmer
4.252
274808UNIV PK N;4U
Adder
6.285
960981AF2-389 GEN
Solar/Wind Harmer
1.905
972259AH1-714 GEN
Adder
24.028
274803UNIV PARK;6U
Adder
7.334
274888KELLY CRK;1U
Solar/Wind Harmer
7.426
274887GEN-1.85
Solar/Wind Harmer
6.705
276843GEN-1.7
Solar/Wind Harmer
0.721
958011AF2-095 GEN
Solar/Wind Harmer
18.114
247620Y3-023
Adder
0.579
961051AF2-396 GEN
Solar/Wind Harmer
19.871
961051AF2-396 GEN
Solar/Wind Harmer
9.242
274674JOLIET 9 ;6U
Adder
19.265
274847GR RIDGE ;BU
Solar/Wind Harmer
6.323
971573AH1-285 GEN
Solar/Wind Harmer
10.693
274696ROCKY RD ;4P
Adder
14.103
274695ROCKY RD ;2P
Adder
13.778
274693ROCKY RD ;1P
Adder
13.642
274697ROCKY RD ;3P
Adder
3.743
958481AF2-142 GEN
Solar/Wind Harmer
18.542
274861TOP CROP ;1U
Solar/Wind Harmer
7.488
274862TOP CROP ;2U
Solar/Wind Harmer
6.253
274683WAUKEGAN ;8U
Adder
26.028
274683WAUKEGAN ;8U
Adder
21.94
962691AG1-118 GEN
Solar/Wind Harmer
36.976
970921AG2-575 GEN
Solar/Wind Harmer
12.308
970921AG2-575 GEN
Solar/Wind Harmer
2.862
958491AF2-143 GEN
Solar/Wind Harmer
18.417
970611AG2-400 GEN
Solar/Wind Harmer
12.256
942991AE2-321 GEN
Solar/Wind Harmer
12.253
274879MINONK ;1U
Solar/Wind Harmer
8.265
971333AH1-146 GEN
Solar/Wind Harmer
24.435
971335AH1-147 GEN
Solar/Wind Harmer
24.435
274764LEE CO EC;5U
Adder
11.221
274765LEE CO EC;6U
Adder
11.221
274762LEE CO EC;3U
Adder
11.195
274763LEE CO EC;4U
Adder
11.089
972267AH1-718 GEN
Adder
4.982
971341AH1-150 GEN
Solar/Wind Harmer
0.779
971343AH1-151 GEN
Solar/Wind Harmer
0.779
24721605FLATG1
50/50
1.796
971599AH1-298 GEN
50/50
12.165
962771AG1-126 GEN
Solar/Wind Harmer
95.82
971347AH1-153 GEN
Solar/Wind Harmer
20.131
270071AF1-092 GEN
Solar/Wind Harmer
19.441
960681AF2-359 GEN
Solar/Wind Harmer
4.853
971771AH1-392 GEN
Solar/Wind Harmer
11.51
274775LINCOLN ;6U
Adder
7.927
274776LINCOLN ;7U
Adder
7.927
274777LINCOLN ;8U
Adder
7.927
971769AH1-391 GEN
Solar/Wind Harmer
12.768
274814UNIV PK N;0U
Adder
6.368
274807UNIV PK N;3U
Adder
6.354
274805UNIV PK N;1U
Adder
6.326
274811UNIV PK N;7U
Adder
6.313
274827FISK ;RP
Adder
9.761
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.579
972227AH1-698 GEN1
Adder
3.281
274687WILL CNTY;4U
Adder
35.013
274687WILL CNTY;4U
Adder
35.013
274675JOLIET 29;7U
Adder
38.424
274675JOLIET 29;7U
Adder
37.052
274731ELWOOD EC;2P
Adder
20.557
274733ELWOOD EC;3P
Adder
20.557
274735ELWOOD EC;4P
Adder
20.557
274728ELWOOD EC;5P
Adder
20.557
970833AG2-524 GEN
Solar/Wind Harmer
10.916
970833AG2-524 GEN
Solar/Wind Harmer
5.077
274746AC1-111 G10
Adder
6.964
274744AC1-111 GEN8
Adder
6.964
24729505KEY G4
Adder
8.066
270536AF1-215 GEN2
Solar/Wind Harmer
5.645
944161AF1-084 GEN
Solar/Wind Harmer
2.743
958391AF2-133 GEN
Solar/Wind Harmer
11.115
971177AH1-047 GEN
Solar/Wind Harmer
7.179
276868AE1-113 GEN
Solar/Wind Harmer
12.396
276882AE2-255 GEN
Solar/Wind Harmer
4.132
971675AH1-338 GEN
Solar/Wind Harmer
22.002
971411AH1-196 GEN
Solar/Wind Harmer
18.333
274863CRW1-WTG
Solar/Wind Harmer
6.807
274864CRW2-WTG
Solar/Wind Harmer
6.807
274823ROCKFORD ;21
Adder
23.677
270054AF2-122 C O1
Solar/Wind Helper
1.538
971171AH1-044 GEN
Solar/Wind Harmer
0.779
944201AF1-088_MTX
Adder
118.565
957141AF2-008_MTX
Adder
59.283
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.937
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.195
MECLTFEXP_MEC->PJM
CLTF
18.51
SIGELTFEXP_SIGE->PJM
CLTF
0.474
LAGNLTFEXP_LAGN->PJM
CLTF
16.31
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.037
TVALTFEXP_TVA->PJM
CLTF
7.713
CPLELTFEXP_CPLE->PJM
CLTF
3.242
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.367
NYPJM->LTFIMP_NY
CLTF
3.759
LGEELTFEXP_LGEE->PJM
CLTF
5.533
WECLTFEXP_WEC->PJM
CLTF
4.633
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.1 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6038.29
MW Contribution:37.43
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
24.069
965681AG1-436 GEN
Solar/Wind Harmer
16.049
965791AG1-447 GEN
Solar/Wind Harmer
8.211
274770LINCOLN ;1U
Adder
7.923
274771LINCOLN ;2U
Adder
7.923
270526AF1-158 GEN
Solar/Wind Harmer
5.8
24441505OLIV SLR
Solar/Wind Harmer
0.171
270216AD2-079_GEN
Solar/Wind Harmer
0.772
957891AF2-083 GEN
Solar/Wind Harmer
4.25
274808UNIV PK N;4U
Adder
6.282
960981AF2-389 GEN
Solar/Wind Harmer
1.904
972259AH1-714 GEN
Adder
24.016
274803UNIV PARK;6U
Adder
7.33
274888KELLY CRK;1U
Solar/Wind Harmer
7.423
274887GEN-1.85
Solar/Wind Harmer
6.702
276843GEN-1.7
Solar/Wind Harmer
0.721
958011AF2-095 GEN
Solar/Wind Harmer
18.105
247620Y3-023
Adder
0.579
961051AF2-396 GEN
Solar/Wind Harmer
19.861
961051AF2-396 GEN
Solar/Wind Harmer
9.238
274674JOLIET 9 ;6U
Adder
19.256
274847GR RIDGE ;BU
Solar/Wind Harmer
6.32
971573AH1-285 GEN
Solar/Wind Harmer
10.688
274696ROCKY RD ;4P
Adder
14.096
274695ROCKY RD ;2P
Adder
13.771
274693ROCKY RD ;1P
Adder
13.635
274697ROCKY RD ;3P
Adder
3.741
958481AF2-142 GEN
Solar/Wind Harmer
18.533
274861TOP CROP ;1U
Solar/Wind Harmer
7.485
274862TOP CROP ;2U
Solar/Wind Harmer
6.25
274683WAUKEGAN ;8U
Adder
26.015
274683WAUKEGAN ;8U
Adder
21.929
962691AG1-118 GEN
Solar/Wind Harmer
36.958
970921AG2-575 GEN
Solar/Wind Harmer
12.301
970921AG2-575 GEN
Solar/Wind Harmer
2.861
958491AF2-143 GEN
Solar/Wind Harmer
18.408
970611AG2-400 GEN
Solar/Wind Harmer
12.25
942991AE2-321 GEN
Solar/Wind Harmer
12.247
274879MINONK ;1U
Solar/Wind Harmer
8.261
971333AH1-146 GEN
Solar/Wind Harmer
24.423
971335AH1-147 GEN
Solar/Wind Harmer
24.423
274764LEE CO EC;5U
Adder
11.215
274765LEE CO EC;6U
Adder
11.215
274762LEE CO EC;3U
Adder
11.189
274763LEE CO EC;4U
Adder
11.084
972267AH1-718 GEN
Adder
4.98
971341AH1-150 GEN
Solar/Wind Harmer
0.779
971343AH1-151 GEN
Solar/Wind Harmer
0.779
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.911
970153AG2-106 GEN
Solar/Wind Harmer
41.773
970513AG2-328 GEN
Solar/Wind Harmer
24.069
970517AG2-330 GEN
Solar/Wind Harmer
21.83
970349AG2-230 GEN
Solar/Wind Harmer
20.122
270043AE2-236 GEN
Solar/Wind Harmer
7.194
274772LINCOLN ;3U
Adder
7.923
247643Z2-116 C
Solar/Wind Harmer
0.089
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.405
970707AG2-453 GEN
Solar/Wind Harmer
35.353
972231SS25-0005
Solar/Wind Harmer
11.983
972181SS23-001
Solar/Wind Harmer
7.489
274752CRETE EC ;2U
Adder
6.171
274753CRETE EC ;3U
Adder
6.171
944531AF1-118 GEN
Solar/Wind Harmer
44.143
274826FISK ;BP
Adder
13.766
274802UNIV PARK;5U
Adder
7.33
276772AC2-154 GEN
Solar/Wind Harmer
3.506
276806AD2-047 C O1
Solar/Wind Harmer
13.45
970941AG2-585 GEN
Solar/Wind Harmer
15.716
972228AH1-698 GEN2
Adder
4.657
274800UNIV PARK;3U
Adder
7.327
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.106
276897AD1-100 C
Solar/Wind Harmer
36.411
939351AE1-166 GEN
Solar/Wind Harmer
7.44
274676JOLIET 29;8U
Adder
37.034
274729ELWOOD EC;1P
Adder
20.547
274730ELWOOD EC;6P
Adder
20.547
274734ELWOOD EC;8P
Adder
20.547
274736ELWOOD EC;9P
Adder
20.547
276893AG1-478 C
Solar/Wind Harmer
0.522
970031AG2-029 GEN
Solar/Wind Harmer
37.434
943121AE2-341 GEN
Solar/Wind Harmer
18.704
943591AF1-030 GEN
Solar/Wind Harmer
12.47
270535AF1-215 GEN1
Solar/Wind Harmer
5.642
276694AA1-018 GEN2
Solar/Wind Harmer
7.797
274682WAUKEGAN ;7U
Adder
22.204
964401AG1-302 GEN
Solar/Wind Harmer
11.162
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
6.295
959331AF2-224 GEN
Solar/Wind Harmer
12.25
965021AG1-366 GEN
Solar/Wind Harmer
2.849
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276799AD1-013 GEN
Solar/Wind Harmer
2.702
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
4.512
274850MENDOTA H;RU
Solar/Wind Harmer
3.137
276602WESTBROOK C
Solar/Wind Harmer
2.597
276863AD2-134 GEN
Solar/Wind Harmer
2.182
959141AF2-205 GEN
Solar/Wind Harmer
7.377
972236AH1-702 GEN2
Adder
2.659
247604X1-042
Adder
0.505
274760LEE CO EC;1U
Adder
11.189
274767LEE CO EC;8U
Adder
11.057
959091AF2-200 GEN
Solar/Wind Harmer
0.779
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.911
24344105CKG2
50/50
10.402
962761AG1-125 GEN
Solar/Wind Harmer
95.798
970149AG2-104 GEN
Solar/Wind Harmer
118.311
970155AG2-107 GEN
Solar/Wind Harmer
41.773
970245AG2-165 GEN
Solar/Wind Harmer
24.069
972207SS24-0001
Solar/Wind Harmer
28.169
274773LINCOLN ;4U
Adder
7.923
274774LINCOLN ;5U
Adder
7.923
274723RIVER EC ;12
Adder
22.666
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0.887
274751CRETE EC ;1U
Adder
6.171
274754CRETE EC ;4U
Adder
6.171
270505AE1-170 C O1
Solar/Wind Harmer
18.913
274812UNIV PK N;8U
Adder
6.309
276776AD2-060 GEN
Solar/Wind Harmer
0.532
274801UNIV PARK;4U
Adder
7.327
945111AF1-176 GEN
Solar/Wind Harmer
22.421
270063AE2-323 C
Solar/Wind Harmer
2.766
941551AE2-152 GEN
Solar/Wind Harmer
5.69
970373AG2-245 GEN
Solar/Wind Harmer
26.348
274676JOLIET 29;8U
Adder
38.405
274674JOLIET 9 ;6U
Adder
19.256
274732ELWOOD EC;7P
Adder
20.547
274871GR RIDGE ;2U
Solar/Wind Harmer
9.608
270449AD2-020 GEN
Solar/Wind Harmer
3.498
943021AE2-325 GEN
Solar/Wind Harmer
4.545
274745AC1-111 GEN9
Adder
6.961
270055AF2-134 C O1
Solar/Wind Harmer
3.761
276691AA1-018 GEN1
Solar/Wind Harmer
0.575
274682WAUKEGAN ;7U
Adder
22.204
274828WAUKEGAN ;BP
Adder
13.637
958381AF2-132 GEN
Solar/Wind Harmer
11.162
960751AF2-366 GEN
Solar/Wind Harmer
3.529
962781AG1-127 GEN
Solar/Wind Harmer
11.699
964861AG1-349 GEN
Solar/Wind Harmer
9.662
971917AH1-482 GEN
Solar/Wind Harmer
11.15
939401AE1-172 GEN
Solar/Wind Harmer
17.129
274872LEEDK;1U
Solar/Wind Harmer
10.091
276901AD2-066 C O1
Solar/Wind Harmer
4.309
965011AG1-365 GEN
Solar/Wind Harmer
12.25
971997AH1-543 GEN
Solar/Wind Harmer
19.262
276861AD2-134 GEN
Solar/Wind Harmer
2.182
274822ROCKFORD ;11
Adder
23.838
972235AH1-702 GEN1
Adder
3.057
274761LEE CO EC;2U
Adder
11.189
274766LEE CO EC;7U
Adder
11.057
970091AG2-072 GEN
Adder
5.255
957471AF2-041 GEN
Solar/Wind Harmer
1.168
959081AF2-199 GEN
Solar/Wind Harmer
0.389
971067AG2-660 GEN
Solar/Wind Harmer
0.091
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.16
962771AG1-126 GEN
Solar/Wind Harmer
95.798
971347AH1-153 GEN
Solar/Wind Harmer
20.122
270071AF1-092 GEN
Solar/Wind Harmer
19.432
960681AF2-359 GEN
Solar/Wind Harmer
4.851
971771AH1-392 GEN
Solar/Wind Harmer
11.504
274775LINCOLN ;6U
Adder
7.923
274776LINCOLN ;7U
Adder
7.923
274777LINCOLN ;8U
Adder
7.923
971769AH1-391 GEN
Solar/Wind Harmer
12.761
274814UNIV PK N;0U
Adder
6.365
274807UNIV PK N;3U
Adder
6.351
274805UNIV PK N;1U
Adder
6.323
274811UNIV PK N;7U
Adder
6.309
274827FISK ;RP
Adder
9.756
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.573
972227AH1-698 GEN1
Adder
3.279
274687WILL CNTY;4U
Adder
34.996
274687WILL CNTY;4U
Adder
34.996
274675JOLIET 29;7U
Adder
38.406
274675JOLIET 29;7U
Adder
37.034
274731ELWOOD EC;2P
Adder
20.547
274733ELWOOD EC;3P
Adder
20.547
274735ELWOOD EC;4P
Adder
20.547
274728ELWOOD EC;5P
Adder
20.547
970833AG2-524 GEN
Solar/Wind Harmer
10.911
970833AG2-524 GEN
Solar/Wind Harmer
5.075
274746AC1-111 G10
Adder
6.961
274744AC1-111 GEN8
Adder
6.961
24729505KEY G4
Adder
8.062
270536AF1-215 GEN2
Solar/Wind Harmer
5.642
944161AF1-084 GEN
Solar/Wind Harmer
2.742
958391AF2-133 GEN
Solar/Wind Harmer
11.109
971177AH1-047 GEN
Solar/Wind Harmer
7.175
276868AE1-113 GEN
Solar/Wind Harmer
12.39
276882AE2-255 GEN
Solar/Wind Harmer
4.13
971675AH1-338 GEN
Solar/Wind Harmer
21.991
971411AH1-196 GEN
Solar/Wind Harmer
18.324
274863CRW1-WTG
Solar/Wind Harmer
6.804
274864CRW2-WTG
Solar/Wind Harmer
6.804
274823ROCKFORD ;21
Adder
23.666
270054AF2-122 C O1
Solar/Wind Helper
1.539
971171AH1-044 GEN
Solar/Wind Harmer
0.779
944201AF1-088_MTX
Adder
118.492
957141AF2-008_MTX
Adder
59.246
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.176
MECLTFEXP_MEC->PJM
CLTF
18.5
SIGELTFEXP_SIGE->PJM
CLTF
0.474
LAGNLTFEXP_LAGN->PJM
CLTF
16.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.03
TVALTFEXP_TVA->PJM
CLTF
7.708
CPLELTFEXP_CPLE->PJM
CLTF
3.241
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.295
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.528
WECLTFEXP_WEC->PJM
CLTF
4.631
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.09 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6037.73
MW Contribution:37.43
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
24.064
965681AG1-436 GEN
Solar/Wind Harmer
16.046
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
7.921
274771LINCOLN ;2U
Adder
7.921
270526AF1-158 GEN
Solar/Wind Harmer
5.799
24441505OLIV SLR
Solar/Wind Harmer
0.171
270216AD2-079_GEN
Solar/Wind Harmer
0.772
957891AF2-083 GEN
Solar/Wind Harmer
4.249
960981AF2-389 GEN
Solar/Wind Harmer
1.904
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
7.421
274887GEN-1.85
Solar/Wind Harmer
6.7
276843GEN-1.7
Solar/Wind Harmer
0.721
958011AF2-095 GEN
Solar/Wind Harmer
18.101
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
19.857
961051AF2-396 GEN
Solar/Wind Harmer
9.236
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
6.319
971573AH1-285 GEN
Solar/Wind Harmer
10.686
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
18.529
274861TOP CROP ;1U
Solar/Wind Harmer
7.483
274862TOP CROP ;2U
Solar/Wind Harmer
6.248
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
36.95
970921AG2-575 GEN
Solar/Wind Harmer
12.299
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
18.404
970611AG2-400 GEN
Solar/Wind Harmer
12.247
942991AE2-321 GEN
Solar/Wind Harmer
12.245
274879MINONK ;1U
Solar/Wind Harmer
8.259
971333AH1-146 GEN
Solar/Wind Harmer
24.417
971335AH1-147 GEN
Solar/Wind Harmer
24.417
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
972267AH1-718 GEN
Adder
4.979
971341AH1-150 GEN
Solar/Wind Harmer
0.778
971343AH1-151 GEN
Solar/Wind Harmer
0.778
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
41.768
970513AG2-328 GEN
Solar/Wind Harmer
24.064
970517AG2-330 GEN
Solar/Wind Harmer
21.825
970349AG2-230 GEN
Solar/Wind Harmer
20.118
270043AE2-236 GEN
Solar/Wind Harmer
7.192
274772LINCOLN ;3U
Adder
7.921
247643Z2-116 C
Solar/Wind Harmer
0.089
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
35.346
972231SS25-0005
Solar/Wind Harmer
11.98
972181SS23-001
Solar/Wind Harmer
7.488
274752CRETE EC ;2U
Adder
6.17
274753CRETE EC ;3U
Adder
6.17
944531AF1-118 GEN
Solar/Wind Harmer
44.133
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276772AC2-154 GEN
Solar/Wind Harmer
3.505
276806AD2-047 C O1
Solar/Wind Harmer
13.447
970941AG2-585 GEN
Solar/Wind Harmer
15.712
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
36.403
939351AE1-166 GEN
Solar/Wind Harmer
7.438
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.522
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
95.789
970149AG2-104 GEN
Solar/Wind Harmer
118.299
970155AG2-107 GEN
Solar/Wind Harmer
41.768
970245AG2-165 GEN
Solar/Wind Harmer
24.064
972207SS24-0001
Solar/Wind Harmer
28.163
274773LINCOLN ;4U
Adder
7.921
274774LINCOLN ;5U
Adder
7.921
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0.887
274751CRETE EC ;1U
Adder
6.17
274754CRETE EC ;4U
Adder
6.17
270505AE1-170 C O1
Solar/Wind Harmer
18.909
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
95.789
971347AH1-153 GEN
Solar/Wind Harmer
20.118
270071AF1-092 GEN
Solar/Wind Harmer
19.428
960681AF2-359 GEN
Solar/Wind Harmer
4.85
971771AH1-392 GEN
Solar/Wind Harmer
11.502
274775LINCOLN ;6U
Adder
7.921
274776LINCOLN ;7U
Adder
7.921
274777LINCOLN ;8U
Adder
7.921
971769AH1-391 GEN
Solar/Wind Harmer
12.759
274814UNIV PK N;0U
Adder
6.363
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.57
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
10.908
970833AG2-524 GEN
Solar/Wind Harmer
5.074
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
5.641
944161AF1-084 GEN
Solar/Wind Harmer
2.741
958391AF2-133 GEN
Solar/Wind Harmer
11.107
971177AH1-047 GEN
Solar/Wind Harmer
7.174
276868AE1-113 GEN
Solar/Wind Harmer
12.387
276882AE2-255 GEN
Solar/Wind Harmer
4.129
971675AH1-338 GEN
Solar/Wind Harmer
21.986
971411AH1-196 GEN
Solar/Wind Harmer
18.32
274863CRW1-WTG
Solar/Wind Harmer
6.802
274864CRW2-WTG
Solar/Wind Harmer
6.802
274823ROCKFORD ;21
Adder
23.66
270054AF2-122 C O1
Solar/Wind Helper
1.539
971171AH1-044 GEN
Solar/Wind Harmer
0.778
970031AG2-029 GEN
Solar/Wind Harmer
37.426
943121AE2-341 GEN
Solar/Wind Harmer
18.7
943591AF1-030 GEN
Solar/Wind Harmer
12.467
270535AF1-215 GEN1
Solar/Wind Harmer
5.641
276694AA1-018 GEN2
Solar/Wind Harmer
7.795
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
11.16
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
6.294
959331AF2-224 GEN
Solar/Wind Harmer
12.247
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276799AD1-013 GEN
Solar/Wind Harmer
2.701
946671AF1-331 GEN
Solar/Wind Harmer
0.511
274855GSG-6 ;RU
Solar/Wind Harmer
4.511
274850MENDOTA H;RU
Solar/Wind Harmer
3.137
276602WESTBROOK C
Solar/Wind Harmer
2.596
276863AD2-134 GEN
Solar/Wind Harmer
2.181
959141AF2-205 GEN
Solar/Wind Harmer
7.375
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
959091AF2-200 GEN
Solar/Wind Harmer
0.778
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.531
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
22.416
270063AE2-323 C
Solar/Wind Harmer
2.766
941551AE2-152 GEN
Solar/Wind Harmer
5.689
970373AG2-245 GEN
Solar/Wind Harmer
26.342
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
9.606
270449AD2-020 GEN
Solar/Wind Harmer
3.497
943021AE2-325 GEN
Solar/Wind Harmer
4.544
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
3.76
276691AA1-018 GEN1
Solar/Wind Harmer
0.575
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
11.16
960751AF2-366 GEN
Solar/Wind Harmer
3.529
962781AG1-127 GEN
Solar/Wind Harmer
11.696
964861AG1-349 GEN
Solar/Wind Harmer
9.66
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
17.125
274872LEEDK;1U
Solar/Wind Harmer
10.089
276901AD2-066 C O1
Solar/Wind Harmer
4.308
965011AG1-365 GEN
Solar/Wind Harmer
12.247
971997AH1-543 GEN
Solar/Wind Harmer
19.257
276861AD2-134 GEN
Solar/Wind Harmer
2.181
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
970091AG2-072 GEN
Adder
5.254
957471AF2-041 GEN
Solar/Wind Harmer
1.168
959081AF2-199 GEN
Solar/Wind Harmer
0.389
971067AG2-660 GEN
Solar/Wind Harmer
0.091
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
59.23
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706
CPLELTFEXP_CPLE->PJM
CLTF
3.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.64 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5971.43
MW Contribution:5.66
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
51.584
970513AG2-328 GEN
Solar/Wind Harmer
4.074
970517AG2-330 GEN
Solar/Wind Harmer
24.444
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
80.781
970149AG2-104 GEN
Solar/Wind Harmer
87.246
970155AG2-107 GEN
Solar/Wind Harmer
51.584
970245AG2-165 GEN
Solar/Wind Harmer
4.074
274773LINCOLN ;4U
Adder
10.782
274774LINCOLN ;5U
Adder
10.782
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.401
274754CRETE EC ;4U
Adder
10.401
270505AE1-170 C O1
Solar/Wind Harmer
9.235
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.916
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
15.639
270063AE2-323 C
Solar/Wind Harmer
0.007
941551AE2-152 GEN
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
18.378
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.544
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
0.007
276691AA1-018 GEN1
Solar/Wind Harmer
1.044
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.166
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
6.413
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
8.544
971997AH1-543 GEN
Solar/Wind Harmer
4.478
276861AD2-134 GEN
Solar/Wind Harmer
0.153
957471AF2-041 GEN
Solar/Wind Harmer
25.469
959081AF2-199 GEN
Solar/Wind Harmer
8.49
971067AG2-660 GEN
Solar/Wind Harmer
2.83
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.593
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
970819AG2-516 GEN
Solar/Wind Harmer
10.134
971475AH1-234 GEN
Solar/Wind Harmer
4.092
970569AG2-363 GEN
Solar/Wind Harmer
25.271
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.438
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.552
958861AF2-177 GEN
Solar/Wind Harmer
3.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.643
970349AG2-230 GEN
Solar/Wind Harmer
14.036
270043AE2-236 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
10.782
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
28.77
274752CRETE EC ;2U
Adder
10.401
274753CRETE EC ;3U
Adder
10.401
944531AF1-118 GEN
Solar/Wind Harmer
39.427
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276806AD2-047 C O1
Solar/Wind Harmer
4.97
970941AG2-585 GEN
Solar/Wind Harmer
10.962
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.345
970031AG2-029 GEN
Solar/Wind Harmer
5.657
943121AE2-341 GEN
Solar/Wind Harmer
14.583
943591AF1-030 GEN
Solar/Wind Harmer
9.698
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.981
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.909
274855GSG-6 ;RU
Solar/Wind Harmer
0.313
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.153
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
16.979
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
970571AG2-364 GEN
Solar/Wind Harmer
16.847
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
276157O29GEN1
Solar/Wind Harmer
1.347
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.289
942111AE2-223 GEN
Solar/Wind Harmer
2.682
965931AG1-462 GEN
Solar/Wind Harmer
20.855
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.514
959611AF2-252 GEN
Solar/Wind Harmer
2.724
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.657
276668AB2-070 GEN1
Solar/Wind Harmer
0.289
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.395
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970289AG2-191 GEN
Solar/Wind Harmer
0.855
970291AG2-192 GEN
Solar/Wind Harmer
0.777
942481AE2-261 GEN
Solar/Wind Harmer
23.013
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.049
970193AG2-126 GEN
Solar/Wind Harmer
11.195
958821AF2-173 GEN
Solar/Wind Harmer
10.43
270004AE1-209 GEN
Solar/Wind Harmer
1.614
971617AH1-308 GEN
Solar/Wind Harmer
6.153
970243AG2-164 GEN
Solar/Wind Harmer
3.851
970519AG2-331 GEN
Solar/Wind Harmer
17.115
970699AG2-449 GEN
Solar/Wind Harmer
1.646
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.078
963741AG1-226 GEN
Solar/Wind Harmer
18.629
276615X2-022 GEN
Solar/Wind Harmer
0.082
970291AG2-192 GEN
Solar/Wind Harmer
1.01
965911AG1-460 GEN
Solar/Wind Harmer
1.539
270032AE2-172
Solar/Wind Harmer
5.104
247521TR3_G114
Solar/Wind Harmer
0.277
270246TR4_N_V150
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
2.021
276903AD2-071 C
Solar/Wind Harmer
8.405
270005AE1-210 C O1
Solar/Wind Harmer
1.614
965031AG1-367 GEN
Solar/Wind Harmer
7.45
24695305TIMB G C
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
4.707
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
4.074
965681AG1-436 GEN
Solar/Wind Harmer
11.195
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
10.782
274771LINCOLN ;2U
Adder
10.782
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.515
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.284
958011AF2-095 GEN
Solar/Wind Harmer
12.628
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
17.455
961051AF2-396 GEN
Solar/Wind Harmer
11.637
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.615
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
12.927
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.166
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
25.779
970921AG2-575 GEN
Solar/Wind Harmer
8.581
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
12.84
970611AG2-400 GEN
Solar/Wind Harmer
8.544
970627AG2-408 GEN
Solar/Wind Harmer
2.563
942991AE2-321 GEN
Solar/Wind Harmer
9.539
274879MINONK ;1U
Solar/Wind Harmer
0.36
971333AH1-146 GEN
Solar/Wind Harmer
17.035
971335AH1-147 GEN
Solar/Wind Harmer
17.035
971341AH1-150 GEN
Solar/Wind Harmer
16.979
971343AH1-151 GEN
Solar/Wind Harmer
16.979
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.199
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.764
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
972267AH1-718 GEN
Adder
4.979
276741O09 GEN1
Solar/Wind Harmer
0.297
276708O09 GEN2
Solar/Wind Harmer
0.297
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.876
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.724
966841AG1-555 GEN
Solar/Wind Harmer
0.919
942221AE2-234 GEN
Solar/Wind Harmer
0.04
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.592
270599AE1-208 GEN
Solar/Wind Harmer
7.039
270031AE2-169
Solar/Wind Harmer
4.223
276916AD2-100_GEN
Solar/Wind Harmer
16.09
276911AD2-131_GEN
Solar/Wind Harmer
1.06
971613AH1-306 GEN
Solar/Wind Harmer
3.675
945391AF1-204 GEN
Solar/Wind Harmer
7.93
960441AF2-335 GEN
Solar/Wind Harmer
7.358
970239AG2-162 GEN
Solar/Wind Harmer
1.646
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
80.781
971347AH1-153 GEN
Solar/Wind Harmer
14.036
270071AF1-092 GEN
Solar/Wind Harmer
17.319
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.916
274775LINCOLN ;6U
Adder
10.782
274776LINCOLN ;7U
Adder
10.782
274777LINCOLN ;8U
Adder
10.782
971769AH1-391 GEN
Solar/Wind Harmer
9.94
971619AH1-309 GEN
Solar/Wind Harmer
3.958
274814UNIV PK N;0U
Adder
6.363
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.77
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
9.589
970833AG2-524 GEN
Solar/Wind Harmer
6.393
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
5.267
276868AE1-113 GEN
Solar/Wind Harmer
1.713
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971675AH1-338 GEN
Solar/Wind Harmer
3.323
971411AH1-196 GEN
Solar/Wind Harmer
12.781
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
16.979
971611AH1-305 GEN
Solar/Wind Harmer
5.045
274823ROCKFORD ;21
Adder
23.66
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.432
970169AG2-114 GEN
Solar/Wind Harmer
8.423
971681AH1-341 GEN
Solar/Wind Harmer
13.539
961011AF2-392 GEN
Solar/Wind Harmer
4.902
957751AF2-069 GEN
Solar/Wind Harmer
0.275
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.664
941731AE2-173 GEN
Solar/Wind Harmer
6.876
946321AF1-296 GEN
Solar/Wind Harmer
4.594
965101AG1-375 GEN
Solar/Wind Harmer
8.195
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.463
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.716
971549AH1-272 GEN
Solar/Wind Harmer
16.349
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.289
276848AB2-070 GEN3
Solar/Wind Harmer
0.287
965041AG1-368 GEN
Solar/Wind Harmer
7.862
970289AG2-191 GEN
Solar/Wind Harmer
1.476
971609AH1-304 GEN
Solar/Wind Harmer
1.254
270594AE1-207 GEN
Solar/Wind Harmer
8.574
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.425
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.008
970115AG2-085 GEN
Solar/Wind Harmer
2.943
270054AF2-122 C O1
Solar/Wind Helper
1.539
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
32.732
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706
CPLELTFEXP_CPLE->PJM
CLTF
3.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.18 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5310.77
MW Contribution:6.73
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
5.145
24721905FLATG4
50/50
94.33
270475AD2-096_GEN
50/50
10.026
270142AC1-141 CT1_
50/50
3.558
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.691
24642205MAYFLWER
50/50
0.992
944961AF1-161 GEN
50/50
4.253
962601AG1-109 GEN
50/50
4.253
247604X1-042
50/50
0.632
970153AG2-106 GEN
Solar/Wind Harmer
76.659
24721805FLATG3
50/50
5.145
24721705FLATG2
50/50
94.33
24344105CKG2
50/50
12.069
270143AC1-141 CT2_
50/50
3.558
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.184
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
120.047
970149AG2-104 GEN
Solar/Wind Harmer
129.655
970155AG2-107 GEN
Solar/Wind Harmer
76.659
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.537
970245AG2-165 GEN
Solar/Wind Harmer
4.559
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.806
945111AF1-176 GEN
Solar/Wind Harmer
18.321
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.329
274773LINCOLN ;4U
Adder
11.972
274774LINCOLN ;5U
Adder
11.972
274723RIVER EC ;12
Adder
25.205
270043AE2-236 GEN
Solar/Wind Harmer
6.969
970349AG2-230 GEN
Solar/Wind Harmer
16.236
959331AF2-224 GEN
Solar/Wind Harmer
7.376
965021AG1-366 GEN
Solar/Wind Harmer
3.512
970513AG2-328 GEN
Solar/Wind Harmer
4.559
970517AG2-330 GEN
Solar/Wind Harmer
27.357
247643Z2-116 C
Solar/Wind Harmer
0
24721605FLATG1
50/50
5.145
971599AH1-298 GEN
50/50
14.587
270144AC1-141 ST1_
50/50
3.152
24653605MOTTVILLE
50/50
0.006
24643105BUCHANAN
50/50
0.019
962771AG1-126 GEN
Solar/Wind Harmer
120.047
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
16.236
270071AF1-092 GEN
Solar/Wind Harmer
20.132
971771AH1-392 GEN
Solar/Wind Harmer
10.346
971619AH1-309 GEN
Solar/Wind Harmer
4.631
971769AH1-391 GEN
Solar/Wind Harmer
11.424
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
24729505KEY G4
Adder
9.267
274775LINCOLN ;6U
Adder
11.972
274776LINCOLN ;7U
Adder
11.972
274777LINCOLN ;8U
Adder
11.972
965041AG1-368 GEN
Solar/Wind Harmer
9.847
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.057
274807UNIV PK N;3U
Adder
7.042
274805UNIV PK N;1U
Adder
7.011
274811UNIV PK N;7U
Adder
6.996
972037AH1-567 GEN1
Adder
0.254
274827FISK ;RP
Adder
10.776
960591AF2-350 GEN
Solar/Wind Harmer
9.68
972227AH1-698 GEN1
Adder
3.616
965051AG1-369 GEN
Solar/Wind Harmer
4.807
274687WILL CNTY;4U
Adder
38.503
274687WILL CNTY;4U
Adder
38.503
274675JOLIET 29;7U
Adder
42.223
274675JOLIET 29;7U
Adder
40.715
274728ELWOOD EC;5P
Adder
22.567
274731ELWOOD EC;2P
Adder
22.566
274733ELWOOD EC;3P
Adder
22.566
274735ELWOOD EC;4P
Adder
22.566
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
970833AG2-524 GEN
Solar/Wind Harmer
10.52
970833AG2-524 GEN
Solar/Wind Harmer
7.013
971549AH1-272 GEN
Solar/Wind Harmer
19.681
274746AC1-111 G10
Adder
7.614
274744AC1-111 GEN8
Adder
7.614
963791AG1-232 GEN
Solar/Wind Harmer
12.76
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.013
971653AH1-327 GEN
Solar/Wind Harmer
1.314
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.855
276882AE2-255 GEN
Solar/Wind Harmer
1.081
971177AH1-047 GEN
Solar/Wind Harmer
5.697
965101AG1-375 GEN
Solar/Wind Harmer
9.202
971411AH1-196 GEN
Solar/Wind Harmer
13.802
971675AH1-338 GEN
Solar/Wind Harmer
3.588
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.454
971171AH1-044 GEN
Solar/Wind Harmer
18.285
274823ROCKFORD ;21
Adder
25.447
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.535
970169AG2-114 GEN
Solar/Wind Harmer
9.023
971681AH1-341 GEN
Solar/Wind Harmer
14.483
247607V1-011 GEN
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
5.219
970615AG2-402 GEN
50/50
3.512
247620Y3-023
50/50
0.722
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.169
270101X2-052 CT2
50/50
2.169
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.537
970627AG2-408 GEN
Solar/Wind Harmer
3.161
970321AG2-212 GEN
Solar/Wind Harmer
4.559
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.013
24441505OLIV SLR
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
20.46
961051AF2-396 GEN
Solar/Wind Harmer
13.64
965681AG1-436 GEN
Solar/Wind Harmer
12.752
965791AG1-447 GEN
Solar/Wind Harmer
9.351
274770LINCOLN ;1U
Adder
11.972
274771LINCOLN ;2U
Adder
11.972
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.965
274803UNIV PARK;6U
Adder
8.1
274888KELLY CRK;1U
Solar/Wind Harmer
0.568
274887GEN-1.85
Solar/Wind Harmer
0.255
276843GEN-1.7
Solar/Wind Harmer
0.313
958011AF2-095 GEN
Solar/Wind Harmer
13.939
972259AH1-714 GEN
Adder
26.463
274674JOLIET 9 ;6U
Adder
21.154
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.764
958481AF2-142 GEN
Solar/Wind Harmer
14.096
274695ROCKY RD ;2P
Adder
14.996
274693ROCKY RD ;1P
Adder
14.848
274697ROCKY RD ;3P
Adder
4.074
274696ROCKY RD ;4P
Adder
15.349
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.271
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.509
274683WAUKEGAN ;8U
Adder
28.303
274683WAUKEGAN ;8U
Adder
23.858
246938BC-WTG3
Solar/Wind Harmer
0.338
246937BC-WTG2
Solar/Wind Harmer
0.379
962691AG1-118 GEN
Solar/Wind Harmer
27.992
970921AG2-575 GEN
Solar/Wind Harmer
9.308
970921AG2-575 GEN
Solar/Wind Harmer
3.103
958491AF2-143 GEN
Solar/Wind Harmer
13.931
274879MINONK ;1U
Solar/Wind Harmer
0.39
942991AE2-321 GEN
Solar/Wind Harmer
10.32
971333AH1-146 GEN
Solar/Wind Harmer
18.389
971335AH1-147 GEN
Solar/Wind Harmer
18.389
971341AH1-150 GEN
Solar/Wind Harmer
18.285
971343AH1-151 GEN
Solar/Wind Harmer
18.285
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
942221AE2-234 GEN
Solar/Wind Harmer
0.046
274856ECOGROVE ;U1
Solar/Wind Harmer
0.213
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
5.096
274764LEE CO EC;5U
Adder
11.975
274765LEE CO EC;6U
Adder
11.975
274762LEE CO EC;3U
Adder
11.947
274763LEE CO EC;4U
Adder
11.834
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270007AE1-245 C
Solar/Wind Harmer
0.002
972267AH1-718 GEN
Adder
5.295
276741O09 GEN1
Solar/Wind Harmer
0.315
276708O09 GEN2
Solar/Wind Harmer
0.315
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
945581AF1-223 GEN
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.292
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.145
941731AE2-173 GEN
Solar/Wind Harmer
7.258
946321AF1-296 GEN
Solar/Wind Harmer
4.827
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.009
971609AH1-304 GEN
Solar/Wind Harmer
1.375
970289AG2-191 GEN
Solar/Wind Harmer
1.578
963841AG1-237 GEN
Solar/Wind Harmer
3.575
270594AE1-207 GEN
Solar/Wind Harmer
9.172
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.295
276848AB2-070 GEN3
Solar/Wind Harmer
0.294
970115AG2-085 GEN
Solar/Wind Harmer
3.159
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.614
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.854
966841AG1-555 GEN
Solar/Wind Harmer
0.959
270599AE1-208 GEN
Solar/Wind Harmer
7.715
270031AE2-169
Solar/Wind Harmer
4.629
971613AH1-306 GEN
Solar/Wind Harmer
3.931
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.69
960441AF2-335 GEN
Solar/Wind Harmer
7.897
970825AG2-519 GEN
Solar/Wind Harmer
8.719
964611AG1-324 GEN
Solar/Wind Harmer
0.584
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.413
247621Y3-024
Adder
0.262
276916AD2-100_GEN
Solar/Wind Harmer
13.41
276911AD2-131_GEN
Solar/Wind Harmer
0.883
274751CRETE EC ;1U
Adder
11.58
274754CRETE EC ;4U
Adder
11.58
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
20.506
274812UNIV PK N;8U
Adder
6.996
274801UNIV PARK;4U
Adder
8.089
276776AD2-060 GEN
Solar/Wind Harmer
1.011
247521TR3_G114
Solar/Wind Harmer
0.351
270246TR4_N_V150
Solar/Wind Harmer
0.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.222
274674JOLIET 9 ;6U
Adder
21.154
274732ELWOOD EC;7P
Adder
22.567
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.614
944231AF1-091 GEN
Solar/Wind Harmer
2.532
24695305TIMB G C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
28.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.138
965651AG1-433 GEN
Solar/Wind Harmer
2.755
274682WAUKEGAN ;7U
Adder
24.169
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.195
274828WAUKEGAN ;BP
Adder
14.836
246936BC-WTG1
Solar/Wind Harmer
0.379
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270462AD2-086
Solar/Wind Harmer
0.02
962781AG1-127 GEN
Solar/Wind Harmer
8.858
939401AE1-172 GEN
Solar/Wind Harmer
6.954
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.843
958861AF2-177 GEN
Solar/Wind Harmer
3.987
276861AD2-134 GEN
Solar/Wind Harmer
0.165
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.452
957471AF2-041 GEN
Solar/Wind Harmer
27.428
959081AF2-199 GEN
Solar/Wind Harmer
9.143
971067AG2-660 GEN
Solar/Wind Harmer
3.048
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
25.633
972235AH1-702 GEN1
Adder
3.284
970819AG2-516 GEN
Solar/Wind Harmer
10.874
971475AH1-234 GEN
Solar/Wind Harmer
4.385
970569AG2-363 GEN
Solar/Wind Harmer
27.095
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.947
274766LEE CO EC;7U
Adder
11.806
276158O29GEN2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.295
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.194
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.873
970291AG2-192 GEN
Solar/Wind Harmer
1.08
270032AE2-172
Solar/Wind Harmer
5.46
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.14
963741AG1-226 GEN
Solar/Wind Harmer
19.026
270005AE1-210 C O1
Solar/Wind Harmer
1.733
965031AG1-367 GEN
Solar/Wind Harmer
8
276615X2-022 GEN
Solar/Wind Harmer
0.084
276903AD2-071 C
Solar/Wind Harmer
8.872
970825AG2-519 GEN
Solar/Wind Harmer
2.793
965911AG1-460 GEN
Solar/Wind Harmer
1.538
24728605AND G2
Adder
3.739
970031AG2-029 GEN
Solar/Wind Harmer
6.732
945111AF1-176 GEN
Solar/Wind Harmer
8.323
944531AF1-118 GEN
Solar/Wind Harmer
45.595
24441205WTRV SLR C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.972
274724RIVER EC ;11
Adder
24.913
274752CRETE EC ;2U
Adder
11.58
274753CRETE EC ;3U
Adder
11.58
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.724
274802UNIV PARK;5U
Adder
8.1
274826FISK ;BP
Adder
15.205
274800UNIV PARK;3U
Adder
8.089
972038AH1-567 GEN2
Adder
0.506
276806AD2-047 C O1
Solar/Wind Harmer
5.485
970941AG2-585 GEN
Solar/Wind Harmer
12.1
972228AH1-698 GEN2
Adder
5.135
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
40.714
274730ELWOOD EC;6P
Adder
22.567
274734ELWOOD EC;8P
Adder
22.567
274736ELWOOD EC;9P
Adder
22.567
274729ELWOOD EC;1P
Adder
22.566
276893AG1-478 C
Solar/Wind Harmer
0.379
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
943121AE2-341 GEN
Solar/Wind Harmer
15.96
943591AF1-030 GEN
Solar/Wind Harmer
10.614
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
24.169
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.341
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.982
274855GSG-6 ;RU
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.165
959091AF2-200 GEN
Solar/Wind Harmer
18.285
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.856
970571AG2-364 GEN
Solar/Wind Harmer
18.064
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.947
274767LEE CO EC;8U
Adder
11.806
276157O29GEN1
Solar/Wind Harmer
1.431
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274878BISHOP HL;2U
Solar/Wind Harmer
0.295
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.785
270404AC1-167 GEN
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
2.831
965931AG1-462 GEN
Solar/Wind Harmer
21.861
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.685
959611AF2-252 GEN
Solar/Wind Harmer
2.854
971617AH1-308 GEN
Solar/Wind Harmer
7.03
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.914
970291AG2-192 GEN
Solar/Wind Harmer
0.831
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
0.295
958821AF2-173 GEN
Solar/Wind Harmer
11.2
270004AE1-209 GEN
Solar/Wind Harmer
1.733
276621W2-048 GEN
Solar/Wind Harmer
0.401
276838X2-022 GEN2
Solar/Wind Harmer
0.448
946031AF1-268 GEN
Solar/Wind Harmer
7.422
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.672
942481AE2-261 GEN
Solar/Wind Harmer
22.986
24728705AND G3
Adder
7.82
24728505AND G1
Adder
3.739
944201AF1-088_MTX
Adder
85.667
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.132
MECLTFEXP_MEC->PJM
CLTF
18.394
SIGELTFEXP_SIGE->PJM
CLTF
0.399
LAGNLTFEXP_LAGN->PJM
CLTF
11.144
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.328
TVALTFEXP_TVA->PJM
CLTF
4.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.989
NYPJM->LTFIMP_NY
CLTF
2.99
LGEELTFEXP_LGEE->PJM
CLTF
4.155
WECLTFEXP_WEC->PJM
CLTF
4.968
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.312
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.73 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4643.02
MW Contribution:4.84
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.603
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.096
24642205MAYFLWER
50/50
0.728
274772LINCOLN ;3U
50/50
9.593
970153AG2-106 GEN
Solar/Wind Harmer
47.639
970349AG2-230 GEN
Solar/Wind Harmer
12.013
970513AG2-328 GEN
Solar/Wind Harmer
3.44
970517AG2-330 GEN
Solar/Wind Harmer
20.64
270043AE2-236 GEN
Solar/Wind Harmer
5.033
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.073
970031AG2-029 GEN
Solar/Wind Harmer
4.844
944531AF1-118 GEN
Solar/Wind Harmer
33.218
274724RIVER EC ;11
Adder
18.771
274752CRETE EC ;2U
Adder
8.717
274753CRETE EC ;3U
Adder
8.717
959331AF2-224 GEN
Solar/Wind Harmer
5.157
965021AG1-366 GEN
Solar/Wind Harmer
2.455
970707AG2-453 GEN
Solar/Wind Harmer
24.03
274826FISK ;BP
Adder
11.498
274802UNIV PARK;5U
Adder
6.123
276806AD2-047 C O1
Solar/Wind Harmer
4.15
970941AG2-585 GEN
Solar/Wind Harmer
9.154
274800UNIV PARK;3U
Adder
6.118
972038AH1-567 GEN2
Adder
0.383
972228AH1-698 GEN2
Adder
3.887
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.865
274729ELWOOD EC;1P
Adder
17.114
274730ELWOOD EC;6P
Adder
17.114
274734ELWOOD EC;8P
Adder
17.114
274736ELWOOD EC;9P
Adder
17.114
276893AG1-478 C
Solar/Wind Harmer
0.288
943121AE2-341 GEN
Solar/Wind Harmer
12.132
943591AF1-030 GEN
Solar/Wind Harmer
8.068
247604X1-042
Adder
0.432
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.416
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
0.258
274850MENDOTA H;RU
Solar/Wind Harmer
0.083
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
14.009
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.191
970571AG2-364 GEN
Solar/Wind Harmer
13.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.191
274767LEE CO EC;8U
Adder
9.083
276157O29GEN1
Solar/Wind Harmer
1.104
274878BISHOP HL;2U
Solar/Wind Harmer
0.228
24721905FLATG4
Adder
19.64
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.747
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.976
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.897
959611AF2-252 GEN
Solar/Wind Harmer
2.211
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.93
276668AB2-070 GEN1
Solar/Wind Harmer
0.231
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.316
276838X2-022 GEN2
Solar/Wind Harmer
0.352
970289AG2-191 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.623
942481AE2-261 GEN
Solar/Wind Harmer
18.215
270491AE1-102 GEN2
Solar/Wind Harmer
0.785
24344105CKG2
50/50
8.939
270143AC1-141 CT2_
50/50
2.603
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.519
274773LINCOLN ;4U
50/50
9.593
274774LINCOLN ;5U
50/50
9.593
962761AG1-125 GEN
Solar/Wind Harmer
74.603
970149AG2-104 GEN
Solar/Wind Harmer
80.573
970155AG2-107 GEN
Solar/Wind Harmer
47.639
970245AG2-165 GEN
Solar/Wind Harmer
3.44
270505AE1-170 C O1
Solar/Wind Harmer
7.896
270063AE2-323 C
Solar/Wind Harmer
0.006
945111AF1-176 GEN
Solar/Wind Harmer
13.37
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.886
274723RIVER EC ;12
Adder
18.99
274751CRETE EC ;1U
Adder
8.717
274754CRETE EC ;4U
Adder
8.717
276164X3-005 C
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
7.366
274812UNIV PK N;8U
Adder
5.278
970373AG2-245 GEN
Solar/Wind Harmer
15.386
276776AD2-060 GEN
Solar/Wind Harmer
0.765
274801UNIV PARK;4U
Adder
6.118
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
32.008
274674JOLIET 9 ;6U
Adder
16.042
274732ELWOOD EC;7P
Adder
17.114
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.788
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276691AA1-018 GEN1
Solar/Wind Harmer
0.866
274682WAUKEGAN ;7U
Adder
18.416
274828WAUKEGAN ;BP
Adder
11.308
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.763
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.233
274872LEEDK;1U
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
5.304
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.701
276861AD2-134 GEN
Solar/Wind Harmer
0.126
957471AF2-041 GEN
Solar/Wind Harmer
21.014
959081AF2-199 GEN
Solar/Wind Harmer
7.005
971067AG2-660 GEN
Solar/Wind Harmer
2.335
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.652
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.717
972235AH1-702 GEN1
Adder
2.519
970819AG2-516 GEN
Solar/Wind Harmer
8.346
971475AH1-234 GEN
Solar/Wind Harmer
3.368
970569AG2-363 GEN
Solar/Wind Harmer
20.788
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.191
274766LEE CO EC;7U
Adder
9.083
965651AG1-433 GEN
Solar/Wind Harmer
2.017
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.228
24721705FLATG2
Adder
19.64
24791305MDL-5G
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
2.923
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.413
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
944231AF1-091 GEN
Solar/Wind Harmer
1.739
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
972175AH1-670 GEN
Solar/Wind Harmer
5.355
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24695305TIMB G C
Solar/Wind Harmer
0.002
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.462
963741AG1-226 GEN
Solar/Wind Harmer
14.839
276615X2-022 GEN
Solar/Wind Harmer
0.066
970291AG2-192 GEN
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.496
270032AE2-172
Solar/Wind Harmer
4.081
965911AG1-460 GEN
Solar/Wind Harmer
1.218
246936BC-WTG1
Solar/Wind Harmer
0.245
270489AE1-102 GEN1
Solar/Wind Harmer
0.785
270102X2-052 ST
50/50
1.747
270100X2-052 CT1
50/50
1.61
270101X2-052 CT2
50/50
1.61
247620Y3-023
50/50
0.525
274770LINCOLN ;1U
50/50
9.593
274771LINCOLN ;2U
50/50
9.593
970321AG2-212 GEN
Solar/Wind Harmer
3.44
270216AD2-079_GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
9.481
965791AG1-447 GEN
Solar/Wind Harmer
6.953
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.924
961051AF2-396 GEN
Solar/Wind Harmer
9.95
970611AG2-400 GEN
Solar/Wind Harmer
7.366
970627AG2-408 GEN
Solar/Wind Harmer
2.21
274808UNIV PK N;4U
Adder
5.255
972259AH1-714 GEN
Adder
20.044
274803UNIV PARK;6U
Adder
6.123
274888KELLY CRK;1U
Solar/Wind Harmer
0.43
274887GEN-1.85
Solar/Wind Harmer
0.193
276843GEN-1.7
Solar/Wind Harmer
0.237
958011AF2-095 GEN
Solar/Wind Harmer
10.545
274674JOLIET 9 ;6U
Adder
16.042
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.342
274695ROCKY RD ;2P
Adder
11.425
274693ROCKY RD ;1P
Adder
11.312
274697ROCKY RD ;3P
Adder
3.104
274696ROCKY RD ;4P
Adder
11.694
958481AF2-142 GEN
Solar/Wind Harmer
10.727
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.967
274683WAUKEGAN ;8U
Adder
21.572
274683WAUKEGAN ;8U
Adder
18.184
962691AG1-118 GEN
Solar/Wind Harmer
21.36
970921AG2-575 GEN
Solar/Wind Harmer
7.106
970921AG2-575 GEN
Solar/Wind Harmer
2.369
958491AF2-143 GEN
Solar/Wind Harmer
10.627
942991AE2-321 GEN
Solar/Wind Harmer
7.889
274879MINONK ;1U
Solar/Wind Harmer
0.298
971333AH1-146 GEN
Solar/Wind Harmer
14.073
971335AH1-147 GEN
Solar/Wind Harmer
14.073
971341AH1-150 GEN
Solar/Wind Harmer
14.009
971343AH1-151 GEN
Solar/Wind Harmer
14.009
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.164
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.917
274764LEE CO EC;5U
Adder
9.213
274765LEE CO EC;6U
Adder
9.213
274762LEE CO EC;3U
Adder
9.191
274763LEE CO EC;4U
Adder
9.105
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.461
960971AF2-388 GEN
Solar/Wind Harmer
4.033
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.082
276741O09 GEN1
Solar/Wind Harmer
0.243
276708O09 GEN2
Solar/Wind Harmer
0.243
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.211
942221AE2-234 GEN
Solar/Wind Harmer
0.033
966841AG1-555 GEN
Solar/Wind Harmer
0.741
270471AD2-092_GEN
Solar/Wind Harmer
0.005
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.657
270599AE1-208 GEN
Solar/Wind Harmer
5.676
270031AE2-169
Solar/Wind Harmer
3.406
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276916AD2-100_GEN
Solar/Wind Harmer
12.71
276911AD2-131_GEN
Solar/Wind Harmer
0.837
246938BC-WTG3
Solar/Wind Harmer
0.219
246937BC-WTG2
Solar/Wind Harmer
0.245
971599AH1-298 GEN
50/50
10.558
270144AC1-141 ST1_
50/50
2.306
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.593
274776LINCOLN ;7U
50/50
9.593
274777LINCOLN ;8U
50/50
9.593
962771AG1-126 GEN
Solar/Wind Harmer
74.603
971347AH1-153 GEN
Solar/Wind Harmer
12.013
270071AF1-092 GEN
Solar/Wind Harmer
14.717
971771AH1-392 GEN
Solar/Wind Harmer
7.604
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.444
971619AH1-309 GEN
Solar/Wind Harmer
3.384
274814UNIV PK N;0U
Adder
5.324
274807UNIV PK N;3U
Adder
5.313
274805UNIV PK N;1U
Adder
5.29
274811UNIV PK N;7U
Adder
5.278
274827FISK ;RP
Adder
8.149
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
7.323
972227AH1-698 GEN1
Adder
2.737
274687WILL CNTY;4U
Adder
29.176
274687WILL CNTY;4U
Adder
29.176
274675JOLIET 29;7U
Adder
32.008
274675JOLIET 29;7U
Adder
30.865
24729505KEY G4
Adder
6.759
274731ELWOOD EC;2P
Adder
17.114
274733ELWOOD EC;3P
Adder
17.114
274735ELWOOD EC;4P
Adder
17.114
274728ELWOOD EC;5P
Adder
17.114
970833AG2-524 GEN
Solar/Wind Harmer
7.985
970833AG2-524 GEN
Solar/Wind Harmer
5.323
274746AC1-111 G10
Adder
5.788
274744AC1-111 GEN8
Adder
5.788
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
971177AH1-047 GEN
Solar/Wind Harmer
4.355
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.417
276882AE2-255 GEN
Solar/Wind Harmer
0.825
971675AH1-338 GEN
Solar/Wind Harmer
2.746
971411AH1-196 GEN
Solar/Wind Harmer
10.56
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971171AH1-044 GEN
Solar/Wind Harmer
14.009
274823ROCKFORD ;21
Adder
19.51
971611AH1-305 GEN
Solar/Wind Harmer
4.152
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.178
970169AG2-114 GEN
Solar/Wind Harmer
6.92
971681AH1-341 GEN
Solar/Wind Harmer
11.133
961011AF2-392 GEN
Solar/Wind Harmer
4.021
957751AF2-069 GEN
Solar/Wind Harmer
0.225
971549AH1-272 GEN
Solar/Wind Harmer
14.034
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
6.746
965041AG1-368 GEN
Solar/Wind Harmer
6.733
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.744
963791AG1-232 GEN
Solar/Wind Harmer
8.989
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.241
963841AG1-237 GEN
Solar/Wind Harmer
2.776
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.231
276848AB2-070 GEN3
Solar/Wind Harmer
0.23
970289AG2-191 GEN
Solar/Wind Harmer
1.184
971609AH1-304 GEN
Solar/Wind Harmer
1.011
270594AE1-207 GEN
Solar/Wind Harmer
6.856
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.765
270284AF1-227 GEN1
Solar/Wind Harmer
0.008
270286AF1-227 GEN2
Solar/Wind Harmer
0.003
270287AF1-227 GEN3
Solar/Wind Harmer
0.003
270054AF2-122 C O1
Solar/Wind Helper
1.65
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.189
MECLTFEXP_MEC->PJM
CLTF
14.69
SIGELTFEXP_SIGE->PJM
CLTF
0.339
LAGNLTFEXP_LAGN->PJM
CLTF
11.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.669
TVALTFEXP_TVA->PJM
CLTF
5.062
CPLELTFEXP_CPLE->PJM
CLTF
1.429
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.023
NYPJM->LTFIMP_NY
CLTF
2.589
LGEELTFEXP_LGEE->PJM
CLTF
3.659
WECLTFEXP_WEC->PJM
CLTF
3.814
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.355

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P7-1_#10944___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.6 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5101.3
MW Contribution:32.37
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
9.068
270143AC1-141 CT2_
50/50
2.636
274773LINCOLN ;4U
50/50
7.2
274774LINCOLN ;5U
50/50
7.2
24639705ELKHART HY
50/50
0.178
970521AG2-332 GEN
50/50
12.672
962761AG1-125 GEN
Solar/Wind Harmer
88.693
970149AG2-104 GEN
Solar/Wind Harmer
109.536
970155AG2-107 GEN
Solar/Wind Harmer
38.674
970245AG2-165 GEN
Solar/Wind Harmer
20.738
972207SS24-0001
Solar/Wind Harmer
24.126
270505AE1-170 C O1
Solar/Wind Harmer
16.366
945111AF1-176 GEN
Solar/Wind Harmer
19.395
270063AE2-323 C
Solar/Wind Harmer
2.395
274723RIVER EC ;12
Adder
19.397
274751CRETE EC ;1U
Adder
5.281
270102X2-052 ST
50/50
1.777
270100X2-052 CT1
50/50
1.637
270101X2-052 CT2
50/50
1.637
274770LINCOLN ;1U
50/50
7.2
274771LINCOLN ;2U
50/50
7.2
247620Y3-023
50/50
0.531
970321AG2-212 GEN
Solar/Wind Harmer
20.738
965681AG1-436 GEN
Solar/Wind Harmer
13.825
965791AG1-447 GEN
Solar/Wind Harmer
7.073
270216AD2-079_GEN
Solar/Wind Harmer
0.668
270526AF1-158 GEN
Solar/Wind Harmer
5.006
24441505OLIV SLR
Solar/Wind Harmer
0.147
957891AF2-083 GEN
Solar/Wind Harmer
3.677
960981AF2-389 GEN
Solar/Wind Harmer
1.648
961051AF2-396 GEN
Solar/Wind Harmer
17.18
961051AF2-396 GEN
Solar/Wind Harmer
7.99
274808UNIV PK N;4U
Adder
5.37
972259AH1-714 GEN
Adder
20.504
274803UNIV PARK;6U
Adder
6.261
274888KELLY CRK;1U
Solar/Wind Harmer
6.338
274887GEN-1.85
Solar/Wind Harmer
5.722
276843GEN-1.7
Solar/Wind Harmer
0.616
958011AF2-095 GEN
Solar/Wind Harmer
15.458
274674JOLIET 9 ;6U
Adder
16.418
274847GR RIDGE ;BU
Solar/Wind Harmer
5.386
970611AG2-400 GEN
Solar/Wind Harmer
10.607
971573AH1-285 GEN
Solar/Wind Harmer
9.097
274695ROCKY RD ;2P
Adder
11.708
274693ROCKY RD ;1P
Adder
11.593
274697ROCKY RD ;3P
Adder
3.181
274696ROCKY RD ;4P
Adder
11.984
958481AF2-142 GEN
Solar/Wind Harmer
15.755
274861TOP CROP ;1U
Solar/Wind Harmer
6.362
274862TOP CROP ;2U
Solar/Wind Harmer
5.313
274683WAUKEGAN ;8U
Adder
22.11
274683WAUKEGAN ;8U
Adder
18.638
962691AG1-118 GEN
Solar/Wind Harmer
31.39
970921AG2-575 GEN
Solar/Wind Harmer
10.445
270142AC1-141 CT1_
50/50
2.636
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.184
274772LINCOLN ;3U
50/50
7.2
24642205MAYFLWER
50/50
0.738
970153AG2-106 GEN
Solar/Wind Harmer
38.674
970349AG2-230 GEN
Solar/Wind Harmer
17.476
970513AG2-328 GEN
Solar/Wind Harmer
20.738
970517AG2-330 GEN
Solar/Wind Harmer
18.809
270043AE2-236 GEN
Solar/Wind Harmer
6.251
247643Z2-116 C
Solar/Wind Harmer
0.077
945111AF1-176 GEN
Solar/Wind Harmer
6.147
274724RIVER EC ;11
Adder
19.173
944531AF1-118 GEN
Solar/Wind Harmer
37.878
972231SS25-0005
Solar/Wind Harmer
10.253
972181SS23-001
Solar/Wind Harmer
6.408
274752CRETE EC ;2U
Adder
5.281
274753CRETE EC ;3U
Adder
5.281
970031AG2-029 GEN
Solar/Wind Harmer
32.374
970707AG2-453 GEN
Solar/Wind Harmer
30.198
274826FISK ;BP
Adder
11.757
274802UNIV PARK;5U
Adder
6.261
276772AC2-154 GEN
Solar/Wind Harmer
2.994
276806AD2-047 C O1
Solar/Wind Harmer
11.484
970941AG2-585 GEN
Solar/Wind Harmer
13.419
972228AH1-698 GEN2
Adder
3.976
274800UNIV PARK;3U
Adder
6.257
972038AH1-567 GEN2
Adder
0.392
276897AD1-100 C
Solar/Wind Harmer
31.058
939351AE1-166 GEN
Solar/Wind Harmer
6.346
274676JOLIET 29;8U
Adder
31.584
274729ELWOOD EC;1P
Adder
17.516
274730ELWOOD EC;6P
Adder
17.516
274734ELWOOD EC;8P
Adder
17.516
274736ELWOOD EC;9P
Adder
17.516
276893AG1-478 C
Solar/Wind Harmer
0.445
943121AE2-341 GEN
Solar/Wind Harmer
15.932
943591AF1-030 GEN
Solar/Wind Harmer
10.621
959331AF2-224 GEN
Solar/Wind Harmer
10.607
965021AG1-366 GEN
Solar/Wind Harmer
2.467
24441205WTRV SLR C
Solar/Wind Harmer
0.143
270535AF1-215 GEN1
Solar/Wind Harmer
4.803
24721905FLATG4
Adder
21.327
276694AA1-018 GEN2
Solar/Wind Harmer
6.628
274682WAUKEGAN ;7U
Adder
18.874
247604X1-042
Adder
0.436
964401AG1-302 GEN
Solar/Wind Harmer
9.472
274872LEEDK;1U
Solar/Wind Harmer
0.267
276805AD2-038 GEN
Solar/Wind Harmer
5.342
276799AD1-013 GEN
Solar/Wind Harmer
2.29
946671AF1-331 GEN
Solar/Wind Harmer
0.434
274855GSG-6 ;RU
Solar/Wind Harmer
3.824
274850MENDOTA H;RU
Solar/Wind Harmer
2.659
276602WESTBROOK C
Solar/Wind Harmer
2.201
276863AD2-134 GEN
Solar/Wind Harmer
1.849
959141AF2-205 GEN
Solar/Wind Harmer
6.241
972236AH1-702 GEN2
Adder
2.25
274760LEE CO EC;1U
Adder
9.448
274767LEE CO EC;8U
Adder
9.337
959091AF2-200 GEN
Solar/Wind Harmer
0.659
971599AH1-298 GEN
50/50
10.665
270144AC1-141 ST1_
50/50
2.335
274775LINCOLN ;6U
50/50
7.2
274776LINCOLN ;7U
50/50
7.2
274777LINCOLN ;8U
50/50
7.2
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
88.693
971347AH1-153 GEN
Solar/Wind Harmer
17.476
270071AF1-092 GEN
Solar/Wind Harmer
16.765
960681AF2-359 GEN
Solar/Wind Harmer
4.178
971771AH1-392 GEN
Solar/Wind Harmer
9.947
971769AH1-391 GEN
Solar/Wind Harmer
11.009
274814UNIV PK N;0U
Adder
5.441
274807UNIV PK N;3U
Adder
5.429
274805UNIV PK N;1U
Adder
5.405
274811UNIV PK N;7U
Adder
5.394
274827FISK ;RP
Adder
8.332
972037AH1-567 GEN1
Adder
0.197
960591AF2-350 GEN
Solar/Wind Harmer
10.735
972227AH1-698 GEN1
Adder
2.799
944161AF1-084 GEN
Solar/Wind Harmer
2.371
274687WILL CNTY;4U
Adder
29.852
274687WILL CNTY;4U
Adder
29.852
274675JOLIET 29;7U
Adder
32.754
274675JOLIET 29;7U
Adder
31.584
274731ELWOOD EC;2P
Adder
17.516
274733ELWOOD EC;3P
Adder
17.516
274735ELWOOD EC;4P
Adder
17.516
274728ELWOOD EC;5P
Adder
17.516
970833AG2-524 GEN
Solar/Wind Harmer
9.299
970833AG2-524 GEN
Solar/Wind Harmer
4.325
24729505KEY G4
Adder
6.895
274746AC1-111 G10
Adder
5.928
274744AC1-111 GEN8
Adder
5.928
270536AF1-215 GEN2
Solar/Wind Harmer
4.803
971177AH1-047 GEN
Solar/Wind Harmer
6.086
276868AE1-113 GEN
Solar/Wind Harmer
10.506
276882AE2-255 GEN
Solar/Wind Harmer
3.502
958391AF2-133 GEN
Solar/Wind Harmer
9.41
971675AH1-338 GEN
Solar/Wind Harmer
18.64
971411AH1-196 GEN
Solar/Wind Harmer
15.533
274863CRW1-WTG
Solar/Wind Harmer
5.758
274864CRW2-WTG
Solar/Wind Harmer
5.758
274823ROCKFORD ;21
Adder
20.032
270054AF2-122 C O1
Solar/Wind Helper
1.787
971171AH1-044 GEN
Solar/Wind Harmer
0.659
970921AG2-575 GEN
Solar/Wind Harmer
2.429
958491AF2-143 GEN
Solar/Wind Harmer
15.621
942991AE2-321 GEN
Solar/Wind Harmer
10.388
274754CRETE EC ;4U
Adder
5.281
276164X3-005 C
Solar/Wind Harmer
0.759
270449AD2-020 GEN
Solar/Wind Harmer
3.026
943021AE2-325 GEN
Solar/Wind Harmer
3.932
274812UNIV PK N;8U
Adder
5.394
276776AD2-060 GEN
Solar/Wind Harmer
0.454
274801UNIV PARK;4U
Adder
6.257
970373AG2-245 GEN
Solar/Wind Harmer
22.515
941551AE2-152 GEN
Solar/Wind Harmer
4.854
274676JOLIET 29;8U
Adder
32.754
274674JOLIET 9 ;6U
Adder
16.418
274732ELWOOD EC;7P
Adder
17.516
274871GR RIDGE ;2U
Solar/Wind Harmer
8.188
965011AG1-365 GEN
Solar/Wind Harmer
10.607
274745AC1-111 GEN9
Adder
5.928
270055AF2-134 C O1
Solar/Wind Harmer
3.202
24721705FLATG2
Adder
21.327
276691AA1-018 GEN1
Solar/Wind Harmer
0.489
274682WAUKEGAN ;7U
Adder
18.874
274828WAUKEGAN ;BP
Adder
11.59
960751AF2-366 GEN
Solar/Wind Harmer
2.997
962781AG1-127 GEN
Solar/Wind Harmer
9.933
958381AF2-132 GEN
Solar/Wind Harmer
9.472
274872LEEDK;1U
Solar/Wind Harmer
8.565
964861AG1-349 GEN
Solar/Wind Harmer
8.196
971917AH1-482 GEN
Solar/Wind Harmer
9.458
939401AE1-172 GEN
Solar/Wind Harmer
14.53
276901AD2-066 C O1
Solar/Wind Harmer
3.656
971997AH1-543 GEN
Solar/Wind Harmer
16.328
276861AD2-134 GEN
Solar/Wind Harmer
1.849
274822ROCKFORD ;11
Adder
20.179
972235AH1-702 GEN1
Adder
2.587
274761LEE CO EC;2U
Adder
9.448
274766LEE CO EC;7U
Adder
9.337
957471AF2-041 GEN
Solar/Wind Harmer
0.989
959081AF2-199 GEN
Solar/Wind Harmer
0.33
971067AG2-660 GEN
Solar/Wind Harmer
0.077
274879MINONK ;1U
Solar/Wind Harmer
7.005
971333AH1-146 GEN
Solar/Wind Harmer
20.7
971335AH1-147 GEN
Solar/Wind Harmer
20.7
274764LEE CO EC;5U
Adder
9.47
274765LEE CO EC;6U
Adder
9.47
274762LEE CO EC;3U
Adder
9.448
274763LEE CO EC;4U
Adder
9.359
972267AH1-718 GEN
Adder
4.199
971341AH1-150 GEN
Solar/Wind Harmer
0.659
971343AH1-151 GEN
Solar/Wind Harmer
0.659
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.675
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.249
MECLTFEXP_MEC->PJM
CLTF
15.261
SIGELTFEXP_SIGE->PJM
CLTF
0.364
LAGNLTFEXP_LAGN->PJM
CLTF
12.245
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.222
TVALTFEXP_TVA->PJM
CLTF
5.61
CPLELTFEXP_CPLE->PJM
CLTF
1.907
CBM West 2LTFEXP_CBM-W2->PJM
CBM
93.196
NYPJM->LTFIMP_NY
CLTF
2.821
LGEELTFEXP_LGEE->PJM
CLTF
4.037
WECLTFEXP_WEC->PJM
CLTF
3.917
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.99 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5027.51
MW Contribution:33.99
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.761
24344005CKG1
50/50
7.535
24641605TWIN BRNCH
50/50
0.02
24642205MAYFLWER
50/50
0.772
944961AF1-161 GEN
50/50
3.302
962601AG1-109 GEN
50/50
3.302
970153AG2-106 GEN
Solar/Wind Harmer
38.894
970349AG2-230 GEN
Solar/Wind Harmer
18.111
970513AG2-328 GEN
Solar/Wind Harmer
21.268
970517AG2-330 GEN
Solar/Wind Harmer
19.29
270043AE2-236 GEN
Solar/Wind Harmer
6.511
247643Z2-116 C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
6.454
970031AG2-029 GEN
Solar/Wind Harmer
33.986
274772LINCOLN ;3U
Adder
6.975
24441205WTRV SLR C
Solar/Wind Harmer
0.151
959331AF2-224 GEN
Solar/Wind Harmer
11.187
965021AG1-366 GEN
Solar/Wind Harmer
2.602
274724RIVER EC ;11
Adder
19.746
944531AF1-118 GEN
Solar/Wind Harmer
39.003
972231SS25-0005
Solar/Wind Harmer
10.567
972181SS23-001
Solar/Wind Harmer
6.604
274752CRETE EC ;2U
Adder
5.442
274753CRETE EC ;3U
Adder
5.442
247604X1-042
Adder
0.463
970707AG2-453 GEN
Solar/Wind Harmer
31.017
274802UNIV PARK;5U
Adder
6.439
274826FISK ;BP
Adder
12.09
276772AC2-154 GEN
Solar/Wind Harmer
3.077
276806AD2-047 C O1
Solar/Wind Harmer
11.806
970941AG2-585 GEN
Solar/Wind Harmer
13.795
274800UNIV PARK;3U
Adder
6.433
972038AH1-567 GEN2
Adder
0.403
972228AH1-698 GEN2
Adder
4.086
276897AD1-100 C
Solar/Wind Harmer
31.901
939351AE1-166 GEN
Solar/Wind Harmer
6.518
274676JOLIET 29;8U
Adder
32.446
274729ELWOOD EC;1P
Adder
17.991
274730ELWOOD EC;6P
Adder
17.991
274734ELWOOD EC;8P
Adder
17.991
274736ELWOOD EC;9P
Adder
17.991
276893AG1-478 C
Solar/Wind Harmer
0.457
270535AF1-215 GEN1
Solar/Wind Harmer
4.953
943121AE2-341 GEN
Solar/Wind Harmer
16.349
943591AF1-030 GEN
Solar/Wind Harmer
10.899
276694AA1-018 GEN2
Solar/Wind Harmer
6.801
274682WAUKEGAN ;7U
Adder
19.358
964401AG1-302 GEN
Solar/Wind Harmer
9.749
274872LEEDK;1U
Solar/Wind Harmer
0.273
276805AD2-038 GEN
Solar/Wind Harmer
5.478
276799AD1-013 GEN
Solar/Wind Harmer
2.346
946671AF1-331 GEN
Solar/Wind Harmer
0.444
959141AF2-205 GEN
Solar/Wind Harmer
6.413
274855GSG-6 ;RU
Solar/Wind Harmer
3.917
274850MENDOTA H;RU
Solar/Wind Harmer
2.724
276602WESTBROOK C
Solar/Wind Harmer
2.255
276863AD2-134 GEN
Solar/Wind Harmer
1.894
972236AH1-702 GEN2
Adder
2.303
274760LEE CO EC;1U
Adder
9.662
274767LEE CO EC;8U
Adder
9.549
24721905FLATG4
Adder
19.907
24344105CKG2
50/50
9.384
270143AC1-141 CT2_
50/50
2.761
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.281
24307105BERRINSP G
50/50
0.025
962761AG1-125 GEN
Solar/Wind Harmer
89.197
970149AG2-104 GEN
Solar/Wind Harmer
110.158
970155AG2-107 GEN
Solar/Wind Harmer
38.894
970245AG2-165 GEN
Solar/Wind Harmer
21.268
270505AE1-170 C O1
Solar/Wind Harmer
17.176
945111AF1-176 GEN
Solar/Wind Harmer
20.364
270063AE2-323 C
Solar/Wind Harmer
2.513
270449AD2-020 GEN
Solar/Wind Harmer
3.183
943021AE2-325 GEN
Solar/Wind Harmer
4.136
972207SS24-0001
Solar/Wind Harmer
24.8
274773LINCOLN ;4U
Adder
6.975
274774LINCOLN ;5U
Adder
6.975
965011AG1-365 GEN
Solar/Wind Harmer
11.187
274723RIVER EC ;12
Adder
19.976
274751CRETE EC ;1U
Adder
5.442
274754CRETE EC ;4U
Adder
5.442
276164X3-005 C
Solar/Wind Harmer
0.781
274812UNIV PK N;8U
Adder
5.552
970373AG2-245 GEN
Solar/Wind Harmer
23.259
276776AD2-060 GEN
Solar/Wind Harmer
0.467
274801UNIV PARK;4U
Adder
6.433
941551AE2-152 GEN
Solar/Wind Harmer
4.986
274676JOLIET 29;8U
Adder
33.648
274674JOLIET 9 ;6U
Adder
16.864
274732ELWOOD EC;7P
Adder
17.991
274871GR RIDGE ;2U
Solar/Wind Harmer
8.406
270055AF2-134 C O1
Solar/Wind Harmer
3.301
274745AC1-111 GEN9
Adder
6.083
276691AA1-018 GEN1
Solar/Wind Harmer
0.502
274682WAUKEGAN ;7U
Adder
19.358
274828WAUKEGAN ;BP
Adder
11.886
958381AF2-132 GEN
Solar/Wind Harmer
9.749
964861AG1-349 GEN
Solar/Wind Harmer
8.434
971917AH1-482 GEN
Solar/Wind Harmer
9.733
971599AH1-298 GEN
50/50
11.057
270144AC1-141 ST1_
50/50
2.446
24643105BUCHANAN
50/50
0.015
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
89.197
971347AH1-153 GEN
Solar/Wind Harmer
18.111
270071AF1-092 GEN
Solar/Wind Harmer
17.338
971771AH1-392 GEN
Solar/Wind Harmer
10.383
960681AF2-359 GEN
Solar/Wind Harmer
4.333
971769AH1-391 GEN
Solar/Wind Harmer
11.46
944161AF1-084 GEN
Solar/Wind Harmer
2.498
274775LINCOLN ;6U
Adder
6.975
274776LINCOLN ;7U
Adder
6.975
274777LINCOLN ;8U
Adder
6.975
274814UNIV PK N;0U
Adder
5.601
274807UNIV PK N;3U
Adder
5.589
274805UNIV PK N;1U
Adder
5.565
274811UNIV PK N;7U
Adder
5.552
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.568
960591AF2-350 GEN
Solar/Wind Harmer
11.036
972227AH1-698 GEN1
Adder
2.877
274687WILL CNTY;4U
Adder
30.673
274687WILL CNTY;4U
Adder
30.673
274675JOLIET 29;7U
Adder
33.649
274675JOLIET 29;7U
Adder
32.447
274731ELWOOD EC;2P
Adder
17.991
274733ELWOOD EC;3P
Adder
17.991
274735ELWOOD EC;4P
Adder
17.991
274728ELWOOD EC;5P
Adder
17.991
970833AG2-524 GEN
Solar/Wind Harmer
9.547
970833AG2-524 GEN
Solar/Wind Harmer
4.44
24729505KEY G4
Adder
7.093
270536AF1-215 GEN2
Solar/Wind Harmer
4.953
274746AC1-111 G10
Adder
6.083
274744AC1-111 GEN8
Adder
6.083
958391AF2-133 GEN
Solar/Wind Harmer
9.677
971177AH1-047 GEN
Solar/Wind Harmer
6.235
276868AE1-113 GEN
Solar/Wind Harmer
10.768
276882AE2-255 GEN
Solar/Wind Harmer
3.589
971411AH1-196 GEN
Solar/Wind Harmer
15.911
971675AH1-338 GEN
Solar/Wind Harmer
19.093
274823ROCKFORD ;21
Adder
20.508
270054AF2-122 C O1
Solar/Wind Helper
1.62
971549AH1-272 GEN
Solar/Wind Harmer
15.966
960751AF2-366 GEN
Solar/Wind Harmer
3.071
962781AG1-127 GEN
Solar/Wind Harmer
10.181
274872LEEDK;1U
Solar/Wind Harmer
8.777
939401AE1-172 GEN
Solar/Wind Harmer
14.891
276901AD2-066 C O1
Solar/Wind Harmer
3.747
971997AH1-543 GEN
Solar/Wind Harmer
16.729
276861AD2-134 GEN
Solar/Wind Harmer
1.894
274822ROCKFORD ;11
Adder
20.658
972235AH1-702 GEN1
Adder
2.648
274761LEE CO EC;2U
Adder
9.662
274766LEE CO EC;7U
Adder
9.549
24721705FLATG2
Adder
19.907
270102X2-052 ST
50/50
1.844
270100X2-052 CT1
50/50
1.699
270101X2-052 CT2
50/50
1.699
247620Y3-023
50/50
0.557
970321AG2-212 GEN
Solar/Wind Harmer
21.268
270216AD2-079_GEN
Solar/Wind Harmer
0.699
270526AF1-158 GEN
Solar/Wind Harmer
5.214
965681AG1-436 GEN
Solar/Wind Harmer
14.336
965791AG1-447 GEN
Solar/Wind Harmer
7.335
24441505OLIV SLR
Solar/Wind Harmer
0.154
957891AF2-083 GEN
Solar/Wind Harmer
3.858
960981AF2-389 GEN
Solar/Wind Harmer
1.729
961051AF2-396 GEN
Solar/Wind Harmer
18.061
961051AF2-396 GEN
Solar/Wind Harmer
8.401
274770LINCOLN ;1U
Adder
6.975
274771LINCOLN ;2U
Adder
6.975
970611AG2-400 GEN
Solar/Wind Harmer
11.187
274808UNIV PK N;4U
Adder
5.528
274803UNIV PARK;6U
Adder
6.439
972259AH1-714 GEN
Adder
21.064
274888KELLY CRK;1U
Solar/Wind Harmer
6.515
274887GEN-1.85
Solar/Wind Harmer
5.882
276843GEN-1.7
Solar/Wind Harmer
0.633
958011AF2-095 GEN
Solar/Wind Harmer
15.891
274674JOLIET 9 ;6U
Adder
16.864
274847GR RIDGE ;BU
Solar/Wind Harmer
5.529
971573AH1-285 GEN
Solar/Wind Harmer
9.332
274695ROCKY RD ;2P
Adder
12.008
274693ROCKY RD ;1P
Adder
11.89
274697ROCKY RD ;3P
Adder
3.262
274696ROCKY RD ;4P
Adder
12.291
958481AF2-142 GEN
Solar/Wind Harmer
16.166
274861TOP CROP ;1U
Solar/Wind Harmer
6.528
274862TOP CROP ;2U
Solar/Wind Harmer
5.451
274683WAUKEGAN ;8U
Adder
22.675
274683WAUKEGAN ;8U
Adder
19.114
962691AG1-118 GEN
Solar/Wind Harmer
32.178
970921AG2-575 GEN
Solar/Wind Harmer
10.705
970921AG2-575 GEN
Solar/Wind Harmer
2.49
958491AF2-143 GEN
Solar/Wind Harmer
16.016
942991AE2-321 GEN
Solar/Wind Harmer
10.644
274879MINONK ;1U
Solar/Wind Harmer
7.179
971333AH1-146 GEN
Solar/Wind Harmer
21.203
971335AH1-147 GEN
Solar/Wind Harmer
21.203
274764LEE CO EC;5U
Adder
9.685
274765LEE CO EC;6U
Adder
9.685
274762LEE CO EC;3U
Adder
9.662
274763LEE CO EC;4U
Adder
9.571
972267AH1-718 GEN
Adder
4.292
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.22
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.233
MECLTFEXP_MEC->PJM
CLTF
15.452
SIGELTFEXP_SIGE->PJM
CLTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
11.82
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.928
TVALTFEXP_TVA->PJM
CLTF
5.326
CPLELTFEXP_CPLE->PJM
CLTF
1.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.671
NYPJM->LTFIMP_NY
CLTF
2.826
LGEELTFEXP_LGEE->PJM
CLTF
3.895
WECLTFEXP_WEC->PJM
CLTF
4.009
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.373

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.3 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4904.47
MW Contribution:31.97
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.597
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.08
24642205MAYFLWER
50/50
0.726
274772LINCOLN ;3U
50/50
7.031
970153AG2-106 GEN
Solar/Wind Harmer
38.539
970349AG2-230 GEN
Solar/Wind Harmer
17.182
970513AG2-328 GEN
Solar/Wind Harmer
20.275
970517AG2-330 GEN
Solar/Wind Harmer
18.389
270043AE2-236 GEN
Solar/Wind Harmer
6.17
247643Z2-116 C
Solar/Wind Harmer
0.076
945111AF1-176 GEN
Solar/Wind Harmer
6.059
970031AG2-029 GEN
Solar/Wind Harmer
31.974
944531AF1-118 GEN
Solar/Wind Harmer
37.097
274724RIVER EC ;11
Adder
18.728
972231SS25-0005
Solar/Wind Harmer
10.017
972181SS23-001
Solar/Wind Harmer
6.261
274752CRETE EC ;2U
Adder
5.159
274753CRETE EC ;3U
Adder
5.159
959331AF2-224 GEN
Solar/Wind Harmer
10.534
965021AG1-366 GEN
Solar/Wind Harmer
2.45
970707AG2-453 GEN
Solar/Wind Harmer
29.454
274826FISK ;BP
Adder
11.471
274802UNIV PARK;5U
Adder
6.109
276772AC2-154 GEN
Solar/Wind Harmer
2.92
276806AD2-047 C O1
Solar/Wind Harmer
11.203
970941AG2-585 GEN
Solar/Wind Harmer
13.09
274800UNIV PARK;3U
Adder
6.104
972038AH1-567 GEN2
Adder
0.382
972228AH1-698 GEN2
Adder
3.878
24441205WTRV SLR C
Solar/Wind Harmer
0.141
276897AD1-100 C
Solar/Wind Harmer
30.28
939351AE1-166 GEN
Solar/Wind Harmer
6.187
274676JOLIET 29;8U
Adder
30.792
274729ELWOOD EC;1P
Adder
17.074
274730ELWOOD EC;6P
Adder
17.074
274734ELWOOD EC;8P
Adder
17.074
274736ELWOOD EC;9P
Adder
17.074
276893AG1-478 C
Solar/Wind Harmer
0.434
943121AE2-341 GEN
Solar/Wind Harmer
15.521
943591AF1-030 GEN
Solar/Wind Harmer
10.347
247604X1-042
Adder
0.431
270535AF1-215 GEN1
Solar/Wind Harmer
4.686
276694AA1-018 GEN2
Solar/Wind Harmer
6.453
274682WAUKEGAN ;7U
Adder
18.372
964401AG1-302 GEN
Solar/Wind Harmer
9.225
274872LEEDK;1U
Solar/Wind Harmer
0.259
276805AD2-038 GEN
Solar/Wind Harmer
5.197
276799AD1-013 GEN
Solar/Wind Harmer
2.226
946671AF1-331 GEN
Solar/Wind Harmer
0.422
274855GSG-6 ;RU
Solar/Wind Harmer
3.717
274850MENDOTA H;RU
Solar/Wind Harmer
2.585
276602WESTBROOK C
Solar/Wind Harmer
2.14
276863AD2-134 GEN
Solar/Wind Harmer
1.798
959141AF2-205 GEN
Solar/Wind Harmer
6.07
972236AH1-702 GEN2
Adder
2.185
274760LEE CO EC;1U
Adder
9.168
274767LEE CO EC;8U
Adder
9.06
24721905FLATG4
Adder
19.59
959091AF2-200 GEN
Solar/Wind Harmer
0.641
24344105CKG2
50/50
8.921
270143AC1-141 CT2_
50/50
2.597
24639705ELKHART HY
50/50
0.175
970521AG2-332 GEN
50/50
12.491
274773LINCOLN ;4U
50/50
7.031
274774LINCOLN ;5U
50/50
7.031
962761AG1-125 GEN
Solar/Wind Harmer
88.384
970149AG2-104 GEN
Solar/Wind Harmer
109.154
970155AG2-107 GEN
Solar/Wind Harmer
38.539
970245AG2-165 GEN
Solar/Wind Harmer
20.275
270505AE1-170 C O1
Solar/Wind Harmer
16.131
270063AE2-323 C
Solar/Wind Harmer
2.365
945111AF1-176 GEN
Solar/Wind Harmer
19.119
972207SS24-0001
Solar/Wind Harmer
23.558
270449AD2-020 GEN
Solar/Wind Harmer
2.984
943021AE2-325 GEN
Solar/Wind Harmer
3.877
274723RIVER EC ;12
Adder
18.946
274751CRETE EC ;1U
Adder
5.159
274754CRETE EC ;4U
Adder
5.159
276164X3-005 C
Solar/Wind Harmer
0.741
965011AG1-365 GEN
Solar/Wind Harmer
10.534
274812UNIV PK N;8U
Adder
5.266
970373AG2-245 GEN
Solar/Wind Harmer
22.001
276776AD2-060 GEN
Solar/Wind Harmer
0.443
274801UNIV PARK;4U
Adder
6.104
941551AE2-152 GEN
Solar/Wind Harmer
4.732
274676JOLIET 29;8U
Adder
31.933
274674JOLIET 9 ;6U
Adder
16.004
274732ELWOOD EC;7P
Adder
17.074
274871GR RIDGE ;2U
Solar/Wind Harmer
7.979
274745AC1-111 GEN9
Adder
5.774
270055AF2-134 C O1
Solar/Wind Harmer
3.123
276691AA1-018 GEN1
Solar/Wind Harmer
0.476
274682WAUKEGAN ;7U
Adder
18.372
274828WAUKEGAN ;BP
Adder
11.281
958381AF2-132 GEN
Solar/Wind Harmer
9.225
960751AF2-366 GEN
Solar/Wind Harmer
2.915
962781AG1-127 GEN
Solar/Wind Harmer
9.663
964861AG1-349 GEN
Solar/Wind Harmer
7.981
971917AH1-482 GEN
Solar/Wind Harmer
9.21
274872LEEDK;1U
Solar/Wind Harmer
8.331
939401AE1-172 GEN
Solar/Wind Harmer
14.131
276901AD2-066 C O1
Solar/Wind Harmer
3.555
971997AH1-543 GEN
Solar/Wind Harmer
15.875
276861AD2-134 GEN
Solar/Wind Harmer
1.798
274822ROCKFORD ;11
Adder
19.604
972235AH1-702 GEN1
Adder
2.513
274761LEE CO EC;2U
Adder
9.168
274766LEE CO EC;7U
Adder
9.06
24721705FLATG2
Adder
19.59
957471AF2-041 GEN
Solar/Wind Harmer
0.961
959081AF2-199 GEN
Solar/Wind Harmer
0.32
971067AG2-660 GEN
Solar/Wind Harmer
0.075
270102X2-052 ST
50/50
1.744
270100X2-052 CT1
50/50
1.606
270101X2-052 CT2
50/50
1.606
247620Y3-023
50/50
0.524
274770LINCOLN ;1U
50/50
7.031
274771LINCOLN ;2U
50/50
7.031
970321AG2-212 GEN
Solar/Wind Harmer
20.275
270216AD2-079_GEN
Solar/Wind Harmer
0.658
965681AG1-436 GEN
Solar/Wind Harmer
13.559
965791AG1-447 GEN
Solar/Wind Harmer
6.937
270526AF1-158 GEN
Solar/Wind Harmer
4.919
24441505OLIV SLR
Solar/Wind Harmer
0.145
957891AF2-083 GEN
Solar/Wind Harmer
3.624
960981AF2-389 GEN
Solar/Wind Harmer
1.624
961051AF2-396 GEN
Solar/Wind Harmer
16.938
961051AF2-396 GEN
Solar/Wind Harmer
7.878
970611AG2-400 GEN
Solar/Wind Harmer
10.534
274808UNIV PK N;4U
Adder
5.243
972259AH1-714 GEN
Adder
19.997
274803UNIV PARK;6U
Adder
6.109
274888KELLY CRK;1U
Solar/Wind Harmer
6.183
274887GEN-1.85
Solar/Wind Harmer
5.582
276843GEN-1.7
Solar/Wind Harmer
0.601
958011AF2-095 GEN
Solar/Wind Harmer
15.08
274674JOLIET 9 ;6U
Adder
16.004
274847GR RIDGE ;BU
Solar/Wind Harmer
5.248
971573AH1-285 GEN
Solar/Wind Harmer
8.859
274696ROCKY RD ;4P
Adder
11.666
274695ROCKY RD ;2P
Adder
11.398
274693ROCKY RD ;1P
Adder
11.285
274697ROCKY RD ;3P
Adder
3.096
958481AF2-142 GEN
Solar/Wind Harmer
15.339
274861TOP CROP ;1U
Solar/Wind Harmer
6.194
274862TOP CROP ;2U
Solar/Wind Harmer
5.172
274683WAUKEGAN ;8U
Adder
21.521
274683WAUKEGAN ;8U
Adder
18.141
962691AG1-118 GEN
Solar/Wind Harmer
30.542
970921AG2-575 GEN
Solar/Wind Harmer
10.161
970921AG2-575 GEN
Solar/Wind Harmer
2.363
958491AF2-143 GEN
Solar/Wind Harmer
15.196
942991AE2-321 GEN
Solar/Wind Harmer
10.102
274879MINONK ;1U
Solar/Wind Harmer
6.812
971333AH1-146 GEN
Solar/Wind Harmer
20.122
971335AH1-147 GEN
Solar/Wind Harmer
20.122
274764LEE CO EC;5U
Adder
9.19
274765LEE CO EC;6U
Adder
9.19
274762LEE CO EC;3U
Adder
9.168
274763LEE CO EC;4U
Adder
9.082
972267AH1-718 GEN
Adder
4.072
971341AH1-150 GEN
Solar/Wind Harmer
0.641
971343AH1-151 GEN
Solar/Wind Harmer
0.641
971599AH1-298 GEN
50/50
10.537
270144AC1-141 ST1_
50/50
2.301
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.031
274776LINCOLN ;7U
50/50
7.031
274777LINCOLN ;8U
50/50
7.031
962771AG1-126 GEN
Solar/Wind Harmer
88.384
971347AH1-153 GEN
Solar/Wind Harmer
17.182
270071AF1-092 GEN
Solar/Wind Harmer
16.471
971771AH1-392 GEN
Solar/Wind Harmer
9.787
960681AF2-359 GEN
Solar/Wind Harmer
4.098
971769AH1-391 GEN
Solar/Wind Harmer
10.814
944161AF1-084 GEN
Solar/Wind Harmer
2.339
274814UNIV PK N;0U
Adder
5.312
274807UNIV PK N;3U
Adder
5.3
274805UNIV PK N;1U
Adder
5.277
274811UNIV PK N;7U
Adder
5.266
274827FISK ;RP
Adder
8.13
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
10.472
972227AH1-698 GEN1
Adder
2.73
274687WILL CNTY;4U
Adder
29.107
274687WILL CNTY;4U
Adder
29.107
274675JOLIET 29;7U
Adder
31.933
274675JOLIET 29;7U
Adder
30.793
24729505KEY G4
Adder
6.744
274731ELWOOD EC;2P
Adder
17.074
274733ELWOOD EC;3P
Adder
17.074
274735ELWOOD EC;4P
Adder
17.074
274728ELWOOD EC;5P
Adder
17.074
970833AG2-524 GEN
Solar/Wind Harmer
9.062
970833AG2-524 GEN
Solar/Wind Harmer
4.215
274746AC1-111 G10
Adder
5.774
274744AC1-111 GEN8
Adder
5.774
270536AF1-215 GEN2
Solar/Wind Harmer
4.686
971177AH1-047 GEN
Solar/Wind Harmer
5.918
958391AF2-133 GEN
Solar/Wind Harmer
9.158
276868AE1-113 GEN
Solar/Wind Harmer
10.216
276882AE2-255 GEN
Solar/Wind Harmer
3.406
971675AH1-338 GEN
Solar/Wind Harmer
18.12
971411AH1-196 GEN
Solar/Wind Harmer
15.1
274863CRW1-WTG
Solar/Wind Harmer
5.594
274864CRW2-WTG
Solar/Wind Harmer
5.594
274823ROCKFORD ;21
Adder
19.462
270054AF2-122 C O1
Solar/Wind Helper
1.653
971171AH1-044 GEN
Solar/Wind Harmer
0.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
119.66
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.096
MECLTFEXP_MEC->PJM
CLTF
14.649
SIGELTFEXP_SIGE->PJM
CLTF
0.337
LAGNLTFEXP_LAGN->PJM
CLTF
11.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.594
TVALTFEXP_TVA->PJM
CLTF
5.037
CPLELTFEXP_CPLE->PJM
CLTF
1.403
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.692
NYPJM->LTFIMP_NY
CLTF
2.605
LGEELTFEXP_LGEE->PJM
CLTF
3.642
WECLTFEXP_WEC->PJM
CLTF
3.804
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.354

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P2-2_WP-500-DRT5_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-2_WP-500-DRT5_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.58 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4871.68
MW Contribution:31.99
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
8.924
270143AC1-141 CT2_
50/50
2.598
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.496
274773LINCOLN ;4U
50/50
7.034
274774LINCOLN ;5U
50/50
7.034
962761AG1-125 GEN
Solar/Wind Harmer
88.398
970149AG2-104 GEN
Solar/Wind Harmer
109.171
970155AG2-107 GEN
Solar/Wind Harmer
38.546
970245AG2-165 GEN
Solar/Wind Harmer
20.283
270505AE1-170 C O1
Solar/Wind Harmer
16.137
270063AE2-323 C
Solar/Wind Harmer
2.366
945111AF1-176 GEN
Solar/Wind Harmer
19.127
972207SS24-0001
Solar/Wind Harmer
23.568
270449AD2-020 GEN
Solar/Wind Harmer
2.985
943021AE2-325 GEN
Solar/Wind Harmer
3.878
274723RIVER EC ;12
Adder
18.954
274751CRETE EC ;1U
Adder
5.161
274754CRETE EC ;4U
Adder
5.161
276164X3-005 C
Solar/Wind Harmer
0.741
965011AG1-365 GEN
Solar/Wind Harmer
10.538
274812UNIV PK N;8U
Adder
5.268
970373AG2-245 GEN
Solar/Wind Harmer
22.01
276776AD2-060 GEN
Solar/Wind Harmer
0.443
274801UNIV PARK;4U
Adder
6.107
941551AE2-152 GEN
Solar/Wind Harmer
4.734
274676JOLIET 29;8U
Adder
31.946
274674JOLIET 9 ;6U
Adder
16.011
274732ELWOOD EC;7P
Adder
17.081
274871GR RIDGE ;2U
Solar/Wind Harmer
7.982
274745AC1-111 GEN9
Adder
5.777
270055AF2-134 C O1
Solar/Wind Harmer
3.125
276691AA1-018 GEN1
Solar/Wind Harmer
0.476
274682WAUKEGAN ;7U
Adder
18.38
274828WAUKEGAN ;BP
Adder
11.285
958381AF2-132 GEN
Solar/Wind Harmer
9.229
960751AF2-366 GEN
Solar/Wind Harmer
2.916
962781AG1-127 GEN
Solar/Wind Harmer
9.667
964861AG1-349 GEN
Solar/Wind Harmer
7.985
971917AH1-482 GEN
Solar/Wind Harmer
9.214
274872LEEDK;1U
Solar/Wind Harmer
8.334
939401AE1-172 GEN
Solar/Wind Harmer
14.137
276901AD2-066 C O1
Solar/Wind Harmer
3.557
971997AH1-543 GEN
Solar/Wind Harmer
15.882
276861AD2-134 GEN
Solar/Wind Harmer
1.799
274822ROCKFORD ;11
Adder
19.613
972235AH1-702 GEN1
Adder
2.514
274761LEE CO EC;2U
Adder
9.172
274766LEE CO EC;7U
Adder
9.064
24721705FLATG2
Adder
19.599
957471AF2-041 GEN
Solar/Wind Harmer
0.961
959081AF2-199 GEN
Solar/Wind Harmer
0.32
971067AG2-660 GEN
Solar/Wind Harmer
0.075
270142AC1-141 CT1_
50/50
2.598
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.083
24642205MAYFLWER
50/50
0.727
274772LINCOLN ;3U
50/50
7.034
970153AG2-106 GEN
Solar/Wind Harmer
38.546
970349AG2-230 GEN
Solar/Wind Harmer
17.189
970513AG2-328 GEN
Solar/Wind Harmer
20.283
970517AG2-330 GEN
Solar/Wind Harmer
18.396
270043AE2-236 GEN
Solar/Wind Harmer
6.172
247643Z2-116 C
Solar/Wind Harmer
0.076
945111AF1-176 GEN
Solar/Wind Harmer
6.062
970031AG2-029 GEN
Solar/Wind Harmer
31.987
944531AF1-118 GEN
Solar/Wind Harmer
37.113
274724RIVER EC ;11
Adder
18.735
972231SS25-0005
Solar/Wind Harmer
10.021
972181SS23-001
Solar/Wind Harmer
6.263
274752CRETE EC ;2U
Adder
5.161
274753CRETE EC ;3U
Adder
5.161
959331AF2-224 GEN
Solar/Wind Harmer
10.538
965021AG1-366 GEN
Solar/Wind Harmer
2.451
970707AG2-453 GEN
Solar/Wind Harmer
29.466
274826FISK ;BP
Adder
11.476
274802UNIV PARK;5U
Adder
6.111
276772AC2-154 GEN
Solar/Wind Harmer
2.922
276806AD2-047 C O1
Solar/Wind Harmer
11.207
970941AG2-585 GEN
Solar/Wind Harmer
13.095
274800UNIV PARK;3U
Adder
6.107
972038AH1-567 GEN2
Adder
0.382
972228AH1-698 GEN2
Adder
3.879
24441205WTRV SLR C
Solar/Wind Harmer
0.141
276897AD1-100 C
Solar/Wind Harmer
30.293
939351AE1-166 GEN
Solar/Wind Harmer
6.19
274676JOLIET 29;8U
Adder
30.805
274729ELWOOD EC;1P
Adder
17.081
274730ELWOOD EC;6P
Adder
17.081
274734ELWOOD EC;8P
Adder
17.081
274736ELWOOD EC;9P
Adder
17.081
276893AG1-478 C
Solar/Wind Harmer
0.434
943121AE2-341 GEN
Solar/Wind Harmer
15.527
943591AF1-030 GEN
Solar/Wind Harmer
10.352
247604X1-042
Adder
0.431
270535AF1-215 GEN1
Solar/Wind Harmer
4.688
276694AA1-018 GEN2
Solar/Wind Harmer
6.456
274682WAUKEGAN ;7U
Adder
18.38
964401AG1-302 GEN
Solar/Wind Harmer
9.229
274872LEEDK;1U
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
5.199
276799AD1-013 GEN
Solar/Wind Harmer
2.227
946671AF1-331 GEN
Solar/Wind Harmer
0.422
274855GSG-6 ;RU
Solar/Wind Harmer
3.719
274850MENDOTA H;RU
Solar/Wind Harmer
2.586
276602WESTBROOK C
Solar/Wind Harmer
2.141
276863AD2-134 GEN
Solar/Wind Harmer
1.799
959141AF2-205 GEN
Solar/Wind Harmer
6.072
972236AH1-702 GEN2
Adder
2.186
274760LEE CO EC;1U
Adder
9.172
274767LEE CO EC;8U
Adder
9.064
24721905FLATG4
Adder
19.599
959091AF2-200 GEN
Solar/Wind Harmer
0.641
971599AH1-298 GEN
50/50
10.541
270144AC1-141 ST1_
50/50
2.302
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.034
274776LINCOLN ;7U
50/50
7.034
274777LINCOLN ;8U
50/50
7.034
962771AG1-126 GEN
Solar/Wind Harmer
88.398
971347AH1-153 GEN
Solar/Wind Harmer
17.189
270071AF1-092 GEN
Solar/Wind Harmer
16.478
971771AH1-392 GEN
Solar/Wind Harmer
9.791
960681AF2-359 GEN
Solar/Wind Harmer
4.1
971769AH1-391 GEN
Solar/Wind Harmer
10.819
944161AF1-084 GEN
Solar/Wind Harmer
2.34
274814UNIV PK N;0U
Adder
5.314
274807UNIV PK N;3U
Adder
5.303
274805UNIV PK N;1U
Adder
5.28
274811UNIV PK N;7U
Adder
5.268
274827FISK ;RP
Adder
8.133
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
10.476
972227AH1-698 GEN1
Adder
2.731
274687WILL CNTY;4U
Adder
29.119
274687WILL CNTY;4U
Adder
29.119
274675JOLIET 29;7U
Adder
31.946
274675JOLIET 29;7U
Adder
30.805
24729505KEY G4
Adder
6.746
274731ELWOOD EC;2P
Adder
17.081
274733ELWOOD EC;3P
Adder
17.081
274735ELWOOD EC;4P
Adder
17.081
274728ELWOOD EC;5P
Adder
17.081
970833AG2-524 GEN
Solar/Wind Harmer
9.066
970833AG2-524 GEN
Solar/Wind Harmer
4.217
274746AC1-111 G10
Adder
5.777
274744AC1-111 GEN8
Adder
5.777
270536AF1-215 GEN2
Solar/Wind Harmer
4.688
971177AH1-047 GEN
Solar/Wind Harmer
5.92
958391AF2-133 GEN
Solar/Wind Harmer
9.162
276868AE1-113 GEN
Solar/Wind Harmer
10.221
276882AE2-255 GEN
Solar/Wind Harmer
3.407
971675AH1-338 GEN
Solar/Wind Harmer
18.128
971411AH1-196 GEN
Solar/Wind Harmer
15.106
274863CRW1-WTG
Solar/Wind Harmer
5.597
274864CRW2-WTG
Solar/Wind Harmer
5.597
274823ROCKFORD ;21
Adder
19.47
270054AF2-122 C O1
Solar/Wind Helper
1.652
971171AH1-044 GEN
Solar/Wind Harmer
0.641
270102X2-052 ST
50/50
1.744
270100X2-052 CT1
50/50
1.607
270101X2-052 CT2
50/50
1.607
247620Y3-023
50/50
0.524
274770LINCOLN ;1U
50/50
7.034
274771LINCOLN ;2U
50/50
7.034
970321AG2-212 GEN
Solar/Wind Harmer
20.283
270216AD2-079_GEN
Solar/Wind Harmer
0.658
965681AG1-436 GEN
Solar/Wind Harmer
13.565
965791AG1-447 GEN
Solar/Wind Harmer
6.94
270526AF1-158 GEN
Solar/Wind Harmer
4.921
24441505OLIV SLR
Solar/Wind Harmer
0.145
957891AF2-083 GEN
Solar/Wind Harmer
3.625
960981AF2-389 GEN
Solar/Wind Harmer
1.624
961051AF2-396 GEN
Solar/Wind Harmer
16.945
961051AF2-396 GEN
Solar/Wind Harmer
7.882
970611AG2-400 GEN
Solar/Wind Harmer
10.538
274808UNIV PK N;4U
Adder
5.245
972259AH1-714 GEN
Adder
20.005
274803UNIV PARK;6U
Adder
6.111
274888KELLY CRK;1U
Solar/Wind Harmer
6.185
274887GEN-1.85
Solar/Wind Harmer
5.584
276843GEN-1.7
Solar/Wind Harmer
0.601
958011AF2-095 GEN
Solar/Wind Harmer
15.086
274674JOLIET 9 ;6U
Adder
16.011
274847GR RIDGE ;BU
Solar/Wind Harmer
5.251
971573AH1-285 GEN
Solar/Wind Harmer
8.863
274696ROCKY RD ;4P
Adder
11.671
274695ROCKY RD ;2P
Adder
11.402
274693ROCKY RD ;1P
Adder
11.29
274697ROCKY RD ;3P
Adder
3.097
958481AF2-142 GEN
Solar/Wind Harmer
15.345
274861TOP CROP ;1U
Solar/Wind Harmer
6.196
274862TOP CROP ;2U
Solar/Wind Harmer
5.174
274683WAUKEGAN ;8U
Adder
21.53
274683WAUKEGAN ;8U
Adder
18.148
962691AG1-118 GEN
Solar/Wind Harmer
30.555
970921AG2-575 GEN
Solar/Wind Harmer
10.165
970921AG2-575 GEN
Solar/Wind Harmer
2.364
958491AF2-143 GEN
Solar/Wind Harmer
15.202
942991AE2-321 GEN
Solar/Wind Harmer
10.106
274879MINONK ;1U
Solar/Wind Harmer
6.815
971333AH1-146 GEN
Solar/Wind Harmer
20.131
971335AH1-147 GEN
Solar/Wind Harmer
20.131
274764LEE CO EC;5U
Adder
9.194
274765LEE CO EC;6U
Adder
9.194
274762LEE CO EC;3U
Adder
9.172
274763LEE CO EC;4U
Adder
9.086
972267AH1-718 GEN
Adder
4.074
971341AH1-150 GEN
Solar/Wind Harmer
0.641
971343AH1-151 GEN
Solar/Wind Harmer
0.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
119.724
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.112
MECLTFEXP_MEC->PJM
CLTF
14.656
SIGELTFEXP_SIGE->PJM
CLTF
0.337
LAGNLTFEXP_LAGN->PJM
CLTF
11.198
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.608
TVALTFEXP_TVA->PJM
CLTF
5.042
CPLELTFEXP_CPLE->PJM
CLTF
1.407
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.75
NYPJM->LTFIMP_NY
CLTF
2.602
LGEELTFEXP_LGEE->PJM
CLTF
3.645
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.354

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.71 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6157.38
MW Contribution:37.21
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.786
24721905FLATG4
50/50
32.751
970153AG2-106 GEN
Solar/Wind Harmer
41.667
970513AG2-328 GEN
Solar/Wind Harmer
23.936
970517AG2-330 GEN
Solar/Wind Harmer
21.709
970349AG2-230 GEN
Solar/Wind Harmer
20.011
270043AE2-236 GEN
Solar/Wind Harmer
7.153
274772LINCOLN ;3U
Adder
7.877
247643Z2-116 C
Solar/Wind Harmer
0.088
24642205MAYFLWER
Adder
0.8
274724RIVER EC ;11
Adder
22.273
970707AG2-453 GEN
Solar/Wind Harmer
35.145
972231SS25-0005
Solar/Wind Harmer
11.912
972181SS23-001
Solar/Wind Harmer
7.445
274752CRETE EC ;2U
Adder
6.135
274753CRETE EC ;3U
Adder
6.135
944531AF1-118 GEN
Solar/Wind Harmer
43.883
274826FISK ;BP
Adder
13.685
274802UNIV PARK;5U
Adder
7.287
276772AC2-154 GEN
Solar/Wind Harmer
3.485
276806AD2-047 C O1
Solar/Wind Harmer
13.37
970941AG2-585 GEN
Solar/Wind Harmer
15.623
972228AH1-698 GEN2
Adder
4.629
274800UNIV PARK;3U
Adder
7.284
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.064
276897AD1-100 C
Solar/Wind Harmer
36.195
939351AE1-166 GEN
Solar/Wind Harmer
7.396
274676JOLIET 29;8U
Adder
36.814
274729ELWOOD EC;1P
Adder
20.424
274730ELWOOD EC;6P
Adder
20.425
274734ELWOOD EC;8P
Adder
20.425
274736ELWOOD EC;9P
Adder
20.425
276893AG1-478 C
Solar/Wind Harmer
0.519
970031AG2-029 GEN
Solar/Wind Harmer
37.211
943121AE2-341 GEN
Solar/Wind Harmer
18.593
943591AF1-030 GEN
Solar/Wind Harmer
12.395
270535AF1-215 GEN1
Solar/Wind Harmer
5.608
276694AA1-018 GEN2
Solar/Wind Harmer
7.75
274682WAUKEGAN ;7U
Adder
22.07
964401AG1-302 GEN
Solar/Wind Harmer
11.095
274872LEEDK;1U
Solar/Wind Harmer
0.312
276805AD2-038 GEN
Solar/Wind Harmer
6.257
959331AF2-224 GEN
Solar/Wind Harmer
12.175
965021AG1-366 GEN
Solar/Wind Harmer
2.831
24441205WTRV SLR C
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
2.685
946671AF1-331 GEN
Solar/Wind Harmer
0.508
274855GSG-6 ;RU
Solar/Wind Harmer
4.484
274850MENDOTA H;RU
Solar/Wind Harmer
3.118
276602WESTBROOK C
Solar/Wind Harmer
2.581
276863AD2-134 GEN
Solar/Wind Harmer
2.169
959141AF2-205 GEN
Solar/Wind Harmer
7.332
972236AH1-702 GEN2
Adder
2.642
247604X1-042
Adder
0.502
274760LEE CO EC;1U
Adder
11.12
274767LEE CO EC;8U
Adder
10.989
959091AF2-200 GEN
Solar/Wind Harmer
0.774
24721805FLATG3
50/50
1.786
24721705FLATG2
50/50
32.751
24344105CKG2
50/50
10.346
962761AG1-125 GEN
Solar/Wind Harmer
95.557
970149AG2-104 GEN
Solar/Wind Harmer
118.013
970155AG2-107 GEN
Solar/Wind Harmer
41.667
970245AG2-165 GEN
Solar/Wind Harmer
23.936
972207SS24-0001
Solar/Wind Harmer
28.005
274773LINCOLN ;4U
Adder
7.877
274774LINCOLN ;5U
Adder
7.877
274723RIVER EC ;12
Adder
22.533
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0.882
274751CRETE EC ;1U
Adder
6.135
274754CRETE EC ;4U
Adder
6.135
270505AE1-170 C O1
Solar/Wind Harmer
18.802
274812UNIV PK N;8U
Adder
6.272
276776AD2-060 GEN
Solar/Wind Harmer
0.528
274801UNIV PARK;4U
Adder
7.284
945111AF1-176 GEN
Solar/Wind Harmer
22.288
270063AE2-323 C
Solar/Wind Harmer
2.75
941551AE2-152 GEN
Solar/Wind Harmer
5.657
970373AG2-245 GEN
Solar/Wind Harmer
26.192
274676JOLIET 29;8U
Adder
38.177
274674JOLIET 9 ;6U
Adder
19.142
274732ELWOOD EC;7P
Adder
20.425
274871GR RIDGE ;2U
Solar/Wind Harmer
9.551
270449AD2-020 GEN
Solar/Wind Harmer
3.477
943021AE2-325 GEN
Solar/Wind Harmer
4.518
274745AC1-111 GEN9
Adder
6.919
270055AF2-134 C O1
Solar/Wind Harmer
3.738
276691AA1-018 GEN1
Solar/Wind Harmer
0.572
274682WAUKEGAN ;7U
Adder
22.07
274828WAUKEGAN ;BP
Adder
13.555
958381AF2-132 GEN
Solar/Wind Harmer
11.095
960751AF2-366 GEN
Solar/Wind Harmer
3.508
962781AG1-127 GEN
Solar/Wind Harmer
11.628
964861AG1-349 GEN
Solar/Wind Harmer
9.604
971917AH1-482 GEN
Solar/Wind Harmer
11.083
939401AE1-172 GEN
Solar/Wind Harmer
17.025
274872LEEDK;1U
Solar/Wind Harmer
10.03
276901AD2-066 C O1
Solar/Wind Harmer
4.283
965011AG1-365 GEN
Solar/Wind Harmer
12.175
971997AH1-543 GEN
Solar/Wind Harmer
19.145
276861AD2-134 GEN
Solar/Wind Harmer
2.169
274822ROCKFORD ;11
Adder
23.693
972235AH1-702 GEN1
Adder
3.039
274761LEE CO EC;2U
Adder
11.12
274766LEE CO EC;7U
Adder
10.989
970091AG2-072 GEN
Adder
5.216
957471AF2-041 GEN
Solar/Wind Harmer
1.161
959081AF2-199 GEN
Solar/Wind Harmer
0.387
971067AG2-660 GEN
Solar/Wind Harmer
0.09
270102X2-052 ST
50/50
2.048
270100X2-052 CT1
50/50
1.887
270101X2-052 CT2
50/50
1.887
970321AG2-212 GEN
Solar/Wind Harmer
23.936
965681AG1-436 GEN
Solar/Wind Harmer
15.956
965791AG1-447 GEN
Solar/Wind Harmer
8.164
274770LINCOLN ;1U
Adder
7.877
274771LINCOLN ;2U
Adder
7.877
270526AF1-158 GEN
Solar/Wind Harmer
5.766
24441505OLIV SLR
Solar/Wind Harmer
0.17
270216AD2-079_GEN
Solar/Wind Harmer
0.767
957891AF2-083 GEN
Solar/Wind Harmer
4.225
960981AF2-389 GEN
Solar/Wind Harmer
1.893
274808UNIV PK N;4U
Adder
6.245
972259AH1-714 GEN
Adder
23.874
274803UNIV PARK;6U
Adder
7.287
274888KELLY CRK;1U
Solar/Wind Harmer
7.379
274887GEN-1.85
Solar/Wind Harmer
6.662
276843GEN-1.7
Solar/Wind Harmer
0.717
958011AF2-095 GEN
Solar/Wind Harmer
17.998
247620Y3-023
Adder
0.575
961051AF2-396 GEN
Solar/Wind Harmer
19.743
961051AF2-396 GEN
Solar/Wind Harmer
9.183
274674JOLIET 9 ;6U
Adder
19.142
274847GR RIDGE ;BU
Solar/Wind Harmer
6.282
971573AH1-285 GEN
Solar/Wind Harmer
10.624
274695ROCKY RD ;2P
Adder
13.688
274693ROCKY RD ;1P
Adder
13.554
274697ROCKY RD ;3P
Adder
3.718
274696ROCKY RD ;4P
Adder
14.011
958481AF2-142 GEN
Solar/Wind Harmer
18.422
274861TOP CROP ;1U
Solar/Wind Harmer
7.44
274862TOP CROP ;2U
Solar/Wind Harmer
6.212
274683WAUKEGAN ;8U
Adder
25.859
274683WAUKEGAN ;8U
Adder
21.798
962691AG1-118 GEN
Solar/Wind Harmer
36.735
970921AG2-575 GEN
Solar/Wind Harmer
12.227
970921AG2-575 GEN
Solar/Wind Harmer
2.844
958491AF2-143 GEN
Solar/Wind Harmer
18.296
970611AG2-400 GEN
Solar/Wind Harmer
12.175
942991AE2-321 GEN
Solar/Wind Harmer
12.173
274879MINONK ;1U
Solar/Wind Harmer
8.21
971333AH1-146 GEN
Solar/Wind Harmer
24.274
971335AH1-147 GEN
Solar/Wind Harmer
24.274
274764LEE CO EC;5U
Adder
11.146
274765LEE CO EC;6U
Adder
11.146
274762LEE CO EC;3U
Adder
11.12
274763LEE CO EC;4U
Adder
11.015
972267AH1-718 GEN
Adder
4.949
971341AH1-150 GEN
Solar/Wind Harmer
0.774
971343AH1-151 GEN
Solar/Wind Harmer
0.774
24721605FLATG1
50/50
1.786
971599AH1-298 GEN
50/50
12.095
962771AG1-126 GEN
Solar/Wind Harmer
95.557
971347AH1-153 GEN
Solar/Wind Harmer
20.011
270071AF1-092 GEN
Solar/Wind Harmer
19.32
960681AF2-359 GEN
Solar/Wind Harmer
4.823
971771AH1-392 GEN
Solar/Wind Harmer
11.437
274775LINCOLN ;6U
Adder
7.877
274776LINCOLN ;7U
Adder
7.877
274777LINCOLN ;8U
Adder
7.877
971769AH1-391 GEN
Solar/Wind Harmer
12.687
274814UNIV PK N;0U
Adder
6.327
274807UNIV PK N;3U
Adder
6.313
274805UNIV PK N;1U
Adder
6.286
274811UNIV PK N;7U
Adder
6.272
274827FISK ;RP
Adder
9.699
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
12.498
972227AH1-698 GEN1
Adder
3.26
274687WILL CNTY;4U
Adder
34.788
274687WILL CNTY;4U
Adder
34.788
274675JOLIET 29;7U
Adder
38.178
274675JOLIET 29;7U
Adder
36.814
274731ELWOOD EC;2P
Adder
20.424
274733ELWOOD EC;3P
Adder
20.424
274735ELWOOD EC;4P
Adder
20.424
274728ELWOOD EC;5P
Adder
20.425
970833AG2-524 GEN
Solar/Wind Harmer
10.846
970833AG2-524 GEN
Solar/Wind Harmer
5.045
274746AC1-111 G10
Adder
6.919
274744AC1-111 GEN8
Adder
6.919
24729505KEY G4
Adder
8.014
270536AF1-215 GEN2
Solar/Wind Harmer
5.608
944161AF1-084 GEN
Solar/Wind Harmer
2.725
958391AF2-133 GEN
Solar/Wind Harmer
11.042
971177AH1-047 GEN
Solar/Wind Harmer
7.132
276868AE1-113 GEN
Solar/Wind Harmer
12.314
276882AE2-255 GEN
Solar/Wind Harmer
4.105
971675AH1-338 GEN
Solar/Wind Harmer
21.857
971411AH1-196 GEN
Solar/Wind Harmer
18.212
274863CRW1-WTG
Solar/Wind Harmer
6.762
274864CRW2-WTG
Solar/Wind Harmer
6.762
274823ROCKFORD ;21
Adder
23.521
270054AF2-122 C O1
Solar/Wind Helper
1.549
971171AH1-044 GEN
Solar/Wind Harmer
0.774
944201AF1-088_MTX
Adder
117.628
957141AF2-008_MTX
Adder
58.814
CBM West 1LTFEXP_CBM-W1->PJM
CBM
145.765
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.894
MECLTFEXP_MEC->PJM
CLTF
18.376
SIGELTFEXP_SIGE->PJM
CLTF
0.47
LAGNLTFEXP_LAGN->PJM
CLTF
16.151
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.809
TVALTFEXP_TVA->PJM
CLTF
7.633
CPLELTFEXP_CPLE->PJM
CLTF
3.161
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.296
NYPJM->LTFIMP_NY
CLTF
3.802
LGEELTFEXP_LGEE->PJM
CLTF
5.477
WECLTFEXP_WEC->PJM
CLTF
4.602
AG2-052LTFEXP_AG2-052->PJM
LTF
0.284
AH1-155LTFEXP_AH1-155->PJM
LTF
0.425

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.15 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6040.67
MW Contribution:37.45
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.061
270100X2-052 CT1
50/50
1.899
270101X2-052 CT2
50/50
1.899
970321AG2-212 GEN
Solar/Wind Harmer
24.08
965681AG1-436 GEN
Solar/Wind Harmer
16.057
965791AG1-447 GEN
Solar/Wind Harmer
8.215
274770LINCOLN ;1U
Adder
7.927
274771LINCOLN ;2U
Adder
7.927
270526AF1-158 GEN
Solar/Wind Harmer
5.803
24441505OLIV SLR
Solar/Wind Harmer
0.171
270216AD2-079_GEN
Solar/Wind Harmer
0.772
957891AF2-083 GEN
Solar/Wind Harmer
4.252
274808UNIV PK N;4U
Adder
6.285
960981AF2-389 GEN
Solar/Wind Harmer
1.905
972259AH1-714 GEN
Adder
24.028
274803UNIV PARK;6U
Adder
7.334
274888KELLY CRK;1U
Solar/Wind Harmer
7.426
274887GEN-1.85
Solar/Wind Harmer
6.705
276843GEN-1.7
Solar/Wind Harmer
0.721
958011AF2-095 GEN
Solar/Wind Harmer
18.114
247620Y3-023
Adder
0.579
961051AF2-396 GEN
Solar/Wind Harmer
19.871
961051AF2-396 GEN
Solar/Wind Harmer
9.242
274674JOLIET 9 ;6U
Adder
19.265
274847GR RIDGE ;BU
Solar/Wind Harmer
6.323
971573AH1-285 GEN
Solar/Wind Harmer
10.693
274696ROCKY RD ;4P
Adder
14.103
274695ROCKY RD ;2P
Adder
13.778
274693ROCKY RD ;1P
Adder
13.642
274697ROCKY RD ;3P
Adder
3.743
958481AF2-142 GEN
Solar/Wind Harmer
18.542
274861TOP CROP ;1U
Solar/Wind Harmer
7.488
274862TOP CROP ;2U
Solar/Wind Harmer
6.253
274683WAUKEGAN ;8U
Adder
26.028
274683WAUKEGAN ;8U
Adder
21.94
962691AG1-118 GEN
Solar/Wind Harmer
36.976
970921AG2-575 GEN
Solar/Wind Harmer
12.308
970921AG2-575 GEN
Solar/Wind Harmer
2.862
958491AF2-143 GEN
Solar/Wind Harmer
18.417
970611AG2-400 GEN
Solar/Wind Harmer
12.256
942991AE2-321 GEN
Solar/Wind Harmer
12.253
274879MINONK ;1U
Solar/Wind Harmer
8.265
971333AH1-146 GEN
Solar/Wind Harmer
24.435
971335AH1-147 GEN
Solar/Wind Harmer
24.435
274764LEE CO EC;5U
Adder
11.221
274765LEE CO EC;6U
Adder
11.221
274762LEE CO EC;3U
Adder
11.195
274763LEE CO EC;4U
Adder
11.089
972267AH1-718 GEN
Adder
4.982
971341AH1-150 GEN
Solar/Wind Harmer
0.779
971343AH1-151 GEN
Solar/Wind Harmer
0.779
24721605FLATG1
50/50
1.796
971599AH1-298 GEN
50/50
12.165
962771AG1-126 GEN
Solar/Wind Harmer
95.82
971347AH1-153 GEN
Solar/Wind Harmer
20.131
24722005FLATG5
50/50
1.796
24721905FLATG4
50/50
32.926
970153AG2-106 GEN
Solar/Wind Harmer
41.782
970513AG2-328 GEN
Solar/Wind Harmer
24.08
970517AG2-330 GEN
Solar/Wind Harmer
21.84
970349AG2-230 GEN
Solar/Wind Harmer
20.131
270043AE2-236 GEN
Solar/Wind Harmer
7.197
274772LINCOLN ;3U
Adder
7.927
247643Z2-116 C
Solar/Wind Harmer
0.089
24642205MAYFLWER
Adder
0.805
274724RIVER EC ;11
Adder
22.416
970707AG2-453 GEN
Solar/Wind Harmer
35.371
972231SS25-0005
Solar/Wind Harmer
11.989
972181SS23-001
Solar/Wind Harmer
7.493
274752CRETE EC ;2U
Adder
6.174
274753CRETE EC ;3U
Adder
6.174
944531AF1-118 GEN
Solar/Wind Harmer
44.166
274826FISK ;BP
Adder
13.773
274802UNIV PARK;5U
Adder
7.334
276772AC2-154 GEN
Solar/Wind Harmer
3.508
276806AD2-047 C O1
Solar/Wind Harmer
13.456
970941AG2-585 GEN
Solar/Wind Harmer
15.724
972228AH1-698 GEN2
Adder
4.659
274800UNIV PARK;3U
Adder
7.331
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.109
276897AD1-100 C
Solar/Wind Harmer
36.429
939351AE1-166 GEN
Solar/Wind Harmer
7.443
274676JOLIET 29;8U
Adder
37.052
274729ELWOOD EC;1P
Adder
20.557
274730ELWOOD EC;6P
Adder
20.557
274734ELWOOD EC;8P
Adder
20.557
274736ELWOOD EC;9P
Adder
20.557
276893AG1-478 C
Solar/Wind Harmer
0.522
970031AG2-029 GEN
Solar/Wind Harmer
37.453
943121AE2-341 GEN
Solar/Wind Harmer
18.714
943591AF1-030 GEN
Solar/Wind Harmer
12.476
270535AF1-215 GEN1
Solar/Wind Harmer
5.645
276694AA1-018 GEN2
Solar/Wind Harmer
7.801
274682WAUKEGAN ;7U
Adder
22.214
964401AG1-302 GEN
Solar/Wind Harmer
11.168
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
6.299
959331AF2-224 GEN
Solar/Wind Harmer
12.256
965021AG1-366 GEN
Solar/Wind Harmer
2.85
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276799AD1-013 GEN
Solar/Wind Harmer
2.703
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
4.514
274850MENDOTA H;RU
Solar/Wind Harmer
3.139
276602WESTBROOK C
Solar/Wind Harmer
2.598
276863AD2-134 GEN
Solar/Wind Harmer
2.183
959141AF2-205 GEN
Solar/Wind Harmer
7.381
972236AH1-702 GEN2
Adder
2.66
247604X1-042
Adder
0.505
274760LEE CO EC;1U
Adder
11.195
274767LEE CO EC;8U
Adder
11.063
959091AF2-200 GEN
Solar/Wind Harmer
0.779
24721805FLATG3
50/50
1.796
24721705FLATG2
50/50
32.926
24344105CKG2
50/50
10.407
962761AG1-125 GEN
Solar/Wind Harmer
95.82
970149AG2-104 GEN
Solar/Wind Harmer
118.338
970155AG2-107 GEN
Solar/Wind Harmer
41.782
970245AG2-165 GEN
Solar/Wind Harmer
24.08
972207SS24-0001
Solar/Wind Harmer
28.182
274773LINCOLN ;4U
Adder
7.927
274774LINCOLN ;5U
Adder
7.927
274723RIVER EC ;12
Adder
22.677
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0.888
274751CRETE EC ;1U
Adder
6.174
274754CRETE EC ;4U
Adder
6.174
270505AE1-170 C O1
Solar/Wind Harmer
18.922
274812UNIV PK N;8U
Adder
6.313
276776AD2-060 GEN
Solar/Wind Harmer
0.532
274801UNIV PARK;4U
Adder
7.331
945111AF1-176 GEN
Solar/Wind Harmer
22.432
270063AE2-323 C
Solar/Wind Harmer
2.768
941551AE2-152 GEN
Solar/Wind Harmer
5.693
970373AG2-245 GEN
Solar/Wind Harmer
26.361
274676JOLIET 29;8U
Adder
38.424
274674JOLIET 9 ;6U
Adder
19.265
274732ELWOOD EC;7P
Adder
20.557
274871GR RIDGE ;2U
Solar/Wind Harmer
9.612
270449AD2-020 GEN
Solar/Wind Harmer
3.5
943021AE2-325 GEN
Solar/Wind Harmer
4.548
274745AC1-111 GEN9
Adder
6.964
270055AF2-134 C O1
Solar/Wind Harmer
3.763
276691AA1-018 GEN1
Solar/Wind Harmer
0.576
274682WAUKEGAN ;7U
Adder
22.214
274828WAUKEGAN ;BP
Adder
13.643
958381AF2-132 GEN
Solar/Wind Harmer
11.168
960751AF2-366 GEN
Solar/Wind Harmer
3.531
962781AG1-127 GEN
Solar/Wind Harmer
11.704
964861AG1-349 GEN
Solar/Wind Harmer
9.667
971917AH1-482 GEN
Solar/Wind Harmer
11.156
939401AE1-172 GEN
Solar/Wind Harmer
17.137
274872LEEDK;1U
Solar/Wind Harmer
10.096
276901AD2-066 C O1
Solar/Wind Harmer
4.312
965011AG1-365 GEN
Solar/Wind Harmer
12.256
971997AH1-543 GEN
Solar/Wind Harmer
19.271
276861AD2-134 GEN
Solar/Wind Harmer
2.183
274822ROCKFORD ;11
Adder
23.85
972235AH1-702 GEN1
Adder
3.059
274761LEE CO EC;2U
Adder
11.195
274766LEE CO EC;7U
Adder
11.063
970091AG2-072 GEN
Adder
5.259
957471AF2-041 GEN
Solar/Wind Harmer
1.169
959081AF2-199 GEN
Solar/Wind Harmer
0.39
971067AG2-660 GEN
Solar/Wind Harmer
0.091
270071AF1-092 GEN
Solar/Wind Harmer
19.441
960681AF2-359 GEN
Solar/Wind Harmer
4.853
971771AH1-392 GEN
Solar/Wind Harmer
11.51
274775LINCOLN ;6U
Adder
7.927
274776LINCOLN ;7U
Adder
7.927
274777LINCOLN ;8U
Adder
7.927
971769AH1-391 GEN
Solar/Wind Harmer
12.768
274814UNIV PK N;0U
Adder
6.368
274807UNIV PK N;3U
Adder
6.354
274805UNIV PK N;1U
Adder
6.326
274811UNIV PK N;7U
Adder
6.313
274827FISK ;RP
Adder
9.761
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.579
972227AH1-698 GEN1
Adder
3.281
274687WILL CNTY;4U
Adder
35.013
274687WILL CNTY;4U
Adder
35.013
274675JOLIET 29;7U
Adder
38.424
274675JOLIET 29;7U
Adder
37.052
274731ELWOOD EC;2P
Adder
20.557
274733ELWOOD EC;3P
Adder
20.557
274735ELWOOD EC;4P
Adder
20.557
274728ELWOOD EC;5P
Adder
20.557
970833AG2-524 GEN
Solar/Wind Harmer
10.916
970833AG2-524 GEN
Solar/Wind Harmer
5.077
274746AC1-111 G10
Adder
6.964
274744AC1-111 GEN8
Adder
6.964
24729505KEY G4
Adder
8.066
270536AF1-215 GEN2
Solar/Wind Harmer
5.645
944161AF1-084 GEN
Solar/Wind Harmer
2.743
958391AF2-133 GEN
Solar/Wind Harmer
11.115
971177AH1-047 GEN
Solar/Wind Harmer
7.179
276868AE1-113 GEN
Solar/Wind Harmer
12.396
276882AE2-255 GEN
Solar/Wind Harmer
4.132
971675AH1-338 GEN
Solar/Wind Harmer
22.002
971411AH1-196 GEN
Solar/Wind Harmer
18.333
274863CRW1-WTG
Solar/Wind Harmer
6.807
274864CRW2-WTG
Solar/Wind Harmer
6.807
274823ROCKFORD ;21
Adder
23.677
270054AF2-122 C O1
Solar/Wind Helper
1.538
971171AH1-044 GEN
Solar/Wind Harmer
0.779
944201AF1-088_MTX
Adder
118.565
957141AF2-008_MTX
Adder
59.283
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.937
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.195
MECLTFEXP_MEC->PJM
CLTF
18.51
SIGELTFEXP_SIGE->PJM
CLTF
0.474
LAGNLTFEXP_LAGN->PJM
CLTF
16.31
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.037
TVALTFEXP_TVA->PJM
CLTF
7.713
CPLELTFEXP_CPLE->PJM
CLTF
3.242
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.367
NYPJM->LTFIMP_NY
CLTF
3.759
LGEELTFEXP_LGEE->PJM
CLTF
5.533
WECLTFEXP_WEC->PJM
CLTF
4.633
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.12 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6039.4
MW Contribution:37.43
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.911
970153AG2-106 GEN
Solar/Wind Harmer
41.773
970513AG2-328 GEN
Solar/Wind Harmer
24.069
970517AG2-330 GEN
Solar/Wind Harmer
21.83
970349AG2-230 GEN
Solar/Wind Harmer
20.122
270043AE2-236 GEN
Solar/Wind Harmer
7.194
274772LINCOLN ;3U
Adder
7.923
247643Z2-116 C
Solar/Wind Harmer
0.089
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.405
970707AG2-453 GEN
Solar/Wind Harmer
35.353
972231SS25-0005
Solar/Wind Harmer
11.983
972181SS23-001
Solar/Wind Harmer
7.489
274752CRETE EC ;2U
Adder
6.171
274753CRETE EC ;3U
Adder
6.171
944531AF1-118 GEN
Solar/Wind Harmer
44.143
274826FISK ;BP
Adder
13.766
274802UNIV PARK;5U
Adder
7.33
276772AC2-154 GEN
Solar/Wind Harmer
3.506
276806AD2-047 C O1
Solar/Wind Harmer
13.45
970941AG2-585 GEN
Solar/Wind Harmer
15.716
972228AH1-698 GEN2
Adder
4.657
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.911
24344105CKG2
50/50
10.402
962761AG1-125 GEN
Solar/Wind Harmer
95.798
970149AG2-104 GEN
Solar/Wind Harmer
118.311
970155AG2-107 GEN
Solar/Wind Harmer
41.773
970245AG2-165 GEN
Solar/Wind Harmer
24.069
972207SS24-0001
Solar/Wind Harmer
28.169
274773LINCOLN ;4U
Adder
7.923
274774LINCOLN ;5U
Adder
7.923
274723RIVER EC ;12
Adder
22.666
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0.887
274751CRETE EC ;1U
Adder
6.171
274754CRETE EC ;4U
Adder
6.171
270505AE1-170 C O1
Solar/Wind Harmer
18.913
274812UNIV PK N;8U
Adder
6.309
276776AD2-060 GEN
Solar/Wind Harmer
0.532
274801UNIV PARK;4U
Adder
7.327
945111AF1-176 GEN
Solar/Wind Harmer
22.421
270063AE2-323 C
Solar/Wind Harmer
2.766
941551AE2-152 GEN
Solar/Wind Harmer
5.69
970373AG2-245 GEN
Solar/Wind Harmer
26.348
274676JOLIET 29;8U
Adder
38.405
274674JOLIET 9 ;6U
Adder
19.256
274732ELWOOD EC;7P
Adder
20.547
274871GR RIDGE ;2U
Solar/Wind Harmer
9.608
270449AD2-020 GEN
Solar/Wind Harmer
3.498
943021AE2-325 GEN
Solar/Wind Harmer
4.545
274745AC1-111 GEN9
Adder
6.961
270055AF2-134 C O1
Solar/Wind Harmer
3.761
276691AA1-018 GEN1
Solar/Wind Harmer
0.575
274682WAUKEGAN ;7U
Adder
22.204
274828WAUKEGAN ;BP
Adder
13.637
958381AF2-132 GEN
Solar/Wind Harmer
11.162
960751AF2-366 GEN
Solar/Wind Harmer
3.529
962781AG1-127 GEN
Solar/Wind Harmer
11.699
964861AG1-349 GEN
Solar/Wind Harmer
9.662
971917AH1-482 GEN
Solar/Wind Harmer
11.15
939401AE1-172 GEN
Solar/Wind Harmer
17.129
274872LEEDK;1U
Solar/Wind Harmer
10.091
276901AD2-066 C O1
Solar/Wind Harmer
4.309
965011AG1-365 GEN
Solar/Wind Harmer
12.25
971997AH1-543 GEN
Solar/Wind Harmer
19.262
276861AD2-134 GEN
Solar/Wind Harmer
2.182
274822ROCKFORD ;11
Adder
23.838
972235AH1-702 GEN1
Adder
3.057
274761LEE CO EC;2U
Adder
11.189
274766LEE CO EC;7U
Adder
11.057
970091AG2-072 GEN
Adder
5.255
957471AF2-041 GEN
Solar/Wind Harmer
1.168
959081AF2-199 GEN
Solar/Wind Harmer
0.389
971067AG2-660 GEN
Solar/Wind Harmer
0.091
274800UNIV PARK;3U
Adder
7.327
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.106
276897AD1-100 C
Solar/Wind Harmer
36.411
939351AE1-166 GEN
Solar/Wind Harmer
7.44
274676JOLIET 29;8U
Adder
37.034
274729ELWOOD EC;1P
Adder
20.547
274730ELWOOD EC;6P
Adder
20.547
274734ELWOOD EC;8P
Adder
20.547
274736ELWOOD EC;9P
Adder
20.547
276893AG1-478 C
Solar/Wind Harmer
0.522
970031AG2-029 GEN
Solar/Wind Harmer
37.434
943121AE2-341 GEN
Solar/Wind Harmer
18.704
943591AF1-030 GEN
Solar/Wind Harmer
12.47
270535AF1-215 GEN1
Solar/Wind Harmer
5.642
276694AA1-018 GEN2
Solar/Wind Harmer
7.797
274682WAUKEGAN ;7U
Adder
22.204
964401AG1-302 GEN
Solar/Wind Harmer
11.162
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
6.295
959331AF2-224 GEN
Solar/Wind Harmer
12.25
965021AG1-366 GEN
Solar/Wind Harmer
2.849
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276799AD1-013 GEN
Solar/Wind Harmer
2.702
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
4.512
274850MENDOTA H;RU
Solar/Wind Harmer
3.137
276602WESTBROOK C
Solar/Wind Harmer
2.597
276863AD2-134 GEN
Solar/Wind Harmer
2.182
959141AF2-205 GEN
Solar/Wind Harmer
7.377
972236AH1-702 GEN2
Adder
2.659
247604X1-042
Adder
0.505
274760LEE CO EC;1U
Adder
11.189
274767LEE CO EC;8U
Adder
11.057
959091AF2-200 GEN
Solar/Wind Harmer
0.779
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
24.069
965681AG1-436 GEN
Solar/Wind Harmer
16.049
965791AG1-447 GEN
Solar/Wind Harmer
8.211
274770LINCOLN ;1U
Adder
7.923
274771LINCOLN ;2U
Adder
7.923
270526AF1-158 GEN
Solar/Wind Harmer
5.8
24441505OLIV SLR
Solar/Wind Harmer
0.171
270216AD2-079_GEN
Solar/Wind Harmer
0.772
957891AF2-083 GEN
Solar/Wind Harmer
4.25
274808UNIV PK N;4U
Adder
6.282
960981AF2-389 GEN
Solar/Wind Harmer
1.904
972259AH1-714 GEN
Adder
24.016
274803UNIV PARK;6U
Adder
7.33
274888KELLY CRK;1U
Solar/Wind Harmer
7.423
274887GEN-1.85
Solar/Wind Harmer
6.702
276843GEN-1.7
Solar/Wind Harmer
0.721
958011AF2-095 GEN
Solar/Wind Harmer
18.105
247620Y3-023
Adder
0.579
961051AF2-396 GEN
Solar/Wind Harmer
19.861
961051AF2-396 GEN
Solar/Wind Harmer
9.238
274674JOLIET 9 ;6U
Adder
19.256
274847GR RIDGE ;BU
Solar/Wind Harmer
6.32
971573AH1-285 GEN
Solar/Wind Harmer
10.688
274696ROCKY RD ;4P
Adder
14.096
274695ROCKY RD ;2P
Adder
13.771
274693ROCKY RD ;1P
Adder
13.635
274697ROCKY RD ;3P
Adder
3.741
958481AF2-142 GEN
Solar/Wind Harmer
18.533
274861TOP CROP ;1U
Solar/Wind Harmer
7.485
274862TOP CROP ;2U
Solar/Wind Harmer
6.25
274683WAUKEGAN ;8U
Adder
26.015
274683WAUKEGAN ;8U
Adder
21.929
962691AG1-118 GEN
Solar/Wind Harmer
36.958
970921AG2-575 GEN
Solar/Wind Harmer
12.301
970921AG2-575 GEN
Solar/Wind Harmer
2.861
958491AF2-143 GEN
Solar/Wind Harmer
18.408
970611AG2-400 GEN
Solar/Wind Harmer
12.25
942991AE2-321 GEN
Solar/Wind Harmer
12.247
274879MINONK ;1U
Solar/Wind Harmer
8.261
971333AH1-146 GEN
Solar/Wind Harmer
24.423
971335AH1-147 GEN
Solar/Wind Harmer
24.423
274764LEE CO EC;5U
Adder
11.215
274765LEE CO EC;6U
Adder
11.215
274762LEE CO EC;3U
Adder
11.189
274763LEE CO EC;4U
Adder
11.084
972267AH1-718 GEN
Adder
4.98
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.16
962771AG1-126 GEN
Solar/Wind Harmer
95.798
971347AH1-153 GEN
Solar/Wind Harmer
20.122
270071AF1-092 GEN
Solar/Wind Harmer
19.432
960681AF2-359 GEN
Solar/Wind Harmer
4.851
971771AH1-392 GEN
Solar/Wind Harmer
11.504
274775LINCOLN ;6U
Adder
7.923
274776LINCOLN ;7U
Adder
7.923
274777LINCOLN ;8U
Adder
7.923
971769AH1-391 GEN
Solar/Wind Harmer
12.761
274814UNIV PK N;0U
Adder
6.365
274807UNIV PK N;3U
Adder
6.351
274805UNIV PK N;1U
Adder
6.323
274811UNIV PK N;7U
Adder
6.309
274827FISK ;RP
Adder
9.756
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.573
972227AH1-698 GEN1
Adder
3.279
274687WILL CNTY;4U
Adder
34.996
274687WILL CNTY;4U
Adder
34.996
274675JOLIET 29;7U
Adder
38.406
274675JOLIET 29;7U
Adder
37.034
274731ELWOOD EC;2P
Adder
20.547
274733ELWOOD EC;3P
Adder
20.547
274735ELWOOD EC;4P
Adder
20.547
274728ELWOOD EC;5P
Adder
20.547
970833AG2-524 GEN
Solar/Wind Harmer
10.911
970833AG2-524 GEN
Solar/Wind Harmer
5.075
274746AC1-111 G10
Adder
6.961
274744AC1-111 GEN8
Adder
6.961
24729505KEY G4
Adder
8.062
270536AF1-215 GEN2
Solar/Wind Harmer
5.642
944161AF1-084 GEN
Solar/Wind Harmer
2.742
958391AF2-133 GEN
Solar/Wind Harmer
11.109
971177AH1-047 GEN
Solar/Wind Harmer
7.175
276868AE1-113 GEN
Solar/Wind Harmer
12.39
276882AE2-255 GEN
Solar/Wind Harmer
4.13
971675AH1-338 GEN
Solar/Wind Harmer
21.991
971411AH1-196 GEN
Solar/Wind Harmer
18.324
274863CRW1-WTG
Solar/Wind Harmer
6.804
274864CRW2-WTG
Solar/Wind Harmer
6.804
274823ROCKFORD ;21
Adder
23.666
270054AF2-122 C O1
Solar/Wind Helper
1.539
971171AH1-044 GEN
Solar/Wind Harmer
0.779
971341AH1-150 GEN
Solar/Wind Harmer
0.779
971343AH1-151 GEN
Solar/Wind Harmer
0.779
944201AF1-088_MTX
Adder
118.492
957141AF2-008_MTX
Adder
59.246
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.176
MECLTFEXP_MEC->PJM
CLTF
18.5
SIGELTFEXP_SIGE->PJM
CLTF
0.474
LAGNLTFEXP_LAGN->PJM
CLTF
16.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.03
TVALTFEXP_TVA->PJM
CLTF
7.708
CPLELTFEXP_CPLE->PJM
CLTF
3.241
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.295
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.528
WECLTFEXP_WEC->PJM
CLTF
4.631
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.11 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6038.85
MW Contribution:37.43
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
95.789
970149AG2-104 GEN
Solar/Wind Harmer
118.299
970155AG2-107 GEN
Solar/Wind Harmer
41.768
970245AG2-165 GEN
Solar/Wind Harmer
24.064
972207SS24-0001
Solar/Wind Harmer
28.163
274773LINCOLN ;4U
Adder
7.921
274774LINCOLN ;5U
Adder
7.921
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0.887
274751CRETE EC ;1U
Adder
6.17
274754CRETE EC ;4U
Adder
6.17
270505AE1-170 C O1
Solar/Wind Harmer
18.909
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.531
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
22.416
270063AE2-323 C
Solar/Wind Harmer
2.766
941551AE2-152 GEN
Solar/Wind Harmer
5.689
970373AG2-245 GEN
Solar/Wind Harmer
26.342
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
9.606
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
95.789
971347AH1-153 GEN
Solar/Wind Harmer
20.118
270071AF1-092 GEN
Solar/Wind Harmer
19.428
960681AF2-359 GEN
Solar/Wind Harmer
4.85
971771AH1-392 GEN
Solar/Wind Harmer
11.502
274775LINCOLN ;6U
Adder
7.921
274776LINCOLN ;7U
Adder
7.921
274777LINCOLN ;8U
Adder
7.921
971769AH1-391 GEN
Solar/Wind Harmer
12.759
274814UNIV PK N;0U
Adder
6.363
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.57
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
10.908
970833AG2-524 GEN
Solar/Wind Harmer
5.074
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
5.641
944161AF1-084 GEN
Solar/Wind Harmer
2.741
958391AF2-133 GEN
Solar/Wind Harmer
11.107
971177AH1-047 GEN
Solar/Wind Harmer
7.174
276868AE1-113 GEN
Solar/Wind Harmer
12.387
276882AE2-255 GEN
Solar/Wind Harmer
4.129
971675AH1-338 GEN
Solar/Wind Harmer
21.986
971411AH1-196 GEN
Solar/Wind Harmer
18.32
274863CRW1-WTG
Solar/Wind Harmer
6.802
274864CRW2-WTG
Solar/Wind Harmer
6.802
274823ROCKFORD ;21
Adder
23.66
270054AF2-122 C O1
Solar/Wind Helper
1.539
971171AH1-044 GEN
Solar/Wind Harmer
0.778
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
41.768
970513AG2-328 GEN
Solar/Wind Harmer
24.064
970517AG2-330 GEN
Solar/Wind Harmer
21.825
970349AG2-230 GEN
Solar/Wind Harmer
20.118
270043AE2-236 GEN
Solar/Wind Harmer
7.192
274772LINCOLN ;3U
Adder
7.921
247643Z2-116 C
Solar/Wind Harmer
0.089
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
35.346
972231SS25-0005
Solar/Wind Harmer
11.98
972181SS23-001
Solar/Wind Harmer
7.488
274752CRETE EC ;2U
Adder
6.17
274753CRETE EC ;3U
Adder
6.17
944531AF1-118 GEN
Solar/Wind Harmer
44.133
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276772AC2-154 GEN
Solar/Wind Harmer
3.505
276806AD2-047 C O1
Solar/Wind Harmer
13.447
970941AG2-585 GEN
Solar/Wind Harmer
15.712
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
36.403
939351AE1-166 GEN
Solar/Wind Harmer
7.438
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.522
970031AG2-029 GEN
Solar/Wind Harmer
37.426
943121AE2-341 GEN
Solar/Wind Harmer
18.7
943591AF1-030 GEN
Solar/Wind Harmer
12.467
270535AF1-215 GEN1
Solar/Wind Harmer
5.641
276694AA1-018 GEN2
Solar/Wind Harmer
7.795
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
11.16
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
6.294
959331AF2-224 GEN
Solar/Wind Harmer
12.247
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276799AD1-013 GEN
Solar/Wind Harmer
2.701
946671AF1-331 GEN
Solar/Wind Harmer
0.511
274855GSG-6 ;RU
Solar/Wind Harmer
4.511
274850MENDOTA H;RU
Solar/Wind Harmer
3.137
276602WESTBROOK C
Solar/Wind Harmer
2.596
276863AD2-134 GEN
Solar/Wind Harmer
2.181
959141AF2-205 GEN
Solar/Wind Harmer
7.375
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
959091AF2-200 GEN
Solar/Wind Harmer
0.778
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
24.064
965681AG1-436 GEN
Solar/Wind Harmer
16.046
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
7.921
274771LINCOLN ;2U
Adder
7.921
270526AF1-158 GEN
Solar/Wind Harmer
5.799
24441505OLIV SLR
Solar/Wind Harmer
0.171
270216AD2-079_GEN
Solar/Wind Harmer
0.772
957891AF2-083 GEN
Solar/Wind Harmer
4.249
960981AF2-389 GEN
Solar/Wind Harmer
1.904
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
7.421
274887GEN-1.85
Solar/Wind Harmer
6.7
276843GEN-1.7
Solar/Wind Harmer
0.721
958011AF2-095 GEN
Solar/Wind Harmer
18.101
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
19.857
961051AF2-396 GEN
Solar/Wind Harmer
9.236
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
6.319
971573AH1-285 GEN
Solar/Wind Harmer
10.686
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
18.529
274861TOP CROP ;1U
Solar/Wind Harmer
7.483
274862TOP CROP ;2U
Solar/Wind Harmer
6.248
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
36.95
970921AG2-575 GEN
Solar/Wind Harmer
12.299
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
18.404
970611AG2-400 GEN
Solar/Wind Harmer
12.247
942991AE2-321 GEN
Solar/Wind Harmer
12.245
274879MINONK ;1U
Solar/Wind Harmer
8.259
971333AH1-146 GEN
Solar/Wind Harmer
24.417
971335AH1-147 GEN
Solar/Wind Harmer
24.417
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
972267AH1-718 GEN
Adder
4.979
971341AH1-150 GEN
Solar/Wind Harmer
0.778
971343AH1-151 GEN
Solar/Wind Harmer
0.778
270449AD2-020 GEN
Solar/Wind Harmer
3.497
943021AE2-325 GEN
Solar/Wind Harmer
4.544
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
3.76
276691AA1-018 GEN1
Solar/Wind Harmer
0.575
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
11.16
960751AF2-366 GEN
Solar/Wind Harmer
3.529
962781AG1-127 GEN
Solar/Wind Harmer
11.696
964861AG1-349 GEN
Solar/Wind Harmer
9.66
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
17.125
274872LEEDK;1U
Solar/Wind Harmer
10.089
276901AD2-066 C O1
Solar/Wind Harmer
4.308
965011AG1-365 GEN
Solar/Wind Harmer
12.247
971997AH1-543 GEN
Solar/Wind Harmer
19.257
276861AD2-134 GEN
Solar/Wind Harmer
2.181
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
970091AG2-072 GEN
Adder
5.254
957471AF2-041 GEN
Solar/Wind Harmer
1.168
959081AF2-199 GEN
Solar/Wind Harmer
0.389
971067AG2-660 GEN
Solar/Wind Harmer
0.091
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
59.23
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706
CPLELTFEXP_CPLE->PJM
CLTF
3.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.66 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5972.54
MW Contribution:5.66
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
4.074
965681AG1-436 GEN
Solar/Wind Harmer
11.195
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
10.782
274771LINCOLN ;2U
Adder
10.782
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.515
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.284
958011AF2-095 GEN
Solar/Wind Harmer
12.628
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
17.455
961051AF2-396 GEN
Solar/Wind Harmer
11.637
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.615
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
12.927
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.166
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
25.779
970921AG2-575 GEN
Solar/Wind Harmer
8.581
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
12.84
970611AG2-400 GEN
Solar/Wind Harmer
8.544
970627AG2-408 GEN
Solar/Wind Harmer
2.563
942991AE2-321 GEN
Solar/Wind Harmer
9.539
274879MINONK ;1U
Solar/Wind Harmer
0.36
971333AH1-146 GEN
Solar/Wind Harmer
17.035
971335AH1-147 GEN
Solar/Wind Harmer
17.035
971341AH1-150 GEN
Solar/Wind Harmer
16.979
971343AH1-151 GEN
Solar/Wind Harmer
16.979
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.199
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.764
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
972267AH1-718 GEN
Adder
4.979
276741O09 GEN1
Solar/Wind Harmer
0.297
276708O09 GEN2
Solar/Wind Harmer
0.297
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.876
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.724
966841AG1-555 GEN
Solar/Wind Harmer
0.919
942221AE2-234 GEN
Solar/Wind Harmer
0.04
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.592
270599AE1-208 GEN
Solar/Wind Harmer
7.039
270031AE2-169
Solar/Wind Harmer
4.223
276916AD2-100_GEN
Solar/Wind Harmer
16.09
276911AD2-131_GEN
Solar/Wind Harmer
1.06
971613AH1-306 GEN
Solar/Wind Harmer
3.675
945391AF1-204 GEN
Solar/Wind Harmer
7.93
960441AF2-335 GEN
Solar/Wind Harmer
7.358
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
51.584
970513AG2-328 GEN
Solar/Wind Harmer
4.074
970517AG2-330 GEN
Solar/Wind Harmer
24.444
970349AG2-230 GEN
Solar/Wind Harmer
14.036
270043AE2-236 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
10.782
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
28.77
274752CRETE EC ;2U
Adder
10.401
274753CRETE EC ;3U
Adder
10.401
944531AF1-118 GEN
Solar/Wind Harmer
39.427
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276806AD2-047 C O1
Solar/Wind Harmer
4.97
970941AG2-585 GEN
Solar/Wind Harmer
10.962
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.345
970031AG2-029 GEN
Solar/Wind Harmer
5.657
943121AE2-341 GEN
Solar/Wind Harmer
14.583
943591AF1-030 GEN
Solar/Wind Harmer
9.698
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.981
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.909
274855GSG-6 ;RU
Solar/Wind Harmer
0.313
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.153
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
16.979
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
970571AG2-364 GEN
Solar/Wind Harmer
16.847
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
276157O29GEN1
Solar/Wind Harmer
1.347
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.289
942111AE2-223 GEN
Solar/Wind Harmer
2.682
965931AG1-462 GEN
Solar/Wind Harmer
20.855
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.514
959611AF2-252 GEN
Solar/Wind Harmer
2.724
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.657
276668AB2-070 GEN1
Solar/Wind Harmer
0.289
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.395
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970289AG2-191 GEN
Solar/Wind Harmer
0.855
970291AG2-192 GEN
Solar/Wind Harmer
0.777
942481AE2-261 GEN
Solar/Wind Harmer
23.013
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.049
970193AG2-126 GEN
Solar/Wind Harmer
11.195
958821AF2-173 GEN
Solar/Wind Harmer
10.43
270004AE1-209 GEN
Solar/Wind Harmer
1.614
971617AH1-308 GEN
Solar/Wind Harmer
6.153
970243AG2-164 GEN
Solar/Wind Harmer
3.851
970519AG2-331 GEN
Solar/Wind Harmer
17.115
970699AG2-449 GEN
Solar/Wind Harmer
1.646
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
80.781
970149AG2-104 GEN
Solar/Wind Harmer
87.246
970155AG2-107 GEN
Solar/Wind Harmer
51.584
970245AG2-165 GEN
Solar/Wind Harmer
4.074
274773LINCOLN ;4U
Adder
10.782
274774LINCOLN ;5U
Adder
10.782
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.401
274754CRETE EC ;4U
Adder
10.401
270505AE1-170 C O1
Solar/Wind Harmer
9.235
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.916
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
15.639
270063AE2-323 C
Solar/Wind Harmer
0.007
941551AE2-152 GEN
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
18.378
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.544
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
0.007
276691AA1-018 GEN1
Solar/Wind Harmer
1.044
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.166
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
6.413
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
8.544
971997AH1-543 GEN
Solar/Wind Harmer
4.478
276861AD2-134 GEN
Solar/Wind Harmer
0.153
957471AF2-041 GEN
Solar/Wind Harmer
25.469
959081AF2-199 GEN
Solar/Wind Harmer
8.49
971067AG2-660 GEN
Solar/Wind Harmer
2.83
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.593
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
970819AG2-516 GEN
Solar/Wind Harmer
10.134
971475AH1-234 GEN
Solar/Wind Harmer
4.092
970569AG2-363 GEN
Solar/Wind Harmer
25.271
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.438
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.552
958861AF2-177 GEN
Solar/Wind Harmer
3.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.643
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.078
963741AG1-226 GEN
Solar/Wind Harmer
18.629
276615X2-022 GEN
Solar/Wind Harmer
0.082
970291AG2-192 GEN
Solar/Wind Harmer
1.01
965911AG1-460 GEN
Solar/Wind Harmer
1.539
270032AE2-172
Solar/Wind Harmer
5.104
247521TR3_G114
Solar/Wind Harmer
0.277
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
80.781
971347AH1-153 GEN
Solar/Wind Harmer
14.036
270071AF1-092 GEN
Solar/Wind Harmer
17.319
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.916
274775LINCOLN ;6U
Adder
10.782
274776LINCOLN ;7U
Adder
10.782
274777LINCOLN ;8U
Adder
10.782
971769AH1-391 GEN
Solar/Wind Harmer
9.94
971619AH1-309 GEN
Solar/Wind Harmer
3.958
274814UNIV PK N;0U
Adder
6.363
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.77
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
9.589
970833AG2-524 GEN
Solar/Wind Harmer
6.393
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
5.267
276868AE1-113 GEN
Solar/Wind Harmer
1.713
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971675AH1-338 GEN
Solar/Wind Harmer
3.323
971411AH1-196 GEN
Solar/Wind Harmer
12.781
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
16.979
971611AH1-305 GEN
Solar/Wind Harmer
5.045
274823ROCKFORD ;21
Adder
23.66
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.432
970169AG2-114 GEN
Solar/Wind Harmer
8.423
971681AH1-341 GEN
Solar/Wind Harmer
13.539
961011AF2-392 GEN
Solar/Wind Harmer
4.902
957751AF2-069 GEN
Solar/Wind Harmer
0.275
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.664
941731AE2-173 GEN
Solar/Wind Harmer
6.876
946321AF1-296 GEN
Solar/Wind Harmer
4.594
965101AG1-375 GEN
Solar/Wind Harmer
8.195
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.463
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.716
971549AH1-272 GEN
Solar/Wind Harmer
16.349
276785W4-005 GEN1
Solar/Wind Harmer
0.001
270246TR4_N_V150
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
2.021
276903AD2-071 C
Solar/Wind Harmer
8.405
270005AE1-210 C O1
Solar/Wind Harmer
1.614
965031AG1-367 GEN
Solar/Wind Harmer
7.45
24695305TIMB G C
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
4.707
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.289
276848AB2-070 GEN3
Solar/Wind Harmer
0.287
965041AG1-368 GEN
Solar/Wind Harmer
7.862
970289AG2-191 GEN
Solar/Wind Harmer
1.476
971609AH1-304 GEN
Solar/Wind Harmer
1.254
270594AE1-207 GEN
Solar/Wind Harmer
8.574
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.425
24725505WLD G2 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
1.646
24699105WLD G1 C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.008
970115AG2-085 GEN
Solar/Wind Harmer
2.943
270054AF2-122 C O1
Solar/Wind Helper
1.539
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
32.732
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706
CPLELTFEXP_CPLE->PJM
CLTF
3.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.43 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5322.01
MW Contribution:6.73
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
5.145
24721905FLATG4
50/50
94.33
270475AD2-096_GEN
50/50
10.026
270142AC1-141 CT1_
50/50
3.558
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.691
24642205MAYFLWER
50/50
0.992
944961AF1-161 GEN
50/50
4.253
962601AG1-109 GEN
50/50
4.253
247604X1-042
50/50
0.632
970153AG2-106 GEN
Solar/Wind Harmer
76.659
270043AE2-236 GEN
Solar/Wind Harmer
6.969
970349AG2-230 GEN
Solar/Wind Harmer
16.236
959331AF2-224 GEN
Solar/Wind Harmer
7.376
965021AG1-366 GEN
Solar/Wind Harmer
3.512
970513AG2-328 GEN
Solar/Wind Harmer
4.559
970517AG2-330 GEN
Solar/Wind Harmer
27.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
6.732
945111AF1-176 GEN
Solar/Wind Harmer
8.323
944531AF1-118 GEN
Solar/Wind Harmer
45.595
24441205WTRV SLR C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.972
274724RIVER EC ;11
Adder
24.913
274752CRETE EC ;2U
Adder
11.58
274753CRETE EC ;3U
Adder
11.58
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.724
274802UNIV PARK;5U
Adder
8.1
274826FISK ;BP
Adder
15.205
274800UNIV PARK;3U
Adder
8.089
972038AH1-567 GEN2
Adder
0.506
276806AD2-047 C O1
Solar/Wind Harmer
5.485
970941AG2-585 GEN
Solar/Wind Harmer
12.1
972228AH1-698 GEN2
Adder
5.135
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
40.714
274730ELWOOD EC;6P
Adder
22.567
274734ELWOOD EC;8P
Adder
22.567
274736ELWOOD EC;9P
Adder
22.567
274729ELWOOD EC;1P
Adder
22.566
276893AG1-478 C
Solar/Wind Harmer
0.379
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
943121AE2-341 GEN
Solar/Wind Harmer
15.96
943591AF1-030 GEN
Solar/Wind Harmer
10.614
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
24.169
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.341
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.982
274855GSG-6 ;RU
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.165
959091AF2-200 GEN
Solar/Wind Harmer
18.285
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.856
970571AG2-364 GEN
Solar/Wind Harmer
18.064
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.947
274767LEE CO EC;8U
Adder
11.806
276157O29GEN1
Solar/Wind Harmer
1.431
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274878BISHOP HL;2U
Solar/Wind Harmer
0.295
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.785
270404AC1-167 GEN
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
2.831
965931AG1-462 GEN
Solar/Wind Harmer
21.861
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.685
959611AF2-252 GEN
Solar/Wind Harmer
2.854
971617AH1-308 GEN
Solar/Wind Harmer
7.03
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.914
970291AG2-192 GEN
Solar/Wind Harmer
0.831
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
0.295
958821AF2-173 GEN
Solar/Wind Harmer
11.2
270004AE1-209 GEN
Solar/Wind Harmer
1.733
276621W2-048 GEN
Solar/Wind Harmer
0.401
276838X2-022 GEN2
Solar/Wind Harmer
0.448
946031AF1-268 GEN
Solar/Wind Harmer
7.422
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.672
942481AE2-261 GEN
Solar/Wind Harmer
22.986
24728705AND G3
Adder
7.82
24728505AND G1
Adder
3.739
24721805FLATG3
50/50
5.145
24721705FLATG2
50/50
94.33
24344105CKG2
50/50
12.069
270143AC1-141 CT2_
50/50
3.558
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.184
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
120.047
970149AG2-104 GEN
Solar/Wind Harmer
129.655
970155AG2-107 GEN
Solar/Wind Harmer
76.659
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.537
970245AG2-165 GEN
Solar/Wind Harmer
4.559
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.806
945111AF1-176 GEN
Solar/Wind Harmer
18.321
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.329
274773LINCOLN ;4U
Adder
11.972
274774LINCOLN ;5U
Adder
11.972
274723RIVER EC ;12
Adder
25.205
274751CRETE EC ;1U
Adder
11.58
274754CRETE EC ;4U
Adder
11.58
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
20.506
274812UNIV PK N;8U
Adder
6.996
274801UNIV PARK;4U
Adder
8.089
276776AD2-060 GEN
Solar/Wind Harmer
1.011
247521TR3_G114
Solar/Wind Harmer
0.351
270246TR4_N_V150
Solar/Wind Harmer
0.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.222
274674JOLIET 9 ;6U
Adder
21.154
274732ELWOOD EC;7P
Adder
22.567
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.614
944231AF1-091 GEN
Solar/Wind Harmer
2.532
24695305TIMB G C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
28.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.138
965651AG1-433 GEN
Solar/Wind Harmer
2.755
274682WAUKEGAN ;7U
Adder
24.169
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.195
274828WAUKEGAN ;BP
Adder
14.836
246936BC-WTG1
Solar/Wind Harmer
0.379
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270462AD2-086
Solar/Wind Harmer
0.02
962781AG1-127 GEN
Solar/Wind Harmer
8.858
939401AE1-172 GEN
Solar/Wind Harmer
6.954
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.843
958861AF2-177 GEN
Solar/Wind Harmer
3.987
276861AD2-134 GEN
Solar/Wind Harmer
0.165
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.452
957471AF2-041 GEN
Solar/Wind Harmer
27.428
959081AF2-199 GEN
Solar/Wind Harmer
9.143
971067AG2-660 GEN
Solar/Wind Harmer
3.048
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
25.633
972235AH1-702 GEN1
Adder
3.284
970819AG2-516 GEN
Solar/Wind Harmer
10.874
971475AH1-234 GEN
Solar/Wind Harmer
4.385
970569AG2-363 GEN
Solar/Wind Harmer
27.095
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.947
274766LEE CO EC;7U
Adder
11.806
276158O29GEN2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.295
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.194
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.873
970291AG2-192 GEN
Solar/Wind Harmer
1.08
270032AE2-172
Solar/Wind Harmer
5.46
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.14
963741AG1-226 GEN
Solar/Wind Harmer
19.026
270005AE1-210 C O1
Solar/Wind Harmer
1.733
965031AG1-367 GEN
Solar/Wind Harmer
8
276615X2-022 GEN
Solar/Wind Harmer
0.084
276903AD2-071 C
Solar/Wind Harmer
8.872
970825AG2-519 GEN
Solar/Wind Harmer
2.793
965911AG1-460 GEN
Solar/Wind Harmer
1.538
24728605AND G2
Adder
3.739
970615AG2-402 GEN
50/50
3.512
247620Y3-023
50/50
0.722
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.169
270101X2-052 CT2
50/50
2.169
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.537
970627AG2-408 GEN
Solar/Wind Harmer
3.161
970321AG2-212 GEN
Solar/Wind Harmer
4.559
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.013
24441505OLIV SLR
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
20.46
961051AF2-396 GEN
Solar/Wind Harmer
13.64
965681AG1-436 GEN
Solar/Wind Harmer
12.752
965791AG1-447 GEN
Solar/Wind Harmer
9.351
274770LINCOLN ;1U
Adder
11.972
274771LINCOLN ;2U
Adder
11.972
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.965
274803UNIV PARK;6U
Adder
8.1
274888KELLY CRK;1U
Solar/Wind Harmer
0.568
274887GEN-1.85
Solar/Wind Harmer
0.255
276843GEN-1.7
Solar/Wind Harmer
0.313
958011AF2-095 GEN
Solar/Wind Harmer
13.939
972259AH1-714 GEN
Adder
26.463
274674JOLIET 9 ;6U
Adder
21.154
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.764
958481AF2-142 GEN
Solar/Wind Harmer
14.096
274695ROCKY RD ;2P
Adder
14.996
274693ROCKY RD ;1P
Adder
14.848
274697ROCKY RD ;3P
Adder
4.074
274696ROCKY RD ;4P
Adder
15.349
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.271
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.509
274683WAUKEGAN ;8U
Adder
28.303
274683WAUKEGAN ;8U
Adder
23.858
246938BC-WTG3
Solar/Wind Harmer
0.338
246937BC-WTG2
Solar/Wind Harmer
0.379
962691AG1-118 GEN
Solar/Wind Harmer
27.992
970921AG2-575 GEN
Solar/Wind Harmer
9.308
970921AG2-575 GEN
Solar/Wind Harmer
3.103
958491AF2-143 GEN
Solar/Wind Harmer
13.931
274879MINONK ;1U
Solar/Wind Harmer
0.39
942991AE2-321 GEN
Solar/Wind Harmer
10.32
971333AH1-146 GEN
Solar/Wind Harmer
18.389
971335AH1-147 GEN
Solar/Wind Harmer
18.389
971341AH1-150 GEN
Solar/Wind Harmer
18.285
971343AH1-151 GEN
Solar/Wind Harmer
18.285
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
942221AE2-234 GEN
Solar/Wind Harmer
0.046
274856ECOGROVE ;U1
Solar/Wind Harmer
0.213
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
5.096
274764LEE CO EC;5U
Adder
11.975
274765LEE CO EC;6U
Adder
11.975
274762LEE CO EC;3U
Adder
11.947
274763LEE CO EC;4U
Adder
11.834
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270007AE1-245 C
Solar/Wind Harmer
0.002
972267AH1-718 GEN
Adder
5.295
276741O09 GEN1
Solar/Wind Harmer
0.315
276708O09 GEN2
Solar/Wind Harmer
0.315
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.614
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.854
966841AG1-555 GEN
Solar/Wind Harmer
0.959
270599AE1-208 GEN
Solar/Wind Harmer
7.715
270031AE2-169
Solar/Wind Harmer
4.629
971613AH1-306 GEN
Solar/Wind Harmer
3.931
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.69
960441AF2-335 GEN
Solar/Wind Harmer
7.897
970825AG2-519 GEN
Solar/Wind Harmer
8.719
964611AG1-324 GEN
Solar/Wind Harmer
0.584
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.413
247621Y3-024
Adder
0.262
276916AD2-100_GEN
Solar/Wind Harmer
13.41
276911AD2-131_GEN
Solar/Wind Harmer
0.883
24721605FLATG1
50/50
5.145
971599AH1-298 GEN
50/50
14.587
270144AC1-141 ST1_
50/50
3.152
24653605MOTTVILLE
50/50
0.006
24643105BUCHANAN
50/50
0.019
962771AG1-126 GEN
Solar/Wind Harmer
120.047
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
16.236
270071AF1-092 GEN
Solar/Wind Harmer
20.132
971771AH1-392 GEN
Solar/Wind Harmer
10.346
971619AH1-309 GEN
Solar/Wind Harmer
4.631
971769AH1-391 GEN
Solar/Wind Harmer
11.424
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
24729505KEY G4
Adder
9.267
274775LINCOLN ;6U
Adder
11.972
274776LINCOLN ;7U
Adder
11.972
274777LINCOLN ;8U
Adder
11.972
965041AG1-368 GEN
Solar/Wind Harmer
9.847
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.057
274807UNIV PK N;3U
Adder
7.042
274805UNIV PK N;1U
Adder
7.011
274811UNIV PK N;7U
Adder
6.996
972037AH1-567 GEN1
Adder
0.254
274827FISK ;RP
Adder
10.776
960591AF2-350 GEN
Solar/Wind Harmer
9.68
972227AH1-698 GEN1
Adder
3.616
965051AG1-369 GEN
Solar/Wind Harmer
4.807
274687WILL CNTY;4U
Adder
38.503
274687WILL CNTY;4U
Adder
38.503
274675JOLIET 29;7U
Adder
42.223
274675JOLIET 29;7U
Adder
40.715
274728ELWOOD EC;5P
Adder
22.567
274731ELWOOD EC;2P
Adder
22.566
274733ELWOOD EC;3P
Adder
22.566
274735ELWOOD EC;4P
Adder
22.566
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
970833AG2-524 GEN
Solar/Wind Harmer
10.52
970833AG2-524 GEN
Solar/Wind Harmer
7.013
971549AH1-272 GEN
Solar/Wind Harmer
19.681
274746AC1-111 G10
Adder
7.614
274744AC1-111 GEN8
Adder
7.614
963791AG1-232 GEN
Solar/Wind Harmer
12.76
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.013
971653AH1-327 GEN
Solar/Wind Harmer
1.314
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.855
276882AE2-255 GEN
Solar/Wind Harmer
1.081
971177AH1-047 GEN
Solar/Wind Harmer
5.697
965101AG1-375 GEN
Solar/Wind Harmer
9.202
971411AH1-196 GEN
Solar/Wind Harmer
13.802
971675AH1-338 GEN
Solar/Wind Harmer
3.588
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.454
971171AH1-044 GEN
Solar/Wind Harmer
18.285
274823ROCKFORD ;21
Adder
25.447
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.535
970169AG2-114 GEN
Solar/Wind Harmer
9.023
971681AH1-341 GEN
Solar/Wind Harmer
14.483
247607V1-011 GEN
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
5.219
945581AF1-223 GEN
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.292
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.145
941731AE2-173 GEN
Solar/Wind Harmer
7.258
946321AF1-296 GEN
Solar/Wind Harmer
4.827
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.009
971609AH1-304 GEN
Solar/Wind Harmer
1.375
970289AG2-191 GEN
Solar/Wind Harmer
1.578
963841AG1-237 GEN
Solar/Wind Harmer
3.575
270594AE1-207 GEN
Solar/Wind Harmer
9.172
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.295
276848AB2-070 GEN3
Solar/Wind Harmer
0.294
970115AG2-085 GEN
Solar/Wind Harmer
3.159
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
944201AF1-088_MTX
Adder
85.667
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.132
MECLTFEXP_MEC->PJM
CLTF
18.394
SIGELTFEXP_SIGE->PJM
CLTF
0.399
LAGNLTFEXP_LAGN->PJM
CLTF
11.144
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.328
TVALTFEXP_TVA->PJM
CLTF
4.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.989
NYPJM->LTFIMP_NY
CLTF
2.99
LGEELTFEXP_LGEE->PJM
CLTF
4.155
WECLTFEXP_WEC->PJM
CLTF
4.968
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.312
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.86 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4648.25
MW Contribution:4.84
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.603
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.096
24642205MAYFLWER
50/50
0.728
274772LINCOLN ;3U
50/50
9.593
970153AG2-106 GEN
Solar/Wind Harmer
47.639
970349AG2-230 GEN
Solar/Wind Harmer
12.013
970513AG2-328 GEN
Solar/Wind Harmer
3.44
970517AG2-330 GEN
Solar/Wind Harmer
20.64
270043AE2-236 GEN
Solar/Wind Harmer
5.033
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.073
970031AG2-029 GEN
Solar/Wind Harmer
4.844
944531AF1-118 GEN
Solar/Wind Harmer
33.218
274724RIVER EC ;11
Adder
18.771
274752CRETE EC ;2U
Adder
8.717
274753CRETE EC ;3U
Adder
8.717
959331AF2-224 GEN
Solar/Wind Harmer
5.157
965021AG1-366 GEN
Solar/Wind Harmer
2.455
970707AG2-453 GEN
Solar/Wind Harmer
24.03
274826FISK ;BP
Adder
11.498
274802UNIV PARK;5U
Adder
6.123
276806AD2-047 C O1
Solar/Wind Harmer
4.15
970941AG2-585 GEN
Solar/Wind Harmer
9.154
274800UNIV PARK;3U
Adder
6.118
972038AH1-567 GEN2
Adder
0.383
972228AH1-698 GEN2
Adder
3.887
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.865
274729ELWOOD EC;1P
Adder
17.114
274730ELWOOD EC;6P
Adder
17.114
274734ELWOOD EC;8P
Adder
17.114
274736ELWOOD EC;9P
Adder
17.114
276893AG1-478 C
Solar/Wind Harmer
0.288
943121AE2-341 GEN
Solar/Wind Harmer
12.132
943591AF1-030 GEN
Solar/Wind Harmer
8.068
247604X1-042
Adder
0.432
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.416
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24344105CKG2
50/50
8.939
270143AC1-141 CT2_
50/50
2.603
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.519
274773LINCOLN ;4U
50/50
9.593
274774LINCOLN ;5U
50/50
9.593
962761AG1-125 GEN
Solar/Wind Harmer
74.603
970149AG2-104 GEN
Solar/Wind Harmer
80.573
970155AG2-107 GEN
Solar/Wind Harmer
47.639
970245AG2-165 GEN
Solar/Wind Harmer
3.44
270505AE1-170 C O1
Solar/Wind Harmer
7.896
270063AE2-323 C
Solar/Wind Harmer
0.006
945111AF1-176 GEN
Solar/Wind Harmer
13.37
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.886
274723RIVER EC ;12
Adder
18.99
274872LEEDK;1U
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
0.258
274850MENDOTA H;RU
Solar/Wind Harmer
0.083
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
14.009
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.191
970571AG2-364 GEN
Solar/Wind Harmer
13.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.191
274767LEE CO EC;8U
Adder
9.083
276157O29GEN1
Solar/Wind Harmer
1.104
274878BISHOP HL;2U
Solar/Wind Harmer
0.228
24721905FLATG4
Adder
19.64
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.747
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.976
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.897
959611AF2-252 GEN
Solar/Wind Harmer
2.211
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.93
276668AB2-070 GEN1
Solar/Wind Harmer
0.231
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.316
276838X2-022 GEN2
Solar/Wind Harmer
0.352
970289AG2-191 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.623
942481AE2-261 GEN
Solar/Wind Harmer
18.215
270491AE1-102 GEN2
Solar/Wind Harmer
0.785
274751CRETE EC ;1U
Adder
8.717
274754CRETE EC ;4U
Adder
8.717
276164X3-005 C
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
7.366
274812UNIV PK N;8U
Adder
5.278
970373AG2-245 GEN
Solar/Wind Harmer
15.386
276776AD2-060 GEN
Solar/Wind Harmer
0.765
274801UNIV PARK;4U
Adder
6.118
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
32.008
274674JOLIET 9 ;6U
Adder
16.042
274732ELWOOD EC;7P
Adder
17.114
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.788
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276691AA1-018 GEN1
Solar/Wind Harmer
0.866
274682WAUKEGAN ;7U
Adder
18.416
274828WAUKEGAN ;BP
Adder
11.308
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.763
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.233
274872LEEDK;1U
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
5.304
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.701
276861AD2-134 GEN
Solar/Wind Harmer
0.126
957471AF2-041 GEN
Solar/Wind Harmer
21.014
959081AF2-199 GEN
Solar/Wind Harmer
7.005
971067AG2-660 GEN
Solar/Wind Harmer
2.335
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.652
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.717
972235AH1-702 GEN1
Adder
2.519
970819AG2-516 GEN
Solar/Wind Harmer
8.346
971475AH1-234 GEN
Solar/Wind Harmer
3.368
970569AG2-363 GEN
Solar/Wind Harmer
20.788
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.191
274766LEE CO EC;7U
Adder
9.083
965651AG1-433 GEN
Solar/Wind Harmer
2.017
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.228
24721705FLATG2
Adder
19.64
24791305MDL-5G
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
2.923
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.413
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
944231AF1-091 GEN
Solar/Wind Harmer
1.739
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
972175AH1-670 GEN
Solar/Wind Harmer
5.355
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24695305TIMB G C
Solar/Wind Harmer
0.002
274880W4-005 GEN4
Solar/Wind Harmer
0.001
270102X2-052 ST
50/50
1.747
270100X2-052 CT1
50/50
1.61
270101X2-052 CT2
50/50
1.61
247620Y3-023
50/50
0.525
274770LINCOLN ;1U
50/50
9.593
274771LINCOLN ;2U
50/50
9.593
970321AG2-212 GEN
Solar/Wind Harmer
3.44
270216AD2-079_GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
9.481
965791AG1-447 GEN
Solar/Wind Harmer
6.953
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.924
961051AF2-396 GEN
Solar/Wind Harmer
9.95
970611AG2-400 GEN
Solar/Wind Harmer
7.366
970627AG2-408 GEN
Solar/Wind Harmer
2.21
274808UNIV PK N;4U
Adder
5.255
972259AH1-714 GEN
Adder
20.044
274803UNIV PARK;6U
Adder
6.123
274888KELLY CRK;1U
Solar/Wind Harmer
0.43
274887GEN-1.85
Solar/Wind Harmer
0.193
276843GEN-1.7
Solar/Wind Harmer
0.237
958011AF2-095 GEN
Solar/Wind Harmer
10.545
274674JOLIET 9 ;6U
Adder
16.042
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.342
274695ROCKY RD ;2P
Adder
11.425
274693ROCKY RD ;1P
Adder
11.312
274697ROCKY RD ;3P
Adder
3.104
274696ROCKY RD ;4P
Adder
11.694
958481AF2-142 GEN
Solar/Wind Harmer
10.727
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.967
274683WAUKEGAN ;8U
Adder
21.572
274683WAUKEGAN ;8U
Adder
18.184
962691AG1-118 GEN
Solar/Wind Harmer
21.36
970921AG2-575 GEN
Solar/Wind Harmer
7.106
970921AG2-575 GEN
Solar/Wind Harmer
2.369
958491AF2-143 GEN
Solar/Wind Harmer
10.627
942991AE2-321 GEN
Solar/Wind Harmer
7.889
274879MINONK ;1U
Solar/Wind Harmer
0.298
971333AH1-146 GEN
Solar/Wind Harmer
14.073
971335AH1-147 GEN
Solar/Wind Harmer
14.073
971341AH1-150 GEN
Solar/Wind Harmer
14.009
971343AH1-151 GEN
Solar/Wind Harmer
14.009
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.164
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.917
274764LEE CO EC;5U
Adder
9.213
274765LEE CO EC;6U
Adder
9.213
274762LEE CO EC;3U
Adder
9.191
274763LEE CO EC;4U
Adder
9.105
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.461
960971AF2-388 GEN
Solar/Wind Harmer
4.033
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.082
276741O09 GEN1
Solar/Wind Harmer
0.243
276708O09 GEN2
Solar/Wind Harmer
0.243
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.462
963741AG1-226 GEN
Solar/Wind Harmer
14.839
276615X2-022 GEN
Solar/Wind Harmer
0.066
970291AG2-192 GEN
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.496
270032AE2-172
Solar/Wind Harmer
4.081
965911AG1-460 GEN
Solar/Wind Harmer
1.218
246936BC-WTG1
Solar/Wind Harmer
0.245
270489AE1-102 GEN1
Solar/Wind Harmer
0.785
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.211
942221AE2-234 GEN
Solar/Wind Harmer
0.033
966841AG1-555 GEN
Solar/Wind Harmer
0.741
270471AD2-092_GEN
Solar/Wind Harmer
0.005
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.657
270599AE1-208 GEN
Solar/Wind Harmer
5.676
270031AE2-169
Solar/Wind Harmer
3.406
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276916AD2-100_GEN
Solar/Wind Harmer
12.71
276911AD2-131_GEN
Solar/Wind Harmer
0.837
246938BC-WTG3
Solar/Wind Harmer
0.219
246937BC-WTG2
Solar/Wind Harmer
0.245
971599AH1-298 GEN
50/50
10.558
270144AC1-141 ST1_
50/50
2.306
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.593
274776LINCOLN ;7U
50/50
9.593
274777LINCOLN ;8U
50/50
9.593
962771AG1-126 GEN
Solar/Wind Harmer
74.603
971347AH1-153 GEN
Solar/Wind Harmer
12.013
270071AF1-092 GEN
Solar/Wind Harmer
14.717
971771AH1-392 GEN
Solar/Wind Harmer
7.604
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.444
971619AH1-309 GEN
Solar/Wind Harmer
3.384
274814UNIV PK N;0U
Adder
5.324
274807UNIV PK N;3U
Adder
5.313
274805UNIV PK N;1U
Adder
5.29
274811UNIV PK N;7U
Adder
5.278
274827FISK ;RP
Adder
8.149
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
7.323
972227AH1-698 GEN1
Adder
2.737
274687WILL CNTY;4U
Adder
29.176
274687WILL CNTY;4U
Adder
29.176
274675JOLIET 29;7U
Adder
32.008
274675JOLIET 29;7U
Adder
30.865
24729505KEY G4
Adder
6.759
274731ELWOOD EC;2P
Adder
17.114
274733ELWOOD EC;3P
Adder
17.114
274735ELWOOD EC;4P
Adder
17.114
274728ELWOOD EC;5P
Adder
17.114
970833AG2-524 GEN
Solar/Wind Harmer
7.985
970833AG2-524 GEN
Solar/Wind Harmer
5.323
274746AC1-111 G10
Adder
5.788
274744AC1-111 GEN8
Adder
5.788
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
971177AH1-047 GEN
Solar/Wind Harmer
4.355
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.417
276882AE2-255 GEN
Solar/Wind Harmer
0.825
971675AH1-338 GEN
Solar/Wind Harmer
2.746
971411AH1-196 GEN
Solar/Wind Harmer
10.56
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971171AH1-044 GEN
Solar/Wind Harmer
14.009
274823ROCKFORD ;21
Adder
19.51
971611AH1-305 GEN
Solar/Wind Harmer
4.152
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.178
970169AG2-114 GEN
Solar/Wind Harmer
6.92
971681AH1-341 GEN
Solar/Wind Harmer
11.133
961011AF2-392 GEN
Solar/Wind Harmer
4.021
957751AF2-069 GEN
Solar/Wind Harmer
0.225
971549AH1-272 GEN
Solar/Wind Harmer
14.034
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
6.746
965041AG1-368 GEN
Solar/Wind Harmer
6.733
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.744
963791AG1-232 GEN
Solar/Wind Harmer
8.989
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.241
963841AG1-237 GEN
Solar/Wind Harmer
2.776
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.231
276848AB2-070 GEN3
Solar/Wind Harmer
0.23
970289AG2-191 GEN
Solar/Wind Harmer
1.184
971609AH1-304 GEN
Solar/Wind Harmer
1.011
270594AE1-207 GEN
Solar/Wind Harmer
6.856
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.765
270284AF1-227 GEN1
Solar/Wind Harmer
0.008
270286AF1-227 GEN2
Solar/Wind Harmer
0.003
270287AF1-227 GEN3
Solar/Wind Harmer
0.003
270054AF2-122 C O1
Solar/Wind Helper
1.65
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.189
MECLTFEXP_MEC->PJM
CLTF
14.69
SIGELTFEXP_SIGE->PJM
CLTF
0.339
LAGNLTFEXP_LAGN->PJM
CLTF
11.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.669
TVALTFEXP_TVA->PJM
CLTF
5.062
CPLELTFEXP_CPLE->PJM
CLTF
1.429
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.023
NYPJM->LTFIMP_NY
CLTF
2.589
LGEELTFEXP_LGEE->PJM
CLTF
3.659
WECLTFEXP_WEC->PJM
CLTF
3.814
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.355

