AG2-088 Phase I Study Report

v1.00 released 2025-10-29 20:49

Midlothian 230 kV

150.0 MW Capacity / 150.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Hermon Energy Center, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Chesterfield County, Virginia. The installed facilities will have a total capability of 150.0 MW with 150.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-088
Project Name:
Midlothian 230 kV
Project Developer Name:
Hermon Energy Center, LLC
State:
Virginia
County:
Chesterfield
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
150.0
MWE:
150.0
MWC:
150.0
Battery Storage Specification:
600.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-088 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system at the Midlothian 230 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-088 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-088Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$3,500,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$8,000,000$8,000,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$25,765,763$25,765,763
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$37,265,763$33,765,763

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-088

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-088 Project due at DP1
ABA - B
AG2-088$3,376,576$600,000$2,776,576

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install the Point of Change in Ownership (PCO) disconnect switch, the overhead line conductor from the PCO to the bus position that serves as the Point of Interconnection (POI), as well as any metering and associated protection equipment.$3,500,000 $3,500,000
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Add one (1) new 230 kV breaker to the existing Midlothian 230 kV Substation. Additional substation modification/expansion cost may be required after detailed design.$8,000,000 $8,000,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 46 to 50 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-088 was evaluated as a 150.0 MW (150.0 MW Capacity) injection in the Dominion area.

AG2-088 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC203.13 %678.68B1378.616.68
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC185.6 %830.0C1540.516.67
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC185.6 %830.0C1540.4916.67
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC173.49 %830.0C1439.9719.7
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC173.49 %830.0C1439.9719.7
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC140.76 %678.68B955.2811.88
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Base Case
SingleAC113.92 %678.68A773.1612.71
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P7-1: LN 2066-282_SRT-S
TowerAC111.23 %830.0C923.1916.44
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P7-1: LN 219-282_SRT-A
TowerAC110.89 %830.0C920.4316.44
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC202.03 %678.68B1371.1716.68
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC184.71 %830.0C1533.1116.67
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC184.71 %830.0C1533.116.67
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC172.6 %830.0C1432.6119.7
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC172.6 %830.0C1432.6119.7
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC139.68 %678.68B947.9811.88
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Base Case
SingleAC112.86 %678.68A765.9712.71
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P7-1: LN 2066-282_SRT-S
TowerAC110.36 %830.0C916.016.44
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P7-1: LN 219-282_SRT-A
TowerAC110.03 %830.0C913.2616.44
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC196.14 %678.68B1331.1415.41
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC182.57 %830.0C1515.3715.41
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC182.57 %830.0C1515.3415.41
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC175.31 %830.0C1455.0818.19
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC175.31 %830.0C1455.0818.19
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC144.42 %678.68B980.1210.81
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Base Case
SingleAC108.58 %678.68A736.9211.6
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P7-1: LN 2066-282_SRT-S
TowerAC108.52 %830.0C900.7515.08
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P7-1: LN 219-282_SRT-A
TowerAC108.2 %830.0C898.0215.08
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC198.54 %661.76B1313.8815.41
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC185.18 %809.0C1498.115.41
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC185.18 %809.0C1498.0815.41
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC177.73 %809.0C1437.8218.19
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC177.73 %809.0C1437.8218.19
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC145.49 %661.76B962.8210.81
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P7-1: LN 2066-282_SRT-S
TowerAC109.2 %809.0C883.4615.08
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P7-1: LN 219-282_SRT-A
TowerAC108.87 %809.0C880.7315.08
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Base Case
SingleAC108.74 %661.76A719.6211.6
GD2DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S
SingleAC137.15 %1057.5B1450.3352.94
GD2DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: 562T563_SRT-S
BreakerAC125.36 %1265.1C1585.9852.91
GD2DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC123.56 %1265.1C1563.1553.03
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC195.13 %661.76B1291.3115.41
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC182.39 %809.0C1475.5715.41
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC182.39 %809.0C1475.5415.41
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC174.94 %809.0C1415.2718.19
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC174.94 %809.0C1415.2718.19
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC142.1 %661.76B940.3810.81
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P7-1: LN 2066-282_SRT-S
TowerAC106.44 %809.0C861.0715.08
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P7-1: LN 219-282_SRT-A
TowerAC106.1 %809.0C858.3515.08
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Base Case
SingleAC105.36 %661.76A697.2311.6
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC127.97 %3220.44B4121.2823.27
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC126.02 %3220.44B4058.2723.38
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC175.45 %3220.44B5650.1449.13
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC154.63 %3940.0C6092.4349.56
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC154.23 %3940.0C6076.849.61
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC152.97 %3940.0C6027.1349.35
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC136.69 %3220.44B4402.0743.39
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC132.12 %3940.0C5205.644.7
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-1: G202_SRT-S
BreakerAC131.07 %3118.0C4086.8840.52
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B1_SRT-S
BusAC126.92 %3118.0C3957.4440.68
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B2_SRT-S
BusAC126.92 %3118.0C3957.4440.68
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Base Case
SingleAC113.34 %3193.18A3619.1340.68
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: LN 2090-256_SRT-S
TowerAC104.73 %3940.0C4126.1842.18
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: LN 2054-2135_SRT-A
TowerAC104.47 %3940.0C4115.9540.92
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57302_SRT-S
BreakerAC161.07 %3118.0C5022.1631.15
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC150.27 %3220.44B4839.4529.41
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC147.45 %3220.44B4748.630.86
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC134.78 %3940.0C5310.4930.72
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T594_SRT-S
BreakerAC130.91 %3940.0C5157.7329.48
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 515T594_SRT-S
BreakerAC130.47 %3940.0C5140.4629.41
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T573_SRT-S
BreakerAC128.18 %3940.0C5050.2530.92
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-S
BreakerAC210.08 %3940.0C8277.0248.23
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC174.96 %3940.0C6893.440.7
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC172.64 %3220.44B5559.8835.42
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC171.66 %3220.44B5528.2735.93
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 57502_SRT-S
BreakerAC169.18 %3118.0C5274.9933.74
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: H1T581_SRT-S
BreakerAC150.52 %3940.0C5930.6535.87
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC148.0 %3940.0C5831.0435.42
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B2_SRT-S
BusAC128.28 %3118.0C3999.6627.25
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B1_SRT-S
BusAC128.28 %3118.0C3999.6627.25
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Base Case
SingleAC118.49 %3193.18A3783.5627.25
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC118.03 %3940.0C4650.5828.24
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC117.81 %3940.0C4641.5628.24
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-S
BreakerAC211.93 %3940.0C8350.2146.77
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 545T552_SRT-S
BreakerAC182.6 %3118.0C5693.4334.68
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC179.85 %3220.44B5791.8235.34
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC179.37 %3940.0C7067.1439.46
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC175.06 %3220.44B5637.734.81
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC154.28 %3940.0C6078.7935.34
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: H3T552_SRT-S
BreakerAC154.01 %3940.0C6067.8935.31
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P2-2: MORRISVILLE B1_SRT-S
BusAC140.84 %3118.0C4391.426.75
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Base Case
SingleAC129.41 %3220.44A4167.6126.75
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P7-1: LN 2-2199_SRT-A-1
TowerAC124.66 %3940.0C4911.827.83
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P7-1: LN 2-2199_SRT-A-2
TowerAC124.41 %3940.0C4901.6127.83
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC120.67 %3940.0C4754.2127.52

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:203.13 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1378.6
MW Contribution:16.68
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
4.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.018

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1540.5
MW Contribution:16.67
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.541
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.672
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.388
970937AG2-583 GEN
Solar/Wind Harmer
32.774
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.35
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.229
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.484
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.927
3147666LOUISA
Solar/Wind Helper
0.538
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.238
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3151921BEARGRDN G2
50/50
4.541
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.895
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.178
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
0.548
944601AF1-125 GEN
Solar/Wind Harmer
11.266
972205AH1-687 GEN
50/50
22.146
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.67
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.409
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.529
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.745
3151211GRAVEL5
Adder
4.745
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
LAGNLTFEXP_LAGN->PJM
CLTF
1.77
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.515
TVALTFEXP_TVA->PJM
CLTF
0.864
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.202
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1540.49
MW Contribution:16.67
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.671
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.387
970937AG2-583 GEN
Solar/Wind Harmer
32.773
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.835
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.349
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.23
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.485
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.928
3147666LOUISA
Solar/Wind Helper
0.539
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.894
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.177
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
0.549
944601AF1-125 GEN
Solar/Wind Harmer
11.266
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.237
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.53
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
972205AH1-687 GEN
50/50
22.145
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.669
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.408
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.746
3151211GRAVEL5
Adder
4.746
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
LAGNLTFEXP_LAGN->PJM
CLTF
1.769
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.514
TVALTFEXP_TVA->PJM
CLTF
0.864
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.49 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1439.97
MW Contribution:19.7
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.012

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.49 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1439.97
MW Contribution:19.7
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.012

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.76 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:955.28
MW Contribution:11.88
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.855
3144293JTRSVLE
50/50
0.72
970535AG2-341 GEN
50/50
2.712
3152661PLYWOOD A
50/50
0.296
3146776BUCKING
Solar/Wind Harmer
1.65
3146776BUCKING
Solar/Wind Harmer
0.134
970301AG2-198 GEN
Solar/Wind Harmer
12.269
971741AH1-377 GEN
Solar/Wind Harmer
26.723
3147133PAMPLIN
Solar/Wind Harmer
0.266
3147133PAMPLIN
Solar/Wind Harmer
0.213
958211AF2-115 GEN
Solar/Wind Harmer
3.036
963191AG1-168 GEN
Solar/Wind Harmer
1.012
316034AC1-036 C
Solar/Wind Harmer
0.016
970323AG2-213 GEN
Solar/Wind Harmer
9.123
971775AH1-396 GEN
Solar/Wind Harmer
0.342
970933AG2-581 GEN
Solar/Wind Harmer
15.623
970099AG2-077 GEN
Solar/Wind Harmer
20.485
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.109
964791AG1-342 GEN
Solar/Wind Harmer
2.773
3146843MT LREL
Solar/Wind Harmer
0.144
3146843MT LREL
Solar/Wind Harmer
0.144
939181AE1-148 GEN
Solar/Wind Harmer
6.905
971489AH1-241 GEN
Solar/Wind Harmer
7.229
971223AH1-071 GEN
Solar/Wind Harmer
0.95
316222AC1-221 GEN
Solar/Wind Harmer
0.322
942751AE2-291 GEN
Solar/Wind Harmer
4.153
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3143526WINTERP
Solar/Wind Harmer
0.379
3145593CAROLNA
Solar/Wind Harmer
0.072
3145593CAROLNA
Solar/Wind Harmer
0.072
966811AG1-552 GEN
Solar/Wind Harmer
0.782
3145593CAROLNA
Solar/Wind Harmer
0.09
3145783HORNRTN
Solar/Wind Harmer
1.251
3145783HORNRTN
Solar/Wind Harmer
1.001
3145783HORNRTN
Solar/Wind Harmer
0.313
3145783HORNRTN
Solar/Wind Harmer
0.125
316426AA2-053 GEN
Solar/Wind Harmer
0.231
316274AC1-208 GEN
Solar/Wind Harmer
0.318
966001AG1-469 GEN
Solar/Wind Helper
0.176
3151931BEARGRDN S1
50/50
5.924
3151911BEARGRDN G1
50/50
4.59
3144293JTRSVLE
50/50
0.855
3151531CLOVER1
50/50
3.882
3151601KERR 3
50/50
0.286
3151581KERR 1
50/50
0.102
3147043LAWRENC
50/50
0.994
970119AG2-088 GEN
50/50
11.876
3151261ROARAP2
50/50
0.09
3151391GASTONA
50/50
0.153
3151411GASTONB
50/50
0.153
972003AH1-546 GEN
Solar/Wind Harmer
20.35
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.165
970937AG2-583 GEN
Solar/Wind Harmer
24.641
3146926FARMVIL
Solar/Wind Harmer
0.208
316336AC2-165 C
Solar/Wind Harmer
0.011
963171AG1-166 GEN
Solar/Wind Harmer
1.35
971563AH1-280 GEN
Solar/Wind Harmer
2.699
3143336POWHATN
Solar/Wind Harmer
4.458
970685AG2-442 GEN
Solar/Wind Harmer
17.473
962491AG1-098 GEN
Solar/Wind Harmer
12.124
315693AD1-088 GEN
Solar/Wind Harmer
10.001
957481AF2-042 GEN
Solar/Wind Harmer
51.213
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.005
970401AG2-262 GEN
Solar/Wind Harmer
0.847
971377AH1-170 GEN
Solar/Wind Harmer
1.446
3147623JAMES R
Solar/Wind Harmer
0.314
971065AG2-659 GEN
Solar/Wind Harmer
5.084
316003AC1-222 GEN
Solar/Wind Harmer
0.003
316129AC1-054 GEN
Solar/Wind Harmer
0.434
971795AH1-408 GEN
Solar/Wind Harmer
6.303
3143226MDLTHAN
Solar/Wind Harmer
0.089
960081AF2-299 GEN
Solar/Wind Harmer
0.721
3143526WINTERP
Solar/Wind Harmer
0.379
3145783HORNRTN
Solar/Wind Harmer
0.07
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.304
3146263WOODLND
Solar/Wind Harmer
0.058
316011AB1-132 GEN
Solar/Wind Harmer
1.027
962571AG1-106 GEN
Solar/Wind Harmer
0.804
3147983MERCK5
Solar/Wind Helper
0.056
3151921BEARGRDN G2
50/50
4.59
3144293JTRSVLE
50/50
0.855
970413AG2-270 GEN
50/50
16.942
3151591KERR 2
50/50
0.286
3151261ROARAP2
50/50
0.088
3151391GASTONA
50/50
0.153
3151411GASTONB
50/50
0.153
3146776BUCKING
Solar/Wind Harmer
0.149
3146926FARMVIL
Solar/Wind Harmer
0.208
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
3.067
3147133PAMPLIN
Solar/Wind Harmer
0.836
971193AH1-056 GEN
Solar/Wind Harmer
16.215
963181AG1-167 GEN
Solar/Wind Harmer
1.012
316313AB2-026
Solar/Wind Harmer
0.158
316258AE1-075 C
Solar/Wind Harmer
0.189
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.789
959311AF2-222 GEN
Solar/Wind Harmer
19.523
970257AG2-171 GEN
Solar/Wind Harmer
6.842
315785AD2-033 C
Solar/Wind Harmer
1.673
964241AG1-285 GEN
Solar/Wind Harmer
12.307
316478AD1-087 GEN
Solar/Wind Harmer
0.632
316486AD2-202 GEN
Solar/Wind Harmer
0.186
316131AB2-060 GEN
Solar/Wind Harmer
0.54
970221AG2-151 GEN
Solar/Wind Harmer
7.229
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.419
971683AH1-343 GEN
Solar/Wind Harmer
4.069
3147043LAWRENC
Solar/Wind Harmer
0.062
316283AC2-100 C
Solar/Wind Harmer
0.149
313506AB2-031 GEN
Solar/Wind Harmer
0.228
316210AC1-098 GEN
Solar/Wind Harmer
0.545
3146263WOODLND
Solar/Wind Harmer
0.058
316327AA2-057 GEN
Solar/Wind Harmer
0.087
3148013FISHERV
Solar/Wind Helper
0.174
316499AE2-029_GEN
Solar/Wind Helper
0.51
3132273ORANGE
Solar/Wind Helper
0.025
315616AA1-038_C
Solar/Wind Helper
0.547
972205AH1-687 GEN
50/50
22.387
3151541CLOVER2
50/50
3.864
3151611KERR 4
50/50
0.286
3151621KERR 5
50/50
0.286
3151631KERR 6
50/50
0.286
3151641KERR 7
50/50
0.286
316303AF2-085
50/50
1.583
3151281ROARAP4
50/50
0.087
3151281ROARAP4
50/50
0.082
971845AH1-439 GEN
Solar/Wind Harmer
18.454
970285AG2-188 GEN
Solar/Wind Harmer
31.353
315657AE1-056 GEN
Solar/Wind Harmer
9.184
946301AF1-294 GEN
Solar/Wind Harmer
4.993
961791AG1-021 GEN
Solar/Wind Harmer
2.429
970683AG2-441 GEN
Solar/Wind Harmer
15.601
970681AG2-440 GEN
Solar/Wind Harmer
12.481
3144303KENBRDG
Solar/Wind Harmer
0.171
971443AH1-215 GEN
Solar/Wind Harmer
3.563
971967AH1-528 GEN
Solar/Wind Harmer
31.246
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.35
3147173SINAI
Solar/Wind Harmer
0.127
3147243WELCO
Solar/Wind Harmer
0.079
970831AG2-522 GEN
Solar/Wind Harmer
4.741
270494AE1-108_GEN
Solar/Wind Harmer
1.279
970865AG2-541 GEN
Solar/Wind Harmer
3.559
316123AC1-075 GEN
Solar/Wind Harmer
0.118
970165AG2-112 GEN
Solar/Wind Harmer
0.702
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316087AB2-174 GEN
Solar/Wind Harmer
0.002
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.012
971283AH1-107 GEN
Solar/Wind Harmer
1.012
3137643SOCKMAN
Solar/Wind Harmer
0.291
315607AA1-063A GEN
Solar/Wind Harmer
0.135
3146043SEABORD
Solar/Wind Harmer
0.065
971447AH1-217 GEN
Solar/Wind Harmer
1.965
3146033SCOT NK
Solar/Wind Harmer
0.227
965291AG1-394 GEN
Solar/Wind Harmer
0.252
315652AC1-086 GEN
Solar/Wind Harmer
6.215
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.104
3148013FISHERV
Solar/Wind Helper
0.1
3148463FAIRFLD
Solar/Wind Helper
0.121
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.002
LAGNLTFEXP_LAGN->PJM
CLTF
1.432
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.169
TVALTFEXP_TVA->PJM
CLTF
0.699
CPLELTFEXP_CPLE->PJM
CLTF
3.696
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.709
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.172
MECLTFEXP_MEC->PJM
CLTF
0.251
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.442
LGEELTFEXP_LGEE->PJM
CLTF
0.021
WECLTFEXP_WEC->PJM
CLTF
0.005

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.92 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:773.16
MW Contribution:12.71
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.707
3151911BEARGRDN G1
50/50
4.422
3144293JTRSVLE
50/50
0.69
970119AG2-088 GEN
50/50
12.707
3151531CLOVER1
50/50
2.017
3151601KERR 3
50/50
0.192
3151581KERR 1
50/50
0.069
3147043LAWRENC
50/50
0.8
3151261ROARAP2
50/50
0.077
3150851SPRUNCC
50/50
0.297
3151051BRUNSWICKS1
50/50
1.63
3151021BRUNSWICKG1
50/50
0.785
971451AH1-221 GEN
50/50
2.385
315243AE2-183_GT3
50/50
0.972
972003AH1-546 GEN
Solar/Wind Harmer
19.447
970937AG2-583 GEN
Solar/Wind Harmer
23.874
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.178
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.396
963171AG1-166 GEN
Solar/Wind Harmer
1.09
971563AH1-280 GEN
Solar/Wind Harmer
2.18
970685AG2-442 GEN
Solar/Wind Harmer
13.857
962491AG1-098 GEN
Solar/Wind Harmer
7.06
971377AH1-170 GEN
Solar/Wind Harmer
1.272
3147623JAMES R
Solar/Wind Harmer
0.276
315693AD1-088 GEN
Solar/Wind Harmer
5.685
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.095
970401AG2-262 GEN
Solar/Wind Harmer
0.559
957481AF2-042 GEN
Solar/Wind Harmer
24.966
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.579
316129AC1-054 GEN
Solar/Wind Harmer
0.309
3143526WINTERP
Solar/Wind Harmer
0.415
971795AH1-408 GEN
Solar/Wind Harmer
5.206
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.641
3145783HORNRTN
Solar/Wind Harmer
0.061
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
4.587
316023GEN1_S
Solar/Wind Harmer
0.127
3147983MERCK5
Solar/Wind Helper
0.057
3151921BEARGRDN G2
50/50
4.422
3144293JTRSVLE
50/50
0.69
970413AG2-270 GEN
50/50
8.802
3151591KERR 2
50/50
0.192
3151261ROARAP2
50/50
0.076
3150861SPRUNCD
50/50
0.297
3151031BRUNSWICKG2
50/50
0.785
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.156
316258AE1-075 C
Solar/Wind Harmer
0.187
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.737
970909AG2-566 GEN
Solar/Wind Harmer
2.353
3147133PAMPLIN
Solar/Wind Harmer
0.682
971193AH1-056 GEN
Solar/Wind Harmer
13.238
963181AG1-167 GEN
Solar/Wind Harmer
0.817
959311AF2-222 GEN
Solar/Wind Harmer
15.236
970257AG2-171 GEN
Solar/Wind Harmer
5.302
315785AD2-033 C
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
9.125
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970221AG2-151 GEN
Solar/Wind Harmer
6.362
316478AD1-087 GEN
Solar/Wind Harmer
0.328
316486AD2-202 GEN
Solar/Wind Harmer
0.096
3147043LAWRENC
Solar/Wind Harmer
0.05
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.274
971683AH1-343 GEN
Solar/Wind Harmer
2.442
313506AB2-031 GEN
Solar/Wind Harmer
0.2
970917AG2-570 GEN
Solar/Wind Harmer
5.117
316365GEN2_N
Solar/Wind Harmer
0.127
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.562
3132273ORANGE
Solar/Wind Helper
0.024
3144293JTRSVLE
50/50
0.69
3144293JTRSVLE
50/50
0.581
970535AG2-341 GEN
50/50
1.885
3152661PLYWOOD A
50/50
0.185
3151041BRUNSWICKG3
50/50
0.785
972187AH1-678 GEN
50/50
1.802
315242AE2-183_GT2
50/50
0.972
315241AE2-183_GT1
50/50
0.966
972185AH1-677 GEN
50/50
3.505
970533AG2-339 GEN
50/50
5.074
970531AG2-338 GEN
50/50
2.029
3146776BUCKING
Solar/Wind Harmer
1.508
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
9.412
3147133PAMPLIN
Solar/Wind Harmer
0.217
3147133PAMPLIN
Solar/Wind Harmer
0.174
958211AF2-115 GEN
Solar/Wind Harmer
2.452
963191AG1-168 GEN
Solar/Wind Harmer
0.817
971741AH1-377 GEN
Solar/Wind Harmer
19.558
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.069
971775AH1-396 GEN
Solar/Wind Harmer
0.265
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
6.362
962561AG1-105 GEN
Solar/Wind Harmer
4.763
939181AE1-148 GEN
Solar/Wind Harmer
4.697
971223AH1-071 GEN
Solar/Wind Harmer
1.017
964791AG1-342 GEN
Solar/Wind Harmer
1.83
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
970099AG2-077 GEN
Solar/Wind Harmer
9.986
3143526WINTERP
Solar/Wind Harmer
0.415
970933AG2-581 GEN
Solar/Wind Harmer
5.925
316181AB2-040 GEN
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.086
3145783HORNRTN
Solar/Wind Harmer
0.869
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.204
966001AG1-469 GEN
Solar/Wind Helper
0.174
972205AH1-687 GEN
50/50
21.569
316303AF2-085
50/50
1.694
3151541CLOVER2
50/50
2.007
3151611KERR 4
50/50
0.192
3151621KERR 5
50/50
0.192
3151631KERR 6
50/50
0.192
3151641KERR 7
50/50
0.192
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
971285AH1-108 GEN
50/50
0.486
963041AG1-153 GEN
50/50
1.59
315244AE2-183_ST
50/50
1.681
971845AH1-439 GEN
Solar/Wind Harmer
16.786
970285AG2-188 GEN
Solar/Wind Harmer
28.258
315657AE1-056 GEN
Solar/Wind Harmer
7.498
946301AF1-294 GEN
Solar/Wind Harmer
4.032
961791AG1-021 GEN
Solar/Wind Harmer
1.962
970683AG2-441 GEN
Solar/Wind Harmer
12.373
970681AG2-440 GEN
Solar/Wind Harmer
9.898
3144303KENBRDG
Solar/Wind Harmer
0.132
971443AH1-215 GEN
Solar/Wind Harmer
2.755
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
1.107
316118AC1-105 GEN
Solar/Wind Harmer
0.222
970831AG2-522 GEN
Solar/Wind Harmer
3.422
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.107
971283AH1-107 GEN
Solar/Wind Harmer
1.107
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
10.427
3137643SOCKMAN
Solar/Wind Harmer
0.253
970865AG2-541 GEN
Solar/Wind Harmer
2.127
315607AA1-063A GEN
Solar/Wind Harmer
0.122
3146043SEABORD
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
12.427
970673AG2-436 GEN
Solar/Wind Harmer
8.285
970085AG2-068 GEN
Solar/Wind Harmer
3.058
970581AG2-369 GEN
Solar/Wind Harmer
2.63
941031AE2-094 GEN
Solar/Wind Harmer
10.513
944011AF1-069 GEN
Solar/Wind Harmer
3.435
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.783
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.427
CPLELTFEXP_CPLE->PJM
CLTF
3.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.625
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.208
NYPJM->LTFIMP_NY
CLTF
0.345

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2066-282_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2066-282_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.23 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:923.19
MW Contribution:16.44
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.81
3151911BEARGRDN G1
50/50
4.502
3144293JTRSVLE
50/50
0.7
970119AG2-088 GEN
50/50
16.441
972003AH1-546 GEN
Solar/Wind Harmer
26.109
970937AG2-583 GEN
Solar/Wind Harmer
32.485
316322AB2-045
Solar/Wind Harmer
1.45
3146776BUCKING
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
5.96
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.567
963171AG1-166 GEN
Solar/Wind Harmer
2.908
971563AH1-280 GEN
Solar/Wind Harmer
2.908
970685AG2-442 GEN
Solar/Wind Harmer
18.475
971377AH1-170 GEN
Solar/Wind Harmer
1.782
3147623JAMES R
Solar/Wind Harmer
0.221
962491AG1-098 GEN
Solar/Wind Harmer
9.39
3143226MDLTHAN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.718
316237AB2-079_GEN
Solar/Wind Harmer
0.403
970401AG2-262 GEN
Solar/Wind Harmer
0.704
957481AF2-042 GEN
Solar/Wind Harmer
33.096
315687AD1-152 GEN
Solar/Wind Harmer
1.157
971065AG2-659 GEN
Solar/Wind Harmer
4.696
3147043LAWRENC
Adder
0.745
316129AC1-054 GEN
Solar/Wind Harmer
0.805
971795AH1-408 GEN
Solar/Wind Harmer
6.476
316003AC1-222 GEN
Solar/Wind Harmer
0.786
960081AF2-299 GEN
Solar/Wind Harmer
0.821
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
970919AG2-571 GEN
Solar/Wind Harmer
2.043
970087AG2-069 GEN
Solar/Wind Harmer
6.029
3147983MERCK5
Solar/Wind Helper
0.056
3151921BEARGRDN G2
50/50
4.502
3144293JTRSVLE
50/50
0.7
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.811
316258AE1-075 C
Solar/Wind Harmer
0.73
316405AF2-144 C
Solar/Wind Harmer
0.77
3143336POWHATN
Solar/Wind Harmer
3.032
942461AE2-259 GEN
Solar/Wind Harmer
4.363
970909AG2-566 GEN
Solar/Wind Harmer
2.388
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.482
963181AG1-167 GEN
Solar/Wind Harmer
2.181
959311AF2-222 GEN
Solar/Wind Harmer
20.337
970257AG2-171 GEN
Solar/Wind Harmer
7.06
315785AD2-033 C
Solar/Wind Harmer
4.062
964241AG1-285 GEN
Solar/Wind Harmer
12.123
970221AG2-151 GEN
Solar/Wind Harmer
8.911
316131AB2-060 GEN
Solar/Wind Harmer
1.517
316478AD1-087 GEN
Solar/Wind Harmer
0.922
316486AD2-202 GEN
Solar/Wind Harmer
0.27
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.261
960061AF2-297 GEN
Solar/Wind Harmer
4.339
971683AH1-343 GEN
Solar/Wind Harmer
3.24
966621AG1-532 GEN
Solar/Wind Harmer
0.148
313506AB2-031 GEN
Solar/Wind Harmer
0.568
970917AG2-570 GEN
Solar/Wind Harmer
16.142
3148013FISHERV
Solar/Wind Helper
0.177
316499AE2-029_GEN
Solar/Wind Helper
0.512
315616AA1-038_C
Solar/Wind Helper
0.557
3132273ORANGE
Solar/Wind Helper
0.023
3144293JTRSVLE
50/50
0.7
3144293JTRSVLE
50/50
0.589
3146776BUCKING
Solar/Wind Harmer
-0.172
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.575
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.636
963191AG1-168 GEN
Solar/Wind Harmer
2.181
971741AH1-377 GEN
Solar/Wind Harmer
26.113
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.413
971775AH1-396 GEN
Solar/Wind Harmer
1.34
971489AH1-241 GEN
Solar/Wind Harmer
8.46
971223AH1-071 GEN
Solar/Wind Harmer
1.732
313527AB2-043 GEN
Solar/Wind Harmer
2.226
962561AG1-105 GEN
Solar/Wind Harmer
6.315
939181AE1-148 GEN
Solar/Wind Harmer
6.206
964791AG1-342 GEN
Solar/Wind Harmer
2.303
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.238
970933AG2-581 GEN
Solar/Wind Harmer
7.823
316181AB2-040 GEN
Solar/Wind Harmer
0.986
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.766
3145593CAROLNA
Solar/Wind Harmer
0.057
972187AH1-678 GEN
Adder
1.696
3145783HORNRTN
Solar/Wind Harmer
0.793
3145783HORNRTN
Solar/Wind Harmer
0.635
3145783HORNRTN
Solar/Wind Harmer
0.198
3145783HORNRTN
Solar/Wind Harmer
0.079
316426AA2-053 GEN
Solar/Wind Harmer
0.667
972185AH1-677 GEN
Adder
3.297
966001AG1-469 GEN
Solar/Wind Helper
0.17
972205AH1-687 GEN
50/50
21.959
316303AF2-085
50/50
2.192
971845AH1-439 GEN
Solar/Wind Harmer
22.482
970285AG2-188 GEN
Solar/Wind Harmer
35.716
315657AE1-056 GEN
Solar/Wind Harmer
9.289
946301AF1-294 GEN
Solar/Wind Harmer
5.962
961791AG1-021 GEN
Solar/Wind Harmer
2.908
970683AG2-441 GEN
Solar/Wind Harmer
16.495
970681AG2-440 GEN
Solar/Wind Harmer
13.196
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.668
316239AB2-077_GEN
Solar/Wind Harmer
0.403
316238AB2-078_GEN
Solar/Wind Harmer
0.403
270494AE1-108_GEN
Solar/Wind Harmer
2.875
316118AC1-105 GEN
Solar/Wind Harmer
0.668
970831AG2-522 GEN
Solar/Wind Harmer
4.476
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
13.768
946281AF1-292 GEN
Solar/Wind Harmer
0.164
316087AB2-174 GEN
Solar/Wind Harmer
1.019
970865AG2-541 GEN
Solar/Wind Harmer
2.825
3137643SOCKMAN
Solar/Wind Harmer
-0.028
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
315607AA1-063A GEN
Solar/Wind Harmer
0.655
3146043SEABORD
Solar/Wind Harmer
-0.006
970085AG2-068 GEN
Solar/Wind Harmer
4.019
970581AG2-369 GEN
Solar/Wind Harmer
3.457
941031AE2-094 GEN
Solar/Wind Harmer
11.99
944011AF1-069 GEN
Solar/Wind Harmer
3.757
971447AH1-217 GEN
Solar/Wind Harmer
2.264
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.102
3148463FAIRFLD
Solar/Wind Helper
0.123
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.318
LAGNLTFEXP_LAGN->PJM
CLTF
0.917
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.775
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.437
CPLELTFEXP_CPLE->PJM
CLTF
3.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.788
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.251
NYPJM->LTFIMP_NY
CLTF
0.338

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 219-282_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 219-282_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.89 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:920.43
MW Contribution:16.44
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.81
3151911BEARGRDN G1
50/50
4.502
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
16.437
972003AH1-546 GEN
Solar/Wind Harmer
26.108
970937AG2-583 GEN
Solar/Wind Harmer
32.483
316322AB2-045
Solar/Wind Harmer
1.45
3146776BUCKING
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
5.96
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.567
963171AG1-166 GEN
Solar/Wind Harmer
2.908
971563AH1-280 GEN
Solar/Wind Harmer
2.908
970685AG2-442 GEN
Solar/Wind Harmer
18.472
971377AH1-170 GEN
Solar/Wind Harmer
1.782
3147623JAMES R
Solar/Wind Harmer
0.221
962491AG1-098 GEN
Solar/Wind Harmer
9.388
3143526WINTERP
Solar/Wind Harmer
-0.072
3143226MDLTHAN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.716
316237AB2-079_GEN
Solar/Wind Harmer
0.403
970401AG2-262 GEN
Solar/Wind Harmer
0.703
957481AF2-042 GEN
Solar/Wind Harmer
33.086
315687AD1-152 GEN
Solar/Wind Harmer
1.156
971065AG2-659 GEN
Solar/Wind Harmer
4.694
3147043LAWRENC
Adder
0.744
316129AC1-054 GEN
Solar/Wind Harmer
0.804
971795AH1-408 GEN
Solar/Wind Harmer
6.473
316003AC1-222 GEN
Solar/Wind Harmer
0.786
960081AF2-299 GEN
Solar/Wind Harmer
0.821
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
970919AG2-571 GEN
Solar/Wind Harmer
2.042
970087AG2-069 GEN
Solar/Wind Harmer
6.026
3147983MERCK5
Solar/Wind Helper
0.056
3151921BEARGRDN G2
50/50
4.502
3144293JTRSVLE
50/50
0.699
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.811
316258AE1-075 C
Solar/Wind Harmer
0.73
316405AF2-144 C
Solar/Wind Harmer
0.77
3143336POWHATN
Solar/Wind Harmer
3.032
942461AE2-259 GEN
Solar/Wind Harmer
4.363
970909AG2-566 GEN
Solar/Wind Harmer
2.387
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.48
963181AG1-167 GEN
Solar/Wind Harmer
2.181
959311AF2-222 GEN
Solar/Wind Harmer
20.333
970257AG2-171 GEN
Solar/Wind Harmer
7.059
315785AD2-033 C
Solar/Wind Harmer
4.061
964241AG1-285 GEN
Solar/Wind Harmer
12.12
970221AG2-151 GEN
Solar/Wind Harmer
8.909
316131AB2-060 GEN
Solar/Wind Harmer
1.516
316478AD1-087 GEN
Solar/Wind Harmer
0.922
316486AD2-202 GEN
Solar/Wind Harmer
0.27
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.261
960061AF2-297 GEN
Solar/Wind Harmer
4.337
971683AH1-343 GEN
Solar/Wind Harmer
3.239
966621AG1-532 GEN
Solar/Wind Harmer
0.148
313506AB2-031 GEN
Solar/Wind Harmer
0.568
970917AG2-570 GEN
Solar/Wind Harmer
16.134
3148013FISHERV
Solar/Wind Helper
0.177
316499AE2-029_GEN
Solar/Wind Helper
0.512
315616AA1-038_C
Solar/Wind Helper
0.557
3132273ORANGE
Solar/Wind Helper
0.023
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.589
3146776BUCKING
Solar/Wind Harmer
-0.172
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.574
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.635
963191AG1-168 GEN
Solar/Wind Harmer
2.181
971741AH1-377 GEN
Solar/Wind Harmer
26.109
972205AH1-687 GEN
50/50
21.958
316303AF2-085
50/50
2.192
971845AH1-439 GEN
Solar/Wind Harmer
22.48
970285AG2-188 GEN
Solar/Wind Harmer
35.714
315657AE1-056 GEN
Solar/Wind Harmer
9.288
946301AF1-294 GEN
Solar/Wind Harmer
5.962
961791AG1-021 GEN
Solar/Wind Harmer
2.908
970683AG2-441 GEN
Solar/Wind Harmer
16.493
970681AG2-440 GEN
Solar/Wind Harmer
13.194
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.667
316233AE1-074 FULL
Solar/Wind Harmer
0.373
971281AH1-106 GEN
Solar/Wind Harmer
2.251
971283AH1-107 GEN
Solar/Wind Harmer
2.251
316239AB2-077_GEN
Solar/Wind Harmer
0.403
316238AB2-078_GEN
Solar/Wind Harmer
0.403
270494AE1-108_GEN
Solar/Wind Harmer
2.874
316118AC1-105 GEN
Solar/Wind Harmer
0.668
970831AG2-522 GEN
Solar/Wind Harmer
4.474
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
13.762
946281AF1-292 GEN
Solar/Wind Harmer
0.163
316087AB2-174 GEN
Solar/Wind Harmer
1.018
970865AG2-541 GEN
Solar/Wind Harmer
2.824
3137643SOCKMAN
Solar/Wind Harmer
-0.028
970673AG2-436 GEN
Solar/Wind Harmer
13.713
970673AG2-436 GEN
Solar/Wind Harmer
6.943
315607AA1-063A GEN
Solar/Wind Harmer
0.655
3146043SEABORD
Solar/Wind Harmer
-0.006
970085AG2-068 GEN
Solar/Wind Harmer
4.017
970581AG2-369 GEN
Solar/Wind Harmer
3.455
941031AE2-094 GEN
Solar/Wind Harmer
11.984
944011AF1-069 GEN
Solar/Wind Harmer
3.755
971447AH1-217 GEN
Solar/Wind Harmer
2.263
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.102
3148463FAIRFLD
Solar/Wind Helper
0.123
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.412
971775AH1-396 GEN
Solar/Wind Harmer
1.34
971489AH1-241 GEN
Solar/Wind Harmer
8.458
3143526WINTERP
Solar/Wind Harmer
-0.072
971223AH1-071 GEN
Solar/Wind Harmer
1.731
313527AB2-043 GEN
Solar/Wind Harmer
2.225
962561AG1-105 GEN
Solar/Wind Harmer
6.313
939181AE1-148 GEN
Solar/Wind Harmer
6.204
964791AG1-342 GEN
Solar/Wind Harmer
2.302
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.234
970933AG2-581 GEN
Solar/Wind Harmer
7.82
316181AB2-040 GEN
Solar/Wind Harmer
0.986
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.766
3145593CAROLNA
Solar/Wind Harmer
0.057
972187AH1-678 GEN
Adder
1.695
3145783HORNRTN
Solar/Wind Harmer
0.793
3145783HORNRTN
Solar/Wind Harmer
0.634
3145783HORNRTN
Solar/Wind Harmer
0.198
3145783HORNRTN
Solar/Wind Harmer
0.079
316426AA2-053 GEN
Solar/Wind Harmer
0.667
972185AH1-677 GEN
Adder
3.295
966001AG1-469 GEN
Solar/Wind Helper
0.17
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.11
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.323
LAGNLTFEXP_LAGN->PJM
CLTF
0.913
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.768
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.435
CPLELTFEXP_CPLE->PJM
CLTF
3.062
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.758
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.243
NYPJM->LTFIMP_NY
CLTF
0.339

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:202.03 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1371.17
MW Contribution:16.68
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
4.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.018

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.71 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1533.11
MW Contribution:16.67
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.541
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.672
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.388
970937AG2-583 GEN
Solar/Wind Harmer
32.774
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.35
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.229
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.484
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.927
3147666LOUISA
Solar/Wind Helper
0.538
3151921BEARGRDN G2
50/50
4.541
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.895
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.178
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
0.548
944601AF1-125 GEN
Solar/Wind Harmer
11.266
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.238
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.529
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
972205AH1-687 GEN
50/50
22.146
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.67
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.409
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.745
3151211GRAVEL5
Adder
4.745
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
LAGNLTFEXP_LAGN->PJM
CLTF
1.77
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.515
TVALTFEXP_TVA->PJM
CLTF
0.864
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.202
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.71 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1533.1
MW Contribution:16.67
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.671
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.387
970937AG2-583 GEN
Solar/Wind Harmer
32.773
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.835
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.349
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.23
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.485
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.928
3147666LOUISA
Solar/Wind Helper
0.539
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.894
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.177
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
0.549
944601AF1-125 GEN
Solar/Wind Harmer
11.266
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.237
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.53
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
972205AH1-687 GEN
50/50
22.145
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.669
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.408
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.746
3151211GRAVEL5
Adder
4.746
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
LAGNLTFEXP_LAGN->PJM
CLTF
1.769
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.514
TVALTFEXP_TVA->PJM
CLTF
0.864
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:172.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1432.61
MW Contribution:19.7
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.012

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:172.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1432.61
MW Contribution:19.7
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.012

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.68 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:947.98
MW Contribution:11.88
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.855
3144293JTRSVLE
50/50
0.72
970535AG2-341 GEN
50/50
2.712
3152661PLYWOOD A
50/50
0.296
3146776BUCKING
Solar/Wind Harmer
1.65
3146776BUCKING
Solar/Wind Harmer
0.134
970301AG2-198 GEN
Solar/Wind Harmer
12.269
971741AH1-377 GEN
Solar/Wind Harmer
26.723
3147133PAMPLIN
Solar/Wind Harmer
0.266
3147133PAMPLIN
Solar/Wind Harmer
0.213
958211AF2-115 GEN
Solar/Wind Harmer
3.036
963191AG1-168 GEN
Solar/Wind Harmer
1.012
316034AC1-036 C
Solar/Wind Harmer
0.016
970323AG2-213 GEN
Solar/Wind Harmer
9.123
971775AH1-396 GEN
Solar/Wind Harmer
0.342
970933AG2-581 GEN
Solar/Wind Harmer
15.623
970099AG2-077 GEN
Solar/Wind Harmer
20.485
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.109
964791AG1-342 GEN
Solar/Wind Harmer
2.773
3146843MT LREL
Solar/Wind Harmer
0.144
3146843MT LREL
Solar/Wind Harmer
0.144
939181AE1-148 GEN
Solar/Wind Harmer
6.905
971489AH1-241 GEN
Solar/Wind Harmer
7.229
971223AH1-071 GEN
Solar/Wind Harmer
0.95
3151931BEARGRDN S1
50/50
5.924
3151911BEARGRDN G1
50/50
4.59
3144293JTRSVLE
50/50
0.855
3151531CLOVER1
50/50
3.882
3151601KERR 3
50/50
0.286
3151581KERR 1
50/50
0.102
3147043LAWRENC
50/50
0.994
970119AG2-088 GEN
50/50
11.876
3151261ROARAP2
50/50
0.09
3151391GASTONA
50/50
0.153
3151411GASTONB
50/50
0.153
972003AH1-546 GEN
Solar/Wind Harmer
20.35
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.165
970937AG2-583 GEN
Solar/Wind Harmer
24.641
3146926FARMVIL
Solar/Wind Harmer
0.208
316336AC2-165 C
Solar/Wind Harmer
0.011
963171AG1-166 GEN
Solar/Wind Harmer
1.35
971563AH1-280 GEN
Solar/Wind Harmer
2.699
3143336POWHATN
Solar/Wind Harmer
4.458
970685AG2-442 GEN
Solar/Wind Harmer
17.473
962491AG1-098 GEN
Solar/Wind Harmer
12.124
315693AD1-088 GEN
Solar/Wind Harmer
10.001
957481AF2-042 GEN
Solar/Wind Harmer
51.213
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.005
970401AG2-262 GEN
Solar/Wind Harmer
0.847
971377AH1-170 GEN
Solar/Wind Harmer
1.446
3147623JAMES R
Solar/Wind Harmer
0.314
971065AG2-659 GEN
Solar/Wind Harmer
5.084
316003AC1-222 GEN
Solar/Wind Harmer
0.003
316129AC1-054 GEN
Solar/Wind Harmer
0.434
971795AH1-408 GEN
Solar/Wind Harmer
6.303
3143226MDLTHAN
Solar/Wind Harmer
0.089
960081AF2-299 GEN
Solar/Wind Harmer
0.721
3143526WINTERP
Solar/Wind Harmer
0.379
3145783HORNRTN
Solar/Wind Harmer
0.07
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.304
3146263WOODLND
Solar/Wind Harmer
0.058
316011AB1-132 GEN
Solar/Wind Harmer
1.027
962571AG1-106 GEN
Solar/Wind Harmer
0.804
3147983MERCK5
Solar/Wind Helper
0.056
3151921BEARGRDN G2
50/50
4.59
3144293JTRSVLE
50/50
0.855
970413AG2-270 GEN
50/50
16.942
3151591KERR 2
50/50
0.286
3151261ROARAP2
50/50
0.088
3151391GASTONA
50/50
0.153
3151411GASTONB
50/50
0.153
3146776BUCKING
Solar/Wind Harmer
0.149
3146926FARMVIL
Solar/Wind Harmer
0.208
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
3.067
3147133PAMPLIN
Solar/Wind Harmer
0.836
971193AH1-056 GEN
Solar/Wind Harmer
16.215
963181AG1-167 GEN
Solar/Wind Harmer
1.012
316313AB2-026
Solar/Wind Harmer
0.158
316258AE1-075 C
Solar/Wind Harmer
0.189
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.789
959311AF2-222 GEN
Solar/Wind Harmer
19.523
970257AG2-171 GEN
Solar/Wind Harmer
6.842
315785AD2-033 C
Solar/Wind Harmer
1.673
964241AG1-285 GEN
Solar/Wind Harmer
12.307
316478AD1-087 GEN
Solar/Wind Harmer
0.632
316486AD2-202 GEN
Solar/Wind Harmer
0.186
316131AB2-060 GEN
Solar/Wind Harmer
0.54
970221AG2-151 GEN
Solar/Wind Harmer
7.229
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.419
971683AH1-343 GEN
Solar/Wind Harmer
4.069
3147043LAWRENC
Solar/Wind Harmer
0.062
316283AC2-100 C
Solar/Wind Harmer
0.149
313506AB2-031 GEN
Solar/Wind Harmer
0.228
316210AC1-098 GEN
Solar/Wind Harmer
0.545
3146263WOODLND
Solar/Wind Harmer
0.058
316327AA2-057 GEN
Solar/Wind Harmer
0.087
3148013FISHERV
Solar/Wind Helper
0.174
316499AE2-029_GEN
Solar/Wind Helper
0.51
3132273ORANGE
Solar/Wind Helper
0.025
315616AA1-038_C
Solar/Wind Helper
0.547
316222AC1-221 GEN
Solar/Wind Harmer
0.322
942751AE2-291 GEN
Solar/Wind Harmer
4.153
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3143526WINTERP
Solar/Wind Harmer
0.379
3145593CAROLNA
Solar/Wind Harmer
0.072
3145593CAROLNA
Solar/Wind Harmer
0.072
966811AG1-552 GEN
Solar/Wind Harmer
0.782
3145593CAROLNA
Solar/Wind Harmer
0.09
3145783HORNRTN
Solar/Wind Harmer
1.251
3145783HORNRTN
Solar/Wind Harmer
1.001
3145783HORNRTN
Solar/Wind Harmer
0.313
3145783HORNRTN
Solar/Wind Harmer
0.125
316426AA2-053 GEN
Solar/Wind Harmer
0.231
316274AC1-208 GEN
Solar/Wind Harmer
0.318
966001AG1-469 GEN
Solar/Wind Helper
0.176
972205AH1-687 GEN
50/50
22.387
3151541CLOVER2
50/50
3.864
3151611KERR 4
50/50
0.286
3151621KERR 5
50/50
0.286
3151631KERR 6
50/50
0.286
3151641KERR 7
50/50
0.286
316303AF2-085
50/50
1.583
3151281ROARAP4
50/50
0.087
3151281ROARAP4
50/50
0.082
971845AH1-439 GEN
Solar/Wind Harmer
18.454
970285AG2-188 GEN
Solar/Wind Harmer
31.353
315657AE1-056 GEN
Solar/Wind Harmer
9.184
946301AF1-294 GEN
Solar/Wind Harmer
4.993
961791AG1-021 GEN
Solar/Wind Harmer
2.429
970683AG2-441 GEN
Solar/Wind Harmer
15.601
970681AG2-440 GEN
Solar/Wind Harmer
12.481
3144303KENBRDG
Solar/Wind Harmer
0.171
971443AH1-215 GEN
Solar/Wind Harmer
3.563
971967AH1-528 GEN
Solar/Wind Harmer
31.246
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.35
3147173SINAI
Solar/Wind Harmer
0.127
3147243WELCO
Solar/Wind Harmer
0.079
970831AG2-522 GEN
Solar/Wind Harmer
4.741
270494AE1-108_GEN
Solar/Wind Harmer
1.279
970865AG2-541 GEN
Solar/Wind Harmer
3.559
316123AC1-075 GEN
Solar/Wind Harmer
0.118
970165AG2-112 GEN
Solar/Wind Harmer
0.702
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316087AB2-174 GEN
Solar/Wind Harmer
0.002
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.012
971283AH1-107 GEN
Solar/Wind Harmer
1.012
3137643SOCKMAN
Solar/Wind Harmer
0.291
315607AA1-063A GEN
Solar/Wind Harmer
0.135
3146043SEABORD
Solar/Wind Harmer
0.065
971447AH1-217 GEN
Solar/Wind Harmer
1.965
3146033SCOT NK
Solar/Wind Harmer
0.227
965291AG1-394 GEN
Solar/Wind Harmer
0.252
315652AC1-086 GEN
Solar/Wind Harmer
6.215
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.104
3148013FISHERV
Solar/Wind Helper
0.1
3148463FAIRFLD
Solar/Wind Helper
0.121
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.002
LAGNLTFEXP_LAGN->PJM
CLTF
1.432
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.169
TVALTFEXP_TVA->PJM
CLTF
0.699
CPLELTFEXP_CPLE->PJM
CLTF
3.696
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.709
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.172
MECLTFEXP_MEC->PJM
CLTF
0.251
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.442
LGEELTFEXP_LGEE->PJM
CLTF
0.021
WECLTFEXP_WEC->PJM
CLTF
0.005

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.86 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:765.97
MW Contribution:12.71
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.422
3144293JTRSVLE
50/50
0.69
970413AG2-270 GEN
50/50
8.802
3151591KERR 2
50/50
0.192
3151261ROARAP2
50/50
0.076
3150861SPRUNCD
50/50
0.297
3151031BRUNSWICKG2
50/50
0.785
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.156
316258AE1-075 C
Solar/Wind Harmer
0.187
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.737
970909AG2-566 GEN
Solar/Wind Harmer
2.353
3147133PAMPLIN
Solar/Wind Harmer
0.682
971193AH1-056 GEN
Solar/Wind Harmer
13.238
963181AG1-167 GEN
Solar/Wind Harmer
0.817
959311AF2-222 GEN
Solar/Wind Harmer
15.236
970257AG2-171 GEN
Solar/Wind Harmer
5.302
315785AD2-033 C
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
9.125
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970221AG2-151 GEN
Solar/Wind Harmer
6.362
316478AD1-087 GEN
Solar/Wind Harmer
0.328
316486AD2-202 GEN
Solar/Wind Harmer
0.096
3147043LAWRENC
Solar/Wind Harmer
0.05
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.274
971683AH1-343 GEN
Solar/Wind Harmer
2.442
313506AB2-031 GEN
Solar/Wind Harmer
0.2
970917AG2-570 GEN
Solar/Wind Harmer
5.117
316365GEN2_N
Solar/Wind Harmer
0.127
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.562
3132273ORANGE
Solar/Wind Helper
0.024
3151931BEARGRDN S1
50/50
5.707
3151911BEARGRDN G1
50/50
4.422
3144293JTRSVLE
50/50
0.69
970119AG2-088 GEN
50/50
12.707
3151531CLOVER1
50/50
2.017
3151601KERR 3
50/50
0.192
3151581KERR 1
50/50
0.069
3147043LAWRENC
50/50
0.8
3151261ROARAP2
50/50
0.077
3150851SPRUNCC
50/50
0.297
3151051BRUNSWICKS1
50/50
1.63
3151021BRUNSWICKG1
50/50
0.785
971451AH1-221 GEN
50/50
2.385
315243AE2-183_GT3
50/50
0.972
972003AH1-546 GEN
Solar/Wind Harmer
19.447
970937AG2-583 GEN
Solar/Wind Harmer
23.874
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.178
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.396
963171AG1-166 GEN
Solar/Wind Harmer
1.09
971563AH1-280 GEN
Solar/Wind Harmer
2.18
970685AG2-442 GEN
Solar/Wind Harmer
13.857
962491AG1-098 GEN
Solar/Wind Harmer
7.06
971377AH1-170 GEN
Solar/Wind Harmer
1.272
3147623JAMES R
Solar/Wind Harmer
0.276
315693AD1-088 GEN
Solar/Wind Harmer
5.685
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.095
970401AG2-262 GEN
Solar/Wind Harmer
0.559
957481AF2-042 GEN
Solar/Wind Harmer
24.966
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.579
316129AC1-054 GEN
Solar/Wind Harmer
0.309
3143526WINTERP
Solar/Wind Harmer
0.415
971795AH1-408 GEN
Solar/Wind Harmer
5.206
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.641
3145783HORNRTN
Solar/Wind Harmer
0.061
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
4.587
316023GEN1_S
Solar/Wind Harmer
0.127
3147983MERCK5
Solar/Wind Helper
0.057
3144293JTRSVLE
50/50
0.69
3144293JTRSVLE
50/50
0.581
970535AG2-341 GEN
50/50
1.885
3152661PLYWOOD A
50/50
0.185
3151041BRUNSWICKG3
50/50
0.785
972187AH1-678 GEN
50/50
1.802
315242AE2-183_GT2
50/50
0.972
315241AE2-183_GT1
50/50
0.966
972185AH1-677 GEN
50/50
3.505
970533AG2-339 GEN
50/50
5.074
970531AG2-338 GEN
50/50
2.029
3146776BUCKING
Solar/Wind Harmer
1.508
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
9.412
3147133PAMPLIN
Solar/Wind Harmer
0.217
3147133PAMPLIN
Solar/Wind Harmer
0.174
958211AF2-115 GEN
Solar/Wind Harmer
2.452
963191AG1-168 GEN
Solar/Wind Harmer
0.817
971741AH1-377 GEN
Solar/Wind Harmer
19.558
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.069
971775AH1-396 GEN
Solar/Wind Harmer
0.265
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
6.362
962561AG1-105 GEN
Solar/Wind Harmer
4.763
939181AE1-148 GEN
Solar/Wind Harmer
4.697
971223AH1-071 GEN
Solar/Wind Harmer
1.017
964791AG1-342 GEN
Solar/Wind Harmer
1.83
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
970099AG2-077 GEN
Solar/Wind Harmer
9.986
3143526WINTERP
Solar/Wind Harmer
0.415
970933AG2-581 GEN
Solar/Wind Harmer
5.925
316181AB2-040 GEN
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.086
3145783HORNRTN
Solar/Wind Harmer
0.869
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.204
966001AG1-469 GEN
Solar/Wind Helper
0.174
972205AH1-687 GEN
50/50
21.569
316303AF2-085
50/50
1.694
3151541CLOVER2
50/50
2.007
3151611KERR 4
50/50
0.192
3151621KERR 5
50/50
0.192
3151631KERR 6
50/50
0.192
3151641KERR 7
50/50
0.192
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
971285AH1-108 GEN
50/50
0.486
963041AG1-153 GEN
50/50
1.59
315244AE2-183_ST
50/50
1.681
971845AH1-439 GEN
Solar/Wind Harmer
16.786
970285AG2-188 GEN
Solar/Wind Harmer
28.258
315657AE1-056 GEN
Solar/Wind Harmer
7.498
946301AF1-294 GEN
Solar/Wind Harmer
4.032
961791AG1-021 GEN
Solar/Wind Harmer
1.962
970683AG2-441 GEN
Solar/Wind Harmer
12.373
970681AG2-440 GEN
Solar/Wind Harmer
9.898
3144303KENBRDG
Solar/Wind Harmer
0.132
971443AH1-215 GEN
Solar/Wind Harmer
2.755
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
1.107
316118AC1-105 GEN
Solar/Wind Harmer
0.222
970831AG2-522 GEN
Solar/Wind Harmer
3.422
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.107
971283AH1-107 GEN
Solar/Wind Harmer
1.107
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
10.427
3137643SOCKMAN
Solar/Wind Harmer
0.253
970865AG2-541 GEN
Solar/Wind Harmer
2.127
315607AA1-063A GEN
Solar/Wind Harmer
0.122
3146043SEABORD
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
12.427
970673AG2-436 GEN
Solar/Wind Harmer
8.285
970085AG2-068 GEN
Solar/Wind Harmer
3.058
970581AG2-369 GEN
Solar/Wind Harmer
2.63
941031AE2-094 GEN
Solar/Wind Harmer
10.513
944011AF1-069 GEN
Solar/Wind Harmer
3.435
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.783
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.427
CPLELTFEXP_CPLE->PJM
CLTF
3.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.625
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.208
NYPJM->LTFIMP_NY
CLTF
0.345

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2066-282_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2066-282_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.36 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:916.0
MW Contribution:16.44
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.81
3151911BEARGRDN G1
50/50
4.502
3144293JTRSVLE
50/50
0.7
970119AG2-088 GEN
50/50
16.441
972003AH1-546 GEN
Solar/Wind Harmer
26.109
970937AG2-583 GEN
Solar/Wind Harmer
32.485
316322AB2-045
Solar/Wind Harmer
1.45
3146776BUCKING
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
5.96
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.567
963171AG1-166 GEN
Solar/Wind Harmer
2.908
971563AH1-280 GEN
Solar/Wind Harmer
2.908
970685AG2-442 GEN
Solar/Wind Harmer
18.475
971377AH1-170 GEN
Solar/Wind Harmer
1.782
3147623JAMES R
Solar/Wind Harmer
0.221
962491AG1-098 GEN
Solar/Wind Harmer
9.39
3143226MDLTHAN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.718
316237AB2-079_GEN
Solar/Wind Harmer
0.403
970401AG2-262 GEN
Solar/Wind Harmer
0.704
957481AF2-042 GEN
Solar/Wind Harmer
33.096
315687AD1-152 GEN
Solar/Wind Harmer
1.157
971065AG2-659 GEN
Solar/Wind Harmer
4.696
3147043LAWRENC
Adder
0.745
316129AC1-054 GEN
Solar/Wind Harmer
0.805
971795AH1-408 GEN
Solar/Wind Harmer
6.476
316003AC1-222 GEN
Solar/Wind Harmer
0.786
960081AF2-299 GEN
Solar/Wind Harmer
0.821
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
970919AG2-571 GEN
Solar/Wind Harmer
2.043
970087AG2-069 GEN
Solar/Wind Harmer
6.029
3147983MERCK5
Solar/Wind Helper
0.056
3151921BEARGRDN G2
50/50
4.502
3144293JTRSVLE
50/50
0.7
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.811
316258AE1-075 C
Solar/Wind Harmer
0.73
316405AF2-144 C
Solar/Wind Harmer
0.77
3143336POWHATN
Solar/Wind Harmer
3.032
942461AE2-259 GEN
Solar/Wind Harmer
4.363
970909AG2-566 GEN
Solar/Wind Harmer
2.388
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.482
963181AG1-167 GEN
Solar/Wind Harmer
2.181
959311AF2-222 GEN
Solar/Wind Harmer
20.337
970257AG2-171 GEN
Solar/Wind Harmer
7.06
315785AD2-033 C
Solar/Wind Harmer
4.062
964241AG1-285 GEN
Solar/Wind Harmer
12.123
970221AG2-151 GEN
Solar/Wind Harmer
8.911
316131AB2-060 GEN
Solar/Wind Harmer
1.517
316478AD1-087 GEN
Solar/Wind Harmer
0.922
316486AD2-202 GEN
Solar/Wind Harmer
0.27
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.261
960061AF2-297 GEN
Solar/Wind Harmer
4.339
971683AH1-343 GEN
Solar/Wind Harmer
3.24
966621AG1-532 GEN
Solar/Wind Harmer
0.148
313506AB2-031 GEN
Solar/Wind Harmer
0.568
970917AG2-570 GEN
Solar/Wind Harmer
16.142
3148013FISHERV
Solar/Wind Helper
0.177
316499AE2-029_GEN
Solar/Wind Helper
0.512
315616AA1-038_C
Solar/Wind Helper
0.557
3132273ORANGE
Solar/Wind Helper
0.023
972205AH1-687 GEN
50/50
21.959
316303AF2-085
50/50
2.192
971845AH1-439 GEN
Solar/Wind Harmer
22.482
970285AG2-188 GEN
Solar/Wind Harmer
35.716
315657AE1-056 GEN
Solar/Wind Harmer
9.289
946301AF1-294 GEN
Solar/Wind Harmer
5.962
961791AG1-021 GEN
Solar/Wind Harmer
2.908
970683AG2-441 GEN
Solar/Wind Harmer
16.495
970681AG2-440 GEN
Solar/Wind Harmer
13.196
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.668
316239AB2-077_GEN
Solar/Wind Harmer
0.403
316238AB2-078_GEN
Solar/Wind Harmer
0.403
270494AE1-108_GEN
Solar/Wind Harmer
2.875
316118AC1-105 GEN
Solar/Wind Harmer
0.668
970831AG2-522 GEN
Solar/Wind Harmer
4.476
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
13.768
946281AF1-292 GEN
Solar/Wind Harmer
0.164
316087AB2-174 GEN
Solar/Wind Harmer
1.019
970865AG2-541 GEN
Solar/Wind Harmer
2.825
3137643SOCKMAN
Solar/Wind Harmer
-0.028
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
315607AA1-063A GEN
Solar/Wind Harmer
0.655
3146043SEABORD
Solar/Wind Harmer
-0.006
970085AG2-068 GEN
Solar/Wind Harmer
4.019
970581AG2-369 GEN
Solar/Wind Harmer
3.457
941031AE2-094 GEN
Solar/Wind Harmer
11.99
944011AF1-069 GEN
Solar/Wind Harmer
3.757
971447AH1-217 GEN
Solar/Wind Harmer
2.264
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.102
3148463FAIRFLD
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
0.7
3144293JTRSVLE
50/50
0.589
3146776BUCKING
Solar/Wind Harmer
-0.172
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.575
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.636
963191AG1-168 GEN
Solar/Wind Harmer
2.181
971741AH1-377 GEN
Solar/Wind Harmer
26.113
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.413
971775AH1-396 GEN
Solar/Wind Harmer
1.34
971489AH1-241 GEN
Solar/Wind Harmer
8.46
971223AH1-071 GEN
Solar/Wind Harmer
1.732
313527AB2-043 GEN
Solar/Wind Harmer
2.226
962561AG1-105 GEN
Solar/Wind Harmer
6.315
939181AE1-148 GEN
Solar/Wind Harmer
6.206
964791AG1-342 GEN
Solar/Wind Harmer
2.303
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.238
970933AG2-581 GEN
Solar/Wind Harmer
7.823
316181AB2-040 GEN
Solar/Wind Harmer
0.986
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.766
3145593CAROLNA
Solar/Wind Harmer
0.057
972187AH1-678 GEN
Adder
1.696
3145783HORNRTN
Solar/Wind Harmer
0.793
3145783HORNRTN
Solar/Wind Harmer
0.635
3145783HORNRTN
Solar/Wind Harmer
0.198
3145783HORNRTN
Solar/Wind Harmer
0.079
316426AA2-053 GEN
Solar/Wind Harmer
0.667
972185AH1-677 GEN
Adder
3.297
966001AG1-469 GEN
Solar/Wind Helper
0.17
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.318
LAGNLTFEXP_LAGN->PJM
CLTF
0.917
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.775
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.437
CPLELTFEXP_CPLE->PJM
CLTF
3.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.788
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.251
NYPJM->LTFIMP_NY
CLTF
0.338

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 219-282_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 219-282_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.03 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:913.26
MW Contribution:16.44
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.81
3151911BEARGRDN G1
50/50
4.502
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
16.437
972003AH1-546 GEN
Solar/Wind Harmer
26.108
970937AG2-583 GEN
Solar/Wind Harmer
32.483
316322AB2-045
Solar/Wind Harmer
1.45
3146776BUCKING
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
5.96
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.567
963171AG1-166 GEN
Solar/Wind Harmer
2.908
971563AH1-280 GEN
Solar/Wind Harmer
2.908
970685AG2-442 GEN
Solar/Wind Harmer
18.472
971377AH1-170 GEN
Solar/Wind Harmer
1.782
3147623JAMES R
Solar/Wind Harmer
0.221
962491AG1-098 GEN
Solar/Wind Harmer
9.388
3143526WINTERP
Solar/Wind Harmer
-0.072
3143226MDLTHAN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.716
316237AB2-079_GEN
Solar/Wind Harmer
0.403
970401AG2-262 GEN
Solar/Wind Harmer
0.703
957481AF2-042 GEN
Solar/Wind Harmer
33.086
315687AD1-152 GEN
Solar/Wind Harmer
1.156
971065AG2-659 GEN
Solar/Wind Harmer
4.694
3147043LAWRENC
Adder
0.744
316129AC1-054 GEN
Solar/Wind Harmer
0.804
971795AH1-408 GEN
Solar/Wind Harmer
6.473
316003AC1-222 GEN
Solar/Wind Harmer
0.786
960081AF2-299 GEN
Solar/Wind Harmer
0.821
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
970919AG2-571 GEN
Solar/Wind Harmer
2.042
970087AG2-069 GEN
Solar/Wind Harmer
6.026
3147983MERCK5
Solar/Wind Helper
0.056
3151921BEARGRDN G2
50/50
4.502
3144293JTRSVLE
50/50
0.699
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.811
316258AE1-075 C
Solar/Wind Harmer
0.73
316405AF2-144 C
Solar/Wind Harmer
0.77
3143336POWHATN
Solar/Wind Harmer
3.032
942461AE2-259 GEN
Solar/Wind Harmer
4.363
970909AG2-566 GEN
Solar/Wind Harmer
2.387
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.48
963181AG1-167 GEN
Solar/Wind Harmer
2.181
959311AF2-222 GEN
Solar/Wind Harmer
20.333
970257AG2-171 GEN
Solar/Wind Harmer
7.059
315785AD2-033 C
Solar/Wind Harmer
4.061
964241AG1-285 GEN
Solar/Wind Harmer
12.12
970221AG2-151 GEN
Solar/Wind Harmer
8.909
316131AB2-060 GEN
Solar/Wind Harmer
1.516
316478AD1-087 GEN
Solar/Wind Harmer
0.922
316486AD2-202 GEN
Solar/Wind Harmer
0.27
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.261
960061AF2-297 GEN
Solar/Wind Harmer
4.337
971683AH1-343 GEN
Solar/Wind Harmer
3.239
966621AG1-532 GEN
Solar/Wind Harmer
0.148
313506AB2-031 GEN
Solar/Wind Harmer
0.568
970917AG2-570 GEN
Solar/Wind Harmer
16.134
3148013FISHERV
Solar/Wind Helper
0.177
316499AE2-029_GEN
Solar/Wind Helper
0.512
315616AA1-038_C
Solar/Wind Helper
0.557
3132273ORANGE
Solar/Wind Helper
0.023
972205AH1-687 GEN
50/50
21.958
316303AF2-085
50/50
2.192
971845AH1-439 GEN
Solar/Wind Harmer
22.48
970285AG2-188 GEN
Solar/Wind Harmer
35.714
315657AE1-056 GEN
Solar/Wind Harmer
9.288
946301AF1-294 GEN
Solar/Wind Harmer
5.962
961791AG1-021 GEN
Solar/Wind Harmer
2.908
970683AG2-441 GEN
Solar/Wind Harmer
16.493
970681AG2-440 GEN
Solar/Wind Harmer
13.194
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.667
316233AE1-074 FULL
Solar/Wind Harmer
0.373
971281AH1-106 GEN
Solar/Wind Harmer
2.251
971283AH1-107 GEN
Solar/Wind Harmer
2.251
316239AB2-077_GEN
Solar/Wind Harmer
0.403
316238AB2-078_GEN
Solar/Wind Harmer
0.403
270494AE1-108_GEN
Solar/Wind Harmer
2.874
316118AC1-105 GEN
Solar/Wind Harmer
0.668
970831AG2-522 GEN
Solar/Wind Harmer
4.474
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
13.762
946281AF1-292 GEN
Solar/Wind Harmer
0.163
316087AB2-174 GEN
Solar/Wind Harmer
1.018
970865AG2-541 GEN
Solar/Wind Harmer
2.824
3137643SOCKMAN
Solar/Wind Harmer
-0.028
970673AG2-436 GEN
Solar/Wind Harmer
13.713
970673AG2-436 GEN
Solar/Wind Harmer
6.943
315607AA1-063A GEN
Solar/Wind Harmer
0.655
3146043SEABORD
Solar/Wind Harmer
-0.006
970085AG2-068 GEN
Solar/Wind Harmer
4.017
970581AG2-369 GEN
Solar/Wind Harmer
3.455
941031AE2-094 GEN
Solar/Wind Harmer
11.984
944011AF1-069 GEN
Solar/Wind Harmer
3.755
971447AH1-217 GEN
Solar/Wind Harmer
2.263
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.102
3148463FAIRFLD
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.589
3146776BUCKING
Solar/Wind Harmer
-0.172
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.574
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.635
963191AG1-168 GEN
Solar/Wind Harmer
2.181
971741AH1-377 GEN
Solar/Wind Harmer
26.109
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.412
971775AH1-396 GEN
Solar/Wind Harmer
1.34
971489AH1-241 GEN
Solar/Wind Harmer
8.458
3143526WINTERP
Solar/Wind Harmer
-0.072
971223AH1-071 GEN
Solar/Wind Harmer
1.731
313527AB2-043 GEN
Solar/Wind Harmer
2.225
962561AG1-105 GEN
Solar/Wind Harmer
6.313
939181AE1-148 GEN
Solar/Wind Harmer
6.204
964791AG1-342 GEN
Solar/Wind Harmer
2.302
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.234
970933AG2-581 GEN
Solar/Wind Harmer
7.82
316181AB2-040 GEN
Solar/Wind Harmer
0.986
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.766
3145593CAROLNA
Solar/Wind Harmer
0.057
972187AH1-678 GEN
Adder
1.695
3145783HORNRTN
Solar/Wind Harmer
0.793
3145783HORNRTN
Solar/Wind Harmer
0.634
3145783HORNRTN
Solar/Wind Harmer
0.198
3145783HORNRTN
Solar/Wind Harmer
0.079
316426AA2-053 GEN
Solar/Wind Harmer
0.667
972185AH1-677 GEN
Adder
3.295
966001AG1-469 GEN
Solar/Wind Helper
0.17
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.11
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.323
LAGNLTFEXP_LAGN->PJM
CLTF
0.913
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.768
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.435
CPLELTFEXP_CPLE->PJM
CLTF
3.062
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.758
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.243
NYPJM->LTFIMP_NY
CLTF
0.339

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:196.14 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1331.14
MW Contribution:15.41
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.57 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1515.37
MW Contribution:15.41
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.57 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1515.34
MW Contribution:15.41
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.31 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1455.08
MW Contribution:18.19
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.31 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1455.08
MW Contribution:18.19
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:144.42 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:980.12
MW Contribution:10.81
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970535AG2-341 GEN
50/50
2.556
3152661PLYWOOD A
50/50
0.283
971489AH1-241 GEN
Solar/Wind Harmer
21.838
3146776BUCKING
Solar/Wind Harmer
1.539
3146776BUCKING
Solar/Wind Harmer
0.125
970301AG2-198 GEN
Solar/Wind Harmer
11.486
971741AH1-377 GEN
Solar/Wind Harmer
25.037
3147133PAMPLIN
Solar/Wind Harmer
0.249
3147133PAMPLIN
Solar/Wind Harmer
0.199
315821AE2-092 GEN
Solar/Wind Harmer
0.015
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
316034AC1-036 C
Solar/Wind Harmer
0.015
970323AG2-213 GEN
Solar/Wind Harmer
8.565
971775AH1-396 GEN
Solar/Wind Harmer
0.321
970933AG2-581 GEN
Solar/Wind Harmer
14.707
970099AG2-077 GEN
Solar/Wind Harmer
19.291
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
6.748
964791AG1-342 GEN
Solar/Wind Harmer
2.636
3146843MT LREL
Solar/Wind Harmer
0.137
3146843MT LREL
Solar/Wind Harmer
0.137
939181AE1-148 GEN
Solar/Wind Harmer
6.508
971223AH1-071 GEN
Solar/Wind Harmer
0.865
942751AE2-291 GEN
Solar/Wind Harmer
4.374
316222AC1-221 GEN
Solar/Wind Harmer
0.309
316181AB2-040 GEN
Solar/Wind Harmer
0.1
3145593CAROLNA
Solar/Wind Harmer
0.067
3145593CAROLNA
Solar/Wind Harmer
0.067
966811AG1-552 GEN
Solar/Wind Harmer
0.729
3145593CAROLNA
Solar/Wind Harmer
0.084
3143526WINTERP
Solar/Wind Harmer
0.343
3145783HORNRTN
Solar/Wind Harmer
1.168
3145783HORNRTN
Solar/Wind Harmer
0.934
3145783HORNRTN
Solar/Wind Harmer
0.292
3145783HORNRTN
Solar/Wind Harmer
0.117
316426AA2-053 GEN
Solar/Wind Harmer
0.216
316274AC1-208 GEN
Solar/Wind Harmer
0.297
966001AG1-469 GEN
Solar/Wind Helper
0.193
3151921BEARGRDN G2
50/50
4.277
3144293JTRSVLE
50/50
0.801
970413AG2-270 GEN
50/50
15.972
3151591KERR 2
50/50
0.27
966251AG1-494 GEN
50/50
1.325
3151261ROARAP2
50/50
0.082
970221AG2-151 GEN
Solar/Wind Harmer
21.838
3146776BUCKING
Solar/Wind Harmer
0.139
3146926FARMVIL
Solar/Wind Harmer
0.194
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.872
3147133PAMPLIN
Solar/Wind Harmer
0.783
971193AH1-056 GEN
Solar/Wind Harmer
15.186
963181AG1-167 GEN
Solar/Wind Harmer
0.948
316313AB2-026
Solar/Wind Harmer
0.147
316258AE1-075 C
Solar/Wind Harmer
0.175
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.513
959311AF2-222 GEN
Solar/Wind Harmer
18.323
970257AG2-171 GEN
Solar/Wind Harmer
6.424
315785AD2-033 C
Solar/Wind Harmer
1.572
964241AG1-285 GEN
Solar/Wind Harmer
11.577
316478AD1-087 GEN
Solar/Wind Harmer
0.596
316486AD2-202 GEN
Solar/Wind Harmer
0.175
316131AB2-060 GEN
Solar/Wind Harmer
0.509
958131AF2-107 GEN
Solar/Wind Harmer
3.719
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.197
971683AH1-343 GEN
Solar/Wind Harmer
3.989
3147043LAWRENC
Solar/Wind Harmer
0.058
316283AC2-100 C
Solar/Wind Harmer
0.143
313506AB2-031 GEN
Solar/Wind Harmer
0.212
316499AE2-029_GEN
Solar/Wind Helper
0.498
3132273ORANGE
Solar/Wind Helper
0.027
3148013FISHERV
Solar/Wind Helper
0.128
3151931BEARGRDN S1
50/50
5.52
3151911BEARGRDN G1
50/50
4.277
3144293JTRSVLE
50/50
0.801
3151531CLOVER1
50/50
3.66
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3147043LAWRENC
50/50
0.93
970119AG2-088 GEN
50/50
10.808
3151261ROARAP2
50/50
0.084
972003AH1-546 GEN
Solar/Wind Harmer
18.967
971377AH1-170 GEN
Solar/Wind Harmer
4.368
3147623JAMES R
Solar/Wind Harmer
0.949
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.154
970937AG2-583 GEN
Solar/Wind Harmer
22.935
3146926FARMVIL
Solar/Wind Harmer
0.194
316336AC2-165 C
Solar/Wind Harmer
0.011
963171AG1-166 GEN
Solar/Wind Harmer
1.265
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3143336POWHATN
Solar/Wind Harmer
4.133
970685AG2-442 GEN
Solar/Wind Harmer
16.387
962491AG1-098 GEN
Solar/Wind Harmer
11.396
315693AD1-088 GEN
Solar/Wind Harmer
9.404
957481AF2-042 GEN
Solar/Wind Harmer
48.226
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.005
970401AG2-262 GEN
Solar/Wind Harmer
0.806
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.784
316129AC1-054 GEN
Solar/Wind Harmer
0.408
971795AH1-408 GEN
Solar/Wind Harmer
5.893
3143226MDLTHAN
Solar/Wind Harmer
0.081
960081AF2-299 GEN
Solar/Wind Harmer
0.671
3143526WINTERP
Solar/Wind Harmer
0.343
3145783HORNRTN
Solar/Wind Harmer
0.066
316190AA2-174 GEN
Solar/Wind Harmer
0
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.79
3147666LOUISA
Solar/Wind Helper
0.453
315616AA1-038_C
Solar/Wind Helper
0.526
3147666LOUISA
Solar/Wind Helper
0.261
972205AH1-687 GEN
50/50
20.861
3151541CLOVER2
50/50
3.643
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
316303AF2-085
50/50
1.441
3151281ROARAP4
50/50
0.081
3151281ROARAP4
50/50
0.076
971845AH1-439 GEN
Solar/Wind Harmer
17.22
971447AH1-217 GEN
Solar/Wind Harmer
11.445
970285AG2-188 GEN
Solar/Wind Harmer
29.262
270494AE1-108_GEN
Solar/Wind Harmer
3.857
315657AE1-056 GEN
Solar/Wind Harmer
8.602
946301AF1-294 GEN
Solar/Wind Harmer
4.679
961791AG1-021 GEN
Solar/Wind Harmer
2.276
970683AG2-441 GEN
Solar/Wind Harmer
14.631
970681AG2-440 GEN
Solar/Wind Harmer
11.705
3144303KENBRDG
Solar/Wind Harmer
0.16
971443AH1-215 GEN
Solar/Wind Harmer
3.345
971967AH1-528 GEN
Solar/Wind Harmer
29.413
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.334
3147173SINAI
Solar/Wind Harmer
0.122
3147243WELCO
Solar/Wind Harmer
0.076
970831AG2-522 GEN
Solar/Wind Harmer
4.457
970865AG2-541 GEN
Solar/Wind Harmer
3.533
316123AC1-075 GEN
Solar/Wind Harmer
0.121
970165AG2-112 GEN
Solar/Wind Harmer
0.72
970163AG2-111 GEN
Solar/Wind Harmer
0.686
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.271
316233AE1-074 FULL
Solar/Wind Harmer
0.053
971281AH1-106 GEN
Solar/Wind Harmer
0.915
971283AH1-107 GEN
Solar/Wind Harmer
0.915
315607AA1-063A GEN
Solar/Wind Harmer
0.125
3146043SEABORD
Solar/Wind Harmer
0.06
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.073
3148463FAIRFLD
Solar/Wind Helper
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
1.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.134
TVALTFEXP_TVA->PJM
CLTF
0.807
CPLELTFEXP_CPLE->PJM
CLTF
3.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.173
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.591
MECLTFEXP_MEC->PJM
CLTF
0.444
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.484
LGEELTFEXP_LGEE->PJM
CLTF
0.11
WECLTFEXP_WEC->PJM
CLTF
0.05

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.58 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:736.92
MW Contribution:11.6
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.314
3151911BEARGRDN G1
50/50
4.118
3144293JTRSVLE
50/50
0.644
3151531CLOVER1
50/50
1.885
3151601KERR 3
50/50
0.18
3151581KERR 1
50/50
0.064
970119AG2-088 GEN
50/50
11.599
3147043LAWRENC
50/50
0.746
3151261ROARAP2
50/50
0.072
972003AH1-546 GEN
Solar/Wind Harmer
18.108
971377AH1-170 GEN
Solar/Wind Harmer
4.203
3147623JAMES R
Solar/Wind Harmer
0.913
970937AG2-583 GEN
Solar/Wind Harmer
22.204
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.165
316336AC2-165 C
Solar/Wind Harmer
0.01
3143336POWHATN
Solar/Wind Harmer
4.074
963171AG1-166 GEN
Solar/Wind Harmer
1.017
971563AH1-280 GEN
Solar/Wind Harmer
2.035
970685AG2-442 GEN
Solar/Wind Harmer
12.945
962491AG1-098 GEN
Solar/Wind Harmer
6.577
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
5.296
970401AG2-262 GEN
Solar/Wind Harmer
0.531
957481AF2-042 GEN
Solar/Wind Harmer
23.244
3143226MDLTHAN
Solar/Wind Harmer
0.087
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.352
316129AC1-054 GEN
Solar/Wind Harmer
0.289
971795AH1-408 GEN
Solar/Wind Harmer
4.849
3143526WINTERP
Solar/Wind Harmer
0.377
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.595
3145783HORNRTN
Solar/Wind Harmer
0.057
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.752
3144293JTRSVLE
50/50
0.644
3144293JTRSVLE
50/50
0.543
970535AG2-341 GEN
50/50
1.768
3152661PLYWOOD A
50/50
0.177
971489AH1-241 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
1.404
3146776BUCKING
Solar/Wind Harmer
0.114
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
8.767
3147133PAMPLIN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.162
958211AF2-115 GEN
Solar/Wind Harmer
2.289
963191AG1-168 GEN
Solar/Wind Harmer
0.763
971741AH1-377 GEN
Solar/Wind Harmer
18.217
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.61
971775AH1-396 GEN
Solar/Wind Harmer
0.248
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
4.515
939181AE1-148 GEN
Solar/Wind Harmer
4.407
964791AG1-342 GEN
Solar/Wind Harmer
1.738
3146843MT LREL
Solar/Wind Harmer
0.09
3146843MT LREL
Solar/Wind Harmer
0.09
970099AG2-077 GEN
Solar/Wind Harmer
9.298
971223AH1-071 GEN
Solar/Wind Harmer
0.928
3143526WINTERP
Solar/Wind Harmer
0.377
970933AG2-581 GEN
Solar/Wind Harmer
5.476
316181AB2-040 GEN
Solar/Wind Harmer
0.087
3145593CAROLNA
Solar/Wind Harmer
0.058
3145593CAROLNA
Solar/Wind Harmer
0.058
966811AG1-552 GEN
Solar/Wind Harmer
0.627
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.01
3145783HORNRTN
Solar/Wind Harmer
0.808
3145783HORNRTN
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
0.101
966001AG1-469 GEN
Solar/Wind Helper
0.19
3151921BEARGRDN G2
50/50
4.118
3144293JTRSVLE
50/50
0.644
970413AG2-270 GEN
50/50
8.224
3151591KERR 2
50/50
0.18
966251AG1-494 GEN
50/50
1.173
3151261ROARAP2
50/50
0.07
970221AG2-151 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
0.126
3146926FARMVIL
Solar/Wind Harmer
0.165
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.463
970909AG2-566 GEN
Solar/Wind Harmer
2.192
3147133PAMPLIN
Solar/Wind Harmer
0.637
971193AH1-056 GEN
Solar/Wind Harmer
12.353
963181AG1-167 GEN
Solar/Wind Harmer
0.763
959311AF2-222 GEN
Solar/Wind Harmer
14.242
970257AG2-171 GEN
Solar/Wind Harmer
4.957
315785AD2-033 C
Solar/Wind Harmer
1.2
964241AG1-285 GEN
Solar/Wind Harmer
8.548
958131AF2-107 GEN
Solar/Wind Harmer
3.44
316131AB2-060 GEN
Solar/Wind Harmer
0.366
316478AD1-087 GEN
Solar/Wind Harmer
0.307
316486AD2-202 GEN
Solar/Wind Harmer
0.09
3147043LAWRENC
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.155
971683AH1-343 GEN
Solar/Wind Harmer
2.44
313506AB2-031 GEN
Solar/Wind Harmer
0.186
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.54
972205AH1-687 GEN
50/50
20.083
3151541CLOVER2
50/50
1.876
3151611KERR 4
50/50
0.18
3151621KERR 5
50/50
0.18
3151631KERR 6
50/50
0.18
3151641KERR 7
50/50
0.18
316303AF2-085
50/50
1.546
3151281ROARAP4
50/50
0.07
3151281ROARAP4
50/50
0.066
971447AH1-217 GEN
Solar/Wind Harmer
11.004
971845AH1-439 GEN
Solar/Wind Harmer
15.632
970285AG2-188 GEN
Solar/Wind Harmer
26.316
270494AE1-108_GEN
Solar/Wind Harmer
3.693
315657AE1-056 GEN
Solar/Wind Harmer
6.997
946301AF1-294 GEN
Solar/Wind Harmer
3.764
961791AG1-021 GEN
Solar/Wind Harmer
1.831
970683AG2-441 GEN
Solar/Wind Harmer
11.558
970681AG2-440 GEN
Solar/Wind Harmer
9.247
3144303KENBRDG
Solar/Wind Harmer
0.124
971443AH1-215 GEN
Solar/Wind Harmer
2.576
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.212
970831AG2-522 GEN
Solar/Wind Harmer
3.201
3147173SINAI
Solar/Wind Harmer
0.074
3147243WELCO
Solar/Wind Harmer
0.046
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.006
971283AH1-107 GEN
Solar/Wind Harmer
1.006
970865AG2-541 GEN
Solar/Wind Harmer
2.17
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
9.597
3137643SOCKMAN
Solar/Wind Harmer
0.235
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.119
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.029
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.072
LAGNLTFEXP_LAGN->PJM
CLTF
1.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.815
TVALTFEXP_TVA->PJM
CLTF
0.547
CPLELTFEXP_CPLE->PJM
CLTF
2.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.673
MECLTFEXP_MEC->PJM
CLTF
0.138
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.391

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2066-282_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2066-282_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.52 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:900.75
MW Contribution:15.08
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.192
3144293JTRSVLE
50/50
0.653
970221AG2-151 GEN
Solar/Wind Harmer
28.166
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.752
316258AE1-075 C
Solar/Wind Harmer
0.677
316405AF2-144 C
Solar/Wind Harmer
0.714
3143336POWHATN
Solar/Wind Harmer
2.812
3151931BEARGRDN S1
50/50
5.41
3151911BEARGRDN G1
50/50
4.192
3144293JTRSVLE
50/50
0.653
970119AG2-088 GEN
50/50
15.082
972003AH1-546 GEN
Solar/Wind Harmer
24.312
971377AH1-170 GEN
Solar/Wind Harmer
5.633
3147623JAMES R
Solar/Wind Harmer
0.697
970937AG2-583 GEN
Solar/Wind Harmer
30.216
316322AB2-045
Solar/Wind Harmer
1.35
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.534
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.308
963171AG1-166 GEN
Solar/Wind Harmer
2.715
971563AH1-280 GEN
Solar/Wind Harmer
2.715
970685AG2-442 GEN
Solar/Wind Harmer
17.259
962491AG1-098 GEN
Solar/Wind Harmer
8.747
3143226MDLTHAN
Solar/Wind Harmer
-0.013
316237AB2-079_GEN
Solar/Wind Harmer
0.378
315693AD1-088 GEN
Solar/Wind Harmer
6.258
970401AG2-262 GEN
Solar/Wind Harmer
0.669
957481AF2-042 GEN
Solar/Wind Harmer
30.813
315687AD1-152 GEN
Solar/Wind Harmer
1.088
971065AG2-659 GEN
Solar/Wind Harmer
4.397
3147043LAWRENC
Adder
0.694
316129AC1-054 GEN
Solar/Wind Harmer
0.753
971795AH1-408 GEN
Solar/Wind Harmer
6.032
316003AC1-222 GEN
Solar/Wind Harmer
0.772
960081AF2-299 GEN
Solar/Wind Harmer
0.762
3147983MERCK5
Solar/Wind Helper
0.055
972205AH1-687 GEN
50/50
20.447
316303AF2-085
50/50
2.011
971447AH1-217 GEN
Solar/Wind Harmer
14.757
971845AH1-439 GEN
Solar/Wind Harmer
20.937
970285AG2-188 GEN
Solar/Wind Harmer
33.263
270494AE1-108_GEN
Solar/Wind Harmer
9.168
315657AE1-056 GEN
Solar/Wind Harmer
8.668
946301AF1-294 GEN
Solar/Wind Harmer
5.566
961791AG1-021 GEN
Solar/Wind Harmer
2.715
970683AG2-441 GEN
Solar/Wind Harmer
15.41
970681AG2-440 GEN
Solar/Wind Harmer
12.328
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.43
316239AB2-077_GEN
Solar/Wind Harmer
0.378
316238AB2-078_GEN
Solar/Wind Harmer
0.378
316118AC1-105 GEN
Solar/Wind Harmer
0.639
970831AG2-522 GEN
Solar/Wind Harmer
4.187
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.88
946281AF1-292 GEN
Solar/Wind Harmer
0.152
971967AH1-528 GEN
Solar/Wind Harmer
12.673
316087AB2-174 GEN
Solar/Wind Harmer
0.946
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.118
942461AE2-259 GEN
Solar/Wind Harmer
4.067
970909AG2-566 GEN
Solar/Wind Harmer
2.224
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.446
963181AG1-167 GEN
Solar/Wind Harmer
2.036
959311AF2-222 GEN
Solar/Wind Harmer
19.01
970257AG2-171 GEN
Solar/Wind Harmer
6.601
315785AD2-033 C
Solar/Wind Harmer
3.8
964241AG1-285 GEN
Solar/Wind Harmer
11.356
958131AF2-107 GEN
Solar/Wind Harmer
4.67
316131AB2-060 GEN
Solar/Wind Harmer
1.422
316478AD1-087 GEN
Solar/Wind Harmer
0.862
316486AD2-202 GEN
Solar/Wind Harmer
0.252
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.252
960061AF2-297 GEN
Solar/Wind Harmer
4.181
971683AH1-343 GEN
Solar/Wind Harmer
3.236
966621AG1-532 GEN
Solar/Wind Harmer
0.138
313506AB2-031 GEN
Solar/Wind Harmer
0.528
316499AE2-029_GEN
Solar/Wind Helper
0.5
3148013FISHERV
Solar/Wind Helper
0.13
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.535
3144293JTRSVLE
50/50
0.653
3144293JTRSVLE
50/50
0.55
971489AH1-241 GEN
Solar/Wind Harmer
26.74
3146776BUCKING
Solar/Wind Harmer
-0.16
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.489
970301AG2-198 GEN
Solar/Wind Harmer
11.714
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.394
963191AG1-168 GEN
Solar/Wind Harmer
2.036
971741AH1-377 GEN
Solar/Wind Harmer
24.324
316034AC1-036 C
Solar/Wind Harmer
0.327
970323AG2-213 GEN
Solar/Wind Harmer
8.802
971775AH1-396 GEN
Solar/Wind Harmer
1.253
313527AB2-043 GEN
Solar/Wind Harmer
2.088
971223AH1-071 GEN
Solar/Wind Harmer
1.589
962561AG1-105 GEN
Solar/Wind Harmer
5.986
939181AE1-148 GEN
Solar/Wind Harmer
5.822
964791AG1-342 GEN
Solar/Wind Harmer
2.188
3146843MT LREL
Solar/Wind Harmer
-0.01
3146843MT LREL
Solar/Wind Harmer
-0.01
970099AG2-077 GEN
Solar/Wind Harmer
12.325
970933AG2-581 GEN
Solar/Wind Harmer
7.23
316181AB2-040 GEN
Solar/Wind Harmer
0.916
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.712
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.187
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.02
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.044
LAGNLTFEXP_LAGN->PJM
CLTF
1.141
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.807
TVALTFEXP_TVA->PJM
CLTF
0.557
CPLELTFEXP_CPLE->PJM
CLTF
2.977
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.39
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.714
MECLTFEXP_MEC->PJM
CLTF
0.159
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.385

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 219-282_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 219-282_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.2 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:898.02
MW Contribution:15.08
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.41
3151911BEARGRDN G1
50/50
4.192
3144293JTRSVLE
50/50
0.653
970119AG2-088 GEN
50/50
15.079
972003AH1-546 GEN
Solar/Wind Harmer
24.31
971377AH1-170 GEN
Solar/Wind Harmer
5.633
3147623JAMES R
Solar/Wind Harmer
0.697
970937AG2-583 GEN
Solar/Wind Harmer
30.214
316322AB2-045
Solar/Wind Harmer
1.35
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.533
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.307
963171AG1-166 GEN
Solar/Wind Harmer
2.715
971563AH1-280 GEN
Solar/Wind Harmer
2.715
970685AG2-442 GEN
Solar/Wind Harmer
17.256
962491AG1-098 GEN
Solar/Wind Harmer
8.745
3143526WINTERP
Solar/Wind Harmer
-0.066
3143226MDLTHAN
Solar/Wind Harmer
-0.013
316237AB2-079_GEN
Solar/Wind Harmer
0.378
315693AD1-088 GEN
Solar/Wind Harmer
6.256
970401AG2-262 GEN
Solar/Wind Harmer
0.668
957481AF2-042 GEN
Solar/Wind Harmer
30.804
315687AD1-152 GEN
Solar/Wind Harmer
1.088
971065AG2-659 GEN
Solar/Wind Harmer
4.396
3147043LAWRENC
Adder
0.694
316129AC1-054 GEN
Solar/Wind Harmer
0.753
971795AH1-408 GEN
Solar/Wind Harmer
6.029
316003AC1-222 GEN
Solar/Wind Harmer
0.771
960081AF2-299 GEN
Solar/Wind Harmer
0.762
3147983MERCK5
Solar/Wind Helper
0.055
972205AH1-687 GEN
50/50
20.446
316303AF2-085
50/50
2.01
971447AH1-217 GEN
Solar/Wind Harmer
14.756
971845AH1-439 GEN
Solar/Wind Harmer
20.936
970285AG2-188 GEN
Solar/Wind Harmer
33.261
270494AE1-108_GEN
Solar/Wind Harmer
9.167
315657AE1-056 GEN
Solar/Wind Harmer
8.667
946301AF1-294 GEN
Solar/Wind Harmer
5.565
961791AG1-021 GEN
Solar/Wind Harmer
2.715
970683AG2-441 GEN
Solar/Wind Harmer
15.407
970681AG2-440 GEN
Solar/Wind Harmer
12.326
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.429
316233AE1-074 FULL
Solar/Wind Harmer
0.342
971281AH1-106 GEN
Solar/Wind Harmer
2.065
971283AH1-107 GEN
Solar/Wind Harmer
2.065
316239AB2-077_GEN
Solar/Wind Harmer
0.378
316238AB2-078_GEN
Solar/Wind Harmer
0.378
316118AC1-105 GEN
Solar/Wind Harmer
0.639
970831AG2-522 GEN
Solar/Wind Harmer
4.186
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.879
946281AF1-292 GEN
Solar/Wind Harmer
0.152
971967AH1-528 GEN
Solar/Wind Harmer
12.668
316087AB2-174 GEN
Solar/Wind Harmer
0.946
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.118
3151921BEARGRDN G2
50/50
4.192
3144293JTRSVLE
50/50
0.653
970221AG2-151 GEN
Solar/Wind Harmer
28.165
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.752
316258AE1-075 C
Solar/Wind Harmer
0.677
316405AF2-144 C
Solar/Wind Harmer
0.714
3143336POWHATN
Solar/Wind Harmer
2.811
942461AE2-259 GEN
Solar/Wind Harmer
4.067
970909AG2-566 GEN
Solar/Wind Harmer
2.224
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.444
963181AG1-167 GEN
Solar/Wind Harmer
2.036
959311AF2-222 GEN
Solar/Wind Harmer
19.007
970257AG2-171 GEN
Solar/Wind Harmer
6.6
315785AD2-033 C
Solar/Wind Harmer
3.799
964241AG1-285 GEN
Solar/Wind Harmer
11.354
958131AF2-107 GEN
Solar/Wind Harmer
4.669
316131AB2-060 GEN
Solar/Wind Harmer
1.422
316478AD1-087 GEN
Solar/Wind Harmer
0.862
316486AD2-202 GEN
Solar/Wind Harmer
0.252
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.252
960061AF2-297 GEN
Solar/Wind Harmer
4.179
971683AH1-343 GEN
Solar/Wind Harmer
3.235
966621AG1-532 GEN
Solar/Wind Harmer
0.137
313506AB2-031 GEN
Solar/Wind Harmer
0.528
316499AE2-029_GEN
Solar/Wind Helper
0.5
3148013FISHERV
Solar/Wind Helper
0.13
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.535
3144293JTRSVLE
50/50
0.653
3144293JTRSVLE
50/50
0.55
971489AH1-241 GEN
Solar/Wind Harmer
26.738
3146776BUCKING
Solar/Wind Harmer
-0.16
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.488
970301AG2-198 GEN
Solar/Wind Harmer
11.712
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.393
963191AG1-168 GEN
Solar/Wind Harmer
2.036
971741AH1-377 GEN
Solar/Wind Harmer
24.32
316034AC1-036 C
Solar/Wind Harmer
0.327
970323AG2-213 GEN
Solar/Wind Harmer
8.8
971775AH1-396 GEN
Solar/Wind Harmer
1.253
313527AB2-043 GEN
Solar/Wind Harmer
2.087
3143526WINTERP
Solar/Wind Harmer
-0.066
971223AH1-071 GEN
Solar/Wind Harmer
1.588
962561AG1-105 GEN
Solar/Wind Harmer
5.984
939181AE1-148 GEN
Solar/Wind Harmer
5.82
964791AG1-342 GEN
Solar/Wind Harmer
2.187
3146843MT LREL
Solar/Wind Harmer
-0.01
3146843MT LREL
Solar/Wind Harmer
-0.01
970099AG2-077 GEN
Solar/Wind Harmer
12.322
970933AG2-581 GEN
Solar/Wind Harmer
7.227
316181AB2-040 GEN
Solar/Wind Harmer
0.916
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.712
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.187
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.048
LAGNLTFEXP_LAGN->PJM
CLTF
1.137
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.801
TVALTFEXP_TVA->PJM
CLTF
0.555
CPLELTFEXP_CPLE->PJM
CLTF
2.975
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.156
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.386

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:198.54 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1313.88
MW Contribution:15.41
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.18 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1498.1
MW Contribution:15.41
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.18 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1498.08
MW Contribution:15.41
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:177.73 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1437.82
MW Contribution:18.19
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:177.73 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1437.82
MW Contribution:18.19
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.49 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:962.82
MW Contribution:10.81
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970535AG2-341 GEN
50/50
2.556
3152661PLYWOOD A
50/50
0.283
971489AH1-241 GEN
Solar/Wind Harmer
21.838
3146776BUCKING
Solar/Wind Harmer
1.539
3146776BUCKING
Solar/Wind Harmer
0.125
970301AG2-198 GEN
Solar/Wind Harmer
11.486
971741AH1-377 GEN
Solar/Wind Harmer
25.037
3147133PAMPLIN
Solar/Wind Harmer
0.249
3147133PAMPLIN
Solar/Wind Harmer
0.199
315821AE2-092 GEN
Solar/Wind Harmer
0.015
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
316034AC1-036 C
Solar/Wind Harmer
0.015
970323AG2-213 GEN
Solar/Wind Harmer
8.565
971775AH1-396 GEN
Solar/Wind Harmer
0.321
970933AG2-581 GEN
Solar/Wind Harmer
14.707
970099AG2-077 GEN
Solar/Wind Harmer
19.291
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
6.748
964791AG1-342 GEN
Solar/Wind Harmer
2.636
3146843MT LREL
Solar/Wind Harmer
0.137
3146843MT LREL
Solar/Wind Harmer
0.137
939181AE1-148 GEN
Solar/Wind Harmer
6.508
971223AH1-071 GEN
Solar/Wind Harmer
0.865
942751AE2-291 GEN
Solar/Wind Harmer
4.374
316222AC1-221 GEN
Solar/Wind Harmer
0.309
316181AB2-040 GEN
Solar/Wind Harmer
0.1
3145593CAROLNA
Solar/Wind Harmer
0.067
3145593CAROLNA
Solar/Wind Harmer
0.067
966811AG1-552 GEN
Solar/Wind Harmer
0.729
3145593CAROLNA
Solar/Wind Harmer
0.084
3143526WINTERP
Solar/Wind Harmer
0.343
3145783HORNRTN
Solar/Wind Harmer
1.168
3145783HORNRTN
Solar/Wind Harmer
0.934
3145783HORNRTN
Solar/Wind Harmer
0.292
3145783HORNRTN
Solar/Wind Harmer
0.117
316426AA2-053 GEN
Solar/Wind Harmer
0.216
316274AC1-208 GEN
Solar/Wind Harmer
0.297
966001AG1-469 GEN
Solar/Wind Helper
0.193
3151921BEARGRDN G2
50/50
4.277
3144293JTRSVLE
50/50
0.801
970413AG2-270 GEN
50/50
15.972
3151591KERR 2
50/50
0.27
966251AG1-494 GEN
50/50
1.325
3151261ROARAP2
50/50
0.082
970221AG2-151 GEN
Solar/Wind Harmer
21.838
3146776BUCKING
Solar/Wind Harmer
0.139
3146926FARMVIL
Solar/Wind Harmer
0.194
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.872
3147133PAMPLIN
Solar/Wind Harmer
0.783
971193AH1-056 GEN
Solar/Wind Harmer
15.186
963181AG1-167 GEN
Solar/Wind Harmer
0.948
316313AB2-026
Solar/Wind Harmer
0.147
316258AE1-075 C
Solar/Wind Harmer
0.175
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.513
959311AF2-222 GEN
Solar/Wind Harmer
18.323
970257AG2-171 GEN
Solar/Wind Harmer
6.424
315785AD2-033 C
Solar/Wind Harmer
1.572
964241AG1-285 GEN
Solar/Wind Harmer
11.577
316478AD1-087 GEN
Solar/Wind Harmer
0.596
316486AD2-202 GEN
Solar/Wind Harmer
0.175
316131AB2-060 GEN
Solar/Wind Harmer
0.509
958131AF2-107 GEN
Solar/Wind Harmer
3.719
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.197
971683AH1-343 GEN
Solar/Wind Harmer
3.989
3147043LAWRENC
Solar/Wind Harmer
0.058
316283AC2-100 C
Solar/Wind Harmer
0.143
313506AB2-031 GEN
Solar/Wind Harmer
0.212
316499AE2-029_GEN
Solar/Wind Helper
0.498
3132273ORANGE
Solar/Wind Helper
0.027
3148013FISHERV
Solar/Wind Helper
0.128
315616AA1-038_C
Solar/Wind Helper
0.526
3147666LOUISA
Solar/Wind Helper
0.261
3151931BEARGRDN S1
50/50
5.52
3151911BEARGRDN G1
50/50
4.277
3144293JTRSVLE
50/50
0.801
3151531CLOVER1
50/50
3.66
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3147043LAWRENC
50/50
0.93
970119AG2-088 GEN
50/50
10.808
3151261ROARAP2
50/50
0.084
972003AH1-546 GEN
Solar/Wind Harmer
18.967
971377AH1-170 GEN
Solar/Wind Harmer
4.368
3147623JAMES R
Solar/Wind Harmer
0.949
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.154
970937AG2-583 GEN
Solar/Wind Harmer
22.935
3146926FARMVIL
Solar/Wind Harmer
0.194
316336AC2-165 C
Solar/Wind Harmer
0.011
963171AG1-166 GEN
Solar/Wind Harmer
1.265
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3143336POWHATN
Solar/Wind Harmer
4.133
970685AG2-442 GEN
Solar/Wind Harmer
16.387
962491AG1-098 GEN
Solar/Wind Harmer
11.396
315693AD1-088 GEN
Solar/Wind Harmer
9.404
957481AF2-042 GEN
Solar/Wind Harmer
48.226
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.005
970401AG2-262 GEN
Solar/Wind Harmer
0.806
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.784
316129AC1-054 GEN
Solar/Wind Harmer
0.408
971795AH1-408 GEN
Solar/Wind Harmer
5.893
3143226MDLTHAN
Solar/Wind Harmer
0.081
960081AF2-299 GEN
Solar/Wind Harmer
0.671
3143526WINTERP
Solar/Wind Harmer
0.343
3145783HORNRTN
Solar/Wind Harmer
0.066
316190AA2-174 GEN
Solar/Wind Harmer
0
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.79
3147666LOUISA
Solar/Wind Helper
0.453
972205AH1-687 GEN
50/50
20.861
3151541CLOVER2
50/50
3.643
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
316303AF2-085
50/50
1.441
3151281ROARAP4
50/50
0.081
3151281ROARAP4
50/50
0.076
971845AH1-439 GEN
Solar/Wind Harmer
17.22
971447AH1-217 GEN
Solar/Wind Harmer
11.445
970285AG2-188 GEN
Solar/Wind Harmer
29.262
270494AE1-108_GEN
Solar/Wind Harmer
3.857
315657AE1-056 GEN
Solar/Wind Harmer
8.602
946301AF1-294 GEN
Solar/Wind Harmer
4.679
961791AG1-021 GEN
Solar/Wind Harmer
2.276
970683AG2-441 GEN
Solar/Wind Harmer
14.631
970681AG2-440 GEN
Solar/Wind Harmer
11.705
3144303KENBRDG
Solar/Wind Harmer
0.16
971443AH1-215 GEN
Solar/Wind Harmer
3.345
971967AH1-528 GEN
Solar/Wind Harmer
29.413
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.334
3147173SINAI
Solar/Wind Harmer
0.122
3147243WELCO
Solar/Wind Harmer
0.076
970831AG2-522 GEN
Solar/Wind Harmer
4.457
970865AG2-541 GEN
Solar/Wind Harmer
3.533
316123AC1-075 GEN
Solar/Wind Harmer
0.121
970165AG2-112 GEN
Solar/Wind Harmer
0.72
970163AG2-111 GEN
Solar/Wind Harmer
0.686
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.271
316233AE1-074 FULL
Solar/Wind Harmer
0.053
971281AH1-106 GEN
Solar/Wind Harmer
0.915
971283AH1-107 GEN
Solar/Wind Harmer
0.915
315607AA1-063A GEN
Solar/Wind Harmer
0.125
3146043SEABORD
Solar/Wind Harmer
0.06
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.073
3148463FAIRFLD
Solar/Wind Helper
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
1.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.134
TVALTFEXP_TVA->PJM
CLTF
0.807
CPLELTFEXP_CPLE->PJM
CLTF
3.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.173
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.591
MECLTFEXP_MEC->PJM
CLTF
0.444
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.484
LGEELTFEXP_LGEE->PJM
CLTF
0.11
WECLTFEXP_WEC->PJM
CLTF
0.05

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2066-282_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2066-282_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.2 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:883.46
MW Contribution:15.08
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.41
3151911BEARGRDN G1
50/50
4.192
3144293JTRSVLE
50/50
0.653
970119AG2-088 GEN
50/50
15.082
972003AH1-546 GEN
Solar/Wind Harmer
24.312
971377AH1-170 GEN
Solar/Wind Harmer
5.633
3147623JAMES R
Solar/Wind Harmer
0.697
970937AG2-583 GEN
Solar/Wind Harmer
30.216
316322AB2-045
Solar/Wind Harmer
1.35
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.534
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.308
963171AG1-166 GEN
Solar/Wind Harmer
2.715
971563AH1-280 GEN
Solar/Wind Harmer
2.715
970685AG2-442 GEN
Solar/Wind Harmer
17.259
962491AG1-098 GEN
Solar/Wind Harmer
8.747
3143226MDLTHAN
Solar/Wind Harmer
-0.013
316237AB2-079_GEN
Solar/Wind Harmer
0.378
315693AD1-088 GEN
Solar/Wind Harmer
6.258
970401AG2-262 GEN
Solar/Wind Harmer
0.669
957481AF2-042 GEN
Solar/Wind Harmer
30.813
315687AD1-152 GEN
Solar/Wind Harmer
1.088
971065AG2-659 GEN
Solar/Wind Harmer
4.397
3147043LAWRENC
Adder
0.694
316129AC1-054 GEN
Solar/Wind Harmer
0.753
971795AH1-408 GEN
Solar/Wind Harmer
6.032
316003AC1-222 GEN
Solar/Wind Harmer
0.772
960081AF2-299 GEN
Solar/Wind Harmer
0.762
3147983MERCK5
Solar/Wind Helper
0.055
3151921BEARGRDN G2
50/50
4.192
3144293JTRSVLE
50/50
0.653
970221AG2-151 GEN
Solar/Wind Harmer
28.166
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.752
316258AE1-075 C
Solar/Wind Harmer
0.677
316405AF2-144 C
Solar/Wind Harmer
0.714
3143336POWHATN
Solar/Wind Harmer
2.812
942461AE2-259 GEN
Solar/Wind Harmer
4.067
970909AG2-566 GEN
Solar/Wind Harmer
2.224
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.446
963181AG1-167 GEN
Solar/Wind Harmer
2.036
959311AF2-222 GEN
Solar/Wind Harmer
19.01
970257AG2-171 GEN
Solar/Wind Harmer
6.601
315785AD2-033 C
Solar/Wind Harmer
3.8
964241AG1-285 GEN
Solar/Wind Harmer
11.356
958131AF2-107 GEN
Solar/Wind Harmer
4.67
316131AB2-060 GEN
Solar/Wind Harmer
1.422
316478AD1-087 GEN
Solar/Wind Harmer
0.862
316486AD2-202 GEN
Solar/Wind Harmer
0.252
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.252
960061AF2-297 GEN
Solar/Wind Harmer
4.181
971683AH1-343 GEN
Solar/Wind Harmer
3.236
966621AG1-532 GEN
Solar/Wind Harmer
0.138
313506AB2-031 GEN
Solar/Wind Harmer
0.528
316499AE2-029_GEN
Solar/Wind Helper
0.5
3148013FISHERV
Solar/Wind Helper
0.13
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.535
972205AH1-687 GEN
50/50
20.447
316303AF2-085
50/50
2.011
971447AH1-217 GEN
Solar/Wind Harmer
14.757
971845AH1-439 GEN
Solar/Wind Harmer
20.937
970285AG2-188 GEN
Solar/Wind Harmer
33.263
270494AE1-108_GEN
Solar/Wind Harmer
9.168
315657AE1-056 GEN
Solar/Wind Harmer
8.668
946301AF1-294 GEN
Solar/Wind Harmer
5.566
961791AG1-021 GEN
Solar/Wind Harmer
2.715
970683AG2-441 GEN
Solar/Wind Harmer
15.41
970681AG2-440 GEN
Solar/Wind Harmer
12.328
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.43
316239AB2-077_GEN
Solar/Wind Harmer
0.378
316238AB2-078_GEN
Solar/Wind Harmer
0.378
316118AC1-105 GEN
Solar/Wind Harmer
0.639
970831AG2-522 GEN
Solar/Wind Harmer
4.187
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.88
946281AF1-292 GEN
Solar/Wind Harmer
0.152
971967AH1-528 GEN
Solar/Wind Harmer
12.673
316087AB2-174 GEN
Solar/Wind Harmer
0.946
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.118
3144293JTRSVLE
50/50
0.653
3144293JTRSVLE
50/50
0.55
971489AH1-241 GEN
Solar/Wind Harmer
26.74
3146776BUCKING
Solar/Wind Harmer
-0.16
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.489
970301AG2-198 GEN
Solar/Wind Harmer
11.714
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.394
963191AG1-168 GEN
Solar/Wind Harmer
2.036
971741AH1-377 GEN
Solar/Wind Harmer
24.324
316034AC1-036 C
Solar/Wind Harmer
0.327
970323AG2-213 GEN
Solar/Wind Harmer
8.802
971775AH1-396 GEN
Solar/Wind Harmer
1.253
313527AB2-043 GEN
Solar/Wind Harmer
2.088
971223AH1-071 GEN
Solar/Wind Harmer
1.589
962561AG1-105 GEN
Solar/Wind Harmer
5.986
939181AE1-148 GEN
Solar/Wind Harmer
5.822
964791AG1-342 GEN
Solar/Wind Harmer
2.188
3146843MT LREL
Solar/Wind Harmer
-0.01
3146843MT LREL
Solar/Wind Harmer
-0.01
970099AG2-077 GEN
Solar/Wind Harmer
12.325
970933AG2-581 GEN
Solar/Wind Harmer
7.23
316181AB2-040 GEN
Solar/Wind Harmer
0.916
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.712
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.187
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.02
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.044
LAGNLTFEXP_LAGN->PJM
CLTF
1.141
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.807
TVALTFEXP_TVA->PJM
CLTF
0.557
CPLELTFEXP_CPLE->PJM
CLTF
2.977
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.39
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.714
MECLTFEXP_MEC->PJM
CLTF
0.159
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.385

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 219-282_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 219-282_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.87 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:880.73
MW Contribution:15.08
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.41
3151911BEARGRDN G1
50/50
4.192
3144293JTRSVLE
50/50
0.653
970119AG2-088 GEN
50/50
15.079
972003AH1-546 GEN
Solar/Wind Harmer
24.31
971377AH1-170 GEN
Solar/Wind Harmer
5.633
3147623JAMES R
Solar/Wind Harmer
0.697
970937AG2-583 GEN
Solar/Wind Harmer
30.214
316322AB2-045
Solar/Wind Harmer
1.35
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.533
3151921BEARGRDN G2
50/50
4.192
3144293JTRSVLE
50/50
0.653
970221AG2-151 GEN
Solar/Wind Harmer
28.165
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.752
316258AE1-075 C
Solar/Wind Harmer
0.677
316405AF2-144 C
Solar/Wind Harmer
0.714
3143336POWHATN
Solar/Wind Harmer
2.811
942461AE2-259 GEN
Solar/Wind Harmer
4.067
970909AG2-566 GEN
Solar/Wind Harmer
2.224
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.444
963181AG1-167 GEN
Solar/Wind Harmer
2.036
959311AF2-222 GEN
Solar/Wind Harmer
19.007
970257AG2-171 GEN
Solar/Wind Harmer
6.6
315785AD2-033 C
Solar/Wind Harmer
3.799
964241AG1-285 GEN
Solar/Wind Harmer
11.354
958131AF2-107 GEN
Solar/Wind Harmer
4.669
316131AB2-060 GEN
Solar/Wind Harmer
1.422
316478AD1-087 GEN
Solar/Wind Harmer
0.862
316486AD2-202 GEN
Solar/Wind Harmer
0.252
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.252
960061AF2-297 GEN
Solar/Wind Harmer
4.179
971683AH1-343 GEN
Solar/Wind Harmer
3.235
966621AG1-532 GEN
Solar/Wind Harmer
0.137
313506AB2-031 GEN
Solar/Wind Harmer
0.528
316499AE2-029_GEN
Solar/Wind Helper
0.5
3148013FISHERV
Solar/Wind Helper
0.13
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.535
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.307
963171AG1-166 GEN
Solar/Wind Harmer
2.715
971563AH1-280 GEN
Solar/Wind Harmer
2.715
970685AG2-442 GEN
Solar/Wind Harmer
17.256
962491AG1-098 GEN
Solar/Wind Harmer
8.745
3143526WINTERP
Solar/Wind Harmer
-0.066
3143226MDLTHAN
Solar/Wind Harmer
-0.013
316237AB2-079_GEN
Solar/Wind Harmer
0.378
315693AD1-088 GEN
Solar/Wind Harmer
6.256
970401AG2-262 GEN
Solar/Wind Harmer
0.668
957481AF2-042 GEN
Solar/Wind Harmer
30.804
315687AD1-152 GEN
Solar/Wind Harmer
1.088
971065AG2-659 GEN
Solar/Wind Harmer
4.396
3147043LAWRENC
Adder
0.694
316129AC1-054 GEN
Solar/Wind Harmer
0.753
971795AH1-408 GEN
Solar/Wind Harmer
6.029
316003AC1-222 GEN
Solar/Wind Harmer
0.771
960081AF2-299 GEN
Solar/Wind Harmer
0.762
3147983MERCK5
Solar/Wind Helper
0.055
972205AH1-687 GEN
50/50
20.446
316303AF2-085
50/50
2.01
971447AH1-217 GEN
Solar/Wind Harmer
14.756
971845AH1-439 GEN
Solar/Wind Harmer
20.936
970285AG2-188 GEN
Solar/Wind Harmer
33.261
270494AE1-108_GEN
Solar/Wind Harmer
9.167
315657AE1-056 GEN
Solar/Wind Harmer
8.667
946301AF1-294 GEN
Solar/Wind Harmer
5.565
961791AG1-021 GEN
Solar/Wind Harmer
2.715
970683AG2-441 GEN
Solar/Wind Harmer
15.407
970681AG2-440 GEN
Solar/Wind Harmer
12.326
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.429
316233AE1-074 FULL
Solar/Wind Harmer
0.342
971281AH1-106 GEN
Solar/Wind Harmer
2.065
971283AH1-107 GEN
Solar/Wind Harmer
2.065
316239AB2-077_GEN
Solar/Wind Harmer
0.378
316238AB2-078_GEN
Solar/Wind Harmer
0.378
316118AC1-105 GEN
Solar/Wind Harmer
0.639
970831AG2-522 GEN
Solar/Wind Harmer
4.186
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.879
946281AF1-292 GEN
Solar/Wind Harmer
0.152
971967AH1-528 GEN
Solar/Wind Harmer
12.668
316087AB2-174 GEN
Solar/Wind Harmer
0.946
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.118
3144293JTRSVLE
50/50
0.653
3144293JTRSVLE
50/50
0.55
971489AH1-241 GEN
Solar/Wind Harmer
26.738
3146776BUCKING
Solar/Wind Harmer
-0.16
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.488
970301AG2-198 GEN
Solar/Wind Harmer
11.712
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.393
963191AG1-168 GEN
Solar/Wind Harmer
2.036
971741AH1-377 GEN
Solar/Wind Harmer
24.32
316034AC1-036 C
Solar/Wind Harmer
0.327
970323AG2-213 GEN
Solar/Wind Harmer
8.8
971775AH1-396 GEN
Solar/Wind Harmer
1.253
313527AB2-043 GEN
Solar/Wind Harmer
2.087
3143526WINTERP
Solar/Wind Harmer
-0.066
971223AH1-071 GEN
Solar/Wind Harmer
1.588
962561AG1-105 GEN
Solar/Wind Harmer
5.984
939181AE1-148 GEN
Solar/Wind Harmer
5.82
964791AG1-342 GEN
Solar/Wind Harmer
2.187
3146843MT LREL
Solar/Wind Harmer
-0.01
3146843MT LREL
Solar/Wind Harmer
-0.01
970099AG2-077 GEN
Solar/Wind Harmer
12.322
970933AG2-581 GEN
Solar/Wind Harmer
7.227
316181AB2-040 GEN
Solar/Wind Harmer
0.916
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.712
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.187
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.048
LAGNLTFEXP_LAGN->PJM
CLTF
1.137
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.801
TVALTFEXP_TVA->PJM
CLTF
0.555
CPLELTFEXP_CPLE->PJM
CLTF
2.975
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.156
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.386

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.74 %
Rating:661.76 MVA
Rating Type:A
MVA to Mitigate:719.62
MW Contribution:11.6
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.118
3144293JTRSVLE
50/50
0.644
970413AG2-270 GEN
50/50
8.224
3151591KERR 2
50/50
0.18
966251AG1-494 GEN
50/50
1.173
3151261ROARAP2
50/50
0.07
970221AG2-151 GEN
Solar/Wind Harmer
21.013
3151931BEARGRDN S1
50/50
5.314
3151911BEARGRDN G1
50/50
4.118
3144293JTRSVLE
50/50
0.644
3151531CLOVER1
50/50
1.885
3151601KERR 3
50/50
0.18
3151581KERR 1
50/50
0.064
970119AG2-088 GEN
50/50
11.599
3147043LAWRENC
50/50
0.746
3151261ROARAP2
50/50
0.072
972003AH1-546 GEN
Solar/Wind Harmer
18.108
971377AH1-170 GEN
Solar/Wind Harmer
4.203
3147623JAMES R
Solar/Wind Harmer
0.913
970937AG2-583 GEN
Solar/Wind Harmer
22.204
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.165
316336AC2-165 C
Solar/Wind Harmer
0.01
3143336POWHATN
Solar/Wind Harmer
4.074
963171AG1-166 GEN
Solar/Wind Harmer
1.017
971563AH1-280 GEN
Solar/Wind Harmer
2.035
970685AG2-442 GEN
Solar/Wind Harmer
12.945
962491AG1-098 GEN
Solar/Wind Harmer
6.577
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
5.296
970401AG2-262 GEN
Solar/Wind Harmer
0.531
957481AF2-042 GEN
Solar/Wind Harmer
23.244
3143226MDLTHAN
Solar/Wind Harmer
0.087
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.352
316129AC1-054 GEN
Solar/Wind Harmer
0.289
971795AH1-408 GEN
Solar/Wind Harmer
4.849
3143526WINTERP
Solar/Wind Harmer
0.377
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.595
3145783HORNRTN
Solar/Wind Harmer
0.057
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.752
3144293JTRSVLE
50/50
0.644
3144293JTRSVLE
50/50
0.543
970535AG2-341 GEN
50/50
1.768
3152661PLYWOOD A
50/50
0.177
971489AH1-241 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
1.404
3146776BUCKING
Solar/Wind Harmer
0.114
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
8.767
3147133PAMPLIN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.162
958211AF2-115 GEN
Solar/Wind Harmer
2.289
963191AG1-168 GEN
Solar/Wind Harmer
0.763
971741AH1-377 GEN
Solar/Wind Harmer
18.217
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.61
971775AH1-396 GEN
Solar/Wind Harmer
0.248
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
4.515
939181AE1-148 GEN
Solar/Wind Harmer
4.407
964791AG1-342 GEN
Solar/Wind Harmer
1.738
3146843MT LREL
Solar/Wind Harmer
0.09
3146843MT LREL
Solar/Wind Harmer
0.09
970099AG2-077 GEN
Solar/Wind Harmer
9.298
971223AH1-071 GEN
Solar/Wind Harmer
0.928
3143526WINTERP
Solar/Wind Harmer
0.377
970933AG2-581 GEN
Solar/Wind Harmer
5.476
316181AB2-040 GEN
Solar/Wind Harmer
0.087
3145593CAROLNA
Solar/Wind Harmer
0.058
3145593CAROLNA
Solar/Wind Harmer
0.058
966811AG1-552 GEN
Solar/Wind Harmer
0.627
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.01
3145783HORNRTN
Solar/Wind Harmer
0.808
3145783HORNRTN
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
0.101
966001AG1-469 GEN
Solar/Wind Helper
0.19
3146776BUCKING
Solar/Wind Harmer
0.126
3146926FARMVIL
Solar/Wind Harmer
0.165
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.463
970909AG2-566 GEN
Solar/Wind Harmer
2.192
3147133PAMPLIN
Solar/Wind Harmer
0.637
971193AH1-056 GEN
Solar/Wind Harmer
12.353
963181AG1-167 GEN
Solar/Wind Harmer
0.763
959311AF2-222 GEN
Solar/Wind Harmer
14.242
970257AG2-171 GEN
Solar/Wind Harmer
4.957
315785AD2-033 C
Solar/Wind Harmer
1.2
964241AG1-285 GEN
Solar/Wind Harmer
8.548
958131AF2-107 GEN
Solar/Wind Harmer
3.44
316131AB2-060 GEN
Solar/Wind Harmer
0.366
316478AD1-087 GEN
Solar/Wind Harmer
0.307
316486AD2-202 GEN
Solar/Wind Harmer
0.09
3147043LAWRENC
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.155
971683AH1-343 GEN
Solar/Wind Harmer
2.44
313506AB2-031 GEN
Solar/Wind Harmer
0.186
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.54
972205AH1-687 GEN
50/50
20.083
3151541CLOVER2
50/50
1.876
3151611KERR 4
50/50
0.18
3151621KERR 5
50/50
0.18
3151631KERR 6
50/50
0.18
3151641KERR 7
50/50
0.18
316303AF2-085
50/50
1.546
3151281ROARAP4
50/50
0.07
3151281ROARAP4
50/50
0.066
971447AH1-217 GEN
Solar/Wind Harmer
11.004
971845AH1-439 GEN
Solar/Wind Harmer
15.632
970285AG2-188 GEN
Solar/Wind Harmer
26.316
270494AE1-108_GEN
Solar/Wind Harmer
3.693
315657AE1-056 GEN
Solar/Wind Harmer
6.997
946301AF1-294 GEN
Solar/Wind Harmer
3.764
961791AG1-021 GEN
Solar/Wind Harmer
1.831
970683AG2-441 GEN
Solar/Wind Harmer
11.558
970681AG2-440 GEN
Solar/Wind Harmer
9.247
3144303KENBRDG
Solar/Wind Harmer
0.124
971443AH1-215 GEN
Solar/Wind Harmer
2.576
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.212
970831AG2-522 GEN
Solar/Wind Harmer
3.201
3147173SINAI
Solar/Wind Harmer
0.074
3147243WELCO
Solar/Wind Harmer
0.046
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.006
971283AH1-107 GEN
Solar/Wind Harmer
1.006
970865AG2-541 GEN
Solar/Wind Harmer
2.17
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
9.597
3137643SOCKMAN
Solar/Wind Harmer
0.235
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.119
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.029
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.072
LAGNLTFEXP_LAGN->PJM
CLTF
1.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.815
TVALTFEXP_TVA->PJM
CLTF
0.547
CPLELTFEXP_CPLE->PJM
CLTF
2.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.673
MECLTFEXP_MEC->PJM
CLTF
0.138
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.391

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:137.15 %
Rating:1057.5 MVA
Rating Type:B
MVA to Mitigate:1450.33
MW Contribution:52.94
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
52.941
3150851SPRUNCC
50/50
1.044
3143096IRON208
50/50
0.687
3151931BEARGRDN S1
50/50
1.658
3151911BEARGRDN G1
50/50
1.285
3143226MDLTHAN
Solar/Wind Harmer
0.397
3143526WINTERP
Solar/Wind Harmer
1.653
3143336POWHATN
Solar/Wind Harmer
5.221
316336AC2-165 C
Solar/Wind Harmer
0.01
970937AG2-583 GEN
Solar/Wind Harmer
12.089
3142543TWELFTH
Solar/Wind Harmer
0.016
972003AH1-546 GEN
Solar/Wind Harmer
5.766
944631AF1-128 GEN
Adder
61.208
315671AE2-027_GEN
Solar/Wind Harmer
7.993
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.05
971377AH1-170 GEN
Solar/Wind Harmer
1.322
3147623JAMES R
Solar/Wind Harmer
0.287
970129AG2-093 GEN
Solar/Wind Harmer
3.337
316458AB2-190 GEN2
Solar/Wind Harmer
0.626
971069AG2-661 GEN
Solar/Wind Harmer
2.011
3146926FARMVIL
Solar/Wind Harmer
0.068
3142416OLDCHRC
Solar/Wind Harmer
0.283
3142416OLDCHRC
Solar/Wind Harmer
0.109
3142433PROV 92
Solar/Wind Harmer
0.434
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
971647AH1-324 GEN
Solar/Wind Harmer
4.589
970659AG2-427 GEN
Solar/Wind Harmer
5.129
316381AD1-082 GEN
Solar/Wind Harmer
0.11
961611AG1-000B GEN
Solar/Wind Harmer
5.476
970661AG2-428 GEN
Solar/Wind Harmer
10.195
3151171GRAVELC
Adder
1.069
963171AG1-166 GEN
Solar/Wind Harmer
0.527
971563AH1-280 GEN
Solar/Wind Harmer
1.053
3144293JTRSVLE
Adder
0.314
3145336SMITFLD
Solar/Wind Harmer
0.384
970685AG2-442 GEN
Solar/Wind Harmer
7.154
971777AH1-397 GEN
Solar/Wind Harmer
0.248
3141843SHACKLE
Adder
0.481
316159AE1-175 C
Solar/Wind Harmer
0.081
3141766HARMONY
Solar/Wind Harmer
0.018
3138126ROCKLANDING
Solar/Wind Harmer
0.042
316072AD1-144
Solar/Wind Harmer
0.033
316093AE2-104_GEN
Solar/Wind Harmer
1.516
971317AH1-138 GEN
Solar/Wind Harmer
0.671
962491AG1-098 GEN
Solar/Wind Harmer
5.114
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.112
315693AD1-088 GEN
Solar/Wind Harmer
4.267
316023GEN1_S
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.04
940641AE2-051 GEN
Solar/Wind Harmer
7.055
939411AE1-173 GEN
Solar/Wind Harmer
37.578
3138133OCRAN
Solar/Wind Harmer
0.053
316388AE2-253 GEN
Solar/Wind Harmer
0.275
3146456SLIGO L269
Solar/Wind Harmer
0.088
944591AF1-124 GEN
Solar/Wind Harmer
19.745
960081AF2-299 GEN
Solar/Wind Harmer
0.838
971795AH1-408 GEN
Solar/Wind Harmer
5.798
3147043LAWRENC
Adder
0.785
3146516WINFALL
Solar/Wind Harmer
0.281
3146516WINFALL
Solar/Wind Harmer
0.087
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
957481AF2-042 GEN
Solar/Wind Harmer
22.879
3130156CHOWAN
Solar/Wind Harmer
0.085
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.467
3145893MURPHYS
Solar/Wind Harmer
0.336
3145893MURPHYS
Solar/Wind Harmer
0.374
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.72
316011AB1-132 GEN
Solar/Wind Harmer
1.515
962571AG1-106 GEN
Solar/Wind Harmer
1.186
3146173TUNIS
Solar/Wind Harmer
0.083
316190AA2-174 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.083
971547AH1-271 GEN
Solar/Wind Harmer
1.762
3146263WOODLND
Solar/Wind Harmer
0.082
3145783HORNRTN
Solar/Wind Harmer
0.082
970919AG2-571 GEN
Solar/Wind Harmer
2.926
3145683EARLEYS
Solar/Wind Harmer
0.082
970087AG2-069 GEN
Solar/Wind Harmer
6.559
316129AC1-054 GEN
Solar/Wind Harmer
0.308
3145796HORNRTN
Solar/Wind Harmer
0.27
3145796HORNRTN
Solar/Wind Harmer
0.082
971065AG2-659 GEN
Solar/Wind Harmer
3.493
3145823KELFORD
Solar/Wind Harmer
0.081
962861AG1-135 GEN
Solar/Wind Harmer
2.586
3145963POPLR C
Solar/Wind Harmer
0.08
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316212AC1-099_GEN
Solar/Wind Harmer
0.408
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3141726DUNNSVL
Solar/Wind Harmer
0.313
970401AG2-262 GEN
Solar/Wind Harmer
0.457
315722AD1-056 GEN
Solar/Wind Harmer
0.488
3146293MARTNCO
Solar/Wind Harmer
0.071
3150351NORNECKC2
Adder
0.757
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
316494AC1-189 GEN
Solar/Wind Harmer
0.253
3146233WITAKRS
Solar/Wind Harmer
0.298
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.074
3145493TOT1
Solar/Wind Harmer
0.33
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
316359AB2-059 GEN
Solar/Wind Harmer
0.263
316049AB1-081 GEN
Solar/Wind Harmer
0.42
3142053HEARTS
Solar/Wind Harmer
0.129
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316337AD2-073 GEN
Solar/Wind Harmer
0.06
316045AC1-158 PL2
Solar/Wind Helper
2.716
3147666LOUISA
Solar/Wind Helper
0.467
316192AB2-158 GEN
Solar/Wind Helper
0.764
3150861SPRUNCD
50/50
1.044
3143096IRON208
50/50
0.687
3143096IRON208
50/50
0.673
3151921BEARGRDN G2
50/50
1.285
316313AB2-026
Solar/Wind Harmer
0.185
316258AE1-075 C
Solar/Wind Harmer
0.222
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.438
3146776BUCKING
Solar/Wind Harmer
0.045
970221AG2-151 GEN
Solar/Wind Harmer
6.608
965281AG1-393 GEN
Solar/Wind Harmer
1.316
315839AE2-212 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
1.182
970293AG2-193 GEN
Solar/Wind Harmer
1.304
3142946ENON
Solar/Wind Harmer
0.04
970129AG2-093 GEN
Solar/Wind Harmer
7.091
315778AD1-151 GEN
Solar/Wind Harmer
9.051
3146926FARMVIL
Solar/Wind Harmer
0.068
315813AE1-149 C
Solar/Wind Harmer
5.92
316473AC1-191 GEN
Solar/Wind Harmer
0.369
3142416OLDCHRC
Solar/Wind Harmer
1.056
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
1.122
316083AB2-161 GEN
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.784
970909AG2-566 GEN
Solar/Wind Harmer
1.096
970661AG2-428 GEN
Solar/Wind Harmer
2.168
3147133PAMPLIN
Solar/Wind Harmer
0.316
971193AH1-056 GEN
Solar/Wind Harmer
6.137
3151221GRAVEL6
Adder
7.305
3151171GRAVELC
Adder
1.406
963181AG1-167 GEN
Solar/Wind Harmer
0.395
3144293JTRSVLE
Adder
0.314
3145336SMITFLD
Solar/Wind Harmer
0.038
3141843SHACKLE
Adder
0.481
316203AE2-005 GEN
Solar/Wind Harmer
0
959311AF2-222 GEN
Solar/Wind Harmer
8.32
316382AG1-145 C
Solar/Wind Harmer
0.001
970257AG2-171 GEN
Solar/Wind Harmer
2.966
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.23
315785AD2-033 C
Solar/Wind Harmer
0.744
3144216WINCHST
Adder
0.345
3144536CHRHLND
Solar/Wind Harmer
0.014
316156AD2-030 GEN
Solar/Wind Harmer
0.067
3141873WAN 176
Solar/Wind Harmer
1.611
3150921YORKTN3
Adder
2.265
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.251
3145273HOLLAND
Solar/Wind Harmer
0.066
316365GEN2_N
Solar/Wind Harmer
0.199
964241AG1-285 GEN
Solar/Wind Harmer
5.88
3146456SLIGO L269
Solar/Wind Harmer
0.088
971153AH1-033 GEN
Solar/Wind Harmer
1.013
944581AF1-123 GEN
Solar/Wind Harmer
19.675
944601AF1-125 GEN
Solar/Wind Harmer
19.372
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0.001
3147043LAWRENC
Solar/Wind Harmer
0.052
3146516WINFALL
Solar/Wind Harmer
0.087
3146626S HERTFORD
Solar/Wind Harmer
0.086
316131AB2-060 GEN
Solar/Wind Harmer
0.271
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
313506AB2-031 GEN
Solar/Wind Harmer
0.264
3146376EDENTON
Solar/Wind Harmer
0.085
315773AC2-141 GEN
Solar/Wind Harmer
3.093
3145893MURPHYS
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
0.084
962971AG1-146 GEN
Solar/Wind Harmer
1.345
315614AA2-178 GEN
Solar/Wind Harmer
0.481
957521AF2-046 GEN
Solar/Wind Harmer
6.241
961681AG1-008 GEN
Solar/Wind Harmer
6.241
316478AD1-087 GEN
Solar/Wind Harmer
0.292
316486AD2-202 GEN
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3146173TUNIS
Solar/Wind Harmer
0.083
971157AH1-035 GEN
Solar/Wind Harmer
0.997
315737AD1-076 GEN
Solar/Wind Harmer
1.067
316463AE2-346 GEN
Solar/Wind Harmer
0.071
316140AB2-099
Solar/Wind Harmer
0.03
962331AG1-082 GEN
Solar/Wind Harmer
0.882
3146206CASHIE
Solar/Wind Harmer
0.083
970009AG2-005 GEN
Solar/Wind Harmer
0.617
3146263WOODLND
Solar/Wind Harmer
0.082
970917AG2-570 GEN
Solar/Wind Harmer
7.314
3156021HOLLOMANSOL
Solar/Wind Harmer
0.373
3145796HORNRTN
Solar/Wind Harmer
0.327
3145796HORNRTN
Solar/Wind Harmer
0.082
971781AH1-399 GEN
Solar/Wind Harmer
0.107
316317KELFORD C
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.081
316404AE1-155 C
Solar/Wind Harmer
0.018
3145963POPLR C
Solar/Wind Harmer
0.08
316210AC1-098 GEN
Solar/Wind Harmer
0.732
315724AD1-057 GEN
Solar/Wind Harmer
0.29
3145933PARMELE
Solar/Wind Harmer
0.077
966801AG1-551 GEN
Solar/Wind Harmer
0.897
316327AA2-057 GEN
Solar/Wind Harmer
0.115
3150351NORNECKC2
Adder
0.769
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3146233WITAKRS
Solar/Wind Harmer
0.375
3146233WITAKRS
Solar/Wind Harmer
0.051
3138543CONSLDL
Solar/Wind Harmer
0.049
3146073TAR RVR
Solar/Wind Harmer
0.074
3146083TARBORO
Solar/Wind Harmer
0.074
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
961601AG1-000A GEN
Solar/Wind Harmer
5.213
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.088
971683AH1-343 GEN
Solar/Wind Harmer
2.46
316283AC2-100 C
Solar/Wind Harmer
0.122
3141906WESTMOR
Solar/Wind Harmer
0.024
958131AF2-107 GEN
Solar/Wind Harmer
1.633
316044AC1-158 PL1
Solar/Wind Helper
0.848
316450AC1-158 RIC
Solar/Wind Helper
0.226
3147666LOUISA
Solar/Wind Helper
0.269
3142366NRTHEST
50/50
0.483
3150691DARBY 3
50/50
10.163
3150701DARBY 4
50/50
10.139
3150681DARBY 2
50/50
10.127
3150671DARBY 1
50/50
10.115
944641AF1-129 GEN
50/50
66.432
971223AH1-071 GEN
Solar/Wind Harmer
4.235
3143526WINTERP
Solar/Wind Harmer
1.653
316240AF1-291 C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.497
3146776BUCKING
Solar/Wind Harmer
0.04
971489AH1-241 GEN
Solar/Wind Harmer
6.608
3142946ENON
Solar/Wind Harmer
0.012
3142296MT RD221
Adder
0.38
316033AB2-134 GEN
Solar/Wind Harmer
0.006
315697AD1-025 GEN
Solar/Wind Harmer
0.124
316075AC2-137 C
Solar/Wind Harmer
0.03
966871AG1-558 GEN
Solar/Wind Harmer
0.126
970657AG2-426 GEN
Solar/Wind Harmer
3.648
970657AG2-426 GEN
Solar/Wind Harmer
0.765
970301AG2-198 GEN
Solar/Wind Harmer
4.386
3147133PAMPLIN
Solar/Wind Harmer
0.101
3147133PAMPLIN
Solar/Wind Harmer
0.081
971741AH1-377 GEN
Solar/Wind Harmer
9.881
958211AF2-115 GEN
Solar/Wind Harmer
1.185
963191AG1-168 GEN
Solar/Wind Harmer
0.395
3144293JTRSVLE
Adder
0.314
3144293JTRSVLE
Adder
0.265
3144356SAPONY
Solar/Wind Harmer
0.819
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316034AC1-036 C
Solar/Wind Harmer
0.007
970323AG2-213 GEN
Solar/Wind Harmer
3.955
971775AH1-396 GEN
Solar/Wind Harmer
0.148
315821AE2-092 GEN
Solar/Wind Harmer
0.006
316036AC1-147 C
Solar/Wind Harmer
0.017
3150991CHESPKB
Adder
0.933
3150991CHESPKB
Adder
0.911
316316AC1-027 C
Solar/Wind Harmer
0.085
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3145506HICKORY
Solar/Wind Harmer
0.351
3145506HICKORY
Solar/Wind Harmer
0.211
3145506HICKORY
Solar/Wind Harmer
0.053
316339AD2-160 GEN
Solar/Wind Harmer
0.142
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.049
3137176SLIGO L2192
Solar/Wind Harmer
0.349
3146456SLIGO L269
Solar/Wind Harmer
1.551
3130086AYDLETT
Solar/Wind Harmer
0.35
3146386ELIZ CT
Solar/Wind Harmer
0.087
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
970933AG2-581 GEN
Solar/Wind Harmer
6.917
3146626S HERTFORD
Solar/Wind Harmer
0.086
3146626S HERTFORD
Solar/Wind Harmer
0.086
970099AG2-077 GEN
Solar/Wind Harmer
9.151
313527AB2-043 GEN
Solar/Wind Harmer
0.001
972185AH1-677 GEN
Adder
4.805
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3146376EDENTON
Solar/Wind Harmer
0.379
3146376EDENTON
Solar/Wind Harmer
0.379
972187AH1-678 GEN
Adder
2.42
3145893MURPHYS
Solar/Wind Harmer
0.563
3145893MURPHYS
Solar/Wind Harmer
0.151
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
3146173TUNIS
Solar/Wind Harmer
0.083
3146173TUNIS
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.901
3145593CAROLNA
Solar/Wind Harmer
0.103
316426AA2-053 GEN
Solar/Wind Harmer
0.28
316065AD1-022 GEN
Solar/Wind Harmer
3.808
3145783HORNRTN
Solar/Wind Harmer
1.465
3145783HORNRTN
Solar/Wind Harmer
1.172
3145783HORNRTN
Solar/Wind Harmer
0.366
3145783HORNRTN
Solar/Wind Harmer
0.146
939181AE1-148 GEN
Solar/Wind Harmer
3.944
3145796HORNRTN
Solar/Wind Harmer
0.246
316468AD1-105 GEN
Solar/Wind Harmer
-0.026
958261AF2-120 GEN
Solar/Wind Harmer
2.652
962561AG1-105 GEN
Solar/Wind Harmer
3.799
316274AC1-208 GEN
Solar/Wind Harmer
0.409
964791AG1-342 GEN
Solar/Wind Harmer
1.497
3146843MT LREL
Solar/Wind Harmer
0.078
3146843MT LREL
Solar/Wind Harmer
0.078
3145933PARMELE
Solar/Wind Harmer
0.154
3145933PARMELE
Solar/Wind Harmer
0.077
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.795
3150341NORNECKC1
Adder
0.788
3145493TOT1
Solar/Wind Harmer
0.172
3145453TOT5
Solar/Wind Harmer
0.103
3145603CNETO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
1.303
316263AC1-034 GEN
Solar/Wind Harmer
2.786
316222AC1-221 GEN
Solar/Wind Harmer
0.261
316447AC1-158 HLD
Solar/Wind Helper
1.867
316303AF2-085
50/50
7.059
971285AH1-108 GEN
50/50
1.708
972205AH1-687 GEN
50/50
6.267
316233AE1-074 FULL
Solar/Wind Harmer
0.255
971281AH1-106 GEN
Solar/Wind Harmer
4.412
971283AH1-107 GEN
Solar/Wind Harmer
4.412
971845AH1-439 GEN
Solar/Wind Harmer
5.597
970285AG2-188 GEN
Solar/Wind Harmer
9.622
971447AH1-217 GEN
Solar/Wind Harmer
3.562
316132AB2-190 GEN1
Solar/Wind Harmer
0.626
3143316POE
Solar/Wind Harmer
0.447
971167AH1-042 GEN
Solar/Wind Harmer
9.861
316369SG1_INVT
Solar/Wind Harmer
0.004
316312AB1-027
Solar/Wind Harmer
0.195
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
270494AE1-108_GEN
Solar/Wind Harmer
1.234
315976AC1-164 GENA
Solar/Wind Harmer
10.641
316169AC1-164_GENC
Solar/Wind Harmer
9.193
315975AC1-164 GENB
Solar/Wind Harmer
0.315
315657AE1-056 GEN
Solar/Wind Harmer
3.476
972265AH1-717 GEN
Adder
7.802
3151201GRAVEL4
Adder
7.314
3151191GRAVEL3
Adder
7.221
3151211GRAVEL5
Adder
7.221
3143873LANEXA
Solar/Wind Harmer
0.059
946301AF1-294 GEN
Solar/Wind Harmer
1.948
961791AG1-021 GEN
Solar/Wind Harmer
0.948
316315AB2-025 C
Solar/Wind Harmer
0.079
315814AE2-033 C
Solar/Wind Harmer
7.71
971445AH1-216 GEN
Solar/Wind Harmer
6.794
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.066
316311AC2-079 GEN
Solar/Wind Harmer
2.751
970683AG2-441 GEN
Solar/Wind Harmer
6.388
970681AG2-440 GEN
Solar/Wind Harmer
5.11
970189AG2-124 GEN
Solar/Wind Harmer
2.786
316314AB2-024 C
Solar/Wind Harmer
0
3144303KENBRDG
Solar/Wind Harmer
0.074
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.553
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.018
3138283WHITEMARSH
Solar/Wind Harmer
0.021
315835AF2-110_GEN
Solar/Wind Harmer
0.619
3152611GOSPORTB
Adder
1.135
3152621GOSPORTC
Adder
0.963
3152601GOSPORTA
Adder
0.888
3151081ELIZAR1
Adder
8.147
3151091ELIZAR2
Adder
8.006
3141913WHIT STONE
Solar/Wind Harmer
0.088
316305AF2-043 C
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.026
957871AF2-081 GEN
Solar/Wind Harmer
4.367
319010AE1-072 C
Solar/Wind Harmer
0.441
3146406KITTY HAWK
Solar/Wind Harmer
0.011
3146486SUNBURY
Solar/Wind Harmer
0.087
3146486SUNBURY
Solar/Wind Harmer
0.087
313526AB2-022
Solar/Wind Harmer
0.047
941031AE2-094 GEN
Solar/Wind Harmer
16.035
944011AF1-069 GEN
Solar/Wind Harmer
5.239
316321Z2-027
Solar/Wind Harmer
0.016
3145176PASQUOTANK
Solar/Wind Harmer
0.054
3146396TANGLEW
Solar/Wind Harmer
0.24
3141783LANCAST
Solar/Wind Harmer
0.052
3141783LANCAST
Solar/Wind Harmer
0.035
971967AH1-528 GEN
Solar/Wind Harmer
13.837
970673AG2-436 GEN
Solar/Wind Harmer
18.368
970673AG2-436 GEN
Solar/Wind Harmer
12.246
316087AB2-174 GEN
Solar/Wind Harmer
0.002
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
0.085
965291AG1-394 GEN
Solar/Wind Harmer
0.378
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
0.084
3137643SOCKMAN
Solar/Wind Harmer
0.336
962981AG1-147 GEN
Solar/Wind Harmer
3.138
3146043SEABORD
Solar/Wind Harmer
0.084
315816AE2-034 GEN
Solar/Wind Harmer
0.36
315607AA1-063A GEN
Solar/Wind Harmer
0.171
315652AC1-086 GEN
Solar/Wind Harmer
9.169
3130546PLYMOUTH
Solar/Wind Harmer
0.083
315732AD1-074 GEN1
Solar/Wind Harmer
0.476
315733AD1-074 GEN2
Solar/Wind Harmer
0.476
315735AD1-075 GEN1
Solar/Wind Harmer
0.238
3145513AHOSKIE
Solar/Wind Harmer
0.173
3145513AHOSKIE
Solar/Wind Harmer
0.083
3146206CASHIE
Solar/Wind Harmer
0.083
970601AG2-382 GEN
Solar/Wind Harmer
3.084
970327AG2-215 GEN
Solar/Wind Harmer
2.71
3145683EARLEYS
Solar/Wind Harmer
0.164
3145683EARLEYS
Solar/Wind Harmer
0.082
3145683EARLEYS
Solar/Wind Harmer
0.082
970831AG2-522 GEN
Solar/Wind Harmer
3.502
970085AG2-068 GEN
Solar/Wind Harmer
4.372
970581AG2-369 GEN
Solar/Wind Harmer
3.76
3145796HORNRTN
Solar/Wind Harmer
0.262
3145796HORNRTN
Solar/Wind Harmer
0.033
3146033SCOT NK
Solar/Wind Harmer
0.319
972189AH1-679 GEN
Adder
1.329
3141813NORNECK
Solar/Wind Harmer
0.076
316005AA1-067
Solar/Wind Harmer
0.081
3145746EVERETS
Solar/Wind Harmer
0.301
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
970181AG2-120 GEN
Solar/Wind Harmer
0.942
316118AC1-105 GEN
Solar/Wind Harmer
0.194
957861AF2-080 GEN
Solar/Wind Harmer
3.228
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.002
3145573BETHELC
Solar/Wind Harmer
0.074
3145573BETHELC
Solar/Wind Harmer
0.074
3147173SINAI
Solar/Wind Harmer
0.072
3147243WELCO
Solar/Wind Harmer
0.045
970865AG2-541 GEN
Solar/Wind Harmer
2.225
316223AC1-118
Solar/Wind Harmer
0.043
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.477
970163AG2-111 GEN
Solar/Wind Harmer
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
3.494
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.348
TVALTFEXP_TVA->PJM
CLTF
1.763
CPLELTFEXP_CPLE->PJM
CLTF
4.706
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.653
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.067
MECLTFEXP_MEC->PJM
CLTF
1.74
SIGELTFEXP_SIGE->PJM
CLTF
0.053
NYPJM->LTFIMP_NY
CLTF
1.086
LGEELTFEXP_LGEE->PJM
CLTF
0.65
WECLTFEXP_WEC->PJM
CLTF
0.327

