AG2-112 Phase I Study Report

v1.00 released 2025-10-29 22:06

Perth 34.5 kV Substation (Circuit 404)

9.12 MW Capacity / 15.2 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Kangaroo Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Halifax County, Virginia. The installed facilities will have a total capability of 15.2 MW with 9.12 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-112
Project Name:
Perth 34.5 kV Substation (Circuit 404)
Project Developer Name:
Kangaroo Solar, LLC
State:
Virginia
County:
Halifax
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
15.2
MWE:
15.2
MWC:
9.12
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-112 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) distribution system at Perth 34.5 kV Substation circuit number 404.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-112 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-112Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$5,057,464$5,057,464
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$5,057,464$5,057,464

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-112

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-112 Project due at DP1
ABA - B
AG2-112$505,746$60,800$444,946

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

No TO Interconnection Facilities or Physical Network Upgrades are required for this project.

The costs associated with interconnecting to the Dominion distribution system will be documented in the two-party Interconnection Agreement between the Project Developer and the Transmission Owner. The Project Developer will need to coordinate with the Transmission Owner for scope, cost and schedule for this physical interconnection. This PJM report identifies the effects on the transmission system.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-112 was evaluated as a 15.2 MW (9.12 MW Capacity) injection in the Dominion area.

AG2-112 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 15.2 MW (15.2 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
BreakerAC113.77 %388.0B441.430.89
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
BreakerAC113.52 %388.0B440.440.89
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC112.07 %388.0B434.832.0
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC111.93 %388.0B434.32.0
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC109.58 %388.0B425.180.66
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P7-1_#10830___SRT-A
TowerAC104.44 %388.0B405.210.73
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
BusAC104.39 %388.0B405.030.73
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P2-2_#6212_05WLAKE 138_2_SRT-A
BusAC102.03 %388.0B395.890.73
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC121.06 %3393.4B4107.971.0
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC117.02 %3610.0B4224.551.31
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC116.77 %3610.0B4215.431.31
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC116.68 %3610.0B4211.981.31
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC116.36 %3610.0B4200.431.31
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC134.96 %245.0B330.654.9
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC134.95 %245.0B330.634.9
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 1016T1047_SRT-A
BreakerAC128.07 %245.0B313.774.9
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 101672_SRT-A
BreakerAC128.05 %245.0B313.734.9
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 104772_SRT-A
BreakerAC126.62 %245.0B310.214.9
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P1-2: LN 1047_SRT-A
SingleAC106.29 %245.0B260.43.72
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P1-2: LN 1016_SRT-A-1
SingleAC101.51 %245.0B248.713.72
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC100.25 %245.0B245.612.19
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC100.25 %245.0B245.62.19
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC136.34 %245.0B334.024.9
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC136.33 %245.0B334.04.9
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 1016T1047_SRT-A
BreakerAC129.43 %245.0B317.114.9
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 101672_SRT-A
BreakerAC129.42 %245.0B317.074.9
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 104772_SRT-A
BreakerAC127.97 %245.0B313.534.9
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P1-2: LN 1047_SRT-A
SingleAC107.67 %245.0B263.783.72
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P1-2: LN 1016_SRT-A-1
SingleAC102.87 %245.0B252.043.72
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC101.55 %245.0B248.82.19
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC101.55 %245.0B248.792.19
GD2DVP
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.3 %285.76B303.765.28
GD2DVP
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC101.67 %350.0C355.846.96
GD2DVP
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC101.31 %350.0C354.596.96
GD2DVP
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC101.3 %350.0C354.556.96
GD2DVP
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC100.59 %350.0C352.076.96
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC116.18 %285.76B331.995.28
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC112.55 %350.0C393.926.95
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC112.19 %350.0C392.676.95
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC112.18 %350.0C392.636.95
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC111.45 %350.0C390.086.96
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC109.96 %350.0C384.856.98
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC109.7 %350.0C383.946.98
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC109.69 %350.0C383.926.98
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC107.38 %285.76B306.865.24
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC105.51 %350.0C369.277.43
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P7-1_#10781___SRT-A-1
TowerAC102.7 %350.0C359.466.9
GD2DVP
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
DVP_P4-2: H2T296_SRT-A
BreakerAC130.91 %264.1C345.733.96
GD2DVP
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
DVP_P4-6: SEDGE H T452_SRT-A
BreakerAC130.8 %264.1C345.454.41
GD2DVP
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
DVP_P4-5: SEDGE H L202_SRT-A
BreakerAC130.8 %264.1C345.454.41
GD2DVP
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
DVP_P1-3: 6SEDGE HILL-TX#2_SRT-A
SingleAC101.36 %242.52B245.833.35
GD2DVP
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 3202_SRT-A
BreakerAC131.16 %276.6C362.794.4
GD2DVP
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
DVP_P4-2: H1T296_SRT-A
BreakerAC124.63 %276.6C344.733.94
GD2DVP
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
DVP_P4-5: SEDGE H L102_SRT-A
BreakerAC124.48 %276.6C344.324.4
GD2DVP
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 15102_SRT-A
BreakerAC116.84 %276.6C323.184.89
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC137.18 %245.0B336.084.9
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC137.17 %245.0B336.064.9
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 1016T1047_SRT-A
BreakerAC130.26 %245.0B319.144.9
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 101672_SRT-A
BreakerAC130.24 %245.0B319.14.9
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 104772_SRT-A
BreakerAC128.8 %245.0B315.554.9
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P1-2: LN 1047_SRT-A
SingleAC115.43 %230.3B265.843.72
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P1-2: LN 1016_SRT-A-1
SingleAC110.32 %230.3B254.073.72
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Base Case
SingleAC104.83 %156.98A164.561.61
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC102.33 %245.0B250.712.19
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC102.33 %245.0B250.72.19
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC203.13 %678.68B1378.60.53
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC158.61 %678.68B1076.480.51
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC148.82 %830.0C1235.220.68
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC117.42 %800.88B940.370.46
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC117.01 %800.88B937.120.46
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC107.32 %980.0C1051.710.61
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC107.31 %980.0C1051.630.61
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC202.03 %678.68B1371.170.53
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC157.52 %678.68B1069.030.51
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC147.93 %830.0C1227.790.68
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC131.81 %571.52B753.290.9
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC129.23 %571.52B738.580.9
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC129.16 %699.0C902.851.2
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC129.12 %699.0C902.561.2
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC125.93 %699.0C880.221.19
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC119.97 %699.0C838.611.19
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC119.97 %699.0C838.611.19
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC212.98 %699.0C1488.761.57
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC212.93 %699.0C1488.371.57
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC209.35 %699.0C1463.371.57
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC207.29 %571.52B1184.71.19
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC204.76 %571.52B1170.271.19
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC203.45 %699.0C1422.111.57
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC203.45 %699.0C1422.111.57
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC130.37 %699.0C911.290.79
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC130.23 %699.0C910.330.75
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC126.86 %699.0C886.730.78
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC118.39 %699.0C827.520.85
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Base Case
SingleAC112.79 %571.52A644.610.58
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC154.83 %1204.0C1864.160.77
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC145.18 %984.18B1428.840.47
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC119.72 %800.88B958.850.46
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC119.32 %800.88B955.60.46
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC152.97 %1204.0C1841.80.77
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC142.99 %984.18B1407.240.47
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC126.07 %830.0C1046.370.61
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC125.99 %830.0C1045.70.61
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC152.59 %1331.98B2032.490.5
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC114.83 %997.0C1144.92.85
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC108.64 %814.98B885.412.17
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC106.47 %814.98B867.672.17
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P4-2: 57062_SRT-S
BreakerAC100.2 %997.0C998.972.86
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC136.41 %830.0C1132.240.61
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC136.35 %830.0C1131.670.61
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC201.24 %684.0C1376.511.57
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC201.19 %684.0C1376.131.57
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC197.56 %684.0C1351.341.57
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC195.93 %559.3B1095.861.19
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC193.37 %559.3B1081.511.19
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC191.54 %684.0C1310.121.57
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC191.54 %684.0C1310.121.57
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC119.01 %684.0C814.050.75
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC118.81 %684.0C812.650.79
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC115.25 %684.0C788.330.78
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 115KV_SRT-A
BusAC113.26 %684.0C774.731.38
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Base Case
SingleAC101.32 %559.3A566.670.58
GD2DVP
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
DVP_P4-5: 556X2_SRT-S
BreakerAC139.23 %1050.6C1462.741.78
GD2DVP
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
DVP_P4-5: 556X1_SRT-S
BreakerAC138.76 %1053.0C1461.121.78
GD2DVP
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC113.83 %571.52B650.550.9
GD2DVP
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC111.27 %571.52B635.930.9
GD2DVP
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC109.84 %699.0C767.781.2
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC196.14 %678.68B1331.140.56
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC182.57 %830.0C1515.370.73
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC182.57 %830.0C1515.340.73
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC175.31 %830.0C1455.080.7
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC175.31 %830.0C1455.080.7
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC162.3 %678.68B1101.510.54
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC153.09 %830.0C1270.660.71
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P7-1: LN 39-91_SRT-A-2
TowerAC119.33 %830.0C990.470.64
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P2-2: DOOMS B2_SRT-A
BusAC117.39 %830.0C974.310.64
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC112.5 %830.0C933.780.61
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC108.37 %830.0C899.480.6
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC198.54 %661.76B1313.880.56
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC185.18 %809.0C1498.10.73
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC185.18 %809.0C1498.080.73
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC177.73 %809.0C1437.820.7
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC177.73 %809.0C1437.820.7
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC163.84 %661.76B1084.230.54
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC154.93 %809.0C1253.380.71
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P7-1: LN 39-91_SRT-A-2
TowerAC120.29 %809.0C973.170.64
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P2-2: DOOMS B2_SRT-A
BusAC118.3 %809.0C957.010.64
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC113.29 %809.0C916.480.61
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC109.05 %809.0C882.220.6
GD2DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S
SingleAC137.15 %1057.5B1450.330.48
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC195.13 %661.76B1291.310.56
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC182.39 %809.0C1475.570.73
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC182.39 %809.0C1475.540.73
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC174.94 %809.0C1415.270.7
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC174.94 %809.0C1415.270.7
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC160.44 %661.76B1061.70.54
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC152.15 %809.0C1230.870.71
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P7-1: LN 39-91_SRT-A-2
TowerAC117.53 %809.0C950.80.64
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P2-2: DOOMS B2_SRT-A
BusAC115.53 %809.0C934.630.64
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC110.52 %809.0C894.110.61
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC106.26 %809.0C859.670.6
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC126.02 %830.0C1045.980.61
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC125.95 %830.0C1045.350.61
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC139.4 %830.0C1156.990.61
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC139.34 %830.0C1156.560.61
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC109.79 %997.0C1094.572.85
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC103.53 %814.98B843.752.17
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC101.35 %814.98B825.972.17
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC108.88 %1105.0C1203.123.68
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC106.72 %1105.0C1179.243.67
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC106.7 %1105.0C1179.053.67
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC104.45 %1105.0C1154.153.69
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC104.44 %1105.0C1154.093.69
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC140.61 %1478.62B2079.090.5
GD2DVP
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 9344_SRT-A
SingleAC106.63 %3256.16B3472.071.08
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC139.66 %3220.44B4497.831.39
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 56272_SRT-S
BreakerAC131.96 %3118.0C4114.651.68
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 567_SRT-A
SingleAC130.02 %3220.44B4187.081.34
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
SingleAC105.09 %3220.44A3384.281.17
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: LN 158-235_SRT-A
TowerAC104.32 %3940.0C4110.111.69
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC132.78 %4070.2B5404.521.09
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC123.02 %4070.2B5007.081.07
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC146.98 %2442.12B3589.451.06
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC145.46 %2442.12B3552.31.05
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC173.01 %4070.2B7041.781.68
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC153.9 %4070.2B6264.01.42
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Base Case
SingleAC118.98 %4070.2A4842.751.05
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC126.22 %4070.2B5137.221.1
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC124.64 %4070.2B5073.151.06
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC175.45 %3220.44B5650.141.55
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC136.69 %3220.44B4402.071.36
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Base Case
SingleAC113.34 %3193.18A3619.131.19
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC147.45 %3220.44B4748.60.91
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC172.64 %3220.44B5559.881.15
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC171.66 %3220.44B5528.271.17
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC139.73 %4070.2B5687.332.08
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC133.78 %4070.2B5445.282.08
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 58572_SRT-A
BreakerAC124.04 %4996.0C6196.952.74
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-5: W72_SRT-A
BreakerAC123.43 %4996.0C6166.562.73
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: XT585_SRT-S
BreakerAC114.16 %4996.0C5703.662.74
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 54472_SRT-S
BreakerAC111.74 %2858.0C3193.491.93
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC123.06 %4070.2B5008.651.87
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC109.25 %4996.0C5458.062.46
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC108.79 %4996.0C5435.072.46
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC107.19 %4996.0C5355.192.43
GD2DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC103.87 %2931.0C3044.371.22
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC179.85 %3220.44B5791.821.15
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC175.06 %3220.44B5637.71.13
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC126.47 %2442.12B3088.520.95
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC113.0 %1105.0C1248.613.67
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC110.45 %1105.0C1220.463.66
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC110.42 %1105.0C1220.193.66
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC108.84 %1105.0C1202.693.69
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC108.84 %1105.0C1202.633.69
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC103.96 %903.34B939.112.79
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC102.05 %903.34B921.892.79
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC118.6 %285.76B338.915.28
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC114.54 %350.0C400.886.95
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC114.18 %350.0C399.636.95
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC114.17 %350.0C399.596.95
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC113.44 %350.0C397.056.96
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC111.95 %350.0C391.836.98
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC111.69 %350.0C390.936.98
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC111.69 %350.0C390.916.98
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC109.82 %285.76B313.835.24
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC107.51 %350.0C376.287.43
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P7-1_#10781___SRT-A-1
TowerAC104.72 %350.0C366.516.9
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P2-2_#17572_05MUSEVILLE 138_1_SRT-A
BusAC100.61 %350.0C352.156.99
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC239.46 %541.0B1295.463.67
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC234.05 %541.0B1266.233.66
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC234.0 %541.0B1265.963.66
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC231.01 %541.0B1249.793.68
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC231.0 %541.0B1249.743.68
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC192.41 %508.54B978.462.79
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC189.13 %508.54B961.812.79
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC102.04 %541.0B552.012.63
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC125.65 %800.88B1006.310.46
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC125.22 %800.88B1002.880.46
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC136.1 %4070.2B5539.411.87
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC120.36 %4996.0C6013.112.46
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC119.82 %4996.0C5986.292.46
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC118.15 %4996.0C5902.92.43
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC117.76 %571.52B673.040.9
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC115.2 %571.52B658.380.9
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC114.07 %699.0C797.371.2
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC114.03 %699.0C797.081.2
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC110.84 %699.0C774.791.19
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
BreakerAC114.79 %392.0B450.00.89
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
BreakerAC114.54 %392.0B449.010.89
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC113.11 %392.0B443.412.0
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC112.98 %392.0B442.882.0
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC110.67 %392.0B433.830.66
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P7-1_#10830___SRT-A
TowerAC105.56 %392.0B413.780.73
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
BusAC105.51 %392.0B413.60.73
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P2-2_#6212_05WLAKE 138_2_SRT-A
BusAC103.18 %392.0B404.450.73
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC211.67 %684.0C1447.791.57
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC211.61 %684.0C1447.41.57
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC207.99 %684.0C1422.621.57
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC206.17 %559.3B1153.121.19
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC203.59 %559.3B1138.681.19
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC201.95 %684.0C1381.351.57
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC201.95 %684.0C1381.351.57
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC128.21 %684.0C876.960.75
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC128.06 %684.0C875.950.79
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC124.48 %684.0C851.470.78
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC115.8 %684.0C792.060.85
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Base Case
SingleAC110.37 %559.3A617.320.58
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC132.79 %571.52B758.930.9
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC130.22 %571.52B744.240.9
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC129.97 %699.0C908.51.2
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC129.93 %699.0C908.211.2
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC126.73 %699.0C885.861.19
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC120.78 %699.0C844.271.19
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC120.78 %699.0C844.271.19
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC129.2 %4070.2B5258.721.87
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC114.25 %4996.0C5708.122.46
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC113.76 %4996.0C5683.442.46
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC112.13 %4996.0C5601.82.43
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC120.99 %800.88B969.010.46
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC120.59 %800.88B965.750.46
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC109.29 %285.76B312.325.28
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC104.12 %350.0C364.426.96
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC103.76 %350.0C363.166.96
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC103.75 %350.0C363.126.96
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC103.04 %350.0C360.646.96
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC101.53 %350.0C355.376.98
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC101.27 %350.0C354.466.98
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC101.27 %350.0C354.446.98
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC100.5 %285.76B287.195.25
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC127.24 %571.52B727.20.9
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC124.67 %571.52B712.520.9
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC124.28 %699.0C868.711.2
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC124.24 %699.0C868.411.2
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC121.04 %699.0C846.091.19
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC115.09 %699.0C804.511.19
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC115.09 %699.0C804.511.19
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC218.2 %684.0C1492.51.57
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC218.14 %684.0C1492.111.57
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC214.52 %684.0C1467.341.57
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC212.24 %559.3B1187.041.19
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC209.65 %559.3B1172.591.19
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC208.48 %684.0C1426.031.57
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC208.48 %684.0C1426.031.57
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC134.05 %684.0C916.910.75
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC133.94 %684.0C916.120.79
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC130.34 %684.0C891.540.78
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC121.65 %684.0C832.110.85
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Base Case
SingleAC115.81 %559.3A647.70.58
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC219.98 %699.0C1537.651.57
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC219.92 %699.0C1537.261.57
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC216.35 %699.0C1512.311.57
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC213.74 %571.52B1221.61.19
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC211.19 %571.52B1206.971.19
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC210.43 %699.0C1470.91.57
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC210.43 %699.0C1470.91.57
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC137.05 %699.0C957.970.79
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC136.87 %699.0C956.690.75
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC133.52 %699.0C933.310.78
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC125.05 %699.0C874.10.85
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Base Case
SingleAC118.94 %571.52A679.770.58

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P4_#10213_05CLOVRD 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.77 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:441.43
MW Contribution:0.89
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
1.01
970165AG2-112 GEN
Solar/Wind Harmer
0.889
970163AG2-111 GEN
Solar/Wind Harmer
0.849
270455AD2-022 GEN
Solar/Wind Helper
0.935
270457AD2-023 GEN
Solar/Wind Helper
0.616
24684605SMG4
50/50
3.133
24728405LEESVG
50/50
0.336
270197AD1-017 GEN1
Solar/Wind Harmer
6.655
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
8.005
958131AF2-107 GEN
Solar/Wind Harmer
2.397
24684405SMG2
50/50
3.112
24684505SMG3
50/50
1.925
24684305SMG1
50/50
1.128
270013AE1-250 PV
Solar/Wind Harmer
12.518
316217AC1-145 GEN
Solar/Wind Harmer
3.465
316197AC1-042 GEN
Solar/Wind Harmer
2.627
942671AE2-283 GEN
Solar/Wind Harmer
7.071
942751AE2-291 GEN
Solar/Wind Harmer
7.417
24684705SMG5
50/50
1.198
970481AG2-311 GEN
50/50
16.703
24728405LEESVG
50/50
0.334
3151561HALLBR1
50/50
0.448
970223AG2-152 GEN
Solar/Wind Harmer
78.334
270016AE1-250 BESS
Solar/Wind Harmer
12.518
270574AD1-017 GEN2
Solar/Wind Harmer
22.147
270173AC1-122 GEN
Solar/Wind Harmer
3.243
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
8.005
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.228
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.589
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.768
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.079
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.234
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.225
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P4_#10210_05CLOVRD 138_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.52 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:440.44
MW Contribution:0.89
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
1.197
970481AG2-311 GEN
50/50
16.68
24728405LEESVG
50/50
0.334
3151561HALLBR1
50/50
0.448
970223AG2-152 GEN
Solar/Wind Harmer
78.303
270016AE1-250 BESS
Solar/Wind Harmer
12.513
270574AD1-017 GEN2
Solar/Wind Harmer
22.132
270173AC1-122 GEN
Solar/Wind Harmer
3.239
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
7.991
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.215
316123AC1-075 GEN
Solar/Wind Harmer
1.008
970165AG2-112 GEN
Solar/Wind Harmer
0.887
970163AG2-111 GEN
Solar/Wind Harmer
0.846
270455AD2-022 GEN
Solar/Wind Helper
0.937
270457AD2-023 GEN
Solar/Wind Helper
0.617
24684405SMG2
50/50
3.108
24684505SMG3
50/50
1.922
24684305SMG1
50/50
1.127
270013AE1-250 PV
Solar/Wind Harmer
12.513
316217AC1-145 GEN
Solar/Wind Harmer
3.459
316197AC1-042 GEN
Solar/Wind Harmer
2.622
942671AE2-283 GEN
Solar/Wind Harmer
7.059
942751AE2-291 GEN
Solar/Wind Harmer
7.401
24684605SMG4
50/50
3.128
24728405LEESVG
50/50
0.335
270197AD1-017 GEN1
Solar/Wind Harmer
6.65
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
7.991
958131AF2-107 GEN
Solar/Wind Harmer
2.391
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.59
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.771
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.078
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.237
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.226
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.07 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:434.83
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
2.274
970165AG2-112 GEN
Solar/Wind Harmer
2.002
970163AG2-111 GEN
Solar/Wind Harmer
1.91
970865AG2-541 GEN
Solar/Wind Harmer
8.563
270455AD2-022 GEN
Solar/Wind Helper
1.103
270457AD2-023 GEN
Solar/Wind Helper
0.727
24684605SMG4
50/50
2.515
24728405LEESVG
50/50
0.292
270197AD1-017 GEN1
Solar/Wind Harmer
6.03
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
8.047
971683AH1-343 GEN
Solar/Wind Harmer
9.09
958131AF2-107 GEN
Solar/Wind Harmer
2.414
316283AC2-100 C
Solar/Wind Helper
0.6
943811AF1-049 GEN
Solar/Wind Helper
0.69
24684405SMG2
50/50
2.499
24684505SMG3
50/50
1.545
24684305SMG1
50/50
0.906
270013AE1-250 PV
Solar/Wind Harmer
11.82
316217AC1-145 GEN
Solar/Wind Harmer
3.483
316197AC1-042 GEN
Solar/Wind Harmer
2.64
942671AE2-283 GEN
Solar/Wind Harmer
7.108
942751AE2-291 GEN
Solar/Wind Harmer
13.438
316222AC1-221 GEN
Solar/Wind Helper
0.638
24684705SMG5
50/50
0.962
970481AG2-311 GEN
50/50
13.411
24728405LEESVG
50/50
0.291
3151561HALLBR1
50/50
0.484
970223AG2-152 GEN
Solar/Wind Harmer
74.821
270016AE1-250 BESS
Solar/Wind Harmer
11.82
270574AD1-017 GEN2
Solar/Wind Harmer
20.069
270173AC1-122 GEN
Solar/Wind Harmer
2.676
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
8.047
3147123OTTER R
Solar/Wind Harmer
-0.013
316003AC1-222 GEN
Solar/Wind Harmer
2.058
962751AG1-124 GEN
Solar/Wind Harmer
5.305
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.72
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.52
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
0.005
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.563
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.93 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:434.3
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
2.275
970865AG2-541 GEN
Solar/Wind Harmer
8.564
970165AG2-112 GEN
Solar/Wind Harmer
2.003
970163AG2-111 GEN
Solar/Wind Harmer
1.91
270455AD2-022 GEN
Solar/Wind Helper
1.103
270457AD2-023 GEN
Solar/Wind Helper
0.727
24684605SMG4
50/50
2.515
24728405LEESVG
50/50
0.292
270197AD1-017 GEN1
Solar/Wind Harmer
6.031
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
8.047
971683AH1-343 GEN
Solar/Wind Harmer
9.091
958131AF2-107 GEN
Solar/Wind Harmer
2.414
316283AC2-100 C
Solar/Wind Helper
0.599
943811AF1-049 GEN
Solar/Wind Helper
0.69
24684405SMG2
50/50
2.499
24684505SMG3
50/50
1.546
24684305SMG1
50/50
0.906
270013AE1-250 PV
Solar/Wind Harmer
11.821
316217AC1-145 GEN
Solar/Wind Harmer
3.483
316197AC1-042 GEN
Solar/Wind Harmer
2.64
942671AE2-283 GEN
Solar/Wind Harmer
7.108
24684705SMG5
50/50
0.962
970481AG2-311 GEN
50/50
13.412
24728405LEESVG
50/50
0.291
3151561HALLBR1
50/50
0.484
970223AG2-152 GEN
Solar/Wind Harmer
74.825
270016AE1-250 BESS
Solar/Wind Harmer
11.821
270574AD1-017 GEN2
Solar/Wind Harmer
20.07
270173AC1-122 GEN
Solar/Wind Harmer
2.677
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
8.047
3147123OTTER R
Solar/Wind Harmer
-0.013
316003AC1-222 GEN
Solar/Wind Harmer
2.058
962751AG1-124 GEN
Solar/Wind Harmer
5.305
942751AE2-291 GEN
Solar/Wind Harmer
13.439
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.719
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.517
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
0.006
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.562
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.58 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:425.18
MW Contribution:0.66
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
2.437
24728405LEESVG
50/50
0.264
270197AD1-017 GEN1
Solar/Wind Harmer
5.979
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.442
316123AC1-075 GEN
Solar/Wind Harmer
0.751
970165AG2-112 GEN
Solar/Wind Harmer
0.661
970163AG2-111 GEN
Solar/Wind Harmer
0.63
270455AD2-022 GEN
Solar/Wind Helper
1.03
270457AD2-023 GEN
Solar/Wind Helper
0.678
24684705SMG5
50/50
0.932
970481AG2-311 GEN
50/50
12.994
24728405LEESVG
50/50
0.263
3151561HALLBR1
50/50
0.36
970223AG2-152 GEN
Solar/Wind Harmer
74.853
270016AE1-250 BESS
Solar/Wind Harmer
11.803
270574AD1-017 GEN2
Solar/Wind Harmer
19.897
270173AC1-122 GEN
Solar/Wind Harmer
2.59
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.442
3147123OTTER R
Solar/Wind Harmer
-0.009
962751AG1-124 GEN
Solar/Wind Harmer
5.14
958131AF2-107 GEN
Solar/Wind Harmer
2.282
24684405SMG2
50/50
2.421
24684505SMG3
50/50
1.497
24684305SMG1
50/50
0.878
270013AE1-250 PV
Solar/Wind Harmer
11.803
316217AC1-145 GEN
Solar/Wind Harmer
2.788
316197AC1-042 GEN
Solar/Wind Harmer
2.114
942671AE2-283 GEN
Solar/Wind Harmer
5.691
942751AE2-291 GEN
Solar/Wind Harmer
5.679
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.539
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.087
MECLTFEXP_MEC->PJM
CLTF
0.24
SIGELTFEXP_SIGE->PJM
CLTF
0.011
NYPJM->LTFIMP_NY
CLTF
0.163
LGEELTFEXP_LGEE->PJM
CLTF
0.191
WECLTFEXP_WEC->PJM
CLTF
0.083
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.268
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P7-1_#10830___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10830___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.44 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:405.21
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
0.835
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P2-2_#6213_05WLAKE 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.39 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:405.03
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
0.835
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P2-2_#6212_05WLAKE 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6212_05WLAKE 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.03 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:395.89
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
316123AC1-075 GEN
Solar/Wind Harmer
0.835
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4107.97
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
14.457
971277AH1-098 GEN
Solar/Wind Harmer
5.177
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.796
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
0.006
971225AH1-072 GEN
Solar/Wind Harmer
1.905
971227AH1-073 GEN
Solar/Wind Harmer
1.905
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
7.887
966021AG1-471 GEN
Solar/Wind Harmer
4.013
971485AH1-239 GEN
Solar/Wind Harmer
5.928
960161AF2-307 GEN
Solar/Wind Harmer
4.775
339255AE2-071 GEN
Solar/Wind Harmer
-0.119
964781AG1-341 GEN
Solar/Wind Harmer
7.653
971081AG2-670 GEN
Solar/Wind Harmer
5.396
942891AE2-308 GEN
Solar/Wind Harmer
7.099
970653AG2-424 GEN
Solar/Wind Harmer
3.405
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
6.361
971125AH1-004 GEN
Solar/Wind Harmer
2.777
970107AG2-081 GEN
Solar/Wind Harmer
2.083
972043AH1-570 GEN
Solar/Wind Harmer
1.796
972045AH1-571 GEN
Solar/Wind Harmer
1.439
339221AD2-048_GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
4.126
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970239AG2-162 GEN
Solar/Wind Harmer
1.663
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.8
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25183208HLCRTG
Solar/Wind Harmer
0.01
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.958
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
971073AG2-665 GEN
Solar/Wind Harmer
5.761
945391AF1-204 GEN
Solar/Wind Harmer
6.765
276916AD2-100_GEN
Solar/Wind Harmer
13.364
276911AD2-131_GEN
Solar/Wind Harmer
0.88
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.651
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
960251AF2-316 GEN
Solar/Wind Harmer
8.583
960201AF2-311 GEN
Solar/Wind Harmer
5.708
960611AF2-352 GEN
Solar/Wind Harmer
2.073
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.22
276708O09 GEN2
Solar/Wind Harmer
0.22
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.243
276646AC1-214 GEN2
Solar/Wind Harmer
0.243
972267AH1-718 GEN
Adder
3.688
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
12.893
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270173AC1-122 GEN
Solar/Wind Harmer
0.677
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.175
941801AE2-185 GEN
Solar/Wind Harmer
7.452
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.542
270030AE2-140 GEN
Solar/Wind Harmer
21.578
960911AF2-382 GEN
Solar/Wind Harmer
7.638
270016AE1-250 BESS
Solar/Wind Harmer
0.006
970913AG2-568 GEN
Solar/Wind Harmer
7.677
971461AH1-227 GEN
Solar/Wind Harmer
4.886
970223AG2-152 GEN
Solar/Wind Harmer
12.358
270053AF1-130 C
Solar/Wind Harmer
2.047
972103AH1-617 GEN
Solar/Wind Harmer
18.024
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.425
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
8.427
962251AG1-071 GEN
Solar/Wind Harmer
4.496
966571AG1-526 GEN
Solar/Wind Harmer
15.967
970093AG2-073 GEN
Solar/Wind Harmer
7.166
960741AF2-365 GEN
Solar/Wind Harmer
3.563
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
18.055
972167AH1-666 GEN
Solar/Wind Harmer
5.419
958171AF2-111 GEN
Solar/Wind Harmer
16.681
970243AG2-164 GEN
Solar/Wind Harmer
3.891
970519AG2-331 GEN
Solar/Wind Harmer
17.292
970699AG2-449 GEN
Solar/Wind Harmer
1.663
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
9.55
942481AE2-261 GEN
Solar/Wind Harmer
18.997
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.231
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.229
971993AH1-541 GEN
Solar/Wind Harmer
2.905
270356AE2-297 GEN
Solar/Wind Harmer
0.008
253406AD2-031_GEN
Solar/Wind Harmer
0.467
270222AC2-111 GEN
Solar/Wind Harmer
3.158
965931AG1-462 GEN
Solar/Wind Harmer
15.879
270291AC1-194 GEN
Solar/Wind Harmer
4.924
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
18.654
959611AF2-252 GEN
Solar/Wind Harmer
2.073
942111AE2-223 GEN
Solar/Wind Harmer
2.013
274878BISHOP HL;2U
Solar/Wind Harmer
0.208
276157O29GEN1
Solar/Wind Harmer
0.999
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
270437AC2-090 C
Solar/Wind Harmer
0.003
970571AG2-364 GEN
Solar/Wind Harmer
12.296
253415AE1-040 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
1.93
24755605MDL-5G
Solar/Wind Harmer
0.001
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
4.886
971329AH1-144 GEN
Solar/Wind Harmer
11.568
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.429
270336AE1-100 GEN
Solar/Wind Harmer
0.006
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
0.004
958131AF2-107 GEN
Solar/Wind Harmer
5.339
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
0.948
971403AH1-188 GEN
Solar/Wind Harmer
13.153
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
1.695
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
0.249
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
7.218
964901AG1-354 GEN
Solar/Wind Harmer
10.814
962241AG1-070 GEN
Solar/Wind Harmer
3.92
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
1.396
339216AC1-074 GEN
Solar/Wind Harmer
0.187
945681AF1-233 GEN
Solar/Wind Harmer
12.782
927014AC1-188 GEN
Solar/Wind Harmer
0.004
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
4.755
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
0.295
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.331
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
0.066
963831AG1-236 GEN
Solar/Wind Harmer
2.455
274880W4-005 GEN4
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.811
972175AH1-670 GEN
Solar/Wind Harmer
5.171
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.673
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.208
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.519
276903AD2-071 C
Solar/Wind Harmer
6.874
971475AH1-234 GEN
Solar/Wind Harmer
2.986
970819AG2-516 GEN
Solar/Wind Harmer
7.379
970569AG2-363 GEN
Solar/Wind Harmer
18.444
972235AH1-702 GEN1
Adder
2.22
24791305MDL-5G
Solar/Wind Harmer
0.001
274822ROCKFORD ;11
Adder
17.275
957471AF2-041 GEN
Solar/Wind Harmer
18.409
959081AF2-199 GEN
Solar/Wind Harmer
6.136
971067AG2-660 GEN
Solar/Wind Harmer
2.045
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.11
970291AG2-192 GEN
Solar/Wind Harmer
0.796
971997AH1-543 GEN
Solar/Wind Harmer
3.211
270032AE2-172
Solar/Wind Harmer
4.079
270263AC1-001 GEN
Solar/Wind Harmer
0.614
274872LEEDK;1U
Solar/Wind Harmer
0.004
270005AE1-210 C O1
Solar/Wind Harmer
1.324
965031AG1-367 GEN
Solar/Wind Harmer
6.111
962781AG1-127 GEN
Solar/Wind Harmer
5.815
276901AD2-066 C O1
Solar/Wind Harmer
0.006
939401AE1-172 GEN
Solar/Wind Harmer
4.568
970825AG2-519 GEN
Solar/Wind Harmer
2.167
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
276691AA1-018 GEN1
Solar/Wind Harmer
0.737
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
1.993
270069AE2-166 C O1
Solar/Wind Harmer
0.008
971313AH1-133 GEN
Solar/Wind Harmer
10.952
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
2.892
270400AC1-102 GEN
Solar/Wind Harmer
2.892
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
970281AG2-184 GEN
Solar/Wind Harmer
18.925
972143AH1-644 GEN
Solar/Wind Harmer
9.763
971981AH1-535 GEN
Solar/Wind Harmer
5.843
971061AG2-657 GEN
Solar/Wind Harmer
5.368
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
965401AG1-405 GEN
Solar/Wind Harmer
4.227
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
4.677
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
7.568
972165AH1-665 GEN
Solar/Wind Harmer
6.061
971985AH1-537 GEN
Solar/Wind Harmer
2.011
270367AC2-061_GEN
Solar/Wind Harmer
0.005
316123AC1-075 GEN
Solar/Wind Harmer
0.168
970165AG2-112 GEN
Solar/Wind Harmer
0.998
970163AG2-111 GEN
Solar/Wind Harmer
0.952
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
5.761
944221AF1-090 GEN
Solar/Wind Harmer
3.754
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.229
276848AB2-070 GEN3
Solar/Wind Harmer
0.228
963841AG1-237 GEN
Solar/Wind Harmer
2.698
946321AF1-296 GEN
Solar/Wind Harmer
3.483
270340AC2-060 GEN
Solar/Wind Harmer
0.007
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.505
941731AE2-173 GEN
Solar/Wind Harmer
5.162
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.204
961011AF2-392 GEN
Solar/Wind Harmer
3.623
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
9.917
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.045
970169AG2-114 GEN
Solar/Wind Harmer
6.149
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
3.491
274856ECOGROVE ;U1
Solar/Wind Harmer
0.145
276611AD2-172 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
12.273
971343AH1-151 GEN
Solar/Wind Harmer
12.273
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
12.256
971335AH1-147 GEN
Solar/Wind Harmer
12.256
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.834
971613AH1-306 GEN
Solar/Wind Harmer
2.937
274879MINONK ;1U
Solar/Wind Harmer
0.258
970921AG2-575 GEN
Solar/Wind Harmer
6.111
970921AG2-575 GEN
Solar/Wind Harmer
2.037
962691AG1-118 GEN
Solar/Wind Harmer
18.322
958491AF2-143 GEN
Solar/Wind Harmer
9.158
960441AF2-335 GEN
Solar/Wind Harmer
6.106
970825AG2-519 GEN
Solar/Wind Harmer
6.767
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.824
958481AF2-142 GEN
Solar/Wind Harmer
9.131
971573AH1-285 GEN
Solar/Wind Harmer
1.134
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.15
971171AH1-044 GEN
Solar/Wind Harmer
12.273
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
2.39
971411AH1-196 GEN
Solar/Wind Harmer
9.19
970289AG2-191 GEN
Solar/Wind Harmer
1.163
971177AH1-047 GEN
Solar/Wind Harmer
3.774
270594AE1-207 GEN
Solar/Wind Harmer
6.853
276868AE1-113 GEN
Solar/Wind Harmer
1.227
276882AE2-255 GEN
Solar/Wind Harmer
0.715
970115AG2-085 GEN
Solar/Wind Harmer
2.442
971673AH1-337 GEN
Solar/Wind Harmer
3.956
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
971029AG2-637 GEN
Solar/Wind Harmer
2.803
970781AG2-491 GEN
Solar/Wind Harmer
6.144
959091AF2-200 GEN
Solar/Wind Harmer
12.273
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.225
274850MENDOTA H;RU
Solar/Wind Harmer
0.072
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.11
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.654
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
970291AG2-192 GEN
Solar/Wind Harmer
0.612
274872LEEDK;1U
Solar/Wind Harmer
0.224
958821AF2-173 GEN
Solar/Wind Harmer
8.556
270004AE1-209 GEN
Solar/Wind Harmer
1.324
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
15.703
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
946031AF1-268 GEN
Solar/Wind Harmer
5.79
943121AE2-341 GEN
Solar/Wind Harmer
10.192
943591AF1-030 GEN
Solar/Wind Harmer
6.778
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.02 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4224.55
MW Contribution:1.31
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.278
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.241
966251AG1-494 GEN
50/50
4.391
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.012
971329AH1-144 GEN
Solar/Wind Harmer
23.734
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.82
270197AD1-017 GEN1
Solar/Wind Harmer
2.549
270336AE1-100 GEN
Solar/Wind Harmer
2.762
943811AF1-049 GEN
Solar/Wind Harmer
5.705
24728305BUCHG2
Adder
6.772
270018AE2-047 C O1
Solar/Wind Harmer
1.828
958131AF2-107 GEN
Solar/Wind Harmer
7.112
24735205WLF2G2
Adder
8.049
971687AH1-348 GEN
Solar/Wind Harmer
1.364
971403AH1-188 GEN
Solar/Wind Harmer
18.932
24723205RIVRG3
Adder
23.068
971315AH1-136 GEN
Solar/Wind Harmer
2.441
24686105CER G3
Adder
9.94
24686505CER G6
Adder
9.927
270331AC1-082 GEN3
Solar/Wind Harmer
0.49
970947AG2-589 GEN
Solar/Wind Harmer
2.153
24721705FLATG2
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
2.594
971821AH1-427 GEN
Solar/Wind Harmer
10.401
964901AG1-354 GEN
Solar/Wind Harmer
15.577
960001AF2-291 GEN
Solar/Wind Harmer
3.136
339241AF1-083 GEN
Solar/Wind Harmer
1.723
962241AG1-070 GEN
Solar/Wind Harmer
4.662
3429241JKCT 3G
Adder
12.097
3429421JKCT 10G
Adder
8.45
971565AH1-281 GEN
Solar/Wind Harmer
2.012
943111AE2-339 GEN
Solar/Wind Harmer
0.888
339216AC1-074 GEN
Solar/Wind Harmer
1.659
945681AF1-233 GEN
Solar/Wind Harmer
18.436
927014AC1-188 GEN
Solar/Wind Harmer
1.543
970091AG2-072 GEN
Adder
74.457
970333AG2-219 GEN
Solar/Wind Harmer
30.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.271
25196808ZIMRHP
Adder
71.09
252507AC2-088 GEN
Solar/Wind Harmer
1.681
25196008MFTGT1
Adder
1.302
25194608D.CRK4
Adder
1.519
965911AG1-460 GEN
Solar/Wind Harmer
1.278
253432AC1-085 GEN2
Solar/Wind Harmer
0.245
946171AF1-282 GEN
Solar/Wind Harmer
9.139
24728605AND G2
Adder
3.502
276615X2-022 GEN
Solar/Wind Harmer
1.783
963831AG1-236 GEN
Solar/Wind Harmer
8.931
274880W4-005 GEN4
Solar/Wind Harmer
2.743
963741AG1-226 GEN
Solar/Wind Harmer
40.621
274761LEE CO EC;2U
Adder
8.273
274766LEE CO EC;7U
Adder
8.175
972235AH1-702 GEN1
Adder
2.234
274822ROCKFORD ;11
Adder
17.383
274828WAUKEGAN ;BP
Adder
9.716
274682WAUKEGAN ;7U
Adder
15.803
274745AC1-111 GEN9
Adder
4.901
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
315616AA1-038_C
Solar/Wind Helper
3.295
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.727
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.628
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.388
23583801GRNGAP
Solar/Wind Helper
4.315
316095T157 G97
Solar/Wind Helper
1.133
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.355
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316044AC1-158 PL1
Solar/Wind Helper
1.263
316450AC1-158 RIC
Solar/Wind Helper
0.337
316473AC1-191 GEN
Solar/Wind Helper
1.391
972175AH1-670 GEN
Solar/Wind Harmer
4.749
971543AH1-269 GEN
50/50
12.267
966391AG1-508 GEN
Solar/Wind Harmer
6.388
270069AE2-166 C O1
Solar/Wind Harmer
4.514
971313AH1-133 GEN
Solar/Wind Harmer
15.745
24734705WLF1G3
Adder
8.22
24734805WLF1G4
Adder
8.22
24734905WLF1G5
Adder
8.22
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.049
270399AC1-101 GEN
Solar/Wind Harmer
5.58
270400AC1-102 GEN
Solar/Wind Harmer
5.58
941621AE2-160 GEN
Adder
4.308
957241AF2-018 GEN
Solar/Wind Harmer
5.782
970281AG2-184 GEN
Solar/Wind Harmer
27.237
972143AH1-644 GEN
Solar/Wind Harmer
12.97
971981AH1-535 GEN
Solar/Wind Harmer
12.604
962211AG1-066 GEN
Solar/Wind Harmer
3.014
971061AG2-657 GEN
Solar/Wind Harmer
11.059
24477305BRIDGE
Adder
0.422
972203AH1-686 GEN
Adder
2.718
270330AC1-082 GEN2
Solar/Wind Harmer
0.83
270329AC1-082 GEN1
Solar/Wind Harmer
0.489
965401AG1-405 GEN
Solar/Wind Harmer
6.089
965411AG1-406 GEN
Solar/Wind Harmer
2.733
339211AE2-254 GEN
Solar/Wind Harmer
1.572
3429211JKCT 2G
Adder
11.941
970455AG2-298 GEN
Solar/Wind Harmer
6.067
339243AC2-075 GEN1
Solar/Wind Harmer
0.449
972163AH1-664 GEN
Solar/Wind Harmer
9.805
972165AH1-665 GEN
Solar/Wind Harmer
7.844
971985AH1-537 GEN
Solar/Wind Harmer
17.415
270367AC2-061_GEN
Solar/Wind Harmer
3.029
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.435
25196108MFTGT2
Adder
1.332
970879AG2-548 GEN
Solar/Wind Harmer
3.978
944221AF1-090 GEN
Solar/Wind Harmer
10.083
252524AE2-267 GEN
Solar/Wind Harmer
1.454
25196408WSDLE3
Adder
8.135
25196308WSDLE2
Adder
8.064
25196208WSDLE1
Adder
8.044
25196708WSDLE6
Adder
8.024
25196508WSDLE4
Adder
7.822
276785W4-005 GEN1
Solar/Wind Harmer
2.743
276174W4-005 GEN2
Solar/Wind Harmer
2.743
276849AB2-070 GEN2
Solar/Wind Harmer
2.04
276848AB2-070 GEN3
Solar/Wind Harmer
2.04
274823ROCKFORD ;21
Adder
17.257
274746AC1-111 G10
Adder
4.901
274744AC1-111 GEN8
Adder
4.901
25306009OHH W.
Adder
2.523
253372AE2-315 SEC3
Adder
1.658
253372AE2-315 SEC3
Adder
1.658
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.177
238152AF2-075_GEN
Solar/Wind Helper
0.605
316312AB1-027
Solar/Wind Helper
0.425
3141426STAFORD
Solar/Wind Helper
0.049
24290605CLAY-1
50/50
0.256
24290605CLAY-1
50/50
0.256
24290705CLAY-2
50/50
0.256
24290705CLAY-2
50/50
0.256
24684405SMG2
50/50
2.226
24684505SMG3
50/50
1.377
24684305SMG1
50/50
0.807
270583AD2-179 GEN
Solar/Wind Harmer
20.758
270214AC2-123 GEN
Solar/Wind Harmer
4.319
971277AH1-098 GEN
Solar/Wind Harmer
7.435
316217AC1-145 GEN
Solar/Wind Harmer
4.25
316197AC1-042 GEN
Solar/Wind Harmer
3.222
942671AE2-283 GEN
Solar/Wind Harmer
8.674
24728205BUCHG1
Adder
6.772
270013AE1-250 PV
Solar/Wind Harmer
3.259
971225AH1-072 GEN
Solar/Wind Harmer
2.74
971227AH1-073 GEN
Solar/Wind Harmer
2.74
944971AF1-162 GEN
Solar/Wind Harmer
9.108
24723005RIVRG1
Adder
23.068
24723105RIVRG2
Adder
23.068
24685805CER G1
Adder
9.875
24685905CER G2
Adder
9.875
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.779
971485AH1-239 GEN
Solar/Wind Harmer
8.537
339231AF1-038_GEN
Solar/Wind Harmer
1.927
960161AF2-307 GEN
Solar/Wind Harmer
6.695
339255AE2-071 GEN
Solar/Wind Harmer
1.104
964781AG1-341 GEN
Solar/Wind Harmer
11.023
339236AF1-050_GEN
Solar/Wind Harmer
1.882
971081AG2-670 GEN
Solar/Wind Harmer
7.773
942891AE2-308 GEN
Solar/Wind Harmer
10.233
970653AG2-424 GEN
Solar/Wind Harmer
4.906
970653AG2-424 GEN
Solar/Wind Harmer
1.774
964571AG1-320 GEN
Solar/Wind Harmer
8.231
971125AH1-004 GEN
Solar/Wind Harmer
4.003
970107AG2-081 GEN
Solar/Wind Harmer
3.003
972043AH1-570 GEN
Solar/Wind Harmer
2.49
972045AH1-571 GEN
Solar/Wind Harmer
1.992
339221AD2-048_GEN
Solar/Wind Harmer
1.523
970235AG2-159 GEN
Solar/Wind Harmer
3.901
970235AG2-159 GEN
Solar/Wind Harmer
2.382
270186AC1-089 GEN
Solar/Wind Harmer
5.863
970239AG2-162 GEN
Solar/Wind Harmer
10.536
962581AG1-107 GEN
Solar/Wind Harmer
4.763
961491AF2-440 GEN
Solar/Wind Harmer
1.98
270444AC2-157 GEN1
Solar/Wind Harmer
5.271
252509AD1-136 GEN
Solar/Wind Harmer
0.24
25183208HLCRTG
Solar/Wind Harmer
5.62
252519AF1-045_GEN
Solar/Wind Harmer
5.628
252516AE2-318_GEN
Solar/Wind Harmer
4.293
970879AG2-548 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
3.978
25194408D.CRK1
Adder
6.985
25194508D.CRK3
Adder
1.306
945391AF1-204 GEN
Solar/Wind Harmer
12.796
276916AD2-100_GEN
Solar/Wind Harmer
19.269
276911AD2-131_GEN
Solar/Wind Harmer
3.894
957381AF2-032 GEN
Solar/Wind Harmer
0.383
253317AC1-085 GEN4
Solar/Wind Harmer
7.655
276763AC1-053 GEN1
Solar/Wind Harmer
3.59
276764AC1-053 GEN2
Solar/Wind Harmer
3.59
970241AG2-163 GEN
Solar/Wind Harmer
22.567
24728805RICHG1
Adder
3.406
24728905RICHG2
Adder
3.406
972267AH1-718 GEN
Adder
3.711
274764LEE CO EC;5U
Adder
8.292
274765LEE CO EC;6U
Adder
8.292
274762LEE CO EC;3U
Adder
8.273
274763LEE CO EC;4U
Adder
8.195
274683WAUKEGAN ;8U
Adder
18.536
274683WAUKEGAN ;8U
Adder
15.625
274696ROCKY RD ;4P
Adder
10.02
274695ROCKY RD ;2P
Adder
9.789
274693ROCKY RD ;1P
Adder
9.693
274697ROCKY RD ;3P
Adder
2.659
253370AE2-315 SEC1
Adder
1.753
3132123MT JACKSON
Solar/Wind Helper
1.392
315821AE2-092 GEN
Solar/Wind Helper
3.222
966001AG1-469 GEN
Solar/Wind Helper
0.321
315651AD1-115 GEN
Solar/Wind Helper
0.841
316447AC1-158 HLD
Solar/Wind Helper
2.779
966871AG1-558 GEN
Solar/Wind Helper
0.307
316468AD1-105 GEN
Solar/Wind Helper
1.129
970823AG2-518 GEN
50/50
8.396
247619Y1-049
50/50
0.915
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.948
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.959
962751AG1-124 GEN
Solar/Wind Harmer
18.84
958121AF2-106 GEN
Solar/Wind Harmer
9.423
270173AC1-122 GEN
Solar/Wind Harmer
3.281
971331AH1-145 GEN
Solar/Wind Harmer
18.398
943031AE2-326 GEN
Solar/Wind Harmer
6.798
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.82
270574AD1-017 GEN2
Solar/Wind Harmer
8.482
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.986
270030AE2-140 GEN
Solar/Wind Harmer
30.98
960911AF2-382 GEN
Solar/Wind Harmer
10.985
270016AE1-250 BESS
Solar/Wind Harmer
3.259
970913AG2-568 GEN
Solar/Wind Harmer
11.054
971461AH1-227 GEN
Solar/Wind Harmer
7.029
970223AG2-152 GEN
Solar/Wind Harmer
17.643
270053AF1-130 C
Solar/Wind Harmer
4.837
972103AH1-617 GEN
Solar/Wind Harmer
25.94
24686205CER G4
Adder
9.888
24686405CER G5
Adder
9.849
972273AH1-721 GEN
Adder
89.748
24721905FLATG4
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
4.143
339250AF1-203 GEN
Solar/Wind Harmer
0.631
971155AH1-034 GEN
Solar/Wind Harmer
10.404
966571AG1-526 GEN
Solar/Wind Harmer
23.009
962251AG1-071 GEN
Solar/Wind Harmer
5.699
970093AG2-073 GEN
Solar/Wind Harmer
10.328
960741AF2-365 GEN
Solar/Wind Harmer
5.133
971191AH1-055 GEN
Solar/Wind Harmer
22.339
3429391JKCT 9G
Adder
8.45
972167AH1-666 GEN
Solar/Wind Harmer
7.817
957541AF2-048 GEN
Solar/Wind Harmer
1.539
958171AF2-111 GEN
Solar/Wind Harmer
24.064
970243AG2-164 GEN
Solar/Wind Harmer
24.738
970519AG2-331 GEN
Solar/Wind Harmer
16.62
970699AG2-449 GEN
Solar/Wind Harmer
10.995
25196008MFTGT1
Adder
1.261
252510AF1-249 C
Solar/Wind Harmer
0.387
25194608D.CRK4
Adder
1.519
25196608WSDLE5
Adder
7.903
970193AG2-126 GEN
Solar/Wind Harmer
13.773
942481AE2-261 GEN
Solar/Wind Harmer
27.393
253316AC1-085 GEN3
Solar/Wind Harmer
7.655
253433AC1-085 GEN1
Solar/Wind Harmer
4.859
946181AF1-283 GEN
Solar/Wind Harmer
11.881
24728705AND G3
Adder
7.324
24728505AND G1
Adder
3.502
276621W2-048 GEN
Solar/Wind Harmer
5.679
276838X2-022 GEN2
Solar/Wind Harmer
0.212
276686W4-005 GEN3
Solar/Wind Harmer
2.743
276668AB2-070 GEN1
Solar/Wind Harmer
2.04
971993AH1-541 GEN
Solar/Wind Harmer
8.379
253406AD2-031_GEN
Solar/Wind Harmer
1.157
270356AE2-297 GEN
Solar/Wind Harmer
4.125
274760LEE CO EC;1U
Adder
8.273
274767LEE CO EC;8U
Adder
8.175
972236AH1-702 GEN2
Adder
1.942
274682WAUKEGAN ;7U
Adder
15.803
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
274729ELWOOD EC;1P
Adder
1.688
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.091
316254AC1-120 GEN1
Solar/Wind Helper
1.164
316097T157 G90
Solar/Wind Helper
1.133
238148AE2-230_GEN2
Solar/Wind Helper
0.425
316336AC2-165 C
Solar/Wind Helper
1.289
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.042
3142416OLDCHRC
Solar/Wind Helper
0.58
3142416OLDCHRC
Solar/Wind Helper
0.222
944201AF1-088_MTX
Adder
109.749
957141AF2-008_MTX
Adder
54.874
CPLELTFEXP_CPLE->PJM
CLTF
6.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.77
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.491
MECLTFEXP_MEC->PJM
CLTF
15.504
SIGELTFEXP_SIGE->PJM
CLTF
0.511
NYPJM->LTFIMP_NY
CLTF
3.272
LGEELTFEXP_LGEE->PJM
CLTF
6.802
WECLTFEXP_WEC->PJM
CLTF
3.393
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304
LAGNLTFEXP_LAGN->PJM
CLTF
20.369
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.617
TVALTFEXP_TVA->PJM
CLTF
10.651

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.77 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4215.43
MW Contribution:1.31
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.262
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.389
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.006
971329AH1-144 GEN
Solar/Wind Harmer
23.701
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.814
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.759
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24728305BUCHG2
Adder
6.757
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.109
971543AH1-269 GEN
50/50
12.253
966391AG1-508 GEN
Solar/Wind Harmer
6.379
270069AE2-166 C O1
Solar/Wind Harmer
4.509
971313AH1-133 GEN
Solar/Wind Harmer
15.712
24734705WLF1G3
Adder
8.202
24734805WLF1G4
Adder
8.202
24734905WLF1G5
Adder
8.202
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.732
270214AC2-123 GEN
Solar/Wind Harmer
4.313
971277AH1-098 GEN
Solar/Wind Harmer
7.425
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.669
24728205BUCHG1
Adder
6.757
270013AE1-250 PV
Solar/Wind Harmer
3.257
970823AG2-518 GEN
50/50
8.387
247619Y1-049
50/50
0.914
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.94
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.869
962751AG1-124 GEN
Solar/Wind Harmer
18.829
958121AF2-106 GEN
Solar/Wind Harmer
9.412
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.373
943031AE2-326 GEN
Solar/Wind Harmer
6.789
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.814
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.951
270030AE2-140 GEN
Solar/Wind Harmer
30.945
960911AF2-382 GEN
Solar/Wind Harmer
10.959
270016AE1-250 BESS
Solar/Wind Harmer
3.257
24735205WLF2G2
Adder
8.031
971687AH1-348 GEN
Solar/Wind Harmer
1.36
971403AH1-188 GEN
Solar/Wind Harmer
18.877
24723205RIVRG3
Adder
22.989
971315AH1-136 GEN
Solar/Wind Harmer
2.433
24686105CER G3
Adder
9.903
24686505CER G6
Adder
9.89
270331AC1-082 GEN3
Solar/Wind Harmer
0.488
24721705FLATG2
Adder
21.725
970947AG2-589 GEN
Solar/Wind Harmer
2.143
970273AG2-179 GEN
Solar/Wind Harmer
2.585
971821AH1-427 GEN
Solar/Wind Harmer
10.363
964901AG1-354 GEN
Solar/Wind Harmer
15.523
339241AF1-083 GEN
Solar/Wind Harmer
1.717
962241AG1-070 GEN
Solar/Wind Harmer
4.647
960001AF2-291 GEN
Solar/Wind Harmer
3.12
3429241JKCT 3G
Adder
12.05
3429421JKCT 10G
Adder
8.417
971565AH1-281 GEN
Solar/Wind Harmer
2.004
943111AE2-339 GEN
Solar/Wind Harmer
0.884
339216AC1-074 GEN
Solar/Wind Harmer
1.652
945681AF1-233 GEN
Solar/Wind Harmer
18.356
927014AC1-188 GEN
Solar/Wind Harmer
1.535
970091AG2-072 GEN
Adder
74.149
970333AG2-219 GEN
Solar/Wind Harmer
30.107
270445AC2-157 GEN2
Solar/Wind Harmer
5.249
25196808ZIMRHP
Adder
70.761
252507AC2-088 GEN
Solar/Wind Harmer
1.673
25196008MFTGT1
Adder
1.296
25194608D.CRK4
Adder
1.511
965911AG1-460 GEN
Solar/Wind Harmer
1.273
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.095
24728605AND G2
Adder
3.486
276615X2-022 GEN
Solar/Wind Harmer
1.776
963831AG1-236 GEN
Solar/Wind Harmer
8.893
274880W4-005 GEN4
Solar/Wind Harmer
2.731
963741AG1-226 GEN
Solar/Wind Harmer
40.444
274761LEE CO EC;2U
Adder
8.237
274766LEE CO EC;7U
Adder
8.14
972235AH1-702 GEN1
Adder
2.224
274822ROCKFORD ;11
Adder
17.308
274828WAUKEGAN ;BP
Adder
9.674
274682WAUKEGAN ;7U
Adder
15.734
274745AC1-111 GEN9
Adder
4.879
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
315616AA1-038_C
Solar/Wind Helper
3.294
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.387
23583801GRNGAP
Solar/Wind Helper
4.296
316095T157 G97
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.12
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316473AC1-191 GEN
Solar/Wind Helper
1.388
316044AC1-158 PL1
Solar/Wind Helper
1.259
316450AC1-158 RIC
Solar/Wind Helper
0.336
972175AH1-670 GEN
Solar/Wind Harmer
4.729
971225AH1-072 GEN
Solar/Wind Harmer
2.733
971227AH1-073 GEN
Solar/Wind Harmer
2.733
944971AF1-162 GEN
Solar/Wind Harmer
9.08
24723005RIVRG1
Adder
22.989
24723105RIVRG2
Adder
22.989
24685805CER G1
Adder
9.838
24685905CER G2
Adder
9.838
942751AE2-291 GEN
Solar/Wind Harmer
10.387
966021AG1-471 GEN
Solar/Wind Harmer
5.761
971485AH1-239 GEN
Solar/Wind Harmer
8.509
339231AF1-038_GEN
Solar/Wind Harmer
1.921
960161AF2-307 GEN
Solar/Wind Harmer
6.669
339255AE2-071 GEN
Solar/Wind Harmer
1.1
964781AG1-341 GEN
Solar/Wind Harmer
10.986
339236AF1-050_GEN
Solar/Wind Harmer
1.875
971081AG2-670 GEN
Solar/Wind Harmer
7.746
942891AE2-308 GEN
Solar/Wind Harmer
10.193
970653AG2-424 GEN
Solar/Wind Harmer
4.888
970653AG2-424 GEN
Solar/Wind Harmer
1.767
964571AG1-320 GEN
Solar/Wind Harmer
8.199
971125AH1-004 GEN
Solar/Wind Harmer
3.987
970107AG2-081 GEN
Solar/Wind Harmer
2.99
972043AH1-570 GEN
Solar/Wind Harmer
2.479
972045AH1-571 GEN
Solar/Wind Harmer
1.983
339221AD2-048_GEN
Solar/Wind Harmer
1.517
970235AG2-159 GEN
Solar/Wind Harmer
3.885
970235AG2-159 GEN
Solar/Wind Harmer
2.372
270186AC1-089 GEN
Solar/Wind Harmer
5.836
970239AG2-162 GEN
Solar/Wind Harmer
10.492
962581AG1-107 GEN
Solar/Wind Harmer
4.741
961491AF2-440 GEN
Solar/Wind Harmer
1.97
270444AC2-157 GEN1
Solar/Wind Harmer
5.249
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.594
252519AF1-045_GEN
Solar/Wind Harmer
5.601
252516AE2-318_GEN
Solar/Wind Harmer
4.272
970879AG2-548 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
3.956
25194408D.CRK1
Adder
6.953
25194508D.CRK3
Adder
1.3
945391AF1-204 GEN
Solar/Wind Harmer
12.742
276916AD2-100_GEN
Solar/Wind Harmer
19.19
276911AD2-131_GEN
Solar/Wind Harmer
3.878
957381AF2-032 GEN
Solar/Wind Harmer
0.382
253317AC1-085 GEN4
Solar/Wind Harmer
7.618
276763AC1-053 GEN1
Solar/Wind Harmer
3.575
276764AC1-053 GEN2
Solar/Wind Harmer
3.575
970241AG2-163 GEN
Solar/Wind Harmer
22.469
24728805RICHG1
Adder
3.391
24728905RICHG2
Adder
3.391
972267AH1-718 GEN
Adder
3.695
274764LEE CO EC;5U
Adder
8.257
274765LEE CO EC;6U
Adder
8.257
274762LEE CO EC;3U
Adder
8.237
274763LEE CO EC;4U
Adder
8.16
274683WAUKEGAN ;8U
Adder
18.455
274683WAUKEGAN ;8U
Adder
15.556
274696ROCKY RD ;4P
Adder
9.976
274695ROCKY RD ;2P
Adder
9.746
274693ROCKY RD ;1P
Adder
9.65
274697ROCKY RD ;3P
Adder
2.648
253370AE2-315 SEC1
Adder
1.744
3132123MT JACKSON
Solar/Wind Helper
1.39
315821AE2-092 GEN
Solar/Wind Helper
3.218
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.839
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.77
316468AD1-105 GEN
Solar/Wind Helper
1.126
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.031
270399AC1-101 GEN
Solar/Wind Harmer
5.563
270400AC1-102 GEN
Solar/Wind Harmer
5.563
941621AE2-160 GEN
Adder
4.292
957241AF2-018 GEN
Solar/Wind Harmer
5.764
970281AG2-184 GEN
Solar/Wind Harmer
27.16
972143AH1-644 GEN
Solar/Wind Harmer
12.933
971981AH1-535 GEN
Solar/Wind Harmer
12.575
962211AG1-066 GEN
Solar/Wind Harmer
3.005
971061AG2-657 GEN
Solar/Wind Harmer
11.012
24477305BRIDGE
Adder
0.42
972203AH1-686 GEN
Adder
2.709
270330AC1-082 GEN2
Solar/Wind Harmer
0.826
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.068
965411AG1-406 GEN
Solar/Wind Harmer
2.724
339211AE2-254 GEN
Solar/Wind Harmer
1.566
3429211JKCT 2G
Adder
11.894
970455AG2-298 GEN
Solar/Wind Harmer
6.044
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.762
972165AH1-665 GEN
Solar/Wind Harmer
7.81
971985AH1-537 GEN
Solar/Wind Harmer
17.332
270367AC2-061_GEN
Solar/Wind Harmer
3.015
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.428
25196108MFTGT2
Adder
1.326
970879AG2-548 GEN
Solar/Wind Harmer
3.956
944221AF1-090 GEN
Solar/Wind Harmer
10.042
252524AE2-267 GEN
Solar/Wind Harmer
1.447
25196408WSDLE3
Adder
8.097
25196308WSDLE2
Adder
8.027
25196208WSDLE1
Adder
8.006
25196708WSDLE6
Adder
7.986
25196508WSDLE4
Adder
7.785
276849AB2-070 GEN2
Solar/Wind Harmer
2.031
276848AB2-070 GEN3
Solar/Wind Harmer
2.031
276785W4-005 GEN1
Solar/Wind Harmer
2.731
276174W4-005 GEN2
Solar/Wind Harmer
2.731
274823ROCKFORD ;21
Adder
17.182
274746AC1-111 G10
Adder
4.879
274744AC1-111 GEN8
Adder
4.879
25306009OHH W.
Adder
2.51
253372AE2-315 SEC3
Adder
1.649
253372AE2-315 SEC3
Adder
1.649
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
970913AG2-568 GEN
Solar/Wind Harmer
11.019
971461AH1-227 GEN
Solar/Wind Harmer
7.011
970223AG2-152 GEN
Solar/Wind Harmer
17.629
270053AF1-130 C
Solar/Wind Harmer
4.822
972103AH1-617 GEN
Solar/Wind Harmer
25.867
24686205CER G4
Adder
9.851
24686405CER G5
Adder
9.812
972273AH1-721 GEN
Adder
89.448
24721905FLATG4
Adder
21.725
970273AG2-179 GEN
Solar/Wind Harmer
4.129
339250AF1-203 GEN
Solar/Wind Harmer
0.629
971155AH1-034 GEN
Solar/Wind Harmer
10.369
966571AG1-526 GEN
Solar/Wind Harmer
22.923
962251AG1-071 GEN
Solar/Wind Harmer
5.679
970093AG2-073 GEN
Solar/Wind Harmer
10.289
960741AF2-365 GEN
Solar/Wind Harmer
5.115
3429391JKCT 9G
Adder
8.417
971191AH1-055 GEN
Solar/Wind Harmer
22.23
972167AH1-666 GEN
Solar/Wind Harmer
7.783
957541AF2-048 GEN
Solar/Wind Harmer
1.531
958171AF2-111 GEN
Solar/Wind Harmer
23.957
970243AG2-164 GEN
Solar/Wind Harmer
24.633
970519AG2-331 GEN
Solar/Wind Harmer
16.549
970699AG2-449 GEN
Solar/Wind Harmer
10.948
25196008MFTGT1
Adder
1.255
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.511
25196608WSDLE5
Adder
7.866
970193AG2-126 GEN
Solar/Wind Harmer
13.715
942481AE2-261 GEN
Solar/Wind Harmer
27.279
253316AC1-085 GEN3
Solar/Wind Harmer
7.618
253433AC1-085 GEN1
Solar/Wind Harmer
4.836
946181AF1-283 GEN
Solar/Wind Harmer
11.823
24728705AND G3
Adder
7.292
24728505AND G1
Adder
3.486
276621W2-048 GEN
Solar/Wind Harmer
5.656
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.031
276686W4-005 GEN3
Solar/Wind Harmer
2.731
971993AH1-541 GEN
Solar/Wind Harmer
8.344
270356AE2-297 GEN
Solar/Wind Harmer
4.106
253406AD2-031_GEN
Solar/Wind Harmer
1.151
274760LEE CO EC;1U
Adder
8.237
274767LEE CO EC;8U
Adder
8.14
972236AH1-702 GEN2
Adder
1.934
274682WAUKEGAN ;7U
Adder
15.734
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
274729ELWOOD EC;1P
Adder
1.681
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.84
3147666LOUISA
Solar/Wind Helper
1.089
316254AC1-120 GEN1
Solar/Wind Helper
1.161
316097T157 G90
Solar/Wind Helper
1.128
238148AE2-230_GEN2
Solar/Wind Helper
0.424
316336AC2-165 C
Solar/Wind Helper
1.286
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.029
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.173
238152AF2-075_GEN
Solar/Wind Helper
0.603
944201AF1-088_MTX
Adder
109.291
957141AF2-008_MTX
Adder
54.646
CPLELTFEXP_CPLE->PJM
CLTF
6.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.369
MECLTFEXP_MEC->PJM
CLTF
15.442
SIGELTFEXP_SIGE->PJM
CLTF
0.509
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.775
WECLTFEXP_WEC->PJM
CLTF
3.378
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
20.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.62

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.68 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4211.98
MW Contribution:1.31
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.003
971329AH1-144 GEN
Solar/Wind Harmer
23.686
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.812
270197AD1-017 GEN1
Solar/Wind Harmer
2.546
270336AE1-100 GEN
Solar/Wind Harmer
2.757
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.108
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.852
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
2.43
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
2.139
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
10.346
964901AG1-354 GEN
Solar/Wind Harmer
15.5
339241AF1-083 GEN
Solar/Wind Harmer
1.715
962241AG1-070 GEN
Solar/Wind Harmer
4.64
960001AF2-291 GEN
Solar/Wind Harmer
3.113
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
2.001
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.649
945681AF1-233 GEN
Solar/Wind Harmer
18.32
927014AC1-188 GEN
Solar/Wind Harmer
1.532
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
30.05
270445AC2-157 GEN2
Solar/Wind Harmer
5.239
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
1.669
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.075
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
1.772
963831AG1-236 GEN
Solar/Wind Harmer
8.877
274880W4-005 GEN4
Solar/Wind Harmer
2.726
963741AG1-226 GEN
Solar/Wind Harmer
40.366
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
972235AH1-702 GEN1
Adder
2.22
274822ROCKFORD ;11
Adder
17.275
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.72
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971277AH1-098 GEN
Solar/Wind Harmer
7.42
316217AC1-145 GEN
Solar/Wind Harmer
4.247
316197AC1-042 GEN
Solar/Wind Harmer
3.219
942671AE2-283 GEN
Solar/Wind Harmer
8.667
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
3.256
971225AH1-072 GEN
Solar/Wind Harmer
2.73
971227AH1-073 GEN
Solar/Wind Harmer
2.73
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
10.385
966021AG1-471 GEN
Solar/Wind Harmer
5.753
971485AH1-239 GEN
Solar/Wind Harmer
8.497
339231AF1-038_GEN
Solar/Wind Harmer
1.918
960161AF2-307 GEN
Solar/Wind Harmer
6.658
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.97
339236AF1-050_GEN
Solar/Wind Harmer
1.872
971081AG2-670 GEN
Solar/Wind Harmer
7.734
942891AE2-308 GEN
Solar/Wind Harmer
10.176
970653AG2-424 GEN
Solar/Wind Harmer
4.88
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
8.186
971125AH1-004 GEN
Solar/Wind Harmer
3.98
970107AG2-081 GEN
Solar/Wind Harmer
2.985
972043AH1-570 GEN
Solar/Wind Harmer
2.475
972045AH1-571 GEN
Solar/Wind Harmer
1.98
339221AD2-048_GEN
Solar/Wind Harmer
1.514
970235AG2-159 GEN
Solar/Wind Harmer
3.878
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
5.824
970239AG2-162 GEN
Solar/Wind Harmer
10.472
962581AG1-107 GEN
Solar/Wind Harmer
4.731
961491AF2-440 GEN
Solar/Wind Harmer
1.966
270444AC2-157 GEN1
Solar/Wind Harmer
5.239
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.582
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.263
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
970879AG2-548 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
3.946
945391AF1-204 GEN
Solar/Wind Harmer
12.718
276916AD2-100_GEN
Solar/Wind Harmer
19.154
276911AD2-131_GEN
Solar/Wind Harmer
3.871
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.601
276763AC1-053 GEN1
Solar/Wind Harmer
3.568
276764AC1-053 GEN2
Solar/Wind Harmer
3.568
970241AG2-163 GEN
Solar/Wind Harmer
22.426
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
972267AH1-718 GEN
Adder
3.688
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
18.825
958121AF2-106 GEN
Solar/Wind Harmer
9.407
270173AC1-122 GEN
Solar/Wind Harmer
3.278
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.812
270574AD1-017 GEN2
Solar/Wind Harmer
8.473
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.936
270030AE2-140 GEN
Solar/Wind Harmer
30.929
960911AF2-382 GEN
Solar/Wind Harmer
10.948
270016AE1-250 BESS
Solar/Wind Harmer
3.256
970913AG2-568 GEN
Solar/Wind Harmer
11.004
971461AH1-227 GEN
Solar/Wind Harmer
7.003
970223AG2-152 GEN
Solar/Wind Harmer
17.623
270053AF1-130 C
Solar/Wind Harmer
4.815
972103AH1-617 GEN
Solar/Wind Harmer
25.835
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.123
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.354
962251AG1-071 GEN
Solar/Wind Harmer
5.671
966571AG1-526 GEN
Solar/Wind Harmer
22.886
970093AG2-073 GEN
Solar/Wind Harmer
10.271
960741AF2-365 GEN
Solar/Wind Harmer
5.107
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
22.182
972167AH1-666 GEN
Solar/Wind Harmer
7.768
957541AF2-048 GEN
Solar/Wind Harmer
1.528
958171AF2-111 GEN
Solar/Wind Harmer
23.91
970243AG2-164 GEN
Solar/Wind Harmer
24.587
970519AG2-331 GEN
Solar/Wind Harmer
16.518
970699AG2-449 GEN
Solar/Wind Harmer
10.927
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.384
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
13.689
942481AE2-261 GEN
Solar/Wind Harmer
27.229
253316AC1-085 GEN3
Solar/Wind Harmer
7.601
253433AC1-085 GEN1
Solar/Wind Harmer
4.825
946181AF1-283 GEN
Solar/Wind Harmer
11.797
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
5.645
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276686W4-005 GEN3
Solar/Wind Harmer
2.726
276668AB2-070 GEN1
Solar/Wind Harmer
2.027
971993AH1-541 GEN
Solar/Wind Harmer
8.328
270356AE2-297 GEN
Solar/Wind Harmer
4.098
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
972236AH1-702 GEN2
Adder
1.93
274682WAUKEGAN ;7U
Adder
15.703
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
316468AD1-105 GEN
Solar/Wind Helper
1.124
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
6.374
270069AE2-166 C O1
Solar/Wind Harmer
4.507
971313AH1-133 GEN
Solar/Wind Harmer
15.698
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
5.556
270400AC1-102 GEN
Solar/Wind Harmer
5.556
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
5.757
970281AG2-184 GEN
Solar/Wind Harmer
27.126
972143AH1-644 GEN
Solar/Wind Harmer
12.917
971981AH1-535 GEN
Solar/Wind Harmer
12.563
962211AG1-066 GEN
Solar/Wind Harmer
3.001
971061AG2-657 GEN
Solar/Wind Harmer
10.991
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.485
965401AG1-405 GEN
Solar/Wind Harmer
6.059
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
1.563
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
6.034
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972163AH1-664 GEN
Solar/Wind Harmer
9.743
972165AH1-665 GEN
Solar/Wind Harmer
7.794
971985AH1-537 GEN
Solar/Wind Harmer
17.295
270367AC2-061_GEN
Solar/Wind Harmer
3.009
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
3.946
944221AF1-090 GEN
Solar/Wind Harmer
10.024
252524AE2-267 GEN
Solar/Wind Harmer
1.444
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
2.726
276174W4-005 GEN2
Solar/Wind Harmer
2.726
276849AB2-070 GEN2
Solar/Wind Harmer
2.027
276848AB2-070 GEN3
Solar/Wind Harmer
2.027
274823ROCKFORD ;21
Adder
17.15
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.36 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4200.43
MW Contribution:1.31
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
8.386
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.941
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.847
962751AG1-124 GEN
Solar/Wind Harmer
18.831
958121AF2-106 GEN
Solar/Wind Harmer
9.409
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.367
943031AE2-326 GEN
Solar/Wind Harmer
6.787
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.815
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270030AE2-140 GEN
Solar/Wind Harmer
30.942
960911AF2-382 GEN
Solar/Wind Harmer
10.952
270016AE1-250 BESS
Solar/Wind Harmer
3.257
970913AG2-568 GEN
Solar/Wind Harmer
11.009
971461AH1-227 GEN
Solar/Wind Harmer
7.007
970223AG2-152 GEN
Solar/Wind Harmer
17.631
270053AF1-130 C
Solar/Wind Harmer
4.818
972103AH1-617 GEN
Solar/Wind Harmer
25.847
24686205CER G4
Adder
9.841
24686405CER G5
Adder
9.802
972273AH1-721 GEN
Adder
89.369
24721905FLATG4
Adder
21.699
970273AG2-179 GEN
Solar/Wind Harmer
4.125
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.36
962251AG1-071 GEN
Solar/Wind Harmer
5.674
966571AG1-526 GEN
Solar/Wind Harmer
22.9
970093AG2-073 GEN
Solar/Wind Harmer
10.278
960741AF2-365 GEN
Solar/Wind Harmer
5.111
3429391JKCT 9G
Adder
8.407
971191AH1-055 GEN
Solar/Wind Harmer
22.196
972167AH1-666 GEN
Solar/Wind Harmer
7.773
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.926
970243AG2-164 GEN
Solar/Wind Harmer
24.603
970519AG2-331 GEN
Solar/Wind Harmer
16.529
970699AG2-449 GEN
Solar/Wind Harmer
10.935
25196008MFTGT1
Adder
1.253
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.509
25196608WSDLE5
Adder
7.855
970193AG2-126 GEN
Solar/Wind Harmer
13.698
942481AE2-261 GEN
Solar/Wind Harmer
27.248
253316AC1-085 GEN3
Solar/Wind Harmer
7.607
253433AC1-085 GEN1
Solar/Wind Harmer
4.829
946181AF1-283 GEN
Solar/Wind Harmer
11.806
24728705AND G3
Adder
7.283
24728505AND G1
Adder
3.482
276621W2-048 GEN
Solar/Wind Harmer
5.649
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.029
276686W4-005 GEN3
Solar/Wind Harmer
2.728
971993AH1-541 GEN
Solar/Wind Harmer
8.334
270356AE2-297 GEN
Solar/Wind Harmer
4.101
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.227
274767LEE CO EC;8U
Adder
8.131
972236AH1-702 GEN2
Adder
1.932
274682WAUKEGAN ;7U
Adder
15.715
274729ELWOOD EC;1P
Adder
13.491
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.837
3147666LOUISA
Solar/Wind Helper
1.087
316254AC1-120 GEN1
Solar/Wind Helper
1.158
316097T157 G90
Solar/Wind Helper
1.124
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.284
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.02
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
971543AH1-269 GEN
50/50
12.251
966391AG1-508 GEN
Solar/Wind Harmer
6.377
270069AE2-166 C O1
Solar/Wind Harmer
4.508
971313AH1-133 GEN
Solar/Wind Harmer
15.705
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.027
270399AC1-101 GEN
Solar/Wind Harmer
5.558
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.287
957241AF2-018 GEN
Solar/Wind Harmer
5.759
970281AG2-184 GEN
Solar/Wind Harmer
27.14
972143AH1-644 GEN
Solar/Wind Harmer
12.924
971981AH1-535 GEN
Solar/Wind Harmer
12.569
962211AG1-066 GEN
Solar/Wind Harmer
3.003
971061AG2-657 GEN
Solar/Wind Harmer
10.996
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.706
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.063
965411AG1-406 GEN
Solar/Wind Harmer
2.721
339211AE2-254 GEN
Solar/Wind Harmer
1.564
3429211JKCT 2G
Adder
11.881
970455AG2-298 GEN
Solar/Wind Harmer
6.038
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.749
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.306
270367AC2-061_GEN
Solar/Wind Harmer
3.011
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.426
25196108MFTGT2
Adder
1.325
970879AG2-548 GEN
Solar/Wind Harmer
3.949
944221AF1-090 GEN
Solar/Wind Harmer
10.031
252524AE2-267 GEN
Solar/Wind Harmer
1.445
25196408WSDLE3
Adder
8.086
25196308WSDLE2
Adder
8.015
25196208WSDLE1
Adder
7.995
25196708WSDLE6
Adder
7.975
25196508WSDLE4
Adder
7.774
276849AB2-070 GEN2
Solar/Wind Harmer
2.029
276848AB2-070 GEN3
Solar/Wind Harmer
2.029
276785W4-005 GEN1
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
274823ROCKFORD ;21
Adder
17.162
274746AC1-111 G10
Adder
4.873
274744AC1-111 GEN8
Adder
4.873
25306009OHH W.
Adder
2.506
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.171
238152AF2-075_GEN
Solar/Wind Helper
0.601
270583AD2-179 GEN
Solar/Wind Harmer
20.728
270214AC2-123 GEN
Solar/Wind Harmer
4.312
971277AH1-098 GEN
Solar/Wind Harmer
7.423
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.67
24728205BUCHG1
Adder
6.753
270013AE1-250 PV
Solar/Wind Harmer
3.257
971225AH1-072 GEN
Solar/Wind Harmer
2.732
971227AH1-073 GEN
Solar/Wind Harmer
2.732
944971AF1-162 GEN
Solar/Wind Harmer
9.072
24723005RIVRG1
Adder
22.966
24723105RIVRG2
Adder
22.966
24685805CER G1
Adder
9.828
24685905CER G2
Adder
9.828
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.756
971485AH1-239 GEN
Solar/Wind Harmer
8.502
339231AF1-038_GEN
Solar/Wind Harmer
1.919
960161AF2-307 GEN
Solar/Wind Harmer
6.662
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.976
339236AF1-050_GEN
Solar/Wind Harmer
1.873
971081AG2-670 GEN
Solar/Wind Harmer
7.739
942891AE2-308 GEN
Solar/Wind Harmer
10.182
970653AG2-424 GEN
Solar/Wind Harmer
4.883
970653AG2-424 GEN
Solar/Wind Harmer
1.765
964571AG1-320 GEN
Solar/Wind Harmer
8.191
971125AH1-004 GEN
Solar/Wind Harmer
3.983
970107AG2-081 GEN
Solar/Wind Harmer
2.987
972043AH1-570 GEN
Solar/Wind Harmer
2.476
972045AH1-571 GEN
Solar/Wind Harmer
1.981
339221AD2-048_GEN
Solar/Wind Harmer
1.515
970235AG2-159 GEN
Solar/Wind Harmer
3.88
970235AG2-159 GEN
Solar/Wind Harmer
2.369
270186AC1-089 GEN
Solar/Wind Harmer
5.828
970239AG2-162 GEN
Solar/Wind Harmer
10.479
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
270444AC2-157 GEN1
Solar/Wind Harmer
5.243
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.586
252519AF1-045_GEN
Solar/Wind Harmer
5.593
252516AE2-318_GEN
Solar/Wind Harmer
4.266
25194408D.CRK1
Adder
6.943
25194508D.CRK3
Adder
1.298
970879AG2-548 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
3.949
945391AF1-204 GEN
Solar/Wind Harmer
12.727
276916AD2-100_GEN
Solar/Wind Harmer
19.168
276911AD2-131_GEN
Solar/Wind Harmer
3.874
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.607
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
970241AG2-163 GEN
Solar/Wind Harmer
22.442
24728805RICHG1
Adder
3.386
24728905RICHG2
Adder
3.386
972267AH1-718 GEN
Adder
3.691
274764LEE CO EC;5U
Adder
8.247
274765LEE CO EC;6U
Adder
8.247
274762LEE CO EC;3U
Adder
8.227
274763LEE CO EC;4U
Adder
8.15
274683WAUKEGAN ;8U
Adder
18.432
274683WAUKEGAN ;8U
Adder
15.538
274696ROCKY RD ;4P
Adder
9.964
274695ROCKY RD ;2P
Adder
9.734
274693ROCKY RD ;1P
Adder
9.639
274697ROCKY RD ;3P
Adder
2.644
3132123MT JACKSON
Solar/Wind Helper
1.388
315821AE2-092 GEN
Solar/Wind Helper
3.215
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.764
316468AD1-105 GEN
Solar/Wind Helper
1.124
970479AG2-310 GEN
50/50
20.26
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.39
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.005
971329AH1-144 GEN
Solar/Wind Harmer
23.694
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.815
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.758
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24728305BUCHG2
Adder
6.753
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.111
24735205WLF2G2
Adder
8.027
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.861
24723205RIVRG3
Adder
22.966
971315AH1-136 GEN
Solar/Wind Harmer
2.431
24686105CER G3
Adder
9.893
24686505CER G6
Adder
9.88
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.699
970947AG2-589 GEN
Solar/Wind Harmer
2.14
970273AG2-179 GEN
Solar/Wind Harmer
2.583
971821AH1-427 GEN
Solar/Wind Harmer
10.353
964901AG1-354 GEN
Solar/Wind Harmer
15.509
339241AF1-083 GEN
Solar/Wind Harmer
1.716
962241AG1-070 GEN
Solar/Wind Harmer
4.643
960001AF2-291 GEN
Solar/Wind Harmer
3.115
3429241JKCT 3G
Adder
12.037
3429421JKCT 10G
Adder
8.407
971565AH1-281 GEN
Solar/Wind Harmer
2.002
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
18.332
927014AC1-188 GEN
Solar/Wind Harmer
1.533
970091AG2-072 GEN
Adder
74.061
970333AG2-219 GEN
Solar/Wind Harmer
30.071
270445AC2-157 GEN2
Solar/Wind Harmer
5.243
25196808ZIMRHP
Adder
70.665
252507AC2-088 GEN
Solar/Wind Harmer
1.671
25196008MFTGT1
Adder
1.294
25194608D.CRK4
Adder
1.509
965911AG1-460 GEN
Solar/Wind Harmer
1.272
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.081
24728605AND G2
Adder
3.482
276615X2-022 GEN
Solar/Wind Harmer
1.774
963831AG1-236 GEN
Solar/Wind Harmer
8.883
274880W4-005 GEN4
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.395
274761LEE CO EC;2U
Adder
8.227
274766LEE CO EC;7U
Adder
8.131
972235AH1-702 GEN1
Adder
2.221
274822ROCKFORD ;11
Adder
17.288
274828WAUKEGAN ;BP
Adder
9.662
274682WAUKEGAN ;7U
Adder
15.715
274745AC1-111 GEN9
Adder
4.873
315616AA1-038_C
Solar/Wind Helper
3.292
3148013FISHERV
Solar/Wind Helper
0.522
316499AE2-029_GEN
Solar/Wind Helper
1.724
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.284
316095T157 G97
Solar/Wind Helper
1.124
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.318
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.386
316044AC1-158 PL1
Solar/Wind Helper
1.256
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.723
944201AF1-088_MTX
Adder
109.164
957141AF2-008_MTX
Adder
54.582
CPLELTFEXP_CPLE->PJM
CLTF
6.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.197
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.508
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.339
MECLTFEXP_MEC->PJM
CLTF
15.425
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.243
LGEELTFEXP_LGEE->PJM
CLTF
6.767
WECLTFEXP_WEC->PJM
CLTF
3.374
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
20.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.613

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.96 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:330.65
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.036
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.601
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
CPLELTFEXP_CPLE->PJM
CLTF
0.484
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.177
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.013
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.831
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.95 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:330.63
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.035
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.6
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
CPLELTFEXP_CPLE->PJM
CLTF
0.484
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 1016T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.07 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:313.77
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
CPLELTFEXP_CPLE->PJM
CLTF
0.492
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 101672_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.05 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:313.73
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
5.565
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
CPLELTFEXP_CPLE->PJM
CLTF
0.492
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 104772_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.62 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:310.21
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
316123AC1-075 GEN
Solar/Wind Harmer
5.565
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
CPLELTFEXP_CPLE->PJM
CLTF
0.492
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1047_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.29 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:260.4
MW Contribution:3.72
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.295
316003AC1-222 GEN
Solar/Wind Harmer
0.012
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.175
970223AG2-152 GEN
Solar/Wind Harmer
4.628
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.295
971683AH1-343 GEN
Solar/Wind Harmer
16.89
270197AD1-017 GEN1
Solar/Wind Harmer
0.699
316123AC1-075 GEN
Solar/Wind Harmer
0.627
970865AG2-541 GEN
Solar/Wind Harmer
15.911
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.549
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.896
942751AE2-291 GEN
Solar/Wind Harmer
24.967
270013AE1-250 PV
Solar/Wind Harmer
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.484
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1016_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1016_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.51 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:248.71
MW Contribution:3.72
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
0.628
970865AG2-541 GEN
Solar/Wind Harmer
15.914
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.55
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.299
971683AH1-343 GEN
Solar/Wind Harmer
16.893
270197AD1-017 GEN1
Solar/Wind Harmer
0.7
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.899
942751AE2-291 GEN
Solar/Wind Harmer
24.973
270013AE1-250 PV
Solar/Wind Harmer
0.002
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.299
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.176
970223AG2-152 GEN
Solar/Wind Harmer
4.636
CPLELTFEXP_CPLE->PJM
CLTF
0.492
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.154
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.25 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:245.61
MW Contribution:2.19
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
CPLELTFEXP_CPLE->PJM
CLTF
0.729
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.25 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:245.6
MW Contribution:2.19
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
CPLELTFEXP_CPLE->PJM
CLTF
0.729
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.34 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:334.02
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
5.564
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.036
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.601
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
CPLELTFEXP_CPLE->PJM
CLTF
0.484
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.177
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.013
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.831
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.33 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:334.0
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.035
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.6
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
CPLELTFEXP_CPLE->PJM
CLTF
0.484
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 1016T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.43 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:317.11
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
CPLELTFEXP_CPLE->PJM
CLTF
0.492
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 101672_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.42 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:317.07
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
CPLELTFEXP_CPLE->PJM
CLTF
0.492
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 104772_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.97 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:313.53
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
CPLELTFEXP_CPLE->PJM
CLTF
0.492
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1047_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.67 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:263.78
MW Contribution:3.72
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
0.627
970865AG2-541 GEN
Solar/Wind Harmer
15.911
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.549
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.295
971683AH1-343 GEN
Solar/Wind Harmer
16.89
270197AD1-017 GEN1
Solar/Wind Harmer
0.699
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.295
316003AC1-222 GEN
Solar/Wind Harmer
0.012
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.175
970223AG2-152 GEN
Solar/Wind Harmer
4.628
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.896
942751AE2-291 GEN
Solar/Wind Harmer
24.967
270013AE1-250 PV
Solar/Wind Harmer
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.484
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1016_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1016_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.87 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:252.04
MW Contribution:3.72
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.299
3147123OTTER R
Solar/Wind Harmer
0.275
316123AC1-075 GEN
Solar/Wind Harmer
0.628
970865AG2-541 GEN
Solar/Wind Harmer
15.914
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.55
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.176
970223AG2-152 GEN
Solar/Wind Harmer
4.636
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.899
942751AE2-291 GEN
Solar/Wind Harmer
24.973
270013AE1-250 PV
Solar/Wind Harmer
0.002
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.299
971683AH1-343 GEN
Solar/Wind Harmer
16.893
270197AD1-017 GEN1
Solar/Wind Harmer
0.7
CPLELTFEXP_CPLE->PJM
CLTF
0.492
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.154
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.55 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:248.8
MW Contribution:2.19
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
270173AC1-122 GEN
Solar/Wind Harmer
0.706
960061AF2-297 GEN
Solar/Wind Harmer
3.734
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
CPLELTFEXP_CPLE->PJM
CLTF
0.729
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.55 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:248.79
MW Contribution:2.19
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
CPLELTFEXP_CPLE->PJM
CLTF
0.729
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.3 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:303.76
MW Contribution:5.28
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
27.028
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
5.283
970163AG2-111 GEN
Solar/Wind Harmer
5.039
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.036
316239AB2-077_GEN
Solar/Wind Helper
0.188
316238AB2-078_GEN
Solar/Wind Helper
0.188
3144303KENBRDG
Solar/Wind Helper
0.094
24728405LEESVG
50/50
0.206
24684605SMG4
50/50
0.9
24288905REUSENS
50/50
0.018
966251AG1-494 GEN
50/50
1.299
971683AH1-343 GEN
Solar/Wind Harmer
31.005
3147312GRETNA
Solar/Wind Harmer
0.048
941821AE2-187 GEN
Solar/Wind Harmer
7.752
270197AD1-017 GEN1
Solar/Wind Harmer
0.469
958131AF2-107 GEN
Solar/Wind Harmer
1.71
316248AF1-058 C
Solar/Wind Helper
0.404
316131AB2-060 GEN
Solar/Wind Helper
0.823
315785AD2-033 C
Solar/Wind Helper
1.409
24684405SMG2
50/50
0.894
24684505SMG3
50/50
0.553
24684305SMG1
50/50
0.324
942751AE2-291 GEN
Solar/Wind Harmer
31.036
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.003
942671AE2-283 GEN
Solar/Wind Harmer
6.03
3146843MT LREL
Solar/Wind Helper
0.232
3146843MT LREL
Solar/Wind Helper
0.232
316034AC1-036 C
Solar/Wind Helper
0.123
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
24684705SMG5
50/50
0.344
970481AG2-311 GEN
50/50
4.8
3147123OTTER R
Solar/Wind Harmer
0.184
3147312GRETNA
Solar/Wind Harmer
0.194
3146802CHATHAM
Solar/Wind Harmer
0.182
941801AE2-185 GEN
Solar/Wind Harmer
7.752
270173AC1-122 GEN
Solar/Wind Harmer
0.243
962751AG1-124 GEN
Solar/Wind Harmer
3.521
270574AD1-017 GEN2
Solar/Wind Harmer
0
316003AC1-222 GEN
Solar/Wind Helper
1.905
316237AB2-079_GEN
Solar/Wind Helper
0.188
315687AD1-152 GEN
Solar/Wind Helper
0.645
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.077
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.522
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.969
MECLTFEXP_MEC->PJM
CLTF
0.978
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.468
WECLTFEXP_WEC->PJM
CLTF
0.232
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.458
LAGNLTFEXP_LAGN->PJM
CLTF
0.878
TVALTFEXP_TVA->PJM
CLTF
0.49

Details for 3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.67 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:355.84
MW Contribution:6.96
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.207
270173AC1-122 GEN
Solar/Wind Harmer
1.179
962751AG1-124 GEN
Solar/Wind Harmer
5.14
270574AD1-017 GEN2
Solar/Wind Harmer
2.781
316003AC1-222 GEN
Solar/Wind Helper
1.905
316237AB2-079_GEN
Solar/Wind Helper
0.188
315687AD1-152 GEN
Solar/Wind Helper
0.645
970865AG2-541 GEN
Solar/Wind Harmer
35.586
316123AC1-075 GEN
Solar/Wind Harmer
7.9
970165AG2-112 GEN
Solar/Wind Harmer
6.955
970163AG2-111 GEN
Solar/Wind Harmer
6.635
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.036
316239AB2-077_GEN
Solar/Wind Helper
0.188
316238AB2-078_GEN
Solar/Wind Helper
0.188
3144303KENBRDG
Solar/Wind Helper
0.094
942751AE2-291 GEN
Solar/Wind Harmer
40.863
316217AC1-145 GEN
Solar/Wind Harmer
4.418
316197AC1-042 GEN
Solar/Wind Harmer
3.349
942671AE2-283 GEN
Solar/Wind Harmer
9.016
3146843MT LREL
Solar/Wind Helper
0.233
3146843MT LREL
Solar/Wind Helper
0.233
316034AC1-036 C
Solar/Wind Helper
0.123
24728405LEESVG
50/50
0.206
971683AH1-343 GEN
Solar/Wind Harmer
40.822
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.207
270197AD1-017 GEN1
Solar/Wind Harmer
0.836
958131AF2-107 GEN
Solar/Wind Harmer
2.275
316248AF1-058 C
Solar/Wind Helper
0.404
316131AB2-060 GEN
Solar/Wind Helper
0.823
315785AD2-033 C
Solar/Wind Helper
1.41
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.077
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.517
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.967
MECLTFEXP_MEC->PJM
CLTF
0.977
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.468
WECLTFEXP_WEC->PJM
CLTF
0.231
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.459
LAGNLTFEXP_LAGN->PJM
CLTF
0.877
TVALTFEXP_TVA->PJM
CLTF
0.489

Details for 3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.31 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:354.59
MW Contribution:6.96
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.206
971683AH1-343 GEN
Solar/Wind Harmer
40.823
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.207
270197AD1-017 GEN1
Solar/Wind Harmer
0.836
958131AF2-107 GEN
Solar/Wind Harmer
2.276
316248AF1-058 C
Solar/Wind Helper
0.404
316131AB2-060 GEN
Solar/Wind Helper
0.823
315785AD2-033 C
Solar/Wind Helper
1.409
970865AG2-541 GEN
Solar/Wind Harmer
35.587
316123AC1-075 GEN
Solar/Wind Harmer
7.9
970165AG2-112 GEN
Solar/Wind Harmer
6.956
970163AG2-111 GEN
Solar/Wind Harmer
6.635
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.036
316239AB2-077_GEN
Solar/Wind Helper
0.188
316238AB2-078_GEN
Solar/Wind Helper
0.188
3144303KENBRDG
Solar/Wind Helper
0.094
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.207
270173AC1-122 GEN
Solar/Wind Harmer
1.179
962751AG1-124 GEN
Solar/Wind Harmer
5.141
270574AD1-017 GEN2
Solar/Wind Harmer
2.781
316003AC1-222 GEN
Solar/Wind Helper
1.905
316237AB2-079_GEN
Solar/Wind Helper
0.188
315687AD1-152 GEN
Solar/Wind Helper
0.645
942751AE2-291 GEN
Solar/Wind Harmer
40.865
316217AC1-145 GEN
Solar/Wind Harmer
4.418
316197AC1-042 GEN
Solar/Wind Harmer
3.349
942671AE2-283 GEN
Solar/Wind Harmer
9.017
3146843MT LREL
Solar/Wind Helper
0.232
3146843MT LREL
Solar/Wind Helper
0.232
316034AC1-036 C
Solar/Wind Helper
0.123
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.077
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.521
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.969
MECLTFEXP_MEC->PJM
CLTF
0.978
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.468
WECLTFEXP_WEC->PJM
CLTF
0.232
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.458
LAGNLTFEXP_LAGN->PJM
CLTF
0.878
TVALTFEXP_TVA->PJM
CLTF
0.49

Details for 3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.3 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:354.55
MW Contribution:6.96
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.587
316123AC1-075 GEN
Solar/Wind Harmer
7.9
970165AG2-112 GEN
Solar/Wind Harmer
6.956
970163AG2-111 GEN
Solar/Wind Harmer
6.635
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.036
316239AB2-077_GEN
Solar/Wind Helper
0.188
316238AB2-078_GEN
Solar/Wind Helper
0.188
3144303KENBRDG
Solar/Wind Helper
0.094
942751AE2-291 GEN
Solar/Wind Harmer
40.865
316217AC1-145 GEN
Solar/Wind Harmer
4.418
316197AC1-042 GEN
Solar/Wind Harmer
3.349
942671AE2-283 GEN
Solar/Wind Harmer
9.017
3146843MT LREL
Solar/Wind Helper
0.232
3146843MT LREL
Solar/Wind Helper
0.232
316034AC1-036 C
Solar/Wind Helper
0.123
24728405LEESVG
50/50
0.206
971683AH1-343 GEN
Solar/Wind Harmer
40.823
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.207
270197AD1-017 GEN1
Solar/Wind Harmer
0.836
958131AF2-107 GEN
Solar/Wind Harmer
2.276
316248AF1-058 C
Solar/Wind Helper
0.404
316131AB2-060 GEN
Solar/Wind Helper
0.823
315785AD2-033 C
Solar/Wind Helper
1.409
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.207
270173AC1-122 GEN
Solar/Wind Harmer
1.179
962751AG1-124 GEN
Solar/Wind Harmer
5.141
270574AD1-017 GEN2
Solar/Wind Harmer
2.781
316003AC1-222 GEN
Solar/Wind Helper
1.905
316237AB2-079_GEN
Solar/Wind Helper
0.188
315687AD1-152 GEN
Solar/Wind Helper
0.645
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.077
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.522
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.969
MECLTFEXP_MEC->PJM
CLTF
0.978
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.468
WECLTFEXP_WEC->PJM
CLTF
0.232
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.458
LAGNLTFEXP_LAGN->PJM
CLTF
0.878
TVALTFEXP_TVA->PJM
CLTF
0.49

Details for 3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.59 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:352.07
MW Contribution:6.96
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.769
24728405LEESVG
50/50
0.229
24684705SMG5
50/50
0.437
970481AG2-311 GEN
50/50
6.086
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.665
270574AD1-017 GEN2
Solar/Wind Harmer
5.101
270016AE1-250 BESS
Solar/Wind Harmer
2.264
970223AG2-152 GEN
Solar/Wind Harmer
13.058
270173AC1-122 GEN
Solar/Wind Harmer
1.401
962751AG1-124 GEN
Solar/Wind Harmer
5.108
316003AC1-222 GEN
Solar/Wind Helper
1.949
316237AB2-079_GEN
Solar/Wind Helper
0.202
315687AD1-152 GEN
Solar/Wind Helper
0.724
970865AG2-541 GEN
Solar/Wind Harmer
35.485
316123AC1-075 GEN
Solar/Wind Harmer
7.909
970165AG2-112 GEN
Solar/Wind Harmer
6.964
970163AG2-111 GEN
Solar/Wind Harmer
6.643
3147173SINAI
Solar/Wind Helper
0.314
3147243WELCO
Solar/Wind Helper
0.196
316118AC1-105 GEN
Solar/Wind Helper
1.086
316239AB2-077_GEN
Solar/Wind Helper
0.202
316238AB2-078_GEN
Solar/Wind Helper
0.202
3144303KENBRDG
Solar/Wind Helper
0.1
24684405SMG2
50/50
1.134
24684505SMG3
50/50
0.701
24684305SMG1
50/50
0.411
942751AE2-291 GEN
Solar/Wind Harmer
41.056
316217AC1-145 GEN
Solar/Wind Harmer
4.616
316197AC1-042 GEN
Solar/Wind Harmer
3.499
942671AE2-283 GEN
Solar/Wind Harmer
9.42
270013AE1-250 PV
Solar/Wind Harmer
2.264
3146843MT LREL
Solar/Wind Helper
0.245
3146843MT LREL
Solar/Wind Helper
0.245
316034AC1-036 C
Solar/Wind Helper
0.131
24728405LEESVG
50/50
0.23
24684605SMG4
50/50
1.141
971683AH1-343 GEN
Solar/Wind Harmer
40.643
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.665
270197AD1-017 GEN1
Solar/Wind Harmer
1.533
958131AF2-107 GEN
Solar/Wind Harmer
2.307
316248AF1-058 C
Solar/Wind Helper
0.422
316131AB2-060 GEN
Solar/Wind Helper
0.886
315785AD2-033 C
Solar/Wind Helper
1.508
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.376
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.996
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.824
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.391
MECLTFEXP_MEC->PJM
CLTF
0.467
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.1
LGEELTFEXP_LGEE->PJM
CLTF
0.269
WECLTFEXP_WEC->PJM
CLTF
0.129
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.998
TVALTFEXP_TVA->PJM
CLTF
0.041
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.18 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:331.99
MW Contribution:5.28
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
0.892
24684505SMG3
50/50
0.552
24684305SMG1
50/50
0.323
942751AE2-291 GEN
Solar/Wind Harmer
31.022
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.003
942671AE2-283 GEN
Solar/Wind Harmer
6.023
970865AG2-541 GEN
Solar/Wind Harmer
27.019
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
5.281
970163AG2-111 GEN
Solar/Wind Harmer
5.037
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.038
316239AB2-077_GEN
Solar/Wind Helper
0.189
316238AB2-078_GEN
Solar/Wind Helper
0.189
3144303KENBRDG
Solar/Wind Helper
0.094
24728405LEESVG
50/50
0.206
24684605SMG4
50/50
0.898
24288905REUSENS
50/50
0.018
966251AG1-494 GEN
50/50
1.295
971683AH1-343 GEN
Solar/Wind Harmer
30.996
3147312GRETNA
Solar/Wind Harmer
0.048
941821AE2-187 GEN
Solar/Wind Harmer
7.744
270197AD1-017 GEN1
Solar/Wind Harmer
0.467
958131AF2-107 GEN
Solar/Wind Harmer
1.702
316248AF1-058 C
Solar/Wind Helper
0.405
316131AB2-060 GEN
Solar/Wind Helper
0.826
315785AD2-033 C
Solar/Wind Helper
1.415
3146843MT LREL
Solar/Wind Helper
0.233
3146843MT LREL
Solar/Wind Helper
0.233
316034AC1-036 C
Solar/Wind Helper
0.123
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
24684705SMG5
50/50
0.344
970481AG2-311 GEN
50/50
4.788
316003AC1-222 GEN
Solar/Wind Harmer
0.024
3147123OTTER R
Solar/Wind Harmer
0.184
3147312GRETNA
Solar/Wind Harmer
0.193
3146802CHATHAM
Solar/Wind Harmer
0.181
941801AE2-185 GEN
Solar/Wind Harmer
7.744
270173AC1-122 GEN
Solar/Wind Harmer
0.243
962751AG1-124 GEN
Solar/Wind Harmer
3.509
270574AD1-017 GEN2
Solar/Wind Harmer
0
316237AB2-079_GEN
Solar/Wind Helper
0.189
315687AD1-152 GEN
Solar/Wind Helper
0.648
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.748
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.233
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.894
MECLTFEXP_MEC->PJM
CLTF
0.944
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.2
LGEELTFEXP_LGEE->PJM
CLTF
0.454
WECLTFEXP_WEC->PJM
CLTF
0.224
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.472
LAGNLTFEXP_LAGN->PJM
CLTF
0.838
TVALTFEXP_TVA->PJM
CLTF
0.47