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.67 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5104.52
MW Contribution:32.37
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
9.068
270143AC1-141 CT2_
50/50
2.636
274773LINCOLN ;4U
50/50
7.2
274774LINCOLN ;5U
50/50
7.2
24639705ELKHART HY
50/50
0.178
970521AG2-332 GEN
50/50
12.672
962761AG1-125 GEN
Solar/Wind Harmer
88.693
970149AG2-104 GEN
Solar/Wind Harmer
109.536
970155AG2-107 GEN
Solar/Wind Harmer
38.674
970245AG2-165 GEN
Solar/Wind Harmer
20.738
972207SS24-0001
Solar/Wind Harmer
24.126
270505AE1-170 C O1
Solar/Wind Harmer
16.366
945111AF1-176 GEN
Solar/Wind Harmer
19.395
270063AE2-323 C
Solar/Wind Harmer
2.395
274723RIVER EC ;12
Adder
19.397
274751CRETE EC ;1U
Adder
5.281
274754CRETE EC ;4U
Adder
5.281
276164X3-005 C
Solar/Wind Harmer
0.759
270449AD2-020 GEN
Solar/Wind Harmer
3.026
943021AE2-325 GEN
Solar/Wind Harmer
3.932
274812UNIV PK N;8U
Adder
5.394
276776AD2-060 GEN
Solar/Wind Harmer
0.454
274801UNIV PARK;4U
Adder
6.257
970373AG2-245 GEN
Solar/Wind Harmer
22.515
941551AE2-152 GEN
Solar/Wind Harmer
4.854
274676JOLIET 29;8U
Adder
32.754
274674JOLIET 9 ;6U
Adder
16.418
274732ELWOOD EC;7P
Adder
17.516
274871GR RIDGE ;2U
Solar/Wind Harmer
8.188
965011AG1-365 GEN
Solar/Wind Harmer
10.607
274745AC1-111 GEN9
Adder
5.928
270055AF2-134 C O1
Solar/Wind Harmer
3.202
24721705FLATG2
Adder
21.327
276691AA1-018 GEN1
Solar/Wind Harmer
0.489
274682WAUKEGAN ;7U
Adder
18.874
274828WAUKEGAN ;BP
Adder
11.59
960751AF2-366 GEN
Solar/Wind Harmer
2.997
962781AG1-127 GEN
Solar/Wind Harmer
9.933
958381AF2-132 GEN
Solar/Wind Harmer
9.472
274872LEEDK;1U
Solar/Wind Harmer
8.565
964861AG1-349 GEN
Solar/Wind Harmer
8.196
971917AH1-482 GEN
Solar/Wind Harmer
9.458
939401AE1-172 GEN
Solar/Wind Harmer
14.53
276901AD2-066 C O1
Solar/Wind Harmer
3.656
971997AH1-543 GEN
Solar/Wind Harmer
16.328
276861AD2-134 GEN
Solar/Wind Harmer
1.849
274822ROCKFORD ;11
Adder
20.179
972235AH1-702 GEN1
Adder
2.587
274761LEE CO EC;2U
Adder
9.448
274766LEE CO EC;7U
Adder
9.337
957471AF2-041 GEN
Solar/Wind Harmer
0.989
959081AF2-199 GEN
Solar/Wind Harmer
0.33
971067AG2-660 GEN
Solar/Wind Harmer
0.077
971599AH1-298 GEN
50/50
10.665
270144AC1-141 ST1_
50/50
2.335
274775LINCOLN ;6U
50/50
7.2
274776LINCOLN ;7U
50/50
7.2
274777LINCOLN ;8U
50/50
7.2
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
88.693
971347AH1-153 GEN
Solar/Wind Harmer
17.476
270071AF1-092 GEN
Solar/Wind Harmer
16.765
960681AF2-359 GEN
Solar/Wind Harmer
4.178
971771AH1-392 GEN
Solar/Wind Harmer
9.947
971769AH1-391 GEN
Solar/Wind Harmer
11.009
274814UNIV PK N;0U
Adder
5.441
274807UNIV PK N;3U
Adder
5.429
274805UNIV PK N;1U
Adder
5.405
274811UNIV PK N;7U
Adder
5.394
274827FISK ;RP
Adder
8.332
972037AH1-567 GEN1
Adder
0.197
960591AF2-350 GEN
Solar/Wind Harmer
10.735
972227AH1-698 GEN1
Adder
2.799
944161AF1-084 GEN
Solar/Wind Harmer
2.371
274687WILL CNTY;4U
Adder
29.852
274687WILL CNTY;4U
Adder
29.852
274675JOLIET 29;7U
Adder
32.754
274675JOLIET 29;7U
Adder
31.584
274731ELWOOD EC;2P
Adder
17.516
274733ELWOOD EC;3P
Adder
17.516
274735ELWOOD EC;4P
Adder
17.516
274728ELWOOD EC;5P
Adder
17.516
970833AG2-524 GEN
Solar/Wind Harmer
9.299
970833AG2-524 GEN
Solar/Wind Harmer
4.325
24729505KEY G4
Adder
6.895
274746AC1-111 G10
Adder
5.928
274744AC1-111 GEN8
Adder
5.928
270536AF1-215 GEN2
Solar/Wind Harmer
4.803
971177AH1-047 GEN
Solar/Wind Harmer
6.086
276868AE1-113 GEN
Solar/Wind Harmer
10.506
276882AE2-255 GEN
Solar/Wind Harmer
3.502
958391AF2-133 GEN
Solar/Wind Harmer
9.41
971675AH1-338 GEN
Solar/Wind Harmer
18.64
971411AH1-196 GEN
Solar/Wind Harmer
15.533
274863CRW1-WTG
Solar/Wind Harmer
5.758
274864CRW2-WTG
Solar/Wind Harmer
5.758
274823ROCKFORD ;21
Adder
20.032
270054AF2-122 C O1
Solar/Wind Helper
1.787
971171AH1-044 GEN
Solar/Wind Harmer
0.659
270102X2-052 ST
50/50
1.777
270100X2-052 CT1
50/50
1.637
270101X2-052 CT2
50/50
1.637
274770LINCOLN ;1U
50/50
7.2
274771LINCOLN ;2U
50/50
7.2
247620Y3-023
50/50
0.531
970321AG2-212 GEN
Solar/Wind Harmer
20.738
965681AG1-436 GEN
Solar/Wind Harmer
13.825
965791AG1-447 GEN
Solar/Wind Harmer
7.073
270216AD2-079_GEN
Solar/Wind Harmer
0.668
270526AF1-158 GEN
Solar/Wind Harmer
5.006
24441505OLIV SLR
Solar/Wind Harmer
0.147
957891AF2-083 GEN
Solar/Wind Harmer
3.677
960981AF2-389 GEN
Solar/Wind Harmer
1.648
961051AF2-396 GEN
Solar/Wind Harmer
17.18
961051AF2-396 GEN
Solar/Wind Harmer
7.99
274808UNIV PK N;4U
Adder
5.37
972259AH1-714 GEN
Adder
20.504
274803UNIV PARK;6U
Adder
6.261
274888KELLY CRK;1U
Solar/Wind Harmer
6.338
274887GEN-1.85
Solar/Wind Harmer
5.722
276843GEN-1.7
Solar/Wind Harmer
0.616
958011AF2-095 GEN
Solar/Wind Harmer
15.458
274674JOLIET 9 ;6U
Adder
16.418
274847GR RIDGE ;BU
Solar/Wind Harmer
5.386
970611AG2-400 GEN
Solar/Wind Harmer
10.607
971573AH1-285 GEN
Solar/Wind Harmer
9.097
274695ROCKY RD ;2P
Adder
11.708
274693ROCKY RD ;1P
Adder
11.593
274697ROCKY RD ;3P
Adder
3.181
274696ROCKY RD ;4P
Adder
11.984
958481AF2-142 GEN
Solar/Wind Harmer
15.755
274861TOP CROP ;1U
Solar/Wind Harmer
6.362
274862TOP CROP ;2U
Solar/Wind Harmer
5.313
274683WAUKEGAN ;8U
Adder
22.11
274683WAUKEGAN ;8U
Adder
18.638
962691AG1-118 GEN
Solar/Wind Harmer
31.39
970921AG2-575 GEN
Solar/Wind Harmer
10.445
970921AG2-575 GEN
Solar/Wind Harmer
2.429
958491AF2-143 GEN
Solar/Wind Harmer
15.621
942991AE2-321 GEN
Solar/Wind Harmer
10.388
274879MINONK ;1U
Solar/Wind Harmer
7.005
971333AH1-146 GEN
Solar/Wind Harmer
20.7
971335AH1-147 GEN
Solar/Wind Harmer
20.7
274764LEE CO EC;5U
Adder
9.47
274765LEE CO EC;6U
Adder
9.47
274762LEE CO EC;3U
Adder
9.448
274763LEE CO EC;4U
Adder
9.359
972267AH1-718 GEN
Adder
4.199
971341AH1-150 GEN
Solar/Wind Harmer
0.659
971343AH1-151 GEN
Solar/Wind Harmer
0.659
270142AC1-141 CT1_
50/50
2.636
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.184
274772LINCOLN ;3U
50/50
7.2
24642205MAYFLWER
50/50
0.738
970153AG2-106 GEN
Solar/Wind Harmer
38.674
970349AG2-230 GEN
Solar/Wind Harmer
17.476
970513AG2-328 GEN
Solar/Wind Harmer
20.738
970517AG2-330 GEN
Solar/Wind Harmer
18.809
270043AE2-236 GEN
Solar/Wind Harmer
6.251
247643Z2-116 C
Solar/Wind Harmer
0.077
945111AF1-176 GEN
Solar/Wind Harmer
6.147
274724RIVER EC ;11
Adder
19.173
944531AF1-118 GEN
Solar/Wind Harmer
37.878
972231SS25-0005
Solar/Wind Harmer
10.253
972181SS23-001
Solar/Wind Harmer
6.408
274752CRETE EC ;2U
Adder
5.281
274753CRETE EC ;3U
Adder
5.281
970031AG2-029 GEN
Solar/Wind Harmer
32.374
970707AG2-453 GEN
Solar/Wind Harmer
30.198
274826FISK ;BP
Adder
11.757
274802UNIV PARK;5U
Adder
6.261
276772AC2-154 GEN
Solar/Wind Harmer
2.994
276806AD2-047 C O1
Solar/Wind Harmer
11.484
970941AG2-585 GEN
Solar/Wind Harmer
13.419
972228AH1-698 GEN2
Adder
3.976
274800UNIV PARK;3U
Adder
6.257
972038AH1-567 GEN2
Adder
0.392
276897AD1-100 C
Solar/Wind Harmer
31.058
939351AE1-166 GEN
Solar/Wind Harmer
6.346
274676JOLIET 29;8U
Adder
31.584
274729ELWOOD EC;1P
Adder
17.516
274730ELWOOD EC;6P
Adder
17.516
274734ELWOOD EC;8P
Adder
17.516
274736ELWOOD EC;9P
Adder
17.516
276893AG1-478 C
Solar/Wind Harmer
0.445
943121AE2-341 GEN
Solar/Wind Harmer
15.932
943591AF1-030 GEN
Solar/Wind Harmer
10.621
959331AF2-224 GEN
Solar/Wind Harmer
10.607
965021AG1-366 GEN
Solar/Wind Harmer
2.467
24441205WTRV SLR C
Solar/Wind Harmer
0.143
270535AF1-215 GEN1
Solar/Wind Harmer
4.803
24721905FLATG4
Adder
21.327
276694AA1-018 GEN2
Solar/Wind Harmer
6.628
274682WAUKEGAN ;7U
Adder
18.874
247604X1-042
Adder
0.436
964401AG1-302 GEN
Solar/Wind Harmer
9.472
274872LEEDK;1U
Solar/Wind Harmer
0.267
276805AD2-038 GEN
Solar/Wind Harmer
5.342
276799AD1-013 GEN
Solar/Wind Harmer
2.29
946671AF1-331 GEN
Solar/Wind Harmer
0.434
274855GSG-6 ;RU
Solar/Wind Harmer
3.824
274850MENDOTA H;RU
Solar/Wind Harmer
2.659
276602WESTBROOK C
Solar/Wind Harmer
2.201
276863AD2-134 GEN
Solar/Wind Harmer
1.849
959141AF2-205 GEN
Solar/Wind Harmer
6.241
972236AH1-702 GEN2
Adder
2.25
274760LEE CO EC;1U
Adder
9.448
274767LEE CO EC;8U
Adder
9.337
959091AF2-200 GEN
Solar/Wind Harmer
0.659
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.675
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.249
MECLTFEXP_MEC->PJM
CLTF
15.261
SIGELTFEXP_SIGE->PJM
CLTF
0.364
LAGNLTFEXP_LAGN->PJM
CLTF
12.245
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.222
TVALTFEXP_TVA->PJM
CLTF
5.61
CPLELTFEXP_CPLE->PJM
CLTF
1.907
CBM West 2LTFEXP_CBM-W2->PJM
CBM
93.196
NYPJM->LTFIMP_NY
CLTF
2.821
LGEELTFEXP_LGEE->PJM
CLTF
4.037
WECLTFEXP_WEC->PJM
CLTF
3.917
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.09 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5032.32
MW Contribution:33.99
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
9.384
270143AC1-141 CT2_
50/50
2.761
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.281
24307105BERRINSP G
50/50
0.025
962761AG1-125 GEN
Solar/Wind Harmer
89.197
970149AG2-104 GEN
Solar/Wind Harmer
110.158
970155AG2-107 GEN
Solar/Wind Harmer
38.894
970245AG2-165 GEN
Solar/Wind Harmer
21.268
270505AE1-170 C O1
Solar/Wind Harmer
17.176
971599AH1-298 GEN
50/50
11.057
270144AC1-141 ST1_
50/50
2.446
24643105BUCHANAN
50/50
0.015
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
89.197
971347AH1-153 GEN
Solar/Wind Harmer
18.111
270071AF1-092 GEN
Solar/Wind Harmer
17.338
971771AH1-392 GEN
Solar/Wind Harmer
10.383
960681AF2-359 GEN
Solar/Wind Harmer
4.333
971769AH1-391 GEN
Solar/Wind Harmer
11.46
944161AF1-084 GEN
Solar/Wind Harmer
2.498
274775LINCOLN ;6U
Adder
6.975
274776LINCOLN ;7U
Adder
6.975
274777LINCOLN ;8U
Adder
6.975
274814UNIV PK N;0U
Adder
5.601
274807UNIV PK N;3U
Adder
5.589
274805UNIV PK N;1U
Adder
5.565
274811UNIV PK N;7U
Adder
5.552
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.568
960591AF2-350 GEN
Solar/Wind Harmer
11.036
972227AH1-698 GEN1
Adder
2.877
274687WILL CNTY;4U
Adder
30.673
274687WILL CNTY;4U
Adder
30.673
274675JOLIET 29;7U
Adder
33.649
274675JOLIET 29;7U
Adder
32.447
274731ELWOOD EC;2P
Adder
17.991
274733ELWOOD EC;3P
Adder
17.991
274735ELWOOD EC;4P
Adder
17.991
274728ELWOOD EC;5P
Adder
17.991
970833AG2-524 GEN
Solar/Wind Harmer
9.547
970833AG2-524 GEN
Solar/Wind Harmer
4.44
24729505KEY G4
Adder
7.093
270536AF1-215 GEN2
Solar/Wind Harmer
4.953
274746AC1-111 G10
Adder
6.083
274744AC1-111 GEN8
Adder
6.083
958391AF2-133 GEN
Solar/Wind Harmer
9.677
971177AH1-047 GEN
Solar/Wind Harmer
6.235
276868AE1-113 GEN
Solar/Wind Harmer
10.768
276882AE2-255 GEN
Solar/Wind Harmer
3.589
971411AH1-196 GEN
Solar/Wind Harmer
15.911
971675AH1-338 GEN
Solar/Wind Harmer
19.093
274823ROCKFORD ;21
Adder
20.508
270054AF2-122 C O1
Solar/Wind Helper
1.62
971549AH1-272 GEN
Solar/Wind Harmer
15.966
270102X2-052 ST
50/50
1.844
270100X2-052 CT1
50/50
1.699
270101X2-052 CT2
50/50
1.699
247620Y3-023
50/50
0.557
970321AG2-212 GEN
Solar/Wind Harmer
21.268
270216AD2-079_GEN
Solar/Wind Harmer
0.699
270526AF1-158 GEN
Solar/Wind Harmer
5.214
965681AG1-436 GEN
Solar/Wind Harmer
14.336
965791AG1-447 GEN
Solar/Wind Harmer
7.335
24441505OLIV SLR
Solar/Wind Harmer
0.154
957891AF2-083 GEN
Solar/Wind Harmer
3.858
960981AF2-389 GEN
Solar/Wind Harmer
1.729
961051AF2-396 GEN
Solar/Wind Harmer
18.061
961051AF2-396 GEN
Solar/Wind Harmer
8.401
274770LINCOLN ;1U
Adder
6.975
274771LINCOLN ;2U
Adder
6.975
970611AG2-400 GEN
Solar/Wind Harmer
11.187
274808UNIV PK N;4U
Adder
5.528
274803UNIV PARK;6U
Adder
6.439
972259AH1-714 GEN
Adder
21.064
274888KELLY CRK;1U
Solar/Wind Harmer
6.515
274887GEN-1.85
Solar/Wind Harmer
5.882
276843GEN-1.7
Solar/Wind Harmer
0.633
958011AF2-095 GEN
Solar/Wind Harmer
15.891
274674JOLIET 9 ;6U
Adder
16.864
274847GR RIDGE ;BU
Solar/Wind Harmer
5.529
971573AH1-285 GEN
Solar/Wind Harmer
9.332
274695ROCKY RD ;2P
Adder
12.008
274693ROCKY RD ;1P
Adder
11.89
274697ROCKY RD ;3P
Adder
3.262
274696ROCKY RD ;4P
Adder
12.291
958481AF2-142 GEN
Solar/Wind Harmer
16.166
274861TOP CROP ;1U
Solar/Wind Harmer
6.528
274862TOP CROP ;2U
Solar/Wind Harmer
5.451
274683WAUKEGAN ;8U
Adder
22.675
274683WAUKEGAN ;8U
Adder
19.114
962691AG1-118 GEN
Solar/Wind Harmer
32.178
970921AG2-575 GEN
Solar/Wind Harmer
10.705
970921AG2-575 GEN
Solar/Wind Harmer
2.49
958491AF2-143 GEN
Solar/Wind Harmer
16.016
942991AE2-321 GEN
Solar/Wind Harmer
10.644
274879MINONK ;1U
Solar/Wind Harmer
7.179
971333AH1-146 GEN
Solar/Wind Harmer
21.203
971335AH1-147 GEN
Solar/Wind Harmer
21.203
274764LEE CO EC;5U
Adder
9.685
274765LEE CO EC;6U
Adder
9.685
274762LEE CO EC;3U
Adder
9.662
274763LEE CO EC;4U
Adder
9.571
972267AH1-718 GEN
Adder
4.292
270142AC1-141 CT1_
50/50
2.761
24344005CKG1
50/50
7.535
24641605TWIN BRNCH
50/50
0.02
24642205MAYFLWER
50/50
0.772
944961AF1-161 GEN
50/50
3.302
962601AG1-109 GEN
50/50
3.302
970153AG2-106 GEN
Solar/Wind Harmer
38.894
970349AG2-230 GEN
Solar/Wind Harmer
18.111
970513AG2-328 GEN
Solar/Wind Harmer
21.268
970517AG2-330 GEN
Solar/Wind Harmer
19.29
270043AE2-236 GEN
Solar/Wind Harmer
6.511
247643Z2-116 C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
6.454
970031AG2-029 GEN
Solar/Wind Harmer
33.986
274772LINCOLN ;3U
Adder
6.975
24441205WTRV SLR C
Solar/Wind Harmer
0.151
959331AF2-224 GEN
Solar/Wind Harmer
11.187
965021AG1-366 GEN
Solar/Wind Harmer
2.602
274724RIVER EC ;11
Adder
19.746
944531AF1-118 GEN
Solar/Wind Harmer
39.003
972231SS25-0005
Solar/Wind Harmer
10.567
972181SS23-001
Solar/Wind Harmer
6.604
274752CRETE EC ;2U
Adder
5.442
274753CRETE EC ;3U
Adder
5.442
247604X1-042
Adder
0.463
970707AG2-453 GEN
Solar/Wind Harmer
31.017
274802UNIV PARK;5U
Adder
6.439
274826FISK ;BP
Adder
12.09
276772AC2-154 GEN
Solar/Wind Harmer
3.077
276806AD2-047 C O1
Solar/Wind Harmer
11.806
970941AG2-585 GEN
Solar/Wind Harmer
13.795
274800UNIV PARK;3U
Adder
6.433
972038AH1-567 GEN2
Adder
0.403
972228AH1-698 GEN2
Adder
4.086
276897AD1-100 C
Solar/Wind Harmer
31.901
939351AE1-166 GEN
Solar/Wind Harmer
6.518
274676JOLIET 29;8U
Adder
32.446
274729ELWOOD EC;1P
Adder
17.991
274730ELWOOD EC;6P
Adder
17.991
274734ELWOOD EC;8P
Adder
17.991
274736ELWOOD EC;9P
Adder
17.991
276893AG1-478 C
Solar/Wind Harmer
0.457
270535AF1-215 GEN1
Solar/Wind Harmer
4.953
943121AE2-341 GEN
Solar/Wind Harmer
16.349
943591AF1-030 GEN
Solar/Wind Harmer
10.899
276694AA1-018 GEN2
Solar/Wind Harmer
6.801
274682WAUKEGAN ;7U
Adder
19.358
964401AG1-302 GEN
Solar/Wind Harmer
9.749
274872LEEDK;1U
Solar/Wind Harmer
0.273
276805AD2-038 GEN
Solar/Wind Harmer
5.478
276799AD1-013 GEN
Solar/Wind Harmer
2.346
946671AF1-331 GEN
Solar/Wind Harmer
0.444
959141AF2-205 GEN
Solar/Wind Harmer
6.413
274855GSG-6 ;RU
Solar/Wind Harmer
3.917
274850MENDOTA H;RU
Solar/Wind Harmer
2.724
276602WESTBROOK C
Solar/Wind Harmer
2.255
276863AD2-134 GEN
Solar/Wind Harmer
1.894
972236AH1-702 GEN2
Adder
2.303
274760LEE CO EC;1U
Adder
9.662
274767LEE CO EC;8U
Adder
9.549
24721905FLATG4
Adder
19.907
945111AF1-176 GEN
Solar/Wind Harmer
20.364
270063AE2-323 C
Solar/Wind Harmer
2.513
270449AD2-020 GEN
Solar/Wind Harmer
3.183
943021AE2-325 GEN
Solar/Wind Harmer
4.136
972207SS24-0001
Solar/Wind Harmer
24.8
274773LINCOLN ;4U
Adder
6.975
274774LINCOLN ;5U
Adder
6.975
965011AG1-365 GEN
Solar/Wind Harmer
11.187
274723RIVER EC ;12
Adder
19.976
274751CRETE EC ;1U
Adder
5.442
274754CRETE EC ;4U
Adder
5.442
276164X3-005 C
Solar/Wind Harmer
0.781
274812UNIV PK N;8U
Adder
5.552
970373AG2-245 GEN
Solar/Wind Harmer
23.259
276776AD2-060 GEN
Solar/Wind Harmer
0.467
274801UNIV PARK;4U
Adder
6.433
941551AE2-152 GEN
Solar/Wind Harmer
4.986
274676JOLIET 29;8U
Adder
33.648
274674JOLIET 9 ;6U
Adder
16.864
274732ELWOOD EC;7P
Adder
17.991
274871GR RIDGE ;2U
Solar/Wind Harmer
8.406
270055AF2-134 C O1
Solar/Wind Harmer
3.301
274745AC1-111 GEN9
Adder
6.083
276691AA1-018 GEN1
Solar/Wind Harmer
0.502
274682WAUKEGAN ;7U
Adder
19.358
274828WAUKEGAN ;BP
Adder
11.886
958381AF2-132 GEN
Solar/Wind Harmer
9.749
964861AG1-349 GEN
Solar/Wind Harmer
8.434
971917AH1-482 GEN
Solar/Wind Harmer
9.733
960751AF2-366 GEN
Solar/Wind Harmer
3.071
962781AG1-127 GEN
Solar/Wind Harmer
10.181
274872LEEDK;1U
Solar/Wind Harmer
8.777
939401AE1-172 GEN
Solar/Wind Harmer
14.891
276901AD2-066 C O1
Solar/Wind Harmer
3.747
971997AH1-543 GEN
Solar/Wind Harmer
16.729
276861AD2-134 GEN
Solar/Wind Harmer
1.894
274822ROCKFORD ;11
Adder
20.658
972235AH1-702 GEN1
Adder
2.648
274761LEE CO EC;2U
Adder
9.662
274766LEE CO EC;7U
Adder
9.549
24721705FLATG2
Adder
19.907
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.22
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.233
MECLTFEXP_MEC->PJM
CLTF
15.452
SIGELTFEXP_SIGE->PJM
CLTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
11.82
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.928
TVALTFEXP_TVA->PJM
CLTF
5.326
CPLELTFEXP_CPLE->PJM
CLTF
1.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.671
NYPJM->LTFIMP_NY
CLTF
2.826
LGEELTFEXP_LGEE->PJM
CLTF
3.895
WECLTFEXP_WEC->PJM
CLTF
4.009
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.373

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.38 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4908.33
MW Contribution:31.97
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.597
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.08
24642205MAYFLWER
50/50
0.726
274772LINCOLN ;3U
50/50
7.031
970153AG2-106 GEN
Solar/Wind Harmer
38.539
970349AG2-230 GEN
Solar/Wind Harmer
17.182
970513AG2-328 GEN
Solar/Wind Harmer
20.275
970517AG2-330 GEN
Solar/Wind Harmer
18.389
270043AE2-236 GEN
Solar/Wind Harmer
6.17
247643Z2-116 C
Solar/Wind Harmer
0.076
945111AF1-176 GEN
Solar/Wind Harmer
6.059
970031AG2-029 GEN
Solar/Wind Harmer
31.974
944531AF1-118 GEN
Solar/Wind Harmer
37.097
274724RIVER EC ;11
Adder
18.728
972231SS25-0005
Solar/Wind Harmer
10.017
972181SS23-001
Solar/Wind Harmer
6.261
274752CRETE EC ;2U
Adder
5.159
274753CRETE EC ;3U
Adder
5.159
959331AF2-224 GEN
Solar/Wind Harmer
10.534
965021AG1-366 GEN
Solar/Wind Harmer
2.45
970707AG2-453 GEN
Solar/Wind Harmer
29.454
274826FISK ;BP
Adder
11.471
274802UNIV PARK;5U
Adder
6.109
276772AC2-154 GEN
Solar/Wind Harmer
2.92
276806AD2-047 C O1
Solar/Wind Harmer
11.203
970941AG2-585 GEN
Solar/Wind Harmer
13.09
274800UNIV PARK;3U
Adder
6.104
972038AH1-567 GEN2
Adder
0.382
972228AH1-698 GEN2
Adder
3.878
24441205WTRV SLR C
Solar/Wind Harmer
0.141
276897AD1-100 C
Solar/Wind Harmer
30.28
939351AE1-166 GEN
Solar/Wind Harmer
6.187
274676JOLIET 29;8U
Adder
30.792
274729ELWOOD EC;1P
Adder
17.074
274730ELWOOD EC;6P
Adder
17.074
274734ELWOOD EC;8P
Adder
17.074
274736ELWOOD EC;9P
Adder
17.074
276893AG1-478 C
Solar/Wind Harmer
0.434
943121AE2-341 GEN
Solar/Wind Harmer
15.521
943591AF1-030 GEN
Solar/Wind Harmer
10.347
247604X1-042
Adder
0.431
270535AF1-215 GEN1
Solar/Wind Harmer
4.686
276694AA1-018 GEN2
Solar/Wind Harmer
6.453
274682WAUKEGAN ;7U
Adder
18.372
964401AG1-302 GEN
Solar/Wind Harmer
9.225
274872LEEDK;1U
Solar/Wind Harmer
0.259
276805AD2-038 GEN
Solar/Wind Harmer
5.197
276799AD1-013 GEN
Solar/Wind Harmer
2.226
946671AF1-331 GEN
Solar/Wind Harmer
0.422
274855GSG-6 ;RU
Solar/Wind Harmer
3.717
274850MENDOTA H;RU
Solar/Wind Harmer
2.585
276602WESTBROOK C
Solar/Wind Harmer
2.14
276863AD2-134 GEN
Solar/Wind Harmer
1.798
959141AF2-205 GEN
Solar/Wind Harmer
6.07
972236AH1-702 GEN2
Adder
2.185
274760LEE CO EC;1U
Adder
9.168
274767LEE CO EC;8U
Adder
9.06
24721905FLATG4
Adder
19.59
959091AF2-200 GEN
Solar/Wind Harmer
0.641
24344105CKG2
50/50
8.921
270143AC1-141 CT2_
50/50
2.597
24639705ELKHART HY
50/50
0.175
970521AG2-332 GEN
50/50
12.491
274773LINCOLN ;4U
50/50
7.031
274774LINCOLN ;5U
50/50
7.031
962761AG1-125 GEN
Solar/Wind Harmer
88.384
970149AG2-104 GEN
Solar/Wind Harmer
109.154
970155AG2-107 GEN
Solar/Wind Harmer
38.539
970245AG2-165 GEN
Solar/Wind Harmer
20.275
270505AE1-170 C O1
Solar/Wind Harmer
16.131
270063AE2-323 C
Solar/Wind Harmer
2.365
945111AF1-176 GEN
Solar/Wind Harmer
19.119
972207SS24-0001
Solar/Wind Harmer
23.558
270449AD2-020 GEN
Solar/Wind Harmer
2.984
943021AE2-325 GEN
Solar/Wind Harmer
3.877
274723RIVER EC ;12
Adder
18.946
274751CRETE EC ;1U
Adder
5.159
274754CRETE EC ;4U
Adder
5.159
276164X3-005 C
Solar/Wind Harmer
0.741
965011AG1-365 GEN
Solar/Wind Harmer
10.534
274812UNIV PK N;8U
Adder
5.266
970373AG2-245 GEN
Solar/Wind Harmer
22.001
276776AD2-060 GEN
Solar/Wind Harmer
0.443
274801UNIV PARK;4U
Adder
6.104
941551AE2-152 GEN
Solar/Wind Harmer
4.732
274676JOLIET 29;8U
Adder
31.933
274674JOLIET 9 ;6U
Adder
16.004
274732ELWOOD EC;7P
Adder
17.074
274871GR RIDGE ;2U
Solar/Wind Harmer
7.979
274745AC1-111 GEN9
Adder
5.774
270055AF2-134 C O1
Solar/Wind Harmer
3.123
276691AA1-018 GEN1
Solar/Wind Harmer
0.476
274682WAUKEGAN ;7U
Adder
18.372
274828WAUKEGAN ;BP
Adder
11.281
958381AF2-132 GEN
Solar/Wind Harmer
9.225
960751AF2-366 GEN
Solar/Wind Harmer
2.915
962781AG1-127 GEN
Solar/Wind Harmer
9.663
964861AG1-349 GEN
Solar/Wind Harmer
7.981
971917AH1-482 GEN
Solar/Wind Harmer
9.21
274872LEEDK;1U
Solar/Wind Harmer
8.331
939401AE1-172 GEN
Solar/Wind Harmer
14.131
276901AD2-066 C O1
Solar/Wind Harmer
3.555
971997AH1-543 GEN
Solar/Wind Harmer
15.875
276861AD2-134 GEN
Solar/Wind Harmer
1.798
274822ROCKFORD ;11
Adder
19.604
972235AH1-702 GEN1
Adder
2.513
274761LEE CO EC;2U
Adder
9.168
274766LEE CO EC;7U
Adder
9.06
24721705FLATG2
Adder
19.59
957471AF2-041 GEN
Solar/Wind Harmer
0.961
959081AF2-199 GEN
Solar/Wind Harmer
0.32
971067AG2-660 GEN
Solar/Wind Harmer
0.075
971599AH1-298 GEN
50/50
10.537
270144AC1-141 ST1_
50/50
2.301
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.031
274776LINCOLN ;7U
50/50
7.031
274777LINCOLN ;8U
50/50
7.031
962771AG1-126 GEN
Solar/Wind Harmer
88.384
971347AH1-153 GEN
Solar/Wind Harmer
17.182
270071AF1-092 GEN
Solar/Wind Harmer
16.471
971771AH1-392 GEN
Solar/Wind Harmer
9.787
960681AF2-359 GEN
Solar/Wind Harmer
4.098
971769AH1-391 GEN
Solar/Wind Harmer
10.814
944161AF1-084 GEN
Solar/Wind Harmer
2.339
274814UNIV PK N;0U
Adder
5.312
274807UNIV PK N;3U
Adder
5.3
274805UNIV PK N;1U
Adder
5.277
274811UNIV PK N;7U
Adder
5.266
274827FISK ;RP
Adder
8.13
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
10.472
972227AH1-698 GEN1
Adder
2.73
274687WILL CNTY;4U
Adder
29.107
274687WILL CNTY;4U
Adder
29.107
274675JOLIET 29;7U
Adder
31.933
274675JOLIET 29;7U
Adder
30.793
24729505KEY G4
Adder
6.744
274731ELWOOD EC;2P
Adder
17.074
274733ELWOOD EC;3P
Adder
17.074
274735ELWOOD EC;4P
Adder
17.074
274728ELWOOD EC;5P
Adder
17.074
970833AG2-524 GEN
Solar/Wind Harmer
9.062
970833AG2-524 GEN
Solar/Wind Harmer
4.215
274746AC1-111 G10
Adder
5.774
274744AC1-111 GEN8
Adder
5.774
270536AF1-215 GEN2
Solar/Wind Harmer
4.686
971177AH1-047 GEN
Solar/Wind Harmer
5.918
958391AF2-133 GEN
Solar/Wind Harmer
9.158
276868AE1-113 GEN
Solar/Wind Harmer
10.216
276882AE2-255 GEN
Solar/Wind Harmer
3.406
971675AH1-338 GEN
Solar/Wind Harmer
18.12
971411AH1-196 GEN
Solar/Wind Harmer
15.1
274863CRW1-WTG
Solar/Wind Harmer
5.594
274864CRW2-WTG
Solar/Wind Harmer
5.594
274823ROCKFORD ;21
Adder
19.462
270054AF2-122 C O1
Solar/Wind Helper
1.653
971171AH1-044 GEN
Solar/Wind Harmer
0.641
270102X2-052 ST
50/50
1.744
270100X2-052 CT1
50/50
1.606
270101X2-052 CT2
50/50
1.606
247620Y3-023
50/50
0.524
274770LINCOLN ;1U
50/50
7.031
274771LINCOLN ;2U
50/50
7.031
970321AG2-212 GEN
Solar/Wind Harmer
20.275
270216AD2-079_GEN
Solar/Wind Harmer
0.658
965681AG1-436 GEN
Solar/Wind Harmer
13.559
965791AG1-447 GEN
Solar/Wind Harmer
6.937
270526AF1-158 GEN
Solar/Wind Harmer
4.919
24441505OLIV SLR
Solar/Wind Harmer
0.145
957891AF2-083 GEN
Solar/Wind Harmer
3.624
960981AF2-389 GEN
Solar/Wind Harmer
1.624
961051AF2-396 GEN
Solar/Wind Harmer
16.938
961051AF2-396 GEN
Solar/Wind Harmer
7.878
970611AG2-400 GEN
Solar/Wind Harmer
10.534
274808UNIV PK N;4U
Adder
5.243
972259AH1-714 GEN
Adder
19.997
274803UNIV PARK;6U
Adder
6.109
274888KELLY CRK;1U
Solar/Wind Harmer
6.183
274887GEN-1.85
Solar/Wind Harmer
5.582
276843GEN-1.7
Solar/Wind Harmer
0.601
958011AF2-095 GEN
Solar/Wind Harmer
15.08
274674JOLIET 9 ;6U
Adder
16.004
274847GR RIDGE ;BU
Solar/Wind Harmer
5.248
971573AH1-285 GEN
Solar/Wind Harmer
8.859
274696ROCKY RD ;4P
Adder
11.666
274695ROCKY RD ;2P
Adder
11.398
274693ROCKY RD ;1P
Adder
11.285
274697ROCKY RD ;3P
Adder
3.096
958481AF2-142 GEN
Solar/Wind Harmer
15.339
274861TOP CROP ;1U
Solar/Wind Harmer
6.194
274862TOP CROP ;2U
Solar/Wind Harmer
5.172
274683WAUKEGAN ;8U
Adder
21.521
274683WAUKEGAN ;8U
Adder
18.141
962691AG1-118 GEN
Solar/Wind Harmer
30.542
970921AG2-575 GEN
Solar/Wind Harmer
10.161
970921AG2-575 GEN
Solar/Wind Harmer
2.363
958491AF2-143 GEN
Solar/Wind Harmer
15.196
942991AE2-321 GEN
Solar/Wind Harmer
10.102
274879MINONK ;1U
Solar/Wind Harmer
6.812
971333AH1-146 GEN
Solar/Wind Harmer
20.122
971335AH1-147 GEN
Solar/Wind Harmer
20.122
274764LEE CO EC;5U
Adder
9.19
274765LEE CO EC;6U
Adder
9.19
274762LEE CO EC;3U
Adder
9.168
274763LEE CO EC;4U
Adder
9.082
972267AH1-718 GEN
Adder
4.072
971341AH1-150 GEN
Solar/Wind Harmer
0.641
971343AH1-151 GEN
Solar/Wind Harmer
0.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
119.66
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.096
MECLTFEXP_MEC->PJM
CLTF
14.649
SIGELTFEXP_SIGE->PJM
CLTF
0.337
LAGNLTFEXP_LAGN->PJM
CLTF
11.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.594
TVALTFEXP_TVA->PJM
CLTF
5.037
CPLELTFEXP_CPLE->PJM
CLTF
1.403
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.692
NYPJM->LTFIMP_NY
CLTF
2.605
LGEELTFEXP_LGEE->PJM
CLTF
3.642
WECLTFEXP_WEC->PJM
CLTF
3.804
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.354

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT5_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT5_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.67 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4875.89
MW Contribution:31.99
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.598
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.083
24642205MAYFLWER
50/50
0.727
274772LINCOLN ;3U
50/50
7.034
970153AG2-106 GEN
Solar/Wind Harmer
38.546
970349AG2-230 GEN
Solar/Wind Harmer
17.189
970513AG2-328 GEN
Solar/Wind Harmer
20.283
970517AG2-330 GEN
Solar/Wind Harmer
18.396
270043AE2-236 GEN
Solar/Wind Harmer
6.172
247643Z2-116 C
Solar/Wind Harmer
0.076
945111AF1-176 GEN
Solar/Wind Harmer
6.062
970031AG2-029 GEN
Solar/Wind Harmer
31.987
944531AF1-118 GEN
Solar/Wind Harmer
37.113
274724RIVER EC ;11
Adder
18.735
972231SS25-0005
Solar/Wind Harmer
10.021
972181SS23-001
Solar/Wind Harmer
6.263
274752CRETE EC ;2U
Adder
5.161
274753CRETE EC ;3U
Adder
5.161
959331AF2-224 GEN
Solar/Wind Harmer
10.538
965021AG1-366 GEN
Solar/Wind Harmer
2.451
970707AG2-453 GEN
Solar/Wind Harmer
29.466
274826FISK ;BP
Adder
11.476
274802UNIV PARK;5U
Adder
6.111
276772AC2-154 GEN
Solar/Wind Harmer
2.922
276806AD2-047 C O1
Solar/Wind Harmer
11.207
970941AG2-585 GEN
Solar/Wind Harmer
13.095
274800UNIV PARK;3U
Adder
6.107
972038AH1-567 GEN2
Adder
0.382
972228AH1-698 GEN2
Adder
3.879
24441205WTRV SLR C
Solar/Wind Harmer
0.141
276897AD1-100 C
Solar/Wind Harmer
30.293
939351AE1-166 GEN
Solar/Wind Harmer
6.19
274676JOLIET 29;8U
Adder
30.805
274729ELWOOD EC;1P
Adder
17.081
274730ELWOOD EC;6P
Adder
17.081
274734ELWOOD EC;8P
Adder
17.081
274736ELWOOD EC;9P
Adder
17.081
276893AG1-478 C
Solar/Wind Harmer
0.434
943121AE2-341 GEN
Solar/Wind Harmer
15.527
943591AF1-030 GEN
Solar/Wind Harmer
10.352
247604X1-042
Adder
0.431
270535AF1-215 GEN1
Solar/Wind Harmer
4.688
276694AA1-018 GEN2
Solar/Wind Harmer
6.456
274682WAUKEGAN ;7U
Adder
18.38
964401AG1-302 GEN
Solar/Wind Harmer
9.229
274872LEEDK;1U
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
5.199
276799AD1-013 GEN
Solar/Wind Harmer
2.227
946671AF1-331 GEN
Solar/Wind Harmer
0.422
274855GSG-6 ;RU
Solar/Wind Harmer
3.719
274850MENDOTA H;RU
Solar/Wind Harmer
2.586
276602WESTBROOK C
Solar/Wind Harmer
2.141
276863AD2-134 GEN
Solar/Wind Harmer
1.799
959141AF2-205 GEN
Solar/Wind Harmer
6.072
972236AH1-702 GEN2
Adder
2.186
274760LEE CO EC;1U
Adder
9.172
274767LEE CO EC;8U
Adder
9.064
24721905FLATG4
Adder
19.599
959091AF2-200 GEN
Solar/Wind Harmer
0.641
24344105CKG2
50/50
8.924
270143AC1-141 CT2_
50/50
2.598
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.496
274773LINCOLN ;4U
50/50
7.034
274774LINCOLN ;5U
50/50
7.034
962761AG1-125 GEN
Solar/Wind Harmer
88.398
970149AG2-104 GEN
Solar/Wind Harmer
109.171
970155AG2-107 GEN
Solar/Wind Harmer
38.546
970245AG2-165 GEN
Solar/Wind Harmer
20.283
270505AE1-170 C O1
Solar/Wind Harmer
16.137
270063AE2-323 C
Solar/Wind Harmer
2.366
945111AF1-176 GEN
Solar/Wind Harmer
19.127
972207SS24-0001
Solar/Wind Harmer
23.568
270449AD2-020 GEN
Solar/Wind Harmer
2.985
943021AE2-325 GEN
Solar/Wind Harmer
3.878
274723RIVER EC ;12
Adder
18.954
274751CRETE EC ;1U
Adder
5.161
274754CRETE EC ;4U
Adder
5.161
276164X3-005 C
Solar/Wind Harmer
0.741
965011AG1-365 GEN
Solar/Wind Harmer
10.538
274812UNIV PK N;8U
Adder
5.268
970373AG2-245 GEN
Solar/Wind Harmer
22.01
276776AD2-060 GEN
Solar/Wind Harmer
0.443
274801UNIV PARK;4U
Adder
6.107
941551AE2-152 GEN
Solar/Wind Harmer
4.734
274676JOLIET 29;8U
Adder
31.946
274674JOLIET 9 ;6U
Adder
16.011
274732ELWOOD EC;7P
Adder
17.081
274871GR RIDGE ;2U
Solar/Wind Harmer
7.982
274745AC1-111 GEN9
Adder
5.777
270055AF2-134 C O1
Solar/Wind Harmer
3.125
276691AA1-018 GEN1
Solar/Wind Harmer
0.476
274682WAUKEGAN ;7U
Adder
18.38
274828WAUKEGAN ;BP
Adder
11.285
958381AF2-132 GEN
Solar/Wind Harmer
9.229
960751AF2-366 GEN
Solar/Wind Harmer
2.916
962781AG1-127 GEN
Solar/Wind Harmer
9.667
964861AG1-349 GEN
Solar/Wind Harmer
7.985
971917AH1-482 GEN
Solar/Wind Harmer
9.214
274872LEEDK;1U
Solar/Wind Harmer
8.334
939401AE1-172 GEN
Solar/Wind Harmer
14.137
276901AD2-066 C O1
Solar/Wind Harmer
3.557
971997AH1-543 GEN
Solar/Wind Harmer
15.882
276861AD2-134 GEN
Solar/Wind Harmer
1.799
274822ROCKFORD ;11
Adder
19.613
972235AH1-702 GEN1
Adder
2.514
274761LEE CO EC;2U
Adder
9.172
274766LEE CO EC;7U
Adder
9.064
24721705FLATG2
Adder
19.599
957471AF2-041 GEN
Solar/Wind Harmer
0.961
959081AF2-199 GEN
Solar/Wind Harmer
0.32
971067AG2-660 GEN
Solar/Wind Harmer
0.075
971599AH1-298 GEN
50/50
10.541
270144AC1-141 ST1_
50/50
2.302
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.034
274776LINCOLN ;7U
50/50
7.034
274777LINCOLN ;8U
50/50
7.034
962771AG1-126 GEN
Solar/Wind Harmer
88.398
971347AH1-153 GEN
Solar/Wind Harmer
17.189
270071AF1-092 GEN
Solar/Wind Harmer
16.478
971771AH1-392 GEN
Solar/Wind Harmer
9.791
960681AF2-359 GEN
Solar/Wind Harmer
4.1
971769AH1-391 GEN
Solar/Wind Harmer
10.819
944161AF1-084 GEN
Solar/Wind Harmer
2.34
274814UNIV PK N;0U
Adder
5.314
274807UNIV PK N;3U
Adder
5.303
274805UNIV PK N;1U
Adder
5.28
274811UNIV PK N;7U
Adder
5.268
274827FISK ;RP
Adder
8.133
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
10.476
972227AH1-698 GEN1
Adder
2.731
274687WILL CNTY;4U
Adder
29.119
274687WILL CNTY;4U
Adder
29.119
274675JOLIET 29;7U
Adder
31.946
274675JOLIET 29;7U
Adder
30.805
24729505KEY G4
Adder
6.746
274731ELWOOD EC;2P
Adder
17.081
274733ELWOOD EC;3P
Adder
17.081
274735ELWOOD EC;4P
Adder
17.081
274728ELWOOD EC;5P
Adder
17.081
970833AG2-524 GEN
Solar/Wind Harmer
9.066
970833AG2-524 GEN
Solar/Wind Harmer
4.217
274746AC1-111 G10
Adder
5.777
274744AC1-111 GEN8
Adder
5.777
270536AF1-215 GEN2
Solar/Wind Harmer
4.688
971177AH1-047 GEN
Solar/Wind Harmer
5.92
958391AF2-133 GEN
Solar/Wind Harmer
9.162
276868AE1-113 GEN
Solar/Wind Harmer
10.221
276882AE2-255 GEN
Solar/Wind Harmer
3.407
971675AH1-338 GEN
Solar/Wind Harmer
18.128
971411AH1-196 GEN
Solar/Wind Harmer
15.106
274863CRW1-WTG
Solar/Wind Harmer
5.597
274864CRW2-WTG
Solar/Wind Harmer
5.597
274823ROCKFORD ;21
Adder
19.47
270054AF2-122 C O1
Solar/Wind Helper
1.652
971171AH1-044 GEN
Solar/Wind Harmer
0.641
270102X2-052 ST
50/50
1.744
270100X2-052 CT1
50/50
1.607
270101X2-052 CT2
50/50
1.607
247620Y3-023
50/50
0.524
274770LINCOLN ;1U
50/50
7.034
274771LINCOLN ;2U
50/50
7.034
970321AG2-212 GEN
Solar/Wind Harmer
20.283
270216AD2-079_GEN
Solar/Wind Harmer
0.658
965681AG1-436 GEN
Solar/Wind Harmer
13.565
965791AG1-447 GEN
Solar/Wind Harmer
6.94
270526AF1-158 GEN
Solar/Wind Harmer
4.921
24441505OLIV SLR
Solar/Wind Harmer
0.145
957891AF2-083 GEN
Solar/Wind Harmer
3.625
960981AF2-389 GEN
Solar/Wind Harmer
1.624
961051AF2-396 GEN
Solar/Wind Harmer
16.945
961051AF2-396 GEN
Solar/Wind Harmer
7.882
970611AG2-400 GEN
Solar/Wind Harmer
10.538
274808UNIV PK N;4U
Adder
5.245
972259AH1-714 GEN
Adder
20.005
274803UNIV PARK;6U
Adder
6.111
274888KELLY CRK;1U
Solar/Wind Harmer
6.185
274887GEN-1.85
Solar/Wind Harmer
5.584
276843GEN-1.7
Solar/Wind Harmer
0.601
958011AF2-095 GEN
Solar/Wind Harmer
15.086
274674JOLIET 9 ;6U
Adder
16.011
274847GR RIDGE ;BU
Solar/Wind Harmer
5.251
971573AH1-285 GEN
Solar/Wind Harmer
8.863
274696ROCKY RD ;4P
Adder
11.671
274695ROCKY RD ;2P
Adder
11.402
274693ROCKY RD ;1P
Adder
11.29
274697ROCKY RD ;3P
Adder
3.097
958481AF2-142 GEN
Solar/Wind Harmer
15.345
274861TOP CROP ;1U
Solar/Wind Harmer
6.196
274862TOP CROP ;2U
Solar/Wind Harmer
5.174
274683WAUKEGAN ;8U
Adder
21.53
274683WAUKEGAN ;8U
Adder
18.148
962691AG1-118 GEN
Solar/Wind Harmer
30.555
970921AG2-575 GEN
Solar/Wind Harmer
10.165
970921AG2-575 GEN
Solar/Wind Harmer
2.364
958491AF2-143 GEN
Solar/Wind Harmer
15.202
942991AE2-321 GEN
Solar/Wind Harmer
10.106
274879MINONK ;1U
Solar/Wind Harmer
6.815
971333AH1-146 GEN
Solar/Wind Harmer
20.131
971335AH1-147 GEN
Solar/Wind Harmer
20.131
274764LEE CO EC;5U
Adder
9.194
274765LEE CO EC;6U
Adder
9.194
274762LEE CO EC;3U
Adder
9.172
274763LEE CO EC;4U
Adder
9.086
972267AH1-718 GEN
Adder
4.074
971341AH1-150 GEN
Solar/Wind Harmer
0.641
971343AH1-151 GEN
Solar/Wind Harmer
0.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
119.724
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.112
MECLTFEXP_MEC->PJM
CLTF
14.656
SIGELTFEXP_SIGE->PJM
CLTF
0.337
LAGNLTFEXP_LAGN->PJM
CLTF
11.198
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.608
TVALTFEXP_TVA->PJM
CLTF
5.042
CPLELTFEXP_CPLE->PJM
CLTF
1.407
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.75
NYPJM->LTFIMP_NY
CLTF
2.602
LGEELTFEXP_LGEE->PJM
CLTF
3.645
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.354

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.87 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6911.8
MW Contribution:62.69
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.827
270144AC1-141 ST1_
50/50
4.726
24643105BUCHANAN
50/50
0.028
274775LINCOLN ;6U
50/50
14.464
274776LINCOLN ;7U
50/50
14.464
274777LINCOLN ;8U
50/50
14.464
971347AH1-153 GEN
Solar/Wind Harmer
35.693
960681AF2-359 GEN
Solar/Wind Harmer
8.494
971771AH1-392 GEN
Solar/Wind Harmer
20.116
971769AH1-391 GEN
Solar/Wind Harmer
22.322
270071AF1-092 GEN
Solar/Wind Harmer
32.714
944161AF1-084 GEN
Solar/Wind Harmer
4.796
270536AF1-215 GEN2
Solar/Wind Harmer
9.847
274814UNIV PK N;0U
Adder
10.897
274807UNIV PK N;3U
Adder
10.873
274805UNIV PK N;1U
Adder
10.826
274811UNIV PK N;7U
Adder
10.802
972037AH1-567 GEN1
Adder
0.393
274827FISK ;RP
Adder
16.653
960591AF2-350 GEN
Solar/Wind Harmer
21.457
972227AH1-698 GEN1
Adder
5.595
958391AF2-133 GEN
Solar/Wind Harmer
19.344
274687WILL CNTY;4U
Adder
59.525
274687WILL CNTY;4U
Adder
59.525
274675JOLIET 29;7U
Adder
65.285
274675JOLIET 29;7U
Adder
62.954
274731ELWOOD EC;2P
Adder
34.908
274733ELWOOD EC;3P
Adder
34.908
274735ELWOOD EC;4P
Adder
34.908
274728ELWOOD EC;5P
Adder
34.908
970833AG2-524 GEN
Solar/Wind Harmer
18.525
970833AG2-524 GEN
Solar/Wind Harmer
8.616
274746AC1-111 G10
Adder
11.776
274744AC1-111 GEN8
Adder
11.776
24690905MDL-1G C
Solar/Wind Harmer
16.46
270180AB1-006 GEN1
Solar/Wind Harmer
14.745
946581AF1-322 GEN
Solar/Wind Harmer
20.975
24691005MDL-2G C
Solar/Wind Harmer
7.582
24697605MDL-3G C
Solar/Wind Harmer
7.558
24697905MDL-4G C
Solar/Wind Harmer
4.705
270181AB1-006 GEN2
Solar/Wind Harmer
1.466
276868AE1-113 GEN
Solar/Wind Harmer
20.743
276882AE2-255 GEN
Solar/Wind Harmer
6.915
971177AH1-047 GEN
Solar/Wind Harmer
11.982
274863CRW1-WTG
Solar/Wind Harmer
11.396
274864CRW2-WTG
Solar/Wind Harmer
11.396
971675AH1-338 GEN
Solar/Wind Harmer
36.661
971411AH1-196 GEN
Solar/Wind Harmer
30.544
274823ROCKFORD ;21
Adder
39.271
24729505KEY G4
Adder
12.781
270054AF2-122 C O1
Solar/Wind Helper
1.198
971171AH1-044 GEN
Solar/Wind Harmer
0.703
24344105CKG2
50/50
18.684
270143AC1-141 CT2_
50/50
5.336
274773LINCOLN ;4U
50/50
14.464
274774LINCOLN ;5U
50/50
14.464
24639705ELKHART HY
50/50
0.356
970245AG2-165 GEN
Solar/Wind Harmer
43.637
270505AE1-170 C O1
Solar/Wind Harmer
33.093
972207SS24-0001
Solar/Wind Harmer
48.463
970373AG2-245 GEN
Solar/Wind Harmer
46.063
945111AF1-176 GEN
Solar/Wind Harmer
39.1
270449AD2-020 GEN
Solar/Wind Harmer
6.117
943021AE2-325 GEN
Solar/Wind Harmer
7.949
274723RIVER EC ;12
Adder
38.895
274751CRETE EC ;1U
Adder
10.596
274754CRETE EC ;4U
Adder
10.596
270055AF2-134 C O1
Solar/Wind Harmer
6.564
276164X3-005 C
Solar/Wind Harmer
1.52
274812UNIV PK N;8U
Adder
10.802
276776AD2-060 GEN
Solar/Wind Harmer
0.907
274801UNIV PARK;4U
Adder
12.503
958381AF2-132 GEN
Solar/Wind Harmer
19.452
964861AG1-349 GEN
Solar/Wind Harmer
16.835
971917AH1-482 GEN
Solar/Wind Harmer
19.427
941551AE2-152 GEN
Solar/Wind Harmer
9.695
274676JOLIET 29;8U
Adder
65.284
274674JOLIET 9 ;6U
Adder
32.718
274732ELWOOD EC;7P
Adder
34.908
270063AE2-323 C
Solar/Wind Harmer
4.678
274871GR RIDGE ;2U
Solar/Wind Harmer
16.309
940581AE2-045 GEN
Solar/Wind Harmer
21.545
971605AH1-302 GEN
Solar/Wind Harmer
18.424
274745AC1-111 GEN9
Adder
11.776
970333AG2-219 GEN
Solar/Wind Harmer
65.98
276691AA1-018 GEN1
Solar/Wind Harmer
0.97
274682WAUKEGAN ;7U
Adder
37.343
274828WAUKEGAN ;BP
Adder
22.921
939401AE1-172 GEN
Solar/Wind Harmer
28.837
960751AF2-366 GEN
Solar/Wind Harmer
5.914
962781AG1-127 GEN
Solar/Wind Harmer
19.604
276901AD2-066 C O1
Solar/Wind Harmer
7.228
274872LEEDK;1U
Solar/Wind Harmer
16.893
24791305MDL-5G
Solar/Wind Harmer
4.944
971997AH1-543 GEN
Solar/Wind Harmer
32.241
276861AD2-134 GEN
Solar/Wind Harmer
3.637
276876AE1-163_GEN2
Solar/Wind Harmer
13.606
274822ROCKFORD ;11
Adder
39.558
972235AH1-702 GEN1
Adder
5.068
274761LEE CO EC;2U
Adder
18.426
274766LEE CO EC;7U
Adder
18.209
970091AG2-072 GEN
Adder
143.374
270349AD2-093_GEN
Solar/Wind Helper
1.574
957471AF2-041 GEN
Solar/Wind Harmer
1.055
959081AF2-199 GEN
Solar/Wind Harmer
0.352
971067AG2-660 GEN
Solar/Wind Harmer
0.082
270102X2-052 ST
50/50
3.618
270100X2-052 CT1
50/50
3.334
270101X2-052 CT2
50/50
3.334
274770LINCOLN ;1U
50/50
14.464
274771LINCOLN ;2U
50/50
14.464
970321AG2-212 GEN
Solar/Wind Harmer
43.637
965681AG1-436 GEN
Solar/Wind Harmer
28.105
965791AG1-447 GEN
Solar/Wind Harmer
14.379
270526AF1-158 GEN
Solar/Wind Harmer
10.145
24441505OLIV SLR
Solar/Wind Harmer
0.299
270216AD2-079_GEN
Solar/Wind Harmer
1.343
957891AF2-083 GEN
Solar/Wind Harmer
7.428
960981AF2-389 GEN
Solar/Wind Harmer
3.328
961051AF2-396 GEN
Solar/Wind Harmer
34.696
961051AF2-396 GEN
Solar/Wind Harmer
16.138
247620Y3-023
Adder
0.995
274808UNIV PK N;4U
Adder
10.755
972259AH1-714 GEN
Adder
40.962
274803UNIV PARK;6U
Adder
12.517
274888KELLY CRK;1U
Solar/Wind Harmer
12.668
274887GEN-1.85
Solar/Wind Harmer
11.437
276843GEN-1.7
Solar/Wind Harmer
1.231
958011AF2-095 GEN
Solar/Wind Harmer
30.899
274674JOLIET 9 ;6U
Adder
32.718
274847GR RIDGE ;BU
Solar/Wind Harmer
10.728
971573AH1-285 GEN
Solar/Wind Harmer
18.045
970239AG2-162 GEN
Solar/Wind Harmer
22.993
958481AF2-142 GEN
Solar/Wind Harmer
31.243
945421AF1-207 GEN
Solar/Wind Harmer
29.246
957841AF2-078 GEN
Solar/Wind Harmer
12.586
274695ROCKY RD ;2P
Adder
23.176
274693ROCKY RD ;1P
Adder
22.948
274697ROCKY RD ;3P
Adder
6.296
274861TOP CROP ;1U
Solar/Wind Harmer
12.614
274862TOP CROP ;2U
Solar/Wind Harmer
10.533
274696ROCKY RD ;4P
Adder
23.723
274683WAUKEGAN ;8U
Adder
43.726
274683WAUKEGAN ;8U
Adder
36.859
962691AG1-118 GEN
Solar/Wind Harmer
61.999
970921AG2-575 GEN
Solar/Wind Harmer
20.614
970921AG2-575 GEN
Solar/Wind Harmer
4.794
958491AF2-143 GEN
Solar/Wind Harmer
30.883
274879MINONK ;1U
Solar/Wind Harmer
13.83
942991AE2-321 GEN
Solar/Wind Harmer
20.456
971333AH1-146 GEN
Solar/Wind Harmer
40.697
971335AH1-147 GEN
Solar/Wind Harmer
40.697
276872AE1-163_GEN1
Solar/Wind Harmer
13.606
274764LEE CO EC;5U
Adder
18.47
274765LEE CO EC;6U
Adder
18.47
274762LEE CO EC;3U
Adder
18.426
274763LEE CO EC;4U
Adder
18.253
972267AH1-718 GEN
Adder
8.164
270471AD2-092_GEN
Solar/Wind Helper
1.574
971341AH1-150 GEN
Solar/Wind Harmer
0.703
971343AH1-151 GEN
Solar/Wind Harmer
0.703
24344005CKG1
50/50
14.627
270142AC1-141 CT1_
50/50
5.336
24641605TWIN BRNCH
50/50
0.039
24642205MAYFLWER
50/50
1.492
274772LINCOLN ;3U
50/50
14.464
970513AG2-328 GEN
Solar/Wind Harmer
43.637
970517AG2-330 GEN
Solar/Wind Harmer
39.578
970349AG2-230 GEN
Solar/Wind Harmer
35.693
247643Z2-116 C
Solar/Wind Harmer
0.155
270043AE2-236 GEN
Solar/Wind Harmer
12.097
945111AF1-176 GEN
Solar/Wind Harmer
12.392
274724RIVER EC ;11
Adder
38.445
972231SS25-0005
Solar/Wind Harmer
20.573
972181SS23-001
Solar/Wind Harmer
12.858
274752CRETE EC ;2U
Adder
10.596
274753CRETE EC ;3U
Adder
10.596
270535AF1-215 GEN1
Solar/Wind Harmer
9.847
970707AG2-453 GEN
Solar/Wind Harmer
60.348
274802UNIV PARK;5U
Adder
12.517
274826FISK ;BP
Adder
23.497
276772AC2-154 GEN
Solar/Wind Harmer
5.984
276806AD2-047 C O1
Solar/Wind Harmer
22.954
970941AG2-585 GEN
Solar/Wind Harmer
26.822
972228AH1-698 GEN2
Adder
7.946
274800UNIV PARK;3U
Adder
12.503
972038AH1-567 GEN2
Adder
0.783
24441205WTRV SLR C
Solar/Wind Harmer
0.289
964401AG1-302 GEN
Solar/Wind Harmer
19.452
276897AD1-100 C
Solar/Wind Harmer
62.038
939351AE1-166 GEN
Solar/Wind Harmer
12.676
274676JOLIET 29;8U
Adder
62.953
247604X1-042
Adder
0.885
274729ELWOOD EC;1P
Adder
34.908
274730ELWOOD EC;6P
Adder
34.908
274734ELWOOD EC;8P
Adder
34.908
274736ELWOOD EC;9P
Adder
34.908
959141AF2-205 GEN
Solar/Wind Harmer
12.838
276893AG1-478 C
Solar/Wind Harmer
0.886
943121AE2-341 GEN
Solar/Wind Harmer
31.655
943591AF1-030 GEN
Solar/Wind Harmer
21.103
970243AG2-164 GEN
Solar/Wind Harmer
53.983
970519AG2-331 GEN
Solar/Wind Harmer
36.268
970699AG2-449 GEN
Solar/Wind Harmer
23.993
970031AG2-029 GEN
Solar/Wind Harmer
62.689
276694AA1-018 GEN2
Solar/Wind Harmer
13.144
274682WAUKEGAN ;7U
Adder
37.343
276805AD2-038 GEN
Solar/Wind Harmer
10.562
274872LEEDK;1U
Solar/Wind Harmer
0.526
24755605MDL-5G
Solar/Wind Harmer
4.944
970781AG2-491 GEN
Solar/Wind Harmer
20.497
276799AD1-013 GEN
Solar/Wind Harmer
4.505
946671AF1-331 GEN
Solar/Wind Harmer
0.853
274855GSG-6 ;RU
Solar/Wind Harmer
7.52
274850MENDOTA H;RU
Solar/Wind Harmer
5.229
276602WESTBROOK C
Solar/Wind Harmer
4.329
276863AD2-134 GEN
Solar/Wind Harmer
3.637
276889AE2-281 GEN
Solar/Wind Harmer
3.888
972236AH1-702 GEN2
Adder
4.407
274760LEE CO EC;1U
Adder
18.426
274767LEE CO EC;8U
Adder
18.209
959091AF2-200 GEN
Solar/Wind Harmer
0.703
944201AF1-088_MTX
Adder
194.417
957141AF2-008_MTX
Adder
28.027
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.655
CBM West 1LTFEXP_CBM-W1->PJM
CBM
232.718
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.494
MECLTFEXP_MEC->PJM
CLTF
27.999
SIGELTFEXP_SIGE->PJM
CLTF
0.538
LAGNLTFEXP_LAGN->PJM
CLTF
14.568
TVALTFEXP_TVA->PJM
CLTF
5.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
137.493
NYPJM->LTFIMP_NY
CLTF
3.58
LGEELTFEXP_LGEE->PJM
CLTF
4.109
WECLTFEXP_WEC->PJM
CLTF
7.66
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.418
AG2-052LTFEXP_AG2-052->PJM
LTF
0.484
AH1-155LTFEXP_AH1-155->PJM
LTF
0.727

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.24 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6388.47
MW Contribution:62.78
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.606
270100X2-052 CT1
50/50
3.322
270101X2-052 CT2
50/50
3.322
970321AG2-212 GEN
Solar/Wind Harmer
44.073
970239AG2-162 GEN
Solar/Wind Harmer
24.863
965681AG1-436 GEN
Solar/Wind Harmer
27.976
965791AG1-447 GEN
Solar/Wind Harmer
14.313
270526AF1-158 GEN
Solar/Wind Harmer
10.118
24441505OLIV SLR
Solar/Wind Harmer
0.298
270216AD2-079_GEN
Solar/Wind Harmer
1.344
957891AF2-083 GEN
Solar/Wind Harmer
7.429
960981AF2-389 GEN
Solar/Wind Harmer
3.328
961051AF2-396 GEN
Solar/Wind Harmer
34.708
961051AF2-396 GEN
Solar/Wind Harmer
16.143
274770LINCOLN ;1U
Adder
13.446
274771LINCOLN ;2U
Adder
13.446
247620Y3-023
Adder
0.996
274808UNIV PK N;4U
Adder
10.604
274803UNIV PARK;6U
Adder
12.325
972259AH1-714 GEN
Adder
40.299
24344105CKG2
50/50
18.741
274888KELLY CRK;1U
Solar/Wind Harmer
12.465
274887GEN-1.85
Solar/Wind Harmer
11.254
276843GEN-1.7
Solar/Wind Harmer
1.211
958011AF2-095 GEN
Solar/Wind Harmer
30.403
274674JOLIET 9 ;6U
Adder
32.155
274847GR RIDGE ;BU
Solar/Wind Harmer
10.533
971573AH1-285 GEN
Solar/Wind Harmer
17.714
945421AF1-207 GEN
Solar/Wind Harmer
28.747
957841AF2-078 GEN
Solar/Wind Harmer
12.371
274695ROCKY RD ;2P
Adder
22.735
274693ROCKY RD ;1P
Adder
22.511
274697ROCKY RD ;3P
Adder
6.176
274696ROCKY RD ;4P
Adder
23.271
958481AF2-142 GEN
Solar/Wind Harmer
30.611
274861TOP CROP ;1U
Solar/Wind Harmer
12.359
274862TOP CROP ;2U
Solar/Wind Harmer
10.32
274683WAUKEGAN ;8U
Adder
42.888
274683WAUKEGAN ;8U
Adder
36.153
962691AG1-118 GEN
Solar/Wind Harmer
60.767
970921AG2-575 GEN
Solar/Wind Harmer
20.199
970921AG2-575 GEN
Solar/Wind Harmer
4.697
958491AF2-143 GEN
Solar/Wind Harmer
30.201
942991AE2-321 GEN
Solar/Wind Harmer
20.031
274879MINONK ;1U
Solar/Wind Harmer
13.514
274764LEE CO EC;5U
Adder
18.019
274765LEE CO EC;6U
Adder
18.019
274762LEE CO EC;3U
Adder
17.977
274763LEE CO EC;4U
Adder
17.808
972267AH1-718 GEN
Adder
7.955
247621Y3-024
Adder
0.32
270471AD2-092_GEN
Solar/Wind Helper
1.53
971333AH1-146 GEN
Solar/Wind Harmer
33.502
971335AH1-147 GEN
Solar/Wind Harmer
33.502
971599AH1-298 GEN
50/50
20.9
270144AC1-141 ST1_
50/50
4.729
24643105BUCHANAN
50/50
0.028
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
35.714
960681AF2-359 GEN
Solar/Wind Harmer
8.455
971771AH1-392 GEN
Solar/Wind Harmer
20.095
971769AH1-391 GEN
Solar/Wind Harmer
22.253
270071AF1-092 GEN
Solar/Wind Harmer
32.895
944161AF1-084 GEN
Solar/Wind Harmer
4.798
274775LINCOLN ;6U
Adder
13.446
274776LINCOLN ;7U
Adder
13.446
274777LINCOLN ;8U
Adder
13.446
270536AF1-215 GEN2
Solar/Wind Harmer
9.745
274814UNIV PK N;0U
Adder
10.744
274807UNIV PK N;3U
Adder
10.721
274805UNIV PK N;1U
Adder
10.674
274811UNIV PK N;7U
Adder
10.651
972037AH1-567 GEN1
Adder
0.387
274827FISK ;RP
Adder
16.398
960591AF2-350 GEN
Solar/Wind Harmer
21.113
972227AH1-698 GEN1
Adder
5.503
958391AF2-133 GEN
Solar/Wind Harmer
19.092
274687WILL CNTY;4U
Adder
58.542
274687WILL CNTY;4U
Adder
58.542
274675JOLIET 29;7U
Adder
64.194
274675JOLIET 29;7U
Adder
61.901
274731ELWOOD EC;2P
Adder
34.297
274733ELWOOD EC;3P
Adder
34.297
274735ELWOOD EC;4P
Adder
34.297
274728ELWOOD EC;5P
Adder
34.297
970833AG2-524 GEN
Solar/Wind Harmer
18.19
970833AG2-524 GEN
Solar/Wind Harmer
8.46
274746AC1-111 G10
Adder
11.564
274744AC1-111 GEN8
Adder
11.564
276868AE1-113 GEN
Solar/Wind Harmer
20.269
276882AE2-255 GEN
Solar/Wind Harmer
6.757
971177AH1-047 GEN
Solar/Wind Harmer
11.733
24690905MDL-1G C
Solar/Wind Harmer
16.067
270180AB1-006 GEN1
Solar/Wind Harmer
14.393
946581AF1-322 GEN
Solar/Wind Harmer
20.475
24691005MDL-2G C
Solar/Wind Harmer
7.401
24697605MDL-3G C
Solar/Wind Harmer
7.378
24697905MDL-4G C
Solar/Wind Harmer
4.593
270181AB1-006 GEN2
Solar/Wind Harmer
1.431
971411AH1-196 GEN
Solar/Wind Harmer
29.896
971675AH1-338 GEN
Solar/Wind Harmer
35.874
24729505KEY G4
Adder
12.834
274823ROCKFORD ;21
Adder
38.397
270143AC1-141 CT2_
50/50
5.339
24639705ELKHART HY
50/50
0.356
970521AG2-332 GEN
50/50
25.327
24307105BERRINSP G
50/50
0.047
970245AG2-165 GEN
Solar/Wind Harmer
44.073
970333AG2-219 GEN
Solar/Wind Harmer
71.347
270505AE1-170 C O1
Solar/Wind Harmer
33.103
945111AF1-176 GEN
Solar/Wind Harmer
39.113
270449AD2-020 GEN
Solar/Wind Harmer
6.12
943021AE2-325 GEN
Solar/Wind Harmer
7.951
970373AG2-245 GEN
Solar/Wind Harmer
45.678
972207SS24-0001
Solar/Wind Harmer
47.808
274773LINCOLN ;4U
Adder
13.446
274774LINCOLN ;5U
Adder
13.446
270055AF2-134 C O1
Solar/Wind Harmer
6.496
274723RIVER EC ;12
Adder
38.388
274751CRETE EC ;1U
Adder
10.462
274754CRETE EC ;4U
Adder
10.462
276164X3-005 C
Solar/Wind Harmer
1.498
270063AE2-323 C
Solar/Wind Harmer
4.686
274812UNIV PK N;8U
Adder
10.651
958381AF2-132 GEN
Solar/Wind Harmer
19.217
964861AG1-349 GEN
Solar/Wind Harmer
16.628
971917AH1-482 GEN
Solar/Wind Harmer
19.189
276776AD2-060 GEN
Solar/Wind Harmer
0.893
274801UNIV PARK;4U
Adder
12.307
941551AE2-152 GEN
Solar/Wind Harmer
9.522
274676JOLIET 29;8U
Adder
64.193
274674JOLIET 9 ;6U
Adder
32.155
274732ELWOOD EC;7P
Adder
34.297
274871GR RIDGE ;2U
Solar/Wind Harmer
16.013
940581AE2-045 GEN
Solar/Wind Harmer
21.231
971605AH1-302 GEN
Solar/Wind Harmer
18.155
274745AC1-111 GEN9
Adder
11.564
276691AA1-018 GEN1
Solar/Wind Harmer
0.95
274682WAUKEGAN ;7U
Adder
36.631
274828WAUKEGAN ;BP
Adder
22.481
960751AF2-366 GEN
Solar/Wind Harmer
5.795
962781AG1-127 GEN
Solar/Wind Harmer
19.209
939401AE1-172 GEN
Solar/Wind Harmer
28.102
274872LEEDK;1U
Solar/Wind Harmer
16.548
276901AD2-066 C O1
Solar/Wind Harmer
7.062
24791305MDL-5G
Solar/Wind Harmer
4.826
971997AH1-543 GEN
Solar/Wind Harmer
31.477
276861AD2-134 GEN
Solar/Wind Harmer
3.559
274822ROCKFORD ;11
Adder
38.678
972235AH1-702 GEN1
Adder
4.954
274761LEE CO EC;2U
Adder
17.977
274766LEE CO EC;7U
Adder
17.765
24728605AND G2
Adder
5.044
970091AG2-072 GEN
Adder
4.904
270349AD2-093_GEN
Solar/Wind Helper
1.53
24344005CKG1
50/50
14.639
270142AC1-141 CT1_
50/50
5.339
24641605TWIN BRNCH
50/50
0.039
24642205MAYFLWER
50/50
1.49
944961AF1-161 GEN
50/50
6.347
962601AG1-109 GEN
50/50
6.347
970513AG2-328 GEN
Solar/Wind Harmer
44.073
970517AG2-330 GEN
Solar/Wind Harmer
39.973
970349AG2-230 GEN
Solar/Wind Harmer
35.714
970243AG2-164 GEN
Solar/Wind Harmer
58.375
970519AG2-331 GEN
Solar/Wind Harmer
39.218
970699AG2-449 GEN
Solar/Wind Harmer
25.944
247643Z2-116 C
Solar/Wind Harmer
0.155
270043AE2-236 GEN
Solar/Wind Harmer
12.133
945111AF1-176 GEN
Solar/Wind Harmer
12.396
274772LINCOLN ;3U
Adder
13.446
24441205WTRV SLR C
Solar/Wind Harmer
0.289
270535AF1-215 GEN1
Solar/Wind Harmer
9.745
274724RIVER EC ;11
Adder
37.943
972231SS25-0005
Solar/Wind Harmer
20.313
972181SS23-001
Solar/Wind Harmer
12.696
274752CRETE EC ;2U
Adder
10.462
274753CRETE EC ;3U
Adder
10.462
247604X1-042
Adder
0.885
970707AG2-453 GEN
Solar/Wind Harmer
59.407
964401AG1-302 GEN
Solar/Wind Harmer
19.217
274802UNIV PARK;5U
Adder
12.325
274826FISK ;BP
Adder
23.138
276772AC2-154 GEN
Solar/Wind Harmer
5.888
276806AD2-047 C O1
Solar/Wind Harmer
22.586
970941AG2-585 GEN
Solar/Wind Harmer
26.392
274800UNIV PARK;3U
Adder
12.307
972038AH1-567 GEN2
Adder
0.77
972228AH1-698 GEN2
Adder
7.816
276897AD1-100 C
Solar/Wind Harmer
60.93
939351AE1-166 GEN
Solar/Wind Harmer
12.45
959141AF2-205 GEN
Solar/Wind Harmer
12.662
970031AG2-029 GEN
Solar/Wind Harmer
62.778
274676JOLIET 29;8U
Adder
61.9
274729ELWOOD EC;1P
Adder
34.297
274730ELWOOD EC;6P
Adder
34.297
274734ELWOOD EC;8P
Adder
34.297
274736ELWOOD EC;9P
Adder
34.297
276893AG1-478 C
Solar/Wind Harmer
0.871
943121AE2-341 GEN
Solar/Wind Harmer
31.095
943591AF1-030 GEN
Solar/Wind Harmer
20.73
276694AA1-018 GEN2
Solar/Wind Harmer
12.879
274682WAUKEGAN ;7U
Adder
36.631
944531AF1-118 GEN
Solar/Wind Harmer
70.934
274872LEEDK;1U
Solar/Wind Harmer
0.515
276805AD2-038 GEN
Solar/Wind Harmer
10.329
24755605MDL-5G
Solar/Wind Harmer
4.826
970781AG2-491 GEN
Solar/Wind Harmer
20.008
276799AD1-013 GEN
Solar/Wind Harmer
4.408
946671AF1-331 GEN
Solar/Wind Harmer
0.835
274855GSG-6 ;RU
Solar/Wind Harmer
7.359
274850MENDOTA H;RU
Solar/Wind Harmer
5.117
276602WESTBROOK C
Solar/Wind Harmer
4.236
276863AD2-134 GEN
Solar/Wind Harmer
3.559
972236AH1-702 GEN2
Adder
4.308
274760LEE CO EC;1U
Adder
17.977
274767LEE CO EC;8U
Adder
17.765
24728705AND G3
Adder
10.55
24728505AND G1
Adder
5.044
944201AF1-088_MTX
Adder
146.322
957141AF2-008_MTX
Adder
73.161
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.633
CBM West 1LTFEXP_CBM-W1->PJM
CBM
228.49
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.819
MECLTFEXP_MEC->PJM
CLTF
26.916
SIGELTFEXP_SIGE->PJM
CLTF
0.505
LAGNLTFEXP_LAGN->PJM
CLTF
13.672
TVALTFEXP_TVA->PJM
CLTF
5.007
CBM West 2LTFEXP_CBM-W2->PJM
CBM
127.851
NYPJM->LTFIMP_NY
CLTF
3.427
LGEELTFEXP_LGEE->PJM
CLTF
4.47
WECLTFEXP_WEC->PJM
CLTF
7.49
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.475
AH1-155LTFEXP_AH1-155->PJM
LTF
0.712

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.33 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6350.84
MW Contribution:58.98
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
19.943
270144AC1-141 ST1_
50/50
4.4
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
13.384
274776LINCOLN ;7U
50/50
13.384
274777LINCOLN ;8U
50/50
13.384
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
33.197
960681AF2-359 GEN
Solar/Wind Harmer
7.853
971771AH1-392 GEN
Solar/Wind Harmer
18.701
971769AH1-391 GEN
Solar/Wind Harmer
20.689
270071AF1-092 GEN
Solar/Wind Harmer
30.794
944161AF1-084 GEN
Solar/Wind Harmer
4.463
274814UNIV PK N;0U
Adder
10.075
274807UNIV PK N;3U
Adder
10.053
274805UNIV PK N;1U
Adder
10.009
274811UNIV PK N;7U
Adder
9.987
972037AH1-567 GEN1
Adder
0.363
274827FISK ;RP
Adder
15.4
960591AF2-350 GEN
Solar/Wind Harmer
19.839
972227AH1-698 GEN1
Adder
5.172
270536AF1-215 GEN2
Solar/Wind Harmer
8.953
274687WILL CNTY;4U
Adder
55.044
274687WILL CNTY;4U
Adder
55.044
274675JOLIET 29;7U
Adder
60.371
274675JOLIET 29;7U
Adder
58.215
274731ELWOOD EC;2P
Adder
32.272
274733ELWOOD EC;3P
Adder
32.272
274735ELWOOD EC;4P
Adder
32.272
274728ELWOOD EC;5P
Adder
32.272
970833AG2-524 GEN
Solar/Wind Harmer
17.125
970833AG2-524 GEN
Solar/Wind Harmer
7.965
274746AC1-111 G10
Adder
10.891
274744AC1-111 GEN8
Adder
10.891
958391AF2-133 GEN
Solar/Wind Harmer
17.467
24729505KEY G4
Adder
12.444
276868AE1-113 GEN
Solar/Wind Harmer
19.163
276882AE2-255 GEN
Solar/Wind Harmer
6.388
971177AH1-047 GEN
Solar/Wind Harmer
11.082
971675AH1-338 GEN
Solar/Wind Harmer
33.905
971411AH1-196 GEN
Solar/Wind Harmer
28.25
274863CRW1-WTG
Solar/Wind Harmer
10.504
274864CRW2-WTG
Solar/Wind Harmer
10.504
971171AH1-044 GEN
Solar/Wind Harmer
37.421
274823ROCKFORD ;21
Adder
36.321
24344105CKG2
50/50
17.375
270143AC1-141 CT2_
50/50
4.968
24639705ELKHART HY
50/50
0.332
274773LINCOLN ;4U
50/50
13.384
274774LINCOLN ;5U
50/50
13.384
970521AG2-332 GEN
50/50
23.621
970245AG2-165 GEN
Solar/Wind Harmer
39.594
270505AE1-170 C O1
Solar/Wind Harmer
30.803
945111AF1-176 GEN
Solar/Wind Harmer
36.413
972207SS24-0001
Solar/Wind Harmer
44.846
270449AD2-020 GEN
Solar/Wind Harmer
5.693
943021AE2-325 GEN
Solar/Wind Harmer
7.398
274723RIVER EC ;12
Adder
35.977
970373AG2-245 GEN
Solar/Wind Harmer
42.088
274751CRETE EC ;1U
Adder
9.796
274754CRETE EC ;4U
Adder
9.796
276164X3-005 C
Solar/Wind Harmer
1.405
270063AE2-323 C
Solar/Wind Harmer
4.395
274812UNIV PK N;8U
Adder
9.987
276776AD2-060 GEN
Solar/Wind Harmer
0.839
274801UNIV PARK;4U
Adder
11.561
941551AE2-152 GEN
Solar/Wind Harmer
8.961
270055AF2-134 C O1
Solar/Wind Harmer
5.968
274676JOLIET 29;8U
Adder
60.37
274674JOLIET 9 ;6U
Adder
30.252
274732ELWOOD EC;7P
Adder
32.272
274871GR RIDGE ;2U
Solar/Wind Harmer
15.077
274745AC1-111 GEN9
Adder
10.891
958381AF2-132 GEN
Solar/Wind Harmer
17.606
964861AG1-349 GEN
Solar/Wind Harmer
15.23
971917AH1-482 GEN
Solar/Wind Harmer
17.576
276691AA1-018 GEN1
Solar/Wind Harmer
0.896
274682WAUKEGAN ;7U
Adder
34.537
274828WAUKEGAN ;BP
Adder
21.199
939401AE1-172 GEN
Solar/Wind Harmer
26.601
960751AF2-366 GEN
Solar/Wind Harmer
5.47
962781AG1-127 GEN
Solar/Wind Harmer
18.131
274872LEEDK;1U
Solar/Wind Harmer
15.624
940581AE2-045 GEN
Solar/Wind Harmer
19.376
276901AD2-066 C O1
Solar/Wind Harmer
6.676
971605AH1-302 GEN
Solar/Wind Harmer
16.569
971997AH1-543 GEN
Solar/Wind Harmer
29.779
276861AD2-134 GEN
Solar/Wind Harmer
3.363
957471AF2-041 GEN
Solar/Wind Harmer
56.132
959081AF2-199 GEN
Solar/Wind Harmer
18.711
971067AG2-660 GEN
Solar/Wind Harmer
4.351
276876AE1-163_GEN2
Solar/Wind Harmer
12.566
274822ROCKFORD ;11
Adder
36.587
972235AH1-702 GEN1
Adder
4.687
274761LEE CO EC;2U
Adder
17.04
274766LEE CO EC;7U
Adder
16.84
970091AG2-072 GEN
Adder
32.358
270349AD2-093_GEN
Solar/Wind Helper
1.555
270102X2-052 ST
50/50
3.346
270100X2-052 CT1
50/50
3.083
270101X2-052 CT2
50/50
3.083
274770LINCOLN ;1U
50/50
13.384
274771LINCOLN ;2U
50/50
13.384
970321AG2-212 GEN
Solar/Wind Harmer
39.594
965681AG1-436 GEN
Solar/Wind Harmer
25.984
965791AG1-447 GEN
Solar/Wind Harmer
13.294
270526AF1-158 GEN
Solar/Wind Harmer
9.408
24441505OLIV SLR
Solar/Wind Harmer
0.277
270216AD2-079_GEN
Solar/Wind Harmer
1.252
957891AF2-083 GEN
Solar/Wind Harmer
6.914
960981AF2-389 GEN
Solar/Wind Harmer
3.098
961051AF2-396 GEN
Solar/Wind Harmer
32.298
961051AF2-396 GEN
Solar/Wind Harmer
15.022
247620Y3-023
Adder
0.93
274808UNIV PK N;4U
Adder
9.944
972259AH1-714 GEN
Adder
37.882
274803UNIV PARK;6U
Adder
11.574
274888KELLY CRK;1U
Solar/Wind Harmer
11.713
274887GEN-1.85
Solar/Wind Harmer
10.575
276843GEN-1.7
Solar/Wind Harmer
1.138
958011AF2-095 GEN
Solar/Wind Harmer
28.568
274674JOLIET 9 ;6U
Adder
30.252
274847GR RIDGE ;BU
Solar/Wind Harmer
9.918
971573AH1-285 GEN
Solar/Wind Harmer
16.69
274695ROCKY RD ;2P
Adder
21.435
274693ROCKY RD ;1P
Adder
21.224
274697ROCKY RD ;3P
Adder
5.823
274696ROCKY RD ;4P
Adder
21.94
958481AF2-142 GEN
Solar/Wind Harmer
28.872
274861TOP CROP ;1U
Solar/Wind Harmer
11.657
274862TOP CROP ;2U
Solar/Wind Harmer
9.734
274683WAUKEGAN ;8U
Adder
40.442
274683WAUKEGAN ;8U
Adder
34.091
962691AG1-118 GEN
Solar/Wind Harmer
57.342
970921AG2-575 GEN
Solar/Wind Harmer
19.065
970921AG2-575 GEN
Solar/Wind Harmer
4.434
958491AF2-143 GEN
Solar/Wind Harmer
28.532
274879MINONK ;1U
Solar/Wind Harmer
12.777
942991AE2-321 GEN
Solar/Wind Harmer
18.919
971333AH1-146 GEN
Solar/Wind Harmer
37.64
971335AH1-147 GEN
Solar/Wind Harmer
37.64
971341AH1-150 GEN
Solar/Wind Harmer
37.421
971343AH1-151 GEN
Solar/Wind Harmer
37.421
276872AE1-163_GEN1
Solar/Wind Harmer
12.566
274764LEE CO EC;5U
Adder
17.08
274765LEE CO EC;6U
Adder
17.08
274762LEE CO EC;3U
Adder
17.04
274763LEE CO EC;4U
Adder
16.88
972267AH1-718 GEN
Adder
7.55
270471AD2-092_GEN
Solar/Wind Helper
1.555
945421AF1-207 GEN
Solar/Wind Harmer
23.561
24344005CKG1
50/50
13.598
270142AC1-141 CT1_
50/50
4.968
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.387
274772LINCOLN ;3U
50/50
13.384
970513AG2-328 GEN
Solar/Wind Harmer
39.594
970517AG2-330 GEN
Solar/Wind Harmer
35.91
970349AG2-230 GEN
Solar/Wind Harmer
33.197
270043AE2-236 GEN
Solar/Wind Harmer
11.487
247643Z2-116 C
Solar/Wind Harmer
0.144
945111AF1-176 GEN
Solar/Wind Harmer
11.54
274724RIVER EC ;11
Adder
35.562
972231SS25-0005
Solar/Wind Harmer
19.02
972181SS23-001
Solar/Wind Harmer
11.887
274752CRETE EC ;2U
Adder
9.796
274753CRETE EC ;3U
Adder
9.796
24441205WTRV SLR C
Solar/Wind Harmer
0.269
970707AG2-453 GEN
Solar/Wind Harmer
55.829
274802UNIV PARK;5U
Adder
11.574
274826FISK ;BP
Adder
21.73
276772AC2-154 GEN
Solar/Wind Harmer
5.533
276806AD2-047 C O1
Solar/Wind Harmer
21.223
970941AG2-585 GEN
Solar/Wind Harmer
24.799
972228AH1-698 GEN2
Adder
7.346
274800UNIV PARK;3U
Adder
11.561
972038AH1-567 GEN2
Adder
0.724
276897AD1-100 C
Solar/Wind Harmer
57.337
939351AE1-166 GEN
Solar/Wind Harmer
11.715
247604X1-042
Adder
0.823
270535AF1-215 GEN1
Solar/Wind Harmer
8.953
274676JOLIET 29;8U
Adder
58.214
970031AG2-029 GEN
Solar/Wind Harmer
58.977
274729ELWOOD EC;1P
Adder
32.272
274730ELWOOD EC;6P
Adder
32.272
274734ELWOOD EC;8P
Adder
32.272
274736ELWOOD EC;9P
Adder
32.272
276893AG1-478 C
Solar/Wind Harmer
0.82
944531AF1-118 GEN
Solar/Wind Harmer
68.666
943121AE2-341 GEN
Solar/Wind Harmer
29.28
943591AF1-030 GEN
Solar/Wind Harmer
19.52
964401AG1-302 GEN
Solar/Wind Harmer
17.606
276694AA1-018 GEN2
Solar/Wind Harmer
12.147
274682WAUKEGAN ;7U
Adder
34.537
959141AF2-205 GEN
Solar/Wind Harmer
11.571
276805AD2-038 GEN
Solar/Wind Harmer
9.758
274872LEEDK;1U
Solar/Wind Harmer
0.487
276799AD1-013 GEN
Solar/Wind Harmer
4.166
946671AF1-331 GEN
Solar/Wind Harmer
0.789
274855GSG-6 ;RU
Solar/Wind Harmer
6.955
274850MENDOTA H;RU
Solar/Wind Harmer
4.836
276602WESTBROOK C
Solar/Wind Harmer
4.003
276863AD2-134 GEN
Solar/Wind Harmer
3.363
959091AF2-200 GEN
Solar/Wind Harmer
37.421
276889AE2-281 GEN
Solar/Wind Harmer
3.59
972236AH1-702 GEN2
Adder
4.076
274760LEE CO EC;1U
Adder
17.04
274767LEE CO EC;8U
Adder
16.84
944201AF1-088_MTX
Adder
162.845
957141AF2-008_MTX
Adder
81.423
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.535
CBM West 1LTFEXP_CBM-W1->PJM
CBM
216.955
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.977
MECLTFEXP_MEC->PJM
CLTF
25.953
SIGELTFEXP_SIGE->PJM
CLTF
0.549
LAGNLTFEXP_LAGN->PJM
CLTF
14.056
TVALTFEXP_TVA->PJM
CLTF
5.361
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.514
NYPJM->LTFIMP_NY
CLTF
3.416
LGEELTFEXP_LGEE->PJM
CLTF
5.556
WECLTFEXP_WEC->PJM
CLTF
7.087
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.221
AG2-052LTFEXP_AG2-052->PJM
LTF
0.446
AH1-155LTFEXP_AH1-155->PJM
LTF
0.669

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.73 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6284.8
MW Contribution:59.12
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
19.983
270144AC1-141 ST1_
50/50
4.41
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
13.415
274776LINCOLN ;7U
50/50
13.415
274777LINCOLN ;8U
50/50
13.415
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
33.266
960681AF2-359 GEN
Solar/Wind Harmer
7.871
971771AH1-392 GEN
Solar/Wind Harmer
18.742
971769AH1-391 GEN
Solar/Wind Harmer
20.735
270071AF1-092 GEN
Solar/Wind Harmer
30.863
944161AF1-084 GEN
Solar/Wind Harmer
4.473
274814UNIV PK N;0U
Adder
10.098
274807UNIV PK N;3U
Adder
10.076
274805UNIV PK N;1U
Adder
10.033
274811UNIV PK N;7U
Adder
10.011
972037AH1-567 GEN1
Adder
0.364
274827FISK ;RP
Adder
15.436
960591AF2-350 GEN
Solar/Wind Harmer
19.885
972227AH1-698 GEN1
Adder
5.185
270536AF1-215 GEN2
Solar/Wind Harmer
8.974
274687WILL CNTY;4U
Adder
55.173
274687WILL CNTY;4U
Adder
55.173
274675JOLIET 29;7U
Adder
60.513
274675JOLIET 29;7U
Adder
58.351
274731ELWOOD EC;2P
Adder
32.348
274733ELWOOD EC;3P
Adder
32.348
274735ELWOOD EC;4P
Adder
32.348
274728ELWOOD EC;5P
Adder
32.348
970833AG2-524 GEN
Solar/Wind Harmer
17.166
970833AG2-524 GEN
Solar/Wind Harmer
7.984
274746AC1-111 G10
Adder
10.916
274744AC1-111 GEN8
Adder
10.916
958391AF2-133 GEN
Solar/Wind Harmer
17.509
24729505KEY G4
Adder
12.474
276868AE1-113 GEN
Solar/Wind Harmer
19.21
276882AE2-255 GEN
Solar/Wind Harmer
6.404
971177AH1-047 GEN
Solar/Wind Harmer
11.109
971675AH1-338 GEN
Solar/Wind Harmer
33.988
971411AH1-196 GEN
Solar/Wind Harmer
28.319
274863CRW1-WTG
Solar/Wind Harmer
10.53
274864CRW2-WTG
Solar/Wind Harmer
10.53
971171AH1-044 GEN
Solar/Wind Harmer
37.513
274823ROCKFORD ;21
Adder
36.411
24344105CKG2
50/50
17.41
270143AC1-141 CT2_
50/50
4.979
24639705ELKHART HY
50/50
0.333
274773LINCOLN ;4U
50/50
13.415
274774LINCOLN ;5U
50/50
13.415
970521AG2-332 GEN
50/50
23.674
970245AG2-165 GEN
Solar/Wind Harmer
39.676
270505AE1-170 C O1
Solar/Wind Harmer
30.872
945111AF1-176 GEN
Solar/Wind Harmer
36.495
972207SS24-0001
Solar/Wind Harmer
44.948
270449AD2-020 GEN
Solar/Wind Harmer
5.706
943021AE2-325 GEN
Solar/Wind Harmer
7.414
274723RIVER EC ;12
Adder
36.059
970373AG2-245 GEN
Solar/Wind Harmer
42.185
274751CRETE EC ;1U
Adder
9.818
274754CRETE EC ;4U
Adder
9.818
276164X3-005 C
Solar/Wind Harmer
1.409
270063AE2-323 C
Solar/Wind Harmer
4.405
274812UNIV PK N;8U
Adder
10.011
276776AD2-060 GEN
Solar/Wind Harmer
0.841
274801UNIV PARK;4U
Adder
11.588
941551AE2-152 GEN
Solar/Wind Harmer
8.982
270055AF2-134 C O1
Solar/Wind Harmer
5.982
274676JOLIET 29;8U
Adder
60.512
274674JOLIET 9 ;6U
Adder
30.323
274732ELWOOD EC;7P
Adder
32.348
274871GR RIDGE ;2U
Solar/Wind Harmer
15.112
274745AC1-111 GEN9
Adder
10.916
958381AF2-132 GEN
Solar/Wind Harmer
17.648
964861AG1-349 GEN
Solar/Wind Harmer
15.267
971917AH1-482 GEN
Solar/Wind Harmer
17.617
276691AA1-018 GEN1
Solar/Wind Harmer
0.898
274682WAUKEGAN ;7U
Adder
34.62
274828WAUKEGAN ;BP
Adder
21.25
939401AE1-172 GEN
Solar/Wind Harmer
26.665
960751AF2-366 GEN
Solar/Wind Harmer
5.483
962781AG1-127 GEN
Solar/Wind Harmer
18.175
274872LEEDK;1U
Solar/Wind Harmer
15.662
940581AE2-045 GEN
Solar/Wind Harmer
19.423
971605AH1-302 GEN
Solar/Wind Harmer
16.609
276901AD2-066 C O1
Solar/Wind Harmer
6.692
971997AH1-543 GEN
Solar/Wind Harmer
29.852
276861AD2-134 GEN
Solar/Wind Harmer
3.372
957471AF2-041 GEN
Solar/Wind Harmer
56.27
959081AF2-199 GEN
Solar/Wind Harmer
18.757
971067AG2-660 GEN
Solar/Wind Harmer
4.362
276876AE1-163_GEN2
Solar/Wind Harmer
12.597
274822ROCKFORD ;11
Adder
36.677
972235AH1-702 GEN1
Adder
4.699
274761LEE CO EC;2U
Adder
17.083
274766LEE CO EC;7U
Adder
16.882
970091AG2-072 GEN
Adder
32.467
270349AD2-093_GEN
Solar/Wind Helper
1.548
270102X2-052 ST
50/50
3.353
270100X2-052 CT1
50/50
3.09
270101X2-052 CT2
50/50
3.09
274770LINCOLN ;1U
50/50
13.415
274771LINCOLN ;2U
50/50
13.415
970321AG2-212 GEN
Solar/Wind Harmer
39.676
965681AG1-436 GEN
Solar/Wind Harmer
26.042
965791AG1-447 GEN
Solar/Wind Harmer
13.324
270526AF1-158 GEN
Solar/Wind Harmer
9.429
24441505OLIV SLR
Solar/Wind Harmer
0.278
270216AD2-079_GEN
Solar/Wind Harmer
1.255
957891AF2-083 GEN
Solar/Wind Harmer
6.929
960981AF2-389 GEN
Solar/Wind Harmer
3.105
961051AF2-396 GEN
Solar/Wind Harmer
32.372
961051AF2-396 GEN
Solar/Wind Harmer
15.057
247620Y3-023
Adder
0.932
274808UNIV PK N;4U
Adder
9.967
972259AH1-714 GEN
Adder
37.97
274803UNIV PARK;6U
Adder
11.601
274888KELLY CRK;1U
Solar/Wind Harmer
11.74
274887GEN-1.85
Solar/Wind Harmer
10.599
276843GEN-1.7
Solar/Wind Harmer
1.14
958011AF2-095 GEN
Solar/Wind Harmer
28.635
274674JOLIET 9 ;6U
Adder
30.323
274847GR RIDGE ;BU
Solar/Wind Harmer
9.941
971573AH1-285 GEN
Solar/Wind Harmer
16.73
274695ROCKY RD ;2P
Adder
21.486
274693ROCKY RD ;1P
Adder
21.275
274697ROCKY RD ;3P
Adder
5.837
274696ROCKY RD ;4P
Adder
21.993
958481AF2-142 GEN
Solar/Wind Harmer
28.942
274861TOP CROP ;1U
Solar/Wind Harmer
11.685
274862TOP CROP ;2U
Solar/Wind Harmer
9.757
274683WAUKEGAN ;8U
Adder
40.539
274683WAUKEGAN ;8U
Adder
34.173
962691AG1-118 GEN
Solar/Wind Harmer
57.48
970921AG2-575 GEN
Solar/Wind Harmer
19.111
970921AG2-575 GEN
Solar/Wind Harmer
4.444
958491AF2-143 GEN
Solar/Wind Harmer
28.602
274879MINONK ;1U
Solar/Wind Harmer
12.808
942991AE2-321 GEN
Solar/Wind Harmer
18.965
971333AH1-146 GEN
Solar/Wind Harmer
37.732
971335AH1-147 GEN
Solar/Wind Harmer
37.732
971341AH1-150 GEN
Solar/Wind Harmer
37.513
971343AH1-151 GEN
Solar/Wind Harmer
37.513
276872AE1-163_GEN1
Solar/Wind Harmer
12.597
274764LEE CO EC;5U
Adder
17.123
274765LEE CO EC;6U
Adder
17.123
274762LEE CO EC;3U
Adder
17.083
274763LEE CO EC;4U
Adder
16.922
972267AH1-718 GEN
Adder
7.569
270471AD2-092_GEN
Solar/Wind Helper
1.548
945421AF1-207 GEN
Solar/Wind Harmer
23.62
24344005CKG1
50/50
13.628
270142AC1-141 CT1_
50/50
4.979
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.39
274772LINCOLN ;3U
50/50
13.415
970513AG2-328 GEN
Solar/Wind Harmer
39.676
970517AG2-330 GEN
Solar/Wind Harmer
35.985
970349AG2-230 GEN
Solar/Wind Harmer
33.266
270043AE2-236 GEN
Solar/Wind Harmer
11.512
247643Z2-116 C
Solar/Wind Harmer
0.145
945111AF1-176 GEN
Solar/Wind Harmer
11.566
274724RIVER EC ;11
Adder
35.644
972231SS25-0005
Solar/Wind Harmer
19.064
972181SS23-001
Solar/Wind Harmer
11.915
274752CRETE EC ;2U
Adder
9.818
274753CRETE EC ;3U
Adder
9.818
24441205WTRV SLR C
Solar/Wind Harmer
0.27
970707AG2-453 GEN
Solar/Wind Harmer
55.958
274802UNIV PARK;5U
Adder
11.601
274826FISK ;BP
Adder
21.78
276772AC2-154 GEN
Solar/Wind Harmer
5.545
276806AD2-047 C O1
Solar/Wind Harmer
21.273
970941AG2-585 GEN
Solar/Wind Harmer
24.857
972228AH1-698 GEN2
Adder
7.363
274800UNIV PARK;3U
Adder
11.588
972038AH1-567 GEN2
Adder
0.725
276897AD1-100 C
Solar/Wind Harmer
57.471
939351AE1-166 GEN
Solar/Wind Harmer
11.743
247604X1-042
Adder
0.825
270535AF1-215 GEN1
Solar/Wind Harmer
8.974
274676JOLIET 29;8U
Adder
58.35
970031AG2-029 GEN
Solar/Wind Harmer
59.115
274729ELWOOD EC;1P
Adder
32.348
274730ELWOOD EC;6P
Adder
32.348
274734ELWOOD EC;8P
Adder
32.348
274736ELWOOD EC;9P
Adder
32.348
276893AG1-478 C
Solar/Wind Harmer
0.821
944531AF1-118 GEN
Solar/Wind Harmer
68.828
943121AE2-341 GEN
Solar/Wind Harmer
29.349
943591AF1-030 GEN
Solar/Wind Harmer
19.566
964401AG1-302 GEN
Solar/Wind Harmer
17.648
276694AA1-018 GEN2
Solar/Wind Harmer
12.176
274682WAUKEGAN ;7U
Adder
34.62
959141AF2-205 GEN
Solar/Wind Harmer
11.599
276805AD2-038 GEN
Solar/Wind Harmer
9.782
274872LEEDK;1U
Solar/Wind Harmer
0.488
276799AD1-013 GEN
Solar/Wind Harmer
4.176
946671AF1-331 GEN
Solar/Wind Harmer
0.791
274855GSG-6 ;RU
Solar/Wind Harmer
6.972
274850MENDOTA H;RU
Solar/Wind Harmer
4.848
276602WESTBROOK C
Solar/Wind Harmer
4.013
276863AD2-134 GEN
Solar/Wind Harmer
3.372
959091AF2-200 GEN
Solar/Wind Harmer
37.513
276889AE2-281 GEN
Solar/Wind Harmer
3.599
972236AH1-702 GEN2
Adder
4.086
274760LEE CO EC;1U
Adder
17.083
274767LEE CO EC;8U
Adder
16.882
944201AF1-088_MTX
Adder
163.382
957141AF2-008_MTX
Adder
81.691
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.154
MECLTFEXP_MEC->PJM
CLTF
26.031
SIGELTFEXP_SIGE->PJM
CLTF
0.551
LAGNLTFEXP_LAGN->PJM
CLTF
14.15
TVALTFEXP_TVA->PJM
CLTF
5.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.138
NYPJM->LTFIMP_NY
CLTF
3.386
LGEELTFEXP_LGEE->PJM
CLTF
5.588
WECLTFEXP_WEC->PJM
CLTF
7.104
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.447
AH1-155LTFEXP_AH1-155->PJM
LTF
0.671

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.65 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6032.93
MW Contribution:8.94
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
17.41
270143AC1-141 CT2_
50/50
4.979
24639705ELKHART HY
50/50
0.333
274773LINCOLN ;4U
50/50
18.26
274774LINCOLN ;5U
50/50
18.26
970521AG2-332 GEN
50/50
23.674
970245AG2-165 GEN
Solar/Wind Harmer
6.717
270505AE1-170 C O1
Solar/Wind Harmer
15.077
945111AF1-176 GEN
Solar/Wind Harmer
25.462
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.414
274723RIVER EC ;12
Adder
36.059
970373AG2-245 GEN
Solar/Wind Harmer
29.431
274751CRETE EC ;1U
Adder
16.552
274754CRETE EC ;4U
Adder
16.552
276164X3-005 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0.011
274812UNIV PK N;8U
Adder
10.011
276776AD2-060 GEN
Solar/Wind Harmer
1.448
274801UNIV PARK;4U
Adder
11.588
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.011
274676JOLIET 29;8U
Adder
60.512
274674JOLIET 9 ;6U
Adder
30.323
274732ELWOOD EC;7P
Adder
32.348
274871GR RIDGE ;2U
Solar/Wind Harmer
0.002
274745AC1-111 GEN9
Adder
10.916
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
17.617
276691AA1-018 GEN1
Solar/Wind Harmer
1.631
274682WAUKEGAN ;7U
Adder
34.62
274828WAUKEGAN ;BP
Adder
21.25
939401AE1-172 GEN
Solar/Wind Harmer
9.985
962781AG1-127 GEN
Solar/Wind Harmer
12.689
274872LEEDK;1U
Solar/Wind Harmer
0.008
940581AE2-045 GEN
Solar/Wind Harmer
-0.003
971605AH1-302 GEN
Solar/Wind Harmer
16.609
276901AD2-066 C O1
Solar/Wind Harmer
0.013
971997AH1-543 GEN
Solar/Wind Harmer
6.942
276861AD2-134 GEN
Solar/Wind Harmer
0.236
957471AF2-041 GEN
Solar/Wind Harmer
39.258
959081AF2-199 GEN
Solar/Wind Harmer
13.086
971067AG2-660 GEN
Solar/Wind Harmer
4.362
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
36.677
972235AH1-702 GEN1
Adder
4.699
970819AG2-516 GEN
Solar/Wind Harmer
15.555
970569AG2-363 GEN
Solar/Wind Harmer
38.8
971475AH1-234 GEN
Solar/Wind Harmer
6.272
274857EASY ROAD;U1
Solar/Wind Harmer
0.003
274761LEE CO EC;2U
Adder
17.083
274766LEE CO EC;7U
Adder
16.882
24791305MDL-5G
Solar/Wind Harmer
0.002
965011AG1-365 GEN
Solar/Wind Harmer
12.726
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.423
965651AG1-433 GEN
Solar/Wind Harmer
3.688
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
17.52
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.005
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
958861AF2-177 GEN
Solar/Wind Harmer
5.328
972175AH1-670 GEN
Solar/Wind Harmer
9.878
945371AF1-202 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
27.693
274880W4-005 GEN4
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
4.513
276615X2-022 GEN
Solar/Wind Harmer
0.12
944231AF1-091 GEN
Solar/Wind Harmer
3.041
970291AG2-192 GEN
Solar/Wind Harmer
1.481
270032AE2-172
Solar/Wind Harmer
7.401
965911AG1-460 GEN
Solar/Wind Harmer
2.209
276903AD2-071 C
Solar/Wind Harmer
12.04
970333AG2-219 GEN
Solar/Wind Harmer
7.687
270005AE1-210 C O1
Solar/Wind Harmer
2.283
965031AG1-367 GEN
Solar/Wind Harmer
10.536
970825AG2-519 GEN
Solar/Wind Harmer
3.643
247521TR3_G114
Solar/Wind Harmer
0.37
270246TR4_N_V150
Solar/Wind Harmer
0.066
24695305TIMB G C
Solar/Wind Harmer
0.003
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.029
247536S-71 GEN
Solar/Wind Harmer
0.355
965421AG1-410 GEN
Solar/Wind Harmer
25.459
970773AG2-487 GEN
Solar/Wind Harmer
1.469
246936BC-WTG1
Solar/Wind Harmer
0.326
270489AE1-102 GEN1
Solar/Wind Harmer
1.045
270349AD2-093_GEN
Solar/Wind Helper
1.548
270102X2-052 ST
50/50
3.353
270100X2-052 CT1
50/50
3.09
270101X2-052 CT2
50/50
3.09
274770LINCOLN ;1U
50/50
18.26
274771LINCOLN ;2U
50/50
18.26
970321AG2-212 GEN
Solar/Wind Harmer
6.717
965681AG1-436 GEN
Solar/Wind Harmer
18.169
965791AG1-447 GEN
Solar/Wind Harmer
13.324
270526AF1-158 GEN
Solar/Wind Harmer
0.018
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
28.457
961051AF2-396 GEN
Solar/Wind Harmer
18.971
247620Y3-023
Adder
0.932
274808UNIV PK N;4U
Adder
9.967
972259AH1-714 GEN
Adder
37.97
274803UNIV PARK;6U
Adder
11.601
274888KELLY CRK;1U
Solar/Wind Harmer
0.815
274887GEN-1.85
Solar/Wind Harmer
0.365
276843GEN-1.7
Solar/Wind Harmer
0.449
958011AF2-095 GEN
Solar/Wind Harmer
19.978
274674JOLIET 9 ;6U
Adder
30.323
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.529
274695ROCKY RD ;2P
Adder
21.486
274693ROCKY RD ;1P
Adder
21.275
274697ROCKY RD ;3P
Adder
5.837
274696ROCKY RD ;4P
Adder
21.993
958481AF2-142 GEN
Solar/Wind Harmer
20.192
274861TOP CROP ;1U
Solar/Wind Harmer
0.004
274862TOP CROP ;2U
Solar/Wind Harmer
1.82
274683WAUKEGAN ;8U
Adder
40.539
274683WAUKEGAN ;8U
Adder
34.173
962691AG1-118 GEN
Solar/Wind Harmer
40.102
970921AG2-575 GEN
Solar/Wind Harmer
13.333
970921AG2-575 GEN
Solar/Wind Harmer
4.444
958491AF2-143 GEN
Solar/Wind Harmer
19.955
274879MINONK ;1U
Solar/Wind Harmer
0.559
942991AE2-321 GEN
Solar/Wind Harmer
14.775
971333AH1-146 GEN
Solar/Wind Harmer
26.325
971335AH1-147 GEN
Solar/Wind Harmer
26.325
971341AH1-150 GEN
Solar/Wind Harmer
26.172
971343AH1-151 GEN
Solar/Wind Harmer
26.172
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.305
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
7.288
274764LEE CO EC;5U
Adder
17.123
274765LEE CO EC;6U
Adder
17.123
274762LEE CO EC;3U
Adder
17.083
274763LEE CO EC;4U
Adder
16.922
276603SUBLETTE C
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
12.726
970627AG2-408 GEN
Solar/Wind Harmer
3.818
972267AH1-718 GEN
Adder
7.569
276741O09 GEN1
Solar/Wind Harmer
0.451
276708O09 GEN2
Solar/Wind Harmer
0.451
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.497
276646AC1-214 GEN2
Solar/Wind Harmer
0.497
276782AC1-033 GEN
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.842
960971AF2-388 GEN
Solar/Wind Harmer
7.376
966841AG1-555 GEN
Solar/Wind Harmer
1.399
960611AF2-352 GEN
Solar/Wind Harmer
4.101
970241AG2-163 GEN
Solar/Wind Harmer
6.826
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
971613AH1-306 GEN
Solar/Wind Harmer
5.329
270599AE1-208 GEN
Solar/Wind Harmer
10.158
270031AE2-169
Solar/Wind Harmer
6.095
276916AD2-100_GEN
Solar/Wind Harmer
23.006
276911AD2-131_GEN
Solar/Wind Harmer
1.515
970239AG2-162 GEN
Solar/Wind Harmer
2.688
945391AF1-204 GEN
Solar/Wind Harmer
11.282
960441AF2-335 GEN
Solar/Wind Harmer
10.327
970825AG2-519 GEN
Solar/Wind Harmer
11.373
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.189
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.716
270201AC2-176 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
970623AG2-406 GEN
Solar/Wind Harmer
1.6
970883AG2-550 GEN
Solar/Wind Harmer
8.324
970885AG2-551 GEN
Solar/Wind Harmer
2.775
270007AE1-245 C
Solar/Wind Harmer
0.002
246938BC-WTG3
Solar/Wind Harmer
0.291
246937BC-WTG2
Solar/Wind Harmer
0.326
270471AD2-092_GEN
Solar/Wind Helper
1.548
24344005CKG1
50/50
13.628
270142AC1-141 CT1_
50/50
4.979
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.39
274772LINCOLN ;3U
50/50
18.26
970513AG2-328 GEN
Solar/Wind Harmer
6.717
970517AG2-330 GEN
Solar/Wind Harmer
40.303
970349AG2-230 GEN
Solar/Wind Harmer
23.209
270043AE2-236 GEN
Solar/Wind Harmer
9.37
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.566
274724RIVER EC ;11
Adder
35.644
274752CRETE EC ;2U
Adder
16.552
274753CRETE EC ;3U
Adder
16.552
24441205WTRV SLR C
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
45.547
274802UNIV PARK;5U
Adder
11.601
274826FISK ;BP
Adder
21.78
276806AD2-047 C O1
Solar/Wind Harmer
7.862
970941AG2-585 GEN
Solar/Wind Harmer
17.342
972228AH1-698 GEN2
Adder
7.363
274800UNIV PARK;3U
Adder
11.588
972038AH1-567 GEN2
Adder
0.725
276897AD1-100 C
Solar/Wind Harmer
0.018
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247604X1-042
Adder
0.825
270535AF1-215 GEN1
Solar/Wind Harmer
0.017
274676JOLIET 29;8U
Adder
58.35
970031AG2-029 GEN
Solar/Wind Harmer
8.936
274729ELWOOD EC;1P
Adder
32.348
274730ELWOOD EC;6P
Adder
32.348
274734ELWOOD EC;8P
Adder
32.348
274736ELWOOD EC;9P
Adder
32.348
276893AG1-478 C
Solar/Wind Harmer
0.544
944531AF1-118 GEN
Solar/Wind Harmer
61.488
943121AE2-341 GEN
Solar/Wind Harmer
22.888
943591AF1-030 GEN
Solar/Wind Harmer
15.221
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
34.62
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.004
274872LEEDK;1U
Solar/Wind Harmer
0.488
276799AD1-013 GEN
Solar/Wind Harmer
0.003
946671AF1-331 GEN
Solar/Wind Harmer
1.406
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.155
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.236
959091AF2-200 GEN
Solar/Wind Harmer
26.172
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
4.086
970571AG2-364 GEN
Solar/Wind Harmer
25.867
274858EASY ROAD;U2
Solar/Wind Harmer
0.003
274760LEE CO EC;1U
Adder
17.083
274767LEE CO EC;8U
Adder
16.882
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
12.802
959331AF2-224 GEN
Solar/Wind Harmer
8.908
965021AG1-366 GEN
Solar/Wind Harmer
4.242
276157O29GEN1
Solar/Wind Harmer
2.046
274878BISHOP HL;2U
Solar/Wind Harmer
0.423
942111AE2-223 GEN
Solar/Wind Harmer
4.067
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
36.906
959611AF2-252 GEN
Solar/Wind Harmer
4.101
965931AG1-462 GEN
Solar/Wind Harmer
31.198
247642Z2-115 C
Solar/Wind Harmer
0.005
276686W4-005 GEN3
Solar/Wind Harmer
0.002
971993AH1-541 GEN
Solar/Wind Harmer
5.377
276668AB2-070 GEN1
Solar/Wind Harmer
0.424
276621W2-048 GEN
Solar/Wind Harmer
0.577
276838X2-022 GEN2
Solar/Wind Harmer
0.644
970289AG2-191 GEN
Solar/Wind Harmer
1.253
970291AG2-192 GEN
Solar/Wind Harmer
1.139
942481AE2-261 GEN
Solar/Wind Harmer
33.028
970243AG2-164 GEN
Solar/Wind Harmer
6.289
970519AG2-331 GEN
Solar/Wind Harmer
27.951
970699AG2-449 GEN
Solar/Wind Harmer
2.688
970193AG2-126 GEN
Solar/Wind Harmer
15.928
958821AF2-173 GEN
Solar/Wind Harmer
14.751
270004AE1-209 GEN
Solar/Wind Harmer
2.283
971617AH1-308 GEN
Solar/Wind Harmer
8.548
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.066
946031AF1-268 GEN
Solar/Wind Harmer
9.517
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
14.144
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270491AE1-102 GEN2
Solar/Wind Harmer
1.045
971599AH1-298 GEN
50/50
19.983
270144AC1-141 ST1_
50/50
4.41
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
18.26
274776LINCOLN ;7U
50/50
18.26
274777LINCOLN ;8U
50/50
18.26
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
23.209
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971771AH1-392 GEN
Solar/Wind Harmer
14.529
971769AH1-391 GEN
Solar/Wind Harmer
16.154
971619AH1-309 GEN
Solar/Wind Harmer
6.462
270071AF1-092 GEN
Solar/Wind Harmer
27.514
274814UNIV PK N;0U
Adder
10.098
274807UNIV PK N;3U
Adder
10.076
274805UNIV PK N;1U
Adder
10.033
274811UNIV PK N;7U
Adder
10.011
972037AH1-567 GEN1
Adder
0.364
274827FISK ;RP
Adder
15.436
960591AF2-350 GEN
Solar/Wind Harmer
13.873
972227AH1-698 GEN1
Adder
5.185
270536AF1-215 GEN2
Solar/Wind Harmer
0.017
274687WILL CNTY;4U
Adder
55.173
274687WILL CNTY;4U
Adder
55.173
274675JOLIET 29;7U
Adder
60.513
274675JOLIET 29;7U
Adder
58.351
274731ELWOOD EC;2P
Adder
32.348
274733ELWOOD EC;3P
Adder
32.348
274735ELWOOD EC;4P
Adder
32.348
274728ELWOOD EC;5P
Adder
32.348
970833AG2-524 GEN
Solar/Wind Harmer
15.09
970833AG2-524 GEN
Solar/Wind Harmer
10.06
274746AC1-111 G10
Adder
10.916
274744AC1-111 GEN8
Adder
10.916
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.474
971611AH1-305 GEN
Solar/Wind Harmer
7.91
276868AE1-113 GEN
Solar/Wind Harmer
2.657
276882AE2-255 GEN
Solar/Wind Harmer
1.548
971177AH1-047 GEN
Solar/Wind Harmer
8.156
971675AH1-338 GEN
Solar/Wind Harmer
5.138
971411AH1-196 GEN
Solar/Wind Harmer
19.757
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
26.172
274823ROCKFORD ;21
Adder
36.411
970169AG2-114 GEN
Solar/Wind Harmer
12.957
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
2.2
971549AH1-272 GEN
Solar/Wind Harmer
26.668
971681AH1-341 GEN
Solar/Wind Harmer
20.716
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.003
24697605MDL-3G C
Solar/Wind Harmer
0.003
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
961011AF2-392 GEN
Solar/Wind Harmer
7.462
957751AF2-069 GEN
Solar/Wind Harmer
0.418
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
13.14
941731AE2-173 GEN
Solar/Wind Harmer
10.429
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
6.891
965101AG1-375 GEN
Solar/Wind Harmer
12.296
963841AG1-237 GEN
Solar/Wind Harmer
5.208
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.002
276174W4-005 GEN2
Solar/Wind Harmer
0.002
276849AB2-070 GEN2
Solar/Wind Harmer
0.424
276848AB2-070 GEN3
Solar/Wind Harmer
0.422
963791AG1-232 GEN
Solar/Wind Harmer
15.504
970289AG2-191 GEN
Solar/Wind Harmer
2.164
270594AE1-207 GEN
Solar/Wind Harmer
12.434
971609AH1-304 GEN
Solar/Wind Harmer
1.81
965041AG1-368 GEN
Solar/Wind Harmer
11.055
944221AF1-090 GEN
Solar/Wind Harmer
6.244
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
4.131
270024AE2-089 GEN
Solar/Wind Harmer
0.011
965051AG1-369 GEN
Solar/Wind Harmer
5.072
270240V3-007_GEN2
Solar/Wind Harmer
0.003
270543AE2-219 C
Solar/Wind Harmer
0.005
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.018
971029AG2-637 GEN
Solar/Wind Harmer
11.658
971673AH1-337 GEN
Solar/Wind Harmer
4.919
944201AF1-088_MTX
Adder
163.382
957141AF2-008_MTX
Adder
69.441
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.154
MECLTFEXP_MEC->PJM
CLTF
26.031
SIGELTFEXP_SIGE->PJM
CLTF
0.551
LAGNLTFEXP_LAGN->PJM
CLTF
14.15
TVALTFEXP_TVA->PJM
CLTF
5.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.138
NYPJM->LTFIMP_NY
CLTF
3.386
LGEELTFEXP_LGEE->PJM
CLTF
5.588
WECLTFEXP_WEC->PJM
CLTF
7.104
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.447
AH1-155LTFEXP_AH1-155->PJM
LTF
0.671

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#2995_05E LIMA 345_M_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2995_05E LIMA 345_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.3 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6018.36
MW Contribution:61.23
Bus #Bus NameTypeMW Contribution
24727105RPMNG2
50/50
2.046
965431AG1-411 GEN
50/50
24.956
24641605TWIN BRNCH
50/50
0.035
270142AC1-141 CT1_
50/50
4.843
24344005CKG1
50/50
13.154
24642205MAYFLWER
50/50
1.348
944961AF1-161 GEN
50/50
5.748
962601AG1-109 GEN
50/50
5.748
270043AE2-236 GEN
Solar/Wind Harmer
11.825
959331AF2-224 GEN
Solar/Wind Harmer
21.485
965021AG1-366 GEN
Solar/Wind Harmer
4.996
270491AE1-102 GEN2
Solar/Wind Harmer
2.79
970349AG2-230 GEN
Solar/Wind Harmer
32.134
970513AG2-328 GEN
Solar/Wind Harmer
37.203
970517AG2-330 GEN
Solar/Wind Harmer
33.742
970031AG2-029 GEN
Solar/Wind Harmer
61.231
247643Z2-116 C
Solar/Wind Harmer
0.141
945111AF1-176 GEN
Solar/Wind Harmer
11.286
944531AF1-118 GEN
Solar/Wind Harmer
69.657
274772LINCOLN ;3U
Adder
12.031
24441205WTRV SLR C
Solar/Wind Harmer
0.261
274724RIVER EC ;11
Adder
33.985
972231SS25-0005
Solar/Wind Harmer
18.18
972181SS23-001
Solar/Wind Harmer
11.362
274752CRETE EC ;2U
Adder
9.363
274753CRETE EC ;3U
Adder
9.363
247604X1-042
Adder
0.795
970707AG2-453 GEN
Solar/Wind Harmer
53.178
274802UNIV PARK;5U
Adder
11.035
274826FISK ;BP
Adder
20.719
276772AC2-154 GEN
Solar/Wind Harmer
5.271
276806AD2-047 C O1
Solar/Wind Harmer
20.222
970941AG2-585 GEN
Solar/Wind Harmer
23.629
274800UNIV PARK;3U
Adder
11.02
972038AH1-567 GEN2
Adder
0.69
972228AH1-698 GEN2
Adder
6.996
276897AD1-100 C
Solar/Wind Harmer
54.537
939351AE1-166 GEN
Solar/Wind Harmer
11.143
274676JOLIET 29;8U
Adder
55.43
274730ELWOOD EC;6P
Adder
30.711
274734ELWOOD EC;8P
Adder
30.711
274736ELWOOD EC;9P
Adder
30.711
274729ELWOOD EC;1P
Adder
30.71
276893AG1-478 C
Solar/Wind Harmer
0.78
943121AE2-341 GEN
Solar/Wind Harmer
27.85
943591AF1-030 GEN
Solar/Wind Harmer
18.567
270535AF1-215 GEN1
Solar/Wind Harmer
8.428
276694AA1-018 GEN2
Solar/Wind Harmer
11.537
970615AG2-402 GEN
50/50
4.996
270102X2-052 ST
50/50
3.216
270100X2-052 CT1
50/50
2.963
270101X2-052 CT2
50/50
2.963
247620Y3-023
50/50
0.981
970611AG2-400 GEN
Solar/Wind Harmer
21.485
246938BC-WTG3
Solar/Wind Harmer
8.542
246937BC-WTG2
Solar/Wind Harmer
8.398
970321AG2-212 GEN
Solar/Wind Harmer
37.203
270216AD2-079_GEN
Solar/Wind Harmer
1.229
270526AF1-158 GEN
Solar/Wind Harmer
9.099
957891AF2-083 GEN
Solar/Wind Harmer
6.742
960981AF2-389 GEN
Solar/Wind Harmer
3.021
24441505OLIV SLR
Solar/Wind Harmer
0.268
965681AG1-436 GEN
Solar/Wind Harmer
24.955
965791AG1-447 GEN
Solar/Wind Harmer
12.768
961051AF2-396 GEN
Solar/Wind Harmer
31.495
961051AF2-396 GEN
Solar/Wind Harmer
14.649
274770LINCOLN ;1U
Adder
12.031
274771LINCOLN ;2U
Adder
12.031
274808UNIV PK N;4U
Adder
9.492
274803UNIV PARK;6U
Adder
11.035
972259AH1-714 GEN
Adder
36.075
274888KELLY CRK;1U
Solar/Wind Harmer
11.16
274887GEN-1.85
Solar/Wind Harmer
10.076
276843GEN-1.7
Solar/Wind Harmer
1.084
958011AF2-095 GEN
Solar/Wind Harmer
27.22
274674JOLIET 9 ;6U
Adder
28.794
274847GR RIDGE ;BU
Solar/Wind Harmer
9.431
971573AH1-285 GEN
Solar/Wind Harmer
15.868
274695ROCKY RD ;2P
Adder
20.37
274693ROCKY RD ;1P
Adder
20.17
274697ROCKY RD ;3P
Adder
5.534
274696ROCKY RD ;4P
Adder
20.85
958481AF2-142 GEN
Solar/Wind Harmer
27.421
274861TOP CROP ;1U
Solar/Wind Harmer
11.071
274862TOP CROP ;2U
Solar/Wind Harmer
9.244
274683WAUKEGAN ;8U
Adder
38.432
274683WAUKEGAN ;8U
Adder
32.396
962691AG1-118 GEN
Solar/Wind Harmer
54.457
970921AG2-575 GEN
Solar/Wind Harmer
18.103
970921AG2-575 GEN
Solar/Wind Harmer
4.21
958491AF2-143 GEN
Solar/Wind Harmer
27.059
944541AF1-119 GEN
Solar/Wind Harmer
7.534
960971AF2-388 GEN
Solar/Wind Harmer
19.66
942991AE2-321 GEN
Solar/Wind Harmer
17.957
274879MINONK ;1U
Solar/Wind Harmer
12.109
971333AH1-146 GEN
Solar/Wind Harmer
35.709
971335AH1-147 GEN
Solar/Wind Harmer
35.709
24344105CKG2
50/50
16.752
24727005RPMNG1
50/50
2.039
270143AC1-141 CT2_
50/50
4.843
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.389
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
21.485
965421AG1-410 GEN
Solar/Wind Harmer
64.386
246936BC-WTG1
Solar/Wind Harmer
8.398
270489AE1-102 GEN1
Solar/Wind Harmer
2.79
970245AG2-165 GEN
Solar/Wind Harmer
37.203
270063AE2-323 C
Solar/Wind Harmer
4.466
270505AE1-170 C O1
Solar/Wind Harmer
30.011
945111AF1-176 GEN
Solar/Wind Harmer
35.611
270449AD2-020 GEN
Solar/Wind Harmer
5.542
943021AE2-325 GEN
Solar/Wind Harmer
7.201
972207SS24-0001
Solar/Wind Harmer
42.777
274773LINCOLN ;4U
Adder
12.031
274774LINCOLN ;5U
Adder
12.031
274723RIVER EC ;12
Adder
34.382
274751CRETE EC ;1U
Adder
9.363
274754CRETE EC ;4U
Adder
9.363
276164X3-005 C
Solar/Wind Harmer
1.342
274812UNIV PK N;8U
Adder
9.534
970373AG2-245 GEN
Solar/Wind Harmer
39.866
276776AD2-060 GEN
Solar/Wind Harmer
0.799
274801UNIV PARK;4U
Adder
11.02
941551AE2-152 GEN
Solar/Wind Harmer
8.523
274676JOLIET 29;8U
Adder
57.483
274674JOLIET 9 ;6U
Adder
28.794
274732ELWOOD EC;7P
Adder
30.711
274871GR RIDGE ;2U
Solar/Wind Harmer
14.337
270055AF2-134 C O1
Solar/Wind Harmer
5.618
274745AC1-111 GEN9
Adder
10.357
276691AA1-018 GEN1
Solar/Wind Harmer
0.851
274682WAUKEGAN ;7U
Adder
32.824
274828WAUKEGAN ;BP
Adder
20.145
958381AF2-132 GEN
Solar/Wind Harmer
16.482
964861AG1-349 GEN
Solar/Wind Harmer
14.25
971917AH1-482 GEN
Solar/Wind Harmer
16.444
971599AH1-298 GEN
50/50
20.529
24727205RPMNG3
50/50
2.029
270144AC1-141 ST1_
50/50
4.29
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
9.733
270435AC2-044 GEN
Solar/Wind Harmer
4.292
971347AH1-153 GEN
Solar/Wind Harmer
32.134
270071AF1-092 GEN
Solar/Wind Harmer
31.087
971771AH1-392 GEN
Solar/Wind Harmer
18.192
971769AH1-391 GEN
Solar/Wind Harmer
19.979
960681AF2-359 GEN
Solar/Wind Harmer
7.542
944161AF1-084 GEN
Solar/Wind Harmer
4.339
274775LINCOLN ;6U
Adder
12.031
274776LINCOLN ;7U
Adder
12.031
274777LINCOLN ;8U
Adder
12.031
24729505KEY G4
Adder
12.581
274814UNIV PK N;0U
Adder
9.617
274807UNIV PK N;3U
Adder
9.597
274805UNIV PK N;1U
Adder
9.555
274811UNIV PK N;7U
Adder
9.534
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.684
960591AF2-350 GEN
Solar/Wind Harmer
18.903
972227AH1-698 GEN1
Adder
4.926
274687WILL CNTY;4U
Adder
52.424
274687WILL CNTY;4U
Adder
52.424
274675JOLIET 29;7U
Adder
57.484
274675JOLIET 29;7U
Adder
55.431
274728ELWOOD EC;5P
Adder
30.711
274731ELWOOD EC;2P
Adder
30.71
274733ELWOOD EC;3P
Adder
30.71
274735ELWOOD EC;4P
Adder
30.71
970833AG2-524 GEN
Solar/Wind Harmer
16.286
274682WAUKEGAN ;7U
Adder
32.824
964401AG1-302 GEN
Solar/Wind Harmer
16.482
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
9.254
276799AD1-013 GEN
Solar/Wind Harmer
3.952
946671AF1-331 GEN
Solar/Wind Harmer
0.748
274855GSG-6 ;RU
Solar/Wind Harmer
6.597
274850MENDOTA H;RU
Solar/Wind Harmer
4.587
276602WESTBROOK C
Solar/Wind Harmer
3.797
276863AD2-134 GEN
Solar/Wind Harmer
3.19
959141AF2-205 GEN
Solar/Wind Harmer
10.776
972236AH1-702 GEN2
Adder
3.863
274760LEE CO EC;1U
Adder
16.13
274767LEE CO EC;8U
Adder
15.94
24728705AND G3
Adder
9.586
24728505AND G1
Adder
4.583
959091AF2-200 GEN
Solar/Wind Harmer
13.312
960751AF2-366 GEN
Solar/Wind Harmer
5.194
962781AG1-127 GEN
Solar/Wind Harmer
17.216
274872LEEDK;1U
Solar/Wind Harmer
14.832
939401AE1-172 GEN
Solar/Wind Harmer
25.153
276901AD2-066 C O1
Solar/Wind Harmer
6.326
965651AG1-433 GEN
Solar/Wind Harmer
9.83
971997AH1-543 GEN
Solar/Wind Harmer
28.2
276861AD2-134 GEN
Solar/Wind Harmer
3.19
274822ROCKFORD ;11
Adder
34.687
972235AH1-702 GEN1
Adder
4.443
274761LEE CO EC;2U
Adder
16.13
274766LEE CO EC;7U
Adder
15.94
24728605AND G2
Adder
4.583
270349AD2-093_GEN
Solar/Wind Helper
1.743
957471AF2-041 GEN
Solar/Wind Harmer
19.968
959081AF2-199 GEN
Solar/Wind Harmer
6.656
971067AG2-660 GEN
Solar/Wind Harmer
1.548
274764LEE CO EC;5U
Adder
16.168
274765LEE CO EC;6U
Adder
16.168
274762LEE CO EC;3U
Adder
16.13
274763LEE CO EC;4U
Adder
15.978
972267AH1-718 GEN
Adder
7.14
247621Y3-024
Adder
0.307
270471AD2-092_GEN
Solar/Wind Helper
1.743
971341AH1-150 GEN
Solar/Wind Harmer
13.312
971343AH1-151 GEN
Solar/Wind Harmer
13.312
970833AG2-524 GEN
Solar/Wind Harmer
7.575
270536AF1-215 GEN2
Solar/Wind Harmer
8.428
274746AC1-111 G10
Adder
10.357
274744AC1-111 GEN8
Adder
10.357
958711AF2-162 GEN
Solar/Wind Harmer
1.82
958391AF2-133 GEN
Solar/Wind Harmer
16.304
971177AH1-047 GEN
Solar/Wind Harmer
10.518
276868AE1-113 GEN
Solar/Wind Harmer
18.162
276882AE2-255 GEN
Solar/Wind Harmer
6.054
971411AH1-196 GEN
Solar/Wind Harmer
26.803
971675AH1-338 GEN
Solar/Wind Harmer
32.161
971549AH1-272 GEN
Solar/Wind Harmer
32.93
274863CRW1-WTG
Solar/Wind Harmer
9.908
274864CRW2-WTG
Solar/Wind Harmer
9.908
274823ROCKFORD ;21
Adder
34.435
270284AF1-227 GEN1
Solar/Wind Helper
2.32
270286AF1-227 GEN2
Solar/Wind Helper
0.851
270287AF1-227 GEN3
Solar/Wind Helper
0.851
270054AF2-122 C O1
Solar/Wind Helper
1.203
971171AH1-044 GEN
Solar/Wind Harmer
13.312
944201AF1-088_MTX
Adder
133.023
957141AF2-008_MTX
Adder
52.933
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.282
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.706
MECLTFEXP_MEC->PJM
CLTF
24.31
SIGELTFEXP_SIGE->PJM
CLTF
0.467
LAGNLTFEXP_LAGN->PJM
CLTF
13.148
TVALTFEXP_TVA->PJM
CLTF
5.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.577
NYPJM->LTFIMP_NY
CLTF
3.196
LGEELTFEXP_LGEE->PJM
CLTF
4.313
WECLTFEXP_WEC->PJM
CLTF
6.719
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.8
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.633

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P7-1_#11010___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11010___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:141.23 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5849.93
MW Contribution:60.64
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.85
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.183
24642205MAYFLWER
50/50
1.35
944961AF1-161 GEN
50/50
5.755
962601AG1-109 GEN
50/50
5.755
270043AE2-236 GEN
Solar/Wind Harmer
11.845
970349AG2-230 GEN
Solar/Wind Harmer
32.247
970513AG2-328 GEN
Solar/Wind Harmer
37.354
970517AG2-330 GEN
Solar/Wind Harmer
33.879
959331AF2-224 GEN
Solar/Wind Harmer
20.561
965021AG1-366 GEN
Solar/Wind Harmer
4.782
247643Z2-116 C
Solar/Wind Harmer
0.142
970031AG2-029 GEN
Solar/Wind Harmer
60.641
944531AF1-118 GEN
Solar/Wind Harmer
70.444
945111AF1-176 GEN
Solar/Wind Harmer
11.293
274772LINCOLN ;3U
Adder
12.075
24441205WTRV SLR C
Solar/Wind Harmer
0.261
274724RIVER EC ;11
Adder
34.095
972231SS25-0005
Solar/Wind Harmer
18.237
972181SS23-001
Solar/Wind Harmer
11.398
274752CRETE EC ;2U
Adder
9.392
274753CRETE EC ;3U
Adder
9.392
247604X1-042
Adder
0.796
970707AG2-453 GEN
Solar/Wind Harmer
53.373
274802UNIV PARK;5U
Adder
11.073
274826FISK ;BP
Adder
20.79
276772AC2-154 GEN
Solar/Wind Harmer
5.29
276806AD2-047 C O1
Solar/Wind Harmer
20.292
970941AG2-585 GEN
Solar/Wind Harmer
23.711
274800UNIV PARK;3U
Adder
11.059
972038AH1-567 GEN2
Adder
0.692
972228AH1-698 GEN2
Adder
7.021
276897AD1-100 C
Solar/Wind Harmer
54.734
939351AE1-166 GEN
Solar/Wind Harmer
11.184
274676JOLIET 29;8U
Adder
55.629
274730ELWOOD EC;6P
Adder
30.821
274734ELWOOD EC;8P
Adder
30.821
274736ELWOOD EC;9P
Adder
30.821
274729ELWOOD EC;1P
Adder
30.821
276893AG1-478 C
Solar/Wind Harmer
0.783
943121AE2-341 GEN
Solar/Wind Harmer
27.954
943591AF1-030 GEN
Solar/Wind Harmer
18.636
270535AF1-215 GEN1
Solar/Wind Harmer
8.453
24344105CKG2
50/50
16.81
270143AC1-141 CT2_
50/50
4.85
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.355
24307105BERRINSP G
50/50
0.043
970245AG2-165 GEN
Solar/Wind Harmer
37.354
965011AG1-365 GEN
Solar/Wind Harmer
20.561
270063AE2-323 C
Solar/Wind Harmer
4.439
270505AE1-170 C O1
Solar/Wind Harmer
30.051
945111AF1-176 GEN
Solar/Wind Harmer
35.632
270449AD2-020 GEN
Solar/Wind Harmer
5.549
943021AE2-325 GEN
Solar/Wind Harmer
7.21
972207SS24-0001
Solar/Wind Harmer
42.931
274773LINCOLN ;4U
Adder
12.075
274774LINCOLN ;5U
Adder
12.075
274723RIVER EC ;12
Adder
34.493
274751CRETE EC ;1U
Adder
9.392
274754CRETE EC ;4U
Adder
9.392
276164X3-005 C
Solar/Wind Harmer
1.346
274812UNIV PK N;8U
Adder
9.565
970373AG2-245 GEN
Solar/Wind Harmer
39.985
276776AD2-060 GEN
Solar/Wind Harmer
0.802
274801UNIV PARK;4U
Adder
11.059
941551AE2-152 GEN
Solar/Wind Harmer
8.554
274676JOLIET 29;8U
Adder
57.689
274674JOLIET 9 ;6U
Adder
28.897
274732ELWOOD EC;7P
Adder
30.821
274871GR RIDGE ;2U
Solar/Wind Harmer
14.39
270055AF2-134 C O1
Solar/Wind Harmer
5.635
274745AC1-111 GEN9
Adder
10.396
276691AA1-018 GEN1
Solar/Wind Harmer
0.854
274682WAUKEGAN ;7U
Adder
32.947
274828WAUKEGAN ;BP
Adder
20.221
958381AF2-132 GEN
Solar/Wind Harmer
16.533
964861AG1-349 GEN
Solar/Wind Harmer
14.293
971917AH1-482 GEN
Solar/Wind Harmer
16.494
965651AG1-433 GEN
Solar/Wind Harmer
9.938
960751AF2-366 GEN
Solar/Wind Harmer
5.214
962781AG1-127 GEN
Solar/Wind Harmer
17.282
274872LEEDK;1U
Solar/Wind Harmer
14.889
939401AE1-172 GEN
Solar/Wind Harmer
25.25
276901AD2-066 C O1
Solar/Wind Harmer
6.35
971997AH1-543 GEN
Solar/Wind Harmer
28.31
276861AD2-134 GEN
Solar/Wind Harmer
3.203
274822ROCKFORD ;11
Adder
34.824
972235AH1-702 GEN1
Adder
4.461
274761LEE CO EC;2U
Adder
16.195
274766LEE CO EC;7U
Adder
16.004
24728605AND G2
Adder
4.622
970091AG2-072 GEN
Adder
1.052
270349AD2-093_GEN
Solar/Wind Helper
1.724
957471AF2-041 GEN
Solar/Wind Harmer
42.297
959081AF2-199 GEN
Solar/Wind Harmer
14.099
971067AG2-660 GEN
Solar/Wind Harmer
3.279
971599AH1-298 GEN
50/50
20.751
270144AC1-141 ST1_
50/50
4.296
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.026
24729505KEY G4
50/50
13.5
971347AH1-153 GEN
Solar/Wind Harmer
32.247
270071AF1-092 GEN
Solar/Wind Harmer
31.239
971771AH1-392 GEN
Solar/Wind Harmer
18.224
971769AH1-391 GEN
Solar/Wind Harmer
20.026
960681AF2-359 GEN
Solar/Wind Harmer
7.564
944161AF1-084 GEN
Solar/Wind Harmer
4.344
276694AA1-018 GEN2
Solar/Wind Harmer
11.579
274682WAUKEGAN ;7U
Adder
32.947
964401AG1-302 GEN
Solar/Wind Harmer
16.533
274872LEEDK;1U
Solar/Wind Harmer
0.464
276805AD2-038 GEN
Solar/Wind Harmer
9.289
276799AD1-013 GEN
Solar/Wind Harmer
3.967
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
6.623
274850MENDOTA H;RU
Solar/Wind Harmer
4.605
276602WESTBROOK C
Solar/Wind Harmer
3.812
276863AD2-134 GEN
Solar/Wind Harmer
3.203
959141AF2-205 GEN
Solar/Wind Harmer
10.81
972236AH1-702 GEN2
Adder
3.879
274760LEE CO EC;1U
Adder
16.195
274767LEE CO EC;8U
Adder
16.004
24728705AND G3
Adder
9.666
24728505AND G1
Adder
4.622
959091AF2-200 GEN
Solar/Wind Harmer
28.198
970615AG2-402 GEN
50/50
4.782
270102X2-052 ST
50/50
3.225
270100X2-052 CT1
50/50
2.972
270101X2-052 CT2
50/50
2.972
247620Y3-023
50/50
0.979
24729405KEY G3
50/50
0.737
24729305KEY G2
50/50
0.724
24729205KEY G1
50/50
0.721
970321AG2-212 GEN
Solar/Wind Harmer
37.354
970611AG2-400 GEN
Solar/Wind Harmer
20.561
270216AD2-079_GEN
Solar/Wind Harmer
1.23
270526AF1-158 GEN
Solar/Wind Harmer
9.119
24441505OLIV SLR
Solar/Wind Harmer
0.268
965681AG1-436 GEN
Solar/Wind Harmer
25.028
965791AG1-447 GEN
Solar/Wind Harmer
12.805
957891AF2-083 GEN
Solar/Wind Harmer
6.749
960981AF2-389 GEN
Solar/Wind Harmer
3.024
961051AF2-396 GEN
Solar/Wind Harmer
31.526
961051AF2-396 GEN
Solar/Wind Harmer
14.663
274770LINCOLN ;1U
Adder
12.075
274771LINCOLN ;2U
Adder
12.075
274808UNIV PK N;4U
Adder
9.523
274803UNIV PARK;6U
Adder
11.073
972259AH1-714 GEN
Adder
36.205
274888KELLY CRK;1U
Solar/Wind Harmer
11.199
274887GEN-1.85
Solar/Wind Harmer
10.111
276843GEN-1.7
Solar/Wind Harmer
1.088
958011AF2-095 GEN
Solar/Wind Harmer
27.315
274674JOLIET 9 ;6U
Adder
28.897
274847GR RIDGE ;BU
Solar/Wind Harmer
9.466
971573AH1-285 GEN
Solar/Wind Harmer
15.928
274695ROCKY RD ;2P
Adder
20.447
274693ROCKY RD ;1P
Adder
20.246
274697ROCKY RD ;3P
Adder
5.555
274696ROCKY RD ;4P
Adder
20.929
958481AF2-142 GEN
Solar/Wind Harmer
27.523
274861TOP CROP ;1U
Solar/Wind Harmer
11.112
274862TOP CROP ;2U
Solar/Wind Harmer
9.279
274683WAUKEGAN ;8U
Adder
38.577
274683WAUKEGAN ;8U
Adder
32.519
962691AG1-118 GEN
Solar/Wind Harmer
54.666
944541AF1-119 GEN
Solar/Wind Harmer
7.616
960971AF2-388 GEN
Solar/Wind Harmer
19.875
970921AG2-575 GEN
Solar/Wind Harmer
18.172
970921AG2-575 GEN
Solar/Wind Harmer
4.226
958491AF2-143 GEN
Solar/Wind Harmer
27.161
942991AE2-321 GEN
Solar/Wind Harmer
18.026
274879MINONK ;1U
Solar/Wind Harmer
12.156
971333AH1-146 GEN
Solar/Wind Harmer
35.848
971335AH1-147 GEN
Solar/Wind Harmer
35.848
274764LEE CO EC;5U
Adder
16.233
274765LEE CO EC;6U
Adder
16.233
274762LEE CO EC;3U
Adder
16.195
274763LEE CO EC;4U
Adder
16.043
972267AH1-718 GEN
Adder
7.169
247621Y3-024
Adder
0.306
270471AD2-092_GEN
Solar/Wind Helper
1.724
971341AH1-150 GEN
Solar/Wind Harmer
28.198
971343AH1-151 GEN
Solar/Wind Harmer
28.198
274775LINCOLN ;6U
Adder
12.075
274776LINCOLN ;7U
Adder
12.075
274777LINCOLN ;8U
Adder
12.075
274814UNIV PK N;0U
Adder
9.649
274807UNIV PK N;3U
Adder
9.628
274805UNIV PK N;1U
Adder
9.586
274811UNIV PK N;7U
Adder
9.565
972037AH1-567 GEN1
Adder
0.348
274827FISK ;RP
Adder
14.734
960591AF2-350 GEN
Solar/Wind Harmer
18.969
972227AH1-698 GEN1
Adder
4.944
274687WILL CNTY;4U
Adder
52.61
274687WILL CNTY;4U
Adder
52.61
274675JOLIET 29;7U
Adder
57.69
274675JOLIET 29;7U
Adder
55.63
274728ELWOOD EC;5P
Adder
30.821
274731ELWOOD EC;2P
Adder
30.821
274733ELWOOD EC;3P
Adder
30.821
274735ELWOOD EC;4P
Adder
30.821
970833AG2-524 GEN
Solar/Wind Harmer
16.346
970833AG2-524 GEN
Solar/Wind Harmer
7.603
270536AF1-215 GEN2
Solar/Wind Harmer
8.453
274746AC1-111 G10
Adder
10.396
274744AC1-111 GEN8
Adder
10.396
958711AF2-162 GEN
Solar/Wind Harmer
1.84
958391AF2-133 GEN
Solar/Wind Harmer
16.354
971177AH1-047 GEN
Solar/Wind Harmer
10.559
276868AE1-113 GEN
Solar/Wind Harmer
18.232
276882AE2-255 GEN
Solar/Wind Harmer
6.078
971411AH1-196 GEN
Solar/Wind Harmer
26.908
971675AH1-338 GEN
Solar/Wind Harmer
32.287
971549AH1-272 GEN
Solar/Wind Harmer
32.985
274863CRW1-WTG
Solar/Wind Harmer
9.948
274864CRW2-WTG
Solar/Wind Harmer
9.948
274823ROCKFORD ;21
Adder
34.571
270284AF1-227 GEN1
Solar/Wind Helper
2.284
270286AF1-227 GEN2
Solar/Wind Helper
0.838
270287AF1-227 GEN3
Solar/Wind Helper
0.838
270054AF2-122 C O1
Solar/Wind Helper
1.189
971171AH1-044 GEN
Solar/Wind Harmer
28.198
944201AF1-088_MTX
Adder
133.959
957141AF2-008_MTX
Adder
66.98
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.245
CBM West 1LTFEXP_CBM-W1->PJM
CBM
202.385
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.042
MECLTFEXP_MEC->PJM
CLTF
24.435
SIGELTFEXP_SIGE->PJM
CLTF
0.471
LAGNLTFEXP_LAGN->PJM
CLTF
13.321
TVALTFEXP_TVA->PJM
CLTF
5.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.715
NYPJM->LTFIMP_NY
CLTF
3.14
LGEELTFEXP_LGEE->PJM
CLTF
4.376
WECLTFEXP_WEC->PJM
CLTF
6.746
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.739
AG2-052LTFEXP_AG2-052->PJM
LTF
0.423
AH1-155LTFEXP_AH1-155->PJM
LTF
0.635

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#6463_16757_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#6463_16757_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.14 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5804.66
MW Contribution:9.25
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
16.743
24727005RPMNG1
50/50
2.036
270143AC1-141 CT2_
50/50
4.84
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.369
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
14.965
965421AG1-410 GEN
Solar/Wind Harmer
44.849
246936BC-WTG1
Solar/Wind Harmer
0.606
270489AE1-102 GEN1
Solar/Wind Harmer
1.943
970245AG2-165 GEN
Solar/Wind Harmer
6.295
270063AE2-323 C
Solar/Wind Harmer
0.012
270505AE1-170 C O1
Solar/Wind Harmer
14.646
945111AF1-176 GEN
Solar/Wind Harmer
24.826
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.196
274773LINCOLN ;4U
Adder
16.368
274774LINCOLN ;5U
Adder
16.368
274723RIVER EC ;12
Adder
34.361
274751CRETE EC ;1U
Adder
15.774
274754CRETE EC ;4U
Adder
15.774
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
9.528
970373AG2-245 GEN
Solar/Wind Harmer
27.796
274801UNIV PARK;4U
Adder
11.014
276776AD2-060 GEN
Solar/Wind Harmer
1.376
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
57.45
274674JOLIET 9 ;6U
Adder
28.777
274732ELWOOD EC;7P
Adder
30.693
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.01
274745AC1-111 GEN9
Adder
10.351
276691AA1-018 GEN1
Solar/Wind Harmer
1.544
274682WAUKEGAN ;7U
Adder
32.805
274828WAUKEGAN ;BP
Adder
20.134
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
16.434
962781AG1-127 GEN
Solar/Wind Harmer
12.012
274872LEEDK;1U
Solar/Wind Harmer
0.008
939401AE1-172 GEN
Solar/Wind Harmer
9.413
276901AD2-066 C O1
Solar/Wind Harmer
0.012
965651AG1-433 GEN
Solar/Wind Harmer
3.678
971997AH1-543 GEN
Solar/Wind Harmer
6.554
276861AD2-134 GEN
Solar/Wind Harmer
0.223
957471AF2-041 GEN
Solar/Wind Harmer
37.108
959081AF2-199 GEN
Solar/Wind Harmer
12.369
971067AG2-660 GEN
Solar/Wind Harmer
4.123
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
34.667
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
15.377
972235AH1-702 GEN1
Adder
4.441
970819AG2-516 GEN
Solar/Wind Harmer
14.695
958861AF2-177 GEN
Solar/Wind Harmer
5.294
971475AH1-234 GEN
Solar/Wind Harmer
5.925
970569AG2-363 GEN
Solar/Wind Harmer
36.555
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
16.12
274766LEE CO EC;7U
Adder
15.93
276158O29GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
3.153
274877BISHOP HL;1U
Solar/Wind Harmer
0.397
24791305MDL-5G
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
16.327
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
9.129
247521TR3_G114
Solar/Wind Harmer
0.393
270246TR4_N_V150
Solar/Wind Harmer
0.07
970291AG2-192 GEN
Solar/Wind Harmer
1.393
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
4.146
963741AG1-226 GEN
Solar/Wind Harmer
24.913
276615X2-022 GEN
Solar/Wind Harmer
0.11
270032AE2-172
Solar/Wind Harmer
6.993
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.203
965031AG1-367 GEN
Solar/Wind Harmer
10.168
276903AD2-071 C
Solar/Wind Harmer
11.298
965911AG1-460 GEN
Solar/Wind Harmer
2.014
970825AG2-519 GEN
Solar/Wind Harmer
3.499
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.684
247536S-71 GEN
Solar/Wind Harmer
0.341
24728605AND G2
Adder
4.579
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970333AG2-219 GEN
Solar/Wind Harmer
5.528
970773AG2-487 GEN
Solar/Wind Harmer
1.34
270349AD2-093_GEN
Solar/Wind Helper
1.737
970615AG2-402 GEN
50/50
4.988
270102X2-052 ST
50/50
3.214
270100X2-052 CT1
50/50
2.961
270101X2-052 CT2
50/50
2.961
247620Y3-023
50/50
0.98
970611AG2-400 GEN
Solar/Wind Harmer
14.965
970627AG2-408 GEN
Solar/Wind Harmer
4.49
246938BC-WTG3
Solar/Wind Harmer
0.542
246937BC-WTG2
Solar/Wind Harmer
0.606
970321AG2-212 GEN
Solar/Wind Harmer
6.295
270216AD2-079_GEN
Solar/Wind Harmer
0.002
270526AF1-158 GEN
Solar/Wind Harmer
0.017
957891AF2-083 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
17.4
965791AG1-447 GEN
Solar/Wind Harmer
12.76
961051AF2-396 GEN
Solar/Wind Harmer
27.667
961051AF2-396 GEN
Solar/Wind Harmer
18.445
274770LINCOLN ;1U
Adder
16.368
274771LINCOLN ;2U
Adder
16.368
274808UNIV PK N;4U
Adder
9.487
274803UNIV PARK;6U
Adder
11.029
972259AH1-714 GEN
Adder
36.054
274888KELLY CRK;1U
Solar/Wind Harmer
0.774
274887GEN-1.85
Solar/Wind Harmer
0.347
276843GEN-1.7
Solar/Wind Harmer
0.427
958011AF2-095 GEN
Solar/Wind Harmer
18.98
274674JOLIET 9 ;6U
Adder
28.777
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.397
274695ROCKY RD ;2P
Adder
20.358
274693ROCKY RD ;1P
Adder
20.158
274697ROCKY RD ;3P
Adder
5.53
274696ROCKY RD ;4P
Adder
20.838
958481AF2-142 GEN
Solar/Wind Harmer
19.12
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.724
274683WAUKEGAN ;8U
Adder
38.41
274683WAUKEGAN ;8U
Adder
32.378
962691AG1-118 GEN
Solar/Wind Harmer
37.971
970921AG2-575 GEN
Solar/Wind Harmer
12.623
970921AG2-575 GEN
Solar/Wind Harmer
4.208
958491AF2-143 GEN
Solar/Wind Harmer
18.868
944541AF1-119 GEN
Solar/Wind Harmer
0.84
960971AF2-388 GEN
Solar/Wind Harmer
7.355
942991AE2-321 GEN
Solar/Wind Harmer
13.981
274879MINONK ;1U
Solar/Wind Harmer
0.528
971333AH1-146 GEN
Solar/Wind Harmer
24.899
971335AH1-147 GEN
Solar/Wind Harmer
24.899
971341AH1-150 GEN
Solar/Wind Harmer
24.739
971343AH1-151 GEN
Solar/Wind Harmer
24.739
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.288
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.879
274764LEE CO EC;5U
Adder
16.158
274765LEE CO EC;6U
Adder
16.158
274762LEE CO EC;3U
Adder
16.12
274763LEE CO EC;4U
Adder
15.968
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
7.136
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
276741O09 GEN1
Solar/Wind Harmer
0.425
276708O09 GEN2
Solar/Wind Harmer
0.425
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.467
276646AC1-214 GEN2
Solar/Wind Harmer
0.467
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.81
966841AG1-555 GEN
Solar/Wind Harmer
1.27
270599AE1-208 GEN
Solar/Wind Harmer
9.916
270031AE2-169
Solar/Wind Harmer
5.95
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
6.141
971613AH1-306 GEN
Solar/Wind Harmer
5.035
276916AD2-100_GEN
Solar/Wind Harmer
20.939
276911AD2-131_GEN
Solar/Wind Harmer
1.379
960441AF2-335 GEN
Solar/Wind Harmer
9.92
970825AG2-519 GEN
Solar/Wind Harmer
10.923
945391AF1-204 GEN
Solar/Wind Harmer
9.973
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.306
970623AG2-406 GEN
Solar/Wind Harmer
1.558
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
5.849
970883AG2-550 GEN
Solar/Wind Harmer
7.917
970885AG2-551 GEN
Solar/Wind Harmer
2.639
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.933
270471AD2-092_GEN
Solar/Wind Helper
1.737
24727105RPMNG2
50/50
2.043
965431AG1-411 GEN
50/50
24.916
270142AC1-141 CT1_
50/50
4.84
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.145
24642205MAYFLWER
50/50
1.347
944961AF1-161 GEN
50/50
5.744
962601AG1-109 GEN
50/50
5.744
270043AE2-236 GEN
Solar/Wind Harmer
9.614
959331AF2-224 GEN
Solar/Wind Harmer
10.476
965021AG1-366 GEN
Solar/Wind Harmer
4.988
270491AE1-102 GEN2
Solar/Wind Harmer
1.943
970349AG2-230 GEN
Solar/Wind Harmer
22.406
970513AG2-328 GEN
Solar/Wind Harmer
6.295
970517AG2-330 GEN
Solar/Wind Harmer
37.773
970031AG2-029 GEN
Solar/Wind Harmer
9.246
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.278
944531AF1-118 GEN
Solar/Wind Harmer
62.173
274772LINCOLN ;3U
Adder
16.368
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
33.965
274752CRETE EC ;2U
Adder
15.774
274753CRETE EC ;3U
Adder
15.774
247604X1-042
Adder
0.795
970707AG2-453 GEN
Solar/Wind Harmer
43.26
274802UNIV PARK;5U
Adder
11.029
274826FISK ;BP
Adder
20.707
274800UNIV PARK;3U
Adder
11.014
972038AH1-567 GEN2
Adder
0.689
276806AD2-047 C O1
Solar/Wind Harmer
7.469
970941AG2-585 GEN
Solar/Wind Harmer
16.476
972228AH1-698 GEN2
Adder
6.992
276897AD1-100 C
Solar/Wind Harmer
0.017
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
55.398
274729ELWOOD EC;1P
Adder
30.692
274730ELWOOD EC;6P
Adder
30.693
274734ELWOOD EC;8P
Adder
30.693
274736ELWOOD EC;9P
Adder
30.693
276893AG1-478 C
Solar/Wind Harmer
0.516
943121AE2-341 GEN
Solar/Wind Harmer
21.706
943591AF1-030 GEN
Solar/Wind Harmer
14.435
270535AF1-215 GEN1
Solar/Wind Harmer
0.016
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
32.805
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
0.004
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.457
274850MENDOTA H;RU
Solar/Wind Harmer
0.147
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
959091AF2-200 GEN
Solar/Wind Harmer
24.739
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.861
970571AG2-364 GEN
Solar/Wind Harmer
24.37
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
16.12
274767LEE CO EC;8U
Adder
15.93
276157O29GEN1
Solar/Wind Harmer
1.927
274878BISHOP HL;2U
Solar/Wind Harmer
0.397
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
11.712
942111AE2-223 GEN
Solar/Wind Harmer
3.79
965931AG1-462 GEN
Solar/Wind Harmer
29.323
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
34.294
959611AF2-252 GEN
Solar/Wind Harmer
3.81
247642Z2-115 C
Solar/Wind Harmer
0.005
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.07
970289AG2-191 GEN
Solar/Wind Harmer
1.179
970291AG2-192 GEN
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.944
276668AB2-070 GEN1
Solar/Wind Harmer
0.39
276621W2-048 GEN
Solar/Wind Harmer
0.529
276838X2-022 GEN2
Solar/Wind Harmer
0.591
971617AH1-308 GEN
Solar/Wind Harmer
8.654
958821AF2-173 GEN
Solar/Wind Harmer
14.235
270004AE1-209 GEN
Solar/Wind Harmer
2.203
942481AE2-261 GEN
Solar/Wind Harmer
30.115
946031AF1-268 GEN
Solar/Wind Harmer
9.153
970193AG2-126 GEN
Solar/Wind Harmer
14.08
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.732
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.579
970243AG2-164 GEN
Solar/Wind Harmer
4.523
970519AG2-331 GEN
Solar/Wind Harmer
20.102
970699AG2-449 GEN
Solar/Wind Harmer
1.933
270356AE2-297 GEN
Solar/Wind Harmer
0.01
971599AH1-298 GEN
50/50
20.512
24727205RPMNG3
50/50
2.026
270144AC1-141 ST1_
50/50
4.287
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.893
971347AH1-153 GEN
Solar/Wind Harmer
22.406
270071AF1-092 GEN
Solar/Wind Harmer
27.685
971771AH1-392 GEN
Solar/Wind Harmer
14.093
971619AH1-309 GEN
Solar/Wind Harmer
6.277
971769AH1-391 GEN
Solar/Wind Harmer
15.555
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274775LINCOLN ;6U
Adder
16.368
274776LINCOLN ;7U
Adder
16.368
274777LINCOLN ;8U
Adder
16.368
24729505KEY G4
Adder
12.57
274814UNIV PK N;0U
Adder
9.612
274807UNIV PK N;3U
Adder
9.591
274805UNIV PK N;1U
Adder
9.549
274811UNIV PK N;7U
Adder
9.528
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.675
960591AF2-350 GEN
Solar/Wind Harmer
13.18
972227AH1-698 GEN1
Adder
4.923
274687WILL CNTY;4U
Adder
52.393
274687WILL CNTY;4U
Adder
52.393
274675JOLIET 29;7U
Adder
57.451
274675JOLIET 29;7U
Adder
55.399
274731ELWOOD EC;2P
Adder
30.692
274733ELWOOD EC;3P
Adder
30.692
274735ELWOOD EC;4P
Adder
30.692
274728ELWOOD EC;5P
Adder
30.693
970833AG2-524 GEN
Solar/Wind Harmer
14.308
970833AG2-524 GEN
Solar/Wind Harmer
9.539
270536AF1-215 GEN2
Solar/Wind Harmer
0.016
274746AC1-111 G10
Adder
10.351
274744AC1-111 GEN8
Adder
10.351
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971177AH1-047 GEN
Solar/Wind Harmer
7.718
276868AE1-113 GEN
Solar/Wind Harmer
2.511
276882AE2-255 GEN
Solar/Wind Harmer
1.463
971411AH1-196 GEN
Solar/Wind Harmer
18.689
971675AH1-338 GEN
Solar/Wind Harmer
4.859
971549AH1-272 GEN
Solar/Wind Harmer
25.626
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
24.739
274823ROCKFORD ;21
Adder
34.415
971611AH1-305 GEN
Solar/Wind Harmer
7.323
963791AG1-232 GEN
Solar/Wind Harmer
16.568
276612AE2-035 GEN
Solar/Wind Harmer
0.003
965101AG1-375 GEN
Solar/Wind Harmer
12.216
926823AC1-168 GEN
Solar/Wind Harmer
2.071
970169AG2-114 GEN
Solar/Wind Harmer
12.156
971681AH1-341 GEN
Solar/Wind Harmer
19.553
961011AF2-392 GEN
Solar/Wind Harmer
7.036
965041AG1-368 GEN
Solar/Wind Harmer
11.932
957751AF2-069 GEN
Solar/Wind Harmer
0.392
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
12.245
941731AE2-173 GEN
Solar/Wind Harmer
9.718
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
6.48
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.707
971609AH1-304 GEN
Solar/Wind Harmer
1.767
965051AG1-369 GEN
Solar/Wind Harmer
5.379
970289AG2-191 GEN
Solar/Wind Harmer
2.036
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.39
276848AB2-070 GEN3
Solar/Wind Harmer
0.388
270594AE1-207 GEN
Solar/Wind Harmer
11.748
270024AE2-089 GEN
Solar/Wind Harmer
0.011
970115AG2-085 GEN
Solar/Wind Harmer
3.968
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
5.647
270240V3-007_GEN2
Solar/Wind Harmer
0.003
247607V1-011 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
10.94
971673AH1-337 GEN
Solar/Wind Harmer
4.593
270284AF1-227 GEN1
Solar/Wind Helper
2.302
270286AF1-227 GEN2
Solar/Wind Helper
0.844
270287AF1-227 GEN3
Solar/Wind Helper
0.844
270054AF2-122 C O1
Solar/Wind Helper
1.201
944201AF1-088_MTX
Adder
132.938
957141AF2-008_MTX
Adder
17.09
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.281
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.695
MECLTFEXP_MEC->PJM
CLTF
24.295
SIGELTFEXP_SIGE->PJM
CLTF
0.466
LAGNLTFEXP_LAGN->PJM
CLTF
13.14
TVALTFEXP_TVA->PJM
CLTF
5.018
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.505
NYPJM->LTFIMP_NY
CLTF
3.194
LGEELTFEXP_LGEE->PJM
CLTF
4.31
WECLTFEXP_WEC->PJM
CLTF
6.715
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.799
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.632

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P7-1_#17567_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#17567_SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:140.03 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5799.9
MW Contribution:57.56
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.706
24344005CKG1
50/50
12.844
24641605TWIN BRNCH
50/50
0.034
24642205MAYFLWER
50/50
1.31
944961AF1-161 GEN
50/50
5.605
962601AG1-109 GEN
50/50
5.605
970349AG2-230 GEN
Solar/Wind Harmer
31.136
270043AE2-236 GEN
Solar/Wind Harmer
11.189
970513AG2-328 GEN
Solar/Wind Harmer
36.028
970517AG2-330 GEN
Solar/Wind Harmer
32.677
247643Z2-116 C
Solar/Wind Harmer
0.137
945111AF1-176 GEN
Solar/Wind Harmer
10.963
970031AG2-029 GEN
Solar/Wind Harmer
57.557
24441205WTRV SLR C
Solar/Wind Harmer
0.256
944531AF1-118 GEN
Solar/Wind Harmer
66.164
959331AF2-224 GEN
Solar/Wind Harmer
18.821
965021AG1-366 GEN
Solar/Wind Harmer
4.377
274772LINCOLN ;3U
Adder
11.65
247604X1-042
Adder
0.782
274724RIVER EC ;11
Adder
32.899
972231SS25-0005
Solar/Wind Harmer
17.6
972181SS23-001
Solar/Wind Harmer
11
274752CRETE EC ;2U
Adder
9.065
274753CRETE EC ;3U
Adder
9.065
970707AG2-453 GEN
Solar/Wind Harmer
51.485
24344105CKG2
50/50
16.266
270143AC1-141 CT2_
50/50
4.706
24639705ELKHART HY
50/50
0.317
970521AG2-332 GEN
50/50
22.545
24307105BERRINSP G
50/50
0.042
970245AG2-165 GEN
Solar/Wind Harmer
36.028
270505AE1-170 C O1
Solar/Wind Harmer
29.203
945111AF1-176 GEN
Solar/Wind Harmer
34.591
270063AE2-323 C
Solar/Wind Harmer
4.268
270449AD2-020 GEN
Solar/Wind Harmer
5.404
943021AE2-325 GEN
Solar/Wind Harmer
7.022
965011AG1-365 GEN
Solar/Wind Harmer
18.821
972207SS24-0001
Solar/Wind Harmer
41.419
274773LINCOLN ;4U
Adder
11.65
274774LINCOLN ;5U
Adder
11.65
274723RIVER EC ;12
Adder
33.283
274751CRETE EC ;1U
Adder
9.065
274754CRETE EC ;4U
Adder
9.065
276164X3-005 C
Solar/Wind Harmer
1.299
274812UNIV PK N;8U
Adder
9.23
970373AG2-245 GEN
Solar/Wind Harmer
38.641
274801UNIV PARK;4U
Adder
10.668
276776AD2-060 GEN
Solar/Wind Harmer
0.774
941551AE2-152 GEN
Solar/Wind Harmer
8.252
274676JOLIET 29;8U
Adder
55.648
274674JOLIET 9 ;6U
Adder
27.874
274732ELWOOD EC;7P
Adder
29.73
274871GR RIDGE ;2U
Solar/Wind Harmer
13.88
270055AF2-134 C O1
Solar/Wind Harmer
5.442
274745AC1-111 GEN9
Adder
10.026
276691AA1-018 GEN1
Solar/Wind Harmer
0.824
274682WAUKEGAN ;7U
Adder
31.772
274828WAUKEGAN ;BP
Adder
19.5
958381AF2-132 GEN
Solar/Wind Harmer
15.959
964861AG1-349 GEN
Solar/Wind Harmer
13.796
971917AH1-482 GEN
Solar/Wind Harmer
15.92
960751AF2-366 GEN
Solar/Wind Harmer
5.027
962781AG1-127 GEN
Solar/Wind Harmer
16.663
274872LEEDK;1U
Solar/Wind Harmer
14.356
939401AE1-172 GEN
Solar/Wind Harmer
24.351
276901AD2-066 C O1
Solar/Wind Harmer
6.124
971997AH1-543 GEN
Solar/Wind Harmer
27.297
276861AD2-134 GEN
Solar/Wind Harmer
3.088
965651AG1-433 GEN
Solar/Wind Harmer
9.384
274822ROCKFORD ;11
Adder
33.569
972235AH1-702 GEN1
Adder
4.3
274761LEE CO EC;2U
Adder
15.609
274766LEE CO EC;7U
Adder
15.425
24728605AND G2
Adder
4.468
972301AH1-735 GEN
Adder
2.524
270349AD2-093_GEN
Solar/Wind Helper
2.215
957471AF2-041 GEN
Solar/Wind Harmer
40.776
959081AF2-199 GEN
Solar/Wind Harmer
13.592
971067AG2-660 GEN
Solar/Wind Harmer
3.161
971599AH1-298 GEN
50/50
19.41
270144AC1-141 ST1_
50/50
4.168
24643105BUCHANAN
50/50
0.025
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
31.136
270071AF1-092 GEN
Solar/Wind Harmer
29.457
971771AH1-392 GEN
Solar/Wind Harmer
17.645
971769AH1-391 GEN
Solar/Wind Harmer
19.396
960681AF2-359 GEN
Solar/Wind Harmer
7.318
944161AF1-084 GEN
Solar/Wind Harmer
4.238
274775LINCOLN ;6U
Adder
11.65
274776LINCOLN ;7U
Adder
11.65
274777LINCOLN ;8U
Adder
11.65
24729505KEY G4
Adder
11.965
274814UNIV PK N;0U
Adder
9.311
274807UNIV PK N;3U
Adder
9.29
274805UNIV PK N;1U
Adder
9.25
274811UNIV PK N;7U
Adder
9.23
972037AH1-567 GEN1
Adder
0.335
270102X2-052 ST
50/50
3.121
270100X2-052 CT1
50/50
2.876
270101X2-052 CT2
50/50
2.876
247620Y3-023
50/50
0.945
970615AG2-402 GEN
50/50
4.377
970321AG2-212 GEN
Solar/Wind Harmer
36.028
270216AD2-079_GEN
Solar/Wind Harmer
1.189
270526AF1-158 GEN
Solar/Wind Harmer
8.831
957891AF2-083 GEN
Solar/Wind Harmer
6.556
960981AF2-389 GEN
Solar/Wind Harmer
2.938
24441505OLIV SLR
Solar/Wind Harmer
0.26
965681AG1-436 GEN
Solar/Wind Harmer
24.212
965791AG1-447 GEN
Solar/Wind Harmer
12.387
961051AF2-396 GEN
Solar/Wind Harmer
30.667
961051AF2-396 GEN
Solar/Wind Harmer
14.264
970611AG2-400 GEN
Solar/Wind Harmer
18.821
274770LINCOLN ;1U
Adder
11.65
274771LINCOLN ;2U
Adder
11.65
274808UNIV PK N;4U
Adder
9.189
274803UNIV PARK;6U
Adder
10.683
972259AH1-714 GEN
Adder
34.925
274888KELLY CRK;1U
Solar/Wind Harmer
10.804
274887GEN-1.85
Solar/Wind Harmer
9.754
276843GEN-1.7
Solar/Wind Harmer
1.049
958011AF2-095 GEN
Solar/Wind Harmer
26.352
274674JOLIET 9 ;6U
Adder
27.874
274847GR RIDGE ;BU
Solar/Wind Harmer
9.13
971573AH1-285 GEN
Solar/Wind Harmer
15.361
274695ROCKY RD ;2P
Adder
19.718
274693ROCKY RD ;1P
Adder
19.524
274697ROCKY RD ;3P
Adder
5.356
274696ROCKY RD ;4P
Adder
20.183
958481AF2-142 GEN
Solar/Wind Harmer
26.544
274861TOP CROP ;1U
Solar/Wind Harmer
10.717
274862TOP CROP ;2U
Solar/Wind Harmer
8.949
274683WAUKEGAN ;8U
Adder
37.2
274683WAUKEGAN ;8U
Adder
31.358
962691AG1-118 GEN
Solar/Wind Harmer
52.711
970921AG2-575 GEN
Solar/Wind Harmer
17.522
970921AG2-575 GEN
Solar/Wind Harmer
4.075
958491AF2-143 GEN
Solar/Wind Harmer
26.192
942991AE2-321 GEN
Solar/Wind Harmer
17.38
274879MINONK ;1U
Solar/Wind Harmer
11.721
971333AH1-146 GEN
Solar/Wind Harmer
34.561
971335AH1-147 GEN
Solar/Wind Harmer
34.561
944541AF1-119 GEN
Solar/Wind Harmer
7.192
960971AF2-388 GEN
Solar/Wind Harmer
18.769
274764LEE CO EC;5U
Adder
15.646
274765LEE CO EC;6U
Adder
15.646
274762LEE CO EC;3U
Adder
15.609
274763LEE CO EC;4U
Adder
15.462
972267AH1-718 GEN
Adder
6.909
247621Y3-024
Adder
0.305
270471AD2-092_GEN
Solar/Wind Helper
2.215
971341AH1-150 GEN
Solar/Wind Harmer
27.184
971343AH1-151 GEN
Solar/Wind Harmer
27.184
274802UNIV PARK;5U
Adder
10.683
274826FISK ;BP
Adder
20.057
970941AG2-585 GEN
Solar/Wind Harmer
22.875
274800UNIV PARK;3U
Adder
10.668
972038AH1-567 GEN2
Adder
0.668
276772AC2-154 GEN
Solar/Wind Harmer
5.103
276806AD2-047 C O1
Solar/Wind Harmer
19.577
972228AH1-698 GEN2
Adder
6.773
276897AD1-100 C
Solar/Wind Harmer
52.8
939351AE1-166 GEN
Solar/Wind Harmer
10.788
274676JOLIET 29;8U
Adder
53.66
274729ELWOOD EC;1P
Adder
29.73
274730ELWOOD EC;6P
Adder
29.73
274734ELWOOD EC;8P
Adder
29.73
274736ELWOOD EC;9P
Adder
29.73
276893AG1-478 C
Solar/Wind Harmer
0.755
943121AE2-341 GEN
Solar/Wind Harmer
26.96
943591AF1-030 GEN
Solar/Wind Harmer
17.973
270535AF1-215 GEN1
Solar/Wind Harmer
8.164
276694AA1-018 GEN2
Solar/Wind Harmer
11.167
274682WAUKEGAN ;7U
Adder
31.772
964401AG1-302 GEN
Solar/Wind Harmer
15.959
274872LEEDK;1U
Solar/Wind Harmer
0.447
276805AD2-038 GEN
Solar/Wind Harmer
8.958
276799AD1-013 GEN
Solar/Wind Harmer
3.825
946671AF1-331 GEN
Solar/Wind Harmer
0.724
274855GSG-6 ;RU
Solar/Wind Harmer
6.385
274850MENDOTA H;RU
Solar/Wind Harmer
4.44
276602WESTBROOK C
Solar/Wind Harmer
3.675
276863AD2-134 GEN
Solar/Wind Harmer
3.088
959141AF2-205 GEN
Solar/Wind Harmer
10.429
972236AH1-702 GEN2
Adder
3.739
274760LEE CO EC;1U
Adder
15.609
274767LEE CO EC;8U
Adder
15.425
24728705AND G3
Adder
9.344
24728505AND G1
Adder
4.468
959091AF2-200 GEN
Solar/Wind Harmer
27.184
274827FISK ;RP
Adder
14.215
960591AF2-350 GEN
Solar/Wind Harmer
18.3
972227AH1-698 GEN1
Adder
4.769
274687WILL CNTY;4U
Adder
50.75
274687WILL CNTY;4U
Adder
50.75
274675JOLIET 29;7U
Adder
55.649
274675JOLIET 29;7U
Adder
53.661
274731ELWOOD EC;2P
Adder
29.73
274733ELWOOD EC;3P
Adder
29.73
274735ELWOOD EC;4P
Adder
29.73
274728ELWOOD EC;5P
Adder
29.73
970833AG2-524 GEN
Solar/Wind Harmer
15.767
970833AG2-524 GEN
Solar/Wind Harmer
7.333
270536AF1-215 GEN2
Solar/Wind Harmer
8.164
274746AC1-111 G10
Adder
10.026
274744AC1-111 GEN8
Adder
10.026
971549AH1-272 GEN
Solar/Wind Harmer
32.892
958391AF2-133 GEN
Solar/Wind Harmer
15.781
971177AH1-047 GEN
Solar/Wind Harmer
10.18
276868AE1-113 GEN
Solar/Wind Harmer
17.58
276882AE2-255 GEN
Solar/Wind Harmer
5.86
971411AH1-196 GEN
Solar/Wind Harmer
25.942
971675AH1-338 GEN
Solar/Wind Harmer
31.127
274863CRW1-WTG
Solar/Wind Harmer
9.592
274864CRW2-WTG
Solar/Wind Harmer
9.592
958711AF2-162 GEN
Solar/Wind Harmer
1.737
274823ROCKFORD ;21
Adder
33.326
270054AF2-122 C O1
Solar/Wind Helper
1.3
971171AH1-044 GEN
Solar/Wind Harmer
27.184
944201AF1-088_MTX
Adder
128.814
957141AF2-008_MTX
Adder
64.407
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.385
CBM West 1LTFEXP_CBM-W1->PJM
CBM
204.072
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.768
MECLTFEXP_MEC->PJM
CLTF
23.493
SIGELTFEXP_SIGE->PJM
CLTF
0.454
LAGNLTFEXP_LAGN->PJM
CLTF
12.499
TVALTFEXP_TVA->PJM
CLTF
4.733
CBM West 2LTFEXP_CBM-W2->PJM
CBM
114.06
NYPJM->LTFIMP_NY
CLTF
3.145
LGEELTFEXP_LGEE->PJM
CLTF
4.258
WECLTFEXP_WEC->PJM
CLTF
6.502
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.96
AG2-052LTFEXP_AG2-052->PJM
LTF
0.408
AH1-155LTFEXP_AH1-155->PJM
LTF
0.612