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.36 %
Rating:1265.1 MVA
Rating Type:C
MVA to Mitigate:1585.98
MW Contribution:52.91
Bus #Bus NameTypeMW Contribution
3150861SPRUNCD
50/50
1.043
3143096IRON208
50/50
0.685
3143096IRON208
50/50
0.672
3151921BEARGRDN G2
50/50
1.287
316313AB2-026
Solar/Wind Harmer
0.89
316258AE1-075 C
Solar/Wind Harmer
0.801
316405AF2-144 C
Solar/Wind Harmer
0.845
3143336POWHATN
Solar/Wind Harmer
3.328
3146776BUCKING
Solar/Wind Harmer
-0.005
970221AG2-151 GEN
Solar/Wind Harmer
8.715
315839AE2-212 C
Solar/Wind Harmer
0.419
965281AG1-393 GEN
Solar/Wind Harmer
1.738
970133AG2-095 GEN
Solar/Wind Harmer
1.553
970293AG2-193 GEN
Solar/Wind Harmer
1.709
970119AG2-088 GEN
50/50
52.906
3150851SPRUNCC
50/50
1.043
3143096IRON208
50/50
0.685
3151931BEARGRDN S1
50/50
1.661
3151911BEARGRDN G1
50/50
1.287
3143226MDLTHAN
Solar/Wind Harmer
-0.044
3143526WINTERP
Solar/Wind Harmer
-0.185
3143336POWHATN
Solar/Wind Harmer
3.915
316336AC2-165 C
Solar/Wind Harmer
5.205
970937AG2-583 GEN
Solar/Wind Harmer
15.927
3142543TWELFTH
Solar/Wind Harmer
-0.002
972003AH1-546 GEN
Solar/Wind Harmer
7.621
944631AF1-128 GEN
Adder
60.98
315671AE2-027_GEN
Solar/Wind Harmer
10.549
316322AB2-045
Solar/Wind Harmer
0.472
3146776BUCKING
Solar/Wind Harmer
-0.006
971377AH1-170 GEN
Solar/Wind Harmer
1.743
3147623JAMES R
Solar/Wind Harmer
0.216
970129AG2-093 GEN
Solar/Wind Harmer
2.995
316458AB2-190 GEN2
Solar/Wind Harmer
1.321
3146926FARMVIL
Solar/Wind Harmer
-0.008
971069AG2-661 GEN
Solar/Wind Harmer
2.001
3142416OLDCHRC
Solar/Wind Harmer
-0.032
3142416OLDCHRC
Solar/Wind Harmer
-0.012
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
971647AH1-324 GEN
Solar/Wind Harmer
6.002
970659AG2-427 GEN
Solar/Wind Harmer
6.334
316381AD1-082 GEN
Solar/Wind Harmer
1.083
961611AG1-000B GEN
Solar/Wind Harmer
5.745
970661AG2-428 GEN
Solar/Wind Harmer
12.22
963171AG1-166 GEN
Solar/Wind Harmer
1.401
971563AH1-280 GEN
Solar/Wind Harmer
1.401
3144293JTRSVLE
Adder
0.317
3151171GRAVELC
Adder
1.059
970685AG2-442 GEN
Solar/Wind Harmer
9.521
3145336SMITFLD
Solar/Wind Harmer
-0.042
971777AH1-397 GEN
Solar/Wind Harmer
1.23
3141843SHACKLE
Adder
0.476
316159AE1-175 C
Solar/Wind Harmer
0.278
3141766HARMONY
Solar/Wind Harmer
-0.002
962491AG1-098 GEN
Solar/Wind Harmer
6.852
315693AD1-088 GEN
Solar/Wind Harmer
5.084
316023GEN1_S
Solar/Wind Harmer
0.679
3138126ROCKLANDING
Solar/Wind Harmer
0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.922
316072AD1-144
Solar/Wind Harmer
0.203
939411AE1-173 GEN
Solar/Wind Harmer
50.033
971317AH1-138 GEN
Solar/Wind Harmer
1.242
960081AF2-299 GEN
Solar/Wind Harmer
1.115
971795AH1-408 GEN
Solar/Wind Harmer
7.407
316375AC2-012 GEN
Solar/Wind Harmer
3.414
3150981CHESPKA
Adder
1.096
3147043LAWRENC
Adder
0.794
957481AF2-042 GEN
Solar/Wind Harmer
30.736
316246AF1-032 C
Solar/Wind Harmer
0.199
3138133OCRAN
Solar/Wind Harmer
-0.006
316388AE2-253 GEN
Solar/Wind Harmer
0.656
3146456SLIGO L269
Solar/Wind Harmer
-0.01
316237AB2-079_GEN
Solar/Wind Harmer
0.292
944591AF1-124 GEN
Solar/Wind Harmer
44.111
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.01
315800Z1-036_GEN1
Solar/Wind Harmer
2.363
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.038
970919AG2-571 GEN
Solar/Wind Harmer
2.997
3145893MURPHYS
Solar/Wind Harmer
0.281
3142366NRTHEST
50/50
0.481
3150691DARBY 3
50/50
10.129
3150701DARBY 4
50/50
10.105
3150681DARBY 2
50/50
10.093
3150671DARBY 1
50/50
10.082
944641AF1-129 GEN
50/50
66.507
971223AH1-071 GEN
Solar/Wind Harmer
5.573
3143526WINTERP
Solar/Wind Harmer
-0.185
316240AF1-291 C
Solar/Wind Harmer
0.438
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.005
971489AH1-241 GEN
Solar/Wind Harmer
8.274
3142946ENON
Solar/Wind Harmer
-0.001
3142296MT RD221
Adder
0.379
316033AB2-134 GEN
Solar/Wind Harmer
3.986
315697AD1-025 GEN
Solar/Wind Harmer
2.5
316075AC2-137 C
Solar/Wind Harmer
0.333
966871AG1-558 GEN
Solar/Wind Harmer
0.367
316303AF2-085
50/50
7.054
971285AH1-108 GEN
50/50
1.707
972205AH1-687 GEN
50/50
6.277
316233AE1-074 FULL
Solar/Wind Harmer
0.961
971281AH1-106 GEN
Solar/Wind Harmer
5.803
971283AH1-107 GEN
Solar/Wind Harmer
5.803
971845AH1-439 GEN
Solar/Wind Harmer
7.405
970285AG2-188 GEN
Solar/Wind Harmer
12.021
971447AH1-217 GEN
Solar/Wind Harmer
4.697
316132AB2-190 GEN1
Solar/Wind Harmer
1.321
3143316POE
Solar/Wind Harmer
-0.05
971167AH1-042 GEN
Solar/Wind Harmer
11.94
316369SG1_INVT
Solar/Wind Harmer
2.209
316312AB1-027
Solar/Wind Harmer
0.411
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
270494AE1-108_GEN
Solar/Wind Harmer
3.015
315976AC1-164 GENA
Solar/Wind Harmer
12.09
316169AC1-164_GENC
Solar/Wind Harmer
10.444
315975AC1-164 GENB
Solar/Wind Harmer
0.358
315657AE1-056 GEN
Solar/Wind Harmer
4.288
946301AF1-294 GEN
Solar/Wind Harmer
2.872
961791AG1-021 GEN
Solar/Wind Harmer
1.401
972265AH1-717 GEN
Adder
7.73
3151201GRAVEL4
Adder
7.246
3151191GRAVEL3
Adder
7.154
3151211GRAVEL5
Adder
7.154
316315AB2-025 C
Solar/Wind Harmer
0.301
315814AE2-033 C
Solar/Wind Harmer
10.33
3143873LANEXA
Solar/Wind Harmer
-0.007
970683AG2-441 GEN
Solar/Wind Harmer
8.501
970681AG2-440 GEN
Solar/Wind Harmer
6.8
315833AF1-017_GEN
Solar/Wind Harmer
2.038
316349AD2-085 GEN
Solar/Wind Harmer
0.954
971445AH1-216 GEN
Solar/Wind Harmer
6.636
316311AC2-079 GEN
Solar/Wind Harmer
5.405
3144303KENBRDG
Solar/Wind Harmer
-0.008
971443AH1-215 GEN
Solar/Wind Harmer
2.068
316314AB2-024 C
Solar/Wind Harmer
0.887
315662AE1-191 GEN
Solar/Wind Harmer
1.241
315666AE1-190 GEN
Solar/Wind Harmer
0.31
316059AD1-063 C
Solar/Wind Harmer
0.232
957601AF2-054 GEN
Solar/Wind Harmer
0.301
3141873WAN 176
Solar/Wind Harmer
-0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.256
941031AE2-094 GEN
Solar/Wind Harmer
18.82
944011AF1-069 GEN
Solar/Wind Harmer
5.897
957831AF2-077 GEN
Solar/Wind Harmer
0.301
3138283WHITEMARSH
Solar/Wind Harmer
0.016
971967AH1-528 GEN
Solar/Wind Harmer
18.721
970673AG2-436 GEN
Solar/Wind Harmer
20.845
970673AG2-436 GEN
Solar/Wind Harmer
10.555
946281AF1-292 GEN
Solar/Wind Harmer
0.222
3152611GOSPORTB
Adder
1.118
3152621GOSPORTC
Adder
0.949
3152601GOSPORTA
Adder
0.875
3151081ELIZAR1
Adder
8.028
3151091ELIZAR2
Adder
7.888
316305AF2-043 C
Solar/Wind Harmer
0.296
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3138133OCRAN
Solar/Wind Harmer
-0.003
316087AB2-174 GEN
Solar/Wind Harmer
1.39
3146486SUNBURY
Solar/Wind Harmer
-0.01
3146486SUNBURY
Solar/Wind Harmer
-0.01
957871AF2-081 GEN
Solar/Wind Harmer
4.862
319010AE1-072 C
Solar/Wind Harmer
1.965
3146406KITTY HAWK
Solar/Wind Harmer
0.008
316239AB2-077_GEN
Solar/Wind Harmer
0.292
316238AB2-078_GEN
Solar/Wind Harmer
0.292
313526AB2-022
Solar/Wind Harmer
0.261
316321Z2-027
Solar/Wind Harmer
0.261
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3146396TANGLEW
Solar/Wind Harmer
0.178
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
965291AG1-394 GEN
Solar/Wind Harmer
0.85
315611Z1-036_GEN2
Solar/Wind Harmer
2.363
3137643SOCKMAN
Solar/Wind Harmer
-0.038
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3146043SEABORD
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.957
316318V4-068
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.009
972189AH1-679 GEN
Adder
1.322
315652AC1-086 GEN
Solar/Wind Harmer
9.306
3142946ENON
Solar/Wind Harmer
-0.004
970129AG2-093 GEN
Solar/Wind Harmer
7.393
3146926FARMVIL
Solar/Wind Harmer
-0.008
315778AD1-151 GEN
Solar/Wind Harmer
10.957
315813AE1-149 C
Solar/Wind Harmer
7.813
316473AC1-191 GEN
Solar/Wind Harmer
1.315
3142416OLDCHRC
Solar/Wind Harmer
1.229
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
942461AE2-259 GEN
Solar/Wind Harmer
1.815
970659AG2-427 GEN
Solar/Wind Harmer
1.122
316083AB2-161 GEN
Solar/Wind Harmer
1.918
970909AG2-566 GEN
Solar/Wind Harmer
1.109
961611AG1-000B GEN
Solar/Wind Harmer
2.451
970661AG2-428 GEN
Solar/Wind Harmer
2.166
3147133PAMPLIN
Solar/Wind Harmer
-0.036
971193AH1-056 GEN
Solar/Wind Harmer
7.146
963181AG1-167 GEN
Solar/Wind Harmer
1.051
3144293JTRSVLE
Adder
0.317
3151221GRAVEL6
Adder
7.238
3151171GRAVELC
Adder
1.393
3145336SMITFLD
Solar/Wind Harmer
-0.004
959311AF2-222 GEN
Solar/Wind Harmer
11.099
970257AG2-171 GEN
Solar/Wind Harmer
3.95
3141843SHACKLE
Adder
0.476
316203AE2-005 GEN
Solar/Wind Harmer
4.409
315785AD2-033 C
Solar/Wind Harmer
2.356
316382AG1-145 C
Solar/Wind Harmer
0.312
316280AD1-041 GEN
Solar/Wind Harmer
0.776
3141766HARMONY
Solar/Wind Harmer
0.913
3144216WINCHST
Adder
0.34
3144536CHRHLND
Solar/Wind Harmer
-0.002
316156AD2-030 GEN
Solar/Wind Harmer
0.269
3141873WAN 176
Solar/Wind Harmer
1.195
316365GEN2_N
Solar/Wind Harmer
0.679
964241AG1-285 GEN
Solar/Wind Harmer
7.839
3150921YORKTN3
Adder
2.229
3145273HOLLAND
Solar/Wind Harmer
-0.007
966621AG1-532 GEN
Solar/Wind Harmer
0.201
3144873MCLAUGH
Solar/Wind Harmer
0
3147043LAWRENC
Solar/Wind Harmer
-0.006
3151101ELIZAR3
Adder
8.131
316131AB2-060 GEN
Solar/Wind Harmer
1.059
3146456SLIGO L269
Solar/Wind Harmer
-0.01
971153AH1-033 GEN
Solar/Wind Harmer
1.185
316320Y1-086
Solar/Wind Harmer
0.568
313506AB2-031 GEN
Solar/Wind Harmer
0.777
316435W1029_GEN3
Solar/Wind Harmer
1.751
944581AF1-123 GEN
Solar/Wind Harmer
43.953
944601AF1-125 GEN
Solar/Wind Harmer
43.267
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3156081AA2-088 GEN
Solar/Wind Harmer
3.115
316478AD1-087 GEN
Solar/Wind Harmer
0.83
316486AD2-202 GEN
Solar/Wind Harmer
0.243
3146376EDENTON
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
-0.009
970917AG2-570 GEN
Solar/Wind Harmer
23.678
3150351NORNECKC2
Adder
0.761
316044AC1-158 PL1
Solar/Wind Helper
0.852
316450AC1-158 RIC
Solar/Wind Helper
0.227
3147666LOUISA
Solar/Wind Helper
0.27
316011AB1-132 GEN
Solar/Wind Harmer
1.976
3150351NORNECKC2
Adder
0.748
316045AC1-158 PL2
Solar/Wind Helper
2.728
3147666LOUISA
Solar/Wind Helper
0.47
316192AB2-158 GEN
Solar/Wind Helper
0.767
966871AG1-558 GEN
Solar/Wind Harmer
0.126
970657AG2-426 GEN
Solar/Wind Harmer
3.655
970657AG2-426 GEN
Solar/Wind Harmer
0.764
970301AG2-198 GEN
Solar/Wind Harmer
5.841
3147133PAMPLIN
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.009
971741AH1-377 GEN
Solar/Wind Harmer
13.177
958211AF2-115 GEN
Solar/Wind Harmer
1.751
963191AG1-168 GEN
Solar/Wind Harmer
1.051
3144293JTRSVLE
Adder
0.317
3144293JTRSVLE
Adder
0.267
3144356SAPONY
Solar/Wind Harmer
0.389
316236AE1-162_GEN
Solar/Wind Harmer
0.322
316034AC1-036 C
Solar/Wind Harmer
0.195
970323AG2-213 GEN
Solar/Wind Harmer
5.267
971775AH1-396 GEN
Solar/Wind Harmer
0.75
316441AF1-014 GEN
Solar/Wind Harmer
0.705
315821AE2-092 GEN
Solar/Wind Harmer
2.144
970933AG2-581 GEN
Solar/Wind Harmer
9.321
316036AC1-147 C
Solar/Wind Harmer
0.266
3150991CHESPKB
Adder
0.92
3150991CHESPKB
Adder
0.898
972185AH1-677 GEN
Adder
4.927
315742AE1-103 GEN
Solar/Wind Harmer
1.029
970099AG2-077 GEN
Solar/Wind Harmer
12.294
316316AC1-027 C
Solar/Wind Harmer
0.301
3142956BIRDNECK
Solar/Wind Harmer
0.526
972187AH1-678 GEN
Adder
2.481
313527AB2-043 GEN
Solar/Wind Harmer
1.585
316185AD1-033 GEN
Solar/Wind Harmer
1.029
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.023
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.656
316018AA1-139 ULT2
Solar/Wind Harmer
0.833
316017AA1-139 ULT1
Solar/Wind Harmer
0.787
3137176SLIGO L2192
Solar/Wind Harmer
-0.038
3146456SLIGO L269
Solar/Wind Harmer
1.148
3130086AYDLETT
Solar/Wind Harmer
-0.039
3146386ELIZ CT
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
1.349
316431W1029_GEN1
Solar/Wind Harmer
1.751
316433W1029_GEN2
Solar/Wind Harmer
1.751
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3146376EDENTON
Solar/Wind Harmer
0.282
3146376EDENTON
Solar/Wind Harmer
0.282
3145893MURPHYS
Solar/Wind Harmer
0.264
3145893MURPHYS
Solar/Wind Harmer
-0.017
3150341NORNECKC1
Adder
0.786
3150341NORNECKC1
Adder
0.779
316447AC1-158 HLD
Solar/Wind Helper
1.875
LAGNLTFEXP_LAGN->PJM
CLTF
3.549
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.514
TVALTFEXP_TVA->PJM
CLTF
1.79
CPLELTFEXP_CPLE->PJM
CLTF
4.781
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.949
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.546
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.162
MECLTFEXP_MEC->PJM
CLTF
1.768
SIGELTFEXP_SIGE->PJM
CLTF
0.054
NYPJM->LTFIMP_NY
CLTF
1.094
LGEELTFEXP_LGEE->PJM
CLTF
0.661
WECLTFEXP_WEC->PJM
CLTF
0.333

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.56 %
Rating:1265.1 MVA
Rating Type:C
MVA to Mitigate:1563.15
MW Contribution:53.03
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
7.071
971285AH1-108 GEN
50/50
1.718
972205AH1-687 GEN
50/50
6.266
316233AE1-074 FULL
Solar/Wind Harmer
0.964
971281AH1-106 GEN
Solar/Wind Harmer
5.823
971283AH1-107 GEN
Solar/Wind Harmer
5.823
971845AH1-439 GEN
Solar/Wind Harmer
7.348
970285AG2-188 GEN
Solar/Wind Harmer
11.918
316132AB2-190 GEN1
Solar/Wind Harmer
1.338
971447AH1-217 GEN
Solar/Wind Harmer
4.689
3143316POE
Solar/Wind Harmer
-0.052
971167AH1-042 GEN
Solar/Wind Harmer
12.093
316369SG1_INVT
Solar/Wind Harmer
2.235
316312AB1-027
Solar/Wind Harmer
0.416
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
315976AC1-164 GENA
Solar/Wind Harmer
12.24
316169AC1-164_GENC
Solar/Wind Harmer
10.574
315975AC1-164 GENB
Solar/Wind Harmer
0.362
270494AE1-108_GEN
Solar/Wind Harmer
3.007
316315AB2-025 C
Solar/Wind Harmer
0.31
315814AE2-033 C
Solar/Wind Harmer
10.64
972265AH1-717 GEN
Adder
7.808
3151201GRAVEL4
Adder
7.319
3151191GRAVEL3
Adder
7.227
3151211GRAVEL5
Adder
7.227
315657AE1-056 GEN
Solar/Wind Harmer
4.225
3143873LANEXA
Solar/Wind Harmer
-0.007
946301AF1-294 GEN
Solar/Wind Harmer
2.828
961791AG1-021 GEN
Solar/Wind Harmer
1.38
315833AF1-017_GEN
Solar/Wind Harmer
2.058
316349AD2-085 GEN
Solar/Wind Harmer
0.964
971445AH1-216 GEN
Solar/Wind Harmer
6.695
316311AC2-079 GEN
Solar/Wind Harmer
5.457
970683AG2-441 GEN
Solar/Wind Harmer
8.368
970681AG2-440 GEN
Solar/Wind Harmer
6.695
316314AB2-024 C
Solar/Wind Harmer
0.899
315662AE1-191 GEN
Solar/Wind Harmer
1.258
315666AE1-190 GEN
Solar/Wind Harmer
0.314
316059AD1-063 C
Solar/Wind Harmer
0.235
3144303KENBRDG
Solar/Wind Harmer
-0.008
971443AH1-215 GEN
Solar/Wind Harmer
2.035
957601AF2-054 GEN
Solar/Wind Harmer
0.305
3141873WAN 176
Solar/Wind Harmer
-0.002
957831AF2-077 GEN
Solar/Wind Harmer
0.305
3138283WHITEMARSH
Solar/Wind Harmer
0.016
315835AF2-110_GEN
Solar/Wind Harmer
1.263
946281AF1-292 GEN
Solar/Wind Harmer
0.224
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3152611GOSPORTB
Adder
1.125
3152621GOSPORTC
Adder
0.955
3152601GOSPORTA
Adder
0.881
3151081ELIZAR1
Adder
8.079
3151091ELIZAR2
Adder
7.939
3138133OCRAN
Solar/Wind Harmer
-0.003
316305AF2-043 C
Solar/Wind Harmer
0.297
316087AB2-174 GEN
Solar/Wind Harmer
1.398
957871AF2-081 GEN
Solar/Wind Harmer
4.888
3146486SUNBURY
Solar/Wind Harmer
-0.01
3146486SUNBURY
Solar/Wind Harmer
-0.01
319010AE1-072 C
Solar/Wind Harmer
1.975
3146406KITTY HAWK
Solar/Wind Harmer
0.008
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
313526AB2-022
Solar/Wind Harmer
0.262
316321Z2-027
Solar/Wind Harmer
0.262
3146396TANGLEW
Solar/Wind Harmer
0.179
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
2.371
965291AG1-394 GEN
Solar/Wind Harmer
0.851
3137643SOCKMAN
Solar/Wind Harmer
-0.038
941031AE2-094 GEN
Solar/Wind Harmer
17.899
944011AF1-069 GEN
Solar/Wind Harmer
5.608
3130156CHOWAN
Solar/Wind Harmer
-0.01
3130156CHOWAN
Solar/Wind Harmer
-0.01
316239AB2-077_GEN
Solar/Wind Harmer
0.287
316238AB2-078_GEN
Solar/Wind Harmer
0.287
315652AC1-086 GEN
Solar/Wind Harmer
10.692
971967AH1-528 GEN
Solar/Wind Harmer
17.858
3146043SEABORD
Solar/Wind Harmer
-0.009
316318V4-068
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.958
962981AG1-147 GEN
Solar/Wind Harmer
4.144
972189AH1-679 GEN
Adder
1.34
970673AG2-436 GEN
Solar/Wind Harmer
16.786
970673AG2-436 GEN
Solar/Wind Harmer
8.499
3150861SPRUNCD
50/50
1.05
3143096IRON208
50/50
0.691
3143096IRON208
50/50
0.677
3151921BEARGRDN G2
50/50
1.285
316313AB2-026
Solar/Wind Harmer
0.891
316258AE1-075 C
Solar/Wind Harmer
0.802
316405AF2-144 C
Solar/Wind Harmer
0.846
3143336POWHATN
Solar/Wind Harmer
3.333
315839AE2-212 C
Solar/Wind Harmer
0.428
965281AG1-393 GEN
Solar/Wind Harmer
1.772
970133AG2-095 GEN
Solar/Wind Harmer
1.574
3146776BUCKING
Solar/Wind Harmer
-0.005
970221AG2-151 GEN
Solar/Wind Harmer
8.699
970293AG2-193 GEN
Solar/Wind Harmer
1.728
3142946ENON
Solar/Wind Harmer
-0.004
970129AG2-093 GEN
Solar/Wind Harmer
7.488
315778AD1-151 GEN
Solar/Wind Harmer
11.091
315813AE1-149 C
Solar/Wind Harmer
7.967
3146926FARMVIL
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
1.33
3142416OLDCHRC
Solar/Wind Harmer
1.243
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
970659AG2-427 GEN
Solar/Wind Harmer
1.141
316083AB2-161 GEN
Solar/Wind Harmer
1.949
942461AE2-259 GEN
Solar/Wind Harmer
1.79
961611AG1-000B GEN
Solar/Wind Harmer
2.478
970661AG2-428 GEN
Solar/Wind Harmer
2.197
970909AG2-566 GEN
Solar/Wind Harmer
1.087
3151221GRAVEL6
Adder
7.311
3151171GRAVELC
Adder
1.407
3147133PAMPLIN
Solar/Wind Harmer
-0.035
971193AH1-056 GEN
Solar/Wind Harmer
7.041
963181AG1-167 GEN
Solar/Wind Harmer
1.035
3144293JTRSVLE
Adder
0.313
3145336SMITFLD
Solar/Wind Harmer
-0.004
3141843SHACKLE
Adder
0.482
316203AE2-005 GEN
Solar/Wind Harmer
4.468
316382AG1-145 C
Solar/Wind Harmer
0.316
959311AF2-222 GEN
Solar/Wind Harmer
10.922
316280AD1-041 GEN
Solar/Wind Harmer
0.786
3141766HARMONY
Solar/Wind Harmer
0.925
970257AG2-171 GEN
Solar/Wind Harmer
3.886
3144216WINCHST
Adder
0.344
315785AD2-033 C
Solar/Wind Harmer
2.318
316365GEN2_N
Solar/Wind Harmer
0.689
316156AD2-030 GEN
Solar/Wind Harmer
0.272
3141873WAN 176
Solar/Wind Harmer
1.211
3144536CHRHLND
Solar/Wind Harmer
-0.002
3150921YORKTN3
Adder
2.258
966621AG1-532 GEN
Solar/Wind Harmer
0.203
3145273HOLLAND
Solar/Wind Harmer
-0.007
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
8.182
3147043LAWRENC
Solar/Wind Harmer
-0.006
964241AG1-285 GEN
Solar/Wind Harmer
7.705
3146456SLIGO L269
Solar/Wind Harmer
-0.01
971153AH1-033 GEN
Solar/Wind Harmer
1.191
316320Y1-086
Solar/Wind Harmer
0.57
944581AF1-123 GEN
Solar/Wind Harmer
44.219
944601AF1-125 GEN
Solar/Wind Harmer
43.529
313506AB2-031 GEN
Solar/Wind Harmer
0.781
316435W1029_GEN3
Solar/Wind Harmer
1.758
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
316131AB2-060 GEN
Solar/Wind Harmer
1.04
3156081AA2-088 GEN
Solar/Wind Harmer
3.122
3146376EDENTON
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
-0.009
962971AG1-146 GEN
Solar/Wind Harmer
1.776
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
957521AF2-046 GEN
Solar/Wind Harmer
7.444
961681AG1-008 GEN
Solar/Wind Harmer
7.444
3150351NORNECKC2
Adder
0.772
316044AC1-158 PL1
Solar/Wind Helper
0.845
316450AC1-158 RIC
Solar/Wind Helper
0.225
3147666LOUISA
Solar/Wind Helper
0.268
970119AG2-088 GEN
50/50
53.032
3150851SPRUNCC
50/50
1.05
3143096IRON208
50/50
0.691
3151931BEARGRDN S1
50/50
1.658
3151911BEARGRDN G1
50/50
1.285
3143226MDLTHAN
Solar/Wind Harmer
-0.045
3143526WINTERP
Solar/Wind Harmer
-0.185
3143336POWHATN
Solar/Wind Harmer
3.921
316336AC2-165 C
Solar/Wind Harmer
5.212
970937AG2-583 GEN
Solar/Wind Harmer
15.928
3142543TWELFTH
Solar/Wind Harmer
-0.002
972003AH1-546 GEN
Solar/Wind Harmer
7.6
944631AF1-128 GEN
Adder
61.666
315671AE2-027_GEN
Solar/Wind Harmer
10.745
316322AB2-045
Solar/Wind Harmer
0.469
3146776BUCKING
Solar/Wind Harmer
-0.006
971377AH1-170 GEN
Solar/Wind Harmer
1.74
3147623JAMES R
Solar/Wind Harmer
0.215
970129AG2-093 GEN
Solar/Wind Harmer
3.033
316458AB2-190 GEN2
Solar/Wind Harmer
1.338
971069AG2-661 GEN
Solar/Wind Harmer
2.026
3146926FARMVIL
Solar/Wind Harmer
-0.007
3142416OLDCHRC
Solar/Wind Harmer
-0.032
3142416OLDCHRC
Solar/Wind Harmer
-0.012
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971647AH1-324 GEN
Solar/Wind Harmer
6.07
970659AG2-427 GEN
Solar/Wind Harmer
6.44
316381AD1-082 GEN
Solar/Wind Harmer
1.101
961611AG1-000B GEN
Solar/Wind Harmer
5.807
970661AG2-428 GEN
Solar/Wind Harmer
12.397
3151171GRAVELC
Adder
1.07
963171AG1-166 GEN
Solar/Wind Harmer
1.38
971563AH1-280 GEN
Solar/Wind Harmer
1.38
3144293JTRSVLE
Adder
0.313
3145336SMITFLD
Solar/Wind Harmer
-0.043
970685AG2-442 GEN
Solar/Wind Harmer
9.372
971777AH1-397 GEN
Solar/Wind Harmer
1.247
3141843SHACKLE
Adder
0.482
316159AE1-175 C
Solar/Wind Harmer
0.282
3141766HARMONY
Solar/Wind Harmer
-0.002
316023GEN1_S
Solar/Wind Harmer
0.689
3138126ROCKLANDING
Solar/Wind Harmer
0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.937
316072AD1-144
Solar/Wind Harmer
0.204
971317AH1-138 GEN
Solar/Wind Harmer
1.259
960081AF2-299 GEN
Solar/Wind Harmer
1.124
316375AC2-012 GEN
Solar/Wind Harmer
3.436
3150981CHESPKA
Adder
1.103
962491AG1-098 GEN
Solar/Wind Harmer
6.636
971795AH1-408 GEN
Solar/Wind Harmer
7.428
3138133OCRAN
Solar/Wind Harmer
-0.006
3147043LAWRENC
Adder
0.794
316246AF1-032 C
Solar/Wind Harmer
0.2
315693AD1-088 GEN
Solar/Wind Harmer
4.92
316388AE2-253 GEN
Solar/Wind Harmer
0.66
3146456SLIGO L269
Solar/Wind Harmer
-0.01
944591AF1-124 GEN
Solar/Wind Harmer
44.378
939411AE1-173 GEN
Solar/Wind Harmer
48.513
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.01
940641AE2-051 GEN
Solar/Wind Harmer
9.075
315800Z1-036_GEN1
Solar/Wind Harmer
2.371
3130156CHOWAN
Solar/Wind Harmer
-0.01
316237AB2-079_GEN
Solar/Wind Harmer
0.287
316011AB1-132 GEN
Solar/Wind Harmer
1.988
962571AG1-106 GEN
Solar/Wind Harmer
1.366
3145893MURPHYS
Solar/Wind Harmer
-0.038
3145893MURPHYS
Solar/Wind Harmer
0.281
957481AF2-042 GEN
Solar/Wind Harmer
29.606
3150351NORNECKC2
Adder
0.759
316045AC1-158 PL2
Solar/Wind Helper
2.706
3147666LOUISA
Solar/Wind Helper
0.466
316192AB2-158 GEN
Solar/Wind Helper
0.76
3142366NRTHEST
50/50
0.486
3150691DARBY 3
50/50
10.231
3150701DARBY 4
50/50
10.207
3150681DARBY 2
50/50
10.195
3150671DARBY 1
50/50
10.183
944641AF1-129 GEN
50/50
67.565
971223AH1-071 GEN
Solar/Wind Harmer
5.586
3143526WINTERP
Solar/Wind Harmer
-0.185
316240AF1-291 C
Solar/Wind Harmer
0.446
3146776BUCKING
Solar/Wind Harmer
-0.055
3146776BUCKING
Solar/Wind Harmer
-0.005
971489AH1-241 GEN
Solar/Wind Harmer
8.259
3142946ENON
Solar/Wind Harmer
-0.001
3142296MT RD221
Adder
0.383
316033AB2-134 GEN
Solar/Wind Harmer
4.034
315697AD1-025 GEN
Solar/Wind Harmer
2.53
316075AC2-137 C
Solar/Wind Harmer
0.337
966871AG1-558 GEN
Solar/Wind Harmer
0.371
966871AG1-558 GEN
Solar/Wind Harmer
0.127
970657AG2-426 GEN
Solar/Wind Harmer
3.712
970657AG2-426 GEN
Solar/Wind Harmer
0.776
3144356SAPONY
Solar/Wind Harmer
0.401
970301AG2-198 GEN
Solar/Wind Harmer
5.724
3147133PAMPLIN
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.009
971741AH1-377 GEN
Solar/Wind Harmer
12.88
958211AF2-115 GEN
Solar/Wind Harmer
1.725
963191AG1-168 GEN
Solar/Wind Harmer
1.035
3144293JTRSVLE
Adder
0.313
3144293JTRSVLE
Adder
0.263
316236AE1-162_GEN
Solar/Wind Harmer
0.325
316441AF1-014 GEN
Solar/Wind Harmer
0.714
316034AC1-036 C
Solar/Wind Harmer
0.192
970323AG2-213 GEN
Solar/Wind Harmer
5.182
971775AH1-396 GEN
Solar/Wind Harmer
0.738
315821AE2-092 GEN
Solar/Wind Harmer
2.142
316036AC1-147 C
Solar/Wind Harmer
0.268
3150991CHESPKB
Adder
0.926
3150991CHESPKB
Adder
0.903
315742AE1-103 GEN
Solar/Wind Harmer
1.033
316316AC1-027 C
Solar/Wind Harmer
0.303
3142956BIRDNECK
Solar/Wind Harmer
0.529
316185AD1-033 GEN
Solar/Wind Harmer
1.035
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.023
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.66
316018AA1-139 ULT2
Solar/Wind Harmer
0.838
316017AA1-139 ULT1
Solar/Wind Harmer
0.791
3137176SLIGO L2192
Solar/Wind Harmer
-0.039
3146456SLIGO L269
Solar/Wind Harmer
1.154
3130086AYDLETT
Solar/Wind Harmer
-0.039
3146386ELIZ CT
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
1.355
316431W1029_GEN1
Solar/Wind Harmer
1.758
316433W1029_GEN2
Solar/Wind Harmer
1.758
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
313527AB2-043 GEN
Solar/Wind Harmer
1.557
3146376EDENTON
Solar/Wind Harmer
0.283
3146376EDENTON
Solar/Wind Harmer
0.283
970933AG2-581 GEN
Solar/Wind Harmer
8.917
3145893MURPHYS
Solar/Wind Harmer
0.265
3145893MURPHYS
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
11.843
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
972185AH1-677 GEN
Adder
4.694
972187AH1-678 GEN
Adder
2.365
3150341NORNECKC1
Adder
0.798
3150341NORNECKC1
Adder
0.791
316447AC1-158 HLD
Solar/Wind Helper
1.861
LAGNLTFEXP_LAGN->PJM
CLTF
3.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.237
TVALTFEXP_TVA->PJM
CLTF
1.744
CPLELTFEXP_CPLE->PJM
CLTF
4.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.458
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.232
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.004
MECLTFEXP_MEC->PJM
CLTF
1.722
SIGELTFEXP_SIGE->PJM
CLTF
0.053
NYPJM->LTFIMP_NY
CLTF
1.079
LGEELTFEXP_LGEE->PJM
CLTF
0.644
WECLTFEXP_WEC->PJM
CLTF
0.324

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.13 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1291.31
MW Contribution:15.41
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.39 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1475.57
MW Contribution:15.41
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.39 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1475.54
MW Contribution:15.41
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.94 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1415.27
MW Contribution:18.19
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.94 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1415.27
MW Contribution:18.19
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.1 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:940.38
MW Contribution:10.81
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970535AG2-341 GEN
50/50
2.556
3152661PLYWOOD A
50/50
0.283
971489AH1-241 GEN
Solar/Wind Harmer
21.838
3146776BUCKING
Solar/Wind Harmer
1.539
3146776BUCKING
Solar/Wind Harmer
0.125
970301AG2-198 GEN
Solar/Wind Harmer
11.486
971741AH1-377 GEN
Solar/Wind Harmer
25.037
3147133PAMPLIN
Solar/Wind Harmer
0.249
3147133PAMPLIN
Solar/Wind Harmer
0.199
315821AE2-092 GEN
Solar/Wind Harmer
0.015
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
316034AC1-036 C
Solar/Wind Harmer
0.015
970323AG2-213 GEN
Solar/Wind Harmer
8.565
971775AH1-396 GEN
Solar/Wind Harmer
0.321
970933AG2-581 GEN
Solar/Wind Harmer
14.707
970099AG2-077 GEN
Solar/Wind Harmer
19.291
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
6.748
964791AG1-342 GEN
Solar/Wind Harmer
2.636
3146843MT LREL
Solar/Wind Harmer
0.137
3146843MT LREL
Solar/Wind Harmer
0.137
939181AE1-148 GEN
Solar/Wind Harmer
6.508
971223AH1-071 GEN
Solar/Wind Harmer
0.865
942751AE2-291 GEN
Solar/Wind Harmer
4.374
316222AC1-221 GEN
Solar/Wind Harmer
0.309
316181AB2-040 GEN
Solar/Wind Harmer
0.1
3145593CAROLNA
Solar/Wind Harmer
0.067
3145593CAROLNA
Solar/Wind Harmer
0.067
966811AG1-552 GEN
Solar/Wind Harmer
0.729
3145593CAROLNA
Solar/Wind Harmer
0.084
3143526WINTERP
Solar/Wind Harmer
0.343
3145783HORNRTN
Solar/Wind Harmer
1.168
3145783HORNRTN
Solar/Wind Harmer
0.934
3145783HORNRTN
Solar/Wind Harmer
0.292
3145783HORNRTN
Solar/Wind Harmer
0.117
316426AA2-053 GEN
Solar/Wind Harmer
0.216
316274AC1-208 GEN
Solar/Wind Harmer
0.297
966001AG1-469 GEN
Solar/Wind Helper
0.193
3151931BEARGRDN S1
50/50
5.52
3151911BEARGRDN G1
50/50
4.277
3144293JTRSVLE
50/50
0.801
3151531CLOVER1
50/50
3.66
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3147043LAWRENC
50/50
0.93
970119AG2-088 GEN
50/50
10.808
3151261ROARAP2
50/50
0.084
972003AH1-546 GEN
Solar/Wind Harmer
18.967
971377AH1-170 GEN
Solar/Wind Harmer
4.368
3147623JAMES R
Solar/Wind Harmer
0.949
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.154
970937AG2-583 GEN
Solar/Wind Harmer
22.935
3146926FARMVIL
Solar/Wind Harmer
0.194
316336AC2-165 C
Solar/Wind Harmer
0.011
963171AG1-166 GEN
Solar/Wind Harmer
1.265
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3143336POWHATN
Solar/Wind Harmer
4.133
970685AG2-442 GEN
Solar/Wind Harmer
16.387
962491AG1-098 GEN
Solar/Wind Harmer
11.396
315693AD1-088 GEN
Solar/Wind Harmer
9.404
957481AF2-042 GEN
Solar/Wind Harmer
48.226
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.005
970401AG2-262 GEN
Solar/Wind Harmer
0.806
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.784
316129AC1-054 GEN
Solar/Wind Harmer
0.408
971795AH1-408 GEN
Solar/Wind Harmer
5.893
3143226MDLTHAN
Solar/Wind Harmer
0.081
960081AF2-299 GEN
Solar/Wind Harmer
0.671
3143526WINTERP
Solar/Wind Harmer
0.343
3145783HORNRTN
Solar/Wind Harmer
0.066
316190AA2-174 GEN
Solar/Wind Harmer
0
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.79
3147666LOUISA
Solar/Wind Helper
0.453
3151921BEARGRDN G2
50/50
4.277
3144293JTRSVLE
50/50
0.801
970413AG2-270 GEN
50/50
15.972
3151591KERR 2
50/50
0.27
966251AG1-494 GEN
50/50
1.325
3151261ROARAP2
50/50
0.082
970221AG2-151 GEN
Solar/Wind Harmer
21.838
3146776BUCKING
Solar/Wind Harmer
0.139
3146926FARMVIL
Solar/Wind Harmer
0.194
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.872
3147133PAMPLIN
Solar/Wind Harmer
0.783
971193AH1-056 GEN
Solar/Wind Harmer
15.186
963181AG1-167 GEN
Solar/Wind Harmer
0.948
316313AB2-026
Solar/Wind Harmer
0.147
316258AE1-075 C
Solar/Wind Harmer
0.175
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.513
959311AF2-222 GEN
Solar/Wind Harmer
18.323
970257AG2-171 GEN
Solar/Wind Harmer
6.424
315785AD2-033 C
Solar/Wind Harmer
1.572
964241AG1-285 GEN
Solar/Wind Harmer
11.577
316478AD1-087 GEN
Solar/Wind Harmer
0.596
316486AD2-202 GEN
Solar/Wind Harmer
0.175
316131AB2-060 GEN
Solar/Wind Harmer
0.509
958131AF2-107 GEN
Solar/Wind Harmer
3.719
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.197
971683AH1-343 GEN
Solar/Wind Harmer
3.989
3147043LAWRENC
Solar/Wind Harmer
0.058
316283AC2-100 C
Solar/Wind Harmer
0.143
313506AB2-031 GEN
Solar/Wind Harmer
0.212
316499AE2-029_GEN
Solar/Wind Helper
0.498
3132273ORANGE
Solar/Wind Helper
0.027
3148013FISHERV
Solar/Wind Helper
0.128
315616AA1-038_C
Solar/Wind Helper
0.526
3147666LOUISA
Solar/Wind Helper
0.261
972205AH1-687 GEN
50/50
20.861
3151541CLOVER2
50/50
3.643
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
316303AF2-085
50/50
1.441
3151281ROARAP4
50/50
0.081
3151281ROARAP4
50/50
0.076
971845AH1-439 GEN
Solar/Wind Harmer
17.22
971447AH1-217 GEN
Solar/Wind Harmer
11.445
970285AG2-188 GEN
Solar/Wind Harmer
29.262
270494AE1-108_GEN
Solar/Wind Harmer
3.857
315657AE1-056 GEN
Solar/Wind Harmer
8.602
946301AF1-294 GEN
Solar/Wind Harmer
4.679
961791AG1-021 GEN
Solar/Wind Harmer
2.276
970683AG2-441 GEN
Solar/Wind Harmer
14.631
970681AG2-440 GEN
Solar/Wind Harmer
11.705
3144303KENBRDG
Solar/Wind Harmer
0.16
971443AH1-215 GEN
Solar/Wind Harmer
3.345
971967AH1-528 GEN
Solar/Wind Harmer
29.413
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.334
3147173SINAI
Solar/Wind Harmer
0.122
3147243WELCO
Solar/Wind Harmer
0.076
970831AG2-522 GEN
Solar/Wind Harmer
4.457
970865AG2-541 GEN
Solar/Wind Harmer
3.533
316123AC1-075 GEN
Solar/Wind Harmer
0.121
970165AG2-112 GEN
Solar/Wind Harmer
0.72
970163AG2-111 GEN
Solar/Wind Harmer
0.686
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.271
316233AE1-074 FULL
Solar/Wind Harmer
0.053
971281AH1-106 GEN
Solar/Wind Harmer
0.915
971283AH1-107 GEN
Solar/Wind Harmer
0.915
315607AA1-063A GEN
Solar/Wind Harmer
0.125
3146043SEABORD
Solar/Wind Harmer
0.06
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.073
3148463FAIRFLD
Solar/Wind Helper
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
1.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.134
TVALTFEXP_TVA->PJM
CLTF
0.807
CPLELTFEXP_CPLE->PJM
CLTF
3.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.173
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.591
MECLTFEXP_MEC->PJM
CLTF
0.444
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.484
LGEELTFEXP_LGEE->PJM
CLTF
0.11
WECLTFEXP_WEC->PJM
CLTF
0.05

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2066-282_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2066-282_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.44 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:861.07
MW Contribution:15.08
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.41
3151911BEARGRDN G1
50/50
4.192
3144293JTRSVLE
50/50
0.653
970119AG2-088 GEN
50/50
15.082
972003AH1-546 GEN
Solar/Wind Harmer
24.312
971377AH1-170 GEN
Solar/Wind Harmer
5.633
3147623JAMES R
Solar/Wind Harmer
0.697
970937AG2-583 GEN
Solar/Wind Harmer
30.216
316322AB2-045
Solar/Wind Harmer
1.35
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.534
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.308
963171AG1-166 GEN
Solar/Wind Harmer
2.715
971563AH1-280 GEN
Solar/Wind Harmer
2.715
970685AG2-442 GEN
Solar/Wind Harmer
17.259
962491AG1-098 GEN
Solar/Wind Harmer
8.747
3143226MDLTHAN
Solar/Wind Harmer
-0.013
316237AB2-079_GEN
Solar/Wind Harmer
0.378
315693AD1-088 GEN
Solar/Wind Harmer
6.258
970401AG2-262 GEN
Solar/Wind Harmer
0.669
957481AF2-042 GEN
Solar/Wind Harmer
30.813
315687AD1-152 GEN
Solar/Wind Harmer
1.088
971065AG2-659 GEN
Solar/Wind Harmer
4.397
972205AH1-687 GEN
50/50
20.447
316303AF2-085
50/50
2.011
971447AH1-217 GEN
Solar/Wind Harmer
14.757
971845AH1-439 GEN
Solar/Wind Harmer
20.937
970285AG2-188 GEN
Solar/Wind Harmer
33.263
270494AE1-108_GEN
Solar/Wind Harmer
9.168
315657AE1-056 GEN
Solar/Wind Harmer
8.668
946301AF1-294 GEN
Solar/Wind Harmer
5.566
961791AG1-021 GEN
Solar/Wind Harmer
2.715
970683AG2-441 GEN
Solar/Wind Harmer
15.41
970681AG2-440 GEN
Solar/Wind Harmer
12.328
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.43
316239AB2-077_GEN
Solar/Wind Harmer
0.378
316238AB2-078_GEN
Solar/Wind Harmer
0.378
316118AC1-105 GEN
Solar/Wind Harmer
0.639
970831AG2-522 GEN
Solar/Wind Harmer
4.187
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.88
946281AF1-292 GEN
Solar/Wind Harmer
0.152
971967AH1-528 GEN
Solar/Wind Harmer
12.673
316087AB2-174 GEN
Solar/Wind Harmer
0.946
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.118
3151921BEARGRDN G2
50/50
4.192
3144293JTRSVLE
50/50
0.653
970221AG2-151 GEN
Solar/Wind Harmer
28.166
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.752
316258AE1-075 C
Solar/Wind Harmer
0.677
316405AF2-144 C
Solar/Wind Harmer
0.714
3143336POWHATN
Solar/Wind Harmer
2.812
942461AE2-259 GEN
Solar/Wind Harmer
4.067
970909AG2-566 GEN
Solar/Wind Harmer
2.224
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.446
963181AG1-167 GEN
Solar/Wind Harmer
2.036
959311AF2-222 GEN
Solar/Wind Harmer
19.01
970257AG2-171 GEN
Solar/Wind Harmer
6.601
315785AD2-033 C
Solar/Wind Harmer
3.8
964241AG1-285 GEN
Solar/Wind Harmer
11.356
958131AF2-107 GEN
Solar/Wind Harmer
4.67
316131AB2-060 GEN
Solar/Wind Harmer
1.422
316478AD1-087 GEN
Solar/Wind Harmer
0.862
316486AD2-202 GEN
Solar/Wind Harmer
0.252
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.252
960061AF2-297 GEN
Solar/Wind Harmer
4.181
971683AH1-343 GEN
Solar/Wind Harmer
3.236
966621AG1-532 GEN
Solar/Wind Harmer
0.138
313506AB2-031 GEN
Solar/Wind Harmer
0.528
316499AE2-029_GEN
Solar/Wind Helper
0.5
3148013FISHERV
Solar/Wind Helper
0.13
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.535
3144293JTRSVLE
50/50
0.653
3144293JTRSVLE
50/50
0.55
971489AH1-241 GEN
Solar/Wind Harmer
26.74
3146776BUCKING
Solar/Wind Harmer
-0.16
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.489
970301AG2-198 GEN
Solar/Wind Harmer
11.714
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.394
963191AG1-168 GEN
Solar/Wind Harmer
2.036
971741AH1-377 GEN
Solar/Wind Harmer
24.324
316034AC1-036 C
Solar/Wind Harmer
0.327
970323AG2-213 GEN
Solar/Wind Harmer
8.802
971775AH1-396 GEN
Solar/Wind Harmer
1.253
313527AB2-043 GEN
Solar/Wind Harmer
2.088
971223AH1-071 GEN
Solar/Wind Harmer
1.589
962561AG1-105 GEN
Solar/Wind Harmer
5.986
939181AE1-148 GEN
Solar/Wind Harmer
5.822
964791AG1-342 GEN
Solar/Wind Harmer
2.188
3146843MT LREL
Solar/Wind Harmer
-0.01
3146843MT LREL
Solar/Wind Harmer
-0.01
970099AG2-077 GEN
Solar/Wind Harmer
12.325
970933AG2-581 GEN
Solar/Wind Harmer
7.23
316181AB2-040 GEN
Solar/Wind Harmer
0.916
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.712
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.187
3147043LAWRENC
Adder
0.694
316129AC1-054 GEN
Solar/Wind Harmer
0.753
971795AH1-408 GEN
Solar/Wind Harmer
6.032
316003AC1-222 GEN
Solar/Wind Harmer
0.772
960081AF2-299 GEN
Solar/Wind Harmer
0.762
3147983MERCK5
Solar/Wind Helper
0.055
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.02
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.044
LAGNLTFEXP_LAGN->PJM
CLTF
1.141
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.807
TVALTFEXP_TVA->PJM
CLTF
0.557
CPLELTFEXP_CPLE->PJM
CLTF
2.977
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.39
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.714
MECLTFEXP_MEC->PJM
CLTF
0.159
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.385

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 219-282_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 219-282_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.1 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:858.35
MW Contribution:15.08
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.446
316303AF2-085
50/50
2.01
971447AH1-217 GEN
Solar/Wind Harmer
14.756
971845AH1-439 GEN
Solar/Wind Harmer
20.936
970285AG2-188 GEN
Solar/Wind Harmer
33.261
270494AE1-108_GEN
Solar/Wind Harmer
9.167
315657AE1-056 GEN
Solar/Wind Harmer
8.667
946301AF1-294 GEN
Solar/Wind Harmer
5.565
961791AG1-021 GEN
Solar/Wind Harmer
2.715
970683AG2-441 GEN
Solar/Wind Harmer
15.407
970681AG2-440 GEN
Solar/Wind Harmer
12.326
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.429
316233AE1-074 FULL
Solar/Wind Harmer
0.342
971281AH1-106 GEN
Solar/Wind Harmer
2.065
971283AH1-107 GEN
Solar/Wind Harmer
2.065
316239AB2-077_GEN
Solar/Wind Harmer
0.378
316238AB2-078_GEN
Solar/Wind Harmer
0.378
316118AC1-105 GEN
Solar/Wind Harmer
0.639
970831AG2-522 GEN
Solar/Wind Harmer
4.186
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.879
946281AF1-292 GEN
Solar/Wind Harmer
0.152
971967AH1-528 GEN
Solar/Wind Harmer
12.668
316087AB2-174 GEN
Solar/Wind Harmer
0.946
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.118
3151921BEARGRDN G2
50/50
4.192
3144293JTRSVLE
50/50
0.653
970221AG2-151 GEN
Solar/Wind Harmer
28.165
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.752
316258AE1-075 C
Solar/Wind Harmer
0.677
316405AF2-144 C
Solar/Wind Harmer
0.714
3143336POWHATN
Solar/Wind Harmer
2.811
942461AE2-259 GEN
Solar/Wind Harmer
4.067
970909AG2-566 GEN
Solar/Wind Harmer
2.224
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.444
963181AG1-167 GEN
Solar/Wind Harmer
2.036
959311AF2-222 GEN
Solar/Wind Harmer
19.007
970257AG2-171 GEN
Solar/Wind Harmer
6.6
315785AD2-033 C
Solar/Wind Harmer
3.799
3144293JTRSVLE
50/50
0.653
3144293JTRSVLE
50/50
0.55
971489AH1-241 GEN
Solar/Wind Harmer
26.738
3146776BUCKING
Solar/Wind Harmer
-0.16
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.488
970301AG2-198 GEN
Solar/Wind Harmer
11.712
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.393
963191AG1-168 GEN
Solar/Wind Harmer
2.036
971741AH1-377 GEN
Solar/Wind Harmer
24.32
316034AC1-036 C
Solar/Wind Harmer
0.327
970323AG2-213 GEN
Solar/Wind Harmer
8.8
971775AH1-396 GEN
Solar/Wind Harmer
1.253
313527AB2-043 GEN
Solar/Wind Harmer
2.087
3143526WINTERP
Solar/Wind Harmer
-0.066
971223AH1-071 GEN
Solar/Wind Harmer
1.588
962561AG1-105 GEN
Solar/Wind Harmer
5.984
939181AE1-148 GEN
Solar/Wind Harmer
5.82
964791AG1-342 GEN
Solar/Wind Harmer
2.187
3146843MT LREL
Solar/Wind Harmer
-0.01
3146843MT LREL
Solar/Wind Harmer
-0.01
970099AG2-077 GEN
Solar/Wind Harmer
12.322
970933AG2-581 GEN
Solar/Wind Harmer
7.227
316181AB2-040 GEN
Solar/Wind Harmer
0.916
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.712
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.187
3151931BEARGRDN S1
50/50
5.41
3151911BEARGRDN G1
50/50
4.192
3144293JTRSVLE
50/50
0.653
970119AG2-088 GEN
50/50
15.079
972003AH1-546 GEN
Solar/Wind Harmer
24.31
971377AH1-170 GEN
Solar/Wind Harmer
5.633
3147623JAMES R
Solar/Wind Harmer
0.697
970937AG2-583 GEN
Solar/Wind Harmer
30.214
316322AB2-045
Solar/Wind Harmer
1.35
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.533
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.307
963171AG1-166 GEN
Solar/Wind Harmer
2.715
971563AH1-280 GEN
Solar/Wind Harmer
2.715
970685AG2-442 GEN
Solar/Wind Harmer
17.256
962491AG1-098 GEN
Solar/Wind Harmer
8.745
3143526WINTERP
Solar/Wind Harmer
-0.066
3143226MDLTHAN
Solar/Wind Harmer
-0.013
316237AB2-079_GEN
Solar/Wind Harmer
0.378
315693AD1-088 GEN
Solar/Wind Harmer
6.256
970401AG2-262 GEN
Solar/Wind Harmer
0.668
957481AF2-042 GEN
Solar/Wind Harmer
30.804
315687AD1-152 GEN
Solar/Wind Harmer
1.088
971065AG2-659 GEN
Solar/Wind Harmer
4.396
3147043LAWRENC
Adder
0.694
316129AC1-054 GEN
Solar/Wind Harmer
0.753
971795AH1-408 GEN
Solar/Wind Harmer
6.029
316003AC1-222 GEN
Solar/Wind Harmer
0.771
960081AF2-299 GEN
Solar/Wind Harmer
0.762
3147983MERCK5
Solar/Wind Helper
0.055
964241AG1-285 GEN
Solar/Wind Harmer
11.354
958131AF2-107 GEN
Solar/Wind Harmer
4.669
316131AB2-060 GEN
Solar/Wind Harmer
1.422
316478AD1-087 GEN
Solar/Wind Harmer
0.862
316486AD2-202 GEN
Solar/Wind Harmer
0.252
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.252
960061AF2-297 GEN
Solar/Wind Harmer
4.179
971683AH1-343 GEN
Solar/Wind Harmer
3.235
966621AG1-532 GEN
Solar/Wind Harmer
0.137
313506AB2-031 GEN
Solar/Wind Harmer
0.528
316499AE2-029_GEN
Solar/Wind Helper
0.5
3148013FISHERV
Solar/Wind Helper
0.13
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.535
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.048
LAGNLTFEXP_LAGN->PJM
CLTF
1.137
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.801
TVALTFEXP_TVA->PJM
CLTF
0.555
CPLELTFEXP_CPLE->PJM
CLTF
2.975
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.156
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.386

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:661.76 MVA
Rating Type:A
MVA to Mitigate:697.23
MW Contribution:11.6
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.314
3151911BEARGRDN G1
50/50
4.118
3144293JTRSVLE
50/50
0.644
3151531CLOVER1
50/50
1.885
3151601KERR 3
50/50
0.18
3151581KERR 1
50/50
0.064
970119AG2-088 GEN
50/50
11.599
3147043LAWRENC
50/50
0.746
3151261ROARAP2
50/50
0.072
972003AH1-546 GEN
Solar/Wind Harmer
18.108
971377AH1-170 GEN
Solar/Wind Harmer
4.203
3147623JAMES R
Solar/Wind Harmer
0.913
970937AG2-583 GEN
Solar/Wind Harmer
22.204
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.165
316336AC2-165 C
Solar/Wind Harmer
0.01
3143336POWHATN
Solar/Wind Harmer
4.074
963171AG1-166 GEN
Solar/Wind Harmer
1.017
971563AH1-280 GEN
Solar/Wind Harmer
2.035
970685AG2-442 GEN
Solar/Wind Harmer
12.945
962491AG1-098 GEN
Solar/Wind Harmer
6.577
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
5.296
970401AG2-262 GEN
Solar/Wind Harmer
0.531
957481AF2-042 GEN
Solar/Wind Harmer
23.244
3143226MDLTHAN
Solar/Wind Harmer
0.087
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.352
316129AC1-054 GEN
Solar/Wind Harmer
0.289
971795AH1-408 GEN
Solar/Wind Harmer
4.849
3143526WINTERP
Solar/Wind Harmer
0.377
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.595
3145783HORNRTN
Solar/Wind Harmer
0.057
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.752
3144293JTRSVLE
50/50
0.644
3144293JTRSVLE
50/50
0.543
970535AG2-341 GEN
50/50
1.768
3152661PLYWOOD A
50/50
0.177
971489AH1-241 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
1.404
3146776BUCKING
Solar/Wind Harmer
0.114
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
8.767
3147133PAMPLIN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.162
958211AF2-115 GEN
Solar/Wind Harmer
2.289
963191AG1-168 GEN
Solar/Wind Harmer
0.763
971741AH1-377 GEN
Solar/Wind Harmer
18.217
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.61
971775AH1-396 GEN
Solar/Wind Harmer
0.248
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
4.515
939181AE1-148 GEN
Solar/Wind Harmer
4.407
964791AG1-342 GEN
Solar/Wind Harmer
1.738
3146843MT LREL
Solar/Wind Harmer
0.09
3146843MT LREL
Solar/Wind Harmer
0.09
970099AG2-077 GEN
Solar/Wind Harmer
9.298
971223AH1-071 GEN
Solar/Wind Harmer
0.928
3143526WINTERP
Solar/Wind Harmer
0.377
970933AG2-581 GEN
Solar/Wind Harmer
5.476
316181AB2-040 GEN
Solar/Wind Harmer
0.087
3145593CAROLNA
Solar/Wind Harmer
0.058
3145593CAROLNA
Solar/Wind Harmer
0.058
966811AG1-552 GEN
Solar/Wind Harmer
0.627
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.01
3145783HORNRTN
Solar/Wind Harmer
0.808
3145783HORNRTN
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
0.101
966001AG1-469 GEN
Solar/Wind Helper
0.19
3151921BEARGRDN G2
50/50
4.118
3144293JTRSVLE
50/50
0.644
970413AG2-270 GEN
50/50
8.224
3151591KERR 2
50/50
0.18
966251AG1-494 GEN
50/50
1.173
3151261ROARAP2
50/50
0.07
970221AG2-151 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
0.126
3146926FARMVIL
Solar/Wind Harmer
0.165
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.463
970909AG2-566 GEN
Solar/Wind Harmer
2.192
3147133PAMPLIN
Solar/Wind Harmer
0.637
971193AH1-056 GEN
Solar/Wind Harmer
12.353
963181AG1-167 GEN
Solar/Wind Harmer
0.763
959311AF2-222 GEN
Solar/Wind Harmer
14.242
970257AG2-171 GEN
Solar/Wind Harmer
4.957
315785AD2-033 C
Solar/Wind Harmer
1.2
964241AG1-285 GEN
Solar/Wind Harmer
8.548
958131AF2-107 GEN
Solar/Wind Harmer
3.44
316131AB2-060 GEN
Solar/Wind Harmer
0.366
316478AD1-087 GEN
Solar/Wind Harmer
0.307
316486AD2-202 GEN
Solar/Wind Harmer
0.09
3147043LAWRENC
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.155
971683AH1-343 GEN
Solar/Wind Harmer
2.44
313506AB2-031 GEN
Solar/Wind Harmer
0.186
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.54
972205AH1-687 GEN
50/50
20.083
3151541CLOVER2
50/50
1.876
3151611KERR 4
50/50
0.18
3151621KERR 5
50/50
0.18
3151631KERR 6
50/50
0.18
3151641KERR 7
50/50
0.18
316303AF2-085
50/50
1.546
3151281ROARAP4
50/50
0.07
3151281ROARAP4
50/50
0.066
971447AH1-217 GEN
Solar/Wind Harmer
11.004
971845AH1-439 GEN
Solar/Wind Harmer
15.632
970285AG2-188 GEN
Solar/Wind Harmer
26.316
270494AE1-108_GEN
Solar/Wind Harmer
3.693
315657AE1-056 GEN
Solar/Wind Harmer
6.997
946301AF1-294 GEN
Solar/Wind Harmer
3.764
961791AG1-021 GEN
Solar/Wind Harmer
1.831
970683AG2-441 GEN
Solar/Wind Harmer
11.558
970681AG2-440 GEN
Solar/Wind Harmer
9.247
3144303KENBRDG
Solar/Wind Harmer
0.124
971443AH1-215 GEN
Solar/Wind Harmer
2.576
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.212
970831AG2-522 GEN
Solar/Wind Harmer
3.201
3147173SINAI
Solar/Wind Harmer
0.074
3147243WELCO
Solar/Wind Harmer
0.046
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.006
971283AH1-107 GEN
Solar/Wind Harmer
1.006
970865AG2-541 GEN
Solar/Wind Harmer
2.17
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
9.597
3137643SOCKMAN
Solar/Wind Harmer
0.235
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.119
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.029
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.072
LAGNLTFEXP_LAGN->PJM
CLTF
1.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.815
TVALTFEXP_TVA->PJM
CLTF
0.547
CPLELTFEXP_CPLE->PJM
CLTF
2.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.673
MECLTFEXP_MEC->PJM
CLTF
0.138
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.391

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.97 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4121.28
MW Contribution:23.27
Bus #Bus NameTypeMW Contribution
3142296MT RD221
50/50
0.601
971133AH1-012 GEN
50/50
3.127
3142366NRTHEST
50/50
0.606
3150691DARBY 3
50/50
13.299
3150701DARBY 4
50/50
13.268
316447AC1-158 HLD
Solar/Wind Harmer
2.345
971223AH1-071 GEN
Solar/Wind Harmer
1.861
3143526WINTERP
Solar/Wind Harmer
0.906
3150681DARBY 2
Adder
12.489
3150671DARBY 1
Adder
12.475
957411AF2-035 GEN
Solar/Wind Harmer
7.362
970317AG2-208 GEN
Solar/Wind Harmer
6.82
316075AC2-137 C
Solar/Wind Harmer
0.047
315673AE1-157 GEN
Solar/Wind Harmer
11.841
3142946ENON
Solar/Wind Harmer
0.017
944641AF1-129 GEN
Adder
81.317
316240AF1-291 C
Solar/Wind Harmer
0.001
3150391LDYSMT3
Adder
22.619
972195AH1-682 GEN
Adder
2.972
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.189
966871AG1-558 GEN
Solar/Wind Harmer
0.194
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.031
3150991CHESPKB
Adder
1.739
3150991CHESPKB
Adder
1.697
316316AC1-027 C
Solar/Wind Harmer
0.159
3142956BIRDNECK
Solar/Wind Harmer
0
970657AG2-426 GEN
Solar/Wind Harmer
5.802
970657AG2-426 GEN
Solar/Wind Harmer
1.216
316185AD1-033 GEN
Solar/Wind Harmer
0.005
3145506HICKORY
Solar/Wind Harmer
0.66
3145506HICKORY
Solar/Wind Harmer
0.396
3145506HICKORY
Solar/Wind Harmer
0.099
316339AD2-160 GEN
Solar/Wind Harmer
0.267
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.092
3137176SLIGO L2192
Solar/Wind Harmer
0.653
3146456SLIGO L269
Solar/Wind Harmer
2.905
3130086AYDLETT
Solar/Wind Harmer
0.656
3146386ELIZ CT
Solar/Wind Harmer
0.163
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.161
3146516WINFALL
Solar/Wind Harmer
0.161
3146516WINFALL
Solar/Wind Harmer
0.161
3146626S HERTFORD
Solar/Wind Harmer
0.16
3146626S HERTFORD
Solar/Wind Harmer
0.16
3144356SAPONY
Solar/Wind Harmer
1.336
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.696
3146376EDENTON
Solar/Wind Harmer
0.696
972185AH1-677 GEN
Adder
8.772
972187AH1-678 GEN
Adder
4.406
970933AG2-581 GEN
Solar/Wind Harmer
12.222
316065AD1-022 GEN
Solar/Wind Harmer
6.894
3145893MURPHYS
Solar/Wind Harmer
0.995
3145893MURPHYS
Solar/Wind Harmer
0.267
3146173TUNIS
Solar/Wind Harmer
0.147
3146173TUNIS
Solar/Wind Harmer
0.147
970099AG2-077 GEN
Solar/Wind Harmer
15.421
316181AB2-040 GEN
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.144
3142666NORTHAMPTON
Solar/Wind Harmer
0.144
3142666NORTHAMPTON
Solar/Wind Harmer
0.144
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
316426AA2-053 GEN
Solar/Wind Harmer
0.484
958261AF2-120 GEN
Solar/Wind Harmer
4.72
3145593CAROLNA
Solar/Wind Harmer
0.142
3145593CAROLNA
Solar/Wind Harmer
0.142
966811AG1-552 GEN
Solar/Wind Harmer
1.547
3145593CAROLNA
Solar/Wind Harmer
0.177
3145783HORNRTN
Solar/Wind Harmer
2.522
3145783HORNRTN
Solar/Wind Harmer
2.017
3145783HORNRTN
Solar/Wind Harmer
0.63
3145783HORNRTN
Solar/Wind Harmer
0.252
3145796HORNRTN
Solar/Wind Harmer
0.425
3145933PARMELE
Solar/Wind Harmer
0.277
3145933PARMELE
Solar/Wind Harmer
0.138
971741AH1-377 GEN
Solar/Wind Harmer
13.68
3152261N ANNA2
50/50
10.366
970497AG2-320 GEN
50/50
17.429
971645AH1-323 GEN
50/50
15.92
315051AA1-145 CT1
50/50
1.401
316044AC1-158 PL1
Solar/Wind Harmer
1.067
316450AC1-158 RIC
Solar/Wind Harmer
0.284
3142416OLDCHRC
Solar/Wind Harmer
1.7
3150861SPRUNCD
Adder
0.799
970293AG2-193 GEN
Solar/Wind Harmer
1.848
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.709
3142946ENON
Solar/Wind Harmer
0.057
970133AG2-095 GEN
Solar/Wind Harmer
1.632
970129AG2-093 GEN
Solar/Wind Harmer
10.232
315839AE2-212 C
Solar/Wind Harmer
0.001
3150401LDYSMT4
Adder
22.661
3150371LDYSMT1
Adder
21.897
965281AG1-393 GEN
Solar/Wind Harmer
1.801
315778AD1-151 GEN
Solar/Wind Harmer
13.503
316382AG1-145 C
Solar/Wind Harmer
0.001
315773AC2-141 GEN
Solar/Wind Harmer
6.138
316473AC1-191 GEN
Solar/Wind Harmer
0.568
961611AG1-000B GEN
Solar/Wind Harmer
4.473
3151221GRAVEL6
Adder
12.163
3151171GRAVELC
Adder
2.34
3144216WINCHST
Adder
0.63
3150921YORKTN3
Adder
4.197
315813AE1-149 C
Solar/Wind Harmer
8.901
3145336SMITFLD
Solar/Wind Harmer
0.067
3144536CHRHLND
Solar/Wind Harmer
0.025
944581AF1-123 GEN
Solar/Wind Harmer
37.404
944601AF1-125 GEN
Solar/Wind Harmer
36.828
3151101ELIZAR3
Adder
15.417
970659AG2-427 GEN
Solar/Wind Harmer
1.756
3144873MCLAUGH
Solar/Wind Harmer
0.004
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
3.498
3146456SLIGO L269
Solar/Wind Harmer
0.164
971153AH1-033 GEN
Solar/Wind Harmer
1.898
3142433PROV 92
Adder
0.319
3142433PROV 92
Adder
0.319
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.161
3146626S HERTFORD
Solar/Wind Harmer
0.16
3152251N ANNA1
50/50
10.367
315052AA1-145 CT2
50/50
1.407
970119AG2-088 GEN
50/50
23.265
316045AC1-158 PL2
Solar/Wind Harmer
3.412
3142416OLDCHRC
Solar/Wind Harmer
0.456
3142416OLDCHRC
Solar/Wind Harmer
0.175
3143226MDLTHAN
Solar/Wind Harmer
0.174
3143526WINTERP
Solar/Wind Harmer
0.906
3150851SPRUNCC
Adder
0.799
3143096IRON208
Adder
0.724
3142543TWELFTH
Solar/Wind Harmer
0.017
966881AG1-559 GEN
Solar/Wind Harmer
0.199
944631AF1-128 GEN
Adder
81.611
970129AG2-093 GEN
Solar/Wind Harmer
4.815
316458AB2-190 GEN2
Solar/Wind Harmer
0.908
315671AE2-027_GEN
Solar/Wind Harmer
10.821
972197AH1-683 GEN
Adder
3.539
972219AH1-694 GEN
Adder
2.548
971069AG2-661 GEN
Solar/Wind Harmer
3.001
316159AE1-175 C
Solar/Wind Harmer
0.145
971647AH1-324 GEN
Solar/Wind Harmer
7.173
316294AC1-161 GEN
Solar/Wind Harmer
2.912
961611AG1-000B GEN
Solar/Wind Harmer
8.797
3151171GRAVELC
Adder
1.78
3138126ROCKLANDING
Solar/Wind Harmer
0.077
3145336SMITFLD
Solar/Wind Harmer
0.667
971317AH1-138 GEN
Solar/Wind Harmer
1.242
944591AF1-124 GEN
Solar/Wind Harmer
37.537
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.073
970659AG2-427 GEN
Solar/Wind Harmer
8.027
316381AD1-082 GEN
Solar/Wind Harmer
0.173
970661AG2-428 GEN
Solar/Wind Harmer
16.448
939411AE1-173 GEN
Solar/Wind Harmer
70.555
940641AE2-051 GEN
Solar/Wind Harmer
13.225
316072AD1-144
Solar/Wind Harmer
0.06
316388AE2-253 GEN
Solar/Wind Harmer
0.516
3146456SLIGO L269
Solar/Wind Harmer
0.164
3142433PROV 92
Solar/Wind Harmer
0.656
3142433PROV 92
Adder
0.319
3142433PROV 92
Adder
0.319
316246AF1-032 C
Solar/Wind Harmer
0.074
316093AE2-104_GEN
Solar/Wind Harmer
2.744
3146516WINFALL
Solar/Wind Harmer
0.52
3146516WINFALL
Solar/Wind Harmer
0.161
3141766HARMONY
Solar/Wind Harmer
0.032
971777AH1-397 GEN
Solar/Wind Harmer
0.421
3141843SHACKLE
Adder
0.814
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3147666LOUISA
Solar/Wind Harmer
0.628
3130156CHOWAN
Solar/Wind Harmer
0.157
316192AB2-158 GEN
Solar/Wind Harmer
0.873
3143336POWHATN
Solar/Wind Harmer
2.742
3138133OCRAN
Solar/Wind Harmer
0.092
3145663CRESWEL
Solar/Wind Harmer
0.43
971163AH1-040 GEN
Solar/Wind Harmer
12.28
970919AG2-571 GEN
Solar/Wind Harmer
5.328
970087AG2-069 GEN
Solar/Wind Harmer
11.945
3146206CASHIE
Solar/Wind Harmer
0.149
971547AH1-271 GEN
Solar/Wind Harmer
3.183
316023GEN1_S
Solar/Wind Harmer
0.335
316336AC2-165 C
Solar/Wind Harmer
0.006
3145893MURPHYS
Solar/Wind Harmer
0.595
3145893MURPHYS
Solar/Wind Harmer
0.661
3146173TUNIS
Solar/Wind Harmer
0.147
3145683EARLEYS
Solar/Wind Harmer
0.146
960081AF2-299 GEN
Solar/Wind Harmer
1.399
3146263WOODLND
Solar/Wind Harmer
0.145
957481AF2-042 GEN
Solar/Wind Harmer
38.552
3145963POPLR C
Solar/Wind Harmer
0.144
962861AG1-135 GEN
Solar/Wind Harmer
4.597
316011AB1-132 GEN
Solar/Wind Harmer
2.611
962571AG1-106 GEN
Solar/Wind Harmer
2.043
3145823KELFORD
Solar/Wind Harmer
0.143
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
9.537
316174AB2-169 GEN
Solar/Wind Harmer
0.004
315693AD1-088 GEN
Solar/Wind Harmer
6.837
962491AG1-098 GEN
Solar/Wind Harmer
8.111
3145783HORNRTN
Solar/Wind Harmer
0.142
3147043LAWRENC
Adder
1.283
3145796HORNRTN
Solar/Wind Harmer
0.467
3145796HORNRTN
Solar/Wind Harmer
0.142
3141726DUNNSVL
Solar/Wind Harmer
0.559
316212AC1-099_GEN
Solar/Wind Harmer
0.717
3146293MARTNCO
Solar/Wind Harmer
0.128
316129AC1-054 GEN
Solar/Wind Harmer
0.514
3150351NORNECKC2
Adder
1.362
971065AG2-659 GEN
Solar/Wind Harmer
5.808
3145746EVERETS
Solar/Wind Harmer
0.136
3145746EVERETS
Solar/Wind Harmer
0.136
970937AG2-583 GEN
Solar/Wind Harmer
8.299
315722AD1-056 GEN
Solar/Wind Harmer
0.855
316494AC1-189 GEN
Solar/Wind Harmer
0.452
315687AD1-152 GEN
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
9.903
316237AB2-079_GEN
Solar/Wind Harmer
0.001
963171AG1-166 GEN
Solar/Wind Harmer
0.707
971563AH1-280 GEN
Solar/Wind Harmer
1.414
3144293JTRSVLE
Adder
0.422
3146926FARMVIL
Solar/Wind Harmer
0.079
3146233WITAKRS
Solar/Wind Harmer
0.525
961671AG1-007 GEN
Solar/Wind Harmer
0.02
3146083TARBORO
Solar/Wind Harmer
0.132
3145493TOT1
Solar/Wind Harmer
0.587
3145543BTLEBRO
Solar/Wind Harmer
0.13
3145543BTLEBRO
Solar/Wind Harmer
0.104
316359AB2-059 GEN
Solar/Wind Harmer
0.466
316049AB1-081 GEN
Solar/Wind Harmer
0.743
3142053HEARTS
Solar/Wind Harmer
0.229
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.051
972277AH1-723 GEN
Adder
75.653
970401AG2-262 GEN
Solar/Wind Harmer
0.743
316337AD2-073 GEN
Solar/Wind Harmer
0.11
972003AH1-546 GEN
Solar/Wind Harmer
5.295
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.255
3147623JAMES R
Solar/Wind Harmer
0.273
3141766HARMONY
Solar/Wind Harmer
2.125
3141843SHACKLE
Adder
0.814
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3145273HOLLAND
Solar/Wind Harmer
0.119
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316156AD2-030 GEN
Solar/Wind Harmer
0.117
3141873WAN 176
Solar/Wind Harmer
2.802
3147666LOUISA
Solar/Wind Harmer
0.361
3146376EDENTON
Solar/Wind Harmer
0.157
316313AB2-026
Solar/Wind Harmer
0.097
316258AE1-075 C
Solar/Wind Harmer
0.116
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.331
315614AA2-178 GEN
Solar/Wind Harmer
0.878
971157AH1-035 GEN
Solar/Wind Harmer
1.813
315737AD1-076 GEN
Solar/Wind Harmer
1.938
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
970917AG2-570 GEN
Solar/Wind Harmer
13.32
3146206CASHIE
Solar/Wind Harmer
0.149
316365GEN2_N
Solar/Wind Harmer
0.335
3145893MURPHYS
Solar/Wind Harmer
0.249
3145893MURPHYS
Solar/Wind Harmer
0.149
957521AF2-046 GEN
Solar/Wind Harmer
11.038
961681AG1-008 GEN
Solar/Wind Harmer
11.038
962971AG1-146 GEN
Solar/Wind Harmer
2.372
3146173TUNIS
Solar/Wind Harmer
0.147
3156021HOLLOMANSOL
Solar/Wind Harmer
0.668
316463AE2-346 GEN
Solar/Wind Harmer
0.126
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
1.566
970009AG2-005 GEN
Solar/Wind Harmer
1.091
3146263WOODLND
Solar/Wind Harmer
0.145
313506AB2-031 GEN
Solar/Wind Harmer
0.446
3145963POPLR C
Solar/Wind Harmer
0.144
3142666NORTHAMPTON
Solar/Wind Harmer
0.144
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.143
316404AE1-155 C
Solar/Wind Harmer
0.032
3147043LAWRENC
Solar/Wind Harmer
0.085
3145796HORNRTN
Solar/Wind Harmer
0.566
3145796HORNRTN
Solar/Wind Harmer
0.142
316478AD1-087 GEN
Solar/Wind Harmer
0.488
316486AD2-202 GEN
Solar/Wind Harmer
0.143
316210AC1-098 GEN
Solar/Wind Harmer
1.287
3145933PARMELE
Solar/Wind Harmer
0.138
966801AG1-551 GEN
Solar/Wind Harmer
1.612
3150351NORNECKC2
Adder
1.385
970909AG2-566 GEN
Solar/Wind Harmer
1.457
3145746EVERETS
Solar/Wind Harmer
0.136
3145746EVERETS
Solar/Wind Harmer
0.136
315724AD1-057 GEN
Solar/Wind Harmer
0.507
316327AA2-057 GEN
Solar/Wind Harmer
0.202
971781AH1-399 GEN
Solar/Wind Harmer
0.175
316131AB2-060 GEN
Solar/Wind Harmer
0.418
964241AG1-285 GEN
Solar/Wind Harmer
8.854
315785AD2-033 C
Solar/Wind Harmer
1.079
970257AG2-171 GEN
Solar/Wind Harmer
4.246
959311AF2-222 GEN
Solar/Wind Harmer
11.794
963181AG1-167 GEN
Solar/Wind Harmer
0.53
3144293JTRSVLE
Adder
0.422
3147133PAMPLIN
Solar/Wind Harmer
0.416
971193AH1-056 GEN
Solar/Wind Harmer
8.068
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.079
3146233WITAKRS
Solar/Wind Harmer
0.662
3146233WITAKRS
Solar/Wind Harmer
0.09
3146073TAR RVR
Solar/Wind Harmer
0.132
3146083TARBORO
Solar/Wind Harmer
0.132
3138543CONSLDL
Solar/Wind Harmer
0.087
961601AG1-000A GEN
Solar/Wind Harmer
9.233
3145543BTLEBRO
Solar/Wind Harmer
0.13
3145543BTLEBRO
Solar/Wind Harmer
0.13
971623AH1-311 GEN
Solar/Wind Harmer
0.26
3146776BUCKING
Solar/Wind Harmer
0.046
972255AH1-712 GEN
Adder
64.922
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.212
970221AG2-151 GEN
Solar/Wind Harmer
6.277
3141906WESTMOR
Solar/Wind Harmer
0.046
971683AH1-343 GEN
Solar/Wind Harmer
4.21
227287AC2-120 GEN
Solar/Wind Helper
0.383
226910AB2-157 C
Solar/Wind Helper
0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.715
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.431
3150341NORNECKC1
Adder
1.419
970301AG2-198 GEN
Solar/Wind Harmer
5.826
939181AE1-148 GEN
Solar/Wind Harmer
6.4
316468AD1-105 GEN
Solar/Wind Harmer
-0.043
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.662
971775AH1-396 GEN
Solar/Wind Harmer
0.212
958211AF2-115 GEN
Solar/Wind Harmer
1.591
963191AG1-168 GEN
Solar/Wind Harmer
0.53
3144293JTRSVLE
Adder
0.422
3144293JTRSVLE
Adder
0.355
3147133PAMPLIN
Solar/Wind Harmer
0.132
3147133PAMPLIN
Solar/Wind Harmer
0.106
3145493TOT1
Solar/Wind Harmer
0.306
3145453TOT5
Solar/Wind Harmer
0.184
3145603CNETO
Solar/Wind Harmer
0.122
961601AG1-000A GEN
Solar/Wind Harmer
2.308
316263AC1-034 GEN
Solar/Wind Harmer
4.932
3146776BUCKING
Solar/Wind Harmer
0.513
3146776BUCKING
Solar/Wind Harmer
0.042
962561AG1-105 GEN
Solar/Wind Harmer
6.124
964791AG1-342 GEN
Solar/Wind Harmer
2.431
3146843MT LREL
Solar/Wind Harmer
0.126
3146843MT LREL
Solar/Wind Harmer
0.126
971489AH1-241 GEN
Solar/Wind Harmer
6.277
226929AD2-058 GEN
Solar/Wind Helper
0.117
972189AH1-679 GEN
50/50
3.14
316303AF2-085
50/50
3.102
316312AB1-027
Solar/Wind Harmer
0.314
316233AE1-074 FULL
Solar/Wind Harmer
0.14
971281AH1-106 GEN
Solar/Wind Harmer
2.419
971283AH1-107 GEN
Solar/Wind Harmer
2.419
971285AH1-108 GEN
Adder
1.308
315976AC1-164 GENA
Solar/Wind Harmer
17.697
316169AC1-164_GENC
Solar/Wind Harmer
15.289
315975AC1-164 GENB
Solar/Wind Harmer
0.524
316132AB2-190 GEN1
Solar/Wind Harmer
0.908
3150411LDYSMT5
Adder
22.732
3150381LDYSMT2
Adder
21.755
972213AH1-691 GEN
Adder
3.68
972215AH1-692 GEN
Adder
3.68
316369SG1_INVT
Solar/Wind Harmer
0.006
972265AH1-717 GEN
Adder
12.989
3151201GRAVEL4
Adder
12.177
3151191GRAVEL3
Adder
12.023
3151211GRAVEL5
Adder
12.023
3143316POE
Solar/Wind Harmer
0.661
971445AH1-216 GEN
Solar/Wind Harmer
11.749
3151081ELIZAR1
Adder
15.223
3151091ELIZAR2
Adder
14.958
3152611GOSPORTB
Adder
2.114
3152621GOSPORTC
Adder
1.794
3152601GOSPORTA
Adder
1.655
971167AH1-042 GEN
Solar/Wind Harmer
14.623
957871AF2-081 GEN
Solar/Wind Harmer
8.19
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.113
316311AC2-079 GEN
Solar/Wind Harmer
4.713
319010AE1-072 C
Solar/Wind Harmer
0.826
3142433PROV 92
Adder
0.319
3142433PROV 92
Adder
0.319
3146406KITTY HAWK
Solar/Wind Harmer
0.02
316305AF2-043 C
Solar/Wind Harmer
0.001
315835AF2-110_GEN
Solar/Wind Harmer
1.12
313526AB2-022
Solar/Wind Harmer
0.088
3138283WHITEMARSH
Solar/Wind Harmer
0.038
3146486SUNBURY
Solar/Wind Harmer
0.162
3146486SUNBURY
Solar/Wind Harmer
0.162
316321Z2-027
Solar/Wind Harmer
0.03
3146396TANGLEW
Solar/Wind Harmer
0.446
3145176PASQUOTANK
Solar/Wind Harmer
0.1
3143873LANEXA
Solar/Wind Harmer
0.097
316314AB2-024 C
Solar/Wind Harmer
0.001
941031AE2-094 GEN
Solar/Wind Harmer
29.45
944011AF1-069 GEN
Solar/Wind Harmer
9.623
316315AB2-025 C
Solar/Wind Harmer
0.129
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.72
315814AE2-033 C
Solar/Wind Harmer
12.59
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.032
970673AG2-436 GEN
Solar/Wind Harmer
33.603
970673AG2-436 GEN
Solar/Wind Harmer
22.402
3130156CHOWAN
Solar/Wind Harmer
0.157
3130156CHOWAN
Solar/Wind Harmer
0.157
971967AH1-528 GEN
Solar/Wind Harmer
24.944
3141913WHIT STONE
Solar/Wind Harmer
0.154
3138133OCRAN
Solar/Wind Harmer
0.046
315816AE2-034 GEN
Solar/Wind Harmer
0.659
3141783LANCAST
Solar/Wind Harmer
0.091
3141783LANCAST
Solar/Wind Harmer
0.061
3130546PLYMOUTH
Solar/Wind Harmer
0.151
315732AD1-074 GEN1
Solar/Wind Harmer
0.866
315733AD1-074 GEN2
Solar/Wind Harmer
0.866
315735AD1-075 GEN1
Solar/Wind Harmer
0.433
965291AG1-394 GEN
Solar/Wind Harmer
0.666
970085AG2-068 GEN
Solar/Wind Harmer
7.964
970581AG2-369 GEN
Solar/Wind Harmer
6.849
3146206CASHIE
Solar/Wind Harmer
0.149
970601AG2-382 GEN
Solar/Wind Harmer
5.57
3145893MURPHYS
Solar/Wind Harmer
0.401
3145893MURPHYS
Solar/Wind Harmer
0.149
962981AG1-147 GEN
Solar/Wind Harmer
5.535
3145513AHOSKIE
Solar/Wind Harmer
0.307
3145513AHOSKIE
Solar/Wind Harmer
0.147
970327AG2-215 GEN
Solar/Wind Harmer
4.797
3145683EARLEYS
Solar/Wind Harmer
0.292
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.146
3146043SEABORD
Solar/Wind Harmer
0.146
315607AA1-063A GEN
Solar/Wind Harmer
0.297
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
15.794
3137643SOCKMAN
Solar/Wind Harmer
0.572
3145796HORNRTN
Solar/Wind Harmer
0.453
3145796HORNRTN
Solar/Wind Harmer
0.057
3146033SCOT NK
Solar/Wind Harmer
0.563
970831AG2-522 GEN
Solar/Wind Harmer
5.855
3141813NORNECK
Solar/Wind Harmer
0.137
316164AC1-076 GEN
Solar/Wind Harmer
0.191
316005AA1-067
Solar/Wind Harmer
0.146
3145746EVERETS
Solar/Wind Harmer
0.54
3145746EVERETS
Solar/Wind Harmer
0.136
3145746EVERETS
Solar/Wind Harmer
0.136
3145746EVERETS
Solar/Wind Harmer
0.136
970181AG2-120 GEN
Solar/Wind Harmer
1.69
957861AF2-080 GEN
Solar/Wind Harmer
5.767
316420AA1-050 GEN
Solar/Wind Harmer
0.004
971443AH1-215 GEN
Solar/Wind Harmer
2.229
3144303KENBRDG
Solar/Wind Harmer
0.106
970683AG2-441 GEN
Solar/Wind Harmer
8.842
970681AG2-440 GEN
Solar/Wind Harmer
7.073
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
946301AF1-294 GEN
Solar/Wind Harmer
2.616
961791AG1-021 GEN
Solar/Wind Harmer
1.273
315657AE1-056 GEN
Solar/Wind Harmer
4.57
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
0.132
970285AG2-188 GEN
Solar/Wind Harmer
10.232
971845AH1-439 GEN
Solar/Wind Harmer
5.836
972193AH1-681 GEN
Adder
2.901
316118AC1-105 GEN
Solar/Wind Harmer
0.321
972205AH1-687 GEN
Adder
5.288
3147173SINAI
Solar/Wind Harmer
0.122
3147243WELCO
Solar/Wind Harmer
0.076
971447AH1-217 GEN
Solar/Wind Harmer
3.508
316223AC1-118
Solar/Wind Harmer
0.083
LAGNLTFEXP_LAGN->PJM
CLTF
7.273
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.609
TVALTFEXP_TVA->PJM
CLTF
3.681
CPLELTFEXP_CPLE->PJM
CLTF
8.649
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.229
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.332
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.839
MECLTFEXP_MEC->PJM
CLTF
3.961
SIGELTFEXP_SIGE->PJM
CLTF
0.123
NYPJM->LTFIMP_NY
CLTF
2.77
LGEELTFEXP_LGEE->PJM
CLTF
1.53
WECLTFEXP_WEC->PJM
CLTF
0.776

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.02 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4058.27
MW Contribution:23.38
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
10.483
315052AA1-145 CT2
50/50
1.411
970119AG2-088 GEN
50/50
23.375
3142416OLDCHRC
Solar/Wind Harmer
0.457
3142416OLDCHRC
Solar/Wind Harmer
0.175
3143226MDLTHAN
Solar/Wind Harmer
0.175
3143526WINTERP
Solar/Wind Harmer
0.91
3150851SPRUNCC
Adder
0.802
3143096IRON208
Adder
0.726
3142543TWELFTH
Solar/Wind Harmer
0.017
966881AG1-559 GEN
Solar/Wind Harmer
0.2
944631AF1-128 GEN
Adder
81.922
970129AG2-093 GEN
Solar/Wind Harmer
4.835
316458AB2-190 GEN2
Solar/Wind Harmer
0.912
315671AE2-027_GEN
Solar/Wind Harmer
10.867
971069AG2-661 GEN
Solar/Wind Harmer
3.013
972197AH1-683 GEN
Adder
3.547
972219AH1-694 GEN
Adder
2.554
316159AE1-175 C
Solar/Wind Harmer
0.146
971647AH1-324 GEN
Solar/Wind Harmer
7.203
316294AC1-161 GEN
Solar/Wind Harmer
2.925
961611AG1-000B GEN
Solar/Wind Harmer
8.835
3151171GRAVELC
Adder
1.787
3138126ROCKLANDING
Solar/Wind Harmer
0.077
3145336SMITFLD
Solar/Wind Harmer
0.67
971317AH1-138 GEN
Solar/Wind Harmer
1.247
944591AF1-124 GEN
Solar/Wind Harmer
37.708
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.082
970659AG2-427 GEN
Solar/Wind Harmer
8.063
316381AD1-082 GEN
Solar/Wind Harmer
0.174
939411AE1-173 GEN
Solar/Wind Harmer
70.913
940641AE2-051 GEN
Solar/Wind Harmer
13.295
970661AG2-428 GEN
Solar/Wind Harmer
16.522
316072AD1-144
Solar/Wind Harmer
0.06
316388AE2-253 GEN
Solar/Wind Harmer
0.518
3146456SLIGO L269
Solar/Wind Harmer
0.165
3142433PROV 92
Solar/Wind Harmer
0.658
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
316246AF1-032 C
Solar/Wind Harmer
0.074
316093AE2-104_GEN
Solar/Wind Harmer
2.756
3146516WINFALL
Solar/Wind Harmer
0.523
3146516WINFALL
Solar/Wind Harmer
0.161
3141766HARMONY
Solar/Wind Harmer
0.032
971777AH1-397 GEN
Solar/Wind Harmer
0.422
3141843SHACKLE
Adder
0.817
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.157
3143336POWHATN
Solar/Wind Harmer
2.747
3138133OCRAN
Solar/Wind Harmer
0.093
3145663CRESWEL
Solar/Wind Harmer
0.432
971163AH1-040 GEN
Solar/Wind Harmer
12.337
3147666LOUISA
Solar/Wind Harmer
0.616
316192AB2-158 GEN
Solar/Wind Harmer
0.855
970919AG2-571 GEN
Solar/Wind Harmer
5.356
970087AG2-069 GEN
Solar/Wind Harmer
12.008
3146206CASHIE
Solar/Wind Harmer
0.15
971547AH1-271 GEN
Solar/Wind Harmer
3.198
316023GEN1_S
Solar/Wind Harmer
0.336
3145893MURPHYS
Solar/Wind Harmer
0.597
3145893MURPHYS
Solar/Wind Harmer
0.664
316336AC2-165 C
Solar/Wind Harmer
0.006
3146173TUNIS
Solar/Wind Harmer
0.148
3145683EARLEYS
Solar/Wind Harmer
0.147
960081AF2-299 GEN
Solar/Wind Harmer
1.405
3146263WOODLND
Solar/Wind Harmer
0.146
957481AF2-042 GEN
Solar/Wind Harmer
38.725
3145963POPLR C
Solar/Wind Harmer
0.145
316011AB1-132 GEN
Solar/Wind Harmer
2.623
962571AG1-106 GEN
Solar/Wind Harmer
2.053
962861AG1-135 GEN
Solar/Wind Harmer
4.617
3145823KELFORD
Solar/Wind Harmer
0.144
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
9.579
316174AB2-169 GEN
Solar/Wind Harmer
0.004
315693AD1-088 GEN
Solar/Wind Harmer
6.864
962491AG1-098 GEN
Solar/Wind Harmer
8.142
3145783HORNRTN
Solar/Wind Harmer
0.142
3147043LAWRENC
Adder
1.289
3145796HORNRTN
Solar/Wind Harmer
0.469
3145796HORNRTN
Solar/Wind Harmer
0.142
3141726DUNNSVL
Solar/Wind Harmer
0.561
316212AC1-099_GEN
Solar/Wind Harmer
0.721
3146293MARTNCO
Solar/Wind Harmer
0.129
316129AC1-054 GEN
Solar/Wind Harmer
0.516
3150351NORNECKC2
Adder
1.368
971065AG2-659 GEN
Solar/Wind Harmer
5.833
3145746EVERETS
Solar/Wind Harmer
0.136
3145746EVERETS
Solar/Wind Harmer
0.136
315722AD1-056 GEN
Solar/Wind Harmer
0.859
970937AG2-583 GEN
Solar/Wind Harmer
8.284
316494AC1-189 GEN
Solar/Wind Harmer
0.454
315687AD1-152 GEN
Solar/Wind Harmer
0.004
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
9.925
963171AG1-166 GEN
Solar/Wind Harmer
0.708
971563AH1-280 GEN
Solar/Wind Harmer
1.417
3144293JTRSVLE
Adder
0.423
3146233WITAKRS
Solar/Wind Harmer
0.528
961671AG1-007 GEN
Solar/Wind Harmer
0.02
3146083TARBORO
Solar/Wind Harmer
0.133
3145493TOT1
Solar/Wind Harmer
0.59
3146926FARMVIL
Solar/Wind Harmer
0.079
3145543BTLEBRO
Solar/Wind Harmer
0.13
3145543BTLEBRO
Solar/Wind Harmer
0.104
316359AB2-059 GEN
Solar/Wind Harmer
0.469
316049AB1-081 GEN
Solar/Wind Harmer
0.746
3142053HEARTS
Solar/Wind Harmer
0.23
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.051
970401AG2-262 GEN
Solar/Wind Harmer
0.746
316337AD2-073 GEN
Solar/Wind Harmer
0.11
972277AH1-723 GEN
Adder
75.69
972003AH1-546 GEN
Solar/Wind Harmer
5.274
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.25
3147623JAMES R
Solar/Wind Harmer
0.271
3152261N ANNA2
50/50
10.482
970497AG2-320 GEN
50/50
17.465
971645AH1-323 GEN
50/50
15.968
315051AA1-145 CT1
50/50
1.405
3142416OLDCHRC
Solar/Wind Harmer
1.706
3150861SPRUNCD
Adder
0.802
970293AG2-193 GEN
Solar/Wind Harmer
1.855
3143096IRON208
Adder
0.726
3143096IRON208
Adder
0.712
3142946ENON
Solar/Wind Harmer
0.057
970133AG2-095 GEN
Solar/Wind Harmer
1.638
970129AG2-093 GEN
Solar/Wind Harmer
10.274
315839AE2-212 C
Solar/Wind Harmer
0.001
965281AG1-393 GEN
Solar/Wind Harmer
1.809
315778AD1-151 GEN
Solar/Wind Harmer
13.559
3150401LDYSMT4
Adder
22.715
3150371LDYSMT1
Adder
21.949
316382AG1-145 C
Solar/Wind Harmer
0.001
315773AC2-141 GEN
Solar/Wind Harmer
6.165
316473AC1-191 GEN
Solar/Wind Harmer
0.569
961611AG1-000B GEN
Solar/Wind Harmer
4.492
3151221GRAVEL6
Adder
12.215
3151171GRAVELC
Adder
2.35
3144216WINCHST
Adder
0.633
3150921YORKTN3
Adder
4.214
315813AE1-149 C
Solar/Wind Harmer
8.94
3145336SMITFLD
Solar/Wind Harmer
0.067
3144536CHRHLND
Solar/Wind Harmer
0.025
944581AF1-123 GEN
Solar/Wind Harmer
37.574
944601AF1-125 GEN
Solar/Wind Harmer
36.995
3151101ELIZAR3
Adder
15.487
970659AG2-427 GEN
Solar/Wind Harmer
1.764
3144873MCLAUGH
Solar/Wind Harmer
0.004
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
3.514
3146456SLIGO L269
Solar/Wind Harmer
0.165
971153AH1-033 GEN
Solar/Wind Harmer
1.907
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.161
3146626S HERTFORD
Solar/Wind Harmer
0.16
3145273HOLLAND
Solar/Wind Harmer
0.12
3141766HARMONY
Solar/Wind Harmer
2.133
3141843SHACKLE
Adder
0.817
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316156AD2-030 GEN
Solar/Wind Harmer
0.117
3141873WAN 176
Solar/Wind Harmer
2.813
3146376EDENTON
Solar/Wind Harmer
0.157
316313AB2-026
Solar/Wind Harmer
0.097
316258AE1-075 C
Solar/Wind Harmer
0.117
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.335
315614AA2-178 GEN
Solar/Wind Harmer
0.882
3147666LOUISA
Solar/Wind Harmer
0.354
971157AH1-035 GEN
Solar/Wind Harmer
1.821
315737AD1-076 GEN
Solar/Wind Harmer
1.947
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
970917AG2-570 GEN
Solar/Wind Harmer
13.391
3146206CASHIE
Solar/Wind Harmer
0.15
316365GEN2_N
Solar/Wind Harmer
0.336
3145893MURPHYS
Solar/Wind Harmer
0.25
3145893MURPHYS
Solar/Wind Harmer
0.149
957521AF2-046 GEN
Solar/Wind Harmer
11.089
961681AG1-008 GEN
Solar/Wind Harmer
11.089
962971AG1-146 GEN
Solar/Wind Harmer
2.382
3146173TUNIS
Solar/Wind Harmer
0.148
3156021HOLLOMANSOL
Solar/Wind Harmer
0.671
316463AE2-346 GEN
Solar/Wind Harmer
0.127
316140AB2-099
Solar/Wind Harmer
0.053
962331AG1-082 GEN
Solar/Wind Harmer
1.573
970009AG2-005 GEN
Solar/Wind Harmer
1.096
3146263WOODLND
Solar/Wind Harmer
0.146
313506AB2-031 GEN
Solar/Wind Harmer
0.448
3145963POPLR C
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.144
316404AE1-155 C
Solar/Wind Harmer
0.032
3147043LAWRENC
Solar/Wind Harmer
0.085
3145796HORNRTN
Solar/Wind Harmer
0.569
3145796HORNRTN
Solar/Wind Harmer
0.142
316478AD1-087 GEN
Solar/Wind Harmer
0.49
316486AD2-202 GEN
Solar/Wind Harmer
0.144
316210AC1-098 GEN
Solar/Wind Harmer
1.293
3145933PARMELE
Solar/Wind Harmer
0.139
966801AG1-551 GEN
Solar/Wind Harmer
1.62
3150351NORNECKC2
Adder
1.391
970909AG2-566 GEN
Solar/Wind Harmer
1.459
3145746EVERETS
Solar/Wind Harmer
0.136
3145746EVERETS
Solar/Wind Harmer
0.136
315724AD1-057 GEN
Solar/Wind Harmer
0.509
316327AA2-057 GEN
Solar/Wind Harmer
0.203
971781AH1-399 GEN
Solar/Wind Harmer
0.176
316131AB2-060 GEN
Solar/Wind Harmer
0.419
964241AG1-285 GEN
Solar/Wind Harmer
8.883
315785AD2-033 C
Solar/Wind Harmer
1.082
970257AG2-171 GEN
Solar/Wind Harmer
4.258
959311AF2-222 GEN
Solar/Wind Harmer
11.824
963181AG1-167 GEN
Solar/Wind Harmer
0.531
3144293JTRSVLE
Adder
0.423
3147133PAMPLIN
Solar/Wind Harmer
0.416
971193AH1-056 GEN
Solar/Wind Harmer
8.081
3146233WITAKRS
Solar/Wind Harmer
0.666
3146233WITAKRS
Solar/Wind Harmer
0.09
3146073TAR RVR
Solar/Wind Harmer
0.133
3146083TARBORO
Solar/Wind Harmer
0.133
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3138543CONSLDL
Solar/Wind Harmer
0.087
3146926FARMVIL
Solar/Wind Harmer
0.079
961601AG1-000A GEN
Solar/Wind Harmer
9.279
3145543BTLEBRO
Solar/Wind Harmer
0.13
3145543BTLEBRO
Solar/Wind Harmer
0.13
971623AH1-311 GEN
Solar/Wind Harmer
0.261
3146776BUCKING
Solar/Wind Harmer
0.046
972255AH1-712 GEN
Adder
64.953
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.234
970221AG2-151 GEN
Solar/Wind Harmer
6.249
3141906WESTMOR
Solar/Wind Harmer
0.046
971683AH1-343 GEN
Solar/Wind Harmer
4.228
227287AC2-120 GEN
Solar/Wind Helper
0.382
226910AB2-157 C
Solar/Wind Helper
0.015
3142296MT RD221
50/50
0.603
3142366NRTHEST
50/50
0.608
3150691DARBY 3
50/50
13.346
3150701DARBY 4
50/50
13.315
971223AH1-071 GEN
Solar/Wind Harmer
1.87
3143526WINTERP
Solar/Wind Harmer
0.91
3150681DARBY 2
Adder
12.534
3150671DARBY 1
Adder
12.519
957411AF2-035 GEN
Solar/Wind Harmer
7.381
970317AG2-208 GEN
Solar/Wind Harmer
6.838
316075AC2-137 C
Solar/Wind Harmer
0.047
3142946ENON
Solar/Wind Harmer
0.017
315673AE1-157 GEN
Solar/Wind Harmer
11.872
944641AF1-129 GEN
Adder
81.65
316240AF1-291 C
Solar/Wind Harmer
0.001
3150391LDYSMT3
Adder
22.673
972195AH1-682 GEN
Adder
2.98
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.19
966871AG1-558 GEN
Solar/Wind Harmer
0.195
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.031
3150991CHESPKB
Adder
1.747
3150991CHESPKB
Adder
1.705
316316AC1-027 C
Solar/Wind Harmer
0.16
3142956BIRDNECK
Solar/Wind Harmer
0
970657AG2-426 GEN
Solar/Wind Harmer
5.828
970657AG2-426 GEN
Solar/Wind Harmer
1.222
316185AD1-033 GEN
Solar/Wind Harmer
0.005
3145506HICKORY
Solar/Wind Harmer
0.663
3145506HICKORY
Solar/Wind Harmer
0.398
3145506HICKORY
Solar/Wind Harmer
0.1
316339AD2-160 GEN
Solar/Wind Harmer
0.268
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.092
3137176SLIGO L2192
Solar/Wind Harmer
0.656
3146456SLIGO L269
Solar/Wind Harmer
2.919
3130086AYDLETT
Solar/Wind Harmer
0.659
3146386ELIZ CT
Solar/Wind Harmer
0.163
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.161
3146516WINFALL
Solar/Wind Harmer
0.161
3146516WINFALL
Solar/Wind Harmer
0.161
3146626S HERTFORD
Solar/Wind Harmer
0.16
3146626S HERTFORD
Solar/Wind Harmer
0.16
3144356SAPONY
Solar/Wind Harmer
1.342
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.7
3146376EDENTON
Solar/Wind Harmer
0.7
972185AH1-677 GEN
Adder
8.818
972187AH1-678 GEN
Adder
4.429
970933AG2-581 GEN
Solar/Wind Harmer
12.283
316065AD1-022 GEN
Solar/Wind Harmer
6.926
3145893MURPHYS
Solar/Wind Harmer
1
3145893MURPHYS
Solar/Wind Harmer
0.269
3146173TUNIS
Solar/Wind Harmer
0.148
3146173TUNIS
Solar/Wind Harmer
0.148
970099AG2-077 GEN
Solar/Wind Harmer
15.49
316181AB2-040 GEN
Solar/Wind Harmer
0.21
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.087
316426AA2-053 GEN
Solar/Wind Harmer
0.486
958261AF2-120 GEN
Solar/Wind Harmer
4.741
3145593CAROLNA
Solar/Wind Harmer
0.143
3145593CAROLNA
Solar/Wind Harmer
0.143
966811AG1-552 GEN
Solar/Wind Harmer
1.554
3145593CAROLNA
Solar/Wind Harmer
0.178
3145783HORNRTN
Solar/Wind Harmer
2.534
3145783HORNRTN
Solar/Wind Harmer
2.027
3145783HORNRTN
Solar/Wind Harmer
0.633
3145783HORNRTN
Solar/Wind Harmer
0.253
3145796HORNRTN
Solar/Wind Harmer
0.427
3145933PARMELE
Solar/Wind Harmer
0.278
3145933PARMELE
Solar/Wind Harmer
0.139
316274AC1-208 GEN
Solar/Wind Harmer
0.718
971741AH1-377 GEN
Solar/Wind Harmer
13.711
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.437
3150341NORNECKC1
Adder
1.426
970301AG2-198 GEN
Solar/Wind Harmer
5.837
939181AE1-148 GEN
Solar/Wind Harmer
6.426
316468AD1-105 GEN
Solar/Wind Harmer
-0.043
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.677
971775AH1-396 GEN
Solar/Wind Harmer
0.213
958211AF2-115 GEN
Solar/Wind Harmer
1.594
963191AG1-168 GEN
Solar/Wind Harmer
0.531
3144293JTRSVLE
Adder
0.423
3144293JTRSVLE
Adder
0.356
3147133PAMPLIN
Solar/Wind Harmer
0.133
3147133PAMPLIN
Solar/Wind Harmer
0.106
3145493TOT1
Solar/Wind Harmer
0.307
3145453TOT5
Solar/Wind Harmer
0.184
3145603CNETO
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
2.32
316263AC1-034 GEN
Solar/Wind Harmer
4.956
3146776BUCKING
Solar/Wind Harmer
0.512
3146776BUCKING
Solar/Wind Harmer
0.041
962561AG1-105 GEN
Solar/Wind Harmer
6.148
964791AG1-342 GEN
Solar/Wind Harmer
2.441
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
971489AH1-241 GEN
Solar/Wind Harmer
6.249
226929AD2-058 GEN
Solar/Wind Helper
0.117
972189AH1-679 GEN
50/50
3.149
316303AF2-085
50/50
3.117
316312AB1-027
Solar/Wind Harmer
0.315
316233AE1-074 FULL
Solar/Wind Harmer
0.14
971281AH1-106 GEN
Solar/Wind Harmer
2.429
971283AH1-107 GEN
Solar/Wind Harmer
2.429
971285AH1-108 GEN
Adder
1.313
315976AC1-164 GENA
Solar/Wind Harmer
17.761
316169AC1-164_GENC
Solar/Wind Harmer
15.344
315975AC1-164 GENB
Solar/Wind Harmer
0.525
316132AB2-190 GEN1
Solar/Wind Harmer
0.912
3150411LDYSMT5
Adder
22.786
3150381LDYSMT2
Adder
21.807
972213AH1-691 GEN
Adder
3.689
972215AH1-692 GEN
Adder
3.689
316369SG1_INVT
Solar/Wind Harmer
0.006
972265AH1-717 GEN
Adder
13.045
3151201GRAVEL4
Adder
12.229
3151191GRAVEL3
Adder
12.074
3151211GRAVEL5
Adder
12.074
3143316POE
Solar/Wind Harmer
0.664
971445AH1-216 GEN
Solar/Wind Harmer
11.8
3151081ELIZAR1
Adder
15.291
3151091ELIZAR2
Adder
15.026
3152611GOSPORTB
Adder
2.124
3152621GOSPORTC
Adder
1.802
3152601GOSPORTA
Adder
1.662
971167AH1-042 GEN
Solar/Wind Harmer
14.68
957871AF2-081 GEN
Solar/Wind Harmer
8.227
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.113
316311AC2-079 GEN
Solar/Wind Harmer
4.735
319010AE1-072 C
Solar/Wind Harmer
0.83
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
316305AF2-043 C
Solar/Wind Harmer
0.001
315835AF2-110_GEN
Solar/Wind Harmer
1.125
313526AB2-022
Solar/Wind Harmer
0.088
3138283WHITEMARSH
Solar/Wind Harmer
0.038
3146486SUNBURY
Solar/Wind Harmer
0.163
3146486SUNBURY
Solar/Wind Harmer
0.163
316321Z2-027
Solar/Wind Harmer
0.03
3146396TANGLEW
Solar/Wind Harmer
0.448
3145176PASQUOTANK
Solar/Wind Harmer
0.101
3143873LANEXA
Solar/Wind Harmer
0.097
316314AB2-024 C
Solar/Wind Harmer
0.001
941031AE2-094 GEN
Solar/Wind Harmer
29.608
944011AF1-069 GEN
Solar/Wind Harmer
9.674
316315AB2-025 C
Solar/Wind Harmer
0.13
316059AD1-063 C
Solar/Wind Harmer
0.001
315814AE2-033 C
Solar/Wind Harmer
12.651
970189AG2-124 GEN
Solar/Wind Harmer
4.739
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
970673AG2-436 GEN
Solar/Wind Harmer
33.781
970673AG2-436 GEN
Solar/Wind Harmer
22.521
3141873WAN 176
Solar/Wind Harmer
0.032
3130156CHOWAN
Solar/Wind Harmer
0.157
3130156CHOWAN
Solar/Wind Harmer
0.157
971967AH1-528 GEN
Solar/Wind Harmer
25.073
3141913WHIT STONE
Solar/Wind Harmer
0.155
3138133OCRAN
Solar/Wind Harmer
0.046
315816AE2-034 GEN
Solar/Wind Harmer
0.662
3141783LANCAST
Solar/Wind Harmer
0.092
3141783LANCAST
Solar/Wind Harmer
0.061
3130546PLYMOUTH
Solar/Wind Harmer
0.152
315732AD1-074 GEN1
Solar/Wind Harmer
0.87
315733AD1-074 GEN2
Solar/Wind Harmer
0.87
315735AD1-075 GEN1
Solar/Wind Harmer
0.435
965291AG1-394 GEN
Solar/Wind Harmer
0.67
970085AG2-068 GEN
Solar/Wind Harmer
8.006
970581AG2-369 GEN
Solar/Wind Harmer
6.885
3146206CASHIE
Solar/Wind Harmer
0.15
970601AG2-382 GEN
Solar/Wind Harmer
5.596
3145893MURPHYS
Solar/Wind Harmer
0.403
3145893MURPHYS
Solar/Wind Harmer
0.149
962981AG1-147 GEN
Solar/Wind Harmer
5.559
3145513AHOSKIE
Solar/Wind Harmer
0.308
3145513AHOSKIE
Solar/Wind Harmer
0.147
3145683EARLEYS
Solar/Wind Harmer
0.294
3145683EARLEYS
Solar/Wind Harmer
0.147
3145683EARLEYS
Solar/Wind Harmer
0.147
970327AG2-215 GEN
Solar/Wind Harmer
4.817
3146043SEABORD
Solar/Wind Harmer
0.147
315607AA1-063A GEN
Solar/Wind Harmer
0.299
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
15.869
3137643SOCKMAN
Solar/Wind Harmer
0.575
3145796HORNRTN
Solar/Wind Harmer
0.455
3145796HORNRTN
Solar/Wind Harmer
0.057
3146033SCOT NK
Solar/Wind Harmer
0.566
970831AG2-522 GEN
Solar/Wind Harmer
5.88
3141813NORNECK
Solar/Wind Harmer
0.137
316005AA1-067
Solar/Wind Harmer
0.146
3145746EVERETS
Solar/Wind Harmer
0.543
3145746EVERETS
Solar/Wind Harmer
0.136
3145746EVERETS
Solar/Wind Harmer
0.136
3145746EVERETS
Solar/Wind Harmer
0.136
970181AG2-120 GEN
Solar/Wind Harmer
1.698
957861AF2-080 GEN
Solar/Wind Harmer
5.795
316420AA1-050 GEN
Solar/Wind Harmer
0.004
971443AH1-215 GEN
Solar/Wind Harmer
2.235
3144303KENBRDG
Solar/Wind Harmer
0.106
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
970683AG2-441 GEN
Solar/Wind Harmer
8.862
970681AG2-440 GEN
Solar/Wind Harmer
7.089
946301AF1-294 GEN
Solar/Wind Harmer
2.621
961791AG1-021 GEN
Solar/Wind Harmer
1.275
315657AE1-056 GEN
Solar/Wind Harmer
4.577
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.133
3145573BETHELC
Solar/Wind Harmer
0.133
970285AG2-188 GEN
Solar/Wind Harmer
10.217
971845AH1-439 GEN
Solar/Wind Harmer
5.825
972193AH1-681 GEN
Adder
2.902
316118AC1-105 GEN
Solar/Wind Harmer
0.322
972205AH1-687 GEN
Adder
5.264
3147173SINAI
Solar/Wind Harmer
0.123
3147243WELCO
Solar/Wind Harmer
0.077
316223AC1-118
Solar/Wind Harmer
0.083
971447AH1-217 GEN
Solar/Wind Harmer
3.491
LAGNLTFEXP_LAGN->PJM
CLTF
7.341
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.725
TVALTFEXP_TVA->PJM
CLTF
3.714
CPLELTFEXP_CPLE->PJM
CLTF
8.696
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.674
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.964
MECLTFEXP_MEC->PJM
CLTF
4.016
SIGELTFEXP_SIGE->PJM
CLTF
0.124
NYPJM->LTFIMP_NY
CLTF
2.744
LGEELTFEXP_LGEE->PJM
CLTF
1.552
WECLTFEXP_WEC->PJM
CLTF
0.789

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5650.14
MW Contribution:49.13
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
30.786
970531AG2-338 GEN
50/50
12.314
315242AE2-183_GT2
50/50
5.558
315241AE2-183_GT1
50/50
5.524
972185AH1-677 GEN
50/50
20.036
3151041BRUNSWICKG3
50/50
4.373
972187AH1-678 GEN
50/50
10.036
3150991CHESPKB
50/50
3.415
3150991CHESPKB
50/50
3.333
971223AH1-071 GEN
Solar/Wind Harmer
3.931
3143526WINTERP
Solar/Wind Harmer
1.742
970933AG2-581 GEN
Solar/Wind Harmer
25.944
3144356SAPONY
Solar/Wind Harmer
2.645
316185AD1-033 GEN
Solar/Wind Harmer
0.009
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.295
3145506HICKORY
Solar/Wind Harmer
1.229
3145506HICKORY
Solar/Wind Harmer
0.737
3145506HICKORY
Solar/Wind Harmer
0.184
316036AC1-147 C
Solar/Wind Harmer
0.057
316339AD2-160 GEN
Solar/Wind Harmer
0.497
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.171
3137176SLIGO L2192
Solar/Wind Harmer
1.217
3146456SLIGO L269
Solar/Wind Harmer
5.409
3130086AYDLETT
Solar/Wind Harmer
1.221
3146386ELIZ CT
Solar/Wind Harmer
0.303
970657AG2-426 GEN
Solar/Wind Harmer
10.611
970657AG2-426 GEN
Solar/Wind Harmer
2.224
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3146626S HERTFORD
Solar/Wind Harmer
0.299
3146626S HERTFORD
Solar/Wind Harmer
0.299
970099AG2-077 GEN
Solar/Wind Harmer
31.878
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.308
3146376EDENTON
Solar/Wind Harmer
1.308
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.017
315697AD1-025 GEN
Solar/Wind Harmer
0.325
944641AF1-129 GEN
Adder
137.21
316065AD1-022 GEN
Solar/Wind Harmer
13.074
3145893MURPHYS
Solar/Wind Harmer
1.897
3145893MURPHYS
Solar/Wind Harmer
0.51
3146173TUNIS
Solar/Wind Harmer
0.281
3146173TUNIS
Solar/Wind Harmer
0.281
316181AB2-040 GEN
Solar/Wind Harmer
0.407
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.167
316426AA2-053 GEN
Solar/Wind Harmer
0.935
3145593CAROLNA
Solar/Wind Harmer
0.276
3145593CAROLNA
Solar/Wind Harmer
0.276
966811AG1-552 GEN
Solar/Wind Harmer
2.997
3145593CAROLNA
Solar/Wind Harmer
0.344
3145796HORNRTN
Solar/Wind Harmer
0.825
3145783HORNRTN
Solar/Wind Harmer
4.886
3145783HORNRTN
Solar/Wind Harmer
3.909
3145783HORNRTN
Solar/Wind Harmer
1.222
3145783HORNRTN
Solar/Wind Harmer
0.489
316274AC1-208 GEN
Solar/Wind Harmer
1.384
3145933PARMELE
Solar/Wind Harmer
0.531
3145933PARMELE
Solar/Wind Harmer
0.265
3142946ENON
Solar/Wind Harmer
0.026
971741AH1-377 GEN
Solar/Wind Harmer
26.27
939181AE1-148 GEN
Solar/Wind Harmer
12.567
3142366NRTHEST
Adder
0.844
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970301AG2-198 GEN
Solar/Wind Harmer
10.992
3150691DARBY 3
Adder
18.496
3150701DARBY 4
Adder
18.453
3150681DARBY 2
Adder
18.432
3150671DARBY 1
Adder
18.41
3145493TOT1
Solar/Wind Harmer
0.592
3145453TOT5
Solar/Wind Harmer
0.355
3145603CNETO
Solar/Wind Harmer
0.237
961601AG1-000A GEN
Solar/Wind Harmer
4.486
316263AC1-034 GEN
Solar/Wind Harmer
9.586
316075AC2-137 C
Solar/Wind Harmer
0.069
970323AG2-213 GEN
Solar/Wind Harmer
10.747
971775AH1-396 GEN
Solar/Wind Harmer
0.403
316034AC1-036 C
Solar/Wind Harmer
0.018
962561AG1-105 GEN
Solar/Wind Harmer
11.957
964791AG1-342 GEN
Solar/Wind Harmer
4.752
3146843MT LREL
Solar/Wind Harmer
0.247
3146843MT LREL
Solar/Wind Harmer
0.247
958211AF2-115 GEN
Solar/Wind Harmer
2.961
963191AG1-168 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3144293JTRSVLE
Adder
0.661
3147133PAMPLIN
Solar/Wind Harmer
0.245
3147133PAMPLIN
Solar/Wind Harmer
0.196
3142296MT RD221
Adder
0.748
316222AC1-221 GEN
Solar/Wind Harmer
0.912
966871AG1-558 GEN
Solar/Wind Harmer
0.251
3146776BUCKING
Solar/Wind Harmer
0.848
3146776BUCKING
Solar/Wind Harmer
0.069
958261AF2-120 GEN
Solar/Wind Harmer
6.796
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.997
3150341NORNECKC1
Adder
1.981
942751AE2-291 GEN
Solar/Wind Harmer
9.768
971489AH1-241 GEN
Solar/Wind Harmer
9.113
316468AD1-105 GEN
Solar/Wind Harmer
-0.049
270013AE1-250 PV
Solar/Wind Harmer
0.004
315821AE2-092 GEN
Solar/Wind Harmer
0.008
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.248
316447AC1-158 HLD
Solar/Wind Helper
4.837
315651AD1-115 GEN
Solar/Wind Helper
0.937
226929AD2-058 GEN
Solar/Wind Helper
0.091
970119AG2-088 GEN
50/50
49.132
315243AE2-183_GT3
50/50
5.558
3151051BRUNSWICKS1
50/50
9.077
3151021BRUNSWICKG1
50/50
4.373
971451AH1-221 GEN
50/50
13.283
3150981CHESPKA
50/50
4.07
3150851SPRUNCC
50/50
1.461
3152331SURRY 2
50/50
12.331
3143226MDLTHAN
Solar/Wind Harmer
0.368
940641AE2-051 GEN
Solar/Wind Harmer
28.054
939411AE1-173 GEN
Solar/Wind Harmer
145.057
3143526WINTERP
Solar/Wind Harmer
1.742
970919AG2-571 GEN
Solar/Wind Harmer
11.363
970087AG2-069 GEN
Solar/Wind Harmer
25.456
316294AC1-161 GEN
Solar/Wind Harmer
5.4
944591AF1-124 GEN
Solar/Wind Harmer
69.98
316375AC2-012 GEN
Solar/Wind Harmer
0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.96
3146456SLIGO L269
Solar/Wind Harmer
0.306
316246AF1-032 C
Solar/Wind Harmer
0.137
316093AE2-104_GEN
Solar/Wind Harmer
5.099
970661AG2-428 GEN
Solar/Wind Harmer
30.138
316381AD1-082 GEN
Solar/Wind Harmer
0.316
970659AG2-427 GEN
Solar/Wind Harmer
14.649
316072AD1-144
Solar/Wind Harmer
0.109
3146516WINFALL
Solar/Wind Harmer
0.972
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
1.197
957481AF2-042 GEN
Solar/Wind Harmer
79.695
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
5.25
3130156CHOWAN
Solar/Wind Harmer
0.294
3151171GRAVELC
Adder
3.13
961611AG1-000B GEN
Solar/Wind Harmer
15.335
315671AE2-027_GEN
Solar/Wind Harmer
18.679
316023GEN1_S
Solar/Wind Harmer
0.655
971647AH1-324 GEN
Solar/Wind Harmer
12.413
3145663CRESWEL
Solar/Wind Harmer
0.81
971163AH1-040 GEN
Solar/Wind Harmer
23.157
315693AD1-088 GEN
Solar/Wind Harmer
13.873
971069AG2-661 GEN
Solar/Wind Harmer
5.126
962491AG1-098 GEN
Solar/Wind Harmer
16.401
316458AB2-190 GEN2
Solar/Wind Harmer
1.538
970129AG2-093 GEN
Solar/Wind Harmer
8.145
960081AF2-299 GEN
Solar/Wind Harmer
2.73
3138126ROCKLANDING
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
1.134
3145893MURPHYS
Solar/Wind Harmer
1.26
3146206CASHIE
Solar/Wind Harmer
0.283
971547AH1-271 GEN
Solar/Wind Harmer
6.043
3146173TUNIS
Solar/Wind Harmer
0.281
3142543TWELFTH
Solar/Wind Harmer
0.027
3145683EARLEYS
Solar/Wind Harmer
0.279
316011AB1-132 GEN
Solar/Wind Harmer
5.071
962571AG1-106 GEN
Solar/Wind Harmer
3.968
971795AH1-408 GEN
Solar/Wind Harmer
18.591
3146263WOODLND
Solar/Wind Harmer
0.278
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
2.5
316336AC2-165 C
Solar/Wind Harmer
0.011
971317AH1-138 GEN
Solar/Wind Harmer
2.057
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
0.275
3145783HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
316174AB2-169 GEN
Solar/Wind Harmer
0.007
316159AE1-175 C
Solar/Wind Harmer
0.235
944631AF1-128 GEN
Adder
128.871
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.386
316129AC1-054 GEN
Solar/Wind Harmer
1.006
971065AG2-659 GEN
Solar/Wind Harmer
11.378
3146293MARTNCO
Solar/Wind Harmer
0.246
315722AD1-056 GEN
Solar/Wind Harmer
1.662
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316494AC1-189 GEN
Solar/Wind Harmer
0.872
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
1.019
961671AG1-007 GEN
Solar/Wind Harmer
0.039
3146083TARBORO
Solar/Wind Harmer
0.255
3145493TOT1
Solar/Wind Harmer
1.136
3142433PROV 92
Solar/Wind Harmer
1.012
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
316359AB2-059 GEN
Solar/Wind Harmer
0.906
316049AB1-081 GEN
Solar/Wind Harmer
1.444
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.202
3142053HEARTS
Solar/Wind Harmer
0.444
970685AG2-442 GEN
Solar/Wind Harmer
18.609
970401AG2-262 GEN
Solar/Wind Harmer
1.452
963171AG1-166 GEN
Solar/Wind Harmer
1.316
971563AH1-280 GEN
Solar/Wind Harmer
2.632
3144293JTRSVLE
Adder
0.785
971777AH1-397 GEN
Solar/Wind Harmer
0.643
3141843SHACKLE
Adder
1.244
3141766HARMONY
Solar/Wind Harmer
0.048
3142416OLDCHRC
Solar/Wind Harmer
0.623
3142416OLDCHRC
Solar/Wind Harmer
0.239
3146926FARMVIL
Solar/Wind Harmer
0.141
3138133OCRAN
Solar/Wind Harmer
0.139
316003AC1-222 GEN
Solar/Wind Harmer
0.006
970937AG2-583 GEN
Solar/Wind Harmer
13.92
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.085
962861AG1-135 GEN
Solar/Wind Harmer
6.647
3141726DUNNSVL
Solar/Wind Harmer
0.786
3150351NORNECKC2
Adder
1.901
972003AH1-546 GEN
Solar/Wind Harmer
8.083
971377AH1-170 GEN
Solar/Wind Harmer
1.823
3147623JAMES R
Solar/Wind Harmer
0.396
316337AD2-073 GEN
Solar/Wind Harmer
0.146
970223AG2-152 GEN
Solar/Wind Harmer
10.672
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.084
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.176
972277AH1-723 GEN
Adder
76.921
270030AE2-140 GEN
Solar/Wind Harmer
12.711
316045AC1-158 PL2
Solar/Wind Helper
7.036
3147666LOUISA
Solar/Wind Helper
1.244
316192AB2-158 GEN
Solar/Wind Helper
2.045
316254AC1-120 GEN1
Solar/Wind Helper
1.287
316006AB2-029 C
Solar/Wind Helper
0.13
316303AF2-085
50/50
6.551
315244AE2-183_ST
50/50
9.609
963041AG1-153 GEN
50/50
8.856
315779AE2-040
50/50
4.414
3151081ELIZAR1
50/50
29.922
3151091ELIZAR2
50/50
29.403
941591AE2-156 GEN
50/50
27.332
3152611GOSPORTB
50/50
4.152
3152621GOSPORTC
50/50
3.523
3152601GOSPORTA
50/50
3.25
971285AH1-108 GEN
50/50
2.391
972263AH1-716 GEN
50/50
170.662
941031AE2-094 GEN
Solar/Wind Harmer
63.788
944011AF1-069 GEN
Solar/Wind Harmer
20.842
970673AG2-436 GEN
Solar/Wind Harmer
72.487
970673AG2-436 GEN
Solar/Wind Harmer
48.325
316233AE1-074 FULL
Solar/Wind Harmer
0.268
971281AH1-106 GEN
Solar/Wind Harmer
4.649
971283AH1-107 GEN
Solar/Wind Harmer
4.649
971967AH1-528 GEN
Solar/Wind Harmer
53.477
970085AG2-068 GEN
Solar/Wind Harmer
16.971
970581AG2-369 GEN
Solar/Wind Harmer
14.595
316315AB2-025 C
Solar/Wind Harmer
0.256
315814AE2-033 C
Solar/Wind Harmer
24.917
3143316POE
Solar/Wind Harmer
1.232
957871AF2-081 GEN
Solar/Wind Harmer
15.244
319010AE1-072 C
Solar/Wind Harmer
1.539
3146406KITTY HAWK
Solar/Wind Harmer
0.038
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.164
315835AF2-110_GEN
Solar/Wind Harmer
2.081
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.208
316311AC2-079 GEN
Solar/Wind Harmer
8.702
3146486SUNBURY
Solar/Wind Harmer
0.302
3146486SUNBURY
Solar/Wind Harmer
0.302
316321Z2-027
Solar/Wind Harmer
0.056
3146396TANGLEW
Solar/Wind Harmer
0.833
3145176PASQUOTANK
Solar/Wind Harmer
0.187
971445AH1-216 GEN
Solar/Wind Harmer
21.042
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.294
3130156CHOWAN
Solar/Wind Harmer
0.294
972265AH1-717 GEN
Adder
22.85
3151201GRAVEL4
Adder
21.42
3151191GRAVEL3
Adder
21.149
3151211GRAVEL5
Adder
21.149
316369SG1_INVT
Solar/Wind Harmer
0.011
315816AE2-034 GEN
Solar/Wind Harmer
1.242
316132AB2-190 GEN1
Solar/Wind Harmer
1.538
3130546PLYMOUTH
Solar/Wind Harmer
0.286
965291AG1-394 GEN
Solar/Wind Harmer
1.269
315732AD1-074 GEN1
Solar/Wind Harmer
1.639
315733AD1-074 GEN2
Solar/Wind Harmer
1.639
315735AD1-075 GEN1
Solar/Wind Harmer
0.82
3145893MURPHYS
Solar/Wind Harmer
0.765
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
970601AG2-382 GEN
Solar/Wind Harmer
10.575
316087AB2-174 GEN
Solar/Wind Harmer
0.008
3146043SEABORD
Solar/Wind Harmer
0.28
3145513AHOSKIE
Solar/Wind Harmer
0.586
3145513AHOSKIE
Solar/Wind Harmer
0.28
315607AA1-063A GEN
Solar/Wind Harmer
0.572
3145683EARLEYS
Solar/Wind Harmer
0.558
3145683EARLEYS
Solar/Wind Harmer
0.279
3145683EARLEYS
Solar/Wind Harmer
0.279
315652AC1-086 GEN
Solar/Wind Harmer
30.678
3137643SOCKMAN
Solar/Wind Harmer
1.111
3145796HORNRTN
Solar/Wind Harmer
0.88
3145796HORNRTN
Solar/Wind Harmer
0.11
3146033SCOT NK
Solar/Wind Harmer
1.084
970831AG2-522 GEN
Solar/Wind Harmer
11.448
3138283WHITEMARSH
Solar/Wind Harmer
0.061
316005AA1-067
Solar/Wind Harmer
0.28
3145746EVERETS
Solar/Wind Harmer
1.039
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
970181AG2-120 GEN
Solar/Wind Harmer
3.25
957861AF2-080 GEN
Solar/Wind Harmer
11.129
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.255
3145573BETHELC
Solar/Wind Harmer
0.255
971167AH1-042 GEN
Solar/Wind Harmer
22.645
315976AC1-164 GENA
Solar/Wind Harmer
26.291
316169AC1-164_GENC
Solar/Wind Harmer
22.713
315975AC1-164 GENB
Solar/Wind Harmer
0.778
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
971443AH1-215 GEN
Solar/Wind Harmer
4.236
3144303KENBRDG
Solar/Wind Harmer
0.201
970683AG2-441 GEN
Solar/Wind Harmer
16.616
970681AG2-440 GEN
Solar/Wind Harmer
13.292
946301AF1-294 GEN
Solar/Wind Harmer
4.868
961791AG1-021 GEN
Solar/Wind Harmer
2.368
3143873LANEXA
Solar/Wind Harmer
0.148
315657AE1-056 GEN
Solar/Wind Harmer
8.449
316118AC1-105 GEN
Solar/Wind Harmer
0.629
970189AG2-124 GEN
Solar/Wind Harmer
7.213
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.048
3147173SINAI
Solar/Wind Harmer
0.24
3147243WELCO
Solar/Wind Harmer
0.15
316312AB1-027
Solar/Wind Harmer
0.429
3141913WHIT STONE
Solar/Wind Harmer
0.234
3138133OCRAN
Solar/Wind Harmer
0.069
3141783LANCAST
Solar/Wind Harmer
0.137
3141783LANCAST
Solar/Wind Harmer
0.091
962981AG1-147 GEN
Solar/Wind Harmer
8.172
970285AG2-188 GEN
Solar/Wind Harmer
17.223
971845AH1-439 GEN
Solar/Wind Harmer
9.707
970327AG2-215 GEN
Solar/Wind Harmer
7.016
970865AG2-541 GEN
Solar/Wind Harmer
7.314
316123AC1-075 GEN
Solar/Wind Harmer
0.262
970165AG2-112 GEN
Solar/Wind Harmer
1.554
970163AG2-111 GEN
Solar/Wind Harmer
1.483
3141813NORNECK
Solar/Wind Harmer
0.191
972205AH1-687 GEN
Adder
7.916
971447AH1-217 GEN
Solar/Wind Harmer
4.969
270494AE1-108_GEN
Solar/Wind Harmer
1.845
972189AH1-679 GEN
Adder
2.488
316223AC1-118
Solar/Wind Harmer
0.103
972193AH1-681 GEN
Adder
2.949
316164AC1-076 GEN
Solar/Wind Helper
1.496
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
3151031BRUNSWICKG2
50/50
4.373
3151101ELIZAR3
50/50
30.305
3150861SPRUNCD
50/50
1.461
3151161SURRY 1
50/50
11.304
970917AG2-570 GEN
Solar/Wind Harmer
28.408
315773AC2-141 GEN
Solar/Wind Harmer
11.382
944581AF1-123 GEN
Solar/Wind Harmer
69.733
944601AF1-125 GEN
Solar/Wind Harmer
68.658
3144873MCLAUGH
Solar/Wind Harmer
0.008
3146456SLIGO L269
Solar/Wind Harmer
0.306
971153AH1-033 GEN
Solar/Wind Harmer
3.534
3144536CHRHLND
Solar/Wind Harmer
0.046
316320Y1-086
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
6.41
316083AB2-161 GEN
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
3.204
315813AE1-149 C
Solar/Wind Harmer
16.153
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
0.12
3146626S HERTFORD
Solar/Wind Harmer
0.299
315839AE2-212 C
Solar/Wind Harmer
0.002
3145273HOLLAND
Solar/Wind Harmer
0.223
316313AB2-026
Solar/Wind Harmer
0.186
316258AE1-075 C
Solar/Wind Harmer
0.223
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.463
965281AG1-393 GEN
Solar/Wind Harmer
3.139
3151221GRAVEL6
Adder
21.396
3151171GRAVELC
Adder
4.116
3146376EDENTON
Solar/Wind Harmer
0.294
961611AG1-000B GEN
Solar/Wind Harmer
7.797
316365GEN2_N
Solar/Wind Harmer
0.655
315614AA2-178 GEN
Solar/Wind Harmer
1.657
315778AD1-151 GEN
Solar/Wind Harmer
23.065
3156081AA2-088 GEN
Solar/Wind Harmer
0.007
970129AG2-093 GEN
Solar/Wind Harmer
17.309
316478AD1-087 GEN
Solar/Wind Harmer
0.999
316486AD2-202 GEN
Solar/Wind Harmer
0.293
971157AH1-035 GEN
Solar/Wind Harmer
3.43
315737AD1-076 GEN
Solar/Wind Harmer
3.669
3144216WINCHST
Adder
1.072
970133AG2-095 GEN
Solar/Wind Harmer
2.723
3145893MURPHYS
Solar/Wind Harmer
0.474
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
957521AF2-046 GEN
Solar/Wind Harmer
21.052
961681AG1-008 GEN
Solar/Wind Harmer
21.052
3150921YORKTN3
Adder
7.103
3146173TUNIS
Solar/Wind Harmer
0.281
313506AB2-031 GEN
Solar/Wind Harmer
0.867
3156021HOLLOMANSOL
Solar/Wind Harmer
1.274
316463AE2-346 GEN
Solar/Wind Harmer
0.241
316140AB2-099
Solar/Wind Harmer
0.1
962331AG1-082 GEN
Solar/Wind Harmer
2.99
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3146263WOODLND
Solar/Wind Harmer
0.278
3147043LAWRENC
Solar/Wind Harmer
0.166
316317KELFORD C
Solar/Wind Harmer
0.027
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
1.1
3145796HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
3143096IRON208
Adder
1.124
316382AG1-145 C
Solar/Wind Harmer
0.002
316210AC1-098 GEN
Solar/Wind Harmer
2.485
3145933PARMELE
Solar/Wind Harmer
0.265
966801AG1-551 GEN
Solar/Wind Harmer
3.091
3142946ENON
Solar/Wind Harmer
0.089
315724AD1-057 GEN
Solar/Wind Harmer
0.985
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316327AA2-057 GEN
Solar/Wind Harmer
0.393
970909AG2-566 GEN
Solar/Wind Harmer
2.748
316131AB2-060 GEN
Solar/Wind Harmer
0.81
3146233WITAKRS
Solar/Wind Harmer
1.286
3146233WITAKRS
Solar/Wind Harmer
0.174
3138543CONSLDL
Solar/Wind Harmer
0.169
964241AG1-285 GEN
Solar/Wind Harmer
17.051
3146073TAR RVR
Solar/Wind Harmer
0.255
3146083TARBORO
Solar/Wind Harmer
0.255
970293AG2-193 GEN
Solar/Wind Harmer
2.717
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
315785AD2-033 C
Solar/Wind Harmer
2.056
961601AG1-000A GEN
Solar/Wind Harmer
17.946
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.252
971623AH1-311 GEN
Solar/Wind Harmer
0.505
970257AG2-171 GEN
Solar/Wind Harmer
8.061
959311AF2-222 GEN
Solar/Wind Harmer
22.323
963181AG1-167 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3147133PAMPLIN
Solar/Wind Harmer
0.769
971193AH1-056 GEN
Solar/Wind Harmer
14.916
3141843SHACKLE
Adder
1.244
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3141766HARMONY
Solar/Wind Harmer
3.224
316156AD2-030 GEN
Solar/Wind Harmer
0.179
3141873WAN 176
Solar/Wind Harmer
4.293
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
10.242
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3142416OLDCHRC
Solar/Wind Harmer
2.323
3146926FARMVIL
Solar/Wind Harmer
0.141
971683AH1-343 GEN
Solar/Wind Harmer
8.112
962971AG1-146 GEN
Solar/Wind Harmer
3.502
316283AC2-100 C
Solar/Wind Harmer
0.428
316473AC1-191 GEN
Solar/Wind Harmer
0.734
970009AG2-005 GEN
Solar/Wind Harmer
1.596
3146776BUCKING
Solar/Wind Harmer
0.076
316404AE1-155 C
Solar/Wind Harmer
0.046
3150351NORNECKC2
Adder
1.933
970221AG2-151 GEN
Solar/Wind Harmer
9.113
971781AH1-399 GEN
Solar/Wind Harmer
0.197
3141906WESTMOR
Solar/Wind Harmer
0.057
270197AD1-017 GEN1
Solar/Wind Harmer
0.888
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.176
972255AH1-712 GEN
Adder
66.009
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
970737AG2-469 GEN
Solar/Wind Harmer
5.167
958131AF2-107 GEN
Solar/Wind Harmer
3.333
316044AC1-158 PL1
Solar/Wind Helper
2.198
316450AC1-158 RIC
Solar/Wind Helper
0.586
3147666LOUISA
Solar/Wind Helper
0.715
316170AC1-121 GEN2
Solar/Wind Helper
0.429
3141196NOKESVL
Solar/Wind Helper
1.038
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.311
226910AB2-157 C
Solar/Wind Helper
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
12.487
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.918
TVALTFEXP_TVA->PJM
CLTF
6.285
CPLELTFEXP_CPLE->PJM
CLTF
16.793
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.855
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.654
MECLTFEXP_MEC->PJM
CLTF
6.28
SIGELTFEXP_SIGE->PJM
CLTF
0.191
NYPJM->LTFIMP_NY
CLTF
3.567
LGEELTFEXP_LGEE->PJM
CLTF
2.341
WECLTFEXP_WEC->PJM
CLTF
1.189
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.63 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6092.43
MW Contribution:49.56
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
49.56
315243AE2-183_GT3
50/50
5.597
3151051BRUNSWICKS1
50/50
9.142
3151021BRUNSWICKG1
50/50
4.405
971451AH1-221 GEN
50/50
13.378
3150981CHESPKA
50/50
4.118
3150851SPRUNCC
50/50
1.485
3152331SURRY 2
50/50
12.49
3143226MDLTHAN
Solar/Wind Harmer
-0.042
940641AE2-051 GEN
Solar/Wind Harmer
37.221
939411AE1-173 GEN
Solar/Wind Harmer
192.62
3143526WINTERP
Solar/Wind Harmer
-0.197
970919AG2-571 GEN
Solar/Wind Harmer
11.445
970087AG2-069 GEN
Solar/Wind Harmer
33.76
316294AC1-161 GEN
Solar/Wind Harmer
11.456
944591AF1-124 GEN
Solar/Wind Harmer
160.67
316375AC2-012 GEN
Solar/Wind Harmer
12.086
316388AE2-253 GEN
Solar/Wind Harmer
2.349
3146456SLIGO L269
Solar/Wind Harmer
-0.035
316246AF1-032 C
Solar/Wind Harmer
0.701
970659AG2-427 GEN
Solar/Wind Harmer
18.316
316381AD1-082 GEN
Solar/Wind Harmer
3.162
970661AG2-428 GEN
Solar/Wind Harmer
36.628
316093AE2-104_GEN
Solar/Wind Harmer
10.019
316072AD1-144
Solar/Wind Harmer
0.693
3146516WINFALL
Solar/Wind Harmer
-0.11
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.136
957481AF2-042 GEN
Solar/Wind Harmer
105.713
315800Z1-036_GEN1
Solar/Wind Harmer
8.332
316303AF2-085
50/50
6.608
315244AE2-183_ST
50/50
9.677
963041AG1-153 GEN
50/50
8.919
315779AE2-040
50/50
4.458
3151081ELIZAR1
50/50
30.271
3151091ELIZAR2
50/50
29.745
941591AE2-156 GEN
50/50
27.651
3152611GOSPORTB
50/50
4.2
3152621GOSPORTC
50/50
3.565
3152601GOSPORTA
50/50
3.288
971285AH1-108 GEN
50/50
2.43
972263AH1-716 GEN
50/50
172.931
941031AE2-094 GEN
Solar/Wind Harmer
73.475
944011AF1-069 GEN
Solar/Wind Harmer
23.022
970673AG2-436 GEN
Solar/Wind Harmer
80.77
970673AG2-436 GEN
Solar/Wind Harmer
40.896
316233AE1-074 FULL
Solar/Wind Harmer
1.026
971281AH1-106 GEN
Solar/Wind Harmer
6.195
971283AH1-107 GEN
Solar/Wind Harmer
6.195
971967AH1-528 GEN
Solar/Wind Harmer
71.103
970085AG2-068 GEN
Solar/Wind Harmer
22.506
970581AG2-369 GEN
Solar/Wind Harmer
19.356
316315AB2-025 C
Solar/Wind Harmer
0.968
315814AE2-033 C
Solar/Wind Harmer
33.285
3143316POE
Solar/Wind Harmer
-0.139
957871AF2-081 GEN
Solar/Wind Harmer
17.401
319010AE1-072 C
Solar/Wind Harmer
7.024
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
1.044
313526AB2-022
Solar/Wind Harmer
0.93
315833AF1-017_GEN
Solar/Wind Harmer
6.546
316349AD2-085 GEN
Solar/Wind Harmer
3.065
316311AC2-079 GEN
Solar/Wind Harmer
17.383
315835AF2-110_GEN
Solar/Wind Harmer
4.308
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
316321Z2-027
Solar/Wind Harmer
0.926
3146396TANGLEW
Solar/Wind Harmer
0.632
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
971445AH1-216 GEN
Solar/Wind Harmer
21.053
315611Z1-036_GEN2
Solar/Wind Harmer
8.332
972265AH1-717 GEN
Adder
23.171
3151201GRAVEL4
Adder
21.721
3151191GRAVEL3
Adder
21.446
3151211GRAVEL5
Adder
21.446
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316369SG1_INVT
Solar/Wind Harmer
5.9
315816AE2-034 GEN
Solar/Wind Harmer
2.66
316132AB2-190 GEN1
Solar/Wind Harmer
3.31
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
965291AG1-394 GEN
Solar/Wind Harmer
2.878
315732AD1-074 GEN1
Solar/Wind Harmer
6.549
315733AD1-074 GEN2
Solar/Wind Harmer
6.549
315735AD1-075 GEN1
Solar/Wind Harmer
3.275
946281AF1-292 GEN
Solar/Wind Harmer
0.723
316318V4-068
Solar/Wind Harmer
0.802
3145893MURPHYS
Solar/Wind Harmer
-0.086
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
14.071
316087AB2-174 GEN
Solar/Wind Harmer
4.56
3146043SEABORD
Solar/Wind Harmer
-0.032
3145513AHOSKIE
Solar/Wind Harmer
0.277
961941AG1-037 GEN
Solar/Wind Harmer
0.239
3145513AHOSKIE
Solar/Wind Harmer
-0.032
315607AA1-063A GEN
Solar/Wind Harmer
3.21
3145683EARLEYS
Solar/Wind Harmer
-0.063
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.032
315652AC1-086 GEN
Solar/Wind Harmer
35.613
3137643SOCKMAN
Solar/Wind Harmer
-0.126
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.122
970831AG2-522 GEN
Solar/Wind Harmer
15.209
957831AF2-077 GEN
Solar/Wind Harmer
0.905
3138283WHITEMARSH
Solar/Wind Harmer
0.047
316005AA1-067
Solar/Wind Harmer
0.599
3145746EVERETS
Solar/Wind Harmer
-0.117
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
970181AG2-120 GEN
Solar/Wind Harmer
3.889
957861AF2-080 GEN
Solar/Wind Harmer
12.812
971167AH1-042 GEN
Solar/Wind Harmer
28.174
316239AB2-077_GEN
Solar/Wind Harmer
0.879
316238AB2-078_GEN
Solar/Wind Harmer
0.879
316420AA1-050 GEN
Solar/Wind Harmer
3.326
315976AC1-164 GENA
Solar/Wind Harmer
30.748
316169AC1-164_GENC
Solar/Wind Harmer
26.564
315975AC1-164 GENB
Solar/Wind Harmer
0.91
3142433PROV 92
Adder
0.503
3142433PROV 92
Adder
0.503
316319Z2-044 C
Solar/Wind Harmer
1.605
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
972205AH1-687 GEN
Adder
7.988
972189AH1-679 GEN
Adder
2.712
972193AH1-681 GEN
Adder
3.018
316164AC1-076 GEN
Solar/Wind Helper
1.525
316411AF1-147_GEN1
Solar/Wind Helper
0.816
316415AF1-147_GEN2
Solar/Wind Helper
0.816
3138216PACIFIC
Solar/Wind Helper
0.04
3151031BRUNSWICKG2
50/50
4.405
3151101ELIZAR3
50/50
30.659
3150861SPRUNCD
50/50
1.485
3151161SURRY 1
50/50
11.463
970917AG2-570 GEN
Solar/Wind Harmer
90.418
315773AC2-141 GEN
Solar/Wind Harmer
14.817
944581AF1-123 GEN
Solar/Wind Harmer
160.093
944601AF1-125 GEN
Solar/Wind Harmer
157.595
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.035
971153AH1-033 GEN
Solar/Wind Harmer
4.235
3144536CHRHLND
Solar/Wind Harmer
-0.005
315813AE1-149 C
Solar/Wind Harmer
21.552
970659AG2-427 GEN
Solar/Wind Harmer
3.246
316083AB2-161 GEN
Solar/Wind Harmer
5.596
970661AG2-428 GEN
Solar/Wind Harmer
6.491
316320Y1-086
Solar/Wind Harmer
2.02
316435W1029_GEN3
Solar/Wind Harmer
6.192
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.013
315839AE2-212 C
Solar/Wind Harmer
1.026
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3145273HOLLAND
Solar/Wind Harmer
-0.025
965281AG1-393 GEN
Solar/Wind Harmer
4.197
3151221GRAVEL6
Adder
21.696
3151171GRAVELC
Adder
4.174
316313AB2-026
Solar/Wind Harmer
0.903
316258AE1-075 C
Solar/Wind Harmer
0.813
316405AF2-144 C
Solar/Wind Harmer
0.857
3143336POWHATN
Solar/Wind Harmer
3.376
3146376EDENTON
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
7.019
316365GEN2_N
Solar/Wind Harmer
2.232
315778AD1-151 GEN
Solar/Wind Harmer
28.5
315614AA2-178 GEN
Solar/Wind Harmer
3.547
970129AG2-093 GEN
Solar/Wind Harmer
18.408
3156081AA2-088 GEN
Solar/Wind Harmer
10.555
971157AH1-035 GEN
Solar/Wind Harmer
4.057
3144216WINCHST
Adder
1.088
970133AG2-095 GEN
Solar/Wind Harmer
3.645
316478AD1-087 GEN
Solar/Wind Harmer
2.805
316486AD2-202 GEN
Solar/Wind Harmer
0.821
315737AD1-076 GEN
Solar/Wind Harmer
6.155
966621AG1-532 GEN
Solar/Wind Harmer
0.655
3150921YORKTN3
Adder
7.214
3145893MURPHYS
Solar/Wind Harmer
0.225
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
957521AF2-046 GEN
Solar/Wind Harmer
25.297
961681AG1-008 GEN
Solar/Wind Harmer
25.297
3146173TUNIS
Solar/Wind Harmer
-0.032
3156021HOLLOMANSOL
Solar/Wind Harmer
4.291
313506AB2-031 GEN
Solar/Wind Harmer
2.559
316463AE2-346 GEN
Solar/Wind Harmer
0.515
316140AB2-099
Solar/Wind Harmer
0.215
962331AG1-082 GEN
Solar/Wind Harmer
3.978
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3146263WOODLND
Solar/Wind Harmer
-0.032
3143096IRON208
Adder
1.169
3143096IRON208
Adder
1.146
3147043LAWRENC
Solar/Wind Harmer
-0.019
316317KELFORD C
Solar/Wind Harmer
1.473
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.124
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316382AG1-145 C
Solar/Wind Harmer
0.939
3142946ENON
Solar/Wind Harmer
-0.01
316210AC1-098 GEN
Solar/Wind Harmer
4.769
3145933PARMELE
Solar/Wind Harmer
-0.03
966801AG1-551 GEN
Solar/Wind Harmer
3.764
315724AD1-057 GEN
Solar/Wind Harmer
1.713
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
2.98
970293AG2-193 GEN
Solar/Wind Harmer
3.658
970909AG2-566 GEN
Solar/Wind Harmer
2.77
316131AB2-060 GEN
Solar/Wind Harmer
3.147
3142433PROV 92
Adder
0.503
3142433PROV 92
Adder
0.503
3146233WITAKRS
Solar/Wind Harmer
0.608
3146233WITAKRS
Solar/Wind Harmer
-0.02
3138543CONSLDL
Solar/Wind Harmer
-0.019
3146073TAR RVR
Solar/Wind Harmer
-0.029
3146083TARBORO
Solar/Wind Harmer
-0.029
964241AG1-285 GEN
Solar/Wind Harmer
22.639
3141843SHACKLE
Adder
1.273
3144293JTRSVLE
Adder
0.792
3150351NORNECKC2
Adder
2.004
972255AH1-712 GEN
Adder
67.55
316044AC1-158 PL1
Solar/Wind Helper
2.235
316450AC1-158 RIC
Solar/Wind Helper
0.596
3147666LOUISA
Solar/Wind Helper
0.727
316170AC1-121 GEN2
Solar/Wind Helper
0.437
3141196NOKESVL
Solar/Wind Helper
1.052
3132273ORANGE
Solar/Wind Helper
0.048
227287AC2-120 GEN
Solar/Wind Helper
0.315
226910AB2-157 C
Solar/Wind Helper
0.013
3151171GRAVELC
Adder
3.174
3143336POWHATN
Solar/Wind Harmer
3.972
3130156CHOWAN
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
16.45
315671AE2-027_GEN
Solar/Wind Harmer
24.982
971647AH1-324 GEN
Solar/Wind Harmer
16.587
316023GEN1_S
Solar/Wind Harmer
2.232
971069AG2-661 GEN
Solar/Wind Harmer
5.205
3145663CRESWEL
Solar/Wind Harmer
-0.092
971163AH1-040 GEN
Solar/Wind Harmer
30.822
316458AB2-190 GEN2
Solar/Wind Harmer
3.31
315693AD1-088 GEN
Solar/Wind Harmer
16.359
970129AG2-093 GEN
Solar/Wind Harmer
7.456
962491AG1-098 GEN
Solar/Wind Harmer
21.758
3138126ROCKLANDING
Solar/Wind Harmer
0.099
960081AF2-299 GEN
Solar/Wind Harmer
3.629
3145893MURPHYS
Solar/Wind Harmer
-0.128
3145893MURPHYS
Solar/Wind Harmer
0.955
3142543TWELFTH
Solar/Wind Harmer
-0.003
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
8.041
3146173TUNIS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.032
316011AB1-132 GEN
Solar/Wind Harmer
6.623
962571AG1-106 GEN
Solar/Wind Harmer
4.551
971795AH1-408 GEN
Solar/Wind Harmer
23.72
3146263WOODLND
Solar/Wind Harmer
-0.032
971317AH1-138 GEN
Solar/Wind Harmer
3.934
316190AA2-174 GEN
Solar/Wind Harmer
0.386
3143096IRON208
Adder
1.169
3147043LAWRENC
Adder
2.523
316336AC2-165 C
Solar/Wind Harmer
5.44
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316159AE1-175 C
Solar/Wind Harmer
0.836
944631AF1-128 GEN
Adder
131.354
316174AB2-169 GEN
Solar/Wind Harmer
4.773
315687AD1-152 GEN
Solar/Wind Harmer
3.672
316212AC1-099_GEN
Solar/Wind Harmer
2.649
316129AC1-054 GEN
Solar/Wind Harmer
2.658
971065AG2-659 GEN
Solar/Wind Harmer
15.113
3146293MARTNCO
Solar/Wind Harmer
0.186
315722AD1-056 GEN
Solar/Wind Harmer
3.115
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
316494AC1-189 GEN
Solar/Wind Harmer
3.151
316237AB2-079_GEN
Solar/Wind Harmer
0.879
3142433PROV 92
Solar/Wind Harmer
-0.116
3142433PROV 92
Adder
0.503
3142433PROV 92
Adder
0.503
3146233WITAKRS
Solar/Wind Harmer
-0.115
961671AG1-007 GEN
Solar/Wind Harmer
0.366
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.86
3141843SHACKLE
Adder
1.273
3144293JTRSVLE
Adder
0.792
3150351NORNECKC2
Adder
1.971
972277AH1-723 GEN
Adder
78.716
316045AC1-158 PL2
Solar/Wind Helper
7.153
3147666LOUISA
Solar/Wind Helper
1.265
316192AB2-158 GEN
Solar/Wind Helper
2.08
316254AC1-120 GEN1
Solar/Wind Helper
1.311
316006AB2-029 C
Solar/Wind Helper
0.132
970533AG2-339 GEN
50/50
31.002
970531AG2-338 GEN
50/50
12.401
315242AE2-183_GT2
50/50
5.597
315241AE2-183_GT1
50/50
5.563
972185AH1-677 GEN
50/50
20.179
3151041BRUNSWICKG3
50/50
4.405
972187AH1-678 GEN
50/50
10.108
3150991CHESPKB
50/50
3.455
3150991CHESPKB
50/50
3.372
971223AH1-071 GEN
Solar/Wind Harmer
5.22
3143526WINTERP
Solar/Wind Harmer
-0.197
970933AG2-581 GEN
Solar/Wind Harmer
34.405
3144356SAPONY
Solar/Wind Harmer
1.252
316185AD1-033 GEN
Solar/Wind Harmer
3.69
3142956BIRDNECK
Solar/Wind Harmer
1.875
316316AC1-027 C
Solar/Wind Harmer
1.073
316036AC1-147 C
Solar/Wind Harmer
0.942
3145506HICKORY
Solar/Wind Harmer
-0.139
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.349
316018AA1-139 ULT2
Solar/Wind Harmer
2.981
316017AA1-139 ULT1
Solar/Wind Harmer
2.816
3137176SLIGO L2192
Solar/Wind Harmer
-0.137
3146456SLIGO L269
Solar/Wind Harmer
4.103
3130086AYDLETT
Solar/Wind Harmer
-0.138
970657AG2-426 GEN
Solar/Wind Harmer
10.774
970657AG2-426 GEN
Solar/Wind Harmer
2.253
3146386ELIZ CT
Solar/Wind Harmer
-0.034
316431W1029_GEN1
Solar/Wind Harmer
6.192
316433W1029_GEN2
Solar/Wind Harmer
6.192
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
316236AE1-162_GEN
Solar/Wind Harmer
1.027
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
970099AG2-077 GEN
Solar/Wind Harmer
42.285
315742AE1-103 GEN
Solar/Wind Harmer
3.51
3146376EDENTON
Solar/Wind Harmer
0.992
3146376EDENTON
Solar/Wind Harmer
0.992
316240AF1-291 C
Solar/Wind Harmer
1
316033AB2-134 GEN
Solar/Wind Harmer
10.649
315697AD1-025 GEN
Solar/Wind Harmer
6.679
944641AF1-129 GEN
Adder
139.506
316065AD1-022 GEN
Solar/Wind Harmer
16.121
3145893MURPHYS
Solar/Wind Harmer
0.898
3145893MURPHYS
Solar/Wind Harmer
-0.058
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316181AB2-040 GEN
Solar/Wind Harmer
4.441
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.174
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
966811AG1-552 GEN
Solar/Wind Harmer
3.528
3145593CAROLNA
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145783HORNRTN
Solar/Wind Harmer
3.7
3145783HORNRTN
Solar/Wind Harmer
2.96
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.37
3142946ENON
Solar/Wind Harmer
-0.003
316274AC1-208 GEN
Solar/Wind Harmer
3.264
3145933PARMELE
Solar/Wind Harmer
-0.06
3145933PARMELE
Solar/Wind Harmer
-0.03
971741AH1-377 GEN
Solar/Wind Harmer
34.86
3142366NRTHEST
Adder
0.864
939181AE1-148 GEN
Solar/Wind Harmer
16.686
3150691DARBY 3
Adder
18.921
3150701DARBY 4
Adder
18.877
3150681DARBY 2
Adder
18.855
3150671DARBY 1
Adder
18.833
313527AB2-043 GEN
Solar/Wind Harmer
4.747
970301AG2-198 GEN
Solar/Wind Harmer
14.587
3145493TOT1
Solar/Wind Harmer
0.448
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.179
3144293JTRSVLE
Adder
0.792
3144293JTRSVLE
Adder
0.667
3142296MT RD221
Adder
0.77
3150341NORNECKC1
Adder
2.071
3150341NORNECKC1
Adder
2.054
316447AC1-158 HLD
Solar/Wind Helper
4.918
315651AD1-115 GEN
Solar/Wind Helper
0.954
226929AD2-058 GEN
Solar/Wind Helper
0.092
316075AC2-137 C
Solar/Wind Harmer
0.319
LAGNLTFEXP_LAGN->PJM
CLTF
12.593
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.232
TVALTFEXP_TVA->PJM
CLTF
6.338
CPLELTFEXP_CPLE->PJM
CLTF
16.935
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.417
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.824
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.839
MECLTFEXP_MEC->PJM
CLTF
6.331
SIGELTFEXP_SIGE->PJM
CLTF
0.193
NYPJM->LTFIMP_NY
CLTF
3.61
LGEELTFEXP_LGEE->PJM
CLTF
2.36
WECLTFEXP_WEC->PJM
CLTF
1.198
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.097