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.55 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:393.92
MW Contribution:6.95
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.574
316123AC1-075 GEN
Solar/Wind Harmer
7.896
970165AG2-112 GEN
Solar/Wind Harmer
6.953
970163AG2-111 GEN
Solar/Wind Harmer
6.633
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.038
316239AB2-077_GEN
Solar/Wind Helper
0.189
316238AB2-078_GEN
Solar/Wind Helper
0.189
3144303KENBRDG
Solar/Wind Helper
0.095
24728405LEESVG
50/50
0.206
971683AH1-343 GEN
Solar/Wind Harmer
40.81
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.196
270197AD1-017 GEN1
Solar/Wind Harmer
0.833
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.405
316131AB2-060 GEN
Solar/Wind Helper
0.827
315785AD2-033 C
Solar/Wind Helper
1.416
942751AE2-291 GEN
Solar/Wind Harmer
40.845
316217AC1-145 GEN
Solar/Wind Harmer
4.413
316197AC1-042 GEN
Solar/Wind Harmer
3.345
942671AE2-283 GEN
Solar/Wind Harmer
9.006
3146843MT LREL
Solar/Wind Helper
0.233
3146843MT LREL
Solar/Wind Helper
0.233
316034AC1-036 C
Solar/Wind Helper
0.123
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
316003AC1-222 GEN
Solar/Wind Harmer
9.904
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.196
270173AC1-122 GEN
Solar/Wind Harmer
1.176
962751AG1-124 GEN
Solar/Wind Harmer
5.122
270574AD1-017 GEN2
Solar/Wind Harmer
2.771
316237AB2-079_GEN
Solar/Wind Helper
0.189
315687AD1-152 GEN
Solar/Wind Helper
0.648
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.741
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.228
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.892
MECLTFEXP_MEC->PJM
CLTF
0.944
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.2
LGEELTFEXP_LGEE->PJM
CLTF
0.454
WECLTFEXP_WEC->PJM
CLTF
0.224
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.472
LAGNLTFEXP_LAGN->PJM
CLTF
0.837
TVALTFEXP_TVA->PJM
CLTF
0.469

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.19 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:392.67
MW Contribution:6.95
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.575
316123AC1-075 GEN
Solar/Wind Harmer
7.897
970165AG2-112 GEN
Solar/Wind Harmer
6.953
970163AG2-111 GEN
Solar/Wind Harmer
6.633
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.038
316239AB2-077_GEN
Solar/Wind Helper
0.189
316238AB2-078_GEN
Solar/Wind Helper
0.189
3144303KENBRDG
Solar/Wind Helper
0.094
24728405LEESVG
50/50
0.206
971683AH1-343 GEN
Solar/Wind Harmer
40.811
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.197
270197AD1-017 GEN1
Solar/Wind Harmer
0.833
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.405
316131AB2-060 GEN
Solar/Wind Helper
0.826
315785AD2-033 C
Solar/Wind Helper
1.415
942751AE2-291 GEN
Solar/Wind Harmer
40.846
316217AC1-145 GEN
Solar/Wind Harmer
4.413
316197AC1-042 GEN
Solar/Wind Harmer
3.345
942671AE2-283 GEN
Solar/Wind Harmer
9.007
3146843MT LREL
Solar/Wind Helper
0.233
3146843MT LREL
Solar/Wind Helper
0.233
316034AC1-036 C
Solar/Wind Helper
0.123
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
316003AC1-222 GEN
Solar/Wind Harmer
9.905
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.197
270173AC1-122 GEN
Solar/Wind Harmer
1.176
962751AG1-124 GEN
Solar/Wind Harmer
5.123
270574AD1-017 GEN2
Solar/Wind Harmer
2.771
316237AB2-079_GEN
Solar/Wind Helper
0.189
315687AD1-152 GEN
Solar/Wind Helper
0.648
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.747
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.233
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.894
MECLTFEXP_MEC->PJM
CLTF
0.944
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.2
LGEELTFEXP_LGEE->PJM
CLTF
0.454
WECLTFEXP_WEC->PJM
CLTF
0.224
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.472
LAGNLTFEXP_LAGN->PJM
CLTF
0.838
TVALTFEXP_TVA->PJM
CLTF
0.47

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.18 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:392.63
MW Contribution:6.95
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
316003AC1-222 GEN
Solar/Wind Harmer
9.905
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.197
270173AC1-122 GEN
Solar/Wind Harmer
1.176
962751AG1-124 GEN
Solar/Wind Harmer
5.123
270574AD1-017 GEN2
Solar/Wind Harmer
2.771
316237AB2-079_GEN
Solar/Wind Helper
0.189
315687AD1-152 GEN
Solar/Wind Helper
0.648
970865AG2-541 GEN
Solar/Wind Harmer
35.575
316123AC1-075 GEN
Solar/Wind Harmer
7.897
970165AG2-112 GEN
Solar/Wind Harmer
6.953
970163AG2-111 GEN
Solar/Wind Harmer
6.633
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.038
316239AB2-077_GEN
Solar/Wind Helper
0.189
316238AB2-078_GEN
Solar/Wind Helper
0.189
3144303KENBRDG
Solar/Wind Helper
0.094
942751AE2-291 GEN
Solar/Wind Harmer
40.846
316217AC1-145 GEN
Solar/Wind Harmer
4.413
316197AC1-042 GEN
Solar/Wind Harmer
3.346
942671AE2-283 GEN
Solar/Wind Harmer
9.007
3146843MT LREL
Solar/Wind Helper
0.233
3146843MT LREL
Solar/Wind Helper
0.233
316034AC1-036 C
Solar/Wind Helper
0.123
24728405LEESVG
50/50
0.206
971683AH1-343 GEN
Solar/Wind Harmer
40.811
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.197
270197AD1-017 GEN1
Solar/Wind Harmer
0.833
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.405
316131AB2-060 GEN
Solar/Wind Helper
0.826
315785AD2-033 C
Solar/Wind Helper
1.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.748
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.233
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.894
MECLTFEXP_MEC->PJM
CLTF
0.944
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.2
LGEELTFEXP_LGEE->PJM
CLTF
0.454
WECLTFEXP_WEC->PJM
CLTF
0.224
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.472
LAGNLTFEXP_LAGN->PJM
CLTF
0.838
TVALTFEXP_TVA->PJM
CLTF
0.47

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.45 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:390.08
MW Contribution:6.96
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.229
24684605SMG4
50/50
1.139
971683AH1-343 GEN
Solar/Wind Harmer
40.631
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.654
270197AD1-017 GEN1
Solar/Wind Harmer
1.53
958131AF2-107 GEN
Solar/Wind Harmer
2.297
316248AF1-058 C
Solar/Wind Helper
0.423
316131AB2-060 GEN
Solar/Wind Helper
0.889
315785AD2-033 C
Solar/Wind Helper
1.513
3151561HALLBR1
50/50
0.769
24728405LEESVG
50/50
0.228
24684705SMG5
50/50
0.436
970481AG2-311 GEN
50/50
6.074
316003AC1-222 GEN
Solar/Wind Harmer
9.848
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.654
270574AD1-017 GEN2
Solar/Wind Harmer
5.091
270016AE1-250 BESS
Solar/Wind Harmer
2.26
970223AG2-152 GEN
Solar/Wind Harmer
13.033
270173AC1-122 GEN
Solar/Wind Harmer
1.398
962751AG1-124 GEN
Solar/Wind Harmer
5.091
316237AB2-079_GEN
Solar/Wind Helper
0.203
315687AD1-152 GEN
Solar/Wind Helper
0.727
24684405SMG2
50/50
1.132
24684505SMG3
50/50
0.7
24684305SMG1
50/50
0.41
942751AE2-291 GEN
Solar/Wind Harmer
41.038
316217AC1-145 GEN
Solar/Wind Harmer
4.611
316197AC1-042 GEN
Solar/Wind Harmer
3.495
942671AE2-283 GEN
Solar/Wind Harmer
9.411
270013AE1-250 PV
Solar/Wind Harmer
2.26
3146843MT LREL
Solar/Wind Helper
0.245
3146843MT LREL
Solar/Wind Helper
0.245
316034AC1-036 C
Solar/Wind Helper
0.132
970865AG2-541 GEN
Solar/Wind Harmer
35.473
316123AC1-075 GEN
Solar/Wind Harmer
7.906
970165AG2-112 GEN
Solar/Wind Harmer
6.961
970163AG2-111 GEN
Solar/Wind Harmer
6.641
3147173SINAI
Solar/Wind Helper
0.315
3147243WELCO
Solar/Wind Helper
0.197
316118AC1-105 GEN
Solar/Wind Helper
1.088
316239AB2-077_GEN
Solar/Wind Helper
0.203
316238AB2-078_GEN
Solar/Wind Helper
0.203
3144303KENBRDG
Solar/Wind Helper
0.101
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.384
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.316
MECLTFEXP_MEC->PJM
CLTF
0.433
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.113
LGEELTFEXP_LGEE->PJM
CLTF
0.256
WECLTFEXP_WEC->PJM
CLTF
0.121
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.011
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.96 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:384.85
MW Contribution:6.98
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.382
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.7 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:383.94
MW Contribution:6.98
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.382
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.69 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:383.92
MW Contribution:6.98
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24684405SMG2
50/50
1.116
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.383
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.445
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.019
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.38 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:306.86
MW Contribution:5.24
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
26.894
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
5.243
970163AG2-111 GEN
Solar/Wind Harmer
5.001
3147173SINAI
Solar/Wind Helper
0.305
3147243WELCO
Solar/Wind Helper
0.191
316118AC1-105 GEN
Solar/Wind Helper
1.051
316239AB2-077_GEN
Solar/Wind Helper
0.19
316238AB2-078_GEN
Solar/Wind Helper
0.19
3144303KENBRDG
Solar/Wind Helper
0.094
24728405LEESVG
50/50
0.195
24684605SMG4
50/50
0.822
24288905REUSENS
50/50
0.016
966251AG1-494 GEN
50/50
1.151
971683AH1-343 GEN
Solar/Wind Harmer
30.882
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.488
270197AD1-017 GEN1
Solar/Wind Harmer
0.418
316248AF1-058 C
Solar/Wind Helper
0.41
316131AB2-060 GEN
Solar/Wind Helper
0.829
315785AD2-033 C
Solar/Wind Helper
1.406
3151561HALLBR1
50/50
0.725
24728405LEESVG
50/50
0.195
24684705SMG5
50/50
0.314
970481AG2-311 GEN
50/50
4.381
316003AC1-222 GEN
Solar/Wind Harmer
0.024
3147123OTTER R
Solar/Wind Harmer
0.179
3147312GRETNA
Solar/Wind Harmer
0.187
3146802CHATHAM
Solar/Wind Harmer
0.175
941801AE2-185 GEN
Solar/Wind Harmer
7.488
270173AC1-122 GEN
Solar/Wind Harmer
0.22
962751AG1-124 GEN
Solar/Wind Harmer
3.082
270574AD1-017 GEN2
Solar/Wind Harmer
0
316237AB2-079_GEN
Solar/Wind Helper
0.19
315687AD1-152 GEN
Solar/Wind Helper
0.658
24684405SMG2
50/50
0.816
24684505SMG3
50/50
0.505
24684305SMG1
50/50
0.296
942751AE2-291 GEN
Solar/Wind Harmer
30.733
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.824
3146843MT LREL
Solar/Wind Helper
0.236
3146843MT LREL
Solar/Wind Helper
0.236
316034AC1-036 C
Solar/Wind Helper
0.122
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.22
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.709
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.664
MECLTFEXP_MEC->PJM
CLTF
0.482
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.114
LGEELTFEXP_LGEE->PJM
CLTF
0.255
WECLTFEXP_WEC->PJM
CLTF
0.124
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.654
LAGNLTFEXP_LAGN->PJM
CLTF
0.196
TVALTFEXP_TVA->PJM
CLTF
0.134

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.51 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:369.27
MW Contribution:7.43
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.04
24684505SMG3
50/50
0.643
24684305SMG1
50/50
0.377
942751AE2-291 GEN
Solar/Wind Harmer
44.58
316217AC1-145 GEN
Solar/Wind Harmer
5.995
316197AC1-042 GEN
Solar/Wind Harmer
4.545
942671AE2-283 GEN
Solar/Wind Harmer
12.236
3146843MT LREL
Solar/Wind Helper
0.208
3146843MT LREL
Solar/Wind Helper
0.208
3151561HALLBR1
50/50
0.945
24728405LEESVG
50/50
0.266
24684705SMG5
50/50
0.401
970481AG2-311 GEN
50/50
5.583
316003AC1-222 GEN
Solar/Wind Harmer
10.144
3147123OTTER R
Solar/Wind Harmer
-0.025
3147312GRETNA
Solar/Wind Harmer
-0.03
3146802CHATHAM
Solar/Wind Harmer
-0.028
941801AE2-185 GEN
Solar/Wind Harmer
13.852
270173AC1-122 GEN
Solar/Wind Harmer
1.159
270574AD1-017 GEN2
Solar/Wind Harmer
3.24
316237AB2-079_GEN
Solar/Wind Helper
0.166
970865AG2-541 GEN
Solar/Wind Harmer
37.085
316123AC1-075 GEN
Solar/Wind Harmer
8.439
970165AG2-112 GEN
Solar/Wind Harmer
7.43
970163AG2-111 GEN
Solar/Wind Harmer
7.088
3147173SINAI
Solar/Wind Helper
0.271
3147243WELCO
Solar/Wind Helper
0.169
316118AC1-105 GEN
Solar/Wind Helper
0.93
316239AB2-077_GEN
Solar/Wind Helper
0.166
316238AB2-078_GEN
Solar/Wind Helper
0.166
24728405LEESVG
50/50
0.267
24684605SMG4
50/50
1.047
971683AH1-343 GEN
Solar/Wind Harmer
42.136
3147312GRETNA
Solar/Wind Harmer
-0.007
941821AE2-187 GEN
Solar/Wind Harmer
13.852
270197AD1-017 GEN1
Solar/Wind Harmer
0.973
316248AF1-058 C
Solar/Wind Helper
0.364
316131AB2-060 GEN
Solar/Wind Helper
0.725
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.175
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.905
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.465
MECLTFEXP_MEC->PJM
CLTF
0.347
SIGELTFEXP_SIGE->PJM
CLTF
0.013
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.187
WECLTFEXP_WEC->PJM
CLTF
0.09
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.518
LAGNLTFEXP_LAGN->PJM
CLTF
0.125
TVALTFEXP_TVA->PJM
CLTF
0.091

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P7-1_#10781___SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10781___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.7 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:359.46
MW Contribution:6.9
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.743
24728405LEESVG
50/50
0.21
316003AC1-222 GEN
Solar/Wind Harmer
9.819
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.198
270173AC1-122 GEN
Solar/Wind Harmer
1.218
270574AD1-017 GEN2
Solar/Wind Harmer
3.601
270016AE1-250 BESS
Solar/Wind Harmer
1.363
970223AG2-152 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
4.804
316237AB2-079_GEN
Solar/Wind Helper
0.205
315687AD1-152 GEN
Solar/Wind Helper
0.735
970865AG2-541 GEN
Solar/Wind Harmer
35.284
316123AC1-075 GEN
Solar/Wind Harmer
7.837
970165AG2-112 GEN
Solar/Wind Harmer
6.901
970163AG2-111 GEN
Solar/Wind Harmer
6.583
3147173SINAI
Solar/Wind Helper
0.318
3147243WELCO
Solar/Wind Helper
0.199
316118AC1-105 GEN
Solar/Wind Helper
1.1
316239AB2-077_GEN
Solar/Wind Helper
0.205
316238AB2-078_GEN
Solar/Wind Helper
0.205
3144303KENBRDG
Solar/Wind Helper
0.102
942751AE2-291 GEN
Solar/Wind Harmer
40.562
316217AC1-145 GEN
Solar/Wind Harmer
4.414
316197AC1-042 GEN
Solar/Wind Harmer
3.346
942671AE2-283 GEN
Solar/Wind Harmer
9.009
270013AE1-250 PV
Solar/Wind Harmer
1.363
3146843MT LREL
Solar/Wind Helper
0.248
3146843MT LREL
Solar/Wind Helper
0.248
316034AC1-036 C
Solar/Wind Helper
0.133
24728405LEESVG
50/50
0.21
971683AH1-343 GEN
Solar/Wind Harmer
40.466
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.198
270197AD1-017 GEN1
Solar/Wind Harmer
1.082
958131AF2-107 GEN
Solar/Wind Harmer
2.161
316248AF1-058 C
Solar/Wind Helper
0.428
316131AB2-060 GEN
Solar/Wind Helper
0.9
315785AD2-033 C
Solar/Wind Helper
1.533
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.373
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.967
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.446
MECLTFEXP_MEC->PJM
CLTF
0.486
SIGELTFEXP_SIGE->PJM
CLTF
0.019
NYPJM->LTFIMP_NY
CLTF
0.114
LGEELTFEXP_LGEE->PJM
CLTF
0.278
WECLTFEXP_WEC->PJM
CLTF
0.133
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.003
LAGNLTFEXP_LAGN->PJM
CLTF
0.016
TVALTFEXP_TVA->PJM
CLTF
0.056
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T296_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: H2T296_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.91 %
Rating:264.1 MVA
Rating Type:C
MVA to Mitigate:345.73
MW Contribution:3.96
Bus #Bus NameTypeMW Contribution
316248AF1-058 C
Solar/Wind Harmer
1.877
960061AF2-297 GEN
Solar/Wind Harmer
31.144
971683AH1-343 GEN
Solar/Wind Harmer
23.245
316131AB2-060 GEN
Solar/Wind Harmer
1.756
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.751
964241AG1-285 GEN
Solar/Wind Harmer
11.675
315785AD2-033 C
Solar/Wind Harmer
2.901
970257AG2-171 GEN
Solar/Wind Harmer
4.495
959311AF2-222 GEN
Solar/Wind Harmer
11.882
963181AG1-167 GEN
Solar/Wind Harmer
0.75
3144293JTRSVLE
Adder
0.227
3147043LAWRENC
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.021
971193AH1-056 GEN
Solar/Wind Harmer
4.15
316478AD1-087 GEN
Solar/Wind Helper
0.983
316486AD2-202 GEN
Solar/Wind Helper
0.288
3151561HALLBR1
50/50
0.421
316003AC1-222 GEN
Solar/Wind Harmer
5.643
970401AG2-262 GEN
Solar/Wind Harmer
2.816
3147123OTTER R
Solar/Wind Harmer
-0.012
316237AB2-079_GEN
Solar/Wind Harmer
0.529
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.751
970685AG2-442 GEN
Solar/Wind Harmer
8.682
963171AG1-166 GEN
Solar/Wind Harmer
1
971563AH1-280 GEN
Solar/Wind Harmer
1
3144293JTRSVLE
Adder
0.227
3147043LAWRENC
Adder
0.567
315687AD1-152 GEN
Solar/Wind Helper
1.765
3152661PLYWOOD A
50/50
1.051
3146843MT LREL
Solar/Wind Harmer
-0.043
3146843MT LREL
Solar/Wind Harmer
-0.043
964791AG1-342 GEN
Solar/Wind Harmer
9.217
962561AG1-105 GEN
Solar/Wind Harmer
21.992
942751AE2-291 GEN
Solar/Wind Harmer
23.22
313527AB2-043 GEN
Solar/Wind Harmer
2.693
316217AC1-145 GEN
Solar/Wind Harmer
2.489
316197AC1-042 GEN
Solar/Wind Harmer
1.887
942671AE2-283 GEN
Solar/Wind Harmer
5.08
970323AG2-213 GEN
Solar/Wind Harmer
5.994
971775AH1-396 GEN
Solar/Wind Harmer
0.854
316034AC1-036 C
Solar/Wind Harmer
0.222
939181AE1-148 GEN
Solar/Wind Harmer
5.107
958211AF2-115 GEN
Solar/Wind Harmer
1.25
963191AG1-168 GEN
Solar/Wind Harmer
0.75
3144293JTRSVLE
Adder
0.227
3144293JTRSVLE
Adder
0.191
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3147173SINAI
Solar/Wind Harmer
-0.062
3147243WELCO
Solar/Wind Harmer
-0.039
316118AC1-105 GEN
Solar/Wind Harmer
3.636
970865AG2-541 GEN
Solar/Wind Harmer
20.256
316123AC1-075 GEN
Solar/Wind Harmer
4.492
970165AG2-112 GEN
Solar/Wind Harmer
3.956
970163AG2-111 GEN
Solar/Wind Harmer
3.773
316239AB2-077_GEN
Solar/Wind Harmer
0.529
316238AB2-078_GEN
Solar/Wind Harmer
0.529
971443AH1-215 GEN
Solar/Wind Harmer
2.392
3144303KENBRDG
Solar/Wind Harmer
-0.01
970683AG2-441 GEN
Solar/Wind Harmer
7.751
970681AG2-440 GEN
Solar/Wind Harmer
6.201
946301AF1-294 GEN
Solar/Wind Harmer
2.049
961791AG1-021 GEN
Solar/Wind Harmer
1
315657AE1-056 GEN
Solar/Wind Harmer
2.49
CPLELTFEXP_CPLE->PJM
CLTF
0.132
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.769
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.734
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.413
MECLTFEXP_MEC->PJM
CLTF
0.581
SIGELTFEXP_SIGE->PJM
CLTF
0.019
NYPJM->LTFIMP_NY
CLTF
0.138
LGEELTFEXP_LGEE->PJM
CLTF
0.257
WECLTFEXP_WEC->PJM
CLTF
0.13
LAGNLTFEXP_LAGN->PJM
CLTF
0.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.718
TVALTFEXP_TVA->PJM
CLTF
0.377

Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: SEDGE H T452_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-6: SEDGE H T452_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.8 %
Rating:264.1 MVA
Rating Type:C
MVA to Mitigate:345.45
MW Contribution:4.41
Bus #Bus NameTypeMW Contribution
316248AF1-058 C
Solar/Wind Harmer
2.11
960061AF2-297 GEN
Solar/Wind Harmer
35.005
971683AH1-343 GEN
Solar/Wind Harmer
26.063
316131AB2-060 GEN
Solar/Wind Harmer
2.174
964241AG1-285 GEN
Solar/Wind Harmer
14.639
315785AD2-033 C
Solar/Wind Harmer
3.731
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.153
970257AG2-171 GEN
Solar/Wind Harmer
5.85
959311AF2-222 GEN
Solar/Wind Harmer
15.614
963181AG1-167 GEN
Solar/Wind Harmer
1.065
3144293JTRSVLE
Adder
0.322
3147133PAMPLIN
Solar/Wind Harmer
-0.031
971193AH1-056 GEN
Solar/Wind Harmer
6.202
3147043LAWRENC
Solar/Wind Harmer
-0.005
316283AC2-100 C
Solar/Wind Helper
0.615
3151561HALLBR1
50/50
0.455
316003AC1-222 GEN
Solar/Wind Harmer
6.335
970401AG2-262 GEN
Solar/Wind Harmer
3.216
316237AB2-079_GEN
Solar/Wind Harmer
0.648
3147123OTTER R
Solar/Wind Harmer
-0.013
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.153
970685AG2-442 GEN
Solar/Wind Harmer
11.731
963171AG1-166 GEN
Solar/Wind Harmer
1.421
971563AH1-280 GEN
Solar/Wind Harmer
1.421
3144293JTRSVLE
Adder
0.322
3147043LAWRENC
Adder
0.723
971065AG2-659 GEN
Solar/Wind Harmer
3.959
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971795AH1-408 GEN
Solar/Wind Harmer
5.546
315687AD1-152 GEN
Solar/Wind Helper
0.95
3152661PLYWOOD A
50/50
1.189
970535AG2-341 GEN
50/50
2.368
3146843MT LREL
Solar/Wind Harmer
-0.049
3146843MT LREL
Solar/Wind Harmer
-0.049
964791AG1-342 GEN
Solar/Wind Harmer
10.524
962561AG1-105 GEN
Solar/Wind Harmer
25.243
942751AE2-291 GEN
Solar/Wind Harmer
25.811
313527AB2-043 GEN
Solar/Wind Harmer
3.325
316217AC1-145 GEN
Solar/Wind Harmer
2.663
316197AC1-042 GEN
Solar/Wind Harmer
2.019
942671AE2-283 GEN
Solar/Wind Harmer
5.435
970323AG2-213 GEN
Solar/Wind Harmer
7.8
971775AH1-396 GEN
Solar/Wind Harmer
1.111
316034AC1-036 C
Solar/Wind Harmer
0.288
939181AE1-148 GEN
Solar/Wind Harmer
6.731
958211AF2-115 GEN
Solar/Wind Harmer
1.776
963191AG1-168 GEN
Solar/Wind Harmer
1.065
3144293JTRSVLE
Adder
0.322
3144293JTRSVLE
Adder
0.271
3147133PAMPLIN
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Helper
0.679
3147173SINAI
Solar/Wind Harmer
-0.07
3147243WELCO
Solar/Wind Harmer
-0.043
316118AC1-105 GEN
Solar/Wind Harmer
4.113
970865AG2-541 GEN
Solar/Wind Harmer
22.679
316123AC1-075 GEN
Solar/Wind Harmer
5.01
970165AG2-112 GEN
Solar/Wind Harmer
4.412
970163AG2-111 GEN
Solar/Wind Harmer
4.208
316239AB2-077_GEN
Solar/Wind Harmer
0.648
316238AB2-078_GEN
Solar/Wind Harmer
0.648
971443AH1-215 GEN
Solar/Wind Harmer
3.105
3144303KENBRDG
Solar/Wind Harmer
-0.012
970683AG2-441 GEN
Solar/Wind Harmer
10.474
970681AG2-440 GEN
Solar/Wind Harmer
8.379
946301AF1-294 GEN
Solar/Wind Harmer
2.912
961791AG1-021 GEN
Solar/Wind Harmer
1.421
315657AE1-056 GEN
Solar/Wind Harmer
3.721
970831AG2-522 GEN
Solar/Wind Harmer
3.505
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.384
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.384
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.822
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.06
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-5: SEDGE H L202_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-5: SEDGE H L202_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.8 %
Rating:264.1 MVA
Rating Type:C
MVA to Mitigate:345.45
MW Contribution:4.41
Bus #Bus NameTypeMW Contribution
316248AF1-058 C
Solar/Wind Harmer
2.11
960061AF2-297 GEN
Solar/Wind Harmer
35.005
971683AH1-343 GEN
Solar/Wind Harmer
26.063
316131AB2-060 GEN
Solar/Wind Harmer
2.174
964241AG1-285 GEN
Solar/Wind Harmer
14.639
315785AD2-033 C
Solar/Wind Harmer
3.731
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.153
970257AG2-171 GEN
Solar/Wind Harmer
5.85
959311AF2-222 GEN
Solar/Wind Harmer
15.614
963181AG1-167 GEN
Solar/Wind Harmer
1.065
3144293JTRSVLE
Adder
0.322
3147133PAMPLIN
Solar/Wind Harmer
-0.031
971193AH1-056 GEN
Solar/Wind Harmer
6.202
3147043LAWRENC
Solar/Wind Harmer
-0.005
316283AC2-100 C
Solar/Wind Helper
0.615
3147173SINAI
Solar/Wind Harmer
-0.07
3147243WELCO
Solar/Wind Harmer
-0.043
316118AC1-105 GEN
Solar/Wind Harmer
4.113
970865AG2-541 GEN
Solar/Wind Harmer
22.679
316123AC1-075 GEN
Solar/Wind Harmer
5.01
970165AG2-112 GEN
Solar/Wind Harmer
4.412
970163AG2-111 GEN
Solar/Wind Harmer
4.208
316239AB2-077_GEN
Solar/Wind Harmer
0.648
316238AB2-078_GEN
Solar/Wind Harmer
0.648
971443AH1-215 GEN
Solar/Wind Harmer
3.105
3144303KENBRDG
Solar/Wind Harmer
-0.012
970683AG2-441 GEN
Solar/Wind Harmer
10.474
970681AG2-440 GEN
Solar/Wind Harmer
8.379
946301AF1-294 GEN
Solar/Wind Harmer
2.912
961791AG1-021 GEN
Solar/Wind Harmer
1.421
315657AE1-056 GEN
Solar/Wind Harmer
3.721
970831AG2-522 GEN
Solar/Wind Harmer
3.505
3151561HALLBR1
50/50
0.455
316003AC1-222 GEN
Solar/Wind Harmer
6.335
970401AG2-262 GEN
Solar/Wind Harmer
3.216
316237AB2-079_GEN
Solar/Wind Harmer
0.648
3147123OTTER R
Solar/Wind Harmer
-0.013
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.153
970685AG2-442 GEN
Solar/Wind Harmer
11.731
963171AG1-166 GEN
Solar/Wind Harmer
1.421
971563AH1-280 GEN
Solar/Wind Harmer
1.421
3144293JTRSVLE
Adder
0.322
3147043LAWRENC
Adder
0.723
971065AG2-659 GEN
Solar/Wind Harmer
3.959
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971795AH1-408 GEN
Solar/Wind Harmer
5.546
315687AD1-152 GEN
Solar/Wind Helper
0.95
3152661PLYWOOD A
50/50
1.189
970535AG2-341 GEN
50/50
2.368
3146843MT LREL
Solar/Wind Harmer
-0.049
3146843MT LREL
Solar/Wind Harmer
-0.049
964791AG1-342 GEN
Solar/Wind Harmer
10.524
962561AG1-105 GEN
Solar/Wind Harmer
25.243
942751AE2-291 GEN
Solar/Wind Harmer
25.811
313527AB2-043 GEN
Solar/Wind Harmer
3.325
316217AC1-145 GEN
Solar/Wind Harmer
2.663
316197AC1-042 GEN
Solar/Wind Harmer
2.019
942671AE2-283 GEN
Solar/Wind Harmer
5.435
970323AG2-213 GEN
Solar/Wind Harmer
7.8
971775AH1-396 GEN
Solar/Wind Harmer
1.111
316034AC1-036 C
Solar/Wind Harmer
0.288
939181AE1-148 GEN
Solar/Wind Harmer
6.731
958211AF2-115 GEN
Solar/Wind Harmer
1.776
963191AG1-168 GEN
Solar/Wind Harmer
1.065
3144293JTRSVLE
Adder
0.322
3144293JTRSVLE
Adder
0.271
3147133PAMPLIN
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Helper
0.679
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.384
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.384
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.822
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.06
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-3: 6SEDGE HILL-TX#2_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.36 %
Rating:242.52 MVA
Rating Type:B
MVA to Mitigate:245.83
MW Contribution:3.35
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.186
3151621KERR 5
50/50
0.186
3151631KERR 6
50/50
0.186
3151641KERR 7
50/50
0.186
3147173SINAI
Solar/Wind Harmer
0.623
3147243WELCO
Solar/Wind Harmer
0.389
316118AC1-105 GEN
Solar/Wind Harmer
1.374
970865AG2-541 GEN
Solar/Wind Harmer
17.225
316123AC1-075 GEN
Solar/Wind Harmer
0.565
970165AG2-112 GEN
Solar/Wind Harmer
3.351
970163AG2-111 GEN
Solar/Wind Harmer
3.196
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
2.358
3144303KENBRDG
Solar/Wind Harmer
0.111
970683AG2-441 GEN
Solar/Wind Harmer
7.955
970681AG2-440 GEN
Solar/Wind Harmer
6.364
946301AF1-294 GEN
Solar/Wind Harmer
1.996
961791AG1-021 GEN
Solar/Wind Harmer
0.971
3144293JTRSVLE
50/50
0.342
24728405LEESVG
50/50
0.119
3151591KERR 2
50/50
0.186
316248AF1-058 C
Solar/Wind Harmer
0.005
960061AF2-297 GEN
Solar/Wind Harmer
26.586
971683AH1-343 GEN
Solar/Wind Harmer
19.795
316131AB2-060 GEN
Solar/Wind Harmer
0.564
964241AG1-285 GEN
Solar/Wind Harmer
11.118
315785AD2-033 C
Solar/Wind Harmer
1.191
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.673
970257AG2-171 GEN
Solar/Wind Harmer
4.443
959311AF2-222 GEN
Solar/Wind Harmer
11.835
963181AG1-167 GEN
Solar/Wind Harmer
0.405
3147133PAMPLIN
Solar/Wind Harmer
0.277
971193AH1-056 GEN
Solar/Wind Harmer
5.378
315657AE1-056 GEN
Solar/Wind Harmer
3.046
970831AG2-522 GEN
Solar/Wind Harmer
2.662
3152661PLYWOOD A
50/50
1.189
970535AG2-341 GEN
50/50
2.368
3144293JTRSVLE
50/50
0.342
3144293JTRSVLE
50/50
0.288
3146843MT LREL
Solar/Wind Harmer
0.44
3146843MT LREL
Solar/Wind Harmer
0.44
964791AG1-342 GEN
Solar/Wind Harmer
8.419
962561AG1-105 GEN
Solar/Wind Harmer
19.172
942751AE2-291 GEN
Solar/Wind Harmer
19.603
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.635
970323AG2-213 GEN
Solar/Wind Harmer
5.924
971775AH1-396 GEN
Solar/Wind Harmer
0.222
316034AC1-036 C
Solar/Wind Harmer
0.01
939181AE1-148 GEN
Solar/Wind Harmer
5.112
958211AF2-115 GEN
Solar/Wind Harmer
1.214
963191AG1-168 GEN
Solar/Wind Harmer
0.405
3147133PAMPLIN
Solar/Wind Harmer
0.088
3147133PAMPLIN
Solar/Wind Harmer
0.071
3151561HALLBR1
50/50
0.455
3144293JTRSVLE
50/50
0.342
24728405LEESVG
50/50
0.119
3151601KERR 3
50/50
0.186
3151581KERR 1
50/50
0.066
3147043LAWRENC
50/50
0.767
316003AC1-222 GEN
Solar/Wind Harmer
0.015
970401AG2-262 GEN
Solar/Wind Harmer
2.573
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3147123OTTER R
Solar/Wind Harmer
0.113
3147312GRETNA
Solar/Wind Harmer
0.117
3146802CHATHAM
Solar/Wind Harmer
0.109
941801AE2-185 GEN
Solar/Wind Harmer
4.673
970685AG2-442 GEN
Solar/Wind Harmer
8.91
963171AG1-166 GEN
Solar/Wind Harmer
0.539
971563AH1-280 GEN
Solar/Wind Harmer
1.079
971065AG2-659 GEN
Solar/Wind Harmer
3.007
316129AC1-054 GEN
Solar/Wind Harmer
0.25
971795AH1-408 GEN
Solar/Wind Harmer
4.388
315687AD1-152 GEN
Solar/Wind Helper
0.95
316222AC1-221 GEN
Solar/Wind Helper
0.679
3147043LAWRENC
Solar/Wind Harmer
0.048
316283AC2-100 C
Solar/Wind Helper
0.615
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.384
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.384
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.822
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.06
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 3202_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.16 %
Rating:276.6 MVA
Rating Type:C
MVA to Mitigate:362.79
MW Contribution:4.4
Bus #Bus NameTypeMW Contribution
960061AF2-297 GEN
Solar/Wind Harmer
34.896
971683AH1-343 GEN
Solar/Wind Harmer
25.983
316131AB2-060 GEN
Solar/Wind Harmer
2.168
964241AG1-285 GEN
Solar/Wind Harmer
14.598
315785AD2-033 C
Solar/Wind Harmer
3.721
3151561HALLBR1
50/50
0.454
316003AC1-222 GEN
Solar/Wind Harmer
6.315
970401AG2-262 GEN
Solar/Wind Harmer
3.206
316237AB2-079_GEN
Solar/Wind Harmer
0.646
3147123OTTER R
Solar/Wind Harmer
-0.012
3147312GRETNA
Solar/Wind Harmer
-0.013
3152661PLYWOOD A
50/50
1.185
970535AG2-341 GEN
50/50
2.362
3146843MT LREL
Solar/Wind Harmer
-0.049
3146843MT LREL
Solar/Wind Harmer
-0.049
964791AG1-342 GEN
Solar/Wind Harmer
10.492
962561AG1-105 GEN
Solar/Wind Harmer
25.166
942751AE2-291 GEN
Solar/Wind Harmer
25.733
313527AB2-043 GEN
Solar/Wind Harmer
3.316
316217AC1-145 GEN
Solar/Wind Harmer
2.656
316197AC1-042 GEN
Solar/Wind Harmer
2.013
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.136
970257AG2-171 GEN
Solar/Wind Harmer
5.834
959311AF2-222 GEN
Solar/Wind Harmer
15.571
963181AG1-167 GEN
Solar/Wind Harmer
1.063
3144293JTRSVLE
Adder
0.321
3147133PAMPLIN
Solar/Wind Harmer
-0.031
971193AH1-056 GEN
Solar/Wind Harmer
6.187
3147043LAWRENC
Solar/Wind Harmer
-0.005
316283AC2-100 C
Solar/Wind Helper
0.612
316118AC1-105 GEN
Solar/Wind Harmer
4.1
970865AG2-541 GEN
Solar/Wind Harmer
22.609
316123AC1-075 GEN
Solar/Wind Harmer
4.995
970165AG2-112 GEN
Solar/Wind Harmer
4.398
970163AG2-111 GEN
Solar/Wind Harmer
4.196
316239AB2-077_GEN
Solar/Wind Harmer
0.646
316238AB2-078_GEN
Solar/Wind Harmer
0.646
971443AH1-215 GEN
Solar/Wind Harmer
3.097
3144303KENBRDG
Solar/Wind Harmer
-0.012
970683AG2-441 GEN
Solar/Wind Harmer
10.446
970681AG2-440 GEN
Solar/Wind Harmer
8.357
946301AF1-294 GEN
Solar/Wind Harmer
2.905
961791AG1-021 GEN
Solar/Wind Harmer
1.417
315657AE1-056 GEN
Solar/Wind Harmer
3.712
970831AG2-522 GEN
Solar/Wind Harmer
3.497
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.136
970685AG2-442 GEN
Solar/Wind Harmer
11.7
963171AG1-166 GEN
Solar/Wind Harmer
1.417
971563AH1-280 GEN
Solar/Wind Harmer
1.417
3144293JTRSVLE
Adder
0.321
3147043LAWRENC
Adder
0.721
971065AG2-659 GEN
Solar/Wind Harmer
3.95
316129AC1-054 GEN
Solar/Wind Harmer
0.654
971795AH1-408 GEN
Solar/Wind Harmer
5.534
315687AD1-152 GEN
Solar/Wind Helper
0.946
942671AE2-283 GEN
Solar/Wind Harmer
5.42
970323AG2-213 GEN
Solar/Wind Harmer
7.779
971775AH1-396 GEN
Solar/Wind Harmer
1.108
316034AC1-036 C
Solar/Wind Harmer
0.288
939181AE1-148 GEN
Solar/Wind Harmer
6.713
958211AF2-115 GEN
Solar/Wind Harmer
1.771
963191AG1-168 GEN
Solar/Wind Harmer
1.063
3144293JTRSVLE
Adder
0.321
3144293JTRSVLE
Adder
0.27
3147133PAMPLIN
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Helper
0.676
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.381
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.367
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.057
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.816
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.013
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.049
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T296_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: H1T296_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.63 %
Rating:276.6 MVA
Rating Type:C
MVA to Mitigate:344.73
MW Contribution:3.94
Bus #Bus NameTypeMW Contribution
316248AF1-058 C
Solar/Wind Harmer
1.872
960061AF2-297 GEN
Solar/Wind Harmer
31.054
971683AH1-343 GEN
Solar/Wind Harmer
23.177
316131AB2-060 GEN
Solar/Wind Harmer
1.751
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.735
964241AG1-285 GEN
Solar/Wind Harmer
11.641
315785AD2-033 C
Solar/Wind Harmer
2.893
970257AG2-171 GEN
Solar/Wind Harmer
4.482
959311AF2-222 GEN
Solar/Wind Harmer
11.848
963181AG1-167 GEN
Solar/Wind Harmer
0.748
3144293JTRSVLE
Adder
0.226
3147043LAWRENC
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.021
971193AH1-056 GEN
Solar/Wind Harmer
4.138
316478AD1-087 GEN
Solar/Wind Helper
0.981
316486AD2-202 GEN
Solar/Wind Helper
0.287
3147173SINAI
Solar/Wind Harmer
-0.062
3147243WELCO
Solar/Wind Harmer
-0.038
316118AC1-105 GEN
Solar/Wind Harmer
3.625
970865AG2-541 GEN
Solar/Wind Harmer
20.197
316123AC1-075 GEN
Solar/Wind Harmer
4.479
970165AG2-112 GEN
Solar/Wind Harmer
3.944
970163AG2-111 GEN
Solar/Wind Harmer
3.762
316239AB2-077_GEN
Solar/Wind Harmer
0.527
316238AB2-078_GEN
Solar/Wind Harmer
0.527
971443AH1-215 GEN
Solar/Wind Harmer
2.385
3144303KENBRDG
Solar/Wind Harmer
-0.01
970683AG2-441 GEN
Solar/Wind Harmer
7.729
970681AG2-440 GEN
Solar/Wind Harmer
6.183
946301AF1-294 GEN
Solar/Wind Harmer
2.043
961791AG1-021 GEN
Solar/Wind Harmer
0.997
315657AE1-056 GEN
Solar/Wind Harmer
2.483
3152661PLYWOOD A
50/50
1.048
3146843MT LREL
Solar/Wind Harmer
-0.043
3146843MT LREL
Solar/Wind Harmer
-0.043
964791AG1-342 GEN
Solar/Wind Harmer
9.19
962561AG1-105 GEN
Solar/Wind Harmer
21.928
3151561HALLBR1
50/50
0.42
316003AC1-222 GEN
Solar/Wind Harmer
5.627
970401AG2-262 GEN
Solar/Wind Harmer
2.808
3147123OTTER R
Solar/Wind Harmer
-0.012
316237AB2-079_GEN
Solar/Wind Harmer
0.527
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.735
970685AG2-442 GEN
Solar/Wind Harmer
8.656
963171AG1-166 GEN
Solar/Wind Harmer
0.997
971563AH1-280 GEN
Solar/Wind Harmer
0.997
3144293JTRSVLE
Adder
0.226
3147043LAWRENC
Adder
0.565
315687AD1-152 GEN
Solar/Wind Helper
1.76
942751AE2-291 GEN
Solar/Wind Harmer
23.152
313527AB2-043 GEN
Solar/Wind Harmer
2.685
316217AC1-145 GEN
Solar/Wind Harmer
2.482
316197AC1-042 GEN
Solar/Wind Harmer
1.882
942671AE2-283 GEN
Solar/Wind Harmer
5.066
970323AG2-213 GEN
Solar/Wind Harmer
5.976
971775AH1-396 GEN
Solar/Wind Harmer
0.851
316034AC1-036 C
Solar/Wind Harmer
0.221
939181AE1-148 GEN
Solar/Wind Harmer
5.092
958211AF2-115 GEN
Solar/Wind Harmer
1.246
963191AG1-168 GEN
Solar/Wind Harmer
0.748
3144293JTRSVLE
Adder
0.226
3144293JTRSVLE
Adder
0.19
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.131
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.755
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.409
MECLTFEXP_MEC->PJM
CLTF
0.58
SIGELTFEXP_SIGE->PJM
CLTF
0.019
NYPJM->LTFIMP_NY
CLTF
0.138
LGEELTFEXP_LGEE->PJM
CLTF
0.256
WECLTFEXP_WEC->PJM
CLTF
0.129
LAGNLTFEXP_LAGN->PJM
CLTF
0.711
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.716
TVALTFEXP_TVA->PJM
CLTF
0.376

Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-5: SEDGE H L102_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-5: SEDGE H L102_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.48 %
Rating:276.6 MVA
Rating Type:C
MVA to Mitigate:344.32
MW Contribution:4.4
Bus #Bus NameTypeMW Contribution
316248AF1-058 C
Solar/Wind Harmer
2.103
960061AF2-297 GEN
Solar/Wind Harmer
34.892
971683AH1-343 GEN
Solar/Wind Harmer
25.98
316131AB2-060 GEN
Solar/Wind Harmer
2.167
964241AG1-285 GEN
Solar/Wind Harmer
14.592
315785AD2-033 C
Solar/Wind Harmer
3.719
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.133
970257AG2-171 GEN
Solar/Wind Harmer
5.831
959311AF2-222 GEN
Solar/Wind Harmer
15.563
963181AG1-167 GEN
Solar/Wind Harmer
1.062
3144293JTRSVLE
Adder
0.321
3147133PAMPLIN
Solar/Wind Harmer
-0.031
971193AH1-056 GEN
Solar/Wind Harmer
6.182
3147173SINAI
Solar/Wind Harmer
-0.07
3147243WELCO
Solar/Wind Harmer
-0.043
316118AC1-105 GEN
Solar/Wind Harmer
4.099
3147043LAWRENC
Solar/Wind Harmer
-0.005
316283AC2-100 C
Solar/Wind Helper
0.613
3151561HALLBR1
50/50
0.454
316003AC1-222 GEN
Solar/Wind Harmer
6.314
970401AG2-262 GEN
Solar/Wind Harmer
3.205
316237AB2-079_GEN
Solar/Wind Harmer
0.646
3147123OTTER R
Solar/Wind Harmer
-0.012
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.133
970685AG2-442 GEN
Solar/Wind Harmer
11.693
963171AG1-166 GEN
Solar/Wind Harmer
1.416
971563AH1-280 GEN
Solar/Wind Harmer
1.416
3144293JTRSVLE
Adder
0.321
3147043LAWRENC
Adder
0.721
971065AG2-659 GEN
Solar/Wind Harmer
3.947
316129AC1-054 GEN
Solar/Wind Harmer
0.654
971795AH1-408 GEN
Solar/Wind Harmer
5.528
315687AD1-152 GEN
Solar/Wind Helper
0.947
970865AG2-541 GEN
Solar/Wind Harmer
22.606
316123AC1-075 GEN
Solar/Wind Harmer
4.994
970165AG2-112 GEN
Solar/Wind Harmer
4.397
970163AG2-111 GEN
Solar/Wind Harmer
4.195
316239AB2-077_GEN
Solar/Wind Harmer
0.646
316238AB2-078_GEN
Solar/Wind Harmer
0.646
971443AH1-215 GEN
Solar/Wind Harmer
3.095
3144303KENBRDG
Solar/Wind Harmer
-0.012
970683AG2-441 GEN
Solar/Wind Harmer
10.44
970681AG2-440 GEN
Solar/Wind Harmer
8.352
946301AF1-294 GEN
Solar/Wind Harmer
2.903
961791AG1-021 GEN
Solar/Wind Harmer
1.416
315657AE1-056 GEN
Solar/Wind Harmer
3.709
970831AG2-522 GEN
Solar/Wind Harmer
3.493
3152661PLYWOOD A
50/50
1.185
970535AG2-341 GEN
50/50
2.36
3146843MT LREL
Solar/Wind Harmer
-0.049
3146843MT LREL
Solar/Wind Harmer
-0.049
964791AG1-342 GEN
Solar/Wind Harmer
10.49
962561AG1-105 GEN
Solar/Wind Harmer
25.162
942751AE2-291 GEN
Solar/Wind Harmer
25.728
313527AB2-043 GEN
Solar/Wind Harmer
3.315
316217AC1-145 GEN
Solar/Wind Harmer
2.654
316197AC1-042 GEN
Solar/Wind Harmer
2.012
942671AE2-283 GEN
Solar/Wind Harmer
5.418
970323AG2-213 GEN
Solar/Wind Harmer
7.775
971775AH1-396 GEN
Solar/Wind Harmer
1.107
316034AC1-036 C
Solar/Wind Harmer
0.288
939181AE1-148 GEN
Solar/Wind Harmer
6.709
958211AF2-115 GEN
Solar/Wind Harmer
1.77
963191AG1-168 GEN
Solar/Wind Harmer
1.062
3144293JTRSVLE
Adder
0.321
3144293JTRSVLE
Adder
0.27
3147133PAMPLIN
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Helper
0.676
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.383
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.382
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.819
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.06
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 15102_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 15102_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.84 %
Rating:276.6 MVA
Rating Type:C
MVA to Mitigate:323.18
MW Contribution:4.89
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.507
316003AC1-222 GEN
Solar/Wind Harmer
7.012
970401AG2-262 GEN
Solar/Wind Harmer
3.383
3147123OTTER R
Solar/Wind Harmer
-0.014
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.858
316237AB2-079_GEN
Solar/Wind Harmer
0.467
970685AG2-442 GEN
Solar/Wind Harmer
9.166
963171AG1-166 GEN
Solar/Wind Harmer
1.102
971563AH1-280 GEN
Solar/Wind Harmer
1.102
3144293JTRSVLE
Adder
0.25
3147043LAWRENC
Adder
0.538
270173AC1-122 GEN
Solar/Wind Harmer
0.702
315687AD1-152 GEN
Solar/Wind Helper
0.867
3146843MT LREL
Solar/Wind Harmer
-0.052
3146843MT LREL
Solar/Wind Harmer
-0.052
964791AG1-342 GEN
Solar/Wind Harmer
11.073
962561AG1-105 GEN
Solar/Wind Harmer
26.106
942751AE2-291 GEN
Solar/Wind Harmer
28.608
316217AC1-145 GEN
Solar/Wind Harmer
2.968
316197AC1-042 GEN
Solar/Wind Harmer
2.25
942671AE2-283 GEN
Solar/Wind Harmer
6.058
313527AB2-043 GEN
Solar/Wind Harmer
2.638
970323AG2-213 GEN
Solar/Wind Harmer
6.137
971775AH1-396 GEN
Solar/Wind Harmer
0.874
316034AC1-036 C
Solar/Wind Harmer
0.227
958211AF2-115 GEN
Solar/Wind Harmer
1.377
963191AG1-168 GEN
Solar/Wind Harmer
0.826
3144293JTRSVLE
Adder
0.25
3144293JTRSVLE
Adder
0.21
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
939181AE1-148 GEN
Solar/Wind Harmer
3.943
3147173SINAI
Solar/Wind Harmer
-0.077
3147243WELCO
Solar/Wind Harmer
-0.048
316118AC1-105 GEN
Solar/Wind Harmer
4.46
970865AG2-541 GEN
Solar/Wind Harmer
25.111
316123AC1-075 GEN
Solar/Wind Harmer
5.551
970165AG2-112 GEN
Solar/Wind Harmer
4.887
970163AG2-111 GEN
Solar/Wind Harmer
4.662
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
971443AH1-215 GEN
Solar/Wind Harmer
2.443
3144303KENBRDG
Solar/Wind Harmer
-0.01
970683AG2-441 GEN
Solar/Wind Harmer
8.184
970681AG2-440 GEN
Solar/Wind Harmer
6.547
946301AF1-294 GEN
Solar/Wind Harmer
2.258
961791AG1-021 GEN
Solar/Wind Harmer
1.102
315657AE1-056 GEN
Solar/Wind Harmer
2.862
316248AF1-058 C
Solar/Wind Harmer
2.335
960061AF2-297 GEN
Solar/Wind Harmer
38.738
971683AH1-343 GEN
Solar/Wind Harmer
28.853
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.858
316131AB2-060 GEN
Solar/Wind Harmer
1.725
964241AG1-285 GEN
Solar/Wind Harmer
11.583
315785AD2-033 C
Solar/Wind Harmer
2.941
970257AG2-171 GEN
Solar/Wind Harmer
4.603
959311AF2-222 GEN
Solar/Wind Harmer
12.256
963181AG1-167 GEN
Solar/Wind Harmer
0.826
3144293JTRSVLE
Adder
0.25
3147133PAMPLIN
Solar/Wind Harmer
-0.024
971193AH1-056 GEN
Solar/Wind Harmer
4.77
3147043LAWRENC
Solar/Wind Harmer
-0.004
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.352
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.163
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.238
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
LGEELTFEXP_LGEE->PJM
CLTF
0.026
WECLTFEXP_WEC->PJM
CLTF
0.006
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.788
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.18 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:336.08
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.036
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.601
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
CPLELTFEXP_CPLE->PJM
CLTF
0.484
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.177
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.013
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.831
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.17 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:336.06
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.035
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.6
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
CPLELTFEXP_CPLE->PJM
CLTF
0.484
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 1016T1047_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.26 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:319.14
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
CPLELTFEXP_CPLE->PJM
CLTF
0.492
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 101672_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.24 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:319.1
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
5.565
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
CPLELTFEXP_CPLE->PJM
CLTF
0.492
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 104772_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.8 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:315.55
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
CPLELTFEXP_CPLE->PJM
CLTF
0.492
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1047_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1047_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.43 %
Rating:230.3 MVA
Rating Type:B
MVA to Mitigate:265.84
MW Contribution:3.72
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.896
942751AE2-291 GEN
Solar/Wind Harmer
24.967
270013AE1-250 PV
Solar/Wind Harmer
0.002
316123AC1-075 GEN
Solar/Wind Harmer
0.627
970865AG2-541 GEN
Solar/Wind Harmer
15.911
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.549
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.295
971683AH1-343 GEN
Solar/Wind Harmer
16.89
270197AD1-017 GEN1
Solar/Wind Harmer
0.699
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.295
316003AC1-222 GEN
Solar/Wind Harmer
0.012
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.175
970223AG2-152 GEN
Solar/Wind Harmer
4.628
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1016_SRT-A-1


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1016_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.32 %
Rating:230.3 MVA
Rating Type:B
MVA to Mitigate:254.07
MW Contribution:3.72
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.899
942751AE2-291 GEN
Solar/Wind Harmer
24.973
270013AE1-250 PV
Solar/Wind Harmer
0.002
316123AC1-075 GEN
Solar/Wind Harmer
0.628
970865AG2-541 GEN
Solar/Wind Harmer
15.914
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.55
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.299
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.176
970223AG2-152 GEN
Solar/Wind Harmer
4.636
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.299
971683AH1-343 GEN
Solar/Wind Harmer
16.893
270197AD1-017 GEN1
Solar/Wind Harmer
0.7
CPLELTFEXP_CPLE->PJM
CLTF
0.492
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.154
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.83 %
Rating:156.98 MVA
Rating Type:A
MVA to Mitigate:164.56
MW Contribution:1.61
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
0.932
24684505SMG3
50/50
0.577
24684305SMG1
50/50
0.338
3152661PLYWOOD A
50/50
0.134
316217AC1-145 GEN
Solar/Wind Harmer
0.005
316197AC1-042 GEN
Solar/Wind Harmer
0.004
942671AE2-283 GEN
Solar/Wind Harmer
9.556
942751AE2-291 GEN
Solar/Wind Harmer
12.576
270013AE1-250 PV
Solar/Wind Harmer
0.002
3151561HALLBR1
50/50
0.893
24728405LEESVG
50/50
0.29
24684705SMG5
50/50
0.359
970481AG2-311 GEN
50/50
5.003
3147312GRETNA
Solar/Wind Harmer
0.307
3146802CHATHAM
Solar/Wind Harmer
0.288
941801AE2-185 GEN
Solar/Wind Harmer
12.286
3147123OTTER R
Solar/Wind Harmer
0.203
316003AC1-222 GEN
Solar/Wind Harmer
0.003
270574AD1-017 GEN2
Solar/Wind Harmer
0
270016AE1-250 BESS
Solar/Wind Harmer
0.002
316123AC1-075 GEN
Solar/Wind Harmer
0.271
970165AG2-112 GEN
Solar/Wind Harmer
1.606
970163AG2-111 GEN
Solar/Wind Harmer
1.532
970865AG2-541 GEN
Solar/Wind Harmer
5.06
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
316118AC1-105 GEN
Solar/Wind Harmer
0.154
24728405LEESVG
50/50
0.291
24684605SMG4
50/50
0.938
3147312GRETNA
Solar/Wind Harmer
0.077
941821AE2-187 GEN
Solar/Wind Harmer
12.286
971683AH1-343 GEN
Solar/Wind Harmer
4.429
270197AD1-017 GEN1
Solar/Wind Harmer
0.533
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.866
CPLELTFEXP_CPLE->PJM
CLTF
1.048
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.46
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.027
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.148
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.688
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.33 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:250.71
MW Contribution:2.19
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
CPLELTFEXP_CPLE->PJM
CLTF
0.729
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.33 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:250.7
MW Contribution:2.19
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
CPLELTFEXP_CPLE->PJM
CLTF
0.729
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:203.13 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1378.6
MW Contribution:0.53
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
CPLELTFEXP_CPLE->PJM
CLTF
4.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.018
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:158.61 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1076.48
MW Contribution:0.51
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151601KERR 3
50/50
0.215
3151581KERR 1
50/50
0.077
3151531CLOVER1
50/50
2.214
3147043LAWRENC
50/50
0.833
3151261ROARAP2
50/50
0.071
970937AG2-583 GEN
Solar/Wind Harmer
39.544
316336AC2-165 C
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
26.303
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.202
3146926FARMVIL
Solar/Wind Harmer
0.234
971377AH1-170 GEN
Solar/Wind Harmer
2.874
3147623JAMES R
Solar/Wind Harmer
0.624
963171AG1-166 GEN
Solar/Wind Harmer
1.391
971563AH1-280 GEN
Solar/Wind Harmer
2.782
970685AG2-442 GEN
Solar/Wind Harmer
17.514
962491AG1-098 GEN
Solar/Wind Harmer
8.209
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.543
970401AG2-262 GEN
Solar/Wind Harmer
0.652
957481AF2-042 GEN
Solar/Wind Harmer
26.84
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.856
316129AC1-054 GEN
Solar/Wind Harmer
0.33
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
5.259
960081AF2-299 GEN
Solar/Wind Harmer
0.593
972205AH1-687 GEN
50/50
29.229
3151611KERR 4
50/50
0.215
3151621KERR 5
50/50
0.215
3151631KERR 6
50/50
0.215
3151641KERR 7
50/50
0.215
3151541CLOVER2
50/50
2.204
3151281ROARAP4
50/50
0.069
3151281ROARAP4
50/50
0.065
971845AH1-439 GEN
Solar/Wind Harmer
22.434
970285AG2-188 GEN
Solar/Wind Harmer
37.679
315657AE1-056 GEN
Solar/Wind Harmer
9.629
946301AF1-294 GEN
Solar/Wind Harmer
5.147
961791AG1-021 GEN
Solar/Wind Harmer
2.504
970683AG2-441 GEN
Solar/Wind Harmer
15.638
970681AG2-440 GEN
Solar/Wind Harmer
12.51
270494AE1-108_GEN
Solar/Wind Harmer
2.538
3144303KENBRDG
Solar/Wind Harmer
0.165
971443AH1-215 GEN
Solar/Wind Harmer
3.431
971447AH1-217 GEN
Solar/Wind Harmer
5.812
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3147173SINAI
Solar/Wind Harmer
0.087
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151591KERR 2
50/50
0.215
970413AG2-270 GEN
50/50
9.663
3151261ROARAP2
50/50
0.069
3146776BUCKING
Solar/Wind Harmer
0.182
3146926FARMVIL
Solar/Wind Harmer
0.234
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
0.876
971193AH1-056 GEN
Solar/Wind Harmer
16.999
970221AG2-151 GEN
Solar/Wind Harmer
14.368
963181AG1-167 GEN
Solar/Wind Harmer
1.043
959311AF2-222 GEN
Solar/Wind Harmer
19.082
970257AG2-171 GEN
Solar/Wind Harmer
6.613
315785AD2-033 C
Solar/Wind Harmer
1.59
964241AG1-285 GEN
Solar/Wind Harmer
11.084
316131AB2-060 GEN
Solar/Wind Harmer
0.467
316478AD1-087 GEN
Solar/Wind Harmer
0.361
316486AD2-202 GEN
Solar/Wind Harmer
0.106
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.73
3147043LAWRENC
Solar/Wind Harmer
0.052
958131AF2-107 GEN
Solar/Wind Harmer
2.449
971683AH1-343 GEN
Solar/Wind Harmer
2.857
313506AB2-031 GEN
Solar/Wind Harmer
0.184
3144293JTRSVLE
50/50
0.881
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3152661PLYWOOD A
50/50
0.212
3146776BUCKING
Solar/Wind Harmer
2.017
3146776BUCKING
Solar/Wind Harmer
0.163
970301AG2-198 GEN
Solar/Wind Harmer
12.027
3147243WELCO
Solar/Wind Harmer
0.055
970831AG2-522 GEN
Solar/Wind Harmer
3.614
970865AG2-541 GEN
Solar/Wind Harmer
2.528
316123AC1-075 GEN
Solar/Wind Harmer
0.087
970165AG2-112 GEN
Solar/Wind Harmer
0.513
970163AG2-111 GEN
Solar/Wind Harmer
0.49
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.232
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3147133PAMPLIN
Solar/Wind Harmer
0.279
3147133PAMPLIN
Solar/Wind Harmer
0.223
971489AH1-241 GEN
Solar/Wind Harmer
14.368
958211AF2-115 GEN
Solar/Wind Harmer
3.13
963191AG1-168 GEN
Solar/Wind Harmer
1.043
971741AH1-377 GEN
Solar/Wind Harmer
24.65
316034AC1-036 C
Solar/Wind Harmer
0.015
970323AG2-213 GEN
Solar/Wind Harmer
8.817
971775AH1-396 GEN
Solar/Wind Harmer
0.331
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.577
315821AE2-092 GEN
Solar/Wind Harmer
0.007
939181AE1-148 GEN
Solar/Wind Harmer
5.338
964791AG1-342 GEN
Solar/Wind Harmer
2.134
3146843MT LREL
Solar/Wind Harmer
0.111
3146843MT LREL
Solar/Wind Harmer
0.111
970099AG2-077 GEN
Solar/Wind Harmer
10.736
970933AG2-581 GEN
Solar/Wind Harmer
5.58
316181AB2-040 GEN
Solar/Wind Harmer
0.086
942751AE2-291 GEN
Solar/Wind Harmer
3.114
3145593CAROLNA
Solar/Wind Harmer
0.057
3145593CAROLNA
Solar/Wind Harmer
0.057
966811AG1-552 GEN
Solar/Wind Harmer
0.619
3145593CAROLNA
Solar/Wind Harmer
0.071
966001AG1-469 GEN
Solar/Wind Helper
0.14
CPLELTFEXP_CPLE->PJM
CLTF
3.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.029
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.82 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1235.22
MW Contribution:0.68
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
29.229
971845AH1-439 GEN
Solar/Wind Harmer
29.538
970285AG2-188 GEN
Solar/Wind Harmer
46.824
3144293JTRSVLE
50/50
0.881
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3146776BUCKING
Solar/Wind Harmer
-0.226
3146776BUCKING
Solar/Wind Harmer
-0.018
315657AE1-056 GEN
Solar/Wind Harmer
11.763
946301AF1-294 GEN
Solar/Wind Harmer
7.51
961791AG1-021 GEN
Solar/Wind Harmer
3.664
970683AG2-441 GEN
Solar/Wind Harmer
20.59
970681AG2-440 GEN
Solar/Wind Harmer
16.472
270494AE1-108_GEN
Solar/Wind Harmer
6.187
3144303KENBRDG
Solar/Wind Harmer
-0.019
971443AH1-215 GEN
Solar/Wind Harmer
4.518
971447AH1-217 GEN
Solar/Wind Harmer
7.652
316239AB2-077_GEN
Solar/Wind Harmer
0.475
316238AB2-078_GEN
Solar/Wind Harmer
0.475
316118AC1-105 GEN
Solar/Wind Harmer
0.766
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.758
970865AG2-541 GEN
Solar/Wind Harmer
3.329
316123AC1-075 GEN
Solar/Wind Harmer
0.768
970165AG2-112 GEN
Solar/Wind Harmer
0.676
970163AG2-111 GEN
Solar/Wind Harmer
0.645
946281AF1-292 GEN
Solar/Wind Harmer
0.155
316087AB2-174 GEN
Solar/Wind Harmer
0.965
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
970301AG2-198 GEN
Solar/Wind Harmer
15.836
3147133PAMPLIN
Solar/Wind Harmer
-0.031
3147133PAMPLIN
Solar/Wind Harmer
-0.025
971489AH1-241 GEN
Solar/Wind Harmer
17.959
958211AF2-115 GEN
Solar/Wind Harmer
4.579
963191AG1-168 GEN
Solar/Wind Harmer
2.748
971741AH1-377 GEN
Solar/Wind Harmer
32.456
316034AC1-036 C
Solar/Wind Harmer
0.432
970323AG2-213 GEN
Solar/Wind Harmer
11.609
971775AH1-396 GEN
Solar/Wind Harmer
1.653
313527AB2-043 GEN
Solar/Wind Harmer
2.63
962561AG1-105 GEN
Solar/Wind Harmer
7.343
315821AE2-092 GEN
Solar/Wind Harmer
2.71
939181AE1-148 GEN
Solar/Wind Harmer
7.029
964791AG1-342 GEN
Solar/Wind Harmer
2.668
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.136
970933AG2-581 GEN
Solar/Wind Harmer
7.348
316181AB2-040 GEN
Solar/Wind Harmer
0.933
942751AE2-291 GEN
Solar/Wind Harmer
4.1
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.721
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.14
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
970937AG2-583 GEN
Solar/Wind Harmer
52.066
316336AC2-165 C
Solar/Wind Harmer
12.588
972003AH1-546 GEN
Solar/Wind Harmer
34.691
316322AB2-045
Solar/Wind Harmer
1.907
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.592
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
-0.098
971193AH1-056 GEN
Solar/Wind Harmer
19.605
970221AG2-151 GEN
Solar/Wind Harmer
18.917
963181AG1-167 GEN
Solar/Wind Harmer
2.748
959311AF2-222 GEN
Solar/Wind Harmer
25.175
970257AG2-171 GEN
Solar/Wind Harmer
8.707
315785AD2-033 C
Solar/Wind Harmer
4.981
964241AG1-285 GEN
Solar/Wind Harmer
14.595
316131AB2-060 GEN
Solar/Wind Harmer
1.799
316478AD1-087 GEN
Solar/Wind Harmer
1.005
316486AD2-202 GEN
Solar/Wind Harmer
0.294
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.911
3147043LAWRENC
Solar/Wind Harmer
-0.006
958131AF2-107 GEN
Solar/Wind Harmer
3.26
971683AH1-343 GEN
Solar/Wind Harmer
3.762
966621AG1-532 GEN
Solar/Wind Harmer
0.141
313506AB2-031 GEN
Solar/Wind Harmer
0.538
971377AH1-170 GEN
Solar/Wind Harmer
3.783
3147623JAMES R
Solar/Wind Harmer
0.468
963171AG1-166 GEN
Solar/Wind Harmer
3.664
971563AH1-280 GEN
Solar/Wind Harmer
3.664
970685AG2-442 GEN
Solar/Wind Harmer
23.061
962491AG1-098 GEN
Solar/Wind Harmer
10.808
316237AB2-079_GEN
Solar/Wind Harmer
0.475
315693AD1-088 GEN
Solar/Wind Harmer
7.658
970401AG2-262 GEN
Solar/Wind Harmer
0.815
957481AF2-042 GEN
Solar/Wind Harmer
35.339
315687AD1-152 GEN
Solar/Wind Harmer
1.264
971065AG2-659 GEN
Solar/Wind Harmer
5.078
316129AC1-054 GEN
Solar/Wind Harmer
0.863
3147043LAWRENC
Adder
0.785
316003AC1-222 GEN
Solar/Wind Harmer
0.902
971795AH1-408 GEN
Solar/Wind Harmer
6.647
960081AF2-299 GEN
Solar/Wind Harmer
0.78
CPLELTFEXP_CPLE->PJM
CLTF
3.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.029
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.42 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:940.37
MW Contribution:0.46
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.01 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:937.12
MW Contribution:0.46
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970933AG2-581 GEN
Solar/Wind Harmer
8.922
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
971967AH1-528 GEN
Solar/Wind Harmer
17.843
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.32 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1051.71
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
14.458
971447AH1-217 GEN
Solar/Wind Harmer
10.717
971845AH1-439 GEN
Solar/Wind Harmer
15.427
970285AG2-188 GEN
Solar/Wind Harmer
24.673
270494AE1-108_GEN
Solar/Wind Harmer
6.636
315657AE1-056 GEN
Solar/Wind Harmer
6.684
946301AF1-294 GEN
Solar/Wind Harmer
4.293
961791AG1-021 GEN
Solar/Wind Harmer
2.094
970683AG2-441 GEN
Solar/Wind Harmer
11.891
970681AG2-440 GEN
Solar/Wind Harmer
9.513
3144303KENBRDG
Solar/Wind Harmer
-0.011
971443AH1-215 GEN
Solar/Wind Harmer
2.648
971967AH1-528 GEN
Solar/Wind Harmer
23.681
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.294
316238AB2-078_GEN
Solar/Wind Harmer
0.294
316118AC1-105 GEN
Solar/Wind Harmer
0.567
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.835
316123AC1-075 GEN
Solar/Wind Harmer
0.694
970165AG2-112 GEN
Solar/Wind Harmer
0.611
970163AG2-111 GEN
Solar/Wind Harmer
0.583
316233AE1-074 FULL
Solar/Wind Helper
0.382
316312AB1-027
Solar/Wind Helper
0.22
316132AB2-190 GEN1
Solar/Wind Helper
0.649
3151921BEARGRDN G2
50/50
2.964
3144293JTRSVLE
50/50
0.504
970221AG2-151 GEN
Solar/Wind Harmer
19.915
3146776BUCKING
Solar/Wind Harmer
-0.01
3146926FARMVIL
Solar/Wind Harmer
-0.014
942461AE2-259 GEN
Solar/Wind Harmer
3.135
970909AG2-566 GEN
Solar/Wind Harmer
1.873
3147133PAMPLIN
Solar/Wind Harmer
-0.056
971193AH1-056 GEN
Solar/Wind Harmer
11.141
3151931BEARGRDN S1
50/50
3.826
3151911BEARGRDN G1
50/50
2.964
3144293JTRSVLE
50/50
0.504
972003AH1-546 GEN
Solar/Wind Harmer
17.291
971377AH1-170 GEN
Solar/Wind Harmer
3.983
3147623JAMES R
Solar/Wind Harmer
0.493
316322AB2-045
Solar/Wind Harmer
0.992
3146776BUCKING
Solar/Wind Harmer
-0.012
3146926FARMVIL
Solar/Wind Harmer
-0.014
963171AG1-166 GEN
Solar/Wind Harmer
2.094
971563AH1-280 GEN
Solar/Wind Harmer
2.094
970685AG2-442 GEN
Solar/Wind Harmer
13.318
962491AG1-098 GEN
Solar/Wind Harmer
9.296
315693AD1-088 GEN
Solar/Wind Harmer
6.792
957481AF2-042 GEN
Solar/Wind Harmer
38.61
315687AD1-152 GEN
Solar/Wind Harmer
1.176
316237AB2-079_GEN
Solar/Wind Harmer
0.294
970401AG2-262 GEN
Solar/Wind Harmer
0.568
316003AC1-222 GEN
Solar/Wind Harmer
0.733
316336AC2-165 C
Solar/Wind Helper
5.14
3143226MDLTHAN
Solar/Wind Helper
0.302
3143526WINTERP
Solar/Wind Helper
1.302
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.3
3142416OLDCHRC
Solar/Wind Helper
0.115
316458AB2-190 GEN2
Solar/Wind Helper
0.649
3142433PROV 92
Solar/Wind Helper
0.45
963181AG1-167 GEN
Solar/Wind Harmer
1.571
959311AF2-222 GEN
Solar/Wind Harmer
14.674
970257AG2-171 GEN
Solar/Wind Harmer
5.097
315785AD2-033 C
Solar/Wind Harmer
2.934
958131AF2-107 GEN
Solar/Wind Harmer
3.94
316478AD1-087 GEN
Solar/Wind Harmer
0.998
316486AD2-202 GEN
Solar/Wind Harmer
0.292
964241AG1-285 GEN
Solar/Wind Harmer
8.775
316131AB2-060 GEN
Solar/Wind Harmer
1.1
3148013FISHERV
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.235
960061AF2-297 GEN
Solar/Wind Harmer
3.902
971683AH1-343 GEN
Solar/Wind Harmer
3.125
316313AB2-026
Solar/Wind Helper
1.246
316258AE1-075 C
Solar/Wind Helper
1.122
316405AF2-144 C
Solar/Wind Helper
0.934
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.718
315839AE2-212 C
Solar/Wind Helper
0.157
3144293JTRSVLE
50/50
0.504
3144293JTRSVLE
50/50
0.424
971489AH1-241 GEN
Solar/Wind Harmer
18.907
3146776BUCKING
Solar/Wind Harmer
-0.117
3146776BUCKING
Solar/Wind Harmer
-0.01
315821AE2-092 GEN
Solar/Wind Harmer
4.838
970301AG2-198 GEN
Solar/Wind Harmer
9.862
971741AH1-377 GEN
Solar/Wind Harmer
21.292
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.618
963191AG1-168 GEN
Solar/Wind Harmer
1.571
316034AC1-036 C
Solar/Wind Harmer
0.253
970323AG2-213 GEN
Solar/Wind Harmer
6.795
971775AH1-396 GEN
Solar/Wind Harmer
0.968
970933AG2-581 GEN
Solar/Wind Harmer
11.81
970099AG2-077 GEN
Solar/Wind Harmer
15.444
313527AB2-043 GEN
Solar/Wind Harmer
1.614
962561AG1-105 GEN
Solar/Wind Harmer
4.999
964791AG1-342 GEN
Solar/Wind Harmer
1.858
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
939181AE1-148 GEN
Solar/Wind Harmer
4.411
3143526WINTERP
Solar/Wind Helper
1.302
316240AF1-291 C
Solar/Wind Helper
0.165
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.158
316075AC2-137 C
Solar/Wind Helper
0.175
CPLELTFEXP_CPLE->PJM
CLTF
0.722
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.487
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.852
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.843
MECLTFEXP_MEC->PJM
CLTF
1.109
SIGELTFEXP_SIGE->PJM
CLTF
0.036
NYPJM->LTFIMP_NY
CLTF
0.343
LGEELTFEXP_LGEE->PJM
CLTF
0.473
WECLTFEXP_WEC->PJM
CLTF
0.242
LAGNLTFEXP_LAGN->PJM
CLTF
1.488
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.29
TVALTFEXP_TVA->PJM
CLTF
0.772

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.31 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1051.63
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
14.458
971447AH1-217 GEN
Solar/Wind Harmer
10.717
971845AH1-439 GEN
Solar/Wind Harmer
15.427
970285AG2-188 GEN
Solar/Wind Harmer
24.673
270494AE1-108_GEN
Solar/Wind Harmer
6.636
315657AE1-056 GEN
Solar/Wind Harmer
6.684
946301AF1-294 GEN
Solar/Wind Harmer
4.293
961791AG1-021 GEN
Solar/Wind Harmer
2.094
970683AG2-441 GEN
Solar/Wind Harmer
11.891
970681AG2-440 GEN
Solar/Wind Harmer
9.513
3144303KENBRDG
Solar/Wind Harmer
-0.011
971443AH1-215 GEN
Solar/Wind Harmer
2.648
971967AH1-528 GEN
Solar/Wind Harmer
23.681
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.294
316238AB2-078_GEN
Solar/Wind Harmer
0.294
316118AC1-105 GEN
Solar/Wind Harmer
0.567
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.835
316123AC1-075 GEN
Solar/Wind Harmer
0.694
970165AG2-112 GEN
Solar/Wind Harmer
0.611
970163AG2-111 GEN
Solar/Wind Harmer
0.583
316233AE1-074 FULL
Solar/Wind Helper
0.382
3151921BEARGRDN G2
50/50
2.964
3144293JTRSVLE
50/50
0.504
970221AG2-151 GEN
Solar/Wind Harmer
19.915
3146776BUCKING
Solar/Wind Harmer
-0.01
3146926FARMVIL
Solar/Wind Harmer
-0.014
942461AE2-259 GEN
Solar/Wind Harmer
3.135
970909AG2-566 GEN
Solar/Wind Harmer
1.873
3147133PAMPLIN
Solar/Wind Harmer
-0.056
971193AH1-056 GEN
Solar/Wind Harmer
11.141
3144293JTRSVLE
50/50
0.504
3144293JTRSVLE
50/50
0.424
971489AH1-241 GEN
Solar/Wind Harmer
18.907
3146776BUCKING
Solar/Wind Harmer
-0.117
3146776BUCKING
Solar/Wind Harmer
-0.01
315821AE2-092 GEN
Solar/Wind Harmer
4.838
970301AG2-198 GEN
Solar/Wind Harmer
9.862
971741AH1-377 GEN
Solar/Wind Harmer
21.292
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.618
963181AG1-167 GEN
Solar/Wind Harmer
1.571
959311AF2-222 GEN
Solar/Wind Harmer
14.674
970257AG2-171 GEN
Solar/Wind Harmer
5.097
315785AD2-033 C
Solar/Wind Harmer
2.934
958131AF2-107 GEN
Solar/Wind Harmer
3.94
316478AD1-087 GEN
Solar/Wind Harmer
0.998
316486AD2-202 GEN
Solar/Wind Harmer
0.292
964241AG1-285 GEN
Solar/Wind Harmer
8.775
316131AB2-060 GEN
Solar/Wind Harmer
1.1
3148013FISHERV
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.235
960061AF2-297 GEN
Solar/Wind Harmer
3.902
971683AH1-343 GEN
Solar/Wind Harmer
3.125
316313AB2-026
Solar/Wind Helper
1.246
316258AE1-075 C
Solar/Wind Helper
1.122
316405AF2-144 C
Solar/Wind Helper
0.934
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.718
315839AE2-212 C
Solar/Wind Helper
0.157
3151931BEARGRDN S1
50/50
3.826
3151911BEARGRDN G1
50/50
2.964
3144293JTRSVLE
50/50
0.504
972003AH1-546 GEN
Solar/Wind Harmer
17.291
971377AH1-170 GEN
Solar/Wind Harmer
3.983
3147623JAMES R
Solar/Wind Harmer
0.493
316322AB2-045
Solar/Wind Harmer
0.992
3146776BUCKING
Solar/Wind Harmer
-0.012
3146926FARMVIL
Solar/Wind Harmer
-0.014
963171AG1-166 GEN
Solar/Wind Harmer
2.094
971563AH1-280 GEN
Solar/Wind Harmer
2.094
970685AG2-442 GEN
Solar/Wind Harmer
13.318
962491AG1-098 GEN
Solar/Wind Harmer
9.296
315693AD1-088 GEN
Solar/Wind Harmer
6.792
957481AF2-042 GEN
Solar/Wind Harmer
38.61
315687AD1-152 GEN
Solar/Wind Harmer
1.176
316237AB2-079_GEN
Solar/Wind Harmer
0.294
970401AG2-262 GEN
Solar/Wind Harmer
0.568
316003AC1-222 GEN
Solar/Wind Harmer
0.733
316336AC2-165 C
Solar/Wind Helper
5.14
3143226MDLTHAN
Solar/Wind Helper
0.302
3143526WINTERP
Solar/Wind Helper
1.302
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.3
3142416OLDCHRC
Solar/Wind Helper
0.115
316458AB2-190 GEN2
Solar/Wind Helper
0.649
3142433PROV 92
Solar/Wind Helper
0.45
963191AG1-168 GEN
Solar/Wind Harmer
1.571
316034AC1-036 C
Solar/Wind Harmer
0.253
970323AG2-213 GEN
Solar/Wind Harmer
6.795
971775AH1-396 GEN
Solar/Wind Harmer
0.968
970933AG2-581 GEN
Solar/Wind Harmer
11.81
970099AG2-077 GEN
Solar/Wind Harmer
15.444
313527AB2-043 GEN
Solar/Wind Harmer
1.614
962561AG1-105 GEN
Solar/Wind Harmer
4.999
964791AG1-342 GEN
Solar/Wind Harmer
1.858
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
939181AE1-148 GEN
Solar/Wind Harmer
4.411
3143526WINTERP
Solar/Wind Helper
1.302
316240AF1-291 C
Solar/Wind Helper
0.165
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.158
316075AC2-137 C
Solar/Wind Helper
0.175
316312AB1-027
Solar/Wind Helper
0.22
316132AB2-190 GEN1
Solar/Wind Helper
0.649
CPLELTFEXP_CPLE->PJM
CLTF
0.722
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.487
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.852
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.843
MECLTFEXP_MEC->PJM
CLTF
1.109
SIGELTFEXP_SIGE->PJM
CLTF
0.036
NYPJM->LTFIMP_NY
CLTF
0.343
LGEELTFEXP_LGEE->PJM
CLTF
0.473
WECLTFEXP_WEC->PJM
CLTF
0.242
LAGNLTFEXP_LAGN->PJM
CLTF
1.488
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.29
TVALTFEXP_TVA->PJM
CLTF
0.772

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:202.03 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1371.17
MW Contribution:0.53
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
3152601GOSPORTA
Adder
0.682
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
CPLELTFEXP_CPLE->PJM
CLTF
4.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.018
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:157.52 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1069.03
MW Contribution:0.51
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151601KERR 3
50/50
0.215
3151581KERR 1
50/50
0.077
3151531CLOVER1
50/50
2.214
3147043LAWRENC
50/50
0.833
3151261ROARAP2
50/50
0.071
970937AG2-583 GEN
Solar/Wind Harmer
39.544
316336AC2-165 C
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
26.303
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.202
3146926FARMVIL
Solar/Wind Harmer
0.234
971377AH1-170 GEN
Solar/Wind Harmer
2.874
3147623JAMES R
Solar/Wind Harmer
0.624
963171AG1-166 GEN
Solar/Wind Harmer
1.391
971563AH1-280 GEN
Solar/Wind Harmer
2.782
970685AG2-442 GEN
Solar/Wind Harmer
17.514
962491AG1-098 GEN
Solar/Wind Harmer
8.209
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.543
970401AG2-262 GEN
Solar/Wind Harmer
0.652
957481AF2-042 GEN
Solar/Wind Harmer
26.84
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.856
316129AC1-054 GEN
Solar/Wind Harmer
0.33
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
5.259
960081AF2-299 GEN
Solar/Wind Harmer
0.593
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151591KERR 2
50/50
0.215
970413AG2-270 GEN
50/50
9.663
3151261ROARAP2
50/50
0.069
3146776BUCKING
Solar/Wind Harmer
0.182
3146926FARMVIL
Solar/Wind Harmer
0.234
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
0.876
971193AH1-056 GEN
Solar/Wind Harmer
16.999
970221AG2-151 GEN
Solar/Wind Harmer
14.368
963181AG1-167 GEN
Solar/Wind Harmer
1.043
959311AF2-222 GEN
Solar/Wind Harmer
19.082
970257AG2-171 GEN
Solar/Wind Harmer
6.613
315785AD2-033 C
Solar/Wind Harmer
1.59
964241AG1-285 GEN
Solar/Wind Harmer
11.084
316131AB2-060 GEN
Solar/Wind Harmer
0.467
316478AD1-087 GEN
Solar/Wind Harmer
0.361
316486AD2-202 GEN
Solar/Wind Harmer
0.106
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.73
3147043LAWRENC
Solar/Wind Harmer
0.052
958131AF2-107 GEN
Solar/Wind Harmer
2.449
971683AH1-343 GEN
Solar/Wind Harmer
2.857
313506AB2-031 GEN
Solar/Wind Harmer
0.184
972205AH1-687 GEN
50/50
29.229
3151611KERR 4
50/50
0.215
3151621KERR 5
50/50
0.215
3151631KERR 6
50/50
0.215
3151641KERR 7
50/50
0.215
3151541CLOVER2
50/50
2.204
3151281ROARAP4
50/50
0.069
3151281ROARAP4
50/50
0.065
971845AH1-439 GEN
Solar/Wind Harmer
22.434
970285AG2-188 GEN
Solar/Wind Harmer
37.679
315657AE1-056 GEN
Solar/Wind Harmer
9.629
946301AF1-294 GEN
Solar/Wind Harmer
5.147
961791AG1-021 GEN
Solar/Wind Harmer
2.504
970683AG2-441 GEN
Solar/Wind Harmer
15.638
970681AG2-440 GEN
Solar/Wind Harmer
12.51
270494AE1-108_GEN
Solar/Wind Harmer
2.538
3144303KENBRDG
Solar/Wind Harmer
0.165
971443AH1-215 GEN
Solar/Wind Harmer
3.431
971447AH1-217 GEN
Solar/Wind Harmer
5.812
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3147173SINAI
Solar/Wind Harmer
0.087
3147243WELCO
Solar/Wind Harmer
0.055
970831AG2-522 GEN
Solar/Wind Harmer
3.614
970865AG2-541 GEN
Solar/Wind Harmer
2.528
316123AC1-075 GEN
Solar/Wind Harmer
0.087
970165AG2-112 GEN
Solar/Wind Harmer
0.513
970163AG2-111 GEN
Solar/Wind Harmer
0.49
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.232
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3144293JTRSVLE
50/50
0.881
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3152661PLYWOOD A
50/50
0.212
3146776BUCKING
Solar/Wind Harmer
2.017
3146776BUCKING
Solar/Wind Harmer
0.163
970301AG2-198 GEN
Solar/Wind Harmer
12.027
3147133PAMPLIN
Solar/Wind Harmer
0.279
3147133PAMPLIN
Solar/Wind Harmer
0.223
971489AH1-241 GEN
Solar/Wind Harmer
14.368
958211AF2-115 GEN
Solar/Wind Harmer
3.13
963191AG1-168 GEN
Solar/Wind Harmer
1.043
971741AH1-377 GEN
Solar/Wind Harmer
24.65
316034AC1-036 C
Solar/Wind Harmer
0.015
970323AG2-213 GEN
Solar/Wind Harmer
8.817
971775AH1-396 GEN
Solar/Wind Harmer
0.331
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.577
315821AE2-092 GEN
Solar/Wind Harmer
0.007
939181AE1-148 GEN
Solar/Wind Harmer
5.338
964791AG1-342 GEN
Solar/Wind Harmer
2.134
3146843MT LREL
Solar/Wind Harmer
0.111
3146843MT LREL
Solar/Wind Harmer
0.111
970099AG2-077 GEN
Solar/Wind Harmer
10.736
970933AG2-581 GEN
Solar/Wind Harmer
5.58
316181AB2-040 GEN
Solar/Wind Harmer
0.086
942751AE2-291 GEN
Solar/Wind Harmer
3.114
3145593CAROLNA
Solar/Wind Harmer
0.057
3145593CAROLNA
Solar/Wind Harmer
0.057
966811AG1-552 GEN
Solar/Wind Harmer
0.619
3145593CAROLNA
Solar/Wind Harmer
0.071
966001AG1-469 GEN
Solar/Wind Helper
0.14
CPLELTFEXP_CPLE->PJM
CLTF
3.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.029
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.93 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1227.79
MW Contribution:0.68
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
970937AG2-583 GEN
Solar/Wind Harmer
52.066
316336AC2-165 C
Solar/Wind Harmer
12.588
972003AH1-546 GEN
Solar/Wind Harmer
34.691
316322AB2-045
Solar/Wind Harmer
1.907
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
971377AH1-170 GEN
Solar/Wind Harmer
3.783
3147623JAMES R
Solar/Wind Harmer
0.468
963171AG1-166 GEN
Solar/Wind Harmer
3.664
971563AH1-280 GEN
Solar/Wind Harmer
3.664
970685AG2-442 GEN
Solar/Wind Harmer
23.061
962491AG1-098 GEN
Solar/Wind Harmer
10.808
316237AB2-079_GEN
Solar/Wind Harmer
0.475
315693AD1-088 GEN
Solar/Wind Harmer
7.658
970401AG2-262 GEN
Solar/Wind Harmer
0.815
957481AF2-042 GEN
Solar/Wind Harmer
35.339
315687AD1-152 GEN
Solar/Wind Harmer
1.264
971065AG2-659 GEN
Solar/Wind Harmer
5.078
316129AC1-054 GEN
Solar/Wind Harmer
0.863
3147043LAWRENC
Adder
0.785
316003AC1-222 GEN
Solar/Wind Harmer
0.902
971795AH1-408 GEN
Solar/Wind Harmer
6.647
960081AF2-299 GEN
Solar/Wind Harmer
0.78
972205AH1-687 GEN
50/50
29.229
971845AH1-439 GEN
Solar/Wind Harmer
29.538
970285AG2-188 GEN
Solar/Wind Harmer
46.824
315657AE1-056 GEN
Solar/Wind Harmer
11.763
946301AF1-294 GEN
Solar/Wind Harmer
7.51
961791AG1-021 GEN
Solar/Wind Harmer
3.664
970683AG2-441 GEN
Solar/Wind Harmer
20.59
970681AG2-440 GEN
Solar/Wind Harmer
16.472
270494AE1-108_GEN
Solar/Wind Harmer
6.187
3144303KENBRDG
Solar/Wind Harmer
-0.019
971443AH1-215 GEN
Solar/Wind Harmer
4.518
971447AH1-217 GEN
Solar/Wind Harmer
7.652
316239AB2-077_GEN
Solar/Wind Harmer
0.475
316238AB2-078_GEN
Solar/Wind Harmer
0.475
316118AC1-105 GEN
Solar/Wind Harmer
0.766
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.758
970865AG2-541 GEN
Solar/Wind Harmer
3.329
316123AC1-075 GEN
Solar/Wind Harmer
0.768
970165AG2-112 GEN
Solar/Wind Harmer
0.676
970163AG2-111 GEN
Solar/Wind Harmer
0.645
946281AF1-292 GEN
Solar/Wind Harmer
0.155
316087AB2-174 GEN
Solar/Wind Harmer
0.965
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.592
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
-0.098
971193AH1-056 GEN
Solar/Wind Harmer
19.605
970221AG2-151 GEN
Solar/Wind Harmer
18.917
963181AG1-167 GEN
Solar/Wind Harmer
2.748
959311AF2-222 GEN
Solar/Wind Harmer
25.175
970257AG2-171 GEN
Solar/Wind Harmer
8.707
315785AD2-033 C
Solar/Wind Harmer
4.981
964241AG1-285 GEN
Solar/Wind Harmer
14.595
316131AB2-060 GEN
Solar/Wind Harmer
1.799
316478AD1-087 GEN
Solar/Wind Harmer
1.005
316486AD2-202 GEN
Solar/Wind Harmer
0.294
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.911
3147043LAWRENC
Solar/Wind Harmer
-0.006
958131AF2-107 GEN
Solar/Wind Harmer
3.26
971683AH1-343 GEN
Solar/Wind Harmer
3.762
966621AG1-532 GEN
Solar/Wind Harmer
0.141
313506AB2-031 GEN
Solar/Wind Harmer
0.538
3144293JTRSVLE
50/50
0.881
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3146776BUCKING
Solar/Wind Harmer
-0.226
3146776BUCKING
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
15.836
3147133PAMPLIN
Solar/Wind Harmer
-0.031
3147133PAMPLIN
Solar/Wind Harmer
-0.025
971489AH1-241 GEN
Solar/Wind Harmer
17.959
958211AF2-115 GEN
Solar/Wind Harmer
4.579
963191AG1-168 GEN
Solar/Wind Harmer
2.748
971741AH1-377 GEN
Solar/Wind Harmer
32.456
316034AC1-036 C
Solar/Wind Harmer
0.432
970323AG2-213 GEN
Solar/Wind Harmer
11.609
971775AH1-396 GEN
Solar/Wind Harmer
1.653
313527AB2-043 GEN
Solar/Wind Harmer
2.63
962561AG1-105 GEN
Solar/Wind Harmer
7.343
315821AE2-092 GEN
Solar/Wind Harmer
2.71
939181AE1-148 GEN
Solar/Wind Harmer
7.029
964791AG1-342 GEN
Solar/Wind Harmer
2.668
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.136
970933AG2-581 GEN
Solar/Wind Harmer
7.348
316181AB2-040 GEN
Solar/Wind Harmer
0.933
942751AE2-291 GEN
Solar/Wind Harmer
4.1
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.721
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.14
CPLELTFEXP_CPLE->PJM
CLTF
3.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.029
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.81 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:753.29
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.23 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:738.58
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.16 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:902.85
MW Contribution:1.2
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
970909AG2-566 GEN
Solar/Wind Harmer
6.35
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.445
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.12 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:902.56
MW Contribution:1.2
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.445
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
970909AG2-566 GEN
Solar/Wind Harmer
6.35
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.93 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:880.22
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
73.556
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970301AG2-198 GEN
Solar/Wind Harmer
33.428
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970933AG2-581 GEN
Solar/Wind Harmer
36.681
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.97 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:838.61
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970301AG2-198 GEN
Solar/Wind Harmer
33.428
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.97 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:838.61
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970301AG2-198 GEN
Solar/Wind Harmer
33.428
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:212.98 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1488.76
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:212.93 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1488.37
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:209.35 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1463.37
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970933AG2-581 GEN
Solar/Wind Harmer
36.473
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
971967AH1-528 GEN
Solar/Wind Harmer
73.139
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:207.29 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1184.7
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
971967AH1-528 GEN
Solar/Wind Harmer
55.401
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970933AG2-581 GEN
Solar/Wind Harmer
27.701
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:204.76 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1170.27
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:203.45 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1422.11
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:203.45 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1422.11
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.37 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:911.29
MW Contribution:0.79
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.288
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.006
970535AG2-341 GEN
50/50
2.93
3152661PLYWOOD A
50/50
0.279
3146776BUCKING
Solar/Wind Harmer
-0.308
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.483
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.209
963191AG1-168 GEN
Solar/Wind Harmer
3.725
971741AH1-377 GEN
Solar/Wind Harmer
43.964
316034AC1-036 C
Solar/Wind Harmer
0.583
970323AG2-213 GEN
Solar/Wind Harmer
15.694
971775AH1-396 GEN
Solar/Wind Harmer
2.235
313527AB2-043 GEN
Solar/Wind Harmer
3.534
962561AG1-105 GEN
Solar/Wind Harmer
9.782
939181AE1-148 GEN
Solar/Wind Harmer
9.427
964791AG1-342 GEN
Solar/Wind Harmer
3.547
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.781
970933AG2-581 GEN
Solar/Wind Harmer
9.57
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.288
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.288
970413AG2-270 GEN
50/50
12.878
3146776BUCKING
Solar/Wind Harmer
-0.028
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.6
970909AG2-566 GEN
Solar/Wind Harmer
4.079
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.601
963181AG1-167 GEN
Solar/Wind Harmer
3.725
959311AF2-222 GEN
Solar/Wind Harmer
34.052
970257AG2-171 GEN
Solar/Wind Harmer
11.771
315785AD2-033 C
Solar/Wind Harmer
6.728
964241AG1-285 GEN
Solar/Wind Harmer
19.662
316131AB2-060 GEN
Solar/Wind Harmer
2.419
316478AD1-087 GEN
Solar/Wind Harmer
1.34
316486AD2-202 GEN
Solar/Wind Harmer
0.392
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.446
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.951
3147043LAWRENC
50/50
1.104
316322AB2-045
Solar/Wind Harmer
2.6
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.967
971563AH1-280 GEN
Solar/Wind Harmer
4.967
970685AG2-442 GEN
Solar/Wind Harmer
31.227
962491AG1-098 GEN
Solar/Wind Harmer
14.504
316237AB2-079_GEN
Solar/Wind Harmer
0.638
315693AD1-088 GEN
Solar/Wind Harmer
10.264
970401AG2-262 GEN
Solar/Wind Harmer
1.084
957481AF2-042 GEN
Solar/Wind Harmer
46.952
315687AD1-152 GEN
Solar/Wind Harmer
1.686
971065AG2-659 GEN
Solar/Wind Harmer
6.782
316129AC1-054 GEN
Solar/Wind Harmer
1.152
316003AC1-222 GEN
Solar/Wind Harmer
1.16
971795AH1-408 GEN
Solar/Wind Harmer
8.774
960081AF2-299 GEN
Solar/Wind Harmer
1.019
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
316212AC1-099_GEN
Solar/Wind Harmer
0.612
970919AG2-571 GEN
Solar/Wind Harmer
2.186
970087AG2-069 GEN
Solar/Wind Harmer
6.469
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.401
962571AG1-106 GEN
Solar/Wind Harmer
0.963
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.896
316049AB1-081 GEN
Solar/Wind Harmer
0.717
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.692
316023GEN1_S
Solar/Wind Harmer
0.442
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.19
971683AH1-343 GEN
Solar/Wind Harmer
4.749
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.704
316283AC2-100 C
Solar/Wind Harmer
0.785
316210AC1-098 GEN
Solar/Wind Harmer
1.101
316327AA2-057 GEN
Solar/Wind Harmer
0.705
970917AG2-570 GEN
Solar/Wind Harmer
17.269
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.38
316365GEN2_N
Solar/Wind Harmer
0.442
961601AG1-000A GEN
Solar/Wind Harmer
2.606
316317KELFORD C
Solar/Wind Harmer
0.305
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.082
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.021
961681AG1-008 GEN
Solar/Wind Harmer
5.021
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.333
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.124
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Helper
1.427
316181AB2-040 GEN
Solar/Wind Harmer
1.222
316222AC1-221 GEN
Solar/Wind Harmer
0.854
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.948
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.979
3145783HORNRTN
Solar/Wind Harmer
0.783
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.81
316274AC1-208 GEN
Solar/Wind Harmer
0.791
942751AE2-291 GEN
Solar/Wind Harmer
4.521
972187AH1-678 GEN
Adder
1.767
972185AH1-677 GEN
Adder
3.338
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.115
961601AG1-000A GEN
Solar/Wind Harmer
2.573
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
315821AE2-092 GEN
Solar/Wind Helper
2.966
3151621KERR 5
50/50
0.288
3151631KERR 6
50/50
0.288
3151641KERR 7
50/50
0.288
3151541CLOVER2
50/50
2.937
971845AH1-439 GEN
Solar/Wind Harmer
40.264
970285AG2-188 GEN
Solar/Wind Harmer
63.811
315657AE1-056 GEN
Solar/Wind Harmer
15.96
946301AF1-294 GEN
Solar/Wind Harmer
10.183
961791AG1-021 GEN
Solar/Wind Harmer
4.967
970683AG2-441 GEN
Solar/Wind Harmer
27.881
970681AG2-440 GEN
Solar/Wind Harmer
22.305
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.107
316239AB2-077_GEN
Solar/Wind Harmer
0.638
316238AB2-078_GEN
Solar/Wind Harmer
0.638
316118AC1-105 GEN
Solar/Wind Harmer
1.013
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.344
970865AG2-541 GEN
Solar/Wind Harmer
4.105
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
0.785
970163AG2-111 GEN
Solar/Wind Harmer
0.749
971967AH1-528 GEN
Solar/Wind Harmer
15.159
315607AA1-063A GEN
Solar/Wind Harmer
0.776
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.313
970581AG2-369 GEN
Solar/Wind Harmer
3.709
316319Z2-044 C
Solar/Wind Harmer
0.377
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.536
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.58
970673AG2-436 GEN
Solar/Wind Harmer
13.57
970673AG2-436 GEN
Solar/Wind Harmer
6.871
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.47
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
CPLELTFEXP_CPLE->PJM
CLTF
4.525
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.338
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.871
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.899
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.305
LGEELTFEXP_LGEE->PJM
CLTF
0.208
WECLTFEXP_WEC->PJM
CLTF
0.117
LAGNLTFEXP_LAGN->PJM
CLTF
2.472
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.204
TVALTFEXP_TVA->PJM
CLTF
1.2

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:130.23 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:910.33
MW Contribution:0.75
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3151541CLOVER2
50/50
2.825
971845AH1-439 GEN
Solar/Wind Harmer
40.074
970285AG2-188 GEN
Solar/Wind Harmer
63.49
315657AE1-056 GEN
Solar/Wind Harmer
15.775
946301AF1-294 GEN
Solar/Wind Harmer
10.053
961791AG1-021 GEN
Solar/Wind Harmer
4.904
970683AG2-441 GEN
Solar/Wind Harmer
27.471
970681AG2-440 GEN
Solar/Wind Harmer
21.977
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
5.999
316239AB2-077_GEN
Solar/Wind Harmer
0.62
316238AB2-078_GEN
Solar/Wind Harmer
0.62
316118AC1-105 GEN
Solar/Wind Harmer
0.971
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.022
970865AG2-541 GEN
Solar/Wind Harmer
3.914
946281AF1-292 GEN
Solar/Wind Harmer
0.189
316087AB2-174 GEN
Solar/Wind Harmer
1.174
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.851
970165AG2-112 GEN
Solar/Wind Harmer
0.749
970163AG2-111 GEN
Solar/Wind Harmer
0.714
971967AH1-528 GEN
Solar/Wind Harmer
14.144
315607AA1-063A GEN
Solar/Wind Harmer
0.713
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.505
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.179
3144293JTRSVLE
50/50
0.993
970535AG2-341 GEN
50/50
2.832
3152661PLYWOOD A
50/50
0.267
3146776BUCKING
Solar/Wind Harmer
-0.306
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.246
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.13
963191AG1-168 GEN
Solar/Wind Harmer
3.678
971741AH1-377 GEN
Solar/Wind Harmer
43.39
316034AC1-036 C
Solar/Wind Harmer
0.573
970323AG2-213 GEN
Solar/Wind Harmer
15.422
971775AH1-396 GEN
Solar/Wind Harmer
2.196
313527AB2-043 GEN
Solar/Wind Harmer
3.438
962561AG1-105 GEN
Solar/Wind Harmer
9.444
939181AE1-148 GEN
Solar/Wind Harmer
9.07
964791AG1-342 GEN
Solar/Wind Harmer
3.418
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.069
970933AG2-581 GEN
Solar/Wind Harmer
9.057
316181AB2-040 GEN
Solar/Wind Harmer
1.135
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.876
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.902
3145783HORNRTN
Solar/Wind Harmer
0.721
3145783HORNRTN
Solar/Wind Harmer
0.225
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.766
316426AA2-053 GEN
Solar/Wind Harmer
0.746
942751AE2-291 GEN
Solar/Wind Harmer
4.318
316274AC1-208 GEN
Solar/Wind Harmer
0.714
972187AH1-678 GEN
Adder
1.624
315821AE2-092 GEN
Solar/Wind Helper
2.997
3144293JTRSVLE
50/50
1.179
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.386
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.532
970909AG2-566 GEN
Solar/Wind Harmer
4.034
3147133PAMPLIN
Solar/Wind Harmer
-0.131
971193AH1-056 GEN
Solar/Wind Harmer
26.292
963181AG1-167 GEN
Solar/Wind Harmer
3.678
959311AF2-222 GEN
Solar/Wind Harmer
33.489
970257AG2-171 GEN
Solar/Wind Harmer
11.567
315785AD2-033 C
Solar/Wind Harmer
6.603
964241AG1-285 GEN
Solar/Wind Harmer
19.215
316131AB2-060 GEN
Solar/Wind Harmer
2.356
316478AD1-087 GEN
Solar/Wind Harmer
1.288
316486AD2-202 GEN
Solar/Wind Harmer
0.377
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.37
960061AF2-297 GEN
Solar/Wind Harmer
6.139
971683AH1-343 GEN
Solar/Wind Harmer
4.525
966621AG1-532 GEN
Solar/Wind Harmer
0.171
313506AB2-031 GEN
Solar/Wind Harmer
0.654
316283AC2-100 C
Solar/Wind Harmer
0.703
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.125
3144293JTRSVLE
50/50
1.179
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.838
316322AB2-045
Solar/Wind Harmer
2.588
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.904
971563AH1-280 GEN
Solar/Wind Harmer
4.904
970685AG2-442 GEN
Solar/Wind Harmer
30.768
962491AG1-098 GEN
Solar/Wind Harmer
14.136
316237AB2-079_GEN
Solar/Wind Harmer
0.62
315693AD1-088 GEN
Solar/Wind Harmer
9.987
970401AG2-262 GEN
Solar/Wind Harmer
1.044
957481AF2-042 GEN
Solar/Wind Harmer
45.172
315687AD1-152 GEN
Solar/Wind Harmer
1.609
971065AG2-659 GEN
Solar/Wind Harmer
6.46
316129AC1-054 GEN
Solar/Wind Harmer
1.096
3147043LAWRENC
Adder
0.992
316003AC1-222 GEN
Solar/Wind Harmer
1.105
971795AH1-408 GEN
Solar/Wind Harmer
8.324
960081AF2-299 GEN
Solar/Wind Harmer
0.951
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316336AC2-165 C
Solar/Wind Helper
1.456
CPLELTFEXP_CPLE->PJM
CLTF
3.699
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.437
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.959
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.906
MECLTFEXP_MEC->PJM
CLTF
0.618
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.351
LGEELTFEXP_LGEE->PJM
CLTF
0.175
WECLTFEXP_WEC->PJM
CLTF
0.091
LAGNLTFEXP_LAGN->PJM
CLTF
1.81
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.409
TVALTFEXP_TVA->PJM
CLTF
0.888