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:135.98 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5632.19
MW Contribution:55.42
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.054
270100X2-052 CT1
50/50
2.814
270101X2-052 CT2
50/50
2.814
247620Y3-023
50/50
0.917
970321AG2-212 GEN
Solar/Wind Harmer
35.447
270216AD2-079_GEN
Solar/Wind Harmer
1.158
270526AF1-158 GEN
Solar/Wind Harmer
8.625
965681AG1-436 GEN
Solar/Wind Harmer
23.689
965791AG1-447 GEN
Solar/Wind Harmer
12.12
24441505OLIV SLR
Solar/Wind Harmer
0.254
957891AF2-083 GEN
Solar/Wind Harmer
6.386
960981AF2-389 GEN
Solar/Wind Harmer
2.861
961051AF2-396 GEN
Solar/Wind Harmer
29.854
961051AF2-396 GEN
Solar/Wind Harmer
13.886
274770LINCOLN ;1U
Adder
11.428
274771LINCOLN ;2U
Adder
11.428
274808UNIV PK N;4U
Adder
9.002
274803UNIV PARK;6U
Adder
10.468
972259AH1-714 GEN
Adder
34.24
274888KELLY CRK;1U
Solar/Wind Harmer
10.588
274887GEN-1.85
Solar/Wind Harmer
9.559
276843GEN-1.7
Solar/Wind Harmer
1.029
958011AF2-095 GEN
Solar/Wind Harmer
25.825
274674JOLIET 9 ;6U
Adder
27.32
970611AG2-400 GEN
Solar/Wind Harmer
17.715
274847GR RIDGE ;BU
Solar/Wind Harmer
8.95
971573AH1-285 GEN
Solar/Wind Harmer
15.059
274695ROCKY RD ;2P
Adder
19.327
274693ROCKY RD ;1P
Adder
19.137
274697ROCKY RD ;3P
Adder
5.25
274696ROCKY RD ;4P
Adder
19.783
958481AF2-142 GEN
Solar/Wind Harmer
26.008
274861TOP CROP ;1U
Solar/Wind Harmer
10.5
274862TOP CROP ;2U
Solar/Wind Harmer
8.768
274683WAUKEGAN ;8U
Adder
36.461
274683WAUKEGAN ;8U
Adder
30.735
962691AG1-118 GEN
Solar/Wind Harmer
51.667
970921AG2-575 GEN
Solar/Wind Harmer
17.175
970921AG2-575 GEN
Solar/Wind Harmer
3.994
958491AF2-143 GEN
Solar/Wind Harmer
25.662
942991AE2-321 GEN
Solar/Wind Harmer
17.034
274879MINONK ;1U
Solar/Wind Harmer
11.484
971333AH1-146 GEN
Solar/Wind Harmer
33.871
971335AH1-147 GEN
Solar/Wind Harmer
33.871
274764LEE CO EC;5U
Adder
15.33
274765LEE CO EC;6U
Adder
15.33
274762LEE CO EC;3U
Adder
15.294
274763LEE CO EC;4U
Adder
15.15
972267AH1-718 GEN
Adder
6.769
247621Y3-024
Adder
0.286
270471AD2-092_GEN
Solar/Wind Helper
1.84
971341AH1-150 GEN
Solar/Wind Harmer
32.581
971343AH1-151 GEN
Solar/Wind Harmer
32.581
24344005CKG1
50/50
12.539
270142AC1-141 CT1_
50/50
4.589
24641605TWIN BRNCH
50/50
0.033
24642205MAYFLWER
50/50
1.278
944961AF1-161 GEN
50/50
5.457
962601AG1-109 GEN
50/50
5.457
970349AG2-230 GEN
Solar/Wind Harmer
30.529
970513AG2-328 GEN
Solar/Wind Harmer
35.447
970517AG2-330 GEN
Solar/Wind Harmer
32.149
270043AE2-236 GEN
Solar/Wind Harmer
10.823
247643Z2-116 C
Solar/Wind Harmer
0.133
945111AF1-176 GEN
Solar/Wind Harmer
10.67
970031AG2-029 GEN
Solar/Wind Harmer
55.416
24441205WTRV SLR C
Solar/Wind Harmer
0.249
274772LINCOLN ;3U
Adder
11.428
944531AF1-118 GEN
Solar/Wind Harmer
64.152
247604X1-042
Adder
0.761
274724RIVER EC ;11
Adder
32.23
972231SS25-0005
Solar/Wind Harmer
17.235
972181SS23-001
Solar/Wind Harmer
10.772
274752CRETE EC ;2U
Adder
8.877
274753CRETE EC ;3U
Adder
8.877
970707AG2-453 GEN
Solar/Wind Harmer
50.49
274802UNIV PARK;5U
Adder
10.468
274826FISK ;BP
Adder
19.655
276772AC2-154 GEN
Solar/Wind Harmer
5.001
276806AD2-047 C O1
Solar/Wind Harmer
19.185
970941AG2-585 GEN
Solar/Wind Harmer
22.418
274800UNIV PARK;3U
Adder
10.455
972038AH1-567 GEN2
Adder
0.654
972228AH1-698 GEN2
Adder
6.639
276897AD1-100 C
Solar/Wind Harmer
51.755
939351AE1-166 GEN
Solar/Wind Harmer
10.575
274676JOLIET 29;8U
Adder
52.592
274729ELWOOD EC;1P
Adder
29.137
274730ELWOOD EC;6P
Adder
29.138
274734ELWOOD EC;8P
Adder
29.138
274736ELWOOD EC;9P
Adder
29.138
276893AG1-478 C
Solar/Wind Harmer
0.74
959331AF2-224 GEN
Solar/Wind Harmer
17.715
965021AG1-366 GEN
Solar/Wind Harmer
4.12
943121AE2-341 GEN
Solar/Wind Harmer
26.432
943591AF1-030 GEN
Solar/Wind Harmer
17.621
270535AF1-215 GEN1
Solar/Wind Harmer
7.981
276694AA1-018 GEN2
Solar/Wind Harmer
10.942
274682WAUKEGAN ;7U
Adder
31.14
964401AG1-302 GEN
Solar/Wind Harmer
15.597
274872LEEDK;1U
Solar/Wind Harmer
0.438
276805AD2-038 GEN
Solar/Wind Harmer
8.776
276799AD1-013 GEN
Solar/Wind Harmer
3.749
946671AF1-331 GEN
Solar/Wind Harmer
0.71
274855GSG-6 ;RU
Solar/Wind Harmer
6.258
274850MENDOTA H;RU
Solar/Wind Harmer
4.351
276602WESTBROOK C
Solar/Wind Harmer
3.602
276863AD2-134 GEN
Solar/Wind Harmer
3.026
959141AF2-205 GEN
Solar/Wind Harmer
10.19
972236AH1-702 GEN2
Adder
3.664
274760LEE CO EC;1U
Adder
15.294
274767LEE CO EC;8U
Adder
15.114
24728705AND G3
Adder
8.991
24728505AND G1
Adder
4.299
959091AF2-200 GEN
Solar/Wind Harmer
32.581
971599AH1-298 GEN
50/50
18.905
270144AC1-141 ST1_
50/50
4.065
24643105BUCHANAN
50/50
0.024
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
30.529
971771AH1-392 GEN
Solar/Wind Harmer
17.216
270071AF1-092 GEN
Solar/Wind Harmer
28.557
960681AF2-359 GEN
Solar/Wind Harmer
7.16
971769AH1-391 GEN
Solar/Wind Harmer
18.948
944161AF1-084 GEN
Solar/Wind Harmer
4.125
274775LINCOLN ;6U
Adder
11.428
274776LINCOLN ;7U
Adder
11.428
274777LINCOLN ;8U
Adder
11.428
274814UNIV PK N;0U
Adder
9.121
274807UNIV PK N;3U
Adder
9.101
274805UNIV PK N;1U
Adder
9.061
274811UNIV PK N;7U
Adder
9.041
972037AH1-567 GEN1
Adder
0.329
274827FISK ;RP
Adder
13.93
960591AF2-350 GEN
Solar/Wind Harmer
17.934
972227AH1-698 GEN1
Adder
4.674
24729505KEY G4
Adder
11.594
274687WILL CNTY;4U
Adder
49.737
274687WILL CNTY;4U
Adder
49.737
274675JOLIET 29;7U
Adder
54.541
274675JOLIET 29;7U
Adder
52.593
274731ELWOOD EC;2P
Adder
29.137
274733ELWOOD EC;3P
Adder
29.137
274735ELWOOD EC;4P
Adder
29.137
274728ELWOOD EC;5P
Adder
29.138
970833AG2-524 GEN
Solar/Wind Harmer
15.455
970833AG2-524 GEN
Solar/Wind Harmer
7.188
274746AC1-111 G10
Adder
9.829
274744AC1-111 GEN8
Adder
9.829
270536AF1-215 GEN2
Solar/Wind Harmer
7.981
971549AH1-272 GEN
Solar/Wind Harmer
31.811
971177AH1-047 GEN
Solar/Wind Harmer
9.977
276868AE1-113 GEN
Solar/Wind Harmer
17.225
276882AE2-255 GEN
Solar/Wind Harmer
5.742
958391AF2-133 GEN
Solar/Wind Harmer
15.422
971411AH1-196 GEN
Solar/Wind Harmer
25.424
971675AH1-338 GEN
Solar/Wind Harmer
30.507
274863CRW1-WTG
Solar/Wind Harmer
9.397
274864CRW2-WTG
Solar/Wind Harmer
9.397
274823ROCKFORD ;21
Adder
32.659
270284AF1-227 GEN1
Solar/Wind Helper
2.861
270286AF1-227 GEN2
Solar/Wind Helper
1.049
270287AF1-227 GEN3
Solar/Wind Helper
1.049
270054AF2-122 C O1
Solar/Wind Helper
1.201
971171AH1-044 GEN
Solar/Wind Harmer
32.581
24344105CKG2
50/50
15.989
270143AC1-141 CT2_
50/50
4.589
24639705ELKHART HY
50/50
0.308
970521AG2-332 GEN
50/50
21.897
24307105BERRINSP G
50/50
0.041
970245AG2-165 GEN
Solar/Wind Harmer
35.447
270505AE1-170 C O1
Solar/Wind Harmer
28.453
945111AF1-176 GEN
Solar/Wind Harmer
33.668
270449AD2-020 GEN
Solar/Wind Harmer
5.261
943021AE2-325 GEN
Solar/Wind Harmer
6.837
270063AE2-323 C
Solar/Wind Harmer
4.119
972207SS24-0001
Solar/Wind Harmer
40.631
274773LINCOLN ;4U
Adder
11.428
274774LINCOLN ;5U
Adder
11.428
274723RIVER EC ;12
Adder
32.605
274751CRETE EC ;1U
Adder
8.877
274754CRETE EC ;4U
Adder
8.877
276164X3-005 C
Solar/Wind Harmer
1.273
274812UNIV PK N;8U
Adder
9.041
970373AG2-245 GEN
Solar/Wind Harmer
37.783
276776AD2-060 GEN
Solar/Wind Harmer
0.758
274801UNIV PARK;4U
Adder
10.455
941551AE2-152 GEN
Solar/Wind Harmer
8.088
274676JOLIET 29;8U
Adder
54.54
274674JOLIET 9 ;6U
Adder
27.32
274732ELWOOD EC;7P
Adder
29.138
965011AG1-365 GEN
Solar/Wind Harmer
17.715
274871GR RIDGE ;2U
Solar/Wind Harmer
13.606
274745AC1-111 GEN9
Adder
9.829
270055AF2-134 C O1
Solar/Wind Harmer
5.32
276691AA1-018 GEN1
Solar/Wind Harmer
0.807
274682WAUKEGAN ;7U
Adder
31.14
274828WAUKEGAN ;BP
Adder
19.112
958381AF2-132 GEN
Solar/Wind Harmer
15.597
960751AF2-366 GEN
Solar/Wind Harmer
4.928
962781AG1-127 GEN
Solar/Wind Harmer
16.333
964861AG1-349 GEN
Solar/Wind Harmer
13.483
971917AH1-482 GEN
Solar/Wind Harmer
15.559
274872LEEDK;1U
Solar/Wind Harmer
14.071
939401AE1-172 GEN
Solar/Wind Harmer
23.859
276901AD2-066 C O1
Solar/Wind Harmer
6
971997AH1-543 GEN
Solar/Wind Harmer
26.748
276861AD2-134 GEN
Solar/Wind Harmer
3.026
274822ROCKFORD ;11
Adder
32.898
972235AH1-702 GEN1
Adder
4.214
274761LEE CO EC;2U
Adder
15.294
274766LEE CO EC;7U
Adder
15.114
24728605AND G2
Adder
4.299
970091AG2-072 GEN
Adder
4.41
270349AD2-093_GEN
Solar/Wind Helper
1.84
957471AF2-041 GEN
Solar/Wind Harmer
48.872
959081AF2-199 GEN
Solar/Wind Harmer
16.291
971067AG2-660 GEN
Solar/Wind Harmer
3.789
944201AF1-088_MTX
Adder
125.321
957141AF2-008_MTX
Adder
62.661
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
197.094
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.275
MECLTFEXP_MEC->PJM
CLTF
22.999
SIGELTFEXP_SIGE->PJM
CLTF
0.439
LAGNLTFEXP_LAGN->PJM
CLTF
12.243
TVALTFEXP_TVA->PJM
CLTF
4.635
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.242
NYPJM->LTFIMP_NY
CLTF
3.027
LGEELTFEXP_LGEE->PJM
CLTF
4.067
WECLTFEXP_WEC->PJM
CLTF
6.372
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.882
AG2-052LTFEXP_AG2-052->PJM
LTF
0.399
AH1-155LTFEXP_AH1-155->PJM
LTF
0.599

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:135.75 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5622.57
MW Contribution:55.45
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.055
270100X2-052 CT1
50/50
2.815
270101X2-052 CT2
50/50
2.815
247620Y3-023
50/50
0.917
970321AG2-212 GEN
Solar/Wind Harmer
35.465
270216AD2-079_GEN
Solar/Wind Harmer
1.158
270526AF1-158 GEN
Solar/Wind Harmer
8.63
965681AG1-436 GEN
Solar/Wind Harmer
23.702
965791AG1-447 GEN
Solar/Wind Harmer
12.126
24441505OLIV SLR
Solar/Wind Harmer
0.254
957891AF2-083 GEN
Solar/Wind Harmer
6.389
960981AF2-389 GEN
Solar/Wind Harmer
2.863
961051AF2-396 GEN
Solar/Wind Harmer
29.87
961051AF2-396 GEN
Solar/Wind Harmer
13.893
274770LINCOLN ;1U
Adder
11.434
274771LINCOLN ;2U
Adder
11.434
274808UNIV PK N;4U
Adder
9.007
274803UNIV PARK;6U
Adder
10.474
972259AH1-714 GEN
Adder
34.259
274888KELLY CRK;1U
Solar/Wind Harmer
10.594
274887GEN-1.85
Solar/Wind Harmer
9.565
276843GEN-1.7
Solar/Wind Harmer
1.029
958011AF2-095 GEN
Solar/Wind Harmer
25.84
274674JOLIET 9 ;6U
Adder
27.335
970611AG2-400 GEN
Solar/Wind Harmer
17.725
274847GR RIDGE ;BU
Solar/Wind Harmer
8.955
971573AH1-285 GEN
Solar/Wind Harmer
15.068
274695ROCKY RD ;2P
Adder
19.338
274693ROCKY RD ;1P
Adder
19.148
274697ROCKY RD ;3P
Adder
5.253
274696ROCKY RD ;4P
Adder
19.794
958481AF2-142 GEN
Solar/Wind Harmer
26.023
274861TOP CROP ;1U
Solar/Wind Harmer
10.506
274862TOP CROP ;2U
Solar/Wind Harmer
8.773
274683WAUKEGAN ;8U
Adder
36.482
274683WAUKEGAN ;8U
Adder
30.752
962691AG1-118 GEN
Solar/Wind Harmer
51.697
970921AG2-575 GEN
Solar/Wind Harmer
17.185
970921AG2-575 GEN
Solar/Wind Harmer
3.996
958491AF2-143 GEN
Solar/Wind Harmer
25.677
942991AE2-321 GEN
Solar/Wind Harmer
17.044
274879MINONK ;1U
Solar/Wind Harmer
11.491
24344005CKG1
50/50
12.545
270142AC1-141 CT1_
50/50
4.591
24641605TWIN BRNCH
50/50
0.033
24642205MAYFLWER
50/50
1.278
944961AF1-161 GEN
50/50
5.46
962601AG1-109 GEN
50/50
5.46
970349AG2-230 GEN
Solar/Wind Harmer
30.544
970513AG2-328 GEN
Solar/Wind Harmer
35.465
970517AG2-330 GEN
Solar/Wind Harmer
32.166
270043AE2-236 GEN
Solar/Wind Harmer
10.829
247643Z2-116 C
Solar/Wind Harmer
0.133
945111AF1-176 GEN
Solar/Wind Harmer
10.676
970031AG2-029 GEN
Solar/Wind Harmer
55.447
24441205WTRV SLR C
Solar/Wind Harmer
0.249
274772LINCOLN ;3U
Adder
11.434
944531AF1-118 GEN
Solar/Wind Harmer
64.187
247604X1-042
Adder
0.761
274724RIVER EC ;11
Adder
32.247
972231SS25-0005
Solar/Wind Harmer
17.245
972181SS23-001
Solar/Wind Harmer
10.778
274752CRETE EC ;2U
Adder
8.882
274753CRETE EC ;3U
Adder
8.882
970707AG2-453 GEN
Solar/Wind Harmer
50.518
274802UNIV PARK;5U
Adder
10.474
274826FISK ;BP
Adder
19.666
276772AC2-154 GEN
Solar/Wind Harmer
5.004
276806AD2-047 C O1
Solar/Wind Harmer
19.196
971599AH1-298 GEN
50/50
18.913
970941AG2-585 GEN
Solar/Wind Harmer
22.43
274800UNIV PARK;3U
Adder
10.46
972038AH1-567 GEN2
Adder
0.655
972228AH1-698 GEN2
Adder
6.643
276897AD1-100 C
Solar/Wind Harmer
51.784
939351AE1-166 GEN
Solar/Wind Harmer
10.581
274676JOLIET 29;8U
Adder
52.622
274730ELWOOD EC;6P
Adder
29.154
274734ELWOOD EC;8P
Adder
29.154
274736ELWOOD EC;9P
Adder
29.154
274729ELWOOD EC;1P
Adder
29.154
276893AG1-478 C
Solar/Wind Harmer
0.74
959331AF2-224 GEN
Solar/Wind Harmer
17.725
965021AG1-366 GEN
Solar/Wind Harmer
4.122
943121AE2-341 GEN
Solar/Wind Harmer
26.447
943591AF1-030 GEN
Solar/Wind Harmer
17.631
270535AF1-215 GEN1
Solar/Wind Harmer
7.986
276694AA1-018 GEN2
Solar/Wind Harmer
10.948
274682WAUKEGAN ;7U
Adder
31.159
964401AG1-302 GEN
Solar/Wind Harmer
15.606
274872LEEDK;1U
Solar/Wind Harmer
0.439
276805AD2-038 GEN
Solar/Wind Harmer
8.782
276799AD1-013 GEN
Solar/Wind Harmer
3.751
946671AF1-331 GEN
Solar/Wind Harmer
0.71
274855GSG-6 ;RU
Solar/Wind Harmer
6.262
274850MENDOTA H;RU
Solar/Wind Harmer
4.354
276602WESTBROOK C
Solar/Wind Harmer
3.604
276863AD2-134 GEN
Solar/Wind Harmer
3.028
959141AF2-205 GEN
Solar/Wind Harmer
10.197
972236AH1-702 GEN2
Adder
3.666
274760LEE CO EC;1U
Adder
15.304
274767LEE CO EC;8U
Adder
15.124
24728705AND G3
Adder
8.999
24728505AND G1
Adder
4.303
942871AE2-306 GEN
Solar/Wind Helper
0.456
959091AF2-200 GEN
Solar/Wind Harmer
32.601
971333AH1-146 GEN
Solar/Wind Harmer
33.891
971335AH1-147 GEN
Solar/Wind Harmer
33.891
274764LEE CO EC;5U
Adder
15.34
274765LEE CO EC;6U
Adder
15.34
274762LEE CO EC;3U
Adder
15.304
274763LEE CO EC;4U
Adder
15.16
972267AH1-718 GEN
Adder
6.773
247621Y3-024
Adder
0.286
270471AD2-092_GEN
Solar/Wind Helper
1.839
270224U2-072_GEN2
Solar/Wind Helper
0.897
270227U2-072_GEN3
Solar/Wind Helper
0.897
270228U2-072_GEN4
Solar/Wind Helper
0.897
270231U2-072_GEN5
Solar/Wind Helper
0.897
971341AH1-150 GEN
Solar/Wind Harmer
32.601
971343AH1-151 GEN
Solar/Wind Harmer
32.601
24344105CKG2
50/50
15.997
270143AC1-141 CT2_
50/50
4.591
24639705ELKHART HY
50/50
0.308
970521AG2-332 GEN
50/50
21.908
24307105BERRINSP G
50/50
0.041
970245AG2-165 GEN
Solar/Wind Harmer
35.465
270505AE1-170 C O1
Solar/Wind Harmer
28.468
945111AF1-176 GEN
Solar/Wind Harmer
33.686
270449AD2-020 GEN
Solar/Wind Harmer
5.264
943021AE2-325 GEN
Solar/Wind Harmer
6.84
270063AE2-323 C
Solar/Wind Harmer
4.121
972207SS24-0001
Solar/Wind Harmer
40.653
274773LINCOLN ;4U
Adder
11.434
274774LINCOLN ;5U
Adder
11.434
274723RIVER EC ;12
Adder
32.623
274751CRETE EC ;1U
Adder
8.882
274754CRETE EC ;4U
Adder
8.882
276164X3-005 C
Solar/Wind Harmer
1.273
274812UNIV PK N;8U
Adder
9.046
970373AG2-245 GEN
Solar/Wind Harmer
37.804
276776AD2-060 GEN
Solar/Wind Harmer
0.759
274801UNIV PARK;4U
Adder
10.46
941551AE2-152 GEN
Solar/Wind Harmer
8.093
274676JOLIET 29;8U
Adder
54.571
274674JOLIET 9 ;6U
Adder
27.335
274732ELWOOD EC;7P
Adder
29.154
965011AG1-365 GEN
Solar/Wind Harmer
17.725
274871GR RIDGE ;2U
Solar/Wind Harmer
13.613
274745AC1-111 GEN9
Adder
9.834
270055AF2-134 C O1
Solar/Wind Harmer
5.323
276691AA1-018 GEN1
Solar/Wind Harmer
0.808
274682WAUKEGAN ;7U
Adder
31.159
274828WAUKEGAN ;BP
Adder
19.123
958381AF2-132 GEN
Solar/Wind Harmer
15.606
960751AF2-366 GEN
Solar/Wind Harmer
4.93
962781AG1-127 GEN
Solar/Wind Harmer
16.343
964861AG1-349 GEN
Solar/Wind Harmer
13.491
971917AH1-482 GEN
Solar/Wind Harmer
15.568
274872LEEDK;1U
Solar/Wind Harmer
14.079
939401AE1-172 GEN
Solar/Wind Harmer
23.873
276901AD2-066 C O1
Solar/Wind Harmer
6.004
971997AH1-543 GEN
Solar/Wind Harmer
26.764
276861AD2-134 GEN
Solar/Wind Harmer
3.028
274822ROCKFORD ;11
Adder
32.918
972235AH1-702 GEN1
Adder
4.216
274761LEE CO EC;2U
Adder
15.304
274766LEE CO EC;7U
Adder
15.124
24728605AND G2
Adder
4.303
970091AG2-072 GEN
Adder
4.415
270349AD2-093_GEN
Solar/Wind Helper
1.839
270223U2-072_GEN1
Solar/Wind Helper
0.897
270578AF1-285 GEN2
Solar/Wind Helper
0.608
270391AF1-285 GEN3
Solar/Wind Helper
0.608
957471AF2-041 GEN
Solar/Wind Harmer
48.901
959081AF2-199 GEN
Solar/Wind Harmer
16.3
971067AG2-660 GEN
Solar/Wind Harmer
3.791
270144AC1-141 ST1_
50/50
4.067
24643105BUCHANAN
50/50
0.024
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
30.544
971771AH1-392 GEN
Solar/Wind Harmer
17.225
270071AF1-092 GEN
Solar/Wind Harmer
28.572
960681AF2-359 GEN
Solar/Wind Harmer
7.163
971769AH1-391 GEN
Solar/Wind Harmer
18.958
944161AF1-084 GEN
Solar/Wind Harmer
4.127
274775LINCOLN ;6U
Adder
11.434
274776LINCOLN ;7U
Adder
11.434
274777LINCOLN ;8U
Adder
11.434
274814UNIV PK N;0U
Adder
9.126
274807UNIV PK N;3U
Adder
9.106
274805UNIV PK N;1U
Adder
9.066
274811UNIV PK N;7U
Adder
9.046
972037AH1-567 GEN1
Adder
0.329
274827FISK ;RP
Adder
13.937
960591AF2-350 GEN
Solar/Wind Harmer
17.944
972227AH1-698 GEN1
Adder
4.677
24729505KEY G4
Adder
11.601
274687WILL CNTY;4U
Adder
49.765
274687WILL CNTY;4U
Adder
49.765
274675JOLIET 29;7U
Adder
54.572
274675JOLIET 29;7U
Adder
52.623
274728ELWOOD EC;5P
Adder
29.154
274731ELWOOD EC;2P
Adder
29.154
274733ELWOOD EC;3P
Adder
29.154
274735ELWOOD EC;4P
Adder
29.154
970833AG2-524 GEN
Solar/Wind Harmer
15.464
970833AG2-524 GEN
Solar/Wind Harmer
7.192
274746AC1-111 G10
Adder
9.834
274744AC1-111 GEN8
Adder
9.834
270536AF1-215 GEN2
Solar/Wind Harmer
7.986
971549AH1-272 GEN
Solar/Wind Harmer
31.829
971177AH1-047 GEN
Solar/Wind Harmer
9.983
276868AE1-113 GEN
Solar/Wind Harmer
17.235
276882AE2-255 GEN
Solar/Wind Harmer
5.745
958391AF2-133 GEN
Solar/Wind Harmer
15.431
971411AH1-196 GEN
Solar/Wind Harmer
25.439
971675AH1-338 GEN
Solar/Wind Harmer
30.526
274863CRW1-WTG
Solar/Wind Harmer
9.402
274864CRW2-WTG
Solar/Wind Harmer
9.402
274823ROCKFORD ;21
Adder
32.679
270284AF1-227 GEN1
Solar/Wind Helper
2.858
270286AF1-227 GEN2
Solar/Wind Helper
1.048
270287AF1-227 GEN3
Solar/Wind Helper
1.048
270054AF2-122 C O1
Solar/Wind Helper
1.2
971171AH1-044 GEN
Solar/Wind Harmer
32.601
944201AF1-088_MTX
Adder
125.438
957141AF2-008_MTX
Adder
62.719
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.34
CBM West 1LTFEXP_CBM-W1->PJM
CBM
197.241
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.313
MECLTFEXP_MEC->PJM
CLTF
23.016
SIGELTFEXP_SIGE->PJM
CLTF
0.44
LAGNLTFEXP_LAGN->PJM
CLTF
12.264
TVALTFEXP_TVA->PJM
CLTF
4.645
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.378
NYPJM->LTFIMP_NY
CLTF
3.02
LGEELTFEXP_LGEE->PJM
CLTF
4.074
WECLTFEXP_WEC->PJM
CLTF
6.376
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.875
AG2-052LTFEXP_AG2-052->PJM
LTF
0.399
AH1-155LTFEXP_AH1-155->PJM
LTF
0.599

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.5 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:5281.19
MW Contribution:8.07
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
18.435
270144AC1-141 ST1_
50/50
3.968
24643105BUCHANAN
50/50
0.024
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
20.909
971771AH1-392 GEN
Solar/Wind Harmer
13.038
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971769AH1-391 GEN
Solar/Wind Harmer
14.442
270071AF1-092 GEN
Solar/Wind Harmer
24.752
971619AH1-309 GEN
Solar/Wind Harmer
5.808
274775LINCOLN ;6U
Adder
15.292
274776LINCOLN ;7U
Adder
15.292
274777LINCOLN ;8U
Adder
15.292
274814UNIV PK N;0U
Adder
8.954
274807UNIV PK N;3U
Adder
8.935
274805UNIV PK N;1U
Adder
8.896
274811UNIV PK N;7U
Adder
8.876
972037AH1-567 GEN1
Adder
0.323
274827FISK ;RP
Adder
13.681
960591AF2-350 GEN
Solar/Wind Harmer
12.291
972227AH1-698 GEN1
Adder
4.592
274687WILL CNTY;4U
Adder
48.86
274687WILL CNTY;4U
Adder
48.86
274675JOLIET 29;7U
Adder
53.583
274675JOLIET 29;7U
Adder
51.669
274728ELWOOD EC;5P
Adder
28.626
274731ELWOOD EC;2P
Adder
28.625
274733ELWOOD EC;3P
Adder
28.625
274735ELWOOD EC;4P
Adder
28.625
24729505KEY G4
Adder
11.296
970833AG2-524 GEN
Solar/Wind Harmer
13.35
970833AG2-524 GEN
Solar/Wind Harmer
8.9
274746AC1-111 G10
Adder
9.659
274744AC1-111 GEN8
Adder
9.659
270536AF1-215 GEN2
Solar/Wind Harmer
0.015
971177AH1-047 GEN
Solar/Wind Harmer
7.198
276868AE1-113 GEN
Solar/Wind Harmer
2.341
276882AE2-255 GEN
Solar/Wind Harmer
1.364
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
4.532
971411AH1-196 GEN
Solar/Wind Harmer
17.431
971549AH1-272 GEN
Solar/Wind Harmer
23.961
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
23.073
274823ROCKFORD ;21
Adder
32.096
971611AH1-305 GEN
Solar/Wind Harmer
6.79
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
1.931
970169AG2-114 GEN
Solar/Wind Harmer
11.331
971681AH1-341 GEN
Solar/Wind Harmer
18.233
961011AF2-392 GEN
Solar/Wind Harmer
6.56
957751AF2-069 GEN
Solar/Wind Harmer
0.366
965101AG1-375 GEN
Solar/Wind Harmer
11.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
11.407
941731AE2-173 GEN
Solar/Wind Harmer
9.053
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.04
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963791AG1-232 GEN
Solar/Wind Harmer
13.932
963841AG1-237 GEN
Solar/Wind Harmer
4.358
965041AG1-368 GEN
Solar/Wind Harmer
10.015
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.361
970289AG2-191 GEN
Solar/Wind Harmer
1.856
971609AH1-304 GEN
Solar/Wind Harmer
1.589
270594AE1-207 GEN
Solar/Wind Harmer
10.691
965051AG1-369 GEN
Solar/Wind Harmer
4.577
270024AE2-089 GEN
Solar/Wind Harmer
0.01
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.587
944221AF1-090 GEN
Solar/Wind Harmer
5.246
270240V3-007_GEN2
Solar/Wind Harmer
0.002
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.91
270543AE2-219 C
Solar/Wind Harmer
0.004
971029AG2-637 GEN
Solar/Wind Harmer
9.925
971673AH1-337 GEN
Solar/Wind Harmer
4.175
24344005CKG1
50/50
12.252
270142AC1-141 CT1_
50/50
4.479
24641605TWIN BRNCH
50/50
0.032
24642205MAYFLWER
50/50
1.247
944961AF1-161 GEN
50/50
5.318
962601AG1-109 GEN
50/50
5.318
970349AG2-230 GEN
Solar/Wind Harmer
20.909
970513AG2-328 GEN
Solar/Wind Harmer
5.915
970517AG2-330 GEN
Solar/Wind Harmer
35.487
270043AE2-236 GEN
Solar/Wind Harmer
8.538
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
10.397
274772LINCOLN ;3U
Adder
15.292
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
31.641
944531AF1-118 GEN
Solar/Wind Harmer
55.84
274752CRETE EC ;2U
Adder
14.685
274753CRETE EC ;3U
Adder
14.685
970031AG2-029 GEN
Solar/Wind Harmer
8.073
247604X1-042
Adder
0.74
970707AG2-453 GEN
Solar/Wind Harmer
40.394
274802UNIV PARK;5U
Adder
10.281
274826FISK ;BP
Adder
19.304
276806AD2-047 C O1
Solar/Wind Harmer
6.965
970941AG2-585 GEN
Solar/Wind Harmer
15.363
274800UNIV PARK;3U
Adder
10.269
972038AH1-567 GEN2
Adder
0.643
972228AH1-698 GEN2
Adder
6.522
276897AD1-100 C
Solar/Wind Harmer
0.016
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
24344105CKG2
50/50
15.732
270143AC1-141 CT2_
50/50
4.479
24639705ELKHART HY
50/50
0.3
970521AG2-332 GEN
50/50
21.293
24307105BERRINSP G
50/50
0.04
970245AG2-165 GEN
Solar/Wind Harmer
5.915
270505AE1-170 C O1
Solar/Wind Harmer
13.553
945111AF1-176 GEN
Solar/Wind Harmer
22.888
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
6.663
274773LINCOLN ;4U
Adder
15.292
274774LINCOLN ;5U
Adder
15.292
270063AE2-323 C
Solar/Wind Harmer
0.01
274723RIVER EC ;12
Adder
32.009
274751CRETE EC ;1U
Adder
14.685
274754CRETE EC ;4U
Adder
14.685
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
8.876
970373AG2-245 GEN
Solar/Wind Harmer
25.833
276776AD2-060 GEN
Solar/Wind Harmer
1.283
274801UNIV PARK;4U
Adder
10.269
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
53.582
274674JOLIET 9 ;6U
Adder
26.84
274732ELWOOD EC;7P
Adder
28.626
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
9.659
270055AF2-134 C O1
Solar/Wind Harmer
0.009
276691AA1-018 GEN1
Solar/Wind Harmer
1.44
270102X2-052 ST
50/50
2.992
270100X2-052 CT1
50/50
2.757
270101X2-052 CT2
50/50
2.757
247620Y3-023
50/50
0.89
970321AG2-212 GEN
Solar/Wind Harmer
5.915
270216AD2-079_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
16.197
965791AG1-447 GEN
Solar/Wind Harmer
11.878
270526AF1-158 GEN
Solar/Wind Harmer
0.016
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
25.575
961051AF2-396 GEN
Solar/Wind Harmer
17.05
274770LINCOLN ;1U
Adder
15.292
274771LINCOLN ;2U
Adder
15.292
274808UNIV PK N;4U
Adder
8.838
972259AH1-714 GEN
Adder
33.646
274803UNIV PARK;6U
Adder
10.281
274888KELLY CRK;1U
Solar/Wind Harmer
0.722
274887GEN-1.85
Solar/Wind Harmer
0.324
276843GEN-1.7
Solar/Wind Harmer
0.398
958011AF2-095 GEN
Solar/Wind Harmer
17.698
274674JOLIET 9 ;6U
Adder
26.84
274847GR RIDGE ;BU
Solar/Wind Harmer
0.004
971573AH1-285 GEN
Solar/Wind Harmer
2.237
274695ROCKY RD ;2P
Adder
18.993
274693ROCKY RD ;1P
Adder
18.806
274697ROCKY RD ;3P
Adder
5.159
274696ROCKY RD ;4P
Adder
19.441
958481AF2-142 GEN
Solar/Wind Harmer
17.825
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.607
274683WAUKEGAN ;8U
Adder
35.828
274683WAUKEGAN ;8U
Adder
30.201
962691AG1-118 GEN
Solar/Wind Harmer
35.425
970921AG2-575 GEN
Solar/Wind Harmer
11.776
970921AG2-575 GEN
Solar/Wind Harmer
3.925
958491AF2-143 GEN
Solar/Wind Harmer
17.589
942991AE2-321 GEN
Solar/Wind Harmer
13.041
274879MINONK ;1U
Solar/Wind Harmer
0.492
970611AG2-400 GEN
Solar/Wind Harmer
11.612
970627AG2-408 GEN
Solar/Wind Harmer
3.484
971333AH1-146 GEN
Solar/Wind Harmer
23.223
971335AH1-147 GEN
Solar/Wind Harmer
23.223
971341AH1-150 GEN
Solar/Wind Harmer
23.073
971343AH1-151 GEN
Solar/Wind Harmer
23.073
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.269
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.415
944541AF1-119 GEN
Solar/Wind Harmer
0.756
960971AF2-388 GEN
Solar/Wind Harmer
6.621
274764LEE CO EC;5U
Adder
15.066
274765LEE CO EC;6U
Adder
15.066
274762LEE CO EC;3U
Adder
15.031
274763LEE CO EC;4U
Adder
14.889
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
6.653
276741O09 GEN1
Solar/Wind Harmer
0.396
276708O09 GEN2
Solar/Wind Harmer
0.396
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.436
276646AC1-214 GEN2
Solar/Wind Harmer
0.436
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.549
942221AE2-234 GEN
Solar/Wind Harmer
0.052
966841AG1-555 GEN
Solar/Wind Harmer
1.176
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
5.684
270599AE1-208 GEN
Solar/Wind Harmer
8.918
270031AE2-169
Solar/Wind Harmer
5.351
971613AH1-306 GEN
Solar/Wind Harmer
4.582
276916AD2-100_GEN
Solar/Wind Harmer
19.464
276911AD2-131_GEN
Solar/Wind Harmer
1.282
960441AF2-335 GEN
Solar/Wind Harmer
8.968
970825AG2-519 GEN
Solar/Wind Harmer
9.877
945391AF1-204 GEN
Solar/Wind Harmer
9.229
964611AG1-324 GEN
Solar/Wind Harmer
0.623
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.274
970623AG2-406 GEN
Solar/Wind Harmer
1.433
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.417
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.798
246938BC-WTG3
Solar/Wind Harmer
0.26
246937BC-WTG2
Solar/Wind Harmer
0.291
970883AG2-550 GEN
Solar/Wind Harmer
7.146
970885AG2-551 GEN
Solar/Wind Harmer
2.382
270471AD2-092_GEN
Solar/Wind Helper
1.564
274676JOLIET 29;8U
Adder
51.668
274730ELWOOD EC;6P
Adder
28.626
274734ELWOOD EC;8P
Adder
28.626
274736ELWOOD EC;9P
Adder
28.626
274729ELWOOD EC;1P
Adder
28.625
276893AG1-478 C
Solar/Wind Harmer
0.481
943121AE2-341 GEN
Solar/Wind Harmer
20.258
943591AF1-030 GEN
Solar/Wind Harmer
13.472
270535AF1-215 GEN1
Solar/Wind Harmer
0.015
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
30.6
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.431
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.24
274855GSG-6 ;RU
Solar/Wind Harmer
0.426
274850MENDOTA H;RU
Solar/Wind Harmer
0.137
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.208
959331AF2-224 GEN
Solar/Wind Harmer
8.128
965021AG1-366 GEN
Solar/Wind Harmer
3.871
959091AF2-200 GEN
Solar/Wind Harmer
23.073
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.601
970571AG2-364 GEN
Solar/Wind Harmer
22.715
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
15.031
274767LEE CO EC;8U
Adder
14.854
276157O29GEN1
Solar/Wind Harmer
1.797
274878BISHOP HL;2U
Solar/Wind Harmer
0.37
942111AE2-223 GEN
Solar/Wind Harmer
3.531
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
10.846
965931AG1-462 GEN
Solar/Wind Harmer
27.328
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
31.938
959611AF2-252 GEN
Solar/Wind Harmer
3.549
247642Z2-115 C
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.599
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
970289AG2-191 GEN
Solar/Wind Harmer
1.074
970291AG2-192 GEN
Solar/Wind Harmer
0.977
276621W2-048 GEN
Solar/Wind Harmer
0.492
276838X2-022 GEN2
Solar/Wind Harmer
0.549
274682WAUKEGAN ;7U
Adder
30.6
274828WAUKEGAN ;BP
Adder
18.78
962781AG1-127 GEN
Solar/Wind Harmer
11.207
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.007
939401AE1-172 GEN
Solar/Wind Harmer
8.779
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
15.25
276901AD2-066 C O1
Solar/Wind Harmer
0.012
971997AH1-543 GEN
Solar/Wind Harmer
6.112
276861AD2-134 GEN
Solar/Wind Harmer
0.208
965011AG1-365 GEN
Solar/Wind Harmer
11.612
957471AF2-041 GEN
Solar/Wind Harmer
34.609
959081AF2-199 GEN
Solar/Wind Harmer
11.536
971067AG2-660 GEN
Solar/Wind Harmer
3.845
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
32.33
972235AH1-702 GEN1
Adder
4.141
970819AG2-516 GEN
Solar/Wind Harmer
13.704
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
14.256
971475AH1-234 GEN
Solar/Wind Harmer
5.525
970569AG2-363 GEN
Solar/Wind Harmer
34.072
965651AG1-433 GEN
Solar/Wind Harmer
3.31
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
15.031
274766LEE CO EC;7U
Adder
14.854
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.37
958861AF2-177 GEN
Solar/Wind Harmer
4.768
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
15.209
24791305MDL-5G
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
945371AF1-202 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
944231AF1-091 GEN
Solar/Wind Harmer
2.757
972175AH1-670 GEN
Solar/Wind Harmer
8.498
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.857
970291AG2-192 GEN
Solar/Wind Harmer
1.27
276615X2-022 GEN
Solar/Wind Harmer
0.102
963741AG1-226 GEN
Solar/Wind Harmer
23.062
270032AE2-172
Solar/Wind Harmer
6.364
965911AG1-460 GEN
Solar/Wind Harmer
1.873
276903AD2-071 C
Solar/Wind Harmer
10.292
270005AE1-210 C O1
Solar/Wind Harmer
1.994
965031AG1-367 GEN
Solar/Wind Harmer
9.202
247521TR3_G114
Solar/Wind Harmer
0.334
270246TR4_N_V150
Solar/Wind Harmer
0.059
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
3.164
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.065
24728605AND G2
Adder
4.198
247536S-71 GEN
Solar/Wind Harmer
0.307
965421AG1-410 GEN
Solar/Wind Harmer
22.83
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
970333AG2-219 GEN
Solar/Wind Harmer
5.143
246936BC-WTG1
Solar/Wind Harmer
0.291
270489AE1-102 GEN1
Solar/Wind Harmer
0.934
970773AG2-487 GEN
Solar/Wind Harmer
1.226
270349AD2-093_GEN
Solar/Wind Helper
1.564
942481AE2-261 GEN
Solar/Wind Harmer
27.997
958821AF2-173 GEN
Solar/Wind Harmer
12.883
270004AE1-209 GEN
Solar/Wind Harmer
1.994
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.059
971617AH1-308 GEN
Solar/Wind Harmer
7.545
946031AF1-268 GEN
Solar/Wind Harmer
8.268
970193AG2-126 GEN
Solar/Wind Harmer
13.029
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
12.308
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
8.781
24728505AND G1
Adder
4.198
970243AG2-164 GEN
Solar/Wind Harmer
4.208
970519AG2-331 GEN
Solar/Wind Harmer
18.702
970699AG2-449 GEN
Solar/Wind Harmer
1.798
270491AE1-102 GEN2
Solar/Wind Harmer
0.934
270356AE2-297 GEN
Solar/Wind Harmer
0.009
944201AF1-088_MTX
Adder
123.107
957141AF2-008_MTX
Adder
33.614
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3
CBM West 1LTFEXP_CBM-W1->PJM
CBM
190.688
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.117
MECLTFEXP_MEC->PJM
CLTF
22.614
SIGELTFEXP_SIGE->PJM
CLTF
0.431
LAGNLTFEXP_LAGN->PJM
CLTF
12.118
TVALTFEXP_TVA->PJM
CLTF
4.605
CBM West 2LTFEXP_CBM-W2->PJM
CBM
109.586
NYPJM->LTFIMP_NY
CLTF
2.955
LGEELTFEXP_LGEE->PJM
CLTF
4
WECLTFEXP_WEC->PJM
CLTF
6.262
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.805
AG2-052LTFEXP_AG2-052->PJM
LTF
0.392
AH1-155LTFEXP_AH1-155->PJM
LTF
0.587

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.73 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2666.26
MW Contribution:35.76
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.546
24729405KEY G3
50/50
0.364
24729305KEY G2
50/50
0.357
24729205KEY G1
50/50
0.356
247620Y3-023
50/50
0.458
970611AG2-400 GEN
Solar/Wind Harmer
19.549
942221AE2-234 GEN
Solar/Wind Harmer
0.705
944541AF1-119 GEN
Solar/Wind Harmer
3.722
960971AF2-388 GEN
Solar/Wind Harmer
9.712
270216AD2-079_GEN
Solar/Wind Harmer
0.529
960981AF2-389 GEN
Solar/Wind Harmer
1.248
957891AF2-083 GEN
Solar/Wind Harmer
2.781
961051AF2-396 GEN
Solar/Wind Harmer
12.984
961051AF2-396 GEN
Solar/Wind Harmer
6.039
270526AF1-158 GEN
Solar/Wind Harmer
3.652
24441505OLIV SLR
Solar/Wind Harmer
0.107
965681AG1-436 GEN
Solar/Wind Harmer
9.772
965791AG1-447 GEN
Solar/Wind Harmer
5
270599AE1-208 GEN
Solar/Wind Harmer
6.285
270031AE2-169
Solar/Wind Harmer
6.285
970321AG2-212 GEN
Solar/Wind Harmer
13.514
274808UNIV PK N;4U
Adder
3.701
274770LINCOLN ;1U
Adder
4.584
274771LINCOLN ;2U
Adder
4.584
274803UNIV PARK;6U
Adder
4.284
274888KELLY CRK;1U
Solar/Wind Harmer
4.32
274887GEN-1.85
Solar/Wind Harmer
3.9
276843GEN-1.7
Solar/Wind Harmer
0.42
958011AF2-095 GEN
Solar/Wind Harmer
10.537
972259AH1-714 GEN
Adder
13.877
274674JOLIET 9 ;6U
Adder
11.128
274847GR RIDGE ;BU
Solar/Wind Harmer
3.635
971573AH1-285 GEN
Solar/Wind Harmer
6.11
958481AF2-142 GEN
Solar/Wind Harmer
10.641
274861TOP CROP ;1U
Solar/Wind Harmer
4.297
274862TOP CROP ;2U
Solar/Wind Harmer
3.588
274695ROCKY RD ;2P
Adder
7.863
274693ROCKY RD ;1P
Adder
7.786
274697ROCKY RD ;3P
Adder
2.136
274696ROCKY RD ;4P
Adder
8.048
274683WAUKEGAN ;8U
Adder
14.856
274683WAUKEGAN ;8U
Adder
12.523
945421AF1-207 GEN
Solar/Wind Harmer
9.844
957841AF2-078 GEN
Solar/Wind Harmer
4.236
962691AG1-118 GEN
Solar/Wind Harmer
21.023
958491AF2-143 GEN
Solar/Wind Harmer
10.51
970921AG2-575 GEN
Solar/Wind Harmer
6.991
970921AG2-575 GEN
Solar/Wind Harmer
1.626
274879MINONK ;1U
Solar/Wind Harmer
4.7
942991AE2-321 GEN
Solar/Wind Harmer
6.946
274764LEE CO EC;5U
Adder
6.277
274765LEE CO EC;6U
Adder
6.277
274762LEE CO EC;3U
Adder
6.263
274763LEE CO EC;4U
Adder
6.204
972267AH1-718 GEN
Adder
2.776
247621Y3-024
Adder
0.156
246938BC-WTG3
Solar/Wind Helper
11.153
246937BC-WTG2
Solar/Wind Helper
10.964
270224U2-072_GEN2
Solar/Wind Helper
0.919
270227U2-072_GEN3
Solar/Wind Helper
0.919
270228U2-072_GEN4
Solar/Wind Helper
0.919
270231U2-072_GEN5
Solar/Wind Helper
0.919
270471AD2-092_GEN
Solar/Wind Helper
0.982
253378AE2-206_GEN
Solar/Wind Helper
0.732
276820AF1-078_GEN
Solar/Wind Helper
0.342
241960AC2-195 GEN
Solar/Wind Helper
0.763
24727205RPMNG3
50/50
3.268
971599AH1-298 GEN
50/50
10.228
24729505KEY G4
50/50
6.661
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
16.424
965041AG1-368 GEN
Solar/Wind Harmer
11.874
270071AF1-092 GEN
Solar/Wind Harmer
15.99
965051AG1-369 GEN
Solar/Wind Harmer
5.036
958711AF2-162 GEN
Solar/Wind Harmer
0.899
270024AE2-089 GEN
Solar/Wind Harmer
4.106
965101AG1-375 GEN
Solar/Wind Harmer
8.627
971771AH1-392 GEN
Solar/Wind Harmer
7.458
971347AH1-153 GEN
Solar/Wind Harmer
12.325
945581AF1-223 GEN
Solar/Wind Harmer
3.688
971769AH1-391 GEN
Solar/Wind Harmer
7.977
944161AF1-084 GEN
Solar/Wind Harmer
1.752
960681AF2-359 GEN
Solar/Wind Harmer
2.953
274814UNIV PK N;0U
Adder
3.75
274807UNIV PK N;3U
Adder
3.742
274805UNIV PK N;1U
Adder
3.726
274811UNIV PK N;7U
Adder
3.718
270536AF1-215 GEN2
Solar/Wind Harmer
3.368
274775LINCOLN ;6U
Adder
4.584
274776LINCOLN ;7U
Adder
4.584
274777LINCOLN ;8U
Adder
4.584
972037AH1-567 GEN1
Adder
0.134
274827FISK ;RP
Adder
5.694
960591AF2-350 GEN
Solar/Wind Harmer
7.317
972227AH1-698 GEN1
Adder
1.903
274687WILL CNTY;4U
Adder
20.283
274687WILL CNTY;4U
Adder
20.283
958391AF2-133 GEN
Solar/Wind Harmer
6.575
274675JOLIET 29;7U
Adder
22.222
274675JOLIET 29;7U
Adder
21.428
274731ELWOOD EC;2P
Adder
11.875
274733ELWOOD EC;3P
Adder
11.875
274735ELWOOD EC;4P
Adder
11.875
274728ELWOOD EC;5P
Adder
11.875
970833AG2-524 GEN
Solar/Wind Harmer
6.278
970833AG2-524 GEN
Solar/Wind Harmer
2.92
274746AC1-111 G10
Adder
3.99
274744AC1-111 GEN8
Adder
3.99
965461AG1-414 GEN
Solar/Wind Harmer
1.594
970289AG2-191 GEN
Solar/Wind Harmer
1.336
276868AE1-113 GEN
Solar/Wind Harmer
7.049
276882AE2-255 GEN
Solar/Wind Harmer
2.35
270594AE1-207 GEN
Solar/Wind Harmer
10.213
971177AH1-047 GEN
Solar/Wind Harmer
4.069
274823ROCKFORD ;21
Adder
13.342
957201AF2-014 GEN
Solar/Wind Helper
8.667
270317AD1-130_GEN
Solar/Wind Helper
4.304
966831AG1-554 GEN
Solar/Wind Helper
0.913
270284AF1-227 GEN1
Solar/Wind Helper
2.061
270286AF1-227 GEN2
Solar/Wind Helper
0.756
270287AF1-227 GEN3
Solar/Wind Helper
0.756
270499AE1-146 GEN
Solar/Wind Helper
2.039
945641AF1-229 GEN
Solar/Wind Helper
0.989
253383AE2-342_GEN
Solar/Wind Helper
0.361
971411AH1-196 GEN
Solar/Wind Harmer
5.539
24727005RPMNG1
50/50
3.284
960861AF2-377 GEN
50/50
2.347
970521AG2-332 GEN
50/50
10.682
24639705ELKHART HY
50/50
0.148
965011AG1-365 GEN
Solar/Wind Harmer
19.549
270063AE2-323 C
Solar/Wind Harmer
2.317
247521TR3_G114
Solar/Wind Harmer
3.391
270246TR4_N_V150
Solar/Wind Harmer
0.858
944231AF1-091 GEN
Solar/Wind Harmer
3.689
965651AG1-433 GEN
Solar/Wind Harmer
4.856
24695305TIMB G C
Solar/Wind Harmer
4.856
958861AF2-177 GEN
Solar/Wind Harmer
9.429
945111AF1-176 GEN
Solar/Wind Harmer
14.978
270505AE1-170 C O1
Solar/Wind Harmer
12.278
945371AF1-202 GEN
Solar/Wind Harmer
5.674
270449AD2-020 GEN
Solar/Wind Harmer
2.257
943021AE2-325 GEN
Solar/Wind Harmer
2.933
970245AG2-165 GEN
Solar/Wind Harmer
13.514
970373AG2-245 GEN
Solar/Wind Harmer
15.829
274751CRETE EC ;1U
Adder
3.67
274754CRETE EC ;4U
Adder
3.67
274723RIVER EC ;12
Adder
13.411
274812UNIV PK N;8U
Adder
3.718
276164X3-005 C
Solar/Wind Harmer
0.521
270055AF2-134 C O1
Solar/Wind Harmer
2.245
972207SS24-0001
Solar/Wind Harmer
16.298
274773LINCOLN ;4U
Adder
4.584
274774LINCOLN ;5U
Adder
4.584
274801UNIV PARK;4U
Adder
4.271
276776AD2-060 GEN
Solar/Wind Harmer
0.309
958381AF2-132 GEN
Solar/Wind Harmer
6.626
964861AG1-349 GEN
Solar/Wind Harmer
5.732
971917AH1-482 GEN
Solar/Wind Harmer
6.615
941551AE2-152 GEN
Solar/Wind Harmer
3.286
274676JOLIET 29;8U
Adder
22.222
274674JOLIET 9 ;6U
Adder
11.128
274732ELWOOD EC;7P
Adder
11.875
274871GR RIDGE ;2U
Solar/Wind Harmer
5.526
940581AE2-045 GEN
Solar/Wind Harmer
7.295
971605AH1-302 GEN
Solar/Wind Harmer
6.238
274745AC1-111 GEN9
Adder
3.99
276691AA1-018 GEN1
Solar/Wind Harmer
0.33
274682WAUKEGAN ;7U
Adder
12.686
274828WAUKEGAN ;BP
Adder
7.787
970291AG2-192 GEN
Solar/Wind Harmer
0.914
960751AF2-366 GEN
Solar/Wind Harmer
2.006
962781AG1-127 GEN
Solar/Wind Harmer
6.648
939401AE1-172 GEN
Solar/Wind Harmer
9.737
276901AD2-066 C O1
Solar/Wind Harmer
2.454
270005AE1-210 C O1
Solar/Wind Harmer
3.813
965031AG1-367 GEN
Solar/Wind Harmer
6.977
274872LEEDK;1U
Solar/Wind Harmer
5.729
270032AE2-172
Solar/Wind Harmer
3.232
971997AH1-543 GEN
Solar/Wind Harmer
10.924
274822ROCKFORD ;11
Adder
13.439
972235AH1-702 GEN1
Adder
1.722
274761LEE CO EC;2U
Adder
6.263
274766LEE CO EC;7U
Adder
6.189
24728605AND G2
Adder
2.022
246936BC-WTG1
Solar/Wind Helper
10.964
270462AD2-086
Solar/Wind Helper
3.886
270223U2-072_GEN1
Solar/Wind Helper
0.919
270578AF1-285 GEN2
Solar/Wind Helper
0.623
270391AF1-285 GEN3
Solar/Wind Helper
0.623
247522W1-056 GEN
Solar/Wind Helper
1.219
960841AF2-375 GEN
Solar/Wind Helper
1.228
270349AD2-093_GEN
Solar/Wind Helper
0.982
24727105RPMNG2
50/50
3.296
970583AG2-370 GEN
50/50
2.761
960851AF2-376 GEN
50/50
2.052
24641605TWIN BRNCH
50/50
0.015
959331AF2-224 GEN
Solar/Wind Harmer
19.549
965021AG1-366 GEN
Solar/Wind Harmer
4.546
970031AG2-029 GEN
Solar/Wind Harmer
35.759
270043AE2-236 GEN
Solar/Wind Harmer
6.31
270191TR4_S_V150
Solar/Wind Harmer
3.026
270247TR4_N_V136
Solar/Wind Harmer
0.858
944531AF1-118 GEN
Solar/Wind Harmer
34.867
971617AH1-308 GEN
Solar/Wind Harmer
5.086
247643Z2-116 C
Solar/Wind Harmer
0.061
945111AF1-176 GEN
Solar/Wind Harmer
4.747
970349AG2-230 GEN
Solar/Wind Harmer
12.325
24642205MAYFLWER
Adder
0.518
24441205WTRV SLR C
Solar/Wind Harmer
0.103
970513AG2-328 GEN
Solar/Wind Harmer
13.514
970517AG2-330 GEN
Solar/Wind Harmer
12.257
972231SS25-0005
Solar/Wind Harmer
7.126
972181SS23-001
Solar/Wind Harmer
4.454
274752CRETE EC ;2U
Adder
3.67
274753CRETE EC ;3U
Adder
3.67
274724RIVER EC ;11
Adder
13.248
270535AF1-215 GEN1
Solar/Wind Harmer
3.368
247604X1-042
Adder
0.308
274772LINCOLN ;3U
Adder
4.584
274802UNIV PARK;5U
Adder
4.284
274826FISK ;BP
Adder
8.035
274800UNIV PARK;3U
Adder
4.271
972038AH1-567 GEN2
Adder
0.267
276772AC2-154 GEN
Solar/Wind Harmer
2.041
276806AD2-047 C O1
Solar/Wind Harmer
7.828
970941AG2-585 GEN
Solar/Wind Harmer
9.146
964401AG1-302 GEN
Solar/Wind Harmer
6.626
972228AH1-698 GEN2
Adder
2.703
970707AG2-453 GEN
Solar/Wind Harmer
20.363
276897AD1-100 C
Solar/Wind Harmer
21.024
939351AE1-166 GEN
Solar/Wind Harmer
4.296
274676JOLIET 29;8U
Adder
21.428
276893AG1-478 C
Solar/Wind Harmer
0.302
274729ELWOOD EC;1P
Adder
11.875
274730ELWOOD EC;6P
Adder
11.875
274734ELWOOD EC;8P
Adder
11.875
274736ELWOOD EC;9P
Adder
11.875
959141AF2-205 GEN
Solar/Wind Harmer
4.356
943121AE2-341 GEN
Solar/Wind Harmer
10.713
943591AF1-030 GEN
Solar/Wind Harmer
7.142
247642Z2-115 C
Solar/Wind Harmer
0.046
276694AA1-018 GEN2
Solar/Wind Harmer
4.477
274682WAUKEGAN ;7U
Adder
12.686
970289AG2-191 GEN
Solar/Wind Harmer
0.54
970291AG2-192 GEN
Solar/Wind Harmer
0.491
276805AD2-038 GEN
Solar/Wind Harmer
3.595
958821AF2-173 GEN
Solar/Wind Harmer
9.767
270004AE1-209 GEN
Solar/Wind Harmer
3.813
274872LEEDK;1U
Solar/Wind Harmer
0.178
972236AH1-702 GEN2
Adder
1.497
274760LEE CO EC;1U
Adder
6.263
274767LEE CO EC;8U
Adder
6.189
24728705AND G3
Adder
4.229
24728505AND G1
Adder
2.022
270485AE1-090_GEN
Solar/Wind Helper
0.338
942871AE2-306 GEN
Solar/Wind Helper
0.467
270541AE2-072 C
Solar/Wind Helper
0.991
944201AF1-088_MTX
Adder
55.177
957141AF2-008_MTX
Adder
27.589
990497J1323
External Queue
1.5705512762069702
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.177
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.048
MECLTFEXP_MEC->PJM
CLTF
9.629
SIGELTFEXP_SIGE->PJM
CLTF
0.197
LAGNLTFEXP_LAGN->PJM
CLTF
5.849
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.934
TVALTFEXP_TVA->PJM
CLTF
2.367
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.454
NYPJM->LTFIMP_NY
CLTF
1.28
LGEELTFEXP_LGEE->PJM
CLTF
1.786
WECLTFEXP_WEC->PJM
CLTF
2.606
AG2-052LTFEXP_AG2-052->PJM
LTF
0.169
AH1-155LTFEXP_AH1-155->PJM
LTF
0.253

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.89 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2575.8
MW Contribution:36.14
Bus #Bus NameTypeMW Contribution
24727105RPMNG2
50/50
3.32
970583AG2-370 GEN
50/50
2.809
960851AF2-376 GEN
50/50
2.105
24641605TWIN BRNCH
50/50
0.015
959331AF2-224 GEN
Solar/Wind Harmer
19.727
965021AG1-366 GEN
Solar/Wind Harmer
4.588
970031AG2-029 GEN
Solar/Wind Harmer
36.141
270043AE2-236 GEN
Solar/Wind Harmer
6.378
270191TR4_S_V150
Solar/Wind Harmer
3.093
270247TR4_N_V136
Solar/Wind Harmer
0.877
944531AF1-118 GEN
Solar/Wind Harmer
35.247
971617AH1-308 GEN
Solar/Wind Harmer
5.166
247643Z2-116 C
Solar/Wind Harmer
0.061
945111AF1-176 GEN
Solar/Wind Harmer
4.805
970349AG2-230 GEN
Solar/Wind Harmer
12.452
24642205MAYFLWER
Adder
0.524
24441205WTRV SLR C
Solar/Wind Harmer
0.104
970513AG2-328 GEN
Solar/Wind Harmer
13.624
970517AG2-330 GEN
Solar/Wind Harmer
12.357
972231SS25-0005
Solar/Wind Harmer
7.189
972181SS23-001
Solar/Wind Harmer
4.493
274752CRETE EC ;2U
Adder
3.702
274753CRETE EC ;3U
Adder
3.702
274724RIVER EC ;11
Adder
13.364
247604X1-042
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
3.398
274772LINCOLN ;3U
Adder
4.622
274802UNIV PARK;5U
Adder
4.319
274826FISK ;BP
Adder
8.102
274800UNIV PARK;3U
Adder
4.307
972038AH1-567 GEN2
Adder
0.27
276772AC2-154 GEN
Solar/Wind Harmer
2.057
276806AD2-047 C O1
Solar/Wind Harmer
7.892
970941AG2-585 GEN
Solar/Wind Harmer
9.222
964401AG1-302 GEN
Solar/Wind Harmer
6.683
972228AH1-698 GEN2
Adder
2.725
970707AG2-453 GEN
Solar/Wind Harmer
20.528
276897AD1-100 C
Solar/Wind Harmer
21.195
939351AE1-166 GEN
Solar/Wind Harmer
4.331
274676JOLIET 29;8U
Adder
21.601
276893AG1-478 C
Solar/Wind Harmer
0.304
274730ELWOOD EC;6P
Adder
11.97
274734ELWOOD EC;8P
Adder
11.97
274736ELWOOD EC;9P
Adder
11.97
274729ELWOOD EC;1P
Adder
11.97
959141AF2-205 GEN
Solar/Wind Harmer
4.392
943121AE2-341 GEN
Solar/Wind Harmer
10.796
943591AF1-030 GEN
Solar/Wind Harmer
7.197
247642Z2-115 C
Solar/Wind Harmer
0.046
276694AA1-018 GEN2
Solar/Wind Harmer
4.512
274682WAUKEGAN ;7U
Adder
12.782
970289AG2-191 GEN
Solar/Wind Harmer
0.545
970291AG2-192 GEN
Solar/Wind Harmer
0.496
958821AF2-173 GEN
Solar/Wind Harmer
9.891
270004AE1-209 GEN
Solar/Wind Harmer
3.861
276805AD2-038 GEN
Solar/Wind Harmer
3.622
274872LEEDK;1U
Solar/Wind Harmer
0.18
972236AH1-702 GEN2
Adder
1.508
274760LEE CO EC;1U
Adder
6.304
274767LEE CO EC;8U
Adder
6.23
24728705AND G3
Adder
4.272
24728505AND G1
Adder
2.043
270485AE1-090_GEN
Solar/Wind Helper
0.323
942871AE2-306 GEN
Solar/Wind Helper
0.443
270541AE2-072 C
Solar/Wind Helper
0.932
970615AG2-402 GEN
50/50
4.588
24729405KEY G3
50/50
0.368
24729305KEY G2
50/50
0.361
24729205KEY G1
50/50
0.36
247620Y3-023
50/50
0.463
970611AG2-400 GEN
Solar/Wind Harmer
19.727
942221AE2-234 GEN
Solar/Wind Harmer
0.714
944541AF1-119 GEN
Solar/Wind Harmer
3.764
960971AF2-388 GEN
Solar/Wind Harmer
9.823
270216AD2-079_GEN
Solar/Wind Harmer
0.535
960981AF2-389 GEN
Solar/Wind Harmer
1.263
957891AF2-083 GEN
Solar/Wind Harmer
2.815
961051AF2-396 GEN
Solar/Wind Harmer
13.147
961051AF2-396 GEN
Solar/Wind Harmer
6.115
270526AF1-158 GEN
Solar/Wind Harmer
3.692
24441505OLIV SLR
Solar/Wind Harmer
0.108
965681AG1-436 GEN
Solar/Wind Harmer
9.872
965791AG1-447 GEN
Solar/Wind Harmer
5.051
270599AE1-208 GEN
Solar/Wind Harmer
6.363
270031AE2-169
Solar/Wind Harmer
6.363
970321AG2-212 GEN
Solar/Wind Harmer
13.624
274808UNIV PK N;4U
Adder
3.733
274770LINCOLN ;1U
Adder
4.622
274771LINCOLN ;2U
Adder
4.622
274803UNIV PARK;6U
Adder
4.319
274888KELLY CRK;1U
Solar/Wind Harmer
4.356
274887GEN-1.85
Solar/Wind Harmer
3.932
276843GEN-1.7
Solar/Wind Harmer
0.423
958011AF2-095 GEN
Solar/Wind Harmer
10.624
972259AH1-714 GEN
Adder
13.99
274674JOLIET 9 ;6U
Adder
11.217
274847GR RIDGE ;BU
Solar/Wind Harmer
3.664
971573AH1-285 GEN
Solar/Wind Harmer
6.157
958481AF2-142 GEN
Solar/Wind Harmer
10.724
274861TOP CROP ;1U
Solar/Wind Harmer
4.33
274862TOP CROP ;2U
Solar/Wind Harmer
3.616
274695ROCKY RD ;2P
Adder
7.922
274693ROCKY RD ;1P
Adder
7.844
274697ROCKY RD ;3P
Adder
2.152
274696ROCKY RD ;4P
Adder
8.109
274683WAUKEGAN ;8U
Adder
14.968
274683WAUKEGAN ;8U
Adder
12.617
945421AF1-207 GEN
Solar/Wind Harmer
9.918
957841AF2-078 GEN
Solar/Wind Harmer
4.268
962691AG1-118 GEN
Solar/Wind Harmer
21.179
958491AF2-143 GEN
Solar/Wind Harmer
10.589
970921AG2-575 GEN
Solar/Wind Harmer
7.042
970921AG2-575 GEN
Solar/Wind Harmer
1.638
274879MINONK ;1U
Solar/Wind Harmer
4.734
942991AE2-321 GEN
Solar/Wind Harmer
6.996
274764LEE CO EC;5U
Adder
6.319
274765LEE CO EC;6U
Adder
6.319
274762LEE CO EC;3U
Adder
6.304
274763LEE CO EC;4U
Adder
6.245
972267AH1-718 GEN
Adder
2.793
247621Y3-024
Adder
0.16
246938BC-WTG3
Solar/Wind Helper
11.083
246937BC-WTG2
Solar/Wind Helper
10.895
270224U2-072_GEN2
Solar/Wind Helper
0.871
270227U2-072_GEN3
Solar/Wind Helper
0.871
270228U2-072_GEN4
Solar/Wind Helper
0.871
270231U2-072_GEN5
Solar/Wind Helper
0.871
270471AD2-092_GEN
Solar/Wind Helper
0.85
253378AE2-206_GEN
Solar/Wind Helper
0.684
276820AF1-078_GEN
Solar/Wind Helper
0.319
241960AC2-195 GEN
Solar/Wind Helper
0.69
24727205RPMNG3
50/50
3.292
971599AH1-298 GEN
50/50
10.333
24729505KEY G4
50/50
6.735
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
16.635
965041AG1-368 GEN
Solar/Wind Harmer
12.077
270071AF1-092 GEN
Solar/Wind Harmer
16.152
965051AG1-369 GEN
Solar/Wind Harmer
5.148
958711AF2-162 GEN
Solar/Wind Harmer
0.909
270024AE2-089 GEN
Solar/Wind Harmer
4.17
965101AG1-375 GEN
Solar/Wind Harmer
8.727
971771AH1-392 GEN
Solar/Wind Harmer
7.543
971347AH1-153 GEN
Solar/Wind Harmer
12.452
945581AF1-223 GEN
Solar/Wind Harmer
3.732
971769AH1-391 GEN
Solar/Wind Harmer
8.064
944161AF1-084 GEN
Solar/Wind Harmer
1.775
960681AF2-359 GEN
Solar/Wind Harmer
2.984
274814UNIV PK N;0U
Adder
3.782
274807UNIV PK N;3U
Adder
3.774
274805UNIV PK N;1U
Adder
3.758
274811UNIV PK N;7U
Adder
3.75
270536AF1-215 GEN2
Solar/Wind Harmer
3.398
274775LINCOLN ;6U
Adder
4.622
274776LINCOLN ;7U
Adder
4.622
274777LINCOLN ;8U
Adder
4.622
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.742
960591AF2-350 GEN
Solar/Wind Harmer
7.378
972227AH1-698 GEN1
Adder
1.919
274687WILL CNTY;4U
Adder
20.447
274687WILL CNTY;4U
Adder
20.447
958391AF2-133 GEN
Solar/Wind Harmer
6.63
274675JOLIET 29;7U
Adder
22.401
274675JOLIET 29;7U
Adder
21.601
274728ELWOOD EC;5P
Adder
11.97
274731ELWOOD EC;2P
Adder
11.97
274733ELWOOD EC;3P
Adder
11.97
274735ELWOOD EC;4P
Adder
11.97
970833AG2-524 GEN
Solar/Wind Harmer
6.328
970833AG2-524 GEN
Solar/Wind Harmer
2.943
274746AC1-111 G10
Adder
4.021
274744AC1-111 GEN8
Adder
4.021
965461AG1-414 GEN
Solar/Wind Harmer
1.612
970289AG2-191 GEN
Solar/Wind Harmer
1.35
270594AE1-207 GEN
Solar/Wind Harmer
10.331
276868AE1-113 GEN
Solar/Wind Harmer
7.101
276882AE2-255 GEN
Solar/Wind Harmer
2.367
971177AH1-047 GEN
Solar/Wind Harmer
4.098
274823ROCKFORD ;21
Adder
13.435
957201AF2-014 GEN
Solar/Wind Helper
8.613
270317AD1-130_GEN
Solar/Wind Helper
4.113
966831AG1-554 GEN
Solar/Wind Helper
0.876
270284AF1-227 GEN1
Solar/Wind Helper
1.876
270286AF1-227 GEN2
Solar/Wind Helper
0.688
270287AF1-227 GEN3
Solar/Wind Helper
0.688
270499AE1-146 GEN
Solar/Wind Helper
1.952
945641AF1-229 GEN
Solar/Wind Helper
0.937
971411AH1-196 GEN
Solar/Wind Harmer
5.579
24727005RPMNG1
50/50
3.308
960861AF2-377 GEN
50/50
2.399
970521AG2-332 GEN
50/50
10.806
24639705ELKHART HY
50/50
0.149
965011AG1-365 GEN
Solar/Wind Harmer
19.727
270063AE2-323 C
Solar/Wind Harmer
2.344
247521TR3_G114
Solar/Wind Harmer
3.467
270246TR4_N_V150
Solar/Wind Harmer
0.877
944231AF1-091 GEN
Solar/Wind Harmer
3.756
24695305TIMB G C
Solar/Wind Harmer
4.981
965651AG1-433 GEN
Solar/Wind Harmer
4.912
958861AF2-177 GEN
Solar/Wind Harmer
9.538
945111AF1-176 GEN
Solar/Wind Harmer
15.162
270505AE1-170 C O1
Solar/Wind Harmer
12.429
945371AF1-202 GEN
Solar/Wind Harmer
5.742
270449AD2-020 GEN
Solar/Wind Harmer
2.286
943021AE2-325 GEN
Solar/Wind Harmer
2.97
970245AG2-165 GEN
Solar/Wind Harmer
13.624
970373AG2-245 GEN
Solar/Wind Harmer
15.978
274751CRETE EC ;1U
Adder
3.702
274754CRETE EC ;4U
Adder
3.702
274723RIVER EC ;12
Adder
13.527
274812UNIV PK N;8U
Adder
3.75
276164X3-005 C
Solar/Wind Harmer
0.526
270055AF2-134 C O1
Solar/Wind Harmer
2.265
972207SS24-0001
Solar/Wind Harmer
16.435
274773LINCOLN ;4U
Adder
4.622
274774LINCOLN ;5U
Adder
4.622
274801UNIV PARK;4U
Adder
4.307
276776AD2-060 GEN
Solar/Wind Harmer
0.312
958381AF2-132 GEN
Solar/Wind Harmer
6.683
964861AG1-349 GEN
Solar/Wind Harmer
5.781
971917AH1-482 GEN
Solar/Wind Harmer
6.671
941551AE2-152 GEN
Solar/Wind Harmer
3.312
274676JOLIET 29;8U
Adder
22.401
274674JOLIET 9 ;6U
Adder
11.217
274732ELWOOD EC;7P
Adder
11.97
274871GR RIDGE ;2U
Solar/Wind Harmer
5.57
940581AE2-045 GEN
Solar/Wind Harmer
7.354
971605AH1-302 GEN
Solar/Wind Harmer
6.288
274745AC1-111 GEN9
Adder
4.021
276691AA1-018 GEN1
Solar/Wind Harmer
0.333
274682WAUKEGAN ;7U
Adder
12.782
970291AG2-192 GEN
Solar/Wind Harmer
0.924
274828WAUKEGAN ;BP
Adder
7.846
270005AE1-210 C O1
Solar/Wind Harmer
3.861
965031AG1-367 GEN
Solar/Wind Harmer
7.065
960751AF2-366 GEN
Solar/Wind Harmer
2.02
962781AG1-127 GEN
Solar/Wind Harmer
6.697
939401AE1-172 GEN
Solar/Wind Harmer
9.81
276901AD2-066 C O1
Solar/Wind Harmer
2.472
270032AE2-172
Solar/Wind Harmer
3.269
274872LEEDK;1U
Solar/Wind Harmer
5.771
971997AH1-543 GEN
Solar/Wind Harmer
11.004
274822ROCKFORD ;11
Adder
13.533
972235AH1-702 GEN1
Adder
1.734
274761LEE CO EC;2U
Adder
6.304
274766LEE CO EC;7U
Adder
6.23
24728605AND G2
Adder
2.043
246936BC-WTG1
Solar/Wind Helper
10.895
270462AD2-086
Solar/Wind Helper
3.714
270223U2-072_GEN1
Solar/Wind Helper
0.871
270578AF1-285 GEN2
Solar/Wind Helper
0.59
270391AF1-285 GEN3
Solar/Wind Helper
0.59
247522W1-056 GEN
Solar/Wind Helper
1.168
960841AF2-375 GEN
Solar/Wind Helper
1.175
270349AD2-093_GEN
Solar/Wind Helper
0.85
944201AF1-088_MTX
Adder
55.165
957141AF2-008_MTX
Adder
27.582
990497J1323
External Queue
1.5914489030838013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.309
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.744
MECLTFEXP_MEC->PJM
CLTF
9.656
SIGELTFEXP_SIGE->PJM
CLTF
0.197
LAGNLTFEXP_LAGN->PJM
CLTF
5.694
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.439
TVALTFEXP_TVA->PJM
CLTF
2.27
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.944
NYPJM->LTFIMP_NY
CLTF
1.265
LGEELTFEXP_LGEE->PJM
CLTF
1.782
WECLTFEXP_WEC->PJM
CLTF
2.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.15 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2543.28
MW Contribution:35.17
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.494
24729405KEY G3
50/50
0.357
24729305KEY G2
50/50
0.351
24729205KEY G1
50/50
0.349
247620Y3-023
50/50
0.448
970611AG2-400 GEN
Solar/Wind Harmer
19.324
942221AE2-234 GEN
Solar/Wind Harmer
0.691
944541AF1-119 GEN
Solar/Wind Harmer
3.645
960971AF2-388 GEN
Solar/Wind Harmer
9.511
270216AD2-079_GEN
Solar/Wind Harmer
0.518
960981AF2-389 GEN
Solar/Wind Harmer
1.22
957891AF2-083 GEN
Solar/Wind Harmer
2.72
961051AF2-396 GEN
Solar/Wind Harmer
12.698
961051AF2-396 GEN
Solar/Wind Harmer
5.906
270526AF1-158 GEN
Solar/Wind Harmer
3.57
24441505OLIV SLR
Solar/Wind Harmer
0.104
965681AG1-436 GEN
Solar/Wind Harmer
9.546
965791AG1-447 GEN
Solar/Wind Harmer
4.884
270599AE1-208 GEN
Solar/Wind Harmer
6.137
270031AE2-169
Solar/Wind Harmer
6.137
970321AG2-212 GEN
Solar/Wind Harmer
13.188
274808UNIV PK N;4U
Adder
3.612
274770LINCOLN ;1U
Adder
4.473
274771LINCOLN ;2U
Adder
4.473
274803UNIV PARK;6U
Adder
4.179
274888KELLY CRK;1U
Solar/Wind Harmer
4.214
274887GEN-1.85
Solar/Wind Harmer
3.805
276843GEN-1.7
Solar/Wind Harmer
0.409
958011AF2-095 GEN
Solar/Wind Harmer
10.279
972259AH1-714 GEN
Adder
13.536
274674JOLIET 9 ;6U
Adder
10.853
274847GR RIDGE ;BU
Solar/Wind Harmer
3.545
971573AH1-285 GEN
Solar/Wind Harmer
5.957
958481AF2-142 GEN
Solar/Wind Harmer
10.374
274861TOP CROP ;1U
Solar/Wind Harmer
4.189
274862TOP CROP ;2U
Solar/Wind Harmer
3.498
274695ROCKY RD ;2P
Adder
7.665
274693ROCKY RD ;1P
Adder
7.589
274697ROCKY RD ;3P
Adder
2.082
274696ROCKY RD ;4P
Adder
7.846
274683WAUKEGAN ;8U
Adder
14.481
274683WAUKEGAN ;8U
Adder
12.207
962691AG1-118 GEN
Solar/Wind Harmer
20.49
958491AF2-143 GEN
Solar/Wind Harmer
10.244
945421AF1-207 GEN
Solar/Wind Harmer
9.591
957841AF2-078 GEN
Solar/Wind Harmer
4.127
970921AG2-575 GEN
Solar/Wind Harmer
6.813
970921AG2-575 GEN
Solar/Wind Harmer
1.584
274879MINONK ;1U
Solar/Wind Harmer
4.58
942991AE2-321 GEN
Solar/Wind Harmer
6.769
274764LEE CO EC;5U
Adder
6.113
274765LEE CO EC;6U
Adder
6.113
274762LEE CO EC;3U
Adder
6.098
274763LEE CO EC;4U
Adder
6.041
972267AH1-718 GEN
Adder
2.702
247621Y3-024
Adder
0.152
246938BC-WTG3
Solar/Wind Helper
11.223
246937BC-WTG2
Solar/Wind Helper
11.033
270224U2-072_GEN2
Solar/Wind Helper
0.966
270227U2-072_GEN3
Solar/Wind Helper
0.966
270228U2-072_GEN4
Solar/Wind Helper
0.966
270231U2-072_GEN5
Solar/Wind Helper
0.966
270471AD2-092_GEN
Solar/Wind Helper
1.12
253378AE2-206_GEN
Solar/Wind Helper
0.765
276820AF1-078_GEN
Solar/Wind Helper
0.357
241960AC2-195 GEN
Solar/Wind Helper
0.77
24727205RPMNG3
50/50
3.243
971599AH1-298 GEN
50/50
10.058
24729505KEY G4
50/50
6.532
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
16.143
965041AG1-368 GEN
Solar/Wind Harmer
11.642
270071AF1-092 GEN
Solar/Wind Harmer
15.699
965051AG1-369 GEN
Solar/Wind Harmer
4.914
958711AF2-162 GEN
Solar/Wind Harmer
0.88
270024AE2-089 GEN
Solar/Wind Harmer
4.014
965101AG1-375 GEN
Solar/Wind Harmer
8.444
971771AH1-392 GEN
Solar/Wind Harmer
7.295
971347AH1-153 GEN
Solar/Wind Harmer
12.051
945581AF1-223 GEN
Solar/Wind Harmer
3.606
971769AH1-391 GEN
Solar/Wind Harmer
7.796
944161AF1-084 GEN
Solar/Wind Harmer
1.712
960681AF2-359 GEN
Solar/Wind Harmer
2.885
274814UNIV PK N;0U
Adder
3.66
274807UNIV PK N;3U
Adder
3.652
274805UNIV PK N;1U
Adder
3.636
274811UNIV PK N;7U
Adder
3.628
270536AF1-215 GEN2
Solar/Wind Harmer
3.286
274775LINCOLN ;6U
Adder
4.473
274776LINCOLN ;7U
Adder
4.473
274777LINCOLN ;8U
Adder
4.473
972037AH1-567 GEN1
Adder
0.131
274827FISK ;RP
Adder
5.556
960591AF2-350 GEN
Solar/Wind Harmer
7.138
972227AH1-698 GEN1
Adder
1.856
274687WILL CNTY;4U
Adder
19.783
274687WILL CNTY;4U
Adder
19.783
958391AF2-133 GEN
Solar/Wind Harmer
6.411
274675JOLIET 29;7U
Adder
21.674
274675JOLIET 29;7U
Adder
20.9
274731ELWOOD EC;2P
Adder
11.581
274733ELWOOD EC;3P
Adder
11.581
274735ELWOOD EC;4P
Adder
11.581
274728ELWOOD EC;5P
Adder
11.581
970833AG2-524 GEN
Solar/Wind Harmer
6.122
970833AG2-524 GEN
Solar/Wind Harmer
2.848
274746AC1-111 G10
Adder
3.891
274744AC1-111 GEN8
Adder
3.891
965461AG1-414 GEN
Solar/Wind Harmer
1.554
970289AG2-191 GEN
Solar/Wind Harmer
1.302
276868AE1-113 GEN
Solar/Wind Harmer
6.869
276882AE2-255 GEN
Solar/Wind Harmer
2.29
270594AE1-207 GEN
Solar/Wind Harmer
9.95
971177AH1-047 GEN
Solar/Wind Harmer
3.965
274823ROCKFORD ;21
Adder
12.997
957201AF2-014 GEN
Solar/Wind Helper
8.722
270317AD1-130_GEN
Solar/Wind Helper
4.487
966831AG1-554 GEN
Solar/Wind Helper
0.929
270284AF1-227 GEN1
Solar/Wind Helper
2.25
270286AF1-227 GEN2
Solar/Wind Helper
0.825
270287AF1-227 GEN3
Solar/Wind Helper
0.825
270499AE1-146 GEN
Solar/Wind Helper
2.084
945641AF1-229 GEN
Solar/Wind Helper
1.001
253383AE2-342_GEN
Solar/Wind Helper
0.365
971411AH1-196 GEN
Solar/Wind Harmer
5.397
24727005RPMNG1
50/50
3.259
960861AF2-377 GEN
50/50
2.29
970521AG2-332 GEN
50/50
10.466
24639705ELKHART HY
50/50
0.145
965011AG1-365 GEN
Solar/Wind Harmer
19.324
270063AE2-323 C
Solar/Wind Harmer
2.274
247521TR3_G114
Solar/Wind Harmer
3.309
270246TR4_N_V150
Solar/Wind Harmer
0.837
944231AF1-091 GEN
Solar/Wind Harmer
3.613
965651AG1-433 GEN
Solar/Wind Harmer
4.756
24695305TIMB G C
Solar/Wind Harmer
4.723
958861AF2-177 GEN
Solar/Wind Harmer
9.23
945111AF1-176 GEN
Solar/Wind Harmer
14.654
270505AE1-170 C O1
Solar/Wind Harmer
12.008
945371AF1-202 GEN
Solar/Wind Harmer
5.548
270449AD2-020 GEN
Solar/Wind Harmer
2.207
943021AE2-325 GEN
Solar/Wind Harmer
2.867
970245AG2-165 GEN
Solar/Wind Harmer
13.188
970373AG2-245 GEN
Solar/Wind Harmer
15.45
274751CRETE EC ;1U
Adder
3.582
274754CRETE EC ;4U
Adder
3.582
274723RIVER EC ;12
Adder
13.089
274812UNIV PK N;8U
Adder
3.628
276164X3-005 C
Solar/Wind Harmer
0.509
270055AF2-134 C O1
Solar/Wind Harmer
2.19
972207SS24-0001
Solar/Wind Harmer
15.903
274773LINCOLN ;4U
Adder
4.473
274774LINCOLN ;5U
Adder
4.473
274801UNIV PARK;4U
Adder
4.167
276776AD2-060 GEN
Solar/Wind Harmer
0.302
958381AF2-132 GEN
Solar/Wind Harmer
6.462
964861AG1-349 GEN
Solar/Wind Harmer
5.59
971917AH1-482 GEN
Solar/Wind Harmer
6.451
941551AE2-152 GEN
Solar/Wind Harmer
3.205
274676JOLIET 29;8U
Adder
21.674
274674JOLIET 9 ;6U
Adder
10.853
274732ELWOOD EC;7P
Adder
11.581
274871GR RIDGE ;2U
Solar/Wind Harmer
5.389
940581AE2-045 GEN
Solar/Wind Harmer
7.111
971605AH1-302 GEN
Solar/Wind Harmer
6.081
274745AC1-111 GEN9
Adder
3.891
276691AA1-018 GEN1
Solar/Wind Harmer
0.322
274682WAUKEGAN ;7U
Adder
12.367
274828WAUKEGAN ;BP
Adder
7.591
970291AG2-192 GEN
Solar/Wind Harmer
0.891
960751AF2-366 GEN
Solar/Wind Harmer
1.955
962781AG1-127 GEN
Solar/Wind Harmer
6.479
939401AE1-172 GEN
Solar/Wind Harmer
9.489
276901AD2-066 C O1
Solar/Wind Harmer
2.391
270005AE1-210 C O1
Solar/Wind Harmer
3.716
965031AG1-367 GEN
Solar/Wind Harmer
6.8
274872LEEDK;1U
Solar/Wind Harmer
5.583
270032AE2-172
Solar/Wind Harmer
3.149
971997AH1-543 GEN
Solar/Wind Harmer
10.644
274822ROCKFORD ;11
Adder
13.092
972235AH1-702 GEN1
Adder
1.677
274761LEE CO EC;2U
Adder
6.098
274766LEE CO EC;7U
Adder
6.027
24728605AND G2
Adder
1.957
246936BC-WTG1
Solar/Wind Helper
11.033
270462AD2-086
Solar/Wind Helper
4.05
270223U2-072_GEN1
Solar/Wind Helper
0.966
270578AF1-285 GEN2
Solar/Wind Helper
0.654
270391AF1-285 GEN3
Solar/Wind Helper
0.654
247522W1-056 GEN
Solar/Wind Helper
1.243
960841AF2-375 GEN
Solar/Wind Helper
1.254
270349AD2-093_GEN
Solar/Wind Helper
1.12
24727105RPMNG2
50/50
3.27
970583AG2-370 GEN
50/50
2.707
959331AF2-224 GEN
Solar/Wind Harmer
19.324
965021AG1-366 GEN
Solar/Wind Harmer
4.494
970031AG2-029 GEN
Solar/Wind Harmer
35.17
270043AE2-236 GEN
Solar/Wind Harmer
6.202
270191TR4_S_V150
Solar/Wind Harmer
2.952
270247TR4_N_V136
Solar/Wind Harmer
0.837
944531AF1-118 GEN
Solar/Wind Harmer
34.207
971617AH1-308 GEN
Solar/Wind Harmer
4.972
247643Z2-116 C
Solar/Wind Harmer
0.059
945111AF1-176 GEN
Solar/Wind Harmer
4.644
970349AG2-230 GEN
Solar/Wind Harmer
12.051
24642205MAYFLWER
Adder
0.507
24441205WTRV SLR C
Solar/Wind Harmer
0.1
970513AG2-328 GEN
Solar/Wind Harmer
13.188
970517AG2-330 GEN
Solar/Wind Harmer
11.962
972231SS25-0005
Solar/Wind Harmer
6.955
972181SS23-001
Solar/Wind Harmer
4.347
274752CRETE EC ;2U
Adder
3.582
274753CRETE EC ;3U
Adder
3.582
274724RIVER EC ;11
Adder
12.93
270535AF1-215 GEN1
Solar/Wind Harmer
3.286
247604X1-042
Adder
0.301
274772LINCOLN ;3U
Adder
4.473
274802UNIV PARK;5U
Adder
4.179
274826FISK ;BP
Adder
7.839
274800UNIV PARK;3U
Adder
4.167
972038AH1-567 GEN2
Adder
0.261
276772AC2-154 GEN
Solar/Wind Harmer
1.991
276806AD2-047 C O1
Solar/Wind Harmer
7.636
970941AG2-585 GEN
Solar/Wind Harmer
8.923
964401AG1-302 GEN
Solar/Wind Harmer
6.462
972228AH1-698 GEN2
Adder
2.636
970707AG2-453 GEN
Solar/Wind Harmer
19.862
276897AD1-100 C
Solar/Wind Harmer
20.505
939351AE1-166 GEN
Solar/Wind Harmer
4.19
274676JOLIET 29;8U
Adder
20.899
276893AG1-478 C
Solar/Wind Harmer
0.294
274729ELWOOD EC;1P
Adder
11.581
274730ELWOOD EC;6P
Adder
11.581
274734ELWOOD EC;8P
Adder
11.581
274736ELWOOD EC;9P
Adder
11.581
959141AF2-205 GEN
Solar/Wind Harmer
4.247
943121AE2-341 GEN
Solar/Wind Harmer
10.446
943591AF1-030 GEN
Solar/Wind Harmer
6.964
247642Z2-115 C
Solar/Wind Harmer
0.044
276694AA1-018 GEN2
Solar/Wind Harmer
4.365
274682WAUKEGAN ;7U
Adder
12.367
970289AG2-191 GEN
Solar/Wind Harmer
0.526
970291AG2-192 GEN
Solar/Wind Harmer
0.478
276805AD2-038 GEN
Solar/Wind Harmer
3.503
958821AF2-173 GEN
Solar/Wind Harmer
9.521
270004AE1-209 GEN
Solar/Wind Harmer
3.716
274872LEEDK;1U
Solar/Wind Harmer
0.174
972236AH1-702 GEN2
Adder
1.459
274760LEE CO EC;1U
Adder
6.098
274767LEE CO EC;8U
Adder
6.027
24728705AND G3
Adder
4.093
24728505AND G1
Adder
1.957
270485AE1-090_GEN
Solar/Wind Helper
0.353
942871AE2-306 GEN
Solar/Wind Helper
0.491
270541AE2-072 C
Solar/Wind Helper
1.031
944201AF1-088_MTX
Adder
53.144
957141AF2-008_MTX
Adder
26.572
990497J1323
External Queue
1.5632063150405884
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.805
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.458
MECLTFEXP_MEC->PJM
CLTF
9.34
SIGELTFEXP_SIGE->PJM
CLTF
0.188
LAGNLTFEXP_LAGN->PJM
CLTF
5.535
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.597
TVALTFEXP_TVA->PJM
CLTF
2.211
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.279
NYPJM->LTFIMP_NY
CLTF
1.208
LGEELTFEXP_LGEE->PJM
CLTF
1.678
WECLTFEXP_WEC->PJM
CLTF
2.539
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
AG2-052LTFEXP_AG2-052->PJM
LTF
0.164
AH1-155LTFEXP_AH1-155->PJM
LTF
0.247

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.35 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2472.27
MW Contribution:5.46
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
3.292
971599AH1-298 GEN
50/50
10.333
24729505KEY G4
50/50
6.735
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
11.606
965041AG1-368 GEN
Solar/Wind Harmer
8.426
270071AF1-092 GEN
Solar/Wind Harmer
14.399
965051AG1-369 GEN
Solar/Wind Harmer
3.592
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.088
971771AH1-392 GEN
Solar/Wind Harmer
5.847
971347AH1-153 GEN
Solar/Wind Harmer
8.688
971619AH1-309 GEN
Solar/Wind Harmer
2.601
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.283
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.89
274814UNIV PK N;0U
Adder
3.782
274807UNIV PK N;3U
Adder
3.774
274805UNIV PK N;1U
Adder
3.758
274811UNIV PK N;7U
Adder
3.75
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.292
274776LINCOLN ;7U
Adder
6.292
274777LINCOLN ;8U
Adder
6.292
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.742
960591AF2-350 GEN
Solar/Wind Harmer
5.147
972227AH1-698 GEN1
Adder
1.919
274687WILL CNTY;4U
Adder
20.447
274687WILL CNTY;4U
Adder
20.447
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.401
274675JOLIET 29;7U
Adder
21.601
274728ELWOOD EC;5P
Adder
11.97
274731ELWOOD EC;2P
Adder
11.97
274733ELWOOD EC;3P
Adder
11.97
274735ELWOOD EC;4P
Adder
11.97
970833AG2-524 GEN
Solar/Wind Harmer
5.563
970833AG2-524 GEN
Solar/Wind Harmer
3.709
971611AH1-305 GEN
Solar/Wind Harmer
2.995
274746AC1-111 G10
Adder
4.021
274744AC1-111 GEN8
Adder
4.021
970289AG2-191 GEN
Solar/Wind Harmer
0.942
270594AE1-207 GEN
Solar/Wind Harmer
5.492
276868AE1-113 GEN
Solar/Wind Harmer
0.982
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971177AH1-047 GEN
Solar/Wind Harmer
3.009
971411AH1-196 GEN
Solar/Wind Harmer
7.289
971675AH1-338 GEN
Solar/Wind Harmer
1.894
970115AG2-085 GEN
Solar/Wind Harmer
1.936
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.652
274823ROCKFORD ;21
Adder
13.435
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
4.764
971681AH1-341 GEN
Solar/Wind Harmer
7.643
970615AG2-402 GEN
50/50
4.588
24729405KEY G3
50/50
0.368
24729305KEY G2
50/50
0.361
24729205KEY G1
50/50
0.36
247620Y3-023
50/50
0.463
970611AG2-400 GEN
Solar/Wind Harmer
13.763
970627AG2-408 GEN
Solar/Wind Harmer
4.129
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.42
960971AF2-388 GEN
Solar/Wind Harmer
3.679
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.557
961051AF2-396 GEN
Solar/Wind Harmer
7.705
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.887
965791AG1-447 GEN
Solar/Wind Harmer
5.051
270599AE1-208 GEN
Solar/Wind Harmer
4.993
270031AE2-169
Solar/Wind Harmer
2.996
970321AG2-212 GEN
Solar/Wind Harmer
2.307
274808UNIV PK N;4U
Adder
3.733
274770LINCOLN ;1U
Adder
6.292
274771LINCOLN ;2U
Adder
6.292
274803UNIV PARK;6U
Adder
4.319
274888KELLY CRK;1U
Solar/Wind Harmer
0.302
274887GEN-1.85
Solar/Wind Harmer
0.136
276843GEN-1.7
Solar/Wind Harmer
0.167
958011AF2-095 GEN
Solar/Wind Harmer
7.412
972259AH1-714 GEN
Adder
13.99
274674JOLIET 9 ;6U
Adder
11.217
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
24727005RPMNG1
50/50
3.308
960861AF2-377 GEN
50/50
2.399
970521AG2-332 GEN
50/50
10.806
24639705ELKHART HY
50/50
0.149
965011AG1-365 GEN
Solar/Wind Harmer
13.763
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.262
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.854
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.839
958861AF2-177 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
10.578
270505AE1-170 C O1
Solar/Wind Harmer
6.07
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.97
970245AG2-165 GEN
Solar/Wind Harmer
2.307
970373AG2-245 GEN
Solar/Wind Harmer
11.147
274751CRETE EC ;1U
Adder
6.241
274754CRETE EC ;4U
Adder
6.241
274723RIVER EC ;12
Adder
13.527
274812UNIV PK N;8U
Adder
3.75
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.292
274774LINCOLN ;5U
Adder
6.292
274801UNIV PARK;4U
Adder
4.307
276776AD2-060 GEN
Solar/Wind Harmer
0.537
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.671
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.401
274674JOLIET 9 ;6U
Adder
11.217
274732ELWOOD EC;7P
Adder
11.97
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.288
274745AC1-111 GEN9
Adder
4.021
276691AA1-018 GEN1
Solar/Wind Harmer
0.604
274682WAUKEGAN ;7U
Adder
12.782
970291AG2-192 GEN
Solar/Wind Harmer
0.645
274828WAUKEGAN ;BP
Adder
7.846
270005AE1-210 C O1
Solar/Wind Harmer
1.068
965031AG1-367 GEN
Solar/Wind Harmer
4.929
971573AH1-285 GEN
Solar/Wind Harmer
0.931
958481AF2-142 GEN
Solar/Wind Harmer
7.482
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.675
274695ROCKY RD ;2P
Adder
7.922
274693ROCKY RD ;1P
Adder
7.844
274697ROCKY RD ;3P
Adder
2.152
274696ROCKY RD ;4P
Adder
8.109
274683WAUKEGAN ;8U
Adder
14.968
274683WAUKEGAN ;8U
Adder
12.617
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.776
958491AF2-143 GEN
Solar/Wind Harmer
7.388
970921AG2-575 GEN
Solar/Wind Harmer
4.913
970921AG2-575 GEN
Solar/Wind Harmer
1.638
971613AH1-306 GEN
Solar/Wind Harmer
2.354
274879MINONK ;1U
Solar/Wind Harmer
0.207
942991AE2-321 GEN
Solar/Wind Harmer
5.451
971333AH1-146 GEN
Solar/Wind Harmer
9.71
971335AH1-147 GEN
Solar/Wind Harmer
9.71
960441AF2-335 GEN
Solar/Wind Harmer
4.841
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.652
971343AH1-151 GEN
Solar/Wind Harmer
9.652
970825AG2-519 GEN
Solar/Wind Harmer
5.324
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.689
274764LEE CO EC;5U
Adder
6.319
274765LEE CO EC;6U
Adder
6.319
274762LEE CO EC;3U
Adder
6.304
274763LEE CO EC;4U
Adder
6.245
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.354
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.793
276741O09 GEN1
Solar/Wind Harmer
0.166
276708O09 GEN2
Solar/Wind Harmer
0.166
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
966841AG1-555 GEN
Solar/Wind Harmer
0.525
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.16
960611AF2-352 GEN
Solar/Wind Harmer
1.506
970241AG2-163 GEN
Solar/Wind Harmer
2.545
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.413
276911AD2-131_GEN
Solar/Wind Harmer
0.554
970883AG2-550 GEN
Solar/Wind Harmer
3.912
970885AG2-551 GEN
Solar/Wind Harmer
1.304
945391AF1-204 GEN
Solar/Wind Harmer
4.152
970623AG2-406 GEN
Solar/Wind Harmer
0.681
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.427
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.774
246938BC-WTG3
Solar/Wind Helper
11.083
246937BC-WTG2
Solar/Wind Helper
10.895
270224U2-072_GEN2
Solar/Wind Helper
0.871
270227U2-072_GEN3
Solar/Wind Helper
0.871
270228U2-072_GEN4
Solar/Wind Helper
0.871
270231U2-072_GEN5
Solar/Wind Helper
0.871
270471AD2-092_GEN
Solar/Wind Helper
0.85
253378AE2-206_GEN
Solar/Wind Helper
0.684
276820AF1-078_GEN
Solar/Wind Helper
0.319
241960AC2-195 GEN
Solar/Wind Helper
0.69
24727105RPMNG2
50/50
3.32
970583AG2-370 GEN
50/50
2.809
960851AF2-376 GEN
50/50
2.105
24641605TWIN BRNCH
50/50
0.015
959331AF2-224 GEN
Solar/Wind Harmer
9.634
965021AG1-366 GEN
Solar/Wind Harmer
4.588
970031AG2-029 GEN
Solar/Wind Harmer
5.463
270043AE2-236 GEN
Solar/Wind Harmer
5.191
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.488
971617AH1-308 GEN
Solar/Wind Harmer
5.166
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.805
970349AG2-230 GEN
Solar/Wind Harmer
8.688
24642205MAYFLWER
Adder
0.524
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.307
970517AG2-330 GEN
Solar/Wind Harmer
13.84
274752CRETE EC ;2U
Adder
6.241
274753CRETE EC ;3U
Adder
6.241
274724RIVER EC ;11
Adder
13.364
247604X1-042
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.292
274802UNIV PARK;5U
Adder
4.319
274826FISK ;BP
Adder
8.102
274800UNIV PARK;3U
Adder
4.307
972038AH1-567 GEN2
Adder
0.27
276806AD2-047 C O1
Solar/Wind Harmer
2.917
970941AG2-585 GEN
Solar/Wind Harmer
6.434
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.725
970707AG2-453 GEN
Solar/Wind Harmer
16.709
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.601
276893AG1-478 C
Solar/Wind Harmer
0.201
274730ELWOOD EC;6P
Adder
11.97
274734ELWOOD EC;8P
Adder
11.97
274736ELWOOD EC;9P
Adder
11.97
274729ELWOOD EC;1P
Adder
11.97
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.419
943591AF1-030 GEN
Solar/Wind Harmer
5.599
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.782
970289AG2-191 GEN
Solar/Wind Harmer
0.545
970291AG2-192 GEN
Solar/Wind Harmer
0.496
958821AF2-173 GEN
Solar/Wind Harmer
6.901
270004AE1-209 GEN
Solar/Wind Harmer
1.068
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.18
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.518
274855GSG-6 ;RU
Solar/Wind Harmer
0.178
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.087
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.834
959091AF2-200 GEN
Solar/Wind Harmer
9.652
972236AH1-702 GEN2
Adder
1.508
970571AG2-364 GEN
Solar/Wind Harmer
9.558
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.304
274767LEE CO EC;8U
Adder
6.23
946031AF1-268 GEN
Solar/Wind Harmer
4.492
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.069
276157O29GEN1
Solar/Wind Harmer
0.755
274878BISHOP HL;2U
Solar/Wind Harmer
0.156
942111AE2-223 GEN
Solar/Wind Harmer
1.494
965931AG1-462 GEN
Solar/Wind Harmer
11.522
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.551
959611AF2-252 GEN
Solar/Wind Harmer
1.506
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.156
971993AH1-541 GEN
Solar/Wind Harmer
1.971
276621W2-048 GEN
Solar/Wind Harmer
0.211
276838X2-022 GEN2
Solar/Wind Harmer
0.236
942481AE2-261 GEN
Solar/Wind Harmer
12.085
970193AG2-126 GEN
Solar/Wind Harmer
5.861
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.272
24728505AND G1
Adder
2.043
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.812
970519AG2-331 GEN
Solar/Wind Harmer
8.054
970699AG2-449 GEN
Solar/Wind Harmer
0.774
270485AE1-090_GEN
Solar/Wind Helper
0.323
942871AE2-306 GEN
Solar/Wind Helper
0.443
270541AE2-072 C
Solar/Wind Helper
0.932
962781AG1-127 GEN
Solar/Wind Harmer
4.676
939401AE1-172 GEN
Solar/Wind Harmer
3.674
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.269
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.559
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.477
959081AF2-199 GEN
Solar/Wind Harmer
4.826
971067AG2-660 GEN
Solar/Wind Harmer
1.609
274822ROCKFORD ;11
Adder
13.533
970825AG2-519 GEN
Solar/Wind Harmer
1.705
972235AH1-702 GEN1
Adder
1.734
970819AG2-516 GEN
Solar/Wind Harmer
5.74
970569AG2-363 GEN
Solar/Wind Harmer
14.338
971475AH1-234 GEN
Solar/Wind Harmer
2.315
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.304
274766LEE CO EC;7U
Adder
6.23
276903AD2-071 C
Solar/Wind Harmer
5.249
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.156
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.437
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.624
963741AG1-226 GEN
Solar/Wind Harmer
10.327
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.19
247536S-71 GEN
Solar/Wind Harmer
0.173
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.654
276615X2-022 GEN
Solar/Wind Harmer
0.044
965911AG1-460 GEN
Solar/Wind Harmer
0.808
24728605AND G2
Adder
2.043
970773AG2-487 GEN
Solar/Wind Harmer
0.609
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.215
246936BC-WTG1
Solar/Wind Helper
10.895
270462AD2-086
Solar/Wind Helper
3.714
270223U2-072_GEN1
Solar/Wind Helper
0.871
270578AF1-285 GEN2
Solar/Wind Helper
0.59
270391AF1-285 GEN3
Solar/Wind Helper
0.59
247522W1-056 GEN
Solar/Wind Helper
1.168
960841AF2-375 GEN
Solar/Wind Helper
1.175
270349AD2-093_GEN
Solar/Wind Helper
0.85
971549AH1-272 GEN
Solar/Wind Harmer
9.793
961011AF2-392 GEN
Solar/Wind Harmer
2.754
957751AF2-069 GEN
Solar/Wind Harmer
0.154
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.828
941731AE2-173 GEN
Solar/Wind Harmer
3.831
946321AF1-296 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.949
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.156
276848AB2-070 GEN3
Solar/Wind Harmer
0.155
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.279
971029AG2-637 GEN
Solar/Wind Harmer
5.242
971673AH1-337 GEN
Solar/Wind Harmer
2.175
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.613
270317AD1-130_GEN
Solar/Wind Helper
4.113
966831AG1-554 GEN
Solar/Wind Helper
0.876
270284AF1-227 GEN1
Solar/Wind Helper
1.876
270286AF1-227 GEN2
Solar/Wind Helper
0.688
270287AF1-227 GEN3
Solar/Wind Helper
0.688
270499AE1-146 GEN
Solar/Wind Helper
1.952
945641AF1-229 GEN
Solar/Wind Helper
0.937
944201AF1-088_MTX
Adder
55.165
957141AF2-008_MTX
Adder
22.101
990497J1323
External Queue
1.5914489030838013
990792J1392
External Queue
5.474584102630615
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.309
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.744
MECLTFEXP_MEC->PJM
CLTF
9.656
SIGELTFEXP_SIGE->PJM
CLTF
0.197
LAGNLTFEXP_LAGN->PJM
CLTF
5.694
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.439
TVALTFEXP_TVA->PJM
CLTF
2.27
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.944
NYPJM->LTFIMP_NY
CLTF
1.265
LGEELTFEXP_LGEE->PJM
CLTF
1.782
WECLTFEXP_WEC->PJM
CLTF
2.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.52 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2158.0
MW Contribution:30.01
Bus #Bus NameTypeMW Contribution
24727105RPMNG2
50/50
3.133
970583AG2-370 GEN
50/50
2.348
959331AF2-224 GEN
Solar/Wind Harmer
17.622
965021AG1-366 GEN
Solar/Wind Harmer
4.098
24727205RPMNG3
50/50
3.107
971599AH1-298 GEN
50/50
8.317
963791AG1-232 GEN
Solar/Wind Harmer
14.105
965041AG1-368 GEN
Solar/Wind Harmer
10.094
270071AF1-092 GEN
Solar/Wind Harmer
13.076
965051AG1-369 GEN
Solar/Wind Harmer
4.177
24729505KEY G4
Adder
5.083
270024AE2-089 GEN
Solar/Wind Harmer
3.393
958711AF2-162 GEN
Solar/Wind Harmer
0.725
965101AG1-375 GEN
Solar/Wind Harmer
6.942
945581AF1-223 GEN
Solar/Wind Harmer
2.958
971771AH1-392 GEN
Solar/Wind Harmer
5.726
971347AH1-153 GEN
Solar/Wind Harmer
9.292
971769AH1-391 GEN
Solar/Wind Harmer
6.078
944161AF1-084 GEN
Solar/Wind Harmer
1.333
960681AF2-359 GEN
Solar/Wind Harmer
2.239
270536AF1-215 GEN2
Solar/Wind Harmer
2.572
274814UNIV PK N;0U
Adder
2.846
274807UNIV PK N;3U
Adder
2.84
274805UNIV PK N;1U
Adder
2.827
274811UNIV PK N;7U
Adder
2.821
274775LINCOLN ;6U
Adder
3.455
274776LINCOLN ;7U
Adder
3.455
274777LINCOLN ;8U
Adder
3.455
972037AH1-567 GEN1
Adder
0.102
274827FISK ;RP
Adder
4.315
958391AF2-133 GEN
Solar/Wind Harmer
5.037
960591AF2-350 GEN
Solar/Wind Harmer
5.542
965461AG1-414 GEN
Solar/Wind Harmer
1.256
970289AG2-191 GEN
Solar/Wind Harmer
1.053
972227AH1-698 GEN1
Adder
1.44
274687WILL CNTY;4U
Adder
15.362
274687WILL CNTY;4U
Adder
15.362
274675JOLIET 29;7U
Adder
16.827
274675JOLIET 29;7U
Adder
16.226
270594AE1-207 GEN
Solar/Wind Harmer
8.053
274731ELWOOD EC;2P
Adder
8.992
274733ELWOOD EC;3P
Adder
8.992
274735ELWOOD EC;4P
Adder
8.992
274728ELWOOD EC;5P
Adder
8.993
970833AG2-524 GEN
Solar/Wind Harmer
4.75
970833AG2-524 GEN
Solar/Wind Harmer
2.209
970115AG2-085 GEN
Solar/Wind Harmer
2.173
274746AC1-111 G10
Adder
3.019
274744AC1-111 GEN8
Adder
3.019
24690905MDL-1G C
Solar/Wind Harmer
4.255
270180AB1-006 GEN1
Solar/Wind Harmer
3.812
946581AF1-322 GEN
Solar/Wind Harmer
5.422
24691005MDL-2G C
Solar/Wind Harmer
1.96
24697605MDL-3G C
Solar/Wind Harmer
1.954
24697905MDL-4G C
Solar/Wind Harmer
1.216
270181AB1-006 GEN2
Solar/Wind Harmer
0.379
274823ROCKFORD ;21
Adder
10.12
957201AF2-014 GEN
Solar/Wind Helper
8.977
270317AD1-130_GEN
Solar/Wind Helper
4.715
966831AG1-554 GEN
Solar/Wind Helper
0.991
270284AF1-227 GEN1
Solar/Wind Helper
2.381
270286AF1-227 GEN2
Solar/Wind Helper
0.873
270287AF1-227 GEN3
Solar/Wind Helper
0.873
270499AE1-146 GEN
Solar/Wind Helper
2.27
945641AF1-229 GEN
Solar/Wind Helper
1.091
253383AE2-342_GEN
Solar/Wind Helper
0.4
970615AG2-402 GEN
50/50
4.098
970611AG2-400 GEN
Solar/Wind Harmer
17.622
942221AE2-234 GEN
Solar/Wind Harmer
0.583
247620Y3-023
Adder
0.343
944541AF1-119 GEN
Solar/Wind Harmer
3
960971AF2-388 GEN
Solar/Wind Harmer
7.829
270216AD2-079_GEN
Solar/Wind Harmer
0.412
960981AF2-389 GEN
Solar/Wind Harmer
0.958
957891AF2-083 GEN
Solar/Wind Harmer
2.135
961051AF2-396 GEN
Solar/Wind Harmer
9.957
961051AF2-396 GEN
Solar/Wind Harmer
4.631
270599AE1-208 GEN
Solar/Wind Harmer
5.045
270031AE2-169
Solar/Wind Harmer
5.045
270526AF1-158 GEN
Solar/Wind Harmer
2.787
24441505OLIV SLR
Solar/Wind Harmer
0.081
965681AG1-436 GEN
Solar/Wind Harmer
7.408
965791AG1-447 GEN
Solar/Wind Harmer
3.79
274808UNIV PK N;4U
Adder
2.809
970321AG2-212 GEN
Solar/Wind Harmer
10.037
274770LINCOLN ;1U
Adder
3.455
274771LINCOLN ;2U
Adder
3.455
274803UNIV PARK;6U
Adder
3.247
274888KELLY CRK;1U
Solar/Wind Harmer
3.272
274887GEN-1.85
Solar/Wind Harmer
2.954
276843GEN-1.7
Solar/Wind Harmer
0.318
958011AF2-095 GEN
Solar/Wind Harmer
7.98
972259AH1-714 GEN
Adder
10.492
274674JOLIET 9 ;6U
Adder
8.426
274847GR RIDGE ;BU
Solar/Wind Harmer
2.75
960441AF2-335 GEN
Solar/Wind Harmer
5.431
945421AF1-207 GEN
Solar/Wind Harmer
7.58
957841AF2-078 GEN
Solar/Wind Harmer
3.262
970825AG2-519 GEN
Solar/Wind Harmer
5.68
958481AF2-142 GEN
Solar/Wind Harmer
8.069
274861TOP CROP ;1U
Solar/Wind Harmer
3.259
274862TOP CROP ;2U
Solar/Wind Harmer
2.721
971573AH1-285 GEN
Solar/Wind Harmer
4.623
274696ROCKY RD ;4P
Adder
6.094
274695ROCKY RD ;2P
Adder
5.954
274693ROCKY RD ;1P
Adder
5.895
274697ROCKY RD ;3P
Adder
1.617
274683WAUKEGAN ;8U
Adder
11.254
274683WAUKEGAN ;8U
Adder
9.487
958491AF2-143 GEN
Solar/Wind Harmer
7.973
962691AG1-118 GEN
Solar/Wind Harmer
15.922
970921AG2-575 GEN
Solar/Wind Harmer
5.295
970921AG2-575 GEN
Solar/Wind Harmer
1.231
247621Y3-024
Adder
0.124
274764LEE CO EC;5U
Adder
4.766
274765LEE CO EC;6U
Adder
4.766
274762LEE CO EC;3U
Adder
4.754
274763LEE CO EC;4U
Adder
4.71
972267AH1-718 GEN
Adder
2.108
246938BC-WTG3
Solar/Wind Helper
11.551
246937BC-WTG2
Solar/Wind Helper
11.356
270224U2-072_GEN2
Solar/Wind Helper
1.016
270227U2-072_GEN3
Solar/Wind Helper
1.016
270228U2-072_GEN4
Solar/Wind Helper
1.016
270231U2-072_GEN5
Solar/Wind Helper
1.016
270471AD2-092_GEN
Solar/Wind Helper
1.192
253378AE2-206_GEN
Solar/Wind Helper
0.835
276820AF1-078_GEN
Solar/Wind Helper
0.39
241960AC2-195 GEN
Solar/Wind Helper
0.828
24727005RPMNG1
50/50
3.122
965011AG1-365 GEN
Solar/Wind Harmer
17.622
270063AE2-323 C
Solar/Wind Harmer
1.892
247521TR3_G114
Solar/Wind Harmer
2.813
270246TR4_N_V150
Solar/Wind Harmer
0.712
944231AF1-091 GEN
Solar/Wind Harmer
3.029
965651AG1-433 GEN
Solar/Wind Harmer
3.914
24639705ELKHART HY
Adder
0.11
24695305TIMB G C
Solar/Wind Harmer
3.924
958861AF2-177 GEN
Solar/Wind Harmer
7.588
945371AF1-202 GEN
Solar/Wind Harmer
4.55
945111AF1-176 GEN
Solar/Wind Harmer
11.565
270505AE1-170 C O1
Solar/Wind Harmer
9.4
270449AD2-020 GEN
Solar/Wind Harmer
1.724
943021AE2-325 GEN
Solar/Wind Harmer
2.24
970373AG2-245 GEN
Solar/Wind Harmer
12.06
274751CRETE EC ;1U
Adder
2.789
274754CRETE EC ;4U
Adder
2.789
274723RIVER EC ;12
Adder
10.178
270055AF2-134 C O1
Solar/Wind Harmer
1.715
274812UNIV PK N;8U
Adder
2.821
276164X3-005 C
Solar/Wind Harmer
0.395
970245AG2-165 GEN
Solar/Wind Harmer
10.037
958381AF2-132 GEN
Solar/Wind Harmer
5.071
964861AG1-349 GEN
Solar/Wind Harmer
4.388
971917AH1-482 GEN
Solar/Wind Harmer
5.063
972207SS24-0001
Solar/Wind Harmer
12.284
274773LINCOLN ;4U
Adder
3.455
274774LINCOLN ;5U
Adder
3.455
274801UNIV PARK;4U
Adder
3.236
276776AD2-060 GEN
Solar/Wind Harmer
0.234
970291AG2-192 GEN
Solar/Wind Harmer
0.72
270005AE1-210 C O1
Solar/Wind Harmer
3.027
965031AG1-367 GEN
Solar/Wind Harmer
5.538
940581AE2-045 GEN
Solar/Wind Harmer
5.6
971605AH1-302 GEN
Solar/Wind Harmer
4.789
274676JOLIET 29;8U
Adder
16.827
941551AE2-152 GEN
Solar/Wind Harmer
2.486
270032AE2-172
Solar/Wind Harmer
2.548
274674JOLIET 9 ;6U
Adder
8.426
274732ELWOOD EC;7P
Adder
8.993
274871GR RIDGE ;2U
Solar/Wind Harmer
4.181
274745AC1-111 GEN9
Adder
3.019
970825AG2-519 GEN
Solar/Wind Harmer
1.267
276691AA1-018 GEN1
Solar/Wind Harmer
0.25
274682WAUKEGAN ;7U
Adder
9.61
274828WAUKEGAN ;BP
Adder
5.899
24791305MDL-5G
Solar/Wind Harmer
1.278
276901AD2-066 C O1
Solar/Wind Harmer
1.861
960751AF2-366 GEN
Solar/Wind Harmer
1.519
962781AG1-127 GEN
Solar/Wind Harmer
5.036
274822ROCKFORD ;11
Adder
10.194
972235AH1-702 GEN1
Adder
1.306
274761LEE CO EC;2U
Adder
4.754
274766LEE CO EC;7U
Adder
4.698
246936BC-WTG1
Solar/Wind Helper
11.356
270462AD2-086
Solar/Wind Helper
4.257
270223U2-072_GEN1
Solar/Wind Helper
1.016
270578AF1-285 GEN2
Solar/Wind Helper
0.688
270391AF1-285 GEN3
Solar/Wind Helper
0.688
247522W1-056 GEN
Solar/Wind Helper
1.336
960841AF2-375 GEN
Solar/Wind Helper
1.368
270349AD2-093_GEN
Solar/Wind Helper
1.192
241840AF1-064_GEN
Solar/Wind Helper
0.485
241807AE2-176_GEN
Solar/Wind Helper
0.7
939401AE1-172 GEN
Solar/Wind Harmer
2.473
970031AG2-029 GEN
Solar/Wind Harmer
30.007
270043AE2-236 GEN
Solar/Wind Harmer
5.199
270191TR4_S_V150
Solar/Wind Harmer
2.51
270247TR4_N_V136
Solar/Wind Harmer
0.712
944531AF1-118 GEN
Solar/Wind Harmer
28.273
971617AH1-308 GEN
Solar/Wind Harmer
4.203
247643Z2-116 C
Solar/Wind Harmer
0.047
945111AF1-176 GEN
Solar/Wind Harmer
3.665
24642205MAYFLWER
Adder
0.397
970349AG2-230 GEN
Solar/Wind Harmer
9.292
24441205WTRV SLR C
Solar/Wind Harmer
0.078
972231SS25-0005
Solar/Wind Harmer
5.415
972181SS23-001
Solar/Wind Harmer
3.384
274752CRETE EC ;2U
Adder
2.789
274753CRETE EC ;3U
Adder
2.789
274724RIVER EC ;11
Adder
10.053
270535AF1-215 GEN1
Solar/Wind Harmer
2.572
970513AG2-328 GEN
Solar/Wind Harmer
10.037
970517AG2-330 GEN
Solar/Wind Harmer
9.103
247642Z2-115 C
Solar/Wind Harmer
0.036
964401AG1-302 GEN
Solar/Wind Harmer
5.071
274772LINCOLN ;3U
Adder
3.455
274802UNIV PARK;5U
Adder
3.247
274826FISK ;BP
Adder
6.089
274800UNIV PARK;3U
Adder
3.236
972038AH1-567 GEN2
Adder
0.203
276772AC2-154 GEN
Solar/Wind Harmer
1.545
276806AD2-047 C O1
Solar/Wind Harmer
5.929
970941AG2-585 GEN
Solar/Wind Harmer
6.927
970289AG2-191 GEN
Solar/Wind Harmer
0.425
970291AG2-192 GEN
Solar/Wind Harmer
0.386
958821AF2-173 GEN
Solar/Wind Harmer
7.753
270004AE1-209 GEN
Solar/Wind Harmer
3.027
247604X1-042
Adder
0.231
959141AF2-205 GEN
Solar/Wind Harmer
3.34
972228AH1-698 GEN2
Adder
2.046
970707AG2-453 GEN
Solar/Wind Harmer
15.375
274676JOLIET 29;8U
Adder
16.226
276897AD1-100 C
Solar/Wind Harmer
15.905
939351AE1-166 GEN
Solar/Wind Harmer
3.25
276893AG1-478 C
Solar/Wind Harmer
0.229
274729ELWOOD EC;1P
Adder
8.992
274730ELWOOD EC;6P
Adder
8.993
274734ELWOOD EC;8P
Adder
8.993
274736ELWOOD EC;9P
Adder
8.993
943121AE2-341 GEN
Solar/Wind Harmer
8.102
943591AF1-030 GEN
Solar/Wind Harmer
5.401
276694AA1-018 GEN2
Solar/Wind Harmer
3.395
274682WAUKEGAN ;7U
Adder
9.61
276805AD2-038 GEN
Solar/Wind Harmer
2.727
24755605MDL-5G
Solar/Wind Harmer
1.278
970781AG2-491 GEN
Solar/Wind Harmer
5.299
972236AH1-702 GEN2
Adder
1.136
274760LEE CO EC;1U
Adder
4.754
274767LEE CO EC;8U
Adder
4.698
270485AE1-090_GEN
Solar/Wind Helper
0.37
942871AE2-306 GEN
Solar/Wind Helper
0.516
270541AE2-072 C
Solar/Wind Helper
1.202
990497J1323
External Queue
1.411980390548706
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.78
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.457
MECLTFEXP_MEC->PJM
CLTF
7.38
SIGELTFEXP_SIGE->PJM
CLTF
0.152
LAGNLTFEXP_LAGN->PJM
CLTF
4.78
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.617
TVALTFEXP_TVA->PJM
CLTF
1.99
CPLELTFEXP_CPLE->PJM
CLTF
0.236
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.907
NYPJM->LTFIMP_NY
CLTF
0.985
LGEELTFEXP_LGEE->PJM
CLTF
1.351
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.129
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.54 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2064.97
MW Contribution:29.92
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
3.153
971599AH1-298 GEN
50/50
7.987
963791AG1-232 GEN
Solar/Wind Harmer
14.176
965041AG1-368 GEN
Solar/Wind Harmer
10.32
965051AG1-369 GEN
Solar/Wind Harmer
4.349
270071AF1-092 GEN
Solar/Wind Harmer
12.942
24729505KEY G4
Adder
4.903
270024AE2-089 GEN
Solar/Wind Harmer
3.42
958711AF2-162 GEN
Solar/Wind Harmer
0.701
965101AG1-375 GEN
Solar/Wind Harmer
6.724
945581AF1-223 GEN
Solar/Wind Harmer
2.871
971771AH1-392 GEN
Solar/Wind Harmer
5.677
971347AH1-153 GEN
Solar/Wind Harmer
9.093
971769AH1-391 GEN
Solar/Wind Harmer
6.044
944161AF1-084 GEN
Solar/Wind Harmer
1.326
960681AF2-359 GEN
Solar/Wind Harmer
2.23
270536AF1-215 GEN2
Solar/Wind Harmer
2.65
958391AF2-133 GEN
Solar/Wind Harmer
5.26
965461AG1-414 GEN
Solar/Wind Harmer
1.287
970289AG2-191 GEN
Solar/Wind Harmer
1.078
24690905MDL-1G C
Solar/Wind Harmer
4.549
270180AB1-006 GEN1
Solar/Wind Harmer
4.075
946581AF1-322 GEN
Solar/Wind Harmer
5.797
24691005MDL-2G C
Solar/Wind Harmer
2.096
24697605MDL-3G C
Solar/Wind Harmer
2.089
24697905MDL-4G C
Solar/Wind Harmer
1.301
270181AB1-006 GEN2
Solar/Wind Harmer
0.405
274814UNIV PK N;0U
Adder
2.833
274807UNIV PK N;3U
Adder
2.827
274805UNIV PK N;1U
Adder
2.815
274811UNIV PK N;7U
Adder
2.809
270594AE1-207 GEN
Solar/Wind Harmer
8.184
972037AH1-567 GEN1
Adder
0.101
274827FISK ;RP
Adder
4.292
274775LINCOLN ;6U
Adder
3.422
970615AG2-402 GEN
50/50
4.108
970611AG2-400 GEN
Solar/Wind Harmer
17.665
942221AE2-234 GEN
Solar/Wind Harmer
0.58
247620Y3-023
Adder
0.341
944541AF1-119 GEN
Solar/Wind Harmer
2.902
960971AF2-388 GEN
Solar/Wind Harmer
7.574
270216AD2-079_GEN
Solar/Wind Harmer
0.408
960981AF2-389 GEN
Solar/Wind Harmer
0.951
957891AF2-083 GEN
Solar/Wind Harmer
2.119
961051AF2-396 GEN
Solar/Wind Harmer
9.895
961051AF2-396 GEN
Solar/Wind Harmer
4.602
270599AE1-208 GEN
Solar/Wind Harmer
4.984
270031AE2-169
Solar/Wind Harmer
4.984
270526AF1-158 GEN
Solar/Wind Harmer
2.77
24441505OLIV SLR
Solar/Wind Harmer
0.081
965681AG1-436 GEN
Solar/Wind Harmer
7.379
965791AG1-447 GEN
Solar/Wind Harmer
3.775
945421AF1-207 GEN
Solar/Wind Harmer
8.076
957841AF2-078 GEN
Solar/Wind Harmer
3.475
970321AG2-212 GEN
Solar/Wind Harmer
10.209
274808UNIV PK N;4U
Adder
2.797
274803UNIV PARK;6U
Adder
3.231
274770LINCOLN ;1U
Adder
3.422
274771LINCOLN ;2U
Adder
3.422
274888KELLY CRK;1U
Solar/Wind Harmer
3.256
274887GEN-1.85
Solar/Wind Harmer
2.939
276843GEN-1.7
Solar/Wind Harmer
0.316
958011AF2-095 GEN
Solar/Wind Harmer
7.941
966841AG1-555 GEN
Solar/Wind Harmer
1.376
972259AH1-714 GEN
Adder
10.427
274674JOLIET 9 ;6U
Adder
8.385
24727005RPMNG1
50/50
3.169
960861AF2-377 GEN
50/50
2.027
965011AG1-365 GEN
Solar/Wind Harmer
17.665
247521TR3_G114
Solar/Wind Harmer
2.928
270246TR4_N_V150
Solar/Wind Harmer
0.741
270063AE2-323 C
Solar/Wind Harmer
1.881
944231AF1-091 GEN
Solar/Wind Harmer
3.082
24695305TIMB G C
Solar/Wind Harmer
4.125
24639705ELKHART HY
Adder
0.109
965651AG1-433 GEN
Solar/Wind Harmer
3.787
958861AF2-177 GEN
Solar/Wind Harmer
7.349
945111AF1-176 GEN
Solar/Wind Harmer
11.488
945371AF1-202 GEN
Solar/Wind Harmer
4.417
270505AE1-170 C O1
Solar/Wind Harmer
9.327
270449AD2-020 GEN
Solar/Wind Harmer
1.713
943021AE2-325 GEN
Solar/Wind Harmer
2.226
970373AG2-245 GEN
Solar/Wind Harmer
12.302
270055AF2-134 C O1
Solar/Wind Harmer
1.766
958381AF2-132 GEN
Solar/Wind Harmer
5.27
964861AG1-349 GEN
Solar/Wind Harmer
4.565
971917AH1-482 GEN
Solar/Wind Harmer
5.268
940581AE2-045 GEN
Solar/Wind Harmer
5.894
971605AH1-302 GEN
Solar/Wind Harmer
5.04
970245AG2-165 GEN
Solar/Wind Harmer
10.209
274751CRETE EC ;1U
Adder
2.778
274754CRETE EC ;4U
Adder
2.778
970291AG2-192 GEN
Solar/Wind Harmer
0.738
24791305MDL-5G
Solar/Wind Harmer
1.366
274723RIVER EC ;12
Adder
10.121
274812UNIV PK N;8U
Adder
2.809
276164X3-005 C
Solar/Wind Harmer
0.393
270032AE2-172
Solar/Wind Harmer
2.59
274801UNIV PARK;4U
Adder
3.22
972207SS24-0001
Solar/Wind Harmer
12.167
274773LINCOLN ;4U
Adder
3.422
274774LINCOLN ;5U
Adder
3.422
276776AD2-060 GEN
Solar/Wind Harmer
0.233
24385905FR-11G C
Solar/Wind Harmer
4.56
24387305FR-4G C
Solar/Wind Harmer
2.788
941551AE2-152 GEN
Solar/Wind Harmer
2.475
274676JOLIET 29;8U
Adder
16.739
274732ELWOOD EC;7P
Adder
8.953
274674JOLIET 9 ;6U
Adder
8.385
970333AG2-219 GEN
Solar/Wind Harmer
17.067
274871GR RIDGE ;2U
Solar/Wind Harmer
4.162
270005AE1-210 C O1
Solar/Wind Harmer
2.957
965031AG1-367 GEN
Solar/Wind Harmer
5.411
24727105RPMNG2
50/50
3.18
970583AG2-370 GEN
50/50
2.4
959331AF2-224 GEN
Solar/Wind Harmer
17.665
965021AG1-366 GEN
Solar/Wind Harmer
4.108
970031AG2-029 GEN
Solar/Wind Harmer
29.917
270043AE2-236 GEN
Solar/Wind Harmer
5.102
270191TR4_S_V150
Solar/Wind Harmer
2.613
270247TR4_N_V136
Solar/Wind Harmer
0.741
944531AF1-118 GEN
Solar/Wind Harmer
27.247
971617AH1-308 GEN
Solar/Wind Harmer
4.236
247643Z2-116 C
Solar/Wind Harmer
0.047
945111AF1-176 GEN
Solar/Wind Harmer
3.641
24642205MAYFLWER
Adder
0.394
970349AG2-230 GEN
Solar/Wind Harmer
9.093
270535AF1-215 GEN1
Solar/Wind Harmer
2.65
964401AG1-302 GEN
Solar/Wind Harmer
5.27
959141AF2-205 GEN
Solar/Wind Harmer
3.5
247642Z2-115 C
Solar/Wind Harmer
0.037
24441205WTRV SLR C
Solar/Wind Harmer
0.077
970513AG2-328 GEN
Solar/Wind Harmer
10.209
970517AG2-330 GEN
Solar/Wind Harmer
9.26
972231SS25-0005
Solar/Wind Harmer
5.394
972181SS23-001
Solar/Wind Harmer
3.371
274752CRETE EC ;2U
Adder
2.778
274753CRETE EC ;3U
Adder
2.778
970289AG2-191 GEN
Solar/Wind Harmer
0.436
970291AG2-192 GEN
Solar/Wind Harmer
0.396
24755605MDL-5G
Solar/Wind Harmer
1.366
970781AG2-491 GEN
Solar/Wind Harmer
5.665
274724RIVER EC ;11
Adder
9.996
274802UNIV PARK;5U
Adder
3.231
274826FISK ;BP
Adder
6.057
247604X1-042
Adder
0.23
274800UNIV PARK;3U
Adder
3.22
972038AH1-567 GEN2
Adder
0.202
274772LINCOLN ;3U
Adder
3.422
276772AC2-154 GEN
Solar/Wind Harmer
1.538
276806AD2-047 C O1
Solar/Wind Harmer
5.9
970941AG2-585 GEN
Solar/Wind Harmer
6.893
972228AH1-698 GEN2
Adder
2.035
276897AD1-100 C
Solar/Wind Harmer
15.84
939351AE1-166 GEN
Solar/Wind Harmer
3.237
274676JOLIET 29;8U
Adder
16.141
276893AG1-478 C
Solar/Wind Harmer
0.228
970707AG2-453 GEN
Solar/Wind Harmer
15.256
274730ELWOOD EC;6P
Adder
8.953
274734ELWOOD EC;8P
Adder
8.953
274736ELWOOD EC;9P
Adder
8.953
274729ELWOOD EC;1P
Adder
8.952
970243AG2-164 GEN
Solar/Wind Harmer
13.964
970519AG2-331 GEN
Solar/Wind Harmer
9.382
970699AG2-449 GEN
Solar/Wind Harmer
6.206
958821AF2-173 GEN
Solar/Wind Harmer
7.576
270004AE1-209 GEN
Solar/Wind Harmer
2.957
274745AC1-111 GEN9
Adder
3.002
276691AA1-018 GEN1
Solar/Wind Harmer
0.25
274682WAUKEGAN ;7U
Adder
9.561
274828WAUKEGAN ;BP
Adder
5.87
274822ROCKFORD ;11
Adder
10.153
972235AH1-702 GEN1
Adder
1.301
274761LEE CO EC;2U
Adder
4.74
274766LEE CO EC;7U
Adder
4.685
970091AG2-072 GEN
Adder
38.031
246936BC-WTG1
Solar/Wind Helper
11.192
270462AD2-086
Solar/Wind Helper
3.566
270223U2-072_GEN1
Solar/Wind Helper
0.82
270578AF1-285 GEN2
Solar/Wind Helper
0.555
270391AF1-285 GEN3
Solar/Wind Helper
0.555
247522W1-056 GEN
Solar/Wind Helper
1.172
960841AF2-375 GEN
Solar/Wind Helper
1.199
943121AE2-341 GEN
Solar/Wind Harmer
8.051
943591AF1-030 GEN
Solar/Wind Harmer
5.368
276694AA1-018 GEN2
Solar/Wind Harmer
3.387
274682WAUKEGAN ;7U
Adder
9.561
972236AH1-702 GEN2
Adder
1.131
274760LEE CO EC;1U
Adder
4.74
274767LEE CO EC;8U
Adder
4.685
270485AE1-090_GEN
Solar/Wind Helper
0.31
942871AE2-306 GEN
Solar/Wind Helper
0.417
270541AE2-072 C
Solar/Wind Helper
1.028
274776LINCOLN ;7U
Adder
3.422
274777LINCOLN ;8U
Adder
3.422
960591AF2-350 GEN
Solar/Wind Harmer
5.515
972227AH1-698 GEN1
Adder
1.433
24386205FR-12G C
Solar/Wind Harmer
2.351
24386405FR-21G C
Solar/Wind Harmer
2.359
24386605FR-22G C
Solar/Wind Harmer
2.359
24387005FR-3G C
Solar/Wind Harmer
2.17
274687WILL CNTY;4U
Adder
15.283
274687WILL CNTY;4U
Adder
15.283
274675JOLIET 29;7U
Adder
16.739
274675JOLIET 29;7U
Adder
16.141
274728ELWOOD EC;5P
Adder
8.953
274731ELWOOD EC;2P
Adder
8.952
274733ELWOOD EC;3P
Adder
8.952
274735ELWOOD EC;4P
Adder
8.952
970833AG2-524 GEN
Solar/Wind Harmer
4.728
970833AG2-524 GEN
Solar/Wind Harmer
2.199
970115AG2-085 GEN
Solar/Wind Harmer
2.152
274746AC1-111 G10
Adder
3.002
274744AC1-111 GEN8
Adder
3.002
274823ROCKFORD ;21
Adder
10.079
957201AF2-014 GEN
Solar/Wind Helper
8.848
270317AD1-130_GEN
Solar/Wind Helper
3.949
966831AG1-554 GEN
Solar/Wind Helper
0.871
270499AE1-146 GEN
Solar/Wind Helper
1.994
270284AF1-227 GEN1
Solar/Wind Helper
1.579
270286AF1-227 GEN2
Solar/Wind Helper
0.579
270287AF1-227 GEN3
Solar/Wind Helper
0.579
945641AF1-229 GEN
Solar/Wind Helper
0.93
970239AG2-162 GEN
Solar/Wind Harmer
5.948
274847GR RIDGE ;BU
Solar/Wind Harmer
2.738
960441AF2-335 GEN
Solar/Wind Harmer
5.38
274696ROCKY RD ;4P
Adder
6.063
274695ROCKY RD ;2P
Adder
5.923
274693ROCKY RD ;1P
Adder
5.865
274697ROCKY RD ;3P
Adder
1.609
274683WAUKEGAN ;8U
Adder
11.198
274683WAUKEGAN ;8U
Adder
9.439
247621Y3-024
Adder
0.126
274764LEE CO EC;5U
Adder
4.752
274765LEE CO EC;6U
Adder
4.752
274762LEE CO EC;3U
Adder
4.74
274763LEE CO EC;4U
Adder
4.696
972267AH1-718 GEN
Adder
2.103
246938BC-WTG3
Solar/Wind Helper
11.385
246937BC-WTG2
Solar/Wind Helper
11.192
270224U2-072_GEN2
Solar/Wind Helper
0.82
270227U2-072_GEN3
Solar/Wind Helper
0.82
270228U2-072_GEN4
Solar/Wind Helper
0.82
270231U2-072_GEN5
Solar/Wind Helper
0.82
253378AE2-206_GEN
Solar/Wind Helper
0.673
276820AF1-078_GEN
Solar/Wind Helper
0.314
958481AF2-142 GEN
Solar/Wind Harmer
0.425
944201AF1-088_MTX
Adder
52.894
957141AF2-008_MTX
Adder
14.744
990497J1323
External Queue
1.3854676485061646
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.148
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.322
MECLTFEXP_MEC->PJM
CLTF
7.361
SIGELTFEXP_SIGE->PJM
CLTF
0.152
LAGNLTFEXP_LAGN->PJM
CLTF
4.337
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.169
TVALTFEXP_TVA->PJM
CLTF
1.701
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.068
NYPJM->LTFIMP_NY
CLTF
0.945
LGEELTFEXP_LGEE->PJM
CLTF
1.101
WECLTFEXP_WEC->PJM
CLTF
1.969
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.075
AG2-052LTFEXP_AG2-052->PJM
LTF
0.13
AH1-155LTFEXP_AH1-155->PJM
LTF
0.196

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7443_05DUMONT 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7443_05DUMONT 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.16 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3597.55
MW Contribution:49.52
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.233
24729505KEY G4
50/50
13.359
24727205RPMNG3
50/50
1.299
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
28.446
958711AF2-162 GEN
Solar/Wind Harmer
1.798
965101AG1-375 GEN
Solar/Wind Harmer
17.237
945581AF1-223 GEN
Solar/Wind Harmer
7.354
963791AG1-232 GEN
Solar/Wind Harmer
21.417
965041AG1-368 GEN
Solar/Wind Harmer
15.714
965051AG1-369 GEN
Solar/Wind Harmer
7.257
270024AE2-089 GEN
Solar/Wind Harmer
6.437
970115AG2-085 GEN
Solar/Wind Harmer
5.221
971771AH1-392 GEN
Solar/Wind Harmer
11.61
944161AF1-084 GEN
Solar/Wind Harmer
2.8
270594AE1-207 GEN
Solar/Wind Harmer
18.528
971347AH1-153 GEN
Solar/Wind Harmer
18.754
965461AG1-414 GEN
Solar/Wind Harmer
2.831
970289AG2-191 GEN
Solar/Wind Harmer
2.373
270240V3-007_GEN2
Solar/Wind Harmer
7.66
971769AH1-391 GEN
Solar/Wind Harmer
12.335
961761AG1-017 GEN
Solar/Wind Harmer
0.526
960681AF2-359 GEN
Solar/Wind Harmer
4.523
24725505WLD G2 C
Solar/Wind Harmer
4.748
24699105WLD G1 C
Solar/Wind Harmer
4.693
957201AF2-014 GEN
Solar/Wind Harmer
5.389
270435AC2-044 GEN
Solar/Wind Harmer
2.377
971549AH1-272 GEN
Solar/Wind Harmer
21.937
247607V1-011 GEN
Solar/Wind Harmer
4.688
270536AF1-215 GEN2
Solar/Wind Harmer
5.134
274814UNIV PK N;0U
Adder
5.591
274807UNIV PK N;3U
Adder
5.579
274805UNIV PK N;1U
Adder
5.554
274811UNIV PK N;7U
Adder
5.542
958391AF2-133 GEN
Solar/Wind Harmer
9.99
972037AH1-567 GEN1
Adder
0.2
274827FISK ;RP
Adder
8.463
274775LINCOLN ;6U
Adder
6.747
274776LINCOLN ;7U
Adder
6.747
274777LINCOLN ;8U
Adder
6.747
960591AF2-350 GEN
Solar/Wind Harmer
10.866
972227AH1-698 GEN1
Adder
2.823
274687WILL CNTY;4U
Adder
30.105
274687WILL CNTY;4U
Adder
30.105
274675JOLIET 29;7U
Adder
32.967
274675JOLIET 29;7U
Adder
31.79
274728ELWOOD EC;5P
Adder
17.624
274731ELWOOD EC;2P
Adder
17.623
274733ELWOOD EC;3P
Adder
17.623
274735ELWOOD EC;4P
Adder
17.623
270543AE2-219 C
Solar/Wind Harmer
5.485
970833AG2-524 GEN
Solar/Wind Harmer
9.303
970833AG2-524 GEN
Solar/Wind Harmer
4.327
274746AC1-111 G10
Adder
5.907
274744AC1-111 GEN8
Adder
5.907
274823ROCKFORD ;21
Adder
19.792
270054AF2-122 C O1
Solar/Wind Helper
0.777
270284AF1-227 GEN1
Solar/Wind Helper
1.165
270286AF1-227 GEN2
Solar/Wind Helper
0.427
270287AF1-227 GEN3
Solar/Wind Helper
0.427
270520AE2-214 GEN
Solar/Wind Helper
2.4
970583AG2-370 GEN
50/50
3.654
960851AF2-376 GEN
50/50
3.29
24727105RPMNG2
50/50
1.31
24641605TWIN BRNCH
50/50
0.024
944531AF1-118 GEN
Solar/Wind Harmer
69.986
270043AE2-236 GEN
Solar/Wind Harmer
10.796
959331AF2-224 GEN
Solar/Wind Harmer
18.221
965021AG1-366 GEN
Solar/Wind Harmer
4.237
970031AG2-029 GEN
Solar/Wind Harmer
49.52
270191TR4_S_V150
Solar/Wind Harmer
4.359
270247TR4_N_V136
Solar/Wind Harmer
1.236
958821AF2-173 GEN
Solar/Wind Harmer
19.357
270004AE1-209 GEN
Solar/Wind Harmer
7.556
971617AH1-308 GEN
Solar/Wind Harmer
7.974
247643Z2-116 C
Solar/Wind Harmer
0.094
945111AF1-176 GEN
Solar/Wind Harmer
7.419
946031AF1-268 GEN
Solar/Wind Harmer
10.671
24642205MAYFLWER
Adder
0.811
970349AG2-230 GEN
Solar/Wind Harmer
18.754
970289AG2-191 GEN
Solar/Wind Harmer
0.958
970291AG2-192 GEN
Solar/Wind Harmer
0.871
24441205WTRV SLR C
Solar/Wind Harmer
0.167
270437AC2-090 C
Solar/Wind Harmer
6.912
247642Z2-115 C
Solar/Wind Harmer
0.079
270044AE2-322 C
Solar/Wind Harmer
1.621
270404AC1-167 GEN
Solar/Wind Harmer
1.35
962031AG1-047 GEN
Solar/Wind Harmer
3.717
957741AF2-068 GEN
Solar/Wind Harmer
18.445
270258AD1-119 GEN
Solar/Wind Harmer
3.413
247604X1-042
Adder
0.507
270491AE1-102 GEN2
Solar/Wind Harmer
1.545
958091AF2-103 GEN
Solar/Wind Harmer
0.191
270535AF1-215 GEN1
Solar/Wind Harmer
5.134
972231SS25-0005
Solar/Wind Harmer
10.654
972181SS23-001
Solar/Wind Harmer
6.659
274752CRETE EC ;2U
Adder
5.487
274753CRETE EC ;3U
Adder
5.487
274724RIVER EC ;11
Adder
19.749
964401AG1-302 GEN
Solar/Wind Harmer
10.079
959141AF2-205 GEN
Solar/Wind Harmer
6.613
274802UNIV PARK;5U
Adder
6.37
274826FISK ;BP
Adder
11.941
24729405KEY G3
50/50
0.729
24729305KEY G2
50/50
0.717
24729205KEY G1
50/50
0.713
970615AG2-402 GEN
50/50
4.237
247620Y3-023
50/50
0.69
970611AG2-400 GEN
Solar/Wind Harmer
18.221
944541AF1-119 GEN
Solar/Wind Harmer
7.444
960971AF2-388 GEN
Solar/Wind Harmer
19.425
942221AE2-234 GEN
Solar/Wind Harmer
1.156
270599AE1-208 GEN
Solar/Wind Harmer
11.731
270031AE2-169
Solar/Wind Harmer
11.731
270216AD2-079_GEN
Solar/Wind Harmer
0.818
960441AF2-335 GEN
Solar/Wind Harmer
13.052
970825AG2-519 GEN
Solar/Wind Harmer
13.779
960981AF2-389 GEN
Solar/Wind Harmer
1.96
957891AF2-083 GEN
Solar/Wind Harmer
4.37
961051AF2-396 GEN
Solar/Wind Harmer
20.497
961051AF2-396 GEN
Solar/Wind Harmer
9.534
270526AF1-158 GEN
Solar/Wind Harmer
5.655
964611AG1-324 GEN
Solar/Wind Harmer
1.464
964611AG1-324 GEN
Solar/Wind Harmer
0.65
24379505HDWTR1G C
Solar/Wind Harmer
9.79
270209AC1-174_GEN
Solar/Wind Harmer
6.909
926881AC1-175 GEN
Solar/Wind Harmer
6.909
24441505OLIV SLR
Solar/Wind Harmer
0.165
270201AC2-176 GEN
Solar/Wind Harmer
6.321
965681AG1-436 GEN
Solar/Wind Harmer
14.967
965791AG1-447 GEN
Solar/Wind Harmer
7.657
246938BC-WTG3
Solar/Wind Harmer
4.73
246937BC-WTG2
Solar/Wind Harmer
4.65
247621Y3-024
Adder
0.286
270007AE1-245 C
Solar/Wind Harmer
7.028
270383AD1-128 GEN
Solar/Wind Harmer
6.977
274808UNIV PK N;4U
Adder
5.518
942801AE2-298 GEN
Solar/Wind Harmer
1.657
274803UNIV PARK;6U
Adder
6.37
274770LINCOLN ;1U
Adder
6.747
274771LINCOLN ;2U
Adder
6.747
274888KELLY CRK;1U
Solar/Wind Harmer
6.415
274887GEN-1.85
Solar/Wind Harmer
5.792
276843GEN-1.7
Solar/Wind Harmer
0.623
958011AF2-095 GEN
Solar/Wind Harmer
15.647
970321AG2-212 GEN
Solar/Wind Harmer
19.29
972259AH1-714 GEN
Adder
20.537
274674JOLIET 9 ;6U
Adder
16.509
970883AG2-550 GEN
Solar/Wind Harmer
10.712
970885AG2-551 GEN
Solar/Wind Harmer
2.491
274847GR RIDGE ;BU
Solar/Wind Harmer
5.386
945421AF1-207 GEN
Solar/Wind Harmer
14.883
274696ROCKY RD ;4P
Adder
11.924
274695ROCKY RD ;2P
Adder
11.649
274693ROCKY RD ;1P
Adder
11.534
274697ROCKY RD ;3P
Adder
3.165
274683WAUKEGAN ;8U
Adder
22.024
274683WAUKEGAN ;8U
Adder
18.565
274764LEE CO EC;5U
Adder
9.321
274765LEE CO EC;6U
Adder
9.321
274762LEE CO EC;3U
Adder
9.299
274763LEE CO EC;4U
Adder
9.211
972267AH1-718 GEN
Adder
4.123
24728805RICHG1
Adder
3.034
24728905RICHG2
Adder
3.034
270471AD2-092_GEN
Solar/Wind Helper
1.076
946101AF1-275 GEN
Solar/Wind Helper
0.301
957841AF2-078 GEN
Solar/Wind Harmer
2.133
960861AF2-377 GEN
50/50
3.382
970521AG2-332 GEN
50/50
16.176
24639705ELKHART HY
50/50
0.225
24727005RPMNG1
50/50
1.305
960791AF2-370 GEN
50/50
3.035
965011AG1-365 GEN
Solar/Wind Harmer
18.221
965651AG1-433 GEN
Solar/Wind Harmer
9.713
958861AF2-177 GEN
Solar/Wind Harmer
18.841
945371AF1-202 GEN
Solar/Wind Harmer
11.314
944231AF1-091 GEN
Solar/Wind Harmer
5.796
270063AE2-323 C
Solar/Wind Harmer
3.37
247521TR3_G114
Solar/Wind Harmer
4.887
270246TR4_N_V150
Solar/Wind Harmer
1.236
24695305TIMB G C
Solar/Wind Harmer
7.786
270005AE1-210 C O1
Solar/Wind Harmer
7.556
965031AG1-367 GEN
Solar/Wind Harmer
13.826
945111AF1-176 GEN
Solar/Wind Harmer
23.41
970825AG2-519 GEN
Solar/Wind Harmer
3.074
270505AE1-170 C O1
Solar/Wind Harmer
19.365
270449AD2-020 GEN
Solar/Wind Harmer
3.585
943021AE2-325 GEN
Solar/Wind Harmer
4.658
270032AE2-172
Solar/Wind Harmer
5.863
965421AG1-410 GEN
Solar/Wind Harmer
37.469
970291AG2-192 GEN
Solar/Wind Harmer
1.623
942081AE2-220 GEN
Solar/Wind Harmer
7.915
270239V3-007_GEN1
Solar/Wind Harmer
2.13
276903AD2-071 C
Solar/Wind Harmer
12.035
246936BC-WTG1
Solar/Wind Harmer
4.65
270489AE1-102 GEN1
Solar/Wind Harmer
1.545
970373AG2-245 GEN
Solar/Wind Harmer
24.186
247536S-71 GEN
Solar/Wind Harmer
4.625
270055AF2-134 C O1
Solar/Wind Harmer
3.422
274751CRETE EC ;1U
Adder
5.487
274754CRETE EC ;4U
Adder
5.487
274723RIVER EC ;12
Adder
19.991
958381AF2-132 GEN
Solar/Wind Harmer
10.079
964861AG1-349 GEN
Solar/Wind Harmer
8.717
971917AH1-482 GEN
Solar/Wind Harmer
10.06
274812UNIV PK N;8U
Adder
5.542
276164X3-005 C
Solar/Wind Harmer
0.775
274801UNIV PARK;4U
Adder
6.347
972207SS24-0001
Solar/Wind Harmer
23.99
274773LINCOLN ;4U
Adder
6.747
274774LINCOLN ;5U
Adder
6.747
276776AD2-060 GEN
Solar/Wind Harmer
0.459
940581AE2-045 GEN
Solar/Wind Harmer
11.063
971605AH1-302 GEN
Solar/Wind Harmer
9.46
970245AG2-165 GEN
Solar/Wind Harmer
19.29
274676JOLIET 29;8U
Adder
32.967
941551AE2-152 GEN
Solar/Wind Harmer
4.871
274674JOLIET 9 ;6U
Adder
16.509
274732ELWOOD EC;7P
Adder
17.624
274871GR RIDGE ;2U
Solar/Wind Harmer
8.188
274745AC1-111 GEN9
Adder
5.907
274682WAUKEGAN ;7U
Adder
18.807
274828WAUKEGAN ;BP
Adder
11.544
274822ROCKFORD ;11
Adder
19.937
972235AH1-702 GEN1
Adder
2.555
274761LEE CO EC;2U
Adder
9.299
274766LEE CO EC;7U
Adder
9.189
24728605AND G2
Adder
3.693
972301AH1-735 GEN
Adder
4.399
23906402RICHG1
Adder
0.88
23906502RICHG2&3
Adder
0.873
970091AG2-072 GEN
Adder
0.148
270349AD2-093_GEN
Solar/Wind Helper
1.076
274800UNIV PARK;3U
Adder
6.347
972038AH1-567 GEN2
Adder
0.397
274772LINCOLN ;3U
Adder
6.747
276772AC2-154 GEN
Solar/Wind Harmer
3.03
276806AD2-047 C O1
Solar/Wind Harmer
11.624
970941AG2-585 GEN
Solar/Wind Harmer
13.583
972228AH1-698 GEN2
Adder
4.009
970513AG2-328 GEN
Solar/Wind Harmer
19.29
970517AG2-330 GEN
Solar/Wind Harmer
17.496
274676JOLIET 29;8U
Adder
31.789
276897AD1-100 C
Solar/Wind Harmer
31.167
939351AE1-166 GEN
Solar/Wind Harmer
6.368
970707AG2-453 GEN
Solar/Wind Harmer
30.052
276893AG1-478 C
Solar/Wind Harmer
0.448
274730ELWOOD EC;6P
Adder
17.624
274734ELWOOD EC;8P
Adder
17.624
274736ELWOOD EC;9P
Adder
17.624
274729ELWOOD EC;1P
Adder
17.623
274682WAUKEGAN ;7U
Adder
18.807
972236AH1-702 GEN2
Adder
2.221
274760LEE CO EC;1U
Adder
9.299
274767LEE CO EC;8U
Adder
9.189
24728705AND G3
Adder
7.723
24728505AND G1
Adder
3.693
23906502RICHG2&3
Adder
0.873
944201AF1-088_MTX
Adder
86.769
957141AF2-008_MTX
Adder
43.385
990497J1323
External Queue
1.917611837387085
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.192
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.594
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.211
MECLTFEXP_MEC->PJM
CLTF
14.346
SIGELTFEXP_SIGE->PJM
CLTF
0.331
LAGNLTFEXP_LAGN->PJM
CLTF
8.254
TVALTFEXP_TVA->PJM
CLTF
3.263
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.552
NYPJM->LTFIMP_NY
CLTF
1.999
LGEELTFEXP_LGEE->PJM
CLTF
3.213
WECLTFEXP_WEC->PJM
CLTF
3.867
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.533
AG2-052LTFEXP_AG2-052->PJM
LTF
0.256
AH1-155LTFEXP_AH1-155->PJM
LTF
0.384

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7442_05SORENS 765_K2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7442_05SORENS 765_K2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.09 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3595.31
MW Contribution:49.4
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.218
24729505KEY G4
50/50
13.356
24727205RPMNG3
50/50
1.297
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
28.449
958711AF2-162 GEN
Solar/Wind Harmer
1.798
965101AG1-375 GEN
Solar/Wind Harmer
17.236
945581AF1-223 GEN
Solar/Wind Harmer
7.355
963791AG1-232 GEN
Solar/Wind Harmer
21.4
965041AG1-368 GEN
Solar/Wind Harmer
15.694
965051AG1-369 GEN
Solar/Wind Harmer
7.247
270024AE2-089 GEN
Solar/Wind Harmer
6.436
970115AG2-085 GEN
Solar/Wind Harmer
5.224
971771AH1-392 GEN
Solar/Wind Harmer
11.55
270594AE1-207 GEN
Solar/Wind Harmer
18.557
944161AF1-084 GEN
Solar/Wind Harmer
2.773
971347AH1-153 GEN
Solar/Wind Harmer
18.804
965461AG1-414 GEN
Solar/Wind Harmer
2.837
970289AG2-191 GEN
Solar/Wind Harmer
2.377
270240V3-007_GEN2
Solar/Wind Harmer
7.664
961761AG1-017 GEN
Solar/Wind Harmer
0.526
971769AH1-391 GEN
Solar/Wind Harmer
12.286
24725505WLD G2 C
Solar/Wind Harmer
4.756
24699105WLD G1 C
Solar/Wind Harmer
4.7
960681AF2-359 GEN
Solar/Wind Harmer
4.511
957201AF2-014 GEN
Solar/Wind Harmer
5.38
270435AC2-044 GEN
Solar/Wind Harmer
2.373
247607V1-011 GEN
Solar/Wind Harmer
4.68
971549AH1-272 GEN
Solar/Wind Harmer
21.784
270536AF1-215 GEN2
Solar/Wind Harmer
5.131
274814UNIV PK N;0U
Adder
5.609
274807UNIV PK N;3U
Adder
5.596
274805UNIV PK N;1U
Adder
5.572
274811UNIV PK N;7U
Adder
5.56
958391AF2-133 GEN
Solar/Wind Harmer
9.994
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.497
274775LINCOLN ;6U
Adder
6.786
274776LINCOLN ;7U
Adder
6.786
274777LINCOLN ;8U
Adder
6.786
960591AF2-350 GEN
Solar/Wind Harmer
10.912
972227AH1-698 GEN1
Adder
2.835
274687WILL CNTY;4U
Adder
30.235
274687WILL CNTY;4U
Adder
30.235
274675JOLIET 29;7U
Adder
33.113
274675JOLIET 29;7U
Adder
31.93
274728ELWOOD EC;5P
Adder
17.702
274731ELWOOD EC;2P
Adder
17.701
274733ELWOOD EC;3P
Adder
17.701
274735ELWOOD EC;4P
Adder
17.701
270543AE2-219 C
Solar/Wind Harmer
5.487
970833AG2-524 GEN
Solar/Wind Harmer
9.348
970833AG2-524 GEN
Solar/Wind Harmer
4.348
274746AC1-111 G10
Adder
5.936
274744AC1-111 GEN8
Adder
5.936
274823ROCKFORD ;21
Adder
19.887
270054AF2-122 C O1
Solar/Wind Helper
0.778
270284AF1-227 GEN1
Solar/Wind Helper
1.167
270286AF1-227 GEN2
Solar/Wind Helper
0.428
270287AF1-227 GEN3
Solar/Wind Helper
0.428
270520AE2-214 GEN
Solar/Wind Helper
2.4
24729405KEY G3
50/50
0.729
24729305KEY G2
50/50
0.717
24729205KEY G1
50/50
0.713
970615AG2-402 GEN
50/50
4.232
247620Y3-023
50/50
0.687
970611AG2-400 GEN
Solar/Wind Harmer
18.199
944541AF1-119 GEN
Solar/Wind Harmer
7.443
960971AF2-388 GEN
Solar/Wind Harmer
19.424
942221AE2-234 GEN
Solar/Wind Harmer
1.156
270599AE1-208 GEN
Solar/Wind Harmer
11.735
270031AE2-169
Solar/Wind Harmer
11.735
270216AD2-079_GEN
Solar/Wind Harmer
0.814
960441AF2-335 GEN
Solar/Wind Harmer
13.06
970825AG2-519 GEN
Solar/Wind Harmer
13.786
960981AF2-389 GEN
Solar/Wind Harmer
1.943
957891AF2-083 GEN
Solar/Wind Harmer
4.334
961051AF2-396 GEN
Solar/Wind Harmer
20.314
961051AF2-396 GEN
Solar/Wind Harmer
9.449
964611AG1-324 GEN
Solar/Wind Harmer
1.464
964611AG1-324 GEN
Solar/Wind Harmer
0.65
270526AF1-158 GEN
Solar/Wind Harmer
5.631
24379505HDWTR1G C
Solar/Wind Harmer
9.795
270209AC1-174_GEN
Solar/Wind Harmer
6.913
926881AC1-175 GEN
Solar/Wind Harmer
6.913
270201AC2-176 GEN
Solar/Wind Harmer
6.323
24441505OLIV SLR
Solar/Wind Harmer
0.165
965681AG1-436 GEN
Solar/Wind Harmer
14.927
965791AG1-447 GEN
Solar/Wind Harmer
7.637
247621Y3-024
Adder
0.286
246938BC-WTG3
Solar/Wind Harmer
4.722
246937BC-WTG2
Solar/Wind Harmer
4.642
270007AE1-245 C
Solar/Wind Harmer
7.017
270383AD1-128 GEN
Solar/Wind Harmer
6.981
274808UNIV PK N;4U
Adder
5.536
274803UNIV PARK;6U
Adder
6.395
274770LINCOLN ;1U
Adder
6.786
274771LINCOLN ;2U
Adder
6.786
942801AE2-298 GEN
Solar/Wind Harmer
1.654
970321AG2-212 GEN
Solar/Wind Harmer
19.508
274888KELLY CRK;1U
Solar/Wind Harmer
6.442
274887GEN-1.85
Solar/Wind Harmer
5.816
276843GEN-1.7
Solar/Wind Harmer
0.626
958011AF2-095 GEN
Solar/Wind Harmer
15.713
972259AH1-714 GEN
Adder
20.637
274674JOLIET 9 ;6U
Adder
16.583
970883AG2-550 GEN
Solar/Wind Harmer
10.716
970885AG2-551 GEN
Solar/Wind Harmer
2.492
274847GR RIDGE ;BU
Solar/Wind Harmer
5.412
945421AF1-207 GEN
Solar/Wind Harmer
14.915
274695ROCKY RD ;2P
Adder
11.705
274693ROCKY RD ;1P
Adder
11.59
274697ROCKY RD ;3P
Adder
3.18
274696ROCKY RD ;4P
Adder
11.982
274683WAUKEGAN ;8U
Adder
22.127
274683WAUKEGAN ;8U
Adder
18.652
274764LEE CO EC;5U
Adder
9.365
274765LEE CO EC;6U
Adder
9.365
274762LEE CO EC;3U
Adder
9.343
274763LEE CO EC;4U
Adder
9.255
972267AH1-718 GEN
Adder
4.143
24728805RICHG1
Adder
3.037
24728905RICHG2
Adder
3.037
270471AD2-092_GEN
Solar/Wind Helper
1.077
946101AF1-275 GEN
Solar/Wind Helper
0.301
957841AF2-078 GEN
Solar/Wind Harmer
2.137
960861AF2-377 GEN
50/50
3.377
970521AG2-332 GEN
50/50
16.09
24639705ELKHART HY
50/50
0.224
24727005RPMNG1
50/50
1.303
960791AF2-370 GEN
50/50
3.037
965011AG1-365 GEN
Solar/Wind Harmer
18.199
965651AG1-433 GEN
Solar/Wind Harmer
9.712
958861AF2-177 GEN
Solar/Wind Harmer
18.84
945371AF1-202 GEN
Solar/Wind Harmer
11.315
944231AF1-091 GEN
Solar/Wind Harmer
5.785
270063AE2-323 C
Solar/Wind Harmer
3.359
247521TR3_G114
Solar/Wind Harmer
4.88
270246TR4_N_V150
Solar/Wind Harmer
1.235
24695305TIMB G C
Solar/Wind Harmer
7.775
270005AE1-210 C O1
Solar/Wind Harmer
7.559
965031AG1-367 GEN
Solar/Wind Harmer
13.832
970825AG2-519 GEN
Solar/Wind Harmer
3.076
945111AF1-176 GEN
Solar/Wind Harmer
23.221
270505AE1-170 C O1
Solar/Wind Harmer
19.191
270449AD2-020 GEN
Solar/Wind Harmer
3.551
943021AE2-325 GEN
Solar/Wind Harmer
4.614
270032AE2-172
Solar/Wind Harmer
5.873
970291AG2-192 GEN
Solar/Wind Harmer
1.626
965421AG1-410 GEN
Solar/Wind Harmer
37.41
942081AE2-220 GEN
Solar/Wind Harmer
7.919
270239V3-007_GEN1
Solar/Wind Harmer
2.131
276903AD2-071 C
Solar/Wind Harmer
12.055
246936BC-WTG1
Solar/Wind Harmer
4.642
270489AE1-102 GEN1
Solar/Wind Harmer
1.542
970373AG2-245 GEN
Solar/Wind Harmer
24.151
247536S-71 GEN
Solar/Wind Harmer
4.626
270055AF2-134 C O1
Solar/Wind Harmer
3.42
274751CRETE EC ;1U
Adder
5.501
274754CRETE EC ;4U
Adder
5.501
274723RIVER EC ;12
Adder
20.057
958381AF2-132 GEN
Solar/Wind Harmer
10.08
274812UNIV PK N;8U
Adder
5.56
964861AG1-349 GEN
Solar/Wind Harmer
8.718
971917AH1-482 GEN
Solar/Wind Harmer
10.061
276164X3-005 C
Solar/Wind Harmer
0.778
972207SS24-0001
Solar/Wind Harmer
24.127
274773LINCOLN ;4U
Adder
6.786
274774LINCOLN ;5U
Adder
6.786
274801UNIV PARK;4U
Adder
6.373
970245AG2-165 GEN
Solar/Wind Harmer
19.508
276776AD2-060 GEN
Solar/Wind Harmer
0.461
940581AE2-045 GEN
Solar/Wind Harmer
11.076
971605AH1-302 GEN
Solar/Wind Harmer
9.471
274676JOLIET 29;8U
Adder
33.113
941551AE2-152 GEN
Solar/Wind Harmer
4.894
274674JOLIET 9 ;6U
Adder
16.583
274732ELWOOD EC;7P
Adder
17.702
274871GR RIDGE ;2U
Solar/Wind Harmer
8.227
274745AC1-111 GEN9
Adder
5.936
274682WAUKEGAN ;7U
Adder
18.895
274828WAUKEGAN ;BP
Adder
11.599
274822ROCKFORD ;11
Adder
20.032
972235AH1-702 GEN1
Adder
2.567
274761LEE CO EC;2U
Adder
9.343
274766LEE CO EC;7U
Adder
9.233
24728605AND G2
Adder
3.7
972301AH1-735 GEN
Adder
4.377
23906402RICHG1
Adder
0.875
23906502RICHG2&3
Adder
0.869
970091AG2-072 GEN
Adder
0.149
270349AD2-093_GEN
Solar/Wind Helper
1.077
970583AG2-370 GEN
50/50
3.65
960851AF2-376 GEN
50/50
3.285
24727105RPMNG2
50/50
1.308
24641605TWIN BRNCH
50/50
0.023
944531AF1-118 GEN
Solar/Wind Harmer
69.966
270043AE2-236 GEN
Solar/Wind Harmer
10.785
959331AF2-224 GEN
Solar/Wind Harmer
18.199
965021AG1-366 GEN
Solar/Wind Harmer
4.232
970031AG2-029 GEN
Solar/Wind Harmer
49.401
270191TR4_S_V150
Solar/Wind Harmer
4.354
270247TR4_N_V136
Solar/Wind Harmer
1.235
958821AF2-173 GEN
Solar/Wind Harmer
19.364
270004AE1-209 GEN
Solar/Wind Harmer
7.559
971617AH1-308 GEN
Solar/Wind Harmer
7.972
247643Z2-116 C
Solar/Wind Harmer
0.093
945111AF1-176 GEN
Solar/Wind Harmer
7.359
946031AF1-268 GEN
Solar/Wind Harmer
10.676
24642205MAYFLWER
Adder
0.806
970349AG2-230 GEN
Solar/Wind Harmer
18.804
970289AG2-191 GEN
Solar/Wind Harmer
0.96
970291AG2-192 GEN
Solar/Wind Harmer
0.873
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.916
270044AE2-322 C
Solar/Wind Harmer
1.618
270404AC1-167 GEN
Solar/Wind Harmer
1.347
962031AG1-047 GEN
Solar/Wind Harmer
3.717
957741AF2-068 GEN
Solar/Wind Harmer
18.448
24441205WTRV SLR C
Solar/Wind Harmer
0.165
270258AD1-119 GEN
Solar/Wind Harmer
3.407
247604X1-042
Adder
0.501
270491AE1-102 GEN2
Solar/Wind Harmer
1.542
958091AF2-103 GEN
Solar/Wind Harmer
0.191
270535AF1-215 GEN1
Solar/Wind Harmer
5.131
972231SS25-0005
Solar/Wind Harmer
10.68
972181SS23-001
Solar/Wind Harmer
6.675
274752CRETE EC ;2U
Adder
5.501
274753CRETE EC ;3U
Adder
5.501
274724RIVER EC ;11
Adder
19.816
964401AG1-302 GEN
Solar/Wind Harmer
10.08
274802UNIV PARK;5U
Adder
6.395
274826FISK ;BP
Adder
11.989
959141AF2-205 GEN
Solar/Wind Harmer
6.618
274772LINCOLN ;3U
Adder
6.786
274800UNIV PARK;3U
Adder
6.373
972038AH1-567 GEN2
Adder
0.399
970513AG2-328 GEN
Solar/Wind Harmer
19.508
970517AG2-330 GEN
Solar/Wind Harmer
17.693
276772AC2-154 GEN
Solar/Wind Harmer
3.043
276806AD2-047 C O1
Solar/Wind Harmer
11.673
970941AG2-585 GEN
Solar/Wind Harmer
13.64
972228AH1-698 GEN2
Adder
4.027
274676JOLIET 29;8U
Adder
31.93
276897AD1-100 C
Solar/Wind Harmer
31.315
939351AE1-166 GEN
Solar/Wind Harmer
6.398
970707AG2-453 GEN
Solar/Wind Harmer
30.212
276893AG1-478 C
Solar/Wind Harmer
0.45
274730ELWOOD EC;6P
Adder
17.702
274734ELWOOD EC;8P
Adder
17.702
274736ELWOOD EC;9P
Adder
17.702
274729ELWOOD EC;1P
Adder
17.701
274682WAUKEGAN ;7U
Adder
18.895
972236AH1-702 GEN2
Adder
2.232
274760LEE CO EC;1U
Adder
9.343
274767LEE CO EC;8U
Adder
9.233
24728705AND G3
Adder
7.738
24728505AND G1
Adder
3.7
23906502RICHG2&3
Adder
0.869
944201AF1-088_MTX
Adder
87.117
957141AF2-008_MTX
Adder
43.559
990497J1323
External Queue
1.901388168334961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.288
MECLTFEXP_MEC->PJM
CLTF
14.414
SIGELTFEXP_SIGE->PJM
CLTF
0.332
LAGNLTFEXP_LAGN->PJM
CLTF
8.301
TVALTFEXP_TVA->PJM
CLTF
3.284
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.901
NYPJM->LTFIMP_NY
CLTF
2
LGEELTFEXP_LGEE->PJM
CLTF
3.227
WECLTFEXP_WEC->PJM
CLTF
3.885
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.257
AH1-155LTFEXP_AH1-155->PJM
LTF
0.385