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.23 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6076.8
MW Contribution:49.61
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
6.615
315244AE2-183_ST
50/50
10.085
963041AG1-153 GEN
50/50
9.293
3151081ELIZAR1
50/50
32.533
3151091ELIZAR2
50/50
31.968
941591AE2-156 GEN
50/50
29.713
3152611GOSPORTB
50/50
4.513
3152621GOSPORTC
50/50
3.83
3152601GOSPORTA
50/50
3.533
315779AE2-040
50/50
4.628
972263AH1-716 GEN
50/50
190.384
941031AE2-094 GEN
Solar/Wind Harmer
76.612
944011AF1-069 GEN
Solar/Wind Harmer
24.005
970673AG2-436 GEN
Solar/Wind Harmer
84.191
970673AG2-436 GEN
Solar/Wind Harmer
42.628
971967AH1-528 GEN
Solar/Wind Harmer
74.07
316233AE1-074 FULL
Solar/Wind Harmer
1.025
971281AH1-106 GEN
Solar/Wind Harmer
6.19
971283AH1-107 GEN
Solar/Wind Harmer
6.19
970085AG2-068 GEN
Solar/Wind Harmer
23.438
3151031BRUNSWICKG2
50/50
4.589
3151101ELIZAR3
50/50
32.949
3151161SURRY 1
50/50
12.195
315773AC2-141 GEN
Solar/Wind Harmer
16.075
944581AF1-123 GEN
Solar/Wind Harmer
172.322
944601AF1-125 GEN
Solar/Wind Harmer
169.633
970917AG2-570 GEN
Solar/Wind Harmer
94.165
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.037
971153AH1-033 GEN
Solar/Wind Harmer
4.547
3144536CHRHLND
Solar/Wind Harmer
-0.006
316320Y1-086
Solar/Wind Harmer
2.165
316435W1029_GEN3
Solar/Wind Harmer
6.628
3146516WINFALL
Solar/Wind Harmer
-0.036
3145336SMITFLD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.036
970661AG2-428 GEN
Solar/Wind Harmer
6.819
316083AB2-161 GEN
Solar/Wind Harmer
5.857
3145273HOLLAND
Solar/Wind Harmer
-0.027
970659AG2-427 GEN
Solar/Wind Harmer
3.393
315813AE1-149 C
Solar/Wind Harmer
22.383
3151221GRAVEL6
Adder
23.081
3151171GRAVELC
Adder
4.441
3146376EDENTON
Solar/Wind Harmer
-0.036
961611AG1-000B GEN
Solar/Wind Harmer
7.432
3144216WINCHST
Adder
1.179
3150921YORKTN3
Adder
7.837
315614AA2-178 GEN
Solar/Wind Harmer
3.774
315839AE2-212 C
Solar/Wind Harmer
1.048
316365GEN2_N
Solar/Wind Harmer
2.328
315778AD1-151 GEN
Solar/Wind Harmer
29.865
971157AH1-035 GEN
Solar/Wind Harmer
4.308
965281AG1-393 GEN
Solar/Wind Harmer
4.3
315737AD1-076 GEN
Solar/Wind Harmer
6.532
3156081AA2-088 GEN
Solar/Wind Harmer
11.148
3150861SPRUNCD
Adder
1.401
970129AG2-093 GEN
Solar/Wind Harmer
19.191
3146206CASHIE
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.237
3145893MURPHYS
Solar/Wind Harmer
-0.034
957521AF2-046 GEN
Solar/Wind Harmer
26.697
961681AG1-008 GEN
Solar/Wind Harmer
26.697
316382AG1-145 C
Solar/Wind Harmer
1.02
3146173TUNIS
Solar/Wind Harmer
-0.034
3156021HOLLOMANSOL
Solar/Wind Harmer
4.534
966621AG1-532 GEN
Solar/Wind Harmer
0.682
316478AD1-087 GEN
Solar/Wind Harmer
2.909
316486AD2-202 GEN
Solar/Wind Harmer
0.852
316463AE2-346 GEN
Solar/Wind Harmer
0.543
316140AB2-099
Solar/Wind Harmer
0.226
962331AG1-082 GEN
Solar/Wind Harmer
4.197
970133AG2-095 GEN
Solar/Wind Harmer
3.773
316313AB2-026
Solar/Wind Harmer
0.901
316258AE1-075 C
Solar/Wind Harmer
0.811
316405AF2-144 C
Solar/Wind Harmer
0.856
3143336POWHATN
Solar/Wind Harmer
3.371
3146263WOODLND
Solar/Wind Harmer
-0.033
313506AB2-031 GEN
Solar/Wind Harmer
2.672
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3145963POPLR C
Solar/Wind Harmer
-0.033
316317KELFORD C
Solar/Wind Harmer
1.55
3145823KELFORD
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.13
3145796HORNRTN
Solar/Wind Harmer
-0.033
3147043LAWRENC
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.01
3143096IRON208
Adder
1.188
3143096IRON208
Adder
1.164
316210AC1-098 GEN
Solar/Wind Harmer
5
3145933PARMELE
Solar/Wind Harmer
-0.032
966801AG1-551 GEN
Solar/Wind Harmer
3.962
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
315724AD1-057 GEN
Solar/Wind Harmer
1.79
316327AA2-057 GEN
Solar/Wind Harmer
3.117
3142433PROV 92
Adder
0.53
3142433PROV 92
Adder
0.53
3146233WITAKRS
Solar/Wind Harmer
0.636
3146233WITAKRS
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.03
3146083TARBORO
Solar/Wind Harmer
-0.03
3138543CONSLDL
Solar/Wind Harmer
-0.02
316131AB2-060 GEN
Solar/Wind Harmer
3.254
3141843SHACKLE
Adder
1.366
316203AE2-005 GEN
Solar/Wind Harmer
12.66
316280AD1-041 GEN
Solar/Wind Harmer
2.258
3144293JTRSVLE
Adder
0.813
3150351NORNECKC2
Adder
2.146
316044AC1-158 PL1
Solar/Wind Helper
2.186
316450AC1-158 RIC
Solar/Wind Helper
0.583
3147666LOUISA
Solar/Wind Helper
0.716
316170AC1-121 GEN2
Solar/Wind Helper
0.43
3141196NOKESVL
Solar/Wind Helper
1.041
3132273ORANGE
Solar/Wind Helper
0.048
227287AC2-120 GEN
Solar/Wind Helper
0.313
226910AB2-157 C
Solar/Wind Helper
0.013
970909AG2-566 GEN
Solar/Wind Harmer
2.713
970119AG2-088 GEN
50/50
49.614
315243AE2-183_GT3
50/50
5.833
3151051BRUNSWICKS1
50/50
9.525
3151021BRUNSWICKG1
50/50
4.589
971451AH1-221 GEN
50/50
13.939
3150981CHESPKA
50/50
4.425
3152331SURRY 2
50/50
13.773
3143226MDLTHAN
Solar/Wind Harmer
-0.042
940641AE2-051 GEN
Solar/Wind Harmer
39.09
939411AE1-173 GEN
Solar/Wind Harmer
203.387
316294AC1-161 GEN
Solar/Wind Harmer
12.429
3143526WINTERP
Solar/Wind Harmer
-0.197
944591AF1-124 GEN
Solar/Wind Harmer
172.943
970919AG2-571 GEN
Solar/Wind Harmer
11.92
316375AC2-012 GEN
Solar/Wind Harmer
12.985
970087AG2-069 GEN
Solar/Wind Harmer
35.157
316388AE2-253 GEN
Solar/Wind Harmer
2.523
3146456SLIGO L269
Solar/Wind Harmer
-0.037
316246AF1-032 C
Solar/Wind Harmer
0.751
316093AE2-104_GEN
Solar/Wind Harmer
10.699
316072AD1-144
Solar/Wind Harmer
0.743
3146516WINFALL
Solar/Wind Harmer
-0.118
3146516WINFALL
Solar/Wind Harmer
-0.036
3145336SMITFLD
Solar/Wind Harmer
-0.145
970661AG2-428 GEN
Solar/Wind Harmer
38.478
316381AD1-082 GEN
Solar/Wind Harmer
3.31
970659AG2-427 GEN
Solar/Wind Harmer
19.149
315800Z1-036_GEN1
Solar/Wind Harmer
8.901
3151171GRAVELC
Adder
3.377
3130156CHOWAN
Solar/Wind Harmer
-0.036
961611AG1-000B GEN
Solar/Wind Harmer
17.419
957481AF2-042 GEN
Solar/Wind Harmer
109.742
3138126ROCKLANDING
Solar/Wind Harmer
0.108
971647AH1-324 GEN
Solar/Wind Harmer
17.499
3145663CRESWEL
Solar/Wind Harmer
-0.097
971163AH1-040 GEN
Solar/Wind Harmer
32.791
316023GEN1_S
Solar/Wind Harmer
2.328
971069AG2-661 GEN
Solar/Wind Harmer
5.455
971317AH1-138 GEN
Solar/Wind Harmer
4.281
3150851SPRUNCC
Adder
1.401
316458AB2-190 GEN2
Solar/Wind Harmer
3.453
315671AE2-027_GEN
Solar/Wind Harmer
25.569
970129AG2-093 GEN
Solar/Wind Harmer
7.774
3146206CASHIE
Solar/Wind Harmer
-0.034
971547AH1-271 GEN
Solar/Wind Harmer
8.518
3145893MURPHYS
Solar/Wind Harmer
-0.135
3145893MURPHYS
Solar/Wind Harmer
1.008
315693AD1-088 GEN
Solar/Wind Harmer
16.949
316159AE1-175 C
Solar/Wind Harmer
0.909
3146173TUNIS
Solar/Wind Harmer
-0.034
962491AG1-098 GEN
Solar/Wind Harmer
22.532
960081AF2-299 GEN
Solar/Wind Harmer
3.783
3145683EARLEYS
Solar/Wind Harmer
-0.033
3143336POWHATN
Solar/Wind Harmer
3.966
3146263WOODLND
Solar/Wind Harmer
-0.033
316011AB1-132 GEN
Solar/Wind Harmer
6.928
962571AG1-106 GEN
Solar/Wind Harmer
4.76
3145963POPLR C
Solar/Wind Harmer
-0.033
316190AA2-174 GEN
Solar/Wind Harmer
0.404
971795AH1-408 GEN
Solar/Wind Harmer
24.687
3145823KELFORD
Solar/Wind Harmer
-0.033
316174AB2-169 GEN
Solar/Wind Harmer
5.041
3145796HORNRTN
Solar/Wind Harmer
-0.107
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145783HORNRTN
Solar/Wind Harmer
-0.033
3147043LAWRENC
Adder
2.624
3142543TWELFTH
Solar/Wind Harmer
-0.003
944631AF1-128 GEN
Adder
136.543
3143096IRON208
Adder
1.188
316212AC1-099_GEN
Solar/Wind Harmer
2.778
3146293MARTNCO
Solar/Wind Harmer
0.196
315687AD1-152 GEN
Solar/Wind Harmer
3.804
316129AC1-054 GEN
Solar/Wind Harmer
2.766
971065AG2-659 GEN
Solar/Wind Harmer
15.722
316336AC2-165 C
Solar/Wind Harmer
5.426
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
315722AD1-056 GEN
Solar/Wind Harmer
3.254
316494AC1-189 GEN
Solar/Wind Harmer
3.304
3142433PROV 92
Solar/Wind Harmer
-0.122
3142433PROV 92
Adder
0.53
3142433PROV 92
Adder
0.53
3146233WITAKRS
Solar/Wind Harmer
-0.12
961671AG1-007 GEN
Solar/Wind Harmer
0.384
3146083TARBORO
Solar/Wind Harmer
-0.03
3145493TOT1
Solar/Wind Harmer
0.9
316237AB2-079_GEN
Solar/Wind Harmer
0.91
971777AH1-397 GEN
Solar/Wind Harmer
3.531
3141843SHACKLE
Adder
1.366
3144293JTRSVLE
Adder
0.813
3150351NORNECKC2
Adder
2.111
316045AC1-158 PL2
Solar/Wind Helper
6.998
3147666LOUISA
Solar/Wind Helper
1.245
316192AB2-158 GEN
Solar/Wind Helper
2.049
316254AC1-120 GEN1
Solar/Wind Helper
1.291
316006AB2-029 C
Solar/Wind Helper
0.13
970533AG2-339 GEN
50/50
32.326
970531AG2-338 GEN
50/50
12.93
315242AE2-183_GT2
50/50
5.833
315241AE2-183_GT1
50/50
5.797
972185AH1-677 GEN
50/50
21.03
3151041BRUNSWICKG3
50/50
4.589
972187AH1-678 GEN
50/50
10.532
3150991CHESPKB
50/50
3.712
3150991CHESPKB
50/50
3.623
971223AH1-071 GEN
Solar/Wind Harmer
5.226
970933AG2-581 GEN
Solar/Wind Harmer
35.807
3143526WINTERP
Solar/Wind Harmer
-0.197
316185AD1-033 GEN
Solar/Wind Harmer
3.966
3142956BIRDNECK
Solar/Wind Harmer
2.015
316316AC1-027 C
Solar/Wind Harmer
1.153
316036AC1-147 C
Solar/Wind Harmer
1.012
3145506HICKORY
Solar/Wind Harmer
-0.149
3145506HICKORY
Solar/Wind Harmer
-0.09
3145506HICKORY
Solar/Wind Harmer
-0.022
316339AD2-160 GEN
Solar/Wind Harmer
2.523
316018AA1-139 ULT2
Solar/Wind Harmer
3.202
316017AA1-139 ULT1
Solar/Wind Harmer
3.024
3137176SLIGO L2192
Solar/Wind Harmer
-0.148
3146456SLIGO L269
Solar/Wind Harmer
4.406
3130086AYDLETT
Solar/Wind Harmer
-0.148
3144356SAPONY
Solar/Wind Harmer
1.299
3146386ELIZ CT
Solar/Wind Harmer
-0.037
316431W1029_GEN1
Solar/Wind Harmer
6.628
316433W1029_GEN2
Solar/Wind Harmer
6.628
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
316236AE1-162_GEN
Solar/Wind Harmer
1.097
3146626S HERTFORD
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
11.293
970657AG2-426 GEN
Solar/Wind Harmer
2.361
315742AE1-103 GEN
Solar/Wind Harmer
3.73
3146376EDENTON
Solar/Wind Harmer
1.058
3146376EDENTON
Solar/Wind Harmer
1.058
970099AG2-077 GEN
Solar/Wind Harmer
43.897
316033AB2-134 GEN
Solar/Wind Harmer
11.193
315697AD1-025 GEN
Solar/Wind Harmer
7.02
316065AD1-022 GEN
Solar/Wind Harmer
17.09
3145893MURPHYS
Solar/Wind Harmer
0.948
3145893MURPHYS
Solar/Wind Harmer
-0.061
316240AF1-291 C
Solar/Wind Harmer
1.017
3146173TUNIS
Solar/Wind Harmer
-0.034
3146173TUNIS
Solar/Wind Harmer
-0.034
944641AF1-129 GEN
Adder
141.653
316181AB2-040 GEN
Solar/Wind Harmer
4.638
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
316426AA2-053 GEN
Solar/Wind Harmer
3.327
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
-0.033
966811AG1-552 GEN
Solar/Wind Harmer
3.692
3145593CAROLNA
Solar/Wind Harmer
0.273
3145796HORNRTN
Solar/Wind Harmer
-0.097
3145783HORNRTN
Solar/Wind Harmer
3.873
3145783HORNRTN
Solar/Wind Harmer
3.098
3145783HORNRTN
Solar/Wind Harmer
0.968
3145783HORNRTN
Solar/Wind Harmer
0.387
3142946ENON
Solar/Wind Harmer
-0.003
3145933PARMELE
Solar/Wind Harmer
-0.063
3145933PARMELE
Solar/Wind Harmer
-0.032
316274AC1-208 GEN
Solar/Wind Harmer
3.418
971741AH1-377 GEN
Solar/Wind Harmer
35.868
939181AE1-148 GEN
Solar/Wind Harmer
17.303
3145493TOT1
Solar/Wind Harmer
0.469
3145453TOT5
Solar/Wind Harmer
0.282
3145603CNETO
Solar/Wind Harmer
0.188
316075AC2-137 C
Solar/Wind Harmer
0.818
313527AB2-043 GEN
Solar/Wind Harmer
4.909
316441AF1-014 GEN
Solar/Wind Harmer
2.024
3150691DARBY 3
Adder
18.946
3150701DARBY 4
Adder
18.902
3150681DARBY 2
Adder
18.88
3150671DARBY 1
Adder
18.858
3142366NRTHEST
Adder
0.854
3144293JTRSVLE
Adder
0.813
3144293JTRSVLE
Adder
0.685
3142296MT RD221
Adder
0.722
3150341NORNECKC1
Adder
2.217
3150341NORNECKC1
Adder
2.199
316447AC1-158 HLD
Solar/Wind Helper
4.811
315651AD1-115 GEN
Solar/Wind Helper
0.939
226929AD2-058 GEN
Solar/Wind Helper
0.091
970301AG2-198 GEN
Solar/Wind Harmer
14.287
970581AG2-369 GEN
Solar/Wind Harmer
20.157
957871AF2-081 GEN
Solar/Wind Harmer
18.688
319010AE1-072 C
Solar/Wind Harmer
7.541
3146406KITTY HAWK
Solar/Wind Harmer
0.031
316315AB2-025 C
Solar/Wind Harmer
1.005
316305AF2-043 C
Solar/Wind Harmer
1.119
315814AE2-033 C
Solar/Wind Harmer
34.559
313526AB2-022
Solar/Wind Harmer
0.997
3146486SUNBURY
Solar/Wind Harmer
-0.037
3146486SUNBURY
Solar/Wind Harmer
-0.037
316321Z2-027
Solar/Wind Harmer
0.993
3146396TANGLEW
Solar/Wind Harmer
0.677
3145176PASQUOTANK
Solar/Wind Harmer
-0.023
315835AF2-110_GEN
Solar/Wind Harmer
4.6
316311AC2-079 GEN
Solar/Wind Harmer
18.424
315833AF1-017_GEN
Solar/Wind Harmer
6.937
316349AD2-085 GEN
Solar/Wind Harmer
3.248
3143316POE
Solar/Wind Harmer
-0.143
971445AH1-216 GEN
Solar/Wind Harmer
22.478
315611Z1-036_GEN2
Solar/Wind Harmer
8.901
972265AH1-717 GEN
Adder
24.649
3151201GRAVEL4
Adder
23.107
3151191GRAVEL3
Adder
22.815
3151211GRAVEL5
Adder
22.815
3130156CHOWAN
Solar/Wind Harmer
-0.036
3130156CHOWAN
Solar/Wind Harmer
-0.036
315816AE2-034 GEN
Solar/Wind Harmer
2.83
316369SG1_INVT
Solar/Wind Harmer
6.201
3130546PLYMOUTH
Solar/Wind Harmer
-0.034
315732AD1-074 GEN1
Solar/Wind Harmer
6.95
315733AD1-074 GEN2
Solar/Wind Harmer
6.95
315735AD1-075 GEN1
Solar/Wind Harmer
3.476
965291AG1-394 GEN
Solar/Wind Harmer
3.038
971285AH1-108 GEN
Adder
2.292
316132AB2-190 GEN1
Solar/Wind Harmer
3.453
3146206CASHIE
Solar/Wind Harmer
-0.034
970601AG2-382 GEN
Solar/Wind Harmer
14.907
316318V4-068
Solar/Wind Harmer
0.847
3145893MURPHYS
Solar/Wind Harmer
-0.091
3145893MURPHYS
Solar/Wind Harmer
-0.034
946281AF1-292 GEN
Solar/Wind Harmer
0.753
3145513AHOSKIE
Solar/Wind Harmer
0.293
961941AG1-037 GEN
Solar/Wind Harmer
0.252
3145513AHOSKIE
Solar/Wind Harmer
-0.033
3146043SEABORD
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.066
3145683EARLEYS
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.033
315607AA1-063A GEN
Solar/Wind Harmer
3.371
316087AB2-174 GEN
Solar/Wind Harmer
4.759
315652AC1-086 GEN
Solar/Wind Harmer
37.252
3137643SOCKMAN
Solar/Wind Harmer
-0.131
3145796HORNRTN
Solar/Wind Harmer
-0.104
3145796HORNRTN
Solar/Wind Harmer
-0.013
957831AF2-077 GEN
Solar/Wind Harmer
0.98
3138283WHITEMARSH
Solar/Wind Harmer
0.05
3146033SCOT NK
Solar/Wind Harmer
-0.129
970831AG2-522 GEN
Solar/Wind Harmer
15.839
315976AC1-164 GENA
Solar/Wind Harmer
33.15
316169AC1-164_GENC
Solar/Wind Harmer
28.639
315975AC1-164 GENB
Solar/Wind Harmer
0.981
316005AA1-067
Solar/Wind Harmer
0.63
3145746EVERETS
Solar/Wind Harmer
-0.123
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
970181AG2-120 GEN
Solar/Wind Harmer
4.087
971167AH1-042 GEN
Solar/Wind Harmer
29.578
957861AF2-080 GEN
Solar/Wind Harmer
13.434
3142433PROV 92
Adder
0.53
3142433PROV 92
Adder
0.53
316420AA1-050 GEN
Solar/Wind Harmer
3.484
316319Z2-044 C
Solar/Wind Harmer
1.678
3145573BETHELC
Solar/Wind Harmer
-0.03
3145573BETHELC
Solar/Wind Harmer
-0.03
3143873LANEXA
Solar/Wind Harmer
-0.018
316239AB2-077_GEN
Solar/Wind Harmer
0.91
316238AB2-078_GEN
Solar/Wind Harmer
0.91
316314AB2-024 C
Solar/Wind Harmer
2.562
315662AE1-191 GEN
Solar/Wind Harmer
3.613
315666AE1-190 GEN
Solar/Wind Harmer
0.903
972205AH1-687 GEN
Adder
7.91
972189AH1-679 GEN
Adder
2.347
316164AC1-076 GEN
Solar/Wind Helper
1.495
316411AF1-147_GEN1
Solar/Wind Helper
0.81
316415AF1-147_GEN2
Solar/Wind Helper
0.81
3138216PACIFIC
Solar/Wind Helper
0.04
LAGNLTFEXP_LAGN->PJM
CLTF
12.7
CBM South 2LTFEXP_CBM-S2->PJM
CBM
38.248
TVALTFEXP_TVA->PJM
CLTF
6.385
CPLELTFEXP_CPLE->PJM
CLTF
17.51
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.525
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.942
MECLTFEXP_MEC->PJM
CLTF
6.275
SIGELTFEXP_SIGE->PJM
CLTF
0.19
NYPJM->LTFIMP_NY
CLTF
3.623
LGEELTFEXP_LGEE->PJM
CLTF
2.32
WECLTFEXP_WEC->PJM
CLTF
1.178
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.094

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.97 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6027.13
MW Contribution:49.35
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.377
3151101ELIZAR3
50/50
30.313
3150861SPRUNCD
50/50
1.471
3151161SURRY 1
50/50
11.323
970917AG2-570 GEN
Solar/Wind Harmer
89.846
315773AC2-141 GEN
Solar/Wind Harmer
14.644
944581AF1-123 GEN
Solar/Wind Harmer
158.305
944601AF1-125 GEN
Solar/Wind Harmer
155.834
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.034
971153AH1-033 GEN
Solar/Wind Harmer
4.188
3144536CHRHLND
Solar/Wind Harmer
-0.005
315813AE1-149 C
Solar/Wind Harmer
21.335
970659AG2-427 GEN
Solar/Wind Harmer
3.213
316083AB2-161 GEN
Solar/Wind Harmer
5.538
970661AG2-428 GEN
Solar/Wind Harmer
6.424
316320Y1-086
Solar/Wind Harmer
1.998
316435W1029_GEN3
Solar/Wind Harmer
6.125
3146516WINFALL
Solar/Wind Harmer
-0.034
315839AE2-212 C
Solar/Wind Harmer
1.016
3145336SMITFLD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.025
316313AB2-026
Solar/Wind Harmer
0.898
316258AE1-075 C
Solar/Wind Harmer
0.808
316405AF2-144 C
Solar/Wind Harmer
0.853
3143336POWHATN
Solar/Wind Harmer
3.359
965281AG1-393 GEN
Solar/Wind Harmer
4.153
3151221GRAVEL6
Adder
21.431
3151171GRAVELC
Adder
4.123
3146376EDENTON
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
6.933
316365GEN2_N
Solar/Wind Harmer
2.214
315614AA2-178 GEN
Solar/Wind Harmer
3.511
315778AD1-151 GEN
Solar/Wind Harmer
28.152
970129AG2-093 GEN
Solar/Wind Harmer
18.183
3156081AA2-088 GEN
Solar/Wind Harmer
10.453
316478AD1-087 GEN
Solar/Wind Harmer
2.786
316486AD2-202 GEN
Solar/Wind Harmer
0.816
971157AH1-035 GEN
Solar/Wind Harmer
4.016
315737AD1-076 GEN
Solar/Wind Harmer
6.093
970133AG2-095 GEN
Solar/Wind Harmer
3.601
966621AG1-532 GEN
Solar/Wind Harmer
0.649
3144216WINCHST
Adder
1.073
3145893MURPHYS
Solar/Wind Harmer
0.222
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
957521AF2-046 GEN
Solar/Wind Harmer
25.055
961681AG1-008 GEN
Solar/Wind Harmer
25.055
3150921YORKTN3
Adder
7.106
3146173TUNIS
Solar/Wind Harmer
-0.032
313506AB2-031 GEN
Solar/Wind Harmer
2.537
3156021HOLLOMANSOL
Solar/Wind Harmer
4.249
316463AE2-346 GEN
Solar/Wind Harmer
0.51
316140AB2-099
Solar/Wind Harmer
0.212
962331AG1-082 GEN
Solar/Wind Harmer
3.94
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3146263WOODLND
Solar/Wind Harmer
-0.031
3147043LAWRENC
Solar/Wind Harmer
-0.018
3143096IRON208
Adder
1.154
3143096IRON208
Adder
1.131
316317KELFORD C
Solar/Wind Harmer
1.459
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316382AG1-145 C
Solar/Wind Harmer
0.924
316210AC1-098 GEN
Solar/Wind Harmer
4.726
3142946ENON
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.03
966801AG1-551 GEN
Solar/Wind Harmer
3.729
315724AD1-057 GEN
Solar/Wind Harmer
1.698
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
316327AA2-057 GEN
Solar/Wind Harmer
2.954
970909AG2-566 GEN
Solar/Wind Harmer
2.75
316131AB2-060 GEN
Solar/Wind Harmer
3.123
970293AG2-193 GEN
Solar/Wind Harmer
3.602
3146233WITAKRS
Solar/Wind Harmer
0.603
3146233WITAKRS
Solar/Wind Harmer
-0.019
3138543CONSLDL
Solar/Wind Harmer
-0.019
964241AG1-285 GEN
Solar/Wind Harmer
22.468
3146073TAR RVR
Solar/Wind Harmer
-0.029
3146083TARBORO
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
3144293JTRSVLE
Adder
0.786
3141843SHACKLE
Adder
1.247
3150351NORNECKC2
Adder
1.939
972255AH1-712 GEN
Adder
64.825
316044AC1-158 PL1
Solar/Wind Helper
2.193
316450AC1-158 RIC
Solar/Wind Helper
0.585
3147666LOUISA
Solar/Wind Helper
0.714
316170AC1-121 GEN2
Solar/Wind Helper
0.428
3141196NOKESVL
Solar/Wind Helper
1.035
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.311
226910AB2-157 C
Solar/Wind Helper
0.013
970119AG2-088 GEN
50/50
49.347
315243AE2-183_GT3
50/50
5.563
3151051BRUNSWICKS1
50/50
9.085
3151021BRUNSWICKG1
50/50
4.377
971451AH1-221 GEN
50/50
13.295
3150981CHESPKA
50/50
4.072
3150851SPRUNCC
50/50
1.471
3152331SURRY 2
50/50
12.317
3143226MDLTHAN
Solar/Wind Harmer
-0.041
940641AE2-051 GEN
Solar/Wind Harmer
36.965
939411AE1-173 GEN
Solar/Wind Harmer
191.106
3143526WINTERP
Solar/Wind Harmer
-0.196
970919AG2-571 GEN
Solar/Wind Harmer
11.373
970087AG2-069 GEN
Solar/Wind Harmer
33.546
316294AC1-161 GEN
Solar/Wind Harmer
11.322
944591AF1-124 GEN
Solar/Wind Harmer
158.875
316375AC2-012 GEN
Solar/Wind Harmer
11.949
316388AE2-253 GEN
Solar/Wind Harmer
2.323
3146456SLIGO L269
Solar/Wind Harmer
-0.034
316246AF1-032 C
Solar/Wind Harmer
0.693
970659AG2-427 GEN
Solar/Wind Harmer
18.128
316381AD1-082 GEN
Solar/Wind Harmer
3.129
970661AG2-428 GEN
Solar/Wind Harmer
36.248
316093AE2-104_GEN
Solar/Wind Harmer
9.91
316072AD1-144
Solar/Wind Harmer
0.685
3146516WINFALL
Solar/Wind Harmer
-0.109
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.134
957481AF2-042 GEN
Solar/Wind Harmer
105.016
315800Z1-036_GEN1
Solar/Wind Harmer
8.244
3143336POWHATN
Solar/Wind Harmer
3.951
3151171GRAVELC
Adder
3.136
3130156CHOWAN
Solar/Wind Harmer
-0.033
315671AE2-027_GEN
Solar/Wind Harmer
24.714
961611AG1-000B GEN
Solar/Wind Harmer
16.249
316023GEN1_S
Solar/Wind Harmer
2.214
971647AH1-324 GEN
Solar/Wind Harmer
16.385
3145663CRESWEL
Solar/Wind Harmer
-0.091
971163AH1-040 GEN
Solar/Wind Harmer
30.505
315693AD1-088 GEN
Solar/Wind Harmer
16.249
971069AG2-661 GEN
Solar/Wind Harmer
5.142
316458AB2-190 GEN2
Solar/Wind Harmer
3.27
962491AG1-098 GEN
Solar/Wind Harmer
21.612
970129AG2-093 GEN
Solar/Wind Harmer
7.365
960081AF2-299 GEN
Solar/Wind Harmer
3.599
3138126ROCKLANDING
Solar/Wind Harmer
0.098
3145893MURPHYS
Solar/Wind Harmer
-0.127
3145893MURPHYS
Solar/Wind Harmer
0.946
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
7.961
3142543TWELFTH
Solar/Wind Harmer
-0.003
3146173TUNIS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.031
316011AB1-132 GEN
Solar/Wind Harmer
6.566
962571AG1-106 GEN
Solar/Wind Harmer
4.511
971795AH1-408 GEN
Solar/Wind Harmer
23.527
3146263WOODLND
Solar/Wind Harmer
-0.031
316190AA2-174 GEN
Solar/Wind Harmer
0.382
316336AC2-165 C
Solar/Wind Harmer
5.409
3147043LAWRENC
Adder
2.503
971317AH1-138 GEN
Solar/Wind Harmer
3.871
3143096IRON208
Adder
1.154
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316159AE1-175 C
Solar/Wind Harmer
0.823
316174AB2-169 GEN
Solar/Wind Harmer
4.727
944631AF1-128 GEN
Adder
129.496
315687AD1-152 GEN
Solar/Wind Harmer
3.646
316212AC1-099_GEN
Solar/Wind Harmer
2.626
316129AC1-054 GEN
Solar/Wind Harmer
2.637
971065AG2-659 GEN
Solar/Wind Harmer
14.993
3146293MARTNCO
Solar/Wind Harmer
0.185
315722AD1-056 GEN
Solar/Wind Harmer
3.088
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
316494AC1-189 GEN
Solar/Wind Harmer
3.123
316237AB2-079_GEN
Solar/Wind Harmer
0.873
3146233WITAKRS
Solar/Wind Harmer
-0.114
961671AG1-007 GEN
Solar/Wind Harmer
0.363
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.852
3142433PROV 92
Solar/Wind Harmer
-0.114
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
3144293JTRSVLE
Adder
0.786
3141843SHACKLE
Adder
1.247
3150351NORNECKC2
Adder
1.907
972277AH1-723 GEN
Adder
75.541
316045AC1-158 PL2
Solar/Wind Helper
7.02
3147666LOUISA
Solar/Wind Helper
1.242
316192AB2-158 GEN
Solar/Wind Helper
2.041
316254AC1-120 GEN1
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.129
970533AG2-339 GEN
50/50
30.814
970531AG2-338 GEN
50/50
12.326
315242AE2-183_GT2
50/50
5.563
315241AE2-183_GT1
50/50
5.529
972185AH1-677 GEN
50/50
20.054
3151041BRUNSWICKG3
50/50
4.377
972187AH1-678 GEN
50/50
10.045
3150991CHESPKB
50/50
3.416
3150991CHESPKB
50/50
3.334
971223AH1-071 GEN
Solar/Wind Harmer
5.198
3143526WINTERP
Solar/Wind Harmer
-0.196
970933AG2-581 GEN
Solar/Wind Harmer
34.189
3144356SAPONY
Solar/Wind Harmer
1.242
316185AD1-033 GEN
Solar/Wind Harmer
3.648
3142956BIRDNECK
Solar/Wind Harmer
1.854
316316AC1-027 C
Solar/Wind Harmer
1.061
316036AC1-147 C
Solar/Wind Harmer
0.932
3145506HICKORY
Solar/Wind Harmer
-0.137
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.02
316339AD2-160 GEN
Solar/Wind Harmer
2.323
316018AA1-139 ULT2
Solar/Wind Harmer
2.948
316017AA1-139 ULT1
Solar/Wind Harmer
2.785
3137176SLIGO L2192
Solar/Wind Harmer
-0.136
3146456SLIGO L269
Solar/Wind Harmer
4.058
3130086AYDLETT
Solar/Wind Harmer
-0.137
970657AG2-426 GEN
Solar/Wind Harmer
10.662
970657AG2-426 GEN
Solar/Wind Harmer
2.23
3146386ELIZ CT
Solar/Wind Harmer
-0.034
316431W1029_GEN1
Solar/Wind Harmer
6.125
316433W1029_GEN2
Solar/Wind Harmer
6.125
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
316236AE1-162_GEN
Solar/Wind Harmer
1.015
970099AG2-077 GEN
Solar/Wind Harmer
42.007
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3146626S HERTFORD
Solar/Wind Harmer
-0.033
315742AE1-103 GEN
Solar/Wind Harmer
3.474
3146376EDENTON
Solar/Wind Harmer
0.981
3146376EDENTON
Solar/Wind Harmer
0.981
316240AF1-291 C
Solar/Wind Harmer
0.989
316033AB2-134 GEN
Solar/Wind Harmer
10.519
315697AD1-025 GEN
Solar/Wind Harmer
6.597
944641AF1-129 GEN
Adder
138.008
316065AD1-022 GEN
Solar/Wind Harmer
15.96
3145893MURPHYS
Solar/Wind Harmer
0.889
3145893MURPHYS
Solar/Wind Harmer
-0.057
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316181AB2-040 GEN
Solar/Wind Harmer
4.403
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.146
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
966811AG1-552 GEN
Solar/Wind Harmer
3.497
3145593CAROLNA
Solar/Wind Harmer
0.258
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145783HORNRTN
Solar/Wind Harmer
3.668
3145783HORNRTN
Solar/Wind Harmer
2.934
3145783HORNRTN
Solar/Wind Harmer
0.917
3145783HORNRTN
Solar/Wind Harmer
0.367
316274AC1-208 GEN
Solar/Wind Harmer
3.236
3142946ENON
Solar/Wind Harmer
-0.003
3145933PARMELE
Solar/Wind Harmer
-0.059
3145933PARMELE
Solar/Wind Harmer
-0.03
971741AH1-377 GEN
Solar/Wind Harmer
34.617
939181AE1-148 GEN
Solar/Wind Harmer
16.559
3142366NRTHEST
Adder
0.852
3150691DARBY 3
Adder
18.657
3150701DARBY 4
Adder
18.614
3150681DARBY 2
Adder
18.592
3150671DARBY 1
Adder
18.57
313527AB2-043 GEN
Solar/Wind Harmer
4.711
970301AG2-198 GEN
Solar/Wind Harmer
14.484
3145493TOT1
Solar/Wind Harmer
0.444
3145453TOT5
Solar/Wind Harmer
0.267
3145603CNETO
Solar/Wind Harmer
0.178
3144293JTRSVLE
Adder
0.786
3144293JTRSVLE
Adder
0.662
3142296MT RD221
Adder
0.76
3150341NORNECKC1
Adder
2.003
3150341NORNECKC1
Adder
1.987
316447AC1-158 HLD
Solar/Wind Helper
4.827
315651AD1-115 GEN
Solar/Wind Helper
0.935
226929AD2-058 GEN
Solar/Wind Helper
0.091
316075AC2-137 C
Solar/Wind Harmer
0.313
316303AF2-085
50/50
6.58
315244AE2-183_ST
50/50
9.618
963041AG1-153 GEN
50/50
8.863
315779AE2-040
50/50
4.423
3151081ELIZAR1
50/50
29.93
3151091ELIZAR2
50/50
29.41
941591AE2-156 GEN
50/50
27.339
3152611GOSPORTB
50/50
4.153
3152621GOSPORTC
50/50
3.524
3152601GOSPORTA
50/50
3.251
971285AH1-108 GEN
50/50
2.407
972263AH1-716 GEN
50/50
170.499
941031AE2-094 GEN
Solar/Wind Harmer
73.029
944011AF1-069 GEN
Solar/Wind Harmer
22.883
970673AG2-436 GEN
Solar/Wind Harmer
80.276
970673AG2-436 GEN
Solar/Wind Harmer
40.646
316233AE1-074 FULL
Solar/Wind Harmer
1.019
971281AH1-106 GEN
Solar/Wind Harmer
6.156
971283AH1-107 GEN
Solar/Wind Harmer
6.156
971967AH1-528 GEN
Solar/Wind Harmer
70.663
970085AG2-068 GEN
Solar/Wind Harmer
22.364
970581AG2-369 GEN
Solar/Wind Harmer
19.233
316315AB2-025 C
Solar/Wind Harmer
0.96
315814AE2-033 C
Solar/Wind Harmer
33.023
3143316POE
Solar/Wind Harmer
-0.138
957871AF2-081 GEN
Solar/Wind Harmer
17.208
319010AE1-072 C
Solar/Wind Harmer
6.946
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
1.032
315833AF1-017_GEN
Solar/Wind Harmer
6.476
316349AD2-085 GEN
Solar/Wind Harmer
3.033
316311AC2-079 GEN
Solar/Wind Harmer
17.198
313526AB2-022
Solar/Wind Harmer
0.919
315835AF2-110_GEN
Solar/Wind Harmer
4.261
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
316321Z2-027
Solar/Wind Harmer
0.916
3146396TANGLEW
Solar/Wind Harmer
0.625
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
971445AH1-216 GEN
Solar/Wind Harmer
20.803
315611Z1-036_GEN2
Solar/Wind Harmer
8.244
972265AH1-717 GEN
Adder
22.888
3151201GRAVEL4
Adder
21.456
3151191GRAVEL3
Adder
21.184
3151211GRAVEL5
Adder
21.184
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316369SG1_INVT
Solar/Wind Harmer
5.828
315816AE2-034 GEN
Solar/Wind Harmer
2.633
316132AB2-190 GEN1
Solar/Wind Harmer
3.27
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
965291AG1-394 GEN
Solar/Wind Harmer
2.85
315732AD1-074 GEN1
Solar/Wind Harmer
6.483
315733AD1-074 GEN2
Solar/Wind Harmer
6.483
315735AD1-075 GEN1
Solar/Wind Harmer
3.242
946281AF1-292 GEN
Solar/Wind Harmer
0.717
316318V4-068
Solar/Wind Harmer
0.794
3145893MURPHYS
Solar/Wind Harmer
-0.086
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
13.932
316087AB2-174 GEN
Solar/Wind Harmer
4.521
3146043SEABORD
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.275
961941AG1-037 GEN
Solar/Wind Harmer
0.237
3145513AHOSKIE
Solar/Wind Harmer
-0.031
315607AA1-063A GEN
Solar/Wind Harmer
3.181
3145683EARLEYS
Solar/Wind Harmer
-0.062
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
35.304
3137643SOCKMAN
Solar/Wind Harmer
-0.124
3145796HORNRTN
Solar/Wind Harmer
-0.098
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.121
970831AG2-522 GEN
Solar/Wind Harmer
15.086
957831AF2-077 GEN
Solar/Wind Harmer
0.889
3138283WHITEMARSH
Solar/Wind Harmer
0.046
316005AA1-067
Solar/Wind Harmer
0.594
3145746EVERETS
Solar/Wind Harmer
-0.116
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
970181AG2-120 GEN
Solar/Wind Harmer
3.854
957861AF2-080 GEN
Solar/Wind Harmer
12.697
316239AB2-077_GEN
Solar/Wind Harmer
0.873
316238AB2-078_GEN
Solar/Wind Harmer
0.873
316420AA1-050 GEN
Solar/Wind Harmer
3.296
316319Z2-044 C
Solar/Wind Harmer
1.592
971167AH1-042 GEN
Solar/Wind Harmer
27.693
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
315976AC1-164 GENA
Solar/Wind Harmer
30.185
316169AC1-164_GENC
Solar/Wind Harmer
26.077
315975AC1-164 GENB
Solar/Wind Harmer
0.893
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
972205AH1-687 GEN
Adder
7.923
972189AH1-679 GEN
Adder
2.542
972193AH1-681 GEN
Adder
2.896
316164AC1-076 GEN
Solar/Wind Helper
1.492
316411AF1-147_GEN1
Solar/Wind Helper
0.805
316415AF1-147_GEN2
Solar/Wind Helper
0.805
3138216PACIFIC
Solar/Wind Helper
0.039
LAGNLTFEXP_LAGN->PJM
CLTF
12.464
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.906
TVALTFEXP_TVA->PJM
CLTF
6.273
CPLELTFEXP_CPLE->PJM
CLTF
16.795
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.696
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.329
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.608
MECLTFEXP_MEC->PJM
CLTF
6.26
SIGELTFEXP_SIGE->PJM
CLTF
0.19
NYPJM->LTFIMP_NY
CLTF
3.562
LGEELTFEXP_LGEE->PJM
CLTF
2.331
WECLTFEXP_WEC->PJM
CLTF
1.184
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.69 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4402.07
MW Contribution:43.39
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
43.39
315243AE2-183_GT3
50/50
5.306
3151051BRUNSWICKS1
50/50
8.655
3151021BRUNSWICKG1
50/50
4.17
971451AH1-221 GEN
50/50
12.666
3150981CHESPKA
50/50
3.862
3152331SURRY 2
50/50
11.978
940641AE2-051 GEN
Solar/Wind Harmer
26.972
939411AE1-173 GEN
Solar/Wind Harmer
139.157
3143226MDLTHAN
Solar/Wind Harmer
0.325
970919AG2-571 GEN
Solar/Wind Harmer
10.802
970087AG2-069 GEN
Solar/Wind Harmer
24.19
316294AC1-161 GEN
Solar/Wind Harmer
5.215
944591AF1-124 GEN
Solar/Wind Harmer
66.808
316375AC2-012 GEN
Solar/Wind Harmer
0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.912
3146456SLIGO L269
Solar/Wind Harmer
0.29
316246AF1-032 C
Solar/Wind Harmer
0.13
316093AE2-104_GEN
Solar/Wind Harmer
4.794
3146516WINFALL
Solar/Wind Harmer
0.92
3146516WINFALL
Solar/Wind Harmer
0.284
316072AD1-144
Solar/Wind Harmer
0.103
3143526WINTERP
Solar/Wind Harmer
1.47
957481AF2-042 GEN
Solar/Wind Harmer
74.795
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
1.108
970661AG2-428 GEN
Solar/Wind Harmer
27.311
316381AD1-082 GEN
Solar/Wind Harmer
0.284
3145663CRESWEL
Solar/Wind Harmer
0.761
971163AH1-040 GEN
Solar/Wind Harmer
21.769
970659AG2-427 GEN
Solar/Wind Harmer
13.13
315693AD1-088 GEN
Solar/Wind Harmer
12.923
316023GEN1_S
Solar/Wind Harmer
0.603
3151171GRAVELC
Adder
2.853
962491AG1-098 GEN
Solar/Wind Harmer
15.256
3146206CASHIE
Solar/Wind Harmer
0.265
971547AH1-271 GEN
Solar/Wind Harmer
5.655
3138126ROCKLANDING
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
1.056
3145893MURPHYS
Solar/Wind Harmer
1.174
961611AG1-000B GEN
Solar/Wind Harmer
13.793
3146173TUNIS
Solar/Wind Harmer
0.262
960081AF2-299 GEN
Solar/Wind Harmer
2.514
3145683EARLEYS
Solar/Wind Harmer
0.26
3146263WOODLND
Solar/Wind Harmer
0.259
971647AH1-324 GEN
Solar/Wind Harmer
11.046
316011AB1-132 GEN
Solar/Wind Harmer
4.685
962571AG1-106 GEN
Solar/Wind Harmer
3.666
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
17.096
3145963POPLR C
Solar/Wind Harmer
0.256
971317AH1-138 GEN
Solar/Wind Harmer
1.913
3145823KELFORD
Solar/Wind Harmer
0.256
3143336POWHATN
Solar/Wind Harmer
4.523
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3145783HORNRTN
Solar/Wind Harmer
0.254
3145796HORNRTN
Solar/Wind Harmer
0.838
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Adder
2.297
971069AG2-661 GEN
Solar/Wind Harmer
4.473
315687AD1-152 GEN
Solar/Wind Harmer
0.008
316159AE1-175 C
Solar/Wind Harmer
0.215
316212AC1-099_GEN
Solar/Wind Harmer
1.283
316458AB2-190 GEN2
Solar/Wind Harmer
1.325
3146293MARTNCO
Solar/Wind Harmer
0.229
316129AC1-054 GEN
Solar/Wind Harmer
0.928
970129AG2-093 GEN
Solar/Wind Harmer
7.001
971065AG2-659 GEN
Solar/Wind Harmer
10.492
315671AE2-027_GEN
Solar/Wind Harmer
15.643
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315722AD1-056 GEN
Solar/Wind Harmer
1.533
3150851SPRUNCC
Adder
1.101
316494AC1-189 GEN
Solar/Wind Harmer
0.807
3146233WITAKRS
Solar/Wind Harmer
0.94
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.049
316336AC2-165 C
Solar/Wind Harmer
0.009
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.186
316359AB2-059 GEN
Solar/Wind Harmer
0.835
316049AB1-081 GEN
Solar/Wind Harmer
1.331
3142053HEARTS
Solar/Wind Harmer
0.409
970401AG2-262 GEN
Solar/Wind Harmer
1.326
970685AG2-442 GEN
Solar/Wind Harmer
16.767
944631AF1-128 GEN
Adder
106.166
963171AG1-166 GEN
Solar/Wind Harmer
1.18
971563AH1-280 GEN
Solar/Wind Harmer
2.361
3144293JTRSVLE
Adder
0.705
3142543TWELFTH
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.569
3141843SHACKLE
Adder
1.102
3143096IRON208
Adder
0.902
3141766HARMONY
Solar/Wind Harmer
0.043
3142433PROV 92
Solar/Wind Harmer
0.86
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
3138133OCRAN
Solar/Wind Harmer
0.125
316003AC1-222 GEN
Solar/Wind Harmer
0.006
3146926FARMVIL
Solar/Wind Harmer
0.123
970937AG2-583 GEN
Solar/Wind Harmer
11.537
962861AG1-135 GEN
Solar/Wind Harmer
5.983
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
3141726DUNNSVL
Solar/Wind Harmer
0.706
3150351NORNECKC2
Adder
1.716
3142416OLDCHRC
Solar/Wind Harmer
0.416
3142416OLDCHRC
Solar/Wind Harmer
0.159
972003AH1-546 GEN
Solar/Wind Harmer
6.522
316337AD2-073 GEN
Solar/Wind Harmer
0.133
971377AH1-170 GEN
Solar/Wind Harmer
1.41
3147623JAMES R
Solar/Wind Harmer
0.306
970223AG2-152 GEN
Solar/Wind Harmer
9.004
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.068
316045AC1-158 PL2
Solar/Wind Helper
5.515
3147666LOUISA
Solar/Wind Helper
1.037
316192AB2-158 GEN
Solar/Wind Helper
1.708
3151031BRUNSWICKG2
50/50
4.17
3151101ELIZAR3
50/50
28.777
3151161SURRY 1
50/50
10.302
970917AG2-570 GEN
Solar/Wind Harmer
27.004
315773AC2-141 GEN
Solar/Wind Harmer
10.994
944581AF1-123 GEN
Solar/Wind Harmer
66.571
944601AF1-125 GEN
Solar/Wind Harmer
65.546
3144873MCLAUGH
Solar/Wind Harmer
0.007
3146456SLIGO L269
Solar/Wind Harmer
0.29
971153AH1-033 GEN
Solar/Wind Harmer
3.357
316320Y1-086
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.043
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146626S HERTFORD
Solar/Wind Harmer
0.282
3145273HOLLAND
Solar/Wind Harmer
0.209
3146376EDENTON
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
0.111
970661AG2-428 GEN
Solar/Wind Harmer
5.809
316083AB2-161 GEN
Solar/Wind Harmer
0.004
315614AA2-178 GEN
Solar/Wind Harmer
1.557
970659AG2-427 GEN
Solar/Wind Harmer
2.872
316365GEN2_N
Solar/Wind Harmer
0.603
3151221GRAVEL6
Adder
19.5
3151171GRAVELC
Adder
3.752
971157AH1-035 GEN
Solar/Wind Harmer
3.217
315813AE1-149 C
Solar/Wind Harmer
14.26
315737AD1-076 GEN
Solar/Wind Harmer
3.44
316478AD1-087 GEN
Solar/Wind Harmer
0.932
316486AD2-202 GEN
Solar/Wind Harmer
0.274
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3146206CASHIE
Solar/Wind Harmer
0.265
3144216WINCHST
Adder
0.999
3145893MURPHYS
Solar/Wind Harmer
0.442
3145893MURPHYS
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
6.638
957521AF2-046 GEN
Solar/Wind Harmer
19.613
961681AG1-008 GEN
Solar/Wind Harmer
19.613
961611AG1-000B GEN
Solar/Wind Harmer
7.014
3146173TUNIS
Solar/Wind Harmer
0.262
3156021HOLLOMANSOL
Solar/Wind Harmer
1.189
316463AE2-346 GEN
Solar/Wind Harmer
0.224
316140AB2-099
Solar/Wind Harmer
0.093
962331AG1-082 GEN
Solar/Wind Harmer
2.786
3146263WOODLND
Solar/Wind Harmer
0.259
313506AB2-031 GEN
Solar/Wind Harmer
0.8
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3145963POPLR C
Solar/Wind Harmer
0.256
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.256
316313AB2-026
Solar/Wind Harmer
0.16
316258AE1-075 C
Solar/Wind Harmer
0.192
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.845
3145796HORNRTN
Solar/Wind Harmer
1.016
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Solar/Wind Harmer
0.152
315839AE2-212 C
Solar/Wind Harmer
0.002
315778AD1-151 GEN
Solar/Wind Harmer
20.127
316382AG1-145 C
Solar/Wind Harmer
0.002
965281AG1-393 GEN
Solar/Wind Harmer
2.647
316210AC1-098 GEN
Solar/Wind Harmer
2.301
3145933PARMELE
Solar/Wind Harmer
0.247
966801AG1-551 GEN
Solar/Wind Harmer
2.873
970129AG2-093 GEN
Solar/Wind Harmer
14.877
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315724AD1-057 GEN
Solar/Wind Harmer
0.909
316327AA2-057 GEN
Solar/Wind Harmer
0.363
3150861SPRUNCD
Adder
1.101
970133AG2-095 GEN
Solar/Wind Harmer
2.289
3146233WITAKRS
Solar/Wind Harmer
1.186
3146233WITAKRS
Solar/Wind Harmer
0.161
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
3138543CONSLDL
Solar/Wind Harmer
0.156
316131AB2-060 GEN
Solar/Wind Harmer
0.739
964241AG1-285 GEN
Solar/Wind Harmer
15.529
970909AG2-566 GEN
Solar/Wind Harmer
2.481
961601AG1-000A GEN
Solar/Wind Harmer
16.539
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.232
971623AH1-311 GEN
Solar/Wind Harmer
0.465
315785AD2-033 C
Solar/Wind Harmer
1.864
970257AG2-171 GEN
Solar/Wind Harmer
7.295
959311AF2-222 GEN
Solar/Wind Harmer
20.178
3142946ENON
Solar/Wind Harmer
0.074
963181AG1-167 GEN
Solar/Wind Harmer
0.885
3144293JTRSVLE
Adder
0.705
3147133PAMPLIN
Solar/Wind Harmer
0.687
971193AH1-056 GEN
Solar/Wind Harmer
13.34
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.346
316156AD2-030 GEN
Solar/Wind Harmer
0.16
3141873WAN 176
Solar/Wind Harmer
3.848
316280AD1-041 GEN
Solar/Wind Harmer
0.004
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.102
3143096IRON208
Adder
0.902
3143096IRON208
Adder
0.884
3141766HARMONY
Solar/Wind Harmer
2.867
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.123
316283AC2-100 C
Solar/Wind Harmer
0.389
971683AH1-343 GEN
Solar/Wind Harmer
7.294
962971AG1-146 GEN
Solar/Wind Harmer
3.148
970293AG2-193 GEN
Solar/Wind Harmer
2.064
970009AG2-005 GEN
Solar/Wind Harmer
1.436
316404AE1-155 C
Solar/Wind Harmer
0.042
3146776BUCKING
Solar/Wind Harmer
0.065
3150351NORNECKC2
Adder
1.745
3142416OLDCHRC
Solar/Wind Harmer
1.55
3141906WESTMOR
Solar/Wind Harmer
0.053
970221AG2-151 GEN
Solar/Wind Harmer
7.048
316473AC1-191 GEN
Solar/Wind Harmer
0.412
970737AG2-469 GEN
Solar/Wind Harmer
4.87
316044AC1-158 PL1
Solar/Wind Helper
1.723
316450AC1-158 RIC
Solar/Wind Helper
0.459
3147666LOUISA
Solar/Wind Helper
0.596
970533AG2-339 GEN
50/50
29.471
970531AG2-338 GEN
50/50
11.789
315242AE2-183_GT2
50/50
5.306
315241AE2-183_GT1
50/50
5.273
972185AH1-677 GEN
50/50
19.129
3151041BRUNSWICKG3
50/50
4.17
972187AH1-678 GEN
50/50
9.57
3150991CHESPKB
50/50
3.24
3150991CHESPKB
50/50
3.162
971223AH1-071 GEN
Solar/Wind Harmer
3.471
970933AG2-581 GEN
Solar/Wind Harmer
24.629
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.168
3145506HICKORY
Solar/Wind Harmer
0.701
3145506HICKORY
Solar/Wind Harmer
0.175
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.28
316036AC1-147 C
Solar/Wind Harmer
0.054
316339AD2-160 GEN
Solar/Wind Harmer
0.472
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.162
3137176SLIGO L2192
Solar/Wind Harmer
1.156
3146456SLIGO L269
Solar/Wind Harmer
5.139
3130086AYDLETT
Solar/Wind Harmer
1.16
3144356SAPONY
Solar/Wind Harmer
2.426
3146386ELIZ CT
Solar/Wind Harmer
0.287
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3143526WINTERP
Solar/Wind Harmer
1.47
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
970099AG2-077 GEN
Solar/Wind Harmer
29.918
3146376EDENTON
Solar/Wind Harmer
1.233
3146376EDENTON
Solar/Wind Harmer
1.233
316236AE1-162_GEN
Solar/Wind Harmer
0.002
315742AE1-103 GEN
Solar/Wind Harmer
0.003
970657AG2-426 GEN
Solar/Wind Harmer
9.567
970657AG2-426 GEN
Solar/Wind Harmer
2.006
316065AD1-022 GEN
Solar/Wind Harmer
12.243
3145893MURPHYS
Solar/Wind Harmer
1.767
3145893MURPHYS
Solar/Wind Harmer
0.475
3146173TUNIS
Solar/Wind Harmer
0.262
3146173TUNIS
Solar/Wind Harmer
0.262
316181AB2-040 GEN
Solar/Wind Harmer
0.376
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
316426AA2-053 GEN
Solar/Wind Harmer
0.866
3145593CAROLNA
Solar/Wind Harmer
0.255
3145593CAROLNA
Solar/Wind Harmer
0.255
966811AG1-552 GEN
Solar/Wind Harmer
2.773
3145593CAROLNA
Solar/Wind Harmer
0.318
316033AB2-134 GEN
Solar/Wind Harmer
0.015
315697AD1-025 GEN
Solar/Wind Harmer
0.287
3145783HORNRTN
Solar/Wind Harmer
4.52
3145783HORNRTN
Solar/Wind Harmer
3.616
3145783HORNRTN
Solar/Wind Harmer
1.13
3145783HORNRTN
Solar/Wind Harmer
0.452
3145796HORNRTN
Solar/Wind Harmer
0.762
3145933PARMELE
Solar/Wind Harmer
0.493
3145933PARMELE
Solar/Wind Harmer
0.247
316274AC1-208 GEN
Solar/Wind Harmer
1.28
971741AH1-377 GEN
Solar/Wind Harmer
23.908
939181AE1-148 GEN
Solar/Wind Harmer
11.558
316240AF1-291 C
Solar/Wind Harmer
0.002
3145493TOT1
Solar/Wind Harmer
0.547
3145453TOT5
Solar/Wind Harmer
0.328
3145603CNETO
Solar/Wind Harmer
0.219
313527AB2-043 GEN
Solar/Wind Harmer
0.003
944641AF1-129 GEN
Adder
111.535
970301AG2-198 GEN
Solar/Wind Harmer
9.924
961601AG1-000A GEN
Solar/Wind Harmer
4.135
316263AC1-034 GEN
Solar/Wind Harmer
8.835
970323AG2-213 GEN
Solar/Wind Harmer
9.727
971775AH1-396 GEN
Solar/Wind Harmer
0.365
316034AC1-036 C
Solar/Wind Harmer
0.017
962561AG1-105 GEN
Solar/Wind Harmer
10.919
964791AG1-342 GEN
Solar/Wind Harmer
4.339
3146843MT LREL
Solar/Wind Harmer
0.226
3146843MT LREL
Solar/Wind Harmer
0.226
3142946ENON
Solar/Wind Harmer
0.022
958211AF2-115 GEN
Solar/Wind Harmer
2.656
963191AG1-168 GEN
Solar/Wind Harmer
0.885
3144293JTRSVLE
Adder
0.705
3144293JTRSVLE
Adder
0.593
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
316075AC2-137 C
Solar/Wind Harmer
0.055
316222AC1-221 GEN
Solar/Wind Harmer
0.83
3150691DARBY 3
Adder
13.407
3150701DARBY 4
Adder
13.376
3150681DARBY 2
Adder
13.36
3150671DARBY 1
Adder
13.345
958261AF2-120 GEN
Solar/Wind Harmer
6.119
3142366NRTHEST
Adder
0.595
3146776BUCKING
Solar/Wind Harmer
0.717
3146776BUCKING
Solar/Wind Harmer
0.058
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.803
3150341NORNECKC1
Adder
1.788
942751AE2-291 GEN
Solar/Wind Harmer
8.42
971489AH1-241 GEN
Solar/Wind Harmer
7.048
3142296MT RD221
Adder
0.414
270013AE1-250 PV
Solar/Wind Harmer
0.004
966871AG1-558 GEN
Solar/Wind Harmer
0.141
316447AC1-158 HLD
Solar/Wind Helper
3.792
316303AF2-085
50/50
5.785
315244AE2-183_ST
50/50
9.174
963041AG1-153 GEN
50/50
8.444
3151081ELIZAR1
50/50
28.413
3151091ELIZAR2
50/50
27.92
941591AE2-156 GEN
50/50
25.939
3152611GOSPORTB
50/50
3.939
3152621GOSPORTC
50/50
3.343
3152601GOSPORTA
50/50
3.084
315779AE2-040
50/50
4.048
972263AH1-716 GEN
50/50
164.964
941031AE2-094 GEN
Solar/Wind Harmer
61.065
944011AF1-069 GEN
Solar/Wind Harmer
19.952
970673AG2-436 GEN
Solar/Wind Harmer
69.269
970673AG2-436 GEN
Solar/Wind Harmer
46.179
971967AH1-528 GEN
Solar/Wind Harmer
50.977
970085AG2-068 GEN
Solar/Wind Harmer
16.126
970581AG2-369 GEN
Solar/Wind Harmer
13.869
957871AF2-081 GEN
Solar/Wind Harmer
14.487
319010AE1-072 C
Solar/Wind Harmer
1.462
3146406KITTY HAWK
Solar/Wind Harmer
0.036
316315AB2-025 C
Solar/Wind Harmer
0.234
315814AE2-033 C
Solar/Wind Harmer
22.859
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.156
316321Z2-027
Solar/Wind Harmer
0.053
3146396TANGLEW
Solar/Wind Harmer
0.789
3145176PASQUOTANK
Solar/Wind Harmer
0.177
3146486SUNBURY
Solar/Wind Harmer
0.286
3146486SUNBURY
Solar/Wind Harmer
0.286
315835AF2-110_GEN
Solar/Wind Harmer
1.956
316233AE1-074 FULL
Solar/Wind Harmer
0.226
971281AH1-106 GEN
Solar/Wind Harmer
3.922
971283AH1-107 GEN
Solar/Wind Harmer
3.922
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316311AC2-079 GEN
Solar/Wind Harmer
8.046
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.192
3130156CHOWAN
Solar/Wind Harmer
0.277
3130156CHOWAN
Solar/Wind Harmer
0.277
971445AH1-216 GEN
Solar/Wind Harmer
19.461
3143316POE
Solar/Wind Harmer
1.085
315816AE2-034 GEN
Solar/Wind Harmer
1.168
972265AH1-717 GEN
Adder
20.825
3151201GRAVEL4
Adder
19.522
3151191GRAVEL3
Adder
19.275
3151211GRAVEL5
Adder
19.275
3130546PLYMOUTH
Solar/Wind Harmer
0.268
315732AD1-074 GEN1
Solar/Wind Harmer
1.536
315733AD1-074 GEN2
Solar/Wind Harmer
1.536
315735AD1-075 GEN1
Solar/Wind Harmer
0.769
965291AG1-394 GEN
Solar/Wind Harmer
1.182
3146206CASHIE
Solar/Wind Harmer
0.265
970601AG2-382 GEN
Solar/Wind Harmer
9.896
3145893MURPHYS
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
0.264
3145513AHOSKIE
Solar/Wind Harmer
0.546
3145513AHOSKIE
Solar/Wind Harmer
0.261
3146043SEABORD
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.52
3145683EARLEYS
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.26
316087AB2-174 GEN
Solar/Wind Harmer
0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.531
315652AC1-086 GEN
Solar/Wind Harmer
28.344
3137643SOCKMAN
Solar/Wind Harmer
1.027
316369SG1_INVT
Solar/Wind Harmer
0.01
3145796HORNRTN
Solar/Wind Harmer
0.813
3145796HORNRTN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
1.006
970831AG2-522 GEN
Solar/Wind Harmer
10.563
316132AB2-190 GEN1
Solar/Wind Harmer
1.325
316005AA1-067
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.964
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
970181AG2-120 GEN
Solar/Wind Harmer
3.014
3138283WHITEMARSH
Solar/Wind Harmer
0.056
971285AH1-108 GEN
Adder
1.802
957861AF2-080 GEN
Solar/Wind Harmer
10.3
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.835
3144303KENBRDG
Solar/Wind Harmer
0.182
970683AG2-441 GEN
Solar/Wind Harmer
14.971
970681AG2-440 GEN
Solar/Wind Harmer
11.976
316118AC1-105 GEN
Solar/Wind Harmer
0.574
946301AF1-294 GEN
Solar/Wind Harmer
4.367
961791AG1-021 GEN
Solar/Wind Harmer
2.125
315657AE1-056 GEN
Solar/Wind Harmer
7.556
3147173SINAI
Solar/Wind Harmer
0.219
3147243WELCO
Solar/Wind Harmer
0.137
315976AC1-164 GENA
Solar/Wind Harmer
22.6
316169AC1-164_GENC
Solar/Wind Harmer
19.524
315975AC1-164 GENB
Solar/Wind Harmer
0.669
3141873WAN 176
Solar/Wind Harmer
0.043
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
6.392
971167AH1-042 GEN
Solar/Wind Harmer
19.104
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
3143873LANEXA
Solar/Wind Harmer
0.129
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.21
3138133OCRAN
Solar/Wind Harmer
0.062
3141783LANCAST
Solar/Wind Harmer
0.123
3141783LANCAST
Solar/Wind Harmer
0.082
962981AG1-147 GEN
Solar/Wind Harmer
7.345
970327AG2-215 GEN
Solar/Wind Harmer
6.31
970865AG2-541 GEN
Solar/Wind Harmer
6.523
970285AG2-188 GEN
Solar/Wind Harmer
14.703
971845AH1-439 GEN
Solar/Wind Harmer
8.235
3141813NORNECK
Solar/Wind Harmer
0.172
316123AC1-075 GEN
Solar/Wind Harmer
0.229
970165AG2-112 GEN
Solar/Wind Harmer
1.36
970163AG2-111 GEN
Solar/Wind Harmer
1.297
316312AB1-027
Solar/Wind Harmer
0.286
972205AH1-687 GEN
Adder
6.309
316223AC1-118
Solar/Wind Harmer
0.095
971447AH1-217 GEN
Solar/Wind Harmer
3.746
270494AE1-108_GEN
Solar/Wind Harmer
1.403
316164AC1-076 GEN
Solar/Wind Helper
1.139
LAGNLTFEXP_LAGN->PJM
CLTF
10.194
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.592
TVALTFEXP_TVA->PJM
CLTF
5.103
CPLELTFEXP_CPLE->PJM
CLTF
15.205
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.962
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.385
MECLTFEXP_MEC->PJM
CLTF
4.747
SIGELTFEXP_SIGE->PJM
CLTF
0.142
NYPJM->LTFIMP_NY
CLTF
2.749
LGEELTFEXP_LGEE->PJM
CLTF
1.702
WECLTFEXP_WEC->PJM
CLTF
0.865

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.12 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5205.6
MW Contribution:44.7
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
27.956
970531AG2-338 GEN
50/50
11.182
315242AE2-183_GT2
50/50
5.046
315241AE2-183_GT1
50/50
5.015
972185AH1-677 GEN
50/50
18.191
3151041BRUNSWICKG3
50/50
3.97
972187AH1-678 GEN
50/50
9.111
3150991CHESPKB
50/50
3.124
3150991CHESPKB
50/50
3.049
971223AH1-071 GEN
Solar/Wind Harmer
4.708
3143526WINTERP
Solar/Wind Harmer
-0.178
970933AG2-581 GEN
Solar/Wind Harmer
30.984
3144356SAPONY
Solar/Wind Harmer
1.13
316185AD1-033 GEN
Solar/Wind Harmer
3.336
3142956BIRDNECK
Solar/Wind Harmer
1.696
316316AC1-027 C
Solar/Wind Harmer
0.97
316036AC1-147 C
Solar/Wind Harmer
0.852
3145506HICKORY
Solar/Wind Harmer
-0.126
3145506HICKORY
Solar/Wind Harmer
-0.075
3145506HICKORY
Solar/Wind Harmer
-0.019
316339AD2-160 GEN
Solar/Wind Harmer
2.123
970119AG2-088 GEN
50/50
44.697
315243AE2-183_GT3
50/50
5.046
3151051BRUNSWICKS1
50/50
8.24
3151021BRUNSWICKG1
50/50
3.97
971451AH1-221 GEN
50/50
12.059
3150981CHESPKA
50/50
3.724
3150851SPRUNCC
50/50
1.346
3152331SURRY 2
50/50
11.301
3143226MDLTHAN
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
33.588
939411AE1-173 GEN
Solar/Wind Harmer
173.894
3143526WINTERP
Solar/Wind Harmer
-0.178
970919AG2-571 GEN
Solar/Wind Harmer
10.315
970087AG2-069 GEN
Solar/Wind Harmer
30.424
316294AC1-161 GEN
Solar/Wind Harmer
10.357
944591AF1-124 GEN
Solar/Wind Harmer
145.255
316375AC2-012 GEN
Solar/Wind Harmer
10.929
316388AE2-253 GEN
Solar/Wind Harmer
2.123
3146456SLIGO L269
Solar/Wind Harmer
-0.031
316246AF1-032 C
Solar/Wind Harmer
0.634
970659AG2-427 GEN
Solar/Wind Harmer
16.575
316381AD1-082 GEN
Solar/Wind Harmer
2.861
970661AG2-428 GEN
Solar/Wind Harmer
33.139
316093AE2-104_GEN
Solar/Wind Harmer
9.058
316072AD1-144
Solar/Wind Harmer
0.627
3145336SMITFLD
Solar/Wind Harmer
-0.123
3146516WINFALL
Solar/Wind Harmer
-0.099
3146516WINFALL
Solar/Wind Harmer
-0.031
315800Z1-036_GEN1
Solar/Wind Harmer
7.529
957481AF2-042 GEN
Solar/Wind Harmer
95.029
3151171GRAVELC
Adder
2.875
3130156CHOWAN
Solar/Wind Harmer
-0.03
315671AE2-027_GEN
Solar/Wind Harmer
22.65
961611AG1-000B GEN
Solar/Wind Harmer
14.902
971647AH1-324 GEN
Solar/Wind Harmer
15.03
316023GEN1_S
Solar/Wind Harmer
2.014
3143336POWHATN
Solar/Wind Harmer
3.544
971069AG2-661 GEN
Solar/Wind Harmer
4.719
3145663CRESWEL
Solar/Wind Harmer
-0.083
971163AH1-040 GEN
Solar/Wind Harmer
27.837
316458AB2-190 GEN2
Solar/Wind Harmer
3.001
970129AG2-093 GEN
Solar/Wind Harmer
6.761
315693AD1-088 GEN
Solar/Wind Harmer
14.68
3138126ROCKLANDING
Solar/Wind Harmer
0.09
316018AA1-139 ULT2
Solar/Wind Harmer
2.695
316017AA1-139 ULT1
Solar/Wind Harmer
2.546
3137176SLIGO L2192
Solar/Wind Harmer
-0.124
3146456SLIGO L269
Solar/Wind Harmer
3.71
3130086AYDLETT
Solar/Wind Harmer
-0.125
970657AG2-426 GEN
Solar/Wind Harmer
9.748
970657AG2-426 GEN
Solar/Wind Harmer
2.039
3146386ELIZ CT
Solar/Wind Harmer
-0.031
316431W1029_GEN1
Solar/Wind Harmer
5.597
316433W1029_GEN2
Solar/Wind Harmer
5.597
316236AE1-162_GEN
Solar/Wind Harmer
0.929
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
970099AG2-077 GEN
Solar/Wind Harmer
38.011
315742AE1-103 GEN
Solar/Wind Harmer
3.171
3146376EDENTON
Solar/Wind Harmer
0.896
3146376EDENTON
Solar/Wind Harmer
0.896
316240AF1-291 C
Solar/Wind Harmer
0.906
316033AB2-134 GEN
Solar/Wind Harmer
9.651
315697AD1-025 GEN
Solar/Wind Harmer
6.053
944641AF1-129 GEN
Adder
126.539
316065AD1-022 GEN
Solar/Wind Harmer
14.554
3145893MURPHYS
Solar/Wind Harmer
0.81
3145893MURPHYS
Solar/Wind Harmer
-0.052
3146173TUNIS
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
316181AB2-040 GEN
Solar/Wind Harmer
4.002
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316426AA2-053 GEN
Solar/Wind Harmer
2.861
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
-0.028
966811AG1-552 GEN
Solar/Wind Harmer
3.179
3145593CAROLNA
Solar/Wind Harmer
0.235
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145783HORNRTN
Solar/Wind Harmer
3.335
3145783HORNRTN
Solar/Wind Harmer
2.668
3145783HORNRTN
Solar/Wind Harmer
0.834
3145783HORNRTN
Solar/Wind Harmer
0.334
3142946ENON
Solar/Wind Harmer
-0.003
316274AC1-208 GEN
Solar/Wind Harmer
2.942
3145933PARMELE
Solar/Wind Harmer
-0.054
3145933PARMELE
Solar/Wind Harmer
-0.027
3142366NRTHEST
Adder
0.786
3150691DARBY 3
Adder
17.226
3150701DARBY 4
Adder
17.185
3150681DARBY 2
Adder
17.165
3150671DARBY 1
Adder
17.145
971741AH1-377 GEN
Solar/Wind Harmer
31.097
939181AE1-148 GEN
Solar/Wind Harmer
14.98
316075AC2-137 C
Solar/Wind Harmer
0.711
313527AB2-043 GEN
Solar/Wind Harmer
4.254
3145493TOT1
Solar/Wind Harmer
0.404
3145453TOT5
Solar/Wind Harmer
0.242
3145603CNETO
Solar/Wind Harmer
0.162
970301AG2-198 GEN
Solar/Wind Harmer
12.986
3144293JTRSVLE
Adder
0.705
3144293JTRSVLE
Adder
0.594
3142296MT RD221
Adder
0.704
3150341NORNECKC1
Adder
1.92
3150341NORNECKC1
Adder
1.904
316447AC1-158 HLD
Solar/Wind Helper
6.042
315651AD1-115 GEN
Solar/Wind Helper
1.014
966001AG1-469 GEN
Solar/Wind Helper
0.285
3151031BRUNSWICKG2
50/50
3.97
3151101ELIZAR3
50/50
27.722
3150861SPRUNCD
50/50
1.346
3151161SURRY 1
50/50
10.381
970917AG2-570 GEN
Solar/Wind Harmer
81.486
315773AC2-141 GEN
Solar/Wind Harmer
13.395
944581AF1-123 GEN
Solar/Wind Harmer
144.734
944601AF1-125 GEN
Solar/Wind Harmer
142.475
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.031
971153AH1-033 GEN
Solar/Wind Harmer
3.829
3144536CHRHLND
Solar/Wind Harmer
-0.005
315813AE1-149 C
Solar/Wind Harmer
19.509
970659AG2-427 GEN
Solar/Wind Harmer
2.937
316083AB2-161 GEN
Solar/Wind Harmer
5.063
970661AG2-428 GEN
Solar/Wind Harmer
5.873
316320Y1-086
Solar/Wind Harmer
1.826
316435W1029_GEN3
Solar/Wind Harmer
5.597
315839AE2-212 C
Solar/Wind Harmer
0.929
3145336SMITFLD
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
3145273HOLLAND
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
3.804
3151221GRAVEL6
Adder
19.649
3151171GRAVELC
Adder
3.78
3146376EDENTON
Solar/Wind Harmer
-0.03
961611AG1-000B GEN
Solar/Wind Harmer
6.358
316365GEN2_N
Solar/Wind Harmer
2.014
316313AB2-026
Solar/Wind Harmer
0.805
316258AE1-075 C
Solar/Wind Harmer
0.725
316405AF2-144 C
Solar/Wind Harmer
0.765
3143336POWHATN
Solar/Wind Harmer
3.012
315778AD1-151 GEN
Solar/Wind Harmer
25.835
315614AA2-178 GEN
Solar/Wind Harmer
3.204
970129AG2-093 GEN
Solar/Wind Harmer
16.692
3144216WINCHST
Adder
0.987
970133AG2-095 GEN
Solar/Wind Harmer
3.307
3156081AA2-088 GEN
Solar/Wind Harmer
9.526
971157AH1-035 GEN
Solar/Wind Harmer
3.664
3150921YORKTN3
Adder
6.541
315737AD1-076 GEN
Solar/Wind Harmer
5.557
316478AD1-087 GEN
Solar/Wind Harmer
2.52
316486AD2-202 GEN
Solar/Wind Harmer
0.738
966621AG1-532 GEN
Solar/Wind Harmer
0.59
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.029
957521AF2-046 GEN
Solar/Wind Harmer
22.828
961681AG1-008 GEN
Solar/Wind Harmer
22.828
3146173TUNIS
Solar/Wind Harmer
-0.029
3156021HOLLOMANSOL
Solar/Wind Harmer
3.873
316463AE2-346 GEN
Solar/Wind Harmer
0.465
316140AB2-099
Solar/Wind Harmer
0.194
962331AG1-082 GEN
Solar/Wind Harmer
3.59
313506AB2-031 GEN
Solar/Wind Harmer
2.306
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3146263WOODLND
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.062
3143096IRON208
Adder
1.041
316382AG1-145 C
Solar/Wind Harmer
0.853
3147043LAWRENC
Solar/Wind Harmer
-0.017
316317KELFORD C
Solar/Wind Harmer
1.328
3145823KELFORD
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.112
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3142946ENON
Solar/Wind Harmer
-0.009
316210AC1-098 GEN
Solar/Wind Harmer
4.299
3145933PARMELE
Solar/Wind Harmer
-0.027
966801AG1-551 GEN
Solar/Wind Harmer
3.395
315724AD1-057 GEN
Solar/Wind Harmer
1.544
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970293AG2-193 GEN
Solar/Wind Harmer
3.331
316327AA2-057 GEN
Solar/Wind Harmer
2.686
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
3146233WITAKRS
Solar/Wind Harmer
0.548
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.017
316131AB2-060 GEN
Solar/Wind Harmer
2.82
3146073TAR RVR
Solar/Wind Harmer
-0.026
3146083TARBORO
Solar/Wind Harmer
-0.026
970909AG2-566 GEN
Solar/Wind Harmer
2.466
3141843SHACKLE
Adder
1.162
3144293JTRSVLE
Adder
0.705
3150351NORNECKC2
Adder
1.858
972255AH1-712 GEN
Adder
59.932
316044AC1-158 PL1
Solar/Wind Helper
2.745
316450AC1-158 RIC
Solar/Wind Helper
0.732
3147666LOUISA
Solar/Wind Helper
0.987
316170AC1-121 GEN2
Solar/Wind Helper
0.472
3132273ORANGE
Solar/Wind Helper
0.057
3141196NOKESVL
Solar/Wind Helper
0.931
964241AG1-285 GEN
Solar/Wind Harmer
19.851
3142543TWELFTH
Solar/Wind Harmer
-0.003
962491AG1-098 GEN
Solar/Wind Harmer
19.518
960081AF2-299 GEN
Solar/Wind Harmer
3.271
3145893MURPHYS
Solar/Wind Harmer
-0.116
3145893MURPHYS
Solar/Wind Harmer
0.862
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.259
3146173TUNIS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
971317AH1-138 GEN
Solar/Wind Harmer
3.571
316011AB1-132 GEN
Solar/Wind Harmer
5.973
962571AG1-106 GEN
Solar/Wind Harmer
4.104
3146263WOODLND
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.062
971795AH1-408 GEN
Solar/Wind Harmer
21.355
316190AA2-174 GEN
Solar/Wind Harmer
0.348
316159AE1-175 C
Solar/Wind Harmer
0.759
3147043LAWRENC
Adder
2.27
3145823KELFORD
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
119.343
3145963POPLR C
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
-0.028
316174AB2-169 GEN
Solar/Wind Harmer
4.307
316336AC2-165 C
Solar/Wind Harmer
4.835
316212AC1-099_GEN
Solar/Wind Harmer
2.388
315687AD1-152 GEN
Solar/Wind Harmer
3.298
316129AC1-054 GEN
Solar/Wind Harmer
2.39
971065AG2-659 GEN
Solar/Wind Harmer
13.588
3146293MARTNCO
Solar/Wind Harmer
0.168
315722AD1-056 GEN
Solar/Wind Harmer
2.807
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3142433PROV 92
Solar/Wind Harmer
-0.105
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
316494AC1-189 GEN
Solar/Wind Harmer
2.84
3146233WITAKRS
Solar/Wind Harmer
-0.104
316237AB2-079_GEN
Solar/Wind Harmer
0.788
961671AG1-007 GEN
Solar/Wind Harmer
0.33
3146083TARBORO
Solar/Wind Harmer
-0.026
3145493TOT1
Solar/Wind Harmer
0.775
3141843SHACKLE
Adder
1.162
3144293JTRSVLE
Adder
0.705
3150351NORNECKC2
Adder
1.828
972277AH1-723 GEN
Adder
69.838
316045AC1-158 PL2
Solar/Wind Helper
8.788
3147666LOUISA
Solar/Wind Helper
1.717
316192AB2-158 GEN
Solar/Wind Helper
2.822
316254AC1-120 GEN1
Solar/Wind Helper
1.415
316006AB2-029 C
Solar/Wind Helper
0.131
316303AF2-085
50/50
5.96
315244AE2-183_ST
50/50
8.724
963041AG1-153 GEN
50/50
8.039
315779AE2-040
50/50
4.026
3151081ELIZAR1
50/50
27.372
3151091ELIZAR2
50/50
26.896
941591AE2-156 GEN
50/50
25.004
3152611GOSPORTB
50/50
3.798
3152621GOSPORTC
50/50
3.223
3152601GOSPORTA
50/50
2.973
971285AH1-108 GEN
50/50
2.203
972263AH1-716 GEN
50/50
156.512
941031AE2-094 GEN
Solar/Wind Harmer
66.256
944011AF1-069 GEN
Solar/Wind Harmer
20.76
970673AG2-436 GEN
Solar/Wind Harmer
72.821
970673AG2-436 GEN
Solar/Wind Harmer
36.871
316233AE1-074 FULL
Solar/Wind Harmer
0.927
971281AH1-106 GEN
Solar/Wind Harmer
5.6
971283AH1-107 GEN
Solar/Wind Harmer
5.6
971967AH1-528 GEN
Solar/Wind Harmer
64.075
970085AG2-068 GEN
Solar/Wind Harmer
20.283
970581AG2-369 GEN
Solar/Wind Harmer
17.443
316315AB2-025 C
Solar/Wind Harmer
0.874
315814AE2-033 C
Solar/Wind Harmer
30.059
3143316POE
Solar/Wind Harmer
-0.126
957871AF2-081 GEN
Solar/Wind Harmer
15.731
319010AE1-072 C
Solar/Wind Harmer
6.35
3146406KITTY HAWK
Solar/Wind Harmer
0.026
316305AF2-043 C
Solar/Wind Harmer
0.944
315833AF1-017_GEN
Solar/Wind Harmer
5.92
316349AD2-085 GEN
Solar/Wind Harmer
2.772
316311AC2-079 GEN
Solar/Wind Harmer
15.721
313526AB2-022
Solar/Wind Harmer
0.84
315835AF2-110_GEN
Solar/Wind Harmer
3.894
3146486SUNBURY
Solar/Wind Harmer
-0.031
3146486SUNBURY
Solar/Wind Harmer
-0.031
316321Z2-027
Solar/Wind Harmer
0.837
3146396TANGLEW
Solar/Wind Harmer
0.571
3145176PASQUOTANK
Solar/Wind Harmer
-0.019
971445AH1-216 GEN
Solar/Wind Harmer
19.056
315611Z1-036_GEN2
Solar/Wind Harmer
7.529
972265AH1-717 GEN
Adder
20.984
3151201GRAVEL4
Adder
19.671
3151191GRAVEL3
Adder
19.422
3151211GRAVEL5
Adder
19.422
3130156CHOWAN
Solar/Wind Harmer
-0.03
3130156CHOWAN
Solar/Wind Harmer
-0.03
316369SG1_INVT
Solar/Wind Harmer
5.347
315816AE2-034 GEN
Solar/Wind Harmer
2.403
316132AB2-190 GEN1
Solar/Wind Harmer
3.001
3130546PLYMOUTH
Solar/Wind Harmer
-0.029
965291AG1-394 GEN
Solar/Wind Harmer
2.597
315732AD1-074 GEN1
Solar/Wind Harmer
5.913
315733AD1-074 GEN2
Solar/Wind Harmer
5.913
315735AD1-075 GEN1
Solar/Wind Harmer
2.957
946281AF1-292 GEN
Solar/Wind Harmer
0.651
316318V4-068
Solar/Wind Harmer
0.724
3145893MURPHYS
Solar/Wind Harmer
-0.078
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.703
316087AB2-174 GEN
Solar/Wind Harmer
4.11
3146043SEABORD
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.25
961941AG1-037 GEN
Solar/Wind Harmer
0.216
3145513AHOSKIE
Solar/Wind Harmer
-0.029
315607AA1-063A GEN
Solar/Wind Harmer
2.895
3145683EARLEYS
Solar/Wind Harmer
-0.057
3145683EARLEYS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
315652AC1-086 GEN
Solar/Wind Harmer
32.119
3137643SOCKMAN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.011
3146033SCOT NK
Solar/Wind Harmer
-0.11
957831AF2-077 GEN
Solar/Wind Harmer
0.824
3138283WHITEMARSH
Solar/Wind Harmer
0.042
970831AG2-522 GEN
Solar/Wind Harmer
13.68
316005AA1-067
Solar/Wind Harmer
0.541
3145746EVERETS
Solar/Wind Harmer
-0.106
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970181AG2-120 GEN
Solar/Wind Harmer
3.507
971167AH1-042 GEN
Solar/Wind Harmer
25.67
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
315976AC1-164 GENA
Solar/Wind Harmer
27.981
316169AC1-164_GENC
Solar/Wind Harmer
24.173
315975AC1-164 GENB
Solar/Wind Harmer
0.828
957861AF2-080 GEN
Solar/Wind Harmer
11.55
316420AA1-050 GEN
Solar/Wind Harmer
2.998
316319Z2-044 C
Solar/Wind Harmer
1.447
316239AB2-077_GEN
Solar/Wind Harmer
0.788
316238AB2-078_GEN
Solar/Wind Harmer
0.788
3145573BETHELC
Solar/Wind Harmer
-0.026
3145573BETHELC
Solar/Wind Harmer
-0.026
972205AH1-687 GEN
Adder
6.895
972189AH1-679 GEN
Adder
2.574
972193AH1-681 GEN
Adder
2.678
316164AC1-076 GEN
Solar/Wind Helper
1.627
LAGNLTFEXP_LAGN->PJM
CLTF
11.269
CBM South 2LTFEXP_CBM-S2->PJM
CBM
33.419
TVALTFEXP_TVA->PJM
CLTF
5.67
CPLELTFEXP_CPLE->PJM
CLTF
15.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
60.286
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.53
MECLTFEXP_MEC->PJM
CLTF
5.657
SIGELTFEXP_SIGE->PJM
CLTF
0.172
NYPJM->LTFIMP_NY
CLTF
3.09
LGEELTFEXP_LGEE->PJM
CLTF
2.105
WECLTFEXP_WEC->PJM
CLTF
1.07

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-1: G202_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-1: G202_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.07 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4086.88
MW Contribution:40.52
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
25.233
970531AG2-338 GEN
50/50
10.093
315242AE2-183_GT2
50/50
4.543
315241AE2-183_GT1
50/50
4.515
972185AH1-677 GEN
50/50
16.379
3151041BRUNSWICKG3
50/50
3.571
972187AH1-678 GEN
50/50
8.194
971223AH1-071 GEN
Solar/Wind Harmer
4.269
970933AG2-581 GEN
Solar/Wind Harmer
27.802
3143526WINTERP
Solar/Wind Harmer
-0.15
3144356SAPONY
Solar/Wind Harmer
0.957
970099AG2-077 GEN
Solar/Wind Harmer
33.834
316185AD1-033 GEN
Solar/Wind Harmer
2.627
3145506HICKORY
Solar/Wind Harmer
-0.099
3145506HICKORY
Solar/Wind Harmer
-0.059
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.333
316316AC1-027 C
Solar/Wind Harmer
0.762
316339AD2-160 GEN
Solar/Wind Harmer
1.675
316018AA1-139 ULT2
Solar/Wind Harmer
2.126
316017AA1-139 ULT1
Solar/Wind Harmer
2.009
3137176SLIGO L2192
Solar/Wind Harmer
-0.098
3146456SLIGO L269
Solar/Wind Harmer
2.928
3130086AYDLETT
Solar/Wind Harmer
-0.099
316036AC1-147 C
Solar/Wind Harmer
0.668
3150991CHESPKB
Adder
2.309
3150991CHESPKB
Adder
2.254
3146386ELIZ CT
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
7.663
970657AG2-426 GEN
Solar/Wind Harmer
1.602
316431W1029_GEN1
Solar/Wind Harmer
4.441
316433W1029_GEN2
Solar/Wind Harmer
4.441
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
2.543
3146376EDENTON
Solar/Wind Harmer
0.717
3146376EDENTON
Solar/Wind Harmer
0.717
316181AB2-040 GEN
Solar/Wind Harmer
3.363
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.663
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.661
3145593CAROLNA
Solar/Wind Harmer
0.196
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316426AA2-053 GEN
Solar/Wind Harmer
2.386
316065AD1-022 GEN
Solar/Wind Harmer
11.81
316236AE1-162_GEN
Solar/Wind Harmer
0.711
971741AH1-377 GEN
Solar/Wind Harmer
27.409
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145783HORNRTN
Solar/Wind Harmer
2.79
3145783HORNRTN
Solar/Wind Harmer
2.232
3145783HORNRTN
Solar/Wind Harmer
0.698
3145783HORNRTN
Solar/Wind Harmer
0.279
939181AE1-148 GEN
Solar/Wind Harmer
12.946
970301AG2-198 GEN
Solar/Wind Harmer
11.421
316274AC1-208 GEN
Solar/Wind Harmer
2.458
313527AB2-043 GEN
Solar/Wind Harmer
3.682
316240AF1-291 C
Solar/Wind Harmer
0.675
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
970323AG2-213 GEN
Solar/Wind Harmer
11.053
971775AH1-396 GEN
Solar/Wind Harmer
1.574
316034AC1-036 C
Solar/Wind Harmer
0.41
316033AB2-134 GEN
Solar/Wind Harmer
7.127
315697AD1-025 GEN
Solar/Wind Harmer
4.47
944641AF1-129 GEN
Adder
93.238
962561AG1-105 GEN
Solar/Wind Harmer
12.325
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3142366NRTHEST
Adder
0.501
3150691DARBY 3
Adder
10.867
3150701DARBY 4
Adder
10.841
3150681DARBY 2
Adder
10.829
3150671DARBY 1
Adder
10.816
3142296MT RD221
Adder
0.386
3150341NORNECKC1
Adder
1.198
3150341NORNECKC1
Adder
1.188
316447AC1-158 HLD
Solar/Wind Helper
3.615
3151031BRUNSWICKG2
50/50
3.571
970413AG2-270 GEN
50/50
21.45
3151101ELIZAR3
50/50
21.759
970917AG2-570 GEN
Solar/Wind Harmer
73.039
316313AB2-026
Solar/Wind Harmer
0.72
316258AE1-075 C
Solar/Wind Harmer
0.648
316405AF2-144 C
Solar/Wind Harmer
0.684
3143336POWHATN
Solar/Wind Harmer
2.693
316478AD1-087 GEN
Solar/Wind Harmer
2.233
316486AD2-202 GEN
Solar/Wind Harmer
0.654
316365GEN2_N
Solar/Wind Harmer
1.694
944581AF1-123 GEN
Solar/Wind Harmer
114.149
944601AF1-125 GEN
Solar/Wind Harmer
112.367
315773AC2-141 GEN
Solar/Wind Harmer
10.461
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.022
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.445
970661AG2-428 GEN
Solar/Wind Harmer
4.62
966621AG1-532 GEN
Solar/Wind Harmer
0.498
316435W1029_GEN3
Solar/Wind Harmer
4.441
316083AB2-161 GEN
Solar/Wind Harmer
3.979
970659AG2-427 GEN
Solar/Wind Harmer
2.307
3146516WINFALL
Solar/Wind Harmer
-0.024
315813AE1-149 C
Solar/Wind Harmer
15.291
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.938
3156081AA2-088 GEN
Solar/Wind Harmer
7.776
3147043LAWRENC
Solar/Wind Harmer
-0.014
315614AA2-178 GEN
Solar/Wind Harmer
2.579
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.166
3145893MURPHYS
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.716
957521AF2-046 GEN
Solar/Wind Harmer
18.692
961681AG1-008 GEN
Solar/Wind Harmer
18.692
971157AH1-035 GEN
Solar/Wind Harmer
2.963
315737AD1-076 GEN
Solar/Wind Harmer
4.498
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.381
316140AB2-099
Solar/Wind Harmer
0.159
962331AG1-082 GEN
Solar/Wind Harmer
2.944
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
3150861SPRUNCD
Adder
0.964
3156021HOLLOMANSOL
Solar/Wind Harmer
3.164
316317KELFORD C
Solar/Wind Harmer
1.095
3145823KELFORD
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.888
3145963POPLR C
Solar/Wind Harmer
-0.023
970909AG2-566 GEN
Solar/Wind Harmer
2.169
3151221GRAVEL6
Adder
14.771
3151171GRAVELC
Adder
2.842
316210AC1-098 GEN
Solar/Wind Harmer
3.58
316131AB2-060 GEN
Solar/Wind Harmer
2.441
961611AG1-000B GEN
Solar/Wind Harmer
4.747
315724AD1-057 GEN
Solar/Wind Harmer
1.295
964241AG1-285 GEN
Solar/Wind Harmer
17.552
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.798
316327AA2-057 GEN
Solar/Wind Harmer
2.249
315785AD2-033 C
Solar/Wind Harmer
5.032
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.289
959311AF2-222 GEN
Solar/Wind Harmer
22.999
3146233WITAKRS
Solar/Wind Harmer
0.46
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.014
315778AD1-151 GEN
Solar/Wind Harmer
18.993
3144293JTRSVLE
Adder
0.613
3144216WINCHST
Adder
0.711
3150921YORKTN3
Adder
4.681
3143096IRON208
Adder
0.73
3143096IRON208
Adder
0.715
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
3141843SHACKLE
Adder
0.759
3150351NORNECKC2
Adder
1.16
316044AC1-158 PL1
Solar/Wind Helper
1.642
316450AC1-158 RIC
Solar/Wind Helper
0.438
3147666LOUISA
Solar/Wind Helper
0.519
970119AG2-088 GEN
50/50
40.525
315243AE2-183_GT3
50/50
4.543
3151051BRUNSWICKS1
50/50
7.411
3151021BRUNSWICKG1
50/50
3.571
971451AH1-221 GEN
50/50
10.845
3151531CLOVER1
50/50
4.915
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.721
939411AE1-173 GEN
Solar/Wind Harmer
150.037
970919AG2-571 GEN
Solar/Wind Harmer
9.245
970087AG2-069 GEN
Solar/Wind Harmer
27.26
3143526WINTERP
Solar/Wind Harmer
-0.15
957481AF2-042 GEN
Solar/Wind Harmer
84.586
3143336POWHATN
Solar/Wind Harmer
3.168
315693AD1-088 GEN
Solar/Wind Harmer
13.025
962491AG1-098 GEN
Solar/Wind Harmer
17.31
316023GEN1_S
Solar/Wind Harmer
1.694
944591AF1-124 GEN
Solar/Wind Harmer
114.56
316294AC1-161 GEN
Solar/Wind Harmer
8.089
316388AE2-253 GEN
Solar/Wind Harmer
1.675
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.572
3150981CHESPKA
Adder
2.753
316336AC2-165 C
Solar/Wind Harmer
4.3
316246AF1-032 C
Solar/Wind Harmer
0.5
316093AE2-104_GEN
Solar/Wind Harmer
7.163
970661AG2-428 GEN
Solar/Wind Harmer
26.068
960081AF2-299 GEN
Solar/Wind Harmer
2.759
316381AD1-082 GEN
Solar/Wind Harmer
2.248
970659AG2-427 GEN
Solar/Wind Harmer
13.019
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.024
315800Z1-036_GEN1
Solar/Wind Harmer
6.004
3130156CHOWAN
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
18.101
316072AD1-144
Solar/Wind Harmer
0.488
315687AD1-152 GEN
Solar/Wind Harmer
2.903
3147043LAWRENC
Adder
1.929
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.406
316011AB1-132 GEN
Solar/Wind Harmer
4.994
962571AG1-106 GEN
Solar/Wind Harmer
3.431
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.706
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.29
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.898
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
3150851SPRUNCC
Adder
0.964
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316129AC1-054 GEN
Solar/Wind Harmer
2.042
971065AG2-659 GEN
Solar/Wind Harmer
11.627
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.526
3151171GRAVELC
Adder
2.161
316212AC1-099_GEN
Solar/Wind Harmer
1.989
315671AE2-027_GEN
Solar/Wind Harmer
17.038
316237AB2-079_GEN
Solar/Wind Harmer
0.682
961611AG1-000B GEN
Solar/Wind Harmer
11.126
315722AD1-056 GEN
Solar/Wind Harmer
2.354
3146293MARTNCO
Solar/Wind Harmer
0.139
971647AH1-324 GEN
Solar/Wind Harmer
11.16
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.363
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.469
970685AG2-442 GEN
Solar/Wind Harmer
19.125
3144293JTRSVLE
Adder
0.613
3143096IRON208
Adder
0.73
944631AF1-128 GEN
Adder
80.725
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
3141843SHACKLE
Adder
0.759
3150351NORNECKC2
Adder
1.14
316045AC1-158 PL2
Solar/Wind Helper
5.258
3147666LOUISA
Solar/Wind Helper
0.902
316303AF2-085
50/50
5.403
315244AE2-183_ST
50/50
7.855
963041AG1-153 GEN
50/50
7.23
315779AE2-040
50/50
3.41
3151541CLOVER2
50/50
4.892
941031AE2-094 GEN
Solar/Wind Harmer
59.803
944011AF1-069 GEN
Solar/Wind Harmer
18.738
970673AG2-436 GEN
Solar/Wind Harmer
65.622
970673AG2-436 GEN
Solar/Wind Harmer
33.227
971967AH1-528 GEN
Solar/Wind Harmer
57.655
970085AG2-068 GEN
Solar/Wind Harmer
18.173
970581AG2-369 GEN
Solar/Wind Harmer
15.629
316233AE1-074 FULL
Solar/Wind Harmer
0.781
971281AH1-106 GEN
Solar/Wind Harmer
4.721
971283AH1-107 GEN
Solar/Wind Harmer
4.721
316315AB2-025 C
Solar/Wind Harmer
0.74
315814AE2-033 C
Solar/Wind Harmer
25.448
3143316POE
Solar/Wind Harmer
-0.102
3151081ELIZAR1
Adder
20.247
3151091ELIZAR2
Adder
19.895
957871AF2-081 GEN
Solar/Wind Harmer
12.412
319010AE1-072 C
Solar/Wind Harmer
5.013
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.808
3152621GOSPORTC
Adder
2.383
3152601GOSPORTA
Adder
2.198
316305AF2-043 C
Solar/Wind Harmer
0.745
313526AB2-022
Solar/Wind Harmer
0.665
315835AF2-110_GEN
Solar/Wind Harmer
3.079
316321Z2-027
Solar/Wind Harmer
0.663
3146396TANGLEW
Solar/Wind Harmer
0.452
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.402
315833AF1-017_GEN
Solar/Wind Harmer
4.67
316349AD2-085 GEN
Solar/Wind Harmer
2.187
946281AF1-292 GEN
Solar/Wind Harmer
0.549
315611Z1-036_GEN2
Solar/Wind Harmer
6.004
316087AB2-174 GEN
Solar/Wind Harmer
3.457
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
965291AG1-394 GEN
Solar/Wind Harmer
2.123
315816AE2-034 GEN
Solar/Wind Harmer
1.934
315652AC1-086 GEN
Solar/Wind Harmer
26.851
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.593
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.4
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.786
315733AD1-074 GEN2
Solar/Wind Harmer
4.786
315735AD1-075 GEN1
Solar/Wind Harmer
2.394
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.322
3145513AHOSKIE
Solar/Wind Harmer
0.205
961941AG1-037 GEN
Solar/Wind Harmer
0.177
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.578
971445AH1-216 GEN
Solar/Wind Harmer
14.547
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
970831AG2-522 GEN
Solar/Wind Harmer
11.661
3146033SCOT NK
Solar/Wind Harmer
-0.092
972265AH1-717 GEN
Adder
15.775
3151201GRAVEL4
Adder
14.788
3151191GRAVEL3
Adder
14.601
3151211GRAVEL5
Adder
14.601
316239AB2-077_GEN
Solar/Wind Harmer
0.682
316238AB2-078_GEN
Solar/Wind Harmer
0.682
971443AH1-215 GEN
Solar/Wind Harmer
4.356
316005AA1-067
Solar/Wind Harmer
0.448
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.904
3144303KENBRDG
Solar/Wind Harmer
-0.018
316369SG1_INVT
Solar/Wind Harmer
3.949
957861AF2-080 GEN
Solar/Wind Harmer
9.609
316319Z2-044 C
Solar/Wind Harmer
1.213
316420AA1-050 GEN
Solar/Wind Harmer
2.5
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
972205AH1-687 GEN
Adder
5.892
970683AG2-441 GEN
Solar/Wind Harmer
7.481
970681AG2-440 GEN
Solar/Wind Harmer
5.985
LAGNLTFEXP_LAGN->PJM
CLTF
8.918
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.956
TVALTFEXP_TVA->PJM
CLTF
4.471
CPLELTFEXP_CPLE->PJM
CLTF
12.94
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.681
CBM West 1LTFEXP_CBM-W1->PJM
CBM
26.974
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.275
MECLTFEXP_MEC->PJM
CLTF
4.234
SIGELTFEXP_SIGE->PJM
CLTF
0.127
NYPJM->LTFIMP_NY
CLTF
2.444
LGEELTFEXP_LGEE->PJM
CLTF
1.534
WECLTFEXP_WEC->PJM
CLTF
0.779

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B1_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3957.44
MW Contribution:40.68
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.852
939411AE1-173 GEN
Solar/Wind Harmer
150.731
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
27.383
3143526WINTERP
Solar/Wind Harmer
-0.151
957481AF2-042 GEN
Solar/Wind Harmer
84.959
3143336POWHATN
Solar/Wind Harmer
3.179
315693AD1-088 GEN
Solar/Wind Harmer
13.081
962491AG1-098 GEN
Solar/Wind Harmer
17.384
316023GEN1_S
Solar/Wind Harmer
1.702
944591AF1-124 GEN
Solar/Wind Harmer
115.189
316294AC1-161 GEN
Solar/Wind Harmer
8.133
316388AE2-253 GEN
Solar/Wind Harmer
1.684
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.62
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.503
316336AC2-165 C
Solar/Wind Harmer
4.313
316093AE2-104_GEN
Solar/Wind Harmer
7.202
970661AG2-428 GEN
Solar/Wind Harmer
26.214
316381AD1-082 GEN
Solar/Wind Harmer
2.261
960081AF2-299 GEN
Solar/Wind Harmer
2.773
970659AG2-427 GEN
Solar/Wind Harmer
13.092
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.037
3130156CHOWAN
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
18.192
316072AD1-144
Solar/Wind Harmer
0.491
315687AD1-152 GEN
Solar/Wind Harmer
2.916
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.53
316011AB1-132 GEN
Solar/Wind Harmer
5.02
962571AG1-106 GEN
Solar/Wind Harmer
3.449
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.709
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.931
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.052
971065AG2-659 GEN
Solar/Wind Harmer
11.686
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.546
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
2
315671AE2-027_GEN
Solar/Wind Harmer
17.142
316237AB2-079_GEN
Solar/Wind Harmer
0.685
961611AG1-000B GEN
Solar/Wind Harmer
11.194
315722AD1-056 GEN
Solar/Wind Harmer
2.367
3146293MARTNCO
Solar/Wind Harmer
0.139
971647AH1-324 GEN
Solar/Wind Harmer
11.229
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.377
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.278
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.651
970685AG2-442 GEN
Solar/Wind Harmer
19.204
3144293JTRSVLE
Adder
0.615
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.311
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.153
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
4.285
970933AG2-581 GEN
Solar/Wind Harmer
27.922
3143526WINTERP
Solar/Wind Harmer
-0.151
3144356SAPONY
Solar/Wind Harmer
0.962
970099AG2-077 GEN
Solar/Wind Harmer
33.984
316185AD1-033 GEN
Solar/Wind Harmer
2.641
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.34
316316AC1-027 C
Solar/Wind Harmer
0.766
316339AD2-160 GEN
Solar/Wind Harmer
1.684
316018AA1-139 ULT2
Solar/Wind Harmer
2.138
316017AA1-139 ULT1
Solar/Wind Harmer
2.02
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.944
316036AC1-147 C
Solar/Wind Harmer
0.672
3130086AYDLETT
Solar/Wind Harmer
-0.099
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
7.706
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
4.466
316433W1029_GEN2
Solar/Wind Harmer
4.466
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
2.557
3146376EDENTON
Solar/Wind Harmer
0.721
3146376EDENTON
Solar/Wind Harmer
0.721
316181AB2-040 GEN
Solar/Wind Harmer
3.381
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.667
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.675
3145593CAROLNA
Solar/Wind Harmer
0.198
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316065AD1-022 GEN
Solar/Wind Harmer
11.875
316426AA2-053 GEN
Solar/Wind Harmer
2.399
316236AE1-162_GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.071
971741AH1-377 GEN
Solar/Wind Harmer
27.515
3145783HORNRTN
Solar/Wind Harmer
2.805
3145783HORNRTN
Solar/Wind Harmer
2.244
3145783HORNRTN
Solar/Wind Harmer
0.701
3145783HORNRTN
Solar/Wind Harmer
0.281
939181AE1-148 GEN
Solar/Wind Harmer
13.009
970301AG2-198 GEN
Solar/Wind Harmer
11.463
316274AC1-208 GEN
Solar/Wind Harmer
2.472
313527AB2-043 GEN
Solar/Wind Harmer
3.699
316240AF1-291 C
Solar/Wind Harmer
0.679
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.022
316033AB2-134 GEN
Solar/Wind Harmer
7.172
315697AD1-025 GEN
Solar/Wind Harmer
4.498
970323AG2-213 GEN
Solar/Wind Harmer
11.1
971775AH1-396 GEN
Solar/Wind Harmer
1.581
316034AC1-036 C
Solar/Wind Harmer
0.412
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
12.386
3145493TOT1
Solar/Wind Harmer
0.34
3145453TOT5
Solar/Wind Harmer
0.204
3145603CNETO
Solar/Wind Harmer
0.136
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
3142296MT RD221
Adder
0.39
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
316447AC1-158 HLD
Solar/Wind Helper
3.579
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
60.059
944011AF1-069 GEN
Solar/Wind Harmer
18.818
970673AG2-436 GEN
Solar/Wind Harmer
65.906
970673AG2-436 GEN
Solar/Wind Harmer
33.37
971967AH1-528 GEN
Solar/Wind Harmer
57.904
970085AG2-068 GEN
Solar/Wind Harmer
18.255
970581AG2-369 GEN
Solar/Wind Harmer
15.699
316233AE1-074 FULL
Solar/Wind Harmer
0.785
971281AH1-106 GEN
Solar/Wind Harmer
4.743
971283AH1-107 GEN
Solar/Wind Harmer
4.743
316315AB2-025 C
Solar/Wind Harmer
0.744
315814AE2-033 C
Solar/Wind Harmer
25.573
3143316POE
Solar/Wind Harmer
-0.102
957871AF2-081 GEN
Solar/Wind Harmer
12.48
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
5.041
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.749
313526AB2-022
Solar/Wind Harmer
0.669
315835AF2-110_GEN
Solar/Wind Harmer
3.096
316321Z2-027
Solar/Wind Harmer
0.667
3146396TANGLEW
Solar/Wind Harmer
0.455
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.471
315833AF1-017_GEN
Solar/Wind Harmer
4.696
316349AD2-085 GEN
Solar/Wind Harmer
2.199
946281AF1-292 GEN
Solar/Wind Harmer
0.552
315611Z1-036_GEN2
Solar/Wind Harmer
6.037
316087AB2-174 GEN
Solar/Wind Harmer
3.475
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
965291AG1-394 GEN
Solar/Wind Harmer
2.135
315816AE2-034 GEN
Solar/Wind Harmer
1.945
315652AC1-086 GEN
Solar/Wind Harmer
26.995
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.596
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.413
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.813
315733AD1-074 GEN2
Solar/Wind Harmer
4.813
315735AD1-075 GEN1
Solar/Wind Harmer
2.407
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.379
3145513AHOSKIE
Solar/Wind Harmer
0.206
961941AG1-037 GEN
Solar/Wind Harmer
0.178
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.632
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.72
3146033SCOT NK
Solar/Wind Harmer
-0.092
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.685
316238AB2-078_GEN
Solar/Wind Harmer
0.685
316005AA1-067
Solar/Wind Harmer
0.45
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.92
316369SG1_INVT
Solar/Wind Harmer
3.973
971443AH1-215 GEN
Solar/Wind Harmer
4.375
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.664
316319Z2-044 C
Solar/Wind Harmer
1.22
316420AA1-050 GEN
Solar/Wind Harmer
2.514
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
972205AH1-687 GEN
Adder
5.897
970683AG2-441 GEN
Solar/Wind Harmer
6.68
970681AG2-440 GEN
Solar/Wind Harmer
5.344
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
73.368
316313AB2-026
Solar/Wind Harmer
0.722
316258AE1-075 C
Solar/Wind Harmer
0.65
316405AF2-144 C
Solar/Wind Harmer
0.686
3143336POWHATN
Solar/Wind Harmer
2.702
316478AD1-087 GEN
Solar/Wind Harmer
2.243
316486AD2-202 GEN
Solar/Wind Harmer
0.657
316365GEN2_N
Solar/Wind Harmer
1.702
944581AF1-123 GEN
Solar/Wind Harmer
114.775
944601AF1-125 GEN
Solar/Wind Harmer
112.984
315773AC2-141 GEN
Solar/Wind Harmer
10.519
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.039
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.453
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
4.466
316083AB2-161 GEN
Solar/Wind Harmer
4.001
966621AG1-532 GEN
Solar/Wind Harmer
0.5
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
-0.025
315813AE1-149 C
Solar/Wind Harmer
15.377
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.948
3156081AA2-088 GEN
Solar/Wind Harmer
7.818
3147043LAWRENC
Solar/Wind Harmer
-0.014
315614AA2-178 GEN
Solar/Wind Harmer
2.593
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.72
957521AF2-046 GEN
Solar/Wind Harmer
18.794
961681AG1-008 GEN
Solar/Wind Harmer
18.794
971157AH1-035 GEN
Solar/Wind Harmer
2.979
315737AD1-076 GEN
Solar/Wind Harmer
4.523
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.383
316140AB2-099
Solar/Wind Harmer
0.16
962331AG1-082 GEN
Solar/Wind Harmer
2.96
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.182
316317KELFORD C
Solar/Wind Harmer
1.101
3145823KELFORD
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.906
3145963POPLR C
Solar/Wind Harmer
-0.023
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
3.599
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
2.453
961611AG1-000B GEN
Solar/Wind Harmer
4.776
315724AD1-057 GEN
Solar/Wind Harmer
1.302
964241AG1-285 GEN
Solar/Wind Harmer
17.632
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.814
316327AA2-057 GEN
Solar/Wind Harmer
2.261
315785AD2-033 C
Solar/Wind Harmer
5.054
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.325
959311AF2-222 GEN
Solar/Wind Harmer
23.096
3146233WITAKRS
Solar/Wind Harmer
0.462
3146233WITAKRS
Solar/Wind Harmer
-0.015
315778AD1-151 GEN
Solar/Wind Harmer
19.113
3138543CONSLDL
Solar/Wind Harmer
-0.014
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
3144293JTRSVLE
Adder
0.615
3144216WINCHST
Adder
0.716
3150921YORKTN3
Adder
4.712
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.172
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
2.393
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B2_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B2_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3957.44
MW Contribution:40.68
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.852
939411AE1-173 GEN
Solar/Wind Harmer
150.731
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
27.383
3143526WINTERP
Solar/Wind Harmer
-0.151
957481AF2-042 GEN
Solar/Wind Harmer
84.959
3143336POWHATN
Solar/Wind Harmer
3.179
315693AD1-088 GEN
Solar/Wind Harmer
13.081
962491AG1-098 GEN
Solar/Wind Harmer
17.384
316023GEN1_S
Solar/Wind Harmer
1.702
944591AF1-124 GEN
Solar/Wind Harmer
115.189
316294AC1-161 GEN
Solar/Wind Harmer
8.133
316388AE2-253 GEN
Solar/Wind Harmer
1.684
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.62
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.503
316336AC2-165 C
Solar/Wind Harmer
4.313
316093AE2-104_GEN
Solar/Wind Harmer
7.202
970661AG2-428 GEN
Solar/Wind Harmer
26.214
316381AD1-082 GEN
Solar/Wind Harmer
2.261
960081AF2-299 GEN
Solar/Wind Harmer
2.773
970659AG2-427 GEN
Solar/Wind Harmer
13.092
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.037
3130156CHOWAN
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
18.192
316072AD1-144
Solar/Wind Harmer
0.491
315687AD1-152 GEN
Solar/Wind Harmer
2.916
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.53
316011AB1-132 GEN
Solar/Wind Harmer
5.02
962571AG1-106 GEN
Solar/Wind Harmer
3.449
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.709
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.931
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.052
971065AG2-659 GEN
Solar/Wind Harmer
11.686
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.546
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
2
315671AE2-027_GEN
Solar/Wind Harmer
17.142
316237AB2-079_GEN
Solar/Wind Harmer
0.685
961611AG1-000B GEN
Solar/Wind Harmer
11.194
315722AD1-056 GEN
Solar/Wind Harmer
2.367
3146293MARTNCO
Solar/Wind Harmer
0.139
971647AH1-324 GEN
Solar/Wind Harmer
11.229
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.377
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.278
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.651
970685AG2-442 GEN
Solar/Wind Harmer
19.204
3144293JTRSVLE
Adder
0.615
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.311
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.153
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
4.285
970933AG2-581 GEN
Solar/Wind Harmer
27.922
3143526WINTERP
Solar/Wind Harmer
-0.151
3144356SAPONY
Solar/Wind Harmer
0.962
970099AG2-077 GEN
Solar/Wind Harmer
33.984
316185AD1-033 GEN
Solar/Wind Harmer
2.641
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.34
316316AC1-027 C
Solar/Wind Harmer
0.766
316339AD2-160 GEN
Solar/Wind Harmer
1.684
316018AA1-139 ULT2
Solar/Wind Harmer
2.138
316017AA1-139 ULT1
Solar/Wind Harmer
2.02
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.944
316036AC1-147 C
Solar/Wind Harmer
0.672
3130086AYDLETT
Solar/Wind Harmer
-0.099
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
7.706
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
4.466
316433W1029_GEN2
Solar/Wind Harmer
4.466
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
2.557
3146376EDENTON
Solar/Wind Harmer
0.721
3146376EDENTON
Solar/Wind Harmer
0.721
316181AB2-040 GEN
Solar/Wind Harmer
3.381
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.667
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
60.059
944011AF1-069 GEN
Solar/Wind Harmer
18.818
970673AG2-436 GEN
Solar/Wind Harmer
65.906
970673AG2-436 GEN
Solar/Wind Harmer
33.37
971967AH1-528 GEN
Solar/Wind Harmer
57.904
970085AG2-068 GEN
Solar/Wind Harmer
18.255
970581AG2-369 GEN
Solar/Wind Harmer
15.699
316233AE1-074 FULL
Solar/Wind Harmer
0.785
971281AH1-106 GEN
Solar/Wind Harmer
4.743
971283AH1-107 GEN
Solar/Wind Harmer
4.743
316315AB2-025 C
Solar/Wind Harmer
0.744
315814AE2-033 C
Solar/Wind Harmer
25.573
3143316POE
Solar/Wind Harmer
-0.102
957871AF2-081 GEN
Solar/Wind Harmer
12.48
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
5.041
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.749
313526AB2-022
Solar/Wind Harmer
0.669
315835AF2-110_GEN
Solar/Wind Harmer
3.096
316321Z2-027
Solar/Wind Harmer
0.667
3146396TANGLEW
Solar/Wind Harmer
0.455
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.471
315833AF1-017_GEN
Solar/Wind Harmer
4.696
316349AD2-085 GEN
Solar/Wind Harmer
2.199
946281AF1-292 GEN
Solar/Wind Harmer
0.552
315611Z1-036_GEN2
Solar/Wind Harmer
6.037
316087AB2-174 GEN
Solar/Wind Harmer
3.475
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
965291AG1-394 GEN
Solar/Wind Harmer
2.135
315816AE2-034 GEN
Solar/Wind Harmer
1.945
315652AC1-086 GEN
Solar/Wind Harmer
26.995
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.596
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.413
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.813
315733AD1-074 GEN2
Solar/Wind Harmer
4.813
315735AD1-075 GEN1
Solar/Wind Harmer
2.407
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.379
3145513AHOSKIE
Solar/Wind Harmer
0.206
961941AG1-037 GEN
Solar/Wind Harmer
0.178
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.632
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.72
3146033SCOT NK
Solar/Wind Harmer
-0.092
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.685
316238AB2-078_GEN
Solar/Wind Harmer
0.685
316005AA1-067
Solar/Wind Harmer
0.45
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.92
316369SG1_INVT
Solar/Wind Harmer
3.973
971443AH1-215 GEN
Solar/Wind Harmer
4.375
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.664
316319Z2-044 C
Solar/Wind Harmer
1.22
316420AA1-050 GEN
Solar/Wind Harmer
2.514
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
972205AH1-687 GEN
Adder
5.897
970683AG2-441 GEN
Solar/Wind Harmer
6.68
970681AG2-440 GEN
Solar/Wind Harmer
5.344
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
73.368
316313AB2-026
Solar/Wind Harmer
0.722
316258AE1-075 C
Solar/Wind Harmer
0.65
316405AF2-144 C
Solar/Wind Harmer
0.686
3143336POWHATN
Solar/Wind Harmer
2.702
316478AD1-087 GEN
Solar/Wind Harmer
2.243
316486AD2-202 GEN
Solar/Wind Harmer
0.657
316365GEN2_N
Solar/Wind Harmer
1.702
944581AF1-123 GEN
Solar/Wind Harmer
114.775
944601AF1-125 GEN
Solar/Wind Harmer
112.984
315773AC2-141 GEN
Solar/Wind Harmer
10.519
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.039
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.453
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
4.466
316083AB2-161 GEN
Solar/Wind Harmer
4.001
966621AG1-532 GEN
Solar/Wind Harmer
0.5
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
-0.025
315813AE1-149 C
Solar/Wind Harmer
15.377
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.948
3156081AA2-088 GEN
Solar/Wind Harmer
7.818
3147043LAWRENC
Solar/Wind Harmer
-0.014
315614AA2-178 GEN
Solar/Wind Harmer
2.593
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.72
957521AF2-046 GEN
Solar/Wind Harmer
18.794
961681AG1-008 GEN
Solar/Wind Harmer
18.794
971157AH1-035 GEN
Solar/Wind Harmer
2.979
315737AD1-076 GEN
Solar/Wind Harmer
4.523
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.383
316140AB2-099
Solar/Wind Harmer
0.16
962331AG1-082 GEN
Solar/Wind Harmer
2.96
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.182
316317KELFORD C
Solar/Wind Harmer
1.101
3145823KELFORD
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.906
3145963POPLR C
Solar/Wind Harmer
-0.023
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
3.599
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
2.453
961611AG1-000B GEN
Solar/Wind Harmer
4.776
315724AD1-057 GEN
Solar/Wind Harmer
1.302
964241AG1-285 GEN
Solar/Wind Harmer
17.632
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.814
316327AA2-057 GEN
Solar/Wind Harmer
2.261
315785AD2-033 C
Solar/Wind Harmer
5.054
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.325
959311AF2-222 GEN
Solar/Wind Harmer
23.096
3146233WITAKRS
Solar/Wind Harmer
0.462
3146233WITAKRS
Solar/Wind Harmer
-0.015
315778AD1-151 GEN
Solar/Wind Harmer
19.113
3138543CONSLDL
Solar/Wind Harmer
-0.014
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
3144293JTRSVLE
Adder
0.615
3144216WINCHST
Adder
0.716
3150921YORKTN3
Adder
4.712
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.172
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
966811AG1-552 GEN
Solar/Wind Harmer
2.675
3145593CAROLNA
Solar/Wind Harmer
0.198
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316065AD1-022 GEN
Solar/Wind Harmer
11.875
316426AA2-053 GEN
Solar/Wind Harmer
2.399
316236AE1-162_GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.071
971741AH1-377 GEN
Solar/Wind Harmer
27.515
3145783HORNRTN
Solar/Wind Harmer
2.805
3145783HORNRTN
Solar/Wind Harmer
2.244
3145783HORNRTN
Solar/Wind Harmer
0.701
3145783HORNRTN
Solar/Wind Harmer
0.281
939181AE1-148 GEN
Solar/Wind Harmer
13.009
970301AG2-198 GEN
Solar/Wind Harmer
11.463
316274AC1-208 GEN
Solar/Wind Harmer
2.472
313527AB2-043 GEN
Solar/Wind Harmer
3.699
316240AF1-291 C
Solar/Wind Harmer
0.679
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.022
316033AB2-134 GEN
Solar/Wind Harmer
7.172
315697AD1-025 GEN
Solar/Wind Harmer
4.498
970323AG2-213 GEN
Solar/Wind Harmer
11.1
971775AH1-396 GEN
Solar/Wind Harmer
1.581
316034AC1-036 C
Solar/Wind Harmer
0.412
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
12.386
3145493TOT1
Solar/Wind Harmer
0.34
3145453TOT5
Solar/Wind Harmer
0.204
3145603CNETO
Solar/Wind Harmer
0.136
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
3142296MT RD221
Adder
0.39
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
316447AC1-158 HLD
Solar/Wind Helper
3.579
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
2.393
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.34 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3619.13
MW Contribution:40.68
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
0.305
940641AE2-051 GEN
Solar/Wind Harmer
22.672
939411AE1-173 GEN
Solar/Wind Harmer
114.479
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
20.797
3143526WINTERP
Solar/Wind Harmer
1.35
957481AF2-042 GEN
Solar/Wind Harmer
64.526
3143336POWHATN
Solar/Wind Harmer
4.238
315693AD1-088 GEN
Solar/Wind Harmer
11.177
962491AG1-098 GEN
Solar/Wind Harmer
13.203
316023GEN1_S
Solar/Wind Harmer
0.504
944591AF1-124 GEN
Solar/Wind Harmer
50.741
316294AC1-161 GEN
Solar/Wind Harmer
3.877
316388AE2-253 GEN
Solar/Wind Harmer
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.222
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.1
316336AC2-165 C
Solar/Wind Harmer
0.009
316093AE2-104_GEN
Solar/Wind Harmer
3.708
970661AG2-428 GEN
Solar/Wind Harmer
21.842
316381AD1-082 GEN
Solar/Wind Harmer
0.229
960081AF2-299 GEN
Solar/Wind Harmer
2.106
970659AG2-427 GEN
Solar/Wind Harmer
10.606
3146516WINFALL
Solar/Wind Harmer
0.71
3146516WINFALL
Solar/Wind Harmer
0.219
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.216
971795AH1-408 GEN
Solar/Wind Harmer
14.392
316072AD1-144
Solar/Wind Harmer
0.078
315687AD1-152 GEN
Solar/Wind Harmer
0.007
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
0.599
971163AH1-040 GEN
Solar/Wind Harmer
17.112
316011AB1-132 GEN
Solar/Wind Harmer
3.881
962571AG1-106 GEN
Solar/Wind Harmer
3.037
3145893MURPHYS
Solar/Wind Harmer
0.851
3145893MURPHYS
Solar/Wind Harmer
0.946
3146173TUNIS
Solar/Wind Harmer
0.211
316190AA2-174 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.211
971547AH1-271 GEN
Solar/Wind Harmer
4.504
3145336SMITFLD
Solar/Wind Harmer
0.844
3145796HORNRTN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
0.211
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
316129AC1-054 GEN
Solar/Wind Harmer
0.783
971065AG2-659 GEN
Solar/Wind Harmer
8.875
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.206
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
1.056
315671AE2-027_GEN
Solar/Wind Harmer
13.019
316237AB2-079_GEN
Solar/Wind Harmer
0.002
961611AG1-000B GEN
Solar/Wind Harmer
10.587
315722AD1-056 GEN
Solar/Wind Harmer
1.275
3146293MARTNCO
Solar/Wind Harmer
0.186
971647AH1-324 GEN
Solar/Wind Harmer
8.529
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
316494AC1-189 GEN
Solar/Wind Harmer
0.664
3146233WITAKRS
Solar/Wind Harmer
0.782
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.195
3145493TOT1
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
14.585
970401AG2-262 GEN
Solar/Wind Harmer
1.143
316458AB2-190 GEN2
Solar/Wind Harmer
1.041
316359AB2-059 GEN
Solar/Wind Harmer
0.696
316049AB1-081 GEN
Solar/Wind Harmer
1.109
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.155
3142053HEARTS
Solar/Wind Harmer
0.341
970129AG2-093 GEN
Solar/Wind Harmer
5.511
963171AG1-166 GEN
Solar/Wind Harmer
1.03
971563AH1-280 GEN
Solar/Wind Harmer
2.061
3144293JTRSVLE
Adder
0.615
3138126ROCKLANDING
Solar/Wind Harmer
0.087
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
23.218
316313AB2-026
Solar/Wind Harmer
0.15
316258AE1-075 C
Solar/Wind Harmer
0.18
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.602
316478AD1-087 GEN
Solar/Wind Harmer
0.805
316486AD2-202 GEN
Solar/Wind Harmer
0.236
316365GEN2_N
Solar/Wind Harmer
0.504
944581AF1-123 GEN
Solar/Wind Harmer
50.561
944601AF1-125 GEN
Solar/Wind Harmer
49.783
315773AC2-141 GEN
Solar/Wind Harmer
8.172
3146456SLIGO L269
Solar/Wind Harmer
0.222
971153AH1-033 GEN
Solar/Wind Harmer
2.565
3144873MCLAUGH
Solar/Wind Harmer
0.006
316320Y1-086
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
0.001
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
0.219
315813AE1-149 C
Solar/Wind Harmer
11.679
3144536CHRHLND
Solar/Wind Harmer
0.033
3145273HOLLAND
Solar/Wind Harmer
0.164
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146376EDENTON
Solar/Wind Harmer
0.216
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3147043LAWRENC
Solar/Wind Harmer
0.129
315614AA2-178 GEN
Solar/Wind Harmer
1.224
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3145893MURPHYS
Solar/Wind Harmer
0.356
3145893MURPHYS
Solar/Wind Harmer
0.213
315839AE2-212 C
Solar/Wind Harmer
0.002
957521AF2-046 GEN
Solar/Wind Harmer
15.803
961681AG1-008 GEN
Solar/Wind Harmer
15.803
971157AH1-035 GEN
Solar/Wind Harmer
2.546
315737AD1-076 GEN
Solar/Wind Harmer
2.725
3146173TUNIS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
3145336SMITFLD
Solar/Wind Harmer
0.084
316463AE2-346 GEN
Solar/Wind Harmer
0.181
316140AB2-099
Solar/Wind Harmer
0.075
962331AG1-082 GEN
Solar/Wind Harmer
2.248
3145796HORNRTN
Solar/Wind Harmer
0.842
3145796HORNRTN
Solar/Wind Harmer
0.211
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.954
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
965281AG1-393 GEN
Solar/Wind Harmer
2.207
3145963POPLR C
Solar/Wind Harmer
0.206
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
1.894
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
0.636
961611AG1-000B GEN
Solar/Wind Harmer
5.383
315724AD1-057 GEN
Solar/Wind Harmer
0.756
964241AG1-285 GEN
Solar/Wind Harmer
13.392
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.335
316327AA2-057 GEN
Solar/Wind Harmer
0.301
315785AD2-033 C
Solar/Wind Harmer
1.614
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970257AG2-171 GEN
Solar/Wind Harmer
6.323
959311AF2-222 GEN
Solar/Wind Harmer
17.507
3146233WITAKRS
Solar/Wind Harmer
0.986
3146233WITAKRS
Solar/Wind Harmer
0.134
315778AD1-151 GEN
Solar/Wind Harmer
15.709
3138543CONSLDL
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.195
3146083TARBORO
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
13.786
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.194
971623AH1-311 GEN
Solar/Wind Harmer
0.388
970129AG2-093 GEN
Solar/Wind Harmer
11.71
963181AG1-167 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3147133PAMPLIN
Solar/Wind Harmer
0.602
971193AH1-056 GEN
Solar/Wind Harmer
11.673
970133AG2-095 GEN
Solar/Wind Harmer
1.824
3144216WINCHST
Adder
0.716
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.068
3150921YORKTN3
Adder
4.712
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.11
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
316382AG1-145 C
Solar/Wind Harmer
0.001
971683AH1-343 GEN
Solar/Wind Harmer
6.321
316283AC2-100 C
Solar/Wind Harmer
0.335
3142946ENON
Solar/Wind Harmer
0.055
3146776BUCKING
Solar/Wind Harmer
0.059
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316156AD2-030 GEN
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
2.658
970293AG2-193 GEN
Solar/Wind Harmer
1.582
3141766HARMONY
Solar/Wind Harmer
1.964
962971AG1-146 GEN
Solar/Wind Harmer
2.151
970009AG2-005 GEN
Solar/Wind Harmer
0.978
3142416OLDCHRC
Solar/Wind Harmer
1.237
316404AE1-155 C
Solar/Wind Harmer
0.028
970221AG2-151 GEN
Solar/Wind Harmer
6.633
3150351NORNECKC2
Adder
1.172
316473AC1-191 GEN
Solar/Wind Harmer
0.383
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
3142543TWELFTH
Solar/Wind Harmer
0.018
3146926FARMVIL
Solar/Wind Harmer
0.11
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971317AH1-138 GEN
Solar/Wind Harmer
1.337
970937AG2-583 GEN
Solar/Wind Harmer
10.797
3143096IRON208
Adder
0.735
316159AE1-175 C
Solar/Wind Harmer
0.149
944631AF1-128 GEN
Adder
81.311
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
3142433PROV 92
Solar/Wind Harmer
0.629
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
971777AH1-397 GEN
Solar/Wind Harmer
0.396
3141843SHACKLE
Adder
0.766
3141766HARMONY
Solar/Wind Harmer
0.029
3138133OCRAN
Solar/Wind Harmer
0.086
972003AH1-546 GEN
Solar/Wind Harmer
6.056
3142416OLDCHRC
Solar/Wind Harmer
0.332
3142416OLDCHRC
Solar/Wind Harmer
0.127
962861AG1-135 GEN
Solar/Wind Harmer
4.063
971377AH1-170 GEN
Solar/Wind Harmer
1.327
3147623JAMES R
Solar/Wind Harmer
0.288
3141726DUNNSVL
Solar/Wind Harmer
0.474
3150351NORNECKC2
Adder
1.153
970223AG2-152 GEN
Solar/Wind Harmer
7.902
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
3.255
970933AG2-581 GEN
Solar/Wind Harmer
21.207
3143526WINTERP
Solar/Wind Harmer
1.35
3144356SAPONY
Solar/Wind Harmer
2.053
970099AG2-077 GEN
Solar/Wind Harmer
25.81
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.89
3145506HICKORY
Solar/Wind Harmer
0.534
3145506HICKORY
Solar/Wind Harmer
0.134
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.213
316339AD2-160 GEN
Solar/Wind Harmer
0.36
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.124
3137176SLIGO L2192
Solar/Wind Harmer
0.883
3146456SLIGO L269
Solar/Wind Harmer
3.926
316036AC1-147 C
Solar/Wind Harmer
0.041
3130086AYDLETT
Solar/Wind Harmer
0.886
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
7.686
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.961
3146376EDENTON
Solar/Wind Harmer
0.961
316181AB2-040 GEN
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
3145893MURPHYS
Solar/Wind Harmer
1.424
3145893MURPHYS
Solar/Wind Harmer
0.383
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.211
966811AG1-552 GEN
Solar/Wind Harmer
2.295
3145593CAROLNA
Solar/Wind Harmer
0.263
3146173TUNIS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.211
316065AD1-022 GEN
Solar/Wind Harmer
9.733
316426AA2-053 GEN
Solar/Wind Harmer
0.714
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3145796HORNRTN
Solar/Wind Harmer
0.632
971741AH1-377 GEN
Solar/Wind Harmer
20.897
3145783HORNRTN
Solar/Wind Harmer
3.74
3145783HORNRTN
Solar/Wind Harmer
2.992
3145783HORNRTN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.374
939181AE1-148 GEN
Solar/Wind Harmer
9.88
970301AG2-198 GEN
Solar/Wind Harmer
8.706
316274AC1-208 GEN
Solar/Wind Harmer
1.058
313527AB2-043 GEN
Solar/Wind Harmer
0.003
316240AF1-291 C
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.401
3145933PARMELE
Solar/Wind Harmer
0.2
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.223
970323AG2-213 GEN
Solar/Wind Harmer
8.431
971775AH1-396 GEN
Solar/Wind Harmer
0.316
316034AC1-036 C
Solar/Wind Harmer
0.014
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
9.407
3145493TOT1
Solar/Wind Harmer
0.453
3145453TOT5
Solar/Wind Harmer
0.272
3145603CNETO
Solar/Wind Harmer
0.181
964791AG1-342 GEN
Solar/Wind Harmer
3.74
3146843MT LREL
Solar/Wind Harmer
0.195
3146843MT LREL
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
3.447
316263AC1-034 GEN
Solar/Wind Harmer
7.365
958211AF2-115 GEN
Solar/Wind Harmer
2.318
963191AG1-168 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.153
316222AC1-221 GEN
Solar/Wind Harmer
0.714
3142946ENON
Solar/Wind Harmer
0.016
3146776BUCKING
Solar/Wind Harmer
0.65
3146776BUCKING
Solar/Wind Harmer
0.053
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
316075AC2-137 C
Solar/Wind Harmer
0.04
942751AE2-291 GEN
Solar/Wind Harmer
7.378
958261AF2-120 GEN
Solar/Wind Harmer
4.15
971489AH1-241 GEN
Solar/Wind Harmer
6.633
3142296MT RD221
Adder
0.39
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
966871AG1-558 GEN
Solar/Wind Harmer
0.131
316447AC1-158 HLD
Solar/Wind Helper
3.579
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
52.507
944011AF1-069 GEN
Solar/Wind Harmer
17.156
970673AG2-436 GEN
Solar/Wind Harmer
59.565
970673AG2-436 GEN
Solar/Wind Harmer
39.71
971967AH1-528 GEN
Solar/Wind Harmer
43.86
970085AG2-068 GEN
Solar/Wind Harmer
13.865
970581AG2-369 GEN
Solar/Wind Harmer
11.924
316233AE1-074 FULL
Solar/Wind Harmer
0.208
971281AH1-106 GEN
Solar/Wind Harmer
3.602
971283AH1-107 GEN
Solar/Wind Harmer
3.602
316315AB2-025 C
Solar/Wind Harmer
0.198
315814AE2-033 C
Solar/Wind Harmer
19.336
3143316POE
Solar/Wind Harmer
0.915
957871AF2-081 GEN
Solar/Wind Harmer
11.058
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
1.117
3146406KITTY HAWK
Solar/Wind Harmer
0.028
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.119
315835AF2-110_GEN
Solar/Wind Harmer
1.513
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.607
3145176PASQUOTANK
Solar/Wind Harmer
0.136
3146486SUNBURY
Solar/Wind Harmer
0.22
3146486SUNBURY
Solar/Wind Harmer
0.22
316311AC2-079 GEN
Solar/Wind Harmer
6.318
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.151
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316087AB2-174 GEN
Solar/Wind Harmer
0.006
3130156CHOWAN
Solar/Wind Harmer
0.216
3130156CHOWAN
Solar/Wind Harmer
0.216
965291AG1-394 GEN
Solar/Wind Harmer
0.951
315816AE2-034 GEN
Solar/Wind Harmer
0.918
315652AC1-086 GEN
Solar/Wind Harmer
23.483
3137643SOCKMAN
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.574
3145893MURPHYS
Solar/Wind Harmer
0.213
3146043SEABORD
Solar/Wind Harmer
0.213
315607AA1-063A GEN
Solar/Wind Harmer
0.434
3130546PLYMOUTH
Solar/Wind Harmer
0.212
315732AD1-074 GEN1
Solar/Wind Harmer
1.217
315733AD1-074 GEN2
Solar/Wind Harmer
1.217
315735AD1-075 GEN1
Solar/Wind Harmer
0.609
3146206CASHIE
Solar/Wind Harmer
0.211
970601AG2-382 GEN
Solar/Wind Harmer
7.883
3145513AHOSKIE
Solar/Wind Harmer
0.441
3145513AHOSKIE
Solar/Wind Harmer
0.211
3145796HORNRTN
Solar/Wind Harmer
0.674
3145796HORNRTN
Solar/Wind Harmer
0.084
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.817
3145683EARLEYS
Solar/Wind Harmer
0.42
3145683EARLEYS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
970831AG2-522 GEN
Solar/Wind Harmer
8.902
3146033SCOT NK
Solar/Wind Harmer
0.823
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316005AA1-067
Solar/Wind Harmer
0.212
3145746EVERETS
Solar/Wind Harmer
0.788
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970181AG2-120 GEN
Solar/Wind Harmer
2.464
316369SG1_INVT
Solar/Wind Harmer
0.007
971443AH1-215 GEN
Solar/Wind Harmer
3.323
3144303KENBRDG
Solar/Wind Harmer
0.158
957861AF2-080 GEN
Solar/Wind Harmer
8.475
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.195
3145573BETHELC
Solar/Wind Harmer
0.195
970683AG2-441 GEN
Solar/Wind Harmer
13.022
970681AG2-440 GEN
Solar/Wind Harmer
10.418
316132AB2-190 GEN1
Solar/Wind Harmer
1.041
946301AF1-294 GEN
Solar/Wind Harmer
3.812
961791AG1-021 GEN
Solar/Wind Harmer
1.855
316118AC1-105 GEN
Solar/Wind Harmer
0.495
315657AE1-056 GEN
Solar/Wind Harmer
6.612
3147173SINAI
Solar/Wind Harmer
0.189
3147243WELCO
Solar/Wind Harmer
0.118
3138283WHITEMARSH
Solar/Wind Harmer
0.039
970285AG2-188 GEN
Solar/Wind Harmer
13.256
971845AH1-439 GEN
Solar/Wind Harmer
7.448
970865AG2-541 GEN
Solar/Wind Harmer
5.665
971167AH1-042 GEN
Solar/Wind Harmer
14.133
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3143873LANEXA
Solar/Wind Harmer
0.09
970189AG2-124 GEN
Solar/Wind Harmer
4.44
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.03
316059AD1-063 C
Solar/Wind Harmer
0.001
316123AC1-075 GEN
Solar/Wind Harmer
0.2
970165AG2-112 GEN
Solar/Wind Harmer
1.187
970163AG2-111 GEN
Solar/Wind Harmer
1.132
316314AB2-024 C
Solar/Wind Harmer
0.001
315976AC1-164 GENA
Solar/Wind Harmer
15.083
316169AC1-164_GENC
Solar/Wind Harmer
13.031
315975AC1-164 GENB
Solar/Wind Harmer
0.446
3141913WHIT STONE
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.043
3141783LANCAST
Solar/Wind Harmer
0.084
3141783LANCAST
Solar/Wind Harmer
0.056
972205AH1-687 GEN
Adder
5.897
962981AG1-147 GEN
Solar/Wind Harmer
5.019
970327AG2-215 GEN
Solar/Wind Harmer
4.3
316312AB1-027
Solar/Wind Harmer
0.228
971447AH1-217 GEN
Solar/Wind Harmer
3.55
3141813NORNECK
Solar/Wind Harmer
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
2.393
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2090-256_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2090-256_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.73 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4126.18
MW Contribution:42.18
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.624
315244AE2-183_ST
50/50
8.082
963041AG1-153 GEN
50/50
7.44
315779AE2-040
50/50
3.552
3151541CLOVER2
50/50
5.042
941031AE2-094 GEN
Solar/Wind Harmer
61.515
944011AF1-069 GEN
Solar/Wind Harmer
19.275
970673AG2-436 GEN
Solar/Wind Harmer
67.512
970673AG2-436 GEN
Solar/Wind Harmer
34.183
971967AH1-528 GEN
Solar/Wind Harmer
59.326
316233AE1-074 FULL
Solar/Wind Harmer
0.825
971281AH1-106 GEN
Solar/Wind Harmer
4.985
971283AH1-107 GEN
Solar/Wind Harmer
4.985
970533AG2-339 GEN
50/50
25.956
970531AG2-338 GEN
50/50
10.382
315242AE2-183_GT2
50/50
4.674
315241AE2-183_GT1
50/50
4.646
972185AH1-677 GEN
50/50
16.852
3151041BRUNSWICKG3
50/50
3.674
972187AH1-678 GEN
50/50
8.432
971223AH1-071 GEN
Solar/Wind Harmer
4.443
3143526WINTERP
Solar/Wind Harmer
-0.159
970933AG2-581 GEN
Solar/Wind Harmer
28.617
3144356SAPONY
Solar/Wind Harmer
0.997
970099AG2-077 GEN
Solar/Wind Harmer
34.857
316185AD1-033 GEN
Solar/Wind Harmer
2.743
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.392
316316AC1-027 C
Solar/Wind Harmer
0.796
316339AD2-160 GEN
Solar/Wind Harmer
1.749
316018AA1-139 ULT2
Solar/Wind Harmer
2.22
316017AA1-139 ULT1
Solar/Wind Harmer
2.097
316036AC1-147 C
Solar/Wind Harmer
0.698
3150991CHESPKB
Adder
2.413
3150991CHESPKB
Adder
2.355
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.057
3130086AYDLETT
Solar/Wind Harmer
-0.103
970657AG2-426 GEN
Solar/Wind Harmer
8.074
970657AG2-426 GEN
Solar/Wind Harmer
1.688
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.635
970119AG2-088 GEN
50/50
42.178
315243AE2-183_GT3
50/50
4.674
3151051BRUNSWICKS1
50/50
7.626
3151021BRUNSWICKG1
50/50
3.674
971451AH1-221 GEN
50/50
11.16
3151531CLOVER1
50/50
5.066
3143226MDLTHAN
Solar/Wind Harmer
-0.035
940641AE2-051 GEN
Solar/Wind Harmer
30.624
939411AE1-173 GEN
Solar/Wind Harmer
155.015
3143526WINTERP
Solar/Wind Harmer
-0.159
970919AG2-571 GEN
Solar/Wind Harmer
9.517
970087AG2-069 GEN
Solar/Wind Harmer
28.061
957481AF2-042 GEN
Solar/Wind Harmer
87.144
3143336POWHATN
Solar/Wind Harmer
3.295
315693AD1-088 GEN
Solar/Wind Harmer
13.425
962491AG1-098 GEN
Solar/Wind Harmer
17.843
944591AF1-124 GEN
Solar/Wind Harmer
119.528
316023GEN1_S
Solar/Wind Harmer
1.762
316294AC1-161 GEN
Solar/Wind Harmer
8.432
316388AE2-253 GEN
Solar/Wind Harmer
1.749
316375AC2-012 GEN
Solar/Wind Harmer
8.959
3150981CHESPKA
Adder
2.877
3146456SLIGO L269
Solar/Wind Harmer
-0.026
970659AG2-427 GEN
Solar/Wind Harmer
13.731
316381AD1-082 GEN
Solar/Wind Harmer
2.37
970661AG2-428 GEN
Solar/Wind Harmer
27.441
316246AF1-032 C
Solar/Wind Harmer
0.522
316093AE2-104_GEN
Solar/Wind Harmer
7.488
316336AC2-165 C
Solar/Wind Harmer
4.471
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
960081AF2-299 GEN
Solar/Wind Harmer
2.867
315800Z1-036_GEN1
Solar/Wind Harmer
6.264
3150851SPRUNCC
Adder
1.039
316072AD1-144
Solar/Wind Harmer
0.511
3130156CHOWAN
Solar/Wind Harmer
-0.025
971795AH1-408 GEN
Solar/Wind Harmer
18.794
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.356
3147043LAWRENC
Adder
2.002
315687AD1-152 GEN
Solar/Wind Harmer
2.994
316011AB1-132 GEN
Solar/Wind Harmer
5.193
962571AG1-106 GEN
Solar/Wind Harmer
3.568
3145336SMITFLD
Solar/Wind Harmer
-0.099
3145893MURPHYS
Solar/Wind Harmer
-0.099
3145893MURPHYS
Solar/Wind Harmer
0.735
3146173TUNIS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.143
316190AA2-174 GEN
Solar/Wind Harmer
0.301
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
315671AE2-027_GEN
Solar/Wind Harmer
18.264
3145823KELFORD
Solar/Wind Harmer
-0.024
3151171GRAVELC
Adder
2.286
316129AC1-054 GEN
Solar/Wind Harmer
2.115
971065AG2-659 GEN
Solar/Wind Harmer
12.042
3145963POPLR C
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
11.802
316174AB2-169 GEN
Solar/Wind Harmer
3.669
971647AH1-324 GEN
Solar/Wind Harmer
11.868
316212AC1-099_GEN
Solar/Wind Harmer
2.067
971069AG2-661 GEN
Solar/Wind Harmer
3.706
316237AB2-079_GEN
Solar/Wind Harmer
0.705
315722AD1-056 GEN
Solar/Wind Harmer
2.445
3146293MARTNCO
Solar/Wind Harmer
0.144
316433W1029_GEN2
Solar/Wind Harmer
4.635
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
2.654
3146376EDENTON
Solar/Wind Harmer
0.747
3146376EDENTON
Solar/Wind Harmer
0.747
316181AB2-040 GEN
Solar/Wind Harmer
3.495
316236AE1-162_GEN
Solar/Wind Harmer
0.748
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145893MURPHYS
Solar/Wind Harmer
0.691
3145893MURPHYS
Solar/Wind Harmer
-0.044
316065AD1-022 GEN
Solar/Wind Harmer
12.302
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.765
3145593CAROLNA
Solar/Wind Harmer
0.204
316426AA2-053 GEN
Solar/Wind Harmer
2.48
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145783HORNRTN
Solar/Wind Harmer
2.899
3145783HORNRTN
Solar/Wind Harmer
2.32
3145783HORNRTN
Solar/Wind Harmer
0.725
3145783HORNRTN
Solar/Wind Harmer
0.29
971741AH1-377 GEN
Solar/Wind Harmer
28.28
316240AF1-291 C
Solar/Wind Harmer
0.727
939181AE1-148 GEN
Solar/Wind Harmer
13.388
944641AF1-129 GEN
Adder
100.657
316274AC1-208 GEN
Solar/Wind Harmer
2.554
970301AG2-198 GEN
Solar/Wind Harmer
11.788
316033AB2-134 GEN
Solar/Wind Harmer
7.598
315697AD1-025 GEN
Solar/Wind Harmer
4.765
313527AB2-043 GEN
Solar/Wind Harmer
3.807
3145933PARMELE
Solar/Wind Harmer
-0.046
3145933PARMELE
Solar/Wind Harmer
-0.023
970323AG2-213 GEN
Solar/Wind Harmer
11.427
971775AH1-396 GEN
Solar/Wind Harmer
1.627
316034AC1-036 C
Solar/Wind Harmer
0.424
3145493TOT1
Solar/Wind Harmer
0.351
3145453TOT5
Solar/Wind Harmer
0.21
3145603CNETO
Solar/Wind Harmer
0.14
962561AG1-105 GEN
Solar/Wind Harmer
12.738
3144293JTRSVLE
Adder
0.633
3144293JTRSVLE
Adder
0.533
3142366NRTHEST
Adder
0.564
3150691DARBY 3
Adder
12.219
3150701DARBY 4
Adder
12.191
3150681DARBY 2
Adder
12.177
3150671DARBY 1
Adder
12.163
3142296MT RD221
Adder
0.462
3150341NORNECKC1
Adder
1.318
3150341NORNECKC1
Adder
1.308
316447AC1-158 HLD
Solar/Wind Helper
3.689
316458AB2-190 GEN2
Solar/Wind Harmer
2.348
970129AG2-093 GEN
Solar/Wind Harmer
5.287
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
316494AC1-189 GEN
Solar/Wind Harmer
2.455
3146233WITAKRS
Solar/Wind Harmer
-0.09
3142543TWELFTH
Solar/Wind Harmer
-0.002
961671AG1-007 GEN
Solar/Wind Harmer
0.287
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.672
3144293JTRSVLE
Adder
0.633
3143096IRON208
Adder
0.8
944631AF1-128 GEN
Adder
88.052
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
3141843SHACKLE
Adder
0.825
3150351NORNECKC2
Adder
1.255
316045AC1-158 PL2
Solar/Wind Helper
5.365
3147666LOUISA
Solar/Wind Helper
1.003
316192AB2-158 GEN
Solar/Wind Helper
1.65
970685AG2-442 GEN
Solar/Wind Harmer
7.163
3151031BRUNSWICKG2
50/50
3.674
970413AG2-270 GEN
50/50
22.109
3151101ELIZAR3
50/50
22.735
970917AG2-570 GEN
Solar/Wind Harmer
75.183
316313AB2-026
Solar/Wind Harmer
0.749
316258AE1-075 C
Solar/Wind Harmer
0.674
316405AF2-144 C
Solar/Wind Harmer
0.711
3143336POWHATN
Solar/Wind Harmer
2.8
316478AD1-087 GEN
Solar/Wind Harmer
2.301
316486AD2-202 GEN
Solar/Wind Harmer
0.674
944581AF1-123 GEN
Solar/Wind Harmer
119.099
944601AF1-125 GEN
Solar/Wind Harmer
117.241
316365GEN2_N
Solar/Wind Harmer
1.762
315773AC2-141 GEN
Solar/Wind Harmer
10.906
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.155
315813AE1-149 C
Solar/Wind Harmer
16.172
970659AG2-427 GEN
Solar/Wind Harmer
2.433
316083AB2-161 GEN
Solar/Wind Harmer
4.194
970661AG2-428 GEN
Solar/Wind Harmer
4.863
316320Y1-086
Solar/Wind Harmer
1.508
3144536CHRHLND
Solar/Wind Harmer
-0.004
316435W1029_GEN3
Solar/Wind Harmer
4.635
3146516WINFALL
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
966621AG1-532 GEN
Solar/Wind Harmer
0.517
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3150861SPRUNCD
Adder
1.039
315839AE2-212 C
Solar/Wind Harmer
0.764
3146376EDENTON
Solar/Wind Harmer
-0.025
313506AB2-031 GEN
Solar/Wind Harmer
2.014
3156081AA2-088 GEN
Solar/Wind Harmer
8.101
315614AA2-178 GEN
Solar/Wind Harmer
2.688
3147043LAWRENC
Solar/Wind Harmer
-0.015
3145336SMITFLD
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.173
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.463
961681AG1-008 GEN
Solar/Wind Harmer
19.463
965281AG1-393 GEN
Solar/Wind Harmer
3.089
971157AH1-035 GEN
Solar/Wind Harmer
3.087
315737AD1-076 GEN
Solar/Wind Harmer
4.686
3146173TUNIS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.397
316140AB2-099
Solar/Wind Harmer
0.165
962331AG1-082 GEN
Solar/Wind Harmer
3.064
3145796HORNRTN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.295
316317KELFORD C
Solar/Wind Harmer
1.139
3145823KELFORD
Solar/Wind Harmer
-0.024
3151221GRAVEL6
Adder
15.621
3151171GRAVELC
Adder
3.005
3145963POPLR C
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
5.036
316210AC1-098 GEN
Solar/Wind Harmer
3.72
970909AG2-566 GEN
Solar/Wind Harmer
2.238
315778AD1-151 GEN
Solar/Wind Harmer
20.288
316131AB2-060 GEN
Solar/Wind Harmer
2.524
315724AD1-057 GEN
Solar/Wind Harmer
1.345
3145933PARMELE
Solar/Wind Harmer
-0.023
966801AG1-551 GEN
Solar/Wind Harmer
2.91
964241AG1-285 GEN
Solar/Wind Harmer
18.149
970129AG2-093 GEN
Solar/Wind Harmer
13.053
316327AA2-057 GEN
Solar/Wind Harmer
2.335
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
315785AD2-033 C
Solar/Wind Harmer
5.203
970257AG2-171 GEN
Solar/Wind Harmer
8.57
970133AG2-095 GEN
Solar/Wind Harmer
2.571
3146233WITAKRS
Solar/Wind Harmer
0.477
3146233WITAKRS
Solar/Wind Harmer
-0.015
959311AF2-222 GEN
Solar/Wind Harmer
23.777
3138543CONSLDL
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
3144216WINCHST
Adder
0.753
3144293JTRSVLE
Adder
0.633
3150921YORKTN3
Adder
4.961
3143096IRON208
Adder
0.8
3143096IRON208
Adder
0.784
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
3141843SHACKLE
Adder
0.825
3150351NORNECKC2
Adder
1.276
316044AC1-158 PL1
Solar/Wind Helper
1.676
316450AC1-158 RIC
Solar/Wind Helper
0.447
970085AG2-068 GEN
Solar/Wind Harmer
18.707
970581AG2-369 GEN
Solar/Wind Harmer
16.088
316315AB2-025 C
Solar/Wind Harmer
0.771
315814AE2-033 C
Solar/Wind Harmer
26.508
3143316POE
Solar/Wind Harmer
-0.107
3151081ELIZAR1
Adder
21.155
3151091ELIZAR2
Adder
20.788
957871AF2-081 GEN
Solar/Wind Harmer
12.957
3152611GOSPORTB
Adder
2.934
3152621GOSPORTC
Adder
2.49
3152601GOSPORTA
Adder
2.297
319010AE1-072 C
Solar/Wind Harmer
5.234
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.778
315833AF1-017_GEN
Solar/Wind Harmer
4.898
316349AD2-085 GEN
Solar/Wind Harmer
2.293
316311AC2-079 GEN
Solar/Wind Harmer
13.006
315835AF2-110_GEN
Solar/Wind Harmer
3.219
313526AB2-022
Solar/Wind Harmer
0.694
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.692
3146396TANGLEW
Solar/Wind Harmer
0.472
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
946281AF1-292 GEN
Solar/Wind Harmer
0.571
315611Z1-036_GEN2
Solar/Wind Harmer
6.264
971285AH1-108 GEN
Adder
1.701
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
316087AB2-174 GEN
Solar/Wind Harmer
3.593
965291AG1-394 GEN
Solar/Wind Harmer
2.212
315816AE2-034 GEN
Solar/Wind Harmer
2.016
315652AC1-086 GEN
Solar/Wind Harmer
27.921
3137643SOCKMAN
Solar/Wind Harmer
-0.099
316318V4-068
Solar/Wind Harmer
0.617
3145893MURPHYS
Solar/Wind Harmer
-0.066
3145893MURPHYS
Solar/Wind Harmer
-0.025
971445AH1-216 GEN
Solar/Wind Harmer
15.317
3146043SEABORD
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.496
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
4.987
315733AD1-074 GEN2
Solar/Wind Harmer
4.987
315735AD1-075 GEN1
Solar/Wind Harmer
2.494
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.751
3145513AHOSKIE
Solar/Wind Harmer
0.214
961941AG1-037 GEN
Solar/Wind Harmer
0.184
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
12.084
972265AH1-717 GEN
Adder
16.682
3151201GRAVEL4
Adder
15.639
3151191GRAVEL3
Adder
15.441
3151211GRAVEL5
Adder
15.441
3146033SCOT NK
Solar/Wind Harmer
-0.095
316369SG1_INVT
Solar/Wind Harmer
4.209
316239AB2-077_GEN
Solar/Wind Harmer
0.705
316238AB2-078_GEN
Solar/Wind Harmer
0.705
316132AB2-190 GEN1
Solar/Wind Harmer
2.348
316005AA1-067
Solar/Wind Harmer
0.465
3145746EVERETS
Solar/Wind Harmer
-0.091
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
970181AG2-120 GEN
Solar/Wind Harmer
3.018
971443AH1-215 GEN
Solar/Wind Harmer
4.504
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.982
316319Z2-044 C
Solar/Wind Harmer
1.259
316420AA1-050 GEN
Solar/Wind Harmer
2.596
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
972205AH1-687 GEN
Adder
6.109
972189AH1-679 GEN
Adder
2.243
316164AC1-076 GEN
Solar/Wind Helper
1.087
3147666LOUISA
Solar/Wind Helper
0.577
LAGNLTFEXP_LAGN->PJM
CLTF
9.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.961
TVALTFEXP_TVA->PJM
CLTF
4.659
CPLELTFEXP_CPLE->PJM
CLTF
13.39
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.936
MECLTFEXP_MEC->PJM
CLTF
4.446
SIGELTFEXP_SIGE->PJM
CLTF
0.134
NYPJM->LTFIMP_NY
CLTF
2.509
LGEELTFEXP_LGEE->PJM
CLTF
1.615
WECLTFEXP_WEC->PJM
CLTF
0.822