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:126.86 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:886.73
MW Contribution:0.78
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.899
971845AH1-439 GEN
Solar/Wind Harmer
40.166
970285AG2-188 GEN
Solar/Wind Harmer
63.65
315657AE1-056 GEN
Solar/Wind Harmer
15.889
946301AF1-294 GEN
Solar/Wind Harmer
10.133
961791AG1-021 GEN
Solar/Wind Harmer
4.943
970683AG2-441 GEN
Solar/Wind Harmer
27.73
970681AG2-440 GEN
Solar/Wind Harmer
22.184
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.068
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.995
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.242
970865AG2-541 GEN
Solar/Wind Harmer
4.039
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.259
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.881
970165AG2-112 GEN
Solar/Wind Harmer
0.776
970163AG2-111 GEN
Solar/Wind Harmer
0.74
971967AH1-528 GEN
Solar/Wind Harmer
14.996
315607AA1-063A GEN
Solar/Wind Harmer
0.76
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.198
970581AG2-369 GEN
Solar/Wind Harmer
3.61
315652AC1-086 GEN
Solar/Wind Harmer
7.443
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.358
970673AG2-436 GEN
Solar/Wind Harmer
13.401
970673AG2-436 GEN
Solar/Wind Harmer
6.785
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
4.481
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.189
3144293JTRSVLE
50/50
1.001
970535AG2-341 GEN
50/50
2.895
3152661PLYWOOD A
50/50
0.274
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.395
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.179
963191AG1-168 GEN
Solar/Wind Harmer
3.707
971741AH1-377 GEN
Solar/Wind Harmer
43.759
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.596
971775AH1-396 GEN
Solar/Wind Harmer
2.221
313527AB2-043 GEN
Solar/Wind Harmer
3.501
962561AG1-105 GEN
Solar/Wind Harmer
9.651
939181AE1-148 GEN
Solar/Wind Harmer
9.294
964791AG1-342 GEN
Solar/Wind Harmer
3.496
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.573
970933AG2-581 GEN
Solar/Wind Harmer
9.469
316181AB2-040 GEN
Solar/Wind Harmer
1.215
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.932
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.96
3145783HORNRTN
Solar/Wind Harmer
0.768
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.8
316426AA2-053 GEN
Solar/Wind Harmer
0.794
316274AC1-208 GEN
Solar/Wind Harmer
0.763
942751AE2-291 GEN
Solar/Wind Harmer
4.488
972187AH1-678 GEN
Adder
1.739
972185AH1-677 GEN
Adder
3.291
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
315821AE2-092 GEN
Solar/Wind Helper
2.986
3144293JTRSVLE
50/50
1.189
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.101
3151531CLOVER1
50/50
2.913
3147043LAWRENC
50/50
1.1
316322AB2-045
Solar/Wind Harmer
2.593
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.943
971563AH1-280 GEN
Solar/Wind Harmer
4.943
970685AG2-442 GEN
Solar/Wind Harmer
31.058
962491AG1-098 GEN
Solar/Wind Harmer
14.389
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.178
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
46.433
315687AD1-152 GEN
Solar/Wind Harmer
1.654
971065AG2-659 GEN
Solar/Wind Harmer
6.674
316129AC1-054 GEN
Solar/Wind Harmer
1.134
971795AH1-408 GEN
Solar/Wind Harmer
8.763
316003AC1-222 GEN
Solar/Wind Harmer
1.138
960081AF2-299 GEN
Solar/Wind Harmer
1.022
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.589
970919AG2-571 GEN
Solar/Wind Harmer
2.13
970087AG2-069 GEN
Solar/Wind Harmer
6.297
316023GEN1_S
Solar/Wind Harmer
0.451
316011AB1-132 GEN
Solar/Wind Harmer
1.384
962571AG1-106 GEN
Solar/Wind Harmer
0.951
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.665
316336AC2-165 C
Solar/Wind Helper
1.458
3144293JTRSVLE
50/50
1.189
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.71
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.572
970909AG2-566 GEN
Solar/Wind Harmer
4.062
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.482
963181AG1-167 GEN
Solar/Wind Harmer
3.707
959311AF2-222 GEN
Solar/Wind Harmer
33.848
970257AG2-171 GEN
Solar/Wind Harmer
11.697
315785AD2-033 C
Solar/Wind Harmer
6.684
964241AG1-285 GEN
Solar/Wind Harmer
19.507
316131AB2-060 GEN
Solar/Wind Harmer
2.398
316478AD1-087 GEN
Solar/Wind Harmer
1.322
316486AD2-202 GEN
Solar/Wind Harmer
0.387
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.38
960061AF2-297 GEN
Solar/Wind Harmer
6.313
971683AH1-343 GEN
Solar/Wind Harmer
4.664
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.7
316283AC2-100 C
Solar/Wind Harmer
0.734
316210AC1-098 GEN
Solar/Wind Harmer
1.061
970917AG2-570 GEN
Solar/Wind Harmer
16.827
316365GEN2_N
Solar/Wind Harmer
0.451
316327AA2-057 GEN
Solar/Wind Harmer
0.674
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.366
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
3.934
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.902
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.343
MECLTFEXP_MEC->PJM
CLTF
0.782
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.325
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.127
LAGNLTFEXP_LAGN->PJM
CLTF
2.053
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.953
TVALTFEXP_TVA->PJM
CLTF
1.009

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.39 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:827.52
MW Contribution:0.85
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.559
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.558
970909AG2-566 GEN
Solar/Wind Harmer
4.05
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.415
963181AG1-167 GEN
Solar/Wind Harmer
3.697
959311AF2-222 GEN
Solar/Wind Harmer
33.722
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.998
970535AG2-341 GEN
50/50
2.87
3152661PLYWOOD A
50/50
0.275
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.329
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.162
963191AG1-168 GEN
Solar/Wind Harmer
3.697
971741AH1-377 GEN
Solar/Wind Harmer
43.59
316034AC1-036 C
Solar/Wind Harmer
0.577
970323AG2-213 GEN
Solar/Wind Harmer
15.535
971775AH1-396 GEN
Solar/Wind Harmer
2.212
313527AB2-043 GEN
Solar/Wind Harmer
3.479
962561AG1-105 GEN
Solar/Wind Harmer
9.636
964791AG1-342 GEN
Solar/Wind Harmer
3.494
939181AE1-148 GEN
Solar/Wind Harmer
9.198
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.308
970933AG2-581 GEN
Solar/Wind Harmer
9.214
316181AB2-040 GEN
Solar/Wind Harmer
1.159
942751AE2-291 GEN
Solar/Wind Harmer
5.121
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.895
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.788
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.878
316322AB2-045
Solar/Wind Harmer
2.592
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.929
971563AH1-280 GEN
Solar/Wind Harmer
4.929
970685AG2-442 GEN
Solar/Wind Harmer
30.955
962491AG1-098 GEN
Solar/Wind Harmer
14.261
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.081
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
45.769
315687AD1-152 GEN
Solar/Wind Harmer
1.638
971065AG2-659 GEN
Solar/Wind Harmer
6.564
316129AC1-054 GEN
Solar/Wind Harmer
1.114
3147043LAWRENC
Adder
1.008
316003AC1-222 GEN
Solar/Wind Harmer
1.162
971795AH1-408 GEN
Solar/Wind Harmer
8.467
960081AF2-299 GEN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.565
970919AG2-571 GEN
Solar/Wind Harmer
2.04
970087AG2-069 GEN
Solar/Wind Harmer
6.032
316336AC2-165 C
Solar/Wind Helper
1.446
3145783HORNRTN
Solar/Wind Harmer
0.922
3145783HORNRTN
Solar/Wind Harmer
0.738
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.763
316274AC1-208 GEN
Solar/Wind Harmer
0.732
972187AH1-678 GEN
Adder
1.663
315821AE2-092 GEN
Solar/Wind Helper
2.985
970257AG2-171 GEN
Solar/Wind Harmer
11.651
315785AD2-033 C
Solar/Wind Harmer
6.656
964241AG1-285 GEN
Solar/Wind Harmer
19.405
316131AB2-060 GEN
Solar/Wind Harmer
2.383
316478AD1-087 GEN
Solar/Wind Harmer
1.306
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.383
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.864
971845AH1-439 GEN
Solar/Wind Harmer
40.143
970285AG2-188 GEN
Solar/Wind Harmer
63.606
315657AE1-056 GEN
Solar/Wind Harmer
15.849
946301AF1-294 GEN
Solar/Wind Harmer
10.105
961791AG1-021 GEN
Solar/Wind Harmer
4.929
970683AG2-441 GEN
Solar/Wind Harmer
27.639
970681AG2-440 GEN
Solar/Wind Harmer
22.111
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.044
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
0.998
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.123
970865AG2-541 GEN
Solar/Wind Harmer
4.251
316123AC1-075 GEN
Solar/Wind Harmer
0.968
970165AG2-112 GEN
Solar/Wind Harmer
0.853
970163AG2-111 GEN
Solar/Wind Harmer
0.813
946281AF1-292 GEN
Solar/Wind Harmer
0.193
316087AB2-174 GEN
Solar/Wind Harmer
1.199
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.441
315607AA1-063A GEN
Solar/Wind Harmer
0.73
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.021
970581AG2-369 GEN
Solar/Wind Harmer
3.458
270494AE1-108_GEN
Solar/Wind Helper
4.516
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
960061AF2-297 GEN
Solar/Wind Harmer
6.356
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.828
966621AG1-532 GEN
Solar/Wind Harmer
0.175
313506AB2-031 GEN
Solar/Wind Harmer
0.668
316283AC2-100 C
Solar/Wind Harmer
0.723
316210AC1-098 GEN
Solar/Wind Harmer
1.017
970917AG2-570 GEN
Solar/Wind Harmer
16.116
316327AA2-057 GEN
Solar/Wind Harmer
0.646
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
3.818
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.266
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.791
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.144
MECLTFEXP_MEC->PJM
CLTF
0.716
SIGELTFEXP_SIGE->PJM
CLTF
0.02
NYPJM->LTFIMP_NY
CLTF
0.309
LGEELTFEXP_LGEE->PJM
CLTF
0.214
WECLTFEXP_WEC->PJM
CLTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
1.942
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.684
TVALTFEXP_TVA->PJM
CLTF
0.953

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.79 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:644.61
MW Contribution:0.58
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.182
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.848
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.762
972187AH1-678 GEN
50/50
1.749
3146776BUCKING
Solar/Wind Harmer
2.741
3146776BUCKING
Solar/Wind Harmer
0.222
970301AG2-198 GEN
Solar/Wind Harmer
16.173
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.2
963191AG1-168 GEN
Solar/Wind Harmer
1.4
971741AH1-377 GEN
Solar/Wind Harmer
33.04
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.75
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.214
939181AE1-148 GEN
Solar/Wind Harmer
6.93
964791AG1-342 GEN
Solar/Wind Harmer
2.751
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.815
970933AG2-581 GEN
Solar/Wind Harmer
6.948
316181AB2-040 GEN
Solar/Wind Harmer
0.106
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.761
3145593CAROLNA
Solar/Wind Harmer
0.087
3145783HORNRTN
Solar/Wind Harmer
1.218
3145783HORNRTN
Solar/Wind Harmer
0.974
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.327
316274AC1-208 GEN
Solar/Wind Harmer
0.31
315821AE2-092 GEN
Solar/Wind Helper
2.982
3144293JTRSVLE
50/50
1.182
3151601KERR 3
50/50
0.278
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.857
3147043LAWRENC
50/50
1.061
3151261ROARAP2
50/50
0.087
3151051BRUNSWICKS1
50/50
1.582
3151021BRUNSWICKG1
50/50
0.762
971451AH1-221 GEN
50/50
2.315
316322AB2-045
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.867
971563AH1-280 GEN
Solar/Wind Harmer
3.734
970685AG2-442 GEN
Solar/Wind Harmer
23.432
962491AG1-098 GEN
Solar/Wind Harmer
10.785
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.574
970401AG2-262 GEN
Solar/Wind Harmer
0.841
957481AF2-042 GEN
Solar/Wind Harmer
34.537
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.943
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.643
960081AF2-299 GEN
Solar/Wind Harmer
0.73
3145783HORNRTN
Solar/Wind Harmer
0.068
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
2.021
970087AG2-069 GEN
Solar/Wind Harmer
4.539
316336AC2-165 C
Solar/Wind Helper
1.447
3144293JTRSVLE
50/50
1.182
3151591KERR 2
50/50
0.278
970413AG2-270 GEN
50/50
12.466
3151261ROARAP2
50/50
0.085
3151031BRUNSWICKG2
50/50
0.762
3146776BUCKING
Solar/Wind Harmer
0.247
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.043
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.85
963181AG1-167 GEN
Solar/Wind Harmer
1.4
959311AF2-222 GEN
Solar/Wind Harmer
25.461
970257AG2-171 GEN
Solar/Wind Harmer
8.812
315785AD2-033 C
Solar/Wind Harmer
2.115
964241AG1-285 GEN
Solar/Wind Harmer
14.651
316131AB2-060 GEN
Solar/Wind Harmer
0.614
316478AD1-087 GEN
Solar/Wind Harmer
0.465
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.699
971683AH1-343 GEN
Solar/Wind Harmer
3.468
313506AB2-031 GEN
Solar/Wind Harmer
0.226
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.53
970917AG2-570 GEN
Solar/Wind Harmer
5.054
316327AA2-057 GEN
Solar/Wind Harmer
0.085
316313AB2-026
Solar/Wind Helper
0.339
316258AE1-075 C
Solar/Wind Helper
0.305
316405AF2-144 C
Solar/Wind Helper
0.254
3148013FISHERV
Solar/Wind Helper
0.124
3151611KERR 4
50/50
0.278
3151621KERR 5
50/50
0.278
3151631KERR 6
50/50
0.278
3151641KERR 7
50/50
0.278
3151541CLOVER2
50/50
2.843
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.079
963041AG1-153 GEN
50/50
1.544
971845AH1-439 GEN
Solar/Wind Harmer
30.475
970285AG2-188 GEN
Solar/Wind Harmer
51.158
315657AE1-056 GEN
Solar/Wind Harmer
12.943
946301AF1-294 GEN
Solar/Wind Harmer
6.907
961791AG1-021 GEN
Solar/Wind Harmer
3.36
970683AG2-441 GEN
Solar/Wind Harmer
20.922
970681AG2-440 GEN
Solar/Wind Harmer
16.737
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.571
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.326
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.61
970865AG2-541 GEN
Solar/Wind Harmer
3.002
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.286
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.576
970163AG2-111 GEN
Solar/Wind Harmer
0.549
971967AH1-528 GEN
Solar/Wind Harmer
10.852
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.026
970581AG2-369 GEN
Solar/Wind Harmer
2.602
270494AE1-108_GEN
Solar/Wind Helper
4.482
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
CPLELTFEXP_CPLE->PJM
CLTF
3.771
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.922
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.157
MECLTFEXP_MEC->PJM
CLTF
0.729
SIGELTFEXP_SIGE->PJM
CLTF
0.02
NYPJM->LTFIMP_NY
CLTF
0.308
LGEELTFEXP_LGEE->PJM
CLTF
0.221
WECLTFEXP_WEC->PJM
CLTF
0.117
LAGNLTFEXP_LAGN->PJM
CLTF
1.944
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.608
TVALTFEXP_TVA->PJM
CLTF
0.955

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.83 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1864.16
MW Contribution:0.77
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
1.972
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
970413AG2-270 GEN
50/50
11.155
3151261ROARAP2
50/50
0.144
970533AG2-339 GEN
50/50
14.043
970531AG2-338 GEN
50/50
5.617
315242AE2-183_GT2
50/50
2.516
315241AE2-183_GT1
50/50
2.5
972185AH1-677 GEN
50/50
9.069
3151041BRUNSWICKG3
50/50
1.972
972187AH1-678 GEN
50/50
4.526
3151361ROSEMG1
50/50
0.471
3151371ROSEMS1
50/50
0.292
3151381ROSEMG2
50/50
0.22
3144356SAPONY
Solar/Wind Harmer
0.948
970933AG2-581 GEN
Solar/Wind Harmer
15.092
316181AB2-040 GEN
Solar/Wind Harmer
2.139
3145796HORNRTN
Solar/Wind Harmer
-0.044
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
970099AG2-077 GEN
Solar/Wind Harmer
17.742
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.013
966811AG1-552 GEN
Solar/Wind Harmer
1.5
3145593CAROLNA
Solar/Wind Harmer
0.111
3145783HORNRTN
Solar/Wind Harmer
1.561
3145783HORNRTN
Solar/Wind Harmer
1.249
3145783HORNRTN
Solar/Wind Harmer
0.39
3145783HORNRTN
Solar/Wind Harmer
0.156
316426AA2-053 GEN
Solar/Wind Harmer
1.293
316274AC1-208 GEN
Solar/Wind Harmer
1.319
939181AE1-148 GEN
Solar/Wind Harmer
6.767
961601AG1-000A GEN
Solar/Wind Harmer
4.682
316263AC1-034 GEN
Solar/Wind Harmer
5.552
313527AB2-043 GEN
Solar/Wind Harmer
1.888
3145493TOT1
Solar/Wind Harmer
0.175
3145453TOT5
Solar/Wind Harmer
0.105
3145603CNETO
Solar/Wind Harmer
0.07
962561AG1-105 GEN
Solar/Wind Harmer
6.333
964791AG1-342 GEN
Solar/Wind Harmer
2.391
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970323AG2-213 GEN
Solar/Wind Harmer
5.164
971775AH1-396 GEN
Solar/Wind Harmer
0.735
316034AC1-036 C
Solar/Wind Harmer
0.191
971741AH1-377 GEN
Solar/Wind Harmer
11.893
3146173TUNIS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
316222AC1-221 GEN
Solar/Wind Harmer
1.018
3145893MURPHYS
Solar/Wind Harmer
0.278
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.02
315779AE2-040
50/50
3.378
315244AE2-183_ST
50/50
4.349
963041AG1-153 GEN
50/50
3.994
3151541CLOVER2
50/50
2.544
3151281ROARAP4
50/50
0.144
3151281ROARAP4
50/50
0.134
316315AB2-025 C
Solar/Wind Harmer
0.734
315814AE2-033 C
Solar/Wind Harmer
24.939
941031AE2-094 GEN
Solar/Wind Harmer
33.281
944011AF1-069 GEN
Solar/Wind Harmer
10.428
970673AG2-436 GEN
Solar/Wind Harmer
36.399
970673AG2-436 GEN
Solar/Wind Harmer
18.43
946281AF1-292 GEN
Solar/Wind Harmer
0.383
971967AH1-528 GEN
Solar/Wind Harmer
31.705
970085AG2-068 GEN
Solar/Wind Harmer
10.008
970581AG2-369 GEN
Solar/Wind Harmer
8.607
316087AB2-174 GEN
Solar/Wind Harmer
2.265
315652AC1-086 GEN
Solar/Wind Harmer
17.05
3145796HORNRTN
Solar/Wind Harmer
-0.047
3145796HORNRTN
Solar/Wind Harmer
-0.006
3137643SOCKMAN
Solar/Wind Harmer
-0.057
970831AG2-522 GEN
Solar/Wind Harmer
6.31
315607AA1-063A GEN
Solar/Wind Harmer
1.207
316319Z2-044 C
Solar/Wind Harmer
0.657
3146043SEABORD
Solar/Wind Harmer
-0.012
316239AB2-077_GEN
Solar/Wind Harmer
0.35
316238AB2-078_GEN
Solar/Wind Harmer
0.35
3146033SCOT NK
Solar/Wind Harmer
-0.045
3145573BETHELC
Solar/Wind Harmer
-0.011
3145573BETHELC
Solar/Wind Harmer
-0.011
316420AA1-050 GEN
Solar/Wind Harmer
1.267
316118AC1-105 GEN
Solar/Wind Harmer
0.759
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
4.731
971443AH1-215 GEN
Solar/Wind Harmer
2.043
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
3144303KENBRDG
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.089
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316005AA1-067
Solar/Wind Harmer
0.207
3145746EVERETS
Solar/Wind Harmer
-0.041
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
970181AG2-120 GEN
Solar/Wind Harmer
1.344
316318V4-068
Solar/Wind Harmer
0.249
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.01
965291AG1-394 GEN
Solar/Wind Harmer
0.871
970683AG2-441 GEN
Solar/Wind Harmer
7.621
970681AG2-440 GEN
Solar/Wind Harmer
6.097
3143316POE
Solar/Wind Harmer
-0.038
970865AG2-541 GEN
Solar/Wind Harmer
3.743
946301AF1-294 GEN
Solar/Wind Harmer
2.361
961791AG1-021 GEN
Solar/Wind Harmer
1.152
315657AE1-056 GEN
Solar/Wind Harmer
3.313
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.864
270455AD2-022 GEN
Solar/Wind Harmer
1.529
270457AD2-023 GEN
Solar/Wind Harmer
0.775
315732AD1-074 GEN1
Solar/Wind Harmer
1.65
315733AD1-074 GEN2
Solar/Wind Harmer
1.65
315735AD1-075 GEN1
Solar/Wind Harmer
0.825
316123AC1-075 GEN
Solar/Wind Harmer
0.874
970165AG2-112 GEN
Solar/Wind Harmer
0.77
970163AG2-111 GEN
Solar/Wind Harmer
0.734
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.593
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
316132AB2-190 GEN1
Solar/Wind Helper
0.976
316233AE1-074 FULL
Solar/Wind Helper
0.226
316312AB1-027
Solar/Wind Helper
0.27
3143873LANEXA
Solar/Wind Helper
0.076
316369SG1_INVT
Solar/Wind Helper
0.602
3145933PARMELE
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
4.681
958211AF2-115 GEN
Solar/Wind Harmer
1.439
963191AG1-168 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3144293JTRSVLE
Adder
0.22
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.007
316065AD1-022 GEN
Solar/Wind Harmer
4.293
942751AE2-291 GEN
Solar/Wind Harmer
4.718
315742AE1-103 GEN
Solar/Wind Harmer
0.706
3146376EDENTON
Solar/Wind Harmer
0.191
3146376EDENTON
Solar/Wind Harmer
0.191
316240AF1-291 C
Solar/Wind Helper
0.402
3142946ENON
Solar/Wind Helper
0.017
966871AG1-558 GEN
Solar/Wind Helper
0.221
3143526WINTERP
Solar/Wind Helper
0.769
316468AD1-105 GEN
Solar/Wind Helper
0.714
316075AC2-137 C
Solar/Wind Helper
0.21
316033AB2-134 GEN
Solar/Wind Helper
0.43
315697AD1-025 GEN
Solar/Wind Helper
1.43
315243AE2-183_GT3
50/50
2.516
3151051BRUNSWICKS1
50/50
4.094
3151021BRUNSWICKG1
50/50
1.972
971451AH1-221 GEN
50/50
5.991
3147043LAWRENC
50/50
1.32
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
3151531CLOVER1
50/50
2.556
3151261ROARAP2
50/50
0.148
316023GEN1_S
Solar/Wind Harmer
1.302
960081AF2-299 GEN
Solar/Wind Harmer
1.926
970919AG2-571 GEN
Solar/Wind Harmer
5.093
970087AG2-069 GEN
Solar/Wind Harmer
15.012
971795AH1-408 GEN
Solar/Wind Harmer
11.982
316011AB1-132 GEN
Solar/Wind Harmer
3.171
962571AG1-106 GEN
Solar/Wind Harmer
2.179
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145796HORNRTN
Solar/Wind Harmer
-0.015
957481AF2-042 GEN
Solar/Wind Harmer
44.356
315722AD1-056 GEN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
-0.013
315693AD1-088 GEN
Solar/Wind Harmer
6.574
939411AE1-173 GEN
Solar/Wind Harmer
65.115
962491AG1-098 GEN
Solar/Wind Harmer
8.662
316190AA2-174 GEN
Solar/Wind Harmer
0.157
316129AC1-054 GEN
Solar/Wind Harmer
1.1
315687AD1-152 GEN
Solar/Wind Harmer
1.509
971065AG2-659 GEN
Solar/Wind Harmer
6.236
3146233WITAKRS
Solar/Wind Harmer
-0.047
316359AB2-059 GEN
Solar/Wind Harmer
1.597
316049AB1-081 GEN
Solar/Wind Harmer
1.278
3142053HEARTS
Solar/Wind Harmer
0.139
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.028
316237AB2-079_GEN
Solar/Wind Harmer
0.35
961671AG1-007 GEN
Solar/Wind Harmer
0.143
3146083TARBORO
Solar/Wind Harmer
-0.011
3145493TOT1
Solar/Wind Harmer
0.335
970401AG2-262 GEN
Solar/Wind Harmer
0.731
3146263WOODLND
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.011
316494AC1-189 GEN
Solar/Wind Harmer
1.164
3145683EARLEYS
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
1.004
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
0.296
3146293MARTNCO
Solar/Wind Harmer
0.061
970685AG2-442 GEN
Solar/Wind Harmer
8.535
316174AB2-169 GEN
Solar/Wind Harmer
1.424
963171AG1-166 GEN
Solar/Wind Harmer
1.152
971563AH1-280 GEN
Solar/Wind Harmer
1.152
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.208
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.873
3146926FARMVIL
Solar/Wind Harmer
-0.004
3130156CHOWAN
Solar/Wind Harmer
-0.006
3142543TWELFTH
Solar/Wind Helper
0.024
3142433PROV 92
Solar/Wind Helper
0.7
316458AB2-190 GEN2
Solar/Wind Helper
0.976
3143526WINTERP
Solar/Wind Helper
0.769
3142416OLDCHRC
Solar/Wind Helper
0.369
3142416OLDCHRC
Solar/Wind Helper
0.141
3143226MDLTHAN
Solar/Wind Helper
0.133
316365GEN2_N
Solar/Wind Harmer
1.302
966621AG1-532 GEN
Solar/Wind Harmer
0.347
970917AG2-570 GEN
Solar/Wind Harmer
40.235
3147043LAWRENC
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
1.233
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316478AD1-087 GEN
Solar/Wind Harmer
1.161
316486AD2-202 GEN
Solar/Wind Harmer
0.34
315724AD1-057 GEN
Solar/Wind Harmer
0.758
316327AA2-057 GEN
Solar/Wind Harmer
1.21
961601AG1-000A GEN
Solar/Wind Harmer
4.742
3146233WITAKRS
Solar/Wind Harmer
0.249
3146233WITAKRS
Solar/Wind Harmer
-0.008
3138543CONSLDL
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.244
3146073TAR RVR
Solar/Wind Harmer
-0.011
3146083TARBORO
Solar/Wind Harmer
-0.011
964241AG1-285 GEN
Solar/Wind Harmer
8.72
3146263WOODLND
Solar/Wind Harmer
-0.011
316248AF1-058 C
Solar/Wind Harmer
0.328
960061AF2-297 GEN
Solar/Wind Harmer
5.444
316317KELFORD C
Solar/Wind Harmer
0.511
3145823KELFORD
Solar/Wind Harmer
-0.011
315785AD2-033 C
Solar/Wind Harmer
2.392
970257AG2-171 GEN
Solar/Wind Harmer
3.873
316463AE2-346 GEN
Solar/Wind Harmer
0.166
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.281
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
959311AF2-222 GEN
Solar/Wind Harmer
10.609
3146173TUNIS
Solar/Wind Harmer
-0.01
957521AF2-046 GEN
Solar/Wind Harmer
7.902
961681AG1-008 GEN
Solar/Wind Harmer
7.902
316283AC2-100 C
Solar/Wind Harmer
0.942
3145893MURPHYS
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.233
3156021HOLLOMANSOL
Solar/Wind Harmer
1.319
971683AH1-343 GEN
Solar/Wind Harmer
4.208
3156081AA2-088 GEN
Solar/Wind Harmer
3.105
970909AG2-566 GEN
Solar/Wind Harmer
0.889
963181AG1-167 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.028
971193AH1-056 GEN
Solar/Wind Harmer
5.522
3146206CASHIE
Solar/Wind Harmer
-0.009
315737AD1-076 GEN
Solar/Wind Harmer
1.551
971157AH1-035 GEN
Solar/Wind Harmer
1.003
942461AE2-259 GEN
Solar/Wind Harmer
1.167
315614AA2-178 GEN
Solar/Wind Harmer
0.791
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146376EDENTON
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.966
3142946ENON
Solar/Wind Helper
0.055
316473AC1-191 GEN
Solar/Wind Helper
1
CPLELTFEXP_CPLE->PJM
CLTF
6.792
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.55
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.091
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.934
MECLTFEXP_MEC->PJM
CLTF
2.276
SIGELTFEXP_SIGE->PJM
CLTF
0.068
NYPJM->LTFIMP_NY
CLTF
0.817
LGEELTFEXP_LGEE->PJM
CLTF
0.818
WECLTFEXP_WEC->PJM
CLTF
0.427
LAGNLTFEXP_LAGN->PJM
CLTF
4.648
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.569
TVALTFEXP_TVA->PJM
CLTF
2.315

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.18 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1428.84
MW Contribution:0.47
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
10.894
970531AG2-338 GEN
50/50
4.358
3151361ROSEMG1
50/50
0.433
3151371ROSEMS1
50/50
0.268
3151381ROSEMG2
50/50
0.203
315242AE2-183_GT2
50/50
1.956
315241AE2-183_GT1
50/50
1.944
972185AH1-677 GEN
50/50
7.053
3151041BRUNSWICKG3
50/50
1.536
972187AH1-678 GEN
50/50
3.524
970535AG2-341 GEN
50/50
1.57
3152661PLYWOOD A
50/50
0.18
3144356SAPONY
Solar/Wind Harmer
1.857
316181AB2-040 GEN
Solar/Wind Harmer
0.181
3145796HORNRTN
Solar/Wind Harmer
0.361
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
970933AG2-581 GEN
Solar/Wind Harmer
8.936
3145593CAROLNA
Solar/Wind Harmer
0.109
3145593CAROLNA
Solar/Wind Harmer
0.109
966811AG1-552 GEN
Solar/Wind Harmer
1.182
3145593CAROLNA
Solar/Wind Harmer
0.136
3145783HORNRTN
Solar/Wind Harmer
1.911
3145783HORNRTN
Solar/Wind Harmer
1.529
3145783HORNRTN
Solar/Wind Harmer
0.478
3145783HORNRTN
Solar/Wind Harmer
0.191
316426AA2-053 GEN
Solar/Wind Harmer
0.356
316274AC1-208 GEN
Solar/Wind Harmer
0.518
970099AG2-077 GEN
Solar/Wind Harmer
10.582
961601AG1-000A GEN
Solar/Wind Harmer
1.691
316263AC1-034 GEN
Solar/Wind Harmer
3.592
3145493TOT1
Solar/Wind Harmer
0.212
3145453TOT5
Solar/Wind Harmer
0.127
3145603CNETO
Solar/Wind Harmer
0.085
939181AE1-148 GEN
Solar/Wind Harmer
4.3
3146173TUNIS
Solar/Wind Harmer
0.088
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3145933PARMELE
Solar/Wind Harmer
0.168
3145933PARMELE
Solar/Wind Harmer
0.084
962561AG1-105 GEN
Solar/Wind Harmer
3.947
964791AG1-342 GEN
Solar/Wind Harmer
1.566
3146843MT LREL
Solar/Wind Harmer
0.081
3146843MT LREL
Solar/Wind Harmer
0.081
316065AD1-022 GEN
Solar/Wind Harmer
3.64
970323AG2-213 GEN
Solar/Wind Harmer
3.221
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.303
971741AH1-377 GEN
Solar/Wind Harmer
7.057
3146376EDENTON
Solar/Wind Harmer
0.296
3146376EDENTON
Solar/Wind Harmer
0.296
958211AF2-115 GEN
Solar/Wind Harmer
0.797
963191AG1-168 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
3144293JTRSVLE
Adder
0.178
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
2.77
3147133PAMPLIN
Solar/Wind Harmer
0.063
3147133PAMPLIN
Solar/Wind Harmer
0.051
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.057
316240AF1-291 C
Solar/Wind Helper
0.411
966871AG1-558 GEN
Solar/Wind Helper
0.204
3142946ENON
Solar/Wind Helper
0.015
3143526WINTERP
Solar/Wind Helper
0.72
316468AD1-105 GEN
Solar/Wind Helper
0.653
316075AC2-137 C
Solar/Wind Helper
0.178
315779AE2-040
50/50
3.099
315244AE2-183_ST
50/50
3.382
963041AG1-153 GEN
50/50
3.109
3151281ROARAP4
50/50
0.132
3151281ROARAP4
50/50
0.123
3151541CLOVER2
50/50
2.008
3151611KERR 4
50/50
0.187
3151621KERR 5
50/50
0.187
3151631KERR 6
50/50
0.187
3151641KERR 7
50/50
0.187
316315AB2-025 C
Solar/Wind Harmer
0.179
315814AE2-033 C
Solar/Wind Harmer
17.298
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.694
941031AE2-094 GEN
Solar/Wind Harmer
22.572
944011AF1-069 GEN
Solar/Wind Harmer
7.375
3145796HORNRTN
Solar/Wind Harmer
0.385
3145796HORNRTN
Solar/Wind Harmer
0.048
970673AG2-436 GEN
Solar/Wind Harmer
25.561
970673AG2-436 GEN
Solar/Wind Harmer
17.041
971967AH1-528 GEN
Solar/Wind Harmer
18.68
3137643SOCKMAN
Solar/Wind Harmer
0.464
970085AG2-068 GEN
Solar/Wind Harmer
5.942
970581AG2-369 GEN
Solar/Wind Harmer
5.11
315607AA1-063A GEN
Solar/Wind Harmer
0.204
3146043SEABORD
Solar/Wind Harmer
0.098
970831AG2-522 GEN
Solar/Wind Harmer
4.182
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.379
3145573BETHELC
Solar/Wind Harmer
0.092
3145573BETHELC
Solar/Wind Harmer
0.092
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.09
3145683EARLEYS
Solar/Wind Harmer
0.09
3145513AHOSKIE
Solar/Wind Harmer
0.186
3145513AHOSKIE
Solar/Wind Harmer
0.089
957861AF2-080 GEN
Solar/Wind Harmer
3.828
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
965291AG1-394 GEN
Solar/Wind Harmer
0.382
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.092
3145746EVERETS
Solar/Wind Harmer
0.34
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
970181AG2-120 GEN
Solar/Wind Harmer
1.064
3146206CASHIE
Solar/Wind Harmer
0.08
970601AG2-382 GEN
Solar/Wind Harmer
3.008
316118AC1-105 GEN
Solar/Wind Harmer
0.206
3147173SINAI
Solar/Wind Harmer
0.078
3147243WELCO
Solar/Wind Harmer
0.049
315732AD1-074 GEN1
Solar/Wind Harmer
0.439
315733AD1-074 GEN2
Solar/Wind Harmer
0.439
315735AD1-075 GEN1
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
1.275
3130546PLYMOUTH
Solar/Wind Harmer
0.076
3144303KENBRDG
Solar/Wind Harmer
0.06
3143316POE
Solar/Wind Harmer
0.287
315816AE2-034 GEN
Solar/Wind Harmer
0.308
970683AG2-441 GEN
Solar/Wind Harmer
4.722
970681AG2-440 GEN
Solar/Wind Harmer
3.778
3130156CHOWAN
Solar/Wind Harmer
0.066
3130156CHOWAN
Solar/Wind Harmer
0.066
946301AF1-294 GEN
Solar/Wind Harmer
1.311
961791AG1-021 GEN
Solar/Wind Harmer
0.638
970865AG2-541 GEN
Solar/Wind Harmer
2.298
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315657AE1-056 GEN
Solar/Wind Harmer
2.185
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.473
970163AG2-111 GEN
Solar/Wind Harmer
0.451
3145176PASQUOTANK
Solar/Wind Harmer
0.036
316321Z2-027
Solar/Wind Harmer
0.011
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3146486SUNBURY
Solar/Wind Harmer
0.057
3146486SUNBURY
Solar/Wind Harmer
0.057
316132AB2-190 GEN1
Solar/Wind Helper
0.895
316233AE1-074 FULL
Solar/Wind Helper
0.212
316312AB1-027
Solar/Wind Helper
0.237
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3147043LAWRENC
50/50
1.178
315243AE2-183_GT3
50/50
1.956
3151051BRUNSWICKS1
50/50
3.187
3151021BRUNSWICKG1
50/50
1.536
971451AH1-221 GEN
50/50
4.664
3151261ROARAP2
50/50
0.136
3151531CLOVER1
50/50
2.018
3151601KERR 3
50/50
0.187
3151581KERR 1
50/50
0.067
316023GEN1_S
Solar/Wind Harmer
0.354
960081AF2-299 GEN
Solar/Wind Harmer
1.332
971795AH1-408 GEN
Solar/Wind Harmer
8.516
316011AB1-132 GEN
Solar/Wind Harmer
2.263
962571AG1-106 GEN
Solar/Wind Harmer
1.771
3145796HORNRTN
Solar/Wind Harmer
0.397
3145796HORNRTN
Solar/Wind Harmer
0.12
940641AE2-051 GEN
Solar/Wind Harmer
9.263
970919AG2-571 GEN
Solar/Wind Harmer
3.98
970087AG2-069 GEN
Solar/Wind Harmer
8.913
3145783HORNRTN
Solar/Wind Harmer
0.107
315722AD1-056 GEN
Solar/Wind Harmer
0.674
316190AA2-174 GEN
Solar/Wind Harmer
0
939411AE1-173 GEN
Solar/Wind Harmer
42.901
957481AF2-042 GEN
Solar/Wind Harmer
26.456
316212AC1-099_GEN
Solar/Wind Harmer
0.502
316129AC1-054 GEN
Solar/Wind Harmer
0.364
971065AG2-659 GEN
Solar/Wind Harmer
4.087
3146233WITAKRS
Solar/Wind Harmer
0.38
3146263WOODLND
Solar/Wind Harmer
0.095
316359AB2-059 GEN
Solar/Wind Harmer
0.34
316049AB1-081 GEN
Solar/Wind Harmer
0.541
3142053HEARTS
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.075
3145823KELFORD
Solar/Wind Harmer
0.092
315693AD1-088 GEN
Solar/Wind Harmer
4.418
961671AG1-007 GEN
Solar/Wind Harmer
0.014
3146083TARBORO
Solar/Wind Harmer
0.092
3145493TOT1
Solar/Wind Harmer
0.407
962491AG1-098 GEN
Solar/Wind Harmer
5.172
3145683EARLEYS
Solar/Wind Harmer
0.09
316494AC1-189 GEN
Solar/Wind Harmer
0.3
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.348
3145893MURPHYS
Solar/Wind Harmer
0.387
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3146293MARTNCO
Solar/Wind Harmer
0.078
970401AG2-262 GEN
Solar/Wind Harmer
0.478
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.08
971547AH1-271 GEN
Solar/Wind Harmer
1.719
3145963POPLR C
Solar/Wind Harmer
0.08
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3145663CRESWEL
Solar/Wind Harmer
0.201
971163AH1-040 GEN
Solar/Wind Harmer
5.738
970685AG2-442 GEN
Solar/Wind Harmer
5.289
3130156CHOWAN
Solar/Wind Harmer
0.066
963171AG1-166 GEN
Solar/Wind Harmer
0.354
971563AH1-280 GEN
Solar/Wind Harmer
0.708
3144293JTRSVLE
Adder
0.211
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.066
3146516WINFALL
Solar/Wind Harmer
0.194
3146516WINFALL
Solar/Wind Harmer
0.06
944591AF1-124 GEN
Solar/Wind Harmer
12.705
3142543TWELFTH
Solar/Wind Helper
0.024
316458AB2-190 GEN2
Solar/Wind Helper
0.895
3142433PROV 92
Solar/Wind Helper
0.616
3143526WINTERP
Solar/Wind Helper
0.72
3143226MDLTHAN
Solar/Wind Helper
0.125
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3151031BRUNSWICKG2
50/50
1.536
3151261ROARAP2
50/50
0.133
970413AG2-270 GEN
50/50
8.806
3151591KERR 2
50/50
0.187
316365GEN2_N
Solar/Wind Harmer
0.354
313506AB2-031 GEN
Solar/Wind Harmer
0.385
3147043LAWRENC
Solar/Wind Harmer
0.074
3145796HORNRTN
Solar/Wind Harmer
0.481
3145796HORNRTN
Solar/Wind Harmer
0.12
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970917AG2-570 GEN
Solar/Wind Harmer
9.95
315724AD1-057 GEN
Solar/Wind Harmer
0.4
316210AC1-098 GEN
Solar/Wind Harmer
0.901
316327AA2-057 GEN
Solar/Wind Harmer
0.146
3146233WITAKRS
Solar/Wind Harmer
0.48
3146233WITAKRS
Solar/Wind Harmer
0.065
3138543CONSLDL
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
6.766
3146263WOODLND
Solar/Wind Harmer
0.095
971623AH1-311 GEN
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.094
316478AD1-087 GEN
Solar/Wind Harmer
0.329
316486AD2-202 GEN
Solar/Wind Harmer
0.097
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.092
3146073TAR RVR
Solar/Wind Harmer
0.092
3146083TARBORO
Solar/Wind Harmer
0.092
316463AE2-346 GEN
Solar/Wind Harmer
0.076
316140AB2-099
Solar/Wind Harmer
0.032
962331AG1-082 GEN
Solar/Wind Harmer
0.95
3146173TUNIS
Solar/Wind Harmer
0.088
957521AF2-046 GEN
Solar/Wind Harmer
6.513
961681AG1-008 GEN
Solar/Wind Harmer
6.513
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
3156021HOLLOMANSOL
Solar/Wind Harmer
0.393
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
316131AB2-060 GEN
Solar/Wind Harmer
0.268
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.084
966801AG1-551 GEN
Solar/Wind Harmer
0.976
964241AG1-285 GEN
Solar/Wind Harmer
5.485
3146206CASHIE
Solar/Wind Harmer
0.08
3145963POPLR C
Solar/Wind Harmer
0.08
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.344
315785AD2-033 C
Solar/Wind Harmer
0.629
315737AD1-076 GEN
Solar/Wind Harmer
0.983
971157AH1-035 GEN
Solar/Wind Harmer
0.908
970257AG2-171 GEN
Solar/Wind Harmer
2.416
959311AF2-222 GEN
Solar/Wind Harmer
6.592
316283AC2-100 C
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.41
971683AH1-343 GEN
Solar/Wind Harmer
2.584
3146376EDENTON
Solar/Wind Harmer
0.067
963181AG1-167 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
970909AG2-566 GEN
Solar/Wind Harmer
0.692
3147133PAMPLIN
Solar/Wind Harmer
0.199
971193AH1-056 GEN
Solar/Wind Harmer
3.857
315773AC2-141 GEN
Solar/Wind Harmer
2.248
3146626S HERTFORD
Solar/Wind Harmer
0.061
3145273HOLLAND
Solar/Wind Harmer
0.046
3146516WINFALL
Solar/Wind Harmer
0.06
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
12.66
944601AF1-125 GEN
Solar/Wind Harmer
12.465
315839AE2-212 C
Solar/Wind Helper
0.986
316473AC1-191 GEN
Solar/Wind Helper
0.925
3142946ENON
Solar/Wind Helper
0.049
CPLELTFEXP_CPLE->PJM
CLTF
5.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.951
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.461
MECLTFEXP_MEC->PJM
CLTF
1.839
SIGELTFEXP_SIGE->PJM
CLTF
0.055
NYPJM->LTFIMP_NY
CLTF
0.691
LGEELTFEXP_LGEE->PJM
CLTF
0.659
WECLTFEXP_WEC->PJM
CLTF
0.343
LAGNLTFEXP_LAGN->PJM
CLTF
3.79
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.991
TVALTFEXP_TVA->PJM
CLTF
1.888

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.72 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:958.85
MW Contribution:0.46
Bus #Bus NameTypeMW Contribution
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
970937AG2-583 GEN
Solar/Wind Harmer
28.699
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.32 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:955.6
MW Contribution:0.46
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970933AG2-581 GEN
Solar/Wind Harmer
8.922
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
971967AH1-528 GEN
Solar/Wind Harmer
17.843
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
970937AG2-583 GEN
Solar/Wind Harmer
28.699
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.97 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1841.8
MW Contribution:0.77
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
2.516
3151051BRUNSWICKS1
50/50
4.094
3151021BRUNSWICKG1
50/50
1.972
971451AH1-221 GEN
50/50
5.991
3147043LAWRENC
50/50
1.32
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
3151531CLOVER1
50/50
2.556
3151261ROARAP2
50/50
0.148
316023GEN1_S
Solar/Wind Harmer
1.302
960081AF2-299 GEN
Solar/Wind Harmer
1.926
970919AG2-571 GEN
Solar/Wind Harmer
5.093
970087AG2-069 GEN
Solar/Wind Harmer
15.012
971795AH1-408 GEN
Solar/Wind Harmer
11.982
316011AB1-132 GEN
Solar/Wind Harmer
3.171
962571AG1-106 GEN
Solar/Wind Harmer
2.179
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145796HORNRTN
Solar/Wind Harmer
-0.015
957481AF2-042 GEN
Solar/Wind Harmer
44.356
315722AD1-056 GEN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
-0.013
315693AD1-088 GEN
Solar/Wind Harmer
6.574
939411AE1-173 GEN
Solar/Wind Harmer
65.115
962491AG1-098 GEN
Solar/Wind Harmer
8.662
316190AA2-174 GEN
Solar/Wind Harmer
0.157
316129AC1-054 GEN
Solar/Wind Harmer
1.1
315687AD1-152 GEN
Solar/Wind Harmer
1.509
971065AG2-659 GEN
Solar/Wind Harmer
6.236
3146233WITAKRS
Solar/Wind Harmer
-0.047
316359AB2-059 GEN
Solar/Wind Harmer
1.597
316049AB1-081 GEN
Solar/Wind Harmer
1.278
3142053HEARTS
Solar/Wind Harmer
0.139
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.028
316237AB2-079_GEN
Solar/Wind Harmer
0.35
961671AG1-007 GEN
Solar/Wind Harmer
0.143
3146083TARBORO
Solar/Wind Harmer
-0.011
3145493TOT1
Solar/Wind Harmer
0.335
970401AG2-262 GEN
Solar/Wind Harmer
0.731
3146263WOODLND
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.011
316494AC1-189 GEN
Solar/Wind Harmer
1.164
3145683EARLEYS
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
1.004
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
0.296
3146293MARTNCO
Solar/Wind Harmer
0.061
970685AG2-442 GEN
Solar/Wind Harmer
8.535
316174AB2-169 GEN
Solar/Wind Harmer
1.424
963171AG1-166 GEN
Solar/Wind Harmer
1.152
3151031BRUNSWICKG2
50/50
1.972
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
970413AG2-270 GEN
50/50
11.155
3151261ROARAP2
50/50
0.144
316365GEN2_N
Solar/Wind Harmer
1.302
966621AG1-532 GEN
Solar/Wind Harmer
0.347
970917AG2-570 GEN
Solar/Wind Harmer
40.235
3147043LAWRENC
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
1.233
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316478AD1-087 GEN
Solar/Wind Harmer
1.161
316486AD2-202 GEN
Solar/Wind Harmer
0.34
315724AD1-057 GEN
Solar/Wind Harmer
0.758
316327AA2-057 GEN
Solar/Wind Harmer
1.21
961601AG1-000A GEN
Solar/Wind Harmer
4.742
3146233WITAKRS
Solar/Wind Harmer
0.249
3146233WITAKRS
Solar/Wind Harmer
-0.008
3138543CONSLDL
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.244
3146073TAR RVR
Solar/Wind Harmer
-0.011
3146083TARBORO
Solar/Wind Harmer
-0.011
964241AG1-285 GEN
Solar/Wind Harmer
8.72
3146263WOODLND
Solar/Wind Harmer
-0.011
316248AF1-058 C
Solar/Wind Harmer
0.328
960061AF2-297 GEN
Solar/Wind Harmer
5.444
316317KELFORD C
Solar/Wind Harmer
0.511
3145823KELFORD
Solar/Wind Harmer
-0.011
315785AD2-033 C
Solar/Wind Harmer
2.392
970257AG2-171 GEN
Solar/Wind Harmer
3.873
316463AE2-346 GEN
Solar/Wind Harmer
0.166
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.281
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
959311AF2-222 GEN
Solar/Wind Harmer
10.609
3146173TUNIS
Solar/Wind Harmer
-0.01
957521AF2-046 GEN
Solar/Wind Harmer
7.902
961681AG1-008 GEN
Solar/Wind Harmer
7.902
316283AC2-100 C
Solar/Wind Harmer
0.942
3145893MURPHYS
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.233
3156021HOLLOMANSOL
Solar/Wind Harmer
1.319
971683AH1-343 GEN
Solar/Wind Harmer
4.208
3156081AA2-088 GEN
Solar/Wind Harmer
3.105
970909AG2-566 GEN
Solar/Wind Harmer
0.889
963181AG1-167 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.028
971193AH1-056 GEN
Solar/Wind Harmer
5.522
3146206CASHIE
Solar/Wind Harmer
-0.009
315737AD1-076 GEN
Solar/Wind Harmer
1.551
971157AH1-035 GEN
Solar/Wind Harmer
1.003
942461AE2-259 GEN
Solar/Wind Harmer
1.167
315614AA2-178 GEN
Solar/Wind Harmer
0.791
3146926FARMVIL
Solar/Wind Harmer
-0.004
315779AE2-040
50/50
3.378
315244AE2-183_ST
50/50
4.349
963041AG1-153 GEN
50/50
3.994
3151541CLOVER2
50/50
2.544
3151281ROARAP4
50/50
0.144
3151281ROARAP4
50/50
0.134
316315AB2-025 C
Solar/Wind Harmer
0.734
315814AE2-033 C
Solar/Wind Harmer
24.939
941031AE2-094 GEN
Solar/Wind Harmer
33.281
944011AF1-069 GEN
Solar/Wind Harmer
10.428
970673AG2-436 GEN
Solar/Wind Harmer
36.399
970673AG2-436 GEN
Solar/Wind Harmer
18.43
946281AF1-292 GEN
Solar/Wind Harmer
0.383
971967AH1-528 GEN
Solar/Wind Harmer
31.705
970085AG2-068 GEN
Solar/Wind Harmer
10.008
970581AG2-369 GEN
Solar/Wind Harmer
8.607
316087AB2-174 GEN
Solar/Wind Harmer
2.265
315652AC1-086 GEN
Solar/Wind Harmer
17.05
3145796HORNRTN
Solar/Wind Harmer
-0.047
3145796HORNRTN
Solar/Wind Harmer
-0.006
3137643SOCKMAN
Solar/Wind Harmer
-0.057
970831AG2-522 GEN
Solar/Wind Harmer
6.31
315607AA1-063A GEN
Solar/Wind Harmer
1.207
316319Z2-044 C
Solar/Wind Harmer
0.657
3146043SEABORD
Solar/Wind Harmer
-0.012
3146376EDENTON
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.966
3142946ENON
Solar/Wind Helper
0.055
316473AC1-191 GEN
Solar/Wind Helper
1
971563AH1-280 GEN
Solar/Wind Harmer
1.152
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.208
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.873
3146926FARMVIL
Solar/Wind Harmer
-0.004
3130156CHOWAN
Solar/Wind Harmer
-0.006
970533AG2-339 GEN
50/50
14.043
970531AG2-338 GEN
50/50
5.617
315242AE2-183_GT2
50/50
2.516
315241AE2-183_GT1
50/50
2.5
972185AH1-677 GEN
50/50
9.069
3151041BRUNSWICKG3
50/50
1.972
972187AH1-678 GEN
50/50
4.526
3151361ROSEMG1
50/50
0.471
3151371ROSEMS1
50/50
0.292
3151381ROSEMG2
50/50
0.22
3144356SAPONY
Solar/Wind Harmer
0.948
970933AG2-581 GEN
Solar/Wind Harmer
15.092
316181AB2-040 GEN
Solar/Wind Harmer
2.139
3145796HORNRTN
Solar/Wind Harmer
-0.044
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
970099AG2-077 GEN
Solar/Wind Harmer
17.742
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.013
966811AG1-552 GEN
Solar/Wind Harmer
1.5
3145593CAROLNA
Solar/Wind Harmer
0.111
3145783HORNRTN
Solar/Wind Harmer
1.561
3145783HORNRTN
Solar/Wind Harmer
1.249
3145783HORNRTN
Solar/Wind Harmer
0.39
3145783HORNRTN
Solar/Wind Harmer
0.156
316426AA2-053 GEN
Solar/Wind Harmer
1.293
316274AC1-208 GEN
Solar/Wind Harmer
1.319
939181AE1-148 GEN
Solar/Wind Harmer
6.767
961601AG1-000A GEN
Solar/Wind Harmer
4.682
316263AC1-034 GEN
Solar/Wind Harmer
5.552
313527AB2-043 GEN
Solar/Wind Harmer
1.888
3145493TOT1
Solar/Wind Harmer
0.175
3145453TOT5
Solar/Wind Harmer
0.105
3145603CNETO
Solar/Wind Harmer
0.07
962561AG1-105 GEN
Solar/Wind Harmer
6.333
964791AG1-342 GEN
Solar/Wind Harmer
2.391
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970323AG2-213 GEN
Solar/Wind Harmer
5.164
971775AH1-396 GEN
Solar/Wind Harmer
0.735
316034AC1-036 C
Solar/Wind Harmer
0.191
971741AH1-377 GEN
Solar/Wind Harmer
11.893
3146173TUNIS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
316222AC1-221 GEN
Solar/Wind Harmer
1.018
3145893MURPHYS
Solar/Wind Harmer
0.278
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
4.681
958211AF2-115 GEN
Solar/Wind Harmer
1.439
963191AG1-168 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3144293JTRSVLE
Adder
0.22
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.007
316065AD1-022 GEN
Solar/Wind Harmer
4.293
942751AE2-291 GEN
Solar/Wind Harmer
4.718
315742AE1-103 GEN
Solar/Wind Harmer
0.706
3146376EDENTON
Solar/Wind Harmer
0.191
3146376EDENTON
Solar/Wind Harmer
0.191
316240AF1-291 C
Solar/Wind Helper
0.402
3142946ENON
Solar/Wind Helper
0.017
966871AG1-558 GEN
Solar/Wind Helper
0.221
3143526WINTERP
Solar/Wind Helper
0.769
316468AD1-105 GEN
Solar/Wind Helper
0.714
316075AC2-137 C
Solar/Wind Helper
0.21
316033AB2-134 GEN
Solar/Wind Helper
0.43
316239AB2-077_GEN
Solar/Wind Harmer
0.35
316238AB2-078_GEN
Solar/Wind Harmer
0.35
3146033SCOT NK
Solar/Wind Harmer
-0.045
3145573BETHELC
Solar/Wind Harmer
-0.011
3145573BETHELC
Solar/Wind Harmer
-0.011
316420AA1-050 GEN
Solar/Wind Harmer
1.267
316118AC1-105 GEN
Solar/Wind Harmer
0.759
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
4.731
971443AH1-215 GEN
Solar/Wind Harmer
2.043
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
3144303KENBRDG
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.089
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316005AA1-067
Solar/Wind Harmer
0.207
3145746EVERETS
Solar/Wind Harmer
-0.041
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
970181AG2-120 GEN
Solar/Wind Harmer
1.344
316318V4-068
Solar/Wind Harmer
0.249
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.01
965291AG1-394 GEN
Solar/Wind Harmer
0.871
970683AG2-441 GEN
Solar/Wind Harmer
7.621
970681AG2-440 GEN
Solar/Wind Harmer
6.097
3143316POE
Solar/Wind Harmer
-0.038
970865AG2-541 GEN
Solar/Wind Harmer
3.743
946301AF1-294 GEN
Solar/Wind Harmer
2.361
961791AG1-021 GEN
Solar/Wind Harmer
1.152
315657AE1-056 GEN
Solar/Wind Harmer
3.313
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.864
270455AD2-022 GEN
Solar/Wind Harmer
1.529
270457AD2-023 GEN
Solar/Wind Harmer
0.775
315732AD1-074 GEN1
Solar/Wind Harmer
1.65
315733AD1-074 GEN2
Solar/Wind Harmer
1.65
315735AD1-075 GEN1
Solar/Wind Harmer
0.825
316123AC1-075 GEN
Solar/Wind Harmer
0.874
970165AG2-112 GEN
Solar/Wind Harmer
0.77
970163AG2-111 GEN
Solar/Wind Harmer
0.734
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.593
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
316132AB2-190 GEN1
Solar/Wind Helper
0.976
316233AE1-074 FULL
Solar/Wind Helper
0.226
316312AB1-027
Solar/Wind Helper
0.27
3143873LANEXA
Solar/Wind Helper
0.076
3142543TWELFTH
Solar/Wind Helper
0.024
3142433PROV 92
Solar/Wind Helper
0.7
316458AB2-190 GEN2
Solar/Wind Helper
0.976
3143526WINTERP
Solar/Wind Helper
0.769
3142416OLDCHRC
Solar/Wind Helper
0.369
3142416OLDCHRC
Solar/Wind Helper
0.141
3143226MDLTHAN
Solar/Wind Helper
0.133
316369SG1_INVT
Solar/Wind Helper
0.602
315697AD1-025 GEN
Solar/Wind Helper
1.43
CPLELTFEXP_CPLE->PJM
CLTF
6.792
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.55
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.091
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.934
MECLTFEXP_MEC->PJM
CLTF
2.276
SIGELTFEXP_SIGE->PJM
CLTF
0.068
NYPJM->LTFIMP_NY
CLTF
0.817
LGEELTFEXP_LGEE->PJM
CLTF
0.818
WECLTFEXP_WEC->PJM
CLTF
0.427
LAGNLTFEXP_LAGN->PJM
CLTF
4.648
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.569
TVALTFEXP_TVA->PJM
CLTF
2.315

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.99 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1407.24
MW Contribution:0.47
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3151031BRUNSWICKG2
50/50
1.536
3151261ROARAP2
50/50
0.133
970533AG2-339 GEN
50/50
10.894
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3147043LAWRENC
50/50
1.178
315243AE2-183_GT3
50/50
1.956
3151051BRUNSWICKS1
50/50
3.187
3151021BRUNSWICKG1
50/50
1.536
971451AH1-221 GEN
50/50
4.664
3151261ROARAP2
50/50
0.136
3151531CLOVER1
50/50
2.018
3151601KERR 3
50/50
0.187
3151581KERR 1
50/50
0.067
316023GEN1_S
Solar/Wind Harmer
0.354
960081AF2-299 GEN
Solar/Wind Harmer
1.332
971795AH1-408 GEN
Solar/Wind Harmer
8.516
316011AB1-132 GEN
Solar/Wind Harmer
2.263
962571AG1-106 GEN
Solar/Wind Harmer
1.771
3145796HORNRTN
Solar/Wind Harmer
0.397
3145796HORNRTN
Solar/Wind Harmer
0.12
940641AE2-051 GEN
Solar/Wind Harmer
9.263
970919AG2-571 GEN
Solar/Wind Harmer
3.98
970087AG2-069 GEN
Solar/Wind Harmer
8.913
3145783HORNRTN
Solar/Wind Harmer
0.107
315722AD1-056 GEN
Solar/Wind Harmer
0.674
316190AA2-174 GEN
Solar/Wind Harmer
0
939411AE1-173 GEN
Solar/Wind Harmer
42.901
957481AF2-042 GEN
Solar/Wind Harmer
26.456
316212AC1-099_GEN
Solar/Wind Harmer
0.502
316129AC1-054 GEN
Solar/Wind Harmer
0.364
971065AG2-659 GEN
Solar/Wind Harmer
4.087
3146233WITAKRS
Solar/Wind Harmer
0.38
3146263WOODLND
Solar/Wind Harmer
0.095
316359AB2-059 GEN
Solar/Wind Harmer
0.34
316049AB1-081 GEN
Solar/Wind Harmer
0.541
3142053HEARTS
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.075
3145823KELFORD
Solar/Wind Harmer
0.092
315779AE2-040
50/50
3.099
315244AE2-183_ST
50/50
3.382
963041AG1-153 GEN
50/50
3.109
3151281ROARAP4
50/50
0.132
3151281ROARAP4
50/50
0.123
3151541CLOVER2
50/50
2.008
3151611KERR 4
50/50
0.187
3151621KERR 5
50/50
0.187
3151631KERR 6
50/50
0.187
3151641KERR 7
50/50
0.187
316315AB2-025 C
Solar/Wind Harmer
0.179
315814AE2-033 C
Solar/Wind Harmer
17.298
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.694
941031AE2-094 GEN
Solar/Wind Harmer
22.572
944011AF1-069 GEN
Solar/Wind Harmer
7.375
3145796HORNRTN
Solar/Wind Harmer
0.385
3145796HORNRTN
Solar/Wind Harmer
0.048
970673AG2-436 GEN
Solar/Wind Harmer
25.561
970673AG2-436 GEN
Solar/Wind Harmer
17.041
971967AH1-528 GEN
Solar/Wind Harmer
18.68
3137643SOCKMAN
Solar/Wind Harmer
0.464
970085AG2-068 GEN
Solar/Wind Harmer
5.942
970581AG2-369 GEN
Solar/Wind Harmer
5.11
315607AA1-063A GEN
Solar/Wind Harmer
0.204
3146043SEABORD
Solar/Wind Harmer
0.098
970831AG2-522 GEN
Solar/Wind Harmer
4.182
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.379
3145573BETHELC
Solar/Wind Harmer
0.092
3145573BETHELC
Solar/Wind Harmer
0.092
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.09
3145683EARLEYS
Solar/Wind Harmer
0.09
3145513AHOSKIE
Solar/Wind Harmer
0.186
3145513AHOSKIE
Solar/Wind Harmer
0.089
315693AD1-088 GEN
Solar/Wind Harmer
4.418
961671AG1-007 GEN
Solar/Wind Harmer
0.014
3146083TARBORO
Solar/Wind Harmer
0.092
3145493TOT1
Solar/Wind Harmer
0.407
962491AG1-098 GEN
Solar/Wind Harmer
5.172
3145683EARLEYS
Solar/Wind Harmer
0.09
316494AC1-189 GEN
Solar/Wind Harmer
0.3
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.348
3145893MURPHYS
Solar/Wind Harmer
0.387
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3146293MARTNCO
Solar/Wind Harmer
0.078
970401AG2-262 GEN
Solar/Wind Harmer
0.478
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.08
971547AH1-271 GEN
Solar/Wind Harmer
1.719
3145963POPLR C
Solar/Wind Harmer
0.08
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3145663CRESWEL
Solar/Wind Harmer
0.201
971163AH1-040 GEN
Solar/Wind Harmer
5.738
970685AG2-442 GEN
Solar/Wind Harmer
5.289
3130156CHOWAN
Solar/Wind Harmer
0.066
963171AG1-166 GEN
Solar/Wind Harmer
0.354
971563AH1-280 GEN
Solar/Wind Harmer
0.708
3144293JTRSVLE
Adder
0.211
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.066
957861AF2-080 GEN
Solar/Wind Harmer
3.828
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
965291AG1-394 GEN
Solar/Wind Harmer
0.382
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.092
3145746EVERETS
Solar/Wind Harmer
0.34
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
970181AG2-120 GEN
Solar/Wind Harmer
1.064
3146206CASHIE
Solar/Wind Harmer
0.08
970601AG2-382 GEN
Solar/Wind Harmer
3.008
316118AC1-105 GEN
Solar/Wind Harmer
0.206
3147173SINAI
Solar/Wind Harmer
0.078
3147243WELCO
Solar/Wind Harmer
0.049
315732AD1-074 GEN1
Solar/Wind Harmer
0.439
315733AD1-074 GEN2
Solar/Wind Harmer
0.439
315735AD1-075 GEN1
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
1.275
3130546PLYMOUTH
Solar/Wind Harmer
0.076
3144303KENBRDG
Solar/Wind Harmer
0.06
3143316POE
Solar/Wind Harmer
0.287
315816AE2-034 GEN
Solar/Wind Harmer
0.308
970683AG2-441 GEN
Solar/Wind Harmer
4.722
970681AG2-440 GEN
Solar/Wind Harmer
3.778
3130156CHOWAN
Solar/Wind Harmer
0.066
3130156CHOWAN
Solar/Wind Harmer
0.066
946301AF1-294 GEN
Solar/Wind Harmer
1.311
961791AG1-021 GEN
Solar/Wind Harmer
0.638
970865AG2-541 GEN
Solar/Wind Harmer
2.298
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315657AE1-056 GEN
Solar/Wind Harmer
2.185
970413AG2-270 GEN
50/50
8.806
3151591KERR 2
50/50
0.187
316365GEN2_N
Solar/Wind Harmer
0.354
313506AB2-031 GEN
Solar/Wind Harmer
0.385
3147043LAWRENC
Solar/Wind Harmer
0.074
3145796HORNRTN
Solar/Wind Harmer
0.481
3145796HORNRTN
Solar/Wind Harmer
0.12
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970917AG2-570 GEN
Solar/Wind Harmer
9.95
315724AD1-057 GEN
Solar/Wind Harmer
0.4
316210AC1-098 GEN
Solar/Wind Harmer
0.901
316327AA2-057 GEN
Solar/Wind Harmer
0.146
3146233WITAKRS
Solar/Wind Harmer
0.48
3146233WITAKRS
Solar/Wind Harmer
0.065
3138543CONSLDL
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
6.766
3146263WOODLND
Solar/Wind Harmer
0.095
971623AH1-311 GEN
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.094
316478AD1-087 GEN
Solar/Wind Harmer
0.329
316486AD2-202 GEN
Solar/Wind Harmer
0.097
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.092
3146073TAR RVR
Solar/Wind Harmer
0.092
3146083TARBORO
Solar/Wind Harmer
0.092
316463AE2-346 GEN
Solar/Wind Harmer
0.076
316140AB2-099
Solar/Wind Harmer
0.032
962331AG1-082 GEN
Solar/Wind Harmer
0.95
3146173TUNIS
Solar/Wind Harmer
0.088
957521AF2-046 GEN
Solar/Wind Harmer
6.513
961681AG1-008 GEN
Solar/Wind Harmer
6.513
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
3156021HOLLOMANSOL
Solar/Wind Harmer
0.393
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
316131AB2-060 GEN
Solar/Wind Harmer
0.268
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.084
966801AG1-551 GEN
Solar/Wind Harmer
0.976
964241AG1-285 GEN
Solar/Wind Harmer
5.485
3146206CASHIE
Solar/Wind Harmer
0.08
3145963POPLR C
Solar/Wind Harmer
0.08
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.344
315785AD2-033 C
Solar/Wind Harmer
0.629
315737AD1-076 GEN
Solar/Wind Harmer
0.983
971157AH1-035 GEN
Solar/Wind Harmer
0.908
970257AG2-171 GEN
Solar/Wind Harmer
2.416
959311AF2-222 GEN
Solar/Wind Harmer
6.592
316283AC2-100 C
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.41
971683AH1-343 GEN
Solar/Wind Harmer
2.584
3146376EDENTON
Solar/Wind Harmer
0.067
963181AG1-167 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
970909AG2-566 GEN
Solar/Wind Harmer
0.692
3147133PAMPLIN
Solar/Wind Harmer
0.199
971193AH1-056 GEN
Solar/Wind Harmer
3.857
315773AC2-141 GEN
Solar/Wind Harmer
2.248
3146626S HERTFORD
Solar/Wind Harmer
0.061
3145273HOLLAND
Solar/Wind Harmer
0.046
970531AG2-338 GEN
50/50
4.358
3151361ROSEMG1
50/50
0.433
3151371ROSEMS1
50/50
0.268
3151381ROSEMG2
50/50
0.203
315242AE2-183_GT2
50/50
1.956
315241AE2-183_GT1
50/50
1.944
972185AH1-677 GEN
50/50
7.053
3151041BRUNSWICKG3
50/50
1.536
972187AH1-678 GEN
50/50
3.524
970535AG2-341 GEN
50/50
1.57
3152661PLYWOOD A
50/50
0.18
3144356SAPONY
Solar/Wind Harmer
1.857
316181AB2-040 GEN
Solar/Wind Harmer
0.181
3145796HORNRTN
Solar/Wind Harmer
0.361
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
970933AG2-581 GEN
Solar/Wind Harmer
8.936
3145593CAROLNA
Solar/Wind Harmer
0.109
3145593CAROLNA
Solar/Wind Harmer
0.109
966811AG1-552 GEN
Solar/Wind Harmer
1.182
3145593CAROLNA
Solar/Wind Harmer
0.136
3145783HORNRTN
Solar/Wind Harmer
1.911
3145783HORNRTN
Solar/Wind Harmer
1.529
3145783HORNRTN
Solar/Wind Harmer
0.478
3145783HORNRTN
Solar/Wind Harmer
0.191
316426AA2-053 GEN
Solar/Wind Harmer
0.356
316274AC1-208 GEN
Solar/Wind Harmer
0.518
970099AG2-077 GEN
Solar/Wind Harmer
10.582
961601AG1-000A GEN
Solar/Wind Harmer
1.691
316263AC1-034 GEN
Solar/Wind Harmer
3.592
3145493TOT1
Solar/Wind Harmer
0.212
3145453TOT5
Solar/Wind Harmer
0.127
3145603CNETO
Solar/Wind Harmer
0.085
939181AE1-148 GEN
Solar/Wind Harmer
4.3
3146173TUNIS
Solar/Wind Harmer
0.088
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3145933PARMELE
Solar/Wind Harmer
0.168
3145933PARMELE
Solar/Wind Harmer
0.084
962561AG1-105 GEN
Solar/Wind Harmer
3.947
964791AG1-342 GEN
Solar/Wind Harmer
1.566
3146843MT LREL
Solar/Wind Harmer
0.081
3146843MT LREL
Solar/Wind Harmer
0.081
316065AD1-022 GEN
Solar/Wind Harmer
3.64
970323AG2-213 GEN
Solar/Wind Harmer
3.221
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.303
971741AH1-377 GEN
Solar/Wind Harmer
7.057
3146376EDENTON
Solar/Wind Harmer
0.296
3146376EDENTON
Solar/Wind Harmer
0.296
958211AF2-115 GEN
Solar/Wind Harmer
0.797
963191AG1-168 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
3144293JTRSVLE
Adder
0.178
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
2.77
3147133PAMPLIN
Solar/Wind Harmer
0.063
3147133PAMPLIN
Solar/Wind Harmer
0.051
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.061
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.473
970163AG2-111 GEN
Solar/Wind Harmer
0.451
3145176PASQUOTANK
Solar/Wind Harmer
0.036
316321Z2-027
Solar/Wind Harmer
0.011
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3146486SUNBURY
Solar/Wind Harmer
0.057
3146486SUNBURY
Solar/Wind Harmer
0.057
316132AB2-190 GEN1
Solar/Wind Helper
0.895
316233AE1-074 FULL
Solar/Wind Helper
0.212
316312AB1-027
Solar/Wind Helper
0.237
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.194
3146516WINFALL
Solar/Wind Harmer
0.06
944591AF1-124 GEN
Solar/Wind Harmer
12.705
3142543TWELFTH
Solar/Wind Helper
0.024
316458AB2-190 GEN2
Solar/Wind Helper
0.895
3142433PROV 92
Solar/Wind Helper
0.616
3143526WINTERP
Solar/Wind Helper
0.72
3143226MDLTHAN
Solar/Wind Helper
0.125
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
3146386ELIZ CT
Solar/Wind Harmer
0.057
316240AF1-291 C
Solar/Wind Helper
0.411
966871AG1-558 GEN
Solar/Wind Helper
0.204
3142946ENON
Solar/Wind Helper
0.015
3143526WINTERP
Solar/Wind Helper
0.72
316468AD1-105 GEN
Solar/Wind Helper
0.653
316075AC2-137 C
Solar/Wind Helper
0.178
3146516WINFALL
Solar/Wind Harmer
0.06
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
12.66
944601AF1-125 GEN
Solar/Wind Harmer
12.465
315839AE2-212 C
Solar/Wind Helper
0.986
316473AC1-191 GEN
Solar/Wind Helper
0.925
3142946ENON
Solar/Wind Helper
0.049
CPLELTFEXP_CPLE->PJM
CLTF
5.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.951
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.461
MECLTFEXP_MEC->PJM
CLTF
1.839
SIGELTFEXP_SIGE->PJM
CLTF
0.055
NYPJM->LTFIMP_NY
CLTF
0.691
LGEELTFEXP_LGEE->PJM
CLTF
0.659
WECLTFEXP_WEC->PJM
CLTF
0.343
LAGNLTFEXP_LAGN->PJM
CLTF
3.79
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.991
TVALTFEXP_TVA->PJM
CLTF
1.888

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.07 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1046.37
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.142
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.272
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.898
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.85
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.85
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.927
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.691
316049AB1-081 GEN
Solar/Wind Harmer
2.154
3142053HEARTS
Solar/Wind Harmer
0.235
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.272
316365GEN2_N
Solar/Wind Harmer
3.898
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.567
316210AC1-098 GEN
Solar/Wind Harmer
3.469
316327AA2-057 GEN
Solar/Wind Harmer
2.181
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.106
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.272
3151621KERR 5
50/50
0.272
3151631KERR 6
50/50
0.272
3151641KERR 7
50/50
0.272
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.795
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.467
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.146
970831AG2-522 GEN
Solar/Wind Harmer
10.282
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.056
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.561
957861AF2-080 GEN
Solar/Wind Harmer
7.524
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.04
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.005
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.315
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.221
961681AG1-008 GEN
Solar/Wind Harmer
14.221
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.293
3156081AA2-088 GEN
Solar/Wind Harmer
5.454
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.577
964241AG1-285 GEN
Solar/Wind Harmer
10.88
3146206CASHIE
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.725
971065AG2-659 GEN
Solar/Wind Harmer
9.428
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.85
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.431
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.337
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.248
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.324
3145783HORNRTN
Solar/Wind Harmer
2.659
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.733
316274AC1-208 GEN
Solar/Wind Harmer
2.531
961601AG1-000A GEN
Solar/Wind Harmer
8.004
316263AC1-034 GEN
Solar/Wind Harmer
9.357
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.404
939181AE1-148 GEN
Solar/Wind Harmer
8.303
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.894
970257AG2-171 GEN
Solar/Wind Harmer
4.626
959311AF2-222 GEN
Solar/Wind Harmer
12.552
315737AD1-076 GEN
Solar/Wind Harmer
2.17
971157AH1-035 GEN
Solar/Wind Harmer
1.377
963181AG1-167 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.933
315614AA2-178 GEN
Solar/Wind Harmer
0.962
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.385
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
971683AH1-343 GEN
Solar/Wind Harmer
3.369
942461AE2-259 GEN
Solar/Wind Harmer
1.119
316283AC2-100 C
Solar/Wind Harmer
0.635
970909AG2-566 GEN
Solar/Wind Harmer
0.612
315839AE2-212 C
Solar/Wind Helper
0.202
971443AH1-215 GEN
Solar/Wind Harmer
2.448
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.309
315733AD1-074 GEN2
Solar/Wind Harmer
2.309
315735AD1-075 GEN1
Solar/Wind Harmer
1.155
970683AG2-441 GEN
Solar/Wind Harmer
8.785
970681AG2-440 GEN
Solar/Wind Harmer
7.028
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.616
961791AG1-021 GEN
Solar/Wind Harmer
1.276
316118AC1-105 GEN
Solar/Wind Harmer
0.689
315657AE1-056 GEN
Solar/Wind Harmer
3.56
315816AE2-034 GEN
Solar/Wind Harmer
0.721
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.486
970865AG2-541 GEN
Solar/Wind Harmer
2.987
316123AC1-075 GEN
Solar/Wind Harmer
0.692
970165AG2-112 GEN
Solar/Wind Harmer
0.609
970163AG2-111 GEN
Solar/Wind Harmer
0.581
316315AB2-025 C
Solar/Wind Helper
0.83
3143316POE
Solar/Wind Helper
0.701
316174AB2-169 GEN
Solar/Wind Harmer
2.09
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.737
970685AG2-442 GEN
Solar/Wind Harmer
9.839
963171AG1-166 GEN
Solar/Wind Harmer
1.276
971563AH1-280 GEN
Solar/Wind Harmer
1.276
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.359
957481AF2-042 GEN
Solar/Wind Harmer
25.811
316003AC1-222 GEN
Solar/Wind Harmer
0.806
315693AD1-088 GEN
Solar/Wind Harmer
4.085
315687AD1-152 GEN
Solar/Wind Harmer
0.98
962491AG1-098 GEN
Solar/Wind Harmer
5.404
316065AD1-022 GEN
Solar/Wind Harmer
6.44
970323AG2-213 GEN
Solar/Wind Harmer
6.168
971775AH1-396 GEN
Solar/Wind Harmer
0.878
316034AC1-036 C
Solar/Wind Harmer
0.229
962561AG1-105 GEN
Solar/Wind Harmer
6.652
964791AG1-342 GEN
Solar/Wind Harmer
2.412
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.595
963191AG1-168 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.244
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.324
970933AG2-581 GEN
Solar/Wind Harmer
7.724
315742AE1-103 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
7.95
316222AC1-221 GEN
Solar/Wind Harmer
0.686
970301AG2-198 GEN
Solar/Wind Harmer
3.221
3144356SAPONY
Solar/Wind Helper
0.977
316240AF1-291 C
Solar/Wind Helper
0.173
CPLELTFEXP_CPLE->PJM
CLTF
4.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.843
MECLTFEXP_MEC->PJM
CLTF
1.401
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.512
LGEELTFEXP_LGEE->PJM
CLTF
0.508
WECLTFEXP_WEC->PJM
CLTF
0.264
LAGNLTFEXP_LAGN->PJM
CLTF
2.828
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.165
TVALTFEXP_TVA->PJM
CLTF
1.41

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.99 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1045.7
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.272
3151621KERR 5
50/50
0.272
3151631KERR 6
50/50
0.272
3151641KERR 7
50/50
0.272
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.795
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.467
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.146
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.272
316365GEN2_N
Solar/Wind Harmer
3.898
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.567
316210AC1-098 GEN
Solar/Wind Harmer
3.469
316327AA2-057 GEN
Solar/Wind Harmer
2.181
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.106
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.315
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.221
961681AG1-008 GEN
Solar/Wind Harmer
14.221
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.293
3156081AA2-088 GEN
Solar/Wind Harmer
5.454
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.577
964241AG1-285 GEN
Solar/Wind Harmer
10.88
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.142
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.272
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.898
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.85
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.85
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.927
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.691
316049AB1-081 GEN
Solar/Wind Harmer
2.154
3142053HEARTS
Solar/Wind Harmer
0.235
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.725
971065AG2-659 GEN
Solar/Wind Harmer
9.428
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.85
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.337
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.248
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.324
3145783HORNRTN
Solar/Wind Harmer
2.659
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.733
316274AC1-208 GEN
Solar/Wind Harmer
2.531
961601AG1-000A GEN
Solar/Wind Harmer
8.004
316263AC1-034 GEN
Solar/Wind Harmer
9.357
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.404
939181AE1-148 GEN
Solar/Wind Harmer
8.303
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.431
316174AB2-169 GEN
Solar/Wind Harmer
2.09
3145963POPLR C
Solar/Wind Harmer
-0.013
970831AG2-522 GEN
Solar/Wind Harmer
10.282
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.056
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.561
957861AF2-080 GEN
Solar/Wind Harmer
7.524
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.04
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.005
315785AD2-033 C
Solar/Wind Harmer
2.894
970257AG2-171 GEN
Solar/Wind Harmer
4.626
959311AF2-222 GEN
Solar/Wind Harmer
12.552
315737AD1-076 GEN
Solar/Wind Harmer
2.17
971157AH1-035 GEN
Solar/Wind Harmer
1.377
963181AG1-167 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.933
315614AA2-178 GEN
Solar/Wind Harmer
0.962
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.385
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
971683AH1-343 GEN
Solar/Wind Harmer
3.369
942461AE2-259 GEN
Solar/Wind Harmer
1.119
316283AC2-100 C
Solar/Wind Harmer
0.635
970909AG2-566 GEN
Solar/Wind Harmer
0.612
315839AE2-212 C
Solar/Wind Helper
0.202
971443AH1-215 GEN
Solar/Wind Harmer
2.448
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.309
315733AD1-074 GEN2
Solar/Wind Harmer
2.309
315735AD1-075 GEN1
Solar/Wind Harmer
1.155
970683AG2-441 GEN
Solar/Wind Harmer
8.785
970681AG2-440 GEN
Solar/Wind Harmer
7.028
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.616
961791AG1-021 GEN
Solar/Wind Harmer
1.276
316118AC1-105 GEN
Solar/Wind Harmer
0.689
315657AE1-056 GEN
Solar/Wind Harmer
3.56
315816AE2-034 GEN
Solar/Wind Harmer
0.721
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.486
970865AG2-541 GEN
Solar/Wind Harmer
2.987
316123AC1-075 GEN
Solar/Wind Harmer
0.692
970165AG2-112 GEN
Solar/Wind Harmer
0.609
970163AG2-111 GEN
Solar/Wind Harmer
0.581
316315AB2-025 C
Solar/Wind Helper
0.83
3143316POE
Solar/Wind Helper
0.701
316065AD1-022 GEN
Solar/Wind Harmer
6.44
970323AG2-213 GEN
Solar/Wind Harmer
6.168
971775AH1-396 GEN
Solar/Wind Harmer
0.878
316034AC1-036 C
Solar/Wind Harmer
0.229
962561AG1-105 GEN
Solar/Wind Harmer
6.652
964791AG1-342 GEN
Solar/Wind Harmer
2.412
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.595
963191AG1-168 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.244
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.324
970933AG2-581 GEN
Solar/Wind Harmer
7.724
315742AE1-103 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
7.95
316222AC1-221 GEN
Solar/Wind Harmer
0.686
970301AG2-198 GEN
Solar/Wind Harmer
3.221
3144356SAPONY
Solar/Wind Helper
0.977
316240AF1-291 C
Solar/Wind Helper
0.173
970401AG2-262 GEN
Solar/Wind Harmer
0.737
970685AG2-442 GEN
Solar/Wind Harmer
9.839
963171AG1-166 GEN
Solar/Wind Harmer
1.276
971563AH1-280 GEN
Solar/Wind Harmer
1.276
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.359
957481AF2-042 GEN
Solar/Wind Harmer
25.811
316003AC1-222 GEN
Solar/Wind Harmer
0.806
315693AD1-088 GEN
Solar/Wind Harmer
4.085
315687AD1-152 GEN
Solar/Wind Harmer
0.98
962491AG1-098 GEN
Solar/Wind Harmer
5.404
CPLELTFEXP_CPLE->PJM
CLTF
4.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.843
MECLTFEXP_MEC->PJM
CLTF
1.401
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.512
LGEELTFEXP_LGEE->PJM
CLTF
0.508
WECLTFEXP_WEC->PJM
CLTF
0.264
LAGNLTFEXP_LAGN->PJM
CLTF
2.828
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.165
TVALTFEXP_TVA->PJM
CLTF
1.41

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:152.59 %
Rating:1331.98 MVA
Rating Type:B
MVA to Mitigate:2032.49
MW Contribution:0.5
Bus #Bus NameTypeMW Contribution
3152131X4-039 ST
50/50
2.892
3152121X4-039 GT2
50/50
1.833
3150011OMF A
50/50
0.216
3140676OCCOQUN
50/50
0.286
970467AG2-304 GEN
50/50
14.788
972223AH1-696 GEN
50/50
9.026
3150151POSSMC1
50/50
1.143
3141346CRANES
50/50
0.127
3150221REMNGT2
50/50
13.228
972201AH1-685 GEN
50/50
2.282
3150211REMNGT1
Adder
12.383
3150281M RUN A
Adder
13.357
316006AB2-029 C
Solar/Wind Harmer
0.001
971685AH1-345 GEN
Solar/Wind Harmer
0.73
316045AC1-158 PL2
Solar/Wind Harmer
1.475
972197AH1-683 GEN
Adder
1.98
972219AH1-694 GEN
Adder
1.425
316254AC1-120 GEN1
Solar/Wind Harmer
0.2
972135AH1-637 GEN
Solar/Wind Harmer
0.781
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.218
3147666LOUISA
Solar/Wind Harmer
0.355
316192AB2-158 GEN
Solar/Wind Harmer
0.501
316337AD2-073 GEN
Solar/Wind Harmer
0.077
3150351NORNECKC2
Adder
0.87
3141726DUNNSVL
Solar/Wind Harmer
0.348
962861AG1-135 GEN
Solar/Wind Harmer
2.764
3151751LOISA D
Adder
5.599
3138133OCRAN
Solar/Wind Harmer
0.051
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
0.337
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3152111X4-039 GT1
50/50
1.838
315747AE2-019 GEN
50/50
13.176
3150021OMF B
50/50
0.216
3150101POSSM6S
50/50
1.296
3150081POSSM6A
50/50
0.848
3150151POSSMC1
50/50
1.143
3150151POSSMC1
50/50
1.143
3150231REMNGT3
50/50
14.281
3150241REMNGT4
50/50
13.316
972217AH1-693 GEN
50/50
1.756
963691AG1-221 GEN
Solar/Wind Harmer
2.312
971455AH1-223 GEN
Solar/Wind Harmer
2.312
3141196NOKESVL
Solar/Wind Harmer
0.429
972199AH1-684 GEN
Adder
1.903
3150301M RUN C
Adder
13.349
3150291M RUN B
Adder
13.25
3150331BIRCHWDA
Adder
16.626
3141316ARNOLDS
Adder
0.229
316044AC1-158 PL1
Solar/Wind Harmer
0.461
316450AC1-158 RIC
Solar/Wind Harmer
0.123
3150401LDYSMT4
Adder
12.678
3150371LDYSMT1
Adder
12.251
316170AC1-121 GEN2
Solar/Wind Harmer
0.1
970737AG2-469 GEN
Solar/Wind Harmer
3.872
3141906WESTMOR
Solar/Wind Harmer
0.036
3132273ORANGE
Solar/Wind Harmer
0.018
971781AH1-399 GEN
Solar/Wind Harmer
0.118
3147666LOUISA
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.884
316404AE1-155 C
Solar/Wind Harmer
0.019
3151761LOISA E
Adder
11.415
972183AH1-676 GEN
Adder
92.045
970009AG2-005 GEN
Solar/Wind Harmer
0.643
316473AC1-191 GEN
Solar/Wind Harmer
0.29
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
0.435
3142543TWELFTH
Solar/Wind Harmer
0.008
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.853
3143226MDLTHAN
Solar/Wind Harmer
0.083
316159AE1-175 C
Solar/Wind Harmer
0.072
971317AH1-138 GEN
Solar/Wind Harmer
0.618
970129AG2-093 GEN
Solar/Wind Harmer
2.345
316458AB2-190 GEN2
Solar/Wind Harmer
0.442
315671AE2-027_GEN
Solar/Wind Harmer
5.273
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
3.497
961611AG1-000B GEN
Solar/Wind Harmer
4.29
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
0.325
316294AC1-161 GEN
Solar/Wind Harmer
1.405
970659AG2-427 GEN
Solar/Wind Harmer
3.913
316381AD1-082 GEN
Solar/Wind Harmer
0.084
316375AC2-012 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
8.025
3150981CHESPKA
Adder
1.007
944591AF1-124 GEN
Solar/Wind Harmer
18.213
316072AD1-144
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.251
3146456SLIGO L269
Solar/Wind Harmer
0.08
939411AE1-173 GEN
Solar/Wind Harmer
34.166
316246AF1-032 C
Solar/Wind Harmer
0.036
940641AE2-051 GEN
Solar/Wind Harmer
6.396
316093AE2-104_GEN
Solar/Wind Harmer
1.342
3143336POWHATN
Solar/Wind Harmer
1.412
3146516WINFALL
Solar/Wind Harmer
0.256
3146516WINFALL
Solar/Wind Harmer
0.079
316336AC2-165 C
Solar/Wind Harmer
0.003
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3145663CRESWEL
Solar/Wind Harmer
0.215
971163AH1-040 GEN
Solar/Wind Harmer
6.133
970937AG2-583 GEN
Solar/Wind Harmer
4.64
3146206CASHIE
Solar/Wind Harmer
0.075
971547AH1-271 GEN
Solar/Wind Harmer
1.606
316023GEN1_S
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
5.999
3146173TUNIS
Solar/Wind Harmer
0.075
960081AF2-299 GEN
Solar/Wind Harmer
0.714
3145683EARLEYS
Solar/Wind Harmer
0.074
957481AF2-042 GEN
Solar/Wind Harmer
19.771
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.545
962491AG1-098 GEN
Solar/Wind Harmer
4.214
971795AH1-408 GEN
Solar/Wind Harmer
4.913
3145963POPLR C
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.337
962571AG1-106 GEN
Solar/Wind Harmer
1.046
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Adder
0.664
972003AH1-546 GEN
Solar/Wind Harmer
3.117
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.029
3146926FARMVIL
Solar/Wind Harmer
0.044
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145783HORNRTN
Solar/Wind Harmer
0.073
962971AG1-146 GEN
Solar/Wind Harmer
1.373
3142416OLDCHRC
Solar/Wind Harmer
0.821
3141766HARMONY
Solar/Wind Harmer
1.129
316156AD2-030 GEN
Solar/Wind Harmer
0.063
3141873WAN 176
Solar/Wind Harmer
1.505
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
0.899
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
0.028
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
0.794
970129AG2-093 GEN
Solar/Wind Harmer
4.984
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
6.579
965281AG1-393 GEN
Solar/Wind Harmer
0.877
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.181
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
0.033
315813AE1-149 C
Solar/Wind Harmer
4.334
315773AC2-141 GEN
Solar/Wind Harmer
2.962
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.012
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
18.149
944601AF1-125 GEN
Solar/Wind Harmer
17.869
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.925
316320Y1-086
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.2
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.078
315614AA2-178 GEN
Solar/Wind Harmer
0.439
971157AH1-035 GEN
Solar/Wind Harmer
0.911
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
315737AD1-076 GEN
Solar/Wind Harmer
0.975
3146206CASHIE
Solar/Wind Harmer
0.075
316365GEN2_N
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
970917AG2-570 GEN
Solar/Wind Harmer
6.681
957521AF2-046 GEN
Solar/Wind Harmer
5.587
961681AG1-008 GEN
Solar/Wind Harmer
5.587
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.339
316463AE2-346 GEN
Solar/Wind Harmer
0.064
316140AB2-099
Solar/Wind Harmer
0.027
962331AG1-082 GEN
Solar/Wind Harmer
0.795
3146263WOODLND
Solar/Wind Harmer
0.074
313506AB2-031 GEN
Solar/Wind Harmer
0.228
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.074
970909AG2-566 GEN
Solar/Wind Harmer
0.785
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
963171AG1-166 GEN
Solar/Wind Harmer
0.385
971563AH1-280 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.23
316212AC1-099_GEN
Solar/Wind Harmer
0.372
970685AG2-442 GEN
Solar/Wind Harmer
5.37
972277AH1-723 GEN
Adder
42.854
3146293MARTNCO
Solar/Wind Harmer
0.067
316129AC1-054 GEN
Solar/Wind Harmer
0.27
971377AH1-170 GEN
Solar/Wind Harmer
0.763
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.053
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315722AD1-056 GEN
Solar/Wind Harmer
0.448
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316494AC1-189 GEN
Solar/Wind Harmer
0.238
3146233WITAKRS
Solar/Wind Harmer
0.278
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.07
3145493TOT1
Solar/Wind Harmer
0.31
316359AB2-059 GEN
Solar/Wind Harmer
0.248
316049AB1-081 GEN
Solar/Wind Harmer
0.395
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
3142053HEARTS
Solar/Wind Harmer
0.122
970401AG2-262 GEN
Solar/Wind Harmer
0.404
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315705AF1-075 GEN
Solar/Wind Harmer
2.472
3147983MERCK5
Solar/Wind Harmer
0.024
23779801AA1-109
Solar/Wind Helper
0.218
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.111
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232428Y3-058 C
Solar/Wind Helper
0.203
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
970053AG2-049 GEN
50/50
2.022
3138216PACIFIC
Solar/Wind Harmer
0.025
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
3141426STAFORD
Solar/Wind Harmer
0.023
3150411LDYSMT5
Adder
12.718
3150381LDYSMT2
Adder
12.172
972213AH1-691 GEN
Adder
2.059
972215AH1-692 GEN
Adder
2.059
316164AC1-076 GEN
Solar/Wind Harmer
0.132
944491AF1-114 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Harmer
0.064
972189AH1-679 GEN
Adder
1.467
3141813NORNECK
Solar/Wind Harmer
0.087
970327AG2-215 GEN
Solar/Wind Harmer
2.824
962981AG1-147 GEN
Solar/Wind Harmer
3.203
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.025
3141913WHIT STONE
Solar/Wind Harmer
0.085
3147346CASHSCORNER
Solar/Wind Harmer
0.196
316312AB1-027
Solar/Wind Harmer
0.152
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.017
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.507
3143873LANEXA
Solar/Wind Harmer
0.051
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
7.477
315976AC1-164 GENA
Solar/Wind Harmer
8.72
316169AC1-164_GENC
Solar/Wind Harmer
7.533
315975AC1-164 GENB
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971281AH1-106 GEN
Solar/Wind Harmer
1.161
971283AH1-107 GEN
Solar/Wind Harmer
1.161
971285AH1-108 GEN
Adder
0.631
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316132AB2-190 GEN1
Solar/Wind Harmer
0.442
316369SG1_INVT
Solar/Wind Harmer
0.003
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.723
3143316POE
Solar/Wind Harmer
0.321
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.055
316311AC2-079 GEN
Solar/Wind Harmer
2.303
957871AF2-081 GEN
Solar/Wind Harmer
3.99
316305AF2-043 C
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.403
3146406KITTY HAWK
Solar/Wind Harmer
0.01
315835AF2-110_GEN
Solar/Wind Harmer
0.548
313526AB2-022
Solar/Wind Harmer
0.043
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316321Z2-027
Solar/Wind Harmer
0.015
3146396TANGLEW
Solar/Wind Harmer
0.219
3145176PASQUOTANK
Solar/Wind Harmer
0.049
316315AB2-025 C
Solar/Wind Harmer
0.064
315814AE2-033 C
Solar/Wind Harmer
6.204
941031AE2-094 GEN
Solar/Wind Harmer
14.412
944011AF1-069 GEN
Solar/Wind Harmer
4.709
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
970673AG2-436 GEN
Solar/Wind Harmer
16.54
970673AG2-436 GEN
Solar/Wind Harmer
11.027
971967AH1-528 GEN
Solar/Wind Harmer
12.344
315816AE2-034 GEN
Solar/Wind Harmer
0.329
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.435
315733AD1-074 GEN2
Solar/Wind Harmer
0.435
315735AD1-075 GEN1
Solar/Wind Harmer
0.218
965291AG1-394 GEN
Solar/Wind Harmer
0.336
3146206CASHIE
Solar/Wind Harmer
0.075
970601AG2-382 GEN
Solar/Wind Harmer
2.811
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.149
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.152
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.294
315652AC1-086 GEN
Solar/Wind Harmer
8.087
972205AH1-687 GEN
Adder
3.134
970285AG2-188 GEN
Solar/Wind Harmer
5.802
971845AH1-439 GEN
Solar/Wind Harmer
3.325
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
3146033SCOT NK
Solar/Wind Harmer
0.29
315657AE1-056 GEN
Solar/Wind Harmer
2.494
946301AF1-294 GEN
Solar/Wind Harmer
1.424
961791AG1-021 GEN
Solar/Wind Harmer
0.693
970683AG2-441 GEN
Solar/Wind Harmer
4.794
970681AG2-440 GEN
Solar/Wind Harmer
3.836
970831AG2-522 GEN
Solar/Wind Harmer
3.066
972193AH1-681 GEN
Adder
1.643
3144303KENBRDG
Solar/Wind Harmer
0.057
971443AH1-215 GEN
Solar/Wind Harmer
1.204
971447AH1-217 GEN
Solar/Wind Harmer
2.163
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.883
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
3.032
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
316118AC1-105 GEN
Solar/Wind Harmer
0.176
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.802
3148133STUARTS
Solar/Wind Harmer
0.039
3148013FISHERV
Solar/Wind Harmer
0.037
970865AG2-541 GEN
Solar/Wind Harmer
2.214
316123AC1-075 GEN
Solar/Wind Harmer
0.084
970165AG2-112 GEN
Solar/Wind Harmer
0.5
970163AG2-111 GEN
Solar/Wind Harmer
0.477
3148463FAIRFLD
Solar/Wind Harmer
0.06
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.279
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.162
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
972289AH1-729 GEN
50/50
13.249
3150091POSSM6B
50/50
0.848
3150071POSSM 5
50/50
52.224
3150181POSSMC2
50/50
1.152
3150181POSSMC2
50/50
1.143
3150181POSSMC2
50/50
1.143
316447AC1-158 HLD
Solar/Wind Harmer
1.014
3150391LDYSMT3
Adder
12.655
972195AH1-682 GEN
Adder
1.663
315651AD1-115 GEN
Solar/Wind Harmer
0.003
315673AE1-157 GEN
Solar/Wind Harmer
6.396
957411AF2-035 GEN
Solar/Wind Harmer
3.895
970317AG2-208 GEN
Solar/Wind Harmer
3.609
316468AD1-105 GEN
Solar/Wind Harmer
-0.029
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.051
958261AF2-120 GEN
Solar/Wind Harmer
2.86
3151731LOISA B
Adder
5.599
3151721LOISA A
Adder
5.57
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.023
3142946ENON
Solar/Wind Harmer
0.008
3143526WINTERP
Solar/Wind Harmer
0.435
971223AH1-071 GEN
Solar/Wind Harmer
0.89
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.005
315697AD1-025 GEN
Solar/Wind Harmer
0.092
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.829
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.077
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.193
3145506HICKORY
Solar/Wind Harmer
0.048
316339AD2-160 GEN
Solar/Wind Harmer
0.13
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.045
3137176SLIGO L2192
Solar/Wind Harmer
0.319
3146456SLIGO L269
Solar/Wind Harmer
1.416
3130086AYDLETT
Solar/Wind Harmer
0.32
3146386ELIZ CT
Solar/Wind Harmer
0.08
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3144356SAPONY
Solar/Wind Harmer
0.657
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
972185AH1-677 GEN
Adder
4.331
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
6.107
316065AD1-022 GEN
Solar/Wind Harmer
3.475
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
970099AG2-077 GEN
Solar/Wind Harmer
7.908
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
971741AH1-377 GEN
Solar/Wind Harmer
7.304
970301AG2-198 GEN
Solar/Wind Harmer
3.138
316426AA2-053 GEN
Solar/Wind Harmer
0.248
3146776BUCKING
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.024
966811AG1-552 GEN
Solar/Wind Harmer
0.795
3145593CAROLNA
Solar/Wind Harmer
0.091
3145783HORNRTN
Solar/Wind Harmer
1.299
3145783HORNRTN
Solar/Wind Harmer
1.039
3145783HORNRTN
Solar/Wind Harmer
0.325
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.866
963191AG1-168 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
3145933PARMELE
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.072
316274AC1-208 GEN
Solar/Wind Harmer
0.372
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
3.057
971775AH1-396 GEN
Solar/Wind Harmer
0.115
971489AH1-241 GEN
Solar/Wind Harmer
3.817
313527AB2-043 GEN
Solar/Wind Harmer
0.001
939181AE1-148 GEN
Solar/Wind Harmer
3.402
3145493TOT1
Solar/Wind Harmer
0.162
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.065
315821AE2-092 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
1.228
316263AC1-034 GEN
Solar/Wind Harmer
2.624
964791AG1-342 GEN
Solar/Wind Harmer
1.322
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.264
971761AH1-387 GEN
Solar/Wind Harmer
1.238
942751AE2-291 GEN
Solar/Wind Harmer
3.276
3132123MT JACKSON
Solar/Wind Harmer
0.183
970117AG2-086 GEN
Solar/Wind Harmer
1.401
970117AG2-086 GEN
Solar/Wind Harmer
0.934
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
233946AB2-136 GEN
Solar/Wind Helper
0.341
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.042
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.443
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
3146776BUCKING
Solar/Wind Harmer
0.026
3146926FARMVIL
Solar/Wind Harmer
0.044
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
3147133PAMPLIN
Solar/Wind Harmer
0.227
971193AH1-056 GEN
Solar/Wind Harmer
4.404
963181AG1-167 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
316210AC1-098 GEN
Solar/Wind Harmer
0.668
972255AH1-712 GEN
Adder
36.775
3145933PARMELE
Solar/Wind Harmer
0.072
966801AG1-551 GEN
Solar/Wind Harmer
0.836
959311AF2-222 GEN
Solar/Wind Harmer
6.376
970257AG2-171 GEN
Solar/Wind Harmer
2.293
970221AG2-151 GEN
Solar/Wind Harmer
3.817
315785AD2-033 C
Solar/Wind Harmer
0.582
964241AG1-285 GEN
Solar/Wind Harmer
4.753
316131AB2-060 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.266
316327AA2-057 GEN
Solar/Wind Harmer
0.106
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.912
971623AH1-311 GEN
Solar/Wind Harmer
0.138
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.87
971683AH1-343 GEN
Solar/Wind Harmer
2.391
3148013FISHERV
Solar/Wind Harmer
0.065
316283AC2-100 C
Solar/Wind Harmer
0.124
315616AA1-038_C
Solar/Wind Harmer
0
3151861LOWMORA
Adder
0.645
958131AF2-107 GEN
Solar/Wind Harmer
1.618
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
CPLELTFEXP_CPLE->PJM
CLTF
5.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.965
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.592
MECLTFEXP_MEC->PJM
CLTF
4.449
SIGELTFEXP_SIGE->PJM
CLTF
0.14
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.324
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.565
TVALTFEXP_TVA->PJM
CLTF
3.188