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7444_05DUMONT 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7444_05DUMONT 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.9 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3589.56
MW Contribution:49.56
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.73
24729305KEY G2
50/50
0.718
24729205KEY G1
50/50
0.714
970615AG2-402 GEN
50/50
4.243
247620Y3-023
50/50
0.692
970611AG2-400 GEN
Solar/Wind Harmer
18.246
944541AF1-119 GEN
Solar/Wind Harmer
7.455
960971AF2-388 GEN
Solar/Wind Harmer
19.454
942221AE2-234 GEN
Solar/Wind Harmer
1.157
270599AE1-208 GEN
Solar/Wind Harmer
11.746
270031AE2-169
Solar/Wind Harmer
11.746
270216AD2-079_GEN
Solar/Wind Harmer
0.821
960441AF2-335 GEN
Solar/Wind Harmer
13.068
970825AG2-519 GEN
Solar/Wind Harmer
13.796
960981AF2-389 GEN
Solar/Wind Harmer
1.957
957891AF2-083 GEN
Solar/Wind Harmer
4.363
961051AF2-396 GEN
Solar/Wind Harmer
20.443
960861AF2-377 GEN
50/50
3.387
970521AG2-332 GEN
50/50
16.194
24639705ELKHART HY
50/50
0.225
24727005RPMNG1
50/50
1.307
960791AF2-370 GEN
50/50
3.039
965011AG1-365 GEN
Solar/Wind Harmer
18.246
965651AG1-433 GEN
Solar/Wind Harmer
9.727
958861AF2-177 GEN
Solar/Wind Harmer
18.868
945371AF1-202 GEN
Solar/Wind Harmer
11.33
944231AF1-091 GEN
Solar/Wind Harmer
5.803
270063AE2-323 C
Solar/Wind Harmer
3.379
247521TR3_G114
Solar/Wind Harmer
4.894
270246TR4_N_V150
Solar/Wind Harmer
1.238
24695305TIMB G C
Solar/Wind Harmer
7.798
270005AE1-210 C O1
Solar/Wind Harmer
7.567
965031AG1-367 GEN
Solar/Wind Harmer
13.845
945111AF1-176 GEN
Solar/Wind Harmer
23.371
970825AG2-519 GEN
Solar/Wind Harmer
3.078
270505AE1-170 C O1
Solar/Wind Harmer
19.319
270449AD2-020 GEN
Solar/Wind Harmer
3.573
971599AH1-298 GEN
50/50
20.277
24729505KEY G4
50/50
13.379
24727205RPMNG3
50/50
1.301
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
28.477
958711AF2-162 GEN
Solar/Wind Harmer
1.801
965101AG1-375 GEN
Solar/Wind Harmer
17.262
945581AF1-223 GEN
Solar/Wind Harmer
7.365
963791AG1-232 GEN
Solar/Wind Harmer
21.446
965041AG1-368 GEN
Solar/Wind Harmer
15.736
965051AG1-369 GEN
Solar/Wind Harmer
7.267
270024AE2-089 GEN
Solar/Wind Harmer
6.446
970115AG2-085 GEN
Solar/Wind Harmer
5.227
971771AH1-392 GEN
Solar/Wind Harmer
11.649
971347AH1-153 GEN
Solar/Wind Harmer
19.196
944161AF1-084 GEN
Solar/Wind Harmer
2.789
270594AE1-207 GEN
Solar/Wind Harmer
18.539
965461AG1-414 GEN
Solar/Wind Harmer
2.832
970289AG2-191 GEN
Solar/Wind Harmer
2.373
270240V3-007_GEN2
Solar/Wind Harmer
7.67
971769AH1-391 GEN
Solar/Wind Harmer
12.39
961761AG1-017 GEN
Solar/Wind Harmer
0.527
960681AF2-359 GEN
Solar/Wind Harmer
4.552
24725505WLD G2 C
Solar/Wind Harmer
4.752
24699105WLD G1 C
Solar/Wind Harmer
4.696
957201AF2-014 GEN
Solar/Wind Harmer
5.397
270435AC2-044 GEN
Solar/Wind Harmer
2.38
971549AH1-272 GEN
Solar/Wind Harmer
21.971
247607V1-011 GEN
Solar/Wind Harmer
4.695
270536AF1-215 GEN2
Solar/Wind Harmer
5.155
274814UNIV PK N;0U
Adder
5.61
274807UNIV PK N;3U
Adder
5.598
274805UNIV PK N;1U
Adder
5.574
274811UNIV PK N;7U
Adder
5.562
958391AF2-133 GEN
Solar/Wind Harmer
10.019
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.489
274775LINCOLN ;6U
Adder
6.754
274776LINCOLN ;7U
Adder
6.754
274777LINCOLN ;8U
Adder
6.754
960591AF2-350 GEN
Solar/Wind Harmer
10.896
972227AH1-698 GEN1
Adder
2.829
274687WILL CNTY;4U
Adder
30.181
274687WILL CNTY;4U
Adder
30.181
274675JOLIET 29;7U
Adder
33.046
274675JOLIET 29;7U
Adder
31.866
274728ELWOOD EC;5P
Adder
17.665
274731ELWOOD EC;2P
Adder
17.664
274733ELWOOD EC;3P
Adder
17.664
274735ELWOOD EC;4P
Adder
17.664
270543AE2-219 C
Solar/Wind Harmer
5.493
970833AG2-524 GEN
Solar/Wind Harmer
9.321
970833AG2-524 GEN
Solar/Wind Harmer
4.335
274746AC1-111 G10
Adder
5.917
274744AC1-111 GEN8
Adder
5.917
274823ROCKFORD ;21
Adder
19.829
943021AE2-325 GEN
Solar/Wind Harmer
4.643
270032AE2-172
Solar/Wind Harmer
5.867
965421AG1-410 GEN
Solar/Wind Harmer
37.525
970291AG2-192 GEN
Solar/Wind Harmer
1.624
942081AE2-220 GEN
Solar/Wind Harmer
7.926
270239V3-007_GEN1
Solar/Wind Harmer
2.133
276903AD2-071 C
Solar/Wind Harmer
12.042
246936BC-WTG1
Solar/Wind Harmer
4.657
270489AE1-102 GEN1
Solar/Wind Harmer
1.547
970373AG2-245 GEN
Solar/Wind Harmer
24.301
247536S-71 GEN
Solar/Wind Harmer
4.631
270055AF2-134 C O1
Solar/Wind Harmer
3.436
274751CRETE EC ;1U
Adder
5.51
274754CRETE EC ;4U
Adder
5.51
274723RIVER EC ;12
Adder
20.078
958381AF2-132 GEN
Solar/Wind Harmer
10.112
964861AG1-349 GEN
Solar/Wind Harmer
8.745
971917AH1-482 GEN
Solar/Wind Harmer
10.092
274812UNIV PK N;8U
Adder
5.562
276164X3-005 C
Solar/Wind Harmer
0.778
274801UNIV PARK;4U
Adder
6.366
972207SS24-0001
Solar/Wind Harmer
24.014
274773LINCOLN ;4U
Adder
6.754
274774LINCOLN ;5U
Adder
6.754
276776AD2-060 GEN
Solar/Wind Harmer
0.461
940581AE2-045 GEN
Solar/Wind Harmer
11.089
971605AH1-302 GEN
Solar/Wind Harmer
9.483
274676JOLIET 29;8U
Adder
33.046
941551AE2-152 GEN
Solar/Wind Harmer
4.881
274674JOLIET 9 ;6U
Adder
16.547
274732ELWOOD EC;7P
Adder
17.665
970245AG2-165 GEN
Solar/Wind Harmer
19.169
274871GR RIDGE ;2U
Solar/Wind Harmer
8.203
274745AC1-111 GEN9
Adder
5.917
274682WAUKEGAN ;7U
Adder
18.845
274828WAUKEGAN ;BP
Adder
11.568
274822ROCKFORD ;11
Adder
19.974
972235AH1-702 GEN1
Adder
2.559
274761LEE CO EC;2U
Adder
9.316
274766LEE CO EC;7U
Adder
9.206
24728605AND G2
Adder
3.696
972301AH1-735 GEN
Adder
4.398
23906402RICHG1
Adder
0.88
23906502RICHG2&3
Adder
0.873
970091AG2-072 GEN
Adder
0.148
270349AD2-093_GEN
Solar/Wind Helper
1.074
970583AG2-370 GEN
50/50
3.66
960851AF2-376 GEN
50/50
3.295
24727105RPMNG2
50/50
1.312
24641605TWIN BRNCH
50/50
0.024
944531AF1-118 GEN
Solar/Wind Harmer
70.092
270043AE2-236 GEN
Solar/Wind Harmer
10.813
959331AF2-224 GEN
Solar/Wind Harmer
18.246
965021AG1-366 GEN
Solar/Wind Harmer
4.243
970031AG2-029 GEN
Solar/Wind Harmer
49.558
270191TR4_S_V150
Solar/Wind Harmer
4.366
270247TR4_N_V136
Solar/Wind Harmer
1.238
958821AF2-173 GEN
Solar/Wind Harmer
19.383
270004AE1-209 GEN
Solar/Wind Harmer
7.567
971617AH1-308 GEN
Solar/Wind Harmer
7.985
247643Z2-116 C
Solar/Wind Harmer
0.094
945111AF1-176 GEN
Solar/Wind Harmer
7.407
946031AF1-268 GEN
Solar/Wind Harmer
10.685
970349AG2-230 GEN
Solar/Wind Harmer
19.196
24642205MAYFLWER
Adder
0.812
970289AG2-191 GEN
Solar/Wind Harmer
0.959
970291AG2-192 GEN
Solar/Wind Harmer
0.872
270437AC2-090 C
Solar/Wind Harmer
6.922
247642Z2-115 C
Solar/Wind Harmer
0.079
270044AE2-322 C
Solar/Wind Harmer
1.623
270404AC1-167 GEN
Solar/Wind Harmer
1.352
24441205WTRV SLR C
Solar/Wind Harmer
0.166
962031AG1-047 GEN
Solar/Wind Harmer
3.722
957741AF2-068 GEN
Solar/Wind Harmer
18.469
270258AD1-119 GEN
Solar/Wind Harmer
3.418
247604X1-042
Adder
0.504
270491AE1-102 GEN2
Solar/Wind Harmer
1.547
958091AF2-103 GEN
Solar/Wind Harmer
0.192
270535AF1-215 GEN1
Solar/Wind Harmer
5.155
972231SS25-0005
Solar/Wind Harmer
10.698
972181SS23-001
Solar/Wind Harmer
6.686
274752CRETE EC ;2U
Adder
5.51
274753CRETE EC ;3U
Adder
5.51
274724RIVER EC ;11
Adder
19.836
964401AG1-302 GEN
Solar/Wind Harmer
10.112
959141AF2-205 GEN
Solar/Wind Harmer
6.631
274802UNIV PARK;5U
Adder
6.39
274826FISK ;BP
Adder
11.978
274800UNIV PARK;3U
Adder
6.366
972038AH1-567 GEN2
Adder
0.398
274772LINCOLN ;3U
Adder
6.754
276772AC2-154 GEN
Solar/Wind Harmer
3.039
276806AD2-047 C O1
Solar/Wind Harmer
11.656
970941AG2-585 GEN
Solar/Wind Harmer
13.62
972228AH1-698 GEN2
Adder
4.019
274676JOLIET 29;8U
Adder
31.865
276897AD1-100 C
Solar/Wind Harmer
31.229
939351AE1-166 GEN
Solar/Wind Harmer
6.381
276893AG1-478 C
Solar/Wind Harmer
0.449
970707AG2-453 GEN
Solar/Wind Harmer
30.091
274730ELWOOD EC;6P
Adder
17.665
274734ELWOOD EC;8P
Adder
17.665
274736ELWOOD EC;9P
Adder
17.665
274729ELWOOD EC;1P
Adder
17.664
970513AG2-328 GEN
Solar/Wind Harmer
19.169
970517AG2-330 GEN
Solar/Wind Harmer
17.386
274682WAUKEGAN ;7U
Adder
18.845
972236AH1-702 GEN2
Adder
2.226
274760LEE CO EC;1U
Adder
9.316
274767LEE CO EC;8U
Adder
9.206
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
23906502RICHG2&3
Adder
0.873
961051AF2-396 GEN
Solar/Wind Harmer
9.508
270526AF1-158 GEN
Solar/Wind Harmer
5.679
964611AG1-324 GEN
Solar/Wind Harmer
1.466
964611AG1-324 GEN
Solar/Wind Harmer
0.651
24379505HDWTR1G C
Solar/Wind Harmer
9.803
270209AC1-174_GEN
Solar/Wind Harmer
6.918
926881AC1-175 GEN
Solar/Wind Harmer
6.918
24441505OLIV SLR
Solar/Wind Harmer
0.166
270201AC2-176 GEN
Solar/Wind Harmer
6.33
965681AG1-436 GEN
Solar/Wind Harmer
15.06
965791AG1-447 GEN
Solar/Wind Harmer
7.705
246938BC-WTG3
Solar/Wind Harmer
4.737
246937BC-WTG2
Solar/Wind Harmer
4.657
247621Y3-024
Adder
0.287
270007AE1-245 C
Solar/Wind Harmer
7.038
270383AD1-128 GEN
Solar/Wind Harmer
6.986
274808UNIV PK N;4U
Adder
5.537
942801AE2-298 GEN
Solar/Wind Harmer
1.659
274803UNIV PARK;6U
Adder
6.39
274770LINCOLN ;1U
Adder
6.754
274771LINCOLN ;2U
Adder
6.754
274888KELLY CRK;1U
Solar/Wind Harmer
6.433
274887GEN-1.85
Solar/Wind Harmer
5.808
276843GEN-1.7
Solar/Wind Harmer
0.625
958011AF2-095 GEN
Solar/Wind Harmer
15.69
972259AH1-714 GEN
Adder
20.574
274674JOLIET 9 ;6U
Adder
16.547
970321AG2-212 GEN
Solar/Wind Harmer
19.169
970883AG2-550 GEN
Solar/Wind Harmer
10.727
970885AG2-551 GEN
Solar/Wind Harmer
2.495
274847GR RIDGE ;BU
Solar/Wind Harmer
5.396
945421AF1-207 GEN
Solar/Wind Harmer
14.904
274695ROCKY RD ;2P
Adder
11.671
274693ROCKY RD ;1P
Adder
11.556
274697ROCKY RD ;3P
Adder
3.17
274696ROCKY RD ;4P
Adder
11.946
274683WAUKEGAN ;8U
Adder
22.068
274683WAUKEGAN ;8U
Adder
18.602
274764LEE CO EC;5U
Adder
9.338
274765LEE CO EC;6U
Adder
9.338
274762LEE CO EC;3U
Adder
9.316
274763LEE CO EC;4U
Adder
9.228
972267AH1-718 GEN
Adder
4.131
24728805RICHG1
Adder
3.038
24728905RICHG2
Adder
3.038
270471AD2-092_GEN
Solar/Wind Helper
1.074
946101AF1-275 GEN
Solar/Wind Helper
0.3
957841AF2-078 GEN
Solar/Wind Harmer
2.136
270054AF2-122 C O1
Solar/Wind Helper
0.776
270284AF1-227 GEN1
Solar/Wind Helper
1.163
270286AF1-227 GEN2
Solar/Wind Helper
0.426
270287AF1-227 GEN3
Solar/Wind Helper
0.426
270520AE2-214 GEN
Solar/Wind Helper
2.396
944201AF1-088_MTX
Adder
86.826
957141AF2-008_MTX
Adder
43.413
990497J1323
External Queue
1.9195195436477661
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.237
MECLTFEXP_MEC->PJM
CLTF
14.373
SIGELTFEXP_SIGE->PJM
CLTF
0.331
LAGNLTFEXP_LAGN->PJM
CLTF
8.272
TVALTFEXP_TVA->PJM
CLTF
3.271
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.674
NYPJM->LTFIMP_NY
CLTF
1.996
LGEELTFEXP_LGEE->PJM
CLTF
3.215
WECLTFEXP_WEC->PJM
CLTF
3.875
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.53
AG2-052LTFEXP_AG2-052->PJM
LTF
0.258
AH1-155LTFEXP_AH1-155->PJM
LTF
0.388

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P1-2_#7442_200545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P1-2_#7442_200545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.07 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3439.74
MW Contribution:7.47
Bus #Bus NameTypeMW Contribution
970583AG2-370 GEN
50/50
3.65
960851AF2-376 GEN
50/50
3.285
24727105RPMNG2
50/50
1.308
24641605TWIN BRNCH
50/50
0.023
944531AF1-118 GEN
Solar/Wind Harmer
62.505
270043AE2-236 GEN
Solar/Wind Harmer
8.778
959331AF2-224 GEN
Solar/Wind Harmer
8.888
965021AG1-366 GEN
Solar/Wind Harmer
4.232
970031AG2-029 GEN
Solar/Wind Harmer
7.468
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.065
958821AF2-173 GEN
Solar/Wind Harmer
13.51
270004AE1-209 GEN
Solar/Wind Harmer
2.091
971617AH1-308 GEN
Solar/Wind Harmer
7.972
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
7.359
946031AF1-268 GEN
Solar/Wind Harmer
8.54
24642205MAYFLWER
Adder
0.806
970349AG2-230 GEN
Solar/Wind Harmer
13.119
970289AG2-191 GEN
Solar/Wind Harmer
0.96
970291AG2-192 GEN
Solar/Wind Harmer
0.873
247642Z2-115 C
Solar/Wind Harmer
0.004
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
12.871
24441205WTRV SLR C
Solar/Wind Harmer
0
270258AD1-119 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.501
270491AE1-102 GEN2
Solar/Wind Harmer
1.076
270535AF1-215 GEN1
Solar/Wind Harmer
0.01
274752CRETE EC ;2U
Adder
9.273
274753CRETE EC ;3U
Adder
9.273
274724RIVER EC ;11
Adder
19.816
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274802UNIV PARK;5U
Adder
6.395
274826FISK ;BP
Adder
11.989
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274772LINCOLN ;3U
Adder
9.237
274800UNIV PARK;3U
Adder
6.373
972038AH1-567 GEN2
Adder
0.399
970513AG2-328 GEN
Solar/Wind Harmer
3.303
970517AG2-330 GEN
Solar/Wind Harmer
19.816
276806AD2-047 C O1
Solar/Wind Harmer
4.314
970941AG2-585 GEN
Solar/Wind Harmer
9.516
972228AH1-698 GEN2
Adder
4.027
274676JOLIET 29;8U
Adder
31.93
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
24.591
276893AG1-478 C
Solar/Wind Harmer
0.298
274730ELWOOD EC;6P
Adder
17.702
274734ELWOOD EC;8P
Adder
17.702
274736ELWOOD EC;9P
Adder
17.702
274729ELWOOD EC;1P
Adder
17.701
943121AE2-341 GEN
Solar/Wind Harmer
12.419
943591AF1-030 GEN
Solar/Wind Harmer
8.259
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.895
276805AD2-038 GEN
Solar/Wind Harmer
0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.294
274872LEEDK;1U
Solar/Wind Harmer
0.266
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.766
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.263
274850MENDOTA H;RU
Solar/Wind Harmer
0.085
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.129
959091AF2-200 GEN
Solar/Wind Harmer
14.285
972236AH1-702 GEN2
Adder
2.232
970571AG2-364 GEN
Solar/Wind Harmer
14.206
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.343
274767LEE CO EC;8U
Adder
9.233
276157O29GEN1
Solar/Wind Harmer
1.121
274878BISHOP HL;2U
Solar/Wind Harmer
0.232
942111AE2-223 GEN
Solar/Wind Harmer
2.239
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
20.348
959611AF2-252 GEN
Solar/Wind Harmer
2.261
960861AF2-377 GEN
50/50
3.377
970521AG2-332 GEN
50/50
16.09
24639705ELKHART HY
50/50
0.224
24727005RPMNG1
50/50
1.303
960791AF2-370 GEN
50/50
3.046
965011AG1-365 GEN
Solar/Wind Harmer
12.697
965651AG1-433 GEN
Solar/Wind Harmer
3.637
958861AF2-177 GEN
Solar/Wind Harmer
5.211
945371AF1-202 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
2.856
270063AE2-323 C
Solar/Wind Harmer
0.009
247521TR3_G114
Solar/Wind Harmer
0.369
270246TR4_N_V150
Solar/Wind Harmer
0.065
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.091
965031AG1-367 GEN
Solar/Wind Harmer
9.65
970825AG2-519 GEN
Solar/Wind Harmer
3.236
945111AF1-176 GEN
Solar/Wind Harmer
16.201
270505AE1-170 C O1
Solar/Wind Harmer
9.372
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.614
270032AE2-172
Solar/Wind Harmer
5.873
970291AG2-192 GEN
Solar/Wind Harmer
1.135
965421AG1-410 GEN
Solar/Wind Harmer
26.1
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.336
276903AD2-071 C
Solar/Wind Harmer
9.392
246936BC-WTG1
Solar/Wind Harmer
0.336
270489AE1-102 GEN1
Solar/Wind Harmer
1.076
970373AG2-245 GEN
Solar/Wind Harmer
16.85
247536S-71 GEN
Solar/Wind Harmer
0.321
270055AF2-134 C O1
Solar/Wind Harmer
0.006
274751CRETE EC ;1U
Adder
9.273
274754CRETE EC ;4U
Adder
9.273
274723RIVER EC ;12
Adder
20.057
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274812UNIV PK N;8U
Adder
5.56
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
10.061
276164X3-005 C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
9.237
274774LINCOLN ;5U
Adder
9.237
274801UNIV PARK;4U
Adder
6.373
970245AG2-165 GEN
Solar/Wind Harmer
3.303
276776AD2-060 GEN
Solar/Wind Harmer
0.795
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.471
274676JOLIET 29;8U
Adder
33.113
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
16.583
274732ELWOOD EC;7P
Adder
17.702
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.936
276691AA1-018 GEN1
Solar/Wind Harmer
0.895
274682WAUKEGAN ;7U
Adder
18.895
274828WAUKEGAN ;BP
Adder
11.599
24791305MDL-5G
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
5.451
276901AD2-066 C O1
Solar/Wind Harmer
0.007
962781AG1-127 GEN
Solar/Wind Harmer
6.91
274872LEEDK;1U
Solar/Wind Harmer
0.004
971997AH1-543 GEN
Solar/Wind Harmer
3.793
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.129
957471AF2-041 GEN
Solar/Wind Harmer
21.427
959081AF2-199 GEN
Solar/Wind Harmer
7.142
971067AG2-660 GEN
Solar/Wind Harmer
2.381
274822ROCKFORD ;11
Adder
20.032
972235AH1-702 GEN1
Adder
2.567
970569AG2-363 GEN
Solar/Wind Harmer
21.31
970819AG2-516 GEN
Solar/Wind Harmer
8.5
971475AH1-234 GEN
Solar/Wind Harmer
3.428
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.343
274766LEE CO EC;7U
Adder
9.233
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.232
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.645
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24728605AND G2
Adder
3.7
963741AG1-226 GEN
Solar/Wind Harmer
15.923
970773AG2-487 GEN
Solar/Wind Harmer
1.185
972175AH1-670 GEN
Solar/Wind Harmer
5.466
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.507
276615X2-022 GEN
Solar/Wind Harmer
0.067
965911AG1-460 GEN
Solar/Wind Harmer
1.231
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
3.324
241808AF1-120 C
Solar/Wind Harmer
0.001
241858AF1-205_GEN
Solar/Wind Harmer
1.342
241840AF1-064_GEN
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Helper
1.077
24729405KEY G3
50/50
0.729
24729305KEY G2
50/50
0.717
24729205KEY G1
50/50
0.713
970615AG2-402 GEN
50/50
4.232
247620Y3-023
50/50
0.687
970611AG2-400 GEN
Solar/Wind Harmer
12.697
970627AG2-408 GEN
Solar/Wind Harmer
3.809
944541AF1-119 GEN
Solar/Wind Harmer
0.831
960971AF2-388 GEN
Solar/Wind Harmer
7.274
942221AE2-234 GEN
Solar/Wind Harmer
0.055
270599AE1-208 GEN
Solar/Wind Harmer
9.209
270031AE2-169
Solar/Wind Harmer
5.525
270216AD2-079_GEN
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
9.138
970825AG2-519 GEN
Solar/Wind Harmer
10.102
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
17.858
961051AF2-396 GEN
Solar/Wind Harmer
11.905
971613AH1-306 GEN
Solar/Wind Harmer
4.228
964611AG1-324 GEN
Solar/Wind Harmer
0.65
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.561
965681AG1-436 GEN
Solar/Wind Harmer
10.414
965791AG1-447 GEN
Solar/Wind Harmer
7.637
247621Y3-024
Adder
0.286
246938BC-WTG3
Solar/Wind Harmer
0.3
246937BC-WTG2
Solar/Wind Harmer
0.336
270007AE1-245 C
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
274808UNIV PK N;4U
Adder
5.536
274803UNIV PARK;6U
Adder
6.395
274770LINCOLN ;1U
Adder
9.237
274771LINCOLN ;2U
Adder
9.237
970321AG2-212 GEN
Solar/Wind Harmer
3.303
274888KELLY CRK;1U
Solar/Wind Harmer
0.447
274887GEN-1.85
Solar/Wind Harmer
0.2
276843GEN-1.7
Solar/Wind Harmer
0.246
958011AF2-095 GEN
Solar/Wind Harmer
10.963
972259AH1-714 GEN
Adder
20.637
274674JOLIET 9 ;6U
Adder
16.583
970883AG2-550 GEN
Solar/Wind Harmer
7.476
970885AG2-551 GEN
Solar/Wind Harmer
2.492
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
958481AF2-142 GEN
Solar/Wind Harmer
11.087
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1
971573AH1-285 GEN
Solar/Wind Harmer
1.373
274695ROCKY RD ;2P
Adder
11.705
274693ROCKY RD ;1P
Adder
11.59
274697ROCKY RD ;3P
Adder
3.18
274696ROCKY RD ;4P
Adder
11.982
274683WAUKEGAN ;8U
Adder
22.127
274683WAUKEGAN ;8U
Adder
18.652
958491AF2-143 GEN
Solar/Wind Harmer
10.958
962691AG1-118 GEN
Solar/Wind Harmer
21.835
970921AG2-575 GEN
Solar/Wind Harmer
7.261
970921AG2-575 GEN
Solar/Wind Harmer
2.42
274879MINONK ;1U
Solar/Wind Harmer
0.306
942991AE2-321 GEN
Solar/Wind Harmer
8.062
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
14.365
971335AH1-147 GEN
Solar/Wind Harmer
14.365
971341AH1-150 GEN
Solar/Wind Harmer
14.285
971343AH1-151 GEN
Solar/Wind Harmer
14.285
274856ECOGROVE ;U1
Solar/Wind Harmer
0.167
276611AD2-172 GEN
Solar/Wind Harmer
0.002
966841AG1-555 GEN
Solar/Wind Harmer
0.798
938861AE1-114 GEN
Solar/Wind Harmer
3.985
274764LEE CO EC;5U
Adder
9.365
274765LEE CO EC;6U
Adder
9.365
274762LEE CO EC;3U
Adder
9.343
274763LEE CO EC;4U
Adder
9.255
276603SUBLETTE C
Solar/Wind Harmer
0
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.273
276646AC1-214 GEN2
Solar/Wind Harmer
0.273
972267AH1-718 GEN
Adder
4.143
276741O09 GEN1
Solar/Wind Harmer
0.247
276708O09 GEN2
Solar/Wind Harmer
0.247
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.261
970241AG2-163 GEN
Solar/Wind Harmer
3.925
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
6.577
276916AD2-100_GEN
Solar/Wind Harmer
12.826
276911AD2-131_GEN
Solar/Wind Harmer
0.845
970621AG2-405 GEN
Solar/Wind Harmer
1.049
24728805RICHG1
Adder
3.037
24728905RICHG2
Adder
3.037
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.833
970239AG2-162 GEN
Solar/Wind Harmer
1.162
241996AE2-282_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Helper
1.077
946101AF1-275 GEN
Solar/Wind Helper
0.301
24728705AND G3
Adder
7.738
24728505AND G1
Adder
3.7
965931AG1-462 GEN
Solar/Wind Harmer
17.128
270356AE2-297 GEN
Solar/Wind Harmer
0.009
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.985
276668AB2-070 GEN1
Solar/Wind Harmer
0.236
276621W2-048 GEN
Solar/Wind Harmer
0.321
276838X2-022 GEN2
Solar/Wind Harmer
0.358
970193AG2-126 GEN
Solar/Wind Harmer
9.285
942481AE2-261 GEN
Solar/Wind Harmer
18.401
270222AC2-111 GEN
Solar/Wind Harmer
2.367
970243AG2-164 GEN
Solar/Wind Harmer
2.719
970519AG2-331 GEN
Solar/Wind Harmer
12.086
970699AG2-449 GEN
Solar/Wind Harmer
1.162
270541AE2-072 C
Solar/Wind Harmer
0.005
241832AE2-181_GEN
Solar/Wind Harmer
0.001
958321AF2-126 GEN
Solar/Wind Harmer
0.444
971599AH1-298 GEN
50/50
20.218
24729505KEY G4
50/50
13.356
24727205RPMNG3
50/50
1.297
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
25.362
965101AG1-375 GEN
Solar/Wind Harmer
12.025
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
14.93
965041AG1-368 GEN
Solar/Wind Harmer
10.949
965051AG1-369 GEN
Solar/Wind Harmer
5.056
971609AH1-304 GEN
Solar/Wind Harmer
1.641
270024AE2-089 GEN
Solar/Wind Harmer
0.01
970115AG2-085 GEN
Solar/Wind Harmer
3.655
971771AH1-392 GEN
Solar/Wind Harmer
8.953
971619AH1-309 GEN
Solar/Wind Harmer
4.017
270594AE1-207 GEN
Solar/Wind Harmer
9.866
971347AH1-153 GEN
Solar/Wind Harmer
13.119
970289AG2-191 GEN
Solar/Wind Harmer
1.658
270240V3-007_GEN2
Solar/Wind Harmer
0.003
971769AH1-391 GEN
Solar/Wind Harmer
9.572
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.048
247607V1-011 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
16.964
270536AF1-215 GEN2
Solar/Wind Harmer
0.01
274814UNIV PK N;0U
Adder
5.609
274807UNIV PK N;3U
Adder
5.596
274805UNIV PK N;1U
Adder
5.572
274811UNIV PK N;7U
Adder
5.56
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.497
274775LINCOLN ;6U
Adder
9.237
274776LINCOLN ;7U
Adder
9.237
274777LINCOLN ;8U
Adder
9.237
960591AF2-350 GEN
Solar/Wind Harmer
7.613
972227AH1-698 GEN1
Adder
2.835
971611AH1-305 GEN
Solar/Wind Harmer
4.511
274687WILL CNTY;4U
Adder
30.235
274687WILL CNTY;4U
Adder
30.235
274675JOLIET 29;7U
Adder
33.113
274675JOLIET 29;7U
Adder
31.93
274728ELWOOD EC;5P
Adder
17.702
274731ELWOOD EC;2P
Adder
17.701
274733ELWOOD EC;3P
Adder
17.701
274735ELWOOD EC;4P
Adder
17.701
270543AE2-219 C
Solar/Wind Harmer
0.005
970833AG2-524 GEN
Solar/Wind Harmer
8.217
970833AG2-524 GEN
Solar/Wind Harmer
5.478
274746AC1-111 G10
Adder
5.936
274744AC1-111 GEN8
Adder
5.936
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
276868AE1-113 GEN
Solar/Wind Harmer
1.457
276882AE2-255 GEN
Solar/Wind Harmer
0.849
971177AH1-047 GEN
Solar/Wind Harmer
4.45
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971411AH1-196 GEN
Solar/Wind Harmer
10.784
971675AH1-338 GEN
Solar/Wind Harmer
2.801
971171AH1-044 GEN
Solar/Wind Harmer
14.285
274823ROCKFORD ;21
Adder
19.887
970169AG2-114 GEN
Solar/Wind Harmer
7.099
926823AC1-168 GEN
Solar/Wind Harmer
1.205
276612AE2-035 GEN
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
11.326
961011AF2-392 GEN
Solar/Wind Harmer
4.084
957751AF2-069 GEN
Solar/Wind Harmer
0.229
971029AG2-637 GEN
Solar/Wind Harmer
10.391
276655WTG1_EQ
Solar/Wind Harmer
0.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.234
941731AE2-173 GEN
Solar/Wind Harmer
5.741
963841AG1-237 GEN
Solar/Wind Harmer
2.984
946321AF1-296 GEN
Solar/Wind Harmer
3.782
971673AH1-337 GEN
Solar/Wind Harmer
4.373
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.236
276848AB2-070 GEN3
Solar/Wind Harmer
0.235
944221AF1-090 GEN
Solar/Wind Harmer
3.489
270297AD1-101 GEN
Solar/Wind Harmer
0.001
945411AF1-206 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
0.778
270284AF1-227 GEN1
Solar/Wind Helper
1.167
270286AF1-227 GEN2
Solar/Wind Helper
0.428
270287AF1-227 GEN3
Solar/Wind Helper
0.428
270520AE2-214 GEN
Solar/Wind Helper
2.4
944201AF1-088_MTX
Adder
87.117
957141AF2-008_MTX
Adder
29.672
990792J1392
External Queue
6.540774822235107
991297J1743
External Queue
3.431180715560913
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.288
MECLTFEXP_MEC->PJM
CLTF
14.414
SIGELTFEXP_SIGE->PJM
CLTF
0.332
LAGNLTFEXP_LAGN->PJM
CLTF
8.301
TVALTFEXP_TVA->PJM
CLTF
3.284
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.901
NYPJM->LTFIMP_NY
CLTF
2
LGEELTFEXP_LGEE->PJM
CLTF
3.227
WECLTFEXP_WEC->PJM
CLTF
3.885
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.257
AH1-155LTFEXP_AH1-155->PJM
LTF
0.385

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.19 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6914.12
MW Contribution:62.69
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.827
270144AC1-141 ST1_
50/50
4.726
24643105BUCHANAN
50/50
0.028
24344005CKG1
50/50
14.627
270142AC1-141 CT1_
50/50
5.336
24641605TWIN BRNCH
50/50
0.039
24642205MAYFLWER
50/50
1.492
274772LINCOLN ;3U
50/50
14.464
970513AG2-328 GEN
Solar/Wind Harmer
43.637
970517AG2-330 GEN
Solar/Wind Harmer
39.578
970349AG2-230 GEN
Solar/Wind Harmer
35.693
247643Z2-116 C
Solar/Wind Harmer
0.155
270043AE2-236 GEN
Solar/Wind Harmer
12.097
945111AF1-176 GEN
Solar/Wind Harmer
12.392
274724RIVER EC ;11
Adder
38.445
972231SS25-0005
Solar/Wind Harmer
20.573
972181SS23-001
Solar/Wind Harmer
12.858
274752CRETE EC ;2U
Adder
10.596
274753CRETE EC ;3U
Adder
10.596
270535AF1-215 GEN1
Solar/Wind Harmer
9.847
970707AG2-453 GEN
Solar/Wind Harmer
60.348
274802UNIV PARK;5U
Adder
12.517
274826FISK ;BP
Adder
23.497
276772AC2-154 GEN
Solar/Wind Harmer
5.984
276806AD2-047 C O1
Solar/Wind Harmer
22.954
970941AG2-585 GEN
Solar/Wind Harmer
26.822
972228AH1-698 GEN2
Adder
7.946
270102X2-052 ST
50/50
3.618
270100X2-052 CT1
50/50
3.334
270101X2-052 CT2
50/50
3.334
274770LINCOLN ;1U
50/50
14.464
274771LINCOLN ;2U
50/50
14.464
970321AG2-212 GEN
Solar/Wind Harmer
43.637
965681AG1-436 GEN
Solar/Wind Harmer
28.105
965791AG1-447 GEN
Solar/Wind Harmer
14.379
270526AF1-158 GEN
Solar/Wind Harmer
10.145
24441505OLIV SLR
Solar/Wind Harmer
0.299
270216AD2-079_GEN
Solar/Wind Harmer
1.343
957891AF2-083 GEN
Solar/Wind Harmer
7.428
960981AF2-389 GEN
Solar/Wind Harmer
3.328
961051AF2-396 GEN
Solar/Wind Harmer
34.696
961051AF2-396 GEN
Solar/Wind Harmer
16.138
247620Y3-023
Adder
0.995
274808UNIV PK N;4U
Adder
10.755
972259AH1-714 GEN
Adder
40.962
274803UNIV PARK;6U
Adder
12.517
274888KELLY CRK;1U
Solar/Wind Harmer
12.668
274887GEN-1.85
Solar/Wind Harmer
11.437
276843GEN-1.7
Solar/Wind Harmer
1.231
958011AF2-095 GEN
Solar/Wind Harmer
30.899
274674JOLIET 9 ;6U
Adder
32.718
274847GR RIDGE ;BU
Solar/Wind Harmer
10.728
971573AH1-285 GEN
Solar/Wind Harmer
18.045
970239AG2-162 GEN
Solar/Wind Harmer
22.993
958481AF2-142 GEN
Solar/Wind Harmer
31.243
945421AF1-207 GEN
Solar/Wind Harmer
29.246
957841AF2-078 GEN
Solar/Wind Harmer
12.586
274695ROCKY RD ;2P
Adder
23.176
274693ROCKY RD ;1P
Adder
22.948
274697ROCKY RD ;3P
Adder
6.296
274861TOP CROP ;1U
Solar/Wind Harmer
12.614
274862TOP CROP ;2U
Solar/Wind Harmer
10.533
274696ROCKY RD ;4P
Adder
23.723
274683WAUKEGAN ;8U
Adder
43.726
274683WAUKEGAN ;8U
Adder
36.859
274775LINCOLN ;6U
50/50
14.464
962691AG1-118 GEN
Solar/Wind Harmer
61.999
970921AG2-575 GEN
Solar/Wind Harmer
20.614
970921AG2-575 GEN
Solar/Wind Harmer
4.794
958491AF2-143 GEN
Solar/Wind Harmer
30.883
274879MINONK ;1U
Solar/Wind Harmer
13.83
942991AE2-321 GEN
Solar/Wind Harmer
20.456
971333AH1-146 GEN
Solar/Wind Harmer
40.697
971335AH1-147 GEN
Solar/Wind Harmer
40.697
276872AE1-163_GEN1
Solar/Wind Harmer
13.606
274764LEE CO EC;5U
Adder
18.47
274765LEE CO EC;6U
Adder
18.47
274762LEE CO EC;3U
Adder
18.426
274763LEE CO EC;4U
Adder
18.253
972267AH1-718 GEN
Adder
8.164
270471AD2-092_GEN
Solar/Wind Helper
1.574
971341AH1-150 GEN
Solar/Wind Harmer
0.703
971343AH1-151 GEN
Solar/Wind Harmer
0.703
24344105CKG2
50/50
18.684
270143AC1-141 CT2_
50/50
5.336
274773LINCOLN ;4U
50/50
14.464
274774LINCOLN ;5U
50/50
14.464
24639705ELKHART HY
50/50
0.356
970245AG2-165 GEN
Solar/Wind Harmer
43.637
270505AE1-170 C O1
Solar/Wind Harmer
33.093
972207SS24-0001
Solar/Wind Harmer
48.463
970373AG2-245 GEN
Solar/Wind Harmer
46.063
945111AF1-176 GEN
Solar/Wind Harmer
39.1
270449AD2-020 GEN
Solar/Wind Harmer
6.117
943021AE2-325 GEN
Solar/Wind Harmer
7.949
274723RIVER EC ;12
Adder
38.895
274751CRETE EC ;1U
Adder
10.596
274754CRETE EC ;4U
Adder
10.596
270055AF2-134 C O1
Solar/Wind Harmer
6.564
276164X3-005 C
Solar/Wind Harmer
1.52
274812UNIV PK N;8U
Adder
10.802
276776AD2-060 GEN
Solar/Wind Harmer
0.907
274801UNIV PARK;4U
Adder
12.503
958381AF2-132 GEN
Solar/Wind Harmer
19.452
964861AG1-349 GEN
Solar/Wind Harmer
16.835
971917AH1-482 GEN
Solar/Wind Harmer
19.427
941551AE2-152 GEN
Solar/Wind Harmer
9.695
274676JOLIET 29;8U
Adder
65.284
274674JOLIET 9 ;6U
Adder
32.718
274732ELWOOD EC;7P
Adder
34.908
270063AE2-323 C
Solar/Wind Harmer
4.678
274871GR RIDGE ;2U
Solar/Wind Harmer
16.309
940581AE2-045 GEN
Solar/Wind Harmer
21.545
971605AH1-302 GEN
Solar/Wind Harmer
18.424
274745AC1-111 GEN9
Adder
11.776
970333AG2-219 GEN
Solar/Wind Harmer
65.98
276691AA1-018 GEN1
Solar/Wind Harmer
0.97
274682WAUKEGAN ;7U
Adder
37.343
274828WAUKEGAN ;BP
Adder
22.921
939401AE1-172 GEN
Solar/Wind Harmer
28.837
960751AF2-366 GEN
Solar/Wind Harmer
5.914
962781AG1-127 GEN
Solar/Wind Harmer
19.604
276901AD2-066 C O1
Solar/Wind Harmer
7.228
274872LEEDK;1U
Solar/Wind Harmer
16.893
24791305MDL-5G
Solar/Wind Harmer
4.944
971997AH1-543 GEN
Solar/Wind Harmer
32.241
276861AD2-134 GEN
Solar/Wind Harmer
3.637
276876AE1-163_GEN2
Solar/Wind Harmer
13.606
274822ROCKFORD ;11
Adder
39.558
972235AH1-702 GEN1
Adder
5.068
274761LEE CO EC;2U
Adder
18.426
274766LEE CO EC;7U
Adder
18.209
970091AG2-072 GEN
Adder
143.374
270349AD2-093_GEN
Solar/Wind Helper
1.574
957471AF2-041 GEN
Solar/Wind Harmer
1.055
959081AF2-199 GEN
Solar/Wind Harmer
0.352
971067AG2-660 GEN
Solar/Wind Harmer
0.082
274800UNIV PARK;3U
Adder
12.503
972038AH1-567 GEN2
Adder
0.783
24441205WTRV SLR C
Solar/Wind Harmer
0.289
964401AG1-302 GEN
Solar/Wind Harmer
19.452
276897AD1-100 C
Solar/Wind Harmer
62.038
939351AE1-166 GEN
Solar/Wind Harmer
12.676
274676JOLIET 29;8U
Adder
62.953
247604X1-042
Adder
0.885
274729ELWOOD EC;1P
Adder
34.908
274730ELWOOD EC;6P
Adder
34.908
274734ELWOOD EC;8P
Adder
34.908
274736ELWOOD EC;9P
Adder
34.908
959141AF2-205 GEN
Solar/Wind Harmer
12.838
276893AG1-478 C
Solar/Wind Harmer
0.886
943121AE2-341 GEN
Solar/Wind Harmer
31.655
943591AF1-030 GEN
Solar/Wind Harmer
21.103
970243AG2-164 GEN
Solar/Wind Harmer
53.983
970519AG2-331 GEN
Solar/Wind Harmer
36.268
970699AG2-449 GEN
Solar/Wind Harmer
23.993
970031AG2-029 GEN
Solar/Wind Harmer
62.689
276694AA1-018 GEN2
Solar/Wind Harmer
13.144
274682WAUKEGAN ;7U
Adder
37.343
276805AD2-038 GEN
Solar/Wind Harmer
10.562
274872LEEDK;1U
Solar/Wind Harmer
0.526
24755605MDL-5G
Solar/Wind Harmer
4.944
970781AG2-491 GEN
Solar/Wind Harmer
20.497
276799AD1-013 GEN
Solar/Wind Harmer
4.505
946671AF1-331 GEN
Solar/Wind Harmer
0.853
274855GSG-6 ;RU
Solar/Wind Harmer
7.52
274850MENDOTA H;RU
Solar/Wind Harmer
5.229
276602WESTBROOK C
Solar/Wind Harmer
4.329
276863AD2-134 GEN
Solar/Wind Harmer
3.637
276889AE2-281 GEN
Solar/Wind Harmer
3.888
972236AH1-702 GEN2
Adder
4.407
274760LEE CO EC;1U
Adder
18.426
274767LEE CO EC;8U
Adder
18.209
959091AF2-200 GEN
Solar/Wind Harmer
0.703
274776LINCOLN ;7U
50/50
14.464
274777LINCOLN ;8U
50/50
14.464
971347AH1-153 GEN
Solar/Wind Harmer
35.693
960681AF2-359 GEN
Solar/Wind Harmer
8.494
971771AH1-392 GEN
Solar/Wind Harmer
20.116
971769AH1-391 GEN
Solar/Wind Harmer
22.322
270071AF1-092 GEN
Solar/Wind Harmer
32.714
944161AF1-084 GEN
Solar/Wind Harmer
4.796
270536AF1-215 GEN2
Solar/Wind Harmer
9.847
274814UNIV PK N;0U
Adder
10.897
274807UNIV PK N;3U
Adder
10.873
274805UNIV PK N;1U
Adder
10.826
274811UNIV PK N;7U
Adder
10.802
972037AH1-567 GEN1
Adder
0.393
274827FISK ;RP
Adder
16.653
960591AF2-350 GEN
Solar/Wind Harmer
21.457
972227AH1-698 GEN1
Adder
5.595
958391AF2-133 GEN
Solar/Wind Harmer
19.344
274687WILL CNTY;4U
Adder
59.525
274687WILL CNTY;4U
Adder
59.525
274675JOLIET 29;7U
Adder
65.285
274675JOLIET 29;7U
Adder
62.954
274731ELWOOD EC;2P
Adder
34.908
274733ELWOOD EC;3P
Adder
34.908
274735ELWOOD EC;4P
Adder
34.908
274728ELWOOD EC;5P
Adder
34.908
970833AG2-524 GEN
Solar/Wind Harmer
18.525
970833AG2-524 GEN
Solar/Wind Harmer
8.616
274746AC1-111 G10
Adder
11.776
274744AC1-111 GEN8
Adder
11.776
24690905MDL-1G C
Solar/Wind Harmer
16.46
270180AB1-006 GEN1
Solar/Wind Harmer
14.745
946581AF1-322 GEN
Solar/Wind Harmer
20.975
24691005MDL-2G C
Solar/Wind Harmer
7.582
24697605MDL-3G C
Solar/Wind Harmer
7.558
24697905MDL-4G C
Solar/Wind Harmer
4.705
270181AB1-006 GEN2
Solar/Wind Harmer
1.466
276868AE1-113 GEN
Solar/Wind Harmer
20.743
276882AE2-255 GEN
Solar/Wind Harmer
6.915
971177AH1-047 GEN
Solar/Wind Harmer
11.982
274863CRW1-WTG
Solar/Wind Harmer
11.396
274864CRW2-WTG
Solar/Wind Harmer
11.396
971675AH1-338 GEN
Solar/Wind Harmer
36.661
971411AH1-196 GEN
Solar/Wind Harmer
30.544
274823ROCKFORD ;21
Adder
39.271
24729505KEY G4
Adder
12.781
270054AF2-122 C O1
Solar/Wind Helper
1.198
971171AH1-044 GEN
Solar/Wind Harmer
0.703
944201AF1-088_MTX
Adder
194.417
957141AF2-008_MTX
Adder
28.027
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.655
CBM West 1LTFEXP_CBM-W1->PJM
CBM
232.718
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.494
MECLTFEXP_MEC->PJM
CLTF
27.999
SIGELTFEXP_SIGE->PJM
CLTF
0.538
LAGNLTFEXP_LAGN->PJM
CLTF
14.568
TVALTFEXP_TVA->PJM
CLTF
5.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
137.493
NYPJM->LTFIMP_NY
CLTF
3.58
LGEELTFEXP_LGEE->PJM
CLTF
4.109
WECLTFEXP_WEC->PJM
CLTF
7.66
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.418
AG2-052LTFEXP_AG2-052->PJM
LTF
0.484
AH1-155LTFEXP_AH1-155->PJM
LTF
0.727

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6359.91
MW Contribution:62.78
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.9
270144AC1-141 ST1_
50/50
4.729
24643105BUCHANAN
50/50
0.028
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
35.714
960681AF2-359 GEN
Solar/Wind Harmer
8.455
971771AH1-392 GEN
Solar/Wind Harmer
20.095
971769AH1-391 GEN
Solar/Wind Harmer
22.253
270071AF1-092 GEN
Solar/Wind Harmer
32.895
944161AF1-084 GEN
Solar/Wind Harmer
4.798
274775LINCOLN ;6U
Adder
13.446
274776LINCOLN ;7U
Adder
13.446
274777LINCOLN ;8U
Adder
13.446
270536AF1-215 GEN2
Solar/Wind Harmer
9.745
274814UNIV PK N;0U
Adder
10.744
274807UNIV PK N;3U
Adder
10.721
274805UNIV PK N;1U
Adder
10.674
274811UNIV PK N;7U
Adder
10.651
972037AH1-567 GEN1
Adder
0.387
274827FISK ;RP
Adder
16.398
960591AF2-350 GEN
Solar/Wind Harmer
21.113
972227AH1-698 GEN1
Adder
5.503
958391AF2-133 GEN
Solar/Wind Harmer
19.092
274687WILL CNTY;4U
Adder
58.542
274687WILL CNTY;4U
Adder
58.542
274675JOLIET 29;7U
Adder
64.194
274675JOLIET 29;7U
Adder
61.901
274731ELWOOD EC;2P
Adder
34.297
274733ELWOOD EC;3P
Adder
34.297
274735ELWOOD EC;4P
Adder
34.297
274728ELWOOD EC;5P
Adder
34.297
970833AG2-524 GEN
Solar/Wind Harmer
18.19
970833AG2-524 GEN
Solar/Wind Harmer
8.46
274746AC1-111 G10
Adder
11.564
274744AC1-111 GEN8
Adder
11.564
276868AE1-113 GEN
Solar/Wind Harmer
20.269
276882AE2-255 GEN
Solar/Wind Harmer
6.757
971177AH1-047 GEN
Solar/Wind Harmer
11.733
24690905MDL-1G C
Solar/Wind Harmer
16.067
270180AB1-006 GEN1
Solar/Wind Harmer
14.393
946581AF1-322 GEN
Solar/Wind Harmer
20.475
24691005MDL-2G C
Solar/Wind Harmer
7.401
24697605MDL-3G C
Solar/Wind Harmer
7.378
24697905MDL-4G C
Solar/Wind Harmer
4.593
270181AB1-006 GEN2
Solar/Wind Harmer
1.431
971411AH1-196 GEN
Solar/Wind Harmer
29.896
971675AH1-338 GEN
Solar/Wind Harmer
35.874
24729505KEY G4
Adder
12.834
274823ROCKFORD ;21
Adder
38.397
270102X2-052 ST
50/50
3.606
270100X2-052 CT1
50/50
3.322
270101X2-052 CT2
50/50
3.322
970321AG2-212 GEN
Solar/Wind Harmer
44.073
970239AG2-162 GEN
Solar/Wind Harmer
24.863
965681AG1-436 GEN
Solar/Wind Harmer
27.976
965791AG1-447 GEN
Solar/Wind Harmer
14.313
270526AF1-158 GEN
Solar/Wind Harmer
10.118
24441505OLIV SLR
Solar/Wind Harmer
0.298
270216AD2-079_GEN
Solar/Wind Harmer
1.344
957891AF2-083 GEN
Solar/Wind Harmer
7.429
960981AF2-389 GEN
Solar/Wind Harmer
3.328
961051AF2-396 GEN
Solar/Wind Harmer
34.708
961051AF2-396 GEN
Solar/Wind Harmer
16.143
274770LINCOLN ;1U
Adder
13.446
274771LINCOLN ;2U
Adder
13.446
247620Y3-023
Adder
0.996
274808UNIV PK N;4U
Adder
10.604
274803UNIV PARK;6U
Adder
12.325
972259AH1-714 GEN
Adder
40.299
274888KELLY CRK;1U
Solar/Wind Harmer
12.465
274887GEN-1.85
Solar/Wind Harmer
11.254
276843GEN-1.7
Solar/Wind Harmer
1.211
958011AF2-095 GEN
Solar/Wind Harmer
30.403
274674JOLIET 9 ;6U
Adder
32.155
274847GR RIDGE ;BU
Solar/Wind Harmer
10.533
971573AH1-285 GEN
Solar/Wind Harmer
17.714
945421AF1-207 GEN
Solar/Wind Harmer
28.747
957841AF2-078 GEN
Solar/Wind Harmer
12.371
274695ROCKY RD ;2P
Adder
22.735
274693ROCKY RD ;1P
Adder
22.511
274697ROCKY RD ;3P
Adder
6.176
274696ROCKY RD ;4P
Adder
23.271
958481AF2-142 GEN
Solar/Wind Harmer
30.611
274861TOP CROP ;1U
Solar/Wind Harmer
12.359
274862TOP CROP ;2U
Solar/Wind Harmer
10.32
274683WAUKEGAN ;8U
Adder
42.888
274683WAUKEGAN ;8U
Adder
36.153
962691AG1-118 GEN
Solar/Wind Harmer
60.767
970921AG2-575 GEN
Solar/Wind Harmer
20.199
970921AG2-575 GEN
Solar/Wind Harmer
4.697
958491AF2-143 GEN
Solar/Wind Harmer
30.201
942991AE2-321 GEN
Solar/Wind Harmer
20.031
274879MINONK ;1U
Solar/Wind Harmer
13.514
274764LEE CO EC;5U
Adder
18.019
274765LEE CO EC;6U
Adder
18.019
274762LEE CO EC;3U
Adder
17.977
274763LEE CO EC;4U
Adder
17.808
972267AH1-718 GEN
Adder
7.955
247621Y3-024
Adder
0.32
270471AD2-092_GEN
Solar/Wind Helper
1.53
971333AH1-146 GEN
Solar/Wind Harmer
33.502
971335AH1-147 GEN
Solar/Wind Harmer
33.502
24344105CKG2
50/50
18.741
270143AC1-141 CT2_
50/50
5.339
24639705ELKHART HY
50/50
0.356
970521AG2-332 GEN
50/50
25.327
24307105BERRINSP G
50/50
0.047
970245AG2-165 GEN
Solar/Wind Harmer
44.073
970333AG2-219 GEN
Solar/Wind Harmer
71.347
270505AE1-170 C O1
Solar/Wind Harmer
33.103
945111AF1-176 GEN
Solar/Wind Harmer
39.113
270449AD2-020 GEN
Solar/Wind Harmer
6.12
943021AE2-325 GEN
Solar/Wind Harmer
7.951
970373AG2-245 GEN
Solar/Wind Harmer
45.678
972207SS24-0001
Solar/Wind Harmer
47.808
274773LINCOLN ;4U
Adder
13.446
274774LINCOLN ;5U
Adder
13.446
270055AF2-134 C O1
Solar/Wind Harmer
6.496
274723RIVER EC ;12
Adder
38.388
274751CRETE EC ;1U
Adder
10.462
274754CRETE EC ;4U
Adder
10.462
276164X3-005 C
Solar/Wind Harmer
1.498
270063AE2-323 C
Solar/Wind Harmer
4.686
274812UNIV PK N;8U
Adder
10.651
958381AF2-132 GEN
Solar/Wind Harmer
19.217
964861AG1-349 GEN
Solar/Wind Harmer
16.628
971917AH1-482 GEN
Solar/Wind Harmer
19.189
276776AD2-060 GEN
Solar/Wind Harmer
0.893
274801UNIV PARK;4U
Adder
12.307
941551AE2-152 GEN
Solar/Wind Harmer
9.522
274676JOLIET 29;8U
Adder
64.193
274674JOLIET 9 ;6U
Adder
32.155
274732ELWOOD EC;7P
Adder
34.297
274871GR RIDGE ;2U
Solar/Wind Harmer
16.013
940581AE2-045 GEN
Solar/Wind Harmer
21.231
971605AH1-302 GEN
Solar/Wind Harmer
18.155
274745AC1-111 GEN9
Adder
11.564
276691AA1-018 GEN1
Solar/Wind Harmer
0.95
274682WAUKEGAN ;7U
Adder
36.631
274828WAUKEGAN ;BP
Adder
22.481
960751AF2-366 GEN
Solar/Wind Harmer
5.795
962781AG1-127 GEN
Solar/Wind Harmer
19.209
939401AE1-172 GEN
Solar/Wind Harmer
28.102
274872LEEDK;1U
Solar/Wind Harmer
16.548
276901AD2-066 C O1
Solar/Wind Harmer
7.062
24791305MDL-5G
Solar/Wind Harmer
4.826
971997AH1-543 GEN
Solar/Wind Harmer
31.477
276861AD2-134 GEN
Solar/Wind Harmer
3.559
274822ROCKFORD ;11
Adder
38.678
972235AH1-702 GEN1
Adder
4.954
274761LEE CO EC;2U
Adder
17.977
274766LEE CO EC;7U
Adder
17.765
24728605AND G2
Adder
5.044
970091AG2-072 GEN
Adder
4.904
270349AD2-093_GEN
Solar/Wind Helper
1.53
24344005CKG1
50/50
14.639
270142AC1-141 CT1_
50/50
5.339
24641605TWIN BRNCH
50/50
0.039
24642205MAYFLWER
50/50
1.49
944961AF1-161 GEN
50/50
6.347
962601AG1-109 GEN
50/50
6.347
970513AG2-328 GEN
Solar/Wind Harmer
44.073
970517AG2-330 GEN
Solar/Wind Harmer
39.973
970349AG2-230 GEN
Solar/Wind Harmer
35.714
970243AG2-164 GEN
Solar/Wind Harmer
58.375
970519AG2-331 GEN
Solar/Wind Harmer
39.218
970699AG2-449 GEN
Solar/Wind Harmer
25.944
247643Z2-116 C
Solar/Wind Harmer
0.155
270043AE2-236 GEN
Solar/Wind Harmer
12.133
945111AF1-176 GEN
Solar/Wind Harmer
12.396
274772LINCOLN ;3U
Adder
13.446
24441205WTRV SLR C
Solar/Wind Harmer
0.289
270535AF1-215 GEN1
Solar/Wind Harmer
9.745
274724RIVER EC ;11
Adder
37.943
972231SS25-0005
Solar/Wind Harmer
20.313
972181SS23-001
Solar/Wind Harmer
12.696
274752CRETE EC ;2U
Adder
10.462
274753CRETE EC ;3U
Adder
10.462
247604X1-042
Adder
0.885
970707AG2-453 GEN
Solar/Wind Harmer
59.407
964401AG1-302 GEN
Solar/Wind Harmer
19.217
274802UNIV PARK;5U
Adder
12.325
274826FISK ;BP
Adder
23.138
276772AC2-154 GEN
Solar/Wind Harmer
5.888
276806AD2-047 C O1
Solar/Wind Harmer
22.586
970941AG2-585 GEN
Solar/Wind Harmer
26.392
274800UNIV PARK;3U
Adder
12.307
972038AH1-567 GEN2
Adder
0.77
972228AH1-698 GEN2
Adder
7.816
276897AD1-100 C
Solar/Wind Harmer
60.93
939351AE1-166 GEN
Solar/Wind Harmer
12.45
959141AF2-205 GEN
Solar/Wind Harmer
12.662
970031AG2-029 GEN
Solar/Wind Harmer
62.778
274676JOLIET 29;8U
Adder
61.9
274729ELWOOD EC;1P
Adder
34.297
274730ELWOOD EC;6P
Adder
34.297
274734ELWOOD EC;8P
Adder
34.297
274736ELWOOD EC;9P
Adder
34.297
276893AG1-478 C
Solar/Wind Harmer
0.871
943121AE2-341 GEN
Solar/Wind Harmer
31.095
943591AF1-030 GEN
Solar/Wind Harmer
20.73
276694AA1-018 GEN2
Solar/Wind Harmer
12.879
274682WAUKEGAN ;7U
Adder
36.631
944531AF1-118 GEN
Solar/Wind Harmer
70.934
274872LEEDK;1U
Solar/Wind Harmer
0.515
276805AD2-038 GEN
Solar/Wind Harmer
10.329
24755605MDL-5G
Solar/Wind Harmer
4.826
970781AG2-491 GEN
Solar/Wind Harmer
20.008
276799AD1-013 GEN
Solar/Wind Harmer
4.408
946671AF1-331 GEN
Solar/Wind Harmer
0.835
274855GSG-6 ;RU
Solar/Wind Harmer
7.359
274850MENDOTA H;RU
Solar/Wind Harmer
5.117
276602WESTBROOK C
Solar/Wind Harmer
4.236
276863AD2-134 GEN
Solar/Wind Harmer
3.559
972236AH1-702 GEN2
Adder
4.308
274760LEE CO EC;1U
Adder
17.977
274767LEE CO EC;8U
Adder
17.765
24728705AND G3
Adder
10.55
24728505AND G1
Adder
5.044
944201AF1-088_MTX
Adder
146.322
957141AF2-008_MTX
Adder
73.161
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.633
CBM West 1LTFEXP_CBM-W1->PJM
CBM
228.49
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.819
MECLTFEXP_MEC->PJM
CLTF
26.916
SIGELTFEXP_SIGE->PJM
CLTF
0.505
LAGNLTFEXP_LAGN->PJM
CLTF
13.672
TVALTFEXP_TVA->PJM
CLTF
5.007
CBM West 2LTFEXP_CBM-W2->PJM
CBM
127.851
NYPJM->LTFIMP_NY
CLTF
3.427
LGEELTFEXP_LGEE->PJM
CLTF
4.47
WECLTFEXP_WEC->PJM
CLTF
7.49
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.475
AH1-155LTFEXP_AH1-155->PJM
LTF
0.712

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.88 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6345.03
MW Contribution:58.98
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
17.375
270143AC1-141 CT2_
50/50
4.968
24639705ELKHART HY
50/50
0.332
274773LINCOLN ;4U
50/50
13.384
274774LINCOLN ;5U
50/50
13.384
970521AG2-332 GEN
50/50
23.621
970245AG2-165 GEN
Solar/Wind Harmer
39.594
270505AE1-170 C O1
Solar/Wind Harmer
30.803
945111AF1-176 GEN
Solar/Wind Harmer
36.413
972207SS24-0001
Solar/Wind Harmer
44.846
270449AD2-020 GEN
Solar/Wind Harmer
5.693
943021AE2-325 GEN
Solar/Wind Harmer
7.398
274723RIVER EC ;12
Adder
35.977
970373AG2-245 GEN
Solar/Wind Harmer
42.088
274751CRETE EC ;1U
Adder
9.796
274754CRETE EC ;4U
Adder
9.796
276164X3-005 C
Solar/Wind Harmer
1.405
270063AE2-323 C
Solar/Wind Harmer
4.395
274812UNIV PK N;8U
Adder
9.987
276776AD2-060 GEN
Solar/Wind Harmer
0.839
274801UNIV PARK;4U
Adder
11.561
941551AE2-152 GEN
Solar/Wind Harmer
8.961
270055AF2-134 C O1
Solar/Wind Harmer
5.968
274676JOLIET 29;8U
Adder
60.37
274674JOLIET 9 ;6U
Adder
30.252
274732ELWOOD EC;7P
Adder
32.272
274871GR RIDGE ;2U
Solar/Wind Harmer
15.077
274745AC1-111 GEN9
Adder
10.891
958381AF2-132 GEN
Solar/Wind Harmer
17.606
964861AG1-349 GEN
Solar/Wind Harmer
15.23
971917AH1-482 GEN
Solar/Wind Harmer
17.576
276691AA1-018 GEN1
Solar/Wind Harmer
0.896
274682WAUKEGAN ;7U
Adder
34.537
274828WAUKEGAN ;BP
Adder
21.199
939401AE1-172 GEN
Solar/Wind Harmer
26.601
960751AF2-366 GEN
Solar/Wind Harmer
5.47
962781AG1-127 GEN
Solar/Wind Harmer
18.131
274872LEEDK;1U
Solar/Wind Harmer
15.624
940581AE2-045 GEN
Solar/Wind Harmer
19.376
276901AD2-066 C O1
Solar/Wind Harmer
6.676
971605AH1-302 GEN
Solar/Wind Harmer
16.569
971997AH1-543 GEN
Solar/Wind Harmer
29.779
276861AD2-134 GEN
Solar/Wind Harmer
3.363
957471AF2-041 GEN
Solar/Wind Harmer
56.132
959081AF2-199 GEN
Solar/Wind Harmer
18.711
971067AG2-660 GEN
Solar/Wind Harmer
4.351
276876AE1-163_GEN2
Solar/Wind Harmer
12.566
274822ROCKFORD ;11
Adder
36.587
972235AH1-702 GEN1
Adder
4.687
274761LEE CO EC;2U
Adder
17.04
274766LEE CO EC;7U
Adder
16.84
970091AG2-072 GEN
Adder
32.358
270349AD2-093_GEN
Solar/Wind Helper
1.555
24344005CKG1
50/50
13.598
270142AC1-141 CT1_
50/50
4.968
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.387
274772LINCOLN ;3U
50/50
13.384
970513AG2-328 GEN
Solar/Wind Harmer
39.594
970517AG2-330 GEN
Solar/Wind Harmer
35.91
970349AG2-230 GEN
Solar/Wind Harmer
33.197
270043AE2-236 GEN
Solar/Wind Harmer
11.487
247643Z2-116 C
Solar/Wind Harmer
0.144
945111AF1-176 GEN
Solar/Wind Harmer
11.54
274724RIVER EC ;11
Adder
35.562
972231SS25-0005
Solar/Wind Harmer
19.02
972181SS23-001
Solar/Wind Harmer
11.887
274752CRETE EC ;2U
Adder
9.796
274753CRETE EC ;3U
Adder
9.796
24441205WTRV SLR C
Solar/Wind Harmer
0.269
970707AG2-453 GEN
Solar/Wind Harmer
55.829
274802UNIV PARK;5U
Adder
11.574
274826FISK ;BP
Adder
21.73
276772AC2-154 GEN
Solar/Wind Harmer
5.533
276806AD2-047 C O1
Solar/Wind Harmer
21.223
970941AG2-585 GEN
Solar/Wind Harmer
24.799
972228AH1-698 GEN2
Adder
7.346
274800UNIV PARK;3U
Adder
11.561
972038AH1-567 GEN2
Adder
0.724
276897AD1-100 C
Solar/Wind Harmer
57.337
939351AE1-166 GEN
Solar/Wind Harmer
11.715
247604X1-042
Adder
0.823
270535AF1-215 GEN1
Solar/Wind Harmer
8.953
274676JOLIET 29;8U
Adder
58.214
970031AG2-029 GEN
Solar/Wind Harmer
58.977
274729ELWOOD EC;1P
Adder
32.272
274730ELWOOD EC;6P
Adder
32.272
274734ELWOOD EC;8P
Adder
32.272
274736ELWOOD EC;9P
Adder
32.272
276893AG1-478 C
Solar/Wind Harmer
0.82
944531AF1-118 GEN
Solar/Wind Harmer
68.666
943121AE2-341 GEN
Solar/Wind Harmer
29.28
943591AF1-030 GEN
Solar/Wind Harmer
19.52
964401AG1-302 GEN
Solar/Wind Harmer
17.606
276694AA1-018 GEN2
Solar/Wind Harmer
12.147
274682WAUKEGAN ;7U
Adder
34.537
959141AF2-205 GEN
Solar/Wind Harmer
11.571
276805AD2-038 GEN
Solar/Wind Harmer
9.758
274872LEEDK;1U
Solar/Wind Harmer
0.487
276799AD1-013 GEN
Solar/Wind Harmer
4.166
946671AF1-331 GEN
Solar/Wind Harmer
0.789
274855GSG-6 ;RU
Solar/Wind Harmer
6.955
270102X2-052 ST
50/50
3.346
270100X2-052 CT1
50/50
3.083
270101X2-052 CT2
50/50
3.083
274770LINCOLN ;1U
50/50
13.384
274771LINCOLN ;2U
50/50
13.384
970321AG2-212 GEN
Solar/Wind Harmer
39.594
965681AG1-436 GEN
Solar/Wind Harmer
25.984
965791AG1-447 GEN
Solar/Wind Harmer
13.294
270526AF1-158 GEN
Solar/Wind Harmer
9.408
24441505OLIV SLR
Solar/Wind Harmer
0.277
270216AD2-079_GEN
Solar/Wind Harmer
1.252
957891AF2-083 GEN
Solar/Wind Harmer
6.914
960981AF2-389 GEN
Solar/Wind Harmer
3.098
961051AF2-396 GEN
Solar/Wind Harmer
32.298
961051AF2-396 GEN
Solar/Wind Harmer
15.022
247620Y3-023
Adder
0.93
274808UNIV PK N;4U
Adder
9.944
972259AH1-714 GEN
Adder
37.882
274803UNIV PARK;6U
Adder
11.574
274888KELLY CRK;1U
Solar/Wind Harmer
11.713
274887GEN-1.85
Solar/Wind Harmer
10.575
276843GEN-1.7
Solar/Wind Harmer
1.138
958011AF2-095 GEN
Solar/Wind Harmer
28.568
274674JOLIET 9 ;6U
Adder
30.252
274847GR RIDGE ;BU
Solar/Wind Harmer
9.918
971573AH1-285 GEN
Solar/Wind Harmer
16.69
274695ROCKY RD ;2P
Adder
21.435
274693ROCKY RD ;1P
Adder
21.224
274697ROCKY RD ;3P
Adder
5.823
274696ROCKY RD ;4P
Adder
21.94
958481AF2-142 GEN
Solar/Wind Harmer
28.872
274861TOP CROP ;1U
Solar/Wind Harmer
11.657
274862TOP CROP ;2U
Solar/Wind Harmer
9.734
274683WAUKEGAN ;8U
Adder
40.442
274683WAUKEGAN ;8U
Adder
34.091
962691AG1-118 GEN
Solar/Wind Harmer
57.342
970921AG2-575 GEN
Solar/Wind Harmer
19.065
970921AG2-575 GEN
Solar/Wind Harmer
4.434
958491AF2-143 GEN
Solar/Wind Harmer
28.532
274879MINONK ;1U
Solar/Wind Harmer
12.777
942991AE2-321 GEN
Solar/Wind Harmer
18.919
971333AH1-146 GEN
Solar/Wind Harmer
37.64
971335AH1-147 GEN
Solar/Wind Harmer
37.64
971341AH1-150 GEN
Solar/Wind Harmer
37.421
971343AH1-151 GEN
Solar/Wind Harmer
37.421
276872AE1-163_GEN1
Solar/Wind Harmer
12.566
274764LEE CO EC;5U
Adder
17.08
274765LEE CO EC;6U
Adder
17.08
274762LEE CO EC;3U
Adder
17.04
274763LEE CO EC;4U
Adder
16.88
972267AH1-718 GEN
Adder
7.55
270471AD2-092_GEN
Solar/Wind Helper
1.555
945421AF1-207 GEN
Solar/Wind Harmer
23.561
971599AH1-298 GEN
50/50
19.943
270144AC1-141 ST1_
50/50
4.4
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
13.384
274776LINCOLN ;7U
50/50
13.384
274777LINCOLN ;8U
50/50
13.384
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
33.197
960681AF2-359 GEN
Solar/Wind Harmer
7.853
971771AH1-392 GEN
Solar/Wind Harmer
18.701
971769AH1-391 GEN
Solar/Wind Harmer
20.689
270071AF1-092 GEN
Solar/Wind Harmer
30.794
944161AF1-084 GEN
Solar/Wind Harmer
4.463
274814UNIV PK N;0U
Adder
10.075
274807UNIV PK N;3U
Adder
10.053
274805UNIV PK N;1U
Adder
10.009
274811UNIV PK N;7U
Adder
9.987
972037AH1-567 GEN1
Adder
0.363
274827FISK ;RP
Adder
15.4
960591AF2-350 GEN
Solar/Wind Harmer
19.839
972227AH1-698 GEN1
Adder
5.172
270536AF1-215 GEN2
Solar/Wind Harmer
8.953
274687WILL CNTY;4U
Adder
55.044
274687WILL CNTY;4U
Adder
55.044
274675JOLIET 29;7U
Adder
60.371
274675JOLIET 29;7U
Adder
58.215
274731ELWOOD EC;2P
Adder
32.272
274733ELWOOD EC;3P
Adder
32.272
274735ELWOOD EC;4P
Adder
32.272
274728ELWOOD EC;5P
Adder
32.272
970833AG2-524 GEN
Solar/Wind Harmer
17.125
970833AG2-524 GEN
Solar/Wind Harmer
7.965
274746AC1-111 G10
Adder
10.891
274744AC1-111 GEN8
Adder
10.891
958391AF2-133 GEN
Solar/Wind Harmer
17.467
24729505KEY G4
Adder
12.444
276868AE1-113 GEN
Solar/Wind Harmer
19.163
276882AE2-255 GEN
Solar/Wind Harmer
6.388
971177AH1-047 GEN
Solar/Wind Harmer
11.082
971675AH1-338 GEN
Solar/Wind Harmer
33.905
971411AH1-196 GEN
Solar/Wind Harmer
28.25
274863CRW1-WTG
Solar/Wind Harmer
10.504
274864CRW2-WTG
Solar/Wind Harmer
10.504
274850MENDOTA H;RU
Solar/Wind Harmer
4.836
276602WESTBROOK C
Solar/Wind Harmer
4.003
276863AD2-134 GEN
Solar/Wind Harmer
3.363
959091AF2-200 GEN
Solar/Wind Harmer
37.421
276889AE2-281 GEN
Solar/Wind Harmer
3.59
972236AH1-702 GEN2
Adder
4.076
274760LEE CO EC;1U
Adder
17.04
274767LEE CO EC;8U
Adder
16.84
971171AH1-044 GEN
Solar/Wind Harmer
37.421
274823ROCKFORD ;21
Adder
36.321
944201AF1-088_MTX
Adder
162.845
957141AF2-008_MTX
Adder
81.423
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.535
CBM West 1LTFEXP_CBM-W1->PJM
CBM
216.955
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.977
MECLTFEXP_MEC->PJM
CLTF
25.953
SIGELTFEXP_SIGE->PJM
CLTF
0.549
LAGNLTFEXP_LAGN->PJM
CLTF
14.056
TVALTFEXP_TVA->PJM
CLTF
5.361
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.514
NYPJM->LTFIMP_NY
CLTF
3.416
LGEELTFEXP_LGEE->PJM
CLTF
5.556
WECLTFEXP_WEC->PJM
CLTF
7.087
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.221
AG2-052LTFEXP_AG2-052->PJM
LTF
0.446
AH1-155LTFEXP_AH1-155->PJM
LTF
0.669

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.61 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6274.56
MW Contribution:59.12
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.353
270100X2-052 CT1
50/50
3.09
270101X2-052 CT2
50/50
3.09
274770LINCOLN ;1U
50/50
13.415
274771LINCOLN ;2U
50/50
13.415
970321AG2-212 GEN
Solar/Wind Harmer
39.676
965681AG1-436 GEN
Solar/Wind Harmer
26.042
965791AG1-447 GEN
Solar/Wind Harmer
13.324
270526AF1-158 GEN
Solar/Wind Harmer
9.429
24441505OLIV SLR
Solar/Wind Harmer
0.278
270216AD2-079_GEN
Solar/Wind Harmer
1.255
957891AF2-083 GEN
Solar/Wind Harmer
6.929
960981AF2-389 GEN
Solar/Wind Harmer
3.105
961051AF2-396 GEN
Solar/Wind Harmer
32.372
961051AF2-396 GEN
Solar/Wind Harmer
15.057
247620Y3-023
Adder
0.932
274808UNIV PK N;4U
Adder
9.967
972259AH1-714 GEN
Adder
37.97
274803UNIV PARK;6U
Adder
11.601
274888KELLY CRK;1U
Solar/Wind Harmer
11.74
274887GEN-1.85
Solar/Wind Harmer
10.599
276843GEN-1.7
Solar/Wind Harmer
1.14
958011AF2-095 GEN
Solar/Wind Harmer
28.635
274674JOLIET 9 ;6U
Adder
30.323
274847GR RIDGE ;BU
Solar/Wind Harmer
9.941
971573AH1-285 GEN
Solar/Wind Harmer
16.73
274695ROCKY RD ;2P
Adder
21.486
274693ROCKY RD ;1P
Adder
21.275
274697ROCKY RD ;3P
Adder
5.837
274696ROCKY RD ;4P
Adder
21.993
958481AF2-142 GEN
Solar/Wind Harmer
28.942
274861TOP CROP ;1U
Solar/Wind Harmer
11.685
274862TOP CROP ;2U
Solar/Wind Harmer
9.757
274683WAUKEGAN ;8U
Adder
40.539
274683WAUKEGAN ;8U
Adder
34.173
962691AG1-118 GEN
Solar/Wind Harmer
57.48
970921AG2-575 GEN
Solar/Wind Harmer
19.111
970921AG2-575 GEN
Solar/Wind Harmer
4.444
958491AF2-143 GEN
Solar/Wind Harmer
28.602
274879MINONK ;1U
Solar/Wind Harmer
12.808
942991AE2-321 GEN
Solar/Wind Harmer
18.965
971333AH1-146 GEN
Solar/Wind Harmer
37.732
971335AH1-147 GEN
Solar/Wind Harmer
37.732
971341AH1-150 GEN
Solar/Wind Harmer
37.513
971343AH1-151 GEN
Solar/Wind Harmer
37.513
276872AE1-163_GEN1
Solar/Wind Harmer
12.597
274764LEE CO EC;5U
Adder
17.123
274765LEE CO EC;6U
Adder
17.123
274762LEE CO EC;3U
Adder
17.083
274763LEE CO EC;4U
Adder
16.922
972267AH1-718 GEN
Adder
7.569
270471AD2-092_GEN
Solar/Wind Helper
1.548
945421AF1-207 GEN
Solar/Wind Harmer
23.62
24344105CKG2
50/50
17.41
270143AC1-141 CT2_
50/50
4.979
24639705ELKHART HY
50/50
0.333
274773LINCOLN ;4U
50/50
13.415
274774LINCOLN ;5U
50/50
13.415
970521AG2-332 GEN
50/50
23.674
970245AG2-165 GEN
Solar/Wind Harmer
39.676
270505AE1-170 C O1
Solar/Wind Harmer
30.872
945111AF1-176 GEN
Solar/Wind Harmer
36.495
972207SS24-0001
Solar/Wind Harmer
44.948
270449AD2-020 GEN
Solar/Wind Harmer
5.706
943021AE2-325 GEN
Solar/Wind Harmer
7.414
274723RIVER EC ;12
Adder
36.059
970373AG2-245 GEN
Solar/Wind Harmer
42.185
274751CRETE EC ;1U
Adder
9.818
274754CRETE EC ;4U
Adder
9.818
276164X3-005 C
Solar/Wind Harmer
1.409
270063AE2-323 C
Solar/Wind Harmer
4.405
274812UNIV PK N;8U
Adder
10.011
276776AD2-060 GEN
Solar/Wind Harmer
0.841
274801UNIV PARK;4U
Adder
11.588
941551AE2-152 GEN
Solar/Wind Harmer
8.982
270055AF2-134 C O1
Solar/Wind Harmer
5.982
274676JOLIET 29;8U
Adder
60.512
274674JOLIET 9 ;6U
Adder
30.323
274732ELWOOD EC;7P
Adder
32.348
274871GR RIDGE ;2U
Solar/Wind Harmer
15.112
274745AC1-111 GEN9
Adder
10.916
958381AF2-132 GEN
Solar/Wind Harmer
17.648
964861AG1-349 GEN
Solar/Wind Harmer
15.267
971917AH1-482 GEN
Solar/Wind Harmer
17.617
276691AA1-018 GEN1
Solar/Wind Harmer
0.898
274682WAUKEGAN ;7U
Adder
34.62
274828WAUKEGAN ;BP
Adder
21.25
939401AE1-172 GEN
Solar/Wind Harmer
26.665
960751AF2-366 GEN
Solar/Wind Harmer
5.483
962781AG1-127 GEN
Solar/Wind Harmer
18.175
274872LEEDK;1U
Solar/Wind Harmer
15.662
940581AE2-045 GEN
Solar/Wind Harmer
19.423
971605AH1-302 GEN
Solar/Wind Harmer
16.609
276901AD2-066 C O1
Solar/Wind Harmer
6.692
971997AH1-543 GEN
Solar/Wind Harmer
29.852
276861AD2-134 GEN
Solar/Wind Harmer
3.372
957471AF2-041 GEN
Solar/Wind Harmer
56.27
959081AF2-199 GEN
Solar/Wind Harmer
18.757
971067AG2-660 GEN
Solar/Wind Harmer
4.362
276876AE1-163_GEN2
Solar/Wind Harmer
12.597
274822ROCKFORD ;11
Adder
36.677
972235AH1-702 GEN1
Adder
4.699
274761LEE CO EC;2U
Adder
17.083
274766LEE CO EC;7U
Adder
16.882
970091AG2-072 GEN
Adder
32.467
270349AD2-093_GEN
Solar/Wind Helper
1.548
24344005CKG1
50/50
13.628
270142AC1-141 CT1_
50/50
4.979
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.39
274772LINCOLN ;3U
50/50
13.415
970513AG2-328 GEN
Solar/Wind Harmer
39.676
970517AG2-330 GEN
Solar/Wind Harmer
35.985
970349AG2-230 GEN
Solar/Wind Harmer
33.266
270043AE2-236 GEN
Solar/Wind Harmer
11.512
247643Z2-116 C
Solar/Wind Harmer
0.145
945111AF1-176 GEN
Solar/Wind Harmer
11.566
274724RIVER EC ;11
Adder
35.644
972231SS25-0005
Solar/Wind Harmer
19.064
972181SS23-001
Solar/Wind Harmer
11.915
274752CRETE EC ;2U
Adder
9.818
274753CRETE EC ;3U
Adder
9.818
24441205WTRV SLR C
Solar/Wind Harmer
0.27
970707AG2-453 GEN
Solar/Wind Harmer
55.958
274802UNIV PARK;5U
Adder
11.601
274826FISK ;BP
Adder
21.78
276772AC2-154 GEN
Solar/Wind Harmer
5.545
276806AD2-047 C O1
Solar/Wind Harmer
21.273
970941AG2-585 GEN
Solar/Wind Harmer
24.857
972228AH1-698 GEN2
Adder
7.363
274800UNIV PARK;3U
Adder
11.588
972038AH1-567 GEN2
Adder
0.725
276897AD1-100 C
Solar/Wind Harmer
57.471
939351AE1-166 GEN
Solar/Wind Harmer
11.743
247604X1-042
Adder
0.825
270535AF1-215 GEN1
Solar/Wind Harmer
8.974
274676JOLIET 29;8U
Adder
58.35
970031AG2-029 GEN
Solar/Wind Harmer
59.115
274729ELWOOD EC;1P
Adder
32.348
274730ELWOOD EC;6P
Adder
32.348
274734ELWOOD EC;8P
Adder
32.348
274736ELWOOD EC;9P
Adder
32.348
276893AG1-478 C
Solar/Wind Harmer
0.821
944531AF1-118 GEN
Solar/Wind Harmer
68.828
943121AE2-341 GEN
Solar/Wind Harmer
29.349
943591AF1-030 GEN
Solar/Wind Harmer
19.566
964401AG1-302 GEN
Solar/Wind Harmer
17.648
276694AA1-018 GEN2
Solar/Wind Harmer
12.176
274682WAUKEGAN ;7U
Adder
34.62
959141AF2-205 GEN
Solar/Wind Harmer
11.599
276805AD2-038 GEN
Solar/Wind Harmer
9.782
274872LEEDK;1U
Solar/Wind Harmer
0.488
276799AD1-013 GEN
Solar/Wind Harmer
4.176
946671AF1-331 GEN
Solar/Wind Harmer
0.791
274855GSG-6 ;RU
Solar/Wind Harmer
6.972
274850MENDOTA H;RU
Solar/Wind Harmer
4.848
276602WESTBROOK C
Solar/Wind Harmer
4.013
276863AD2-134 GEN
Solar/Wind Harmer
3.372
959091AF2-200 GEN
Solar/Wind Harmer
37.513
276889AE2-281 GEN
Solar/Wind Harmer
3.599
972236AH1-702 GEN2
Adder
4.086
274760LEE CO EC;1U
Adder
17.083
274767LEE CO EC;8U
Adder
16.882
971599AH1-298 GEN
50/50
19.983
270144AC1-141 ST1_
50/50
4.41
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
13.415
274776LINCOLN ;7U
50/50
13.415
274777LINCOLN ;8U
50/50
13.415
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
33.266
960681AF2-359 GEN
Solar/Wind Harmer
7.871
971771AH1-392 GEN
Solar/Wind Harmer
18.742
971769AH1-391 GEN
Solar/Wind Harmer
20.735
270071AF1-092 GEN
Solar/Wind Harmer
30.863
944161AF1-084 GEN
Solar/Wind Harmer
4.473
274814UNIV PK N;0U
Adder
10.098
274807UNIV PK N;3U
Adder
10.076
274805UNIV PK N;1U
Adder
10.033
274811UNIV PK N;7U
Adder
10.011
972037AH1-567 GEN1
Adder
0.364
274827FISK ;RP
Adder
15.436
960591AF2-350 GEN
Solar/Wind Harmer
19.885
972227AH1-698 GEN1
Adder
5.185
270536AF1-215 GEN2
Solar/Wind Harmer
8.974
274687WILL CNTY;4U
Adder
55.173
274687WILL CNTY;4U
Adder
55.173
274675JOLIET 29;7U
Adder
60.513
274675JOLIET 29;7U
Adder
58.351
274731ELWOOD EC;2P
Adder
32.348
274733ELWOOD EC;3P
Adder
32.348
274735ELWOOD EC;4P
Adder
32.348
274728ELWOOD EC;5P
Adder
32.348
970833AG2-524 GEN
Solar/Wind Harmer
17.166
970833AG2-524 GEN
Solar/Wind Harmer
7.984
274746AC1-111 G10
Adder
10.916
274744AC1-111 GEN8
Adder
10.916
958391AF2-133 GEN
Solar/Wind Harmer
17.509
24729505KEY G4
Adder
12.474
276868AE1-113 GEN
Solar/Wind Harmer
19.21
276882AE2-255 GEN
Solar/Wind Harmer
6.404
971177AH1-047 GEN
Solar/Wind Harmer
11.109
971675AH1-338 GEN
Solar/Wind Harmer
33.988
971411AH1-196 GEN
Solar/Wind Harmer
28.319
274863CRW1-WTG
Solar/Wind Harmer
10.53
274864CRW2-WTG
Solar/Wind Harmer
10.53
971171AH1-044 GEN
Solar/Wind Harmer
37.513
274823ROCKFORD ;21
Adder
36.411
944201AF1-088_MTX
Adder
163.382
957141AF2-008_MTX
Adder
81.691
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.154
MECLTFEXP_MEC->PJM
CLTF
26.031
SIGELTFEXP_SIGE->PJM
CLTF
0.551
LAGNLTFEXP_LAGN->PJM
CLTF
14.15
TVALTFEXP_TVA->PJM
CLTF
5.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.138
NYPJM->LTFIMP_NY
CLTF
3.386
LGEELTFEXP_LGEE->PJM
CLTF
5.588
WECLTFEXP_WEC->PJM
CLTF
7.104
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.447
AH1-155LTFEXP_AH1-155->PJM
LTF
0.671

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6022.77
MW Contribution:8.94
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
17.41
270143AC1-141 CT2_
50/50
4.979
24639705ELKHART HY
50/50
0.333
274773LINCOLN ;4U
50/50
18.26
274774LINCOLN ;5U
50/50
18.26
970521AG2-332 GEN
50/50
23.674
970245AG2-165 GEN
Solar/Wind Harmer
6.717
270505AE1-170 C O1
Solar/Wind Harmer
15.077
945111AF1-176 GEN
Solar/Wind Harmer
25.462
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.414
274723RIVER EC ;12
Adder
36.059
970373AG2-245 GEN
Solar/Wind Harmer
29.431
274751CRETE EC ;1U
Adder
16.552
274754CRETE EC ;4U
Adder
16.552
276164X3-005 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0.011
274812UNIV PK N;8U
Adder
10.011
276776AD2-060 GEN
Solar/Wind Harmer
1.448
274801UNIV PARK;4U
Adder
11.588
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.011
274676JOLIET 29;8U
Adder
60.512
274674JOLIET 9 ;6U
Adder
30.323
274732ELWOOD EC;7P
Adder
32.348
274871GR RIDGE ;2U
Solar/Wind Harmer
0.002
274745AC1-111 GEN9
Adder
10.916
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
17.617
276691AA1-018 GEN1
Solar/Wind Harmer
1.631
274682WAUKEGAN ;7U
Adder
34.62
274828WAUKEGAN ;BP
Adder
21.25
939401AE1-172 GEN
Solar/Wind Harmer
9.985
962781AG1-127 GEN
Solar/Wind Harmer
12.689
274872LEEDK;1U
Solar/Wind Harmer
0.008
940581AE2-045 GEN
Solar/Wind Harmer
-0.003
971605AH1-302 GEN
Solar/Wind Harmer
16.609
276901AD2-066 C O1
Solar/Wind Harmer
0.013
971997AH1-543 GEN
Solar/Wind Harmer
6.942
276861AD2-134 GEN
Solar/Wind Harmer
0.236
957471AF2-041 GEN
Solar/Wind Harmer
39.258
959081AF2-199 GEN
Solar/Wind Harmer
13.086
971067AG2-660 GEN
Solar/Wind Harmer
4.362
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
36.677
972235AH1-702 GEN1
Adder
4.699
970819AG2-516 GEN
Solar/Wind Harmer
15.555
970569AG2-363 GEN
Solar/Wind Harmer
38.8
971475AH1-234 GEN
Solar/Wind Harmer
6.272
274857EASY ROAD;U1
Solar/Wind Harmer
0.003
274761LEE CO EC;2U
Adder
17.083
274766LEE CO EC;7U
Adder
16.882
24791305MDL-5G
Solar/Wind Harmer
0.002
965011AG1-365 GEN
Solar/Wind Harmer
12.726
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.423
965651AG1-433 GEN
Solar/Wind Harmer
3.688
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
17.52
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.005
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
958861AF2-177 GEN
Solar/Wind Harmer
5.328
972175AH1-670 GEN
Solar/Wind Harmer
9.878
945371AF1-202 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
27.693
274880W4-005 GEN4
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
4.513
276615X2-022 GEN
Solar/Wind Harmer
0.12
944231AF1-091 GEN
Solar/Wind Harmer
3.041
970291AG2-192 GEN
Solar/Wind Harmer
1.481
270032AE2-172
Solar/Wind Harmer
7.401
965911AG1-460 GEN
Solar/Wind Harmer
2.209
276903AD2-071 C
Solar/Wind Harmer
12.04
970333AG2-219 GEN
Solar/Wind Harmer
7.687
270005AE1-210 C O1
Solar/Wind Harmer
2.283
965031AG1-367 GEN
Solar/Wind Harmer
10.536
970825AG2-519 GEN
Solar/Wind Harmer
3.643
247521TR3_G114
Solar/Wind Harmer
0.37
270246TR4_N_V150
Solar/Wind Harmer
0.066
24695305TIMB G C
Solar/Wind Harmer
0.003
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.029
247536S-71 GEN
Solar/Wind Harmer
0.355
965421AG1-410 GEN
Solar/Wind Harmer
25.459
970773AG2-487 GEN
Solar/Wind Harmer
1.469
246936BC-WTG1
Solar/Wind Harmer
0.326
270489AE1-102 GEN1
Solar/Wind Harmer
1.045
270349AD2-093_GEN
Solar/Wind Helper
1.548
270102X2-052 ST
50/50
3.353
270100X2-052 CT1
50/50
3.09
270101X2-052 CT2
50/50
3.09
274770LINCOLN ;1U
50/50
18.26
274771LINCOLN ;2U
50/50
18.26
970321AG2-212 GEN
Solar/Wind Harmer
6.717
965681AG1-436 GEN
Solar/Wind Harmer
18.169
965791AG1-447 GEN
Solar/Wind Harmer
13.324
270526AF1-158 GEN
Solar/Wind Harmer
0.018
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
28.457
961051AF2-396 GEN
Solar/Wind Harmer
18.971
247620Y3-023
Adder
0.932
274808UNIV PK N;4U
Adder
9.967
972259AH1-714 GEN
Adder
37.97
274803UNIV PARK;6U
Adder
11.601
274888KELLY CRK;1U
Solar/Wind Harmer
0.815
274887GEN-1.85
Solar/Wind Harmer
0.365
276843GEN-1.7
Solar/Wind Harmer
0.449
958011AF2-095 GEN
Solar/Wind Harmer
19.978
274674JOLIET 9 ;6U
Adder
30.323
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.529
274695ROCKY RD ;2P
Adder
21.486
274693ROCKY RD ;1P
Adder
21.275
274697ROCKY RD ;3P
Adder
5.837
274696ROCKY RD ;4P
Adder
21.993
958481AF2-142 GEN
Solar/Wind Harmer
20.192
274861TOP CROP ;1U
Solar/Wind Harmer
0.004
274862TOP CROP ;2U
Solar/Wind Harmer
1.82
274683WAUKEGAN ;8U
Adder
40.539
274683WAUKEGAN ;8U
Adder
34.173
962691AG1-118 GEN
Solar/Wind Harmer
40.102
970921AG2-575 GEN
Solar/Wind Harmer
13.333
970921AG2-575 GEN
Solar/Wind Harmer
4.444
958491AF2-143 GEN
Solar/Wind Harmer
19.955
274879MINONK ;1U
Solar/Wind Harmer
0.559
942991AE2-321 GEN
Solar/Wind Harmer
14.775
971333AH1-146 GEN
Solar/Wind Harmer
26.325
971335AH1-147 GEN
Solar/Wind Harmer
26.325
971341AH1-150 GEN
Solar/Wind Harmer
26.172
971343AH1-151 GEN
Solar/Wind Harmer
26.172
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.305
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
7.288
274764LEE CO EC;5U
Adder
17.123
274765LEE CO EC;6U
Adder
17.123
274762LEE CO EC;3U
Adder
17.083
274763LEE CO EC;4U
Adder
16.922
276603SUBLETTE C
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
12.726
970627AG2-408 GEN
Solar/Wind Harmer
3.818
972267AH1-718 GEN
Adder
7.569
276741O09 GEN1
Solar/Wind Harmer
0.451
276708O09 GEN2
Solar/Wind Harmer
0.451
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.497
276646AC1-214 GEN2
Solar/Wind Harmer
0.497
276782AC1-033 GEN
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.842
960971AF2-388 GEN
Solar/Wind Harmer
7.376
966841AG1-555 GEN
Solar/Wind Harmer
1.399
960611AF2-352 GEN
Solar/Wind Harmer
4.101
970241AG2-163 GEN
Solar/Wind Harmer
6.826
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
971613AH1-306 GEN
Solar/Wind Harmer
5.329
270599AE1-208 GEN
Solar/Wind Harmer
10.158
270031AE2-169
Solar/Wind Harmer
6.095
276916AD2-100_GEN
Solar/Wind Harmer
23.006
276911AD2-131_GEN
Solar/Wind Harmer
1.515
970239AG2-162 GEN
Solar/Wind Harmer
2.688
945391AF1-204 GEN
Solar/Wind Harmer
11.282
960441AF2-335 GEN
Solar/Wind Harmer
10.327
970825AG2-519 GEN
Solar/Wind Harmer
11.373
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.189
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.716
270201AC2-176 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
24344005CKG1
50/50
13.628
270142AC1-141 CT1_
50/50
4.979
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.39
274772LINCOLN ;3U
50/50
18.26
970513AG2-328 GEN
Solar/Wind Harmer
6.717
970517AG2-330 GEN
Solar/Wind Harmer
40.303
970349AG2-230 GEN
Solar/Wind Harmer
23.209
270043AE2-236 GEN
Solar/Wind Harmer
9.37
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.566
274724RIVER EC ;11
Adder
35.644
274752CRETE EC ;2U
Adder
16.552
274753CRETE EC ;3U
Adder
16.552
24441205WTRV SLR C
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
45.547
274802UNIV PARK;5U
Adder
11.601
274826FISK ;BP
Adder
21.78
276806AD2-047 C O1
Solar/Wind Harmer
7.862
970941AG2-585 GEN
Solar/Wind Harmer
17.342
972228AH1-698 GEN2
Adder
7.363
970623AG2-406 GEN
Solar/Wind Harmer
1.6
970883AG2-550 GEN
Solar/Wind Harmer
8.324
970885AG2-551 GEN
Solar/Wind Harmer
2.775
270007AE1-245 C
Solar/Wind Harmer
0.002
246938BC-WTG3
Solar/Wind Harmer
0.291
246937BC-WTG2
Solar/Wind Harmer
0.326
270471AD2-092_GEN
Solar/Wind Helper
1.548
274800UNIV PARK;3U
Adder
11.588
972038AH1-567 GEN2
Adder
0.725
276897AD1-100 C
Solar/Wind Harmer
0.018
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247604X1-042
Adder
0.825
270535AF1-215 GEN1
Solar/Wind Harmer
0.017
274676JOLIET 29;8U
Adder
58.35
970031AG2-029 GEN
Solar/Wind Harmer
8.936
274729ELWOOD EC;1P
Adder
32.348
274730ELWOOD EC;6P
Adder
32.348
274734ELWOOD EC;8P
Adder
32.348
274736ELWOOD EC;9P
Adder
32.348
276893AG1-478 C
Solar/Wind Harmer
0.544
944531AF1-118 GEN
Solar/Wind Harmer
61.488
943121AE2-341 GEN
Solar/Wind Harmer
22.888
943591AF1-030 GEN
Solar/Wind Harmer
15.221
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
34.62
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.004
274872LEEDK;1U
Solar/Wind Harmer
0.488
276799AD1-013 GEN
Solar/Wind Harmer
0.003
946671AF1-331 GEN
Solar/Wind Harmer
1.406
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.155
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.236
959091AF2-200 GEN
Solar/Wind Harmer
26.172
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
4.086
970571AG2-364 GEN
Solar/Wind Harmer
25.867
274858EASY ROAD;U2
Solar/Wind Harmer
0.003
274760LEE CO EC;1U
Adder
17.083
274767LEE CO EC;8U
Adder
16.882
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
12.802
959331AF2-224 GEN
Solar/Wind Harmer
8.908
965021AG1-366 GEN
Solar/Wind Harmer
4.242
276157O29GEN1
Solar/Wind Harmer
2.046
274878BISHOP HL;2U
Solar/Wind Harmer
0.423
942111AE2-223 GEN
Solar/Wind Harmer
4.067
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
36.906
959611AF2-252 GEN
Solar/Wind Harmer
4.101
965931AG1-462 GEN
Solar/Wind Harmer
31.198
247642Z2-115 C
Solar/Wind Harmer
0.005
276686W4-005 GEN3
Solar/Wind Harmer
0.002
971993AH1-541 GEN
Solar/Wind Harmer
5.377
276668AB2-070 GEN1
Solar/Wind Harmer
0.424
276621W2-048 GEN
Solar/Wind Harmer
0.577
276838X2-022 GEN2
Solar/Wind Harmer
0.644
970289AG2-191 GEN
Solar/Wind Harmer
1.253
970291AG2-192 GEN
Solar/Wind Harmer
1.139
942481AE2-261 GEN
Solar/Wind Harmer
33.028
970243AG2-164 GEN
Solar/Wind Harmer
6.289
970519AG2-331 GEN
Solar/Wind Harmer
27.951
970699AG2-449 GEN
Solar/Wind Harmer
2.688
970193AG2-126 GEN
Solar/Wind Harmer
15.928
958821AF2-173 GEN
Solar/Wind Harmer
14.751
270004AE1-209 GEN
Solar/Wind Harmer
2.283
971617AH1-308 GEN
Solar/Wind Harmer
8.548
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.066
946031AF1-268 GEN
Solar/Wind Harmer
9.517
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
14.144
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270491AE1-102 GEN2
Solar/Wind Harmer
1.045
971599AH1-298 GEN
50/50
19.983
270144AC1-141 ST1_
50/50
4.41
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
18.26
274776LINCOLN ;7U
50/50
18.26
274777LINCOLN ;8U
50/50
18.26
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
23.209
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971771AH1-392 GEN
Solar/Wind Harmer
14.529
971769AH1-391 GEN
Solar/Wind Harmer
16.154
971619AH1-309 GEN
Solar/Wind Harmer
6.462
270071AF1-092 GEN
Solar/Wind Harmer
27.514
274814UNIV PK N;0U
Adder
10.098
274807UNIV PK N;3U
Adder
10.076
274805UNIV PK N;1U
Adder
10.033
274811UNIV PK N;7U
Adder
10.011
972037AH1-567 GEN1
Adder
0.364
274827FISK ;RP
Adder
15.436
960591AF2-350 GEN
Solar/Wind Harmer
13.873
972227AH1-698 GEN1
Adder
5.185
270536AF1-215 GEN2
Solar/Wind Harmer
0.017
274687WILL CNTY;4U
Adder
55.173
274687WILL CNTY;4U
Adder
55.173
274675JOLIET 29;7U
Adder
60.513
274675JOLIET 29;7U
Adder
58.351
274731ELWOOD EC;2P
Adder
32.348
274733ELWOOD EC;3P
Adder
32.348
274735ELWOOD EC;4P
Adder
32.348
274728ELWOOD EC;5P
Adder
32.348
970833AG2-524 GEN
Solar/Wind Harmer
15.09
970833AG2-524 GEN
Solar/Wind Harmer
10.06
274746AC1-111 G10
Adder
10.916
274744AC1-111 GEN8
Adder
10.916
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.474
971611AH1-305 GEN
Solar/Wind Harmer
7.91
276868AE1-113 GEN
Solar/Wind Harmer
2.657
276882AE2-255 GEN
Solar/Wind Harmer
1.548
971177AH1-047 GEN
Solar/Wind Harmer
8.156
971675AH1-338 GEN
Solar/Wind Harmer
5.138
971411AH1-196 GEN
Solar/Wind Harmer
19.757
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
26.172
274823ROCKFORD ;21
Adder
36.411
970169AG2-114 GEN
Solar/Wind Harmer
12.957
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
2.2
971549AH1-272 GEN
Solar/Wind Harmer
26.668
971681AH1-341 GEN
Solar/Wind Harmer
20.716
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.003
24697605MDL-3G C
Solar/Wind Harmer
0.003
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
961011AF2-392 GEN
Solar/Wind Harmer
7.462
957751AF2-069 GEN
Solar/Wind Harmer
0.418
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
13.14
941731AE2-173 GEN
Solar/Wind Harmer
10.429
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
6.891
965101AG1-375 GEN
Solar/Wind Harmer
12.296
963841AG1-237 GEN
Solar/Wind Harmer
5.208
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.002
276174W4-005 GEN2
Solar/Wind Harmer
0.002
276849AB2-070 GEN2
Solar/Wind Harmer
0.424
276848AB2-070 GEN3
Solar/Wind Harmer
0.422
963791AG1-232 GEN
Solar/Wind Harmer
15.504
970289AG2-191 GEN
Solar/Wind Harmer
2.164
270594AE1-207 GEN
Solar/Wind Harmer
12.434
971609AH1-304 GEN
Solar/Wind Harmer
1.81
965041AG1-368 GEN
Solar/Wind Harmer
11.055
944221AF1-090 GEN
Solar/Wind Harmer
6.244
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
4.131
270024AE2-089 GEN
Solar/Wind Harmer
0.011
965051AG1-369 GEN
Solar/Wind Harmer
5.072
270240V3-007_GEN2
Solar/Wind Harmer
0.003
270543AE2-219 C
Solar/Wind Harmer
0.005
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.018
971029AG2-637 GEN
Solar/Wind Harmer
11.658
971673AH1-337 GEN
Solar/Wind Harmer
4.919
944201AF1-088_MTX
Adder
163.382
957141AF2-008_MTX
Adder
69.441
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.154
MECLTFEXP_MEC->PJM
CLTF
26.031
SIGELTFEXP_SIGE->PJM
CLTF
0.551
LAGNLTFEXP_LAGN->PJM
CLTF
14.15
TVALTFEXP_TVA->PJM
CLTF
5.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.138
NYPJM->LTFIMP_NY
CLTF
3.386
LGEELTFEXP_LGEE->PJM
CLTF
5.588
WECLTFEXP_WEC->PJM
CLTF
7.104
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.447
AH1-155LTFEXP_AH1-155->PJM
LTF
0.671

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#2995_05E LIMA 345_M_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2995_05E LIMA 345_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.54 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5994.88
MW Contribution:61.23
Bus #Bus NameTypeMW Contribution
24727105RPMNG2
50/50
2.046
965431AG1-411 GEN
50/50
24.956
24641605TWIN BRNCH
50/50
0.035
270142AC1-141 CT1_
50/50
4.843
24344005CKG1
50/50
13.154
24642205MAYFLWER
50/50
1.348
944961AF1-161 GEN
50/50
5.748
962601AG1-109 GEN
50/50
5.748
270043AE2-236 GEN
Solar/Wind Harmer
11.825
959331AF2-224 GEN
Solar/Wind Harmer
21.485
965021AG1-366 GEN
Solar/Wind Harmer
4.996
270491AE1-102 GEN2
Solar/Wind Harmer
2.79
970349AG2-230 GEN
Solar/Wind Harmer
32.134
970513AG2-328 GEN
Solar/Wind Harmer
37.203
970517AG2-330 GEN
Solar/Wind Harmer
33.742
970031AG2-029 GEN
Solar/Wind Harmer
61.231
970615AG2-402 GEN
50/50
4.996
270102X2-052 ST
50/50
3.216
270100X2-052 CT1
50/50
2.963
270101X2-052 CT2
50/50
2.963
247620Y3-023
50/50
0.981
970611AG2-400 GEN
Solar/Wind Harmer
21.485
246938BC-WTG3
Solar/Wind Harmer
8.542
246937BC-WTG2
Solar/Wind Harmer
8.398
970321AG2-212 GEN
Solar/Wind Harmer
37.203
270216AD2-079_GEN
Solar/Wind Harmer
1.229
270526AF1-158 GEN
Solar/Wind Harmer
9.099
957891AF2-083 GEN
Solar/Wind Harmer
6.742
960981AF2-389 GEN
Solar/Wind Harmer
3.021
24441505OLIV SLR
Solar/Wind Harmer
0.268
965681AG1-436 GEN
Solar/Wind Harmer
24.955
965791AG1-447 GEN
Solar/Wind Harmer
12.768
961051AF2-396 GEN
Solar/Wind Harmer
31.495
961051AF2-396 GEN
Solar/Wind Harmer
14.649
274770LINCOLN ;1U
Adder
12.031
274771LINCOLN ;2U
Adder
12.031
274808UNIV PK N;4U
Adder
9.492
274803UNIV PARK;6U
Adder
11.035
972259AH1-714 GEN
Adder
36.075
274888KELLY CRK;1U
Solar/Wind Harmer
11.16
274887GEN-1.85
Solar/Wind Harmer
10.076
276843GEN-1.7
Solar/Wind Harmer
1.084
958011AF2-095 GEN
Solar/Wind Harmer
27.22
274674JOLIET 9 ;6U
Adder
28.794
274847GR RIDGE ;BU
Solar/Wind Harmer
9.431
971573AH1-285 GEN
Solar/Wind Harmer
15.868
274695ROCKY RD ;2P
Adder
20.37
274693ROCKY RD ;1P
Adder
20.17
274697ROCKY RD ;3P
Adder
5.534
274696ROCKY RD ;4P
Adder
20.85
958481AF2-142 GEN
Solar/Wind Harmer
27.421
274861TOP CROP ;1U
Solar/Wind Harmer
11.071
274862TOP CROP ;2U
Solar/Wind Harmer
9.244
274683WAUKEGAN ;8U
Adder
38.432
274683WAUKEGAN ;8U
Adder
32.396
962691AG1-118 GEN
Solar/Wind Harmer
54.457
970921AG2-575 GEN
Solar/Wind Harmer
18.103
970921AG2-575 GEN
Solar/Wind Harmer
4.21
958491AF2-143 GEN
Solar/Wind Harmer
27.059
944541AF1-119 GEN
Solar/Wind Harmer
7.534
960971AF2-388 GEN
Solar/Wind Harmer
19.66
942991AE2-321 GEN
Solar/Wind Harmer
17.957
274879MINONK ;1U
Solar/Wind Harmer
12.109
971333AH1-146 GEN
Solar/Wind Harmer
35.709
971335AH1-147 GEN
Solar/Wind Harmer
35.709
274764LEE CO EC;5U
Adder
16.168
274765LEE CO EC;6U
Adder
16.168
274762LEE CO EC;3U
Adder
16.13
274763LEE CO EC;4U
Adder
15.978
972267AH1-718 GEN
Adder
7.14
247621Y3-024
Adder
0.307
270471AD2-092_GEN
Solar/Wind Helper
1.743
971341AH1-150 GEN
Solar/Wind Harmer
13.312
971343AH1-151 GEN
Solar/Wind Harmer
13.312
247643Z2-116 C
Solar/Wind Harmer
0.141
945111AF1-176 GEN
Solar/Wind Harmer
11.286
944531AF1-118 GEN
Solar/Wind Harmer
69.657
274772LINCOLN ;3U
Adder
12.031
24441205WTRV SLR C
Solar/Wind Harmer
0.261
274724RIVER EC ;11
Adder
33.985
972231SS25-0005
Solar/Wind Harmer
18.18
972181SS23-001
Solar/Wind Harmer
11.362
274752CRETE EC ;2U
Adder
9.363
274753CRETE EC ;3U
Adder
9.363
247604X1-042
Adder
0.795
970707AG2-453 GEN
Solar/Wind Harmer
53.178
274802UNIV PARK;5U
Adder
11.035
274826FISK ;BP
Adder
20.719
276772AC2-154 GEN
Solar/Wind Harmer
5.271
276806AD2-047 C O1
Solar/Wind Harmer
20.222
970941AG2-585 GEN
Solar/Wind Harmer
23.629
274800UNIV PARK;3U
Adder
11.02
972038AH1-567 GEN2
Adder
0.69
972228AH1-698 GEN2
Adder
6.996
276897AD1-100 C
Solar/Wind Harmer
54.537
939351AE1-166 GEN
Solar/Wind Harmer
11.143
274676JOLIET 29;8U
Adder
55.43
274730ELWOOD EC;6P
Adder
30.711
274734ELWOOD EC;8P
Adder
30.711
274736ELWOOD EC;9P
Adder
30.711
274729ELWOOD EC;1P
Adder
30.71
276893AG1-478 C
Solar/Wind Harmer
0.78
943121AE2-341 GEN
Solar/Wind Harmer
27.85
943591AF1-030 GEN
Solar/Wind Harmer
18.567
270535AF1-215 GEN1
Solar/Wind Harmer
8.428
276694AA1-018 GEN2
Solar/Wind Harmer
11.537
274682WAUKEGAN ;7U
Adder
32.824
964401AG1-302 GEN
Solar/Wind Harmer
16.482
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
9.254
276799AD1-013 GEN
Solar/Wind Harmer
3.952
946671AF1-331 GEN
Solar/Wind Harmer
0.748
274855GSG-6 ;RU
Solar/Wind Harmer
6.597
274850MENDOTA H;RU
Solar/Wind Harmer
4.587
276602WESTBROOK C
Solar/Wind Harmer
3.797
276863AD2-134 GEN
Solar/Wind Harmer
3.19
959141AF2-205 GEN
Solar/Wind Harmer
10.776
972236AH1-702 GEN2
Adder
3.863
274760LEE CO EC;1U
Adder
16.13
274767LEE CO EC;8U
Adder
15.94
24728705AND G3
Adder
9.586
24728505AND G1
Adder
4.583
959091AF2-200 GEN
Solar/Wind Harmer
13.312
971599AH1-298 GEN
50/50
20.529
24727205RPMNG3
50/50
2.029
270144AC1-141 ST1_
50/50
4.29
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
9.733
270435AC2-044 GEN
Solar/Wind Harmer
4.292
971347AH1-153 GEN
Solar/Wind Harmer
32.134
270071AF1-092 GEN
Solar/Wind Harmer
31.087
971771AH1-392 GEN
Solar/Wind Harmer
18.192
971769AH1-391 GEN
Solar/Wind Harmer
19.979
960681AF2-359 GEN
Solar/Wind Harmer
7.542
944161AF1-084 GEN
Solar/Wind Harmer
4.339
274775LINCOLN ;6U
Adder
12.031
274776LINCOLN ;7U
Adder
12.031
274777LINCOLN ;8U
Adder
12.031
24729505KEY G4
Adder
12.581
274814UNIV PK N;0U
Adder
9.617
274807UNIV PK N;3U
Adder
9.597
274805UNIV PK N;1U
Adder
9.555
274811UNIV PK N;7U
Adder
9.534
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.684
960591AF2-350 GEN
Solar/Wind Harmer
18.903
972227AH1-698 GEN1
Adder
4.926
274687WILL CNTY;4U
Adder
52.424
274687WILL CNTY;4U
Adder
52.424
274675JOLIET 29;7U
Adder
57.484
274675JOLIET 29;7U
Adder
55.431
274728ELWOOD EC;5P
Adder
30.711
274731ELWOOD EC;2P
Adder
30.71
274733ELWOOD EC;3P
Adder
30.71
274735ELWOOD EC;4P
Adder
30.71
970833AG2-524 GEN
Solar/Wind Harmer
16.286
970833AG2-524 GEN
Solar/Wind Harmer
7.575
270536AF1-215 GEN2
Solar/Wind Harmer
8.428
274746AC1-111 G10
Adder
10.357
274744AC1-111 GEN8
Adder
10.357
958711AF2-162 GEN
Solar/Wind Harmer
1.82
958391AF2-133 GEN
Solar/Wind Harmer
16.304
971177AH1-047 GEN
Solar/Wind Harmer
10.518
276868AE1-113 GEN
Solar/Wind Harmer
18.162
276882AE2-255 GEN
Solar/Wind Harmer
6.054
971411AH1-196 GEN
Solar/Wind Harmer
26.803
971675AH1-338 GEN
Solar/Wind Harmer
32.161
971549AH1-272 GEN
Solar/Wind Harmer
32.93
274863CRW1-WTG
Solar/Wind Harmer
9.908
274864CRW2-WTG
Solar/Wind Harmer
9.908
274823ROCKFORD ;21
Adder
34.435
270284AF1-227 GEN1
Solar/Wind Helper
2.32
270286AF1-227 GEN2
Solar/Wind Helper
0.851
270287AF1-227 GEN3
Solar/Wind Helper
0.851
270054AF2-122 C O1
Solar/Wind Helper
1.203
971171AH1-044 GEN
Solar/Wind Harmer
13.312
24344105CKG2
50/50
16.752
24727005RPMNG1
50/50
2.039
270143AC1-141 CT2_
50/50
4.843
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.389
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
21.485
965421AG1-410 GEN
Solar/Wind Harmer
64.386
246936BC-WTG1
Solar/Wind Harmer
8.398
270489AE1-102 GEN1
Solar/Wind Harmer
2.79
970245AG2-165 GEN
Solar/Wind Harmer
37.203
270063AE2-323 C
Solar/Wind Harmer
4.466
270505AE1-170 C O1
Solar/Wind Harmer
30.011
945111AF1-176 GEN
Solar/Wind Harmer
35.611
270449AD2-020 GEN
Solar/Wind Harmer
5.542
943021AE2-325 GEN
Solar/Wind Harmer
7.201
972207SS24-0001
Solar/Wind Harmer
42.777
274773LINCOLN ;4U
Adder
12.031
274774LINCOLN ;5U
Adder
12.031
274723RIVER EC ;12
Adder
34.382
274751CRETE EC ;1U
Adder
9.363
274754CRETE EC ;4U
Adder
9.363
276164X3-005 C
Solar/Wind Harmer
1.342
274812UNIV PK N;8U
Adder
9.534
970373AG2-245 GEN
Solar/Wind Harmer
39.866
276776AD2-060 GEN
Solar/Wind Harmer
0.799
274801UNIV PARK;4U
Adder
11.02
941551AE2-152 GEN
Solar/Wind Harmer
8.523
274676JOLIET 29;8U
Adder
57.483
274674JOLIET 9 ;6U
Adder
28.794
274732ELWOOD EC;7P
Adder
30.711
274871GR RIDGE ;2U
Solar/Wind Harmer
14.337
270055AF2-134 C O1
Solar/Wind Harmer
5.618
274745AC1-111 GEN9
Adder
10.357
276691AA1-018 GEN1
Solar/Wind Harmer
0.851
274682WAUKEGAN ;7U
Adder
32.824
274828WAUKEGAN ;BP
Adder
20.145
958381AF2-132 GEN
Solar/Wind Harmer
16.482
964861AG1-349 GEN
Solar/Wind Harmer
14.25
971917AH1-482 GEN
Solar/Wind Harmer
16.444
960751AF2-366 GEN
Solar/Wind Harmer
5.194
962781AG1-127 GEN
Solar/Wind Harmer
17.216
274872LEEDK;1U
Solar/Wind Harmer
14.832
939401AE1-172 GEN
Solar/Wind Harmer
25.153
276901AD2-066 C O1
Solar/Wind Harmer
6.326
965651AG1-433 GEN
Solar/Wind Harmer
9.83
971997AH1-543 GEN
Solar/Wind Harmer
28.2
276861AD2-134 GEN
Solar/Wind Harmer
3.19
274822ROCKFORD ;11
Adder
34.687
972235AH1-702 GEN1
Adder
4.443
274761LEE CO EC;2U
Adder
16.13
274766LEE CO EC;7U
Adder
15.94
24728605AND G2
Adder
4.583
270349AD2-093_GEN
Solar/Wind Helper
1.743
957471AF2-041 GEN
Solar/Wind Harmer
19.968
959081AF2-199 GEN
Solar/Wind Harmer
6.656
971067AG2-660 GEN
Solar/Wind Harmer
1.548
944201AF1-088_MTX
Adder
133.023
957141AF2-008_MTX
Adder
52.933
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.282
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.706
MECLTFEXP_MEC->PJM
CLTF
24.31
SIGELTFEXP_SIGE->PJM
CLTF
0.467
LAGNLTFEXP_LAGN->PJM
CLTF
13.148
TVALTFEXP_TVA->PJM
CLTF
5.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.577
NYPJM->LTFIMP_NY
CLTF
3.196
LGEELTFEXP_LGEE->PJM
CLTF
4.313
WECLTFEXP_WEC->PJM
CLTF
6.719
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.8
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.633

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P7-1_#11010___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11010___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.44 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5823.68
MW Contribution:60.64
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.782
270102X2-052 ST
50/50
3.225
270100X2-052 CT1
50/50
2.972
270101X2-052 CT2
50/50
2.972
247620Y3-023
50/50
0.979
24729405KEY G3
50/50
0.737
24729305KEY G2
50/50
0.724
24729205KEY G1
50/50
0.721
970321AG2-212 GEN
Solar/Wind Harmer
37.354
970611AG2-400 GEN
Solar/Wind Harmer
20.561
270216AD2-079_GEN
Solar/Wind Harmer
1.23
270526AF1-158 GEN
Solar/Wind Harmer
9.119
24441505OLIV SLR
Solar/Wind Harmer
0.268
270142AC1-141 CT1_
50/50
4.85
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.183
24642205MAYFLWER
50/50
1.35
944961AF1-161 GEN
50/50
5.755
962601AG1-109 GEN
50/50
5.755
270043AE2-236 GEN
Solar/Wind Harmer
11.845
970349AG2-230 GEN
Solar/Wind Harmer
32.247
970513AG2-328 GEN
Solar/Wind Harmer
37.354
970517AG2-330 GEN
Solar/Wind Harmer
33.879
959331AF2-224 GEN
Solar/Wind Harmer
20.561
965021AG1-366 GEN
Solar/Wind Harmer
4.782
247643Z2-116 C
Solar/Wind Harmer
0.142
970031AG2-029 GEN
Solar/Wind Harmer
60.641
944531AF1-118 GEN
Solar/Wind Harmer
70.444
945111AF1-176 GEN
Solar/Wind Harmer
11.293
274772LINCOLN ;3U
Adder
12.075
24441205WTRV SLR C
Solar/Wind Harmer
0.261
274724RIVER EC ;11
Adder
34.095
972231SS25-0005
Solar/Wind Harmer
18.237
972181SS23-001
Solar/Wind Harmer
11.398
274752CRETE EC ;2U
Adder
9.392
274753CRETE EC ;3U
Adder
9.392
247604X1-042
Adder
0.796
970707AG2-453 GEN
Solar/Wind Harmer
53.373
274802UNIV PARK;5U
Adder
11.073
274826FISK ;BP
Adder
20.79
276772AC2-154 GEN
Solar/Wind Harmer
5.29
276806AD2-047 C O1
Solar/Wind Harmer
20.292
970941AG2-585 GEN
Solar/Wind Harmer
23.711
274800UNIV PARK;3U
Adder
11.059
972038AH1-567 GEN2
Adder
0.692
972228AH1-698 GEN2
Adder
7.021
276897AD1-100 C
Solar/Wind Harmer
54.734
939351AE1-166 GEN
Solar/Wind Harmer
11.184
274676JOLIET 29;8U
Adder
55.629
274730ELWOOD EC;6P
Adder
30.821
274734ELWOOD EC;8P
Adder
30.821
274736ELWOOD EC;9P
Adder
30.821
274729ELWOOD EC;1P
Adder
30.821
276893AG1-478 C
Solar/Wind Harmer
0.783
943121AE2-341 GEN
Solar/Wind Harmer
27.954
943591AF1-030 GEN
Solar/Wind Harmer
18.636
270535AF1-215 GEN1
Solar/Wind Harmer
8.453
276694AA1-018 GEN2
Solar/Wind Harmer
11.579
274682WAUKEGAN ;7U
Adder
32.947
964401AG1-302 GEN
Solar/Wind Harmer
16.533
274872LEEDK;1U
Solar/Wind Harmer
0.464
276805AD2-038 GEN
Solar/Wind Harmer
9.289
276799AD1-013 GEN
Solar/Wind Harmer
3.967
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
6.623
274850MENDOTA H;RU
Solar/Wind Harmer
4.605
276602WESTBROOK C
Solar/Wind Harmer
3.812
276863AD2-134 GEN
Solar/Wind Harmer
3.203
959141AF2-205 GEN
Solar/Wind Harmer
10.81
972236AH1-702 GEN2
Adder
3.879
274760LEE CO EC;1U
Adder
16.195
274767LEE CO EC;8U
Adder
16.004
24728705AND G3
Adder
9.666
24728505AND G1
Adder
4.622
959091AF2-200 GEN
Solar/Wind Harmer
28.198
24344105CKG2
50/50
16.81
270143AC1-141 CT2_
50/50
4.85
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.355
24307105BERRINSP G
50/50
0.043
970245AG2-165 GEN
Solar/Wind Harmer
37.354
965011AG1-365 GEN
Solar/Wind Harmer
20.561
270063AE2-323 C
Solar/Wind Harmer
4.439
270505AE1-170 C O1
Solar/Wind Harmer
30.051
945111AF1-176 GEN
Solar/Wind Harmer
35.632
270449AD2-020 GEN
Solar/Wind Harmer
5.549
943021AE2-325 GEN
Solar/Wind Harmer
7.21
972207SS24-0001
Solar/Wind Harmer
42.931
274773LINCOLN ;4U
Adder
12.075
274774LINCOLN ;5U
Adder
12.075
274723RIVER EC ;12
Adder
34.493
274751CRETE EC ;1U
Adder
9.392
274754CRETE EC ;4U
Adder
9.392
276164X3-005 C
Solar/Wind Harmer
1.346
274812UNIV PK N;8U
Adder
9.565
970373AG2-245 GEN
Solar/Wind Harmer
39.985
276776AD2-060 GEN
Solar/Wind Harmer
0.802
274801UNIV PARK;4U
Adder
11.059
941551AE2-152 GEN
Solar/Wind Harmer
8.554
274676JOLIET 29;8U
Adder
57.689
274674JOLIET 9 ;6U
Adder
28.897
274732ELWOOD EC;7P
Adder
30.821
274871GR RIDGE ;2U
Solar/Wind Harmer
14.39
270055AF2-134 C O1
Solar/Wind Harmer
5.635
274745AC1-111 GEN9
Adder
10.396
276691AA1-018 GEN1
Solar/Wind Harmer
0.854
274682WAUKEGAN ;7U
Adder
32.947
274828WAUKEGAN ;BP
Adder
20.221
958381AF2-132 GEN
Solar/Wind Harmer
16.533
964861AG1-349 GEN
Solar/Wind Harmer
14.293
971917AH1-482 GEN
Solar/Wind Harmer
16.494
965651AG1-433 GEN
Solar/Wind Harmer
9.938
960751AF2-366 GEN
Solar/Wind Harmer
5.214
962781AG1-127 GEN
Solar/Wind Harmer
17.282
274872LEEDK;1U
Solar/Wind Harmer
14.889
939401AE1-172 GEN
Solar/Wind Harmer
25.25
276901AD2-066 C O1
Solar/Wind Harmer
6.35
971997AH1-543 GEN
Solar/Wind Harmer
28.31
276861AD2-134 GEN
Solar/Wind Harmer
3.203
274822ROCKFORD ;11
Adder
34.824
972235AH1-702 GEN1
Adder
4.461
274761LEE CO EC;2U
Adder
16.195
274766LEE CO EC;7U
Adder
16.004
24728605AND G2
Adder
4.622
970091AG2-072 GEN
Adder
1.052
270349AD2-093_GEN
Solar/Wind Helper
1.724
957471AF2-041 GEN
Solar/Wind Harmer
42.297
959081AF2-199 GEN
Solar/Wind Harmer
14.099
971067AG2-660 GEN
Solar/Wind Harmer
3.279
971599AH1-298 GEN
50/50
20.751
270144AC1-141 ST1_
50/50
4.296
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.026
24729505KEY G4
50/50
13.5
971347AH1-153 GEN
Solar/Wind Harmer
32.247
270071AF1-092 GEN
Solar/Wind Harmer
31.239
971771AH1-392 GEN
Solar/Wind Harmer
18.224
971769AH1-391 GEN
Solar/Wind Harmer
20.026
960681AF2-359 GEN
Solar/Wind Harmer
7.564
944161AF1-084 GEN
Solar/Wind Harmer
4.344
274775LINCOLN ;6U
Adder
12.075
274776LINCOLN ;7U
Adder
12.075
274777LINCOLN ;8U
Adder
12.075
274814UNIV PK N;0U
Adder
9.649
274807UNIV PK N;3U
Adder
9.628
274805UNIV PK N;1U
Adder
9.586
274811UNIV PK N;7U
Adder
9.565
972037AH1-567 GEN1
Adder
0.348
274827FISK ;RP
Adder
14.734
960591AF2-350 GEN
Solar/Wind Harmer
18.969
972227AH1-698 GEN1
Adder
4.944
274687WILL CNTY;4U
Adder
52.61
274687WILL CNTY;4U
Adder
52.61
274675JOLIET 29;7U
Adder
57.69
274675JOLIET 29;7U
Adder
55.63
274728ELWOOD EC;5P
Adder
30.821
274731ELWOOD EC;2P
Adder
30.821
274733ELWOOD EC;3P
Adder
30.821
274735ELWOOD EC;4P
Adder
30.821
970833AG2-524 GEN
Solar/Wind Harmer
16.346
970833AG2-524 GEN
Solar/Wind Harmer
7.603
270536AF1-215 GEN2
Solar/Wind Harmer
8.453
274746AC1-111 G10
Adder
10.396
274744AC1-111 GEN8
Adder
10.396
958711AF2-162 GEN
Solar/Wind Harmer
1.84
958391AF2-133 GEN
Solar/Wind Harmer
16.354
971177AH1-047 GEN
Solar/Wind Harmer
10.559
276868AE1-113 GEN
Solar/Wind Harmer
18.232
276882AE2-255 GEN
Solar/Wind Harmer
6.078
971411AH1-196 GEN
Solar/Wind Harmer
26.908
971675AH1-338 GEN
Solar/Wind Harmer
32.287
971549AH1-272 GEN
Solar/Wind Harmer
32.985
274863CRW1-WTG
Solar/Wind Harmer
9.948
274864CRW2-WTG
Solar/Wind Harmer
9.948
274823ROCKFORD ;21
Adder
34.571
270284AF1-227 GEN1
Solar/Wind Helper
2.284
270286AF1-227 GEN2
Solar/Wind Helper
0.838
270287AF1-227 GEN3
Solar/Wind Helper
0.838
270054AF2-122 C O1
Solar/Wind Helper
1.189
971171AH1-044 GEN
Solar/Wind Harmer
28.198
965681AG1-436 GEN
Solar/Wind Harmer
25.028
965791AG1-447 GEN
Solar/Wind Harmer
12.805
957891AF2-083 GEN
Solar/Wind Harmer
6.749
960981AF2-389 GEN
Solar/Wind Harmer
3.024
961051AF2-396 GEN
Solar/Wind Harmer
31.526
961051AF2-396 GEN
Solar/Wind Harmer
14.663
274770LINCOLN ;1U
Adder
12.075
274771LINCOLN ;2U
Adder
12.075
274808UNIV PK N;4U
Adder
9.523
274803UNIV PARK;6U
Adder
11.073
972259AH1-714 GEN
Adder
36.205
274888KELLY CRK;1U
Solar/Wind Harmer
11.199
274887GEN-1.85
Solar/Wind Harmer
10.111
276843GEN-1.7
Solar/Wind Harmer
1.088
958011AF2-095 GEN
Solar/Wind Harmer
27.315
274674JOLIET 9 ;6U
Adder
28.897
274847GR RIDGE ;BU
Solar/Wind Harmer
9.466
971573AH1-285 GEN
Solar/Wind Harmer
15.928
274695ROCKY RD ;2P
Adder
20.447
274693ROCKY RD ;1P
Adder
20.246
274697ROCKY RD ;3P
Adder
5.555
274696ROCKY RD ;4P
Adder
20.929
958481AF2-142 GEN
Solar/Wind Harmer
27.523
274861TOP CROP ;1U
Solar/Wind Harmer
11.112
274862TOP CROP ;2U
Solar/Wind Harmer
9.279
274683WAUKEGAN ;8U
Adder
38.577
274683WAUKEGAN ;8U
Adder
32.519
962691AG1-118 GEN
Solar/Wind Harmer
54.666
944541AF1-119 GEN
Solar/Wind Harmer
7.616
960971AF2-388 GEN
Solar/Wind Harmer
19.875
970921AG2-575 GEN
Solar/Wind Harmer
18.172
970921AG2-575 GEN
Solar/Wind Harmer
4.226
958491AF2-143 GEN
Solar/Wind Harmer
27.161
942991AE2-321 GEN
Solar/Wind Harmer
18.026
274879MINONK ;1U
Solar/Wind Harmer
12.156
971333AH1-146 GEN
Solar/Wind Harmer
35.848
971335AH1-147 GEN
Solar/Wind Harmer
35.848
274764LEE CO EC;5U
Adder
16.233
274765LEE CO EC;6U
Adder
16.233
274762LEE CO EC;3U
Adder
16.195
274763LEE CO EC;4U
Adder
16.043
972267AH1-718 GEN
Adder
7.169
247621Y3-024
Adder
0.306
270471AD2-092_GEN
Solar/Wind Helper
1.724
971341AH1-150 GEN
Solar/Wind Harmer
28.198
971343AH1-151 GEN
Solar/Wind Harmer
28.198
944201AF1-088_MTX
Adder
133.959
957141AF2-008_MTX
Adder
66.98
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.245
CBM West 1LTFEXP_CBM-W1->PJM
CBM
202.385
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.042
MECLTFEXP_MEC->PJM
CLTF
24.435
SIGELTFEXP_SIGE->PJM
CLTF
0.471
LAGNLTFEXP_LAGN->PJM
CLTF
13.321
TVALTFEXP_TVA->PJM
CLTF
5.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.715
NYPJM->LTFIMP_NY
CLTF
3.14
LGEELTFEXP_LGEE->PJM
CLTF
4.376
WECLTFEXP_WEC->PJM
CLTF
6.746
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.739
AG2-052LTFEXP_AG2-052->PJM
LTF
0.423
AH1-155LTFEXP_AH1-155->PJM
LTF
0.635

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#6463_16757_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#6463_16757_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.68 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5781.3
MW Contribution:9.25
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
16.743
24727005RPMNG1
50/50
2.036
270143AC1-141 CT2_
50/50
4.84
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.369
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
14.965
965421AG1-410 GEN
Solar/Wind Harmer
44.849
246936BC-WTG1
Solar/Wind Harmer
0.606
270489AE1-102 GEN1
Solar/Wind Harmer
1.943
970245AG2-165 GEN
Solar/Wind Harmer
6.295
270063AE2-323 C
Solar/Wind Harmer
0.012
270505AE1-170 C O1
Solar/Wind Harmer
14.646
945111AF1-176 GEN
Solar/Wind Harmer
24.826
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.196
274773LINCOLN ;4U
Adder
16.368
274774LINCOLN ;5U
Adder
16.368
274723RIVER EC ;12
Adder
34.361
274751CRETE EC ;1U
Adder
15.774
274754CRETE EC ;4U
Adder
15.774
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
9.528
970373AG2-245 GEN
Solar/Wind Harmer
27.796
274801UNIV PARK;4U
Adder
11.014
276776AD2-060 GEN
Solar/Wind Harmer
1.376
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
57.45
274674JOLIET 9 ;6U
Adder
28.777
274732ELWOOD EC;7P
Adder
30.693
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.01
274745AC1-111 GEN9
Adder
10.351
276691AA1-018 GEN1
Solar/Wind Harmer
1.544
274682WAUKEGAN ;7U
Adder
32.805
274828WAUKEGAN ;BP
Adder
20.134
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
16.434
962781AG1-127 GEN
Solar/Wind Harmer
12.012
274872LEEDK;1U
Solar/Wind Harmer
0.008
939401AE1-172 GEN
Solar/Wind Harmer
9.413
276901AD2-066 C O1
Solar/Wind Harmer
0.012
965651AG1-433 GEN
Solar/Wind Harmer
3.678
971997AH1-543 GEN
Solar/Wind Harmer
6.554
276861AD2-134 GEN
Solar/Wind Harmer
0.223
957471AF2-041 GEN
Solar/Wind Harmer
37.108
959081AF2-199 GEN
Solar/Wind Harmer
12.369
971067AG2-660 GEN
Solar/Wind Harmer
4.123
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
34.667
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
15.377
972235AH1-702 GEN1
Adder
4.441
970819AG2-516 GEN
Solar/Wind Harmer
14.695
958861AF2-177 GEN
Solar/Wind Harmer
5.294
971475AH1-234 GEN
Solar/Wind Harmer
5.925
970569AG2-363 GEN
Solar/Wind Harmer
36.555
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
16.12
274766LEE CO EC;7U
Adder
15.93
276158O29GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
3.153
274877BISHOP HL;1U
Solar/Wind Harmer
0.397
24791305MDL-5G
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
16.327
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
9.129
247521TR3_G114
Solar/Wind Harmer
0.393
270246TR4_N_V150
Solar/Wind Harmer
0.07
970291AG2-192 GEN
Solar/Wind Harmer
1.393
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
4.146
963741AG1-226 GEN
Solar/Wind Harmer
24.913
276615X2-022 GEN
Solar/Wind Harmer
0.11
270032AE2-172
Solar/Wind Harmer
6.993
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.203
965031AG1-367 GEN
Solar/Wind Harmer
10.168
276903AD2-071 C
Solar/Wind Harmer
11.298
965911AG1-460 GEN
Solar/Wind Harmer
2.014
970825AG2-519 GEN
Solar/Wind Harmer
3.499
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.684
247536S-71 GEN
Solar/Wind Harmer
0.341
24728605AND G2
Adder
4.579
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970333AG2-219 GEN
Solar/Wind Harmer
5.528
970773AG2-487 GEN
Solar/Wind Harmer
1.34
270349AD2-093_GEN
Solar/Wind Helper
1.737
970615AG2-402 GEN
50/50
4.988
270102X2-052 ST
50/50
3.214
270100X2-052 CT1
50/50
2.961
270101X2-052 CT2
50/50
2.961
247620Y3-023
50/50
0.98
970611AG2-400 GEN
Solar/Wind Harmer
14.965
970627AG2-408 GEN
Solar/Wind Harmer
4.49
246938BC-WTG3
Solar/Wind Harmer
0.542
246937BC-WTG2
Solar/Wind Harmer
0.606
970321AG2-212 GEN
Solar/Wind Harmer
6.295
270216AD2-079_GEN
Solar/Wind Harmer
0.002
270526AF1-158 GEN
Solar/Wind Harmer
0.017
957891AF2-083 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
17.4
965791AG1-447 GEN
Solar/Wind Harmer
12.76
961051AF2-396 GEN
Solar/Wind Harmer
27.667
961051AF2-396 GEN
Solar/Wind Harmer
18.445
274770LINCOLN ;1U
Adder
16.368
274771LINCOLN ;2U
Adder
16.368
274808UNIV PK N;4U
Adder
9.487
274803UNIV PARK;6U
Adder
11.029
972259AH1-714 GEN
Adder
36.054
274888KELLY CRK;1U
Solar/Wind Harmer
0.774
274887GEN-1.85
Solar/Wind Harmer
0.347
276843GEN-1.7
Solar/Wind Harmer
0.427
958011AF2-095 GEN
Solar/Wind Harmer
18.98
274674JOLIET 9 ;6U
Adder
28.777
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.397
274695ROCKY RD ;2P
Adder
20.358
274693ROCKY RD ;1P
Adder
20.158
274697ROCKY RD ;3P
Adder
5.53
274696ROCKY RD ;4P
Adder
20.838
958481AF2-142 GEN
Solar/Wind Harmer
19.12
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.724
274683WAUKEGAN ;8U
Adder
38.41
274683WAUKEGAN ;8U
Adder
32.378
962691AG1-118 GEN
Solar/Wind Harmer
37.971
970921AG2-575 GEN
Solar/Wind Harmer
12.623
970921AG2-575 GEN
Solar/Wind Harmer
4.208
958491AF2-143 GEN
Solar/Wind Harmer
18.868
944541AF1-119 GEN
Solar/Wind Harmer
0.84
960971AF2-388 GEN
Solar/Wind Harmer
7.355
942991AE2-321 GEN
Solar/Wind Harmer
13.981
274879MINONK ;1U
Solar/Wind Harmer
0.528
971333AH1-146 GEN
Solar/Wind Harmer
24.899
971335AH1-147 GEN
Solar/Wind Harmer
24.899
971341AH1-150 GEN
Solar/Wind Harmer
24.739
971343AH1-151 GEN
Solar/Wind Harmer
24.739
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.288
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.879
274764LEE CO EC;5U
Adder
16.158
274765LEE CO EC;6U
Adder
16.158
274762LEE CO EC;3U
Adder
16.12
274763LEE CO EC;4U
Adder
15.968
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
7.136
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
276741O09 GEN1
Solar/Wind Harmer
0.425
276708O09 GEN2
Solar/Wind Harmer
0.425
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.467
276646AC1-214 GEN2
Solar/Wind Harmer
0.467
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.81
966841AG1-555 GEN
Solar/Wind Harmer
1.27
270599AE1-208 GEN
Solar/Wind Harmer
9.916
270031AE2-169
Solar/Wind Harmer
5.95
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
6.141
971613AH1-306 GEN
Solar/Wind Harmer
5.035
276916AD2-100_GEN
Solar/Wind Harmer
20.939
276911AD2-131_GEN
Solar/Wind Harmer
1.379
960441AF2-335 GEN
Solar/Wind Harmer
9.92
970825AG2-519 GEN
Solar/Wind Harmer
10.923
945391AF1-204 GEN
Solar/Wind Harmer
9.973
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.306
970623AG2-406 GEN
Solar/Wind Harmer
1.558
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
5.849
970883AG2-550 GEN
Solar/Wind Harmer
7.917
970885AG2-551 GEN
Solar/Wind Harmer
2.639
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.933
24727105RPMNG2
50/50
2.043
965431AG1-411 GEN
50/50
24.916
270142AC1-141 CT1_
50/50
4.84
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.145
24642205MAYFLWER
50/50
1.347
944961AF1-161 GEN
50/50
5.744
962601AG1-109 GEN
50/50
5.744
270043AE2-236 GEN
Solar/Wind Harmer
9.614
959331AF2-224 GEN
Solar/Wind Harmer
10.476
965021AG1-366 GEN
Solar/Wind Harmer
4.988
270491AE1-102 GEN2
Solar/Wind Harmer
1.943
970349AG2-230 GEN
Solar/Wind Harmer
22.406
970513AG2-328 GEN
Solar/Wind Harmer
6.295
970517AG2-330 GEN
Solar/Wind Harmer
37.773
970031AG2-029 GEN
Solar/Wind Harmer
9.246
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.278
944531AF1-118 GEN
Solar/Wind Harmer
62.173
274772LINCOLN ;3U
Adder
16.368
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
33.965
274752CRETE EC ;2U
Adder
15.774
274753CRETE EC ;3U
Adder
15.774
247604X1-042
Adder
0.795
970707AG2-453 GEN
Solar/Wind Harmer
43.26
274802UNIV PARK;5U
Adder
11.029
274826FISK ;BP
Adder
20.707
274800UNIV PARK;3U
Adder
11.014
972038AH1-567 GEN2
Adder
0.689
276806AD2-047 C O1
Solar/Wind Harmer
7.469
970941AG2-585 GEN
Solar/Wind Harmer
16.476
972228AH1-698 GEN2
Adder
6.992
276897AD1-100 C
Solar/Wind Harmer
0.017
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
55.398
274729ELWOOD EC;1P
Adder
30.692
274730ELWOOD EC;6P
Adder
30.693
274734ELWOOD EC;8P
Adder
30.693
274736ELWOOD EC;9P
Adder
30.693
276893AG1-478 C
Solar/Wind Harmer
0.516
943121AE2-341 GEN
Solar/Wind Harmer
21.706
943591AF1-030 GEN
Solar/Wind Harmer
14.435
270535AF1-215 GEN1
Solar/Wind Harmer
0.016
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
32.805
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
0.004
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.457
274850MENDOTA H;RU
Solar/Wind Harmer
0.147
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
959091AF2-200 GEN
Solar/Wind Harmer
24.739
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.861
970571AG2-364 GEN
Solar/Wind Harmer
24.37
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
16.12
274767LEE CO EC;8U
Adder
15.93
276157O29GEN1
Solar/Wind Harmer
1.927
274878BISHOP HL;2U
Solar/Wind Harmer
0.397
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
11.712
942111AE2-223 GEN
Solar/Wind Harmer
3.79
965931AG1-462 GEN
Solar/Wind Harmer
29.323
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
34.294
959611AF2-252 GEN
Solar/Wind Harmer
3.81
247642Z2-115 C
Solar/Wind Harmer
0.005
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.07
970289AG2-191 GEN
Solar/Wind Harmer
1.179
970291AG2-192 GEN
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.944
276668AB2-070 GEN1
Solar/Wind Harmer
0.39
276621W2-048 GEN
Solar/Wind Harmer
0.529
276838X2-022 GEN2
Solar/Wind Harmer
0.591
971617AH1-308 GEN
Solar/Wind Harmer
8.654
958821AF2-173 GEN
Solar/Wind Harmer
14.235
270004AE1-209 GEN
Solar/Wind Harmer
2.203
942481AE2-261 GEN
Solar/Wind Harmer
30.115
946031AF1-268 GEN
Solar/Wind Harmer
9.153
970193AG2-126 GEN
Solar/Wind Harmer
14.08
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.732
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.579
970243AG2-164 GEN
Solar/Wind Harmer
4.523
970519AG2-331 GEN
Solar/Wind Harmer
20.102
970699AG2-449 GEN
Solar/Wind Harmer
1.933
270356AE2-297 GEN
Solar/Wind Harmer
0.01
971599AH1-298 GEN
50/50
20.512
24727205RPMNG3
50/50
2.026
270144AC1-141 ST1_
50/50
4.287
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.893
971347AH1-153 GEN
Solar/Wind Harmer
22.406
270071AF1-092 GEN
Solar/Wind Harmer
27.685
971771AH1-392 GEN
Solar/Wind Harmer
14.093
971619AH1-309 GEN
Solar/Wind Harmer
6.277
971769AH1-391 GEN
Solar/Wind Harmer
15.555
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274775LINCOLN ;6U
Adder
16.368
274776LINCOLN ;7U
Adder
16.368
274777LINCOLN ;8U
Adder
16.368
24729505KEY G4
Adder
12.57
274814UNIV PK N;0U
Adder
9.612
274807UNIV PK N;3U
Adder
9.591
274805UNIV PK N;1U
Adder
9.549
274811UNIV PK N;7U
Adder
9.528
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.675
960591AF2-350 GEN
Solar/Wind Harmer
13.18
972227AH1-698 GEN1
Adder
4.923
274687WILL CNTY;4U
Adder
52.393
274687WILL CNTY;4U
Adder
52.393
274675JOLIET 29;7U
Adder
57.451
274675JOLIET 29;7U
Adder
55.399
274731ELWOOD EC;2P
Adder
30.692
274733ELWOOD EC;3P
Adder
30.692
274735ELWOOD EC;4P
Adder
30.692
274728ELWOOD EC;5P
Adder
30.693
970833AG2-524 GEN
Solar/Wind Harmer
14.308
970833AG2-524 GEN
Solar/Wind Harmer
9.539
270536AF1-215 GEN2
Solar/Wind Harmer
0.016
274746AC1-111 G10
Adder
10.351
274744AC1-111 GEN8
Adder
10.351
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971177AH1-047 GEN
Solar/Wind Harmer
7.718
276868AE1-113 GEN
Solar/Wind Harmer
2.511
276882AE2-255 GEN
Solar/Wind Harmer
1.463
971411AH1-196 GEN
Solar/Wind Harmer
18.689
971675AH1-338 GEN
Solar/Wind Harmer
4.859
971549AH1-272 GEN
Solar/Wind Harmer
25.626
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
24.739
274823ROCKFORD ;21
Adder
34.415
971611AH1-305 GEN
Solar/Wind Harmer
7.323
963791AG1-232 GEN
Solar/Wind Harmer
16.568
276612AE2-035 GEN
Solar/Wind Harmer
0.003
965101AG1-375 GEN
Solar/Wind Harmer
12.216
926823AC1-168 GEN
Solar/Wind Harmer
2.071
970169AG2-114 GEN
Solar/Wind Harmer
12.156
971681AH1-341 GEN
Solar/Wind Harmer
19.553
961011AF2-392 GEN
Solar/Wind Harmer
7.036
965041AG1-368 GEN
Solar/Wind Harmer
11.932
957751AF2-069 GEN
Solar/Wind Harmer
0.392
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
12.245
941731AE2-173 GEN
Solar/Wind Harmer
9.718
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
6.48
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.707
971609AH1-304 GEN
Solar/Wind Harmer
1.767
965051AG1-369 GEN
Solar/Wind Harmer
5.379
970289AG2-191 GEN
Solar/Wind Harmer
2.036
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.39
276848AB2-070 GEN3
Solar/Wind Harmer
0.388
270594AE1-207 GEN
Solar/Wind Harmer
11.748
270024AE2-089 GEN
Solar/Wind Harmer
0.011
970115AG2-085 GEN
Solar/Wind Harmer
3.968
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
5.647
270240V3-007_GEN2
Solar/Wind Harmer
0.003
247607V1-011 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
10.94
971673AH1-337 GEN
Solar/Wind Harmer
4.593
270284AF1-227 GEN1
Solar/Wind Helper
2.302
270286AF1-227 GEN2
Solar/Wind Helper
0.844
270287AF1-227 GEN3
Solar/Wind Helper
0.844
270054AF2-122 C O1
Solar/Wind Helper
1.201
270471AD2-092_GEN
Solar/Wind Helper
1.737
944201AF1-088_MTX
Adder
132.938
957141AF2-008_MTX
Adder
17.09
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.281
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.695
MECLTFEXP_MEC->PJM
CLTF
24.295
SIGELTFEXP_SIGE->PJM
CLTF
0.466
LAGNLTFEXP_LAGN->PJM
CLTF
13.14
TVALTFEXP_TVA->PJM
CLTF
5.018
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.505
NYPJM->LTFIMP_NY
CLTF
3.194
LGEELTFEXP_LGEE->PJM
CLTF
4.31
WECLTFEXP_WEC->PJM
CLTF
6.715
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.799
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.632

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P7-1_#17567_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#17567_SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.6 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5777.18
MW Contribution:57.56
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
19.41
270144AC1-141 ST1_
50/50
4.168
24643105BUCHANAN
50/50
0.025
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
31.136
24344105CKG2
50/50
16.266
270143AC1-141 CT2_
50/50
4.706
24639705ELKHART HY
50/50
0.317
970521AG2-332 GEN
50/50
22.545
24307105BERRINSP G
50/50
0.042
970245AG2-165 GEN
Solar/Wind Harmer
36.028
270505AE1-170 C O1
Solar/Wind Harmer
29.203
945111AF1-176 GEN
Solar/Wind Harmer
34.591
270063AE2-323 C
Solar/Wind Harmer
4.268
270449AD2-020 GEN
Solar/Wind Harmer
5.404
943021AE2-325 GEN
Solar/Wind Harmer
7.022
965011AG1-365 GEN
Solar/Wind Harmer
18.821
972207SS24-0001
Solar/Wind Harmer
41.419
274773LINCOLN ;4U
Adder
11.65
270102X2-052 ST
50/50
3.121
270100X2-052 CT1
50/50
2.876
270101X2-052 CT2
50/50
2.876
247620Y3-023
50/50
0.945
970615AG2-402 GEN
50/50
4.377
970321AG2-212 GEN
Solar/Wind Harmer
36.028
270216AD2-079_GEN
Solar/Wind Harmer
1.189
270526AF1-158 GEN
Solar/Wind Harmer
8.831
957891AF2-083 GEN
Solar/Wind Harmer
6.556
960981AF2-389 GEN
Solar/Wind Harmer
2.938
24441505OLIV SLR
Solar/Wind Harmer
0.26
965681AG1-436 GEN
Solar/Wind Harmer
24.212
965791AG1-447 GEN
Solar/Wind Harmer
12.387
961051AF2-396 GEN
Solar/Wind Harmer
30.667
961051AF2-396 GEN
Solar/Wind Harmer
14.264
970611AG2-400 GEN
Solar/Wind Harmer
18.821
274770LINCOLN ;1U
Adder
11.65
274771LINCOLN ;2U
Adder
11.65
274808UNIV PK N;4U
Adder
9.189
274803UNIV PARK;6U
Adder
10.683
972259AH1-714 GEN
Adder
34.925
274888KELLY CRK;1U
Solar/Wind Harmer
10.804
274887GEN-1.85
Solar/Wind Harmer
9.754
276843GEN-1.7
Solar/Wind Harmer
1.049
958011AF2-095 GEN
Solar/Wind Harmer
26.352
274674JOLIET 9 ;6U
Adder
27.874
274847GR RIDGE ;BU
Solar/Wind Harmer
9.13
971573AH1-285 GEN
Solar/Wind Harmer
15.361
274695ROCKY RD ;2P
Adder
19.718
274693ROCKY RD ;1P
Adder
19.524
274697ROCKY RD ;3P
Adder
5.356
270071AF1-092 GEN
Solar/Wind Harmer
29.457
971771AH1-392 GEN
Solar/Wind Harmer
17.645
971769AH1-391 GEN
Solar/Wind Harmer
19.396
960681AF2-359 GEN
Solar/Wind Harmer
7.318
944161AF1-084 GEN
Solar/Wind Harmer
4.238
274775LINCOLN ;6U
Adder
11.65
274776LINCOLN ;7U
Adder
11.65
274777LINCOLN ;8U
Adder
11.65
24729505KEY G4
Adder
11.965
274814UNIV PK N;0U
Adder
9.311
274807UNIV PK N;3U
Adder
9.29
274805UNIV PK N;1U
Adder
9.25
274811UNIV PK N;7U
Adder
9.23
972037AH1-567 GEN1
Adder
0.335
274827FISK ;RP
Adder
14.215
960591AF2-350 GEN
Solar/Wind Harmer
18.3
972227AH1-698 GEN1
Adder
4.769
274687WILL CNTY;4U
Adder
50.75
274687WILL CNTY;4U
Adder
50.75
274675JOLIET 29;7U
Adder
55.649
274675JOLIET 29;7U
Adder
53.661
274731ELWOOD EC;2P
Adder
29.73
274733ELWOOD EC;3P
Adder
29.73
274735ELWOOD EC;4P
Adder
29.73
274728ELWOOD EC;5P
Adder
29.73
970833AG2-524 GEN
Solar/Wind Harmer
15.767
970833AG2-524 GEN
Solar/Wind Harmer
7.333
270536AF1-215 GEN2
Solar/Wind Harmer
8.164
274746AC1-111 G10
Adder
10.026
274744AC1-111 GEN8
Adder
10.026
971549AH1-272 GEN
Solar/Wind Harmer
32.892
958391AF2-133 GEN
Solar/Wind Harmer
15.781
971177AH1-047 GEN
Solar/Wind Harmer
10.18
276868AE1-113 GEN
Solar/Wind Harmer
17.58
276882AE2-255 GEN
Solar/Wind Harmer
5.86
971411AH1-196 GEN
Solar/Wind Harmer
25.942
274774LINCOLN ;5U
Adder
11.65
274723RIVER EC ;12
Adder
33.283
274751CRETE EC ;1U
Adder
9.065
274754CRETE EC ;4U
Adder
9.065
276164X3-005 C
Solar/Wind Harmer
1.299
274812UNIV PK N;8U
Adder
9.23
970373AG2-245 GEN
Solar/Wind Harmer
38.641
274801UNIV PARK;4U
Adder
10.668
276776AD2-060 GEN
Solar/Wind Harmer
0.774
941551AE2-152 GEN
Solar/Wind Harmer
8.252
274676JOLIET 29;8U
Adder
55.648
274674JOLIET 9 ;6U
Adder
27.874
274732ELWOOD EC;7P
Adder
29.73
274871GR RIDGE ;2U
Solar/Wind Harmer
13.88
270055AF2-134 C O1
Solar/Wind Harmer
5.442
274745AC1-111 GEN9
Adder
10.026
276691AA1-018 GEN1
Solar/Wind Harmer
0.824
274682WAUKEGAN ;7U
Adder
31.772
274828WAUKEGAN ;BP
Adder
19.5
958381AF2-132 GEN
Solar/Wind Harmer
15.959
964861AG1-349 GEN
Solar/Wind Harmer
13.796
971917AH1-482 GEN
Solar/Wind Harmer
15.92
960751AF2-366 GEN
Solar/Wind Harmer
5.027
962781AG1-127 GEN
Solar/Wind Harmer
16.663
274872LEEDK;1U
Solar/Wind Harmer
14.356
939401AE1-172 GEN
Solar/Wind Harmer
24.351
276901AD2-066 C O1
Solar/Wind Harmer
6.124
971997AH1-543 GEN
Solar/Wind Harmer
27.297
276861AD2-134 GEN
Solar/Wind Harmer
3.088
965651AG1-433 GEN
Solar/Wind Harmer
9.384
274822ROCKFORD ;11
Adder
33.569
972235AH1-702 GEN1
Adder
4.3
274761LEE CO EC;2U
Adder
15.609
274766LEE CO EC;7U
Adder
15.425
24728605AND G2
Adder
4.468
972301AH1-735 GEN
Adder
2.524
270349AD2-093_GEN
Solar/Wind Helper
2.215
957471AF2-041 GEN
Solar/Wind Harmer
40.776
959081AF2-199 GEN
Solar/Wind Harmer
13.592
971067AG2-660 GEN
Solar/Wind Harmer
3.161
971675AH1-338 GEN
Solar/Wind Harmer
31.127
274863CRW1-WTG
Solar/Wind Harmer
9.592
274864CRW2-WTG
Solar/Wind Harmer
9.592
958711AF2-162 GEN
Solar/Wind Harmer
1.737
274823ROCKFORD ;21
Adder
33.326
270054AF2-122 C O1
Solar/Wind Helper
1.3
971171AH1-044 GEN
Solar/Wind Harmer
27.184
274696ROCKY RD ;4P
Adder
20.183
958481AF2-142 GEN
Solar/Wind Harmer
26.544
274861TOP CROP ;1U
Solar/Wind Harmer
10.717
274862TOP CROP ;2U
Solar/Wind Harmer
8.949
274683WAUKEGAN ;8U
Adder
37.2
274683WAUKEGAN ;8U
Adder
31.358
962691AG1-118 GEN
Solar/Wind Harmer
52.711
970921AG2-575 GEN
Solar/Wind Harmer
17.522
970921AG2-575 GEN
Solar/Wind Harmer
4.075
958491AF2-143 GEN
Solar/Wind Harmer
26.192
942991AE2-321 GEN
Solar/Wind Harmer
17.38
274879MINONK ;1U
Solar/Wind Harmer
11.721
971333AH1-146 GEN
Solar/Wind Harmer
34.561
971335AH1-147 GEN
Solar/Wind Harmer
34.561
944541AF1-119 GEN
Solar/Wind Harmer
7.192
960971AF2-388 GEN
Solar/Wind Harmer
18.769
274764LEE CO EC;5U
Adder
15.646
274765LEE CO EC;6U
Adder
15.646
274762LEE CO EC;3U
Adder
15.609
274763LEE CO EC;4U
Adder
15.462
972267AH1-718 GEN
Adder
6.909
247621Y3-024
Adder
0.305
270471AD2-092_GEN
Solar/Wind Helper
2.215
971341AH1-150 GEN
Solar/Wind Harmer
27.184
971343AH1-151 GEN
Solar/Wind Harmer
27.184
270142AC1-141 CT1_
50/50
4.706
24344005CKG1
50/50
12.844
24641605TWIN BRNCH
50/50
0.034
24642205MAYFLWER
50/50
1.31
944961AF1-161 GEN
50/50
5.605
962601AG1-109 GEN
50/50
5.605
970349AG2-230 GEN
Solar/Wind Harmer
31.136
270043AE2-236 GEN
Solar/Wind Harmer
11.189
970513AG2-328 GEN
Solar/Wind Harmer
36.028
970517AG2-330 GEN
Solar/Wind Harmer
32.677
247643Z2-116 C
Solar/Wind Harmer
0.137
945111AF1-176 GEN
Solar/Wind Harmer
10.963
970031AG2-029 GEN
Solar/Wind Harmer
57.557
24441205WTRV SLR C
Solar/Wind Harmer
0.256
944531AF1-118 GEN
Solar/Wind Harmer
66.164
959331AF2-224 GEN
Solar/Wind Harmer
18.821
965021AG1-366 GEN
Solar/Wind Harmer
4.377
274772LINCOLN ;3U
Adder
11.65
247604X1-042
Adder
0.782
274724RIVER EC ;11
Adder
32.899
972231SS25-0005
Solar/Wind Harmer
17.6
972181SS23-001
Solar/Wind Harmer
11
274752CRETE EC ;2U
Adder
9.065
274753CRETE EC ;3U
Adder
9.065
970707AG2-453 GEN
Solar/Wind Harmer
51.485
274802UNIV PARK;5U
Adder
10.683
274826FISK ;BP
Adder
20.057
970941AG2-585 GEN
Solar/Wind Harmer
22.875
274800UNIV PARK;3U
Adder
10.668
972038AH1-567 GEN2
Adder
0.668
276772AC2-154 GEN
Solar/Wind Harmer
5.103
276806AD2-047 C O1
Solar/Wind Harmer
19.577
972228AH1-698 GEN2
Adder
6.773
276897AD1-100 C
Solar/Wind Harmer
52.8
939351AE1-166 GEN
Solar/Wind Harmer
10.788
274676JOLIET 29;8U
Adder
53.66
274729ELWOOD EC;1P
Adder
29.73
274730ELWOOD EC;6P
Adder
29.73
274734ELWOOD EC;8P
Adder
29.73
274736ELWOOD EC;9P
Adder
29.73
276893AG1-478 C
Solar/Wind Harmer
0.755
943121AE2-341 GEN
Solar/Wind Harmer
26.96
943591AF1-030 GEN
Solar/Wind Harmer
17.973
270535AF1-215 GEN1
Solar/Wind Harmer
8.164
276694AA1-018 GEN2
Solar/Wind Harmer
11.167
274682WAUKEGAN ;7U
Adder
31.772
964401AG1-302 GEN
Solar/Wind Harmer
15.959
274872LEEDK;1U
Solar/Wind Harmer
0.447
276805AD2-038 GEN
Solar/Wind Harmer
8.958
276799AD1-013 GEN
Solar/Wind Harmer
3.825
946671AF1-331 GEN
Solar/Wind Harmer
0.724
274855GSG-6 ;RU
Solar/Wind Harmer
6.385
274850MENDOTA H;RU
Solar/Wind Harmer
4.44
276602WESTBROOK C
Solar/Wind Harmer
3.675
276863AD2-134 GEN
Solar/Wind Harmer
3.088
959141AF2-205 GEN
Solar/Wind Harmer
10.429
972236AH1-702 GEN2
Adder
3.739
274760LEE CO EC;1U
Adder
15.609
274767LEE CO EC;8U
Adder
15.425
24728705AND G3
Adder
9.344
24728505AND G1
Adder
4.468
959091AF2-200 GEN
Solar/Wind Harmer
27.184
944201AF1-088_MTX
Adder
128.814
957141AF2-008_MTX
Adder
64.407
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.385
CBM West 1LTFEXP_CBM-W1->PJM
CBM
204.072
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.768
MECLTFEXP_MEC->PJM
CLTF
23.493
SIGELTFEXP_SIGE->PJM
CLTF
0.454
LAGNLTFEXP_LAGN->PJM
CLTF
12.499
TVALTFEXP_TVA->PJM
CLTF
4.733
CBM West 2LTFEXP_CBM-W2->PJM
CBM
114.06
NYPJM->LTFIMP_NY
CLTF
3.145
LGEELTFEXP_LGEE->PJM
CLTF
4.258
WECLTFEXP_WEC->PJM
CLTF
6.502
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.96
AG2-052LTFEXP_AG2-052->PJM
LTF
0.408
AH1-155LTFEXP_AH1-155->PJM
LTF
0.612

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.5 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5605.79
MW Contribution:55.42
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
12.539
270142AC1-141 CT1_
50/50
4.589
24641605TWIN BRNCH
50/50
0.033
24642205MAYFLWER
50/50
1.278
944961AF1-161 GEN
50/50
5.457
962601AG1-109 GEN
50/50
5.457
970349AG2-230 GEN
Solar/Wind Harmer
30.529
970513AG2-328 GEN
Solar/Wind Harmer
35.447
970517AG2-330 GEN
Solar/Wind Harmer
32.149
270043AE2-236 GEN
Solar/Wind Harmer
10.823
247643Z2-116 C
Solar/Wind Harmer
0.133
945111AF1-176 GEN
Solar/Wind Harmer
10.67
970031AG2-029 GEN
Solar/Wind Harmer
55.416
24441205WTRV SLR C
Solar/Wind Harmer
0.249
274772LINCOLN ;3U
Adder
11.428
944531AF1-118 GEN
Solar/Wind Harmer
64.152
247604X1-042
Adder
0.761
274724RIVER EC ;11
Adder
32.23
972231SS25-0005
Solar/Wind Harmer
17.235
972181SS23-001
Solar/Wind Harmer
10.772
274752CRETE EC ;2U
Adder
8.877
274753CRETE EC ;3U
Adder
8.877
970707AG2-453 GEN
Solar/Wind Harmer
50.49
274802UNIV PARK;5U
Adder
10.468
274826FISK ;BP
Adder
19.655
276772AC2-154 GEN
Solar/Wind Harmer
5.001
276806AD2-047 C O1
Solar/Wind Harmer
19.185
970941AG2-585 GEN
Solar/Wind Harmer
22.418
274800UNIV PARK;3U
Adder
10.455
972038AH1-567 GEN2
Adder
0.654
972228AH1-698 GEN2
Adder
6.639
276897AD1-100 C
Solar/Wind Harmer
51.755
939351AE1-166 GEN
Solar/Wind Harmer
10.575
274676JOLIET 29;8U
Adder
52.592
274729ELWOOD EC;1P
Adder
29.137
274730ELWOOD EC;6P
Adder
29.138
274734ELWOOD EC;8P
Adder
29.138
274736ELWOOD EC;9P
Adder
29.138
276893AG1-478 C
Solar/Wind Harmer
0.74
959331AF2-224 GEN
Solar/Wind Harmer
17.715
965021AG1-366 GEN
Solar/Wind Harmer
4.12
943121AE2-341 GEN
Solar/Wind Harmer
26.432
943591AF1-030 GEN
Solar/Wind Harmer
17.621
270535AF1-215 GEN1
Solar/Wind Harmer
7.981
276694AA1-018 GEN2
Solar/Wind Harmer
10.942
274682WAUKEGAN ;7U
Adder
31.14
964401AG1-302 GEN
Solar/Wind Harmer
15.597
274872LEEDK;1U
Solar/Wind Harmer
0.438
276805AD2-038 GEN
Solar/Wind Harmer
8.776
276799AD1-013 GEN
Solar/Wind Harmer
3.749
946671AF1-331 GEN
Solar/Wind Harmer
0.71
274855GSG-6 ;RU
Solar/Wind Harmer
6.258
274850MENDOTA H;RU
Solar/Wind Harmer
4.351
276602WESTBROOK C
Solar/Wind Harmer
3.602
276863AD2-134 GEN
Solar/Wind Harmer
3.026
959141AF2-205 GEN
Solar/Wind Harmer
10.19
972236AH1-702 GEN2
Adder
3.664
274760LEE CO EC;1U
Adder
15.294
274767LEE CO EC;8U
Adder
15.114
24728705AND G3
Adder
8.991
24728505AND G1
Adder
4.299
959091AF2-200 GEN
Solar/Wind Harmer
32.581
24344105CKG2
50/50
15.989
270143AC1-141 CT2_
50/50
4.589
24639705ELKHART HY
50/50
0.308
970521AG2-332 GEN
50/50
21.897
24307105BERRINSP G
50/50
0.041
970245AG2-165 GEN
Solar/Wind Harmer
35.447
270505AE1-170 C O1
Solar/Wind Harmer
28.453
945111AF1-176 GEN
Solar/Wind Harmer
33.668
270449AD2-020 GEN
Solar/Wind Harmer
5.261
943021AE2-325 GEN
Solar/Wind Harmer
6.837
270063AE2-323 C
Solar/Wind Harmer
4.119
972207SS24-0001
Solar/Wind Harmer
40.631
274773LINCOLN ;4U
Adder
11.428
274774LINCOLN ;5U
Adder
11.428
274723RIVER EC ;12
Adder
32.605
274751CRETE EC ;1U
Adder
8.877
274754CRETE EC ;4U
Adder
8.877
276164X3-005 C
Solar/Wind Harmer
1.273
274812UNIV PK N;8U
Adder
9.041
970373AG2-245 GEN
Solar/Wind Harmer
37.783
276776AD2-060 GEN
Solar/Wind Harmer
0.758
274801UNIV PARK;4U
Adder
10.455
941551AE2-152 GEN
Solar/Wind Harmer
8.088
274676JOLIET 29;8U
Adder
54.54
274674JOLIET 9 ;6U
Adder
27.32
274732ELWOOD EC;7P
Adder
29.138
965011AG1-365 GEN
Solar/Wind Harmer
17.715
274871GR RIDGE ;2U
Solar/Wind Harmer
13.606
274745AC1-111 GEN9
Adder
9.829
270055AF2-134 C O1
Solar/Wind Harmer
5.32
276691AA1-018 GEN1
Solar/Wind Harmer
0.807
274682WAUKEGAN ;7U
Adder
31.14
274828WAUKEGAN ;BP
Adder
19.112
958381AF2-132 GEN
Solar/Wind Harmer
15.597
960751AF2-366 GEN
Solar/Wind Harmer
4.928
962781AG1-127 GEN
Solar/Wind Harmer
16.333
964861AG1-349 GEN
Solar/Wind Harmer
13.483
971917AH1-482 GEN
Solar/Wind Harmer
15.559
274872LEEDK;1U
Solar/Wind Harmer
14.071
939401AE1-172 GEN
Solar/Wind Harmer
23.859
276901AD2-066 C O1
Solar/Wind Harmer
6
971997AH1-543 GEN
Solar/Wind Harmer
26.748
276861AD2-134 GEN
Solar/Wind Harmer
3.026
274822ROCKFORD ;11
Adder
32.898
972235AH1-702 GEN1
Adder
4.214
274761LEE CO EC;2U
Adder
15.294
274766LEE CO EC;7U
Adder
15.114
24728605AND G2
Adder
4.299
970091AG2-072 GEN
Adder
4.41
270349AD2-093_GEN
Solar/Wind Helper
1.84
957471AF2-041 GEN
Solar/Wind Harmer
48.872
959081AF2-199 GEN
Solar/Wind Harmer
16.291
971067AG2-660 GEN
Solar/Wind Harmer
3.789
971599AH1-298 GEN
50/50
18.905
270144AC1-141 ST1_
50/50
4.065
24643105BUCHANAN
50/50
0.024
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
30.529
971771AH1-392 GEN
Solar/Wind Harmer
17.216
270071AF1-092 GEN
Solar/Wind Harmer
28.557
960681AF2-359 GEN
Solar/Wind Harmer
7.16
971769AH1-391 GEN
Solar/Wind Harmer
18.948
944161AF1-084 GEN
Solar/Wind Harmer
4.125
274775LINCOLN ;6U
Adder
11.428
274776LINCOLN ;7U
Adder
11.428
274777LINCOLN ;8U
Adder
11.428
274814UNIV PK N;0U
Adder
9.121
274807UNIV PK N;3U
Adder
9.101
274805UNIV PK N;1U
Adder
9.061
274811UNIV PK N;7U
Adder
9.041
972037AH1-567 GEN1
Adder
0.329
274827FISK ;RP
Adder
13.93
960591AF2-350 GEN
Solar/Wind Harmer
17.934
972227AH1-698 GEN1
Adder
4.674
24729505KEY G4
Adder
11.594
274687WILL CNTY;4U
Adder
49.737
274687WILL CNTY;4U
Adder
49.737
274675JOLIET 29;7U
Adder
54.541
274675JOLIET 29;7U
Adder
52.593
274731ELWOOD EC;2P
Adder
29.137
274733ELWOOD EC;3P
Adder
29.137
274735ELWOOD EC;4P
Adder
29.137
274728ELWOOD EC;5P
Adder
29.138
970833AG2-524 GEN
Solar/Wind Harmer
15.455
970833AG2-524 GEN
Solar/Wind Harmer
7.188
274746AC1-111 G10
Adder
9.829
274744AC1-111 GEN8
Adder
9.829
270536AF1-215 GEN2
Solar/Wind Harmer
7.981
971549AH1-272 GEN
Solar/Wind Harmer
31.811
971177AH1-047 GEN
Solar/Wind Harmer
9.977
276868AE1-113 GEN
Solar/Wind Harmer
17.225
276882AE2-255 GEN
Solar/Wind Harmer
5.742
958391AF2-133 GEN
Solar/Wind Harmer
15.422
971411AH1-196 GEN
Solar/Wind Harmer
25.424
971675AH1-338 GEN
Solar/Wind Harmer
30.507
274863CRW1-WTG
Solar/Wind Harmer
9.397
274864CRW2-WTG
Solar/Wind Harmer
9.397
274823ROCKFORD ;21
Adder
32.659
270284AF1-227 GEN1
Solar/Wind Helper
2.861
270286AF1-227 GEN2
Solar/Wind Helper
1.049
270287AF1-227 GEN3
Solar/Wind Helper
1.049
270054AF2-122 C O1
Solar/Wind Helper
1.201
971171AH1-044 GEN
Solar/Wind Harmer
32.581
270102X2-052 ST
50/50
3.054
270100X2-052 CT1
50/50
2.814
270101X2-052 CT2
50/50
2.814
247620Y3-023
50/50
0.917
970321AG2-212 GEN
Solar/Wind Harmer
35.447
270216AD2-079_GEN
Solar/Wind Harmer
1.158
270526AF1-158 GEN
Solar/Wind Harmer
8.625
965681AG1-436 GEN
Solar/Wind Harmer
23.689
965791AG1-447 GEN
Solar/Wind Harmer
12.12
24441505OLIV SLR
Solar/Wind Harmer
0.254
957891AF2-083 GEN
Solar/Wind Harmer
6.386
960981AF2-389 GEN
Solar/Wind Harmer
2.861
961051AF2-396 GEN
Solar/Wind Harmer
29.854
961051AF2-396 GEN
Solar/Wind Harmer
13.886
274770LINCOLN ;1U
Adder
11.428
274771LINCOLN ;2U
Adder
11.428
274808UNIV PK N;4U
Adder
9.002
274803UNIV PARK;6U
Adder
10.468
972259AH1-714 GEN
Adder
34.24
274888KELLY CRK;1U
Solar/Wind Harmer
10.588
274887GEN-1.85
Solar/Wind Harmer
9.559
276843GEN-1.7
Solar/Wind Harmer
1.029
958011AF2-095 GEN
Solar/Wind Harmer
25.825
274674JOLIET 9 ;6U
Adder
27.32
970611AG2-400 GEN
Solar/Wind Harmer
17.715
274847GR RIDGE ;BU
Solar/Wind Harmer
8.95
971573AH1-285 GEN
Solar/Wind Harmer
15.059
274695ROCKY RD ;2P
Adder
19.327
274693ROCKY RD ;1P
Adder
19.137
274697ROCKY RD ;3P
Adder
5.25
274696ROCKY RD ;4P
Adder
19.783
958481AF2-142 GEN
Solar/Wind Harmer
26.008
274861TOP CROP ;1U
Solar/Wind Harmer
10.5
274862TOP CROP ;2U
Solar/Wind Harmer
8.768
274683WAUKEGAN ;8U
Adder
36.461
274683WAUKEGAN ;8U
Adder
30.735
962691AG1-118 GEN
Solar/Wind Harmer
51.667
970921AG2-575 GEN
Solar/Wind Harmer
17.175
970921AG2-575 GEN
Solar/Wind Harmer
3.994
958491AF2-143 GEN
Solar/Wind Harmer
25.662
942991AE2-321 GEN
Solar/Wind Harmer
17.034
274879MINONK ;1U
Solar/Wind Harmer
11.484
971333AH1-146 GEN
Solar/Wind Harmer
33.871
971335AH1-147 GEN
Solar/Wind Harmer
33.871
274764LEE CO EC;5U
Adder
15.33
274765LEE CO EC;6U
Adder
15.33
274762LEE CO EC;3U
Adder
15.294
274763LEE CO EC;4U
Adder
15.15
972267AH1-718 GEN
Adder
6.769
247621Y3-024
Adder
0.286
270471AD2-092_GEN
Solar/Wind Helper
1.84
971341AH1-150 GEN
Solar/Wind Harmer
32.581
971343AH1-151 GEN
Solar/Wind Harmer
32.581
944201AF1-088_MTX
Adder
125.321
957141AF2-008_MTX
Adder
62.661
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
197.094
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.275
MECLTFEXP_MEC->PJM
CLTF
22.999
SIGELTFEXP_SIGE->PJM
CLTF
0.439
LAGNLTFEXP_LAGN->PJM
CLTF
12.243
TVALTFEXP_TVA->PJM
CLTF
4.635
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.242
NYPJM->LTFIMP_NY
CLTF
3.027
LGEELTFEXP_LGEE->PJM
CLTF
4.067
WECLTFEXP_WEC->PJM
CLTF
6.372
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.882
AG2-052LTFEXP_AG2-052->PJM
LTF
0.399
AH1-155LTFEXP_AH1-155->PJM
LTF
0.599

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.3 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5594.78
MW Contribution:55.45
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
15.997
270143AC1-141 CT2_
50/50
4.591
24639705ELKHART HY
50/50
0.308
24344005CKG1
50/50
12.545
270142AC1-141 CT1_
50/50
4.591
24641605TWIN BRNCH
50/50
0.033
24642205MAYFLWER
50/50
1.278
944961AF1-161 GEN
50/50
5.46
962601AG1-109 GEN
50/50
5.46
970349AG2-230 GEN
Solar/Wind Harmer
30.544
970513AG2-328 GEN
Solar/Wind Harmer
35.465
970517AG2-330 GEN
Solar/Wind Harmer
32.166
270043AE2-236 GEN
Solar/Wind Harmer
10.829
247643Z2-116 C
Solar/Wind Harmer
0.133
945111AF1-176 GEN
Solar/Wind Harmer
10.676
970031AG2-029 GEN
Solar/Wind Harmer
55.447
24441205WTRV SLR C
Solar/Wind Harmer
0.249
274772LINCOLN ;3U
Adder
11.434
944531AF1-118 GEN
Solar/Wind Harmer
64.187
247604X1-042
Adder
0.761
274724RIVER EC ;11
Adder
32.247
972231SS25-0005
Solar/Wind Harmer
17.245
972181SS23-001
Solar/Wind Harmer
10.778
274752CRETE EC ;2U
Adder
8.882
274753CRETE EC ;3U
Adder
8.882
970707AG2-453 GEN
Solar/Wind Harmer
50.518
274802UNIV PARK;5U
Adder
10.474
274826FISK ;BP
Adder
19.666
276772AC2-154 GEN
Solar/Wind Harmer
5.004
276806AD2-047 C O1
Solar/Wind Harmer
19.196
970941AG2-585 GEN
Solar/Wind Harmer
22.43
274800UNIV PARK;3U
Adder
10.46
972038AH1-567 GEN2
Adder
0.655
972228AH1-698 GEN2
Adder
6.643
276897AD1-100 C
Solar/Wind Harmer
51.784
939351AE1-166 GEN
Solar/Wind Harmer
10.581
274676JOLIET 29;8U
Adder
52.622
274730ELWOOD EC;6P
Adder
29.154
274734ELWOOD EC;8P
Adder
29.154
274736ELWOOD EC;9P
Adder
29.154
274729ELWOOD EC;1P
Adder
29.154
276893AG1-478 C
Solar/Wind Harmer
0.74
959331AF2-224 GEN
Solar/Wind Harmer
17.725
965021AG1-366 GEN
Solar/Wind Harmer
4.122
943121AE2-341 GEN
Solar/Wind Harmer
26.447
943591AF1-030 GEN
Solar/Wind Harmer
17.631
270102X2-052 ST
50/50
3.055
270100X2-052 CT1
50/50
2.815
270101X2-052 CT2
50/50
2.815
247620Y3-023
50/50
0.917
970321AG2-212 GEN
Solar/Wind Harmer
35.465
270216AD2-079_GEN
Solar/Wind Harmer
1.158
270526AF1-158 GEN
Solar/Wind Harmer
8.63
965681AG1-436 GEN
Solar/Wind Harmer
23.702
965791AG1-447 GEN
Solar/Wind Harmer
12.126
24441505OLIV SLR
Solar/Wind Harmer
0.254
957891AF2-083 GEN
Solar/Wind Harmer
6.389
960981AF2-389 GEN
Solar/Wind Harmer
2.863
961051AF2-396 GEN
Solar/Wind Harmer
29.87
961051AF2-396 GEN
Solar/Wind Harmer
13.893
274770LINCOLN ;1U
Adder
11.434
274771LINCOLN ;2U
Adder
11.434
274808UNIV PK N;4U
Adder
9.007
274803UNIV PARK;6U
Adder
10.474
972259AH1-714 GEN
Adder
34.259
274888KELLY CRK;1U
Solar/Wind Harmer
10.594
274887GEN-1.85
Solar/Wind Harmer
9.565
276843GEN-1.7
Solar/Wind Harmer
1.029
958011AF2-095 GEN
Solar/Wind Harmer
25.84
274674JOLIET 9 ;6U
Adder
27.335
970611AG2-400 GEN
Solar/Wind Harmer
17.725
274847GR RIDGE ;BU
Solar/Wind Harmer
8.955
971573AH1-285 GEN
Solar/Wind Harmer
15.068
274695ROCKY RD ;2P
Adder
19.338
274693ROCKY RD ;1P
Adder
19.148
274697ROCKY RD ;3P
Adder
5.253
274696ROCKY RD ;4P
Adder
19.794
958481AF2-142 GEN
Solar/Wind Harmer
26.023
274861TOP CROP ;1U
Solar/Wind Harmer
10.506
274862TOP CROP ;2U
Solar/Wind Harmer
8.773
274683WAUKEGAN ;8U
Adder
36.482
274683WAUKEGAN ;8U
Adder
30.752
962691AG1-118 GEN
Solar/Wind Harmer
51.697
970921AG2-575 GEN
Solar/Wind Harmer
17.185
970921AG2-575 GEN
Solar/Wind Harmer
3.996
958491AF2-143 GEN
Solar/Wind Harmer
25.677
942991AE2-321 GEN
Solar/Wind Harmer
17.044
274879MINONK ;1U
Solar/Wind Harmer
11.491
270535AF1-215 GEN1
Solar/Wind Harmer
7.986
276694AA1-018 GEN2
Solar/Wind Harmer
10.948
274682WAUKEGAN ;7U
Adder
31.159
964401AG1-302 GEN
Solar/Wind Harmer
15.606
274872LEEDK;1U
Solar/Wind Harmer
0.439
276805AD2-038 GEN
Solar/Wind Harmer
8.782
276799AD1-013 GEN
Solar/Wind Harmer
3.751
946671AF1-331 GEN
Solar/Wind Harmer
0.71
274855GSG-6 ;RU
Solar/Wind Harmer
6.262
274850MENDOTA H;RU
Solar/Wind Harmer
4.354
276602WESTBROOK C
Solar/Wind Harmer
3.604
276863AD2-134 GEN
Solar/Wind Harmer
3.028
959141AF2-205 GEN
Solar/Wind Harmer
10.197
972236AH1-702 GEN2
Adder
3.666
274760LEE CO EC;1U
Adder
15.304
274767LEE CO EC;8U
Adder
15.124
24728705AND G3
Adder
8.999
24728505AND G1
Adder
4.303
942871AE2-306 GEN
Solar/Wind Helper
0.456
959091AF2-200 GEN
Solar/Wind Harmer
32.601
970521AG2-332 GEN
50/50
21.908
24307105BERRINSP G
50/50
0.041
970245AG2-165 GEN
Solar/Wind Harmer
35.465
270505AE1-170 C O1
Solar/Wind Harmer
28.468
945111AF1-176 GEN
Solar/Wind Harmer
33.686
270449AD2-020 GEN
Solar/Wind Harmer
5.264
943021AE2-325 GEN
Solar/Wind Harmer
6.84
270063AE2-323 C
Solar/Wind Harmer
4.121
972207SS24-0001
Solar/Wind Harmer
40.653
274773LINCOLN ;4U
Adder
11.434
274774LINCOLN ;5U
Adder
11.434
274723RIVER EC ;12
Adder
32.623
274751CRETE EC ;1U
Adder
8.882
274754CRETE EC ;4U
Adder
8.882
276164X3-005 C
Solar/Wind Harmer
1.273
274812UNIV PK N;8U
Adder
9.046
970373AG2-245 GEN
Solar/Wind Harmer
37.804
276776AD2-060 GEN
Solar/Wind Harmer
0.759
274801UNIV PARK;4U
Adder
10.46
941551AE2-152 GEN
Solar/Wind Harmer
8.093
274676JOLIET 29;8U
Adder
54.571
274674JOLIET 9 ;6U
Adder
27.335
274732ELWOOD EC;7P
Adder
29.154
965011AG1-365 GEN
Solar/Wind Harmer
17.725
274871GR RIDGE ;2U
Solar/Wind Harmer
13.613
274745AC1-111 GEN9
Adder
9.834
270055AF2-134 C O1
Solar/Wind Harmer
5.323
276691AA1-018 GEN1
Solar/Wind Harmer
0.808
274682WAUKEGAN ;7U
Adder
31.159
274828WAUKEGAN ;BP
Adder
19.123
958381AF2-132 GEN
Solar/Wind Harmer
15.606
960751AF2-366 GEN
Solar/Wind Harmer
4.93
962781AG1-127 GEN
Solar/Wind Harmer
16.343
964861AG1-349 GEN
Solar/Wind Harmer
13.491
971917AH1-482 GEN
Solar/Wind Harmer
15.568
274872LEEDK;1U
Solar/Wind Harmer
14.079
939401AE1-172 GEN
Solar/Wind Harmer
23.873
276901AD2-066 C O1
Solar/Wind Harmer
6.004
971997AH1-543 GEN
Solar/Wind Harmer
26.764
276861AD2-134 GEN
Solar/Wind Harmer
3.028
274822ROCKFORD ;11
Adder
32.918
972235AH1-702 GEN1
Adder
4.216
274761LEE CO EC;2U
Adder
15.304
274766LEE CO EC;7U
Adder
15.124
24728605AND G2
Adder
4.303
970091AG2-072 GEN
Adder
4.415
270349AD2-093_GEN
Solar/Wind Helper
1.839
270223U2-072_GEN1
Solar/Wind Helper
0.897
270578AF1-285 GEN2
Solar/Wind Helper
0.608
270391AF1-285 GEN3
Solar/Wind Helper
0.608
957471AF2-041 GEN
Solar/Wind Harmer
48.901
959081AF2-199 GEN
Solar/Wind Harmer
16.3
971067AG2-660 GEN
Solar/Wind Harmer
3.791
971599AH1-298 GEN
50/50
18.913
270144AC1-141 ST1_
50/50
4.067
24643105BUCHANAN
50/50
0.024
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
30.544
971771AH1-392 GEN
Solar/Wind Harmer
17.225
270071AF1-092 GEN
Solar/Wind Harmer
28.572
960681AF2-359 GEN
Solar/Wind Harmer
7.163
971769AH1-391 GEN
Solar/Wind Harmer
18.958
944161AF1-084 GEN
Solar/Wind Harmer
4.127
274775LINCOLN ;6U
Adder
11.434
274776LINCOLN ;7U
Adder
11.434
274777LINCOLN ;8U
Adder
11.434
274814UNIV PK N;0U
Adder
9.126
274807UNIV PK N;3U
Adder
9.106
274805UNIV PK N;1U
Adder
9.066
274811UNIV PK N;7U
Adder
9.046
972037AH1-567 GEN1
Adder
0.329
274827FISK ;RP
Adder
13.937
960591AF2-350 GEN
Solar/Wind Harmer
17.944
972227AH1-698 GEN1
Adder
4.677
24729505KEY G4
Adder
11.601
274687WILL CNTY;4U
Adder
49.765
274687WILL CNTY;4U
Adder
49.765
274675JOLIET 29;7U
Adder
54.572
274675JOLIET 29;7U
Adder
52.623
274728ELWOOD EC;5P
Adder
29.154
274731ELWOOD EC;2P
Adder
29.154
274733ELWOOD EC;3P
Adder
29.154
274735ELWOOD EC;4P
Adder
29.154
970833AG2-524 GEN
Solar/Wind Harmer
15.464
970833AG2-524 GEN
Solar/Wind Harmer
7.192
274746AC1-111 G10
Adder
9.834
274744AC1-111 GEN8
Adder
9.834
270536AF1-215 GEN2
Solar/Wind Harmer
7.986
971549AH1-272 GEN
Solar/Wind Harmer
31.829
971177AH1-047 GEN
Solar/Wind Harmer
9.983
276868AE1-113 GEN
Solar/Wind Harmer
17.235
276882AE2-255 GEN
Solar/Wind Harmer
5.745
958391AF2-133 GEN
Solar/Wind Harmer
15.431
971411AH1-196 GEN
Solar/Wind Harmer
25.439
971675AH1-338 GEN
Solar/Wind Harmer
30.526
274863CRW1-WTG
Solar/Wind Harmer
9.402
274864CRW2-WTG
Solar/Wind Harmer
9.402
274823ROCKFORD ;21
Adder
32.679
270284AF1-227 GEN1
Solar/Wind Helper
2.858
270286AF1-227 GEN2
Solar/Wind Helper
1.048
270287AF1-227 GEN3
Solar/Wind Helper
1.048
270054AF2-122 C O1
Solar/Wind Helper
1.2
971171AH1-044 GEN
Solar/Wind Harmer
32.601
971333AH1-146 GEN
Solar/Wind Harmer
33.891
971335AH1-147 GEN
Solar/Wind Harmer
33.891
274764LEE CO EC;5U
Adder
15.34
274765LEE CO EC;6U
Adder
15.34
274762LEE CO EC;3U
Adder
15.304
274763LEE CO EC;4U
Adder
15.16
972267AH1-718 GEN
Adder
6.773
247621Y3-024
Adder
0.286
270471AD2-092_GEN
Solar/Wind Helper
1.839
270224U2-072_GEN2
Solar/Wind Helper
0.897
270227U2-072_GEN3
Solar/Wind Helper
0.897
270228U2-072_GEN4
Solar/Wind Helper
0.897
270231U2-072_GEN5
Solar/Wind Helper
0.897
971341AH1-150 GEN
Solar/Wind Harmer
32.601
971343AH1-151 GEN
Solar/Wind Harmer
32.601
944201AF1-088_MTX
Adder
125.438
957141AF2-008_MTX
Adder
62.719
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.34
CBM West 1LTFEXP_CBM-W1->PJM
CBM
197.241
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.313
MECLTFEXP_MEC->PJM
CLTF
23.016
SIGELTFEXP_SIGE->PJM
CLTF
0.44
LAGNLTFEXP_LAGN->PJM
CLTF
12.264
TVALTFEXP_TVA->PJM
CLTF
4.645
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.378
NYPJM->LTFIMP_NY
CLTF
3.02
LGEELTFEXP_LGEE->PJM
CLTF
4.074
WECLTFEXP_WEC->PJM
CLTF
6.376
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.875
AG2-052LTFEXP_AG2-052->PJM
LTF
0.399
AH1-155LTFEXP_AH1-155->PJM
LTF
0.599