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2054-2135_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2054-2135_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.47 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4115.95
MW Contribution:40.92
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
25.396
970531AG2-338 GEN
50/50
10.158
315242AE2-183_GT2
50/50
4.579
315241AE2-183_GT1
50/50
4.551
972185AH1-677 GEN
50/50
16.507
3151041BRUNSWICKG3
50/50
3.601
972187AH1-678 GEN
50/50
8.263
971223AH1-071 GEN
Solar/Wind Harmer
4.31
970933AG2-581 GEN
Solar/Wind Harmer
28.14
3143526WINTERP
Solar/Wind Harmer
-0.152
3144356SAPONY
Solar/Wind Harmer
0.965
970099AG2-077 GEN
Solar/Wind Harmer
34.511
316185AD1-033 GEN
Solar/Wind Harmer
2.642
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.341
316339AD2-160 GEN
Solar/Wind Harmer
1.685
316316AC1-027 C
Solar/Wind Harmer
0.767
316018AA1-139 ULT2
Solar/Wind Harmer
2.14
316017AA1-139 ULT1
Solar/Wind Harmer
2.021
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.947
3130086AYDLETT
Solar/Wind Harmer
-0.099
316036AC1-147 C
Solar/Wind Harmer
0.672
3150991CHESPKB
Adder
2.323
3150991CHESPKB
Adder
2.267
3146386ELIZ CT
Solar/Wind Harmer
-0.025
971741AH1-377 GEN
Solar/Wind Harmer
28.815
316431W1029_GEN1
Solar/Wind Harmer
4.473
316433W1029_GEN2
Solar/Wind Harmer
4.473
970657AG2-426 GEN
Solar/Wind Harmer
7.711
970657AG2-426 GEN
Solar/Wind Harmer
1.613
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
2.566
316181AB2-040 GEN
Solar/Wind Harmer
3.416
3146376EDENTON
Solar/Wind Harmer
0.723
3146376EDENTON
Solar/Wind Harmer
0.723
970301AG2-198 GEN
Solar/Wind Harmer
12.1
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.672
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.703
3145593CAROLNA
Solar/Wind Harmer
0.2
316426AA2-053 GEN
Solar/Wind Harmer
2.423
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
2.835
3145783HORNRTN
Solar/Wind Harmer
2.268
3145783HORNRTN
Solar/Wind Harmer
0.709
3145783HORNRTN
Solar/Wind Harmer
0.283
3145796HORNRTN
Solar/Wind Harmer
-0.071
316065AD1-022 GEN
Solar/Wind Harmer
11.938
316236AE1-162_GEN
Solar/Wind Harmer
0.715
939181AE1-148 GEN
Solar/Wind Harmer
13.315
313527AB2-043 GEN
Solar/Wind Harmer
3.812
970323AG2-213 GEN
Solar/Wind Harmer
11.586
971775AH1-396 GEN
Solar/Wind Harmer
1.65
316034AC1-036 C
Solar/Wind Harmer
0.43
316274AC1-208 GEN
Solar/Wind Harmer
2.497
958211AF2-115 GEN
Solar/Wind Harmer
3.581
963191AG1-168 GEN
Solar/Wind Harmer
2.149
3144293JTRSVLE
Adder
0.649
3144293JTRSVLE
Adder
0.547
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.023
962561AG1-105 GEN
Solar/Wind Harmer
12.73
316240AF1-291 C
Solar/Wind Harmer
0.679
944641AF1-129 GEN
Adder
93.798
3142366NRTHEST
Adder
0.504
3150691DARBY 3
Adder
10.929
3150701DARBY 4
Adder
10.903
3150681DARBY 2
Adder
10.891
3150671DARBY 1
Adder
10.878
3142296MT RD221
Adder
0.387
3150341NORNECKC1
Adder
1.196
3150341NORNECKC1
Adder
1.186
316447AC1-158 HLD
Solar/Wind Helper
3.787
966001AG1-469 GEN
Solar/Wind Helper
0.322
315651AD1-115 GEN
Solar/Wind Helper
0.849
964791AG1-342 GEN
Solar/Wind Harmer
3.241
970119AG2-088 GEN
50/50
40.916
315243AE2-183_GT3
50/50
4.579
3151051BRUNSWICKS1
50/50
7.473
3151021BRUNSWICKG1
50/50
3.601
971451AH1-221 GEN
50/50
10.937
3151531CLOVER1
50/50
5.026
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.864
939411AE1-173 GEN
Solar/Wind Harmer
150.793
970919AG2-571 GEN
Solar/Wind Harmer
9.333
970087AG2-069 GEN
Solar/Wind Harmer
27.522
3143526WINTERP
Solar/Wind Harmer
-0.152
3143336POWHATN
Solar/Wind Harmer
3.333
957481AF2-042 GEN
Solar/Wind Harmer
86.276
315693AD1-088 GEN
Solar/Wind Harmer
13.378
962491AG1-098 GEN
Solar/Wind Harmer
17.804
316336AC2-165 C
Solar/Wind Harmer
4.589
316023GEN1_S
Solar/Wind Harmer
1.714
944591AF1-124 GEN
Solar/Wind Harmer
115.211
316294AC1-161 GEN
Solar/Wind Harmer
8.131
316388AE2-253 GEN
Solar/Wind Harmer
1.685
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.622
3150981CHESPKA
Adder
2.768
960081AF2-299 GEN
Solar/Wind Harmer
2.801
316246AF1-032 C
Solar/Wind Harmer
0.503
316093AE2-104_GEN
Solar/Wind Harmer
7.211
970661AG2-428 GEN
Solar/Wind Harmer
26.234
316381AD1-082 GEN
Solar/Wind Harmer
2.262
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
970659AG2-427 GEN
Solar/Wind Harmer
13.1
315687AD1-152 GEN
Solar/Wind Harmer
2.972
971795AH1-408 GEN
Solar/Wind Harmer
18.452
315800Z1-036_GEN1
Solar/Wind Harmer
6.052
3147043LAWRENC
Adder
1.97
3130156CHOWAN
Solar/Wind Harmer
-0.024
316072AD1-144
Solar/Wind Harmer
0.491
316011AB1-132 GEN
Solar/Wind Harmer
5.061
962571AG1-106 GEN
Solar/Wind Harmer
3.477
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.621
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.714
316190AA2-174 GEN
Solar/Wind Harmer
0.294
3146173TUNIS
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.963
3146263WOODLND
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.089
971065AG2-659 GEN
Solar/Wind Harmer
11.903
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.094
3150851SPRUNCC
Adder
0.972
3145823KELFORD
Solar/Wind Harmer
-0.023
316237AB2-079_GEN
Solar/Wind Harmer
0.706
3145963POPLR C
Solar/Wind Harmer
-0.023
316212AC1-099_GEN
Solar/Wind Harmer
2.019
316174AB2-169 GEN
Solar/Wind Harmer
3.571
970685AG2-442 GEN
Solar/Wind Harmer
20.162
3151171GRAVELC
Adder
2.174
963171AG1-166 GEN
Solar/Wind Harmer
2.865
971563AH1-280 GEN
Solar/Wind Harmer
2.865
3144293JTRSVLE
Adder
0.649
315722AD1-056 GEN
Solar/Wind Harmer
2.391
315671AE2-027_GEN
Solar/Wind Harmer
17.138
3146293MARTNCO
Solar/Wind Harmer
0.141
961611AG1-000B GEN
Solar/Wind Harmer
11.191
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.193
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
3141843SHACKLE
Adder
0.762
3150351NORNECKC2
Adder
1.139
3147666LOUISA
Solar/Wind Helper
1.36
316192AB2-158 GEN
Solar/Wind Helper
2.271
316045AC1-158 PL2
Solar/Wind Helper
5.508
316254AC1-120 GEN1
Solar/Wind Helper
1.194
970401AG2-262 GEN
Solar/Wind Harmer
0.99
316303AF2-085
50/50
5.455
315244AE2-183_ST
50/50
7.916
963041AG1-153 GEN
50/50
7.291
315779AE2-040
50/50
3.435
3151541CLOVER2
50/50
5.002
941031AE2-094 GEN
Solar/Wind Harmer
60.188
944011AF1-069 GEN
Solar/Wind Harmer
18.859
970673AG2-436 GEN
Solar/Wind Harmer
66.104
970673AG2-436 GEN
Solar/Wind Harmer
33.47
971967AH1-528 GEN
Solar/Wind Harmer
58.188
970085AG2-068 GEN
Solar/Wind Harmer
18.348
970581AG2-369 GEN
Solar/Wind Harmer
15.779
316233AE1-074 FULL
Solar/Wind Harmer
0.788
971281AH1-106 GEN
Solar/Wind Harmer
4.763
971283AH1-107 GEN
Solar/Wind Harmer
4.763
316315AB2-025 C
Solar/Wind Harmer
0.746
315814AE2-033 C
Solar/Wind Harmer
25.646
3143316POE
Solar/Wind Harmer
-0.102
957871AF2-081 GEN
Solar/Wind Harmer
12.489
3151081ELIZAR1
Adder
20.363
3151091ELIZAR2
Adder
20.009
319010AE1-072 C
Solar/Wind Harmer
5.045
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.824
3152621GOSPORTC
Adder
2.397
3152601GOSPORTA
Adder
2.211
3151031BRUNSWICKG2
50/50
3.601
970413AG2-270 GEN
50/50
21.932
3151101ELIZAR3
50/50
21.884
970917AG2-570 GEN
Solar/Wind Harmer
73.734
316313AB2-026
Solar/Wind Harmer
0.757
316258AE1-075 C
Solar/Wind Harmer
0.682
316405AF2-144 C
Solar/Wind Harmer
0.719
3143336POWHATN
Solar/Wind Harmer
2.833
316478AD1-087 GEN
Solar/Wind Harmer
2.283
316486AD2-202 GEN
Solar/Wind Harmer
0.669
316365GEN2_N
Solar/Wind Harmer
1.714
944581AF1-123 GEN
Solar/Wind Harmer
114.798
944601AF1-125 GEN
Solar/Wind Harmer
113.006
315773AC2-141 GEN
Solar/Wind Harmer
10.516
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.041
3144873MCLAUGH
Solar/Wind Harmer
-0.001
966621AG1-532 GEN
Solar/Wind Harmer
0.505
316320Y1-086
Solar/Wind Harmer
1.455
316435W1029_GEN3
Solar/Wind Harmer
4.473
970661AG2-428 GEN
Solar/Wind Harmer
4.649
316083AB2-161 GEN
Solar/Wind Harmer
4.004
3146516WINFALL
Solar/Wind Harmer
-0.025
970659AG2-427 GEN
Solar/Wind Harmer
2.322
3145273HOLLAND
Solar/Wind Harmer
-0.018
315813AE1-149 C
Solar/Wind Harmer
15.384
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144536CHRHLND
Solar/Wind Harmer
-0.004
313506AB2-031 GEN
Solar/Wind Harmer
1.969
3147043LAWRENC
Solar/Wind Harmer
-0.015
3146376EDENTON
Solar/Wind Harmer
-0.024
3156081AA2-088 GEN
Solar/Wind Harmer
7.869
970909AG2-566 GEN
Solar/Wind Harmer
2.298
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
315614AA2-178 GEN
Solar/Wind Harmer
2.603
3145893MURPHYS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.923
961681AG1-008 GEN
Solar/Wind Harmer
18.923
971157AH1-035 GEN
Solar/Wind Harmer
2.994
3146173TUNIS
Solar/Wind Harmer
-0.024
315737AD1-076 GEN
Solar/Wind Harmer
4.545
315839AE2-212 C
Solar/Wind Harmer
0.72
3145796HORNRTN
Solar/Wind Harmer
-0.095
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.386
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.98
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.202
3145336SMITFLD
Solar/Wind Harmer
-0.009
3150861SPRUNCD
Adder
0.972
316317KELFORD C
Solar/Wind Harmer
1.11
3145823KELFORD
Solar/Wind Harmer
-0.023
316131AB2-060 GEN
Solar/Wind Harmer
2.53
964241AG1-285 GEN
Solar/Wind Harmer
18.252
3145963POPLR C
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.905
315785AD2-033 C
Solar/Wind Harmer
5.263
970257AG2-171 GEN
Solar/Wind Harmer
8.69
316210AC1-098 GEN
Solar/Wind Harmer
3.635
959311AF2-222 GEN
Solar/Wind Harmer
24.148
3151221GRAVEL6
Adder
14.856
3151171GRAVELC
Adder
2.858
963181AG1-167 GEN
Solar/Wind Harmer
2.149
3144293JTRSVLE
Adder
0.649
315724AD1-057 GEN
Solar/Wind Harmer
1.315
3147133PAMPLIN
Solar/Wind Harmer
-0.071
971193AH1-056 GEN
Solar/Wind Harmer
14.27
3145933PARMELE
Solar/Wind Harmer
-0.023
966801AG1-551 GEN
Solar/Wind Harmer
2.838
961611AG1-000B GEN
Solar/Wind Harmer
4.775
316327AA2-057 GEN
Solar/Wind Harmer
2.286
942461AE2-259 GEN
Solar/Wind Harmer
3.394
3144216WINCHST
Adder
0.715
3150921YORKTN3
Adder
4.706
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
3141843SHACKLE
Adder
0.762
3150351NORNECKC2
Adder
1.158
3147666LOUISA
Solar/Wind Helper
0.782
316044AC1-158 PL1
Solar/Wind Helper
1.721
316450AC1-158 RIC
Solar/Wind Helper
0.459
3132273ORANGE
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.398
946281AF1-292 GEN
Solar/Wind Harmer
0.558
316305AF2-043 C
Solar/Wind Harmer
0.75
313526AB2-022
Solar/Wind Harmer
0.67
315835AF2-110_GEN
Solar/Wind Harmer
3.1
316321Z2-027
Solar/Wind Harmer
0.668
3146396TANGLEW
Solar/Wind Harmer
0.456
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
315833AF1-017_GEN
Solar/Wind Harmer
4.701
316349AD2-085 GEN
Solar/Wind Harmer
2.201
316311AC2-079 GEN
Solar/Wind Harmer
12.483
316087AB2-174 GEN
Solar/Wind Harmer
3.511
315611Z1-036_GEN2
Solar/Wind Harmer
6.052
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
3137643SOCKMAN
Solar/Wind Harmer
-0.096
965291AG1-394 GEN
Solar/Wind Harmer
2.149
315652AC1-086 GEN
Solar/Wind Harmer
27.213
315816AE2-034 GEN
Solar/Wind Harmer
1.952
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.435
316318V4-068
Solar/Wind Harmer
0.6
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.837
315733AD1-074 GEN2
Solar/Wind Harmer
4.837
315735AD1-075 GEN1
Solar/Wind Harmer
2.419
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.436
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.922
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
971285AH1-108 GEN
Adder
1.59
971445AH1-216 GEN
Solar/Wind Harmer
14.631
316239AB2-077_GEN
Solar/Wind Harmer
0.706
316238AB2-078_GEN
Solar/Wind Harmer
0.706
3146033SCOT NK
Solar/Wind Harmer
-0.093
971443AH1-215 GEN
Solar/Wind Harmer
4.564
3144303KENBRDG
Solar/Wind Harmer
-0.019
970683AG2-441 GEN
Solar/Wind Harmer
18.002
970681AG2-440 GEN
Solar/Wind Harmer
14.401
972265AH1-717 GEN
Adder
15.866
3151201GRAVEL4
Adder
14.873
3151191GRAVEL3
Adder
14.685
3151211GRAVEL5
Adder
14.685
946301AF1-294 GEN
Solar/Wind Harmer
5.873
961791AG1-021 GEN
Solar/Wind Harmer
2.865
315657AE1-056 GEN
Solar/Wind Harmer
8.562
972205AH1-687 GEN
Adder
7.023
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
316164AC1-076 GEN
Solar/Wind Helper
1.276
LAGNLTFEXP_LAGN->PJM
CLTF
9.537
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.961
TVALTFEXP_TVA->PJM
CLTF
4.788
CPLELTFEXP_CPLE->PJM
CLTF
13.285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.685
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.441
MECLTFEXP_MEC->PJM
CLTF
4.694
SIGELTFEXP_SIGE->PJM
CLTF
0.142
NYPJM->LTFIMP_NY
CLTF
2.522
LGEELTFEXP_LGEE->PJM
CLTF
1.726
WECLTFEXP_WEC->PJM
CLTF
0.88

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57302_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57302_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.07 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:5022.16
MW Contribution:31.15
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
36.753
3151791S ANNAG2
50/50
0.935
3151781S ANNAS1
50/50
0.481
3151741LOISA C
50/50
0.953
3151751LOISA D
50/50
17.42
970119AG2-088 GEN
50/50
31.154
315243AE2-183_GT3
50/50
3.465
3151051BRUNSWICKS1
50/50
5.654
3151021BRUNSWICKG1
50/50
2.724
971451AH1-221 GEN
50/50
8.274
3147666LOUISA
Solar/Wind Harmer
-0.196
316192AB2-158 GEN
Solar/Wind Harmer
5.718
3143226MDLTHAN
Solar/Wind Harmer
-0.026
940641AE2-051 GEN
Solar/Wind Harmer
22.347
3143336POWHATN
Solar/Wind Harmer
2.653
970919AG2-571 GEN
Solar/Wind Harmer
7.047
939411AE1-173 GEN
Solar/Wind Harmer
111.228
970087AG2-069 GEN
Solar/Wind Harmer
20.777
316336AC2-165 C
Solar/Wind Harmer
3.708
3143526WINTERP
Solar/Wind Harmer
-0.11
957481AF2-042 GEN
Solar/Wind Harmer
65.731
315693AD1-088 GEN
Solar/Wind Harmer
10.265
962491AG1-098 GEN
Solar/Wind Harmer
13.684
970937AG2-583 GEN
Solar/Wind Harmer
13.455
315687AD1-152 GEN
Solar/Wind Harmer
2.252
316023GEN1_S
Solar/Wind Harmer
1.247
3146926FARMVIL
Solar/Wind Harmer
-0.011
960081AF2-299 GEN
Solar/Wind Harmer
2.052
971795AH1-408 GEN
Solar/Wind Harmer
13.624
3147043LAWRENC
Adder
1.46
963171AG1-166 GEN
Solar/Wind Harmer
2.258
971563AH1-280 GEN
Solar/Wind Harmer
2.258
3144293JTRSVLE
Adder
0.512
970685AG2-442 GEN
Solar/Wind Harmer
15.768
316237AB2-079_GEN
Solar/Wind Harmer
0.537
971065AG2-659 GEN
Solar/Wind Harmer
8.873
316129AC1-054 GEN
Solar/Wind Harmer
1.554
944591AF1-124 GEN
Solar/Wind Harmer
80.375
316011AB1-132 GEN
Solar/Wind Harmer
3.673
962571AG1-106 GEN
Solar/Wind Harmer
2.523
316322AB2-045
Solar/Wind Harmer
0.588
3146776BUCKING
Solar/Wind Harmer
-0.007
316294AC1-161 GEN
Solar/Wind Harmer
5.641
316388AE2-253 GEN
Solar/Wind Harmer
1.175
316190AA2-174 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.017
316246AF1-032 C
Solar/Wind Harmer
0.351
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.017
316093AE2-104_GEN
Solar/Wind Harmer
5.036
316375AC2-012 GEN
Solar/Wind Harmer
5.989
3150981CHESPKA
Adder
1.923
3146516WINFALL
Solar/Wind Harmer
-0.056
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
0.512
315800Z1-036_GEN1
Solar/Wind Harmer
4.254
3146263WOODLND
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
970661AG2-428 GEN
Solar/Wind Harmer
18.199
316381AD1-082 GEN
Solar/Wind Harmer
1.567
970659AG2-427 GEN
Solar/Wind Harmer
9.07
3145663CRESWEL
Solar/Wind Harmer
-0.048
971163AH1-040 GEN
Solar/Wind Harmer
16.003
3145683EARLEYS
Solar/Wind Harmer
-0.017
970401AG2-262 GEN
Solar/Wind Harmer
1.111
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.247
3145823KELFORD
Solar/Wind Harmer
-0.017
316212AC1-099_GEN
Solar/Wind Harmer
1.463
316072AD1-144
Solar/Wind Harmer
0.339
3150851SPRUNCC
Adder
0.655
3151171GRAVELC
Adder
1.459
972003AH1-546 GEN
Solar/Wind Harmer
6.164
3152261N ANNA2
50/50
36.75
3151771S ANNAG1
50/50
0.935
3151801S ANNAS2
50/50
0.481
3151761LOISA E
50/50
35.514
972183AH1-676 GEN
50/50
276.382
3151031BRUNSWICKG2
50/50
2.724
3147666LOUISA
Solar/Wind Harmer
-0.113
316313AB2-026
Solar/Wind Harmer
0.603
316258AE1-075 C
Solar/Wind Harmer
0.543
316405AF2-144 C
Solar/Wind Harmer
0.573
3143336POWHATN
Solar/Wind Harmer
2.255
970917AG2-570 GEN
Solar/Wind Harmer
55.674
316478AD1-087 GEN
Solar/Wind Harmer
1.738
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
1.825
316365GEN2_N
Solar/Wind Harmer
1.247
3146926FARMVIL
Solar/Wind Harmer
-0.011
966621AG1-532 GEN
Solar/Wind Harmer
0.37
942461AE2-259 GEN
Solar/Wind Harmer
2.731
3147043LAWRENC
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.057
971193AH1-056 GEN
Solar/Wind Harmer
11.307
963181AG1-167 GEN
Solar/Wind Harmer
1.693
3144293JTRSVLE
Adder
0.512
959311AF2-222 GEN
Solar/Wind Harmer
18.777
970257AG2-171 GEN
Solar/Wind Harmer
6.741
315785AD2-033 C
Solar/Wind Harmer
4.07
964241AG1-285 GEN
Solar/Wind Harmer
13.995
313506AB2-031 GEN
Solar/Wind Harmer
1.439
316131AB2-060 GEN
Solar/Wind Harmer
1.93
944581AF1-123 GEN
Solar/Wind Harmer
80.086
944601AF1-125 GEN
Solar/Wind Harmer
78.837
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
315773AC2-141 GEN
Solar/Wind Harmer
7.296
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.122
316320Y1-086
Solar/Wind Harmer
1.017
3151101ELIZAR3
Adder
14.333
3156081AA2-088 GEN
Solar/Wind Harmer
5.629
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.017
3145273HOLLAND
Solar/Wind Harmer
-0.013
3144873MCLAUGH
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
3.133
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.12
3145893MURPHYS
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.562
961681AG1-008 GEN
Solar/Wind Harmer
13.562
3146263WOODLND
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
970661AG2-428 GEN
Solar/Wind Harmer
3.225
316463AE2-346 GEN
Solar/Wind Harmer
0.277
316140AB2-099
Solar/Wind Harmer
0.115
962331AG1-082 GEN
Solar/Wind Harmer
2.137
316083AB2-161 GEN
Solar/Wind Harmer
2.773
970659AG2-427 GEN
Solar/Wind Harmer
1.607
315614AA2-178 GEN
Solar/Wind Harmer
1.842
971157AH1-035 GEN
Solar/Wind Harmer
2.125
315813AE1-149 C
Solar/Wind Harmer
10.623
3156021HOLLOMANSOL
Solar/Wind Harmer
2.289
3146206CASHIE
Solar/Wind Harmer
-0.017
315737AD1-076 GEN
Solar/Wind Harmer
3.228
3144536CHRHLND
Solar/Wind Harmer
-0.003
316317KELFORD C
Solar/Wind Harmer
0.799
3145823KELFORD
Solar/Wind Harmer
-0.017
316210AC1-098 GEN
Solar/Wind Harmer
2.634
3150861SPRUNCD
Adder
0.655
971133AH1-012 GEN
50/50
9.167
3151731LOISA B
50/50
17.42
3151721LOISA A
50/50
17.33
970533AG2-339 GEN
50/50
19.227
970531AG2-338 GEN
50/50
7.691
315242AE2-183_GT2
50/50
3.465
315241AE2-183_GT1
50/50
3.443
972185AH1-677 GEN
50/50
12.491
3151041BRUNSWICKG3
50/50
2.724
972187AH1-678 GEN
50/50
6.252
971223AH1-071 GEN
Solar/Wind Harmer
3.282
966001AG1-469 GEN
Solar/Wind Harmer
0.464
970933AG2-581 GEN
Solar/Wind Harmer
21.362
3143526WINTERP
Solar/Wind Harmer
-0.11
970099AG2-077 GEN
Solar/Wind Harmer
26.292
3144356SAPONY
Solar/Wind Harmer
0.703
971741AH1-377 GEN
Solar/Wind Harmer
22.699
970301AG2-198 GEN
Solar/Wind Harmer
9.614
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.822
963191AG1-168 GEN
Solar/Wind Harmer
1.693
3144293JTRSVLE
Adder
0.512
3144293JTRSVLE
Adder
0.431
316034AC1-036 C
Solar/Wind Harmer
0.333
970323AG2-213 GEN
Solar/Wind Harmer
8.988
971775AH1-396 GEN
Solar/Wind Harmer
1.28
316181AB2-040 GEN
Solar/Wind Harmer
2.496
313527AB2-043 GEN
Solar/Wind Harmer
2.904
939181AE1-148 GEN
Solar/Wind Harmer
10.04
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.97
3145593CAROLNA
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3146776BUCKING
Solar/Wind Harmer
-0.07
3146776BUCKING
Solar/Wind Harmer
-0.006
316185AD1-033 GEN
Solar/Wind Harmer
1.841
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.042
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.175
316426AA2-053 GEN
Solar/Wind Harmer
1.761
316018AA1-139 ULT2
Solar/Wind Harmer
1.493
316017AA1-139 ULT1
Solar/Wind Harmer
1.41
3137176SLIGO L2192
Solar/Wind Harmer
-0.069
3146456SLIGO L269
Solar/Wind Harmer
2.056
3130086AYDLETT
Solar/Wind Harmer
-0.069
3145783HORNRTN
Solar/Wind Harmer
2.065
3145783HORNRTN
Solar/Wind Harmer
1.652
3145783HORNRTN
Solar/Wind Harmer
0.516
3145783HORNRTN
Solar/Wind Harmer
0.206
3142956BIRDNECK
Solar/Wind Harmer
0.933
316316AC1-027 C
Solar/Wind Harmer
0.533
3146386ELIZ CT
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.812
316036AC1-147 C
Solar/Wind Harmer
0.467
3150991CHESPKB
Adder
1.613
3150991CHESPKB
Adder
1.575
316431W1029_GEN1
Solar/Wind Harmer
3.133
316433W1029_GEN2
Solar/Wind Harmer
3.133
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.481
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146376EDENTON
Solar/Wind Harmer
0.509
3146376EDENTON
Solar/Wind Harmer
0.509
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
962561AG1-105 GEN
Solar/Wind Harmer
9.645
970657AG2-426 GEN
Solar/Wind Harmer
5.345
970657AG2-426 GEN
Solar/Wind Harmer
1.118
964791AG1-342 GEN
Solar/Wind Harmer
3.634
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
316065AD1-022 GEN
Solar/Wind Harmer
8.493
316303AF2-085
50/50
4.154
315244AE2-183_ST
50/50
5.99
963041AG1-153 GEN
50/50
5.516
315779AE2-040
50/50
2.503
3147346CASHSCORNER
Solar/Wind Harmer
0.403
941031AE2-094 GEN
Solar/Wind Harmer
45.568
944011AF1-069 GEN
Solar/Wind Harmer
14.278
970673AG2-436 GEN
Solar/Wind Harmer
50.031
970673AG2-436 GEN
Solar/Wind Harmer
25.332
971967AH1-528 GEN
Solar/Wind Harmer
44.101
970085AG2-068 GEN
Solar/Wind Harmer
13.851
970581AG2-369 GEN
Solar/Wind Harmer
11.912
316233AE1-074 FULL
Solar/Wind Harmer
0.574
971281AH1-106 GEN
Solar/Wind Harmer
3.465
971283AH1-107 GEN
Solar/Wind Harmer
3.465
316315AB2-025 C
Solar/Wind Harmer
0.543
315814AE2-033 C
Solar/Wind Harmer
18.684
3143316POE
Solar/Wind Harmer
-0.072
946281AF1-292 GEN
Solar/Wind Harmer
0.409
315657AE1-056 GEN
Solar/Wind Harmer
6.784
946301AF1-294 GEN
Solar/Wind Harmer
4.628
961791AG1-021 GEN
Solar/Wind Harmer
2.258
970683AG2-441 GEN
Solar/Wind Harmer
14.079
970681AG2-440 GEN
Solar/Wind Harmer
11.263
316087AB2-174 GEN
Solar/Wind Harmer
2.568
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.538
316239AB2-077_GEN
Solar/Wind Harmer
0.537
316238AB2-078_GEN
Solar/Wind Harmer
0.537
970831AG2-522 GEN
Solar/Wind Harmer
8.853
3137643SOCKMAN
Solar/Wind Harmer
-0.07
970285AG2-188 GEN
Solar/Wind Harmer
15.458
315652AC1-086 GEN
Solar/Wind Harmer
19.749
971845AH1-439 GEN
Solar/Wind Harmer
9.317
315607AA1-063A GEN
Solar/Wind Harmer
1.762
3146043SEABORD
Solar/Wind Harmer
-0.017
957871AF2-081 GEN
Solar/Wind Harmer
8.713
319010AE1-072 C
Solar/Wind Harmer
3.521
3146406KITTY HAWK
Solar/Wind Harmer
0.014
313526AB2-022
Solar/Wind Harmer
0.468
316305AF2-043 C
Solar/Wind Harmer
0.523
3151081ELIZAR1
Adder
14.152
3151091ELIZAR2
Adder
13.906
965291AG1-394 GEN
Solar/Wind Harmer
1.539
3145796HORNRTN
Solar/Wind Harmer
-0.055
3145796HORNRTN
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.467
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3146396TANGLEW
Solar/Wind Harmer
0.319
315835AF2-110_GEN
Solar/Wind Harmer
2.165
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
3152611GOSPORTB
Adder
1.962
3152621GOSPORTC
Adder
1.665
3152601GOSPORTA
Adder
1.536
316318V4-068
Solar/Wind Harmer
0.43
3145893MURPHYS
Solar/Wind Harmer
-0.046
3145893MURPHYS
Solar/Wind Harmer
-0.017
316311AC2-079 GEN
Solar/Wind Harmer
8.691
315833AF1-017_GEN
Solar/Wind Harmer
3.272
316349AD2-085 GEN
Solar/Wind Harmer
1.532
315611Z1-036_GEN2
Solar/Wind Harmer
4.254
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.149
961941AG1-037 GEN
Solar/Wind Harmer
0.129
3145513AHOSKIE
Solar/Wind Harmer
-0.017
315816AE2-034 GEN
Solar/Wind Harmer
1.381
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3130546PLYMOUTH
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.432
315732AD1-074 GEN1
Solar/Wind Harmer
3.435
315733AD1-074 GEN2
Solar/Wind Harmer
3.435
315735AD1-075 GEN1
Solar/Wind Harmer
1.718
3146033SCOT NK
Solar/Wind Harmer
-0.067
316118AC1-105 GEN
Solar/Wind Harmer
1.149
972205AH1-687 GEN
Adder
6.275
971285AH1-108 GEN
Adder
1.072
972265AH1-717 GEN
Adder
10.649
3151201GRAVEL4
Adder
9.982
3151191GRAVEL3
Adder
9.856
3151211GRAVEL5
Adder
9.856
3151221GRAVEL6
Adder
9.971
3151171GRAVELC
Adder
1.918
3144216WINCHST
Adder
0.464
3150921YORKTN3
Adder
3.034
316274AC1-208 GEN
Solar/Wind Harmer
1.814
944641AF1-129 GEN
Adder
61.579
LAGNLTFEXP_LAGN->PJM
CLTF
6.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.792
TVALTFEXP_TVA->PJM
CLTF
3.107
CPLELTFEXP_CPLE->PJM
CLTF
9.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.98
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.411
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.458
MECLTFEXP_MEC->PJM
CLTF
2.584
SIGELTFEXP_SIGE->PJM
CLTF
0.077
NYPJM->LTFIMP_NY
CLTF
2.601
LGEELTFEXP_LGEE->PJM
CLTF
0.905
WECLTFEXP_WEC->PJM
CLTF
0.439

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:150.27 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4839.45
MW Contribution:29.41
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
10.055
3151731LOISA B
50/50
20.602
3151721LOISA A
50/50
20.496
970533AG2-339 GEN
50/50
18.118
970531AG2-338 GEN
50/50
7.247
315242AE2-183_GT2
50/50
3.266
315241AE2-183_GT1
50/50
3.246
972185AH1-677 GEN
50/50
11.773
3151041BRUNSWICKG3
50/50
2.568
972187AH1-678 GEN
50/50
5.893
316447AC1-158 HLD
Solar/Wind Harmer
7.902
966001AG1-469 GEN
Solar/Wind Harmer
0.166
971223AH1-071 GEN
Solar/Wind Harmer
2.353
970933AG2-581 GEN
Solar/Wind Harmer
15.316
315651AD1-115 GEN
Solar/Wind Harmer
0.006
3143526WINTERP
Solar/Wind Harmer
0.921
970099AG2-077 GEN
Solar/Wind Harmer
18.895
3144356SAPONY
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
16.521
970301AG2-198 GEN
Solar/Wind Harmer
7.019
3147133PAMPLIN
Solar/Wind Harmer
0.155
3147133PAMPLIN
Solar/Wind Harmer
0.124
958211AF2-115 GEN
Solar/Wind Harmer
1.852
963191AG1-168 GEN
Solar/Wind Harmer
0.617
3144293JTRSVLE
Adder
0.491
3144293JTRSVLE
Adder
0.414
3146776BUCKING
Solar/Wind Harmer
0.611
3146776BUCKING
Solar/Wind Harmer
0.049
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.518
971775AH1-396 GEN
Solar/Wind Harmer
0.244
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
7.211
316181AB2-040 GEN
Solar/Wind Harmer
0.216
3145593CAROLNA
Solar/Wind Harmer
0.146
3145593CAROLNA
Solar/Wind Harmer
0.146
966811AG1-552 GEN
Solar/Wind Harmer
1.582
3145593CAROLNA
Solar/Wind Harmer
0.182
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.087
316426AA2-053 GEN
Solar/Wind Harmer
0.49
3145783HORNRTN
Solar/Wind Harmer
2.577
3145783HORNRTN
Solar/Wind Harmer
2.062
3145783HORNRTN
Solar/Wind Harmer
0.644
3145783HORNRTN
Solar/Wind Harmer
0.258
962561AG1-105 GEN
Solar/Wind Harmer
6.941
3145796HORNRTN
Solar/Wind Harmer
0.432
3145506HICKORY
Solar/Wind Harmer
0.574
3145506HICKORY
Solar/Wind Harmer
0.344
3145506HICKORY
Solar/Wind Harmer
0.086
316185AD1-033 GEN
Solar/Wind Harmer
0.004
964791AG1-342 GEN
Solar/Wind Harmer
2.754
316339AD2-160 GEN
Solar/Wind Harmer
0.233
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.08
3137176SLIGO L2192
Solar/Wind Harmer
0.57
3146456SLIGO L269
Solar/Wind Harmer
2.535
3130086AYDLETT
Solar/Wind Harmer
0.573
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.957
3145893MURPHYS
Solar/Wind Harmer
0.257
3142956BIRDNECK
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.143
316316AC1-027 C
Solar/Wind Harmer
0.137
316431W1029_GEN1
Solar/Wind Harmer
0.001
3152251N ANNA1
50/50
35.378
3151791S ANNAG2
50/50
1.098
3151781S ANNAS1
50/50
0.564
3151741LOISA C
50/50
1.127
3151751LOISA D
50/50
20.602
970119AG2-088 GEN
50/50
29.412
315243AE2-183_GT3
50/50
3.266
3151051BRUNSWICKS1
50/50
5.329
3151021BRUNSWICKG1
50/50
2.568
971451AH1-221 GEN
50/50
7.799
316045AC1-158 PL2
Solar/Wind Harmer
11.495
3147666LOUISA
Solar/Wind Harmer
1.947
316192AB2-158 GEN
Solar/Wind Harmer
2.693
316254AC1-120 GEN1
Solar/Wind Harmer
0.471
3143226MDLTHAN
Solar/Wind Harmer
0.22
940641AE2-051 GEN
Solar/Wind Harmer
15.946
3143336POWHATN
Solar/Wind Harmer
3.398
970919AG2-571 GEN
Solar/Wind Harmer
6.642
970087AG2-069 GEN
Solar/Wind Harmer
14.871
939411AE1-173 GEN
Solar/Wind Harmer
79.115
316336AC2-165 C
Solar/Wind Harmer
0.007
3143526WINTERP
Solar/Wind Harmer
0.921
957481AF2-042 GEN
Solar/Wind Harmer
47.237
315693AD1-088 GEN
Solar/Wind Harmer
8.323
962491AG1-098 GEN
Solar/Wind Harmer
9.868
315683AE1-153 C
Solar/Wind Harmer
13.39
970937AG2-583 GEN
Solar/Wind Harmer
10.032
3146926FARMVIL
Solar/Wind Harmer
0.095
315687AD1-152 GEN
Solar/Wind Harmer
0.005
963171AG1-166 GEN
Solar/Wind Harmer
0.823
971563AH1-280 GEN
Solar/Wind Harmer
1.646
3144293JTRSVLE
Adder
0.491
316023GEN1_S
Solar/Wind Harmer
0.345
970685AG2-442 GEN
Solar/Wind Harmer
11.466
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.061
960081AF2-299 GEN
Solar/Wind Harmer
1.461
971795AH1-408 GEN
Solar/Wind Harmer
10.127
3147043LAWRENC
Adder
1.373
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971065AG2-659 GEN
Solar/Wind Harmer
6.351
316129AC1-054 GEN
Solar/Wind Harmer
0.559
972003AH1-546 GEN
Solar/Wind Harmer
6.284
316011AB1-132 GEN
Solar/Wind Harmer
2.654
962571AG1-106 GEN
Solar/Wind Harmer
2.077
316190AA2-174 GEN
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
0.145
944591AF1-124 GEN
Solar/Wind Harmer
32.725
3145796HORNRTN
Solar/Wind Harmer
0.476
3145796HORNRTN
Solar/Wind Harmer
0.144
970401AG2-262 GEN
Solar/Wind Harmer
0.842
316388AE2-253 GEN
Solar/Wind Harmer
0.449
3146456SLIGO L269
Solar/Wind Harmer
0.143
316294AC1-161 GEN
Solar/Wind Harmer
2.482
3145893MURPHYS
Solar/Wind Harmer
0.572
3145893MURPHYS
Solar/Wind Harmer
0.636
316246AF1-032 C
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.143
316093AE2-104_GEN
Solar/Wind Harmer
2.398
3146516WINFALL
Solar/Wind Harmer
0.461
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
1.776
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.141
3145663CRESWEL
Solar/Wind Harmer
0.395
971163AH1-040 GEN
Solar/Wind Harmer
11.283
3145823KELFORD
Solar/Wind Harmer
0.141
970661AG2-428 GEN
Solar/Wind Harmer
13.998
3146206CASHIE
Solar/Wind Harmer
0.14
971547AH1-271 GEN
Solar/Wind Harmer
3
316381AD1-082 GEN
Solar/Wind Harmer
0.146
970659AG2-427 GEN
Solar/Wind Harmer
6.78
316212AC1-099_GEN
Solar/Wind Harmer
0.722
315722AD1-056 GEN
Solar/Wind Harmer
0.876
3145963POPLR C
Solar/Wind Harmer
0.138
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316072AD1-144
Solar/Wind Harmer
0.05
3146293MARTNCO
Solar/Wind Harmer
0.126
3146233WITAKRS
Solar/Wind Harmer
0.538
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
971377AH1-170 GEN
Solar/Wind Harmer
1.433
3147623JAMES R
Solar/Wind Harmer
0.311
316494AC1-189 GEN
Solar/Wind Harmer
0.453
961671AG1-007 GEN
Solar/Wind Harmer
0.02
3146083TARBORO
Solar/Wind Harmer
0.134
3145493TOT1
Solar/Wind Harmer
0.595
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.48
316049AB1-081 GEN
Solar/Wind Harmer
0.765
3142053HEARTS
Solar/Wind Harmer
0.235
3145336SMITFLD
Solar/Wind Harmer
0.528
316003AC1-222 GEN
Solar/Wind Harmer
0.003
3150851SPRUNCC
Adder
0.601
3151171GRAVELC
Adder
1.335
315671AE2-027_GEN
Solar/Wind Harmer
7.939
961611AG1-000B GEN
Solar/Wind Harmer
6.453
971647AH1-324 GEN
Solar/Wind Harmer
5.166
971069AG2-661 GEN
Solar/Wind Harmer
2.09
316458AB2-190 GEN2
Solar/Wind Harmer
0.619
970129AG2-093 GEN
Solar/Wind Harmer
3.27
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.142
3146516WINFALL
Solar/Wind Harmer
0.142
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
316036AC1-147 C
Solar/Wind Harmer
0.026
3150991CHESPKB
Adder
1.49
3150991CHESPKB
Adder
1.454
3146626S HERTFORD
Solar/Wind Harmer
0.142
3146626S HERTFORD
Solar/Wind Harmer
0.142
3146376EDENTON
Solar/Wind Harmer
0.63
3146376EDENTON
Solar/Wind Harmer
0.63
316065AD1-022 GEN
Solar/Wind Harmer
6.472
970657AG2-426 GEN
Solar/Wind Harmer
4.92
970657AG2-426 GEN
Solar/Wind Harmer
1.032
316274AC1-208 GEN
Solar/Wind Harmer
0.727
3145933PARMELE
Solar/Wind Harmer
0.271
3145933PARMELE
Solar/Wind Harmer
0.135
971489AH1-241 GEN
Solar/Wind Harmer
7.167
3145493TOT1
Solar/Wind Harmer
0.31
3145453TOT5
Solar/Wind Harmer
0.186
3145603CNETO
Solar/Wind Harmer
0.124
316263AC1-034 GEN
Solar/Wind Harmer
5.078
961601AG1-000A GEN
Solar/Wind Harmer
2.374
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.509
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.134
944641AF1-129 GEN
Adder
56.042
3152261N ANNA2
50/50
35.375
3151771S ANNAG1
50/50
1.098
3151801S ANNAS2
50/50
0.564
3151761LOISA E
50/50
42.002
972183AH1-676 GEN
50/50
328.628
3151031BRUNSWICKG2
50/50
2.568
316044AC1-158 PL1
Solar/Wind Harmer
3.595
316450AC1-158 RIC
Solar/Wind Harmer
0.958
3147666LOUISA
Solar/Wind Harmer
1.12
3132273ORANGE
Solar/Wind Harmer
0.054
316170AC1-121 GEN2
Solar/Wind Harmer
0.236
316313AB2-026
Solar/Wind Harmer
0.12
316258AE1-075 C
Solar/Wind Harmer
0.144
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.888
970917AG2-570 GEN
Solar/Wind Harmer
16.604
316478AD1-087 GEN
Solar/Wind Harmer
0.59
316486AD2-202 GEN
Solar/Wind Harmer
0.173
970909AG2-566 GEN
Solar/Wind Harmer
1.755
3146926FARMVIL
Solar/Wind Harmer
0.095
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.486
971193AH1-056 GEN
Solar/Wind Harmer
9.427
963181AG1-167 GEN
Solar/Wind Harmer
0.617
3144293JTRSVLE
Adder
0.491
316365GEN2_N
Solar/Wind Harmer
0.345
959311AF2-222 GEN
Solar/Wind Harmer
13.6
3146776BUCKING
Solar/Wind Harmer
0.055
970257AG2-171 GEN
Solar/Wind Harmer
4.889
315785AD2-033 C
Solar/Wind Harmer
1.239
3147043LAWRENC
Solar/Wind Harmer
0.091
964241AG1-285 GEN
Solar/Wind Harmer
10.109
316131AB2-060 GEN
Solar/Wind Harmer
0.475
313506AB2-031 GEN
Solar/Wind Harmer
0.461
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
944581AF1-123 GEN
Solar/Wind Harmer
32.61
944601AF1-125 GEN
Solar/Wind Harmer
32.107
3145796HORNRTN
Solar/Wind Harmer
0.577
3145796HORNRTN
Solar/Wind Harmer
0.144
3156081AA2-088 GEN
Solar/Wind Harmer
0.003
3146456SLIGO L269
Solar/Wind Harmer
0.143
971153AH1-033 GEN
Solar/Wind Harmer
1.656
315773AC2-141 GEN
Solar/Wind Harmer
5.232
3145893MURPHYS
Solar/Wind Harmer
0.239
3145893MURPHYS
Solar/Wind Harmer
0.143
3145273HOLLAND
Solar/Wind Harmer
0.107
316320Y1-086
Solar/Wind Harmer
0.001
957521AF2-046 GEN
Solar/Wind Harmer
10.626
961681AG1-008 GEN
Solar/Wind Harmer
10.626
3146263WOODLND
Solar/Wind Harmer
0.143
3151101ELIZAR3
Adder
13.236
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
3144873MCLAUGH
Solar/Wind Harmer
0.004
3146626S HERTFORD
Solar/Wind Harmer
0.142
316463AE2-346 GEN
Solar/Wind Harmer
0.122
316140AB2-099
Solar/Wind Harmer
0.051
962331AG1-082 GEN
Solar/Wind Harmer
1.513
3146376EDENTON
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.807
3156021HOLLOMANSOL
Solar/Wind Harmer
0.639
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.141
970661AG2-428 GEN
Solar/Wind Harmer
2.977
3146206CASHIE
Solar/Wind Harmer
0.14
971157AH1-035 GEN
Solar/Wind Harmer
1.687
315737AD1-076 GEN
Solar/Wind Harmer
1.808
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970659AG2-427 GEN
Solar/Wind Harmer
1.483
316210AC1-098 GEN
Solar/Wind Harmer
1.296
315813AE1-149 C
Solar/Wind Harmer
7.439
3144536CHRHLND
Solar/Wind Harmer
0.021
315724AD1-057 GEN
Solar/Wind Harmer
0.519
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.888
3145963POPLR C
Solar/Wind Harmer
0.138
316327AA2-057 GEN
Solar/Wind Harmer
0.207
3145933PARMELE
Solar/Wind Harmer
0.135
966801AG1-551 GEN
Solar/Wind Harmer
1.578
3146233WITAKRS
Solar/Wind Harmer
0.679
3146233WITAKRS
Solar/Wind Harmer
0.092
3138543CONSLDL
Solar/Wind Harmer
0.089
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
970221AG2-151 GEN
Solar/Wind Harmer
7.167
3146073TAR RVR
Solar/Wind Harmer
0.134
3146083TARBORO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
971623AH1-311 GEN
Solar/Wind Harmer
0.267
961601AG1-000A GEN
Solar/Wind Harmer
9.498
315839AE2-212 C
Solar/Wind Harmer
0.001
3145336SMITFLD
Solar/Wind Harmer
0.053
3150861SPRUNCD
Adder
0.601
965281AG1-393 GEN
Solar/Wind Harmer
1.359
3151221GRAVEL6
Adder
9.127
3151171GRAVELC
Adder
1.756
971683AH1-343 GEN
Solar/Wind Harmer
4.614
961611AG1-000B GEN
Solar/Wind Harmer
3.281
316283AC2-100 C
Solar/Wind Harmer
0.239
315778AD1-151 GEN
Solar/Wind Harmer
9.406
970129AG2-093 GEN
Solar/Wind Harmer
6.948
316303AF2-085
50/50
3.922
315244AE2-183_ST
50/50
5.646
963041AG1-153 GEN
50/50
5.199
316164AC1-076 GEN
Solar/Wind Harmer
0.44
3147346CASHSCORNER
Solar/Wind Harmer
0.637
941031AE2-094 GEN
Solar/Wind Harmer
37.541
944011AF1-069 GEN
Solar/Wind Harmer
12.266
970673AG2-436 GEN
Solar/Wind Harmer
42.616
970673AG2-436 GEN
Solar/Wind Harmer
28.411
971967AH1-528 GEN
Solar/Wind Harmer
31.505
970085AG2-068 GEN
Solar/Wind Harmer
9.914
970581AG2-369 GEN
Solar/Wind Harmer
8.526
316233AE1-074 FULL
Solar/Wind Harmer
0.142
971281AH1-106 GEN
Solar/Wind Harmer
2.458
971283AH1-107 GEN
Solar/Wind Harmer
2.458
316315AB2-025 C
Solar/Wind Harmer
0.135
315814AE2-033 C
Solar/Wind Harmer
13.201
315657AE1-056 GEN
Solar/Wind Harmer
5.34
946301AF1-294 GEN
Solar/Wind Harmer
3.045
961791AG1-021 GEN
Solar/Wind Harmer
1.481
970285AG2-188 GEN
Solar/Wind Harmer
12.195
970683AG2-441 GEN
Solar/Wind Harmer
10.238
970681AG2-440 GEN
Solar/Wind Harmer
8.19
971845AH1-439 GEN
Solar/Wind Harmer
6.951
3144303KENBRDG
Solar/Wind Harmer
0.122
971443AH1-215 GEN
Solar/Wind Harmer
2.566
3143316POE
Solar/Wind Harmer
0.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316087AB2-174 GEN
Solar/Wind Harmer
0.004
970831AG2-522 GEN
Solar/Wind Harmer
6.33
3137643SOCKMAN
Solar/Wind Harmer
0.589
972205AH1-687 GEN
Adder
6.271
315652AC1-086 GEN
Solar/Wind Harmer
16.059
315607AA1-063A GEN
Solar/Wind Harmer
0.296
3146043SEABORD
Solar/Wind Harmer
0.145
3145796HORNRTN
Solar/Wind Harmer
0.461
3145796HORNRTN
Solar/Wind Harmer
0.058
965291AG1-394 GEN
Solar/Wind Harmer
0.639
957871AF2-081 GEN
Solar/Wind Harmer
7.137
319010AE1-072 C
Solar/Wind Harmer
0.721
3146406KITTY HAWK
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.386
3145893MURPHYS
Solar/Wind Harmer
0.143
313526AB2-022
Solar/Wind Harmer
0.077
316305AF2-043 C
Solar/Wind Harmer
0.001
316321Z2-027
Solar/Wind Harmer
0.027
3146396TANGLEW
Solar/Wind Harmer
0.393
3145176PASQUOTANK
Solar/Wind Harmer
0.088
3151081ELIZAR1
Adder
13.069
3151091ELIZAR2
Adder
12.842
3146486SUNBURY
Solar/Wind Harmer
0.142
3146486SUNBURY
Solar/Wind Harmer
0.142
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3152611GOSPORTB
Adder
1.811
3152621GOSPORTC
Adder
1.537
3152601GOSPORTA
Adder
1.418
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145513AHOSKIE
Solar/Wind Harmer
0.297
3145513AHOSKIE
Solar/Wind Harmer
0.142
316311AC2-079 GEN
Solar/Wind Harmer
4.069
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.097
3130156CHOWAN
Solar/Wind Harmer
0.142
3130156CHOWAN
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.283
3145683EARLEYS
Solar/Wind Harmer
0.141
3145683EARLEYS
Solar/Wind Harmer
0.141
315816AE2-034 GEN
Solar/Wind Harmer
0.605
316118AC1-105 GEN
Solar/Wind Harmer
0.363
3146206CASHIE
Solar/Wind Harmer
0.14
970601AG2-382 GEN
Solar/Wind Harmer
5.25
3130546PLYMOUTH
Solar/Wind Harmer
0.14
315732AD1-074 GEN1
Solar/Wind Harmer
0.807
315733AD1-074 GEN2
Solar/Wind Harmer
0.807
315735AD1-075 GEN1
Solar/Wind Harmer
0.404
3146033SCOT NK
Solar/Wind Harmer
0.56
3147173SINAI
Solar/Wind Harmer
0.138
3147243WELCO
Solar/Wind Harmer
0.086
316319Z2-044 C
Solar/Wind Harmer
0
316005AA1-067
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.535
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
970181AG2-120 GEN
Solar/Wind Harmer
1.673
957861AF2-080 GEN
Solar/Wind Harmer
5.784
316420AA1-050 GEN
Solar/Wind Harmer
0.004
3145573BETHELC
Solar/Wind Harmer
0.134
3145573BETHELC
Solar/Wind Harmer
0.134
971445AH1-216 GEN
Solar/Wind Harmer
9.249
971285AH1-108 GEN
Adder
0.983
971447AH1-217 GEN
Solar/Wind Harmer
3.898
972265AH1-717 GEN
Adder
9.747
3151201GRAVEL4
Adder
9.137
3151191GRAVEL3
Adder
9.022
3151211GRAVEL5
Adder
9.022
970865AG2-541 GEN
Solar/Wind Harmer
4.136
316369SG1_INVT
Solar/Wind Harmer
0.004
316132AB2-190 GEN1
Solar/Wind Harmer
0.619
270494AE1-108_GEN
Solar/Wind Harmer
1.368
LAGNLTFEXP_LAGN->PJM
CLTF
5.7
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.49
TVALTFEXP_TVA->PJM
CLTF
2.869
CPLELTFEXP_CPLE->PJM
CLTF
9.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.38
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.621
MECLTFEXP_MEC->PJM
CLTF
2.309
SIGELTFEXP_SIGE->PJM
CLTF
0.069
NYPJM->LTFIMP_NY
CLTF
2.592
LGEELTFEXP_LGEE->PJM
CLTF
0.801
WECLTFEXP_WEC->PJM
CLTF
0.384

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:147.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4748.6
MW Contribution:30.86
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
36.46
3151791S ANNAG2
50/50
1.04
3151781S ANNAS1
50/50
0.534
3151741LOISA C
50/50
1.06
3151751LOISA D
50/50
19.381
970119AG2-088 GEN
50/50
30.855
315243AE2-183_GT3
50/50
3.43
3151051BRUNSWICKS1
50/50
5.597
3151021BRUNSWICKG1
50/50
2.697
971451AH1-221 GEN
50/50
8.191
3147666LOUISA
Solar/Wind Harmer
1.943
316192AB2-158 GEN
Solar/Wind Harmer
2.682
3143226MDLTHAN
Solar/Wind Harmer
0.231
940641AE2-051 GEN
Solar/Wind Harmer
16.781
3143336POWHATN
Solar/Wind Harmer
3.536
970919AG2-571 GEN
Solar/Wind Harmer
6.978
939411AE1-173 GEN
Solar/Wind Harmer
83.474
970087AG2-069 GEN
Solar/Wind Harmer
15.624
316336AC2-165 C
Solar/Wind Harmer
0.007
3143526WINTERP
Solar/Wind Harmer
0.974
957481AF2-042 GEN
Solar/Wind Harmer
49.548
315693AD1-088 GEN
Solar/Wind Harmer
8.718
962491AG1-098 GEN
Solar/Wind Harmer
10.335
970937AG2-583 GEN
Solar/Wind Harmer
10.339
315687AD1-152 GEN
Solar/Wind Harmer
0.005
3146926FARMVIL
Solar/Wind Harmer
0.098
316023GEN1_S
Solar/Wind Harmer
0.365
963171AG1-166 GEN
Solar/Wind Harmer
0.858
971563AH1-280 GEN
Solar/Wind Harmer
1.716
3144293JTRSVLE
Adder
0.512
960081AF2-299 GEN
Solar/Wind Harmer
1.543
970685AG2-442 GEN
Solar/Wind Harmer
11.971
971795AH1-408 GEN
Solar/Wind Harmer
10.682
3147043LAWRENC
Adder
1.448
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.063
971065AG2-659 GEN
Solar/Wind Harmer
6.688
316129AC1-054 GEN
Solar/Wind Harmer
0.589
316011AB1-132 GEN
Solar/Wind Harmer
2.809
962571AG1-106 GEN
Solar/Wind Harmer
2.198
944591AF1-124 GEN
Solar/Wind Harmer
34.895
316190AA2-174 GEN
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
0.153
316388AE2-253 GEN
Solar/Wind Harmer
0.479
316294AC1-161 GEN
Solar/Wind Harmer
2.649
3146456SLIGO L269
Solar/Wind Harmer
0.153
3145796HORNRTN
Solar/Wind Harmer
0.503
3145796HORNRTN
Solar/Wind Harmer
0.152
315683AE1-153 C
Solar/Wind Harmer
12.128
316246AF1-032 C
Solar/Wind Harmer
0.069
316093AE2-104_GEN
Solar/Wind Harmer
2.556
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
1.895
3145893MURPHYS
Solar/Wind Harmer
0.607
3145893MURPHYS
Solar/Wind Harmer
0.674
3146516WINFALL
Solar/Wind Harmer
0.491
3146516WINFALL
Solar/Wind Harmer
0.152
972003AH1-546 GEN
Solar/Wind Harmer
6.434
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146263WOODLND
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
0.151
970401AG2-262 GEN
Solar/Wind Harmer
0.884
970661AG2-428 GEN
Solar/Wind Harmer
14.943
3145683EARLEYS
Solar/Wind Harmer
0.15
3145663CRESWEL
Solar/Wind Harmer
0.42
971163AH1-040 GEN
Solar/Wind Harmer
11.998
316381AD1-082 GEN
Solar/Wind Harmer
0.156
970659AG2-427 GEN
Solar/Wind Harmer
7.24
3146206CASHIE
Solar/Wind Harmer
0.149
971547AH1-271 GEN
Solar/Wind Harmer
3.186
3145823KELFORD
Solar/Wind Harmer
0.149
316212AC1-099_GEN
Solar/Wind Harmer
0.765
316072AD1-144
Solar/Wind Harmer
0.053
315722AD1-056 GEN
Solar/Wind Harmer
0.927
3145963POPLR C
Solar/Wind Harmer
0.146
316174AB2-169 GEN
Solar/Wind Harmer
0.004
3146293MARTNCO
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
0.569
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
316494AC1-189 GEN
Solar/Wind Harmer
0.48
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.142
3145493TOT1
Solar/Wind Harmer
0.63
3145336SMITFLD
Solar/Wind Harmer
0.565
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.113
316359AB2-059 GEN
Solar/Wind Harmer
0.508
316049AB1-081 GEN
Solar/Wind Harmer
0.809
3142053HEARTS
Solar/Wind Harmer
0.249
3150851SPRUNCC
Adder
0.645
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.465
3147623JAMES R
Solar/Wind Harmer
0.318
3151171GRAVELC
Adder
1.435
315671AE2-027_GEN
Solar/Wind Harmer
8.542
961611AG1-000B GEN
Solar/Wind Harmer
6.943
971647AH1-324 GEN
Solar/Wind Harmer
5.564
971069AG2-661 GEN
Solar/Wind Harmer
2.256
316458AB2-190 GEN2
Solar/Wind Harmer
0.669
971133AH1-012 GEN
50/50
10.162
3151731LOISA B
50/50
19.381
3151721LOISA A
50/50
19.281
970533AG2-339 GEN
50/50
19.027
970531AG2-338 GEN
50/50
7.611
315242AE2-183_GT2
50/50
3.43
315241AE2-183_GT1
50/50
3.409
972185AH1-677 GEN
50/50
12.365
3151041BRUNSWICKG3
50/50
2.697
972187AH1-678 GEN
50/50
6.189
966001AG1-469 GEN
Solar/Wind Harmer
0.142
971223AH1-071 GEN
Solar/Wind Harmer
2.468
970933AG2-581 GEN
Solar/Wind Harmer
16.076
3143526WINTERP
Solar/Wind Harmer
0.974
970099AG2-077 GEN
Solar/Wind Harmer
19.819
3144356SAPONY
Solar/Wind Harmer
1.482
971741AH1-377 GEN
Solar/Wind Harmer
17.227
970301AG2-198 GEN
Solar/Wind Harmer
7.308
3147133PAMPLIN
Solar/Wind Harmer
0.161
3147133PAMPLIN
Solar/Wind Harmer
0.129
958211AF2-115 GEN
Solar/Wind Harmer
1.931
963191AG1-168 GEN
Solar/Wind Harmer
0.644
3144293JTRSVLE
Adder
0.512
3144293JTRSVLE
Adder
0.431
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
6.815
971775AH1-396 GEN
Solar/Wind Harmer
0.256
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
7.578
316181AB2-040 GEN
Solar/Wind Harmer
0.229
3146776BUCKING
Solar/Wind Harmer
0.63
3146776BUCKING
Solar/Wind Harmer
0.051
3145593CAROLNA
Solar/Wind Harmer
0.154
3145593CAROLNA
Solar/Wind Harmer
0.154
966811AG1-552 GEN
Solar/Wind Harmer
1.673
3145593CAROLNA
Solar/Wind Harmer
0.192
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.518
3145783HORNRTN
Solar/Wind Harmer
2.725
3145783HORNRTN
Solar/Wind Harmer
2.18
3145783HORNRTN
Solar/Wind Harmer
0.681
3145783HORNRTN
Solar/Wind Harmer
0.273
316185AD1-033 GEN
Solar/Wind Harmer
0.004
3145506HICKORY
Solar/Wind Harmer
0.612
3145506HICKORY
Solar/Wind Harmer
0.367
3145506HICKORY
Solar/Wind Harmer
0.092
316339AD2-160 GEN
Solar/Wind Harmer
0.248
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.085
3137176SLIGO L2192
Solar/Wind Harmer
0.608
3146456SLIGO L269
Solar/Wind Harmer
2.703
3130086AYDLETT
Solar/Wind Harmer
0.61
3145796HORNRTN
Solar/Wind Harmer
0.458
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.146
3146386ELIZ CT
Solar/Wind Harmer
0.152
315742AE1-103 GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.028
3150991CHESPKB
Adder
1.59
3150991CHESPKB
Adder
1.552
962561AG1-105 GEN
Solar/Wind Harmer
7.287
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
1.015
3145893MURPHYS
Solar/Wind Harmer
0.273
3146516WINFALL
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146626S HERTFORD
Solar/Wind Harmer
0.151
3146626S HERTFORD
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146376EDENTON
Solar/Wind Harmer
0.67
3146376EDENTON
Solar/Wind Harmer
0.67
964791AG1-342 GEN
Solar/Wind Harmer
2.892
3146843MT LREL
Solar/Wind Harmer
0.15
3146843MT LREL
Solar/Wind Harmer
0.15
970657AG2-426 GEN
Solar/Wind Harmer
5.253
970657AG2-426 GEN
Solar/Wind Harmer
1.101
316065AD1-022 GEN
Solar/Wind Harmer
6.875
316274AC1-208 GEN
Solar/Wind Harmer
0.769
3145933PARMELE
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.144
3145493TOT1
Solar/Wind Harmer
0.328
3145453TOT5
Solar/Wind Harmer
0.197
3145603CNETO
Solar/Wind Harmer
0.131
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316263AC1-034 GEN
Solar/Wind Harmer
5.37
961601AG1-000A GEN
Solar/Wind Harmer
2.512
971489AH1-241 GEN
Solar/Wind Harmer
7.325
316240AF1-291 C
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.537
316033AB2-134 GEN
Solar/Wind Harmer
0.008
315697AD1-025 GEN
Solar/Wind Harmer
0.144
944641AF1-129 GEN
Adder
60.502
3152261N ANNA2
50/50
36.457
3151771S ANNAG1
50/50
1.04
3151801S ANNAS2
50/50
0.534
3151761LOISA E
50/50
39.513
972183AH1-676 GEN
50/50
307.587
3151031BRUNSWICKG2
50/50
2.697
3147666LOUISA
Solar/Wind Harmer
1.117
316313AB2-026
Solar/Wind Harmer
0.125
316258AE1-075 C
Solar/Wind Harmer
0.15
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.006
970917AG2-570 GEN
Solar/Wind Harmer
17.445
316478AD1-087 GEN
Solar/Wind Harmer
0.619
316486AD2-202 GEN
Solar/Wind Harmer
0.182
970909AG2-566 GEN
Solar/Wind Harmer
1.827
3146926FARMVIL
Solar/Wind Harmer
0.098
316365GEN2_N
Solar/Wind Harmer
0.365
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.506
971193AH1-056 GEN
Solar/Wind Harmer
9.82
963181AG1-167 GEN
Solar/Wind Harmer
0.644
3144293JTRSVLE
Adder
0.512
3147043LAWRENC
Solar/Wind Harmer
0.096
959311AF2-222 GEN
Solar/Wind Harmer
14.213
970257AG2-171 GEN
Solar/Wind Harmer
5.111
315785AD2-033 C
Solar/Wind Harmer
1.297
964241AG1-285 GEN
Solar/Wind Harmer
10.591
316131AB2-060 GEN
Solar/Wind Harmer
0.498
313506AB2-031 GEN
Solar/Wind Harmer
0.487
3146776BUCKING
Solar/Wind Harmer
0.057
944581AF1-123 GEN
Solar/Wind Harmer
34.771
944601AF1-125 GEN
Solar/Wind Harmer
34.236
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3132273ORANGE
Solar/Wind Harmer
0.031
315773AC2-141 GEN
Solar/Wind Harmer
5.584
3146456SLIGO L269
Solar/Wind Harmer
0.153
971153AH1-033 GEN
Solar/Wind Harmer
1.766
3145796HORNRTN
Solar/Wind Harmer
0.61
3145796HORNRTN
Solar/Wind Harmer
0.152
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
316320Y1-086
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
14.124
3145273HOLLAND
Solar/Wind Harmer
0.114
3144873MCLAUGH
Solar/Wind Harmer
0.004
316435W1029_GEN3
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.254
3145893MURPHYS
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146626S HERTFORD
Solar/Wind Harmer
0.151
957521AF2-046 GEN
Solar/Wind Harmer
11.271
961681AG1-008 GEN
Solar/Wind Harmer
11.271
3146263WOODLND
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146376EDENTON
Solar/Wind Harmer
0.151
316463AE2-346 GEN
Solar/Wind Harmer
0.129
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
1.604
970661AG2-428 GEN
Solar/Wind Harmer
3.178
315614AA2-178 GEN
Solar/Wind Harmer
0.858
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970659AG2-427 GEN
Solar/Wind Harmer
1.584
3156021HOLLOMANSOL
Solar/Wind Harmer
0.678
971157AH1-035 GEN
Solar/Wind Harmer
1.793
3146206CASHIE
Solar/Wind Harmer
0.149
315737AD1-076 GEN
Solar/Wind Harmer
1.921
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.149
315813AE1-149 C
Solar/Wind Harmer
7.948
3144536CHRHLND
Solar/Wind Harmer
0.022
316210AC1-098 GEN
Solar/Wind Harmer
1.371
315724AD1-057 GEN
Solar/Wind Harmer
0.549
3145963POPLR C
Solar/Wind Harmer
0.146
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.188
316327AA2-057 GEN
Solar/Wind Harmer
0.219
3145933PARMELE
Solar/Wind Harmer
0.144
966801AG1-551 GEN
Solar/Wind Harmer
1.673
3146233WITAKRS
Solar/Wind Harmer
0.718
3146233WITAKRS
Solar/Wind Harmer
0.097
3138543CONSLDL
Solar/Wind Harmer
0.094
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
315839AE2-212 C
Solar/Wind Harmer
0.001
3146073TAR RVR
Solar/Wind Harmer
0.142
3146083TARBORO
Solar/Wind Harmer
0.142
3145336SMITFLD
Solar/Wind Harmer
0.057
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.141
971623AH1-311 GEN
Solar/Wind Harmer
0.283
961601AG1-000A GEN
Solar/Wind Harmer
10.046
3150861SPRUNCD
Adder
0.645
970221AG2-151 GEN
Solar/Wind Harmer
7.325
965281AG1-393 GEN
Solar/Wind Harmer
1.459
3151221GRAVEL6
Adder
9.808
3151171GRAVELC
Adder
1.887
961611AG1-000B GEN
Solar/Wind Harmer
3.53
971683AH1-343 GEN
Solar/Wind Harmer
4.854
316283AC2-100 C
Solar/Wind Harmer
0.252
315778AD1-151 GEN
Solar/Wind Harmer
10.15
970129AG2-093 GEN
Solar/Wind Harmer
7.509
3144216WINCHST
Adder
0.455
970133AG2-095 GEN
Solar/Wind Harmer
1.157
3150921YORKTN3
Adder
2.978
970129AG2-093 GEN
Solar/Wind Harmer
3.534
3138126ROCKLANDING
Solar/Wind Harmer
0.055
3142543TWELFTH
Solar/Wind Harmer
0.011
316303AF2-085
50/50
4.114
315244AE2-183_ST
50/50
5.93
963041AG1-153 GEN
50/50
5.461
3147346CASHSCORNER
Solar/Wind Harmer
0.597
941031AE2-094 GEN
Solar/Wind Harmer
39.425
944011AF1-069 GEN
Solar/Wind Harmer
12.882
970673AG2-436 GEN
Solar/Wind Harmer
44.756
970673AG2-436 GEN
Solar/Wind Harmer
29.837
971967AH1-528 GEN
Solar/Wind Harmer
33.079
970085AG2-068 GEN
Solar/Wind Harmer
10.416
970581AG2-369 GEN
Solar/Wind Harmer
8.958
316233AE1-074 FULL
Solar/Wind Harmer
0.15
971281AH1-106 GEN
Solar/Wind Harmer
2.6
971283AH1-107 GEN
Solar/Wind Harmer
2.6
316315AB2-025 C
Solar/Wind Harmer
0.143
315814AE2-033 C
Solar/Wind Harmer
13.959
315657AE1-056 GEN
Solar/Wind Harmer
5.562
946301AF1-294 GEN
Solar/Wind Harmer
3.175
961791AG1-021 GEN
Solar/Wind Harmer
1.544
3143316POE
Solar/Wind Harmer
0.635
970683AG2-441 GEN
Solar/Wind Harmer
10.688
970681AG2-440 GEN
Solar/Wind Harmer
8.55
3144303KENBRDG
Solar/Wind Harmer
0.128
971443AH1-215 GEN
Solar/Wind Harmer
2.682
970285AG2-188 GEN
Solar/Wind Harmer
12.58
316087AB2-174 GEN
Solar/Wind Harmer
0.005
971845AH1-439 GEN
Solar/Wind Harmer
7.164
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
970831AG2-522 GEN
Solar/Wind Harmer
6.67
3137643SOCKMAN
Solar/Wind Harmer
0.622
315652AC1-086 GEN
Solar/Wind Harmer
16.994
315607AA1-063A GEN
Solar/Wind Harmer
0.314
3146043SEABORD
Solar/Wind Harmer
0.153
957871AF2-081 GEN
Solar/Wind Harmer
7.61
319010AE1-072 C
Solar/Wind Harmer
0.769
3146406KITTY HAWK
Solar/Wind Harmer
0.019
3145796HORNRTN
Solar/Wind Harmer
0.488
3145796HORNRTN
Solar/Wind Harmer
0.061
965291AG1-394 GEN
Solar/Wind Harmer
0.678
313526AB2-022
Solar/Wind Harmer
0.082
316305AF2-043 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
13.946
3151091ELIZAR2
Adder
13.704
316321Z2-027
Solar/Wind Harmer
0.028
3146396TANGLEW
Solar/Wind Harmer
0.419
3145176PASQUOTANK
Solar/Wind Harmer
0.094
315835AF2-110_GEN
Solar/Wind Harmer
1.043
3146486SUNBURY
Solar/Wind Harmer
0.152
3146486SUNBURY
Solar/Wind Harmer
0.152
3152611GOSPORTB
Adder
1.933
3152621GOSPORTC
Adder
1.641
3152601GOSPORTA
Adder
1.513
3145893MURPHYS
Solar/Wind Harmer
0.41
3145893MURPHYS
Solar/Wind Harmer
0.152
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316311AC2-079 GEN
Solar/Wind Harmer
4.34
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.104
3130156CHOWAN
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
0.151
3145513AHOSKIE
Solar/Wind Harmer
0.314
3145513AHOSKIE
Solar/Wind Harmer
0.15
972205AH1-687 GEN
Adder
6.411
3145683EARLEYS
Solar/Wind Harmer
0.3
3145683EARLEYS
Solar/Wind Harmer
0.15
3145683EARLEYS
Solar/Wind Harmer
0.15
315816AE2-034 GEN
Solar/Wind Harmer
0.644
3130546PLYMOUTH
Solar/Wind Harmer
0.149
3146206CASHIE
Solar/Wind Harmer
0.149
970601AG2-382 GEN
Solar/Wind Harmer
5.575
315732AD1-074 GEN1
Solar/Wind Harmer
0.858
315733AD1-074 GEN2
Solar/Wind Harmer
0.858
315735AD1-075 GEN1
Solar/Wind Harmer
0.429
3146033SCOT NK
Solar/Wind Harmer
0.593
316118AC1-105 GEN
Solar/Wind Harmer
0.382
3147173SINAI
Solar/Wind Harmer
0.145
3147243WELCO
Solar/Wind Harmer
0.091
316319Z2-044 C
Solar/Wind Harmer
0
316005AA1-067
Solar/Wind Harmer
0.153
3145746EVERETS
Solar/Wind Harmer
0.567
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
970181AG2-120 GEN
Solar/Wind Harmer
1.773
957861AF2-080 GEN
Solar/Wind Harmer
6.125
316420AA1-050 GEN
Solar/Wind Harmer
0.005
3145573BETHELC
Solar/Wind Harmer
0.142
3145573BETHELC
Solar/Wind Harmer
0.142
971445AH1-216 GEN
Solar/Wind Harmer
9.913
971285AH1-108 GEN
Adder
1.055
972265AH1-717 GEN
Adder
10.474
3151201GRAVEL4
Adder
9.819
3151191GRAVEL3
Adder
9.695
3151211GRAVEL5
Adder
9.695
971447AH1-217 GEN
Solar/Wind Harmer
3.983
316369SG1_INVT
Solar/Wind Harmer
0.005
970865AG2-541 GEN
Solar/Wind Harmer
4.353
316132AB2-190 GEN1
Solar/Wind Harmer
0.669
270494AE1-108_GEN
Solar/Wind Harmer
1.404
316123AC1-075 GEN
Solar/Wind Harmer
0.154
970165AG2-112 GEN
Solar/Wind Harmer
0.913
970163AG2-111 GEN
Solar/Wind Harmer
0.871
LAGNLTFEXP_LAGN->PJM
CLTF
6.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.668
TVALTFEXP_TVA->PJM
CLTF
3.105
CPLELTFEXP_CPLE->PJM
CLTF
9.633
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.022
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.582
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.459
MECLTFEXP_MEC->PJM
CLTF
2.598
SIGELTFEXP_SIGE->PJM
CLTF
0.077
NYPJM->LTFIMP_NY
CLTF
2.601
LGEELTFEXP_LGEE->PJM
CLTF
0.913
WECLTFEXP_WEC->PJM
CLTF
0.444

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.78 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5310.49
MW Contribution:30.72
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
36.417
3151791S ANNAG2
50/50
1.042
3151781S ANNAS1
50/50
0.535
3151741LOISA C
50/50
1.062
3151751LOISA D
50/50
19.419
970119AG2-088 GEN
50/50
30.719
315243AE2-183_GT3
50/50
3.412
3151051BRUNSWICKS1
50/50
5.568
3151021BRUNSWICKG1
50/50
2.683
971451AH1-221 GEN
50/50
8.148
316045AC1-158 PL2
Solar/Wind Harmer
27.544
3147666LOUISA
Solar/Wind Harmer
-0.217
316192AB2-158 GEN
Solar/Wind Harmer
6.343
3143226MDLTHAN
Solar/Wind Harmer
-0.026
971133AH1-012 GEN
50/50
10.157
3151731LOISA B
50/50
19.419
3151721LOISA A
50/50
19.318
970533AG2-339 GEN
50/50
18.931
970531AG2-338 GEN
50/50
7.573
315242AE2-183_GT2
50/50
3.412
315241AE2-183_GT1
50/50
3.391
972185AH1-677 GEN
50/50
12.3
3151041BRUNSWICKG3
50/50
2.683
972187AH1-678 GEN
50/50
6.156
316447AC1-158 HLD
Solar/Wind Harmer
18.935
966001AG1-469 GEN
Solar/Wind Harmer
0.523
971223AH1-071 GEN
Solar/Wind Harmer
3.236
970933AG2-581 GEN
Solar/Wind Harmer
21.052
3143526WINTERP
Solar/Wind Harmer
-0.108
970099AG2-077 GEN
Solar/Wind Harmer
25.941
3144356SAPONY
Solar/Wind Harmer
0.69
971741AH1-377 GEN
Solar/Wind Harmer
22.545
970301AG2-198 GEN
Solar/Wind Harmer
9.564
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.806
963191AG1-168 GEN
Solar/Wind Harmer
1.683
3144293JTRSVLE
Adder
0.509
3144293JTRSVLE
Adder
0.428
316034AC1-036 C
Solar/Wind Harmer
0.331
970323AG2-213 GEN
Solar/Wind Harmer
8.912
971775AH1-396 GEN
Solar/Wind Harmer
1.269
313527AB2-043 GEN
Solar/Wind Harmer
2.871
939181AE1-148 GEN
Solar/Wind Harmer
9.906
316181AB2-040 GEN
Solar/Wind Harmer
2.454
3146776BUCKING
Solar/Wind Harmer
-0.07
3146776BUCKING
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.936
3145593CAROLNA
Solar/Wind Harmer
0.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.73
3145783HORNRTN
Solar/Wind Harmer
2.029
3145783HORNRTN
Solar/Wind Harmer
1.623
3145783HORNRTN
Solar/Wind Harmer
0.507
3145783HORNRTN
Solar/Wind Harmer
0.203
316185AD1-033 GEN
Solar/Wind Harmer
1.801
3145506HICKORY
Solar/Wind Harmer
-0.068
3145506HICKORY
Solar/Wind Harmer
-0.041
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.15
316018AA1-139 ULT2
Solar/Wind Harmer
1.461
316017AA1-139 ULT1
Solar/Wind Harmer
1.38
3137176SLIGO L2192
Solar/Wind Harmer
-0.067
3146456SLIGO L269
Solar/Wind Harmer
2.013
3130086AYDLETT
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.051
3142956BIRDNECK
Solar/Wind Harmer
0.913
316316AC1-027 C
Solar/Wind Harmer
0.522
3146386ELIZ CT
Solar/Wind Harmer
-0.017
315742AE1-103 GEN
Solar/Wind Harmer
1.775
316036AC1-147 C
Solar/Wind Harmer
0.457
3150991CHESPKB
Adder
1.578
3150991CHESPKB
Adder
1.541
316431W1029_GEN1
Solar/Wind Harmer
3.067
316433W1029_GEN2
Solar/Wind Harmer
3.067
962561AG1-105 GEN
Solar/Wind Harmer
9.523
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.472
3145893MURPHYS
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
0.499
3146376EDENTON
Solar/Wind Harmer
0.499
964791AG1-342 GEN
Solar/Wind Harmer
3.588
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970657AG2-426 GEN
Solar/Wind Harmer
5.229
970657AG2-426 GEN
Solar/Wind Harmer
1.093
316065AD1-022 GEN
Solar/Wind Harmer
8.326
944641AF1-129 GEN
Adder
59.993
3152261N ANNA2
50/50
36.414
3151771S ANNAG1
50/50
1.042
3151801S ANNAS2
50/50
0.535
3151761LOISA E
50/50
39.589
972183AH1-676 GEN
50/50
308.231
3151031BRUNSWICKG2
50/50
2.683
316044AC1-158 PL1
Solar/Wind Harmer
8.611
316450AC1-158 RIC
Solar/Wind Harmer
2.296
3147666LOUISA
Solar/Wind Harmer
-0.125
316313AB2-026
Solar/Wind Harmer
0.6
316258AE1-075 C
Solar/Wind Harmer
0.54
316405AF2-144 C
Solar/Wind Harmer
0.57
3143336POWHATN
Solar/Wind Harmer
2.243
970917AG2-570 GEN
Solar/Wind Harmer
54.816
316478AD1-087 GEN
Solar/Wind Harmer
1.715
316486AD2-202 GEN
Solar/Wind Harmer
0.502
970909AG2-566 GEN
Solar/Wind Harmer
1.816
3146926FARMVIL
Solar/Wind Harmer
-0.011
316365GEN2_N
Solar/Wind Harmer
1.225
942461AE2-259 GEN
Solar/Wind Harmer
2.724
3132273ORANGE
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.056
971193AH1-056 GEN
Solar/Wind Harmer
11.252
963181AG1-167 GEN
Solar/Wind Harmer
1.683
3144293JTRSVLE
Adder
0.509
966621AG1-532 GEN
Solar/Wind Harmer
0.364
3147043LAWRENC
Solar/Wind Harmer
-0.011
959311AF2-222 GEN
Solar/Wind Harmer
18.625
970257AG2-171 GEN
Solar/Wind Harmer
6.684
315785AD2-033 C
Solar/Wind Harmer
4.033
964241AG1-285 GEN
Solar/Wind Harmer
13.848
316131AB2-060 GEN
Solar/Wind Harmer
1.908
313506AB2-031 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Harmer
-0.006
944581AF1-123 GEN
Solar/Wind Harmer
78.382
944601AF1-125 GEN
Solar/Wind Harmer
77.158
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
315773AC2-141 GEN
Solar/Wind Harmer
7.138
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.077
3145796HORNRTN
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.017
3156081AA2-088 GEN
Solar/Wind Harmer
5.522
316320Y1-086
Solar/Wind Harmer
0.996
3151101ELIZAR3
Adder
14.024
3145273HOLLAND
Solar/Wind Harmer
-0.013
3144873MCLAUGH
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
3.067
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.305
961681AG1-008 GEN
Solar/Wind Harmer
13.305
3146263WOODLND
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.017
316463AE2-346 GEN
Solar/Wind Harmer
0.272
316140AB2-099
Solar/Wind Harmer
0.113
962331AG1-082 GEN
Solar/Wind Harmer
2.097
940641AE2-051 GEN
Solar/Wind Harmer
21.983
3143336POWHATN
Solar/Wind Harmer
2.639
970919AG2-571 GEN
Solar/Wind Harmer
6.939
939411AE1-173 GEN
Solar/Wind Harmer
109.306
970087AG2-069 GEN
Solar/Wind Harmer
20.456
316336AC2-165 C
Solar/Wind Harmer
3.699
3143526WINTERP
Solar/Wind Harmer
-0.108
957481AF2-042 GEN
Solar/Wind Harmer
64.853
315693AD1-088 GEN
Solar/Wind Harmer
10.143
962491AG1-098 GEN
Solar/Wind Harmer
13.526
970937AG2-583 GEN
Solar/Wind Harmer
13.537
315687AD1-152 GEN
Solar/Wind Harmer
2.221
3146926FARMVIL
Solar/Wind Harmer
-0.011
316023GEN1_S
Solar/Wind Harmer
1.225
963171AG1-166 GEN
Solar/Wind Harmer
2.245
971563AH1-280 GEN
Solar/Wind Harmer
2.245
3144293JTRSVLE
Adder
0.509
960081AF2-299 GEN
Solar/Wind Harmer
2.018
970685AG2-442 GEN
Solar/Wind Harmer
15.656
971795AH1-408 GEN
Solar/Wind Harmer
13.409
3147043LAWRENC
Adder
1.438
316237AB2-079_GEN
Solar/Wind Harmer
0.531
316322AB2-045
Solar/Wind Harmer
0.592
3146776BUCKING
Solar/Wind Harmer
-0.007
971065AG2-659 GEN
Solar/Wind Harmer
8.742
316129AC1-054 GEN
Solar/Wind Harmer
1.531
316011AB1-132 GEN
Solar/Wind Harmer
3.607
962571AG1-106 GEN
Solar/Wind Harmer
2.478
944591AF1-124 GEN
Solar/Wind Harmer
78.664
315683AE1-153 C
Solar/Wind Harmer
15.955
316190AA2-174 GEN
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
-0.017
316388AE2-253 GEN
Solar/Wind Harmer
1.15
316294AC1-161 GEN
Solar/Wind Harmer
5.519
3146456SLIGO L269
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.017
316246AF1-032 C
Solar/Wind Harmer
0.344
316093AE2-104_GEN
Solar/Wind Harmer
4.929
316375AC2-012 GEN
Solar/Wind Harmer
5.859
3150981CHESPKA
Adder
1.882
3146516WINFALL
Solar/Wind Harmer
-0.054
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
0.502
972003AH1-546 GEN
Solar/Wind Harmer
8.434
315800Z1-036_GEN1
Solar/Wind Harmer
4.166
3146263WOODLND
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
970401AG2-262 GEN
Solar/Wind Harmer
1.096
970661AG2-428 GEN
Solar/Wind Harmer
17.805
3145663CRESWEL
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.017
971163AH1-040 GEN
Solar/Wind Harmer
15.681
316381AD1-082 GEN
Solar/Wind Harmer
1.533
970659AG2-427 GEN
Solar/Wind Harmer
8.872
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.163
3150851SPRUNCC
Adder
0.64
3151171GRAVELC
Adder
1.424
970661AG2-428 GEN
Solar/Wind Harmer
3.155
315614AA2-178 GEN
Solar/Wind Harmer
1.805
316083AB2-161 GEN
Solar/Wind Harmer
2.713
970659AG2-427 GEN
Solar/Wind Harmer
1.572
3156021HOLLOMANSOL
Solar/Wind Harmer
2.245
971157AH1-035 GEN
Solar/Wind Harmer
2.083
3146206CASHIE
Solar/Wind Harmer
-0.017
3150861SPRUNCD
Adder
0.64
3151221GRAVEL6
Adder
9.73
3151171GRAVELC
Adder
1.872
3144216WINCHST
Adder
0.451
3150921YORKTN3
Adder
2.951
315737AD1-076 GEN
Solar/Wind Harmer
0.403
316303AF2-085
50/50
4.096
315244AE2-183_ST
50/50
5.899
963041AG1-153 GEN
50/50
5.432
3147346CASHSCORNER
Solar/Wind Harmer
0.449
941031AE2-094 GEN
Solar/Wind Harmer
44.868
944011AF1-069 GEN
Solar/Wind Harmer
14.059
970673AG2-436 GEN
Solar/Wind Harmer
49.264
970673AG2-436 GEN
Solar/Wind Harmer
24.944
971967AH1-528 GEN
Solar/Wind Harmer
43.441
970085AG2-068 GEN
Solar/Wind Harmer
13.637
970581AG2-369 GEN
Solar/Wind Harmer
11.728
316233AE1-074 FULL
Solar/Wind Harmer
0.564
971281AH1-106 GEN
Solar/Wind Harmer
3.405
971283AH1-107 GEN
Solar/Wind Harmer
3.405
316315AB2-025 C
Solar/Wind Harmer
0.534
315814AE2-033 C
Solar/Wind Harmer
18.349
315657AE1-056 GEN
Solar/Wind Harmer
6.751
946301AF1-294 GEN
Solar/Wind Harmer
4.601
961791AG1-021 GEN
Solar/Wind Harmer
2.245
946281AF1-292 GEN
Solar/Wind Harmer
0.402
3143316POE
Solar/Wind Harmer
-0.07
970683AG2-441 GEN
Solar/Wind Harmer
13.979
970681AG2-440 GEN
Solar/Wind Harmer
11.183
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.508
970285AG2-188 GEN
Solar/Wind Harmer
15.538
316087AB2-174 GEN
Solar/Wind Harmer
2.524
971845AH1-439 GEN
Solar/Wind Harmer
9.375
316239AB2-077_GEN
Solar/Wind Harmer
0.531
316238AB2-078_GEN
Solar/Wind Harmer
0.531
970831AG2-522 GEN
Solar/Wind Harmer
8.718
3137643SOCKMAN
Solar/Wind Harmer
-0.069
315652AC1-086 GEN
Solar/Wind Harmer
19.393
315607AA1-063A GEN
Solar/Wind Harmer
1.731
3146043SEABORD
Solar/Wind Harmer
-0.017
957871AF2-081 GEN
Solar/Wind Harmer
8.527
319010AE1-072 C
Solar/Wind Harmer
3.447
3146406KITTY HAWK
Solar/Wind Harmer
0.014
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.007
965291AG1-394 GEN
Solar/Wind Harmer
1.51
313526AB2-022
Solar/Wind Harmer
0.458
316305AF2-043 C
Solar/Wind Harmer
0.512
3151081ELIZAR1
Adder
13.847
3151091ELIZAR2
Adder
13.607
316321Z2-027
Solar/Wind Harmer
0.458
3145176PASQUOTANK
Solar/Wind Harmer
-0.01
3146396TANGLEW
Solar/Wind Harmer
0.312
315835AF2-110_GEN
Solar/Wind Harmer
2.119
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
3152611GOSPORTB
Adder
1.919
3152621GOSPORTC
Adder
1.629
3152601GOSPORTA
Adder
1.503
316318V4-068
Solar/Wind Harmer
0.422
3145893MURPHYS
Solar/Wind Harmer
-0.045
3145893MURPHYS
Solar/Wind Harmer
-0.017
316311AC2-079 GEN
Solar/Wind Harmer
8.505
315611Z1-036_GEN2
Solar/Wind Harmer
4.166
315833AF1-017_GEN
Solar/Wind Harmer
3.202
316349AD2-085 GEN
Solar/Wind Harmer
1.5
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.146
961941AG1-037 GEN
Solar/Wind Harmer
0.126
3145513AHOSKIE
Solar/Wind Harmer
-0.017
972205AH1-687 GEN
Adder
6.372
315816AE2-034 GEN
Solar/Wind Harmer
1.353
3145683EARLEYS
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3130546PLYMOUTH
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.286
971285AH1-108 GEN
Adder
1.047
972265AH1-717 GEN
Adder
10.391
3151201GRAVEL4
Adder
9.741
3151191GRAVEL3
Adder
9.617
3151211GRAVEL5
Adder
9.617
315732AD1-074 GEN1
Solar/Wind Harmer
0.429
315733AD1-074 GEN2
Solar/Wind Harmer
0.429
315735AD1-075 GEN1
Solar/Wind Harmer
0.214
LAGNLTFEXP_LAGN->PJM
CLTF
5.952
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.368
TVALTFEXP_TVA->PJM
CLTF
2.995
CPLELTFEXP_CPLE->PJM
CLTF
9.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.532
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.913
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.044
MECLTFEXP_MEC->PJM
CLTF
2.409
SIGELTFEXP_SIGE->PJM
CLTF
0.072
NYPJM->LTFIMP_NY
CLTF
2.685
LGEELTFEXP_LGEE->PJM
CLTF
0.835
WECLTFEXP_WEC->PJM
CLTF
0.4

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.91 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5157.73
MW Contribution:29.48
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
10.1
3151731LOISA B
50/50
20.962
3151721LOISA A
50/50
20.854
970533AG2-339 GEN
50/50
18.154
970531AG2-338 GEN
50/50
7.261
315242AE2-183_GT2
50/50
3.272
315241AE2-183_GT1
50/50
3.252
972185AH1-677 GEN
50/50
11.796
3151041BRUNSWICKG3
50/50
2.573
972187AH1-678 GEN
50/50
5.905
316447AC1-158 HLD
Solar/Wind Harmer
17.909
966001AG1-469 GEN
Solar/Wind Harmer
0.617
971223AH1-071 GEN
Solar/Wind Harmer
3.105
970933AG2-581 GEN
Solar/Wind Harmer
20.21
315651AD1-115 GEN
Solar/Wind Harmer
9.377
3143526WINTERP
Solar/Wind Harmer
-0.103
970099AG2-077 GEN
Solar/Wind Harmer
24.94
3144356SAPONY
Solar/Wind Harmer
0.658
971741AH1-377 GEN
Solar/Wind Harmer
21.833
970301AG2-198 GEN
Solar/Wind Harmer
9.278
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.72
963191AG1-168 GEN
Solar/Wind Harmer
1.632
3144293JTRSVLE
Adder
0.493
3144293JTRSVLE
Adder
0.415
3146776BUCKING
Solar/Wind Harmer
-0.069
3146776BUCKING
Solar/Wind Harmer
-0.006
316034AC1-036 C
Solar/Wind Harmer
0.32
970323AG2-213 GEN
Solar/Wind Harmer
8.614
971775AH1-396 GEN
Solar/Wind Harmer
1.227
313527AB2-043 GEN
Solar/Wind Harmer
2.765
939181AE1-148 GEN
Solar/Wind Harmer
9.523
316181AB2-040 GEN
Solar/Wind Harmer
2.344
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.849
3145593CAROLNA
Solar/Wind Harmer
0.137
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.651
3145783HORNRTN
Solar/Wind Harmer
1.938
3145783HORNRTN
Solar/Wind Harmer
1.55
3145783HORNRTN
Solar/Wind Harmer
0.484
3145783HORNRTN
Solar/Wind Harmer
0.194
962561AG1-105 GEN
Solar/Wind Harmer
9.166
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.01
316185AD1-033 GEN
Solar/Wind Harmer
1.705
964791AG1-342 GEN
Solar/Wind Harmer
3.453
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.089
316018AA1-139 ULT2
Solar/Wind Harmer
1.383
316017AA1-139 ULT1
Solar/Wind Harmer
1.307
3137176SLIGO L2192
Solar/Wind Harmer
-0.064
3146456SLIGO L269
Solar/Wind Harmer
1.906
3130086AYDLETT
Solar/Wind Harmer
-0.064
315742AE1-103 GEN
Solar/Wind Harmer
1.685
3145893MURPHYS
Solar/Wind Harmer
0.449
3145893MURPHYS
Solar/Wind Harmer
-0.029
3142956BIRDNECK
Solar/Wind Harmer
0.864
3146386ELIZ CT
Solar/Wind Harmer
-0.016
316316AC1-027 C
Solar/Wind Harmer
0.494
316431W1029_GEN1
Solar/Wind Harmer
2.907
316433W1029_GEN2
Solar/Wind Harmer
2.907
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316036AC1-147 C
Solar/Wind Harmer
0.432
3150991CHESPKB
Adder
1.493
3150991CHESPKB
Adder
1.457
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146376EDENTON
Solar/Wind Harmer
0.473
3146376EDENTON
Solar/Wind Harmer
0.473
316065AD1-022 GEN
Solar/Wind Harmer
7.917
970657AG2-426 GEN
Solar/Wind Harmer
4.945
970657AG2-426 GEN
Solar/Wind Harmer
1.034
944641AF1-129 GEN
Adder
56.207
3152261N ANNA2
50/50
35.401
3151771S ANNAG1
50/50
1.115
3151801S ANNAS2
50/50
0.573
3151761LOISA E
50/50
42.735
972183AH1-676 GEN
50/50
334.654
3151031BRUNSWICKG2
50/50
2.573
316044AC1-158 PL1
Solar/Wind Harmer
8.144
316450AC1-158 RIC
Solar/Wind Harmer
2.171
3147666LOUISA
Solar/Wind Harmer
-0.126
3132273ORANGE
Solar/Wind Harmer
-0.006
316170AC1-121 GEN2
Solar/Wind Harmer
0.691
316313AB2-026
Solar/Wind Harmer
0.581
316258AE1-075 C
Solar/Wind Harmer
0.523
316405AF2-144 C
Solar/Wind Harmer
0.552
3143336POWHATN
Solar/Wind Harmer
2.174
970917AG2-570 GEN
Solar/Wind Harmer
52.576
316478AD1-087 GEN
Solar/Wind Harmer
1.649
316486AD2-202 GEN
Solar/Wind Harmer
0.483
970909AG2-566 GEN
Solar/Wind Harmer
1.762
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.651
3147133PAMPLIN
Solar/Wind Harmer
-0.055
971193AH1-056 GEN
Solar/Wind Harmer
10.918
963181AG1-167 GEN
Solar/Wind Harmer
1.632
3144293JTRSVLE
Adder
0.493
316365GEN2_N
Solar/Wind Harmer
1.169
3146776BUCKING
Solar/Wind Harmer
-0.006
959311AF2-222 GEN
Solar/Wind Harmer
18.009
970257AG2-171 GEN
Solar/Wind Harmer
6.46
315785AD2-033 C
Solar/Wind Harmer
3.896
966621AG1-532 GEN
Solar/Wind Harmer
0.348
3147043LAWRENC
Solar/Wind Harmer
-0.01
964241AG1-285 GEN
Solar/Wind Harmer
13.355
316131AB2-060 GEN
Solar/Wind Harmer
1.838
313506AB2-031 GEN
Solar/Wind Harmer
1.351
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
944581AF1-123 GEN
Solar/Wind Harmer
74.206
944601AF1-125 GEN
Solar/Wind Harmer
73.048
3145796HORNRTN
Solar/Wind Harmer
-0.065
3145796HORNRTN
Solar/Wind Harmer
-0.016
3156081AA2-088 GEN
Solar/Wind Harmer
5.256
3146456SLIGO L269
Solar/Wind Harmer
-0.016
971153AH1-033 GEN
Solar/Wind Harmer
1.967
315773AC2-141 GEN
Solar/Wind Harmer
6.751
3145893MURPHYS
Solar/Wind Harmer
0.112
3145893MURPHYS
Solar/Wind Harmer
-0.016
3145273HOLLAND
Solar/Wind Harmer
-0.012
316320Y1-086
Solar/Wind Harmer
0.943
957521AF2-046 GEN
Solar/Wind Harmer
12.668
961681AG1-008 GEN
Solar/Wind Harmer
12.668
3146263WOODLND
Solar/Wind Harmer
-0.016
3151101ELIZAR3
Adder
13.269
316435W1029_GEN3
Solar/Wind Harmer
2.907
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316463AE2-346 GEN
Solar/Wind Harmer
0.259
316140AB2-099
Solar/Wind Harmer
0.108
962331AG1-082 GEN
Solar/Wind Harmer
1.997
3146376EDENTON
Solar/Wind Harmer
-0.016
315614AA2-178 GEN
Solar/Wind Harmer
1.714
316317KELFORD C
Solar/Wind Harmer
0.748
3145823KELFORD
Solar/Wind Harmer
-0.016
3156021HOLLOMANSOL
Solar/Wind Harmer
2.136
970661AG2-428 GEN
Solar/Wind Harmer
2.985
3146206CASHIE
Solar/Wind Harmer
-0.016
971157AH1-035 GEN
Solar/Wind Harmer
1.979
3150861SPRUNCD
Adder
0.602
3151221GRAVEL6
Adder
9.152
3151171GRAVELC
Adder
1.761
315737AD1-076 GEN
Solar/Wind Harmer
0.963
3152251N ANNA1
50/50
35.404
3151791S ANNAG2
50/50
1.115
3151781S ANNAS1
50/50
0.573
3151741LOISA C
50/50
1.146
3151751LOISA D
50/50
20.962
970119AG2-088 GEN
50/50
29.475
315243AE2-183_GT3
50/50
3.272
3151051BRUNSWICKS1
50/50
5.34
3151021BRUNSWICKG1
50/50
2.573
971451AH1-221 GEN
50/50
7.815
316045AC1-158 PL2
Solar/Wind Harmer
26.051
3147666LOUISA
Solar/Wind Harmer
-0.219
316192AB2-158 GEN
Solar/Wind Harmer
6.415
316254AC1-120 GEN1
Solar/Wind Harmer
2.072
3143226MDLTHAN
Solar/Wind Harmer
-0.025
940641AE2-051 GEN
Solar/Wind Harmer
21.037
3143336POWHATN
Solar/Wind Harmer
2.558
970919AG2-571 GEN
Solar/Wind Harmer
6.655
970087AG2-069 GEN
Solar/Wind Harmer
19.62
939411AE1-173 GEN
Solar/Wind Harmer
104.381
316336AC2-165 C
Solar/Wind Harmer
3.596
315683AE1-153 C
Solar/Wind Harmer
18.631
3143526WINTERP
Solar/Wind Harmer
-0.103
957481AF2-042 GEN
Solar/Wind Harmer
62.351
315693AD1-088 GEN
Solar/Wind Harmer
9.768
962491AG1-098 GEN
Solar/Wind Harmer
13.03
970937AG2-583 GEN
Solar/Wind Harmer
13.286
3146926FARMVIL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
2.135
963171AG1-166 GEN
Solar/Wind Harmer
2.176
971563AH1-280 GEN
Solar/Wind Harmer
2.176
3144293JTRSVLE
Adder
0.493
316023GEN1_S
Solar/Wind Harmer
1.169
970685AG2-442 GEN
Solar/Wind Harmer
15.155
316322AB2-045
Solar/Wind Harmer
0.581
3146776BUCKING
Solar/Wind Harmer
-0.007
960081AF2-299 GEN
Solar/Wind Harmer
1.928
971795AH1-408 GEN
Solar/Wind Harmer
12.835
3147043LAWRENC
Adder
1.377
316237AB2-079_GEN
Solar/Wind Harmer
0.511
971065AG2-659 GEN
Solar/Wind Harmer
8.385
316129AC1-054 GEN
Solar/Wind Harmer
1.468
972003AH1-546 GEN
Solar/Wind Harmer
8.347
316011AB1-132 GEN
Solar/Wind Harmer
3.442
962571AG1-106 GEN
Solar/Wind Harmer
2.365
316190AA2-174 GEN
Solar/Wind Harmer
0.201
3145783HORNRTN
Solar/Wind Harmer
-0.016
944591AF1-124 GEN
Solar/Wind Harmer
74.473
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.016
970401AG2-262 GEN
Solar/Wind Harmer
1.055
316388AE2-253 GEN
Solar/Wind Harmer
1.089
3146456SLIGO L269
Solar/Wind Harmer
-0.016
316294AC1-161 GEN
Solar/Wind Harmer
5.219
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
0.478
316246AF1-032 C
Solar/Wind Harmer
0.325
3146263WOODLND
Solar/Wind Harmer
-0.016
316093AE2-104_GEN
Solar/Wind Harmer
4.669
3146516WINFALL
Solar/Wind Harmer
-0.052
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316375AC2-012 GEN
Solar/Wind Harmer
5.543
3150981CHESPKA
Adder
1.78
315800Z1-036_GEN1
Solar/Wind Harmer
3.951
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.893
3145823KELFORD
Solar/Wind Harmer
-0.016
970661AG2-428 GEN
Solar/Wind Harmer
16.843
3146206CASHIE
Solar/Wind Harmer
-0.016
971547AH1-271 GEN
Solar/Wind Harmer
3.96
3150851SPRUNCC
Adder
0.602
3151171GRAVELC
Adder
1.339
316303AF2-085
50/50
3.93
315244AE2-183_ST
50/50
5.657
963041AG1-153 GEN
50/50
5.21
316164AC1-076 GEN
Solar/Wind Harmer
3.006
3147346CASHSCORNER
Solar/Wind Harmer
0.486
941031AE2-094 GEN
Solar/Wind Harmer
43.024
944011AF1-069 GEN
Solar/Wind Harmer
13.481
970673AG2-436 GEN
Solar/Wind Harmer
47.245
970673AG2-436 GEN
Solar/Wind Harmer
23.921
971967AH1-528 GEN
Solar/Wind Harmer
41.678
970085AG2-068 GEN
Solar/Wind Harmer
13.08
970581AG2-369 GEN
Solar/Wind Harmer
11.249
316233AE1-074 FULL
Solar/Wind Harmer
0.537
971281AH1-106 GEN
Solar/Wind Harmer
3.245
971283AH1-107 GEN
Solar/Wind Harmer
3.245
316315AB2-025 C
Solar/Wind Harmer
0.509
315814AE2-033 C
Solar/Wind Harmer
17.498
315657AE1-056 GEN
Solar/Wind Harmer
6.551
970285AG2-188 GEN
Solar/Wind Harmer
15.241
946301AF1-294 GEN
Solar/Wind Harmer
4.461
961791AG1-021 GEN
Solar/Wind Harmer
2.176
971845AH1-439 GEN
Solar/Wind Harmer
9.206
970683AG2-441 GEN
Solar/Wind Harmer
13.532
970681AG2-440 GEN
Solar/Wind Harmer
10.825
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.39
946281AF1-292 GEN
Solar/Wind Harmer
0.384
316239AB2-077_GEN
Solar/Wind Harmer
0.511
316238AB2-078_GEN
Solar/Wind Harmer
0.511
3143316POE
Solar/Wind Harmer
-0.067
316087AB2-174 GEN
Solar/Wind Harmer
2.412
970831AG2-522 GEN
Solar/Wind Harmer
8.357
972205AH1-687 GEN
Adder
6.317
3137643SOCKMAN
Solar/Wind Harmer
-0.066
315652AC1-086 GEN
Solar/Wind Harmer
18.506
315607AA1-063A GEN
Solar/Wind Harmer
1.651
3146043SEABORD
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
1.438
957871AF2-081 GEN
Solar/Wind Harmer
8.074
319010AE1-072 C
Solar/Wind Harmer
3.264
3146406KITTY HAWK
Solar/Wind Harmer
0.013
316318V4-068
Solar/Wind Harmer
0.401
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145893MURPHYS
Solar/Wind Harmer
-0.016
313526AB2-022
Solar/Wind Harmer
0.434
316305AF2-043 C
Solar/Wind Harmer
0.485
316321Z2-027
Solar/Wind Harmer
0.434
3145176PASQUOTANK
Solar/Wind Harmer
-0.01
3146396TANGLEW
Solar/Wind Harmer
0.296
3151081ELIZAR1
Adder
13.101
3151091ELIZAR2
Adder
12.874
3146486SUNBURY
Solar/Wind Harmer
-0.016
3146486SUNBURY
Solar/Wind Harmer
-0.016
315835AF2-110_GEN
Solar/Wind Harmer
2.007
3152611GOSPORTB
Adder
1.816
3152621GOSPORTC
Adder
1.541
3152601GOSPORTA
Adder
1.422
315611Z1-036_GEN2
Solar/Wind Harmer
3.951
3145513AHOSKIE
Solar/Wind Harmer
0.139
961941AG1-037 GEN
Solar/Wind Harmer
0.12
3145513AHOSKIE
Solar/Wind Harmer
-0.016
316311AC2-079 GEN
Solar/Wind Harmer
8.051
315833AF1-017_GEN
Solar/Wind Harmer
3.031
316349AD2-085 GEN
Solar/Wind Harmer
1.419
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
315816AE2-034 GEN
Solar/Wind Harmer
1.285
316118AC1-105 GEN
Solar/Wind Harmer
1.09
3146206CASHIE
Solar/Wind Harmer
-0.016
970601AG2-382 GEN
Solar/Wind Harmer
6.929
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
971285AH1-108 GEN
Adder
0.985
972265AH1-717 GEN
Adder
9.774
3151201GRAVEL4
Adder
9.162
3151191GRAVEL3
Adder
9.046
3151211GRAVEL5
Adder
9.046
315732AD1-074 GEN1
Solar/Wind Harmer
1.025
315733AD1-074 GEN2
Solar/Wind Harmer
1.025
315735AD1-075 GEN1
Solar/Wind Harmer
0.513
LAGNLTFEXP_LAGN->PJM
CLTF
5.721
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.547
TVALTFEXP_TVA->PJM
CLTF
2.88
CPLELTFEXP_CPLE->PJM
CLTF
9.138
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.402
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.442
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.658
MECLTFEXP_MEC->PJM
CLTF
2.319
SIGELTFEXP_SIGE->PJM
CLTF
0.069
NYPJM->LTFIMP_NY
CLTF
2.601
LGEELTFEXP_LGEE->PJM
CLTF
0.805
WECLTFEXP_WEC->PJM
CLTF
0.386

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 515T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.47 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5140.46
MW Contribution:29.41
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
10.055
3151731LOISA B
50/50
20.602
3151721LOISA A
50/50
20.496
970533AG2-339 GEN
50/50
18.118
970531AG2-338 GEN
50/50
7.247
315242AE2-183_GT2
50/50
3.266
315241AE2-183_GT1
50/50
3.246
972185AH1-677 GEN
50/50
11.773
3151041BRUNSWICKG3
50/50
2.568
972187AH1-678 GEN
50/50
5.893
316447AC1-158 HLD
Solar/Wind Harmer
17.893
966001AG1-469 GEN
Solar/Wind Harmer
0.606
971223AH1-071 GEN
Solar/Wind Harmer
3.098
970933AG2-581 GEN
Solar/Wind Harmer
20.166
315651AD1-115 GEN
Solar/Wind Harmer
8.933
3143526WINTERP
Solar/Wind Harmer
-0.103
970099AG2-077 GEN
Solar/Wind Harmer
24.878
3144356SAPONY
Solar/Wind Harmer
0.657
971741AH1-377 GEN
Solar/Wind Harmer
21.753
970301AG2-198 GEN
Solar/Wind Harmer
9.241
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.709
963191AG1-168 GEN
Solar/Wind Harmer
1.625
3144293JTRSVLE
Adder
0.491
3144293JTRSVLE
Adder
0.414
3146776BUCKING
Solar/Wind Harmer
-0.068
3146776BUCKING
Solar/Wind Harmer
-0.006
316034AC1-036 C
Solar/Wind Harmer
0.318
970323AG2-213 GEN
Solar/Wind Harmer
8.582
971775AH1-396 GEN
Solar/Wind Harmer
1.222
313527AB2-043 GEN
Solar/Wind Harmer
2.756
939181AE1-148 GEN
Solar/Wind Harmer
9.495
316181AB2-040 GEN
Solar/Wind Harmer
2.338
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.844
3145593CAROLNA
Solar/Wind Harmer
0.136
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.647
3145783HORNRTN
Solar/Wind Harmer
1.933
3145783HORNRTN
Solar/Wind Harmer
1.546
3145783HORNRTN
Solar/Wind Harmer
0.483
3145783HORNRTN
Solar/Wind Harmer
0.193
962561AG1-105 GEN
Solar/Wind Harmer
9.138
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.01
316185AD1-033 GEN
Solar/Wind Harmer
1.701
964791AG1-342 GEN
Solar/Wind Harmer
3.443
316339AD2-160 GEN
Solar/Wind Harmer
1.087
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
316018AA1-139 ULT2
Solar/Wind Harmer
1.38
316017AA1-139 ULT1
Solar/Wind Harmer
1.303
3137176SLIGO L2192
Solar/Wind Harmer
-0.064
3146456SLIGO L269
Solar/Wind Harmer
1.901
3130086AYDLETT
Solar/Wind Harmer
-0.064
315742AE1-103 GEN
Solar/Wind Harmer
1.681
3145893MURPHYS
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.029
3142956BIRDNECK
Solar/Wind Harmer
0.862
3146386ELIZ CT
Solar/Wind Harmer
-0.016
316316AC1-027 C
Solar/Wind Harmer
0.493
316431W1029_GEN1
Solar/Wind Harmer
2.9
316433W1029_GEN2
Solar/Wind Harmer
2.9
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316036AC1-147 C
Solar/Wind Harmer
0.431
3150991CHESPKB
Adder
1.49
3150991CHESPKB
Adder
1.454
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3152261N ANNA2
50/50
35.375
3151771S ANNAG1
50/50
1.098
3151801S ANNAS2
50/50
0.564
3151761LOISA E
50/50
42.002
972183AH1-676 GEN
50/50
328.628
3151031BRUNSWICKG2
50/50
2.568
316044AC1-158 PL1
Solar/Wind Harmer
8.137
316450AC1-158 RIC
Solar/Wind Harmer
2.17
3147666LOUISA
Solar/Wind Harmer
-0.125
3132273ORANGE
Solar/Wind Harmer
-0.006
316170AC1-121 GEN2
Solar/Wind Harmer
0.668
316313AB2-026
Solar/Wind Harmer
0.579
316258AE1-075 C
Solar/Wind Harmer
0.521
316405AF2-144 C
Solar/Wind Harmer
0.55
3143336POWHATN
Solar/Wind Harmer
2.166
970917AG2-570 GEN
Solar/Wind Harmer
52.468
316478AD1-087 GEN
Solar/Wind Harmer
1.645
316486AD2-202 GEN
Solar/Wind Harmer
0.482
970909AG2-566 GEN
Solar/Wind Harmer
1.755
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.639
3147133PAMPLIN
Solar/Wind Harmer
-0.054
971193AH1-056 GEN
Solar/Wind Harmer
10.872
963181AG1-167 GEN
Solar/Wind Harmer
1.625
3144293JTRSVLE
Adder
0.491
316365GEN2_N
Solar/Wind Harmer
1.166
959311AF2-222 GEN
Solar/Wind Harmer
17.943
3146776BUCKING
Solar/Wind Harmer
-0.006
970257AG2-171 GEN
Solar/Wind Harmer
6.437
315785AD2-033 C
Solar/Wind Harmer
3.882
966621AG1-532 GEN
Solar/Wind Harmer
0.347
3147043LAWRENC
Solar/Wind Harmer
-0.01
964241AG1-285 GEN
Solar/Wind Harmer
13.31
316131AB2-060 GEN
Solar/Wind Harmer
1.832
313506AB2-031 GEN
Solar/Wind Harmer
1.347
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
944581AF1-123 GEN
Solar/Wind Harmer
74.024
944601AF1-125 GEN
Solar/Wind Harmer
72.869
3145796HORNRTN
Solar/Wind Harmer
-0.064
3145796HORNRTN
Solar/Wind Harmer
-0.016
3156081AA2-088 GEN
Solar/Wind Harmer
5.243
3146456SLIGO L269
Solar/Wind Harmer
-0.016
971153AH1-033 GEN
Solar/Wind Harmer
1.962
315773AC2-141 GEN
Solar/Wind Harmer
6.734
3145893MURPHYS
Solar/Wind Harmer
0.112
3145893MURPHYS
Solar/Wind Harmer
-0.016
3145273HOLLAND
Solar/Wind Harmer
-0.012
316320Y1-086
Solar/Wind Harmer
0.941
957521AF2-046 GEN
Solar/Wind Harmer
12.636
961681AG1-008 GEN
Solar/Wind Harmer
12.636
3146263WOODLND
Solar/Wind Harmer
-0.016
3151101ELIZAR3
Adder
13.236
316435W1029_GEN3
Solar/Wind Harmer
2.9
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316463AE2-346 GEN
Solar/Wind Harmer
0.258
316140AB2-099
Solar/Wind Harmer
0.107
962331AG1-082 GEN
Solar/Wind Harmer
1.992
3146376EDENTON
Solar/Wind Harmer
-0.016
315614AA2-178 GEN
Solar/Wind Harmer
1.71
3156021HOLLOMANSOL
Solar/Wind Harmer
2.131
316317KELFORD C
Solar/Wind Harmer
0.746
3145823KELFORD
Solar/Wind Harmer
-0.016
970661AG2-428 GEN
Solar/Wind Harmer
2.977
3146206CASHIE
Solar/Wind Harmer
-0.016
971157AH1-035 GEN
Solar/Wind Harmer
1.974
3150861SPRUNCD
Adder
0.601
3151221GRAVEL6
Adder
9.127
3151171GRAVELC
Adder
1.756
315737AD1-076 GEN
Solar/Wind Harmer
2.59
3152251N ANNA1
50/50
35.378
3151791S ANNAG2
50/50
1.098
3151781S ANNAS1
50/50
0.564
3151741LOISA C
50/50
1.127
3151751LOISA D
50/50
20.602
970119AG2-088 GEN
50/50
29.412
315243AE2-183_GT3
50/50
3.266
3151051BRUNSWICKS1
50/50
5.329
3151021BRUNSWICKG1
50/50
2.568
971451AH1-221 GEN
50/50
7.799
316045AC1-158 PL2
Solar/Wind Harmer
26.028
3147666LOUISA
Solar/Wind Harmer
-0.218
316192AB2-158 GEN
Solar/Wind Harmer
6.369
316254AC1-120 GEN1
Solar/Wind Harmer
2.003
3143226MDLTHAN
Solar/Wind Harmer
-0.025
940641AE2-051 GEN
Solar/Wind Harmer
20.996
3143336POWHATN
Solar/Wind Harmer
2.548
970919AG2-571 GEN
Solar/Wind Harmer
6.642
970087AG2-069 GEN
Solar/Wind Harmer
19.58
939411AE1-173 GEN
Solar/Wind Harmer
104.168
316336AC2-165 C
Solar/Wind Harmer
3.581
3143526WINTERP
Solar/Wind Harmer
-0.103
957481AF2-042 GEN
Solar/Wind Harmer
62.195
315693AD1-088 GEN
Solar/Wind Harmer
9.741
962491AG1-098 GEN
Solar/Wind Harmer
12.993
315683AE1-153 C
Solar/Wind Harmer
17.63
970937AG2-583 GEN
Solar/Wind Harmer
13.209
3146926FARMVIL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
2.13
963171AG1-166 GEN
Solar/Wind Harmer
2.167
971563AH1-280 GEN
Solar/Wind Harmer
2.167
3144293JTRSVLE
Adder
0.491
316023GEN1_S
Solar/Wind Harmer
1.166
970685AG2-442 GEN
Solar/Wind Harmer
15.097
316322AB2-045
Solar/Wind Harmer
0.578
3146776BUCKING
Solar/Wind Harmer
-0.007
960081AF2-299 GEN
Solar/Wind Harmer
1.923
971795AH1-408 GEN
Solar/Wind Harmer
12.801
3147043LAWRENC
Adder
1.373
316237AB2-079_GEN
Solar/Wind Harmer
0.51
971065AG2-659 GEN
Solar/Wind Harmer
8.362
316129AC1-054 GEN
Solar/Wind Harmer
1.464
972003AH1-546 GEN
Solar/Wind Harmer
8.288
316011AB1-132 GEN
Solar/Wind Harmer
3.433
962571AG1-106 GEN
Solar/Wind Harmer
2.359
316190AA2-174 GEN
Solar/Wind Harmer
0.2
3145783HORNRTN
Solar/Wind Harmer
-0.016
944591AF1-124 GEN
Solar/Wind Harmer
74.291
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.016
970401AG2-262 GEN
Solar/Wind Harmer
1.052
316388AE2-253 GEN
Solar/Wind Harmer
1.087
3146456SLIGO L269
Solar/Wind Harmer
-0.016
316294AC1-161 GEN
Solar/Wind Harmer
5.207
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
0.477
316246AF1-032 C
Solar/Wind Harmer
0.325
3146263WOODLND
Solar/Wind Harmer
-0.016
316093AE2-104_GEN
Solar/Wind Harmer
4.657
3146516WINFALL
Solar/Wind Harmer
-0.052
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316375AC2-012 GEN
Solar/Wind Harmer
5.53
3150981CHESPKA
Adder
1.776
315800Z1-036_GEN1
Solar/Wind Harmer
3.941
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.856
3145823KELFORD
Solar/Wind Harmer
-0.016
970661AG2-428 GEN
Solar/Wind Harmer
16.801
3146206CASHIE
Solar/Wind Harmer
-0.016
971547AH1-271 GEN
Solar/Wind Harmer
3.95
3150851SPRUNCC
Adder
0.601
3151171GRAVELC
Adder
1.335
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146376EDENTON
Solar/Wind Harmer
0.472
3146376EDENTON
Solar/Wind Harmer
0.472
316065AD1-022 GEN
Solar/Wind Harmer
7.897
944641AF1-129 GEN
Adder
56.042
316303AF2-085
50/50
3.922
315244AE2-183_ST
50/50
5.646
963041AG1-153 GEN
50/50
5.199
316164AC1-076 GEN
Solar/Wind Harmer
2.965
3147346CASHSCORNER
Solar/Wind Harmer
0.478
941031AE2-094 GEN
Solar/Wind Harmer
42.941
944011AF1-069 GEN
Solar/Wind Harmer
13.455
970673AG2-436 GEN
Solar/Wind Harmer
47.152
970673AG2-436 GEN
Solar/Wind Harmer
23.874
971967AH1-528 GEN
Solar/Wind Harmer
41.593
970085AG2-068 GEN
Solar/Wind Harmer
13.053
970581AG2-369 GEN
Solar/Wind Harmer
11.226
316233AE1-074 FULL
Solar/Wind Harmer
0.536
971281AH1-106 GEN
Solar/Wind Harmer
3.237
971283AH1-107 GEN
Solar/Wind Harmer
3.237
316315AB2-025 C
Solar/Wind Harmer
0.508
315814AE2-033 C
Solar/Wind Harmer
17.459
315657AE1-056 GEN
Solar/Wind Harmer
6.523
946301AF1-294 GEN
Solar/Wind Harmer
4.443
961791AG1-021 GEN
Solar/Wind Harmer
2.167
970285AG2-188 GEN
Solar/Wind Harmer
15.154
970683AG2-441 GEN
Solar/Wind Harmer
13.48
970681AG2-440 GEN
Solar/Wind Harmer
10.784
971845AH1-439 GEN
Solar/Wind Harmer
9.152
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.378
946281AF1-292 GEN
Solar/Wind Harmer
0.383
3143316POE
Solar/Wind Harmer
-0.067
316239AB2-077_GEN
Solar/Wind Harmer
0.51
316238AB2-078_GEN
Solar/Wind Harmer
0.51
316087AB2-174 GEN
Solar/Wind Harmer
2.406
970831AG2-522 GEN
Solar/Wind Harmer
8.334
3137643SOCKMAN
Solar/Wind Harmer
-0.066
972205AH1-687 GEN
Adder
6.271
315652AC1-086 GEN
Solar/Wind Harmer
18.46
315607AA1-063A GEN
Solar/Wind Harmer
1.647
3146043SEABORD
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
1.434
957871AF2-081 GEN
Solar/Wind Harmer
8.054
319010AE1-072 C
Solar/Wind Harmer
3.256
3146406KITTY HAWK
Solar/Wind Harmer
0.013
316318V4-068
Solar/Wind Harmer
0.4
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145893MURPHYS
Solar/Wind Harmer
-0.016
313526AB2-022
Solar/Wind Harmer
0.433
316305AF2-043 C
Solar/Wind Harmer
0.483
316321Z2-027
Solar/Wind Harmer
0.433
3146396TANGLEW
Solar/Wind Harmer
0.295
3145176PASQUOTANK
Solar/Wind Harmer
-0.01
3151081ELIZAR1
Adder
13.069
3151091ELIZAR2
Adder
12.842
3146486SUNBURY
Solar/Wind Harmer
-0.016
3146486SUNBURY
Solar/Wind Harmer
-0.016
315835AF2-110_GEN
Solar/Wind Harmer
2.002
3152611GOSPORTB
Adder
1.811
3152621GOSPORTC
Adder
1.537
3152601GOSPORTA
Adder
1.418
315611Z1-036_GEN2
Solar/Wind Harmer
3.941
3145513AHOSKIE
Solar/Wind Harmer
0.139
961941AG1-037 GEN
Solar/Wind Harmer
0.12
3145513AHOSKIE
Solar/Wind Harmer
-0.016
316311AC2-079 GEN
Solar/Wind Harmer
8.031
315833AF1-017_GEN
Solar/Wind Harmer
3.024
316349AD2-085 GEN
Solar/Wind Harmer
1.416
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
315816AE2-034 GEN
Solar/Wind Harmer
1.282
316118AC1-105 GEN
Solar/Wind Harmer
1.087
3146206CASHIE
Solar/Wind Harmer
-0.016
970601AG2-382 GEN
Solar/Wind Harmer
6.912
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
971285AH1-108 GEN
Adder
0.983
972265AH1-717 GEN
Adder
9.747
3151201GRAVEL4
Adder
9.137
3151191GRAVEL3
Adder
9.022
3151211GRAVEL5
Adder
9.022
315732AD1-074 GEN1
Solar/Wind Harmer
2.756
315733AD1-074 GEN2
Solar/Wind Harmer
2.756
315735AD1-075 GEN1
Solar/Wind Harmer
1.378
LAGNLTFEXP_LAGN->PJM
CLTF
5.7
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.49
TVALTFEXP_TVA->PJM
CLTF
2.869
CPLELTFEXP_CPLE->PJM
CLTF
9.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.38
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.621
MECLTFEXP_MEC->PJM
CLTF
2.309
SIGELTFEXP_SIGE->PJM
CLTF
0.069
NYPJM->LTFIMP_NY
CLTF
2.592
LGEELTFEXP_LGEE->PJM
CLTF
0.801
WECLTFEXP_WEC->PJM
CLTF
0.384