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.83 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1144.9
MW Contribution:2.85
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.137
316248AF1-058 C
Solar/Wind Harmer
1.27
960061AF2-297 GEN
Solar/Wind Harmer
21.067
971683AH1-343 GEN
Solar/Wind Harmer
16.042
316283AC2-100 C
Solar/Wind Harmer
2.82
970917AG2-570 GEN
Solar/Wind Harmer
39.759
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.461
270197AD1-017 GEN1
Solar/Wind Harmer
1.353
270018AE2-047 C O1
Solar/Wind Harmer
1.019
943811AF1-049 GEN
Solar/Wind Harmer
2.868
270336AE1-100 GEN
Solar/Wind Harmer
1.167
971367AH1-164 GEN
Solar/Wind Harmer
1.912
961601AG1-000A GEN
Solar/Wind Harmer
2.784
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Helper
3.08
316486AD2-202 GEN
Solar/Wind Helper
0.902
3146926FARMVIL
Solar/Wind Helper
0.145
3146776BUCKING
Solar/Wind Helper
0.07
315773AC2-141 GEN
Solar/Wind Helper
3.622
942461AE2-259 GEN
Solar/Wind Helper
1.133
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.205
3145336SMITFLD
Solar/Wind Helper
0.06
316382AG1-145 C
Solar/Wind Helper
0.193
3146456SLIGO L269
Solar/Wind Helper
0.143
316313AB2-026
Solar/Wind Helper
0.213
316258AE1-075 C
Solar/Wind Helper
0.192
316405AF2-144 C
Solar/Wind Helper
0.16
316156AD2-030 GEN
Solar/Wind Helper
0.206
316280AD1-041 GEN
Solar/Wind Helper
0.457
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.254
316320Y1-086
Solar/Wind Helper
0.059
316404AE1-155 C
Solar/Wind Helper
1.1
316473AC1-191 GEN
Solar/Wind Helper
0.746
3141906WESTMOR
Solar/Wind Helper
0.048
316435W1029_GEN3
Solar/Wind Helper
0.485
3146516WINFALL
Solar/Wind Helper
0.117
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
970865AG2-541 GEN
Solar/Wind Harmer
14.146
316118AC1-105 GEN
Solar/Wind Harmer
2.355
316123AC1-075 GEN
Solar/Wind Harmer
3.235
970165AG2-112 GEN
Solar/Wind Harmer
2.848
970163AG2-111 GEN
Solar/Wind Harmer
2.717
270455AD2-022 GEN
Solar/Wind Harmer
3.531
270457AD2-023 GEN
Solar/Wind Harmer
1.791
970085AG2-068 GEN
Solar/Wind Harmer
9.94
970581AG2-369 GEN
Solar/Wind Harmer
8.549
270069AE2-166 C O1
Solar/Wind Harmer
1.803
971981AH1-535 GEN
Solar/Wind Harmer
4.605
3143316POE
Solar/Wind Helper
0.634
316369SG1_INVT
Solar/Wind Helper
0.701
316132AB2-190 GEN1
Solar/Wind Helper
0.826
957831AF2-077 GEN
Solar/Wind Helper
0.192
319010AE1-072 C
Solar/Wind Helper
1.62
316305AF2-043 C
Solar/Wind Helper
0.189
316349AD2-085 GEN
Solar/Wind Helper
0.637
316233AE1-074 FULL
Solar/Wind Helper
0.211
957601AF2-054 GEN
Solar/Wind Helper
0.183
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.732
315666AE1-190 GEN
Solar/Wind Helper
0.183
3143873LANEXA
Solar/Wind Helper
0.081
316059AD1-063 C
Solar/Wind Helper
0.137
3141913WHIT STONE
Solar/Wind Helper
0.135
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.08
3141783LANCAST
Solar/Wind Helper
0.054
313526AB2-022
Solar/Wind Helper
0.2
316315AB2-025 C
Solar/Wind Helper
0.199
3146486SUNBURY
Solar/Wind Helper
0.128
3146486SUNBURY
Solar/Wind Helper
0.128
3141813NORNECK
Solar/Wind Helper
0.128
316312AB1-027
Solar/Wind Helper
0.241
316321Z2-027
Solar/Wind Helper
0.193
3145176PASQUOTANK
Solar/Wind Helper
0.078
316223AC1-118
Solar/Wind Helper
0.184
3152661PLYWOOD A
50/50
0.685
316222AC1-221 GEN
Solar/Wind Harmer
3.1
942751AE2-291 GEN
Solar/Wind Harmer
17.158
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.579
962561AG1-105 GEN
Solar/Wind Harmer
12.783
316217AC1-145 GEN
Solar/Wind Harmer
2.364
316197AC1-042 GEN
Solar/Wind Harmer
1.792
942671AE2-283 GEN
Solar/Wind Harmer
4.824
270013AE1-250 PV
Solar/Wind Harmer
2.226
961601AG1-000A GEN
Solar/Wind Harmer
2.749
316263AC1-034 GEN
Solar/Wind Harmer
3.259
3146776BUCKING
Solar/Wind Helper
0.779
3146776BUCKING
Solar/Wind Helper
0.063
316036AC1-147 C
Solar/Wind Helper
0.235
316316AC1-027 C
Solar/Wind Helper
0.241
3142956BIRDNECK
Solar/Wind Helper
0.103
316185AD1-033 GEN
Solar/Wind Helper
0.715
316236AE1-162_GEN
Solar/Wind Helper
0.202
3145506HICKORY
Solar/Wind Helper
0.599
3145506HICKORY
Solar/Wind Helper
0.359
3145506HICKORY
Solar/Wind Helper
0.09
316240AF1-291 C
Solar/Wind Helper
0.198
316339AD2-160 GEN
Solar/Wind Helper
0.555
316033AB2-134 GEN
Solar/Wind Helper
0.501
315697AD1-025 GEN
Solar/Wind Helper
1.666
316018AA1-139 ULT2
Solar/Wind Helper
0.622
316017AA1-139 ULT1
Solar/Wind Helper
0.661
3137176SLIGO L2192
Solar/Wind Helper
0.569
3130086AYDLETT
Solar/Wind Helper
0.564
3143526WINTERP
Solar/Wind Helper
0.718
3142946ENON
Solar/Wind Helper
0.014
316075AC2-137 C
Solar/Wind Helper
0.201
316487AF1-042 GEN
Solar/Wind Helper
0.133
3146386ELIZ CT
Solar/Wind Helper
0.131
3144356SAPONY
Solar/Wind Helper
0.234
316077AC2-138 C
Solar/Wind Helper
0.12
966871AG1-558 GEN
Solar/Wind Helper
0.165
316431W1029_GEN1
Solar/Wind Helper
0.485
316433W1029_GEN2
Solar/Wind Helper
0.485
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.568
971629AH1-314 GEN
50/50
13.489
3151561HALLBR1
50/50
0.374
24728405LEESVG
50/50
0.136
315687AD1-152 GEN
Solar/Wind Harmer
8.943
316003AC1-222 GEN
Solar/Wind Harmer
3.856
970401AG2-262 GEN
Solar/Wind Harmer
1.705
3147123OTTER R
Solar/Wind Harmer
-0.01
970087AG2-069 GEN
Solar/Wind Harmer
14.91
970919AG2-571 GEN
Solar/Wind Harmer
5.033
970223AG2-152 GEN
Solar/Wind Harmer
13.358
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.461
270016AE1-250 BESS
Solar/Wind Harmer
2.226
270574AD1-017 GEN2
Solar/Wind Harmer
4.502
270030AE2-140 GEN
Solar/Wind Harmer
14.747
270173AC1-122 GEN
Solar/Wind Harmer
1.038
316359AB2-059 GEN
Solar/Wind Harmer
0.937
316049AB1-081 GEN
Solar/Wind Harmer
0.75
3142053HEARTS
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146926FARMVIL
Solar/Wind Helper
0.145
316322AB2-045
Solar/Wind Helper
0.217
3146776BUCKING
Solar/Wind Helper
0.078
316294AC1-161 GEN
Solar/Wind Helper
3.077
316375AC2-012 GEN
Solar/Wind Helper
0.404
3145336SMITFLD
Solar/Wind Helper
0.602
316381AD1-082 GEN
Solar/Wind Helper
0.757
316388AE2-253 GEN
Solar/Wind Helper
0.555
316458AB2-190 GEN2
Solar/Wind Helper
0.826
316159AE1-175 C
Solar/Wind Helper
0.218
3146456SLIGO L269
Solar/Wind Helper
0.143
316072AD1-144
Solar/Wind Helper
0.163
3143226MDLTHAN
Solar/Wind Helper
0.141
316246AF1-032 C
Solar/Wind Helper
0.161
316336AC2-165 C
Solar/Wind Helper
0.752
3143526WINTERP
Solar/Wind Helper
0.718
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.545
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.081
964211AG1-282 GEN
Solar/Wind Helper
0.173
3141726DUNNSVL
Solar/Wind Helper
0.513
3142416OLDCHRC
Solar/Wind Helper
0.33
3142416OLDCHRC
Solar/Wind Helper
0.126
316337AD2-073 GEN
Solar/Wind Helper
0.188
3146516WINFALL
Solar/Wind Helper
0.38
3146516WINFALL
Solar/Wind Helper
0.117
CPLELTFEXP_CPLE->PJM
CLTF
11.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.541
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.134
MECLTFEXP_MEC->PJM
CLTF
5.224
SIGELTFEXP_SIGE->PJM
CLTF
0.159
NYPJM->LTFIMP_NY
CLTF
0.755
LGEELTFEXP_LGEE->PJM
CLTF
1.98
WECLTFEXP_WEC->PJM
CLTF
1.048
LAGNLTFEXP_LAGN->PJM
CLTF
9.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.294
TVALTFEXP_TVA->PJM
CLTF
4.607

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.64 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:885.41
MW Contribution:2.17
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.687
24684405SMG2
50/50
0.856
24684505SMG3
50/50
0.529
24684305SMG1
50/50
0.31
316222AC1-221 GEN
Solar/Wind Harmer
1.136
942751AE2-291 GEN
Solar/Wind Harmer
13.086
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.482
962561AG1-105 GEN
Solar/Wind Harmer
9.757
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.251
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.124
316263AC1-034 GEN
Solar/Wind Harmer
2.389
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
316236AE1-162_GEN
Solar/Wind Helper
0.2
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.778
316118AC1-105 GEN
Solar/Wind Harmer
0.789
316123AC1-075 GEN
Solar/Wind Harmer
0.366
970165AG2-112 GEN
Solar/Wind Harmer
2.171
970163AG2-111 GEN
Solar/Wind Harmer
2.071
970085AG2-068 GEN
Solar/Wind Harmer
7.603
970581AG2-369 GEN
Solar/Wind Harmer
6.538
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.177
3143316POE
Solar/Wind Helper
0.626
971629AH1-314 GEN
50/50
13.578
3151561HALLBR1
50/50
0.376
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.899
24684705SMG5
50/50
0.33
970481AG2-311 GEN
50/50
4.594
315687AD1-152 GEN
Solar/Wind Harmer
0.022
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.404
970919AG2-571 GEN
Solar/Wind Harmer
5.068
970223AG2-152 GEN
Solar/Wind Harmer
9.437
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.18
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.396
270173AC1-122 GEN
Solar/Wind Harmer
0.217
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146926FARMVIL
Solar/Wind Helper
0.144
316322AB2-045
Solar/Wind Helper
0.215
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.041
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
316369SG1_INVT
Solar/Wind Helper
0.691
316132AB2-190 GEN1
Solar/Wind Helper
0.815
957831AF2-077 GEN
Solar/Wind Helper
0.189
319010AE1-072 C
Solar/Wind Helper
1.597
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.628
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
315666AE1-190 GEN
Solar/Wind Helper
0.18
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.135
3141913WHIT STONE
Solar/Wind Helper
0.133
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.196
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.126
316312AB1-027
Solar/Wind Helper
0.238
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.181
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.862
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.042
971683AH1-343 GEN
Solar/Wind Harmer
12.22
316283AC2-100 C
Solar/Wind Harmer
0.523
970917AG2-570 GEN
Solar/Wind Harmer
12.67
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.18
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.353
961601AG1-000A GEN
Solar/Wind Harmer
4.498
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
942461AE2-259 GEN
Solar/Wind Helper
1.12
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.202
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.191
3146456SLIGO L269
Solar/Wind Helper
0.141
316313AB2-026
Solar/Wind Helper
0.21
316258AE1-075 C
Solar/Wind Helper
0.189
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.203
316280AD1-041 GEN
Solar/Wind Helper
0.451
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.083
316473AC1-191 GEN
Solar/Wind Helper
0.734
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
316159AE1-175 C
Solar/Wind Helper
0.215
3146456SLIGO L269
Solar/Wind Helper
0.141
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.139
316246AF1-032 C
Solar/Wind Helper
0.159
316336AC2-165 C
Solar/Wind Helper
0.741
3143526WINTERP
Solar/Wind Helper
0.708
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.17
3141726DUNNSVL
Solar/Wind Helper
0.505
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.373
3146516WINFALL
Solar/Wind Helper
0.115
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.195
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
315697AD1-025 GEN
Solar/Wind Helper
1.643
316018AA1-139 ULT2
Solar/Wind Helper
0.614
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
3143526WINTERP
Solar/Wind Helper
0.708
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.198
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.162
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.559
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163
NYPJM->LTFIMP_NY
CLTF
0.706
LGEELTFEXP_LGEE->PJM
CLTF
2.033
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.47 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:867.67
MW Contribution:2.17
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.687
24684405SMG2
50/50
0.856
24684505SMG3
50/50
0.529
24684305SMG1
50/50
0.31
316222AC1-221 GEN
Solar/Wind Harmer
1.136
942751AE2-291 GEN
Solar/Wind Harmer
13.086
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.482
962561AG1-105 GEN
Solar/Wind Harmer
9.757
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.251
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.124
316263AC1-034 GEN
Solar/Wind Harmer
2.389
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.195
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
315697AD1-025 GEN
Solar/Wind Helper
1.643
316018AA1-139 ULT2
Solar/Wind Helper
0.614
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
3143526WINTERP
Solar/Wind Helper
0.708
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.198
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.162
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.559
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.778
316118AC1-105 GEN
Solar/Wind Harmer
0.789
316123AC1-075 GEN
Solar/Wind Harmer
0.366
970165AG2-112 GEN
Solar/Wind Harmer
2.171
970163AG2-111 GEN
Solar/Wind Harmer
2.071
970085AG2-068 GEN
Solar/Wind Harmer
7.603
970581AG2-369 GEN
Solar/Wind Harmer
6.538
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.177
3143316POE
Solar/Wind Helper
0.626
316369SG1_INVT
Solar/Wind Helper
0.691
316132AB2-190 GEN1
Solar/Wind Helper
0.815
957831AF2-077 GEN
Solar/Wind Helper
0.189
319010AE1-072 C
Solar/Wind Helper
1.597
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.628
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
315666AE1-190 GEN
Solar/Wind Helper
0.18
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.135
3141913WHIT STONE
Solar/Wind Helper
0.133
971629AH1-314 GEN
50/50
13.578
3151561HALLBR1
50/50
0.376
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.899
24684705SMG5
50/50
0.33
970481AG2-311 GEN
50/50
4.594
315687AD1-152 GEN
Solar/Wind Harmer
0.022
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.404
970223AG2-152 GEN
Solar/Wind Harmer
9.437
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.18
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.396
270173AC1-122 GEN
Solar/Wind Harmer
0.217
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146926FARMVIL
Solar/Wind Helper
0.144
316322AB2-045
Solar/Wind Helper
0.215
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.041
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
316159AE1-175 C
Solar/Wind Helper
0.215
3146456SLIGO L269
Solar/Wind Helper
0.141
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.139
316246AF1-032 C
Solar/Wind Helper
0.159
316336AC2-165 C
Solar/Wind Helper
0.741
3143526WINTERP
Solar/Wind Helper
0.708
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.17
3141726DUNNSVL
Solar/Wind Helper
0.505
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.373
3146516WINFALL
Solar/Wind Helper
0.115
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.196
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.126
316312AB1-027
Solar/Wind Helper
0.238
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.181
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.862
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.042
971683AH1-343 GEN
Solar/Wind Harmer
12.22
316283AC2-100 C
Solar/Wind Harmer
0.523
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.18
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.353
961601AG1-000A GEN
Solar/Wind Harmer
4.498
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
942461AE2-259 GEN
Solar/Wind Helper
1.12
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.202
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.191
3146456SLIGO L269
Solar/Wind Helper
0.141
316313AB2-026
Solar/Wind Helper
0.21
316258AE1-075 C
Solar/Wind Helper
0.189
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.203
316280AD1-041 GEN
Solar/Wind Helper
0.451
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.083
316473AC1-191 GEN
Solar/Wind Helper
0.734
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163
NYPJM->LTFIMP_NY
CLTF
0.706
LGEELTFEXP_LGEE->PJM
CLTF
2.033
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P4-2: 57062_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57062_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.2 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:998.97
MW Contribution:2.86
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.138
316248AF1-058 C
Solar/Wind Harmer
1.273
960061AF2-297 GEN
Solar/Wind Harmer
21.123
971683AH1-343 GEN
Solar/Wind Harmer
16.09
316283AC2-100 C
Solar/Wind Harmer
2.83
970917AG2-570 GEN
Solar/Wind Harmer
40.038
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.503
270197AD1-017 GEN1
Solar/Wind Harmer
1.364
270018AE2-047 C O1
Solar/Wind Harmer
1.028
943811AF1-049 GEN
Solar/Wind Harmer
2.896
270336AE1-100 GEN
Solar/Wind Harmer
1.18
971367AH1-164 GEN
Solar/Wind Harmer
1.939
961601AG1-000A GEN
Solar/Wind Harmer
2.829
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3146926FARMVIL
Solar/Wind Helper
0.144
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
970865AG2-541 GEN
Solar/Wind Harmer
14.192
316118AC1-105 GEN
Solar/Wind Harmer
2.363
316123AC1-075 GEN
Solar/Wind Harmer
3.247
970165AG2-112 GEN
Solar/Wind Harmer
2.859
970163AG2-111 GEN
Solar/Wind Harmer
2.727
270455AD2-022 GEN
Solar/Wind Harmer
3.551
270457AD2-023 GEN
Solar/Wind Harmer
1.801
970085AG2-068 GEN
Solar/Wind Harmer
10.01
970581AG2-369 GEN
Solar/Wind Harmer
8.609
270069AE2-166 C O1
Solar/Wind Harmer
1.824
971981AH1-535 GEN
Solar/Wind Harmer
4.681
3143316POE
Solar/Wind Helper
0.626
316369SG1_INVT
Solar/Wind Helper
0.691
316132AB2-190 GEN1
Solar/Wind Helper
0.815
957831AF2-077 GEN
Solar/Wind Helper
0.189
319010AE1-072 C
Solar/Wind Helper
1.597
316305AF2-043 C
Solar/Wind Helper
0.186
971629AH1-314 GEN
50/50
13.578
3151561HALLBR1
50/50
0.376
24728405LEESVG
50/50
0.138
315687AD1-152 GEN
Solar/Wind Harmer
8.957
316003AC1-222 GEN
Solar/Wind Harmer
3.867
970401AG2-262 GEN
Solar/Wind Harmer
1.712
3147123OTTER R
Solar/Wind Harmer
-0.01
970087AG2-069 GEN
Solar/Wind Harmer
15.015
970919AG2-571 GEN
Solar/Wind Harmer
5.068
970223AG2-152 GEN
Solar/Wind Harmer
13.457
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.503
270016AE1-250 BESS
Solar/Wind Harmer
2.243
270574AD1-017 GEN2
Solar/Wind Harmer
4.541
270030AE2-140 GEN
Solar/Wind Harmer
14.9
270173AC1-122 GEN
Solar/Wind Harmer
1.05
316359AB2-059 GEN
Solar/Wind Harmer
0.952
316049AB1-081 GEN
Solar/Wind Harmer
0.762
3142053HEARTS
Solar/Wind Harmer
0.083
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146926FARMVIL
Solar/Wind Helper
0.144
316322AB2-045
Solar/Wind Helper
0.215
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.041
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
316159AE1-175 C
Solar/Wind Helper
0.215
3146456SLIGO L269
Solar/Wind Helper
0.141
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.139
3152661PLYWOOD A
50/50
0.687
316222AC1-221 GEN
Solar/Wind Harmer
3.111
942751AE2-291 GEN
Solar/Wind Harmer
17.229
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.603
962561AG1-105 GEN
Solar/Wind Harmer
12.846
316217AC1-145 GEN
Solar/Wind Harmer
2.382
316197AC1-042 GEN
Solar/Wind Harmer
1.806
942671AE2-283 GEN
Solar/Wind Harmer
4.861
270013AE1-250 PV
Solar/Wind Harmer
2.243
961601AG1-000A GEN
Solar/Wind Harmer
2.793
316263AC1-034 GEN
Solar/Wind Harmer
3.311
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.195
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
315697AD1-025 GEN
Solar/Wind Helper
1.643
316018AA1-139 ULT2
Solar/Wind Helper
0.614
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
942461AE2-259 GEN
Solar/Wind Helper
1.12
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.202
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.191
3146456SLIGO L269
Solar/Wind Helper
0.141
316349AD2-085 GEN
Solar/Wind Helper
0.628
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
315666AE1-190 GEN
Solar/Wind Helper
0.18
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.135
3141913WHIT STONE
Solar/Wind Helper
0.133
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.196
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.126
316312AB1-027
Solar/Wind Helper
0.238
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.181
3143526WINTERP
Solar/Wind Helper
0.708
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.198
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.162
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.559
316246AF1-032 C
Solar/Wind Helper
0.159
316336AC2-165 C
Solar/Wind Helper
0.741
3143526WINTERP
Solar/Wind Helper
0.708
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.17
3141726DUNNSVL
Solar/Wind Helper
0.505
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.373
3146516WINFALL
Solar/Wind Helper
0.115
316313AB2-026
Solar/Wind Helper
0.21
316258AE1-075 C
Solar/Wind Helper
0.189
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.203
316280AD1-041 GEN
Solar/Wind Helper
0.451
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.083
316473AC1-191 GEN
Solar/Wind Helper
0.734
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163
NYPJM->LTFIMP_NY
CLTF
0.706
LGEELTFEXP_LGEE->PJM
CLTF
2.033
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.41 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1132.24
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.272
3151621KERR 5
50/50
0.272
3151631KERR 6
50/50
0.272
3151641KERR 7
50/50
0.272
315814AE2-033 C
Solar/Wind Harmer
87.045
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.795
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.467
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.146
970831AG2-522 GEN
Solar/Wind Harmer
10.282
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.056
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.561
957861AF2-080 GEN
Solar/Wind Harmer
7.524
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.04
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.005
971443AH1-215 GEN
Solar/Wind Harmer
2.448
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.309
315733AD1-074 GEN2
Solar/Wind Harmer
2.309
315735AD1-075 GEN1
Solar/Wind Harmer
1.155
970683AG2-441 GEN
Solar/Wind Harmer
8.785
970681AG2-440 GEN
Solar/Wind Harmer
7.028
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.616
961791AG1-021 GEN
Solar/Wind Harmer
1.276
316118AC1-105 GEN
Solar/Wind Harmer
0.689
315657AE1-056 GEN
Solar/Wind Harmer
3.56
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.337
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.248
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.324
3145783HORNRTN
Solar/Wind Harmer
2.659
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.733
316274AC1-208 GEN
Solar/Wind Harmer
2.531
961601AG1-000A GEN
Solar/Wind Harmer
8.004
316263AC1-034 GEN
Solar/Wind Harmer
9.357
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.404
939181AE1-148 GEN
Solar/Wind Harmer
8.303
316065AD1-022 GEN
Solar/Wind Harmer
6.44
970323AG2-213 GEN
Solar/Wind Harmer
6.168
971775AH1-396 GEN
Solar/Wind Harmer
0.878
316034AC1-036 C
Solar/Wind Harmer
0.229
962561AG1-105 GEN
Solar/Wind Harmer
6.652
964791AG1-342 GEN
Solar/Wind Harmer
2.412
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.595
963191AG1-168 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.244
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.272
316365GEN2_N
Solar/Wind Harmer
3.898
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.567
316210AC1-098 GEN
Solar/Wind Harmer
3.469
316327AA2-057 GEN
Solar/Wind Harmer
2.181
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.106
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.315
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.221
961681AG1-008 GEN
Solar/Wind Harmer
14.221
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.293
3156081AA2-088 GEN
Solar/Wind Harmer
5.454
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.577
964241AG1-285 GEN
Solar/Wind Harmer
10.88
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.894
970257AG2-171 GEN
Solar/Wind Harmer
4.626
959311AF2-222 GEN
Solar/Wind Harmer
12.552
315737AD1-076 GEN
Solar/Wind Harmer
2.17
971157AH1-035 GEN
Solar/Wind Harmer
1.377
963181AG1-167 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.933
315614AA2-178 GEN
Solar/Wind Harmer
0.962
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.142
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.272
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.898
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.85
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.85
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.927
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.691
316049AB1-081 GEN
Solar/Wind Harmer
2.154
3142053HEARTS
Solar/Wind Harmer
0.235
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.725
971065AG2-659 GEN
Solar/Wind Harmer
9.428
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.85
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.431
316174AB2-169 GEN
Solar/Wind Harmer
2.09
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.737
970685AG2-442 GEN
Solar/Wind Harmer
9.839
963171AG1-166 GEN
Solar/Wind Harmer
1.276
971563AH1-280 GEN
Solar/Wind Harmer
1.276
3144293JTRSVLE
Adder
0.289
315816AE2-034 GEN
Solar/Wind Harmer
0.721
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.486
970865AG2-541 GEN
Solar/Wind Harmer
2.987
316123AC1-075 GEN
Solar/Wind Harmer
0.692
970165AG2-112 GEN
Solar/Wind Harmer
0.609
970163AG2-111 GEN
Solar/Wind Harmer
0.581
316315AB2-025 C
Solar/Wind Helper
0.83
3143316POE
Solar/Wind Helper
0.701
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.385
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
971683AH1-343 GEN
Solar/Wind Harmer
3.369
942461AE2-259 GEN
Solar/Wind Harmer
1.119
316283AC2-100 C
Solar/Wind Harmer
0.635
970909AG2-566 GEN
Solar/Wind Harmer
0.612
315839AE2-212 C
Solar/Wind Helper
0.202
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.359
957481AF2-042 GEN
Solar/Wind Harmer
25.811
316003AC1-222 GEN
Solar/Wind Harmer
0.806
315693AD1-088 GEN
Solar/Wind Harmer
4.085
315687AD1-152 GEN
Solar/Wind Harmer
0.98
962491AG1-098 GEN
Solar/Wind Harmer
5.404
970099AG2-077 GEN
Solar/Wind Harmer
10.324
970933AG2-581 GEN
Solar/Wind Harmer
7.724
315742AE1-103 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
7.95
316222AC1-221 GEN
Solar/Wind Harmer
0.686
970301AG2-198 GEN
Solar/Wind Harmer
3.221
3144356SAPONY
Solar/Wind Helper
0.977
316240AF1-291 C
Solar/Wind Helper
0.173
CPLELTFEXP_CPLE->PJM
CLTF
4.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.843
MECLTFEXP_MEC->PJM
CLTF
1.401
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.512
LGEELTFEXP_LGEE->PJM
CLTF
0.508
WECLTFEXP_WEC->PJM
CLTF
0.264
LAGNLTFEXP_LAGN->PJM
CLTF
2.828
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.165
TVALTFEXP_TVA->PJM
CLTF
1.41

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.35 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1131.67
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.142
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.272
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.898
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.85
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.85
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.927
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.691
316049AB1-081 GEN
Solar/Wind Harmer
2.154
3142053HEARTS
Solar/Wind Harmer
0.235
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.725
971065AG2-659 GEN
Solar/Wind Harmer
9.428
3145683EARLEYS
Solar/Wind Harmer
-0.019
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.272
316365GEN2_N
Solar/Wind Harmer
3.898
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.272
3151621KERR 5
50/50
0.272
3151631KERR 6
50/50
0.272
3151641KERR 7
50/50
0.272
315814AE2-033 C
Solar/Wind Harmer
87.045
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.795
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.467
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.146
970831AG2-522 GEN
Solar/Wind Harmer
10.282
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
315724AD1-057 GEN
Solar/Wind Harmer
1.567
316210AC1-098 GEN
Solar/Wind Harmer
3.469
316327AA2-057 GEN
Solar/Wind Harmer
2.181
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.106
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.315
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.221
961681AG1-008 GEN
Solar/Wind Harmer
14.221
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.293
3156081AA2-088 GEN
Solar/Wind Harmer
5.454
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.577
964241AG1-285 GEN
Solar/Wind Harmer
10.88
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.894
970257AG2-171 GEN
Solar/Wind Harmer
4.626
959311AF2-222 GEN
Solar/Wind Harmer
12.552
315737AD1-076 GEN
Solar/Wind Harmer
2.17
971157AH1-035 GEN
Solar/Wind Harmer
1.377
963181AG1-167 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.933
315614AA2-178 GEN
Solar/Wind Harmer
0.962
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.385
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
971683AH1-343 GEN
Solar/Wind Harmer
3.369
942461AE2-259 GEN
Solar/Wind Harmer
1.119
316283AC2-100 C
Solar/Wind Harmer
0.635
970909AG2-566 GEN
Solar/Wind Harmer
0.612
315839AE2-212 C
Solar/Wind Helper
0.202
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.85
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.431
316174AB2-169 GEN
Solar/Wind Harmer
2.09
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.737
970685AG2-442 GEN
Solar/Wind Harmer
9.839
963171AG1-166 GEN
Solar/Wind Harmer
1.276
971563AH1-280 GEN
Solar/Wind Harmer
1.276
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.359
957481AF2-042 GEN
Solar/Wind Harmer
25.811
316003AC1-222 GEN
Solar/Wind Harmer
0.806
315693AD1-088 GEN
Solar/Wind Harmer
4.085
315687AD1-152 GEN
Solar/Wind Harmer
0.98
962491AG1-098 GEN
Solar/Wind Harmer
5.404
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.337
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.248
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.324
3145783HORNRTN
Solar/Wind Harmer
2.659
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.733
316274AC1-208 GEN
Solar/Wind Harmer
2.531
961601AG1-000A GEN
Solar/Wind Harmer
8.004
316263AC1-034 GEN
Solar/Wind Harmer
9.357
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.404
939181AE1-148 GEN
Solar/Wind Harmer
8.303
316065AD1-022 GEN
Solar/Wind Harmer
6.44
970323AG2-213 GEN
Solar/Wind Harmer
6.168
971775AH1-396 GEN
Solar/Wind Harmer
0.878
316034AC1-036 C
Solar/Wind Harmer
0.229
962561AG1-105 GEN
Solar/Wind Harmer
6.652
964791AG1-342 GEN
Solar/Wind Harmer
2.412
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.595
963191AG1-168 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.244
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.324
970933AG2-581 GEN
Solar/Wind Harmer
7.724
315742AE1-103 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
7.95
316222AC1-221 GEN
Solar/Wind Harmer
0.686
970301AG2-198 GEN
Solar/Wind Harmer
3.221
3144356SAPONY
Solar/Wind Helper
0.977
316240AF1-291 C
Solar/Wind Helper
0.173
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.056
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.561
957861AF2-080 GEN
Solar/Wind Harmer
7.524
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.04
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.005
971443AH1-215 GEN
Solar/Wind Harmer
2.448
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.309
315733AD1-074 GEN2
Solar/Wind Harmer
2.309
315735AD1-075 GEN1
Solar/Wind Harmer
1.155
970683AG2-441 GEN
Solar/Wind Harmer
8.785
970681AG2-440 GEN
Solar/Wind Harmer
7.028
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.616
961791AG1-021 GEN
Solar/Wind Harmer
1.276
316118AC1-105 GEN
Solar/Wind Harmer
0.689
315657AE1-056 GEN
Solar/Wind Harmer
3.56
315816AE2-034 GEN
Solar/Wind Harmer
0.721
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.486
970865AG2-541 GEN
Solar/Wind Harmer
2.987
316123AC1-075 GEN
Solar/Wind Harmer
0.692
970165AG2-112 GEN
Solar/Wind Harmer
0.609
970163AG2-111 GEN
Solar/Wind Harmer
0.581
316315AB2-025 C
Solar/Wind Helper
0.83
3143316POE
Solar/Wind Helper
0.701
CPLELTFEXP_CPLE->PJM
CLTF
4.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.843
MECLTFEXP_MEC->PJM
CLTF
1.401
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.512
LGEELTFEXP_LGEE->PJM
CLTF
0.508
WECLTFEXP_WEC->PJM
CLTF
0.264
LAGNLTFEXP_LAGN->PJM
CLTF
2.828
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.165
TVALTFEXP_TVA->PJM
CLTF
1.41

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.24 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1376.51
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.19 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1376.13
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:197.56 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1351.34
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
971967AH1-528 GEN
Solar/Wind Harmer
73.183
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
970933AG2-581 GEN
Solar/Wind Harmer
36.495
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.93 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1095.86
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970933AG2-581 GEN
Solar/Wind Harmer
27.718
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
971967AH1-528 GEN
Solar/Wind Harmer
55.434
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:193.37 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1081.51
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:191.54 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1310.12
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:191.54 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1310.12
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
316336AC2-165 C
Solar/Wind Helper
1.308
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.01 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:814.05
MW Contribution:0.75
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3151541CLOVER2
50/50
2.829
315657AE1-056 GEN
Solar/Wind Harmer
15.784
946301AF1-294 GEN
Solar/Wind Harmer
10.059
961791AG1-021 GEN
Solar/Wind Harmer
4.907
970683AG2-441 GEN
Solar/Wind Harmer
27.489
970681AG2-440 GEN
Solar/Wind Harmer
21.992
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.004
316239AB2-077_GEN
Solar/Wind Harmer
0.621
316238AB2-078_GEN
Solar/Wind Harmer
0.621
316118AC1-105 GEN
Solar/Wind Harmer
0.972
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.033
970865AG2-541 GEN
Solar/Wind Harmer
3.923
946281AF1-292 GEN
Solar/Wind Harmer
0.19
316087AB2-174 GEN
Solar/Wind Harmer
1.178
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.853
970165AG2-112 GEN
Solar/Wind Harmer
0.751
970163AG2-111 GEN
Solar/Wind Harmer
0.717
971967AH1-528 GEN
Solar/Wind Harmer
14.188
315607AA1-063A GEN
Solar/Wind Harmer
0.715
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.499
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.18
3144293JTRSVLE
50/50
0.994
970535AG2-341 GEN
50/50
2.836
3152661PLYWOOD A
50/50
0.267
970301AG2-198 GEN
Solar/Wind Harmer
21.257
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.133
963191AG1-168 GEN
Solar/Wind Harmer
3.68
971741AH1-377 GEN
Solar/Wind Harmer
43.417
316034AC1-036 C
Solar/Wind Harmer
0.574
970323AG2-213 GEN
Solar/Wind Harmer
15.434
971775AH1-396 GEN
Solar/Wind Harmer
2.198
3144293JTRSVLE
50/50
1.18
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.843
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.907
971563AH1-280 GEN
Solar/Wind Harmer
4.907
970685AG2-442 GEN
Solar/Wind Harmer
30.788
962491AG1-098 GEN
Solar/Wind Harmer
14.151
316237AB2-079_GEN
Solar/Wind Harmer
0.621
315693AD1-088 GEN
Solar/Wind Harmer
9.998
970401AG2-262 GEN
Solar/Wind Harmer
1.046
957481AF2-042 GEN
Solar/Wind Harmer
45.244
315687AD1-152 GEN
Solar/Wind Harmer
1.611
971065AG2-659 GEN
Solar/Wind Harmer
6.471
316129AC1-054 GEN
Solar/Wind Harmer
1.098
3147043LAWRENC
Adder
0.994
316003AC1-222 GEN
Solar/Wind Harmer
1.108
971795AH1-408 GEN
Solar/Wind Harmer
8.341
960081AF2-299 GEN
Solar/Wind Harmer
0.953
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316212AC1-099_GEN
Solar/Wind Harmer
0.553
316322AB2-045
Solar/Wind Helper
0.97
3146776BUCKING
Solar/Wind Helper
0.348
316336AC2-165 C
Solar/Wind Helper
1.454
313527AB2-043 GEN
Solar/Wind Harmer
3.442
962561AG1-105 GEN
Solar/Wind Harmer
9.457
939181AE1-148 GEN
Solar/Wind Harmer
9.083
964791AG1-342 GEN
Solar/Wind Harmer
3.423
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.098
970933AG2-581 GEN
Solar/Wind Harmer
9.079
316181AB2-040 GEN
Solar/Wind Harmer
1.138
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.878
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.905
3145783HORNRTN
Solar/Wind Harmer
0.724
3145783HORNRTN
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.769
316426AA2-053 GEN
Solar/Wind Harmer
0.748
942751AE2-291 GEN
Solar/Wind Harmer
4.333
316274AC1-208 GEN
Solar/Wind Harmer
0.717
972187AH1-678 GEN
Adder
1.63
3146776BUCKING
Solar/Wind Helper
3.482
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.994
3144293JTRSVLE
50/50
1.18
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.405
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.535
970909AG2-566 GEN
Solar/Wind Harmer
4.036
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.307
963181AG1-167 GEN
Solar/Wind Harmer
3.68
959311AF2-222 GEN
Solar/Wind Harmer
33.514
970257AG2-171 GEN
Solar/Wind Harmer
11.575
315785AD2-033 C
Solar/Wind Harmer
6.609
964241AG1-285 GEN
Solar/Wind Harmer
19.233
316131AB2-060 GEN
Solar/Wind Harmer
2.359
316478AD1-087 GEN
Solar/Wind Harmer
1.29
316486AD2-202 GEN
Solar/Wind Harmer
0.378
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.371
960061AF2-297 GEN
Solar/Wind Harmer
6.151
971683AH1-343 GEN
Solar/Wind Harmer
4.535
966621AG1-532 GEN
Solar/Wind Harmer
0.172
313506AB2-031 GEN
Solar/Wind Harmer
0.656
316283AC2-100 C
Solar/Wind Harmer
0.705
316210AC1-098 GEN
Solar/Wind Harmer
0.995
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.306
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.125
CPLELTFEXP_CPLE->PJM
CLTF
3.717
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.651
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.966
MECLTFEXP_MEC->PJM
CLTF
0.645
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.186
WECLTFEXP_WEC->PJM
CLTF
0.097
LAGNLTFEXP_LAGN->PJM
CLTF
1.842
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.457
TVALTFEXP_TVA->PJM
CLTF
0.904

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.81 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:812.65
MW Contribution:0.79
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.289
970413AG2-270 GEN
50/50
12.897
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.289
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.955
3147043LAWRENC
50/50
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.97
971563AH1-280 GEN
Solar/Wind Harmer
4.97
970685AG2-442 GEN
Solar/Wind Harmer
31.247
962491AG1-098 GEN
Solar/Wind Harmer
14.52
316237AB2-079_GEN
Solar/Wind Harmer
0.639
315693AD1-088 GEN
Solar/Wind Harmer
10.276
970401AG2-262 GEN
Solar/Wind Harmer
1.085
957481AF2-042 GEN
Solar/Wind Harmer
47.025
315687AD1-152 GEN
Solar/Wind Harmer
1.689
971065AG2-659 GEN
Solar/Wind Harmer
6.793
316129AC1-054 GEN
Solar/Wind Harmer
1.154
316003AC1-222 GEN
Solar/Wind Harmer
1.163
971795AH1-408 GEN
Solar/Wind Harmer
8.792
960081AF2-299 GEN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.099
316212AC1-099_GEN
Solar/Wind Harmer
0.614
970919AG2-571 GEN
Solar/Wind Harmer
2.193
970087AG2-069 GEN
Solar/Wind Harmer
6.491
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.406
962571AG1-106 GEN
Solar/Wind Harmer
0.966
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.899
316049AB1-081 GEN
Solar/Wind Harmer
0.72
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.694
316023GEN1_S
Solar/Wind Harmer
0.443
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.007
970535AG2-341 GEN
50/50
2.934
3152661PLYWOOD A
50/50
0.28
970301AG2-198 GEN
Solar/Wind Harmer
21.495
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.212
963191AG1-168 GEN
Solar/Wind Harmer
3.727
971741AH1-377 GEN
Solar/Wind Harmer
43.991
316034AC1-036 C
Solar/Wind Harmer
0.584
970323AG2-213 GEN
Solar/Wind Harmer
15.706
971775AH1-396 GEN
Solar/Wind Harmer
2.237
313527AB2-043 GEN
Solar/Wind Harmer
3.538
962561AG1-105 GEN
Solar/Wind Harmer
9.795
939181AE1-148 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.552
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.81
970933AG2-581 GEN
Solar/Wind Harmer
9.592
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316222AC1-221 GEN
Solar/Wind Harmer
0.857
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.951
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.982
3145783HORNRTN
Solar/Wind Harmer
0.786
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
0.793
942751AE2-291 GEN
Solar/Wind Harmer
4.536
972187AH1-678 GEN
Adder
1.773
972185AH1-677 GEN
Adder
3.35
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3151611KERR 4
50/50
0.289
3151621KERR 5
50/50
0.289
3151631KERR 6
50/50
0.289
3151641KERR 7
50/50
0.289
3151541CLOVER2
50/50
2.941
315657AE1-056 GEN
Solar/Wind Harmer
15.969
946301AF1-294 GEN
Solar/Wind Harmer
10.188
961791AG1-021 GEN
Solar/Wind Harmer
4.97
970683AG2-441 GEN
Solar/Wind Harmer
27.899
970681AG2-440 GEN
Solar/Wind Harmer
22.32
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.111
316239AB2-077_GEN
Solar/Wind Harmer
0.639
316238AB2-078_GEN
Solar/Wind Harmer
0.639
316118AC1-105 GEN
Solar/Wind Harmer
1.014
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.355
970865AG2-541 GEN
Solar/Wind Harmer
4.115
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.265
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
0.787
970163AG2-111 GEN
Solar/Wind Harmer
0.751
971967AH1-528 GEN
Solar/Wind Harmer
15.203
315607AA1-063A GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.327
970581AG2-369 GEN
Solar/Wind Harmer
3.722
316319Z2-044 C
Solar/Wind Harmer
0.378
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.562
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.582
970673AG2-436 GEN
Solar/Wind Harmer
13.618
970673AG2-436 GEN
Solar/Wind Harmer
6.895
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.464
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.126
961601AG1-000A GEN
Solar/Wind Harmer
2.583
3145893MURPHYS
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
3146776BUCKING
Solar/Wind Helper
3.457
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.963
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.604
970909AG2-566 GEN
Solar/Wind Harmer
4.081
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.615
963181AG1-167 GEN
Solar/Wind Harmer
3.727
959311AF2-222 GEN
Solar/Wind Harmer
34.076
970257AG2-171 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
6.734
964241AG1-285 GEN
Solar/Wind Harmer
19.68
316131AB2-060 GEN
Solar/Wind Harmer
2.422
316478AD1-087 GEN
Solar/Wind Harmer
1.342
316486AD2-202 GEN
Solar/Wind Harmer
0.393
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.458
971683AH1-343 GEN
Solar/Wind Harmer
4.759
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.706
316283AC2-100 C
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.105
316327AA2-057 GEN
Solar/Wind Harmer
0.707
970917AG2-570 GEN
Solar/Wind Harmer
17.327
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.382
316365GEN2_N
Solar/Wind Harmer
0.443
961601AG1-000A GEN
Solar/Wind Harmer
2.615
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.09
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.039
961681AG1-008 GEN
Solar/Wind Harmer
5.039
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.332
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.123
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.346
316336AC2-165 C
Solar/Wind Helper
1.425
CPLELTFEXP_CPLE->PJM
CLTF
4.543
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.552
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.96
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.219
WECLTFEXP_WEC->PJM
CLTF
0.123
LAGNLTFEXP_LAGN->PJM
CLTF
2.505
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.252
TVALTFEXP_TVA->PJM
CLTF
1.216

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.25 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:788.33
MW Contribution:0.78
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.19
3144293JTRSVLE
50/50
1.002
970535AG2-341 GEN
50/50
2.898
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.406
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.183
963191AG1-168 GEN
Solar/Wind Harmer
3.71
971741AH1-377 GEN
Solar/Wind Harmer
43.786
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.608
971775AH1-396 GEN
Solar/Wind Harmer
2.223
3144293JTRSVLE
50/50
1.19
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.729
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.576
970909AG2-566 GEN
Solar/Wind Harmer
4.064
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.496
963181AG1-167 GEN
Solar/Wind Harmer
3.71
959311AF2-222 GEN
Solar/Wind Harmer
33.872
970257AG2-171 GEN
Solar/Wind Harmer
11.706
315785AD2-033 C
Solar/Wind Harmer
6.689
3144293JTRSVLE
50/50
1.19
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.102
3151531CLOVER1
50/50
2.917
3147043LAWRENC
50/50
1.102
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.946
971563AH1-280 GEN
Solar/Wind Harmer
4.946
970685AG2-442 GEN
Solar/Wind Harmer
31.078
962491AG1-098 GEN
Solar/Wind Harmer
14.404
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.19
970401AG2-262 GEN
Solar/Wind Harmer
1.07
957481AF2-042 GEN
Solar/Wind Harmer
46.506
315687AD1-152 GEN
Solar/Wind Harmer
1.657
971065AG2-659 GEN
Solar/Wind Harmer
6.686
316129AC1-054 GEN
Solar/Wind Harmer
1.136
971795AH1-408 GEN
Solar/Wind Harmer
8.781
316003AC1-222 GEN
Solar/Wind Harmer
1.14
960081AF2-299 GEN
Solar/Wind Harmer
1.025
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.591
970919AG2-571 GEN
Solar/Wind Harmer
2.137
970087AG2-069 GEN
Solar/Wind Harmer
6.318
316023GEN1_S
Solar/Wind Harmer
0.452
316011AB1-132 GEN
Solar/Wind Harmer
1.389
962571AG1-106 GEN
Solar/Wind Harmer
0.954
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.667
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.456
964241AG1-285 GEN
Solar/Wind Harmer
19.525
316131AB2-060 GEN
Solar/Wind Harmer
2.4
316478AD1-087 GEN
Solar/Wind Harmer
1.324
316486AD2-202 GEN
Solar/Wind Harmer
0.388
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.381
960061AF2-297 GEN
Solar/Wind Harmer
6.325
971683AH1-343 GEN
Solar/Wind Harmer
4.674
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.702
316283AC2-100 C
Solar/Wind Harmer
0.736
316210AC1-098 GEN
Solar/Wind Harmer
1.064
970917AG2-570 GEN
Solar/Wind Harmer
16.885
316365GEN2_N
Solar/Wind Harmer
0.452
316327AA2-057 GEN
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.367
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.124
313527AB2-043 GEN
Solar/Wind Harmer
3.505
962561AG1-105 GEN
Solar/Wind Harmer
9.664
939181AE1-148 GEN
Solar/Wind Harmer
9.308
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.602
970933AG2-581 GEN
Solar/Wind Harmer
9.49
316181AB2-040 GEN
Solar/Wind Harmer
1.218
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.963
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.802
316426AA2-053 GEN
Solar/Wind Harmer
0.797
316274AC1-208 GEN
Solar/Wind Harmer
0.766
942751AE2-291 GEN
Solar/Wind Harmer
4.503
972187AH1-678 GEN
Adder
1.745
972185AH1-677 GEN
Adder
3.302
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.47
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.982
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.903
315657AE1-056 GEN
Solar/Wind Harmer
15.898
946301AF1-294 GEN
Solar/Wind Harmer
10.139
961791AG1-021 GEN
Solar/Wind Harmer
4.946
970683AG2-441 GEN
Solar/Wind Harmer
27.748
970681AG2-440 GEN
Solar/Wind Harmer
22.198
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.073
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.997
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.254
970865AG2-541 GEN
Solar/Wind Harmer
4.048
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
0.778
970163AG2-111 GEN
Solar/Wind Harmer
0.742
971967AH1-528 GEN
Solar/Wind Harmer
15.039
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.212
970581AG2-369 GEN
Solar/Wind Harmer
3.623
315652AC1-086 GEN
Solar/Wind Harmer
7.469
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.36
970673AG2-436 GEN
Solar/Wind Harmer
13.449
970673AG2-436 GEN
Solar/Wind Harmer
6.81
965291AG1-394 GEN
Solar/Wind Harmer
0.565
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
CPLELTFEXP_CPLE->PJM
CLTF
3.951
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.023
NYPJM->LTFIMP_NY
CLTF
0.315
LGEELTFEXP_LGEE->PJM
CLTF
0.251
WECLTFEXP_WEC->PJM
CLTF
0.133
LAGNLTFEXP_LAGN->PJM
CLTF
2.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.001
TVALTFEXP_TVA->PJM
CLTF
1.025

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 115KV_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 115KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.26 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:774.73
MW Contribution:1.38
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.203
3151601KERR 3
50/50
0.292
3151581KERR 1
50/50
0.104
3151531CLOVER1
50/50
2.981
3147043LAWRENC
50/50
1.112
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
5.001
971563AH1-280 GEN
Solar/Wind Harmer
5.001
970685AG2-442 GEN
Solar/Wind Harmer
31.502
962491AG1-098 GEN
Solar/Wind Harmer
14.564
316237AB2-079_GEN
Solar/Wind Harmer
0.652
315693AD1-088 GEN
Solar/Wind Harmer
10.309
970401AG2-262 GEN
Solar/Wind Harmer
1.156
3151611KERR 4
50/50
0.292
3151621KERR 5
50/50
0.292
3151631KERR 6
50/50
0.292
3151641KERR 7
50/50
0.292
3151541CLOVER2
50/50
2.967
315657AE1-056 GEN
Solar/Wind Harmer
16.053
946301AF1-294 GEN
Solar/Wind Harmer
10.253
961791AG1-021 GEN
Solar/Wind Harmer
5.001
970683AG2-441 GEN
Solar/Wind Harmer
28.127
970681AG2-440 GEN
Solar/Wind Harmer
22.501
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.178
316239AB2-077_GEN
Solar/Wind Harmer
0.652
316238AB2-078_GEN
Solar/Wind Harmer
0.652
316118AC1-105 GEN
Solar/Wind Harmer
1.105
316123AC1-075 GEN
Solar/Wind Harmer
1.561
970165AG2-112 GEN
Solar/Wind Harmer
1.375
970163AG2-111 GEN
Solar/Wind Harmer
1.311
970865AG2-541 GEN
Solar/Wind Harmer
5.879
3147173SINAI
Solar/Wind Harmer
-0.014
3147243WELCO
Solar/Wind Harmer
-0.009
970831AG2-522 GEN
Solar/Wind Harmer
6.369
946281AF1-292 GEN
Solar/Wind Harmer
0.201
316087AB2-174 GEN
Solar/Wind Harmer
1.25
3137643SOCKMAN
Solar/Wind Harmer
-0.034
971967AH1-528 GEN
Solar/Wind Harmer
14.997
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.185
970581AG2-369 GEN
Solar/Wind Harmer
3.599
3146033SCOT NK
Solar/Wind Harmer
-0.026
315652AC1-086 GEN
Solar/Wind Harmer
7.298
316319Z2-044 C
Solar/Wind Harmer
0.358
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.567
970673AG2-436 GEN
Solar/Wind Harmer
13.3
970673AG2-436 GEN
Solar/Wind Harmer
6.734
270494AE1-108_GEN
Solar/Wind Helper
4.519
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
957481AF2-042 GEN
Solar/Wind Harmer
47.203
3147123OTTER R
Solar/Wind Harmer
-0.009
316003AC1-222 GEN
Solar/Wind Harmer
1.413
315687AD1-152 GEN
Solar/Wind Harmer
1.721
971065AG2-659 GEN
Solar/Wind Harmer
6.825
316129AC1-054 GEN
Solar/Wind Harmer
1.158
971795AH1-408 GEN
Solar/Wind Harmer
8.808
960081AF2-299 GEN
Solar/Wind Harmer
1.012
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.59
970919AG2-571 GEN
Solar/Wind Harmer
2.123
970087AG2-069 GEN
Solar/Wind Harmer
6.277
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.357
962571AG1-106 GEN
Solar/Wind Harmer
0.932
3146233WITAKRS
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.006
316023GEN1_S
Solar/Wind Harmer
0.431
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.345
316336AC2-165 C
Solar/Wind Helper
1.43
3144293JTRSVLE
50/50
1.203
3144293JTRSVLE
50/50
1.013
970535AG2-341 GEN
50/50
2.978
3152661PLYWOOD A
50/50
0.306
970301AG2-198 GEN
Solar/Wind Harmer
21.525
3147133PAMPLIN
Solar/Wind Harmer
-0.043
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.252
963191AG1-168 GEN
Solar/Wind Harmer
3.751
971741AH1-377 GEN
Solar/Wind Harmer
44.063
316034AC1-036 C
Solar/Wind Harmer
0.59
970323AG2-213 GEN
Solar/Wind Harmer
15.873
971775AH1-396 GEN
Solar/Wind Harmer
2.26
313527AB2-043 GEN
Solar/Wind Harmer
3.607
962561AG1-105 GEN
Solar/Wind Harmer
10.348
964791AG1-342 GEN
Solar/Wind Harmer
3.783
3146843MT LREL
Solar/Wind Harmer
-0.018
3144293JTRSVLE
50/50
1.203
3151591KERR 2
50/50
0.292
970413AG2-270 GEN
50/50
13.01
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.625
970909AG2-566 GEN
Solar/Wind Harmer
4.087
3147133PAMPLIN
Solar/Wind Harmer
-0.134
971193AH1-056 GEN
Solar/Wind Harmer
26.755
963181AG1-167 GEN
Solar/Wind Harmer
3.751
959311AF2-222 GEN
Solar/Wind Harmer
34.411
970257AG2-171 GEN
Solar/Wind Harmer
11.905
315785AD2-033 C
Solar/Wind Harmer
6.813
964241AG1-285 GEN
Solar/Wind Harmer
19.989
316131AB2-060 GEN
Solar/Wind Harmer
2.467
3146843MT LREL
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.553
970099AG2-077 GEN
Solar/Wind Harmer
18.881
942751AE2-291 GEN
Solar/Wind Harmer
9.226
970933AG2-581 GEN
Solar/Wind Harmer
9.531
316181AB2-040 GEN
Solar/Wind Harmer
1.209
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.828
3145783HORNRTN
Solar/Wind Harmer
0.962
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
316426AA2-053 GEN
Solar/Wind Harmer
0.796
316274AC1-208 GEN
Solar/Wind Harmer
0.764
972187AH1-678 GEN
Adder
1.732
972185AH1-677 GEN
Adder
3.271
3145796HORNRTN
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.456
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.97
316478AD1-087 GEN
Solar/Wind Harmer
1.354
316486AD2-202 GEN
Solar/Wind Harmer
0.396
971683AH1-343 GEN
Solar/Wind Harmer
6.24
316248AF1-058 C
Solar/Wind Harmer
0.436
960061AF2-297 GEN
Solar/Wind Harmer
7.234
3147043LAWRENC
Solar/Wind Harmer
-0.008
966621AG1-532 GEN
Solar/Wind Harmer
0.182
313506AB2-031 GEN
Solar/Wind Harmer
0.697
316283AC2-100 C
Solar/Wind Harmer
0.759
316210AC1-098 GEN
Solar/Wind Harmer
1.062
970917AG2-570 GEN
Solar/Wind Harmer
16.773
316327AA2-057 GEN
Solar/Wind Harmer
0.674
3146263WOODLND
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316365GEN2_N
Solar/Wind Harmer
0.431
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.334
316258AE1-075 C
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.25
3148013FISHERV
Solar/Wind Helper
0.123
CPLELTFEXP_CPLE->PJM
CLTF
3.953
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.193
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.695
SIGELTFEXP_SIGE->PJM
CLTF
0.019
NYPJM->LTFIMP_NY
CLTF
0.29
LGEELTFEXP_LGEE->PJM
CLTF
0.201
WECLTFEXP_WEC->PJM
CLTF
0.107
LAGNLTFEXP_LAGN->PJM
CLTF
1.949
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.898
TVALTFEXP_TVA->PJM
CLTF
0.953

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.32 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:566.67
MW Contribution:0.58
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971

Details for 6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-5: 556X2_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-5: 556X2_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.23 %
Rating:1050.6 MVA
Rating Type:C
MVA to Mitigate:1462.74
MW Contribution:1.78
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.954
3144293JTRSVLE
50/50
0.803
970535AG2-341 GEN
50/50
4.477
3152661PLYWOOD A
50/50
0.537
971741AH1-377 GEN
Solar/Wind Harmer
58.955
970301AG2-198 GEN
Solar/Wind Harmer
23.48
970099AG2-077 GEN
Solar/Wind Harmer
54.72
3147133PAMPLIN
Solar/Wind Harmer
-0.032
3147133PAMPLIN
Solar/Wind Harmer
-0.026
958211AF2-115 GEN
Solar/Wind Harmer
4.957
963191AG1-168 GEN
Solar/Wind Harmer
2.974
316034AC1-036 C
Solar/Wind Harmer
0.564
970323AG2-213 GEN
Solar/Wind Harmer
15.2
971775AH1-396 GEN
Solar/Wind Harmer
2.165
313527AB2-043 GEN
Solar/Wind Harmer
4.69
939181AE1-148 GEN
Solar/Wind Harmer
15.738
962561AG1-105 GEN
Solar/Wind Harmer
15.589
964791AG1-342 GEN
Solar/Wind Harmer
5.876
3146843MT LREL
Solar/Wind Harmer
-0.027
3146843MT LREL
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.099
3146776BUCKING
Solar/Wind Harmer
-0.008
942751AE2-291 GEN
Solar/Wind Harmer
10.674
316222AC1-221 GEN
Solar/Wind Harmer
1.342
971489AH1-241 GEN
Solar/Wind Harmer
6.897
316217AC1-145 GEN
Solar/Wind Harmer
1.425
316197AC1-042 GEN
Solar/Wind Harmer
1.08
942671AE2-283 GEN
Solar/Wind Harmer
2.907
315821AE2-092 GEN
Solar/Wind Harmer
1.728
316036AC1-147 C
Solar/Wind Helper
0.189
3142956BIRDNECK
Solar/Wind Helper
0.083
316316AC1-027 C
Solar/Wind Helper
0.194
316185AD1-033 GEN
Solar/Wind Helper
0.577
970413AG2-270 GEN
50/50
36.366
3144293JTRSVLE
50/50
0.954
3151591KERR 2
50/50
0.512
3151921BEARGRDN G2
50/50
1.071
970909AG2-566 GEN
Solar/Wind Harmer
4.458
316478AD1-087 GEN
Solar/Wind Harmer
3.778
316486AD2-202 GEN
Solar/Wind Harmer
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
5.027
3147133PAMPLIN
Solar/Wind Harmer
-0.101
971193AH1-056 GEN
Solar/Wind Harmer
20.111
963181AG1-167 GEN
Solar/Wind Harmer
2.974
959311AF2-222 GEN
Solar/Wind Harmer
31.935
970257AG2-171 GEN
Solar/Wind Harmer
11.4
315785AD2-033 C
Solar/Wind Harmer
6.828
964241AG1-285 GEN
Solar/Wind Harmer
22.977
316131AB2-060 GEN
Solar/Wind Harmer
3.126
316248AF1-058 C
Solar/Wind Harmer
0.799
960061AF2-297 GEN
Solar/Wind Harmer
13.263
3146776BUCKING
Solar/Wind Harmer
-0.009
971683AH1-343 GEN
Solar/Wind Harmer
10.071
316283AC2-100 C
Solar/Wind Harmer
1.212
3147043LAWRENC
Solar/Wind Harmer
-0.007
970221AG2-151 GEN
Solar/Wind Harmer
7.265
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
3.291
958131AF2-107 GEN
Solar/Wind Harmer
2.165
315773AC2-141 GEN
Solar/Wind Helper
2.933
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.018
3151541CLOVER2
50/50
8.294
3151611KERR 4
50/50
0.512
3151621KERR 5
50/50
0.512
3151631KERR 6
50/50
0.512
3151641KERR 7
50/50
0.512
972205AH1-687 GEN
50/50
5.225
315657AE1-056 GEN
Solar/Wind Harmer
12.067
946301AF1-294 GEN
Solar/Wind Harmer
8.13
961791AG1-021 GEN
Solar/Wind Harmer
3.966
970683AG2-441 GEN
Solar/Wind Harmer
24.284
970681AG2-440 GEN
Solar/Wind Harmer
19.428
3144303KENBRDG
Solar/Wind Harmer
-0.024
971443AH1-215 GEN
Solar/Wind Harmer
5.973
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
970285AG2-188 GEN
Solar/Wind Harmer
23.989
316118AC1-105 GEN
Solar/Wind Harmer
1.858
3147173SINAI
Solar/Wind Harmer
-0.026
3147243WELCO
Solar/Wind Harmer
-0.016
971845AH1-439 GEN
Solar/Wind Harmer
13.717
970865AG2-541 GEN
Solar/Wind Harmer
8.867
970831AG2-522 GEN
Solar/Wind Harmer
9.395
316123AC1-075 GEN
Solar/Wind Harmer
2.019
970165AG2-112 GEN
Solar/Wind Harmer
1.778
970163AG2-111 GEN
Solar/Wind Harmer
1.696
971447AH1-217 GEN
Solar/Wind Harmer
3.892
270494AE1-108_GEN
Solar/Wind Harmer
2.597
270455AD2-022 GEN
Solar/Wind Harmer
1.324
270457AD2-023 GEN
Solar/Wind Harmer
0.671
3151531CLOVER1
50/50
8.333
3144293JTRSVLE
50/50
0.954
3151601KERR 3
50/50
0.512
3151581KERR 1
50/50
0.183
3151931BEARGRDN S1
50/50
1.383
3151911BEARGRDN G1
50/50
1.071
315693AD1-088 GEN
Solar/Wind Harmer
31.661
962491AG1-098 GEN
Solar/Wind Harmer
41.781
957481AF2-042 GEN
Solar/Wind Harmer
136.799
315687AD1-152 GEN
Solar/Wind Harmer
4.384
3146926FARMVIL
Solar/Wind Harmer
-0.021
963171AG1-166 GEN
Solar/Wind Harmer
3.966
971563AH1-280 GEN
Solar/Wind Harmer
3.966
970685AG2-442 GEN
Solar/Wind Harmer
27.199
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970401AG2-262 GEN
Solar/Wind Harmer
1.795
316322AB2-045
Solar/Wind Harmer
0.84
3146776BUCKING
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
2.424
971065AG2-659 GEN
Solar/Wind Harmer
10.717
316129AC1-054 GEN
Solar/Wind Harmer
1.767
972003AH1-546 GEN
Solar/Wind Harmer
7.559
3147043LAWRENC
Adder
0.99
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
3147123OTTER R
Solar/Wind Harmer
-0.006
971795AH1-408 GEN
Solar/Wind Harmer
7.507
970937AG2-583 GEN
Solar/Wind Harmer
6.673
3147312GRETNA
Solar/Wind Harmer
-0.007
3146802CHATHAM
Solar/Wind Harmer
-0.007
941801AE2-185 GEN
Solar/Wind Harmer
3.291
316294AC1-161 GEN
Solar/Wind Helper
2.492
316375AC2-012 GEN
Solar/Wind Helper
0.324
3145506HICKORY
Solar/Wind Helper
0.484
3145506HICKORY
Solar/Wind Helper
0.291
3145506HICKORY
Solar/Wind Helper
0.073
316339AD2-160 GEN
Solar/Wind Helper
0.45
316018AA1-139 ULT2
Solar/Wind Helper
0.505
316017AA1-139 ULT1
Solar/Wind Helper
0.536
316236AE1-162_GEN
Solar/Wind Helper
0.157
3137176SLIGO L2192
Solar/Wind Helper
0.462
3130086AYDLETT
Solar/Wind Helper
0.459
3143316POE
Solar/Wind Helper
0.479
319010AE1-072 C
Solar/Wind Helper
1.317
316305AF2-043 C
Solar/Wind Helper
0.151
3145336SMITFLD
Solar/Wind Helper
0.047
3146456SLIGO L269
Solar/Wind Helper
0.116
316388AE2-253 GEN
Solar/Wind Helper
0.45
3145336SMITFLD
Solar/Wind Helper
0.467
3146456SLIGO L269
Solar/Wind Helper
0.116
316246AF1-032 C
Solar/Wind Helper
0.129
316072AD1-144
Solar/Wind Helper
0.129
CPLELTFEXP_CPLE->PJM
CLTF
2.622
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.961
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.001
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.345
MECLTFEXP_MEC->PJM
CLTF
1.48
SIGELTFEXP_SIGE->PJM
CLTF
0.047
NYPJM->LTFIMP_NY
CLTF
0.45
LGEELTFEXP_LGEE->PJM
CLTF
0.594
WECLTFEXP_WEC->PJM
CLTF
0.305
LAGNLTFEXP_LAGN->PJM
CLTF
2.391
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.949
TVALTFEXP_TVA->PJM
CLTF
1.221

Details for 6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: 556X1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-5: 556X1_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.76 %
Rating:1053.0 MVA
Rating Type:C
MVA to Mitigate:1461.12
MW Contribution:1.78
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.953
3144293JTRSVLE
50/50
0.802
970535AG2-341 GEN
50/50
4.472
3152661PLYWOOD A
50/50
0.536
971741AH1-377 GEN
Solar/Wind Harmer
58.889
970301AG2-198 GEN
Solar/Wind Harmer
23.454
970099AG2-077 GEN
Solar/Wind Harmer
54.659
3147133PAMPLIN
Solar/Wind Harmer
-0.032
3147133PAMPLIN
Solar/Wind Harmer
-0.026
958211AF2-115 GEN
Solar/Wind Harmer
4.952
963191AG1-168 GEN
Solar/Wind Harmer
2.971
316034AC1-036 C
Solar/Wind Harmer
0.563
970323AG2-213 GEN
Solar/Wind Harmer
15.183
971775AH1-396 GEN
Solar/Wind Harmer
2.162
313527AB2-043 GEN
Solar/Wind Harmer
4.685
939181AE1-148 GEN
Solar/Wind Harmer
15.721
962561AG1-105 GEN
Solar/Wind Harmer
15.572
964791AG1-342 GEN
Solar/Wind Harmer
5.869
3146843MT LREL
Solar/Wind Harmer
-0.027
3146843MT LREL
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.099
3146776BUCKING
Solar/Wind Harmer
-0.008
942751AE2-291 GEN
Solar/Wind Harmer
10.662
316222AC1-221 GEN
Solar/Wind Harmer
1.341
971489AH1-241 GEN
Solar/Wind Harmer
6.89
970413AG2-270 GEN
50/50
36.326
3144293JTRSVLE
50/50
0.953
3151591KERR 2
50/50
0.511
3151921BEARGRDN G2
50/50
1.07
970909AG2-566 GEN
Solar/Wind Harmer
4.453
316478AD1-087 GEN
Solar/Wind Harmer
3.774
316486AD2-202 GEN
Solar/Wind Harmer
1.105
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
5.021
3147133PAMPLIN
Solar/Wind Harmer
-0.1
971193AH1-056 GEN
Solar/Wind Harmer
20.089
963181AG1-167 GEN
Solar/Wind Harmer
2.971
959311AF2-222 GEN
Solar/Wind Harmer
31.9
970257AG2-171 GEN
Solar/Wind Harmer
11.387
315785AD2-033 C
Solar/Wind Harmer
6.821
964241AG1-285 GEN
Solar/Wind Harmer
22.951
316131AB2-060 GEN
Solar/Wind Harmer
3.123
316248AF1-058 C
Solar/Wind Harmer
0.798
960061AF2-297 GEN
Solar/Wind Harmer
13.248
3146776BUCKING
Solar/Wind Harmer
-0.009
971683AH1-343 GEN
Solar/Wind Harmer
10.06
316283AC2-100 C
Solar/Wind Harmer
1.21
3147043LAWRENC
Solar/Wind Harmer
-0.007
970221AG2-151 GEN
Solar/Wind Harmer
7.257
3151531CLOVER1
50/50
8.324
3144293JTRSVLE
50/50
0.953
3151601KERR 3
50/50
0.511
3151581KERR 1
50/50
0.182
3151931BEARGRDN S1
50/50
1.381
3151911BEARGRDN G1
50/50
1.07
315693AD1-088 GEN
Solar/Wind Harmer
31.626
962491AG1-098 GEN
Solar/Wind Harmer
41.735
957481AF2-042 GEN
Solar/Wind Harmer
136.647
315687AD1-152 GEN
Solar/Wind Harmer
4.379
3146926FARMVIL
Solar/Wind Harmer
-0.021
963171AG1-166 GEN
Solar/Wind Harmer
3.962
971563AH1-280 GEN
Solar/Wind Harmer
3.962
970685AG2-442 GEN
Solar/Wind Harmer
27.168
316237AB2-079_GEN
Solar/Wind Harmer
0.865
970401AG2-262 GEN
Solar/Wind Harmer
1.793
316322AB2-045
Solar/Wind Harmer
0.839
3146776BUCKING
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
2.421
971065AG2-659 GEN
Solar/Wind Harmer
10.705
316129AC1-054 GEN
Solar/Wind Harmer
1.765
972003AH1-546 GEN
Solar/Wind Harmer
7.55
3147043LAWRENC
Adder
0.989
971377AH1-170 GEN
Solar/Wind Harmer
1.451
3147623JAMES R
Solar/Wind Harmer
0.18
3147123OTTER R
Solar/Wind Harmer
-0.006
971795AH1-408 GEN
Solar/Wind Harmer
7.499
970937AG2-583 GEN
Solar/Wind Harmer
6.666
3147312GRETNA
Solar/Wind Harmer
-0.007
3146802CHATHAM
Solar/Wind Harmer
-0.007
941801AE2-185 GEN
Solar/Wind Harmer
3.288
316294AC1-161 GEN
Solar/Wind Helper
2.489
316375AC2-012 GEN
Solar/Wind Helper
0.324
316388AE2-253 GEN
Solar/Wind Helper
0.45
3145336SMITFLD
Solar/Wind Helper
0.467
3146456SLIGO L269
Solar/Wind Helper
0.116
316246AF1-032 C
Solar/Wind Helper
0.128
316072AD1-144
Solar/Wind Helper
0.128
3151541CLOVER2
50/50
8.284
3151611KERR 4
50/50
0.511
3151621KERR 5
50/50
0.511
3151631KERR 6
50/50
0.511
3151641KERR 7
50/50
0.511
972205AH1-687 GEN
50/50
5.219
315657AE1-056 GEN
Solar/Wind Harmer
12.053
946301AF1-294 GEN
Solar/Wind Harmer
8.121
961791AG1-021 GEN
Solar/Wind Harmer
3.962
970683AG2-441 GEN
Solar/Wind Harmer
24.258
970681AG2-440 GEN
Solar/Wind Harmer
19.406
3144303KENBRDG
Solar/Wind Harmer
-0.024
971443AH1-215 GEN
Solar/Wind Harmer
5.967
316239AB2-077_GEN
Solar/Wind Harmer
0.865
316238AB2-078_GEN
Solar/Wind Harmer
0.865
970285AG2-188 GEN
Solar/Wind Harmer
23.962
316118AC1-105 GEN
Solar/Wind Harmer
1.856
3147173SINAI
Solar/Wind Harmer
-0.026
3147243WELCO
Solar/Wind Harmer
-0.016
971845AH1-439 GEN
Solar/Wind Harmer
13.702
970865AG2-541 GEN
Solar/Wind Harmer
8.857
970831AG2-522 GEN
Solar/Wind Harmer
9.385
316123AC1-075 GEN
Solar/Wind Harmer
2.017
970165AG2-112 GEN
Solar/Wind Harmer
1.776
970163AG2-111 GEN
Solar/Wind Harmer
1.694
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
3.288
958131AF2-107 GEN
Solar/Wind Harmer
2.163
315773AC2-141 GEN
Solar/Wind Helper
2.93
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.018
3145336SMITFLD
Solar/Wind Helper
0.047
3146456SLIGO L269
Solar/Wind Helper
0.116
971447AH1-217 GEN
Solar/Wind Harmer
3.888
270494AE1-108_GEN
Solar/Wind Harmer
2.594
270455AD2-022 GEN
Solar/Wind Harmer
1.322
270457AD2-023 GEN
Solar/Wind Harmer
0.671
3143316POE
Solar/Wind Helper
0.479
319010AE1-072 C
Solar/Wind Helper
1.315
316305AF2-043 C
Solar/Wind Helper
0.151
316217AC1-145 GEN
Solar/Wind Harmer
1.423
316197AC1-042 GEN
Solar/Wind Harmer
1.079
942671AE2-283 GEN
Solar/Wind Harmer
2.904
315821AE2-092 GEN
Solar/Wind Harmer
1.726
316036AC1-147 C
Solar/Wind Helper
0.188
3142956BIRDNECK
Solar/Wind Helper
0.083
316316AC1-027 C
Solar/Wind Helper
0.194
316185AD1-033 GEN
Solar/Wind Helper
0.577
3145506HICKORY
Solar/Wind Helper
0.484
3145506HICKORY
Solar/Wind Helper
0.29
3145506HICKORY
Solar/Wind Helper
0.073
316339AD2-160 GEN
Solar/Wind Helper
0.45
316018AA1-139 ULT2
Solar/Wind Helper
0.504
316017AA1-139 ULT1
Solar/Wind Helper
0.536
316236AE1-162_GEN
Solar/Wind Helper
0.157
3137176SLIGO L2192
Solar/Wind Helper
0.461
3130086AYDLETT
Solar/Wind Helper
0.459
CPLELTFEXP_CPLE->PJM
CLTF
2.619
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.946
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.989
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.34
MECLTFEXP_MEC->PJM
CLTF
1.478
SIGELTFEXP_SIGE->PJM
CLTF
0.046
NYPJM->LTFIMP_NY
CLTF
0.449
LGEELTFEXP_LGEE->PJM
CLTF
0.593
WECLTFEXP_WEC->PJM
CLTF
0.305
LAGNLTFEXP_LAGN->PJM
CLTF
2.389
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.942
TVALTFEXP_TVA->PJM
CLTF
1.22

Details for 6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.83 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:650.55
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
270494AE1-108_GEN
Solar/Wind Helper
2.768
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for 6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.27 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:635.93
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for 6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.84 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:767.78
MW Contribution:1.2
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:196.14 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1331.14
MW Contribution:0.56
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.57 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1515.37
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.57 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1515.34
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.31 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1455.08
MW Contribution:0.7
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.31 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1455.08
MW Contribution:0.7
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:162.3 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1101.51
MW Contribution:0.54
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151591KERR 2
50/50
0.202
970413AG2-270 GEN
50/50
9.029
966251AG1-494 GEN
50/50
1.716
970221AG2-151 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.218
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
0.818
971193AH1-056 GEN
Solar/Wind Harmer
15.872
963181AG1-167 GEN
Solar/Wind Harmer
0.975
959311AF2-222 GEN
Solar/Wind Harmer
17.841
970257AG2-171 GEN
Solar/Wind Harmer
6.184
972205AH1-687 GEN
50/50
27.249
3151611KERR 4
50/50
0.202
3151621KERR 5
50/50
0.202
3151631KERR 6
50/50
0.202
3151641KERR 7
50/50
0.202
3151541CLOVER2
50/50
2.059
971447AH1-217 GEN
Solar/Wind Harmer
15.037
971845AH1-439 GEN
Solar/Wind Harmer
20.916
970285AG2-188 GEN
Solar/Wind Harmer
35.131
270494AE1-108_GEN
Solar/Wind Harmer
5.032
315657AE1-056 GEN
Solar/Wind Harmer
8.99
946301AF1-294 GEN
Solar/Wind Harmer
4.808
961791AG1-021 GEN
Solar/Wind Harmer
2.339
970683AG2-441 GEN
Solar/Wind Harmer
14.613
970681AG2-440 GEN
Solar/Wind Harmer
11.691
3144303KENBRDG
Solar/Wind Harmer
0.154
971443AH1-215 GEN
Solar/Wind Harmer
3.209
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
315785AD2-033 C
Solar/Wind Harmer
1.488
958131AF2-107 GEN
Solar/Wind Harmer
4.835
964241AG1-285 GEN
Solar/Wind Harmer
10.382
316131AB2-060 GEN
Solar/Wind Harmer
0.438
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151601KERR 3
50/50
0.202
3151581KERR 1
50/50
0.072
3151531CLOVER1
50/50
2.069
3147043LAWRENC
50/50
0.777
970937AG2-583 GEN
Solar/Wind Harmer
36.866
316336AC2-165 C
Solar/Wind Harmer
0.024
972003AH1-546 GEN
Solar/Wind Harmer
24.522
971377AH1-170 GEN
Solar/Wind Harmer
5.701
3147623JAMES R
Solar/Wind Harmer
1.238
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.188
3146926FARMVIL
Solar/Wind Harmer
0.218
963171AG1-166 GEN
Solar/Wind Harmer
1.299
971563AH1-280 GEN
Solar/Wind Harmer
2.599
970685AG2-442 GEN
Solar/Wind Harmer
16.367
962491AG1-098 GEN
Solar/Wind Harmer
7.651
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.098
970401AG2-262 GEN
Solar/Wind Harmer
0.618
957481AF2-042 GEN
Solar/Wind Harmer
24.997
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.611
316129AC1-054 GEN
Solar/Wind Harmer
0.309
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
4.899
962751AG1-124 GEN
Solar/Wind Harmer
3.147
960081AF2-299 GEN
Solar/Wind Harmer
0.55
316118AC1-105 GEN
Solar/Wind Harmer
0.244
3147173SINAI
Solar/Wind Harmer
0.084
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.381
970865AG2-541 GEN
Solar/Wind Harmer
2.545
316123AC1-075 GEN
Solar/Wind Harmer
0.091
970165AG2-112 GEN
Solar/Wind Harmer
0.539
970163AG2-111 GEN
Solar/Wind Harmer
0.514
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
316478AD1-087 GEN
Solar/Wind Harmer
0.337
316486AD2-202 GEN
Solar/Wind Harmer
0.099
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.582
3147043LAWRENC
Solar/Wind Harmer
0.049
971683AH1-343 GEN
Solar/Wind Harmer
2.828
3132273ORANGE
Solar/Wind Helper
0.023
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
3152661PLYWOOD A
50/50
0.202
971489AH1-241 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
1.881
3146776BUCKING
Solar/Wind Harmer
0.152
315821AE2-092 GEN
Solar/Wind Harmer
0.02
970301AG2-198 GEN
Solar/Wind Harmer
11.214
3147133PAMPLIN
Solar/Wind Harmer
0.26
3147133PAMPLIN
Solar/Wind Harmer
0.208
958211AF2-115 GEN
Solar/Wind Harmer
2.924
963191AG1-168 GEN
Solar/Wind Harmer
0.975
971741AH1-377 GEN
Solar/Wind Harmer
22.982
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.246
971775AH1-396 GEN
Solar/Wind Harmer
0.309
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.277
964791AG1-342 GEN
Solar/Wind Harmer
2.024
3146843MT LREL
Solar/Wind Harmer
0.105
3146843MT LREL
Solar/Wind Harmer
0.105
939181AE1-148 GEN
Solar/Wind Harmer
5.007
970099AG2-077 GEN
Solar/Wind Harmer
9.999
970933AG2-581 GEN
Solar/Wind Harmer
5.154
942751AE2-291 GEN
Solar/Wind Harmer
3.374
966001AG1-469 GEN
Solar/Wind Helper
0.159
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.09 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1270.66
MW Contribution:0.71
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
970937AG2-583 GEN
Solar/Wind Harmer
48.541
316336AC2-165 C
Solar/Wind Harmer
11.736
972003AH1-546 GEN
Solar/Wind Harmer
32.342
971377AH1-170 GEN
Solar/Wind Harmer
7.506
3147623JAMES R
Solar/Wind Harmer
0.929
316322AB2-045
Solar/Wind Harmer
1.778
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
963171AG1-166 GEN
Solar/Wind Harmer
3.422
971563AH1-280 GEN
Solar/Wind Harmer
3.422
970685AG2-442 GEN
Solar/Wind Harmer
21.55
962491AG1-098 GEN
Solar/Wind Harmer
10.074
316237AB2-079_GEN
Solar/Wind Harmer
0.446
315693AD1-088 GEN
Solar/Wind Harmer
7.137
970401AG2-262 GEN
Solar/Wind Harmer
0.773
957481AF2-042 GEN
Solar/Wind Harmer
32.913
315687AD1-152 GEN
Solar/Wind Harmer
1.189
971065AG2-659 GEN
Solar/Wind Harmer
4.755
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.732
316003AC1-222 GEN
Solar/Wind Harmer
0.879
971795AH1-408 GEN
Solar/Wind Harmer
6.192
962751AG1-124 GEN
Solar/Wind Harmer
4.595
960081AF2-299 GEN
Solar/Wind Harmer
0.724
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
970221AG2-151 GEN
Solar/Wind Harmer
37.53
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.024
942461AE2-259 GEN
Solar/Wind Harmer
5.218
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
-0.092
971193AH1-056 GEN
Solar/Wind Harmer
18.305
963181AG1-167 GEN
Solar/Wind Harmer
2.566
959311AF2-222 GEN
Solar/Wind Harmer
23.538
970257AG2-171 GEN
Solar/Wind Harmer
8.143
315785AD2-033 C
Solar/Wind Harmer
4.66
958131AF2-107 GEN
Solar/Wind Harmer
6.437
964241AG1-285 GEN
Solar/Wind Harmer
13.669
316131AB2-060 GEN
Solar/Wind Harmer
1.687
316478AD1-087 GEN
Solar/Wind Harmer
0.939
316486AD2-202 GEN
Solar/Wind Harmer
0.275
316248AF1-058 C
Solar/Wind Harmer
0.284
960061AF2-297 GEN
Solar/Wind Harmer
4.717
3147043LAWRENC
Solar/Wind Harmer
-0.005
971683AH1-343 GEN
Solar/Wind Harmer
3.724
966621AG1-532 GEN
Solar/Wind Harmer
0.131
3132273ORANGE
Solar/Wind Helper
0.023
972205AH1-687 GEN
50/50
27.249
971447AH1-217 GEN
Solar/Wind Harmer
19.799
971845AH1-439 GEN
Solar/Wind Harmer
27.54
970285AG2-188 GEN
Solar/Wind Harmer
43.657
270494AE1-108_GEN
Solar/Wind Harmer
12.267
315657AE1-056 GEN
Solar/Wind Harmer
10.983
946301AF1-294 GEN
Solar/Wind Harmer
7.014
961791AG1-021 GEN
Solar/Wind Harmer
3.422
970683AG2-441 GEN
Solar/Wind Harmer
19.241
970681AG2-440 GEN
Solar/Wind Harmer
15.393
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.225
316239AB2-077_GEN
Solar/Wind Harmer
0.446
316238AB2-078_GEN
Solar/Wind Harmer
0.446
316118AC1-105 GEN
Solar/Wind Harmer
0.73
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.452
970865AG2-541 GEN
Solar/Wind Harmer
3.351
316123AC1-075 GEN
Solar/Wind Harmer
0.806
970165AG2-112 GEN
Solar/Wind Harmer
0.709
970163AG2-111 GEN
Solar/Wind Harmer
0.677
946281AF1-292 GEN
Solar/Wind Harmer
0.144
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
971489AH1-241 GEN
Solar/Wind Harmer
35.629
3146776BUCKING
Solar/Wind Harmer
-0.21
3146776BUCKING
Solar/Wind Harmer
-0.017
315821AE2-092 GEN
Solar/Wind Harmer
7.77
970301AG2-198 GEN
Solar/Wind Harmer
14.765
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.277
963191AG1-168 GEN
Solar/Wind Harmer
2.566
971741AH1-377 GEN
Solar/Wind Harmer
30.26
316034AC1-036 C
Solar/Wind Harmer
0.404
970323AG2-213 GEN
Solar/Wind Harmer
10.857
971775AH1-396 GEN
Solar/Wind Harmer
1.546
313527AB2-043 GEN
Solar/Wind Harmer
2.466
962561AG1-105 GEN
Solar/Wind Harmer
6.948
964791AG1-342 GEN
Solar/Wind Harmer
2.529
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
939181AE1-148 GEN
Solar/Wind Harmer
6.592
970099AG2-077 GEN
Solar/Wind Harmer
13.165
970933AG2-581 GEN
Solar/Wind Harmer
6.786
942751AE2-291 GEN
Solar/Wind Harmer
4.443
966001AG1-469 GEN
Solar/Wind Helper
0.159
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 39-91_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 39-91_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.33 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:990.47
MW Contribution:0.64
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.692
971447AH1-217 GEN
Solar/Wind Harmer
18.622
971845AH1-439 GEN
Solar/Wind Harmer
22.237
270494AE1-108_GEN
Solar/Wind Harmer
10.551
970285AG2-188 GEN
Solar/Wind Harmer
35.335
315657AE1-056 GEN
Solar/Wind Harmer
9.243
946301AF1-294 GEN
Solar/Wind Harmer
5.939
961791AG1-021 GEN
Solar/Wind Harmer
2.897
970683AG2-441 GEN
Solar/Wind Harmer
16.461
970681AG2-440 GEN
Solar/Wind Harmer
13.169
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.67
316239AB2-077_GEN
Solar/Wind Harmer
0.407
316238AB2-078_GEN
Solar/Wind Harmer
0.407
316118AC1-105 GEN
Solar/Wind Harmer
0.689
970831AG2-522 GEN
Solar/Wind Harmer
4.571
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.238
971281AH1-106 GEN
Solar/Wind Harmer
1.438
971283AH1-107 GEN
Solar/Wind Harmer
1.438
970865AG2-541 GEN
Solar/Wind Harmer
3.115
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.055
971967AH1-528 GEN
Solar/Wind Harmer
13.769
3137643SOCKMAN
Solar/Wind Harmer
-0.029
316123AC1-075 GEN
Solar/Wind Harmer
0.731
970165AG2-112 GEN
Solar/Wind Harmer
0.643
970163AG2-111 GEN
Solar/Wind Harmer
0.614
315607AA1-063A GEN
Solar/Wind Harmer
0.681
971285AH1-108 GEN
Adder
0.449
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
970085AG2-068 GEN
Solar/Wind Harmer
4.042
970581AG2-369 GEN
Solar/Wind Harmer
3.477
941031AE2-094 GEN
Solar/Wind Harmer
11.972
944011AF1-069 GEN
Solar/Wind Harmer
3.751
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.132
3148013FISHERV
Solar/Wind Helper
0.127
3148463FAIRFLD
Solar/Wind Helper
0.134
3144293JTRSVLE
50/50
0.697
3144293JTRSVLE
50/50
0.587
971489AH1-241 GEN
Solar/Wind Harmer
30.786
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.481
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.621
963191AG1-168 GEN
Solar/Wind Harmer
2.173
971741AH1-377 GEN
Solar/Wind Harmer
25.942
3151921BEARGRDN G2
50/50
4.448
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.416
971775AH1-396 GEN
Solar/Wind Harmer
1.341
313527AB2-043 GEN
Solar/Wind Harmer
2.245
962561AG1-105 GEN
Solar/Wind Harmer
6.444
939181AE1-148 GEN
Solar/Wind Harmer
6.287
964791AG1-342 GEN
Solar/Wind Harmer
2.356
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.272
971223AH1-071 GEN
Solar/Wind Harmer
1.326
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.828
316181AB2-040 GEN
Solar/Wind Harmer
1.022
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.794
3145593CAROLNA
Solar/Wind Harmer
0.059
3145783HORNRTN
Solar/Wind Harmer
0.823
3145783HORNRTN
Solar/Wind Harmer
0.658
3145783HORNRTN
Solar/Wind Harmer
0.206
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.692
972187AH1-678 GEN
Adder
1.699
972185AH1-677 GEN
Adder
3.299
966001AG1-469 GEN
Solar/Wind Helper
0.187
3132123MT JACKSON
Solar/Wind Helper
0.368
3144293JTRSVLE
50/50
0.697
970221AG2-151 GEN
Solar/Wind Harmer
32.428
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.331
316313AB2-026
Solar/Wind Harmer
0.751
316258AE1-075 C
Solar/Wind Harmer
0.676
316405AF2-144 C
Solar/Wind Harmer
0.713
3143336POWHATN
Solar/Wind Harmer
2.809
970909AG2-566 GEN
Solar/Wind Harmer
2.37
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.405
963181AG1-167 GEN
Solar/Wind Harmer
2.173
959311AF2-222 GEN
Solar/Wind Harmer
20.328
970257AG2-171 GEN
Solar/Wind Harmer
7.062
315785AD2-033 C
Solar/Wind Harmer
4.068
958131AF2-107 GEN
Solar/Wind Harmer
5.359
964241AG1-285 GEN
Solar/Wind Harmer
12.184
316131AB2-060 GEN
Solar/Wind Harmer
1.528
316478AD1-087 GEN
Solar/Wind Harmer
0.928
316486AD2-202 GEN
Solar/Wind Harmer
0.272
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.272
960061AF2-297 GEN
Solar/Wind Harmer
4.511
971683AH1-343 GEN
Solar/Wind Harmer
3.497
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.589
3150861SPRUNCD
Adder
0.274
970917AG2-570 GEN
Solar/Wind Harmer
16.228
316365GEN2_N
Solar/Wind Harmer
0.43
3148013FISHERV
Solar/Wind Helper
0.221
316499AE2-029_GEN
Solar/Wind Helper
0.571
315616AA1-038_C
Solar/Wind Helper
0.608
3132273ORANGE
Solar/Wind Helper
0.026
3151931BEARGRDN S1
50/50
5.74
3151911BEARGRDN G1
50/50
4.448
3144293JTRSVLE
50/50
0.697
971377AH1-170 GEN
Solar/Wind Harmer
6.486
3147623JAMES R
Solar/Wind Harmer
0.803
972003AH1-546 GEN
Solar/Wind Harmer
25.797
970937AG2-583 GEN
Solar/Wind Harmer
31.587
316322AB2-045
Solar/Wind Harmer
1.434
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.623
3143336POWHATN
Solar/Wind Harmer
3.304
963171AG1-166 GEN
Solar/Wind Harmer
2.897
971563AH1-280 GEN
Solar/Wind Harmer
2.897
970685AG2-442 GEN
Solar/Wind Harmer
18.436
962491AG1-098 GEN
Solar/Wind Harmer
9.378
316237AB2-079_GEN
Solar/Wind Harmer
0.407
315693AD1-088 GEN
Solar/Wind Harmer
6.713
970401AG2-262 GEN
Solar/Wind Harmer
0.72
957481AF2-042 GEN
Solar/Wind Harmer
33.181
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.173
971065AG2-659 GEN
Solar/Wind Harmer
4.785
3147043LAWRENC
Adder
0.762
316129AC1-054 GEN
Solar/Wind Harmer
0.821
971795AH1-408 GEN
Solar/Wind Harmer
6.648
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.833
960081AF2-299 GEN
Solar/Wind Harmer
0.851
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.274
970919AG2-571 GEN
Solar/Wind Harmer
2.054
970087AG2-069 GEN
Solar/Wind Harmer
6.064
316023GEN1_S
Solar/Wind Harmer
0.43
3147983MERCK5
Solar/Wind Helper
0.062
CPLELTFEXP_CPLE->PJM
CLTF
3.247
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.539
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.798
MECLTFEXP_MEC->PJM
CLTF
0.142
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.409
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.087
LAGNLTFEXP_LAGN->PJM
CLTF
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.305
TVALTFEXP_TVA->PJM
CLTF
0.589

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P2-2: DOOMS B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: DOOMS B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.39 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:974.31
MW Contribution:0.64
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.676
971447AH1-217 GEN
Solar/Wind Harmer
18.608
971845AH1-439 GEN
Solar/Wind Harmer
22.218
270494AE1-108_GEN
Solar/Wind Harmer
10.541
970285AG2-188 GEN
Solar/Wind Harmer
35.303
315657AE1-056 GEN
Solar/Wind Harmer
9.23
946301AF1-294 GEN
Solar/Wind Harmer
5.931
961791AG1-021 GEN
Solar/Wind Harmer
2.893
970683AG2-441 GEN
Solar/Wind Harmer
16.436
970681AG2-440 GEN
Solar/Wind Harmer
13.149
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.664
316239AB2-077_GEN
Solar/Wind Harmer
0.406
316238AB2-078_GEN
Solar/Wind Harmer
0.406
316118AC1-105 GEN
Solar/Wind Harmer
0.687
970831AG2-522 GEN
Solar/Wind Harmer
4.556
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.237
971281AH1-106 GEN
Solar/Wind Harmer
1.433
971283AH1-107 GEN
Solar/Wind Harmer
1.433
970865AG2-541 GEN
Solar/Wind Harmer
3.104
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.051
971967AH1-528 GEN
Solar/Wind Harmer
13.715
3137643SOCKMAN
Solar/Wind Harmer
-0.028
316123AC1-075 GEN
Solar/Wind Harmer
0.728
970165AG2-112 GEN
Solar/Wind Harmer
0.641
970163AG2-111 GEN
Solar/Wind Harmer
0.611
315607AA1-063A GEN
Solar/Wind Harmer
0.678
971285AH1-108 GEN
Adder
0.447
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.659
970673AG2-436 GEN
Solar/Wind Harmer
6.916
970085AG2-068 GEN
Solar/Wind Harmer
4.024
970581AG2-369 GEN
Solar/Wind Harmer
3.461
941031AE2-094 GEN
Solar/Wind Harmer
11.918
944011AF1-069 GEN
Solar/Wind Harmer
3.734
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.136
3148013FISHERV
Solar/Wind Helper
0.13
3148463FAIRFLD
Solar/Wind Helper
0.135
3144293JTRSVLE
50/50
0.696
3144293JTRSVLE
50/50
0.586
315821AE2-092 GEN
Solar/Wind Harmer
10.863
971489AH1-241 GEN
Solar/Wind Harmer
30.763
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.465
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.616
963191AG1-168 GEN
Solar/Wind Harmer
2.17
971741AH1-377 GEN
Solar/Wind Harmer
25.905
316034AC1-036 C
Solar/Wind Harmer
0.349
970323AG2-213 GEN
Solar/Wind Harmer
9.401
971775AH1-396 GEN
Solar/Wind Harmer
1.339
313527AB2-043 GEN
Solar/Wind Harmer
2.24
962561AG1-105 GEN
Solar/Wind Harmer
6.427
939181AE1-148 GEN
Solar/Wind Harmer
6.27
964791AG1-342 GEN
Solar/Wind Harmer
2.35
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.235
971223AH1-071 GEN
Solar/Wind Harmer
1.322
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.8
316181AB2-040 GEN
Solar/Wind Harmer
1.018
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.791
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.819
3145783HORNRTN
Solar/Wind Harmer
0.655
3145783HORNRTN
Solar/Wind Harmer
0.205
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.689
972187AH1-678 GEN
Adder
1.691
972185AH1-677 GEN
Adder
3.285
966001AG1-469 GEN
Solar/Wind Helper
0.188
3132123MT JACKSON
Solar/Wind Helper
0.367
3151921BEARGRDN G2
50/50
4.444
3144293JTRSVLE
50/50
0.696
970221AG2-151 GEN
Solar/Wind Harmer
32.404
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.326
316313AB2-026
Solar/Wind Harmer
0.75
316258AE1-075 C
Solar/Wind Harmer
0.675
316405AF2-144 C
Solar/Wind Harmer
0.712
3143336POWHATN
Solar/Wind Harmer
2.805
970909AG2-566 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.384
963181AG1-167 GEN
Solar/Wind Harmer
2.17
959311AF2-222 GEN
Solar/Wind Harmer
20.295
970257AG2-171 GEN
Solar/Wind Harmer
7.05
315785AD2-033 C
Solar/Wind Harmer
4.061
958131AF2-107 GEN
Solar/Wind Harmer
5.349
964241AG1-285 GEN
Solar/Wind Harmer
12.16
316131AB2-060 GEN
Solar/Wind Harmer
1.525
316478AD1-087 GEN
Solar/Wind Harmer
0.925
316486AD2-202 GEN
Solar/Wind Harmer
0.271
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.271
960061AF2-297 GEN
Solar/Wind Harmer
4.496
971683AH1-343 GEN
Solar/Wind Harmer
3.484
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.586
3150861SPRUNCD
Adder
0.273
970917AG2-570 GEN
Solar/Wind Harmer
16.156
316365GEN2_N
Solar/Wind Harmer
0.428
3148013FISHERV
Solar/Wind Helper
0.227
316499AE2-029_GEN
Solar/Wind Helper
0.572
315616AA1-038_C
Solar/Wind Helper
0.611
3132273ORANGE
Solar/Wind Helper
0.026
3151931BEARGRDN S1
50/50
5.736
3151911BEARGRDN G1
50/50
4.444
3144293JTRSVLE
50/50
0.696
971377AH1-170 GEN
Solar/Wind Harmer
6.481
3147623JAMES R
Solar/Wind Harmer
0.802
972003AH1-546 GEN
Solar/Wind Harmer
25.777
970937AG2-583 GEN
Solar/Wind Harmer
31.56
316322AB2-045
Solar/Wind Harmer
1.433
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.617
3143336POWHATN
Solar/Wind Harmer
3.3
963171AG1-166 GEN
Solar/Wind Harmer
2.893
971563AH1-280 GEN
Solar/Wind Harmer
2.893
970685AG2-442 GEN
Solar/Wind Harmer
18.409
962491AG1-098 GEN
Solar/Wind Harmer
9.357
316237AB2-079_GEN
Solar/Wind Harmer
0.406
315693AD1-088 GEN
Solar/Wind Harmer
6.698
970401AG2-262 GEN
Solar/Wind Harmer
0.718
957481AF2-042 GEN
Solar/Wind Harmer
33.088
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.169
971065AG2-659 GEN
Solar/Wind Harmer
4.77
3147043LAWRENC
Adder
0.76
316129AC1-054 GEN
Solar/Wind Harmer
0.818
971795AH1-408 GEN
Solar/Wind Harmer
6.626
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.83
960081AF2-299 GEN
Solar/Wind Harmer
0.847
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.273
970919AG2-571 GEN
Solar/Wind Harmer
2.045
970087AG2-069 GEN
Solar/Wind Harmer
6.037
316023GEN1_S
Solar/Wind Harmer
0.428
3147983MERCK5
Solar/Wind Helper
0.063
CPLELTFEXP_CPLE->PJM
CLTF
3.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.302
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.731
MECLTFEXP_MEC->PJM
CLTF
0.113
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.42
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.046
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.122
LAGNLTFEXP_LAGN->PJM
CLTF
1.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.249
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.571

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.5 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:933.78
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.655
3144293JTRSVLE
50/50
0.551
971489AH1-241 GEN
Solar/Wind Harmer
26.337
3146776BUCKING
Solar/Wind Harmer
-0.158
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.386
970301AG2-198 GEN
Solar/Wind Harmer
11.705
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.404
963191AG1-168 GEN
Solar/Wind Harmer
2.042
971741AH1-377 GEN
Solar/Wind Harmer
24.381
316034AC1-036 C
Solar/Wind Harmer
0.331
970323AG2-213 GEN
Solar/Wind Harmer
8.895
971775AH1-396 GEN
Solar/Wind Harmer
1.267
313527AB2-043 GEN
Solar/Wind Harmer
2.141
962561AG1-105 GEN
Solar/Wind Harmer
6.187
939181AE1-148 GEN
Solar/Wind Harmer
6.061
964791AG1-342 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
12.748
971223AH1-071 GEN
Solar/Wind Harmer
1.248
3143526WINTERP
Solar/Wind Harmer
-0.043
970933AG2-581 GEN
Solar/Wind Harmer
7.571
316181AB2-040 GEN
Solar/Wind Harmer
1.004
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.784
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.814
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.204
3145783HORNRTN
Solar/Wind Harmer
0.081
316426AA2-053 GEN
Solar/Wind Harmer
0.684
972187AH1-678 GEN
Adder
1.664
972185AH1-677 GEN
Adder
3.229
966001AG1-469 GEN
Solar/Wind Helper
0.189
972205AH1-687 GEN
50/50
20.143
971447AH1-217 GEN
Solar/Wind Harmer
14.529
971845AH1-439 GEN
Solar/Wind Harmer
20.7
970285AG2-188 GEN
Solar/Wind Harmer
32.906
270494AE1-108_GEN
Solar/Wind Harmer
9.015
315657AE1-056 GEN
Solar/Wind Harmer
8.675
946301AF1-294 GEN
Solar/Wind Harmer
5.582
961791AG1-021 GEN
Solar/Wind Harmer
2.723
970683AG2-441 GEN
Solar/Wind Harmer
15.505
970681AG2-440 GEN
Solar/Wind Harmer
12.404
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.467
316239AB2-077_GEN
Solar/Wind Harmer
0.389
316238AB2-078_GEN
Solar/Wind Harmer
0.389
316118AC1-105 GEN
Solar/Wind Harmer
0.665
970831AG2-522 GEN
Solar/Wind Harmer
4.449
3147173SINAI
Solar/Wind Harmer
-0.009
3151931BEARGRDN S1
50/50
5.33
3151911BEARGRDN G1
50/50
4.13
3144293JTRSVLE
50/50
0.655
972003AH1-546 GEN
Solar/Wind Harmer
23.962
971377AH1-170 GEN
Solar/Wind Harmer
5.548
3147623JAMES R
Solar/Wind Harmer
0.687
970937AG2-583 GEN
Solar/Wind Harmer
29.352
316322AB2-045
Solar/Wind Harmer
1.334
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.233
3143336POWHATN
Solar/Wind Harmer
3.078
963171AG1-166 GEN
Solar/Wind Harmer
2.723
971563AH1-280 GEN
Solar/Wind Harmer
2.723
970685AG2-442 GEN
Solar/Wind Harmer
17.365
962491AG1-098 GEN
Solar/Wind Harmer
8.919
316237AB2-079_GEN
Solar/Wind Harmer
0.389
315693AD1-088 GEN
Solar/Wind Harmer
6.394
970401AG2-262 GEN
Solar/Wind Harmer
0.692
957481AF2-042 GEN
Solar/Wind Harmer
31.87
3143226MDLTHAN
Solar/Wind Harmer
-0.01
315687AD1-152 GEN
Solar/Wind Harmer
1.137
971065AG2-659 GEN
Solar/Wind Harmer
4.648
3147043LAWRENC
Adder
0.737
316129AC1-054 GEN
Solar/Wind Harmer
0.798
971795AH1-408 GEN
Solar/Wind Harmer
6.453
3143526WINTERP
Solar/Wind Harmer
-0.043
316003AC1-222 GEN
Solar/Wind Harmer
0.805
960081AF2-299 GEN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.083
970919AG2-571 GEN
Solar/Wind Harmer
2.03
970087AG2-069 GEN
Solar/Wind Harmer
6
3150851SPRUNCC
Adder
0.261
3147983MERCK5
Solar/Wind Helper
0.055
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Harmer
0.225
971281AH1-106 GEN
Solar/Wind Harmer
1.359
971283AH1-107 GEN
Solar/Wind Harmer
1.359
946281AF1-292 GEN
Solar/Wind Harmer
0.166
970865AG2-541 GEN
Solar/Wind Harmer
2.988
316087AB2-174 GEN
Solar/Wind Harmer
1.035
971967AH1-528 GEN
Solar/Wind Harmer
13.383
3137643SOCKMAN
Solar/Wind Harmer
-0.028
315607AA1-063A GEN
Solar/Wind Harmer
0.672
3146043SEABORD
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.694
970165AG2-112 GEN
Solar/Wind Harmer
0.611
970163AG2-111 GEN
Solar/Wind Harmer
0.583
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
970673AG2-436 GEN
Solar/Wind Harmer
13.415
970673AG2-436 GEN
Solar/Wind Harmer
6.792
971285AH1-108 GEN
Adder
0.428
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.12
3151921BEARGRDN G2
50/50
4.13
3144293JTRSVLE
50/50
0.655
970221AG2-151 GEN
Solar/Wind Harmer
27.742
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.053
316313AB2-026
Solar/Wind Harmer
0.699
316258AE1-075 C
Solar/Wind Harmer
0.63
316405AF2-144 C
Solar/Wind Harmer
0.664
3143336POWHATN
Solar/Wind Harmer
2.616
970909AG2-566 GEN
Solar/Wind Harmer
2.223
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.459
963181AG1-167 GEN
Solar/Wind Harmer
2.042
959311AF2-222 GEN
Solar/Wind Harmer
19.185
970257AG2-171 GEN
Solar/Wind Harmer
6.671
315785AD2-033 C
Solar/Wind Harmer
3.847
964241AG1-285 GEN
Solar/Wind Harmer
11.573
316131AB2-060 GEN
Solar/Wind Harmer
1.457
958131AF2-107 GEN
Solar/Wind Harmer
4.54
316478AD1-087 GEN
Solar/Wind Harmer
0.893
316486AD2-202 GEN
Solar/Wind Harmer
0.261
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.376
971683AH1-343 GEN
Solar/Wind Harmer
3.368
966621AG1-532 GEN
Solar/Wind Harmer
0.15
313506AB2-031 GEN
Solar/Wind Harmer
0.578
970917AG2-570 GEN
Solar/Wind Harmer
16.041
3150861SPRUNCD
Adder
0.261
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.545
CPLELTFEXP_CPLE->PJM
CLTF
3.638
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.961
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.309
MECLTFEXP_MEC->PJM
CLTF
0.208
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.389
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.045
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.115
LAGNLTFEXP_LAGN->PJM
CLTF
1.574
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.039
TVALTFEXP_TVA->PJM
CLTF
0.757