Details for 05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.98 %
Rating:6066.0 MVA
Rating Type:B
MVA to Mitigate:6914.12
MW Contribution:62.69
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.827
270144AC1-141 ST1_
50/50
4.726
24643105BUCHANAN
50/50
0.028
274775LINCOLN ;6U
50/50
14.464
274776LINCOLN ;7U
50/50
14.464
274777LINCOLN ;8U
50/50
14.464
971347AH1-153 GEN
Solar/Wind Harmer
35.693
960681AF2-359 GEN
Solar/Wind Harmer
8.494
971771AH1-392 GEN
Solar/Wind Harmer
20.116
971769AH1-391 GEN
Solar/Wind Harmer
22.322
270071AF1-092 GEN
Solar/Wind Harmer
32.714
944161AF1-084 GEN
Solar/Wind Harmer
4.796
270536AF1-215 GEN2
Solar/Wind Harmer
9.847
274814UNIV PK N;0U
Adder
10.897
274807UNIV PK N;3U
Adder
10.873
274805UNIV PK N;1U
Adder
10.826
274811UNIV PK N;7U
Adder
10.802
972037AH1-567 GEN1
Adder
0.393
274827FISK ;RP
Adder
16.653
960591AF2-350 GEN
Solar/Wind Harmer
21.457
972227AH1-698 GEN1
Adder
5.595
270102X2-052 ST
50/50
3.618
270100X2-052 CT1
50/50
3.334
270101X2-052 CT2
50/50
3.334
274770LINCOLN ;1U
50/50
14.464
274771LINCOLN ;2U
50/50
14.464
970321AG2-212 GEN
Solar/Wind Harmer
43.637
965681AG1-436 GEN
Solar/Wind Harmer
28.105
965791AG1-447 GEN
Solar/Wind Harmer
14.379
270526AF1-158 GEN
Solar/Wind Harmer
10.145
24441505OLIV SLR
Solar/Wind Harmer
0.299
270216AD2-079_GEN
Solar/Wind Harmer
1.343
957891AF2-083 GEN
Solar/Wind Harmer
7.428
960981AF2-389 GEN
Solar/Wind Harmer
3.328
961051AF2-396 GEN
Solar/Wind Harmer
34.696
961051AF2-396 GEN
Solar/Wind Harmer
16.138
247620Y3-023
Adder
0.995
274808UNIV PK N;4U
Adder
10.755
972259AH1-714 GEN
Adder
40.962
274803UNIV PARK;6U
Adder
12.517
274888KELLY CRK;1U
Solar/Wind Harmer
12.668
274887GEN-1.85
Solar/Wind Harmer
11.437
276843GEN-1.7
Solar/Wind Harmer
1.231
958011AF2-095 GEN
Solar/Wind Harmer
30.899
274674JOLIET 9 ;6U
Adder
32.718
274847GR RIDGE ;BU
Solar/Wind Harmer
10.728
971573AH1-285 GEN
Solar/Wind Harmer
18.045
970239AG2-162 GEN
Solar/Wind Harmer
22.993
958481AF2-142 GEN
Solar/Wind Harmer
31.243
945421AF1-207 GEN
Solar/Wind Harmer
29.246
957841AF2-078 GEN
Solar/Wind Harmer
12.586
274695ROCKY RD ;2P
Adder
23.176
274693ROCKY RD ;1P
Adder
22.948
274697ROCKY RD ;3P
Adder
6.296
274861TOP CROP ;1U
Solar/Wind Harmer
12.614
274862TOP CROP ;2U
Solar/Wind Harmer
10.533
274696ROCKY RD ;4P
Adder
23.723
274683WAUKEGAN ;8U
Adder
43.726
274683WAUKEGAN ;8U
Adder
36.859
962691AG1-118 GEN
Solar/Wind Harmer
61.999
970921AG2-575 GEN
Solar/Wind Harmer
20.614
970921AG2-575 GEN
Solar/Wind Harmer
4.794
958491AF2-143 GEN
Solar/Wind Harmer
30.883
274879MINONK ;1U
Solar/Wind Harmer
13.83
942991AE2-321 GEN
Solar/Wind Harmer
20.456
971333AH1-146 GEN
Solar/Wind Harmer
40.697
971335AH1-147 GEN
Solar/Wind Harmer
40.697
276872AE1-163_GEN1
Solar/Wind Harmer
13.606
274764LEE CO EC;5U
Adder
18.47
274765LEE CO EC;6U
Adder
18.47
274762LEE CO EC;3U
Adder
18.426
274763LEE CO EC;4U
Adder
18.253
972267AH1-718 GEN
Adder
8.164
270471AD2-092_GEN
Solar/Wind Helper
1.574
971341AH1-150 GEN
Solar/Wind Harmer
0.703
971343AH1-151 GEN
Solar/Wind Harmer
0.703
24344105CKG2
50/50
18.684
270143AC1-141 CT2_
50/50
5.336
274773LINCOLN ;4U
50/50
14.464
274774LINCOLN ;5U
50/50
14.464
24639705ELKHART HY
50/50
0.356
970245AG2-165 GEN
Solar/Wind Harmer
43.637
270505AE1-170 C O1
Solar/Wind Harmer
33.093
972207SS24-0001
Solar/Wind Harmer
48.463
970373AG2-245 GEN
Solar/Wind Harmer
46.063
945111AF1-176 GEN
Solar/Wind Harmer
39.1
270449AD2-020 GEN
Solar/Wind Harmer
6.117
943021AE2-325 GEN
Solar/Wind Harmer
7.949
274723RIVER EC ;12
Adder
38.895
274751CRETE EC ;1U
Adder
10.596
274754CRETE EC ;4U
Adder
10.596
270055AF2-134 C O1
Solar/Wind Harmer
6.564
276164X3-005 C
Solar/Wind Harmer
1.52
274812UNIV PK N;8U
Adder
10.802
276776AD2-060 GEN
Solar/Wind Harmer
0.907
274801UNIV PARK;4U
Adder
12.503
958381AF2-132 GEN
Solar/Wind Harmer
19.452
964861AG1-349 GEN
Solar/Wind Harmer
16.835
971917AH1-482 GEN
Solar/Wind Harmer
19.427
941551AE2-152 GEN
Solar/Wind Harmer
9.695
274676JOLIET 29;8U
Adder
65.284
274674JOLIET 9 ;6U
Adder
32.718
274732ELWOOD EC;7P
Adder
34.908
270063AE2-323 C
Solar/Wind Harmer
4.678
274871GR RIDGE ;2U
Solar/Wind Harmer
16.309
940581AE2-045 GEN
Solar/Wind Harmer
21.545
971605AH1-302 GEN
Solar/Wind Harmer
18.424
274745AC1-111 GEN9
Adder
11.776
970333AG2-219 GEN
Solar/Wind Harmer
65.98
276691AA1-018 GEN1
Solar/Wind Harmer
0.97
274682WAUKEGAN ;7U
Adder
37.343
274828WAUKEGAN ;BP
Adder
22.921
939401AE1-172 GEN
Solar/Wind Harmer
28.837
960751AF2-366 GEN
Solar/Wind Harmer
5.914
962781AG1-127 GEN
Solar/Wind Harmer
19.604
276901AD2-066 C O1
Solar/Wind Harmer
7.228
274872LEEDK;1U
Solar/Wind Harmer
16.893
24791305MDL-5G
Solar/Wind Harmer
4.944
971997AH1-543 GEN
Solar/Wind Harmer
32.241
276861AD2-134 GEN
Solar/Wind Harmer
3.637
276876AE1-163_GEN2
Solar/Wind Harmer
13.606
274822ROCKFORD ;11
Adder
39.558
972235AH1-702 GEN1
Adder
5.068
274761LEE CO EC;2U
Adder
18.426
274766LEE CO EC;7U
Adder
18.209
970091AG2-072 GEN
Adder
143.374
270349AD2-093_GEN
Solar/Wind Helper
1.574
957471AF2-041 GEN
Solar/Wind Harmer
1.055
959081AF2-199 GEN
Solar/Wind Harmer
0.352
971067AG2-660 GEN
Solar/Wind Harmer
0.082
24344005CKG1
50/50
14.627
270142AC1-141 CT1_
50/50
5.336
24641605TWIN BRNCH
50/50
0.039
24642205MAYFLWER
50/50
1.492
274772LINCOLN ;3U
50/50
14.464
970513AG2-328 GEN
Solar/Wind Harmer
43.637
970517AG2-330 GEN
Solar/Wind Harmer
39.578
970349AG2-230 GEN
Solar/Wind Harmer
35.693
247643Z2-116 C
Solar/Wind Harmer
0.155
270043AE2-236 GEN
Solar/Wind Harmer
12.097
945111AF1-176 GEN
Solar/Wind Harmer
12.392
274724RIVER EC ;11
Adder
38.445
972231SS25-0005
Solar/Wind Harmer
20.573
972181SS23-001
Solar/Wind Harmer
12.858
274752CRETE EC ;2U
Adder
10.596
274753CRETE EC ;3U
Adder
10.596
270535AF1-215 GEN1
Solar/Wind Harmer
9.847
970707AG2-453 GEN
Solar/Wind Harmer
60.348
274802UNIV PARK;5U
Adder
12.517
274826FISK ;BP
Adder
23.497
276772AC2-154 GEN
Solar/Wind Harmer
5.984
276806AD2-047 C O1
Solar/Wind Harmer
22.954
970941AG2-585 GEN
Solar/Wind Harmer
26.822
972228AH1-698 GEN2
Adder
7.946
274800UNIV PARK;3U
Adder
12.503
972038AH1-567 GEN2
Adder
0.783
24441205WTRV SLR C
Solar/Wind Harmer
0.289
964401AG1-302 GEN
Solar/Wind Harmer
19.452
276897AD1-100 C
Solar/Wind Harmer
62.038
939351AE1-166 GEN
Solar/Wind Harmer
12.676
274676JOLIET 29;8U
Adder
62.953
247604X1-042
Adder
0.885
274729ELWOOD EC;1P
Adder
34.908
274730ELWOOD EC;6P
Adder
34.908
274734ELWOOD EC;8P
Adder
34.908
274736ELWOOD EC;9P
Adder
34.908
959141AF2-205 GEN
Solar/Wind Harmer
12.838
276893AG1-478 C
Solar/Wind Harmer
0.886
943121AE2-341 GEN
Solar/Wind Harmer
31.655
943591AF1-030 GEN
Solar/Wind Harmer
21.103
970243AG2-164 GEN
Solar/Wind Harmer
53.983
970519AG2-331 GEN
Solar/Wind Harmer
36.268
970699AG2-449 GEN
Solar/Wind Harmer
23.993
970031AG2-029 GEN
Solar/Wind Harmer
62.689
276694AA1-018 GEN2
Solar/Wind Harmer
13.144
274682WAUKEGAN ;7U
Adder
37.343
276805AD2-038 GEN
Solar/Wind Harmer
10.562
274872LEEDK;1U
Solar/Wind Harmer
0.526
24755605MDL-5G
Solar/Wind Harmer
4.944
970781AG2-491 GEN
Solar/Wind Harmer
20.497
276799AD1-013 GEN
Solar/Wind Harmer
4.505
946671AF1-331 GEN
Solar/Wind Harmer
0.853
274855GSG-6 ;RU
Solar/Wind Harmer
7.52
274850MENDOTA H;RU
Solar/Wind Harmer
5.229
276602WESTBROOK C
Solar/Wind Harmer
4.329
276863AD2-134 GEN
Solar/Wind Harmer
3.637
276889AE2-281 GEN
Solar/Wind Harmer
3.888
972236AH1-702 GEN2
Adder
4.407
274760LEE CO EC;1U
Adder
18.426
274767LEE CO EC;8U
Adder
18.209
959091AF2-200 GEN
Solar/Wind Harmer
0.703
958391AF2-133 GEN
Solar/Wind Harmer
19.344
274687WILL CNTY;4U
Adder
59.525
274687WILL CNTY;4U
Adder
59.525
274675JOLIET 29;7U
Adder
65.285
274675JOLIET 29;7U
Adder
62.954
274731ELWOOD EC;2P
Adder
34.908
274733ELWOOD EC;3P
Adder
34.908
274735ELWOOD EC;4P
Adder
34.908
274728ELWOOD EC;5P
Adder
34.908
970833AG2-524 GEN
Solar/Wind Harmer
18.525
970833AG2-524 GEN
Solar/Wind Harmer
8.616
274746AC1-111 G10
Adder
11.776
274744AC1-111 GEN8
Adder
11.776
24690905MDL-1G C
Solar/Wind Harmer
16.46
270180AB1-006 GEN1
Solar/Wind Harmer
14.745
946581AF1-322 GEN
Solar/Wind Harmer
20.975
24691005MDL-2G C
Solar/Wind Harmer
7.582
24697605MDL-3G C
Solar/Wind Harmer
7.558
24697905MDL-4G C
Solar/Wind Harmer
4.705
270181AB1-006 GEN2
Solar/Wind Harmer
1.466
276868AE1-113 GEN
Solar/Wind Harmer
20.743
276882AE2-255 GEN
Solar/Wind Harmer
6.915
971177AH1-047 GEN
Solar/Wind Harmer
11.982
274863CRW1-WTG
Solar/Wind Harmer
11.396
274864CRW2-WTG
Solar/Wind Harmer
11.396
971675AH1-338 GEN
Solar/Wind Harmer
36.661
971411AH1-196 GEN
Solar/Wind Harmer
30.544
274823ROCKFORD ;21
Adder
39.271
24729505KEY G4
Adder
12.781
270054AF2-122 C O1
Solar/Wind Helper
1.198
971171AH1-044 GEN
Solar/Wind Harmer
0.703
944201AF1-088_MTX
Adder
194.417
957141AF2-008_MTX
Adder
28.027
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.655
CBM West 1LTFEXP_CBM-W1->PJM
CBM
232.718
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.494
MECLTFEXP_MEC->PJM
CLTF
27.999
SIGELTFEXP_SIGE->PJM
CLTF
0.538
LAGNLTFEXP_LAGN->PJM
CLTF
14.568
TVALTFEXP_TVA->PJM
CLTF
5.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
137.493
NYPJM->LTFIMP_NY
CLTF
3.58
LGEELTFEXP_LGEE->PJM
CLTF
4.109
WECLTFEXP_WEC->PJM
CLTF
7.66
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.418
AG2-052LTFEXP_AG2-052->PJM
LTF
0.484
AH1-155LTFEXP_AH1-155->PJM
LTF
0.727

Details for 05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.32 %
Rating:6066.0 MVA
Rating Type:B
MVA to Mitigate:6388.47
MW Contribution:62.78
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
18.741
270143AC1-141 CT2_
50/50
5.339
24639705ELKHART HY
50/50
0.356
970521AG2-332 GEN
50/50
25.327
24307105BERRINSP G
50/50
0.047
970245AG2-165 GEN
Solar/Wind Harmer
44.073
970333AG2-219 GEN
Solar/Wind Harmer
71.347
270505AE1-170 C O1
Solar/Wind Harmer
33.103
945111AF1-176 GEN
Solar/Wind Harmer
39.113
270449AD2-020 GEN
Solar/Wind Harmer
6.12
943021AE2-325 GEN
Solar/Wind Harmer
7.951
970373AG2-245 GEN
Solar/Wind Harmer
45.678
972207SS24-0001
Solar/Wind Harmer
47.808
274773LINCOLN ;4U
Adder
13.446
274774LINCOLN ;5U
Adder
13.446
270055AF2-134 C O1
Solar/Wind Harmer
6.496
274723RIVER EC ;12
Adder
38.388
274751CRETE EC ;1U
Adder
10.462
274754CRETE EC ;4U
Adder
10.462
276164X3-005 C
Solar/Wind Harmer
1.498
270063AE2-323 C
Solar/Wind Harmer
4.686
274812UNIV PK N;8U
Adder
10.651
958381AF2-132 GEN
Solar/Wind Harmer
19.217
964861AG1-349 GEN
Solar/Wind Harmer
16.628
971917AH1-482 GEN
Solar/Wind Harmer
19.189
276776AD2-060 GEN
Solar/Wind Harmer
0.893
274801UNIV PARK;4U
Adder
12.307
941551AE2-152 GEN
Solar/Wind Harmer
9.522
274676JOLIET 29;8U
Adder
64.193
274674JOLIET 9 ;6U
Adder
32.155
274732ELWOOD EC;7P
Adder
34.297
274871GR RIDGE ;2U
Solar/Wind Harmer
16.013
940581AE2-045 GEN
Solar/Wind Harmer
21.231
971605AH1-302 GEN
Solar/Wind Harmer
18.155
274745AC1-111 GEN9
Adder
11.564
276691AA1-018 GEN1
Solar/Wind Harmer
0.95
274682WAUKEGAN ;7U
Adder
36.631
274828WAUKEGAN ;BP
Adder
22.481
960751AF2-366 GEN
Solar/Wind Harmer
5.795
962781AG1-127 GEN
Solar/Wind Harmer
19.209
939401AE1-172 GEN
Solar/Wind Harmer
28.102
274872LEEDK;1U
Solar/Wind Harmer
16.548
276901AD2-066 C O1
Solar/Wind Harmer
7.062
24791305MDL-5G
Solar/Wind Harmer
4.826
971997AH1-543 GEN
Solar/Wind Harmer
31.477
276861AD2-134 GEN
Solar/Wind Harmer
3.559
274822ROCKFORD ;11
Adder
38.678
972235AH1-702 GEN1
Adder
4.954
274761LEE CO EC;2U
Adder
17.977
274766LEE CO EC;7U
Adder
17.765
24728605AND G2
Adder
5.044
970091AG2-072 GEN
Adder
4.904
270349AD2-093_GEN
Solar/Wind Helper
1.53
24344005CKG1
50/50
14.639
270142AC1-141 CT1_
50/50
5.339
24641605TWIN BRNCH
50/50
0.039
24642205MAYFLWER
50/50
1.49
944961AF1-161 GEN
50/50
6.347
962601AG1-109 GEN
50/50
6.347
970513AG2-328 GEN
Solar/Wind Harmer
44.073
970517AG2-330 GEN
Solar/Wind Harmer
39.973
970349AG2-230 GEN
Solar/Wind Harmer
35.714
970243AG2-164 GEN
Solar/Wind Harmer
58.375
970519AG2-331 GEN
Solar/Wind Harmer
39.218
970699AG2-449 GEN
Solar/Wind Harmer
25.944
247643Z2-116 C
Solar/Wind Harmer
0.155
270102X2-052 ST
50/50
3.606
270100X2-052 CT1
50/50
3.322
270101X2-052 CT2
50/50
3.322
970321AG2-212 GEN
Solar/Wind Harmer
44.073
970239AG2-162 GEN
Solar/Wind Harmer
24.863
965681AG1-436 GEN
Solar/Wind Harmer
27.976
965791AG1-447 GEN
Solar/Wind Harmer
14.313
270526AF1-158 GEN
Solar/Wind Harmer
10.118
24441505OLIV SLR
Solar/Wind Harmer
0.298
270216AD2-079_GEN
Solar/Wind Harmer
1.344
957891AF2-083 GEN
Solar/Wind Harmer
7.429
960981AF2-389 GEN
Solar/Wind Harmer
3.328
961051AF2-396 GEN
Solar/Wind Harmer
34.708
961051AF2-396 GEN
Solar/Wind Harmer
16.143
274770LINCOLN ;1U
Adder
13.446
274771LINCOLN ;2U
Adder
13.446
247620Y3-023
Adder
0.996
274808UNIV PK N;4U
Adder
10.604
274803UNIV PARK;6U
Adder
12.325
972259AH1-714 GEN
Adder
40.299
274888KELLY CRK;1U
Solar/Wind Harmer
12.465
274887GEN-1.85
Solar/Wind Harmer
11.254
276843GEN-1.7
Solar/Wind Harmer
1.211
958011AF2-095 GEN
Solar/Wind Harmer
30.403
274674JOLIET 9 ;6U
Adder
32.155
274847GR RIDGE ;BU
Solar/Wind Harmer
10.533
971573AH1-285 GEN
Solar/Wind Harmer
17.714
945421AF1-207 GEN
Solar/Wind Harmer
28.747
957841AF2-078 GEN
Solar/Wind Harmer
12.371
274695ROCKY RD ;2P
Adder
22.735
274693ROCKY RD ;1P
Adder
22.511
274697ROCKY RD ;3P
Adder
6.176
274696ROCKY RD ;4P
Adder
23.271
958481AF2-142 GEN
Solar/Wind Harmer
30.611
274861TOP CROP ;1U
Solar/Wind Harmer
12.359
274862TOP CROP ;2U
Solar/Wind Harmer
10.32
274683WAUKEGAN ;8U
Adder
42.888
274683WAUKEGAN ;8U
Adder
36.153
962691AG1-118 GEN
Solar/Wind Harmer
60.767
970921AG2-575 GEN
Solar/Wind Harmer
20.199
970921AG2-575 GEN
Solar/Wind Harmer
4.697
958491AF2-143 GEN
Solar/Wind Harmer
30.201
942991AE2-321 GEN
Solar/Wind Harmer
20.031
274879MINONK ;1U
Solar/Wind Harmer
13.514
274764LEE CO EC;5U
Adder
18.019
274765LEE CO EC;6U
Adder
18.019
274762LEE CO EC;3U
Adder
17.977
274763LEE CO EC;4U
Adder
17.808
972267AH1-718 GEN
Adder
7.955
247621Y3-024
Adder
0.32
270471AD2-092_GEN
Solar/Wind Helper
1.53
971333AH1-146 GEN
Solar/Wind Harmer
33.502
971335AH1-147 GEN
Solar/Wind Harmer
33.502
270043AE2-236 GEN
Solar/Wind Harmer
12.133
945111AF1-176 GEN
Solar/Wind Harmer
12.396
274772LINCOLN ;3U
Adder
13.446
24441205WTRV SLR C
Solar/Wind Harmer
0.289
270535AF1-215 GEN1
Solar/Wind Harmer
9.745
274724RIVER EC ;11
Adder
37.943
972231SS25-0005
Solar/Wind Harmer
20.313
972181SS23-001
Solar/Wind Harmer
12.696
274752CRETE EC ;2U
Adder
10.462
274753CRETE EC ;3U
Adder
10.462
247604X1-042
Adder
0.885
970707AG2-453 GEN
Solar/Wind Harmer
59.407
964401AG1-302 GEN
Solar/Wind Harmer
19.217
274802UNIV PARK;5U
Adder
12.325
274826FISK ;BP
Adder
23.138
276772AC2-154 GEN
Solar/Wind Harmer
5.888
276806AD2-047 C O1
Solar/Wind Harmer
22.586
970941AG2-585 GEN
Solar/Wind Harmer
26.392
274800UNIV PARK;3U
Adder
12.307
972038AH1-567 GEN2
Adder
0.77
972228AH1-698 GEN2
Adder
7.816
276897AD1-100 C
Solar/Wind Harmer
60.93
939351AE1-166 GEN
Solar/Wind Harmer
12.45
959141AF2-205 GEN
Solar/Wind Harmer
12.662
970031AG2-029 GEN
Solar/Wind Harmer
62.778
274676JOLIET 29;8U
Adder
61.9
274729ELWOOD EC;1P
Adder
34.297
274730ELWOOD EC;6P
Adder
34.297
274734ELWOOD EC;8P
Adder
34.297
274736ELWOOD EC;9P
Adder
34.297
276893AG1-478 C
Solar/Wind Harmer
0.871
943121AE2-341 GEN
Solar/Wind Harmer
31.095
943591AF1-030 GEN
Solar/Wind Harmer
20.73
276694AA1-018 GEN2
Solar/Wind Harmer
12.879
274682WAUKEGAN ;7U
Adder
36.631
944531AF1-118 GEN
Solar/Wind Harmer
70.934
274872LEEDK;1U
Solar/Wind Harmer
0.515
276805AD2-038 GEN
Solar/Wind Harmer
10.329
24755605MDL-5G
Solar/Wind Harmer
4.826
970781AG2-491 GEN
Solar/Wind Harmer
20.008
276799AD1-013 GEN
Solar/Wind Harmer
4.408
946671AF1-331 GEN
Solar/Wind Harmer
0.835
274855GSG-6 ;RU
Solar/Wind Harmer
7.359
274850MENDOTA H;RU
Solar/Wind Harmer
5.117
276602WESTBROOK C
Solar/Wind Harmer
4.236
276863AD2-134 GEN
Solar/Wind Harmer
3.559
972236AH1-702 GEN2
Adder
4.308
274760LEE CO EC;1U
Adder
17.977
274767LEE CO EC;8U
Adder
17.765
24728705AND G3
Adder
10.55
24728505AND G1
Adder
5.044
971599AH1-298 GEN
50/50
20.9
270144AC1-141 ST1_
50/50
4.729
24643105BUCHANAN
50/50
0.028
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
35.714
960681AF2-359 GEN
Solar/Wind Harmer
8.455
971771AH1-392 GEN
Solar/Wind Harmer
20.095
971769AH1-391 GEN
Solar/Wind Harmer
22.253
270071AF1-092 GEN
Solar/Wind Harmer
32.895
944161AF1-084 GEN
Solar/Wind Harmer
4.798
274775LINCOLN ;6U
Adder
13.446
274776LINCOLN ;7U
Adder
13.446
274777LINCOLN ;8U
Adder
13.446
270536AF1-215 GEN2
Solar/Wind Harmer
9.745
274814UNIV PK N;0U
Adder
10.744
274807UNIV PK N;3U
Adder
10.721
274805UNIV PK N;1U
Adder
10.674
274811UNIV PK N;7U
Adder
10.651
972037AH1-567 GEN1
Adder
0.387
274827FISK ;RP
Adder
16.398
960591AF2-350 GEN
Solar/Wind Harmer
21.113
972227AH1-698 GEN1
Adder
5.503
958391AF2-133 GEN
Solar/Wind Harmer
19.092
274687WILL CNTY;4U
Adder
58.542
274687WILL CNTY;4U
Adder
58.542
274675JOLIET 29;7U
Adder
64.194
274675JOLIET 29;7U
Adder
61.901
274731ELWOOD EC;2P
Adder
34.297
274733ELWOOD EC;3P
Adder
34.297
274735ELWOOD EC;4P
Adder
34.297
274728ELWOOD EC;5P
Adder
34.297
970833AG2-524 GEN
Solar/Wind Harmer
18.19
970833AG2-524 GEN
Solar/Wind Harmer
8.46
274746AC1-111 G10
Adder
11.564
274744AC1-111 GEN8
Adder
11.564
276868AE1-113 GEN
Solar/Wind Harmer
20.269
276882AE2-255 GEN
Solar/Wind Harmer
6.757
971177AH1-047 GEN
Solar/Wind Harmer
11.733
24690905MDL-1G C
Solar/Wind Harmer
16.067
270180AB1-006 GEN1
Solar/Wind Harmer
14.393
946581AF1-322 GEN
Solar/Wind Harmer
20.475
24691005MDL-2G C
Solar/Wind Harmer
7.401
24697605MDL-3G C
Solar/Wind Harmer
7.378
24697905MDL-4G C
Solar/Wind Harmer
4.593
270181AB1-006 GEN2
Solar/Wind Harmer
1.431
971411AH1-196 GEN
Solar/Wind Harmer
29.896
971675AH1-338 GEN
Solar/Wind Harmer
35.874
24729505KEY G4
Adder
12.834
274823ROCKFORD ;21
Adder
38.397
944201AF1-088_MTX
Adder
146.322
957141AF2-008_MTX
Adder
73.161
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.633
CBM West 1LTFEXP_CBM-W1->PJM
CBM
228.49
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.819
MECLTFEXP_MEC->PJM
CLTF
26.916
SIGELTFEXP_SIGE->PJM
CLTF
0.505
LAGNLTFEXP_LAGN->PJM
CLTF
13.672
TVALTFEXP_TVA->PJM
CLTF
5.007
CBM West 2LTFEXP_CBM-W2->PJM
CBM
127.851
NYPJM->LTFIMP_NY
CLTF
3.427
LGEELTFEXP_LGEE->PJM
CLTF
4.47
WECLTFEXP_WEC->PJM
CLTF
7.49
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.475
AH1-155LTFEXP_AH1-155->PJM
LTF
0.712

Details for 05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.7 %
Rating:6066.0 MVA
Rating Type:B
MVA to Mitigate:6350.84
MW Contribution:58.98
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.346
270100X2-052 CT1
50/50
3.083
270101X2-052 CT2
50/50
3.083
274770LINCOLN ;1U
50/50
13.384
274771LINCOLN ;2U
50/50
13.384
970321AG2-212 GEN
Solar/Wind Harmer
39.594
965681AG1-436 GEN
Solar/Wind Harmer
25.984
965791AG1-447 GEN
Solar/Wind Harmer
13.294
270526AF1-158 GEN
Solar/Wind Harmer
9.408
24441505OLIV SLR
Solar/Wind Harmer
0.277
270216AD2-079_GEN
Solar/Wind Harmer
1.252
957891AF2-083 GEN
Solar/Wind Harmer
6.914
960981AF2-389 GEN
Solar/Wind Harmer
3.098
961051AF2-396 GEN
Solar/Wind Harmer
32.298
961051AF2-396 GEN
Solar/Wind Harmer
15.022
247620Y3-023
Adder
0.93
274808UNIV PK N;4U
Adder
9.944
972259AH1-714 GEN
Adder
37.882
274803UNIV PARK;6U
Adder
11.574
274888KELLY CRK;1U
Solar/Wind Harmer
11.713
274887GEN-1.85
Solar/Wind Harmer
10.575
276843GEN-1.7
Solar/Wind Harmer
1.138
958011AF2-095 GEN
Solar/Wind Harmer
28.568
274674JOLIET 9 ;6U
Adder
30.252
274847GR RIDGE ;BU
Solar/Wind Harmer
9.918
971573AH1-285 GEN
Solar/Wind Harmer
16.69
274695ROCKY RD ;2P
Adder
21.435
274693ROCKY RD ;1P
Adder
21.224
274697ROCKY RD ;3P
Adder
5.823
274696ROCKY RD ;4P
Adder
21.94
958481AF2-142 GEN
Solar/Wind Harmer
28.872
274861TOP CROP ;1U
Solar/Wind Harmer
11.657
274862TOP CROP ;2U
Solar/Wind Harmer
9.734
274683WAUKEGAN ;8U
Adder
40.442
24344005CKG1
50/50
13.598
270142AC1-141 CT1_
50/50
4.968
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.387
274772LINCOLN ;3U
50/50
13.384
970513AG2-328 GEN
Solar/Wind Harmer
39.594
970517AG2-330 GEN
Solar/Wind Harmer
35.91
970349AG2-230 GEN
Solar/Wind Harmer
33.197
270043AE2-236 GEN
Solar/Wind Harmer
11.487
247643Z2-116 C
Solar/Wind Harmer
0.144
945111AF1-176 GEN
Solar/Wind Harmer
11.54
274724RIVER EC ;11
Adder
35.562
972231SS25-0005
Solar/Wind Harmer
19.02
972181SS23-001
Solar/Wind Harmer
11.887
274752CRETE EC ;2U
Adder
9.796
274753CRETE EC ;3U
Adder
9.796
24441205WTRV SLR C
Solar/Wind Harmer
0.269
970707AG2-453 GEN
Solar/Wind Harmer
55.829
274802UNIV PARK;5U
Adder
11.574
274826FISK ;BP
Adder
21.73
276772AC2-154 GEN
Solar/Wind Harmer
5.533
276806AD2-047 C O1
Solar/Wind Harmer
21.223
970941AG2-585 GEN
Solar/Wind Harmer
24.799
972228AH1-698 GEN2
Adder
7.346
274800UNIV PARK;3U
Adder
11.561
972038AH1-567 GEN2
Adder
0.724
276897AD1-100 C
Solar/Wind Harmer
57.337
939351AE1-166 GEN
Solar/Wind Harmer
11.715
247604X1-042
Adder
0.823
270535AF1-215 GEN1
Solar/Wind Harmer
8.953
274676JOLIET 29;8U
Adder
58.214
970031AG2-029 GEN
Solar/Wind Harmer
58.977
274729ELWOOD EC;1P
Adder
32.272
274730ELWOOD EC;6P
Adder
32.272
274734ELWOOD EC;8P
Adder
32.272
274736ELWOOD EC;9P
Adder
32.272
276893AG1-478 C
Solar/Wind Harmer
0.82
944531AF1-118 GEN
Solar/Wind Harmer
68.666
943121AE2-341 GEN
Solar/Wind Harmer
29.28
943591AF1-030 GEN
Solar/Wind Harmer
19.52
964401AG1-302 GEN
Solar/Wind Harmer
17.606
276694AA1-018 GEN2
Solar/Wind Harmer
12.147
274682WAUKEGAN ;7U
Adder
34.537
959141AF2-205 GEN
Solar/Wind Harmer
11.571
276805AD2-038 GEN
Solar/Wind Harmer
9.758
274872LEEDK;1U
Solar/Wind Harmer
0.487
276799AD1-013 GEN
Solar/Wind Harmer
4.166
946671AF1-331 GEN
Solar/Wind Harmer
0.789
274855GSG-6 ;RU
Solar/Wind Harmer
6.955
274850MENDOTA H;RU
Solar/Wind Harmer
4.836
276602WESTBROOK C
Solar/Wind Harmer
4.003
276863AD2-134 GEN
Solar/Wind Harmer
3.363
959091AF2-200 GEN
Solar/Wind Harmer
37.421
276889AE2-281 GEN
Solar/Wind Harmer
3.59
972236AH1-702 GEN2
Adder
4.076
274760LEE CO EC;1U
Adder
17.04
274767LEE CO EC;8U
Adder
16.84
971599AH1-298 GEN
50/50
19.943
270144AC1-141 ST1_
50/50
4.4
24344105CKG2
50/50
17.375
270143AC1-141 CT2_
50/50
4.968
24639705ELKHART HY
50/50
0.332
274773LINCOLN ;4U
50/50
13.384
274774LINCOLN ;5U
50/50
13.384
970521AG2-332 GEN
50/50
23.621
970245AG2-165 GEN
Solar/Wind Harmer
39.594
270505AE1-170 C O1
Solar/Wind Harmer
30.803
945111AF1-176 GEN
Solar/Wind Harmer
36.413
972207SS24-0001
Solar/Wind Harmer
44.846
270449AD2-020 GEN
Solar/Wind Harmer
5.693
943021AE2-325 GEN
Solar/Wind Harmer
7.398
274723RIVER EC ;12
Adder
35.977
970373AG2-245 GEN
Solar/Wind Harmer
42.088
274751CRETE EC ;1U
Adder
9.796
274754CRETE EC ;4U
Adder
9.796
276164X3-005 C
Solar/Wind Harmer
1.405
270063AE2-323 C
Solar/Wind Harmer
4.395
274812UNIV PK N;8U
Adder
9.987
276776AD2-060 GEN
Solar/Wind Harmer
0.839
274801UNIV PARK;4U
Adder
11.561
941551AE2-152 GEN
Solar/Wind Harmer
8.961
270055AF2-134 C O1
Solar/Wind Harmer
5.968
274676JOLIET 29;8U
Adder
60.37
274674JOLIET 9 ;6U
Adder
30.252
274732ELWOOD EC;7P
Adder
32.272
274871GR RIDGE ;2U
Solar/Wind Harmer
15.077
274745AC1-111 GEN9
Adder
10.891
958381AF2-132 GEN
Solar/Wind Harmer
17.606
964861AG1-349 GEN
Solar/Wind Harmer
15.23
971917AH1-482 GEN
Solar/Wind Harmer
17.576
276691AA1-018 GEN1
Solar/Wind Harmer
0.896
274682WAUKEGAN ;7U
Adder
34.537
274828WAUKEGAN ;BP
Adder
21.199
939401AE1-172 GEN
Solar/Wind Harmer
26.601
960751AF2-366 GEN
Solar/Wind Harmer
5.47
962781AG1-127 GEN
Solar/Wind Harmer
18.131
274872LEEDK;1U
Solar/Wind Harmer
15.624
940581AE2-045 GEN
Solar/Wind Harmer
19.376
276901AD2-066 C O1
Solar/Wind Harmer
6.676
971605AH1-302 GEN
Solar/Wind Harmer
16.569
971997AH1-543 GEN
Solar/Wind Harmer
29.779
276861AD2-134 GEN
Solar/Wind Harmer
3.363
957471AF2-041 GEN
Solar/Wind Harmer
56.132
959081AF2-199 GEN
Solar/Wind Harmer
18.711
971067AG2-660 GEN
Solar/Wind Harmer
4.351
276876AE1-163_GEN2
Solar/Wind Harmer
12.566
274822ROCKFORD ;11
Adder
36.587
972235AH1-702 GEN1
Adder
4.687
274761LEE CO EC;2U
Adder
17.04
274766LEE CO EC;7U
Adder
16.84
970091AG2-072 GEN
Adder
32.358
270349AD2-093_GEN
Solar/Wind Helper
1.555
274683WAUKEGAN ;8U
Adder
34.091
962691AG1-118 GEN
Solar/Wind Harmer
57.342
970921AG2-575 GEN
Solar/Wind Harmer
19.065
970921AG2-575 GEN
Solar/Wind Harmer
4.434
958491AF2-143 GEN
Solar/Wind Harmer
28.532
274879MINONK ;1U
Solar/Wind Harmer
12.777
942991AE2-321 GEN
Solar/Wind Harmer
18.919
971333AH1-146 GEN
Solar/Wind Harmer
37.64
971335AH1-147 GEN
Solar/Wind Harmer
37.64
971341AH1-150 GEN
Solar/Wind Harmer
37.421
971343AH1-151 GEN
Solar/Wind Harmer
37.421
276872AE1-163_GEN1
Solar/Wind Harmer
12.566
274764LEE CO EC;5U
Adder
17.08
274765LEE CO EC;6U
Adder
17.08
274762LEE CO EC;3U
Adder
17.04
274763LEE CO EC;4U
Adder
16.88
972267AH1-718 GEN
Adder
7.55
270471AD2-092_GEN
Solar/Wind Helper
1.555
945421AF1-207 GEN
Solar/Wind Harmer
23.561
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
13.384
274776LINCOLN ;7U
50/50
13.384
274777LINCOLN ;8U
50/50
13.384
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
33.197
960681AF2-359 GEN
Solar/Wind Harmer
7.853
971771AH1-392 GEN
Solar/Wind Harmer
18.701
971769AH1-391 GEN
Solar/Wind Harmer
20.689
270071AF1-092 GEN
Solar/Wind Harmer
30.794
944161AF1-084 GEN
Solar/Wind Harmer
4.463
274814UNIV PK N;0U
Adder
10.075
274807UNIV PK N;3U
Adder
10.053
274805UNIV PK N;1U
Adder
10.009
274811UNIV PK N;7U
Adder
9.987
972037AH1-567 GEN1
Adder
0.363
274827FISK ;RP
Adder
15.4
960591AF2-350 GEN
Solar/Wind Harmer
19.839
972227AH1-698 GEN1
Adder
5.172
270536AF1-215 GEN2
Solar/Wind Harmer
8.953
274687WILL CNTY;4U
Adder
55.044
274687WILL CNTY;4U
Adder
55.044
274675JOLIET 29;7U
Adder
60.371
274675JOLIET 29;7U
Adder
58.215
274731ELWOOD EC;2P
Adder
32.272
274733ELWOOD EC;3P
Adder
32.272
274735ELWOOD EC;4P
Adder
32.272
274728ELWOOD EC;5P
Adder
32.272
970833AG2-524 GEN
Solar/Wind Harmer
17.125
970833AG2-524 GEN
Solar/Wind Harmer
7.965
274746AC1-111 G10
Adder
10.891
274744AC1-111 GEN8
Adder
10.891
958391AF2-133 GEN
Solar/Wind Harmer
17.467
24729505KEY G4
Adder
12.444
276868AE1-113 GEN
Solar/Wind Harmer
19.163
276882AE2-255 GEN
Solar/Wind Harmer
6.388
971177AH1-047 GEN
Solar/Wind Harmer
11.082
971675AH1-338 GEN
Solar/Wind Harmer
33.905
971411AH1-196 GEN
Solar/Wind Harmer
28.25
274863CRW1-WTG
Solar/Wind Harmer
10.504
274864CRW2-WTG
Solar/Wind Harmer
10.504
971171AH1-044 GEN
Solar/Wind Harmer
37.421
274823ROCKFORD ;21
Adder
36.321
944201AF1-088_MTX
Adder
162.845
957141AF2-008_MTX
Adder
81.423
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.535
CBM West 1LTFEXP_CBM-W1->PJM
CBM
216.955
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.977
MECLTFEXP_MEC->PJM
CLTF
25.953
SIGELTFEXP_SIGE->PJM
CLTF
0.549
LAGNLTFEXP_LAGN->PJM
CLTF
14.056
TVALTFEXP_TVA->PJM
CLTF
5.361
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.514
NYPJM->LTFIMP_NY
CLTF
3.416
LGEELTFEXP_LGEE->PJM
CLTF
5.556
WECLTFEXP_WEC->PJM
CLTF
7.087
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.221
AG2-052LTFEXP_AG2-052->PJM
LTF
0.446
AH1-155LTFEXP_AH1-155->PJM
LTF
0.669

Details for 05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.61 %
Rating:6066.0 MVA
Rating Type:B
MVA to Mitigate:6284.8
MW Contribution:59.12
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
17.41
270143AC1-141 CT2_
50/50
4.979
24639705ELKHART HY
50/50
0.333
274773LINCOLN ;4U
50/50
13.415
274774LINCOLN ;5U
50/50
13.415
970521AG2-332 GEN
50/50
23.674
970245AG2-165 GEN
Solar/Wind Harmer
39.676
270505AE1-170 C O1
Solar/Wind Harmer
30.872
945111AF1-176 GEN
Solar/Wind Harmer
36.495
972207SS24-0001
Solar/Wind Harmer
44.948
270449AD2-020 GEN
Solar/Wind Harmer
5.706
943021AE2-325 GEN
Solar/Wind Harmer
7.414
274723RIVER EC ;12
Adder
36.059
970373AG2-245 GEN
Solar/Wind Harmer
42.185
274751CRETE EC ;1U
Adder
9.818
274754CRETE EC ;4U
Adder
9.818
276164X3-005 C
Solar/Wind Harmer
1.409
270063AE2-323 C
Solar/Wind Harmer
4.405
274812UNIV PK N;8U
Adder
10.011
276776AD2-060 GEN
Solar/Wind Harmer
0.841
274801UNIV PARK;4U
Adder
11.588
941551AE2-152 GEN
Solar/Wind Harmer
8.982
270055AF2-134 C O1
Solar/Wind Harmer
5.982
274676JOLIET 29;8U
Adder
60.512
274674JOLIET 9 ;6U
Adder
30.323
274732ELWOOD EC;7P
Adder
32.348
274871GR RIDGE ;2U
Solar/Wind Harmer
15.112
274745AC1-111 GEN9
Adder
10.916
958381AF2-132 GEN
Solar/Wind Harmer
17.648
964861AG1-349 GEN
Solar/Wind Harmer
15.267
971917AH1-482 GEN
Solar/Wind Harmer
17.617
276691AA1-018 GEN1
Solar/Wind Harmer
0.898
274682WAUKEGAN ;7U
Adder
34.62
274828WAUKEGAN ;BP
Adder
21.25
939401AE1-172 GEN
Solar/Wind Harmer
26.665
960751AF2-366 GEN
Solar/Wind Harmer
5.483
962781AG1-127 GEN
Solar/Wind Harmer
18.175
274872LEEDK;1U
Solar/Wind Harmer
15.662
940581AE2-045 GEN
Solar/Wind Harmer
19.423
971605AH1-302 GEN
Solar/Wind Harmer
16.609
276901AD2-066 C O1
Solar/Wind Harmer
6.692
971997AH1-543 GEN
Solar/Wind Harmer
29.852
276861AD2-134 GEN
Solar/Wind Harmer
3.372
957471AF2-041 GEN
Solar/Wind Harmer
56.27
959081AF2-199 GEN
Solar/Wind Harmer
18.757
971067AG2-660 GEN
Solar/Wind Harmer
4.362
276876AE1-163_GEN2
Solar/Wind Harmer
12.597
274822ROCKFORD ;11
Adder
36.677
972235AH1-702 GEN1
Adder
4.699
274761LEE CO EC;2U
Adder
17.083
274766LEE CO EC;7U
Adder
16.882
970091AG2-072 GEN
Adder
32.467
270349AD2-093_GEN
Solar/Wind Helper
1.548
24344005CKG1
50/50
13.628
270142AC1-141 CT1_
50/50
4.979
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.39
274772LINCOLN ;3U
50/50
13.415
970513AG2-328 GEN
Solar/Wind Harmer
39.676
970517AG2-330 GEN
Solar/Wind Harmer
35.985
970349AG2-230 GEN
Solar/Wind Harmer
33.266
270043AE2-236 GEN
Solar/Wind Harmer
11.512
247643Z2-116 C
Solar/Wind Harmer
0.145
945111AF1-176 GEN
Solar/Wind Harmer
11.566
274724RIVER EC ;11
Adder
35.644
972231SS25-0005
Solar/Wind Harmer
19.064
972181SS23-001
Solar/Wind Harmer
11.915
274752CRETE EC ;2U
Adder
9.818
274753CRETE EC ;3U
Adder
9.818
24441205WTRV SLR C
Solar/Wind Harmer
0.27
970707AG2-453 GEN
Solar/Wind Harmer
55.958
274802UNIV PARK;5U
Adder
11.601
274826FISK ;BP
Adder
21.78
276772AC2-154 GEN
Solar/Wind Harmer
5.545
276806AD2-047 C O1
Solar/Wind Harmer
21.273
970941AG2-585 GEN
Solar/Wind Harmer
24.857
972228AH1-698 GEN2
Adder
7.363
274800UNIV PARK;3U
Adder
11.588
972038AH1-567 GEN2
Adder
0.725
276897AD1-100 C
Solar/Wind Harmer
57.471
939351AE1-166 GEN
Solar/Wind Harmer
11.743
247604X1-042
Adder
0.825
270535AF1-215 GEN1
Solar/Wind Harmer
8.974
274676JOLIET 29;8U
Adder
58.35
970031AG2-029 GEN
Solar/Wind Harmer
59.115
274729ELWOOD EC;1P
Adder
32.348
274730ELWOOD EC;6P
Adder
32.348
274734ELWOOD EC;8P
Adder
32.348
274736ELWOOD EC;9P
Adder
32.348
276893AG1-478 C
Solar/Wind Harmer
0.821
944531AF1-118 GEN
Solar/Wind Harmer
68.828
943121AE2-341 GEN
Solar/Wind Harmer
29.349
943591AF1-030 GEN
Solar/Wind Harmer
19.566
964401AG1-302 GEN
Solar/Wind Harmer
17.648
276694AA1-018 GEN2
Solar/Wind Harmer
12.176
274682WAUKEGAN ;7U
Adder
34.62
959141AF2-205 GEN
Solar/Wind Harmer
11.599
276805AD2-038 GEN
Solar/Wind Harmer
9.782
274872LEEDK;1U
Solar/Wind Harmer
0.488
276799AD1-013 GEN
Solar/Wind Harmer
4.176
946671AF1-331 GEN
Solar/Wind Harmer
0.791
274855GSG-6 ;RU
Solar/Wind Harmer
6.972
274850MENDOTA H;RU
Solar/Wind Harmer
4.848
276602WESTBROOK C
Solar/Wind Harmer
4.013
276863AD2-134 GEN
Solar/Wind Harmer
3.372
959091AF2-200 GEN
Solar/Wind Harmer
37.513
276889AE2-281 GEN
Solar/Wind Harmer
3.599
972236AH1-702 GEN2
Adder
4.086
274760LEE CO EC;1U
Adder
17.083
274767LEE CO EC;8U
Adder
16.882
971599AH1-298 GEN
50/50
19.983
270144AC1-141 ST1_
50/50
4.41
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
13.415
274776LINCOLN ;7U
50/50
13.415
274777LINCOLN ;8U
50/50
13.415
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
33.266
960681AF2-359 GEN
Solar/Wind Harmer
7.871
971771AH1-392 GEN
Solar/Wind Harmer
18.742
971769AH1-391 GEN
Solar/Wind Harmer
20.735
270071AF1-092 GEN
Solar/Wind Harmer
30.863
944161AF1-084 GEN
Solar/Wind Harmer
4.473
274814UNIV PK N;0U
Adder
10.098
274807UNIV PK N;3U
Adder
10.076
274805UNIV PK N;1U
Adder
10.033
274811UNIV PK N;7U
Adder
10.011
972037AH1-567 GEN1
Adder
0.364
274827FISK ;RP
Adder
15.436
960591AF2-350 GEN
Solar/Wind Harmer
19.885
972227AH1-698 GEN1
Adder
5.185
270536AF1-215 GEN2
Solar/Wind Harmer
8.974
274687WILL CNTY;4U
Adder
55.173
274687WILL CNTY;4U
Adder
55.173
274675JOLIET 29;7U
Adder
60.513
274675JOLIET 29;7U
Adder
58.351
274731ELWOOD EC;2P
Adder
32.348
274733ELWOOD EC;3P
Adder
32.348
274735ELWOOD EC;4P
Adder
32.348
274728ELWOOD EC;5P
Adder
32.348
970833AG2-524 GEN
Solar/Wind Harmer
17.166
970833AG2-524 GEN
Solar/Wind Harmer
7.984
274746AC1-111 G10
Adder
10.916
274744AC1-111 GEN8
Adder
10.916
958391AF2-133 GEN
Solar/Wind Harmer
17.509
24729505KEY G4
Adder
12.474
276868AE1-113 GEN
Solar/Wind Harmer
19.21
270102X2-052 ST
50/50
3.353
270100X2-052 CT1
50/50
3.09
270101X2-052 CT2
50/50
3.09
274770LINCOLN ;1U
50/50
13.415
274771LINCOLN ;2U
50/50
13.415
970321AG2-212 GEN
Solar/Wind Harmer
39.676
965681AG1-436 GEN
Solar/Wind Harmer
26.042
965791AG1-447 GEN
Solar/Wind Harmer
13.324
270526AF1-158 GEN
Solar/Wind Harmer
9.429
24441505OLIV SLR
Solar/Wind Harmer
0.278
270216AD2-079_GEN
Solar/Wind Harmer
1.255
957891AF2-083 GEN
Solar/Wind Harmer
6.929
960981AF2-389 GEN
Solar/Wind Harmer
3.105
961051AF2-396 GEN
Solar/Wind Harmer
32.372
961051AF2-396 GEN
Solar/Wind Harmer
15.057
247620Y3-023
Adder
0.932
274808UNIV PK N;4U
Adder
9.967
972259AH1-714 GEN
Adder
37.97
274803UNIV PARK;6U
Adder
11.601
274888KELLY CRK;1U
Solar/Wind Harmer
11.74
274887GEN-1.85
Solar/Wind Harmer
10.599
276843GEN-1.7
Solar/Wind Harmer
1.14
958011AF2-095 GEN
Solar/Wind Harmer
28.635
274674JOLIET 9 ;6U
Adder
30.323
274847GR RIDGE ;BU
Solar/Wind Harmer
9.941
971573AH1-285 GEN
Solar/Wind Harmer
16.73
274695ROCKY RD ;2P
Adder
21.486
274693ROCKY RD ;1P
Adder
21.275
274697ROCKY RD ;3P
Adder
5.837
274696ROCKY RD ;4P
Adder
21.993
958481AF2-142 GEN
Solar/Wind Harmer
28.942
274861TOP CROP ;1U
Solar/Wind Harmer
11.685
274862TOP CROP ;2U
Solar/Wind Harmer
9.757
274683WAUKEGAN ;8U
Adder
40.539
274683WAUKEGAN ;8U
Adder
34.173
962691AG1-118 GEN
Solar/Wind Harmer
57.48
970921AG2-575 GEN
Solar/Wind Harmer
19.111
970921AG2-575 GEN
Solar/Wind Harmer
4.444
958491AF2-143 GEN
Solar/Wind Harmer
28.602
274879MINONK ;1U
Solar/Wind Harmer
12.808
942991AE2-321 GEN
Solar/Wind Harmer
18.965
971333AH1-146 GEN
Solar/Wind Harmer
37.732
971335AH1-147 GEN
Solar/Wind Harmer
37.732
971341AH1-150 GEN
Solar/Wind Harmer
37.513
971343AH1-151 GEN
Solar/Wind Harmer
37.513
276872AE1-163_GEN1
Solar/Wind Harmer
12.597
274764LEE CO EC;5U
Adder
17.123
274765LEE CO EC;6U
Adder
17.123
274762LEE CO EC;3U
Adder
17.083
274763LEE CO EC;4U
Adder
16.922
972267AH1-718 GEN
Adder
7.569
270471AD2-092_GEN
Solar/Wind Helper
1.548
945421AF1-207 GEN
Solar/Wind Harmer
23.62
276882AE2-255 GEN
Solar/Wind Harmer
6.404
971177AH1-047 GEN
Solar/Wind Harmer
11.109
971675AH1-338 GEN
Solar/Wind Harmer
33.988
971411AH1-196 GEN
Solar/Wind Harmer
28.319
274863CRW1-WTG
Solar/Wind Harmer
10.53
274864CRW2-WTG
Solar/Wind Harmer
10.53
971171AH1-044 GEN
Solar/Wind Harmer
37.513
274823ROCKFORD ;21
Adder
36.411
944201AF1-088_MTX
Adder
163.382
957141AF2-008_MTX
Adder
81.691
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.154
MECLTFEXP_MEC->PJM
CLTF
26.031
SIGELTFEXP_SIGE->PJM
CLTF
0.551
LAGNLTFEXP_LAGN->PJM
CLTF
14.15
TVALTFEXP_TVA->PJM
CLTF
5.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.138
NYPJM->LTFIMP_NY
CLTF
3.386
LGEELTFEXP_LGEE->PJM
CLTF
5.588
WECLTFEXP_WEC->PJM
CLTF
7.104
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.447
AH1-155LTFEXP_AH1-155->PJM
LTF
0.671

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.08 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2967.71
MW Contribution:16.05
Bus #Bus NameTypeMW Contribution
964351AG1-297 GEN
50/50
22.593
961161AF2-407 GEN
50/50
55.693
24728705AND G3
50/50
11.013
24728505AND G1
50/50
5.266
270437AC2-090 C
Solar/Wind Harmer
13.802
270356AE2-297 GEN
Solar/Wind Harmer
10.957
958821AF2-173 GEN
Solar/Wind Harmer
26.801
270004AE1-209 GEN
Solar/Wind Harmer
10.462
946031AF1-268 GEN
Solar/Wind Harmer
13.344
962031AG1-047 GEN
Solar/Wind Harmer
3.781
957741AF2-068 GEN
Solar/Wind Harmer
18.765
270222AC2-111 GEN
Solar/Wind Harmer
10.014
944531AF1-118 GEN
Solar/Wind Harmer
42.975
970289AG2-191 GEN
Solar/Wind Harmer
0.923
970291AG2-192 GEN
Solar/Wind Harmer
0.839
247642Z2-115 C
Solar/Wind Harmer
0.07
971617AH1-308 GEN
Solar/Wind Harmer
6.273
970193AG2-126 GEN
Solar/Wind Harmer
9.994
270043AE2-236 GEN
Solar/Wind Harmer
3.487
959331AF2-224 GEN
Solar/Wind Harmer
5.374
965021AG1-366 GEN
Solar/Wind Harmer
1.25
970031AG2-029 GEN
Solar/Wind Harmer
16.051
24755605MDL-5G
Solar/Wind Harmer
1.223
970781AG2-491 GEN
Solar/Wind Harmer
5.069
276686W4-005 GEN3
Solar/Wind Harmer
1.513
971993AH1-541 GEN
Solar/Wind Harmer
4.621
276668AB2-070 GEN1
Solar/Wind Harmer
1.124
276621W2-048 GEN
Solar/Wind Harmer
3.106
276838X2-022 GEN2
Solar/Wind Harmer
0.116
942481AE2-261 GEN
Solar/Wind Harmer
14.791
274853TWINGROVE;U1
Solar/Wind Harmer
3.535
965091AG1-374 GEN
Solar/Wind Harmer
14.716
959611AF2-252 GEN
Solar/Wind Harmer
1.141
942111AE2-223 GEN
Solar/Wind Harmer
4.014
959141AF2-205 GEN
Solar/Wind Harmer
2.954
964401AG1-302 GEN
Solar/Wind Harmer
4.4
270535AF1-215 GEN1
Solar/Wind Harmer
2.186
247643Z2-116 C
Solar/Wind Harmer
0.033
274752CRETE EC ;2U
Adder
3.842
274753CRETE EC ;3U
Adder
3.842
274724RIVER EC ;11
Adder
8.239
24642205MAYFLWER
Adder
0.295
972228AH1-698 GEN2
Adder
1.721
274802UNIV PARK;5U
Adder
2.707
274800UNIV PARK;3U
Adder
2.705
972038AH1-567 GEN2
Adder
0.169
274826FISK ;BP
Adder
5.075
274729ELWOOD EC;1P
Adder
7.617
274730ELWOOD EC;6P
Adder
7.617
274734ELWOOD EC;8P
Adder
7.617
274736ELWOOD EC;9P
Adder
7.617
274676JOLIET 29;8U
Adder
13.667
274772LINCOLN ;3U
Adder
3.895
274682WAUKEGAN ;7U
Adder
8.211
972236AH1-702 GEN2
Adder
0.99
274760LEE CO EC;1U
Adder
4.19
252510AF1-249 C
Solar/Wind Helper
0.565
253406AD2-031_GEN
Solar/Wind Helper
0.857
253415AE1-040 GEN
Solar/Wind Helper
0.538
253338AC1-165 GEN
Solar/Wind Helper
0.547
253333AC1-068 GEN
Solar/Wind Helper
0.567
24729405KEY G3
50/50
0.486
24729305KEY G2
50/50
0.478
24729205KEY G1
50/50
0.475
247621Y3-024
50/50
0.306
24728805RICHG1
50/50
4.511
24728905RICHG2
50/50
4.511
24379505HDWTR1G C
Solar/Wind Harmer
19.548
270209AC1-174_GEN
Solar/Wind Harmer
13.796
926881AC1-175 GEN
Solar/Wind Harmer
13.796
970825AG2-519 GEN
Solar/Wind Harmer
17.311
960441AF2-335 GEN
Solar/Wind Harmer
16.096
270383AD1-128 GEN
Solar/Wind Harmer
9.53
944541AF1-119 GEN
Solar/Wind Harmer
6.179
960971AF2-388 GEN
Solar/Wind Harmer
16.125
270599AE1-208 GEN
Solar/Wind Harmer
11.727
270031AE2-169
Solar/Wind Harmer
11.727
24726405LAWG1A
50/50
5.74
960791AF2-370 GEN
50/50
3.743
961171AF2-408 GEN
50/50
15.013
24728605AND G2
50/50
5.266
942081AE2-220 GEN
Solar/Wind Harmer
15.805
270239V3-007_GEN1
Solar/Wind Harmer
4.254
270005AE1-210 C O1
Solar/Wind Harmer
10.462
965031AG1-367 GEN
Solar/Wind Harmer
19.144
945371AF1-202 GEN
Solar/Wind Harmer
11.502
970825AG2-519 GEN
Solar/Wind Harmer
3.863
958861AF2-177 GEN
Solar/Wind Harmer
16.776
965651AG1-433 GEN
Solar/Wind Harmer
8.063
276903AD2-071 C
Solar/Wind Harmer
13.602
270032AE2-172
Solar/Wind Harmer
6.131
247536S-71 GEN
Solar/Wind Harmer
4.887
970291AG2-192 GEN
Solar/Wind Harmer
1.564
963741AG1-226 GEN
Solar/Wind Harmer
26.2
965011AG1-365 GEN
Solar/Wind Harmer
5.374
24385905FR-11G C
Solar/Wind Harmer
4.414
24387305FR-4G C
Solar/Wind Harmer
2.699
270063AE2-323 C
Solar/Wind Harmer
1.127
24791305MDL-5G
Solar/Wind Harmer
1.223
274880W4-005 GEN4
Solar/Wind Harmer
1.513
963831AG1-236 GEN
Solar/Wind Harmer
4.91
270445AC2-157 GEN2
Solar/Wind Harmer
2.779
276615X2-022 GEN
Solar/Wind Harmer
0.975
972175AH1-670 GEN
Solar/Wind Harmer
6.772
965911AG1-460 GEN
Solar/Wind Harmer
0.69
940581AE2-045 GEN
Solar/Wind Harmer
5.003
971605AH1-302 GEN
Solar/Wind Harmer
4.278
274854TWINGROVE;U2
Solar/Wind Harmer
3.461
276726Z2-087_GEN
Solar/Wind Harmer
3.873
939741AE1-205 GEN
Solar/Wind Harmer
9.793
964861AG1-349 GEN
Solar/Wind Harmer
3.816
971917AH1-482 GEN
Solar/Wind Harmer
4.403
958381AF2-132 GEN
Solar/Wind Harmer
4.4
24639705ELKHART HY
Adder
0.074
270055AF2-134 C O1
Solar/Wind Harmer
1.457
970373AG2-245 GEN
Solar/Wind Harmer
10.009
274751CRETE EC ;1U
Adder
3.842
274754CRETE EC ;4U
Adder
3.842
274723RIVER EC ;12
Adder
8.339
274812UNIV PK N;8U
Adder
2.33
274801UNIV PARK;4U
Adder
2.705
274732ELWOOD EC;7P
Adder
7.617
274674JOLIET 9 ;6U
Adder
7.123
274676JOLIET 29;8U
Adder
14.173
274773LINCOLN ;4U
Adder
3.895
274774LINCOLN ;5U
Adder
3.895
274745AC1-111 GEN9
Adder
2.566
274682WAUKEGAN ;7U
Adder
8.211
274828WAUKEGAN ;BP
Adder
5.044
274822ROCKFORD ;11
Adder
8.874
972235AH1-702 GEN1
Adder
1.139
274761LEE CO EC;2U
Adder
1.231
252507AC2-088 GEN
Solar/Wind Helper
1.706
339216AC1-074 GEN
Solar/Wind Helper
0.957
253343AC1-166 GEN
Solar/Wind Helper
0.547
253325AC1-069 GEN
Solar/Wind Helper
0.567
943111AE2-339 GEN
Solar/Wind Helper
0.361
939401AE1-172 GEN
Solar/Wind Harmer
4.626
24726905LAWG2S
50/50
8.873
24726605LAWG1S
50/50
8.864
24726705LAWG2A
50/50
5.965
24726505LAWG1B
50/50
5.923
24726805LAWG2B
50/50
5.905
24729505KEY G4
50/50
8.904
270240V3-007_GEN2
Solar/Wind Harmer
15.295
945581AF1-223 GEN
Solar/Wind Harmer
7.477
970115AG2-085 GEN
Solar/Wind Harmer
6.438
965101AG1-375 GEN
Solar/Wind Harmer
15.348
958711AF2-162 GEN
Solar/Wind Harmer
1.492
24725505WLD G2 C
Solar/Wind Harmer
5.718
24699105WLD G1 C
Solar/Wind Harmer
5.651
270594AE1-207 GEN
Solar/Wind Harmer
19.374
961761AG1-017 GEN
Solar/Wind Harmer
0.535
944031AF1-071 GEN
Solar/Wind Harmer
1.234
965461AG1-414 GEN
Solar/Wind Harmer
2.728
970289AG2-191 GEN
Solar/Wind Harmer
2.286
270543AE2-219 C
Solar/Wind Harmer
6.069
971029AG2-637 GEN
Solar/Wind Harmer
17.299
971673AH1-337 GEN
Solar/Wind Harmer
5.229
270024AE2-089 GEN
Solar/Wind Harmer
5.064
963791AG1-232 GEN
Solar/Wind Harmer
10.819
270071AF1-092 GEN
Solar/Wind Harmer
10.537
963841AG1-237 GEN
Solar/Wind Harmer
6.094
24386205FR-12G C
Solar/Wind Harmer
2.276
24386405FR-21G C
Solar/Wind Harmer
2.284
24386605FR-22G C
Solar/Wind Harmer
2.284
24387005FR-3G C
Solar/Wind Harmer
2.101
24690905MDL-1G C
Solar/Wind Harmer
4.071
270180AB1-006 GEN1
Solar/Wind Harmer
3.646
946581AF1-322 GEN
Solar/Wind Harmer
5.187
24691005MDL-2G C
Solar/Wind Harmer
1.875
24697605MDL-3G C
Solar/Wind Harmer
1.869
24697905MDL-4G C
Solar/Wind Harmer
1.164
270181AB1-006 GEN2
Solar/Wind Harmer
0.363
276785W4-005 GEN1
Solar/Wind Harmer
1.513
276174W4-005 GEN2
Solar/Wind Harmer
1.513
276849AB2-070 GEN2
Solar/Wind Harmer
1.124
276848AB2-070 GEN3
Solar/Wind Harmer
1.124
944221AF1-090 GEN
Solar/Wind Harmer
5.422
276655WTG1_EQ
Solar/Wind Harmer
4.275
276656WTG2_EQ
Solar/Wind Harmer
0.566
959341AF2-225 GEN
Solar/Wind Harmer
7.344
941731AE2-173 GEN
Solar/Wind Harmer
2.847
958391AF2-133 GEN
Solar/Wind Harmer
4.419
270536AF1-215 GEN2
Solar/Wind Harmer
2.186
970169AG2-114 GEN
Solar/Wind Harmer
4.799
274863CRW1-WTG
Solar/Wind Harmer
2.666
274864CRW2-WTG
Solar/Wind Harmer
2.666
965041AG1-368 GEN
Solar/Wind Harmer
4.759
274814UNIV PK N;0U
Adder
2.35
274807UNIV PK N;3U
Adder
2.345
274805UNIV PK N;1U
Adder
2.335
274811UNIV PK N;7U
Adder
2.33
972227AH1-698 GEN1
Adder
1.212
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.597
274731ELWOOD EC;2P
Adder
7.617
274733ELWOOD EC;3P
Adder
7.617
274735ELWOOD EC;4P
Adder
7.617
274728ELWOOD EC;5P
Adder
7.617
274687WILL CNTY;4U
Adder
12.918
274687WILL CNTY;4U
Adder
12.918
274675JOLIET 29;7U
Adder
14.173
274675JOLIET 29;7U
Adder
13.667
274775LINCOLN ;6U
Adder
3.895
274776LINCOLN ;7U
Adder
3.895
274777LINCOLN ;8U
Adder
3.895
274746AC1-111 G10
Adder
2.566
274744AC1-111 GEN8
Adder
2.566
274823ROCKFORD ;21
Adder
8.809
252524AE2-267 GEN
Solar/Wind Helper
0.835
270367AC2-061_GEN
Solar/Wind Helper
1.885
241972AD1-140 GEN
Solar/Wind Helper
2.815
270340AC2-060 GEN
Solar/Wind Helper
1.185
339243AC2-075 GEN1
Solar/Wind Helper
0.22
945631AF1-228 GEN
Solar/Wind Helper
0.936
964611AG1-324 GEN
Solar/Wind Harmer
1.564
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
6.431
970883AG2-550 GEN
Solar/Wind Harmer
11.853
970885AG2-551 GEN
Solar/Wind Harmer
2.757
942221AE2-234 GEN
Solar/Wind Harmer
0.776
945391AF1-204 GEN
Solar/Wind Harmer
9.285
970241AG2-163 GEN
Solar/Wind Harmer
14.556
970611AG2-400 GEN
Solar/Wind Harmer
5.374
966841AG1-555 GEN
Solar/Wind Harmer
1.332
276763AC1-053 GEN1
Solar/Wind Harmer
1.974
276764AC1-053 GEN2
Solar/Wind Harmer
1.974
270444AC2-157 GEN1
Solar/Wind Harmer
2.779
945421AF1-207 GEN
Solar/Wind Harmer
6.965
957841AF2-078 GEN
Solar/Wind Harmer
2.997
276916AD2-100_GEN
Solar/Wind Harmer
10.395
276911AD2-131_GEN
Solar/Wind Harmer
2.101
957381AF2-032 GEN
Solar/Wind Harmer
0.207
960611AF2-352 GEN
Solar/Wind Harmer
1.141
247620Y3-023
Adder
0.225
270216AD2-079_GEN
Solar/Wind Harmer
0.29
274808UNIV PK N;4U
Adder
2.319
274803UNIV PARK;6U
Adder
2.707
274674JOLIET 9 ;6U
Adder
7.123
972259AH1-714 GEN
Adder
8.825
274770LINCOLN ;1U
Adder
3.895
274771LINCOLN ;2U
Adder
3.895
274696ROCKY RD ;4P
Adder
5.21
274695ROCKY RD ;2P
Adder
5.09
274693ROCKY RD ;1P
Adder
5.04
274697ROCKY RD ;3P
Adder
1.383
274683WAUKEGAN ;8U
Adder
9.622
274683WAUKEGAN ;8U
Adder
8.111
274764LEE CO EC;5U
Adder
4.2
274765LEE CO EC;6U
Adder
4.2
252509AD1-136 GEN
Solar/Wind Helper
0.244
25183208HLCRTG
Solar/Wind Helper
2.602
253394AE2-221_GEN
Solar/Wind Helper
1.545
253398AE2-221_GEN2
Solar/Wind Helper
1.545
270186AC1-089 GEN
Solar/Wind Helper
0.823
962581AG1-107 GEN
Solar/Wind Helper
0.942
961491AF2-440 GEN
Solar/Wind Helper
0.039
270518AE2-148 GEN
Solar/Wind Helper
7.331
339221AD2-048_GEN
Solar/Wind Helper
0.779
253378AE2-206_GEN
Solar/Wind Helper
0.65
276820AF1-078_GEN
Solar/Wind Helper
0.303
944201AF1-088_MTX
Adder
57.869
957141AF2-008_MTX
Adder
28.934
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.161
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.286
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.39
MECLTFEXP_MEC->PJM
CLTF
6.961
SIGELTFEXP_SIGE->PJM
CLTF
0.246
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
TVALTFEXP_TVA->PJM
CLTF
1.489
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.516
NYPJM->LTFIMP_NY
CLTF
0.679
WECLTFEXP_WEC->PJM
CLTF
1.72
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.323
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.179

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.08 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2967.55
MW Contribution:16.05
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
8.873
24726605LAWG1S
50/50
8.864
24726705LAWG2A
50/50
5.965
24726505LAWG1B
50/50
5.923
24726805LAWG2B
50/50
5.905
24729505KEY G4
50/50
8.904
270240V3-007_GEN2
Solar/Wind Harmer
15.295
945581AF1-223 GEN
Solar/Wind Harmer
7.477
970115AG2-085 GEN
Solar/Wind Harmer
6.438
965101AG1-375 GEN
Solar/Wind Harmer
15.348
958711AF2-162 GEN
Solar/Wind Harmer
1.492
24725505WLD G2 C
Solar/Wind Harmer
5.718
24699105WLD G1 C
Solar/Wind Harmer
5.651
270594AE1-207 GEN
Solar/Wind Harmer
19.374
961761AG1-017 GEN
Solar/Wind Harmer
0.535
944031AF1-071 GEN
Solar/Wind Harmer
1.234
965461AG1-414 GEN
Solar/Wind Harmer
2.728
970289AG2-191 GEN
Solar/Wind Harmer
2.286
270543AE2-219 C
Solar/Wind Harmer
6.069
971029AG2-637 GEN
Solar/Wind Harmer
17.299
971673AH1-337 GEN
Solar/Wind Harmer
5.229
270024AE2-089 GEN
Solar/Wind Harmer
5.064
963791AG1-232 GEN
Solar/Wind Harmer
10.819
270071AF1-092 GEN
Solar/Wind Harmer
10.537
963841AG1-237 GEN
Solar/Wind Harmer
6.094
24386205FR-12G C
Solar/Wind Harmer
2.276
24386405FR-21G C
Solar/Wind Harmer
2.284
24386605FR-22G C
Solar/Wind Harmer
2.284
24387005FR-3G C
Solar/Wind Harmer
2.101
24690905MDL-1G C
Solar/Wind Harmer
4.071
270180AB1-006 GEN1
Solar/Wind Harmer
3.646
946581AF1-322 GEN
Solar/Wind Harmer
5.187
24691005MDL-2G C
Solar/Wind Harmer
1.875
24697605MDL-3G C
Solar/Wind Harmer
1.869
24697905MDL-4G C
Solar/Wind Harmer
1.164
270181AB1-006 GEN2
Solar/Wind Harmer
0.363
276785W4-005 GEN1
Solar/Wind Harmer
1.513
276174W4-005 GEN2
Solar/Wind Harmer
1.513
276849AB2-070 GEN2
Solar/Wind Harmer
1.124
276848AB2-070 GEN3
Solar/Wind Harmer
1.124
944221AF1-090 GEN
Solar/Wind Harmer
5.422
276655WTG1_EQ
Solar/Wind Harmer
4.275
276656WTG2_EQ
Solar/Wind Harmer
0.566
959341AF2-225 GEN
Solar/Wind Harmer
7.344
941731AE2-173 GEN
Solar/Wind Harmer
2.847
958391AF2-133 GEN
Solar/Wind Harmer
4.419
270536AF1-215 GEN2
Solar/Wind Harmer
2.186
970169AG2-114 GEN
Solar/Wind Harmer
4.799
274863CRW1-WTG
Solar/Wind Harmer
2.666
274864CRW2-WTG
Solar/Wind Harmer
2.666
965041AG1-368 GEN
Solar/Wind Harmer
4.759
274814UNIV PK N;0U
Adder
2.35
274807UNIV PK N;3U
Adder
2.345
274805UNIV PK N;1U
Adder
2.335
274811UNIV PK N;7U
Adder
2.33
972227AH1-698 GEN1
Adder
1.212
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.597
274731ELWOOD EC;2P
Adder
7.617
274733ELWOOD EC;3P
Adder
7.617
274735ELWOOD EC;4P
Adder
7.617
274728ELWOOD EC;5P
Adder
7.617
274687WILL CNTY;4U
Adder
12.918
274687WILL CNTY;4U
Adder
12.918
274675JOLIET 29;7U
Adder
14.173
274675JOLIET 29;7U
Adder
13.667
274775LINCOLN ;6U
Adder
3.895
274776LINCOLN ;7U
Adder
3.895
274777LINCOLN ;8U
Adder
3.895
274746AC1-111 G10
Adder
2.566
274744AC1-111 GEN8
Adder
2.566
274823ROCKFORD ;21
Adder
8.809
252524AE2-267 GEN
Solar/Wind Helper
0.835
270367AC2-061_GEN
Solar/Wind Helper
1.885
241972AD1-140 GEN
Solar/Wind Helper
2.815
270340AC2-060 GEN
Solar/Wind Helper
1.185
339243AC2-075 GEN1
Solar/Wind Helper
0.22
945631AF1-228 GEN
Solar/Wind Helper
0.936
964351AG1-297 GEN
50/50
22.593
961161AF2-407 GEN
50/50
55.693
24728705AND G3
50/50
11.013
24728505AND G1
50/50
5.266
270437AC2-090 C
Solar/Wind Harmer
13.802
270356AE2-297 GEN
Solar/Wind Harmer
10.957
958821AF2-173 GEN
Solar/Wind Harmer
26.801
270004AE1-209 GEN
Solar/Wind Harmer
10.462
946031AF1-268 GEN
Solar/Wind Harmer
13.344
962031AG1-047 GEN
Solar/Wind Harmer
3.781
957741AF2-068 GEN
Solar/Wind Harmer
18.765
270222AC2-111 GEN
Solar/Wind Harmer
10.014
944531AF1-118 GEN
Solar/Wind Harmer
42.975
970289AG2-191 GEN
Solar/Wind Harmer
0.923
970291AG2-192 GEN
Solar/Wind Harmer
0.839
247642Z2-115 C
Solar/Wind Harmer
0.07
971617AH1-308 GEN
Solar/Wind Harmer
6.273
970193AG2-126 GEN
Solar/Wind Harmer
9.994
270043AE2-236 GEN
Solar/Wind Harmer
3.487
959331AF2-224 GEN
Solar/Wind Harmer
5.374
965021AG1-366 GEN
Solar/Wind Harmer
1.25
970031AG2-029 GEN
Solar/Wind Harmer
16.051
24755605MDL-5G
Solar/Wind Harmer
1.223
970781AG2-491 GEN
Solar/Wind Harmer
5.069
276686W4-005 GEN3
Solar/Wind Harmer
1.513
971993AH1-541 GEN
Solar/Wind Harmer
4.621
276668AB2-070 GEN1
Solar/Wind Harmer
1.124
276621W2-048 GEN
Solar/Wind Harmer
3.106
276838X2-022 GEN2
Solar/Wind Harmer
0.116
942481AE2-261 GEN
Solar/Wind Harmer
14.791
274853TWINGROVE;U1
Solar/Wind Harmer
3.535
965091AG1-374 GEN
Solar/Wind Harmer
14.716
959611AF2-252 GEN
Solar/Wind Harmer
1.141
942111AE2-223 GEN
Solar/Wind Harmer
4.014
959141AF2-205 GEN
Solar/Wind Harmer
2.954
964401AG1-302 GEN
Solar/Wind Harmer
4.4
270535AF1-215 GEN1
Solar/Wind Harmer
2.186
247643Z2-116 C
Solar/Wind Harmer
0.033
274752CRETE EC ;2U
Adder
3.842
274753CRETE EC ;3U
Adder
3.842
274724RIVER EC ;11
Adder
8.239
24642205MAYFLWER
Adder
0.295
972228AH1-698 GEN2
Adder
1.721
274802UNIV PARK;5U
Adder
2.707
274800UNIV PARK;3U
Adder
2.705
972038AH1-567 GEN2
Adder
0.169
274826FISK ;BP
Adder
5.075
274729ELWOOD EC;1P
Adder
7.617
274730ELWOOD EC;6P
Adder
7.617
274734ELWOOD EC;8P
Adder
7.617
274736ELWOOD EC;9P
Adder
7.617
274676JOLIET 29;8U
Adder
13.667
274772LINCOLN ;3U
Adder
3.895
274682WAUKEGAN ;7U
Adder
8.211
972236AH1-702 GEN2
Adder
0.99
274760LEE CO EC;1U
Adder
4.19
252510AF1-249 C
Solar/Wind Helper
0.565
253406AD2-031_GEN
Solar/Wind Helper
0.857
253415AE1-040 GEN
Solar/Wind Helper
0.538
253338AC1-165 GEN
Solar/Wind Helper
0.547
253333AC1-068 GEN
Solar/Wind Helper
0.567
24729405KEY G3
50/50
0.486
24729305KEY G2
50/50
0.478
24729205KEY G1
50/50
0.475
247621Y3-024
50/50
0.306
24728805RICHG1
50/50
4.511
24728905RICHG2
50/50
4.511
24379505HDWTR1G C
Solar/Wind Harmer
19.548
270209AC1-174_GEN
Solar/Wind Harmer
13.796
926881AC1-175 GEN
Solar/Wind Harmer
13.796
970825AG2-519 GEN
Solar/Wind Harmer
17.311
960441AF2-335 GEN
Solar/Wind Harmer
16.096
270383AD1-128 GEN
Solar/Wind Harmer
9.53
944541AF1-119 GEN
Solar/Wind Harmer
6.179
960971AF2-388 GEN
Solar/Wind Harmer
16.125
270599AE1-208 GEN
Solar/Wind Harmer
11.727
270031AE2-169
Solar/Wind Harmer
11.727
964611AG1-324 GEN
Solar/Wind Harmer
1.564
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
6.431
970883AG2-550 GEN
Solar/Wind Harmer
11.853
970885AG2-551 GEN
Solar/Wind Harmer
2.757
942221AE2-234 GEN
Solar/Wind Harmer
0.776
945391AF1-204 GEN
Solar/Wind Harmer
9.285
970241AG2-163 GEN
Solar/Wind Harmer
14.556
970611AG2-400 GEN
Solar/Wind Harmer
5.374
966841AG1-555 GEN
Solar/Wind Harmer
1.332
276763AC1-053 GEN1
Solar/Wind Harmer
1.974
276764AC1-053 GEN2
Solar/Wind Harmer
1.974
270444AC2-157 GEN1
Solar/Wind Harmer
2.779
945421AF1-207 GEN
Solar/Wind Harmer
6.965
957841AF2-078 GEN
Solar/Wind Harmer
2.997
276916AD2-100_GEN
Solar/Wind Harmer
10.395
276911AD2-131_GEN
Solar/Wind Harmer
2.101
957381AF2-032 GEN
Solar/Wind Harmer
0.207
960611AF2-352 GEN
Solar/Wind Harmer
1.141
247620Y3-023
Adder
0.225
270216AD2-079_GEN
Solar/Wind Harmer
0.29
274808UNIV PK N;4U
Adder
2.319
274803UNIV PARK;6U
Adder
2.707
274674JOLIET 9 ;6U
Adder
7.123
972259AH1-714 GEN
Adder
8.825
274770LINCOLN ;1U
Adder
3.895
274771LINCOLN ;2U
Adder
3.895
274696ROCKY RD ;4P
Adder
5.21
274695ROCKY RD ;2P
Adder
5.09
274693ROCKY RD ;1P
Adder
5.04
274697ROCKY RD ;3P
Adder
1.383
274683WAUKEGAN ;8U
Adder
9.622
274683WAUKEGAN ;8U
Adder
8.111
274764LEE CO EC;5U
Adder
4.2
274765LEE CO EC;6U
Adder
4.2
252509AD1-136 GEN
Solar/Wind Helper
0.244
25183208HLCRTG
Solar/Wind Helper
2.602
253394AE2-221_GEN
Solar/Wind Helper
1.545
253398AE2-221_GEN2
Solar/Wind Helper
1.545
270186AC1-089 GEN
Solar/Wind Helper
0.823
962581AG1-107 GEN
Solar/Wind Helper
0.942
961491AF2-440 GEN
Solar/Wind Helper
0.039
270518AE2-148 GEN
Solar/Wind Helper
7.331
339221AD2-048_GEN
Solar/Wind Helper
0.779
253378AE2-206_GEN
Solar/Wind Helper
0.65
276820AF1-078_GEN
Solar/Wind Helper
0.303
24726405LAWG1A
50/50
5.74
960791AF2-370 GEN
50/50
3.743
961171AF2-408 GEN
50/50
15.013
24728605AND G2
50/50
5.266
942081AE2-220 GEN
Solar/Wind Harmer
15.805
270239V3-007_GEN1
Solar/Wind Harmer
4.254
270005AE1-210 C O1
Solar/Wind Harmer
10.462
965031AG1-367 GEN
Solar/Wind Harmer
19.144
945371AF1-202 GEN
Solar/Wind Harmer
11.502
970825AG2-519 GEN
Solar/Wind Harmer
3.863
958861AF2-177 GEN
Solar/Wind Harmer
16.776
965651AG1-433 GEN
Solar/Wind Harmer
8.063
276903AD2-071 C
Solar/Wind Harmer
13.602
270032AE2-172
Solar/Wind Harmer
6.131
247536S-71 GEN
Solar/Wind Harmer
4.887
970291AG2-192 GEN
Solar/Wind Harmer
1.564
963741AG1-226 GEN
Solar/Wind Harmer
26.2
965011AG1-365 GEN
Solar/Wind Harmer
5.374
24385905FR-11G C
Solar/Wind Harmer
4.414
24387305FR-4G C
Solar/Wind Harmer
2.699
270063AE2-323 C
Solar/Wind Harmer
1.127
24791305MDL-5G
Solar/Wind Harmer
1.223
274880W4-005 GEN4
Solar/Wind Harmer
1.513
963831AG1-236 GEN
Solar/Wind Harmer
4.91
270445AC2-157 GEN2
Solar/Wind Harmer
2.779
276615X2-022 GEN
Solar/Wind Harmer
0.975
972175AH1-670 GEN
Solar/Wind Harmer
6.772
965911AG1-460 GEN
Solar/Wind Harmer
0.69
940581AE2-045 GEN
Solar/Wind Harmer
5.003
971605AH1-302 GEN
Solar/Wind Harmer
4.278
274854TWINGROVE;U2
Solar/Wind Harmer
3.461
276726Z2-087_GEN
Solar/Wind Harmer
3.873
939741AE1-205 GEN
Solar/Wind Harmer
9.793
964861AG1-349 GEN
Solar/Wind Harmer
3.816
971917AH1-482 GEN
Solar/Wind Harmer
4.403
958381AF2-132 GEN
Solar/Wind Harmer
4.4
24639705ELKHART HY
Adder
0.074
270055AF2-134 C O1
Solar/Wind Harmer
1.457
970373AG2-245 GEN
Solar/Wind Harmer
10.009
274751CRETE EC ;1U
Adder
3.842
274754CRETE EC ;4U
Adder
3.842
274723RIVER EC ;12
Adder
8.339
274812UNIV PK N;8U
Adder
2.33
274801UNIV PARK;4U
Adder
2.705
274732ELWOOD EC;7P
Adder
7.617
274674JOLIET 9 ;6U
Adder
7.123
274676JOLIET 29;8U
Adder
14.173
274773LINCOLN ;4U
Adder
3.895
274774LINCOLN ;5U
Adder
3.895
274745AC1-111 GEN9
Adder
2.566
274682WAUKEGAN ;7U
Adder
8.211
274828WAUKEGAN ;BP
Adder
5.044
274822ROCKFORD ;11
Adder
8.874
972235AH1-702 GEN1
Adder
1.139
274761LEE CO EC;2U
Adder
1.231
252507AC2-088 GEN
Solar/Wind Helper
1.706
339216AC1-074 GEN
Solar/Wind Helper
0.957
253343AC1-166 GEN
Solar/Wind Helper
0.547
253325AC1-069 GEN
Solar/Wind Helper
0.567
943111AE2-339 GEN
Solar/Wind Helper
0.361
939401AE1-172 GEN
Solar/Wind Harmer
4.626
944201AF1-088_MTX
Adder
57.869
957141AF2-008_MTX
Adder
28.934
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.161
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.286
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.39
MECLTFEXP_MEC->PJM
CLTF
6.961
SIGELTFEXP_SIGE->PJM
CLTF
0.246
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
TVALTFEXP_TVA->PJM
CLTF
1.489
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.516
NYPJM->LTFIMP_NY
CLTF
0.679
WECLTFEXP_WEC->PJM
CLTF
1.72
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.323
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.179

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.23 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2739.4
MW Contribution:2.15
Bus #Bus NameTypeMW Contribution
24726405LAWG1A
50/50
3.336
961171AF2-408 GEN
50/50
9.412
960791AF2-370 GEN
50/50
2.332
24728605AND G2
50/50
3.373
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.702
970773AG2-487 GEN
Solar/Wind Harmer
1.765
270005AE1-210 C O1
Solar/Wind Harmer
1.806
965031AG1-367 GEN
Solar/Wind Harmer
8.337
945371AF1-202 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
2.512
958861AF2-177 GEN
Solar/Wind Harmer
3.038
965651AG1-433 GEN
Solar/Wind Harmer
1.996
276903AD2-071 C
Solar/Wind Harmer
7.007
270032AE2-172
Solar/Wind Harmer
4.078
970291AG2-192 GEN
Solar/Wind Harmer
0.75
247536S-71 GEN
Solar/Wind Harmer
0.183
963741AG1-226 GEN
Solar/Wind Harmer
9.071
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.442
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.575
958381AF2-132 GEN
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
1.517
270055AF2-134 C O1
Solar/Wind Harmer
0.003
970373AG2-245 GEN
Solar/Wind Harmer
7.265
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.835
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.8
963831AG1-236 GEN
Solar/Wind Harmer
1.336
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
276615X2-022 GEN
Solar/Wind Harmer
0.036
939401AE1-172 GEN
Solar/Wind Harmer
2.544
274773LINCOLN ;4U
Adder
4.104
274774LINCOLN ;5U
Adder
4.104
941551AE2-152 GEN
Solar/Wind Harmer
0
964351AG1-297 GEN
50/50
13.747
961161AF2-407 GEN
50/50
35.482
24728705AND G3
50/50
7.054
24728505AND G1
50/50
3.373
270437AC2-090 C
Solar/Wind Harmer
0.005
270356AE2-297 GEN
Solar/Wind Harmer
0.013
958821AF2-173 GEN
Solar/Wind Harmer
11.671
270004AE1-209 GEN
Solar/Wind Harmer
1.806
946031AF1-268 GEN
Solar/Wind Harmer
6.483
944531AF1-118 GEN
Solar/Wind Harmer
26.617
970289AG2-191 GEN
Solar/Wind Harmer
0.635
970291AG2-192 GEN
Solar/Wind Harmer
0.577
247642Z2-115 C
Solar/Wind Harmer
0.002
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.517
971617AH1-308 GEN
Solar/Wind Harmer
3.776
970193AG2-126 GEN
Solar/Wind Harmer
6.096
270043AE2-236 GEN
Solar/Wind Harmer
2.401
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.622
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970513AG2-328 GEN
Solar/Wind Harmer
1.517
970517AG2-330 GEN
Solar/Wind Harmer
9.105
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.587
276668AB2-070 GEN1
Solar/Wind Harmer
0.125
942111AE2-223 GEN
Solar/Wind Harmer
1.114
970349AG2-230 GEN
Solar/Wind Harmer
5.141
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.269
959611AF2-252 GEN
Solar/Wind Harmer
1.141
276621W2-048 GEN
Solar/Wind Harmer
0.172
276838X2-022 GEN2
Solar/Wind Harmer
0.192
274772LINCOLN ;3U
Adder
4.104
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
942481AE2-261 GEN
Solar/Wind Harmer
10.124
274724RIVER EC ;11
Adder
8.577
972228AH1-698 GEN2
Adder
1.794
276806AD2-047 C O1
Solar/Wind Harmer
1.914
970941AG2-585 GEN
Solar/Wind Harmer
4.222
274752CRETE EC ;2U
Adder
3.99
274753CRETE EC ;3U
Adder
3.99
274802UNIV PARK;5U
Adder
2.819
274800UNIV PARK;3U
Adder
2.818
972038AH1-567 GEN2
Adder
0.176
274826FISK ;BP
Adder
5.288
970707AG2-453 GEN
Solar/Wind Harmer
11.009
276893AG1-478 C
Solar/Wind Harmer
0.133
274729ELWOOD EC;1P
Adder
7.93
274730ELWOOD EC;6P
Adder
7.929
274734ELWOOD EC;8P
Adder
7.929
274736ELWOOD EC;9P
Adder
7.929
274676JOLIET 29;8U
Adder
14.249
276694AA1-018 GEN2
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
5.605
943591AF1-030 GEN
Solar/Wind Harmer
3.727
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.644
274682WAUKEGAN ;7U
Adder
8.557
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.153
274872LEEDK;1U
Solar/Wind Harmer
0.121
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.352
274855GSG-6 ;RU
Solar/Wind Harmer
0.121
274850MENDOTA H;RU
Solar/Wind Harmer
0.039
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.059
274878BISHOP HL;2U
Solar/Wind Harmer
0.111
959091AF2-200 GEN
Solar/Wind Harmer
6.576
276157O29GEN1
Solar/Wind Harmer
0.527
965911AG1-460 GEN
Solar/Wind Harmer
0.677
274723RIVER EC ;12
Adder
8.679
276776AD2-060 GEN
Solar/Wind Harmer
0.353
274751CRETE EC ;1U
Adder
3.99
274754CRETE EC ;4U
Adder
3.99
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.423
274801UNIV PARK;4U
Adder
2.818
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.929
274674JOLIET 9 ;6U
Adder
7.422
274676JOLIET 29;8U
Adder
14.777
276901AD2-066 C O1
Solar/Wind Harmer
0.003
276691AA1-018 GEN1
Solar/Wind Harmer
0.406
971997AH1-543 GEN
Solar/Wind Harmer
1.755
274745AC1-111 GEN9
Adder
2.679
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
970569AG2-363 GEN
Solar/Wind Harmer
9.966
274682WAUKEGAN ;7U
Adder
8.557
274828WAUKEGAN ;BP
Adder
5.256
962781AG1-127 GEN
Solar/Wind Harmer
3.152
274872LEEDK;1U
Solar/Wind Harmer
0.002
970091AG2-072 GEN
Adder
34.24
276861AD2-134 GEN
Solar/Wind Harmer
0.059
274877BISHOP HL;1U
Solar/Wind Harmer
0.111
957471AF2-041 GEN
Solar/Wind Harmer
9.864
959081AF2-199 GEN
Solar/Wind Harmer
3.288
971067AG2-660 GEN
Solar/Wind Harmer
1.096
970819AG2-516 GEN
Solar/Wind Harmer
3.925
971475AH1-234 GEN
Solar/Wind Harmer
1.584
276158O29GEN2
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
3.407
945111AF1-176 GEN
Solar/Wind Harmer
5.786
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.673
970333AG2-219 GEN
Solar/Wind Harmer
2.279
252507AC2-088 GEN
Solar/Wind Helper
1.361
253343AC1-166 GEN
Solar/Wind Helper
0.58
253325AC1-069 GEN
Solar/Wind Helper
0.601
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
2.628
965931AG1-462 GEN
Solar/Wind Harmer
8.158
270222AC2-111 GEN
Solar/Wind Harmer
1.616
970243AG2-164 GEN
Solar/Wind Harmer
1.864
970519AG2-331 GEN
Solar/Wind Harmer
8.287
970699AG2-449 GEN
Solar/Wind Harmer
0.797
24441205WTRV SLR C
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Helper
0.648
253406AD2-031_GEN
Solar/Wind Helper
0.903
253415AE1-040 GEN
Solar/Wind Helper
0.547
253338AC1-165 GEN
Solar/Wind Helper
0.58
253333AC1-068 GEN
Solar/Wind Helper
0.601
241974AD2-163_GEN2
Solar/Wind Helper
1.018
241955AC1-078 GEN
Solar/Wind Helper
0.969
25194708EBND2
50/50
6.266
24729405KEY G3
50/50
0.332
24729305KEY G2
50/50
0.327
24729205KEY G1
50/50
0.325
247621Y3-024
50/50
0.169
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.843
960441AF2-335 GEN
Solar/Wind Harmer
6.997
944541AF1-119 GEN
Solar/Wind Harmer
0.456
960971AF2-388 GEN
Solar/Wind Harmer
3.991
270599AE1-208 GEN
Solar/Wind Harmer
5.883
270031AE2-169
Solar/Wind Harmer
3.53
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
2.936
964611AG1-324 GEN
Solar/Wind Harmer
0.405
270201AC2-176 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.024
970883AG2-550 GEN
Solar/Wind Harmer
4.232
970885AG2-551 GEN
Solar/Wind Harmer
1.411
945391AF1-204 GEN
Solar/Wind Harmer
4.318
970241AG2-163 GEN
Solar/Wind Harmer
2.236
966841AG1-555 GEN
Solar/Wind Harmer
0.418
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.691
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970321AG2-212 GEN
Solar/Wind Harmer
1.517
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.141
274770LINCOLN ;1U
Adder
4.104
274771LINCOLN ;2U
Adder
4.104
276916AD2-100_GEN
Solar/Wind Harmer
7.107
276911AD2-131_GEN
Solar/Wind Harmer
0.468
965681AG1-436 GEN
Solar/Wind Harmer
4.229
965791AG1-447 GEN
Solar/Wind Harmer
3.101
274888KELLY CRK;1U
Solar/Wind Harmer
0.198
274887GEN-1.85
Solar/Wind Harmer
0.089
276843GEN-1.7
Solar/Wind Harmer
0.109
958011AF2-095 GEN
Solar/Wind Harmer
4.864
274808UNIV PK N;4U
Adder
2.412
972259AH1-714 GEN
Adder
9.225
274803UNIV PARK;6U
Adder
2.819
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
7.422
24728805RICHG1
Adder
1.818
24728905RICHG2
Adder
1.818
958481AF2-142 GEN
Solar/Wind Harmer
5.024
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.453
958491AF2-143 GEN
Solar/Wind Harmer
5.012
24441505OLIV SLR
Solar/Wind Harmer
0
274879MINONK ;1U
Solar/Wind Harmer
0.141
270526AF1-158 GEN
Solar/Wind Harmer
0.004
971573AH1-285 GEN
Solar/Wind Harmer
0.621
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274696ROCKY RD ;4P
Adder
5.432
274695ROCKY RD ;2P
Adder
5.307
274693ROCKY RD ;1P
Adder
5.255
274697ROCKY RD ;3P
Adder
1.442
274683WAUKEGAN ;8U
Adder
10.027
274683WAUKEGAN ;8U
Adder
8.452
962691AG1-118 GEN
Solar/Wind Harmer
9.946
970921AG2-575 GEN
Solar/Wind Harmer
3.312
970921AG2-575 GEN
Solar/Wind Harmer
1.104
270216AD2-079_GEN
Solar/Wind Harmer
0
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.13
276646AC1-214 GEN2
Solar/Wind Harmer
0.13
942991AE2-321 GEN
Solar/Wind Harmer
3.685
276782AC1-033 GEN
Solar/Wind Harmer
0
971333AH1-146 GEN
Solar/Wind Harmer
6.586
971335AH1-147 GEN
Solar/Wind Harmer
6.586
971341AH1-150 GEN
Solar/Wind Harmer
6.576
971343AH1-151 GEN
Solar/Wind Harmer
6.576
274856ECOGROVE ;U1
Solar/Wind Harmer
0.077
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.85
276741O09 GEN1
Solar/Wind Harmer
0.116
276708O09 GEN2
Solar/Wind Harmer
0.116
276603SUBLETTE C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
6.438
961051AF2-396 GEN
Solar/Wind Harmer
4.292
970239AG2-162 GEN
Solar/Wind Harmer
0.797
25183208HLCRTG
Solar/Wind Helper
2.467
252509AD1-136 GEN
Solar/Wind Helper
0.194
253394AE2-221_GEN
Solar/Wind Helper
1.592
253398AE2-221_GEN2
Solar/Wind Helper
1.592
253378AE2-206_GEN
Solar/Wind Helper
0.968
276820AF1-078_GEN
Solar/Wind Helper
0.452
962581AG1-107 GEN
Solar/Wind Helper
1.007
961491AF2-440 GEN
Solar/Wind Helper
0.041
270186AC1-089 GEN
Solar/Wind Helper
0.814
270518AE2-148 GEN
Solar/Wind Helper
8.413
24726905LAWG2S
50/50
5.157
24726605LAWG1S
50/50
5.152
24726705LAWG2A
50/50
3.467
24726505LAWG1B
50/50
3.443
24726805LAWG2B
50/50
3.432
24729505KEY G4
50/50
6.086
270240V3-007_GEN2
Solar/Wind Harmer
0.003
945581AF1-223 GEN
Solar/Wind Harmer
0.001
965101AG1-375 GEN
Solar/Wind Harmer
7.011
970115AG2-085 GEN
Solar/Wind Harmer
2.799
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.048
270594AE1-207 GEN
Solar/Wind Harmer
6.851
970289AG2-191 GEN
Solar/Wind Harmer
1.096
270024AE2-089 GEN
Solar/Wind Harmer
0.005
270543AE2-219 C
Solar/Wind Harmer
0.003
270071AF1-092 GEN
Solar/Wind Harmer
7.808
971029AG2-637 GEN
Solar/Wind Harmer
5.775
963841AG1-237 GEN
Solar/Wind Harmer
1.631
963791AG1-232 GEN
Solar/Wind Harmer
5.031
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
971673AH1-337 GEN
Solar/Wind Harmer
2.397
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.115
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.125
276848AB2-070 GEN3
Solar/Wind Harmer
0.125
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.6
941731AE2-173 GEN
Solar/Wind Harmer
2.857
971347AH1-153 GEN
Solar/Wind Harmer
5.141
970169AG2-114 GEN
Solar/Wind Harmer
3.406
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274775LINCOLN ;6U
Adder
4.104
274776LINCOLN ;7U
Adder
4.104
274777LINCOLN ;8U
Adder
4.104
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
972227AH1-698 GEN1
Adder
1.263
944221AF1-090 GEN
Solar/Wind Harmer
1.982
960591AF2-350 GEN
Solar/Wind Harmer
3.378
274814UNIV PK N;0U
Adder
2.444
274807UNIV PK N;3U
Adder
2.439
274805UNIV PK N;1U
Adder
2.428
274811UNIV PK N;7U
Adder
2.423
972037AH1-567 GEN1
Adder
0.088
274827FISK ;RP
Adder
3.748
970833AG2-524 GEN
Solar/Wind Harmer
3.704
970833AG2-524 GEN
Solar/Wind Harmer
2.47
274731ELWOOD EC;2P
Adder
7.93
274733ELWOOD EC;3P
Adder
7.93
274735ELWOOD EC;4P
Adder
7.93
274728ELWOOD EC;5P
Adder
7.929
274687WILL CNTY;4U
Adder
13.464
274687WILL CNTY;4U
Adder
13.464
274675JOLIET 29;7U
Adder
14.777
274675JOLIET 29;7U
Adder
14.249
274746AC1-111 G10
Adder
2.679
274744AC1-111 GEN8
Adder
2.679
971769AH1-391 GEN
Solar/Wind Harmer
3.73
276868AE1-113 GEN
Solar/Wind Harmer
0.67
276882AE2-255 GEN
Solar/Wind Harmer
0.39
926823AC1-168 GEN
Solar/Wind Harmer
0.566
971771AH1-392 GEN
Solar/Wind Harmer
3.324
957751AF2-069 GEN
Solar/Wind Harmer
0.109
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
2.035
971675AH1-338 GEN
Solar/Wind Harmer
1.286
971411AH1-196 GEN
Solar/Wind Harmer
4.94
971171AH1-044 GEN
Solar/Wind Harmer
6.576
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.259
961011AF2-392 GEN
Solar/Wind Harmer
1.909
971619AH1-309 GEN
Solar/Wind Harmer
1.46
946321AF1-296 GEN
Solar/Wind Harmer
1.796
252524AE2-267 GEN
Solar/Wind Helper
1.054
241972AD1-140 GEN
Solar/Wind Helper
3.429
270367AC2-061_GEN
Solar/Wind Helper
1.955
253383AE2-342_GEN
Solar/Wind Helper
0.463
270340AC2-060 GEN
Solar/Wind Helper
1.177
945631AF1-228 GEN
Solar/Wind Helper
1.077
241973AD2-163_GEN1
Solar/Wind Helper
1.018
944201AF1-088_MTX
Adder
61.158
957141AF2-008_MTX
Adder
30.579
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.258
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.271
MECLTFEXP_MEC->PJM
CLTF
7.181
SIGELTFEXP_SIGE->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
4.763
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.507
TVALTFEXP_TVA->PJM
CLTF
1.913
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.453
NYPJM->LTFIMP_NY
CLTF
0.653
LGEELTFEXP_LGEE->PJM
CLTF
1.404
WECLTFEXP_WEC->PJM
CLTF
1.789
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.177

Details for 18MOROCCO-02ALLEN 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-034T_SRT-A


Base Case Flowgate

Area:ATSI/METC
Facility Description:
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-034T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.58 %
Rating:1793.0 MVA
Rating Type:B
MVA to Mitigate:1946.81
MW Contribution:15.55
Bus #Bus NameTypeMW Contribution
961051AF2-396 GEN
Solar/Wind Harmer
11.459
961051AF2-396 GEN
Solar/Wind Harmer
5.33
957891AF2-083 GEN
Solar/Wind Harmer
2.349
960981AF2-389 GEN
Solar/Wind Harmer
1.053
270216AD2-079_GEN
Solar/Wind Harmer
0.38
270526AF1-158 GEN
Solar/Wind Harmer
2.808
24441505OLIV SLR
Solar/Wind Harmer
0.082
247620Y3-023
Adder
0.274
965681AG1-436 GEN
Solar/Wind Harmer
7.212
965791AG1-447 GEN
Solar/Wind Harmer
3.69
274808UNIV PK N;4U
Adder
2.483
274803UNIV PARK;6U
Adder
2.854
274888KELLY CRK;1U
Solar/Wind Harmer
2.866
274887GEN-1.85
Solar/Wind Harmer
2.588
276843GEN-1.7
Solar/Wind Harmer
0.278
958011AF2-095 GEN
Solar/Wind Harmer
6.991
274770LINCOLN ;1U
Adder
2.999
274771LINCOLN ;2U
Adder
2.999
972259AH1-714 GEN
Adder
9.154
274674JOLIET 9 ;6U
Adder
7.368
274847GR RIDGE ;BU
Solar/Wind Harmer
2.399
958481AF2-142 GEN
Solar/Wind Harmer
7.06
274861TOP CROP ;1U
Solar/Wind Harmer
2.852
274862TOP CROP ;2U
Solar/Wind Harmer
2.382
971573AH1-285 GEN
Solar/Wind Harmer
4.028
274696ROCKY RD ;4P
Adder
5.317
274695ROCKY RD ;2P
Adder
5.195
274693ROCKY RD ;1P
Adder
5.144
274697ROCKY RD ;3P
Adder
1.411
274683WAUKEGAN ;8U
Adder
9.828
274683WAUKEGAN ;8U
Adder
8.285
958491AF2-143 GEN
Solar/Wind Harmer
6.97
970321AG2-212 GEN
Solar/Wind Harmer
8.295
962691AG1-118 GEN
Solar/Wind Harmer
13.883
970921AG2-575 GEN
Solar/Wind Harmer
4.617
970921AG2-575 GEN
Solar/Wind Harmer
1.074
274879MINONK ;1U
Solar/Wind Harmer
3.113
942991AE2-321 GEN
Solar/Wind Harmer
4.594
971333AH1-146 GEN
Solar/Wind Harmer
9.139
971335AH1-147 GEN
Solar/Wind Harmer
9.139
247604X1-042
Adder
0.358
24441205WTRV SLR C
Solar/Wind Harmer
0.11
945111AF1-176 GEN
Solar/Wind Harmer
3.927
24642205MAYFLWER
Adder
0.425
247643Z2-116 C
Solar/Wind Harmer
0.044
970349AG2-230 GEN
Solar/Wind Harmer
8.425
270535AF1-215 GEN1
Solar/Wind Harmer
2.357
970031AG2-029 GEN
Solar/Wind Harmer
15.546
972231SS25-0005
Solar/Wind Harmer
4.819
972181SS23-001
Solar/Wind Harmer
3.012
274752CRETE EC ;2U
Adder
2.482
274753CRETE EC ;3U
Adder
2.482
964401AG1-302 GEN
Solar/Wind Harmer
4.552
274724RIVER EC ;11
Adder
8.868
274802UNIV PARK;5U
Adder
2.854
274826FISK ;BP
Adder
5.344
274800UNIV PARK;3U
Adder
2.839
972038AH1-567 GEN2
Adder
0.178
959141AF2-205 GEN
Solar/Wind Harmer
2.942
276772AC2-154 GEN
Solar/Wind Harmer
1.354
276806AD2-047 C O1
Solar/Wind Harmer
5.193
970941AG2-585 GEN
Solar/Wind Harmer
6.068
274772LINCOLN ;3U
Adder
2.999
972228AH1-698 GEN2
Adder
1.79
274676JOLIET 29;8U
Adder
14.201
276893AG1-478 C
Solar/Wind Harmer
0.2
274729ELWOOD EC;1P
Adder
7.866
274730ELWOOD EC;6P
Adder
7.866
274734ELWOOD EC;8P
Adder
7.866
274736ELWOOD EC;9P
Adder
7.866
276897AD1-100 C
Solar/Wind Harmer
13.875
939351AE1-166 GEN
Solar/Wind Harmer
2.835
970707AG2-453 GEN
Solar/Wind Harmer
13.377
270449AD2-020 GEN
Solar/Wind Harmer
2.069
943021AE2-325 GEN
Solar/Wind Harmer
2.688
270505AE1-170 C O1
Solar/Wind Harmer
10.556
945111AF1-176 GEN
Solar/Wind Harmer
12.391
24639705ELKHART HY
Adder
0.095
970373AG2-245 GEN
Solar/Wind Harmer
11.296
270055AF2-134 C O1
Solar/Wind Harmer
1.571
274751CRETE EC ;1U
Adder
2.482
274754CRETE EC ;4U
Adder
2.482
958381AF2-132 GEN
Solar/Wind Harmer
4.552
274723RIVER EC ;12
Adder
8.975
964861AG1-349 GEN
Solar/Wind Harmer
3.93
971917AH1-482 GEN
Solar/Wind Harmer
4.536
274812UNIV PK N;8U
Adder
2.494
270063AE2-323 C
Solar/Wind Harmer
1.09
276164X3-005 C
Solar/Wind Harmer
0.347
274801UNIV PARK;4U
Adder
2.839
276776AD2-060 GEN
Solar/Wind Harmer
0.205
972207SS24-0001
Solar/Wind Harmer
10.663
274773LINCOLN ;4U
Adder
2.999
274774LINCOLN ;5U
Adder
2.999
274676JOLIET 29;8U
Adder
14.726
274732ELWOOD EC;7P
Adder
7.866
274674JOLIET 9 ;6U
Adder
7.368
940581AE2-045 GEN
Solar/Wind Harmer
4.88
971605AH1-302 GEN
Solar/Wind Harmer
4.173
941551AE2-152 GEN
Solar/Wind Harmer
2.168
274871GR RIDGE ;2U
Solar/Wind Harmer
3.647
274745AC1-111 GEN9
Adder
2.633
276691AA1-018 GEN1
Solar/Wind Harmer
0.219
274682WAUKEGAN ;7U
Adder
8.393
274828WAUKEGAN ;BP
Adder
5.152
970245AG2-165 GEN
Solar/Wind Harmer
8.295
276901AD2-066 C O1
Solar/Wind Harmer
1.623
960751AF2-366 GEN
Solar/Wind Harmer
1.325
962781AG1-127 GEN
Solar/Wind Harmer
4.391
274872LEEDK;1U
Solar/Wind Harmer
3.784
939401AE1-172 GEN
Solar/Wind Harmer
6.411
971997AH1-543 GEN
Solar/Wind Harmer
7.215
276861AD2-134 GEN
Solar/Wind Harmer
0.816
276876AE1-163_GEN2
Solar/Wind Harmer
3.065
274822ROCKFORD ;11
Adder
8.894
972235AH1-702 GEN1
Adder
1.14
274761LEE CO EC;2U
Adder
4.147
274766LEE CO EC;7U
Adder
4.098
241808AF1-120 C
Solar/Wind Helper
1.428
241840AF1-064_GEN
Solar/Wind Helper
1.322
241807AE2-176_GEN
Solar/Wind Helper
1.436
241885AC2-103 GEN1
Solar/Wind Helper
1.906
960841AF2-375 GEN
Solar/Wind Helper
1.047
957471AF2-041 GEN
Solar/Wind Harmer
6.257
959081AF2-199 GEN
Solar/Wind Harmer
2.086
971067AG2-660 GEN
Solar/Wind Harmer
0.485
276694AA1-018 GEN2
Solar/Wind Harmer
2.97
943121AE2-341 GEN
Solar/Wind Harmer
7.059
943591AF1-030 GEN
Solar/Wind Harmer
4.706
274682WAUKEGAN ;7U
Adder
8.393
276805AD2-038 GEN
Solar/Wind Harmer
2.384
970513AG2-328 GEN
Solar/Wind Harmer
8.295
970517AG2-330 GEN
Solar/Wind Harmer
7.523
274872LEEDK;1U
Solar/Wind Harmer
0.118
276799AD1-013 GEN
Solar/Wind Harmer
1.01
946671AF1-331 GEN
Solar/Wind Harmer
0.191
274855GSG-6 ;RU
Solar/Wind Harmer
1.687
274850MENDOTA H;RU
Solar/Wind Harmer
1.173
276602WESTBROOK C
Solar/Wind Harmer
0.971
276863AD2-134 GEN
Solar/Wind Harmer
0.816
276889AE2-281 GEN
Solar/Wind Harmer
0.876
972236AH1-702 GEN2
Adder
0.991
274760LEE CO EC;1U
Adder
4.147
274767LEE CO EC;8U
Adder
4.098
241832AE2-181_GEN
Solar/Wind Helper
1.096
270541AE2-072 C
Solar/Wind Helper
1.484
959091AF2-200 GEN
Solar/Wind Harmer
4.171
276872AE1-163_GEN1
Solar/Wind Harmer
3.065
945421AF1-207 GEN
Solar/Wind Harmer
6.406
957841AF2-078 GEN
Solar/Wind Harmer
2.757
274764LEE CO EC;5U
Adder
4.157
274765LEE CO EC;6U
Adder
4.157
274762LEE CO EC;3U
Adder
4.147
274763LEE CO EC;4U
Adder
4.108
972267AH1-718 GEN
Adder
1.839
241996AE2-282_GEN
Solar/Wind Helper
2.556
971341AH1-150 GEN
Solar/Wind Harmer
4.171
971343AH1-151 GEN
Solar/Wind Harmer
4.171
971549AH1-272 GEN
Solar/Wind Harmer
20.205
944161AF1-084 GEN
Solar/Wind Harmer
1.682
971771AH1-392 GEN
Solar/Wind Harmer
5.682
971769AH1-391 GEN
Solar/Wind Harmer
6.148
960681AF2-359 GEN
Solar/Wind Harmer
2.18
971347AH1-153 GEN
Solar/Wind Harmer
8.425
270536AF1-215 GEN2
Solar/Wind Harmer
2.357
274814UNIV PK N;0U
Adder
2.516
274807UNIV PK N;3U
Adder
2.51
274805UNIV PK N;1U
Adder
2.5
274811UNIV PK N;7U
Adder
2.494
958391AF2-133 GEN
Solar/Wind Harmer
4.473
972037AH1-567 GEN1
Adder
0.09
274827FISK ;RP
Adder
3.787
960591AF2-350 GEN
Solar/Wind Harmer
4.855
274775LINCOLN ;6U
Adder
2.999
274776LINCOLN ;7U
Adder
2.999
274777LINCOLN ;8U
Adder
2.999
972227AH1-698 GEN1
Adder
1.26
274687WILL CNTY;4U
Adder
13.454
274687WILL CNTY;4U
Adder
13.454
274675JOLIET 29;7U
Adder
14.727
274675JOLIET 29;7U
Adder
14.201
274731ELWOOD EC;2P
Adder
7.866
274733ELWOOD EC;3P
Adder
7.866
274735ELWOOD EC;4P
Adder
7.866
274728ELWOOD EC;5P
Adder
7.866
970833AG2-524 GEN
Solar/Wind Harmer
4.144
970833AG2-524 GEN
Solar/Wind Harmer
1.928
274746AC1-111 G10
Adder
2.633
274744AC1-111 GEN8
Adder
2.633
276868AE1-113 GEN
Solar/Wind Harmer
4.668
276882AE2-255 GEN
Solar/Wind Harmer
1.556
971177AH1-047 GEN
Solar/Wind Harmer
2.691
971411AH1-196 GEN
Solar/Wind Harmer
6.862
971675AH1-338 GEN
Solar/Wind Harmer
8.221
274823ROCKFORD ;21
Adder
8.829
945411AF1-206 GEN
Solar/Wind Helper
4.842
241886AC2-103 GEN2
Solar/Wind Helper
1.906
270499AE1-146 GEN
Solar/Wind Helper
1.599
945641AF1-229 GEN
Solar/Wind Helper
0.873
971171AH1-044 GEN
Solar/Wind Harmer
4.171
991182J1586 G
External Queue
59.18217849731445
991227J1663 G
External Queue
12.7299222946167
990527J1329
External Queue
5.287156105041504
990142J1224
External Queue
38.64910888671875
991177J1571 G
External Queue
62.399627685546875
CBM West 1LTFEXP_CBM-W1->PJM
CBM
149.957
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.099
MECLTFEXP_MEC->PJM
CLTF
6.451
SIGELTFEXP_SIGE->PJM
CLTF
0.132
LAGNLTFEXP_LAGN->PJM
CLTF
4.363
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.93
TVALTFEXP_TVA->PJM
CLTF
1.864
CPLELTFEXP_CPLE->PJM
CLTF
0.396
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.904
NYPJM->LTFIMP_NY
CLTF
0.9
LGEELTFEXP_LGEE->PJM
CLTF
1.381
WECLTFEXP_WEC->PJM
CLTF
1.727
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168

Details for 18MOROCCO-02ALLEN 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-033T_SRT-A


Base Case Flowgate

Area:ATSI/METC
Facility Description:
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-033T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.35 %
Rating:1793.0 MVA
Rating Type:B
MVA to Mitigate:1942.65
MW Contribution:15.29
Bus #Bus NameTypeMW Contribution
971549AH1-272 GEN
Solar/Wind Harmer
20.173
944161AF1-084 GEN
Solar/Wind Harmer
1.671
971771AH1-392 GEN
Solar/Wind Harmer
5.626
971769AH1-391 GEN
Solar/Wind Harmer
6.085
960681AF2-359 GEN
Solar/Wind Harmer
2.155
971347AH1-153 GEN
Solar/Wind Harmer
8.323
270536AF1-215 GEN2
Solar/Wind Harmer
2.325
274814UNIV PK N;0U
Adder
2.48
274807UNIV PK N;3U
Adder
2.475
274805UNIV PK N;1U
Adder
2.464
274811UNIV PK N;7U
Adder
2.459
958391AF2-133 GEN
Solar/Wind Harmer
4.409
972037AH1-567 GEN1
Adder
0.088
961051AF2-396 GEN
Solar/Wind Harmer
11.373
961051AF2-396 GEN
Solar/Wind Harmer
5.29
957891AF2-083 GEN
Solar/Wind Harmer
2.33
960981AF2-389 GEN
Solar/Wind Harmer
1.044
270216AD2-079_GEN
Solar/Wind Harmer
0.376
270526AF1-158 GEN
Solar/Wind Harmer
2.78
24441505OLIV SLR
Solar/Wind Harmer
0.082
247620Y3-023
Adder
0.271
965681AG1-436 GEN
Solar/Wind Harmer
7.13
965791AG1-447 GEN
Solar/Wind Harmer
3.648
274808UNIV PK N;4U
Adder
2.448
274803UNIV PARK;6U
Adder
2.812
274888KELLY CRK;1U
Solar/Wind Harmer
2.824
274887GEN-1.85
Solar/Wind Harmer
2.55
276843GEN-1.7
Solar/Wind Harmer
0.274
958011AF2-095 GEN
Solar/Wind Harmer
6.888
274770LINCOLN ;1U
Adder
2.955
274771LINCOLN ;2U
Adder
2.955
972259AH1-714 GEN
Adder
9.018
274674JOLIET 9 ;6U
Adder
7.258
274847GR RIDGE ;BU
Solar/Wind Harmer
2.363
958481AF2-142 GEN
Solar/Wind Harmer
6.953
274861TOP CROP ;1U
Solar/Wind Harmer
2.809
274862TOP CROP ;2U
Solar/Wind Harmer
2.345
971573AH1-285 GEN
Solar/Wind Harmer
3.967
274696ROCKY RD ;4P
Adder
5.236
274695ROCKY RD ;2P
Adder
5.115
274693ROCKY RD ;1P
Adder
5.065
274697ROCKY RD ;3P
Adder
1.39
274683WAUKEGAN ;8U
Adder
9.678
274683WAUKEGAN ;8U
Adder
8.158
958491AF2-143 GEN
Solar/Wind Harmer
6.863
970321AG2-212 GEN
Solar/Wind Harmer
8.162
962691AG1-118 GEN
Solar/Wind Harmer
13.669
970921AG2-575 GEN
Solar/Wind Harmer
4.546
970921AG2-575 GEN
Solar/Wind Harmer
1.057
274879MINONK ;1U
Solar/Wind Harmer
3.064
942991AE2-321 GEN
Solar/Wind Harmer
4.522
971333AH1-146 GEN
Solar/Wind Harmer
8.996
971335AH1-147 GEN
Solar/Wind Harmer
8.996
276872AE1-163_GEN1
Solar/Wind Harmer
3.017
945421AF1-207 GEN
Solar/Wind Harmer
6.302
957841AF2-078 GEN
Solar/Wind Harmer
2.712
274764LEE CO EC;5U
Adder
4.09
274765LEE CO EC;6U
Adder
4.09
274762LEE CO EC;3U
Adder
4.08
274763LEE CO EC;4U
Adder
4.042
972267AH1-718 GEN
Adder
1.809
241996AE2-282_GEN
Solar/Wind Helper
2.512
971341AH1-150 GEN
Solar/Wind Harmer
4.106
971343AH1-151 GEN
Solar/Wind Harmer
4.106
247604X1-042
Adder
0.356
24441205WTRV SLR C
Solar/Wind Harmer
0.11
945111AF1-176 GEN
Solar/Wind Harmer
3.895
24642205MAYFLWER
Adder
0.421
247643Z2-116 C
Solar/Wind Harmer
0.043
970349AG2-230 GEN
Solar/Wind Harmer
8.323
270535AF1-215 GEN1
Solar/Wind Harmer
2.325
970031AG2-029 GEN
Solar/Wind Harmer
15.287
972231SS25-0005
Solar/Wind Harmer
4.752
972181SS23-001
Solar/Wind Harmer
2.97
274752CRETE EC ;2U
Adder
2.448
274753CRETE EC ;3U
Adder
2.448
964401AG1-302 GEN
Solar/Wind Harmer
4.488
274724RIVER EC ;11
Adder
8.744
274802UNIV PARK;5U
Adder
2.812
274826FISK ;BP
Adder
5.266
274800UNIV PARK;3U
Adder
2.797
972038AH1-567 GEN2
Adder
0.175
959141AF2-205 GEN
Solar/Wind Harmer
2.898
276772AC2-154 GEN
Solar/Wind Harmer
1.334
276806AD2-047 C O1
Solar/Wind Harmer
5.117
970941AG2-585 GEN
Solar/Wind Harmer
5.98
274772LINCOLN ;3U
Adder
2.955
972228AH1-698 GEN2
Adder
1.764
274676JOLIET 29;8U
Adder
13.99
276893AG1-478 C
Solar/Wind Harmer
0.197
274729ELWOOD EC;1P
Adder
7.749
274730ELWOOD EC;6P
Adder
7.749
274734ELWOOD EC;8P
Adder
7.749
274736ELWOOD EC;9P
Adder
7.749
276897AD1-100 C
Solar/Wind Harmer
13.667
939351AE1-166 GEN
Solar/Wind Harmer
2.793
970707AG2-453 GEN
Solar/Wind Harmer
13.177
276694AA1-018 GEN2
Solar/Wind Harmer
2.925
943121AE2-341 GEN
Solar/Wind Harmer
6.952
943591AF1-030 GEN
Solar/Wind Harmer
4.635
274682WAUKEGAN ;7U
Adder
8.265
276805AD2-038 GEN
Solar/Wind Harmer
2.347
970513AG2-328 GEN
Solar/Wind Harmer
8.162
970517AG2-330 GEN
Solar/Wind Harmer
7.403
274872LEEDK;1U
Solar/Wind Harmer
0.116
276799AD1-013 GEN
Solar/Wind Harmer
0.994
946671AF1-331 GEN
Solar/Wind Harmer
0.188
274855GSG-6 ;RU
Solar/Wind Harmer
1.66
274850MENDOTA H;RU
Solar/Wind Harmer
1.154
276602WESTBROOK C
Solar/Wind Harmer
0.956
276863AD2-134 GEN
Solar/Wind Harmer
0.803
276889AE2-281 GEN
Solar/Wind Harmer
0.862
972236AH1-702 GEN2
Adder
0.975
274760LEE CO EC;1U
Adder
4.08
274767LEE CO EC;8U
Adder
4.032
241832AE2-181_GEN
Solar/Wind Helper
1.079
270541AE2-072 C
Solar/Wind Helper
1.503
959091AF2-200 GEN
Solar/Wind Harmer
4.106
274827FISK ;RP
Adder
3.732
960591AF2-350 GEN
Solar/Wind Harmer
4.784
274775LINCOLN ;6U
Adder
2.955
274776LINCOLN ;7U
Adder
2.955
274777LINCOLN ;8U
Adder
2.955
972227AH1-698 GEN1
Adder
1.242
274687WILL CNTY;4U
Adder
13.255
274687WILL CNTY;4U
Adder
13.255
274675JOLIET 29;7U
Adder
14.508
274675JOLIET 29;7U
Adder
13.99
274731ELWOOD EC;2P
Adder
7.749
274733ELWOOD EC;3P
Adder
7.749
274735ELWOOD EC;4P
Adder
7.749
274728ELWOOD EC;5P
Adder
7.749
970833AG2-524 GEN
Solar/Wind Harmer
4.082
970833AG2-524 GEN
Solar/Wind Harmer
1.899
274746AC1-111 G10
Adder
2.593
274744AC1-111 GEN8
Adder
2.593
276868AE1-113 GEN
Solar/Wind Harmer
4.596
276882AE2-255 GEN
Solar/Wind Harmer
1.532
971177AH1-047 GEN
Solar/Wind Harmer
2.649
971411AH1-196 GEN
Solar/Wind Harmer
6.755
971675AH1-338 GEN
Solar/Wind Harmer
8.093
274823ROCKFORD ;21
Adder
8.69
945411AF1-206 GEN
Solar/Wind Helper
4.76
241886AC2-103 GEN2
Solar/Wind Helper
1.76
270499AE1-146 GEN
Solar/Wind Helper
1.702
945641AF1-229 GEN
Solar/Wind Helper
0.975
971171AH1-044 GEN
Solar/Wind Harmer
4.106
270449AD2-020 GEN
Solar/Wind Harmer
2.054
943021AE2-325 GEN
Solar/Wind Harmer
2.669
270505AE1-170 C O1
Solar/Wind Harmer
10.473
945111AF1-176 GEN
Solar/Wind Harmer
12.289
24639705ELKHART HY
Adder
0.094
970373AG2-245 GEN
Solar/Wind Harmer
11.153
270055AF2-134 C O1
Solar/Wind Harmer
1.55
274751CRETE EC ;1U
Adder
2.448
274754CRETE EC ;4U
Adder
2.448
958381AF2-132 GEN
Solar/Wind Harmer
4.488
274723RIVER EC ;12
Adder
8.849
964861AG1-349 GEN
Solar/Wind Harmer
3.875
971917AH1-482 GEN
Solar/Wind Harmer
4.471
274812UNIV PK N;8U
Adder
2.459
276164X3-005 C
Solar/Wind Harmer
0.342
270063AE2-323 C
Solar/Wind Harmer
1.072
274801UNIV PARK;4U
Adder
2.797
276776AD2-060 GEN
Solar/Wind Harmer
0.202
972207SS24-0001
Solar/Wind Harmer
10.506
274773LINCOLN ;4U
Adder
2.955
274774LINCOLN ;5U
Adder
2.955
274676JOLIET 29;8U
Adder
14.508
274732ELWOOD EC;7P
Adder
7.749
274674JOLIET 9 ;6U
Adder
7.258
940581AE2-045 GEN
Solar/Wind Harmer
4.806
971605AH1-302 GEN
Solar/Wind Harmer
4.11
941551AE2-152 GEN
Solar/Wind Harmer
2.136
274871GR RIDGE ;2U
Solar/Wind Harmer
3.592
274745AC1-111 GEN9
Adder
2.593
276691AA1-018 GEN1
Solar/Wind Harmer
0.216
274682WAUKEGAN ;7U
Adder
8.265
274828WAUKEGAN ;BP
Adder
5.073
970245AG2-165 GEN
Solar/Wind Harmer
8.162
276901AD2-066 C O1
Solar/Wind Harmer
1.598
960751AF2-366 GEN
Solar/Wind Harmer
1.304
962781AG1-127 GEN
Solar/Wind Harmer
4.323
274872LEEDK;1U
Solar/Wind Harmer
3.726
939401AE1-172 GEN
Solar/Wind Harmer
6.31
971997AH1-543 GEN
Solar/Wind Harmer
7.102
276861AD2-134 GEN
Solar/Wind Harmer
0.803
276876AE1-163_GEN2
Solar/Wind Harmer
3.017
274822ROCKFORD ;11
Adder
8.753
972235AH1-702 GEN1
Adder
1.122
274761LEE CO EC;2U
Adder
4.08
274766LEE CO EC;7U
Adder
4.032
241808AF1-120 C
Solar/Wind Helper
1.404
241840AF1-064_GEN
Solar/Wind Helper
1.299
241807AE2-176_GEN
Solar/Wind Helper
1.359
241885AC2-103 GEN1
Solar/Wind Helper
1.76
960841AF2-375 GEN
Solar/Wind Helper
1.115
957471AF2-041 GEN
Solar/Wind Harmer
6.159
959081AF2-199 GEN
Solar/Wind Harmer
2.053
971067AG2-660 GEN
Solar/Wind Harmer
0.477
991182J1586 G
External Queue
59.741127014160156
991227J1663 G
External Queue
12.83681869506836
990527J1329
External Queue
5.334218978881836
990142J1224
External Queue
38.99313735961914
991177J1571 G
External Queue
62.85662078857422
CBM West 1LTFEXP_CBM-W1->PJM
CBM
149.7
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.83
MECLTFEXP_MEC->PJM
CLTF
6.33
SIGELTFEXP_SIGE->PJM
CLTF
0.128
LAGNLTFEXP_LAGN->PJM
CLTF
4.227
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.789
TVALTFEXP_TVA->PJM
CLTF
1.796
CPLELTFEXP_CPLE->PJM
CLTF
0.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.929
NYPJM->LTFIMP_NY
CLTF
0.875
LGEELTFEXP_LGEE->PJM
CLTF
1.321
WECLTFEXP_WEC->PJM
CLTF
1.7
AG2-052LTFEXP_AG2-052->PJM
LTF
0.111
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166

Details for 19MON12-02LALLENDORF 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-023T_SRT-SL


Base Case Flowgate

Area:ATSI/ITCT
Facility Description:
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-023T_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.29 %
Rating:1660.0 MVA
Rating Type:B
MVA to Mitigate:1946.94
MW Contribution:16.4
Bus #Bus NameTypeMW Contribution
270449AD2-020 GEN
Solar/Wind Harmer
2.155
943021AE2-325 GEN
Solar/Wind Harmer
2.8
270505AE1-170 C O1
Solar/Wind Harmer
11.001
945111AF1-176 GEN
Solar/Wind Harmer
12.923
24639705ELKHART HY
Adder
0.1
247604X1-042
50/50
0.395
24441205WTRV SLR C
Solar/Wind Harmer
0.115
945111AF1-176 GEN
Solar/Wind Harmer
4.096
24642205MAYFLWER
Adder
0.443
247643Z2-116 C
Solar/Wind Harmer
0.046
970349AG2-230 GEN
Solar/Wind Harmer
8.79
970031AG2-029 GEN
Solar/Wind Harmer
16.396
270535AF1-215 GEN1
Solar/Wind Harmer
2.459
972231SS25-0005
Solar/Wind Harmer
5.029
972181SS23-001
Solar/Wind Harmer
3.143
274752CRETE EC ;2U
Adder
2.59
274753CRETE EC ;3U
Adder
2.59
964401AG1-302 GEN
Solar/Wind Harmer
4.752
274724RIVER EC ;11
Adder
9.257
274802UNIV PARK;5U
Adder
2.979
274826FISK ;BP
Adder
5.578
274800UNIV PARK;3U
Adder
2.963
972038AH1-567 GEN2
Adder
0.185
959141AF2-205 GEN
Solar/Wind Harmer
3.072
276772AC2-154 GEN
Solar/Wind Harmer
1.413
276806AD2-047 C O1
Solar/Wind Harmer
5.421
970941AG2-585 GEN
Solar/Wind Harmer
6.335
274772LINCOLN ;3U
Adder
3.131
972228AH1-698 GEN2
Adder
1.869
274676JOLIET 29;8U
Adder
14.823
276893AG1-478 C
Solar/Wind Harmer
0.209
274729ELWOOD EC;1P
Adder
8.211
274730ELWOOD EC;6P
Adder
8.212
274734ELWOOD EC;8P
Adder
8.212
274736ELWOOD EC;9P
Adder
8.212
276897AD1-100 C
Solar/Wind Harmer
14.484
939351AE1-166 GEN
Solar/Wind Harmer
2.96
961051AF2-396 GEN
Solar/Wind Harmer
11.942
961051AF2-396 GEN
Solar/Wind Harmer
5.555
957891AF2-083 GEN
Solar/Wind Harmer
2.449
960981AF2-389 GEN
Solar/Wind Harmer
1.097
270216AD2-079_GEN
Solar/Wind Harmer
0.397
270526AF1-158 GEN
Solar/Wind Harmer
2.929
24441505OLIV SLR
Solar/Wind Harmer
0.086
247620Y3-023
Adder
0.289
965681AG1-436 GEN
Solar/Wind Harmer
7.521
965791AG1-447 GEN
Solar/Wind Harmer
3.848
274808UNIV PK N;4U
Adder
2.592
274803UNIV PARK;6U
Adder
2.979
274888KELLY CRK;1U
Solar/Wind Harmer
2.992
274887GEN-1.85
Solar/Wind Harmer
2.701
276843GEN-1.7
Solar/Wind Harmer
0.291
958011AF2-095 GEN
Solar/Wind Harmer
7.297
274770LINCOLN ;1U
Adder
3.131
274771LINCOLN ;2U
Adder
3.131
972259AH1-714 GEN
Adder
9.556
274674JOLIET 9 ;6U
Adder
7.691
274847GR RIDGE ;BU
Solar/Wind Harmer
2.504
958481AF2-142 GEN
Solar/Wind Harmer
7.37
274861TOP CROP ;1U
Solar/Wind Harmer
2.977
274862TOP CROP ;2U
Solar/Wind Harmer
2.486
971573AH1-285 GEN
Solar/Wind Harmer
4.205
274696ROCKY RD ;4P
Adder
5.551
274695ROCKY RD ;2P
Adder
5.423
274693ROCKY RD ;1P
Adder
5.369
274697ROCKY RD ;3P
Adder
1.473
274683WAUKEGAN ;8U
Adder
10.259
274683WAUKEGAN ;8U
Adder
8.648
970321AG2-212 GEN
Solar/Wind Harmer
8.665
958491AF2-143 GEN
Solar/Wind Harmer
7.276
962691AG1-118 GEN
Solar/Wind Harmer
14.492
970921AG2-575 GEN
Solar/Wind Harmer
4.82
970921AG2-575 GEN
Solar/Wind Harmer
1.121
274879MINONK ;1U
Solar/Wind Harmer
3.249
942991AE2-321 GEN
Solar/Wind Harmer
4.795
971333AH1-146 GEN
Solar/Wind Harmer
9.539
971335AH1-147 GEN
Solar/Wind Harmer
9.539
276872AE1-163_GEN1
Solar/Wind Harmer
3.2
945421AF1-207 GEN
Solar/Wind Harmer
6.692
957841AF2-078 GEN
Solar/Wind Harmer
2.88
274764LEE CO EC;5U
Adder
4.339
274765LEE CO EC;6U
Adder
4.339
274762LEE CO EC;3U
Adder
4.329
274763LEE CO EC;4U
Adder
4.288
972267AH1-718 GEN
Adder
1.919
241996AE2-282_GEN
Solar/Wind Helper
0.994
971341AH1-150 GEN
Solar/Wind Harmer
4.354
971343AH1-151 GEN
Solar/Wind Harmer
4.354
970373AG2-245 GEN
Solar/Wind Harmer
11.786
270055AF2-134 C O1
Solar/Wind Harmer
1.639
270063AE2-323 C
Solar/Wind Harmer
1.177
274751CRETE EC ;1U
Adder
2.59
274754CRETE EC ;4U
Adder
2.59
958381AF2-132 GEN
Solar/Wind Harmer
4.752
274723RIVER EC ;12
Adder
9.368
964861AG1-349 GEN
Solar/Wind Harmer
4.103
971917AH1-482 GEN
Solar/Wind Harmer
4.735
274812UNIV PK N;8U
Adder
2.603
276164X3-005 C
Solar/Wind Harmer
0.363
274801UNIV PARK;4U
Adder
2.963
276776AD2-060 GEN
Solar/Wind Harmer
0.214
972207SS24-0001
Solar/Wind Harmer
11.132
274773LINCOLN ;4U
Adder
3.131
274774LINCOLN ;5U
Adder
3.131
274676JOLIET 29;8U
Adder
15.372
940581AE2-045 GEN
Solar/Wind Harmer
5.096
971605AH1-302 GEN
Solar/Wind Harmer
4.358
274732ELWOOD EC;7P
Adder
8.212
274674JOLIET 9 ;6U
Adder
7.691
941551AE2-152 GEN
Solar/Wind Harmer
2.264
274871GR RIDGE ;2U
Solar/Wind Harmer
3.807
274745AC1-111 GEN9
Adder
2.748
276691AA1-018 GEN1
Solar/Wind Harmer
0.229
274682WAUKEGAN ;7U
Adder
8.761
274828WAUKEGAN ;BP
Adder
5.378
970245AG2-165 GEN
Solar/Wind Harmer
8.665
276901AD2-066 C O1
Solar/Wind Harmer
1.695
960751AF2-366 GEN
Solar/Wind Harmer
1.383
962781AG1-127 GEN
Solar/Wind Harmer
4.583
274872LEEDK;1U
Solar/Wind Harmer
3.95
939401AE1-172 GEN
Solar/Wind Harmer
6.693
971997AH1-543 GEN
Solar/Wind Harmer
7.532
276861AD2-134 GEN
Solar/Wind Harmer
0.851
276876AE1-163_GEN2
Solar/Wind Harmer
3.2
274822ROCKFORD ;11
Adder
9.283
972235AH1-702 GEN1
Adder
1.189
274761LEE CO EC;2U
Adder
4.329
274766LEE CO EC;7U
Adder
4.278
241885AC2-103 GEN1
Solar/Wind Helper
2.07
241807AE2-176_GEN
Solar/Wind Helper
1.363
241808AF1-120 C
Solar/Wind Helper
0.555
241840AF1-064_GEN
Solar/Wind Helper
0.673
960841AF2-375 GEN
Solar/Wind Helper
1.036
957471AF2-041 GEN
Solar/Wind Harmer
6.531
959081AF2-199 GEN
Solar/Wind Harmer
2.177
971067AG2-660 GEN
Solar/Wind Harmer
0.506
971549AH1-272 GEN
Solar/Wind Harmer
20.75
944161AF1-084 GEN
Solar/Wind Harmer
1.752
971771AH1-392 GEN
Solar/Wind Harmer
5.93
971769AH1-391 GEN
Solar/Wind Harmer
6.412
960681AF2-359 GEN
Solar/Wind Harmer
2.273
971347AH1-153 GEN
Solar/Wind Harmer
8.79
270536AF1-215 GEN2
Solar/Wind Harmer
2.459
274814UNIV PK N;0U
Adder
2.626
274807UNIV PK N;3U
Adder
2.62
274805UNIV PK N;1U
Adder
2.609
274811UNIV PK N;7U
Adder
2.603
958391AF2-133 GEN
Solar/Wind Harmer
4.67
972037AH1-567 GEN1
Adder
0.094
274827FISK ;RP
Adder
3.953
960591AF2-350 GEN
Solar/Wind Harmer
5.068
274775LINCOLN ;6U
Adder
3.131
274776LINCOLN ;7U
Adder
3.131
274777LINCOLN ;8U
Adder
3.131
972227AH1-698 GEN1
Adder
1.316
274687WILL CNTY;4U
Adder
14.044
274687WILL CNTY;4U
Adder
14.044
274675JOLIET 29;7U
Adder
15.373
274675JOLIET 29;7U
Adder
14.824
274731ELWOOD EC;2P
Adder
8.211
274733ELWOOD EC;3P
Adder
8.211
274735ELWOOD EC;4P
Adder
8.211
274728ELWOOD EC;5P
Adder
8.212
970833AG2-524 GEN
Solar/Wind Harmer
4.326
970833AG2-524 GEN
Solar/Wind Harmer
2.012
274746AC1-111 G10
Adder
2.748
274744AC1-111 GEN8
Adder
2.748
276868AE1-113 GEN
Solar/Wind Harmer
4.873
276882AE2-255 GEN
Solar/Wind Harmer
1.625
971177AH1-047 GEN
Solar/Wind Harmer
2.809
971411AH1-196 GEN
Solar/Wind Harmer
7.163
971675AH1-338 GEN
Solar/Wind Harmer
8.582
274823ROCKFORD ;21
Adder
9.216
241886AC2-103 GEN2
Solar/Wind Helper
2.07
945411AF1-206 GEN
Solar/Wind Helper
1.882
945641AF1-229 GEN
Solar/Wind Helper
1.018
270499AE1-146 GEN
Solar/Wind Helper
1.555
971171AH1-044 GEN
Solar/Wind Harmer
4.354
970707AG2-453 GEN
Solar/Wind Harmer
13.965
276694AA1-018 GEN2
Solar/Wind Harmer
3.101
943121AE2-341 GEN
Solar/Wind Harmer
7.369
943591AF1-030 GEN
Solar/Wind Harmer
4.913
274682WAUKEGAN ;7U
Adder
8.761
970513AG2-328 GEN
Solar/Wind Harmer
8.665
970517AG2-330 GEN
Solar/Wind Harmer
7.859
276805AD2-038 GEN
Solar/Wind Harmer
2.488
274872LEEDK;1U
Solar/Wind Harmer
0.123
276799AD1-013 GEN
Solar/Wind Harmer
1.054
946671AF1-331 GEN
Solar/Wind Harmer
0.2
274855GSG-6 ;RU
Solar/Wind Harmer
1.76
274850MENDOTA H;RU
Solar/Wind Harmer
1.224
276602WESTBROOK C
Solar/Wind Harmer
1.013
276863AD2-134 GEN
Solar/Wind Harmer
0.851
276889AE2-281 GEN
Solar/Wind Harmer
0.914
972236AH1-702 GEN2
Adder
1.034
274760LEE CO EC;1U
Adder
4.329
274767LEE CO EC;8U
Adder
4.278
241832AE2-181_GEN
Solar/Wind Helper
0.429
959091AF2-200 GEN
Solar/Wind Harmer
4.354
991182J1586 G
External Queue
55.963897705078125
991227J1663 G
External Queue
12.278471946716309
990527J1329
External Queue
4.328737258911133
990142J1224
External Queue
31.64306640625
991177J1571 G
External Queue
36.20563507080078
CBM West 1LTFEXP_CBM-W1->PJM
CBM
164.071
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.37
MECLTFEXP_MEC->PJM
CLTF
6.73
SIGELTFEXP_SIGE->PJM
CLTF
0.138
LAGNLTFEXP_LAGN->PJM
CLTF
4.532
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.937
TVALTFEXP_TVA->PJM
CLTF
1.933
CPLELTFEXP_CPLE->PJM
CLTF
0.382
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.37
NYPJM->LTFIMP_NY
CLTF
0.969
LGEELTFEXP_LGEE->PJM
CLTF
1.44
WECLTFEXP_WEC->PJM
CLTF
1.803
AG2-052LTFEXP_AG2-052->PJM
LTF
0.117
AH1-155LTFEXP_AH1-155->PJM
LTF
0.176

Details for 19MON12-02LALLENDORF 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-022T_SRT-A


Base Case Flowgate

Area:ATSI/ITCT
Facility Description:
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-022T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.16 %
Rating:1660.0 MVA
Rating Type:B
MVA to Mitigate:1944.85
MW Contribution:16.4
Bus #Bus NameTypeMW Contribution
961051AF2-396 GEN
Solar/Wind Harmer
11.943
961051AF2-396 GEN
Solar/Wind Harmer
5.555
957891AF2-083 GEN
Solar/Wind Harmer
2.449
960981AF2-389 GEN
Solar/Wind Harmer
1.097
270216AD2-079_GEN
Solar/Wind Harmer
0.397
270526AF1-158 GEN
Solar/Wind Harmer
2.929
24441505OLIV SLR
Solar/Wind Harmer
0.086
247620Y3-023
Adder
0.289
965681AG1-436 GEN
Solar/Wind Harmer
7.522
965791AG1-447 GEN
Solar/Wind Harmer
3.849
274808UNIV PK N;4U
Adder
2.592
247604X1-042
50/50
0.395
24441205WTRV SLR C
Solar/Wind Harmer
0.115
945111AF1-176 GEN
Solar/Wind Harmer
4.096
24642205MAYFLWER
Adder
0.443
247643Z2-116 C
Solar/Wind Harmer
0.046
970349AG2-230 GEN
Solar/Wind Harmer
8.791
970031AG2-029 GEN
Solar/Wind Harmer
16.401
270535AF1-215 GEN1
Solar/Wind Harmer
2.46
972231SS25-0005
Solar/Wind Harmer
5.03
972181SS23-001
Solar/Wind Harmer
3.144
274752CRETE EC ;2U
Adder
2.591
274753CRETE EC ;3U
Adder
2.591
964401AG1-302 GEN
Solar/Wind Harmer
4.753
274724RIVER EC ;11
Adder
9.258
274802UNIV PARK;5U
Adder
2.979
274826FISK ;BP
Adder
5.579
274800UNIV PARK;3U
Adder
2.963
972038AH1-567 GEN2
Adder
0.185
959141AF2-205 GEN
Solar/Wind Harmer
3.072
276772AC2-154 GEN
Solar/Wind Harmer
1.413
276806AD2-047 C O1
Solar/Wind Harmer
5.422
970941AG2-585 GEN
Solar/Wind Harmer
6.335
274772LINCOLN ;3U
Adder
3.131
972228AH1-698 GEN2
Adder
1.869
274676JOLIET 29;8U
Adder
14.825
276893AG1-478 C
Solar/Wind Harmer
0.209
274729ELWOOD EC;1P
Adder
8.212
274730ELWOOD EC;6P
Adder
8.213
274734ELWOOD EC;8P
Adder
8.213
274736ELWOOD EC;9P
Adder
8.213
276897AD1-100 C
Solar/Wind Harmer
14.486
939351AE1-166 GEN
Solar/Wind Harmer
2.96
970707AG2-453 GEN
Solar/Wind Harmer
13.966
276694AA1-018 GEN2
Solar/Wind Harmer
3.101
943121AE2-341 GEN
Solar/Wind Harmer
7.37
943591AF1-030 GEN
Solar/Wind Harmer
4.913
274682WAUKEGAN ;7U
Adder
8.762
970513AG2-328 GEN
Solar/Wind Harmer
8.666
971549AH1-272 GEN
Solar/Wind Harmer
20.75
944161AF1-084 GEN
Solar/Wind Harmer
1.752
971771AH1-392 GEN
Solar/Wind Harmer
5.93
971769AH1-391 GEN
Solar/Wind Harmer
6.412
960681AF2-359 GEN
Solar/Wind Harmer
2.273
971347AH1-153 GEN
Solar/Wind Harmer
8.791
270536AF1-215 GEN2
Solar/Wind Harmer
2.46
274814UNIV PK N;0U
Adder
2.626
274807UNIV PK N;3U
Adder
2.621
274805UNIV PK N;1U
Adder
2.609
274811UNIV PK N;7U
Adder
2.604
958391AF2-133 GEN
Solar/Wind Harmer
4.671
972037AH1-567 GEN1
Adder
0.094
274827FISK ;RP
Adder
3.954
960591AF2-350 GEN
Solar/Wind Harmer
5.068
274775LINCOLN ;6U
Adder
3.131
274776LINCOLN ;7U
Adder
3.131
274777LINCOLN ;8U
Adder
3.131
972227AH1-698 GEN1
Adder
1.316
274687WILL CNTY;4U
Adder
14.046
274687WILL CNTY;4U
Adder
14.046
274675JOLIET 29;7U
Adder
15.374
274675JOLIET 29;7U
Adder
14.825
274731ELWOOD EC;2P
Adder
8.212
274733ELWOOD EC;3P
Adder
8.212
274735ELWOOD EC;4P
Adder
8.212
274728ELWOOD EC;5P
Adder
8.213
970833AG2-524 GEN
Solar/Wind Harmer
4.327
970833AG2-524 GEN
Solar/Wind Harmer
2.012
274746AC1-111 G10
Adder
2.749
274744AC1-111 GEN8
Adder
2.749
276868AE1-113 GEN
Solar/Wind Harmer
4.874
276882AE2-255 GEN
Solar/Wind Harmer
1.625
971177AH1-047 GEN
Solar/Wind Harmer
2.809
971411AH1-196 GEN
Solar/Wind Harmer
7.164
971675AH1-338 GEN
Solar/Wind Harmer
8.583
274823ROCKFORD ;21
Adder
9.217
241886AC2-103 GEN2
Solar/Wind Helper
2.071
945411AF1-206 GEN
Solar/Wind Helper
1.844
945641AF1-229 GEN
Solar/Wind Helper
1.019
270499AE1-146 GEN
Solar/Wind Helper
1.555
971171AH1-044 GEN
Solar/Wind Harmer
4.355
274803UNIV PARK;6U
Adder
2.979
274888KELLY CRK;1U
Solar/Wind Harmer
2.992
274887GEN-1.85
Solar/Wind Harmer
2.702
276843GEN-1.7
Solar/Wind Harmer
0.291
958011AF2-095 GEN
Solar/Wind Harmer
7.298
274770LINCOLN ;1U
Adder
3.131
274771LINCOLN ;2U
Adder
3.131
972259AH1-714 GEN
Adder
9.558
274674JOLIET 9 ;6U
Adder
7.692
274847GR RIDGE ;BU
Solar/Wind Harmer
2.505
274861TOP CROP ;1U
Solar/Wind Harmer
2.978
274862TOP CROP ;2U
Solar/Wind Harmer
2.486
958481AF2-142 GEN
Solar/Wind Harmer
7.371
971573AH1-285 GEN
Solar/Wind Harmer
4.206
274696ROCKY RD ;4P
Adder
5.551
274695ROCKY RD ;2P
Adder
5.423
274693ROCKY RD ;1P
Adder
5.37
274697ROCKY RD ;3P
Adder
1.473
274683WAUKEGAN ;8U
Adder
10.261
274683WAUKEGAN ;8U
Adder
8.649
970321AG2-212 GEN
Solar/Wind Harmer
8.666
958491AF2-143 GEN
Solar/Wind Harmer
7.277
962691AG1-118 GEN
Solar/Wind Harmer
14.494
970921AG2-575 GEN
Solar/Wind Harmer
4.82
970921AG2-575 GEN
Solar/Wind Harmer
1.121
274879MINONK ;1U
Solar/Wind Harmer
3.249
942991AE2-321 GEN
Solar/Wind Harmer
4.796
971333AH1-146 GEN
Solar/Wind Harmer
9.541
971335AH1-147 GEN
Solar/Wind Harmer
9.541
276872AE1-163_GEN1
Solar/Wind Harmer
3.2
945421AF1-207 GEN
Solar/Wind Harmer
6.693
957841AF2-078 GEN
Solar/Wind Harmer
2.88
274764LEE CO EC;5U
Adder
4.339
274765LEE CO EC;6U
Adder
4.339
274762LEE CO EC;3U
Adder
4.329
274763LEE CO EC;4U
Adder
4.288
972267AH1-718 GEN
Adder
1.919
241996AE2-282_GEN
Solar/Wind Helper
0.973
971341AH1-150 GEN
Solar/Wind Harmer
4.355
971343AH1-151 GEN
Solar/Wind Harmer
4.355
270449AD2-020 GEN
Solar/Wind Harmer
2.155
943021AE2-325 GEN
Solar/Wind Harmer
2.801
270505AE1-170 C O1
Solar/Wind Harmer
11.002
945111AF1-176 GEN
Solar/Wind Harmer
12.924
24639705ELKHART HY
Adder
0.1
970373AG2-245 GEN
Solar/Wind Harmer
11.788
270055AF2-134 C O1
Solar/Wind Harmer
1.64
270063AE2-323 C
Solar/Wind Harmer
1.178
274751CRETE EC ;1U
Adder
2.591
274754CRETE EC ;4U
Adder
2.591
958381AF2-132 GEN
Solar/Wind Harmer
4.753
274723RIVER EC ;12
Adder
9.37
964861AG1-349 GEN
Solar/Wind Harmer
4.104
971917AH1-482 GEN
Solar/Wind Harmer
4.736
274812UNIV PK N;8U
Adder
2.604
276164X3-005 C
Solar/Wind Harmer
0.363
274801UNIV PARK;4U
Adder
2.963
276776AD2-060 GEN
Solar/Wind Harmer
0.214
972207SS24-0001
Solar/Wind Harmer
11.133
274773LINCOLN ;4U
Adder
3.131
274774LINCOLN ;5U
Adder
3.131
274676JOLIET 29;8U
Adder
15.374
940581AE2-045 GEN
Solar/Wind Harmer
5.097
971605AH1-302 GEN
Solar/Wind Harmer
4.358
274732ELWOOD EC;7P
Adder
8.213
274674JOLIET 9 ;6U
Adder
7.692
941551AE2-152 GEN
Solar/Wind Harmer
2.264
274871GR RIDGE ;2U
Solar/Wind Harmer
3.808
274745AC1-111 GEN9
Adder
2.749
276691AA1-018 GEN1
Solar/Wind Harmer
0.229
274682WAUKEGAN ;7U
Adder
8.762
274828WAUKEGAN ;BP
Adder
5.378
970245AG2-165 GEN
Solar/Wind Harmer
8.666
276901AD2-066 C O1
Solar/Wind Harmer
1.695
960751AF2-366 GEN
Solar/Wind Harmer
1.383
962781AG1-127 GEN
Solar/Wind Harmer
4.584
274872LEEDK;1U
Solar/Wind Harmer
3.951
939401AE1-172 GEN
Solar/Wind Harmer
6.694
971997AH1-543 GEN
Solar/Wind Harmer
7.533
276861AD2-134 GEN
Solar/Wind Harmer
0.851
276876AE1-163_GEN2
Solar/Wind Harmer
3.2
274822ROCKFORD ;11
Adder
9.285
972235AH1-702 GEN1
Adder
1.19
274761LEE CO EC;2U
Adder
4.329
274766LEE CO EC;7U
Adder
4.278
241885AC2-103 GEN1
Solar/Wind Helper
2.071
241807AE2-176_GEN
Solar/Wind Helper
1.362
241808AF1-120 C
Solar/Wind Helper
0.544
241840AF1-064_GEN
Solar/Wind Helper
0.672
960841AF2-375 GEN
Solar/Wind Helper
1.036
957471AF2-041 GEN
Solar/Wind Harmer
6.532
959081AF2-199 GEN
Solar/Wind Harmer
2.177
971067AG2-660 GEN
Solar/Wind Harmer
0.506
970517AG2-330 GEN
Solar/Wind Harmer
7.86
276805AD2-038 GEN
Solar/Wind Harmer
2.489
274872LEEDK;1U
Solar/Wind Harmer
0.123
276799AD1-013 GEN
Solar/Wind Harmer
1.055
946671AF1-331 GEN
Solar/Wind Harmer
0.2
274855GSG-6 ;RU
Solar/Wind Harmer
1.761
274850MENDOTA H;RU
Solar/Wind Harmer
1.224
276602WESTBROOK C
Solar/Wind Harmer
1.013
276863AD2-134 GEN
Solar/Wind Harmer
0.851
276889AE2-281 GEN
Solar/Wind Harmer
0.914
972236AH1-702 GEN2
Adder
1.034
274760LEE CO EC;1U
Adder
4.329
274767LEE CO EC;8U
Adder
4.278
241832AE2-181_GEN
Solar/Wind Helper
0.421
959091AF2-200 GEN
Solar/Wind Harmer
4.355
991182J1586 G
External Queue
55.95536804199219
991227J1663 G
External Queue
12.277408599853516
990527J1329
External Queue
4.328125953674316
990142J1224
External Queue
31.638599395751953
991177J1571 G
External Queue
36.20295715332031
CBM West 1LTFEXP_CBM-W1->PJM
CBM
164.076
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.371
MECLTFEXP_MEC->PJM
CLTF
6.731
SIGELTFEXP_SIGE->PJM
CLTF
0.138
LAGNLTFEXP_LAGN->PJM
CLTF
4.532
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.936
TVALTFEXP_TVA->PJM
CLTF
1.933
CPLELTFEXP_CPLE->PJM
CLTF
0.382
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.373
NYPJM->LTFIMP_NY
CLTF
0.97
LGEELTFEXP_LGEE->PJM
CLTF
1.44
WECLTFEXP_WEC->PJM
CLTF
1.803
AG2-052LTFEXP_AG2-052->PJM
LTF
0.117
AH1-155LTFEXP_AH1-155->PJM
LTF
0.176