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T573_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.18 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5050.25
MW Contribution:30.92
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
36.486
3151771S ANNAG1
50/50
1.047
3151801S ANNAS2
50/50
0.538
3151761LOISA E
50/50
39.805
972183AH1-676 GEN
50/50
309.976
3151031BRUNSWICKG2
50/50
2.703
3147666LOUISA
Solar/Wind Harmer
-0.125
316313AB2-026
Solar/Wind Harmer
0.604
316258AE1-075 C
Solar/Wind Harmer
0.544
316405AF2-144 C
Solar/Wind Harmer
0.574
3143336POWHATN
Solar/Wind Harmer
2.261
970917AG2-570 GEN
Solar/Wind Harmer
55.248
316478AD1-087 GEN
Solar/Wind Harmer
1.73
316486AD2-202 GEN
Solar/Wind Harmer
0.507
970909AG2-566 GEN
Solar/Wind Harmer
1.832
3146926FARMVIL
Solar/Wind Harmer
-0.011
316365GEN2_N
Solar/Wind Harmer
1.237
942461AE2-259 GEN
Solar/Wind Harmer
2.75
3132273ORANGE
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.057
971193AH1-056 GEN
Solar/Wind Harmer
11.36
963181AG1-167 GEN
Solar/Wind Harmer
1.7
3144293JTRSVLE
Adder
0.514
966621AG1-532 GEN
Solar/Wind Harmer
0.367
3147043LAWRENC
Solar/Wind Harmer
-0.011
959311AF2-222 GEN
Solar/Wind Harmer
18.805
970257AG2-171 GEN
Solar/Wind Harmer
6.749
315785AD2-033 C
Solar/Wind Harmer
4.072
964241AG1-285 GEN
Solar/Wind Harmer
13.983
316131AB2-060 GEN
Solar/Wind Harmer
1.926
313506AB2-031 GEN
Solar/Wind Harmer
1.428
3146776BUCKING
Solar/Wind Harmer
-0.006
944581AF1-123 GEN
Solar/Wind Harmer
79.168
944601AF1-125 GEN
Solar/Wind Harmer
77.932
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
315773AC2-141 GEN
Solar/Wind Harmer
7.21
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.098
3145796HORNRTN
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.017
3156081AA2-088 GEN
Solar/Wind Harmer
5.579
316320Y1-086
Solar/Wind Harmer
1.006
3151101ELIZAR3
Adder
14.167
3145273HOLLAND
Solar/Wind Harmer
-0.013
3144873MCLAUGH
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
3.099
3145893MURPHYS
Solar/Wind Harmer
0.119
3145893MURPHYS
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.441
961681AG1-008 GEN
Solar/Wind Harmer
13.441
3146263WOODLND
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.017
316463AE2-346 GEN
Solar/Wind Harmer
0.274
316140AB2-099
Solar/Wind Harmer
0.114
962331AG1-082 GEN
Solar/Wind Harmer
2.118
970661AG2-428 GEN
Solar/Wind Harmer
3.188
315614AA2-178 GEN
Solar/Wind Harmer
1.823
316083AB2-161 GEN
Solar/Wind Harmer
2.741
970659AG2-427 GEN
Solar/Wind Harmer
1.589
3156021HOLLOMANSOL
Solar/Wind Harmer
2.268
971157AH1-035 GEN
Solar/Wind Harmer
2.104
3146206CASHIE
Solar/Wind Harmer
-0.017
315737AD1-076 GEN
Solar/Wind Harmer
3.197
3150861SPRUNCD
Adder
0.647
3151221GRAVEL6
Adder
9.841
3151171GRAVELC
Adder
1.893
3144216WINCHST
Adder
0.457
3150921YORKTN3
Adder
2.989
316317KELFORD C
Solar/Wind Harmer
0.786
3152251N ANNA1
50/50
36.489
3151791S ANNAG2
50/50
1.047
3151781S ANNAS1
50/50
0.538
3151741LOISA C
50/50
1.068
3151751LOISA D
50/50
19.525
970119AG2-088 GEN
50/50
30.924
315243AE2-183_GT3
50/50
3.437
3151051BRUNSWICKS1
50/50
5.61
3151021BRUNSWICKG1
50/50
2.703
971451AH1-221 GEN
50/50
8.209
3147666LOUISA
Solar/Wind Harmer
-0.218
316192AB2-158 GEN
Solar/Wind Harmer
6.364
3143226MDLTHAN
Solar/Wind Harmer
-0.026
940641AE2-051 GEN
Solar/Wind Harmer
22.145
3143336POWHATN
Solar/Wind Harmer
2.66
970919AG2-571 GEN
Solar/Wind Harmer
6.993
939411AE1-173 GEN
Solar/Wind Harmer
110.17
970087AG2-069 GEN
Solar/Wind Harmer
20.618
316336AC2-165 C
Solar/Wind Harmer
3.729
3143526WINTERP
Solar/Wind Harmer
-0.109
957481AF2-042 GEN
Solar/Wind Harmer
65.393
315693AD1-088 GEN
Solar/Wind Harmer
10.229
962491AG1-098 GEN
Solar/Wind Harmer
13.642
970937AG2-583 GEN
Solar/Wind Harmer
13.661
315687AD1-152 GEN
Solar/Wind Harmer
2.242
3146926FARMVIL
Solar/Wind Harmer
-0.011
316023GEN1_S
Solar/Wind Harmer
1.237
963171AG1-166 GEN
Solar/Wind Harmer
2.266
971563AH1-280 GEN
Solar/Wind Harmer
2.266
3144293JTRSVLE
Adder
0.514
960081AF2-299 GEN
Solar/Wind Harmer
2.037
970685AG2-442 GEN
Solar/Wind Harmer
15.808
971795AH1-408 GEN
Solar/Wind Harmer
13.539
3147043LAWRENC
Adder
1.452
316237AB2-079_GEN
Solar/Wind Harmer
0.536
316322AB2-045
Solar/Wind Harmer
0.597
3146776BUCKING
Solar/Wind Harmer
-0.007
971065AG2-659 GEN
Solar/Wind Harmer
8.829
316129AC1-054 GEN
Solar/Wind Harmer
1.546
316011AB1-132 GEN
Solar/Wind Harmer
3.643
962571AG1-106 GEN
Solar/Wind Harmer
2.503
944591AF1-124 GEN
Solar/Wind Harmer
79.453
315683AE1-153 C
Solar/Wind Harmer
16.116
316190AA2-174 GEN
Solar/Wind Harmer
0.212
3145783HORNRTN
Solar/Wind Harmer
-0.017
316388AE2-253 GEN
Solar/Wind Harmer
1.162
316294AC1-161 GEN
Solar/Wind Harmer
5.575
3146456SLIGO L269
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.017
316246AF1-032 C
Solar/Wind Harmer
0.347
316093AE2-104_GEN
Solar/Wind Harmer
4.98
316375AC2-012 GEN
Solar/Wind Harmer
5.919
3150981CHESPKA
Adder
1.901
3145893MURPHYS
Solar/Wind Harmer
-0.068
3146516WINFALL
Solar/Wind Harmer
-0.055
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.507
972003AH1-546 GEN
Solar/Wind Harmer
8.52
315800Z1-036_GEN1
Solar/Wind Harmer
4.209
3146263WOODLND
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
970401AG2-262 GEN
Solar/Wind Harmer
1.108
970661AG2-428 GEN
Solar/Wind Harmer
17.989
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145663CRESWEL
Solar/Wind Harmer
-0.047
971163AH1-040 GEN
Solar/Wind Harmer
15.843
316381AD1-082 GEN
Solar/Wind Harmer
1.549
970659AG2-427 GEN
Solar/Wind Harmer
8.964
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.207
3150851SPRUNCC
Adder
0.647
3151171GRAVELC
Adder
1.44
971133AH1-012 GEN
50/50
10.184
3151731LOISA B
50/50
19.525
3151721LOISA A
50/50
19.424
970533AG2-339 GEN
50/50
19.068
970531AG2-338 GEN
50/50
7.627
315242AE2-183_GT2
50/50
3.437
315241AE2-183_GT1
50/50
3.416
972185AH1-677 GEN
50/50
12.391
3151041BRUNSWICKG3
50/50
2.703
972187AH1-678 GEN
50/50
6.203
966001AG1-469 GEN
Solar/Wind Harmer
0.526
971223AH1-071 GEN
Solar/Wind Harmer
3.257
970933AG2-581 GEN
Solar/Wind Harmer
21.214
3143526WINTERP
Solar/Wind Harmer
-0.109
970099AG2-077 GEN
Solar/Wind Harmer
26.157
3144356SAPONY
Solar/Wind Harmer
0.696
971741AH1-377 GEN
Solar/Wind Harmer
22.746
970301AG2-198 GEN
Solar/Wind Harmer
9.65
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.015
958211AF2-115 GEN
Solar/Wind Harmer
2.833
963191AG1-168 GEN
Solar/Wind Harmer
1.7
3144293JTRSVLE
Adder
0.514
3144293JTRSVLE
Adder
0.433
316034AC1-036 C
Solar/Wind Harmer
0.334
970323AG2-213 GEN
Solar/Wind Harmer
8.998
971775AH1-396 GEN
Solar/Wind Harmer
1.281
313527AB2-043 GEN
Solar/Wind Harmer
2.899
939181AE1-148 GEN
Solar/Wind Harmer
10.003
316181AB2-040 GEN
Solar/Wind Harmer
2.478
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.955
3145593CAROLNA
Solar/Wind Harmer
0.144
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.747
3145783HORNRTN
Solar/Wind Harmer
2.049
3145783HORNRTN
Solar/Wind Harmer
1.64
3145783HORNRTN
Solar/Wind Harmer
0.512
3145783HORNRTN
Solar/Wind Harmer
0.205
316185AD1-033 GEN
Solar/Wind Harmer
1.82
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.041
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.162
316018AA1-139 ULT2
Solar/Wind Harmer
1.476
316017AA1-139 ULT1
Solar/Wind Harmer
1.394
3137176SLIGO L2192
Solar/Wind Harmer
-0.068
3146456SLIGO L269
Solar/Wind Harmer
2.033
3130086AYDLETT
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.051
3142956BIRDNECK
Solar/Wind Harmer
0.922
316316AC1-027 C
Solar/Wind Harmer
0.527
3146386ELIZ CT
Solar/Wind Harmer
-0.017
315742AE1-103 GEN
Solar/Wind Harmer
1.793
316036AC1-147 C
Solar/Wind Harmer
0.461
3150991CHESPKB
Adder
1.595
3150991CHESPKB
Adder
1.556
316431W1029_GEN1
Solar/Wind Harmer
3.099
316433W1029_GEN2
Solar/Wind Harmer
3.099
962561AG1-105 GEN
Solar/Wind Harmer
9.62
3145893MURPHYS
Solar/Wind Harmer
0.477
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
0.504
3146376EDENTON
Solar/Wind Harmer
0.504
964791AG1-342 GEN
Solar/Wind Harmer
3.625
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970657AG2-426 GEN
Solar/Wind Harmer
5.283
970657AG2-426 GEN
Solar/Wind Harmer
1.105
316065AD1-022 GEN
Solar/Wind Harmer
8.412
944641AF1-129 GEN
Adder
60.727
316303AF2-085
50/50
4.123
315244AE2-183_ST
50/50
5.943
963041AG1-153 GEN
50/50
5.473
3147346CASHSCORNER
Solar/Wind Harmer
0.451
941031AE2-094 GEN
Solar/Wind Harmer
45.192
944011AF1-069 GEN
Solar/Wind Harmer
14.16
970673AG2-436 GEN
Solar/Wind Harmer
49.627
970673AG2-436 GEN
Solar/Wind Harmer
25.128
971967AH1-528 GEN
Solar/Wind Harmer
43.766
970085AG2-068 GEN
Solar/Wind Harmer
13.745
970581AG2-369 GEN
Solar/Wind Harmer
11.821
316233AE1-074 FULL
Solar/Wind Harmer
0.568
971281AH1-106 GEN
Solar/Wind Harmer
3.433
971283AH1-107 GEN
Solar/Wind Harmer
3.433
316315AB2-025 C
Solar/Wind Harmer
0.538
315814AE2-033 C
Solar/Wind Harmer
18.51
315657AE1-056 GEN
Solar/Wind Harmer
6.816
946301AF1-294 GEN
Solar/Wind Harmer
4.646
961791AG1-021 GEN
Solar/Wind Harmer
2.266
946281AF1-292 GEN
Solar/Wind Harmer
0.406
3143316POE
Solar/Wind Harmer
-0.071
970683AG2-441 GEN
Solar/Wind Harmer
14.114
970681AG2-440 GEN
Solar/Wind Harmer
11.291
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.542
970285AG2-188 GEN
Solar/Wind Harmer
15.689
316087AB2-174 GEN
Solar/Wind Harmer
2.549
971845AH1-439 GEN
Solar/Wind Harmer
9.467
316239AB2-077_GEN
Solar/Wind Harmer
0.536
316238AB2-078_GEN
Solar/Wind Harmer
0.536
970831AG2-522 GEN
Solar/Wind Harmer
8.805
3137643SOCKMAN
Solar/Wind Harmer
-0.07
315652AC1-086 GEN
Solar/Wind Harmer
19.588
315607AA1-063A GEN
Solar/Wind Harmer
1.748
3146043SEABORD
Solar/Wind Harmer
-0.017
957871AF2-081 GEN
Solar/Wind Harmer
8.614
319010AE1-072 C
Solar/Wind Harmer
3.482
3146406KITTY HAWK
Solar/Wind Harmer
0.014
3145796HORNRTN
Solar/Wind Harmer
-0.055
3145796HORNRTN
Solar/Wind Harmer
-0.007
965291AG1-394 GEN
Solar/Wind Harmer
1.526
313526AB2-022
Solar/Wind Harmer
0.463
316305AF2-043 C
Solar/Wind Harmer
0.517
3151081ELIZAR1
Adder
13.988
3151091ELIZAR2
Adder
13.745
316321Z2-027
Solar/Wind Harmer
0.462
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3146396TANGLEW
Solar/Wind Harmer
0.315
315835AF2-110_GEN
Solar/Wind Harmer
2.141
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
3152611GOSPORTB
Adder
1.939
3152621GOSPORTC
Adder
1.646
3152601GOSPORTA
Adder
1.518
316318V4-068
Solar/Wind Harmer
0.426
3145893MURPHYS
Solar/Wind Harmer
-0.046
3145893MURPHYS
Solar/Wind Harmer
-0.017
316311AC2-079 GEN
Solar/Wind Harmer
8.593
315611Z1-036_GEN2
Solar/Wind Harmer
4.209
315833AF1-017_GEN
Solar/Wind Harmer
3.235
316349AD2-085 GEN
Solar/Wind Harmer
1.515
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.148
961941AG1-037 GEN
Solar/Wind Harmer
0.127
3145513AHOSKIE
Solar/Wind Harmer
-0.017
972205AH1-687 GEN
Adder
6.438
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
315816AE2-034 GEN
Solar/Wind Harmer
1.367
3130546PLYMOUTH
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.362
315732AD1-074 GEN1
Solar/Wind Harmer
3.402
315733AD1-074 GEN2
Solar/Wind Harmer
3.402
315735AD1-075 GEN1
Solar/Wind Harmer
1.701
971285AH1-108 GEN
Adder
1.059
972265AH1-717 GEN
Adder
10.51
3151201GRAVEL4
Adder
9.853
3151191GRAVEL3
Adder
9.728
3151211GRAVEL5
Adder
9.728
LAGNLTFEXP_LAGN->PJM
CLTF
6.191
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.725
TVALTFEXP_TVA->PJM
CLTF
3.115
CPLELTFEXP_CPLE->PJM
CLTF
9.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.121
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.634
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.492
MECLTFEXP_MEC->PJM
CLTF
2.607
SIGELTFEXP_SIGE->PJM
CLTF
0.078
NYPJM->LTFIMP_NY
CLTF
2.609
LGEELTFEXP_LGEE->PJM
CLTF
0.916
WECLTFEXP_WEC->PJM
CLTF
0.445

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.08 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:8277.02
MW Contribution:48.23
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
24.932
970119AG2-088 GEN
50/50
48.227
3150851SPRUNCC
50/50
1.706
3143096IRON208
50/50
1.529
3143226MDLTHAN
Solar/Wind Harmer
-0.041
3143526WINTERP
Solar/Wind Harmer
-0.207
3142543TWELFTH
Solar/Wind Harmer
-0.004
3142416OLDCHRC
Solar/Wind Harmer
-0.1
3142416OLDCHRC
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
35.93
944631AF1-128 GEN
Adder
162.412
315671AE2-027_GEN
Solar/Wind Harmer
28.648
939411AE1-173 GEN
Solar/Wind Harmer
190.668
316294AC1-161 GEN
Solar/Wind Harmer
12.329
970129AG2-093 GEN
Solar/Wind Harmer
8.69
316458AB2-190 GEN2
Solar/Wind Harmer
3.853
971069AG2-661 GEN
Solar/Wind Harmer
6.016
971647AH1-324 GEN
Solar/Wind Harmer
18.957
961611AG1-000B GEN
Solar/Wind Harmer
18.682
3151171GRAVELC
Adder
3.577
316159AE1-175 C
Solar/Wind Harmer
1.013
3145336SMITFLD
Solar/Wind Harmer
-0.15
944591AF1-124 GEN
Solar/Wind Harmer
172.182
966881AG1-559 GEN
Solar/Wind Harmer
0.388
316375AC2-012 GEN
Solar/Wind Harmer
13.033
3150981CHESPKA
Adder
4.185
970659AG2-427 GEN
Solar/Wind Harmer
20.009
3138126ROCKLANDING
Solar/Wind Harmer
0.115
316381AD1-082 GEN
Solar/Wind Harmer
3.451
970661AG2-428 GEN
Solar/Wind Harmer
39.862
971317AH1-138 GEN
Solar/Wind Harmer
4.684
316388AE2-253 GEN
Solar/Wind Harmer
2.52
316072AD1-144
Solar/Wind Harmer
0.755
3146456SLIGO L269
Solar/Wind Harmer
-0.037
316246AF1-032 C
Solar/Wind Harmer
0.752
316093AE2-104_GEN
Solar/Wind Harmer
10.761
3142433PROV 92
Solar/Wind Harmer
-0.147
3142433PROV 92
Adder
0.64
3142433PROV 92
Adder
0.64
972197AH1-683 GEN
Adder
6.897
972219AH1-694 GEN
Adder
4.966
3146516WINFALL
Solar/Wind Harmer
-0.117
3146516WINFALL
Solar/Wind Harmer
-0.036
3147666LOUISA
Solar/Wind Harmer
-0.144
971777AH1-397 GEN
Solar/Wind Harmer
4.252
3141843SHACKLE
Adder
1.644
3141766HARMONY
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
8.871
3130156CHOWAN
Solar/Wind Harmer
-0.035
316192AB2-158 GEN
Solar/Wind Harmer
4.195
3138133OCRAN
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
4.148
3145663CRESWEL
Solar/Wind Harmer
-0.097
971163AH1-040 GEN
Solar/Wind Harmer
32.582
970919AG2-571 GEN
Solar/Wind Harmer
10.938
970087AG2-069 GEN
Solar/Wind Harmer
32.274
961951AG1-038 GEN
Solar/Wind Harmer
4.47
316023GEN1_S
Solar/Wind Harmer
2.287
3146206CASHIE
Solar/Wind Harmer
-0.034
971547AH1-271 GEN
Solar/Wind Harmer
8.439
3145893MURPHYS
Solar/Wind Harmer
-0.134
3145893MURPHYS
Solar/Wind Harmer
0.999
962861AG1-135 GEN
Solar/Wind Harmer
12.565
316336AC2-165 C
Solar/Wind Harmer
5.815
3146173TUNIS
Solar/Wind Harmer
-0.033
960081AF2-299 GEN
Solar/Wind Harmer
3.72
957481AF2-042 GEN
Solar/Wind Harmer
103.301
3145683EARLEYS
Solar/Wind Harmer
-0.033
3146263WOODLND
Solar/Wind Harmer
-0.033
964211AG1-282 GEN
Solar/Wind Harmer
0.987
3141726DUNNSVL
Solar/Wind Harmer
-0.131
3145963POPLR C
Solar/Wind Harmer
-0.032
316011AB1-132 GEN
Solar/Wind Harmer
6.808
962571AG1-106 GEN
Solar/Wind Harmer
4.677
3145823KELFORD
Solar/Wind Harmer
-0.032
315693AD1-088 GEN
Solar/Wind Harmer
16.208
316190AA2-174 GEN
Solar/Wind Harmer
0.398
971795AH1-408 GEN
Solar/Wind Harmer
24.298
962491AG1-098 GEN
Solar/Wind Harmer
21.614
3150351NORNECKC2
Adder
2.867
316174AB2-169 GEN
Solar/Wind Harmer
4.976
3147043LAWRENC
Adder
2.584
3145783HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.105
3145796HORNRTN
Solar/Wind Harmer
-0.032
316212AC1-099_GEN
Solar/Wind Harmer
2.729
3146293MARTNCO
Solar/Wind Harmer
0.193
3144293JTRSVLE
Adder
0.837
972277AH1-723 GEN
Adder
133.532
3151751LOISA D
Adder
11.364
316045AC1-158 PL2
Solar/Wind Helper
15.147
316006AB2-029 C
Solar/Wind Helper
0.159
316254AC1-120 GEN1
Solar/Wind Helper
1.225
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.373
237080AD1-060 GEN
Solar/Wind Helper
0.304
237038AE2-054 C
Solar/Wind Helper
0.241
235062AE1-101 C1
Solar/Wind Helper
1.47
966131AG1-482 GEN
Solar/Wind Helper
0.075
233930AB2-032 GEN
Solar/Wind Helper
0.369
233915AB1-141 GEN
Solar/Wind Helper
0.487
232422X3-066 FULL
Solar/Wind Helper
0.111
233964AF2-378 GEN
Solar/Wind Helper
0.04
232426Y1-080 FULL
Solar/Wind Helper
0.038
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.491
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.293
238148AE2-230_GEN2
Solar/Wind Helper
0.39
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.126
971133AH1-012 GEN
50/50
6.819
3142296MT RD221
50/50
1.172
3142366NRTHEST
50/50
1.196
3150691DARBY 3
50/50
26.261
3150701DARBY 4
50/50
26.199
3150681DARBY 2
50/50
26.169
971223AH1-071 GEN
Solar/Wind Harmer
5.08
3143526WINTERP
Solar/Wind Harmer
-0.207
3150671DARBY 1
Adder
24.633
944641AF1-129 GEN
Adder
162.93
316240AF1-291 C
Solar/Wind Harmer
1.156
316075AC2-137 C
Solar/Wind Harmer
1.03
3142946ENON
Solar/Wind Harmer
-0.004
316033AB2-134 GEN
Solar/Wind Harmer
12.245
315697AD1-025 GEN
Solar/Wind Harmer
7.68
316236AE1-162_GEN
Solar/Wind Harmer
1.137
957411AF2-035 GEN
Solar/Wind Harmer
16.975
970317AG2-208 GEN
Solar/Wind Harmer
16.504
316036AC1-147 C
Solar/Wind Harmer
1.016
3150991CHESPKB
Adder
3.511
3150991CHESPKB
Adder
3.427
316316AC1-027 C
Solar/Wind Harmer
1.154
3142956BIRDNECK
Solar/Wind Harmer
2.018
970657AG2-426 GEN
Solar/Wind Harmer
11.745
970657AG2-426 GEN
Solar/Wind Harmer
2.456
316185AD1-033 GEN
Solar/Wind Harmer
3.963
3145506HICKORY
Solar/Wind Harmer
-0.149
3145506HICKORY
Solar/Wind Harmer
-0.09
3145506HICKORY
Solar/Wind Harmer
-0.022
315673AE1-157 GEN
Solar/Wind Harmer
28.094
316339AD2-160 GEN
Solar/Wind Harmer
2.52
966871AG1-558 GEN
Solar/Wind Harmer
1.122
966871AG1-558 GEN
Solar/Wind Harmer
0.384
316018AA1-139 ULT2
Solar/Wind Harmer
3.198
316017AA1-139 ULT1
Solar/Wind Harmer
3.021
3137176SLIGO L2192
Solar/Wind Harmer
-0.147
3146456SLIGO L269
Solar/Wind Harmer
4.4
3130086AYDLETT
Solar/Wind Harmer
-0.148
3150391LDYSMT3
Adder
44.085
972195AH1-682 GEN
Adder
5.793
3146386ELIZ CT
Solar/Wind Harmer
-0.037
3144356SAPONY
Solar/Wind Harmer
1.276
316431W1029_GEN1
Solar/Wind Harmer
6.618
316433W1029_GEN2
Solar/Wind Harmer
6.618
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
972185AH1-677 GEN
Adder
18.085
316441AF1-014 GEN
Solar/Wind Harmer
2.437
972187AH1-678 GEN
Adder
9.074
315742AE1-103 GEN
Solar/Wind Harmer
3.731
3146376EDENTON
Solar/Wind Harmer
1.053
3146376EDENTON
Solar/Wind Harmer
1.053
970933AG2-581 GEN
Solar/Wind Harmer
33.038
316487AF1-042 GEN
Solar/Wind Harmer
4.47
316065AD1-022 GEN
Solar/Wind Harmer
16.937
3145893MURPHYS
Solar/Wind Harmer
0.939
3145893MURPHYS
Solar/Wind Harmer
-0.06
3146173TUNIS
Solar/Wind Harmer
-0.033
3146173TUNIS
Solar/Wind Harmer
-0.033
958261AF2-120 GEN
Solar/Wind Harmer
12.924
970099AG2-077 GEN
Solar/Wind Harmer
41.32
316181AB2-040 GEN
Solar/Wind Harmer
4.56
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.274
316077AC2-138 C
Solar/Wind Harmer
0.682
3150341NORNECKC1
Adder
3.012
3150341NORNECKC1
Adder
2.987
3145593CAROLNA
Solar/Wind Harmer
-0.032
3145593CAROLNA
Solar/Wind Harmer
-0.032
966811AG1-552 GEN
Solar/Wind Harmer
3.63
3145593CAROLNA
Solar/Wind Harmer
0.268
3145783HORNRTN
Solar/Wind Harmer
3.807
3145783HORNRTN
Solar/Wind Harmer
3.046
3145783HORNRTN
Solar/Wind Harmer
0.952
3145783HORNRTN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
-0.096
316468AD1-105 GEN
Solar/Wind Harmer
3.513
3145933PARMELE
Solar/Wind Harmer
-0.062
3145933PARMELE
Solar/Wind Harmer
-0.031
316274AC1-208 GEN
Solar/Wind Harmer
3.354
3144293JTRSVLE
Adder
0.837
3144293JTRSVLE
Adder
0.705
3151731LOISA B
Adder
11.364
3151721LOISA A
Adder
11.305
316447AC1-158 HLD
Solar/Wind Helper
10.414
315651AD1-115 GEN
Solar/Wind Helper
0.939
226929AD2-058 GEN
Solar/Wind Helper
0.108
23777801MSM_W1-116
Solar/Wind Helper
0.111
237025AB1-124 C
Solar/Wind Helper
0.161
237006AB1-125 GEN
Solar/Wind Helper
0.121
237034AC2-136 C
Solar/Wind Helper
0.211
23777901MDS_W4-102
Solar/Wind Helper
0.157
235020AA1-095 C
Solar/Wind Helper
0.046
237001AB1-127_GEN
Solar/Wind Helper
0.396
237002AB1-128_GEN
Solar/Wind Helper
0.396
235063AE1-101 C2
Solar/Wind Helper
1.47
238175AF1-290_GEN
Solar/Wind Helper
0.127
238169AE2-226 GEN1
Solar/Wind Helper
0.578
238170AE2-226 GEN2
Solar/Wind Helper
0.578
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
205916AD1-020 GEN
Solar/Wind Helper
1.656
233933AB2-153 GEN
Solar/Wind Helper
0.225
233987AB2-037 GEN
Solar/Wind Helper
2.269
233944AB2-135 GEN
Solar/Wind Helper
0.57
232424Y1-079 C
Solar/Wind Helper
0.113
233946AB2-136 GEN
Solar/Wind Helper
0.55
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.491
232410W1-006 C
Solar/Wind Helper
0.491
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
20390526W1-045 C
Solar/Wind Helper
0.327
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
3152261N ANNA2
50/50
24.93
970497AG2-320 GEN
50/50
33.128
3150861SPRUNCD
50/50
1.706
971645AH1-323 GEN
50/50
30.891
3143096IRON208
50/50
1.529
3143096IRON208
50/50
1.499
3142416OLDCHRC
Solar/Wind Harmer
3.892
970293AG2-193 GEN
Solar/Wind Harmer
4.804
315839AE2-212 C
Solar/Wind Harmer
1.153
970133AG2-095 GEN
Solar/Wind Harmer
4.299
3142946ENON
Solar/Wind Harmer
-0.013
965281AG1-393 GEN
Solar/Wind Harmer
4.773
315773AC2-141 GEN
Solar/Wind Harmer
15.945
970129AG2-093 GEN
Solar/Wind Harmer
21.453
315778AD1-151 GEN
Solar/Wind Harmer
32.937
315813AE1-149 C
Solar/Wind Harmer
23.666
961611AG1-000B GEN
Solar/Wind Harmer
7.971
3151221GRAVEL6
Adder
24.448
3151171GRAVELC
Adder
4.704
316382AG1-145 C
Solar/Wind Harmer
1.138
3145336SMITFLD
Solar/Wind Harmer
-0.015
944581AF1-123 GEN
Solar/Wind Harmer
171.564
944601AF1-125 GEN
Solar/Wind Harmer
168.886
966881AG1-559 GEN
Solar/Wind Harmer
1.134
3144536CHRHLND
Solar/Wind Harmer
-0.006
3151101ELIZAR3
Adder
31.133
970659AG2-427 GEN
Solar/Wind Harmer
3.546
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3144216WINCHST
Adder
1.263
316083AB2-161 GEN
Solar/Wind Harmer
6.107
3150921YORKTN3
Adder
8.413
970661AG2-428 GEN
Solar/Wind Harmer
7.064
316473AC1-191 GEN
Solar/Wind Harmer
4.017
3146456SLIGO L269
Solar/Wind Harmer
-0.037
971153AH1-033 GEN
Solar/Wind Harmer
4.542
3142433PROV 92
Adder
0.64
3142433PROV 92
Adder
0.64
3150401LDYSMT4
Adder
44.168
3150371LDYSMT1
Adder
42.678
316320Y1-086
Solar/Wind Harmer
2.162
316435W1029_GEN3
Solar/Wind Harmer
6.618
3146516WINFALL
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
3147666LOUISA
Solar/Wind Harmer
-0.083
3141843SHACKLE
Adder
1.644
316203AE2-005 GEN
Solar/Wind Harmer
15.244
3141766HARMONY
Solar/Wind Harmer
3.217
3145273HOLLAND
Solar/Wind Harmer
-0.027
316280AD1-041 GEN
Solar/Wind Harmer
2.715
316156AD2-030 GEN
Solar/Wind Harmer
0.958
3141873WAN 176
Solar/Wind Harmer
4.258
3146376EDENTON
Solar/Wind Harmer
-0.035
316313AB2-026
Solar/Wind Harmer
0.943
316258AE1-075 C
Solar/Wind Harmer
0.849
316405AF2-144 C
Solar/Wind Harmer
0.895
3143336POWHATN
Solar/Wind Harmer
3.526
315614AA2-178 GEN
Solar/Wind Harmer
3.75
970917AG2-570 GEN
Solar/Wind Harmer
86.408
962971AG1-146 GEN
Solar/Wind Harmer
6.43
971157AH1-035 GEN
Solar/Wind Harmer
4.274
3156081AA2-088 GEN
Solar/Wind Harmer
11.067
315737AD1-076 GEN
Solar/Wind Harmer
6.478
316484AD2-074 GEN
Solar/Wind Harmer
8.542
970009AG2-005 GEN
Solar/Wind Harmer
4.242
316365GEN2_N
Solar/Wind Harmer
2.287
3146206CASHIE
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
-0.034
957521AF2-046 GEN
Solar/Wind Harmer
26.442
961681AG1-008 GEN
Solar/Wind Harmer
26.442
3146173TUNIS
Solar/Wind Harmer
-0.033
316404AE1-155 C
Solar/Wind Harmer
6.434
3156021HOLLOMANSOL
Solar/Wind Harmer
4.485
316463AE2-346 GEN
Solar/Wind Harmer
0.537
316140AB2-099
Solar/Wind Harmer
0.224
962331AG1-082 GEN
Solar/Wind Harmer
4.15
966621AG1-532 GEN
Solar/Wind Harmer
0.671
3146263WOODLND
Solar/Wind Harmer
-0.033
313506AB2-031 GEN
Solar/Wind Harmer
2.628
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3145963POPLR C
Solar/Wind Harmer
-0.032
316317KELFORD C
Solar/Wind Harmer
1.529
3145823KELFORD
Solar/Wind Harmer
-0.032
3150351NORNECKC2
Adder
2.915
3147043LAWRENC
Solar/Wind Harmer
-0.019
3145796HORNRTN
Solar/Wind Harmer
-0.128
3145796HORNRTN
Solar/Wind Harmer
-0.032
316478AD1-087 GEN
Solar/Wind Harmer
2.758
316486AD2-202 GEN
Solar/Wind Harmer
0.808
971781AH1-399 GEN
Solar/Wind Harmer
1.944
316210AC1-098 GEN
Solar/Wind Harmer
4.912
3145933PARMELE
Solar/Wind Harmer
-0.031
966801AG1-551 GEN
Solar/Wind Harmer
3.899
3144293JTRSVLE
Adder
0.837
972255AH1-712 GEN
Adder
114.59
3151761LOISA E
Adder
23.168
972183AH1-676 GEN
Adder
179.308
3141316ARNOLDS
Adder
0.38
3150331BIRCHWDA
Adder
23.913
3151861LOWMORA
Adder
1.295
316044AC1-158 PL1
Solar/Wind Helper
4.732
316450AC1-158 RIC
Solar/Wind Helper
1.262
3141196NOKESVL
Solar/Wind Helper
1.429
227287AC2-120 GEN
Solar/Wind Helper
0.373
226910AB2-157 C
Solar/Wind Helper
0.015
316170AC1-121 GEN2
Solar/Wind Helper
0.408
237030AB1-096 C
Solar/Wind Helper
0.069
223402AF1-300 C
Solar/Wind Helper
0.373
238221AF1-254 C O1
Solar/Wind Helper
0.245
235067AD1-061 GEN
Solar/Wind Helper
0.438
205917AD1-020 ES
Solar/Wind Helper
0.356
233918AB1-142 GEN
Solar/Wind Helper
0.487
233982AB2-133 GEN
Solar/Wind Helper
0.347
233994AC2-023 GEN
Solar/Wind Helper
0.931
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.491
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
238147AE2-230_GEN1
Solar/Wind Helper
0.388
238149AF1-291A_GEN
Solar/Wind Helper
0.111
230430AE1-229_GEN
Solar/Wind Helper
3.252
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.106
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.11
959561AF2-247 GEN
Solar/Wind Helper
0.02
316303AF2-085
50/50
6.43
971285AH1-108 GEN
50/50
2.792
316233AE1-074 FULL
Solar/Wind Harmer
1.077
971281AH1-106 GEN
Solar/Wind Harmer
6.508
971283AH1-107 GEN
Solar/Wind Harmer
6.508
316312AB1-027
Solar/Wind Harmer
1.301
972189AH1-679 GEN
Adder
5.748
316132AB2-190 GEN1
Solar/Wind Harmer
3.853
3143316POE
Solar/Wind Harmer
-0.15
316369SG1_INVT
Solar/Wind Harmer
6.784
315976AC1-164 GENA
Solar/Wind Harmer
40.068
316169AC1-164_GENC
Solar/Wind Harmer
34.615
315975AC1-164 GENB
Solar/Wind Harmer
1.185
972265AH1-717 GEN
Adder
26.11
3151201GRAVEL4
Adder
24.476
3151191GRAVEL3
Adder
24.166
3151211GRAVEL5
Adder
24.166
971445AH1-216 GEN
Solar/Wind Harmer
23.358
3151081ELIZAR1
Adder
30.739
3151091ELIZAR2
Adder
30.205
3152611GOSPORTB
Adder
4.268
3152621GOSPORTC
Adder
3.622
3152601GOSPORTA
Adder
3.342
957871AF2-081 GEN
Solar/Wind Harmer
18.665
315833AF1-017_GEN
Solar/Wind Harmer
7.074
316349AD2-085 GEN
Solar/Wind Harmer
3.313
316311AC2-079 GEN
Solar/Wind Harmer
18.784
319010AE1-072 C
Solar/Wind Harmer
7.531
3146406KITTY HAWK
Solar/Wind Harmer
0.031
316305AF2-043 C
Solar/Wind Harmer
1.121
941031AE2-094 GEN
Solar/Wind Harmer
69.631
944011AF1-069 GEN
Solar/Wind Harmer
21.818
971167AH1-042 GEN
Solar/Wind Harmer
35.733
315835AF2-110_GEN
Solar/Wind Harmer
4.626
3142433PROV 92
Adder
0.64
3142433PROV 92
Adder
0.64
3150411LDYSMT5
Adder
44.306
3150381LDYSMT2
Adder
42.402
972213AH1-691 GEN
Adder
7.173
972215AH1-692 GEN
Adder
7.173
313526AB2-022
Solar/Wind Harmer
0.995
3146486SUNBURY
Solar/Wind Harmer
-0.037
3146486SUNBURY
Solar/Wind Harmer
-0.037
957831AF2-077 GEN
Solar/Wind Harmer
1.106
3138283WHITEMARSH
Solar/Wind Harmer
0.057
316321Z2-027
Solar/Wind Harmer
0.991
3146396TANGLEW
Solar/Wind Harmer
0.676
3145176PASQUOTANK
Solar/Wind Harmer
-0.023
316315AB2-025 C
Solar/Wind Harmer
0.987
3143873LANEXA
Solar/Wind Harmer
-0.022
970673AG2-436 GEN
Solar/Wind Harmer
76.723
970673AG2-436 GEN
Solar/Wind Harmer
38.847
315814AE2-033 C
Solar/Wind Harmer
33.934
316314AB2-024 C
Solar/Wind Harmer
3.103
316059AD1-063 C
Solar/Wind Harmer
0.817
971967AH1-528 GEN
Solar/Wind Harmer
67.827
315662AE1-191 GEN
Solar/Wind Harmer
4.344
315666AE1-190 GEN
Solar/Wind Harmer
1.086
315611Z1-036_GEN2
Solar/Wind Harmer
8.871
957601AF2-054 GEN
Solar/Wind Harmer
1.073
3141873WAN 176
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.035
3130156CHOWAN
Solar/Wind Harmer
-0.035
3141913WHIT STONE
Solar/Wind Harmer
-0.035
3138133OCRAN
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.021
3141783LANCAST
Solar/Wind Harmer
-0.014
315816AE2-034 GEN
Solar/Wind Harmer
2.812
970085AG2-068 GEN
Solar/Wind Harmer
21.516
970581AG2-369 GEN
Solar/Wind Harmer
18.504
962981AG1-147 GEN
Solar/Wind Harmer
15.002
3130546PLYMOUTH
Solar/Wind Harmer
-0.034
315732AD1-074 GEN1
Solar/Wind Harmer
6.893
315733AD1-074 GEN2
Solar/Wind Harmer
6.893
315735AD1-075 GEN1
Solar/Wind Harmer
3.447
965291AG1-394 GEN
Solar/Wind Harmer
3.013
3146206CASHIE
Solar/Wind Harmer
-0.034
970601AG2-382 GEN
Solar/Wind Harmer
14.768
316318V4-068
Solar/Wind Harmer
0.839
3145893MURPHYS
Solar/Wind Harmer
-0.09
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145513AHOSKIE
Solar/Wind Harmer
0.289
961941AG1-037 GEN
Solar/Wind Harmer
0.25
3145513AHOSKIE
Solar/Wind Harmer
-0.033
946281AF1-292 GEN
Solar/Wind Harmer
0.741
3145683EARLEYS
Solar/Wind Harmer
-0.066
3145683EARLEYS
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.033
3146043SEABORD
Solar/Wind Harmer
-0.033
315607AA1-063A GEN
Solar/Wind Harmer
3.327
316087AB2-174 GEN
Solar/Wind Harmer
4.68
315652AC1-086 GEN
Solar/Wind Harmer
36.606
3137643SOCKMAN
Solar/Wind Harmer
-0.129
3141813NORNECK
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.013
3146033SCOT NK
Solar/Wind Harmer
-0.127
972205AH1-687 GEN
Adder
10.039
972193AH1-681 GEN
Adder
5.12
3151881LOWMORC
Adder
1.285
3151881LOWMORC
Adder
1.265
3151861LOWMORA
Adder
1.245
316164AC1-076 GEN
Solar/Wind Helper
1.978
316411AF1-147_GEN1
Solar/Wind Helper
1.078
316415AF1-147_GEN2
Solar/Wind Helper
1.078
3138216PACIFIC
Solar/Wind Helper
0.053
237085AD2-009_GEN
Solar/Wind Helper
1.439
238208AF1-136 C
Solar/Wind Helper
0.182
960921AF2-383 GEN
Solar/Wind Helper
0.176
205943AE1-185 GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.23
205932AD2-116_GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.928
233990AG1-397 GEN
Solar/Wind Helper
0.029
234033AF1-007_GEN
Solar/Wind Helper
6.799
232432Z2-076 GEN
Solar/Wind Helper
0.065
959381AF2-229 GEN
Solar/Wind Helper
0.334
238152AF2-075_GEN
Solar/Wind Helper
0.554
964001AG1-254 GEN
Solar/Wind Helper
0.922
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
970831AG2-522 GEN
Solar/Wind Harmer
4.516
LAGNLTFEXP_LAGN->PJM
CLTF
12.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.435
TVALTFEXP_TVA->PJM
CLTF
6.314
CPLELTFEXP_CPLE->PJM
CLTF
16.95
CBM West 2LTFEXP_CBM-W2->PJM
CBM
65.721
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.411
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.636
MECLTFEXP_MEC->PJM
CLTF
5.976
SIGELTFEXP_SIGE->PJM
CLTF
0.183
NYPJM->LTFIMP_NY
CLTF
4.79
LGEELTFEXP_LGEE->PJM
CLTF
2.231
WECLTFEXP_WEC->PJM
CLTF
1.099

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.96 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6893.4
MW Contribution:40.7
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
31.958
3151031BRUNSWICKG2
50/50
3.587
3151101ELIZAR3
50/50
25.035
3147666LOUISA
Solar/Wind Harmer
-0.108
316313AB2-026
Solar/Wind Harmer
0.798
316258AE1-075 C
Solar/Wind Harmer
0.719
316405AF2-144 C
Solar/Wind Harmer
0.758
3143336POWHATN
Solar/Wind Harmer
2.986
970917AG2-570 GEN
Solar/Wind Harmer
73.668
315773AC2-141 GEN
Solar/Wind Harmer
12.096
944581AF1-123 GEN
Solar/Wind Harmer
130.69
944601AF1-125 GEN
Solar/Wind Harmer
128.65
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.028
971153AH1-033 GEN
Solar/Wind Harmer
3.459
3144536CHRHLND
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
17.615
316083AB2-161 GEN
Solar/Wind Harmer
4.573
970659AG2-427 GEN
Solar/Wind Harmer
2.653
970661AG2-428 GEN
Solar/Wind Harmer
5.305
316320Y1-086
Solar/Wind Harmer
1.65
3150861SPRUNCD
Adder
1.15
316435W1029_GEN3
Solar/Wind Harmer
5.059
3146516WINFALL
Solar/Wind Harmer
-0.028
3145336SMITFLD
Solar/Wind Harmer
-0.011
315839AE2-212 C
Solar/Wind Harmer
0.839
3146626S HERTFORD
Solar/Wind Harmer
-0.028
3145273HOLLAND
Solar/Wind Harmer
-0.021
965281AG1-393 GEN
Solar/Wind Harmer
3.435
3151221GRAVEL6
Adder
17.751
3151171GRAVELC
Adder
3.415
3146376EDENTON
Solar/Wind Harmer
-0.027
961611AG1-000B GEN
Solar/Wind Harmer
5.745
316365GEN2_N
Solar/Wind Harmer
1.828
316478AD1-087 GEN
Solar/Wind Harmer
2.335
316486AD2-202 GEN
Solar/Wind Harmer
0.684
315778AD1-151 GEN
Solar/Wind Harmer
23.348
315614AA2-178 GEN
Solar/Wind Harmer
2.901
970129AG2-093 GEN
Solar/Wind Harmer
15.087
3156081AA2-088 GEN
Solar/Wind Harmer
8.655
3151761LOISA E
Adder
31.328
970133AG2-095 GEN
Solar/Wind Harmer
2.99
966621AG1-532 GEN
Solar/Wind Harmer
0.539
3144216WINCHST
Adder
0.891
971157AH1-035 GEN
Solar/Wind Harmer
3.319
315737AD1-076 GEN
Solar/Wind Harmer
5.035
3150921YORKTN3
Adder
5.907
3145893MURPHYS
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.026
957521AF2-046 GEN
Solar/Wind Harmer
20.741
961681AG1-008 GEN
Solar/Wind Harmer
20.741
3146206CASHIE
Solar/Wind Harmer
-0.026
313506AB2-031 GEN
Solar/Wind Harmer
2.107
3146173TUNIS
Solar/Wind Harmer
-0.026
316463AE2-346 GEN
Solar/Wind Harmer
0.422
316140AB2-099
Solar/Wind Harmer
0.176
962331AG1-082 GEN
Solar/Wind Harmer
3.26
3156021HOLLOMANSOL
Solar/Wind Harmer
3.513
3147043LAWRENC
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3146263WOODLND
Solar/Wind Harmer
-0.026
970909AG2-566 GEN
Solar/Wind Harmer
2.462
3143096IRON208
Adder
0.962
3143096IRON208
Adder
0.943
316317KELFORD C
Solar/Wind Harmer
1.207
3145823KELFORD
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.026
972183AH1-676 GEN
Adder
243.274
316382AG1-145 C
Solar/Wind Harmer
0.77
3145963POPLR C
Solar/Wind Harmer
-0.025
3142946ENON
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
3.914
316131AB2-060 GEN
Solar/Wind Harmer
2.677
964241AG1-285 GEN
Solar/Wind Harmer
19.386
315785AD2-033 C
Solar/Wind Harmer
5.622
970257AG2-171 GEN
Solar/Wind Harmer
9.302
959311AF2-222 GEN
Solar/Wind Harmer
25.891
3144293JTRSVLE
Adder
0.703
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
3141843SHACKLE
Adder
1.042
3150351NORNECKC2
Adder
1.625
972255AH1-712 GEN
Adder
63.154
316044AC1-158 PL1
Solar/Wind Helper
3.502
316450AC1-158 RIC
Solar/Wind Helper
0.934
3141196NOKESVL
Solar/Wind Helper
1.078
227287AC2-120 GEN
Solar/Wind Helper
0.305
226910AB2-157 C
Solar/Wind Helper
0.012
3152251N ANNA1
50/50
31.961
970119AG2-088 GEN
50/50
40.696
315243AE2-183_GT3
50/50
4.555
3151051BRUNSWICKS1
50/50
7.445
3151021BRUNSWICKG1
50/50
3.587
971451AH1-221 GEN
50/50
10.895
3150981CHESPKA
50/50
3.363
3147666LOUISA
Solar/Wind Harmer
-0.188
316192AB2-158 GEN
Solar/Wind Harmer
5.479
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
30.211
3143526WINTERP
Solar/Wind Harmer
-0.162
939411AE1-173 GEN
Solar/Wind Harmer
156.554
3143336POWHATN
Solar/Wind Harmer
3.513
970919AG2-571 GEN
Solar/Wind Harmer
9.325
970087AG2-069 GEN
Solar/Wind Harmer
27.507
316294AC1-161 GEN
Solar/Wind Harmer
9.352
944591AF1-124 GEN
Solar/Wind Harmer
131.161
316375AC2-012 GEN
Solar/Wind Harmer
9.869
316388AE2-253 GEN
Solar/Wind Harmer
1.918
3146456SLIGO L269
Solar/Wind Harmer
-0.028
316336AC2-165 C
Solar/Wind Harmer
4.931
316246AF1-032 C
Solar/Wind Harmer
0.572
316381AD1-082 GEN
Solar/Wind Harmer
2.584
970659AG2-427 GEN
Solar/Wind Harmer
14.969
970661AG2-428 GEN
Solar/Wind Harmer
29.933
316093AE2-104_GEN
Solar/Wind Harmer
8.186
957481AF2-042 GEN
Solar/Wind Harmer
87.747
3150851SPRUNCC
Adder
1.15
316072AD1-144
Solar/Wind Harmer
0.567
3146516WINFALL
Solar/Wind Harmer
-0.09
3146516WINFALL
Solar/Wind Harmer
-0.028
3145336SMITFLD
Solar/Wind Harmer
-0.111
315800Z1-036_GEN1
Solar/Wind Harmer
6.81
315693AD1-088 GEN
Solar/Wind Harmer
13.752
3151171GRAVELC
Adder
2.597
962491AG1-098 GEN
Solar/Wind Harmer
18.339
3130156CHOWAN
Solar/Wind Harmer
-0.027
961611AG1-000B GEN
Solar/Wind Harmer
13.464
315671AE2-027_GEN
Solar/Wind Harmer
20.456
971647AH1-324 GEN
Solar/Wind Harmer
13.581
316023GEN1_S
Solar/Wind Harmer
1.828
971069AG2-661 GEN
Solar/Wind Harmer
4.264
3145663CRESWEL
Solar/Wind Harmer
-0.075
971163AH1-040 GEN
Solar/Wind Harmer
25.206
316458AB2-190 GEN2
Solar/Wind Harmer
2.713
970129AG2-093 GEN
Solar/Wind Harmer
6.111
3151751LOISA D
Adder
15.367
960081AF2-299 GEN
Solar/Wind Harmer
2.989
3138126ROCKLANDING
Solar/Wind Harmer
0.081
3142543TWELFTH
Solar/Wind Harmer
-0.003
3145893MURPHYS
Solar/Wind Harmer
-0.105
3145893MURPHYS
Solar/Wind Harmer
0.783
3146206CASHIE
Solar/Wind Harmer
-0.026
971547AH1-271 GEN
Solar/Wind Harmer
6.58
971795AH1-408 GEN
Solar/Wind Harmer
19.653
3146173TUNIS
Solar/Wind Harmer
-0.026
3147043LAWRENC
Adder
2.097
3145683EARLEYS
Solar/Wind Harmer
-0.026
316011AB1-132 GEN
Solar/Wind Harmer
5.429
962571AG1-106 GEN
Solar/Wind Harmer
3.73
3146263WOODLND
Solar/Wind Harmer
-0.026
316190AA2-174 GEN
Solar/Wind Harmer
0.317
3143096IRON208
Adder
0.962
971317AH1-138 GEN
Solar/Wind Harmer
3.222
3145783HORNRTN
Solar/Wind Harmer
-0.026
3145823KELFORD
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145796HORNRTN
Solar/Wind Harmer
-0.026
316159AE1-175 C
Solar/Wind Harmer
0.686
3145963POPLR C
Solar/Wind Harmer
-0.025
944631AF1-128 GEN
Adder
107.977
315687AD1-152 GEN
Solar/Wind Harmer
3.055
316174AB2-169 GEN
Solar/Wind Harmer
3.908
970937AG2-583 GEN
Solar/Wind Harmer
18.128
316129AC1-054 GEN
Solar/Wind Harmer
2.211
971065AG2-659 GEN
Solar/Wind Harmer
12.582
316212AC1-099_GEN
Solar/Wind Harmer
2.175
970685AG2-442 GEN
Solar/Wind Harmer
21.702
3144293JTRSVLE
Adder
0.703
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
3141843SHACKLE
Adder
1.042
3150351NORNECKC2
Adder
1.599
972277AH1-723 GEN
Adder
73.593
316045AC1-158 PL2
Solar/Wind Helper
11.209
971133AH1-012 GEN
50/50
8.834
970533AG2-339 GEN
50/50
25.186
970531AG2-338 GEN
50/50
10.074
315242AE2-183_GT2
50/50
4.555
315241AE2-183_GT1
50/50
4.527
972185AH1-677 GEN
50/50
16.42
3151041BRUNSWICKG3
50/50
3.587
972187AH1-678 GEN
50/50
8.232
3150991CHESPKB
50/50
2.821
3150991CHESPKB
50/50
2.753
971223AH1-071 GEN
Solar/Wind Harmer
4.287
3143526WINTERP
Solar/Wind Harmer
-0.162
970933AG2-581 GEN
Solar/Wind Harmer
28.21
3144356SAPONY
Solar/Wind Harmer
1.021
316185AD1-033 GEN
Solar/Wind Harmer
3.013
3142956BIRDNECK
Solar/Wind Harmer
1.531
316316AC1-027 C
Solar/Wind Harmer
0.876
316036AC1-147 C
Solar/Wind Harmer
0.769
3145506HICKORY
Solar/Wind Harmer
-0.113
3145506HICKORY
Solar/Wind Harmer
-0.068
3145506HICKORY
Solar/Wind Harmer
-0.017
316339AD2-160 GEN
Solar/Wind Harmer
1.918
316018AA1-139 ULT2
Solar/Wind Harmer
2.435
316017AA1-139 ULT1
Solar/Wind Harmer
2.3
3137176SLIGO L2192
Solar/Wind Harmer
-0.112
3146456SLIGO L269
Solar/Wind Harmer
3.351
3130086AYDLETT
Solar/Wind Harmer
-0.113
970657AG2-426 GEN
Solar/Wind Harmer
8.805
970657AG2-426 GEN
Solar/Wind Harmer
1.841
3146386ELIZ CT
Solar/Wind Harmer
-0.028
970099AG2-077 GEN
Solar/Wind Harmer
35.099
316431W1029_GEN1
Solar/Wind Harmer
5.059
316433W1029_GEN2
Solar/Wind Harmer
5.059
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
316236AE1-162_GEN
Solar/Wind Harmer
0.839
3146626S HERTFORD
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.028
315742AE1-103 GEN
Solar/Wind Harmer
2.873
3146376EDENTON
Solar/Wind Harmer
0.811
3146376EDENTON
Solar/Wind Harmer
0.811
316240AF1-291 C
Solar/Wind Harmer
0.819
316033AB2-134 GEN
Solar/Wind Harmer
8.722
315697AD1-025 GEN
Solar/Wind Harmer
5.47
944641AF1-129 GEN
Adder
114.368
3151731LOISA B
Adder
15.367
3151721LOISA A
Adder
15.287
3145893MURPHYS
Solar/Wind Harmer
0.736
3145893MURPHYS
Solar/Wind Harmer
-0.047
316065AD1-022 GEN
Solar/Wind Harmer
13.191
971741AH1-377 GEN
Solar/Wind Harmer
30.569
316181AB2-040 GEN
Solar/Wind Harmer
3.656
3146173TUNIS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
970301AG2-198 GEN
Solar/Wind Harmer
12.968
316426AA2-053 GEN
Solar/Wind Harmer
2.61
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
966811AG1-552 GEN
Solar/Wind Harmer
2.903
3145593CAROLNA
Solar/Wind Harmer
0.214
3145783HORNRTN
Solar/Wind Harmer
3.044
3145783HORNRTN
Solar/Wind Harmer
2.436
3145783HORNRTN
Solar/Wind Harmer
0.761
3145783HORNRTN
Solar/Wind Harmer
0.304
3145796HORNRTN
Solar/Wind Harmer
-0.076
3142946ENON
Solar/Wind Harmer
-0.003
939181AE1-148 GEN
Solar/Wind Harmer
13.998
316274AC1-208 GEN
Solar/Wind Harmer
2.681
313527AB2-043 GEN
Solar/Wind Harmer
4.032
316034AC1-036 C
Solar/Wind Harmer
0.46
970323AG2-213 GEN
Solar/Wind Harmer
12.403
971775AH1-396 GEN
Solar/Wind Harmer
1.766
3144293JTRSVLE
Adder
0.703
3144293JTRSVLE
Adder
0.592
3142366NRTHEST
Adder
0.712
3150691DARBY 3
Adder
15.594
3150701DARBY 4
Adder
15.558
3150681DARBY 2
Adder
15.54
3150671DARBY 1
Adder
15.522
3142296MT RD221
Adder
0.637
3150341NORNECKC1
Adder
1.679
3150341NORNECKC1
Adder
1.666
316447AC1-158 HLD
Solar/Wind Helper
7.707
226929AD2-058 GEN
Solar/Wind Helper
0.088
316303AF2-085
50/50
5.426
315244AE2-183_ST
50/50
7.875
963041AG1-153 GEN
50/50
7.263
315779AE2-040
50/50
3.636
3151081ELIZAR1
50/50
24.718
3151091ELIZAR2
50/50
24.289
941591AE2-156 GEN
50/50
22.58
3152611GOSPORTB
50/50
3.43
3152621GOSPORTC
50/50
2.911
3152601GOSPORTA
50/50
2.685
941031AE2-094 GEN
Solar/Wind Harmer
59.691
944011AF1-069 GEN
Solar/Wind Harmer
18.703
316233AE1-074 FULL
Solar/Wind Harmer
0.843
971281AH1-106 GEN
Solar/Wind Harmer
5.091
971283AH1-107 GEN
Solar/Wind Harmer
5.091
970673AG2-436 GEN
Solar/Wind Harmer
65.689
970673AG2-436 GEN
Solar/Wind Harmer
33.26
971967AH1-528 GEN
Solar/Wind Harmer
58.02
970085AG2-068 GEN
Solar/Wind Harmer
18.338
970581AG2-369 GEN
Solar/Wind Harmer
15.771
316315AB2-025 C
Solar/Wind Harmer
0.79
315814AE2-033 C
Solar/Wind Harmer
27.155
3143316POE
Solar/Wind Harmer
-0.114
957871AF2-081 GEN
Solar/Wind Harmer
14.21
319010AE1-072 C
Solar/Wind Harmer
5.736
3146406KITTY HAWK
Solar/Wind Harmer
0.024
316305AF2-043 C
Solar/Wind Harmer
0.853
315833AF1-017_GEN
Solar/Wind Harmer
5.349
316349AD2-085 GEN
Solar/Wind Harmer
2.505
316311AC2-079 GEN
Solar/Wind Harmer
14.204
313526AB2-022
Solar/Wind Harmer
0.759
315835AF2-110_GEN
Solar/Wind Harmer
3.519
3146486SUNBURY
Solar/Wind Harmer
-0.028
3146486SUNBURY
Solar/Wind Harmer
-0.028
316321Z2-027
Solar/Wind Harmer
0.757
3146396TANGLEW
Solar/Wind Harmer
0.516
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971285AH1-108 GEN
Adder
1.882
971445AH1-216 GEN
Solar/Wind Harmer
17.213
315611Z1-036_GEN2
Solar/Wind Harmer
6.81
972265AH1-717 GEN
Adder
18.958
3151201GRAVEL4
Adder
17.771
3151191GRAVEL3
Adder
17.547
3151211GRAVEL5
Adder
17.547
3130156CHOWAN
Solar/Wind Harmer
-0.027
3130156CHOWAN
Solar/Wind Harmer
-0.027
316369SG1_INVT
Solar/Wind Harmer
4.832
315816AE2-034 GEN
Solar/Wind Harmer
2.176
316132AB2-190 GEN1
Solar/Wind Harmer
2.713
965291AG1-394 GEN
Solar/Wind Harmer
2.36
946281AF1-292 GEN
Solar/Wind Harmer
0.595
3130546PLYMOUTH
Solar/Wind Harmer
-0.026
315732AD1-074 GEN1
Solar/Wind Harmer
5.358
315733AD1-074 GEN2
Solar/Wind Harmer
5.358
315735AD1-075 GEN1
Solar/Wind Harmer
2.68
316318V4-068
Solar/Wind Harmer
0.658
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
-0.026
3146206CASHIE
Solar/Wind Harmer
-0.026
970601AG2-382 GEN
Solar/Wind Harmer
11.515
316087AB2-174 GEN
Solar/Wind Harmer
3.755
3146043SEABORD
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
2.638
3145513AHOSKIE
Solar/Wind Harmer
0.227
961941AG1-037 GEN
Solar/Wind Harmer
0.196
3145513AHOSKIE
Solar/Wind Harmer
-0.026
3137643SOCKMAN
Solar/Wind Harmer
-0.103
3145683EARLEYS
Solar/Wind Harmer
-0.052
3145683EARLEYS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
315652AC1-086 GEN
Solar/Wind Harmer
29.194
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.01
970831AG2-522 GEN
Solar/Wind Harmer
12.637
3146033SCOT NK
Solar/Wind Harmer
-0.1
971443AH1-215 GEN
Solar/Wind Harmer
4.884
3144303KENBRDG
Solar/Wind Harmer
-0.02
3147346CASHSCORNER
Solar/Wind Harmer
0.384
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
972205AH1-687 GEN
Adder
8.575
972189AH1-679 GEN
Adder
2.228
972193AH1-681 GEN
Adder
2.822
316411AF1-147_GEN1
Solar/Wind Helper
0.847
316415AF1-147_GEN2
Solar/Wind Helper
0.847
3138216PACIFIC
Solar/Wind Helper
0.041
316164AC1-076 GEN
Solar/Wind Helper
1.148
970683AG2-441 GEN
Solar/Wind Harmer
5.411
970681AG2-440 GEN
Solar/Wind Harmer
4.329
LAGNLTFEXP_LAGN->PJM
CLTF
9.821
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.397
TVALTFEXP_TVA->PJM
CLTF
4.963
CPLELTFEXP_CPLE->PJM
CLTF
13.878
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.117
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.809
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.931
MECLTFEXP_MEC->PJM
CLTF
4.554
SIGELTFEXP_SIGE->PJM
CLTF
0.138
NYPJM->LTFIMP_NY
CLTF
3.837
LGEELTFEXP_LGEE->PJM
CLTF
1.676
WECLTFEXP_WEC->PJM
CLTF
0.823

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:172.64 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5559.88
MW Contribution:35.42
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
5.491
944641AF1-129 GEN
50/50
122.767
970533AG2-339 GEN
50/50
21.564
970531AG2-338 GEN
50/50
8.626
3142366NRTHEST
50/50
0.836
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
971223AH1-071 GEN
Solar/Wind Harmer
2.834
3143526WINTERP
Solar/Wind Harmer
1.342
316240AF1-291 C
Solar/Wind Harmer
0.002
3150691DARBY 3
Adder
17.296
3150701DARBY 4
Adder
17.255
3150681DARBY 2
Adder
17.235
3150671DARBY 1
Adder
17.215
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.516
3150991CHESPKB
Adder
2.456
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.27
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.23
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.395
970657AG2-426 GEN
Solar/Wind Harmer
1.76
3142296MT RD221
Adder
0.763
3145506HICKORY
Solar/Wind Harmer
0.957
3145506HICKORY
Solar/Wind Harmer
0.574
3145506HICKORY
Solar/Wind Harmer
0.144
3142946ENON
Solar/Wind Harmer
0.024
316339AD2-160 GEN
Solar/Wind Harmer
0.387
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
3137176SLIGO L2192
Solar/Wind Harmer
0.946
3146456SLIGO L269
Solar/Wind Harmer
4.208
3130086AYDLETT
Solar/Wind Harmer
0.95
316075AC2-137 C
Solar/Wind Harmer
0.065
972185AH1-677 GEN
Adder
13.26
3144356SAPONY
Solar/Wind Harmer
1.973
3146386ELIZ CT
Solar/Wind Harmer
0.235
972187AH1-678 GEN
Adder
6.65
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
18.37
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.008
3146376EDENTON
Solar/Wind Harmer
1.008
957411AF2-035 GEN
Solar/Wind Harmer
9.597
970317AG2-208 GEN
Solar/Wind Harmer
8.892
315673AE1-157 GEN
Solar/Wind Harmer
15.364
3150391LDYSMT3
Adder
29.101
972195AH1-682 GEN
Adder
3.824
316065AD1-022 GEN
Solar/Wind Harmer
9.976
3145893MURPHYS
Solar/Wind Harmer
1.442
3145893MURPHYS
Solar/Wind Harmer
0.388
970099AG2-077 GEN
Solar/Wind Harmer
22.899
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.97
316181AB2-040 GEN
Solar/Wind Harmer
0.305
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.126
316426AA2-053 GEN
Solar/Wind Harmer
0.702
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
966811AG1-552 GEN
Solar/Wind Harmer
2.246
3145593CAROLNA
Solar/Wind Harmer
0.258
3145783HORNRTN
Solar/Wind Harmer
3.66
3145783HORNRTN
Solar/Wind Harmer
2.928
3145783HORNRTN
Solar/Wind Harmer
0.915
3145783HORNRTN
Solar/Wind Harmer
0.366
3145796HORNRTN
Solar/Wind Harmer
0.617
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.143
3150341NORNECKC1
Adder
2.126
971741AH1-377 GEN
Solar/Wind Harmer
19.869
3145933PARMELE
Solar/Wind Harmer
0.399
3145933PARMELE
Solar/Wind Harmer
0.2
316274AC1-208 GEN
Solar/Wind Harmer
1.034
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
970301AG2-198 GEN
Solar/Wind Harmer
8.419
939181AE1-148 GEN
Solar/Wind Harmer
9.29
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.155
971775AH1-396 GEN
Solar/Wind Harmer
0.306
3145493TOT1
Solar/Wind Harmer
0.441
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.282
963191AG1-168 GEN
Solar/Wind Harmer
0.761
3144293JTRSVLE
Adder
0.605
3144293JTRSVLE
Adder
0.51
3147133PAMPLIN
Solar/Wind Harmer
0.19
3147133PAMPLIN
Solar/Wind Harmer
0.152
961601AG1-000A GEN
Solar/Wind Harmer
3.325
316263AC1-034 GEN
Solar/Wind Harmer
7.104
962561AG1-105 GEN
Solar/Wind Harmer
8.835
964791AG1-342 GEN
Solar/Wind Harmer
3.505
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Harmer
0.661
971489AH1-241 GEN
Solar/Wind Harmer
8.416
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.289
3151731LOISA B
Adder
8.676
3151721LOISA A
Adder
8.631
316447AC1-158 HLD
Solar/Wind Helper
11.481
3152251N ANNA1
50/50
20.321
970119AG2-088 GEN
50/50
35.422
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.99
3150771HOPHCF1
50/50
0.977
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.342
3147666LOUISA
Solar/Wind Harmer
1.028
316192AB2-158 GEN
Solar/Wind Harmer
1.415
940641AE2-051 GEN
Solar/Wind Harmer
19.964
939411AE1-173 GEN
Solar/Wind Harmer
105.426
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.211
315671AE2-027_GEN
Solar/Wind Harmer
15.496
944591AF1-124 GEN
Solar/Wind Harmer
54.408
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
971069AG2-661 GEN
Solar/Wind Harmer
4.274
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3
970659AG2-427 GEN
Solar/Wind Harmer
11.613
971647AH1-324 GEN
Solar/Wind Harmer
10.242
3145336SMITFLD
Solar/Wind Harmer
0.959
316381AD1-082 GEN
Solar/Wind Harmer
0.25
944631AF1-128 GEN
Adder
114.357
961611AG1-000B GEN
Solar/Wind Harmer
12.579
3151171GRAVELC
Adder
2.549
970661AG2-428 GEN
Solar/Wind Harmer
23.801
316388AE2-253 GEN
Solar/Wind Harmer
0.747
3146456SLIGO L269
Solar/Wind Harmer
0.238
3142416OLDCHRC
Solar/Wind Harmer
0.618
3142416OLDCHRC
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.086
3138126ROCKLANDING
Solar/Wind Harmer
0.109
316246AF1-032 C
Solar/Wind Harmer
0.107
316159AE1-175 C
Solar/Wind Harmer
0.205
316093AE2-104_GEN
Solar/Wind Harmer
3.974
971317AH1-138 GEN
Solar/Wind Harmer
1.762
3146516WINFALL
Solar/Wind Harmer
0.754
3146516WINFALL
Solar/Wind Harmer
0.233
3142433PROV 92
Solar/Wind Harmer
0.928
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141843SHACKLE
Adder
1.16
3143336POWHATN
Solar/Wind Harmer
4.034
3130156CHOWAN
Solar/Wind Harmer
0.227
3141766HARMONY
Solar/Wind Harmer
0.045
970919AG2-571 GEN
Solar/Wind Harmer
8.004
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
17.934
3145663CRESWEL
Solar/Wind Harmer
0.622
971163AH1-040 GEN
Solar/Wind Harmer
17.772
3138133OCRAN
Solar/Wind Harmer
0.133
316023GEN1_S
Solar/Wind Harmer
0.489
972197AH1-683 GEN
Adder
4.553
972219AH1-694 GEN
Adder
3.278
316336AC2-165 C
Solar/Wind Harmer
0.008
3146206CASHIE
Solar/Wind Harmer
0.216
971547AH1-271 GEN
Solar/Wind Harmer
4.607
3145893MURPHYS
Solar/Wind Harmer
0.862
3145893MURPHYS
Solar/Wind Harmer
0.958
957481AF2-042 GEN
Solar/Wind Harmer
57.247
3146173TUNIS
Solar/Wind Harmer
0.213
960081AF2-299 GEN
Solar/Wind Harmer
2.041
962861AG1-135 GEN
Solar/Wind Harmer
6.774
3145683EARLEYS
Solar/Wind Harmer
0.211
3146263WOODLND
Solar/Wind Harmer
0.21
315693AD1-088 GEN
Solar/Wind Harmer
10.091
962491AG1-098 GEN
Solar/Wind Harmer
11.959
316011AB1-132 GEN
Solar/Wind Harmer
3.796
962571AG1-106 GEN
Solar/Wind Harmer
2.971
971795AH1-408 GEN
Solar/Wind Harmer
13.893
3145963POPLR C
Solar/Wind Harmer
0.208
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.208
3141726DUNNSVL
Solar/Wind Harmer
0.83
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3147043LAWRENC
Adder
1.868
3145783HORNRTN
Solar/Wind Harmer
0.206
3145796HORNRTN
Solar/Wind Harmer
0.678
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.04
316212AC1-099_GEN
Solar/Wind Harmer
1.038
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.434
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
315722AD1-056 GEN
Solar/Wind Harmer
1.237
316337AD2-073 GEN
Solar/Wind Harmer
0.169
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.651
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970937AG2-583 GEN
Solar/Wind Harmer
11.696
970685AG2-442 GEN
Solar/Wind Harmer
14.234
3146233WITAKRS
Solar/Wind Harmer
0.757
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.19
3145493TOT1
Solar/Wind Harmer
0.845
963171AG1-166 GEN
Solar/Wind Harmer
1.014
971563AH1-280 GEN
Solar/Wind Harmer
2.028
3144293JTRSVLE
Adder
0.605
3146926FARMVIL
Solar/Wind Harmer
0.113
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.672
316049AB1-081 GEN
Solar/Wind Harmer
1.07
3142053HEARTS
Solar/Wind Harmer
0.329
970401AG2-262 GEN
Solar/Wind Harmer
1.071
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.247
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.431
971377AH1-170 GEN
Solar/Wind Harmer
1.683
3147623JAMES R
Solar/Wind Harmer
0.366
972277AH1-723 GEN
Adder
87.353
3151751LOISA D
Adder
8.676
970223AG2-152 GEN
Solar/Wind Harmer
7.908
316045AC1-158 PL2
Solar/Wind Helper
16.699
316006AB2-029 C
Solar/Wind Helper
0.14
3152261N ANNA2
50/50
20.32
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.056
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151101ELIZAR3
50/50
23.68
3151161SURRY 1
50/50
9.205
3147666LOUISA
Solar/Wind Harmer
0.591
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.876
965281AG1-393 GEN
Solar/Wind Harmer
2.585
315813AE1-149 C
Solar/Wind Harmer
12.873
970133AG2-095 GEN
Solar/Wind Harmer
2.314
944581AF1-123 GEN
Solar/Wind Harmer
54.216
944601AF1-125 GEN
Solar/Wind Harmer
53.381
970129AG2-093 GEN
Solar/Wind Harmer
14.547
315778AD1-151 GEN
Solar/Wind Harmer
19.233
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.54
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
961611AG1-000B GEN
Solar/Wind Harmer
6.396
3151221GRAVEL6
Adder
17.422
3151171GRAVELC
Adder
3.352
970661AG2-428 GEN
Solar/Wind Harmer
5.062
970293AG2-193 GEN
Solar/Wind Harmer
2.548
3142946ENON
Solar/Wind Harmer
0.08
3146456SLIGO L269
Solar/Wind Harmer
0.238
971153AH1-033 GEN
Solar/Wind Harmer
2.749
3142416OLDCHRC
Solar/Wind Harmer
2.305
3144216WINCHST
Adder
0.896
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.233
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316473AC1-191 GEN
Solar/Wind Harmer
0.778
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.143
316258AE1-075 C
Solar/Wind Harmer
0.171
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.429
3146376EDENTON
Solar/Wind Harmer
0.227
3141766HARMONY
Solar/Wind Harmer
3.024
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
4.011
970917AG2-570 GEN
Solar/Wind Harmer
20.009
315614AA2-178 GEN
Solar/Wind Harmer
1.271
971157AH1-035 GEN
Solar/Wind Harmer
2.623
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.489
315737AD1-076 GEN
Solar/Wind Harmer
2.804
3150401LDYSMT4
Adder
29.156
3150371LDYSMT1
Adder
28.172
962971AG1-146 GEN
Solar/Wind Harmer
3.461
3146206CASHIE
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
0.361
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.996
961681AG1-008 GEN
Solar/Wind Harmer
15.996
970009AG2-005 GEN
Solar/Wind Harmer
1.599
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.967
316463AE2-346 GEN
Solar/Wind Harmer
0.183
316140AB2-099
Solar/Wind Harmer
0.076
962331AG1-082 GEN
Solar/Wind Harmer
2.268
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.21
313506AB2-031 GEN
Solar/Wind Harmer
0.649
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145963POPLR C
Solar/Wind Harmer
0.208
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
316478AD1-087 GEN
Solar/Wind Harmer
0.721
316486AD2-202 GEN
Solar/Wind Harmer
0.212
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.822
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.861
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.326
971781AH1-399 GEN
Solar/Wind Harmer
0.26
970909AG2-566 GEN
Solar/Wind Harmer
2.105
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
315724AD1-057 GEN
Solar/Wind Harmer
0.733
316327AA2-057 GEN
Solar/Wind Harmer
0.292
316131AB2-060 GEN
Solar/Wind Harmer
0.604
964241AG1-285 GEN
Solar/Wind Harmer
12.793
315785AD2-033 C
Solar/Wind Harmer
1.556
970257AG2-171 GEN
Solar/Wind Harmer
6.117
959311AF2-222 GEN
Solar/Wind Harmer
16.978
3146233WITAKRS
Solar/Wind Harmer
0.955
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.19
3146083TARBORO
Solar/Wind Harmer
0.19
963181AG1-167 GEN
Solar/Wind Harmer
0.761
3144293JTRSVLE
Adder
0.605
3138543CONSLDL
Solar/Wind Harmer
0.125
3147133PAMPLIN
Solar/Wind Harmer
0.596
971193AH1-056 GEN
Solar/Wind Harmer
11.558
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.113
961601AG1-000A GEN
Solar/Wind Harmer
13.299
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.187
971623AH1-311 GEN
Solar/Wind Harmer
0.374
3141906WESTMOR
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.064
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.491
970737AG2-469 GEN
Solar/Wind Harmer
7.435
971683AH1-343 GEN
Solar/Wind Harmer
5.965
316283AC2-100 C
Solar/Wind Harmer
0.31
970221AG2-151 GEN
Solar/Wind Harmer
8.416
972255AH1-712 GEN
Adder
74.962
3151761LOISA E
Adder
17.688
972183AH1-676 GEN
Adder
136.298
3141316ARNOLDS
Adder
0.29
316044AC1-158 PL1
Solar/Wind Helper
5.216
316450AC1-158 RIC
Solar/Wind Helper
1.391
3141196NOKESVL
Solar/Wind Helper
1.131
316303AF2-085
50/50
4.723
971285AH1-108 GEN
50/50
1.99
970603AG2-384 GEN
50/50
5.178
972263AH1-716 GEN
50/50
139.063
316233AE1-074 FULL
Solar/Wind Harmer
0.207
971281AH1-106 GEN
Solar/Wind Harmer
3.58
971283AH1-107 GEN
Solar/Wind Harmer
3.58
3143316POE
Solar/Wind Harmer
0.964
941031AE2-094 GEN
Solar/Wind Harmer
44.68
944011AF1-069 GEN
Solar/Wind Harmer
14.599
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
3151081ELIZAR1
Adder
22.034
3151091ELIZAR2
Adder
21.652
3152611GOSPORTB
Adder
3.059
3152621GOSPORTC
Adder
2.596
3152601GOSPORTA
Adder
2.395
316369SG1_INVT
Solar/Wind Harmer
0.009
971445AH1-216 GEN
Solar/Wind Harmer
16.89
972265AH1-717 GEN
Adder
18.606
3151201GRAVEL4
Adder
17.442
3151191GRAVEL3
Adder
17.221
3151211GRAVEL5
Adder
17.221
970673AG2-436 GEN
Solar/Wind Harmer
50.858
970673AG2-436 GEN
Solar/Wind Harmer
33.905
957871AF2-081 GEN
Solar/Wind Harmer
11.862
316312AB1-027
Solar/Wind Harmer
0.425
319010AE1-072 C
Solar/Wind Harmer
1.197
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
316311AC2-079 GEN
Solar/Wind Harmer
6.823
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.621
316315AB2-025 C
Solar/Wind Harmer
0.191
315976AC1-164 GENA
Solar/Wind Harmer
24.444
316169AC1-164_GENC
Solar/Wind Harmer
21.117
315975AC1-164 GENB
Solar/Wind Harmer
0.723
313526AB2-022
Solar/Wind Harmer
0.128
971967AH1-528 GEN
Solar/Wind Harmer
37.658
315814AE2-033 C
Solar/Wind Harmer
18.587
3146486SUNBURY
Solar/Wind Harmer
0.235
3146486SUNBURY
Solar/Wind Harmer
0.235
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.646
3145176PASQUOTANK
Solar/Wind Harmer
0.145
972189AH1-679 GEN
Adder
3.913
971167AH1-042 GEN
Solar/Wind Harmer
20.686
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3138283WHITEMARSH
Solar/Wind Harmer
0.054
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3143873LANEXA
Solar/Wind Harmer
0.137
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.729
3130156CHOWAN
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
970085AG2-068 GEN
Solar/Wind Harmer
11.956
970581AG2-369 GEN
Solar/Wind Harmer
10.282
3141913WHIT STONE
Solar/Wind Harmer
0.222
315816AE2-034 GEN
Solar/Wind Harmer
0.953
3138133OCRAN
Solar/Wind Harmer
0.066
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.252
315733AD1-074 GEN2
Solar/Wind Harmer
1.252
315735AD1-075 GEN1
Solar/Wind Harmer
0.627
965291AG1-394 GEN
Solar/Wind Harmer
0.966
3150411LDYSMT5
Adder
29.247
3150381LDYSMT2
Adder
27.99
972213AH1-691 GEN
Adder
4.735
972215AH1-692 GEN
Adder
4.735
962981AG1-147 GEN
Solar/Wind Harmer
8.075
3146206CASHIE
Solar/Wind Harmer
0.216
970601AG2-382 GEN
Solar/Wind Harmer
8.061
3145893MURPHYS
Solar/Wind Harmer
0.582
3145893MURPHYS
Solar/Wind Harmer
0.215
970327AG2-215 GEN
Solar/Wind Harmer
7.029
3145513AHOSKIE
Solar/Wind Harmer
0.444
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.212
3145683EARLEYS
Solar/Wind Harmer
0.423
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.431
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.967
3137643SOCKMAN
Solar/Wind Harmer
0.832
3145796HORNRTN
Solar/Wind Harmer
0.658
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
0.815
970831AG2-522 GEN
Solar/Wind Harmer
8.503
316005AA1-067
Solar/Wind Harmer
0.21
3145746EVERETS
Solar/Wind Harmer
0.779
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
970181AG2-120 GEN
Solar/Wind Harmer
2.436
957861AF2-080 GEN
Solar/Wind Harmer
8.31
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.006
971443AH1-215 GEN
Solar/Wind Harmer
3.212
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
12.709
970681AG2-440 GEN
Solar/Wind Harmer
10.167
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.19
3145573BETHELC
Solar/Wind Harmer
0.19
946301AF1-294 GEN
Solar/Wind Harmer
3.752
961791AG1-021 GEN
Solar/Wind Harmer
1.825
315657AE1-056 GEN
Solar/Wind Harmer
6.547
316223AC1-118
Solar/Wind Harmer
0.132
970285AG2-188 GEN
Solar/Wind Harmer
14.341
971845AH1-439 GEN
Solar/Wind Harmer
8.154
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.204
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
5.394
971447AH1-217 GEN
Solar/Wind Harmer
4.654
972193AH1-681 GEN
Adder
3.349
316123AC1-075 GEN
Solar/Wind Harmer
0.195
970165AG2-112 GEN
Solar/Wind Harmer
1.154
970163AG2-111 GEN
Solar/Wind Harmer
1.101
270494AE1-108_GEN
Solar/Wind Harmer
1.672
3147346CASHSCORNER
Solar/Wind Harmer
0.293
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.38
316411AF1-147_GEN1
Solar/Wind Helper
0.79
316415AF1-147_GEN2
Solar/Wind Helper
0.79
3138216PACIFIC
Solar/Wind Helper
0.038
LAGNLTFEXP_LAGN->PJM
CLTF
8.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.505
TVALTFEXP_TVA->PJM
CLTF
4.252
CPLELTFEXP_CPLE->PJM
CLTF
12.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.163
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.441
MECLTFEXP_MEC->PJM
CLTF
3.751
SIGELTFEXP_SIGE->PJM
CLTF
0.114
NYPJM->LTFIMP_NY
CLTF
3.266
LGEELTFEXP_LGEE->PJM
CLTF
1.371
WECLTFEXP_WEC->PJM
CLTF
0.662

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.66 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5528.27
MW Contribution:35.93
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
5.467
944641AF1-129 GEN
50/50
125.042
3142366NRTHEST
50/50
0.853
970533AG2-339 GEN
50/50
21.877
970531AG2-338 GEN
50/50
8.751
3150781HOPHCF2
50/50
0.996
3150791HOPHCF3
50/50
0.996
3150761HOPPOLC
50/50
0.631
971213AH1-066 GEN
50/50
0.873
3150691DARBY 3
50/50
18.729
3150701DARBY 4
50/50
18.685
971223AH1-071 GEN
Solar/Wind Harmer
2.875
3143526WINTERP
Solar/Wind Harmer
1.363
316240AF1-291 C
Solar/Wind Harmer
0.002
3150681DARBY 2
Adder
17.588
3150671DARBY 1
Adder
17.568
3142296MT RD221
Adder
0.779
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.275
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.56
3150991CHESPKB
Adder
2.499
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.234
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.541
970657AG2-426 GEN
Solar/Wind Harmer
1.79
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.973
3145506HICKORY
Solar/Wind Harmer
0.584
3145506HICKORY
Solar/Wind Harmer
0.146
316339AD2-160 GEN
Solar/Wind Harmer
0.393
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.135
316075AC2-137 C
Solar/Wind Harmer
0.066
3137176SLIGO L2192
Solar/Wind Harmer
0.963
3146456SLIGO L269
Solar/Wind Harmer
4.28
3130086AYDLETT
Solar/Wind Harmer
0.966
972185AH1-677 GEN
Adder
13.452
3144356SAPONY
Solar/Wind Harmer
2.004
3146386ELIZ CT
Solar/Wind Harmer
0.239
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.746
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
966871AG1-558 GEN
Solar/Wind Harmer
0.272
3146626S HERTFORD
Solar/Wind Harmer
0.235
3146626S HERTFORD
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
18.633
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.864
970317AG2-208 GEN
Solar/Wind Harmer
9.139
3146376EDENTON
Solar/Wind Harmer
1.025
3146376EDENTON
Solar/Wind Harmer
1.025
315673AE1-157 GEN
Solar/Wind Harmer
15.809
3150391LDYSMT3
Adder
30.003
972195AH1-682 GEN
Adder
3.943
316065AD1-022 GEN
Solar/Wind Harmer
10.141
3145893MURPHYS
Solar/Wind Harmer
1.466
3145893MURPHYS
Solar/Wind Harmer
0.394
970099AG2-077 GEN
Solar/Wind Harmer
23.222
3146173TUNIS
Solar/Wind Harmer
0.217
3146173TUNIS
Solar/Wind Harmer
0.217
958261AF2-120 GEN
Solar/Wind Harmer
7.118
316181AB2-040 GEN
Solar/Wind Harmer
0.309
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
316426AA2-053 GEN
Solar/Wind Harmer
0.713
3145593CAROLNA
Solar/Wind Harmer
0.21
3145593CAROLNA
Solar/Wind Harmer
0.21
966811AG1-552 GEN
Solar/Wind Harmer
2.282
3145593CAROLNA
Solar/Wind Harmer
0.262
3145783HORNRTN
Solar/Wind Harmer
3.718
3145783HORNRTN
Solar/Wind Harmer
2.974
3145783HORNRTN
Solar/Wind Harmer
0.93
3145783HORNRTN
Solar/Wind Harmer
0.372
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.19
3150341NORNECKC1
Adder
2.172
3145796HORNRTN
Solar/Wind Harmer
0.626
3145933PARMELE
Solar/Wind Harmer
0.406
3145933PARMELE
Solar/Wind Harmer
0.203
971741AH1-377 GEN
Solar/Wind Harmer
20.122
316274AC1-208 GEN
Solar/Wind Harmer
1.051
316468AD1-105 GEN
Solar/Wind Harmer
-0.066
970301AG2-198 GEN
Solar/Wind Harmer
8.524
939181AE1-148 GEN
Solar/Wind Harmer
9.423
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.264
971775AH1-396 GEN
Solar/Wind Harmer
0.31
3145493TOT1
Solar/Wind Harmer
0.448
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.179
958211AF2-115 GEN
Solar/Wind Harmer
2.311
963191AG1-168 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.154
961601AG1-000A GEN
Solar/Wind Harmer
3.377
316263AC1-034 GEN
Solar/Wind Harmer
7.215
962561AG1-105 GEN
Solar/Wind Harmer
8.959
964791AG1-342 GEN
Solar/Wind Harmer
3.555
3146843MT LREL
Solar/Wind Harmer
0.185
3146843MT LREL
Solar/Wind Harmer
0.185
3146776BUCKING
Solar/Wind Harmer
0.723
3146776BUCKING
Solar/Wind Harmer
0.059
316222AC1-221 GEN
Solar/Wind Harmer
0.67
971489AH1-241 GEN
Solar/Wind Harmer
8.483
942751AE2-291 GEN
Solar/Wind Harmer
7.393
315821AE2-092 GEN
Solar/Wind Harmer
0.008
3151731LOISA B
Adder
8.255
3151721LOISA A
Adder
8.212
316447AC1-158 HLD
Solar/Wind Helper
11.564
315651AD1-115 GEN
Solar/Wind Helper
1.026
3152251N ANNA1
50/50
20.435
970119AG2-088 GEN
50/50
35.934
3150851SPRUNCC
50/50
1.238
3143096IRON208
50/50
1.099
3152331SURRY 2
50/50
10.173
3150771HOPHCF1
50/50
0.996
3143226MDLTHAN
Solar/Wind Harmer
0.269
3143526WINTERP
Solar/Wind Harmer
1.363
3147666LOUISA
Solar/Wind Harmer
1.017
940641AE2-051 GEN
Solar/Wind Harmer
20.264
939411AE1-173 GEN
Solar/Wind Harmer
107.071
3142543TWELFTH
Solar/Wind Harmer
0.024
316192AB2-158 GEN
Solar/Wind Harmer
1.397
316294AC1-161 GEN
Solar/Wind Harmer
4.284
315671AE2-027_GEN
Solar/Wind Harmer
15.779
970129AG2-093 GEN
Solar/Wind Harmer
6.973
316458AB2-190 GEN2
Solar/Wind Harmer
1.315
944591AF1-124 GEN
Solar/Wind Harmer
55.346
971069AG2-661 GEN
Solar/Wind Harmer
4.353
944631AF1-128 GEN
Adder
116.602
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3.052
971647AH1-324 GEN
Solar/Wind Harmer
10.43
970659AG2-427 GEN
Solar/Wind Harmer
11.815
3145336SMITFLD
Solar/Wind Harmer
0.976
961611AG1-000B GEN
Solar/Wind Harmer
12.808
316381AD1-082 GEN
Solar/Wind Harmer
0.254
3151171GRAVELC
Adder
2.595
970661AG2-428 GEN
Solar/Wind Harmer
24.214
3142416OLDCHRC
Solar/Wind Harmer
0.631
3142416OLDCHRC
Solar/Wind Harmer
0.242
316388AE2-253 GEN
Solar/Wind Harmer
0.76
3138126ROCKLANDING
Solar/Wind Harmer
0.111
3146456SLIGO L269
Solar/Wind Harmer
0.242
316072AD1-144
Solar/Wind Harmer
0.088
316159AE1-175 C
Solar/Wind Harmer
0.209
316246AF1-032 C
Solar/Wind Harmer
0.109
971317AH1-138 GEN
Solar/Wind Harmer
1.796
316093AE2-104_GEN
Solar/Wind Harmer
4.042
3142433PROV 92
Solar/Wind Harmer
0.947
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.766
3146516WINFALL
Solar/Wind Harmer
0.236
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
971777AH1-397 GEN
Solar/Wind Harmer
0.612
3141843SHACKLE
Adder
1.184
3141766HARMONY
Solar/Wind Harmer
0.046
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3130156CHOWAN
Solar/Wind Harmer
0.23
3143336POWHATN
Solar/Wind Harmer
4.084
970919AG2-571 GEN
Solar/Wind Harmer
8.12
970087AG2-069 GEN
Solar/Wind Harmer
18.195
3138133OCRAN
Solar/Wind Harmer
0.136
3145663CRESWEL
Solar/Wind Harmer
0.632
971163AH1-040 GEN
Solar/Wind Harmer
18.07
972197AH1-683 GEN
Adder
4.694
972219AH1-694 GEN
Adder
3.38
316023GEN1_S
Solar/Wind Harmer
0.497
3146206CASHIE
Solar/Wind Harmer
0.219
971547AH1-271 GEN
Solar/Wind Harmer
4.683
316336AC2-165 C
Solar/Wind Harmer
0.009
3145893MURPHYS
Solar/Wind Harmer
0.876
3145893MURPHYS
Solar/Wind Harmer
0.974
957481AF2-042 GEN
Solar/Wind Harmer
58.056
3146173TUNIS
Solar/Wind Harmer
0.217
962861AG1-135 GEN
Solar/Wind Harmer
6.917
960081AF2-299 GEN
Solar/Wind Harmer
2.073
3145683EARLEYS
Solar/Wind Harmer
0.215
3146263WOODLND
Solar/Wind Harmer
0.214
315693AD1-088 GEN
Solar/Wind Harmer
10.231
962491AG1-098 GEN
Solar/Wind Harmer
12.124
316011AB1-132 GEN
Solar/Wind Harmer
3.856
962571AG1-106 GEN
Solar/Wind Harmer
3.018
3141726DUNNSVL
Solar/Wind Harmer
0.847
3145963POPLR C
Solar/Wind Harmer
0.211
971795AH1-408 GEN
Solar/Wind Harmer
14.105
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.211
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3147043LAWRENC
Adder
1.896
3145783HORNRTN
Solar/Wind Harmer
0.209
3150351NORNECKC2
Adder
2.084
3145796HORNRTN
Solar/Wind Harmer
0.689
3145796HORNRTN
Solar/Wind Harmer
0.209
316212AC1-099_GEN
Solar/Wind Harmer
1.054
3146293MARTNCO
Solar/Wind Harmer
0.188
316129AC1-054 GEN
Solar/Wind Harmer
0.758
971065AG2-659 GEN
Solar/Wind Harmer
8.56
316337AD2-073 GEN
Solar/Wind Harmer
0.173
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
315722AD1-056 GEN
Solar/Wind Harmer
1.256
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.661
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
0.769
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.193
3145493TOT1
Solar/Wind Harmer
0.859
970685AG2-442 GEN
Solar/Wind Harmer
14.419
970937AG2-583 GEN
Solar/Wind Harmer
11.813
963171AG1-166 GEN
Solar/Wind Harmer
1.027
971563AH1-280 GEN
Solar/Wind Harmer
2.054
3144293JTRSVLE
Adder
0.613
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.152
316359AB2-059 GEN
Solar/Wind Harmer
0.682
316049AB1-081 GEN
Solar/Wind Harmer
1.086
3142053HEARTS
Solar/Wind Harmer
0.334
970401AG2-262 GEN
Solar/Wind Harmer
1.086
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.307
972135AH1-637 GEN
Solar/Wind Harmer
1.466
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971377AH1-170 GEN
Solar/Wind Harmer
1.697
3147623JAMES R
Solar/Wind Harmer
0.369
972277AH1-723 GEN
Adder
89.316
3151751LOISA D
Adder
8.255
970223AG2-152 GEN
Solar/Wind Harmer
8.023
316045AC1-158 PL2
Solar/Wind Helper
16.818
316006AB2-029 C
Solar/Wind Helper
0.152
316254AC1-120 GEN1
Solar/Wind Helper
1.388
3152261N ANNA2
50/50
20.433
3150861SPRUNCD
50/50
1.238
3143096IRON208
50/50
1.099
3143096IRON208
50/50
1.077
3150801HOPHCF4
50/50
1.448
971211AH1-065 GEN
50/50
1.746
3151161SURRY 1
50/50
9.371
3147666LOUISA
Solar/Wind Harmer
0.585
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
9.03
965281AG1-393 GEN
Solar/Wind Harmer
2.631
315813AE1-149 C
Solar/Wind Harmer
13.098
970133AG2-095 GEN
Solar/Wind Harmer
2.358
970129AG2-093 GEN
Solar/Wind Harmer
14.818
944581AF1-123 GEN
Solar/Wind Harmer
55.15
944601AF1-125 GEN
Solar/Wind Harmer
54.301
315778AD1-151 GEN
Solar/Wind Harmer
19.588
3151101ELIZAR3
Adder
22.703
3144536CHRHLND
Solar/Wind Harmer
0.037
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.585
3145336SMITFLD
Solar/Wind Harmer
0.098
961611AG1-000B GEN
Solar/Wind Harmer
6.513
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.737
3151171GRAVELC
Adder
3.413
970293AG2-193 GEN
Solar/Wind Harmer
2.6
3142946ENON
Solar/Wind Harmer
0.081
970661AG2-428 GEN
Solar/Wind Harmer
5.15
3142416OLDCHRC
Solar/Wind Harmer
2.354
3144216WINCHST
Adder
0.913
3146456SLIGO L269
Solar/Wind Harmer
0.242
971153AH1-033 GEN
Solar/Wind Harmer
2.796
3150921YORKTN3
Adder
6.079
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.236
316473AC1-191 GEN
Solar/Wind Harmer
0.795
3146626S HERTFORD
Solar/Wind Harmer
0.235
3145273HOLLAND
Solar/Wind Harmer
0.176
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
3.085
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.23
316156AD2-030 GEN
Solar/Wind Harmer
0.17
3141873WAN 176
Solar/Wind Harmer
4.092
316313AB2-026
Solar/Wind Harmer
0.145
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.472
970917AG2-570 GEN
Solar/Wind Harmer
20.3
315614AA2-178 GEN
Solar/Wind Harmer
1.293
3150401LDYSMT4
Adder
30.059
3150371LDYSMT1
Adder
29.045
971157AH1-035 GEN
Solar/Wind Harmer
2.667
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315737AD1-076 GEN
Solar/Wind Harmer
2.851
316365GEN2_N
Solar/Wind Harmer
0.497
962971AG1-146 GEN
Solar/Wind Harmer
3.533
3146206CASHIE
Solar/Wind Harmer
0.219
3145893MURPHYS
Solar/Wind Harmer
0.367
3145893MURPHYS
Solar/Wind Harmer
0.219
970009AG2-005 GEN
Solar/Wind Harmer
1.633
957521AF2-046 GEN
Solar/Wind Harmer
16.257
961681AG1-008 GEN
Solar/Wind Harmer
16.257
3146173TUNIS
Solar/Wind Harmer
0.217
3156021HOLLOMANSOL
Solar/Wind Harmer
0.983
316463AE2-346 GEN
Solar/Wind Harmer
0.186
316140AB2-099
Solar/Wind Harmer
0.077
962331AG1-082 GEN
Solar/Wind Harmer
2.305
316404AE1-155 C
Solar/Wind Harmer
0.048
3146263WOODLND
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.659
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3145963POPLR C
Solar/Wind Harmer
0.211
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Harmer
0.731
316486AD2-202 GEN
Solar/Wind Harmer
0.215
3150351NORNECKC2
Adder
2.12
3145796HORNRTN
Solar/Wind Harmer
0.835
3145796HORNRTN
Solar/Wind Harmer
0.209
316210AC1-098 GEN
Solar/Wind Harmer
1.891
3145933PARMELE
Solar/Wind Harmer
0.203
966801AG1-551 GEN
Solar/Wind Harmer
2.363
971781AH1-399 GEN
Solar/Wind Harmer
0.266
970909AG2-566 GEN
Solar/Wind Harmer
2.131
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
315724AD1-057 GEN
Solar/Wind Harmer
0.745
316327AA2-057 GEN
Solar/Wind Harmer
0.297
316131AB2-060 GEN
Solar/Wind Harmer
0.613
964241AG1-285 GEN
Solar/Wind Harmer
12.969
315785AD2-033 C
Solar/Wind Harmer
1.576
970257AG2-171 GEN
Solar/Wind Harmer
6.198
959311AF2-222 GEN
Solar/Wind Harmer
17.202
3146233WITAKRS
Solar/Wind Harmer
0.97
3146233WITAKRS
Solar/Wind Harmer
0.131
3146073TAR RVR
Solar/Wind Harmer
0.193
3146083TARBORO
Solar/Wind Harmer
0.193
3138543CONSLDL
Solar/Wind Harmer
0.127
963181AG1-167 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.613
3147133PAMPLIN
Solar/Wind Harmer
0.603
971193AH1-056 GEN
Solar/Wind Harmer
11.702
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
13.507
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.19
971623AH1-311 GEN
Solar/Wind Harmer
0.38
3141906WESTMOR
Solar/Wind Harmer
0.075
3146776BUCKING
Solar/Wind Harmer
0.065
970737AG2-469 GEN
Solar/Wind Harmer
7.61
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.598
971683AH1-343 GEN
Solar/Wind Harmer
6.05
316283AC2-100 C
Solar/Wind Harmer
0.314
970221AG2-151 GEN
Solar/Wind Harmer
8.483
972255AH1-712 GEN
Adder
76.646
3151761LOISA E
Adder
16.829
3141316ARNOLDS
Adder
0.299
972183AH1-676 GEN
Adder
129.168
3150331BIRCHWDA
Adder
19.249
316044AC1-158 PL1
Solar/Wind Helper
5.254
316450AC1-158 RIC
Solar/Wind Helper
1.401
316170AC1-121 GEN2
Solar/Wind Helper
0.463
3141196NOKESVL
Solar/Wind Helper
1.151
316303AF2-085
50/50
4.791
971285AH1-108 GEN
50/50
2.026
970603AG2-384 GEN
50/50
5.274
316233AE1-074 FULL
Solar/Wind Harmer
0.21
971281AH1-106 GEN
Solar/Wind Harmer
3.638
971283AH1-107 GEN
Solar/Wind Harmer
3.638
3143316POE
Solar/Wind Harmer
0.98
941031AE2-094 GEN
Solar/Wind Harmer
45.33
944011AF1-069 GEN
Solar/Wind Harmer
14.811
316132AB2-190 GEN1
Solar/Wind Harmer
1.315
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
22.416
3151091ELIZAR2
Adder
22.027
3152611GOSPORTB
Adder
3.112
3152621GOSPORTC
Adder
2.641
3152601GOSPORTA
Adder
2.437
971445AH1-216 GEN
Solar/Wind Harmer
17.191
972265AH1-717 GEN
Adder
18.943
3151201GRAVEL4
Adder
17.758
3151191GRAVEL3
Adder
17.533
3151211GRAVEL5
Adder
17.533
316312AB1-027
Solar/Wind Harmer
0.435
957871AF2-081 GEN
Solar/Wind Harmer
12.066
970673AG2-436 GEN
Solar/Wind Harmer
51.597
970673AG2-436 GEN
Solar/Wind Harmer
34.398
319010AE1-072 C
Solar/Wind Harmer
1.218
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.166
316311AC2-079 GEN
Solar/Wind Harmer
6.941
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.95
316169AC1-164_GENC
Solar/Wind Harmer
21.555
315975AC1-164 GENB
Solar/Wind Harmer
0.738
315835AF2-110_GEN
Solar/Wind Harmer
1.649
316315AB2-025 C
Solar/Wind Harmer
0.194
313526AB2-022
Solar/Wind Harmer
0.13
972189AH1-679 GEN
Adder
4.009
3146486SUNBURY
Solar/Wind Harmer
0.239
3146486SUNBURY
Solar/Wind Harmer
0.239
971967AH1-528 GEN
Solar/Wind Harmer
38.202
315814AE2-033 C
Solar/Wind Harmer
18.884
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.658
3145176PASQUOTANK
Solar/Wind Harmer
0.148
971167AH1-042 GEN
Solar/Wind Harmer
21.1
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3138283WHITEMARSH
Solar/Wind Harmer
0.055
3143873LANEXA
Solar/Wind Harmer
0.14
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.866
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.23
3130156CHOWAN
Solar/Wind Harmer
0.23
3141873WAN 176
Solar/Wind Harmer
0.046
970085AG2-068 GEN
Solar/Wind Harmer
12.13
970581AG2-369 GEN
Solar/Wind Harmer
10.432
3141913WHIT STONE
Solar/Wind Harmer
0.227
3138133OCRAN
Solar/Wind Harmer
0.068
315816AE2-034 GEN
Solar/Wind Harmer
0.969
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
3150411LDYSMT5
Adder
30.153
3150381LDYSMT2
Adder
28.858
972213AH1-691 GEN
Adder
4.882
972215AH1-692 GEN
Adder
4.882
3130546PLYMOUTH
Solar/Wind Harmer
0.222
315732AD1-074 GEN1
Solar/Wind Harmer
1.273
315733AD1-074 GEN2
Solar/Wind Harmer
1.273
315735AD1-075 GEN1
Solar/Wind Harmer
0.637
965291AG1-394 GEN
Solar/Wind Harmer
0.982
962981AG1-147 GEN
Solar/Wind Harmer
8.243
3146206CASHIE
Solar/Wind Harmer
0.219
970601AG2-382 GEN
Solar/Wind Harmer
8.195
3145893MURPHYS
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
0.219
970327AG2-215 GEN
Solar/Wind Harmer
7.177
3145513AHOSKIE
Solar/Wind Harmer
0.452
3145513AHOSKIE
Solar/Wind Harmer
0.216
3146043SEABORD
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.43
3145683EARLEYS
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.215
315607AA1-063A GEN
Solar/Wind Harmer
0.438
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
23.331
3137643SOCKMAN
Solar/Wind Harmer
0.845
3141813NORNECK
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.668
3145796HORNRTN
Solar/Wind Harmer
0.084
3146033SCOT NK
Solar/Wind Harmer
0.828
970831AG2-522 GEN
Solar/Wind Harmer
8.631
316005AA1-067
Solar/Wind Harmer
0.213
3145746EVERETS
Solar/Wind Harmer
0.791
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
970181AG2-120 GEN
Solar/Wind Harmer
2.475
957861AF2-080 GEN
Solar/Wind Harmer
8.442
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.006
971443AH1-215 GEN
Solar/Wind Harmer
3.255
3144303KENBRDG
Solar/Wind Harmer
0.155
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.193
3145573BETHELC
Solar/Wind Harmer
0.193
970683AG2-441 GEN
Solar/Wind Harmer
12.874
970681AG2-440 GEN
Solar/Wind Harmer
10.299
946301AF1-294 GEN
Solar/Wind Harmer
3.8
961791AG1-021 GEN
Solar/Wind Harmer
1.849
315657AE1-056 GEN
Solar/Wind Harmer
6.628
316223AC1-118
Solar/Wind Harmer
0.135
970285AG2-188 GEN
Solar/Wind Harmer
14.487
971845AH1-439 GEN
Solar/Wind Harmer
8.236
316118AC1-105 GEN
Solar/Wind Harmer
0.469
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
972205AH1-687 GEN
Adder
7.261
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
5.471
971447AH1-217 GEN
Solar/Wind Harmer
4.69
972193AH1-681 GEN
Adder
3.425
316123AC1-075 GEN
Solar/Wind Harmer
0.197
970165AG2-112 GEN
Solar/Wind Harmer
1.171
970163AG2-111 GEN
Solar/Wind Harmer
1.117
270494AE1-108_GEN
Solar/Wind Harmer
1.686
3147346CASHSCORNER
Solar/Wind Harmer
0.279
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
2.196
316411AF1-147_GEN1
Solar/Wind Helper
0.801
316415AF1-147_GEN2
Solar/Wind Helper
0.801
3138216PACIFIC
Solar/Wind Helper
0.039
LAGNLTFEXP_LAGN->PJM
CLTF
8.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.899
TVALTFEXP_TVA->PJM
CLTF
4.316
CPLELTFEXP_CPLE->PJM
CLTF
12.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.813
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.369
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.657
MECLTFEXP_MEC->PJM
CLTF
3.808
SIGELTFEXP_SIGE->PJM
CLTF
0.116
NYPJM->LTFIMP_NY
CLTF
3.309
LGEELTFEXP_LGEE->PJM
CLTF
1.392
WECLTFEXP_WEC->PJM
CLTF
0.673

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 57502_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57502_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:169.18 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:5274.99
MW Contribution:33.74
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
32.429
970119AG2-088 GEN
50/50
33.739
315243AE2-183_GT3
50/50
3.74
3151051BRUNSWICKS1
50/50
6.107
3151021BRUNSWICKG1
50/50
2.942
971451AH1-221 GEN
50/50
8.937
3151791S ANNAG2
50/50
0.782
3151781S ANNAS1
50/50
0.402
3151741LOISA C
50/50
0.792
3151751LOISA D
50/50
14.488
3147666LOUISA
Solar/Wind Harmer
-0.169
316192AB2-158 GEN
Solar/Wind Harmer
4.93
3143226MDLTHAN
Solar/Wind Harmer
-0.028
940641AE2-051 GEN
Solar/Wind Harmer
24.512
939411AE1-173 GEN
Solar/Wind Harmer
124.766
3143526WINTERP
Solar/Wind Harmer
-0.128
3143336POWHATN
Solar/Wind Harmer
2.867
970919AG2-571 GEN
Solar/Wind Harmer
7.628
970087AG2-069 GEN
Solar/Wind Harmer
22.494
316336AC2-165 C
Solar/Wind Harmer
4.004
957481AF2-042 GEN
Solar/Wind Harmer
71.332
315693AD1-088 GEN
Solar/Wind Harmer
11.147
962491AG1-098 GEN
Solar/Wind Harmer
14.859
944591AF1-124 GEN
Solar/Wind Harmer
98.183
316294AC1-161 GEN
Solar/Wind Harmer
6.948
316388AE2-253 GEN
Solar/Wind Harmer
1.436
316375AC2-012 GEN
Solar/Wind Harmer
7.364
3150981CHESPKA
Adder
2.365
3146456SLIGO L269
Solar/Wind Harmer
-0.021
316023GEN1_S
Solar/Wind Harmer
1.431
316246AF1-032 C
Solar/Wind Harmer
0.429
316093AE2-104_GEN
Solar/Wind Harmer
6.144
970661AG2-428 GEN
Solar/Wind Harmer
22.438
316381AD1-082 GEN
Solar/Wind Harmer
1.936
970659AG2-427 GEN
Solar/Wind Harmer
11.217
3146516WINFALL
Solar/Wind Harmer
-0.068
3146516WINFALL
Solar/Wind Harmer
-0.021
960081AF2-299 GEN
Solar/Wind Harmer
2.343
316072AD1-144
Solar/Wind Harmer
0.421
315800Z1-036_GEN1
Solar/Wind Harmer
5.136
3150851SPRUNCC
Adder
0.848
3130156CHOWAN
Solar/Wind Harmer
-0.021
971795AH1-408 GEN
Solar/Wind Harmer
15.455
3147043LAWRENC
Adder
1.651
3145336SMITFLD
Solar/Wind Harmer
-0.081
315687AD1-152 GEN
Solar/Wind Harmer
2.461
3145663CRESWEL
Solar/Wind Harmer
-0.057
971163AH1-040 GEN
Solar/Wind Harmer
19.129
3145893MURPHYS
Solar/Wind Harmer
-0.081
3145893MURPHYS
Solar/Wind Harmer
0.601
316011AB1-132 GEN
Solar/Wind Harmer
4.229
962571AG1-106 GEN
Solar/Wind Harmer
2.906
970937AG2-583 GEN
Solar/Wind Harmer
14.494
3146173TUNIS
Solar/Wind Harmer
-0.02
3146206CASHIE
Solar/Wind Harmer
-0.02
971547AH1-271 GEN
Solar/Wind Harmer
5.026
316190AA2-174 GEN
Solar/Wind Harmer
0.247
3146263WOODLND
Solar/Wind Harmer
-0.02
3145783HORNRTN
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.02
3151171GRAVELC
Adder
1.889
3145796HORNRTN
Solar/Wind Harmer
-0.065
3145796HORNRTN
Solar/Wind Harmer
-0.02
315671AE2-027_GEN
Solar/Wind Harmer
14.951
316129AC1-054 GEN
Solar/Wind Harmer
1.746
971065AG2-659 GEN
Solar/Wind Harmer
9.947
3146926FARMVIL
Solar/Wind Harmer
-0.012
963171AG1-166 GEN
Solar/Wind Harmer
2.471
971563AH1-280 GEN
Solar/Wind Harmer
2.471
3144293JTRSVLE
Adder
0.56
970685AG2-442 GEN
Solar/Wind Harmer
17.294
961611AG1-000B GEN
Solar/Wind Harmer
9.753
3145823KELFORD
Solar/Wind Harmer
-0.02
316237AB2-079_GEN
Solar/Wind Harmer
0.594
971647AH1-324 GEN
Solar/Wind Harmer
9.808
3145963POPLR C
Solar/Wind Harmer
-0.019
3143096IRON208
Adder
0.665
944631AF1-128 GEN
Adder
73.735
3142433PROV 92
Adder
0.28
3142433PROV 92
Adder
0.28
3141843SHACKLE
Adder
0.703
316045AC1-158 PL2
Solar/Wind Helper
10.491
3152261N ANNA2
50/50
32.427
3151031BRUNSWICKG2
50/50
2.942
3151771S ANNAG1
50/50
0.782
3151801S ANNAS2
50/50
0.402
3151761LOISA E
50/50
29.536
972183AH1-676 GEN
50/50
229.088
3147666LOUISA
Solar/Wind Harmer
-0.097
316313AB2-026
Solar/Wind Harmer
0.652
316258AE1-075 C
Solar/Wind Harmer
0.587
316405AF2-144 C
Solar/Wind Harmer
0.619
3143336POWHATN
Solar/Wind Harmer
2.437
970917AG2-570 GEN
Solar/Wind Harmer
60.26
316478AD1-087 GEN
Solar/Wind Harmer
1.891
316486AD2-202 GEN
Solar/Wind Harmer
0.554
944581AF1-123 GEN
Solar/Wind Harmer
97.831
944601AF1-125 GEN
Solar/Wind Harmer
96.304
315773AC2-141 GEN
Solar/Wind Harmer
8.987
3151101ELIZAR3
Adder
17.61
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.021
971153AH1-033 GEN
Solar/Wind Harmer
2.591
316365GEN2_N
Solar/Wind Harmer
1.431
316320Y1-086
Solar/Wind Harmer
1.238
970661AG2-428 GEN
Solar/Wind Harmer
3.976
316083AB2-161 GEN
Solar/Wind Harmer
3.427
970659AG2-427 GEN
Solar/Wind Harmer
1.988
315813AE1-149 C
Solar/Wind Harmer
13.193
3144536CHRHLND
Solar/Wind Harmer
-0.003
316435W1029_GEN3
Solar/Wind Harmer
3.804
3146516WINFALL
Solar/Wind Harmer
-0.021
3145273HOLLAND
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.021
970909AG2-566 GEN
Solar/Wind Harmer
1.979
966621AG1-532 GEN
Solar/Wind Harmer
0.423
3150861SPRUNCD
Adder
0.848
315839AE2-212 C
Solar/Wind Harmer
0.622
3146376EDENTON
Solar/Wind Harmer
-0.021
3147043LAWRENC
Solar/Wind Harmer
-0.012
313506AB2-031 GEN
Solar/Wind Harmer
1.647
3145336SMITFLD
Solar/Wind Harmer
-0.008
3156081AA2-088 GEN
Solar/Wind Harmer
6.634
315614AA2-178 GEN
Solar/Wind Harmer
2.202
3145893MURPHYS
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
-0.02
957521AF2-046 GEN
Solar/Wind Harmer
15.928
961681AG1-008 GEN
Solar/Wind Harmer
15.928
971157AH1-035 GEN
Solar/Wind Harmer
2.527
965281AG1-393 GEN
Solar/Wind Harmer
2.525
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
315737AD1-076 GEN
Solar/Wind Harmer
3.836
3146173TUNIS
Solar/Wind Harmer
-0.02
3146206CASHIE
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.324
316140AB2-099
Solar/Wind Harmer
0.135
962331AG1-082 GEN
Solar/Wind Harmer
2.506
3146263WOODLND
Solar/Wind Harmer
-0.02
3156021HOLLOMANSOL
Solar/Wind Harmer
2.693
3151221GRAVEL6
Adder
12.908
3151171GRAVELC
Adder
2.483
3145796HORNRTN
Solar/Wind Harmer
-0.079
3145796HORNRTN
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.012
942461AE2-259 GEN
Solar/Wind Harmer
2.971
3147133PAMPLIN
Solar/Wind Harmer
-0.062
971193AH1-056 GEN
Solar/Wind Harmer
12.355
963181AG1-167 GEN
Solar/Wind Harmer
1.853
3144293JTRSVLE
Adder
0.56
959311AF2-222 GEN
Solar/Wind Harmer
20.628
970257AG2-171 GEN
Solar/Wind Harmer
7.411
961611AG1-000B GEN
Solar/Wind Harmer
4.161
315785AD2-033 C
Solar/Wind Harmer
4.478
964241AG1-285 GEN
Solar/Wind Harmer
15.437
316317KELFORD C
Solar/Wind Harmer
0.931
3145823KELFORD
Solar/Wind Harmer
-0.02
316131AB2-060 GEN
Solar/Wind Harmer
2.132
3145963POPLR C
Solar/Wind Harmer
-0.019
3144216WINCHST
Adder
0.63
3150921YORKTN3
Adder
4.159
3143096IRON208
Adder
0.665
3143096IRON208
Adder
0.651
3142433PROV 92
Adder
0.28
3142433PROV 92
Adder
0.28
3141843SHACKLE
Adder
0.703
316044AC1-158 PL1
Solar/Wind Helper
3.277
316450AC1-158 RIC
Solar/Wind Helper
0.874
971133AH1-012 GEN
50/50
7.972
970533AG2-339 GEN
50/50
20.723
970531AG2-338 GEN
50/50
8.289
315242AE2-183_GT2
50/50
3.74
315241AE2-183_GT1
50/50
3.717
972185AH1-677 GEN
50/50
13.482
3151041BRUNSWICKG3
50/50
2.942
972187AH1-678 GEN
50/50
6.752
3151731LOISA B
50/50
14.488
3151721LOISA A
50/50
14.413
971223AH1-071 GEN
Solar/Wind Harmer
3.554
3143526WINTERP
Solar/Wind Harmer
-0.128
970933AG2-581 GEN
Solar/Wind Harmer
23.091
3144356SAPONY
Solar/Wind Harmer
0.804
970099AG2-077 GEN
Solar/Wind Harmer
28.533
316185AD1-033 GEN
Solar/Wind Harmer
2.253
3145506HICKORY
Solar/Wind Harmer
-0.085
3145506HICKORY
Solar/Wind Harmer
-0.051
3145506HICKORY
Solar/Wind Harmer
-0.013
3142956BIRDNECK
Solar/Wind Harmer
1.144
316316AC1-027 C
Solar/Wind Harmer
0.654
316339AD2-160 GEN
Solar/Wind Harmer
1.436
316036AC1-147 C
Solar/Wind Harmer
0.574
3150991CHESPKB
Adder
1.984
3150991CHESPKB
Adder
1.936
316018AA1-139 ULT2
Solar/Wind Harmer
1.823
316017AA1-139 ULT1
Solar/Wind Harmer
1.722
3137176SLIGO L2192
Solar/Wind Harmer
-0.084
3146456SLIGO L269
Solar/Wind Harmer
2.51
3130086AYDLETT
Solar/Wind Harmer
-0.085
971741AH1-377 GEN
Solar/Wind Harmer
24.619
3146386ELIZ CT
Solar/Wind Harmer
-0.021
970657AG2-426 GEN
Solar/Wind Harmer
6.599
970657AG2-426 GEN
Solar/Wind Harmer
1.38
316431W1029_GEN1
Solar/Wind Harmer
3.804
316433W1029_GEN2
Solar/Wind Harmer
3.804
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
970301AG2-198 GEN
Solar/Wind Harmer
10.423
315742AE1-103 GEN
Solar/Wind Harmer
2.176
3146376EDENTON
Solar/Wind Harmer
0.613
3146376EDENTON
Solar/Wind Harmer
0.613
316181AB2-040 GEN
Solar/Wind Harmer
2.859
316236AE1-162_GEN
Solar/Wind Harmer
0.617
3145893MURPHYS
Solar/Wind Harmer
0.565
3145893MURPHYS
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.012
316065AD1-022 GEN
Solar/Wind Harmer
10.065
3146173TUNIS
Solar/Wind Harmer
-0.02
3146173TUNIS
Solar/Wind Harmer
-0.02
3145593CAROLNA
Solar/Wind Harmer
-0.02
3145593CAROLNA
Solar/Wind Harmer
-0.02
966811AG1-552 GEN
Solar/Wind Harmer
2.263
3145593CAROLNA
Solar/Wind Harmer
0.167
316426AA2-053 GEN
Solar/Wind Harmer
2.029
3145783HORNRTN
Solar/Wind Harmer
2.372
3145783HORNRTN
Solar/Wind Harmer
1.898
3145783HORNRTN
Solar/Wind Harmer
0.593
3145783HORNRTN
Solar/Wind Harmer
0.237
3145796HORNRTN
Solar/Wind Harmer
-0.059
939181AE1-148 GEN
Solar/Wind Harmer
11.135
3147133PAMPLIN
Solar/Wind Harmer
-0.02
3147133PAMPLIN
Solar/Wind Harmer
-0.016
958211AF2-115 GEN
Solar/Wind Harmer
3.088
963191AG1-168 GEN
Solar/Wind Harmer
1.853
3144293JTRSVLE
Adder
0.56
3144293JTRSVLE
Adder
0.472
316034AC1-036 C
Solar/Wind Harmer
0.367
970323AG2-213 GEN
Solar/Wind Harmer
9.881
971775AH1-396 GEN
Solar/Wind Harmer
1.407
313527AB2-043 GEN
Solar/Wind Harmer
3.21
316240AF1-291 C
Solar/Wind Harmer
0.595
966001AG1-469 GEN
Solar/Wind Harmer
0.369
944641AF1-129 GEN
Adder
82.518
3142366NRTHEST
Adder
0.471
3150691DARBY 3
Adder
10.241
3150701DARBY 4
Adder
10.217
3150681DARBY 2
Adder
10.205
3150671DARBY 1
Adder
10.193
3142296MT RD221
Adder
0.388
316447AC1-158 HLD
Solar/Wind Helper
7.213
316033AB2-134 GEN
Solar/Wind Harmer
5.503
316303AF2-085
50/50
4.498
315244AE2-183_ST
50/50
6.466
963041AG1-153 GEN
50/50
5.958
315779AE2-040
50/50
2.865
941031AE2-094 GEN
Solar/Wind Harmer
49.114
944011AF1-069 GEN
Solar/Wind Harmer
15.389
970673AG2-436 GEN
Solar/Wind Harmer
53.974
970673AG2-436 GEN
Solar/Wind Harmer
27.329
971967AH1-528 GEN
Solar/Wind Harmer
47.608
316233AE1-074 FULL
Solar/Wind Harmer
0.665
971281AH1-106 GEN
Solar/Wind Harmer
4.02
971283AH1-107 GEN
Solar/Wind Harmer
4.02
970085AG2-068 GEN
Solar/Wind Harmer
14.996
970581AG2-369 GEN
Solar/Wind Harmer
12.896
316315AB2-025 C
Solar/Wind Harmer
0.622
315814AE2-033 C
Solar/Wind Harmer
21.391
3143316POE
Solar/Wind Harmer
-0.087
3147346CASHSCORNER
Solar/Wind Harmer
0.337
3151081ELIZAR1
Adder
17.387
3151091ELIZAR2
Adder
17.085
957871AF2-081 GEN
Solar/Wind Harmer
10.642
3152611GOSPORTB
Adder
2.412
3152621GOSPORTC
Adder
2.047
3152601GOSPORTA
Adder
1.888
319010AE1-072 C
Solar/Wind Harmer
4.298
3146406KITTY HAWK
Solar/Wind Harmer
0.018
316305AF2-043 C
Solar/Wind Harmer
0.639
315835AF2-110_GEN
Solar/Wind Harmer
2.641
313526AB2-022
Solar/Wind Harmer
0.57
315833AF1-017_GEN
Solar/Wind Harmer
4.012
316349AD2-085 GEN
Solar/Wind Harmer
1.879
316311AC2-079 GEN
Solar/Wind Harmer
10.655
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.021
316321Z2-027
Solar/Wind Harmer
0.568
3146396TANGLEW
Solar/Wind Harmer
0.388
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
946281AF1-292 GEN
Solar/Wind Harmer
0.467
315611Z1-036_GEN2
Solar/Wind Harmer
5.136
971285AH1-108 GEN
Adder
1.388
3130156CHOWAN
Solar/Wind Harmer
-0.021
3130156CHOWAN
Solar/Wind Harmer
-0.021
316087AB2-174 GEN
Solar/Wind Harmer
2.938
971445AH1-216 GEN
Solar/Wind Harmer
12.633
965291AG1-394 GEN
Solar/Wind Harmer
1.811
315816AE2-034 GEN
Solar/Wind Harmer
1.651
3137643SOCKMAN
Solar/Wind Harmer
-0.081
316318V4-068
Solar/Wind Harmer
0.505
3145893MURPHYS
Solar/Wind Harmer
-0.054
3145893MURPHYS
Solar/Wind Harmer
-0.02
3146043SEABORD
Solar/Wind Harmer
-0.02
315607AA1-063A GEN
Solar/Wind Harmer
2.043
3130546PLYMOUTH
Solar/Wind Harmer
-0.02
315652AC1-086 GEN
Solar/Wind Harmer
22.742
315732AD1-074 GEN1
Solar/Wind Harmer
4.081
315733AD1-074 GEN2
Solar/Wind Harmer
4.081
315735AD1-075 GEN1
Solar/Wind Harmer
2.041
3146206CASHIE
Solar/Wind Harmer
-0.02
970601AG2-382 GEN
Solar/Wind Harmer
8.795
3145513AHOSKIE
Solar/Wind Harmer
0.175
961941AG1-037 GEN
Solar/Wind Harmer
0.151
3145513AHOSKIE
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.04
3145683EARLEYS
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.02
972265AH1-717 GEN
Adder
13.785
3151201GRAVEL4
Adder
12.922
3151191GRAVEL3
Adder
12.759
3151211GRAVEL5
Adder
12.759
3145796HORNRTN
Solar/Wind Harmer
-0.063
3145796HORNRTN
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
9.966
315657AE1-056 GEN
Solar/Wind Harmer
7.413
946301AF1-294 GEN
Solar/Wind Harmer
5.065
961791AG1-021 GEN
Solar/Wind Harmer
2.471
970683AG2-441 GEN
Solar/Wind Harmer
15.441
970681AG2-440 GEN
Solar/Wind Harmer
12.353
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.891
316239AB2-077_GEN
Solar/Wind Harmer
0.594
316238AB2-078_GEN
Solar/Wind Harmer
0.594
3146033SCOT NK
Solar/Wind Harmer
-0.078
972205AH1-687 GEN
Adder
6.743
3142433PROV 92
Adder
0.28
3142433PROV 92
Adder
0.28
LAGNLTFEXP_LAGN->PJM
CLTF
7.115
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.438
TVALTFEXP_TVA->PJM
CLTF
3.587
CPLELTFEXP_CPLE->PJM
CLTF
10.87
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.96
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.227
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.109
MECLTFEXP_MEC->PJM
CLTF
3.039
SIGELTFEXP_SIGE->PJM
CLTF
0.091
NYPJM->LTFIMP_NY
CLTF
2.887
LGEELTFEXP_LGEE->PJM
CLTF
1.081
WECLTFEXP_WEC->PJM
CLTF
0.523

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.52 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5930.65
MW Contribution:35.87
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
20.538
3150861SPRUNCD
50/50
1.233
3143096IRON208
50/50
1.093
3143096IRON208
50/50
1.071
3150801HOPHCF4
50/50
1.442
971211AH1-065 GEN
50/50
1.739
3151101ELIZAR3
50/50
24.061
3151161SURRY 1
50/50
9.348
3147666LOUISA
Solar/Wind Harmer
-0.066
315773AC2-141 GEN
Solar/Wind Harmer
11.614
315839AE2-212 C
Solar/Wind Harmer
0.835
965281AG1-393 GEN
Solar/Wind Harmer
3.451
315813AE1-149 C
Solar/Wind Harmer
17.198
944581AF1-123 GEN
Solar/Wind Harmer
125.059
944601AF1-125 GEN
Solar/Wind Harmer
123.108
970133AG2-095 GEN
Solar/Wind Harmer
3.091
970129AG2-093 GEN
Solar/Wind Harmer
15.452
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
315778AD1-151 GEN
Solar/Wind Harmer
23.752
970659AG2-427 GEN
Solar/Wind Harmer
2.578
3145336SMITFLD
Solar/Wind Harmer
-0.011
961611AG1-000B GEN
Solar/Wind Harmer
5.762
316083AB2-161 GEN
Solar/Wind Harmer
4.441
3151221GRAVEL6
Adder
17.693
3151171GRAVELC
Adder
3.404
970661AG2-428 GEN
Solar/Wind Harmer
5.139
3142946ENON
Solar/Wind Harmer
-0.009
970293AG2-193 GEN
Solar/Wind Harmer
3.403
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.31
3144216WINCHST
Adder
0.911
3150921YORKTN3
Adder
6.062
3142416OLDCHRC
Solar/Wind Harmer
2.734
316382AG1-145 C
Solar/Wind Harmer
0.815
316320Y1-086
Solar/Wind Harmer
1.576
316435W1029_GEN3
Solar/Wind Harmer
4.824
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.02
316473AC1-191 GEN
Solar/Wind Harmer
2.815
3146376EDENTON
Solar/Wind Harmer
-0.026
3141843SHACKLE
Adder
1.176
316203AE2-005 GEN
Solar/Wind Harmer
10.898
3141766HARMONY
Solar/Wind Harmer
2.298
316313AB2-026
Solar/Wind Harmer
0.695
316258AE1-075 C
Solar/Wind Harmer
0.626
316405AF2-144 C
Solar/Wind Harmer
0.66
3143336POWHATN
Solar/Wind Harmer
2.601
316280AD1-041 GEN
Solar/Wind Harmer
1.942
316156AD2-030 GEN
Solar/Wind Harmer
0.685
3141873WAN 176
Solar/Wind Harmer
3.046
970917AG2-570 GEN
Solar/Wind Harmer
64.143
315614AA2-178 GEN
Solar/Wind Harmer
2.735
971157AH1-035 GEN
Solar/Wind Harmer
3.118
3156081AA2-088 GEN
Solar/Wind Harmer
8.083
315737AD1-076 GEN
Solar/Wind Harmer
4.727
316365GEN2_N
Solar/Wind Harmer
1.677
3146206CASHIE
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.172
3145893MURPHYS
Solar/Wind Harmer
-0.025
962971AG1-146 GEN
Solar/Wind Harmer
4.602
957521AF2-046 GEN
Solar/Wind Harmer
19.314
961681AG1-008 GEN
Solar/Wind Harmer
19.314
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.275
316484AD2-074 GEN
Solar/Wind Harmer
6.115
970009AG2-005 GEN
Solar/Wind Harmer
3.036
316463AE2-346 GEN
Solar/Wind Harmer
0.393
316140AB2-099
Solar/Wind Harmer
0.163
962331AG1-082 GEN
Solar/Wind Harmer
3.031
966621AG1-532 GEN
Solar/Wind Harmer
0.492
966881AG1-559 GEN
Solar/Wind Harmer
0.724
3146263WOODLND
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.925
316404AE1-155 C
Solar/Wind Harmer
4.606
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145963POPLR C
Solar/Wind Harmer
-0.024
316317KELFORD C
Solar/Wind Harmer
1.117
3145823KELFORD
Solar/Wind Harmer
-0.024
316478AD1-087 GEN
Solar/Wind Harmer
2.037
316486AD2-202 GEN
Solar/Wind Harmer
0.597
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.088
316210AC1-098 GEN
Solar/Wind Harmer
3.591
3150401LDYSMT4
Adder
26.739
3150371LDYSMT1
Adder
25.837
3144293JTRSVLE
Adder
0.613
972255AH1-712 GEN
Adder
76.926
3151761LOISA E
Adder
16.965
972183AH1-676 GEN
Adder
130.241
3141316ARNOLDS
Adder
0.278
316044AC1-158 PL1
Solar/Wind Helper
5.238
316450AC1-158 RIC
Solar/Wind Helper
1.397
316170AC1-121 GEN2
Solar/Wind Helper
0.46
3141196NOKESVL
Solar/Wind Helper
1.151
3152251N ANNA1
50/50
20.54
970119AG2-088 GEN
50/50
35.865
3150851SPRUNCC
50/50
1.233
3143096IRON208
50/50
1.093
3152331SURRY 2
50/50
10.164
3150771HOPHCF1
50/50
0.992
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.152
3147666LOUISA
Solar/Wind Harmer
-0.114
940641AE2-051 GEN
Solar/Wind Harmer
26.675
939411AE1-173 GEN
Solar/Wind Harmer
140.912
316192AB2-158 GEN
Solar/Wind Harmer
3.325
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.98
315671AE2-027_GEN
Solar/Wind Harmer
20.692
944591AF1-124 GEN
Solar/Wind Harmer
125.51
970129AG2-093 GEN
Solar/Wind Harmer
6.259
316458AB2-190 GEN2
Solar/Wind Harmer
2.776
316375AC2-012 GEN
Solar/Wind Harmer
9.491
3150981CHESPKA
Adder
3.048
971069AG2-661 GEN
Solar/Wind Harmer
4.338
970659AG2-427 GEN
Solar/Wind Harmer
14.549
3145336SMITFLD
Solar/Wind Harmer
-0.109
971647AH1-324 GEN
Solar/Wind Harmer
13.692
961611AG1-000B GEN
Solar/Wind Harmer
13.505
316381AD1-082 GEN
Solar/Wind Harmer
2.509
944631AF1-128 GEN
Adder
116.045
3151171GRAVELC
Adder
2.589
970661AG2-428 GEN
Solar/Wind Harmer
28.997
316388AE2-253 GEN
Solar/Wind Harmer
1.836
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316072AD1-144
Solar/Wind Harmer
0.549
3138126ROCKLANDING
Solar/Wind Harmer
0.083
316246AF1-032 C
Solar/Wind Harmer
0.548
3142416OLDCHRC
Solar/Wind Harmer
-0.07
3142416OLDCHRC
Solar/Wind Harmer
-0.027
316159AE1-175 C
Solar/Wind Harmer
0.726
316093AE2-104_GEN
Solar/Wind Harmer
7.84
971317AH1-138 GEN
Solar/Wind Harmer
3.367
3146516WINFALL
Solar/Wind Harmer
-0.086
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.105
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
315800Z1-036_GEN1
Solar/Wind Harmer
6.468
3130156CHOWAN
Solar/Wind Harmer
-0.026
971777AH1-397 GEN
Solar/Wind Harmer
3.039
3141843SHACKLE
Adder
1.176
3141766HARMONY
Solar/Wind Harmer
-0.005
3143336POWHATN
Solar/Wind Harmer
3.06
970919AG2-571 GEN
Solar/Wind Harmer
8.119
970087AG2-069 GEN
Solar/Wind Harmer
23.954
3145663CRESWEL
Solar/Wind Harmer
-0.071
971163AH1-040 GEN
Solar/Wind Harmer
23.766
3138133OCRAN
Solar/Wind Harmer
-0.015
316023GEN1_S
Solar/Wind Harmer
1.677
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.159
316336AC2-165 C
Solar/Wind Harmer
4.278
3145893MURPHYS
Solar/Wind Harmer
-0.098
3145893MURPHYS
Solar/Wind Harmer
0.73
957481AF2-042 GEN
Solar/Wind Harmer
76.436
3146173TUNIS
Solar/Wind Harmer
-0.024
961951AG1-038 GEN
Solar/Wind Harmer
3.2
960081AF2-299 GEN
Solar/Wind Harmer
2.727
3145683EARLEYS
Solar/Wind Harmer
-0.024
966881AG1-559 GEN
Solar/Wind Harmer
0.248
3146263WOODLND
Solar/Wind Harmer
-0.024
962861AG1-135 GEN
Solar/Wind Harmer
8.995
315693AD1-088 GEN
Solar/Wind Harmer
11.973
962491AG1-098 GEN
Solar/Wind Harmer
15.963
316011AB1-132 GEN
Solar/Wind Harmer
4.983
962571AG1-106 GEN
Solar/Wind Harmer
3.424
971795AH1-408 GEN
Solar/Wind Harmer
17.814
3145963POPLR C
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.291
3145823KELFORD
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.632
3147043LAWRENC
Adder
1.895
964211AG1-282 GEN
Solar/Wind Harmer
0.706
3141726DUNNSVL
Solar/Wind Harmer
-0.093
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.053
316212AC1-099_GEN
Solar/Wind Harmer
1.995
972197AH1-683 GEN
Adder
4.175
972219AH1-694 GEN
Adder
3.006
3144293JTRSVLE
Adder
0.613
972277AH1-723 GEN
Adder
89.642
3151751LOISA D
Adder
8.322
316045AC1-158 PL2
Solar/Wind Helper
16.768
316006AB2-029 C
Solar/Wind Helper
0.152
316254AC1-120 GEN1
Solar/Wind Helper
1.381
971133AH1-012 GEN
50/50
5.498
944641AF1-129 GEN
50/50
124.495
970533AG2-339 GEN
50/50
21.875
970531AG2-338 GEN
50/50
8.75
3150781HOPHCF2
50/50
0.992
3150791HOPHCF3
50/50
0.992
3150761HOPPOLC
50/50
0.629
971213AH1-066 GEN
50/50
0.87
3142366NRTHEST
50/50
0.848
971223AH1-071 GEN
Solar/Wind Harmer
3.778
3143526WINTERP
Solar/Wind Harmer
-0.152
316240AF1-291 C
Solar/Wind Harmer
0.834
316036AC1-147 C
Solar/Wind Harmer
0.74
3150991CHESPKB
Adder
2.557
3150991CHESPKB
Adder
2.496
316033AB2-134 GEN
Solar/Wind Harmer
8.837
315697AD1-025 GEN
Solar/Wind Harmer
5.542
316316AC1-027 C
Solar/Wind Harmer
0.841
3142956BIRDNECK
Solar/Wind Harmer
1.47
316236AE1-162_GEN
Solar/Wind Harmer
0.825
3150691DARBY 3
Adder
17.538
3150701DARBY 4
Adder
17.497
3150681DARBY 2
Adder
17.476
3150671DARBY 1
Adder
17.456
316185AD1-033 GEN
Solar/Wind Harmer
2.888
970657AG2-426 GEN
Solar/Wind Harmer
8.542
970657AG2-426 GEN
Solar/Wind Harmer
1.786
3145506HICKORY
Solar/Wind Harmer
-0.109
3145506HICKORY
Solar/Wind Harmer
-0.065
3145506HICKORY
Solar/Wind Harmer
-0.016
3142296MT RD221
Adder
0.773
316339AD2-160 GEN
Solar/Wind Harmer
1.836
3142946ENON
Solar/Wind Harmer
-0.003
316018AA1-139 ULT2
Solar/Wind Harmer
2.33
316017AA1-139 ULT1
Solar/Wind Harmer
2.201
3137176SLIGO L2192
Solar/Wind Harmer
-0.107
3146456SLIGO L269
Solar/Wind Harmer
3.207
3130086AYDLETT
Solar/Wind Harmer
-0.108
316075AC2-137 C
Solar/Wind Harmer
0.73
972185AH1-677 GEN
Adder
13.451
3146386ELIZ CT
Solar/Wind Harmer
-0.027
3144356SAPONY
Solar/Wind Harmer
0.938
316431W1029_GEN1
Solar/Wind Harmer
4.824
316433W1029_GEN2
Solar/Wind Harmer
4.824
972187AH1-678 GEN
Adder
6.746
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
970933AG2-581 GEN
Solar/Wind Harmer
24.532
966871AG1-558 GEN
Solar/Wind Harmer
0.787
966871AG1-558 GEN
Solar/Wind Harmer
0.269
315742AE1-103 GEN
Solar/Wind Harmer
2.721
3146376EDENTON
Solar/Wind Harmer
0.768
3146376EDENTON
Solar/Wind Harmer
0.768
316441AF1-014 GEN
Solar/Wind Harmer
1.742
316065AD1-022 GEN
Solar/Wind Harmer
12.361
3145893MURPHYS
Solar/Wind Harmer
0.686
3145893MURPHYS
Solar/Wind Harmer
-0.044
970099AG2-077 GEN
Solar/Wind Harmer
30.574
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316487AF1-042 GEN
Solar/Wind Harmer
3.2
957411AF2-035 GEN
Solar/Wind Harmer
10.838
970317AG2-208 GEN
Solar/Wind Harmer
10.537
316181AB2-040 GEN
Solar/Wind Harmer
3.34
958261AF2-120 GEN
Solar/Wind Harmer
9.253
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.396
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.657
3145593CAROLNA
Solar/Wind Harmer
0.196
3145783HORNRTN
Solar/Wind Harmer
2.786
3145783HORNRTN
Solar/Wind Harmer
2.229
3145783HORNRTN
Solar/Wind Harmer
0.697
3145783HORNRTN
Solar/Wind Harmer
0.279
315673AE1-157 GEN
Solar/Wind Harmer
17.6
3145796HORNRTN
Solar/Wind Harmer
-0.07
316077AC2-138 C
Solar/Wind Harmer
0.488
3150341NORNECKC1
Adder
2.157
3150341NORNECKC1
Adder
2.139
3150391LDYSMT3
Adder
26.689
972195AH1-682 GEN
Adder
3.507
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3151731LOISA B
Adder
8.322
3151721LOISA A
Adder
8.279
316447AC1-158 HLD
Solar/Wind Helper
11.529
315651AD1-115 GEN
Solar/Wind Helper
1.021
971741AH1-377 GEN
Solar/Wind Harmer
12.626
316303AF2-085
50/50
4.782
971285AH1-108 GEN
50/50
2.017
970603AG2-384 GEN
50/50
5.251
972263AH1-716 GEN
50/50
141.451
316233AE1-074 FULL
Solar/Wind Harmer
0.79
971281AH1-106 GEN
Solar/Wind Harmer
4.774
971283AH1-107 GEN
Solar/Wind Harmer
4.774
3143316POE
Solar/Wind Harmer
-0.109
941031AE2-094 GEN
Solar/Wind Harmer
51.844
944011AF1-069 GEN
Solar/Wind Harmer
16.245
3151081ELIZAR1
Adder
22.389
3151091ELIZAR2
Adder
22
316132AB2-190 GEN1
Solar/Wind Harmer
2.776
3152611GOSPORTB
Adder
3.108
3152621GOSPORTC
Adder
2.638
3152601GOSPORTA
Adder
2.434
316369SG1_INVT
Solar/Wind Harmer
4.896
971445AH1-216 GEN
Solar/Wind Harmer
16.942
972265AH1-717 GEN
Adder
18.896
3151201GRAVEL4
Adder
17.714
3151191GRAVEL3
Adder
17.489
3151211GRAVEL5
Adder
17.489
957871AF2-081 GEN
Solar/Wind Harmer
13.602
970673AG2-436 GEN
Solar/Wind Harmer
57.084
970673AG2-436 GEN
Solar/Wind Harmer
28.903
319010AE1-072 C
Solar/Wind Harmer
5.488
3146406KITTY HAWK
Solar/Wind Harmer
0.023
315833AF1-017_GEN
Solar/Wind Harmer
5.15
316349AD2-085 GEN
Solar/Wind Harmer
2.412
316311AC2-079 GEN
Solar/Wind Harmer
13.676
316305AF2-043 C
Solar/Wind Harmer
0.817
316312AB1-027
Solar/Wind Harmer
0.914
315835AF2-110_GEN
Solar/Wind Harmer
3.371
315976AC1-164 GENA
Solar/Wind Harmer
28.429
316169AC1-164_GENC
Solar/Wind Harmer
24.56
315975AC1-164 GENB
Solar/Wind Harmer
0.841
313526AB2-022
Solar/Wind Harmer
0.725
316315AB2-025 C
Solar/Wind Harmer
0.725
971967AH1-528 GEN
Solar/Wind Harmer
50.429
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146486SUNBURY
Solar/Wind Harmer
-0.027
315814AE2-033 C
Solar/Wind Harmer
24.939
316321Z2-027
Solar/Wind Harmer
0.722
3146396TANGLEW
Solar/Wind Harmer
0.493
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971167AH1-042 GEN
Solar/Wind Harmer
25.534
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
957831AF2-077 GEN
Solar/Wind Harmer
0.794
3138283WHITEMARSH
Solar/Wind Harmer
0.041
315611Z1-036_GEN2
Solar/Wind Harmer
6.468
3143873LANEXA
Solar/Wind Harmer
-0.015
972189AH1-679 GEN
Adder
3.879
316314AB2-024 C
Solar/Wind Harmer
2.214
3130156CHOWAN
Solar/Wind Harmer
-0.026
3130156CHOWAN
Solar/Wind Harmer
-0.026
316059AD1-063 C
Solar/Wind Harmer
0.583
315662AE1-191 GEN
Solar/Wind Harmer
3.107
315666AE1-190 GEN
Solar/Wind Harmer
0.777
957601AF2-054 GEN
Solar/Wind Harmer
0.768
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.97
970581AG2-369 GEN
Solar/Wind Harmer
13.734
315816AE2-034 GEN
Solar/Wind Harmer
2.051
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.029
315733AD1-074 GEN2
Solar/Wind Harmer
5.029
315735AD1-075 GEN1
Solar/Wind Harmer
2.515
965291AG1-394 GEN
Solar/Wind Harmer
2.201
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.779
316318V4-068
Solar/Wind Harmer
0.613
3145893MURPHYS
Solar/Wind Harmer
-0.066
3145893MURPHYS
Solar/Wind Harmer
-0.025
962981AG1-147 GEN
Solar/Wind Harmer
10.738
3145513AHOSKIE
Solar/Wind Harmer
0.211
961941AG1-037 GEN
Solar/Wind Harmer
0.182
3145513AHOSKIE
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.543
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.048
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.433
316087AB2-174 GEN
Solar/Wind Harmer
3.429
315652AC1-086 GEN
Solar/Wind Harmer
26.795
3137643SOCKMAN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.093
3141813NORNECK
Solar/Wind Harmer
-0.023
3150411LDYSMT5
Adder
26.823
3150381LDYSMT2
Adder
25.67
972213AH1-691 GEN
Adder
4.342
972215AH1-692 GEN
Adder
4.342
972205AH1-687 GEN
Adder
7.266
972193AH1-681 GEN
Adder
3.437
316164AC1-076 GEN
Solar/Wind Helper
2.187
316411AF1-147_GEN1
Solar/Wind Helper
0.802
316415AF1-147_GEN2
Solar/Wind Helper
0.802
3138216PACIFIC
Solar/Wind Helper
0.039
LAGNLTFEXP_LAGN->PJM
CLTF
8.538
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.91
TVALTFEXP_TVA->PJM
CLTF
4.323
CPLELTFEXP_CPLE->PJM
CLTF
12.318
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.908
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.684
MECLTFEXP_MEC->PJM
CLTF
3.82
SIGELTFEXP_SIGE->PJM
CLTF
0.116
NYPJM->LTFIMP_NY
CLTF
3.309
LGEELTFEXP_LGEE->PJM
CLTF
1.397
WECLTFEXP_WEC->PJM
CLTF
0.676