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.37 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:899.48
MW Contribution:0.6
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
19.851
971447AH1-217 GEN
Solar/Wind Harmer
14.274
971845AH1-439 GEN
Solar/Wind Harmer
20.334
970285AG2-188 GEN
Solar/Wind Harmer
32.307
270494AE1-108_GEN
Solar/Wind Harmer
8.922
315657AE1-056 GEN
Solar/Wind Harmer
8.438
946301AF1-294 GEN
Solar/Wind Harmer
5.421
961791AG1-021 GEN
Solar/Wind Harmer
2.645
970683AG2-441 GEN
Solar/Wind Harmer
15.022
970681AG2-440 GEN
Solar/Wind Harmer
12.017
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.347
316239AB2-077_GEN
Solar/Wind Harmer
0.371
316238AB2-078_GEN
Solar/Wind Harmer
0.371
316118AC1-105 GEN
Solar/Wind Harmer
0.63
970831AG2-522 GEN
Solar/Wind Harmer
4.14
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Harmer
0.21
971281AH1-106 GEN
Solar/Wind Harmer
1.27
971283AH1-107 GEN
Solar/Wind Harmer
1.27
3144293JTRSVLE
50/50
0.636
3144293JTRSVLE
50/50
0.536
971489AH1-241 GEN
Solar/Wind Harmer
25.934
3146776BUCKING
Solar/Wind Harmer
-0.155
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.214
970301AG2-198 GEN
Solar/Wind Harmer
11.385
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.306
963191AG1-168 GEN
Solar/Wind Harmer
1.983
971741AH1-377 GEN
Solar/Wind Harmer
23.646
316034AC1-036 C
Solar/Wind Harmer
0.319
970323AG2-213 GEN
Solar/Wind Harmer
8.59
971775AH1-396 GEN
Solar/Wind Harmer
1.223
313527AB2-043 GEN
Solar/Wind Harmer
2.045
962561AG1-105 GEN
Solar/Wind Harmer
5.883
939181AE1-148 GEN
Solar/Wind Harmer
5.719
964791AG1-342 GEN
Solar/Wind Harmer
2.152
3146843MT LREL
Solar/Wind Harmer
-0.01
3146843MT LREL
Solar/Wind Harmer
-0.01
970099AG2-077 GEN
Solar/Wind Harmer
11.998
971223AH1-071 GEN
Solar/Wind Harmer
1.179
3143526WINTERP
Solar/Wind Harmer
-0.04
970933AG2-581 GEN
Solar/Wind Harmer
7.011
3151921BEARGRDN G2
50/50
4.07
3144293JTRSVLE
50/50
0.636
970221AG2-151 GEN
Solar/Wind Harmer
27.317
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.018
942461AE2-259 GEN
Solar/Wind Harmer
3.955
316313AB2-026
Solar/Wind Harmer
0.683
316258AE1-075 C
Solar/Wind Harmer
0.615
316405AF2-144 C
Solar/Wind Harmer
0.649
3143336POWHATN
Solar/Wind Harmer
2.554
970909AG2-566 GEN
Solar/Wind Harmer
2.162
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.064
963181AG1-167 GEN
Solar/Wind Harmer
1.983
959311AF2-222 GEN
Solar/Wind Harmer
18.545
970257AG2-171 GEN
Solar/Wind Harmer
6.442
315785AD2-033 C
Solar/Wind Harmer
3.71
964241AG1-285 GEN
Solar/Wind Harmer
11.106
958131AF2-107 GEN
Solar/Wind Harmer
4.655
316131AB2-060 GEN
Solar/Wind Harmer
1.393
316478AD1-087 GEN
Solar/Wind Harmer
0.841
316486AD2-202 GEN
Solar/Wind Harmer
0.246
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.249
960061AF2-297 GEN
Solar/Wind Harmer
4.131
3151931BEARGRDN S1
50/50
5.253
3151911BEARGRDN G1
50/50
4.07
3144293JTRSVLE
50/50
0.636
972003AH1-546 GEN
Solar/Wind Harmer
23.604
971377AH1-170 GEN
Solar/Wind Harmer
5.463
3147623JAMES R
Solar/Wind Harmer
0.676
970937AG2-583 GEN
Solar/Wind Harmer
28.861
316322AB2-045
Solar/Wind Harmer
1.311
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
5.122
3143336POWHATN
Solar/Wind Harmer
3.004
963171AG1-166 GEN
Solar/Wind Harmer
2.645
971563AH1-280 GEN
Solar/Wind Harmer
2.645
970685AG2-442 GEN
Solar/Wind Harmer
16.824
962491AG1-098 GEN
Solar/Wind Harmer
8.511
316237AB2-079_GEN
Solar/Wind Harmer
0.371
315693AD1-088 GEN
Solar/Wind Harmer
6.09
970401AG2-262 GEN
Solar/Wind Harmer
0.658
957481AF2-042 GEN
Solar/Wind Harmer
29.994
3143226MDLTHAN
Solar/Wind Harmer
-0.009
315687AD1-152 GEN
Solar/Wind Harmer
1.066
971065AG2-659 GEN
Solar/Wind Harmer
4.339
3147043LAWRENC
Adder
0.688
316129AC1-054 GEN
Solar/Wind Harmer
0.744
971795AH1-408 GEN
Solar/Wind Harmer
5.995
316003AC1-222 GEN
Solar/Wind Harmer
0.766
3143526WINTERP
Solar/Wind Harmer
-0.04
971683AH1-343 GEN
Solar/Wind Harmer
3.224
966621AG1-532 GEN
Solar/Wind Harmer
0.138
313506AB2-031 GEN
Solar/Wind Harmer
0.528
316499AE2-029_GEN
Solar/Wind Helper
0.551
3148013FISHERV
Solar/Wind Helper
0.152
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.264
960081AF2-299 GEN
Solar/Wind Harmer
0.763
3147983MERCK5
Solar/Wind Helper
0.06
316192AB2-158 GEN
Solar/Wind Helper
0.803
3147666LOUISA
Solar/Wind Helper
0.46
316181AB2-040 GEN
Solar/Wind Harmer
0.917
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.713
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.2
3132123MT JACKSON
Solar/Wind Helper
0.351
970865AG2-541 GEN
Solar/Wind Harmer
2.883
946281AF1-292 GEN
Solar/Wind Harmer
0.152
316087AB2-174 GEN
Solar/Wind Harmer
0.947
971967AH1-528 GEN
Solar/Wind Harmer
12.263
3137643SOCKMAN
Solar/Wind Harmer
-0.026
316123AC1-075 GEN
Solar/Wind Harmer
0.683
970165AG2-112 GEN
Solar/Wind Harmer
0.601
970163AG2-111 GEN
Solar/Wind Harmer
0.573
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.091
3148013FISHERV
Solar/Wind Helper
0.088
CPLELTFEXP_CPLE->PJM
CLTF
3.029
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.957
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.668
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.188
MECLTFEXP_MEC->PJM
CLTF
0.344
SIGELTFEXP_SIGE->PJM
CLTF
0.009
NYPJM->LTFIMP_NY
CLTF
0.444
LGEELTFEXP_LGEE->PJM
CLTF
0.079
WECLTFEXP_WEC->PJM
CLTF
0.033
LAGNLTFEXP_LAGN->PJM
CLTF
1.383
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.08
TVALTFEXP_TVA->PJM
CLTF
0.685

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:198.54 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1313.88
MW Contribution:0.56
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.18 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1498.1
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.18 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1498.08
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:177.73 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1437.82
MW Contribution:0.7
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:177.73 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1437.82
MW Contribution:0.7
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:163.84 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1084.23
MW Contribution:0.54
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151601KERR 3
50/50
0.202
3151581KERR 1
50/50
0.072
3151531CLOVER1
50/50
2.069
972205AH1-687 GEN
50/50
27.249
3151611KERR 4
50/50
0.202
3151621KERR 5
50/50
0.202
3151631KERR 6
50/50
0.202
3151641KERR 7
50/50
0.202
3151541CLOVER2
50/50
2.059
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151591KERR 2
50/50
0.202
970413AG2-270 GEN
50/50
9.029
966251AG1-494 GEN
50/50
1.716
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
3152661PLYWOOD A
50/50
0.202
970221AG2-151 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.218
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
0.818
971193AH1-056 GEN
Solar/Wind Harmer
15.872
963181AG1-167 GEN
Solar/Wind Harmer
0.975
959311AF2-222 GEN
Solar/Wind Harmer
17.841
970257AG2-171 GEN
Solar/Wind Harmer
6.184
315785AD2-033 C
Solar/Wind Harmer
1.488
958131AF2-107 GEN
Solar/Wind Harmer
4.835
964241AG1-285 GEN
Solar/Wind Harmer
10.382
316131AB2-060 GEN
Solar/Wind Harmer
0.438
316478AD1-087 GEN
Solar/Wind Harmer
0.337
316486AD2-202 GEN
Solar/Wind Harmer
0.099
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.582
3147043LAWRENC
Solar/Wind Harmer
0.049
971683AH1-343 GEN
Solar/Wind Harmer
2.828
3132273ORANGE
Solar/Wind Helper
0.023
971489AH1-241 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
1.881
3146776BUCKING
Solar/Wind Harmer
0.152
315821AE2-092 GEN
Solar/Wind Harmer
0.02
970301AG2-198 GEN
Solar/Wind Harmer
11.214
3147133PAMPLIN
Solar/Wind Harmer
0.26
3147133PAMPLIN
Solar/Wind Harmer
0.208
958211AF2-115 GEN
Solar/Wind Harmer
2.924
963191AG1-168 GEN
Solar/Wind Harmer
0.975
971741AH1-377 GEN
Solar/Wind Harmer
22.982
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.246
971775AH1-396 GEN
Solar/Wind Harmer
0.309
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.277
964791AG1-342 GEN
Solar/Wind Harmer
2.024
3146843MT LREL
Solar/Wind Harmer
0.105
3146843MT LREL
Solar/Wind Harmer
0.105
939181AE1-148 GEN
Solar/Wind Harmer
5.007
970099AG2-077 GEN
Solar/Wind Harmer
9.999
970933AG2-581 GEN
Solar/Wind Harmer
5.154
942751AE2-291 GEN
Solar/Wind Harmer
3.374
966001AG1-469 GEN
Solar/Wind Helper
0.159
3147043LAWRENC
50/50
0.777
970937AG2-583 GEN
Solar/Wind Harmer
36.866
316336AC2-165 C
Solar/Wind Harmer
0.024
972003AH1-546 GEN
Solar/Wind Harmer
24.522
971377AH1-170 GEN
Solar/Wind Harmer
5.701
971447AH1-217 GEN
Solar/Wind Harmer
15.037
971845AH1-439 GEN
Solar/Wind Harmer
20.916
970285AG2-188 GEN
Solar/Wind Harmer
35.131
270494AE1-108_GEN
Solar/Wind Harmer
5.032
315657AE1-056 GEN
Solar/Wind Harmer
8.99
946301AF1-294 GEN
Solar/Wind Harmer
4.808
961791AG1-021 GEN
Solar/Wind Harmer
2.339
970683AG2-441 GEN
Solar/Wind Harmer
14.613
970681AG2-440 GEN
Solar/Wind Harmer
11.691
3144303KENBRDG
Solar/Wind Harmer
0.154
971443AH1-215 GEN
Solar/Wind Harmer
3.209
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.244
3147173SINAI
Solar/Wind Harmer
0.084
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.381
970865AG2-541 GEN
Solar/Wind Harmer
2.545
316123AC1-075 GEN
Solar/Wind Harmer
0.091
970165AG2-112 GEN
Solar/Wind Harmer
0.539
970163AG2-111 GEN
Solar/Wind Harmer
0.514
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3147623JAMES R
Solar/Wind Harmer
1.238
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.188
3146926FARMVIL
Solar/Wind Harmer
0.218
963171AG1-166 GEN
Solar/Wind Harmer
1.299
971563AH1-280 GEN
Solar/Wind Harmer
2.599
970685AG2-442 GEN
Solar/Wind Harmer
16.367
962491AG1-098 GEN
Solar/Wind Harmer
7.651
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.098
970401AG2-262 GEN
Solar/Wind Harmer
0.618
957481AF2-042 GEN
Solar/Wind Harmer
24.997
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.611
316129AC1-054 GEN
Solar/Wind Harmer
0.309
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
4.899
962751AG1-124 GEN
Solar/Wind Harmer
3.147
960081AF2-299 GEN
Solar/Wind Harmer
0.55
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.93 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1253.38
MW Contribution:0.71
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
972205AH1-687 GEN
50/50
27.249
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
970221AG2-151 GEN
Solar/Wind Harmer
37.53
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.024
942461AE2-259 GEN
Solar/Wind Harmer
5.218
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
-0.092
971193AH1-056 GEN
Solar/Wind Harmer
18.305
963181AG1-167 GEN
Solar/Wind Harmer
2.566
959311AF2-222 GEN
Solar/Wind Harmer
23.538
970257AG2-171 GEN
Solar/Wind Harmer
8.143
315785AD2-033 C
Solar/Wind Harmer
4.66
958131AF2-107 GEN
Solar/Wind Harmer
6.437
964241AG1-285 GEN
Solar/Wind Harmer
13.669
316131AB2-060 GEN
Solar/Wind Harmer
1.687
316478AD1-087 GEN
Solar/Wind Harmer
0.939
316486AD2-202 GEN
Solar/Wind Harmer
0.275
316248AF1-058 C
Solar/Wind Harmer
0.284
960061AF2-297 GEN
Solar/Wind Harmer
4.717
3147043LAWRENC
Solar/Wind Harmer
-0.005
971683AH1-343 GEN
Solar/Wind Harmer
3.724
966621AG1-532 GEN
Solar/Wind Harmer
0.131
3132273ORANGE
Solar/Wind Helper
0.023
970937AG2-583 GEN
Solar/Wind Harmer
48.541
316336AC2-165 C
Solar/Wind Harmer
11.736
972003AH1-546 GEN
Solar/Wind Harmer
32.342
971377AH1-170 GEN
Solar/Wind Harmer
7.506
3147623JAMES R
Solar/Wind Harmer
0.929
316322AB2-045
Solar/Wind Harmer
1.778
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
963171AG1-166 GEN
Solar/Wind Harmer
3.422
971563AH1-280 GEN
Solar/Wind Harmer
3.422
970685AG2-442 GEN
Solar/Wind Harmer
21.55
962491AG1-098 GEN
Solar/Wind Harmer
10.074
316237AB2-079_GEN
Solar/Wind Harmer
0.446
315693AD1-088 GEN
Solar/Wind Harmer
7.137
970401AG2-262 GEN
Solar/Wind Harmer
0.773
957481AF2-042 GEN
Solar/Wind Harmer
32.913
315687AD1-152 GEN
Solar/Wind Harmer
1.189
971065AG2-659 GEN
Solar/Wind Harmer
4.755
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.732
316003AC1-222 GEN
Solar/Wind Harmer
0.879
971795AH1-408 GEN
Solar/Wind Harmer
6.192
962751AG1-124 GEN
Solar/Wind Harmer
4.595
960081AF2-299 GEN
Solar/Wind Harmer
0.724
970535AG2-341 GEN
50/50
2.047
971489AH1-241 GEN
Solar/Wind Harmer
35.629
3146776BUCKING
Solar/Wind Harmer
-0.21
3146776BUCKING
Solar/Wind Harmer
-0.017
315821AE2-092 GEN
Solar/Wind Harmer
7.77
970301AG2-198 GEN
Solar/Wind Harmer
14.765
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.277
963191AG1-168 GEN
Solar/Wind Harmer
2.566
971741AH1-377 GEN
Solar/Wind Harmer
30.26
316034AC1-036 C
Solar/Wind Harmer
0.404
970323AG2-213 GEN
Solar/Wind Harmer
10.857
971775AH1-396 GEN
Solar/Wind Harmer
1.546
313527AB2-043 GEN
Solar/Wind Harmer
2.466
962561AG1-105 GEN
Solar/Wind Harmer
6.948
964791AG1-342 GEN
Solar/Wind Harmer
2.529
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
939181AE1-148 GEN
Solar/Wind Harmer
6.592
970099AG2-077 GEN
Solar/Wind Harmer
13.165
970933AG2-581 GEN
Solar/Wind Harmer
6.786
942751AE2-291 GEN
Solar/Wind Harmer
4.443
966001AG1-469 GEN
Solar/Wind Helper
0.159
971447AH1-217 GEN
Solar/Wind Harmer
19.799
971845AH1-439 GEN
Solar/Wind Harmer
27.54
970285AG2-188 GEN
Solar/Wind Harmer
43.657
270494AE1-108_GEN
Solar/Wind Harmer
12.267
315657AE1-056 GEN
Solar/Wind Harmer
10.983
946301AF1-294 GEN
Solar/Wind Harmer
7.014
961791AG1-021 GEN
Solar/Wind Harmer
3.422
970683AG2-441 GEN
Solar/Wind Harmer
19.241
970681AG2-440 GEN
Solar/Wind Harmer
15.393
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.225
316239AB2-077_GEN
Solar/Wind Harmer
0.446
316238AB2-078_GEN
Solar/Wind Harmer
0.446
316118AC1-105 GEN
Solar/Wind Harmer
0.73
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.452
970865AG2-541 GEN
Solar/Wind Harmer
3.351
316123AC1-075 GEN
Solar/Wind Harmer
0.806
970165AG2-112 GEN
Solar/Wind Harmer
0.709
970163AG2-111 GEN
Solar/Wind Harmer
0.677
946281AF1-292 GEN
Solar/Wind Harmer
0.144
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 39-91_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 39-91_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.29 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:973.17
MW Contribution:0.64
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.692
971447AH1-217 GEN
Solar/Wind Harmer
18.622
971845AH1-439 GEN
Solar/Wind Harmer
22.237
270494AE1-108_GEN
Solar/Wind Harmer
10.551
970285AG2-188 GEN
Solar/Wind Harmer
35.335
315657AE1-056 GEN
Solar/Wind Harmer
9.243
946301AF1-294 GEN
Solar/Wind Harmer
5.939
961791AG1-021 GEN
Solar/Wind Harmer
2.897
970683AG2-441 GEN
Solar/Wind Harmer
16.461
970681AG2-440 GEN
Solar/Wind Harmer
13.169
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.67
316239AB2-077_GEN
Solar/Wind Harmer
0.407
3144293JTRSVLE
50/50
0.697
3144293JTRSVLE
50/50
0.587
971489AH1-241 GEN
Solar/Wind Harmer
30.786
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.481
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.621
963191AG1-168 GEN
Solar/Wind Harmer
2.173
971741AH1-377 GEN
Solar/Wind Harmer
25.942
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.416
971775AH1-396 GEN
Solar/Wind Harmer
1.341
313527AB2-043 GEN
Solar/Wind Harmer
2.245
962561AG1-105 GEN
Solar/Wind Harmer
6.444
939181AE1-148 GEN
Solar/Wind Harmer
6.287
964791AG1-342 GEN
Solar/Wind Harmer
2.356
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.272
971223AH1-071 GEN
Solar/Wind Harmer
1.326
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.828
316181AB2-040 GEN
Solar/Wind Harmer
1.022
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.794
3145593CAROLNA
Solar/Wind Harmer
0.059
3145783HORNRTN
Solar/Wind Harmer
0.823
3145783HORNRTN
Solar/Wind Harmer
0.658
3145783HORNRTN
Solar/Wind Harmer
0.206
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.692
972187AH1-678 GEN
Adder
1.699
972185AH1-677 GEN
Adder
3.299
966001AG1-469 GEN
Solar/Wind Helper
0.187
3132123MT JACKSON
Solar/Wind Helper
0.368
3151931BEARGRDN S1
50/50
5.74
3151911BEARGRDN G1
50/50
4.448
3144293JTRSVLE
50/50
0.697
971377AH1-170 GEN
Solar/Wind Harmer
6.486
3147623JAMES R
Solar/Wind Harmer
0.803
972003AH1-546 GEN
Solar/Wind Harmer
25.797
970937AG2-583 GEN
Solar/Wind Harmer
31.587
316322AB2-045
Solar/Wind Harmer
1.434
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.623
3143336POWHATN
Solar/Wind Harmer
3.304
963171AG1-166 GEN
Solar/Wind Harmer
2.897
971563AH1-280 GEN
Solar/Wind Harmer
2.897
970685AG2-442 GEN
Solar/Wind Harmer
18.436
962491AG1-098 GEN
Solar/Wind Harmer
9.378
316237AB2-079_GEN
Solar/Wind Harmer
0.407
315693AD1-088 GEN
Solar/Wind Harmer
6.713
970401AG2-262 GEN
Solar/Wind Harmer
0.72
957481AF2-042 GEN
Solar/Wind Harmer
33.181
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.173
971065AG2-659 GEN
Solar/Wind Harmer
4.785
3147043LAWRENC
Adder
0.762
316129AC1-054 GEN
Solar/Wind Harmer
0.821
971795AH1-408 GEN
Solar/Wind Harmer
6.648
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.833
960081AF2-299 GEN
Solar/Wind Harmer
0.851
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.274
970919AG2-571 GEN
Solar/Wind Harmer
2.054
3151921BEARGRDN G2
50/50
4.448
3144293JTRSVLE
50/50
0.697
970221AG2-151 GEN
Solar/Wind Harmer
32.428
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.331
316313AB2-026
Solar/Wind Harmer
0.751
316258AE1-075 C
Solar/Wind Harmer
0.676
316405AF2-144 C
Solar/Wind Harmer
0.713
3143336POWHATN
Solar/Wind Harmer
2.809
970909AG2-566 GEN
Solar/Wind Harmer
2.37
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.405
963181AG1-167 GEN
Solar/Wind Harmer
2.173
959311AF2-222 GEN
Solar/Wind Harmer
20.328
970257AG2-171 GEN
Solar/Wind Harmer
7.062
315785AD2-033 C
Solar/Wind Harmer
4.068
958131AF2-107 GEN
Solar/Wind Harmer
5.359
964241AG1-285 GEN
Solar/Wind Harmer
12.184
316131AB2-060 GEN
Solar/Wind Harmer
1.528
316478AD1-087 GEN
Solar/Wind Harmer
0.928
316486AD2-202 GEN
Solar/Wind Harmer
0.272
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.272
960061AF2-297 GEN
Solar/Wind Harmer
4.511
971683AH1-343 GEN
Solar/Wind Harmer
3.497
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.589
3150861SPRUNCD
Adder
0.274
970917AG2-570 GEN
Solar/Wind Harmer
16.228
316365GEN2_N
Solar/Wind Harmer
0.43
3148013FISHERV
Solar/Wind Helper
0.221
316499AE2-029_GEN
Solar/Wind Helper
0.571
315616AA1-038_C
Solar/Wind Helper
0.608
3132273ORANGE
Solar/Wind Helper
0.026
970087AG2-069 GEN
Solar/Wind Harmer
6.064
316023GEN1_S
Solar/Wind Harmer
0.43
3147983MERCK5
Solar/Wind Helper
0.062
316238AB2-078_GEN
Solar/Wind Harmer
0.407
316118AC1-105 GEN
Solar/Wind Harmer
0.689
970831AG2-522 GEN
Solar/Wind Harmer
4.571
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.238
971281AH1-106 GEN
Solar/Wind Harmer
1.438
971283AH1-107 GEN
Solar/Wind Harmer
1.438
970865AG2-541 GEN
Solar/Wind Harmer
3.115
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.055
971967AH1-528 GEN
Solar/Wind Harmer
13.769
3137643SOCKMAN
Solar/Wind Harmer
-0.029
316123AC1-075 GEN
Solar/Wind Harmer
0.731
970165AG2-112 GEN
Solar/Wind Harmer
0.643
970163AG2-111 GEN
Solar/Wind Harmer
0.614
315607AA1-063A GEN
Solar/Wind Harmer
0.681
971285AH1-108 GEN
Adder
0.449
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
970085AG2-068 GEN
Solar/Wind Harmer
4.042
970581AG2-369 GEN
Solar/Wind Harmer
3.477
941031AE2-094 GEN
Solar/Wind Harmer
11.972
944011AF1-069 GEN
Solar/Wind Harmer
3.751
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.132
3148013FISHERV
Solar/Wind Helper
0.127
3148463FAIRFLD
Solar/Wind Helper
0.134
CPLELTFEXP_CPLE->PJM
CLTF
3.247
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.539
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.798
MECLTFEXP_MEC->PJM
CLTF
0.142
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.409
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.087
LAGNLTFEXP_LAGN->PJM
CLTF
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.305
TVALTFEXP_TVA->PJM
CLTF
0.589

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P2-2: DOOMS B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: DOOMS B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.3 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:957.01
MW Contribution:0.64
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.736
3151911BEARGRDN G1
50/50
4.444
3144293JTRSVLE
50/50
0.696
971377AH1-170 GEN
Solar/Wind Harmer
6.481
3147623JAMES R
Solar/Wind Harmer
0.802
972003AH1-546 GEN
Solar/Wind Harmer
25.777
970937AG2-583 GEN
Solar/Wind Harmer
31.56
316322AB2-045
Solar/Wind Harmer
1.433
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.617
3143336POWHATN
Solar/Wind Harmer
3.3
963171AG1-166 GEN
Solar/Wind Harmer
2.893
971563AH1-280 GEN
Solar/Wind Harmer
2.893
3144293JTRSVLE
50/50
0.696
3144293JTRSVLE
50/50
0.586
315821AE2-092 GEN
Solar/Wind Harmer
10.863
971489AH1-241 GEN
Solar/Wind Harmer
30.763
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.465
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.616
963191AG1-168 GEN
Solar/Wind Harmer
2.17
971741AH1-377 GEN
Solar/Wind Harmer
25.905
316034AC1-036 C
Solar/Wind Harmer
0.349
970323AG2-213 GEN
Solar/Wind Harmer
9.401
971775AH1-396 GEN
Solar/Wind Harmer
1.339
313527AB2-043 GEN
Solar/Wind Harmer
2.24
962561AG1-105 GEN
Solar/Wind Harmer
6.427
939181AE1-148 GEN
Solar/Wind Harmer
6.27
964791AG1-342 GEN
Solar/Wind Harmer
2.35
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.235
971223AH1-071 GEN
Solar/Wind Harmer
1.322
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.8
316181AB2-040 GEN
Solar/Wind Harmer
1.018
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.791
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.819
3145783HORNRTN
Solar/Wind Harmer
0.655
3145783HORNRTN
Solar/Wind Harmer
0.205
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.689
972187AH1-678 GEN
Adder
1.691
972185AH1-677 GEN
Adder
3.285
966001AG1-469 GEN
Solar/Wind Helper
0.188
3132123MT JACKSON
Solar/Wind Helper
0.367
970685AG2-442 GEN
Solar/Wind Harmer
18.409
962491AG1-098 GEN
Solar/Wind Harmer
9.357
316237AB2-079_GEN
Solar/Wind Harmer
0.406
315693AD1-088 GEN
Solar/Wind Harmer
6.698
970401AG2-262 GEN
Solar/Wind Harmer
0.718
957481AF2-042 GEN
Solar/Wind Harmer
33.088
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.169
971065AG2-659 GEN
Solar/Wind Harmer
4.77
3147043LAWRENC
Adder
0.76
316129AC1-054 GEN
Solar/Wind Harmer
0.818
971795AH1-408 GEN
Solar/Wind Harmer
6.626
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.83
960081AF2-299 GEN
Solar/Wind Harmer
0.847
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.273
970919AG2-571 GEN
Solar/Wind Harmer
2.045
970087AG2-069 GEN
Solar/Wind Harmer
6.037
316023GEN1_S
Solar/Wind Harmer
0.428
3147983MERCK5
Solar/Wind Helper
0.063
972205AH1-687 GEN
50/50
21.676
971447AH1-217 GEN
Solar/Wind Harmer
18.608
971845AH1-439 GEN
Solar/Wind Harmer
22.218
270494AE1-108_GEN
Solar/Wind Harmer
10.541
970285AG2-188 GEN
Solar/Wind Harmer
35.303
315657AE1-056 GEN
Solar/Wind Harmer
9.23
946301AF1-294 GEN
Solar/Wind Harmer
5.931
961791AG1-021 GEN
Solar/Wind Harmer
2.893
970683AG2-441 GEN
Solar/Wind Harmer
16.436
970681AG2-440 GEN
Solar/Wind Harmer
13.149
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.664
316239AB2-077_GEN
Solar/Wind Harmer
0.406
316238AB2-078_GEN
Solar/Wind Harmer
0.406
316118AC1-105 GEN
Solar/Wind Harmer
0.687
970831AG2-522 GEN
Solar/Wind Harmer
4.556
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.237
971281AH1-106 GEN
Solar/Wind Harmer
1.433
971283AH1-107 GEN
Solar/Wind Harmer
1.433
970865AG2-541 GEN
Solar/Wind Harmer
3.104
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.051
971967AH1-528 GEN
Solar/Wind Harmer
13.715
3137643SOCKMAN
Solar/Wind Harmer
-0.028
316123AC1-075 GEN
Solar/Wind Harmer
0.728
970165AG2-112 GEN
Solar/Wind Harmer
0.641
970163AG2-111 GEN
Solar/Wind Harmer
0.611
315607AA1-063A GEN
Solar/Wind Harmer
0.678
971285AH1-108 GEN
Adder
0.447
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.659
970673AG2-436 GEN
Solar/Wind Harmer
6.916
970085AG2-068 GEN
Solar/Wind Harmer
4.024
970581AG2-369 GEN
Solar/Wind Harmer
3.461
941031AE2-094 GEN
Solar/Wind Harmer
11.918
944011AF1-069 GEN
Solar/Wind Harmer
3.734
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.136
3148013FISHERV
Solar/Wind Helper
0.13
3148463FAIRFLD
Solar/Wind Helper
0.135
3151921BEARGRDN G2
50/50
4.444
3144293JTRSVLE
50/50
0.696
970221AG2-151 GEN
Solar/Wind Harmer
32.404
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.326
316313AB2-026
Solar/Wind Harmer
0.75
316258AE1-075 C
Solar/Wind Harmer
0.675
316405AF2-144 C
Solar/Wind Harmer
0.712
3143336POWHATN
Solar/Wind Harmer
2.805
970909AG2-566 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.384
963181AG1-167 GEN
Solar/Wind Harmer
2.17
959311AF2-222 GEN
Solar/Wind Harmer
20.295
970257AG2-171 GEN
Solar/Wind Harmer
7.05
315785AD2-033 C
Solar/Wind Harmer
4.061
958131AF2-107 GEN
Solar/Wind Harmer
5.349
964241AG1-285 GEN
Solar/Wind Harmer
12.16
316131AB2-060 GEN
Solar/Wind Harmer
1.525
316478AD1-087 GEN
Solar/Wind Harmer
0.925
316486AD2-202 GEN
Solar/Wind Harmer
0.271
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.271
960061AF2-297 GEN
Solar/Wind Harmer
4.496
971683AH1-343 GEN
Solar/Wind Harmer
3.484
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.586
3150861SPRUNCD
Adder
0.273
970917AG2-570 GEN
Solar/Wind Harmer
16.156
316365GEN2_N
Solar/Wind Harmer
0.428
3148013FISHERV
Solar/Wind Helper
0.227
316499AE2-029_GEN
Solar/Wind Helper
0.572
315616AA1-038_C
Solar/Wind Helper
0.611
3132273ORANGE
Solar/Wind Helper
0.026
CPLELTFEXP_CPLE->PJM
CLTF
3.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.302
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.731
MECLTFEXP_MEC->PJM
CLTF
0.113
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.42
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.046
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.122
LAGNLTFEXP_LAGN->PJM
CLTF
1.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.249
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.571

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.29 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:916.48
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.143
971447AH1-217 GEN
Solar/Wind Harmer
14.529
971845AH1-439 GEN
Solar/Wind Harmer
20.7
970285AG2-188 GEN
Solar/Wind Harmer
32.906
270494AE1-108_GEN
Solar/Wind Harmer
9.015
315657AE1-056 GEN
Solar/Wind Harmer
8.675
946301AF1-294 GEN
Solar/Wind Harmer
5.582
961791AG1-021 GEN
Solar/Wind Harmer
2.723
970683AG2-441 GEN
Solar/Wind Harmer
15.505
970681AG2-440 GEN
Solar/Wind Harmer
12.404
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.467
316239AB2-077_GEN
Solar/Wind Harmer
0.389
316238AB2-078_GEN
Solar/Wind Harmer
0.389
316118AC1-105 GEN
Solar/Wind Harmer
0.665
970831AG2-522 GEN
Solar/Wind Harmer
4.449
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Harmer
0.225
971281AH1-106 GEN
Solar/Wind Harmer
1.359
971283AH1-107 GEN
Solar/Wind Harmer
1.359
946281AF1-292 GEN
Solar/Wind Harmer
0.166
970865AG2-541 GEN
Solar/Wind Harmer
2.988
316087AB2-174 GEN
Solar/Wind Harmer
1.035
971967AH1-528 GEN
Solar/Wind Harmer
13.383
3137643SOCKMAN
Solar/Wind Harmer
-0.028
315607AA1-063A GEN
Solar/Wind Harmer
0.672
3146043SEABORD
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.694
970165AG2-112 GEN
Solar/Wind Harmer
0.611
970163AG2-111 GEN
Solar/Wind Harmer
0.583
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
970673AG2-436 GEN
Solar/Wind Harmer
13.415
970673AG2-436 GEN
Solar/Wind Harmer
6.792
971285AH1-108 GEN
Adder
0.428
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.12
3151931BEARGRDN S1
50/50
5.33
3151911BEARGRDN G1
50/50
4.13
3144293JTRSVLE
50/50
0.655
972003AH1-546 GEN
Solar/Wind Harmer
23.962
971377AH1-170 GEN
Solar/Wind Harmer
5.548
3147623JAMES R
Solar/Wind Harmer
0.687
970937AG2-583 GEN
Solar/Wind Harmer
29.352
316322AB2-045
Solar/Wind Harmer
1.334
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.233
3143336POWHATN
Solar/Wind Harmer
3.078
963171AG1-166 GEN
Solar/Wind Harmer
2.723
971563AH1-280 GEN
Solar/Wind Harmer
2.723
970685AG2-442 GEN
Solar/Wind Harmer
17.365
962491AG1-098 GEN
Solar/Wind Harmer
8.919
316237AB2-079_GEN
Solar/Wind Harmer
0.389
315693AD1-088 GEN
Solar/Wind Harmer
6.394
970401AG2-262 GEN
Solar/Wind Harmer
0.692
957481AF2-042 GEN
Solar/Wind Harmer
31.87
3143226MDLTHAN
Solar/Wind Harmer
-0.01
315687AD1-152 GEN
Solar/Wind Harmer
1.137
971065AG2-659 GEN
Solar/Wind Harmer
4.648
3147043LAWRENC
Adder
0.737
3144293JTRSVLE
50/50
0.655
3144293JTRSVLE
50/50
0.551
971489AH1-241 GEN
Solar/Wind Harmer
26.337
3146776BUCKING
Solar/Wind Harmer
-0.158
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.386
970301AG2-198 GEN
Solar/Wind Harmer
11.705
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.404
963191AG1-168 GEN
Solar/Wind Harmer
2.042
971741AH1-377 GEN
Solar/Wind Harmer
24.381
316034AC1-036 C
Solar/Wind Harmer
0.331
970323AG2-213 GEN
Solar/Wind Harmer
8.895
971775AH1-396 GEN
Solar/Wind Harmer
1.267
313527AB2-043 GEN
Solar/Wind Harmer
2.141
962561AG1-105 GEN
Solar/Wind Harmer
6.187
939181AE1-148 GEN
Solar/Wind Harmer
6.061
964791AG1-342 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
12.748
971223AH1-071 GEN
Solar/Wind Harmer
1.248
3143526WINTERP
Solar/Wind Harmer
-0.043
970933AG2-581 GEN
Solar/Wind Harmer
7.571
316181AB2-040 GEN
Solar/Wind Harmer
1.004
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.784
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.814
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.204
3145783HORNRTN
Solar/Wind Harmer
0.081
316426AA2-053 GEN
Solar/Wind Harmer
0.684
972187AH1-678 GEN
Adder
1.664
972185AH1-677 GEN
Adder
3.229
966001AG1-469 GEN
Solar/Wind Helper
0.189
316129AC1-054 GEN
Solar/Wind Harmer
0.798
971795AH1-408 GEN
Solar/Wind Harmer
6.453
3143526WINTERP
Solar/Wind Harmer
-0.043
316003AC1-222 GEN
Solar/Wind Harmer
0.805
960081AF2-299 GEN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.083
970919AG2-571 GEN
Solar/Wind Harmer
2.03
970087AG2-069 GEN
Solar/Wind Harmer
6
3150851SPRUNCC
Adder
0.261
3147983MERCK5
Solar/Wind Helper
0.055
3151921BEARGRDN G2
50/50
4.13
3144293JTRSVLE
50/50
0.655
970221AG2-151 GEN
Solar/Wind Harmer
27.742
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.053
316313AB2-026
Solar/Wind Harmer
0.699
316258AE1-075 C
Solar/Wind Harmer
0.63
316405AF2-144 C
Solar/Wind Harmer
0.664
3143336POWHATN
Solar/Wind Harmer
2.616
970909AG2-566 GEN
Solar/Wind Harmer
2.223
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.459
963181AG1-167 GEN
Solar/Wind Harmer
2.042
959311AF2-222 GEN
Solar/Wind Harmer
19.185
970257AG2-171 GEN
Solar/Wind Harmer
6.671
315785AD2-033 C
Solar/Wind Harmer
3.847
964241AG1-285 GEN
Solar/Wind Harmer
11.573
316131AB2-060 GEN
Solar/Wind Harmer
1.457
958131AF2-107 GEN
Solar/Wind Harmer
4.54
316478AD1-087 GEN
Solar/Wind Harmer
0.893
316486AD2-202 GEN
Solar/Wind Harmer
0.261
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.376
971683AH1-343 GEN
Solar/Wind Harmer
3.368
966621AG1-532 GEN
Solar/Wind Harmer
0.15
313506AB2-031 GEN
Solar/Wind Harmer
0.578
970917AG2-570 GEN
Solar/Wind Harmer
16.041
3150861SPRUNCD
Adder
0.261
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.545
CPLELTFEXP_CPLE->PJM
CLTF
3.638
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.961
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.309
MECLTFEXP_MEC->PJM
CLTF
0.208
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.389
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.045
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.115
LAGNLTFEXP_LAGN->PJM
CLTF
1.574
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.039
TVALTFEXP_TVA->PJM
CLTF
0.757

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.05 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:882.22
MW Contribution:0.6
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.07
3144293JTRSVLE
50/50
0.636
970221AG2-151 GEN
Solar/Wind Harmer
27.317
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.018
942461AE2-259 GEN
Solar/Wind Harmer
3.955
316313AB2-026
Solar/Wind Harmer
0.683
316258AE1-075 C
Solar/Wind Harmer
0.615
316405AF2-144 C
Solar/Wind Harmer
0.649
3143336POWHATN
Solar/Wind Harmer
2.554
970909AG2-566 GEN
Solar/Wind Harmer
2.162
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.064
963181AG1-167 GEN
Solar/Wind Harmer
1.983
959311AF2-222 GEN
Solar/Wind Harmer
18.545
970257AG2-171 GEN
Solar/Wind Harmer
6.442
315785AD2-033 C
Solar/Wind Harmer
3.71
964241AG1-285 GEN
Solar/Wind Harmer
11.106
958131AF2-107 GEN
Solar/Wind Harmer
4.655
316131AB2-060 GEN
Solar/Wind Harmer
1.393
316478AD1-087 GEN
Solar/Wind Harmer
0.841
316486AD2-202 GEN
Solar/Wind Harmer
0.246
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.249
960061AF2-297 GEN
Solar/Wind Harmer
4.131
971683AH1-343 GEN
Solar/Wind Harmer
3.224
966621AG1-532 GEN
Solar/Wind Harmer
0.138
313506AB2-031 GEN
Solar/Wind Harmer
0.528
316499AE2-029_GEN
Solar/Wind Helper
0.551
3148013FISHERV
Solar/Wind Helper
0.152
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.264
3151931BEARGRDN S1
50/50
5.253
3151911BEARGRDN G1
50/50
4.07
3144293JTRSVLE
50/50
0.636
972003AH1-546 GEN
Solar/Wind Harmer
23.604
971377AH1-170 GEN
Solar/Wind Harmer
5.463
3147623JAMES R
Solar/Wind Harmer
0.676
970937AG2-583 GEN
Solar/Wind Harmer
28.861
316322AB2-045
Solar/Wind Harmer
1.311
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
5.122
3143336POWHATN
Solar/Wind Harmer
3.004
963171AG1-166 GEN
Solar/Wind Harmer
2.645
971563AH1-280 GEN
Solar/Wind Harmer
2.645
970685AG2-442 GEN
Solar/Wind Harmer
16.824
962491AG1-098 GEN
Solar/Wind Harmer
8.511
316237AB2-079_GEN
Solar/Wind Harmer
0.371
315693AD1-088 GEN
Solar/Wind Harmer
6.09
970401AG2-262 GEN
Solar/Wind Harmer
0.658
957481AF2-042 GEN
Solar/Wind Harmer
29.994
3143226MDLTHAN
Solar/Wind Harmer
-0.009
315687AD1-152 GEN
Solar/Wind Harmer
1.066
971065AG2-659 GEN
Solar/Wind Harmer
4.339
3147043LAWRENC
Adder
0.688
316129AC1-054 GEN
Solar/Wind Harmer
0.744
971795AH1-408 GEN
Solar/Wind Harmer
5.995
316003AC1-222 GEN
Solar/Wind Harmer
0.766
3143526WINTERP
Solar/Wind Harmer
-0.04
960081AF2-299 GEN
Solar/Wind Harmer
0.763
3147983MERCK5
Solar/Wind Helper
0.06
316192AB2-158 GEN
Solar/Wind Helper
0.803
3147666LOUISA
Solar/Wind Helper
0.46
3144293JTRSVLE
50/50
0.636
3144293JTRSVLE
50/50
0.536
971489AH1-241 GEN
Solar/Wind Harmer
25.934
3146776BUCKING
Solar/Wind Harmer
-0.155
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.214
970301AG2-198 GEN
Solar/Wind Harmer
11.385
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.306
963191AG1-168 GEN
Solar/Wind Harmer
1.983
971741AH1-377 GEN
Solar/Wind Harmer
23.646
316034AC1-036 C
Solar/Wind Harmer
0.319
970323AG2-213 GEN
Solar/Wind Harmer
8.59
971775AH1-396 GEN
Solar/Wind Harmer
1.223
313527AB2-043 GEN
Solar/Wind Harmer
2.045
962561AG1-105 GEN
Solar/Wind Harmer
5.883
939181AE1-148 GEN
Solar/Wind Harmer
5.719
964791AG1-342 GEN
Solar/Wind Harmer
2.152
3146843MT LREL
Solar/Wind Harmer
-0.01
3146843MT LREL
Solar/Wind Harmer
-0.01
970099AG2-077 GEN
Solar/Wind Harmer
11.998
971223AH1-071 GEN
Solar/Wind Harmer
1.179
3143526WINTERP
Solar/Wind Harmer
-0.04
970933AG2-581 GEN
Solar/Wind Harmer
7.011
316181AB2-040 GEN
Solar/Wind Harmer
0.917
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.713
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.2
3132123MT JACKSON
Solar/Wind Helper
0.351
972205AH1-687 GEN
50/50
19.851
971447AH1-217 GEN
Solar/Wind Harmer
14.274
971845AH1-439 GEN
Solar/Wind Harmer
20.334
970285AG2-188 GEN
Solar/Wind Harmer
32.307
270494AE1-108_GEN
Solar/Wind Harmer
8.922
315657AE1-056 GEN
Solar/Wind Harmer
8.438
946301AF1-294 GEN
Solar/Wind Harmer
5.421
961791AG1-021 GEN
Solar/Wind Harmer
2.645
970683AG2-441 GEN
Solar/Wind Harmer
15.022
970681AG2-440 GEN
Solar/Wind Harmer
12.017
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.347
316239AB2-077_GEN
Solar/Wind Harmer
0.371
316238AB2-078_GEN
Solar/Wind Harmer
0.371
316118AC1-105 GEN
Solar/Wind Harmer
0.63
970831AG2-522 GEN
Solar/Wind Harmer
4.14
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Harmer
0.21
971281AH1-106 GEN
Solar/Wind Harmer
1.27
971283AH1-107 GEN
Solar/Wind Harmer
1.27
970865AG2-541 GEN
Solar/Wind Harmer
2.883
946281AF1-292 GEN
Solar/Wind Harmer
0.152
316087AB2-174 GEN
Solar/Wind Harmer
0.947
971967AH1-528 GEN
Solar/Wind Harmer
12.263
3137643SOCKMAN
Solar/Wind Harmer
-0.026
316123AC1-075 GEN
Solar/Wind Harmer
0.683
970165AG2-112 GEN
Solar/Wind Harmer
0.601
970163AG2-111 GEN
Solar/Wind Harmer
0.573
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.091
3148013FISHERV
Solar/Wind Helper
0.088
CPLELTFEXP_CPLE->PJM
CLTF
3.029
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.957
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.668
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.188
MECLTFEXP_MEC->PJM
CLTF
0.344
SIGELTFEXP_SIGE->PJM
CLTF
0.009
NYPJM->LTFIMP_NY
CLTF
0.444
LGEELTFEXP_LGEE->PJM
CLTF
0.079
WECLTFEXP_WEC->PJM
CLTF
0.033
LAGNLTFEXP_LAGN->PJM
CLTF
1.383
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.08
TVALTFEXP_TVA->PJM
CLTF
0.685

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:137.15 %
Rating:1057.5 MVA
Rating Type:B
MVA to Mitigate:1450.33
MW Contribution:0.48
Bus #Bus NameTypeMW Contribution
3150861SPRUNCD
50/50
1.044
3143096IRON208
50/50
0.687
3143096IRON208
50/50
0.673
3151921BEARGRDN G2
50/50
1.285
316313AB2-026
Solar/Wind Harmer
0.185
316258AE1-075 C
Solar/Wind Harmer
0.222
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.438
3146776BUCKING
Solar/Wind Harmer
0.045
970221AG2-151 GEN
Solar/Wind Harmer
6.608
965281AG1-393 GEN
Solar/Wind Harmer
1.316
315839AE2-212 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
1.182
970293AG2-193 GEN
Solar/Wind Harmer
1.304
3142946ENON
Solar/Wind Harmer
0.04
970129AG2-093 GEN
Solar/Wind Harmer
7.091
315778AD1-151 GEN
Solar/Wind Harmer
9.051
3146926FARMVIL
Solar/Wind Harmer
0.068
315813AE1-149 C
Solar/Wind Harmer
5.92
316473AC1-191 GEN
Solar/Wind Harmer
0.369
3142416OLDCHRC
Solar/Wind Harmer
1.056
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
1.122
316083AB2-161 GEN
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.784
970909AG2-566 GEN
Solar/Wind Harmer
1.096
970661AG2-428 GEN
Solar/Wind Harmer
2.168
3147133PAMPLIN
Solar/Wind Harmer
0.316
971193AH1-056 GEN
Solar/Wind Harmer
6.137
3151221GRAVEL6
Adder
7.305
3151171GRAVELC
Adder
1.406
963181AG1-167 GEN
Solar/Wind Harmer
0.395
3144293JTRSVLE
Adder
0.314
3145336SMITFLD
Solar/Wind Harmer
0.038
3141843SHACKLE
Adder
0.481
316203AE2-005 GEN
Solar/Wind Harmer
0
959311AF2-222 GEN
Solar/Wind Harmer
8.32
316382AG1-145 C
Solar/Wind Harmer
0.001
970257AG2-171 GEN
Solar/Wind Harmer
2.966
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.23
315785AD2-033 C
Solar/Wind Harmer
0.744
3144216WINCHST
Adder
0.345
3144536CHRHLND
Solar/Wind Harmer
0.014
316156AD2-030 GEN
Solar/Wind Harmer
0.067
3141873WAN 176
Solar/Wind Harmer
1.611
3150921YORKTN3
Adder
2.265
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.251
3145273HOLLAND
Solar/Wind Harmer
0.066
316365GEN2_N
Solar/Wind Harmer
0.199
964241AG1-285 GEN
Solar/Wind Harmer
5.88
3146456SLIGO L269
Solar/Wind Harmer
0.088
971153AH1-033 GEN
Solar/Wind Harmer
1.013
944581AF1-123 GEN
Solar/Wind Harmer
19.675
944601AF1-125 GEN
Solar/Wind Harmer
19.372
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0.001
3147043LAWRENC
Solar/Wind Harmer
0.052
3146516WINFALL
Solar/Wind Harmer
0.087
3146626S HERTFORD
Solar/Wind Harmer
0.086
316131AB2-060 GEN
Solar/Wind Harmer
0.271
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
313506AB2-031 GEN
Solar/Wind Harmer
0.264
3146376EDENTON
Solar/Wind Harmer
0.085
315773AC2-141 GEN
Solar/Wind Harmer
3.093
3145893MURPHYS
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
0.084
962971AG1-146 GEN
Solar/Wind Harmer
1.345
315614AA2-178 GEN
Solar/Wind Harmer
0.481
957521AF2-046 GEN
Solar/Wind Harmer
6.241
961681AG1-008 GEN
Solar/Wind Harmer
6.241
316478AD1-087 GEN
Solar/Wind Harmer
0.292
316486AD2-202 GEN
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3146173TUNIS
Solar/Wind Harmer
0.083
971157AH1-035 GEN
Solar/Wind Harmer
0.997
315737AD1-076 GEN
Solar/Wind Harmer
1.067
316463AE2-346 GEN
Solar/Wind Harmer
0.071
316140AB2-099
Solar/Wind Harmer
0.03
962331AG1-082 GEN
Solar/Wind Harmer
0.882
3146206CASHIE
Solar/Wind Harmer
0.083
970009AG2-005 GEN
Solar/Wind Harmer
0.617
3146263WOODLND
Solar/Wind Harmer
0.082
970917AG2-570 GEN
Solar/Wind Harmer
7.314
3156021HOLLOMANSOL
Solar/Wind Harmer
0.373
3145796HORNRTN
Solar/Wind Harmer
0.327
3145796HORNRTN
Solar/Wind Harmer
0.082
971781AH1-399 GEN
Solar/Wind Harmer
0.107
316317KELFORD C
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.081
316404AE1-155 C
Solar/Wind Harmer
0.018
3145963POPLR C
Solar/Wind Harmer
0.08
316210AC1-098 GEN
Solar/Wind Harmer
0.732
316303AF2-085
50/50
7.059
971285AH1-108 GEN
50/50
1.708
972205AH1-687 GEN
50/50
6.267
316233AE1-074 FULL
Solar/Wind Harmer
0.255
971281AH1-106 GEN
Solar/Wind Harmer
4.412
971283AH1-107 GEN
Solar/Wind Harmer
4.412
971845AH1-439 GEN
Solar/Wind Harmer
5.597
970285AG2-188 GEN
Solar/Wind Harmer
9.622
971447AH1-217 GEN
Solar/Wind Harmer
3.562
316132AB2-190 GEN1
Solar/Wind Harmer
0.626
3143316POE
Solar/Wind Harmer
0.447
971167AH1-042 GEN
Solar/Wind Harmer
9.861
316369SG1_INVT
Solar/Wind Harmer
0.004
316312AB1-027
Solar/Wind Harmer
0.195
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
270494AE1-108_GEN
Solar/Wind Harmer
1.234
315976AC1-164 GENA
Solar/Wind Harmer
10.641
316169AC1-164_GENC
Solar/Wind Harmer
9.193
315975AC1-164 GENB
Solar/Wind Harmer
0.315
315657AE1-056 GEN
Solar/Wind Harmer
3.476
972265AH1-717 GEN
Adder
7.802
3151201GRAVEL4
Adder
7.314
3151191GRAVEL3
Adder
7.221
3151211GRAVEL5
Adder
7.221
3143873LANEXA
Solar/Wind Harmer
0.059
946301AF1-294 GEN
Solar/Wind Harmer
1.948
961791AG1-021 GEN
Solar/Wind Harmer
0.948
316315AB2-025 C
Solar/Wind Harmer
0.079
315814AE2-033 C
Solar/Wind Harmer
7.71
971445AH1-216 GEN
Solar/Wind Harmer
6.794
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.066
316311AC2-079 GEN
Solar/Wind Harmer
2.751
970683AG2-441 GEN
Solar/Wind Harmer
6.388
970681AG2-440 GEN
Solar/Wind Harmer
5.11
970189AG2-124 GEN
Solar/Wind Harmer
2.786
316314AB2-024 C
Solar/Wind Harmer
0
3144303KENBRDG
Solar/Wind Harmer
0.074
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.553
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.018
3138283WHITEMARSH
Solar/Wind Harmer
0.021
315835AF2-110_GEN
Solar/Wind Harmer
0.619
3152611GOSPORTB
Adder
1.135
3152621GOSPORTC
Adder
0.963
3152601GOSPORTA
Adder
0.888
3151081ELIZAR1
Adder
8.147
3151091ELIZAR2
Adder
8.006
3141913WHIT STONE
Solar/Wind Harmer
0.088
316305AF2-043 C
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.026
957871AF2-081 GEN
Solar/Wind Harmer
4.367
319010AE1-072 C
Solar/Wind Harmer
0.441
3146406KITTY HAWK
Solar/Wind Harmer
0.011
3146486SUNBURY
Solar/Wind Harmer
0.087
3146486SUNBURY
Solar/Wind Harmer
0.087
313526AB2-022
Solar/Wind Harmer
0.047
941031AE2-094 GEN
Solar/Wind Harmer
16.035
944011AF1-069 GEN
Solar/Wind Harmer
5.239
316321Z2-027
Solar/Wind Harmer
0.016
3145176PASQUOTANK
Solar/Wind Harmer
0.054
3146396TANGLEW
Solar/Wind Harmer
0.24
3141783LANCAST
Solar/Wind Harmer
0.052
3141783LANCAST
Solar/Wind Harmer
0.035
971967AH1-528 GEN
Solar/Wind Harmer
13.837
970673AG2-436 GEN
Solar/Wind Harmer
18.368
970673AG2-436 GEN
Solar/Wind Harmer
12.246
316087AB2-174 GEN
Solar/Wind Harmer
0.002
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
0.085
965291AG1-394 GEN
Solar/Wind Harmer
0.378
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
0.084
3137643SOCKMAN
Solar/Wind Harmer
0.336
962981AG1-147 GEN
Solar/Wind Harmer
3.138
3146043SEABORD
Solar/Wind Harmer
0.084
315816AE2-034 GEN
Solar/Wind Harmer
0.36
315607AA1-063A GEN
Solar/Wind Harmer
0.171
315652AC1-086 GEN
Solar/Wind Harmer
9.169
3130546PLYMOUTH
Solar/Wind Harmer
0.083
315732AD1-074 GEN1
Solar/Wind Harmer
0.476
315733AD1-074 GEN2
Solar/Wind Harmer
0.476
315735AD1-075 GEN1
Solar/Wind Harmer
0.238
3142366NRTHEST
50/50
0.483
3150691DARBY 3
50/50
10.163
3150701DARBY 4
50/50
10.139
3150681DARBY 2
50/50
10.127
3150671DARBY 1
50/50
10.115
944641AF1-129 GEN
50/50
66.432
971223AH1-071 GEN
Solar/Wind Harmer
4.235
3143526WINTERP
Solar/Wind Harmer
1.653
316240AF1-291 C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.497
3146776BUCKING
Solar/Wind Harmer
0.04
971489AH1-241 GEN
Solar/Wind Harmer
6.608
3142946ENON
Solar/Wind Harmer
0.012
3142296MT RD221
Adder
0.38
316033AB2-134 GEN
Solar/Wind Harmer
0.006
315697AD1-025 GEN
Solar/Wind Harmer
0.124
316075AC2-137 C
Solar/Wind Harmer
0.03
966871AG1-558 GEN
Solar/Wind Harmer
0.126
970657AG2-426 GEN
Solar/Wind Harmer
3.648
970657AG2-426 GEN
Solar/Wind Harmer
0.765
970301AG2-198 GEN
Solar/Wind Harmer
4.386
3147133PAMPLIN
Solar/Wind Harmer
0.101
3147133PAMPLIN
Solar/Wind Harmer
0.081
971741AH1-377 GEN
Solar/Wind Harmer
9.881
958211AF2-115 GEN
Solar/Wind Harmer
1.185
963191AG1-168 GEN
Solar/Wind Harmer
0.395
3144293JTRSVLE
Adder
0.314
3144293JTRSVLE
Adder
0.265
3144356SAPONY
Solar/Wind Harmer
0.819
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316034AC1-036 C
Solar/Wind Harmer
0.007
970323AG2-213 GEN
Solar/Wind Harmer
3.955
971775AH1-396 GEN
Solar/Wind Harmer
0.148
315821AE2-092 GEN
Solar/Wind Harmer
0.006
316036AC1-147 C
Solar/Wind Harmer
0.017
3150991CHESPKB
Adder
0.933
3150991CHESPKB
Adder
0.911
316316AC1-027 C
Solar/Wind Harmer
0.085
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3145506HICKORY
Solar/Wind Harmer
0.351
3145506HICKORY
Solar/Wind Harmer
0.211
3145506HICKORY
Solar/Wind Harmer
0.053
316339AD2-160 GEN
Solar/Wind Harmer
0.142
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.049
3137176SLIGO L2192
Solar/Wind Harmer
0.349
3146456SLIGO L269
Solar/Wind Harmer
1.551
3130086AYDLETT
Solar/Wind Harmer
0.35
3146386ELIZ CT
Solar/Wind Harmer
0.087
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
970933AG2-581 GEN
Solar/Wind Harmer
6.917
3146626S HERTFORD
Solar/Wind Harmer
0.086
3146626S HERTFORD
Solar/Wind Harmer
0.086
970099AG2-077 GEN
Solar/Wind Harmer
9.151
313527AB2-043 GEN
Solar/Wind Harmer
0.001
972185AH1-677 GEN
Adder
4.805
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3146376EDENTON
Solar/Wind Harmer
0.379
3146376EDENTON
Solar/Wind Harmer
0.379
972187AH1-678 GEN
Adder
2.42
3145893MURPHYS
Solar/Wind Harmer
0.563
3145893MURPHYS
Solar/Wind Harmer
0.151
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
3146173TUNIS
Solar/Wind Harmer
0.083
3146173TUNIS
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.901
3145593CAROLNA
Solar/Wind Harmer
0.103
316426AA2-053 GEN
Solar/Wind Harmer
0.28
316065AD1-022 GEN
Solar/Wind Harmer
3.808
3145783HORNRTN
Solar/Wind Harmer
1.465
3145783HORNRTN
Solar/Wind Harmer
1.172
3145783HORNRTN
Solar/Wind Harmer
0.366
3145783HORNRTN
Solar/Wind Harmer
0.146
939181AE1-148 GEN
Solar/Wind Harmer
3.944
3145796HORNRTN
Solar/Wind Harmer
0.246
316468AD1-105 GEN
Solar/Wind Harmer
-0.026
958261AF2-120 GEN
Solar/Wind Harmer
2.652
962561AG1-105 GEN
Solar/Wind Harmer
3.799
316274AC1-208 GEN
Solar/Wind Harmer
0.409
964791AG1-342 GEN
Solar/Wind Harmer
1.497
970119AG2-088 GEN
50/50
52.941
3150851SPRUNCC
50/50
1.044
3143096IRON208
50/50
0.687
3151931BEARGRDN S1
50/50
1.658
3151911BEARGRDN G1
50/50
1.285
3143226MDLTHAN
Solar/Wind Harmer
0.397
3143526WINTERP
Solar/Wind Harmer
1.653
3143336POWHATN
Solar/Wind Harmer
5.221
316336AC2-165 C
Solar/Wind Harmer
0.01
970937AG2-583 GEN
Solar/Wind Harmer
12.089
3142543TWELFTH
Solar/Wind Harmer
0.016
972003AH1-546 GEN
Solar/Wind Harmer
5.766
944631AF1-128 GEN
Adder
61.208
315671AE2-027_GEN
Solar/Wind Harmer
7.993
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.05
971377AH1-170 GEN
Solar/Wind Harmer
1.322
3147623JAMES R
Solar/Wind Harmer
0.287
970129AG2-093 GEN
Solar/Wind Harmer
3.337
316458AB2-190 GEN2
Solar/Wind Harmer
0.626
971069AG2-661 GEN
Solar/Wind Harmer
2.011
3146926FARMVIL
Solar/Wind Harmer
0.068
3142416OLDCHRC
Solar/Wind Harmer
0.283
3142416OLDCHRC
Solar/Wind Harmer
0.109
3142433PROV 92
Solar/Wind Harmer
0.434
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
971647AH1-324 GEN
Solar/Wind Harmer
4.589
970659AG2-427 GEN
Solar/Wind Harmer
5.129
316381AD1-082 GEN
Solar/Wind Harmer
0.11
961611AG1-000B GEN
Solar/Wind Harmer
5.476
970661AG2-428 GEN
Solar/Wind Harmer
10.195
3151171GRAVELC
Adder
1.069
963171AG1-166 GEN
Solar/Wind Harmer
0.527
971563AH1-280 GEN
Solar/Wind Harmer
1.053
3144293JTRSVLE
Adder
0.314
3145336SMITFLD
Solar/Wind Harmer
0.384
970685AG2-442 GEN
Solar/Wind Harmer
7.154
971777AH1-397 GEN
Solar/Wind Harmer
0.248
3141843SHACKLE
Adder
0.481
316159AE1-175 C
Solar/Wind Harmer
0.081
3141766HARMONY
Solar/Wind Harmer
0.018
3138126ROCKLANDING
Solar/Wind Harmer
0.042
316072AD1-144
Solar/Wind Harmer
0.033
316093AE2-104_GEN
Solar/Wind Harmer
1.516
971317AH1-138 GEN
Solar/Wind Harmer
0.671
962491AG1-098 GEN
Solar/Wind Harmer
5.114
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.112
315693AD1-088 GEN
Solar/Wind Harmer
4.267
316023GEN1_S
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.04
940641AE2-051 GEN
Solar/Wind Harmer
7.055
939411AE1-173 GEN
Solar/Wind Harmer
37.578
3138133OCRAN
Solar/Wind Harmer
0.053
316388AE2-253 GEN
Solar/Wind Harmer
0.275
3146456SLIGO L269
Solar/Wind Harmer
0.088
944591AF1-124 GEN
Solar/Wind Harmer
19.745
960081AF2-299 GEN
Solar/Wind Harmer
0.838
971795AH1-408 GEN
Solar/Wind Harmer
5.798
3147043LAWRENC
Adder
0.785
3146516WINFALL
Solar/Wind Harmer
0.281
3146516WINFALL
Solar/Wind Harmer
0.087
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
957481AF2-042 GEN
Solar/Wind Harmer
22.879
3130156CHOWAN
Solar/Wind Harmer
0.085
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.467
3145893MURPHYS
Solar/Wind Harmer
0.336
3145893MURPHYS
Solar/Wind Harmer
0.374
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.72
316011AB1-132 GEN
Solar/Wind Harmer
1.515
962571AG1-106 GEN
Solar/Wind Harmer
1.186
3146173TUNIS
Solar/Wind Harmer
0.083
316190AA2-174 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.083
971547AH1-271 GEN
Solar/Wind Harmer
1.762
3146263WOODLND
Solar/Wind Harmer
0.082
3145783HORNRTN
Solar/Wind Harmer
0.082
970919AG2-571 GEN
Solar/Wind Harmer
2.926
3145683EARLEYS
Solar/Wind Harmer
0.082
970087AG2-069 GEN
Solar/Wind Harmer
6.559
316129AC1-054 GEN
Solar/Wind Harmer
0.308
3145796HORNRTN
Solar/Wind Harmer
0.27
3145796HORNRTN
Solar/Wind Harmer
0.082
971065AG2-659 GEN
Solar/Wind Harmer
3.493
3145823KELFORD
Solar/Wind Harmer
0.081
962861AG1-135 GEN
Solar/Wind Harmer
2.586
3145963POPLR C
Solar/Wind Harmer
0.08
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316212AC1-099_GEN
Solar/Wind Harmer
0.408
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3141726DUNNSVL
Solar/Wind Harmer
0.313
970401AG2-262 GEN
Solar/Wind Harmer
0.457
3145513AHOSKIE
Solar/Wind Harmer
0.173
3145513AHOSKIE
Solar/Wind Harmer
0.083
3146206CASHIE
Solar/Wind Harmer
0.083
970601AG2-382 GEN
Solar/Wind Harmer
3.084
970327AG2-215 GEN
Solar/Wind Harmer
2.71
3145683EARLEYS
Solar/Wind Harmer
0.164
3145683EARLEYS
Solar/Wind Harmer
0.082
3145683EARLEYS
Solar/Wind Harmer
0.082
970831AG2-522 GEN
Solar/Wind Harmer
3.502
970085AG2-068 GEN
Solar/Wind Harmer
4.372
970581AG2-369 GEN
Solar/Wind Harmer
3.76
3145796HORNRTN
Solar/Wind Harmer
0.262
3145796HORNRTN
Solar/Wind Harmer
0.033
3146033SCOT NK
Solar/Wind Harmer
0.319
972189AH1-679 GEN
Adder
1.329
315724AD1-057 GEN
Solar/Wind Harmer
0.29
3145933PARMELE
Solar/Wind Harmer
0.077
966801AG1-551 GEN
Solar/Wind Harmer
0.897
316327AA2-057 GEN
Solar/Wind Harmer
0.115
3150351NORNECKC2
Adder
0.769
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3146233WITAKRS
Solar/Wind Harmer
0.375
3146233WITAKRS
Solar/Wind Harmer
0.051
3138543CONSLDL
Solar/Wind Harmer
0.049
3146073TAR RVR
Solar/Wind Harmer
0.074
3146083TARBORO
Solar/Wind Harmer
0.074
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
961601AG1-000A GEN
Solar/Wind Harmer
5.213
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.088
971683AH1-343 GEN
Solar/Wind Harmer
2.46
316283AC2-100 C
Solar/Wind Harmer
0.122
3141906WESTMOR
Solar/Wind Harmer
0.024
958131AF2-107 GEN
Solar/Wind Harmer
1.633
316044AC1-158 PL1
Solar/Wind Helper
0.848
316450AC1-158 RIC
Solar/Wind Helper
0.226
3147666LOUISA
Solar/Wind Helper
0.269
3141813NORNECK
Solar/Wind Harmer
0.076
316005AA1-067
Solar/Wind Harmer
0.081
3145746EVERETS
Solar/Wind Harmer
0.301
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
970181AG2-120 GEN
Solar/Wind Harmer
0.942
316118AC1-105 GEN
Solar/Wind Harmer
0.194
957861AF2-080 GEN
Solar/Wind Harmer
3.228
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.002
3145573BETHELC
Solar/Wind Harmer
0.074
3145573BETHELC
Solar/Wind Harmer
0.074
3147173SINAI
Solar/Wind Harmer
0.072
3147243WELCO
Solar/Wind Harmer
0.045
970865AG2-541 GEN
Solar/Wind Harmer
2.225
316223AC1-118
Solar/Wind Harmer
0.043
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.477
970163AG2-111 GEN
Solar/Wind Harmer
0.455
3146843MT LREL
Solar/Wind Harmer
0.078
3146843MT LREL
Solar/Wind Harmer
0.078
3145933PARMELE
Solar/Wind Harmer
0.154
3145933PARMELE
Solar/Wind Harmer
0.077
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.795
3150341NORNECKC1
Adder
0.788
3145493TOT1
Solar/Wind Harmer
0.172
3145453TOT5
Solar/Wind Harmer
0.103
3145603CNETO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
1.303
316263AC1-034 GEN
Solar/Wind Harmer
2.786
316222AC1-221 GEN
Solar/Wind Harmer
0.261
316447AC1-158 HLD
Solar/Wind Helper
1.867
315722AD1-056 GEN
Solar/Wind Harmer
0.488
3146293MARTNCO
Solar/Wind Harmer
0.071
3150351NORNECKC2
Adder
0.757
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
316494AC1-189 GEN
Solar/Wind Harmer
0.253
3146233WITAKRS
Solar/Wind Harmer
0.298
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.074
3145493TOT1
Solar/Wind Harmer
0.33
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
316359AB2-059 GEN
Solar/Wind Harmer
0.263
316049AB1-081 GEN
Solar/Wind Harmer
0.42
3142053HEARTS
Solar/Wind Harmer
0.129
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316337AD2-073 GEN
Solar/Wind Harmer
0.06
316045AC1-158 PL2
Solar/Wind Helper
2.716
3147666LOUISA
Solar/Wind Helper
0.467
316192AB2-158 GEN
Solar/Wind Helper
0.764
CPLELTFEXP_CPLE->PJM
CLTF
4.706
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.653
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.067
MECLTFEXP_MEC->PJM
CLTF
1.74
SIGELTFEXP_SIGE->PJM
CLTF
0.053
NYPJM->LTFIMP_NY
CLTF
1.086
LGEELTFEXP_LGEE->PJM
CLTF
0.65
WECLTFEXP_WEC->PJM
CLTF
0.327
LAGNLTFEXP_LAGN->PJM
CLTF
3.494
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.348
TVALTFEXP_TVA->PJM
CLTF
1.763

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.13 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1291.31
MW Contribution:0.56
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.39 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1475.57
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
3148463FAIRFLD
Solar/Wind Helper
0.116
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.39 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1475.54
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.94 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1415.27
MW Contribution:0.7
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.94 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1415.27
MW Contribution:0.7
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:160.44 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1061.7
MW Contribution:0.54
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151591KERR 2
50/50
0.202
970413AG2-270 GEN
50/50
9.029
966251AG1-494 GEN
50/50
1.716
970221AG2-151 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.218
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
0.818
971193AH1-056 GEN
Solar/Wind Harmer
15.872
963181AG1-167 GEN
Solar/Wind Harmer
0.975
959311AF2-222 GEN
Solar/Wind Harmer
17.841
970257AG2-171 GEN
Solar/Wind Harmer
6.184
315785AD2-033 C
Solar/Wind Harmer
1.488
958131AF2-107 GEN
Solar/Wind Harmer
4.835
964241AG1-285 GEN
Solar/Wind Harmer
10.382
316131AB2-060 GEN
Solar/Wind Harmer
0.438
316478AD1-087 GEN
Solar/Wind Harmer
0.337
316486AD2-202 GEN
Solar/Wind Harmer
0.099
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.582
3147043LAWRENC
Solar/Wind Harmer
0.049
971683AH1-343 GEN
Solar/Wind Harmer
2.828
3132273ORANGE
Solar/Wind Helper
0.023
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151601KERR 3
50/50
0.202
3151581KERR 1
50/50
0.072
3151531CLOVER1
50/50
2.069
3147043LAWRENC
50/50
0.777
970937AG2-583 GEN
Solar/Wind Harmer
36.866
316336AC2-165 C
Solar/Wind Harmer
0.024
972003AH1-546 GEN
Solar/Wind Harmer
24.522
971377AH1-170 GEN
Solar/Wind Harmer
5.701
3147623JAMES R
Solar/Wind Harmer
1.238
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.188
3146926FARMVIL
Solar/Wind Harmer
0.218
963171AG1-166 GEN
Solar/Wind Harmer
1.299
971563AH1-280 GEN
Solar/Wind Harmer
2.599
970685AG2-442 GEN
Solar/Wind Harmer
16.367
962491AG1-098 GEN
Solar/Wind Harmer
7.651
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.098
970401AG2-262 GEN
Solar/Wind Harmer
0.618
957481AF2-042 GEN
Solar/Wind Harmer
24.997
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.611
316129AC1-054 GEN
Solar/Wind Harmer
0.309
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
4.899
962751AG1-124 GEN
Solar/Wind Harmer
3.147
960081AF2-299 GEN
Solar/Wind Harmer
0.55
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
3152661PLYWOOD A
50/50
0.202
971489AH1-241 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
1.881
3146776BUCKING
Solar/Wind Harmer
0.152
315821AE2-092 GEN
Solar/Wind Harmer
0.02
970301AG2-198 GEN
Solar/Wind Harmer
11.214
3147133PAMPLIN
Solar/Wind Harmer
0.26
3147133PAMPLIN
Solar/Wind Harmer
0.208
958211AF2-115 GEN
Solar/Wind Harmer
2.924
963191AG1-168 GEN
Solar/Wind Harmer
0.975
971741AH1-377 GEN
Solar/Wind Harmer
22.982
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.246
971775AH1-396 GEN
Solar/Wind Harmer
0.309
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.277
964791AG1-342 GEN
Solar/Wind Harmer
2.024
3146843MT LREL
Solar/Wind Harmer
0.105
3146843MT LREL
Solar/Wind Harmer
0.105
939181AE1-148 GEN
Solar/Wind Harmer
5.007
970099AG2-077 GEN
Solar/Wind Harmer
9.999
970933AG2-581 GEN
Solar/Wind Harmer
5.154
942751AE2-291 GEN
Solar/Wind Harmer
3.374
966001AG1-469 GEN
Solar/Wind Helper
0.159
972205AH1-687 GEN
50/50
27.249
3151611KERR 4
50/50
0.202
3151621KERR 5
50/50
0.202
3151631KERR 6
50/50
0.202
3151641KERR 7
50/50
0.202
3151541CLOVER2
50/50
2.059
971447AH1-217 GEN
Solar/Wind Harmer
15.037
971845AH1-439 GEN
Solar/Wind Harmer
20.916
970285AG2-188 GEN
Solar/Wind Harmer
35.131
270494AE1-108_GEN
Solar/Wind Harmer
5.032
315657AE1-056 GEN
Solar/Wind Harmer
8.99
946301AF1-294 GEN
Solar/Wind Harmer
4.808
961791AG1-021 GEN
Solar/Wind Harmer
2.339
970683AG2-441 GEN
Solar/Wind Harmer
14.613
970681AG2-440 GEN
Solar/Wind Harmer
11.691
3144303KENBRDG
Solar/Wind Harmer
0.154
971443AH1-215 GEN
Solar/Wind Harmer
3.209
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.244
3147173SINAI
Solar/Wind Harmer
0.084
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.381
970865AG2-541 GEN
Solar/Wind Harmer
2.545
316123AC1-075 GEN
Solar/Wind Harmer
0.091
970165AG2-112 GEN
Solar/Wind Harmer
0.539
970163AG2-111 GEN
Solar/Wind Harmer
0.514
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.15 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1230.87
MW Contribution:0.71
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
971489AH1-241 GEN
Solar/Wind Harmer
35.629
3146776BUCKING
Solar/Wind Harmer
-0.21
3146776BUCKING
Solar/Wind Harmer
-0.017
315821AE2-092 GEN
Solar/Wind Harmer
7.77
970301AG2-198 GEN
Solar/Wind Harmer
14.765
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.277
963191AG1-168 GEN
Solar/Wind Harmer
2.566
971741AH1-377 GEN
Solar/Wind Harmer
30.26
316034AC1-036 C
Solar/Wind Harmer
0.404
970323AG2-213 GEN
Solar/Wind Harmer
10.857
971775AH1-396 GEN
Solar/Wind Harmer
1.546
313527AB2-043 GEN
Solar/Wind Harmer
2.466
962561AG1-105 GEN
Solar/Wind Harmer
6.948
964791AG1-342 GEN
Solar/Wind Harmer
2.529
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
939181AE1-148 GEN
Solar/Wind Harmer
6.592
970099AG2-077 GEN
Solar/Wind Harmer
13.165
970933AG2-581 GEN
Solar/Wind Harmer
6.786
942751AE2-291 GEN
Solar/Wind Harmer
4.443
966001AG1-469 GEN
Solar/Wind Helper
0.159
972205AH1-687 GEN
50/50
27.249
971447AH1-217 GEN
Solar/Wind Harmer
19.799
971845AH1-439 GEN
Solar/Wind Harmer
27.54
970285AG2-188 GEN
Solar/Wind Harmer
43.657
270494AE1-108_GEN
Solar/Wind Harmer
12.267
315657AE1-056 GEN
Solar/Wind Harmer
10.983
946301AF1-294 GEN
Solar/Wind Harmer
7.014
961791AG1-021 GEN
Solar/Wind Harmer
3.422
970683AG2-441 GEN
Solar/Wind Harmer
19.241
970681AG2-440 GEN
Solar/Wind Harmer
15.393
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.225
316239AB2-077_GEN
Solar/Wind Harmer
0.446
316238AB2-078_GEN
Solar/Wind Harmer
0.446
316118AC1-105 GEN
Solar/Wind Harmer
0.73
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.452
970865AG2-541 GEN
Solar/Wind Harmer
3.351
316123AC1-075 GEN
Solar/Wind Harmer
0.806
970165AG2-112 GEN
Solar/Wind Harmer
0.709
970163AG2-111 GEN
Solar/Wind Harmer
0.677
946281AF1-292 GEN
Solar/Wind Harmer
0.144
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
970937AG2-583 GEN
Solar/Wind Harmer
48.541
316336AC2-165 C
Solar/Wind Harmer
11.736
972003AH1-546 GEN
Solar/Wind Harmer
32.342
971377AH1-170 GEN
Solar/Wind Harmer
7.506
3147623JAMES R
Solar/Wind Harmer
0.929
316322AB2-045
Solar/Wind Harmer
1.778
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
963171AG1-166 GEN
Solar/Wind Harmer
3.422
971563AH1-280 GEN
Solar/Wind Harmer
3.422
970685AG2-442 GEN
Solar/Wind Harmer
21.55
962491AG1-098 GEN
Solar/Wind Harmer
10.074
316237AB2-079_GEN
Solar/Wind Harmer
0.446
315693AD1-088 GEN
Solar/Wind Harmer
7.137
970401AG2-262 GEN
Solar/Wind Harmer
0.773
957481AF2-042 GEN
Solar/Wind Harmer
32.913
315687AD1-152 GEN
Solar/Wind Harmer
1.189
971065AG2-659 GEN
Solar/Wind Harmer
4.755
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.732
316003AC1-222 GEN
Solar/Wind Harmer
0.879
971795AH1-408 GEN
Solar/Wind Harmer
6.192
962751AG1-124 GEN
Solar/Wind Harmer
4.595
960081AF2-299 GEN
Solar/Wind Harmer
0.724
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
970221AG2-151 GEN
Solar/Wind Harmer
37.53
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.024
942461AE2-259 GEN
Solar/Wind Harmer
5.218
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
-0.092
971193AH1-056 GEN
Solar/Wind Harmer
18.305
963181AG1-167 GEN
Solar/Wind Harmer
2.566
959311AF2-222 GEN
Solar/Wind Harmer
23.538
970257AG2-171 GEN
Solar/Wind Harmer
8.143
315785AD2-033 C
Solar/Wind Harmer
4.66
958131AF2-107 GEN
Solar/Wind Harmer
6.437
964241AG1-285 GEN
Solar/Wind Harmer
13.669
316131AB2-060 GEN
Solar/Wind Harmer
1.687
316478AD1-087 GEN
Solar/Wind Harmer
0.939
316486AD2-202 GEN
Solar/Wind Harmer
0.275
316248AF1-058 C
Solar/Wind Harmer
0.284
960061AF2-297 GEN
Solar/Wind Harmer
4.717
3147043LAWRENC
Solar/Wind Harmer
-0.005
971683AH1-343 GEN
Solar/Wind Harmer
3.724
966621AG1-532 GEN
Solar/Wind Harmer
0.131
3132273ORANGE
Solar/Wind Helper
0.023
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 39-91_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 39-91_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.53 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:950.8
MW Contribution:0.64
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.448
3144293JTRSVLE
50/50
0.697
970221AG2-151 GEN
Solar/Wind Harmer
32.428
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.331
316313AB2-026
Solar/Wind Harmer
0.751
316258AE1-075 C
Solar/Wind Harmer
0.676
316405AF2-144 C
Solar/Wind Harmer
0.713
3143336POWHATN
Solar/Wind Harmer
2.809
970909AG2-566 GEN
Solar/Wind Harmer
2.37
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.405
963181AG1-167 GEN
Solar/Wind Harmer
2.173
959311AF2-222 GEN
Solar/Wind Harmer
20.328
970257AG2-171 GEN
Solar/Wind Harmer
7.062
315785AD2-033 C
Solar/Wind Harmer
4.068
958131AF2-107 GEN
Solar/Wind Harmer
5.359
964241AG1-285 GEN
Solar/Wind Harmer
12.184
316131AB2-060 GEN
Solar/Wind Harmer
1.528
316478AD1-087 GEN
Solar/Wind Harmer
0.928
316486AD2-202 GEN
Solar/Wind Harmer
0.272
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.272
960061AF2-297 GEN
Solar/Wind Harmer
4.511
971683AH1-343 GEN
Solar/Wind Harmer
3.497
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.589
3150861SPRUNCD
Adder
0.274
970917AG2-570 GEN
Solar/Wind Harmer
16.228
316365GEN2_N
Solar/Wind Harmer
0.43
3148013FISHERV
Solar/Wind Helper
0.221
316499AE2-029_GEN
Solar/Wind Helper
0.571
315616AA1-038_C
Solar/Wind Helper
0.608
3132273ORANGE
Solar/Wind Helper
0.026
3151931BEARGRDN S1
50/50
5.74
3151911BEARGRDN G1
50/50
4.448
3144293JTRSVLE
50/50
0.697
971377AH1-170 GEN
Solar/Wind Harmer
6.486
3147623JAMES R
Solar/Wind Harmer
0.803
972003AH1-546 GEN
Solar/Wind Harmer
25.797
970937AG2-583 GEN
Solar/Wind Harmer
31.587
316322AB2-045
Solar/Wind Harmer
1.434
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.623
3143336POWHATN
Solar/Wind Harmer
3.304
963171AG1-166 GEN
Solar/Wind Harmer
2.897
971563AH1-280 GEN
Solar/Wind Harmer
2.897
970685AG2-442 GEN
Solar/Wind Harmer
18.436
962491AG1-098 GEN
Solar/Wind Harmer
9.378
316237AB2-079_GEN
Solar/Wind Harmer
0.407
315693AD1-088 GEN
Solar/Wind Harmer
6.713
970401AG2-262 GEN
Solar/Wind Harmer
0.72
957481AF2-042 GEN
Solar/Wind Harmer
33.181
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.173
971065AG2-659 GEN
Solar/Wind Harmer
4.785
3147043LAWRENC
Adder
0.762
316129AC1-054 GEN
Solar/Wind Harmer
0.821
971795AH1-408 GEN
Solar/Wind Harmer
6.648
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.833
960081AF2-299 GEN
Solar/Wind Harmer
0.851
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.274
970919AG2-571 GEN
Solar/Wind Harmer
2.054
970087AG2-069 GEN
Solar/Wind Harmer
6.064
316023GEN1_S
Solar/Wind Harmer
0.43
3147983MERCK5
Solar/Wind Helper
0.062
3144293JTRSVLE
50/50
0.697
3144293JTRSVLE
50/50
0.587
971489AH1-241 GEN
Solar/Wind Harmer
30.786
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.481
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.621
963191AG1-168 GEN
Solar/Wind Harmer
2.173
971741AH1-377 GEN
Solar/Wind Harmer
25.942
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.416
971775AH1-396 GEN
Solar/Wind Harmer
1.341
313527AB2-043 GEN
Solar/Wind Harmer
2.245
962561AG1-105 GEN
Solar/Wind Harmer
6.444
939181AE1-148 GEN
Solar/Wind Harmer
6.287
964791AG1-342 GEN
Solar/Wind Harmer
2.356
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.272
971223AH1-071 GEN
Solar/Wind Harmer
1.326
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.828
316181AB2-040 GEN
Solar/Wind Harmer
1.022
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.794
3145593CAROLNA
Solar/Wind Harmer
0.059
3145783HORNRTN
Solar/Wind Harmer
0.823
3145783HORNRTN
Solar/Wind Harmer
0.658
3145783HORNRTN
Solar/Wind Harmer
0.206
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.692
972187AH1-678 GEN
Adder
1.699
972185AH1-677 GEN
Adder
3.299
966001AG1-469 GEN
Solar/Wind Helper
0.187
3132123MT JACKSON
Solar/Wind Helper
0.368
972205AH1-687 GEN
50/50
21.692
971447AH1-217 GEN
Solar/Wind Harmer
18.622
971845AH1-439 GEN
Solar/Wind Harmer
22.237
270494AE1-108_GEN
Solar/Wind Harmer
10.551
970285AG2-188 GEN
Solar/Wind Harmer
35.335
315657AE1-056 GEN
Solar/Wind Harmer
9.243
946301AF1-294 GEN
Solar/Wind Harmer
5.939
961791AG1-021 GEN
Solar/Wind Harmer
2.897
970683AG2-441 GEN
Solar/Wind Harmer
16.461
970681AG2-440 GEN
Solar/Wind Harmer
13.169
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.67
316239AB2-077_GEN
Solar/Wind Harmer
0.407
316238AB2-078_GEN
Solar/Wind Harmer
0.407
316118AC1-105 GEN
Solar/Wind Harmer
0.689
970831AG2-522 GEN
Solar/Wind Harmer
4.571
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.238
971281AH1-106 GEN
Solar/Wind Harmer
1.438
971283AH1-107 GEN
Solar/Wind Harmer
1.438
970865AG2-541 GEN
Solar/Wind Harmer
3.115
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.055
971967AH1-528 GEN
Solar/Wind Harmer
13.769
3137643SOCKMAN
Solar/Wind Harmer
-0.029
316123AC1-075 GEN
Solar/Wind Harmer
0.731
970165AG2-112 GEN
Solar/Wind Harmer
0.643
970163AG2-111 GEN
Solar/Wind Harmer
0.614
315607AA1-063A GEN
Solar/Wind Harmer
0.681
971285AH1-108 GEN
Adder
0.449
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
970085AG2-068 GEN
Solar/Wind Harmer
4.042
970581AG2-369 GEN
Solar/Wind Harmer
3.477
941031AE2-094 GEN
Solar/Wind Harmer
11.972
944011AF1-069 GEN
Solar/Wind Harmer
3.751
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.132
3148013FISHERV
Solar/Wind Helper
0.127
3148463FAIRFLD
Solar/Wind Helper
0.134
CPLELTFEXP_CPLE->PJM
CLTF
3.247
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.539
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.798
MECLTFEXP_MEC->PJM
CLTF
0.142
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.409
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.087
LAGNLTFEXP_LAGN->PJM
CLTF
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.305
TVALTFEXP_TVA->PJM
CLTF
0.589

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P2-2: DOOMS B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: DOOMS B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.53 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:934.63
MW Contribution:0.64
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.696
3144293JTRSVLE
50/50
0.586
315821AE2-092 GEN
Solar/Wind Harmer
10.863
971489AH1-241 GEN
Solar/Wind Harmer
30.763
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.465
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.616
963191AG1-168 GEN
Solar/Wind Harmer
2.17
971741AH1-377 GEN
Solar/Wind Harmer
25.905
316034AC1-036 C
Solar/Wind Harmer
0.349
970323AG2-213 GEN
Solar/Wind Harmer
9.401
971775AH1-396 GEN
Solar/Wind Harmer
1.339
313527AB2-043 GEN
Solar/Wind Harmer
2.24
962561AG1-105 GEN
Solar/Wind Harmer
6.427
939181AE1-148 GEN
Solar/Wind Harmer
6.27
964791AG1-342 GEN
Solar/Wind Harmer
2.35
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.235
971223AH1-071 GEN
Solar/Wind Harmer
1.322
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.8
316181AB2-040 GEN
Solar/Wind Harmer
1.018
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
50/50
21.676
971447AH1-217 GEN
Solar/Wind Harmer
18.608
971845AH1-439 GEN
Solar/Wind Harmer
22.218
270494AE1-108_GEN
Solar/Wind Harmer
10.541
970285AG2-188 GEN
Solar/Wind Harmer
35.303
315657AE1-056 GEN
Solar/Wind Harmer
9.23
946301AF1-294 GEN
Solar/Wind Harmer
5.931
961791AG1-021 GEN
Solar/Wind Harmer
2.893
970683AG2-441 GEN
Solar/Wind Harmer
16.436
970681AG2-440 GEN
Solar/Wind Harmer
13.149
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.664
316239AB2-077_GEN
Solar/Wind Harmer
0.406
316238AB2-078_GEN
Solar/Wind Harmer
0.406
316118AC1-105 GEN
Solar/Wind Harmer
0.687
970831AG2-522 GEN
Solar/Wind Harmer
4.556
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.237
971281AH1-106 GEN
Solar/Wind Harmer
1.433
971283AH1-107 GEN
Solar/Wind Harmer
1.433
970865AG2-541 GEN
Solar/Wind Harmer
3.104
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.051
971967AH1-528 GEN
Solar/Wind Harmer
13.715
3137643SOCKMAN
Solar/Wind Harmer
-0.028
316123AC1-075 GEN
Solar/Wind Harmer
0.728
970165AG2-112 GEN
Solar/Wind Harmer
0.641
970163AG2-111 GEN
Solar/Wind Harmer
0.611
315607AA1-063A GEN
Solar/Wind Harmer
0.678
971285AH1-108 GEN
Adder
0.447
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.659
970673AG2-436 GEN
Solar/Wind Harmer
6.916
970085AG2-068 GEN
Solar/Wind Harmer
4.024
970581AG2-369 GEN
Solar/Wind Harmer
3.461
941031AE2-094 GEN
Solar/Wind Harmer
11.918
944011AF1-069 GEN
Solar/Wind Harmer
3.734
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.136
3148013FISHERV
Solar/Wind Helper
0.13
3148463FAIRFLD
Solar/Wind Helper
0.135
3151921BEARGRDN G2
50/50
4.444
3144293JTRSVLE
50/50
0.696
970221AG2-151 GEN
Solar/Wind Harmer
32.404
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.326
316313AB2-026
Solar/Wind Harmer
0.75
966811AG1-552 GEN
Solar/Wind Harmer
0.791
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.819
3145783HORNRTN
Solar/Wind Harmer
0.655
3145783HORNRTN
Solar/Wind Harmer
0.205
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.689
972187AH1-678 GEN
Adder
1.691
972185AH1-677 GEN
Adder
3.285
966001AG1-469 GEN
Solar/Wind Helper
0.188
3132123MT JACKSON
Solar/Wind Helper
0.367
3151931BEARGRDN S1
50/50
5.736
3151911BEARGRDN G1
50/50
4.444
3144293JTRSVLE
50/50
0.696
971377AH1-170 GEN
Solar/Wind Harmer
6.481
3147623JAMES R
Solar/Wind Harmer
0.802
972003AH1-546 GEN
Solar/Wind Harmer
25.777
970937AG2-583 GEN
Solar/Wind Harmer
31.56
316322AB2-045
Solar/Wind Harmer
1.433
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.617
3143336POWHATN
Solar/Wind Harmer
3.3
963171AG1-166 GEN
Solar/Wind Harmer
2.893
971563AH1-280 GEN
Solar/Wind Harmer
2.893
970685AG2-442 GEN
Solar/Wind Harmer
18.409
962491AG1-098 GEN
Solar/Wind Harmer
9.357
316237AB2-079_GEN
Solar/Wind Harmer
0.406
315693AD1-088 GEN
Solar/Wind Harmer
6.698
970401AG2-262 GEN
Solar/Wind Harmer
0.718
957481AF2-042 GEN
Solar/Wind Harmer
33.088
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.169
971065AG2-659 GEN
Solar/Wind Harmer
4.77
3147043LAWRENC
Adder
0.76
316129AC1-054 GEN
Solar/Wind Harmer
0.818
971795AH1-408 GEN
Solar/Wind Harmer
6.626
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.83
960081AF2-299 GEN
Solar/Wind Harmer
0.847
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.273
970919AG2-571 GEN
Solar/Wind Harmer
2.045
970087AG2-069 GEN
Solar/Wind Harmer
6.037
316023GEN1_S
Solar/Wind Harmer
0.428
3147983MERCK5
Solar/Wind Helper
0.063
316258AE1-075 C
Solar/Wind Harmer
0.675
316405AF2-144 C
Solar/Wind Harmer
0.712
3143336POWHATN
Solar/Wind Harmer
2.805
970909AG2-566 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.384
963181AG1-167 GEN
Solar/Wind Harmer
2.17
959311AF2-222 GEN
Solar/Wind Harmer
20.295
970257AG2-171 GEN
Solar/Wind Harmer
7.05
315785AD2-033 C
Solar/Wind Harmer
4.061
958131AF2-107 GEN
Solar/Wind Harmer
5.349
964241AG1-285 GEN
Solar/Wind Harmer
12.16
316131AB2-060 GEN
Solar/Wind Harmer
1.525
316478AD1-087 GEN
Solar/Wind Harmer
0.925
316486AD2-202 GEN
Solar/Wind Harmer
0.271
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.271
960061AF2-297 GEN
Solar/Wind Harmer
4.496
971683AH1-343 GEN
Solar/Wind Harmer
3.484
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.586
3150861SPRUNCD
Adder
0.273
970917AG2-570 GEN
Solar/Wind Harmer
16.156
316365GEN2_N
Solar/Wind Harmer
0.428
3148013FISHERV
Solar/Wind Helper
0.227
316499AE2-029_GEN
Solar/Wind Helper
0.572
315616AA1-038_C
Solar/Wind Helper
0.611
3132273ORANGE
Solar/Wind Helper
0.026
CPLELTFEXP_CPLE->PJM
CLTF
3.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.302
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.731
MECLTFEXP_MEC->PJM
CLTF
0.113
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.42
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.046
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.122
LAGNLTFEXP_LAGN->PJM
CLTF
1.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.249
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.571

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.52 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:894.11
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.143
971447AH1-217 GEN
Solar/Wind Harmer
14.529
971845AH1-439 GEN
Solar/Wind Harmer
20.7
970285AG2-188 GEN
Solar/Wind Harmer
32.906
270494AE1-108_GEN
Solar/Wind Harmer
9.015
315657AE1-056 GEN
Solar/Wind Harmer
8.675
946301AF1-294 GEN
Solar/Wind Harmer
5.582
961791AG1-021 GEN
Solar/Wind Harmer
2.723
970683AG2-441 GEN
Solar/Wind Harmer
15.505
970681AG2-440 GEN
Solar/Wind Harmer
12.404
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.467
316239AB2-077_GEN
Solar/Wind Harmer
0.389
316238AB2-078_GEN
Solar/Wind Harmer
0.389
316118AC1-105 GEN
Solar/Wind Harmer
0.665
970831AG2-522 GEN
Solar/Wind Harmer
4.449
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Harmer
0.225
971281AH1-106 GEN
Solar/Wind Harmer
1.359
971283AH1-107 GEN
Solar/Wind Harmer
1.359
946281AF1-292 GEN
Solar/Wind Harmer
0.166
970865AG2-541 GEN
Solar/Wind Harmer
2.988
316087AB2-174 GEN
Solar/Wind Harmer
1.035
971967AH1-528 GEN
Solar/Wind Harmer
13.383
3137643SOCKMAN
Solar/Wind Harmer
-0.028
315607AA1-063A GEN
Solar/Wind Harmer
0.672
3146043SEABORD
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.694
970165AG2-112 GEN
Solar/Wind Harmer
0.611
970163AG2-111 GEN
Solar/Wind Harmer
0.583
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
970673AG2-436 GEN
Solar/Wind Harmer
13.415
970673AG2-436 GEN
Solar/Wind Harmer
6.792
971285AH1-108 GEN
Adder
0.428
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.12
3144293JTRSVLE
50/50
0.655
3144293JTRSVLE
50/50
0.551
971489AH1-241 GEN
Solar/Wind Harmer
26.337
3146776BUCKING
Solar/Wind Harmer
-0.158
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.386
970301AG2-198 GEN
Solar/Wind Harmer
11.705
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.404
963191AG1-168 GEN
Solar/Wind Harmer
2.042
971741AH1-377 GEN
Solar/Wind Harmer
24.381
316034AC1-036 C
Solar/Wind Harmer
0.331
970323AG2-213 GEN
Solar/Wind Harmer
8.895
971775AH1-396 GEN
Solar/Wind Harmer
1.267
313527AB2-043 GEN
Solar/Wind Harmer
2.141
962561AG1-105 GEN
Solar/Wind Harmer
6.187
939181AE1-148 GEN
Solar/Wind Harmer
6.061
964791AG1-342 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
12.748
971223AH1-071 GEN
Solar/Wind Harmer
1.248
3143526WINTERP
Solar/Wind Harmer
-0.043
970933AG2-581 GEN
Solar/Wind Harmer
7.571
316181AB2-040 GEN
Solar/Wind Harmer
1.004
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.784
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.814
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.204
3145783HORNRTN
Solar/Wind Harmer
0.081
316426AA2-053 GEN
Solar/Wind Harmer
0.684
972187AH1-678 GEN
Adder
1.664
972185AH1-677 GEN
Adder
3.229
966001AG1-469 GEN
Solar/Wind Helper
0.189
3151931BEARGRDN S1
50/50
5.33
3151911BEARGRDN G1
50/50
4.13
3144293JTRSVLE
50/50
0.655
972003AH1-546 GEN
Solar/Wind Harmer
23.962
971377AH1-170 GEN
Solar/Wind Harmer
5.548
3147623JAMES R
Solar/Wind Harmer
0.687
970937AG2-583 GEN
Solar/Wind Harmer
29.352
316322AB2-045
Solar/Wind Harmer
1.334
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
3151921BEARGRDN G2
50/50
4.13
3144293JTRSVLE
50/50
0.655
970221AG2-151 GEN
Solar/Wind Harmer
27.742
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.053
316313AB2-026
Solar/Wind Harmer
0.699
316258AE1-075 C
Solar/Wind Harmer
0.63
316405AF2-144 C
Solar/Wind Harmer
0.664
3143336POWHATN
Solar/Wind Harmer
2.616
970909AG2-566 GEN
Solar/Wind Harmer
2.223
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.459
963181AG1-167 GEN
Solar/Wind Harmer
2.042
959311AF2-222 GEN
Solar/Wind Harmer
19.185
970257AG2-171 GEN
Solar/Wind Harmer
6.671
315785AD2-033 C
Solar/Wind Harmer
3.847
964241AG1-285 GEN
Solar/Wind Harmer
11.573
316131AB2-060 GEN
Solar/Wind Harmer
1.457
958131AF2-107 GEN
Solar/Wind Harmer
4.54
316478AD1-087 GEN
Solar/Wind Harmer
0.893
316486AD2-202 GEN
Solar/Wind Harmer
0.261
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.376
971683AH1-343 GEN
Solar/Wind Harmer
3.368
966621AG1-532 GEN
Solar/Wind Harmer
0.15
313506AB2-031 GEN
Solar/Wind Harmer
0.578
970917AG2-570 GEN
Solar/Wind Harmer
16.041
3150861SPRUNCD
Adder
0.261
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.545
316336AC2-165 C
Solar/Wind Harmer
5.233
3143336POWHATN
Solar/Wind Harmer
3.078
963171AG1-166 GEN
Solar/Wind Harmer
2.723
971563AH1-280 GEN
Solar/Wind Harmer
2.723
970685AG2-442 GEN
Solar/Wind Harmer
17.365
962491AG1-098 GEN
Solar/Wind Harmer
8.919
316237AB2-079_GEN
Solar/Wind Harmer
0.389
315693AD1-088 GEN
Solar/Wind Harmer
6.394
970401AG2-262 GEN
Solar/Wind Harmer
0.692
957481AF2-042 GEN
Solar/Wind Harmer
31.87
3143226MDLTHAN
Solar/Wind Harmer
-0.01
315687AD1-152 GEN
Solar/Wind Harmer
1.137
971065AG2-659 GEN
Solar/Wind Harmer
4.648
3147043LAWRENC
Adder
0.737
316129AC1-054 GEN
Solar/Wind Harmer
0.798
971795AH1-408 GEN
Solar/Wind Harmer
6.453
3143526WINTERP
Solar/Wind Harmer
-0.043
316003AC1-222 GEN
Solar/Wind Harmer
0.805
960081AF2-299 GEN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.083
970919AG2-571 GEN
Solar/Wind Harmer
2.03
970087AG2-069 GEN
Solar/Wind Harmer
6
3150851SPRUNCC
Adder
0.261
3147983MERCK5
Solar/Wind Helper
0.055
CPLELTFEXP_CPLE->PJM
CLTF
3.638
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.961
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.309
MECLTFEXP_MEC->PJM
CLTF
0.208
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.389
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.045
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.115
LAGNLTFEXP_LAGN->PJM
CLTF
1.574
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.039
TVALTFEXP_TVA->PJM
CLTF
0.757