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-009_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-009_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.39 %
Rating:1499.0 MVA
Rating Type:B
MVA to Mitigate:2479.15
MW Contribution:15.9
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
12.736
972211AH1-690 GEN
50/50
275.935
23888502TROY G1
50/50
1.742
23888602TROY G2
50/50
1.742
23860102FRMENG 1
50/50
1.188
23860202FRMENG 2
50/50
1.188
241886AC2-103 GEN2
Solar/Wind Harmer
25.595
970817AG2-515 GEN
Solar/Wind Harmer
14.806
945411AF1-206 GEN
Solar/Wind Harmer
8.02
270499AE1-146 GEN
Solar/Wind Harmer
2.385
945641AF1-229 GEN
Solar/Wind Harmer
3.427
971549AH1-272 GEN
Solar/Wind Harmer
12.688
270297AD1-101 GEN
Solar/Wind Harmer
1.9
966831AG1-554 GEN
Solar/Wind Harmer
0.712
971989AH1-539 GEN
Solar/Wind Harmer
7.704
247607V1-011 GEN
Solar/Wind Harmer
2.309
957201AF2-014 GEN
Solar/Wind Harmer
2.623
270435AC2-044 GEN
Solar/Wind Harmer
1.157
944161AF1-084 GEN
Solar/Wind Harmer
1.256
24191202EL_AA1-006
Adder
0.123
965041AG1-368 GEN
Solar/Wind Harmer
5.428
965051AG1-369 GEN
Solar/Wind Harmer
2.697
971771AH1-392 GEN
Solar/Wind Harmer
4.684
270302AB2-170 GEN
Solar/Wind Harmer
4.348
270317AD1-130_GEN
Solar/Wind Harmer
1.667
971567AH1-282 GEN
Solar/Wind Harmer
7.657
971769AH1-391 GEN
Solar/Wind Harmer
5.074
960681AF2-359 GEN
Solar/Wind Harmer
1.844
971347AH1-153 GEN
Solar/Wind Harmer
7.29
963791AG1-232 GEN
Solar/Wind Harmer
6.504
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.093
270071AF1-092 GEN
Solar/Wind Harmer
6.841
274814UNIV PK N;0U
Adder
2.266
274807UNIV PK N;3U
Adder
2.261
274805UNIV PK N;1U
Adder
2.251
274811UNIV PK N;7U
Adder
2.246
958391AF2-133 GEN
Solar/Wind Harmer
4.069
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.436
960591AF2-350 GEN
Solar/Wind Harmer
4.415
274775LINCOLN ;6U
Adder
2.736
24189902OREGON_CT2
50/50
2.559
23888702TROY G3
50/50
1.742
972253AH1-711 GEN
50/50
53.201
23856402BAYSG1
50/50
1.289
23920202STRYCT
50/50
1.895
23860302FRMENG 3
50/50
2.426
241885AC2-103 GEN1
Solar/Wind Harmer
25.595
241858AF1-205_GEN
Solar/Wind Harmer
5.472
241808AF1-120 C
Solar/Wind Harmer
1.197
241840AF1-064_GEN
Solar/Wind Harmer
1.39
972301AH1-735 GEN
Adder
6.573
23906402RICHG1
Adder
1.315
23906502RICHG2&3
Adder
1.312
270361_3
Solar/Wind Harmer
8.607
960841AF2-375 GEN
Solar/Wind Harmer
3.799
241807AE2-176_GEN
Solar/Wind Harmer
3.58
247522W1-056 GEN
Solar/Wind Harmer
1.591
970515AG2-329 GEN
Solar/Wind Harmer
10.186
944231AF1-091 GEN
Solar/Wind Harmer
2.443
270428AC2-015 C
Solar/Wind Harmer
3.305
246936BC-WTG1
Solar/Wind Harmer
2.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.752
965421AG1-410 GEN
Solar/Wind Harmer
17.181
270449AD2-020 GEN
Solar/Wind Harmer
1.572
943021AE2-325 GEN
Solar/Wind Harmer
2.042
24695305TIMB G C
Solar/Wind Harmer
3.08
945111AF1-176 GEN
Solar/Wind Harmer
9.795
270505AE1-170 C O1
Solar/Wind Harmer
8.226
247521TR3_G114
Solar/Wind Harmer
1.816
270246TR4_N_V150
Solar/Wind Harmer
0.459
24639705ELKHART HY
Adder
0.082
270063AE2-323 C
Solar/Wind Harmer
1.171
965011AG1-365 GEN
Solar/Wind Harmer
5.199
270462AD2-086
Solar/Wind Harmer
3.617
270223U2-072_GEN1
Solar/Wind Harmer
0.952
270578AF1-285 GEN2
Solar/Wind Harmer
0.582
270391AF1-285 GEN3
Solar/Wind Harmer
0.582
970905AG2-564 GEN
Solar/Wind Harmer
2.368
970373AG2-245 GEN
Solar/Wind Harmer
9.864
270055AF2-134 C O1
Solar/Wind Harmer
1.395
274751CRETE EC ;1U
Adder
2.22
274754CRETE EC ;4U
Adder
2.22
958381AF2-132 GEN
Solar/Wind Harmer
4.106
964861AG1-349 GEN
Solar/Wind Harmer
3.551
971917AH1-482 GEN
Solar/Wind Harmer
4.098
274723RIVER EC ;12
Adder
8.075
274812UNIV PK N;8U
Adder
2.246
276164X3-005 C
Solar/Wind Harmer
0.314
274801UNIV PARK;4U
Adder
2.578
940581AE2-045 GEN
Solar/Wind Harmer
4.504
274776LINCOLN ;7U
Adder
2.736
274777LINCOLN ;8U
Adder
2.736
972227AH1-698 GEN1
Adder
1.148
274687WILL CNTY;4U
Adder
12.261
274687WILL CNTY;4U
Adder
12.261
274675JOLIET 29;7U
Adder
13.435
274675JOLIET 29;7U
Adder
12.955
274728ELWOOD EC;5P
Adder
7.185
274731ELWOOD EC;2P
Adder
7.185
274733ELWOOD EC;3P
Adder
7.185
274735ELWOOD EC;4P
Adder
7.185
270024AE2-089 GEN
Solar/Wind Harmer
2.045
970833AG2-524 GEN
Solar/Wind Harmer
3.797
970833AG2-524 GEN
Solar/Wind Harmer
1.766
274746AC1-111 G10
Adder
2.416
274744AC1-111 GEN8
Adder
2.416
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.112
203846AF2-130 C
Solar/Wind Helper
0.246
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.861
24190002OREGON_ST1
50/50
3.442
24189802OREGON_CT1
50/50
2.611
23888802TROY G4
50/50
1.742
241996AE2-282_GEN
Solar/Wind Harmer
2.147
971677AH1-339 GEN
Solar/Wind Harmer
6.747
270007AE1-245 C
Solar/Wind Harmer
3.464
942801AE2-298 GEN
Solar/Wind Harmer
0.877
246938BC-WTG3
Solar/Wind Harmer
2.302
246937BC-WTG2
Solar/Wind Harmer
2.263
961051AF2-396 GEN
Solar/Wind Harmer
8.832
961051AF2-396 GEN
Solar/Wind Harmer
4.108
960981AF2-389 GEN
Solar/Wind Harmer
0.827
957891AF2-083 GEN
Solar/Wind Harmer
1.844
247620Y3-023
Adder
0.247
270216AD2-079_GEN
Solar/Wind Harmer
0.32
970611AG2-400 GEN
Solar/Wind Harmer
5.199
270526AF1-158 GEN
Solar/Wind Harmer
2.317
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.102
965791AG1-447 GEN
Solar/Wind Harmer
3.122
270224U2-072_GEN2
Solar/Wind Harmer
0.952
270227U2-072_GEN3
Solar/Wind Harmer
0.952
270228U2-072_GEN4
Solar/Wind Harmer
0.952
270231U2-072_GEN5
Solar/Wind Harmer
0.952
971231AH1-075 GEN
Solar/Wind Harmer
0.379
274808UNIV PK N;4U
Adder
2.237
274803UNIV PARK;6U
Adder
2.587
274888KELLY CRK;1U
Solar/Wind Harmer
2.607
274887GEN-1.85
Solar/Wind Harmer
2.354
276843GEN-1.7
Solar/Wind Harmer
0.253
958011AF2-095 GEN
Solar/Wind Harmer
6.358
274770LINCOLN ;1U
Adder
2.736
274771LINCOLN ;2U
Adder
2.736
942221AE2-234 GEN
Solar/Wind Harmer
0.323
972259AH1-714 GEN
Adder
8.361
274674JOLIET 9 ;6U
Adder
6.73
970321AG2-212 GEN
Solar/Wind Harmer
7.784
274847GR RIDGE ;BU
Solar/Wind Harmer
2.199
203947AF1-006 C
Solar/Wind Helper
0.379
203980AG1-197 GEN
Solar/Wind Helper
0.248
203979AG1-198 GEN
Solar/Wind Helper
0.193
241967AE2-285_GEN
Solar/Wind Helper
0.337
241801AE1-079 GEN
Solar/Wind Helper
0.131
241985AE1-237 GEN
Solar/Wind Helper
0.131
962101AG1-054 GEN
Solar/Wind Helper
0.325
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
276776AD2-060 GEN
Solar/Wind Harmer
0.187
971605AH1-302 GEN
Solar/Wind Harmer
3.851
972207SS24-0001
Solar/Wind Harmer
9.729
274773LINCOLN ;4U
Adder
2.736
274774LINCOLN ;5U
Adder
2.736
241847AF2-150_GEN
Solar/Wind Harmer
1.821
274676JOLIET 29;8U
Adder
13.435
941551AE2-152 GEN
Solar/Wind Harmer
1.984
274732ELWOOD EC;7P
Adder
7.185
274674JOLIET 9 ;6U
Adder
6.73
970245AG2-165 GEN
Solar/Wind Harmer
7.784
274871GR RIDGE ;2U
Solar/Wind Harmer
3.343
274745AC1-111 GEN9
Adder
2.416
961971AG1-040 GEN
Solar/Wind Helper
0.333
203835AF1-098 GEN
Solar/Wind Helper
1.311
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
23929302BS-PKR
50/50
2.268
241832AE2-181_GEN
Solar/Wind Harmer
1.946
958321AF2-126 GEN
Solar/Wind Harmer
1.49
23906502RICHG2&3
Adder
1.312
270575GUS2 35KV
Solar/Wind Harmer
10.14
270541AE2-072 C
Solar/Wind Harmer
4.319
970217AG2-149 GEN
Solar/Wind Harmer
22.462
270044AE2-322 C
Solar/Wind Harmer
0.849
270404AC1-167 GEN
Solar/Wind Harmer
0.707
270588AE1-091_GEN
Solar/Wind Harmer
6.832
270258AD1-119 GEN
Solar/Wind Harmer
1.729
247604X1-042
Adder
0.25
24441205WTRV SLR C
Solar/Wind Harmer
0.079
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.752
945111AF1-176 GEN
Solar/Wind Harmer
3.104
270191TR4_S_V150
Solar/Wind Harmer
1.62
270247TR4_N_V136
Solar/Wind Harmer
0.459
24642205MAYFLWER
Adder
0.339
970031AG2-029 GEN
Solar/Wind Harmer
15.896
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.199
965021AG1-366 GEN
Solar/Wind Harmer
1.209
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270043AE2-236 GEN
Solar/Wind Harmer
2.698
970349AG2-230 GEN
Solar/Wind Harmer
7.29
942871AE2-306 GEN
Solar/Wind Harmer
0.437
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270377AD1-106 GEN
Solar/Wind Harmer
2.928
270535AF1-215 GEN1
Solar/Wind Harmer
2.093
972231SS25-0005
Solar/Wind Harmer
4.31
972181SS23-001
Solar/Wind Harmer
2.694
274752CRETE EC ;2U
Adder
2.22
274753CRETE EC ;3U
Adder
2.22
964401AG1-302 GEN
Solar/Wind Harmer
4.106
274724RIVER EC ;11
Adder
7.979
959141AF2-205 GEN
Solar/Wind Harmer
2.693
274802UNIV PARK;5U
Adder
2.587
274826FISK ;BP
Adder
4.849
274800UNIV PARK;3U
Adder
2.578
972038AH1-567 GEN2
Adder
0.161
276772AC2-154 GEN
Solar/Wind Harmer
1.231
276806AD2-047 C O1
Solar/Wind Harmer
4.723
970941AG2-585 GEN
Solar/Wind Harmer
5.519
274772LINCOLN ;3U
Adder
2.736
972228AH1-698 GEN2
Adder
1.631
961961AG1-039 GEN
Solar/Wind Harmer
1.256
274676JOLIET 29;8U
Adder
12.955
276897AD1-100 C
Solar/Wind Harmer
12.695
939351AE1-166 GEN
Solar/Wind Harmer
2.594
276893AG1-478 C
Solar/Wind Harmer
0.183
274730ELWOOD EC;6P
Adder
7.185
274734ELWOOD EC;8P
Adder
7.185
274736ELWOOD EC;9P
Adder
7.185
970707AG2-453 GEN
Solar/Wind Harmer
12.238
274729ELWOOD EC;1P
Adder
7.185
970513AG2-328 GEN
Solar/Wind Harmer
7.784
970517AG2-330 GEN
Solar/Wind Harmer
7.06
971617AH1-308 GEN
Solar/Wind Harmer
2.534
962511AG1-100 GEN
Solar/Wind Helper
0.34
203830AF1-094 GEN
Solar/Wind Helper
0.322
959441AF2-235 GEN
Solar/Wind Helper
0.146
254305AE2-115 C
Solar/Wind Helper
0.112
20334926Z1-069 C
Solar/Wind Helper
0.641
943121AE2-341 GEN
Solar/Wind Harmer
2.014
943591AF1-030 GEN
Solar/Wind Harmer
1.343
991182J1586 G
External Queue
23.962841033935547
990527J1329
External Queue
1.7522491216659546
990142J1224
External Queue
12.808939933776855
991177J1571 G
External Queue
14.786787033081055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.542
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.6
MECLTFEXP_MEC->PJM
CLTF
6.243
SIGELTFEXP_SIGE->PJM
CLTF
0.163
LAGNLTFEXP_LAGN->PJM
CLTF
4.78
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.107
TVALTFEXP_TVA->PJM
CLTF
2.169
CPLELTFEXP_CPLE->PJM
CLTF
0.311
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.23
NYPJM->LTFIMP_NY
CLTF
2.01
LGEELTFEXP_LGEE->PJM
CLTF
1.95
WECLTFEXP_WEC->PJM
CLTF
1.601
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-12_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-12_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.45 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2615.26
MW Contribution:16.09
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
14.146
972211AH1-690 GEN
50/50
289.964
23888502TROY G1
50/50
1.811
23888602TROY G2
50/50
1.811
241886AC2-103 GEN2
Solar/Wind Harmer
26.657
970817AG2-515 GEN
Solar/Wind Harmer
15.186
945411AF1-206 GEN
Solar/Wind Harmer
8.014
945641AF1-229 GEN
Solar/Wind Harmer
3.431
270499AE1-146 GEN
Solar/Wind Harmer
2.196
971549AH1-272 GEN
Solar/Wind Harmer
12.968
270297AD1-101 GEN
Solar/Wind Harmer
1.865
247607V1-011 GEN
Solar/Wind Harmer
2.296
957201AF2-014 GEN
Solar/Wind Harmer
2.627
270435AC2-044 GEN
Solar/Wind Harmer
1.158
944161AF1-084 GEN
Solar/Wind Harmer
1.278
966831AG1-554 GEN
Solar/Wind Harmer
0.671
971989AH1-539 GEN
Solar/Wind Harmer
7.259
965041AG1-368 GEN
Solar/Wind Harmer
5.434
965051AG1-369 GEN
Solar/Wind Harmer
2.696
971771AH1-392 GEN
Solar/Wind Harmer
4.755
270302AB2-170 GEN
Solar/Wind Harmer
4.326
270317AD1-130_GEN
Solar/Wind Harmer
1.658
971769AH1-391 GEN
Solar/Wind Harmer
5.15
971567AH1-282 GEN
Solar/Wind Harmer
7.434
960681AF2-359 GEN
Solar/Wind Harmer
1.871
971347AH1-153 GEN
Solar/Wind Harmer
7.391
963791AG1-232 GEN
Solar/Wind Harmer
6.533
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
270536AF1-215 GEN2
Solar/Wind Harmer
2.12
270071AF1-092 GEN
Solar/Wind Harmer
6.896
274814UNIV PK N;0U
Adder
2.295
274807UNIV PK N;3U
Adder
2.29
274805UNIV PK N;1U
Adder
2.28
274811UNIV PK N;7U
Adder
2.275
958391AF2-133 GEN
Solar/Wind Harmer
4.12
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.48
960591AF2-350 GEN
Solar/Wind Harmer
4.471
274775LINCOLN ;6U
Adder
2.77
274776LINCOLN ;7U
Adder
2.77
274777LINCOLN ;8U
Adder
2.77
972227AH1-698 GEN1
Adder
1.163
274687WILL CNTY;4U
Adder
12.414
274687WILL CNTY;4U
Adder
12.414
274675JOLIET 29;7U
Adder
13.602
274675JOLIET 29;7U
Adder
13.116
274728ELWOOD EC;5P
Adder
7.275
274731ELWOOD EC;2P
Adder
7.274
24189902OREGON_CT2
50/50
2.688
23888702TROY G3
50/50
1.811
972253AH1-711 GEN
50/50
55.325
23856402BAYSG1
50/50
1.231
23920202STRYCT
50/50
1.893
241885AC2-103 GEN1
Solar/Wind Harmer
26.657
241858AF1-205_GEN
Solar/Wind Harmer
5.459
241808AF1-120 C
Solar/Wind Harmer
1.196
241840AF1-064_GEN
Solar/Wind Harmer
1.357
972301AH1-735 GEN
Adder
6.543
23906402RICHG1
Adder
1.309
23906502RICHG2&3
Adder
1.306
270361_3
Solar/Wind Harmer
7.852
960841AF2-375 GEN
Solar/Wind Harmer
3.479
970515AG2-329 GEN
Solar/Wind Harmer
10.037
247522W1-056 GEN
Solar/Wind Harmer
1.482
944231AF1-091 GEN
Solar/Wind Harmer
2.45
246936BC-WTG1
Solar/Wind Harmer
2.266
270489AE1-102 GEN1
Solar/Wind Harmer
0.753
965421AG1-410 GEN
Solar/Wind Harmer
17.213
270449AD2-020 GEN
Solar/Wind Harmer
1.599
943021AE2-325 GEN
Solar/Wind Harmer
2.077
24695305TIMB G C
Solar/Wind Harmer
3.074
945111AF1-176 GEN
Solar/Wind Harmer
9.954
270505AE1-170 C O1
Solar/Wind Harmer
8.362
24639705ELKHART HY
Adder
0.083
247521TR3_G114
Solar/Wind Harmer
1.816
270246TR4_N_V150
Solar/Wind Harmer
0.459
270063AE2-323 C
Solar/Wind Harmer
1.184
965011AG1-365 GEN
Solar/Wind Harmer
5.229
270462AD2-086
Solar/Wind Harmer
3.599
270223U2-072_GEN1
Solar/Wind Harmer
0.947
270578AF1-285 GEN2
Solar/Wind Harmer
0.579
270391AF1-285 GEN3
Solar/Wind Harmer
0.579
970373AG2-245 GEN
Solar/Wind Harmer
9.997
270055AF2-134 C O1
Solar/Wind Harmer
1.413
23929302BS-PKR
50/50
2.166
241832AE2-181_GEN
Solar/Wind Harmer
1.946
958321AF2-126 GEN
Solar/Wind Harmer
1.455
23906502RICHG2&3
Adder
1.306
270541AE2-072 C
Solar/Wind Harmer
4.224
270575GUS2 35KV
Solar/Wind Harmer
9.25
970217AG2-149 GEN
Solar/Wind Harmer
22.132
270044AE2-322 C
Solar/Wind Harmer
0.845
270404AC1-167 GEN
Solar/Wind Harmer
0.704
270258AD1-119 GEN
Solar/Wind Harmer
1.722
247604X1-042
Adder
0.255
24441205WTRV SLR C
Solar/Wind Harmer
0.081
270588AE1-091_GEN
Solar/Wind Harmer
6.538
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.753
945111AF1-176 GEN
Solar/Wind Harmer
3.155
24642205MAYFLWER
Adder
0.345
24190002OREGON_ST1
50/50
3.617
24189802OREGON_CT1
50/50
2.744
23888802TROY G4
50/50
1.811
241996AE2-282_GEN
Solar/Wind Harmer
2.146
971677AH1-339 GEN
Solar/Wind Harmer
6.235
270007AE1-245 C
Solar/Wind Harmer
3.444
246938BC-WTG3
Solar/Wind Harmer
2.305
246937BC-WTG2
Solar/Wind Harmer
2.266
942801AE2-298 GEN
Solar/Wind Harmer
0.872
961051AF2-396 GEN
Solar/Wind Harmer
8.981
961051AF2-396 GEN
Solar/Wind Harmer
4.177
960981AF2-389 GEN
Solar/Wind Harmer
0.84
957891AF2-083 GEN
Solar/Wind Harmer
1.874
247620Y3-023
Adder
0.25
270216AD2-079_GEN
Solar/Wind Harmer
0.325
970611AG2-400 GEN
Solar/Wind Harmer
5.229
270526AF1-158 GEN
Solar/Wind Harmer
2.352
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.19
965791AG1-447 GEN
Solar/Wind Harmer
3.167
270224U2-072_GEN2
Solar/Wind Harmer
0.947
270227U2-072_GEN3
Solar/Wind Harmer
0.947
270228U2-072_GEN4
Solar/Wind Harmer
0.947
270231U2-072_GEN5
Solar/Wind Harmer
0.947
274808UNIV PK N;4U
Adder
2.265
274803UNIV PARK;6U
Adder
2.619
274888KELLY CRK;1U
Solar/Wind Harmer
2.639
274887GEN-1.85
Solar/Wind Harmer
2.383
276843GEN-1.7
Solar/Wind Harmer
0.256
958011AF2-095 GEN
Solar/Wind Harmer
6.438
274770LINCOLN ;1U
Adder
2.77
274771LINCOLN ;2U
Adder
2.77
972259AH1-714 GEN
Adder
8.465
942221AE2-234 GEN
Solar/Wind Harmer
0.325
274674JOLIET 9 ;6U
Adder
6.813
970321AG2-212 GEN
Solar/Wind Harmer
7.876
274847GR RIDGE ;BU
Solar/Wind Harmer
2.226
274695ROCKY RD ;2P
Adder
4.836
274693ROCKY RD ;1P
Adder
4.789
274697ROCKY RD ;3P
Adder
1.314
274696ROCKY RD ;4P
Adder
4.95
274683WAUKEGAN ;8U
Adder
9.148
274683WAUKEGAN ;8U
Adder
7.711
203947AF1-006 C
Solar/Wind Helper
0.375
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241967AE2-285_GEN
Solar/Wind Helper
0.335
241801AE1-079 GEN
Solar/Wind Helper
0.13
241985AE1-237 GEN
Solar/Wind Helper
0.13
962101AG1-054 GEN
Solar/Wind Helper
0.323
946381AF1-302 GEN
Solar/Wind Helper
0.104
958481AF2-142 GEN
Solar/Wind Harmer
1.857
274751CRETE EC ;1U
Adder
2.249
274754CRETE EC ;4U
Adder
2.249
958381AF2-132 GEN
Solar/Wind Harmer
4.158
964861AG1-349 GEN
Solar/Wind Harmer
3.596
971917AH1-482 GEN
Solar/Wind Harmer
4.15
274723RIVER EC ;12
Adder
8.179
274812UNIV PK N;8U
Adder
2.275
276164X3-005 C
Solar/Wind Harmer
0.318
274801UNIV PARK;4U
Adder
2.611
276776AD2-060 GEN
Solar/Wind Harmer
0.189
940581AE2-045 GEN
Solar/Wind Harmer
4.559
972207SS24-0001
Solar/Wind Harmer
9.85
274773LINCOLN ;4U
Adder
2.77
274774LINCOLN ;5U
Adder
2.77
971605AH1-302 GEN
Solar/Wind Harmer
3.898
274676JOLIET 29;8U
Adder
13.602
941551AE2-152 GEN
Solar/Wind Harmer
2.009
274732ELWOOD EC;7P
Adder
7.275
274674JOLIET 9 ;6U
Adder
6.813
970245AG2-165 GEN
Solar/Wind Harmer
7.876
274871GR RIDGE ;2U
Solar/Wind Harmer
3.384
274745AC1-111 GEN9
Adder
2.446
276691AA1-018 GEN1
Solar/Wind Harmer
0.204
274682WAUKEGAN ;7U
Adder
7.809
274828WAUKEGAN ;BP
Adder
4.795
961971AG1-040 GEN
Solar/Wind Helper
0.329
203835AF1-098 GEN
Solar/Wind Helper
1.298
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
270191TR4_S_V150
Solar/Wind Harmer
1.62
270247TR4_N_V136
Solar/Wind Harmer
0.459
970031AG2-029 GEN
Solar/Wind Harmer
16.085
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.229
965021AG1-366 GEN
Solar/Wind Harmer
1.216
270485AE1-090_GEN
Solar/Wind Harmer
0.313
270043AE2-236 GEN
Solar/Wind Harmer
2.722
970349AG2-230 GEN
Solar/Wind Harmer
7.391
942871AE2-306 GEN
Solar/Wind Harmer
0.434
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
270535AF1-215 GEN1
Solar/Wind Harmer
2.12
972231SS25-0005
Solar/Wind Harmer
4.366
972181SS23-001
Solar/Wind Harmer
2.729
274752CRETE EC ;2U
Adder
2.249
274753CRETE EC ;3U
Adder
2.249
964401AG1-302 GEN
Solar/Wind Harmer
4.158
274724RIVER EC ;11
Adder
8.081
959141AF2-205 GEN
Solar/Wind Harmer
2.726
274802UNIV PARK;5U
Adder
2.619
274826FISK ;BP
Adder
4.91
274800UNIV PARK;3U
Adder
2.611
972038AH1-567 GEN2
Adder
0.163
276772AC2-154 GEN
Solar/Wind Harmer
1.247
276806AD2-047 C O1
Solar/Wind Harmer
4.783
970941AG2-585 GEN
Solar/Wind Harmer
5.588
274772LINCOLN ;3U
Adder
2.77
972228AH1-698 GEN2
Adder
1.651
274676JOLIET 29;8U
Adder
13.116
276897AD1-100 C
Solar/Wind Harmer
12.852
939351AE1-166 GEN
Solar/Wind Harmer
2.626
276893AG1-478 C
Solar/Wind Harmer
0.185
274730ELWOOD EC;6P
Adder
7.275
274734ELWOOD EC;8P
Adder
7.275
274736ELWOOD EC;9P
Adder
7.275
970707AG2-453 GEN
Solar/Wind Harmer
12.39
274729ELWOOD EC;1P
Adder
7.274
970513AG2-328 GEN
Solar/Wind Harmer
7.876
970517AG2-330 GEN
Solar/Wind Harmer
7.143
971617AH1-308 GEN
Solar/Wind Harmer
2.543
943121AE2-341 GEN
Solar/Wind Harmer
6.56
943591AF1-030 GEN
Solar/Wind Harmer
4.374
276694AA1-018 GEN2
Solar/Wind Harmer
2.759
274682WAUKEGAN ;7U
Adder
7.809
962511AG1-100 GEN
Solar/Wind Helper
0.337
203830AF1-094 GEN
Solar/Wind Helper
0.319
959441AF2-235 GEN
Solar/Wind Helper
0.145
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.636
274733ELWOOD EC;3P
Adder
7.274
274735ELWOOD EC;4P
Adder
7.274
970833AG2-524 GEN
Solar/Wind Harmer
3.844
970833AG2-524 GEN
Solar/Wind Harmer
1.788
274746AC1-111 G10
Adder
2.446
274744AC1-111 GEN8
Adder
2.446
270024AE2-089 GEN
Solar/Wind Harmer
2.053
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.244
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.854
991182J1586 G
External Queue
24.90056610107422
990527J1329
External Queue
1.8186211585998535
990142J1224
External Queue
13.294119834899902
991177J1571 G
External Queue
15.212156295776367
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.632
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.641
MECLTFEXP_MEC->PJM
CLTF
6.31
SIGELTFEXP_SIGE->PJM
CLTF
0.163
LAGNLTFEXP_LAGN->PJM
CLTF
4.814
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.113
TVALTFEXP_TVA->PJM
CLTF
2.181
CPLELTFEXP_CPLE->PJM
CLTF
0.312
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.518
NYPJM->LTFIMP_NY
CLTF
1.998
LGEELTFEXP_LGEE->PJM
CLTF
1.955
WECLTFEXP_WEC->PJM
CLTF
1.62
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-F1_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.45 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2615.26
MW Contribution:16.09
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.166
241832AE2-181_GEN
Solar/Wind Harmer
1.946
958321AF2-126 GEN
Solar/Wind Harmer
1.455
23906502RICHG2&3
Adder
1.306
270541AE2-072 C
Solar/Wind Harmer
4.224
270575GUS2 35KV
Solar/Wind Harmer
9.25
970217AG2-149 GEN
Solar/Wind Harmer
22.132
270044AE2-322 C
Solar/Wind Harmer
0.845
270404AC1-167 GEN
Solar/Wind Harmer
0.704
270258AD1-119 GEN
Solar/Wind Harmer
1.722
247604X1-042
Adder
0.255
24441205WTRV SLR C
Solar/Wind Harmer
0.081
270588AE1-091_GEN
Solar/Wind Harmer
6.538
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.753
945111AF1-176 GEN
Solar/Wind Harmer
3.155
24642205MAYFLWER
Adder
0.345
270191TR4_S_V150
Solar/Wind Harmer
1.62
270247TR4_N_V136
Solar/Wind Harmer
0.459
970031AG2-029 GEN
Solar/Wind Harmer
16.085
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.229
965021AG1-366 GEN
Solar/Wind Harmer
1.216
270485AE1-090_GEN
Solar/Wind Harmer
0.313
270043AE2-236 GEN
Solar/Wind Harmer
2.722
970349AG2-230 GEN
Solar/Wind Harmer
7.391
942871AE2-306 GEN
Solar/Wind Harmer
0.434
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
270535AF1-215 GEN1
Solar/Wind Harmer
2.12
972231SS25-0005
Solar/Wind Harmer
4.366
972181SS23-001
Solar/Wind Harmer
2.729
274752CRETE EC ;2U
Adder
2.249
274753CRETE EC ;3U
Adder
2.249
964401AG1-302 GEN
Solar/Wind Harmer
4.158
274724RIVER EC ;11
Adder
8.081
959141AF2-205 GEN
Solar/Wind Harmer
2.726
274802UNIV PARK;5U
Adder
2.619
274826FISK ;BP
Adder
4.91
274800UNIV PARK;3U
Adder
2.611
972038AH1-567 GEN2
Adder
0.163
276772AC2-154 GEN
Solar/Wind Harmer
1.247
276806AD2-047 C O1
Solar/Wind Harmer
4.783
970941AG2-585 GEN
Solar/Wind Harmer
5.588
274772LINCOLN ;3U
Adder
2.77
972228AH1-698 GEN2
Adder
1.651
274676JOLIET 29;8U
Adder
13.116
276897AD1-100 C
Solar/Wind Harmer
12.852
939351AE1-166 GEN
Solar/Wind Harmer
2.626
276893AG1-478 C
Solar/Wind Harmer
0.185
274730ELWOOD EC;6P
Adder
7.275
274734ELWOOD EC;8P
Adder
7.275
274736ELWOOD EC;9P
Adder
7.275
970707AG2-453 GEN
Solar/Wind Harmer
12.39
274729ELWOOD EC;1P
Adder
7.274
970513AG2-328 GEN
Solar/Wind Harmer
7.876
970517AG2-330 GEN
Solar/Wind Harmer
7.143
971617AH1-308 GEN
Solar/Wind Harmer
2.543
943121AE2-341 GEN
Solar/Wind Harmer
6.56
943591AF1-030 GEN
Solar/Wind Harmer
4.374
276694AA1-018 GEN2
Solar/Wind Harmer
2.759
274682WAUKEGAN ;7U
Adder
7.809
962511AG1-100 GEN
Solar/Wind Helper
0.337
203830AF1-094 GEN
Solar/Wind Helper
0.319
959441AF2-235 GEN
Solar/Wind Helper
0.145
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.636
24190002OREGON_ST1
50/50
3.617
24189802OREGON_CT1
50/50
2.744
23888802TROY G4
50/50
1.811
241996AE2-282_GEN
Solar/Wind Harmer
2.146
971677AH1-339 GEN
Solar/Wind Harmer
6.235
270007AE1-245 C
Solar/Wind Harmer
3.444
246938BC-WTG3
Solar/Wind Harmer
2.305
246937BC-WTG2
Solar/Wind Harmer
2.266
942801AE2-298 GEN
Solar/Wind Harmer
0.872
961051AF2-396 GEN
Solar/Wind Harmer
8.981
961051AF2-396 GEN
Solar/Wind Harmer
4.177
960981AF2-389 GEN
Solar/Wind Harmer
0.84
957891AF2-083 GEN
Solar/Wind Harmer
1.874
247620Y3-023
Adder
0.25
270216AD2-079_GEN
Solar/Wind Harmer
0.325
970611AG2-400 GEN
Solar/Wind Harmer
5.229
270526AF1-158 GEN
Solar/Wind Harmer
2.352
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.19
965791AG1-447 GEN
Solar/Wind Harmer
3.167
270224U2-072_GEN2
Solar/Wind Harmer
0.947
270227U2-072_GEN3
Solar/Wind Harmer
0.947
270228U2-072_GEN4
Solar/Wind Harmer
0.947
270231U2-072_GEN5
Solar/Wind Harmer
0.947
274808UNIV PK N;4U
Adder
2.265
274803UNIV PARK;6U
Adder
2.619
274888KELLY CRK;1U
Solar/Wind Harmer
2.639
274887GEN-1.85
Solar/Wind Harmer
2.383
276843GEN-1.7
Solar/Wind Harmer
0.256
958011AF2-095 GEN
Solar/Wind Harmer
6.438
274770LINCOLN ;1U
Adder
2.77
274771LINCOLN ;2U
Adder
2.77
972259AH1-714 GEN
Adder
8.465
942221AE2-234 GEN
Solar/Wind Harmer
0.325
274674JOLIET 9 ;6U
Adder
6.813
970321AG2-212 GEN
Solar/Wind Harmer
7.876
274847GR RIDGE ;BU
Solar/Wind Harmer
2.226
274695ROCKY RD ;2P
Adder
4.836
274693ROCKY RD ;1P
Adder
4.789
274697ROCKY RD ;3P
Adder
1.314
274696ROCKY RD ;4P
Adder
4.95
274683WAUKEGAN ;8U
Adder
9.148
274683WAUKEGAN ;8U
Adder
7.711
203947AF1-006 C
Solar/Wind Helper
0.375
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241967AE2-285_GEN
Solar/Wind Helper
0.335
241801AE1-079 GEN
Solar/Wind Helper
0.13
241985AE1-237 GEN
Solar/Wind Helper
0.13
962101AG1-054 GEN
Solar/Wind Helper
0.323
946381AF1-302 GEN
Solar/Wind Helper
0.104
958481AF2-142 GEN
Solar/Wind Harmer
1.857
24189902OREGON_CT2
50/50
2.688
23888702TROY G3
50/50
1.811
972253AH1-711 GEN
50/50
55.325
23856402BAYSG1
50/50
1.231
23920202STRYCT
50/50
1.893
241885AC2-103 GEN1
Solar/Wind Harmer
26.657
241858AF1-205_GEN
Solar/Wind Harmer
5.459
241808AF1-120 C
Solar/Wind Harmer
1.196
241840AF1-064_GEN
Solar/Wind Harmer
1.357
972301AH1-735 GEN
Adder
6.543
23906402RICHG1
Adder
1.309
23906502RICHG2&3
Adder
1.306
270361_3
Solar/Wind Harmer
7.852
960841AF2-375 GEN
Solar/Wind Harmer
3.479
970515AG2-329 GEN
Solar/Wind Harmer
10.037
247522W1-056 GEN
Solar/Wind Harmer
1.482
944231AF1-091 GEN
Solar/Wind Harmer
2.45
246936BC-WTG1
Solar/Wind Harmer
2.266
270489AE1-102 GEN1
Solar/Wind Harmer
0.753
965421AG1-410 GEN
Solar/Wind Harmer
17.213
270449AD2-020 GEN
Solar/Wind Harmer
1.599
943021AE2-325 GEN
Solar/Wind Harmer
2.077
24695305TIMB G C
Solar/Wind Harmer
3.074
945111AF1-176 GEN
Solar/Wind Harmer
9.954
270505AE1-170 C O1
Solar/Wind Harmer
8.362
24639705ELKHART HY
Adder
0.083
247521TR3_G114
Solar/Wind Harmer
1.816
270246TR4_N_V150
Solar/Wind Harmer
0.459
270063AE2-323 C
Solar/Wind Harmer
1.184
965011AG1-365 GEN
Solar/Wind Harmer
5.229
270462AD2-086
Solar/Wind Harmer
3.599
270223U2-072_GEN1
Solar/Wind Harmer
0.947
270578AF1-285 GEN2
Solar/Wind Harmer
0.579
270391AF1-285 GEN3
Solar/Wind Harmer
0.579
970373AG2-245 GEN
Solar/Wind Harmer
9.997
270055AF2-134 C O1
Solar/Wind Harmer
1.413
274751CRETE EC ;1U
Adder
2.249
274754CRETE EC ;4U
Adder
2.249
958381AF2-132 GEN
Solar/Wind Harmer
4.158
964861AG1-349 GEN
Solar/Wind Harmer
3.596
971917AH1-482 GEN
Solar/Wind Harmer
4.15
274723RIVER EC ;12
Adder
8.179
274812UNIV PK N;8U
Adder
2.275
276164X3-005 C
Solar/Wind Harmer
0.318
274801UNIV PARK;4U
Adder
2.611
276776AD2-060 GEN
Solar/Wind Harmer
0.189
940581AE2-045 GEN
Solar/Wind Harmer
4.559
972207SS24-0001
Solar/Wind Harmer
9.85
274773LINCOLN ;4U
Adder
2.77
274774LINCOLN ;5U
Adder
2.77
971605AH1-302 GEN
Solar/Wind Harmer
3.898
274676JOLIET 29;8U
Adder
13.602
941551AE2-152 GEN
Solar/Wind Harmer
2.009
274732ELWOOD EC;7P
Adder
7.275
274674JOLIET 9 ;6U
Adder
6.813
970245AG2-165 GEN
Solar/Wind Harmer
7.876
274871GR RIDGE ;2U
Solar/Wind Harmer
3.384
274745AC1-111 GEN9
Adder
2.446
276691AA1-018 GEN1
Solar/Wind Harmer
0.204
274682WAUKEGAN ;7U
Adder
7.809
274828WAUKEGAN ;BP
Adder
4.795
961971AG1-040 GEN
Solar/Wind Helper
0.329
203835AF1-098 GEN
Solar/Wind Helper
1.298
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
23867002DVBSG1
50/50
14.146
972211AH1-690 GEN
50/50
289.964
23888502TROY G1
50/50
1.811
23888602TROY G2
50/50
1.811
241886AC2-103 GEN2
Solar/Wind Harmer
26.657
970817AG2-515 GEN
Solar/Wind Harmer
15.186
945411AF1-206 GEN
Solar/Wind Harmer
8.014
945641AF1-229 GEN
Solar/Wind Harmer
3.431
270499AE1-146 GEN
Solar/Wind Harmer
2.196
971549AH1-272 GEN
Solar/Wind Harmer
12.968
270297AD1-101 GEN
Solar/Wind Harmer
1.865
247607V1-011 GEN
Solar/Wind Harmer
2.296
957201AF2-014 GEN
Solar/Wind Harmer
2.627
270435AC2-044 GEN
Solar/Wind Harmer
1.158
944161AF1-084 GEN
Solar/Wind Harmer
1.278
966831AG1-554 GEN
Solar/Wind Harmer
0.671
971989AH1-539 GEN
Solar/Wind Harmer
7.259
965041AG1-368 GEN
Solar/Wind Harmer
5.434
965051AG1-369 GEN
Solar/Wind Harmer
2.696
971771AH1-392 GEN
Solar/Wind Harmer
4.755
270302AB2-170 GEN
Solar/Wind Harmer
4.326
270317AD1-130_GEN
Solar/Wind Harmer
1.658
971769AH1-391 GEN
Solar/Wind Harmer
5.15
971567AH1-282 GEN
Solar/Wind Harmer
7.434
960681AF2-359 GEN
Solar/Wind Harmer
1.871
971347AH1-153 GEN
Solar/Wind Harmer
7.391
963791AG1-232 GEN
Solar/Wind Harmer
6.533
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
270536AF1-215 GEN2
Solar/Wind Harmer
2.12
270071AF1-092 GEN
Solar/Wind Harmer
6.896
274814UNIV PK N;0U
Adder
2.295
274807UNIV PK N;3U
Adder
2.29
274805UNIV PK N;1U
Adder
2.28
274811UNIV PK N;7U
Adder
2.275
958391AF2-133 GEN
Solar/Wind Harmer
4.12
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.48
960591AF2-350 GEN
Solar/Wind Harmer
4.471
274775LINCOLN ;6U
Adder
2.77
274776LINCOLN ;7U
Adder
2.77
274777LINCOLN ;8U
Adder
2.77
972227AH1-698 GEN1
Adder
1.163
274687WILL CNTY;4U
Adder
12.414
274687WILL CNTY;4U
Adder
12.414
274675JOLIET 29;7U
Adder
13.602
274675JOLIET 29;7U
Adder
13.116
274728ELWOOD EC;5P
Adder
7.275
274731ELWOOD EC;2P
Adder
7.274
274733ELWOOD EC;3P
Adder
7.274
274735ELWOOD EC;4P
Adder
7.274
970833AG2-524 GEN
Solar/Wind Harmer
3.844
970833AG2-524 GEN
Solar/Wind Harmer
1.788
274746AC1-111 G10
Adder
2.446
274744AC1-111 GEN8
Adder
2.446
270024AE2-089 GEN
Solar/Wind Harmer
2.053
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.244
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.854
991182J1586 G
External Queue
24.90056610107422
990527J1329
External Queue
1.8186211585998535
990142J1224
External Queue
13.294119834899902
991177J1571 G
External Queue
15.212156295776367
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.632
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.641
MECLTFEXP_MEC->PJM
CLTF
6.31
SIGELTFEXP_SIGE->PJM
CLTF
0.163
LAGNLTFEXP_LAGN->PJM
CLTF
4.814
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.113
TVALTFEXP_TVA->PJM
CLTF
2.181
CPLELTFEXP_CPLE->PJM
CLTF
0.312
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.518
NYPJM->LTFIMP_NY
CLTF
1.998
LGEELTFEXP_LGEE->PJM
CLTF
1.955
WECLTFEXP_WEC->PJM
CLTF
1.62
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-3_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.16 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2556.01
MW Contribution:15.99
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.596
23888702TROY G3
50/50
1.764
972253AH1-711 GEN
50/50
53.875
23856402BAYSG1
50/50
1.286
23920202STRYCT
50/50
1.905
241885AC2-103 GEN1
Solar/Wind Harmer
25.888
241858AF1-205_GEN
Solar/Wind Harmer
5.501
241808AF1-120 C
Solar/Wind Harmer
1.204
241840AF1-064_GEN
Solar/Wind Harmer
1.392
972301AH1-735 GEN
Adder
6.601
23906402RICHG1
Adder
1.32
23906502RICHG2&3
Adder
1.318
270361_3
Solar/Wind Harmer
8.502
960841AF2-375 GEN
Solar/Wind Harmer
3.755
241807AE2-176_GEN
Solar/Wind Harmer
2.785
247522W1-056 GEN
Solar/Wind Harmer
1.573
970515AG2-329 GEN
Solar/Wind Harmer
10.138
944231AF1-091 GEN
Solar/Wind Harmer
2.455
246936BC-WTG1
Solar/Wind Harmer
2.271
270489AE1-102 GEN1
Solar/Wind Harmer
0.755
965421AG1-410 GEN
Solar/Wind Harmer
17.247
270449AD2-020 GEN
Solar/Wind Harmer
1.583
943021AE2-325 GEN
Solar/Wind Harmer
2.057
270428AC2-015 C
Solar/Wind Harmer
3.089
24695305TIMB G C
Solar/Wind Harmer
3.089
945111AF1-176 GEN
Solar/Wind Harmer
9.863
270505AE1-170 C O1
Solar/Wind Harmer
8.284
247521TR3_G114
Solar/Wind Harmer
1.822
270246TR4_N_V150
Solar/Wind Harmer
0.461
24639705ELKHART HY
Adder
0.082
24190002OREGON_ST1
50/50
3.493
24189802OREGON_CT1
50/50
2.65
23929302BS-PKR
50/50
2.264
241832AE2-181_GEN
Solar/Wind Harmer
1.957
958321AF2-126 GEN
Solar/Wind Harmer
1.492
23906502RICHG2&3
Adder
1.318
270575GUS2 35KV
Solar/Wind Harmer
10.016
270541AE2-072 C
Solar/Wind Harmer
4.321
970217AG2-149 GEN
Solar/Wind Harmer
22.356
270044AE2-322 C
Solar/Wind Harmer
0.852
270404AC1-167 GEN
Solar/Wind Harmer
0.709
270258AD1-119 GEN
Solar/Wind Harmer
1.735
270588AE1-091_GEN
Solar/Wind Harmer
6.791
247604X1-042
Adder
0.252
24441205WTRV SLR C
Solar/Wind Harmer
0.08
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270491AE1-102 GEN2
Solar/Wind Harmer
0.755
945111AF1-176 GEN
Solar/Wind Harmer
3.126
270191TR4_S_V150
Solar/Wind Harmer
1.626
270247TR4_N_V136
Solar/Wind Harmer
0.461
24642205MAYFLWER
Adder
0.342
970031AG2-029 GEN
Solar/Wind Harmer
15.991
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.223
965021AG1-366 GEN
Solar/Wind Harmer
1.215
270485AE1-090_GEN
Solar/Wind Harmer
0.315
270043AE2-236 GEN
Solar/Wind Harmer
2.712
970349AG2-230 GEN
Solar/Wind Harmer
7.336
942871AE2-306 GEN
Solar/Wind Harmer
0.438
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270377AD1-106 GEN
Solar/Wind Harmer
2.871
270535AF1-215 GEN1
Solar/Wind Harmer
2.105
972231SS25-0005
Solar/Wind Harmer
4.336
972181SS23-001
Solar/Wind Harmer
2.71
274752CRETE EC ;2U
Adder
2.233
274753CRETE EC ;3U
Adder
2.233
964401AG1-302 GEN
Solar/Wind Harmer
4.13
274724RIVER EC ;11
Adder
8.026
959141AF2-205 GEN
Solar/Wind Harmer
2.708
274802UNIV PARK;5U
Adder
2.602
274826FISK ;BP
Adder
4.877
274800UNIV PARK;3U
Adder
2.593
972038AH1-567 GEN2
Adder
0.162
276772AC2-154 GEN
Solar/Wind Harmer
1.239
276806AD2-047 C O1
Solar/Wind Harmer
4.751
970941AG2-585 GEN
Solar/Wind Harmer
5.551
274772LINCOLN ;3U
Adder
2.752
972228AH1-698 GEN2
Adder
1.64
274676JOLIET 29;8U
Adder
13.03
276897AD1-100 C
Solar/Wind Harmer
12.768
939351AE1-166 GEN
Solar/Wind Harmer
2.609
276893AG1-478 C
Solar/Wind Harmer
0.184
274729ELWOOD EC;1P
Adder
7.227
274730ELWOOD EC;6P
Adder
7.227
274734ELWOOD EC;8P
Adder
7.227
274736ELWOOD EC;9P
Adder
7.227
970707AG2-453 GEN
Solar/Wind Harmer
12.309
970513AG2-328 GEN
Solar/Wind Harmer
7.828
970517AG2-330 GEN
Solar/Wind Harmer
7.1
971617AH1-308 GEN
Solar/Wind Harmer
2.543
274682WAUKEGAN ;7U
Adder
7.759
962511AG1-100 GEN
Solar/Wind Helper
0.34
203830AF1-094 GEN
Solar/Wind Helper
0.322
959441AF2-235 GEN
Solar/Wind Helper
0.146
254305AE2-115 C
Solar/Wind Helper
0.112
20334926Z1-069 C
Solar/Wind Helper
0.642
943121AE2-341 GEN
Solar/Wind Harmer
3.856
943591AF1-030 GEN
Solar/Wind Harmer
2.571
23888802TROY G4
50/50
1.764
241996AE2-282_GEN
Solar/Wind Harmer
2.159
971677AH1-339 GEN
Solar/Wind Harmer
6.666
270007AE1-245 C
Solar/Wind Harmer
3.473
942801AE2-298 GEN
Solar/Wind Harmer
0.88
246938BC-WTG3
Solar/Wind Harmer
2.311
246937BC-WTG2
Solar/Wind Harmer
2.271
961051AF2-396 GEN
Solar/Wind Harmer
8.895
961051AF2-396 GEN
Solar/Wind Harmer
4.137
960981AF2-389 GEN
Solar/Wind Harmer
0.832
957891AF2-083 GEN
Solar/Wind Harmer
1.857
247620Y3-023
Adder
0.249
270216AD2-079_GEN
Solar/Wind Harmer
0.322
970611AG2-400 GEN
Solar/Wind Harmer
5.223
270526AF1-158 GEN
Solar/Wind Harmer
2.332
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.141
965791AG1-447 GEN
Solar/Wind Harmer
3.142
270224U2-072_GEN2
Solar/Wind Harmer
0.954
270227U2-072_GEN3
Solar/Wind Harmer
0.954
270228U2-072_GEN4
Solar/Wind Harmer
0.954
270231U2-072_GEN5
Solar/Wind Harmer
0.954
971231AH1-075 GEN
Solar/Wind Harmer
0.372
274808UNIV PK N;4U
Adder
2.25
274803UNIV PARK;6U
Adder
2.602
274888KELLY CRK;1U
Solar/Wind Harmer
2.622
274887GEN-1.85
Solar/Wind Harmer
2.367
276843GEN-1.7
Solar/Wind Harmer
0.255
958011AF2-095 GEN
Solar/Wind Harmer
6.395
274770LINCOLN ;1U
Adder
2.752
274771LINCOLN ;2U
Adder
2.752
942221AE2-234 GEN
Solar/Wind Harmer
0.324
972259AH1-714 GEN
Adder
8.409
274674JOLIET 9 ;6U
Adder
6.769
970321AG2-212 GEN
Solar/Wind Harmer
7.828
274847GR RIDGE ;BU
Solar/Wind Harmer
2.211
274696ROCKY RD ;4P
Adder
4.919
274695ROCKY RD ;2P
Adder
4.805
274693ROCKY RD ;1P
Adder
4.758
274697ROCKY RD ;3P
Adder
1.305
274683WAUKEGAN ;8U
Adder
9.089
274683WAUKEGAN ;8U
Adder
7.662
203947AF1-006 C
Solar/Wind Helper
0.379
203980AG1-197 GEN
Solar/Wind Helper
0.248
203979AG1-198 GEN
Solar/Wind Helper
0.193
241967AE2-285_GEN
Solar/Wind Helper
0.337
241801AE1-079 GEN
Solar/Wind Helper
0.131
241985AE1-237 GEN
Solar/Wind Helper
0.131
962101AG1-054 GEN
Solar/Wind Helper
0.326
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
270063AE2-323 C
Solar/Wind Harmer
1.178
965011AG1-365 GEN
Solar/Wind Harmer
5.223
270462AD2-086
Solar/Wind Harmer
3.624
270223U2-072_GEN1
Solar/Wind Harmer
0.954
270578AF1-285 GEN2
Solar/Wind Harmer
0.583
270391AF1-285 GEN3
Solar/Wind Harmer
0.583
970373AG2-245 GEN
Solar/Wind Harmer
9.924
270055AF2-134 C O1
Solar/Wind Harmer
1.403
274751CRETE EC ;1U
Adder
2.233
274754CRETE EC ;4U
Adder
2.233
958381AF2-132 GEN
Solar/Wind Harmer
4.13
964861AG1-349 GEN
Solar/Wind Harmer
3.572
971917AH1-482 GEN
Solar/Wind Harmer
4.122
274723RIVER EC ;12
Adder
8.123
274812UNIV PK N;8U
Adder
2.26
276164X3-005 C
Solar/Wind Harmer
0.316
274801UNIV PARK;4U
Adder
2.593
940581AE2-045 GEN
Solar/Wind Harmer
4.53
276776AD2-060 GEN
Solar/Wind Harmer
0.188
971605AH1-302 GEN
Solar/Wind Harmer
3.873
972207SS24-0001
Solar/Wind Harmer
9.786
274773LINCOLN ;4U
Adder
2.752
274774LINCOLN ;5U
Adder
2.752
274676JOLIET 29;8U
Adder
13.513
941551AE2-152 GEN
Solar/Wind Harmer
1.995
274732ELWOOD EC;7P
Adder
7.227
274674JOLIET 9 ;6U
Adder
6.769
970245AG2-165 GEN
Solar/Wind Harmer
7.828
274871GR RIDGE ;2U
Solar/Wind Harmer
3.362
970905AG2-564 GEN
Solar/Wind Harmer
2.184
274745AC1-111 GEN9
Adder
2.43
274682WAUKEGAN ;7U
Adder
7.759
23867002DVBSG1
50/50
13.062
972211AH1-690 GEN
50/50
279.989
23888502TROY G1
50/50
1.764
23888602TROY G2
50/50
1.764
241886AC2-103 GEN2
Solar/Wind Harmer
25.888
970817AG2-515 GEN
Solar/Wind Harmer
14.956
945411AF1-206 GEN
Solar/Wind Harmer
8.063
945641AF1-229 GEN
Solar/Wind Harmer
3.434
270499AE1-146 GEN
Solar/Wind Harmer
2.36
971549AH1-272 GEN
Solar/Wind Harmer
12.795
270297AD1-101 GEN
Solar/Wind Harmer
1.901
966831AG1-554 GEN
Solar/Wind Harmer
0.706
971989AH1-539 GEN
Solar/Wind Harmer
7.631
247607V1-011 GEN
Solar/Wind Harmer
2.315
957201AF2-014 GEN
Solar/Wind Harmer
2.633
270435AC2-044 GEN
Solar/Wind Harmer
1.161
944161AF1-084 GEN
Solar/Wind Harmer
1.265
965041AG1-368 GEN
Solar/Wind Harmer
5.449
965051AG1-369 GEN
Solar/Wind Harmer
2.706
971771AH1-392 GEN
Solar/Wind Harmer
4.715
270302AB2-170 GEN
Solar/Wind Harmer
4.356
270317AD1-130_GEN
Solar/Wind Harmer
1.67
971769AH1-391 GEN
Solar/Wind Harmer
5.107
971567AH1-282 GEN
Solar/Wind Harmer
7.577
960681AF2-359 GEN
Solar/Wind Harmer
1.856
971347AH1-153 GEN
Solar/Wind Harmer
7.336
963791AG1-232 GEN
Solar/Wind Harmer
6.532
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.105
270071AF1-092 GEN
Solar/Wind Harmer
6.875
274814UNIV PK N;0U
Adder
2.28
274807UNIV PK N;3U
Adder
2.275
274805UNIV PK N;1U
Adder
2.265
274811UNIV PK N;7U
Adder
2.26
958391AF2-133 GEN
Solar/Wind Harmer
4.092
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.457
960591AF2-350 GEN
Solar/Wind Harmer
4.441
274775LINCOLN ;6U
Adder
2.752
274776LINCOLN ;7U
Adder
2.752
274777LINCOLN ;8U
Adder
2.752
972227AH1-698 GEN1
Adder
1.155
274687WILL CNTY;4U
Adder
12.332
274687WILL CNTY;4U
Adder
12.332
274675JOLIET 29;7U
Adder
13.513
274675JOLIET 29;7U
Adder
13.03
274731ELWOOD EC;2P
Adder
7.227
274733ELWOOD EC;3P
Adder
7.227
274735ELWOOD EC;4P
Adder
7.227
274728ELWOOD EC;5P
Adder
7.227
270024AE2-089 GEN
Solar/Wind Harmer
2.053
970833AG2-524 GEN
Solar/Wind Harmer
3.819
970833AG2-524 GEN
Solar/Wind Harmer
1.776
274746AC1-111 G10
Adder
2.43
274744AC1-111 GEN8
Adder
2.43
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.112
203846AF2-130 C
Solar/Wind Helper
0.247
241997AF1-093 GEN
Solar/Wind Helper
0.13
203804AE2-113_GEN
Solar/Wind Helper
0.862
274828WAUKEGAN ;BP
Adder
4.764
961971AG1-040 GEN
Solar/Wind Helper
0.333
203835AF1-098 GEN
Solar/Wind Helper
1.311
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.13
254303AC2-168 GEN
Solar/Wind Helper
0.075
991182J1586 G
External Queue
24.279396057128906
990527J1329
External Queue
1.7751743793487549
990142J1224
External Queue
12.976524353027344
991177J1571 G
External Queue
14.956707954406738
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.626
MECLTFEXP_MEC->PJM
CLTF
6.275
SIGELTFEXP_SIGE->PJM
CLTF
0.163
LAGNLTFEXP_LAGN->PJM
CLTF
4.798
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.107
TVALTFEXP_TVA->PJM
CLTF
2.176
CPLELTFEXP_CPLE->PJM
CLTF
0.309
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.387
NYPJM->LTFIMP_NY
CLTF
2.013
LGEELTFEXP_LGEE->PJM
CLTF
1.955
WECLTFEXP_WEC->PJM
CLTF
1.61
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.156

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010B1_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010B1_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.11 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2537.18
MW Contribution:15.88
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.585
24189802OREGON_CT1
50/50
2.72
23888802TROY G4
50/50
1.793
241996AE2-282_GEN
Solar/Wind Harmer
2.116
971677AH1-339 GEN
Solar/Wind Harmer
6.097
270007AE1-245 C
Solar/Wind Harmer
3.395
246938BC-WTG3
Solar/Wind Harmer
2.274
246937BC-WTG2
Solar/Wind Harmer
2.236
942801AE2-298 GEN
Solar/Wind Harmer
0.86
961051AF2-396 GEN
Solar/Wind Harmer
8.873
961051AF2-396 GEN
Solar/Wind Harmer
4.127
960981AF2-389 GEN
Solar/Wind Harmer
0.83
957891AF2-083 GEN
Solar/Wind Harmer
1.852
247620Y3-023
Adder
0.247
270216AD2-079_GEN
Solar/Wind Harmer
0.321
970611AG2-400 GEN
Solar/Wind Harmer
5.161
270526AF1-158 GEN
Solar/Wind Harmer
2.323
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.114
965791AG1-447 GEN
Solar/Wind Harmer
3.128
270224U2-072_GEN2
Solar/Wind Harmer
0.933
270227U2-072_GEN3
Solar/Wind Harmer
0.933
270228U2-072_GEN4
Solar/Wind Harmer
0.933
270231U2-072_GEN5
Solar/Wind Harmer
0.933
274808UNIV PK N;4U
Adder
2.237
274803UNIV PARK;6U
Adder
2.587
274888KELLY CRK;1U
Solar/Wind Harmer
2.607
274887GEN-1.85
Solar/Wind Harmer
2.354
276843GEN-1.7
Solar/Wind Harmer
0.253
23867002DVBSG1
50/50
14.099
972211AH1-690 GEN
50/50
287.424
23888502TROY G1
50/50
1.793
23888602TROY G2
50/50
1.793
241886AC2-103 GEN2
Solar/Wind Harmer
26.725
958011AF2-095 GEN
Solar/Wind Harmer
6.358
274770LINCOLN ;1U
Adder
2.736
274771LINCOLN ;2U
Adder
2.736
972259AH1-714 GEN
Adder
8.36
942221AE2-234 GEN
Solar/Wind Harmer
0.32
274674JOLIET 9 ;6U
Adder
6.729
970321AG2-212 GEN
Solar/Wind Harmer
7.778
274847GR RIDGE ;BU
Solar/Wind Harmer
2.198
203947AF1-006 C
Solar/Wind Helper
0.37
203980AG1-197 GEN
Solar/Wind Helper
0.242
203979AG1-198 GEN
Solar/Wind Helper
0.188
241967AE2-285_GEN
Solar/Wind Helper
0.33
241801AE1-079 GEN
Solar/Wind Helper
0.128
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.319
946381AF1-302 GEN
Solar/Wind Helper
0.102
958481AF2-142 GEN
Solar/Wind Harmer
6.372
970817AG2-515 GEN
Solar/Wind Harmer
15.015
945411AF1-206 GEN
Solar/Wind Harmer
7.902
945641AF1-229 GEN
Solar/Wind Harmer
3.386
270499AE1-146 GEN
Solar/Wind Harmer
2.146
971549AH1-272 GEN
Solar/Wind Harmer
12.819
270297AD1-101 GEN
Solar/Wind Harmer
1.836
247607V1-011 GEN
Solar/Wind Harmer
2.263
944161AF1-084 GEN
Solar/Wind Harmer
1.263
957201AF2-014 GEN
Solar/Wind Harmer
2.591
270435AC2-044 GEN
Solar/Wind Harmer
1.143
966831AG1-554 GEN
Solar/Wind Harmer
0.658
971989AH1-539 GEN
Solar/Wind Harmer
7.115
965041AG1-368 GEN
Solar/Wind Harmer
5.36
965051AG1-369 GEN
Solar/Wind Harmer
2.659
971771AH1-392 GEN
Solar/Wind Harmer
4.698
270302AB2-170 GEN
Solar/Wind Harmer
4.265
270317AD1-130_GEN
Solar/Wind Harmer
1.635
971769AH1-391 GEN
Solar/Wind Harmer
5.087
960681AF2-359 GEN
Solar/Wind Harmer
1.848
971567AH1-282 GEN
Solar/Wind Harmer
7.317
971347AH1-153 GEN
Solar/Wind Harmer
7.301
963791AG1-232 GEN
Solar/Wind Harmer
6.446
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
2.094
270071AF1-092 GEN
Solar/Wind Harmer
6.808
274814UNIV PK N;0U
Adder
2.267
274807UNIV PK N;3U
Adder
2.262
274805UNIV PK N;1U
Adder
2.252
274811UNIV PK N;7U
Adder
2.247
958391AF2-133 GEN
Solar/Wind Harmer
4.069
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.437
960591AF2-350 GEN
Solar/Wind Harmer
4.415
274775LINCOLN ;6U
Adder
2.736
274776LINCOLN ;7U
Adder
2.736
274777LINCOLN ;8U
Adder
2.736
972227AH1-698 GEN1
Adder
1.148
274687WILL CNTY;4U
Adder
12.26
274687WILL CNTY;4U
Adder
12.26
274675JOLIET 29;7U
Adder
13.434
274675JOLIET 29;7U
Adder
12.954
274731ELWOOD EC;2P
Adder
7.184
274733ELWOOD EC;3P
Adder
7.184
274735ELWOOD EC;4P
Adder
7.184
274728ELWOOD EC;5P
Adder
7.185
970833AG2-524 GEN
Solar/Wind Harmer
3.797
970833AG2-524 GEN
Solar/Wind Harmer
1.766
274746AC1-111 G10
Adder
2.415
274744AC1-111 GEN8
Adder
2.415
241982AE2-343 S C
Solar/Wind Helper
0.115
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.241
241997AF1-093 GEN
Solar/Wind Helper
0.127
203804AE2-113_GEN
Solar/Wind Helper
0.842
24189902OREGON_CT2
50/50
2.665
23888702TROY G3
50/50
1.793
972253AH1-711 GEN
50/50
54.781
23856402BAYSG1
50/50
1.208
23920202STRYCT
50/50
1.866
241885AC2-103 GEN1
Solar/Wind Harmer
26.725
241858AF1-205_GEN
Solar/Wind Harmer
5.381
241808AF1-120 C
Solar/Wind Harmer
1.18
241840AF1-064_GEN
Solar/Wind Harmer
1.335
972301AH1-735 GEN
Adder
6.449
23906402RICHG1
Adder
1.29
23906502RICHG2&3
Adder
1.287
270361_3
Solar/Wind Harmer
7.665
960841AF2-375 GEN
Solar/Wind Harmer
3.397
970515AG2-329 GEN
Solar/Wind Harmer
9.891
247522W1-056 GEN
Solar/Wind Harmer
1.451
944231AF1-091 GEN
Solar/Wind Harmer
2.417
246936BC-WTG1
Solar/Wind Harmer
2.236
270489AE1-102 GEN1
Solar/Wind Harmer
0.743
965421AG1-410 GEN
Solar/Wind Harmer
16.981
270449AD2-020 GEN
Solar/Wind Harmer
1.58
943021AE2-325 GEN
Solar/Wind Harmer
2.053
945111AF1-176 GEN
Solar/Wind Harmer
9.834
270505AE1-170 C O1
Solar/Wind Harmer
8.262
24695305TIMB G C
Solar/Wind Harmer
3.031
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
1.791
270246TR4_N_V150
Solar/Wind Harmer
0.453
270063AE2-323 C
Solar/Wind Harmer
1.169
965011AG1-365 GEN
Solar/Wind Harmer
5.161
270462AD2-086
Solar/Wind Harmer
3.548
270223U2-072_GEN1
Solar/Wind Harmer
0.933
270578AF1-285 GEN2
Solar/Wind Harmer
0.571
270391AF1-285 GEN3
Solar/Wind Harmer
0.571
970373AG2-245 GEN
Solar/Wind Harmer
9.875
270055AF2-134 C O1
Solar/Wind Harmer
1.396
274751CRETE EC ;1U
Adder
2.221
274754CRETE EC ;4U
Adder
2.221
958381AF2-132 GEN
Solar/Wind Harmer
4.107
964861AG1-349 GEN
Solar/Wind Harmer
3.552
971917AH1-482 GEN
Solar/Wind Harmer
4.099
274723RIVER EC ;12
Adder
8.078
274812UNIV PK N;8U
Adder
2.247
276164X3-005 C
Solar/Wind Harmer
0.314
274801UNIV PARK;4U
Adder
2.578
276776AD2-060 GEN
Solar/Wind Harmer
0.187
940581AE2-045 GEN
Solar/Wind Harmer
4.502
971605AH1-302 GEN
Solar/Wind Harmer
3.85
972207SS24-0001
Solar/Wind Harmer
9.728
274773LINCOLN ;4U
Adder
2.736
274774LINCOLN ;5U
Adder
2.736
274676JOLIET 29;8U
Adder
13.434
941551AE2-152 GEN
Solar/Wind Harmer
1.984
274732ELWOOD EC;7P
Adder
7.185
274674JOLIET 9 ;6U
Adder
6.729
970245AG2-165 GEN
Solar/Wind Harmer
7.778
274871GR RIDGE ;2U
Solar/Wind Harmer
3.342
274745AC1-111 GEN9
Adder
2.415
276691AA1-018 GEN1
Solar/Wind Harmer
0.201
961971AG1-040 GEN
Solar/Wind Helper
0.325
203835AF1-098 GEN
Solar/Wind Helper
1.28
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.127
241807AE2-176_GEN
Solar/Wind Helper
0.767
254303AC2-168 GEN
Solar/Wind Helper
0.074
23929302BS-PKR
50/50
2.125
241832AE2-181_GEN
Solar/Wind Harmer
1.919
958321AF2-126 GEN
Solar/Wind Harmer
1.431
23906502RICHG2&3
Adder
1.287
270541AE2-072 C
Solar/Wind Harmer
4.156
270575GUS2 35KV
Solar/Wind Harmer
9.03
970217AG2-149 GEN
Solar/Wind Harmer
21.811
270044AE2-322 C
Solar/Wind Harmer
0.833
270404AC1-167 GEN
Solar/Wind Harmer
0.694
270258AD1-119 GEN
Solar/Wind Harmer
1.698
247604X1-042
Adder
0.252
24441205WTRV SLR C
Solar/Wind Harmer
0.08
270588AE1-091_GEN
Solar/Wind Harmer
6.42
958091AF2-103 GEN
Solar/Wind Harmer
0.092
270491AE1-102 GEN2
Solar/Wind Harmer
0.743
945111AF1-176 GEN
Solar/Wind Harmer
3.117
24642205MAYFLWER
Adder
0.34
270191TR4_S_V150
Solar/Wind Harmer
1.598
270247TR4_N_V136
Solar/Wind Harmer
0.453
247643Z2-116 C
Solar/Wind Harmer
0.037
970031AG2-029 GEN
Solar/Wind Harmer
15.885
959331AF2-224 GEN
Solar/Wind Harmer
5.161
965021AG1-366 GEN
Solar/Wind Harmer
1.2
270485AE1-090_GEN
Solar/Wind Harmer
0.308
270043AE2-236 GEN
Solar/Wind Harmer
2.687
970349AG2-230 GEN
Solar/Wind Harmer
7.301
942871AE2-306 GEN
Solar/Wind Harmer
0.428
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
2.094
972231SS25-0005
Solar/Wind Harmer
4.312
972181SS23-001
Solar/Wind Harmer
2.695
274752CRETE EC ;2U
Adder
2.221
274753CRETE EC ;3U
Adder
2.221
964401AG1-302 GEN
Solar/Wind Harmer
4.107
274724RIVER EC ;11
Adder
7.981
959141AF2-205 GEN
Solar/Wind Harmer
2.692
274802UNIV PARK;5U
Adder
2.587
274826FISK ;BP
Adder
4.849
274800UNIV PARK;3U
Adder
2.578
972038AH1-567 GEN2
Adder
0.161
276772AC2-154 GEN
Solar/Wind Harmer
1.231
276806AD2-047 C O1
Solar/Wind Harmer
4.724
970941AG2-585 GEN
Solar/Wind Harmer
5.519
274772LINCOLN ;3U
Adder
2.736
972228AH1-698 GEN2
Adder
1.631
274676JOLIET 29;8U
Adder
12.954
276897AD1-100 C
Solar/Wind Harmer
12.693
939351AE1-166 GEN
Solar/Wind Harmer
2.593
276893AG1-478 C
Solar/Wind Harmer
0.183
274729ELWOOD EC;1P
Adder
7.184
274730ELWOOD EC;6P
Adder
7.185
274734ELWOOD EC;8P
Adder
7.185
274736ELWOOD EC;9P
Adder
7.185
970707AG2-453 GEN
Solar/Wind Harmer
12.236
970513AG2-328 GEN
Solar/Wind Harmer
7.778
970517AG2-330 GEN
Solar/Wind Harmer
7.054
943121AE2-341 GEN
Solar/Wind Harmer
6.479
943591AF1-030 GEN
Solar/Wind Harmer
4.319
276694AA1-018 GEN2
Solar/Wind Harmer
2.725
962511AG1-100 GEN
Solar/Wind Helper
0.332
203830AF1-094 GEN
Solar/Wind Helper
0.314
959441AF2-235 GEN
Solar/Wind Helper
0.143
254305AE2-115 C
Solar/Wind Helper
0.109
991182J1586 G
External Queue
24.65229034423828
990527J1329
External Queue
1.8002409934997559
990142J1224
External Queue
13.159761428833008
991177J1571 G
External Queue
15.044508934020996
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.578
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.528
MECLTFEXP_MEC->PJM
CLTF
6.231
SIGELTFEXP_SIGE->PJM
CLTF
0.161
LAGNLTFEXP_LAGN->PJM
CLTF
4.752
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.085
TVALTFEXP_TVA->PJM
CLTF
2.153
CPLELTFEXP_CPLE->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.025
NYPJM->LTFIMP_NY
CLTF
1.97
LGEELTFEXP_LGEE->PJM
CLTF
1.929
WECLTFEXP_WEC->PJM
CLTF
1.6
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-810_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-810_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.08 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2212.91
MW Contribution:2.4
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
14.099
972211AH1-690 GEN
50/50
287.424
23888502TROY G1
50/50
1.793
23888602TROY G2
50/50
1.793
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
10.476
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.027
971549AH1-272 GEN
Solar/Wind Harmer
9.983
270297AD1-101 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.505
971619AH1-309 GEN
Solar/Wind Harmer
1.729
971989AH1-539 GEN
Solar/Wind Harmer
1.655
965041AG1-368 GEN
Solar/Wind Harmer
3.74
965051AG1-369 GEN
Solar/Wind Harmer
1.855
971771AH1-392 GEN
Solar/Wind Harmer
3.641
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.5
971769AH1-391 GEN
Solar/Wind Harmer
3.963
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971567AH1-282 GEN
Solar/Wind Harmer
5.105
971347AH1-153 GEN
Solar/Wind Harmer
5.093
963791AG1-232 GEN
Solar/Wind Harmer
4.498
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
24190002OREGON_ST1
50/50
3.585
24189802OREGON_CT1
50/50
2.72
23888802TROY G4
50/50
1.793
241996AE2-282_GEN
Solar/Wind Harmer
0.005
971677AH1-339 GEN
Solar/Wind Harmer
0.599
970621AG2-405 GEN
Solar/Wind Harmer
0.843
970623AG2-406 GEN
Solar/Wind Harmer
0.778
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.144
246937BC-WTG2
Solar/Wind Harmer
0.162
961051AF2-396 GEN
Solar/Wind Harmer
7.8
961051AF2-396 GEN
Solar/Wind Harmer
5.2
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.247
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.601
970627AG2-408 GEN
Solar/Wind Harmer
1.08
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.266
965791AG1-447 GEN
Solar/Wind Harmer
3.128
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.237
274803UNIV PARK;6U
Adder
2.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.181
24189902OREGON_CT2
50/50
2.665
23888702TROY G3
50/50
1.793
972253AH1-711 GEN
50/50
54.781
23856402BAYSG1
50/50
1.208
23920202STRYCT
50/50
1.866
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
3.754
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.449
23906402RICHG1
Adder
1.29
23906502RICHG2&3
Adder
1.287
270361_3
Solar/Wind Harmer
4.19
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.364
247522W1-056 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.193
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.518
965421AG1-410 GEN
Solar/Wind Harmer
11.847
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.053
945111AF1-176 GEN
Solar/Wind Harmer
6.861
270505AE1-170 C O1
Solar/Wind Harmer
4.035
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
0.135
270246TR4_N_V150
Solar/Wind Harmer
0.024
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.601
270462AD2-086
Solar/Wind Harmer
0.007
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.889
270055AF2-134 C O1
Solar/Wind Harmer
0.002
274751CRETE EC ;1U
Adder
3.744
274754CRETE EC ;4U
Adder
3.744
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.099
274723RIVER EC ;12
Adder
8.078
274812UNIV PK N;8U
Adder
2.247
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.578
276776AD2-060 GEN
Solar/Wind Harmer
0.322
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.85
274773LINCOLN ;4U
Adder
3.725
274774LINCOLN ;5U
Adder
3.725
274676JOLIET 29;8U
Adder
13.434
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.185
274674JOLIET 9 ;6U
Adder
6.729
970245AG2-165 GEN
Solar/Wind Harmer
1.317
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.415
276691AA1-018 GEN1
Solar/Wind Harmer
0.365
961971AG1-040 GEN
Solar/Wind Helper
0.325
203835AF1-098 GEN
Solar/Wind Helper
1.28
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.127
241807AE2-176_GEN
Solar/Wind Helper
0.767
254303AC2-168 GEN
Solar/Wind Helper
0.074
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.069
274814UNIV PK N;0U
Adder
2.267
274807UNIV PK N;3U
Adder
2.262
274805UNIV PK N;1U
Adder
2.252
274811UNIV PK N;7U
Adder
2.247
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.437
960591AF2-350 GEN
Solar/Wind Harmer
3.081
971611AH1-305 GEN
Solar/Wind Harmer
1.834
274775LINCOLN ;6U
Adder
3.725
274776LINCOLN ;7U
Adder
3.725
274777LINCOLN ;8U
Adder
3.725
972227AH1-698 GEN1
Adder
1.148
274687WILL CNTY;4U
Adder
12.26
274687WILL CNTY;4U
Adder
12.26
274675JOLIET 29;7U
Adder
13.434
274675JOLIET 29;7U
Adder
12.954
274731ELWOOD EC;2P
Adder
7.184
274733ELWOOD EC;3P
Adder
7.184
274735ELWOOD EC;4P
Adder
7.184
274728ELWOOD EC;5P
Adder
7.185
970833AG2-524 GEN
Solar/Wind Harmer
3.337
970833AG2-524 GEN
Solar/Wind Harmer
2.225
274746AC1-111 G10
Adder
2.415
274744AC1-111 GEN8
Adder
2.415
270024AE2-089 GEN
Solar/Wind Harmer
0.003
241982AE2-343 S C
Solar/Wind Helper
0.115
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.241
241997AF1-093 GEN
Solar/Wind Helper
0.127
203804AE2-113_GEN
Solar/Wind Helper
0.842
23929302BS-PKR
50/50
2.125
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.109
23906502RICHG2&3
Adder
1.287
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.19
970217AG2-149 GEN
Solar/Wind Harmer
4.121
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.252
24441205WTRV SLR C
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
3.185
270491AE1-102 GEN2
Solar/Wind Harmer
0.518
945111AF1-176 GEN
Solar/Wind Harmer
3.117
24642205MAYFLWER
Adder
0.34
270191TR4_S_V150
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.024
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.401
959331AF2-224 GEN
Solar/Wind Harmer
2.52
965021AG1-366 GEN
Solar/Wind Harmer
1.2
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.187
970349AG2-230 GEN
Solar/Wind Harmer
5.093
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.744
274753CRETE EC ;3U
Adder
3.744
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
7.981
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.587
274826FISK ;BP
Adder
4.849
274800UNIV PARK;3U
Adder
2.578
972038AH1-567 GEN2
Adder
0.161
276806AD2-047 C O1
Solar/Wind Harmer
1.746
970941AG2-585 GEN
Solar/Wind Harmer
3.851
274772LINCOLN ;3U
Adder
3.725
972228AH1-698 GEN2
Adder
1.631
274676JOLIET 29;8U
Adder
12.954
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.184
274730ELWOOD EC;6P
Adder
7.185
274734ELWOOD EC;8P
Adder
7.185
274736ELWOOD EC;9P
Adder
7.185
970707AG2-453 GEN
Solar/Wind Harmer
9.96
970513AG2-328 GEN
Solar/Wind Harmer
1.317
970517AG2-330 GEN
Solar/Wind Harmer
7.901
943121AE2-341 GEN
Solar/Wind Harmer
5.053
943591AF1-030 GEN
Solar/Wind Harmer
3.36
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.509
962511AG1-100 GEN
Solar/Wind Helper
0.332
203830AF1-094 GEN
Solar/Wind Helper
0.314
959441AF2-235 GEN
Solar/Wind Helper
0.143
254305AE2-115 C
Solar/Wind Helper
0.109
274887GEN-1.85
Solar/Wind Harmer
0.081
276843GEN-1.7
Solar/Wind Harmer
0.1
958011AF2-095 GEN
Solar/Wind Harmer
4.436
274770LINCOLN ;1U
Adder
3.725
274771LINCOLN ;2U
Adder
3.725
972259AH1-714 GEN
Adder
8.36
942221AE2-234 GEN
Solar/Wind Harmer
0.015
274674JOLIET 9 ;6U
Adder
6.729
970321AG2-212 GEN
Solar/Wind Harmer
1.317
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.519
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.408
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.56
203947AF1-006 C
Solar/Wind Helper
0.37
203980AG1-197 GEN
Solar/Wind Helper
0.242
203979AG1-198 GEN
Solar/Wind Helper
0.188
241967AE2-285_GEN
Solar/Wind Helper
0.33
241801AE1-079 GEN
Solar/Wind Helper
0.128
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.319
946381AF1-302 GEN
Solar/Wind Helper
0.102
991182J1586 G
External Queue
24.65229034423828
990527J1329
External Queue
1.8002409934997559
990142J1224
External Queue
13.159761428833008
991177J1571 G
External Queue
15.044508934020996
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.578
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.528
MECLTFEXP_MEC->PJM
CLTF
6.231
SIGELTFEXP_SIGE->PJM
CLTF
0.161
LAGNLTFEXP_LAGN->PJM
CLTF
4.752
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.085
TVALTFEXP_TVA->PJM
CLTF
2.153
CPLELTFEXP_CPLE->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.025
NYPJM->LTFIMP_NY
CLTF
1.97
LGEELTFEXP_LGEE->PJM
CLTF
1.929
WECLTFEXP_WEC->PJM
CLTF
1.6
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.76 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2117.36
MW Contribution:2.38
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.251
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.147
23906502RICHG2&3
Adder
1.303
270575GUS2 35KV
Solar/Wind Harmer
4.647
270541AE2-072 C
Solar/Wind Harmer
0.008
970217AG2-149 GEN
Solar/Wind Harmer
4.178
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270588AE1-091_GEN
Solar/Wind Harmer
3.347
247604X1-042
Adder
0.248
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.52
945111AF1-176 GEN
Solar/Wind Harmer
3.081
270191TR4_S_V150
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.024
24642205MAYFLWER
Adder
0.337
970031AG2-029 GEN
Solar/Wind Harmer
2.384
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.518
965021AG1-366 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.178
970349AG2-230 GEN
Solar/Wind Harmer
5.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.222
270377AD1-106 GEN
Solar/Wind Harmer
1.233
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.712
274753CRETE EC ;3U
Adder
3.712
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
7.915
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.566
274826FISK ;BP
Adder
4.81
274800UNIV PARK;3U
Adder
2.557
972038AH1-567 GEN2
Adder
0.16
276806AD2-047 C O1
Solar/Wind Harmer
1.732
970941AG2-585 GEN
Solar/Wind Harmer
3.82
274772LINCOLN ;3U
Adder
3.695
972228AH1-698 GEN2
Adder
1.618
274676JOLIET 29;8U
Adder
12.851
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.12
274730ELWOOD EC;6P
Adder
7.127
274734ELWOOD EC;8P
Adder
7.127
274736ELWOOD EC;9P
Adder
7.127
970707AG2-453 GEN
Solar/Wind Harmer
9.881
274729ELWOOD EC;1P
Adder
7.127
970513AG2-328 GEN
Solar/Wind Harmer
1.307
970517AG2-330 GEN
Solar/Wind Harmer
7.843
971617AH1-308 GEN
Solar/Wind Harmer
2.511
962511AG1-100 GEN
Solar/Wind Helper
0.336
203830AF1-094 GEN
Solar/Wind Helper
0.318
959441AF2-235 GEN
Solar/Wind Helper
0.145
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.635
24189902OREGON_CT2
50/50
2.548
23888702TROY G3
50/50
1.734
972253AH1-711 GEN
50/50
52.952
23856402BAYSG1
50/50
1.279
23920202STRYCT
50/50
1.883
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
3.794
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.527
23906402RICHG1
Adder
1.305
23906502RICHG2&3
Adder
1.303
270361_3
Solar/Wind Harmer
4.647
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
241807AE2-176_GEN
Solar/Wind Harmer
0.004
247522W1-056 GEN
Solar/Wind Harmer
0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.533
944231AF1-091 GEN
Solar/Wind Harmer
1.197
270428AC2-015 C
Solar/Wind Harmer
0.002
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.52
965421AG1-410 GEN
Solar/Wind Harmer
11.884
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.028
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.783
270505AE1-170 C O1
Solar/Wind Harmer
3.988
247521TR3_G114
Solar/Wind Harmer
0.136
270246TR4_N_V150
Solar/Wind Harmer
0.024
24639705ELKHART HY
Adder
0.081
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.597
270462AD2-086
Solar/Wind Harmer
0.008
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.828
270055AF2-134 C O1
Solar/Wind Harmer
0.002
970905AG2-564 GEN
Solar/Wind Harmer
1.725
274751CRETE EC ;1U
Adder
3.712
274754CRETE EC ;4U
Adder
3.712
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.065
274723RIVER EC ;12
Adder
8.011
274812UNIV PK N;8U
Adder
2.229
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.557
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.82
276776AD2-060 GEN
Solar/Wind Harmer
0.319
274773LINCOLN ;4U
Adder
3.695
274774LINCOLN ;5U
Adder
3.695
274676JOLIET 29;8U
Adder
13.326
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.127
274674JOLIET 9 ;6U
Adder
6.676
970245AG2-165 GEN
Solar/Wind Harmer
1.307
274871GR RIDGE ;2U
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.329
203835AF1-098 GEN
Solar/Wind Helper
1.297
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.075
23867002DVBSG1
50/50
12.718
972211AH1-690 GEN
50/50
274.788
23888502TROY G1
50/50
1.734
23888602TROY G2
50/50
1.734
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
10.276
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
9.816
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
1.766
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.507
971619AH1-309 GEN
Solar/Wind Harmer
1.709
965041AG1-368 GEN
Solar/Wind Harmer
3.755
965051AG1-369 GEN
Solar/Wind Harmer
1.865
971771AH1-392 GEN
Solar/Wind Harmer
3.604
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.505
24191202EL_AA1-006
Adder
0.112
971769AH1-391 GEN
Solar/Wind Harmer
3.923
971567AH1-282 GEN
Solar/Wind Harmer
5.235
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.047
963791AG1-232 GEN
Solar/Wind Harmer
4.499
270578AF1-285 GEN2
Solar/Wind Harmer
0.222
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.048
274814UNIV PK N;0U
Adder
2.248
274807UNIV PK N;3U
Adder
2.243
274805UNIV PK N;1U
Adder
2.233
274811UNIV PK N;7U
Adder
2.229
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.409
971611AH1-305 GEN
Solar/Wind Harmer
1.819
960591AF2-350 GEN
Solar/Wind Harmer
3.056
274775LINCOLN ;6U
Adder
3.695
274776LINCOLN ;7U
Adder
3.695
274777LINCOLN ;8U
Adder
3.695
972227AH1-698 GEN1
Adder
1.139
274687WILL CNTY;4U
Adder
12.162
274687WILL CNTY;4U
Adder
12.162
274675JOLIET 29;7U
Adder
13.327
24190002OREGON_ST1
50/50
3.428
24189802OREGON_CT1
50/50
2.6
23888802TROY G4
50/50
1.734
241996AE2-282_GEN
Solar/Wind Harmer
0.005
971677AH1-339 GEN
Solar/Wind Harmer
0.654
970621AG2-405 GEN
Solar/Wind Harmer
0.864
970623AG2-406 GEN
Solar/Wind Harmer
0.785
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.162
961051AF2-396 GEN
Solar/Wind Harmer
7.707
961051AF2-396 GEN
Solar/Wind Harmer
5.138
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.245
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.597
970627AG2-408 GEN
Solar/Wind Harmer
1.079
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.224
965791AG1-447 GEN
Solar/Wind Harmer
3.098
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.372
274808UNIV PK N;4U
Adder
2.219
274803UNIV PARK;6U
Adder
2.566
274888KELLY CRK;1U
Solar/Wind Harmer
0.179
274887GEN-1.85
Solar/Wind Harmer
0.08
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.4
274770LINCOLN ;1U
Adder
3.695
274771LINCOLN ;2U
Adder
3.695
942221AE2-234 GEN
Solar/Wind Harmer
0.015
972259AH1-714 GEN
Adder
8.293
274674JOLIET 9 ;6U
Adder
6.676
970321AG2-212 GEN
Solar/Wind Harmer
1.307
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
203947AF1-006 C
Solar/Wind Helper
0.375
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241967AE2-285_GEN
Solar/Wind Helper
0.334
241801AE1-079 GEN
Solar/Wind Helper
0.13
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.322
946381AF1-302 GEN
Solar/Wind Helper
0.103
274675JOLIET 29;7U
Adder
12.851
274728ELWOOD EC;5P
Adder
7.127
274731ELWOOD EC;2P
Adder
7.127
274733ELWOOD EC;3P
Adder
7.127
274735ELWOOD EC;4P
Adder
7.127
270024AE2-089 GEN
Solar/Wind Harmer
0.003
970833AG2-524 GEN
Solar/Wind Harmer
3.311
970833AG2-524 GEN
Solar/Wind Harmer
2.207
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.244
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.852
991182J1586 G
External Queue
23.868927001953125
990527J1329
External Queue
1.745489239692688
990142J1224
External Queue
12.759525299072266
991177J1571 G
External Queue
14.724894523620605
CBM West 1LTFEXP_CBM-W1->PJM
CBM
89.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.514
MECLTFEXP_MEC->PJM
CLTF
6.19
SIGELTFEXP_SIGE->PJM
CLTF
0.161
LAGNLTFEXP_LAGN->PJM
CLTF
4.735
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.079
TVALTFEXP_TVA->PJM
CLTF
2.148
CPLELTFEXP_CPLE->PJM
CLTF
0.305
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.878
NYPJM->LTFIMP_NY
CLTF
1.99
LGEELTFEXP_LGEE->PJM
CLTF
1.931
WECLTFEXP_WEC->PJM
CLTF
1.588
AG2-052LTFEXP_AG2-052->PJM
LTF
0.102
AH1-155LTFEXP_AH1-155->PJM
LTF
0.153

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.17 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2805.14
MW Contribution:35.76
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.284
960861AF2-377 GEN
50/50
2.347
970521AG2-332 GEN
50/50
10.682
24639705ELKHART HY
50/50
0.148
965421AG1-410 GEN
Solar/Wind Harmer
116.328
965011AG1-365 GEN
Solar/Wind Harmer
19.549
270063AE2-323 C
Solar/Wind Harmer
2.317
247521TR3_G114
Solar/Wind Harmer
3.391
270246TR4_N_V150
Solar/Wind Harmer
0.858
944231AF1-091 GEN
Solar/Wind Harmer
3.689
965651AG1-433 GEN
Solar/Wind Harmer
4.856
24695305TIMB G C
Solar/Wind Harmer
4.856
958861AF2-177 GEN
Solar/Wind Harmer
9.429
945111AF1-176 GEN
Solar/Wind Harmer
14.978
270505AE1-170 C O1
Solar/Wind Harmer
12.278
945371AF1-202 GEN
Solar/Wind Harmer
5.674
270449AD2-020 GEN
Solar/Wind Harmer
2.257
943021AE2-325 GEN
Solar/Wind Harmer
2.933
970245AG2-165 GEN
Solar/Wind Harmer
13.514
970373AG2-245 GEN
Solar/Wind Harmer
15.829
274751CRETE EC ;1U
Adder
3.67
274754CRETE EC ;4U
Adder
3.67
274723RIVER EC ;12
Adder
13.411
274812UNIV PK N;8U
Adder
3.718
276164X3-005 C
Solar/Wind Harmer
0.521
270055AF2-134 C O1
Solar/Wind Harmer
2.245
972207SS24-0001
Solar/Wind Harmer
16.298
274773LINCOLN ;4U
Adder
4.584
274774LINCOLN ;5U
Adder
4.584
274801UNIV PARK;4U
Adder
4.271
276776AD2-060 GEN
Solar/Wind Harmer
0.309
958381AF2-132 GEN
Solar/Wind Harmer
6.626
964861AG1-349 GEN
Solar/Wind Harmer
5.732
971917AH1-482 GEN
Solar/Wind Harmer
6.615
941551AE2-152 GEN
Solar/Wind Harmer
3.286
274676JOLIET 29;8U
Adder
22.222
274674JOLIET 9 ;6U
Adder
11.128
274732ELWOOD EC;7P
Adder
11.875
274871GR RIDGE ;2U
Solar/Wind Harmer
5.526
24727205RPMNG3
50/50
3.268
971599AH1-298 GEN
50/50
10.228
24729505KEY G4
50/50
6.661
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
16.424
965041AG1-368 GEN
Solar/Wind Harmer
11.874
270071AF1-092 GEN
Solar/Wind Harmer
15.99
965051AG1-369 GEN
Solar/Wind Harmer
5.036
958711AF2-162 GEN
Solar/Wind Harmer
0.899
270024AE2-089 GEN
Solar/Wind Harmer
4.106
965101AG1-375 GEN
Solar/Wind Harmer
8.627
971771AH1-392 GEN
Solar/Wind Harmer
7.458
971347AH1-153 GEN
Solar/Wind Harmer
12.325
945581AF1-223 GEN
Solar/Wind Harmer
3.688
971769AH1-391 GEN
Solar/Wind Harmer
7.977
944161AF1-084 GEN
Solar/Wind Harmer
1.752
960681AF2-359 GEN
Solar/Wind Harmer
2.953
274814UNIV PK N;0U
Adder
3.75
274807UNIV PK N;3U
Adder
3.742
274805UNIV PK N;1U
Adder
3.726
274811UNIV PK N;7U
Adder
3.718
270536AF1-215 GEN2
Solar/Wind Harmer
3.368
274775LINCOLN ;6U
Adder
4.584
274776LINCOLN ;7U
Adder
4.584
274777LINCOLN ;8U
Adder
4.584
972037AH1-567 GEN1
Adder
0.134
274827FISK ;RP
Adder
5.694
960591AF2-350 GEN
Solar/Wind Harmer
7.317
972227AH1-698 GEN1
Adder
1.903
274687WILL CNTY;4U
Adder
20.283
274687WILL CNTY;4U
Adder
20.283
958391AF2-133 GEN
Solar/Wind Harmer
6.575
274675JOLIET 29;7U
Adder
22.222
274675JOLIET 29;7U
Adder
21.428
274731ELWOOD EC;2P
Adder
11.875
274733ELWOOD EC;3P
Adder
11.875
274735ELWOOD EC;4P
Adder
11.875
274728ELWOOD EC;5P
Adder
11.875
970833AG2-524 GEN
Solar/Wind Harmer
6.278
970833AG2-524 GEN
Solar/Wind Harmer
2.92
274746AC1-111 G10
Adder
3.99
274744AC1-111 GEN8
Adder
3.99
965461AG1-414 GEN
Solar/Wind Harmer
1.594
970289AG2-191 GEN
Solar/Wind Harmer
1.336
276868AE1-113 GEN
Solar/Wind Harmer
7.049
276882AE2-255 GEN
Solar/Wind Harmer
2.35
270594AE1-207 GEN
Solar/Wind Harmer
10.213
274823ROCKFORD ;21
Adder
13.342
957201AF2-014 GEN
Solar/Wind Helper
8.667
270317AD1-130_GEN
Solar/Wind Helper
4.304
966831AG1-554 GEN
Solar/Wind Helper
0.913
270284AF1-227 GEN1
Solar/Wind Helper
2.061
270286AF1-227 GEN2
Solar/Wind Helper
0.756
270287AF1-227 GEN3
Solar/Wind Helper
0.756
270499AE1-146 GEN
Solar/Wind Helper
2.039
945641AF1-229 GEN
Solar/Wind Helper
0.989
253383AE2-342_GEN
Solar/Wind Helper
0.361
940581AE2-045 GEN
Solar/Wind Harmer
7.295
971605AH1-302 GEN
Solar/Wind Harmer
6.238
274745AC1-111 GEN9
Adder
3.99
276691AA1-018 GEN1
Solar/Wind Harmer
0.33
274682WAUKEGAN ;7U
Adder
12.686
274828WAUKEGAN ;BP
Adder
7.787
970291AG2-192 GEN
Solar/Wind Harmer
0.914
960751AF2-366 GEN
Solar/Wind Harmer
2.006
962781AG1-127 GEN
Solar/Wind Harmer
6.648
939401AE1-172 GEN
Solar/Wind Harmer
9.737
276901AD2-066 C O1
Solar/Wind Harmer
2.454
270005AE1-210 C O1
Solar/Wind Harmer
3.813
965031AG1-367 GEN
Solar/Wind Harmer
6.977
274872LEEDK;1U
Solar/Wind Harmer
5.729
270032AE2-172
Solar/Wind Harmer
3.232
274822ROCKFORD ;11
Adder
13.439
972235AH1-702 GEN1
Adder
1.722
274761LEE CO EC;2U
Adder
6.263
274766LEE CO EC;7U
Adder
6.189
24728605AND G2
Adder
2.022
246936BC-WTG1
Solar/Wind Helper
10.964
270462AD2-086
Solar/Wind Helper
3.886
270223U2-072_GEN1
Solar/Wind Helper
0.919
270578AF1-285 GEN2
Solar/Wind Helper
0.623
270391AF1-285 GEN3
Solar/Wind Helper
0.623
247522W1-056 GEN
Solar/Wind Helper
1.219
960841AF2-375 GEN
Solar/Wind Helper
1.228
270349AD2-093_GEN
Solar/Wind Helper
0.982
965431AG1-411 GEN
50/50
45.089
24727105RPMNG2
50/50
3.296
970583AG2-370 GEN
50/50
2.761
959331AF2-224 GEN
Solar/Wind Harmer
19.549
965021AG1-366 GEN
Solar/Wind Harmer
4.546
970031AG2-029 GEN
Solar/Wind Harmer
35.759
270043AE2-236 GEN
Solar/Wind Harmer
6.31
270191TR4_S_V150
Solar/Wind Harmer
3.026
270247TR4_N_V136
Solar/Wind Harmer
0.858
944531AF1-118 GEN
Solar/Wind Harmer
34.867
971617AH1-308 GEN
Solar/Wind Harmer
5.086
247643Z2-116 C
Solar/Wind Harmer
0.061
945111AF1-176 GEN
Solar/Wind Harmer
4.747
970349AG2-230 GEN
Solar/Wind Harmer
12.325
24642205MAYFLWER
Adder
0.518
24441205WTRV SLR C
Solar/Wind Harmer
0.103
970513AG2-328 GEN
Solar/Wind Harmer
13.514
970517AG2-330 GEN
Solar/Wind Harmer
12.257
972231SS25-0005
Solar/Wind Harmer
7.126
972181SS23-001
Solar/Wind Harmer
4.454
274752CRETE EC ;2U
Adder
3.67
274753CRETE EC ;3U
Adder
3.67
274724RIVER EC ;11
Adder
13.248
270535AF1-215 GEN1
Solar/Wind Harmer
3.368
247604X1-042
Adder
0.308
274772LINCOLN ;3U
Adder
4.584
274802UNIV PARK;5U
Adder
4.284
274826FISK ;BP
Adder
8.035
274800UNIV PARK;3U
Adder
4.271
972038AH1-567 GEN2
Adder
0.267
276772AC2-154 GEN
Solar/Wind Harmer
2.041
276806AD2-047 C O1
Solar/Wind Harmer
7.828
970941AG2-585 GEN
Solar/Wind Harmer
9.146
964401AG1-302 GEN
Solar/Wind Harmer
6.626
972228AH1-698 GEN2
Adder
2.703
970707AG2-453 GEN
Solar/Wind Harmer
20.363
276897AD1-100 C
Solar/Wind Harmer
21.024
939351AE1-166 GEN
Solar/Wind Harmer
4.296
274676JOLIET 29;8U
Adder
21.428
276893AG1-478 C
Solar/Wind Harmer
0.302
274729ELWOOD EC;1P
Adder
11.875
274730ELWOOD EC;6P
Adder
11.875
274734ELWOOD EC;8P
Adder
11.875
274736ELWOOD EC;9P
Adder
11.875
959141AF2-205 GEN
Solar/Wind Harmer
4.356
943121AE2-341 GEN
Solar/Wind Harmer
10.713
943591AF1-030 GEN
Solar/Wind Harmer
7.142
247642Z2-115 C
Solar/Wind Harmer
0.046
276694AA1-018 GEN2
Solar/Wind Harmer
4.477
274682WAUKEGAN ;7U
Adder
12.686
970289AG2-191 GEN
Solar/Wind Harmer
0.54
970291AG2-192 GEN
Solar/Wind Harmer
0.491
276805AD2-038 GEN
Solar/Wind Harmer
3.595
958821AF2-173 GEN
Solar/Wind Harmer
9.767
270004AE1-209 GEN
Solar/Wind Harmer
3.813
274872LEEDK;1U
Solar/Wind Harmer
0.178
972236AH1-702 GEN2
Adder
1.497
274760LEE CO EC;1U
Adder
6.263
274767LEE CO EC;8U
Adder
6.189
24728705AND G3
Adder
4.229
24728505AND G1
Adder
2.022
270485AE1-090_GEN
Solar/Wind Helper
0.338
942871AE2-306 GEN
Solar/Wind Helper
0.467
270541AE2-072 C
Solar/Wind Helper
0.991
970615AG2-402 GEN
50/50
4.546
24729405KEY G3
50/50
0.364
24729305KEY G2
50/50
0.357
24729205KEY G1
50/50
0.356
247620Y3-023
50/50
0.458
970611AG2-400 GEN
Solar/Wind Harmer
19.549
942221AE2-234 GEN
Solar/Wind Harmer
0.705
944541AF1-119 GEN
Solar/Wind Harmer
3.722
960971AF2-388 GEN
Solar/Wind Harmer
9.712
270216AD2-079_GEN
Solar/Wind Harmer
0.529
960981AF2-389 GEN
Solar/Wind Harmer
1.248
957891AF2-083 GEN
Solar/Wind Harmer
2.781
961051AF2-396 GEN
Solar/Wind Harmer
12.984
961051AF2-396 GEN
Solar/Wind Harmer
6.039
270526AF1-158 GEN
Solar/Wind Harmer
3.652
24441505OLIV SLR
Solar/Wind Harmer
0.107
965681AG1-436 GEN
Solar/Wind Harmer
9.772
965791AG1-447 GEN
Solar/Wind Harmer
5
270599AE1-208 GEN
Solar/Wind Harmer
6.285
270031AE2-169
Solar/Wind Harmer
6.285
970321AG2-212 GEN
Solar/Wind Harmer
13.514
274808UNIV PK N;4U
Adder
3.701
274770LINCOLN ;1U
Adder
4.584
274771LINCOLN ;2U
Adder
4.584
274803UNIV PARK;6U
Adder
4.284
274888KELLY CRK;1U
Solar/Wind Harmer
4.32
274887GEN-1.85
Solar/Wind Harmer
3.9
276843GEN-1.7
Solar/Wind Harmer
0.42
958011AF2-095 GEN
Solar/Wind Harmer
10.537
972259AH1-714 GEN
Adder
13.877
274674JOLIET 9 ;6U
Adder
11.128
274847GR RIDGE ;BU
Solar/Wind Harmer
3.635
971573AH1-285 GEN
Solar/Wind Harmer
6.11
958481AF2-142 GEN
Solar/Wind Harmer
10.641
274861TOP CROP ;1U
Solar/Wind Harmer
4.297
274862TOP CROP ;2U
Solar/Wind Harmer
3.588
274695ROCKY RD ;2P
Adder
7.863
274693ROCKY RD ;1P
Adder
7.786
274697ROCKY RD ;3P
Adder
2.136
274696ROCKY RD ;4P
Adder
8.048
274683WAUKEGAN ;8U
Adder
14.856
274683WAUKEGAN ;8U
Adder
12.523
945421AF1-207 GEN
Solar/Wind Harmer
9.844
957841AF2-078 GEN
Solar/Wind Harmer
4.236
962691AG1-118 GEN
Solar/Wind Harmer
21.023
958491AF2-143 GEN
Solar/Wind Harmer
10.51
970921AG2-575 GEN
Solar/Wind Harmer
6.991
970921AG2-575 GEN
Solar/Wind Harmer
1.626
274879MINONK ;1U
Solar/Wind Harmer
4.7
274764LEE CO EC;5U
Adder
6.277
274765LEE CO EC;6U
Adder
6.277
274762LEE CO EC;3U
Adder
6.263
274763LEE CO EC;4U
Adder
6.204
972267AH1-718 GEN
Adder
2.776
247621Y3-024
Adder
0.156
246938BC-WTG3
Solar/Wind Helper
11.153
246937BC-WTG2
Solar/Wind Helper
10.964
270224U2-072_GEN2
Solar/Wind Helper
0.919
270227U2-072_GEN3
Solar/Wind Helper
0.919
270228U2-072_GEN4
Solar/Wind Helper
0.919
270231U2-072_GEN5
Solar/Wind Helper
0.919
270471AD2-092_GEN
Solar/Wind Helper
0.982
253378AE2-206_GEN
Solar/Wind Helper
0.732
276820AF1-078_GEN
Solar/Wind Helper
0.342
241960AC2-195 GEN
Solar/Wind Helper
0.763
942991AE2-321 GEN
Solar/Wind Harmer
6.674
944201AF1-088_MTX
Adder
55.177
957141AF2-008_MTX
Adder
27.589
990497J1323
External Queue
1.5705512762069702
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.177
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.048
MECLTFEXP_MEC->PJM
CLTF
9.629
SIGELTFEXP_SIGE->PJM
CLTF
0.197
LAGNLTFEXP_LAGN->PJM
CLTF
5.849
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.934
TVALTFEXP_TVA->PJM
CLTF
2.367
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.454
NYPJM->LTFIMP_NY
CLTF
1.28
LGEELTFEXP_LGEE->PJM
CLTF
1.786
WECLTFEXP_WEC->PJM
CLTF
2.606
AG2-052LTFEXP_AG2-052->PJM
LTF
0.169
AH1-155LTFEXP_AH1-155->PJM
LTF
0.253

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.37 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2715.52
MW Contribution:36.14
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.588
24729405KEY G3
50/50
0.368
24729305KEY G2
50/50
0.361
24729205KEY G1
50/50
0.36
247620Y3-023
50/50
0.463
970611AG2-400 GEN
Solar/Wind Harmer
19.727
942221AE2-234 GEN
Solar/Wind Harmer
0.714
944541AF1-119 GEN
Solar/Wind Harmer
3.764
960971AF2-388 GEN
Solar/Wind Harmer
9.823
270216AD2-079_GEN
Solar/Wind Harmer
0.535
960981AF2-389 GEN
Solar/Wind Harmer
1.263
957891AF2-083 GEN
Solar/Wind Harmer
2.815
961051AF2-396 GEN
Solar/Wind Harmer
13.147
961051AF2-396 GEN
Solar/Wind Harmer
6.115
270526AF1-158 GEN
Solar/Wind Harmer
3.692
24441505OLIV SLR
Solar/Wind Harmer
0.108
965681AG1-436 GEN
Solar/Wind Harmer
9.872
965791AG1-447 GEN
Solar/Wind Harmer
5.051
270599AE1-208 GEN
Solar/Wind Harmer
6.363
270031AE2-169
Solar/Wind Harmer
6.363
970321AG2-212 GEN
Solar/Wind Harmer
13.624
274808UNIV PK N;4U
Adder
3.733
274770LINCOLN ;1U
Adder
4.622
274771LINCOLN ;2U
Adder
4.622
274803UNIV PARK;6U
Adder
4.319
274888KELLY CRK;1U
Solar/Wind Harmer
4.356
274887GEN-1.85
Solar/Wind Harmer
3.932
276843GEN-1.7
Solar/Wind Harmer
0.423
958011AF2-095 GEN
Solar/Wind Harmer
10.624
972259AH1-714 GEN
Adder
13.99
274674JOLIET 9 ;6U
Adder
11.217
274847GR RIDGE ;BU
Solar/Wind Harmer
3.664
971573AH1-285 GEN
Solar/Wind Harmer
6.157
958481AF2-142 GEN
Solar/Wind Harmer
10.724
24727005RPMNG1
50/50
3.308
960861AF2-377 GEN
50/50
2.399
970521AG2-332 GEN
50/50
10.806
24639705ELKHART HY
50/50
0.149
965421AG1-410 GEN
Solar/Wind Harmer
117.153
965011AG1-365 GEN
Solar/Wind Harmer
19.727
270063AE2-323 C
Solar/Wind Harmer
2.344
247521TR3_G114
Solar/Wind Harmer
3.467
270246TR4_N_V150
Solar/Wind Harmer
0.877
944231AF1-091 GEN
Solar/Wind Harmer
3.756
24695305TIMB G C
Solar/Wind Harmer
4.981
965651AG1-433 GEN
Solar/Wind Harmer
4.912
958861AF2-177 GEN
Solar/Wind Harmer
9.538
945111AF1-176 GEN
Solar/Wind Harmer
15.162
270505AE1-170 C O1
Solar/Wind Harmer
12.429
945371AF1-202 GEN
Solar/Wind Harmer
5.742
270449AD2-020 GEN
Solar/Wind Harmer
2.286
943021AE2-325 GEN
Solar/Wind Harmer
2.97
970245AG2-165 GEN
Solar/Wind Harmer
13.624
970373AG2-245 GEN
Solar/Wind Harmer
15.978
274751CRETE EC ;1U
Adder
3.702
274754CRETE EC ;4U
Adder
3.702
274723RIVER EC ;12
Adder
13.527
274812UNIV PK N;8U
Adder
3.75
276164X3-005 C
Solar/Wind Harmer
0.526
270055AF2-134 C O1
Solar/Wind Harmer
2.265
972207SS24-0001
Solar/Wind Harmer
16.435
274773LINCOLN ;4U
Adder
4.622
274774LINCOLN ;5U
Adder
4.622
274801UNIV PARK;4U
Adder
4.307
276776AD2-060 GEN
Solar/Wind Harmer
0.312
958381AF2-132 GEN
Solar/Wind Harmer
6.683
964861AG1-349 GEN
Solar/Wind Harmer
5.781
971917AH1-482 GEN
Solar/Wind Harmer
6.671
941551AE2-152 GEN
Solar/Wind Harmer
3.312
274676JOLIET 29;8U
Adder
22.401
274674JOLIET 9 ;6U
Adder
11.217
274732ELWOOD EC;7P
Adder
11.97
274871GR RIDGE ;2U
Solar/Wind Harmer
5.57
940581AE2-045 GEN
Solar/Wind Harmer
7.354
971605AH1-302 GEN
Solar/Wind Harmer
6.288
274745AC1-111 GEN9
Adder
4.021
276691AA1-018 GEN1
Solar/Wind Harmer
0.333
274682WAUKEGAN ;7U
Adder
12.782
970291AG2-192 GEN
Solar/Wind Harmer
0.924
274828WAUKEGAN ;BP
Adder
7.846
270005AE1-210 C O1
Solar/Wind Harmer
3.861
965031AG1-367 GEN
Solar/Wind Harmer
7.065
960751AF2-366 GEN
Solar/Wind Harmer
2.02
962781AG1-127 GEN
Solar/Wind Harmer
6.697
939401AE1-172 GEN
Solar/Wind Harmer
9.81
276901AD2-066 C O1
Solar/Wind Harmer
2.472
270032AE2-172
Solar/Wind Harmer
3.269
274872LEEDK;1U
Solar/Wind Harmer
5.771
274822ROCKFORD ;11
Adder
13.533
972235AH1-702 GEN1
Adder
1.734
274761LEE CO EC;2U
Adder
6.304
274766LEE CO EC;7U
Adder
6.23
24728605AND G2
Adder
2.043
246936BC-WTG1
Solar/Wind Helper
10.895
270462AD2-086
Solar/Wind Helper
3.714
270223U2-072_GEN1
Solar/Wind Helper
0.871
270578AF1-285 GEN2
Solar/Wind Helper
0.59
270391AF1-285 GEN3
Solar/Wind Helper
0.59
247522W1-056 GEN
Solar/Wind Helper
1.168
960841AF2-375 GEN
Solar/Wind Helper
1.175
270349AD2-093_GEN
Solar/Wind Helper
0.85
965431AG1-411 GEN
50/50
45.408
24727105RPMNG2
50/50
3.32
970583AG2-370 GEN
50/50
2.809
959331AF2-224 GEN
Solar/Wind Harmer
19.727
965021AG1-366 GEN
Solar/Wind Harmer
4.588
970031AG2-029 GEN
Solar/Wind Harmer
36.141
270043AE2-236 GEN
Solar/Wind Harmer
6.378
270191TR4_S_V150
Solar/Wind Harmer
3.093
270247TR4_N_V136
Solar/Wind Harmer
0.877
944531AF1-118 GEN
Solar/Wind Harmer
35.247
971617AH1-308 GEN
Solar/Wind Harmer
5.166
247643Z2-116 C
Solar/Wind Harmer
0.061
945111AF1-176 GEN
Solar/Wind Harmer
4.805
970349AG2-230 GEN
Solar/Wind Harmer
12.452
24642205MAYFLWER
Adder
0.524
24441205WTRV SLR C
Solar/Wind Harmer
0.104
970513AG2-328 GEN
Solar/Wind Harmer
13.624
970517AG2-330 GEN
Solar/Wind Harmer
12.357
972231SS25-0005
Solar/Wind Harmer
7.189
972181SS23-001
Solar/Wind Harmer
4.493
274752CRETE EC ;2U
Adder
3.702
274753CRETE EC ;3U
Adder
3.702
274724RIVER EC ;11
Adder
13.364
247604X1-042
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
3.398
274772LINCOLN ;3U
Adder
4.622
274802UNIV PARK;5U
Adder
4.319
274826FISK ;BP
Adder
8.102
274800UNIV PARK;3U
Adder
4.307
972038AH1-567 GEN2
Adder
0.27
276772AC2-154 GEN
Solar/Wind Harmer
2.057
276806AD2-047 C O1
Solar/Wind Harmer
7.892
970941AG2-585 GEN
Solar/Wind Harmer
9.222
964401AG1-302 GEN
Solar/Wind Harmer
6.683
972228AH1-698 GEN2
Adder
2.725
970707AG2-453 GEN
Solar/Wind Harmer
20.528
276897AD1-100 C
Solar/Wind Harmer
21.195
939351AE1-166 GEN
Solar/Wind Harmer
4.331
274676JOLIET 29;8U
Adder
21.601
276893AG1-478 C
Solar/Wind Harmer
0.304
274730ELWOOD EC;6P
Adder
11.97
274734ELWOOD EC;8P
Adder
11.97
274736ELWOOD EC;9P
Adder
11.97
274729ELWOOD EC;1P
Adder
11.97
959141AF2-205 GEN
Solar/Wind Harmer
4.392
943121AE2-341 GEN
Solar/Wind Harmer
10.796
943591AF1-030 GEN
Solar/Wind Harmer
7.197
247642Z2-115 C
Solar/Wind Harmer
0.046
276694AA1-018 GEN2
Solar/Wind Harmer
4.512
274682WAUKEGAN ;7U
Adder
12.782
970289AG2-191 GEN
Solar/Wind Harmer
0.545
970291AG2-192 GEN
Solar/Wind Harmer
0.496
958821AF2-173 GEN
Solar/Wind Harmer
9.891
270004AE1-209 GEN
Solar/Wind Harmer
3.861
276805AD2-038 GEN
Solar/Wind Harmer
3.622
274872LEEDK;1U
Solar/Wind Harmer
0.18
972236AH1-702 GEN2
Adder
1.508
274760LEE CO EC;1U
Adder
6.304
274767LEE CO EC;8U
Adder
6.23
24728705AND G3
Adder
4.272
24728505AND G1
Adder
2.043
270485AE1-090_GEN
Solar/Wind Helper
0.323
942871AE2-306 GEN
Solar/Wind Helper
0.443
270541AE2-072 C
Solar/Wind Helper
0.932
274861TOP CROP ;1U
Solar/Wind Harmer
4.33
274862TOP CROP ;2U
Solar/Wind Harmer
3.616
274695ROCKY RD ;2P
Adder
7.922
274693ROCKY RD ;1P
Adder
7.844
274697ROCKY RD ;3P
Adder
2.152
274696ROCKY RD ;4P
Adder
8.109
274683WAUKEGAN ;8U
Adder
14.968
274683WAUKEGAN ;8U
Adder
12.617
945421AF1-207 GEN
Solar/Wind Harmer
9.918
957841AF2-078 GEN
Solar/Wind Harmer
4.268
962691AG1-118 GEN
Solar/Wind Harmer
21.179
958491AF2-143 GEN
Solar/Wind Harmer
10.589
970921AG2-575 GEN
Solar/Wind Harmer
7.042
970921AG2-575 GEN
Solar/Wind Harmer
1.638
274879MINONK ;1U
Solar/Wind Harmer
4.734
274764LEE CO EC;5U
Adder
6.319
274765LEE CO EC;6U
Adder
6.319
274762LEE CO EC;3U
Adder
6.304
274763LEE CO EC;4U
Adder
6.245
972267AH1-718 GEN
Adder
2.793
247621Y3-024
Adder
0.16
246938BC-WTG3
Solar/Wind Helper
11.083
246937BC-WTG2
Solar/Wind Helper
10.895
270224U2-072_GEN2
Solar/Wind Helper
0.871
270227U2-072_GEN3
Solar/Wind Helper
0.871
270228U2-072_GEN4
Solar/Wind Helper
0.871
270231U2-072_GEN5
Solar/Wind Helper
0.871
270471AD2-092_GEN
Solar/Wind Helper
0.85
253378AE2-206_GEN
Solar/Wind Helper
0.684
276820AF1-078_GEN
Solar/Wind Helper
0.319
241960AC2-195 GEN
Solar/Wind Helper
0.69
942991AE2-321 GEN
Solar/Wind Harmer
6.723
24727205RPMNG3
50/50
3.292
971599AH1-298 GEN
50/50
10.333
24729505KEY G4
50/50
6.735
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
16.635
965041AG1-368 GEN
Solar/Wind Harmer
12.077
270071AF1-092 GEN
Solar/Wind Harmer
16.152
965051AG1-369 GEN
Solar/Wind Harmer
5.148
958711AF2-162 GEN
Solar/Wind Harmer
0.909
270024AE2-089 GEN
Solar/Wind Harmer
4.17
965101AG1-375 GEN
Solar/Wind Harmer
8.727
971771AH1-392 GEN
Solar/Wind Harmer
7.543
971347AH1-153 GEN
Solar/Wind Harmer
12.452
945581AF1-223 GEN
Solar/Wind Harmer
3.732
971769AH1-391 GEN
Solar/Wind Harmer
8.064
944161AF1-084 GEN
Solar/Wind Harmer
1.775
960681AF2-359 GEN
Solar/Wind Harmer
2.984
274814UNIV PK N;0U
Adder
3.782
274807UNIV PK N;3U
Adder
3.774
274805UNIV PK N;1U
Adder
3.758
274811UNIV PK N;7U
Adder
3.75
270536AF1-215 GEN2
Solar/Wind Harmer
3.398
274775LINCOLN ;6U
Adder
4.622
274776LINCOLN ;7U
Adder
4.622
274777LINCOLN ;8U
Adder
4.622
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.742
960591AF2-350 GEN
Solar/Wind Harmer
7.378
972227AH1-698 GEN1
Adder
1.919
274687WILL CNTY;4U
Adder
20.447
274687WILL CNTY;4U
Adder
20.447
958391AF2-133 GEN
Solar/Wind Harmer
6.63
274675JOLIET 29;7U
Adder
22.401
274675JOLIET 29;7U
Adder
21.601
274728ELWOOD EC;5P
Adder
11.97
274731ELWOOD EC;2P
Adder
11.97
274733ELWOOD EC;3P
Adder
11.97
274735ELWOOD EC;4P
Adder
11.97
970833AG2-524 GEN
Solar/Wind Harmer
6.328
970833AG2-524 GEN
Solar/Wind Harmer
2.943
274746AC1-111 G10
Adder
4.021
274744AC1-111 GEN8
Adder
4.021
965461AG1-414 GEN
Solar/Wind Harmer
1.612
970289AG2-191 GEN
Solar/Wind Harmer
1.35
270594AE1-207 GEN
Solar/Wind Harmer
10.331
276868AE1-113 GEN
Solar/Wind Harmer
7.101
276882AE2-255 GEN
Solar/Wind Harmer
2.367
274823ROCKFORD ;21
Adder
13.435
957201AF2-014 GEN
Solar/Wind Helper
8.613
270317AD1-130_GEN
Solar/Wind Helper
4.113
966831AG1-554 GEN
Solar/Wind Helper
0.876
270284AF1-227 GEN1
Solar/Wind Helper
1.876
270286AF1-227 GEN2
Solar/Wind Helper
0.688
270287AF1-227 GEN3
Solar/Wind Helper
0.688
270499AE1-146 GEN
Solar/Wind Helper
1.952
945641AF1-229 GEN
Solar/Wind Helper
0.937
944201AF1-088_MTX
Adder
55.165
957141AF2-008_MTX
Adder
27.582
990497J1323
External Queue
1.5914489030838013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.309
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.744
MECLTFEXP_MEC->PJM
CLTF
9.656
SIGELTFEXP_SIGE->PJM
CLTF
0.197
LAGNLTFEXP_LAGN->PJM
CLTF
5.694
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.439
TVALTFEXP_TVA->PJM
CLTF
2.27
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.944
NYPJM->LTFIMP_NY
CLTF
1.265
LGEELTFEXP_LGEE->PJM
CLTF
1.782
WECLTFEXP_WEC->PJM
CLTF
2.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.67 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2683.73
MW Contribution:35.17
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.494
24729405KEY G3
50/50
0.357
24729305KEY G2
50/50
0.351
24729205KEY G1
50/50
0.349
247620Y3-023
50/50
0.448
970611AG2-400 GEN
Solar/Wind Harmer
19.324
942221AE2-234 GEN
Solar/Wind Harmer
0.691
944541AF1-119 GEN
Solar/Wind Harmer
3.645
960971AF2-388 GEN
Solar/Wind Harmer
9.511
270216AD2-079_GEN
Solar/Wind Harmer
0.518
960981AF2-389 GEN
Solar/Wind Harmer
1.22
957891AF2-083 GEN
Solar/Wind Harmer
2.72
961051AF2-396 GEN
Solar/Wind Harmer
12.698
961051AF2-396 GEN
Solar/Wind Harmer
5.906
270526AF1-158 GEN
Solar/Wind Harmer
3.57
24441505OLIV SLR
Solar/Wind Harmer
0.104
965681AG1-436 GEN
Solar/Wind Harmer
9.546
965791AG1-447 GEN
Solar/Wind Harmer
4.884
270599AE1-208 GEN
Solar/Wind Harmer
6.137
270031AE2-169
Solar/Wind Harmer
6.137
970321AG2-212 GEN
Solar/Wind Harmer
13.188
274808UNIV PK N;4U
Adder
3.612
274770LINCOLN ;1U
Adder
4.473
274771LINCOLN ;2U
Adder
4.473
274803UNIV PARK;6U
Adder
4.179
274888KELLY CRK;1U
Solar/Wind Harmer
4.214
274887GEN-1.85
Solar/Wind Harmer
3.805
276843GEN-1.7
Solar/Wind Harmer
0.409
958011AF2-095 GEN
Solar/Wind Harmer
10.279
972259AH1-714 GEN
Adder
13.536
274674JOLIET 9 ;6U
Adder
10.853
274847GR RIDGE ;BU
Solar/Wind Harmer
3.545
971573AH1-285 GEN
Solar/Wind Harmer
5.957
958481AF2-142 GEN
Solar/Wind Harmer
10.374
274861TOP CROP ;1U
Solar/Wind Harmer
4.189
274862TOP CROP ;2U
Solar/Wind Harmer
3.498
274695ROCKY RD ;2P
Adder
7.665
274693ROCKY RD ;1P
Adder
7.589
274697ROCKY RD ;3P
Adder
2.082
274696ROCKY RD ;4P
Adder
7.846
274683WAUKEGAN ;8U
Adder
14.481
274683WAUKEGAN ;8U
Adder
12.207
962691AG1-118 GEN
Solar/Wind Harmer
20.49
958491AF2-143 GEN
Solar/Wind Harmer
10.244
945421AF1-207 GEN
Solar/Wind Harmer
9.591
957841AF2-078 GEN
Solar/Wind Harmer
4.127
970921AG2-575 GEN
Solar/Wind Harmer
6.813
970921AG2-575 GEN
Solar/Wind Harmer
1.584
274879MINONK ;1U
Solar/Wind Harmer
4.58
274764LEE CO EC;5U
Adder
6.113
274765LEE CO EC;6U
Adder
6.113
274762LEE CO EC;3U
Adder
6.098
274763LEE CO EC;4U
Adder
6.041
972267AH1-718 GEN
Adder
2.702
247621Y3-024
Adder
0.152
246938BC-WTG3
Solar/Wind Helper
11.223
246937BC-WTG2
Solar/Wind Helper
11.033
270224U2-072_GEN2
Solar/Wind Helper
0.966
270227U2-072_GEN3
Solar/Wind Helper
0.966
270228U2-072_GEN4
Solar/Wind Helper
0.966
270231U2-072_GEN5
Solar/Wind Helper
0.966
270471AD2-092_GEN
Solar/Wind Helper
1.12
253378AE2-206_GEN
Solar/Wind Helper
0.765
276820AF1-078_GEN
Solar/Wind Helper
0.357
241960AC2-195 GEN
Solar/Wind Helper
0.77
942991AE2-321 GEN
Solar/Wind Harmer
6.504
24727205RPMNG3
50/50
3.243
971599AH1-298 GEN
50/50
10.058
24729505KEY G4
50/50
6.532
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
16.143
965041AG1-368 GEN
Solar/Wind Harmer
11.642
270071AF1-092 GEN
Solar/Wind Harmer
15.699
965051AG1-369 GEN
Solar/Wind Harmer
4.914
958711AF2-162 GEN
Solar/Wind Harmer
0.88
270024AE2-089 GEN
Solar/Wind Harmer
4.014
965101AG1-375 GEN
Solar/Wind Harmer
8.444
971771AH1-392 GEN
Solar/Wind Harmer
7.295
971347AH1-153 GEN
Solar/Wind Harmer
12.051
945581AF1-223 GEN
Solar/Wind Harmer
3.606
971769AH1-391 GEN
Solar/Wind Harmer
7.796
944161AF1-084 GEN
Solar/Wind Harmer
1.712
960681AF2-359 GEN
Solar/Wind Harmer
2.885
274814UNIV PK N;0U
Adder
3.66
24727005RPMNG1
50/50
3.259
960861AF2-377 GEN
50/50
2.29
970521AG2-332 GEN
50/50
10.466
24639705ELKHART HY
50/50
0.145
965421AG1-410 GEN
Solar/Wind Harmer
115.488
965011AG1-365 GEN
Solar/Wind Harmer
19.324
270063AE2-323 C
Solar/Wind Harmer
2.274
247521TR3_G114
Solar/Wind Harmer
3.309
270246TR4_N_V150
Solar/Wind Harmer
0.837
944231AF1-091 GEN
Solar/Wind Harmer
3.613
965651AG1-433 GEN
Solar/Wind Harmer
4.756
24695305TIMB G C
Solar/Wind Harmer
4.723
958861AF2-177 GEN
Solar/Wind Harmer
9.23
945111AF1-176 GEN
Solar/Wind Harmer
14.654
270505AE1-170 C O1
Solar/Wind Harmer
12.008
945371AF1-202 GEN
Solar/Wind Harmer
5.548
270449AD2-020 GEN
Solar/Wind Harmer
2.207
943021AE2-325 GEN
Solar/Wind Harmer
2.867
970245AG2-165 GEN
Solar/Wind Harmer
13.188
970373AG2-245 GEN
Solar/Wind Harmer
15.45
274751CRETE EC ;1U
Adder
3.582
274754CRETE EC ;4U
Adder
3.582
274723RIVER EC ;12
Adder
13.089
274812UNIV PK N;8U
Adder
3.628
276164X3-005 C
Solar/Wind Harmer
0.509
270055AF2-134 C O1
Solar/Wind Harmer
2.19
972207SS24-0001
Solar/Wind Harmer
15.903
274773LINCOLN ;4U
Adder
4.473
274774LINCOLN ;5U
Adder
4.473
274801UNIV PARK;4U
Adder
4.167
276776AD2-060 GEN
Solar/Wind Harmer
0.302
958381AF2-132 GEN
Solar/Wind Harmer
6.462
964861AG1-349 GEN
Solar/Wind Harmer
5.59
971917AH1-482 GEN
Solar/Wind Harmer
6.451
941551AE2-152 GEN
Solar/Wind Harmer
3.205
274676JOLIET 29;8U
Adder
21.674
274674JOLIET 9 ;6U
Adder
10.853
274732ELWOOD EC;7P
Adder
11.581
274871GR RIDGE ;2U
Solar/Wind Harmer
5.389
940581AE2-045 GEN
Solar/Wind Harmer
7.111
971605AH1-302 GEN
Solar/Wind Harmer
6.081
274745AC1-111 GEN9
Adder
3.891
276691AA1-018 GEN1
Solar/Wind Harmer
0.322
274682WAUKEGAN ;7U
Adder
12.367
274828WAUKEGAN ;BP
Adder
7.591
970291AG2-192 GEN
Solar/Wind Harmer
0.891
960751AF2-366 GEN
Solar/Wind Harmer
1.955
962781AG1-127 GEN
Solar/Wind Harmer
6.479
939401AE1-172 GEN
Solar/Wind Harmer
9.489
276901AD2-066 C O1
Solar/Wind Harmer
2.391
270005AE1-210 C O1
Solar/Wind Harmer
3.716
965031AG1-367 GEN
Solar/Wind Harmer
6.8
274872LEEDK;1U
Solar/Wind Harmer
5.583
270032AE2-172
Solar/Wind Harmer
3.149
274822ROCKFORD ;11
Adder
13.092
972235AH1-702 GEN1
Adder
1.677
274761LEE CO EC;2U
Adder
6.098
274766LEE CO EC;7U
Adder
6.027
24728605AND G2
Adder
1.957
246936BC-WTG1
Solar/Wind Helper
11.033
270462AD2-086
Solar/Wind Helper
4.05
270223U2-072_GEN1
Solar/Wind Helper
0.966
270578AF1-285 GEN2
Solar/Wind Helper
0.654
270391AF1-285 GEN3
Solar/Wind Helper
0.654
247522W1-056 GEN
Solar/Wind Helper
1.243
960841AF2-375 GEN
Solar/Wind Helper
1.254
270349AD2-093_GEN
Solar/Wind Helper
1.12
274807UNIV PK N;3U
Adder
3.652
274805UNIV PK N;1U
Adder
3.636
274811UNIV PK N;7U
Adder
3.628
270536AF1-215 GEN2
Solar/Wind Harmer
3.286
274775LINCOLN ;6U
Adder
4.473
274776LINCOLN ;7U
Adder
4.473
274777LINCOLN ;8U
Adder
4.473
972037AH1-567 GEN1
Adder
0.131
274827FISK ;RP
Adder
5.556
960591AF2-350 GEN
Solar/Wind Harmer
7.138
972227AH1-698 GEN1
Adder
1.856
274687WILL CNTY;4U
Adder
19.783
274687WILL CNTY;4U
Adder
19.783
958391AF2-133 GEN
Solar/Wind Harmer
6.411
274675JOLIET 29;7U
Adder
21.674
274675JOLIET 29;7U
Adder
20.9
274731ELWOOD EC;2P
Adder
11.581
274733ELWOOD EC;3P
Adder
11.581
274735ELWOOD EC;4P
Adder
11.581
274728ELWOOD EC;5P
Adder
11.581
970833AG2-524 GEN
Solar/Wind Harmer
6.122
970833AG2-524 GEN
Solar/Wind Harmer
2.848
274746AC1-111 G10
Adder
3.891
274744AC1-111 GEN8
Adder
3.891
965461AG1-414 GEN
Solar/Wind Harmer
1.554
970289AG2-191 GEN
Solar/Wind Harmer
1.302
276868AE1-113 GEN
Solar/Wind Harmer
6.869
276882AE2-255 GEN
Solar/Wind Harmer
2.29
270594AE1-207 GEN
Solar/Wind Harmer
9.95
274823ROCKFORD ;21
Adder
12.997
957201AF2-014 GEN
Solar/Wind Helper
8.722
270317AD1-130_GEN
Solar/Wind Helper
4.487
966831AG1-554 GEN
Solar/Wind Helper
0.929
270284AF1-227 GEN1
Solar/Wind Helper
2.25
270286AF1-227 GEN2
Solar/Wind Helper
0.825
270287AF1-227 GEN3
Solar/Wind Helper
0.825
270499AE1-146 GEN
Solar/Wind Helper
2.084
945641AF1-229 GEN
Solar/Wind Helper
1.001
253383AE2-342_GEN
Solar/Wind Helper
0.365
965431AG1-411 GEN
50/50
44.763
24727105RPMNG2
50/50
3.27
970583AG2-370 GEN
50/50
2.707
959331AF2-224 GEN
Solar/Wind Harmer
19.324
965021AG1-366 GEN
Solar/Wind Harmer
4.494
970031AG2-029 GEN
Solar/Wind Harmer
35.17
270043AE2-236 GEN
Solar/Wind Harmer
6.202
270191TR4_S_V150
Solar/Wind Harmer
2.952
270247TR4_N_V136
Solar/Wind Harmer
0.837
944531AF1-118 GEN
Solar/Wind Harmer
34.207
971617AH1-308 GEN
Solar/Wind Harmer
4.972
247643Z2-116 C
Solar/Wind Harmer
0.059
945111AF1-176 GEN
Solar/Wind Harmer
4.644
970349AG2-230 GEN
Solar/Wind Harmer
12.051
24642205MAYFLWER
Adder
0.507
24441205WTRV SLR C
Solar/Wind Harmer
0.1
970513AG2-328 GEN
Solar/Wind Harmer
13.188
970517AG2-330 GEN
Solar/Wind Harmer
11.962
972231SS25-0005
Solar/Wind Harmer
6.955
972181SS23-001
Solar/Wind Harmer
4.347
274752CRETE EC ;2U
Adder
3.582
274753CRETE EC ;3U
Adder
3.582
274724RIVER EC ;11
Adder
12.93
270535AF1-215 GEN1
Solar/Wind Harmer
3.286
247604X1-042
Adder
0.301
274772LINCOLN ;3U
Adder
4.473
274802UNIV PARK;5U
Adder
4.179
274826FISK ;BP
Adder
7.839
274800UNIV PARK;3U
Adder
4.167
972038AH1-567 GEN2
Adder
0.261
276772AC2-154 GEN
Solar/Wind Harmer
1.991
276806AD2-047 C O1
Solar/Wind Harmer
7.636
970941AG2-585 GEN
Solar/Wind Harmer
8.923
964401AG1-302 GEN
Solar/Wind Harmer
6.462
972228AH1-698 GEN2
Adder
2.636
970707AG2-453 GEN
Solar/Wind Harmer
19.862
276897AD1-100 C
Solar/Wind Harmer
20.505
939351AE1-166 GEN
Solar/Wind Harmer
4.19
274676JOLIET 29;8U
Adder
20.899
276893AG1-478 C
Solar/Wind Harmer
0.294
274729ELWOOD EC;1P
Adder
11.581
274730ELWOOD EC;6P
Adder
11.581
274734ELWOOD EC;8P
Adder
11.581
274736ELWOOD EC;9P
Adder
11.581
959141AF2-205 GEN
Solar/Wind Harmer
4.247
943121AE2-341 GEN
Solar/Wind Harmer
10.446
943591AF1-030 GEN
Solar/Wind Harmer
6.964
247642Z2-115 C
Solar/Wind Harmer
0.044
276694AA1-018 GEN2
Solar/Wind Harmer
4.365
274682WAUKEGAN ;7U
Adder
12.367
970289AG2-191 GEN
Solar/Wind Harmer
0.526
970291AG2-192 GEN
Solar/Wind Harmer
0.478
276805AD2-038 GEN
Solar/Wind Harmer
3.503
958821AF2-173 GEN
Solar/Wind Harmer
9.521
270004AE1-209 GEN
Solar/Wind Harmer
3.716
274872LEEDK;1U
Solar/Wind Harmer
0.174
972236AH1-702 GEN2
Adder
1.459
274760LEE CO EC;1U
Adder
6.098
274767LEE CO EC;8U
Adder
6.027
24728705AND G3
Adder
4.093
24728505AND G1
Adder
1.957
270485AE1-090_GEN
Solar/Wind Helper
0.353
942871AE2-306 GEN
Solar/Wind Helper
0.491
270541AE2-072 C
Solar/Wind Helper
1.031
944201AF1-088_MTX
Adder
53.144
957141AF2-008_MTX
Adder
26.572
990497J1323
External Queue
1.5632063150405884
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.805
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.458
MECLTFEXP_MEC->PJM
CLTF
9.34
SIGELTFEXP_SIGE->PJM
CLTF
0.188
LAGNLTFEXP_LAGN->PJM
CLTF
5.535
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.597
TVALTFEXP_TVA->PJM
CLTF
2.211
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.279
NYPJM->LTFIMP_NY
CLTF
1.208
LGEELTFEXP_LGEE->PJM
CLTF
1.678
WECLTFEXP_WEC->PJM
CLTF
2.539
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
AG2-052LTFEXP_AG2-052->PJM
LTF
0.164
AH1-155LTFEXP_AH1-155->PJM
LTF
0.247

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.82 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2593.18
MW Contribution:5.46
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.308
960861AF2-377 GEN
50/50
2.399
970521AG2-332 GEN
50/50
10.806
24639705ELKHART HY
50/50
0.149
965421AG1-410 GEN
Solar/Wind Harmer
81.734
965011AG1-365 GEN
Solar/Wind Harmer
13.763
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.262
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.854
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.839
958861AF2-177 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
10.578
270505AE1-170 C O1
Solar/Wind Harmer
6.07
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.97
970245AG2-165 GEN
Solar/Wind Harmer
2.307
970373AG2-245 GEN
Solar/Wind Harmer
11.147
274751CRETE EC ;1U
Adder
6.241
274754CRETE EC ;4U
Adder
6.241
274723RIVER EC ;12
Adder
13.527
274812UNIV PK N;8U
Adder
3.75
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.292
274774LINCOLN ;5U
Adder
6.292
274801UNIV PARK;4U
Adder
4.307
276776AD2-060 GEN
Solar/Wind Harmer
0.537
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.671
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.401
274674JOLIET 9 ;6U
Adder
11.217
274732ELWOOD EC;7P
Adder
11.97
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.288
274745AC1-111 GEN9
Adder
4.021
276691AA1-018 GEN1
Solar/Wind Harmer
0.604
274682WAUKEGAN ;7U
Adder
12.782
970291AG2-192 GEN
Solar/Wind Harmer
0.645
274828WAUKEGAN ;BP
Adder
7.846
270005AE1-210 C O1
Solar/Wind Harmer
1.068
965031AG1-367 GEN
Solar/Wind Harmer
4.929
962781AG1-127 GEN
Solar/Wind Harmer
4.676
939401AE1-172 GEN
Solar/Wind Harmer
3.674
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.269
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.559
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.477
959081AF2-199 GEN
Solar/Wind Harmer
4.826
971067AG2-660 GEN
Solar/Wind Harmer
1.609
274822ROCKFORD ;11
Adder
13.533
970825AG2-519 GEN
Solar/Wind Harmer
1.705
972235AH1-702 GEN1
Adder
1.734
970819AG2-516 GEN
Solar/Wind Harmer
5.74
970569AG2-363 GEN
Solar/Wind Harmer
14.338
971475AH1-234 GEN
Solar/Wind Harmer
2.315
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.304
274766LEE CO EC;7U
Adder
6.23
276903AD2-071 C
Solar/Wind Harmer
5.249
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.156
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.437
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.624
963741AG1-226 GEN
Solar/Wind Harmer
10.327
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.19
247536S-71 GEN
Solar/Wind Harmer
0.173
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.654
276615X2-022 GEN
Solar/Wind Harmer
0.044
965911AG1-460 GEN
Solar/Wind Harmer
0.808
24728605AND G2
Adder
2.043
970773AG2-487 GEN
Solar/Wind Harmer
0.609
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.215
246936BC-WTG1
Solar/Wind Helper
10.895
270462AD2-086
Solar/Wind Helper
3.714
270223U2-072_GEN1
Solar/Wind Helper
0.871
270578AF1-285 GEN2
Solar/Wind Helper
0.59
270391AF1-285 GEN3
Solar/Wind Helper
0.59
247522W1-056 GEN
Solar/Wind Helper
1.168
960841AF2-375 GEN
Solar/Wind Helper
1.175
270349AD2-093_GEN
Solar/Wind Helper
0.85
970615AG2-402 GEN
50/50
4.588
24729405KEY G3
50/50
0.368
24729305KEY G2
50/50
0.361
24729205KEY G1
50/50
0.36
247620Y3-023
50/50
0.463
970611AG2-400 GEN
Solar/Wind Harmer
13.763
970627AG2-408 GEN
Solar/Wind Harmer
4.129
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.42
960971AF2-388 GEN
Solar/Wind Harmer
3.679
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.557
961051AF2-396 GEN
Solar/Wind Harmer
7.705
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.887
965791AG1-447 GEN
Solar/Wind Harmer
5.051
270599AE1-208 GEN
Solar/Wind Harmer
4.993
270031AE2-169
Solar/Wind Harmer
2.996
970321AG2-212 GEN
Solar/Wind Harmer
2.307
274808UNIV PK N;4U
Adder
3.733
274770LINCOLN ;1U
Adder
6.292
274771LINCOLN ;2U
Adder
6.292
274803UNIV PARK;6U
Adder
4.319
274888KELLY CRK;1U
Solar/Wind Harmer
0.302
274887GEN-1.85
Solar/Wind Harmer
0.136
276843GEN-1.7
Solar/Wind Harmer
0.167
958011AF2-095 GEN
Solar/Wind Harmer
7.412
972259AH1-714 GEN
Adder
13.99
274674JOLIET 9 ;6U
Adder
11.217
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.931
958481AF2-142 GEN
Solar/Wind Harmer
7.482
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.675
274695ROCKY RD ;2P
Adder
7.922
274693ROCKY RD ;1P
Adder
7.844
274697ROCKY RD ;3P
Adder
2.152
274696ROCKY RD ;4P
Adder
8.109
274683WAUKEGAN ;8U
Adder
14.968
274683WAUKEGAN ;8U
Adder
12.617
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.776
958491AF2-143 GEN
Solar/Wind Harmer
7.388
970921AG2-575 GEN
Solar/Wind Harmer
4.913
970921AG2-575 GEN
Solar/Wind Harmer
1.638
971613AH1-306 GEN
Solar/Wind Harmer
2.354
274879MINONK ;1U
Solar/Wind Harmer
0.207
942991AE2-321 GEN
Solar/Wind Harmer
5.451
971333AH1-146 GEN
Solar/Wind Harmer
9.71
971335AH1-147 GEN
Solar/Wind Harmer
9.71
960441AF2-335 GEN
Solar/Wind Harmer
4.841
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.652
971343AH1-151 GEN
Solar/Wind Harmer
9.652
970825AG2-519 GEN
Solar/Wind Harmer
5.324
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.689
274764LEE CO EC;5U
Adder
6.319
274765LEE CO EC;6U
Adder
6.319
274762LEE CO EC;3U
Adder
6.304
274763LEE CO EC;4U
Adder
6.245
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.354
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.793
276741O09 GEN1
Solar/Wind Harmer
0.166
276708O09 GEN2
Solar/Wind Harmer
0.166
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
966841AG1-555 GEN
Solar/Wind Harmer
0.525
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.16
960611AF2-352 GEN
Solar/Wind Harmer
1.506
970241AG2-163 GEN
Solar/Wind Harmer
2.545
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.413
276911AD2-131_GEN
Solar/Wind Harmer
0.554
970883AG2-550 GEN
Solar/Wind Harmer
3.912
970885AG2-551 GEN
Solar/Wind Harmer
1.304
945391AF1-204 GEN
Solar/Wind Harmer
4.152
970623AG2-406 GEN
Solar/Wind Harmer
0.681
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.427
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.774
246938BC-WTG3
Solar/Wind Helper
11.083
246937BC-WTG2
Solar/Wind Helper
10.895
270224U2-072_GEN2
Solar/Wind Helper
0.871
270227U2-072_GEN3
Solar/Wind Helper
0.871
270228U2-072_GEN4
Solar/Wind Helper
0.871
270231U2-072_GEN5
Solar/Wind Helper
0.871
270471AD2-092_GEN
Solar/Wind Helper
0.85
253378AE2-206_GEN
Solar/Wind Helper
0.684
276820AF1-078_GEN
Solar/Wind Helper
0.319
241960AC2-195 GEN
Solar/Wind Helper
0.69
965431AG1-411 GEN
50/50
45.408
24727105RPMNG2
50/50
3.32
970583AG2-370 GEN
50/50
2.809
959331AF2-224 GEN
Solar/Wind Harmer
9.634
965021AG1-366 GEN
Solar/Wind Harmer
4.588
970031AG2-029 GEN
Solar/Wind Harmer
5.463
270043AE2-236 GEN
Solar/Wind Harmer
5.191
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.488
971617AH1-308 GEN
Solar/Wind Harmer
5.166
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.805
970349AG2-230 GEN
Solar/Wind Harmer
8.688
24642205MAYFLWER
Adder
0.524
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.307
970517AG2-330 GEN
Solar/Wind Harmer
13.84
274752CRETE EC ;2U
Adder
6.241
274753CRETE EC ;3U
Adder
6.241
274724RIVER EC ;11
Adder
13.364
247604X1-042
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.292
274802UNIV PARK;5U
Adder
4.319
274826FISK ;BP
Adder
8.102
274800UNIV PARK;3U
Adder
4.307
972038AH1-567 GEN2
Adder
0.27
276806AD2-047 C O1
Solar/Wind Harmer
2.917
970941AG2-585 GEN
Solar/Wind Harmer
6.434
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.725
970707AG2-453 GEN
Solar/Wind Harmer
16.709
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.601
276893AG1-478 C
Solar/Wind Harmer
0.201
274730ELWOOD EC;6P
Adder
11.97
274734ELWOOD EC;8P
Adder
11.97
274736ELWOOD EC;9P
Adder
11.97
274729ELWOOD EC;1P
Adder
11.97
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.419
943591AF1-030 GEN
Solar/Wind Harmer
5.599
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.782
970289AG2-191 GEN
Solar/Wind Harmer
0.545
970291AG2-192 GEN
Solar/Wind Harmer
0.496
958821AF2-173 GEN
Solar/Wind Harmer
6.901
270004AE1-209 GEN
Solar/Wind Harmer
1.068
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.18
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.518
274855GSG-6 ;RU
Solar/Wind Harmer
0.178
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.087
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.834
959091AF2-200 GEN
Solar/Wind Harmer
9.652
972236AH1-702 GEN2
Adder
1.508
970571AG2-364 GEN
Solar/Wind Harmer
9.558
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.304
274767LEE CO EC;8U
Adder
6.23
946031AF1-268 GEN
Solar/Wind Harmer
4.492
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.069
276157O29GEN1
Solar/Wind Harmer
0.755
274878BISHOP HL;2U
Solar/Wind Harmer
0.156
942111AE2-223 GEN
Solar/Wind Harmer
1.494
965931AG1-462 GEN
Solar/Wind Harmer
11.522
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.551
959611AF2-252 GEN
Solar/Wind Harmer
1.506
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.156
971993AH1-541 GEN
Solar/Wind Harmer
1.971
276621W2-048 GEN
Solar/Wind Harmer
0.211
276838X2-022 GEN2
Solar/Wind Harmer
0.236
942481AE2-261 GEN
Solar/Wind Harmer
12.085
970193AG2-126 GEN
Solar/Wind Harmer
5.861
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.272
24728505AND G1
Adder
2.043
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.812
970519AG2-331 GEN
Solar/Wind Harmer
8.054
970699AG2-449 GEN
Solar/Wind Harmer
0.774
270485AE1-090_GEN
Solar/Wind Helper
0.323
942871AE2-306 GEN
Solar/Wind Helper
0.443
270541AE2-072 C
Solar/Wind Helper
0.932
24727205RPMNG3
50/50
3.292
971599AH1-298 GEN
50/50
10.333
24729505KEY G4
50/50
6.735
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
11.606
965041AG1-368 GEN
Solar/Wind Harmer
8.426
270071AF1-092 GEN
Solar/Wind Harmer
14.399
965051AG1-369 GEN
Solar/Wind Harmer
3.592
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.088
971771AH1-392 GEN
Solar/Wind Harmer
5.847
971347AH1-153 GEN
Solar/Wind Harmer
8.688
971619AH1-309 GEN
Solar/Wind Harmer
2.601
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.283
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.89
274814UNIV PK N;0U
Adder
3.782
274807UNIV PK N;3U
Adder
3.774
274805UNIV PK N;1U
Adder
3.758
274811UNIV PK N;7U
Adder
3.75
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.292
274776LINCOLN ;7U
Adder
6.292
274777LINCOLN ;8U
Adder
6.292
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.742
960591AF2-350 GEN
Solar/Wind Harmer
5.147
972227AH1-698 GEN1
Adder
1.919
274687WILL CNTY;4U
Adder
20.447
274687WILL CNTY;4U
Adder
20.447
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.401
274675JOLIET 29;7U
Adder
21.601
274728ELWOOD EC;5P
Adder
11.97
274731ELWOOD EC;2P
Adder
11.97
274733ELWOOD EC;3P
Adder
11.97
274735ELWOOD EC;4P
Adder
11.97
970833AG2-524 GEN
Solar/Wind Harmer
5.563
970833AG2-524 GEN
Solar/Wind Harmer
3.709
971611AH1-305 GEN
Solar/Wind Harmer
2.995
274746AC1-111 G10
Adder
4.021
274744AC1-111 GEN8
Adder
4.021
970289AG2-191 GEN
Solar/Wind Harmer
0.942
270594AE1-207 GEN
Solar/Wind Harmer
5.492
276868AE1-113 GEN
Solar/Wind Harmer
0.982
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971177AH1-047 GEN
Solar/Wind Harmer
3.009
971411AH1-196 GEN
Solar/Wind Harmer
7.289
971675AH1-338 GEN
Solar/Wind Harmer
1.894
970115AG2-085 GEN
Solar/Wind Harmer
1.936
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.652
274823ROCKFORD ;21
Adder
13.435
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
4.764
971681AH1-341 GEN
Solar/Wind Harmer
7.643
971549AH1-272 GEN
Solar/Wind Harmer
9.793
961011AF2-392 GEN
Solar/Wind Harmer
2.754
957751AF2-069 GEN
Solar/Wind Harmer
0.154
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.828
941731AE2-173 GEN
Solar/Wind Harmer
3.831
946321AF1-296 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.949
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.156
276848AB2-070 GEN3
Solar/Wind Harmer
0.155
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.279
971029AG2-637 GEN
Solar/Wind Harmer
5.242
971673AH1-337 GEN
Solar/Wind Harmer
2.175
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.613
270317AD1-130_GEN
Solar/Wind Helper
4.113
966831AG1-554 GEN
Solar/Wind Helper
0.876
270284AF1-227 GEN1
Solar/Wind Helper
1.876
270286AF1-227 GEN2
Solar/Wind Helper
0.688
270287AF1-227 GEN3
Solar/Wind Helper
0.688
270499AE1-146 GEN
Solar/Wind Helper
1.952
945641AF1-229 GEN
Solar/Wind Helper
0.937
944201AF1-088_MTX
Adder
55.165
957141AF2-008_MTX
Adder
17.696
990497J1323
External Queue
1.5914489030838013
990792J1392
External Queue
5.474584102630615
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.309
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.744
MECLTFEXP_MEC->PJM
CLTF
9.656
SIGELTFEXP_SIGE->PJM
CLTF
0.197
LAGNLTFEXP_LAGN->PJM
CLTF
5.694
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.439
TVALTFEXP_TVA->PJM
CLTF
2.27
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.944
NYPJM->LTFIMP_NY
CLTF
1.265
LGEELTFEXP_LGEE->PJM
CLTF
1.782
WECLTFEXP_WEC->PJM
CLTF
2.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.96 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2296.84
MW Contribution:30.01
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.122
965421AG1-410 GEN
Solar/Wind Harmer
111.394
965011AG1-365 GEN
Solar/Wind Harmer
17.622
270063AE2-323 C
Solar/Wind Harmer
1.892
247521TR3_G114
Solar/Wind Harmer
2.813
270246TR4_N_V150
Solar/Wind Harmer
0.712
944231AF1-091 GEN
Solar/Wind Harmer
3.029
965651AG1-433 GEN
Solar/Wind Harmer
3.914
24639705ELKHART HY
Adder
0.11
24695305TIMB G C
Solar/Wind Harmer
3.924
958861AF2-177 GEN
Solar/Wind Harmer
7.588
945371AF1-202 GEN
Solar/Wind Harmer
4.55
945111AF1-176 GEN
Solar/Wind Harmer
11.565
270505AE1-170 C O1
Solar/Wind Harmer
9.4
270449AD2-020 GEN
Solar/Wind Harmer
1.724
943021AE2-325 GEN
Solar/Wind Harmer
2.24
970373AG2-245 GEN
Solar/Wind Harmer
12.06
274751CRETE EC ;1U
Adder
2.789
274754CRETE EC ;4U
Adder
2.789
274723RIVER EC ;12
Adder
10.178
270055AF2-134 C O1
Solar/Wind Harmer
1.715
274812UNIV PK N;8U
Adder
2.821
276164X3-005 C
Solar/Wind Harmer
0.395
970245AG2-165 GEN
Solar/Wind Harmer
10.037
958381AF2-132 GEN
Solar/Wind Harmer
5.071
964861AG1-349 GEN
Solar/Wind Harmer
4.388
971917AH1-482 GEN
Solar/Wind Harmer
5.063
972207SS24-0001
Solar/Wind Harmer
12.284
274773LINCOLN ;4U
Adder
3.455
274774LINCOLN ;5U
Adder
3.455
274801UNIV PARK;4U
Adder
3.236
276776AD2-060 GEN
Solar/Wind Harmer
0.234
970291AG2-192 GEN
Solar/Wind Harmer
0.72
270005AE1-210 C O1
Solar/Wind Harmer
3.027
965031AG1-367 GEN
Solar/Wind Harmer
5.538
940581AE2-045 GEN
Solar/Wind Harmer
5.6
971605AH1-302 GEN
Solar/Wind Harmer
4.789
274676JOLIET 29;8U
Adder
16.827
941551AE2-152 GEN
Solar/Wind Harmer
2.486
270032AE2-172
Solar/Wind Harmer
2.548
274674JOLIET 9 ;6U
Adder
8.426
274732ELWOOD EC;7P
Adder
8.993
274871GR RIDGE ;2U
Solar/Wind Harmer
4.181
274745AC1-111 GEN9
Adder
3.019
970825AG2-519 GEN
Solar/Wind Harmer
1.267
276691AA1-018 GEN1
Solar/Wind Harmer
0.25
274682WAUKEGAN ;7U
Adder
9.61
274828WAUKEGAN ;BP
Adder
5.899
24791305MDL-5G
Solar/Wind Harmer
1.278
274822ROCKFORD ;11
Adder
10.194
972235AH1-702 GEN1
Adder
1.306
274761LEE CO EC;2U
Adder
4.754
274766LEE CO EC;7U
Adder
4.698
246936BC-WTG1
Solar/Wind Helper
11.356
270462AD2-086
Solar/Wind Helper
4.257
270223U2-072_GEN1
Solar/Wind Helper
1.016
270578AF1-285 GEN2
Solar/Wind Helper
0.688
270391AF1-285 GEN3
Solar/Wind Helper
0.688
247522W1-056 GEN
Solar/Wind Helper
1.336
960841AF2-375 GEN
Solar/Wind Helper
1.368
270349AD2-093_GEN
Solar/Wind Helper
1.192
241840AF1-064_GEN
Solar/Wind Helper
0.485
241807AE2-176_GEN
Solar/Wind Helper
0.7
276901AD2-066 C O1
Solar/Wind Harmer
1.531
965431AG1-411 GEN
50/50
43.176
24727105RPMNG2
50/50
3.133
970583AG2-370 GEN
50/50
2.348
959331AF2-224 GEN
Solar/Wind Harmer
17.622
965021AG1-366 GEN
Solar/Wind Harmer
4.098
970031AG2-029 GEN
Solar/Wind Harmer
30.007
270043AE2-236 GEN
Solar/Wind Harmer
5.199
270191TR4_S_V150
Solar/Wind Harmer
2.51
270247TR4_N_V136
Solar/Wind Harmer
0.712
944531AF1-118 GEN
Solar/Wind Harmer
28.273
971617AH1-308 GEN
Solar/Wind Harmer
4.203
247643Z2-116 C
Solar/Wind Harmer
0.047
945111AF1-176 GEN
Solar/Wind Harmer
3.665
24642205MAYFLWER
Adder
0.397
970349AG2-230 GEN
Solar/Wind Harmer
9.292
24441205WTRV SLR C
Solar/Wind Harmer
0.078
972231SS25-0005
Solar/Wind Harmer
5.415
972181SS23-001
Solar/Wind Harmer
3.384
274752CRETE EC ;2U
Adder
2.789
274753CRETE EC ;3U
Adder
2.789
274724RIVER EC ;11
Adder
10.053
270535AF1-215 GEN1
Solar/Wind Harmer
2.572
970513AG2-328 GEN
Solar/Wind Harmer
10.037
970517AG2-330 GEN
Solar/Wind Harmer
9.103
247642Z2-115 C
Solar/Wind Harmer
0.036
964401AG1-302 GEN
Solar/Wind Harmer
5.071
274772LINCOLN ;3U
Adder
3.455
274802UNIV PARK;5U
Adder
3.247
274826FISK ;BP
Adder
6.089
274800UNIV PARK;3U
Adder
3.236
972038AH1-567 GEN2
Adder
0.203
276772AC2-154 GEN
Solar/Wind Harmer
1.545
276806AD2-047 C O1
Solar/Wind Harmer
5.929
970941AG2-585 GEN
Solar/Wind Harmer
6.927
970289AG2-191 GEN
Solar/Wind Harmer
0.425
970291AG2-192 GEN
Solar/Wind Harmer
0.386
958821AF2-173 GEN
Solar/Wind Harmer
7.753
270004AE1-209 GEN
Solar/Wind Harmer
3.027
247604X1-042
Adder
0.231
959141AF2-205 GEN
Solar/Wind Harmer
3.34
972228AH1-698 GEN2
Adder
2.046
970707AG2-453 GEN
Solar/Wind Harmer
15.375
274676JOLIET 29;8U
Adder
16.226
276897AD1-100 C
Solar/Wind Harmer
15.905
939351AE1-166 GEN
Solar/Wind Harmer
3.25
276893AG1-478 C
Solar/Wind Harmer
0.229
274729ELWOOD EC;1P
Adder
8.992
274730ELWOOD EC;6P
Adder
8.993
274734ELWOOD EC;8P
Adder
8.993
274736ELWOOD EC;9P
Adder
8.993
943121AE2-341 GEN
Solar/Wind Harmer
8.102
943591AF1-030 GEN
Solar/Wind Harmer
5.401
276694AA1-018 GEN2
Solar/Wind Harmer
3.395
274682WAUKEGAN ;7U
Adder
9.61
276805AD2-038 GEN
Solar/Wind Harmer
2.727
24755605MDL-5G
Solar/Wind Harmer
1.278
970781AG2-491 GEN
Solar/Wind Harmer
5.299
972236AH1-702 GEN2
Adder
1.136
274760LEE CO EC;1U
Adder
4.754
274767LEE CO EC;8U
Adder
4.698
270485AE1-090_GEN
Solar/Wind Helper
0.37
942871AE2-306 GEN
Solar/Wind Helper
0.516
270541AE2-072 C
Solar/Wind Helper
1.202
970615AG2-402 GEN
50/50
4.098
970611AG2-400 GEN
Solar/Wind Harmer
17.622
942221AE2-234 GEN
Solar/Wind Harmer
0.583
247620Y3-023
Adder
0.343
944541AF1-119 GEN
Solar/Wind Harmer
3
960971AF2-388 GEN
Solar/Wind Harmer
7.829
270216AD2-079_GEN
Solar/Wind Harmer
0.412
960981AF2-389 GEN
Solar/Wind Harmer
0.958
957891AF2-083 GEN
Solar/Wind Harmer
2.135
961051AF2-396 GEN
Solar/Wind Harmer
9.957
961051AF2-396 GEN
Solar/Wind Harmer
4.631
270599AE1-208 GEN
Solar/Wind Harmer
5.045
270031AE2-169
Solar/Wind Harmer
5.045
270526AF1-158 GEN
Solar/Wind Harmer
2.787
24441505OLIV SLR
Solar/Wind Harmer
0.081
965681AG1-436 GEN
Solar/Wind Harmer
7.408
965791AG1-447 GEN
Solar/Wind Harmer
3.79
274808UNIV PK N;4U
Adder
2.809
970321AG2-212 GEN
Solar/Wind Harmer
10.037
274770LINCOLN ;1U
Adder
3.455
274771LINCOLN ;2U
Adder
3.455
274803UNIV PARK;6U
Adder
3.247
274888KELLY CRK;1U
Solar/Wind Harmer
3.272
274887GEN-1.85
Solar/Wind Harmer
2.954
276843GEN-1.7
Solar/Wind Harmer
0.318
958011AF2-095 GEN
Solar/Wind Harmer
7.98
972259AH1-714 GEN
Adder
10.492
274674JOLIET 9 ;6U
Adder
8.426
274847GR RIDGE ;BU
Solar/Wind Harmer
2.75
960441AF2-335 GEN
Solar/Wind Harmer
5.431
945421AF1-207 GEN
Solar/Wind Harmer
7.58
957841AF2-078 GEN
Solar/Wind Harmer
3.262
970825AG2-519 GEN
Solar/Wind Harmer
5.68
958481AF2-142 GEN
Solar/Wind Harmer
8.069
274861TOP CROP ;1U
Solar/Wind Harmer
3.259
274862TOP CROP ;2U
Solar/Wind Harmer
2.721
971573AH1-285 GEN
Solar/Wind Harmer
4.623
274696ROCKY RD ;4P
Adder
6.094
274695ROCKY RD ;2P
Adder
5.954
274693ROCKY RD ;1P
Adder
5.895
274697ROCKY RD ;3P
Adder
1.617
274683WAUKEGAN ;8U
Adder
11.254
274683WAUKEGAN ;8U
Adder
9.487
958491AF2-143 GEN
Solar/Wind Harmer
7.973
962691AG1-118 GEN
Solar/Wind Harmer
15.922
247621Y3-024
Adder
0.124
274764LEE CO EC;5U
Adder
4.766
274765LEE CO EC;6U
Adder
4.766
274762LEE CO EC;3U
Adder
4.754
274763LEE CO EC;4U
Adder
4.71
972267AH1-718 GEN
Adder
2.108
246938BC-WTG3
Solar/Wind Helper
11.551
246937BC-WTG2
Solar/Wind Helper
11.356
270224U2-072_GEN2
Solar/Wind Helper
1.016
270227U2-072_GEN3
Solar/Wind Helper
1.016
270228U2-072_GEN4
Solar/Wind Helper
1.016
270231U2-072_GEN5
Solar/Wind Helper
1.016
270471AD2-092_GEN
Solar/Wind Helper
1.192
253378AE2-206_GEN
Solar/Wind Helper
0.835
276820AF1-078_GEN
Solar/Wind Helper
0.39
241960AC2-195 GEN
Solar/Wind Helper
0.828
24727205RPMNG3
50/50
3.107
971599AH1-298 GEN
50/50
8.317
963791AG1-232 GEN
Solar/Wind Harmer
14.105
965041AG1-368 GEN
Solar/Wind Harmer
10.094
270071AF1-092 GEN
Solar/Wind Harmer
13.076
965051AG1-369 GEN
Solar/Wind Harmer
4.177
24729505KEY G4
Adder
5.083
270024AE2-089 GEN
Solar/Wind Harmer
3.393
958711AF2-162 GEN
Solar/Wind Harmer
0.725
965101AG1-375 GEN
Solar/Wind Harmer
6.942
945581AF1-223 GEN
Solar/Wind Harmer
2.958
971771AH1-392 GEN
Solar/Wind Harmer
5.726
971347AH1-153 GEN
Solar/Wind Harmer
9.292
971769AH1-391 GEN
Solar/Wind Harmer
6.078
944161AF1-084 GEN
Solar/Wind Harmer
1.333
960681AF2-359 GEN
Solar/Wind Harmer
2.239
270536AF1-215 GEN2
Solar/Wind Harmer
2.572
274814UNIV PK N;0U
Adder
2.846
274807UNIV PK N;3U
Adder
2.84
274805UNIV PK N;1U
Adder
2.827
274811UNIV PK N;7U
Adder
2.821
274775LINCOLN ;6U
Adder
3.455
274776LINCOLN ;7U
Adder
3.455
274777LINCOLN ;8U
Adder
3.455
972037AH1-567 GEN1
Adder
0.102
274827FISK ;RP
Adder
4.315
958391AF2-133 GEN
Solar/Wind Harmer
5.037
960591AF2-350 GEN
Solar/Wind Harmer
5.542
965461AG1-414 GEN
Solar/Wind Harmer
1.256
970289AG2-191 GEN
Solar/Wind Harmer
1.053
972227AH1-698 GEN1
Adder
1.44
274687WILL CNTY;4U
Adder
15.362
274687WILL CNTY;4U
Adder
15.362
274675JOLIET 29;7U
Adder
16.827
274675JOLIET 29;7U
Adder
16.226
270594AE1-207 GEN
Solar/Wind Harmer
8.053
274731ELWOOD EC;2P
Adder
8.992
274733ELWOOD EC;3P
Adder
8.992
274735ELWOOD EC;4P
Adder
8.992
274728ELWOOD EC;5P
Adder
8.993
970833AG2-524 GEN
Solar/Wind Harmer
4.75
970833AG2-524 GEN
Solar/Wind Harmer
2.209
970115AG2-085 GEN
Solar/Wind Harmer
2.173
274746AC1-111 G10
Adder
3.019
274744AC1-111 GEN8
Adder
3.019
24690905MDL-1G C
Solar/Wind Harmer
4.255
270180AB1-006 GEN1
Solar/Wind Harmer
3.812
946581AF1-322 GEN
Solar/Wind Harmer
5.422
24691005MDL-2G C
Solar/Wind Harmer
1.96
24697605MDL-3G C
Solar/Wind Harmer
1.954
24697905MDL-4G C
Solar/Wind Harmer
1.216
270181AB1-006 GEN2
Solar/Wind Harmer
0.379
274823ROCKFORD ;21
Adder
10.12
957201AF2-014 GEN
Solar/Wind Helper
8.977
270317AD1-130_GEN
Solar/Wind Helper
4.715
966831AG1-554 GEN
Solar/Wind Helper
0.991
270284AF1-227 GEN1
Solar/Wind Helper
2.381
270286AF1-227 GEN2
Solar/Wind Helper
0.873
270287AF1-227 GEN3
Solar/Wind Helper
0.873
270499AE1-146 GEN
Solar/Wind Helper
2.27
945641AF1-229 GEN
Solar/Wind Helper
1.091
253383AE2-342_GEN
Solar/Wind Helper
0.4
990497J1323
External Queue
1.411980390548706
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.78
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.457
MECLTFEXP_MEC->PJM
CLTF
7.38
SIGELTFEXP_SIGE->PJM
CLTF
0.152
LAGNLTFEXP_LAGN->PJM
CLTF
4.78
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.617
TVALTFEXP_TVA->PJM
CLTF
1.99
CPLELTFEXP_CPLE->PJM
CLTF
0.236
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.907
NYPJM->LTFIMP_NY
CLTF
0.985
LGEELTFEXP_LGEE->PJM
CLTF
1.351
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.129
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.83 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2201.01
MW Contribution:29.92
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.108
970611AG2-400 GEN
Solar/Wind Harmer
17.665
942221AE2-234 GEN
Solar/Wind Harmer
0.58
247620Y3-023
Adder
0.341
944541AF1-119 GEN
Solar/Wind Harmer
2.902
960971AF2-388 GEN
Solar/Wind Harmer
7.574
270216AD2-079_GEN
Solar/Wind Harmer
0.408
960981AF2-389 GEN
Solar/Wind Harmer
0.951
957891AF2-083 GEN
Solar/Wind Harmer
2.119
961051AF2-396 GEN
Solar/Wind Harmer
9.895
961051AF2-396 GEN
Solar/Wind Harmer
4.602
270599AE1-208 GEN
Solar/Wind Harmer
4.984
270031AE2-169
Solar/Wind Harmer
4.984
270526AF1-158 GEN
Solar/Wind Harmer
2.77
24441505OLIV SLR
Solar/Wind Harmer
0.081
965681AG1-436 GEN
Solar/Wind Harmer
7.379
965791AG1-447 GEN
Solar/Wind Harmer
3.775
945421AF1-207 GEN
Solar/Wind Harmer
8.076
957841AF2-078 GEN
Solar/Wind Harmer
3.475
970321AG2-212 GEN
Solar/Wind Harmer
10.209
274808UNIV PK N;4U
Adder
2.797
274803UNIV PARK;6U
Adder
3.231
274770LINCOLN ;1U
Adder
3.422
274771LINCOLN ;2U
Adder
3.422
274888KELLY CRK;1U
Solar/Wind Harmer
3.256
274887GEN-1.85
Solar/Wind Harmer
2.939
276843GEN-1.7
Solar/Wind Harmer
0.316
958011AF2-095 GEN
Solar/Wind Harmer
7.941
966841AG1-555 GEN
Solar/Wind Harmer
1.376
972259AH1-714 GEN
Adder
10.427
274674JOLIET 9 ;6U
Adder
8.385
970239AG2-162 GEN
Solar/Wind Harmer
5.948
274847GR RIDGE ;BU
Solar/Wind Harmer
2.738
960441AF2-335 GEN
Solar/Wind Harmer
5.38
274696ROCKY RD ;4P
Adder
6.063
274695ROCKY RD ;2P
Adder
5.923
274693ROCKY RD ;1P
Adder
5.865
274697ROCKY RD ;3P
Adder
1.609
274683WAUKEGAN ;8U
Adder
11.198
274683WAUKEGAN ;8U
Adder
9.439
247621Y3-024
Adder
0.126
274764LEE CO EC;5U
Adder
4.752
274765LEE CO EC;6U
Adder
4.752
274762LEE CO EC;3U
Adder
4.74
274763LEE CO EC;4U
Adder
4.696
972267AH1-718 GEN
Adder
2.103
246938BC-WTG3
Solar/Wind Helper
11.385
246937BC-WTG2
Solar/Wind Helper
11.192
270224U2-072_GEN2
Solar/Wind Helper
0.82
270227U2-072_GEN3
Solar/Wind Helper
0.82
270228U2-072_GEN4
Solar/Wind Helper
0.82
965431AG1-411 GEN
50/50
43.89
24727105RPMNG2
50/50
3.18
970583AG2-370 GEN
50/50
2.4
959331AF2-224 GEN
Solar/Wind Harmer
17.665
965021AG1-366 GEN
Solar/Wind Harmer
4.108
970031AG2-029 GEN
Solar/Wind Harmer
29.917
270043AE2-236 GEN
Solar/Wind Harmer
5.102
270191TR4_S_V150
Solar/Wind Harmer
2.613
270247TR4_N_V136
Solar/Wind Harmer
0.741
944531AF1-118 GEN
Solar/Wind Harmer
27.247
971617AH1-308 GEN
Solar/Wind Harmer
4.236
247643Z2-116 C
Solar/Wind Harmer
0.047
945111AF1-176 GEN
Solar/Wind Harmer
3.641
24642205MAYFLWER
Adder
0.394
970349AG2-230 GEN
Solar/Wind Harmer
9.093
270535AF1-215 GEN1
Solar/Wind Harmer
2.65
964401AG1-302 GEN
Solar/Wind Harmer
5.27
959141AF2-205 GEN
Solar/Wind Harmer
3.5
247642Z2-115 C
Solar/Wind Harmer
0.037
24441205WTRV SLR C
Solar/Wind Harmer
0.077
970513AG2-328 GEN
Solar/Wind Harmer
10.209
970517AG2-330 GEN
Solar/Wind Harmer
9.26
972231SS25-0005
Solar/Wind Harmer
5.394
972181SS23-001
Solar/Wind Harmer
3.371
274752CRETE EC ;2U
Adder
2.778
274753CRETE EC ;3U
Adder
2.778
970289AG2-191 GEN
Solar/Wind Harmer
0.436
970291AG2-192 GEN
Solar/Wind Harmer
0.396
24755605MDL-5G
Solar/Wind Harmer
1.366
24727005RPMNG1
50/50
3.169
960861AF2-377 GEN
50/50
2.027
965421AG1-410 GEN
Solar/Wind Harmer
113.236
965011AG1-365 GEN
Solar/Wind Harmer
17.665
247521TR3_G114
Solar/Wind Harmer
2.928
270246TR4_N_V150
Solar/Wind Harmer
0.741
270063AE2-323 C
Solar/Wind Harmer
1.881
944231AF1-091 GEN
Solar/Wind Harmer
3.082
24695305TIMB G C
Solar/Wind Harmer
4.125
24639705ELKHART HY
Adder
0.109
965651AG1-433 GEN
Solar/Wind Harmer
3.787
958861AF2-177 GEN
Solar/Wind Harmer
7.349
945111AF1-176 GEN
Solar/Wind Harmer
11.488
945371AF1-202 GEN
Solar/Wind Harmer
4.417
270505AE1-170 C O1
Solar/Wind Harmer
9.327
270449AD2-020 GEN
Solar/Wind Harmer
1.713
943021AE2-325 GEN
Solar/Wind Harmer
2.226
970373AG2-245 GEN
Solar/Wind Harmer
12.302
270055AF2-134 C O1
Solar/Wind Harmer
1.766
958381AF2-132 GEN
Solar/Wind Harmer
5.27
964861AG1-349 GEN
Solar/Wind Harmer
4.565
971917AH1-482 GEN
Solar/Wind Harmer
5.268
940581AE2-045 GEN
Solar/Wind Harmer
5.894
971605AH1-302 GEN
Solar/Wind Harmer
5.04
970245AG2-165 GEN
Solar/Wind Harmer
10.209
274751CRETE EC ;1U
Adder
2.778
274754CRETE EC ;4U
Adder
2.778
970291AG2-192 GEN
Solar/Wind Harmer
0.738
24727205RPMNG3
50/50
3.153
971599AH1-298 GEN
50/50
7.987
963791AG1-232 GEN
Solar/Wind Harmer
14.176
965041AG1-368 GEN
Solar/Wind Harmer
10.32
965051AG1-369 GEN
Solar/Wind Harmer
4.349
270071AF1-092 GEN
Solar/Wind Harmer
12.942
24729505KEY G4
Adder
4.903
970781AG2-491 GEN
Solar/Wind Harmer
5.665
274724RIVER EC ;11
Adder
9.996
274802UNIV PARK;5U
Adder
3.231
274826FISK ;BP
Adder
6.057
247604X1-042
Adder
0.23
274800UNIV PARK;3U
Adder
3.22
972038AH1-567 GEN2
Adder
0.202
274772LINCOLN ;3U
Adder
3.422
276772AC2-154 GEN
Solar/Wind Harmer
1.538
276806AD2-047 C O1
Solar/Wind Harmer
5.9
970941AG2-585 GEN
Solar/Wind Harmer
6.893
972228AH1-698 GEN2
Adder
2.035
276897AD1-100 C
Solar/Wind Harmer
15.84
939351AE1-166 GEN
Solar/Wind Harmer
3.237
274676JOLIET 29;8U
Adder
16.141
276893AG1-478 C
Solar/Wind Harmer
0.228
970707AG2-453 GEN
Solar/Wind Harmer
15.256
274730ELWOOD EC;6P
Adder
8.953
274734ELWOOD EC;8P
Adder
8.953
274736ELWOOD EC;9P
Adder
8.953
274729ELWOOD EC;1P
Adder
8.952
970243AG2-164 GEN
Solar/Wind Harmer
13.964
970519AG2-331 GEN
Solar/Wind Harmer
9.382
970699AG2-449 GEN
Solar/Wind Harmer
6.206
958821AF2-173 GEN
Solar/Wind Harmer
7.576
270004AE1-209 GEN
Solar/Wind Harmer
2.957
274682WAUKEGAN ;7U
Adder
9.561
972236AH1-702 GEN2
Adder
1.131
274760LEE CO EC;1U
Adder
4.74
274767LEE CO EC;8U
Adder
4.685
270485AE1-090_GEN
Solar/Wind Helper
0.31
942871AE2-306 GEN
Solar/Wind Helper
0.417
270541AE2-072 C
Solar/Wind Helper
1.028
943121AE2-341 GEN
Solar/Wind Harmer
0.827
943591AF1-030 GEN
Solar/Wind Harmer
0.552
270024AE2-089 GEN
Solar/Wind Harmer
3.42
958711AF2-162 GEN
Solar/Wind Harmer
0.701
965101AG1-375 GEN
Solar/Wind Harmer
6.724
945581AF1-223 GEN
Solar/Wind Harmer
2.871
971771AH1-392 GEN
Solar/Wind Harmer
5.677
971347AH1-153 GEN
Solar/Wind Harmer
9.093
971769AH1-391 GEN
Solar/Wind Harmer
6.044
944161AF1-084 GEN
Solar/Wind Harmer
1.326
960681AF2-359 GEN
Solar/Wind Harmer
2.23
270536AF1-215 GEN2
Solar/Wind Harmer
2.65
958391AF2-133 GEN
Solar/Wind Harmer
5.26
965461AG1-414 GEN
Solar/Wind Harmer
1.287
970289AG2-191 GEN
Solar/Wind Harmer
1.078
24690905MDL-1G C
Solar/Wind Harmer
4.549
270180AB1-006 GEN1
Solar/Wind Harmer
4.075
946581AF1-322 GEN
Solar/Wind Harmer
5.797
24691005MDL-2G C
Solar/Wind Harmer
2.096
24697605MDL-3G C
Solar/Wind Harmer
2.089
24697905MDL-4G C
Solar/Wind Harmer
1.301
270181AB1-006 GEN2
Solar/Wind Harmer
0.405
274814UNIV PK N;0U
Adder
2.833
274807UNIV PK N;3U
Adder
2.827
274805UNIV PK N;1U
Adder
2.815
274811UNIV PK N;7U
Adder
2.809
270594AE1-207 GEN
Solar/Wind Harmer
8.184
972037AH1-567 GEN1
Adder
0.101
274827FISK ;RP
Adder
4.292
274775LINCOLN ;6U
Adder
3.422
274776LINCOLN ;7U
Adder
3.422
274777LINCOLN ;8U
Adder
3.422
960591AF2-350 GEN
Solar/Wind Harmer
5.515
972227AH1-698 GEN1
Adder
1.433
24386205FR-12G C
Solar/Wind Harmer
2.351
24386405FR-21G C
Solar/Wind Harmer
2.359
24386605FR-22G C
Solar/Wind Harmer
2.359
24387005FR-3G C
Solar/Wind Harmer
2.17
274687WILL CNTY;4U
Adder
15.283
274687WILL CNTY;4U
Adder
15.283
274675JOLIET 29;7U
Adder
16.739
274675JOLIET 29;7U
Adder
16.141
274728ELWOOD EC;5P
Adder
8.953
274731ELWOOD EC;2P
Adder
8.952
274733ELWOOD EC;3P
Adder
8.952
274735ELWOOD EC;4P
Adder
8.952
970833AG2-524 GEN
Solar/Wind Harmer
4.728
970833AG2-524 GEN
Solar/Wind Harmer
2.199
970115AG2-085 GEN
Solar/Wind Harmer
2.152
274746AC1-111 G10
Adder
3.002
274744AC1-111 GEN8
Adder
3.002
274823ROCKFORD ;21
Adder
10.079
957201AF2-014 GEN
Solar/Wind Helper
8.848
270317AD1-130_GEN
Solar/Wind Helper
3.949
966831AG1-554 GEN
Solar/Wind Helper
0.871
270499AE1-146 GEN
Solar/Wind Helper
1.994
270284AF1-227 GEN1
Solar/Wind Helper
1.579
270286AF1-227 GEN2
Solar/Wind Helper
0.579
270287AF1-227 GEN3
Solar/Wind Helper
0.579
945641AF1-229 GEN
Solar/Wind Helper
0.93
270231U2-072_GEN5
Solar/Wind Helper
0.82
253378AE2-206_GEN
Solar/Wind Helper
0.673
276820AF1-078_GEN
Solar/Wind Helper
0.314
24791305MDL-5G
Solar/Wind Harmer
1.366
274723RIVER EC ;12
Adder
10.121
274812UNIV PK N;8U
Adder
2.809
276164X3-005 C
Solar/Wind Harmer
0.393
270032AE2-172
Solar/Wind Harmer
2.59
274801UNIV PARK;4U
Adder
3.22
972207SS24-0001
Solar/Wind Harmer
12.167
274773LINCOLN ;4U
Adder
3.422
274774LINCOLN ;5U
Adder
3.422
276776AD2-060 GEN
Solar/Wind Harmer
0.233
24385905FR-11G C
Solar/Wind Harmer
4.56
24387305FR-4G C
Solar/Wind Harmer
2.788
941551AE2-152 GEN
Solar/Wind Harmer
2.475
274676JOLIET 29;8U
Adder
16.739
274732ELWOOD EC;7P
Adder
8.953
274674JOLIET 9 ;6U
Adder
8.385
970333AG2-219 GEN
Solar/Wind Harmer
17.067
274871GR RIDGE ;2U
Solar/Wind Harmer
4.162
270005AE1-210 C O1
Solar/Wind Harmer
2.957
965031AG1-367 GEN
Solar/Wind Harmer
5.411
274745AC1-111 GEN9
Adder
3.002
274682WAUKEGAN ;7U
Adder
9.561
274828WAUKEGAN ;BP
Adder
5.87
274822ROCKFORD ;11
Adder
10.153
972235AH1-702 GEN1
Adder
1.301
274761LEE CO EC;2U
Adder
4.74
274766LEE CO EC;7U
Adder
4.685
970091AG2-072 GEN
Adder
38.031
246936BC-WTG1
Solar/Wind Helper
11.192
270462AD2-086
Solar/Wind Helper
3.566
270223U2-072_GEN1
Solar/Wind Helper
0.82
270578AF1-285 GEN2
Solar/Wind Helper
0.555
270391AF1-285 GEN3
Solar/Wind Helper
0.555
247522W1-056 GEN
Solar/Wind Helper
1.172
960841AF2-375 GEN
Solar/Wind Helper
1.199
944201AF1-088_MTX
Adder
52.894
957141AF2-008_MTX
Adder
9.455
990497J1323
External Queue
1.3854676485061646
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.148
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.322
MECLTFEXP_MEC->PJM
CLTF
7.361
SIGELTFEXP_SIGE->PJM
CLTF
0.152
LAGNLTFEXP_LAGN->PJM
CLTF
4.337
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.169
TVALTFEXP_TVA->PJM
CLTF
1.701
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.068
NYPJM->LTFIMP_NY
CLTF
0.945
LGEELTFEXP_LGEE->PJM
CLTF
1.101
WECLTFEXP_WEC->PJM
CLTF
1.969
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.075
AG2-052LTFEXP_AG2-052->PJM
LTF
0.13
AH1-155LTFEXP_AH1-155->PJM
LTF
0.196

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P7-1_#11067___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11067___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.58 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1953.56
MW Contribution:29.71
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.177
960861AF2-377 GEN
50/50
3.548
965421AG1-410 GEN
Solar/Wind Harmer
113.126
965011AG1-365 GEN
Solar/Wind Harmer
18.176
247521TR3_G114
Solar/Wind Harmer
5.127
270246TR4_N_V150
Solar/Wind Harmer
1.297
24695305TIMB G C
Solar/Wind Harmer
8.397
270063AE2-323 C
Solar/Wind Harmer
1.87
944231AF1-091 GEN
Solar/Wind Harmer
2.978
965651AG1-433 GEN
Solar/Wind Harmer
3.776
24639705ELKHART HY
Adder
0.103
958861AF2-177 GEN
Solar/Wind Harmer
7.322
945371AF1-202 GEN
Solar/Wind Harmer
4.392
945111AF1-176 GEN
Solar/Wind Harmer
10.738
270505AE1-170 C O1
Solar/Wind Harmer
8.657
270449AD2-020 GEN
Solar/Wind Harmer
1.588
943021AE2-325 GEN
Solar/Wind Harmer
2.064
270005AE1-210 C O1
Solar/Wind Harmer
2.924
965031AG1-367 GEN
Solar/Wind Harmer
5.351
970291AG2-192 GEN
Solar/Wind Harmer
0.687
270032AE2-172
Solar/Wind Harmer
2.44
970825AG2-519 GEN
Solar/Wind Harmer
1.235
970373AG2-245 GEN
Solar/Wind Harmer
10.893
270055AF2-134 C O1
Solar/Wind Harmer
1.55
274751CRETE EC ;1U
Adder
2.501
274754CRETE EC ;4U
Adder
2.501
274723RIVER EC ;12
Adder
9.109
958381AF2-132 GEN
Solar/Wind Harmer
4.589
964861AG1-349 GEN
Solar/Wind Harmer
3.971
971917AH1-482 GEN
Solar/Wind Harmer
4.583
274812UNIV PK N;8U
Adder
2.524
276164X3-005 C
Solar/Wind Harmer
0.353
276903AD2-071 C
Solar/Wind Harmer
5.014
940581AE2-045 GEN
Solar/Wind Harmer
5.075
971605AH1-302 GEN
Solar/Wind Harmer
4.34
274801UNIV PARK;4U
Adder
2.887
276776AD2-060 GEN
Solar/Wind Harmer
0.209
24727205RPMNG3
50/50
3.161
971599AH1-298 GEN
50/50
7.975
965041AG1-368 GEN
Solar/Wind Harmer
15.259
965051AG1-369 GEN
Solar/Wind Harmer
7.613
963791AG1-232 GEN
Solar/Wind Harmer
15.554
270071AF1-092 GEN
Solar/Wind Harmer
12.783
270024AE2-089 GEN
Solar/Wind Harmer
3.593
24729505KEY G4
Adder
4.902
958711AF2-162 GEN
Solar/Wind Harmer
0.699
965101AG1-375 GEN
Solar/Wind Harmer
6.699
970615AG2-402 GEN
50/50
4.227
970611AG2-400 GEN
Solar/Wind Harmer
18.176
942221AE2-234 GEN
Solar/Wind Harmer
0.601
247620Y3-023
Adder
0.327
944541AF1-119 GEN
Solar/Wind Harmer
2.894
960971AF2-388 GEN
Solar/Wind Harmer
7.553
270216AD2-079_GEN
Solar/Wind Harmer
0.384
270599AE1-208 GEN
Solar/Wind Harmer
4.946
270031AE2-169
Solar/Wind Harmer
4.946
960981AF2-389 GEN
Solar/Wind Harmer
0.885
957891AF2-083 GEN
Solar/Wind Harmer
1.971
961051AF2-396 GEN
Solar/Wind Harmer
9.202
961051AF2-396 GEN
Solar/Wind Harmer
4.28
270526AF1-158 GEN
Solar/Wind Harmer
2.539
24441505OLIV SLR
Solar/Wind Harmer
0.074
965681AG1-436 GEN
Solar/Wind Harmer
6.673
965791AG1-447 GEN
Solar/Wind Harmer
3.414
960441AF2-335 GEN
Solar/Wind Harmer
5.291
270201AC2-176 GEN
Solar/Wind Harmer
2.717
964611AG1-324 GEN
Solar/Wind Harmer
0.62
964611AG1-324 GEN
Solar/Wind Harmer
0.275
247621Y3-024
Adder
0.127
970825AG2-519 GEN
Solar/Wind Harmer
5.534
274808UNIV PK N;4U
Adder
2.513
274803UNIV PARK;6U
Adder
2.898
274888KELLY CRK;1U
Solar/Wind Harmer
2.917
274887GEN-1.85
Solar/Wind Harmer
2.634
276843GEN-1.7
Solar/Wind Harmer
0.283
958011AF2-095 GEN
Solar/Wind Harmer
7.115
274770LINCOLN ;1U
Adder
3.062
274771LINCOLN ;2U
Adder
3.062
945421AF1-207 GEN
Solar/Wind Harmer
6.878
957841AF2-078 GEN
Solar/Wind Harmer
2.96
972259AH1-714 GEN
Adder
9.328
970321AG2-212 GEN
Solar/Wind Harmer
8.719
274674JOLIET 9 ;6U
Adder
7.503
274847GR RIDGE ;BU
Solar/Wind Harmer
2.446
958481AF2-142 GEN
Solar/Wind Harmer
7.191
274861TOP CROP ;1U
Solar/Wind Harmer
2.904
274862TOP CROP ;2U
Solar/Wind Harmer
2.425
274696ROCKY RD ;4P
Adder
5.417
274695ROCKY RD ;2P
Adder
5.292
274693ROCKY RD ;1P
Adder
5.24
274697ROCKY RD ;3P
Adder
1.438
274683WAUKEGAN ;8U
Adder
10.008
274683WAUKEGAN ;8U
Adder
8.437
274764LEE CO EC;5U
Adder
4.235
274765LEE CO EC;6U
Adder
4.235
274762LEE CO EC;3U
Adder
4.225
274763LEE CO EC;4U
Adder
4.185
972267AH1-718 GEN
Adder
1.873
246938BC-WTG3
Solar/Wind Helper
11.408
246937BC-WTG2
Solar/Wind Helper
11.215
270224U2-072_GEN2
Solar/Wind Helper
0.863
270227U2-072_GEN3
Solar/Wind Helper
0.863
270228U2-072_GEN4
Solar/Wind Helper
0.863
270231U2-072_GEN5
Solar/Wind Helper
0.863
270007AE1-245 C
Solar/Wind Helper
1.926
942801AE2-298 GEN
Solar/Wind Helper
0.419
253378AE2-206_GEN
Solar/Wind Helper
0.755
276820AF1-078_GEN
Solar/Wind Helper
0.353
965431AG1-411 GEN
50/50
43.847
24727105RPMNG2
50/50
3.188
970583AG2-370 GEN
50/50
3.549
960851AF2-376 GEN
50/50
3.548
959331AF2-224 GEN
Solar/Wind Harmer
18.176
965021AG1-366 GEN
Solar/Wind Harmer
4.227
270191TR4_S_V150
Solar/Wind Harmer
4.574
270247TR4_N_V136
Solar/Wind Harmer
1.297
970031AG2-029 GEN
Solar/Wind Harmer
29.711
270043AE2-236 GEN
Solar/Wind Harmer
5.133
944531AF1-118 GEN
Solar/Wind Harmer
27.261
971617AH1-308 GEN
Solar/Wind Harmer
4.45
247643Z2-116 C
Solar/Wind Harmer
0.044
945111AF1-176 GEN
Solar/Wind Harmer
3.403
24642205MAYFLWER
Adder
0.364
970349AG2-230 GEN
Solar/Wind Harmer
8.302
958821AF2-173 GEN
Solar/Wind Harmer
7.491
270004AE1-209 GEN
Solar/Wind Harmer
2.924
247642Z2-115 C
Solar/Wind Harmer
0.034
962031AG1-047 GEN
Solar/Wind Harmer
1.598
957741AF2-068 GEN
Solar/Wind Harmer
7.929
970289AG2-191 GEN
Solar/Wind Harmer
0.405
970291AG2-192 GEN
Solar/Wind Harmer
0.368
24441205WTRV SLR C
Solar/Wind Harmer
0.071
946031AF1-268 GEN
Solar/Wind Harmer
4.287
270535AF1-215 GEN1
Solar/Wind Harmer
2.326
972231SS25-0005
Solar/Wind Harmer
4.857
972181SS23-001
Solar/Wind Harmer
3.035
274752CRETE EC ;2U
Adder
2.501
274753CRETE EC ;3U
Adder
2.501
274724RIVER EC ;11
Adder
8.995
964401AG1-302 GEN
Solar/Wind Harmer
4.589
247604X1-042
Adder
0.21
959141AF2-205 GEN
Solar/Wind Harmer
3.026
274802UNIV PARK;5U
Adder
2.898
274826FISK ;BP
Adder
5.433
274800UNIV PARK;3U
Adder
2.887
972038AH1-567 GEN2
Adder
0.181
276772AC2-154 GEN
Solar/Wind Harmer
1.378
276806AD2-047 C O1
Solar/Wind Harmer
5.286
970941AG2-585 GEN
Solar/Wind Harmer
6.176
274772LINCOLN ;3U
Adder
3.062
972228AH1-698 GEN2
Adder
1.822
274676JOLIET 29;8U
Adder
14.451
970513AG2-328 GEN
Solar/Wind Harmer
8.719
970517AG2-330 GEN
Solar/Wind Harmer
7.908
276897AD1-100 C
Solar/Wind Harmer
14.152
939351AE1-166 GEN
Solar/Wind Harmer
2.892
276893AG1-478 C
Solar/Wind Harmer
0.204
970707AG2-453 GEN
Solar/Wind Harmer
13.644
274729ELWOOD EC;1P
Adder
8.009
274730ELWOOD EC;6P
Adder
8.009
274734ELWOOD EC;8P
Adder
8.009
274736ELWOOD EC;9P
Adder
8.009
24755605MDL-5G
Solar/Wind Harmer
1.16
970781AG2-491 GEN
Solar/Wind Harmer
4.809
943121AE2-341 GEN
Solar/Wind Harmer
7.196
943591AF1-030 GEN
Solar/Wind Harmer
4.798
276694AA1-018 GEN2
Solar/Wind Harmer
3.025
274682WAUKEGAN ;7U
Adder
8.546
972236AH1-702 GEN2
Adder
1.009
274760LEE CO EC;1U
Adder
4.225
274767LEE CO EC;8U
Adder
4.175
270485AE1-090_GEN
Solar/Wind Helper
0.327
942871AE2-306 GEN
Solar/Wind Helper
0.439
270541AE2-072 C
Solar/Wind Helper
1.255
972207SS24-0001
Solar/Wind Harmer
10.888
274773LINCOLN ;4U
Adder
3.062
274774LINCOLN ;5U
Adder
3.062
274676JOLIET 29;8U
Adder
14.986
970245AG2-165 GEN
Solar/Wind Harmer
8.719
941551AE2-152 GEN
Solar/Wind Harmer
2.212
274674JOLIET 9 ;6U
Adder
7.503
274732ELWOOD EC;7P
Adder
8.009
274871GR RIDGE ;2U
Solar/Wind Harmer
3.718
24791305MDL-5G
Solar/Wind Harmer
1.16
274745AC1-111 GEN9
Adder
2.683
276691AA1-018 GEN1
Solar/Wind Harmer
0.223
274682WAUKEGAN ;7U
Adder
8.546
274828WAUKEGAN ;BP
Adder
5.246
274822ROCKFORD ;11
Adder
9.059
972235AH1-702 GEN1
Adder
1.161
274761LEE CO EC;2U
Adder
4.225
274766LEE CO EC;7U
Adder
4.175
246936BC-WTG1
Solar/Wind Helper
11.215
270462AD2-086
Solar/Wind Helper
3.753
270223U2-072_GEN1
Solar/Wind Helper
0.863
270578AF1-285 GEN2
Solar/Wind Helper
0.585
270391AF1-285 GEN3
Solar/Wind Helper
0.585
247522W1-056 GEN
Solar/Wind Helper
1.341
960841AF2-375 GEN
Solar/Wind Helper
1.344
241840AF1-064_GEN
Solar/Wind Helper
0.498
247536S-71 GEN
Solar/Wind Harmer
0.056
945581AF1-223 GEN
Solar/Wind Harmer
2.855
971771AH1-392 GEN
Solar/Wind Harmer
5.26
944161AF1-084 GEN
Solar/Wind Harmer
1.227
971347AH1-153 GEN
Solar/Wind Harmer
8.302
971769AH1-391 GEN
Solar/Wind Harmer
5.526
960681AF2-359 GEN
Solar/Wind Harmer
2.017
970115AG2-085 GEN
Solar/Wind Harmer
2.116
961761AG1-017 GEN
Solar/Wind Harmer
0.226
965461AG1-414 GEN
Solar/Wind Harmer
1.197
970289AG2-191 GEN
Solar/Wind Harmer
1.003
270594AE1-207 GEN
Solar/Wind Harmer
7.712
270536AF1-215 GEN2
Solar/Wind Harmer
2.326
274814UNIV PK N;0U
Adder
2.546
274807UNIV PK N;3U
Adder
2.541
274805UNIV PK N;1U
Adder
2.53
274811UNIV PK N;7U
Adder
2.524
958391AF2-133 GEN
Solar/Wind Harmer
4.561
972037AH1-567 GEN1
Adder
0.091
274827FISK ;RP
Adder
3.85
960591AF2-350 GEN
Solar/Wind Harmer
4.941
274775LINCOLN ;6U
Adder
3.062
274776LINCOLN ;7U
Adder
3.062
274777LINCOLN ;8U
Adder
3.062
24725505WLD G2 C
Solar/Wind Harmer
1.96
24699105WLD G1 C
Solar/Wind Harmer
1.937
972227AH1-698 GEN1
Adder
1.283
274687WILL CNTY;4U
Adder
13.687
274687WILL CNTY;4U
Adder
13.687
274675JOLIET 29;7U
Adder
14.986
274675JOLIET 29;7U
Adder
14.451
274731ELWOOD EC;2P
Adder
8.009
274733ELWOOD EC;3P
Adder
8.009
274735ELWOOD EC;4P
Adder
8.009
274728ELWOOD EC;5P
Adder
8.009
970833AG2-524 GEN
Solar/Wind Harmer
4.225
970833AG2-524 GEN
Solar/Wind Harmer
1.965
24690905MDL-1G C
Solar/Wind Harmer
3.861
270180AB1-006 GEN1
Solar/Wind Harmer
3.459
946581AF1-322 GEN
Solar/Wind Harmer
4.921
24691005MDL-2G C
Solar/Wind Harmer
1.779
24697605MDL-3G C
Solar/Wind Harmer
1.773
24697905MDL-4G C
Solar/Wind Harmer
1.104
270181AB1-006 GEN2
Solar/Wind Harmer
0.344
274746AC1-111 G10
Adder
2.683
274744AC1-111 GEN8
Adder
2.683
274823ROCKFORD ;21
Adder
8.993
957201AF2-014 GEN
Solar/Wind Helper
8.866
270317AD1-130_GEN
Solar/Wind Helper
4.157
966831AG1-554 GEN
Solar/Wind Helper
0.987
270499AE1-146 GEN
Solar/Wind Helper
2.247
247607V1-011 GEN
Solar/Wind Helper
1.284
270284AF1-227 GEN1
Solar/Wind Helper
1.663
270286AF1-227 GEN2
Solar/Wind Helper
0.61
270287AF1-227 GEN3
Solar/Wind Helper
0.61
945641AF1-229 GEN
Solar/Wind Helper
1.005
990497J1323
External Queue
1.4821711778640747
990792J1392
External Queue
5.098668575286865
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.195
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.309
MECLTFEXP_MEC->PJM
CLTF
6.539
SIGELTFEXP_SIGE->PJM
CLTF
0.138
LAGNLTFEXP_LAGN->PJM
CLTF
4.06
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.825
TVALTFEXP_TVA->PJM
CLTF
1.657
CPLELTFEXP_CPLE->PJM
CLTF
0.003
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.046
NYPJM->LTFIMP_NY
CLTF
0.85
LGEELTFEXP_LGEE->PJM
CLTF
1.227
WECLTFEXP_WEC->PJM
CLTF
1.758
AG2-052LTFEXP_AG2-052->PJM
LTF
0.116
AH1-155LTFEXP_AH1-155->PJM
LTF
0.174