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.0 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5831.04
MW Contribution:35.42
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
20.32
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.056
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151101ELIZAR3
50/50
23.68
3151161SURRY 1
50/50
9.205
3147666LOUISA
Solar/Wind Harmer
-0.066
315839AE2-212 C
Solar/Wind Harmer
0.823
315773AC2-141 GEN
Solar/Wind Harmer
11.425
965281AG1-393 GEN
Solar/Wind Harmer
3.403
315813AE1-149 C
Solar/Wind Harmer
16.949
970133AG2-095 GEN
Solar/Wind Harmer
3.047
944581AF1-123 GEN
Solar/Wind Harmer
123.071
944601AF1-125 GEN
Solar/Wind Harmer
121.15
970129AG2-093 GEN
Solar/Wind Harmer
15.226
315778AD1-151 GEN
Solar/Wind Harmer
23.4
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.54
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.375
961611AG1-000B GEN
Solar/Wind Harmer
5.675
3151221GRAVEL6
Adder
17.422
3151171GRAVELC
Adder
3.352
970661AG2-428 GEN
Solar/Wind Harmer
5.062
970293AG2-193 GEN
Solar/Wind Harmer
3.354
3142946ENON
Solar/Wind Harmer
-0.009
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.257
3142416OLDCHRC
Solar/Wind Harmer
2.696
3144216WINCHST
Adder
0.896
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.802
316320Y1-086
Solar/Wind Harmer
1.551
316435W1029_GEN3
Solar/Wind Harmer
4.748
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316473AC1-191 GEN
Solar/Wind Harmer
2.785
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
10.757
316313AB2-026
Solar/Wind Harmer
0.688
316258AE1-075 C
Solar/Wind Harmer
0.619
316405AF2-144 C
Solar/Wind Harmer
0.653
3143336POWHATN
Solar/Wind Harmer
2.572
3146376EDENTON
Solar/Wind Harmer
-0.025
3141766HARMONY
Solar/Wind Harmer
2.268
316280AD1-041 GEN
Solar/Wind Harmer
1.917
316156AD2-030 GEN
Solar/Wind Harmer
0.677
3152251N ANNA1
50/50
20.321
970119AG2-088 GEN
50/50
35.422
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.99
3150771HOPHCF1
50/50
0.977
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.15
3147666LOUISA
Solar/Wind Harmer
-0.115
316192AB2-158 GEN
Solar/Wind Harmer
3.345
940641AE2-051 GEN
Solar/Wind Harmer
26.285
939411AE1-173 GEN
Solar/Wind Harmer
138.811
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.834
315671AE2-027_GEN
Solar/Wind Harmer
20.403
944591AF1-124 GEN
Solar/Wind Harmer
123.514
970129AG2-093 GEN
Solar/Wind Harmer
6.167
316458AB2-190 GEN2
Solar/Wind Harmer
2.735
971069AG2-661 GEN
Solar/Wind Harmer
4.274
316375AC2-012 GEN
Solar/Wind Harmer
9.341
3150981CHESPKA
Adder
3
970659AG2-427 GEN
Solar/Wind Harmer
14.335
971647AH1-324 GEN
Solar/Wind Harmer
13.486
3145336SMITFLD
Solar/Wind Harmer
-0.107
316381AD1-082 GEN
Solar/Wind Harmer
2.472
944631AF1-128 GEN
Adder
114.357
961611AG1-000B GEN
Solar/Wind Harmer
13.3
3151171GRAVELC
Adder
2.549
970661AG2-428 GEN
Solar/Wind Harmer
28.566
316388AE2-253 GEN
Solar/Wind Harmer
1.807
3146456SLIGO L269
Solar/Wind Harmer
-0.027
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.54
3138126ROCKLANDING
Solar/Wind Harmer
0.082
316246AF1-032 C
Solar/Wind Harmer
0.54
316159AE1-175 C
Solar/Wind Harmer
0.715
316093AE2-104_GEN
Solar/Wind Harmer
7.718
971317AH1-138 GEN
Solar/Wind Harmer
3.315
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
315800Z1-036_GEN1
Solar/Wind Harmer
6.367
971777AH1-397 GEN
Solar/Wind Harmer
3
3141843SHACKLE
Adder
1.16
3143336POWHATN
Solar/Wind Harmer
3.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3141766HARMONY
Solar/Wind Harmer
-0.005
970919AG2-571 GEN
Solar/Wind Harmer
8.004
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
23.613
3145663CRESWEL
Solar/Wind Harmer
-0.07
971163AH1-040 GEN
Solar/Wind Harmer
23.4
3138133OCRAN
Solar/Wind Harmer
-0.015
316023GEN1_S
Solar/Wind Harmer
1.652
972197AH1-683 GEN
Adder
4.553
972219AH1-694 GEN
Adder
3.278
316336AC2-165 C
Solar/Wind Harmer
4.232
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.065
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.719
957481AF2-042 GEN
Solar/Wind Harmer
75.375
961951AG1-038 GEN
Solar/Wind Harmer
3.17
3146173TUNIS
Solar/Wind Harmer
-0.024
960081AF2-299 GEN
Solar/Wind Harmer
2.688
962861AG1-135 GEN
Solar/Wind Harmer
8.919
3145683EARLEYS
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.811
962491AG1-098 GEN
Solar/Wind Harmer
15.746
316011AB1-132 GEN
Solar/Wind Harmer
4.91
962571AG1-106 GEN
Solar/Wind Harmer
3.374
971795AH1-408 GEN
Solar/Wind Harmer
17.56
3145963POPLR C
Solar/Wind Harmer
-0.023
316190AA2-174 GEN
Solar/Wind Harmer
0.287
3145823KELFORD
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316174AB2-169 GEN
Solar/Wind Harmer
3.577
3147043LAWRENC
Adder
1.868
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.04
316212AC1-099_GEN
Solar/Wind Harmer
1.965
3144293JTRSVLE
Adder
0.605
972277AH1-723 GEN
Adder
87.353
3151751LOISA D
Adder
8.676
316045AC1-158 PL2
Solar/Wind Helper
16.699
316006AB2-029 C
Solar/Wind Helper
0.14
971133AH1-012 GEN
50/50
5.491
944641AF1-129 GEN
50/50
122.767
970533AG2-339 GEN
50/50
21.564
970531AG2-338 GEN
50/50
8.626
3142366NRTHEST
50/50
0.836
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
971223AH1-071 GEN
Solar/Wind Harmer
3.731
3143526WINTERP
Solar/Wind Harmer
-0.15
316240AF1-291 C
Solar/Wind Harmer
0.822
3150691DARBY 3
Adder
17.296
3150701DARBY 4
Adder
17.255
3150681DARBY 2
Adder
17.235
3150671DARBY 1
Adder
17.215
316036AC1-147 C
Solar/Wind Harmer
0.728
3150991CHESPKB
Adder
2.516
3150991CHESPKB
Adder
2.456
316033AB2-134 GEN
Solar/Wind Harmer
8.705
315697AD1-025 GEN
Solar/Wind Harmer
5.46
3142956BIRDNECK
Solar/Wind Harmer
1.447
316316AC1-027 C
Solar/Wind Harmer
0.828
316236AE1-162_GEN
Solar/Wind Harmer
0.812
316185AD1-033 GEN
Solar/Wind Harmer
2.842
970657AG2-426 GEN
Solar/Wind Harmer
8.416
970657AG2-426 GEN
Solar/Wind Harmer
1.76
3142296MT RD221
Adder
0.763
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
3142946ENON
Solar/Wind Harmer
-0.003
316339AD2-160 GEN
Solar/Wind Harmer
1.807
316018AA1-139 ULT2
Solar/Wind Harmer
2.294
316017AA1-139 ULT1
Solar/Wind Harmer
2.166
3137176SLIGO L2192
Solar/Wind Harmer
-0.106
3146456SLIGO L269
Solar/Wind Harmer
3.156
3130086AYDLETT
Solar/Wind Harmer
-0.106
316075AC2-137 C
Solar/Wind Harmer
0.719
972185AH1-677 GEN
Adder
13.26
3144356SAPONY
Solar/Wind Harmer
0.924
3146386ELIZ CT
Solar/Wind Harmer
-0.026
972187AH1-678 GEN
Adder
6.65
316431W1029_GEN1
Solar/Wind Harmer
4.748
316433W1029_GEN2
Solar/Wind Harmer
4.748
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.778
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
24.187
315742AE1-103 GEN
Solar/Wind Harmer
2.679
316441AF1-014 GEN
Solar/Wind Harmer
1.72
3146376EDENTON
Solar/Wind Harmer
0.756
3146376EDENTON
Solar/Wind Harmer
0.756
957411AF2-035 GEN
Solar/Wind Harmer
11.373
970317AG2-208 GEN
Solar/Wind Harmer
11.057
315673AE1-157 GEN
Solar/Wind Harmer
18.722
3150391LDYSMT3
Adder
29.101
972195AH1-682 GEN
Adder
3.824
316065AD1-022 GEN
Solar/Wind Harmer
12.172
3145893MURPHYS
Solar/Wind Harmer
0.676
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
30.15
316487AF1-042 GEN
Solar/Wind Harmer
3.17
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.177
316181AB2-040 GEN
Solar/Wind Harmer
3.292
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.36
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.618
3145593CAROLNA
Solar/Wind Harmer
0.193
3145783HORNRTN
Solar/Wind Harmer
2.745
3145783HORNRTN
Solar/Wind Harmer
2.196
3145783HORNRTN
Solar/Wind Harmer
0.686
3145783HORNRTN
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3150341NORNECKC1
Adder
2.143
3150341NORNECKC1
Adder
2.126
3144293JTRSVLE
Adder
0.605
3144293JTRSVLE
Adder
0.51
3151731LOISA B
Adder
8.676
3151721LOISA A
Adder
8.631
316447AC1-158 HLD
Solar/Wind Helper
11.481
971741AH1-377 GEN
Solar/Wind Harmer
12.466
3141873WAN 176
Solar/Wind Harmer
3.008
970917AG2-570 GEN
Solar/Wind Harmer
63.229
966881AG1-559 GEN
Solar/Wind Harmer
0.76
315614AA2-178 GEN
Solar/Wind Harmer
2.693
971157AH1-035 GEN
Solar/Wind Harmer
3.07
3156081AA2-088 GEN
Solar/Wind Harmer
7.961
316365GEN2_N
Solar/Wind Harmer
1.652
315737AD1-076 GEN
Solar/Wind Harmer
4.654
3150401LDYSMT4
Adder
29.156
3150371LDYSMT1
Adder
28.172
962971AG1-146 GEN
Solar/Wind Harmer
4.557
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
19.023
961681AG1-008 GEN
Solar/Wind Harmer
19.023
316484AD2-074 GEN
Solar/Wind Harmer
6.058
970009AG2-005 GEN
Solar/Wind Harmer
3.008
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.225
966621AG1-532 GEN
Solar/Wind Harmer
0.485
316463AE2-346 GEN
Solar/Wind Harmer
0.387
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.986
316404AE1-155 C
Solar/Wind Harmer
4.568
3146263WOODLND
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.897
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.1
3145823KELFORD
Solar/Wind Harmer
-0.023
316478AD1-087 GEN
Solar/Wind Harmer
2.009
316486AD2-202 GEN
Solar/Wind Harmer
0.588
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
3.537
3144293JTRSVLE
Adder
0.605
972255AH1-712 GEN
Adder
74.962
3151761LOISA E
Adder
17.688
972183AH1-676 GEN
Adder
136.298
3141316ARNOLDS
Adder
0.29
316044AC1-158 PL1
Solar/Wind Helper
5.216
316450AC1-158 RIC
Solar/Wind Helper
1.391
3141196NOKESVL
Solar/Wind Helper
1.131
316303AF2-085
50/50
4.723
971285AH1-108 GEN
50/50
1.99
970603AG2-384 GEN
50/50
5.178
972263AH1-716 GEN
50/50
139.063
316233AE1-074 FULL
Solar/Wind Harmer
0.78
971281AH1-106 GEN
Solar/Wind Harmer
4.714
971283AH1-107 GEN
Solar/Wind Harmer
4.714
3143316POE
Solar/Wind Harmer
-0.108
941031AE2-094 GEN
Solar/Wind Harmer
51.106
944011AF1-069 GEN
Solar/Wind Harmer
16.013
316132AB2-190 GEN1
Solar/Wind Harmer
2.735
3151081ELIZAR1
Adder
22.034
3151091ELIZAR2
Adder
21.652
3152611GOSPORTB
Adder
3.059
3152621GOSPORTC
Adder
2.596
3152601GOSPORTA
Adder
2.395
316369SG1_INVT
Solar/Wind Harmer
4.823
971445AH1-216 GEN
Solar/Wind Harmer
16.679
972265AH1-717 GEN
Adder
18.606
3151201GRAVEL4
Adder
17.442
3151191GRAVEL3
Adder
17.221
3151211GRAVEL5
Adder
17.221
970673AG2-436 GEN
Solar/Wind Harmer
56.272
970673AG2-436 GEN
Solar/Wind Harmer
28.492
957871AF2-081 GEN
Solar/Wind Harmer
13.387
316312AB1-027
Solar/Wind Harmer
0.901
319010AE1-072 C
Solar/Wind Harmer
5.402
315833AF1-017_GEN
Solar/Wind Harmer
5.072
316349AD2-085 GEN
Solar/Wind Harmer
2.375
316311AC2-079 GEN
Solar/Wind Harmer
13.467
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.804
315835AF2-110_GEN
Solar/Wind Harmer
3.318
316315AB2-025 C
Solar/Wind Harmer
0.715
315976AC1-164 GENA
Solar/Wind Harmer
27.987
316169AC1-164_GENC
Solar/Wind Harmer
24.178
315975AC1-164 GENB
Solar/Wind Harmer
0.828
313526AB2-022
Solar/Wind Harmer
0.714
971967AH1-528 GEN
Solar/Wind Harmer
49.715
315814AE2-033 C
Solar/Wind Harmer
24.583
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.711
3146396TANGLEW
Solar/Wind Harmer
0.485
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
972189AH1-679 GEN
Adder
3.913
971167AH1-042 GEN
Solar/Wind Harmer
25.191
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
957831AF2-077 GEN
Solar/Wind Harmer
0.783
3138283WHITEMARSH
Solar/Wind Harmer
0.04
315611Z1-036_GEN2
Solar/Wind Harmer
6.367
3143873LANEXA
Solar/Wind Harmer
-0.015
316314AB2-024 C
Solar/Wind Harmer
2.185
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
316059AD1-063 C
Solar/Wind Harmer
0.576
315662AE1-191 GEN
Solar/Wind Harmer
3.067
315666AE1-190 GEN
Solar/Wind Harmer
0.767
957601AF2-054 GEN
Solar/Wind Harmer
0.758
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.742
970581AG2-369 GEN
Solar/Wind Harmer
13.538
3141913WHIT STONE
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.02
3138133OCRAN
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.952
315733AD1-074 GEN2
Solar/Wind Harmer
4.952
315735AD1-075 GEN1
Solar/Wind Harmer
2.477
965291AG1-394 GEN
Solar/Wind Harmer
2.168
3150411LDYSMT5
Adder
29.247
3150381LDYSMT2
Adder
27.99
972213AH1-691 GEN
Adder
4.735
972215AH1-692 GEN
Adder
4.735
962981AG1-147 GEN
Solar/Wind Harmer
10.632
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.614
316318V4-068
Solar/Wind Harmer
0.603
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.535
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.18
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.397
316087AB2-174 GEN
Solar/Wind Harmer
3.379
315652AC1-086 GEN
Solar/Wind Harmer
26.401
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
3141813NORNECK
Solar/Wind Harmer
-0.023
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.204
972193AH1-681 GEN
Adder
3.349
316164AC1-076 GEN
Solar/Wind Helper
1.38
316411AF1-147_GEN1
Solar/Wind Helper
0.79
316415AF1-147_GEN2
Solar/Wind Helper
0.79
3138216PACIFIC
Solar/Wind Helper
0.038
LAGNLTFEXP_LAGN->PJM
CLTF
8.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.505
TVALTFEXP_TVA->PJM
CLTF
4.252
CPLELTFEXP_CPLE->PJM
CLTF
12.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.163
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.441
MECLTFEXP_MEC->PJM
CLTF
3.751
SIGELTFEXP_SIGE->PJM
CLTF
0.114
NYPJM->LTFIMP_NY
CLTF
3.266
LGEELTFEXP_LGEE->PJM
CLTF
1.371
WECLTFEXP_WEC->PJM
CLTF
0.662

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B2_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B2_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.28 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3999.66
MW Contribution:27.25
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.634
971285AH1-108 GEN
50/50
1.469
315244AE2-183_ST
50/50
5.196
963041AG1-153 GEN
50/50
4.793
3151081ELIZAR1
50/50
17.423
3151091ELIZAR2
50/50
17.121
941591AE2-156 GEN
50/50
15.921
3152611GOSPORTB
50/50
2.419
3152621GOSPORTC
50/50
2.053
3152601GOSPORTA
50/50
1.894
315779AE2-040
50/50
2.493
316233AE1-074 FULL
Solar/Wind Harmer
0.589
971281AH1-106 GEN
Solar/Wind Harmer
3.557
971283AH1-107 GEN
Solar/Wind Harmer
3.557
941031AE2-094 GEN
Solar/Wind Harmer
39.382
944011AF1-069 GEN
Solar/Wind Harmer
12.34
970673AG2-436 GEN
Solar/Wind Harmer
43.344
970673AG2-436 GEN
Solar/Wind Harmer
21.946
3143316POE
Solar/Wind Harmer
-0.08
971967AH1-528 GEN
Solar/Wind Harmer
38.278
316315AB2-025 C
Solar/Wind Harmer
0.541
315814AE2-033 C
Solar/Wind Harmer
18.612
957871AF2-081 GEN
Solar/Wind Harmer
9.987
971445AH1-216 GEN
Solar/Wind Harmer
12.352
319010AE1-072 C
Solar/Wind Harmer
4.03
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.781
316349AD2-085 GEN
Solar/Wind Harmer
1.77
316311AC2-079 GEN
Solar/Wind Harmer
10.04
316305AF2-043 C
Solar/Wind Harmer
0.6
972265AH1-717 GEN
Adder
13.734
3151201GRAVEL4
Adder
12.875
3151191GRAVEL3
Adder
12.712
3151211GRAVEL5
Adder
12.712
316369SG1_INVT
Solar/Wind Harmer
3.546
316132AB2-190 GEN1
Solar/Wind Harmer
2.006
315835AF2-110_GEN
Solar/Wind Harmer
2.476
313526AB2-022
Solar/Wind Harmer
0.533
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.531
3146396TANGLEW
Solar/Wind Harmer
0.362
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.107
970581AG2-369 GEN
Solar/Wind Harmer
10.412
315611Z1-036_GEN2
Solar/Wind Harmer
4.76
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
19.998
316169AC1-164_GENC
Solar/Wind Harmer
17.276
315975AC1-164 GENB
Solar/Wind Harmer
0.592
957831AF2-077 GEN
Solar/Wind Harmer
0.569
3138283WHITEMARSH
Solar/Wind Harmer
0.029
971167AH1-042 GEN
Solar/Wind Harmer
18.178
316312AB1-027
Solar/Wind Harmer
0.636
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315816AE2-034 GEN
Solar/Wind Harmer
1.513
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.714
315733AD1-074 GEN2
Solar/Wind Harmer
3.714
315735AD1-075 GEN1
Solar/Wind Harmer
1.858
965291AG1-394 GEN
Solar/Wind Harmer
1.63
316314AB2-024 C
Solar/Wind Harmer
1.568
315662AE1-191 GEN
Solar/Wind Harmer
2.207
315666AE1-190 GEN
Solar/Wind Harmer
0.552
316059AD1-063 C
Solar/Wind Harmer
0.414
957601AF2-054 GEN
Solar/Wind Harmer
0.546
3141873WAN 176
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.968
316318V4-068
Solar/Wind Harmer
0.454
3145893MURPHYS
Solar/Wind Harmer
-0.049
3145893MURPHYS
Solar/Wind Harmer
-0.018
946281AF1-292 GEN
Solar/Wind Harmer
0.405
3145513AHOSKIE
Solar/Wind Harmer
0.157
961941AG1-037 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
316087AB2-174 GEN
Solar/Wind Harmer
2.556
972189AH1-679 GEN
Adder
2.672
3138133OCRAN
Solar/Wind Harmer
-0.005
315607AA1-063A GEN
Solar/Wind Harmer
1.808
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
315652AC1-086 GEN
Solar/Wind Harmer
19.944
3137643SOCKMAN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
7.617
3146033SCOT NK
Solar/Wind Harmer
-0.069
970831AG2-522 GEN
Solar/Wind Harmer
8.501
3150411LDYSMT5
Adder
18.406
3150381LDYSMT2
Adder
17.615
972213AH1-691 GEN
Adder
2.98
972215AH1-692 GEN
Adder
2.98
972205AH1-687 GEN
Adder
5.489
316164AC1-076 GEN
Solar/Wind Helper
1.636
3152261N ANNA2
50/50
17.597
3150861SPRUNCD
50/50
0.898
3151031BRUNSWICKG2
50/50
2.367
3151101ELIZAR3
50/50
17.646
3147666LOUISA
Solar/Wind Harmer
-0.057
315773AC2-141 GEN
Solar/Wind Harmer
8.509
315839AE2-212 C
Solar/Wind Harmer
0.609
944581AF1-123 GEN
Solar/Wind Harmer
91.816
944601AF1-125 GEN
Solar/Wind Harmer
90.383
315813AE1-149 C
Solar/Wind Harmer
12.605
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
2.513
970659AG2-427 GEN
Solar/Wind Harmer
1.891
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.257
970661AG2-428 GEN
Solar/Wind Harmer
3.77
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.43
3151221GRAVEL6
Adder
12.86
3151171GRAVELC
Adder
2.474
961611AG1-000B GEN
Solar/Wind Harmer
4.183
315778AD1-151 GEN
Solar/Wind Harmer
17.189
970129AG2-093 GEN
Solar/Wind Harmer
11.167
970133AG2-095 GEN
Solar/Wind Harmer
2.23
3143096IRON208
Adder
0.737
3143096IRON208
Adder
0.722
316320Y1-086
Solar/Wind Harmer
1.158
3144216WINCHST
Adder
0.657
316435W1029_GEN3
Solar/Wind Harmer
3.546
316313AB2-026
Solar/Wind Harmer
0.527
316258AE1-075 C
Solar/Wind Harmer
0.475
316405AF2-144 C
Solar/Wind Harmer
0.501
3143336POWHATN
Solar/Wind Harmer
1.973
3146516WINFALL
Solar/Wind Harmer
-0.019
3150921YORKTN3
Adder
4.366
970917AG2-570 GEN
Solar/Wind Harmer
48.634
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
3142946ENON
Solar/Wind Harmer
-0.006
316382AG1-145 C
Solar/Wind Harmer
0.582
970293AG2-193 GEN
Solar/Wind Harmer
2.398
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.904
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315614AA2-178 GEN
Solar/Wind Harmer
2.017
316365GEN2_N
Solar/Wind Harmer
1.25
3156081AA2-088 GEN
Solar/Wind Harmer
5.982
971157AH1-035 GEN
Solar/Wind Harmer
2.302
315737AD1-076 GEN
Solar/Wind Harmer
3.491
3141843SHACKLE
Adder
0.835
316203AE2-005 GEN
Solar/Wind Harmer
7.74
316280AD1-041 GEN
Solar/Wind Harmer
1.38
3141766HARMONY
Solar/Wind Harmer
1.629
316156AD2-030 GEN
Solar/Wind Harmer
0.487
3141873WAN 176
Solar/Wind Harmer
2.165
3146206CASHIE
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.127
3145893MURPHYS
Solar/Wind Harmer
-0.018
316473AC1-191 GEN
Solar/Wind Harmer
1.956
957521AF2-046 GEN
Solar/Wind Harmer
14.304
961681AG1-008 GEN
Solar/Wind Harmer
14.304
966621AG1-532 GEN
Solar/Wind Harmer
0.367
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.424
316463AE2-346 GEN
Solar/Wind Harmer
0.291
316140AB2-099
Solar/Wind Harmer
0.121
962331AG1-082 GEN
Solar/Wind Harmer
2.246
313506AB2-031 GEN
Solar/Wind Harmer
1.435
3146263WOODLND
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.541
316486AD2-202 GEN
Solar/Wind Harmer
0.451
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145963POPLR C
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.829
3145823KELFORD
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.017
962971AG1-146 GEN
Solar/Wind Harmer
3.264
316484AD2-074 GEN
Solar/Wind Harmer
4.335
970009AG2-005 GEN
Solar/Wind Harmer
2.153
316210AC1-098 GEN
Solar/Wind Harmer
2.67
970909AG2-566 GEN
Solar/Wind Harmer
1.611
3152251N ANNA1
50/50
17.599
970119AG2-088 GEN
50/50
27.254
3150851SPRUNCC
50/50
0.898
315243AE2-183_GT3
50/50
3.006
3151051BRUNSWICKS1
50/50
4.913
3151021BRUNSWICKG1
50/50
2.367
971451AH1-221 GEN
50/50
7.19
3150981CHESPKA
50/50
2.372
3147666LOUISA
Solar/Wind Harmer
-0.099
316192AB2-158 GEN
Solar/Wind Harmer
2.866
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.113
940641AE2-051 GEN
Solar/Wind Harmer
20.147
939411AE1-173 GEN
Solar/Wind Harmer
105.7
316294AC1-161 GEN
Solar/Wind Harmer
6.579
944591AF1-124 GEN
Solar/Wind Harmer
92.147
316375AC2-012 GEN
Solar/Wind Harmer
6.96
970659AG2-427 GEN
Solar/Wind Harmer
10.669
316381AD1-082 GEN
Solar/Wind Harmer
1.84
315671AE2-027_GEN
Solar/Wind Harmer
15.038
970661AG2-428 GEN
Solar/Wind Harmer
21.272
3142543TWELFTH
Solar/Wind Harmer
-0.002
316388AE2-253 GEN
Solar/Wind Harmer
1.348
3145336SMITFLD
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.403
3151171GRAVELC
Adder
1.882
316072AD1-144
Solar/Wind Harmer
0.402
961611AG1-000B GEN
Solar/Wind Harmer
9.803
971647AH1-324 GEN
Solar/Wind Harmer
9.928
971069AG2-661 GEN
Solar/Wind Harmer
3.14
316458AB2-190 GEN2
Solar/Wind Harmer
2.006
970129AG2-093 GEN
Solar/Wind Harmer
4.523
316093AE2-104_GEN
Solar/Wind Harmer
5.759
3143096IRON208
Adder
0.737
3143336POWHATN
Solar/Wind Harmer
2.321
3138126ROCKLANDING
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
-0.063
3146516WINFALL
Solar/Wind Harmer
-0.019
944631AF1-128 GEN
Adder
82.804
970919AG2-571 GEN
Solar/Wind Harmer
6.156
970087AG2-069 GEN
Solar/Wind Harmer
18.16
971317AH1-138 GEN
Solar/Wind Harmer
2.416
316159AE1-175 C
Solar/Wind Harmer
0.519
315800Z1-036_GEN1
Solar/Wind Harmer
4.76
3130156CHOWAN
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142433PROV 92
Solar/Wind Harmer
-0.075
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3145663CRESWEL
Solar/Wind Harmer
-0.052
971163AH1-040 GEN
Solar/Wind Harmer
17.53
316336AC2-165 C
Solar/Wind Harmer
3.244
316023GEN1_S
Solar/Wind Harmer
1.25
957481AF2-042 GEN
Solar/Wind Harmer
57.87
971777AH1-397 GEN
Solar/Wind Harmer
2.159
3141843SHACKLE
Adder
0.835
3141766HARMONY
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.553
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.54
315693AD1-088 GEN
Solar/Wind Harmer
9.06
960081AF2-299 GEN
Solar/Wind Harmer
2.034
962491AG1-098 GEN
Solar/Wind Harmer
12.078
3146173TUNIS
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.31
316011AB1-132 GEN
Solar/Wind Harmer
3.709
962571AG1-106 GEN
Solar/Wind Harmer
2.548
316190AA2-174 GEN
Solar/Wind Harmer
0.217
3147043LAWRENC
Adder
1.417
3145963POPLR C
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.017
316174AB2-169 GEN
Solar/Wind Harmer
2.689
961951AG1-038 GEN
Solar/Wind Harmer
2.268
316212AC1-099_GEN
Solar/Wind Harmer
1.483
962861AG1-135 GEN
Solar/Wind Harmer
6.373
316129AC1-054 GEN
Solar/Wind Harmer
1.485
3150351NORNECKC2
Adder
1.452
3144293JTRSVLE
Adder
0.462
972197AH1-683 GEN
Adder
2.865
972219AH1-694 GEN
Adder
2.063
316045AC1-158 PL2
Solar/Wind Helper
17.173
316006AB2-029 C
Solar/Wind Helper
0.112
971133AH1-012 GEN
50/50
4.727
970533AG2-339 GEN
50/50
16.617
970531AG2-338 GEN
50/50
6.647
315242AE2-183_GT2
50/50
3.006
315241AE2-183_GT1
50/50
2.987
972185AH1-677 GEN
50/50
10.835
3151041BRUNSWICKG3
50/50
2.367
972187AH1-678 GEN
50/50
5.432
3150991CHESPKB
50/50
1.99
3150991CHESPKB
50/50
1.942
971223AH1-071 GEN
Solar/Wind Harmer
2.871
3143526WINTERP
Solar/Wind Harmer
-0.113
316036AC1-147 C
Solar/Wind Harmer
0.543
3142956BIRDNECK
Solar/Wind Harmer
1.078
316316AC1-027 C
Solar/Wind Harmer
0.617
316185AD1-033 GEN
Solar/Wind Harmer
2.119
316240AF1-291 C
Solar/Wind Harmer
0.605
3144356SAPONY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
-0.08
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.265
970657AG2-426 GEN
Solar/Wind Harmer
1.31
944641AF1-129 GEN
Adder
84.93
316339AD2-160 GEN
Solar/Wind Harmer
1.348
316018AA1-139 ULT2
Solar/Wind Harmer
1.711
316017AA1-139 ULT1
Solar/Wind Harmer
1.616
316236AE1-162_GEN
Solar/Wind Harmer
0.602
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.355
3130086AYDLETT
Solar/Wind Harmer
-0.079
970933AG2-581 GEN
Solar/Wind Harmer
18.608
316033AB2-134 GEN
Solar/Wind Harmer
6.401
315697AD1-025 GEN
Solar/Wind Harmer
4.014
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.546
316433W1029_GEN2
Solar/Wind Harmer
3.546
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3142366NRTHEST
Adder
0.565
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.388
3150701DARBY 4
Adder
12.359
3150681DARBY 2
Adder
12.344
3150671DARBY 1
Adder
12.33
315742AE1-103 GEN
Solar/Wind Harmer
2.005
3146376EDENTON
Solar/Wind Harmer
0.566
3146376EDENTON
Solar/Wind Harmer
0.566
316075AC2-137 C
Solar/Wind Harmer
0.513
3142296MT RD221
Adder
0.537
970099AG2-077 GEN
Solar/Wind Harmer
23.148
316441AF1-014 GEN
Solar/Wind Harmer
1.237
316065AD1-022 GEN
Solar/Wind Harmer
9.134
3145893MURPHYS
Solar/Wind Harmer
0.508
3145893MURPHYS
Solar/Wind Harmer
-0.033
966871AG1-558 GEN
Solar/Wind Harmer
0.547
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
316181AB2-040 GEN
Solar/Wind Harmer
2.49
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.782
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
1.979
3145593CAROLNA
Solar/Wind Harmer
0.146
3145783HORNRTN
Solar/Wind Harmer
2.075
3145783HORNRTN
Solar/Wind Harmer
1.66
3145783HORNRTN
Solar/Wind Harmer
0.519
3145783HORNRTN
Solar/Wind Harmer
0.207
3145796HORNRTN
Solar/Wind Harmer
-0.052
971741AH1-377 GEN
Solar/Wind Harmer
20.037
316487AF1-042 GEN
Solar/Wind Harmer
2.268
970301AG2-198 GEN
Solar/Wind Harmer
8.487
316274AC1-208 GEN
Solar/Wind Harmer
1.826
3150341NORNECKC1
Adder
1.525
3150341NORNECKC1
Adder
1.513
3144293JTRSVLE
Adder
0.462
3144293JTRSVLE
Adder
0.389
3150391LDYSMT3
Adder
18.314
972195AH1-682 GEN
Adder
2.407
316447AC1-158 HLD
Solar/Wind Helper
11.807
958261AF2-120 GEN
Solar/Wind Harmer
3.594
316404AE1-155 C
Solar/Wind Harmer
3.263
3150351NORNECKC2
Adder
1.476
3144293JTRSVLE
Adder
0.462
3150401LDYSMT4
Adder
18.348
3150371LDYSMT1
Adder
17.729
316044AC1-158 PL1
Solar/Wind Helper
5.365
316450AC1-158 RIC
Solar/Wind Helper
1.431
LAGNLTFEXP_LAGN->PJM
CLTF
6.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.05
TVALTFEXP_TVA->PJM
CLTF
3.173
CPLELTFEXP_CPLE->PJM
CLTF
9.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.753
MECLTFEXP_MEC->PJM
CLTF
2.757
SIGELTFEXP_SIGE->PJM
CLTF
0.083
NYPJM->LTFIMP_NY
CLTF
2.427
LGEELTFEXP_LGEE->PJM
CLTF
1
WECLTFEXP_WEC->PJM
CLTF
0.483

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B1_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.28 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3999.66
MW Contribution:27.25
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.634
971285AH1-108 GEN
50/50
1.469
315244AE2-183_ST
50/50
5.196
963041AG1-153 GEN
50/50
4.793
3151081ELIZAR1
50/50
17.423
3151091ELIZAR2
50/50
17.121
941591AE2-156 GEN
50/50
15.921
3152611GOSPORTB
50/50
2.419
3152621GOSPORTC
50/50
2.053
3152601GOSPORTA
50/50
1.894
315779AE2-040
50/50
2.493
316233AE1-074 FULL
Solar/Wind Harmer
0.589
971281AH1-106 GEN
Solar/Wind Harmer
3.557
971283AH1-107 GEN
Solar/Wind Harmer
3.557
941031AE2-094 GEN
Solar/Wind Harmer
39.382
944011AF1-069 GEN
Solar/Wind Harmer
12.34
970673AG2-436 GEN
Solar/Wind Harmer
43.344
970673AG2-436 GEN
Solar/Wind Harmer
21.946
3143316POE
Solar/Wind Harmer
-0.08
971967AH1-528 GEN
Solar/Wind Harmer
38.278
316315AB2-025 C
Solar/Wind Harmer
0.541
315814AE2-033 C
Solar/Wind Harmer
18.612
957871AF2-081 GEN
Solar/Wind Harmer
9.987
971445AH1-216 GEN
Solar/Wind Harmer
12.352
319010AE1-072 C
Solar/Wind Harmer
4.03
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.781
316349AD2-085 GEN
Solar/Wind Harmer
1.77
316311AC2-079 GEN
Solar/Wind Harmer
10.04
316305AF2-043 C
Solar/Wind Harmer
0.6
972265AH1-717 GEN
Adder
13.734
3151201GRAVEL4
Adder
12.875
3151191GRAVEL3
Adder
12.712
3151211GRAVEL5
Adder
12.712
316369SG1_INVT
Solar/Wind Harmer
3.546
316132AB2-190 GEN1
Solar/Wind Harmer
2.006
315835AF2-110_GEN
Solar/Wind Harmer
2.476
313526AB2-022
Solar/Wind Harmer
0.533
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.531
3146396TANGLEW
Solar/Wind Harmer
0.362
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.107
970581AG2-369 GEN
Solar/Wind Harmer
10.412
315611Z1-036_GEN2
Solar/Wind Harmer
4.76
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
19.998
316169AC1-164_GENC
Solar/Wind Harmer
17.276
315975AC1-164 GENB
Solar/Wind Harmer
0.592
957831AF2-077 GEN
Solar/Wind Harmer
0.569
3138283WHITEMARSH
Solar/Wind Harmer
0.029
971167AH1-042 GEN
Solar/Wind Harmer
18.178
316312AB1-027
Solar/Wind Harmer
0.636
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315816AE2-034 GEN
Solar/Wind Harmer
1.513
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.714
315733AD1-074 GEN2
Solar/Wind Harmer
3.714
315735AD1-075 GEN1
Solar/Wind Harmer
1.858
965291AG1-394 GEN
Solar/Wind Harmer
1.63
316314AB2-024 C
Solar/Wind Harmer
1.568
315662AE1-191 GEN
Solar/Wind Harmer
2.207
315666AE1-190 GEN
Solar/Wind Harmer
0.552
316059AD1-063 C
Solar/Wind Harmer
0.414
957601AF2-054 GEN
Solar/Wind Harmer
0.546
3141873WAN 176
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.968
316318V4-068
Solar/Wind Harmer
0.454
3145893MURPHYS
Solar/Wind Harmer
-0.049
3145893MURPHYS
Solar/Wind Harmer
-0.018
946281AF1-292 GEN
Solar/Wind Harmer
0.405
3145513AHOSKIE
Solar/Wind Harmer
0.157
961941AG1-037 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
316087AB2-174 GEN
Solar/Wind Harmer
2.556
972189AH1-679 GEN
Adder
2.672
3152251N ANNA1
50/50
17.599
970119AG2-088 GEN
50/50
27.254
3150851SPRUNCC
50/50
0.898
315243AE2-183_GT3
50/50
3.006
3151051BRUNSWICKS1
50/50
4.913
3151021BRUNSWICKG1
50/50
2.367
971451AH1-221 GEN
50/50
7.19
3150981CHESPKA
50/50
2.372
3147666LOUISA
Solar/Wind Harmer
-0.099
316192AB2-158 GEN
Solar/Wind Harmer
2.866
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.113
940641AE2-051 GEN
Solar/Wind Harmer
20.147
939411AE1-173 GEN
Solar/Wind Harmer
105.7
316294AC1-161 GEN
Solar/Wind Harmer
6.579
944591AF1-124 GEN
Solar/Wind Harmer
92.147
316375AC2-012 GEN
Solar/Wind Harmer
6.96
970659AG2-427 GEN
Solar/Wind Harmer
10.669
316381AD1-082 GEN
Solar/Wind Harmer
1.84
315671AE2-027_GEN
Solar/Wind Harmer
15.038
970661AG2-428 GEN
Solar/Wind Harmer
21.272
3142543TWELFTH
Solar/Wind Harmer
-0.002
316388AE2-253 GEN
Solar/Wind Harmer
1.348
3145336SMITFLD
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.403
3151171GRAVELC
Adder
1.882
316072AD1-144
Solar/Wind Harmer
0.402
961611AG1-000B GEN
Solar/Wind Harmer
9.803
971647AH1-324 GEN
Solar/Wind Harmer
9.928
971069AG2-661 GEN
Solar/Wind Harmer
3.14
316458AB2-190 GEN2
Solar/Wind Harmer
2.006
970129AG2-093 GEN
Solar/Wind Harmer
4.523
316093AE2-104_GEN
Solar/Wind Harmer
5.759
3143096IRON208
Adder
0.737
3143336POWHATN
Solar/Wind Harmer
2.321
3138126ROCKLANDING
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
-0.063
3146516WINFALL
Solar/Wind Harmer
-0.019
944631AF1-128 GEN
Adder
82.804
970919AG2-571 GEN
Solar/Wind Harmer
6.156
970087AG2-069 GEN
Solar/Wind Harmer
18.16
971317AH1-138 GEN
Solar/Wind Harmer
2.416
316159AE1-175 C
Solar/Wind Harmer
0.519
315800Z1-036_GEN1
Solar/Wind Harmer
4.76
3130156CHOWAN
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142433PROV 92
Solar/Wind Harmer
-0.075
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3145663CRESWEL
Solar/Wind Harmer
-0.052
971163AH1-040 GEN
Solar/Wind Harmer
17.53
316336AC2-165 C
Solar/Wind Harmer
3.244
316023GEN1_S
Solar/Wind Harmer
1.25
957481AF2-042 GEN
Solar/Wind Harmer
57.87
971777AH1-397 GEN
Solar/Wind Harmer
2.159
3141843SHACKLE
Adder
0.835
3141766HARMONY
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.553
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.54
315693AD1-088 GEN
Solar/Wind Harmer
9.06
960081AF2-299 GEN
Solar/Wind Harmer
2.034
962491AG1-098 GEN
Solar/Wind Harmer
12.078
3146173TUNIS
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.31
316011AB1-132 GEN
Solar/Wind Harmer
3.709
962571AG1-106 GEN
Solar/Wind Harmer
2.548
316190AA2-174 GEN
Solar/Wind Harmer
0.217
3147043LAWRENC
Adder
1.417
3145963POPLR C
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.017
316174AB2-169 GEN
Solar/Wind Harmer
2.689
961951AG1-038 GEN
Solar/Wind Harmer
2.268
316212AC1-099_GEN
Solar/Wind Harmer
1.483
962861AG1-135 GEN
Solar/Wind Harmer
6.373
316129AC1-054 GEN
Solar/Wind Harmer
1.485
3150351NORNECKC2
Adder
1.452
3144293JTRSVLE
Adder
0.462
972197AH1-683 GEN
Adder
2.865
972219AH1-694 GEN
Adder
2.063
316045AC1-158 PL2
Solar/Wind Helper
17.173
316006AB2-029 C
Solar/Wind Helper
0.112
971133AH1-012 GEN
50/50
4.727
970533AG2-339 GEN
50/50
16.617
970531AG2-338 GEN
50/50
6.647
315242AE2-183_GT2
50/50
3.006
315241AE2-183_GT1
50/50
2.987
972185AH1-677 GEN
50/50
10.835
3151041BRUNSWICKG3
50/50
2.367
972187AH1-678 GEN
50/50
5.432
3150991CHESPKB
50/50
1.99
3150991CHESPKB
50/50
1.942
971223AH1-071 GEN
Solar/Wind Harmer
2.871
3143526WINTERP
Solar/Wind Harmer
-0.113
316036AC1-147 C
Solar/Wind Harmer
0.543
3142956BIRDNECK
Solar/Wind Harmer
1.078
316316AC1-027 C
Solar/Wind Harmer
0.617
316185AD1-033 GEN
Solar/Wind Harmer
2.119
316240AF1-291 C
Solar/Wind Harmer
0.605
3144356SAPONY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
-0.08
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.265
970657AG2-426 GEN
Solar/Wind Harmer
1.31
944641AF1-129 GEN
Adder
84.93
316339AD2-160 GEN
Solar/Wind Harmer
1.348
316018AA1-139 ULT2
Solar/Wind Harmer
1.711
316017AA1-139 ULT1
Solar/Wind Harmer
1.616
316236AE1-162_GEN
Solar/Wind Harmer
0.602
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.355
3130086AYDLETT
Solar/Wind Harmer
-0.079
970933AG2-581 GEN
Solar/Wind Harmer
18.608
316033AB2-134 GEN
Solar/Wind Harmer
6.401
315697AD1-025 GEN
Solar/Wind Harmer
4.014
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.546
316433W1029_GEN2
Solar/Wind Harmer
3.546
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3142366NRTHEST
Adder
0.565
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.388
3150701DARBY 4
Adder
12.359
3150681DARBY 2
Adder
12.344
3150671DARBY 1
Adder
12.33
315742AE1-103 GEN
Solar/Wind Harmer
2.005
3146376EDENTON
Solar/Wind Harmer
0.566
3146376EDENTON
Solar/Wind Harmer
0.566
316075AC2-137 C
Solar/Wind Harmer
0.513
3142296MT RD221
Adder
0.537
970099AG2-077 GEN
Solar/Wind Harmer
23.148
316441AF1-014 GEN
Solar/Wind Harmer
1.237
316065AD1-022 GEN
Solar/Wind Harmer
9.134
3145893MURPHYS
Solar/Wind Harmer
0.508
3145893MURPHYS
Solar/Wind Harmer
-0.033
966871AG1-558 GEN
Solar/Wind Harmer
0.547
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
316181AB2-040 GEN
Solar/Wind Harmer
2.49
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.782
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
1.979
3145593CAROLNA
Solar/Wind Harmer
0.146
3145783HORNRTN
Solar/Wind Harmer
2.075
3145783HORNRTN
Solar/Wind Harmer
1.66
3145783HORNRTN
Solar/Wind Harmer
0.519
3145783HORNRTN
Solar/Wind Harmer
0.207
3145796HORNRTN
Solar/Wind Harmer
-0.052
971741AH1-377 GEN
Solar/Wind Harmer
20.037
316487AF1-042 GEN
Solar/Wind Harmer
2.268
970301AG2-198 GEN
Solar/Wind Harmer
8.487
316274AC1-208 GEN
Solar/Wind Harmer
1.826
3150341NORNECKC1
Adder
1.525
3150341NORNECKC1
Adder
1.513
3144293JTRSVLE
Adder
0.462
3144293JTRSVLE
Adder
0.389
3150391LDYSMT3
Adder
18.314
972195AH1-682 GEN
Adder
2.407
316447AC1-158 HLD
Solar/Wind Helper
11.807
958261AF2-120 GEN
Solar/Wind Harmer
3.594
3138133OCRAN
Solar/Wind Harmer
-0.005
315607AA1-063A GEN
Solar/Wind Harmer
1.808
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
315652AC1-086 GEN
Solar/Wind Harmer
19.944
3137643SOCKMAN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
7.617
3146033SCOT NK
Solar/Wind Harmer
-0.069
970831AG2-522 GEN
Solar/Wind Harmer
8.501
3150411LDYSMT5
Adder
18.406
3150381LDYSMT2
Adder
17.615
972213AH1-691 GEN
Adder
2.98
972215AH1-692 GEN
Adder
2.98
972205AH1-687 GEN
Adder
5.489
316164AC1-076 GEN
Solar/Wind Helper
1.636
3152261N ANNA2
50/50
17.597
3150861SPRUNCD
50/50
0.898
3151031BRUNSWICKG2
50/50
2.367
3151101ELIZAR3
50/50
17.646
3147666LOUISA
Solar/Wind Harmer
-0.057
315773AC2-141 GEN
Solar/Wind Harmer
8.509
315839AE2-212 C
Solar/Wind Harmer
0.609
944581AF1-123 GEN
Solar/Wind Harmer
91.816
944601AF1-125 GEN
Solar/Wind Harmer
90.383
315813AE1-149 C
Solar/Wind Harmer
12.605
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
2.513
970659AG2-427 GEN
Solar/Wind Harmer
1.891
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.257
970661AG2-428 GEN
Solar/Wind Harmer
3.77
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.43
3151221GRAVEL6
Adder
12.86
3151171GRAVELC
Adder
2.474
961611AG1-000B GEN
Solar/Wind Harmer
4.183
315778AD1-151 GEN
Solar/Wind Harmer
17.189
970129AG2-093 GEN
Solar/Wind Harmer
11.167
970133AG2-095 GEN
Solar/Wind Harmer
2.23
3143096IRON208
Adder
0.737
3143096IRON208
Adder
0.722
316320Y1-086
Solar/Wind Harmer
1.158
3144216WINCHST
Adder
0.657
316435W1029_GEN3
Solar/Wind Harmer
3.546
316313AB2-026
Solar/Wind Harmer
0.527
316258AE1-075 C
Solar/Wind Harmer
0.475
316405AF2-144 C
Solar/Wind Harmer
0.501
3143336POWHATN
Solar/Wind Harmer
1.973
3146516WINFALL
Solar/Wind Harmer
-0.019
3150921YORKTN3
Adder
4.366
970917AG2-570 GEN
Solar/Wind Harmer
48.634
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
3142946ENON
Solar/Wind Harmer
-0.006
316382AG1-145 C
Solar/Wind Harmer
0.582
970293AG2-193 GEN
Solar/Wind Harmer
2.398
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.904
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315614AA2-178 GEN
Solar/Wind Harmer
2.017
316365GEN2_N
Solar/Wind Harmer
1.25
3156081AA2-088 GEN
Solar/Wind Harmer
5.982
971157AH1-035 GEN
Solar/Wind Harmer
2.302
315737AD1-076 GEN
Solar/Wind Harmer
3.491
3141843SHACKLE
Adder
0.835
316203AE2-005 GEN
Solar/Wind Harmer
7.74
316280AD1-041 GEN
Solar/Wind Harmer
1.38
3141766HARMONY
Solar/Wind Harmer
1.629
316156AD2-030 GEN
Solar/Wind Harmer
0.487
3141873WAN 176
Solar/Wind Harmer
2.165
3146206CASHIE
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.127
3145893MURPHYS
Solar/Wind Harmer
-0.018
316473AC1-191 GEN
Solar/Wind Harmer
1.956
957521AF2-046 GEN
Solar/Wind Harmer
14.304
961681AG1-008 GEN
Solar/Wind Harmer
14.304
966621AG1-532 GEN
Solar/Wind Harmer
0.367
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.424
316463AE2-346 GEN
Solar/Wind Harmer
0.291
316140AB2-099
Solar/Wind Harmer
0.121
962331AG1-082 GEN
Solar/Wind Harmer
2.246
313506AB2-031 GEN
Solar/Wind Harmer
1.435
3146263WOODLND
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.541
316486AD2-202 GEN
Solar/Wind Harmer
0.451
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145963POPLR C
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.829
3145823KELFORD
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.017
962971AG1-146 GEN
Solar/Wind Harmer
3.264
316484AD2-074 GEN
Solar/Wind Harmer
4.335
970009AG2-005 GEN
Solar/Wind Harmer
2.153
316210AC1-098 GEN
Solar/Wind Harmer
2.67
970909AG2-566 GEN
Solar/Wind Harmer
1.611
316404AE1-155 C
Solar/Wind Harmer
3.263
3150351NORNECKC2
Adder
1.476
3144293JTRSVLE
Adder
0.462
3150401LDYSMT4
Adder
18.348
3150371LDYSMT1
Adder
17.729
316044AC1-158 PL1
Solar/Wind Helper
5.365
316450AC1-158 RIC
Solar/Wind Helper
1.431
LAGNLTFEXP_LAGN->PJM
CLTF
6.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.05
TVALTFEXP_TVA->PJM
CLTF
3.173
CPLELTFEXP_CPLE->PJM
CLTF
9.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.753
MECLTFEXP_MEC->PJM
CLTF
2.757
SIGELTFEXP_SIGE->PJM
CLTF
0.083
NYPJM->LTFIMP_NY
CLTF
2.427
LGEELTFEXP_LGEE->PJM
CLTF
1
WECLTFEXP_WEC->PJM
CLTF
0.483

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.49 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3783.56
MW Contribution:27.25
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
17.599
970119AG2-088 GEN
50/50
27.254
3150851SPRUNCC
50/50
0.898
315243AE2-183_GT3
50/50
3.006
3151051BRUNSWICKS1
50/50
4.913
3151021BRUNSWICKG1
50/50
2.367
971451AH1-221 GEN
50/50
7.19
3150981CHESPKA
50/50
2.372
3147666LOUISA
Solar/Wind Harmer
0.882
316192AB2-158 GEN
Solar/Wind Harmer
1.212
3143226MDLTHAN
Solar/Wind Harmer
0.204
3143526WINTERP
Solar/Wind Harmer
1.012
940641AE2-051 GEN
Solar/Wind Harmer
15.302
939411AE1-173 GEN
Solar/Wind Harmer
80.278
316294AC1-161 GEN
Solar/Wind Harmer
3.136
944591AF1-124 GEN
Solar/Wind Harmer
40.591
316375AC2-012 GEN
Solar/Wind Harmer
0.005
970659AG2-427 GEN
Solar/Wind Harmer
8.643
316381AD1-082 GEN
Solar/Wind Harmer
0.186
315671AE2-027_GEN
Solar/Wind Harmer
11.421
970661AG2-428 GEN
Solar/Wind Harmer
17.724
3142543TWELFTH
Solar/Wind Harmer
0.017
316388AE2-253 GEN
Solar/Wind Harmer
0.557
3145336SMITFLD
Solar/Wind Harmer
0.711
3146456SLIGO L269
Solar/Wind Harmer
0.177
316246AF1-032 C
Solar/Wind Harmer
0.08
3151171GRAVELC
Adder
1.882
316072AD1-144
Solar/Wind Harmer
0.064
961611AG1-000B GEN
Solar/Wind Harmer
9.271
971647AH1-324 GEN
Solar/Wind Harmer
7.54
971069AG2-661 GEN
Solar/Wind Harmer
3.14
316458AB2-190 GEN2
Solar/Wind Harmer
0.947
970129AG2-093 GEN
Solar/Wind Harmer
5.021
316093AE2-104_GEN
Solar/Wind Harmer
2.965
3143096IRON208
Adder
0.737
3143336POWHATN
Solar/Wind Harmer
3.095
3138126ROCKLANDING
Solar/Wind Harmer
0.08
3146516WINFALL
Solar/Wind Harmer
0.563
3146516WINFALL
Solar/Wind Harmer
0.174
944631AF1-128 GEN
Adder
82.804
970919AG2-571 GEN
Solar/Wind Harmer
6.156
970087AG2-069 GEN
Solar/Wind Harmer
13.793
971317AH1-138 GEN
Solar/Wind Harmer
1.284
316159AE1-175 C
Solar/Wind Harmer
0.148
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.17
3142416OLDCHRC
Solar/Wind Harmer
0.437
3142416OLDCHRC
Solar/Wind Harmer
0.167
3142433PROV 92
Solar/Wind Harmer
0.669
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3145663CRESWEL
Solar/Wind Harmer
0.466
971163AH1-040 GEN
Solar/Wind Harmer
13.314
316336AC2-165 C
Solar/Wind Harmer
0.006
316023GEN1_S
Solar/Wind Harmer
0.37
957481AF2-042 GEN
Solar/Wind Harmer
43.952
971777AH1-397 GEN
Solar/Wind Harmer
0.431
3141843SHACKLE
Adder
0.835
3141766HARMONY
Solar/Wind Harmer
0.033
3146206CASHIE
Solar/Wind Harmer
0.162
971547AH1-271 GEN
Solar/Wind Harmer
3.458
3145893MURPHYS
Solar/Wind Harmer
0.648
3145893MURPHYS
Solar/Wind Harmer
0.72
315693AD1-088 GEN
Solar/Wind Harmer
7.741
960081AF2-299 GEN
Solar/Wind Harmer
1.545
962491AG1-098 GEN
Solar/Wind Harmer
9.173
3146173TUNIS
Solar/Wind Harmer
0.161
3138133OCRAN
Solar/Wind Harmer
0.096
3145683EARLEYS
Solar/Wind Harmer
0.159
3146263WOODLND
Solar/Wind Harmer
0.158
971795AH1-408 GEN
Solar/Wind Harmer
10.53
316011AB1-132 GEN
Solar/Wind Harmer
2.868
962571AG1-106 GEN
Solar/Wind Harmer
2.244
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
1.417
3145963POPLR C
Solar/Wind Harmer
0.156
3145823KELFORD
Solar/Wind Harmer
0.156
3145783HORNRTN
Solar/Wind Harmer
0.155
3145796HORNRTN
Solar/Wind Harmer
0.512
3145796HORNRTN
Solar/Wind Harmer
0.155
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316212AC1-099_GEN
Solar/Wind Harmer
0.783
962861AG1-135 GEN
Solar/Wind Harmer
4.841
316129AC1-054 GEN
Solar/Wind Harmer
0.567
3146293MARTNCO
Solar/Wind Harmer
0.139
971065AG2-659 GEN
Solar/Wind Harmer
6.41
315687AD1-152 GEN
Solar/Wind Harmer
0.005
3141726DUNNSVL
Solar/Wind Harmer
0.591
315722AD1-056 GEN
Solar/Wind Harmer
0.935
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
966881AG1-559 GEN
Solar/Wind Harmer
0.17
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970937AG2-583 GEN
Solar/Wind Harmer
8.939
3150351NORNECKC2
Adder
1.452
316494AC1-189 GEN
Solar/Wind Harmer
0.491
970685AG2-442 GEN
Solar/Wind Harmer
10.862
963171AG1-166 GEN
Solar/Wind Harmer
0.774
971563AH1-280 GEN
Solar/Wind Harmer
1.548
3144293JTRSVLE
Adder
0.462
3146233WITAKRS
Solar/Wind Harmer
0.573
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.144
3145493TOT1
Solar/Wind Harmer
0.639
3146926FARMVIL
Solar/Wind Harmer
0.086
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.113
316359AB2-059 GEN
Solar/Wind Harmer
0.508
316049AB1-081 GEN
Solar/Wind Harmer
0.809
3142053HEARTS
Solar/Wind Harmer
0.249
970401AG2-262 GEN
Solar/Wind Harmer
0.817
316337AD2-073 GEN
Solar/Wind Harmer
0.12
972197AH1-683 GEN
Adder
2.865
972219AH1-694 GEN
Adder
2.063
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
972003AH1-546 GEN
Solar/Wind Harmer
5.523
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.278
3147623JAMES R
Solar/Wind Harmer
0.278
972135AH1-637 GEN
Solar/Wind Harmer
0.998
316045AC1-158 PL2
Solar/Wind Helper
17.173
316006AB2-029 C
Solar/Wind Helper
0.112
3152261N ANNA2
50/50
17.597
3150861SPRUNCD
50/50
0.898
3151031BRUNSWICKG2
50/50
2.367
3151101ELIZAR3
50/50
17.646
3147666LOUISA
Solar/Wind Harmer
0.507
315773AC2-141 GEN
Solar/Wind Harmer
6.611
315839AE2-212 C
Solar/Wind Harmer
0.001
944581AF1-123 GEN
Solar/Wind Harmer
40.447
944601AF1-125 GEN
Solar/Wind Harmer
39.824
315813AE1-149 C
Solar/Wind Harmer
9.573
3144873MCLAUGH
Solar/Wind Harmer
0.004
965281AG1-393 GEN
Solar/Wind Harmer
1.908
970659AG2-427 GEN
Solar/Wind Harmer
1.891
3144536CHRHLND
Solar/Wind Harmer
0.027
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
3.77
3145336SMITFLD
Solar/Wind Harmer
0.071
3146456SLIGO L269
Solar/Wind Harmer
0.177
971153AH1-033 GEN
Solar/Wind Harmer
2.051
3151221GRAVEL6
Adder
12.86
3151171GRAVELC
Adder
2.474
961611AG1-000B GEN
Solar/Wind Harmer
4.714
315778AD1-151 GEN
Solar/Wind Harmer
14.128
970129AG2-093 GEN
Solar/Wind Harmer
10.67
970133AG2-095 GEN
Solar/Wind Harmer
1.693
3143096IRON208
Adder
0.737
3143096IRON208
Adder
0.722
316320Y1-086
Solar/Wind Harmer
0.001
3144216WINCHST
Adder
0.657
316435W1029_GEN3
Solar/Wind Harmer
0.001
316313AB2-026
Solar/Wind Harmer
0.11
316258AE1-075 C
Solar/Wind Harmer
0.131
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.631
3146516WINFALL
Solar/Wind Harmer
0.174
3150921YORKTN3
Adder
4.366
970917AG2-570 GEN
Solar/Wind Harmer
15.39
3146626S HERTFORD
Solar/Wind Harmer
0.173
3145273HOLLAND
Solar/Wind Harmer
0.129
3142946ENON
Solar/Wind Harmer
0.058
316382AG1-145 C
Solar/Wind Harmer
0.001
970293AG2-193 GEN
Solar/Wind Harmer
1.821
3146376EDENTON
Solar/Wind Harmer
0.17
3142416OLDCHRC
Solar/Wind Harmer
1.628
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315614AA2-178 GEN
Solar/Wind Harmer
0.952
316365GEN2_N
Solar/Wind Harmer
0.37
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
971157AH1-035 GEN
Solar/Wind Harmer
1.967
315737AD1-076 GEN
Solar/Wind Harmer
2.103
3141843SHACKLE
Adder
0.835
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
2.172
316156AD2-030 GEN
Solar/Wind Harmer
0.12
3141873WAN 176
Solar/Wind Harmer
2.887
3146206CASHIE
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
0.271
3145893MURPHYS
Solar/Wind Harmer
0.162
316473AC1-191 GEN
Solar/Wind Harmer
0.547
957521AF2-046 GEN
Solar/Wind Harmer
12.028
961681AG1-008 GEN
Solar/Wind Harmer
12.028
3146173TUNIS
Solar/Wind Harmer
0.161
3156021HOLLOMANSOL
Solar/Wind Harmer
0.727
316463AE2-346 GEN
Solar/Wind Harmer
0.137
316140AB2-099
Solar/Wind Harmer
0.057
962331AG1-082 GEN
Solar/Wind Harmer
1.706
313506AB2-031 GEN
Solar/Wind Harmer
0.491
3146263WOODLND
Solar/Wind Harmer
0.158
316478AD1-087 GEN
Solar/Wind Harmer
0.553
316486AD2-202 GEN
Solar/Wind Harmer
0.162
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.094
3145963POPLR C
Solar/Wind Harmer
0.156
316317KELFORD C
Solar/Wind Harmer
0.015
3145823KELFORD
Solar/Wind Harmer
0.156
3145796HORNRTN
Solar/Wind Harmer
0.621
3145796HORNRTN
Solar/Wind Harmer
0.155
962971AG1-146 GEN
Solar/Wind Harmer
2.479
970009AG2-005 GEN
Solar/Wind Harmer
1.144
316210AC1-098 GEN
Solar/Wind Harmer
1.405
970909AG2-566 GEN
Solar/Wind Harmer
1.611
316404AE1-155 C
Solar/Wind Harmer
0.034
3145933PARMELE
Solar/Wind Harmer
0.15
966801AG1-551 GEN
Solar/Wind Harmer
1.752
315724AD1-057 GEN
Solar/Wind Harmer
0.554
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
316131AB2-060 GEN
Solar/Wind Harmer
0.461
316327AA2-057 GEN
Solar/Wind Harmer
0.221
964241AG1-285 GEN
Solar/Wind Harmer
9.755
315785AD2-033 C
Solar/Wind Harmer
1.187
970257AG2-171 GEN
Solar/Wind Harmer
4.666
959311AF2-222 GEN
Solar/Wind Harmer
12.953
3150351NORNECKC2
Adder
1.476
963181AG1-167 GEN
Solar/Wind Harmer
0.581
3144293JTRSVLE
Adder
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.455
971193AH1-056 GEN
Solar/Wind Harmer
8.824
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.722
3146233WITAKRS
Solar/Wind Harmer
0.098
3146073TAR RVR
Solar/Wind Harmer
0.144
3146083TARBORO
Solar/Wind Harmer
0.144
3138543CONSLDL
Solar/Wind Harmer
0.095
3146926FARMVIL
Solar/Wind Harmer
0.086
961601AG1-000A GEN
Solar/Wind Harmer
10.061
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.141
971623AH1-311 GEN
Solar/Wind Harmer
0.283
971781AH1-399 GEN
Solar/Wind Harmer
0.181
3150401LDYSMT4
Adder
18.348
3150371LDYSMT1
Adder
17.729
3146776BUCKING
Solar/Wind Harmer
0.049
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.713
3141906WESTMOR
Solar/Wind Harmer
0.052
971683AH1-343 GEN
Solar/Wind Harmer
4.538
970737AG2-469 GEN
Solar/Wind Harmer
5.206
316283AC2-100 C
Solar/Wind Harmer
0.236
970221AG2-151 GEN
Solar/Wind Harmer
6.389
316044AC1-158 PL1
Solar/Wind Helper
5.365
316450AC1-158 RIC
Solar/Wind Helper
1.431
971133AH1-012 GEN
50/50
4.727
970533AG2-339 GEN
50/50
16.617
970531AG2-338 GEN
50/50
6.647
315242AE2-183_GT2
50/50
3.006
315241AE2-183_GT1
50/50
2.987
972185AH1-677 GEN
50/50
10.835
3151041BRUNSWICKG3
50/50
2.367
972187AH1-678 GEN
50/50
5.432
3150991CHESPKB
50/50
1.99
3150991CHESPKB
50/50
1.942
971223AH1-071 GEN
Solar/Wind Harmer
2.18
3143526WINTERP
Solar/Wind Harmer
1.012
316036AC1-147 C
Solar/Wind Harmer
0.033
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.172
316185AD1-033 GEN
Solar/Wind Harmer
0.005
316240AF1-291 C
Solar/Wind Harmer
0.001
3144356SAPONY
Solar/Wind Harmer
1.494
3145506HICKORY
Solar/Wind Harmer
0.714
3145506HICKORY
Solar/Wind Harmer
0.428
3145506HICKORY
Solar/Wind Harmer
0.107
970657AG2-426 GEN
Solar/Wind Harmer
6.25
970657AG2-426 GEN
Solar/Wind Harmer
1.31
944641AF1-129 GEN
Adder
84.93
316339AD2-160 GEN
Solar/Wind Harmer
0.288
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.099
316236AE1-162_GEN
Solar/Wind Harmer
0.001
3137176SLIGO L2192
Solar/Wind Harmer
0.706
3146456SLIGO L269
Solar/Wind Harmer
3.14
3130086AYDLETT
Solar/Wind Harmer
0.709
970933AG2-581 GEN
Solar/Wind Harmer
14.133
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.199
3146386ELIZ CT
Solar/Wind Harmer
0.176
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.174
3146516WINFALL
Solar/Wind Harmer
0.174
3146516WINFALL
Solar/Wind Harmer
0.174
3142366NRTHEST
Adder
0.565
3146626S HERTFORD
Solar/Wind Harmer
0.173
3146626S HERTFORD
Solar/Wind Harmer
0.173
3142946ENON
Solar/Wind Harmer
0.017
3150691DARBY 3
Adder
12.388
3150701DARBY 4
Adder
12.359
3150681DARBY 2
Adder
12.344
3150671DARBY 1
Adder
12.33
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.754
3146376EDENTON
Solar/Wind Harmer
0.754
316075AC2-137 C
Solar/Wind Harmer
0.046
3142296MT RD221
Adder
0.537
970099AG2-077 GEN
Solar/Wind Harmer
17.581
316065AD1-022 GEN
Solar/Wind Harmer
7.487
3145893MURPHYS
Solar/Wind Harmer
1.084
3145893MURPHYS
Solar/Wind Harmer
0.291
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3146173TUNIS
Solar/Wind Harmer
0.161
3146173TUNIS
Solar/Wind Harmer
0.161
316181AB2-040 GEN
Solar/Wind Harmer
0.23
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.095
316426AA2-053 GEN
Solar/Wind Harmer
0.53
3145593CAROLNA
Solar/Wind Harmer
0.156
3145593CAROLNA
Solar/Wind Harmer
0.156
966811AG1-552 GEN
Solar/Wind Harmer
1.698
3145593CAROLNA
Solar/Wind Harmer
0.195
3145783HORNRTN
Solar/Wind Harmer
2.766
3145783HORNRTN
Solar/Wind Harmer
2.213
3145783HORNRTN
Solar/Wind Harmer
0.692
3145783HORNRTN
Solar/Wind Harmer
0.277
3145796HORNRTN
Solar/Wind Harmer
0.466
971741AH1-377 GEN
Solar/Wind Harmer
15.218
970301AG2-198 GEN
Solar/Wind Harmer
6.446
316274AC1-208 GEN
Solar/Wind Harmer
0.781
958261AF2-120 GEN
Solar/Wind Harmer
4.978
3145933PARMELE
Solar/Wind Harmer
0.301
3145933PARMELE
Solar/Wind Harmer
0.15
939181AE1-148 GEN
Solar/Wind Harmer
7.079
957411AF2-035 GEN
Solar/Wind Harmer
6.288
970317AG2-208 GEN
Solar/Wind Harmer
5.826
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.221
971775AH1-396 GEN
Solar/Wind Harmer
0.233
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.525
3150341NORNECKC1
Adder
1.513
958211AF2-115 GEN
Solar/Wind Harmer
1.742
963191AG1-168 GEN
Solar/Wind Harmer
0.581
3144293JTRSVLE
Adder
0.462
3144293JTRSVLE
Adder
0.389
3147133PAMPLIN
Solar/Wind Harmer
0.145
3147133PAMPLIN
Solar/Wind Harmer
0.116
3145493TOT1
Solar/Wind Harmer
0.333
3145453TOT5
Solar/Wind Harmer
0.2
3145603CNETO
Solar/Wind Harmer
0.133
315673AE1-157 GEN
Solar/Wind Harmer
9.924
961601AG1-000A GEN
Solar/Wind Harmer
2.515
316263AC1-034 GEN
Solar/Wind Harmer
5.374
962561AG1-105 GEN
Solar/Wind Harmer
6.736
964791AG1-342 GEN
Solar/Wind Harmer
2.673
3146843MT LREL
Solar/Wind Harmer
0.139
3146843MT LREL
Solar/Wind Harmer
0.139
316468AD1-105 GEN
Solar/Wind Harmer
-0.045
3150391LDYSMT3
Adder
18.314
972195AH1-682 GEN
Adder
2.407
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
316222AC1-221 GEN
Solar/Wind Harmer
0.503
971489AH1-241 GEN
Solar/Wind Harmer
6.389
316447AC1-158 HLD
Solar/Wind Helper
11.807
316303AF2-085
50/50
3.634
971285AH1-108 GEN
50/50
1.469
315244AE2-183_ST
50/50
5.196
963041AG1-153 GEN
50/50
4.793
3151081ELIZAR1
50/50
17.423
3151091ELIZAR2
50/50
17.121
941591AE2-156 GEN
50/50
15.921
3152611GOSPORTB
50/50
2.419
3152621GOSPORTC
50/50
2.053
3152601GOSPORTA
50/50
1.894
315779AE2-040
50/50
2.493
316233AE1-074 FULL
Solar/Wind Harmer
0.156
971281AH1-106 GEN
Solar/Wind Harmer
2.702
971283AH1-107 GEN
Solar/Wind Harmer
2.702
941031AE2-094 GEN
Solar/Wind Harmer
34.43
944011AF1-069 GEN
Solar/Wind Harmer
11.25
970673AG2-436 GEN
Solar/Wind Harmer
39.174
970673AG2-436 GEN
Solar/Wind Harmer
26.116
3143316POE
Solar/Wind Harmer
0.721
971967AH1-528 GEN
Solar/Wind Harmer
28.994
316315AB2-025 C
Solar/Wind Harmer
0.144
315814AE2-033 C
Solar/Wind Harmer
14.072
957871AF2-081 GEN
Solar/Wind Harmer
8.849
971445AH1-216 GEN
Solar/Wind Harmer
12.508
319010AE1-072 C
Solar/Wind Harmer
0.893
3146406KITTY HAWK
Solar/Wind Harmer
0.022
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.121
316311AC2-079 GEN
Solar/Wind Harmer
5.087
316305AF2-043 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
13.734
3151201GRAVEL4
Adder
12.875
3151191GRAVEL3
Adder
12.712
3151211GRAVEL5
Adder
12.712
316369SG1_INVT
Solar/Wind Harmer
0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.947
315835AF2-110_GEN
Solar/Wind Harmer
1.21
313526AB2-022
Solar/Wind Harmer
0.095
3146486SUNBURY
Solar/Wind Harmer
0.175
3146486SUNBURY
Solar/Wind Harmer
0.175
316321Z2-027
Solar/Wind Harmer
0.033
3146396TANGLEW
Solar/Wind Harmer
0.483
3145176PASQUOTANK
Solar/Wind Harmer
0.109
970085AG2-068 GEN
Solar/Wind Harmer
9.195
970581AG2-369 GEN
Solar/Wind Harmer
7.908
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.17
3130156CHOWAN
Solar/Wind Harmer
0.17
315976AC1-164 GENA
Solar/Wind Harmer
17.467
316169AC1-164_GENC
Solar/Wind Harmer
15.09
315975AC1-164 GENB
Solar/Wind Harmer
0.517
3138283WHITEMARSH
Solar/Wind Harmer
0.039
971167AH1-042 GEN
Solar/Wind Harmer
14.927
316312AB1-027
Solar/Wind Harmer
0.3
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315816AE2-034 GEN
Solar/Wind Harmer
0.714
3143873LANEXA
Solar/Wind Harmer
0.099
3130546PLYMOUTH
Solar/Wind Harmer
0.164
315732AD1-074 GEN1
Solar/Wind Harmer
0.939
315733AD1-074 GEN2
Solar/Wind Harmer
0.939
315735AD1-075 GEN1
Solar/Wind Harmer
0.47
965291AG1-394 GEN
Solar/Wind Harmer
0.726
970189AG2-124 GEN
Solar/Wind Harmer
4.842
316314AB2-024 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.032
3146206CASHIE
Solar/Wind Harmer
0.162
970601AG2-382 GEN
Solar/Wind Harmer
6.052
3145893MURPHYS
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.162
3145513AHOSKIE
Solar/Wind Harmer
0.334
3145513AHOSKIE
Solar/Wind Harmer
0.16
3141913WHIT STONE
Solar/Wind Harmer
0.16
3146043SEABORD
Solar/Wind Harmer
0.16
316087AB2-174 GEN
Solar/Wind Harmer
0.005
972189AH1-679 GEN
Adder
2.672
3138133OCRAN
Solar/Wind Harmer
0.048
315607AA1-063A GEN
Solar/Wind Harmer
0.325
3145683EARLEYS
Solar/Wind Harmer
0.318
3145683EARLEYS
Solar/Wind Harmer
0.159
3145683EARLEYS
Solar/Wind Harmer
0.159
3141783LANCAST
Solar/Wind Harmer
0.095
3141783LANCAST
Solar/Wind Harmer
0.063
315652AC1-086 GEN
Solar/Wind Harmer
17.349
3137643SOCKMAN
Solar/Wind Harmer
0.629
3145796HORNRTN
Solar/Wind Harmer
0.497
3145796HORNRTN
Solar/Wind Harmer
0.062
962981AG1-147 GEN
Solar/Wind Harmer
5.785
3146033SCOT NK
Solar/Wind Harmer
0.614
970327AG2-215 GEN
Solar/Wind Harmer
5.03
970831AG2-522 GEN
Solar/Wind Harmer
6.456
316005AA1-067
Solar/Wind Harmer
0.158
3145746EVERETS
Solar/Wind Harmer
0.587
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
970181AG2-120 GEN
Solar/Wind Harmer
1.837
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.45
3144303KENBRDG
Solar/Wind Harmer
0.117
3141813NORNECK
Solar/Wind Harmer
0.146
957861AF2-080 GEN
Solar/Wind Harmer
6.272
970683AG2-441 GEN
Solar/Wind Harmer
9.698
970681AG2-440 GEN
Solar/Wind Harmer
7.758
946301AF1-294 GEN
Solar/Wind Harmer
2.864
961791AG1-021 GEN
Solar/Wind Harmer
1.393
315657AE1-056 GEN
Solar/Wind Harmer
4.998
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.144
3145573BETHELC
Solar/Wind Harmer
0.144
970285AG2-188 GEN
Solar/Wind Harmer
10.95
971845AH1-439 GEN
Solar/Wind Harmer
6.225
3150411LDYSMT5
Adder
18.406
3150381LDYSMT2
Adder
17.615
972213AH1-691 GEN
Adder
2.98
972215AH1-692 GEN
Adder
2.98
316118AC1-105 GEN
Solar/Wind Harmer
0.352
3147173SINAI
Solar/Wind Harmer
0.134
3147243WELCO
Solar/Wind Harmer
0.084
316223AC1-118
Solar/Wind Harmer
0.093
972205AH1-687 GEN
Adder
5.489
970865AG2-541 GEN
Solar/Wind Harmer
4.099
971447AH1-217 GEN
Solar/Wind Harmer
3.524
316164AC1-076 GEN
Solar/Wind Helper
1.636
LAGNLTFEXP_LAGN->PJM
CLTF
6.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.05
TVALTFEXP_TVA->PJM
CLTF
3.173
CPLELTFEXP_CPLE->PJM
CLTF
9.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.753
MECLTFEXP_MEC->PJM
CLTF
2.757
SIGELTFEXP_SIGE->PJM
CLTF
0.083
NYPJM->LTFIMP_NY
CLTF
2.427
LGEELTFEXP_LGEE->PJM
CLTF
1
WECLTFEXP_WEC->PJM
CLTF
0.483

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:118.03 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4650.58
MW Contribution:28.24
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
17.758
3151771S ANNAG1
50/50
0.883
3151801S ANNAS2
50/50
0.454
3151761LOISA E
50/50
34.843
972183AH1-676 GEN
50/50
278.318
3150861SPRUNCD
50/50
0.925
3151031BRUNSWICKG2
50/50
2.447
3147666LOUISA
Solar/Wind Harmer
-0.078
316313AB2-026
Solar/Wind Harmer
0.573
316258AE1-075 C
Solar/Wind Harmer
0.516
316405AF2-144 C
Solar/Wind Harmer
0.544
3143336POWHATN
Solar/Wind Harmer
2.142
315773AC2-141 GEN
Solar/Wind Harmer
8.749
315839AE2-212 C
Solar/Wind Harmer
0.627
944581AF1-123 GEN
Solar/Wind Harmer
94.449
944601AF1-125 GEN
Solar/Wind Harmer
92.975
315813AE1-149 C
Solar/Wind Harmer
12.969
3151101ELIZAR3
Adder
17.107
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
2.584
970659AG2-427 GEN
Solar/Wind Harmer
1.946
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.352
970661AG2-428 GEN
Solar/Wind Harmer
3.88
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.501
3151221GRAVEL6
Adder
13.222
3151171GRAVELC
Adder
2.544
961611AG1-000B GEN
Solar/Wind Harmer
4.3
315778AD1-151 GEN
Solar/Wind Harmer
17.67
970129AG2-093 GEN
Solar/Wind Harmer
11.479
970133AG2-095 GEN
Solar/Wind Harmer
2.292
316320Y1-086
Solar/Wind Harmer
1.192
3143096IRON208
Adder
0.757
3143096IRON208
Adder
0.742
316435W1029_GEN3
Solar/Wind Harmer
3.654
970917AG2-570 GEN
Solar/Wind Harmer
50.335
3146516WINFALL
Solar/Wind Harmer
-0.02
3144216WINCHST
Adder
0.675
3150921YORKTN3
Adder
4.485
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.007
316382AG1-145 C
Solar/Wind Harmer
0.598
970293AG2-193 GEN
Solar/Wind Harmer
2.461
3146376EDENTON
Solar/Wind Harmer
-0.02
3142416OLDCHRC
Solar/Wind Harmer
1.951
315614AA2-178 GEN
Solar/Wind Harmer
2.084
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
316365GEN2_N
Solar/Wind Harmer
1.295
3156081AA2-088 GEN
Solar/Wind Harmer
6.195
971157AH1-035 GEN
Solar/Wind Harmer
2.38
315737AD1-076 GEN
Solar/Wind Harmer
3.609
3145893MURPHYS
Solar/Wind Harmer
0.132
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
957521AF2-046 GEN
Solar/Wind Harmer
14.82
961681AG1-008 GEN
Solar/Wind Harmer
14.82
966621AG1-532 GEN
Solar/Wind Harmer
0.382
3141843SHACKLE
Adder
0.855
316203AE2-005 GEN
Solar/Wind Harmer
7.929
316280AD1-041 GEN
Solar/Wind Harmer
1.413
3141766HARMONY
Solar/Wind Harmer
1.669
3146173TUNIS
Solar/Wind Harmer
-0.019
316478AD1-087 GEN
Solar/Wind Harmer
1.619
316486AD2-202 GEN
Solar/Wind Harmer
0.474
316156AD2-030 GEN
Solar/Wind Harmer
0.499
3141873WAN 176
Solar/Wind Harmer
2.218
3156021HOLLOMANSOL
Solar/Wind Harmer
2.51
316463AE2-346 GEN
Solar/Wind Harmer
0.301
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.327
316473AC1-191 GEN
Solar/Wind Harmer
2.002
313506AB2-031 GEN
Solar/Wind Harmer
1.493
970909AG2-566 GEN
Solar/Wind Harmer
1.761
3152251N ANNA1
50/50
17.76
3151791S ANNAG2
50/50
0.883
3151781S ANNAS1
50/50
0.454
3151741LOISA C
50/50
0.935
3151751LOISA D
50/50
17.091
970119AG2-088 GEN
50/50
28.238
3150851SPRUNCC
50/50
0.925
315243AE2-183_GT3
50/50
3.105
3151051BRUNSWICKS1
50/50
5.079
3151021BRUNSWICKG1
50/50
2.447
971451AH1-221 GEN
50/50
7.433
3147666LOUISA
Solar/Wind Harmer
-0.135
316192AB2-158 GEN
Solar/Wind Harmer
4.001
315683AE1-153 C
Solar/Wind Harmer
25.661
3143226MDLTHAN
Solar/Wind Harmer
-0.024
3143526WINTERP
Solar/Wind Harmer
-0.117
940641AE2-051 GEN
Solar/Wind Harmer
20.735
939411AE1-173 GEN
Solar/Wind Harmer
108.776
3143336POWHATN
Solar/Wind Harmer
2.52
316294AC1-161 GEN
Solar/Wind Harmer
6.764
944591AF1-124 GEN
Solar/Wind Harmer
94.789
316375AC2-012 GEN
Solar/Wind Harmer
7.16
3150981CHESPKA
Adder
2.299
970659AG2-427 GEN
Solar/Wind Harmer
10.98
316381AD1-082 GEN
Solar/Wind Harmer
1.894
315671AE2-027_GEN
Solar/Wind Harmer
15.462
970661AG2-428 GEN
Solar/Wind Harmer
21.895
3142543TWELFTH
Solar/Wind Harmer
-0.002
316388AE2-253 GEN
Solar/Wind Harmer
1.387
316336AC2-165 C
Solar/Wind Harmer
3.574
3145336SMITFLD
Solar/Wind Harmer
-0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.414
316072AD1-144
Solar/Wind Harmer
0.413
3151171GRAVELC
Adder
1.935
961611AG1-000B GEN
Solar/Wind Harmer
10.078
971647AH1-324 GEN
Solar/Wind Harmer
10.206
316093AE2-104_GEN
Solar/Wind Harmer
5.931
971069AG2-661 GEN
Solar/Wind Harmer
3.227
316458AB2-190 GEN2
Solar/Wind Harmer
2.062
970129AG2-093 GEN
Solar/Wind Harmer
4.65
3143096IRON208
Adder
0.757
970919AG2-571 GEN
Solar/Wind Harmer
6.372
3146516WINFALL
Solar/Wind Harmer
-0.065
3146516WINFALL
Solar/Wind Harmer
-0.02
3138126ROCKLANDING
Solar/Wind Harmer
0.062
970087AG2-069 GEN
Solar/Wind Harmer
18.798
944631AF1-128 GEN
Adder
85.046
315800Z1-036_GEN1
Solar/Wind Harmer
4.908
971317AH1-138 GEN
Solar/Wind Harmer
2.48
316159AE1-175 C
Solar/Wind Harmer
0.532
3130156CHOWAN
Solar/Wind Harmer
-0.02
957481AF2-042 GEN
Solar/Wind Harmer
60.65
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3145663CRESWEL
Solar/Wind Harmer
-0.054
971163AH1-040 GEN
Solar/Wind Harmer
18.105
3142433PROV 92
Solar/Wind Harmer
-0.077
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
316023GEN1_S
Solar/Wind Harmer
1.295
315693AD1-088 GEN
Solar/Wind Harmer
9.573
962491AG1-098 GEN
Solar/Wind Harmer
12.783
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.56
970937AG2-583 GEN
Solar/Wind Harmer
13.548
3146206CASHIE
Solar/Wind Harmer
-0.019
971547AH1-271 GEN
Solar/Wind Harmer
4.71
960081AF2-299 GEN
Solar/Wind Harmer
2.117
971777AH1-397 GEN
Solar/Wind Harmer
2.211
3141843SHACKLE
Adder
0.855
3141766HARMONY
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.019
971795AH1-408 GEN
Solar/Wind Harmer
13.912
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.484
316011AB1-132 GEN
Solar/Wind Harmer
3.849
962571AG1-106 GEN
Solar/Wind Harmer
2.644
316190AA2-174 GEN
Solar/Wind Harmer
0.225
3138133OCRAN
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.06
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
2.787
3144293JTRSVLE
Adder
0.505
3150351NORNECKC2
Adder
1.48
972197AH1-683 GEN
Adder
2.852
972219AH1-694 GEN
Adder
2.053
316045AC1-158 PL2
Solar/Wind Helper
17.311
316254AC1-120 GEN1
Solar/Wind Helper
2.093
316006AB2-029 C
Solar/Wind Helper
0.162
316303AF2-085
50/50
3.765
971285AH1-108 GEN
50/50
1.513
315244AE2-183_ST
50/50
5.368
963041AG1-153 GEN
50/50
4.955
3147346CASHSCORNER
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.609
971281AH1-106 GEN
Solar/Wind Harmer
3.677
971283AH1-107 GEN
Solar/Wind Harmer
3.677
941031AE2-094 GEN
Solar/Wind Harmer
40.621
944011AF1-069 GEN
Solar/Wind Harmer
12.728
970673AG2-436 GEN
Solar/Wind Harmer
44.754
970673AG2-436 GEN
Solar/Wind Harmer
22.66
971967AH1-528 GEN
Solar/Wind Harmer
39.617
3143316POE
Solar/Wind Harmer
-0.083
3151081ELIZAR1
Adder
16.891
3151091ELIZAR2
Adder
16.598
316315AB2-025 C
Solar/Wind Harmer
0.558
3152611GOSPORTB
Adder
2.345
3152621GOSPORTC
Adder
1.99
3152601GOSPORTA
Adder
1.836
315814AE2-033 C
Solar/Wind Harmer
19.205
957871AF2-081 GEN
Solar/Wind Harmer
10.278
971445AH1-216 GEN
Solar/Wind Harmer
12.702
319010AE1-072 C
Solar/Wind Harmer
4.148
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.893
316349AD2-085 GEN
Solar/Wind Harmer
1.823
316311AC2-079 GEN
Solar/Wind Harmer
10.336
316305AF2-043 C
Solar/Wind Harmer
0.617
972265AH1-717 GEN
Adder
14.121
3151201GRAVEL4
Adder
13.238
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.86
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.701
3147133PAMPLIN
Solar/Wind Harmer
-0.056
3144293JTRSVLE
Adder
0.505
3150351NORNECKC2
Adder
1.505
3150401LDYSMT4
Adder
18.264
3150371LDYSMT1
Adder
17.648
316044AC1-158 PL1
Solar/Wind Helper
5.408
316450AC1-158 RIC
Solar/Wind Helper
1.442
316170AC1-121 GEN2
Solar/Wind Helper
0.698
971193AH1-056 GEN
Solar/Wind Harmer
5.031
971133AH1-012 GEN
50/50
5.78
3151731LOISA B
50/50
17.091
3151721LOISA A
50/50
17.002
970533AG2-339 GEN
50/50
17.139
970531AG2-338 GEN
50/50
6.856
315242AE2-183_GT2
50/50
3.105
315241AE2-183_GT1
50/50
3.086
972185AH1-677 GEN
50/50
11.194
3151041BRUNSWICKG3
50/50
2.447
972187AH1-678 GEN
50/50
5.616
966001AG1-469 GEN
Solar/Wind Harmer
0.521
971223AH1-071 GEN
Solar/Wind Harmer
2.974
3143526WINTERP
Solar/Wind Harmer
-0.117
3144356SAPONY
Solar/Wind Harmer
0.722
316036AC1-147 C
Solar/Wind Harmer
0.558
3150991CHESPKB
Adder
1.929
3150991CHESPKB
Adder
1.882
3142956BIRDNECK
Solar/Wind Harmer
1.109
316316AC1-027 C
Solar/Wind Harmer
0.635
316185AD1-033 GEN
Solar/Wind Harmer
2.18
3145506HICKORY
Solar/Wind Harmer
-0.082
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
316240AF1-291 C
Solar/Wind Harmer
0.622
970657AG2-426 GEN
Solar/Wind Harmer
6.448
970657AG2-426 GEN
Solar/Wind Harmer
1.348
970933AG2-581 GEN
Solar/Wind Harmer
19.327
944641AF1-129 GEN
Adder
87.32
316339AD2-160 GEN
Solar/Wind Harmer
1.387
316018AA1-139 ULT2
Solar/Wind Harmer
1.761
316017AA1-139 ULT1
Solar/Wind Harmer
1.663
316236AE1-162_GEN
Solar/Wind Harmer
0.619
3137176SLIGO L2192
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
2.424
3130086AYDLETT
Solar/Wind Harmer
-0.082
316033AB2-134 GEN
Solar/Wind Harmer
6.58
315697AD1-025 GEN
Solar/Wind Harmer
4.127
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.654
316433W1029_GEN2
Solar/Wind Harmer
3.654
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.58
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.715
3150701DARBY 4
Adder
12.685
3150681DARBY 2
Adder
12.67
3150671DARBY 1
Adder
12.655
315742AE1-103 GEN
Solar/Wind Harmer
2.07
3146376EDENTON
Solar/Wind Harmer
0.584
3146376EDENTON
Solar/Wind Harmer
0.584
316075AC2-137 C
Solar/Wind Harmer
0.526
3142296MT RD221
Adder
0.55
970099AG2-077 GEN
Solar/Wind Harmer
24.26
316065AD1-022 GEN
Solar/Wind Harmer
9.447
3145893MURPHYS
Solar/Wind Harmer
0.526
3145893MURPHYS
Solar/Wind Harmer
-0.034
316441AF1-014 GEN
Solar/Wind Harmer
1.268
3146173TUNIS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.019
971741AH1-377 GEN
Solar/Wind Harmer
21.726
966871AG1-558 GEN
Solar/Wind Harmer
0.559
966871AG1-558 GEN
Solar/Wind Harmer
0.191
316181AB2-040 GEN
Solar/Wind Harmer
2.591
970301AG2-198 GEN
Solar/Wind Harmer
9.277
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.853
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
2.059
3145593CAROLNA
Solar/Wind Harmer
0.152
3145783HORNRTN
Solar/Wind Harmer
2.159
3145783HORNRTN
Solar/Wind Harmer
1.727
3145783HORNRTN
Solar/Wind Harmer
0.54
3145783HORNRTN
Solar/Wind Harmer
0.216
3145796HORNRTN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3144293JTRSVLE
Adder
0.505
3144293JTRSVLE
Adder
0.425
3150341NORNECKC1
Adder
1.555
3150341NORNECKC1
Adder
1.542
3150391LDYSMT3
Adder
18.23
972195AH1-682 GEN
Adder
2.396
316447AC1-158 HLD
Solar/Wind Helper
11.902
315651AD1-115 GEN
Solar/Wind Helper
1.457
3151191GRAVEL3
Adder
13.07
3151211GRAVEL5
Adder
13.07
316369SG1_INVT
Solar/Wind Harmer
3.645
315835AF2-110_GEN
Solar/Wind Harmer
2.55
316132AB2-190 GEN1
Solar/Wind Harmer
2.062
313526AB2-022
Solar/Wind Harmer
0.549
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.547
3146396TANGLEW
Solar/Wind Harmer
0.373
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
970085AG2-068 GEN
Solar/Wind Harmer
12.532
970581AG2-369 GEN
Solar/Wind Harmer
10.778
315611Z1-036_GEN2
Solar/Wind Harmer
4.908
3130156CHOWAN
Solar/Wind Harmer
-0.02
3130156CHOWAN
Solar/Wind Harmer
-0.02
315976AC1-164 GENA
Solar/Wind Harmer
20.509
316169AC1-164_GENC
Solar/Wind Harmer
17.718
315975AC1-164 GENB
Solar/Wind Harmer
0.607
957831AF2-077 GEN
Solar/Wind Harmer
0.583
3138283WHITEMARSH
Solar/Wind Harmer
0.03
971167AH1-042 GEN
Solar/Wind Harmer
18.644
316312AB1-027
Solar/Wind Harmer
0.652
315816AE2-034 GEN
Solar/Wind Harmer
1.563
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
965291AG1-394 GEN
Solar/Wind Harmer
1.688
315732AD1-074 GEN1
Solar/Wind Harmer
3.84
315733AD1-074 GEN2
Solar/Wind Harmer
3.84
315735AD1-075 GEN1
Solar/Wind Harmer
1.921
3143873LANEXA
Solar/Wind Harmer
-0.011
316318V4-068
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
-0.051
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
970601AG2-382 GEN
Solar/Wind Harmer
8.243
946281AF1-292 GEN
Solar/Wind Harmer
0.421
316314AB2-024 C
Solar/Wind Harmer
1.606
315662AE1-191 GEN
Solar/Wind Harmer
2.261
315666AE1-190 GEN
Solar/Wind Harmer
0.565
316059AD1-063 C
Solar/Wind Harmer
0.424
957601AF2-054 GEN
Solar/Wind Harmer
0.559
3141873WAN 176
Solar/Wind Harmer
-0.004
316087AB2-174 GEN
Solar/Wind Harmer
2.66
3146043SEABORD
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.14
3145513AHOSKIE
Solar/Wind Harmer
-0.019
315607AA1-063A GEN
Solar/Wind Harmer
1.878
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.073
315652AC1-086 GEN
Solar/Wind Harmer
20.696
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.006
972189AH1-679 GEN
Adder
2.721
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.071
970285AG2-188 GEN
Solar/Wind Harmer
15.636
972205AH1-687 GEN
Adder
6.614
3150411LDYSMT5
Adder
18.321
3150381LDYSMT2
Adder
17.534
972213AH1-691 GEN
Adder
2.966
972215AH1-692 GEN
Adder
2.966
316164AC1-076 GEN
Solar/Wind Helper
2.448
LAGNLTFEXP_LAGN->PJM
CLTF
6.822
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.257
TVALTFEXP_TVA->PJM
CLTF
3.456
CPLELTFEXP_CPLE->PJM
CLTF
9.69
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.259
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.42
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.761
MECLTFEXP_MEC->PJM
CLTF
3.094
SIGELTFEXP_SIGE->PJM
CLTF
0.094
NYPJM->LTFIMP_NY
CLTF
2.632
LGEELTFEXP_LGEE->PJM
CLTF
1.138
WECLTFEXP_WEC->PJM
CLTF
0.551

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.81 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4641.56
MW Contribution:28.24
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
17.76
3151791S ANNAG2
50/50
0.883
3151781S ANNAS1
50/50
0.454
3151741LOISA C
50/50
0.935
3151751LOISA D
50/50
17.091
970119AG2-088 GEN
50/50
28.238
3150851SPRUNCC
50/50
0.925
315243AE2-183_GT3
50/50
3.105
3151051BRUNSWICKS1
50/50
5.079
3151021BRUNSWICKG1
50/50
2.447
971451AH1-221 GEN
50/50
7.433
3147666LOUISA
Solar/Wind Harmer
-0.135
316192AB2-158 GEN
Solar/Wind Harmer
4.001
3143226MDLTHAN
Solar/Wind Harmer
-0.024
3143526WINTERP
Solar/Wind Harmer
-0.117
940641AE2-051 GEN
Solar/Wind Harmer
20.735
939411AE1-173 GEN
Solar/Wind Harmer
108.776
3143336POWHATN
Solar/Wind Harmer
2.52
316294AC1-161 GEN
Solar/Wind Harmer
6.764
944591AF1-124 GEN
Solar/Wind Harmer
94.789
316375AC2-012 GEN
Solar/Wind Harmer
7.16
3150981CHESPKA
Adder
2.299
970659AG2-427 GEN
Solar/Wind Harmer
10.98
316381AD1-082 GEN
Solar/Wind Harmer
1.894
315671AE2-027_GEN
Solar/Wind Harmer
15.462
970661AG2-428 GEN
Solar/Wind Harmer
21.895
3142543TWELFTH
Solar/Wind Harmer
-0.002
316388AE2-253 GEN
Solar/Wind Harmer
1.387
316336AC2-165 C
Solar/Wind Harmer
3.574
3145336SMITFLD
Solar/Wind Harmer
-0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.414
316072AD1-144
Solar/Wind Harmer
0.413
3151171GRAVELC
Adder
1.935
961611AG1-000B GEN
Solar/Wind Harmer
10.078
971647AH1-324 GEN
Solar/Wind Harmer
10.206
316093AE2-104_GEN
Solar/Wind Harmer
5.931
971069AG2-661 GEN
Solar/Wind Harmer
3.227
316458AB2-190 GEN2
Solar/Wind Harmer
2.062
970129AG2-093 GEN
Solar/Wind Harmer
4.65
3143096IRON208
Adder
0.757
970919AG2-571 GEN
Solar/Wind Harmer
6.372
3146516WINFALL
Solar/Wind Harmer
-0.065
3146516WINFALL
Solar/Wind Harmer
-0.02
3138126ROCKLANDING
Solar/Wind Harmer
0.062
970087AG2-069 GEN
Solar/Wind Harmer
18.798
944631AF1-128 GEN
Adder
85.046
315800Z1-036_GEN1
Solar/Wind Harmer
4.908
971317AH1-138 GEN
Solar/Wind Harmer
2.48
316159AE1-175 C
Solar/Wind Harmer
0.532
3130156CHOWAN
Solar/Wind Harmer
-0.02
957481AF2-042 GEN
Solar/Wind Harmer
60.65
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3145663CRESWEL
Solar/Wind Harmer
-0.054
971163AH1-040 GEN
Solar/Wind Harmer
18.105
3142433PROV 92
Solar/Wind Harmer
-0.077
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
316023GEN1_S
Solar/Wind Harmer
1.295
315693AD1-088 GEN
Solar/Wind Harmer
9.573
962491AG1-098 GEN
Solar/Wind Harmer
12.783
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.56
970937AG2-583 GEN
Solar/Wind Harmer
13.548
3146206CASHIE
Solar/Wind Harmer
-0.019
971547AH1-271 GEN
Solar/Wind Harmer
4.71
960081AF2-299 GEN
Solar/Wind Harmer
2.117
971777AH1-397 GEN
Solar/Wind Harmer
2.211
3141843SHACKLE
Adder
0.855
3141766HARMONY
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.019
971795AH1-408 GEN
Solar/Wind Harmer
13.912
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.484
316011AB1-132 GEN
Solar/Wind Harmer
3.849
962571AG1-106 GEN
Solar/Wind Harmer
2.644
316190AA2-174 GEN
Solar/Wind Harmer
0.225
3138133OCRAN
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.06
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
2.787
3144293JTRSVLE
Adder
0.505
3150351NORNECKC2
Adder
1.48
972197AH1-683 GEN
Adder
2.852
972219AH1-694 GEN
Adder
2.053
316045AC1-158 PL2
Solar/Wind Helper
17.311
316254AC1-120 GEN1
Solar/Wind Helper
2.093
316006AB2-029 C
Solar/Wind Helper
0.162
3152261N ANNA2
50/50
17.758
3151771S ANNAG1
50/50
0.883
3151801S ANNAS2
50/50
0.454
3151761LOISA E
50/50
34.843
972183AH1-676 GEN
50/50
278.318
3150861SPRUNCD
50/50
0.925
3151031BRUNSWICKG2
50/50
2.447
3147666LOUISA
Solar/Wind Harmer
-0.078
316313AB2-026
Solar/Wind Harmer
0.573
316258AE1-075 C
Solar/Wind Harmer
0.516
316405AF2-144 C
Solar/Wind Harmer
0.544
3143336POWHATN
Solar/Wind Harmer
2.142
315773AC2-141 GEN
Solar/Wind Harmer
8.749
315839AE2-212 C
Solar/Wind Harmer
0.627
944581AF1-123 GEN
Solar/Wind Harmer
94.449
944601AF1-125 GEN
Solar/Wind Harmer
92.975
315813AE1-149 C
Solar/Wind Harmer
12.969
3151101ELIZAR3
Adder
17.107
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
2.584
970659AG2-427 GEN
Solar/Wind Harmer
1.946
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.352
970661AG2-428 GEN
Solar/Wind Harmer
3.88
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.501
3151221GRAVEL6
Adder
13.222
3151171GRAVELC
Adder
2.544
961611AG1-000B GEN
Solar/Wind Harmer
4.3
315778AD1-151 GEN
Solar/Wind Harmer
17.67
970129AG2-093 GEN
Solar/Wind Harmer
11.479
970133AG2-095 GEN
Solar/Wind Harmer
2.292
316320Y1-086
Solar/Wind Harmer
1.192
3143096IRON208
Adder
0.757
3143096IRON208
Adder
0.742
316435W1029_GEN3
Solar/Wind Harmer
3.654
970917AG2-570 GEN
Solar/Wind Harmer
50.335
3146516WINFALL
Solar/Wind Harmer
-0.02
3144216WINCHST
Adder
0.675
3150921YORKTN3
Adder
4.485
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.007
316382AG1-145 C
Solar/Wind Harmer
0.598
970293AG2-193 GEN
Solar/Wind Harmer
2.461
3146376EDENTON
Solar/Wind Harmer
-0.02
3142416OLDCHRC
Solar/Wind Harmer
1.951
315614AA2-178 GEN
Solar/Wind Harmer
2.084
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
316365GEN2_N
Solar/Wind Harmer
1.295
3156081AA2-088 GEN
Solar/Wind Harmer
6.195
971157AH1-035 GEN
Solar/Wind Harmer
2.38
315737AD1-076 GEN
Solar/Wind Harmer
3.609
3145893MURPHYS
Solar/Wind Harmer
0.132
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
957521AF2-046 GEN
Solar/Wind Harmer
14.82
961681AG1-008 GEN
Solar/Wind Harmer
14.82
966621AG1-532 GEN
Solar/Wind Harmer
0.382
3141843SHACKLE
Adder
0.855
316203AE2-005 GEN
Solar/Wind Harmer
7.929
316280AD1-041 GEN
Solar/Wind Harmer
1.413
3141766HARMONY
Solar/Wind Harmer
1.669
3146173TUNIS
Solar/Wind Harmer
-0.019
316478AD1-087 GEN
Solar/Wind Harmer
1.619
316486AD2-202 GEN
Solar/Wind Harmer
0.474
316156AD2-030 GEN
Solar/Wind Harmer
0.499
3141873WAN 176
Solar/Wind Harmer
2.218
3156021HOLLOMANSOL
Solar/Wind Harmer
2.51
316463AE2-346 GEN
Solar/Wind Harmer
0.301
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.327
316473AC1-191 GEN
Solar/Wind Harmer
2.002
313506AB2-031 GEN
Solar/Wind Harmer
1.493
970909AG2-566 GEN
Solar/Wind Harmer
1.761
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.86
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.701
3147133PAMPLIN
Solar/Wind Harmer
-0.056
971193AH1-056 GEN
Solar/Wind Harmer
11.159
3144293JTRSVLE
Adder
0.505
3150351NORNECKC2
Adder
1.505
3150401LDYSMT4
Adder
18.264
3150371LDYSMT1
Adder
17.648
316044AC1-158 PL1
Solar/Wind Helper
5.408
316450AC1-158 RIC
Solar/Wind Helper
1.442
316170AC1-121 GEN2
Solar/Wind Helper
0.698
971133AH1-012 GEN
50/50
5.78
3151731LOISA B
50/50
17.091
3151721LOISA A
50/50
17.002
970533AG2-339 GEN
50/50
17.139
970531AG2-338 GEN
50/50
6.856
315242AE2-183_GT2
50/50
3.105
315241AE2-183_GT1
50/50
3.086
972185AH1-677 GEN
50/50
11.194
3151041BRUNSWICKG3
50/50
2.447
972187AH1-678 GEN
50/50
5.616
966001AG1-469 GEN
Solar/Wind Harmer
0.521
971223AH1-071 GEN
Solar/Wind Harmer
2.974
3143526WINTERP
Solar/Wind Harmer
-0.117
3144356SAPONY
Solar/Wind Harmer
0.722
316036AC1-147 C
Solar/Wind Harmer
0.558
3150991CHESPKB
Adder
1.929
3150991CHESPKB
Adder
1.882
3142956BIRDNECK
Solar/Wind Harmer
1.109
316316AC1-027 C
Solar/Wind Harmer
0.635
316185AD1-033 GEN
Solar/Wind Harmer
2.18
3145506HICKORY
Solar/Wind Harmer
-0.082
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
316240AF1-291 C
Solar/Wind Harmer
0.622
970657AG2-426 GEN
Solar/Wind Harmer
6.448
970657AG2-426 GEN
Solar/Wind Harmer
1.348
970933AG2-581 GEN
Solar/Wind Harmer
19.327
944641AF1-129 GEN
Adder
87.32
316339AD2-160 GEN
Solar/Wind Harmer
1.387
316018AA1-139 ULT2
Solar/Wind Harmer
1.761
316017AA1-139 ULT1
Solar/Wind Harmer
1.663
316236AE1-162_GEN
Solar/Wind Harmer
0.619
3137176SLIGO L2192
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
2.424
3130086AYDLETT
Solar/Wind Harmer
-0.082
316033AB2-134 GEN
Solar/Wind Harmer
6.58
315697AD1-025 GEN
Solar/Wind Harmer
4.127
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.654
316433W1029_GEN2
Solar/Wind Harmer
3.654
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.58
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.715
3150701DARBY 4
Adder
12.685
3150681DARBY 2
Adder
12.67
3150671DARBY 1
Adder
12.655
315742AE1-103 GEN
Solar/Wind Harmer
2.07
3146376EDENTON
Solar/Wind Harmer
0.584
3146376EDENTON
Solar/Wind Harmer
0.584
316075AC2-137 C
Solar/Wind Harmer
0.526
3142296MT RD221
Adder
0.55
970099AG2-077 GEN
Solar/Wind Harmer
24.26
316065AD1-022 GEN
Solar/Wind Harmer
9.447
3145893MURPHYS
Solar/Wind Harmer
0.526
3145893MURPHYS
Solar/Wind Harmer
-0.034
316441AF1-014 GEN
Solar/Wind Harmer
1.268
3146173TUNIS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.019
971741AH1-377 GEN
Solar/Wind Harmer
21.726
966871AG1-558 GEN
Solar/Wind Harmer
0.559
966871AG1-558 GEN
Solar/Wind Harmer
0.191
316181AB2-040 GEN
Solar/Wind Harmer
2.591
970301AG2-198 GEN
Solar/Wind Harmer
9.277
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.853
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
2.059
3145593CAROLNA
Solar/Wind Harmer
0.152
3145783HORNRTN
Solar/Wind Harmer
2.159
3145783HORNRTN
Solar/Wind Harmer
1.727
3145783HORNRTN
Solar/Wind Harmer
0.54
3145783HORNRTN
Solar/Wind Harmer
0.216
3145796HORNRTN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3144293JTRSVLE
Adder
0.505
3144293JTRSVLE
Adder
0.425
3150341NORNECKC1
Adder
1.555
3150341NORNECKC1
Adder
1.542
3150391LDYSMT3
Adder
18.23
972195AH1-682 GEN
Adder
2.396
316447AC1-158 HLD
Solar/Wind Helper
11.902
315651AD1-115 GEN
Solar/Wind Helper
1.457
316303AF2-085
50/50
3.765
971285AH1-108 GEN
50/50
1.513
315244AE2-183_ST
50/50
5.368
963041AG1-153 GEN
50/50
4.955
3147346CASHSCORNER
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.609
971281AH1-106 GEN
Solar/Wind Harmer
3.677
971283AH1-107 GEN
Solar/Wind Harmer
3.677
941031AE2-094 GEN
Solar/Wind Harmer
40.621
944011AF1-069 GEN
Solar/Wind Harmer
12.728
970673AG2-436 GEN
Solar/Wind Harmer
44.754
970673AG2-436 GEN
Solar/Wind Harmer
22.66
971967AH1-528 GEN
Solar/Wind Harmer
39.617
3143316POE
Solar/Wind Harmer
-0.083
3151081ELIZAR1
Adder
16.891
3151091ELIZAR2
Adder
16.598
316315AB2-025 C
Solar/Wind Harmer
0.558
3152611GOSPORTB
Adder
2.345
3152621GOSPORTC
Adder
1.99
3152601GOSPORTA
Adder
1.836
315814AE2-033 C
Solar/Wind Harmer
19.205
957871AF2-081 GEN
Solar/Wind Harmer
10.278
971445AH1-216 GEN
Solar/Wind Harmer
12.702
319010AE1-072 C
Solar/Wind Harmer
4.148
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.893
316349AD2-085 GEN
Solar/Wind Harmer
1.823
316311AC2-079 GEN
Solar/Wind Harmer
10.336
316305AF2-043 C
Solar/Wind Harmer
0.617
972265AH1-717 GEN
Adder
14.121
3151201GRAVEL4
Adder
13.238
3151191GRAVEL3
Adder
13.07
3151211GRAVEL5
Adder
13.07
316369SG1_INVT
Solar/Wind Harmer
3.645
315835AF2-110_GEN
Solar/Wind Harmer
2.55
316132AB2-190 GEN1
Solar/Wind Harmer
2.062
313526AB2-022
Solar/Wind Harmer
0.549
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.547
3146396TANGLEW
Solar/Wind Harmer
0.373
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
970085AG2-068 GEN
Solar/Wind Harmer
12.532
970581AG2-369 GEN
Solar/Wind Harmer
10.778
315611Z1-036_GEN2
Solar/Wind Harmer
4.908
3130156CHOWAN
Solar/Wind Harmer
-0.02
3130156CHOWAN
Solar/Wind Harmer
-0.02
315976AC1-164 GENA
Solar/Wind Harmer
20.509
316169AC1-164_GENC
Solar/Wind Harmer
17.718
315975AC1-164 GENB
Solar/Wind Harmer
0.607
957831AF2-077 GEN
Solar/Wind Harmer
0.583
3138283WHITEMARSH
Solar/Wind Harmer
0.03
971167AH1-042 GEN
Solar/Wind Harmer
18.644
316312AB1-027
Solar/Wind Harmer
0.652
315816AE2-034 GEN
Solar/Wind Harmer
1.563
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
965291AG1-394 GEN
Solar/Wind Harmer
1.688
315732AD1-074 GEN1
Solar/Wind Harmer
3.84
315733AD1-074 GEN2
Solar/Wind Harmer
3.84
315735AD1-075 GEN1
Solar/Wind Harmer
1.921
3143873LANEXA
Solar/Wind Harmer
-0.011
316318V4-068
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
-0.051
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
970601AG2-382 GEN
Solar/Wind Harmer
8.243
946281AF1-292 GEN
Solar/Wind Harmer
0.421
316314AB2-024 C
Solar/Wind Harmer
1.606
315662AE1-191 GEN
Solar/Wind Harmer
2.261
315666AE1-190 GEN
Solar/Wind Harmer
0.565
316059AD1-063 C
Solar/Wind Harmer
0.424
957601AF2-054 GEN
Solar/Wind Harmer
0.559
3141873WAN 176
Solar/Wind Harmer
-0.004
316087AB2-174 GEN
Solar/Wind Harmer
2.66
3146043SEABORD
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.14
3145513AHOSKIE
Solar/Wind Harmer
-0.019
315607AA1-063A GEN
Solar/Wind Harmer
1.878
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.073
315652AC1-086 GEN
Solar/Wind Harmer
20.696
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.006
972189AH1-679 GEN
Adder
2.721
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.071
970285AG2-188 GEN
Solar/Wind Harmer
15.636
315657AE1-056 GEN
Solar/Wind Harmer
6.696
972205AH1-687 GEN
Adder
6.614
3150411LDYSMT5
Adder
18.321
3150381LDYSMT2
Adder
17.534
972213AH1-691 GEN
Adder
2.966
972215AH1-692 GEN
Adder
2.966
316164AC1-076 GEN
Solar/Wind Helper
2.448
970831AG2-522 GEN
Solar/Wind Harmer
3.798
LAGNLTFEXP_LAGN->PJM
CLTF
6.822
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.257
TVALTFEXP_TVA->PJM
CLTF
3.456
CPLELTFEXP_CPLE->PJM
CLTF
9.69
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.259
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.42
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.761
MECLTFEXP_MEC->PJM
CLTF
3.094
SIGELTFEXP_SIGE->PJM
CLTF
0.094
NYPJM->LTFIMP_NY
CLTF
2.632
LGEELTFEXP_LGEE->PJM
CLTF
1.138
WECLTFEXP_WEC->PJM
CLTF
0.551

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:211.93 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:8350.21
MW Contribution:46.77
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
24.095
970119AG2-088 GEN
50/50
46.768
3150851SPRUNCC
50/50
1.653
3143096IRON208
50/50
1.481
316045AC1-158 PL2
Solar/Wind Harmer
23.52
3143226MDLTHAN
Solar/Wind Harmer
-0.039
3143526WINTERP
Solar/Wind Harmer
-0.201
3142543TWELFTH
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.149
3142416OLDCHRC
Solar/Wind Harmer
-0.097
3142416OLDCHRC
Solar/Wind Harmer
-0.037
940641AE2-051 GEN
Solar/Wind Harmer
34.79
944631AF1-128 GEN
Adder
157.238
315671AE2-027_GEN
Solar/Wind Harmer
27.738
939411AE1-173 GEN
Solar/Wind Harmer
184.612
316294AC1-161 GEN
Solar/Wind Harmer
11.936
970129AG2-093 GEN
Solar/Wind Harmer
8.413
316458AB2-190 GEN2
Solar/Wind Harmer
3.73
971069AG2-661 GEN
Solar/Wind Harmer
5.824
971647AH1-324 GEN
Solar/Wind Harmer
18.353
961611AG1-000B GEN
Solar/Wind Harmer
18.086
316192AB2-158 GEN
Solar/Wind Harmer
4.354
3151171GRAVELC
Adder
3.463
316159AE1-175 C
Solar/Wind Harmer
0.981
3145336SMITFLD
Solar/Wind Harmer
-0.145
944591AF1-124 GEN
Solar/Wind Harmer
166.698
316375AC2-012 GEN
Solar/Wind Harmer
12.618
3150981CHESPKA
Adder
4.052
970659AG2-427 GEN
Solar/Wind Harmer
19.373
966881AG1-559 GEN
Solar/Wind Harmer
0.375
3138126ROCKLANDING
Solar/Wind Harmer
0.112
316381AD1-082 GEN
Solar/Wind Harmer
3.341
970661AG2-428 GEN
Solar/Wind Harmer
38.595
971317AH1-138 GEN
Solar/Wind Harmer
4.533
316388AE2-253 GEN
Solar/Wind Harmer
2.44
316072AD1-144
Solar/Wind Harmer
0.731
3146456SLIGO L269
Solar/Wind Harmer
-0.036
316246AF1-032 C
Solar/Wind Harmer
0.728
316093AE2-104_GEN
Solar/Wind Harmer
10.418
3142433PROV 92
Solar/Wind Harmer
-0.143
3142433PROV 92
Adder
0.62
3142433PROV 92
Adder
0.62
972197AH1-683 GEN
Adder
6.656
972219AH1-694 GEN
Adder
4.792
3146516WINFALL
Solar/Wind Harmer
-0.114
3146516WINFALL
Solar/Wind Harmer
-0.035
971777AH1-397 GEN
Solar/Wind Harmer
4.114
3141843SHACKLE
Adder
1.591
3141766HARMONY
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
8.589
3130156CHOWAN
Solar/Wind Harmer
-0.034
3143336POWHATN
Solar/Wind Harmer
4.05
3138133OCRAN
Solar/Wind Harmer
-0.02
3145663CRESWEL
Solar/Wind Harmer
-0.094
971163AH1-040 GEN
Solar/Wind Harmer
31.545
970919AG2-571 GEN
Solar/Wind Harmer
10.592
970087AG2-069 GEN
Solar/Wind Harmer
31.254
316023GEN1_S
Solar/Wind Harmer
2.215
961951AG1-038 GEN
Solar/Wind Harmer
4.322
316336AC2-165 C
Solar/Wind Harmer
5.691
3146206CASHIE
Solar/Wind Harmer
-0.033
971547AH1-271 GEN
Solar/Wind Harmer
8.17
3145893MURPHYS
Solar/Wind Harmer
-0.13
3145893MURPHYS
Solar/Wind Harmer
0.967
962861AG1-135 GEN
Solar/Wind Harmer
12.147
3146173TUNIS
Solar/Wind Harmer
-0.032
957481AF2-042 GEN
Solar/Wind Harmer
100.212
960081AF2-299 GEN
Solar/Wind Harmer
3.604
3145683EARLEYS
Solar/Wind Harmer
-0.032
3146263WOODLND
Solar/Wind Harmer
-0.032
964211AG1-282 GEN
Solar/Wind Harmer
0.954
3141726DUNNSVL
Solar/Wind Harmer
-0.126
316011AB1-132 GEN
Solar/Wind Harmer
6.592
962571AG1-106 GEN
Solar/Wind Harmer
4.529
3145963POPLR C
Solar/Wind Harmer
-0.031
315693AD1-088 GEN
Solar/Wind Harmer
15.742
971795AH1-408 GEN
Solar/Wind Harmer
23.556
3145823KELFORD
Solar/Wind Harmer
-0.031
962491AG1-098 GEN
Solar/Wind Harmer
20.998
316190AA2-174 GEN
Solar/Wind Harmer
0.385
316174AB2-169 GEN
Solar/Wind Harmer
4.817
3150351NORNECKC2
Adder
2.771
3147043LAWRENC
Adder
2.506
3145783HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.031
3144293JTRSVLE
Adder
0.817
972277AH1-723 GEN
Adder
129.895
3151751LOISA D
Adder
13.353
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.373
237080AD1-060 GEN
Solar/Wind Helper
0.304
237038AE2-054 C
Solar/Wind Helper
0.241
235062AE1-101 C1
Solar/Wind Helper
1.47
966131AG1-482 GEN
Solar/Wind Helper
0.075
233930AB2-032 GEN
Solar/Wind Helper
0.369
233915AB1-141 GEN
Solar/Wind Helper
0.487
232422X3-066 FULL
Solar/Wind Helper
0.111
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.492
232428Y3-058 C
Solar/Wind Helper
0.328
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.113
233972AC1-094 C
Solar/Wind Helper
0.293
238148AE2-230_GEN2
Solar/Wind Helper
0.391
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.126
20720728JCB_W1-129
Solar/Wind Helper
0.055
971133AH1-012 GEN
50/50
6.863
3142296MT RD221
50/50
1.135
3142366NRTHEST
50/50
1.158
3150691DARBY 3
50/50
25.424
3150701DARBY 4
50/50
25.364
3150681DARBY 2
50/50
25.335
316447AC1-158 HLD
Solar/Wind Harmer
16.169
971223AH1-071 GEN
Solar/Wind Harmer
4.926
3143526WINTERP
Solar/Wind Harmer
-0.201
3150671DARBY 1
Adder
23.848
944641AF1-129 GEN
Adder
157.758
316240AF1-291 C
Solar/Wind Harmer
1.119
316075AC2-137 C
Solar/Wind Harmer
0.997
3142946ENON
Solar/Wind Harmer
-0.004
316033AB2-134 GEN
Solar/Wind Harmer
11.856
315697AD1-025 GEN
Solar/Wind Harmer
7.436
316236AE1-162_GEN
Solar/Wind Harmer
1.101
316036AC1-147 C
Solar/Wind Harmer
0.984
3150991CHESPKB
Adder
3.399
3150991CHESPKB
Adder
3.318
957411AF2-035 GEN
Solar/Wind Harmer
16.399
970317AG2-208 GEN
Solar/Wind Harmer
15.944
316316AC1-027 C
Solar/Wind Harmer
1.117
3142956BIRDNECK
Solar/Wind Harmer
1.953
970657AG2-426 GEN
Solar/Wind Harmer
11.372
970657AG2-426 GEN
Solar/Wind Harmer
2.378
316185AD1-033 GEN
Solar/Wind Harmer
3.837
3145506HICKORY
Solar/Wind Harmer
-0.144
3145506HICKORY
Solar/Wind Harmer
-0.087
3145506HICKORY
Solar/Wind Harmer
-0.022
316339AD2-160 GEN
Solar/Wind Harmer
2.44
315673AE1-157 GEN
Solar/Wind Harmer
27.13
316018AA1-139 ULT2
Solar/Wind Harmer
3.096
316017AA1-139 ULT1
Solar/Wind Harmer
2.925
966871AG1-558 GEN
Solar/Wind Harmer
1.086
966871AG1-558 GEN
Solar/Wind Harmer
0.372
3137176SLIGO L2192
Solar/Wind Harmer
-0.143
3146456SLIGO L269
Solar/Wind Harmer
4.26
3130086AYDLETT
Solar/Wind Harmer
-0.143
3146386ELIZ CT
Solar/Wind Harmer
-0.036
3150391LDYSMT3
Adder
42.542
972195AH1-682 GEN
Adder
5.591
3144356SAPONY
Solar/Wind Harmer
1.235
316431W1029_GEN1
Solar/Wind Harmer
6.407
316433W1029_GEN2
Solar/Wind Harmer
6.407
3146516WINFALL
Solar/Wind Harmer
-0.035
3146516WINFALL
Solar/Wind Harmer
-0.035
3146516WINFALL
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.035
972185AH1-677 GEN
Adder
17.515
316441AF1-014 GEN
Solar/Wind Harmer
2.358
972187AH1-678 GEN
Adder
8.788
315742AE1-103 GEN
Solar/Wind Harmer
3.612
3146376EDENTON
Solar/Wind Harmer
1.02
3146376EDENTON
Solar/Wind Harmer
1.02
970933AG2-581 GEN
Solar/Wind Harmer
32.018
316487AF1-042 GEN
Solar/Wind Harmer
4.322
316065AD1-022 GEN
Solar/Wind Harmer
16.398
3145893MURPHYS
Solar/Wind Harmer
0.909
3145893MURPHYS
Solar/Wind Harmer
-0.059
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
958261AF2-120 GEN
Solar/Wind Harmer
12.494
970099AG2-077 GEN
Solar/Wind Harmer
40.085
316181AB2-040 GEN
Solar/Wind Harmer
4.418
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.171
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
966811AG1-552 GEN
Solar/Wind Harmer
3.517
3145593CAROLNA
Solar/Wind Harmer
0.26
316077AC2-138 C
Solar/Wind Harmer
0.659
3150341NORNECKC1
Adder
2.91
3150341NORNECKC1
Adder
2.887
3145783HORNRTN
Solar/Wind Harmer
3.688
3145783HORNRTN
Solar/Wind Harmer
2.95
3145783HORNRTN
Solar/Wind Harmer
0.922
3145783HORNRTN
Solar/Wind Harmer
0.369
3145796HORNRTN
Solar/Wind Harmer
-0.093
316468AD1-105 GEN
Solar/Wind Harmer
3.393
3144293JTRSVLE
Adder
0.817
3144293JTRSVLE
Adder
0.688
3151731LOISA B
Adder
13.353
3151721LOISA A
Adder
13.284
226929AD2-058 GEN
Solar/Wind Helper
0.107
23777801MSM_W1-116
Solar/Wind Helper
0.111
237025AB1-124 C
Solar/Wind Helper
0.161
237006AB1-125 GEN
Solar/Wind Helper
0.121
237034AC2-136 C
Solar/Wind Helper
0.211
23777901MDS_W4-102
Solar/Wind Helper
0.157
235020AA1-095 C
Solar/Wind Helper
0.046
237001AB1-127_GEN
Solar/Wind Helper
0.396
237002AB1-128_GEN
Solar/Wind Helper
0.396
235063AE1-101 C2
Solar/Wind Helper
1.47
238175AF1-290_GEN
Solar/Wind Helper
0.127
238169AE2-226 GEN1
Solar/Wind Helper
0.579
238170AE2-226 GEN2
Solar/Wind Helper
0.579
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
205916AD1-020 GEN
Solar/Wind Helper
1.657
233933AB2-153 GEN
Solar/Wind Helper
0.225
233987AB2-037 GEN
Solar/Wind Helper
2.27
233944AB2-135 GEN
Solar/Wind Helper
0.571
232424Y1-079 C
Solar/Wind Helper
0.113
233946AB2-136 GEN
Solar/Wind Helper
0.551
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.492
232410W1-006 C
Solar/Wind Helper
0.492
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
20390526W1-045 C
Solar/Wind Helper
0.328
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
3152261N ANNA2
50/50
24.093
970497AG2-320 GEN
50/50
31.984
3150861SPRUNCD
50/50
1.653
971645AH1-323 GEN
50/50
29.901
3143096IRON208
50/50
1.481
3143096IRON208
50/50
1.451
316044AC1-158 PL1
Solar/Wind Harmer
7.353
316450AC1-158 RIC
Solar/Wind Harmer
1.961
3147666LOUISA
Solar/Wind Harmer
-0.086
3142416OLDCHRC
Solar/Wind Harmer
3.768
970293AG2-193 GEN
Solar/Wind Harmer
4.65
315839AE2-212 C
Solar/Wind Harmer
1.116
970133AG2-095 GEN
Solar/Wind Harmer
4.162
965281AG1-393 GEN
Solar/Wind Harmer
4.621
3142946ENON
Solar/Wind Harmer
-0.012
315773AC2-141 GEN
Solar/Wind Harmer
15.437
970129AG2-093 GEN
Solar/Wind Harmer
20.77
315778AD1-151 GEN
Solar/Wind Harmer
31.888
315813AE1-149 C
Solar/Wind Harmer
22.914
961611AG1-000B GEN
Solar/Wind Harmer
7.717
3151221GRAVEL6
Adder
23.669
3151171GRAVELC
Adder
4.554
316382AG1-145 C
Solar/Wind Harmer
1.101
3145336SMITFLD
Solar/Wind Harmer
-0.014
944581AF1-123 GEN
Solar/Wind Harmer
166.1
944601AF1-125 GEN
Solar/Wind Harmer
163.508
3144536CHRHLND
Solar/Wind Harmer
-0.006
3151101ELIZAR3
Adder
30.141
970659AG2-427 GEN
Solar/Wind Harmer
3.433
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3144216WINCHST
Adder
1.223
966881AG1-559 GEN
Solar/Wind Harmer
1.096
316083AB2-161 GEN
Solar/Wind Harmer
5.913
3150921YORKTN3
Adder
8.144
970661AG2-428 GEN
Solar/Wind Harmer
6.84
316473AC1-191 GEN
Solar/Wind Harmer
3.887
3146456SLIGO L269
Solar/Wind Harmer
-0.036
971153AH1-033 GEN
Solar/Wind Harmer
4.397
3142433PROV 92
Adder
0.62
3142433PROV 92
Adder
0.62
316320Y1-086
Solar/Wind Harmer
2.093
3150401LDYSMT4
Adder
42.622
3150371LDYSMT1
Adder
41.184
316435W1029_GEN3
Solar/Wind Harmer
6.407
3146516WINFALL
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.035
3141843SHACKLE
Adder
1.591
316203AE2-005 GEN
Solar/Wind Harmer
14.749
3145273HOLLAND
Solar/Wind Harmer
-0.026
3141766HARMONY
Solar/Wind Harmer
3.112
316280AD1-041 GEN
Solar/Wind Harmer
2.627
316156AD2-030 GEN
Solar/Wind Harmer
0.927
3141873WAN 176
Solar/Wind Harmer
4.119
3146376EDENTON
Solar/Wind Harmer
-0.034
316313AB2-026
Solar/Wind Harmer
0.92
316258AE1-075 C
Solar/Wind Harmer
0.829
316405AF2-144 C
Solar/Wind Harmer
0.874
3143336POWHATN
Solar/Wind Harmer
3.443
315614AA2-178 GEN
Solar/Wind Harmer
3.63
970917AG2-570 GEN
Solar/Wind Harmer
83.678
962971AG1-146 GEN
Solar/Wind Harmer
6.217
971157AH1-035 GEN
Solar/Wind Harmer
4.137
3156081AA2-088 GEN
Solar/Wind Harmer
10.718
315737AD1-076 GEN
Solar/Wind Harmer
6.272
316365GEN2_N
Solar/Wind Harmer
2.215
316484AD2-074 GEN
Solar/Wind Harmer
8.259
970009AG2-005 GEN
Solar/Wind Harmer
4.101
3146206CASHIE
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
-0.032
957521AF2-046 GEN
Solar/Wind Harmer
25.606
961681AG1-008 GEN
Solar/Wind Harmer
25.606
3146173TUNIS
Solar/Wind Harmer
-0.032
316404AE1-155 C
Solar/Wind Harmer
6.22
3156021HOLLOMANSOL
Solar/Wind Harmer
4.342
316463AE2-346 GEN
Solar/Wind Harmer
0.52
316140AB2-099
Solar/Wind Harmer
0.217
962331AG1-082 GEN
Solar/Wind Harmer
4.019
966621AG1-532 GEN
Solar/Wind Harmer
0.65
3146263WOODLND
Solar/Wind Harmer
-0.032
313506AB2-031 GEN
Solar/Wind Harmer
2.546
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316317KELFORD C
Solar/Wind Harmer
1.48
3145823KELFORD
Solar/Wind Harmer
-0.031
3150351NORNECKC2
Adder
2.817
3147043LAWRENC
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.031
316478AD1-087 GEN
Solar/Wind Harmer
2.676
316486AD2-202 GEN
Solar/Wind Harmer
0.784
3144293JTRSVLE
Adder
0.817
972255AH1-712 GEN
Adder
111.469
3151761LOISA E
Adder
27.223
972183AH1-676 GEN
Adder
213.104
3141316ARNOLDS
Adder
0.364
3150331BIRCHWDA
Adder
22.835
3151861LOWMORA
Adder
1.276
3141196NOKESVL
Solar/Wind Helper
1.408
227287AC2-120 GEN
Solar/Wind Helper
0.371
226910AB2-157 C
Solar/Wind Helper
0.015
237030AB1-096 C
Solar/Wind Helper
0.069
223402AF1-300 C
Solar/Wind Helper
0.373
238221AF1-254 C O1
Solar/Wind Helper
0.245
235067AD1-061 GEN
Solar/Wind Helper
0.438
205917AD1-020 ES
Solar/Wind Helper
0.356
233918AB1-142 GEN
Solar/Wind Helper
0.487
233982AB2-133 GEN
Solar/Wind Helper
0.347
233994AC2-023 GEN
Solar/Wind Helper
0.932
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.492
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
238147AE2-230_GEN1
Solar/Wind Helper
0.39
238149AF1-291A_GEN
Solar/Wind Helper
0.111
230430AE1-229_GEN
Solar/Wind Helper
3.256
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.11
959561AF2-247 GEN
Solar/Wind Helper
0.02
20716028EGP_W2-019
Solar/Wind Helper
0.018
20720828JCB_W4-025
Solar/Wind Helper
0.061
20715028HAN_X4-015
Solar/Wind Helper
0.055
971781AH1-399 GEN
Solar/Wind Harmer
0.994
316303AF2-085
50/50
6.236
971285AH1-108 GEN
50/50
2.704
316233AE1-074 FULL
Solar/Wind Harmer
1.044
971281AH1-106 GEN
Solar/Wind Harmer
6.308
971283AH1-107 GEN
Solar/Wind Harmer
6.308
316312AB1-027
Solar/Wind Harmer
1.259
972189AH1-679 GEN
Adder
5.56
316132AB2-190 GEN1
Solar/Wind Harmer
3.73
3143316POE
Solar/Wind Harmer
-0.145
316369SG1_INVT
Solar/Wind Harmer
6.568
315976AC1-164 GENA
Solar/Wind Harmer
38.783
316169AC1-164_GENC
Solar/Wind Harmer
33.504
315975AC1-164 GENB
Solar/Wind Harmer
1.147
972265AH1-717 GEN
Adder
25.277
3151201GRAVEL4
Adder
23.696
3151191GRAVEL3
Adder
23.396
3151211GRAVEL5
Adder
23.396
971445AH1-216 GEN
Solar/Wind Harmer
22.614
3151081ELIZAR1
Adder
29.76
3151091ELIZAR2
Adder
29.243
3152611GOSPORTB
Adder
4.132
3152621GOSPORTC
Adder
3.507
3152601GOSPORTA
Adder
3.235
957871AF2-081 GEN
Solar/Wind Harmer
18.071
315833AF1-017_GEN
Solar/Wind Harmer
6.849
316349AD2-085 GEN
Solar/Wind Harmer
3.207
316311AC2-079 GEN
Solar/Wind Harmer
18.186
319010AE1-072 C
Solar/Wind Harmer
7.291
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
1.085
941031AE2-094 GEN
Solar/Wind Harmer
67.43
944011AF1-069 GEN
Solar/Wind Harmer
21.128
971167AH1-042 GEN
Solar/Wind Harmer
34.583
315835AF2-110_GEN
Solar/Wind Harmer
4.479
3142433PROV 92
Adder
0.62
3142433PROV 92
Adder
0.62
313526AB2-022
Solar/Wind Harmer
0.963
3150411LDYSMT5
Adder
42.755
3150381LDYSMT2
Adder
40.918
972213AH1-691 GEN
Adder
6.922
972215AH1-692 GEN
Adder
6.922
3146486SUNBURY
Solar/Wind Harmer
-0.036
3146486SUNBURY
Solar/Wind Harmer
-0.036
957831AF2-077 GEN
Solar/Wind Harmer
1.07
3138283WHITEMARSH
Solar/Wind Harmer
0.055
316321Z2-027
Solar/Wind Harmer
0.959
3146396TANGLEW
Solar/Wind Harmer
0.654
3145176PASQUOTANK
Solar/Wind Harmer
-0.022
316315AB2-025 C
Solar/Wind Harmer
0.955
970673AG2-436 GEN
Solar/Wind Harmer
74.301
970673AG2-436 GEN
Solar/Wind Harmer
37.621
3143873LANEXA
Solar/Wind Harmer
-0.021
315814AE2-033 C
Solar/Wind Harmer
32.86
316314AB2-024 C
Solar/Wind Harmer
3.002
316059AD1-063 C
Solar/Wind Harmer
0.79
971967AH1-528 GEN
Solar/Wind Harmer
65.706
315662AE1-191 GEN
Solar/Wind Harmer
4.203
315666AE1-190 GEN
Solar/Wind Harmer
1.051
315611Z1-036_GEN2
Solar/Wind Harmer
8.589
957601AF2-054 GEN
Solar/Wind Harmer
1.038
3141873WAN 176
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.034
3130156CHOWAN
Solar/Wind Harmer
-0.034
3141913WHIT STONE
Solar/Wind Harmer
-0.034
3138133OCRAN
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.02
3141783LANCAST
Solar/Wind Harmer
-0.013
315816AE2-034 GEN
Solar/Wind Harmer
2.723
970085AG2-068 GEN
Solar/Wind Harmer
20.836
970581AG2-369 GEN
Solar/Wind Harmer
17.919
962981AG1-147 GEN
Solar/Wind Harmer
14.507
3130546PLYMOUTH
Solar/Wind Harmer
-0.033
315732AD1-074 GEN1
Solar/Wind Harmer
6.673
315733AD1-074 GEN2
Solar/Wind Harmer
6.673
315735AD1-075 GEN1
Solar/Wind Harmer
3.338
965291AG1-394 GEN
Solar/Wind Harmer
2.918
3146206CASHIE
Solar/Wind Harmer
-0.033
970601AG2-382 GEN
Solar/Wind Harmer
14.298
316318V4-068
Solar/Wind Harmer
0.812
3145893MURPHYS
Solar/Wind Harmer
-0.087
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145513AHOSKIE
Solar/Wind Harmer
0.28
961941AG1-037 GEN
Solar/Wind Harmer
0.242
3145513AHOSKIE
Solar/Wind Harmer
-0.032
946281AF1-292 GEN
Solar/Wind Harmer
0.718
3145683EARLEYS
Solar/Wind Harmer
-0.064
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.032
3146043SEABORD
Solar/Wind Harmer
-0.032
315607AA1-063A GEN
Solar/Wind Harmer
3.223
316087AB2-174 GEN
Solar/Wind Harmer
4.534
315652AC1-086 GEN
Solar/Wind Harmer
35.448
3137643SOCKMAN
Solar/Wind Harmer
-0.125
3141813NORNECK
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.123
972205AH1-687 GEN
Adder
9.958
972193AH1-681 GEN
Adder
4.981
3151881LOWMORC
Adder
1.266
3151881LOWMORC
Adder
1.246
3151861LOWMORA
Adder
1.226
316411AF1-147_GEN1
Solar/Wind Helper
1.074
316415AF1-147_GEN2
Solar/Wind Helper
1.074
3138216PACIFIC
Solar/Wind Helper
0.052
237085AD2-009_GEN
Solar/Wind Helper
1.439
238208AF1-136 C
Solar/Wind Helper
0.182
960921AF2-383 GEN
Solar/Wind Helper
0.176
205943AE1-185 GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.231
205932AD2-116_GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.929
233990AG1-397 GEN
Solar/Wind Helper
0.029
234033AF1-007_GEN
Solar/Wind Helper
6.804
232432Z2-076 GEN
Solar/Wind Helper
0.065
238152AF2-075_GEN
Solar/Wind Helper
0.557
959381AF2-229 GEN
Solar/Wind Helper
0.335
964001AG1-254 GEN
Solar/Wind Helper
0.923
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.092
20715828PEM_W1-120
Solar/Wind Helper
0.092
LAGNLTFEXP_LAGN->PJM
CLTF
11.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.13
TVALTFEXP_TVA->PJM
CLTF
6.026
CPLELTFEXP_CPLE->PJM
CLTF
16.389
CBM West 2LTFEXP_CBM-W2->PJM
CBM
62.285
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.397
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.604
MECLTFEXP_MEC->PJM
CLTF
5.595
SIGELTFEXP_SIGE->PJM
CLTF
0.171
NYPJM->LTFIMP_NY
CLTF
4.81
LGEELTFEXP_LGEE->PJM
CLTF
2.081
WECLTFEXP_WEC->PJM
CLTF
1.018

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.6 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:5693.43
MW Contribution:34.68
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
19.45
971507AH1-251 GEN
50/50
16.115
970119AG2-088 GEN
50/50
34.68
3150851SPRUNCC
50/50
1.198
3143096IRON208
50/50
1.065
316045AC1-158 PL2
Solar/Wind Harmer
21.331
3147666LOUISA
Solar/Wind Harmer
-0.117
3143226MDLTHAN
Solar/Wind Harmer
-0.029
316192AB2-158 GEN
Solar/Wind Harmer
3.431
3143526WINTERP
Solar/Wind Harmer
-0.147
940641AE2-051 GEN
Solar/Wind Harmer
25.691
939411AE1-173 GEN
Solar/Wind Harmer
135.819
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.675
315671AE2-027_GEN
Solar/Wind Harmer
20.092
970129AG2-093 GEN
Solar/Wind Harmer
6.077
316458AB2-190 GEN2
Solar/Wind Harmer
2.695
944631AF1-128 GEN
Adder
112.977
971069AG2-661 GEN
Solar/Wind Harmer
4.21
944591AF1-124 GEN
Solar/Wind Harmer
121.264
971647AH1-324 GEN
Solar/Wind Harmer
13.278
961611AG1-000B GEN
Solar/Wind Harmer
13.092
316375AC2-012 GEN
Solar/Wind Harmer
9.174
3150981CHESPKA
Adder
2.946
970659AG2-427 GEN
Solar/Wind Harmer
14.084
3145336SMITFLD
Solar/Wind Harmer
-0.105
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
2.508
316381AD1-082 GEN
Solar/Wind Harmer
2.429
970661AG2-428 GEN
Solar/Wind Harmer
28.06
3138126ROCKLANDING
Solar/Wind Harmer
0.081
316388AE2-253 GEN
Solar/Wind Harmer
1.774
316159AE1-175 C
Solar/Wind Harmer
0.706
316072AD1-144
Solar/Wind Harmer
0.531
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.53
971317AH1-138 GEN
Solar/Wind Harmer
3.272
316093AE2-104_GEN
Solar/Wind Harmer
7.576
3142433PROV 92
Solar/Wind Harmer
-0.103
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
966881AG1-559 GEN
Solar/Wind Harmer
0.262
971777AH1-397 GEN
Solar/Wind Harmer
2.977
3141843SHACKLE
Adder
1.151
3141766HARMONY
Solar/Wind Harmer
-0.005
315800Z1-036_GEN1
Solar/Wind Harmer
6.245
3143336POWHATN
Solar/Wind Harmer
2.977
3130156CHOWAN
Solar/Wind Harmer
-0.025
972197AH1-683 GEN
Adder
4.637
972219AH1-694 GEN
Adder
3.339
3138133OCRAN
Solar/Wind Harmer
-0.015
970919AG2-571 GEN
Solar/Wind Harmer
7.807
970087AG2-069 GEN
Solar/Wind Harmer
23.032
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.931
316336AC2-165 C
Solar/Wind Harmer
4.171
961951AG1-038 GEN
Solar/Wind Harmer
3.162
316023GEN1_S
Solar/Wind Harmer
1.617
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.939
962861AG1-135 GEN
Solar/Wind Harmer
8.906
3145893MURPHYS
Solar/Wind Harmer
-0.094
3145893MURPHYS
Solar/Wind Harmer
0.704
957481AF2-042 GEN
Solar/Wind Harmer
73.619
3146173TUNIS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.629
964211AG1-282 GEN
Solar/Wind Harmer
0.702
3141726DUNNSVL
Solar/Wind Harmer
-0.093
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
315693AD1-088 GEN
Solar/Wind Harmer
11.547
3150351NORNECKC2
Adder
2.044
962491AG1-098 GEN
Solar/Wind Harmer
15.398
316011AB1-132 GEN
Solar/Wind Harmer
4.801
962571AG1-106 GEN
Solar/Wind Harmer
3.298
971795AH1-408 GEN
Solar/Wind Harmer
17.176
3145963POPLR C
Solar/Wind Harmer
-0.023
316190AA2-174 GEN
Solar/Wind Harmer
0.281
3145823KELFORD
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.498
3147043LAWRENC
Adder
1.827
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.074
3145796HORNRTN
Solar/Wind Harmer
-0.023
3144293JTRSVLE
Adder
0.594
3151751LOISA D
Adder
10.119
972277AH1-723 GEN
Adder
86.298
316006AB2-029 C
Solar/Wind Helper
0.108
3152261N ANNA2
50/50
19.448
3150861SPRUNCD
50/50
1.198
3143096IRON208
50/50
1.065
3143096IRON208
50/50
1.043
316044AC1-158 PL1
Solar/Wind Harmer
6.668
316450AC1-158 RIC
Solar/Wind Harmer
1.778
3147666LOUISA
Solar/Wind Harmer
-0.067
315839AE2-212 C
Solar/Wind Harmer
0.81
315773AC2-141 GEN
Solar/Wind Harmer
11.22
965281AG1-393 GEN
Solar/Wind Harmer
3.35
970133AG2-095 GEN
Solar/Wind Harmer
3.004
315813AE1-149 C
Solar/Wind Harmer
16.657
970129AG2-093 GEN
Solar/Wind Harmer
15.004
315778AD1-151 GEN
Solar/Wind Harmer
23.05
944581AF1-123 GEN
Solar/Wind Harmer
120.829
944601AF1-125 GEN
Solar/Wind Harmer
118.944
970293AG2-193 GEN
Solar/Wind Harmer
3.321
3151101ELIZAR3
Adder
21.915
961611AG1-000B GEN
Solar/Wind Harmer
5.586
3144536CHRHLND
Solar/Wind Harmer
-0.004
3142946ENON
Solar/Wind Harmer
-0.009
970659AG2-427 GEN
Solar/Wind Harmer
2.496
3145336SMITFLD
Solar/Wind Harmer
-0.01
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142416OLDCHRC
Solar/Wind Harmer
2.673
3151221GRAVEL6
Adder
17.144
3151171GRAVELC
Adder
3.298
316083AB2-161 GEN
Solar/Wind Harmer
4.299
970661AG2-428 GEN
Solar/Wind Harmer
4.973
3144216WINCHST
Adder
0.884
3150921YORKTN3
Adder
5.882
316382AG1-145 C
Solar/Wind Harmer
0.792
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.198
316320Y1-086
Solar/Wind Harmer
1.522
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
316473AC1-191 GEN
Solar/Wind Harmer
2.772
316435W1029_GEN3
Solar/Wind Harmer
4.659
3146516WINFALL
Solar/Wind Harmer
-0.026
966881AG1-559 GEN
Solar/Wind Harmer
0.767
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
3141843SHACKLE
Adder
1.151
316203AE2-005 GEN
Solar/Wind Harmer
10.672
3141766HARMONY
Solar/Wind Harmer
2.25
316280AD1-041 GEN
Solar/Wind Harmer
1.902
316156AD2-030 GEN
Solar/Wind Harmer
0.672
3141873WAN 176
Solar/Wind Harmer
2.985
316313AB2-026
Solar/Wind Harmer
0.677
316258AE1-075 C
Solar/Wind Harmer
0.609
316405AF2-144 C
Solar/Wind Harmer
0.643
3143336POWHATN
Solar/Wind Harmer
2.53
3146376EDENTON
Solar/Wind Harmer
-0.025
3150401LDYSMT4
Adder
29.698
3150371LDYSMT1
Adder
28.696
970917AG2-570 GEN
Solar/Wind Harmer
61.676
315614AA2-178 GEN
Solar/Wind Harmer
2.639
962971AG1-146 GEN
Solar/Wind Harmer
4.54
971157AH1-035 GEN
Solar/Wind Harmer
3.007
3156081AA2-088 GEN
Solar/Wind Harmer
7.797
316484AD2-074 GEN
Solar/Wind Harmer
6.042
970009AG2-005 GEN
Solar/Wind Harmer
3
315737AD1-076 GEN
Solar/Wind Harmer
4.558
316365GEN2_N
Solar/Wind Harmer
1.617
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.564
957521AF2-046 GEN
Solar/Wind Harmer
18.624
961681AG1-008 GEN
Solar/Wind Harmer
18.624
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.157
316463AE2-346 GEN
Solar/Wind Harmer
0.378
316140AB2-099
Solar/Wind Harmer
0.158
962331AG1-082 GEN
Solar/Wind Harmer
2.922
966621AG1-532 GEN
Solar/Wind Harmer
0.474
3146263WOODLND
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.855
3150351NORNECKC2
Adder
2.079
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.076
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.962
316486AD2-202 GEN
Solar/Wind Harmer
0.574
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.023
3144293JTRSVLE
Adder
0.594
3151761LOISA E
Adder
20.63
972183AH1-676 GEN
Adder
160.944
972255AH1-712 GEN
Adder
74.056
3141316ARNOLDS
Adder
0.31
3150331BIRCHWDA
Adder
20.259
3141196NOKESVL
Solar/Wind Helper
0.97
971133AH1-012 GEN
50/50
5.464
944641AF1-129 GEN
50/50
120.961
3142366NRTHEST
50/50
0.827
3150691DARBY 3
50/50
18.162
3150701DARBY 4
50/50
18.119
316447AC1-158 HLD
Solar/Wind Harmer
14.664
971223AH1-071 GEN
Solar/Wind Harmer
3.653
3143526WINTERP
Solar/Wind Harmer
-0.147
316240AF1-291 C
Solar/Wind Harmer
0.81
3150681DARBY 2
Adder
17.056
3150671DARBY 1
Adder
17.036
3142296MT RD221
Adder
0.757
316033AB2-134 GEN
Solar/Wind Harmer
8.573
315697AD1-025 GEN
Solar/Wind Harmer
5.377
316036AC1-147 C
Solar/Wind Harmer
0.715
3150991CHESPKB
Adder
2.471
3150991CHESPKB
Adder
2.412
3142946ENON
Solar/Wind Harmer
-0.003
316236AE1-162_GEN
Solar/Wind Harmer
0.799
316316AC1-027 C
Solar/Wind Harmer
0.813
3142956BIRDNECK
Solar/Wind Harmer
1.42
970657AG2-426 GEN
Solar/Wind Harmer
8.268
970657AG2-426 GEN
Solar/Wind Harmer
1.729
316185AD1-033 GEN
Solar/Wind Harmer
2.79
3145506HICKORY
Solar/Wind Harmer
-0.105
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316075AC2-137 C
Solar/Wind Harmer
0.712
316339AD2-160 GEN
Solar/Wind Harmer
1.774
316018AA1-139 ULT2
Solar/Wind Harmer
2.252
316017AA1-139 ULT1
Solar/Wind Harmer
2.127
3137176SLIGO L2192
Solar/Wind Harmer
-0.104
3146456SLIGO L269
Solar/Wind Harmer
3.098
3130086AYDLETT
Solar/Wind Harmer
-0.104
3146386ELIZ CT
Solar/Wind Harmer
-0.026
3144356SAPONY
Solar/Wind Harmer
0.905
972185AH1-677 GEN
Adder
12.941
966871AG1-558 GEN
Solar/Wind Harmer
0.774
966871AG1-558 GEN
Solar/Wind Harmer
0.265
316431W1029_GEN1
Solar/Wind Harmer
4.659
316433W1029_GEN2
Solar/Wind Harmer
4.659
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
972187AH1-678 GEN
Adder
6.489
957411AF2-035 GEN
Solar/Wind Harmer
11.475
970317AG2-208 GEN
Solar/Wind Harmer
11.157
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316441AF1-014 GEN
Solar/Wind Harmer
1.706
315673AE1-157 GEN
Solar/Wind Harmer
18.955
970933AG2-581 GEN
Solar/Wind Harmer
23.615
315742AE1-103 GEN
Solar/Wind Harmer
2.627
3146376EDENTON
Solar/Wind Harmer
0.741
3146376EDENTON
Solar/Wind Harmer
0.741
3150391LDYSMT3
Adder
29.642
972195AH1-682 GEN
Adder
3.895
316487AF1-042 GEN
Solar/Wind Harmer
3.162
316065AD1-022 GEN
Solar/Wind Harmer
11.919
3145893MURPHYS
Solar/Wind Harmer
0.662
3145893MURPHYS
Solar/Wind Harmer
-0.043
958261AF2-120 GEN
Solar/Wind Harmer
9.168
970099AG2-077 GEN
Solar/Wind Harmer
29.447
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.22
316077AC2-138 C
Solar/Wind Harmer
0.486
3150341NORNECKC1
Adder
2.147
3150341NORNECKC1
Adder
2.13
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.308
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.56
3145593CAROLNA
Solar/Wind Harmer
0.189
3145783HORNRTN
Solar/Wind Harmer
2.684
3145783HORNRTN
Solar/Wind Harmer
2.147
3145783HORNRTN
Solar/Wind Harmer
0.671
3145783HORNRTN
Solar/Wind Harmer
0.268
3145796HORNRTN
Solar/Wind Harmer
-0.067
3144293JTRSVLE
Adder
0.594
3144293JTRSVLE
Adder
0.5
3151731LOISA B
Adder
10.119
3151721LOISA A
Adder
10.067
316468AD1-105 GEN
Solar/Wind Harmer
1.252
971531AH1-263 GEN
50/50
59.005
316303AF2-085
50/50
4.624
971285AH1-108 GEN
50/50
1.961
970603AG2-384 GEN
50/50
5.102
316164AC1-076 GEN
Solar/Wind Harmer
2.874
316233AE1-074 FULL
Solar/Wind Harmer
0.766
971281AH1-106 GEN
Solar/Wind Harmer
4.628
971283AH1-107 GEN
Solar/Wind Harmer
4.628
3143316POE
Solar/Wind Harmer
-0.106
316132AB2-190 GEN1
Solar/Wind Harmer
2.695
941031AE2-094 GEN
Solar/Wind Harmer
49.887
944011AF1-069 GEN
Solar/Wind Harmer
15.631
316369SG1_INVT
Solar/Wind Harmer
4.75
3151081ELIZAR1
Adder
21.638
3151091ELIZAR2
Adder
21.263
3152611GOSPORTB
Adder
3.004
3152621GOSPORTC
Adder
2.55
3152601GOSPORTA
Adder
2.352
971445AH1-216 GEN
Solar/Wind Harmer
16.401
316312AB1-027
Solar/Wind Harmer
0.894
972265AH1-717 GEN
Adder
18.309
3151201GRAVEL4
Adder
17.164
3151191GRAVEL3
Adder
16.946
3151211GRAVEL5
Adder
16.946
957871AF2-081 GEN
Solar/Wind Harmer
13.142
315976AC1-164 GENA
Solar/Wind Harmer
27.715
316169AC1-164_GENC
Solar/Wind Harmer
23.943
315975AC1-164 GENB
Solar/Wind Harmer
0.82
315833AF1-017_GEN
Solar/Wind Harmer
4.98
316349AD2-085 GEN
Solar/Wind Harmer
2.332
316311AC2-079 GEN
Solar/Wind Harmer
13.224
319010AE1-072 C
Solar/Wind Harmer
5.302
972189AH1-679 GEN
Adder
3.909
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.789
970673AG2-436 GEN
Solar/Wind Harmer
54.922
970673AG2-436 GEN
Solar/Wind Harmer
27.809
315835AF2-110_GEN
Solar/Wind Harmer
3.257
313526AB2-022
Solar/Wind Harmer
0.701
316315AB2-025 C
Solar/Wind Harmer
0.7
971167AH1-042 GEN
Solar/Wind Harmer
24.945
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.698
3146396TANGLEW
Solar/Wind Harmer
0.476
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
315814AE2-033 C
Solar/Wind Harmer
24.069
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
971967AH1-528 GEN
Solar/Wind Harmer
48.532
957831AF2-077 GEN
Solar/Wind Harmer
0.774
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143873LANEXA
Solar/Wind Harmer
-0.015
316314AB2-024 C
Solar/Wind Harmer
2.168
316059AD1-063 C
Solar/Wind Harmer
0.572
315611Z1-036_GEN2
Solar/Wind Harmer
6.245
315662AE1-191 GEN
Solar/Wind Harmer
3.043
315666AE1-190 GEN
Solar/Wind Harmer
0.761
957601AF2-054 GEN
Solar/Wind Harmer
0.752
3141873WAN 176
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3150411LDYSMT5
Adder
29.791
3150381LDYSMT2
Adder
28.511
972213AH1-691 GEN
Adder
4.823
972215AH1-692 GEN
Adder
4.823
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
970085AG2-068 GEN
Solar/Wind Harmer
15.354
970581AG2-369 GEN
Solar/Wind Harmer
13.205
315816AE2-034 GEN
Solar/Wind Harmer
1.979
962981AG1-147 GEN
Solar/Wind Harmer
10.594
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.85
315733AD1-074 GEN2
Solar/Wind Harmer
4.85
315735AD1-075 GEN1
Solar/Wind Harmer
2.426
965291AG1-394 GEN
Solar/Wind Harmer
2.123
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.393
316318V4-068
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145513AHOSKIE
Solar/Wind Harmer
0.204
961941AG1-037 GEN
Solar/Wind Harmer
0.176
3145513AHOSKIE
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.523
3146043SEABORD
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
315607AA1-063A GEN
Solar/Wind Harmer
2.345
316087AB2-174 GEN
Solar/Wind Harmer
3.305
3141813NORNECK
Solar/Wind Harmer
-0.023
315652AC1-086 GEN
Solar/Wind Harmer
25.813
3137643SOCKMAN
Solar/Wind Harmer
-0.091
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.009
972205AH1-687 GEN
Adder
7.173
972193AH1-681 GEN
Adder
3.309
316411AF1-147_GEN1
Solar/Wind Helper
0.769
316415AF1-147_GEN2
Solar/Wind Helper
0.769
3138216PACIFIC
Solar/Wind Helper
0.038
LAGNLTFEXP_LAGN->PJM
CLTF
7.753
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.482
TVALTFEXP_TVA->PJM
CLTF
3.93
CPLELTFEXP_CPLE->PJM
CLTF
11.751
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.921
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.526
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.238
MECLTFEXP_MEC->PJM
CLTF
3.227
SIGELTFEXP_SIGE->PJM
CLTF
0.097
NYPJM->LTFIMP_NY
CLTF
3.258
LGEELTFEXP_LGEE->PJM
CLTF
1.156
WECLTFEXP_WEC->PJM
CLTF
0.544