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.26 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:859.67
MW Contribution:0.6
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.07
3144293JTRSVLE
50/50
0.636
970221AG2-151 GEN
Solar/Wind Harmer
27.317
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.018
942461AE2-259 GEN
Solar/Wind Harmer
3.955
316313AB2-026
Solar/Wind Harmer
0.683
316258AE1-075 C
Solar/Wind Harmer
0.615
316405AF2-144 C
Solar/Wind Harmer
0.649
3143336POWHATN
Solar/Wind Harmer
2.554
970909AG2-566 GEN
Solar/Wind Harmer
2.162
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.064
963181AG1-167 GEN
Solar/Wind Harmer
1.983
959311AF2-222 GEN
Solar/Wind Harmer
18.545
970257AG2-171 GEN
Solar/Wind Harmer
6.442
315785AD2-033 C
Solar/Wind Harmer
3.71
964241AG1-285 GEN
Solar/Wind Harmer
11.106
958131AF2-107 GEN
Solar/Wind Harmer
4.655
316131AB2-060 GEN
Solar/Wind Harmer
1.393
316478AD1-087 GEN
Solar/Wind Harmer
0.841
316486AD2-202 GEN
Solar/Wind Harmer
0.246
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.249
960061AF2-297 GEN
Solar/Wind Harmer
4.131
971683AH1-343 GEN
Solar/Wind Harmer
3.224
966621AG1-532 GEN
Solar/Wind Harmer
0.138
313506AB2-031 GEN
Solar/Wind Harmer
0.528
316499AE2-029_GEN
Solar/Wind Helper
0.551
3148013FISHERV
Solar/Wind Helper
0.152
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.264
3151931BEARGRDN S1
50/50
5.253
3151911BEARGRDN G1
50/50
4.07
3144293JTRSVLE
50/50
0.636
972003AH1-546 GEN
Solar/Wind Harmer
23.604
971377AH1-170 GEN
Solar/Wind Harmer
5.463
3147623JAMES R
Solar/Wind Harmer
0.676
970937AG2-583 GEN
Solar/Wind Harmer
28.861
316322AB2-045
Solar/Wind Harmer
1.311
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
5.122
3143336POWHATN
Solar/Wind Harmer
3.004
963171AG1-166 GEN
Solar/Wind Harmer
2.645
971563AH1-280 GEN
Solar/Wind Harmer
2.645
970685AG2-442 GEN
Solar/Wind Harmer
16.824
962491AG1-098 GEN
Solar/Wind Harmer
8.511
316237AB2-079_GEN
Solar/Wind Harmer
0.371
315693AD1-088 GEN
Solar/Wind Harmer
6.09
970401AG2-262 GEN
Solar/Wind Harmer
0.658
957481AF2-042 GEN
Solar/Wind Harmer
29.994
3143226MDLTHAN
Solar/Wind Harmer
-0.009
315687AD1-152 GEN
Solar/Wind Harmer
1.066
971065AG2-659 GEN
Solar/Wind Harmer
4.339
3147043LAWRENC
Adder
0.688
316129AC1-054 GEN
Solar/Wind Harmer
0.744
971795AH1-408 GEN
Solar/Wind Harmer
5.995
316003AC1-222 GEN
Solar/Wind Harmer
0.766
3143526WINTERP
Solar/Wind Harmer
-0.04
960081AF2-299 GEN
Solar/Wind Harmer
0.763
3147983MERCK5
Solar/Wind Helper
0.06
316192AB2-158 GEN
Solar/Wind Helper
0.803
3147666LOUISA
Solar/Wind Helper
0.46
3144293JTRSVLE
50/50
0.636
3144293JTRSVLE
50/50
0.536
971489AH1-241 GEN
Solar/Wind Harmer
25.934
3146776BUCKING
Solar/Wind Harmer
-0.155
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.214
970301AG2-198 GEN
Solar/Wind Harmer
11.385
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.306
963191AG1-168 GEN
Solar/Wind Harmer
1.983
971741AH1-377 GEN
Solar/Wind Harmer
23.646
316034AC1-036 C
Solar/Wind Harmer
0.319
970323AG2-213 GEN
Solar/Wind Harmer
8.59
971775AH1-396 GEN
Solar/Wind Harmer
1.223
313527AB2-043 GEN
Solar/Wind Harmer
2.045
962561AG1-105 GEN
Solar/Wind Harmer
5.883
939181AE1-148 GEN
Solar/Wind Harmer
5.719
964791AG1-342 GEN
Solar/Wind Harmer
2.152
3146843MT LREL
Solar/Wind Harmer
-0.01
3146843MT LREL
Solar/Wind Harmer
-0.01
970099AG2-077 GEN
Solar/Wind Harmer
11.998
971223AH1-071 GEN
Solar/Wind Harmer
1.179
3143526WINTERP
Solar/Wind Harmer
-0.04
970933AG2-581 GEN
Solar/Wind Harmer
7.011
316181AB2-040 GEN
Solar/Wind Harmer
0.917
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.713
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.2
3132123MT JACKSON
Solar/Wind Helper
0.351
972205AH1-687 GEN
50/50
19.851
971447AH1-217 GEN
Solar/Wind Harmer
14.274
971845AH1-439 GEN
Solar/Wind Harmer
20.334
970285AG2-188 GEN
Solar/Wind Harmer
32.307
270494AE1-108_GEN
Solar/Wind Harmer
8.922
315657AE1-056 GEN
Solar/Wind Harmer
8.438
946301AF1-294 GEN
Solar/Wind Harmer
5.421
961791AG1-021 GEN
Solar/Wind Harmer
2.645
970683AG2-441 GEN
Solar/Wind Harmer
15.022
970681AG2-440 GEN
Solar/Wind Harmer
12.017
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.347
316239AB2-077_GEN
Solar/Wind Harmer
0.371
316238AB2-078_GEN
Solar/Wind Harmer
0.371
316118AC1-105 GEN
Solar/Wind Harmer
0.63
970831AG2-522 GEN
Solar/Wind Harmer
4.14
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Harmer
0.21
971281AH1-106 GEN
Solar/Wind Harmer
1.27
971283AH1-107 GEN
Solar/Wind Harmer
1.27
970865AG2-541 GEN
Solar/Wind Harmer
2.883
946281AF1-292 GEN
Solar/Wind Harmer
0.152
316087AB2-174 GEN
Solar/Wind Harmer
0.947
971967AH1-528 GEN
Solar/Wind Harmer
12.263
3137643SOCKMAN
Solar/Wind Harmer
-0.026
316123AC1-075 GEN
Solar/Wind Harmer
0.683
970165AG2-112 GEN
Solar/Wind Harmer
0.601
970163AG2-111 GEN
Solar/Wind Harmer
0.573
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.091
3148013FISHERV
Solar/Wind Helper
0.088
CPLELTFEXP_CPLE->PJM
CLTF
3.029
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.957
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.668
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.188
MECLTFEXP_MEC->PJM
CLTF
0.344
SIGELTFEXP_SIGE->PJM
CLTF
0.009
NYPJM->LTFIMP_NY
CLTF
0.444
LGEELTFEXP_LGEE->PJM
CLTF
0.079
WECLTFEXP_WEC->PJM
CLTF
0.033
LAGNLTFEXP_LAGN->PJM
CLTF
1.383
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.08
TVALTFEXP_TVA->PJM
CLTF
0.685

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.02 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1045.98
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.142
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.272
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.898
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.85
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.272
3151621KERR 5
50/50
0.272
3151631KERR 6
50/50
0.272
3151641KERR 7
50/50
0.272
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.795
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.467
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.146
970831AG2-522 GEN
Solar/Wind Harmer
10.282
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.056
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.561
957861AF2-080 GEN
Solar/Wind Harmer
7.524
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.04
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.005
971443AH1-215 GEN
Solar/Wind Harmer
2.448
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.309
315733AD1-074 GEN2
Solar/Wind Harmer
2.309
315735AD1-075 GEN1
Solar/Wind Harmer
1.155
970683AG2-441 GEN
Solar/Wind Harmer
8.785
970681AG2-440 GEN
Solar/Wind Harmer
7.028
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.616
961791AG1-021 GEN
Solar/Wind Harmer
1.276
316118AC1-105 GEN
Solar/Wind Harmer
0.689
315657AE1-056 GEN
Solar/Wind Harmer
3.56
315816AE2-034 GEN
Solar/Wind Harmer
0.721
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.486
970865AG2-541 GEN
Solar/Wind Harmer
2.987
316123AC1-075 GEN
Solar/Wind Harmer
0.692
970165AG2-112 GEN
Solar/Wind Harmer
0.609
970163AG2-111 GEN
Solar/Wind Harmer
0.581
316315AB2-025 C
Solar/Wind Helper
0.83
3143316POE
Solar/Wind Helper
0.701
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.272
316365GEN2_N
Solar/Wind Harmer
3.898
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.567
316210AC1-098 GEN
Solar/Wind Harmer
3.469
316327AA2-057 GEN
Solar/Wind Harmer
2.181
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.106
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.315
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.221
961681AG1-008 GEN
Solar/Wind Harmer
14.221
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.293
3156081AA2-088 GEN
Solar/Wind Harmer
5.454
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.577
964241AG1-285 GEN
Solar/Wind Harmer
10.88
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.894
970257AG2-171 GEN
Solar/Wind Harmer
4.626
959311AF2-222 GEN
Solar/Wind Harmer
12.552
315737AD1-076 GEN
Solar/Wind Harmer
2.17
971157AH1-035 GEN
Solar/Wind Harmer
1.377
963181AG1-167 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.933
315614AA2-178 GEN
Solar/Wind Harmer
0.962
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.385
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
971683AH1-343 GEN
Solar/Wind Harmer
3.369
942461AE2-259 GEN
Solar/Wind Harmer
1.119
316283AC2-100 C
Solar/Wind Harmer
0.635
970909AG2-566 GEN
Solar/Wind Harmer
0.612
315839AE2-212 C
Solar/Wind Helper
0.202
315722AD1-056 GEN
Solar/Wind Harmer
2.85
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.927
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.691
316049AB1-081 GEN
Solar/Wind Harmer
2.154
3142053HEARTS
Solar/Wind Harmer
0.235
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.725
971065AG2-659 GEN
Solar/Wind Harmer
9.428
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.85
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.431
316174AB2-169 GEN
Solar/Wind Harmer
2.09
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.737
970685AG2-442 GEN
Solar/Wind Harmer
9.839
963171AG1-166 GEN
Solar/Wind Harmer
1.276
971563AH1-280 GEN
Solar/Wind Harmer
1.276
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.359
957481AF2-042 GEN
Solar/Wind Harmer
25.811
316003AC1-222 GEN
Solar/Wind Harmer
0.806
315693AD1-088 GEN
Solar/Wind Harmer
4.085
315687AD1-152 GEN
Solar/Wind Harmer
0.98
962491AG1-098 GEN
Solar/Wind Harmer
5.404
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.337
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.248
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.324
3145783HORNRTN
Solar/Wind Harmer
2.659
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.733
316274AC1-208 GEN
Solar/Wind Harmer
2.531
961601AG1-000A GEN
Solar/Wind Harmer
8.004
316263AC1-034 GEN
Solar/Wind Harmer
9.357
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.404
939181AE1-148 GEN
Solar/Wind Harmer
8.303
316065AD1-022 GEN
Solar/Wind Harmer
6.44
970323AG2-213 GEN
Solar/Wind Harmer
6.168
971775AH1-396 GEN
Solar/Wind Harmer
0.878
316034AC1-036 C
Solar/Wind Harmer
0.229
962561AG1-105 GEN
Solar/Wind Harmer
6.652
964791AG1-342 GEN
Solar/Wind Harmer
2.412
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.595
963191AG1-168 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.244
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.324
970933AG2-581 GEN
Solar/Wind Harmer
7.724
315742AE1-103 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
7.95
316222AC1-221 GEN
Solar/Wind Harmer
0.686
970301AG2-198 GEN
Solar/Wind Harmer
3.221
3144356SAPONY
Solar/Wind Helper
0.977
316240AF1-291 C
Solar/Wind Helper
0.173
CPLELTFEXP_CPLE->PJM
CLTF
4.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.843
MECLTFEXP_MEC->PJM
CLTF
1.401
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.512
LGEELTFEXP_LGEE->PJM
CLTF
0.508
WECLTFEXP_WEC->PJM
CLTF
0.264
LAGNLTFEXP_LAGN->PJM
CLTF
2.828
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.165
TVALTFEXP_TVA->PJM
CLTF
1.41

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.95 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1045.35
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.142
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.272
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.898
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.85
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.85
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.927
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.691
316049AB1-081 GEN
Solar/Wind Harmer
2.154
3142053HEARTS
Solar/Wind Harmer
0.235
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.725
971065AG2-659 GEN
Solar/Wind Harmer
9.428
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.272
3151621KERR 5
50/50
0.272
3151631KERR 6
50/50
0.272
3151641KERR 7
50/50
0.272
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.795
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.467
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.146
970831AG2-522 GEN
Solar/Wind Harmer
10.282
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.337
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.272
316365GEN2_N
Solar/Wind Harmer
3.898
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.567
316210AC1-098 GEN
Solar/Wind Harmer
3.469
316327AA2-057 GEN
Solar/Wind Harmer
2.181
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.106
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.315
3146173TUNIS
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.248
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.324
3145783HORNRTN
Solar/Wind Harmer
2.659
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.733
316274AC1-208 GEN
Solar/Wind Harmer
2.531
961601AG1-000A GEN
Solar/Wind Harmer
8.004
316263AC1-034 GEN
Solar/Wind Harmer
9.357
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.221
961681AG1-008 GEN
Solar/Wind Harmer
14.221
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.293
3156081AA2-088 GEN
Solar/Wind Harmer
5.454
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.577
964241AG1-285 GEN
Solar/Wind Harmer
10.88
3146206CASHIE
Solar/Wind Harmer
-0.014
316420AA1-050 GEN
Solar/Wind Harmer
2.056
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.561
957861AF2-080 GEN
Solar/Wind Harmer
7.524
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.04
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.005
971443AH1-215 GEN
Solar/Wind Harmer
2.448
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.309
315733AD1-074 GEN2
Solar/Wind Harmer
2.309
315735AD1-075 GEN1
Solar/Wind Harmer
1.155
970683AG2-441 GEN
Solar/Wind Harmer
8.785
970681AG2-440 GEN
Solar/Wind Harmer
7.028
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.616
961791AG1-021 GEN
Solar/Wind Harmer
1.276
316118AC1-105 GEN
Solar/Wind Harmer
0.689
315657AE1-056 GEN
Solar/Wind Harmer
3.56
315816AE2-034 GEN
Solar/Wind Harmer
0.721
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.486
970865AG2-541 GEN
Solar/Wind Harmer
2.987
316123AC1-075 GEN
Solar/Wind Harmer
0.692
970165AG2-112 GEN
Solar/Wind Harmer
0.609
970163AG2-111 GEN
Solar/Wind Harmer
0.581
316315AB2-025 C
Solar/Wind Helper
0.83
3143316POE
Solar/Wind Helper
0.701
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.894
970257AG2-171 GEN
Solar/Wind Harmer
4.626
959311AF2-222 GEN
Solar/Wind Harmer
12.552
315737AD1-076 GEN
Solar/Wind Harmer
2.17
971157AH1-035 GEN
Solar/Wind Harmer
1.377
963181AG1-167 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.933
315614AA2-178 GEN
Solar/Wind Harmer
0.962
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.385
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
971683AH1-343 GEN
Solar/Wind Harmer
3.369
942461AE2-259 GEN
Solar/Wind Harmer
1.119
316283AC2-100 C
Solar/Wind Harmer
0.635
970909AG2-566 GEN
Solar/Wind Harmer
0.612
315839AE2-212 C
Solar/Wind Helper
0.202
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.404
939181AE1-148 GEN
Solar/Wind Harmer
8.303
316065AD1-022 GEN
Solar/Wind Harmer
6.44
970323AG2-213 GEN
Solar/Wind Harmer
6.168
971775AH1-396 GEN
Solar/Wind Harmer
0.878
316034AC1-036 C
Solar/Wind Harmer
0.229
962561AG1-105 GEN
Solar/Wind Harmer
6.652
964791AG1-342 GEN
Solar/Wind Harmer
2.412
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.595
963191AG1-168 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.244
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.324
970933AG2-581 GEN
Solar/Wind Harmer
7.724
315742AE1-103 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
7.95
316222AC1-221 GEN
Solar/Wind Harmer
0.686
970301AG2-198 GEN
Solar/Wind Harmer
3.221
3144356SAPONY
Solar/Wind Helper
0.977
316240AF1-291 C
Solar/Wind Helper
0.173
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.85
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.431
316174AB2-169 GEN
Solar/Wind Harmer
2.09
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.737
970685AG2-442 GEN
Solar/Wind Harmer
9.839
963171AG1-166 GEN
Solar/Wind Harmer
1.276
971563AH1-280 GEN
Solar/Wind Harmer
1.276
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.359
957481AF2-042 GEN
Solar/Wind Harmer
25.811
316003AC1-222 GEN
Solar/Wind Harmer
0.806
315693AD1-088 GEN
Solar/Wind Harmer
4.085
315687AD1-152 GEN
Solar/Wind Harmer
0.98
962491AG1-098 GEN
Solar/Wind Harmer
5.404
CPLELTFEXP_CPLE->PJM
CLTF
4.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.843
MECLTFEXP_MEC->PJM
CLTF
1.401
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.512
LGEELTFEXP_LGEE->PJM
CLTF
0.508
WECLTFEXP_WEC->PJM
CLTF
0.264
LAGNLTFEXP_LAGN->PJM
CLTF
2.828
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.165
TVALTFEXP_TVA->PJM
CLTF
1.41

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.4 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1156.99
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3147043LAWRENC
50/50
3.14
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.271
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.897
960081AF2-299 GEN
Solar/Wind Harmer
5.216
971795AH1-408 GEN
Solar/Wind Harmer
29.838
316011AB1-132 GEN
Solar/Wind Harmer
7.998
962571AG1-106 GEN
Solar/Wind Harmer
5.495
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.848
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.925
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.689
316049AB1-081 GEN
Solar/Wind Harmer
2.152
3142053HEARTS
Solar/Wind Harmer
0.234
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.724
971065AG2-659 GEN
Solar/Wind Harmer
9.42
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.849
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.427
316174AB2-169 GEN
Solar/Wind Harmer
2.087
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.736
970685AG2-442 GEN
Solar/Wind Harmer
9.824
963171AG1-166 GEN
Solar/Wind Harmer
1.274
971563AH1-280 GEN
Solar/Wind Harmer
1.274
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.342
957481AF2-042 GEN
Solar/Wind Harmer
25.757
316003AC1-222 GEN
Solar/Wind Harmer
0.805
315693AD1-088 GEN
Solar/Wind Harmer
4.077
315687AD1-152 GEN
Solar/Wind Harmer
0.978
962491AG1-098 GEN
Solar/Wind Harmer
5.393
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3151261ROARAP2
50/50
0.312
3151591KERR 2
50/50
0.271
316365GEN2_N
Solar/Wind Harmer
3.897
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.063
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.566
316210AC1-098 GEN
Solar/Wind Harmer
3.466
316327AA2-057 GEN
Solar/Wind Harmer
2.179
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.099
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.313
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.207
961681AG1-008 GEN
Solar/Wind Harmer
14.207
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.291
3156081AA2-088 GEN
Solar/Wind Harmer
5.448
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.847
316131AB2-060 GEN
Solar/Wind Harmer
1.576
964241AG1-285 GEN
Solar/Wind Harmer
10.867
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.89
970257AG2-171 GEN
Solar/Wind Harmer
4.619
959311AF2-222 GEN
Solar/Wind Harmer
12.534
315737AD1-076 GEN
Solar/Wind Harmer
2.166
971157AH1-035 GEN
Solar/Wind Harmer
1.375
963181AG1-167 GEN
Solar/Wind Harmer
0.956
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.922
315614AA2-178 GEN
Solar/Wind Harmer
0.96
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.376
316478AD1-087 GEN
Solar/Wind Harmer
0.718
316486AD2-202 GEN
Solar/Wind Harmer
0.21
971683AH1-343 GEN
Solar/Wind Harmer
3.362
942461AE2-259 GEN
Solar/Wind Harmer
1.117
316283AC2-100 C
Solar/Wind Harmer
0.633
970909AG2-566 GEN
Solar/Wind Harmer
0.61
315839AE2-212 C
Solar/Wind Helper
0.202
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.334
3144356SAPONY
Solar/Wind Harmer
3.329
316181AB2-040 GEN
Solar/Wind Harmer
5.316
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.246
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.322
3145783HORNRTN
Solar/Wind Harmer
2.657
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.731
316274AC1-208 GEN
Solar/Wind Harmer
2.529
961601AG1-000A GEN
Solar/Wind Harmer
7.998
316263AC1-034 GEN
Solar/Wind Harmer
9.349
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.5
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.401
939181AE1-148 GEN
Solar/Wind Harmer
8.293
316065AD1-022 GEN
Solar/Wind Harmer
6.431
970323AG2-213 GEN
Solar/Wind Harmer
6.159
971775AH1-396 GEN
Solar/Wind Harmer
0.877
316034AC1-036 C
Solar/Wind Harmer
0.228
962561AG1-105 GEN
Solar/Wind Harmer
6.642
964791AG1-342 GEN
Solar/Wind Harmer
2.408
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.593
963191AG1-168 GEN
Solar/Wind Harmer
0.956
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.243
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.303
970933AG2-581 GEN
Solar/Wind Harmer
7.708
315742AE1-103 GEN
Solar/Wind Harmer
0.833
971741AH1-377 GEN
Solar/Wind Harmer
7.93
316222AC1-221 GEN
Solar/Wind Harmer
0.684
970301AG2-198 GEN
Solar/Wind Harmer
3.213
316240AF1-291 C
Solar/Wind Helper
0.173
315779AE2-040
50/50
11.856
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.271
3151621KERR 5
50/50
0.271
3151631KERR 6
50/50
0.271
3151641KERR 7
50/50
0.271
316315AB2-025 C
Solar/Wind Harmer
2.574
315814AE2-033 C
Solar/Wind Harmer
87.029
946281AF1-292 GEN
Solar/Wind Harmer
1.038
316087AB2-174 GEN
Solar/Wind Harmer
5.792
315652AC1-086 GEN
Solar/Wind Harmer
43.007
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.131
315607AA1-063A GEN
Solar/Wind Harmer
2.465
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.145
970831AG2-522 GEN
Solar/Wind Harmer
10.274
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.054
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.56
957861AF2-080 GEN
Solar/Wind Harmer
7.517
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.038
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
5.997
971443AH1-215 GEN
Solar/Wind Harmer
2.445
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.305
315733AD1-074 GEN2
Solar/Wind Harmer
2.305
315735AD1-075 GEN1
Solar/Wind Harmer
1.153
970683AG2-441 GEN
Solar/Wind Harmer
8.771
970681AG2-440 GEN
Solar/Wind Harmer
7.017
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.612
961791AG1-021 GEN
Solar/Wind Harmer
1.274
316118AC1-105 GEN
Solar/Wind Harmer
0.687
315657AE1-056 GEN
Solar/Wind Harmer
3.553
315816AE2-034 GEN
Solar/Wind Harmer
0.72
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.454
970865AG2-541 GEN
Solar/Wind Harmer
2.98
316123AC1-075 GEN
Solar/Wind Harmer
0.69
970165AG2-112 GEN
Solar/Wind Harmer
0.608
970163AG2-111 GEN
Solar/Wind Harmer
0.58
3143316POE
Solar/Wind Helper
0.702
CPLELTFEXP_CPLE->PJM
CLTF
4.641
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.852
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.173
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.798
MECLTFEXP_MEC->PJM
CLTF
1.381
SIGELTFEXP_SIGE->PJM
CLTF
0.041
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.5
WECLTFEXP_WEC->PJM
CLTF
0.26
LAGNLTFEXP_LAGN->PJM
CLTF
2.804
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.13
TVALTFEXP_TVA->PJM
CLTF
1.399

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.34 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1156.56
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3147043LAWRENC
50/50
3.14
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.271
3151581KERR 1
50/50
0.097
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3151261ROARAP2
50/50
0.312
3151591KERR 2
50/50
0.271
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.334
3144356SAPONY
Solar/Wind Harmer
3.329
315779AE2-040
50/50
11.856
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.271
3151621KERR 5
50/50
0.271
3151631KERR 6
50/50
0.271
3151641KERR 7
50/50
0.271
316181AB2-040 GEN
Solar/Wind Harmer
5.316
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.246
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.322
3145783HORNRTN
Solar/Wind Harmer
2.657
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.731
316274AC1-208 GEN
Solar/Wind Harmer
2.529
961601AG1-000A GEN
Solar/Wind Harmer
7.998
316263AC1-034 GEN
Solar/Wind Harmer
9.349
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.5
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.401
939181AE1-148 GEN
Solar/Wind Harmer
8.293
316065AD1-022 GEN
Solar/Wind Harmer
6.431
970323AG2-213 GEN
Solar/Wind Harmer
6.159
971775AH1-396 GEN
Solar/Wind Harmer
0.877
316034AC1-036 C
Solar/Wind Harmer
0.228
962561AG1-105 GEN
Solar/Wind Harmer
6.642
964791AG1-342 GEN
Solar/Wind Harmer
2.408
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.593
963191AG1-168 GEN
Solar/Wind Harmer
0.956
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.243
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.303
970933AG2-581 GEN
Solar/Wind Harmer
7.708
315742AE1-103 GEN
Solar/Wind Harmer
0.833
971741AH1-377 GEN
Solar/Wind Harmer
7.93
316222AC1-221 GEN
Solar/Wind Harmer
0.684
970301AG2-198 GEN
Solar/Wind Harmer
3.213
316240AF1-291 C
Solar/Wind Helper
0.173
316315AB2-025 C
Solar/Wind Harmer
2.574
315814AE2-033 C
Solar/Wind Harmer
87.029
946281AF1-292 GEN
Solar/Wind Harmer
1.038
316087AB2-174 GEN
Solar/Wind Harmer
5.792
315652AC1-086 GEN
Solar/Wind Harmer
43.007
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.131
315607AA1-063A GEN
Solar/Wind Harmer
2.465
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.145
970831AG2-522 GEN
Solar/Wind Harmer
10.274
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.054
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.56
957861AF2-080 GEN
Solar/Wind Harmer
7.517
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.038
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
5.997
971443AH1-215 GEN
Solar/Wind Harmer
2.445
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.305
315733AD1-074 GEN2
Solar/Wind Harmer
2.305
315735AD1-075 GEN1
Solar/Wind Harmer
1.153
970683AG2-441 GEN
Solar/Wind Harmer
8.771
970681AG2-440 GEN
Solar/Wind Harmer
7.017
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.612
961791AG1-021 GEN
Solar/Wind Harmer
1.274
316118AC1-105 GEN
Solar/Wind Harmer
0.687
315657AE1-056 GEN
Solar/Wind Harmer
3.553
316023GEN1_S
Solar/Wind Harmer
3.897
960081AF2-299 GEN
Solar/Wind Harmer
5.216
971795AH1-408 GEN
Solar/Wind Harmer
29.838
316011AB1-132 GEN
Solar/Wind Harmer
7.998
962571AG1-106 GEN
Solar/Wind Harmer
5.495
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.848
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316365GEN2_N
Solar/Wind Harmer
3.897
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.063
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.566
316210AC1-098 GEN
Solar/Wind Harmer
3.466
316327AA2-057 GEN
Solar/Wind Harmer
2.179
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.099
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.313
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.207
961681AG1-008 GEN
Solar/Wind Harmer
14.207
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.291
3156081AA2-088 GEN
Solar/Wind Harmer
5.448
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.847
316131AB2-060 GEN
Solar/Wind Harmer
1.576
964241AG1-285 GEN
Solar/Wind Harmer
10.867
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.89
970257AG2-171 GEN
Solar/Wind Harmer
4.619
959311AF2-222 GEN
Solar/Wind Harmer
12.534
315737AD1-076 GEN
Solar/Wind Harmer
2.166
971157AH1-035 GEN
Solar/Wind Harmer
1.375
963181AG1-167 GEN
Solar/Wind Harmer
0.956
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.922
315614AA2-178 GEN
Solar/Wind Harmer
0.96
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.376
316478AD1-087 GEN
Solar/Wind Harmer
0.718
316486AD2-202 GEN
Solar/Wind Harmer
0.21
971683AH1-343 GEN
Solar/Wind Harmer
3.362
942461AE2-259 GEN
Solar/Wind Harmer
1.117
316283AC2-100 C
Solar/Wind Harmer
0.633
970909AG2-566 GEN
Solar/Wind Harmer
0.61
315839AE2-212 C
Solar/Wind Helper
0.202
315816AE2-034 GEN
Solar/Wind Harmer
0.72
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.454
970865AG2-541 GEN
Solar/Wind Harmer
2.98
316123AC1-075 GEN
Solar/Wind Harmer
0.69
970165AG2-112 GEN
Solar/Wind Harmer
0.608
970163AG2-111 GEN
Solar/Wind Harmer
0.58
3143316POE
Solar/Wind Helper
0.702
316212AC1-099_GEN
Solar/Wind Harmer
1.925
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.689
316049AB1-081 GEN
Solar/Wind Harmer
2.152
3142053HEARTS
Solar/Wind Harmer
0.234
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.724
971065AG2-659 GEN
Solar/Wind Harmer
9.42
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.849
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.427
316174AB2-169 GEN
Solar/Wind Harmer
2.087
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.736
970685AG2-442 GEN
Solar/Wind Harmer
9.824
963171AG1-166 GEN
Solar/Wind Harmer
1.274
971563AH1-280 GEN
Solar/Wind Harmer
1.274
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.342
957481AF2-042 GEN
Solar/Wind Harmer
25.757
316003AC1-222 GEN
Solar/Wind Harmer
0.805
315693AD1-088 GEN
Solar/Wind Harmer
4.077
315687AD1-152 GEN
Solar/Wind Harmer
0.978
962491AG1-098 GEN
Solar/Wind Harmer
5.393
CPLELTFEXP_CPLE->PJM
CLTF
4.641
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.852
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.173
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.798
MECLTFEXP_MEC->PJM
CLTF
1.381
SIGELTFEXP_SIGE->PJM
CLTF
0.041
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.5
WECLTFEXP_WEC->PJM
CLTF
0.26
LAGNLTFEXP_LAGN->PJM
CLTF
2.804
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.13
TVALTFEXP_TVA->PJM
CLTF
1.399

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.79 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1094.57
MW Contribution:2.85
Bus #Bus NameTypeMW Contribution
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
970865AG2-541 GEN
Solar/Wind Harmer
14.161
316118AC1-105 GEN
Solar/Wind Harmer
2.358
316123AC1-075 GEN
Solar/Wind Harmer
3.239
970165AG2-112 GEN
Solar/Wind Harmer
2.852
970163AG2-111 GEN
Solar/Wind Harmer
2.72
270455AD2-022 GEN
Solar/Wind Harmer
3.538
270457AD2-023 GEN
Solar/Wind Harmer
1.794
970085AG2-068 GEN
Solar/Wind Harmer
9.963
970581AG2-369 GEN
Solar/Wind Harmer
8.568
270069AE2-166 C O1
Solar/Wind Harmer
1.81
971981AH1-535 GEN
Solar/Wind Harmer
4.63
3143316POE
Solar/Wind Helper
0.631
316369SG1_INVT
Solar/Wind Helper
0.698
316132AB2-190 GEN1
Solar/Wind Helper
0.823
957831AF2-077 GEN
Solar/Wind Helper
0.191
319010AE1-072 C
Solar/Wind Helper
1.613
316305AF2-043 C
Solar/Wind Helper
0.188
316349AD2-085 GEN
Solar/Wind Helper
0.634
316233AE1-074 FULL
Solar/Wind Helper
0.21
957601AF2-054 GEN
Solar/Wind Helper
0.182
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.728
315666AE1-190 GEN
Solar/Wind Helper
0.182
3152661PLYWOOD A
50/50
0.686
316222AC1-221 GEN
Solar/Wind Harmer
3.103
942751AE2-291 GEN
Solar/Wind Harmer
17.181
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.586
962561AG1-105 GEN
Solar/Wind Harmer
12.803
316217AC1-145 GEN
Solar/Wind Harmer
2.369
316197AC1-042 GEN
Solar/Wind Harmer
1.796
942671AE2-283 GEN
Solar/Wind Harmer
4.836
270013AE1-250 PV
Solar/Wind Harmer
2.232
961601AG1-000A GEN
Solar/Wind Harmer
2.764
316263AC1-034 GEN
Solar/Wind Harmer
3.276
3146776BUCKING
Solar/Wind Helper
0.776
3146776BUCKING
Solar/Wind Helper
0.063
316036AC1-147 C
Solar/Wind Helper
0.234
3142956BIRDNECK
Solar/Wind Helper
0.103
316316AC1-027 C
Solar/Wind Helper
0.24
971629AH1-314 GEN
50/50
13.518
3151561HALLBR1
50/50
0.374
24728405LEESVG
50/50
0.137
316003AC1-222 GEN
Solar/Wind Harmer
3.859
970401AG2-262 GEN
Solar/Wind Harmer
1.707
3147123OTTER R
Solar/Wind Harmer
-0.01
970087AG2-069 GEN
Solar/Wind Harmer
14.944
970919AG2-571 GEN
Solar/Wind Harmer
5.044
970223AG2-152 GEN
Solar/Wind Harmer
13.39
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.475
270016AE1-250 BESS
Solar/Wind Harmer
2.232
270574AD1-017 GEN2
Solar/Wind Harmer
4.514
270030AE2-140 GEN
Solar/Wind Harmer
14.796
270173AC1-122 GEN
Solar/Wind Harmer
1.042
316359AB2-059 GEN
Solar/Wind Harmer
0.942
316049AB1-081 GEN
Solar/Wind Harmer
0.754
3142053HEARTS
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
315687AD1-152 GEN
Solar/Wind Helper
4.938
3146926FARMVIL
Solar/Wind Helper
0.145
316322AB2-045
Solar/Wind Helper
0.216
3146776BUCKING
Solar/Wind Helper
0.078
316294AC1-161 GEN
Solar/Wind Helper
3.066
316375AC2-012 GEN
Solar/Wind Helper
0.403
3145336SMITFLD
Solar/Wind Helper
0.6
316381AD1-082 GEN
Solar/Wind Helper
0.754
316388AE2-253 GEN
Solar/Wind Helper
0.553
316458AB2-190 GEN2
Solar/Wind Helper
0.823
316159AE1-175 C
Solar/Wind Helper
0.217
3146456SLIGO L269
Solar/Wind Helper
0.142
316072AD1-144
Solar/Wind Helper
0.162
3143226MDLTHAN
Solar/Wind Helper
0.14
316246AF1-032 C
Solar/Wind Helper
0.16
316336AC2-165 C
Solar/Wind Helper
0.748
3143526WINTERP
Solar/Wind Helper
0.715
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.543
24728405LEESVG
50/50
0.137
316248AF1-058 C
Solar/Wind Harmer
1.271
960061AF2-297 GEN
Solar/Wind Harmer
21.085
971683AH1-343 GEN
Solar/Wind Harmer
16.057
316283AC2-100 C
Solar/Wind Harmer
2.823
970917AG2-570 GEN
Solar/Wind Harmer
39.848
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.475
270197AD1-017 GEN1
Solar/Wind Harmer
1.356
270018AE2-047 C O1
Solar/Wind Harmer
1.022
943811AF1-049 GEN
Solar/Wind Harmer
2.877
270336AE1-100 GEN
Solar/Wind Harmer
1.171
971367AH1-164 GEN
Solar/Wind Harmer
1.921
961601AG1-000A GEN
Solar/Wind Harmer
2.799
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3143873LANEXA
Solar/Wind Helper
0.081
316059AD1-063 C
Solar/Wind Helper
0.136
3141913WHIT STONE
Solar/Wind Helper
0.134
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.08
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.199
316315AB2-025 C
Solar/Wind Helper
0.198
3146486SUNBURY
Solar/Wind Helper
0.128
3146486SUNBURY
Solar/Wind Helper
0.128
3141813NORNECK
Solar/Wind Helper
0.127
316312AB1-027
Solar/Wind Helper
0.24
316321Z2-027
Solar/Wind Helper
0.192
3145176PASQUOTANK
Solar/Wind Helper
0.078
316223AC1-118
Solar/Wind Helper
0.183
316185AD1-033 GEN
Solar/Wind Helper
0.713
316236AE1-162_GEN
Solar/Wind Helper
0.201
3145506HICKORY
Solar/Wind Helper
0.597
3145506HICKORY
Solar/Wind Helper
0.358
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.197
316339AD2-160 GEN
Solar/Wind Helper
0.553
316033AB2-134 GEN
Solar/Wind Helper
0.499
315697AD1-025 GEN
Solar/Wind Helper
1.658
316018AA1-139 ULT2
Solar/Wind Helper
0.62
316017AA1-139 ULT1
Solar/Wind Helper
0.658
3137176SLIGO L2192
Solar/Wind Helper
0.566
3130086AYDLETT
Solar/Wind Helper
0.562
3143526WINTERP
Solar/Wind Helper
0.715
3142946ENON
Solar/Wind Helper
0.014
316075AC2-137 C
Solar/Wind Helper
0.2
316487AF1-042 GEN
Solar/Wind Helper
0.132
3146386ELIZ CT
Solar/Wind Helper
0.131
3144356SAPONY
Solar/Wind Helper
0.233
316077AC2-138 C
Solar/Wind Helper
0.12
966871AG1-558 GEN
Solar/Wind Helper
0.164
316431W1029_GEN1
Solar/Wind Helper
0.482
316433W1029_GEN2
Solar/Wind Helper
0.482
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.565
316478AD1-087 GEN
Solar/Wind Helper
3.077
316486AD2-202 GEN
Solar/Wind Helper
0.901
3146926FARMVIL
Solar/Wind Helper
0.145
3146776BUCKING
Solar/Wind Helper
0.07
315773AC2-141 GEN
Solar/Wind Helper
3.608
942461AE2-259 GEN
Solar/Wind Helper
1.129
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.204
3145336SMITFLD
Solar/Wind Helper
0.06
316382AG1-145 C
Solar/Wind Helper
0.193
3146456SLIGO L269
Solar/Wind Helper
0.142
316313AB2-026
Solar/Wind Helper
0.212
316258AE1-075 C
Solar/Wind Helper
0.191
316405AF2-144 C
Solar/Wind Helper
0.159
316156AD2-030 GEN
Solar/Wind Helper
0.205
316280AD1-041 GEN
Solar/Wind Helper
0.455
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.253
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.094
316473AC1-191 GEN
Solar/Wind Helper
0.742
3141906WESTMOR
Solar/Wind Helper
0.048
316435W1029_GEN3
Solar/Wind Helper
0.482
3146516WINFALL
Solar/Wind Helper
0.117
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.172
3141726DUNNSVL
Solar/Wind Helper
0.511
3142416OLDCHRC
Solar/Wind Helper
0.328
3142416OLDCHRC
Solar/Wind Helper
0.126
316337AD2-073 GEN
Solar/Wind Helper
0.187
3146516WINFALL
Solar/Wind Helper
0.378
3146516WINFALL
Solar/Wind Helper
0.117
CPLELTFEXP_CPLE->PJM
CLTF
11.178
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.871
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.424
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.227
MECLTFEXP_MEC->PJM
CLTF
5.265
SIGELTFEXP_SIGE->PJM
CLTF
0.161
NYPJM->LTFIMP_NY
CLTF
0.739
LGEELTFEXP_LGEE->PJM
CLTF
1.997
WECLTFEXP_WEC->PJM
CLTF
1.057
LAGNLTFEXP_LAGN->PJM
CLTF
9.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.368
TVALTFEXP_TVA->PJM
CLTF
4.632

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.53 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:843.75
MW Contribution:2.17
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.688
24684405SMG2
50/50
0.859
24684505SMG3
50/50
0.531
24684305SMG1
50/50
0.311
316222AC1-221 GEN
Solar/Wind Harmer
1.137
942751AE2-291 GEN
Solar/Wind Harmer
13.103
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.488
962561AG1-105 GEN
Solar/Wind Harmer
9.772
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.259
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.13
316263AC1-034 GEN
Solar/Wind Harmer
2.401
3146776BUCKING
Solar/Wind Helper
0.769
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.231
316316AC1-027 C
Solar/Wind Helper
0.237
3142956BIRDNECK
Solar/Wind Helper
0.101
316185AD1-033 GEN
Solar/Wind Helper
0.703
316236AE1-162_GEN
Solar/Wind Helper
0.199
3145506HICKORY
Solar/Wind Helper
0.589
3145506HICKORY
Solar/Wind Helper
0.353
3145506HICKORY
Solar/Wind Helper
0.088
316240AF1-291 C
Solar/Wind Helper
0.194
316339AD2-160 GEN
Solar/Wind Helper
0.545
316033AB2-134 GEN
Solar/Wind Helper
0.492
315697AD1-025 GEN
Solar/Wind Helper
1.636
316018AA1-139 ULT2
Solar/Wind Helper
0.611
316017AA1-139 ULT1
Solar/Wind Helper
0.649
3137176SLIGO L2192
Solar/Wind Helper
0.558
3130086AYDLETT
Solar/Wind Helper
0.554
971629AH1-314 GEN
50/50
13.606
3151561HALLBR1
50/50
0.377
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.905
24684705SMG5
50/50
0.331
970481AG2-311 GEN
50/50
4.609
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.371
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.429
970919AG2-571 GEN
Solar/Wind Harmer
5.079
970223AG2-152 GEN
Solar/Wind Harmer
9.459
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.19
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.43
270173AC1-122 GEN
Solar/Wind Harmer
0.218
316359AB2-059 GEN
Solar/Wind Harmer
0.227
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
315687AD1-152 GEN
Solar/Wind Helper
4.927
3146926FARMVIL
Solar/Wind Helper
0.143
316322AB2-045
Solar/Wind Helper
0.214
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.03
316375AC2-012 GEN
Solar/Wind Helper
0.398
3145336SMITFLD
Solar/Wind Helper
0.592
316381AD1-082 GEN
Solar/Wind Helper
0.744
316388AE2-253 GEN
Solar/Wind Helper
0.545
316458AB2-190 GEN2
Solar/Wind Helper
0.811
316159AE1-175 C
Solar/Wind Helper
0.214
3146456SLIGO L269
Solar/Wind Helper
0.14
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.138
316246AF1-032 C
Solar/Wind Helper
0.158
316336AC2-165 C
Solar/Wind Helper
0.738
3143526WINTERP
Solar/Wind Helper
0.705
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.535
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.079
964211AG1-282 GEN
Solar/Wind Helper
0.169
3141726DUNNSVL
Solar/Wind Helper
0.503
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.184
3146516WINFALL
Solar/Wind Helper
0.371
3146516WINFALL
Solar/Wind Helper
0.115
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.789
316118AC1-105 GEN
Solar/Wind Harmer
0.79
316123AC1-075 GEN
Solar/Wind Harmer
0.367
970165AG2-112 GEN
Solar/Wind Harmer
2.174
970163AG2-111 GEN
Solar/Wind Harmer
2.074
970085AG2-068 GEN
Solar/Wind Harmer
7.62
970581AG2-369 GEN
Solar/Wind Harmer
6.553
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.189
3143316POE
Solar/Wind Helper
0.623
316369SG1_INVT
Solar/Wind Helper
0.688
316132AB2-190 GEN1
Solar/Wind Helper
0.811
957831AF2-077 GEN
Solar/Wind Helper
0.188
319010AE1-072 C
Solar/Wind Helper
1.59
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.625
316233AE1-074 FULL
Solar/Wind Helper
0.207
957601AF2-054 GEN
Solar/Wind Helper
0.179
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.718
315666AE1-190 GEN
Solar/Wind Helper
0.179
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.134
3141913WHIT STONE
Solar/Wind Helper
0.132
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.196
316315AB2-025 C
Solar/Wind Helper
0.195
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.125
316312AB1-027
Solar/Wind Helper
0.236
316321Z2-027
Solar/Wind Helper
0.189
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.18
3143526WINTERP
Solar/Wind Helper
0.705
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.197
316487AF1-042 GEN
Solar/Wind Helper
0.13
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.229
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.161
316431W1029_GEN1
Solar/Wind Helper
0.474
316433W1029_GEN2
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.556
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.864
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.056
971683AH1-343 GEN
Solar/Wind Harmer
12.232
316283AC2-100 C
Solar/Wind Harmer
0.524
970917AG2-570 GEN
Solar/Wind Harmer
12.699
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.19
270197AD1-017 GEN1
Solar/Wind Harmer
0.768
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.359
961601AG1-000A GEN
Solar/Wind Harmer
4.52
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.067
316486AD2-202 GEN
Solar/Wind Helper
0.898
3146926FARMVIL
Solar/Wind Helper
0.143
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.566
942461AE2-259 GEN
Solar/Wind Helper
1.116
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.201
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.19
3146456SLIGO L269
Solar/Wind Helper
0.14
316313AB2-026
Solar/Wind Helper
0.209
316258AE1-075 C
Solar/Wind Helper
0.188
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.202
316280AD1-041 GEN
Solar/Wind Helper
0.449
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.249
316320Y1-086
Solar/Wind Helper
0.057
316404AE1-155 C
Solar/Wind Helper
1.078
316473AC1-191 GEN
Solar/Wind Helper
0.73
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
CPLELTFEXP_CPLE->PJM
CLTF
11.262
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.898
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.517
MECLTFEXP_MEC->PJM
CLTF
5.393
SIGELTFEXP_SIGE->PJM
CLTF
0.165
NYPJM->LTFIMP_NY
CLTF
0.69
LGEELTFEXP_LGEE->PJM
CLTF
2.05
WECLTFEXP_WEC->PJM
CLTF
1.087
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
LAGNLTFEXP_LAGN->PJM
CLTF
9.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.599
TVALTFEXP_TVA->PJM
CLTF
4.709

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.35 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:825.97
MW Contribution:2.17
Bus #Bus NameTypeMW Contribution
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.789
316118AC1-105 GEN
Solar/Wind Harmer
0.79
316123AC1-075 GEN
Solar/Wind Harmer
0.367
970165AG2-112 GEN
Solar/Wind Harmer
2.174
970163AG2-111 GEN
Solar/Wind Harmer
2.074
970085AG2-068 GEN
Solar/Wind Harmer
7.62
970581AG2-369 GEN
Solar/Wind Harmer
6.553
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.189
3143316POE
Solar/Wind Helper
0.623
316369SG1_INVT
Solar/Wind Helper
0.688
316132AB2-190 GEN1
Solar/Wind Helper
0.811
957831AF2-077 GEN
Solar/Wind Helper
0.188
319010AE1-072 C
Solar/Wind Helper
1.59
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.625
316233AE1-074 FULL
Solar/Wind Helper
0.207
957601AF2-054 GEN
Solar/Wind Helper
0.179
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.718
315666AE1-190 GEN
Solar/Wind Helper
0.179
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.134
3141913WHIT STONE
Solar/Wind Helper
0.132
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.196
971629AH1-314 GEN
50/50
13.606
3151561HALLBR1
50/50
0.377
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.905
24684705SMG5
50/50
0.331
970481AG2-311 GEN
50/50
4.609
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.371
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.429
970223AG2-152 GEN
Solar/Wind Harmer
9.459
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.19
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.43
270173AC1-122 GEN
Solar/Wind Harmer
0.218
316359AB2-059 GEN
Solar/Wind Harmer
0.227
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
315687AD1-152 GEN
Solar/Wind Helper
4.927
3146926FARMVIL
Solar/Wind Helper
0.143
316322AB2-045
Solar/Wind Helper
0.214
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.03
316375AC2-012 GEN
Solar/Wind Helper
0.398
3145336SMITFLD
Solar/Wind Helper
0.592
316381AD1-082 GEN
Solar/Wind Helper
0.744
316388AE2-253 GEN
Solar/Wind Helper
0.545
316458AB2-190 GEN2
Solar/Wind Helper
0.811
316159AE1-175 C
Solar/Wind Helper
0.214
3146456SLIGO L269
Solar/Wind Helper
0.14
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.138
316246AF1-032 C
Solar/Wind Helper
0.158
316336AC2-165 C
Solar/Wind Helper
0.738
3143526WINTERP
Solar/Wind Helper
0.705
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.535
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.079
964211AG1-282 GEN
Solar/Wind Helper
0.169
3141726DUNNSVL
Solar/Wind Helper
0.503
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.184
3146516WINFALL
Solar/Wind Helper
0.371
3146516WINFALL
Solar/Wind Helper
0.115
316315AB2-025 C
Solar/Wind Helper
0.195
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.125
316312AB1-027
Solar/Wind Helper
0.236
316321Z2-027
Solar/Wind Helper
0.189
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.18
3152661PLYWOOD A
50/50
0.688
24684405SMG2
50/50
0.859
24684505SMG3
50/50
0.531
24684305SMG1
50/50
0.311
316222AC1-221 GEN
Solar/Wind Harmer
1.137
942751AE2-291 GEN
Solar/Wind Harmer
13.103
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.488
962561AG1-105 GEN
Solar/Wind Harmer
9.772
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.259
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.13
316263AC1-034 GEN
Solar/Wind Harmer
2.401
3146776BUCKING
Solar/Wind Helper
0.769
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.231
316316AC1-027 C
Solar/Wind Helper
0.237
3142956BIRDNECK
Solar/Wind Helper
0.101
316185AD1-033 GEN
Solar/Wind Helper
0.703
316236AE1-162_GEN
Solar/Wind Helper
0.199
3145506HICKORY
Solar/Wind Helper
0.589
3145506HICKORY
Solar/Wind Helper
0.353
3145506HICKORY
Solar/Wind Helper
0.088
316240AF1-291 C
Solar/Wind Helper
0.194
316339AD2-160 GEN
Solar/Wind Helper
0.545
316033AB2-134 GEN
Solar/Wind Helper
0.492
315697AD1-025 GEN
Solar/Wind Helper
1.636
316018AA1-139 ULT2
Solar/Wind Helper
0.611
316017AA1-139 ULT1
Solar/Wind Helper
0.649
3137176SLIGO L2192
Solar/Wind Helper
0.558
3130086AYDLETT
Solar/Wind Helper
0.554
3143526WINTERP
Solar/Wind Helper
0.705
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.197
316487AF1-042 GEN
Solar/Wind Helper
0.13
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.229
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.161
316431W1029_GEN1
Solar/Wind Helper
0.474
316433W1029_GEN2
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.556
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.864
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.056
971683AH1-343 GEN
Solar/Wind Harmer
12.232
316283AC2-100 C
Solar/Wind Harmer
0.524
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.19
270197AD1-017 GEN1
Solar/Wind Harmer
0.768
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.359
961601AG1-000A GEN
Solar/Wind Harmer
4.52
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.067
316486AD2-202 GEN
Solar/Wind Helper
0.898
3146926FARMVIL
Solar/Wind Helper
0.143
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.566
942461AE2-259 GEN
Solar/Wind Helper
1.116
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.201
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.19
3146456SLIGO L269
Solar/Wind Helper
0.14
316313AB2-026
Solar/Wind Helper
0.209
316258AE1-075 C
Solar/Wind Helper
0.188
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.202
316280AD1-041 GEN
Solar/Wind Helper
0.449
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.249
316320Y1-086
Solar/Wind Helper
0.057
316404AE1-155 C
Solar/Wind Helper
1.078
316473AC1-191 GEN
Solar/Wind Helper
0.73
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
CPLELTFEXP_CPLE->PJM
CLTF
11.262
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.898
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.517
MECLTFEXP_MEC->PJM
CLTF
5.393
SIGELTFEXP_SIGE->PJM
CLTF
0.165
NYPJM->LTFIMP_NY
CLTF
0.69
LGEELTFEXP_LGEE->PJM
CLTF
2.05
WECLTFEXP_WEC->PJM
CLTF
1.087
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
LAGNLTFEXP_LAGN->PJM
CLTF
9.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.599
TVALTFEXP_TVA->PJM
CLTF
4.709

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.88 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1203.12
MW Contribution:3.68
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.765
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.237
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.767
971967AH1-528 GEN
Solar/Wind Harmer
100.764
970865AG2-541 GEN
Solar/Wind Harmer
19.09
316123AC1-075 GEN
Solar/Wind Harmer
4.175
970165AG2-112 GEN
Solar/Wind Harmer
3.676
970163AG2-111 GEN
Solar/Wind Harmer
3.506
316239AB2-077_GEN
Solar/Wind Harmer
1.109
316238AB2-078_GEN
Solar/Wind Harmer
1.109
971443AH1-215 GEN
Solar/Wind Harmer
6.887
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.754
970681AG2-440 GEN
Solar/Wind Harmer
21.403
946301AF1-294 GEN
Solar/Wind Harmer
8.613
961791AG1-021 GEN
Solar/Wind Harmer
4.201
315657AE1-056 GEN
Solar/Wind Harmer
12.436
970285AG2-188 GEN
Solar/Wind Harmer
21.464
971845AH1-439 GEN
Solar/Wind Harmer
12.355
970831AG2-522 GEN
Solar/Wind Harmer
10.03
971447AH1-217 GEN
Solar/Wind Harmer
3.932
270494AE1-108_GEN
Solar/Wind Harmer
2.515
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.12
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.372
270457AD2-023 GEN
Solar/Wind Helper
0.904
3152661PLYWOOD A
50/50
1.087
3144293JTRSVLE
50/50
1.01
3144293JTRSVLE
50/50
0.851
970535AG2-341 GEN
50/50
5.156
970099AG2-077 GEN
Solar/Wind Harmer
67.945
970933AG2-581 GEN
Solar/Wind Harmer
50.247
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.651
962561AG1-105 GEN
Solar/Wind Harmer
26.897
971741AH1-377 GEN
Solar/Wind Harmer
48.415
970301AG2-198 GEN
Solar/Wind Harmer
19.501
313527AB2-043 GEN
Solar/Wind Harmer
5.92
970323AG2-213 GEN
Solar/Wind Harmer
17.464
971775AH1-396 GEN
Solar/Wind Harmer
2.487
316034AC1-036 C
Solar/Wind Harmer
0.648
958211AF2-115 GEN
Solar/Wind Harmer
5.252
970413AG2-270 GEN
50/50
47.203
3144293JTRSVLE
50/50
1.01
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.074
316248AF1-058 C
Solar/Wind Harmer
1.794
960061AF2-297 GEN
Solar/Wind Harmer
29.766
316478AD1-087 GEN
Solar/Wind Harmer
4.933
316486AD2-202 GEN
Solar/Wind Harmer
1.445
971683AH1-343 GEN
Solar/Wind Harmer
22.023
970909AG2-566 GEN
Solar/Wind Harmer
3.703
316131AB2-060 GEN
Solar/Wind Harmer
3.921
964241AG1-285 GEN
Solar/Wind Harmer
28.048
315785AD2-033 C
Solar/Wind Harmer
7.977
970257AG2-171 GEN
Solar/Wind Harmer
13.098
959311AF2-222 GEN
Solar/Wind Harmer
36.247
963181AG1-167 GEN
Solar/Wind Harmer
3.151
3147133PAMPLIN
Solar/Wind Harmer
-0.104
971193AH1-056 GEN
Solar/Wind Harmer
20.727
942461AE2-259 GEN
Solar/Wind Harmer
4.793
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.538
970221AG2-151 GEN
Solar/Wind Harmer
7.287
966621AG1-532 GEN
Solar/Wind Harmer
0.168
313506AB2-031 GEN
Solar/Wind Harmer
0.617
316313AB2-026
Solar/Wind Harmer
0.177
316258AE1-075 C
Solar/Wind Harmer
0.159
316405AF2-144 C
Solar/Wind Harmer
0.168
3143336POWHATN
Solar/Wind Harmer
0.661
316283AC2-100 C
Solar/Wind Helper
2.321
3151531CLOVER1
50/50
10.817
3144293JTRSVLE
50/50
1.01
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.438
3151561HALLBR1
50/50
0.348
3151931BEARGRDN S1
50/50
1.386
3151911BEARGRDN G1
50/50
1.074
315687AD1-152 GEN
Solar/Wind Harmer
7.758
316003AC1-222 GEN
Solar/Wind Harmer
5.37
957481AF2-042 GEN
Solar/Wind Harmer
169.864
315693AD1-088 GEN
Solar/Wind Harmer
25.266
962491AG1-098 GEN
Solar/Wind Harmer
33.395
970401AG2-262 GEN
Solar/Wind Harmer
3.255
316237AB2-079_GEN
Solar/Wind Harmer
1.109
970685AG2-442 GEN
Solar/Wind Harmer
29.964
963171AG1-166 GEN
Solar/Wind Harmer
4.201
971563AH1-280 GEN
Solar/Wind Harmer
4.201
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.371
316322AB2-045
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.88
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.352
971795AH1-408 GEN
Solar/Wind Harmer
10.596
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.538
971377AH1-170 GEN
Solar/Wind Harmer
1.457
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.58
960081AF2-299 GEN
Solar/Wind Harmer
0.929
316336AC2-165 C
Solar/Wind Harmer
1.333
3143336POWHATN
Solar/Wind Harmer
0.777
963191AG1-168 GEN
Solar/Wind Harmer
3.151
942751AE2-291 GEN
Solar/Wind Harmer
21.312
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.148
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.964
316197AC1-042 GEN
Solar/Wind Harmer
1.489
942671AE2-283 GEN
Solar/Wind Harmer
4.009
971489AH1-241 GEN
Solar/Wind Harmer
6.918
315821AE2-092 GEN
Solar/Wind Harmer
1.803
316181AB2-040 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.79
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.556
G-007ALTFEXP_G-007A->PJM
CMTX
0.495
VTFLTFEXP_VFT->PJM
CMTX
1.304
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.8
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.478
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.891
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.359
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.834
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.63
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.72 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1179.24
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
47.114
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.077
316248AF1-058 C
Solar/Wind Harmer
1.79
960061AF2-297 GEN
Solar/Wind Harmer
29.705
316478AD1-087 GEN
Solar/Wind Harmer
4.923
316486AD2-202 GEN
Solar/Wind Harmer
1.442
971683AH1-343 GEN
Solar/Wind Harmer
21.974
970909AG2-566 GEN
Solar/Wind Harmer
3.698
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.993
315785AD2-033 C
Solar/Wind Harmer
7.962
970257AG2-171 GEN
Solar/Wind Harmer
13.074
959311AF2-222 GEN
Solar/Wind Harmer
36.183
963181AG1-167 GEN
Solar/Wind Harmer
3.146
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.696
942461AE2-259 GEN
Solar/Wind Harmer
4.788
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.143
970099AG2-077 GEN
Solar/Wind Harmer
67.819
970933AG2-581 GEN
Solar/Wind Harmer
50.154
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.629
962561AG1-105 GEN
Solar/Wind Harmer
26.841
971741AH1-377 GEN
Solar/Wind Harmer
48.342
970301AG2-198 GEN
Solar/Wind Harmer
19.474
313527AB2-043 GEN
Solar/Wind Harmer
5.908
970323AG2-213 GEN
Solar/Wind Harmer
17.432
971775AH1-396 GEN
Solar/Wind Harmer
2.482
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.244
963191AG1-168 GEN
Solar/Wind Harmer
3.146
942751AE2-291 GEN
Solar/Wind Harmer
21.251
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.099
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
3151541CLOVER2
50/50
10.745
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.251
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.759
971967AH1-528 GEN
Solar/Wind Harmer
100.577
970865AG2-541 GEN
Solar/Wind Harmer
19.046
316123AC1-075 GEN
Solar/Wind Harmer
4.164
970165AG2-112 GEN
Solar/Wind Harmer
3.666
970163AG2-111 GEN
Solar/Wind Harmer
3.497
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.874
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.709
970681AG2-440 GEN
Solar/Wind Harmer
21.367
946301AF1-294 GEN
Solar/Wind Harmer
8.599
961791AG1-021 GEN
Solar/Wind Harmer
4.195
315657AE1-056 GEN
Solar/Wind Harmer
12.418
970285AG2-188 GEN
Solar/Wind Harmer
21.458
971845AH1-439 GEN
Solar/Wind Harmer
12.354
970831AG2-522 GEN
Solar/Wind Harmer
10.001
3151531CLOVER1
50/50
10.796
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.437
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.389
3151911BEARGRDN G1
50/50
1.077
315687AD1-152 GEN
Solar/Wind Harmer
7.743
316003AC1-222 GEN
Solar/Wind Harmer
5.358
957481AF2-042 GEN
Solar/Wind Harmer
169.548
315693AD1-088 GEN
Solar/Wind Harmer
25.22
962491AG1-098 GEN
Solar/Wind Harmer
33.335
970401AG2-262 GEN
Solar/Wind Harmer
3.248
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.914
963171AG1-166 GEN
Solar/Wind Harmer
4.195
971563AH1-280 GEN
Solar/Wind Harmer
4.195
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.337
316322AB2-045
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.875
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.511
970221AG2-151 GEN
Solar/Wind Harmer
7.306
966621AG1-532 GEN
Solar/Wind Harmer
0.168
313506AB2-031 GEN
Solar/Wind Harmer
0.617
316313AB2-026
Solar/Wind Harmer
0.179
316258AE1-075 C
Solar/Wind Harmer
0.161
316405AF2-144 C
Solar/Wind Harmer
0.17
3143336POWHATN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Helper
2.34
270018AE2-047 C O1
Solar/Wind Helper
0.398
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.366
971795AH1-408 GEN
Solar/Wind Harmer
10.594
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.511
971377AH1-170 GEN
Solar/Wind Harmer
1.461
3147623JAMES R
Solar/Wind Harmer
0.181
970937AG2-583 GEN
Solar/Wind Harmer
7.619
960081AF2-299 GEN
Solar/Wind Harmer
0.931
316336AC2-165 C
Solar/Wind Harmer
1.347
3143336POWHATN
Solar/Wind Harmer
0.788
316217AC1-145 GEN
Solar/Wind Harmer
1.952
316197AC1-042 GEN
Solar/Wind Harmer
1.48
942671AE2-283 GEN
Solar/Wind Harmer
3.984
971489AH1-241 GEN
Solar/Wind Harmer
6.936
315821AE2-092 GEN
Solar/Wind Harmer
1.81
316181AB2-040 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.576
971447AH1-217 GEN
Solar/Wind Harmer
3.943
270494AE1-108_GEN
Solar/Wind Harmer
2.518
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.121
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.392
270457AD2-023 GEN
Solar/Wind Helper
0.917
G-007ALTFEXP_G-007A->PJM
CMTX
0.588
VTFLTFEXP_VFT->PJM
CMTX
1.552
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.847
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.64
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.009
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.461
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.854
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.69
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1179.05
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.745
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.251
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.759
971967AH1-528 GEN
Solar/Wind Harmer
100.577
970865AG2-541 GEN
Solar/Wind Harmer
19.046
316123AC1-075 GEN
Solar/Wind Harmer
4.164
970165AG2-112 GEN
Solar/Wind Harmer
3.666
970163AG2-111 GEN
Solar/Wind Harmer
3.497
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.874
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.709
970681AG2-440 GEN
Solar/Wind Harmer
21.367
946301AF1-294 GEN
Solar/Wind Harmer
8.599
961791AG1-021 GEN
Solar/Wind Harmer
4.195
315657AE1-056 GEN
Solar/Wind Harmer
12.418
970285AG2-188 GEN
Solar/Wind Harmer
21.458
971845AH1-439 GEN
Solar/Wind Harmer
12.354
970831AG2-522 GEN
Solar/Wind Harmer
10.001
971447AH1-217 GEN
Solar/Wind Harmer
3.943
270494AE1-108_GEN
Solar/Wind Harmer
2.518
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.121
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.392
270457AD2-023 GEN
Solar/Wind Helper
0.917
3151531CLOVER1
50/50
10.796
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.437
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.389
3151911BEARGRDN G1
50/50
1.077
315687AD1-152 GEN
Solar/Wind Harmer
7.743
316003AC1-222 GEN
Solar/Wind Harmer
5.358
957481AF2-042 GEN
Solar/Wind Harmer
169.548
315693AD1-088 GEN
Solar/Wind Harmer
25.22
962491AG1-098 GEN
Solar/Wind Harmer
33.335
970401AG2-262 GEN
Solar/Wind Harmer
3.248
970413AG2-270 GEN
50/50
47.114
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.077
316248AF1-058 C
Solar/Wind Harmer
1.79
960061AF2-297 GEN
Solar/Wind Harmer
29.705
316478AD1-087 GEN
Solar/Wind Harmer
4.923
316486AD2-202 GEN
Solar/Wind Harmer
1.442
971683AH1-343 GEN
Solar/Wind Harmer
21.974
970909AG2-566 GEN
Solar/Wind Harmer
3.698
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.993
315785AD2-033 C
Solar/Wind Harmer
7.962
970257AG2-171 GEN
Solar/Wind Harmer
13.074
959311AF2-222 GEN
Solar/Wind Harmer
36.183
963181AG1-167 GEN
Solar/Wind Harmer
3.146
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.696
942461AE2-259 GEN
Solar/Wind Harmer
4.788
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.511
970221AG2-151 GEN
Solar/Wind Harmer
7.306
966621AG1-532 GEN
Solar/Wind Harmer
0.168
313506AB2-031 GEN
Solar/Wind Harmer
0.617
316313AB2-026
Solar/Wind Harmer
0.179
316258AE1-075 C
Solar/Wind Harmer
0.161
316405AF2-144 C
Solar/Wind Harmer
0.17
3143336POWHATN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Helper
2.34
270018AE2-047 C O1
Solar/Wind Helper
0.398
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.143
970099AG2-077 GEN
Solar/Wind Harmer
67.819
970933AG2-581 GEN
Solar/Wind Harmer
50.154
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.629
962561AG1-105 GEN
Solar/Wind Harmer
26.841
971741AH1-377 GEN
Solar/Wind Harmer
48.342
970301AG2-198 GEN
Solar/Wind Harmer
19.474
313527AB2-043 GEN
Solar/Wind Harmer
5.908
970323AG2-213 GEN
Solar/Wind Harmer
17.432
971775AH1-396 GEN
Solar/Wind Harmer
2.482
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.244
963191AG1-168 GEN
Solar/Wind Harmer
3.146
942751AE2-291 GEN
Solar/Wind Harmer
21.251
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.099
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.952
316197AC1-042 GEN
Solar/Wind Harmer
1.48
942671AE2-283 GEN
Solar/Wind Harmer
3.984
971489AH1-241 GEN
Solar/Wind Harmer
6.936
315821AE2-092 GEN
Solar/Wind Harmer
1.81
316181AB2-040 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.576
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.914
963171AG1-166 GEN
Solar/Wind Harmer
4.195
971563AH1-280 GEN
Solar/Wind Harmer
4.195
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.337
316322AB2-045
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.875
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.366
971795AH1-408 GEN
Solar/Wind Harmer
10.594
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.511
971377AH1-170 GEN
Solar/Wind Harmer
1.461
3147623JAMES R
Solar/Wind Harmer
0.181
970937AG2-583 GEN
Solar/Wind Harmer
7.619
960081AF2-299 GEN
Solar/Wind Harmer
0.931
316336AC2-165 C
Solar/Wind Harmer
1.347
3143336POWHATN
Solar/Wind Harmer
0.788
G-007ALTFEXP_G-007A->PJM
CMTX
0.588
VTFLTFEXP_VFT->PJM
CMTX
1.552
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.847
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.64
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.009
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.461
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.854
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.69
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.45 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1154.15
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
47.647
3144293JTRSVLE
50/50
1.004
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.06
316248AF1-058 C
Solar/Wind Harmer
1.8
960061AF2-297 GEN
Solar/Wind Harmer
29.874
316478AD1-087 GEN
Solar/Wind Harmer
4.979
316486AD2-202 GEN
Solar/Wind Harmer
1.458
971683AH1-343 GEN
Solar/Wind Harmer
22.104
970909AG2-566 GEN
Solar/Wind Harmer
3.651
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.972
315785AD2-033 C
Solar/Wind Harmer
7.946
970257AG2-171 GEN
Solar/Wind Harmer
13.041
959311AF2-222 GEN
Solar/Wind Harmer
36.078
963181AG1-167 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.572
942461AE2-259 GEN
Solar/Wind Harmer
4.746
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.561
970221AG2-151 GEN
Solar/Wind Harmer
7.194
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.616
316313AB2-026
Solar/Wind Harmer
0.174
316258AE1-075 C
Solar/Wind Harmer
0.157
316405AF2-144 C
Solar/Wind Harmer
0.166
3143336POWHATN
Solar/Wind Harmer
0.652
316283AC2-100 C
Solar/Wind Helper
2.307
3151531CLOVER1
50/50
10.918
3144293JTRSVLE
50/50
1.004
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.35
3151931BEARGRDN S1
50/50
1.368
3151911BEARGRDN G1
50/50
1.06
315687AD1-152 GEN
Solar/Wind Harmer
7.81
957481AF2-042 GEN
Solar/Wind Harmer
173.007
316003AC1-222 GEN
Solar/Wind Harmer
5.389
970401AG2-262 GEN
Solar/Wind Harmer
3.261
315693AD1-088 GEN
Solar/Wind Harmer
24.89
962491AG1-098 GEN
Solar/Wind Harmer
32.899
316237AB2-079_GEN
Solar/Wind Harmer
1.107
970685AG2-442 GEN
Solar/Wind Harmer
29.8
963171AG1-166 GEN
Solar/Wind Harmer
4.173
971563AH1-280 GEN
Solar/Wind Harmer
4.173
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.345
316322AB2-045
Solar/Wind Harmer
0.75
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.876
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.257
971795AH1-408 GEN
Solar/Wind Harmer
10.577
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.561
971377AH1-170 GEN
Solar/Wind Harmer
1.439
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.48
960081AF2-299 GEN
Solar/Wind Harmer
0.928
316336AC2-165 C
Solar/Wind Harmer
1.315
3143336POWHATN
Solar/Wind Harmer
0.767
3152661PLYWOOD A
50/50
1.09
3144293JTRSVLE
50/50
1.004
3144293JTRSVLE
50/50
0.845
970535AG2-341 GEN
50/50
5.145
970099AG2-077 GEN
Solar/Wind Harmer
69.203
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.672
962561AG1-105 GEN
Solar/Wind Harmer
26.937
971741AH1-377 GEN
Solar/Wind Harmer
47.726
970301AG2-198 GEN
Solar/Wind Harmer
19.228
313527AB2-043 GEN
Solar/Wind Harmer
5.909
970323AG2-213 GEN
Solar/Wind Harmer
17.388
971775AH1-396 GEN
Solar/Wind Harmer
2.476
316034AC1-036 C
Solar/Wind Harmer
0.645
942751AE2-291 GEN
Solar/Wind Harmer
21.395
958211AF2-115 GEN
Solar/Wind Harmer
5.217
963191AG1-168 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.11
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.974
316197AC1-042 GEN
Solar/Wind Harmer
1.496
942671AE2-283 GEN
Solar/Wind Harmer
4.029
971489AH1-241 GEN
Solar/Wind Harmer
6.83
315821AE2-092 GEN
Solar/Wind Harmer
1.78
316181AB2-040 GEN
Solar/Wind Harmer
1.069
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.541
3151541CLOVER2
50/50
10.866
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.169
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.778
970865AG2-541 GEN
Solar/Wind Harmer
19.161
316123AC1-075 GEN
Solar/Wind Harmer
4.191
970165AG2-112 GEN
Solar/Wind Harmer
3.69
970163AG2-111 GEN
Solar/Wind Harmer
3.52
316239AB2-077_GEN
Solar/Wind Harmer
1.107
316238AB2-078_GEN
Solar/Wind Harmer
1.107
971443AH1-215 GEN
Solar/Wind Harmer
6.858
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.607
970681AG2-440 GEN
Solar/Wind Harmer
21.285
946301AF1-294 GEN
Solar/Wind Harmer
8.556
961791AG1-021 GEN
Solar/Wind Harmer
4.173
315657AE1-056 GEN
Solar/Wind Harmer
12.343
970285AG2-188 GEN
Solar/Wind Harmer
21.187
971845AH1-439 GEN
Solar/Wind Harmer
12.195
970831AG2-522 GEN
Solar/Wind Harmer
10.008
971447AH1-217 GEN
Solar/Wind Harmer
3.882
270494AE1-108_GEN
Solar/Wind Harmer
2.486
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.118
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.363
270457AD2-023 GEN
Solar/Wind Helper
0.898
G-007ALTFEXP_G-007A->PJM
CMTX
0.474
VTFLTFEXP_VFT->PJM
CMTX
1.248
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.441
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.862
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.44 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1154.09
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.865
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.17
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.778
970865AG2-541 GEN
Solar/Wind Harmer
19.161
316123AC1-075 GEN
Solar/Wind Harmer
4.19
970165AG2-112 GEN
Solar/Wind Harmer
3.69
970163AG2-111 GEN
Solar/Wind Harmer
3.52
316239AB2-077_GEN
Solar/Wind Harmer
1.107
316238AB2-078_GEN
Solar/Wind Harmer
1.107
971443AH1-215 GEN
Solar/Wind Harmer
6.858
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.608
970681AG2-440 GEN
Solar/Wind Harmer
21.286
946301AF1-294 GEN
Solar/Wind Harmer
8.556
961791AG1-021 GEN
Solar/Wind Harmer
4.174
315657AE1-056 GEN
Solar/Wind Harmer
12.344
970285AG2-188 GEN
Solar/Wind Harmer
21.189
971845AH1-439 GEN
Solar/Wind Harmer
12.197
970413AG2-270 GEN
50/50
47.644
3144293JTRSVLE
50/50
1.004
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.06
316248AF1-058 C
Solar/Wind Harmer
1.8
960061AF2-297 GEN
Solar/Wind Harmer
29.873
316478AD1-087 GEN
Solar/Wind Harmer
4.978
316486AD2-202 GEN
Solar/Wind Harmer
1.458
971683AH1-343 GEN
Solar/Wind Harmer
22.104
970909AG2-566 GEN
Solar/Wind Harmer
3.651
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.973
315785AD2-033 C
Solar/Wind Harmer
7.946
970257AG2-171 GEN
Solar/Wind Harmer
13.042
959311AF2-222 GEN
Solar/Wind Harmer
36.079
963181AG1-167 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.573
942461AE2-259 GEN
Solar/Wind Harmer
4.746
3146926FARMVIL
Solar/Wind Harmer
-0.018
3152661PLYWOOD A
50/50
1.09
3144293JTRSVLE
50/50
1.004
3144293JTRSVLE
50/50
0.845
970535AG2-341 GEN
50/50
5.145
970099AG2-077 GEN
Solar/Wind Harmer
69.194
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.672
962561AG1-105 GEN
Solar/Wind Harmer
26.937
971741AH1-377 GEN
Solar/Wind Harmer
47.731
970301AG2-198 GEN
Solar/Wind Harmer
19.23
313527AB2-043 GEN
Solar/Wind Harmer
5.909
970323AG2-213 GEN
Solar/Wind Harmer
17.389
971775AH1-396 GEN
Solar/Wind Harmer
2.476
316034AC1-036 C
Solar/Wind Harmer
0.645
942751AE2-291 GEN
Solar/Wind Harmer
21.394
958211AF2-115 GEN
Solar/Wind Harmer
5.217
963191AG1-168 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.11
3151531CLOVER1
50/50
10.918
3144293JTRSVLE
50/50
1.004
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.436
3151561HALLBR1
50/50
0.35
3151931BEARGRDN S1
50/50
1.368
3151911BEARGRDN G1
50/50
1.06
315687AD1-152 GEN
Solar/Wind Harmer
7.809
957481AF2-042 GEN
Solar/Wind Harmer
172.984
316003AC1-222 GEN
Solar/Wind Harmer
5.389
970401AG2-262 GEN
Solar/Wind Harmer
3.261
315693AD1-088 GEN
Solar/Wind Harmer
24.893
962491AG1-098 GEN
Solar/Wind Harmer
32.903
316237AB2-079_GEN
Solar/Wind Harmer
1.107
970685AG2-442 GEN
Solar/Wind Harmer
29.801
963171AG1-166 GEN
Solar/Wind Harmer
4.174
971563AH1-280 GEN
Solar/Wind Harmer
4.174
3146926FARMVIL
Solar/Wind Harmer
-0.018
970831AG2-522 GEN
Solar/Wind Harmer
10.008
971447AH1-217 GEN
Solar/Wind Harmer
3.882
270494AE1-108_GEN
Solar/Wind Harmer
2.486
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.118
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.363
270457AD2-023 GEN
Solar/Wind Helper
0.898
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.974
316197AC1-042 GEN
Solar/Wind Harmer
1.496
942671AE2-283 GEN
Solar/Wind Harmer
4.029
971489AH1-241 GEN
Solar/Wind Harmer
6.83
315821AE2-092 GEN
Solar/Wind Harmer
1.78
316181AB2-040 GEN
Solar/Wind Harmer
1.069
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.541
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.561
970221AG2-151 GEN
Solar/Wind Harmer
7.195
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.616
316313AB2-026
Solar/Wind Harmer
0.174
316258AE1-075 C
Solar/Wind Harmer
0.157
316405AF2-144 C
Solar/Wind Harmer
0.166
3143336POWHATN
Solar/Wind Harmer
0.652
316283AC2-100 C
Solar/Wind Helper
2.307
971065AG2-659 GEN
Solar/Wind Harmer
11.345
316322AB2-045
Solar/Wind Harmer
0.75
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.876
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.258
971795AH1-408 GEN
Solar/Wind Harmer
10.578
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.561
971377AH1-170 GEN
Solar/Wind Harmer
1.439
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.481
960081AF2-299 GEN
Solar/Wind Harmer
0.928
316336AC2-165 C
Solar/Wind Harmer
1.315
3143336POWHATN
Solar/Wind Harmer
0.767
G-007ALTFEXP_G-007A->PJM
CMTX
0.475
VTFLTFEXP_VFT->PJM
CMTX
1.249
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.441
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.862
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.61 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:2079.09
MW Contribution:0.5
Bus #Bus NameTypeMW Contribution
972289AH1-729 GEN
50/50
13.249
3150091POSSM6B
50/50
0.848
3150071POSSM 5
50/50
52.224
3150181POSSMC2
50/50
1.152
3150181POSSMC2
50/50
1.143
3150181POSSMC2
50/50
1.143
316447AC1-158 HLD
Solar/Wind Harmer
1.014
3150391LDYSMT3
Adder
12.655
972195AH1-682 GEN
Adder
1.663
315651AD1-115 GEN
Solar/Wind Harmer
0.003
315673AE1-157 GEN
Solar/Wind Harmer
6.396
957411AF2-035 GEN
Solar/Wind Harmer
3.895
970317AG2-208 GEN
Solar/Wind Harmer
3.609
316468AD1-105 GEN
Solar/Wind Harmer
-0.029
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.051
958261AF2-120 GEN
Solar/Wind Harmer
2.86
3151731LOISA B
Adder
5.599
3151721LOISA A
Adder
5.57
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.023
3142946ENON
Solar/Wind Harmer
0.008
3143526WINTERP
Solar/Wind Harmer
0.435
971223AH1-071 GEN
Solar/Wind Harmer
0.89
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.005
315697AD1-025 GEN
Solar/Wind Harmer
0.092
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.829
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.077
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.193
3145506HICKORY
Solar/Wind Harmer
0.048
316339AD2-160 GEN
Solar/Wind Harmer
0.13
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.045
3137176SLIGO L2192
Solar/Wind Harmer
0.319
3146456SLIGO L269
Solar/Wind Harmer
1.416
3130086AYDLETT
Solar/Wind Harmer
0.32
3146386ELIZ CT
Solar/Wind Harmer
0.08
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3144356SAPONY
Solar/Wind Harmer
0.657
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
972185AH1-677 GEN
Adder
4.331
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
6.107
316065AD1-022 GEN
Solar/Wind Harmer
3.475
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
970099AG2-077 GEN
Solar/Wind Harmer
7.908
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
971741AH1-377 GEN
Solar/Wind Harmer
7.304
970301AG2-198 GEN
Solar/Wind Harmer
3.138
316426AA2-053 GEN
Solar/Wind Harmer
0.248
3146776BUCKING
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.024
966811AG1-552 GEN
Solar/Wind Harmer
0.795
3145593CAROLNA
Solar/Wind Harmer
0.091
3145783HORNRTN
Solar/Wind Harmer
1.299
3145783HORNRTN
Solar/Wind Harmer
1.039
3145783HORNRTN
Solar/Wind Harmer
0.325
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.866
963191AG1-168 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
3145933PARMELE
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.072
316274AC1-208 GEN
Solar/Wind Harmer
0.372
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
3.057
971775AH1-396 GEN
Solar/Wind Harmer
0.115
971489AH1-241 GEN
Solar/Wind Harmer
3.817
313527AB2-043 GEN
Solar/Wind Harmer
0.001
939181AE1-148 GEN
Solar/Wind Harmer
3.402
3145493TOT1
Solar/Wind Harmer
0.162
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.065
315821AE2-092 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
1.228
316263AC1-034 GEN
Solar/Wind Harmer
2.624
964791AG1-342 GEN
Solar/Wind Harmer
1.322
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.264
971761AH1-387 GEN
Solar/Wind Harmer
1.238
942751AE2-291 GEN
Solar/Wind Harmer
3.276
3132123MT JACKSON
Solar/Wind Harmer
0.183
970117AG2-086 GEN
Solar/Wind Harmer
1.401
970117AG2-086 GEN
Solar/Wind Harmer
0.934
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
970053AG2-049 GEN
50/50
2.022
3138216PACIFIC
Solar/Wind Harmer
0.025
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
3141426STAFORD
Solar/Wind Harmer
0.023
3150411LDYSMT5
Adder
12.718
3150381LDYSMT2
Adder
12.172
972213AH1-691 GEN
Adder
2.059
972215AH1-692 GEN
Adder
2.059
316164AC1-076 GEN
Solar/Wind Harmer
0.132
944491AF1-114 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Harmer
0.064
972189AH1-679 GEN
Adder
1.467
3141813NORNECK
Solar/Wind Harmer
0.087
970327AG2-215 GEN
Solar/Wind Harmer
2.824
962981AG1-147 GEN
Solar/Wind Harmer
3.203
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.025
3141913WHIT STONE
Solar/Wind Harmer
0.085
3147346CASHSCORNER
Solar/Wind Harmer
0.196
316312AB1-027
Solar/Wind Harmer
0.152
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.017
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.507
3143873LANEXA
Solar/Wind Harmer
0.051
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
7.477
315976AC1-164 GENA
Solar/Wind Harmer
8.72
316169AC1-164_GENC
Solar/Wind Harmer
7.533
315975AC1-164 GENB
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971281AH1-106 GEN
Solar/Wind Harmer
1.161
971283AH1-107 GEN
Solar/Wind Harmer
1.161
971285AH1-108 GEN
Adder
0.631
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316132AB2-190 GEN1
Solar/Wind Harmer
0.442
316369SG1_INVT
Solar/Wind Harmer
0.003
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.723
3143316POE
Solar/Wind Harmer
0.321
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.055
316311AC2-079 GEN
Solar/Wind Harmer
2.303
957871AF2-081 GEN
Solar/Wind Harmer
3.99
316305AF2-043 C
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.403
3146406KITTY HAWK
Solar/Wind Harmer
0.01
315835AF2-110_GEN
Solar/Wind Harmer
0.548
313526AB2-022
Solar/Wind Harmer
0.043
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316321Z2-027
Solar/Wind Harmer
0.015
3146396TANGLEW
Solar/Wind Harmer
0.219
3145176PASQUOTANK
Solar/Wind Harmer
0.049
316315AB2-025 C
Solar/Wind Harmer
0.064
315814AE2-033 C
Solar/Wind Harmer
6.204
941031AE2-094 GEN
Solar/Wind Harmer
14.412
944011AF1-069 GEN
Solar/Wind Harmer
4.709
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
970673AG2-436 GEN
Solar/Wind Harmer
16.54
970673AG2-436 GEN
Solar/Wind Harmer
11.027
971967AH1-528 GEN
Solar/Wind Harmer
12.344
315816AE2-034 GEN
Solar/Wind Harmer
0.329
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.435
315733AD1-074 GEN2
Solar/Wind Harmer
0.435
315735AD1-075 GEN1
Solar/Wind Harmer
0.218
965291AG1-394 GEN
Solar/Wind Harmer
0.336
3146206CASHIE
Solar/Wind Harmer
0.075
970601AG2-382 GEN
Solar/Wind Harmer
2.811
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.149
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.152
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.294
315652AC1-086 GEN
Solar/Wind Harmer
8.087
972205AH1-687 GEN
Adder
3.134
970285AG2-188 GEN
Solar/Wind Harmer
5.802
971845AH1-439 GEN
Solar/Wind Harmer
3.325
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
3146033SCOT NK
Solar/Wind Harmer
0.29
315657AE1-056 GEN
Solar/Wind Harmer
2.494
946301AF1-294 GEN
Solar/Wind Harmer
1.424
961791AG1-021 GEN
Solar/Wind Harmer
0.693
970683AG2-441 GEN
Solar/Wind Harmer
4.794
970681AG2-440 GEN
Solar/Wind Harmer
3.836
970831AG2-522 GEN
Solar/Wind Harmer
3.066
972193AH1-681 GEN
Adder
1.643
3144303KENBRDG
Solar/Wind Harmer
0.057
971443AH1-215 GEN
Solar/Wind Harmer
1.204
971447AH1-217 GEN
Solar/Wind Harmer
2.163
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.883
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
3.032
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
316118AC1-105 GEN
Solar/Wind Harmer
0.176
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.802
3148133STUARTS
Solar/Wind Harmer
0.039
3148013FISHERV
Solar/Wind Harmer
0.037
970865AG2-541 GEN
Solar/Wind Harmer
2.214
316123AC1-075 GEN
Solar/Wind Harmer
0.084
970165AG2-112 GEN
Solar/Wind Harmer
0.5
970163AG2-111 GEN
Solar/Wind Harmer
0.477
3148463FAIRFLD
Solar/Wind Harmer
0.06
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.279
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.162
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
3152111X4-039 GT1
50/50
1.838
315747AE2-019 GEN
50/50
13.176
3150021OMF B
50/50
0.216
3150101POSSM6S
50/50
1.296
3150081POSSM6A
50/50
0.848
3150151POSSMC1
50/50
1.143
3150151POSSMC1
50/50
1.143
3150231REMNGT3
50/50
14.281
3150241REMNGT4
50/50
13.316
972217AH1-693 GEN
50/50
1.756
963691AG1-221 GEN
Solar/Wind Harmer
2.312
971455AH1-223 GEN
Solar/Wind Harmer
2.312
3141196NOKESVL
Solar/Wind Harmer
0.429
972199AH1-684 GEN
Adder
1.903
3150301M RUN C
Adder
13.349
3150291M RUN B
Adder
13.25
3150331BIRCHWDA
Adder
16.626
3141316ARNOLDS
Adder
0.229
316044AC1-158 PL1
Solar/Wind Harmer
0.461
316450AC1-158 RIC
Solar/Wind Harmer
0.123
3150401LDYSMT4
Adder
12.678
3150371LDYSMT1
Adder
12.251
316170AC1-121 GEN2
Solar/Wind Harmer
0.1
970737AG2-469 GEN
Solar/Wind Harmer
3.872
3141906WESTMOR
Solar/Wind Harmer
0.036
3132273ORANGE
Solar/Wind Harmer
0.018
971781AH1-399 GEN
Solar/Wind Harmer
0.118
3147666LOUISA
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.884
316404AE1-155 C
Solar/Wind Harmer
0.019
3151761LOISA E
Adder
11.415
972183AH1-676 GEN
Adder
92.045
970009AG2-005 GEN
Solar/Wind Harmer
0.643
316473AC1-191 GEN
Solar/Wind Harmer
0.29
962971AG1-146 GEN
Solar/Wind Harmer
1.373
3142416OLDCHRC
Solar/Wind Harmer
0.821
3141766HARMONY
Solar/Wind Harmer
1.129
316156AD2-030 GEN
Solar/Wind Harmer
0.063
3141873WAN 176
Solar/Wind Harmer
1.505
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
0.899
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
0.028
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
0.794
970129AG2-093 GEN
Solar/Wind Harmer
4.984
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
6.579
965281AG1-393 GEN
Solar/Wind Harmer
0.877
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.181
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
0.033
315813AE1-149 C
Solar/Wind Harmer
4.334
315773AC2-141 GEN
Solar/Wind Harmer
2.962
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.012
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
18.149
944601AF1-125 GEN
Solar/Wind Harmer
17.869
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.925
316320Y1-086
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.2
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.078
315614AA2-178 GEN
Solar/Wind Harmer
0.439
971157AH1-035 GEN
Solar/Wind Harmer
0.911
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
315737AD1-076 GEN
Solar/Wind Harmer
0.975
3146206CASHIE
Solar/Wind Harmer
0.075
316365GEN2_N
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
970917AG2-570 GEN
Solar/Wind Harmer
6.681
957521AF2-046 GEN
Solar/Wind Harmer
5.587
961681AG1-008 GEN
Solar/Wind Harmer
5.587
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.339
316463AE2-346 GEN
Solar/Wind Harmer
0.064
316140AB2-099
Solar/Wind Harmer
0.027
962331AG1-082 GEN
Solar/Wind Harmer
0.795
3146263WOODLND
Solar/Wind Harmer
0.074
313506AB2-031 GEN
Solar/Wind Harmer
0.228
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.074
970909AG2-566 GEN
Solar/Wind Harmer
0.785
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
3146776BUCKING
Solar/Wind Harmer
0.026
3146926FARMVIL
Solar/Wind Harmer
0.044
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
3147133PAMPLIN
Solar/Wind Harmer
0.227
971193AH1-056 GEN
Solar/Wind Harmer
4.404
963181AG1-167 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
316210AC1-098 GEN
Solar/Wind Harmer
0.668
972255AH1-712 GEN
Adder
36.775
3145933PARMELE
Solar/Wind Harmer
0.072
966801AG1-551 GEN
Solar/Wind Harmer
0.836
959311AF2-222 GEN
Solar/Wind Harmer
6.376
970257AG2-171 GEN
Solar/Wind Harmer
2.293
970221AG2-151 GEN
Solar/Wind Harmer
3.817
315785AD2-033 C
Solar/Wind Harmer
0.582
964241AG1-285 GEN
Solar/Wind Harmer
4.753
316131AB2-060 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.266
316327AA2-057 GEN
Solar/Wind Harmer
0.106
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.912
971623AH1-311 GEN
Solar/Wind Harmer
0.138
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.87
971683AH1-343 GEN
Solar/Wind Harmer
2.391
3148013FISHERV
Solar/Wind Harmer
0.065
316283AC2-100 C
Solar/Wind Harmer
0.124
315616AA1-038_C
Solar/Wind Harmer
0
3151861LOWMORA
Adder
0.645
958131AF2-107 GEN
Solar/Wind Harmer
1.618
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
233946AB2-136 GEN
Solar/Wind Helper
0.341
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.042
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.443
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
3152131X4-039 ST
50/50
2.892
3152121X4-039 GT2
50/50
1.833
3150011OMF A
50/50
0.216
3140676OCCOQUN
50/50
0.286
970467AG2-304 GEN
50/50
14.788
972223AH1-696 GEN
50/50
9.026
3150151POSSMC1
50/50
1.143
3141346CRANES
50/50
0.127
3150221REMNGT2
50/50
13.228
972201AH1-685 GEN
50/50
2.282
3150211REMNGT1
Adder
12.383
3150281M RUN A
Adder
13.357
316006AB2-029 C
Solar/Wind Harmer
0.001
971685AH1-345 GEN
Solar/Wind Harmer
0.73
316045AC1-158 PL2
Solar/Wind Harmer
1.475
972197AH1-683 GEN
Adder
1.98
972219AH1-694 GEN
Adder
1.425
316254AC1-120 GEN1
Solar/Wind Harmer
0.2
972135AH1-637 GEN
Solar/Wind Harmer
0.781
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.218
3147666LOUISA
Solar/Wind Harmer
0.355
316192AB2-158 GEN
Solar/Wind Harmer
0.501
316337AD2-073 GEN
Solar/Wind Harmer
0.077
3150351NORNECKC2
Adder
0.87
3141726DUNNSVL
Solar/Wind Harmer
0.348
962861AG1-135 GEN
Solar/Wind Harmer
2.764
3151751LOISA D
Adder
5.599
3138133OCRAN
Solar/Wind Harmer
0.051
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
0.337
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
0.435
3142543TWELFTH
Solar/Wind Harmer
0.008
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.853
3143226MDLTHAN
Solar/Wind Harmer
0.083
316159AE1-175 C
Solar/Wind Harmer
0.072
971317AH1-138 GEN
Solar/Wind Harmer
0.618
970129AG2-093 GEN
Solar/Wind Harmer
2.345
316458AB2-190 GEN2
Solar/Wind Harmer
0.442
315671AE2-027_GEN
Solar/Wind Harmer
5.273
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
3.497
961611AG1-000B GEN
Solar/Wind Harmer
4.29
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
0.325
316294AC1-161 GEN
Solar/Wind Harmer
1.405
970659AG2-427 GEN
Solar/Wind Harmer
3.913
316381AD1-082 GEN
Solar/Wind Harmer
0.084
316375AC2-012 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
8.025
3150981CHESPKA
Adder
1.007
944591AF1-124 GEN
Solar/Wind Harmer
18.213
316072AD1-144
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.251
3146456SLIGO L269
Solar/Wind Harmer
0.08
939411AE1-173 GEN
Solar/Wind Harmer
34.166
316246AF1-032 C
Solar/Wind Harmer
0.036
940641AE2-051 GEN
Solar/Wind Harmer
6.396
316093AE2-104_GEN
Solar/Wind Harmer
1.342
3143336POWHATN
Solar/Wind Harmer
1.412
3146516WINFALL
Solar/Wind Harmer
0.256
3146516WINFALL
Solar/Wind Harmer
0.079
316336AC2-165 C
Solar/Wind Harmer
0.003
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3145663CRESWEL
Solar/Wind Harmer
0.215
971163AH1-040 GEN
Solar/Wind Harmer
6.133
970937AG2-583 GEN
Solar/Wind Harmer
4.64
3146206CASHIE
Solar/Wind Harmer
0.075
971547AH1-271 GEN
Solar/Wind Harmer
1.606
316023GEN1_S
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
5.999
3146173TUNIS
Solar/Wind Harmer
0.075
960081AF2-299 GEN
Solar/Wind Harmer
0.714
3145683EARLEYS
Solar/Wind Harmer
0.074
957481AF2-042 GEN
Solar/Wind Harmer
19.771
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.545
962491AG1-098 GEN
Solar/Wind Harmer
4.214
971795AH1-408 GEN
Solar/Wind Harmer
4.913
3145963POPLR C
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.337
962571AG1-106 GEN
Solar/Wind Harmer
1.046
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Adder
0.664
972003AH1-546 GEN
Solar/Wind Harmer
3.117
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.029
3146926FARMVIL
Solar/Wind Harmer
0.044
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
963171AG1-166 GEN
Solar/Wind Harmer
0.385
971563AH1-280 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.23
316212AC1-099_GEN
Solar/Wind Harmer
0.372
970685AG2-442 GEN
Solar/Wind Harmer
5.37
972277AH1-723 GEN
Adder
42.854
3146293MARTNCO
Solar/Wind Harmer
0.067
316129AC1-054 GEN
Solar/Wind Harmer
0.27
971377AH1-170 GEN
Solar/Wind Harmer
0.763
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.053
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315722AD1-056 GEN
Solar/Wind Harmer
0.448
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316494AC1-189 GEN
Solar/Wind Harmer
0.238
3146233WITAKRS
Solar/Wind Harmer
0.278
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.07
3145493TOT1
Solar/Wind Harmer
0.31
316359AB2-059 GEN
Solar/Wind Harmer
0.248
316049AB1-081 GEN
Solar/Wind Harmer
0.395
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
3142053HEARTS
Solar/Wind Harmer
0.122
970401AG2-262 GEN
Solar/Wind Harmer
0.404
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315705AF1-075 GEN
Solar/Wind Harmer
2.472
3147983MERCK5
Solar/Wind Harmer
0.024
23779801AA1-109
Solar/Wind Helper
0.218
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.111
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232428Y3-058 C
Solar/Wind Helper
0.203
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
CPLELTFEXP_CPLE->PJM
CLTF
5.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.965
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.592
MECLTFEXP_MEC->PJM
CLTF
4.449
SIGELTFEXP_SIGE->PJM
CLTF
0.14
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.324
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.565
TVALTFEXP_TVA->PJM
CLTF
3.188