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P7-1_#11068___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11068___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.67 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1936.6
MW Contribution:29.46
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
43.671
24727105RPMNG2
50/50
3.172
970583AG2-370 GEN
50/50
3.094
960851AF2-376 GEN
50/50
2.788
959331AF2-224 GEN
Solar/Wind Harmer
17.974
965021AG1-366 GEN
Solar/Wind Harmer
4.18
270191TR4_S_V150
Solar/Wind Harmer
4.439
270247TR4_N_V136
Solar/Wind Harmer
1.259
958091AF2-103 GEN
Solar/Wind Harmer
0.162
970031AG2-029 GEN
Solar/Wind Harmer
29.463
270043AE2-236 GEN
Solar/Wind Harmer
5.095
944531AF1-118 GEN
Solar/Wind Harmer
27.043
971617AH1-308 GEN
Solar/Wind Harmer
4.441
270258AD1-119 GEN
Solar/Wind Harmer
1.801
247643Z2-116 C
Solar/Wind Harmer
0.044
945111AF1-176 GEN
Solar/Wind Harmer
3.378
24642205MAYFLWER
Adder
0.362
270044AE2-322 C
Solar/Wind Harmer
0.731
24727205RPMNG3
50/50
3.146
971599AH1-298 GEN
50/50
7.901
965051AG1-369 GEN
Solar/Wind Harmer
7.389
965041AG1-368 GEN
Solar/Wind Harmer
13.306
963791AG1-232 GEN
Solar/Wind Harmer
15.24
247607V1-011 GEN
Solar/Wind Harmer
3.978
270071AF1-092 GEN
Solar/Wind Harmer
12.666
270024AE2-089 GEN
Solar/Wind Harmer
3.585
24729505KEY G4
Adder
4.864
958711AF2-162 GEN
Solar/Wind Harmer
0.694
965101AG1-375 GEN
Solar/Wind Harmer
6.653
945581AF1-223 GEN
Solar/Wind Harmer
2.837
971771AH1-392 GEN
Solar/Wind Harmer
5.22
944161AF1-084 GEN
Solar/Wind Harmer
1.217
971347AH1-153 GEN
Solar/Wind Harmer
8.232
971769AH1-391 GEN
Solar/Wind Harmer
5.482
961761AG1-017 GEN
Solar/Wind Harmer
0.231
960681AF2-359 GEN
Solar/Wind Harmer
2
970115AG2-085 GEN
Solar/Wind Harmer
2.112
965461AG1-414 GEN
Solar/Wind Harmer
1.192
970289AG2-191 GEN
Solar/Wind Harmer
0.999
270594AE1-207 GEN
Solar/Wind Harmer
7.685
270536AF1-215 GEN2
Solar/Wind Harmer
2.307
274814UNIV PK N;0U
Adder
2.525
274807UNIV PK N;3U
Adder
2.52
274805UNIV PK N;1U
Adder
2.509
274811UNIV PK N;7U
Adder
2.504
958391AF2-133 GEN
Solar/Wind Harmer
4.525
972037AH1-567 GEN1
Adder
0.09
274827FISK ;RP
Adder
3.819
24725505WLD G2 C
Solar/Wind Harmer
1.952
24699105WLD G1 C
Solar/Wind Harmer
1.929
960591AF2-350 GEN
Solar/Wind Harmer
4.9
274775LINCOLN ;6U
Adder
3.037
274776LINCOLN ;7U
Adder
3.037
274777LINCOLN ;8U
Adder
3.037
972227AH1-698 GEN1
Adder
1.272
274687WILL CNTY;4U
Adder
13.575
274687WILL CNTY;4U
Adder
13.575
274675JOLIET 29;7U
Adder
14.863
274675JOLIET 29;7U
Adder
14.332
274731ELWOOD EC;2P
Adder
7.943
274733ELWOOD EC;3P
Adder
7.943
274735ELWOOD EC;4P
Adder
7.943
274728ELWOOD EC;5P
Adder
7.943
970833AG2-524 GEN
Solar/Wind Harmer
4.19
970833AG2-524 GEN
Solar/Wind Harmer
1.949
24690905MDL-1G C
Solar/Wind Harmer
3.831
270180AB1-006 GEN1
Solar/Wind Harmer
3.432
946581AF1-322 GEN
Solar/Wind Harmer
4.882
24691005MDL-2G C
Solar/Wind Harmer
1.765
24697605MDL-3G C
Solar/Wind Harmer
1.759
24697905MDL-4G C
Solar/Wind Harmer
1.095
270181AB1-006 GEN2
Solar/Wind Harmer
0.341
274746AC1-111 G10
Adder
2.661
274744AC1-111 GEN8
Adder
2.661
274823ROCKFORD ;21
Adder
8.92
957201AF2-014 GEN
Solar/Wind Helper
8.894
270317AD1-130_GEN
Solar/Wind Helper
4.173
966831AG1-554 GEN
Solar/Wind Helper
0.997
270499AE1-146 GEN
Solar/Wind Helper
2.247
270284AF1-227 GEN1
Solar/Wind Helper
1.668
270286AF1-227 GEN2
Solar/Wind Helper
0.612
270404AC1-167 GEN
Solar/Wind Harmer
0.608
970349AG2-230 GEN
Solar/Wind Harmer
8.232
962031AG1-047 GEN
Solar/Wind Harmer
1.633
957741AF2-068 GEN
Solar/Wind Harmer
8.103
958821AF2-173 GEN
Solar/Wind Harmer
7.457
270004AE1-209 GEN
Solar/Wind Harmer
2.911
247642Z2-115 C
Solar/Wind Harmer
0.034
970289AG2-191 GEN
Solar/Wind Harmer
0.404
970291AG2-192 GEN
Solar/Wind Harmer
0.367
24441205WTRV SLR C
Solar/Wind Harmer
0.07
946031AF1-268 GEN
Solar/Wind Harmer
4.304
270535AF1-215 GEN1
Solar/Wind Harmer
2.307
972231SS25-0005
Solar/Wind Harmer
4.817
972181SS23-001
Solar/Wind Harmer
3.011
274752CRETE EC ;2U
Adder
2.481
274753CRETE EC ;3U
Adder
2.481
274724RIVER EC ;11
Adder
8.922
964401AG1-302 GEN
Solar/Wind Harmer
4.552
247604X1-042
Adder
0.209
959141AF2-205 GEN
Solar/Wind Harmer
3.002
274802UNIV PARK;5U
Adder
2.875
274826FISK ;BP
Adder
5.388
274800UNIV PARK;3U
Adder
2.863
972038AH1-567 GEN2
Adder
0.179
276772AC2-154 GEN
Solar/Wind Harmer
1.367
276806AD2-047 C O1
Solar/Wind Harmer
5.242
970941AG2-585 GEN
Solar/Wind Harmer
6.125
274772LINCOLN ;3U
Adder
3.037
972228AH1-698 GEN2
Adder
1.807
274676JOLIET 29;8U
Adder
14.332
970513AG2-328 GEN
Solar/Wind Harmer
8.645
970517AG2-330 GEN
Solar/Wind Harmer
7.84
276897AD1-100 C
Solar/Wind Harmer
14.036
939351AE1-166 GEN
Solar/Wind Harmer
2.868
276893AG1-478 C
Solar/Wind Harmer
0.202
970707AG2-453 GEN
Solar/Wind Harmer
13.532
274729ELWOOD EC;1P
Adder
7.943
274730ELWOOD EC;6P
Adder
7.943
274734ELWOOD EC;8P
Adder
7.943
274736ELWOOD EC;9P
Adder
7.943
24755605MDL-5G
Solar/Wind Harmer
1.151
970781AG2-491 GEN
Solar/Wind Harmer
4.771
943121AE2-341 GEN
Solar/Wind Harmer
7.137
943591AF1-030 GEN
Solar/Wind Harmer
4.758
276694AA1-018 GEN2
Solar/Wind Harmer
3
274682WAUKEGAN ;7U
Adder
8.476
972236AH1-702 GEN2
Adder
1.001
274760LEE CO EC;1U
Adder
4.19
274767LEE CO EC;8U
Adder
4.141
270485AE1-090_GEN
Solar/Wind Helper
0.328
942871AE2-306 GEN
Solar/Wind Helper
0.44
270541AE2-072 C
Solar/Wind Helper
1.21
24727005RPMNG1
50/50
3.161
960861AF2-377 GEN
50/50
3.444
965421AG1-410 GEN
Solar/Wind Harmer
112.671
965011AG1-365 GEN
Solar/Wind Harmer
17.974
247521TR3_G114
Solar/Wind Harmer
4.976
270246TR4_N_V150
Solar/Wind Harmer
1.259
24695305TIMB G C
Solar/Wind Harmer
6.598
944231AF1-091 GEN
Solar/Wind Harmer
3.224
270063AE2-323 C
Solar/Wind Harmer
1.863
965651AG1-433 GEN
Solar/Wind Harmer
3.75
24639705ELKHART HY
Adder
0.103
958861AF2-177 GEN
Solar/Wind Harmer
7.272
945371AF1-202 GEN
Solar/Wind Harmer
4.365
945111AF1-176 GEN
Solar/Wind Harmer
10.659
270505AE1-170 C O1
Solar/Wind Harmer
8.591
270449AD2-020 GEN
Solar/Wind Harmer
1.576
943021AE2-325 GEN
Solar/Wind Harmer
2.048
270005AE1-210 C O1
Solar/Wind Harmer
2.911
965031AG1-367 GEN
Solar/Wind Harmer
5.326
970291AG2-192 GEN
Solar/Wind Harmer
0.684
970825AG2-519 GEN
Solar/Wind Harmer
1.233
270032AE2-172
Solar/Wind Harmer
2.432
970373AG2-245 GEN
Solar/Wind Harmer
10.805
270055AF2-134 C O1
Solar/Wind Harmer
1.538
274751CRETE EC ;1U
Adder
2.481
274754CRETE EC ;4U
Adder
2.481
274723RIVER EC ;12
Adder
9.034
958381AF2-132 GEN
Solar/Wind Harmer
4.552
964861AG1-349 GEN
Solar/Wind Harmer
3.94
971917AH1-482 GEN
Solar/Wind Harmer
4.546
274812UNIV PK N;8U
Adder
2.504
276903AD2-071 C
Solar/Wind Harmer
4.993
276164X3-005 C
Solar/Wind Harmer
0.35
940581AE2-045 GEN
Solar/Wind Harmer
5.035
971605AH1-302 GEN
Solar/Wind Harmer
4.305
274801UNIV PARK;4U
Adder
2.863
276776AD2-060 GEN
Solar/Wind Harmer
0.207
972207SS24-0001
Solar/Wind Harmer
10.798
274773LINCOLN ;4U
Adder
3.037
274774LINCOLN ;5U
Adder
3.037
247536S-71 GEN
Solar/Wind Harmer
1.975
274676JOLIET 29;8U
Adder
14.863
970245AG2-165 GEN
Solar/Wind Harmer
8.645
941551AE2-152 GEN
Solar/Wind Harmer
2.194
274732ELWOOD EC;7P
Adder
7.943
274674JOLIET 9 ;6U
Adder
7.441
274871GR RIDGE ;2U
Solar/Wind Harmer
3.688
24791305MDL-5G
Solar/Wind Harmer
1.151
274745AC1-111 GEN9
Adder
2.661
276691AA1-018 GEN1
Solar/Wind Harmer
0.221
274682WAUKEGAN ;7U
Adder
8.476
274828WAUKEGAN ;BP
Adder
5.203
274822ROCKFORD ;11
Adder
8.985
972235AH1-702 GEN1
Adder
1.151
274761LEE CO EC;2U
Adder
4.19
274766LEE CO EC;7U
Adder
4.141
246936BC-WTG1
Solar/Wind Helper
11.251
270462AD2-086
Solar/Wind Helper
3.768
270223U2-072_GEN1
Solar/Wind Helper
0.866
270578AF1-285 GEN2
Solar/Wind Helper
0.587
270391AF1-285 GEN3
Solar/Wind Helper
0.587
247522W1-056 GEN
Solar/Wind Helper
1.341
960841AF2-375 GEN
Solar/Wind Helper
1.344
241840AF1-064_GEN
Solar/Wind Helper
0.475
270287AF1-227 GEN3
Solar/Wind Helper
0.612
945641AF1-229 GEN
Solar/Wind Helper
1.006
970615AG2-402 GEN
50/50
4.18
970611AG2-400 GEN
Solar/Wind Harmer
17.974
270007AE1-245 C
Solar/Wind Harmer
5.966
942221AE2-234 GEN
Solar/Wind Harmer
0.595
247620Y3-023
Adder
0.326
944541AF1-119 GEN
Solar/Wind Harmer
2.874
960971AF2-388 GEN
Solar/Wind Harmer
7.5
942801AE2-298 GEN
Solar/Wind Harmer
1.003
270216AD2-079_GEN
Solar/Wind Harmer
0.382
270599AE1-208 GEN
Solar/Wind Harmer
4.924
270031AE2-169
Solar/Wind Harmer
4.924
960981AF2-389 GEN
Solar/Wind Harmer
0.878
957891AF2-083 GEN
Solar/Wind Harmer
1.956
961051AF2-396 GEN
Solar/Wind Harmer
9.132
961051AF2-396 GEN
Solar/Wind Harmer
4.248
270526AF1-158 GEN
Solar/Wind Harmer
2.519
24441505OLIV SLR
Solar/Wind Harmer
0.073
270201AC2-176 GEN
Solar/Wind Harmer
2.777
964611AG1-324 GEN
Solar/Wind Harmer
0.632
964611AG1-324 GEN
Solar/Wind Harmer
0.28
247621Y3-024
Adder
0.128
965681AG1-436 GEN
Solar/Wind Harmer
6.619
965791AG1-447 GEN
Solar/Wind Harmer
3.386
960441AF2-335 GEN
Solar/Wind Harmer
5.281
970825AG2-519 GEN
Solar/Wind Harmer
5.526
274808UNIV PK N;4U
Adder
2.493
274803UNIV PARK;6U
Adder
2.875
274888KELLY CRK;1U
Solar/Wind Harmer
2.893
274887GEN-1.85
Solar/Wind Harmer
2.612
276843GEN-1.7
Solar/Wind Harmer
0.281
958011AF2-095 GEN
Solar/Wind Harmer
7.056
274770LINCOLN ;1U
Adder
3.037
274771LINCOLN ;2U
Adder
3.037
945421AF1-207 GEN
Solar/Wind Harmer
6.824
957841AF2-078 GEN
Solar/Wind Harmer
2.937
972259AH1-714 GEN
Adder
9.252
970321AG2-212 GEN
Solar/Wind Harmer
8.645
274674JOLIET 9 ;6U
Adder
7.441
274847GR RIDGE ;BU
Solar/Wind Harmer
2.426
274695ROCKY RD ;2P
Adder
5.249
274693ROCKY RD ;1P
Adder
5.197
274697ROCKY RD ;3P
Adder
1.426
274696ROCKY RD ;4P
Adder
5.373
274683WAUKEGAN ;8U
Adder
9.926
274683WAUKEGAN ;8U
Adder
8.367
274764LEE CO EC;5U
Adder
4.2
274765LEE CO EC;6U
Adder
4.2
274762LEE CO EC;3U
Adder
4.19
274763LEE CO EC;4U
Adder
4.151
972267AH1-718 GEN
Adder
1.858
246938BC-WTG3
Solar/Wind Helper
11.444
246937BC-WTG2
Solar/Wind Helper
11.251
270224U2-072_GEN2
Solar/Wind Helper
0.866
270227U2-072_GEN3
Solar/Wind Helper
0.866
270228U2-072_GEN4
Solar/Wind Helper
0.866
270231U2-072_GEN5
Solar/Wind Helper
0.866
253378AE2-206_GEN
Solar/Wind Helper
0.736
276820AF1-078_GEN
Solar/Wind Helper
0.344
958481AF2-142 GEN
Solar/Wind Harmer
2.583
990497J1323
External Queue
1.486285924911499
990792J1392
External Queue
5.112823486328125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.833
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.255
MECLTFEXP_MEC->PJM
CLTF
6.486
SIGELTFEXP_SIGE->PJM
CLTF
0.137
LAGNLTFEXP_LAGN->PJM
CLTF
4.023
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.793
TVALTFEXP_TVA->PJM
CLTF
1.641
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.767
NYPJM->LTFIMP_NY
CLTF
0.854
LGEELTFEXP_LGEE->PJM
CLTF
1.221
WECLTFEXP_WEC->PJM
CLTF
1.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.115
AH1-155LTFEXP_AH1-155->PJM
LTF
0.173

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.68 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1899.39
MW Contribution:28.45
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
43.64
24727105RPMNG2
50/50
3.157
970583AG2-370 GEN
50/50
2.333
959331AF2-224 GEN
Solar/Wind Harmer
17.341
965021AG1-366 GEN
Solar/Wind Harmer
4.033
970031AG2-029 GEN
Solar/Wind Harmer
28.445
270043AE2-236 GEN
Solar/Wind Harmer
4.864
270191TR4_S_V150
Solar/Wind Harmer
2.534
270247TR4_N_V136
Solar/Wind Harmer
0.719
944531AF1-118 GEN
Solar/Wind Harmer
26.231
971617AH1-308 GEN
Solar/Wind Harmer
4.088
247643Z2-116 C
Solar/Wind Harmer
0.042
945111AF1-176 GEN
Solar/Wind Harmer
3.303
24642205MAYFLWER
Adder
0.354
970349AG2-230 GEN
Solar/Wind Harmer
8.117
958821AF2-173 GEN
Solar/Wind Harmer
7.246
270004AE1-209 GEN
Solar/Wind Harmer
2.829
24441205WTRV SLR C
Solar/Wind Harmer
0.069
247642Z2-115 C
Solar/Wind Harmer
0.033
970289AG2-191 GEN
Solar/Wind Harmer
0.391
970291AG2-192 GEN
Solar/Wind Harmer
0.356
962031AG1-047 GEN
Solar/Wind Harmer
1.535
957741AF2-068 GEN
Solar/Wind Harmer
7.618
972231SS25-0005
Solar/Wind Harmer
4.749
972181SS23-001
Solar/Wind Harmer
2.968
274752CRETE EC ;2U
Adder
2.446
274753CRETE EC ;3U
Adder
2.446
270535AF1-215 GEN1
Solar/Wind Harmer
2.271
946031AF1-268 GEN
Solar/Wind Harmer
4.138
274724RIVER EC ;11
Adder
8.8
964401AG1-302 GEN
Solar/Wind Harmer
4.482
247604X1-042
Adder
0.206
959141AF2-205 GEN
Solar/Wind Harmer
2.955
274802UNIV PARK;5U
Adder
2.837
274826FISK ;BP
Adder
5.318
274800UNIV PARK;3U
Adder
2.826
972038AH1-567 GEN2
Adder
0.177
274772LINCOLN ;3U
Adder
3.002
276772AC2-154 GEN
Solar/Wind Harmer
1.349
276806AD2-047 C O1
Solar/Wind Harmer
5.175
970941AG2-585 GEN
Solar/Wind Harmer
6.047
972228AH1-698 GEN2
Adder
1.784
970513AG2-328 GEN
Solar/Wind Harmer
8.576
970517AG2-330 GEN
Solar/Wind Harmer
7.779
274676JOLIET 29;8U
Adder
14.153
276897AD1-100 C
Solar/Wind Harmer
13.864
939351AE1-166 GEN
Solar/Wind Harmer
2.833
970707AG2-453 GEN
Solar/Wind Harmer
13.372
276893AG1-478 C
Solar/Wind Harmer
0.199
274729ELWOOD EC;1P
Adder
7.844
274730ELWOOD EC;6P
Adder
7.844
274734ELWOOD EC;8P
Adder
7.844
274736ELWOOD EC;9P
Adder
7.844
943121AE2-341 GEN
Solar/Wind Harmer
7.053
943591AF1-030 GEN
Solar/Wind Harmer
4.702
24755605MDL-5G
Solar/Wind Harmer
1.133
970781AG2-491 GEN
Solar/Wind Harmer
4.697
276694AA1-018 GEN2
Solar/Wind Harmer
2.963
274682WAUKEGAN ;7U
Adder
8.374
972236AH1-702 GEN2
Adder
0.989
274760LEE CO EC;1U
Adder
4.142
274767LEE CO EC;8U
Adder
4.093
270485AE1-090_GEN
Solar/Wind Helper
0.309
942871AE2-306 GEN
Solar/Wind Helper
0.413
270541AE2-072 C
Solar/Wind Helper
1.056
24727005RPMNG1
50/50
3.146
965421AG1-410 GEN
Solar/Wind Harmer
112.59
965011AG1-365 GEN
Solar/Wind Harmer
17.341
247521TR3_G114
Solar/Wind Harmer
2.841
270246TR4_N_V150
Solar/Wind Harmer
0.719
270063AE2-323 C
Solar/Wind Harmer
1.77
944231AF1-091 GEN
Solar/Wind Harmer
2.955
24695305TIMB G C
Solar/Wind Harmer
3.982
965651AG1-433 GEN
Solar/Wind Harmer
3.639
24639705ELKHART HY
Adder
0.1
958861AF2-177 GEN
Solar/Wind Harmer
7.058
945371AF1-202 GEN
Solar/Wind Harmer
4.238
945111AF1-176 GEN
Solar/Wind Harmer
10.423
270505AE1-170 C O1
Solar/Wind Harmer
8.42
270449AD2-020 GEN
Solar/Wind Harmer
1.545
943021AE2-325 GEN
Solar/Wind Harmer
2.008
270005AE1-210 C O1
Solar/Wind Harmer
2.829
965031AG1-367 GEN
Solar/Wind Harmer
5.176
970291AG2-192 GEN
Solar/Wind Harmer
0.663
270032AE2-172
Solar/Wind Harmer
2.358
24727205RPMNG3
50/50
3.131
971599AH1-298 GEN
50/50
7.666
963791AG1-232 GEN
Solar/Wind Harmer
13.777
965041AG1-368 GEN
Solar/Wind Harmer
10.032
965051AG1-369 GEN
Solar/Wind Harmer
4.218
270071AF1-092 GEN
Solar/Wind Harmer
12.147
24729505KEY G4
Adder
4.718
270024AE2-089 GEN
Solar/Wind Harmer
3.3
958711AF2-162 GEN
Solar/Wind Harmer
0.674
965101AG1-375 GEN
Solar/Wind Harmer
6.458
945581AF1-223 GEN
Solar/Wind Harmer
2.755
971771AH1-392 GEN
Solar/Wind Harmer
5.113
971347AH1-153 GEN
Solar/Wind Harmer
8.117
944161AF1-084 GEN
Solar/Wind Harmer
1.194
971769AH1-391 GEN
Solar/Wind Harmer
5.387
960681AF2-359 GEN
Solar/Wind Harmer
1.97
965461AG1-414 GEN
Solar/Wind Harmer
1.157
970289AG2-191 GEN
Solar/Wind Harmer
0.969
970115AG2-085 GEN
Solar/Wind Harmer
2.04
961761AG1-017 GEN
Solar/Wind Harmer
0.217
270594AE1-207 GEN
Solar/Wind Harmer
7.45
270536AF1-215 GEN2
Solar/Wind Harmer
2.271
274814UNIV PK N;0U
Adder
2.491
274807UNIV PK N;3U
Adder
2.486
274805UNIV PK N;1U
Adder
2.475
274811UNIV PK N;7U
Adder
2.47
958391AF2-133 GEN
Solar/Wind Harmer
4.454
972037AH1-567 GEN1
Adder
0.089
274827FISK ;RP
Adder
3.769
274775LINCOLN ;6U
Adder
3.002
274776LINCOLN ;7U
Adder
3.002
274777LINCOLN ;8U
Adder
3.002
960591AF2-350 GEN
Solar/Wind Harmer
4.838
972227AH1-698 GEN1
Adder
1.256
274687WILL CNTY;4U
Adder
13.404
274687WILL CNTY;4U
Adder
13.404
274675JOLIET 29;7U
Adder
14.678
274675JOLIET 29;7U
Adder
14.153
274731ELWOOD EC;2P
Adder
7.844
274733ELWOOD EC;3P
Adder
7.844
274735ELWOOD EC;4P
Adder
7.844
274728ELWOOD EC;5P
Adder
7.844
24725505WLD G2 C
Solar/Wind Harmer
1.895
24699105WLD G1 C
Solar/Wind Harmer
1.873
970833AG2-524 GEN
Solar/Wind Harmer
4.139
970833AG2-524 GEN
Solar/Wind Harmer
1.925
274746AC1-111 G10
Adder
2.629
274744AC1-111 GEN8
Adder
2.629
24690905MDL-1G C
Solar/Wind Harmer
3.771
270180AB1-006 GEN1
Solar/Wind Harmer
3.379
946581AF1-322 GEN
Solar/Wind Harmer
4.806
24691005MDL-2G C
Solar/Wind Harmer
1.737
24697605MDL-3G C
Solar/Wind Harmer
1.732
24697905MDL-4G C
Solar/Wind Harmer
1.078
270181AB1-006 GEN2
Solar/Wind Harmer
0.336
274823ROCKFORD ;21
Adder
8.816
957201AF2-014 GEN
Solar/Wind Helper
8.887
270317AD1-130_GEN
Solar/Wind Helper
3.931
966831AG1-554 GEN
Solar/Wind Helper
0.877
270499AE1-146 GEN
Solar/Wind Helper
2.022
270284AF1-227 GEN1
Solar/Wind Helper
1.537
270286AF1-227 GEN2
Solar/Wind Helper
0.564
270287AF1-227 GEN3
Solar/Wind Helper
0.564
945641AF1-229 GEN
Solar/Wind Helper
0.946
970615AG2-402 GEN
50/50
4.033
970611AG2-400 GEN
Solar/Wind Harmer
17.341
942221AE2-234 GEN
Solar/Wind Harmer
0.557
247620Y3-023
Adder
0.315
944541AF1-119 GEN
Solar/Wind Harmer
2.789
960971AF2-388 GEN
Solar/Wind Harmer
7.278
270216AD2-079_GEN
Solar/Wind Harmer
0.372
270599AE1-208 GEN
Solar/Wind Harmer
4.734
270031AE2-169
Solar/Wind Harmer
4.734
960981AF2-389 GEN
Solar/Wind Harmer
0.86
957891AF2-083 GEN
Solar/Wind Harmer
1.915
961051AF2-396 GEN
Solar/Wind Harmer
8.944
961051AF2-396 GEN
Solar/Wind Harmer
4.16
270526AF1-158 GEN
Solar/Wind Harmer
2.474
24441505OLIV SLR
Solar/Wind Harmer
0.072
965681AG1-436 GEN
Solar/Wind Harmer
6.519
965791AG1-447 GEN
Solar/Wind Harmer
3.335
960441AF2-335 GEN
Solar/Wind Harmer
5.099
270201AC2-176 GEN
Solar/Wind Harmer
2.611
964611AG1-324 GEN
Solar/Wind Harmer
0.596
964611AG1-324 GEN
Solar/Wind Harmer
0.265
970825AG2-519 GEN
Solar/Wind Harmer
5.337
247621Y3-024
Adder
0.121
274808UNIV PK N;4U
Adder
2.459
274803UNIV PARK;6U
Adder
2.837
274770LINCOLN ;1U
Adder
3.002
274771LINCOLN ;2U
Adder
3.002
274888KELLY CRK;1U
Solar/Wind Harmer
2.856
274887GEN-1.85
Solar/Wind Harmer
2.579
276843GEN-1.7
Solar/Wind Harmer
0.277
958011AF2-095 GEN
Solar/Wind Harmer
6.966
970321AG2-212 GEN
Solar/Wind Harmer
8.576
972259AH1-714 GEN
Adder
9.139
945421AF1-207 GEN
Solar/Wind Harmer
6.716
957841AF2-078 GEN
Solar/Wind Harmer
2.89
274674JOLIET 9 ;6U
Adder
7.349
274847GR RIDGE ;BU
Solar/Wind Harmer
2.396
958481AF2-142 GEN
Solar/Wind Harmer
7.043
274861TOP CROP ;1U
Solar/Wind Harmer
2.844
274862TOP CROP ;2U
Solar/Wind Harmer
2.375
274696ROCKY RD ;4P
Adder
5.309
274695ROCKY RD ;2P
Adder
5.186
274693ROCKY RD ;1P
Adder
5.135
274697ROCKY RD ;3P
Adder
1.409
274683WAUKEGAN ;8U
Adder
9.807
274683WAUKEGAN ;8U
Adder
8.267
274764LEE CO EC;5U
Adder
4.152
274765LEE CO EC;6U
Adder
4.152
274762LEE CO EC;3U
Adder
4.142
274763LEE CO EC;4U
Adder
4.103
972267AH1-718 GEN
Adder
1.837
246938BC-WTG3
Solar/Wind Helper
11.435
246937BC-WTG2
Solar/Wind Helper
11.242
270224U2-072_GEN2
Solar/Wind Helper
0.814
270227U2-072_GEN3
Solar/Wind Helper
0.814
270228U2-072_GEN4
Solar/Wind Helper
0.814
270231U2-072_GEN5
Solar/Wind Helper
0.814
253378AE2-206_GEN
Solar/Wind Helper
0.664
276820AF1-078_GEN
Solar/Wind Helper
0.31
971573AH1-285 GEN
Solar/Wind Harmer
0.055
970373AG2-245 GEN
Solar/Wind Harmer
10.639
970825AG2-519 GEN
Solar/Wind Harmer
1.191
274751CRETE EC ;1U
Adder
2.446
274754CRETE EC ;4U
Adder
2.446
270055AF2-134 C O1
Solar/Wind Harmer
1.514
274723RIVER EC ;12
Adder
8.911
958381AF2-132 GEN
Solar/Wind Harmer
4.482
964861AG1-349 GEN
Solar/Wind Harmer
3.878
971917AH1-482 GEN
Solar/Wind Harmer
4.475
274812UNIV PK N;8U
Adder
2.47
276164X3-005 C
Solar/Wind Harmer
0.345
940581AE2-045 GEN
Solar/Wind Harmer
4.956
971605AH1-302 GEN
Solar/Wind Harmer
4.238
274801UNIV PARK;4U
Adder
2.826
276903AD2-071 C
Solar/Wind Harmer
4.847
972207SS24-0001
Solar/Wind Harmer
10.672
274773LINCOLN ;4U
Adder
3.002
274774LINCOLN ;5U
Adder
3.002
276776AD2-060 GEN
Solar/Wind Harmer
0.205
970245AG2-165 GEN
Solar/Wind Harmer
8.576
274676JOLIET 29;8U
Adder
14.678
941551AE2-152 GEN
Solar/Wind Harmer
2.167
274674JOLIET 9 ;6U
Adder
7.349
274732ELWOOD EC;7P
Adder
7.844
274871GR RIDGE ;2U
Solar/Wind Harmer
3.643
274745AC1-111 GEN9
Adder
2.629
24791305MDL-5G
Solar/Wind Harmer
1.133
276691AA1-018 GEN1
Solar/Wind Harmer
0.219
274682WAUKEGAN ;7U
Adder
8.374
274828WAUKEGAN ;BP
Adder
5.141
274822ROCKFORD ;11
Adder
8.88
972235AH1-702 GEN1
Adder
1.138
274761LEE CO EC;2U
Adder
4.142
274766LEE CO EC;7U
Adder
4.093
246936BC-WTG1
Solar/Wind Helper
11.242
270462AD2-086
Solar/Wind Helper
3.549
270223U2-072_GEN1
Solar/Wind Helper
0.814
270578AF1-285 GEN2
Solar/Wind Helper
0.551
270391AF1-285 GEN3
Solar/Wind Helper
0.551
247522W1-056 GEN
Solar/Wind Helper
1.183
960841AF2-375 GEN
Solar/Wind Helper
1.217
990497J1323
External Queue
1.3905925750732422
990792J1392
External Queue
4.783638000488281
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.951
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.321
MECLTFEXP_MEC->PJM
CLTF
6.422
SIGELTFEXP_SIGE->PJM
CLTF
0.136
LAGNLTFEXP_LAGN->PJM
CLTF
4.038
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.912
TVALTFEXP_TVA->PJM
CLTF
1.659
CPLELTFEXP_CPLE->PJM
CLTF
0.031
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.631
NYPJM->LTFIMP_NY
CLTF
0.857
LGEELTFEXP_LGEE->PJM
CLTF
1.232
WECLTFEXP_WEC->PJM
CLTF
1.723
AG2-052LTFEXP_AG2-052->PJM
LTF
0.114
AH1-155LTFEXP_AH1-155->PJM
LTF
0.17

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P2-2_#11848_05HAVILND2 69.0_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#11848_05HAVILND2 69.0_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.29 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1873.49
MW Contribution:28.71
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
43.604
24727105RPMNG2
50/50
3.161
970583AG2-370 GEN
50/50
3.283
960851AF2-376 GEN
50/50
3.283
959331AF2-224 GEN
Solar/Wind Harmer
17.632
965021AG1-366 GEN
Solar/Wind Harmer
4.1
970031AG2-029 GEN
Solar/Wind Harmer
28.706
270043AE2-236 GEN
Solar/Wind Harmer
4.928
270191TR4_S_V150
Solar/Wind Harmer
2.64
270247TR4_N_V136
Solar/Wind Harmer
0.749
944531AF1-118 GEN
Solar/Wind Harmer
26.316
971617AH1-308 GEN
Solar/Wind Harmer
4.202
247643Z2-116 C
Solar/Wind Harmer
0.042
945111AF1-176 GEN
Solar/Wind Harmer
3.283
24642205MAYFLWER
Adder
0.351
970349AG2-230 GEN
Solar/Wind Harmer
8.011
958821AF2-173 GEN
Solar/Wind Harmer
7.233
270004AE1-209 GEN
Solar/Wind Harmer
2.823
247642Z2-115 C
Solar/Wind Harmer
0.033
970289AG2-191 GEN
Solar/Wind Harmer
0.39
970291AG2-192 GEN
Solar/Wind Harmer
0.355
24441205WTRV SLR C
Solar/Wind Harmer
0.068
962031AG1-047 GEN
Solar/Wind Harmer
1.532
957741AF2-068 GEN
Solar/Wind Harmer
7.602
946031AF1-268 GEN
Solar/Wind Harmer
4.129
270535AF1-215 GEN1
Solar/Wind Harmer
2.245
972231SS25-0005
Solar/Wind Harmer
4.688
972181SS23-001
Solar/Wind Harmer
2.93
274752CRETE EC ;2U
Adder
2.414
274753CRETE EC ;3U
Adder
2.414
274724RIVER EC ;11
Adder
8.682
964401AG1-302 GEN
Solar/Wind Harmer
4.429
247604X1-042
Adder
0.203
959141AF2-205 GEN
Solar/Wind Harmer
2.92
274802UNIV PARK;5U
Adder
2.798
274826FISK ;BP
Adder
5.244
274800UNIV PARK;3U
Adder
2.786
972038AH1-567 GEN2
Adder
0.174
276772AC2-154 GEN
Solar/Wind Harmer
1.33
276806AD2-047 C O1
Solar/Wind Harmer
5.102
970941AG2-585 GEN
Solar/Wind Harmer
5.961
274772LINCOLN ;3U
Adder
2.956
972228AH1-698 GEN2
Adder
1.759
274676JOLIET 29;8U
Adder
13.948
970513AG2-328 GEN
Solar/Wind Harmer
8.414
970517AG2-330 GEN
Solar/Wind Harmer
7.631
276897AD1-100 C
Solar/Wind Harmer
13.66
939351AE1-166 GEN
Solar/Wind Harmer
2.791
276893AG1-478 C
Solar/Wind Harmer
0.197
970707AG2-453 GEN
Solar/Wind Harmer
13.17
274729ELWOOD EC;1P
Adder
7.73
24727205RPMNG3
50/50
3.134
971599AH1-298 GEN
50/50
7.698
965041AG1-368 GEN
Solar/Wind Harmer
14.119
963791AG1-232 GEN
Solar/Wind Harmer
14.505
965051AG1-369 GEN
Solar/Wind Harmer
4.394
270071AF1-092 GEN
Solar/Wind Harmer
12.275
24729505KEY G4
Adder
4.732
270024AE2-089 GEN
Solar/Wind Harmer
3.392
958711AF2-162 GEN
Solar/Wind Harmer
0.675
965101AG1-375 GEN
Solar/Wind Harmer
6.467
945581AF1-223 GEN
Solar/Wind Harmer
2.756
971771AH1-392 GEN
Solar/Wind Harmer
5.073
944161AF1-084 GEN
Solar/Wind Harmer
1.183
971347AH1-153 GEN
Solar/Wind Harmer
8.011
971769AH1-391 GEN
Solar/Wind Harmer
5.331
960681AF2-359 GEN
Solar/Wind Harmer
1.946
970115AG2-085 GEN
Solar/Wind Harmer
2.039
965461AG1-414 GEN
Solar/Wind Harmer
1.154
970289AG2-191 GEN
Solar/Wind Harmer
0.967
961761AG1-017 GEN
Solar/Wind Harmer
0.217
970615AG2-402 GEN
50/50
4.1
970611AG2-400 GEN
Solar/Wind Harmer
17.632
942221AE2-234 GEN
Solar/Wind Harmer
0.57
247620Y3-023
Adder
0.316
944541AF1-119 GEN
Solar/Wind Harmer
2.794
960971AF2-388 GEN
Solar/Wind Harmer
7.291
270216AD2-079_GEN
Solar/Wind Harmer
0.371
270599AE1-208 GEN
Solar/Wind Harmer
4.756
270031AE2-169
Solar/Wind Harmer
4.756
960981AF2-389 GEN
Solar/Wind Harmer
0.853
957891AF2-083 GEN
Solar/Wind Harmer
1.901
961051AF2-396 GEN
Solar/Wind Harmer
8.876
961051AF2-396 GEN
Solar/Wind Harmer
4.128
270526AF1-158 GEN
Solar/Wind Harmer
2.45
24441505OLIV SLR
Solar/Wind Harmer
0.071
965681AG1-436 GEN
Solar/Wind Harmer
6.44
965791AG1-447 GEN
Solar/Wind Harmer
3.295
960441AF2-335 GEN
Solar/Wind Harmer
5.097
270201AC2-176 GEN
Solar/Wind Harmer
2.605
970825AG2-519 GEN
Solar/Wind Harmer
5.332
964611AG1-324 GEN
Solar/Wind Harmer
0.595
964611AG1-324 GEN
Solar/Wind Harmer
0.264
247621Y3-024
Adder
0.121
274808UNIV PK N;4U
Adder
2.426
274803UNIV PARK;6U
Adder
2.798
274888KELLY CRK;1U
Solar/Wind Harmer
2.816
274887GEN-1.85
Solar/Wind Harmer
2.542
276843GEN-1.7
Solar/Wind Harmer
0.273
958011AF2-095 GEN
Solar/Wind Harmer
6.867
274770LINCOLN ;1U
Adder
2.956
274771LINCOLN ;2U
Adder
2.956
945421AF1-207 GEN
Solar/Wind Harmer
6.64
957841AF2-078 GEN
Solar/Wind Harmer
2.857
972259AH1-714 GEN
Adder
9.004
970321AG2-212 GEN
Solar/Wind Harmer
8.414
24727005RPMNG1
50/50
3.15
960861AF2-377 GEN
50/50
2.048
965421AG1-410 GEN
Solar/Wind Harmer
112.499
965011AG1-365 GEN
Solar/Wind Harmer
17.632
24695305TIMB G C
Solar/Wind Harmer
7.77
247521TR3_G114
Solar/Wind Harmer
2.959
270246TR4_N_V150
Solar/Wind Harmer
0.749
270063AE2-323 C
Solar/Wind Harmer
1.793
944231AF1-091 GEN
Solar/Wind Harmer
2.939
965651AG1-433 GEN
Solar/Wind Harmer
3.646
24639705ELKHART HY
Adder
0.1
958861AF2-177 GEN
Solar/Wind Harmer
7.068
945371AF1-202 GEN
Solar/Wind Harmer
4.24
945111AF1-176 GEN
Solar/Wind Harmer
10.358
270505AE1-170 C O1
Solar/Wind Harmer
8.351
270449AD2-020 GEN
Solar/Wind Harmer
1.532
943021AE2-325 GEN
Solar/Wind Harmer
1.991
270005AE1-210 C O1
Solar/Wind Harmer
2.823
965031AG1-367 GEN
Solar/Wind Harmer
5.166
970291AG2-192 GEN
Solar/Wind Harmer
0.661
270032AE2-172
Solar/Wind Harmer
2.352
970825AG2-519 GEN
Solar/Wind Harmer
1.19
970373AG2-245 GEN
Solar/Wind Harmer
10.512
270055AF2-134 C O1
Solar/Wind Harmer
1.496
274751CRETE EC ;1U
Adder
2.414
274754CRETE EC ;4U
Adder
2.414
274723RIVER EC ;12
Adder
8.792
958381AF2-132 GEN
Solar/Wind Harmer
4.429
964861AG1-349 GEN
Solar/Wind Harmer
3.833
971917AH1-482 GEN
Solar/Wind Harmer
4.423
274812UNIV PK N;8U
Adder
2.436
276164X3-005 C
Solar/Wind Harmer
0.341
276903AD2-071 C
Solar/Wind Harmer
4.832
940581AE2-045 GEN
Solar/Wind Harmer
4.899
971605AH1-302 GEN
Solar/Wind Harmer
4.189
274801UNIV PARK;4U
Adder
2.786
276776AD2-060 GEN
Solar/Wind Harmer
0.202
972207SS24-0001
Solar/Wind Harmer
10.509
274773LINCOLN ;4U
Adder
2.956
274774LINCOLN ;5U
Adder
2.956
274676JOLIET 29;8U
Adder
14.465
970245AG2-165 GEN
Solar/Wind Harmer
8.414
941551AE2-152 GEN
Solar/Wind Harmer
2.135
274674JOLIET 9 ;6U
Adder
7.242
274732ELWOOD EC;7P
Adder
7.731
274871GR RIDGE ;2U
Solar/Wind Harmer
3.589
24791305MDL-5G
Solar/Wind Harmer
1.12
274745AC1-111 GEN9
Adder
2.59
276691AA1-018 GEN1
Solar/Wind Harmer
0.215
274682WAUKEGAN ;7U
Adder
8.25
274828WAUKEGAN ;BP
Adder
5.064
274822ROCKFORD ;11
Adder
8.745
972235AH1-702 GEN1
Adder
1.121
274761LEE CO EC;2U
Adder
4.079
274766LEE CO EC;7U
Adder
4.03
246936BC-WTG1
Solar/Wind Helper
11.257
270462AD2-086
Solar/Wind Helper
3.681
270223U2-072_GEN1
Solar/Wind Helper
0.846
270578AF1-285 GEN2
Solar/Wind Helper
0.573
270391AF1-285 GEN3
Solar/Wind Helper
0.573
247522W1-056 GEN
Solar/Wind Helper
1.273
960841AF2-375 GEN
Solar/Wind Helper
1.292
241840AF1-064_GEN
Solar/Wind Helper
0.462
270594AE1-207 GEN
Solar/Wind Harmer
7.431
270536AF1-215 GEN2
Solar/Wind Harmer
2.245
274814UNIV PK N;0U
Adder
2.458
274807UNIV PK N;3U
Adder
2.452
274805UNIV PK N;1U
Adder
2.442
274811UNIV PK N;7U
Adder
2.436
958391AF2-133 GEN
Solar/Wind Harmer
4.402
972037AH1-567 GEN1
Adder
0.088
274827FISK ;RP
Adder
3.716
960591AF2-350 GEN
Solar/Wind Harmer
4.769
274775LINCOLN ;6U
Adder
2.956
274776LINCOLN ;7U
Adder
2.956
274777LINCOLN ;8U
Adder
2.956
24725505WLD G2 C
Solar/Wind Harmer
1.889
24699105WLD G1 C
Solar/Wind Harmer
1.867
972227AH1-698 GEN1
Adder
1.238
274687WILL CNTY;4U
Adder
13.211
274687WILL CNTY;4U
Adder
13.211
274675JOLIET 29;7U
Adder
14.465
274675JOLIET 29;7U
Adder
13.948
274731ELWOOD EC;2P
Adder
7.73
274733ELWOOD EC;3P
Adder
7.73
274735ELWOOD EC;4P
Adder
7.73
274728ELWOOD EC;5P
Adder
7.731
970833AG2-524 GEN
Solar/Wind Harmer
4.078
970833AG2-524 GEN
Solar/Wind Harmer
1.897
24690905MDL-1G C
Solar/Wind Harmer
3.728
270180AB1-006 GEN1
Solar/Wind Harmer
3.34
946581AF1-322 GEN
Solar/Wind Harmer
4.751
24691005MDL-2G C
Solar/Wind Harmer
1.717
24697605MDL-3G C
Solar/Wind Harmer
1.712
24697905MDL-4G C
Solar/Wind Harmer
1.066
270181AB1-006 GEN2
Solar/Wind Harmer
0.332
274746AC1-111 G10
Adder
2.59
274744AC1-111 GEN8
Adder
2.59
274823ROCKFORD ;21
Adder
8.682
957201AF2-014 GEN
Solar/Wind Helper
8.899
270317AD1-130_GEN
Solar/Wind Helper
4.078
966831AG1-554 GEN
Solar/Wind Helper
0.944
247607V1-011 GEN
Solar/Wind Helper
1.377
270499AE1-146 GEN
Solar/Wind Helper
2.155
270284AF1-227 GEN1
Solar/Wind Helper
1.624
270286AF1-227 GEN2
Solar/Wind Helper
0.595
270287AF1-227 GEN3
Solar/Wind Helper
0.595
945641AF1-229 GEN
Solar/Wind Helper
0.979
274674JOLIET 9 ;6U
Adder
7.242
274847GR RIDGE ;BU
Solar/Wind Harmer
2.361
958481AF2-142 GEN
Solar/Wind Harmer
6.941
274861TOP CROP ;1U
Solar/Wind Harmer
2.803
274862TOP CROP ;2U
Solar/Wind Harmer
2.341
274696ROCKY RD ;4P
Adder
5.229
274695ROCKY RD ;2P
Adder
5.109
274693ROCKY RD ;1P
Adder
5.058
274697ROCKY RD ;3P
Adder
1.388
274683WAUKEGAN ;8U
Adder
9.661
274683WAUKEGAN ;8U
Adder
8.144
274764LEE CO EC;5U
Adder
4.088
274765LEE CO EC;6U
Adder
4.088
274762LEE CO EC;3U
Adder
4.079
274763LEE CO EC;4U
Adder
4.04
972267AH1-718 GEN
Adder
1.808
246938BC-WTG3
Solar/Wind Helper
11.451
246937BC-WTG2
Solar/Wind Helper
11.257
270224U2-072_GEN2
Solar/Wind Helper
0.846
270227U2-072_GEN3
Solar/Wind Helper
0.846
270228U2-072_GEN4
Solar/Wind Helper
0.846
270231U2-072_GEN5
Solar/Wind Helper
0.846
270007AE1-245 C
Solar/Wind Helper
2.066
253378AE2-206_GEN
Solar/Wind Helper
0.708
276820AF1-078_GEN
Solar/Wind Helper
0.331
942801AE2-298 GEN
Solar/Wind Helper
0.294
971573AH1-285 GEN
Solar/Wind Harmer
0.054
274730ELWOOD EC;6P
Adder
7.731
274734ELWOOD EC;8P
Adder
7.731
274736ELWOOD EC;9P
Adder
7.731
24755605MDL-5G
Solar/Wind Harmer
1.12
970781AG2-491 GEN
Solar/Wind Harmer
4.642
943121AE2-341 GEN
Solar/Wind Harmer
6.946
943591AF1-030 GEN
Solar/Wind Harmer
4.631
276694AA1-018 GEN2
Solar/Wind Harmer
2.92
274682WAUKEGAN ;7U
Adder
8.25
972236AH1-702 GEN2
Adder
0.974
274760LEE CO EC;1U
Adder
4.079
274767LEE CO EC;8U
Adder
4.03
270485AE1-090_GEN
Solar/Wind Helper
0.32
942871AE2-306 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
1.169
990497J1323
External Queue
1.4294555187225342
990792J1392
External Queue
4.917326927185059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
40.675
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.11
MECLTFEXP_MEC->PJM
CLTF
6.314
SIGELTFEXP_SIGE->PJM
CLTF
0.133
LAGNLTFEXP_LAGN->PJM
CLTF
3.926
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.801
TVALTFEXP_TVA->PJM
CLTF
1.603
CPLELTFEXP_CPLE->PJM
CLTF
0.004
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.88
NYPJM->LTFIMP_NY
CLTF
0.824
LGEELTFEXP_LGEE->PJM
CLTF
1.192
WECLTFEXP_WEC->PJM
CLTF
1.697
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-024_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1   /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-015_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P2-3_MP-500-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-008B_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1          /*02DAV-BE     345.0 - 02LEMOYN     345.0
 DISCONNECT BUS 238670                                          /*02DVBSG1      25.0
 REMOVE MACHINE 1 FROM BUS 238670                               /*02DVBSG1      25.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-013_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238654 CKT 1          /*02LEMOYN     345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238890 CKT 2          /*02LEMOYN     345.0 - 02LEMOYN     138.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 238889 TO BUS 238961 CKT 1 /*02LEMOYN     345.0 - 02MIDWAY     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238889 TO BUS 238961 CKT 1 /*02LEMOYN     345.0 - 02MIDWAY     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238654 CKT 1   /*02LEMOYN     345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238890 CKT 1   /*02LEMOYN     345.0 - 02LEMOYN     138.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-009_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-602_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P7-1_OEC-345-002_SRT-A'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1   /*02BEAVER     345.0 - 02LAKEAVE    345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2   /*02BEAVER     345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-901_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 239725 TO BUS 238569 CKT 1 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 1 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-007A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-031_SRT-A'
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 238569 CKT 2   /*02LAKEAVE    345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 239726 CKT 1   /*02LAKEAVE    345.0 - 02LAKEAVE    138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-002_SRT-A'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238607 CKT 1   /*02BEAVER     345.0 - 02CARLIL     345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1   /*02BEAVER     345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-003_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1394 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 238566 TO BUS 238569 CKT 1 /*02WLORAIN    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 238566 TO BUS 238569 CKT 1 /*02WLORAIN    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 238569 CKT 1   /*02LAKEAVE    345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 239726 CKT 1   /*02LAKEAVE    345.0 - 02LAKEAVE    138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-005_SRT-A'
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239171 CKT 2   /*02WLORAIN    345.0 - 02WLORG-2     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239172 CKT 3   /*02WLORAIN    345.0 - 02WLORG-3     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239173 CKT 4   /*02WLORAIN    345.0 - 02WLORG-4     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239174 CKT 5   /*02WLORAIN    345.0 - 02WLORG-5     13.8
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238566 CKT 1   /*02BEAVER     345.0 - 02WLORAIN    345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 241877 CKT 1   /*02BEAVER     345.0 - AC2-103 TAP  345.0
 DISCONNECT BUS 239171                                   /*02WLORG-2     13.8
 DISCONNECT BUS 239172                                   /*02WLORG-3     13.8
 DISCONNECT BUS 239173                                   /*02WLORG-4     13.8
 DISCONNECT BUS 239174                                   /*02WLORG-5     13.8
 REMOVE MACHINE 2 FROM BUS 239171                        /*02WLORG-2     13.8
 REMOVE MACHINE 3 FROM BUS 239172                        /*02WLORG-3     13.8
 REMOVE MACHINE 4 FROM BUS 239173                        /*02WLORG-4     13.8
 REMOVE MACHINE 5 FROM BUS 239174                        /*02WLORG-5     13.8
END
CONTINGENCY 'ATSI_P2-3_OEC-345-006_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 241877 CKT 1          /*02BEAVER     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1          /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1878 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET POSTCONTRATING 1892 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1542 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET PRECONTRATING 1555 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-825_SRT-A'
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-824_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-F1_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 2   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-12_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 1   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010B1_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1          /*02DAV-BE     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010B2_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1          /*02DAV-BE     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1878 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1542 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-3_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 1   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-810_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-809_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-007_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1          /*02DAV-BE     345.0 - 02BAY SH     345.0
 DISCONNECT BUS 238670                                          /*02DVBSG1      25.0
 REMOVE MACHINE 1 FROM BUS 238670                               /*02DVBSG1      25.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-004_SRT-A'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 238654 CKT 1   /*02BAY SH     345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 2   /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-005_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 238654 CKT 1          /*02BAY SH     345.0 - 02DAV-BE     345.0
 REDUCE BUS 238563 SHUNT BY 100 PERCENT                         /*02BAY SH     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-006_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1          /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-601_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1   /*02DAV-BE     345.0 - 02BAY SH     345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-021_SRT-A-1'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 1   /*02BAY SH     345.0 - AH1-690 TP   345.0
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 2   /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#8075_05MARYSV 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P4_#9728_05MALIS 138_L1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 2    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9730_05MALIS 138_P1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243553 CKT 1    /*05MALIS      138.0 - 05POLARS     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9729_05MALIS 138_M1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 1    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7222_05MALIS 765_D_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7216_05VASSEL 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1   /*05MALIS      765.0 - 05VASSEL     765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1    /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#706_05GAVIN 765_C1_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-027A_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1   /*02DAV-BE     345.0 - 02HAYES      345.0
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT14_SRT-SL'
 OPEN BRANCH FROM BUS 235109 TO BUS 235081 CKT 1                /*AB1-106 POI  500.0 - T-174  1     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT5_SRT-SL'
 OPEN BRANCH FROM BUS 235851 TO BUS 235850 CKT 1                /*01NTHLNV     500.0 - 01LONGVIEW   500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235111 TO BUS 235851 CKT 1 /*01 502 J     500.0 - 01NTHLNV     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235851 TO BUS 235106 CKT 1 /*01NTHLNV     500.0 - 01FMARTN     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235111 TO BUS 235851 CKT 1 /*01 502 J     500.0 - 01NTHLNV     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235851 TO BUS 235106 CKT 1 /*01NTHLNV     500.0 - 01FMARTN     500.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 970238 TO BUS 290599 CKT 1    /*AG2-162 TP   765.0 - 05JEFFRSN_RG 765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#2995_05E LIMA 345_M_SRT-A'
 OPEN BRANCH FROM BUS 242935 TO BUS 245128 CKT 2   /*05E LIMA     345.0 - 05E.LIMA 2EQ   1.0
 OPEN BRANCH FROM BUS 242935 TO BUS 246929 CKT 1   /*05E LIMA     345.0 - 05MADDOX     345.0
 OPEN BRANCH FROM BUS 242989 TO BUS 245128 CKT 2   /*05E LIMA     138.0 - 05E.LIMA 2EQ   1.0
 OPEN BRANCH FROM BUS 245128 TO BUS 245148 CKT 2   /*05E.LIMA 2EQ   1.0 - 05E.LIMA T2   13.8
END
CONTINGENCY 'AEP_P7-1_#11010___SRT-A'
 OPEN BRANCH FROM BUS 242933 TO BUS 243211 CKT 1   /*05RPMONE     345.0 - 05ALLEN      345.0
 OPEN BRANCH FROM BUS 243211 TO BUS 243232 CKT 1   /*05ALLEN      345.0 - 05SORENS     345.0
END
CONTINGENCY 'AEP_P1-2_#6463_16757_SRT-A'
 OPEN BRANCH FROM BUS 242935 TO BUS 246929 CKT 1   /*05E LIMA     345.0 - 05MADDOX     345.0
END
CONTINGENCY 'AEP_P7-1_#17567_SRT-SL'
 OPEN BRANCH FROM BUS 242939 TO BUS 242945 CKT 1   /*05MARYSV     345.0 - 05SW LIM     345.0
 OPEN BRANCH FROM BUS 242939 TO BUS 290984 CKT 1   /*05MARYSV     345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243902 TO BUS 243903 CKT 1   /*05HARDIN SW  345.0 - 05GUNN RD SW 345.0
END
CONTINGENCY 'AEP_P4_#7443_05DUMONT 765_A_SRT-A'
 OPEN BRANCH FROM BUS 243205 TO BUS 243206 CKT 1    /*05COOK       765.0 - 05DUMONT     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P4_#7442_05SORENS 765_K2_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P4_#7444_05DUMONT 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243641 CKT 2    /*05DUMONT     765.0 - 05DUMONT 2EQ   1.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 243219 TO BUS 243641 CKT 2    /*05DUMONT     345.0 - 05DUMONT 2EQ   1.0
 OPEN BRANCH FROM BUS 243641 TO BUS 243642 CKT 2    /*05DUMONT 2EQ   1.0 - 05DUMONT T2   34.5
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P1-2_#7442_200545_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P2-2_#9456_06DEARB1 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
CONTINGENCY 'AEP_P4_#9456_06DEARB1 345_DC_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-034T_SRT-A'
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 242936 CKT 1   /*02LALLENDORF 345.0 - 05FOSTOR     345.0
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-033T_SRT-A'
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 972210 CKT 1   /*02LALLENDORF 345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-023T_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238530 TO BUS 239344 CKT 3          /*02ALLEN      345.0 - 02ALLEN-2    138.0
 DISCONNECT BRANCH FROM BUS 238530 TO BUS 256583 CKT 1          /*02ALLEN      345.0 - 18MOROCCO    345.0
 SET POSTCONTRATING 1394 BRANCH FROM BUS 238530 TO BUS 238961 CKT 1 /*02ALLEN      345.0 - 02MIDWAY     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 238530 TO BUS 238961 CKT 1 /*02ALLEN      345.0 - 02MIDWAY     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-022T_SRT-A'
 DISCONNECT BRANCH FROM BUS 238530 TO BUS 239018 CKT 1   /*02ALLEN      345.0 - 02FULTON     345.0
 DISCONNECT BRANCH FROM BUS 238530 TO BUS 256583 CKT 1   /*02ALLEN      345.0 - 18MOROCCO    345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-009_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239289 CKT 1          /*02BEAVER     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'AEP_P7-1_#11067___SRT-A'
 OPEN BRANCH FROM BUS 243051 TO BUS 247864 CKT 1   /*05NDELPH     138.0 - 05LOGTOWN    138.0
 OPEN BRANCH FROM BUS 246352 TO BUS 246950 CKT 1   /*05HAVILAND2  138.0 - 05TIMBER SW  138.0
END
CONTINGENCY 'AEP_P7-1_#11068___SRT-A'
 OPEN BRANCH FROM BUS 242989 TO BUS 243017 CKT 1   /*05E LIMA     138.0 - 05HAVILAND1  138.0
 OPEN BRANCH FROM BUS 243051 TO BUS 247864 CKT 1   /*05NDELPH     138.0 - 05LOGTOWN    138.0
END
CONTINGENCY 'AEP_P2-2_#11848_05HAVILND2 69.0_2_SRT-A'
 OPEN BRANCH FROM BUS 243169 TO BUS 245866 CKT 1   /*05HAVILND2    69.0 - 05CAVETT      69.0
 OPEN BRANCH FROM BUS 243169 TO BUS 245898 CKT 1   /*05HAVILND2    69.0 - 05PAULDING    69.0
 OPEN BRANCH FROM BUS 243169 TO BUS 246352 CKT 4   /*05HAVILND2    69.0 - 05HAVILAND2  138.0
 OPEN BRANCH FROM BUS 246352 TO BUS 246950 CKT 1   /*05HAVILAND2  138.0 - 05TIMBER SW  138.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
238563 to 238654 ckt 1
238569 to 238607 ckt 1
238569 to 239725 ckt 1
238569 to 239725 ckt 2
238654 to 239289 ckt 1
238654 to 241877 ckt 1
239289 to 238569 ckt 1
238889 to 238654 ckt 1
243211 to 242933 ckt 1
290984 to 242939 ckt 1
242922 to 290622 ckt 1
243903 to 290984 ckt 1
290618 to 242924 ckt Z1
243458 to 246752 ckt 1
243208 to 242865 ckt 2
242865 to 248000 ckt 1
242925 to 235117 ckt 1
290623 to 242925 ckt Z1
246929 to 242935 ckt 1
242926 to 246751 ckt 1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
242933 to 965420 ckt 1
243232 to 246999 ckt 3
246999 to 290607 ckt Z1
290607 to 290608 ckt 1
243233 to 249567 ckt 1
256583 to 238530 ckt 1
264612 to 241901 ckt 1
241877 to 238569 ckt 1
965420 to 246929 ckt 1

Winter Peak Analysis

The New Service Request AG2-029 was evaluated as a 300.0 MW (39.0 MW Capacity) injection in the AEP area.

AG2-029 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 300.0 MW (300.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC120.08 %1737.0B2085.732.09
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC117.93 %1737.0B2048.412.11
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC115.82 %1737.0B2011.722.11
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC115.73 %1737.0B2010.182.05
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC114.0 %4961.0B5655.613.67
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC104.24 %4961.0B5171.463.45
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC102.76 %4961.0B5098.143.46
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC102.76 %4961.0B5098.113.46
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC100.41 %4961.0B4981.373.68
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC103.24 %2219.0B2290.852.09
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC109.35 %2317.0B2533.640.82
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC108.51 %2317.0B2514.080.82
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
BreakerAC107.9 %2317.0B2499.970.93
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
BusAC107.9 %2317.0B2499.960.93
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC105.42 %2219.0B2339.212.09
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC102.19 %2219.0B2267.592.11
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC102.19 %2219.0B2267.562.11
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC101.94 %2219.0B2262.152.05

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.08 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2085.73
MW Contribution:2.09
Bus #Bus NameTypeMW Contribution
247620Y3-023
50/50
0.46
965041AG1-368 GEN
Solar/Wind Harmer
0.694
270191TR4_S_V150
Solar/Wind Harmer
6.398
965101AG1-375 GEN
Solar/Wind Harmer
0.505
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.368
971917AH1-482 GEN
Solar/Wind Harmer
6.668
276691AA1-018 GEN1
Solar/Wind Harmer
0.448
276872AE1-163_GEN1
Solar/Wind Harmer
9.042
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.622
971067AG2-660 GEN
Solar/Wind Harmer
1.611
970115AG2-085 GEN
Solar/Wind Harmer
0.161
276741O09 GEN1
Solar/Wind Harmer
4.795
276655WTG1_EQ
Solar/Wind Harmer
6.613
270578AF1-285 GEN2
Solar/Wind Helper
0.282
247522W1-056 GEN
Solar/Wind Helper
1.885
270286AF1-227 GEN2
Solar/Wind Helper
0.344
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.289
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.887
970517AG2-330 GEN
Solar/Wind Harmer
13.834
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.464
962781AG1-127 GEN
Solar/Wind Harmer
0.39
958821AF2-173 GEN
Solar/Wind Harmer
0.573
971335AH1-147 GEN
Solar/Wind Harmer
0.81
24697605MDL-3G C
Solar/Wind Harmer
5.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.805
926823AC1-168 GEN
Solar/Wind Harmer
4.888
24385905FR-11G C
Solar/Wind Harmer
5.945
276782AC1-033 GEN
Solar/Wind Harmer
5.076
24725505WLD G2 C
Solar/Wind Harmer
4.997
946321AF1-296 GEN
Solar/Wind Harmer
11.312
958581AF2-149 GEN
Solar/Wind Helper
0.216
960611AF2-352 GEN
Solar/Wind Harmer
1.01
970583AG2-370 GEN
50/50
2.775
970031AG2-029 GEN
Solar/Wind Harmer
2.089
270247TR4_N_V136
Solar/Wind Harmer
1.16
965051AG1-369 GEN
Solar/Wind Harmer
0.295
960591AF2-350 GEN
Solar/Wind Harmer
0.429
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.024
939401AE1-172 GEN
Solar/Wind Harmer
16.293
276876AE1-163_GEN2
Solar/Wind Harmer
9.042
274857EASY ROAD;U1
Solar/Wind Harmer
6.189
961761AG1-017 GEN
Solar/Wind Harmer
0.383
276656WTG2_EQ
Solar/Wind Harmer
0.876
941731AE2-173 GEN
Solar/Wind Harmer
3.84
270462AD2-086
Solar/Wind Helper
1.767
270317AD1-130_GEN
Solar/Wind Helper
1.153
270287AF1-227 GEN3
Solar/Wind Helper
0.344
970615AG2-402 GEN
50/50
4.56
24729405KEY G3
50/50
6.792
24729505KEY G4
50/50
6.679
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.437
270505AE1-170 C O1
Solar/Wind Harmer
0.719
274888KELLY CRK;1U
Solar/Wind Harmer
8.705
970941AG2-585 GEN
Solar/Wind Harmer
0.536
971605AH1-302 GEN
Solar/Wind Harmer
6.289
276805AD2-038 GEN
Solar/Wind Harmer
7.442
274850MENDOTA H;RU
Solar/Wind Harmer
3.644
276861AD2-134 GEN
Solar/Wind Harmer
2.487
274864CRW2-WTG
Solar/Wind Harmer
7.63
970569AG2-363 GEN
Solar/Wind Harmer
1.196
274858EASY ROAD;U2
Solar/Wind Harmer
6.189
276157O29GEN1
Solar/Wind Harmer
5.697
957751AF2-069 GEN
Solar/Wind Harmer
0.51
939741AE1-205 GEN
Solar/Wind Harmer
0.768
246938BC-WTG3
Solar/Wind Helper
5.468
246936BC-WTG1
Solar/Wind Helper
5.531
24639705ELKHART HY
50/50
0.149
963791AG1-232 GEN
Solar/Wind Harmer
0.959
270246TR4_N_V150
Solar/Wind Harmer
1.16
24695305TIMB G C
Solar/Wind Harmer
9.67
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.419
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.409
971343AH1-151 GEN
Solar/Wind Harmer
0.805
970169AG2-114 GEN
Solar/Wind Harmer
0.398
961011AF2-392 GEN
Solar/Wind Harmer
12.167
270227U2-072_GEN3
Solar/Wind Helper
0.141
270228U2-072_GEN4
Solar/Wind Helper
0.141
276820AF1-078_GEN
Solar/Wind Helper
0.151
960851AF2-376 GEN
50/50
2.066
965021AG1-366 GEN
Solar/Wind Harmer
4.56
958861AF2-177 GEN
Solar/Wind Harmer
15.756
945371AF1-202 GEN
Solar/Wind Harmer
7.43
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.232
270594AE1-207 GEN
Solar/Wind Harmer
0.652
270032AE2-172
Solar/Wind Harmer
3.259
971997AH1-543 GEN
Solar/Wind Harmer
0.64
276863AD2-134 GEN
Solar/Wind Harmer
2.487
274863CRW1-WTG
Solar/Wind Harmer
7.63
276889AE2-281 GEN
Solar/Wind Harmer
2.583
24691005MDL-2G C
Solar/Wind Harmer
5.066
274856ECOGROVE ;U1
Solar/Wind Harmer
4.672
971549AH1-272 GEN
Solar/Wind Harmer
0.724
276158O29GEN2
Solar/Wind Harmer
5.697
276708O09 GEN2
Solar/Wind Harmer
4.795
246937BC-WTG2
Solar/Wind Helper
5.531
270485AE1-090_GEN
Solar/Wind Helper
0.154
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.14
945111AF1-176 GEN
Solar/Wind Harmer
0.877
945111AF1-176 GEN
Solar/Wind Harmer
4.78
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.467
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.563
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.239
970571AG2-364 GEN
Solar/Wind Harmer
0.798
970825AG2-519 GEN
Solar/Wind Harmer
0.442
970825AG2-519 GEN
Solar/Wind Harmer
1.697
971681AH1-341 GEN
Solar/Wind Harmer
0.594
938861AE1-114 GEN
Solar/Wind Harmer
9.271
276603SUBLETTE C
Solar/Wind Harmer
1.346
253378AE2-206_GEN
Solar/Wind Helper
0.334
971599AH1-298 GEN
50/50
10.28
960861AF2-377 GEN
50/50
2.361
24729305KEY G2
50/50
6.792
970611AG2-400 GEN
Solar/Wind Harmer
1.14
270071AF1-092 GEN
Solar/Wind Harmer
0.935
970321AG2-212 GEN
Solar/Wind Harmer
0.887
270005AE1-210 C O1
Solar/Wind Harmer
6.381
276602WESTBROOK C
Solar/Wind Harmer
2.837
276645AC1-214 GEN1
Solar/Wind Harmer
1.672
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.583
24387305FR-4G C
Solar/Wind Harmer
4.536
24386605FR-22G C
Solar/Wind Harmer
3.024
24387005FR-3G C
Solar/Wind Harmer
2.994
942111AE2-223 GEN
Solar/Wind Harmer
8.986
960841AF2-375 GEN
Solar/Wind Helper
0.553
24641605TWIN BRNCH
50/50
0.015
944531AF1-118 GEN
Solar/Wind Harmer
2.039
274887GEN-1.85
Solar/Wind Harmer
7.997
970707AG2-453 GEN
Solar/Wind Harmer
1.193
970833AG2-524 GEN
Solar/Wind Harmer
3.709
958481AF2-142 GEN
Solar/Wind Harmer
0.624
276868AE1-113 GEN
Solar/Wind Harmer
13.718
971675AH1-338 GEN
Solar/Wind Harmer
0.729
970781AG2-491 GEN
Solar/Wind Harmer
0.403
960791AF2-370 GEN
Solar/Wind Harmer
1.606
276903AD2-071 C
Solar/Wind Harmer
0.391
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.31
270224U2-072_GEN2
Solar/Wind Helper
0.141
270391AF1-285 GEN3
Solar/Wind Helper
0.282
241847AF2-150_GEN
Solar/Wind Helper
0.259
971617AH1-308 GEN
Solar/Wind Harmer
5.12
943021AE2-325 GEN
Solar/Wind Harmer
2.954
958011AF2-095 GEN
Solar/Wind Harmer
0.618
971573AH1-285 GEN
Solar/Wind Harmer
0.358
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.616
942991AE2-321 GEN
Solar/Wind Harmer
0.407
971333AH1-146 GEN
Solar/Wind Harmer
0.81
24697905MDL-4G C
Solar/Wind Harmer
3.34
970819AG2-516 GEN
Solar/Wind Harmer
0.479
274851PROVIDENC;RU
Solar/Wind Harmer
3.693
964611AG1-324 GEN
Solar/Wind Harmer
0.35
270201AC2-176 GEN
Solar/Wind Harmer
6.57
274878BISHOP HL;2U
Solar/Wind Harmer
4.493
24699105WLD G1 C
Solar/Wind Harmer
4.967
965931AG1-462 GEN
Solar/Wind Harmer
0.963
270499AE1-146 GEN
Solar/Wind Helper
0.534
24729205KEY G1
50/50
6.679
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.927
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.196
270004AE1-209 GEN
Solar/Wind Harmer
6.381
274872LEEDK;1U
Solar/Wind Harmer
0.18
270180AB1-006 GEN1
Solar/Wind Harmer
9.491
24791305MDL-5G
Solar/Wind Harmer
3.34
959081AF2-199 GEN
Solar/Wind Harmer
0.403
971475AH1-234 GEN
Solar/Wind Harmer
0.892
276646AC1-214 GEN2
Solar/Wind Harmer
1.672
24386205FR-12G C
Solar/Wind Harmer
3.157
276726Z2-087_GEN
Solar/Wind Harmer
9.984
972181SS23-001
Solar/Wind Harmer
0.44
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.3
970289AG2-191 GEN
Solar/Wind Harmer
0.078
24755605MDL-5G
Solar/Wind Harmer
3.34
959091AF2-200 GEN
Solar/Wind Harmer
0.805
946031AF1-268 GEN
Solar/Wind Harmer
0.324
274849CRESCENT ;1U
Solar/Wind Harmer
2.552
274877BISHOP HL;1U
Solar/Wind Harmer
4.493
270349AD2-093_GEN
Solar/Wind Helper
0.444
965651AG1-433 GEN
Solar/Wind Harmer
8.113
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.816
943121AE2-341 GEN
Solar/Wind Harmer
0.628
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.544
957471AF2-041 GEN
Solar/Wind Harmer
1.208
274848CAMPGROVE;RU
Solar/Wind Harmer
7.026
959341AF2-225 GEN
Solar/Wind Harmer
0.576
957201AF2-014 GEN
Solar/Wind Helper
3.936
270284AF1-227 GEN1
Solar/Wind Helper
0.932
270428AC2-015 C
Solar/Wind Helper
0.365
970521AG2-332 GEN
50/50
10.75
247521TR3_G114
Solar/Wind Harmer
8.58
276806AD2-047 C O1
Solar/Wind Harmer
13.208
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.511
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.495
971341AH1-150 GEN
Solar/Wind Harmer
0.805
270302AB2-170 GEN
Solar/Wind Helper
1.153
270231U2-072_GEN5
Solar/Wind Helper
0.141
270471AD2-092_GEN
Solar/Wind Helper
0.444
960971AF2-388 GEN
Solar/Wind Harmer
16.226
970349AG2-230 GEN
Solar/Wind Harmer
0.722
971347AH1-153 GEN
Solar/Wind Harmer
0.722
961051AF2-396 GEN
Solar/Wind Harmer
0.958
961051AF2-396 GEN
Solar/Wind Harmer
7.664
270599AE1-208 GEN
Solar/Wind Harmer
0.368
970245AG2-165 GEN
Solar/Wind Harmer
0.887
972231SS25-0005
Solar/Wind Harmer
0.704
274862TOP CROP ;2U
Solar/Wind Harmer
6.808
970921AG2-575 GEN
Solar/Wind Harmer
0.41
970921AG2-575 GEN
Solar/Wind Harmer
1.639
274879MINONK ;1U
Solar/Wind Harmer
9.594
971411AH1-196 GEN
Solar/Wind Harmer
0.608
274855GSG-6 ;RU
Solar/Wind Harmer
5.144
24386405FR-21G C
Solar/Wind Harmer
3.024
942871AE2-306 GEN
Solar/Wind Helper
0.211
945641AF1-229 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.447
959331AF2-224 GEN
Solar/Wind Harmer
1.14
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.037
276843GEN-1.7
Solar/Wind Harmer
0.708
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.858
276882AE2-255 GEN
Solar/Wind Harmer
4.328
960441AF2-335 GEN
Solar/Wind Harmer
0.402
270223U2-072_GEN1
Solar/Wind Helper
0.141
966831AG1-554 GEN
Solar/Wind Helper
0.276
274854TWINGROVE;U2
Solar/Wind Harmer
6.161
944201AF1-088_MTX
Adder
55.858
957141AF2-008_MTX
Adder
27.929
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.501
NYPJM->LTFIMP_NY
CLTF
1.242
MECLTFEXP_MEC->PJM
CLTF
9.671
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.201
WECLTFEXP_WEC->PJM
CLTF
2.632
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.085
TVALTFEXP_TVA->PJM
CLTF
2.406
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.398
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.626
LGEELTFEXP_LGEE->PJM
CLTF
1.821
LAGNLTFEXP_LAGN->PJM
CLTF
5.9
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.93 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2048.41
MW Contribution:2.11
Bus #Bus NameTypeMW Contribution
247620Y3-023
50/50
0.466
270144AC1-141 ST1_
50/50
1.789
24642205MAYFLWER
50/50
0.618
962601AG1-109 GEN
50/50
2.389
965041AG1-368 GEN
Solar/Wind Harmer
0.706
270191TR4_S_V150
Solar/Wind Harmer
6.54
965101AG1-375 GEN
Solar/Wind Harmer
0.511
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.373
971917AH1-482 GEN
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
970115AG2-085 GEN
Solar/Wind Harmer
0.163
276872AE1-163_GEN1
Solar/Wind Harmer
9.109
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.701
971067AG2-660 GEN
Solar/Wind Harmer
1.622
276741O09 GEN1
Solar/Wind Harmer
4.827
276655WTG1_EQ
Solar/Wind Harmer
6.657
270578AF1-285 GEN2
Solar/Wind Helper
0.267
247522W1-056 GEN
Solar/Wind Helper
1.806
270286AF1-227 GEN2
Solar/Wind Helper
0.313
961961AG1-039 GEN
Solar/Wind Helper
0.152
241960AC2-195 GEN
Solar/Wind Helper
0.26
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.894
970517AG2-330 GEN
Solar/Wind Harmer
13.95
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.467
958821AF2-173 GEN
Solar/Wind Harmer
0.58
962781AG1-127 GEN
Solar/Wind Harmer
0.393
971335AH1-147 GEN
Solar/Wind Harmer
0.816
24697605MDL-3G C
Solar/Wind Harmer
5.096
270181AB1-006 GEN2
Solar/Wind Harmer
0.634
971171AH1-044 GEN
Solar/Wind Harmer
0.811
926823AC1-168 GEN
Solar/Wind Harmer
4.923
24385905FR-11G C
Solar/Wind Harmer
5.987
276782AC1-033 GEN
Solar/Wind Harmer
5.11
24725505WLD G2 C
Solar/Wind Harmer
5.056
946321AF1-296 GEN
Solar/Wind Harmer
11.381
960611AF2-352 GEN
Solar/Wind Harmer
1.153
970583AG2-370 GEN
50/50
2.823
970031AG2-029 GEN
Solar/Wind Harmer
2.112
270247TR4_N_V136
Solar/Wind Harmer
1.186
965051AG1-369 GEN
Solar/Wind Harmer
0.301
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.088
939401AE1-172 GEN
Solar/Wind Harmer
16.42
276876AE1-163_GEN2
Solar/Wind Harmer
9.109
274857EASY ROAD;U1
Solar/Wind Harmer
6.231
961761AG1-017 GEN
Solar/Wind Harmer
0.391
276656WTG2_EQ
Solar/Wind Harmer
0.882
941731AE2-173 GEN
Solar/Wind Harmer
3.866
270462AD2-086
Solar/Wind Helper
1.688
270317AD1-130_GEN
Solar/Wind Helper
1.101
270287AF1-227 GEN3
Solar/Wind Helper
0.313
970615AG2-402 GEN
50/50
4.602
24729405KEY G3
50/50
6.868
24729505KEY G4
50/50
6.754
944961AF1-161 GEN
50/50
2.389
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.442
270505AE1-170 C O1
Solar/Wind Harmer
0.728
274888KELLY CRK;1U
Solar/Wind Harmer
8.779
970941AG2-585 GEN
Solar/Wind Harmer
0.541
971605AH1-302 GEN
Solar/Wind Harmer
6.341
276805AD2-038 GEN
Solar/Wind Harmer
7.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.67
276861AD2-134 GEN
Solar/Wind Harmer
2.505
274864CRW2-WTG
Solar/Wind Harmer
7.688
970569AG2-363 GEN
Solar/Wind Harmer
1.205
274858EASY ROAD;U2
Solar/Wind Harmer
6.231
276157O29GEN1
Solar/Wind Harmer
5.735
957751AF2-069 GEN
Solar/Wind Harmer
0.514
939741AE1-205 GEN
Solar/Wind Harmer
0.773
246938BC-WTG3
Solar/Wind Helper
5.433
246936BC-WTG1
Solar/Wind Helper
5.496
24639705ELKHART HY
50/50
0.15
270142AC1-141 CT1_
50/50
2.02
270143AC1-141 CT2_
50/50
2.02
963791AG1-232 GEN
Solar/Wind Harmer
0.972
270246TR4_N_V150
Solar/Wind Harmer
1.186
24695305TIMB G C
Solar/Wind Harmer
9.919
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.422
965031AG1-367 GEN
Solar/Wind Harmer
0.414
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
0.401
961011AF2-392 GEN
Solar/Wind Harmer
12.249
270227U2-072_GEN3
Solar/Wind Helper
0.133
270228U2-072_GEN4
Solar/Wind Helper
0.133
276820AF1-078_GEN
Solar/Wind Helper
0.141
960851AF2-376 GEN
50/50
2.119
965021AG1-366 GEN
Solar/Wind Harmer
4.602
958861AF2-177 GEN
Solar/Wind Harmer
15.941
945371AF1-202 GEN
Solar/Wind Harmer
7.519
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.242
270594AE1-207 GEN
Solar/Wind Harmer
0.66
270032AE2-172
Solar/Wind Harmer
3.298
971997AH1-543 GEN
Solar/Wind Harmer
0.645
276863AD2-134 GEN
Solar/Wind Harmer
2.505
274863CRW1-WTG
Solar/Wind Harmer
7.688
276889AE2-281 GEN
Solar/Wind Harmer
2.603
24691005MDL-2G C
Solar/Wind Harmer
5.104
274856ECOGROVE ;U1
Solar/Wind Harmer
4.705
971549AH1-272 GEN
Solar/Wind Harmer
0.738
276158O29GEN2
Solar/Wind Harmer
5.735
276708O09 GEN2
Solar/Wind Harmer
4.827
246937BC-WTG2
Solar/Wind Helper
5.496
270485AE1-090_GEN
Solar/Wind Helper
0.147
24653605MOTTVILLE
50/50
0.003
270100X2-052 CT1
50/50
1.18
24307105BERRINSP G
50/50
0.017
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.888
945111AF1-176 GEN
Solar/Wind Harmer
4.84
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.472
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.926
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.24
970825AG2-519 GEN
Solar/Wind Harmer
0.448
970825AG2-519 GEN
Solar/Wind Harmer
1.72
970571AG2-364 GEN
Solar/Wind Harmer
0.803
971681AH1-341 GEN
Solar/Wind Harmer
0.599
938861AE1-114 GEN
Solar/Wind Harmer
9.335
276603SUBLETTE C
Solar/Wind Harmer
1.356
253378AE2-206_GEN
Solar/Wind Helper
0.312
971599AH1-298 GEN
50/50
10.386
960861AF2-377 GEN
50/50
2.413
24729305KEY G2
50/50
6.868
970611AG2-400 GEN
Solar/Wind Harmer
1.15
270071AF1-092 GEN
Solar/Wind Harmer
0.944
970321AG2-212 GEN
Solar/Wind Harmer
0.894
270005AE1-210 C O1
Solar/Wind Harmer
6.463
276602WESTBROOK C
Solar/Wind Harmer
2.858
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.594
276645AC1-214 GEN1
Solar/Wind Harmer
1.683
24387305FR-4G C
Solar/Wind Harmer
4.568
24386605FR-22G C
Solar/Wind Harmer
3.045
24387005FR-3G C
Solar/Wind Harmer
3.015
942111AE2-223 GEN
Solar/Wind Harmer
9.047
960841AF2-375 GEN
Solar/Wind Helper
0.529
24641605TWIN BRNCH
50/50
0.015
24643105BUCHANAN
50/50
0.011
24344005CKG1
50/50
7.905
944531AF1-118 GEN
Solar/Wind Harmer
2.062
274887GEN-1.85
Solar/Wind Harmer
8.065
970707AG2-453 GEN
Solar/Wind Harmer
1.203
970833AG2-524 GEN
Solar/Wind Harmer
3.74
958481AF2-142 GEN
Solar/Wind Harmer
0.629
276868AE1-113 GEN
Solar/Wind Harmer
13.822
971675AH1-338 GEN
Solar/Wind Harmer
0.735
960791AF2-370 GEN
Solar/Wind Harmer
1.628
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.395
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.371
270224U2-072_GEN2
Solar/Wind Helper
0.133
270391AF1-285 GEN3
Solar/Wind Helper
0.267
241847AF2-150_GEN
Solar/Wind Helper
0.239
270102X2-052 ST
50/50
1.277
970901AG2-562 GEN
50/50
4.84
960971AF2-388 GEN
Solar/Wind Harmer
16.413
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
0.97
961051AF2-396 GEN
Solar/Wind Harmer
7.761
270599AE1-208 GEN
Solar/Wind Harmer
0.373
970245AG2-165 GEN
Solar/Wind Harmer
0.894
972231SS25-0005
Solar/Wind Harmer
0.71
274862TOP CROP ;2U
Solar/Wind Harmer
6.862
970921AG2-575 GEN
Solar/Wind Harmer
0.413
970921AG2-575 GEN
Solar/Wind Harmer
1.652
274879MINONK ;1U
Solar/Wind Harmer
9.667
971411AH1-196 GEN
Solar/Wind Harmer
0.613
274855GSG-6 ;RU
Solar/Wind Harmer
5.182
24386405FR-21G C
Solar/Wind Harmer
3.045
942871AE2-306 GEN
Solar/Wind Helper
0.2
945641AF1-229 GEN
Solar/Wind Helper
0.422
270541AE2-072 C
Solar/Wind Helper
0.42
971617AH1-308 GEN
Solar/Wind Harmer
5.201
943021AE2-325 GEN
Solar/Wind Harmer
2.992
958011AF2-095 GEN
Solar/Wind Harmer
0.623
971573AH1-285 GEN
Solar/Wind Harmer
0.361
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.621
942991AE2-321 GEN
Solar/Wind Harmer
0.41
971333AH1-146 GEN
Solar/Wind Harmer
0.816
24697905MDL-4G C
Solar/Wind Harmer
3.365
970819AG2-516 GEN
Solar/Wind Harmer
0.483
964611AG1-324 GEN
Solar/Wind Harmer
0.357
270201AC2-176 GEN
Solar/Wind Harmer
6.697
274851PROVIDENC;RU
Solar/Wind Harmer
3.718
274878BISHOP HL;2U
Solar/Wind Harmer
4.523
24699105WLD G1 C
Solar/Wind Harmer
5.025
270499AE1-146 GEN
Solar/Wind Helper
0.511
24729205KEY G1
50/50
6.754
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.936
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.261
270004AE1-209 GEN
Solar/Wind Harmer
6.463
274872LEEDK;1U
Solar/Wind Harmer
0.181
270180AB1-006 GEN1
Solar/Wind Harmer
9.562
24791305MDL-5G
Solar/Wind Harmer
3.365
959081AF2-199 GEN
Solar/Wind Harmer
0.406
971475AH1-234 GEN
Solar/Wind Harmer
0.898
276646AC1-214 GEN2
Solar/Wind Harmer
1.683
24386205FR-12G C
Solar/Wind Harmer
3.179
276726Z2-087_GEN
Solar/Wind Harmer
10.052
972181SS23-001
Solar/Wind Harmer
0.444
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.311
970289AG2-191 GEN
Solar/Wind Harmer
0.079
24755605MDL-5G
Solar/Wind Harmer
3.365
959091AF2-200 GEN
Solar/Wind Harmer
0.811
946031AF1-268 GEN
Solar/Wind Harmer
0.329
274849CRESCENT ;1U
Solar/Wind Harmer
2.569
274877BISHOP HL;1U
Solar/Wind Harmer
4.523
270349AD2-093_GEN
Solar/Wind Helper
0.383
965651AG1-433 GEN
Solar/Wind Harmer
8.207
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.896
943121AE2-341 GEN
Solar/Wind Harmer
0.633
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.55
957471AF2-041 GEN
Solar/Wind Harmer
1.217
274848CAMPGROVE;RU
Solar/Wind Harmer
7.073
959341AF2-225 GEN
Solar/Wind Harmer
0.58
957201AF2-014 GEN
Solar/Wind Helper
3.911
270284AF1-227 GEN1
Solar/Wind Helper
0.847
270428AC2-015 C
Solar/Wind Helper
0.344
970521AG2-332 GEN
50/50
10.877
247521TR3_G114
Solar/Wind Harmer
8.771
276806AD2-047 C O1
Solar/Wind Harmer
13.32
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.573
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.5
971341AH1-150 GEN
Solar/Wind Harmer
0.811
270302AB2-170 GEN
Solar/Wind Helper
1.101
270231U2-072_GEN5
Solar/Wind Helper
0.133
270471AD2-092_GEN
Solar/Wind Helper
0.383
24344105CKG2
50/50
6.335
270101X2-052 CT2
50/50
1.18
959331AF2-224 GEN
Solar/Wind Harmer
1.15
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.09
276843GEN-1.7
Solar/Wind Harmer
0.714
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.948
276882AE2-255 GEN
Solar/Wind Harmer
4.361
960441AF2-335 GEN
Solar/Wind Harmer
0.407
270223U2-072_GEN1
Solar/Wind Helper
0.133
966831AG1-554 GEN
Solar/Wind Helper
0.265
274854TWINGROVE;U2
Solar/Wind Harmer
7.034
944201AF1-088_MTX
Adder
55.87
957141AF2-008_MTX
Adder
27.935
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.599
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.154
LGEELTFEXP_LGEE->PJM
CLTF
1.819
MECLTFEXP_MEC->PJM
CLTF
9.7
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.901
WECLTFEXP_WEC->PJM
CLTF
2.651
LAGNLTFEXP_LAGN->PJM
CLTF
5.747
AH1-155LTFEXP_AH1-155->PJM
LTF
0.251
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.505
NYPJM->LTFIMP_NY
CLTF
1.226
TVALTFEXP_TVA->PJM
CLTF
2.31
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.037

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.82 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2011.72
MW Contribution:2.11
Bus #Bus NameTypeMW Contribution
247620Y3-023
50/50
0.466
965041AG1-368 GEN
Solar/Wind Harmer
0.706
270191TR4_S_V150
Solar/Wind Harmer
6.54
965101AG1-375 GEN
Solar/Wind Harmer
0.511
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.373
971917AH1-482 GEN
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
970115AG2-085 GEN
Solar/Wind Harmer
0.163
276872AE1-163_GEN1
Solar/Wind Harmer
9.109
946581AF1-322 GEN
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.894
970517AG2-330 GEN
Solar/Wind Harmer
13.95
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.467
958821AF2-173 GEN
Solar/Wind Harmer
0.58
962781AG1-127 GEN
Solar/Wind Harmer
0.393
971335AH1-147 GEN
Solar/Wind Harmer
0.816
24697605MDL-3G C
Solar/Wind Harmer
5.096
270181AB1-006 GEN2
Solar/Wind Harmer
0.634
971171AH1-044 GEN
Solar/Wind Harmer
0.811
926823AC1-168 GEN
Solar/Wind Harmer
4.923
24385905FR-11G C
Solar/Wind Harmer
5.987
276782AC1-033 GEN
Solar/Wind Harmer
5.11
24725505WLD G2 C
Solar/Wind Harmer
5.056
946321AF1-296 GEN
Solar/Wind Harmer
11.381
960611AF2-352 GEN
Solar/Wind Harmer
1.153
970583AG2-370 GEN
50/50
2.823
970031AG2-029 GEN
Solar/Wind Harmer
2.112
970615AG2-402 GEN
50/50
4.602
24729405KEY G3
50/50
6.868
24729505KEY G4
50/50
6.754
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.442
270505AE1-170 C O1
Solar/Wind Harmer
0.728
274888KELLY CRK;1U
Solar/Wind Harmer
8.779
970941AG2-585 GEN
Solar/Wind Harmer
0.541
971605AH1-302 GEN
Solar/Wind Harmer
6.341
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
0.972
270246TR4_N_V150
Solar/Wind Harmer
1.186
24695305TIMB G C
Solar/Wind Harmer
9.919
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.422
965031AG1-367 GEN
Solar/Wind Harmer
0.414
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
0.401
961011AF2-392 GEN
Solar/Wind Harmer
12.249
270227U2-072_GEN3
Solar/Wind Helper
0.133
270228U2-072_GEN4
Solar/Wind Helper
0.133
276820AF1-078_GEN
Solar/Wind Helper
0.141
276805AD2-038 GEN
Solar/Wind Harmer
7.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.67
276861AD2-134 GEN
Solar/Wind Harmer
2.505
274864CRW2-WTG
Solar/Wind Harmer
7.688
970569AG2-363 GEN
Solar/Wind Harmer
1.205
274858EASY ROAD;U2
Solar/Wind Harmer
6.231
276157O29GEN1
Solar/Wind Harmer
5.735
957751AF2-069 GEN
Solar/Wind Harmer
0.514
939741AE1-205 GEN
Solar/Wind Harmer
0.773
246938BC-WTG3
Solar/Wind Helper
5.433
246936BC-WTG1
Solar/Wind Helper
5.496
960851AF2-376 GEN
50/50
2.119
965021AG1-366 GEN
Solar/Wind Harmer
4.602
958861AF2-177 GEN
Solar/Wind Harmer
15.941
945371AF1-202 GEN
Solar/Wind Harmer
7.519
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.242
270594AE1-207 GEN
Solar/Wind Harmer
0.66
270032AE2-172
Solar/Wind Harmer
3.298
971997AH1-543 GEN
Solar/Wind Harmer
0.645
276863AD2-134 GEN
Solar/Wind Harmer
2.505
274863CRW1-WTG
Solar/Wind Harmer
7.688
276889AE2-281 GEN
Solar/Wind Harmer
2.603
24691005MDL-2G C
Solar/Wind Harmer
5.104
274856ECOGROVE ;U1
Solar/Wind Harmer
4.705
971549AH1-272 GEN
Solar/Wind Harmer
0.738
276158O29GEN2
Solar/Wind Harmer
5.735
276708O09 GEN2
Solar/Wind Harmer
4.827
246937BC-WTG2
Solar/Wind Helper
5.496
270485AE1-090_GEN
Solar/Wind Helper
0.147
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.888
945111AF1-176 GEN
Solar/Wind Harmer
4.84
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.472
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.926
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.24
970825AG2-519 GEN
Solar/Wind Harmer
0.448
970825AG2-519 GEN
Solar/Wind Harmer
1.72
970571AG2-364 GEN
Solar/Wind Harmer
0.803
971681AH1-341 GEN
Solar/Wind Harmer
0.599
938861AE1-114 GEN
Solar/Wind Harmer
9.335
276603SUBLETTE C
Solar/Wind Harmer
1.356
253378AE2-206_GEN
Solar/Wind Helper
0.312
971599AH1-298 GEN
50/50
10.386
960861AF2-377 GEN
50/50
2.413
24729305KEY G2
50/50
6.868
970611AG2-400 GEN
Solar/Wind Harmer
1.15
270071AF1-092 GEN
Solar/Wind Harmer
0.944
970321AG2-212 GEN
Solar/Wind Harmer
0.894
270005AE1-210 C O1
Solar/Wind Harmer
6.463
276602WESTBROOK C
Solar/Wind Harmer
2.858
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.594
276645AC1-214 GEN1
Solar/Wind Harmer
1.683
24387305FR-4G C
Solar/Wind Harmer
4.568
24386605FR-22G C
Solar/Wind Harmer
3.045
24387005FR-3G C
Solar/Wind Harmer
3.015
942111AE2-223 GEN
Solar/Wind Harmer
9.047
960841AF2-375 GEN
Solar/Wind Helper
0.529
270247TR4_N_V136
Solar/Wind Harmer
1.186
965051AG1-369 GEN
Solar/Wind Harmer
0.301
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.088
939401AE1-172 GEN
Solar/Wind Harmer
16.42
276876AE1-163_GEN2
Solar/Wind Harmer
9.109
274857EASY ROAD;U1
Solar/Wind Harmer
6.231
961761AG1-017 GEN
Solar/Wind Harmer
0.391
276656WTG2_EQ
Solar/Wind Harmer
0.882
941731AE2-173 GEN
Solar/Wind Harmer
3.866
270462AD2-086
Solar/Wind Helper
1.688
270317AD1-130_GEN
Solar/Wind Helper
1.101
270287AF1-227 GEN3
Solar/Wind Helper
0.313
24641605TWIN BRNCH
50/50
0.015
944531AF1-118 GEN
Solar/Wind Harmer
2.062
274887GEN-1.85
Solar/Wind Harmer
8.065
970707AG2-453 GEN
Solar/Wind Harmer
1.203
970833AG2-524 GEN
Solar/Wind Harmer
3.74
958481AF2-142 GEN
Solar/Wind Harmer
0.629
276868AE1-113 GEN
Solar/Wind Harmer
13.822
971675AH1-338 GEN
Solar/Wind Harmer
0.735
960791AF2-370 GEN
Solar/Wind Harmer
1.628
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.395
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.371
270224U2-072_GEN2
Solar/Wind Helper
0.133
270391AF1-285 GEN3
Solar/Wind Helper
0.267
241847AF2-150_GEN
Solar/Wind Helper
0.239
24690905MDL-1G C
Solar/Wind Harmer
10.701
971067AG2-660 GEN
Solar/Wind Harmer
1.622
276741O09 GEN1
Solar/Wind Harmer
4.827
276655WTG1_EQ
Solar/Wind Harmer
6.657
270578AF1-285 GEN2
Solar/Wind Helper
0.267
247522W1-056 GEN
Solar/Wind Helper
1.806
270286AF1-227 GEN2
Solar/Wind Helper
0.313
961961AG1-039 GEN
Solar/Wind Helper
0.152
241960AC2-195 GEN
Solar/Wind Helper
0.26
971617AH1-308 GEN
Solar/Wind Harmer
5.201
943021AE2-325 GEN
Solar/Wind Harmer
2.992
958011AF2-095 GEN
Solar/Wind Harmer
0.623
971573AH1-285 GEN
Solar/Wind Harmer
0.361
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.621
942991AE2-321 GEN
Solar/Wind Harmer
0.41
971333AH1-146 GEN
Solar/Wind Harmer
0.816
24697905MDL-4G C
Solar/Wind Harmer
3.365
970819AG2-516 GEN
Solar/Wind Harmer
0.483
964611AG1-324 GEN
Solar/Wind Harmer
0.357
270201AC2-176 GEN
Solar/Wind Harmer
6.697
274851PROVIDENC;RU
Solar/Wind Harmer
3.718
274878BISHOP HL;2U
Solar/Wind Harmer
4.523
24699105WLD G1 C
Solar/Wind Harmer
5.025
270499AE1-146 GEN
Solar/Wind Helper
0.511
24729205KEY G1
50/50
6.754
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.936
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.261
270004AE1-209 GEN
Solar/Wind Harmer
6.463
274872LEEDK;1U
Solar/Wind Harmer
0.181
270180AB1-006 GEN1
Solar/Wind Harmer
9.562
24791305MDL-5G
Solar/Wind Harmer
3.365
959081AF2-199 GEN
Solar/Wind Harmer
0.406
971475AH1-234 GEN
Solar/Wind Harmer
0.898
276646AC1-214 GEN2
Solar/Wind Harmer
1.683
24386205FR-12G C
Solar/Wind Harmer
3.179
276726Z2-087_GEN
Solar/Wind Harmer
10.052
972181SS23-001
Solar/Wind Harmer
0.444
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.311
970289AG2-191 GEN
Solar/Wind Harmer
0.079
24755605MDL-5G
Solar/Wind Harmer
3.365
959091AF2-200 GEN
Solar/Wind Harmer
0.811
946031AF1-268 GEN
Solar/Wind Harmer
0.329
274849CRESCENT ;1U
Solar/Wind Harmer
2.569
274877BISHOP HL;1U
Solar/Wind Harmer
4.523
270349AD2-093_GEN
Solar/Wind Helper
0.383
965651AG1-433 GEN
Solar/Wind Harmer
8.207
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.896
943121AE2-341 GEN
Solar/Wind Harmer
0.633
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.55
957471AF2-041 GEN
Solar/Wind Harmer
1.217
274848CAMPGROVE;RU
Solar/Wind Harmer
7.073
959341AF2-225 GEN
Solar/Wind Harmer
0.58
957201AF2-014 GEN
Solar/Wind Helper
3.911
270284AF1-227 GEN1
Solar/Wind Helper
0.847
270428AC2-015 C
Solar/Wind Helper
0.344
970521AG2-332 GEN
50/50
10.877
247521TR3_G114
Solar/Wind Harmer
8.771
276806AD2-047 C O1
Solar/Wind Harmer
13.32
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.573
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.5
971341AH1-150 GEN
Solar/Wind Harmer
0.811
270302AB2-170 GEN
Solar/Wind Helper
1.101
270231U2-072_GEN5
Solar/Wind Helper
0.133
270471AD2-092_GEN
Solar/Wind Helper
0.383
960971AF2-388 GEN
Solar/Wind Harmer
16.413
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
0.97
961051AF2-396 GEN
Solar/Wind Harmer
7.761
270599AE1-208 GEN
Solar/Wind Harmer
0.373
970245AG2-165 GEN
Solar/Wind Harmer
0.894
972231SS25-0005
Solar/Wind Harmer
0.71
274862TOP CROP ;2U
Solar/Wind Harmer
6.862
970921AG2-575 GEN
Solar/Wind Harmer
0.413
970921AG2-575 GEN
Solar/Wind Harmer
1.652
274879MINONK ;1U
Solar/Wind Harmer
9.667
971411AH1-196 GEN
Solar/Wind Harmer
0.613
274855GSG-6 ;RU
Solar/Wind Harmer
5.182
24386405FR-21G C
Solar/Wind Harmer
3.045
942871AE2-306 GEN
Solar/Wind Helper
0.2
945641AF1-229 GEN
Solar/Wind Helper
0.422
270541AE2-072 C
Solar/Wind Helper
0.42
959331AF2-224 GEN
Solar/Wind Harmer
1.15
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.09
276843GEN-1.7
Solar/Wind Harmer
0.714
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.948
276882AE2-255 GEN
Solar/Wind Harmer
4.361
960441AF2-335 GEN
Solar/Wind Harmer
0.407
270223U2-072_GEN1
Solar/Wind Helper
0.133
966831AG1-554 GEN
Solar/Wind Helper
0.265
274854TWINGROVE;U2
Solar/Wind Harmer
7.034
944201AF1-088_MTX
Adder
55.87
957141AF2-008_MTX
Adder
27.935
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.901
WECLTFEXP_WEC->PJM
CLTF
2.651
LAGNLTFEXP_LAGN->PJM
CLTF
5.747
AH1-155LTFEXP_AH1-155->PJM
LTF
0.251
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.505
NYPJM->LTFIMP_NY
CLTF
1.226
TVALTFEXP_TVA->PJM
CLTF
2.31
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.154
LGEELTFEXP_LGEE->PJM
CLTF
1.819
MECLTFEXP_MEC->PJM
CLTF
9.7
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.599
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.73 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2010.18
MW Contribution:2.05
Bus #Bus NameTypeMW Contribution
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.864
970517AG2-330 GEN
Solar/Wind Harmer
13.48
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
958821AF2-173 GEN
Solar/Wind Harmer
0.557
971335AH1-147 GEN
Solar/Wind Harmer
0.788
24697605MDL-3G C
Solar/Wind Harmer
4.918
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.942
270246TR4_N_V150
Solar/Wind Harmer
1.13
24695305TIMB G C
Solar/Wind Harmer
9.393
970615AG2-402 GEN
50/50
4.505
24729405KEY G3
50/50
6.653
24729505KEY G4
50/50
6.542
270043AE2-236 GEN
Solar/Wind Harmer
0.362
971771AH1-392 GEN
Solar/Wind Harmer
0.427
270505AE1-170 C O1
Solar/Wind Harmer
0.702
274888KELLY CRK;1U
Solar/Wind Harmer
8.479
970941AG2-585 GEN
Solar/Wind Harmer
0.522
971605AH1-302 GEN
Solar/Wind Harmer
6.121
276805AD2-038 GEN
Solar/Wind Harmer
7.241
274850MENDOTA H;RU
Solar/Wind Harmer
3.544
276861AD2-134 GEN
Solar/Wind Harmer
2.419
274864CRW2-WTG
Solar/Wind Harmer
7.421
970569AG2-363 GEN
Solar/Wind Harmer
1.163
274858EASY ROAD;U2
Solar/Wind Harmer
6.016
960851AF2-376 GEN
50/50
2.006
965021AG1-366 GEN
Solar/Wind Harmer
4.505
958861AF2-177 GEN
Solar/Wind Harmer
15.401
945371AF1-202 GEN
Solar/Wind Harmer
7.254
276893AG1-478 C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.199
957841AF2-078 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.634
270032AE2-172
Solar/Wind Harmer
3.17
971997AH1-543 GEN
Solar/Wind Harmer
0.623
276863AD2-134 GEN
Solar/Wind Harmer
2.419
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.857
945111AF1-176 GEN
Solar/Wind Harmer
4.67
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.456
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
42.42
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.232
970571AG2-364 GEN
Solar/Wind Harmer
0.776
970825AG2-519 GEN
Solar/Wind Harmer
0.43
970825AG2-519 GEN
Solar/Wind Harmer
1.65
971681AH1-341 GEN
Solar/Wind Harmer
0.578
938861AE1-114 GEN
Solar/Wind Harmer
9.013
276603SUBLETTE C
Solar/Wind Harmer
1.309
253378AE2-206_GEN
Solar/Wind Helper
0.35
971599AH1-298 GEN
50/50
10.098
960861AF2-377 GEN
50/50
2.301
24729305KEY G2
50/50
6.653
970611AG2-400 GEN
Solar/Wind Harmer
1.126
270071AF1-092 GEN
Solar/Wind Harmer
0.917
970321AG2-212 GEN
Solar/Wind Harmer
0.864
270005AE1-210 C O1
Solar/Wind Harmer
6.21
276602WESTBROOK C
Solar/Wind Harmer
2.759
276645AC1-214 GEN1
Solar/Wind Harmer
1.624
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.566
24387305FR-4G C
Solar/Wind Harmer
4.405
24386605FR-22G C
Solar/Wind Harmer
2.937
24387005FR-3G C
Solar/Wind Harmer
2.908
942111AE2-223 GEN
Solar/Wind Harmer
8.728
960841AF2-375 GEN
Solar/Wind Helper
0.566
970583AG2-370 GEN
50/50
2.718
970031AG2-029 GEN
Solar/Wind Harmer
2.053
270247TR4_N_V136
Solar/Wind Harmer
1.13
965051AG1-369 GEN
Solar/Wind Harmer
0.287
960591AF2-350 GEN
Solar/Wind Harmer
0.418
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
7.81
939401AE1-172 GEN
Solar/Wind Harmer
15.852
276876AE1-163_GEN2
Solar/Wind Harmer
8.794
274857EASY ROAD;U1
Solar/Wind Harmer
6.016
961761AG1-017 GEN
Solar/Wind Harmer
0.372
276656WTG2_EQ
Solar/Wind Harmer
0.85
941731AE2-173 GEN
Solar/Wind Harmer
3.73
270462AD2-086
Solar/Wind Helper
1.844
270317AD1-130_GEN
Solar/Wind Helper
1.203
270287AF1-227 GEN3
Solar/Wind Helper
0.376
944531AF1-118 GEN
Solar/Wind Harmer
1.998
274887GEN-1.85
Solar/Wind Harmer
7.789
970707AG2-453 GEN
Solar/Wind Harmer
1.162
970833AG2-524 GEN
Solar/Wind Harmer
3.611
958481AF2-142 GEN
Solar/Wind Harmer
0.607
276868AE1-113 GEN
Solar/Wind Harmer
13.346
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
960791AF2-370 GEN
Solar/Wind Harmer
1.562
276903AD2-071 C
Solar/Wind Harmer
0.38
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.04
270224U2-072_GEN2
Solar/Wind Helper
0.148
270391AF1-285 GEN3
Solar/Wind Helper
0.296
241847AF2-150_GEN
Solar/Wind Helper
0.259
247620Y3-023
50/50
0.451
965041AG1-368 GEN
Solar/Wind Harmer
0.679
270191TR4_S_V150
Solar/Wind Harmer
6.235
965101AG1-375 GEN
Solar/Wind Harmer
0.494
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.359
971917AH1-482 GEN
Solar/Wind Harmer
6.492
276691AA1-018 GEN1
Solar/Wind Harmer
0.436
276872AE1-163_GEN1
Solar/Wind Harmer
8.794
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.326
971067AG2-660 GEN
Solar/Wind Harmer
1.567
970115AG2-085 GEN
Solar/Wind Harmer
0.156
276741O09 GEN1
Solar/Wind Harmer
4.66
276655WTG1_EQ
Solar/Wind Harmer
6.423
971617AH1-308 GEN
Solar/Wind Harmer
4.999
943021AE2-325 GEN
Solar/Wind Harmer
2.884
958011AF2-095 GEN
Solar/Wind Harmer
0.601
971573AH1-285 GEN
Solar/Wind Harmer
0.349
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
942991AE2-321 GEN
Solar/Wind Harmer
0.396
971333AH1-146 GEN
Solar/Wind Harmer
0.788
24697905MDL-4G C
Solar/Wind Harmer
3.247
970819AG2-516 GEN
Solar/Wind Harmer
0.466
274851PROVIDENC;RU
Solar/Wind Harmer
3.588
964611AG1-324 GEN
Solar/Wind Harmer
0.34
270201AC2-176 GEN
Solar/Wind Harmer
6.374
274878BISHOP HL;2U
Solar/Wind Harmer
4.366
24699105WLD G1 C
Solar/Wind Harmer
4.824
965931AG1-462 GEN
Solar/Wind Harmer
0.935
270499AE1-146 GEN
Solar/Wind Helper
0.547
24729205KEY G1
50/50
6.542
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.904
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
7.977
270004AE1-209 GEN
Solar/Wind Harmer
6.21
274872LEEDK;1U
Solar/Wind Harmer
0.175
270180AB1-006 GEN1
Solar/Wind Harmer
9.228
24791305MDL-5G
Solar/Wind Harmer
3.247
959081AF2-199 GEN
Solar/Wind Harmer
0.392
971475AH1-234 GEN
Solar/Wind Harmer
0.867
276646AC1-214 GEN2
Solar/Wind Harmer
1.624
24386205FR-12G C
Solar/Wind Harmer
3.066
276726Z2-087_GEN
Solar/Wind Harmer
9.698
270578AF1-285 GEN2
Solar/Wind Helper
0.296
270286AF1-227 GEN2
Solar/Wind Helper
0.376
247522W1-056 GEN
Solar/Wind Helper
1.925
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.292
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.408
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.398
971343AH1-151 GEN
Solar/Wind Harmer
0.783
970169AG2-114 GEN
Solar/Wind Harmer
0.387
961011AF2-392 GEN
Solar/Wind Harmer
11.826
270227U2-072_GEN3
Solar/Wind Helper
0.148
270228U2-072_GEN4
Solar/Wind Helper
0.148
276820AF1-078_GEN
Solar/Wind Helper
0.158
972181SS23-001
Solar/Wind Harmer
0.429
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.267
970289AG2-191 GEN
Solar/Wind Harmer
0.076
24755605MDL-5G
Solar/Wind Harmer
3.247
959091AF2-200 GEN
Solar/Wind Harmer
0.783
946031AF1-268 GEN
Solar/Wind Harmer
0.315
274849CRESCENT ;1U
Solar/Wind Harmer
2.48
274877BISHOP HL;1U
Solar/Wind Harmer
4.366
270349AD2-093_GEN
Solar/Wind Helper
0.507
965651AG1-433 GEN
Solar/Wind Harmer
7.934
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.557
943121AE2-341 GEN
Solar/Wind Harmer
0.611
970291AG2-192 GEN
Solar/Wind Harmer
0.052
970289AG2-191 GEN
Solar/Wind Harmer
0.529
957471AF2-041 GEN
Solar/Wind Harmer
1.175
274848CAMPGROVE;RU
Solar/Wind Harmer
6.827
959341AF2-225 GEN
Solar/Wind Harmer
0.56
957201AF2-014 GEN
Solar/Wind Helper
3.962
270284AF1-227 GEN1
Solar/Wind Helper
1.019
270428AC2-015 C
Solar/Wind Helper
0.368
253383AE2-342_GEN
Solar/Wind Helper
0.101
970521AG2-332 GEN
50/50
10.52
247521TR3_G114
Solar/Wind Harmer
8.362
276806AD2-047 C O1
Solar/Wind Harmer
12.864
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.313
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.481
971341AH1-150 GEN
Solar/Wind Harmer
0.783
270302AB2-170 GEN
Solar/Wind Helper
1.203
270231U2-072_GEN5
Solar/Wind Helper
0.148
270471AD2-092_GEN
Solar/Wind Helper
0.507
960971AF2-388 GEN
Solar/Wind Harmer
15.869
970349AG2-230 GEN
Solar/Wind Harmer
0.705
971347AH1-153 GEN
Solar/Wind Harmer
0.705
961051AF2-396 GEN
Solar/Wind Harmer
0.936
961051AF2-396 GEN
Solar/Wind Harmer
7.484
270599AE1-208 GEN
Solar/Wind Harmer
0.359
970245AG2-165 GEN
Solar/Wind Harmer
0.864
972231SS25-0005
Solar/Wind Harmer
0.686
274862TOP CROP ;2U
Solar/Wind Harmer
6.626
970921AG2-575 GEN
Solar/Wind Harmer
0.399
970921AG2-575 GEN
Solar/Wind Harmer
1.595
274879MINONK ;1U
Solar/Wind Harmer
9.334
971411AH1-196 GEN
Solar/Wind Harmer
0.592
274855GSG-6 ;RU
Solar/Wind Harmer
5.004
24386405FR-21G C
Solar/Wind Harmer
2.937
942871AE2-306 GEN
Solar/Wind Helper
0.222
945641AF1-229 GEN
Solar/Wind Helper
0.452
270541AE2-072 C
Solar/Wind Helper
0.467
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
276157O29GEN1
Solar/Wind Harmer
5.536
957751AF2-069 GEN
Solar/Wind Harmer
0.496
939741AE1-205 GEN
Solar/Wind Harmer
0.746
246938BC-WTG3
Solar/Wind Helper
5.504
246936BC-WTG1
Solar/Wind Helper
5.567
971171AH1-044 GEN
Solar/Wind Harmer
0.783
926823AC1-168 GEN
Solar/Wind Harmer
4.753
24385905FR-11G C
Solar/Wind Harmer
5.774
276782AC1-033 GEN
Solar/Wind Harmer
4.932
24725505WLD G2 C
Solar/Wind Harmer
4.854
946321AF1-296 GEN
Solar/Wind Harmer
10.986
958581AF2-149 GEN
Solar/Wind Helper
0.21
960611AF2-352 GEN
Solar/Wind Harmer
0.98
959331AF2-224 GEN
Solar/Wind Harmer
1.126
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.913
276843GEN-1.7
Solar/Wind Harmer
0.69
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.537
276882AE2-255 GEN
Solar/Wind Harmer
4.21
960441AF2-335 GEN
Solar/Wind Harmer
0.39
270223U2-072_GEN1
Solar/Wind Helper
0.148
966831AG1-554 GEN
Solar/Wind Helper
0.282
274854TWINGROVE;U2
Solar/Wind Harmer
5.982
274863CRW1-WTG
Solar/Wind Harmer
7.421
276889AE2-281 GEN
Solar/Wind Harmer
2.513
24691005MDL-2G C
Solar/Wind Harmer
4.926
274856ECOGROVE ;U1
Solar/Wind Harmer
4.543
971549AH1-272 GEN
Solar/Wind Harmer
0.704
276158O29GEN2
Solar/Wind Harmer
5.536
276708O09 GEN2
Solar/Wind Harmer
4.66
246937BC-WTG2
Solar/Wind Helper
5.567
270485AE1-090_GEN
Solar/Wind Helper
0.16
944201AF1-088_MTX
Adder
53.676
957141AF2-008_MTX
Adder
26.838
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.712
TVALTFEXP_TVA->PJM
CLTF
2.237
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.26
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.277
LGEELTFEXP_LGEE->PJM
CLTF
1.703
LAGNLTFEXP_LAGN->PJM
CLTF
5.561
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.562
WECLTFEXP_WEC->PJM
CLTF
2.559
SIGELTFEXP_SIGE->PJM
CLTF
0.191
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.912
NYPJM->LTFIMP_NY
CLTF
1.178
MECLTFEXP_MEC->PJM
CLTF
9.361
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.0 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5655.61
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
270100X2-052 CT1
50/50
3.356
274770LINCOLN ;1U
50/50
19.802
274771LINCOLN ;2U
50/50
19.802
971769AH1-391 GEN
Solar/Wind Harmer
1.305
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.286
945111AF1-176 GEN
Solar/Wind Harmer
12.464
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
128.268
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.701
970571AG2-364 GEN
Solar/Wind Harmer
2.343
971681AH1-341 GEN
Solar/Wind Harmer
1.746
971599AH1-298 GEN
50/50
20.938
970321AG2-212 GEN
Solar/Wind Harmer
2.856
270071AF1-092 GEN
Solar/Wind Harmer
1.913
970333AG2-219 GEN
Solar/Wind Harmer
4.04
276602WESTBROOK C
Solar/Wind Harmer
8.341
24387305FR-4G C
Solar/Wind Harmer
13.565
24386605FR-22G C
Solar/Wind Harmer
9.043
24387005FR-3G C
Solar/Wind Harmer
8.953
276645AC1-214 GEN1
Solar/Wind Harmer
4.919
942111AE2-223 GEN
Solar/Wind Harmer
26.656
970611AG2-400 GEN
Solar/Wind Harmer
1.115
274775LINCOLN ;6U
50/50
19.802
960591AF2-350 GEN
Solar/Wind Harmer
1.255
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
970519AG2-331 GEN
Solar/Wind Harmer
38.197
970031AG2-029 GEN
Solar/Wind Harmer
3.667
276694AA1-018 GEN2
Solar/Wind Harmer
23.507
939401AE1-172 GEN
Solar/Wind Harmer
48.146
276876AE1-163_GEN2
Solar/Wind Harmer
26.538
274857EASY ROAD;U1
Solar/Wind Harmer
18.167
276656WTG2_EQ
Solar/Wind Harmer
2.597
941731AE2-173 GEN
Solar/Wind Harmer
11.391
24344005CKG1
50/50
22.413
24641605TWIN BRNCH
50/50
0.039
24643105BUCHANAN
50/50
0.028
970707AG2-453 GEN
Solar/Wind Harmer
3.529
274887GEN-1.85
Solar/Wind Harmer
23.402
970833AG2-524 GEN
Solar/Wind Harmer
10.921
970699AG2-449 GEN
Solar/Wind Harmer
1.469
958481AF2-142 GEN
Solar/Wind Harmer
1.827
970781AG2-491 GEN
Solar/Wind Harmer
1.199
276868AE1-113 GEN
Solar/Wind Harmer
40.278
971675AH1-338 GEN
Solar/Wind Harmer
2.144
944531AF1-118 GEN
Solar/Wind Harmer
4.133
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
27.647
943021AE2-325 GEN
Solar/Wind Harmer
7.995
958011AF2-095 GEN
Solar/Wind Harmer
1.807
971573AH1-285 GEN
Solar/Wind Harmer
1.055
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
1.806
24697905MDL-4G C
Solar/Wind Harmer
9.928
942991AE2-321 GEN
Solar/Wind Harmer
1.197
971333AH1-146 GEN
Solar/Wind Harmer
2.381
970819AG2-516 GEN
Solar/Wind Harmer
1.407
274851PROVIDENC;RU
Solar/Wind Harmer
10.865
274878BISHOP HL;2U
Solar/Wind Harmer
13.215
965091AG1-374 GEN
Solar/Wind Harmer
3.362
965931AG1-462 GEN
Solar/Wind Harmer
2.821
274776LINCOLN ;7U
50/50
19.802
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.694
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
24.007
274872LEEDK;1U
Solar/Wind Harmer
0.529
270180AB1-006 GEN1
Solar/Wind Harmer
28.214
24791305MDL-5G
Solar/Wind Harmer
9.928
959081AF2-199 GEN
Solar/Wind Harmer
1.183
971475AH1-234 GEN
Solar/Wind Harmer
2.618
24386205FR-12G C
Solar/Wind Harmer
9.441
276646AC1-214 GEN2
Solar/Wind Harmer
4.919
276726Z2-087_GEN
Solar/Wind Harmer
29.618
963741AG1-226 GEN
Solar/Wind Harmer
4.923
276764AC1-053 GEN2
Solar/Wind Harmer
9.884
270144AC1-141 ST1_
50/50
4.757
24642205MAYFLWER
50/50
1.656
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
19.542
276691AA1-018 GEN1
Solar/Wind Harmer
1.312
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
31.574
276872AE1-163_GEN1
Solar/Wind Harmer
26.538
971067AG2-660 GEN
Solar/Wind Harmer
4.734
276741O09 GEN1
Solar/Wind Harmer
14.08
276655WTG1_EQ
Solar/Wind Harmer
19.616
963841AG1-237 GEN
Solar/Wind Harmer
35.114
276686W4-005 GEN3
Solar/Wind Harmer
10.58
270142AC1-141 CT1_
50/50
5.371
270143AC1-141 CT2_
50/50
5.371
24639705ELKHART HY
50/50
0.358
965681AG1-436 GEN
Solar/Wind Harmer
1.643
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.234
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.367
970169AG2-114 GEN
Solar/Wind Harmer
1.177
961011AF2-392 GEN
Solar/Wind Harmer
35.715
276785W4-005 GEN1
Solar/Wind Harmer
10.58
972207SS24-0001
Solar/Wind Harmer
3.857
972181SS23-001
Solar/Wind Harmer
1.268
270055AF2-134 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
9.928
959091AF2-200 GEN
Solar/Wind Harmer
2.367
274849CRESCENT ;1U
Solar/Wind Harmer
7.509
274877BISHOP HL;1U
Solar/Wind Harmer
13.215
270349AD2-093_GEN
Solar/Wind Helper
0.709
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
28.905
943121AE2-341 GEN
Solar/Wind Harmer
1.851
957471AF2-041 GEN
Solar/Wind Harmer
3.55
959341AF2-225 GEN
Solar/Wind Harmer
1.709
274848CAMPGROVE;RU
Solar/Wind Harmer
20.674
965651AG1-433 GEN
Solar/Wind Harmer
16.774
276849AB2-070 GEN2
Solar/Wind Harmer
8.046
276806AD2-047 C O1
Solar/Wind Harmer
38.651
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
22.119
971341AH1-150 GEN
Solar/Wind Harmer
2.367
276848AB2-070 GEN3
Solar/Wind Harmer
8.048
270471AD2-092_GEN
Solar/Wind Helper
0.709
270102X2-052 ST
50/50
3.632
970901AG2-562 GEN
50/50
13.762
274777LINCOLN ;8U
50/50
19.802
970245AG2-165 GEN
Solar/Wind Harmer
2.856
970349AG2-230 GEN
Solar/Wind Harmer
2.086
274772LINCOLN ;3U
50/50
19.802
274774LINCOLN ;5U
50/50
19.802
971771AH1-392 GEN
Solar/Wind Harmer
1.176
270505AE1-170 C O1
Solar/Wind Harmer
1.935
270043AE2-236 GEN
Solar/Wind Harmer
0.707
274888KELLY CRK;1U
Solar/Wind Harmer
25.475
970941AG2-585 GEN
Solar/Wind Harmer
1.569
971605AH1-302 GEN
Solar/Wind Harmer
18.534
970243AG2-164 GEN
Solar/Wind Harmer
3.306
276805AD2-038 GEN
Solar/Wind Harmer
21.819
274864CRW2-WTG
Solar/Wind Harmer
22.565
274850MENDOTA H;RU
Solar/Wind Harmer
10.714
276861AD2-134 GEN
Solar/Wind Harmer
7.313
970569AG2-363 GEN
Solar/Wind Harmer
3.514
274858EASY ROAD;U2
Solar/Wind Harmer
18.167
957751AF2-069 GEN
Solar/Wind Harmer
1.501
276157O29GEN1
Solar/Wind Harmer
16.728
939741AE1-205 GEN
Solar/Wind Harmer
2.278
970241AG2-163 GEN
Solar/Wind Harmer
2.735
276668AB2-070 GEN1
Solar/Wind Harmer
8.046
970513AG2-328 GEN
Solar/Wind Harmer
2.856
970517AG2-330 GEN
Solar/Wind Harmer
44.557
959141AF2-205 GEN
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.365
962781AG1-127 GEN
Solar/Wind Harmer
1.147
24697605MDL-3G C
Solar/Wind Harmer
15.036
270181AB1-006 GEN2
Solar/Wind Harmer
1.871
971335AH1-147 GEN
Solar/Wind Harmer
2.381
971171AH1-044 GEN
Solar/Wind Harmer
2.367
926823AC1-168 GEN
Solar/Wind Harmer
14.39
24385905FR-11G C
Solar/Wind Harmer
17.778
276782AC1-033 GEN
Solar/Wind Harmer
14.93
959611AF2-252 GEN
Solar/Wind Harmer
4.483
960611AF2-352 GEN
Solar/Wind Harmer
4.483
946321AF1-296 GEN
Solar/Wind Harmer
33.152
971347AH1-153 GEN
Solar/Wind Harmer
2.086
961051AF2-396 GEN
Solar/Wind Harmer
2.556
961051AF2-396 GEN
Solar/Wind Harmer
20.451
972231SS25-0005
Solar/Wind Harmer
2.028
274862TOP CROP ;2U
Solar/Wind Harmer
19.941
970921AG2-575 GEN
Solar/Wind Harmer
1.206
970921AG2-575 GEN
Solar/Wind Harmer
4.823
274879MINONK ;1U
Solar/Wind Harmer
28.171
971411AH1-196 GEN
Solar/Wind Harmer
1.787
274855GSG-6 ;RU
Solar/Wind Harmer
15.127
24386405FR-21G C
Solar/Wind Harmer
9.043
960971AF2-388 GEN
Solar/Wind Harmer
33.549
270054AF2-122 C O1
Solar/Wind Helper
0.54
276763AC1-053 GEN1
Solar/Wind Harmer
9.884
24344105CKG2
50/50
19.281
270101X2-052 CT2
50/50
3.356
965791AG1-447 GEN
Solar/Wind Harmer
14.461
276843GEN-1.7
Solar/Wind Harmer
2.073
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
34.888
276882AE2-255 GEN
Solar/Wind Harmer
12.707
274854TWINGROVE;U2
Solar/Wind Harmer
27.356
959331AF2-224 GEN
Solar/Wind Harmer
1.115
944541AF1-119 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
50/50
19.802
276893AG1-478 C
Solar/Wind Harmer
-0.001
970239AG2-162 GEN
Solar/Wind Harmer
1.408
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
3.627
24691005MDL-2G C
Solar/Wind Harmer
15.061
971997AH1-543 GEN
Solar/Wind Harmer
1.886
274863CRW1-WTG
Solar/Wind Harmer
22.565
276863AD2-134 GEN
Solar/Wind Harmer
7.313
276889AE2-281 GEN
Solar/Wind Harmer
7.582
274856ECOGROVE ;U1
Solar/Wind Harmer
13.719
971549AH1-272 GEN
Solar/Wind Harmer
2.146
276158O29GEN2
Solar/Wind Harmer
16.728
276708O09 GEN2
Solar/Wind Harmer
14.08
965021AG1-366 GEN
Solar/Wind Harmer
4.46
274880W4-005 GEN4
Solar/Wind Harmer
10.58
971993AH1-541 GEN
Solar/Wind Harmer
0.983
938861AE1-114 GEN
Solar/Wind Harmer
27.221
276603SUBLETTE C
Solar/Wind Harmer
3.953
965011AG1-365 GEN
Solar/Wind Harmer
1.115
972175AH1-670 GEN
Solar/Wind Harmer
42.535
276174W4-005 GEN2
Solar/Wind Harmer
10.58
944201AF1-088_MTX
Adder
195.89
957141AF2-008_MTX
Adder
97.945
CBM West 2LTFEXP_CBM-W2->PJM
CBM
140.353
WECLTFEXP_WEC->PJM
CLTF
7.718
MECLTFEXP_MEC->PJM
CLTF
28.039
AG2-052LTFEXP_AG2-052->PJM
LTF
0.481
NYPJM->LTFIMP_NY
CLTF
3.498
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.601
SIGELTFEXP_SIGE->PJM
CLTF
0.546
CBM West 1LTFEXP_CBM-W1->PJM
CBM
237.091
LGEELTFEXP_LGEE->PJM
CLTF
4.156
TVALTFEXP_TVA->PJM
CLTF
5.396
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
50.705
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.703
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.329
LAGNLTFEXP_LAGN->PJM
CLTF
14.593
AH1-155LTFEXP_AH1-155->PJM
LTF
0.721

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.24 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5171.46
MW Contribution:3.45
Bus #Bus NameTypeMW Contribution
972207SS24-0001
Solar/Wind Harmer
3.572
972181SS23-001
Solar/Wind Harmer
1.173
270055AF2-134 C O1
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
2.19
24755605MDL-5G
Solar/Wind Harmer
8.873
274849CRESCENT ;1U
Solar/Wind Harmer
6.934
274877BISHOP HL;1U
Solar/Wind Harmer
12.205
270349AD2-093_GEN
Solar/Wind Helper
0.7
970521AG2-332 GEN
50/50
23.771
276806AD2-047 C O1
Solar/Wind Harmer
35.756
274847GR RIDGE ;BU
Solar/Wind Harmer
20.461
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.19
247642Z2-115 C
Solar/Wind Harmer
-0.001
276848AB2-070 GEN3
Solar/Wind Harmer
7.37
270471AD2-092_GEN
Solar/Wind Helper
0.7
274772LINCOLN ;3U
50/50
18.334
274774LINCOLN ;5U
50/50
18.334
270043AE2-236 GEN
Solar/Wind Harmer
0.672
971771AH1-392 GEN
Solar/Wind Harmer
1.094
270505AE1-170 C O1
Solar/Wind Harmer
1.802
274888KELLY CRK;1U
Solar/Wind Harmer
23.567
970941AG2-585 GEN
Solar/Wind Harmer
1.451
276805AD2-038 GEN
Solar/Wind Harmer
20.171
971605AH1-302 GEN
Solar/Wind Harmer
16.681
274850MENDOTA H;RU
Solar/Wind Harmer
9.914
276861AD2-134 GEN
Solar/Wind Harmer
6.767
274864CRW2-WTG
Solar/Wind Harmer
20.812
970569AG2-363 GEN
Solar/Wind Harmer
3.247
274858EASY ROAD;U2
Solar/Wind Harmer
16.811
276157O29GEN1
Solar/Wind Harmer
15.471
957751AF2-069 GEN
Solar/Wind Harmer
1.386
939741AE1-205 GEN
Solar/Wind Harmer
2.095
970241AG2-163 GEN
Solar/Wind Harmer
2.45
276668AB2-070 GEN1
Solar/Wind Harmer
7.368
970513AG2-328 GEN
Solar/Wind Harmer
2.593
970517AG2-330 GEN
Solar/Wind Harmer
40.453
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.263
959141AF2-205 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
1.061
971335AH1-147 GEN
Solar/Wind Harmer
2.203
971171AH1-044 GEN
Solar/Wind Harmer
2.19
926823AC1-168 GEN
Solar/Wind Harmer
13.291
24697605MDL-3G C
Solar/Wind Harmer
13.438
270181AB1-006 GEN2
Solar/Wind Harmer
1.672
276782AC1-033 GEN
Solar/Wind Harmer
13.789
24385905FR-11G C
Solar/Wind Harmer
15.873
946321AF1-296 GEN
Solar/Wind Harmer
30.676
959611AF2-252 GEN
Solar/Wind Harmer
4.119
960611AF2-352 GEN
Solar/Wind Harmer
4.119
945581AF1-223 GEN
Solar/Wind Harmer
0
270102X2-052 ST
50/50
3.361
970901AG2-562 GEN
50/50
12.734
274777LINCOLN ;8U
50/50
18.334
970245AG2-165 GEN
Solar/Wind Harmer
2.593
970349AG2-230 GEN
Solar/Wind Harmer
1.941
971347AH1-153 GEN
Solar/Wind Harmer
1.941
961051AF2-396 GEN
Solar/Wind Harmer
2.381
961051AF2-396 GEN
Solar/Wind Harmer
19.048
972231SS25-0005
Solar/Wind Harmer
1.876
274862TOP CROP ;2U
Solar/Wind Harmer
18.439
970921AG2-575 GEN
Solar/Wind Harmer
1.116
970921AG2-575 GEN
Solar/Wind Harmer
4.463
274879MINONK ;1U
Solar/Wind Harmer
26.041
971411AH1-196 GEN
Solar/Wind Harmer
1.654
274855GSG-6 ;RU
Solar/Wind Harmer
13.998
960971AF2-388 GEN
Solar/Wind Harmer
32.84
24386405FR-21G C
Solar/Wind Harmer
8.074
276763AC1-053 GEN1
Solar/Wind Harmer
5.055
270144AC1-141 ST1_
50/50
4.431
24642205MAYFLWER
50/50
1.54
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.692
276691AA1-018 GEN1
Solar/Wind Harmer
1.213
971067AG2-660 GEN
Solar/Wind Harmer
4.38
276872AE1-163_GEN1
Solar/Wind Harmer
24.524
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
28.218
276741O09 GEN1
Solar/Wind Harmer
13.022
276655WTG1_EQ
Solar/Wind Harmer
18.038
965101AG1-375 GEN
Solar/Wind Harmer
1.03
963841AG1-237 GEN
Solar/Wind Harmer
31.4
276686W4-005 GEN3
Solar/Wind Harmer
9.69
943021AE2-325 GEN
Solar/Wind Harmer
7.445
958011AF2-095 GEN
Solar/Wind Harmer
1.672
971573AH1-285 GEN
Solar/Wind Harmer
0.977
958491AF2-143 GEN
Solar/Wind Harmer
1.67
942991AE2-321 GEN
Solar/Wind Harmer
1.107
971333AH1-146 GEN
Solar/Wind Harmer
2.203
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.302
24697905MDL-4G C
Solar/Wind Harmer
8.873
274851PROVIDENC;RU
Solar/Wind Harmer
10.033
274878BISHOP HL;2U
Solar/Wind Harmer
12.205
965091AG1-374 GEN
Solar/Wind Harmer
3.089
965931AG1-462 GEN
Solar/Wind Harmer
2.61
270142AC1-141 CT1_
50/50
5.003
270143AC1-141 CT2_
50/50
5.003
24639705ELKHART HY
50/50
0.334
965681AG1-436 GEN
Solar/Wind Harmer
1.52
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.142
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.19
970169AG2-114 GEN
Solar/Wind Harmer
1.084
961011AF2-392 GEN
Solar/Wind Harmer
33.045
276785W4-005 GEN1
Solar/Wind Harmer
9.69
24344005CKG1
50/50
20.846
24641605TWIN BRNCH
50/50
0.036
24643105BUCHANAN
50/50
0.026
970707AG2-453 GEN
Solar/Wind Harmer
3.267
274887GEN-1.85
Solar/Wind Harmer
21.649
944531AF1-118 GEN
Solar/Wind Harmer
4.019
970833AG2-524 GEN
Solar/Wind Harmer
10.102
958481AF2-142 GEN
Solar/Wind Harmer
1.69
276868AE1-113 GEN
Solar/Wind Harmer
37.233
971675AH1-338 GEN
Solar/Wind Harmer
1.984
970781AG2-491 GEN
Solar/Wind Harmer
1.072
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
25.403
24344105CKG2
50/50
17.939
270101X2-052 CT2
50/50
3.105
965791AG1-447 GEN
Solar/Wind Harmer
13.376
276843GEN-1.7
Solar/Wind Harmer
1.918
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
32.286
276882AE2-255 GEN
Solar/Wind Harmer
11.746
959331AF2-224 GEN
Solar/Wind Harmer
1.065
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
25.135
274775LINCOLN ;6U
50/50
18.334
960591AF2-350 GEN
Solar/Wind Harmer
1.161
939351AE1-166 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.451
958381AF2-132 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
21.736
939401AE1-172 GEN
Solar/Wind Harmer
44.44
276876AE1-163_GEN2
Solar/Wind Harmer
24.524
274857EASY ROAD;U1
Solar/Wind Harmer
16.811
276656WTG2_EQ
Solar/Wind Harmer
2.388
941731AE2-173 GEN
Solar/Wind Harmer
10.475
274773LINCOLN ;4U
50/50
18.334
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.356
971997AH1-543 GEN
Solar/Wind Harmer
1.743
276863AD2-134 GEN
Solar/Wind Harmer
6.767
274863CRW1-WTG
Solar/Wind Harmer
20.812
276889AE2-281 GEN
Solar/Wind Harmer
7.007
957841AF2-078 GEN
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
12.696
971549AH1-272 GEN
Solar/Wind Harmer
2
24691005MDL-2G C
Solar/Wind Harmer
13.46
965021AG1-366 GEN
Solar/Wind Harmer
4.261
276158O29GEN2
Solar/Wind Harmer
15.471
276708O09 GEN2
Solar/Wind Harmer
13.022
958861AF2-177 GEN
Solar/Wind Harmer
32.122
945371AF1-202 GEN
Solar/Wind Harmer
15.376
274880W4-005 GEN4
Solar/Wind Harmer
9.69
971993AH1-541 GEN
Solar/Wind Harmer
0.9
270100X2-052 CT1
50/50
3.105
274770LINCOLN ;1U
50/50
18.334
274771LINCOLN ;2U
50/50
18.334
24653605MOTTVILLE
50/50
0.007
971769AH1-391 GEN
Solar/Wind Harmer
1.21
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.13
945111AF1-176 GEN
Solar/Wind Harmer
11.613
276897AD1-100 C
Solar/Wind Harmer
118.617
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.649
970571AG2-364 GEN
Solar/Wind Harmer
2.164
971681AH1-341 GEN
Solar/Wind Harmer
1.615
938861AE1-114 GEN
Solar/Wind Harmer
25.188
276603SUBLETTE C
Solar/Wind Harmer
3.658
965011AG1-365 GEN
Solar/Wind Harmer
1.065
972175AH1-670 GEN
Solar/Wind Harmer
39.016
276174W4-005 GEN2
Solar/Wind Harmer
9.69
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
26.738
943121AE2-341 GEN
Solar/Wind Harmer
1.714
957471AF2-041 GEN
Solar/Wind Harmer
3.285
965651AG1-433 GEN
Solar/Wind Harmer
16.42
274848CAMPGROVE;RU
Solar/Wind Harmer
19.088
959341AF2-225 GEN
Solar/Wind Harmer
1.571
276849AB2-070 GEN2
Solar/Wind Harmer
7.368
971599AH1-298 GEN
50/50
20.056
970321AG2-212 GEN
Solar/Wind Harmer
2.593
270071AF1-092 GEN
Solar/Wind Harmer
1.802
276602WESTBROOK C
Solar/Wind Harmer
7.719
970611AG2-400 GEN
Solar/Wind Harmer
1.065
276645AC1-214 GEN1
Solar/Wind Harmer
4.542
942111AE2-223 GEN
Solar/Wind Harmer
24.512
24387305FR-4G C
Solar/Wind Harmer
12.111
24386605FR-22G C
Solar/Wind Harmer
8.074
24387005FR-3G C
Solar/Wind Harmer
7.993
274776LINCOLN ;7U
50/50
18.334
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.463
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
22.199
274872LEEDK;1U
Solar/Wind Harmer
0.49
959081AF2-199 GEN
Solar/Wind Harmer
1.095
971475AH1-234 GEN
Solar/Wind Harmer
2.423
270180AB1-006 GEN1
Solar/Wind Harmer
25.216
24791305MDL-5G
Solar/Wind Harmer
8.873
276646AC1-214 GEN2
Solar/Wind Harmer
4.542
276726Z2-087_GEN
Solar/Wind Harmer
27.235
24386205FR-12G C
Solar/Wind Harmer
8.429
963741AG1-226 GEN
Solar/Wind Harmer
4.409
276764AC1-053 GEN2
Solar/Wind Harmer
5.055
944201AF1-088_MTX
Adder
164.341
957141AF2-008_MTX
Adder
82.17
CBM West 1LTFEXP_CBM-W1->PJM
CBM
221.335
LGEELTFEXP_LGEE->PJM
CLTF
5.67
TVALTFEXP_TVA->PJM
CLTF
5.42
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.769
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.252
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.132
LAGNLTFEXP_LAGN->PJM
CLTF
14.106
AH1-155LTFEXP_AH1-155->PJM
LTF
0.661
NYPJM->LTFIMP_NY
CLTF
3.333
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.48
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.208
WECLTFEXP_WEC->PJM
CLTF
7.144
MECLTFEXP_MEC->PJM
CLTF
26.01
AG2-052LTFEXP_AG2-052->PJM
LTF
0.441

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.76 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5098.14
MW Contribution:3.46
Bus #Bus NameTypeMW Contribution
970513AG2-328 GEN
Solar/Wind Harmer
2.599
270144AC1-141 ST1_
50/50
4.442
24642205MAYFLWER
50/50
1.544
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.74
276691AA1-018 GEN1
Solar/Wind Harmer
1.216
971067AG2-660 GEN
Solar/Wind Harmer
4.392
276872AE1-163_GEN1
Solar/Wind Harmer
24.592
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
28.298
276741O09 GEN1
Solar/Wind Harmer
13.059
276655WTG1_EQ
Solar/Wind Harmer
18.09
965101AG1-375 GEN
Solar/Wind Harmer
1.033
963841AG1-237 GEN
Solar/Wind Harmer
31.494
276686W4-005 GEN3
Solar/Wind Harmer
9.72
943021AE2-325 GEN
Solar/Wind Harmer
7.464
958011AF2-095 GEN
Solar/Wind Harmer
1.676
971573AH1-285 GEN
Solar/Wind Harmer
0.979
958491AF2-143 GEN
Solar/Wind Harmer
1.674
942991AE2-321 GEN
Solar/Wind Harmer
1.111
971333AH1-146 GEN
Solar/Wind Harmer
2.209
274772LINCOLN ;3U
50/50
18.381
274774LINCOLN ;5U
50/50
18.381
270043AE2-236 GEN
Solar/Wind Harmer
0.674
971771AH1-392 GEN
Solar/Wind Harmer
1.097
270505AE1-170 C O1
Solar/Wind Harmer
1.807
274888KELLY CRK;1U
Solar/Wind Harmer
23.628
970941AG2-585 GEN
Solar/Wind Harmer
1.455
276805AD2-038 GEN
Solar/Wind Harmer
20.225
971605AH1-302 GEN
Solar/Wind Harmer
16.727
274850MENDOTA H;RU
Solar/Wind Harmer
9.942
276861AD2-134 GEN
Solar/Wind Harmer
6.785
274864CRW2-WTG
Solar/Wind Harmer
20.869
970569AG2-363 GEN
Solar/Wind Harmer
3.256
270142AC1-141 CT1_
50/50
5.015
270143AC1-141 CT2_
50/50
5.015
24639705ELKHART HY
50/50
0.335
965681AG1-436 GEN
Solar/Wind Harmer
1.524
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.145
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.196
970169AG2-114 GEN
Solar/Wind Harmer
1.087
961011AF2-392 GEN
Solar/Wind Harmer
33.139
276785W4-005 GEN1
Solar/Wind Harmer
9.72
270102X2-052 ST
50/50
3.369
970901AG2-562 GEN
50/50
12.765
274777LINCOLN ;8U
50/50
18.381
970245AG2-165 GEN
Solar/Wind Harmer
2.599
970349AG2-230 GEN
Solar/Wind Harmer
1.946
971347AH1-153 GEN
Solar/Wind Harmer
1.946
961051AF2-396 GEN
Solar/Wind Harmer
2.387
961051AF2-396 GEN
Solar/Wind Harmer
19.097
972231SS25-0005
Solar/Wind Harmer
1.881
274862TOP CROP ;2U
Solar/Wind Harmer
18.489
970921AG2-575 GEN
Solar/Wind Harmer
1.119
970921AG2-575 GEN
Solar/Wind Harmer
4.476
274879MINONK ;1U
Solar/Wind Harmer
26.112
971411AH1-196 GEN
Solar/Wind Harmer
1.658
274855GSG-6 ;RU
Solar/Wind Harmer
14.037
960971AF2-388 GEN
Solar/Wind Harmer
32.934
24386405FR-21G C
Solar/Wind Harmer
8.098
276763AC1-053 GEN1
Solar/Wind Harmer
5.071
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.306
24697905MDL-4G C
Solar/Wind Harmer
8.898
274851PROVIDENC;RU
Solar/Wind Harmer
10.062
274878BISHOP HL;2U
Solar/Wind Harmer
12.24
965091AG1-374 GEN
Solar/Wind Harmer
3.098
965931AG1-462 GEN
Solar/Wind Harmer
2.618
24344105CKG2
50/50
17.979
270101X2-052 CT2
50/50
3.113
965791AG1-447 GEN
Solar/Wind Harmer
13.41
276843GEN-1.7
Solar/Wind Harmer
1.923
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
32.374
276882AE2-255 GEN
Solar/Wind Harmer
11.778
959331AF2-224 GEN
Solar/Wind Harmer
1.068
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
25.209
24344005CKG1
50/50
20.898
24641605TWIN BRNCH
50/50
0.036
24643105BUCHANAN
50/50
0.026
970707AG2-453 GEN
Solar/Wind Harmer
3.275
274887GEN-1.85
Solar/Wind Harmer
21.706
944531AF1-118 GEN
Solar/Wind Harmer
4.029
970833AG2-524 GEN
Solar/Wind Harmer
10.129
958481AF2-142 GEN
Solar/Wind Harmer
1.694
276868AE1-113 GEN
Solar/Wind Harmer
37.335
971675AH1-338 GEN
Solar/Wind Harmer
1.99
970781AG2-491 GEN
Solar/Wind Harmer
1.075
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
25.477
274775LINCOLN ;6U
50/50
18.381
960591AF2-350 GEN
Solar/Wind Harmer
1.164
939351AE1-166 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.46
958381AF2-132 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
21.795
939401AE1-172 GEN
Solar/Wind Harmer
44.561
276876AE1-163_GEN2
Solar/Wind Harmer
24.592
274857EASY ROAD;U1
Solar/Wind Harmer
16.859
276656WTG2_EQ
Solar/Wind Harmer
2.395
941731AE2-173 GEN
Solar/Wind Harmer
10.505
274773LINCOLN ;4U
50/50
18.381
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.365
971997AH1-543 GEN
Solar/Wind Harmer
1.748
276863AD2-134 GEN
Solar/Wind Harmer
6.785
970517AG2-330 GEN
Solar/Wind Harmer
40.548
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.266
959141AF2-205 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
1.064
971335AH1-147 GEN
Solar/Wind Harmer
2.209
971171AH1-044 GEN
Solar/Wind Harmer
2.196
926823AC1-168 GEN
Solar/Wind Harmer
13.329
24697605MDL-3G C
Solar/Wind Harmer
13.476
270181AB1-006 GEN2
Solar/Wind Harmer
1.676
276782AC1-033 GEN
Solar/Wind Harmer
13.828
24385905FR-11G C
Solar/Wind Harmer
15.919
946321AF1-296 GEN
Solar/Wind Harmer
30.766
959611AF2-252 GEN
Solar/Wind Harmer
4.131
960611AF2-352 GEN
Solar/Wind Harmer
4.131
945581AF1-223 GEN
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
3.113
274770LINCOLN ;1U
50/50
18.381
274771LINCOLN ;2U
50/50
18.381
24653605MOTTVILLE
50/50
0.007
971769AH1-391 GEN
Solar/Wind Harmer
1.213
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.136
945111AF1-176 GEN
Solar/Wind Harmer
11.643
276897AD1-100 C
Solar/Wind Harmer
118.927
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.65
970571AG2-364 GEN
Solar/Wind Harmer
2.17
971681AH1-341 GEN
Solar/Wind Harmer
1.62
938861AE1-114 GEN
Solar/Wind Harmer
25.259
276603SUBLETTE C
Solar/Wind Harmer
3.668
965011AG1-365 GEN
Solar/Wind Harmer
1.068
972175AH1-670 GEN
Solar/Wind Harmer
39.134
276174W4-005 GEN2
Solar/Wind Harmer
9.72
274863CRW1-WTG
Solar/Wind Harmer
20.869
276889AE2-281 GEN
Solar/Wind Harmer
7.026
957841AF2-078 GEN
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
12.731
971549AH1-272 GEN
Solar/Wind Harmer
2.005
24691005MDL-2G C
Solar/Wind Harmer
13.498
965021AG1-366 GEN
Solar/Wind Harmer
4.273
276158O29GEN2
Solar/Wind Harmer
15.515
276708O09 GEN2
Solar/Wind Harmer
13.059
958861AF2-177 GEN
Solar/Wind Harmer
32.216
945371AF1-202 GEN
Solar/Wind Harmer
15.423
274880W4-005 GEN4
Solar/Wind Harmer
9.72
971993AH1-541 GEN
Solar/Wind Harmer
0.903
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
26.808
943121AE2-341 GEN
Solar/Wind Harmer
1.718
957471AF2-041 GEN
Solar/Wind Harmer
3.294
965651AG1-433 GEN
Solar/Wind Harmer
16.467
274848CAMPGROVE;RU
Solar/Wind Harmer
19.143
959341AF2-225 GEN
Solar/Wind Harmer
1.576
276849AB2-070 GEN2
Solar/Wind Harmer
7.391
274858EASY ROAD;U2
Solar/Wind Harmer
16.859
276157O29GEN1
Solar/Wind Harmer
15.515
957751AF2-069 GEN
Solar/Wind Harmer
1.39
939741AE1-205 GEN
Solar/Wind Harmer
2.101
970241AG2-163 GEN
Solar/Wind Harmer
2.457
276668AB2-070 GEN1
Solar/Wind Harmer
7.391
971599AH1-298 GEN
50/50
20.101
970321AG2-212 GEN
Solar/Wind Harmer
2.599
270071AF1-092 GEN
Solar/Wind Harmer
1.806
276602WESTBROOK C
Solar/Wind Harmer
7.74
970611AG2-400 GEN
Solar/Wind Harmer
1.068
276645AC1-214 GEN1
Solar/Wind Harmer
4.555
942111AE2-223 GEN
Solar/Wind Harmer
24.582
24387305FR-4G C
Solar/Wind Harmer
12.146
24386605FR-22G C
Solar/Wind Harmer
8.098
24387005FR-3G C
Solar/Wind Harmer
8.017
274776LINCOLN ;7U
50/50
18.381
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.469
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
22.259
274872LEEDK;1U
Solar/Wind Harmer
0.491
959081AF2-199 GEN
Solar/Wind Harmer
1.098
971475AH1-234 GEN
Solar/Wind Harmer
2.43
270180AB1-006 GEN1
Solar/Wind Harmer
25.287
24791305MDL-5G
Solar/Wind Harmer
8.898
276646AC1-214 GEN2
Solar/Wind Harmer
4.555
276726Z2-087_GEN
Solar/Wind Harmer
27.314
24386205FR-12G C
Solar/Wind Harmer
8.454
963741AG1-226 GEN
Solar/Wind Harmer
4.423
276764AC1-053 GEN2
Solar/Wind Harmer
5.071
970521AG2-332 GEN
50/50
23.831
276806AD2-047 C O1
Solar/Wind Harmer
35.85
274847GR RIDGE ;BU
Solar/Wind Harmer
20.515
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.196
247642Z2-115 C
Solar/Wind Harmer
-0.001
276848AB2-070 GEN3
Solar/Wind Harmer
7.393
270471AD2-092_GEN
Solar/Wind Helper
0.697
972207SS24-0001
Solar/Wind Harmer
3.581
972181SS23-001
Solar/Wind Harmer
1.176
270055AF2-134 C O1
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
2.196
24755605MDL-5G
Solar/Wind Harmer
8.898
274849CRESCENT ;1U
Solar/Wind Harmer
6.954
274877BISHOP HL;1U
Solar/Wind Harmer
12.24
270349AD2-093_GEN
Solar/Wind Helper
0.697
944201AF1-088_MTX
Adder
164.946
957141AF2-008_MTX
Adder
82.473
NYPJM->LTFIMP_NY
CLTF
3.299
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.459
SIGELTFEXP_SIGE->PJM
CLTF
0.559
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.912
WECLTFEXP_WEC->PJM
CLTF
7.164
MECLTFEXP_MEC->PJM
CLTF
26.098
AG2-052LTFEXP_AG2-052->PJM
LTF
0.442
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.451
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.097
LAGNLTFEXP_LAGN->PJM
CLTF
14.212
AH1-155LTFEXP_AH1-155->PJM
LTF
0.663
CBM West 1LTFEXP_CBM-W1->PJM
CBM
222.098
LGEELTFEXP_LGEE->PJM
CLTF
5.706
TVALTFEXP_TVA->PJM
CLTF
5.473
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.769

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.76 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5098.11
MW Contribution:3.46
Bus #Bus NameTypeMW Contribution
270144AC1-141 ST1_
50/50
4.442
24642205MAYFLWER
50/50
1.544
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.74
276691AA1-018 GEN1
Solar/Wind Harmer
1.216
971067AG2-660 GEN
Solar/Wind Harmer
4.392
276872AE1-163_GEN1
Solar/Wind Harmer
24.592
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
28.298
276741O09 GEN1
Solar/Wind Harmer
13.059
276655WTG1_EQ
Solar/Wind Harmer
18.09
965101AG1-375 GEN
Solar/Wind Harmer
1.033
963841AG1-237 GEN
Solar/Wind Harmer
31.494
276686W4-005 GEN3
Solar/Wind Harmer
9.72
970513AG2-328 GEN
Solar/Wind Harmer
2.599
970517AG2-330 GEN
Solar/Wind Harmer
40.548
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.266
959141AF2-205 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
1.064
971335AH1-147 GEN
Solar/Wind Harmer
2.209
971171AH1-044 GEN
Solar/Wind Harmer
2.196
926823AC1-168 GEN
Solar/Wind Harmer
13.329
24697605MDL-3G C
Solar/Wind Harmer
13.476
270181AB1-006 GEN2
Solar/Wind Harmer
1.676
276782AC1-033 GEN
Solar/Wind Harmer
13.828
24385905FR-11G C
Solar/Wind Harmer
15.919
946321AF1-296 GEN
Solar/Wind Harmer
30.766
959611AF2-252 GEN
Solar/Wind Harmer
4.131
960611AF2-352 GEN
Solar/Wind Harmer
4.131
945581AF1-223 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
50/50
18.381
960591AF2-350 GEN
Solar/Wind Harmer
1.164
939351AE1-166 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.46
958381AF2-132 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
21.795
939401AE1-172 GEN
Solar/Wind Harmer
44.561
276876AE1-163_GEN2
Solar/Wind Harmer
24.592
274857EASY ROAD;U1
Solar/Wind Harmer
16.859
276656WTG2_EQ
Solar/Wind Harmer
2.395
941731AE2-173 GEN
Solar/Wind Harmer
10.505
274772LINCOLN ;3U
50/50
18.381
274774LINCOLN ;5U
50/50
18.381
270043AE2-236 GEN
Solar/Wind Harmer
0.674
971771AH1-392 GEN
Solar/Wind Harmer
1.097
270505AE1-170 C O1
Solar/Wind Harmer
1.807
274888KELLY CRK;1U
Solar/Wind Harmer
23.628
970941AG2-585 GEN
Solar/Wind Harmer
1.455
276805AD2-038 GEN
Solar/Wind Harmer
20.225
971605AH1-302 GEN
Solar/Wind Harmer
16.727
274850MENDOTA H;RU
Solar/Wind Harmer
9.942
276861AD2-134 GEN
Solar/Wind Harmer
6.785
274864CRW2-WTG
Solar/Wind Harmer
20.869
970569AG2-363 GEN
Solar/Wind Harmer
3.256
274858EASY ROAD;U2
Solar/Wind Harmer
16.859
276157O29GEN1
Solar/Wind Harmer
15.515
957751AF2-069 GEN
Solar/Wind Harmer
1.39
939741AE1-205 GEN
Solar/Wind Harmer
2.101
970241AG2-163 GEN
Solar/Wind Harmer
2.457
276668AB2-070 GEN1
Solar/Wind Harmer
7.391
270142AC1-141 CT1_
50/50
5.015
270143AC1-141 CT2_
50/50
5.015
24639705ELKHART HY
50/50
0.335
965681AG1-436 GEN
Solar/Wind Harmer
1.524
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.145
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.196
970169AG2-114 GEN
Solar/Wind Harmer
1.087
961011AF2-392 GEN
Solar/Wind Harmer
33.139
276785W4-005 GEN1
Solar/Wind Harmer
9.72
274773LINCOLN ;4U
50/50
18.381
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.365
971997AH1-543 GEN
Solar/Wind Harmer
1.748
276863AD2-134 GEN
Solar/Wind Harmer
6.785
274863CRW1-WTG
Solar/Wind Harmer
20.869
276889AE2-281 GEN
Solar/Wind Harmer
7.026
957841AF2-078 GEN
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
12.731
971549AH1-272 GEN
Solar/Wind Harmer
2.005
24691005MDL-2G C
Solar/Wind Harmer
13.498
965021AG1-366 GEN
Solar/Wind Harmer
4.273
276158O29GEN2
Solar/Wind Harmer
15.515
276708O09 GEN2
Solar/Wind Harmer
13.059
958861AF2-177 GEN
Solar/Wind Harmer
32.216
945371AF1-202 GEN
Solar/Wind Harmer
15.423
274880W4-005 GEN4
Solar/Wind Harmer
9.72
971993AH1-541 GEN
Solar/Wind Harmer
0.903
270100X2-052 CT1
50/50
3.113
274770LINCOLN ;1U
50/50
18.381
274771LINCOLN ;2U
50/50
18.381
24653605MOTTVILLE
50/50
0.007
971769AH1-391 GEN
Solar/Wind Harmer
1.213
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.136
945111AF1-176 GEN
Solar/Wind Harmer
11.643
276897AD1-100 C
Solar/Wind Harmer
118.927
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.65
970571AG2-364 GEN
Solar/Wind Harmer
2.17
971681AH1-341 GEN
Solar/Wind Harmer
1.62
938861AE1-114 GEN
Solar/Wind Harmer
25.259
276603SUBLETTE C
Solar/Wind Harmer
3.668
965011AG1-365 GEN
Solar/Wind Harmer
1.068
972175AH1-670 GEN
Solar/Wind Harmer
39.134
276174W4-005 GEN2
Solar/Wind Harmer
9.72
971599AH1-298 GEN
50/50
20.101
970321AG2-212 GEN
Solar/Wind Harmer
2.599
270071AF1-092 GEN
Solar/Wind Harmer
1.806
276602WESTBROOK C
Solar/Wind Harmer
7.74
970611AG2-400 GEN
Solar/Wind Harmer
1.068
276645AC1-214 GEN1
Solar/Wind Harmer
4.555
942111AE2-223 GEN
Solar/Wind Harmer
24.582
24387305FR-4G C
Solar/Wind Harmer
12.146
24386605FR-22G C
Solar/Wind Harmer
8.098
24387005FR-3G C
Solar/Wind Harmer
8.017
24344005CKG1
50/50
20.898
24641605TWIN BRNCH
50/50
0.036
24643105BUCHANAN
50/50
0.026
970707AG2-453 GEN
Solar/Wind Harmer
3.275
274887GEN-1.85
Solar/Wind Harmer
21.706
944531AF1-118 GEN
Solar/Wind Harmer
4.029
970833AG2-524 GEN
Solar/Wind Harmer
10.129
958481AF2-142 GEN
Solar/Wind Harmer
1.694
276868AE1-113 GEN
Solar/Wind Harmer
37.335
971675AH1-338 GEN
Solar/Wind Harmer
1.99
970781AG2-491 GEN
Solar/Wind Harmer
1.075
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
25.477
943021AE2-325 GEN
Solar/Wind Harmer
7.464
958011AF2-095 GEN
Solar/Wind Harmer
1.676
971573AH1-285 GEN
Solar/Wind Harmer
0.979
958491AF2-143 GEN
Solar/Wind Harmer
1.674
942991AE2-321 GEN
Solar/Wind Harmer
1.111
971333AH1-146 GEN
Solar/Wind Harmer
2.209
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.306
24697905MDL-4G C
Solar/Wind Harmer
8.898
274851PROVIDENC;RU
Solar/Wind Harmer
10.062
274878BISHOP HL;2U
Solar/Wind Harmer
12.24
965091AG1-374 GEN
Solar/Wind Harmer
3.098
965931AG1-462 GEN
Solar/Wind Harmer
2.618
274776LINCOLN ;7U
50/50
18.381
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.469
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
22.259
274872LEEDK;1U
Solar/Wind Harmer
0.491
959081AF2-199 GEN
Solar/Wind Harmer
1.098
971475AH1-234 GEN
Solar/Wind Harmer
2.43
270180AB1-006 GEN1
Solar/Wind Harmer
25.287
24791305MDL-5G
Solar/Wind Harmer
8.898
276646AC1-214 GEN2
Solar/Wind Harmer
4.555
276726Z2-087_GEN
Solar/Wind Harmer
27.314
24386205FR-12G C
Solar/Wind Harmer
8.454
963741AG1-226 GEN
Solar/Wind Harmer
4.423
276764AC1-053 GEN2
Solar/Wind Harmer
5.071
972207SS24-0001
Solar/Wind Harmer
3.581
972181SS23-001
Solar/Wind Harmer
1.176
270055AF2-134 C O1
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
2.196
24755605MDL-5G
Solar/Wind Harmer
8.898
274849CRESCENT ;1U
Solar/Wind Harmer
6.954
274877BISHOP HL;1U
Solar/Wind Harmer
12.24
270349AD2-093_GEN
Solar/Wind Helper
0.697
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
26.808
943121AE2-341 GEN
Solar/Wind Harmer
1.718
957471AF2-041 GEN
Solar/Wind Harmer
3.294
965651AG1-433 GEN
Solar/Wind Harmer
16.467
274848CAMPGROVE;RU
Solar/Wind Harmer
19.143
959341AF2-225 GEN
Solar/Wind Harmer
1.576
276849AB2-070 GEN2
Solar/Wind Harmer
7.391
970521AG2-332 GEN
50/50
23.831
276806AD2-047 C O1
Solar/Wind Harmer
35.85
274847GR RIDGE ;BU
Solar/Wind Harmer
20.515
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.196
247642Z2-115 C
Solar/Wind Harmer
-0.001
276848AB2-070 GEN3
Solar/Wind Harmer
7.393
270471AD2-092_GEN
Solar/Wind Helper
0.697
270102X2-052 ST
50/50
3.369
970901AG2-562 GEN
50/50
12.765
274777LINCOLN ;8U
50/50
18.381
970245AG2-165 GEN
Solar/Wind Harmer
2.599
970349AG2-230 GEN
Solar/Wind Harmer
1.946
971347AH1-153 GEN
Solar/Wind Harmer
1.946
961051AF2-396 GEN
Solar/Wind Harmer
2.387
961051AF2-396 GEN
Solar/Wind Harmer
19.097
972231SS25-0005
Solar/Wind Harmer
1.881
274862TOP CROP ;2U
Solar/Wind Harmer
18.489
970921AG2-575 GEN
Solar/Wind Harmer
1.119
970921AG2-575 GEN
Solar/Wind Harmer
4.476
274879MINONK ;1U
Solar/Wind Harmer
26.112
971411AH1-196 GEN
Solar/Wind Harmer
1.658
274855GSG-6 ;RU
Solar/Wind Harmer
14.037
960971AF2-388 GEN
Solar/Wind Harmer
32.934
24386405FR-21G C
Solar/Wind Harmer
8.098
276763AC1-053 GEN1
Solar/Wind Harmer
5.071
24344105CKG2
50/50
17.979
270101X2-052 CT2
50/50
3.113
965791AG1-447 GEN
Solar/Wind Harmer
13.41
276843GEN-1.7
Solar/Wind Harmer
1.923
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
32.374
276882AE2-255 GEN
Solar/Wind Harmer
11.778
959331AF2-224 GEN
Solar/Wind Harmer
1.068
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
25.209
944201AF1-088_MTX
Adder
164.946
957141AF2-008_MTX
Adder
82.473
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.451
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.097
LAGNLTFEXP_LAGN->PJM
CLTF
14.212
AH1-155LTFEXP_AH1-155->PJM
LTF
0.663
CBM West 1LTFEXP_CBM-W1->PJM
CBM
222.098
LGEELTFEXP_LGEE->PJM
CLTF
5.706
TVALTFEXP_TVA->PJM
CLTF
5.473
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.769
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.912
WECLTFEXP_WEC->PJM
CLTF
7.164
MECLTFEXP_MEC->PJM
CLTF
26.098
AG2-052LTFEXP_AG2-052->PJM
LTF
0.442
NYPJM->LTFIMP_NY
CLTF
3.299
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.459
SIGELTFEXP_SIGE->PJM
CLTF
0.559

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.41 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:4981.37
MW Contribution:3.68
Bus #Bus NameTypeMW Contribution
943021AE2-325 GEN
Solar/Wind Harmer
8.008
958011AF2-095 GEN
Solar/Wind Harmer
1.781
971573AH1-285 GEN
Solar/Wind Harmer
1.038
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
1.769
942991AE2-321 GEN
Solar/Wind Harmer
1.174
24344105CKG2
50/50
19.362
270101X2-052 CT2
50/50
3.348
965791AG1-447 GEN
Solar/Wind Harmer
14.413
276843GEN-1.7
Solar/Wind Harmer
2.043
24344005CKG1
50/50
22.459
24641605TWIN BRNCH
50/50
0.039
24643105BUCHANAN
50/50
0.028
970699AG2-449 GEN
Solar/Wind Harmer
1.59
970707AG2-453 GEN
Solar/Wind Harmer
3.479
274887GEN-1.85
Solar/Wind Harmer
23.06
970833AG2-524 GEN
Solar/Wind Harmer
10.74
958481AF2-142 GEN
Solar/Wind Harmer
1.793
944531AF1-118 GEN
Solar/Wind Harmer
4.156
276868AE1-113 GEN
Solar/Wind Harmer
39.421
970781AG2-491 GEN
Solar/Wind Harmer
1.172
971675AH1-338 GEN
Solar/Wind Harmer
2.102
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
26.481
970519AG2-331 GEN
Solar/Wind Harmer
41.339
958381AF2-132 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.237
939351AE1-166 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.677
276694AA1-018 GEN2
Solar/Wind Harmer
23.067
939401AE1-172 GEN
Solar/Wind Harmer
46.994
276876AE1-163_GEN2
Solar/Wind Harmer
25.923
274857EASY ROAD;U1
Solar/Wind Harmer
17.754
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
34.229
276882AE2-255 GEN
Solar/Wind Harmer
12.436
959331AF2-224 GEN
Solar/Wind Harmer
1.123
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
26.202
24697905MDL-4G C
Solar/Wind Harmer
9.707
971333AH1-146 GEN
Solar/Wind Harmer
2.334
970819AG2-516 GEN
Solar/Wind Harmer
1.377
274851PROVIDENC;RU
Solar/Wind Harmer
10.555
274878BISHOP HL;2U
Solar/Wind Harmer
12.834
965931AG1-462 GEN
Solar/Wind Harmer
2.743
965091AG1-374 GEN
Solar/Wind Harmer
3.22
270144AC1-141 ST1_
50/50
4.766
24642205MAYFLWER
50/50
1.656
962601AG1-109 GEN
50/50
6.392
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
19.33
276691AA1-018 GEN1
Solar/Wind Harmer
1.287
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
30.87
971067AG2-660 GEN
Solar/Wind Harmer
4.636
276872AE1-163_GEN1
Solar/Wind Harmer
25.923
276741O09 GEN1
Solar/Wind Harmer
13.724
276655WTG1_EQ
Solar/Wind Harmer
18.863
963841AG1-237 GEN
Solar/Wind Harmer
33.488
965101AG1-375 GEN
Solar/Wind Harmer
1.056
276686W4-005 GEN3
Solar/Wind Harmer
7.56
276656WTG2_EQ
Solar/Wind Harmer
2.498
941731AE2-173 GEN
Solar/Wind Harmer
10.954
970513AG2-328 GEN
Solar/Wind Harmer
2.888
970517AG2-330 GEN
Solar/Wind Harmer
45.053
270063AE2-323 C
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.342
962781AG1-127 GEN
Solar/Wind Harmer
1.125
24697605MDL-3G C
Solar/Wind Harmer
14.701
270181AB1-006 GEN2
Solar/Wind Harmer
1.829
971335AH1-147 GEN
Solar/Wind Harmer
2.334
971171AH1-044 GEN
Solar/Wind Harmer
2.318
926823AC1-168 GEN
Solar/Wind Harmer
14.021
24385905FR-11G C
Solar/Wind Harmer
17.109
276782AC1-033 GEN
Solar/Wind Harmer
14.5
946321AF1-296 GEN
Solar/Wind Harmer
32.251
959611AF2-252 GEN
Solar/Wind Harmer
4.294
960611AF2-352 GEN
Solar/Wind Harmer
4.294
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
3.348
24653605MOTTVILLE
50/50
0.008
24307105BERRINSP G
50/50
0.048
971769AH1-391 GEN
Solar/Wind Harmer
1.303
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.29
945111AF1-176 GEN
Solar/Wind Harmer
12.484
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
126.162
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.687
970571AG2-364 GEN
Solar/Wind Harmer
2.284
971681AH1-341 GEN
Solar/Wind Harmer
1.706
938861AE1-114 GEN
Solar/Wind Harmer
26.61
276603SUBLETTE C
Solar/Wind Harmer
3.862
965011AG1-365 GEN
Solar/Wind Harmer
1.123
972175AH1-670 GEN
Solar/Wind Harmer
40.448
276174W4-005 GEN2
Solar/Wind Harmer
7.56
970239AG2-162 GEN
Solar/Wind Harmer
1.524
276893AG1-478 C
Solar/Wind Harmer
-0.001
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
3.56
24691005MDL-2G C
Solar/Wind Harmer
14.724
971997AH1-543 GEN
Solar/Wind Harmer
1.844
276863AD2-134 GEN
Solar/Wind Harmer
7.166
971549AH1-272 GEN
Solar/Wind Harmer
2.153
274863CRW1-WTG
Solar/Wind Harmer
21.955
276889AE2-281 GEN
Solar/Wind Harmer
7.407
274856ECOGROVE ;U1
Solar/Wind Harmer
13.423
965021AG1-366 GEN
Solar/Wind Harmer
4.491
276158O29GEN2
Solar/Wind Harmer
16.305
276708O09 GEN2
Solar/Wind Harmer
13.724
958861AF2-177 GEN
Solar/Wind Harmer
32.945
945371AF1-202 GEN
Solar/Wind Harmer
15.713
274880W4-005 GEN4
Solar/Wind Harmer
7.56
270142AC1-141 CT1_
50/50
5.381
270143AC1-141 CT2_
50/50
5.381
24639705ELKHART HY
50/50
0.359
965681AG1-436 GEN
Solar/Wind Harmer
1.638
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.214
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.318
970169AG2-114 GEN
Solar/Wind Harmer
1.141
961011AF2-392 GEN
Solar/Wind Harmer
34.864
963791AG1-232 GEN
Solar/Wind Harmer
1.357
276785W4-005 GEN1
Solar/Wind Harmer
7.56
944961AF1-161 GEN
50/50
6.392
970243AG2-164 GEN
Solar/Wind Harmer
3.577
971771AH1-392 GEN
Solar/Wind Harmer
1.176
270505AE1-170 C O1
Solar/Wind Harmer
1.938
270043AE2-236 GEN
Solar/Wind Harmer
0.71
274888KELLY CRK;1U
Solar/Wind Harmer
25.103
970941AG2-585 GEN
Solar/Wind Harmer
1.546
971605AH1-302 GEN
Solar/Wind Harmer
18.291
276805AD2-038 GEN
Solar/Wind Harmer
21.371
274850MENDOTA H;RU
Solar/Wind Harmer
10.5
276861AD2-134 GEN
Solar/Wind Harmer
7.166
274864CRW2-WTG
Solar/Wind Harmer
21.955
970569AG2-363 GEN
Solar/Wind Harmer
3.426
274858EASY ROAD;U2
Solar/Wind Harmer
17.754
276157O29GEN1
Solar/Wind Harmer
16.305
957751AF2-069 GEN
Solar/Wind Harmer
1.458
939741AE1-205 GEN
Solar/Wind Harmer
2.191
970241AG2-163 GEN
Solar/Wind Harmer
2.585
971599AH1-298 GEN
50/50
21.036
970321AG2-212 GEN
Solar/Wind Harmer
2.888
970333AG2-219 GEN
Solar/Wind Harmer
4.372
270071AF1-092 GEN
Solar/Wind Harmer
1.926
276602WESTBROOK C
Solar/Wind Harmer
8.175
970611AG2-400 GEN
Solar/Wind Harmer
1.123
24387305FR-4G C
Solar/Wind Harmer
13.054
24386605FR-22G C
Solar/Wind Harmer
8.703
24387005FR-3G C
Solar/Wind Harmer
8.616
276645AC1-214 GEN1
Solar/Wind Harmer
4.778
942111AE2-223 GEN
Solar/Wind Harmer
25.633
270102X2-052 ST
50/50
3.624
970901AG2-562 GEN
50/50
13.732
970245AG2-165 GEN
Solar/Wind Harmer
2.888
970349AG2-230 GEN
Solar/Wind Harmer
2.09
971347AH1-153 GEN
Solar/Wind Harmer
2.09
961051AF2-396 GEN
Solar/Wind Harmer
2.561
961051AF2-396 GEN
Solar/Wind Harmer
20.485
972231SS25-0005
Solar/Wind Harmer
2.005
274862TOP CROP ;2U
Solar/Wind Harmer
19.567
970921AG2-575 GEN
Solar/Wind Harmer
1.183
970921AG2-575 GEN
Solar/Wind Harmer
4.733
274879MINONK ;1U
Solar/Wind Harmer
27.571
971411AH1-196 GEN
Solar/Wind Harmer
1.752
274855GSG-6 ;RU
Solar/Wind Harmer
14.825
24386405FR-21G C
Solar/Wind Harmer
8.703
960971AF2-388 GEN
Solar/Wind Harmer
33.741
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.675
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
23.557
274872LEEDK;1U
Solar/Wind Harmer
0.519
270180AB1-006 GEN1
Solar/Wind Harmer
27.585
24791305MDL-5G
Solar/Wind Harmer
9.707
959081AF2-199 GEN
Solar/Wind Harmer
1.159
971475AH1-234 GEN
Solar/Wind Harmer
2.562
24386205FR-12G C
Solar/Wind Harmer
9.086
276646AC1-214 GEN2
Solar/Wind Harmer
4.778
276726Z2-087_GEN
Solar/Wind Harmer
28.481
963741AG1-226 GEN
Solar/Wind Harmer
4.654
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
28.423
943121AE2-341 GEN
Solar/Wind Harmer
1.821
957471AF2-041 GEN
Solar/Wind Harmer
3.477
274848CAMPGROVE;RU
Solar/Wind Harmer
20.056
959341AF2-225 GEN
Solar/Wind Harmer
1.643
965651AG1-433 GEN
Solar/Wind Harmer
16.87
970291AG2-192 GEN
Solar/Wind Harmer
0.133
970289AG2-191 GEN
Solar/Wind Harmer
1.352
970521AG2-332 GEN
50/50
25.509
276806AD2-047 C O1
Solar/Wind Harmer
38.087
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
21.75
971341AH1-150 GEN
Solar/Wind Harmer
2.318
247642Z2-115 C
Solar/Wind Harmer
-0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.229
270471AD2-092_GEN
Solar/Wind Helper
0.687
972207SS24-0001
Solar/Wind Harmer
3.811
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
1.253
24755605MDL-5G
Solar/Wind Harmer
9.707
959091AF2-200 GEN
Solar/Wind Harmer
2.318
274849CRESCENT ;1U
Solar/Wind Harmer
7.294
274877BISHOP HL;1U
Solar/Wind Harmer
12.834
970289AG2-191 GEN
Solar/Wind Harmer
0.195
270349AD2-093_GEN
Solar/Wind Helper
0.687
944201AF1-088_MTX
Adder
148.128
957141AF2-008_MTX
Adder
74.064
NYPJM->LTFIMP_NY
CLTF
3.326
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.568
SIGELTFEXP_SIGE->PJM
CLTF
0.513
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.171
WECLTFEXP_WEC->PJM
CLTF
7.559
MECLTFEXP_MEC->PJM
CLTF
26.993
AG2-052LTFEXP_AG2-052->PJM
LTF
0.47
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.173
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.261
LAGNLTFEXP_LAGN->PJM
CLTF
13.768
AH1-155LTFEXP_AH1-155->PJM
LTF
0.706
CBM West 1LTFEXP_CBM-W1->PJM
CBM
232.762
LGEELTFEXP_LGEE->PJM
CLTF
4.567
TVALTFEXP_TVA->PJM
CLTF
5.095
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
52.01