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.85 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5791.82
MW Contribution:35.34
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
19.951
971507AH1-251 GEN
50/50
16.627
970119AG2-088 GEN
50/50
35.342
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.079
3152331SURRY 2
50/50
9.986
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
9.742
3147666LOUISA
Solar/Wind Harmer
1.096
316192AB2-158 GEN
Solar/Wind Harmer
1.516
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.34
940641AE2-051 GEN
Solar/Wind Harmer
19.885
939411AE1-173 GEN
Solar/Wind Harmer
105.071
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.205
315671AE2-027_GEN
Solar/Wind Harmer
15.49
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
944591AF1-124 GEN
Solar/Wind Harmer
54.321
971069AG2-661 GEN
Solar/Wind Harmer
4.273
944631AF1-128 GEN
Adder
114.478
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.995
971647AH1-324 GEN
Solar/Wind Harmer
10.238
970659AG2-427 GEN
Solar/Wind Harmer
11.598
961611AG1-000B GEN
Solar/Wind Harmer
12.573
3145336SMITFLD
Solar/Wind Harmer
0.958
316381AD1-082 GEN
Solar/Wind Harmer
0.25
3151171GRAVELC
Adder
2.547
970661AG2-428 GEN
Solar/Wind Harmer
23.769
3142416OLDCHRC
Solar/Wind Harmer
0.62
3142416OLDCHRC
Solar/Wind Harmer
0.237
316388AE2-253 GEN
Solar/Wind Harmer
0.746
3138126ROCKLANDING
Solar/Wind Harmer
0.109
3146456SLIGO L269
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.086
316159AE1-175 C
Solar/Wind Harmer
0.205
316246AF1-032 C
Solar/Wind Harmer
0.107
971317AH1-138 GEN
Solar/Wind Harmer
1.763
316093AE2-104_GEN
Solar/Wind Harmer
3.967
3142433PROV 92
Solar/Wind Harmer
0.929
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
0.752
3146516WINFALL
Solar/Wind Harmer
0.232
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.063
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141843SHACKLE
Adder
1.161
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.226
966881AG1-559 GEN
Solar/Wind Harmer
0.262
970919AG2-571 GEN
Solar/Wind Harmer
7.971
970087AG2-069 GEN
Solar/Wind Harmer
17.86
3138133OCRAN
Solar/Wind Harmer
0.133
3145663CRESWEL
Solar/Wind Harmer
0.62
971163AH1-040 GEN
Solar/Wind Harmer
17.736
972197AH1-683 GEN
Adder
4.589
972219AH1-694 GEN
Adder
3.304
316336AC2-165 C
Solar/Wind Harmer
0.009
316023GEN1_S
Solar/Wind Harmer
0.488
3146206CASHIE
Solar/Wind Harmer
0.215
971547AH1-271 GEN
Solar/Wind Harmer
4.597
3145893MURPHYS
Solar/Wind Harmer
0.86
3145893MURPHYS
Solar/Wind Harmer
0.956
957481AF2-042 GEN
Solar/Wind Harmer
57.154
3146173TUNIS
Solar/Wind Harmer
0.213
960081AF2-299 GEN
Solar/Wind Harmer
2.037
962861AG1-135 GEN
Solar/Wind Harmer
6.776
3145683EARLEYS
Solar/Wind Harmer
0.211
315693AD1-088 GEN
Solar/Wind Harmer
10.092
3146263WOODLND
Solar/Wind Harmer
0.21
962491AG1-098 GEN
Solar/Wind Harmer
11.964
316011AB1-132 GEN
Solar/Wind Harmer
3.787
962571AG1-106 GEN
Solar/Wind Harmer
2.963
971795AH1-408 GEN
Solar/Wind Harmer
13.875
3145963POPLR C
Solar/Wind Harmer
0.207
3141726DUNNSVL
Solar/Wind Harmer
0.83
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.207
3147043LAWRENC
Adder
1.866
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3145783HORNRTN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.677
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.041
316212AC1-099_GEN
Solar/Wind Harmer
1.035
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.425
971133AH1-012 GEN
50/50
5.665
944641AF1-129 GEN
50/50
122.768
3142366NRTHEST
50/50
0.838
970533AG2-339 GEN
50/50
21.472
970531AG2-338 GEN
50/50
8.589
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.39
316447AC1-158 HLD
Solar/Wind Harmer
6.696
971223AH1-071 GEN
Solar/Wind Harmer
2.827
3143526WINTERP
Solar/Wind Harmer
1.34
316240AF1-291 C
Solar/Wind Harmer
0.002
3150701DARBY 4
Adder
17.29
3150681DARBY 2
Adder
17.27
3150671DARBY 1
Adder
17.25
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.27
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.513
3150991CHESPKB
Adder
2.452
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.23
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.383
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.955
3145506HICKORY
Solar/Wind Harmer
0.573
3145506HICKORY
Solar/Wind Harmer
0.143
316339AD2-160 GEN
Solar/Wind Harmer
0.386
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
316075AC2-137 C
Solar/Wind Harmer
0.065
3137176SLIGO L2192
Solar/Wind Harmer
0.945
3146456SLIGO L269
Solar/Wind Harmer
4.201
3130086AYDLETT
Solar/Wind Harmer
0.948
972185AH1-677 GEN
Adder
13.205
3144356SAPONY
Solar/Wind Harmer
1.967
3146386ELIZ CT
Solar/Wind Harmer
0.235
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.623
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
970933AG2-581 GEN
Solar/Wind Harmer
18.312
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.66
970317AG2-208 GEN
Solar/Wind Harmer
8.949
3146376EDENTON
Solar/Wind Harmer
1.006
3146376EDENTON
Solar/Wind Harmer
1.006
315673AE1-157 GEN
Solar/Wind Harmer
15.472
3150391LDYSMT3
Adder
29.334
972195AH1-682 GEN
Adder
3.855
316065AD1-022 GEN
Solar/Wind Harmer
9.955
3145893MURPHYS
Solar/Wind Harmer
1.439
3145893MURPHYS
Solar/Wind Harmer
0.387
970099AG2-077 GEN
Solar/Wind Harmer
22.861
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.972
316181AB2-040 GEN
Solar/Wind Harmer
0.304
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.125
316426AA2-053 GEN
Solar/Wind Harmer
0.701
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
966811AG1-552 GEN
Solar/Wind Harmer
2.242
3145593CAROLNA
Solar/Wind Harmer
0.257
3145783HORNRTN
Solar/Wind Harmer
3.653
3145783HORNRTN
Solar/Wind Harmer
2.922
3145783HORNRTN
Solar/Wind Harmer
0.913
3145783HORNRTN
Solar/Wind Harmer
0.365
3145796HORNRTN
Solar/Wind Harmer
0.615
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.144
3150341NORNECKC1
Adder
2.127
971741AH1-377 GEN
Solar/Wind Harmer
19.978
3145933PARMELE
Solar/Wind Harmer
0.398
3145933PARMELE
Solar/Wind Harmer
0.199
316274AC1-208 GEN
Solar/Wind Harmer
1.032
970301AG2-198 GEN
Solar/Wind Harmer
8.48
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
939181AE1-148 GEN
Solar/Wind Harmer
9.287
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.19
971775AH1-396 GEN
Solar/Wind Harmer
0.307
958211AF2-115 GEN
Solar/Wind Harmer
2.298
963191AG1-168 GEN
Solar/Wind Harmer
0.766
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.153
3145493TOT1
Solar/Wind Harmer
0.439
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
961601AG1-000A GEN
Solar/Wind Harmer
3.314
316263AC1-034 GEN
Solar/Wind Harmer
7.082
962561AG1-105 GEN
Solar/Wind Harmer
8.835
3146776BUCKING
Solar/Wind Harmer
0.73
3146776BUCKING
Solar/Wind Harmer
0.059
964791AG1-342 GEN
Solar/Wind Harmer
3.505
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
966001AG1-469 GEN
Solar/Wind Harmer
0.098
3151731LOISA B
Adder
10.898
3151721LOISA A
Adder
10.842
971489AH1-241 GEN
Solar/Wind Harmer
8.67
316222AC1-221 GEN
Solar/Wind Harmer
0.658
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.283
315651AD1-115 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315722AD1-056 GEN
Solar/Wind Harmer
1.233
316337AD2-073 GEN
Solar/Wind Harmer
0.169
970937AG2-583 GEN
Solar/Wind Harmer
11.922
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.649
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
14.314
963171AG1-166 GEN
Solar/Wind Harmer
1.021
971563AH1-280 GEN
Solar/Wind Harmer
2.042
3144293JTRSVLE
Adder
0.609
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.755
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.189
3145493TOT1
Solar/Wind Harmer
0.843
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.669
316049AB1-081 GEN
Solar/Wind Harmer
1.066
3142053HEARTS
Solar/Wind Harmer
0.328
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.073
970401AG2-262 GEN
Solar/Wind Harmer
1.071
972003AH1-546 GEN
Solar/Wind Harmer
7.446
316254AC1-120 GEN1
Solar/Wind Harmer
0.366
316003AC1-222 GEN
Solar/Wind Harmer
0.004
3151751LOISA D
Adder
10.898
972135AH1-637 GEN
Solar/Wind Harmer
1.429
971377AH1-170 GEN
Solar/Wind Harmer
1.734
3147623JAMES R
Solar/Wind Harmer
0.377
972277AH1-723 GEN
Adder
88.606
971531AH1-263 GEN
50/50
60.398
316303AF2-085
50/50
4.712
971285AH1-108 GEN
50/50
1.991
970603AG2-384 GEN
50/50
5.178
316164AC1-076 GEN
Solar/Wind Harmer
0.448
316233AE1-074 FULL
Solar/Wind Harmer
0.206
971281AH1-106 GEN
Solar/Wind Harmer
3.576
971283AH1-107 GEN
Solar/Wind Harmer
3.576
3143316POE
Solar/Wind Harmer
0.962
941031AE2-094 GEN
Solar/Wind Harmer
44.489
944011AF1-069 GEN
Solar/Wind Harmer
14.536
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
22.001
3151091ELIZAR2
Adder
21.619
3152611GOSPORTB
Adder
3.055
3152621GOSPORTC
Adder
2.593
3152601GOSPORTA
Adder
2.392
971445AH1-216 GEN
Solar/Wind Harmer
16.874
972265AH1-717 GEN
Adder
18.594
3151201GRAVEL4
Adder
17.43
3151191GRAVEL3
Adder
17.21
3151211GRAVEL5
Adder
17.21
316312AB1-027
Solar/Wind Harmer
0.427
957871AF2-081 GEN
Solar/Wind Harmer
11.843
970673AG2-436 GEN
Solar/Wind Harmer
50.646
970673AG2-436 GEN
Solar/Wind Harmer
33.764
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
319010AE1-072 C
Solar/Wind Harmer
1.195
316311AC2-079 GEN
Solar/Wind Harmer
6.813
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.491
316169AC1-164_GENC
Solar/Wind Harmer
21.158
315975AC1-164 GENB
Solar/Wind Harmer
0.725
315835AF2-110_GEN
Solar/Wind Harmer
1.619
316315AB2-025 C
Solar/Wind Harmer
0.19
313526AB2-022
Solar/Wind Harmer
0.127
972189AH1-679 GEN
Adder
3.932
3146486SUNBURY
Solar/Wind Harmer
0.234
3146486SUNBURY
Solar/Wind Harmer
0.234
971967AH1-528 GEN
Solar/Wind Harmer
37.517
315814AE2-033 C
Solar/Wind Harmer
18.537
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.645
3145176PASQUOTANK
Solar/Wind Harmer
0.145
971167AH1-042 GEN
Solar/Wind Harmer
20.705
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3138283WHITEMARSH
Solar/Wind Harmer
0.054
3143873LANEXA
Solar/Wind Harmer
0.138
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.735
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.226
3130156CHOWAN
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
0.045
970085AG2-068 GEN
Solar/Wind Harmer
11.907
970581AG2-369 GEN
Solar/Wind Harmer
10.24
3141913WHIT STONE
Solar/Wind Harmer
0.222
3138133OCRAN
Solar/Wind Harmer
0.066
315816AE2-034 GEN
Solar/Wind Harmer
0.951
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3150411LDYSMT5
Adder
29.481
3150381LDYSMT2
Adder
28.214
972213AH1-691 GEN
Adder
4.773
972215AH1-692 GEN
Adder
4.773
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.25
315733AD1-074 GEN2
Solar/Wind Harmer
1.25
315735AD1-075 GEN1
Solar/Wind Harmer
0.626
965291AG1-394 GEN
Solar/Wind Harmer
0.964
962981AG1-147 GEN
Solar/Wind Harmer
8.079
3146206CASHIE
Solar/Wind Harmer
0.215
970601AG2-382 GEN
Solar/Wind Harmer
8.044
3145893MURPHYS
Solar/Wind Harmer
0.581
3145893MURPHYS
Solar/Wind Harmer
0.215
970327AG2-215 GEN
Solar/Wind Harmer
7.032
3145513AHOSKIE
Solar/Wind Harmer
0.443
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.422
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.431
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.91
3137643SOCKMAN
Solar/Wind Harmer
0.831
3145796HORNRTN
Solar/Wind Harmer
0.656
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
0.813
970831AG2-522 GEN
Solar/Wind Harmer
8.493
316005AA1-067
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.776
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
970181AG2-120 GEN
Solar/Wind Harmer
2.429
957861AF2-080 GEN
Solar/Wind Harmer
8.286
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.225
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
12.781
970681AG2-440 GEN
Solar/Wind Harmer
10.225
946301AF1-294 GEN
Solar/Wind Harmer
3.778
961791AG1-021 GEN
Solar/Wind Harmer
1.838
315657AE1-056 GEN
Solar/Wind Harmer
6.598
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.189
3145573BETHELC
Solar/Wind Harmer
0.189
970285AG2-188 GEN
Solar/Wind Harmer
14.603
316223AC1-118
Solar/Wind Harmer
0.132
971845AH1-439 GEN
Solar/Wind Harmer
8.313
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.416
3147346CASHSCORNER
Solar/Wind Harmer
0.37
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971447AH1-217 GEN
Solar/Wind Harmer
4.798
970865AG2-541 GEN
Solar/Wind Harmer
5.388
972193AH1-681 GEN
Adder
3.397
270494AE1-108_GEN
Solar/Wind Harmer
1.716
316123AC1-075 GEN
Solar/Wind Harmer
0.194
970165AG2-112 GEN
Solar/Wind Harmer
1.153
970163AG2-111 GEN
Solar/Wind Harmer
1.1
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.82
316415AF1-147_GEN2
Solar/Wind Helper
0.82
3138216PACIFIC
Solar/Wind Helper
0.04
3152261N ANNA2
50/50
19.95
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.079
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.199
316044AC1-158 PL1
Solar/Wind Harmer
3.047
316450AC1-158 RIC
Solar/Wind Harmer
0.812
3147666LOUISA
Solar/Wind Harmer
0.63
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.863
965281AG1-393 GEN
Solar/Wind Harmer
2.583
970133AG2-095 GEN
Solar/Wind Harmer
2.314
315813AE1-149 C
Solar/Wind Harmer
12.857
970129AG2-093 GEN
Solar/Wind Harmer
14.547
944581AF1-123 GEN
Solar/Wind Harmer
54.129
944601AF1-125 GEN
Solar/Wind Harmer
53.295
315778AD1-151 GEN
Solar/Wind Harmer
19.229
3151101ELIZAR3
Adder
22.283
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.537
961611AG1-000B GEN
Solar/Wind Harmer
6.393
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.41
3151171GRAVELC
Adder
3.35
970293AG2-193 GEN
Solar/Wind Harmer
2.553
3142946ENON
Solar/Wind Harmer
0.08
970661AG2-428 GEN
Solar/Wind Harmer
5.055
3142416OLDCHRC
Solar/Wind Harmer
2.311
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
0.237
971153AH1-033 GEN
Solar/Wind Harmer
2.744
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
0.232
316473AC1-191 GEN
Solar/Wind Harmer
0.781
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.172
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.453
3141843SHACKLE
Adder
1.161
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
3.026
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.226
316156AD2-030 GEN
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
4.013
970917AG2-570 GEN
Solar/Wind Harmer
19.927
315614AA2-178 GEN
Solar/Wind Harmer
1.269
3150401LDYSMT4
Adder
29.389
3150371LDYSMT1
Adder
28.398
971157AH1-035 GEN
Solar/Wind Harmer
2.618
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.488
315737AD1-076 GEN
Solar/Wind Harmer
2.798
962971AG1-146 GEN
Solar/Wind Harmer
3.462
3146206CASHIE
Solar/Wind Harmer
0.215
3145893MURPHYS
Solar/Wind Harmer
0.36
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.963
961681AG1-008 GEN
Solar/Wind Harmer
15.963
970009AG2-005 GEN
Solar/Wind Harmer
1.6
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.965
316463AE2-346 GEN
Solar/Wind Harmer
0.182
316140AB2-099
Solar/Wind Harmer
0.076
962331AG1-082 GEN
Solar/Wind Harmer
2.263
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.21
313506AB2-031 GEN
Solar/Wind Harmer
0.648
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145963POPLR C
Solar/Wind Harmer
0.207
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.207
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.82
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.857
3145933PARMELE
Solar/Wind Harmer
0.199
966801AG1-551 GEN
Solar/Wind Harmer
2.319
970909AG2-566 GEN
Solar/Wind Harmer
2.12
971781AH1-399 GEN
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315724AD1-057 GEN
Solar/Wind Harmer
0.731
316327AA2-057 GEN
Solar/Wind Harmer
0.292
316131AB2-060 GEN
Solar/Wind Harmer
0.605
964241AG1-285 GEN
Solar/Wind Harmer
12.823
315785AD2-033 C
Solar/Wind Harmer
1.561
970257AG2-171 GEN
Solar/Wind Harmer
6.143
959311AF2-222 GEN
Solar/Wind Harmer
17.057
963181AG1-167 GEN
Solar/Wind Harmer
0.766
3144293JTRSVLE
Adder
0.609
3147133PAMPLIN
Solar/Wind Harmer
0.6
971193AH1-056 GEN
Solar/Wind Harmer
11.648
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.953
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.189
3146083TARBORO
Solar/Wind Harmer
0.189
3138543CONSLDL
Solar/Wind Harmer
0.125
3132273ORANGE
Solar/Wind Harmer
0.038
961601AG1-000A GEN
Solar/Wind Harmer
13.257
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.186
971623AH1-311 GEN
Solar/Wind Harmer
0.373
3141906WESTMOR
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.481
970737AG2-469 GEN
Solar/Wind Harmer
7.427
316170AC1-121 GEN2
Solar/Wind Harmer
0.183
3151761LOISA E
Adder
22.218
972183AH1-676 GEN
Adder
173.787
970221AG2-151 GEN
Solar/Wind Harmer
8.67
971683AH1-343 GEN
Solar/Wind Harmer
5.958
316283AC2-100 C
Solar/Wind Harmer
0.309
972255AH1-712 GEN
Adder
76.037
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.164
LAGNLTFEXP_LAGN->PJM
CLTF
8.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
4.157
CPLELTFEXP_CPLE->PJM
CLTF
12.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.739
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.068
MECLTFEXP_MEC->PJM
CLTF
3.555
SIGELTFEXP_SIGE->PJM
CLTF
0.108
NYPJM->LTFIMP_NY
CLTF
3.433
LGEELTFEXP_LGEE->PJM
CLTF
1.291
WECLTFEXP_WEC->PJM
CLTF
0.616

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.37 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:7067.14
MW Contribution:39.46
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
8.748
970533AG2-339 GEN
50/50
24.369
970531AG2-338 GEN
50/50
9.748
315242AE2-183_GT2
50/50
4.407
315241AE2-183_GT1
50/50
4.38
972185AH1-677 GEN
50/50
15.889
3151041BRUNSWICKG3
50/50
3.471
972187AH1-678 GEN
50/50
7.965
3151731LOISA B
50/50
17.992
3151721LOISA A
50/50
17.899
3152261N ANNA2
50/50
30.741
3151771S ANNAG1
50/50
0.958
3151801S ANNAS2
50/50
0.492
3151031BRUNSWICKG2
50/50
3.471
3151761LOISA E
50/50
36.68
972183AH1-676 GEN
50/50
287.058
316044AC1-158 PL1
Solar/Wind Harmer
8.509
316450AC1-158 RIC
Solar/Wind Harmer
2.269
3147666LOUISA
Solar/Wind Harmer
-0.109
316313AB2-026
Solar/Wind Harmer
0.78
316258AE1-075 C
Solar/Wind Harmer
0.702
316405AF2-144 C
Solar/Wind Harmer
0.741
3143336POWHATN
Solar/Wind Harmer
2.916
970917AG2-570 GEN
Solar/Wind Harmer
71.277
315773AC2-141 GEN
Solar/Wind Harmer
11.72
944581AF1-123 GEN
Solar/Wind Harmer
126.633
944601AF1-125 GEN
Solar/Wind Harmer
124.656
3151101ELIZAR3
Adder
22.862
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.351
3144536CHRHLND
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
17.079
970659AG2-427 GEN
Solar/Wind Harmer
2.572
316083AB2-161 GEN
Solar/Wind Harmer
4.433
970661AG2-428 GEN
Solar/Wind Harmer
5.142
316320Y1-086
Solar/Wind Harmer
1.598
3132273ORANGE
Solar/Wind Harmer
-0.005
3150861SPRUNCD
Adder
1.117
316435W1029_GEN3
Solar/Wind Harmer
4.902
315839AE2-212 C
Solar/Wind Harmer
0.814
3146516WINFALL
Solar/Wind Harmer
-0.027
3145336SMITFLD
Solar/Wind Harmer
-0.011
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3145273HOLLAND
Solar/Wind Harmer
-0.02
965281AG1-393 GEN
Solar/Wind Harmer
3.333
3151221GRAVEL6
Adder
17.215
3151171GRAVELC
Adder
3.312
3146376EDENTON
Solar/Wind Harmer
-0.026
961611AG1-000B GEN
Solar/Wind Harmer
5.572
316365GEN2_N
Solar/Wind Harmer
1.771
315778AD1-151 GEN
Solar/Wind Harmer
22.655
316478AD1-087 GEN
Solar/Wind Harmer
2.264
316486AD2-202 GEN
Solar/Wind Harmer
0.663
315614AA2-178 GEN
Solar/Wind Harmer
2.81
970129AG2-093 GEN
Solar/Wind Harmer
14.642
3156081AA2-088 GEN
Solar/Wind Harmer
8.385
970133AG2-095 GEN
Solar/Wind Harmer
2.902
3144216WINCHST
Adder
0.865
966621AG1-532 GEN
Solar/Wind Harmer
0.522
971157AH1-035 GEN
Solar/Wind Harmer
3.215
315737AD1-076 GEN
Solar/Wind Harmer
4.877
3150921YORKTN3
Adder
5.73
3145893MURPHYS
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
20.091
961681AG1-008 GEN
Solar/Wind Harmer
20.091
3146206CASHIE
Solar/Wind Harmer
-0.025
313506AB2-031 GEN
Solar/Wind Harmer
2.041
3146173TUNIS
Solar/Wind Harmer
-0.025
970909AG2-566 GEN
Solar/Wind Harmer
2.403
316463AE2-346 GEN
Solar/Wind Harmer
0.409
316140AB2-099
Solar/Wind Harmer
0.17
962331AG1-082 GEN
Solar/Wind Harmer
3.158
3156021HOLLOMANSOL
Solar/Wind Harmer
3.402
3147043LAWRENC
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3143096IRON208
Adder
0.935
3143096IRON208
Adder
0.916
316382AG1-145 C
Solar/Wind Harmer
0.748
316317KELFORD C
Solar/Wind Harmer
1.169
3145823KELFORD
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.025
3142946ENON
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.014
942461AE2-259 GEN
Solar/Wind Harmer
3.644
3147133PAMPLIN
Solar/Wind Harmer
-0.076
971193AH1-056 GEN
Solar/Wind Harmer
15.132
963181AG1-167 GEN
Solar/Wind Harmer
2.268
3144293JTRSVLE
Adder
0.686
3142433PROV 92
Adder
0.401
3142433PROV 92
Adder
0.401
3141843SHACKLE
Adder
1.013
3150351NORNECKC2
Adder
1.583
972255AH1-712 GEN
Adder
61.879
3141196NOKESVL
Solar/Wind Helper
1.074
959311AF2-222 GEN
Solar/Wind Harmer
12.268
3152251N ANNA1
50/50
30.744
970119AG2-088 GEN
50/50
39.456
3151791S ANNAG2
50/50
0.958
3151781S ANNAS1
50/50
0.492
315243AE2-183_GT3
50/50
4.407
3151051BRUNSWICKS1
50/50
7.204
3151021BRUNSWICKG1
50/50
3.471
971451AH1-221 GEN
50/50
10.542
3151741LOISA C
50/50
0.984
3151751LOISA D
50/50
17.992
316045AC1-158 PL2
Solar/Wind Harmer
27.219
3147666LOUISA
Solar/Wind Harmer
-0.19
316192AB2-158 GEN
Solar/Wind Harmer
5.545
3143226MDLTHAN
Solar/Wind Harmer
-0.033
940641AE2-051 GEN
Solar/Wind Harmer
29.235
3143526WINTERP
Solar/Wind Harmer
-0.157
939411AE1-173 GEN
Solar/Wind Harmer
151.543
3143336POWHATN
Solar/Wind Harmer
3.431
970919AG2-571 GEN
Solar/Wind Harmer
9.022
970087AG2-069 GEN
Solar/Wind Harmer
26.614
316294AC1-161 GEN
Solar/Wind Harmer
9.062
944591AF1-124 GEN
Solar/Wind Harmer
127.089
316336AC2-165 C
Solar/Wind Harmer
4.826
316375AC2-012 GEN
Solar/Wind Harmer
9.564
3150981CHESPKA
Adder
3.071
316388AE2-253 GEN
Solar/Wind Harmer
1.858
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316246AF1-032 C
Solar/Wind Harmer
0.555
970659AG2-427 GEN
Solar/Wind Harmer
14.512
316381AD1-082 GEN
Solar/Wind Harmer
2.505
970661AG2-428 GEN
Solar/Wind Harmer
29.016
316093AE2-104_GEN
Solar/Wind Harmer
7.933
3150851SPRUNCC
Adder
1.117
957481AF2-042 GEN
Solar/Wind Harmer
85.059
316072AD1-144
Solar/Wind Harmer
0.549
3145336SMITFLD
Solar/Wind Harmer
-0.107
3146516WINFALL
Solar/Wind Harmer
-0.087
3146516WINFALL
Solar/Wind Harmer
-0.027
315800Z1-036_GEN1
Solar/Wind Harmer
6.597
315693AD1-088 GEN
Solar/Wind Harmer
13.348
962491AG1-098 GEN
Solar/Wind Harmer
17.806
3151171GRAVELC
Adder
2.519
3130156CHOWAN
Solar/Wind Harmer
-0.026
315671AE2-027_GEN
Solar/Wind Harmer
19.85
961611AG1-000B GEN
Solar/Wind Harmer
13.059
971647AH1-324 GEN
Solar/Wind Harmer
13.175
316023GEN1_S
Solar/Wind Harmer
1.771
971069AG2-661 GEN
Solar/Wind Harmer
4.138
3145663CRESWEL
Solar/Wind Harmer
-0.073
971163AH1-040 GEN
Solar/Wind Harmer
24.415
316458AB2-190 GEN2
Solar/Wind Harmer
2.633
970129AG2-093 GEN
Solar/Wind Harmer
5.931
960081AF2-299 GEN
Solar/Wind Harmer
2.896
3138126ROCKLANDING
Solar/Wind Harmer
0.079
3142543TWELFTH
Solar/Wind Harmer
-0.002
3145893MURPHYS
Solar/Wind Harmer
-0.102
3145893MURPHYS
Solar/Wind Harmer
0.759
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.373
971795AH1-408 GEN
Solar/Wind Harmer
19.052
3146173TUNIS
Solar/Wind Harmer
-0.025
3147043LAWRENC
Adder
2.033
3145683EARLEYS
Solar/Wind Harmer
-0.025
316011AB1-132 GEN
Solar/Wind Harmer
5.258
962571AG1-106 GEN
Solar/Wind Harmer
3.612
3146263WOODLND
Solar/Wind Harmer
-0.025
3143096IRON208
Adder
0.935
316190AA2-174 GEN
Solar/Wind Harmer
0.307
971317AH1-138 GEN
Solar/Wind Harmer
3.127
970937AG2-583 GEN
Solar/Wind Harmer
17.864
3145783HORNRTN
Solar/Wind Harmer
-0.025
316159AE1-175 C
Solar/Wind Harmer
0.666
3145823KELFORD
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.025
944631AF1-128 GEN
Adder
104.9
3145963POPLR C
Solar/Wind Harmer
-0.025
315687AD1-152 GEN
Solar/Wind Harmer
2.961
316174AB2-169 GEN
Solar/Wind Harmer
3.783
316129AC1-054 GEN
Solar/Wind Harmer
2.143
971065AG2-659 GEN
Solar/Wind Harmer
12.198
3146926FARMVIL
Solar/Wind Harmer
-0.014
963171AG1-166 GEN
Solar/Wind Harmer
3.025
971563AH1-280 GEN
Solar/Wind Harmer
3.025
3144293JTRSVLE
Adder
0.686
970685AG2-442 GEN
Solar/Wind Harmer
21.155
3142433PROV 92
Adder
0.401
3142433PROV 92
Adder
0.401
3141843SHACKLE
Adder
1.013
3150351NORNECKC2
Adder
1.557
972277AH1-723 GEN
Adder
72.107
316303AF2-085
50/50
5.261
315244AE2-183_ST
50/50
7.62
963041AG1-153 GEN
50/50
7.028
315779AE2-040
50/50
3.522
316164AC1-076 GEN
Solar/Wind Harmer
2.938
941031AE2-094 GEN
Solar/Wind Harmer
57.754
944011AF1-069 GEN
Solar/Wind Harmer
18.096
316233AE1-074 FULL
Solar/Wind Harmer
0.818
971281AH1-106 GEN
Solar/Wind Harmer
4.94
971283AH1-107 GEN
Solar/Wind Harmer
4.94
970673AG2-436 GEN
Solar/Wind Harmer
63.56
970673AG2-436 GEN
Solar/Wind Harmer
32.182
316447AC1-158 HLD
Solar/Wind Harmer
18.712
971223AH1-071 GEN
Solar/Wind Harmer
4.156
3143526WINTERP
Solar/Wind Harmer
-0.157
970933AG2-581 GEN
Solar/Wind Harmer
27.317
3144356SAPONY
Solar/Wind Harmer
0.989
966001AG1-469 GEN
Solar/Wind Harmer
0.532
316185AD1-033 GEN
Solar/Wind Harmer
2.919
3142956BIRDNECK
Solar/Wind Harmer
1.484
316316AC1-027 C
Solar/Wind Harmer
0.849
316036AC1-147 C
Solar/Wind Harmer
0.746
3150991CHESPKB
Adder
2.576
3150991CHESPKB
Adder
2.515
3145506HICKORY
Solar/Wind Harmer
-0.11
3145506HICKORY
Solar/Wind Harmer
-0.066
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.858
316018AA1-139 ULT2
Solar/Wind Harmer
2.359
316017AA1-139 ULT1
Solar/Wind Harmer
2.228
3137176SLIGO L2192
Solar/Wind Harmer
-0.109
3146456SLIGO L269
Solar/Wind Harmer
3.247
3130086AYDLETT
Solar/Wind Harmer
-0.109
970657AG2-426 GEN
Solar/Wind Harmer
8.535
970657AG2-426 GEN
Solar/Wind Harmer
1.785
3146386ELIZ CT
Solar/Wind Harmer
-0.027
970099AG2-077 GEN
Solar/Wind Harmer
34.024
316431W1029_GEN1
Solar/Wind Harmer
4.902
316433W1029_GEN2
Solar/Wind Harmer
4.902
316236AE1-162_GEN
Solar/Wind Harmer
0.814
3146516WINFALL
Solar/Wind Harmer
-0.027
3146516WINFALL
Solar/Wind Harmer
-0.027
3146516WINFALL
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
315742AE1-103 GEN
Solar/Wind Harmer
2.783
3146376EDENTON
Solar/Wind Harmer
0.785
3146376EDENTON
Solar/Wind Harmer
0.785
316240AF1-291 C
Solar/Wind Harmer
0.795
316033AB2-134 GEN
Solar/Wind Harmer
8.462
315697AD1-025 GEN
Solar/Wind Harmer
5.307
944641AF1-129 GEN
Adder
111.019
971741AH1-377 GEN
Solar/Wind Harmer
29.798
3145893MURPHYS
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
-0.046
316065AD1-022 GEN
Solar/Wind Harmer
12.776
316181AB2-040 GEN
Solar/Wind Harmer
3.542
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
12.658
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
316426AA2-053 GEN
Solar/Wind Harmer
2.529
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
966811AG1-552 GEN
Solar/Wind Harmer
2.813
3145593CAROLNA
Solar/Wind Harmer
0.208
3145783HORNRTN
Solar/Wind Harmer
2.949
3145783HORNRTN
Solar/Wind Harmer
2.359
3145783HORNRTN
Solar/Wind Harmer
0.737
3145783HORNRTN
Solar/Wind Harmer
0.295
3145796HORNRTN
Solar/Wind Harmer
-0.074
3142946ENON
Solar/Wind Harmer
-0.002
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
958211AF2-115 GEN
Solar/Wind Harmer
3.781
963191AG1-168 GEN
Solar/Wind Harmer
2.268
3144293JTRSVLE
Adder
0.686
3144293JTRSVLE
Adder
0.577
3142366NRTHEST
Adder
0.692
3150691DARBY 3
Adder
15.167
3150701DARBY 4
Adder
15.132
3150681DARBY 2
Adder
15.114
3150671DARBY 1
Adder
15.096
3142296MT RD221
Adder
0.621
3150341NORNECKC1
Adder
1.636
3150341NORNECKC1
Adder
1.623
226929AD2-058 GEN
Solar/Wind Helper
0.087
971967AH1-528 GEN
Solar/Wind Harmer
56.158
970085AG2-068 GEN
Solar/Wind Harmer
17.743
970581AG2-369 GEN
Solar/Wind Harmer
15.259
316315AB2-025 C
Solar/Wind Harmer
0.765
315814AE2-033 C
Solar/Wind Harmer
26.3
3143316POE
Solar/Wind Harmer
-0.11
3151081ELIZAR1
Adder
22.573
3151091ELIZAR2
Adder
22.181
3152611GOSPORTB
Adder
3.132
3152621GOSPORTC
Adder
2.658
3152601GOSPORTA
Adder
2.452
957871AF2-081 GEN
Solar/Wind Harmer
13.769
319010AE1-072 C
Solar/Wind Harmer
5.558
3147346CASHSCORNER
Solar/Wind Harmer
0.425
3146406KITTY HAWK
Solar/Wind Harmer
0.023
316305AF2-043 C
Solar/Wind Harmer
0.826
315833AF1-017_GEN
Solar/Wind Harmer
5.184
316349AD2-085 GEN
Solar/Wind Harmer
2.427
316311AC2-079 GEN
Solar/Wind Harmer
13.767
315835AF2-110_GEN
Solar/Wind Harmer
3.41
313526AB2-022
Solar/Wind Harmer
0.736
971285AH1-108 GEN
Adder
1.828
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146486SUNBURY
Solar/Wind Harmer
-0.027
316321Z2-027
Solar/Wind Harmer
0.733
3146396TANGLEW
Solar/Wind Harmer
0.5
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971445AH1-216 GEN
Solar/Wind Harmer
16.689
315611Z1-036_GEN2
Solar/Wind Harmer
6.597
972265AH1-717 GEN
Adder
18.385
3151201GRAVEL4
Adder
17.235
3151191GRAVEL3
Adder
17.017
3151211GRAVEL5
Adder
17.017
3130156CHOWAN
Solar/Wind Harmer
-0.026
3130156CHOWAN
Solar/Wind Harmer
-0.026
316369SG1_INVT
Solar/Wind Harmer
4.688
315816AE2-034 GEN
Solar/Wind Harmer
2.107
316132AB2-190 GEN1
Solar/Wind Harmer
2.633
965291AG1-394 GEN
Solar/Wind Harmer
2.286
946281AF1-292 GEN
Solar/Wind Harmer
0.577
3130546PLYMOUTH
Solar/Wind Harmer
-0.026
315732AD1-074 GEN1
Solar/Wind Harmer
5.189
315733AD1-074 GEN2
Solar/Wind Harmer
5.189
315735AD1-075 GEN1
Solar/Wind Harmer
2.595
316318V4-068
Solar/Wind Harmer
0.637
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
-0.025
316087AB2-174 GEN
Solar/Wind Harmer
3.638
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
11.153
3146043SEABORD
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.556
3145513AHOSKIE
Solar/Wind Harmer
0.22
961941AG1-037 GEN
Solar/Wind Harmer
0.19
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3137643SOCKMAN
Solar/Wind Harmer
-0.1
3145683EARLEYS
Solar/Wind Harmer
-0.05
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.271
3145796HORNRTN
Solar/Wind Harmer
-0.079
3145796HORNRTN
Solar/Wind Harmer
-0.01
970831AG2-522 GEN
Solar/Wind Harmer
12.25
3146033SCOT NK
Solar/Wind Harmer
-0.097
315657AE1-056 GEN
Solar/Wind Harmer
9.079
946301AF1-294 GEN
Solar/Wind Harmer
6.2
961791AG1-021 GEN
Solar/Wind Harmer
3.025
970683AG2-441 GEN
Solar/Wind Harmer
18.888
970681AG2-440 GEN
Solar/Wind Harmer
15.111
3142433PROV 92
Adder
0.401
3142433PROV 92
Adder
0.401
972205AH1-687 GEN
Adder
8.511
972189AH1-679 GEN
Adder
2.2
972193AH1-681 GEN
Adder
2.765
316411AF1-147_GEN1
Solar/Wind Helper
0.849
316415AF1-147_GEN2
Solar/Wind Helper
0.849
3138216PACIFIC
Solar/Wind Helper
0.042
LAGNLTFEXP_LAGN->PJM
CLTF
9.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.279
TVALTFEXP_TVA->PJM
CLTF
4.707
CPLELTFEXP_CPLE->PJM
CLTF
13.402
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.993
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.945
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.004
MECLTFEXP_MEC->PJM
CLTF
4.2
SIGELTFEXP_SIGE->PJM
CLTF
0.127
NYPJM->LTFIMP_NY
CLTF
3.877
LGEELTFEXP_LGEE->PJM
CLTF
1.536
WECLTFEXP_WEC->PJM
CLTF
0.747

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.06 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5637.7
MW Contribution:34.81
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
5.548
944641AF1-129 GEN
50/50
120.841
970533AG2-339 GEN
50/50
21.15
970531AG2-338 GEN
50/50
8.46
3142366NRTHEST
50/50
0.824
3150781HOPHCF2
50/50
0.962
3150791HOPHCF3
50/50
0.962
3150761HOPPOLC
50/50
0.61
971213AH1-066 GEN
50/50
0.844
3150691DARBY 3
50/50
18.094
3150701DARBY 4
50/50
18.052
316447AC1-158 HLD
Solar/Wind Harmer
6.644
971223AH1-071 GEN
Solar/Wind Harmer
2.784
3143526WINTERP
Solar/Wind Harmer
1.319
316240AF1-291 C
Solar/Wind Harmer
0.002
3150681DARBY 2
Adder
16.992
3150671DARBY 1
Adder
16.973
3142296MT RD221
Adder
0.753
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.266
316036AC1-147 C
Solar/Wind Harmer
0.044
3150991CHESPKB
Adder
2.474
3150991CHESPKB
Adder
2.414
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.226
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.254
970657AG2-426 GEN
Solar/Wind Harmer
1.73
3145506HICKORY
Solar/Wind Harmer
0.94
3145506HICKORY
Solar/Wind Harmer
0.564
3145506HICKORY
Solar/Wind Harmer
0.141
3142946ENON
Solar/Wind Harmer
0.023
316339AD2-160 GEN
Solar/Wind Harmer
0.38
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.131
3137176SLIGO L2192
Solar/Wind Harmer
0.93
316075AC2-137 C
Solar/Wind Harmer
0.064
3146456SLIGO L269
Solar/Wind Harmer
4.136
3130086AYDLETT
Solar/Wind Harmer
0.933
972185AH1-677 GEN
Adder
13.007
3144356SAPONY
Solar/Wind Harmer
1.937
3146386ELIZ CT
Solar/Wind Harmer
0.231
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.523
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
966871AG1-558 GEN
Solar/Wind Harmer
0.263
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
970933AG2-581 GEN
Solar/Wind Harmer
18.033
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.99
3146376EDENTON
Solar/Wind Harmer
0.99
957411AF2-035 GEN
Solar/Wind Harmer
9.498
970317AG2-208 GEN
Solar/Wind Harmer
8.8
315673AE1-157 GEN
Solar/Wind Harmer
15.213
3150391LDYSMT3
Adder
28.839
972195AH1-682 GEN
Adder
3.79
316065AD1-022 GEN
Solar/Wind Harmer
9.8
3145893MURPHYS
Solar/Wind Harmer
1.417
3145893MURPHYS
Solar/Wind Harmer
0.381
970099AG2-077 GEN
Solar/Wind Harmer
22.503
3146173TUNIS
Solar/Wind Harmer
0.21
3146173TUNIS
Solar/Wind Harmer
0.21
958261AF2-120 GEN
Solar/Wind Harmer
6.863
316181AB2-040 GEN
Solar/Wind Harmer
0.299
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.123
316426AA2-053 GEN
Solar/Wind Harmer
0.69
3145593CAROLNA
Solar/Wind Harmer
0.203
3145593CAROLNA
Solar/Wind Harmer
0.203
966811AG1-552 GEN
Solar/Wind Harmer
2.207
3145593CAROLNA
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
3.596
3145783HORNRTN
Solar/Wind Harmer
2.876
3145783HORNRTN
Solar/Wind Harmer
0.899
3145783HORNRTN
Solar/Wind Harmer
0.36
3145796HORNRTN
Solar/Wind Harmer
0.606
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.11
3150341NORNECKC1
Adder
2.093
971741AH1-377 GEN
Solar/Wind Harmer
19.637
3145933PARMELE
Solar/Wind Harmer
0.392
3145933PARMELE
Solar/Wind Harmer
0.196
316274AC1-208 GEN
Solar/Wind Harmer
1.016
970301AG2-198 GEN
Solar/Wind Harmer
8.333
316468AD1-105 GEN
Solar/Wind Harmer
-0.063
939181AE1-148 GEN
Solar/Wind Harmer
9.137
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.051
971775AH1-396 GEN
Solar/Wind Harmer
0.302
958211AF2-115 GEN
Solar/Wind Harmer
2.257
963191AG1-168 GEN
Solar/Wind Harmer
0.752
3144293JTRSVLE
Adder
0.599
3144293JTRSVLE
Adder
0.504
3147133PAMPLIN
Solar/Wind Harmer
0.188
3147133PAMPLIN
Solar/Wind Harmer
0.15
3145493TOT1
Solar/Wind Harmer
0.432
3145453TOT5
Solar/Wind Harmer
0.259
3145603CNETO
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
3.262
316263AC1-034 GEN
Solar/Wind Harmer
6.97
962561AG1-105 GEN
Solar/Wind Harmer
8.691
964791AG1-342 GEN
Solar/Wind Harmer
3.448
3146843MT LREL
Solar/Wind Harmer
0.179
3146843MT LREL
Solar/Wind Harmer
0.179
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
3151731LOISA B
Adder
10.327
3151721LOISA A
Adder
10.274
971489AH1-241 GEN
Solar/Wind Harmer
8.48
316222AC1-221 GEN
Solar/Wind Harmer
0.648
966001AG1-469 GEN
Solar/Wind Harmer
0.09
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.158
3152251N ANNA1
50/50
19.719
970119AG2-088 GEN
50/50
34.806
3150851SPRUNCC
50/50
1.197
3143096IRON208
50/50
1.062
3152331SURRY 2
50/50
9.829
3150771HOPHCF1
50/50
0.962
316045AC1-158 PL2
Solar/Wind Harmer
9.665
3147666LOUISA
Solar/Wind Harmer
1.067
3143226MDLTHAN
Solar/Wind Harmer
0.261
316192AB2-158 GEN
Solar/Wind Harmer
1.475
3143526WINTERP
Solar/Wind Harmer
1.319
940641AE2-051 GEN
Solar/Wind Harmer
19.587
939411AE1-173 GEN
Solar/Wind Harmer
103.486
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.14
315671AE2-027_GEN
Solar/Wind Harmer
15.248
970129AG2-093 GEN
Solar/Wind Harmer
6.738
316458AB2-190 GEN2
Solar/Wind Harmer
1.271
944591AF1-124 GEN
Solar/Wind Harmer
53.482
971069AG2-661 GEN
Solar/Wind Harmer
4.206
944631AF1-128 GEN
Adder
112.66
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.949
971647AH1-324 GEN
Solar/Wind Harmer
10.078
970659AG2-427 GEN
Solar/Wind Harmer
11.419
3145336SMITFLD
Solar/Wind Harmer
0.943
961611AG1-000B GEN
Solar/Wind Harmer
12.376
316381AD1-082 GEN
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
2.508
970661AG2-428 GEN
Solar/Wind Harmer
23.401
3142416OLDCHRC
Solar/Wind Harmer
0.61
3142416OLDCHRC
Solar/Wind Harmer
0.234
316388AE2-253 GEN
Solar/Wind Harmer
0.734
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3146456SLIGO L269
Solar/Wind Harmer
0.234
316072AD1-144
Solar/Wind Harmer
0.085
316159AE1-175 C
Solar/Wind Harmer
0.201
316246AF1-032 C
Solar/Wind Harmer
0.105
971317AH1-138 GEN
Solar/Wind Harmer
1.735
316093AE2-104_GEN
Solar/Wind Harmer
3.906
3142433PROV 92
Solar/Wind Harmer
0.914
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3146516WINFALL
Solar/Wind Harmer
0.741
3146516WINFALL
Solar/Wind Harmer
0.229
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.993
971777AH1-397 GEN
Solar/Wind Harmer
0.591
3141843SHACKLE
Adder
1.143
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.223
966881AG1-559 GEN
Solar/Wind Harmer
0.257
970919AG2-571 GEN
Solar/Wind Harmer
7.85
970087AG2-069 GEN
Solar/Wind Harmer
17.59
3138133OCRAN
Solar/Wind Harmer
0.131
3145663CRESWEL
Solar/Wind Harmer
0.611
971163AH1-040 GEN
Solar/Wind Harmer
17.461
972197AH1-683 GEN
Adder
4.512
972219AH1-694 GEN
Adder
3.248
316336AC2-165 C
Solar/Wind Harmer
0.008
316023GEN1_S
Solar/Wind Harmer
0.481
3146206CASHIE
Solar/Wind Harmer
0.212
971547AH1-271 GEN
Solar/Wind Harmer
4.525
3145893MURPHYS
Solar/Wind Harmer
0.847
3145893MURPHYS
Solar/Wind Harmer
0.941
957481AF2-042 GEN
Solar/Wind Harmer
56.258
3146173TUNIS
Solar/Wind Harmer
0.21
960081AF2-299 GEN
Solar/Wind Harmer
2.005
962861AG1-135 GEN
Solar/Wind Harmer
6.67
3145683EARLEYS
Solar/Wind Harmer
0.208
315693AD1-088 GEN
Solar/Wind Harmer
9.93
3146263WOODLND
Solar/Wind Harmer
0.207
962491AG1-098 GEN
Solar/Wind Harmer
11.772
316011AB1-132 GEN
Solar/Wind Harmer
3.728
962571AG1-106 GEN
Solar/Wind Harmer
2.917
971795AH1-408 GEN
Solar/Wind Harmer
13.656
3145963POPLR C
Solar/Wind Harmer
0.204
3141726DUNNSVL
Solar/Wind Harmer
0.817
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.204
3147043LAWRENC
Adder
1.836
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3145783HORNRTN
Solar/Wind Harmer
0.202
3145796HORNRTN
Solar/Wind Harmer
0.666
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.009
316212AC1-099_GEN
Solar/Wind Harmer
1.019
3146293MARTNCO
Solar/Wind Harmer
0.182
316129AC1-054 GEN
Solar/Wind Harmer
0.734
971065AG2-659 GEN
Solar/Wind Harmer
8.291
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315722AD1-056 GEN
Solar/Wind Harmer
1.214
316337AD2-073 GEN
Solar/Wind Harmer
0.167
315687AD1-152 GEN
Solar/Wind Harmer
0.006
970937AG2-583 GEN
Solar/Wind Harmer
11.689
316494AC1-189 GEN
Solar/Wind Harmer
0.639
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
14.068
963171AG1-166 GEN
Solar/Wind Harmer
1.003
971563AH1-280 GEN
Solar/Wind Harmer
2.007
3144293JTRSVLE
Adder
0.599
3146233WITAKRS
Solar/Wind Harmer
0.743
3146926FARMVIL
Solar/Wind Harmer
0.112
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.186
3145493TOT1
Solar/Wind Harmer
0.829
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.147
316359AB2-059 GEN
Solar/Wind Harmer
0.659
316049AB1-081 GEN
Solar/Wind Harmer
1.05
3142053HEARTS
Solar/Wind Harmer
0.323
970401AG2-262 GEN
Solar/Wind Harmer
1.053
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.289
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.408
3151751LOISA D
Adder
10.327
971377AH1-170 GEN
Solar/Wind Harmer
1.696
3147623JAMES R
Solar/Wind Harmer
0.368
972277AH1-723 GEN
Adder
86.868
316254AC1-120 GEN1
Solar/Wind Harmer
0.26
316303AF2-085
50/50
4.641
971285AH1-108 GEN
50/50
1.959
970603AG2-384 GEN
50/50
5.097
316233AE1-074 FULL
Solar/Wind Harmer
0.203
971281AH1-106 GEN
Solar/Wind Harmer
3.521
971283AH1-107 GEN
Solar/Wind Harmer
3.521
3143316POE
Solar/Wind Harmer
0.947
941031AE2-094 GEN
Solar/Wind Harmer
43.824
944011AF1-069 GEN
Solar/Wind Harmer
14.319
316132AB2-190 GEN1
Solar/Wind Harmer
1.271
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
21.661
3151091ELIZAR2
Adder
21.285
3152611GOSPORTB
Adder
3.008
3152621GOSPORTC
Adder
2.552
3152601GOSPORTA
Adder
2.355
971445AH1-216 GEN
Solar/Wind Harmer
16.611
972265AH1-717 GEN
Adder
18.304
3151201GRAVEL4
Adder
17.158
3151191GRAVEL3
Adder
16.941
3151211GRAVEL5
Adder
16.941
316312AB1-027
Solar/Wind Harmer
0.42
957871AF2-081 GEN
Solar/Wind Harmer
11.66
316164AC1-076 GEN
Solar/Wind Harmer
0.329
970673AG2-436 GEN
Solar/Wind Harmer
49.886
970673AG2-436 GEN
Solar/Wind Harmer
33.257
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.16
319010AE1-072 C
Solar/Wind Harmer
1.177
316311AC2-079 GEN
Solar/Wind Harmer
6.708
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.098
316169AC1-164_GENC
Solar/Wind Harmer
20.818
315975AC1-164 GENB
Solar/Wind Harmer
0.713
315835AF2-110_GEN
Solar/Wind Harmer
1.594
316315AB2-025 C
Solar/Wind Harmer
0.187
313526AB2-022
Solar/Wind Harmer
0.125
971967AH1-528 GEN
Solar/Wind Harmer
36.95
3146486SUNBURY
Solar/Wind Harmer
0.231
3146486SUNBURY
Solar/Wind Harmer
0.231
972189AH1-679 GEN
Adder
3.867
315814AE2-033 C
Solar/Wind Harmer
18.254
316321Z2-027
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
971167AH1-042 GEN
Solar/Wind Harmer
20.377
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143873LANEXA
Solar/Wind Harmer
0.135
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.628
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.223
3130156CHOWAN
Solar/Wind Harmer
0.223
3141873WAN 176
Solar/Wind Harmer
0.044
970085AG2-068 GEN
Solar/Wind Harmer
11.727
970581AG2-369 GEN
Solar/Wind Harmer
10.085
3141913WHIT STONE
Solar/Wind Harmer
0.219
3138133OCRAN
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.937
3141783LANCAST
Solar/Wind Harmer
0.13
3141783LANCAST
Solar/Wind Harmer
0.087
3150411LDYSMT5
Adder
28.983
3150381LDYSMT2
Adder
27.738
972213AH1-691 GEN
Adder
4.692
972215AH1-692 GEN
Adder
4.692
3130546PLYMOUTH
Solar/Wind Harmer
0.215
315732AD1-074 GEN1
Solar/Wind Harmer
1.23
315733AD1-074 GEN2
Solar/Wind Harmer
1.23
315735AD1-075 GEN1
Solar/Wind Harmer
0.616
965291AG1-394 GEN
Solar/Wind Harmer
0.949
962981AG1-147 GEN
Solar/Wind Harmer
7.952
3146206CASHIE
Solar/Wind Harmer
0.212
970601AG2-382 GEN
Solar/Wind Harmer
7.919
3145893MURPHYS
Solar/Wind Harmer
0.572
3145893MURPHYS
Solar/Wind Harmer
0.212
970327AG2-215 GEN
Solar/Wind Harmer
6.922
3145513AHOSKIE
Solar/Wind Harmer
0.437
3145513AHOSKIE
Solar/Wind Harmer
0.209
3146043SEABORD
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.416
3145683EARLEYS
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.208
315607AA1-063A GEN
Solar/Wind Harmer
0.424
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.553
3137643SOCKMAN
Solar/Wind Harmer
0.818
3145796HORNRTN
Solar/Wind Harmer
0.646
3145796HORNRTN
Solar/Wind Harmer
0.081
3141813NORNECK
Solar/Wind Harmer
0.201
3146033SCOT NK
Solar/Wind Harmer
0.8
970831AG2-522 GEN
Solar/Wind Harmer
8.358
316005AA1-067
Solar/Wind Harmer
0.206
3145746EVERETS
Solar/Wind Harmer
0.764
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
970181AG2-120 GEN
Solar/Wind Harmer
2.391
957861AF2-080 GEN
Solar/Wind Harmer
8.156
316239AB2-077_GEN
Solar/Wind Harmer
0.002
3152261N ANNA2
50/50
19.717
3150861SPRUNCD
50/50
1.197
3143096IRON208
50/50
1.062
3143096IRON208
50/50
1.041
3150801HOPHCF4
50/50
1.399
971211AH1-065 GEN
50/50
1.687
3151161SURRY 1
50/50
9.055
316044AC1-158 PL1
Solar/Wind Harmer
3.023
316450AC1-158 RIC
Solar/Wind Harmer
0.806
3147666LOUISA
Solar/Wind Harmer
0.614
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.726
965281AG1-393 GEN
Solar/Wind Harmer
2.543
315813AE1-149 C
Solar/Wind Harmer
12.658
970133AG2-095 GEN
Solar/Wind Harmer
2.278
970129AG2-093 GEN
Solar/Wind Harmer
14.319
944581AF1-123 GEN
Solar/Wind Harmer
53.293
944601AF1-125 GEN
Solar/Wind Harmer
52.472
315778AD1-151 GEN
Solar/Wind Harmer
18.928
3151101ELIZAR3
Adder
21.938
3144536CHRHLND
Solar/Wind Harmer
0.035
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.498
3145336SMITFLD
Solar/Wind Harmer
0.094
961611AG1-000B GEN
Solar/Wind Harmer
6.293
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.139
3151171GRAVELC
Adder
3.297
970293AG2-193 GEN
Solar/Wind Harmer
2.512
970661AG2-428 GEN
Solar/Wind Harmer
4.977
3142946ENON
Solar/Wind Harmer
0.079
3142416OLDCHRC
Solar/Wind Harmer
2.274
3144216WINCHST
Adder
0.882
3146456SLIGO L269
Solar/Wind Harmer
0.234
971153AH1-033 GEN
Solar/Wind Harmer
2.702
3150921YORKTN3
Adder
5.872
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3146516WINFALL
Solar/Wind Harmer
0.229
316473AC1-191 GEN
Solar/Wind Harmer
0.768
3146626S HERTFORD
Solar/Wind Harmer
0.227
3145273HOLLAND
Solar/Wind Harmer
0.17
316313AB2-026
Solar/Wind Harmer
0.142
316258AE1-075 C
Solar/Wind Harmer
0.17
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.394
3141843SHACKLE
Adder
1.143
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.978
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.223
316156AD2-030 GEN
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
3.95
970917AG2-570 GEN
Solar/Wind Harmer
19.626
315614AA2-178 GEN
Solar/Wind Harmer
1.249
3150401LDYSMT4
Adder
28.893
3150371LDYSMT1
Adder
27.918
971157AH1-035 GEN
Solar/Wind Harmer
2.577
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.481
315737AD1-076 GEN
Solar/Wind Harmer
2.755
962971AG1-146 GEN
Solar/Wind Harmer
3.408
3146206CASHIE
Solar/Wind Harmer
0.212
3145893MURPHYS
Solar/Wind Harmer
0.354
3145893MURPHYS
Solar/Wind Harmer
0.212
957521AF2-046 GEN
Solar/Wind Harmer
15.715
961681AG1-008 GEN
Solar/Wind Harmer
15.715
970009AG2-005 GEN
Solar/Wind Harmer
1.575
3146173TUNIS
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.95
316463AE2-346 GEN
Solar/Wind Harmer
0.179
316140AB2-099
Solar/Wind Harmer
0.075
962331AG1-082 GEN
Solar/Wind Harmer
2.227
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.207
313506AB2-031 GEN
Solar/Wind Harmer
0.638
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3145963POPLR C
Solar/Wind Harmer
0.204
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.204
316478AD1-087 GEN
Solar/Wind Harmer
0.708
316486AD2-202 GEN
Solar/Wind Harmer
0.208
3147043LAWRENC
Solar/Wind Harmer
0.122
3145796HORNRTN
Solar/Wind Harmer
0.807
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.043
316210AC1-098 GEN
Solar/Wind Harmer
1.828
3145933PARMELE
Solar/Wind Harmer
0.196
966801AG1-551 GEN
Solar/Wind Harmer
2.283
970909AG2-566 GEN
Solar/Wind Harmer
2.083
971781AH1-399 GEN
Solar/Wind Harmer
0.256
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315724AD1-057 GEN
Solar/Wind Harmer
0.72
316327AA2-057 GEN
Solar/Wind Harmer
0.287
316131AB2-060 GEN
Solar/Wind Harmer
0.595
964241AG1-285 GEN
Solar/Wind Harmer
12.61
315785AD2-033 C
Solar/Wind Harmer
1.535
970257AG2-171 GEN
Solar/Wind Harmer
6.039
959311AF2-222 GEN
Solar/Wind Harmer
16.767
963181AG1-167 GEN
Solar/Wind Harmer
0.752
3144293JTRSVLE
Adder
0.599
3147133PAMPLIN
Solar/Wind Harmer
0.59
971193AH1-056 GEN
Solar/Wind Harmer
11.443
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.938
3146233WITAKRS
Solar/Wind Harmer
0.127
3146926FARMVIL
Solar/Wind Harmer
0.112
3146073TAR RVR
Solar/Wind Harmer
0.186
3146083TARBORO
Solar/Wind Harmer
0.186
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.049
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.183
971623AH1-311 GEN
Solar/Wind Harmer
0.367
3141906WESTMOR
Solar/Wind Harmer
0.072
3146776BUCKING
Solar/Wind Harmer
0.064
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.36
970737AG2-469 GEN
Solar/Wind Harmer
7.314
971683AH1-343 GEN
Solar/Wind Harmer
5.86
3151761LOISA E
Adder
21.054
970221AG2-151 GEN
Solar/Wind Harmer
8.48
3132273ORANGE
Solar/Wind Harmer
0.031
316283AC2-100 C
Solar/Wind Harmer
0.304
972183AH1-676 GEN
Adder
164.313
972255AH1-712 GEN
Adder
74.545
316170AC1-121 GEN2
Solar/Wind Harmer
0.13
3141316ARNOLDS
Adder
0.285
3141196NOKESVL
Solar/Wind Helper
1.139
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.171
3144303KENBRDG
Solar/Wind Harmer
0.151
970683AG2-441 GEN
Solar/Wind Harmer
12.561
970681AG2-440 GEN
Solar/Wind Harmer
10.049
946301AF1-294 GEN
Solar/Wind Harmer
3.712
961791AG1-021 GEN
Solar/Wind Harmer
1.806
315657AE1-056 GEN
Solar/Wind Harmer
6.482
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.186
3145573BETHELC
Solar/Wind Harmer
0.186
970285AG2-188 GEN
Solar/Wind Harmer
14.319
316223AC1-118
Solar/Wind Harmer
0.13
971845AH1-439 GEN
Solar/Wind Harmer
8.149
316118AC1-105 GEN
Solar/Wind Harmer
0.454
3147173SINAI
Solar/Wind Harmer
0.172
3147243WELCO
Solar/Wind Harmer
0.108
972205AH1-687 GEN
Adder
7.256
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971447AH1-217 GEN
Solar/Wind Harmer
4.692
970865AG2-541 GEN
Solar/Wind Harmer
5.299
3147346CASHSCORNER
Solar/Wind Harmer
0.35
972193AH1-681 GEN
Adder
3.331
316123AC1-075 GEN
Solar/Wind Harmer
0.191
970165AG2-112 GEN
Solar/Wind Harmer
1.134
970163AG2-111 GEN
Solar/Wind Harmer
1.081
270494AE1-108_GEN
Solar/Wind Harmer
1.679
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.804
316415AF1-147_GEN2
Solar/Wind Helper
0.804
3138216PACIFIC
Solar/Wind Helper
0.039
LAGNLTFEXP_LAGN->PJM
CLTF
8.056
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.878
TVALTFEXP_TVA->PJM
CLTF
4.082
CPLELTFEXP_CPLE->PJM
CLTF
11.88
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.966
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.76
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.813
MECLTFEXP_MEC->PJM
CLTF
3.485
SIGELTFEXP_SIGE->PJM
CLTF
0.106
NYPJM->LTFIMP_NY
CLTF
3.369
LGEELTFEXP_LGEE->PJM
CLTF
1.264
WECLTFEXP_WEC->PJM
CLTF
0.603

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.28 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6078.79
MW Contribution:35.34
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
60.398
316303AF2-085
50/50
4.712
971285AH1-108 GEN
50/50
1.991
970603AG2-384 GEN
50/50
5.178
316164AC1-076 GEN
Solar/Wind Harmer
3.019
316233AE1-074 FULL
Solar/Wind Harmer
0.779
971281AH1-106 GEN
Solar/Wind Harmer
4.708
971283AH1-107 GEN
Solar/Wind Harmer
4.708
3143316POE
Solar/Wind Harmer
-0.107
941031AE2-094 GEN
Solar/Wind Harmer
50.888
944011AF1-069 GEN
Solar/Wind Harmer
15.945
316132AB2-190 GEN1
Solar/Wind Harmer
2.735
316369SG1_INVT
Solar/Wind Harmer
4.821
3151081ELIZAR1
Adder
22.001
3151091ELIZAR2
Adder
21.619
3152611GOSPORTB
Adder
3.055
3152621GOSPORTC
Adder
2.593
3152601GOSPORTA
Adder
2.392
971445AH1-216 GEN
Solar/Wind Harmer
16.663
972265AH1-717 GEN
Adder
18.594
3151201GRAVEL4
Adder
17.43
3151191GRAVEL3
Adder
17.21
3151211GRAVEL5
Adder
17.21
316312AB1-027
Solar/Wind Harmer
0.904
957871AF2-081 GEN
Solar/Wind Harmer
13.366
970673AG2-436 GEN
Solar/Wind Harmer
56.037
970673AG2-436 GEN
Solar/Wind Harmer
28.373
315833AF1-017_GEN
Solar/Wind Harmer
5.064
316349AD2-085 GEN
Solar/Wind Harmer
2.371
319010AE1-072 C
Solar/Wind Harmer
5.393
316311AC2-079 GEN
Solar/Wind Harmer
13.447
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.803
315976AC1-164 GENA
Solar/Wind Harmer
28.04
316169AC1-164_GENC
Solar/Wind Harmer
24.224
315975AC1-164 GENB
Solar/Wind Harmer
0.83
315835AF2-110_GEN
Solar/Wind Harmer
3.313
316315AB2-025 C
Solar/Wind Harmer
0.713
313526AB2-022
Solar/Wind Harmer
0.713
972189AH1-679 GEN
Adder
3.932
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
971967AH1-528 GEN
Solar/Wind Harmer
49.529
315814AE2-033 C
Solar/Wind Harmer
24.517
316321Z2-027
Solar/Wind Harmer
0.71
3146396TANGLEW
Solar/Wind Harmer
0.484
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
971167AH1-042 GEN
Solar/Wind Harmer
25.215
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
957831AF2-077 GEN
Solar/Wind Harmer
0.783
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143873LANEXA
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.355
316314AB2-024 C
Solar/Wind Harmer
2.187
316059AD1-063 C
Solar/Wind Harmer
0.576
315662AE1-191 GEN
Solar/Wind Harmer
3.069
315666AE1-190 GEN
Solar/Wind Harmer
0.767
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
957601AF2-054 GEN
Solar/Wind Harmer
0.759
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.677
970581AG2-369 GEN
Solar/Wind Harmer
13.482
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
2.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3150411LDYSMT5
Adder
29.481
3150381LDYSMT2
Adder
28.214
972213AH1-691 GEN
Adder
4.773
972215AH1-692 GEN
Adder
4.773
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.942
315733AD1-074 GEN2
Solar/Wind Harmer
4.942
315735AD1-075 GEN1
Solar/Wind Harmer
2.472
965291AG1-394 GEN
Solar/Wind Harmer
2.164
962981AG1-147 GEN
Solar/Wind Harmer
10.637
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.591
316318V4-068
Solar/Wind Harmer
0.602
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.534
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.392
316087AB2-174 GEN
Solar/Wind Harmer
3.373
315652AC1-086 GEN
Solar/Wind Harmer
26.336
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
3141813NORNECK
Solar/Wind Harmer
-0.023
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.416
972193AH1-681 GEN
Adder
3.397
316411AF1-147_GEN1
Solar/Wind Helper
0.82
316415AF1-147_GEN2
Solar/Wind Helper
0.82
3138216PACIFIC
Solar/Wind Helper
0.04
3152261N ANNA2
50/50
19.95
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.079
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.199
316044AC1-158 PL1
Solar/Wind Harmer
6.895
316450AC1-158 RIC
Solar/Wind Harmer
1.839
3147666LOUISA
Solar/Wind Harmer
-0.07
315839AE2-212 C
Solar/Wind Harmer
0.822
315773AC2-141 GEN
Solar/Wind Harmer
11.408
965281AG1-393 GEN
Solar/Wind Harmer
3.401
970133AG2-095 GEN
Solar/Wind Harmer
3.047
315813AE1-149 C
Solar/Wind Harmer
16.929
970129AG2-093 GEN
Solar/Wind Harmer
15.225
944581AF1-123 GEN
Solar/Wind Harmer
122.873
944601AF1-125 GEN
Solar/Wind Harmer
120.955
315778AD1-151 GEN
Solar/Wind Harmer
23.395
3151101ELIZAR3
Adder
22.283
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.537
961611AG1-000B GEN
Solar/Wind Harmer
5.672
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.37
3151221GRAVEL6
Adder
17.41
3151171GRAVELC
Adder
3.35
970293AG2-193 GEN
Solar/Wind Harmer
3.361
3142946ENON
Solar/Wind Harmer
-0.009
970661AG2-428 GEN
Solar/Wind Harmer
5.055
3142416OLDCHRC
Solar/Wind Harmer
2.704
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.252
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.803
316320Y1-086
Solar/Wind Harmer
1.548
316435W1029_GEN3
Solar/Wind Harmer
4.74
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
-0.026
316473AC1-191 GEN
Solar/Wind Harmer
2.794
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.692
316258AE1-075 C
Solar/Wind Harmer
0.623
316405AF2-144 C
Solar/Wind Harmer
0.658
3143336POWHATN
Solar/Wind Harmer
2.59
3141843SHACKLE
Adder
1.161
316203AE2-005 GEN
Solar/Wind Harmer
10.766
3141766HARMONY
Solar/Wind Harmer
2.27
316280AD1-041 GEN
Solar/Wind Harmer
1.918
966881AG1-559 GEN
Solar/Wind Harmer
0.765
3146376EDENTON
Solar/Wind Harmer
-0.025
316156AD2-030 GEN
Solar/Wind Harmer
0.677
3141873WAN 176
Solar/Wind Harmer
3.01
970917AG2-570 GEN
Solar/Wind Harmer
62.97
315614AA2-178 GEN
Solar/Wind Harmer
2.688
3150401LDYSMT4
Adder
29.389
3150371LDYSMT1
Adder
28.398
971157AH1-035 GEN
Solar/Wind Harmer
3.064
3156081AA2-088 GEN
Solar/Wind Harmer
7.946
316365GEN2_N
Solar/Wind Harmer
1.648
315737AD1-076 GEN
Solar/Wind Harmer
4.644
962971AG1-146 GEN
Solar/Wind Harmer
4.559
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.984
961681AG1-008 GEN
Solar/Wind Harmer
18.984
316484AD2-074 GEN
Solar/Wind Harmer
6.061
970009AG2-005 GEN
Solar/Wind Harmer
3.009
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.218
966621AG1-532 GEN
Solar/Wind Harmer
0.484
316463AE2-346 GEN
Solar/Wind Harmer
0.386
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.979
316404AE1-155 C
Solar/Wind Harmer
4.57
3146263WOODLND
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.893
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.098
3145823KELFORD
Solar/Wind Harmer
-0.023
316478AD1-087 GEN
Solar/Wind Harmer
2.006
316486AD2-202 GEN
Solar/Wind Harmer
0.588
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.075
3144293JTRSVLE
Adder
0.609
3151761LOISA E
Adder
22.218
972183AH1-676 GEN
Adder
173.787
972255AH1-712 GEN
Adder
76.037
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.164
3152251N ANNA1
50/50
19.951
971507AH1-251 GEN
50/50
16.627
970119AG2-088 GEN
50/50
35.342
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.079
3152331SURRY 2
50/50
9.986
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
22.057
3147666LOUISA
Solar/Wind Harmer
-0.123
316192AB2-158 GEN
Solar/Wind Harmer
3.585
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.15
940641AE2-051 GEN
Solar/Wind Harmer
26.182
939411AE1-173 GEN
Solar/Wind Harmer
138.344
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.821
315671AE2-027_GEN
Solar/Wind Harmer
20.395
970129AG2-093 GEN
Solar/Wind Harmer
6.167
316458AB2-190 GEN2
Solar/Wind Harmer
2.735
944591AF1-124 GEN
Solar/Wind Harmer
123.316
971069AG2-661 GEN
Solar/Wind Harmer
4.273
944631AF1-128 GEN
Adder
114.478
316375AC2-012 GEN
Solar/Wind Harmer
9.327
3150981CHESPKA
Adder
2.995
971647AH1-324 GEN
Solar/Wind Harmer
13.48
970659AG2-427 GEN
Solar/Wind Harmer
14.317
961611AG1-000B GEN
Solar/Wind Harmer
13.293
3145336SMITFLD
Solar/Wind Harmer
-0.107
316381AD1-082 GEN
Solar/Wind Harmer
2.469
3151171GRAVELC
Adder
2.547
970661AG2-428 GEN
Solar/Wind Harmer
28.527
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.027
316388AE2-253 GEN
Solar/Wind Harmer
1.804
3138126ROCKLANDING
Solar/Wind Harmer
0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316072AD1-144
Solar/Wind Harmer
0.54
316159AE1-175 C
Solar/Wind Harmer
0.715
316246AF1-032 C
Solar/Wind Harmer
0.539
971317AH1-138 GEN
Solar/Wind Harmer
3.316
316093AE2-104_GEN
Solar/Wind Harmer
7.706
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.355
3143336POWHATN
Solar/Wind Harmer
3.047
971777AH1-397 GEN
Solar/Wind Harmer
3.003
3141843SHACKLE
Adder
1.161
3141766HARMONY
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.025
966881AG1-559 GEN
Solar/Wind Harmer
0.262
970919AG2-571 GEN
Solar/Wind Harmer
7.971
970087AG2-069 GEN
Solar/Wind Harmer
23.516
3138133OCRAN
Solar/Wind Harmer
-0.015
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.353
972197AH1-683 GEN
Adder
4.589
972219AH1-694 GEN
Adder
3.304
316336AC2-165 C
Solar/Wind Harmer
4.275
316023GEN1_S
Solar/Wind Harmer
1.648
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.052
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.717
957481AF2-042 GEN
Solar/Wind Harmer
75.252
961951AG1-038 GEN
Solar/Wind Harmer
3.171
3146173TUNIS
Solar/Wind Harmer
-0.024
960081AF2-299 GEN
Solar/Wind Harmer
2.682
962861AG1-135 GEN
Solar/Wind Harmer
8.922
3145683EARLEYS
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.811
3146263WOODLND
Solar/Wind Harmer
-0.024
962491AG1-098 GEN
Solar/Wind Harmer
15.753
316011AB1-132 GEN
Solar/Wind Harmer
4.898
962571AG1-106 GEN
Solar/Wind Harmer
3.365
971795AH1-408 GEN
Solar/Wind Harmer
17.538
3145963POPLR C
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316190AA2-174 GEN
Solar/Wind Harmer
0.286
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Adder
1.866
316174AB2-169 GEN
Solar/Wind Harmer
3.568
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.041
3144293JTRSVLE
Adder
0.609
3151751LOISA D
Adder
10.898
972277AH1-723 GEN
Adder
88.606
971133AH1-012 GEN
50/50
5.665
944641AF1-129 GEN
50/50
122.768
3142366NRTHEST
50/50
0.838
970533AG2-339 GEN
50/50
21.472
970531AG2-338 GEN
50/50
8.589
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.39
316447AC1-158 HLD
Solar/Wind Harmer
15.163
971223AH1-071 GEN
Solar/Wind Harmer
3.723
3143526WINTERP
Solar/Wind Harmer
-0.15
316240AF1-291 C
Solar/Wind Harmer
0.822
3150701DARBY 4
Adder
17.29
3150681DARBY 2
Adder
17.27
3150671DARBY 1
Adder
17.25
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
8.703
315697AD1-025 GEN
Solar/Wind Harmer
5.458
316036AC1-147 C
Solar/Wind Harmer
0.727
3150991CHESPKB
Adder
2.513
3150991CHESPKB
Adder
2.452
316236AE1-162_GEN
Solar/Wind Harmer
0.812
3142956BIRDNECK
Solar/Wind Harmer
1.444
316316AC1-027 C
Solar/Wind Harmer
0.826
316185AD1-033 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
8.405
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3142946ENON
Solar/Wind Harmer
-0.003
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.804
316018AA1-139 ULT2
Solar/Wind Harmer
2.29
316017AA1-139 ULT1
Solar/Wind Harmer
2.163
316075AC2-137 C
Solar/Wind Harmer
0.72
3137176SLIGO L2192
Solar/Wind Harmer
-0.106
3146456SLIGO L269
Solar/Wind Harmer
3.151
3130086AYDLETT
Solar/Wind Harmer
-0.106
972185AH1-677 GEN
Adder
13.205
3144356SAPONY
Solar/Wind Harmer
0.922
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.74
316433W1029_GEN2
Solar/Wind Harmer
4.74
972187AH1-678 GEN
Adder
6.623
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.781
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
970933AG2-581 GEN
Solar/Wind Harmer
24.111
315742AE1-103 GEN
Solar/Wind Harmer
2.675
316441AF1-014 GEN
Solar/Wind Harmer
1.721
957411AF2-035 GEN
Solar/Wind Harmer
11.447
970317AG2-208 GEN
Solar/Wind Harmer
11.129
3146376EDENTON
Solar/Wind Harmer
0.755
3146376EDENTON
Solar/Wind Harmer
0.755
315673AE1-157 GEN
Solar/Wind Harmer
18.853
3150391LDYSMT3
Adder
29.334
972195AH1-682 GEN
Adder
3.855
316065AD1-022 GEN
Solar/Wind Harmer
12.145
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
30.101
316487AF1-042 GEN
Solar/Wind Harmer
3.171
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.18
316181AB2-040 GEN
Solar/Wind Harmer
3.285
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.355
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.613
3145593CAROLNA
Solar/Wind Harmer
0.193
3145783HORNRTN
Solar/Wind Harmer
2.74
3145783HORNRTN
Solar/Wind Harmer
2.192
3145783HORNRTN
Solar/Wind Harmer
0.685
3145783HORNRTN
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3150341NORNECKC1
Adder
2.144
3150341NORNECKC1
Adder
2.127
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3151731LOISA B
Adder
10.898
3151721LOISA A
Adder
10.842
971741AH1-377 GEN
Solar/Wind Harmer
1.355
LAGNLTFEXP_LAGN->PJM
CLTF
8.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
4.157
CPLELTFEXP_CPLE->PJM
CLTF
12.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.739
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.068
MECLTFEXP_MEC->PJM
CLTF
3.555
SIGELTFEXP_SIGE->PJM
CLTF
0.108
NYPJM->LTFIMP_NY
CLTF
3.433
LGEELTFEXP_LGEE->PJM
CLTF
1.291
WECLTFEXP_WEC->PJM
CLTF
0.616

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H3T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.01 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6067.89
MW Contribution:35.31
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
19.936
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.42
971211AH1-065 GEN
50/50
1.713
3151161SURRY 1
50/50
9.192
316044AC1-158 PL1
Solar/Wind Harmer
6.891
316450AC1-158 RIC
Solar/Wind Harmer
1.837
3147666LOUISA
Solar/Wind Harmer
-0.07
315839AE2-212 C
Solar/Wind Harmer
0.822
315773AC2-141 GEN
Solar/Wind Harmer
11.4
965281AG1-393 GEN
Solar/Wind Harmer
3.399
970133AG2-095 GEN
Solar/Wind Harmer
3.045
315813AE1-149 C
Solar/Wind Harmer
16.916
970129AG2-093 GEN
Solar/Wind Harmer
15.214
944581AF1-123 GEN
Solar/Wind Harmer
122.781
944601AF1-125 GEN
Solar/Wind Harmer
120.864
315778AD1-151 GEN
Solar/Wind Harmer
23.378
3151101ELIZAR3
Adder
22.266
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.535
961611AG1-000B GEN
Solar/Wind Harmer
5.668
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.366
3151221GRAVEL6
Adder
17.397
3151171GRAVELC
Adder
3.347
970293AG2-193 GEN
Solar/Wind Harmer
3.359
3142946ENON
Solar/Wind Harmer
-0.009
970661AG2-428 GEN
Solar/Wind Harmer
5.052
3142416OLDCHRC
Solar/Wind Harmer
2.702
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.25
3150921YORKTN3
Adder
5.961
316382AG1-145 C
Solar/Wind Harmer
0.802
316320Y1-086
Solar/Wind Harmer
1.547
316435W1029_GEN3
Solar/Wind Harmer
4.736
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146516WINFALL
Solar/Wind Harmer
-0.026
316473AC1-191 GEN
Solar/Wind Harmer
2.792
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.692
316258AE1-075 C
Solar/Wind Harmer
0.623
316405AF2-144 C
Solar/Wind Harmer
0.657
3143336POWHATN
Solar/Wind Harmer
2.588
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
10.758
3141766HARMONY
Solar/Wind Harmer
2.268
316280AD1-041 GEN
Solar/Wind Harmer
1.917
966881AG1-559 GEN
Solar/Wind Harmer
0.764
3146376EDENTON
Solar/Wind Harmer
-0.025
316156AD2-030 GEN
Solar/Wind Harmer
0.677
3141873WAN 176
Solar/Wind Harmer
3.008
970917AG2-570 GEN
Solar/Wind Harmer
62.922
315614AA2-178 GEN
Solar/Wind Harmer
2.686
3150401LDYSMT4
Adder
29.367
3150371LDYSMT1
Adder
28.377
971157AH1-035 GEN
Solar/Wind Harmer
3.061
3156081AA2-088 GEN
Solar/Wind Harmer
7.94
316365GEN2_N
Solar/Wind Harmer
1.647
315737AD1-076 GEN
Solar/Wind Harmer
4.641
962971AG1-146 GEN
Solar/Wind Harmer
4.555
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.97
961681AG1-008 GEN
Solar/Wind Harmer
18.97
316484AD2-074 GEN
Solar/Wind Harmer
6.056
970009AG2-005 GEN
Solar/Wind Harmer
3.007
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.215
966621AG1-532 GEN
Solar/Wind Harmer
0.483
316463AE2-346 GEN
Solar/Wind Harmer
0.385
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.977
316404AE1-155 C
Solar/Wind Harmer
4.567
3146263WOODLND
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.892
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.097
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Solar/Wind Harmer
-0.014
316478AD1-087 GEN
Solar/Wind Harmer
2.005
316486AD2-202 GEN
Solar/Wind Harmer
0.587
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.074
3144293JTRSVLE
Adder
0.609
3151761LOISA E
Adder
22.198
972183AH1-676 GEN
Adder
173.63
972255AH1-712 GEN
Adder
75.968
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.139
3152251N ANNA1
50/50
19.938
971507AH1-251 GEN
50/50
16.616
970119AG2-088 GEN
50/50
35.315
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.978
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
22.043
3147666LOUISA
Solar/Wind Harmer
-0.123
316192AB2-158 GEN
Solar/Wind Harmer
3.583
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.15
940641AE2-051 GEN
Solar/Wind Harmer
26.162
939411AE1-173 GEN
Solar/Wind Harmer
138.24
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.814
315671AE2-027_GEN
Solar/Wind Harmer
20.38
970129AG2-093 GEN
Solar/Wind Harmer
6.163
316458AB2-190 GEN2
Solar/Wind Harmer
2.733
944591AF1-124 GEN
Solar/Wind Harmer
123.223
971069AG2-661 GEN
Solar/Wind Harmer
4.27
944631AF1-128 GEN
Adder
114.392
316375AC2-012 GEN
Solar/Wind Harmer
9.32
3150981CHESPKA
Adder
2.993
971647AH1-324 GEN
Solar/Wind Harmer
13.47
970659AG2-427 GEN
Solar/Wind Harmer
14.306
961611AG1-000B GEN
Solar/Wind Harmer
13.283
3145336SMITFLD
Solar/Wind Harmer
-0.107
316381AD1-082 GEN
Solar/Wind Harmer
2.467
3151171GRAVELC
Adder
2.545
970661AG2-428 GEN
Solar/Wind Harmer
28.505
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
316388AE2-253 GEN
Solar/Wind Harmer
1.803
3138126ROCKLANDING
Solar/Wind Harmer
0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316072AD1-144
Solar/Wind Harmer
0.539
316159AE1-175 C
Solar/Wind Harmer
0.714
316246AF1-032 C
Solar/Wind Harmer
0.538
971317AH1-138 GEN
Solar/Wind Harmer
3.313
316093AE2-104_GEN
Solar/Wind Harmer
7.7
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.351
3143336POWHATN
Solar/Wind Harmer
3.045
971777AH1-397 GEN
Solar/Wind Harmer
3
3141843SHACKLE
Adder
1.16
3141766HARMONY
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.025
966881AG1-559 GEN
Solar/Wind Harmer
0.261
970919AG2-571 GEN
Solar/Wind Harmer
7.965
970087AG2-069 GEN
Solar/Wind Harmer
23.498
3138133OCRAN
Solar/Wind Harmer
-0.015
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.335
972197AH1-683 GEN
Adder
4.586
972219AH1-694 GEN
Adder
3.302
316336AC2-165 C
Solar/Wind Harmer
4.272
316023GEN1_S
Solar/Wind Harmer
1.647
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.047
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.717
957481AF2-042 GEN
Solar/Wind Harmer
75.195
961951AG1-038 GEN
Solar/Wind Harmer
3.169
3146173TUNIS
Solar/Wind Harmer
-0.024
960081AF2-299 GEN
Solar/Wind Harmer
2.68
962861AG1-135 GEN
Solar/Wind Harmer
8.916
3145683EARLEYS
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.802
3146263WOODLND
Solar/Wind Harmer
-0.023
962491AG1-098 GEN
Solar/Wind Harmer
15.74
316011AB1-132 GEN
Solar/Wind Harmer
4.894
962571AG1-106 GEN
Solar/Wind Harmer
3.363
971795AH1-408 GEN
Solar/Wind Harmer
17.524
3145963POPLR C
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316190AA2-174 GEN
Solar/Wind Harmer
0.286
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Adder
1.864
316174AB2-169 GEN
Solar/Wind Harmer
3.565
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.039
3144293JTRSVLE
Adder
0.609
3151751LOISA D
Adder
10.888
972277AH1-723 GEN
Adder
88.526
971133AH1-012 GEN
50/50
5.661
944641AF1-129 GEN
50/50
122.675
3142366NRTHEST
50/50
0.837
970533AG2-339 GEN
50/50
21.455
970531AG2-338 GEN
50/50
8.582
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.619
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.376
316447AC1-158 HLD
Solar/Wind Harmer
15.154
971223AH1-071 GEN
Solar/Wind Harmer
3.72
3143526WINTERP
Solar/Wind Harmer
-0.15
316240AF1-291 C
Solar/Wind Harmer
0.821
3150701DARBY 4
Adder
17.277
3150681DARBY 2
Adder
17.257
3150671DARBY 1
Adder
17.237
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
8.696
315697AD1-025 GEN
Solar/Wind Harmer
5.454
316036AC1-147 C
Solar/Wind Harmer
0.727
3150991CHESPKB
Adder
2.511
3150991CHESPKB
Adder
2.451
316236AE1-162_GEN
Solar/Wind Harmer
0.811
3142956BIRDNECK
Solar/Wind Harmer
1.443
316316AC1-027 C
Solar/Wind Harmer
0.826
316185AD1-033 GEN
Solar/Wind Harmer
2.835
970657AG2-426 GEN
Solar/Wind Harmer
8.398
970657AG2-426 GEN
Solar/Wind Harmer
1.756
3142946ENON
Solar/Wind Harmer
-0.003
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.803
316018AA1-139 ULT2
Solar/Wind Harmer
2.288
316017AA1-139 ULT1
Solar/Wind Harmer
2.161
316075AC2-137 C
Solar/Wind Harmer
0.72
3137176SLIGO L2192
Solar/Wind Harmer
-0.105
3146456SLIGO L269
Solar/Wind Harmer
3.148
3130086AYDLETT
Solar/Wind Harmer
-0.106
972185AH1-677 GEN
Adder
13.195
3144356SAPONY
Solar/Wind Harmer
0.921
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.736
316433W1029_GEN2
Solar/Wind Harmer
4.736
972187AH1-678 GEN
Adder
6.618
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.78
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
970933AG2-581 GEN
Solar/Wind Harmer
24.093
315742AE1-103 GEN
Solar/Wind Harmer
2.673
316441AF1-014 GEN
Solar/Wind Harmer
1.72
957411AF2-035 GEN
Solar/Wind Harmer
11.438
970317AG2-208 GEN
Solar/Wind Harmer
11.12
3146376EDENTON
Solar/Wind Harmer
0.754
3146376EDENTON
Solar/Wind Harmer
0.754
315673AE1-157 GEN
Solar/Wind Harmer
18.839
3150391LDYSMT3
Adder
29.312
972195AH1-682 GEN
Adder
3.852
316065AD1-022 GEN
Solar/Wind Harmer
12.136
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
30.078
316487AF1-042 GEN
Solar/Wind Harmer
3.169
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.173
316181AB2-040 GEN
Solar/Wind Harmer
3.283
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.354
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.611
3145593CAROLNA
Solar/Wind Harmer
0.193
3145783HORNRTN
Solar/Wind Harmer
2.737
3145783HORNRTN
Solar/Wind Harmer
2.19
3145783HORNRTN
Solar/Wind Harmer
0.684
3145783HORNRTN
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3150341NORNECKC1
Adder
2.142
3150341NORNECKC1
Adder
2.125
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3151731LOISA B
Adder
10.888
3151721LOISA A
Adder
10.832
971741AH1-377 GEN
Solar/Wind Harmer
1.353
971531AH1-263 GEN
50/50
60.354
316303AF2-085
50/50
4.709
971285AH1-108 GEN
50/50
1.989
970603AG2-384 GEN
50/50
5.174
316164AC1-076 GEN
Solar/Wind Harmer
3.016
316233AE1-074 FULL
Solar/Wind Harmer
0.779
971281AH1-106 GEN
Solar/Wind Harmer
4.705
971283AH1-107 GEN
Solar/Wind Harmer
4.705
3143316POE
Solar/Wind Harmer
-0.107
941031AE2-094 GEN
Solar/Wind Harmer
50.85
944011AF1-069 GEN
Solar/Wind Harmer
15.933
316132AB2-190 GEN1
Solar/Wind Harmer
2.733
316369SG1_INVT
Solar/Wind Harmer
4.818
3151081ELIZAR1
Adder
21.985
3151091ELIZAR2
Adder
21.603
3152611GOSPORTB
Adder
3.052
3152621GOSPORTC
Adder
2.591
3152601GOSPORTA
Adder
2.39
971445AH1-216 GEN
Solar/Wind Harmer
16.65
972265AH1-717 GEN
Adder
18.58
3151201GRAVEL4
Adder
17.417
3151191GRAVEL3
Adder
17.197
3151211GRAVEL5
Adder
17.197
316312AB1-027
Solar/Wind Harmer
0.903
957871AF2-081 GEN
Solar/Wind Harmer
13.355
970673AG2-436 GEN
Solar/Wind Harmer
55.995
970673AG2-436 GEN
Solar/Wind Harmer
28.352
315833AF1-017_GEN
Solar/Wind Harmer
5.061
316349AD2-085 GEN
Solar/Wind Harmer
2.37
319010AE1-072 C
Solar/Wind Harmer
5.389
316311AC2-079 GEN
Solar/Wind Harmer
13.437
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.802
315976AC1-164 GENA
Solar/Wind Harmer
28.019
316169AC1-164_GENC
Solar/Wind Harmer
24.206
315975AC1-164 GENB
Solar/Wind Harmer
0.829
315835AF2-110_GEN
Solar/Wind Harmer
3.311
316315AB2-025 C
Solar/Wind Harmer
0.712
313526AB2-022
Solar/Wind Harmer
0.712
972189AH1-679 GEN
Adder
3.929
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
971967AH1-528 GEN
Solar/Wind Harmer
49.492
315814AE2-033 C
Solar/Wind Harmer
24.499
316321Z2-027
Solar/Wind Harmer
0.709
3146396TANGLEW
Solar/Wind Harmer
0.484
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
971167AH1-042 GEN
Solar/Wind Harmer
25.196
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
957831AF2-077 GEN
Solar/Wind Harmer
0.782
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143873LANEXA
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.351
316314AB2-024 C
Solar/Wind Harmer
2.185
316059AD1-063 C
Solar/Wind Harmer
0.576
315662AE1-191 GEN
Solar/Wind Harmer
3.067
315666AE1-190 GEN
Solar/Wind Harmer
0.767
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
957601AF2-054 GEN
Solar/Wind Harmer
0.758
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.665
970581AG2-369 GEN
Solar/Wind Harmer
13.472
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
2.014
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3150411LDYSMT5
Adder
29.459
3150381LDYSMT2
Adder
28.193
972213AH1-691 GEN
Adder
4.769
972215AH1-692 GEN
Adder
4.769
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.938
315733AD1-074 GEN2
Solar/Wind Harmer
4.938
315735AD1-075 GEN1
Solar/Wind Harmer
2.47
965291AG1-394 GEN
Solar/Wind Harmer
2.162
962981AG1-147 GEN
Solar/Wind Harmer
10.629
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.583
316318V4-068
Solar/Wind Harmer
0.602
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.534
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.391
316087AB2-174 GEN
Solar/Wind Harmer
3.37
315652AC1-086 GEN
Solar/Wind Harmer
26.316
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
3141813NORNECK
Solar/Wind Harmer
-0.023
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.409
972193AH1-681 GEN
Adder
3.394
316411AF1-147_GEN1
Solar/Wind Helper
0.818
316415AF1-147_GEN2
Solar/Wind Helper
0.818
3138216PACIFIC
Solar/Wind Helper
0.04
LAGNLTFEXP_LAGN->PJM
CLTF
8.194
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.289
TVALTFEXP_TVA->PJM
CLTF
4.152
CPLELTFEXP_CPLE->PJM
CLTF
12.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.692
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.16
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.053
MECLTFEXP_MEC->PJM
CLTF
3.551
SIGELTFEXP_SIGE->PJM
CLTF
0.108
NYPJM->LTFIMP_NY
CLTF
3.429
LGEELTFEXP_LGEE->PJM
CLTF
1.289
WECLTFEXP_WEC->PJM
CLTF
0.615

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P2-2: MORRISVILLE B1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: MORRISVILLE B1_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:140.84 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4391.4
MW Contribution:26.75
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.567
971285AH1-108 GEN
50/50
1.443
315244AE2-183_ST
50/50
5.089
963041AG1-153 GEN
50/50
4.694
3151081ELIZAR1
50/50
17.092
3151091ELIZAR2
50/50
16.795
316164AC1-076 GEN
Solar/Wind Harmer
2.467
316233AE1-074 FULL
Solar/Wind Harmer
0.578
971281AH1-106 GEN
Solar/Wind Harmer
3.494
971283AH1-107 GEN
Solar/Wind Harmer
3.494
941031AE2-094 GEN
Solar/Wind Harmer
38.562
944011AF1-069 GEN
Solar/Wind Harmer
12.083
970673AG2-436 GEN
Solar/Wind Harmer
42.445
970673AG2-436 GEN
Solar/Wind Harmer
21.491
3143316POE
Solar/Wind Harmer
-0.079
971967AH1-528 GEN
Solar/Wind Harmer
37.503
3152611GOSPORTB
Adder
2.236
3152621GOSPORTC
Adder
1.898
3152601GOSPORTA
Adder
1.751
316315AB2-025 C
Solar/Wind Harmer
0.531
957871AF2-081 GEN
Solar/Wind Harmer
9.796
315814AE2-033 C
Solar/Wind Harmer
18.244
971445AH1-216 GEN
Solar/Wind Harmer
12.122
319010AE1-072 C
Solar/Wind Harmer
3.953
3146406KITTY HAWK
Solar/Wind Harmer
0.016
315833AF1-017_GEN
Solar/Wind Harmer
3.709
316349AD2-085 GEN
Solar/Wind Harmer
1.737
316311AC2-079 GEN
Solar/Wind Harmer
9.849
316305AF2-043 C
Solar/Wind Harmer
0.588
972265AH1-717 GEN
Adder
13.481
3151201GRAVEL4
Adder
12.638
3151191GRAVEL3
Adder
12.478
3151211GRAVEL5
Adder
12.478
316369SG1_INVT
Solar/Wind Harmer
3.482
316132AB2-190 GEN1
Solar/Wind Harmer
1.97
315835AF2-110_GEN
Solar/Wind Harmer
2.429
313526AB2-022
Solar/Wind Harmer
0.523
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
316321Z2-027
Solar/Wind Harmer
0.521
3146396TANGLEW
Solar/Wind Harmer
0.355
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
11.856
970581AG2-369 GEN
Solar/Wind Harmer
10.196
315611Z1-036_GEN2
Solar/Wind Harmer
4.669
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
19.666
316169AC1-164_GENC
Solar/Wind Harmer
16.99
315975AC1-164 GENB
Solar/Wind Harmer
0.582
316312AB1-027
Solar/Wind Harmer
0.626
957831AF2-077 GEN
Solar/Wind Harmer
0.558
3138283WHITEMARSH
Solar/Wind Harmer
0.029
971167AH1-042 GEN
Solar/Wind Harmer
17.862
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315816AE2-034 GEN
Solar/Wind Harmer
1.484
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
316314AB2-024 C
Solar/Wind Harmer
1.54
965291AG1-394 GEN
Solar/Wind Harmer
1.598
315732AD1-074 GEN1
Solar/Wind Harmer
3.642
315733AD1-074 GEN2
Solar/Wind Harmer
3.642
315735AD1-075 GEN1
Solar/Wind Harmer
1.821
315662AE1-191 GEN
Solar/Wind Harmer
2.168
315666AE1-190 GEN
Solar/Wind Harmer
0.542
316059AD1-063 C
Solar/Wind Harmer
0.406
957601AF2-054 GEN
Solar/Wind Harmer
0.536
3141873WAN 176
Solar/Wind Harmer
-0.004
316318V4-068
Solar/Wind Harmer
0.445
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.812
946281AF1-292 GEN
Solar/Wind Harmer
0.397
972189AH1-679 GEN
Adder
2.633
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.154
961941AG1-037 GEN
Solar/Wind Harmer
0.132
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
316087AB2-174 GEN
Solar/Wind Harmer
2.508
3138133OCRAN
Solar/Wind Harmer
-0.005
315607AA1-063A GEN
Solar/Wind Harmer
1.773
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3141783LANCAST
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.007
315652AC1-086 GEN
Solar/Wind Harmer
19.55
3137643SOCKMAN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
7.478
3146033SCOT NK
Solar/Wind Harmer
-0.067
970831AG2-522 GEN
Solar/Wind Harmer
8.348
3150411LDYSMT5
Adder
18.158
3150381LDYSMT2
Adder
17.377
972213AH1-691 GEN
Adder
2.94
972215AH1-692 GEN
Adder
2.94
972205AH1-687 GEN
Adder
5.595
3152261N ANNA2
50/50
17.068
3150861SPRUNCD
50/50
0.882
3151031BRUNSWICKG2
50/50
2.318
3151101ELIZAR3
50/50
17.311
316044AC1-158 PL1
Solar/Wind Harmer
6.723
316450AC1-158 RIC
Solar/Wind Harmer
1.793
3147666LOUISA
Solar/Wind Harmer
-0.06
315773AC2-141 GEN
Solar/Wind Harmer
8.348
315839AE2-212 C
Solar/Wind Harmer
0.598
944581AF1-123 GEN
Solar/Wind Harmer
90.063
944601AF1-125 GEN
Solar/Wind Harmer
88.657
315813AE1-149 C
Solar/Wind Harmer
12.369
965281AG1-393 GEN
Solar/Wind Harmer
2.467
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
1.855
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.196
970661AG2-428 GEN
Solar/Wind Harmer
3.699
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.019
971153AH1-033 GEN
Solar/Wind Harmer
2.384
3151221GRAVEL6
Adder
12.623
3151171GRAVELC
Adder
2.429
961611AG1-000B GEN
Solar/Wind Harmer
4.106
315778AD1-151 GEN
Solar/Wind Harmer
16.88
970129AG2-093 GEN
Solar/Wind Harmer
10.967
970133AG2-095 GEN
Solar/Wind Harmer
2.19
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.71
316313AB2-026
Solar/Wind Harmer
0.524
316258AE1-075 C
Solar/Wind Harmer
0.471
316405AF2-144 C
Solar/Wind Harmer
0.497
3143336POWHATN
Solar/Wind Harmer
1.959
316320Y1-086
Solar/Wind Harmer
1.136
3144216WINCHST
Adder
0.645
316435W1029_GEN3
Solar/Wind Harmer
3.478
3150921YORKTN3
Adder
4.287
3146516WINFALL
Solar/Wind Harmer
-0.019
970917AG2-570 GEN
Solar/Wind Harmer
47.625
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.006
3145273HOLLAND
Solar/Wind Harmer
-0.014
316382AG1-145 C
Solar/Wind Harmer
0.572
970293AG2-193 GEN
Solar/Wind Harmer
2.359
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.874
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315614AA2-178 GEN
Solar/Wind Harmer
1.978
316365GEN2_N
Solar/Wind Harmer
1.225
3156081AA2-088 GEN
Solar/Wind Harmer
5.867
971157AH1-035 GEN
Solar/Wind Harmer
2.257
3141843SHACKLE
Adder
0.82
316203AE2-005 GEN
Solar/Wind Harmer
7.603
315737AD1-076 GEN
Solar/Wind Harmer
3.423
316280AD1-041 GEN
Solar/Wind Harmer
1.355
3141766HARMONY
Solar/Wind Harmer
1.601
316156AD2-030 GEN
Solar/Wind Harmer
0.479
3141873WAN 176
Solar/Wind Harmer
2.127
316473AC1-191 GEN
Solar/Wind Harmer
1.925
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3146206CASHIE
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.027
961681AG1-008 GEN
Solar/Wind Harmer
14.027
3132273ORANGE
Solar/Wind Harmer
-0.004
966621AG1-532 GEN
Solar/Wind Harmer
0.36
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.376
316463AE2-346 GEN
Solar/Wind Harmer
0.285
316140AB2-099
Solar/Wind Harmer
0.119
962331AG1-082 GEN
Solar/Wind Harmer
2.202
313506AB2-031 GEN
Solar/Wind Harmer
1.407
316478AD1-087 GEN
Solar/Wind Harmer
1.513
316486AD2-202 GEN
Solar/Wind Harmer
0.443
3146263WOODLND
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3147043LAWRENC
Solar/Wind Harmer
-0.01
316317KELFORD C
Solar/Wind Harmer
0.812
3145823KELFORD
Solar/Wind Harmer
-0.017
3145963POPLR C
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.017
962971AG1-146 GEN
Solar/Wind Harmer
3.205
316484AD2-074 GEN
Solar/Wind Harmer
4.255
970009AG2-005 GEN
Solar/Wind Harmer
2.113
970909AG2-566 GEN
Solar/Wind Harmer
1.6
3144293JTRSVLE
Adder
0.458
3150351NORNECKC2
Adder
1.449
3151761LOISA E
Adder
18.847
972183AH1-676 GEN
Adder
147.354
3150401LDYSMT4
Adder
18.101
3150371LDYSMT1
Adder
17.49
316210AC1-098 GEN
Solar/Wind Harmer
1.148
3152251N ANNA1
50/50
17.069
971507AH1-251 GEN
50/50
10.56
970119AG2-088 GEN
50/50
26.753
3150851SPRUNCC
50/50
0.882
315243AE2-183_GT3
50/50
2.943
3151051BRUNSWICKS1
50/50
4.812
3151021BRUNSWICKG1
50/50
2.318
971451AH1-221 GEN
50/50
7.041
316045AC1-158 PL2
Solar/Wind Harmer
21.506
3147666LOUISA
Solar/Wind Harmer
-0.105
316192AB2-158 GEN
Solar/Wind Harmer
3.057
3143226MDLTHAN
Solar/Wind Harmer
-0.022
3143526WINTERP
Solar/Wind Harmer
-0.111
940641AE2-051 GEN
Solar/Wind Harmer
19.731
939411AE1-173 GEN
Solar/Wind Harmer
103.557
316294AC1-161 GEN
Solar/Wind Harmer
6.454
944591AF1-124 GEN
Solar/Wind Harmer
90.387
316375AC2-012 GEN
Solar/Wind Harmer
6.828
3150981CHESPKA
Adder
2.192
970659AG2-427 GEN
Solar/Wind Harmer
10.468
316381AD1-082 GEN
Solar/Wind Harmer
1.806
315671AE2-027_GEN
Solar/Wind Harmer
14.765
3142543TWELFTH
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
20.871
316388AE2-253 GEN
Solar/Wind Harmer
1.322
3145336SMITFLD
Solar/Wind Harmer
-0.078
3146456SLIGO L269
Solar/Wind Harmer
-0.019
316246AF1-032 C
Solar/Wind Harmer
0.395
3151171GRAVELC
Adder
1.847
961611AG1-000B GEN
Solar/Wind Harmer
9.624
971647AH1-324 GEN
Solar/Wind Harmer
9.747
316072AD1-144
Solar/Wind Harmer
0.394
971069AG2-661 GEN
Solar/Wind Harmer
3.083
316458AB2-190 GEN2
Solar/Wind Harmer
1.97
970129AG2-093 GEN
Solar/Wind Harmer
4.442
3143096IRON208
Adder
0.724
316093AE2-104_GEN
Solar/Wind Harmer
5.649
3143336POWHATN
Solar/Wind Harmer
2.304
3138126ROCKLANDING
Solar/Wind Harmer
0.059
944631AF1-128 GEN
Adder
81.389
3146516WINFALL
Solar/Wind Harmer
-0.062
3146516WINFALL
Solar/Wind Harmer
-0.019
970919AG2-571 GEN
Solar/Wind Harmer
6.028
316159AE1-175 C
Solar/Wind Harmer
0.509
971317AH1-138 GEN
Solar/Wind Harmer
2.373
970087AG2-069 GEN
Solar/Wind Harmer
17.783
315800Z1-036_GEN1
Solar/Wind Harmer
4.669
3130156CHOWAN
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
3.232
3142416OLDCHRC
Solar/Wind Harmer
-0.048
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3142433PROV 92
Solar/Wind Harmer
-0.074
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
3145663CRESWEL
Solar/Wind Harmer
-0.051
971163AH1-040 GEN
Solar/Wind Harmer
17.189
957481AF2-042 GEN
Solar/Wind Harmer
56.834
316023GEN1_S
Solar/Wind Harmer
1.225
971777AH1-397 GEN
Solar/Wind Harmer
2.121
3141843SHACKLE
Adder
0.82
3141766HARMONY
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.53
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.464
315693AD1-088 GEN
Solar/Wind Harmer
8.916
962491AG1-098 GEN
Solar/Wind Harmer
11.891
960081AF2-299 GEN
Solar/Wind Harmer
1.996
3146173TUNIS
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.017
3146263WOODLND
Solar/Wind Harmer
-0.017
971795AH1-408 GEN
Solar/Wind Harmer
13.07
316011AB1-132 GEN
Solar/Wind Harmer
3.636
962571AG1-106 GEN
Solar/Wind Harmer
2.498
316190AA2-174 GEN
Solar/Wind Harmer
0.212
3147043LAWRENC
Adder
1.392
3145823KELFORD
Solar/Wind Harmer
-0.017
3145963POPLR C
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.017
316174AB2-169 GEN
Solar/Wind Harmer
2.636
961951AG1-038 GEN
Solar/Wind Harmer
2.227
962861AG1-135 GEN
Solar/Wind Harmer
6.255
3144293JTRSVLE
Adder
0.458
3150351NORNECKC2
Adder
1.425
3151751LOISA D
Adder
9.244
972197AH1-683 GEN
Adder
2.827
972219AH1-694 GEN
Adder
2.035
316212AC1-099_GEN
Solar/Wind Harmer
0.638
971133AH1-012 GEN
50/50
4.837
970533AG2-339 GEN
50/50
16.271
970531AG2-338 GEN
50/50
6.508
315242AE2-183_GT2
50/50
2.943
315241AE2-183_GT1
50/50
2.925
972185AH1-677 GEN
50/50
10.611
3151041BRUNSWICKG3
50/50
2.318
972187AH1-678 GEN
50/50
5.32
316447AC1-158 HLD
Solar/Wind Harmer
14.784
971223AH1-071 GEN
Solar/Wind Harmer
2.818
3143526WINTERP
Solar/Wind Harmer
-0.111
316036AC1-147 C
Solar/Wind Harmer
0.532
3150991CHESPKB
Adder
1.839
3150991CHESPKB
Adder
1.795
3142956BIRDNECK
Solar/Wind Harmer
1.058
316316AC1-027 C
Solar/Wind Harmer
0.605
316185AD1-033 GEN
Solar/Wind Harmer
2.079
316240AF1-291 C
Solar/Wind Harmer
0.594
3145506HICKORY
Solar/Wind Harmer
-0.078
3145506HICKORY
Solar/Wind Harmer
-0.047
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.147
970657AG2-426 GEN
Solar/Wind Harmer
1.286
3144356SAPONY
Solar/Wind Harmer
0.686
944641AF1-129 GEN
Adder
83.418
316339AD2-160 GEN
Solar/Wind Harmer
1.322
316236AE1-162_GEN
Solar/Wind Harmer
0.591
316018AA1-139 ULT2
Solar/Wind Harmer
1.678
316017AA1-139 ULT1
Solar/Wind Harmer
1.585
3137176SLIGO L2192
Solar/Wind Harmer
-0.077
3146456SLIGO L269
Solar/Wind Harmer
2.31
3130086AYDLETT
Solar/Wind Harmer
-0.078
316033AB2-134 GEN
Solar/Wind Harmer
6.285
315697AD1-025 GEN
Solar/Wind Harmer
3.942
970933AG2-581 GEN
Solar/Wind Harmer
18.245
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.478
316433W1029_GEN2
Solar/Wind Harmer
3.478
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3142366NRTHEST
Adder
0.556
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3150691DARBY 3
Adder
12.185
3150701DARBY 4
Adder
12.157
3150681DARBY 2
Adder
12.142
3150671DARBY 1
Adder
12.128
3142946ENON
Solar/Wind Harmer
-0.002
315742AE1-103 GEN
Solar/Wind Harmer
1.967
316075AC2-137 C
Solar/Wind Harmer
0.504
3146376EDENTON
Solar/Wind Harmer
0.555
3146376EDENTON
Solar/Wind Harmer
0.555
3142296MT RD221
Adder
0.528
970099AG2-077 GEN
Solar/Wind Harmer
22.734
316441AF1-014 GEN
Solar/Wind Harmer
1.216
316065AD1-022 GEN
Solar/Wind Harmer
8.955
966871AG1-558 GEN
Solar/Wind Harmer
0.538
966871AG1-558 GEN
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
0.498
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
316181AB2-040 GEN
Solar/Wind Harmer
2.443
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.748
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.941
3145593CAROLNA
Solar/Wind Harmer
0.143
3145783HORNRTN
Solar/Wind Harmer
2.035
3145783HORNRTN
Solar/Wind Harmer
1.628
3145783HORNRTN
Solar/Wind Harmer
0.509
3145783HORNRTN
Solar/Wind Harmer
0.203
3145796HORNRTN
Solar/Wind Harmer
-0.051
971741AH1-377 GEN
Solar/Wind Harmer
19.85
316487AF1-042 GEN
Solar/Wind Harmer
2.227
970301AG2-198 GEN
Solar/Wind Harmer
8.425
3144293JTRSVLE
Adder
0.458
3144293JTRSVLE
Adder
0.386
3150341NORNECKC1
Adder
1.496
3150341NORNECKC1
Adder
1.484
3151731LOISA B
Adder
9.244
3151721LOISA A
Adder
9.197
3150391LDYSMT3
Adder
18.067
972195AH1-682 GEN
Adder
2.374
LAGNLTFEXP_LAGN->PJM
CLTF
5.963
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.52
TVALTFEXP_TVA->PJM
CLTF
3.02
CPLELTFEXP_CPLE->PJM
CLTF
9
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.817
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.186
MECLTFEXP_MEC->PJM
CLTF
2.509
SIGELTFEXP_SIGE->PJM
CLTF
0.076
NYPJM->LTFIMP_NY
CLTF
2.547
LGEELTFEXP_LGEE->PJM
CLTF
0.9
WECLTFEXP_WEC->PJM
CLTF
0.426

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.41 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:4167.61
MW Contribution:26.75
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
17.069
971507AH1-251 GEN
50/50
10.56
970119AG2-088 GEN
50/50
26.753
3150851SPRUNCC
50/50
0.882
315243AE2-183_GT3
50/50
2.943
3151051BRUNSWICKS1
50/50
4.812
3151021BRUNSWICKG1
50/50
2.318
971451AH1-221 GEN
50/50
7.041
316045AC1-158 PL2
Solar/Wind Harmer
9.498
3147666LOUISA
Solar/Wind Harmer
0.935
316192AB2-158 GEN
Solar/Wind Harmer
1.293
3143226MDLTHAN
Solar/Wind Harmer
0.2
3143526WINTERP
Solar/Wind Harmer
0.994
940641AE2-051 GEN
Solar/Wind Harmer
14.986
939411AE1-173 GEN
Solar/Wind Harmer
78.651
316294AC1-161 GEN
Solar/Wind Harmer
3.077
944591AF1-124 GEN
Solar/Wind Harmer
39.816
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.192
970659AG2-427 GEN
Solar/Wind Harmer
8.481
316381AD1-082 GEN
Solar/Wind Harmer
0.183
315671AE2-027_GEN
Solar/Wind Harmer
11.214
3142543TWELFTH
Solar/Wind Harmer
0.017
970661AG2-428 GEN
Solar/Wind Harmer
17.39
316388AE2-253 GEN
Solar/Wind Harmer
0.547
3145336SMITFLD
Solar/Wind Harmer
0.697
3146456SLIGO L269
Solar/Wind Harmer
0.174
316246AF1-032 C
Solar/Wind Harmer
0.078
3151171GRAVELC
Adder
1.847
961611AG1-000B GEN
Solar/Wind Harmer
9.102
971647AH1-324 GEN
Solar/Wind Harmer
7.403
316072AD1-144
Solar/Wind Harmer
0.063
971069AG2-661 GEN
Solar/Wind Harmer
3.083
316458AB2-190 GEN2
Solar/Wind Harmer
0.93
970129AG2-093 GEN
Solar/Wind Harmer
4.931
3143096IRON208
Adder
0.724
316093AE2-104_GEN
Solar/Wind Harmer
2.908
3143336POWHATN
Solar/Wind Harmer
3.072
3138126ROCKLANDING
Solar/Wind Harmer
0.078
944631AF1-128 GEN
Adder
81.389
3146516WINFALL
Solar/Wind Harmer
0.552
3146516WINFALL
Solar/Wind Harmer
0.17
970919AG2-571 GEN
Solar/Wind Harmer
6.028
316159AE1-175 C
Solar/Wind Harmer
0.146
971317AH1-138 GEN
Solar/Wind Harmer
1.261
970087AG2-069 GEN
Solar/Wind Harmer
13.506
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.166
316336AC2-165 C
Solar/Wind Harmer
0.006
3142416OLDCHRC
Solar/Wind Harmer
0.43
3142416OLDCHRC
Solar/Wind Harmer
0.165
3142433PROV 92
Solar/Wind Harmer
0.658
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
3145663CRESWEL
Solar/Wind Harmer
0.457
971163AH1-040 GEN
Solar/Wind Harmer
13.055
957481AF2-042 GEN
Solar/Wind Harmer
43.165
316023GEN1_S
Solar/Wind Harmer
0.363
971777AH1-397 GEN
Solar/Wind Harmer
0.424
3141843SHACKLE
Adder
0.82
3141766HARMONY
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.635
3145893MURPHYS
Solar/Wind Harmer
0.706
3146206CASHIE
Solar/Wind Harmer
0.159
971547AH1-271 GEN
Solar/Wind Harmer
3.39
315693AD1-088 GEN
Solar/Wind Harmer
7.618
962491AG1-098 GEN
Solar/Wind Harmer
9.031
960081AF2-299 GEN
Solar/Wind Harmer
1.516
3146173TUNIS
Solar/Wind Harmer
0.157
3138133OCRAN
Solar/Wind Harmer
0.094
3145683EARLEYS
Solar/Wind Harmer
0.156
3146263WOODLND
Solar/Wind Harmer
0.155
971795AH1-408 GEN
Solar/Wind Harmer
10.34
316011AB1-132 GEN
Solar/Wind Harmer
2.811
962571AG1-106 GEN
Solar/Wind Harmer
2.2
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
1.392
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145783HORNRTN
Solar/Wind Harmer
0.152
3145796HORNRTN
Solar/Wind Harmer
0.502
3145796HORNRTN
Solar/Wind Harmer
0.152
316174AB2-169 GEN
Solar/Wind Harmer
0.004
962861AG1-135 GEN
Solar/Wind Harmer
4.751
316212AC1-099_GEN
Solar/Wind Harmer
0.768
316129AC1-054 GEN
Solar/Wind Harmer
0.557
971065AG2-659 GEN
Solar/Wind Harmer
6.296
3146293MARTNCO
Solar/Wind Harmer
0.137
970937AG2-583 GEN
Solar/Wind Harmer
9.004
3152261N ANNA2
50/50
17.068
3150861SPRUNCD
50/50
0.882
3151031BRUNSWICKG2
50/50
2.318
3151101ELIZAR3
50/50
17.311
316044AC1-158 PL1
Solar/Wind Harmer
2.971
316450AC1-158 RIC
Solar/Wind Harmer
0.792
3147666LOUISA
Solar/Wind Harmer
0.538
315773AC2-141 GEN
Solar/Wind Harmer
6.485
315839AE2-212 C
Solar/Wind Harmer
0.001
944581AF1-123 GEN
Solar/Wind Harmer
39.675
944601AF1-125 GEN
Solar/Wind Harmer
39.064
315813AE1-149 C
Solar/Wind Harmer
9.394
965281AG1-393 GEN
Solar/Wind Harmer
1.874
3144873MCLAUGH
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
1.855
3144536CHRHLND
Solar/Wind Harmer
0.026
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
3.699
3145336SMITFLD
Solar/Wind Harmer
0.07
3146456SLIGO L269
Solar/Wind Harmer
0.174
971153AH1-033 GEN
Solar/Wind Harmer
2.012
3151221GRAVEL6
Adder
12.623
3151171GRAVELC
Adder
2.429
961611AG1-000B GEN
Solar/Wind Harmer
4.628
315778AD1-151 GEN
Solar/Wind Harmer
13.874
970129AG2-093 GEN
Solar/Wind Harmer
10.479
970133AG2-095 GEN
Solar/Wind Harmer
1.663
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.71
316313AB2-026
Solar/Wind Harmer
0.109
316258AE1-075 C
Solar/Wind Harmer
0.13
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.611
316320Y1-086
Solar/Wind Harmer
0.001
3144216WINCHST
Adder
0.645
316435W1029_GEN3
Solar/Wind Harmer
0.001
3150921YORKTN3
Adder
4.287
3146516WINFALL
Solar/Wind Harmer
0.17
970917AG2-570 GEN
Solar/Wind Harmer
15.071
3146626S HERTFORD
Solar/Wind Harmer
0.169
3142946ENON
Solar/Wind Harmer
0.057
3145273HOLLAND
Solar/Wind Harmer
0.127
316382AG1-145 C
Solar/Wind Harmer
0.001
970293AG2-193 GEN
Solar/Wind Harmer
1.792
3146376EDENTON
Solar/Wind Harmer
0.166
3142416OLDCHRC
Solar/Wind Harmer
1.602
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315614AA2-178 GEN
Solar/Wind Harmer
0.934
316365GEN2_N
Solar/Wind Harmer
0.363
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
971157AH1-035 GEN
Solar/Wind Harmer
1.929
3141843SHACKLE
Adder
0.82
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
315737AD1-076 GEN
Solar/Wind Harmer
2.062
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
2.134
316156AD2-030 GEN
Solar/Wind Harmer
0.118
3141873WAN 176
Solar/Wind Harmer
2.836
316473AC1-191 GEN
Solar/Wind Harmer
0.538
3145893MURPHYS
Solar/Wind Harmer
0.266
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
957521AF2-046 GEN
Solar/Wind Harmer
11.795
961681AG1-008 GEN
Solar/Wind Harmer
11.795
3132273ORANGE
Solar/Wind Harmer
0.032
971133AH1-012 GEN
50/50
4.837
970533AG2-339 GEN
50/50
16.271
970531AG2-338 GEN
50/50
6.508
315242AE2-183_GT2
50/50
2.943
315241AE2-183_GT1
50/50
2.925
972185AH1-677 GEN
50/50
10.611
3151041BRUNSWICKG3
50/50
2.318
972187AH1-678 GEN
50/50
5.32
316447AC1-158 HLD
Solar/Wind Harmer
6.529
971223AH1-071 GEN
Solar/Wind Harmer
2.14
3143526WINTERP
Solar/Wind Harmer
0.994
316036AC1-147 C
Solar/Wind Harmer
0.033
3150991CHESPKB
Adder
1.839
3150991CHESPKB
Adder
1.795
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.168
316185AD1-033 GEN
Solar/Wind Harmer
0.005
316240AF1-291 C
Solar/Wind Harmer
0.001
3145506HICKORY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
0.42
3145506HICKORY
Solar/Wind Harmer
0.105
970657AG2-426 GEN
Solar/Wind Harmer
6.132
970657AG2-426 GEN
Solar/Wind Harmer
1.286
3144356SAPONY
Solar/Wind Harmer
1.464
944641AF1-129 GEN
Adder
83.418
316339AD2-160 GEN
Solar/Wind Harmer
0.283
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.097
3137176SLIGO L2192
Solar/Wind Harmer
0.693
3146456SLIGO L269
Solar/Wind Harmer
3.08
3130086AYDLETT
Solar/Wind Harmer
0.695
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.195
970933AG2-581 GEN
Solar/Wind Harmer
13.857
3146386ELIZ CT
Solar/Wind Harmer
0.172
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3142366NRTHEST
Adder
0.556
3146626S HERTFORD
Solar/Wind Harmer
0.169
3146626S HERTFORD
Solar/Wind Harmer
0.169
3150691DARBY 3
Adder
12.185
3150701DARBY 4
Adder
12.157
3150681DARBY 2
Adder
12.142
3150671DARBY 1
Adder
12.128
3142946ENON
Solar/Wind Harmer
0.017
315742AE1-103 GEN
Solar/Wind Harmer
0.002
316075AC2-137 C
Solar/Wind Harmer
0.046
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
3142296MT RD221
Adder
0.528
970099AG2-077 GEN
Solar/Wind Harmer
17.266
316065AD1-022 GEN
Solar/Wind Harmer
7.34
966871AG1-558 GEN
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
1.063
3145893MURPHYS
Solar/Wind Harmer
0.286
3146173TUNIS
Solar/Wind Harmer
0.157
3146173TUNIS
Solar/Wind Harmer
0.157
316181AB2-040 GEN
Solar/Wind Harmer
0.226
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.093
316426AA2-053 GEN
Solar/Wind Harmer
0.52
3145593CAROLNA
Solar/Wind Harmer
0.153
3145593CAROLNA
Solar/Wind Harmer
0.153
966811AG1-552 GEN
Solar/Wind Harmer
1.665
3145593CAROLNA
Solar/Wind Harmer
0.191
3145783HORNRTN
Solar/Wind Harmer
2.713
3145783HORNRTN
Solar/Wind Harmer
2.17
3145783HORNRTN
Solar/Wind Harmer
0.678
3145783HORNRTN
Solar/Wind Harmer
0.271
3145796HORNRTN
Solar/Wind Harmer
0.457
971741AH1-377 GEN
Solar/Wind Harmer
15.076
970301AG2-198 GEN
Solar/Wind Harmer
6.399
958261AF2-120 GEN
Solar/Wind Harmer
4.886
316274AC1-208 GEN
Solar/Wind Harmer
0.766
3145933PARMELE
Solar/Wind Harmer
0.295
3145933PARMELE
Solar/Wind Harmer
0.147
957411AF2-035 GEN
Solar/Wind Harmer
6.2
970317AG2-208 GEN
Solar/Wind Harmer
5.744
939181AE1-148 GEN
Solar/Wind Harmer
6.96
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.152
971775AH1-396 GEN
Solar/Wind Harmer
0.231
958211AF2-115 GEN
Solar/Wind Harmer
1.728
963191AG1-168 GEN
Solar/Wind Harmer
0.576
3144293JTRSVLE
Adder
0.458
3144293JTRSVLE
Adder
0.386
3147133PAMPLIN
Solar/Wind Harmer
0.144
3147133PAMPLIN
Solar/Wind Harmer
0.115
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.496
3150341NORNECKC1
Adder
1.484
966001AG1-469 GEN
Solar/Wind Harmer
0.083
3151731LOISA B
Adder
9.244
3151721LOISA A
Adder
9.197
315673AE1-157 GEN
Solar/Wind Harmer
9.786
3145493TOT1
Solar/Wind Harmer
0.326
3145453TOT5
Solar/Wind Harmer
0.196
3145603CNETO
Solar/Wind Harmer
0.13
961601AG1-000A GEN
Solar/Wind Harmer
2.463
316263AC1-034 GEN
Solar/Wind Harmer
5.264
962561AG1-105 GEN
Solar/Wind Harmer
6.627
3146776BUCKING
Solar/Wind Harmer
0.551
3146776BUCKING
Solar/Wind Harmer
0.045
964791AG1-342 GEN
Solar/Wind Harmer
2.629
3146843MT LREL
Solar/Wind Harmer
0.137
3146843MT LREL
Solar/Wind Harmer
0.137
3150391LDYSMT3
Adder
18.067
972195AH1-682 GEN
Adder
2.374
316468AD1-105 GEN
Solar/Wind Harmer
-0.044
971489AH1-241 GEN
Solar/Wind Harmer
6.519
316222AC1-221 GEN
Solar/Wind Harmer
0.492
3146173TUNIS
Solar/Wind Harmer
0.157
3156021HOLLOMANSOL
Solar/Wind Harmer
0.713
316463AE2-346 GEN
Solar/Wind Harmer
0.135
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.672
313506AB2-031 GEN
Solar/Wind Harmer
0.482
316478AD1-087 GEN
Solar/Wind Harmer
0.543
316486AD2-202 GEN
Solar/Wind Harmer
0.159
3146263WOODLND
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3147043LAWRENC
Solar/Wind Harmer
0.092
316317KELFORD C
Solar/Wind Harmer
0.015
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145796HORNRTN
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.152
962971AG1-146 GEN
Solar/Wind Harmer
2.434
970009AG2-005 GEN
Solar/Wind Harmer
1.123
970909AG2-566 GEN
Solar/Wind Harmer
1.6
316210AC1-098 GEN
Solar/Wind Harmer
1.377
316404AE1-155 C
Solar/Wind Harmer
0.033
3145933PARMELE
Solar/Wind Harmer
0.147
966801AG1-551 GEN
Solar/Wind Harmer
1.716
315724AD1-057 GEN
Solar/Wind Harmer
0.543
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
316131AB2-060 GEN
Solar/Wind Harmer
0.454
964241AG1-285 GEN
Solar/Wind Harmer
9.624
315785AD2-033 C
Solar/Wind Harmer
1.173
970257AG2-171 GEN
Solar/Wind Harmer
4.614
959311AF2-222 GEN
Solar/Wind Harmer
12.815
316170AC1-121 GEN2
Solar/Wind Harmer
0.154
963181AG1-167 GEN
Solar/Wind Harmer
0.576
3144293JTRSVLE
Adder
0.458
3147133PAMPLIN
Solar/Wind Harmer
0.452
971193AH1-056 GEN
Solar/Wind Harmer
8.764
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.086
316327AA2-057 GEN
Solar/Wind Harmer
0.217
3150351NORNECKC2
Adder
1.449
3151761LOISA E
Adder
18.847
3146233WITAKRS
Solar/Wind Harmer
0.708
3146233WITAKRS
Solar/Wind Harmer
0.096
3138543CONSLDL
Solar/Wind Harmer
0.093
3146073TAR RVR
Solar/Wind Harmer
0.141
3146083TARBORO
Solar/Wind Harmer
0.141
961601AG1-000A GEN
Solar/Wind Harmer
9.854
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.138
971623AH1-311 GEN
Solar/Wind Harmer
0.277
972183AH1-676 GEN
Adder
147.354
3146776BUCKING
Solar/Wind Harmer
0.05
3150401LDYSMT4
Adder
18.101
3150371LDYSMT1
Adder
17.49
971781AH1-399 GEN
Solar/Wind Harmer
0.177
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.61
3141906WESTMOR
Solar/Wind Harmer
0.051
970221AG2-151 GEN
Solar/Wind Harmer
6.519
971683AH1-343 GEN
Solar/Wind Harmer
4.456
970737AG2-469 GEN
Solar/Wind Harmer
5.095
316283AC2-100 C
Solar/Wind Harmer
0.231
315687AD1-152 GEN
Solar/Wind Harmer
0.005
966881AG1-559 GEN
Solar/Wind Harmer
0.168
3141726DUNNSVL
Solar/Wind Harmer
0.58
315722AD1-056 GEN
Solar/Wind Harmer
0.916
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
970685AG2-442 GEN
Solar/Wind Harmer
10.759
316254AC1-120 GEN1
Solar/Wind Harmer
0.307
316237AB2-079_GEN
Solar/Wind Harmer
0.001
963171AG1-166 GEN
Solar/Wind Harmer
0.768
971563AH1-280 GEN
Solar/Wind Harmer
1.536
3144293JTRSVLE
Adder
0.458
3146926FARMVIL
Solar/Wind Harmer
0.086
3150351NORNECKC2
Adder
1.425
316494AC1-189 GEN
Solar/Wind Harmer
0.481
3151751LOISA D
Adder
9.244
3146233WITAKRS
Solar/Wind Harmer
0.561
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.141
3145493TOT1
Solar/Wind Harmer
0.626
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.111
316359AB2-059 GEN
Solar/Wind Harmer
0.498
316049AB1-081 GEN
Solar/Wind Harmer
0.793
3142053HEARTS
Solar/Wind Harmer
0.244
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
970401AG2-262 GEN
Solar/Wind Harmer
0.803
316337AD2-073 GEN
Solar/Wind Harmer
0.118
972197AH1-683 GEN
Adder
2.827
972219AH1-694 GEN
Adder
2.035
972003AH1-546 GEN
Solar/Wind Harmer
5.618
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.304
3147623JAMES R
Solar/Wind Harmer
0.283
972135AH1-637 GEN
Solar/Wind Harmer
0.976
316303AF2-085
50/50
3.567
971285AH1-108 GEN
50/50
1.443
315244AE2-183_ST
50/50
5.089
963041AG1-153 GEN
50/50
4.694
3151081ELIZAR1
50/50
17.092
3151091ELIZAR2
50/50
16.795
316164AC1-076 GEN
Solar/Wind Harmer
0.366
316233AE1-074 FULL
Solar/Wind Harmer
0.153
971281AH1-106 GEN
Solar/Wind Harmer
2.654
971283AH1-107 GEN
Solar/Wind Harmer
2.654
941031AE2-094 GEN
Solar/Wind Harmer
33.713
944011AF1-069 GEN
Solar/Wind Harmer
11.015
970673AG2-436 GEN
Solar/Wind Harmer
38.362
970673AG2-436 GEN
Solar/Wind Harmer
25.574
3143316POE
Solar/Wind Harmer
0.707
971967AH1-528 GEN
Solar/Wind Harmer
28.408
3152611GOSPORTB
Adder
2.236
3152621GOSPORTC
Adder
1.898
3152601GOSPORTA
Adder
1.751
316315AB2-025 C
Solar/Wind Harmer
0.141
957871AF2-081 GEN
Solar/Wind Harmer
8.68
315814AE2-033 C
Solar/Wind Harmer
13.794
971445AH1-216 GEN
Solar/Wind Harmer
12.275
319010AE1-072 C
Solar/Wind Harmer
0.876
3146406KITTY HAWK
Solar/Wind Harmer
0.022
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.119
316311AC2-079 GEN
Solar/Wind Harmer
4.99
316305AF2-043 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
13.481
3151201GRAVEL4
Adder
12.638
3151191GRAVEL3
Adder
12.478
3151211GRAVEL5
Adder
12.478
316369SG1_INVT
Solar/Wind Harmer
0.006
316132AB2-190 GEN1
Solar/Wind Harmer
0.93
315835AF2-110_GEN
Solar/Wind Harmer
1.187
313526AB2-022
Solar/Wind Harmer
0.093
3146486SUNBURY
Solar/Wind Harmer
0.172
3146486SUNBURY
Solar/Wind Harmer
0.172
316321Z2-027
Solar/Wind Harmer
0.032
3146396TANGLEW
Solar/Wind Harmer
0.473
3145176PASQUOTANK
Solar/Wind Harmer
0.106
970085AG2-068 GEN
Solar/Wind Harmer
9.004
970581AG2-369 GEN
Solar/Wind Harmer
7.744
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.166
3130156CHOWAN
Solar/Wind Harmer
0.166
315976AC1-164 GENA
Solar/Wind Harmer
17.177
316169AC1-164_GENC
Solar/Wind Harmer
14.839
315975AC1-164 GENB
Solar/Wind Harmer
0.508
316312AB1-027
Solar/Wind Harmer
0.296
3138283WHITEMARSH
Solar/Wind Harmer
0.038
971167AH1-042 GEN
Solar/Wind Harmer
14.667
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315816AE2-034 GEN
Solar/Wind Harmer
0.7
3143873LANEXA
Solar/Wind Harmer
0.097
3130546PLYMOUTH
Solar/Wind Harmer
0.161
970189AG2-124 GEN
Solar/Wind Harmer
4.756
316314AB2-024 C
Solar/Wind Harmer
0.001
965291AG1-394 GEN
Solar/Wind Harmer
0.712
315732AD1-074 GEN1
Solar/Wind Harmer
0.921
315733AD1-074 GEN2
Solar/Wind Harmer
0.921
315735AD1-075 GEN1
Solar/Wind Harmer
0.461
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.429
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
970601AG2-382 GEN
Solar/Wind Harmer
5.933
972189AH1-679 GEN
Adder
2.633
3141913WHIT STONE
Solar/Wind Harmer
0.157
3145513AHOSKIE
Solar/Wind Harmer
0.328
3145513AHOSKIE
Solar/Wind Harmer
0.157
3146043SEABORD
Solar/Wind Harmer
0.156
316087AB2-174 GEN
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
0.047
315607AA1-063A GEN
Solar/Wind Harmer
0.319
3145683EARLEYS
Solar/Wind Harmer
0.312
3145683EARLEYS
Solar/Wind Harmer
0.156
3145683EARLEYS
Solar/Wind Harmer
0.156
3141783LANCAST
Solar/Wind Harmer
0.093
3141783LANCAST
Solar/Wind Harmer
0.062
315652AC1-086 GEN
Solar/Wind Harmer
17.007
3137643SOCKMAN
Solar/Wind Harmer
0.617
3145796HORNRTN
Solar/Wind Harmer
0.487
3145796HORNRTN
Solar/Wind Harmer
0.061
962981AG1-147 GEN
Solar/Wind Harmer
5.679
3146033SCOT NK
Solar/Wind Harmer
0.602
970327AG2-215 GEN
Solar/Wind Harmer
4.937
970831AG2-522 GEN
Solar/Wind Harmer
6.34
316005AA1-067
Solar/Wind Harmer
0.155
3145746EVERETS
Solar/Wind Harmer
0.575
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
970181AG2-120 GEN
Solar/Wind Harmer
1.799
971443AH1-215 GEN
Solar/Wind Harmer
2.423
3144303KENBRDG
Solar/Wind Harmer
0.115
970683AG2-441 GEN
Solar/Wind Harmer
9.607
970681AG2-440 GEN
Solar/Wind Harmer
7.685
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
946301AF1-294 GEN
Solar/Wind Harmer
2.841
961791AG1-021 GEN
Solar/Wind Harmer
1.382
315657AE1-056 GEN
Solar/Wind Harmer
4.964
3141813NORNECK
Solar/Wind Harmer
0.143
957861AF2-080 GEN
Solar/Wind Harmer
6.144
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.141
3145573BETHELC
Solar/Wind Harmer
0.141
970285AG2-188 GEN
Solar/Wind Harmer
11.015
971845AH1-439 GEN
Solar/Wind Harmer
6.271
3150411LDYSMT5
Adder
18.158
3150381LDYSMT2
Adder
17.377
972213AH1-691 GEN
Adder
2.94
972215AH1-692 GEN
Adder
2.94
3147346CASHSCORNER
Solar/Wind Harmer
0.311
316118AC1-105 GEN
Solar/Wind Harmer
0.346
3147173SINAI
Solar/Wind Harmer
0.131
3147243WELCO
Solar/Wind Harmer
0.082
972205AH1-687 GEN
Adder
5.595
316223AC1-118
Solar/Wind Harmer
0.091
971447AH1-217 GEN
Solar/Wind Harmer
3.599
970865AG2-541 GEN
Solar/Wind Harmer
4.024
LAGNLTFEXP_LAGN->PJM
CLTF
5.963
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.52
TVALTFEXP_TVA->PJM
CLTF
3.02
CPLELTFEXP_CPLE->PJM
CLTF
9
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.817
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.186
MECLTFEXP_MEC->PJM
CLTF
2.509
SIGELTFEXP_SIGE->PJM
CLTF
0.076
NYPJM->LTFIMP_NY
CLTF
2.547
LGEELTFEXP_LGEE->PJM
CLTF
0.9
WECLTFEXP_WEC->PJM
CLTF
0.426