Details for 8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 9344_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9344_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.63 %
Rating:3256.16 MVA
Rating Type:B
MVA to Mitigate:3472.07
MW Contribution:1.08
Bus #Bus NameTypeMW Contribution
316447AC1-158 HLD
Solar/Wind Harmer
3.008
315651AD1-115 GEN
Solar/Wind Harmer
0.009
966001AG1-469 GEN
Solar/Wind Harmer
0.139
3150391LDYSMT3
Adder
31.782
972195AH1-682 GEN
Adder
4.177
3151731LOISA B
Adder
15.317
3151721LOISA A
Adder
15.238
315673AE1-157 GEN
Solar/Wind Harmer
16.074
957411AF2-035 GEN
Solar/Wind Harmer
9.794
970317AG2-208 GEN
Solar/Wind Harmer
9.074
3150071POSSM 5
Adder
101.873
3150181POSSMC2
Adder
2.248
3150181POSSMC2
Adder
2.229
3150181POSSMC2
Adder
2.229
316468AD1-105 GEN
Solar/Wind Harmer
-0.071
966871AG1-558 GEN
Solar/Wind Harmer
0.248
3142296MT RD221
Adder
0.683
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.231
3150341NORNECKC1
Adder
2.213
971223AH1-071 GEN
Solar/Wind Harmer
2.268
3143526WINTERP
Solar/Wind Harmer
1.104
3142366NRTHEST
Adder
0.693
958261AF2-120 GEN
Solar/Wind Harmer
7.015
3150691DARBY 3
Adder
15.26
3150701DARBY 4
Adder
15.225
3150681DARBY 2
Adder
15.207
3150671DARBY 1
Adder
15.189
316075AC2-137 C
Solar/Wind Harmer
0.058
3142946ENON
Solar/Wind Harmer
0.021
944641AF1-129 GEN
Adder
98.867
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.231
316236AE1-162_GEN
Solar/Wind Harmer
0.002
970657AG2-426 GEN
Solar/Wind Harmer
7.052
970657AG2-426 GEN
Solar/Wind Harmer
1.478
316036AC1-147 C
Solar/Wind Harmer
0.037
3150991CHESPKB
Adder
2.106
3150991CHESPKB
Adder
2.056
316316AC1-027 C
Solar/Wind Harmer
0.193
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.8
3145506HICKORY
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
0.12
316339AD2-160 GEN
Solar/Wind Harmer
0.323
316018AA1-139 ULT2
Solar/Wind Harmer
0.005
316017AA1-139 ULT1
Solar/Wind Harmer
0.111
3137176SLIGO L2192
Solar/Wind Harmer
0.792
3146456SLIGO L269
Solar/Wind Harmer
3.521
3130086AYDLETT
Solar/Wind Harmer
0.795
3146386ELIZ CT
Solar/Wind Harmer
0.197
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.195
3144356SAPONY
Solar/Wind Harmer
1.625
3146626S HERTFORD
Solar/Wind Harmer
0.194
3146626S HERTFORD
Solar/Wind Harmer
0.194
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.847
3146376EDENTON
Solar/Wind Harmer
0.847
972185AH1-677 GEN
Adder
10.672
972187AH1-678 GEN
Adder
5.366
970933AG2-581 GEN
Solar/Wind Harmer
14.962
316065AD1-022 GEN
Solar/Wind Harmer
8.417
3145893MURPHYS
Solar/Wind Harmer
1.217
3145893MURPHYS
Solar/Wind Harmer
0.327
3146173TUNIS
Solar/Wind Harmer
0.18
3146173TUNIS
Solar/Wind Harmer
0.18
970099AG2-077 GEN
Solar/Wind Harmer
19.085
316181AB2-040 GEN
Solar/Wind Harmer
0.257
971741AH1-377 GEN
Solar/Wind Harmer
17.523
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
316164AC1-076 GEN
Solar/Wind Harmer
0.382
3150411LDYSMT5
Adder
31.941
3150381LDYSMT2
Adder
30.569
972213AH1-691 GEN
Adder
5.171
972215AH1-692 GEN
Adder
5.171
3147346CASHSCORNER
Solar/Wind Harmer
0.532
3141426STAFORD
Solar/Wind Harmer
0.05
972189AH1-679 GEN
Adder
3.695
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.155
316312AB1-027
Solar/Wind Harmer
0.381
3141813NORNECK
Solar/Wind Harmer
0.213
316233AE1-074 FULL
Solar/Wind Harmer
0.17
971281AH1-106 GEN
Solar/Wind Harmer
2.946
971283AH1-107 GEN
Solar/Wind Harmer
2.946
970053AG2-049 GEN
Adder
3.548
970327AG2-215 GEN
Solar/Wind Harmer
6.945
962981AG1-147 GEN
Solar/Wind Harmer
7.889
971285AH1-108 GEN
Adder
1.591
3141783LANCAST
Solar/Wind Harmer
0.126
3141783LANCAST
Solar/Wind Harmer
0.084
315976AC1-164 GENA
Solar/Wind Harmer
21.836
316169AC1-164_GENC
Solar/Wind Harmer
18.864
315975AC1-164 GENB
Solar/Wind Harmer
0.646
3138133OCRAN
Solar/Wind Harmer
0.063
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.21
3143873LANEXA
Solar/Wind Harmer
0.126
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
971167AH1-042 GEN
Solar/Wind Harmer
18.654
970189AG2-124 GEN
Solar/Wind Harmer
6.224
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.042
3138283WHITEMARSH
Solar/Wind Harmer
0.048
316132AB2-190 GEN1
Solar/Wind Harmer
1.107
316369SG1_INVT
Solar/Wind Harmer
0.008
972265AH1-717 GEN
Adder
15.821
3151201GRAVEL4
Adder
14.831
3151191GRAVEL3
Adder
14.643
3151211GRAVEL5
Adder
14.643
3143316POE
Solar/Wind Harmer
0.803
971445AH1-216 GEN
Solar/Wind Harmer
14.282
3151081ELIZAR1
Adder
18.434
3151091ELIZAR2
Adder
18.114
3152611GOSPORTB
Adder
2.56
3152621GOSPORTC
Adder
2.173
3152601GOSPORTA
Adder
2.005
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.137
316311AC2-079 GEN
Solar/Wind Harmer
5.725
957871AF2-081 GEN
Solar/Wind Harmer
9.922
319010AE1-072 C
Solar/Wind Harmer
1.001
316305AF2-043 C
Solar/Wind Harmer
0.002
3146406KITTY HAWK
Solar/Wind Harmer
0.025
315835AF2-110_GEN
Solar/Wind Harmer
1.359
313526AB2-022
Solar/Wind Harmer
0.107
3146486SUNBURY
Solar/Wind Harmer
0.197
3146486SUNBURY
Solar/Wind Harmer
0.197
316321Z2-027
Solar/Wind Harmer
0.037
3146396TANGLEW
Solar/Wind Harmer
0.542
3145176PASQUOTANK
Solar/Wind Harmer
0.122
316315AB2-025 C
Solar/Wind Harmer
0.157
941031AE2-094 GEN
Solar/Wind Harmer
35.747
944011AF1-069 GEN
Solar/Wind Harmer
11.68
315814AE2-033 C
Solar/Wind Harmer
15.327
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
40.848
970673AG2-436 GEN
Solar/Wind Harmer
27.232
3130156CHOWAN
Solar/Wind Harmer
0.19
3130156CHOWAN
Solar/Wind Harmer
0.19
971967AH1-528 GEN
Solar/Wind Harmer
30.407
315816AE2-034 GEN
Solar/Wind Harmer
0.803
3130546PLYMOUTH
Solar/Wind Harmer
0.184
315732AD1-074 GEN1
Solar/Wind Harmer
1.056
315733AD1-074 GEN2
Solar/Wind Harmer
1.056
315735AD1-075 GEN1
Solar/Wind Harmer
0.529
965291AG1-394 GEN
Solar/Wind Harmer
0.815
970085AG2-068 GEN
Solar/Wind Harmer
9.72
970581AG2-369 GEN
Solar/Wind Harmer
8.359
3146206CASHIE
Solar/Wind Harmer
0.182
970601AG2-382 GEN
Solar/Wind Harmer
6.803
3145893MURPHYS
Solar/Wind Harmer
0.491
3145893MURPHYS
Solar/Wind Harmer
0.182
3145513AHOSKIE
Solar/Wind Harmer
0.376
3145513AHOSKIE
Solar/Wind Harmer
0.179
3146043SEABORD
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.358
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.179
315607AA1-063A GEN
Solar/Wind Harmer
0.365
316087AB2-174 GEN
Solar/Wind Harmer
0.005
3137643SOCKMAN
Solar/Wind Harmer
0.704
315652AC1-086 GEN
Solar/Wind Harmer
19.374
970285AG2-188 GEN
Solar/Wind Harmer
13.847
971845AH1-439 GEN
Solar/Wind Harmer
7.933
972205AH1-687 GEN
Adder
7.463
3145796HORNRTN
Solar/Wind Harmer
0.556
3145796HORNRTN
Solar/Wind Harmer
0.07
3146033SCOT NK
Solar/Wind Harmer
0.691
315657AE1-056 GEN
Solar/Wind Harmer
5.923
946301AF1-294 GEN
Solar/Wind Harmer
3.377
961791AG1-021 GEN
Solar/Wind Harmer
1.643
970683AG2-441 GEN
Solar/Wind Harmer
11.355
970681AG2-440 GEN
Solar/Wind Harmer
9.084
970831AG2-522 GEN
Solar/Wind Harmer
7.264
3144303KENBRDG
Solar/Wind Harmer
0.135
971443AH1-215 GEN
Solar/Wind Harmer
2.845
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.179
3145746EVERETS
Solar/Wind Harmer
0.664
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
970181AG2-120 GEN
Solar/Wind Harmer
2.078
971447AH1-217 GEN
Solar/Wind Harmer
5.04
957861AF2-080 GEN
Solar/Wind Harmer
7.098
316420AA1-050 GEN
Solar/Wind Harmer
0.005
972193AH1-681 GEN
Adder
3.732
316319Z2-044 C
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.007
971255AH1-087 GEN
50/50
5.432
971259AH1-089 GEN
50/50
5.432
3150281M RUN A
50/50
43.576
3150221REMNGT2
50/50
40.487
972201AH1-685 GEN
50/50
6.985
3150211REMNGT1
Adder
37.902
316006AB2-029 C
Solar/Wind Harmer
0.002
971685AH1-345 GEN
Solar/Wind Harmer
2.219
316045AC1-158 PL2
Solar/Wind Harmer
4.376
316254AC1-120 GEN1
Solar/Wind Harmer
0.583
315683AE1-153 C
Solar/Wind Harmer
20.71
3147666LOUISA
Solar/Wind Harmer
0.979
316192AB2-158 GEN
Solar/Wind Harmer
1.381
972197AH1-683 GEN
Adder
4.972
972219AH1-694 GEN
Adder
3.58
3151751LOISA D
Adder
15.317
3140676OCCOQUN
Adder
0.566
966881AG1-559 GEN
Solar/Wind Harmer
0.265
3141346CRANES
Adder
0.266
972223AH1-696 GEN
Adder
17.606
3150151POSSMC1
Adder
2.229
972135AH1-637 GEN
Solar/Wind Harmer
1.858
316337AD2-073 GEN
Solar/Wind Harmer
0.187
3142416OLDCHRC
Solar/Wind Harmer
0.554
3142416OLDCHRC
Solar/Wind Harmer
0.212
3150351NORNECKC2
Adder
2.124
3141726DUNNSVL
Solar/Wind Harmer
0.851
3143226MDLTHAN
Solar/Wind Harmer
0.212
3143526WINTERP
Solar/Wind Harmer
1.104
962861AG1-135 GEN
Solar/Wind Harmer
6.784
3150851SPRUNCC
Adder
0.972
3143096IRON208
Adder
0.883
3142543TWELFTH
Solar/Wind Harmer
0.02
3138133OCRAN
Solar/Wind Harmer
0.126
3141766HARMONY
Solar/Wind Harmer
0.042
3142433PROV 92
Solar/Wind Harmer
0.84
3138266HYDRAULIC
Solar/Wind Harmer
0.004
3145573BETHELC
Solar/Wind Harmer
0.163
3145573BETHELC
Solar/Wind Harmer
0.163
316118AC1-105 GEN
Solar/Wind Harmer
0.404
3147173SINAI
Solar/Wind Harmer
0.154
3147243WELCO
Solar/Wind Harmer
0.096
270494AE1-108_GEN
Solar/Wind Harmer
1.806
970865AG2-541 GEN
Solar/Wind Harmer
4.891
3148133STUARTS
Solar/Wind Harmer
0.083
3148013FISHERV
Solar/Wind Harmer
0.079
316123AC1-075 GEN
Solar/Wind Harmer
0.181
971253AH1-086 GEN
50/50
24.442
971257AH1-088 GEN
50/50
5.432
3150301M RUN C
50/50
43.549
3150291M RUN B
50/50
43.226
3150231REMNGT3
50/50
43.711
3150241REMNGT4
50/50
40.756
972217AH1-693 GEN
50/50
5.373
972199AH1-684 GEN
Adder
5.823
3141196NOKESVL
Solar/Wind Harmer
1.195
316044AC1-158 PL1
Solar/Wind Harmer
1.369
316450AC1-158 RIC
Solar/Wind Harmer
0.365
316170AC1-121 GEN2
Solar/Wind Harmer
0.291
3132273ORANGE
Solar/Wind Harmer
0.051
3147666LOUISA
Solar/Wind Harmer
0.563
3150401LDYSMT4
Adder
31.841
3150371LDYSMT1
Adder
30.767
3151761LOISA E
Adder
31.228
972183AH1-676 GEN
Adder
251.695
3150331BIRCHWDA
Adder
38.122
3150151POSSMC1
Adder
2.229
3150151POSSMC1
Adder
2.229
3141316ARNOLDS
Adder
0.53
971781AH1-399 GEN
Solar/Wind Harmer
0.287
970737AG2-469 GEN
Solar/Wind Harmer
9.258
3141906WESTMOR
Solar/Wind Harmer
0.086
316473AC1-191 GEN
Solar/Wind Harmer
0.726
3142416OLDCHRC
Solar/Wind Harmer
2.065
3150351NORNECKC2
Adder
2.16
316404AE1-155 C
Solar/Wind Harmer
0.048
970293AG2-193 GEN
Solar/Wind Harmer
2.259
970009AG2-005 GEN
Solar/Wind Harmer
1.58
962971AG1-146 GEN
Solar/Wind Harmer
3.381
3150861SPRUNCD
Adder
0.972
3143096IRON208
Adder
0.883
3143096IRON208
Adder
0.866
3141766HARMONY
Solar/Wind Harmer
2.802
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.073
3142946ENON
Solar/Wind Harmer
0.07
316280AD1-041 GEN
Solar/Wind Harmer
0.004
316156AD2-030 GEN
Solar/Wind Harmer
0.155
3141873WAN 176
Solar/Wind Harmer
3.731
316382AG1-145 C
Solar/Wind Harmer
0.002
970133AG2-095 GEN
Solar/Wind Harmer
1.99
970129AG2-093 GEN
Solar/Wind Harmer
12.476
965281AG1-393 GEN
Solar/Wind Harmer
2.197
315778AD1-151 GEN
Solar/Wind Harmer
16.459
3150921YORKTN3
Adder
5.164
315839AE2-212 C
Solar/Wind Harmer
0.002
3144216WINCHST
Adder
0.774
961611AG1-000B GEN
Solar/Wind Harmer
5.45
3151221GRAVEL6
Adder
14.814
3151171GRAVELC
Adder
2.85
315813AE1-149 C
Solar/Wind Harmer
10.825
3145336SMITFLD
Solar/Wind Harmer
0.081
315773AC2-141 GEN
Solar/Wind Harmer
7.404
970659AG2-427 GEN
Solar/Wind Harmer
2.135
3144536CHRHLND
Solar/Wind Harmer
0.03
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
18.67
3144873MCLAUGH
Solar/Wind Harmer
0.005
944581AF1-123 GEN
Solar/Wind Harmer
45.254
944601AF1-125 GEN
Solar/Wind Harmer
44.557
970661AG2-428 GEN
Solar/Wind Harmer
4.252
3146456SLIGO L269
Solar/Wind Harmer
0.199
971153AH1-033 GEN
Solar/Wind Harmer
2.3
316313AB2-026
Solar/Wind Harmer
0.124
316258AE1-075 C
Solar/Wind Harmer
0.149
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.984
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.195
3146626S HERTFORD
Solar/Wind Harmer
0.194
3145273HOLLAND
Solar/Wind Harmer
0.145
3146376EDENTON
Solar/Wind Harmer
0.19
315614AA2-178 GEN
Solar/Wind Harmer
1.07
971157AH1-035 GEN
Solar/Wind Harmer
2.212
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
315737AD1-076 GEN
Solar/Wind Harmer
2.365
970917AG2-570 GEN
Solar/Wind Harmer
16.254
316365GEN2_N
Solar/Wind Harmer
0.409
3146206CASHIE
Solar/Wind Harmer
0.182
3145893MURPHYS
Solar/Wind Harmer
0.304
3145893MURPHYS
Solar/Wind Harmer
0.182
957521AF2-046 GEN
Solar/Wind Harmer
13.506
961681AG1-008 GEN
Solar/Wind Harmer
13.506
3146173TUNIS
Solar/Wind Harmer
0.18
3156021HOLLOMANSOL
Solar/Wind Harmer
0.817
316463AE2-346 GEN
Solar/Wind Harmer
0.154
316140AB2-099
Solar/Wind Harmer
0.064
962331AG1-082 GEN
Solar/Wind Harmer
1.916
3146263WOODLND
Solar/Wind Harmer
0.178
313506AB2-031 GEN
Solar/Wind Harmer
0.548
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3145963POPLR C
Solar/Wind Harmer
0.176
970909AG2-566 GEN
Solar/Wind Harmer
1.881
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.176
3147043LAWRENC
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.105
3146776BUCKING
Solar/Wind Harmer
0.063
3145796HORNRTN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
0.174
316478AD1-087 GEN
Solar/Wind Harmer
0.607
316486AD2-202 GEN
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.539
971193AH1-056 GEN
Solar/Wind Harmer
10.456
963181AG1-167 GEN
Solar/Wind Harmer
0.685
3144293JTRSVLE
Adder
0.545
316210AC1-098 GEN
Solar/Wind Harmer
1.582
3145933PARMELE
Solar/Wind Harmer
0.17
966801AG1-551 GEN
Solar/Wind Harmer
1.979
959311AF2-222 GEN
Solar/Wind Harmer
15.084
970257AG2-171 GEN
Solar/Wind Harmer
5.422
315785AD2-033 C
Solar/Wind Harmer
1.375
964241AG1-285 GEN
Solar/Wind Harmer
11.211
970221AG2-151 GEN
Solar/Wind Harmer
8.948
316131AB2-060 GEN
Solar/Wind Harmer
0.527
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
315724AD1-057 GEN
Solar/Wind Harmer
0.624
316327AA2-057 GEN
Solar/Wind Harmer
0.25
972255AH1-712 GEN
Adder
83.534
3146233WITAKRS
Solar/Wind Harmer
0.817
3146233WITAKRS
Solar/Wind Harmer
0.111
3146073TAR RVR
Solar/Wind Harmer
0.163
3146083TARBORO
Solar/Wind Harmer
0.163
3138543CONSLDL
Solar/Wind Harmer
0.107
961601AG1-000A GEN
Solar/Wind Harmer
11.396
3145543BTLEBRO
Solar/Wind Harmer
0.16
3145543BTLEBRO
Solar/Wind Harmer
0.16
971623AH1-311 GEN
Solar/Wind Harmer
0.32
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.556
971683AH1-343 GEN
Solar/Wind Harmer
5.342
316283AC2-100 C
Solar/Wind Harmer
0.274
3148013FISHERV
Solar/Wind Harmer
0.138
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
971777AH1-397 GEN
Solar/Wind Harmer
0.554
3141843SHACKLE
Adder
1.073
944631AF1-128 GEN
Adder
99.968
316159AE1-175 C
Solar/Wind Harmer
0.179
971317AH1-138 GEN
Solar/Wind Harmer
1.542
970129AG2-093 GEN
Solar/Wind Harmer
5.871
315671AE2-027_GEN
Solar/Wind Harmer
13.209
316458AB2-190 GEN2
Solar/Wind Harmer
1.107
971069AG2-661 GEN
Solar/Wind Harmer
3.658
3138126ROCKLANDING
Solar/Wind Harmer
0.094
971647AH1-324 GEN
Solar/Wind Harmer
8.741
961611AG1-000B GEN
Solar/Wind Harmer
10.718
3151171GRAVELC
Adder
2.168
3145336SMITFLD
Solar/Wind Harmer
0.811
316294AC1-161 GEN
Solar/Wind Harmer
3.512
970659AG2-427 GEN
Solar/Wind Harmer
9.759
316381AD1-082 GEN
Solar/Wind Harmer
0.21
316375AC2-012 GEN
Solar/Wind Harmer
0.005
3150981CHESPKA
Adder
2.51
944591AF1-124 GEN
Solar/Wind Harmer
45.415
970661AG2-428 GEN
Solar/Wind Harmer
19.99
316072AD1-144
Solar/Wind Harmer
0.072
939411AE1-173 GEN
Solar/Wind Harmer
85.364
940641AE2-051 GEN
Solar/Wind Harmer
15.997
316388AE2-253 GEN
Solar/Wind Harmer
0.625
3146456SLIGO L269
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.09
316093AE2-104_GEN
Solar/Wind Harmer
3.331
3143336POWHATN
Solar/Wind Harmer
3.511
3146516WINFALL
Solar/Wind Harmer
0.632
3146516WINFALL
Solar/Wind Harmer
0.195
316336AC2-165 C
Solar/Wind Harmer
0.008
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.19
3145663CRESWEL
Solar/Wind Harmer
0.523
971163AH1-040 GEN
Solar/Wind Harmer
14.962
970937AG2-583 GEN
Solar/Wind Harmer
11.244
970919AG2-571 GEN
Solar/Wind Harmer
6.502
316023GEN1_S
Solar/Wind Harmer
0.409
970087AG2-069 GEN
Solar/Wind Harmer
14.579
3146206CASHIE
Solar/Wind Harmer
0.182
971547AH1-271 GEN
Solar/Wind Harmer
3.887
3145893MURPHYS
Solar/Wind Harmer
0.727
3145893MURPHYS
Solar/Wind Harmer
0.809
3146173TUNIS
Solar/Wind Harmer
0.18
960081AF2-299 GEN
Solar/Wind Harmer
1.72
3145683EARLEYS
Solar/Wind Harmer
0.179
957481AF2-042 GEN
Solar/Wind Harmer
47.712
3146263WOODLND
Solar/Wind Harmer
0.178
315693AD1-088 GEN
Solar/Wind Harmer
8.533
962491AG1-098 GEN
Solar/Wind Harmer
10.141
971795AH1-408 GEN
Solar/Wind Harmer
11.784
3145963POPLR C
Solar/Wind Harmer
0.176
316011AB1-132 GEN
Solar/Wind Harmer
3.202
962571AG1-106 GEN
Solar/Wind Harmer
2.506
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.176
3147043LAWRENC
Adder
1.589
3146926FARMVIL
Solar/Wind Harmer
0.105
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.07
972003AH1-546 GEN
Solar/Wind Harmer
7.424
3145783HORNRTN
Solar/Wind Harmer
0.174
3145796HORNRTN
Solar/Wind Harmer
0.573
3145796HORNRTN
Solar/Wind Harmer
0.174
963171AG1-166 GEN
Solar/Wind Harmer
0.913
971563AH1-280 GEN
Solar/Wind Harmer
1.826
3144293JTRSVLE
Adder
0.545
316212AC1-099_GEN
Solar/Wind Harmer
0.882
970685AG2-442 GEN
Solar/Wind Harmer
12.717
3146293MARTNCO
Solar/Wind Harmer
0.158
316129AC1-054 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
7.218
971377AH1-170 GEN
Solar/Wind Harmer
1.79
3147623JAMES R
Solar/Wind Harmer
0.389
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
315722AD1-056 GEN
Solar/Wind Harmer
1.053
315687AD1-152 GEN
Solar/Wind Harmer
0.005
316494AC1-189 GEN
Solar/Wind Harmer
0.556
972277AH1-723 GEN
Adder
97.342
3146233WITAKRS
Solar/Wind Harmer
0.648
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.163
3145493TOT1
Solar/Wind Harmer
0.723
3145543BTLEBRO
Solar/Wind Harmer
0.16
3145543BTLEBRO
Solar/Wind Harmer
0.128
316359AB2-059 GEN
Solar/Wind Harmer
0.576
316049AB1-081 GEN
Solar/Wind Harmer
0.917
3142053HEARTS
Solar/Wind Harmer
0.282
970401AG2-262 GEN
Solar/Wind Harmer
0.935
316003AC1-222 GEN
Solar/Wind Harmer
0.004
3147983MERCK5
Solar/Wind Harmer
0.05
315705AF1-075 GEN
Solar/Wind Harmer
4.991
23779801AA1-109
Solar/Wind Helper
0.222
237080AD1-060 GEN
Solar/Wind Helper
0.373
237038AE2-054 C
Solar/Wind Helper
0.293
235062AE1-101 C1
Solar/Wind Helper
1.773
233998TM1NIN_3.36
Solar/Wind Helper
0.269
233972AC1-094 C
Solar/Wind Helper
0.312
232404W1-003 C
Solar/Wind Helper
0.523
232428Y3-058 C
Solar/Wind Helper
0.348
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
233954AC2-188 GEN
Solar/Wind Helper
0.239
233950AC2-186 GEN
Solar/Wind Helper
0.12
232422X3-066 FULL
Solar/Wind Helper
0.117
233930AB2-032 GEN
Solar/Wind Helper
0.391
233915AB1-141 GEN
Solar/Wind Helper
0.516
966131AG1-482 GEN
Solar/Wind Helper
0.138
230511AF1-262
Solar/Wind Helper
0.015
228728W1-130C
Solar/Wind Helper
0.055
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.283
237061AD1-155 GEN
Solar/Wind Harmer
0.003
238221AF1-254 C O1
Solar/Wind Helper
0.304
237030AB1-096 C
Solar/Wind Helper
0.08
235067AD1-061 GEN
Solar/Wind Helper
0.532
205917AD1-020 ES
Solar/Wind Helper
0.38
233994AC2-023 GEN
Solar/Wind Helper
0.99
233996TM1833_GEN
Solar/Wind Helper
0.269
233997TMININ_4.2
Solar/Wind Helper
0.269
233971AC1-093 C
Solar/Wind Helper
0.369
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.239
233918AB1-142 GEN
Solar/Wind Helper
0.516
233982AB2-133 GEN
Solar/Wind Helper
0.368
230430AE1-229_GEN
Solar/Wind Helper
3.449
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.113
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.056
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.153
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.043
219348LDSOLAR C
Solar/Wind Helper
0.117
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.058
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219276PARKLANDSO C
Solar/Wind Helper
0.091
20720528MAN_W1-024
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.028
219908AB1-139 C
Solar/Wind Helper
0.075
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
970165AG2-112 GEN
Solar/Wind Harmer
1.076
970163AG2-111 GEN
Solar/Wind Harmer
1.027
3148463FAIRFLD
Solar/Wind Harmer
0.12
3151881LOWMORC
Adder
1.273
3151881LOWMORC
Adder
1.253
3151861LOWMORA
Adder
1.233
237085AD2-009_GEN
Solar/Wind Helper
1.73
238208AF1-136 C
Solar/Wind Helper
0.215
959381AF2-229 GEN
Solar/Wind Helper
0.375
234033AF1-007_GEN
Solar/Wind Helper
7.236
233923SMA
Solar/Wind Helper
0.988
233990AG1-397 GEN
Solar/Wind Helper
0.278
232432Z2-076 GEN
Solar/Wind Helper
0.069
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.3
203975AE1-071-GEN
Solar/Wind Helper
2.597
964001AG1-254 GEN
Solar/Wind Helper
0.977
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.027
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.117
219688LUMSOLAR_S C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.082
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.097
20715828PEM_W1-120
Solar/Wind Helper
0.097
207459AE1-142 C O1
Solar/Wind Helper
0.295
219620RIDERU C
Solar/Wind Helper
0.001
205943AE1-185 GEN
Solar/Wind Helper
0.503
205956AE1-196_GEN
Solar/Wind Helper
0.502
205932AD2-116_GEN
Solar/Wind Helper
0.502
960921AF2-383 GEN
Solar/Wind Helper
0.358
218526CNTRALGAS2 C
Solar/Wind Helper
0.163
20675528CPH_W2-050
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
3142666NORTHAMPTON
Solar/Wind Harmer
0.106
970301AG2-198 GEN
Solar/Wind Harmer
7.522
316426AA2-053 GEN
Solar/Wind Harmer
0.594
3145593CAROLNA
Solar/Wind Harmer
0.175
3145593CAROLNA
Solar/Wind Harmer
0.175
966811AG1-552 GEN
Solar/Wind Harmer
1.903
3145593CAROLNA
Solar/Wind Harmer
0.218
3146776BUCKING
Solar/Wind Harmer
0.699
3146776BUCKING
Solar/Wind Harmer
0.057
3145783HORNRTN
Solar/Wind Harmer
3.102
3145783HORNRTN
Solar/Wind Harmer
2.482
3145783HORNRTN
Solar/Wind Harmer
0.776
3145783HORNRTN
Solar/Wind Harmer
0.31
3145796HORNRTN
Solar/Wind Harmer
0.521
3147133PAMPLIN
Solar/Wind Harmer
0.172
3147133PAMPLIN
Solar/Wind Harmer
0.137
958211AF2-115 GEN
Solar/Wind Harmer
2.054
963191AG1-168 GEN
Solar/Wind Harmer
0.685
3144293JTRSVLE
Adder
0.545
3144293JTRSVLE
Adder
0.459
3145933PARMELE
Solar/Wind Harmer
0.34
3145933PARMELE
Solar/Wind Harmer
0.17
316274AC1-208 GEN
Solar/Wind Harmer
0.88
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.229
971775AH1-396 GEN
Solar/Wind Harmer
0.271
971489AH1-241 GEN
Solar/Wind Harmer
8.948
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
8.005
3145493TOT1
Solar/Wind Harmer
0.377
3145453TOT5
Solar/Wind Harmer
0.226
3145603CNETO
Solar/Wind Harmer
0.151
962561AG1-105 GEN
Solar/Wind Harmer
7.712
961601AG1-000A GEN
Solar/Wind Harmer
2.849
316263AC1-034 GEN
Solar/Wind Harmer
6.088
964791AG1-342 GEN
Solar/Wind Harmer
3.061
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
315821AE2-092 GEN
Solar/Wind Harmer
0.01
971761AH1-387 GEN
Solar/Wind Harmer
2.843
316222AC1-221 GEN
Solar/Wind Harmer
0.583
942751AE2-291 GEN
Solar/Wind Harmer
6.934
3132123MT JACKSON
Solar/Wind Harmer
0.381
970117AG2-086 GEN
Solar/Wind Harmer
2.919
970117AG2-086 GEN
Solar/Wind Harmer
1.946
235020AA1-095 C
Solar/Wind Helper
0.059
23777901MDS_W4-102
Solar/Wind Helper
0.197
237034AC2-136 C
Solar/Wind Helper
0.259
23777801MSM_W1-116
Solar/Wind Helper
0.131
237001AB1-127_GEN
Solar/Wind Helper
0.481
237025AB1-124 C
Solar/Wind Helper
0.187
237006AB1-125 GEN
Solar/Wind Helper
0.14
237002AB1-128_GEN
Solar/Wind Helper
0.48
235063AE1-101 C2
Solar/Wind Helper
1.773
20390526W1-045 C
Solar/Wind Helper
0.368
205916AD1-020 GEN
Solar/Wind Helper
1.767
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.78
20674628WNG_W3-110
Solar/Wind Helper
0.09
233987AB2-037 GEN
Solar/Wind Helper
2.414
233901CHERRYDALE C
Solar/Wind Helper
0.239
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.585
234036AF2-325 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.12
233944AB2-135 GEN
Solar/Wind Helper
0.605
233933AB2-153 GEN
Solar/Wind Helper
0.239
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.057
963391AG1-188 GEN
Solar/Wind Helper
0.084
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.192
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.017
20673828FLE_V3-070
Solar/Wind Helper
0.092
207442AE1-156 GEN
Solar/Wind Helper
0.329
20676128MHD_W3-029
Solar/Wind Helper
0.097
217081WEATEXAS C
Solar/Wind Helper
0.013
20671828STAW2-080
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20676228FRD_X1-012
Solar/Wind Helper
0.092
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
230434AG1-499 GEN
Solar/Wind Helper
0.235
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219904AC1-010 C
Solar/Wind Helper
0.062
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.041
219907AC1-030 C
Solar/Wind Helper
0.035
219304NAMERICA C
Solar/Wind Helper
0.134
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714828MDF_W3-079
Solar/Wind Helper
0.132
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
207454AA2-184 E
Solar/Wind Helper
0.315
20742028HF_AC1-207
Solar/Wind Helper
0.143
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.077
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.494
207439AE1-081 C O1
Solar/Wind Helper
0.019
20675828AU_W4-064
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.579
20671928W4-073
Solar/Wind Helper
0.09
CPLELTFEXP_CPLE->PJM
CLTF
10.838
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.117
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.101
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.667
MECLTFEXP_MEC->PJM
CLTF
5.134
SIGELTFEXP_SIGE->PJM
CLTF
0.16
NYPJM->LTFIMP_NY
CLTF
4.891
LGEELTFEXP_LGEE->PJM
CLTF
2.004
WECLTFEXP_WEC->PJM
CLTF
1.006
LAGNLTFEXP_LAGN->PJM
CLTF
9.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.867
TVALTFEXP_TVA->PJM
CLTF
4.772

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.66 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4497.83
MW Contribution:1.39
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
10.008
963041AG1-153 GEN
50/50
9.194
315779AE2-040
50/50
3.994
3151541CLOVER2
50/50
5.877
3151081ELIZAR1
50/50
26.432
941031AE2-094 GEN
Solar/Wind Harmer
66.901
944011AF1-069 GEN
Solar/Wind Harmer
21.859
970673AG2-436 GEN
Solar/Wind Harmer
75.678
970673AG2-436 GEN
Solar/Wind Harmer
50.452
971967AH1-528 GEN
Solar/Wind Harmer
55.275
970085AG2-068 GEN
Solar/Wind Harmer
17.517
970581AG2-369 GEN
Solar/Wind Harmer
15.064
316315AB2-025 C
Solar/Wind Harmer
0.231
315814AE2-033 C
Solar/Wind Harmer
22.552
957871AF2-081 GEN
Solar/Wind Harmer
13.58
319010AE1-072 C
Solar/Wind Harmer
1.371
3146406KITTY HAWK
Solar/Wind Harmer
0.034
3151091ELIZAR2
Adder
24.477
3152611GOSPORTB
Adder
3.448
3152621GOSPORTC
Adder
2.926
3152601GOSPORTA
Adder
2.699
313526AB2-022
Solar/Wind Harmer
0.146
316305AF2-043 C
Solar/Wind Harmer
0.002
316321Z2-027
Solar/Wind Harmer
0.05
3146396TANGLEW
Solar/Wind Harmer
0.743
3145176PASQUOTANK
Solar/Wind Harmer
0.167
3146486SUNBURY
Solar/Wind Harmer
0.269
3146486SUNBURY
Solar/Wind Harmer
0.269
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.82
3130156CHOWAN
Solar/Wind Harmer
0.263
3130156CHOWAN
Solar/Wind Harmer
0.263
315816AE2-034 GEN
Solar/Wind Harmer
1.116
3130546PLYMOUTH
Solar/Wind Harmer
0.257
315732AD1-074 GEN1
Solar/Wind Harmer
1.477
315733AD1-074 GEN2
Solar/Wind Harmer
1.477
315735AD1-075 GEN1
Solar/Wind Harmer
0.74
965291AG1-394 GEN
Solar/Wind Harmer
1.138
3146206CASHIE
Solar/Wind Harmer
0.256
970601AG2-382 GEN
Solar/Wind Harmer
9.549
316311AC2-079 GEN
Solar/Wind Harmer
7.334
315833AF1-017_GEN
Solar/Wind Harmer
0.001
3151031BRUNSWICKG2
50/50
4.54
970413AG2-270 GEN
50/50
25.77
3151101ELIZAR3
50/50
26.77
970917AG2-570 GEN
Solar/Wind Harmer
29.34
315773AC2-141 GEN
Solar/Wind Harmer
10.33
944581AF1-123 GEN
Solar/Wind Harmer
62.596
944601AF1-125 GEN
Solar/Wind Harmer
61.631
316478AD1-087 GEN
Solar/Wind Harmer
0.962
316486AD2-202 GEN
Solar/Wind Harmer
0.283
3146456SLIGO L269
Solar/Wind Harmer
0.272
971153AH1-033 GEN
Solar/Wind Harmer
3.148
3144873MCLAUGH
Solar/Wind Harmer
0.007
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.268
3146626S HERTFORD
Solar/Wind Harmer
0.267
316365GEN2_N
Solar/Wind Harmer
0.594
3146376EDENTON
Solar/Wind Harmer
0.263
3144536CHRHLND
Solar/Wind Harmer
0.039
3145273HOLLAND
Solar/Wind Harmer
0.197
315614AA2-178 GEN
Solar/Wind Harmer
1.489
971157AH1-035 GEN
Solar/Wind Harmer
3.091
315737AD1-076 GEN
Solar/Wind Harmer
3.308
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3146206CASHIE
Solar/Wind Harmer
0.256
3145893MURPHYS
Solar/Wind Harmer
0.427
3145893MURPHYS
Solar/Wind Harmer
0.255
957521AF2-046 GEN
Solar/Wind Harmer
18.955
961681AG1-008 GEN
Solar/Wind Harmer
18.955
313506AB2-031 GEN
Solar/Wind Harmer
0.786
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3146173TUNIS
Solar/Wind Harmer
0.254
3156021HOLLOMANSOL
Solar/Wind Harmer
1.153
316463AE2-346 GEN
Solar/Wind Harmer
0.218
970533AG2-339 GEN
50/50
32.288
970531AG2-338 GEN
50/50
12.915
315242AE2-183_GT2
50/50
5.789
315241AE2-183_GT1
50/50
5.753
972185AH1-677 GEN
50/50
20.868
3151041BRUNSWICKG3
50/50
4.54
972187AH1-678 GEN
50/50
10.419
970933AG2-581 GEN
Solar/Wind Harmer
26.407
970099AG2-077 GEN
Solar/Wind Harmer
31.122
3144356SAPONY
Solar/Wind Harmer
2.393
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.094
3145506HICKORY
Solar/Wind Harmer
0.657
3145506HICKORY
Solar/Wind Harmer
0.164
316339AD2-160 GEN
Solar/Wind Harmer
0.443
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.152
3142956BIRDNECK
Solar/Wind Harmer
0
3137176SLIGO L2192
Solar/Wind Harmer
1.084
3146456SLIGO L269
Solar/Wind Harmer
4.819
316316AC1-027 C
Solar/Wind Harmer
0.261
3130086AYDLETT
Solar/Wind Harmer
1.088
316036AC1-147 C
Solar/Wind Harmer
0.05
3150991CHESPKB
Adder
2.836
3150991CHESPKB
Adder
2.768
3146386ELIZ CT
Solar/Wind Harmer
0.27
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.268
3146516WINFALL
Solar/Wind Harmer
0.268
3146516WINFALL
Solar/Wind Harmer
0.268
3146626S HERTFORD
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.267
3146376EDENTON
Solar/Wind Harmer
1.171
3146376EDENTON
Solar/Wind Harmer
1.171
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316065AD1-022 GEN
Solar/Wind Harmer
11.799
3145893MURPHYS
Solar/Wind Harmer
1.706
3145893MURPHYS
Solar/Wind Harmer
0.459
316181AB2-040 GEN
Solar/Wind Harmer
0.369
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.254
3146173TUNIS
Solar/Wind Harmer
0.254
316426AA2-053 GEN
Solar/Wind Harmer
0.849
3145796HORNRTN
Solar/Wind Harmer
0.754
3145593CAROLNA
Solar/Wind Harmer
0.251
3145593CAROLNA
Solar/Wind Harmer
0.251
966811AG1-552 GEN
Solar/Wind Harmer
2.724
3145593CAROLNA
Solar/Wind Harmer
0.313
3145783HORNRTN
Solar/Wind Harmer
4.447
3145783HORNRTN
Solar/Wind Harmer
3.557
3145783HORNRTN
Solar/Wind Harmer
1.112
3145783HORNRTN
Solar/Wind Harmer
0.445
316274AC1-208 GEN
Solar/Wind Harmer
1.268
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.486
3145933PARMELE
Solar/Wind Harmer
0.243
970657AG2-426 GEN
Solar/Wind Harmer
8.443
970657AG2-426 GEN
Solar/Wind Harmer
1.77
939181AE1-148 GEN
Solar/Wind Harmer
11.415
3145493TOT1
Solar/Wind Harmer
0.548
3145453TOT5
Solar/Wind Harmer
0.329
3145603CNETO
Solar/Wind Harmer
0.219
961601AG1-000A GEN
Solar/Wind Harmer
4.164
316263AC1-034 GEN
Solar/Wind Harmer
8.897
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
10.79
964791AG1-342 GEN
Solar/Wind Harmer
4.311
3146843MT LREL
Solar/Wind Harmer
0.224
3146843MT LREL
Solar/Wind Harmer
0.224
971741AH1-377 GEN
Solar/Wind Harmer
21.422
316222AC1-221 GEN
Solar/Wind Harmer
0.867
970323AG2-213 GEN
Solar/Wind Harmer
8.785
971775AH1-396 GEN
Solar/Wind Harmer
0.329
316034AC1-036 C
Solar/Wind Harmer
0.015
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.225
970301AG2-198 GEN
Solar/Wind Harmer
8.511
958211AF2-115 GEN
Solar/Wind Harmer
2.259
963191AG1-168 GEN
Solar/Wind Harmer
0.753
3144293JTRSVLE
Adder
0.599
3144293JTRSVLE
Adder
0.505
3147133PAMPLIN
Solar/Wind Harmer
0.182
3147133PAMPLIN
Solar/Wind Harmer
0.146
316349AD2-085 GEN
Solar/Wind Harmer
0.175
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3145893MURPHYS
Solar/Wind Harmer
0.688
3145893MURPHYS
Solar/Wind Harmer
0.255
315652AC1-086 GEN
Solar/Wind Harmer
27.966
3145513AHOSKIE
Solar/Wind Harmer
0.53
3145513AHOSKIE
Solar/Wind Harmer
0.253
3146043SEABORD
Solar/Wind Harmer
0.253
315607AA1-063A GEN
Solar/Wind Harmer
0.517
3145683EARLEYS
Solar/Wind Harmer
0.506
3145683EARLEYS
Solar/Wind Harmer
0.253
3145683EARLEYS
Solar/Wind Harmer
0.253
3137643SOCKMAN
Solar/Wind Harmer
1.009
3145796HORNRTN
Solar/Wind Harmer
0.804
3145796HORNRTN
Solar/Wind Harmer
0.101
3146033SCOT NK
Solar/Wind Harmer
0.989
970831AG2-522 GEN
Solar/Wind Harmer
10.446
3143316POE
Solar/Wind Harmer
0.965
971445AH1-216 GEN
Solar/Wind Harmer
17.029
316005AA1-067
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.955
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
970181AG2-120 GEN
Solar/Wind Harmer
2.987
957861AF2-080 GEN
Solar/Wind Harmer
10.262
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
17.569
3151201GRAVEL4
Adder
16.47
3151191GRAVEL3
Adder
16.261
3151211GRAVEL5
Adder
16.261
316118AC1-105 GEN
Solar/Wind Harmer
0.578
3147173SINAI
Solar/Wind Harmer
0.223
3147243WELCO
Solar/Wind Harmer
0.14
971443AH1-215 GEN
Solar/Wind Harmer
3.472
3144303KENBRDG
Solar/Wind Harmer
0.165
316369SG1_INVT
Solar/Wind Harmer
0.007
970683AG2-441 GEN
Solar/Wind Harmer
13.122
970681AG2-440 GEN
Solar/Wind Harmer
10.498
970865AG2-541 GEN
Solar/Wind Harmer
6.671
946301AF1-294 GEN
Solar/Wind Harmer
3.715
961791AG1-021 GEN
Solar/Wind Harmer
1.807
3138283WHITEMARSH
Solar/Wind Harmer
0.044
316132AB2-190 GEN1
Solar/Wind Harmer
0.989
315657AE1-056 GEN
Solar/Wind Harmer
6.288
316123AC1-075 GEN
Solar/Wind Harmer
0.235
970165AG2-112 GEN
Solar/Wind Harmer
1.394
970163AG2-111 GEN
Solar/Wind Harmer
1.33
3141873WAN 176
Solar/Wind Harmer
0.031
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316140AB2-099
Solar/Wind Harmer
0.091
962331AG1-082 GEN
Solar/Wind Harmer
2.704
3146263WOODLND
Solar/Wind Harmer
0.252
3145796HORNRTN
Solar/Wind Harmer
1.005
3145796HORNRTN
Solar/Wind Harmer
0.251
316317KELFORD C
Solar/Wind Harmer
0.024
3145823KELFORD
Solar/Wind Harmer
0.25
3145963POPLR C
Solar/Wind Harmer
0.249
3147043LAWRENC
Solar/Wind Harmer
0.149
316210AC1-098 GEN
Solar/Wind Harmer
2.273
970661AG2-428 GEN
Solar/Wind Harmer
5.16
3145336SMITFLD
Solar/Wind Harmer
0.097
3145933PARMELE
Solar/Wind Harmer
0.243
966801AG1-551 GEN
Solar/Wind Harmer
2.83
315724AD1-057 GEN
Solar/Wind Harmer
0.908
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
316327AA2-057 GEN
Solar/Wind Harmer
0.362
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.515
3146233WITAKRS
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.161
3138543CONSLDL
Solar/Wind Harmer
0.156
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
961601AG1-000A GEN
Solar/Wind Harmer
16.657
3145543BTLEBRO
Solar/Wind Harmer
0.234
3145543BTLEBRO
Solar/Wind Harmer
0.234
971623AH1-311 GEN
Solar/Wind Harmer
0.468
315813AE1-149 C
Solar/Wind Harmer
12.227
3151221GRAVEL6
Adder
16.451
3151171GRAVELC
Adder
3.165
316131AB2-060 GEN
Solar/Wind Harmer
0.707
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.527
3144216WINCHST
Adder
0.83
964241AG1-285 GEN
Solar/Wind Harmer
14.603
3150921YORKTN3
Adder
5.498
961611AG1-000B GEN
Solar/Wind Harmer
5.762
315785AD2-033 C
Solar/Wind Harmer
1.703
316283AC2-100 C
Solar/Wind Harmer
0.406
970257AG2-171 GEN
Solar/Wind Harmer
6.589
959311AF2-222 GEN
Solar/Wind Harmer
18.071
971683AH1-343 GEN
Solar/Wind Harmer
7.451
315839AE2-212 C
Solar/Wind Harmer
0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.128
315778AD1-151 GEN
Solar/Wind Harmer
15.484
316382AG1-145 C
Solar/Wind Harmer
0.002
965281AG1-393 GEN
Solar/Wind Harmer
2.04
963181AG1-167 GEN
Solar/Wind Harmer
0.753
3144293JTRSVLE
Adder
0.599
970129AG2-093 GEN
Solar/Wind Harmer
11.049
3147133PAMPLIN
Solar/Wind Harmer
0.572
971193AH1-056 GEN
Solar/Wind Harmer
11.101
970133AG2-095 GEN
Solar/Wind Harmer
1.61
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.114
3141873WAN 176
Solar/Wind Harmer
2.731
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
0.764
3141766HARMONY
Solar/Wind Harmer
1.984
3146926FARMVIL
Solar/Wind Harmer
0.088
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
962971AG1-146 GEN
Solar/Wind Harmer
2.159
3142946ENON
Solar/Wind Harmer
0.044
970009AG2-005 GEN
Solar/Wind Harmer
0.976
316404AE1-155 C
Solar/Wind Harmer
0.028
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
316044AC1-158 PL1
Solar/Wind Helper
1.631
316450AC1-158 RIC
Solar/Wind Helper
0.435
3147666LOUISA
Solar/Wind Helper
0.576
316170AC1-121 GEN2
Solar/Wind Helper
0.345
315243AE2-183_GT3
50/50
5.789
3151051BRUNSWICKS1
50/50
9.423
3151021BRUNSWICKG1
50/50
4.54
971451AH1-221 GEN
50/50
13.79
3151531CLOVER1
50/50
5.905
940641AE2-051 GEN
Solar/Wind Harmer
28.987
939411AE1-173 GEN
Solar/Wind Harmer
145.254
970919AG2-571 GEN
Solar/Wind Harmer
11.736
970087AG2-069 GEN
Solar/Wind Harmer
26.275
957481AF2-042 GEN
Solar/Wind Harmer
77.806
316294AC1-161 GEN
Solar/Wind Harmer
4.901
944591AF1-124 GEN
Solar/Wind Harmer
62.818
316388AE2-253 GEN
Solar/Wind Harmer
0.855
3146456SLIGO L269
Solar/Wind Harmer
0.272
315693AD1-088 GEN
Solar/Wind Harmer
13.02
316375AC2-012 GEN
Solar/Wind Harmer
0.007
3150981CHESPKA
Adder
3.38
316246AF1-032 C
Solar/Wind Harmer
0.122
3146516WINFALL
Solar/Wind Harmer
0.867
3146516WINFALL
Solar/Wind Harmer
0.268
962491AG1-098 GEN
Solar/Wind Harmer
15.268
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
316093AE2-104_GEN
Solar/Wind Harmer
4.461
316023GEN1_S
Solar/Wind Harmer
0.594
3130156CHOWAN
Solar/Wind Harmer
0.263
3145663CRESWEL
Solar/Wind Harmer
0.728
971163AH1-040 GEN
Solar/Wind Harmer
20.811
316072AD1-144
Solar/Wind Harmer
0.094
315687AD1-152 GEN
Solar/Wind Harmer
0.008
960081AF2-299 GEN
Solar/Wind Harmer
2.469
3146206CASHIE
Solar/Wind Harmer
0.256
971547AH1-271 GEN
Solar/Wind Harmer
5.457
3145893MURPHYS
Solar/Wind Harmer
1.02
3145893MURPHYS
Solar/Wind Harmer
1.134
316011AB1-132 GEN
Solar/Wind Harmer
4.622
962571AG1-106 GEN
Solar/Wind Harmer
3.617
3146173TUNIS
Solar/Wind Harmer
0.254
3145683EARLEYS
Solar/Wind Harmer
0.253
3146263WOODLND
Solar/Wind Harmer
0.252
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.829
3145796HORNRTN
Solar/Wind Harmer
0.251
971795AH1-408 GEN
Solar/Wind Harmer
16.715
3145823KELFORD
Solar/Wind Harmer
0.25
3145783HORNRTN
Solar/Wind Harmer
0.25
3145963POPLR C
Solar/Wind Harmer
0.249
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3147043LAWRENC
Adder
2.242
316212AC1-099_GEN
Solar/Wind Harmer
1.268
316129AC1-054 GEN
Solar/Wind Harmer
0.918
970661AG2-428 GEN
Solar/Wind Harmer
24.263
970189AG2-124 GEN
Solar/Wind Harmer
4.431
316059AD1-063 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.147
316314AB2-024 C
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.044
3143873LANEXA
Solar/Wind Harmer
0.086
3141783LANCAST
Solar/Wind Harmer
0.085
3141783LANCAST
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
971167AH1-042 GEN
Solar/Wind Harmer
12.277
315976AC1-164 GENA
Solar/Wind Harmer
14.222
316169AC1-164_GENC
Solar/Wind Harmer
12.287
315975AC1-164 GENB
Solar/Wind Harmer
0.421
962981AG1-147 GEN
Solar/Wind Harmer
5.038
970327AG2-215 GEN
Solar/Wind Harmer
4.29
316164AC1-076 GEN
Solar/Wind Helper
1.17
316240AF1-291 C
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
78.098
942751AE2-291 GEN
Solar/Wind Harmer
8.652
3142946ENON
Solar/Wind Harmer
0.013
270013AE1-250 PV
Solar/Wind Harmer
0.004
958261AF2-120 GEN
Solar/Wind Harmer
4.097
316075AC2-137 C
Solar/Wind Harmer
0.033
316447AC1-158 HLD
Solar/Wind Helper
3.59
315651AD1-115 GEN
Solar/Wind Helper
0.751
971065AG2-659 GEN
Solar/Wind Harmer
10.39
3145336SMITFLD
Solar/Wind Harmer
0.973
3146293MARTNCO
Solar/Wind Harmer
0.225
315722AD1-056 GEN
Solar/Wind Harmer
1.532
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
316381AD1-082 GEN
Solar/Wind Harmer
0.249
316494AC1-189 GEN
Solar/Wind Harmer
0.804
970659AG2-427 GEN
Solar/Wind Harmer
11.496
3146233WITAKRS
Solar/Wind Harmer
0.942
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.05
316359AB2-059 GEN
Solar/Wind Harmer
0.841
316049AB1-081 GEN
Solar/Wind Harmer
1.34
3145543BTLEBRO
Solar/Wind Harmer
0.234
3145543BTLEBRO
Solar/Wind Harmer
0.187
3142053HEARTS
Solar/Wind Harmer
0.412
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3151171GRAVELC
Adder
2.407
970401AG2-262 GEN
Solar/Wind Harmer
1.317
3138126ROCKLANDING
Solar/Wind Harmer
0.101
961611AG1-000B GEN
Solar/Wind Harmer
11.332
316003AC1-222 GEN
Solar/Wind Harmer
0.006
971647AH1-324 GEN
Solar/Wind Harmer
8.873
971317AH1-138 GEN
Solar/Wind Harmer
1.539
970685AG2-442 GEN
Solar/Wind Harmer
14.697
971069AG2-661 GEN
Solar/Wind Harmer
3.441
316159AE1-175 C
Solar/Wind Harmer
0.165
963171AG1-166 GEN
Solar/Wind Harmer
1.004
971563AH1-280 GEN
Solar/Wind Harmer
2.008
3144293JTRSVLE
Adder
0.599
316458AB2-190 GEN2
Solar/Wind Harmer
0.989
315671AE2-027_GEN
Solar/Wind Harmer
11.755
970129AG2-093 GEN
Solar/Wind Harmer
5.199
971777AH1-397 GEN
Solar/Wind Harmer
0.395
3141843SHACKLE
Adder
0.764
3141766HARMONY
Solar/Wind Harmer
0.03
3146926FARMVIL
Solar/Wind Harmer
0.088
3138133OCRAN
Solar/Wind Harmer
0.087
3142433PROV 92
Solar/Wind Harmer
0.557
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
970223AG2-152 GEN
Solar/Wind Harmer
9.565
944631AF1-128 GEN
Adder
62.411
270016AE1-250 BESS
Solar/Wind Harmer
0.004
962861AG1-135 GEN
Solar/Wind Harmer
4.023
3147123OTTER R
Solar/Wind Harmer
0.07
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3141726DUNNSVL
Solar/Wind Harmer
0.457
316045AC1-158 PL2
Solar/Wind Helper
5.221
3147666LOUISA
Solar/Wind Helper
1.002
316192AB2-158 GEN
Solar/Wind Helper
1.658
316254AC1-120 GEN1
Solar/Wind Helper
1.035
CPLELTFEXP_CPLE->PJM
CLTF
15.998
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.498
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.7
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.348
MECLTFEXP_MEC->PJM
CLTF
5.484
SIGELTFEXP_SIGE->PJM
CLTF
0.165
NYPJM->LTFIMP_NY
CLTF
2.873
LGEELTFEXP_LGEE->PJM
CLTF
2
WECLTFEXP_WEC->PJM
CLTF
1.023
LAGNLTFEXP_LAGN->PJM
CLTF
11.265
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.702
TVALTFEXP_TVA->PJM
CLTF
5.645

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 56272_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56272_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.96 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4114.65
MW Contribution:1.68
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.755
3151051BRUNSWICKS1
50/50
9.355
3151021BRUNSWICKG1
50/50
4.507
971451AH1-221 GEN
50/50
13.69
3151531CLOVER1
50/50
5.718
3151601KERR 3
50/50
0.458
3151581KERR 1
50/50
0.163
3147043LAWRENC
50/50
2.116
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.266
970919AG2-571 GEN
Solar/Wind Harmer
11.601
970087AG2-069 GEN
Solar/Wind Harmer
34.181
939411AE1-173 GEN
Solar/Wind Harmer
170.129
957481AF2-042 GEN
Solar/Wind Harmer
99.882
315693AD1-088 GEN
Solar/Wind Harmer
14.731
962491AG1-098 GEN
Solar/Wind Harmer
19.405
315687AD1-152 GEN
Solar/Wind Harmer
3.35
316023GEN1_S
Solar/Wind Harmer
1.761
960081AF2-299 GEN
Solar/Wind Harmer
2.853
971795AH1-408 GEN
Solar/Wind Harmer
18.718
971065AG2-659 GEN
Solar/Wind Harmer
12.309
316129AC1-054 GEN
Solar/Wind Harmer
2.154
316011AB1-132 GEN
Solar/Wind Harmer
5.114
962571AG1-106 GEN
Solar/Wind Harmer
3.514
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
970401AG2-262 GEN
Solar/Wind Harmer
1.534
316237AB2-079_GEN
Solar/Wind Harmer
0.708
315722AD1-056 GEN
Solar/Wind Harmer
2.456
316212AC1-099_GEN
Solar/Wind Harmer
2.016
3146263WOODLND
Solar/Wind Harmer
-0.023
3146233WITAKRS
Solar/Wind Harmer
-0.091
316359AB2-059 GEN
Solar/Wind Harmer
3.083
316049AB1-081 GEN
Solar/Wind Harmer
2.467
3142053HEARTS
Solar/Wind Harmer
0.269
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.023
961671AG1-007 GEN
Solar/Wind Harmer
0.286
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.672
3145893MURPHYS
Solar/Wind Harmer
-0.09
3145893MURPHYS
Solar/Wind Harmer
0.671
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316494AC1-189 GEN
Solar/Wind Harmer
2.416
316003AC1-222 GEN
Solar/Wind Harmer
2.177
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3146293MARTNCO
Solar/Wind Harmer
0.137
316174AB2-169 GEN
Solar/Wind Harmer
3.387
3146206CASHIE
Solar/Wind Harmer
-0.022
971547AH1-271 GEN
Solar/Wind Harmer
5.488
3145963POPLR C
Solar/Wind Harmer
-0.022
3145663CRESWEL
Solar/Wind Harmer
-0.06
971163AH1-040 GEN
Solar/Wind Harmer
20.04
3130156CHOWAN
Solar/Wind Harmer
-0.021
315800Z1-036_GEN1
Solar/Wind Harmer
5.153
3146516WINFALL
Solar/Wind Harmer
-0.066
3146516WINFALL
Solar/Wind Harmer
-0.021
316093AE2-104_GEN
Solar/Wind Harmer
5.989
316246AF1-032 C
Solar/Wind Harmer
0.415
970685AG2-442 GEN
Solar/Wind Harmer
17.619
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316388AE2-253 GEN
Solar/Wind Harmer
1.348
970661AG2-428 GEN
Solar/Wind Harmer
21.192
944591AF1-124 GEN
Solar/Wind Harmer
90.948
316381AD1-082 GEN
Solar/Wind Harmer
1.816
970659AG2-427 GEN
Solar/Wind Harmer
10.495
316375AC2-012 GEN
Solar/Wind Harmer
6.72
3150981CHESPKA
Adder
2.158
963171AG1-166 GEN
Solar/Wind Harmer
2.398
971563AH1-280 GEN
Solar/Wind Harmer
2.398
3144293JTRSVLE
Adder
0.543
316072AD1-144
Solar/Wind Harmer
0.387
315244AE2-183_ST
50/50
9.95
963041AG1-153 GEN
50/50
9.127
3151541CLOVER2
50/50
5.691
315779AE2-040
50/50
3.626
3151611KERR 4
50/50
0.458
3151621KERR 5
50/50
0.458
3151631KERR 6
50/50
0.458
3151641KERR 7
50/50
0.458
3151281ROARAP4
50/50
0.259
3151281ROARAP4
50/50
0.243
941031AE2-094 GEN
Solar/Wind Harmer
76.337
944011AF1-069 GEN
Solar/Wind Harmer
23.919
970673AG2-436 GEN
Solar/Wind Harmer
83.349
970673AG2-436 GEN
Solar/Wind Harmer
42.202
971967AH1-528 GEN
Solar/Wind Harmer
72.452
970085AG2-068 GEN
Solar/Wind Harmer
22.787
970581AG2-369 GEN
Solar/Wind Harmer
19.597
316315AB2-025 C
Solar/Wind Harmer
0.787
315814AE2-033 C
Solar/Wind Harmer
27.034
946281AF1-292 GEN
Solar/Wind Harmer
0.568
316087AB2-174 GEN
Solar/Wind Harmer
3.556
970831AG2-522 GEN
Solar/Wind Harmer
12.26
315652AC1-086 GEN
Solar/Wind Harmer
27.499
3137643SOCKMAN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.01
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
316118AC1-105 GEN
Solar/Wind Harmer
1.62
316239AB2-077_GEN
Solar/Wind Harmer
0.708
316238AB2-078_GEN
Solar/Wind Harmer
0.708
315607AA1-063A GEN
Solar/Wind Harmer
2.372
3146043SEABORD
Solar/Wind Harmer
-0.023
316319Z2-044 C
Solar/Wind Harmer
1.269
3146033SCOT NK
Solar/Wind Harmer
-0.091
3143316POE
Solar/Wind Harmer
-0.09
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
965291AG1-394 GEN
Solar/Wind Harmer
2.008
316318V4-068
Solar/Wind Harmer
0.563
3145893MURPHYS
Solar/Wind Harmer
-0.061
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.197
961941AG1-037 GEN
Solar/Wind Harmer
0.17
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316420AA1-050 GEN
Solar/Wind Harmer
2.577
957861AF2-080 GEN
Solar/Wind Harmer
9.823
316005AA1-067
Solar/Wind Harmer
0.45
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.918
3146206CASHIE
Solar/Wind Harmer
-0.022
970601AG2-382 GEN
Solar/Wind Harmer
9.603
315732AD1-074 GEN1
Solar/Wind Harmer
4.385
315733AD1-074 GEN2
Solar/Wind Harmer
4.385
315735AD1-075 GEN1
Solar/Wind Harmer
2.193
3130546PLYMOUTH
Solar/Wind Harmer
-0.022
315816AE2-034 GEN
Solar/Wind Harmer
1.73
971443AH1-215 GEN
Solar/Wind Harmer
4.181
3144303KENBRDG
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.021
3130156CHOWAN
Solar/Wind Harmer
-0.021
315611Z1-036_GEN2
Solar/Wind Harmer
5.153
315835AF2-110_GEN
Solar/Wind Harmer
2.575
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.021
316305AF2-043 C
Solar/Wind Harmer
0.619
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
316321Z2-027
Solar/Wind Harmer
0.551
3146396TANGLEW
Solar/Wind Harmer
0.375
313526AB2-022
Solar/Wind Harmer
0.548
316311AC2-079 GEN
Solar/Wind Harmer
10.237
315833AF1-017_GEN
Solar/Wind Harmer
3.854
316349AD2-085 GEN
Solar/Wind Harmer
1.805
970683AG2-441 GEN
Solar/Wind Harmer
15.731
970681AG2-440 GEN
Solar/Wind Harmer
12.585
3146406KITTY HAWK
Solar/Wind Harmer
0.017
319010AE1-072 C
Solar/Wind Harmer
4.06
970865AG2-541 GEN
Solar/Wind Harmer
8.137
957871AF2-081 GEN
Solar/Wind Harmer
10.005
3151081ELIZAR1
Adder
15.891
3151091ELIZAR2
Adder
15.615
3152611GOSPORTB
Adder
2.203
3152621GOSPORTC
Adder
1.869
3152601GOSPORTA
Adder
1.724
946301AF1-294 GEN
Solar/Wind Harmer
4.916
961791AG1-021 GEN
Solar/Wind Harmer
2.398
270455AD2-022 GEN
Solar/Wind Harmer
3.325
270457AD2-023 GEN
Solar/Wind Harmer
1.686
3151031BRUNSWICKG2
50/50
4.507
970413AG2-270 GEN
50/50
24.952
3151591KERR 2
50/50
0.458
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.26
970917AG2-570 GEN
Solar/Wind Harmer
91.647
316478AD1-087 GEN
Solar/Wind Harmer
2.597
316486AD2-202 GEN
Solar/Wind Harmer
0.761
316365GEN2_N
Solar/Wind Harmer
1.761
966621AG1-532 GEN
Solar/Wind Harmer
0.515
3147043LAWRENC
Solar/Wind Harmer
-0.015
313506AB2-031 GEN
Solar/Wind Harmer
1.989
3145796HORNRTN
Solar/Wind Harmer
-0.096
3145796HORNRTN
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
316248AF1-058 C
Solar/Wind Harmer
0.711
960061AF2-297 GEN
Solar/Wind Harmer
11.79
315724AD1-057 GEN
Solar/Wind Harmer
1.351
316131AB2-060 GEN
Solar/Wind Harmer
2.509
316210AC1-098 GEN
Solar/Wind Harmer
3.629
316327AA2-057 GEN
Solar/Wind Harmer
2.332
3146263WOODLND
Solar/Wind Harmer
-0.023
3146233WITAKRS
Solar/Wind Harmer
0.481
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
961601AG1-000A GEN
Solar/Wind Harmer
9.103
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.074
3145823KELFORD
Solar/Wind Harmer
-0.023
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
0.158
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
17.808
961681AG1-008 GEN
Solar/Wind Harmer
17.808
964241AG1-285 GEN
Solar/Wind Harmer
17.664
3146173TUNIS
Solar/Wind Harmer
-0.023
316463AE2-346 GEN
Solar/Wind Harmer
0.366
316140AB2-099
Solar/Wind Harmer
0.152
962331AG1-082 GEN
Solar/Wind Harmer
2.826
3156081AA2-088 GEN
Solar/Wind Harmer
7.311
3156021HOLLOMANSOL
Solar/Wind Harmer
3.009
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.766
3146206CASHIE
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
316283AC2-100 C
Solar/Wind Harmer
2.053
315737AD1-076 GEN
Solar/Wind Harmer
4.121
971157AH1-035 GEN
Solar/Wind Harmer
2.704
315785AD2-033 C
Solar/Wind Harmer
4.883
315614AA2-178 GEN
Solar/Wind Harmer
2.306
3145273HOLLAND
Solar/Wind Harmer
-0.016
971683AH1-343 GEN
Solar/Wind Harmer
9.136
970257AG2-171 GEN
Solar/Wind Harmer
7.93
3146376EDENTON
Solar/Wind Harmer
-0.021
970909AG2-566 GEN
Solar/Wind Harmer
1.981
959311AF2-222 GEN
Solar/Wind Harmer
21.769
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
316435W1029_GEN3
Solar/Wind Harmer
3.733
316320Y1-086
Solar/Wind Harmer
1.19
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.444
970661AG2-428 GEN
Solar/Wind Harmer
3.756
944581AF1-123 GEN
Solar/Wind Harmer
90.622
944601AF1-125 GEN
Solar/Wind Harmer
89.208
316083AB2-161 GEN
Solar/Wind Harmer
3.214
970659AG2-427 GEN
Solar/Wind Harmer
1.86
315813AE1-149 C
Solar/Wind Harmer
12.185
3151101ELIZAR3
Adder
16.095
3144873MCLAUGH
Solar/Wind Harmer
0
963181AG1-167 GEN
Solar/Wind Harmer
1.798
3144293JTRSVLE
Adder
0.543
3144536CHRHLND
Solar/Wind Harmer
-0.003
970533AG2-339 GEN
50/50
32.21
970531AG2-338 GEN
50/50
12.884
315242AE2-183_GT2
50/50
5.755
315241AE2-183_GT1
50/50
5.72
972185AH1-677 GEN
50/50
20.748
3151041BRUNSWICKG3
50/50
4.507
972187AH1-678 GEN
50/50
10.344
3151361ROSEMG1
50/50
0.776
3151371ROSEMS1
50/50
0.481
3151381ROSEMG2
50/50
0.363
970535AG2-341 GEN
50/50
3.826
3152661PLYWOOD A
50/50
0.474
970933AG2-581 GEN
Solar/Wind Harmer
34.364
970099AG2-077 GEN
Solar/Wind Harmer
39.953
3144356SAPONY
Solar/Wind Harmer
1.018
316181AB2-040 GEN
Solar/Wind Harmer
3.451
939181AE1-148 GEN
Solar/Wind Harmer
13.835
3145796HORNRTN
Solar/Wind Harmer
-0.072
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.705
3145593CAROLNA
Solar/Wind Harmer
0.2
3145783HORNRTN
Solar/Wind Harmer
2.839
3145783HORNRTN
Solar/Wind Harmer
2.272
3145783HORNRTN
Solar/Wind Harmer
0.71
3145783HORNRTN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
2.403
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
964791AG1-342 GEN
Solar/Wind Harmer
5.022
962561AG1-105 GEN
Solar/Wind Harmer
13.216
313527AB2-043 GEN
Solar/Wind Harmer
3.804
316274AC1-208 GEN
Solar/Wind Harmer
2.516
961601AG1-000A GEN
Solar/Wind Harmer
8.989
316263AC1-034 GEN
Solar/Wind Harmer
10.719
971741AH1-377 GEN
Solar/Wind Harmer
26.554
3145493TOT1
Solar/Wind Harmer
0.35
3145453TOT5
Solar/Wind Harmer
0.21
3145603CNETO
Solar/Wind Harmer
0.14
3145893MURPHYS
Solar/Wind Harmer
0.631
3145893MURPHYS
Solar/Wind Harmer
-0.041
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
316222AC1-221 GEN
Solar/Wind Harmer
2.217
316065AD1-022 GEN
Solar/Wind Harmer
10.926
315742AE1-103 GEN
Solar/Wind Harmer
2.245
970323AG2-213 GEN
Solar/Wind Harmer
10.573
971775AH1-396 GEN
Solar/Wind Harmer
1.506
316034AC1-036 C
Solar/Wind Harmer
0.392
3146376EDENTON
Solar/Wind Harmer
0.624
3146376EDENTON
Solar/Wind Harmer
0.624
970301AG2-198 GEN
Solar/Wind Harmer
10.435
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
316431W1029_GEN1
Solar/Wind Harmer
3.733
316433W1029_GEN2
Solar/Wind Harmer
3.733
3146386ELIZ CT
Solar/Wind Harmer
-0.02
3130086AYDLETT
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.368
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
316018AA1-139 ULT2
Solar/Wind Harmer
1.714
316017AA1-139 ULT1
Solar/Wind Harmer
1.619
316339AD2-160 GEN
Solar/Wind Harmer
1.348
3145506HICKORY
Solar/Wind Harmer
-0.079
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.206
970657AG2-426 GEN
Solar/Wind Harmer
1.298
316185AD1-033 GEN
Solar/Wind Harmer
2.091
3142956BIRDNECK
Solar/Wind Harmer
1.055
316316AC1-027 C
Solar/Wind Harmer
0.603
316036AC1-147 C
Solar/Wind Harmer
0.524
3150991CHESPKB
Adder
1.81
3150991CHESPKB
Adder
1.767
958211AF2-115 GEN
Solar/Wind Harmer
2.997
963191AG1-168 GEN
Solar/Wind Harmer
1.798
3144293JTRSVLE
Adder
0.543
3144293JTRSVLE
Adder
0.458
3147133PAMPLIN
Solar/Wind Harmer
-0.058
971193AH1-056 GEN
Solar/Wind Harmer
11.575
3145336SMITFLD
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.509
3151221GRAVEL6
Adder
9.984
3151171GRAVELC
Adder
1.921
3144216WINCHST
Adder
0.443
3150921YORKTN3
Adder
2.878
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
315657AE1-056 GEN
Solar/Wind Harmer
6.945
316123AC1-075 GEN
Solar/Wind Harmer
1.908
970165AG2-112 GEN
Solar/Wind Harmer
1.68
970163AG2-111 GEN
Solar/Wind Harmer
1.602
972265AH1-717 GEN
Adder
10.663
3151201GRAVEL4
Adder
9.996
3151191GRAVEL3
Adder
9.869
3151211GRAVEL5
Adder
9.869
971445AH1-216 GEN
Solar/Wind Harmer
2.771
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.015
316236AE1-162_GEN
Solar/Wind Harmer
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.845
3145336SMITFLD
Solar/Wind Harmer
-0.067
3151171GRAVELC
Adder
1.461
3143226MDLTHAN
Solar/Wind Helper
0.294
316045AC1-158 PL2
Solar/Wind Helper
4.138
CPLELTFEXP_CPLE->PJM
CLTF
14.701
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.1
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.472
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.988
MECLTFEXP_MEC->PJM
CLTF
4.732
SIGELTFEXP_SIGE->PJM
CLTF
0.141
NYPJM->LTFIMP_NY
CLTF
2.22
LGEELTFEXP_LGEE->PJM
CLTF
1.693
WECLTFEXP_WEC->PJM
CLTF
0.873
LAGNLTFEXP_LAGN->PJM
CLTF
9.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.656
TVALTFEXP_TVA->PJM
CLTF
4.976

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.02 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4187.08
MW Contribution:1.34
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.909
3151051BRUNSWICKS1
50/50
9.612
3151021BRUNSWICKG1
50/50
4.631
971451AH1-221 GEN
50/50
14.067
3152331SURRY 2
50/50
12.237
3150981CHESPKA
50/50
3.828
940641AE2-051 GEN
Solar/Wind Harmer
30.053
939411AE1-173 GEN
Solar/Wind Harmer
151.675
970919AG2-571 GEN
Solar/Wind Harmer
11.95
970087AG2-069 GEN
Solar/Wind Harmer
26.75
316294AC1-161 GEN
Solar/Wind Harmer
5.441
944591AF1-124 GEN
Solar/Wind Harmer
67.777
957481AF2-042 GEN
Solar/Wind Harmer
78.492
316388AE2-253 GEN
Solar/Wind Harmer
0.915
3146456SLIGO L269
Solar/Wind Harmer
0.291
316375AC2-012 GEN
Solar/Wind Harmer
0.007
316246AF1-032 C
Solar/Wind Harmer
0.129
3146516WINFALL
Solar/Wind Harmer
0.918
3146516WINFALL
Solar/Wind Harmer
0.283
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
316093AE2-104_GEN
Solar/Wind Harmer
4.671
3130156CHOWAN
Solar/Wind Harmer
0.277
315693AD1-088 GEN
Solar/Wind Harmer
13.054
3145663CRESWEL
Solar/Wind Harmer
0.761
971163AH1-040 GEN
Solar/Wind Harmer
21.745
316072AD1-144
Solar/Wind Harmer
0.098
962491AG1-098 GEN
Solar/Wind Harmer
15.287
3146206CASHIE
Solar/Wind Harmer
0.264
971547AH1-271 GEN
Solar/Wind Harmer
5.647
316023GEN1_S
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
1.045
3145893MURPHYS
Solar/Wind Harmer
1.162
3146173TUNIS
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.259
315687AD1-152 GEN
Solar/Wind Harmer
0.008
3146263WOODLND
Solar/Wind Harmer
0.257
3145963POPLR C
Solar/Wind Harmer
0.257
960081AF2-299 GEN
Solar/Wind Harmer
2.46
3151031BRUNSWICKG2
50/50
4.631
3151101ELIZAR3
50/50
28.615
3151161SURRY 1
50/50
8.552
970917AG2-570 GEN
Solar/Wind Harmer
29.876
315773AC2-141 GEN
Solar/Wind Harmer
11.469
944581AF1-123 GEN
Solar/Wind Harmer
67.537
944601AF1-125 GEN
Solar/Wind Harmer
66.496
3146456SLIGO L269
Solar/Wind Harmer
0.291
971153AH1-033 GEN
Solar/Wind Harmer
3.364
3144873MCLAUGH
Solar/Wind Harmer
0.007
316320Y1-086
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.283
3146626S HERTFORD
Solar/Wind Harmer
0.282
3144536CHRHLND
Solar/Wind Harmer
0.041
316478AD1-087 GEN
Solar/Wind Harmer
0.967
316486AD2-202 GEN
Solar/Wind Harmer
0.284
3146376EDENTON
Solar/Wind Harmer
0.277
3145273HOLLAND
Solar/Wind Harmer
0.205
315614AA2-178 GEN
Solar/Wind Harmer
1.556
971157AH1-035 GEN
Solar/Wind Harmer
3.215
315737AD1-076 GEN
Solar/Wind Harmer
3.437
3146206CASHIE
Solar/Wind Harmer
0.264
316365GEN2_N
Solar/Wind Harmer
0.591
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3145893MURPHYS
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.261
3156021HOLLOMANSOL
Solar/Wind Harmer
1.186
957521AF2-046 GEN
Solar/Wind Harmer
19.425
961681AG1-008 GEN
Solar/Wind Harmer
19.425
3146173TUNIS
Solar/Wind Harmer
0.26
316463AE2-346 GEN
Solar/Wind Harmer
0.223
316140AB2-099
Solar/Wind Harmer
0.093
962331AG1-082 GEN
Solar/Wind Harmer
2.771
3146263WOODLND
Solar/Wind Harmer
0.257
3145963POPLR C
Solar/Wind Harmer
0.257
315244AE2-183_ST
50/50
10.216
963041AG1-153 GEN
50/50
9.378
3151081ELIZAR1
50/50
28.253
3151091ELIZAR2
50/50
27.762
941591AE2-156 GEN
50/50
25.74
3152611GOSPORTB
50/50
3.904
3152621GOSPORTC
50/50
3.313
3152601GOSPORTA
50/50
3.057
972263AH1-716 GEN
50/50
164.489
315779AE2-040
50/50
3.913
941031AE2-094 GEN
Solar/Wind Harmer
68.4
944011AF1-069 GEN
Solar/Wind Harmer
22.349
970673AG2-436 GEN
Solar/Wind Harmer
77.293
970673AG2-436 GEN
Solar/Wind Harmer
51.529
971967AH1-528 GEN
Solar/Wind Harmer
56.362
970085AG2-068 GEN
Solar/Wind Harmer
17.833
970581AG2-369 GEN
Solar/Wind Harmer
15.337
957871AF2-081 GEN
Solar/Wind Harmer
14.522
319010AE1-072 C
Solar/Wind Harmer
1.465
3146406KITTY HAWK
Solar/Wind Harmer
0.036
313526AB2-022
Solar/Wind Harmer
0.156
316321Z2-027
Solar/Wind Harmer
0.053
3146396TANGLEW
Solar/Wind Harmer
0.789
3145176PASQUOTANK
Solar/Wind Harmer
0.177
316305AF2-043 C
Solar/Wind Harmer
0.002
3146486SUNBURY
Solar/Wind Harmer
0.285
3146486SUNBURY
Solar/Wind Harmer
0.285
316315AB2-025 C
Solar/Wind Harmer
0.227
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315814AE2-033 C
Solar/Wind Harmer
22.11
315835AF2-110_GEN
Solar/Wind Harmer
1.906
3130156CHOWAN
Solar/Wind Harmer
0.277
3130156CHOWAN
Solar/Wind Harmer
0.277
315816AE2-034 GEN
Solar/Wind Harmer
1.167
3130546PLYMOUTH
Solar/Wind Harmer
0.268
315732AD1-074 GEN1
Solar/Wind Harmer
1.535
315733AD1-074 GEN2
Solar/Wind Harmer
1.535
315735AD1-075 GEN1
Solar/Wind Harmer
0.768
3146206CASHIE
Solar/Wind Harmer
0.264
970601AG2-382 GEN
Solar/Wind Harmer
9.883
965291AG1-394 GEN
Solar/Wind Harmer
1.166
3145893MURPHYS
Solar/Wind Harmer
0.705
3145893MURPHYS
Solar/Wind Harmer
0.261
3145513AHOSKIE
Solar/Wind Harmer
0.543
3145513AHOSKIE
Solar/Wind Harmer
0.26
316311AC2-079 GEN
Solar/Wind Harmer
7.457
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.178
3145683EARLEYS
Solar/Wind Harmer
0.518
3145683EARLEYS
Solar/Wind Harmer
0.259
3145683EARLEYS
Solar/Wind Harmer
0.259
3146043SEABORD
Solar/Wind Harmer
0.257
315607AA1-063A GEN
Solar/Wind Harmer
0.525
970533AG2-339 GEN
50/50
33.012
970531AG2-338 GEN
50/50
13.205
315242AE2-183_GT2
50/50
5.909
315241AE2-183_GT1
50/50
5.872
972185AH1-677 GEN
50/50
21.302
3151041BRUNSWICKG3
50/50
4.631
972187AH1-678 GEN
50/50
10.628
3150991CHESPKB
50/50
3.212
3150991CHESPKB
50/50
3.134
970933AG2-581 GEN
Solar/Wind Harmer
26.853
970099AG2-077 GEN
Solar/Wind Harmer
31.397
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.172
3145506HICKORY
Solar/Wind Harmer
0.703
3145506HICKORY
Solar/Wind Harmer
0.176
316339AD2-160 GEN
Solar/Wind Harmer
0.474
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.163
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.279
3137176SLIGO L2192
Solar/Wind Harmer
1.158
3146456SLIGO L269
Solar/Wind Harmer
5.15
3130086AYDLETT
Solar/Wind Harmer
1.162
316036AC1-147 C
Solar/Wind Harmer
0.054
3146386ELIZ CT
Solar/Wind Harmer
0.287
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.283
3146516WINFALL
Solar/Wind Harmer
0.283
3146516WINFALL
Solar/Wind Harmer
0.283
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
3144356SAPONY
Solar/Wind Harmer
2.345
3146376EDENTON
Solar/Wind Harmer
1.231
3146376EDENTON
Solar/Wind Harmer
1.231
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316065AD1-022 GEN
Solar/Wind Harmer
12.23
3145893MURPHYS
Solar/Wind Harmer
1.749
3145893MURPHYS
Solar/Wind Harmer
0.47
3146173TUNIS
Solar/Wind Harmer
0.26
3146173TUNIS
Solar/Wind Harmer
0.26
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
316181AB2-040 GEN
Solar/Wind Harmer
0.37
316426AA2-053 GEN
Solar/Wind Harmer
0.859
3145593CAROLNA
Solar/Wind Harmer
0.253
3145593CAROLNA
Solar/Wind Harmer
0.253
966811AG1-552 GEN
Solar/Wind Harmer
2.746
3145593CAROLNA
Solar/Wind Harmer
0.315
3145796HORNRTN
Solar/Wind Harmer
0.757
3145783HORNRTN
Solar/Wind Harmer
4.484
3145783HORNRTN
Solar/Wind Harmer
3.587
3145783HORNRTN
Solar/Wind Harmer
1.121
3145783HORNRTN
Solar/Wind Harmer
0.448
3145933PARMELE
Solar/Wind Harmer
0.497
3145933PARMELE
Solar/Wind Harmer
0.248
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316274AC1-208 GEN
Solar/Wind Harmer
1.28
3145493TOT1
Solar/Wind Harmer
0.553
3145453TOT5
Solar/Wind Harmer
0.332
3145603CNETO
Solar/Wind Harmer
0.221
939181AE1-148 GEN
Solar/Wind Harmer
11.37
961601AG1-000A GEN
Solar/Wind Harmer
4.187
316263AC1-034 GEN
Solar/Wind Harmer
8.947
970657AG2-426 GEN
Solar/Wind Harmer
8.169
970657AG2-426 GEN
Solar/Wind Harmer
1.713
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
10.674
964791AG1-342 GEN
Solar/Wind Harmer
4.265
3146843MT LREL
Solar/Wind Harmer
0.222
3146843MT LREL
Solar/Wind Harmer
0.222
971741AH1-377 GEN
Solar/Wind Harmer
20.961
316222AC1-221 GEN
Solar/Wind Harmer
0.858
970323AG2-213 GEN
Solar/Wind Harmer
8.579
971775AH1-396 GEN
Solar/Wind Harmer
0.322
316034AC1-036 C
Solar/Wind Harmer
0.015
970301AG2-198 GEN
Solar/Wind Harmer
8.245
958211AF2-115 GEN
Solar/Wind Harmer
2.178
963191AG1-168 GEN
Solar/Wind Harmer
0.726
3144293JTRSVLE
Adder
0.578
3144293JTRSVLE
Adder
0.487
316033AB2-134 GEN
Solar/Wind Harmer
0.011
316011AB1-132 GEN
Solar/Wind Harmer
4.645
962571AG1-106 GEN
Solar/Wind Harmer
3.635
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.255
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.833
3145796HORNRTN
Solar/Wind Harmer
0.252
3145783HORNRTN
Solar/Wind Harmer
0.252
971795AH1-408 GEN
Solar/Wind Harmer
16.631
3146293MARTNCO
Solar/Wind Harmer
0.23
3145336SMITFLD
Solar/Wind Harmer
0.992
316212AC1-099_GEN
Solar/Wind Harmer
1.284
3147043LAWRENC
Adder
2.229
315697AD1-025 GEN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.175
3147133PAMPLIN
Solar/Wind Harmer
0.14
315652AC1-086 GEN
Solar/Wind Harmer
28.1
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3137643SOCKMAN
Solar/Wind Harmer
1.014
3145796HORNRTN
Solar/Wind Harmer
0.808
3145796HORNRTN
Solar/Wind Harmer
0.101
3146033SCOT NK
Solar/Wind Harmer
1.005
971445AH1-216 GEN
Solar/Wind Harmer
17.313
970831AG2-522 GEN
Solar/Wind Harmer
10.467
316005AA1-067
Solar/Wind Harmer
0.262
3145746EVERETS
Solar/Wind Harmer
0.972
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
970181AG2-120 GEN
Solar/Wind Harmer
3.041
957861AF2-080 GEN
Solar/Wind Harmer
10.405
316420AA1-050 GEN
Solar/Wind Harmer
0.008
3145573BETHELC
Solar/Wind Harmer
0.239
3145573BETHELC
Solar/Wind Harmer
0.239
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
3143316POE
Solar/Wind Harmer
0.886
972265AH1-717 GEN
Adder
17.287
3151201GRAVEL4
Adder
16.205
3151191GRAVEL3
Adder
16
3151211GRAVEL5
Adder
16
316118AC1-105 GEN
Solar/Wind Harmer
0.572
3147173SINAI
Solar/Wind Harmer
0.221
3147243WELCO
Solar/Wind Harmer
0.138
971443AH1-215 GEN
Solar/Wind Harmer
3.393
3144303KENBRDG
Solar/Wind Harmer
0.161
970683AG2-441 GEN
Solar/Wind Harmer
12.733
970681AG2-440 GEN
Solar/Wind Harmer
10.187
970865AG2-541 GEN
Solar/Wind Harmer
6.495
946301AF1-294 GEN
Solar/Wind Harmer
3.582
961791AG1-021 GEN
Solar/Wind Harmer
1.742
316369SG1_INVT
Solar/Wind Harmer
0.007
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.255
313506AB2-031 GEN
Solar/Wind Harmer
0.787
3145796HORNRTN
Solar/Wind Harmer
1.01
3145796HORNRTN
Solar/Wind Harmer
0.252
3145933PARMELE
Solar/Wind Harmer
0.248
966801AG1-551 GEN
Solar/Wind Harmer
2.893
3145336SMITFLD
Solar/Wind Harmer
0.099
316210AC1-098 GEN
Solar/Wind Harmer
2.302
3147043LAWRENC
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
315724AD1-057 GEN
Solar/Wind Harmer
0.913
316327AA2-057 GEN
Solar/Wind Harmer
0.365
3146073TAR RVR
Solar/Wind Harmer
0.239
3146083TARBORO
Solar/Wind Harmer
0.239
3146233WITAKRS
Solar/Wind Harmer
1.197
3146233WITAKRS
Solar/Wind Harmer
0.162
970661AG2-428 GEN
Solar/Wind Harmer
5.046
3138543CONSLDL
Solar/Wind Harmer
0.157
961601AG1-000A GEN
Solar/Wind Harmer
16.749
3145543BTLEBRO
Solar/Wind Harmer
0.235
3145543BTLEBRO
Solar/Wind Harmer
0.235
971623AH1-311 GEN
Solar/Wind Harmer
0.471
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.402
3151221GRAVEL6
Adder
16.187
3151171GRAVELC
Adder
3.114
3144216WINCHST
Adder
0.839
316131AB2-060 GEN
Solar/Wind Harmer
0.698
3150921YORKTN3
Adder
5.575
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.432
964241AG1-285 GEN
Solar/Wind Harmer
14.377
315813AE1-149 C
Solar/Wind Harmer
11.28
961611AG1-000B GEN
Solar/Wind Harmer
5.505
316283AC2-100 C
Solar/Wind Harmer
0.403
315785AD2-033 C
Solar/Wind Harmer
1.667
970257AG2-171 GEN
Solar/Wind Harmer
6.434
971683AH1-343 GEN
Solar/Wind Harmer
7.298
959311AF2-222 GEN
Solar/Wind Harmer
17.616
970909AG2-566 GEN
Solar/Wind Harmer
2.061
963181AG1-167 GEN
Solar/Wind Harmer
0.726
3144293JTRSVLE
Adder
0.578
3147133PAMPLIN
Solar/Wind Harmer
0.549
316129AC1-054 GEN
Solar/Wind Harmer
0.919
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
971065AG2-659 GEN
Solar/Wind Harmer
10.397
315722AD1-056 GEN
Solar/Wind Harmer
1.539
316494AC1-189 GEN
Solar/Wind Harmer
0.815
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.239
3145493TOT1
Solar/Wind Harmer
1.061
3146233WITAKRS
Solar/Wind Harmer
0.949
970661AG2-428 GEN
Solar/Wind Harmer
23.724
3145543BTLEBRO
Solar/Wind Harmer
0.235
3145543BTLEBRO
Solar/Wind Harmer
0.188
316359AB2-059 GEN
Solar/Wind Harmer
0.846
316049AB1-081 GEN
Solar/Wind Harmer
1.347
3142053HEARTS
Solar/Wind Harmer
0.415
316381AD1-082 GEN
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
10.983
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3151171GRAVELC
Adder
2.368
3138126ROCKLANDING
Solar/Wind Harmer
0.102
970401AG2-262 GEN
Solar/Wind Harmer
1.303
316003AC1-222 GEN
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
10.827
971317AH1-138 GEN
Solar/Wind Harmer
1.51
971647AH1-324 GEN
Solar/Wind Harmer
8.259
970685AG2-442 GEN
Solar/Wind Harmer
14.261
963171AG1-166 GEN
Solar/Wind Harmer
0.968
971563AH1-280 GEN
Solar/Wind Harmer
1.936
3144293JTRSVLE
Adder
0.578
315657AE1-056 GEN
Solar/Wind Harmer
6.032
3138283WHITEMARSH
Solar/Wind Harmer
0.04
316123AC1-075 GEN
Solar/Wind Harmer
0.226
970165AG2-112 GEN
Solar/Wind Harmer
1.338
970163AG2-111 GEN
Solar/Wind Harmer
1.276
316132AB2-190 GEN1
Solar/Wind Harmer
0.837
971193AH1-056 GEN
Solar/Wind Harmer
10.649
316382AG1-145 C
Solar/Wind Harmer
0.001
315778AD1-151 GEN
Solar/Wind Harmer
13.656
315839AE2-212 C
Solar/Wind Harmer
0.001
965281AG1-393 GEN
Solar/Wind Harmer
1.676
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970129AG2-093 GEN
Solar/Wind Harmer
9.286
3146926FARMVIL
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
1.245
316156AD2-030 GEN
Solar/Wind Harmer
0.088
3141873WAN 176
Solar/Wind Harmer
2.112
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316044AC1-158 PL1
Solar/Wind Helper
1.37
316450AC1-158 RIC
Solar/Wind Helper
0.365
3147666LOUISA
Solar/Wind Helper
0.514
3141873WAN 176
Solar/Wind Harmer
0.024
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
942751AE2-291 GEN
Solar/Wind Harmer
8.208
316240AF1-291 C
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
58.874
270013AE1-250 PV
Solar/Wind Harmer
0.004
316447AC1-158 HLD
Solar/Wind Helper
3.015
316159AE1-175 C
Solar/Wind Harmer
0.148
971069AG2-661 GEN
Solar/Wind Harmer
3.035
316458AB2-190 GEN2
Solar/Wind Harmer
0.837
970129AG2-093 GEN
Solar/Wind Harmer
4.37
315671AE2-027_GEN
Solar/Wind Harmer
9.434
3146926FARMVIL
Solar/Wind Harmer
0.081
970223AG2-152 GEN
Solar/Wind Harmer
8.965
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3143226MDLTHAN
Solar/Wind Helper
0.285
316045AC1-158 PL2
Solar/Wind Helper
4.385
3147666LOUISA
Solar/Wind Helper
0.894
CPLELTFEXP_CPLE->PJM
CLTF
15.827
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.426
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.541
MECLTFEXP_MEC->PJM
CLTF
4.755
SIGELTFEXP_SIGE->PJM
CLTF
0.141
NYPJM->LTFIMP_NY
CLTF
2.482
LGEELTFEXP_LGEE->PJM
CLTF
1.68
WECLTFEXP_WEC->PJM
CLTF
0.862
LAGNLTFEXP_LAGN->PJM
CLTF
10.343
CBM South 2LTFEXP_CBM-S2->PJM
CBM
33.715
TVALTFEXP_TVA->PJM
CLTF
5.16

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.09 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3384.28
MW Contribution:1.17
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.174
3151051BRUNSWICKS1
50/50
8.414
3151021BRUNSWICKG1
50/50
4.054
971451AH1-221 GEN
50/50
12.314
3151531CLOVER1
50/50
5.17
940641AE2-051 GEN
Solar/Wind Harmer
25.663
939411AE1-173 GEN
Solar/Wind Harmer
126.366
970919AG2-571 GEN
Solar/Wind Harmer
10.453
970087AG2-069 GEN
Solar/Wind Harmer
23.397
957481AF2-042 GEN
Solar/Wind Harmer
68.436
315693AD1-088 GEN
Solar/Wind Harmer
11.355
962491AG1-098 GEN
Solar/Wind Harmer
13.293
316294AC1-161 GEN
Solar/Wind Harmer
3.96
944591AF1-124 GEN
Solar/Wind Harmer
50.934
315687AD1-152 GEN
Solar/Wind Harmer
0.007
316023GEN1_S
Solar/Wind Harmer
0.501
316388AE2-253 GEN
Solar/Wind Harmer
0.692
3146456SLIGO L269
Solar/Wind Harmer
0.22
316246AF1-032 C
Solar/Wind Harmer
0.098
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.721
3151031BRUNSWICKG2
50/50
4.054
970413AG2-270 GEN
50/50
22.561
3151101ELIZAR3
50/50
21.566
970917AG2-570 GEN
Solar/Wind Harmer
26.133
316478AD1-087 GEN
Solar/Wind Harmer
0.842
316486AD2-202 GEN
Solar/Wind Harmer
0.247
315773AC2-141 GEN
Solar/Wind Harmer
8.348
944581AF1-123 GEN
Solar/Wind Harmer
50.754
944601AF1-125 GEN
Solar/Wind Harmer
49.972
316365GEN2_N
Solar/Wind Harmer
0.501
3146456SLIGO L269
Solar/Wind Harmer
0.22
971153AH1-033 GEN
Solar/Wind Harmer
2.55
316320Y1-086
Solar/Wind Harmer
0.001
3144873MCLAUGH
Solar/Wind Harmer
0.005
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.217
3146626S HERTFORD
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.215
313506AB2-031 GEN
Solar/Wind Harmer
0.662
3145273HOLLAND
Solar/Wind Harmer
0.16
315614AA2-178 GEN
Solar/Wind Harmer
1.222
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
971157AH1-035 GEN
Solar/Wind Harmer
2.545
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315737AD1-076 GEN
Solar/Wind Harmer
2.725
3145796HORNRTN
Solar/Wind Harmer
0.846
3145796HORNRTN
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
0.354
3145893MURPHYS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
957521AF2-046 GEN
Solar/Wind Harmer
15.712
961681AG1-008 GEN
Solar/Wind Harmer
15.712
3146173TUNIS
Solar/Wind Harmer
0.211
3156021HOLLOMANSOL
Solar/Wind Harmer
0.955
316463AE2-346 GEN
Solar/Wind Harmer
0.181
316140AB2-099
Solar/Wind Harmer
0.075
3146263WOODLND
Solar/Wind Harmer
0.21
962331AG1-082 GEN
Solar/Wind Harmer
2.245
3144536CHRHLND
Solar/Wind Harmer
0.031
3147043LAWRENC
Solar/Wind Harmer
0.126
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.207
316210AC1-098 GEN
Solar/Wind Harmer
1.908
315724AD1-057 GEN
Solar/Wind Harmer
0.766
3145933PARMELE
Solar/Wind Harmer
0.203
966801AG1-551 GEN
Solar/Wind Harmer
2.363
316327AA2-057 GEN
Solar/Wind Harmer
0.305
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
3146233WITAKRS
Solar/Wind Harmer
1.004
3146233WITAKRS
Solar/Wind Harmer
0.136
3138543CONSLDL
Solar/Wind Harmer
0.132
3146073TAR RVR
Solar/Wind Harmer
0.199
3146083TARBORO
Solar/Wind Harmer
0.199
961601AG1-000A GEN
Solar/Wind Harmer
14.088
3145543BTLEBRO
Solar/Wind Harmer
0.198
3145543BTLEBRO
Solar/Wind Harmer
0.198
971623AH1-311 GEN
Solar/Wind Harmer
0.396
970661AG2-428 GEN
Solar/Wind Harmer
4.071
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.184
316131AB2-060 GEN
Solar/Wind Harmer
0.6
3145336SMITFLD
Solar/Wind Harmer
0.076
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
1.969
964241AG1-285 GEN
Solar/Wind Harmer
12.343
316283AC2-100 C
Solar/Wind Harmer
0.349
315813AE1-149 C
Solar/Wind Harmer
9.464
315785AD2-033 C
Solar/Wind Harmer
1.43
971683AH1-343 GEN
Solar/Wind Harmer
6.344
970257AG2-171 GEN
Solar/Wind Harmer
5.516
3151221GRAVEL6
Adder
12.414
3151171GRAVELC
Adder
2.388
959311AF2-222 GEN
Solar/Wind Harmer
15.096
970909AG2-566 GEN
Solar/Wind Harmer
1.775
3144216WINCHST
Adder
0.609
961611AG1-000B GEN
Solar/Wind Harmer
4.271
3150921YORKTN3
Adder
4.021
963181AG1-167 GEN
Solar/Wind Harmer
0.621
3144293JTRSVLE
Adder
0.494
3147133PAMPLIN
Solar/Wind Harmer
0.469
971193AH1-056 GEN
Solar/Wind Harmer
9.098
315839AE2-212 C
Solar/Wind Harmer
0.001
965281AG1-393 GEN
Solar/Wind Harmer
1.464
315778AD1-151 GEN
Solar/Wind Harmer
10.941
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
7.591
3146926FARMVIL
Solar/Wind Harmer
0.069
316044AC1-158 PL1
Solar/Wind Helper
1.278
316450AC1-158 RIC
Solar/Wind Helper
0.341
3146516WINFALL
Solar/Wind Harmer
0.705
3146516WINFALL
Solar/Wind Harmer
0.217
960081AF2-299 GEN
Solar/Wind Harmer
2.083
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.215
316093AE2-104_GEN
Solar/Wind Harmer
3.601
316011AB1-132 GEN
Solar/Wind Harmer
3.888
962571AG1-106 GEN
Solar/Wind Harmer
3.042
3145663CRESWEL
Solar/Wind Harmer
0.597
971163AH1-040 GEN
Solar/Wind Harmer
17.076
971795AH1-408 GEN
Solar/Wind Harmer
14.122
3145796HORNRTN
Solar/Wind Harmer
0.698
3145796HORNRTN
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
0.845
3145893MURPHYS
Solar/Wind Harmer
0.939
3146206CASHIE
Solar/Wind Harmer
0.211
971547AH1-271 GEN
Solar/Wind Harmer
4.506
316190AA2-174 GEN
Solar/Wind Harmer
0
3146173TUNIS
Solar/Wind Harmer
0.211
3146263WOODLND
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
3147043LAWRENC
Adder
1.895
3145823KELFORD
Solar/Wind Harmer
0.208
316129AC1-054 GEN
Solar/Wind Harmer
0.781
971065AG2-659 GEN
Solar/Wind Harmer
8.844
3145963POPLR C
Solar/Wind Harmer
0.207
316072AD1-144
Solar/Wind Harmer
0.075
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316212AC1-099_GEN
Solar/Wind Harmer
1.064
315722AD1-056 GEN
Solar/Wind Harmer
1.293
3146293MARTNCO
Solar/Wind Harmer
0.188
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
3146233WITAKRS
Solar/Wind Harmer
0.796
316494AC1-189 GEN
Solar/Wind Harmer
0.676
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.199
3145493TOT1
Solar/Wind Harmer
0.885
316359AB2-059 GEN
Solar/Wind Harmer
0.711
316049AB1-081 GEN
Solar/Wind Harmer
1.133
3145543BTLEBRO
Solar/Wind Harmer
0.198
3145543BTLEBRO
Solar/Wind Harmer
0.158
3142053HEARTS
Solar/Wind Harmer
0.349
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
19.138
970401AG2-262 GEN
Solar/Wind Harmer
1.126
3145336SMITFLD
Solar/Wind Harmer
0.755
316381AD1-082 GEN
Solar/Wind Harmer
0.196
970659AG2-427 GEN
Solar/Wind Harmer
8.999
316003AC1-222 GEN
Solar/Wind Harmer
0.005
3151171GRAVELC
Adder
1.816
970685AG2-442 GEN
Solar/Wind Harmer
12.211
3138126ROCKLANDING
Solar/Wind Harmer
0.074
961611AG1-000B GEN
Solar/Wind Harmer
8.399
963171AG1-166 GEN
Solar/Wind Harmer
0.828
971563AH1-280 GEN
Solar/Wind Harmer
1.656
3144293JTRSVLE
Adder
0.494
971647AH1-324 GEN
Solar/Wind Harmer
6.473
971317AH1-138 GEN
Solar/Wind Harmer
1.095
971069AG2-661 GEN
Solar/Wind Harmer
2.431
316159AE1-175 C
Solar/Wind Harmer
0.112
315671AE2-027_GEN
Solar/Wind Harmer
8.259
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
970129AG2-093 GEN
Solar/Wind Harmer
3.572
3146926FARMVIL
Solar/Wind Harmer
0.069
3143226MDLTHAN
Solar/Wind Helper
0.299
316045AC1-158 PL2
Solar/Wind Helper
4.09
315244AE2-183_ST
50/50
8.945
963041AG1-153 GEN
50/50
8.209
315779AE2-040
50/50
3.384
3151541CLOVER2
50/50
5.145
3151081ELIZAR1
50/50
21.293
941031AE2-094 GEN
Solar/Wind Harmer
59.933
944011AF1-069 GEN
Solar/Wind Harmer
19.582
970673AG2-436 GEN
Solar/Wind Harmer
67.697
970673AG2-436 GEN
Solar/Wind Harmer
45.131
971967AH1-528 GEN
Solar/Wind Harmer
49.335
970085AG2-068 GEN
Solar/Wind Harmer
15.598
970581AG2-369 GEN
Solar/Wind Harmer
13.414
316315AB2-025 C
Solar/Wind Harmer
0.196
315814AE2-033 C
Solar/Wind Harmer
19.104
957871AF2-081 GEN
Solar/Wind Harmer
10.995
319010AE1-072 C
Solar/Wind Harmer
1.11
3146406KITTY HAWK
Solar/Wind Harmer
0.027
313526AB2-022
Solar/Wind Harmer
0.119
3151091ELIZAR2
Adder
19.718
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.603
3145176PASQUOTANK
Solar/Wind Harmer
0.136
316305AF2-043 C
Solar/Wind Harmer
0.002
3146486SUNBURY
Solar/Wind Harmer
0.218
3146486SUNBURY
Solar/Wind Harmer
0.218
3152611GOSPORTB
Adder
2.775
3152621GOSPORTC
Adder
2.355
3152601GOSPORTA
Adder
2.173
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.215
3130156CHOWAN
Solar/Wind Harmer
0.215
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315835AF2-110_GEN
Solar/Wind Harmer
1.469
315652AC1-086 GEN
Solar/Wind Harmer
23.522
315816AE2-034 GEN
Solar/Wind Harmer
0.916
3137643SOCKMAN
Solar/Wind Harmer
0.849
3130546PLYMOUTH
Solar/Wind Harmer
0.212
965291AG1-394 GEN
Solar/Wind Harmer
0.942
315732AD1-074 GEN1
Solar/Wind Harmer
1.217
315733AD1-074 GEN2
Solar/Wind Harmer
1.217
315735AD1-075 GEN1
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.677
3145796HORNRTN
Solar/Wind Harmer
0.085
3146043SEABORD
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.57
3145893MURPHYS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
970601AG2-382 GEN
Solar/Wind Harmer
7.886
3145513AHOSKIE
Solar/Wind Harmer
0.44
3145513AHOSKIE
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.42
3145683EARLEYS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
970831AG2-522 GEN
Solar/Wind Harmer
8.873
3146033SCOT NK
Solar/Wind Harmer
0.827
316311AC2-079 GEN
Solar/Wind Harmer
5.862
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.14
316005AA1-067
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.8
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
970181AG2-120 GEN
Solar/Wind Harmer
2.501
316319Z2-044 C
Solar/Wind Harmer
0
957861AF2-080 GEN
Solar/Wind Harmer
8.623
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.199
3145573BETHELC
Solar/Wind Harmer
0.199
3143316POE
Solar/Wind Harmer
0.769
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.495
3147173SINAI
Solar/Wind Harmer
0.192
3147243WELCO
Solar/Wind Harmer
0.12
971445AH1-216 GEN
Solar/Wind Harmer
13.184
971443AH1-215 GEN
Solar/Wind Harmer
2.909
3144303KENBRDG
Solar/Wind Harmer
0.138
972265AH1-717 GEN
Adder
13.258
3151201GRAVEL4
Adder
12.428
3151191GRAVEL3
Adder
12.271
3151211GRAVEL5
Adder
12.271
970683AG2-441 GEN
Solar/Wind Harmer
10.903
970681AG2-440 GEN
Solar/Wind Harmer
8.722
970865AG2-541 GEN
Solar/Wind Harmer
5.652
946301AF1-294 GEN
Solar/Wind Harmer
3.063
961791AG1-021 GEN
Solar/Wind Harmer
1.49
315657AE1-056 GEN
Solar/Wind Harmer
5.154
316123AC1-075 GEN
Solar/Wind Harmer
0.197
970165AG2-112 GEN
Solar/Wind Harmer
1.167
970163AG2-111 GEN
Solar/Wind Harmer
1.113
316369SG1_INVT
Solar/Wind Harmer
0.005
3138283WHITEMARSH
Solar/Wind Harmer
0.03
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
970533AG2-339 GEN
50/50
28.925
970531AG2-338 GEN
50/50
11.57
315242AE2-183_GT2
50/50
5.174
315241AE2-183_GT1
50/50
5.142
972185AH1-677 GEN
50/50
18.653
3151041BRUNSWICKG3
50/50
4.054
972187AH1-678 GEN
50/50
9.304
970933AG2-581 GEN
Solar/Wind Harmer
23.481
970099AG2-077 GEN
Solar/Wind Harmer
27.375
3144356SAPONY
Solar/Wind Harmer
2.028
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.885
3145506HICKORY
Solar/Wind Harmer
0.531
3145506HICKORY
Solar/Wind Harmer
0.133
316339AD2-160 GEN
Solar/Wind Harmer
0.358
316018AA1-139 ULT2
Solar/Wind Harmer
0.005
316017AA1-139 ULT1
Solar/Wind Harmer
0.123
3137176SLIGO L2192
Solar/Wind Harmer
0.878
3146456SLIGO L269
Solar/Wind Harmer
3.903
3130086AYDLETT
Solar/Wind Harmer
0.881
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.211
3146386ELIZ CT
Solar/Wind Harmer
0.219
316036AC1-147 C
Solar/Wind Harmer
0.04
3150991CHESPKB
Adder
2.282
3150991CHESPKB
Adder
2.228
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.217
3146516WINFALL
Solar/Wind Harmer
0.217
3146516WINFALL
Solar/Wind Harmer
0.217
3146626S HERTFORD
Solar/Wind Harmer
0.217
3146626S HERTFORD
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.957
3146376EDENTON
Solar/Wind Harmer
0.957
316181AB2-040 GEN
Solar/Wind Harmer
0.311
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3145796HORNRTN
Solar/Wind Harmer
0.634
316065AD1-022 GEN
Solar/Wind Harmer
9.736
3145893MURPHYS
Solar/Wind Harmer
1.414
3145893MURPHYS
Solar/Wind Harmer
0.38
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.211
966811AG1-552 GEN
Solar/Wind Harmer
2.291
3145593CAROLNA
Solar/Wind Harmer
0.263
316426AA2-053 GEN
Solar/Wind Harmer
0.712
3146173TUNIS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.211
3145783HORNRTN
Solar/Wind Harmer
3.739
3145783HORNRTN
Solar/Wind Harmer
2.991
3145783HORNRTN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.374
316274AC1-208 GEN
Solar/Wind Harmer
1.066
939181AE1-148 GEN
Solar/Wind Harmer
9.756
3145933PARMELE
Solar/Wind Harmer
0.406
3145933PARMELE
Solar/Wind Harmer
0.203
3145493TOT1
Solar/Wind Harmer
0.462
3145453TOT5
Solar/Wind Harmer
0.277
3145603CNETO
Solar/Wind Harmer
0.185
961601AG1-000A GEN
Solar/Wind Harmer
3.522
316263AC1-034 GEN
Solar/Wind Harmer
7.526
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
9.215
3146843MT LREL
Solar/Wind Harmer
0.192
3146843MT LREL
Solar/Wind Harmer
0.192
964791AG1-342 GEN
Solar/Wind Harmer
3.686
970657AG2-426 GEN
Solar/Wind Harmer
6.636
970657AG2-426 GEN
Solar/Wind Harmer
1.391
316236AE1-162_GEN
Solar/Wind Harmer
0.002
971741AH1-377 GEN
Solar/Wind Harmer
18.103
316222AC1-221 GEN
Solar/Wind Harmer
0.745
970323AG2-213 GEN
Solar/Wind Harmer
7.354
971775AH1-396 GEN
Solar/Wind Harmer
0.276
316034AC1-036 C
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.099
958211AF2-115 GEN
Solar/Wind Harmer
1.863
963191AG1-168 GEN
Solar/Wind Harmer
0.621
3144293JTRSVLE
Adder
0.494
3144293JTRSVLE
Adder
0.416
3147133PAMPLIN
Solar/Wind Harmer
0.149
3147133PAMPLIN
Solar/Wind Harmer
0.119
316033AB2-134 GEN
Solar/Wind Harmer
0.008
315697AD1-025 GEN
Solar/Wind Harmer
0.161
942751AE2-291 GEN
Solar/Wind Harmer
7.176
316240AF1-291 C
Solar/Wind Harmer
0.001
316447AC1-158 HLD
Solar/Wind Helper
2.812
CPLELTFEXP_CPLE->PJM
CLTF
13.67
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.575
MECLTFEXP_MEC->PJM
CLTF
4.294
SIGELTFEXP_SIGE->PJM
CLTF
0.128
NYPJM->LTFIMP_NY
CLTF
2.148
LGEELTFEXP_LGEE->PJM
CLTF
1.532
WECLTFEXP_WEC->PJM
CLTF
0.787
LAGNLTFEXP_LAGN->PJM
CLTF
9.15
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.306
TVALTFEXP_TVA->PJM
CLTF
4.569