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.24 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2290.85
MW Contribution:2.09
Bus #Bus NameTypeMW Contribution
972181SS23-001
Solar/Wind Harmer
0.44
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.3
970289AG2-191 GEN
Solar/Wind Harmer
0.078
24755605MDL-5G
Solar/Wind Harmer
3.34
959091AF2-200 GEN
Solar/Wind Harmer
0.805
946031AF1-268 GEN
Solar/Wind Harmer
0.324
274849CRESCENT ;1U
Solar/Wind Harmer
2.552
274877BISHOP HL;1U
Solar/Wind Harmer
4.493
270349AD2-093_GEN
Solar/Wind Helper
0.444
970521AG2-332 GEN
50/50
10.75
247521TR3_G114
Solar/Wind Harmer
8.58
276806AD2-047 C O1
Solar/Wind Harmer
13.208
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.511
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.495
970615AG2-402 GEN
50/50
4.56
24729405KEY G3
50/50
6.792
24729505KEY G4
50/50
6.679
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.437
270505AE1-170 C O1
Solar/Wind Harmer
0.719
274888KELLY CRK;1U
Solar/Wind Harmer
8.705
970941AG2-585 GEN
Solar/Wind Harmer
0.536
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.887
970517AG2-330 GEN
Solar/Wind Harmer
13.834
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.464
962781AG1-127 GEN
Solar/Wind Harmer
0.39
958821AF2-173 GEN
Solar/Wind Harmer
0.573
971335AH1-147 GEN
Solar/Wind Harmer
0.81
24697605MDL-3G C
Solar/Wind Harmer
5.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.805
926823AC1-168 GEN
Solar/Wind Harmer
4.888
24385905FR-11G C
Solar/Wind Harmer
5.945
276782AC1-033 GEN
Solar/Wind Harmer
5.076
24725505WLD G2 C
Solar/Wind Harmer
4.997
946321AF1-296 GEN
Solar/Wind Harmer
11.312
958581AF2-149 GEN
Solar/Wind Helper
0.216
960611AF2-352 GEN
Solar/Wind Harmer
1.01
960971AF2-388 GEN
Solar/Wind Harmer
16.226
24727005RPMNG1
50/50
68.465
247620Y3-023
50/50
0.46
965041AG1-368 GEN
Solar/Wind Harmer
0.694
270191TR4_S_V150
Solar/Wind Harmer
6.398
965101AG1-375 GEN
Solar/Wind Harmer
0.505
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.368
971917AH1-482 GEN
Solar/Wind Harmer
6.668
276691AA1-018 GEN1
Solar/Wind Harmer
0.448
276872AE1-163_GEN1
Solar/Wind Harmer
9.042
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.622
971067AG2-660 GEN
Solar/Wind Harmer
1.611
970115AG2-085 GEN
Solar/Wind Harmer
0.161
276741O09 GEN1
Solar/Wind Harmer
4.795
276655WTG1_EQ
Solar/Wind Harmer
6.613
270578AF1-285 GEN2
Solar/Wind Helper
0.282
247522W1-056 GEN
Solar/Wind Helper
1.885
270286AF1-227 GEN2
Solar/Wind Helper
0.344
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.289
971617AH1-308 GEN
Solar/Wind Harmer
5.12
943021AE2-325 GEN
Solar/Wind Harmer
2.954
958011AF2-095 GEN
Solar/Wind Harmer
0.618
971573AH1-285 GEN
Solar/Wind Harmer
0.358
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.616
942991AE2-321 GEN
Solar/Wind Harmer
0.407
971333AH1-146 GEN
Solar/Wind Harmer
0.81
24697905MDL-4G C
Solar/Wind Harmer
3.34
970819AG2-516 GEN
Solar/Wind Harmer
0.479
274851PROVIDENC;RU
Solar/Wind Harmer
3.693
964611AG1-324 GEN
Solar/Wind Harmer
0.35
270201AC2-176 GEN
Solar/Wind Harmer
6.57
274878BISHOP HL;2U
Solar/Wind Harmer
4.493
24699105WLD G1 C
Solar/Wind Harmer
4.967
965931AG1-462 GEN
Solar/Wind Harmer
0.963
270499AE1-146 GEN
Solar/Wind Helper
0.534
971605AH1-302 GEN
Solar/Wind Harmer
6.289
276805AD2-038 GEN
Solar/Wind Harmer
7.442
274850MENDOTA H;RU
Solar/Wind Harmer
3.644
276861AD2-134 GEN
Solar/Wind Harmer
2.487
274864CRW2-WTG
Solar/Wind Harmer
7.63
970569AG2-363 GEN
Solar/Wind Harmer
1.196
274858EASY ROAD;U2
Solar/Wind Harmer
6.189
276157O29GEN1
Solar/Wind Harmer
5.697
957751AF2-069 GEN
Solar/Wind Harmer
0.51
939741AE1-205 GEN
Solar/Wind Harmer
0.768
246938BC-WTG3
Solar/Wind Helper
5.468
246936BC-WTG1
Solar/Wind Helper
5.531
24727205RPMNG3
50/50
68.465
24639705ELKHART HY
50/50
0.149
963791AG1-232 GEN
Solar/Wind Harmer
0.959
270246TR4_N_V150
Solar/Wind Harmer
1.16
24695305TIMB G C
Solar/Wind Harmer
9.67
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.419
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.409
971343AH1-151 GEN
Solar/Wind Harmer
0.805
970169AG2-114 GEN
Solar/Wind Harmer
0.398
961011AF2-392 GEN
Solar/Wind Harmer
12.167
270227U2-072_GEN3
Solar/Wind Helper
0.141
270228U2-072_GEN4
Solar/Wind Helper
0.141
276820AF1-078_GEN
Solar/Wind Helper
0.151
970349AG2-230 GEN
Solar/Wind Harmer
0.722
971347AH1-153 GEN
Solar/Wind Harmer
0.722
961051AF2-396 GEN
Solar/Wind Harmer
0.958
961051AF2-396 GEN
Solar/Wind Harmer
7.664
270599AE1-208 GEN
Solar/Wind Harmer
0.368
970245AG2-165 GEN
Solar/Wind Harmer
0.887
972231SS25-0005
Solar/Wind Harmer
0.704
274862TOP CROP ;2U
Solar/Wind Harmer
6.808
970921AG2-575 GEN
Solar/Wind Harmer
0.41
970921AG2-575 GEN
Solar/Wind Harmer
1.639
274879MINONK ;1U
Solar/Wind Harmer
9.594
971411AH1-196 GEN
Solar/Wind Harmer
0.608
274855GSG-6 ;RU
Solar/Wind Harmer
5.144
24386405FR-21G C
Solar/Wind Harmer
3.024
942871AE2-306 GEN
Solar/Wind Helper
0.211
945641AF1-229 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.447
24641605TWIN BRNCH
50/50
0.015
944531AF1-118 GEN
Solar/Wind Harmer
2.039
959331AF2-224 GEN
Solar/Wind Harmer
1.14
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.037
276843GEN-1.7
Solar/Wind Harmer
0.708
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.858
276882AE2-255 GEN
Solar/Wind Harmer
4.328
960441AF2-335 GEN
Solar/Wind Harmer
0.402
270223U2-072_GEN1
Solar/Wind Helper
0.141
966831AG1-554 GEN
Solar/Wind Helper
0.276
274854TWINGROVE;U2
Solar/Wind Harmer
6.161
274887GEN-1.85
Solar/Wind Harmer
7.997
970707AG2-453 GEN
Solar/Wind Harmer
1.193
970833AG2-524 GEN
Solar/Wind Harmer
3.709
958481AF2-142 GEN
Solar/Wind Harmer
0.624
276868AE1-113 GEN
Solar/Wind Harmer
13.718
971675AH1-338 GEN
Solar/Wind Harmer
0.729
970781AG2-491 GEN
Solar/Wind Harmer
0.403
960791AF2-370 GEN
Solar/Wind Harmer
1.606
276903AD2-071 C
Solar/Wind Harmer
0.391
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.31
270224U2-072_GEN2
Solar/Wind Helper
0.141
270391AF1-285 GEN3
Solar/Wind Helper
0.282
241847AF2-150_GEN
Solar/Wind Helper
0.259
970583AG2-370 GEN
50/50
2.775
970031AG2-029 GEN
Solar/Wind Harmer
2.089
270247TR4_N_V136
Solar/Wind Harmer
1.16
965051AG1-369 GEN
Solar/Wind Harmer
0.295
960591AF2-350 GEN
Solar/Wind Harmer
0.429
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.024
939401AE1-172 GEN
Solar/Wind Harmer
16.293
276876AE1-163_GEN2
Solar/Wind Harmer
9.042
274857EASY ROAD;U1
Solar/Wind Harmer
6.189
961761AG1-017 GEN
Solar/Wind Harmer
0.383
276656WTG2_EQ
Solar/Wind Harmer
0.876
941731AE2-173 GEN
Solar/Wind Harmer
3.84
270462AD2-086
Solar/Wind Helper
1.767
270317AD1-130_GEN
Solar/Wind Helper
1.153
270287AF1-227 GEN3
Solar/Wind Helper
0.344
960851AF2-376 GEN
50/50
2.066
965021AG1-366 GEN
Solar/Wind Harmer
4.56
958861AF2-177 GEN
Solar/Wind Harmer
15.756
945371AF1-202 GEN
Solar/Wind Harmer
7.43
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.232
270594AE1-207 GEN
Solar/Wind Harmer
0.652
270032AE2-172
Solar/Wind Harmer
3.259
971997AH1-543 GEN
Solar/Wind Harmer
0.64
276863AD2-134 GEN
Solar/Wind Harmer
2.487
274863CRW1-WTG
Solar/Wind Harmer
7.63
276889AE2-281 GEN
Solar/Wind Harmer
2.583
24691005MDL-2G C
Solar/Wind Harmer
5.066
274856ECOGROVE ;U1
Solar/Wind Harmer
4.672
971549AH1-272 GEN
Solar/Wind Harmer
0.724
276158O29GEN2
Solar/Wind Harmer
5.697
276708O09 GEN2
Solar/Wind Harmer
4.795
246937BC-WTG2
Solar/Wind Helper
5.531
270485AE1-090_GEN
Solar/Wind Helper
0.154
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.14
945111AF1-176 GEN
Solar/Wind Harmer
0.877
945111AF1-176 GEN
Solar/Wind Harmer
4.78
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.467
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.563
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.239
970571AG2-364 GEN
Solar/Wind Harmer
0.798
970825AG2-519 GEN
Solar/Wind Harmer
0.442
970825AG2-519 GEN
Solar/Wind Harmer
1.697
971681AH1-341 GEN
Solar/Wind Harmer
0.594
938861AE1-114 GEN
Solar/Wind Harmer
9.271
276603SUBLETTE C
Solar/Wind Harmer
1.346
253378AE2-206_GEN
Solar/Wind Helper
0.334
24727105RPMNG2
50/50
68.465
965651AG1-433 GEN
Solar/Wind Harmer
8.113
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.816
943121AE2-341 GEN
Solar/Wind Harmer
0.628
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.544
957471AF2-041 GEN
Solar/Wind Harmer
1.208
274848CAMPGROVE;RU
Solar/Wind Harmer
7.026
959341AF2-225 GEN
Solar/Wind Harmer
0.576
957201AF2-014 GEN
Solar/Wind Helper
3.936
270284AF1-227 GEN1
Solar/Wind Helper
0.932
270428AC2-015 C
Solar/Wind Helper
0.365
971599AH1-298 GEN
50/50
10.28
960861AF2-377 GEN
50/50
2.361
24729305KEY G2
50/50
6.792
970611AG2-400 GEN
Solar/Wind Harmer
1.14
270071AF1-092 GEN
Solar/Wind Harmer
0.935
970321AG2-212 GEN
Solar/Wind Harmer
0.887
270005AE1-210 C O1
Solar/Wind Harmer
6.381
276602WESTBROOK C
Solar/Wind Harmer
2.837
276645AC1-214 GEN1
Solar/Wind Harmer
1.672
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.583
24387305FR-4G C
Solar/Wind Harmer
4.536
24386605FR-22G C
Solar/Wind Harmer
3.024
24387005FR-3G C
Solar/Wind Harmer
2.994
942111AE2-223 GEN
Solar/Wind Harmer
8.986
960841AF2-375 GEN
Solar/Wind Helper
0.553
24729205KEY G1
50/50
6.679
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.927
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.196
270004AE1-209 GEN
Solar/Wind Harmer
6.381
274872LEEDK;1U
Solar/Wind Harmer
0.18
270180AB1-006 GEN1
Solar/Wind Harmer
9.491
24791305MDL-5G
Solar/Wind Harmer
3.34
959081AF2-199 GEN
Solar/Wind Harmer
0.403
971475AH1-234 GEN
Solar/Wind Harmer
0.892
276646AC1-214 GEN2
Solar/Wind Harmer
1.672
24386205FR-12G C
Solar/Wind Harmer
3.157
276726Z2-087_GEN
Solar/Wind Harmer
9.984
971341AH1-150 GEN
Solar/Wind Harmer
0.805
270302AB2-170 GEN
Solar/Wind Helper
1.153
270231U2-072_GEN5
Solar/Wind Helper
0.141
270471AD2-092_GEN
Solar/Wind Helper
0.444
944201AF1-088_MTX
Adder
55.858
957141AF2-008_MTX
Adder
27.929
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.626
LGEELTFEXP_LGEE->PJM
CLTF
1.821
LAGNLTFEXP_LAGN->PJM
CLTF
5.9
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.085
TVALTFEXP_TVA->PJM
CLTF
2.406
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.398
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.501
NYPJM->LTFIMP_NY
CLTF
1.242
MECLTFEXP_MEC->PJM
CLTF
9.671
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.201
WECLTFEXP_WEC->PJM
CLTF
2.632
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.35 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2533.64
MW Contribution:0.82
Bus #Bus NameTypeMW Contribution
25194708EBND2
50/50
6.244
965101AG1-375 GEN
Solar/Wind Harmer
0.582
970115AG2-085 GEN
Solar/Wind Harmer
0.232
270031AE2-169
Solar/Wind Harmer
0.434
270383AD1-128 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
9.729
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
7.898
971917AH1-482 GEN
Solar/Wind Harmer
4.546
276686W4-005 GEN3
Solar/Wind Harmer
2.827
276655WTG1_EQ
Solar/Wind Harmer
4.886
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.298
276872AE1-163_GEN1
Solar/Wind Harmer
6.172
252509AD1-136 GEN
Solar/Wind Helper
0.048
270186AC1-089 GEN
Solar/Wind Helper
0.586
24726905LAWG2S
50/50
5.646
24726705LAWG2A
50/50
3.664
270437AC2-090 C
Solar/Wind Harmer
0
958821AF2-173 GEN
Solar/Wind Harmer
0.969
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
7.055
247536S-71 GEN
Solar/Wind Harmer
5.241
970883AG2-550 GEN
Solar/Wind Harmer
0.35
970193AG2-126 GEN
Solar/Wind Harmer
0.505
24385905FR-11G C
Solar/Wind Harmer
4.688
24697605MDL-3G C
Solar/Wind Harmer
3.761
270181AB1-006 GEN2
Solar/Wind Harmer
0.468
959141AF2-205 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.58
970517AG2-330 GEN
Solar/Wind Harmer
9.046
963831AG1-236 GEN
Solar/Wind Harmer
7.964
959611AF2-252 GEN
Solar/Wind Harmer
1.133
960611AF2-352 GEN
Solar/Wind Harmer
1.133
970833AG2-524 GEN
Solar/Wind Harmer
0.307
926823AC1-168 GEN
Solar/Wind Harmer
3.387
962781AG1-127 GEN
Solar/Wind Harmer
0.261
253415AE1-040 GEN
Solar/Wind Helper
0.164
24728705AND G3
50/50
8.872
926881AC1-175 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
0.41
958381AF2-132 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0.647
941731AE2-173 GEN
Solar/Wind Harmer
2.838
939401AE1-172 GEN
Solar/Wind Harmer
11.199
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.28
276694AA1-018 GEN2
Solar/Wind Harmer
5.349
276876AE1-163_GEN2
Solar/Wind Harmer
6.172
970031AG2-029 GEN
Solar/Wind Harmer
0.822
252507AC2-088 GEN
Solar/Wind Helper
0.339
253406AD2-031_GEN
Solar/Wind Helper
0.227
24726605LAWG1S
50/50
5.646
24729405KEY G3
50/50
6.143
24729505KEY G4
50/50
6.041
970241AG2-163 GEN
Solar/Wind Harmer
0.794
270043AE2-236 GEN
Solar/Wind Harmer
0.17
971605AH1-302 GEN
Solar/Wind Harmer
4.413
276668AB2-070 GEN1
Solar/Wind Harmer
2.149
939741AE1-205 GEN
Solar/Wind Harmer
0.568
274864CRW2-WTG
Solar/Wind Harmer
5.328
274888KELLY CRK;1U
Solar/Wind Harmer
5.675
970941AG2-585 GEN
Solar/Wind Harmer
0.349
276805AD2-038 GEN
Solar/Wind Harmer
5.01
971771AH1-392 GEN
Solar/Wind Harmer
0.248
970569AG2-363 GEN
Solar/Wind Harmer
0.825
957751AF2-069 GEN
Solar/Wind Harmer
0.359
961491AF2-440 GEN
Solar/Wind Helper
0.207
965031AG1-367 GEN
Solar/Wind Harmer
0.692
270024AE2-089 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
0.417
270445AC2-157 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
2.827
970169AG2-114 GEN
Solar/Wind Harmer
0.282
965681AG1-436 GEN
Solar/Wind Harmer
0.35
276901AD2-066 C O1
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.277
253303V4-073 C
Solar/Wind Helper
0.01
276820AF1-078_GEN
Solar/Wind Helper
0.202
241974AD2-163_GEN2
Solar/Wind Helper
0.284
241955AC1-078 GEN
Solar/Wind Helper
0.525
24726505LAWG1B
50/50
3.664
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
9.597
958861AF2-177 GEN
Solar/Wind Harmer
18.162
270594AE1-207 GEN
Solar/Wind Harmer
0.812
270032AE2-172
Solar/Wind Harmer
4.061
24691005MDL-2G C
Solar/Wind Harmer
3.767
957841AF2-078 GEN
Solar/Wind Harmer
0
274880W4-005 GEN4
Solar/Wind Harmer
2.827
971993AH1-541 GEN
Solar/Wind Harmer
0.263
276838X2-022 GEN2
Solar/Wind Harmer
0.23
274863CRW1-WTG
Solar/Wind Harmer
5.328
942481AE2-261 GEN
Solar/Wind Harmer
0.838
276893AG1-478 C
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
0.436
276889AE2-281 GEN
Solar/Wind Harmer
1.763
962691AG1-118 GEN
Solar/Wind Harmer
0.823
270367AC2-061_GEN
Solar/Wind Helper
0.527
962581AG1-107 GEN
Solar/Wind Helper
0.622
24726405LAWG1A
50/50
3.664
970825AG2-519 GEN
Solar/Wind Harmer
0.652
970825AG2-519 GEN
Solar/Wind Harmer
2.503
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
2.827
972175AH1-670 GEN
Solar/Wind Harmer
11.068
276621W2-048 GEN
Solar/Wind Harmer
6.104
276897AD1-100 C
Solar/Wind Harmer
28.765
971769AH1-391 GEN
Solar/Wind Harmer
0.276
970571AG2-364 GEN
Solar/Wind Harmer
0.55
253378AE2-206_GEN
Solar/Wind Helper
0.449
24729305KEY G2
50/50
6.143
270240V3-007_GEN2
Solar/Wind Harmer
17.763
270239V3-007_GEN1
Solar/Wind Harmer
4.932
270005AE1-210 C O1
Solar/Wind Harmer
10.803
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.623
270543AE2-219 C
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
0.506
24387305FR-4G C
Solar/Wind Harmer
3.577
24386605FR-22G C
Solar/Wind Harmer
2.385
24387005FR-3G C
Solar/Wind Harmer
2.361
971673AH1-337 GEN
Solar/Wind Harmer
0.14
970321AG2-212 GEN
Solar/Wind Harmer
0.58
942111AE2-223 GEN
Solar/Wind Harmer
6.64
276645AC1-214 GEN1
Solar/Wind Harmer
1.175
252510AF1-249 C
Solar/Wind Helper
0.172
253394AE2-221_GEN
Solar/Wind Helper
0.729
253398AE2-221_GEN2
Solar/Wind Helper
0.729
960791AF2-370 GEN
Solar/Wind Harmer
2.324
276903AD2-071 C
Solar/Wind Harmer
0.521
944531AF1-118 GEN
Solar/Wind Harmer
1.725
945391AF1-204 GEN
Solar/Wind Harmer
13.393
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.3
274853TWINGROVE;U1
Solar/Wind Harmer
6.988
276615X2-022 GEN
Solar/Wind Harmer
1.935
965911AG1-460 GEN
Solar/Wind Harmer
0.672
274887GEN-1.85
Solar/Wind Harmer
5.213
970707AG2-453 GEN
Solar/Wind Harmer
0.781
970833AG2-524 GEN
Solar/Wind Harmer
2.453
958481AF2-142 GEN
Solar/Wind Harmer
0.416
276868AE1-113 GEN
Solar/Wind Harmer
9.278
942051AE2-217 GEN
Solar/Wind Helper
0.581
961161AF2-407 GEN
50/50
35.348
960971AF2-388 GEN
Solar/Wind Harmer
17.622
270599AE1-208 GEN
Solar/Wind Harmer
0.434
971029AG2-637 GEN
Solar/Wind Harmer
0.478
24386405FR-21G C
Solar/Wind Harmer
2.385
970245AG2-165 GEN
Solar/Wind Harmer
0.58
970349AG2-230 GEN
Solar/Wind Harmer
0.426
24726805LAWG2B
50/50
3.442
24699105WLD G1 C
Solar/Wind Harmer
7.012
964611AG1-324 GEN
Solar/Wind Harmer
0.403
270201AC2-176 GEN
Solar/Wind Harmer
7.021
971617AH1-308 GEN
Solar/Wind Harmer
3.755
24697905MDL-4G C
Solar/Wind Harmer
2.483
945421AF1-207 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
0.85
958011AF2-095 GEN
Solar/Wind Harmer
0.403
958491AF2-143 GEN
Solar/Wind Harmer
0.415
971573AH1-285 GEN
Solar/Wind Harmer
0.237
274851PROVIDENC;RU
Solar/Wind Harmer
2.596
942991AE2-321 GEN
Solar/Wind Harmer
0.273
241972AD1-140 GEN
Solar/Wind Helper
0.861
253325AC1-069 GEN
Solar/Wind Helper
0.159
945631AF1-228 GEN
Solar/Wind Helper
0.492
24729205KEY G1
50/50
6.041
270004AE1-209 GEN
Solar/Wind Harmer
10.803
970885AG2-551 GEN
Solar/Wind Harmer
1.402
963741AG1-226 GEN
Solar/Wind Harmer
1.429
24386205FR-12G C
Solar/Wind Harmer
2.489
270180AB1-006 GEN1
Solar/Wind Harmer
7.057
24791305MDL-5G
Solar/Wind Harmer
2.483
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.601
276726Z2-087_GEN
Solar/Wind Harmer
7.378
276764AC1-053 GEN2
Solar/Wind Harmer
3.687
276911AD2-131_GEN
Solar/Wind Harmer
0.14
274861TOP CROP ;1U
Solar/Wind Harmer
5.465
270526AF1-158 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.12
276646AC1-214 GEN2
Solar/Wind Harmer
1.175
25183208HLCRTG
Solar/Wind Helper
1.129
964351AG1-297 GEN
50/50
13.711
946031AF1-268 GEN
Solar/Wind Harmer
0.469
970289AG2-191 GEN
Solar/Wind Harmer
0.091
24755605MDL-5G
Solar/Wind Harmer
2.483
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
0.843
276916AD2-100_GEN
Solar/Wind Harmer
0.588
972181SS23-001
Solar/Wind Harmer
0.28
274849CRESCENT ;1U
Solar/Wind Harmer
1.794
253343AC1-166 GEN
Solar/Wind Helper
0.159
961171AF2-408 GEN
50/50
9.376
24728605AND G2
50/50
4.191
965651AG1-433 GEN
Solar/Wind Harmer
8.811
970291AG2-192 GEN
Solar/Wind Harmer
0.062
970289AG2-191 GEN
Solar/Wind Harmer
0.632
276849AB2-070 GEN2
Solar/Wind Harmer
2.149
959341AF2-225 GEN
Solar/Wind Harmer
0.426
274871GR RIDGE ;2U
Solar/Wind Harmer
6.494
943121AE2-341 GEN
Solar/Wind Harmer
0.415
252524AE2-267 GEN
Solar/Wind Helper
0.567
253317AC1-085 GEN4
Solar/Wind Helper
0.685
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253383AE2-342_GEN
Solar/Wind Helper
0.13
253333AC1-068 GEN
Solar/Wind Helper
0.159
241973AD2-163_GEN1
Solar/Wind Helper
0.284
274848CAMPGROVE;RU
Solar/Wind Harmer
3.648
24728505AND G1
50/50
4.191
247621Y3-024
50/50
0.245
970291AG2-192 GEN
Solar/Wind Harmer
0.574
247642Z2-115 C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
2.15
276806AD2-047 C O1
Solar/Wind Harmer
8.611
274847GR RIDGE ;BU
Solar/Wind Harmer
4.97
253316AC1-085 GEN3
Solar/Wind Helper
0.685
253433AC1-085 GEN1
Solar/Wind Helper
0.434
253338AC1-165 GEN
Solar/Wind Helper
0.159
971347AH1-153 GEN
Solar/Wind Harmer
0.426
276763AC1-053 GEN1
Solar/Wind Harmer
3.687
972231SS25-0005
Solar/Wind Harmer
0.447
274862TOP CROP ;2U
Solar/Wind Harmer
4.539
274879MINONK ;1U
Solar/Wind Harmer
6.489
970921AG2-575 GEN
Solar/Wind Harmer
0.274
970921AG2-575 GEN
Solar/Wind Harmer
1.096
24379505HDWTR1G C
Solar/Wind Harmer
22.695
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
960441AF2-335 GEN
Solar/Wind Harmer
0.581
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
6.915
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.081
276843GEN-1.7
Solar/Wind Harmer
0.462
944221AF1-090 GEN
Solar/Wind Harmer
8.723
276882AE2-255 GEN
Solar/Wind Harmer
2.927
274872LEEDK;1U
Solar/Wind Harmer
7.942
270518AE2-148 GEN
Solar/Wind Helper
2.228
270340AC2-060 GEN
Solar/Wind Helper
0.387
944201AF1-088_MTX
Adder
60.781
957141AF2-008_MTX
Adder
30.391
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.564
NYPJM->LTFIMP_NY
CLTF
0.669
TVALTFEXP_TVA->PJM
CLTF
1.863
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.122
WECLTFEXP_WEC->PJM
CLTF
1.777
LAGNLTFEXP_LAGN->PJM
CLTF
4.643
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.409
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.008
SIGELTFEXP_SIGE->PJM
CLTF
0.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.326
LGEELTFEXP_LGEE->PJM
CLTF
1.409
MECLTFEXP_MEC->PJM
CLTF
7.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.51 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2514.08
MW Contribution:0.82
Bus #Bus NameTypeMW Contribution
24729305KEY G2
50/50
6.143
270240V3-007_GEN2
Solar/Wind Harmer
17.763
270239V3-007_GEN1
Solar/Wind Harmer
4.932
270005AE1-210 C O1
Solar/Wind Harmer
10.803
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.623
270543AE2-219 C
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
0.506
24387305FR-4G C
Solar/Wind Harmer
3.577
24386605FR-22G C
Solar/Wind Harmer
2.385
24387005FR-3G C
Solar/Wind Harmer
2.361
971673AH1-337 GEN
Solar/Wind Harmer
0.14
926881AC1-175 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
0.41
958381AF2-132 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0.647
941731AE2-173 GEN
Solar/Wind Harmer
2.838
939401AE1-172 GEN
Solar/Wind Harmer
11.199
960791AF2-370 GEN
Solar/Wind Harmer
2.324
276903AD2-071 C
Solar/Wind Harmer
0.521
944531AF1-118 GEN
Solar/Wind Harmer
1.725
945391AF1-204 GEN
Solar/Wind Harmer
13.393
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.3
274853TWINGROVE;U1
Solar/Wind Harmer
6.988
24726805LAWG2B
50/50
3.442
24699105WLD G1 C
Solar/Wind Harmer
7.012
964611AG1-324 GEN
Solar/Wind Harmer
0.403
24729205KEY G1
50/50
6.041
270004AE1-209 GEN
Solar/Wind Harmer
10.803
970885AG2-551 GEN
Solar/Wind Harmer
1.402
963741AG1-226 GEN
Solar/Wind Harmer
1.429
24386205FR-12G C
Solar/Wind Harmer
2.489
270180AB1-006 GEN1
Solar/Wind Harmer
7.057
24791305MDL-5G
Solar/Wind Harmer
2.483
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.601
276726Z2-087_GEN
Solar/Wind Harmer
7.378
276764AC1-053 GEN2
Solar/Wind Harmer
3.687
276911AD2-131_GEN
Solar/Wind Harmer
0.14
25194708EBND2
50/50
6.244
965101AG1-375 GEN
Solar/Wind Harmer
0.582
970115AG2-085 GEN
Solar/Wind Harmer
0.232
270031AE2-169
Solar/Wind Harmer
0.434
270383AD1-128 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
9.729
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
7.898
971917AH1-482 GEN
Solar/Wind Harmer
4.546
276686W4-005 GEN3
Solar/Wind Harmer
2.827
276655WTG1_EQ
Solar/Wind Harmer
4.886
965031AG1-367 GEN
Solar/Wind Harmer
0.692
270024AE2-089 GEN
Solar/Wind Harmer
0
964351AG1-297 GEN
50/50
13.711
946031AF1-268 GEN
Solar/Wind Harmer
0.469
970289AG2-191 GEN
Solar/Wind Harmer
0.091
24755605MDL-5G
Solar/Wind Harmer
2.483
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
0.843
276916AD2-100_GEN
Solar/Wind Harmer
0.588
972181SS23-001
Solar/Wind Harmer
0.28
274849CRESCENT ;1U
Solar/Wind Harmer
1.794
253343AC1-166 GEN
Solar/Wind Helper
0.159
961171AF2-408 GEN
50/50
9.376
965651AG1-433 GEN
Solar/Wind Harmer
8.811
970291AG2-192 GEN
Solar/Wind Harmer
0.062
970289AG2-191 GEN
Solar/Wind Harmer
0.632
276849AB2-070 GEN2
Solar/Wind Harmer
2.149
959341AF2-225 GEN
Solar/Wind Harmer
0.426
274871GR RIDGE ;2U
Solar/Wind Harmer
6.494
943121AE2-341 GEN
Solar/Wind Harmer
0.415
252524AE2-267 GEN
Solar/Wind Helper
0.567
253317AC1-085 GEN4
Solar/Wind Helper
0.685
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253383AE2-342_GEN
Solar/Wind Helper
0.13
253333AC1-068 GEN
Solar/Wind Helper
0.159
241973AD2-163_GEN1
Solar/Wind Helper
0.284
274848CAMPGROVE;RU
Solar/Wind Harmer
3.648
970291AG2-192 GEN
Solar/Wind Harmer
0.574
247642Z2-115 C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
2.15
276806AD2-047 C O1
Solar/Wind Harmer
8.611
274847GR RIDGE ;BU
Solar/Wind Harmer
4.97
253316AC1-085 GEN3
Solar/Wind Helper
0.685
253433AC1-085 GEN1
Solar/Wind Helper
0.434
253338AC1-165 GEN
Solar/Wind Helper
0.159
24726605LAWG1S
50/50
5.646
24729405KEY G3
50/50
6.143
24729505KEY G4
50/50
6.041
970241AG2-163 GEN
Solar/Wind Harmer
0.794
270043AE2-236 GEN
Solar/Wind Harmer
0.17
971605AH1-302 GEN
Solar/Wind Harmer
4.413
276668AB2-070 GEN1
Solar/Wind Harmer
2.149
939741AE1-205 GEN
Solar/Wind Harmer
0.568
274864CRW2-WTG
Solar/Wind Harmer
5.328
274888KELLY CRK;1U
Solar/Wind Harmer
5.675
970941AG2-585 GEN
Solar/Wind Harmer
0.349
276805AD2-038 GEN
Solar/Wind Harmer
5.01
971771AH1-392 GEN
Solar/Wind Harmer
0.248
970569AG2-363 GEN
Solar/Wind Harmer
0.825
957751AF2-069 GEN
Solar/Wind Harmer
0.359
961491AF2-440 GEN
Solar/Wind Helper
0.207
24726905LAWG2S
50/50
5.646
24726705LAWG2A
50/50
3.664
270437AC2-090 C
Solar/Wind Harmer
0
958821AF2-173 GEN
Solar/Wind Harmer
0.969
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
7.055
247536S-71 GEN
Solar/Wind Harmer
5.241
970883AG2-550 GEN
Solar/Wind Harmer
0.35
970193AG2-126 GEN
Solar/Wind Harmer
0.505
24385905FR-11G C
Solar/Wind Harmer
4.688
24697605MDL-3G C
Solar/Wind Harmer
3.761
270181AB1-006 GEN2
Solar/Wind Harmer
0.468
959141AF2-205 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.58
970517AG2-330 GEN
Solar/Wind Harmer
9.046
963831AG1-236 GEN
Solar/Wind Harmer
7.964
959611AF2-252 GEN
Solar/Wind Harmer
1.133
960611AF2-352 GEN
Solar/Wind Harmer
1.133
970833AG2-524 GEN
Solar/Wind Harmer
0.307
926823AC1-168 GEN
Solar/Wind Harmer
3.387
962781AG1-127 GEN
Solar/Wind Harmer
0.261
253415AE1-040 GEN
Solar/Wind Helper
0.164
961161AF2-407 GEN
50/50
35.348
960971AF2-388 GEN
Solar/Wind Harmer
17.622
270599AE1-208 GEN
Solar/Wind Harmer
0.434
971029AG2-637 GEN
Solar/Wind Harmer
0.478
24386405FR-21G C
Solar/Wind Harmer
2.385
970245AG2-165 GEN
Solar/Wind Harmer
0.58
970349AG2-230 GEN
Solar/Wind Harmer
0.426
971347AH1-153 GEN
Solar/Wind Harmer
0.426
276763AC1-053 GEN1
Solar/Wind Harmer
3.687
972231SS25-0005
Solar/Wind Harmer
0.447
274862TOP CROP ;2U
Solar/Wind Harmer
4.539
274879MINONK ;1U
Solar/Wind Harmer
6.489
970921AG2-575 GEN
Solar/Wind Harmer
0.274
970921AG2-575 GEN
Solar/Wind Harmer
1.096
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.298
276872AE1-163_GEN1
Solar/Wind Harmer
6.172
252509AD1-136 GEN
Solar/Wind Helper
0.048
270186AC1-089 GEN
Solar/Wind Helper
0.586
24379505HDWTR1G C
Solar/Wind Harmer
22.695
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
960441AF2-335 GEN
Solar/Wind Harmer
0.581
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
6.915
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.081
276843GEN-1.7
Solar/Wind Harmer
0.462
944221AF1-090 GEN
Solar/Wind Harmer
8.723
276882AE2-255 GEN
Solar/Wind Harmer
2.927
274872LEEDK;1U
Solar/Wind Harmer
7.942
270518AE2-148 GEN
Solar/Wind Helper
2.228
270340AC2-060 GEN
Solar/Wind Helper
0.387
270201AC2-176 GEN
Solar/Wind Harmer
7.021
971617AH1-308 GEN
Solar/Wind Harmer
3.755
24697905MDL-4G C
Solar/Wind Harmer
2.483
945421AF1-207 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
0.85
958011AF2-095 GEN
Solar/Wind Harmer
0.403
958491AF2-143 GEN
Solar/Wind Harmer
0.415
971573AH1-285 GEN
Solar/Wind Harmer
0.237
274851PROVIDENC;RU
Solar/Wind Harmer
2.596
942991AE2-321 GEN
Solar/Wind Harmer
0.273
241972AD1-140 GEN
Solar/Wind Helper
0.861
253325AC1-069 GEN
Solar/Wind Helper
0.159
945631AF1-228 GEN
Solar/Wind Helper
0.492
24726505LAWG1B
50/50
3.664
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
9.597
958861AF2-177 GEN
Solar/Wind Harmer
18.162
270594AE1-207 GEN
Solar/Wind Harmer
0.812
270032AE2-172
Solar/Wind Harmer
4.061
24691005MDL-2G C
Solar/Wind Harmer
3.767
957841AF2-078 GEN
Solar/Wind Harmer
0
274880W4-005 GEN4
Solar/Wind Harmer
2.827
971993AH1-541 GEN
Solar/Wind Harmer
0.263
276838X2-022 GEN2
Solar/Wind Harmer
0.23
274863CRW1-WTG
Solar/Wind Harmer
5.328
942481AE2-261 GEN
Solar/Wind Harmer
0.838
276893AG1-478 C
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
0.436
276889AE2-281 GEN
Solar/Wind Harmer
1.763
962691AG1-118 GEN
Solar/Wind Harmer
0.823
270367AC2-061_GEN
Solar/Wind Helper
0.527
962581AG1-107 GEN
Solar/Wind Helper
0.622
963791AG1-232 GEN
Solar/Wind Harmer
0.417
270445AC2-157 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
2.827
970169AG2-114 GEN
Solar/Wind Harmer
0.282
965681AG1-436 GEN
Solar/Wind Harmer
0.35
276901AD2-066 C O1
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.277
253303V4-073 C
Solar/Wind Helper
0.01
276820AF1-078_GEN
Solar/Wind Helper
0.202
241974AD2-163_GEN2
Solar/Wind Helper
0.284
241955AC1-078 GEN
Solar/Wind Helper
0.525
276615X2-022 GEN
Solar/Wind Harmer
1.935
965911AG1-460 GEN
Solar/Wind Harmer
0.672
274887GEN-1.85
Solar/Wind Harmer
5.213
970707AG2-453 GEN
Solar/Wind Harmer
0.781
970833AG2-524 GEN
Solar/Wind Harmer
2.453
958481AF2-142 GEN
Solar/Wind Harmer
0.416
276868AE1-113 GEN
Solar/Wind Harmer
9.278
942051AE2-217 GEN
Solar/Wind Helper
0.581
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.28
276694AA1-018 GEN2
Solar/Wind Harmer
5.349
276876AE1-163_GEN2
Solar/Wind Harmer
6.172
970031AG2-029 GEN
Solar/Wind Harmer
0.822
252507AC2-088 GEN
Solar/Wind Helper
0.339
253406AD2-031_GEN
Solar/Wind Helper
0.227
24726405LAWG1A
50/50
3.664
970825AG2-519 GEN
Solar/Wind Harmer
0.652
970825AG2-519 GEN
Solar/Wind Harmer
2.503
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
2.827
972175AH1-670 GEN
Solar/Wind Harmer
11.068
276621W2-048 GEN
Solar/Wind Harmer
6.104
276897AD1-100 C
Solar/Wind Harmer
28.765
971769AH1-391 GEN
Solar/Wind Harmer
0.276
970571AG2-364 GEN
Solar/Wind Harmer
0.55
253378AE2-206_GEN
Solar/Wind Helper
0.449
970321AG2-212 GEN
Solar/Wind Harmer
0.58
942111AE2-223 GEN
Solar/Wind Harmer
6.64
276645AC1-214 GEN1
Solar/Wind Harmer
1.175
252510AF1-249 C
Solar/Wind Helper
0.172
253394AE2-221_GEN
Solar/Wind Helper
0.729
253398AE2-221_GEN2
Solar/Wind Helper
0.729
274861TOP CROP ;1U
Solar/Wind Harmer
5.465
270526AF1-158 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.12
276646AC1-214 GEN2
Solar/Wind Harmer
1.175
25183208HLCRTG
Solar/Wind Helper
1.129
944201AF1-088_MTX
Adder
60.781
957141AF2-008_MTX
Adder
30.391
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.122
WECLTFEXP_WEC->PJM
CLTF
1.777
LAGNLTFEXP_LAGN->PJM
CLTF
4.643
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.564
NYPJM->LTFIMP_NY
CLTF
0.669
TVALTFEXP_TVA->PJM
CLTF
1.863
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.326
LGEELTFEXP_LGEE->PJM
CLTF
1.409
MECLTFEXP_MEC->PJM
CLTF
7.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.409
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.008
SIGELTFEXP_SIGE->PJM
CLTF
0.233

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.9 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2499.97
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
964351AG1-297 GEN
50/50
22.581
946031AF1-268 GEN
Solar/Wind Harmer
0.775
970289AG2-191 GEN
Solar/Wind Harmer
0.133
24755605MDL-5G
Solar/Wind Harmer
2.438
276916AD2-100_GEN
Solar/Wind Harmer
0.603
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
0.271
274849CRESCENT ;1U
Solar/Wind Harmer
1.761
972207SS24-0001
Solar/Wind Harmer
0.804
274877BISHOP HL;1U
Solar/Wind Harmer
3.102
253343AC1-166 GEN
Solar/Wind Helper
0.15
943111AE2-339 GEN
Solar/Wind Helper
0.1
961171AF2-408 GEN
50/50
15.002
24728605AND G2
50/50
6.569
965651AG1-433 GEN
Solar/Wind Harmer
13.372
970291AG2-192 GEN
Solar/Wind Harmer
0.091
970289AG2-191 GEN
Solar/Wind Harmer
0.923
276849AB2-070 GEN2
Solar/Wind Harmer
2.195
959341AF2-225 GEN
Solar/Wind Harmer
0.426
274871GR RIDGE ;2U
Solar/Wind Harmer
6.267
274848CAMPGROVE;RU
Solar/Wind Harmer
4.885
252524AE2-267 GEN
Solar/Wind Helper
0.448
253317AC1-085 GEN4
Solar/Wind Helper
0.695
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253333AC1-068 GEN
Solar/Wind Helper
0.15
24728505AND G1
50/50
6.569
247621Y3-024
50/50
0.444
970291AG2-192 GEN
Solar/Wind Harmer
0.839
247642Z2-115 C
Solar/Wind Harmer
-0.001
276848AB2-070 GEN3
Solar/Wind Harmer
2.196
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
8.313
274847GR RIDGE ;BU
Solar/Wind Harmer
4.796
253316AC1-085 GEN3
Solar/Wind Helper
0.695
253433AC1-085 GEN1
Solar/Wind Helper
0.44
253338AC1-165 GEN
Solar/Wind Helper
0.15
24726605LAWG1S
50/50
9.725
24729405KEY G3
50/50
9.018
24729505KEY G4
50/50
8.868
270043AE2-236 GEN
Solar/Wind Harmer
0.203
970241AG2-163 GEN
Solar/Wind Harmer
0.845
276668AB2-070 GEN1
Solar/Wind Harmer
2.195
971605AH1-302 GEN
Solar/Wind Harmer
4.274
939741AE1-205 GEN
Solar/Wind Harmer
0.569
274864CRW2-WTG
Solar/Wind Harmer
5.241
971771AH1-392 GEN
Solar/Wind Harmer
0.246
274888KELLY CRK;1U
Solar/Wind Harmer
5.479
970941AG2-585 GEN
Solar/Wind Harmer
0.337
276805AD2-038 GEN
Solar/Wind Harmer
4.87
957751AF2-069 GEN
Solar/Wind Harmer
0.352
970569AG2-363 GEN
Solar/Wind Harmer
0.806
270505AE1-170 C O1
Solar/Wind Harmer
0.402
961491AF2-440 GEN
Solar/Wind Helper
0.193
24726905LAWG2S
50/50
9.725
24726705LAWG2A
50/50
6.312
270437AC2-090 C
Solar/Wind Harmer
0
958821AF2-173 GEN
Solar/Wind Harmer
1.557
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
10.89
247536S-71 GEN
Solar/Wind Harmer
9.762
970883AG2-550 GEN
Solar/Wind Harmer
0.689
970193AG2-126 GEN
Solar/Wind Harmer
0.58
24385905FR-11G C
Solar/Wind Harmer
4.727
270063AE2-323 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
3.692
270181AB1-006 GEN2
Solar/Wind Harmer
0.459
963831AG1-236 GEN
Solar/Wind Harmer
8.138
959611AF2-252 GEN
Solar/Wind Harmer
1.139
960611AF2-352 GEN
Solar/Wind Harmer
1.139
959141AF2-205 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
3.314
970833AG2-524 GEN
Solar/Wind Harmer
0.296
276782AC1-033 GEN
Solar/Wind Harmer
3.504
253415AE1-040 GEN
Solar/Wind Helper
0.16
339216AC1-074 GEN
Solar/Wind Helper
0.253
961161AF2-407 GEN
50/50
55.656
24728905RICHG2
50/50
5.707
960971AF2-388 GEN
Solar/Wind Harmer
26.744
270599AE1-208 GEN
Solar/Wind Harmer
0.681
971029AG2-637 GEN
Solar/Wind Harmer
1.005
24386405FR-21G C
Solar/Wind Harmer
2.404
276763AC1-053 GEN1
Solar/Wind Harmer
3.767
972231SS25-0005
Solar/Wind Harmer
0.433
970349AG2-230 GEN
Solar/Wind Harmer
0.405
971347AH1-153 GEN
Solar/Wind Harmer
0.405
274862TOP CROP ;2U
Solar/Wind Harmer
4.404
274879MINONK ;1U
Solar/Wind Harmer
6.309
961051AF2-396 GEN
Solar/Wind Harmer
0.504
961051AF2-396 GEN
Solar/Wind Harmer
4.034
24728805RICHG1
50/50
5.707
970115AG2-085 GEN
Solar/Wind Harmer
0.375
270383AD1-128 GEN
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
0.892
270031AE2-169
Solar/Wind Harmer
0.681
270222AC2-111 GEN
Solar/Wind Harmer
0.582
963841AG1-237 GEN
Solar/Wind Harmer
10.103
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
7.752
276686W4-005 GEN3
Solar/Wind Harmer
2.888
276655WTG1_EQ
Solar/Wind Harmer
4.896
971917AH1-482 GEN
Solar/Wind Harmer
4.398
965041AG1-368 GEN
Solar/Wind Harmer
0.276
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.29
276872AE1-163_GEN1
Solar/Wind Harmer
6.018
252509AD1-136 GEN
Solar/Wind Helper
0.061
270186AC1-089 GEN
Solar/Wind Helper
0.591
339243AC2-075 GEN1
Solar/Wind Helper
0.063
24379505HDWTR1G C
Solar/Wind Harmer
37.341
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
960441AF2-335 GEN
Solar/Wind Harmer
0.938
944541AF1-119 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
0.312
944221AF1-090 GEN
Solar/Wind Harmer
8.986
274854TWINGROVE;U2
Solar/Wind Harmer
6.952
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
2.974
276843GEN-1.7
Solar/Wind Harmer
0.446
276882AE2-255 GEN
Solar/Wind Harmer
2.846
270518AE2-148 GEN
Solar/Wind Helper
1.934
270340AC2-060 GEN
Solar/Wind Helper
0.388
339221AD2-048_GEN
Solar/Wind Helper
0.215
24726805LAWG2B
50/50
5.93
24699105WLD G1 C
Solar/Wind Harmer
10.823
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
12.282
971617AH1-308 GEN
Solar/Wind Harmer
6.268
24697905MDL-4G C
Solar/Wind Harmer
2.438
945421AF1-207 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
0.854
958011AF2-095 GEN
Solar/Wind Harmer
0.389
958491AF2-143 GEN
Solar/Wind Harmer
0.403
274851PROVIDENC;RU
Solar/Wind Harmer
2.548
274878BISHOP HL;2U
Solar/Wind Harmer
3.102
241972AD1-140 GEN
Solar/Wind Helper
0.704
253325AC1-069 GEN
Solar/Wind Helper
0.15
945631AF1-228 GEN
Solar/Wind Helper
0.426
24726505LAWG1B
50/50
6.312
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
14.943
958861AF2-177 GEN
Solar/Wind Harmer
27.824
270594AE1-207 GEN
Solar/Wind Harmer
1.225
270032AE2-172
Solar/Wind Harmer
6.127
965021AG1-366 GEN
Solar/Wind Harmer
1.248
24691005MDL-2G C
Solar/Wind Harmer
3.698
274880W4-005 GEN4
Solar/Wind Harmer
2.888
971993AH1-541 GEN
Solar/Wind Harmer
0.268
276838X2-022 GEN2
Solar/Wind Harmer
0.235
957841AF2-078 GEN
Solar/Wind Harmer
0
942481AE2-261 GEN
Solar/Wind Harmer
0.859
274863CRW1-WTG
Solar/Wind Harmer
5.241
971997AH1-543 GEN
Solar/Wind Harmer
0.424
276893AG1-478 C
Solar/Wind Harmer
0
276889AE2-281 GEN
Solar/Wind Harmer
1.72
270367AC2-061_GEN
Solar/Wind Helper
0.507
962581AG1-107 GEN
Solar/Wind Helper
0.58
965031AG1-367 GEN
Solar/Wind Harmer
1.112
270024AE2-089 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
0.628
276785W4-005 GEN1
Solar/Wind Harmer
2.888
270445AC2-157 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
0.279
965681AG1-436 GEN
Solar/Wind Harmer
0.338
276901AD2-066 C O1
Solar/Wind Harmer
0
253303V4-073 C
Solar/Wind Helper
0.008
276820AF1-078_GEN
Solar/Wind Helper
0.135
960791AF2-370 GEN
Solar/Wind Harmer
3.752
276903AD2-071 C
Solar/Wind Harmer
0.79
944531AF1-118 GEN
Solar/Wind Harmer
2.497
945391AF1-204 GEN
Solar/Wind Harmer
15.394
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.294
276615X2-022 GEN
Solar/Wind Harmer
1.978
965911AG1-460 GEN
Solar/Wind Harmer
0.689
274853TWINGROVE;U1
Solar/Wind Harmer
7.026
274887GEN-1.85
Solar/Wind Harmer
5.033
970833AG2-524 GEN
Solar/Wind Harmer
2.367
958481AF2-142 GEN
Solar/Wind Harmer
0.403
276868AE1-113 GEN
Solar/Wind Harmer
9.021
970707AG2-453 GEN
Solar/Wind Harmer
0.749
942051AE2-217 GEN
Solar/Wind Helper
0.46
24728705AND G3
50/50
13.905
926881AC1-175 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
0.716
970031AG2-029 GEN
Solar/Wind Harmer
0.932
276656WTG2_EQ
Solar/Wind Harmer
0.648
941731AE2-173 GEN
Solar/Wind Harmer
2.843
958381AF2-132 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
10.958
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.27
276694AA1-018 GEN2
Solar/Wind Harmer
5.188
276876AE1-163_GEN2
Solar/Wind Harmer
6.018
252507AC2-088 GEN
Solar/Wind Helper
0.426
253406AD2-031_GEN
Solar/Wind Helper
0.215
24726405LAWG1A
50/50
6.312
970825AG2-519 GEN
Solar/Wind Harmer
1.058
970825AG2-519 GEN
Solar/Wind Harmer
4.06
965011AG1-365 GEN
Solar/Wind Harmer
0.312
276174W4-005 GEN2
Solar/Wind Harmer
2.888
276621W2-048 GEN
Solar/Wind Harmer
6.241
972175AH1-670 GEN
Solar/Wind Harmer
11.223
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
27.79
945111AF1-176 GEN
Solar/Wind Harmer
0.483
945111AF1-176 GEN
Solar/Wind Harmer
2.633
971769AH1-391 GEN
Solar/Wind Harmer
0.271
957891AF2-083 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
0.537
253378AE2-206_GEN
Solar/Wind Helper
0.3
24729305KEY G2
50/50
9.018
270240V3-007_GEN2
Solar/Wind Harmer
29.226
270239V3-007_GEN1
Solar/Wind Harmer
8.115
270005AE1-210 C O1
Solar/Wind Harmer
17.353
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.09
270543AE2-219 C
Solar/Wind Harmer
0
971673AH1-337 GEN
Solar/Wind Harmer
0.304
270071AF1-092 GEN
Solar/Wind Harmer
0.612
970611AG2-400 GEN
Solar/Wind Harmer
0.312
24387305FR-4G C
Solar/Wind Harmer
3.607
24386605FR-22G C
Solar/Wind Harmer
2.404
24387005FR-3G C
Solar/Wind Harmer
2.38
942111AE2-223 GEN
Solar/Wind Harmer
6.653
276645AC1-214 GEN1
Solar/Wind Harmer
1.154
252510AF1-249 C
Solar/Wind Helper
0.15
253394AE2-221_GEN
Solar/Wind Helper
0.706
253398AE2-221_GEN2
Solar/Wind Helper
0.706
24729205KEY G1
50/50
8.868
270004AE1-209 GEN
Solar/Wind Harmer
17.353
970885AG2-551 GEN
Solar/Wind Harmer
2.754
963741AG1-226 GEN
Solar/Wind Harmer
1.522
24386205FR-12G C
Solar/Wind Harmer
2.51
270180AB1-006 GEN1
Solar/Wind Harmer
6.927
24791305MDL-5G
Solar/Wind Harmer
2.438
276764AC1-053 GEN2
Solar/Wind Harmer
3.767
276911AD2-131_GEN
Solar/Wind Harmer
0.144
276726Z2-087_GEN
Solar/Wind Harmer
7.392
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.581
270526AF1-158 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
5.302
276646AC1-214 GEN2
Solar/Wind Harmer
1.154
25183208HLCRTG
Solar/Wind Helper
1.188
944201AF1-088_MTX
Adder
57.805
957141AF2-008_MTX
Adder
28.902
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.249
WECLTFEXP_WEC->PJM
CLTF
1.719
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.173
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.276
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
4.036
NYPJM->LTFIMP_NY
CLTF
0.68
TVALTFEXP_TVA->PJM
CLTF
1.464
SIGELTFEXP_SIGE->PJM
CLTF
0.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.919
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.324
MECLTFEXP_MEC->PJM
CLTF
6.937
AH1-155LTFEXP_AH1-155->PJM
LTF
0.182

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.9 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2499.96
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
960791AF2-370 GEN
Solar/Wind Harmer
3.752
276903AD2-071 C
Solar/Wind Harmer
0.79
944531AF1-118 GEN
Solar/Wind Harmer
2.497
945391AF1-204 GEN
Solar/Wind Harmer
15.394
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.294
276615X2-022 GEN
Solar/Wind Harmer
1.978
965911AG1-460 GEN
Solar/Wind Harmer
0.689
274853TWINGROVE;U1
Solar/Wind Harmer
7.026
274887GEN-1.85
Solar/Wind Harmer
5.033
970833AG2-524 GEN
Solar/Wind Harmer
2.367
958481AF2-142 GEN
Solar/Wind Harmer
0.403
276868AE1-113 GEN
Solar/Wind Harmer
9.021
970707AG2-453 GEN
Solar/Wind Harmer
0.749
942051AE2-217 GEN
Solar/Wind Helper
0.46
24379505HDWTR1G C
Solar/Wind Harmer
37.341
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
960441AF2-335 GEN
Solar/Wind Harmer
0.938
944541AF1-119 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
0.312
944221AF1-090 GEN
Solar/Wind Harmer
8.986
274854TWINGROVE;U2
Solar/Wind Harmer
6.952
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
2.974
276843GEN-1.7
Solar/Wind Harmer
0.446
276882AE2-255 GEN
Solar/Wind Harmer
2.846
270518AE2-148 GEN
Solar/Wind Helper
1.934
270340AC2-060 GEN
Solar/Wind Helper
0.388
339221AD2-048_GEN
Solar/Wind Helper
0.215
24726805LAWG2B
50/50
5.93
24699105WLD G1 C
Solar/Wind Harmer
10.823
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
12.282
971617AH1-308 GEN
Solar/Wind Harmer
6.268
24697905MDL-4G C
Solar/Wind Harmer
2.438
945421AF1-207 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
0.854
958011AF2-095 GEN
Solar/Wind Harmer
0.389
958491AF2-143 GEN
Solar/Wind Harmer
0.403
274851PROVIDENC;RU
Solar/Wind Harmer
2.548
274878BISHOP HL;2U
Solar/Wind Harmer
3.102
241972AD1-140 GEN
Solar/Wind Helper
0.704
253325AC1-069 GEN
Solar/Wind Helper
0.15
945631AF1-228 GEN
Solar/Wind Helper
0.426
24728805RICHG1
50/50
5.707
970115AG2-085 GEN
Solar/Wind Harmer
0.375
270383AD1-128 GEN
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
0.892
270031AE2-169
Solar/Wind Harmer
0.681
270222AC2-111 GEN
Solar/Wind Harmer
0.582
963841AG1-237 GEN
Solar/Wind Harmer
10.103
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
7.752
276686W4-005 GEN3
Solar/Wind Harmer
2.888
276655WTG1_EQ
Solar/Wind Harmer
4.896
24728705AND G3
50/50
13.905
926881AC1-175 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
0.716
970031AG2-029 GEN
Solar/Wind Harmer
0.932
276656WTG2_EQ
Solar/Wind Harmer
0.648
941731AE2-173 GEN
Solar/Wind Harmer
2.843
958381AF2-132 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
10.958
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.27
276694AA1-018 GEN2
Solar/Wind Harmer
5.188
276876AE1-163_GEN2
Solar/Wind Harmer
6.018
252507AC2-088 GEN
Solar/Wind Helper
0.426
253406AD2-031_GEN
Solar/Wind Helper
0.215
24726905LAWG2S
50/50
9.725
24726705LAWG2A
50/50
6.312
270437AC2-090 C
Solar/Wind Harmer
0
958821AF2-173 GEN
Solar/Wind Harmer
1.557
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
10.89
247536S-71 GEN
Solar/Wind Harmer
9.762
970883AG2-550 GEN
Solar/Wind Harmer
0.689
970193AG2-126 GEN
Solar/Wind Harmer
0.58
24385905FR-11G C
Solar/Wind Harmer
4.727
270063AE2-323 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
3.692
270181AB1-006 GEN2
Solar/Wind Harmer
0.459
963831AG1-236 GEN
Solar/Wind Harmer
8.138
24726405LAWG1A
50/50
6.312
970825AG2-519 GEN
Solar/Wind Harmer
1.058
970825AG2-519 GEN
Solar/Wind Harmer
4.06
965011AG1-365 GEN
Solar/Wind Harmer
0.312
276174W4-005 GEN2
Solar/Wind Harmer
2.888
276621W2-048 GEN
Solar/Wind Harmer
6.241
972175AH1-670 GEN
Solar/Wind Harmer
11.223
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
27.79
945111AF1-176 GEN
Solar/Wind Harmer
0.483
945111AF1-176 GEN
Solar/Wind Harmer
2.633
971769AH1-391 GEN
Solar/Wind Harmer
0.271
957891AF2-083 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
0.537
253378AE2-206_GEN
Solar/Wind Helper
0.3
24726505LAWG1B
50/50
6.312
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
14.943
958861AF2-177 GEN
Solar/Wind Harmer
27.824
270594AE1-207 GEN
Solar/Wind Harmer
1.225
270032AE2-172
Solar/Wind Harmer
6.127
965021AG1-366 GEN
Solar/Wind Harmer
1.248
24691005MDL-2G C
Solar/Wind Harmer
3.698
274880W4-005 GEN4
Solar/Wind Harmer
2.888
971993AH1-541 GEN
Solar/Wind Harmer
0.268
276838X2-022 GEN2
Solar/Wind Harmer
0.235
957841AF2-078 GEN
Solar/Wind Harmer
0
942481AE2-261 GEN
Solar/Wind Harmer
0.859
274863CRW1-WTG
Solar/Wind Harmer
5.241
971997AH1-543 GEN
Solar/Wind Harmer
0.424
276893AG1-478 C
Solar/Wind Harmer
0
276889AE2-281 GEN
Solar/Wind Harmer
1.72
270367AC2-061_GEN
Solar/Wind Helper
0.507
962581AG1-107 GEN
Solar/Wind Helper
0.58
965031AG1-367 GEN
Solar/Wind Harmer
1.112
270024AE2-089 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
0.628
276785W4-005 GEN1
Solar/Wind Harmer
2.888
270445AC2-157 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
0.279
965681AG1-436 GEN
Solar/Wind Harmer
0.338
276901AD2-066 C O1
Solar/Wind Harmer
0
253303V4-073 C
Solar/Wind Helper
0.008
276820AF1-078_GEN
Solar/Wind Helper
0.135
24726605LAWG1S
50/50
9.725
24729405KEY G3
50/50
9.018
24729505KEY G4
50/50
8.868
270043AE2-236 GEN
Solar/Wind Harmer
0.203
970241AG2-163 GEN
Solar/Wind Harmer
0.845
276668AB2-070 GEN1
Solar/Wind Harmer
2.195
971605AH1-302 GEN
Solar/Wind Harmer
4.274
939741AE1-205 GEN
Solar/Wind Harmer
0.569
274864CRW2-WTG
Solar/Wind Harmer
5.241
971771AH1-392 GEN
Solar/Wind Harmer
0.246
274888KELLY CRK;1U
Solar/Wind Harmer
5.479
970941AG2-585 GEN
Solar/Wind Harmer
0.337
276805AD2-038 GEN
Solar/Wind Harmer
4.87
957751AF2-069 GEN
Solar/Wind Harmer
0.352
970569AG2-363 GEN
Solar/Wind Harmer
0.806
270505AE1-170 C O1
Solar/Wind Harmer
0.402
961491AF2-440 GEN
Solar/Wind Helper
0.193
24729305KEY G2
50/50
9.018
270240V3-007_GEN2
Solar/Wind Harmer
29.226
270239V3-007_GEN1
Solar/Wind Harmer
8.115
270005AE1-210 C O1
Solar/Wind Harmer
17.353
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.09
270543AE2-219 C
Solar/Wind Harmer
0
971673AH1-337 GEN
Solar/Wind Harmer
0.304
270071AF1-092 GEN
Solar/Wind Harmer
0.612
970611AG2-400 GEN
Solar/Wind Harmer
0.312
24387305FR-4G C
Solar/Wind Harmer
3.607
24386605FR-22G C
Solar/Wind Harmer
2.404
24387005FR-3G C
Solar/Wind Harmer
2.38
942111AE2-223 GEN
Solar/Wind Harmer
6.653
276645AC1-214 GEN1
Solar/Wind Harmer
1.154
252510AF1-249 C
Solar/Wind Helper
0.15
253394AE2-221_GEN
Solar/Wind Helper
0.706
253398AE2-221_GEN2
Solar/Wind Helper
0.706
971917AH1-482 GEN
Solar/Wind Harmer
4.398
965041AG1-368 GEN
Solar/Wind Harmer
0.276
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.29
276872AE1-163_GEN1
Solar/Wind Harmer
6.018
252509AD1-136 GEN
Solar/Wind Helper
0.061
270186AC1-089 GEN
Solar/Wind Helper
0.591
339243AC2-075 GEN1
Solar/Wind Helper
0.063
959611AF2-252 GEN
Solar/Wind Harmer
1.139
960611AF2-352 GEN
Solar/Wind Harmer
1.139
959141AF2-205 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
3.314
970833AG2-524 GEN
Solar/Wind Harmer
0.296
276782AC1-033 GEN
Solar/Wind Harmer
3.504
253415AE1-040 GEN
Solar/Wind Helper
0.16
339216AC1-074 GEN
Solar/Wind Helper
0.253
961161AF2-407 GEN
50/50
55.656
24728905RICHG2
50/50
5.707
960971AF2-388 GEN
Solar/Wind Harmer
26.744
270599AE1-208 GEN
Solar/Wind Harmer
0.681
971029AG2-637 GEN
Solar/Wind Harmer
1.005
24386405FR-21G C
Solar/Wind Harmer
2.404
276763AC1-053 GEN1
Solar/Wind Harmer
3.767
972231SS25-0005
Solar/Wind Harmer
0.433
970349AG2-230 GEN
Solar/Wind Harmer
0.405
971347AH1-153 GEN
Solar/Wind Harmer
0.405
274862TOP CROP ;2U
Solar/Wind Harmer
4.404
274879MINONK ;1U
Solar/Wind Harmer
6.309
961051AF2-396 GEN
Solar/Wind Harmer
0.504
961051AF2-396 GEN
Solar/Wind Harmer
4.034
24729205KEY G1
50/50
8.868
270004AE1-209 GEN
Solar/Wind Harmer
17.353
970885AG2-551 GEN
Solar/Wind Harmer
2.754
963741AG1-226 GEN
Solar/Wind Harmer
1.522
24386205FR-12G C
Solar/Wind Harmer
2.51
270180AB1-006 GEN1
Solar/Wind Harmer
6.927
24791305MDL-5G
Solar/Wind Harmer
2.438
276764AC1-053 GEN2
Solar/Wind Harmer
3.767
276911AD2-131_GEN
Solar/Wind Harmer
0.144
276726Z2-087_GEN
Solar/Wind Harmer
7.392
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.581
270526AF1-158 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
5.302
276646AC1-214 GEN2
Solar/Wind Harmer
1.154
25183208HLCRTG
Solar/Wind Helper
1.188
961171AF2-408 GEN
50/50
15.002
24728605AND G2
50/50
6.569
965651AG1-433 GEN
Solar/Wind Harmer
13.372
970291AG2-192 GEN
Solar/Wind Harmer
0.091
970289AG2-191 GEN
Solar/Wind Harmer
0.923
276849AB2-070 GEN2
Solar/Wind Harmer
2.195
959341AF2-225 GEN
Solar/Wind Harmer
0.426
274871GR RIDGE ;2U
Solar/Wind Harmer
6.267
274848CAMPGROVE;RU
Solar/Wind Harmer
4.885
252524AE2-267 GEN
Solar/Wind Helper
0.448
253317AC1-085 GEN4
Solar/Wind Helper
0.695
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253333AC1-068 GEN
Solar/Wind Helper
0.15
24728505AND G1
50/50
6.569
247621Y3-024
50/50
0.444
970291AG2-192 GEN
Solar/Wind Harmer
0.839
247642Z2-115 C
Solar/Wind Harmer
-0.001
276848AB2-070 GEN3
Solar/Wind Harmer
2.196
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
8.313
274847GR RIDGE ;BU
Solar/Wind Harmer
4.796
253316AC1-085 GEN3
Solar/Wind Helper
0.695
253433AC1-085 GEN1
Solar/Wind Helper
0.44
253338AC1-165 GEN
Solar/Wind Helper
0.15
964351AG1-297 GEN
50/50
22.581
946031AF1-268 GEN
Solar/Wind Harmer
0.775
970289AG2-191 GEN
Solar/Wind Harmer
0.133
24755605MDL-5G
Solar/Wind Harmer
2.438
276916AD2-100_GEN
Solar/Wind Harmer
0.603
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
0.271
274849CRESCENT ;1U
Solar/Wind Harmer
1.761
972207SS24-0001
Solar/Wind Harmer
0.804
274877BISHOP HL;1U
Solar/Wind Harmer
3.102
253343AC1-166 GEN
Solar/Wind Helper
0.15
943111AE2-339 GEN
Solar/Wind Helper
0.1
944201AF1-088_MTX
Adder
57.805
957141AF2-008_MTX
Adder
28.902
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.249
WECLTFEXP_WEC->PJM
CLTF
1.719
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.173
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.276
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
4.036
NYPJM->LTFIMP_NY
CLTF
0.68
TVALTFEXP_TVA->PJM
CLTF
1.464
SIGELTFEXP_SIGE->PJM
CLTF
0.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.919
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.324
MECLTFEXP_MEC->PJM
CLTF
6.937
AH1-155LTFEXP_AH1-155->PJM
LTF
0.182

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.42 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2339.21
MW Contribution:2.09
Bus #Bus NameTypeMW Contribution
965421AG1-410 GEN
Solar/Wind Harmer
6.773
972181SS23-001
Solar/Wind Harmer
0.44
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.3
970289AG2-191 GEN
Solar/Wind Harmer
0.078
24755605MDL-5G
Solar/Wind Harmer
3.34
959091AF2-200 GEN
Solar/Wind Harmer
0.805
946031AF1-268 GEN
Solar/Wind Harmer
0.324
274849CRESCENT ;1U
Solar/Wind Harmer
2.552
274877BISHOP HL;1U
Solar/Wind Harmer
4.493
270349AD2-093_GEN
Solar/Wind Helper
0.444
24727105RPMNG2
50/50
68.465
965651AG1-433 GEN
Solar/Wind Harmer
8.113
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.816
943121AE2-341 GEN
Solar/Wind Harmer
0.628
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970521AG2-332 GEN
50/50
10.75
247521TR3_G114
Solar/Wind Harmer
8.58
276806AD2-047 C O1
Solar/Wind Harmer
13.208
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.511
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.495
971341AH1-150 GEN
Solar/Wind Harmer
0.805
270302AB2-170 GEN
Solar/Wind Helper
1.153
270231U2-072_GEN5
Solar/Wind Helper
0.141
270471AD2-092_GEN
Solar/Wind Helper
0.444
970615AG2-402 GEN
50/50
4.56
24729405KEY G3
50/50
6.792
24729505KEY G4
50/50
6.679
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.437
270505AE1-170 C O1
Solar/Wind Harmer
0.719
274888KELLY CRK;1U
Solar/Wind Harmer
8.705
970941AG2-585 GEN
Solar/Wind Harmer
0.536
971605AH1-302 GEN
Solar/Wind Harmer
6.289
276805AD2-038 GEN
Solar/Wind Harmer
7.442
274850MENDOTA H;RU
Solar/Wind Harmer
3.644
276861AD2-134 GEN
Solar/Wind Harmer
2.487
274864CRW2-WTG
Solar/Wind Harmer
7.63
970569AG2-363 GEN
Solar/Wind Harmer
1.196
274858EASY ROAD;U2
Solar/Wind Harmer
6.189
276157O29GEN1
Solar/Wind Harmer
5.697
957751AF2-069 GEN
Solar/Wind Harmer
0.51
939741AE1-205 GEN
Solar/Wind Harmer
0.768
246938BC-WTG3
Solar/Wind Helper
5.468
246936BC-WTG1
Solar/Wind Helper
5.531
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.887
970517AG2-330 GEN
Solar/Wind Harmer
13.834
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.464
962781AG1-127 GEN
Solar/Wind Harmer
0.39
958821AF2-173 GEN
Solar/Wind Harmer
0.573
971335AH1-147 GEN
Solar/Wind Harmer
0.81
24697605MDL-3G C
Solar/Wind Harmer
5.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.805
926823AC1-168 GEN
Solar/Wind Harmer
4.888
24385905FR-11G C
Solar/Wind Harmer
5.945
276782AC1-033 GEN
Solar/Wind Harmer
5.076
24725505WLD G2 C
Solar/Wind Harmer
4.997
946321AF1-296 GEN
Solar/Wind Harmer
11.312
958581AF2-149 GEN
Solar/Wind Helper
0.216
960611AF2-352 GEN
Solar/Wind Harmer
0.85
960971AF2-388 GEN
Solar/Wind Harmer
16.226
970349AG2-230 GEN
Solar/Wind Harmer
0.722
971347AH1-153 GEN
Solar/Wind Harmer
0.722
961051AF2-396 GEN
Solar/Wind Harmer
0.958
961051AF2-396 GEN
Solar/Wind Harmer
7.664
270599AE1-208 GEN
Solar/Wind Harmer
0.368
970245AG2-165 GEN
Solar/Wind Harmer
0.887
972231SS25-0005
Solar/Wind Harmer
0.704
274862TOP CROP ;2U
Solar/Wind Harmer
6.808
970921AG2-575 GEN
Solar/Wind Harmer
0.41
970921AG2-575 GEN
Solar/Wind Harmer
1.639
274879MINONK ;1U
Solar/Wind Harmer
9.594
971411AH1-196 GEN
Solar/Wind Harmer
0.608
274855GSG-6 ;RU
Solar/Wind Harmer
5.144
24386405FR-21G C
Solar/Wind Harmer
3.024
942871AE2-306 GEN
Solar/Wind Helper
0.211
945641AF1-229 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.447
24727005RPMNG1
50/50
68.465
247620Y3-023
50/50
0.46
965041AG1-368 GEN
Solar/Wind Harmer
0.694
270191TR4_S_V150
Solar/Wind Harmer
6.398
965101AG1-375 GEN
Solar/Wind Harmer
0.505
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.368
971917AH1-482 GEN
Solar/Wind Harmer
6.668
276691AA1-018 GEN1
Solar/Wind Harmer
0.448
276872AE1-163_GEN1
Solar/Wind Harmer
9.042
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.622
971067AG2-660 GEN
Solar/Wind Harmer
1.611
970115AG2-085 GEN
Solar/Wind Harmer
0.161
276741O09 GEN1
Solar/Wind Harmer
4.795
276655WTG1_EQ
Solar/Wind Harmer
6.613
270578AF1-285 GEN2
Solar/Wind Helper
0.282
247522W1-056 GEN
Solar/Wind Helper
1.885
270286AF1-227 GEN2
Solar/Wind Helper
0.344
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.289
959331AF2-224 GEN
Solar/Wind Harmer
1.14
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.037
276843GEN-1.7
Solar/Wind Harmer
0.708
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.858
276882AE2-255 GEN
Solar/Wind Harmer
4.328
960441AF2-335 GEN
Solar/Wind Harmer
0.402
270223U2-072_GEN1
Solar/Wind Helper
0.141
966831AG1-554 GEN
Solar/Wind Helper
0.276
274854TWINGROVE;U2
Solar/Wind Harmer
5.188
971617AH1-308 GEN
Solar/Wind Harmer
5.12
943021AE2-325 GEN
Solar/Wind Harmer
2.954
958011AF2-095 GEN
Solar/Wind Harmer
0.618
971573AH1-285 GEN
Solar/Wind Harmer
0.358
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.616
942991AE2-321 GEN
Solar/Wind Harmer
0.407
971333AH1-146 GEN
Solar/Wind Harmer
0.81
24697905MDL-4G C
Solar/Wind Harmer
3.34
970819AG2-516 GEN
Solar/Wind Harmer
0.479
274851PROVIDENC;RU
Solar/Wind Harmer
3.693
964611AG1-324 GEN
Solar/Wind Harmer
0.35
270201AC2-176 GEN
Solar/Wind Harmer
6.57
274878BISHOP HL;2U
Solar/Wind Harmer
4.493
24699105WLD G1 C
Solar/Wind Harmer
4.967
965931AG1-462 GEN
Solar/Wind Harmer
0.963
270499AE1-146 GEN
Solar/Wind Helper
0.534
965021AG1-366 GEN
Solar/Wind Harmer
4.56
958861AF2-177 GEN
Solar/Wind Harmer
15.756
945371AF1-202 GEN
Solar/Wind Harmer
7.43
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.232
270594AE1-207 GEN
Solar/Wind Harmer
0.652
270032AE2-172
Solar/Wind Harmer
3.259
971997AH1-543 GEN
Solar/Wind Harmer
0.64
276863AD2-134 GEN
Solar/Wind Harmer
2.487
274863CRW1-WTG
Solar/Wind Harmer
7.63
276889AE2-281 GEN
Solar/Wind Harmer
2.583
965431AG1-411 GEN
50/50
45.157
24727205RPMNG3
50/50
68.465
24639705ELKHART HY
50/50
0.149
963791AG1-232 GEN
Solar/Wind Harmer
0.959
270246TR4_N_V150
Solar/Wind Harmer
1.16
24695305TIMB G C
Solar/Wind Harmer
9.67
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.419
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.409
971343AH1-151 GEN
Solar/Wind Harmer
0.805
970169AG2-114 GEN
Solar/Wind Harmer
0.398
961011AF2-392 GEN
Solar/Wind Harmer
12.167
270227U2-072_GEN3
Solar/Wind Helper
0.141
270228U2-072_GEN4
Solar/Wind Helper
0.141
276820AF1-078_GEN
Solar/Wind Helper
0.151
944531AF1-118 GEN
Solar/Wind Harmer
2.039
274887GEN-1.85
Solar/Wind Harmer
7.997
970707AG2-453 GEN
Solar/Wind Harmer
1.193
970833AG2-524 GEN
Solar/Wind Harmer
3.709
958481AF2-142 GEN
Solar/Wind Harmer
0.624
276868AE1-113 GEN
Solar/Wind Harmer
13.718
971675AH1-338 GEN
Solar/Wind Harmer
0.729
970781AG2-491 GEN
Solar/Wind Harmer
0.403
960791AF2-370 GEN
Solar/Wind Harmer
1.606
276903AD2-071 C
Solar/Wind Harmer
0.391
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.31
270224U2-072_GEN2
Solar/Wind Helper
0.141
270391AF1-285 GEN3
Solar/Wind Helper
0.282
241847AF2-150_GEN
Solar/Wind Helper
0.259
970583AG2-370 GEN
50/50
2.775
970031AG2-029 GEN
Solar/Wind Harmer
2.089
270247TR4_N_V136
Solar/Wind Harmer
1.16
965051AG1-369 GEN
Solar/Wind Harmer
0.295
960591AF2-350 GEN
Solar/Wind Harmer
0.429
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.024
939401AE1-172 GEN
Solar/Wind Harmer
16.293
276876AE1-163_GEN2
Solar/Wind Harmer
9.042
274857EASY ROAD;U1
Solar/Wind Harmer
6.189
961761AG1-017 GEN
Solar/Wind Harmer
0.383
276656WTG2_EQ
Solar/Wind Harmer
0.876
941731AE2-173 GEN
Solar/Wind Harmer
3.84
270462AD2-086
Solar/Wind Helper
1.767
270317AD1-130_GEN
Solar/Wind Helper
1.153
270287AF1-227 GEN3
Solar/Wind Helper
0.344
24691005MDL-2G C
Solar/Wind Harmer
5.066
274856ECOGROVE ;U1
Solar/Wind Harmer
4.672
971549AH1-272 GEN
Solar/Wind Harmer
0.724
276158O29GEN2
Solar/Wind Harmer
5.697
276708O09 GEN2
Solar/Wind Harmer
4.795
246937BC-WTG2
Solar/Wind Helper
5.531
270485AE1-090_GEN
Solar/Wind Helper
0.154
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.14
945111AF1-176 GEN
Solar/Wind Harmer
0.877
945111AF1-176 GEN
Solar/Wind Harmer
4.78
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.467
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.563
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.239
970571AG2-364 GEN
Solar/Wind Harmer
0.798
970825AG2-519 GEN
Solar/Wind Harmer
0.442
970825AG2-519 GEN
Solar/Wind Harmer
1.697
971681AH1-341 GEN
Solar/Wind Harmer
0.594
938861AE1-114 GEN
Solar/Wind Harmer
9.271
276603SUBLETTE C
Solar/Wind Harmer
1.346
253378AE2-206_GEN
Solar/Wind Helper
0.334
970289AG2-191 GEN
Solar/Wind Harmer
0.544
957471AF2-041 GEN
Solar/Wind Harmer
1.208
274848CAMPGROVE;RU
Solar/Wind Harmer
7.026
959341AF2-225 GEN
Solar/Wind Harmer
0.576
957201AF2-014 GEN
Solar/Wind Helper
3.936
270284AF1-227 GEN1
Solar/Wind Helper
0.932
270428AC2-015 C
Solar/Wind Helper
0.365
971599AH1-298 GEN
50/50
10.28
960861AF2-377 GEN
50/50
2.361
24729305KEY G2
50/50
6.792
970611AG2-400 GEN
Solar/Wind Harmer
1.14
270071AF1-092 GEN
Solar/Wind Harmer
0.935
970321AG2-212 GEN
Solar/Wind Harmer
0.887
270005AE1-210 C O1
Solar/Wind Harmer
6.381
276602WESTBROOK C
Solar/Wind Harmer
2.837
276645AC1-214 GEN1
Solar/Wind Harmer
1.672
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.583
24387305FR-4G C
Solar/Wind Harmer
4.536
24386605FR-22G C
Solar/Wind Harmer
3.024
24387005FR-3G C
Solar/Wind Harmer
2.994
942111AE2-223 GEN
Solar/Wind Harmer
8.986
960841AF2-375 GEN
Solar/Wind Helper
0.553
24729205KEY G1
50/50
6.679
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.927
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.196
270004AE1-209 GEN
Solar/Wind Harmer
6.381
274872LEEDK;1U
Solar/Wind Harmer
0.18
270180AB1-006 GEN1
Solar/Wind Harmer
9.491
24791305MDL-5G
Solar/Wind Harmer
3.34
959081AF2-199 GEN
Solar/Wind Harmer
0.403
971475AH1-234 GEN
Solar/Wind Harmer
0.892
276646AC1-214 GEN2
Solar/Wind Harmer
1.672
24386205FR-12G C
Solar/Wind Harmer
3.157
276726Z2-087_GEN
Solar/Wind Harmer
9.984
944201AF1-088_MTX
Adder
55.858
957141AF2-008_MTX
Adder
27.929
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.201
WECLTFEXP_WEC->PJM
CLTF
2.632
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.501
NYPJM->LTFIMP_NY
CLTF
1.242
MECLTFEXP_MEC->PJM
CLTF
9.671
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.626
LGEELTFEXP_LGEE->PJM
CLTF
1.821
LAGNLTFEXP_LAGN->PJM
CLTF
5.9
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.085
TVALTFEXP_TVA->PJM
CLTF
2.406
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.398

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2267.59
MW Contribution:2.11
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
68.971
247620Y3-023
50/50
0.466
965041AG1-368 GEN
Solar/Wind Harmer
0.706
270191TR4_S_V150
Solar/Wind Harmer
6.54
965101AG1-375 GEN
Solar/Wind Harmer
0.511
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.373
965431AG1-411 GEN
50/50
45.479
24727205RPMNG3
50/50
68.971
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
0.972
270246TR4_N_V150
Solar/Wind Harmer
1.186
24695305TIMB G C
Solar/Wind Harmer
9.919
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.422
965031AG1-367 GEN
Solar/Wind Harmer
0.414
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
0.401
961011AF2-392 GEN
Solar/Wind Harmer
12.249
270227U2-072_GEN3
Solar/Wind Helper
0.133
270228U2-072_GEN4
Solar/Wind Helper
0.133
960971AF2-388 GEN
Solar/Wind Harmer
16.413
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
0.97
961051AF2-396 GEN
Solar/Wind Harmer
7.761
270599AE1-208 GEN
Solar/Wind Harmer
0.373
970245AG2-165 GEN
Solar/Wind Harmer
0.894
972231SS25-0005
Solar/Wind Harmer
0.71
274862TOP CROP ;2U
Solar/Wind Harmer
6.862
970921AG2-575 GEN
Solar/Wind Harmer
0.413
970921AG2-575 GEN
Solar/Wind Harmer
1.652
274879MINONK ;1U
Solar/Wind Harmer
9.667
971411AH1-196 GEN
Solar/Wind Harmer
0.613
274855GSG-6 ;RU
Solar/Wind Harmer
5.182
24386405FR-21G C
Solar/Wind Harmer
3.045
971617AH1-308 GEN
Solar/Wind Harmer
5.201
943021AE2-325 GEN
Solar/Wind Harmer
2.992
958011AF2-095 GEN
Solar/Wind Harmer
0.623
971573AH1-285 GEN
Solar/Wind Harmer
0.361
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.621
942991AE2-321 GEN
Solar/Wind Harmer
0.41
971333AH1-146 GEN
Solar/Wind Harmer
0.816
24697905MDL-4G C
Solar/Wind Harmer
3.365
970819AG2-516 GEN
Solar/Wind Harmer
0.483
964611AG1-324 GEN
Solar/Wind Harmer
0.357
270201AC2-176 GEN
Solar/Wind Harmer
6.697
274851PROVIDENC;RU
Solar/Wind Harmer
3.718
274878BISHOP HL;2U
Solar/Wind Harmer
4.523
24699105WLD G1 C
Solar/Wind Harmer
5.025
270499AE1-146 GEN
Solar/Wind Helper
0.511
959331AF2-224 GEN
Solar/Wind Harmer
1.15
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.09
276843GEN-1.7
Solar/Wind Harmer
0.714
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.948
276882AE2-255 GEN
Solar/Wind Harmer
4.361
960441AF2-335 GEN
Solar/Wind Harmer
0.407
270223U2-072_GEN1
Solar/Wind Helper
0.133
966831AG1-554 GEN
Solar/Wind Helper
0.265
274854TWINGROVE;U2
Solar/Wind Harmer
6.054
944531AF1-118 GEN
Solar/Wind Harmer
2.062
274887GEN-1.85
Solar/Wind Harmer
8.065
970707AG2-453 GEN
Solar/Wind Harmer
1.203
970833AG2-524 GEN
Solar/Wind Harmer
3.74
958481AF2-142 GEN
Solar/Wind Harmer
0.629
276868AE1-113 GEN
Solar/Wind Harmer
13.822
971675AH1-338 GEN
Solar/Wind Harmer
0.735
960791AF2-370 GEN
Solar/Wind Harmer
1.628
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.395
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.371
270224U2-072_GEN2
Solar/Wind Helper
0.133
270391AF1-285 GEN3
Solar/Wind Helper
0.267
241847AF2-150_GEN
Solar/Wind Helper
0.239
970583AG2-370 GEN
50/50
2.823
970031AG2-029 GEN
Solar/Wind Harmer
2.112
270247TR4_N_V136
Solar/Wind Harmer
1.186
965051AG1-369 GEN
Solar/Wind Harmer
0.301
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.088
939401AE1-172 GEN
Solar/Wind Harmer
16.42
276876AE1-163_GEN2
Solar/Wind Harmer
9.109
274857EASY ROAD;U1
Solar/Wind Harmer
6.231
961761AG1-017 GEN
Solar/Wind Harmer
0.391
276656WTG2_EQ
Solar/Wind Harmer
0.882
941731AE2-173 GEN
Solar/Wind Harmer
3.866
270462AD2-086
Solar/Wind Helper
1.688
270317AD1-130_GEN
Solar/Wind Helper
1.101
270287AF1-227 GEN3
Solar/Wind Helper
0.313
971917AH1-482 GEN
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
970115AG2-085 GEN
Solar/Wind Harmer
0.163
276872AE1-163_GEN1
Solar/Wind Harmer
9.109
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.701
971067AG2-660 GEN
Solar/Wind Harmer
1.622
276741O09 GEN1
Solar/Wind Harmer
4.827
276655WTG1_EQ
Solar/Wind Harmer
6.657
270578AF1-285 GEN2
Solar/Wind Helper
0.267
247522W1-056 GEN
Solar/Wind Helper
1.806
270286AF1-227 GEN2
Solar/Wind Helper
0.313
961961AG1-039 GEN
Solar/Wind Helper
0.152
241960AC2-195 GEN
Solar/Wind Helper
0.26
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.894
970517AG2-330 GEN
Solar/Wind Harmer
13.95
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.467
958821AF2-173 GEN
Solar/Wind Harmer
0.58
962781AG1-127 GEN
Solar/Wind Harmer
0.393
971335AH1-147 GEN
Solar/Wind Harmer
0.816
24697605MDL-3G C
Solar/Wind Harmer
5.096
270181AB1-006 GEN2
Solar/Wind Harmer
0.634
971171AH1-044 GEN
Solar/Wind Harmer
0.811
926823AC1-168 GEN
Solar/Wind Harmer
4.923
24385905FR-11G C
Solar/Wind Harmer
5.987
276782AC1-033 GEN
Solar/Wind Harmer
5.11
24725505WLD G2 C
Solar/Wind Harmer
5.056
946321AF1-296 GEN
Solar/Wind Harmer
11.381
960611AF2-352 GEN
Solar/Wind Harmer
0.992
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.888
945111AF1-176 GEN
Solar/Wind Harmer
4.84
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.472
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.926
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.24
970825AG2-519 GEN
Solar/Wind Harmer
0.448
970825AG2-519 GEN
Solar/Wind Harmer
1.72
970571AG2-364 GEN
Solar/Wind Harmer
0.803
971681AH1-341 GEN
Solar/Wind Harmer
0.599
938861AE1-114 GEN
Solar/Wind Harmer
9.335
276603SUBLETTE C
Solar/Wind Harmer
1.356
253378AE2-206_GEN
Solar/Wind Helper
0.312
965021AG1-366 GEN
Solar/Wind Harmer
4.602
958861AF2-177 GEN
Solar/Wind Harmer
15.941
945371AF1-202 GEN
Solar/Wind Harmer
7.519
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.242
270594AE1-207 GEN
Solar/Wind Harmer
0.66
270032AE2-172
Solar/Wind Harmer
3.298
971997AH1-543 GEN
Solar/Wind Harmer
0.645
276863AD2-134 GEN
Solar/Wind Harmer
2.505
274863CRW1-WTG
Solar/Wind Harmer
7.688
276889AE2-281 GEN
Solar/Wind Harmer
2.603
24691005MDL-2G C
Solar/Wind Harmer
5.104
274856ECOGROVE ;U1
Solar/Wind Harmer
4.705
971549AH1-272 GEN
Solar/Wind Harmer
0.738
276158O29GEN2
Solar/Wind Harmer
5.735
276708O09 GEN2
Solar/Wind Harmer
4.827
246937BC-WTG2
Solar/Wind Helper
5.496
270485AE1-090_GEN
Solar/Wind Helper
0.147
276820AF1-078_GEN
Solar/Wind Helper
0.141
24727105RPMNG2
50/50
68.971
965651AG1-433 GEN
Solar/Wind Harmer
8.207
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.896
943121AE2-341 GEN
Solar/Wind Harmer
0.633
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.55
957471AF2-041 GEN
Solar/Wind Harmer
1.217
274848CAMPGROVE;RU
Solar/Wind Harmer
7.073
959341AF2-225 GEN
Solar/Wind Harmer
0.58
957201AF2-014 GEN
Solar/Wind Helper
3.911
270284AF1-227 GEN1
Solar/Wind Helper
0.847
270428AC2-015 C
Solar/Wind Helper
0.344
970615AG2-402 GEN
50/50
4.602
24729405KEY G3
50/50
6.868
24729505KEY G4
50/50
6.754
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.442
270505AE1-170 C O1
Solar/Wind Harmer
0.728
274888KELLY CRK;1U
Solar/Wind Harmer
8.779
970941AG2-585 GEN
Solar/Wind Harmer
0.541
971605AH1-302 GEN
Solar/Wind Harmer
6.341
276805AD2-038 GEN
Solar/Wind Harmer
7.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.67
276861AD2-134 GEN
Solar/Wind Harmer
2.505
274864CRW2-WTG
Solar/Wind Harmer
7.688
970569AG2-363 GEN
Solar/Wind Harmer
1.205
274858EASY ROAD;U2
Solar/Wind Harmer
6.231
276157O29GEN1
Solar/Wind Harmer
5.735
957751AF2-069 GEN
Solar/Wind Harmer
0.514
939741AE1-205 GEN
Solar/Wind Harmer
0.773
246938BC-WTG3
Solar/Wind Helper
5.433
246936BC-WTG1
Solar/Wind Helper
5.496
971599AH1-298 GEN
50/50
10.386
960861AF2-377 GEN
50/50
2.413
24729305KEY G2
50/50
6.868
970611AG2-400 GEN
Solar/Wind Harmer
1.15
270071AF1-092 GEN
Solar/Wind Harmer
0.944
970321AG2-212 GEN
Solar/Wind Harmer
0.894
270005AE1-210 C O1
Solar/Wind Harmer
6.463
276602WESTBROOK C
Solar/Wind Harmer
2.858
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.594
276645AC1-214 GEN1
Solar/Wind Harmer
1.683
24387305FR-4G C
Solar/Wind Harmer
4.568
24386605FR-22G C
Solar/Wind Harmer
3.045
24387005FR-3G C
Solar/Wind Harmer
3.015
942111AE2-223 GEN
Solar/Wind Harmer
9.047
960841AF2-375 GEN
Solar/Wind Helper
0.529
24729205KEY G1
50/50
6.754
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.936
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.261
270004AE1-209 GEN
Solar/Wind Harmer
6.463
274872LEEDK;1U
Solar/Wind Harmer
0.181
270180AB1-006 GEN1
Solar/Wind Harmer
9.562
24791305MDL-5G
Solar/Wind Harmer
3.365
959081AF2-199 GEN
Solar/Wind Harmer
0.406
971475AH1-234 GEN
Solar/Wind Harmer
0.898
276646AC1-214 GEN2
Solar/Wind Harmer
1.683
24386205FR-12G C
Solar/Wind Harmer
3.179
276726Z2-087_GEN
Solar/Wind Harmer
10.052
942871AE2-306 GEN
Solar/Wind Helper
0.2
945641AF1-229 GEN
Solar/Wind Helper
0.422
270541AE2-072 C
Solar/Wind Helper
0.42
970521AG2-332 GEN
50/50
10.877
247521TR3_G114
Solar/Wind Harmer
8.771
276806AD2-047 C O1
Solar/Wind Harmer
13.32
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.573
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.5
971341AH1-150 GEN
Solar/Wind Harmer
0.811
270302AB2-170 GEN
Solar/Wind Helper
1.101
270231U2-072_GEN5
Solar/Wind Helper
0.133
270471AD2-092_GEN
Solar/Wind Helper
0.383
965421AG1-410 GEN
Solar/Wind Harmer
6.822
972181SS23-001
Solar/Wind Harmer
0.444
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.311
970289AG2-191 GEN
Solar/Wind Harmer
0.079
24755605MDL-5G
Solar/Wind Harmer
3.365
959091AF2-200 GEN
Solar/Wind Harmer
0.811
946031AF1-268 GEN
Solar/Wind Harmer
0.329
274849CRESCENT ;1U
Solar/Wind Harmer
2.569
274877BISHOP HL;1U
Solar/Wind Harmer
4.523
270349AD2-093_GEN
Solar/Wind Helper
0.383
944201AF1-088_MTX
Adder
55.87
957141AF2-008_MTX
Adder
27.935
990497J1323
External Queue
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.505
NYPJM->LTFIMP_NY
CLTF
1.226
TVALTFEXP_TVA->PJM
CLTF
2.31
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.901
WECLTFEXP_WEC->PJM
CLTF
2.651
LAGNLTFEXP_LAGN->PJM
CLTF
5.747
AH1-155LTFEXP_AH1-155->PJM
LTF
0.251
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.599
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.154
LGEELTFEXP_LGEE->PJM
CLTF
1.819
MECLTFEXP_MEC->PJM
CLTF
9.7
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2267.56
MW Contribution:2.11
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
68.971
247620Y3-023
50/50
0.466
965041AG1-368 GEN
Solar/Wind Harmer
0.706
270191TR4_S_V150
Solar/Wind Harmer
6.54
965101AG1-375 GEN
Solar/Wind Harmer
0.511
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.373
971917AH1-482 GEN
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
970115AG2-085 GEN
Solar/Wind Harmer
0.163
276872AE1-163_GEN1
Solar/Wind Harmer
9.109
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.701
971067AG2-660 GEN
Solar/Wind Harmer
1.622
276741O09 GEN1
Solar/Wind Harmer
4.827
276655WTG1_EQ
Solar/Wind Harmer
6.657
270578AF1-285 GEN2
Solar/Wind Helper
0.267
247522W1-056 GEN
Solar/Wind Helper
1.806
270286AF1-227 GEN2
Solar/Wind Helper
0.313
961961AG1-039 GEN
Solar/Wind Helper
0.152
241960AC2-195 GEN
Solar/Wind Helper
0.26
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.894
970517AG2-330 GEN
Solar/Wind Harmer
13.95
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.467
958821AF2-173 GEN
Solar/Wind Harmer
0.58
962781AG1-127 GEN
Solar/Wind Harmer
0.393
971335AH1-147 GEN
Solar/Wind Harmer
0.816
24697605MDL-3G C
Solar/Wind Harmer
5.096
270181AB1-006 GEN2
Solar/Wind Harmer
0.634
971171AH1-044 GEN
Solar/Wind Harmer
0.811
926823AC1-168 GEN
Solar/Wind Harmer
4.923
24385905FR-11G C
Solar/Wind Harmer
5.987
276782AC1-033 GEN
Solar/Wind Harmer
5.11
24725505WLD G2 C
Solar/Wind Harmer
5.056
946321AF1-296 GEN
Solar/Wind Harmer
11.381
960611AF2-352 GEN
Solar/Wind Harmer
0.992
970583AG2-370 GEN
50/50
2.823
970031AG2-029 GEN
Solar/Wind Harmer
2.112
270247TR4_N_V136
Solar/Wind Harmer
1.186
965051AG1-369 GEN
Solar/Wind Harmer
0.301
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.088
939401AE1-172 GEN
Solar/Wind Harmer
16.42
276876AE1-163_GEN2
Solar/Wind Harmer
9.109
274857EASY ROAD;U1
Solar/Wind Harmer
6.231
961761AG1-017 GEN
Solar/Wind Harmer
0.391
276656WTG2_EQ
Solar/Wind Harmer
0.882
941731AE2-173 GEN
Solar/Wind Harmer
3.866
270462AD2-086
Solar/Wind Helper
1.688
270317AD1-130_GEN
Solar/Wind Helper
1.101
270287AF1-227 GEN3
Solar/Wind Helper
0.313
970615AG2-402 GEN
50/50
4.602
24729405KEY G3
50/50
6.868
24729505KEY G4
50/50
6.754
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.442
270505AE1-170 C O1
Solar/Wind Harmer
0.728
274888KELLY CRK;1U
Solar/Wind Harmer
8.779
970941AG2-585 GEN
Solar/Wind Harmer
0.541
971605AH1-302 GEN
Solar/Wind Harmer
6.341
276805AD2-038 GEN
Solar/Wind Harmer
7.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.67
276861AD2-134 GEN
Solar/Wind Harmer
2.505
274864CRW2-WTG
Solar/Wind Harmer
7.688
970569AG2-363 GEN
Solar/Wind Harmer
1.205
274858EASY ROAD;U2
Solar/Wind Harmer
6.231
276157O29GEN1
Solar/Wind Harmer
5.735
957751AF2-069 GEN
Solar/Wind Harmer
0.514
939741AE1-205 GEN
Solar/Wind Harmer
0.773
246938BC-WTG3
Solar/Wind Helper
5.433
246936BC-WTG1
Solar/Wind Helper
5.496
965431AG1-411 GEN
50/50
45.479
24727205RPMNG3
50/50
68.971
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
0.972
270246TR4_N_V150
Solar/Wind Harmer
1.186
24695305TIMB G C
Solar/Wind Harmer
9.919
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.422
965031AG1-367 GEN
Solar/Wind Harmer
0.414
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
0.401
961011AF2-392 GEN
Solar/Wind Harmer
12.249
270227U2-072_GEN3
Solar/Wind Helper
0.133
270228U2-072_GEN4
Solar/Wind Helper
0.133
276820AF1-078_GEN
Solar/Wind Helper
0.141
965021AG1-366 GEN
Solar/Wind Harmer
4.602
958861AF2-177 GEN
Solar/Wind Harmer
15.941
945371AF1-202 GEN
Solar/Wind Harmer
7.519
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.242
270594AE1-207 GEN
Solar/Wind Harmer
0.66
270032AE2-172
Solar/Wind Harmer
3.298
971997AH1-543 GEN
Solar/Wind Harmer
0.645
276863AD2-134 GEN
Solar/Wind Harmer
2.505
274863CRW1-WTG
Solar/Wind Harmer
7.688
276889AE2-281 GEN
Solar/Wind Harmer
2.603
24691005MDL-2G C
Solar/Wind Harmer
5.104
274856ECOGROVE ;U1
Solar/Wind Harmer
4.705
971549AH1-272 GEN
Solar/Wind Harmer
0.738
276158O29GEN2
Solar/Wind Harmer
5.735
276708O09 GEN2
Solar/Wind Harmer
4.827
246937BC-WTG2
Solar/Wind Helper
5.496
270485AE1-090_GEN
Solar/Wind Helper
0.147
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.888
945111AF1-176 GEN
Solar/Wind Harmer
4.84
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.472
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.926
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.24
970825AG2-519 GEN
Solar/Wind Harmer
0.448
970825AG2-519 GEN
Solar/Wind Harmer
1.72
970571AG2-364 GEN
Solar/Wind Harmer
0.803
971681AH1-341 GEN
Solar/Wind Harmer
0.599
938861AE1-114 GEN
Solar/Wind Harmer
9.335
276603SUBLETTE C
Solar/Wind Harmer
1.356
253378AE2-206_GEN
Solar/Wind Helper
0.312
971599AH1-298 GEN
50/50
10.386
960861AF2-377 GEN
50/50
2.413
24729305KEY G2
50/50
6.868
970611AG2-400 GEN
Solar/Wind Harmer
1.15
270071AF1-092 GEN
Solar/Wind Harmer
0.944
970321AG2-212 GEN
Solar/Wind Harmer
0.894
270005AE1-210 C O1
Solar/Wind Harmer
6.463
276602WESTBROOK C
Solar/Wind Harmer
2.858
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.594
276645AC1-214 GEN1
Solar/Wind Harmer
1.683
24387305FR-4G C
Solar/Wind Harmer
4.568
24386605FR-22G C
Solar/Wind Harmer
3.045
24387005FR-3G C
Solar/Wind Harmer
3.015
942111AE2-223 GEN
Solar/Wind Harmer
9.047
960841AF2-375 GEN
Solar/Wind Helper
0.529
944531AF1-118 GEN
Solar/Wind Harmer
2.062
274887GEN-1.85
Solar/Wind Harmer
8.065
970707AG2-453 GEN
Solar/Wind Harmer
1.203
970833AG2-524 GEN
Solar/Wind Harmer
3.74
958481AF2-142 GEN
Solar/Wind Harmer
0.629
276868AE1-113 GEN
Solar/Wind Harmer
13.822
971675AH1-338 GEN
Solar/Wind Harmer
0.735
960791AF2-370 GEN
Solar/Wind Harmer
1.628
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.395
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.371
270224U2-072_GEN2
Solar/Wind Helper
0.133
270391AF1-285 GEN3
Solar/Wind Helper
0.267
241847AF2-150_GEN
Solar/Wind Helper
0.239
971617AH1-308 GEN
Solar/Wind Harmer
5.201
943021AE2-325 GEN
Solar/Wind Harmer
2.992
958011AF2-095 GEN
Solar/Wind Harmer
0.623
971573AH1-285 GEN
Solar/Wind Harmer
0.361
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.621
942991AE2-321 GEN
Solar/Wind Harmer
0.41
971333AH1-146 GEN
Solar/Wind Harmer
0.816
24697905MDL-4G C
Solar/Wind Harmer
3.365
970819AG2-516 GEN
Solar/Wind Harmer
0.483
964611AG1-324 GEN
Solar/Wind Harmer
0.357
270201AC2-176 GEN
Solar/Wind Harmer
6.697
274851PROVIDENC;RU
Solar/Wind Harmer
3.718
274878BISHOP HL;2U
Solar/Wind Harmer
4.523
24699105WLD G1 C
Solar/Wind Harmer
5.025
270499AE1-146 GEN
Solar/Wind Helper
0.511
24729205KEY G1
50/50
6.754
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.936
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.261
270004AE1-209 GEN
Solar/Wind Harmer
6.463
274872LEEDK;1U
Solar/Wind Harmer
0.181
270180AB1-006 GEN1
Solar/Wind Harmer
9.562
24791305MDL-5G
Solar/Wind Harmer
3.365
959081AF2-199 GEN
Solar/Wind Harmer
0.406
971475AH1-234 GEN
Solar/Wind Harmer
0.898
276646AC1-214 GEN2
Solar/Wind Harmer
1.683
24386205FR-12G C
Solar/Wind Harmer
3.179
276726Z2-087_GEN
Solar/Wind Harmer
10.052
965421AG1-410 GEN
Solar/Wind Harmer
6.822
972181SS23-001
Solar/Wind Harmer
0.444
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.311
970289AG2-191 GEN
Solar/Wind Harmer
0.079
24755605MDL-5G
Solar/Wind Harmer
3.365
959091AF2-200 GEN
Solar/Wind Harmer
0.811
946031AF1-268 GEN
Solar/Wind Harmer
0.329
274849CRESCENT ;1U
Solar/Wind Harmer
2.569
274877BISHOP HL;1U
Solar/Wind Harmer
4.523
270349AD2-093_GEN
Solar/Wind Helper
0.383
24727105RPMNG2
50/50
68.971
965651AG1-433 GEN
Solar/Wind Harmer
8.207
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.896
943121AE2-341 GEN
Solar/Wind Harmer
0.633
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.55
957471AF2-041 GEN
Solar/Wind Harmer
1.217
274848CAMPGROVE;RU
Solar/Wind Harmer
7.073
959341AF2-225 GEN
Solar/Wind Harmer
0.58
957201AF2-014 GEN
Solar/Wind Helper
3.911
270284AF1-227 GEN1
Solar/Wind Helper
0.847
270428AC2-015 C
Solar/Wind Helper
0.344
970521AG2-332 GEN
50/50
10.877
247521TR3_G114
Solar/Wind Harmer
8.771
276806AD2-047 C O1
Solar/Wind Harmer
13.32
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.573
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.5
971341AH1-150 GEN
Solar/Wind Harmer
0.811
270302AB2-170 GEN
Solar/Wind Helper
1.101
270231U2-072_GEN5
Solar/Wind Helper
0.133
270471AD2-092_GEN
Solar/Wind Helper
0.383
960971AF2-388 GEN
Solar/Wind Harmer
16.413
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
0.97
961051AF2-396 GEN
Solar/Wind Harmer
7.761
270599AE1-208 GEN
Solar/Wind Harmer
0.373
970245AG2-165 GEN
Solar/Wind Harmer
0.894
972231SS25-0005
Solar/Wind Harmer
0.71
274862TOP CROP ;2U
Solar/Wind Harmer
6.862
970921AG2-575 GEN
Solar/Wind Harmer
0.413
970921AG2-575 GEN
Solar/Wind Harmer
1.652
274879MINONK ;1U
Solar/Wind Harmer
9.667
971411AH1-196 GEN
Solar/Wind Harmer
0.613
274855GSG-6 ;RU
Solar/Wind Harmer
5.182
24386405FR-21G C
Solar/Wind Harmer
3.045
942871AE2-306 GEN
Solar/Wind Helper
0.2
945641AF1-229 GEN
Solar/Wind Helper
0.422
270541AE2-072 C
Solar/Wind Helper
0.42
959331AF2-224 GEN
Solar/Wind Harmer
1.15
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.09
276843GEN-1.7
Solar/Wind Harmer
0.714
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.948
276882AE2-255 GEN
Solar/Wind Harmer
4.361
960441AF2-335 GEN
Solar/Wind Harmer
0.407
270223U2-072_GEN1
Solar/Wind Helper
0.133
966831AG1-554 GEN
Solar/Wind Helper
0.265
274854TWINGROVE;U2
Solar/Wind Harmer
6.054
944201AF1-088_MTX
Adder
55.87
957141AF2-008_MTX
Adder
27.935
990497J1323
External Queue
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.599
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.154
LGEELTFEXP_LGEE->PJM
CLTF
1.819
MECLTFEXP_MEC->PJM
CLTF
9.7
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.901
WECLTFEXP_WEC->PJM
CLTF
2.651
LAGNLTFEXP_LAGN->PJM
CLTF
5.747
AH1-155LTFEXP_AH1-155->PJM
LTF
0.251
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.505
NYPJM->LTFIMP_NY
CLTF
1.226
TVALTFEXP_TVA->PJM
CLTF
2.31
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.037

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.94 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2262.15
MW Contribution:2.05
Bus #Bus NameTypeMW Contribution
971617AH1-308 GEN
Solar/Wind Harmer
4.999
943021AE2-325 GEN
Solar/Wind Harmer
2.884
958011AF2-095 GEN
Solar/Wind Harmer
0.601
971573AH1-285 GEN
Solar/Wind Harmer
0.349
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
942991AE2-321 GEN
Solar/Wind Harmer
0.396
971333AH1-146 GEN
Solar/Wind Harmer
0.788
24697905MDL-4G C
Solar/Wind Harmer
3.247
970819AG2-516 GEN
Solar/Wind Harmer
0.466
274851PROVIDENC;RU
Solar/Wind Harmer
3.588
964611AG1-324 GEN
Solar/Wind Harmer
0.34
270201AC2-176 GEN
Solar/Wind Harmer
6.374
274878BISHOP HL;2U
Solar/Wind Harmer
4.366
24699105WLD G1 C
Solar/Wind Harmer
4.824
965931AG1-462 GEN
Solar/Wind Harmer
0.935
270499AE1-146 GEN
Solar/Wind Helper
0.547
959331AF2-224 GEN
Solar/Wind Harmer
1.126
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.913
276843GEN-1.7
Solar/Wind Harmer
0.69
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.537
276882AE2-255 GEN
Solar/Wind Harmer
4.21
960441AF2-335 GEN
Solar/Wind Harmer
0.39
270223U2-072_GEN1
Solar/Wind Helper
0.148
966831AG1-554 GEN
Solar/Wind Helper
0.282
274854TWINGROVE;U2
Solar/Wind Harmer
5.038
944531AF1-118 GEN
Solar/Wind Harmer
1.998
274887GEN-1.85
Solar/Wind Harmer
7.789
970707AG2-453 GEN
Solar/Wind Harmer
1.162
970833AG2-524 GEN
Solar/Wind Harmer
3.611
958481AF2-142 GEN
Solar/Wind Harmer
0.607
276868AE1-113 GEN
Solar/Wind Harmer
13.346
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
960791AF2-370 GEN
Solar/Wind Harmer
1.562
276903AD2-071 C
Solar/Wind Harmer
0.38
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.04
270224U2-072_GEN2
Solar/Wind Helper
0.148
270391AF1-285 GEN3
Solar/Wind Helper
0.296
241847AF2-150_GEN
Solar/Wind Helper
0.259
970583AG2-370 GEN
50/50
2.718
970031AG2-029 GEN
Solar/Wind Harmer
2.053
270247TR4_N_V136
Solar/Wind Harmer
1.13
965051AG1-369 GEN
Solar/Wind Harmer
0.287
960591AF2-350 GEN
Solar/Wind Harmer
0.418
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
7.81
939401AE1-172 GEN
Solar/Wind Harmer
15.852
276876AE1-163_GEN2
Solar/Wind Harmer
8.794
274857EASY ROAD;U1
Solar/Wind Harmer
6.016
961761AG1-017 GEN
Solar/Wind Harmer
0.372
276656WTG2_EQ
Solar/Wind Harmer
0.85
941731AE2-173 GEN
Solar/Wind Harmer
3.73
270462AD2-086
Solar/Wind Helper
1.844
270317AD1-130_GEN
Solar/Wind Helper
1.203
270287AF1-227 GEN3
Solar/Wind Helper
0.376
24727005RPMNG1
50/50
67.91
247620Y3-023
50/50
0.451
965041AG1-368 GEN
Solar/Wind Harmer
0.679
270191TR4_S_V150
Solar/Wind Harmer
6.235
965101AG1-375 GEN
Solar/Wind Harmer
0.494
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.359
971917AH1-482 GEN
Solar/Wind Harmer
6.492
276691AA1-018 GEN1
Solar/Wind Harmer
0.436
276872AE1-163_GEN1
Solar/Wind Harmer
8.794
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.326
971067AG2-660 GEN
Solar/Wind Harmer
1.567
970115AG2-085 GEN
Solar/Wind Harmer
0.156
276741O09 GEN1
Solar/Wind Harmer
4.66
276655WTG1_EQ
Solar/Wind Harmer
6.423
270578AF1-285 GEN2
Solar/Wind Helper
0.296
270286AF1-227 GEN2
Solar/Wind Helper
0.376
247522W1-056 GEN
Solar/Wind Helper
1.925
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.292
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.864
970517AG2-330 GEN
Solar/Wind Harmer
13.48
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
958821AF2-173 GEN
Solar/Wind Harmer
0.557
971335AH1-147 GEN
Solar/Wind Harmer
0.788
24697605MDL-3G C
Solar/Wind Harmer
4.918
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.783
926823AC1-168 GEN
Solar/Wind Harmer
4.753
24385905FR-11G C
Solar/Wind Harmer
5.774
276782AC1-033 GEN
Solar/Wind Harmer
4.932
24725505WLD G2 C
Solar/Wind Harmer
4.854
946321AF1-296 GEN
Solar/Wind Harmer
10.986
958581AF2-149 GEN
Solar/Wind Helper
0.21
960611AF2-352 GEN
Solar/Wind Harmer
0.826
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.857
945111AF1-176 GEN
Solar/Wind Harmer
4.67
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.456
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
42.42
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.232
970571AG2-364 GEN
Solar/Wind Harmer
0.776
970825AG2-519 GEN
Solar/Wind Harmer
0.43
970825AG2-519 GEN
Solar/Wind Harmer
1.65
971681AH1-341 GEN
Solar/Wind Harmer
0.578
938861AE1-114 GEN
Solar/Wind Harmer
9.013
276603SUBLETTE C
Solar/Wind Harmer
1.309
253378AE2-206_GEN
Solar/Wind Helper
0.35
965021AG1-366 GEN
Solar/Wind Harmer
4.505
958861AF2-177 GEN
Solar/Wind Harmer
15.401
945371AF1-202 GEN
Solar/Wind Harmer
7.254
276893AG1-478 C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.199
957841AF2-078 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.634
270032AE2-172
Solar/Wind Harmer
3.17
971997AH1-543 GEN
Solar/Wind Harmer
0.623
276863AD2-134 GEN
Solar/Wind Harmer
2.419
274863CRW1-WTG
Solar/Wind Harmer
7.421
276889AE2-281 GEN
Solar/Wind Harmer
2.513
24691005MDL-2G C
Solar/Wind Harmer
4.926
274856ECOGROVE ;U1
Solar/Wind Harmer
4.543
971549AH1-272 GEN
Solar/Wind Harmer
0.704
276158O29GEN2
Solar/Wind Harmer
5.536
276708O09 GEN2
Solar/Wind Harmer
4.66
246937BC-WTG2
Solar/Wind Helper
5.567
270485AE1-090_GEN
Solar/Wind Helper
0.16
965431AG1-411 GEN
50/50
44.816
24727205RPMNG3
50/50
67.91
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.942
270246TR4_N_V150
Solar/Wind Harmer
1.13
24695305TIMB G C
Solar/Wind Harmer
9.393
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.408
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.398
971343AH1-151 GEN
Solar/Wind Harmer
0.783
970169AG2-114 GEN
Solar/Wind Harmer
0.387
961011AF2-392 GEN
Solar/Wind Harmer
11.826
270227U2-072_GEN3
Solar/Wind Helper
0.148
270228U2-072_GEN4
Solar/Wind Helper
0.148
276820AF1-078_GEN
Solar/Wind Helper
0.158
24727105RPMNG2
50/50
67.91
965651AG1-433 GEN
Solar/Wind Harmer
7.934
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.557
943121AE2-341 GEN
Solar/Wind Harmer
0.611
970291AG2-192 GEN
Solar/Wind Harmer
0.052
970289AG2-191 GEN
Solar/Wind Harmer
0.529
957471AF2-041 GEN
Solar/Wind Harmer
1.175
274848CAMPGROVE;RU
Solar/Wind Harmer
6.827
970615AG2-402 GEN
50/50
4.505
24729405KEY G3
50/50
6.653
24729505KEY G4
50/50
6.542
270043AE2-236 GEN
Solar/Wind Harmer
0.362
971771AH1-392 GEN
Solar/Wind Harmer
0.427
270505AE1-170 C O1
Solar/Wind Harmer
0.702
274888KELLY CRK;1U
Solar/Wind Harmer
8.479
970941AG2-585 GEN
Solar/Wind Harmer
0.522
971605AH1-302 GEN
Solar/Wind Harmer
6.121
276805AD2-038 GEN
Solar/Wind Harmer
7.241
274850MENDOTA H;RU
Solar/Wind Harmer
3.544
276861AD2-134 GEN
Solar/Wind Harmer
2.419
274864CRW2-WTG
Solar/Wind Harmer
7.421
970569AG2-363 GEN
Solar/Wind Harmer
1.163
274858EASY ROAD;U2
Solar/Wind Harmer
6.016
276157O29GEN1
Solar/Wind Harmer
5.536
957751AF2-069 GEN
Solar/Wind Harmer
0.496
939741AE1-205 GEN
Solar/Wind Harmer
0.746
246938BC-WTG3
Solar/Wind Helper
5.504
246936BC-WTG1
Solar/Wind Helper
5.567
971599AH1-298 GEN
50/50
10.098
960861AF2-377 GEN
50/50
2.301
24729305KEY G2
50/50
6.653
970611AG2-400 GEN
Solar/Wind Harmer
1.126
270071AF1-092 GEN
Solar/Wind Harmer
0.917
970321AG2-212 GEN
Solar/Wind Harmer
0.864
270005AE1-210 C O1
Solar/Wind Harmer
6.21
276602WESTBROOK C
Solar/Wind Harmer
2.759
276645AC1-214 GEN1
Solar/Wind Harmer
1.624
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.566
24387305FR-4G C
Solar/Wind Harmer
4.405
24386605FR-22G C
Solar/Wind Harmer
2.937
24387005FR-3G C
Solar/Wind Harmer
2.908
942111AE2-223 GEN
Solar/Wind Harmer
8.728
960841AF2-375 GEN
Solar/Wind Helper
0.566
24729205KEY G1
50/50
6.542
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.904
960971AF2-388 GEN
Solar/Wind Harmer
15.869
970349AG2-230 GEN
Solar/Wind Harmer
0.705
971347AH1-153 GEN
Solar/Wind Harmer
0.705
961051AF2-396 GEN
Solar/Wind Harmer
0.936
961051AF2-396 GEN
Solar/Wind Harmer
7.484
270599AE1-208 GEN
Solar/Wind Harmer
0.359
970245AG2-165 GEN
Solar/Wind Harmer
0.864
972231SS25-0005
Solar/Wind Harmer
0.686
274862TOP CROP ;2U
Solar/Wind Harmer
6.626
970921AG2-575 GEN
Solar/Wind Harmer
0.399
970921AG2-575 GEN
Solar/Wind Harmer
1.595
274879MINONK ;1U
Solar/Wind Harmer
9.334
971411AH1-196 GEN
Solar/Wind Harmer
0.592
274855GSG-6 ;RU
Solar/Wind Harmer
5.004
24386405FR-21G C
Solar/Wind Harmer
2.937
942871AE2-306 GEN
Solar/Wind Helper
0.222
945641AF1-229 GEN
Solar/Wind Helper
0.452
270541AE2-072 C
Solar/Wind Helper
0.467
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
7.977
270004AE1-209 GEN
Solar/Wind Harmer
6.21
274872LEEDK;1U
Solar/Wind Harmer
0.175
270180AB1-006 GEN1
Solar/Wind Harmer
9.228
24791305MDL-5G
Solar/Wind Harmer
3.247
959081AF2-199 GEN
Solar/Wind Harmer
0.392
971475AH1-234 GEN
Solar/Wind Harmer
0.867
276646AC1-214 GEN2
Solar/Wind Harmer
1.624
24386205FR-12G C
Solar/Wind Harmer
3.066
276726Z2-087_GEN
Solar/Wind Harmer
9.698
959341AF2-225 GEN
Solar/Wind Harmer
0.56
957201AF2-014 GEN
Solar/Wind Helper
3.962
270284AF1-227 GEN1
Solar/Wind Helper
1.019
270428AC2-015 C
Solar/Wind Helper
0.368
253383AE2-342_GEN
Solar/Wind Helper
0.101
970521AG2-332 GEN
50/50
10.52
247521TR3_G114
Solar/Wind Harmer
8.362
276806AD2-047 C O1
Solar/Wind Harmer
12.864
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.313
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.481
971341AH1-150 GEN
Solar/Wind Harmer
0.783
270302AB2-170 GEN
Solar/Wind Helper
1.203
270231U2-072_GEN5
Solar/Wind Helper
0.148
270471AD2-092_GEN
Solar/Wind Helper
0.507
965421AG1-410 GEN
Solar/Wind Harmer
6.722
972181SS23-001
Solar/Wind Harmer
0.429
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.267
970289AG2-191 GEN
Solar/Wind Harmer
0.076
24755605MDL-5G
Solar/Wind Harmer
3.247
959091AF2-200 GEN
Solar/Wind Harmer
0.783
946031AF1-268 GEN
Solar/Wind Harmer
0.315
274849CRESCENT ;1U
Solar/Wind Harmer
2.48
274877BISHOP HL;1U
Solar/Wind Harmer
4.366
270349AD2-093_GEN
Solar/Wind Helper
0.507
944201AF1-088_MTX
Adder
53.676
957141AF2-008_MTX
Adder
26.838
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.277
LGEELTFEXP_LGEE->PJM
CLTF
1.703
LAGNLTFEXP_LAGN->PJM
CLTF
5.561
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.712
TVALTFEXP_TVA->PJM
CLTF
2.237
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.26
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.912
NYPJM->LTFIMP_NY
CLTF
1.178
MECLTFEXP_MEC->PJM
CLTF
9.361
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.562
WECLTFEXP_WEC->PJM
CLTF
2.559
SIGELTFEXP_SIGE->PJM
CLTF
0.191
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1    /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 970238 TO BUS 290599 CKT 1    /*AG2-162 TP   765.0 - 05JEFFRSN_RG 765.0
END
CONTINGENCY 'AEP_P4_#9456_06DEARB1 345_DC_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
CONTINGENCY 'AEP_P2-2_#9456_06DEARB1 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
243211 to 242933 ckt 1
290608 to 242928 ckt Z1
242933 to 965420 ckt 1
243233 to 249567 ckt 1
965420 to 246929 ckt 1

Light Load Analysis

The New Service Request AG2-029 was evaluated as a 300.0 MW injection

AG2-029 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 300.0 MW (300.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05WHIPPLEDTC-05DESOTO 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC101.75 %897.0B912.689.09
GD2AEP
05WHIPPLEDTC-05DESOTO 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC101.37 %897.0B909.269.11

Details for 05WHIPPLEDTC-05DESOTO 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05WHIPPLEDTC-05DESOTO 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.75 %
Rating:897.0 MVA
Rating Type:B
MVA to Mitigate:912.68
MW Contribution:9.09
Bus #Bus NameTypeMW Contribution
24379505HDWTR1G C
Solar/Wind Helper
7.878
24699105WLD G1 C
Solar/Wind Helper
1.957
24725505WLD G2 C
Solar/Wind Helper
1.957
270201AC2-176 GEN
Solar/Wind Helper
3.045
270209AC1-174_GEN
Solar/Wind Helper
3.501
270437AC2-090 C
Solar/Wind Helper
3.939
270383AD1-128 GEN
Solar/Wind Helper
5.126
270543AE2-219 C
Solar/Wind Helper
2.163
270043AE2-236 GEN
Solar/Wind Harmer
1.975
270356AE2-297 GEN
Solar/Wind Helper
3.396
270063AE2-323 C
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
3.241
270071AF1-092 GEN
Solar/Wind Harmer
4.518
926881AC1-175 GEN
Solar/Wind Helper
3.939
944031AF1-071 GEN
Solar/Wind Helper
0.32
970825AG2-519 GEN
50/50
Charging
4.61
270239V3-007_GEN1
Solar/Wind Helper
1.71
270240V3-007_GEN2
Solar/Wind Helper
6.168
247536S-71 GEN
Solar/Wind Helper
2.643
942081AE2-220 GEN
Solar/Wind Helper
4.924
944231AF1-091 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
-16.025
944541AF1-119 GEN
Solar/Wind Harmer
82.134
945371AF1-202 GEN
Solar/Wind Harmer
57.874
945581AF1-223 GEN
Solar/Wind Harmer
0.003
958711AF2-162 GEN
Solar/Wind Harmer
-3.606
959331AF2-224 GEN
Solar/Wind Harmer
3.541
960971AF2-388 GEN
Solar/Wind Harmer
85.035
961161AF2-407 GEN
50/50
Charging
30.06
961761AG1-017 GEN
Solar/Wind Helper
0.296
962031AG1-047 GEN
Solar/Wind Helper
2.342
970031AG2-029 GEN
Solar/Wind Harmer
9.088
970611AG2-400 GEN
Solar/Wind Harmer
3.541
964611AG1-324 GEN
Solar/Wind Helper
0.993
965011AG1-365 GEN
Solar/Wind Harmer
3.541
965021AG1-366 GEN
Solar/Wind Harmer
3.219
965041AG1-368 GEN
Solar/Wind Harmer
2.781
965651AG1-433 GEN
Solar/Wind Harmer
42.517
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.744
NYPJM->LTFIMP_NY
CLTF
0.408
GibsonPJM->LTFIMP_GIBSON
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.683
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.662
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.414
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.873
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.524
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
1.344
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
4.754
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
85.543

Details for 05WHIPPLEDTC-05DESOTO 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05WHIPPLEDTC-05DESOTO 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.37 %
Rating:897.0 MVA
Rating Type:B
MVA to Mitigate:909.26
MW Contribution:9.11
Bus #Bus NameTypeMW Contribution
24379505HDWTR1G C
Solar/Wind Helper
7.874
24699105WLD G1 C
Solar/Wind Helper
1.956
24725505WLD G2 C
Solar/Wind Helper
1.956
270201AC2-176 GEN
Solar/Wind Helper
3.041
270209AC1-174_GEN
Solar/Wind Helper
3.499
270437AC2-090 C
Solar/Wind Helper
3.937
270383AD1-128 GEN
Solar/Wind Helper
5.122
270543AE2-219 C
Solar/Wind Helper
2.16
270043AE2-236 GEN
Solar/Wind Harmer
1.979
270356AE2-297 GEN
Solar/Wind Helper
3.394
270063AE2-323 C
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
3.248
270071AF1-092 GEN
Solar/Wind Harmer
4.528
926881AC1-175 GEN
Solar/Wind Helper
3.937
944031AF1-071 GEN
Solar/Wind Helper
0.319
970825AG2-519 GEN
50/50
Charging
4.606
270239V3-007_GEN1
Solar/Wind Helper
1.709
270240V3-007_GEN2
Solar/Wind Helper
6.165
247536S-71 GEN
Solar/Wind Helper
2.639
942081AE2-220 GEN
Solar/Wind Helper
4.921
944231AF1-091 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
-16.028
944541AF1-119 GEN
Solar/Wind Harmer
82.148
945371AF1-202 GEN
Solar/Wind Harmer
57.882
945581AF1-223 GEN
Solar/Wind Harmer
0.003
958711AF2-162 GEN
Solar/Wind Harmer
-3.607
959331AF2-224 GEN
Solar/Wind Harmer
3.552
960971AF2-388 GEN
Solar/Wind Harmer
85.05
961161AF2-407 GEN
50/50
Charging
30.045
961761AG1-017 GEN
Solar/Wind Helper
0.296
962031AG1-047 GEN
Solar/Wind Helper
2.339
970031AG2-029 GEN
Solar/Wind Harmer
9.111
970611AG2-400 GEN
Solar/Wind Harmer
3.552
964611AG1-324 GEN
Solar/Wind Helper
0.992
965011AG1-365 GEN
Solar/Wind Harmer
3.552
965021AG1-366 GEN
Solar/Wind Harmer
3.229
965041AG1-368 GEN
Solar/Wind Harmer
2.795
965651AG1-433 GEN
Solar/Wind Harmer
42.525
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.838
NYPJM->LTFIMP_NY
CLTF
0.408
GibsonPJM->LTFIMP_GIBSON
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.683
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.677
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.424
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.887
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.526
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
1.341
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
4.762
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
85.198
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
288691 to 243218 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-087Sullivan 345kV #1Under Construction
AB1-088Sullivan 345kV #2Engineering & Procurement
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-049Gloucester Township 12kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-093Ormet 138kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-111Aurora 138kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-141Cook-East Elkhart 345kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-015Chatfield-Howard 138kVPartially in Service - Under Construction
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-103Beaver-Davis Besse 345 kV IEngineering & Procurement
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVUnder Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-176Groton 138 kV SolarIn Service
AE2-181Snyder 69kVUnder Construction
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-216Hardin Switch 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-276Sullivan 345kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-282East Fayette 138 kVIn Service
AE2-285Maysville 69 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVEngineering & Procurement
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-322Mark Center 69 kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-064Weston 69 kVUnder Construction
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-084Hartford-Almena 69 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-120East Fayette 2 138 kVIn Service
AF1-122Cardington-Liberty 69 kVSuspended
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVActive
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-205Napoleon Muni 138 kVSuspended
AF1-206East Fayette 138 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-004Beaver 345 kVEngineering & Procurement
AF2-005Beaver 138 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-103Haviland 138 kVIn Service
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-126Weston 69 kV IIActive
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-149Sharp Road 69 kVEngineering & Procurement
AF2-150Galion 138 kVUnder Construction
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-370Delaware-Royerton 138 kVActive
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-376Timber Switch 138 kVActive
AF2-377Logtown 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-389Kenzie Creek-Stone Lake 69 kVWithdrawn
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AF2-407Fall Creek 345 kVActive
AF2-408Fall Creek 138 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-017Jay 138 kVUnder Construction
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-039Galion 138 kV IIUnder Construction
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-109Valley 138 kVActive
AG1-118Sugar Grove-Waterman 138kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-297Hanna-Tanners Creek 345 kVActive
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Glendale-Stephensburg 69 kVActive
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-411Maddox Creek-RP Mone 345 kVActive
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-500Beaver 345 kVEngineering & Procurement
AG1-501Beaver 138 kVEngineering & Procurement
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-014Meadow Lake 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-109Fitchville-New London 69 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-332East Elkhart – Elcona Tap 138 kVActive
AG2-343Eugene - Dequine 345 kVActive
AG2-344Dequine 345 bkVActive
AG2-345Eugene - Dequine 345 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-370Tillman 138 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-402Allen 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-492Meadow Lake 345 kVActive
AG2-515Midway 345 kV IIIActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-562Elderberry 345 kVActive
AG2-564Sulphur Springs 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-582Flint Run 500 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-069Jerome – Mohicanville 69 kVActive
AH1-070Jerome – Mohicanville 69 kVActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-196Prairie 345 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-298Meridian 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-339West Crawford 69 kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-704Hannibal 138 kVActive
AH1-711Lemoyne 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-719Beverly 345 kVActive
AH1-735Richland 138 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
METC
RTEP ID / TO ID
(Pending) / METC_TC1_16078
Title
Perform sag mitigation on Allen Junction - Morocco 345kV line. New ratings will be 1861/2124 MVA.
Description
Perform sag mitigation on Allen Junction - Morocco 345kV line. New ratings will be 1861/2124 MVA.
Total Cost ($USD)
$625,000
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ITCT
RTEP ID / TO ID
(Pending) / ITCT_TC1_15164
Title
Reconductor ITCT section of Lallendorf-Monroe line. Post upgrade ratings will be 1677/2124.
Description
Reconductor ITCT section of Lallendorf-Monroe line. Post upgrade ratings will be 1677/2124.
Total Cost ($USD)
$43,500,000
Allocated Cost ($USD)
$0
Time Estimate
36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)

New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Study Pending
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-029 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
AEP(Pending) / AEP-TC2-18693Greentown 765 kV to Marysville 765 kV - Greenfield Line$57,344,152
AEP(Pending) / AEP-TC2-1865305MALIS 765.0 kV to 05VASSEL 765.0 kV ckt 1 - Replace Equipment$14,361,607
AEP(Pending) / AEP-TC2-1868605MADDOX 345.0 kV to 05E LIMA 345.0 kV ckt 1 - String the 2nd conductor$10,215,121
AEP(Pending) / AEP-TC2-1870005GUNN RD SW 345.0 kV to 05BOKESCRK 345.0 kV ckt 1- Rebuild$7,690,422
ATSI(Pending) / TC2-ATSI-020.dReconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line$5,835,961
ATSI(Pending) / TC2-ATSI-015.aReconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV$5,726,959
ATSI(Pending) / TC2-ATSI-002.dReconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends$3,726,804
AEPn7683Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA.$2,893,473
AEP(Pending) / AEP-TC2-18689AG1-410 TP 345.0 kV to 05MADDOX 345.0 kV ckt 1 - string the 2nd circuit$1,136,386
AEP(Pending) / AEP-TC2-1870705ALLEN 345.0 kV to 05RPMONE 345.0 kV ckt 1 - Replace Equipment$933,382
AEP(Pending) / AEP-TC2-1873305BOKESCRK 345kV to 05MARYSV 345kV ckt 1 - Reconductor$794,214
AEP(Pending) / AEP-TC2-1865905MARYSVL_RS 765.0 kV to 05MARYSV 765.0 kV ckt Z1 - Replace Equipment$782,187
AEP(Pending) / AEP-TC2-1873205RPMONE 345kV to AG1-410 TP 345kV ckt 1 - Replace Equipment$705,383
ATSI(Pending) / TC2-ATSI-015.cUpgrade (2) 3000A CBs at Davis Besse and (1) 3000A CB at Lemoyne$286,099
ATSI(Pending) / TC2-ATSI-002.gUpgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse$238,661
ATSI(Pending) / TC2-ATSI-015.iUpgrade (10) 3000A bus and line side disconnect switches at Davis Besse and Lemoyne (34624, A34604, D345:63A,63B,64D,64C,01N,01S,02W,02E)$189,671
ATSI(Pending) / TC2-ATSI-020.aUpgrade B185 and B182 circuit breakers at Beaver$158,348
ATSI(Pending) / TC2-ATSI-002.mUpgrade (7) 3000A disconnect switches (D34545:N,S, D3454:W,E, A34673, D34561C, and 34623)and (2) B34545 impedance relays at Bayshore and Davis Besse$116,491
ATSI(Pending) / TC2-ATSI-015.gUpgrade (2) B34501 and B34502 relay thermals at Lemoyne and (3) 34563 relay and meter thermals at Davis Besse$102,564
ATSI(Pending) / TC2-ATSI-015.dUpgrade (12) dual 1590 ACSR SCCIR at Davis Besse and Lemoyne$99,376
ATSI(Pending) / TC2-ATSI-015.fUpgrade the B34502 CB at Lemoyne$99,274
ATSI(Pending) / TC2-ATSI-020.bUpgrade (4) disconnect switches at Beaver (D186,184,181,183)$66,391
ATSI(Pending) / TC2-ATSI-015.bUpgrade (4) L300 wavetraps at Davis Besse and Lemoyne$51,429
ATSI(Pending) / TC2-ATSI-020.gUpgrade (2) B185 and B182 revenue meter CTs at Beaver$49,163
ATSI(Pending) / TC2-ATSI-015.eUpgrade (2) 8.6 Ohm impedance relays at Davis Besse and (2) 7.8 Ohm impedance relays at Lemoyne$48,935
ATSI(Pending) / TC2-ATSI-015.hUpgrade (12) 4.00 SPS.AL PIPE at Lemoyne$46,128
ATSI(Pending) / TC2-ATSI-002.bUpgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse$40,584
ATSI(Pending) / TC2-ATSI-002.fUpgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse$37,260
ATSI(Pending) / TC2-ATSI-002.aUpgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse$33,696
ATSI(Pending) / TC2-ATSI-002.kUpgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse$30,614
ATSI(Pending) / TC2-ATSI-020.eUpgrade (2) L3000 wavetraps at Beaver$25,240
ATSI(Pending) / TC2-ATSI-002.iUpgrade B34544 CT at BAYSHORE$21,833
ATSI(Pending) / TC2-ATSI-020.fUpgrade (2) B182 impedance relays at Beaver (SEL-321: Z2-BU & Z2-PR)$19,917
ATSI(Pending) / TC2-ATSI-020.iUpgrade B182 relay thermal at Beaver$19,917
ATSI(Pending) / TC2-ATSI-020.jUpgrade (2) B182 impedance relays at Beaver (SEL-321: Z4-BU & Z4-PR)$19,917
ATSI(Pending) / TC2-ATSI-020.hUpgrade the B185 CT to PVD at Beaver$13,670
ATSI(Pending) / TC2-ATSI-002.jUpgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse$12,072
ATSI(Pending) / TC2-ATSI-002.lUpgrade (5) 4.00 SPS AL PIPE 61 sub conductors at BAYSHORE on the Bayshore - Davis Besse 345kV line$8,104
ATSI(Pending) / TC2-ATSI-002.cUpgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse$7,900
ATSI(Pending) / TC2-ATSI-002.eUpgrade 345kV 3500 SAC 127 sub conductor at Davis Besse$7,900
ATSI(Pending) / TC2-ATSI-020.cUpgrade 3000 AAC B185 and B185 breaker leads at Beaver$7,322
ATSI(Pending) / TC2-ATSI-002.hUpgrade (8) 1590 AAC 61 sub conductor at BAYSHORE$6,471
Grand Total:$114,010,998

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18693
Title
Greentown 765 kV to Marysville 765 kV - Greenfield Line
Description
Construct a new greenfield 765kV line from Greentown to Marysville (~160 miles). Install 2 new 765kV breakers at Marysville and 2 new 765kV breakers at Greentown. Install 765kV shunt reactors at both Marysville and Greentown The new 765kV line reduces equipment at Dumont to be replaced to CB A2 and switch A2S2. s3442.26 replaces Dumont 765kV CB A2 and A2S2 "CONTINGENCY 'AEP_P1-2_GREENTOWN TO MARYSVILLE 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_GREENTOWN CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_MARYSVILLE CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END"
Total Cost ($USD)
$1,000,000,000
Allocated Cost ($USD)
$57,344,152
Time Estimate
72 to 120 Months

Contributor

FacilityContingency
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line(Any)
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
174.9 MW5.7%$57,344,152
AG2-072
540.7 MW17.7%$177,273,817
AG2-164
166.8 MW5.5%$54,704,127
AG2-165
201.2 MW6.6%$65,982,922
AG2-212
201.2 MW6.6%$65,982,922
AG2-219
256.3 MW8.4%$84,044,734
AG2-328
201.2 MW6.6%$65,982,922
AG2-363
173.7 MW5.7%$56,958,574
AG2-364
115.8 MW3.8%$37,971,836
AG2-453
178.7 MW5.9%$58,593,344
AG2-660
20.1 MW0.7%$6,591,210
AH1-044
166.7 MW5.5%$54,655,930
AH1-146
159.5 MW5.2%$52,300,825
AH1-147
159.5 MW5.2%$52,300,825
AH1-150
166.7 MW5.5%$54,655,930
AH1-151
166.7 MW5.5%$54,655,930

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18653
Title
05MALIS 765.0 kV to 05VASSEL 765.0 kV ckt 1 - Replace Equipment
Description
Replace circuit breaker B, Disconnects, and reconductor between structures 432-453 to bring rating up to the sub conductor.
Total Cost ($USD)
$153,100,000
Allocated Cost ($USD)
$14,361,607
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
43.3 MW9.4%$14,361,607
AG2-104
108.7 MW23.5%$36,021,171
AG2-106
47.5 MW10.3%$15,751,205
AG2-107
47.5 MW10.3%$15,751,205
AG2-165
23.6 MW5.1%$7,831,194
AG2-212
23.6 MW5.1%$7,831,194
AG2-328
23.6 MW5.1%$7,831,194
AG2-363
25.2 MW5.5%$8,360,122
AG2-364
16.8 MW3.6%$5,573,304
AG2-660
2.8 MW0.6%$934,905
AH1-044
16.9 MW3.7%$5,609,097
AH1-146
24.2 MW5.2%$8,012,806
AH1-147
24.2 MW5.2%$8,012,806
AH1-150
16.9 MW3.7%$5,609,097
AH1-151
16.9 MW3.7%$5,609,097

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18686
Title
05MADDOX 345.0 kV to 05E LIMA 345.0 kV ckt 1 - String the 2nd conductor
Description
AEP owned line; string the 2nd conductor (2-bundle 954 ACSS) ~30.28 miles on the double circuit line & six wire, At East Lima station replace sub conductor & relay trip limit and at Maddox Creek replace 5.0 IPS Sch. 40 bus work, sub conductor & relay trip limit
Total Cost ($USD)
$48,000,000
Allocated Cost ($USD)
$10,215,121
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
35.5 MW21.3%$10,215,121
AG2-072
37.4 MW22.4%$10,764,049
AG2-165
13.4 MW8.0%$3,845,946
AG2-212
13.4 MW8.0%$3,845,946
AG2-328
13.4 MW8.0%$3,845,946
AG2-363
14.2 MW8.5%$4,075,984
AG2-364
9.4 MW5.7%$2,717,323
AG2-660
1.6 MW1.0%$457,488
AH1-044
9.5 MW5.7%$2,744,065
AH1-150
9.5 MW5.7%$2,744,065
AH1-151
9.5 MW5.7%$2,744,065

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18700
Title
05GUNN RD SW 345.0 kV to 05BOKESCRK 345.0 kV ckt 1- Rebuild
Description
AEP owned line, 16.54 miles of 345kV single circuit with PE conductor (1-1275 ACSR/PE 54/19) needs to be rebuilt
Total Cost ($USD)
$66,000,000
Allocated Cost ($USD)
$7,690,422
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.7 MW11.7%$7,690,422
AH1-539
10.9 MW8.0%$5,308,563
AH1-690
89.1 MW66.0%$43,588,025
AH1-711
19.2 MW14.3%$9,412,990

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.d
Title
Reconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line
Description
Reconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$149,403,319
Allocated Cost ($USD)
$5,835,961
Time Estimate
82 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$5,835,961
AG2-149
22.1 MW5.4%$8,125,408
AG2-165
7.9 MW1.9%$2,891,547
AG2-212
7.9 MW1.9%$2,891,547
AG2-328
7.9 MW1.9%$2,891,547
AH1-690
290.0 MW71.3%$106,455,624
AH1-711
55.3 MW13.6%$20,311,685

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.a
Title
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV
Description
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$126,131,949
Allocated Cost ($USD)
$5,726,959
Time Estimate
73 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.5%$5,726,959
AG2-149
26.0 MW6.1%$7,692,075
AG2-165
9.2 MW2.2%$2,716,066
AG2-212
9.2 MW2.2%$2,716,066
AG2-328
9.2 MW2.2%$2,716,066
AG2-515
20.4 MW4.8%$6,022,672
AG2-660
1.2 MW0.3%$356,864
AH1-044
7.3 MW1.7%$2,142,071
AH1-150
7.3 MW1.7%$2,142,071
AH1-151
7.3 MW1.7%$2,142,071
AH1-690
230.6 MW54.0%$68,126,768
AH1-711
80.0 MW18.7%$23,632,200

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.d
Title
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends
Description
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$121,594,776
Allocated Cost ($USD)
$3,726,804
Time Estimate
71 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$3,726,804
AG2-149
24.2 MW4.0%$4,914,548
AG2-165
9.0 MW1.5%$1,840,616
AG2-212
9.0 MW1.5%$1,840,616
AG2-328
9.0 MW1.5%$1,840,616
AG2-363
10.7 MW1.8%$2,168,781
AG2-364
7.1 MW1.2%$1,445,922
AG2-660
1.2 MW0.2%$241,903
AH1-044
7.1 MW1.2%$1,451,212
AH1-150
7.1 MW1.2%$1,451,212
AH1-151
7.1 MW1.2%$1,451,212
AH1-690
441.8 MW73.9%$89,885,811
AH1-711
45.9 MW7.7%$9,335,525

System Reinforcement: n7683
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n7683
Title
Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA.
Description
Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA.
Total Cost ($USD)
$18,460,000
Allocated Cost ($USD)
$2,893,473
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
35.8 MW15.7%$2,893,473
AG2-072
38.0 MW16.7%$3,077,314
AG2-165
13.5 MW5.9%$1,093,498
AG2-212
13.5 MW5.9%$1,093,498
AG2-328
13.5 MW5.9%$1,093,498
AG2-363
14.3 MW6.3%$1,160,173
AG2-364
9.6 MW4.2%$773,395
AG2-400
19.5 MW8.6%$1,581,826
AG2-453
20.4 MW8.9%$1,647,691
AG2-660
1.6 MW0.7%$131,246
AH1-044
9.7 MW4.2%$781,001
AH1-146
9.7 MW4.3%$785,694
AH1-147
9.7 MW4.3%$785,694
AH1-150
9.7 MW4.2%$781,001
AH1-151
9.7 MW4.2%$781,001

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18689
Title
AG1-410 TP 345.0 kV to 05MADDOX 345.0 kV ckt 1 - string the 2nd circuit
Description
AEP owned line; string the 2nd circuit on the rebuilt double circuit line, ~ 2.85 miles of 2-bundle 1590 ACSR conductor. At Maddox Creek: Replace 345kV circuit breaker B2, subconductor, disconnect switches.
Total Cost ($USD)
$7,250,000
Allocated Cost ($USD)
$1,136,386
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
35.8 MW15.7%$1,136,386
AG2-072
38.0 MW16.7%$1,208,588
AG2-165
13.5 MW5.9%$429,462
AG2-212
13.5 MW5.9%$429,462
AG2-328
13.5 MW5.9%$429,462
AG2-363
14.3 MW6.3%$455,647
AG2-364
9.6 MW4.2%$303,744
AG2-400
19.5 MW8.6%$621,248
AG2-453
20.4 MW8.9%$647,116
AG2-660
1.6 MW0.7%$51,546
AH1-044
9.7 MW4.2%$306,731
AH1-146
9.7 MW4.3%$308,574
AH1-147
9.7 MW4.3%$308,574
AH1-150
9.7 MW4.2%$306,731
AH1-151
9.7 MW4.2%$306,731

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18707
Title
05ALLEN 345.0 kV to 05RPMONE 345.0 kV ckt 1 - Replace Equipment
Description
At RP Mone: Replace CB B and B2 and associated disconnect switches. Replace 2 - 1700 KCM AAC station conductor. At Allen: Replace the disconnect switches for CBs C and C2 at Allen. Replace 2 - 2000 KCM AAC station conductor. B3851.1 to rebuild the Allen - RP Mone line needs to be completed. CB B is also be proposed to be replaced on another flowgate
Total Cost ($USD)
$5,000,000
Allocated Cost ($USD)
$933,382
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
36.4 MW18.7%$933,382
AG2-165
13.9 MW7.1%$356,344
AG2-212
13.9 MW7.1%$356,344
AG2-328
13.9 MW7.1%$356,344
AG2-363
14.8 MW7.6%$379,162
AG2-364
9.9 MW5.1%$252,766
AG2-400
19.8 MW10.1%$506,712
AG2-453
21.0 MW10.8%$537,555
AG2-660
1.7 MW0.9%$42,534
AH1-044
10.0 MW5.1%$255,176
AH1-146
10.0 MW5.1%$256,663
AH1-147
10.0 MW5.1%$256,663
AH1-150
10.0 MW5.1%$255,176
AH1-151
10.0 MW5.1%$255,176

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18733
Title
05BOKESCRK 345kV to 05MARYSV 345kV ckt 1 - Reconductor
Description
Reconductor line between Marysville - Boke Creek 345 kV due to paper expanded line. New line will be 2-954 ACSR RAIL
Total Cost ($USD)
$6,810,000
Allocated Cost ($USD)
$794,214
Time Estimate
48 to 52 Months

Contributor

FacilityContingency
05MARYSV-05BOKESCRK 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.4 MW11.7%$794,214
AH1-539
10.6 MW8.0%$547,769
AH1-690
87.6 MW66.2%$4,507,618
AH1-711
18.7 MW14.1%$960,398

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18659
Title
05MARYSVL_RS 765.0 kV to 05MARYSV 765.0 kV ckt Z1 - Replace Equipment
Description
Replace wave trap, CB-B, and disconnect swiches at Marysville.
Total Cost ($USD)
$9,500,000
Allocated Cost ($USD)
$782,187
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
62.7 MW8.2%$782,187
AG2-072
143.4 MW18.8%$1,788,915
AG2-164
54.0 MW7.1%$673,560
AG2-165
43.6 MW5.7%$544,470
AG2-212
43.6 MW5.7%$544,470
AG2-219
66.0 MW8.7%$823,250
AG2-245
46.1 MW6.0%$574,740
AG2-328
43.6 MW5.7%$544,470
AG2-453
60.3 MW7.9%$752,978
AG2-660
4.4 MW0.6%$54,650
AH1-044
37.4 MW4.9%$466,912
AH1-146
40.7 MW5.3%$507,787
AH1-147
40.7 MW5.3%$507,787
AH1-150
37.4 MW4.9%$466,912
AH1-151
37.4 MW4.9%$466,912

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18732
Title
05RPMONE 345kV to AG1-410 TP 345kV ckt 1 - Replace Equipment
Description
At R.P. Mone: Replace 345kV circuit breakers B & B1, Bus bar 4 x 3/4 Ph C, angle bus buar 4x4x1/4 Ph B, sub conductor, disconnect switches on B and B1 breakers
Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$705,383
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
35.8 MW15.7%$705,383
AG2-072
38.0 MW16.7%$750,201
AG2-165
13.5 MW5.9%$266,578
AG2-212
13.5 MW5.9%$266,578
AG2-328
13.5 MW5.9%$266,578
AG2-363
14.3 MW6.3%$282,832
AG2-364
9.6 MW4.2%$188,541
AG2-400
19.5 MW8.6%$385,624
AG2-453
20.4 MW8.9%$401,681
AG2-660
1.6 MW0.7%$31,739
AH1-044
9.7 MW4.2%$190,396
AH1-146
9.7 MW4.3%$191,540
AH1-147
9.7 MW4.3%$191,540
AH1-150
9.7 MW4.2%$190,396
AH1-151
9.7 MW4.2%$190,396

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.c
Title
Upgrade (2) 3000A CBs at Davis Besse and (1) 3000A CB at Lemoyne
Description
Upgrade (2) 3000A CBs at Davis Besse and (1) 3000A CB at Lemoyne
Total Cost ($USD)
$5,962,261
Allocated Cost ($USD)
$286,099
Time Estimate
56 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$286,099
AG2-149
26.0 MW6.4%$384,270
AG2-165
9.2 MW2.3%$135,685
AG2-212
9.2 MW2.3%$135,685
AG2-328
9.2 MW2.3%$135,685
AG2-515
20.4 MW5.0%$300,872
AH1-690
230.6 MW57.1%$3,403,380
AH1-711
80.0 MW19.8%$1,180,584

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.g
Title
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$7,786,806
Allocated Cost ($USD)
$238,661
Time Estimate
60 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$238,661
AG2-149
24.2 MW4.0%$314,723
AG2-165
9.0 MW1.5%$117,871
AG2-212
9.0 MW1.5%$117,871
AG2-328
9.0 MW1.5%$117,871
AG2-363
10.7 MW1.8%$138,887
AG2-364
7.1 MW1.2%$92,595
AG2-660
1.2 MW0.2%$15,491
AH1-044
7.1 MW1.2%$92,934
AH1-150
7.1 MW1.2%$92,934
AH1-151
7.1 MW1.2%$92,934
AH1-690
441.8 MW73.9%$5,756,196
AH1-711
45.9 MW7.7%$597,838

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.i
Title
Upgrade (10) 3000A bus and line side disconnect switches at Davis Besse and Lemoyne (34624, A34604, D345:63A,63B,64D,64C,01N,01S,02W,02E)
Description
Upgrade (10) 3000A bus and line side disconnect switches at Davis Besse and Lemoyne (34624, A34604, D345:63A,63B,64D,64C,01N,01S,02W,02E)
Total Cost ($USD)
$3,952,709
Allocated Cost ($USD)
$189,671
Time Estimate
29 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$189,671
AG2-149
26.0 MW6.4%$254,753
AG2-165
9.2 MW2.3%$89,953
AG2-212
9.2 MW2.3%$89,953
AG2-328
9.2 MW2.3%$89,953
AG2-515
20.4 MW5.0%$199,465
AH1-690
230.6 MW57.1%$2,256,287
AH1-711
80.0 MW19.8%$782,674

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.a
Title
Upgrade B185 and B182 circuit breakers at Beaver
Description
Upgrade B185 and B182 circuit breakers at Beaver
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$158,348
Time Estimate
56 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW4.1%$158,348
AG2-149
22.5 MW5.7%$223,755
AG2-165
7.8 MW2.0%$77,540
AG2-212
7.8 MW2.0%$77,540
AG2-328
7.8 MW2.0%$77,540
AH1-690
275.9 MW70.6%$2,748,721
AH1-711
53.2 MW13.6%$529,961

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.m
Title
Upgrade (7) 3000A disconnect switches (D34545:N,S, D3454:W,E, A34673, D34561C, and 34623)and (2) B34545 impedance relays at Bayshore and Davis Besse
Description
Upgrade (7) 3000A disconnect switches (D34545:N,S, D3454:W,E, A34673, D34561C, and 34623)and (2) B34545 impedance relays at Bayshore and Davis Besse
Total Cost ($USD)
$3,544,138
Allocated Cost ($USD)
$116,491
Time Estimate
42 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.3%$116,491
AG2-149
24.2 MW4.3%$153,617
AG2-165
9.0 MW1.6%$57,533
AG2-212
9.0 MW1.6%$57,533
AG2-328
9.0 MW1.6%$57,533
AH1-690
441.8 MW79.3%$2,809,622
AH1-711
45.9 MW8.2%$291,807

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.g
Title
Upgrade (2) B34501 and B34502 relay thermals at Lemoyne and (3) 34563 relay and meter thermals at Davis Besse
Description
Upgrade (2) B34501 and B34502 relay thermals at Lemoyne and (3) 34563 relay and meter thermals at Davis Besse
Total Cost ($USD)
$2,137,421
Allocated Cost ($USD)
$102,564
Time Estimate
20 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$102,564
AG2-149
26.0 MW6.4%$137,758
AG2-165
9.2 MW2.3%$48,642
AG2-212
9.2 MW2.3%$48,642
AG2-328
9.2 MW2.3%$48,642
AG2-515
20.4 MW5.0%$107,860
AH1-690
230.6 MW57.1%$1,220,083
AH1-711
80.0 MW19.8%$423,229

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.d
Title
Upgrade (12) dual 1590 ACSR SCCIR at Davis Besse and Lemoyne
Description
Upgrade (12) dual 1590 ACSR SCCIR at Davis Besse and Lemoyne
Total Cost ($USD)
$2,070,983
Allocated Cost ($USD)
$99,376
Time Estimate
12 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$99,376
AG2-149
26.0 MW6.4%$133,476
AG2-165
9.2 MW2.3%$47,130
AG2-212
9.2 MW2.3%$47,130
AG2-328
9.2 MW2.3%$47,130
AG2-515
20.4 MW5.0%$104,507
AH1-690
230.6 MW57.1%$1,182,159
AH1-711
80.0 MW19.8%$410,074

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.f
Title
Upgrade the B34502 CB at Lemoyne
Description
Upgrade the B34502 CB at Lemoyne
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$99,274
Time Estimate
54 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$99,274
AG2-149
26.0 MW6.4%$133,338
AG2-165
9.2 MW2.3%$47,082
AG2-212
9.2 MW2.3%$47,082
AG2-328
9.2 MW2.3%$47,082
AG2-515
20.4 MW5.0%$104,400
AH1-690
230.6 MW57.1%$1,180,945
AH1-711
80.0 MW19.8%$409,653

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.b
Title
Upgrade (4) disconnect switches at Beaver (D186,184,181,183)
Description
Upgrade (4) disconnect switches at Beaver (D186,184,181,183)
Total Cost ($USD)
$1,699,640
Allocated Cost ($USD)
$66,391
Time Estimate
25 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$66,391
AG2-149
22.1 MW5.4%$92,436
AG2-165
7.9 MW1.9%$32,895
AG2-212
7.9 MW1.9%$32,895
AG2-328
7.9 MW1.9%$32,895
AH1-690
290.0 MW71.3%$1,211,059
AH1-711
55.3 MW13.6%$231,070

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.b
Title
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Description
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Total Cost ($USD)
$1,132,675
Allocated Cost ($USD)
$51,429
Time Estimate
22 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.5%$51,429
AG2-149
26.0 MW6.1%$69,075
AG2-165
9.2 MW2.2%$24,390
AG2-212
9.2 MW2.2%$24,390
AG2-328
9.2 MW2.2%$24,390
AG2-515
20.4 MW4.8%$54,084
AG2-660
1.2 MW0.3%$3,205
AH1-044
7.3 MW1.7%$19,236
AH1-150
7.3 MW1.7%$19,236
AH1-151
7.3 MW1.7%$19,236
AH1-690
230.6 MW54.0%$611,784
AH1-711
80.0 MW18.7%$212,219

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.g
Title
Upgrade (2) B185 and B182 revenue meter CTs at Beaver
Description
Upgrade (2) B185 and B182 revenue meter CTs at Beaver
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$49,163
Time Estimate
21 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$49,163
AG2-149
22.1 MW5.4%$68,450
AG2-165
7.9 MW1.9%$24,359
AG2-212
7.9 MW1.9%$24,359
AG2-328
7.9 MW1.9%$24,359
AH1-690
290.0 MW71.3%$896,798
AH1-711
55.3 MW13.6%$171,109

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.e
Title
Upgrade (2) 8.6 Ohm impedance relays at Davis Besse and (2) 7.8 Ohm impedance relays at Lemoyne
Description
Upgrade (2) 8.6 Ohm impedance relays at Davis Besse and (2) 7.8 Ohm impedance relays at Lemoyne
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$48,935
Time Estimate
18 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$48,935
AG2-149
26.0 MW6.4%$65,726
AG2-165
9.2 MW2.3%$23,208
AG2-212
9.2 MW2.3%$23,208
AG2-328
9.2 MW2.3%$23,208
AG2-515
20.4 MW5.0%$51,461
AH1-690
230.6 MW57.1%$582,117
AH1-711
80.0 MW19.8%$201,928

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.h
Title
Upgrade (12) 4.00 SPS.AL PIPE at Lemoyne
Description
Upgrade (12) 4.00 SPS.AL PIPE at Lemoyne
Total Cost ($USD)
$961,300
Allocated Cost ($USD)
$46,128
Time Estimate
22 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$46,128
AG2-149
26.0 MW6.4%$61,956
AG2-165
9.2 MW2.3%$21,877
AG2-212
9.2 MW2.3%$21,877
AG2-328
9.2 MW2.3%$21,877
AG2-515
20.4 MW5.0%$48,510
AH1-690
230.6 MW57.1%$548,730
AH1-711
80.0 MW19.8%$190,346

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.b
Title
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Description
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Total Cost ($USD)
$1,324,127
Allocated Cost ($USD)
$40,584
Time Estimate
37 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$40,584
AG2-149
24.2 MW4.0%$53,518
AG2-165
9.0 MW1.5%$20,044
AG2-212
9.0 MW1.5%$20,044
AG2-328
9.0 MW1.5%$20,044
AG2-363
10.7 MW1.8%$23,617
AG2-364
7.1 MW1.2%$15,746
AG2-660
1.2 MW0.2%$2,634
AH1-044
7.1 MW1.2%$15,803
AH1-150
7.1 MW1.2%$15,803
AH1-151
7.1 MW1.2%$15,803
AH1-690
441.8 MW73.9%$978,827
AH1-711
45.9 MW7.7%$101,661

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.f
Title
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$1,215,694
Allocated Cost ($USD)
$37,260
Time Estimate
22 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$37,260
AG2-149
24.2 MW4.0%$49,135
AG2-165
9.0 MW1.5%$18,402
AG2-212
9.0 MW1.5%$18,402
AG2-328
9.0 MW1.5%$18,402
AG2-363
10.7 MW1.8%$21,683
AG2-364
7.1 MW1.2%$14,456
AG2-660
1.2 MW0.2%$2,419
AH1-044
7.1 MW1.2%$14,509
AH1-150
7.1 MW1.2%$14,509
AH1-151
7.1 MW1.2%$14,509
AH1-690
441.8 MW73.9%$898,671
AH1-711
45.9 MW7.7%$93,336

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.a
Title
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Description
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Total Cost ($USD)
$1,099,401
Allocated Cost ($USD)
$33,696
Time Estimate
14 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$33,696
AG2-149
24.2 MW4.0%$44,435
AG2-165
9.0 MW1.5%$16,642
AG2-212
9.0 MW1.5%$16,642
AG2-328
9.0 MW1.5%$16,642
AG2-363
10.7 MW1.8%$19,609
AG2-364
7.1 MW1.2%$13,073
AG2-660
1.2 MW0.2%$2,187
AH1-044
7.1 MW1.2%$13,121
AH1-150
7.1 MW1.2%$13,121
AH1-151
7.1 MW1.2%$13,121
AH1-690
441.8 MW73.9%$812,704
AH1-711
45.9 MW7.7%$84,407

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.k
Title
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Description
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Total Cost ($USD)
$998,835
Allocated Cost ($USD)
$30,614
Time Estimate
19 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$30,614
AG2-149
24.2 MW4.0%$40,370
AG2-165
9.0 MW1.5%$15,120
AG2-212
9.0 MW1.5%$15,120
AG2-328
9.0 MW1.5%$15,120
AG2-363
10.7 MW1.8%$17,815
AG2-364
7.1 MW1.2%$11,877
AG2-660
1.2 MW0.2%$1,987
AH1-044
7.1 MW1.2%$11,921
AH1-150
7.1 MW1.2%$11,921
AH1-151
7.1 MW1.2%$11,921
AH1-690
441.8 MW73.9%$738,363
AH1-711
45.9 MW7.7%$76,686

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.e
Title
Upgrade (2) L3000 wavetraps at Beaver
Description
Upgrade (2) L3000 wavetraps at Beaver
Total Cost ($USD)
$620,600
Allocated Cost ($USD)
$25,240
Time Estimate
18 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW4.1%$25,240
AG2-149
22.5 MW5.7%$35,666
AG2-165
7.8 MW2.0%$12,360
AG2-212
7.8 MW2.0%$12,360
AG2-328
7.8 MW2.0%$12,360
AH1-690
275.9 MW70.6%$438,140
AH1-711
53.2 MW13.6%$84,475

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.i
Title
Upgrade B34544 CT at BAYSHORE
Description
Upgrade B34544 CT at BAYSHORE
Total Cost ($USD)
$712,356
Allocated Cost ($USD)
$21,833
Time Estimate
20 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$21,833
AG2-149
24.2 MW4.0%$28,792
AG2-165
9.0 MW1.5%$10,783
AG2-212
9.0 MW1.5%$10,783
AG2-328
9.0 MW1.5%$10,783
AG2-363
10.7 MW1.8%$12,706
AG2-364
7.1 MW1.2%$8,471
AG2-660
1.2 MW0.2%$1,417
AH1-044
7.1 MW1.2%$8,502
AH1-150
7.1 MW1.2%$8,502
AH1-151
7.1 MW1.2%$8,502
AH1-690
441.8 MW73.9%$526,591
AH1-711
45.9 MW7.7%$54,692

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.f
Title
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z2-BU & Z2-PR)
Description
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z2-BU & Z2-PR)
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$19,917
Time Estimate
19 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$19,917
AG2-149
22.1 MW5.4%$27,731
AG2-165
7.9 MW1.9%$9,868
AG2-212
7.9 MW1.9%$9,868
AG2-328
7.9 MW1.9%$9,868
AH1-690
290.0 MW71.3%$363,320
AH1-711
55.3 MW13.6%$69,321

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.i
Title
Upgrade B182 relay thermal at Beaver
Description
Upgrade B182 relay thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$19,917
Time Estimate
19 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$19,917
AG2-149
22.1 MW5.4%$27,731
AG2-165
7.9 MW1.9%$9,868
AG2-212
7.9 MW1.9%$9,868
AG2-328
7.9 MW1.9%$9,868
AH1-690
290.0 MW71.3%$363,320
AH1-711
55.3 MW13.6%$69,321

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.j
Title
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z4-BU & Z4-PR)
Description
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z4-BU & Z4-PR)
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$19,917
Time Estimate
19 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$19,917
AG2-149
22.1 MW5.4%$27,731
AG2-165
7.9 MW1.9%$9,868
AG2-212
7.9 MW1.9%$9,868
AG2-328
7.9 MW1.9%$9,868
AH1-690
290.0 MW71.3%$363,320
AH1-711
55.3 MW13.6%$69,321

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.h
Title
Upgrade the B185 CT to PVD at Beaver
Description
Upgrade the B185 CT to PVD at Beaver
Total Cost ($USD)
$349,952
Allocated Cost ($USD)
$13,670
Time Estimate
17 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$13,670
AG2-149
22.1 MW5.4%$19,032
AG2-165
7.9 MW1.9%$6,773
AG2-212
7.9 MW1.9%$6,773
AG2-328
7.9 MW1.9%$6,773
AH1-690
290.0 MW71.3%$249,354
AH1-711
55.3 MW13.6%$47,577

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.j
Title
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Description
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Total Cost ($USD)
$393,871
Allocated Cost ($USD)
$12,072
Time Estimate
13 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$12,072
AG2-149
24.2 MW4.0%$15,919
AG2-165
9.0 MW1.5%$5,962
AG2-212
9.0 MW1.5%$5,962
AG2-328
9.0 MW1.5%$5,962
AG2-363
10.7 MW1.8%$7,025
AG2-364
7.1 MW1.2%$4,684
AG2-660
1.2 MW0.2%$784
AH1-044
7.1 MW1.2%$4,701
AH1-150
7.1 MW1.2%$4,701
AH1-151
7.1 MW1.2%$4,701
AH1-690
441.8 MW73.9%$291,159
AH1-711
45.9 MW7.7%$30,240

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.l
Title
Upgrade (5) 4.00 SPS AL PIPE 61 sub conductors at BAYSHORE on the Bayshore - Davis Besse 345kV line
Description
Upgrade (5) 4.00 SPS AL PIPE 61 sub conductors at BAYSHORE on the Bayshore - Davis Besse 345kV line
Total Cost ($USD)
$246,545
Allocated Cost ($USD)
$8,104
Time Estimate
14 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.3%$8,104
AG2-149
24.2 MW4.3%$10,686
AG2-165
9.0 MW1.6%$4,002
AG2-212
9.0 MW1.6%$4,002
AG2-328
9.0 MW1.6%$4,002
AH1-690
441.8 MW79.3%$195,449
AH1-711
45.9 MW8.2%$20,299

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.c
Title
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Description
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$7,900
Time Estimate
13 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$7,900
AG2-149
24.2 MW4.0%$10,418
AG2-165
9.0 MW1.5%$3,902
AG2-212
9.0 MW1.5%$3,902
AG2-328
9.0 MW1.5%$3,902
AG2-363
10.7 MW1.8%$4,597
AG2-364
7.1 MW1.2%$3,065
AG2-660
1.2 MW0.2%$513
AH1-044
7.1 MW1.2%$3,076
AH1-150
7.1 MW1.2%$3,076
AH1-151
7.1 MW1.2%$3,076
AH1-690
441.8 MW73.9%$190,544
AH1-711
45.9 MW7.7%$19,790

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.e
Title
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Description
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$7,900
Time Estimate
13 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$7,900
AG2-149
24.2 MW4.0%$10,418
AG2-165
9.0 MW1.5%$3,902
AG2-212
9.0 MW1.5%$3,902
AG2-328
9.0 MW1.5%$3,902
AG2-363
10.7 MW1.8%$4,597
AG2-364
7.1 MW1.2%$3,065
AG2-660
1.2 MW0.2%$513
AH1-044
7.1 MW1.2%$3,076
AH1-150
7.1 MW1.2%$3,076
AH1-151
7.1 MW1.2%$3,076
AH1-690
441.8 MW73.9%$190,544
AH1-711
45.9 MW7.7%$19,790

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.c
Title
Upgrade 3000 AAC B185 and B185 breaker leads at Beaver
Description
Upgrade 3000 AAC B185 and B185 breaker leads at Beaver
Total Cost ($USD)
$187,449
Allocated Cost ($USD)
$7,322
Time Estimate
13 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$7,322
AG2-149
22.1 MW5.4%$10,195
AG2-165
7.9 MW1.9%$3,628
AG2-212
7.9 MW1.9%$3,628
AG2-328
7.9 MW1.9%$3,628
AH1-690
290.0 MW71.3%$133,565
AH1-711
55.3 MW13.6%$25,484

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.h
Title
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Description
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Total Cost ($USD)
$211,119
Allocated Cost ($USD)
$6,471
Time Estimate
13 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$6,471
AG2-149
24.2 MW4.0%$8,533
AG2-165
9.0 MW1.5%$3,196
AG2-212
9.0 MW1.5%$3,196
AG2-328
9.0 MW1.5%$3,196
AG2-363
10.7 MW1.8%$3,766
AG2-364
7.1 MW1.2%$2,510
AG2-660
1.2 MW0.2%$420
AH1-044
7.1 MW1.2%$2,520
AH1-150
7.1 MW1.2%$2,520
AH1-151
7.1 MW1.2%$2,520
AH1-690
441.8 MW73.9%$156,064
AH1-711
45.9 MW7.7%$16,209

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9322.0
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
n9322.0 / TE-AG1-S-0012a
Title
Replace Four (4) disconnect switches, four (4) breaker leads, and one (1) meter, and reconductor two (2) transmission line drops on the Morocco 345 kV line terminal at Allen Junction.
Description
Replace (4) disconnect switches at Allen Junction Replace (4) breaker leads at Allen Junction Reconductor (2) TL Drops at Allen Junction Replace (1) meter at Allen Junction New FE Ratings 1868 / 2249 / 2586 MVA SN/SE/SLD
Total Cost ($USD)
$1,408,997
Allocated Cost ($USD)
$0
Time Estimate
38 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.a
Title
Upgrade D120 and D125 disconnect switches at Beaver substation
Description
Upgrade D120 and D125 disconnect switches at Beaver substation
Total Cost ($USD)
$929,516
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.b
Title
Upgrade (1) 3000 SAC 169 line drop at Beaver
Description
Upgrade (1) 3000 SAC 169 line drop at Beaver
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.c
Title
Reconductor (possible rebuild) 18.22 miles of 954 ACSR 48/7 transmission line and (3) line drops at Beaver on the Beaver - Carlisle Ckt 1 345 kV
Description
Reconductor (possible rebuild) 18.22 miles of 954 ACSR 48/7 transmission line and (3) line drops at Beaver on the Beaver - Carlisle Ckt 1 345 kV using dual (2) 795 26/7 "Drake ACSS
Total Cost ($USD)
$109,211,408
Allocated Cost ($USD)
$0
Time Estimate
63 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.d
Title
Upgrade (1) 3500 SAC 127 D120-to-B121 breaker lead at Beaver
Description
Upgrade (1) 3500 SAC 127 D120-to-B121 breaker lead at Beaver
Total Cost ($USD)
$265,209
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.a
Title
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line
Description
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$175,902,477
Allocated Cost ($USD)
$0
Time Estimate
90 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.b
Title
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Description
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.c
Title
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Description
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Total Cost ($USD)
$729,124
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.d
Title
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Description
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Total Cost ($USD)
$7,937,520
Allocated Cost ($USD)
$0
Time Estimate
60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.e
Title
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Description
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.f
Title
Upgrade the B6 CT at Hayes
Description
Upgrade the B6 CT at Hayes
Total Cost ($USD)
$727,300
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.g
Title
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3)
Description
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3) using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$591,863
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.h
Title
Upgrade the B88 and B115 CTs at Beaver
Description
Upgrade the B88 and B115 CTs at Beaver
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.i
Title
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Description
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.j
Title
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Description
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.k
Title
Upgrade (9) 3000A disconnect switches at Beaver and Hayes (D:74,92,93,116,4,5,7,8,11)
Description
Upgrade (9) 3000A disconnect switches at Beaver and Hayes (D:74,92,93,116,4,5,7,8,11)
Total Cost ($USD)
$3,774,791
Allocated Cost ($USD)
$0
Time Estimate
29 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.a
Title
Upgrade (3) disconnect switches at Beaver (D:120,166,165)
Description
Upgrade (3) disconnect switches at Beaver (D:120,166,165)
Total Cost ($USD)
$1,350,788
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.b
Title
Upgrade (4) 954 ACSR 45/7 overhead line and line drops at Beaver Substation
Description
Upgrade (4) 954 ACSR 45/7 overhead line and line drops at Beaver Substation
Total Cost ($USD)
$809,465
Allocated Cost ($USD)
$0
Time Estimate
15 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005c
Title
Upgrade 3500 SAC 127 B161 (2) breaker leads and (1) B121-to-D120 breaker lead at Beaver
Description
Upgrade 3500 SAC 127 B161 (2) breaker leads and (1) B121-to-D120 breaker lead at Beaver
Total Cost ($USD)
$191,109
Allocated Cost ($USD)
$0
Time Estimate
11 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.d
Title
Reconductor (possible rebuild) 8.37 miles of 954 ACSR 48/7 transmission line on the Beaver - Lake Avenue Ckt 1 345 kV
Description
Reconductor (possible rebuild) 8.37 miles of 954 ACSR 48/7 transmission line on the Beaver - Lake Avenue Ckt 1 345 kV using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$50,053,445
Allocated Cost ($USD)
$0
Time Estimate
38 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9227.0
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
n9227.0 / TC1-ATSI-001.b
Title
Upgrade T-line drops, overhead substation conductor and TL reconductor
Description
Reconductor (possible rebuild) of 8.12 miles of dual transmission line and (2) single conductor line drops at Beaver on the Beaver-Lake Ave Ckt 2 345 kV line using triple (3) 1113 54/19 ""Finch"" ACSS"
Total Cost ($USD)
$48,873,856
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.a
Title
Upgrade (4) circuit breakers at Beaver and Lake Ave (B:3,4,216,219)
Description
Upgrade (4) circuit breakers at Beaver and Lake Ave (B:3,4,216,219)
Total Cost ($USD)
$7,786,809
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.b
Title
Upgrade 1590 AAC B3, B4, B216 and B219 breaker leads at Beaver and Lake Ave
Description
Upgrade 1590 AAC B3, B4, B216 and B219 breaker leads at Beaver and Lake Ave
Total Cost ($USD)
$305,540
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.c
Title
Upgrade the (3) B216, B219 and B4 1500 CTs
Description
Upgrade the (3) B216, B219 and B4 1500 CTs
Total Cost ($USD)
$853,850
Allocated Cost ($USD)
$0
Time Estimate
16 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.d
Title
Upgrade (3) 1590 line drops at Beaver and Lake Ave
Description
Upgrade (3) 1590 line drops at Beaver and Lake Ave
Total Cost ($USD)
$690,685
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.e
Title
Upgrade the (1) B219 1200 CT to PVD at Beaver
Description
Upgrade the (1) B219 1200 CT to PVD at Beaver
Total Cost ($USD)
$349,952
Allocated Cost ($USD)
$0
Time Estimate
16 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.f
Title
Upgrade the (1) B216 relay thermal at Beaver
Description
Upgrade the (1) B216 relay thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.g
Title
Upgrade (1) 4.00 SPS.AL PIPE at Beaver
Description
Upgrade (1) 4.00 SPS.AL PIPE at Beaver
Total Cost ($USD)
$178,089
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.h
Title
Upgrade (9) disconnect switches at Beaver and Lake Ave (D: 19,20,21,22, 212,215,217,218,220)
Description
Upgrade (9) disconnect switches at Beaver and Lake Ave (D: 19,20,21,22, 212,215,217,218,220)
Total Cost ($USD)
$3,850,794
Allocated Cost ($USD)
$0
Time Estimate
39 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.i
Title
Upgrade the (2) B3 SEL411L impedance relays at Lake Ave
Description
Upgrade the (2) B3 SEL411L impedance relays at Lake Ave
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.j
Title
Upgrade (2) 2.50 SPS.AL PIPE SCCIR at Beaver
Description
Upgrade (2) 2.50 SPS.AL PIPE SCCIR at Beaver
Total Cost ($USD)
$173,391
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.k
Title
Upgrade the (15) B216, B219, B3 and B4 2000 CTs at Beaver and Lake Ave
Description
Upgrade the (15) B216, B219, B3 and B4 2000 CTs at Beaver and Lake Ave
Total Cost ($USD)
$2,701,212
Allocated Cost ($USD)
$0
Time Estimate
17 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.l
Title
Upgrade the (2) B216 SEL411L impedance relays at Lake Ave
Description
Upgrade the (2) B216 SEL411L impedance relays at Lake Ave
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.m
Title
Upgrade (8) 5.00 SPS.AL PIPE SCCIR at Beaver
Description
Upgrade (8) 5.00 SPS.AL PIPE SCCIR at Beaver
Total Cost ($USD)
$250,039
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.a
Title
Reconductor (possible rebuild) 30.25 miles of 954 ACSR 48/7 transmission line and line drops (line drops at Davis Besse) on the Davis Besse-Hayes 345 kV line
Description
Reconductor (possible rebuild) 30.25 miles of 954 ACSR 48/7 transmission line and line drops (line drops at Davis Besse) on the Davis Besse-Hayes 345 kV line using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$179,916,169
Allocated Cost ($USD)
$0
Time Estimate
90 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.b
Title
Upgrade 3500 SAC 127 OVERHEAD PIPE to disc sw. 34625 at Davis Besse and B18 breaker leads at Hayes
Description
Upgrade 3500 SAC 127 OVERHEAD PIPE to disc sw. 34625 at Davis Besse and B18 breaker leads at Hayes
Total Cost ($USD)
$284,061
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.c
Title
Upgrade (2) Wave Traps at Davis Besse and (2) Wave Traps at Hayes
Description
Upgrade (2) Wave Traps at Davis Besse and (2) Wave Traps at Hayes
Total Cost ($USD)
$1,215,695
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.d
Title
Upgrade (2) B18 & B12 345 kV Ciruit Breakers at Hayes
Description
Upgrade (2) B18 & B12 345 kV Ciruit Breakers at Hayes
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.e
Title
Upgrade (2) B12 and B18 CTs at Hayes
Description
Upgrade (2) B12 and B18 CTs at Hayes
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.f
Title
Upgrade (10) 1590 ACSR sub conductor (B66 and B67 breaker leads, wave trap subconductor, Overheadline-34625) at Davis Besse and B12 breaker leads at Hayes
Description
Upgrade (10) 1590 ACSR sub conductor (B66 and B67 breaker leads, wave trap subconductor, Overheadline-34625) at Davis Besse and B12 breaker leads at Hayes
Total Cost ($USD)
$305,149
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.g
Title
Upgrade B66 and B67 circuit breakers at Davis Besse substation
Description
Upgrade B66 and B67 circuit breakers at Davis Besse substation
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.i
Title
Upgrade (2) 9.6 Ohms impedance relays at Hayes and (2) 12.9 Ohms impedance relays at Davis Besse
Description
Upgrade (2) 9.6 Ohms impedance relays at Hayes and (2) 12.9 Ohms impedance relays at Davis Besse
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.h
Title
Upgrade B66 (1) meter and (1) relay thermals and B67 (1) meter thermal at Davis Besse substation
Description
Upgrade B66 (1) meter and (1) relay thermals and B67 (1) meter thermal at Davis Besse substation
Total Cost ($USD)
$852,462
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.j
Title
Upgrade (6) disconnect switches at Davis Besse (D27,28,29,30,34625,37) and (5) disconnect switches at Hayes (D20,19,16,13,14)
Description
Upgrade (6) disconnect switches at Davis Besse (D27,28,29,30,34625,37) and (5) disconnect switches at Hayes (D20,19,16,13,14)
Total Cost ($USD)
$4,525,814
Allocated Cost ($USD)
$0
Time Estimate
31 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.k
Title
Upgrade (1) 1590 AACSR Phase A/C line drop at Davis Besse substation and (3) Phase 3 "B-B", Phase 1&2 "C-C", and shared node to wave trap line drops at Hayes
Description
Upgrade (1) 1590 AACSR Phase A/C line drop at Davis Besse substation and (3) Phase 3 "B-B", Phase 1&2 "C-C", and shared node to wave trap line drops at Hayes
Total Cost ($USD)
$855,032
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.i
Title
Upgrade (4) 1590 ACSR 45/7 sub conductors at Davis Besse
Description
Upgrade (4) 1590 ACSR 45/7 sub conductors at Davis Besse
Total Cost ($USD)
$756,208
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.j
Title
Upgrade (2) 13.03 Ohm B65 Impedance Relays at Davis Besse
Description
Upgrade (2) 13.03 Ohm B65 Impedance Relays at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.k
Title
Upgrade (2) 6.65 Ohm B65 Impedance Relays at Davis Besse
Description
Upgrade (2) 6.65 Ohm B65 Impedance Relays at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.l
Title
Upgrade Circuit Breaker B65 at Davis Besse
Description
Upgrade Circuit Breaker B65 at Davis Besse
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$0
Time Estimate
54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.m
Title
Upgrade (2) B65 Meter Thermals at Davis Besse
Description
Upgrade (2) B65 Meter Thermals at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.a
Title
Upgrade D41 and D42 disconnect switches at Davis Besse
Description
Upgrade D41 and D42 disconnect switches at Davis Besse
Total Cost ($USD)
$967,716
Allocated Cost ($USD)
$0
Time Estimate
36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.b
Title
Upgrade (1) 1024 ACAR 6E550-52-1 "A" line drop at Davis Besse
Description
Upgrade (1) 1024 ACAR 6E550-52-1 "A" line drop at Davis Besse
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.c
Title
Reconductor (possible rebuild) 15.6 miles of 954 ACSR 45/7 on the Davis Besse - AC2-103 Tap 345 kV line
Description
Reconductor (possible rebuild) 15.6 miles of 954 ACSR 45/7 on the Davis Besse - AC2-103 Tap 345 kV line using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$91,775,258
Allocated Cost ($USD)
$0
Time Estimate
57 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.d
Title
Upgrade (2) 3500 SAC 127 line drops at Davis Besse
Description
Upgrade (2) 3500 SAC 127 line drops at Davis Besse
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.e
Title
Upgrade 3500 SAC B65 breaker leads and subconductor (D42 to wave trap) at Davis Besse
Description
Upgrade 3500 SAC B65 breaker leads and subconductor (D42 to wave trap) at Davis Besse
Total Cost ($USD)
$197,592
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.f
Title
Reconductor (possible rebuild) 18.7 miles of 954 ACSR 48/7 on the Davis Besse - AC2-103 TAP 345kV
Description
Reconductor (possible rebuild) 18.7 miles of 954 ACSR 48/7 on the Davis Besse - AC2-103 TAP 345kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$111,822,087
Allocated Cost ($USD)
$0
Time Estimate
64 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.g
Title
Upgrade (2) Wave Traps at Davis Besse
Description
Upgrade (2) Wave Traps at Davis Besse
Total Cost ($USD)
$620,599
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.h
Title
Upgrade Circuit Breaker 34564 at Davis Besse
Description
Upgrade Circuit Breaker 34564 at Davis Besse
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$0
Time Estimate
54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9228.0
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
n9228.0 / TC1-ATSI-002.b
Title
Rebuild 6.6 miles of the Lallendorf-Monroe 345 kV line and install OPGW. Replace line drops and wave traps at Lallendorf.
Description
Rebuild approximately 6.6 miles of the Lallendorf-Monroe 345 kV line from Lallendorf to the state line. Transfer and reuse approximately 0.9 miles of existing conductor on the Fostoria Central – Lallendorf 345 kV line to maintain double circuit with Lallendorf – Monroe line. Transfer and reuse approximately 5.7 miles of existing conductor on the Lemoyne – Majestic 345 kV line to maintain double circuit with Lallendorf – Monroe line. At Lallendorf substation, Replace line drops and (2) wave traps on the Monroe terminal.
Total Cost ($USD)
$38,362,639
Allocated Cost ($USD)
$0
Time Estimate
29 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)

System Reinforcement: s3148.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s3148.1
Title
05WHIPPLEDTC 345.0 kV to 05DESOTO 345.0 kV ckt 1 - s3148.1
Description
Sorenson - Desoto 345kV: Rebuild the ~51.5 mile line as is using double circuit 345kV construction. Replace jumpers at Sorenson and Desoto to accommodate the new structure entrances at the stations.
Cost Information
Time Estimate
Jun 10 2027

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05DESOTO-05WHIPPLEDTC 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18626
Title
05FLTLCK 765.0 kV to 05GAVIN_RF 765.0 kV ckt 1 - Replace Equipment
Description
At Flatlick Station replace the following equipment: CB-A, CB-B, GCB A PH. A, GCB A PH. B, GCB A PH. C, GCB B PH. A, GCB B PH. B, GCB B PH. C, Traps, CTTL 3000 Amps
Total Cost ($USD)
$2,000,000
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
05FLTLCK-05GAVIN_RF 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18687
Title
05HANGRCK_RJ 765.0 kV to 05HANG R 765.0 kV ckt Z1 - Replace Equipment
Description
At Hanging Rock Station replace the following equipment: D1S1 PH A, D1S1 PH B, D1S1 PH C, D1S2 PH A, D1S2 PH B, D1S2 PH C, D2S1 PH A, D2S1 PH B, D2S1 PH C, D2S2 PH A, D2S2 PH B, D2S2 PH C, Jefferson Trap PH A, Jefferson Trap PH B, Jefferson Trap PH C
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
05HANG R-05HANGRCK_RJ 765.0 kV Ckt Z1 line(Any)

System Reinforcement: n9243.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9243.0 / AEPSERG13
Title
Expand Jefferson 345 kV station. Install a second 765/345 kV 750 MVA transformer. Install a second Jefferson - Clifty Creek 345 kV single circuit ~0.8 miles.
Description
At the Jefferson Station: • Expand the northeast corner of the station • Remove Circuit breaker C1 • Install one (1) new 765/345 kV transformer and associated equipment • Install one (1) new 765 kV circuit breaker with associated control relaying and breaker disconnect switches • Install one (1) new 345 kV circuit breaker with associated control relaying and breaker disconnect switches • Install a new station service center At the Clifty Creek Station: • Extend 345 kV bus 1 and 2 to make room for a new breaker string • Move a section of the 138 kV bus underground to make room for the new breaker string • Relocate circuit breaker S to the new string • Install two (2) new 345 kV circuit breakers on the new string •Remove the existing Jefferson – Clifty Creek 345 kV line •Construct a new Jefferson – Clifty Creek 345 kV double circuit line •Evaluate line settings for all appropriate lines •Install direct fiber relaying between the Jefferson and Clifty Creek station •Associated conductors (buswork, ground grid, jumpers), telecom terminal equipment, insulators, arresters, foundations, and structures
Total Cost ($USD)
$200,238,000
Allocated Cost ($USD)
$0
Time Estimate
55 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
05JEFRSO-05JEFRSO 345.0/765.0 kV Ckt 2 transformer(Any)
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3775.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.1
Title
Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line
Description
Outside of the Green Acres substation, swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line to the University Park N-Olive 345 kV line to create a University Park N-Green Acres-Olive and St. John-Olive 345 kV lines.
Cost Information
Time Estimate
Dec 01 2026

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18635
Title
05MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Equipment
Description
Replace wave tap at Maliszewski towards Marysville along with circuit breakers, disconnects, and Sub Conductor.
Total Cost ($USD)
$24,200,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18680
Title
05MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Equipment
Description
Replace wave trap and associated equipment on Marysville Reactor towards Maliszewski.
Total Cost ($USD)
$2,200,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b3878.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3878.1
Title
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station
Description
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station. In addition, the project will upgrade the existing wavetrap towards Sorenson.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b3851.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.1 / B3851.1
Title
Rebuild Allen-RP Mone 345kV
Description
Rebuild Allen –R.P. Mone 345kV line (18.6 miles).
Cost Information
Time Estimate
Jun 01 2027

Contingent

Note: Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 may need this upgrade in-service to be deliverable to the PJM system. If AG2-029 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18821
Title
AEP Reinforcements for DEOK New Sub and New 345kV Line from Tanner's Creek
Description
AEP Scope of Work: At Tanners Creek station- install a 345 kV circuit breaker "T", relocate Lawrenceburg #1 345 kV line (between breakers T and T2), relocate Miami Fort 345 kV line (between breakers T and T1), relocate formerly East Bend 345 kV line (to Idlewild Duke station) (between breakers S and S1), and install new Tanners Creek - Idlewild 345 kV line #2 (between breakers R and R1), ~0.35 miles of AEP install and ~2.48 miles of Duke install.
Total Cost ($USD)
$6,700,000
Allocated Cost ($USD)
$0
Time Estimate
72 to 84 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
(Pending) / F4504
Title
DEOK New Sub and New 345kV Line from Tanner's Creek
Description
This Network Upgrade will be joint effort between DEOK & AEP to mitigate the Miami Fort - Tanner's Creek 345kV violations. DEOK Scope of Work: - DEOK will construct a new 5-breaker Ring Bus, 345kV Switching Station in Northern Kentucky called 'Idlewild'(Lat: 39° 5'15.11"N, Long: 84°49'10.14"W) - DEOK will loop the Tanner's Creek (AEP) - East Bend (DEOK) and Miami Fort (DEOK) - Terminal (DEOK) 345kV circuits into Idlewild Substation - In order to loop the Miami Fort - Terminal circuit into Idlewild Substation, DEOK will retire ~0.68 miles of the Miami Fort - Terminal circuit and add ~0.95 miles of new 345kV conductor (954ACSR 45x7, 2cond/ph, 100C). The new conductor will be built on existing DEOK easement. - DEOK will construct a new 345kV circuit from Idlewild substation to a pole that is just outside AEP's Tanner's Creek Substation. This circuit will be ~2.48 miles long with (1) Ohio River Crossing. The new 345kV circuit will be built will 954ACSS/TW, 2-conductor/phase, 200C conductor. Part of the new 345kV circuit will be built on existing DEOK easement, but DEOK will need to obtain ~1.0 mile of new easement. Line ownership for this new circuit will change at the tower which is just outside AEP's Tanner's Creek Substation in Lawrenceburg, Indiana.
Total Cost ($USD)
$72,000,000
Allocated Cost ($USD)
$0
Time Estimate
72 to 84 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-029 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-029 could receive cost allocation. Although AG2-029 may not presently have cost responsibility for this upgrade, AG2-029 is a potential Aggregate Pool Contributor.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P1-2_#7441_100545_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#7445_05MARYSV 765_B_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#7441_05SORENS 765_J1_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P2-2_#9456_06DEARB1 345_1_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P7-1_#485___SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#7446_05MARYSV 765_B2_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineDEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#9456_06DEARB1 345_DC_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineDEOK_P4_1579_EASTBEND_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
          New AG2-165 765kV swyd - AEP: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-165, AG2-212, AG2-328
        
          Powerton ;B 345 kV  (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-363, AG2-364
        
          Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-660, AH1-044, AH1-150, AH1-151
        
          Byron - Wayne 345 kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AH1-146, AH1-147
        

Attachments

AG2-029 One Line Diagram

AG2-029 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.