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:124.66 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4911.8
MW Contribution:27.83
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.711
971285AH1-108 GEN
50/50
1.495
315244AE2-183_ST
50/50
5.281
316164AC1-076 GEN
Solar/Wind Harmer
3.466
3147346CASHSCORNER
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.601
971281AH1-106 GEN
Solar/Wind Harmer
3.628
971283AH1-107 GEN
Solar/Wind Harmer
3.628
941031AE2-094 GEN
Solar/Wind Harmer
39.963
944011AF1-069 GEN
Solar/Wind Harmer
12.522
970673AG2-436 GEN
Solar/Wind Harmer
44.026
970673AG2-436 GEN
Solar/Wind Harmer
22.292
3143316POE
Solar/Wind Harmer
-0.082
3152261N ANNA2
50/50
17.342
3151771S ANNAG1
50/50
0.915
3151801S ANNAS2
50/50
0.47
3151761LOISA E
50/50
36.194
972183AH1-676 GEN
50/50
289.654
3150861SPRUNCD
50/50
0.914
3151031BRUNSWICKG2
50/50
2.407
316044AC1-158 PL1
Solar/Wind Harmer
6.731
316450AC1-158 RIC
Solar/Wind Harmer
1.795
316170AC1-121 GEN2
Solar/Wind Harmer
1.027
3147666LOUISA
Solar/Wind Harmer
-0.078
3132273ORANGE
Solar/Wind Harmer
-0.007
316313AB2-026
Solar/Wind Harmer
0.567
316258AE1-075 C
Solar/Wind Harmer
0.51
316405AF2-144 C
Solar/Wind Harmer
0.538
3143336POWHATN
Solar/Wind Harmer
2.119
315773AC2-141 GEN
Solar/Wind Harmer
8.631
315839AE2-212 C
Solar/Wind Harmer
0.619
944581AF1-123 GEN
Solar/Wind Harmer
93.163
944601AF1-125 GEN
Solar/Wind Harmer
91.709
315813AE1-149 C
Solar/Wind Harmer
12.797
3151101ELIZAR3
Adder
16.875
965281AG1-393 GEN
Solar/Wind Harmer
2.551
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
1.92
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.307
970661AG2-428 GEN
Solar/Wind Harmer
3.828
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.467
3151221GRAVEL6
Adder
13.054
3151171GRAVELC
Adder
2.512
961611AG1-000B GEN
Solar/Wind Harmer
4.246
315778AD1-151 GEN
Solar/Wind Harmer
17.454
970129AG2-093 GEN
Solar/Wind Harmer
11.34
970133AG2-095 GEN
Solar/Wind Harmer
2.265
3143096IRON208
Adder
0.749
3143096IRON208
Adder
0.734
316320Y1-086
Solar/Wind Harmer
1.176
316435W1029_GEN3
Solar/Wind Harmer
3.602
3144216WINCHST
Adder
0.666
3146516WINFALL
Solar/Wind Harmer
-0.02
3150921YORKTN3
Adder
4.43
970917AG2-570 GEN
Solar/Wind Harmer
49.496
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.006
316382AG1-145 C
Solar/Wind Harmer
0.591
970293AG2-193 GEN
Solar/Wind Harmer
2.436
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.934
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
315614AA2-178 GEN
Solar/Wind Harmer
2.053
316365GEN2_N
Solar/Wind Harmer
1.275
3156081AA2-088 GEN
Solar/Wind Harmer
6.102
971157AH1-035 GEN
Solar/Wind Harmer
2.344
315737AD1-076 GEN
Solar/Wind Harmer
3.555
3141843SHACKLE
Adder
0.846
316203AE2-005 GEN
Solar/Wind Harmer
7.84
3145893MURPHYS
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.018
316280AD1-041 GEN
Solar/Wind Harmer
1.397
3141766HARMONY
Solar/Wind Harmer
1.65
957521AF2-046 GEN
Solar/Wind Harmer
14.595
961681AG1-008 GEN
Solar/Wind Harmer
14.595
966621AG1-532 GEN
Solar/Wind Harmer
0.376
316156AD2-030 GEN
Solar/Wind Harmer
0.493
3141873WAN 176
Solar/Wind Harmer
2.193
316473AC1-191 GEN
Solar/Wind Harmer
1.984
3146173TUNIS
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.593
316486AD2-202 GEN
Solar/Wind Harmer
0.467
3156021HOLLOMANSOL
Solar/Wind Harmer
2.471
316463AE2-346 GEN
Solar/Wind Harmer
0.297
316140AB2-099
Solar/Wind Harmer
0.124
962331AG1-082 GEN
Solar/Wind Harmer
2.291
970909AG2-566 GEN
Solar/Wind Harmer
1.74
313506AB2-031 GEN
Solar/Wind Harmer
1.47
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.846
3145823KELFORD
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.018
3144293JTRSVLE
Adder
0.498
3150351NORNECKC2
Adder
1.488
3150401LDYSMT4
Adder
18.261
3150371LDYSMT1
Adder
17.645
942461AE2-259 GEN
Solar/Wind Harmer
0.234
3152251N ANNA1
50/50
17.343
971507AH1-251 GEN
50/50
12.192
3151791S ANNAG2
50/50
0.915
3151781S ANNAS1
50/50
0.47
3151741LOISA C
50/50
0.971
3151751LOISA D
50/50
17.753
970119AG2-088 GEN
50/50
27.833
3150851SPRUNCC
50/50
0.914
315243AE2-183_GT3
50/50
3.054
3151051BRUNSWICKS1
50/50
4.996
3151021BRUNSWICKG1
50/50
2.407
316045AC1-158 PL2
Solar/Wind Harmer
21.532
316254AC1-120 GEN1
Solar/Wind Harmer
3.082
3147666LOUISA
Solar/Wind Harmer
-0.136
316192AB2-158 GEN
Solar/Wind Harmer
4.034
315683AE1-153 C
Solar/Wind Harmer
26.707
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.116
940641AE2-051 GEN
Solar/Wind Harmer
20.412
939411AE1-173 GEN
Solar/Wind Harmer
107.132
3143336POWHATN
Solar/Wind Harmer
2.493
316294AC1-161 GEN
Solar/Wind Harmer
6.674
944591AF1-124 GEN
Solar/Wind Harmer
93.498
316375AC2-012 GEN
Solar/Wind Harmer
7.063
3150981CHESPKA
Adder
2.268
970659AG2-427 GEN
Solar/Wind Harmer
10.833
316381AD1-082 GEN
Solar/Wind Harmer
1.869
316336AC2-165 C
Solar/Wind Harmer
3.539
315671AE2-027_GEN
Solar/Wind Harmer
15.27
3142543TWELFTH
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
21.6
316388AE2-253 GEN
Solar/Wind Harmer
1.368
3145336SMITFLD
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.409
3151171GRAVELC
Adder
1.91
316072AD1-144
Solar/Wind Harmer
0.408
961611AG1-000B GEN
Solar/Wind Harmer
9.952
971647AH1-324 GEN
Solar/Wind Harmer
10.079
971069AG2-661 GEN
Solar/Wind Harmer
3.188
316458AB2-190 GEN2
Solar/Wind Harmer
2.037
970129AG2-093 GEN
Solar/Wind Harmer
4.593
316093AE2-104_GEN
Solar/Wind Harmer
5.849
3143096IRON208
Adder
0.749
3138126ROCKLANDING
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
-0.064
3146516WINFALL
Solar/Wind Harmer
-0.02
944631AF1-128 GEN
Adder
84.115
970919AG2-571 GEN
Solar/Wind Harmer
6.265
970087AG2-069 GEN
Solar/Wind Harmer
18.484
316159AE1-175 C
Solar/Wind Harmer
0.526
971317AH1-138 GEN
Solar/Wind Harmer
2.451
315800Z1-036_GEN1
Solar/Wind Harmer
4.839
3130156CHOWAN
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
957481AF2-042 GEN
Solar/Wind Harmer
59.695
3142433PROV 92
Solar/Wind Harmer
-0.076
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
3145663CRESWEL
Solar/Wind Harmer
-0.053
971163AH1-040 GEN
Solar/Wind Harmer
17.838
316023GEN1_S
Solar/Wind Harmer
1.275
315693AD1-088 GEN
Solar/Wind Harmer
9.429
962491AG1-098 GEN
Solar/Wind Harmer
12.593
970937AG2-583 GEN
Solar/Wind Harmer
13.457
971777AH1-397 GEN
Solar/Wind Harmer
2.187
3141843SHACKLE
Adder
0.846
3145893MURPHYS
Solar/Wind Harmer
-0.074
3145893MURPHYS
Solar/Wind Harmer
0.551
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.639
3141766HARMONY
Solar/Wind Harmer
-0.004
960081AF2-299 GEN
Solar/Wind Harmer
2.084
3146173TUNIS
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.698
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.461
3138133OCRAN
Solar/Wind Harmer
-0.011
316011AB1-132 GEN
Solar/Wind Harmer
3.788
962571AG1-106 GEN
Solar/Wind Harmer
2.602
316190AA2-174 GEN
Solar/Wind Harmer
0.222
3145823KELFORD
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.059
3145796HORNRTN
Solar/Wind Harmer
-0.018
316174AB2-169 GEN
Solar/Wind Harmer
2.743
3144293JTRSVLE
Adder
0.498
3150351NORNECKC2
Adder
1.463
972197AH1-683 GEN
Adder
2.852
972219AH1-694 GEN
Adder
2.053
316006AB2-029 C
Solar/Wind Helper
0.152
971967AH1-528 GEN
Solar/Wind Harmer
38.978
3151081ELIZAR1
Adder
16.662
3151091ELIZAR2
Adder
16.373
3152611GOSPORTB
Adder
2.313
3152621GOSPORTC
Adder
1.963
3152601GOSPORTA
Adder
1.811
316315AB2-025 C
Solar/Wind Harmer
0.55
315814AE2-033 C
Solar/Wind Harmer
18.917
957871AF2-081 GEN
Solar/Wind Harmer
10.138
971445AH1-216 GEN
Solar/Wind Harmer
12.537
319010AE1-072 C
Solar/Wind Harmer
4.091
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.84
316349AD2-085 GEN
Solar/Wind Harmer
1.798
316311AC2-079 GEN
Solar/Wind Harmer
10.195
316305AF2-043 C
Solar/Wind Harmer
0.609
972265AH1-717 GEN
Adder
13.942
3151201GRAVEL4
Adder
13.069
3151191GRAVEL3
Adder
12.904
3151211GRAVEL5
Adder
12.904
316369SG1_INVT
Solar/Wind Harmer
3.601
316132AB2-190 GEN1
Solar/Wind Harmer
2.037
315835AF2-110_GEN
Solar/Wind Harmer
2.515
313526AB2-022
Solar/Wind Harmer
0.541
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.539
3146396TANGLEW
Solar/Wind Harmer
0.368
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.323
970581AG2-369 GEN
Solar/Wind Harmer
10.597
315611Z1-036_GEN2
Solar/Wind Harmer
4.839
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
20.303
316169AC1-164_GENC
Solar/Wind Harmer
17.54
315975AC1-164 GENB
Solar/Wind Harmer
0.601
316312AB1-027
Solar/Wind Harmer
0.647
957831AF2-077 GEN
Solar/Wind Harmer
0.576
3138283WHITEMARSH
Solar/Wind Harmer
0.03
971167AH1-042 GEN
Solar/Wind Harmer
18.438
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
315816AE2-034 GEN
Solar/Wind Harmer
1.54
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
965291AG1-394 GEN
Solar/Wind Harmer
1.663
315732AD1-074 GEN1
Solar/Wind Harmer
3.783
315733AD1-074 GEN2
Solar/Wind Harmer
3.783
315735AD1-075 GEN1
Solar/Wind Harmer
1.892
316314AB2-024 C
Solar/Wind Harmer
1.588
316318V4-068
Solar/Wind Harmer
0.463
3145893MURPHYS
Solar/Wind Harmer
-0.05
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
8.117
315662AE1-191 GEN
Solar/Wind Harmer
2.236
315666AE1-190 GEN
Solar/Wind Harmer
0.559
316059AD1-063 C
Solar/Wind Harmer
0.419
946281AF1-292 GEN
Solar/Wind Harmer
0.415
957601AF2-054 GEN
Solar/Wind Harmer
0.553
3141873WAN 176
Solar/Wind Harmer
-0.004
316087AB2-174 GEN
Solar/Wind Harmer
2.619
3146043SEABORD
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.16
961941AG1-037 GEN
Solar/Wind Harmer
0.138
3145513AHOSKIE
Solar/Wind Harmer
-0.018
315607AA1-063A GEN
Solar/Wind Harmer
1.849
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.072
972189AH1-679 GEN
Adder
2.703
3138133OCRAN
Solar/Wind Harmer
-0.005
315652AC1-086 GEN
Solar/Wind Harmer
20.367
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
Adder
6.589
3150411LDYSMT5
Adder
18.318
3150381LDYSMT2
Adder
17.531
972213AH1-691 GEN
Adder
2.966
972215AH1-692 GEN
Adder
2.966
971133AH1-012 GEN
50/50
5.76
3151731LOISA B
50/50
17.753
3151721LOISA A
50/50
17.662
970533AG2-339 GEN
50/50
16.862
970531AG2-338 GEN
50/50
6.745
315242AE2-183_GT2
50/50
3.054
315241AE2-183_GT1
50/50
3.036
972185AH1-677 GEN
50/50
11.011
3151041BRUNSWICKG3
50/50
2.407
972187AH1-678 GEN
50/50
5.524
316447AC1-158 HLD
Solar/Wind Harmer
14.802
315651AD1-115 GEN
Solar/Wind Harmer
16.777
966001AG1-469 GEN
Solar/Wind Harmer
0.563
971223AH1-071 GEN
Solar/Wind Harmer
2.932
3143526WINTERP
Solar/Wind Harmer
-0.116
316036AC1-147 C
Solar/Wind Harmer
0.551
3150991CHESPKB
Adder
1.903
3150991CHESPKB
Adder
1.857
3142956BIRDNECK
Solar/Wind Harmer
1.094
316316AC1-027 C
Solar/Wind Harmer
0.626
3144356SAPONY
Solar/Wind Harmer
0.711
316185AD1-033 GEN
Solar/Wind Harmer
2.151
316240AF1-291 C
Solar/Wind Harmer
0.614
970657AG2-426 GEN
Solar/Wind Harmer
6.362
970657AG2-426 GEN
Solar/Wind Harmer
1.33
3145506HICKORY
Solar/Wind Harmer
-0.081
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
944641AF1-129 GEN
Adder
86.27
316339AD2-160 GEN
Solar/Wind Harmer
1.368
970933AG2-581 GEN
Solar/Wind Harmer
19.018
316018AA1-139 ULT2
Solar/Wind Harmer
1.737
316017AA1-139 ULT1
Solar/Wind Harmer
1.641
316236AE1-162_GEN
Solar/Wind Harmer
0.611
3137176SLIGO L2192
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.39
3130086AYDLETT
Solar/Wind Harmer
-0.08
316033AB2-134 GEN
Solar/Wind Harmer
6.499
315697AD1-025 GEN
Solar/Wind Harmer
4.076
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.602
316433W1029_GEN2
Solar/Wind Harmer
3.602
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.574
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3150691DARBY 3
Adder
12.588
3150701DARBY 4
Adder
12.559
3150681DARBY 2
Adder
12.544
3150671DARBY 1
Adder
12.529
3142946ENON
Solar/Wind Harmer
-0.002
315742AE1-103 GEN
Solar/Wind Harmer
2.04
3146376EDENTON
Solar/Wind Harmer
0.575
3146376EDENTON
Solar/Wind Harmer
0.575
316075AC2-137 C
Solar/Wind Harmer
0.521
3142296MT RD221
Adder
0.545
970099AG2-077 GEN
Solar/Wind Harmer
23.878
316065AD1-022 GEN
Solar/Wind Harmer
9.304
316441AF1-014 GEN
Solar/Wind Harmer
1.254
3145893MURPHYS
Solar/Wind Harmer
0.518
3145893MURPHYS
Solar/Wind Harmer
-0.033
971741AH1-377 GEN
Solar/Wind Harmer
21.449
966871AG1-558 GEN
Solar/Wind Harmer
0.554
966871AG1-558 GEN
Solar/Wind Harmer
0.19
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
9.165
316181AB2-040 GEN
Solar/Wind Harmer
2.55
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.824
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
2.027
3145593CAROLNA
Solar/Wind Harmer
0.15
3145783HORNRTN
Solar/Wind Harmer
2.124
3145783HORNRTN
Solar/Wind Harmer
1.7
3145783HORNRTN
Solar/Wind Harmer
0.531
3145783HORNRTN
Solar/Wind Harmer
0.212
3145796HORNRTN
Solar/Wind Harmer
-0.053
3144293JTRSVLE
Adder
0.498
3144293JTRSVLE
Adder
0.42
3150341NORNECKC1
Adder
1.537
3150341NORNECKC1
Adder
1.525
3150391LDYSMT3
Adder
18.227
972195AH1-682 GEN
Adder
2.395
LAGNLTFEXP_LAGN->PJM
CLTF
6.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.695
TVALTFEXP_TVA->PJM
CLTF
3.275
CPLELTFEXP_CPLE->PJM
CLTF
9.48
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.839
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.781
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.081
MECLTFEXP_MEC->PJM
CLTF
2.792
SIGELTFEXP_SIGE->PJM
CLTF
0.085
NYPJM->LTFIMP_NY
CLTF
2.76
LGEELTFEXP_LGEE->PJM
CLTF
1.015
WECLTFEXP_WEC->PJM
CLTF
0.483

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:124.41 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4901.61
MW Contribution:27.83
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
17.342
3151771S ANNAG1
50/50
0.915
3151801S ANNAS2
50/50
0.47
3151761LOISA E
50/50
36.194
972183AH1-676 GEN
50/50
289.654
3150861SPRUNCD
50/50
0.914
3151031BRUNSWICKG2
50/50
2.407
316044AC1-158 PL1
Solar/Wind Harmer
6.731
316450AC1-158 RIC
Solar/Wind Harmer
1.795
316170AC1-121 GEN2
Solar/Wind Harmer
1.027
3147666LOUISA
Solar/Wind Harmer
-0.078
3132273ORANGE
Solar/Wind Harmer
-0.007
316313AB2-026
Solar/Wind Harmer
0.567
316258AE1-075 C
Solar/Wind Harmer
0.51
316405AF2-144 C
Solar/Wind Harmer
0.538
3143336POWHATN
Solar/Wind Harmer
2.119
315773AC2-141 GEN
Solar/Wind Harmer
8.631
315839AE2-212 C
Solar/Wind Harmer
0.619
944581AF1-123 GEN
Solar/Wind Harmer
93.163
944601AF1-125 GEN
Solar/Wind Harmer
91.709
315813AE1-149 C
Solar/Wind Harmer
12.797
3151101ELIZAR3
Adder
16.875
965281AG1-393 GEN
Solar/Wind Harmer
2.551
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
1.92
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.307
970661AG2-428 GEN
Solar/Wind Harmer
3.828
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.467
3151221GRAVEL6
Adder
13.054
3151171GRAVELC
Adder
2.512
961611AG1-000B GEN
Solar/Wind Harmer
4.246
315778AD1-151 GEN
Solar/Wind Harmer
17.454
970129AG2-093 GEN
Solar/Wind Harmer
11.34
970133AG2-095 GEN
Solar/Wind Harmer
2.265
3143096IRON208
Adder
0.749
3143096IRON208
Adder
0.734
316320Y1-086
Solar/Wind Harmer
1.176
316435W1029_GEN3
Solar/Wind Harmer
3.602
3144216WINCHST
Adder
0.666
3146516WINFALL
Solar/Wind Harmer
-0.02
3150921YORKTN3
Adder
4.43
970917AG2-570 GEN
Solar/Wind Harmer
49.496
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.006
316382AG1-145 C
Solar/Wind Harmer
0.591
970293AG2-193 GEN
Solar/Wind Harmer
2.436
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.934
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
315614AA2-178 GEN
Solar/Wind Harmer
2.053
316365GEN2_N
Solar/Wind Harmer
1.275
3156081AA2-088 GEN
Solar/Wind Harmer
6.102
971157AH1-035 GEN
Solar/Wind Harmer
2.344
315737AD1-076 GEN
Solar/Wind Harmer
3.555
3141843SHACKLE
Adder
0.846
316203AE2-005 GEN
Solar/Wind Harmer
7.84
3145893MURPHYS
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.018
316280AD1-041 GEN
Solar/Wind Harmer
1.397
3141766HARMONY
Solar/Wind Harmer
1.65
957521AF2-046 GEN
Solar/Wind Harmer
14.595
961681AG1-008 GEN
Solar/Wind Harmer
14.595
966621AG1-532 GEN
Solar/Wind Harmer
0.376
316156AD2-030 GEN
Solar/Wind Harmer
0.493
3141873WAN 176
Solar/Wind Harmer
2.193
316473AC1-191 GEN
Solar/Wind Harmer
1.984
3146173TUNIS
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.593
316486AD2-202 GEN
Solar/Wind Harmer
0.467
3156021HOLLOMANSOL
Solar/Wind Harmer
2.471
316463AE2-346 GEN
Solar/Wind Harmer
0.297
316140AB2-099
Solar/Wind Harmer
0.124
962331AG1-082 GEN
Solar/Wind Harmer
2.291
970909AG2-566 GEN
Solar/Wind Harmer
1.74
313506AB2-031 GEN
Solar/Wind Harmer
1.47
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.846
3145823KELFORD
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.018
942461AE2-259 GEN
Solar/Wind Harmer
2.672
3144293JTRSVLE
Adder
0.498
3150351NORNECKC2
Adder
1.488
3150401LDYSMT4
Adder
18.261
3150371LDYSMT1
Adder
17.645
3152251N ANNA1
50/50
17.343
971507AH1-251 GEN
50/50
12.192
3151791S ANNAG2
50/50
0.915
3151781S ANNAS1
50/50
0.47
3151741LOISA C
50/50
0.971
3151751LOISA D
50/50
17.753
970119AG2-088 GEN
50/50
27.833
3150851SPRUNCC
50/50
0.914
315243AE2-183_GT3
50/50
3.054
3151051BRUNSWICKS1
50/50
4.996
3151021BRUNSWICKG1
50/50
2.407
316045AC1-158 PL2
Solar/Wind Harmer
21.532
316254AC1-120 GEN1
Solar/Wind Harmer
3.082
3147666LOUISA
Solar/Wind Harmer
-0.136
316192AB2-158 GEN
Solar/Wind Harmer
4.034
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.116
940641AE2-051 GEN
Solar/Wind Harmer
20.412
939411AE1-173 GEN
Solar/Wind Harmer
107.132
3143336POWHATN
Solar/Wind Harmer
2.493
316294AC1-161 GEN
Solar/Wind Harmer
6.674
944591AF1-124 GEN
Solar/Wind Harmer
93.498
316375AC2-012 GEN
Solar/Wind Harmer
7.063
3150981CHESPKA
Adder
2.268
970659AG2-427 GEN
Solar/Wind Harmer
10.833
316381AD1-082 GEN
Solar/Wind Harmer
1.869
316336AC2-165 C
Solar/Wind Harmer
3.539
315671AE2-027_GEN
Solar/Wind Harmer
15.27
3142543TWELFTH
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
21.6
316388AE2-253 GEN
Solar/Wind Harmer
1.368
3145336SMITFLD
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.409
3151171GRAVELC
Adder
1.91
316072AD1-144
Solar/Wind Harmer
0.408
961611AG1-000B GEN
Solar/Wind Harmer
9.952
971647AH1-324 GEN
Solar/Wind Harmer
10.079
971069AG2-661 GEN
Solar/Wind Harmer
3.188
316458AB2-190 GEN2
Solar/Wind Harmer
2.037
970129AG2-093 GEN
Solar/Wind Harmer
4.593
316093AE2-104_GEN
Solar/Wind Harmer
5.849
3143096IRON208
Adder
0.749
3138126ROCKLANDING
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
-0.064
3146516WINFALL
Solar/Wind Harmer
-0.02
944631AF1-128 GEN
Adder
84.115
970919AG2-571 GEN
Solar/Wind Harmer
6.265
970087AG2-069 GEN
Solar/Wind Harmer
18.484
316159AE1-175 C
Solar/Wind Harmer
0.526
971317AH1-138 GEN
Solar/Wind Harmer
2.451
315800Z1-036_GEN1
Solar/Wind Harmer
4.839
3130156CHOWAN
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
957481AF2-042 GEN
Solar/Wind Harmer
59.695
3142433PROV 92
Solar/Wind Harmer
-0.076
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
3145663CRESWEL
Solar/Wind Harmer
-0.053
971163AH1-040 GEN
Solar/Wind Harmer
17.838
316023GEN1_S
Solar/Wind Harmer
1.275
315693AD1-088 GEN
Solar/Wind Harmer
9.429
962491AG1-098 GEN
Solar/Wind Harmer
12.593
970937AG2-583 GEN
Solar/Wind Harmer
13.457
971777AH1-397 GEN
Solar/Wind Harmer
2.187
3141843SHACKLE
Adder
0.846
3145893MURPHYS
Solar/Wind Harmer
-0.074
3145893MURPHYS
Solar/Wind Harmer
0.551
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.639
3141766HARMONY
Solar/Wind Harmer
-0.004
960081AF2-299 GEN
Solar/Wind Harmer
2.084
3146173TUNIS
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.698
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.461
3138133OCRAN
Solar/Wind Harmer
-0.011
316011AB1-132 GEN
Solar/Wind Harmer
3.788
962571AG1-106 GEN
Solar/Wind Harmer
2.602
316190AA2-174 GEN
Solar/Wind Harmer
0.222
3145823KELFORD
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.059
3145796HORNRTN
Solar/Wind Harmer
-0.018
316174AB2-169 GEN
Solar/Wind Harmer
2.743
3144293JTRSVLE
Adder
0.498
3150351NORNECKC2
Adder
1.463
972197AH1-683 GEN
Adder
2.852
972219AH1-694 GEN
Adder
2.053
316006AB2-029 C
Solar/Wind Helper
0.152
316303AF2-085
50/50
3.711
971285AH1-108 GEN
50/50
1.495
315244AE2-183_ST
50/50
5.281
316164AC1-076 GEN
Solar/Wind Harmer
3.466
3147346CASHSCORNER
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.601
971281AH1-106 GEN
Solar/Wind Harmer
3.628
971283AH1-107 GEN
Solar/Wind Harmer
3.628
941031AE2-094 GEN
Solar/Wind Harmer
39.963
944011AF1-069 GEN
Solar/Wind Harmer
12.522
970673AG2-436 GEN
Solar/Wind Harmer
44.026
970673AG2-436 GEN
Solar/Wind Harmer
22.292
3143316POE
Solar/Wind Harmer
-0.082
971967AH1-528 GEN
Solar/Wind Harmer
38.978
3151081ELIZAR1
Adder
16.662
3151091ELIZAR2
Adder
16.373
3152611GOSPORTB
Adder
2.313
3152621GOSPORTC
Adder
1.963
3152601GOSPORTA
Adder
1.811
316315AB2-025 C
Solar/Wind Harmer
0.55
315814AE2-033 C
Solar/Wind Harmer
18.917
957871AF2-081 GEN
Solar/Wind Harmer
10.138
971445AH1-216 GEN
Solar/Wind Harmer
12.537
319010AE1-072 C
Solar/Wind Harmer
4.091
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.84
316349AD2-085 GEN
Solar/Wind Harmer
1.798
316311AC2-079 GEN
Solar/Wind Harmer
10.195
316305AF2-043 C
Solar/Wind Harmer
0.609
972265AH1-717 GEN
Adder
13.942
3151201GRAVEL4
Adder
13.069
3151191GRAVEL3
Adder
12.904
3151211GRAVEL5
Adder
12.904
316369SG1_INVT
Solar/Wind Harmer
3.601
316132AB2-190 GEN1
Solar/Wind Harmer
2.037
315835AF2-110_GEN
Solar/Wind Harmer
2.515
313526AB2-022
Solar/Wind Harmer
0.541
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.539
3146396TANGLEW
Solar/Wind Harmer
0.368
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.323
970581AG2-369 GEN
Solar/Wind Harmer
10.597
315611Z1-036_GEN2
Solar/Wind Harmer
4.839
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
20.303
316169AC1-164_GENC
Solar/Wind Harmer
17.54
315975AC1-164 GENB
Solar/Wind Harmer
0.601
316312AB1-027
Solar/Wind Harmer
0.647
957831AF2-077 GEN
Solar/Wind Harmer
0.576
3138283WHITEMARSH
Solar/Wind Harmer
0.03
971167AH1-042 GEN
Solar/Wind Harmer
18.438
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
315816AE2-034 GEN
Solar/Wind Harmer
1.54
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
965291AG1-394 GEN
Solar/Wind Harmer
1.663
315732AD1-074 GEN1
Solar/Wind Harmer
3.783
315733AD1-074 GEN2
Solar/Wind Harmer
3.783
315735AD1-075 GEN1
Solar/Wind Harmer
1.892
316314AB2-024 C
Solar/Wind Harmer
1.588
316318V4-068
Solar/Wind Harmer
0.463
3145893MURPHYS
Solar/Wind Harmer
-0.05
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
8.117
315662AE1-191 GEN
Solar/Wind Harmer
2.236
315666AE1-190 GEN
Solar/Wind Harmer
0.559
316059AD1-063 C
Solar/Wind Harmer
0.419
946281AF1-292 GEN
Solar/Wind Harmer
0.415
957601AF2-054 GEN
Solar/Wind Harmer
0.553
3141873WAN 176
Solar/Wind Harmer
-0.004
316087AB2-174 GEN
Solar/Wind Harmer
2.619
3146043SEABORD
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.16
961941AG1-037 GEN
Solar/Wind Harmer
0.138
3145513AHOSKIE
Solar/Wind Harmer
-0.018
315607AA1-063A GEN
Solar/Wind Harmer
1.849
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.072
972189AH1-679 GEN
Adder
2.703
3138133OCRAN
Solar/Wind Harmer
-0.005
315652AC1-086 GEN
Solar/Wind Harmer
20.367
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
Adder
6.589
3150411LDYSMT5
Adder
18.318
3150381LDYSMT2
Adder
17.531
972213AH1-691 GEN
Adder
2.966
972215AH1-692 GEN
Adder
2.966
970285AG2-188 GEN
Solar/Wind Harmer
14.082
971133AH1-012 GEN
50/50
5.76
3151731LOISA B
50/50
17.753
3151721LOISA A
50/50
17.662
970533AG2-339 GEN
50/50
16.862
970531AG2-338 GEN
50/50
6.745
315242AE2-183_GT2
50/50
3.054
315241AE2-183_GT1
50/50
3.036
972185AH1-677 GEN
50/50
11.011
3151041BRUNSWICKG3
50/50
2.407
972187AH1-678 GEN
50/50
5.524
316447AC1-158 HLD
Solar/Wind Harmer
14.802
315651AD1-115 GEN
Solar/Wind Harmer
16.777
966001AG1-469 GEN
Solar/Wind Harmer
0.563
971223AH1-071 GEN
Solar/Wind Harmer
2.932
3143526WINTERP
Solar/Wind Harmer
-0.116
316036AC1-147 C
Solar/Wind Harmer
0.551
3150991CHESPKB
Adder
1.903
3150991CHESPKB
Adder
1.857
3142956BIRDNECK
Solar/Wind Harmer
1.094
316316AC1-027 C
Solar/Wind Harmer
0.626
3144356SAPONY
Solar/Wind Harmer
0.711
316185AD1-033 GEN
Solar/Wind Harmer
2.151
316240AF1-291 C
Solar/Wind Harmer
0.614
970657AG2-426 GEN
Solar/Wind Harmer
6.362
970657AG2-426 GEN
Solar/Wind Harmer
1.33
3145506HICKORY
Solar/Wind Harmer
-0.081
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
944641AF1-129 GEN
Adder
86.27
316339AD2-160 GEN
Solar/Wind Harmer
1.368
970933AG2-581 GEN
Solar/Wind Harmer
19.018
316018AA1-139 ULT2
Solar/Wind Harmer
1.737
316017AA1-139 ULT1
Solar/Wind Harmer
1.641
316236AE1-162_GEN
Solar/Wind Harmer
0.611
3137176SLIGO L2192
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.39
3130086AYDLETT
Solar/Wind Harmer
-0.08
316033AB2-134 GEN
Solar/Wind Harmer
6.499
315697AD1-025 GEN
Solar/Wind Harmer
4.076
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.602
316433W1029_GEN2
Solar/Wind Harmer
3.602
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.574
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3150691DARBY 3
Adder
12.588
3150701DARBY 4
Adder
12.559
3150681DARBY 2
Adder
12.544
3150671DARBY 1
Adder
12.529
3142946ENON
Solar/Wind Harmer
-0.002
315742AE1-103 GEN
Solar/Wind Harmer
2.04
3146376EDENTON
Solar/Wind Harmer
0.575
3146376EDENTON
Solar/Wind Harmer
0.575
316075AC2-137 C
Solar/Wind Harmer
0.521
3142296MT RD221
Adder
0.545
970099AG2-077 GEN
Solar/Wind Harmer
23.878
316065AD1-022 GEN
Solar/Wind Harmer
9.304
316441AF1-014 GEN
Solar/Wind Harmer
1.254
3145893MURPHYS
Solar/Wind Harmer
0.518
3145893MURPHYS
Solar/Wind Harmer
-0.033
971741AH1-377 GEN
Solar/Wind Harmer
21.449
966871AG1-558 GEN
Solar/Wind Harmer
0.554
966871AG1-558 GEN
Solar/Wind Harmer
0.19
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
9.165
316181AB2-040 GEN
Solar/Wind Harmer
2.55
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.824
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
2.027
3145593CAROLNA
Solar/Wind Harmer
0.15
3145783HORNRTN
Solar/Wind Harmer
2.124
3145783HORNRTN
Solar/Wind Harmer
1.7
3145783HORNRTN
Solar/Wind Harmer
0.531
3145783HORNRTN
Solar/Wind Harmer
0.212
3145796HORNRTN
Solar/Wind Harmer
-0.053
3144293JTRSVLE
Adder
0.498
3144293JTRSVLE
Adder
0.42
3150341NORNECKC1
Adder
1.537
3150341NORNECKC1
Adder
1.525
3150391LDYSMT3
Adder
18.227
972195AH1-682 GEN
Adder
2.395
LAGNLTFEXP_LAGN->PJM
CLTF
6.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.695
TVALTFEXP_TVA->PJM
CLTF
3.275
CPLELTFEXP_CPLE->PJM
CLTF
9.48
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.839
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.781
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.081
MECLTFEXP_MEC->PJM
CLTF
2.792
SIGELTFEXP_SIGE->PJM
CLTF
0.085
NYPJM->LTFIMP_NY
CLTF
2.76
LGEELTFEXP_LGEE->PJM
CLTF
1.015
WECLTFEXP_WEC->PJM
CLTF
0.483

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.67 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4754.21
MW Contribution:27.52
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
17.235
971507AH1-251 GEN
50/50
10.732
3151791S ANNAG2
50/50
0.836
3151781S ANNAS1
50/50
0.43
3151741LOISA C
50/50
0.884
3151751LOISA D
50/50
16.164
970119AG2-088 GEN
50/50
27.523
3150851SPRUNCC
50/50
0.904
315243AE2-183_GT3
50/50
3.022
316303AF2-085
50/50
3.67
971285AH1-108 GEN
50/50
1.479
315244AE2-183_ST
50/50
5.225
316164AC1-076 GEN
Solar/Wind Harmer
2.601
3147346CASHSCORNER
Solar/Wind Harmer
0.387
316233AE1-074 FULL
Solar/Wind Harmer
0.594
971281AH1-106 GEN
Solar/Wind Harmer
3.589
971283AH1-107 GEN
Solar/Wind Harmer
3.589
941031AE2-094 GEN
Solar/Wind Harmer
39.549
944011AF1-069 GEN
Solar/Wind Harmer
12.392
970673AG2-436 GEN
Solar/Wind Harmer
43.562
970673AG2-436 GEN
Solar/Wind Harmer
22.057
3143316POE
Solar/Wind Harmer
-0.081
971967AH1-528 GEN
Solar/Wind Harmer
38.553
3151081ELIZAR1
Adder
16.492
3151091ELIZAR2
Adder
16.205
3152611GOSPORTB
Adder
2.29
3152621GOSPORTC
Adder
1.943
3152601GOSPORTA
Adder
1.792
316315AB2-025 C
Solar/Wind Harmer
0.544
315814AE2-033 C
Solar/Wind Harmer
18.717
957871AF2-081 GEN
Solar/Wind Harmer
10.033
971445AH1-216 GEN
Solar/Wind Harmer
12.409
319010AE1-072 C
Solar/Wind Harmer
4.049
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.8
316349AD2-085 GEN
Solar/Wind Harmer
1.779
316311AC2-079 GEN
Solar/Wind Harmer
10.09
316305AF2-043 C
Solar/Wind Harmer
0.603
972265AH1-717 GEN
Adder
13.799
3151201GRAVEL4
Adder
12.936
3151191GRAVEL3
Adder
12.772
3151211GRAVEL5
Adder
12.772
316369SG1_INVT
Solar/Wind Harmer
3.564
316132AB2-190 GEN1
Solar/Wind Harmer
2.016
315835AF2-110_GEN
Solar/Wind Harmer
2.489
313526AB2-022
Solar/Wind Harmer
0.536
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.533
3146396TANGLEW
Solar/Wind Harmer
0.364
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.189
970581AG2-369 GEN
Solar/Wind Harmer
10.482
315611Z1-036_GEN2
Solar/Wind Harmer
4.788
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
20.098
316169AC1-164_GENC
Solar/Wind Harmer
17.362
315975AC1-164 GENB
Solar/Wind Harmer
0.595
957831AF2-077 GEN
Solar/Wind Harmer
0.571
3138283WHITEMARSH
Solar/Wind Harmer
0.029
316312AB1-027
Solar/Wind Harmer
0.64
971167AH1-042 GEN
Solar/Wind Harmer
18.254
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
315816AE2-034 GEN
Solar/Wind Harmer
1.523
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.644
315732AD1-074 GEN1
Solar/Wind Harmer
3.741
315733AD1-074 GEN2
Solar/Wind Harmer
3.741
315735AD1-075 GEN1
Solar/Wind Harmer
1.871
316314AB2-024 C
Solar/Wind Harmer
1.573
316318V4-068
Solar/Wind Harmer
0.458
3145893MURPHYS
Solar/Wind Harmer
-0.049
3145893MURPHYS
Solar/Wind Harmer
-0.018
315662AE1-191 GEN
Solar/Wind Harmer
2.214
315666AE1-190 GEN
Solar/Wind Harmer
0.553
316059AD1-063 C
Solar/Wind Harmer
0.415
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
8.029
946281AF1-292 GEN
Solar/Wind Harmer
0.41
957601AF2-054 GEN
Solar/Wind Harmer
0.547
3141873WAN 176
Solar/Wind Harmer
-0.004
316087AB2-174 GEN
Solar/Wind Harmer
2.588
3146043SEABORD
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.158
961941AG1-037 GEN
Solar/Wind Harmer
0.136
3145513AHOSKIE
Solar/Wind Harmer
-0.018
315607AA1-063A GEN
Solar/Wind Harmer
1.827
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
972189AH1-679 GEN
Adder
2.678
3138133OCRAN
Solar/Wind Harmer
-0.005
3137643SOCKMAN
Solar/Wind Harmer
-0.071
315652AC1-086 GEN
Solar/Wind Harmer
20.135
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.069
962981AG1-147 GEN
Solar/Wind Harmer
7.624
970831AG2-522 GEN
Solar/Wind Harmer
8.659
972205AH1-687 GEN
Adder
6.375
3150411LDYSMT5
Adder
18.197
3150381LDYSMT2
Adder
17.416
972213AH1-691 GEN
Adder
2.946
972215AH1-692 GEN
Adder
2.946
3152261N ANNA2
50/50
17.234
3151771S ANNAG1
50/50
0.836
3151801S ANNAS2
50/50
0.43
3151761LOISA E
50/50
32.955
972183AH1-676 GEN
50/50
263.019
3150861SPRUNCD
50/50
0.904
3151031BRUNSWICKG2
50/50
2.381
316044AC1-158 PL1
Solar/Wind Harmer
6.712
316450AC1-158 RIC
Solar/Wind Harmer
1.79
3147666LOUISA
Solar/Wind Harmer
-0.074
3132273ORANGE
Solar/Wind Harmer
-0.005
316313AB2-026
Solar/Wind Harmer
0.556
316258AE1-075 C
Solar/Wind Harmer
0.501
316405AF2-144 C
Solar/Wind Harmer
0.528
3143336POWHATN
Solar/Wind Harmer
2.08
315773AC2-141 GEN
Solar/Wind Harmer
8.544
315839AE2-212 C
Solar/Wind Harmer
0.612
944581AF1-123 GEN
Solar/Wind Harmer
92.211
944601AF1-125 GEN
Solar/Wind Harmer
90.772
315813AE1-149 C
Solar/Wind Harmer
12.666
3151101ELIZAR3
Adder
16.703
965281AG1-393 GEN
Solar/Wind Harmer
2.525
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
1.9
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.273
970661AG2-428 GEN
Solar/Wind Harmer
3.788
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.442
3151221GRAVEL6
Adder
12.921
3151171GRAVELC
Adder
2.486
961611AG1-000B GEN
Solar/Wind Harmer
4.203
315778AD1-151 GEN
Solar/Wind Harmer
17.275
970129AG2-093 GEN
Solar/Wind Harmer
11.224
970133AG2-095 GEN
Solar/Wind Harmer
2.241
3143096IRON208
Adder
0.741
3143096IRON208
Adder
0.727
316320Y1-086
Solar/Wind Harmer
1.163
316435W1029_GEN3
Solar/Wind Harmer
3.565
3144216WINCHST
Adder
0.66
3146516WINFALL
Solar/Wind Harmer
-0.02
3150921YORKTN3
Adder
4.385
970917AG2-570 GEN
Solar/Wind Harmer
48.958
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.006
316382AG1-145 C
Solar/Wind Harmer
0.585
970293AG2-193 GEN
Solar/Wind Harmer
2.411
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.915
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
315614AA2-178 GEN
Solar/Wind Harmer
2.031
316365GEN2_N
Solar/Wind Harmer
1.26
3156081AA2-088 GEN
Solar/Wind Harmer
6.034
971157AH1-035 GEN
Solar/Wind Harmer
2.319
315737AD1-076 GEN
Solar/Wind Harmer
3.516
3141843SHACKLE
Adder
0.837
316203AE2-005 GEN
Solar/Wind Harmer
7.763
3145893MURPHYS
Solar/Wind Harmer
0.128
3145893MURPHYS
Solar/Wind Harmer
-0.018
316280AD1-041 GEN
Solar/Wind Harmer
1.384
3141766HARMONY
Solar/Wind Harmer
1.634
3146206CASHIE
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.432
961681AG1-008 GEN
Solar/Wind Harmer
14.432
966621AG1-532 GEN
Solar/Wind Harmer
0.371
316156AD2-030 GEN
Solar/Wind Harmer
0.489
3141873WAN 176
Solar/Wind Harmer
2.171
316473AC1-191 GEN
Solar/Wind Harmer
1.965
3146173TUNIS
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.572
316486AD2-202 GEN
Solar/Wind Harmer
0.46
3156021HOLLOMANSOL
Solar/Wind Harmer
2.444
316463AE2-346 GEN
Solar/Wind Harmer
0.293
316140AB2-099
Solar/Wind Harmer
0.122
962331AG1-082 GEN
Solar/Wind Harmer
2.266
313506AB2-031 GEN
Solar/Wind Harmer
1.452
316170AC1-121 GEN2
Solar/Wind Harmer
0.484
3146263WOODLND
Solar/Wind Harmer
-0.018
970909AG2-566 GEN
Solar/Wind Harmer
1.707
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
316317KELFORD C
Solar/Wind Harmer
0.837
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.01
962971AG1-146 GEN
Solar/Wind Harmer
3.267
942461AE2-259 GEN
Solar/Wind Harmer
2.615
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3144293JTRSVLE
Adder
0.489
3150351NORNECKC2
Adder
1.474
3150401LDYSMT4
Adder
18.141
3150371LDYSMT1
Adder
17.529
971193AH1-056 GEN
Solar/Wind Harmer
2.03
971133AH1-012 GEN
50/50
5.563
3151731LOISA B
50/50
16.164
3151721LOISA A
50/50
16.081
970533AG2-339 GEN
50/50
16.687
970531AG2-338 GEN
50/50
6.675
315242AE2-183_GT2
50/50
3.022
315241AE2-183_GT1
50/50
3.003
972185AH1-677 GEN
50/50
10.895
3151041BRUNSWICKG3
50/50
2.381
972187AH1-678 GEN
50/50
5.465
316447AC1-158 HLD
Solar/Wind Harmer
14.76
966001AG1-469 GEN
Solar/Wind Harmer
0.484
971223AH1-071 GEN
Solar/Wind Harmer
2.899
3143526WINTERP
Solar/Wind Harmer
-0.114
316036AC1-147 C
Solar/Wind Harmer
0.545
3150991CHESPKB
Adder
1.883
3150991CHESPKB
Adder
1.838
3142956BIRDNECK
Solar/Wind Harmer
1.083
316316AC1-027 C
Solar/Wind Harmer
0.62
316185AD1-033 GEN
Solar/Wind Harmer
2.129
3144356SAPONY
Solar/Wind Harmer
0.704
316240AF1-291 C
Solar/Wind Harmer
0.608
970657AG2-426 GEN
Solar/Wind Harmer
6.296
970657AG2-426 GEN
Solar/Wind Harmer
1.317
3145506HICKORY
Solar/Wind Harmer
-0.08
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
944641AF1-129 GEN
Adder
85.383
316339AD2-160 GEN
Solar/Wind Harmer
1.354
316018AA1-139 ULT2
Solar/Wind Harmer
1.719
316017AA1-139 ULT1
Solar/Wind Harmer
1.624
316236AE1-162_GEN
Solar/Wind Harmer
0.605
970933AG2-581 GEN
Solar/Wind Harmer
18.801
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.366
3130086AYDLETT
Solar/Wind Harmer
-0.08
316033AB2-134 GEN
Solar/Wind Harmer
6.432
315697AD1-025 GEN
Solar/Wind Harmer
4.034
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.565
316433W1029_GEN2
Solar/Wind Harmer
3.565
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.568
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3150691DARBY 3
Adder
12.459
3150701DARBY 4
Adder
12.43
3150681DARBY 2
Adder
12.416
3150671DARBY 1
Adder
12.401
3142946ENON
Solar/Wind Harmer
-0.002
315742AE1-103 GEN
Solar/Wind Harmer
2.019
3146376EDENTON
Solar/Wind Harmer
0.569
3146376EDENTON
Solar/Wind Harmer
0.569
316075AC2-137 C
Solar/Wind Harmer
0.516
3142296MT RD221
Adder
0.54
970099AG2-077 GEN
Solar/Wind Harmer
23.572
316441AF1-014 GEN
Solar/Wind Harmer
1.241
316065AD1-022 GEN
Solar/Wind Harmer
9.202
3145893MURPHYS
Solar/Wind Harmer
0.513
3145893MURPHYS
Solar/Wind Harmer
-0.033
966871AG1-558 GEN
Solar/Wind Harmer
0.549
966871AG1-558 GEN
Solar/Wind Harmer
0.188
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
971741AH1-377 GEN
Solar/Wind Harmer
21.065
316181AB2-040 GEN
Solar/Wind Harmer
2.52
3151051BRUNSWICKS1
50/50
4.943
3151021BRUNSWICKG1
50/50
2.381
316045AC1-158 PL2
Solar/Wind Harmer
21.471
3147666LOUISA
Solar/Wind Harmer
-0.13
316192AB2-158 GEN
Solar/Wind Harmer
3.833
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.114
940641AE2-051 GEN
Solar/Wind Harmer
20.206
939411AE1-173 GEN
Solar/Wind Harmer
106.047
3143336POWHATN
Solar/Wind Harmer
2.448
316294AC1-161 GEN
Solar/Wind Harmer
6.606
944591AF1-124 GEN
Solar/Wind Harmer
92.543
316375AC2-012 GEN
Solar/Wind Harmer
6.991
3150981CHESPKA
Adder
2.245
970659AG2-427 GEN
Solar/Wind Harmer
10.721
316381AD1-082 GEN
Solar/Wind Harmer
1.849
315671AE2-027_GEN
Solar/Wind Harmer
15.114
3142543TWELFTH
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
21.377
316388AE2-253 GEN
Solar/Wind Harmer
1.354
3145336SMITFLD
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.404
3151171GRAVELC
Adder
1.89
316072AD1-144
Solar/Wind Harmer
0.404
961611AG1-000B GEN
Solar/Wind Harmer
9.85
316336AC2-165 C
Solar/Wind Harmer
3.467
971647AH1-324 GEN
Solar/Wind Harmer
9.976
971069AG2-661 GEN
Solar/Wind Harmer
3.155
316458AB2-190 GEN2
Solar/Wind Harmer
2.016
970129AG2-093 GEN
Solar/Wind Harmer
4.546
316093AE2-104_GEN
Solar/Wind Harmer
5.788
3143096IRON208
Adder
0.741
3138126ROCKLANDING
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
-0.063
3146516WINFALL
Solar/Wind Harmer
-0.02
944631AF1-128 GEN
Adder
83.254
970919AG2-571 GEN
Solar/Wind Harmer
6.197
970087AG2-069 GEN
Solar/Wind Harmer
18.283
316159AE1-175 C
Solar/Wind Harmer
0.521
971317AH1-138 GEN
Solar/Wind Harmer
2.426
315800Z1-036_GEN1
Solar/Wind Harmer
4.788
3130156CHOWAN
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142433PROV 92
Solar/Wind Harmer
-0.075
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
957481AF2-042 GEN
Solar/Wind Harmer
58.931
3145663CRESWEL
Solar/Wind Harmer
-0.052
971163AH1-040 GEN
Solar/Wind Harmer
17.646
316023GEN1_S
Solar/Wind Harmer
1.26
315693AD1-088 GEN
Solar/Wind Harmer
9.296
962491AG1-098 GEN
Solar/Wind Harmer
12.413
971777AH1-397 GEN
Solar/Wind Harmer
2.165
3141843SHACKLE
Adder
0.837
3145893MURPHYS
Solar/Wind Harmer
-0.073
3145893MURPHYS
Solar/Wind Harmer
0.545
3141766HARMONY
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.588
960081AF2-299 GEN
Solar/Wind Harmer
2.059
970937AG2-583 GEN
Solar/Wind Harmer
13.101
3146173TUNIS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.527
316254AC1-120 GEN1
Solar/Wind Harmer
1.451
3146263WOODLND
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.011
3147043LAWRENC
Adder
1.442
316011AB1-132 GEN
Solar/Wind Harmer
3.745
962571AG1-106 GEN
Solar/Wind Harmer
2.573
316190AA2-174 GEN
Solar/Wind Harmer
0.219
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.018
316174AB2-169 GEN
Solar/Wind Harmer
2.712
3146926FARMVIL
Solar/Wind Harmer
-0.01
3144293JTRSVLE
Adder
0.489
3150351NORNECKC2
Adder
1.45
972197AH1-683 GEN
Adder
2.833
972219AH1-694 GEN
Adder
2.04
970301AG2-198 GEN
Solar/Wind Harmer
8.99
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.803
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
2.003
3145593CAROLNA
Solar/Wind Harmer
0.148
3145783HORNRTN
Solar/Wind Harmer
2.099
3145783HORNRTN
Solar/Wind Harmer
1.68
3145783HORNRTN
Solar/Wind Harmer
0.525
3145783HORNRTN
Solar/Wind Harmer
0.21
3145796HORNRTN
Solar/Wind Harmer
-0.053
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3144293JTRSVLE
Adder
0.489
3144293JTRSVLE
Adder
0.412
3150341NORNECKC1
Adder
1.523
3150341NORNECKC1
Adder
1.511
3150391LDYSMT3
Adder
18.107
972195AH1-682 GEN
Adder
2.379
LAGNLTFEXP_LAGN->PJM
CLTF
6.351
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.405
TVALTFEXP_TVA->PJM
CLTF
3.22
CPLELTFEXP_CPLE->PJM
CLTF
9.356
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.269
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.456
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.892
MECLTFEXP_MEC->PJM
CLTF
2.739
SIGELTFEXP_SIGE->PJM
CLTF
0.083
NYPJM->LTFIMP_NY
CLTF
2.701
LGEELTFEXP_LGEE->PJM
CLTF
0.994
WECLTFEXP_WEC->PJM
CLTF
0.473
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: WT576_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P7-1: LN 2066-282_SRT-S'
 OPEN BRANCH FROM BUS 313740 TO BUS 314322 CKT 1                /*6GENITO      230.0 - 6MDLTHAN     230.0
 OPEN BRANCH FROM BUS 313740 TO BUS 314352 CKT 1                /*6GENITO      230.0 - 6WINTERP     230.0
 OPEN BRANCH FROM BUS 314307 TO BUS 314311 CKT 1                /*6HULL282     230.0 - 6IRON282     230.0
 OPEN BRANCH FROM BUS 314307 TO BUS 314322 CKT 1                /*6HULL282     230.0 - 6MDLTHAN     230.0
 OPEN BRANCH FROM BUS 314311 TO BUS 314339 CKT 1                /*6IRON282     230.0 - 6SPRUNCE     230.0
 OPEN BRANCH FROM BUS 314339 TO BUS 315083 CKT 1                /*6SPRUNCE     230.0 - 1SPRUNCA      13.8
 OPEN BRANCH FROM BUS 314339 TO BUS 315084 CKT 1                /*6SPRUNCE     230.0 - 1SPRUNCB      13.8
 OPEN BUS 313740                                                /*6GENITO      230.0
 OPEN BUS 314307                                                /*6HULL282     230.0
 OPEN BUS 314311                                                /*6IRON282     230.0
 OPEN BUS 315083                                                /*1SPRUNCA      13.8
 OPEN BUS 315084                                                /*1SPRUNCB      13.8
 SET POSTCONTRATING 876 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
END
CONTINGENCY 'DVP_P7-1: LN 219-282_SRT-A'
 OPEN BRANCH FROM BUS 314306 TO BUS 314338 CKT 1   /*6HULL219     230.0 - 6SOUWEST     230.0
 OPEN BRANCH FROM BUS 314306 TO BUS 314352 CKT 1   /*6HULL219     230.0 - 6WINTERP     230.0
 OPEN BRANCH FROM BUS 314307 TO BUS 314311 CKT 1   /*6HULL282     230.0 - 6IRON282     230.0
 OPEN BRANCH FROM BUS 314307 TO BUS 314322 CKT 1   /*6HULL282     230.0 - 6MDLTHAN     230.0
 OPEN BRANCH FROM BUS 314311 TO BUS 314339 CKT 1   /*6IRON282     230.0 - 6SPRUNCE     230.0
 OPEN BRANCH FROM BUS 314339 TO BUS 315083 CKT 1   /*6SPRUNCE     230.0 - 1SPRUNCA      13.8
 OPEN BRANCH FROM BUS 314339 TO BUS 315084 CKT 1   /*6SPRUNCE     230.0 - 1SPRUNCB      13.8
 OPEN BUS 314306                                   /*6HULL219     230.0
 OPEN BUS 314307                                   /*6HULL282     230.0
 OPEN BUS 314311                                   /*6IRON282     230.0
 OPEN BUS 315083                                   /*1SPRUNCA      13.8
 OPEN BUS 315084                                   /*1SPRUNCB      13.8
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1   /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-S'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T574_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 574T575_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-1: G202_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 315226 CKT 1                /*8NO ANNA     500.0 - 1N ANNA2      22.0
 OPEN BUS 315226                                                /*1N ANNA2      22.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P2-2: NORTH ANNA B1_SRT-S'
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P2-2: NORTH ANNA B2_SRT-S'
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2090-256_SRT-S'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1                /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1                /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1                /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 314150 TO BUS 314212 CKT 1                /*6STJOHN      230.0 - 6FOUR RIVERS 230.0
 OPEN BRANCH FROM BUS 314197 TO BUS 315672 CKT 1                /*6LDYSMITH CT 230.0 - AE1-157 TAP  230.0
 OPEN BUS 313837                                                /*6SUMMIT      230.0
 OPEN BUS 314138                                                /*6MINE RD     230.0
 OPEN BUS 314149                                                /*3STJOHND     115.0
 OPEN BUS 314150                                                /*6STJOHN      230.0
 OPEN BUS 314154                                                /*3STJOHNS     115.0
 OPEN BUS 315672                                                /*AE1-157 TAP  230.0
 OPEN BUS 315673                                                /*AE1-157 GEN    0.6
 OPEN BUS 315803                                                /*AE1-157 MAIN 230.0
 OPEN BUS 315804                                                /*AE1-157 COL1  34.5
 OPEN BUS 315805                                                /*AE1-157 COL2  34.5
 SET POSTCONTRATING 657 BRANCH FROM BUS 313027 TO BUS 314212 CKT 1 /*6FOUR RIVER1 230.0 - 6FOUR RIVERS 230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314212 TO BUS 315610 CKT 1 /*6FOUR RIVERS 230.0 - AA1-145 MAIN 230.0
 SET PRECONTRATING 598 BRANCH FROM BUS 313027 TO BUS 314212 CKT 1 /*6FOUR RIVER1 230.0 - 6FOUR RIVERS 230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314212 TO BUS 315610 CKT 1 /*6FOUR RIVERS 230.0 - AA1-145 MAIN 230.0
END
CONTINGENCY 'DVP_P7-1: LN 2054-2135_SRT-A'
 OPEN BRANCH FROM BUS 314734 TO BUS 314758 CKT 1   /*6CASHSCORNER 230.0 - 6GORDNVL     230.0
 OPEN BRANCH FROM BUS 314734 TO BUS 314759 CKT 1   /*6CASHSCORNER 230.0 - 6HOLLYMD     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1   /*6CHARLVL     230.0 - 6PROFFIT     230.0
 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1   /*6HOLLYMD     230.0 - 6PROFFIT     230.0
 OPEN BUS 314734                                   /*6CASHSCORNER 230.0
 OPEN BUS 314772                                   /*6PROFFIT     230.0
END
CONTINGENCY 'DVP_P4-2: 57302_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314063 TO BUS 314916 CKT 1                /*6MORRSVL     230.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P4-2: 515T594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314934 TO BUS 314944 CKT 1                /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 OPEN BUS 314944                                                /*8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T573_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P4-2: 568T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1                /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 57502_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 1                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H1T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P7-1: LN 11-2199_SRT-A-1'
 OPEN BRANCH FROM BUS 313227 TO BUS 314769 CKT 1   /*3ORANGE      115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314769 CKT 1   /*3DOUBLDY     115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314776 CKT 1   /*3DOUBLDY     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314757 TO BUS 314776 CKT 1   /*3GORDNVL     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314769 TO BUS 314815 CKT 1   /*3ORANGE TAP  115.0 - 3OAK GRE     115.0
 OPEN BRANCH FROM BUS 314776 TO BUS 314884 CKT 1   /*3SOMRSET     115.0 - 3SOMRS_1     115.0
 OPEN BUS 313227                                   /*3ORANGE      115.0
 OPEN BUS 314756                                   /*3DOUBLDY     115.0
 OPEN BUS 314769                                   /*3ORANGE TAP  115.0
 OPEN BUS 314776                                   /*3SOMRSET     115.0
 OPEN BUS 314884                                   /*3SOMRS_1     115.0
END
CONTINGENCY 'DVP_P7-1: LN 11-2199_SRT-A-2'
 OPEN BRANCH FROM BUS 313227 TO BUS 314769 CKT 1   /*3ORANGE      115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314769 CKT 1   /*3DOUBLDY     115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314776 CKT 1   /*3DOUBLDY     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314757 TO BUS 314776 CKT 1   /*3GORDNVL     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314769 TO BUS 314815 CKT 1   /*3ORANGE TAP  115.0 - 3OAK GRE     115.0
 OPEN BRANCH FROM BUS 314776 TO BUS 314884 CKT 1   /*3SOMRSET     115.0 - 3SOMRS_1     115.0
 OPEN BUS 313227                                   /*3ORANGE      115.0
 OPEN BUS 314756                                   /*3DOUBLDY     115.0
 OPEN BUS 314769                                   /*3ORANGE TAP  115.0
 OPEN BUS 314776                                   /*3SOMRSET     115.0
 OPEN BUS 314884                                   /*3SOMRS_1     115.0
END
CONTINGENCY 'DVP_P4-2: 545T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1                /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H3T552_SRT-S'
 OPEN BRANCH FROM BUS 314130 TO BUS 314900 CKT 2                /*6BRISTER     230.0 - 8BRISTER     500.0
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P2-2: MORRISVILLE B1_SRT-S'
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2-2199_SRT-A-1'
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314078 TO BUS 314743 CKT 1   /*3REMNGTN     115.0 - 3BRANDY      115.0
 OPEN BRANCH FROM BUS 314743 TO BUS 316256 CKT 1   /*3BRANDY      115.0 - AC1-043 TAP  115.0
 OPEN BUS 314743                                   /*3BRANDY      115.0
END
CONTINGENCY 'DVP_P7-1: LN 2-2199_SRT-A-2'
 OPEN BRANCH FROM BUS 314078 TO BUS 314743 CKT 1   /*3REMNGTN     115.0 - 3BRANDY      115.0
 OPEN BRANCH FROM BUS 314743 TO BUS 316256 CKT 1   /*3BRANDY      115.0 - AC1-043 TAP  115.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
 OPEN BUS 314743                                   /*3BRANDY      115.0
END
CONTINGENCY 'DVP_P2-2: GERMANNA_SRT-A'
 OPEN BRANCH FROM BUS 313671 TO BUS 313679 CKT 1   /*6GERMANNA    230.0 - 6CIRRUS      230.0
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
 OPEN BUS 315678                                   /*AE1-153 TAP  230.0
 OPEN BUS 315679                                   /*AE1-153 MAIN 230.0
 OPEN BUS 315680                                   /*AE1-153 COL1  34.5
 OPEN BUS 315681                                   /*AE1-153 COL2  34.5
 OPEN BUS 315682                                   /*AE1-153 TER   13.8
 OPEN BUS 315683                                   /*AE1-153 C      0.6
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314322 to 314914 ckt 1
314765 to 314749 ckt 1
314911 to 314922 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314934 to 314916 ckt 1

Winter Peak Analysis

The New Service Request AG2-088 was evaluated as a 150.0 MW (150.0 MW Capacity) injection in the Dominion area.

AG2-088 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-088 was evaluated as a 150.0 MW injection and 150.0 MW withdrawal in the Dominion area.

AG2-088 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC118.65 %830.96B985.9216.39
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC112.18 %830.96B932.1711.18
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC118.47 %830.96B984.4116.39
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC112.0 %830.96B930.6411.18
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC111.19 %722.86B803.7513.34
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 217_SRT-L
SingleAC104.04 %722.86B752.0410.68
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC121.87 %830.96B1012.6815.14
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC117.54 %830.96B976.749.96
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC124.77 %808.4B1008.6115.14
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC120.34 %808.4B972.839.96
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC124.16 %808.4B1003.715.14
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC119.74 %808.4B967.959.96

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.65 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:985.92
MW Contribution:16.39
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.98
3147133PAMPLIN
Solar/Wind Harmer
1.894
3147133PAMPLIN
Solar/Wind Harmer
0.603
3147133PAMPLIN
Solar/Wind Harmer
0.482
3143336POWHATN
Solar/Wind Harmer
2.767
3143336POWHATN
Solar/Wind Harmer
2.352
3146776BUCKING
Solar/Wind Harmer
4.03
3146776BUCKING
Solar/Wind Harmer
0.403
3146776BUCKING
Solar/Wind Harmer
0.363
3146776BUCKING
Solar/Wind Harmer
0.326
3146926FARMVIL
Solar/Wind Harmer
0.482
3146926FARMVIL
Solar/Wind Harmer
0.482
316303AF2-085
50/50
2.185
3144303KENBRDG
Solar/Wind Harmer
0.377
315616AA1-038_C
Solar/Wind Helper
1.093
315779AE2-040
50/50
1.062
316499AE2-029_GEN
Solar/Wind Helper
0.95
315657AE1-056 GEN
Solar/Wind Harmer
7.237
315785AD2-033 C
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.029
316192AB2-158 GEN
Solar/Wind Helper
1.356
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
18.776
946301AF1-294 GEN
Solar/Wind Harmer
4.672
959311AF2-222 GEN
Solar/Wind Harmer
16.226
961791AG1-021 GEN
Solar/Wind Harmer
2.279
962491AG1-098 GEN
Solar/Wind Harmer
5.987
963041AG1-153 GEN
50/50
5.603
963171AG1-166 GEN
Solar/Wind Harmer
2.279
963181AG1-167 GEN
Solar/Wind Harmer
1.709
963191AG1-168 GEN
Solar/Wind Harmer
1.709
970119AG2-088 GEN
50/50
16.39
970257AG2-171 GEN
Solar/Wind Harmer
5.655
970285AG2-188 GEN
Solar/Wind Harmer
26.806
970301AG2-198 GEN
Solar/Wind Harmer
9.831
970323AG2-213 GEN
Solar/Wind Harmer
7.539
970413AG2-270 GEN
50/50
15.291
970531AG2-338 GEN
50/50
2.942
970533AG2-339 GEN
50/50
7.355
970535AG2-341 GEN
50/50
5.504
970681AG2-440 GEN
Solar/Wind Harmer
10.44
970683AG2-441 GEN
Solar/Wind Harmer
13.049
970685AG2-442 GEN
Solar/Wind Harmer
14.615
970909AG2-566 GEN
Solar/Wind Harmer
6.356
970937AG2-583 GEN
Solar/Wind Harmer
23.968
971193AH1-056 GEN
Solar/Wind Harmer
12.062
971563AH1-280 GEN
Solar/Wind Harmer
2.279
941591AE2-156 GEN
50/50
5.885
958211AF2-115 GEN
Solar/Wind Harmer
2.849
964241AG1-285 GEN
Solar/Wind Harmer
9.945
966001AG1-469 GEN
Solar/Wind Helper
0.309
971741AH1-377 GEN
Solar/Wind Harmer
20.67
971775AH1-396 GEN
Solar/Wind Harmer
1.131
971845AH1-439 GEN
Solar/Wind Harmer
16.834
972003AH1-546 GEN
Solar/Wind Harmer
19.314
972185AH1-677 GEN
50/50
4.982
972187AH1-678 GEN
50/50
2.54
972205AH1-687 GEN
50/50
22.082
NYPJM->LTFIMP_NY
CLTF
0.685
CPLELTFEXP_CPLE->PJM
CLTF
3.897
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.088
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.247
LAGNLTFEXP_LAGN->PJM
CLTF
1.443
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.1
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.233
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.452
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.744
MECLTFEXP_MEC->PJM
CLTF
0.086
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.518

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.18 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:932.17
MW Contribution:11.18
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.755
3147133PAMPLIN
Solar/Wind Harmer
1.703
3147133PAMPLIN
Solar/Wind Harmer
0.542
3147133PAMPLIN
Solar/Wind Harmer
0.434
3143336POWHATN
Solar/Wind Harmer
2.42
3143336POWHATN
Solar/Wind Harmer
2.057
3146776BUCKING
Solar/Wind Harmer
3.767
3146776BUCKING
Solar/Wind Harmer
0.377
3146776BUCKING
Solar/Wind Harmer
0.339
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.443
3146926FARMVIL
Solar/Wind Harmer
0.443
316303AF2-085
50/50
1.49
3144303KENBRDG
Solar/Wind Harmer
0.331
315616AA1-038_C
Solar/Wind Helper
1.713
315760AF1-028 GEN
50/50
Charging
15.615
316499AE2-029_GEN
Solar/Wind Helper
1.238
315657AE1-056 GEN
Solar/Wind Harmer
6.507
315785AD2-033 C
Solar/Wind Harmer
0
316322AB2-045
Solar/Wind Harmer
0.027
316192AB2-158 GEN
Solar/Wind Helper
1.361
942461AE2-259 GEN
Solar/Wind Harmer
0
946301AF1-294 GEN
Solar/Wind Harmer
4.18
959311AF2-222 GEN
Solar/Wind Harmer
14.287
961791AG1-021 GEN
Solar/Wind Harmer
2.039
962491AG1-098 GEN
Solar/Wind Harmer
4.897
963171AG1-166 GEN
Solar/Wind Harmer
2.039
963181AG1-167 GEN
Solar/Wind Harmer
1.529
963191AG1-168 GEN
Solar/Wind Harmer
1.529
970117AG2-086 GEN
50/50
Charging
1.26
970119AG2-088 GEN
50/50
11.178
970257AG2-171 GEN
Solar/Wind Harmer
4.962
970285AG2-188 GEN
Solar/Wind Harmer
24.963
970301AG2-198 GEN
Solar/Wind Harmer
8.766
970323AG2-213 GEN
Solar/Wind Harmer
6.616
970413AG2-270 GEN
50/50
11.997
970535AG2-341 GEN
50/50
4.562
970681AG2-440 GEN
Solar/Wind Harmer
9.261
970683AG2-441 GEN
Solar/Wind Harmer
11.576
970685AG2-442 GEN
Solar/Wind Harmer
12.965
970909AG2-566 GEN
Solar/Wind Harmer
5.668
970937AG2-583 GEN
Solar/Wind Harmer
22.266
971193AH1-056 GEN
Solar/Wind Harmer
10.845
971563AH1-280 GEN
Solar/Wind Harmer
2.039
958211AF2-115 GEN
Solar/Wind Harmer
2.549
964241AG1-285 GEN
Solar/Wind Harmer
8.546
966001AG1-469 GEN
Solar/Wind Helper
0.327
971741AH1-377 GEN
Solar/Wind Harmer
18.185
971775AH1-396 GEN
Solar/Wind Harmer
0.992
971845AH1-439 GEN
Solar/Wind Harmer
15.715
972003AH1-546 GEN
Solar/Wind Harmer
18.259
972205AH1-687 GEN
50/50
20.919
NYPJM->LTFIMP_NY
CLTF
0.687
LGEELTFEXP_LGEE->PJM
CLTF
0.301
WECLTFEXP_WEC->PJM
CLTF
0.145
CPLELTFEXP_CPLE->PJM
CLTF
3.207
LAGNLTFEXP_LAGN->PJM
CLTF
2.195
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.697
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.948
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.845
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.99
TVALTFEXP_TVA->PJM
CLTF
1.148
MECLTFEXP_MEC->PJM
CLTF
0.888
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
9.963

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.47 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:984.41
MW Contribution:16.39
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.98
3147133PAMPLIN
Solar/Wind Harmer
1.894
3147133PAMPLIN
Solar/Wind Harmer
0.603
3147133PAMPLIN
Solar/Wind Harmer
0.482
3143336POWHATN
Solar/Wind Harmer
2.767
3143336POWHATN
Solar/Wind Harmer
2.352
3146776BUCKING
Solar/Wind Harmer
4.03
3146776BUCKING
Solar/Wind Harmer
0.403
3146776BUCKING
Solar/Wind Harmer
0.363
3146776BUCKING
Solar/Wind Harmer
0.326
3146926FARMVIL
Solar/Wind Harmer
0.482
3146926FARMVIL
Solar/Wind Harmer
0.482
316303AF2-085
50/50
2.185
3144303KENBRDG
Solar/Wind Harmer
0.377
315616AA1-038_C
Solar/Wind Helper
1.093
315779AE2-040
50/50
1.062
316499AE2-029_GEN
Solar/Wind Helper
0.95
315657AE1-056 GEN
Solar/Wind Harmer
7.237
315785AD2-033 C
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.029
316192AB2-158 GEN
Solar/Wind Helper
1.356
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
18.776
946301AF1-294 GEN
Solar/Wind Harmer
4.672
959311AF2-222 GEN
Solar/Wind Harmer
16.226
961791AG1-021 GEN
Solar/Wind Harmer
2.279
962491AG1-098 GEN
Solar/Wind Harmer
5.987
963041AG1-153 GEN
50/50
5.603
963171AG1-166 GEN
Solar/Wind Harmer
2.279
963181AG1-167 GEN
Solar/Wind Harmer
1.709
963191AG1-168 GEN
Solar/Wind Harmer
1.709
970119AG2-088 GEN
50/50
16.39
970257AG2-171 GEN
Solar/Wind Harmer
5.655
970285AG2-188 GEN
Solar/Wind Harmer
26.806
970301AG2-198 GEN
Solar/Wind Harmer
9.831
970323AG2-213 GEN
Solar/Wind Harmer
7.539
970413AG2-270 GEN
50/50
15.291
970531AG2-338 GEN
50/50
2.942
970533AG2-339 GEN
50/50
7.355
970535AG2-341 GEN
50/50
5.504
970681AG2-440 GEN
Solar/Wind Harmer
10.44
970683AG2-441 GEN
Solar/Wind Harmer
13.049
970685AG2-442 GEN
Solar/Wind Harmer
14.615
970909AG2-566 GEN
Solar/Wind Harmer
6.356
970937AG2-583 GEN
Solar/Wind Harmer
23.968
971193AH1-056 GEN
Solar/Wind Harmer
12.062
971563AH1-280 GEN
Solar/Wind Harmer
2.279
941591AE2-156 GEN
50/50
5.885
958211AF2-115 GEN
Solar/Wind Harmer
2.849
964241AG1-285 GEN
Solar/Wind Harmer
9.945
966001AG1-469 GEN
Solar/Wind Helper
0.309
971741AH1-377 GEN
Solar/Wind Harmer
20.67
971775AH1-396 GEN
Solar/Wind Harmer
1.131
971845AH1-439 GEN
Solar/Wind Harmer
16.834
972003AH1-546 GEN
Solar/Wind Harmer
19.314
972185AH1-677 GEN
50/50
4.982
972187AH1-678 GEN
50/50
2.54
972205AH1-687 GEN
50/50
22.082
NYPJM->LTFIMP_NY
CLTF
0.685
CPLELTFEXP_CPLE->PJM
CLTF
3.897
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.088
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.247
LAGNLTFEXP_LAGN->PJM
CLTF
1.443
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.1
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.233
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.452
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.744
MECLTFEXP_MEC->PJM
CLTF
0.086
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.518

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.0 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:930.64
MW Contribution:11.18
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.755
3147133PAMPLIN
Solar/Wind Harmer
1.703
3147133PAMPLIN
Solar/Wind Harmer
0.542
3147133PAMPLIN
Solar/Wind Harmer
0.434
3143336POWHATN
Solar/Wind Harmer
2.42
3143336POWHATN
Solar/Wind Harmer
2.057
3146776BUCKING
Solar/Wind Harmer
3.767
3146776BUCKING
Solar/Wind Harmer
0.377
3146776BUCKING
Solar/Wind Harmer
0.339
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.443
3146926FARMVIL
Solar/Wind Harmer
0.443
316303AF2-085
50/50
1.49
3144303KENBRDG
Solar/Wind Harmer
0.331
315616AA1-038_C
Solar/Wind Helper
1.713
315760AF1-028 GEN
50/50
Charging
15.615
316499AE2-029_GEN
Solar/Wind Helper
1.238
315657AE1-056 GEN
Solar/Wind Harmer
6.507
315785AD2-033 C
Solar/Wind Harmer
0
316322AB2-045
Solar/Wind Harmer
0.027
316192AB2-158 GEN
Solar/Wind Helper
1.361
942461AE2-259 GEN
Solar/Wind Harmer
0
946301AF1-294 GEN
Solar/Wind Harmer
4.18
959311AF2-222 GEN
Solar/Wind Harmer
14.287
961791AG1-021 GEN
Solar/Wind Harmer
2.039
962491AG1-098 GEN
Solar/Wind Harmer
4.897
963171AG1-166 GEN
Solar/Wind Harmer
2.039
963181AG1-167 GEN
Solar/Wind Harmer
1.529
963191AG1-168 GEN
Solar/Wind Harmer
1.529
970117AG2-086 GEN
50/50
Charging
1.26
970119AG2-088 GEN
50/50
11.178
970257AG2-171 GEN
Solar/Wind Harmer
4.962
970285AG2-188 GEN
Solar/Wind Harmer
24.963
970301AG2-198 GEN
Solar/Wind Harmer
8.766
970323AG2-213 GEN
Solar/Wind Harmer
6.616
970413AG2-270 GEN
50/50
11.997
970535AG2-341 GEN
50/50
4.562
970681AG2-440 GEN
Solar/Wind Harmer
9.261
970683AG2-441 GEN
Solar/Wind Harmer
11.576
970685AG2-442 GEN
Solar/Wind Harmer
12.965
970909AG2-566 GEN
Solar/Wind Harmer
5.668
970937AG2-583 GEN
Solar/Wind Harmer
22.266
971193AH1-056 GEN
Solar/Wind Harmer
10.845
971563AH1-280 GEN
Solar/Wind Harmer
2.039
958211AF2-115 GEN
Solar/Wind Harmer
2.549
964241AG1-285 GEN
Solar/Wind Harmer
8.546
966001AG1-469 GEN
Solar/Wind Helper
0.327
971741AH1-377 GEN
Solar/Wind Harmer
18.185
971775AH1-396 GEN
Solar/Wind Harmer
0.992
971845AH1-439 GEN
Solar/Wind Harmer
15.715
972003AH1-546 GEN
Solar/Wind Harmer
18.259
972205AH1-687 GEN
50/50
20.919
NYPJM->LTFIMP_NY
CLTF
0.687
LGEELTFEXP_LGEE->PJM
CLTF
0.301
WECLTFEXP_WEC->PJM
CLTF
0.145
CPLELTFEXP_CPLE->PJM
CLTF
3.207
LAGNLTFEXP_LAGN->PJM
CLTF
2.195
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.697
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.948
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.845
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.99
TVALTFEXP_TVA->PJM
CLTF
1.148
MECLTFEXP_MEC->PJM
CLTF
0.888
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
9.963

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.19 %
Rating:722.86 MVA
Rating Type:B
MVA to Mitigate:803.75
MW Contribution:13.34
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.689
3143316POE
Solar/Wind Harmer
1.758
3144356SAPONY
Solar/Wind Harmer
1.204
316258AE1-075 C
Solar/Wind Helper
0.296
316303AF2-085
50/50
Charging
1.778
316336AC2-165 C
Solar/Wind Helper
1.446
316405AF2-144 C
50/50
Charging
0.67
3145336SMITFLD
Solar/Wind Harmer
0.813
3145336SMITFLD
Solar/Wind Harmer
0.081
316033AB2-134 GEN
Solar/Wind Harmer
0
315779AE2-040
50/50
1.629
315814AE2-033 C
Solar/Wind Harmer
8.863
315671AE2-027_GEN
Solar/Wind Harmer
5.491
315813AE1-149 C
Solar/Wind Harmer
7.13
315697AD1-025 GEN
Solar/Wind Harmer
0
315778AD1-151 GEN
Solar/Wind Harmer
8.057
316313AB2-026
Solar/Wind Helper
0.329
315652AC1-086 GEN
Solar/Wind Harmer
7.206
316083AB2-161 GEN
Solar/Wind Harmer
1.069
316311AC2-079 GEN
Solar/Wind Harmer
4.004
316233AE1-074 FULL
Solar/Wind Helper
0.35
944011AF1-069 GEN
Solar/Wind Harmer
2.029
944011AF1-069 GEN
Solar/Wind Harmer
2.52
944641AF1-129 GEN
50/50
137.395
960081AF2-299 GEN
Solar/Wind Harmer
0.756
963041AG1-153 GEN
50/50
4.827
970119AG2-088 GEN
50/50
Charging
13.335
970133AG2-095 GEN
Solar/Wind Harmer
1.298
970413AG2-270 GEN
50/50
7.54
970531AG2-338 GEN
50/50
2.714
970533AG2-339 GEN
50/50
6.785
970603AG2-384 GEN
50/50
14.488
970657AG2-426 GEN
Solar/Wind Harmer
3.02
970657AG2-426 GEN
Solar/Wind Harmer
2.15
970659AG2-427 GEN
Solar/Wind Harmer
5.394
970659AG2-427 GEN
Solar/Wind Harmer
3.255
970661AG2-428 GEN
Solar/Wind Harmer
9.817
970661AG2-428 GEN
Solar/Wind Harmer
5.924
971069AG2-661 GEN
Solar/Wind Harmer
5.165
971211AH1-065 GEN
50/50
2.487
971213AH1-066 GEN
50/50
1.244
971647AH1-324 GEN
Solar/Wind Harmer
4.248
941031AE2-094 GEN
Solar/Wind Harmer
6.476
941031AE2-094 GEN
Solar/Wind Harmer
7.712
941591AE2-156 GEN
50/50
5.949
965281AG1-393 GEN
Solar/Wind Harmer
1.078
972185AH1-677 GEN
50/50
4.383
972187AH1-678 GEN
50/50
2.188
972265AH1-717 GEN
50/50
7.106
NYPJM->LTFIMP_NY
CLTF
0.604
LGEELTFEXP_LGEE->PJM
CLTF
0.263
WECLTFEXP_WEC->PJM
CLTF
0.137
CPLELTFEXP_CPLE->PJM
CLTF
3.375
LAGNLTFEXP_LAGN->PJM
CLTF
2.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.674
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.052
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.475
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.888
TVALTFEXP_TVA->PJM
CLTF
1.04
MECLTFEXP_MEC->PJM
CLTF
0.825
SIGELTFEXP_SIGE->PJM
CLTF
0.024
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
8.583

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 217_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:722.86 MVA
Rating Type:B
MVA to Mitigate:752.04
MW Contribution:10.68
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Harmer
0.047
3147043LAWRENC
50/50
0.625
3147133PAMPLIN
Solar/Wind Harmer
0.087
3147133PAMPLIN
Solar/Wind Harmer
0.028
3147133PAMPLIN
Solar/Wind Harmer
0.022
3137176SLIGO L2192
Solar/Wind Harmer
0.262
3143316POE
Solar/Wind Harmer
0.935
3144356SAPONY
Solar/Wind Harmer
0.566
3145506HICKORY
Solar/Wind Harmer
0.261
3145506HICKORY
Solar/Wind Harmer
0.157
3145506HICKORY
Solar/Wind Harmer
0.039
3146386ELIZ CT
Solar/Wind Harmer
0.067
3146396TANGLEW
Solar/Wind Harmer
0.041
3138133OCRAN
Solar/Wind Harmer
0.003
3138133OCRAN
Solar/Wind Harmer
0.001
3141766HARMONY
Solar/Wind Harmer
0.005
3141766HARMONY
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.002
3141783LANCAST
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.005
3143226MDLTHAN
Solar/Wind Harmer
-0.096
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.068
3146376EDENTON
Solar/Wind Harmer
0.068
3146376EDENTON
Solar/Wind Harmer
0.068
3146456SLIGO L269
Solar/Wind Harmer
0.262
3146456SLIGO L269
Solar/Wind Harmer
0.066
3146456SLIGO L269
Solar/Wind Harmer
0.066
3146486SUNBURY
Solar/Wind Harmer
0.068
3146486SUNBURY
Solar/Wind Harmer
0.068
3146516WINFALL
Solar/Wind Harmer
0.218
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.068
3146626S HERTFORD
Solar/Wind Harmer
0.068
3146626S HERTFORD
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.044
3146843MT LREL
Solar/Wind Harmer
0.044
3146926FARMVIL
Solar/Wind Harmer
0.007
3146926FARMVIL
Solar/Wind Harmer
0.007
3147123OTTER R
Solar/Wind Harmer
0.01
3147312GRETNA
Solar/Wind Harmer
0.011
3147312GRETNA
Solar/Wind Harmer
0.003
3145663CRESWEL
Solar/Wind Harmer
0.191
316303AF2-085
50/50
Charging
1.424
316316AC1-027 C
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.068
3130156CHOWAN
Solar/Wind Harmer
0.068
3130156CHOWAN
Solar/Wind Harmer
0.068
3145336SMITFLD
Solar/Wind Harmer
0.369
3145336SMITFLD
Solar/Wind Harmer
0.037
3146802CHATHAM
Solar/Wind Harmer
0.011
3147243WELCO
Solar/Wind Harmer
0.026
3141873WAN 176
Solar/Wind Harmer
0.025
3141873WAN 176
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
-0.395
3143526WINTERP
Solar/Wind Harmer
-0.395
316033AB2-134 GEN
Solar/Wind Harmer
0
3145176PASQUOTANK
Solar/Wind Harmer
0.041
3142543TWELFTH
Solar/Wind Harmer
-0.023
3144303KENBRDG
Solar/Wind Harmer
0.03
3147173SINAI
Solar/Wind Harmer
0.041
3156081AA2-088 GEN
Solar/Wind Harmer
0
315835AF2-110_GEN
Solar/Wind Harmer
0.69
315779AE2-040
50/50
1.657
315814AE2-033 C
Solar/Wind Harmer
8.993
315671AE2-027_GEN
Solar/Wind Harmer
6.698
315813AE1-149 C
Solar/Wind Harmer
8.113
315697AD1-025 GEN
Solar/Wind Harmer
0
316473AC1-191 GEN
Solar/Wind Helper
1.201
315778AD1-151 GEN
Solar/Wind Harmer
9.319
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145746EVERETS
Solar/Wind Harmer
0.253
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3146206CASHIE
Solar/Wind Harmer
0.07
3146206CASHIE
Solar/Wind Harmer
0.07
3146206CASHIE
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
315652AC1-086 GEN
Solar/Wind Harmer
6.657
316083AB2-161 GEN
Solar/Wind Harmer
1.173
316311AC2-079 GEN
Solar/Wind Harmer
4.01
316233AE1-074 FULL
Solar/Wind Helper
0.305
316093AE2-104_GEN
Solar/Wind Harmer
1.69
3130546PLYMOUTH
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.021
3145683EARLEYS
Solar/Wind Harmer
0.144
3145683EARLEYS
Solar/Wind Harmer
0.072
3145683EARLEYS
Solar/Wind Harmer
0.072
3145683EARLEYS
Solar/Wind Harmer
0.072
3130086AYDLETT
Solar/Wind Harmer
0.264
3137643SOCKMAN
Solar/Wind Harmer
0.319
3138543CONSLDL
Solar/Wind Harmer
0.043
3142946ENON
Solar/Wind Harmer
0.011
3142946ENON
Solar/Wind Harmer
0.003
3144536CHRHLND
Solar/Wind Harmer
0.011
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145493TOT1
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3145783HORNRTN
Solar/Wind Harmer
0.301
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.03
3145796HORNRTN
Solar/Wind Harmer
0.329
3145796HORNRTN
Solar/Wind Harmer
0.272
3145796HORNRTN
Solar/Wind Harmer
0.264
3145796HORNRTN
Solar/Wind Harmer
0.247
3145796HORNRTN
Solar/Wind Harmer
0.082
3145796HORNRTN
Solar/Wind Harmer
0.082
3145796HORNRTN
Solar/Wind Harmer
0.033
3145823KELFORD
Solar/Wind Harmer
0.071
3145823KELFORD
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.3
3145893MURPHYS
Solar/Wind Harmer
0.519
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.135
3145893MURPHYS
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.075
3145933PARMELE
Solar/Wind Harmer
0.129
3145933PARMELE
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.066
3145963POPLR C
Solar/Wind Harmer
0.066
3146033SCOT NK
Solar/Wind Harmer
0.282
3146043SEABORD
Solar/Wind Harmer
0.076
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
3146233WITAKRS
Solar/Wind Harmer
0.258
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
0.044
3146263WOODLND
Solar/Wind Harmer
0.073
3146263WOODLND
Solar/Wind Harmer
0.073
3146406KITTY HAWK
Solar/Wind Harmer
0.002
316318V4-068
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
171.597
960081AF2-299 GEN
Solar/Wind Harmer
0.709
966811AG1-552 GEN
Solar/Wind Harmer
0.594
970119AG2-088 GEN
50/50
Charging
10.679
970133AG2-095 GEN
Solar/Wind Harmer
1.573
970603AG2-384 GEN
50/50
18.095
970657AG2-426 GEN
Solar/Wind Harmer
3.291
970657AG2-426 GEN
Solar/Wind Harmer
2.343
970659AG2-427 GEN
Solar/Wind Harmer
5.961
970659AG2-427 GEN
Solar/Wind Harmer
3.597
970661AG2-428 GEN
Solar/Wind Harmer
10.558
970661AG2-428 GEN
Solar/Wind Harmer
6.371
971069AG2-661 GEN
Solar/Wind Harmer
5.974
971211AH1-065 GEN
50/50
3.014
971213AH1-066 GEN
50/50
1.507
971645AH1-323 GEN
50/50
Charging
5.587
971647AH1-324 GEN
Solar/Wind Harmer
4.736
941591AE2-156 GEN
50/50
5.075
965281AG1-393 GEN
Solar/Wind Harmer
1.3
965291AG1-394 GEN
Solar/Wind Harmer
0.47
971795AH1-408 GEN
Solar/Wind Harmer
4.25
972265AH1-717 GEN
50/50
7.415
NYPJM->LTFIMP_NY
CLTF
0.476
LGEELTFEXP_LGEE->PJM
CLTF
0.143
WECLTFEXP_WEC->PJM
CLTF
0.074
CPLELTFEXP_CPLE->PJM
CLTF
2.563
LAGNLTFEXP_LAGN->PJM
CLTF
1.388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.403
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.596
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.347
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.094
TVALTFEXP_TVA->PJM
CLTF
0.713
MECLTFEXP_MEC->PJM
CLTF
0.494
SIGELTFEXP_SIGE->PJM
CLTF
0.014
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
6.528

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.87 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:1012.68
MW Contribution:15.14
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.919
3147133PAMPLIN
Solar/Wind Harmer
1.771
3147133PAMPLIN
Solar/Wind Harmer
0.564
3147133PAMPLIN
Solar/Wind Harmer
0.451
3143336POWHATN
Solar/Wind Harmer
2.572
3143336POWHATN
Solar/Wind Harmer
2.186
3146776BUCKING
Solar/Wind Harmer
3.757
3146776BUCKING
Solar/Wind Harmer
0.376
3146776BUCKING
Solar/Wind Harmer
0.338
3146776BUCKING
Solar/Wind Harmer
0.304
3146926FARMVIL
Solar/Wind Harmer
0.45
3146926FARMVIL
Solar/Wind Harmer
0.45
316303AF2-085
50/50
2.018
315616AA1-038_C
Solar/Wind Helper
1.051
315760AF1-028 GEN
50/50
Charging
11.333
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
315779AE2-040
50/50
0.984
316499AE2-029_GEN
Solar/Wind Helper
0.927
315657AE1-056 GEN
Solar/Wind Harmer
6.767
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.542
316322AB2-045
Solar/Wind Harmer
0.027
316192AB2-158 GEN
Solar/Wind Helper
1.482
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
25.205
946301AF1-294 GEN
Solar/Wind Harmer
4.371
959311AF2-222 GEN
Solar/Wind Harmer
15.206
961791AG1-021 GEN
Solar/Wind Harmer
2.132
963041AG1-153 GEN
50/50
5.221
963171AG1-166 GEN
Solar/Wind Harmer
2.132
963181AG1-167 GEN
Solar/Wind Harmer
1.599
963191AG1-168 GEN
Solar/Wind Harmer
1.599
970119AG2-088 GEN
50/50
15.136
970221AG2-151 GEN
Solar/Wind Harmer
20.807
970257AG2-171 GEN
Solar/Wind Harmer
0.174
970285AG2-188 GEN
Solar/Wind Harmer
24.994
970301AG2-198 GEN
Solar/Wind Harmer
9.178
970323AG2-213 GEN
Solar/Wind Harmer
7.068
970413AG2-270 GEN
50/50
14.358
970531AG2-338 GEN
50/50
2.734
970533AG2-339 GEN
50/50
6.834
970535AG2-341 GEN
50/50
5.181
970681AG2-440 GEN
Solar/Wind Harmer
9.775
970683AG2-441 GEN
Solar/Wind Harmer
12.219
970685AG2-442 GEN
Solar/Wind Harmer
13.686
970909AG2-566 GEN
Solar/Wind Harmer
5.934
970937AG2-583 GEN
Solar/Wind Harmer
22.319
971193AH1-056 GEN
Solar/Wind Harmer
11.279
971377AH1-170 GEN
Solar/Wind Harmer
4.161
971447AH1-217 GEN
Solar/Wind Harmer
10.898
971489AH1-241 GEN
Solar/Wind Harmer
20.807
971563AH1-280 GEN
Solar/Wind Harmer
2.132
941591AE2-156 GEN
50/50
5.412
958211AF2-115 GEN
Solar/Wind Harmer
2.665
966001AG1-469 GEN
Solar/Wind Helper
0.334
966251AG1-494 GEN
50/50
3.128
971741AH1-377 GEN
Solar/Wind Harmer
19.305
971845AH1-439 GEN
Solar/Wind Harmer
15.695
972003AH1-546 GEN
Solar/Wind Harmer
17.998
972185AH1-677 GEN
50/50
4.638
972187AH1-678 GEN
50/50
2.367
972205AH1-687 GEN
50/50
20.575
NYPJM->LTFIMP_NY
CLTF
0.718
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
3.782
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.646
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.617
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.656
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.434
TVALTFEXP_TVA->PJM
CLTF
0.852
MECLTFEXP_MEC->PJM
CLTF
0.289
SIGELTFEXP_SIGE->PJM
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.463

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.54 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:976.74
MW Contribution:9.96
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.699
3147133PAMPLIN
Solar/Wind Harmer
1.582
3147133PAMPLIN
Solar/Wind Harmer
0.504
3147133PAMPLIN
Solar/Wind Harmer
0.403
3143336POWHATN
Solar/Wind Harmer
2.224
3143336POWHATN
Solar/Wind Harmer
1.89
3146776BUCKING
Solar/Wind Harmer
3.491
3146776BUCKING
Solar/Wind Harmer
0.349
3146776BUCKING
Solar/Wind Harmer
0.314
3146776BUCKING
Solar/Wind Harmer
0.283
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
316303AF2-085
50/50
1.328
315616AA1-038_C
Solar/Wind Helper
1.725
315760AF1-028 GEN
50/50
Charging
15.678
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
316499AE2-029_GEN
Solar/Wind Helper
1.242
315657AE1-056 GEN
Solar/Wind Harmer
6.045
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.51
316322AB2-045
Solar/Wind Harmer
0.025
316192AB2-158 GEN
Solar/Wind Helper
1.52
942461AE2-259 GEN
Solar/Wind Harmer
0
946301AF1-294 GEN
Solar/Wind Harmer
3.885
959311AF2-222 GEN
Solar/Wind Harmer
13.304
961791AG1-021 GEN
Solar/Wind Harmer
1.895
963171AG1-166 GEN
Solar/Wind Harmer
1.895
963181AG1-167 GEN
Solar/Wind Harmer
1.421
963191AG1-168 GEN
Solar/Wind Harmer
1.421
970117AG2-086 GEN
50/50
Charging
1.272
970119AG2-088 GEN
50/50
9.961
970221AG2-151 GEN
Solar/Wind Harmer
19.574
970257AG2-171 GEN
Solar/Wind Harmer
0.152
970285AG2-188 GEN
Solar/Wind Harmer
23.134
970301AG2-198 GEN
Solar/Wind Harmer
8.122
970323AG2-213 GEN
Solar/Wind Harmer
6.163
970413AG2-270 GEN
50/50
11.154
970535AG2-341 GEN
50/50
4.269
970681AG2-440 GEN
Solar/Wind Harmer
8.617
970683AG2-441 GEN
Solar/Wind Harmer
10.771
970685AG2-442 GEN
Solar/Wind Harmer
12.063
970909AG2-566 GEN
Solar/Wind Harmer
5.252
970937AG2-583 GEN
Solar/Wind Harmer
20.592
971193AH1-056 GEN
Solar/Wind Harmer
10.075
971377AH1-170 GEN
Solar/Wind Harmer
3.915
971447AH1-217 GEN
Solar/Wind Harmer
10.18
971489AH1-241 GEN
Solar/Wind Harmer
19.574
971563AH1-280 GEN
Solar/Wind Harmer
1.895
958211AF2-115 GEN
Solar/Wind Harmer
2.369
966001AG1-469 GEN
Solar/Wind Helper
0.358
966251AG1-494 GEN
50/50
3.897
971741AH1-377 GEN
Solar/Wind Harmer
16.848
971845AH1-439 GEN
Solar/Wind Harmer
14.563
972003AH1-546 GEN
Solar/Wind Harmer
16.919
972205AH1-687 GEN
50/50
19.383
NYPJM->LTFIMP_NY
CLTF
0.753
LGEELTFEXP_LGEE->PJM
CLTF
0.45
WECLTFEXP_WEC->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
3.191
LAGNLTFEXP_LAGN->PJM
CLTF
2.588
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.46
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.28
TVALTFEXP_TVA->PJM
CLTF
1.354
MECLTFEXP_MEC->PJM
CLTF
1.224
SIGELTFEXP_SIGE->PJM
CLTF
0.038
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.77 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:1008.61
MW Contribution:15.14
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.919
3147133PAMPLIN
Solar/Wind Harmer
1.771
3147133PAMPLIN
Solar/Wind Harmer
0.564
3147133PAMPLIN
Solar/Wind Harmer
0.451
3143336POWHATN
Solar/Wind Harmer
2.572
3143336POWHATN
Solar/Wind Harmer
2.186
3146776BUCKING
Solar/Wind Harmer
3.757
3146776BUCKING
Solar/Wind Harmer
0.376
3146776BUCKING
Solar/Wind Harmer
0.338
3146776BUCKING
Solar/Wind Harmer
0.304
3146926FARMVIL
Solar/Wind Harmer
0.45
3146926FARMVIL
Solar/Wind Harmer
0.45
316303AF2-085
50/50
2.018
315616AA1-038_C
Solar/Wind Helper
1.051
315760AF1-028 GEN
50/50
Charging
11.333
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
315779AE2-040
50/50
0.984
316499AE2-029_GEN
Solar/Wind Helper
0.927
315657AE1-056 GEN
Solar/Wind Harmer
6.767
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.542
316322AB2-045
Solar/Wind Harmer
0.027
316192AB2-158 GEN
Solar/Wind Helper
1.482
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
25.205
946301AF1-294 GEN
Solar/Wind Harmer
4.371
959311AF2-222 GEN
Solar/Wind Harmer
15.206
961791AG1-021 GEN
Solar/Wind Harmer
2.132
963041AG1-153 GEN
50/50
5.221
963171AG1-166 GEN
Solar/Wind Harmer
2.132
963181AG1-167 GEN
Solar/Wind Harmer
1.599
963191AG1-168 GEN
Solar/Wind Harmer
1.599
970119AG2-088 GEN
50/50
15.136
970221AG2-151 GEN
Solar/Wind Harmer
20.807
970257AG2-171 GEN
Solar/Wind Harmer
0.174
970285AG2-188 GEN
Solar/Wind Harmer
24.994
970301AG2-198 GEN
Solar/Wind Harmer
9.178
970323AG2-213 GEN
Solar/Wind Harmer
7.068
970413AG2-270 GEN
50/50
14.358
970531AG2-338 GEN
50/50
2.734
970533AG2-339 GEN
50/50
6.834
970535AG2-341 GEN
50/50
5.181
970681AG2-440 GEN
Solar/Wind Harmer
9.775
970683AG2-441 GEN
Solar/Wind Harmer
12.219
970685AG2-442 GEN
Solar/Wind Harmer
13.686
970909AG2-566 GEN
Solar/Wind Harmer
5.934
970937AG2-583 GEN
Solar/Wind Harmer
22.319
971193AH1-056 GEN
Solar/Wind Harmer
11.279
971377AH1-170 GEN
Solar/Wind Harmer
4.161
971447AH1-217 GEN
Solar/Wind Harmer
10.898
971489AH1-241 GEN
Solar/Wind Harmer
20.807
971563AH1-280 GEN
Solar/Wind Harmer
2.132
941591AE2-156 GEN
50/50
5.412
958211AF2-115 GEN
Solar/Wind Harmer
2.665
966001AG1-469 GEN
Solar/Wind Helper
0.334
966251AG1-494 GEN
50/50
3.128
971741AH1-377 GEN
Solar/Wind Harmer
19.305
971845AH1-439 GEN
Solar/Wind Harmer
15.695
972003AH1-546 GEN
Solar/Wind Harmer
17.998
972185AH1-677 GEN
50/50
4.638
972187AH1-678 GEN
50/50
2.367
972205AH1-687 GEN
50/50
20.575
NYPJM->LTFIMP_NY
CLTF
0.718
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
3.782
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.646
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.617
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.656
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.434
TVALTFEXP_TVA->PJM
CLTF
0.852
MECLTFEXP_MEC->PJM
CLTF
0.289
SIGELTFEXP_SIGE->PJM
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.463

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.34 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:972.83
MW Contribution:9.96
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.699
3147133PAMPLIN
Solar/Wind Harmer
1.582
3147133PAMPLIN
Solar/Wind Harmer
0.504
3147133PAMPLIN
Solar/Wind Harmer
0.403
3143336POWHATN
Solar/Wind Harmer
2.224
3143336POWHATN
Solar/Wind Harmer
1.89
3146776BUCKING
Solar/Wind Harmer
3.491
3146776BUCKING
Solar/Wind Harmer
0.349
3146776BUCKING
Solar/Wind Harmer
0.314
3146776BUCKING
Solar/Wind Harmer
0.283
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
316303AF2-085
50/50
1.328
315616AA1-038_C
Solar/Wind Helper
1.725
315760AF1-028 GEN
50/50
Charging
15.678
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
316499AE2-029_GEN
Solar/Wind Helper
1.242
315657AE1-056 GEN
Solar/Wind Harmer
6.045
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.51
316322AB2-045
Solar/Wind Harmer
0.025
316192AB2-158 GEN
Solar/Wind Helper
1.52
942461AE2-259 GEN
Solar/Wind Harmer
0
946301AF1-294 GEN
Solar/Wind Harmer
3.885
959311AF2-222 GEN
Solar/Wind Harmer
13.304
961791AG1-021 GEN
Solar/Wind Harmer
1.895
963171AG1-166 GEN
Solar/Wind Harmer
1.895
963181AG1-167 GEN
Solar/Wind Harmer
1.421
963191AG1-168 GEN
Solar/Wind Harmer
1.421
970117AG2-086 GEN
50/50
Charging
1.272
970119AG2-088 GEN
50/50
9.961
970221AG2-151 GEN
Solar/Wind Harmer
19.574
970257AG2-171 GEN
Solar/Wind Harmer
0.152
970285AG2-188 GEN
Solar/Wind Harmer
23.134
970301AG2-198 GEN
Solar/Wind Harmer
8.122
970323AG2-213 GEN
Solar/Wind Harmer
6.163
970413AG2-270 GEN
50/50
11.154
970535AG2-341 GEN
50/50
4.269
970681AG2-440 GEN
Solar/Wind Harmer
8.617
970683AG2-441 GEN
Solar/Wind Harmer
10.771
970685AG2-442 GEN
Solar/Wind Harmer
12.063
970909AG2-566 GEN
Solar/Wind Harmer
5.252
970937AG2-583 GEN
Solar/Wind Harmer
20.592
971193AH1-056 GEN
Solar/Wind Harmer
10.075
971377AH1-170 GEN
Solar/Wind Harmer
3.915
971447AH1-217 GEN
Solar/Wind Harmer
10.18
971489AH1-241 GEN
Solar/Wind Harmer
19.574
971563AH1-280 GEN
Solar/Wind Harmer
1.895
958211AF2-115 GEN
Solar/Wind Harmer
2.369
966001AG1-469 GEN
Solar/Wind Helper
0.358
966251AG1-494 GEN
50/50
3.897
971741AH1-377 GEN
Solar/Wind Harmer
16.848
971845AH1-439 GEN
Solar/Wind Harmer
14.563
972003AH1-546 GEN
Solar/Wind Harmer
16.919
972205AH1-687 GEN
50/50
19.383
NYPJM->LTFIMP_NY
CLTF
0.753
LGEELTFEXP_LGEE->PJM
CLTF
0.45
WECLTFEXP_WEC->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
3.191
LAGNLTFEXP_LAGN->PJM
CLTF
2.588
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.46
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.28
TVALTFEXP_TVA->PJM
CLTF
1.354
MECLTFEXP_MEC->PJM
CLTF
1.224
SIGELTFEXP_SIGE->PJM
CLTF
0.038
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.16 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:1003.7
MW Contribution:15.14
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.919
3147133PAMPLIN
Solar/Wind Harmer
1.771
3147133PAMPLIN
Solar/Wind Harmer
0.564
3147133PAMPLIN
Solar/Wind Harmer
0.451
3143336POWHATN
Solar/Wind Harmer
2.572
3143336POWHATN
Solar/Wind Harmer
2.186
3146776BUCKING
Solar/Wind Harmer
3.757
3146776BUCKING
Solar/Wind Harmer
0.376
3146776BUCKING
Solar/Wind Harmer
0.338
3146776BUCKING
Solar/Wind Harmer
0.304
3146926FARMVIL
Solar/Wind Harmer
0.45
3146926FARMVIL
Solar/Wind Harmer
0.45
316303AF2-085
50/50
2.018
315616AA1-038_C
Solar/Wind Helper
1.051
315760AF1-028 GEN
50/50
Charging
11.333
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
315779AE2-040
50/50
0.984
316499AE2-029_GEN
Solar/Wind Helper
0.927
315657AE1-056 GEN
Solar/Wind Harmer
6.767
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.542
316322AB2-045
Solar/Wind Harmer
0.027
316192AB2-158 GEN
Solar/Wind Helper
1.482
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
25.205
946301AF1-294 GEN
Solar/Wind Harmer
4.371
959311AF2-222 GEN
Solar/Wind Harmer
15.206
961791AG1-021 GEN
Solar/Wind Harmer
2.132
963041AG1-153 GEN
50/50
5.221
963171AG1-166 GEN
Solar/Wind Harmer
2.132
963181AG1-167 GEN
Solar/Wind Harmer
1.599
963191AG1-168 GEN
Solar/Wind Harmer
1.599
970119AG2-088 GEN
50/50
15.136
970221AG2-151 GEN
Solar/Wind Harmer
20.807
970257AG2-171 GEN
Solar/Wind Harmer
0.174
970285AG2-188 GEN
Solar/Wind Harmer
24.994
970301AG2-198 GEN
Solar/Wind Harmer
9.178
970323AG2-213 GEN
Solar/Wind Harmer
7.068
970413AG2-270 GEN
50/50
14.358
970531AG2-338 GEN
50/50
2.734
970533AG2-339 GEN
50/50
6.834
970535AG2-341 GEN
50/50
5.181
970681AG2-440 GEN
Solar/Wind Harmer
9.775
970683AG2-441 GEN
Solar/Wind Harmer
12.219
970685AG2-442 GEN
Solar/Wind Harmer
13.686
970909AG2-566 GEN
Solar/Wind Harmer
5.934
970937AG2-583 GEN
Solar/Wind Harmer
22.319
971193AH1-056 GEN
Solar/Wind Harmer
11.279
971377AH1-170 GEN
Solar/Wind Harmer
4.161
971447AH1-217 GEN
Solar/Wind Harmer
10.898
971489AH1-241 GEN
Solar/Wind Harmer
20.807
971563AH1-280 GEN
Solar/Wind Harmer
2.132
941591AE2-156 GEN
50/50
5.412
958211AF2-115 GEN
Solar/Wind Harmer
2.665
966001AG1-469 GEN
Solar/Wind Helper
0.334
966251AG1-494 GEN
50/50
3.128
971741AH1-377 GEN
Solar/Wind Harmer
19.305
971845AH1-439 GEN
Solar/Wind Harmer
15.695
972003AH1-546 GEN
Solar/Wind Harmer
17.998
972185AH1-677 GEN
50/50
4.638
972187AH1-678 GEN
50/50
2.367
972205AH1-687 GEN
50/50
20.575
NYPJM->LTFIMP_NY
CLTF
0.718
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
3.782
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.646
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.617
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.656
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.434
TVALTFEXP_TVA->PJM
CLTF
0.852
MECLTFEXP_MEC->PJM
CLTF
0.289
SIGELTFEXP_SIGE->PJM
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.463

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.74 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:967.95
MW Contribution:9.96
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.699
3147133PAMPLIN
Solar/Wind Harmer
1.582
3147133PAMPLIN
Solar/Wind Harmer
0.504
3147133PAMPLIN
Solar/Wind Harmer
0.403
3143336POWHATN
Solar/Wind Harmer
2.224
3143336POWHATN
Solar/Wind Harmer
1.89
3146776BUCKING
Solar/Wind Harmer
3.491
3146776BUCKING
Solar/Wind Harmer
0.349
3146776BUCKING
Solar/Wind Harmer
0.314
3146776BUCKING
Solar/Wind Harmer
0.283
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
316303AF2-085
50/50
1.328
315616AA1-038_C
Solar/Wind Helper
1.725
315760AF1-028 GEN
50/50
Charging
15.678
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
316499AE2-029_GEN
Solar/Wind Helper
1.242
315657AE1-056 GEN
Solar/Wind Harmer
6.045
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.51
316322AB2-045
Solar/Wind Harmer
0.025
316192AB2-158 GEN
Solar/Wind Helper
1.52
942461AE2-259 GEN
Solar/Wind Harmer
0
946301AF1-294 GEN
Solar/Wind Harmer
3.885
959311AF2-222 GEN
Solar/Wind Harmer
13.304
961791AG1-021 GEN
Solar/Wind Harmer
1.895
963171AG1-166 GEN
Solar/Wind Harmer
1.895
963181AG1-167 GEN
Solar/Wind Harmer
1.421
963191AG1-168 GEN
Solar/Wind Harmer
1.421
970117AG2-086 GEN
50/50
Charging
1.272
970119AG2-088 GEN
50/50
9.961
970221AG2-151 GEN
Solar/Wind Harmer
19.574
970257AG2-171 GEN
Solar/Wind Harmer
0.152
970285AG2-188 GEN
Solar/Wind Harmer
23.134
970301AG2-198 GEN
Solar/Wind Harmer
8.122
970323AG2-213 GEN
Solar/Wind Harmer
6.163
970413AG2-270 GEN
50/50
11.154
970535AG2-341 GEN
50/50
4.269
970681AG2-440 GEN
Solar/Wind Harmer
8.617
970683AG2-441 GEN
Solar/Wind Harmer
10.771
970685AG2-442 GEN
Solar/Wind Harmer
12.063
970909AG2-566 GEN
Solar/Wind Harmer
5.252
970937AG2-583 GEN
Solar/Wind Harmer
20.592
971193AH1-056 GEN
Solar/Wind Harmer
10.075
971377AH1-170 GEN
Solar/Wind Harmer
3.915
971447AH1-217 GEN
Solar/Wind Harmer
10.18
971489AH1-241 GEN
Solar/Wind Harmer
19.574
971563AH1-280 GEN
Solar/Wind Harmer
1.895
958211AF2-115 GEN
Solar/Wind Harmer
2.369
966001AG1-469 GEN
Solar/Wind Helper
0.358
966251AG1-494 GEN
50/50
3.897
971741AH1-377 GEN
Solar/Wind Harmer
16.848
971845AH1-439 GEN
Solar/Wind Harmer
14.563
972003AH1-546 GEN
Solar/Wind Harmer
16.919
972205AH1-687 GEN
50/50
19.383
NYPJM->LTFIMP_NY
CLTF
0.753
LGEELTFEXP_LGEE->PJM
CLTF
0.45
WECLTFEXP_WEC->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
3.191
LAGNLTFEXP_LAGN->PJM
CLTF
2.588
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.46
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.28
TVALTFEXP_TVA->PJM
CLTF
1.354
MECLTFEXP_MEC->PJM
CLTF
1.224
SIGELTFEXP_SIGE->PJM
CLTF
0.038
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284
CONTINGENCY 'DVP_P1-2: LN 576_SRT-L'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3914 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 3880 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-L'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3359 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 3377 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 217_SRT-L'
 OPEN BRANCH FROM BUS 314225 TO BUS 314227 CKT 1                /*6CHARCTY     230.0 - 6LAKESIDE    230.0
 OPEN BRANCH FROM BUS 314225 TO BUS 314260 CKT 1                /*6CHARCTY     230.0 - 6VARINA      230.0
 OPEN BRANCH FROM BUS 314260 TO BUS 314287 CKT 1                /*6VARINA      230.0 - 6CHESTF B    230.0
 OPEN BUS 314225                                                /*6CHARCTY     230.0
 OPEN BUS 314260                                                /*6VARINA      230.0
 SET POSTCONTRATING 1092 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
 SET PRECONTRATING 1036 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314287 to 314276 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314765 to 314749 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA1-145Four Rivers 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-132Thelma 230kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-058St. Barnabas 13 kVIn Service
AD2-065Atco 12 kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-116Hokes-Grantley 69 kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-153Remington-Gordonsville 230 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-140Axton-Danville 138 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-183Rogers Road 500 kVIn Service
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-028Endless Caverns 115 kVUnder Construction
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF2-035St. Johns 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-107Clifford 138 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-153Heritage 500 kVActive
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-397Walston 12 kVWithdrawn
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-494Boxwood-Riverville 138 kVActive
AG1-499Lambs 12.47 kVUnder Construction
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-086Mt. Jackson DP-Mt. Jackson 115 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-320Ladysmith 230 kVActive
AG2-338Rogers Road - Carson 500 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-384Chesterfield 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-012Louisa - North Anna 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-056Red House DP 115kVActive
AH1-065Hopewell 34.5kVActive
AH1-066Hopewell 34.5kVActive
AH1-071Midlothian 34.5 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-170Columbia DP 115kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-221Heritage 500 kVActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-323Elmont 230 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-377Clover- Farmville 230kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-676Gordonsville 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-712Cunningham 500 kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
AH1-723Cunningham 500 kVActive
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-068Murphy's 34.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
X3-066Church Hill 69kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-088 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
Dominionn9248.0 / TC1-PH2-DOM-042Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.$10,967,705
Dominion(Pending) / TC2-PH1-DOM-0075Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"$5,883,523
Dominion(Pending) / TC2-PH1-DOM-0071Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".$4,892,618
Dominionn7568 / dom-369-TC2Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.$1,445,217
Dominionn9203.0 / TC1-PH2-DOM-008-TC2Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.$1,184,612
Dominionn7569 / dom-490-TC2Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.$524,657
Dominionn9644.0 / TC1-PH3-DOM-006-TC2Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.$330,472
Dominionn9198.0 / TC1-PH2-DOM-003-TC2Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).$89,747
Dominion(Pending) / TC2-PH1-DOM-0072Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV$47,005
Dominion(Pending) / TC2-PH1-DOM-0073Replace Wave Trap 573WT at Spotsylvania 500 KV$47,005
Dominion(Pending) / TC2-PH1-DOM-0076Replace Wave Trap 594WT at Morrisville 500 KV$37,901
Dominion(Pending) / TC2-PH1-DOM-0077Replace Wave Trap 594WT at Spotsylvania 500 KV$37,901
Dominion(Pending) / TC2-PH1-DOM-0078Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV$37,901
Dominion(Pending) / TC2-PH1-DOM-2065Replace switches 219324 and 219325 at Bremo 230 kV$33,965
Dominion(Pending) / TC2-PH1-DOM-2072Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV$19,635
Dominion(Pending) / TC2-PH1-DOM-2068Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C$18,287
Dominion(Pending) / TC2-PH1-DOM-2066Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV$17,891
Dominion(Pending) / TC2-PH1-DOM-2067Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV$17,891
Dominion(Pending) / TC2-PH1-DOM-2064Replace 2-1590 line lead on line 2193 at Fork Union 230 kV$17,891
Dominion(Pending) / TC2-PH1-DOM-2063Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C$17,747
Dominion(Pending) / TC2-PH1-DOM-0080Replace switch 219326 at Bremo 230 kV$16,982
Dominion(Pending) / TC2-PH1-DOM-2070Replace wave trap 2028WT at Fork Union 230 kV$16,041
Dominion(Pending) / TC2-PH1-DOM-2069Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV$15,999
Dominion(Pending) / TC2-PH1-DOM-2073Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV$15,733
Dominion(Pending) / TC2-PH1-DOM-2071Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV$15,733
Dominion(Pending) / TC1-PH3-DOM-007Replace Wave Trap 2028WT at Charlottesville$15,708
Grand Total:$25,765,767

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.354
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b4000.354
Title
Ladysmith substation breakers replacement: 574T575 and 568T581
Description
Expand Ladysmith substation to a add redundant circuit breakers to the middle breakers on both 500kV strings (574T575 and 568T581). The equipment including switches 57518, 57515, H115 will be replaced with 5000A equipment.
Cost Information
Time Estimate
Nov 14 2029

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 568T581_SRT-S
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 568T581_SRT-S

System Reinforcement: n9248.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9248.0 / TC1-PH2-DOM-042
Title
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Description
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Total Cost ($USD)
$345,766,000
Allocated Cost ($USD)
$10,967,705
Time Estimate
48 to 60 Months

Contributor

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 557_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 557T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
49.1 MW3.2%$10,967,705
AG2-338
12.3 MW0.8%$2,748,846
AG2-339
30.8 MW2.0%$6,872,339
AG2-428
79.4 MW5.1%$17,734,681
AG2-436
235.2 MW15.2%$52,507,120
AG2-570
114.4 MW7.4%$25,532,306
AG2-571
22.2 MW1.4%$4,965,737
AH1-528
104.3 MW6.7%$23,286,172
AH1-681
10.3 MW0.7%$2,301,272
AH1-712
230.7 MW14.9%$51,504,150
AH1-716
391.2 MW25.3%$87,327,776
AH1-723
268.9 MW17.4%$60,017,895

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0075
Title
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Description
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Total Cost ($USD)
$110,625,000
Allocated Cost ($USD)
$5,883,523
Time Estimate
18 to 60 Months

Contributor

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P2-2: MORRISVILLE B1_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 545T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H1T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H3T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 550_SRT-A
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
34.7 MW5.3%$5,883,523
AG2-428
33.0 MW5.1%$5,604,107
AG2-436
82.7 MW12.7%$14,035,461
AG2-570
61.7 MW9.5%$10,463,443
AG2-571
7.8 MW1.2%$1,324,471
AH1-263
59.0 MW9.0%$10,010,303
AH1-528
48.5 MW7.4%$8,233,540
AH1-676
160.9 MW24.7%$27,304,435
AH1-681
3.3 MW0.5%$561,378
AH1-712
74.1 MW11.4%$12,563,732
AH1-723
86.3 MW13.2%$14,640,609

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0071
Title
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Description
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Total Cost ($USD)
$82,718,000
Allocated Cost ($USD)
$4,892,618
Time Estimate
18 to 48 Months

Contributor

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
35.4 MW5.9%$4,892,618
AG2-436
84.8 MW14.2%$11,707,917
AH1-528
37.7 MW6.3%$5,201,462
AH1-676
136.3 MW22.8%$18,825,984
AH1-681
3.3 MW0.6%$462,576
AH1-712
75.0 MW12.5%$10,354,029
AH1-716
139.1 MW23.2%$19,207,896
AH1-723
87.4 MW14.6%$12,065,519

System Reinforcement: n7568
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7568 / dom-369-TC2
Title
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Description
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Total Cost ($USD)
$36,802,018
Allocated Cost ($USD)
$1,445,217
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$386,666
AG2-069
6.2 MW1.6%$580,093
AG2-077
11.7 MW3.0%$1,098,680
AG2-088
15.4 MW3.9%$1,445,217
AG2-151
21.6 MW5.5%$2,028,498
AG2-171
8.1 MW2.1%$763,488
AG2-188
27.6 MW7.0%$2,583,932
AG2-198
9.6 MW2.4%$898,502
AG2-213
7.4 MW1.9%$693,918
AG2-270
14.4 MW3.7%$1,346,206
AG2-338
2.8 MW0.7%$263,278
AG2-339
7.0 MW1.8%$658,101
AG2-369
0.8 MW0.2%$79,602
AG2-428
7.8 MW2.0%$733,766
AG2-436
28.3 MW7.2%$2,654,439
AG2-440
10.2 MW2.6%$958,602
AG2-441
12.8 MW3.3%$1,198,253
AG2-442
14.3 MW3.6%$1,341,987
AG2-566
5.9 MW1.5%$556,372
AG2-570
6.9 MW1.8%$647,038
AG2-571
2.8 MW0.7%$258,778
AG2-581
7.5 MW1.9%$699,918
AG2-583
23.2 MW5.9%$2,176,826
AH1-056
13.4 MW3.4%$1,260,884
AH1-217
11.3 MW2.9%$1,062,957
AH1-241
21.6 MW5.5%$2,028,498
AH1-377
20.2 MW5.1%$1,891,795
AH1-439
16.3 MW4.2%$1,531,101
AH1-528
13.7 MW3.5%$1,285,543
AH1-546
18.7 MW4.8%$1,751,062
AH1-687
20.7 MW5.3%$1,938,019

System Reinforcement: n9203.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9203.0 / TC1-PH2-DOM-008-TC2
Title
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Description
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Total Cost ($USD)
$29,539,973
Allocated Cost ($USD)
$1,184,612
Time Estimate
45 to 46 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$316,942
AG2-069
6.2 MW1.6%$475,489
AG2-077
11.7 MW3.0%$900,563
AG2-088
15.4 MW4.0%$1,184,612
AG2-151
21.6 MW5.6%$1,662,714
AG2-188
27.6 MW7.2%$2,117,991
AG2-198
9.6 MW2.5%$736,482
AG2-213
7.4 MW1.9%$568,789
AG2-270
14.4 MW3.7%$1,103,455
AG2-338
2.8 MW0.7%$215,803
AG2-339
7.0 MW1.8%$539,431
AG2-369
0.8 MW0.2%$65,248
AG2-428
7.8 MW2.0%$601,451
AG2-436
28.3 MW7.4%$2,175,784
AG2-440
10.2 MW2.7%$785,745
AG2-441
12.8 MW3.3%$982,181
AG2-442
14.3 MW3.7%$1,099,996
AG2-566
5.9 MW1.5%$456,045
AG2-570
6.9 MW1.8%$530,362
AG2-571
2.8 MW0.7%$212,114
AG2-581
7.5 MW1.9%$573,707
AG2-583
23.2 MW6.0%$1,784,295
AH1-056
13.4 MW3.5%$1,033,519
AH1-217
11.3 MW2.9%$871,282
AH1-241
21.6 MW5.6%$1,662,714
AH1-377
20.2 MW5.2%$1,550,662
AH1-439
16.3 MW4.2%$1,255,009
AH1-528
13.7 MW3.6%$1,053,731
AH1-546
18.7 MW4.9%$1,435,306
AH1-687
20.7 MW5.4%$1,588,551

System Reinforcement: n7569
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7569 / dom-490-TC2
Title
Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.
Description
Uograde 3.78 miles of transmission line 2028 between Mt. Eagle and Grape Vine with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"". The segment runs from Mt Eagle to structure 2080/73.
Total Cost ($USD)
$13,360,242
Allocated Cost ($USD)
$524,657
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$140,371
AG2-069
6.2 MW1.6%$210,591
AG2-077
11.7 MW3.0%$398,854
AG2-088
15.4 MW3.9%$524,657
AG2-151
21.6 MW5.5%$736,406
AG2-171
8.1 MW2.1%$277,169
AG2-188
27.6 MW7.0%$938,045
AG2-198
9.6 MW2.4%$326,183
AG2-213
7.4 MW1.9%$251,913
AG2-270
14.4 MW3.7%$488,713
AG2-338
2.8 MW0.7%$95,578
AG2-339
7.0 MW1.8%$238,911
AG2-369
0.8 MW0.2%$28,898
AG2-428
7.8 MW2.0%$266,379
AG2-436
28.3 MW7.2%$963,641
AG2-440
10.2 MW2.6%$348,002
AG2-441
12.8 MW3.3%$435,002
AG2-442
14.3 MW3.6%$487,182
AG2-566
5.9 MW1.5%$201,980
AG2-570
6.9 MW1.8%$234,894
AG2-571
2.8 MW0.7%$93,944
AG2-581
7.5 MW1.9%$254,091
AG2-583
23.2 MW5.9%$790,253
AH1-056
13.4 MW3.4%$457,739
AH1-217
11.3 MW2.9%$385,885
AH1-241
21.6 MW5.5%$736,406
AH1-377
20.2 MW5.1%$686,779
AH1-439
16.3 MW4.2%$555,836
AH1-528
13.7 MW3.5%$466,691
AH1-546
18.7 MW4.8%$635,688
AH1-687
20.7 MW5.3%$703,559

System Reinforcement: n9644.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9644.0 / TC1-PH3-DOM-006-TC2
Title
Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.
Description
Rebuild a 2.73 mile segment of 230kV line 2028 between Mt. Eagle and Grape Vinew with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @250 degrees C.
Total Cost ($USD)
$8,415,380
Allocated Cost ($USD)
$330,472
Time Estimate
Mar 31 2029

Contributor

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$88,418
AG2-069
6.2 MW1.6%$132,648
AG2-077
11.7 MW3.0%$251,231
AG2-088
15.4 MW3.9%$330,472
AG2-151
21.6 MW5.5%$463,849
AG2-171
8.1 MW2.1%$174,584
AG2-188
27.6 MW7.0%$590,858
AG2-198
9.6 MW2.4%$205,457
AG2-213
7.4 MW1.9%$158,676
AG2-270
14.4 MW3.7%$307,832
AG2-338
2.8 MW0.7%$60,203
AG2-339
7.0 MW1.8%$150,486
AG2-369
0.8 MW0.2%$18,202
AG2-428
7.8 MW2.0%$167,787
AG2-436
28.3 MW7.2%$606,981
AG2-440
10.2 MW2.6%$219,200
AG2-441
12.8 MW3.3%$274,000
AG2-442
14.3 MW3.6%$306,867
AG2-566
5.9 MW1.5%$127,223
AG2-570
6.9 MW1.8%$147,956
AG2-571
2.8 MW0.7%$59,174
AG2-581
7.5 MW1.9%$160,048
AG2-583
23.2 MW5.9%$497,767
AH1-056
13.4 MW3.4%$288,322
AH1-217
11.3 MW2.9%$243,062
AH1-241
21.6 MW5.5%$463,849
AH1-377
20.2 MW5.1%$432,590
AH1-439
16.3 MW4.2%$350,111
AH1-528
13.7 MW3.5%$293,960
AH1-546
18.7 MW4.8%$400,409
AH1-687
20.7 MW5.3%$443,160

System Reinforcement: n9198.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9198.0 / TC1-PH2-DOM-003-TC2
Title
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Description
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Total Cost ($USD)
$2,113,879
Allocated Cost ($USD)
$89,747
Time Estimate
40 to 41 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.5 MW0.7%$14,813
AG2-069
8.3 MW1.1%$22,223
AG2-077
20.7 MW2.6%$55,670
AG2-088
33.4 MW4.2%$89,747
AG2-151
27.7 MW3.5%$74,401
AG2-171
17.4 MW2.2%$46,851
AG2-188
59.1 MW7.5%$159,015
AG2-198
20.5 MW2.6%$55,218
AG2-213
17.6 MW2.2%$47,443
AG2-270
30.6 MW3.9%$82,279
AG2-338
6.0 MW0.8%$16,245
AG2-339
15.1 MW1.9%$40,615
AG2-369
4.1 MW0.5%$10,993
AG2-428
17.0 MW2.2%$45,705
AG2-436
60.8 MW7.7%$163,599
AG2-440
20.9 MW2.7%$56,176
AG2-441
26.1 MW3.3%$70,215
AG2-442
30.6 MW3.9%$82,225
AG2-566
12.7 MW1.6%$34,201
AG2-570
14.8 MW1.9%$39,732
AG2-571
5.9 MW0.8%$15,890
AG2-581
16.0 MW2.0%$43,020
AG2-583
49.9 MW6.3%$134,134
AH1-056
28.8 MW3.7%$77,366
AH1-241
27.7 MW3.5%$74,401
AH1-377
43.2 MW5.5%$116,216
AH1-408
16.7 MW2.1%$44,930
AH1-439
35.0 MW4.5%$94,235
AH1-528
29.4 MW3.7%$79,147
AH1-546
40.1 MW5.1%$107,827
AH1-687
44.4 MW5.6%$119,347

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0072
Title
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Description
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$47,005
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
35.9 MW7.8%$47,005
AG2-436
86.0 MW18.7%$112,489
AH1-528
38.2 MW8.3%$49,971
AH1-676
129.2 MW28.2%$168,963
AH1-681
3.4 MW0.7%$4,480
AH1-712
76.6 MW16.7%$100,259
AH1-723
89.3 MW19.5%$116,833

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0073
Title
Replace Wave Trap 573WT at Spotsylvania 500 KV
Description
Replace Wave Trap 573WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$47,005
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
35.9 MW7.8%$47,005
AG2-436
86.0 MW18.7%$112,489
AH1-528
38.2 MW8.3%$49,971
AH1-676
129.2 MW28.2%$168,963
AH1-681
3.4 MW0.7%$4,480
AH1-712
76.6 MW16.7%$100,259
AH1-723
89.3 MW19.5%$116,833

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0076
Title
Replace Wave Trap 594WT at Morrisville 500 KV
Description
Replace Wave Trap 594WT at Morrisville 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$37,901
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
35.3 MW6.3%$37,901
AG2-436
84.4 MW15.1%$90,521
AH1-263
60.4 MW10.8%$64,771
AH1-528
37.5 MW6.7%$40,233
AH1-676
173.8 MW31.1%$186,369
AH1-681
3.4 MW0.6%$3,643
AH1-712
76.0 MW13.6%$81,542
AH1-723
88.6 MW15.8%$95,021

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0077
Title
Replace Wave Trap 594WT at Spotsylvania 500 KV
Description
Replace Wave Trap 594WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$37,901
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
35.3 MW6.3%$37,901
AG2-436
84.4 MW15.1%$90,521
AH1-263
60.4 MW10.8%$64,771
AH1-528
37.5 MW6.7%$40,233
AH1-676
173.8 MW31.1%$186,369
AH1-681
3.4 MW0.6%$3,643
AH1-712
76.0 MW13.6%$81,542
AH1-723
88.6 MW15.8%$95,021

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0078
Title
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Description
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$37,901
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
35.3 MW6.3%$37,901
AG2-436
84.4 MW15.1%$90,521
AH1-263
60.4 MW10.8%$64,771
AH1-528
37.5 MW6.7%$40,233
AH1-676
173.8 MW31.1%$186,369
AH1-681
3.4 MW0.6%$3,643
AH1-712
76.0 MW13.6%$81,542
AH1-723
88.6 MW15.8%$95,021

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2065
Title
Replace switches 219324 and 219325 at Bremo 230 kV
Description
Replace switches 219324 and 219325 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$33,965
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.7%$5,606
AG2-069
4.1 MW1.1%$8,410
AG2-077
10.3 MW2.6%$21,068
AG2-088
16.7 MW4.2%$33,965
AG2-151
13.8 MW3.5%$28,157
AG2-171
8.7 MW2.2%$17,731
AG2-188
29.6 MW7.5%$60,179
AG2-198
10.3 MW2.6%$20,897
AG2-213
8.8 MW2.2%$17,955
AG2-270
15.3 MW3.9%$31,138
AG2-338
3.0 MW0.8%$6,148
AG2-339
7.5 MW1.9%$15,371
AG2-369
2.0 MW0.5%$4,160
AG2-428
8.5 MW2.2%$17,297
AG2-436
30.4 MW7.7%$61,914
AG2-440
10.4 MW2.7%$21,260
AG2-441
13.0 MW3.3%$26,573
AG2-442
15.3 MW3.9%$31,118
AG2-566
6.4 MW1.6%$12,943
AG2-570
7.4 MW1.9%$15,037
AG2-571
3.0 MW0.8%$6,013
AG2-581
8.0 MW2.0%$16,281
AG2-583
24.9 MW6.3%$50,763
AH1-056
14.4 MW3.7%$29,279
AH1-241
13.8 MW3.5%$28,157
AH1-377
21.6 MW5.5%$43,982
AH1-408
8.3 MW2.1%$17,004
AH1-439
17.5 MW4.5%$35,663
AH1-528
14.7 MW3.7%$29,953
AH1-546
20.0 MW5.1%$40,807
AH1-687
22.2 MW5.6%$45,167

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2072
Title
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Description
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$19,635
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$5,253
AG2-069
6.2 MW1.6%$7,881
AG2-077
11.7 MW3.0%$14,927
AG2-088
15.4 MW3.9%$19,635
AG2-151
21.6 MW5.5%$27,560
AG2-171
8.1 MW2.1%$10,373
AG2-188
27.6 MW7.0%$35,106
AG2-198
9.6 MW2.4%$12,207
AG2-213
7.4 MW1.9%$9,428
AG2-270
14.4 MW3.7%$18,290
AG2-338
2.8 MW0.7%$3,577
AG2-339
7.0 MW1.8%$8,941
AG2-369
0.8 MW0.2%$1,081
AG2-428
7.8 MW2.0%$9,969
AG2-436
28.3 MW7.2%$36,064
AG2-440
10.2 MW2.6%$13,024
AG2-441
12.8 MW3.3%$16,280
AG2-442
14.3 MW3.6%$18,233
AG2-566
5.9 MW1.5%$7,559
AG2-570
6.9 MW1.8%$8,791
AG2-571
2.8 MW0.7%$3,516
AG2-581
7.5 MW1.9%$9,509
AG2-583
23.2 MW5.9%$29,575
AH1-056
13.4 MW3.4%$17,131
AH1-217
11.3 MW2.9%$14,442
AH1-241
21.6 MW5.5%$27,560
AH1-377
20.2 MW5.1%$25,702
AH1-439
16.3 MW4.2%$20,802
AH1-528
13.7 MW3.5%$17,466
AH1-546
18.7 MW4.8%$23,790
AH1-687
20.7 MW5.3%$26,330

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2068
Title
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$456,000
Allocated Cost ($USD)
$18,287
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$4,893
AG2-069
6.2 MW1.6%$7,340
AG2-077
11.7 MW3.0%$13,902
AG2-088
15.4 MW4.0%$18,287
AG2-151
21.6 MW5.6%$25,667
AG2-188
27.6 MW7.2%$32,695
AG2-198
9.6 MW2.5%$11,369
AG2-213
7.4 MW1.9%$8,780
AG2-270
14.4 MW3.7%$17,034
AG2-338
2.8 MW0.7%$3,331
AG2-339
7.0 MW1.8%$8,327
AG2-369
0.8 MW0.2%$1,007
AG2-428
7.8 MW2.0%$9,284
AG2-436
28.3 MW7.4%$33,587
AG2-440
10.2 MW2.7%$12,129
AG2-441
12.8 MW3.3%$15,162
AG2-442
14.3 MW3.7%$16,980
AG2-566
5.9 MW1.5%$7,040
AG2-570
6.9 MW1.8%$8,187
AG2-571
2.8 MW0.7%$3,274
AG2-581
7.5 MW1.9%$8,856
AG2-583
23.2 MW6.0%$27,544
AH1-056
13.4 MW3.5%$15,954
AH1-217
11.3 MW2.9%$13,450
AH1-241
21.6 MW5.6%$25,667
AH1-377
20.2 MW5.2%$23,937
AH1-439
16.3 MW4.2%$19,373
AH1-528
13.7 MW3.6%$16,266
AH1-546
18.7 MW4.9%$22,156
AH1-687
20.7 MW5.4%$24,522

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2066
Title
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Description
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$17,891
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.6%$2,954
AG2-069
4.1 MW0.9%$4,432
AG2-077
10.3 MW2.2%$11,102
AG2-088
16.7 MW3.6%$17,891
AG2-151
13.8 MW3.0%$14,838
AG2-171
8.7 MW1.9%$9,343
AG2-188
36.7 MW7.9%$39,350
AG2-198
13.5 MW2.9%$14,479
AG2-213
11.6 MW2.5%$12,458
AG2-270
15.3 MW3.3%$16,409
AG2-338
3.0 MW0.6%$3,240
AG2-339
7.5 MW1.6%$8,100
AG2-369
2.0 MW0.4%$2,192
AG2-428
9.9 MW2.1%$10,624
AG2-436
30.4 MW6.5%$32,614
AG2-440
11.3 MW2.4%$12,126
AG2-441
14.1 MW3.0%$15,157
AG2-442
20.1 MW4.3%$21,562
AG2-566
6.4 MW1.4%$6,821
AG2-570
23.3 MW5.0%$25,024
AG2-571
3.0 MW0.6%$3,168
AG2-581
10.5 MW2.3%$11,289
AG2-583
32.8 MW7.0%$35,169
AH1-056
16.6 MW3.6%$17,769
AH1-241
13.8 MW3.0%$14,838
AH1-377
28.4 MW6.1%$30,476
AH1-408
8.3 MW1.8%$8,960
AH1-439
23.0 MW4.9%$24,707
AH1-528
19.4 MW4.2%$20,828
AH1-546
26.4 MW5.7%$28,317
AH1-687
22.1 MW4.8%$23,765

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2067
Title
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Description
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$17,891
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.6%$2,954
AG2-069
4.1 MW0.9%$4,432
AG2-077
10.3 MW2.2%$11,102
AG2-088
16.7 MW3.6%$17,891
AG2-151
13.8 MW3.0%$14,838
AG2-171
8.7 MW1.9%$9,343
AG2-188
36.7 MW7.9%$39,350
AG2-198
13.5 MW2.9%$14,479
AG2-213
11.6 MW2.5%$12,458
AG2-270
15.3 MW3.3%$16,409
AG2-338
3.0 MW0.6%$3,240
AG2-339
7.5 MW1.6%$8,100
AG2-369
2.0 MW0.4%$2,192
AG2-428
9.9 MW2.1%$10,624
AG2-436
30.4 MW6.5%$32,614
AG2-440
11.3 MW2.4%$12,126
AG2-441
14.1 MW3.0%$15,157
AG2-442
20.1 MW4.3%$21,562
AG2-566
6.4 MW1.4%$6,821
AG2-570
23.3 MW5.0%$25,024
AG2-571
3.0 MW0.6%$3,168
AG2-581
10.5 MW2.3%$11,289
AG2-583
32.8 MW7.0%$35,169
AH1-056
16.6 MW3.6%$17,769
AH1-241
13.8 MW3.0%$14,838
AH1-377
28.4 MW6.1%$30,476
AH1-408
8.3 MW1.8%$8,960
AH1-439
23.0 MW4.9%$24,707
AH1-528
19.4 MW4.2%$20,828
AH1-546
26.4 MW5.7%$28,317
AH1-687
22.1 MW4.8%$23,765

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2064
Title
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Description
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$17,891
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.6%$2,954
AG2-069
4.1 MW0.9%$4,432
AG2-077
10.3 MW2.2%$11,102
AG2-088
16.7 MW3.6%$17,891
AG2-151
13.8 MW3.0%$14,838
AG2-171
8.7 MW1.9%$9,343
AG2-188
36.7 MW7.9%$39,350
AG2-198
13.5 MW2.9%$14,479
AG2-213
11.6 MW2.5%$12,458
AG2-270
15.3 MW3.3%$16,409
AG2-338
3.0 MW0.6%$3,240
AG2-339
7.5 MW1.6%$8,100
AG2-369
2.0 MW0.4%$2,192
AG2-428
9.9 MW2.1%$10,624
AG2-436
30.4 MW6.5%$32,614
AG2-440
11.3 MW2.4%$12,126
AG2-441
14.1 MW3.0%$15,157
AG2-442
20.1 MW4.3%$21,562
AG2-566
6.4 MW1.4%$6,821
AG2-570
23.3 MW5.0%$25,024
AG2-571
3.0 MW0.6%$3,168
AG2-581
10.5 MW2.3%$11,289
AG2-583
32.8 MW7.0%$35,169
AH1-056
16.6 MW3.6%$17,769
AH1-241
13.8 MW3.0%$14,838
AH1-377
28.4 MW6.1%$30,476
AH1-408
8.3 MW1.8%$8,960
AH1-439
23.0 MW4.9%$24,707
AH1-528
19.4 MW4.2%$20,828
AH1-546
26.4 MW5.7%$28,317
AH1-687
22.1 MW4.8%$23,765

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2063
Title
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$418,000
Allocated Cost ($USD)
$17,747
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.7%$2,929
AG2-069
4.1 MW1.1%$4,394
AG2-077
10.3 MW2.6%$11,008
AG2-088
16.7 MW4.2%$17,747
AG2-151
13.8 MW3.5%$14,712
AG2-171
8.7 MW2.2%$9,264
AG2-188
29.6 MW7.5%$31,444
AG2-198
10.3 MW2.6%$10,919
AG2-213
8.8 MW2.2%$9,381
AG2-270
15.3 MW3.9%$16,270
AG2-338
3.0 MW0.8%$3,212
AG2-339
7.5 MW1.9%$8,031
AG2-369
2.0 MW0.5%$2,174
AG2-428
8.5 MW2.2%$9,038
AG2-436
30.4 MW7.7%$32,350
AG2-440
10.4 MW2.7%$11,108
AG2-441
13.0 MW3.3%$13,884
AG2-442
15.3 MW3.9%$16,259
AG2-566
6.4 MW1.6%$6,763
AG2-570
7.4 MW1.9%$7,857
AG2-571
3.0 MW0.8%$3,142
AG2-581
8.0 MW2.0%$8,507
AG2-583
24.9 MW6.3%$26,524
AH1-056
14.4 MW3.7%$15,298
AH1-241
13.8 MW3.5%$14,712
AH1-377
21.6 MW5.5%$22,981
AH1-408
8.3 MW2.1%$8,885
AH1-439
17.5 MW4.5%$18,634
AH1-528
14.7 MW3.7%$15,651
AH1-546
20.0 MW5.1%$21,322
AH1-687
22.2 MW5.6%$23,600

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0080
Title
Replace switch 219326 at Bremo 230 kV
Description
Replace switch 219326 at Bremo 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$16,982
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.7%$2,803
AG2-069
4.1 MW1.1%$4,205
AG2-077
10.3 MW2.6%$10,534
AG2-088
16.7 MW4.2%$16,982
AG2-151
13.8 MW3.5%$14,079
AG2-171
8.7 MW2.2%$8,865
AG2-188
29.6 MW7.5%$30,090
AG2-198
10.3 MW2.6%$10,449
AG2-213
8.8 MW2.2%$8,977
AG2-270
15.3 MW3.9%$15,569
AG2-338
3.0 MW0.8%$3,074
AG2-339
7.5 MW1.9%$7,685
AG2-369
2.0 MW0.5%$2,080
AG2-428
8.5 MW2.2%$8,649
AG2-436
30.4 MW7.7%$30,957
AG2-440
10.4 MW2.7%$10,630
AG2-441
13.0 MW3.3%$13,286
AG2-442
15.3 MW3.9%$15,559
AG2-566
6.4 MW1.6%$6,472
AG2-570
7.4 MW1.9%$7,518
AG2-571
3.0 MW0.8%$3,007
AG2-581
8.0 MW2.0%$8,140
AG2-583
24.9 MW6.3%$25,382
AH1-056
14.4 MW3.7%$14,640
AH1-241
13.8 MW3.5%$14,079
AH1-377
21.6 MW5.5%$21,991
AH1-408
8.3 MW2.1%$8,502
AH1-439
17.5 MW4.5%$17,832
AH1-528
14.7 MW3.7%$14,977
AH1-546
20.0 MW5.1%$20,404
AH1-687
22.2 MW5.6%$22,584

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2070
Title
Replace wave trap 2028WT at Fork Union 230 kV
Description
Replace wave trap 2028WT at Fork Union 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$16,041
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$4,292
AG2-069
6.2 MW1.6%$6,439
AG2-077
11.7 MW3.0%$12,195
AG2-088
15.4 MW4.0%$16,041
AG2-151
21.6 MW5.6%$22,515
AG2-188
27.6 MW7.2%$28,680
AG2-198
9.6 MW2.5%$9,973
AG2-213
7.4 MW1.9%$7,702
AG2-270
14.4 MW3.7%$14,942
AG2-338
2.8 MW0.7%$2,922
AG2-339
7.0 MW1.8%$7,304
AG2-369
0.8 MW0.2%$884
AG2-428
7.8 MW2.0%$8,144
AG2-436
28.3 MW7.4%$29,462
AG2-440
10.2 MW2.7%$10,640
AG2-441
12.8 MW3.3%$13,300
AG2-442
14.3 MW3.7%$14,895
AG2-566
5.9 MW1.5%$6,175
AG2-570
6.9 MW1.8%$7,182
AG2-571
2.8 MW0.7%$2,872
AG2-581
7.5 MW1.9%$7,769
AG2-583
23.2 MW6.0%$24,161
AH1-056
13.4 MW3.5%$13,995
AH1-217
11.3 MW2.9%$11,798
AH1-241
21.6 MW5.6%$22,515
AH1-377
20.2 MW5.2%$20,997
AH1-439
16.3 MW4.2%$16,994
AH1-528
13.7 MW3.6%$14,269
AH1-546
18.7 MW4.9%$19,435
AH1-687
20.7 MW5.4%$21,511

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2069
Title
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Description
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$15,999
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.4 MW1.1%$5,636
AG2-069
8.1 MW1.7%$8,454
AG2-077
15.4 MW3.2%$16,005
AG2-088
15.4 MW3.2%$15,999
AG2-151
28.4 MW5.9%$29,526
AG2-188
34.2 MW7.1%$35,506
AG2-198
12.6 MW2.6%$13,084
AG2-213
9.7 MW2.0%$10,104
AG2-270
14.4 MW3.0%$14,911
AG2-338
2.8 MW0.6%$2,916
AG2-339
7.0 MW1.5%$7,289
AG2-369
2.0 MW0.4%$2,042
AG2-428
9.1 MW1.9%$9,472
AG2-436
28.3 MW5.9%$29,388
AG2-440
13.4 MW2.8%$13,958
AG2-441
16.8 MW3.5%$17,448
AG2-442
18.8 MW3.9%$19,541
AG2-566
5.9 MW1.2%$6,162
AG2-570
21.8 MW4.5%$22,634
AG2-571
2.8 MW0.6%$2,865
AG2-581
9.8 MW2.0%$10,199
AG2-583
30.5 MW6.3%$31,692
AH1-056
15.5 MW3.2%$16,081
AH1-217
14.9 MW3.1%$15,470
AH1-241
27.0 MW5.6%$28,031
AH1-377
26.5 MW5.5%$27,548
AH1-439
21.5 MW4.5%$22,291
AH1-528
18.1 MW3.8%$18,786
AH1-546
24.6 MW5.1%$25,534
AH1-687
20.6 MW4.3%$21,427

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2073
Title
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$15,733
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.4 MW1.1%$5,542
AG2-069
8.1 MW1.7%$8,314
AG2-077
15.4 MW3.1%$15,739
AG2-088
15.4 MW3.1%$15,733
AG2-151
28.4 MW5.8%$29,035
AG2-171
8.1 MW1.7%$8,316
AG2-188
34.2 MW7.0%$34,915
AG2-198
12.6 MW2.6%$12,866
AG2-213
9.7 MW2.0%$9,936
AG2-270
14.4 MW2.9%$14,663
AG2-338
2.8 MW0.6%$2,868
AG2-339
7.0 MW1.4%$7,168
AG2-369
2.0 MW0.4%$2,008
AG2-428
9.1 MW1.9%$9,314
AG2-436
28.3 MW5.8%$28,899
AG2-440
13.4 MW2.7%$13,726
AG2-441
16.8 MW3.4%$17,157
AG2-442
18.8 MW3.8%$19,216
AG2-566
5.9 MW1.2%$6,060
AG2-570
21.8 MW4.5%$22,257
AG2-571
2.8 MW0.6%$2,818
AG2-581
9.8 MW2.0%$10,029
AG2-583
30.5 MW6.2%$31,165
AH1-056
15.5 MW3.2%$15,813
AH1-217
14.9 MW3.0%$15,213
AH1-241
27.0 MW5.5%$27,565
AH1-377
26.5 MW5.4%$27,090
AH1-439
21.5 MW4.4%$21,920
AH1-528
18.1 MW3.7%$18,474
AH1-546
24.6 MW5.0%$25,110
AH1-687
20.6 MW4.2%$21,071

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2071
Title
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$15,733
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.4 MW1.1%$5,542
AG2-069
8.1 MW1.7%$8,314
AG2-077
15.4 MW3.1%$15,739
AG2-088
15.4 MW3.1%$15,733
AG2-151
28.4 MW5.8%$29,035
AG2-171
8.1 MW1.7%$8,316
AG2-188
34.2 MW7.0%$34,915
AG2-198
12.6 MW2.6%$12,866
AG2-213
9.7 MW2.0%$9,936
AG2-270
14.4 MW2.9%$14,663
AG2-338
2.8 MW0.6%$2,868
AG2-339
7.0 MW1.4%$7,168
AG2-369
2.0 MW0.4%$2,008
AG2-428
9.1 MW1.9%$9,314
AG2-436
28.3 MW5.8%$28,899
AG2-440
13.4 MW2.7%$13,726
AG2-441
16.8 MW3.4%$17,157
AG2-442
18.8 MW3.8%$19,216
AG2-566
5.9 MW1.2%$6,060
AG2-570
21.8 MW4.5%$22,257
AG2-571
2.8 MW0.6%$2,818
AG2-581
9.8 MW2.0%$10,029
AG2-583
30.5 MW6.2%$31,165
AH1-056
15.5 MW3.2%$15,813
AH1-217
14.9 MW3.0%$15,213
AH1-241
27.0 MW5.5%$27,565
AH1-377
26.5 MW5.4%$27,090
AH1-439
21.5 MW4.4%$21,920
AH1-528
18.1 MW3.7%$18,474
AH1-546
24.6 MW5.0%$25,110
AH1-687
20.6 MW4.2%$21,071

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH3-DOM-007
Title
Replace Wave Trap 2028WT at Charlottesville
Description
Replace Wave Trap 2028WT at Charlottesville
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$15,708
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$4,203
AG2-069
6.2 MW1.6%$6,305
AG2-077
11.7 MW3.0%$11,942
AG2-088
15.4 MW3.9%$15,708
AG2-151
21.6 MW5.5%$22,048
AG2-171
8.1 MW2.1%$8,298
AG2-188
27.6 MW7.0%$28,085
AG2-198
9.6 MW2.4%$9,766
AG2-213
7.4 MW1.9%$7,542
AG2-270
14.4 MW3.7%$14,632
AG2-338
2.8 MW0.7%$2,862
AG2-339
7.0 MW1.8%$7,153
AG2-369
0.8 MW0.2%$865
AG2-428
7.8 MW2.0%$7,975
AG2-436
28.3 MW7.2%$28,851
AG2-440
10.2 MW2.6%$10,419
AG2-441
12.8 MW3.3%$13,024
AG2-442
14.3 MW3.6%$14,586
AG2-566
5.9 MW1.5%$6,047
AG2-570
6.9 MW1.8%$7,033
AG2-571
2.8 MW0.7%$2,813
AG2-581
7.5 MW1.9%$7,607
AG2-583
23.2 MW5.9%$23,660
AH1-056
13.4 MW3.4%$13,705
AH1-217
11.3 MW2.9%$11,553
AH1-241
21.6 MW5.5%$22,048
AH1-377
20.2 MW5.1%$20,562
AH1-439
16.3 MW4.2%$16,641
AH1-528
13.7 MW3.5%$13,973
AH1-546
18.7 MW4.8%$19,032
AH1-687
20.7 MW5.3%$21,064

System Reinforcement: n9112.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9112.0 / TC1-PH2-DOM-063
Title
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Description
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Total Cost ($USD)
$87,030,447
Allocated Cost ($USD)
$0
Time Estimate
46 to 47 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-088 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-088 could receive cost allocation. Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9265.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9265.0 / TC1-PH2-DOM-064
Title
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Description
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Total Cost ($USD)
$396,021
Allocated Cost ($USD)
$0
Time Estimate
14 to 15 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-088 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-088 could receive cost allocation. Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9199.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9199.0 / TC1-PH2-DOM-004
Title
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Description
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Total Cost ($USD)
$7,947,612
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-088 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-088 could receive cost allocation. Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Contingent

Note: Based on PJM cost allocation criteria, AG2-088 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-088 could receive cost allocation. Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-088 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-088 could receive cost allocation. Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-088 may not presently have cost responsibility for this upgrade, AG2-088 may need this upgrade in-service to be deliverable to the PJM system. If AG2-088 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
          AE2-094 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-338, AG2-339
        
          AG2-570 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-570, AG2-571
        
          Cunningham 500 kV (Dominion): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AH1-681, AH1-712, AH1-723
        
          AG2-068 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-068, AG2-069, AG2-369
        
          AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-198, AG2-566
        
          AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-440, AG2-441, AG2-442
        

Attachments

AG2-088 One Line Diagram

AG2-088 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.