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 158-235_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 158-235_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.32 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4110.11
MW Contribution:1.69
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.273
970413AG2-270 GEN
50/50
26.101
3151591KERR 2
50/50
0.476
3151101ELIZAR3
50/50
22.398
970917AG2-570 GEN
Solar/Wind Harmer
87.11
970909AG2-566 GEN
Solar/Wind Harmer
3.096
316478AD1-087 GEN
Solar/Wind Harmer
2.716
316486AD2-202 GEN
Solar/Wind Harmer
0.795
315773AC2-141 GEN
Solar/Wind Harmer
11.146
316365GEN2_N
Solar/Wind Harmer
1.782
944581AF1-123 GEN
Solar/Wind Harmer
119.632
944601AF1-125 GEN
Solar/Wind Harmer
117.765
966621AG1-532 GEN
Solar/Wind Harmer
0.525
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.141
316320Y1-086
Solar/Wind Harmer
1.503
313506AB2-031 GEN
Solar/Wind Harmer
2.058
315244AE2-183_ST
50/50
9.399
963041AG1-153 GEN
50/50
8.651
3151541CLOVER2
50/50
5.953
315779AE2-040
50/50
3.527
3151611KERR 4
50/50
0.476
3151621KERR 5
50/50
0.476
3151631KERR 6
50/50
0.476
3151641KERR 7
50/50
0.476
3151081ELIZAR1
50/50
22.115
941031AE2-094 GEN
Solar/Wind Harmer
71.566
944011AF1-069 GEN
Solar/Wind Harmer
22.424
970673AG2-436 GEN
Solar/Wind Harmer
78.526
970673AG2-436 GEN
Solar/Wind Harmer
39.76
971967AH1-528 GEN
Solar/Wind Harmer
69.276
970085AG2-068 GEN
Solar/Wind Harmer
21.666
970581AG2-369 GEN
Solar/Wind Harmer
18.633
316315AB2-025 C
Solar/Wind Harmer
0.766
315814AE2-033 C
Solar/Wind Harmer
26.348
946281AF1-292 GEN
Solar/Wind Harmer
0.579
957871AF2-081 GEN
Solar/Wind Harmer
12.899
319010AE1-072 C
Solar/Wind Harmer
5.211
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316087AB2-174 GEN
Solar/Wind Harmer
3.664
313526AB2-022
Solar/Wind Harmer
0.692
970831AG2-522 GEN
Solar/Wind Harmer
12.819
316321Z2-027
Solar/Wind Harmer
0.69
3146396TANGLEW
Solar/Wind Harmer
0.471
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3151091ELIZAR2
Adder
20.479
316305AF2-043 C
Solar/Wind Harmer
0.769
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3137643SOCKMAN
Solar/Wind Harmer
-0.101
3152611GOSPORTB
Adder
2.882
3152621GOSPORTC
Adder
2.446
3152601GOSPORTA
Adder
2.257
315652AC1-086 GEN
Solar/Wind Harmer
28.562
315611Z1-036_GEN2
Solar/Wind Harmer
6.266
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.551
3146043SEABORD
Solar/Wind Harmer
-0.025
965291AG1-394 GEN
Solar/Wind Harmer
2.231
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.01
315816AE2-034 GEN
Solar/Wind Harmer
2.032
316318V4-068
Solar/Wind Harmer
0.625
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
-0.025
315835AF2-110_GEN
Solar/Wind Harmer
3.131
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.047
315733AD1-074 GEN2
Solar/Wind Harmer
5.047
315735AD1-075 GEN1
Solar/Wind Harmer
2.524
3145513AHOSKIE
Solar/Wind Harmer
0.217
961941AG1-037 GEN
Solar/Wind Harmer
0.187
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.904
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
3146033SCOT NK
Solar/Wind Harmer
-0.098
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
316118AC1-105 GEN
Solar/Wind Harmer
1.653
316319Z2-044 C
Solar/Wind Harmer
1.319
316311AC2-079 GEN
Solar/Wind Harmer
12.041
316005AA1-067
Solar/Wind Harmer
0.483
3145746EVERETS
Solar/Wind Harmer
-0.094
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970181AG2-120 GEN
Solar/Wind Harmer
3.132
315833AF1-017_GEN
Solar/Wind Harmer
4.53
316349AD2-085 GEN
Solar/Wind Harmer
2.121
957861AF2-080 GEN
Solar/Wind Harmer
10.406
316239AB2-077_GEN
Solar/Wind Harmer
0.716
316238AB2-078_GEN
Solar/Wind Harmer
0.716
316420AA1-050 GEN
Solar/Wind Harmer
2.712
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
3144303KENBRDG
Solar/Wind Harmer
-0.019
946301AF1-294 GEN
Solar/Wind Harmer
6.052
961791AG1-021 GEN
Solar/Wind Harmer
2.952
3143316POE
Solar/Wind Harmer
-0.089
971445AH1-216 GEN
Solar/Wind Harmer
13.527
970865AG2-541 GEN
Solar/Wind Harmer
8.264
972265AH1-717 GEN
Adder
13.778
3151201GRAVEL4
Adder
12.916
3151191GRAVEL3
Adder
12.753
3151211GRAVEL5
Adder
12.753
270455AD2-022 GEN
Solar/Wind Harmer
3.312
270457AD2-023 GEN
Solar/Wind Harmer
1.68
316123AC1-075 GEN
Solar/Wind Harmer
1.924
970165AG2-112 GEN
Solar/Wind Harmer
1.694
970163AG2-111 GEN
Solar/Wind Harmer
1.616
316369SG1_INVT
Solar/Wind Harmer
2.993
971443AH1-215 GEN
Solar/Wind Harmer
3.238
970533AG2-339 GEN
50/50
30.197
970531AG2-338 GEN
50/50
12.079
315242AE2-183_GT2
50/50
5.436
315241AE2-183_GT1
50/50
5.403
972185AH1-677 GEN
50/50
19.599
3151041BRUNSWICKG3
50/50
4.273
972187AH1-678 GEN
50/50
9.805
970933AG2-581 GEN
Solar/Wind Harmer
33.58
970099AG2-077 GEN
Solar/Wind Harmer
41.334
971741AH1-377 GEN
Solar/Wind Harmer
37.913
970301AG2-198 GEN
Solar/Wind Harmer
16.306
3144356SAPONY
Solar/Wind Harmer
0.99
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316185AD1-033 GEN
Solar/Wind Harmer
2.727
316339AD2-160 GEN
Solar/Wind Harmer
1.741
316018AA1-139 ULT2
Solar/Wind Harmer
2.21
316017AA1-139 ULT1
Solar/Wind Harmer
2.087
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.043
3130086AYDLETT
Solar/Wind Harmer
-0.102
3142956BIRDNECK
Solar/Wind Harmer
1.377
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316316AC1-027 C
Solar/Wind Harmer
0.787
316181AB2-040 GEN
Solar/Wind Harmer
3.572
316431W1029_GEN1
Solar/Wind Harmer
4.617
316433W1029_GEN2
Solar/Wind Harmer
4.617
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
939181AE1-148 GEN
Solar/Wind Harmer
14.321
316036AC1-147 C
Solar/Wind Harmer
0.686
3150991CHESPKB
Adder
2.371
3150991CHESPKB
Adder
2.314
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
966811AG1-552 GEN
Solar/Wind Harmer
2.849
3145593CAROLNA
Solar/Wind Harmer
0.21
3146376EDENTON
Solar/Wind Harmer
0.75
3146376EDENTON
Solar/Wind Harmer
0.75
316426AA2-053 GEN
Solar/Wind Harmer
2.551
3145783HORNRTN
Solar/Wind Harmer
2.991
3145783HORNRTN
Solar/Wind Harmer
2.393
3145783HORNRTN
Solar/Wind Harmer
0.748
3145783HORNRTN
Solar/Wind Harmer
0.299
3145796HORNRTN
Solar/Wind Harmer
-0.075
315742AE1-103 GEN
Solar/Wind Harmer
2.623
3145893MURPHYS
Solar/Wind Harmer
0.699
3145893MURPHYS
Solar/Wind Harmer
-0.045
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
316065AD1-022 GEN
Solar/Wind Harmer
12.467
316274AC1-208 GEN
Solar/Wind Harmer
2.649
3145933PARMELE
Solar/Wind Harmer
-0.048
3145933PARMELE
Solar/Wind Harmer
-0.024
3146843MT LREL
Solar/Wind Harmer
-0.024
3146843MT LREL
Solar/Wind Harmer
-0.024
964791AG1-342 GEN
Solar/Wind Harmer
5.11
962561AG1-105 GEN
Solar/Wind Harmer
13.432
3145493TOT1
Solar/Wind Harmer
0.367
3145453TOT5
Solar/Wind Harmer
0.22
3145603CNETO
Solar/Wind Harmer
0.147
316263AC1-034 GEN
Solar/Wind Harmer
11.081
961601AG1-000A GEN
Solar/Wind Harmer
9.29
313527AB2-043 GEN
Solar/Wind Harmer
3.838
970323AG2-213 GEN
Solar/Wind Harmer
11.811
971775AH1-396 GEN
Solar/Wind Harmer
1.682
958211AF2-115 GEN
Solar/Wind Harmer
3.69
963191AG1-168 GEN
Solar/Wind Harmer
2.214
3144293JTRSVLE
Adder
0.669
3144293JTRSVLE
Adder
0.563
970657AG2-426 GEN
Solar/Wind Harmer
6.92
970657AG2-426 GEN
Solar/Wind Harmer
1.447
316222AC1-221 GEN
Solar/Wind Harmer
2.234
316236AE1-162_GEN
Solar/Wind Harmer
0.665
316033AB2-134 GEN
Solar/Wind Harmer
5.402
315697AD1-025 GEN
Solar/Wind Harmer
3.388
316447AC1-158 HLD
Solar/Wind Helper
2.837
942751AE2-291 GEN
Solar/Wind Harmer
2.754
316435W1029_GEN3
Solar/Wind Harmer
4.617
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3146376EDENTON
Solar/Wind Harmer
-0.025
3147043LAWRENC
Solar/Wind Harmer
-0.015
3156081AA2-088 GEN
Solar/Wind Harmer
8.159
3145796HORNRTN
Solar/Wind Harmer
-0.1
3145796HORNRTN
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.709
3145273HOLLAND
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.722
961681AG1-008 GEN
Solar/Wind Harmer
19.722
3146263WOODLND
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
971157AH1-035 GEN
Solar/Wind Harmer
3.122
315737AD1-076 GEN
Solar/Wind Harmer
4.743
316463AE2-346 GEN
Solar/Wind Harmer
0.404
316140AB2-099
Solar/Wind Harmer
0.168
962331AG1-082 GEN
Solar/Wind Harmer
3.118
3146206CASHIE
Solar/Wind Harmer
-0.025
3156021HOLLOMANSOL
Solar/Wind Harmer
3.351
316317KELFORD C
Solar/Wind Harmer
1.168
3145823KELFORD
Solar/Wind Harmer
-0.025
316210AC1-098 GEN
Solar/Wind Harmer
3.85
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145963POPLR C
Solar/Wind Harmer
-0.024
315724AD1-057 GEN
Solar/Wind Harmer
1.398
316248AF1-058 C
Solar/Wind Harmer
0.727
960061AF2-297 GEN
Solar/Wind Harmer
12.068
316327AA2-057 GEN
Solar/Wind Harmer
2.437
3145933PARMELE
Solar/Wind Harmer
-0.024
966801AG1-551 GEN
Solar/Wind Harmer
3.006
3146233WITAKRS
Solar/Wind Harmer
0.5
3146233WITAKRS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3138543CONSLDL
Solar/Wind Harmer
-0.016
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.407
316131AB2-060 GEN
Solar/Wind Harmer
2.549
315785AD2-033 C
Solar/Wind Harmer
5.354
970257AG2-171 GEN
Solar/Wind Harmer
8.858
963181AG1-167 GEN
Solar/Wind Harmer
2.214
3144293JTRSVLE
Adder
0.669
970661AG2-428 GEN
Solar/Wind Harmer
4.234
3145336SMITFLD
Solar/Wind Harmer
-0.009
316283AC2-100 C
Solar/Wind Harmer
2.067
316083AB2-161 GEN
Solar/Wind Harmer
3.56
970659AG2-427 GEN
Solar/Wind Harmer
2.047
971683AH1-343 GEN
Solar/Wind Harmer
9.304
964241AG1-285 GEN
Solar/Wind Harmer
16.391
315813AE1-149 C
Solar/Wind Harmer
12.953
3151221GRAVEL6
Adder
12.901
3151171GRAVELC
Adder
2.482
3144216WINCHST
Adder
0.633
961611AG1-000B GEN
Solar/Wind Harmer
3.938
3150921YORKTN3
Adder
4.178
315839AE2-212 C
Solar/Wind Harmer
0.516
316313AB2-026
Solar/Wind Helper
0.361
316258AE1-075 C
Solar/Wind Helper
0.324
316405AF2-144 C
Solar/Wind Helper
0.27
316044AC1-158 PL1
Solar/Wind Helper
1.289
316450AC1-158 RIC
Solar/Wind Helper
0.344
315243AE2-183_GT3
50/50
5.436
3151051BRUNSWICKS1
50/50
8.868
3151021BRUNSWICKG1
50/50
4.273
971451AH1-221 GEN
50/50
12.977
3151531CLOVER1
50/50
5.981
3151601KERR 3
50/50
0.476
3151581KERR 1
50/50
0.17
940641AE2-051 GEN
Solar/Wind Harmer
35.003
970919AG2-571 GEN
Solar/Wind Harmer
11.027
970087AG2-069 GEN
Solar/Wind Harmer
32.499
939411AE1-173 GEN
Solar/Wind Harmer
172.453
957481AF2-042 GEN
Solar/Wind Harmer
103.335
315693AD1-088 GEN
Solar/Wind Harmer
16.309
962491AG1-098 GEN
Solar/Wind Harmer
21.813
315687AD1-152 GEN
Solar/Wind Harmer
3.479
316294AC1-161 GEN
Solar/Wind Harmer
8.618
316023GEN1_S
Solar/Wind Harmer
1.782
944591AF1-124 GEN
Solar/Wind Harmer
120.063
960081AF2-299 GEN
Solar/Wind Harmer
2.909
316388AE2-253 GEN
Solar/Wind Harmer
1.741
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971065AG2-659 GEN
Solar/Wind Harmer
12.852
316129AC1-054 GEN
Solar/Wind Harmer
2.251
316246AF1-032 C
Solar/Wind Harmer
0.516
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.8
3150981CHESPKA
Adder
2.826
971795AH1-408 GEN
Solar/Wind Harmer
19.043
316011AB1-132 GEN
Solar/Wind Harmer
5.312
962571AG1-106 GEN
Solar/Wind Harmer
3.65
315800Z1-036_GEN1
Solar/Wind Harmer
6.266
3130156CHOWAN
Solar/Wind Harmer
-0.025
316190AA2-174 GEN
Solar/Wind Harmer
0.31
3145783HORNRTN
Solar/Wind Harmer
-0.025
3147043LAWRENC
Adder
2.027
3145796HORNRTN
Solar/Wind Harmer
-0.083
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145663CRESWEL
Solar/Wind Harmer
-0.07
971163AH1-040 GEN
Solar/Wind Harmer
23.537
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.744
316093AE2-104_GEN
Solar/Wind Harmer
7.284
3146263WOODLND
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.231
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145823KELFORD
Solar/Wind Harmer
-0.025
316212AC1-099_GEN
Solar/Wind Harmer
2.139
3145963POPLR C
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.761
315722AD1-056 GEN
Solar/Wind Harmer
2.542
316072AD1-144
Solar/Wind Harmer
0.487
3146293MARTNCO
Solar/Wind Harmer
0.149
970401AG2-262 GEN
Solar/Wind Harmer
1.561
3146233WITAKRS
Solar/Wind Harmer
-0.094
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316494AC1-189 GEN
Solar/Wind Harmer
2.559
316237AB2-079_GEN
Solar/Wind Harmer
0.716
961671AG1-007 GEN
Solar/Wind Harmer
0.3
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.704
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.187
316049AB1-081 GEN
Solar/Wind Harmer
2.551
3142053HEARTS
Solar/Wind Harmer
0.278
963171AG1-166 GEN
Solar/Wind Harmer
2.952
971563AH1-280 GEN
Solar/Wind Harmer
2.952
3144293JTRSVLE
Adder
0.669
316003AC1-222 GEN
Solar/Wind Harmer
2.223
970661AG2-428 GEN
Solar/Wind Harmer
23.895
3145336SMITFLD
Solar/Wind Harmer
-0.088
316381AD1-082 GEN
Solar/Wind Harmer
2.012
970659AG2-427 GEN
Solar/Wind Harmer
11.552
3151171GRAVELC
Adder
1.888
3138126ROCKLANDING
Solar/Wind Harmer
0.058
961611AG1-000B GEN
Solar/Wind Harmer
9.23
971647AH1-324 GEN
Solar/Wind Harmer
8.86
971317AH1-138 GEN
Solar/Wind Harmer
2.139
3143226MDLTHAN
Solar/Wind Helper
0.31
316045AC1-158 PL2
Solar/Wind Helper
4.126
CPLELTFEXP_CPLE->PJM
CLTF
14.618
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.054
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.456
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.389
MECLTFEXP_MEC->PJM
CLTF
4.488
SIGELTFEXP_SIGE->PJM
CLTF
0.133
NYPJM->LTFIMP_NY
CLTF
2.212
LGEELTFEXP_LGEE->PJM
CLTF
1.591
WECLTFEXP_WEC->PJM
CLTF
0.819
LAGNLTFEXP_LAGN->PJM
CLTF
9.651
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.23
TVALTFEXP_TVA->PJM
CLTF
4.814

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.78 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5404.52
MW Contribution:1.09
Bus #Bus NameTypeMW Contribution
971507AH1-251 GEN
50/50
17.73
3152251N ANNA1
50/50
14.579
972197AH1-683 GEN
50/50
5.816
972219AH1-694 GEN
50/50
4.188
315052AA1-145 CT2
50/50
2.039
316045AC1-158 PL2
Solar/Wind Harmer
4.87
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
0.648
3142416OLDCHRC
Solar/Wind Harmer
0.248
3143526WINTERP
Solar/Wind Harmer
1.273
3143096IRON208
Adder
1.025
971531AH1-263 GEN
50/50
86.379
3150411LDYSMT5
50/50
37.362
3150381LDYSMT2
50/50
35.757
972213AH1-691 GEN
50/50
6.049
972215AH1-692 GEN
50/50
6.049
963051AG1-154 GEN
50/50
4.653
972189AH1-679 GEN
Adder
4.288
316312AB1-027
Solar/Wind Harmer
0.446
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971281AH1-106 GEN
Solar/Wind Harmer
3.397
971283AH1-107 GEN
Solar/Wind Harmer
3.397
971285AH1-108 GEN
Adder
1.844
315976AC1-164 GENA
Solar/Wind Harmer
25.197
316169AC1-164_GENC
Solar/Wind Harmer
21.768
315975AC1-164 GENB
Solar/Wind Harmer
0.745
316164AC1-076 GEN
Solar/Wind Harmer
0.34
316132AB2-190 GEN1
Solar/Wind Harmer
1.28
316369SG1_INVT
Solar/Wind Harmer
0.009
971167AH1-042 GEN
Solar/Wind Harmer
21.021
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
972265AH1-717 GEN
Adder
18.278
3151201GRAVEL4
Adder
17.134
3150391LDYSMT3
50/50
37.176
972195AH1-682 GEN
50/50
4.885
316447AC1-158 HLD
Solar/Wind Harmer
3.348
315673AE1-157 GEN
Solar/Wind Harmer
17.981
957411AF2-035 GEN
Solar/Wind Harmer
11.052
970317AG2-208 GEN
Solar/Wind Harmer
10.239
3142296MT RD221
Adder
0.803
3142366NRTHEST
Adder
0.809
3150691DARBY 3
Adder
17.772
3150701DARBY 4
Adder
17.73
3150681DARBY 2
Adder
17.71
3150671DARBY 1
Adder
17.689
3143526WINTERP
Solar/Wind Harmer
1.273
316075AC2-137 C
Solar/Wind Harmer
0.067
971223AH1-071 GEN
Solar/Wind Harmer
2.604
966871AG1-558 GEN
Solar/Wind Harmer
0.281
3142946ENON
Solar/Wind Harmer
0.024
944641AF1-129 GEN
Adder
114.635
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.267
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.043
3150991CHESPKB
Adder
2.436
3150991CHESPKB
Adder
2.378
970657AG2-426 GEN
Solar/Wind Harmer
8.137
970657AG2-426 GEN
Solar/Wind Harmer
1.706
316316AC1-027 C
Solar/Wind Harmer
0.223
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.925
3145506HICKORY
Solar/Wind Harmer
0.555
3145506HICKORY
Solar/Wind Harmer
0.139
316339AD2-160 GEN
Solar/Wind Harmer
0.374
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.129
3137176SLIGO L2192
Solar/Wind Harmer
0.914
3146456SLIGO L269
Solar/Wind Harmer
4.065
3130086AYDLETT
Solar/Wind Harmer
0.917
3146386ELIZ CT
Solar/Wind Harmer
0.227
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
3146626S HERTFORD
Solar/Wind Harmer
0.223
3146626S HERTFORD
Solar/Wind Harmer
0.223
3144356SAPONY
Solar/Wind Harmer
1.861
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.969
3146376EDENTON
Solar/Wind Harmer
0.969
958261AF2-120 GEN
Solar/Wind Harmer
7.183
972185AH1-677 GEN
Adder
12.157
972187AH1-678 GEN
Adder
6.1
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.219
3150341NORNECKC1
Adder
2.202
316468AD1-105 GEN
Solar/Wind Harmer
-0.069
970933AG2-581 GEN
Solar/Wind Harmer
16.879
316065AD1-022 GEN
Solar/Wind Harmer
9.548
3145893MURPHYS
Solar/Wind Harmer
1.376
3145893MURPHYS
Solar/Wind Harmer
0.37
3146173TUNIS
Solar/Wind Harmer
0.204
3146173TUNIS
Solar/Wind Harmer
0.204
316181AB2-040 GEN
Solar/Wind Harmer
0.288
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3150851SPRUNCC
Adder
1.127
3143226MDLTHAN
Solar/Wind Harmer
0.244
3142543TWELFTH
Solar/Wind Harmer
0.023
944631AF1-128 GEN
Adder
115.654
316159AE1-175 C
Solar/Wind Harmer
0.206
970129AG2-093 GEN
Solar/Wind Harmer
6.792
316458AB2-190 GEN2
Solar/Wind Harmer
1.28
315671AE2-027_GEN
Solar/Wind Harmer
15.26
971069AG2-661 GEN
Solar/Wind Harmer
4.23
971647AH1-324 GEN
Solar/Wind Harmer
10.104
971317AH1-138 GEN
Solar/Wind Harmer
1.765
3138126ROCKLANDING
Solar/Wind Harmer
0.108
3142433PROV 92
Solar/Wind Harmer
0.944
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
12.386
316294AC1-161 GEN
Solar/Wind Harmer
4.079
3151171GRAVELC
Adder
2.504
3145336SMITFLD
Solar/Wind Harmer
0.937
970659AG2-427 GEN
Solar/Wind Harmer
11.263
944591AF1-124 GEN
Solar/Wind Harmer
52.565
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.904
316381AD1-082 GEN
Solar/Wind Harmer
0.242
3141766HARMONY
Solar/Wind Harmer
0.046
970661AG2-428 GEN
Solar/Wind Harmer
23.062
971777AH1-397 GEN
Solar/Wind Harmer
0.612
3141843SHACKLE
Adder
1.184
316072AD1-144
Solar/Wind Harmer
0.084
939411AE1-173 GEN
Solar/Wind Harmer
98.509
940641AE2-051 GEN
Solar/Wind Harmer
18.448
316388AE2-253 GEN
Solar/Wind Harmer
0.722
3146456SLIGO L269
Solar/Wind Harmer
0.23
316246AF1-032 C
Solar/Wind Harmer
0.103
316093AE2-104_GEN
Solar/Wind Harmer
3.838
3138133OCRAN
Solar/Wind Harmer
0.136
3146516WINFALL
Solar/Wind Harmer
0.727
3146516WINFALL
Solar/Wind Harmer
0.224
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.218
962861AG1-135 GEN
Solar/Wind Harmer
6.976
3141726DUNNSVL
Solar/Wind Harmer
0.859
3145663CRESWEL
Solar/Wind Harmer
0.597
971163AH1-040 GEN
Solar/Wind Harmer
17.057
3150351NORNECKC2
Adder
2.113
3143336POWHATN
Solar/Wind Harmer
3.747
970919AG2-571 GEN
Solar/Wind Harmer
7.353
3146206CASHIE
Solar/Wind Harmer
0.206
971547AH1-271 GEN
Solar/Wind Harmer
4.407
316023GEN1_S
Solar/Wind Harmer
0.463
970087AG2-069 GEN
Solar/Wind Harmer
16.479
3145893MURPHYS
Solar/Wind Harmer
0.822
3145893MURPHYS
Solar/Wind Harmer
0.914
3146173TUNIS
Solar/Wind Harmer
0.204
316337AD2-073 GEN
Solar/Wind Harmer
0.177
316336AC2-165 C
Solar/Wind Harmer
0.008
3145683EARLEYS
Solar/Wind Harmer
0.202
3147666LOUISA
Solar/Wind Harmer
0.804
960081AF2-299 GEN
Solar/Wind Harmer
1.928
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.199
957481AF2-042 GEN
Solar/Wind Harmer
52.836
316011AB1-132 GEN
Solar/Wind Harmer
3.595
962571AG1-106 GEN
Solar/Wind Harmer
2.814
3145823KELFORD
Solar/Wind Harmer
0.198
316190AA2-174 GEN
Solar/Wind Harmer
0
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316192AB2-158 GEN
Solar/Wind Harmer
1.112
971795AH1-408 GEN
Solar/Wind Harmer
13.096
3145783HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.642
3145796HORNRTN
Solar/Wind Harmer
0.195
315693AD1-088 GEN
Solar/Wind Harmer
9.336
3147043LAWRENC
Adder
1.759
962491AG1-098 GEN
Solar/Wind Harmer
11.068
316212AC1-099_GEN
Solar/Wind Harmer
0.984
3146293MARTNCO
Solar/Wind Harmer
0.176
316129AC1-054 GEN
Solar/Wind Harmer
0.701
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
971065AG2-659 GEN
Solar/Wind Harmer
7.918
315722AD1-056 GEN
Solar/Wind Harmer
1.169
316494AC1-189 GEN
Solar/Wind Harmer
0.617
315687AD1-152 GEN
Solar/Wind Harmer
0.006
961671AG1-007 GEN
Solar/Wind Harmer
0.028
3146083TARBORO
Solar/Wind Harmer
0.18
3145493TOT1
Solar/Wind Harmer
0.8
3146233WITAKRS
Solar/Wind Harmer
0.716
970937AG2-583 GEN
Solar/Wind Harmer
11.013
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
13.329
972135AH1-637 GEN
Solar/Wind Harmer
1.522
963171AG1-166 GEN
Solar/Wind Harmer
0.95
971563AH1-280 GEN
Solar/Wind Harmer
1.9
3144293JTRSVLE
Adder
0.567
3152261N ANNA2
50/50
14.578
970497AG2-320 GEN
50/50
26.215
3150401LDYSMT4
50/50
37.246
3150371LDYSMT1
50/50
35.99
315051AA1-145 CT1
50/50
2.03
316044AC1-158 PL1
Solar/Wind Harmer
1.523
316450AC1-158 RIC
Solar/Wind Harmer
0.406
3142416OLDCHRC
Solar/Wind Harmer
2.415
970293AG2-193 GEN
Solar/Wind Harmer
2.624
3143096IRON208
Adder
1.025
3143096IRON208
Adder
1.004
3150861SPRUNCD
Adder
1.127
316473AC1-191 GEN
Solar/Wind Harmer
0.822
3142946ENON
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
2.304
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.433
315778AD1-151 GEN
Solar/Wind Harmer
19.035
965281AG1-393 GEN
Solar/Wind Harmer
2.538
315839AE2-212 C
Solar/Wind Harmer
0.002
3150921YORKTN3
Adder
5.938
3144216WINCHST
Adder
0.891
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
6.298
315773AC2-141 GEN
Solar/Wind Harmer
8.598
3151221GRAVEL6
Adder
17.114
3151171GRAVELC
Adder
3.293
3145336SMITFLD
Solar/Wind Harmer
0.094
315813AE1-149 C
Solar/Wind Harmer
12.5
3144536CHRHLND
Solar/Wind Harmer
0.035
970659AG2-427 GEN
Solar/Wind Harmer
2.464
944581AF1-123 GEN
Solar/Wind Harmer
52.379
944601AF1-125 GEN
Solar/Wind Harmer
51.572
3151101ELIZAR3
Adder
21.599
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.092
970661AG2-428 GEN
Solar/Wind Harmer
4.905
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.17
3141873WAN 176
Solar/Wind Harmer
4.089
3146456SLIGO L269
Solar/Wind Harmer
0.23
971153AH1-033 GEN
Solar/Wind Harmer
2.655
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.224
3146626S HERTFORD
Solar/Wind Harmer
0.223
3145273HOLLAND
Solar/Wind Harmer
0.166
962971AG1-146 GEN
Solar/Wind Harmer
3.551
970009AG2-005 GEN
Solar/Wind Harmer
1.644
3146376EDENTON
Solar/Wind Harmer
0.218
316404AE1-155 C
Solar/Wind Harmer
0.049
315614AA2-178 GEN
Solar/Wind Harmer
1.22
3150351NORNECKC2
Adder
2.148
971781AH1-399 GEN
Solar/Wind Harmer
0.278
316313AB2-026
Solar/Wind Harmer
0.133
316258AE1-075 C
Solar/Wind Harmer
0.159
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.185
971157AH1-035 GEN
Solar/Wind Harmer
2.514
315737AD1-076 GEN
Solar/Wind Harmer
2.686
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
970917AG2-570 GEN
Solar/Wind Harmer
18.383
3146206CASHIE
Solar/Wind Harmer
0.206
316365GEN2_N
Solar/Wind Harmer
0.463
3145893MURPHYS
Solar/Wind Harmer
0.344
3145893MURPHYS
Solar/Wind Harmer
0.206
957521AF2-046 GEN
Solar/Wind Harmer
15.264
961681AG1-008 GEN
Solar/Wind Harmer
15.264
3146173TUNIS
Solar/Wind Harmer
0.204
3156021HOLLOMANSOL
Solar/Wind Harmer
0.924
316463AE2-346 GEN
Solar/Wind Harmer
0.174
316140AB2-099
Solar/Wind Harmer
0.072
962331AG1-082 GEN
Solar/Wind Harmer
2.163
3147666LOUISA
Solar/Wind Harmer
0.462
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.199
313506AB2-031 GEN
Solar/Wind Harmer
0.614
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.198
3145796HORNRTN
Solar/Wind Harmer
0.778
3145796HORNRTN
Solar/Wind Harmer
0.195
3147043LAWRENC
Solar/Wind Harmer
0.117
3141906WESTMOR
Solar/Wind Harmer
0.077
316478AD1-087 GEN
Solar/Wind Harmer
0.667
316486AD2-202 GEN
Solar/Wind Harmer
0.196
316210AC1-098 GEN
Solar/Wind Harmer
1.765
3145933PARMELE
Solar/Wind Harmer
0.19
966801AG1-551 GEN
Solar/Wind Harmer
2.213
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
315724AD1-057 GEN
Solar/Wind Harmer
0.693
970737AG2-469 GEN
Solar/Wind Harmer
7.863
970909AG2-566 GEN
Solar/Wind Harmer
1.962
316327AA2-057 GEN
Solar/Wind Harmer
0.277
3146073TAR RVR
Solar/Wind Harmer
0.18
3146083TARBORO
Solar/Wind Harmer
0.18
3146233WITAKRS
Solar/Wind Harmer
0.903
3146233WITAKRS
Solar/Wind Harmer
0.122
316131AB2-060 GEN
Solar/Wind Harmer
0.565
3138543CONSLDL
Solar/Wind Harmer
0.118
964241AG1-285 GEN
Solar/Wind Harmer
11.97
315785AD2-033 C
Solar/Wind Harmer
1.456
970257AG2-171 GEN
Solar/Wind Harmer
5.726
959311AF2-222 GEN
Solar/Wind Harmer
15.895
963181AG1-167 GEN
Solar/Wind Harmer
0.712
3144293JTRSVLE
Adder
0.567
3147133PAMPLIN
Solar/Wind Harmer
0.558
971193AH1-056 GEN
Solar/Wind Harmer
10.829
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3151191GRAVEL3
Adder
16.917
3151211GRAVEL5
Adder
16.917
971445AH1-216 GEN
Solar/Wind Harmer
16.508
3143316POE
Solar/Wind Harmer
0.927
3143873LANEXA
Solar/Wind Harmer
0.14
3138283WHITEMARSH
Solar/Wind Harmer
0.054
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
21.327
3151091ELIZAR2
Adder
20.956
3152611GOSPORTB
Adder
2.962
3152621GOSPORTC
Adder
2.514
3152601GOSPORTA
Adder
2.319
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.866
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
957871AF2-081 GEN
Solar/Wind Harmer
11.461
3141873WAN 176
Solar/Wind Harmer
0.046
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.158
316311AC2-079 GEN
Solar/Wind Harmer
6.6
319010AE1-072 C
Solar/Wind Harmer
1.156
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.566
313526AB2-022
Solar/Wind Harmer
0.123
3141913WHIT STONE
Solar/Wind Harmer
0.227
3146486SUNBURY
Solar/Wind Harmer
0.227
3146486SUNBURY
Solar/Wind Harmer
0.227
3138133OCRAN
Solar/Wind Harmer
0.068
316321Z2-027
Solar/Wind Harmer
0.042
3146396TANGLEW
Solar/Wind Harmer
0.624
3145176PASQUOTANK
Solar/Wind Harmer
0.14
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
316315AB2-025 C
Solar/Wind Harmer
0.18
941031AE2-094 GEN
Solar/Wind Harmer
40.915
944011AF1-069 GEN
Solar/Wind Harmer
13.368
962981AG1-147 GEN
Solar/Wind Harmer
8.287
315814AE2-033 C
Solar/Wind Harmer
17.537
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970327AG2-215 GEN
Solar/Wind Harmer
7.225
970673AG2-436 GEN
Solar/Wind Harmer
46.61
970673AG2-436 GEN
Solar/Wind Harmer
31.073
3130156CHOWAN
Solar/Wind Harmer
0.218
3130156CHOWAN
Solar/Wind Harmer
0.218
971967AH1-528 GEN
Solar/Wind Harmer
34.545
315816AE2-034 GEN
Solar/Wind Harmer
0.915
3141813NORNECK
Solar/Wind Harmer
0.212
3130546PLYMOUTH
Solar/Wind Harmer
0.209
315732AD1-074 GEN1
Solar/Wind Harmer
1.2
315733AD1-074 GEN2
Solar/Wind Harmer
1.2
315735AD1-075 GEN1
Solar/Wind Harmer
0.6
965291AG1-394 GEN
Solar/Wind Harmer
0.923
3146206CASHIE
Solar/Wind Harmer
0.206
970601AG2-382 GEN
Solar/Wind Harmer
7.712
970085AG2-068 GEN
Solar/Wind Harmer
10.986
970581AG2-369 GEN
Solar/Wind Harmer
9.448
3145893MURPHYS
Solar/Wind Harmer
0.555
3145893MURPHYS
Solar/Wind Harmer
0.206
3145513AHOSKIE
Solar/Wind Harmer
0.424
3145513AHOSKIE
Solar/Wind Harmer
0.203
3145683EARLEYS
Solar/Wind Harmer
0.403
3145683EARLEYS
Solar/Wind Harmer
0.202
3145683EARLEYS
Solar/Wind Harmer
0.202
3146043SEABORD
Solar/Wind Harmer
0.201
315607AA1-063A GEN
Solar/Wind Harmer
0.41
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
21.753
3137643SOCKMAN
Solar/Wind Harmer
0.788
3145796HORNRTN
Solar/Wind Harmer
0.623
3145796HORNRTN
Solar/Wind Harmer
0.078
3146033SCOT NK
Solar/Wind Harmer
0.774
316223AC1-118
Solar/Wind Harmer
0.139
970831AG2-522 GEN
Solar/Wind Harmer
7.995
316005AA1-067
Solar/Wind Harmer
0.2
3145746EVERETS
Solar/Wind Harmer
0.74
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
970181AG2-120 GEN
Solar/Wind Harmer
2.314
957861AF2-080 GEN
Solar/Wind Harmer
7.879
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.18
3145573BETHELC
Solar/Wind Harmer
0.18
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
3.007
3144303KENBRDG
Solar/Wind Harmer
0.143
970683AG2-441 GEN
Solar/Wind Harmer
11.901
970681AG2-440 GEN
Solar/Wind Harmer
9.521
946301AF1-294 GEN
Solar/Wind Harmer
3.515
961791AG1-021 GEN
Solar/Wind Harmer
1.71
315657AE1-056 GEN
Solar/Wind Harmer
6.134
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970099AG2-077 GEN
Solar/Wind Harmer
21.134
316426AA2-053 GEN
Solar/Wind Harmer
0.666
3145593CAROLNA
Solar/Wind Harmer
0.196
3145593CAROLNA
Solar/Wind Harmer
0.196
966811AG1-552 GEN
Solar/Wind Harmer
2.127
3145593CAROLNA
Solar/Wind Harmer
0.244
3145783HORNRTN
Solar/Wind Harmer
3.466
3145783HORNRTN
Solar/Wind Harmer
2.773
3145783HORNRTN
Solar/Wind Harmer
0.866
3145783HORNRTN
Solar/Wind Harmer
0.347
3145796HORNRTN
Solar/Wind Harmer
0.584
3145933PARMELE
Solar/Wind Harmer
0.38
3145933PARMELE
Solar/Wind Harmer
0.19
316274AC1-208 GEN
Solar/Wind Harmer
0.98
971741AH1-377 GEN
Solar/Wind Harmer
18.489
970301AG2-198 GEN
Solar/Wind Harmer
7.849
939181AE1-148 GEN
Solar/Wind Harmer
8.688
3145493TOT1
Solar/Wind Harmer
0.417
3145453TOT5
Solar/Wind Harmer
0.25
3145603CNETO
Solar/Wind Harmer
0.167
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.634
971775AH1-396 GEN
Solar/Wind Harmer
0.286
958211AF2-115 GEN
Solar/Wind Harmer
2.137
963191AG1-168 GEN
Solar/Wind Harmer
0.712
3144293JTRSVLE
Adder
0.567
3144293JTRSVLE
Adder
0.477
3147133PAMPLIN
Solar/Wind Harmer
0.178
3147133PAMPLIN
Solar/Wind Harmer
0.142
961601AG1-000A GEN
Solar/Wind Harmer
3.141
316263AC1-034 GEN
Solar/Wind Harmer
6.71
962561AG1-105 GEN
Solar/Wind Harmer
8.256
964791AG1-342 GEN
Solar/Wind Harmer
3.275
3146843MT LREL
Solar/Wind Harmer
0.17
3146843MT LREL
Solar/Wind Harmer
0.17
3146776BUCKING
Solar/Wind Harmer
0.676
3146776BUCKING
Solar/Wind Harmer
0.055
971489AH1-241 GEN
Solar/Wind Harmer
8.062
316222AC1-221 GEN
Solar/Wind Harmer
0.618
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.907
966001AG1-469 GEN
Solar/Wind Harmer
0.072
3151731LOISA B
Adder
8.04
3151721LOISA A
Adder
7.998
970285AG2-188 GEN
Solar/Wind Harmer
13.517
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971845AH1-439 GEN
Solar/Wind Harmer
7.694
316118AC1-105 GEN
Solar/Wind Harmer
0.432
972193AH1-681 GEN
Adder
3.772
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.102
972205AH1-687 GEN
Adder
6.859
971447AH1-217 GEN
Solar/Wind Harmer
4.479
970865AG2-541 GEN
Solar/Wind Harmer
5.067
316123AC1-075 GEN
Solar/Wind Harmer
0.184
970165AG2-112 GEN
Solar/Wind Harmer
1.09
970163AG2-111 GEN
Solar/Wind Harmer
1.039
270494AE1-108_GEN
Solar/Wind Harmer
1.609
3147346CASHSCORNER
Solar/Wind Harmer
0.278
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.141
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.011
3142053HEARTS
Solar/Wind Harmer
0.311
3146926FARMVIL
Solar/Wind Harmer
0.106
970401AG2-262 GEN
Solar/Wind Harmer
1.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.068
972277AH1-723 GEN
Adder
98.366
972003AH1-546 GEN
Solar/Wind Harmer
6.888
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.612
3147623JAMES R
Solar/Wind Harmer
0.35
3151751LOISA D
Adder
8.04
316254AC1-120 GEN1
Solar/Wind Harmer
0.262
961601AG1-000A GEN
Solar/Wind Harmer
12.564
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.176
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3146926FARMVIL
Solar/Wind Harmer
0.106
3146776BUCKING
Solar/Wind Harmer
0.061
972255AH1-712 GEN
Adder
84.412
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.993
971683AH1-343 GEN
Solar/Wind Harmer
5.591
970221AG2-151 GEN
Solar/Wind Harmer
8.062
316283AC2-100 C
Solar/Wind Harmer
0.29
3132273ORANGE
Solar/Wind Harmer
0.028
3141316ARNOLDS
Adder
0.324
3150331BIRCHWDA
Adder
21.287
3151761LOISA E
Adder
16.391
316170AC1-121 GEN2
Solar/Wind Harmer
0.131
972183AH1-676 GEN
Adder
128.276
3141196NOKESVL
Solar/Wind Helper
1.252
CPLELTFEXP_CPLE->PJM
CLTF
11.392
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.447
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.85
MECLTFEXP_MEC->PJM
CLTF
3.626
SIGELTFEXP_SIGE->PJM
CLTF
0.111
NYPJM->LTFIMP_NY
CLTF
3.261
LGEELTFEXP_LGEE->PJM
CLTF
1.336
WECLTFEXP_WEC->PJM
CLTF
0.644
LAGNLTFEXP_LAGN->PJM
CLTF
8.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.001
TVALTFEXP_TVA->PJM
CLTF
4.071

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.02 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5007.08
MW Contribution:1.07
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
73.177
3150411LDYSMT5
50/50
36.98
3150381LDYSMT2
50/50
35.391
972213AH1-691 GEN
50/50
5.987
972215AH1-692 GEN
50/50
5.987
963051AG1-154 GEN
50/50
4.605
3152261N ANNA2
50/50
14.366
970497AG2-320 GEN
50/50
25.942
3150401LDYSMT4
50/50
36.865
3150371LDYSMT1
50/50
35.621
3152251N ANNA1
50/50
14.367
972197AH1-683 GEN
50/50
5.757
972219AH1-694 GEN
50/50
4.145
315052AA1-145 CT2
50/50
2.014
3150391LDYSMT3
50/50
36.796
972195AH1-682 GEN
50/50
4.835
966881AG1-559 GEN
Solar/Wind Harmer
0.296
3142416OLDCHRC
Solar/Wind Harmer
0.639
3142416OLDCHRC
Solar/Wind Harmer
0.245
3143526WINTERP
Solar/Wind Harmer
1.255
3143096IRON208
Adder
1.011
3150851SPRUNCC
Adder
1.112
3142543TWELFTH
Solar/Wind Harmer
0.023
3143226MDLTHAN
Solar/Wind Harmer
0.24
944631AF1-128 GEN
Adder
114.169
316159AE1-175 C
Solar/Wind Harmer
0.204
970129AG2-093 GEN
Solar/Wind Harmer
6.704
316458AB2-190 GEN2
Solar/Wind Harmer
1.264
315671AE2-027_GEN
Solar/Wind Harmer
15.06
971069AG2-661 GEN
Solar/Wind Harmer
4.175
971647AH1-324 GEN
Solar/Wind Harmer
9.972
971317AH1-138 GEN
Solar/Wind Harmer
1.742
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3142433PROV 92
Solar/Wind Harmer
0.932
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
961611AG1-000B GEN
Solar/Wind Harmer
12.225
316294AC1-161 GEN
Solar/Wind Harmer
4.025
3151171GRAVELC
Adder
2.471
3145336SMITFLD
Solar/Wind Harmer
0.925
970659AG2-427 GEN
Solar/Wind Harmer
11.115
944591AF1-124 GEN
Solar/Wind Harmer
51.874
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.866
316381AD1-082 GEN
Solar/Wind Harmer
0.239
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.604
3141843SHACKLE
Adder
1.169
970661AG2-428 GEN
Solar/Wind Harmer
22.759
316072AD1-144
Solar/Wind Harmer
0.082
939411AE1-173 GEN
Solar/Wind Harmer
97.185
940641AE2-051 GEN
Solar/Wind Harmer
18.198
316388AE2-253 GEN
Solar/Wind Harmer
0.712
3146456SLIGO L269
Solar/Wind Harmer
0.227
316246AF1-032 C
Solar/Wind Harmer
0.102
316093AE2-104_GEN
Solar/Wind Harmer
3.787
3138133OCRAN
Solar/Wind Harmer
0.134
3146516WINFALL
Solar/Wind Harmer
0.717
3146516WINFALL
Solar/Wind Harmer
0.221
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
962861AG1-135 GEN
Solar/Wind Harmer
6.892
3130156CHOWAN
Solar/Wind Harmer
0.215
3141726DUNNSVL
Solar/Wind Harmer
0.848
3145663CRESWEL
Solar/Wind Harmer
0.589
971163AH1-040 GEN
Solar/Wind Harmer
16.833
3150351NORNECKC2
Adder
2.088
3143336POWHATN
Solar/Wind Harmer
3.678
970919AG2-571 GEN
Solar/Wind Harmer
7.253
3146206CASHIE
Solar/Wind Harmer
0.204
971547AH1-271 GEN
Solar/Wind Harmer
4.349
316023GEN1_S
Solar/Wind Harmer
0.456
970087AG2-069 GEN
Solar/Wind Harmer
16.254
3145893MURPHYS
Solar/Wind Harmer
0.811
3145893MURPHYS
Solar/Wind Harmer
0.902
3146173TUNIS
Solar/Wind Harmer
0.201
316337AD2-073 GEN
Solar/Wind Harmer
0.175
315051AA1-145 CT1
50/50
2.006
3142416OLDCHRC
Solar/Wind Harmer
2.384
970293AG2-193 GEN
Solar/Wind Harmer
2.591
3143096IRON208
Adder
1.011
3143096IRON208
Adder
0.991
3150861SPRUNCD
Adder
1.112
316473AC1-191 GEN
Solar/Wind Harmer
0.812
3142946ENON
Solar/Wind Harmer
0.08
970133AG2-095 GEN
Solar/Wind Harmer
2.274
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.245
315778AD1-151 GEN
Solar/Wind Harmer
18.787
965281AG1-393 GEN
Solar/Wind Harmer
2.505
315839AE2-212 C
Solar/Wind Harmer
0.002
3150921YORKTN3
Adder
5.862
3144216WINCHST
Adder
0.879
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
961611AG1-000B GEN
Solar/Wind Harmer
6.216
315773AC2-141 GEN
Solar/Wind Harmer
8.485
3151221GRAVEL6
Adder
16.891
3151171GRAVELC
Adder
3.25
3145336SMITFLD
Solar/Wind Harmer
0.093
315813AE1-149 C
Solar/Wind Harmer
12.335
3144536CHRHLND
Solar/Wind Harmer
0.034
970659AG2-427 GEN
Solar/Wind Harmer
2.431
944581AF1-123 GEN
Solar/Wind Harmer
51.69
944601AF1-125 GEN
Solar/Wind Harmer
50.894
3151101ELIZAR3
Adder
21.316
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.053
3141843SHACKLE
Adder
1.169
970661AG2-428 GEN
Solar/Wind Harmer
4.841
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
4.038
3146456SLIGO L269
Solar/Wind Harmer
0.227
971153AH1-033 GEN
Solar/Wind Harmer
2.621
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
0.22
962971AG1-146 GEN
Solar/Wind Harmer
3.508
3145273HOLLAND
Solar/Wind Harmer
0.164
970009AG2-005 GEN
Solar/Wind Harmer
1.624
3146376EDENTON
Solar/Wind Harmer
0.215
316404AE1-155 C
Solar/Wind Harmer
0.048
315614AA2-178 GEN
Solar/Wind Harmer
1.204
3150351NORNECKC2
Adder
2.123
971781AH1-399 GEN
Solar/Wind Harmer
0.275
316313AB2-026
Solar/Wind Harmer
0.13
316258AE1-075 C
Solar/Wind Harmer
0.156
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.126
971157AH1-035 GEN
Solar/Wind Harmer
2.481
315737AD1-076 GEN
Solar/Wind Harmer
2.651
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
970917AG2-570 GEN
Solar/Wind Harmer
18.132
3146206CASHIE
Solar/Wind Harmer
0.204
316365GEN2_N
Solar/Wind Harmer
0.456
3145893MURPHYS
Solar/Wind Harmer
0.34
3145893MURPHYS
Solar/Wind Harmer
0.203
957521AF2-046 GEN
Solar/Wind Harmer
15.061
961681AG1-008 GEN
Solar/Wind Harmer
15.061
3146173TUNIS
Solar/Wind Harmer
0.201
3156021HOLLOMANSOL
Solar/Wind Harmer
0.911
316463AE2-346 GEN
Solar/Wind Harmer
0.172
316140AB2-099
Solar/Wind Harmer
0.071
962331AG1-082 GEN
Solar/Wind Harmer
2.134
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
313506AB2-031 GEN
Solar/Wind Harmer
0.605
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.768
3145796HORNRTN
Solar/Wind Harmer
0.192
3147043LAWRENC
Solar/Wind Harmer
0.115
3141906WESTMOR
Solar/Wind Harmer
0.076
3147666LOUISA
Solar/Wind Harmer
0.435
316478AD1-087 GEN
Solar/Wind Harmer
0.657
316486AD2-202 GEN
Solar/Wind Harmer
0.193
316210AC1-098 GEN
Solar/Wind Harmer
1.741
3145933PARMELE
Solar/Wind Harmer
0.187
966801AG1-551 GEN
Solar/Wind Harmer
2.184
972189AH1-679 GEN
Adder
4.237
316312AB1-027
Solar/Wind Harmer
0.44
316233AE1-074 FULL
Solar/Wind Harmer
0.193
971281AH1-106 GEN
Solar/Wind Harmer
3.35
971283AH1-107 GEN
Solar/Wind Harmer
3.35
971285AH1-108 GEN
Adder
1.819
315976AC1-164 GENA
Solar/Wind Harmer
24.88
316169AC1-164_GENC
Solar/Wind Harmer
21.494
315975AC1-164 GENB
Solar/Wind Harmer
0.736
316132AB2-190 GEN1
Solar/Wind Harmer
1.264
316369SG1_INVT
Solar/Wind Harmer
0.009
971167AH1-042 GEN
Solar/Wind Harmer
20.755
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
972265AH1-717 GEN
Adder
18.039
3151201GRAVEL4
Adder
16.911
3151191GRAVEL3
Adder
16.697
3151211GRAVEL5
Adder
16.697
971445AH1-216 GEN
Solar/Wind Harmer
16.292
3143316POE
Solar/Wind Harmer
0.915
3143873LANEXA
Solar/Wind Harmer
0.139
3138283WHITEMARSH
Solar/Wind Harmer
0.053
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
21.046
3151091ELIZAR2
Adder
20.681
3152611GOSPORTB
Adder
2.923
3152621GOSPORTC
Adder
2.481
3152601GOSPORTA
Adder
2.288
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.781
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
957871AF2-081 GEN
Solar/Wind Harmer
11.31
3141873WAN 176
Solar/Wind Harmer
0.045
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.155
316311AC2-079 GEN
Solar/Wind Harmer
6.513
319010AE1-072 C
Solar/Wind Harmer
1.141
3146406KITTY HAWK
Solar/Wind Harmer
0.028
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.545
3141913WHIT STONE
Solar/Wind Harmer
0.224
313526AB2-022
Solar/Wind Harmer
0.121
3138133OCRAN
Solar/Wind Harmer
0.067
3146486SUNBURY
Solar/Wind Harmer
0.224
3146486SUNBURY
Solar/Wind Harmer
0.224
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.616
3145176PASQUOTANK
Solar/Wind Harmer
0.138
3145683EARLEYS
Solar/Wind Harmer
0.199
316336AC2-165 C
Solar/Wind Harmer
0.008
960081AF2-299 GEN
Solar/Wind Harmer
1.901
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
957481AF2-042 GEN
Solar/Wind Harmer
52.064
316011AB1-132 GEN
Solar/Wind Harmer
3.547
962571AG1-106 GEN
Solar/Wind Harmer
2.776
3145823KELFORD
Solar/Wind Harmer
0.195
316190AA2-174 GEN
Solar/Wind Harmer
0
316174AB2-169 GEN
Solar/Wind Harmer
0.005
971795AH1-408 GEN
Solar/Wind Harmer
12.912
3145783HORNRTN
Solar/Wind Harmer
0.192
3145796HORNRTN
Solar/Wind Harmer
0.634
3145796HORNRTN
Solar/Wind Harmer
0.192
3147043LAWRENC
Adder
1.734
315693AD1-088 GEN
Solar/Wind Harmer
9.193
962491AG1-098 GEN
Solar/Wind Harmer
10.897
3147666LOUISA
Solar/Wind Harmer
0.757
316212AC1-099_GEN
Solar/Wind Harmer
0.971
3146293MARTNCO
Solar/Wind Harmer
0.174
316192AB2-158 GEN
Solar/Wind Harmer
1.044
315673AE1-157 GEN
Solar/Wind Harmer
17.789
957411AF2-035 GEN
Solar/Wind Harmer
10.93
970317AG2-208 GEN
Solar/Wind Harmer
10.126
3142296MT RD221
Adder
0.793
3142366NRTHEST
Adder
0.798
3150691DARBY 3
Adder
17.545
3150701DARBY 4
Adder
17.505
3150681DARBY 2
Adder
17.484
3150671DARBY 1
Adder
17.464
316075AC2-137 C
Solar/Wind Harmer
0.066
3143526WINTERP
Solar/Wind Harmer
1.255
971223AH1-071 GEN
Solar/Wind Harmer
2.567
966871AG1-558 GEN
Solar/Wind Harmer
0.278
3142946ENON
Solar/Wind Harmer
0.024
944641AF1-129 GEN
Adder
113.139
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.263
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.043
3150991CHESPKB
Adder
2.404
3150991CHESPKB
Adder
2.347
970657AG2-426 GEN
Solar/Wind Harmer
8.03
970657AG2-426 GEN
Solar/Wind Harmer
1.684
316316AC1-027 C
Solar/Wind Harmer
0.22
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.912
3145506HICKORY
Solar/Wind Harmer
0.547
3145506HICKORY
Solar/Wind Harmer
0.137
316339AD2-160 GEN
Solar/Wind Harmer
0.369
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.127
3137176SLIGO L2192
Solar/Wind Harmer
0.902
3146456SLIGO L269
Solar/Wind Harmer
4.012
3130086AYDLETT
Solar/Wind Harmer
0.905
3146386ELIZ CT
Solar/Wind Harmer
0.224
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
0.22
3146626S HERTFORD
Solar/Wind Harmer
0.22
3144356SAPONY
Solar/Wind Harmer
1.836
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.957
3146376EDENTON
Solar/Wind Harmer
0.957
958261AF2-120 GEN
Solar/Wind Harmer
7.097
972185AH1-677 GEN
Adder
11.991
972187AH1-678 GEN
Adder
6.016
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.193
3150341NORNECKC1
Adder
2.176
316468AD1-105 GEN
Solar/Wind Harmer
-0.068
970933AG2-581 GEN
Solar/Wind Harmer
16.641
316065AD1-022 GEN
Solar/Wind Harmer
9.423
3145893MURPHYS
Solar/Wind Harmer
1.358
3145893MURPHYS
Solar/Wind Harmer
0.365
3146173TUNIS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.201
316181AB2-040 GEN
Solar/Wind Harmer
0.284
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.117
970099AG2-077 GEN
Solar/Wind Harmer
20.826
316426AA2-053 GEN
Solar/Wind Harmer
0.657
3145593CAROLNA
Solar/Wind Harmer
0.193
3145593CAROLNA
Solar/Wind Harmer
0.193
966811AG1-552 GEN
Solar/Wind Harmer
2.098
3145593CAROLNA
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
3.419
3145783HORNRTN
Solar/Wind Harmer
2.735
3145783HORNRTN
Solar/Wind Harmer
0.855
3145783HORNRTN
Solar/Wind Harmer
0.342
3145796HORNRTN
Solar/Wind Harmer
0.576
3145933PARMELE
Solar/Wind Harmer
0.375
3145933PARMELE
Solar/Wind Harmer
0.187
316274AC1-208 GEN
Solar/Wind Harmer
0.967
3141783LANCAST
Solar/Wind Harmer
0.133
3141783LANCAST
Solar/Wind Harmer
0.089
316315AB2-025 C
Solar/Wind Harmer
0.177
962981AG1-147 GEN
Solar/Wind Harmer
8.186
941031AE2-094 GEN
Solar/Wind Harmer
40.356
944011AF1-069 GEN
Solar/Wind Harmer
13.186
315814AE2-033 C
Solar/Wind Harmer
17.302
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970327AG2-215 GEN
Solar/Wind Harmer
7.138
970673AG2-436 GEN
Solar/Wind Harmer
45.972
970673AG2-436 GEN
Solar/Wind Harmer
30.648
3130156CHOWAN
Solar/Wind Harmer
0.215
3130156CHOWAN
Solar/Wind Harmer
0.215
971967AH1-528 GEN
Solar/Wind Harmer
34.067
315816AE2-034 GEN
Solar/Wind Harmer
0.903
3141813NORNECK
Solar/Wind Harmer
0.209
3130546PLYMOUTH
Solar/Wind Harmer
0.207
315732AD1-074 GEN1
Solar/Wind Harmer
1.184
315733AD1-074 GEN2
Solar/Wind Harmer
1.184
315735AD1-075 GEN1
Solar/Wind Harmer
0.593
965291AG1-394 GEN
Solar/Wind Harmer
0.91
3146206CASHIE
Solar/Wind Harmer
0.204
970601AG2-382 GEN
Solar/Wind Harmer
7.61
970085AG2-068 GEN
Solar/Wind Harmer
10.836
970581AG2-369 GEN
Solar/Wind Harmer
9.319
3145893MURPHYS
Solar/Wind Harmer
0.548
3145893MURPHYS
Solar/Wind Harmer
0.203
3145513AHOSKIE
Solar/Wind Harmer
0.418
3145513AHOSKIE
Solar/Wind Harmer
0.2
3145683EARLEYS
Solar/Wind Harmer
0.398
3145683EARLEYS
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.199
3146043SEABORD
Solar/Wind Harmer
0.198
315607AA1-063A GEN
Solar/Wind Harmer
0.404
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
21.462
3137643SOCKMAN
Solar/Wind Harmer
0.777
3145796HORNRTN
Solar/Wind Harmer
0.615
3145796HORNRTN
Solar/Wind Harmer
0.077
3146033SCOT NK
Solar/Wind Harmer
0.764
316223AC1-118
Solar/Wind Harmer
0.137
970831AG2-522 GEN
Solar/Wind Harmer
7.881
316005AA1-067
Solar/Wind Harmer
0.197
3145746EVERETS
Solar/Wind Harmer
0.73
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
970181AG2-120 GEN
Solar/Wind Harmer
2.284
957861AF2-080 GEN
Solar/Wind Harmer
7.776
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.178
3145573BETHELC
Solar/Wind Harmer
0.178
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.956
3144303KENBRDG
Solar/Wind Harmer
0.141
970683AG2-441 GEN
Solar/Wind Harmer
11.694
970681AG2-440 GEN
Solar/Wind Harmer
9.355
946301AF1-294 GEN
Solar/Wind Harmer
3.451
961791AG1-021 GEN
Solar/Wind Harmer
1.679
315657AE1-056 GEN
Solar/Wind Harmer
6.021
971741AH1-377 GEN
Solar/Wind Harmer
18.163
970301AG2-198 GEN
Solar/Wind Harmer
7.705
939181AE1-148 GEN
Solar/Wind Harmer
8.56
3145493TOT1
Solar/Wind Harmer
0.412
3145453TOT5
Solar/Wind Harmer
0.247
3145603CNETO
Solar/Wind Harmer
0.165
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.506
971775AH1-396 GEN
Solar/Wind Harmer
0.281
958211AF2-115 GEN
Solar/Wind Harmer
2.099
963191AG1-168 GEN
Solar/Wind Harmer
0.7
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
13.206
971845AH1-439 GEN
Solar/Wind Harmer
7.514
316118AC1-105 GEN
Solar/Wind Harmer
0.425
972193AH1-681 GEN
Adder
3.717
3147173SINAI
Solar/Wind Harmer
0.161
3147243WELCO
Solar/Wind Harmer
0.101
972205AH1-687 GEN
Adder
6.67
970865AG2-541 GEN
Solar/Wind Harmer
4.995
971447AH1-217 GEN
Solar/Wind Harmer
4.355
316123AC1-075 GEN
Solar/Wind Harmer
0.181
970165AG2-112 GEN
Solar/Wind Harmer
1.074
970163AG2-111 GEN
Solar/Wind Harmer
1.025
270494AE1-108_GEN
Solar/Wind Harmer
1.568
316411AF1-147_GEN1
Solar/Wind Helper
0.784
316415AF1-147_GEN2
Solar/Wind Helper
0.784
3138216PACIFIC
Solar/Wind Helper
0.038
3144293JTRSVLE
Adder
0.557
3144293JTRSVLE
Adder
0.469
3147133PAMPLIN
Solar/Wind Harmer
0.174
3147133PAMPLIN
Solar/Wind Harmer
0.139
961601AG1-000A GEN
Solar/Wind Harmer
3.1
316263AC1-034 GEN
Solar/Wind Harmer
6.622
962561AG1-105 GEN
Solar/Wind Harmer
8.133
964791AG1-342 GEN
Solar/Wind Harmer
3.227
3146843MT LREL
Solar/Wind Harmer
0.168
3146843MT LREL
Solar/Wind Harmer
0.168
3146776BUCKING
Solar/Wind Harmer
0.66
3146776BUCKING
Solar/Wind Harmer
0.053
971489AH1-241 GEN
Solar/Wind Harmer
7.84
316222AC1-221 GEN
Solar/Wind Harmer
0.61
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.812
316447AC1-158 HLD
Solar/Wind Helper
4.161
316129AC1-054 GEN
Solar/Wind Harmer
0.691
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
971065AG2-659 GEN
Solar/Wind Harmer
7.805
315722AD1-056 GEN
Solar/Wind Harmer
1.154
316494AC1-189 GEN
Solar/Wind Harmer
0.609
315687AD1-152 GEN
Solar/Wind Harmer
0.006
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.178
3145493TOT1
Solar/Wind Harmer
0.79
3146233WITAKRS
Solar/Wind Harmer
0.707
316237AB2-079_GEN
Solar/Wind Harmer
0.001
972135AH1-637 GEN
Solar/Wind Harmer
1.506
970685AG2-442 GEN
Solar/Wind Harmer
13.097
970937AG2-583 GEN
Solar/Wind Harmer
10.754
963171AG1-166 GEN
Solar/Wind Harmer
0.933
971563AH1-280 GEN
Solar/Wind Harmer
1.866
3144293JTRSVLE
Adder
0.557
3145543BTLEBRO
Solar/Wind Harmer
0.174
3145543BTLEBRO
Solar/Wind Harmer
0.139
316359AB2-059 GEN
Solar/Wind Harmer
0.626
316049AB1-081 GEN
Solar/Wind Harmer
0.997
3142053HEARTS
Solar/Wind Harmer
0.307
3146926FARMVIL
Solar/Wind Harmer
0.104
970401AG2-262 GEN
Solar/Wind Harmer
0.986
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.066
972277AH1-723 GEN
Adder
96.942
972003AH1-546 GEN
Solar/Wind Harmer
6.703
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
970737AG2-469 GEN
Solar/Wind Harmer
7.78
315724AD1-057 GEN
Solar/Wind Harmer
0.684
316327AA2-057 GEN
Solar/Wind Harmer
0.273
970909AG2-566 GEN
Solar/Wind Harmer
1.926
3146073TAR RVR
Solar/Wind Harmer
0.178
3146083TARBORO
Solar/Wind Harmer
0.178
3146233WITAKRS
Solar/Wind Harmer
0.891
3146233WITAKRS
Solar/Wind Harmer
0.121
3138543CONSLDL
Solar/Wind Harmer
0.117
316131AB2-060 GEN
Solar/Wind Harmer
0.557
964241AG1-285 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
1.432
970257AG2-171 GEN
Solar/Wind Harmer
5.629
959311AF2-222 GEN
Solar/Wind Harmer
15.624
963181AG1-167 GEN
Solar/Wind Harmer
0.7
3144293JTRSVLE
Adder
0.557
3147133PAMPLIN
Solar/Wind Harmer
0.548
971193AH1-056 GEN
Solar/Wind Harmer
10.629
961601AG1-000A GEN
Solar/Wind Harmer
12.399
3145543BTLEBRO
Solar/Wind Harmer
0.174
3145543BTLEBRO
Solar/Wind Harmer
0.174
971623AH1-311 GEN
Solar/Wind Harmer
0.349
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.104
3146776BUCKING
Solar/Wind Harmer
0.059
972255AH1-712 GEN
Adder
83.19
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.893
971683AH1-343 GEN
Solar/Wind Harmer
5.511
970221AG2-151 GEN
Solar/Wind Harmer
7.84
316283AC2-100 C
Solar/Wind Harmer
0.286
3141316ARNOLDS
Adder
0.322
3150331BIRCHWDA
Adder
21.148
316044AC1-158 PL1
Solar/Wind Helper
1.891
316450AC1-158 RIC
Solar/Wind Helper
0.504
3141196NOKESVL
Solar/Wind Helper
1.226
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.568
3147623JAMES R
Solar/Wind Harmer
0.341
316045AC1-158 PL2
Solar/Wind Helper
6.052
316006AB2-029 C
Solar/Wind Helper
0.11
CPLELTFEXP_CPLE->PJM
CLTF
11.252
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.535
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.991
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.831
MECLTFEXP_MEC->PJM
CLTF
3.667
SIGELTFEXP_SIGE->PJM
CLTF
0.112
NYPJM->LTFIMP_NY
CLTF
3.144
LGEELTFEXP_LGEE->PJM
CLTF
1.356
WECLTFEXP_WEC->PJM
CLTF
0.657
LAGNLTFEXP_LAGN->PJM
CLTF
8.007
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.726
TVALTFEXP_TVA->PJM
CLTF
4.059

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:146.98 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3589.45
MW Contribution:1.06
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
238.379
3151081ELIZAR1
50/50
34.239
3151091ELIZAR2
50/50
33.645
941591AE2-156 GEN
50/50
31.25
3152611GOSPORTB
50/50
4.742
3152621GOSPORTC
50/50
4.025
3152601GOSPORTA
50/50
3.713
957871AF2-081 GEN
Solar/Wind Harmer
17.29
319010AE1-072 C
Solar/Wind Harmer
1.74
3146406KITTY HAWK
Solar/Wind Harmer
0.043
3138283WHITEMARSH
Solar/Wind Harmer
0.08
316305AF2-043 C
Solar/Wind Harmer
0.003
315976AC1-164 GENA
Solar/Wind Harmer
35.232
316169AC1-164_GENC
Solar/Wind Harmer
30.437
315975AC1-164 GENB
Solar/Wind Harmer
1.042
313526AB2-022
Solar/Wind Harmer
0.184
316321Z2-027
Solar/Wind Harmer
0.062
3146396TANGLEW
Solar/Wind Harmer
0.926
3145176PASQUOTANK
Solar/Wind Harmer
0.208
3146486SUNBURY
Solar/Wind Harmer
0.335
3146486SUNBURY
Solar/Wind Harmer
0.335
971445AH1-216 GEN
Solar/Wind Harmer
23.372
315835AF2-110_GEN
Solar/Wind Harmer
2.259
316314AB2-024 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
24.957
3151201GRAVEL4
Adder
23.396
3151191GRAVEL3
Adder
23.099
3151211GRAVEL5
Adder
23.099
315611Z1-036_GEN2
Solar/Wind Harmer
0.003
316059AD1-063 C
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.064
315662AE1-191 GEN
Solar/Wind Harmer
0.01
315666AE1-190 GEN
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.314
3130156CHOWAN
Solar/Wind Harmer
0.314
970189AG2-124 GEN
Solar/Wind Harmer
9.301
316311AC2-079 GEN
Solar/Wind Harmer
8.93
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.213
3141913WHIT STONE
Solar/Wind Harmer
0.31
3138133OCRAN
Solar/Wind Harmer
0.092
3143873LANEXA
Solar/Wind Harmer
0.185
3141783LANCAST
Solar/Wind Harmer
0.182
3141783LANCAST
Solar/Wind Harmer
0.122
315816AE2-034 GEN
Solar/Wind Harmer
1.293
962981AG1-147 GEN
Solar/Wind Harmer
11.004
3130546PLYMOUTH
Solar/Wind Harmer
0.291
316369SG1_INVT
Solar/Wind Harmer
0.011
315732AD1-074 GEN1
Solar/Wind Harmer
1.665
315733AD1-074 GEN2
Solar/Wind Harmer
1.665
315735AD1-075 GEN1
Solar/Wind Harmer
0.833
970327AG2-215 GEN
Solar/Wind Harmer
9.499
3146206CASHIE
Solar/Wind Harmer
0.283
970601AG2-382 GEN
Solar/Wind Harmer
10.56
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
971167AH1-042 GEN
Solar/Wind Harmer
24.515
965291AG1-394 GEN
Solar/Wind Harmer
1.225
941031AE2-094 GEN
Solar/Wind Harmer
50.437
944011AF1-069 GEN
Solar/Wind Harmer
16.48
316132AB2-190 GEN1
Solar/Wind Harmer
1.466
3145893MURPHYS
Solar/Wind Harmer
0.736
3145893MURPHYS
Solar/Wind Harmer
0.273
3145513AHOSKIE
Solar/Wind Harmer
0.561
3145513AHOSKIE
Solar/Wind Harmer
0.268
970673AG2-436 GEN
Solar/Wind Harmer
57.198
970673AG2-436 GEN
Solar/Wind Harmer
38.132
3145683EARLEYS
Solar/Wind Harmer
0.534
3145683EARLEYS
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.267
3141813NORNECK
Solar/Wind Harmer
0.265
971967AH1-528 GEN
Solar/Wind Harmer
41.999
3146043SEABORD
Solar/Wind Harmer
0.257
315607AA1-063A GEN
Solar/Wind Harmer
0.522
316315AB2-025 C
Solar/Wind Harmer
0.206
315814AE2-033 C
Solar/Wind Harmer
20.097
970085AG2-068 GEN
Solar/Wind Harmer
13.326
970581AG2-369 GEN
Solar/Wind Harmer
11.461
3146033SCOT NK
Solar/Wind Harmer
0.989
3143316POE
Solar/Wind Harmer
0.966
315652AC1-086 GEN
Solar/Wind Harmer
26.799
3137643SOCKMAN
Solar/Wind Harmer
0.964
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3145796HORNRTN
Solar/Wind Harmer
0.766
3145796HORNRTN
Solar/Wind Harmer
0.096
316005AA1-067
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.951
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
970181AG2-120 GEN
Solar/Wind Harmer
2.976
957861AF2-080 GEN
Solar/Wind Harmer
9.959
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.224
3145573BETHELC
Solar/Wind Harmer
0.224
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
9.415
316223AC1-118
Solar/Wind Harmer
0.153
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.071
3144303KENBRDG
Solar/Wind Harmer
0.146
316118AC1-105 GEN
Solar/Wind Harmer
0.468
3147173SINAI
Solar/Wind Harmer
0.178
3150991CHESPKB
50/50
3.902
3150991CHESPKB
50/50
3.808
316185AD1-033 GEN
Solar/Wind Harmer
0.01
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.337
316036AC1-147 C
Solar/Wind Harmer
0.065
3145506HICKORY
Solar/Wind Harmer
1.401
3145506HICKORY
Solar/Wind Harmer
0.841
3145506HICKORY
Solar/Wind Harmer
0.21
316339AD2-160 GEN
Solar/Wind Harmer
0.564
316018AA1-139 ULT2
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.194
3137176SLIGO L2192
Solar/Wind Harmer
1.377
3146456SLIGO L269
Solar/Wind Harmer
6.122
3130086AYDLETT
Solar/Wind Harmer
1.379
3146386ELIZ CT
Solar/Wind Harmer
0.339
316236AE1-162_GEN
Solar/Wind Harmer
0.003
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.33
3146516WINFALL
Solar/Wind Harmer
0.33
3146516WINFALL
Solar/Wind Harmer
0.33
3146626S HERTFORD
Solar/Wind Harmer
0.326
3146626S HERTFORD
Solar/Wind Harmer
0.326
3146376EDENTON
Solar/Wind Harmer
1.396
3146376EDENTON
Solar/Wind Harmer
1.396
315742AE1-103 GEN
Solar/Wind Harmer
0.004
316033AB2-134 GEN
Solar/Wind Harmer
0.017
315697AD1-025 GEN
Solar/Wind Harmer
0.327
3142946ENON
Solar/Wind Harmer
0.028
316065AD1-022 GEN
Solar/Wind Harmer
13.139
970657AG2-426 GEN
Solar/Wind Harmer
9.959
970657AG2-426 GEN
Solar/Wind Harmer
2.088
958261AF2-120 GEN
Solar/Wind Harmer
9.287
316075AC2-137 C
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
1.826
3145893MURPHYS
Solar/Wind Harmer
0.491
3146173TUNIS
Solar/Wind Harmer
0.27
3146173TUNIS
Solar/Wind Harmer
0.27
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.78
3150341NORNECKC1
Adder
2.758
972185AH1-677 GEN
Adder
14.884
972187AH1-678 GEN
Adder
7.445
3144356SAPONY
Solar/Wind Harmer
2.128
970933AG2-581 GEN
Solar/Wind Harmer
20.23
3145933PARMELE
Solar/Wind Harmer
0.496
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
316426AA2-053 GEN
Solar/Wind Harmer
0.834
3145593CAROLNA
Solar/Wind Harmer
0.242
3145593CAROLNA
Solar/Wind Harmer
0.242
966811AG1-552 GEN
Solar/Wind Harmer
2.63
3145593CAROLNA
Solar/Wind Harmer
0.302
3145783HORNRTN
Solar/Wind Harmer
4.289
3145783HORNRTN
Solar/Wind Harmer
3.432
3145783HORNRTN
Solar/Wind Harmer
1.072
3145783HORNRTN
Solar/Wind Harmer
0.429
316181AB2-040 GEN
Solar/Wind Harmer
0.349
3145796HORNRTN
Solar/Wind Harmer
0.718
316274AC1-208 GEN
Solar/Wind Harmer
1.219
970099AG2-077 GEN
Solar/Wind Harmer
24.387
3145493TOT1
Solar/Wind Harmer
0.519
3145453TOT5
Solar/Wind Harmer
0.311
3145603CNETO
Solar/Wind Harmer
0.208
961601AG1-000A GEN
Solar/Wind Harmer
3.829
316263AC1-034 GEN
Solar/Wind Harmer
8.179
316240AF1-291 C
Solar/Wind Harmer
0.002
944641AF1-129 GEN
Adder
100.049
939181AE1-148 GEN
Solar/Wind Harmer
9.766
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
8.948
971741AH1-377 GEN
Solar/Wind Harmer
18.452
964791AG1-342 GEN
Solar/Wind Harmer
3.551
3146843MT LREL
Solar/Wind Harmer
0.185
3146843MT LREL
Solar/Wind Harmer
0.185
3150691DARBY 3
Adder
13.256
3150701DARBY 4
Adder
13.225
3150681DARBY 2
Adder
13.21
3150671DARBY 1
Adder
13.194
970323AG2-213 GEN
Solar/Wind Harmer
7.78
971775AH1-396 GEN
Solar/Wind Harmer
0.292
316034AC1-036 C
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.54
971223AH1-071 GEN
Solar/Wind Harmer
1.839
958211AF2-115 GEN
Solar/Wind Harmer
2.062
963191AG1-168 GEN
Solar/Wind Harmer
0.687
3144293JTRSVLE
Adder
0.547
3144293JTRSVLE
Adder
0.461
3143526WINTERP
Solar/Wind Harmer
0.885
3152331SURRY 2
50/50
17.341
971353AH1-157 GEN
50/50
32.652
970017AG2-010 GEN
50/50
24.601
3150981CHESPKA
50/50
4.651
316294AC1-161 GEN
Solar/Wind Harmer
6.621
971317AH1-138 GEN
Solar/Wind Harmer
2.751
3138126ROCKLANDING
Solar/Wind Harmer
0.168
316159AE1-175 C
Solar/Wind Harmer
0.315
944591AF1-124 GEN
Solar/Wind Harmer
80.715
316375AC2-012 GEN
Solar/Wind Harmer
0.009
316388AE2-253 GEN
Solar/Wind Harmer
1.09
3146456SLIGO L269
Solar/Wind Harmer
0.346
316246AF1-032 C
Solar/Wind Harmer
0.154
316072AD1-144
Solar/Wind Harmer
0.123
3145336SMITFLD
Solar/Wind Harmer
1.331
3146516WINFALL
Solar/Wind Harmer
1.07
3146516WINFALL
Solar/Wind Harmer
0.33
316093AE2-104_GEN
Solar/Wind Harmer
5.536
3151171GRAVELC
Adder
3.419
315800Z1-036_GEN1
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
0.064
939411AE1-173 GEN
Solar/Wind Harmer
134.654
3130156CHOWAN
Solar/Wind Harmer
0.314
971777AH1-397 GEN
Solar/Wind Harmer
0.828
3141843SHACKLE
Adder
1.603
961611AG1-000B GEN
Solar/Wind Harmer
16.242
3138133OCRAN
Solar/Wind Harmer
0.185
940641AE2-051 GEN
Solar/Wind Harmer
24.257
3145663CRESWEL
Solar/Wind Harmer
0.843
971163AH1-040 GEN
Solar/Wind Harmer
24.101
971647AH1-324 GEN
Solar/Wind Harmer
12.816
970661AG2-428 GEN
Solar/Wind Harmer
28.811
971069AG2-661 GEN
Solar/Wind Harmer
5.046
962861AG1-135 GEN
Solar/Wind Harmer
9.061
3146206CASHIE
Solar/Wind Harmer
0.283
971547AH1-271 GEN
Solar/Wind Harmer
6.034
3142433PROV 92
Solar/Wind Harmer
1.129
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
316381AD1-082 GEN
Solar/Wind Harmer
0.293
970659AG2-427 GEN
Solar/Wind Harmer
13.452
316458AB2-190 GEN2
Solar/Wind Harmer
1.466
3145893MURPHYS
Solar/Wind Harmer
1.091
3145893MURPHYS
Solar/Wind Harmer
1.213
3141726DUNNSVL
Solar/Wind Harmer
1.09
970129AG2-093 GEN
Solar/Wind Harmer
7.721
3146173TUNIS
Solar/Wind Harmer
0.27
3145963POPLR C
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
2.647
944631AF1-128 GEN
Adder
125.685
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3146263WOODLND
Solar/Wind Harmer
0.26
3145823KELFORD
Solar/Wind Harmer
0.257
970919AG2-571 GEN
Solar/Wind Harmer
8.925
970087AG2-069 GEN
Solar/Wind Harmer
19.989
3146293MARTNCO
Solar/Wind Harmer
0.23
316190AA2-174 GEN
Solar/Wind Harmer
0
316023GEN1_S
Solar/Wind Harmer
0.553
316011AB1-132 GEN
Solar/Wind Harmer
4.429
962571AG1-106 GEN
Solar/Wind Harmer
3.466
3145783HORNRTN
Solar/Wind Harmer
0.241
316337AD2-073 GEN
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.79
3145796HORNRTN
Solar/Wind Harmer
0.239
316212AC1-099_GEN
Solar/Wind Harmer
1.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
960081AF2-299 GEN
Solar/Wind Harmer
2.29
316494AC1-189 GEN
Solar/Wind Harmer
0.78
971795AH1-408 GEN
Solar/Wind Harmer
15.293
957481AF2-042 GEN
Solar/Wind Harmer
60.968
315671AE2-027_GEN
Solar/Wind Harmer
14.563
315722AD1-056 GEN
Solar/Wind Harmer
1.431
3147043LAWRENC
Adder
2.037
961671AG1-007 GEN
Solar/Wind Harmer
0.034
3146083TARBORO
Solar/Wind Harmer
0.224
3145493TOT1
Solar/Wind Harmer
0.996
3146233WITAKRS
Solar/Wind Harmer
0.879
316129AC1-054 GEN
Solar/Wind Harmer
0.821
315693AD1-088 GEN
Solar/Wind Harmer
10.427
971065AG2-659 GEN
Solar/Wind Harmer
9.224
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.172
316359AB2-059 GEN
Solar/Wind Harmer
0.773
316049AB1-081 GEN
Solar/Wind Harmer
1.232
3142053HEARTS
Solar/Wind Harmer
0.379
962491AG1-098 GEN
Solar/Wind Harmer
12.277
3143096IRON208
Adder
0.898
315687AD1-152 GEN
Solar/Wind Harmer
0.007
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.018
970401AG2-262 GEN
Solar/Wind Harmer
1.085
3150851SPRUNCC
Adder
0.82
970685AG2-442 GEN
Solar/Wind Harmer
13.21
972135AH1-637 GEN
Solar/Wind Harmer
1.474
3143226MDLTHAN
Solar/Wind Harmer
0.172
963171AG1-166 GEN
Solar/Wind Harmer
0.916
971563AH1-280 GEN
Solar/Wind Harmer
1.832
3144293JTRSVLE
Adder
0.547
3143526WINTERP
Solar/Wind Harmer
0.885
3150921YORKTN3
50/50
9.838
3144216WINCHST
50/50
1.454
3151101ELIZAR3
50/50
34.678
3151161SURRY 1
50/50
12.347
315773AC2-141 GEN
Solar/Wind Harmer
13.957
316382AG1-145 C
Solar/Wind Harmer
0.003
944581AF1-123 GEN
Solar/Wind Harmer
80.429
944601AF1-125 GEN
Solar/Wind Harmer
79.19
3144873MCLAUGH
Solar/Wind Harmer
0.009
3144536CHRHLND
Solar/Wind Harmer
0.052
3146456SLIGO L269
Solar/Wind Harmer
0.346
971153AH1-033 GEN
Solar/Wind Harmer
3.999
316320Y1-086
Solar/Wind Harmer
0.002
3145336SMITFLD
Solar/Wind Harmer
0.133
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.33
3146626S HERTFORD
Solar/Wind Harmer
0.326
3151221GRAVEL6
Adder
23.369
3151171GRAVELC
Adder
4.496
3141766HARMONY
Solar/Wind Harmer
4.28
316156AD2-030 GEN
Solar/Wind Harmer
0.236
3141873WAN 176
Solar/Wind Harmer
5.657
316280AD1-041 GEN
Solar/Wind Harmer
0.006
3146376EDENTON
Solar/Wind Harmer
0.314
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.603
3145273HOLLAND
Solar/Wind Harmer
0.235
961611AG1-000B GEN
Solar/Wind Harmer
8.258
315614AA2-178 GEN
Solar/Wind Harmer
1.724
962971AG1-146 GEN
Solar/Wind Harmer
4.716
971157AH1-035 GEN
Solar/Wind Harmer
3.498
315737AD1-076 GEN
Solar/Wind Harmer
3.727
970661AG2-428 GEN
Solar/Wind Harmer
6.128
970009AG2-005 GEN
Solar/Wind Harmer
2.161
3142946ENON
Solar/Wind Harmer
0.096
315778AD1-151 GEN
Solar/Wind Harmer
22.705
3146206CASHIE
Solar/Wind Harmer
0.283
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
316083AB2-161 GEN
Solar/Wind Harmer
0.004
316404AE1-155 C
Solar/Wind Harmer
0.063
970659AG2-427 GEN
Solar/Wind Harmer
2.943
3156081AA2-088 GEN
Solar/Wind Harmer
0.007
3156021HOLLOMANSOL
Solar/Wind Harmer
1.24
3145893MURPHYS
Solar/Wind Harmer
0.457
3145893MURPHYS
Solar/Wind Harmer
0.273
957521AF2-046 GEN
Solar/Wind Harmer
20.241
961681AG1-008 GEN
Solar/Wind Harmer
20.241
970129AG2-093 GEN
Solar/Wind Harmer
16.408
3146173TUNIS
Solar/Wind Harmer
0.27
316463AE2-346 GEN
Solar/Wind Harmer
0.231
316140AB2-099
Solar/Wind Harmer
0.096
962331AG1-082 GEN
Solar/Wind Harmer
2.864
3145963POPLR C
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
2.691
315813AE1-149 C
Solar/Wind Harmer
13.997
3146263WOODLND
Solar/Wind Harmer
0.26
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.257
970133AG2-095 GEN
Solar/Wind Harmer
2.439
970917AG2-570 GEN
Solar/Wind Harmer
22.313
3145933PARMELE
Solar/Wind Harmer
0.248
966801AG1-551 GEN
Solar/Wind Harmer
2.89
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
316365GEN2_N
Solar/Wind Harmer
0.553
313506AB2-031 GEN
Solar/Wind Harmer
0.743
3145796HORNRTN
Solar/Wind Harmer
0.958
3145796HORNRTN
Solar/Wind Harmer
0.239
316210AC1-098 GEN
Solar/Wind Harmer
2.222
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
965281AG1-393 GEN
Solar/Wind Harmer
2.451
970293AG2-193 GEN
Solar/Wind Harmer
2.439
316327AA2-057 GEN
Solar/Wind Harmer
0.342
315724AD1-057 GEN
Solar/Wind Harmer
0.848
3147043LAWRENC
Solar/Wind Harmer
0.135
315839AE2-212 C
Solar/Wind Harmer
0.002
3146073TAR RVR
Solar/Wind Harmer
0.224
3146083TARBORO
Solar/Wind Harmer
0.224
3146233WITAKRS
Solar/Wind Harmer
1.108
3146233WITAKRS
Solar/Wind Harmer
0.15
3138543CONSLDL
Solar/Wind Harmer
0.145
316478AD1-087 GEN
Solar/Wind Harmer
0.759
316486AD2-202 GEN
Solar/Wind Harmer
0.223
961601AG1-000A GEN
Solar/Wind Harmer
15.318
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.215
971623AH1-311 GEN
Solar/Wind Harmer
0.43
3143096IRON208
Adder
0.898
3143096IRON208
Adder
0.88
3141906WESTMOR
Solar/Wind Harmer
0.085
316131AB2-060 GEN
Solar/Wind Harmer
0.609
964241AG1-285 GEN
Solar/Wind Harmer
12.68
970737AG2-469 GEN
Solar/Wind Harmer
8.068
315785AD2-033 C
Solar/Wind Harmer
1.5
970257AG2-171 GEN
Solar/Wind Harmer
5.835
959311AF2-222 GEN
Solar/Wind Harmer
16.07
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.598
3150861SPRUNCD
Adder
0.82
970909AG2-566 GEN
Solar/Wind Harmer
1.885
3147133PAMPLIN
Solar/Wind Harmer
0.168
3147133PAMPLIN
Solar/Wind Harmer
0.134
316222AC1-221 GEN
Solar/Wind Harmer
0.683
3142366NRTHEST
Adder
0.52
942751AE2-291 GEN
Solar/Wind Harmer
6.426
3146776BUCKING
Solar/Wind Harmer
0.466
3146776BUCKING
Solar/Wind Harmer
0.038
3147243WELCO
Solar/Wind Harmer
0.111
971285AH1-108 GEN
Adder
1.342
970683AG2-441 GEN
Solar/Wind Harmer
11.794
970681AG2-440 GEN
Solar/Wind Harmer
9.435
946301AF1-294 GEN
Solar/Wind Harmer
3.39
961791AG1-021 GEN
Solar/Wind Harmer
1.649
316233AE1-074 FULL
Solar/Wind Harmer
0.136
971281AH1-106 GEN
Solar/Wind Harmer
2.362
971283AH1-107 GEN
Solar/Wind Harmer
2.362
316312AB1-027
Solar/Wind Harmer
0.304
315657AE1-056 GEN
Solar/Wind Harmer
5.802
944491AF1-114 GEN
Solar/Wind Harmer
0
970865AG2-541 GEN
Solar/Wind Harmer
5.175
316123AC1-075 GEN
Solar/Wind Harmer
0.178
970165AG2-112 GEN
Solar/Wind Harmer
1.056
970163AG2-111 GEN
Solar/Wind Harmer
1.007
970285AG2-188 GEN
Solar/Wind Harmer
9.811
971845AH1-439 GEN
Solar/Wind Harmer
5.401
963181AG1-167 GEN
Solar/Wind Harmer
0.687
3144293JTRSVLE
Adder
0.547
3142416OLDCHRC
Solar/Wind Harmer
1.645
3147133PAMPLIN
Solar/Wind Harmer
0.528
971193AH1-056 GEN
Solar/Wind Harmer
10.243
316283AC2-100 C
Solar/Wind Harmer
0.32
971683AH1-343 GEN
Solar/Wind Harmer
5.838
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.088
316313AB2-026
Solar/Wind Harmer
0.085
316258AE1-075 C
Solar/Wind Harmer
0.102
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.047
3146776BUCKING
Solar/Wind Harmer
0.042
3142416OLDCHRC
Solar/Wind Harmer
0.441
3142416OLDCHRC
Solar/Wind Harmer
0.169
316003AC1-222 GEN
Solar/Wind Harmer
0.004
3146926FARMVIL
Solar/Wind Harmer
0.088
3143336POWHATN
Solar/Wind Harmer
2.408
316336AC2-165 C
Solar/Wind Harmer
0.005
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.047
CPLELTFEXP_CPLE->PJM
CLTF
12.747
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.757
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.09
MECLTFEXP_MEC->PJM
CLTF
2.89
SIGELTFEXP_SIGE->PJM
CLTF
0.083
NYPJM->LTFIMP_NY
CLTF
2.157
LGEELTFEXP_LGEE->PJM
CLTF
0.951
WECLTFEXP_WEC->PJM
CLTF
0.477
LAGNLTFEXP_LAGN->PJM
CLTF
7.286
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.32
TVALTFEXP_TVA->PJM
CLTF
3.623

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.46 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3552.3
MW Contribution:1.05
Bus #Bus NameTypeMW Contribution
3150991CHESPKB
50/50
3.881
972263AH1-716 GEN
50/50
236.435
3151081ELIZAR1
50/50
34.071
3151091ELIZAR2
50/50
33.48
941591AE2-156 GEN
50/50
31.086
3152611GOSPORTB
50/50
4.716
3152621GOSPORTC
50/50
4.003
3152601GOSPORTA
50/50
3.692
957871AF2-081 GEN
Solar/Wind Harmer
17.231
319010AE1-072 C
Solar/Wind Harmer
1.734
3146406KITTY HAWK
Solar/Wind Harmer
0.043
316305AF2-043 C
Solar/Wind Harmer
0.003
313526AB2-022
Solar/Wind Harmer
0.183
316321Z2-027
Solar/Wind Harmer
0.062
3146396TANGLEW
Solar/Wind Harmer
0.923
3145176PASQUOTANK
Solar/Wind Harmer
0.207
3146486SUNBURY
Solar/Wind Harmer
0.334
3150991CHESPKB
50/50
3.787
316185AD1-033 GEN
Solar/Wind Harmer
0.01
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.335
3145506HICKORY
Solar/Wind Harmer
1.396
3145506HICKORY
Solar/Wind Harmer
0.838
3145506HICKORY
Solar/Wind Harmer
0.21
316036AC1-147 C
Solar/Wind Harmer
0.065
316339AD2-160 GEN
Solar/Wind Harmer
0.562
316018AA1-139 ULT2
Solar/Wind Harmer
0.009
3150921YORKTN3
50/50
9.609
3144216WINCHST
50/50
1.419
3151101ELIZAR3
50/50
34.507
3151161SURRY 1
50/50
11.945
315773AC2-141 GEN
Solar/Wind Harmer
13.978
944581AF1-123 GEN
Solar/Wind Harmer
80.3
944601AF1-125 GEN
Solar/Wind Harmer
79.064
316382AG1-145 C
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.009
3146456SLIGO L269
Solar/Wind Harmer
0.345
971153AH1-033 GEN
Solar/Wind Harmer
3.986
3144536CHRHLND
Solar/Wind Harmer
0.051
316320Y1-086
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146486SUNBURY
Solar/Wind Harmer
0.334
3138283WHITEMARSH
Solar/Wind Harmer
0.077
315835AF2-110_GEN
Solar/Wind Harmer
2.241
971445AH1-216 GEN
Solar/Wind Harmer
22.847
315611Z1-036_GEN2
Solar/Wind Harmer
0.003
315976AC1-164 GENA
Solar/Wind Harmer
32.93
316169AC1-164_GENC
Solar/Wind Harmer
28.449
315975AC1-164 GENB
Solar/Wind Harmer
0.974
3130156CHOWAN
Solar/Wind Harmer
0.313
3130156CHOWAN
Solar/Wind Harmer
0.313
972265AH1-717 GEN
Adder
24.145
3151201GRAVEL4
Adder
22.635
3151191GRAVEL3
Adder
22.348
3151211GRAVEL5
Adder
22.348
316311AC2-079 GEN
Solar/Wind Harmer
8.775
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.209
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.06
315816AE2-034 GEN
Solar/Wind Harmer
1.289
315662AE1-191 GEN
Solar/Wind Harmer
0.01
315666AE1-190 GEN
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
8.787
3141913WHIT STONE
Solar/Wind Harmer
0.294
3138133OCRAN
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.29
315732AD1-074 GEN1
Solar/Wind Harmer
1.66
315733AD1-074 GEN2
Solar/Wind Harmer
1.66
315735AD1-075 GEN1
Solar/Wind Harmer
0.831
3141783LANCAST
Solar/Wind Harmer
0.173
3141783LANCAST
Solar/Wind Harmer
0.115
3143873LANEXA
Solar/Wind Harmer
0.173
941031AE2-094 GEN
Solar/Wind Harmer
52.388
944011AF1-069 GEN
Solar/Wind Harmer
17.117
3146206CASHIE
Solar/Wind Harmer
0.282
970601AG2-382 GEN
Solar/Wind Harmer
10.532
962981AG1-147 GEN
Solar/Wind Harmer
10.429
970673AG2-436 GEN
Solar/Wind Harmer
59.327
970673AG2-436 GEN
Solar/Wind Harmer
39.552
316369SG1_INVT
Solar/Wind Harmer
0.01
965291AG1-394 GEN
Solar/Wind Harmer
1.219
970327AG2-215 GEN
Solar/Wind Harmer
8.996
3145893MURPHYS
Solar/Wind Harmer
0.733
3152331SURRY 2
50/50
17.238
971353AH1-157 GEN
50/50
31.744
970017AG2-010 GEN
50/50
24.039
3150981CHESPKA
50/50
4.626
316294AC1-161 GEN
Solar/Wind Harmer
6.631
971317AH1-138 GEN
Solar/Wind Harmer
2.676
944591AF1-124 GEN
Solar/Wind Harmer
80.586
3138126ROCKLANDING
Solar/Wind Harmer
0.164
316159AE1-175 C
Solar/Wind Harmer
0.304
316375AC2-012 GEN
Solar/Wind Harmer
0.009
316388AE2-253 GEN
Solar/Wind Harmer
1.086
3146456SLIGO L269
Solar/Wind Harmer
0.345
316246AF1-032 C
Solar/Wind Harmer
0.153
316072AD1-144
Solar/Wind Harmer
0.122
3146516WINFALL
Solar/Wind Harmer
1.066
3146516WINFALL
Solar/Wind Harmer
0.329
316093AE2-104_GEN
Solar/Wind Harmer
5.492
3145336SMITFLD
Solar/Wind Harmer
1.303
939411AE1-173 GEN
Solar/Wind Harmer
137.667
315800Z1-036_GEN1
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.313
940641AE2-051 GEN
Solar/Wind Harmer
25.037
3151171GRAVELC
Adder
3.308
3141766HARMONY
Solar/Wind Harmer
0.061
3145663CRESWEL
Solar/Wind Harmer
0.84
971163AH1-040 GEN
Solar/Wind Harmer
24.028
961611AG1-000B GEN
Solar/Wind Harmer
15.572
971777AH1-397 GEN
Solar/Wind Harmer
0.783
3141843SHACKLE
Adder
1.515
3138133OCRAN
Solar/Wind Harmer
0.176
971647AH1-324 GEN
Solar/Wind Harmer
12.191
3146206CASHIE
Solar/Wind Harmer
0.282
971547AH1-271 GEN
Solar/Wind Harmer
6.019
970661AG2-428 GEN
Solar/Wind Harmer
27.952
3145893MURPHYS
Solar/Wind Harmer
1.086
3145893MURPHYS
Solar/Wind Harmer
1.208
316381AD1-082 GEN
Solar/Wind Harmer
0.283
3146173TUNIS
Solar/Wind Harmer
0.269
962861AG1-135 GEN
Solar/Wind Harmer
8.574
970659AG2-427 GEN
Solar/Wind Harmer
12.95
3145963POPLR C
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.266
971069AG2-661 GEN
Solar/Wind Harmer
4.727
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3146263WOODLND
Solar/Wind Harmer
0.259
970919AG2-571 GEN
Solar/Wind Harmer
9.228
3142433PROV 92
Solar/Wind Harmer
1.037
3142433PROV 92
Adder
0.504
316017AA1-139 ULT1
Solar/Wind Harmer
0.193
3137176SLIGO L2192
Solar/Wind Harmer
1.372
3146456SLIGO L269
Solar/Wind Harmer
6.101
3130086AYDLETT
Solar/Wind Harmer
1.375
3146386ELIZ CT
Solar/Wind Harmer
0.338
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.329
3146516WINFALL
Solar/Wind Harmer
0.329
3146516WINFALL
Solar/Wind Harmer
0.329
316236AE1-162_GEN
Solar/Wind Harmer
0.003
3146626S HERTFORD
Solar/Wind Harmer
0.325
3146626S HERTFORD
Solar/Wind Harmer
0.325
3146376EDENTON
Solar/Wind Harmer
1.391
3146376EDENTON
Solar/Wind Harmer
1.391
315742AE1-103 GEN
Solar/Wind Harmer
0.004
316065AD1-022 GEN
Solar/Wind Harmer
13.104
970657AG2-426 GEN
Solar/Wind Harmer
9.628
970657AG2-426 GEN
Solar/Wind Harmer
2.018
972185AH1-677 GEN
Adder
15.426
316033AB2-134 GEN
Solar/Wind Harmer
0.016
315697AD1-025 GEN
Solar/Wind Harmer
0.309
3145893MURPHYS
Solar/Wind Harmer
1.818
3145893MURPHYS
Solar/Wind Harmer
0.489
972187AH1-678 GEN
Adder
7.708
3146173TUNIS
Solar/Wind Harmer
0.269
3146173TUNIS
Solar/Wind Harmer
0.269
958261AF2-120 GEN
Solar/Wind Harmer
8.785
970933AG2-581 GEN
Solar/Wind Harmer
20.809
3142946ENON
Solar/Wind Harmer
0.026
3144356SAPONY
Solar/Wind Harmer
2.113
316075AC2-137 C
Solar/Wind Harmer
0.069
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.624
3150341NORNECKC1
Adder
2.603
3145933PARMELE
Solar/Wind Harmer
0.496
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
316426AA2-053 GEN
Solar/Wind Harmer
0.831
3145593CAROLNA
Solar/Wind Harmer
0.241
3145593CAROLNA
Solar/Wind Harmer
0.241
966811AG1-552 GEN
Solar/Wind Harmer
2.62
3145593CAROLNA
Solar/Wind Harmer
0.301
3145783HORNRTN
Solar/Wind Harmer
4.275
3145783HORNRTN
Solar/Wind Harmer
3.42
3145783HORNRTN
Solar/Wind Harmer
1.069
3145783HORNRTN
Solar/Wind Harmer
0.428
316181AB2-040 GEN
Solar/Wind Harmer
0.347
3145796HORNRTN
Solar/Wind Harmer
0.717
316274AC1-208 GEN
Solar/Wind Harmer
1.217
970099AG2-077 GEN
Solar/Wind Harmer
24.744
3145493TOT1
Solar/Wind Harmer
0.52
3145453TOT5
Solar/Wind Harmer
0.312
3145603CNETO
Solar/Wind Harmer
0.208
961601AG1-000A GEN
Solar/Wind Harmer
3.839
316263AC1-034 GEN
Solar/Wind Harmer
8.198
939181AE1-148 GEN
Solar/Wind Harmer
9.694
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316240AF1-291 C
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
8.858
944641AF1-129 GEN
Adder
87.436
964791AG1-342 GEN
Solar/Wind Harmer
3.522
3146843MT LREL
Solar/Wind Harmer
0.183
3146843MT LREL
Solar/Wind Harmer
0.183
971741AH1-377 GEN
Solar/Wind Harmer
17.569
970323AG2-213 GEN
Solar/Wind Harmer
7.438
971775AH1-396 GEN
Solar/Wind Harmer
0.279
316034AC1-036 C
Solar/Wind Harmer
0.013
316222AC1-221 GEN
Solar/Wind Harmer
0.689
970301AG2-198 GEN
Solar/Wind Harmer
7.044
958211AF2-115 GEN
Solar/Wind Harmer
1.922
963191AG1-168 GEN
Solar/Wind Harmer
0.641
3144293JTRSVLE
Adder
0.51
3144293JTRSVLE
Adder
0.429
3147133PAMPLIN
Solar/Wind Harmer
0.155
3147133PAMPLIN
Solar/Wind Harmer
0.124
3150691DARBY 3
Adder
10.708
3150701DARBY 4
Adder
10.683
3150681DARBY 2
Adder
10.671
3150671DARBY 1
Adder
10.658
3142366NRTHEST
Adder
0.396
942751AE2-291 GEN
Solar/Wind Harmer
6.34
3145893MURPHYS
Solar/Wind Harmer
0.271
971967AH1-528 GEN
Solar/Wind Harmer
43.419
3145513AHOSKIE
Solar/Wind Harmer
0.56
3145513AHOSKIE
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.533
3145683EARLEYS
Solar/Wind Harmer
0.266
3145683EARLEYS
Solar/Wind Harmer
0.266
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
970085AG2-068 GEN
Solar/Wind Harmer
13.776
970581AG2-369 GEN
Solar/Wind Harmer
11.847
3146043SEABORD
Solar/Wind Harmer
0.256
315607AA1-063A GEN
Solar/Wind Harmer
0.52
316132AB2-190 GEN1
Solar/Wind Harmer
1.358
316315AB2-025 C
Solar/Wind Harmer
0.204
971167AH1-042 GEN
Solar/Wind Harmer
22.411
315814AE2-033 C
Solar/Wind Harmer
19.96
3141813NORNECK
Solar/Wind Harmer
0.25
3146033SCOT NK
Solar/Wind Harmer
0.988
315652AC1-086 GEN
Solar/Wind Harmer
26.724
3137643SOCKMAN
Solar/Wind Harmer
0.96
316005AA1-067
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.952
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
970181AG2-120 GEN
Solar/Wind Harmer
2.978
3145796HORNRTN
Solar/Wind Harmer
0.765
3145796HORNRTN
Solar/Wind Harmer
0.096
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3143316POE
Solar/Wind Harmer
0.921
957861AF2-080 GEN
Solar/Wind Harmer
9.971
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.224
3145573BETHELC
Solar/Wind Harmer
0.224
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
9.375
316223AC1-118
Solar/Wind Harmer
0.144
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.467
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
971443AH1-215 GEN
Solar/Wind Harmer
2.94
3144303KENBRDG
Solar/Wind Harmer
0.139
970683AG2-441 GEN
Solar/Wind Harmer
11.135
970681AG2-440 GEN
Solar/Wind Harmer
8.908
946301AF1-294 GEN
Solar/Wind Harmer
3.16
961791AG1-021 GEN
Solar/Wind Harmer
1.537
315657AE1-056 GEN
Solar/Wind Harmer
5.357
970865AG2-541 GEN
Solar/Wind Harmer
5.15
316312AB1-027
Solar/Wind Harmer
0.253
944491AF1-114 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Harmer
0.176
970165AG2-112 GEN
Solar/Wind Harmer
1.046
970163AG2-111 GEN
Solar/Wind Harmer
0.997
971285AH1-108 GEN
Adder
0.868
3146516WINFALL
Solar/Wind Harmer
0.329
3145336SMITFLD
Solar/Wind Harmer
0.13
3146626S HERTFORD
Solar/Wind Harmer
0.325
3146376EDENTON
Solar/Wind Harmer
0.313
3145273HOLLAND
Solar/Wind Harmer
0.233
3151221GRAVEL6
Adder
22.609
3151171GRAVELC
Adder
4.35
3141766HARMONY
Solar/Wind Harmer
4.054
316156AD2-030 GEN
Solar/Wind Harmer
0.224
3141873WAN 176
Solar/Wind Harmer
5.376
315614AA2-178 GEN
Solar/Wind Harmer
1.719
316280AD1-041 GEN
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
7.918
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.515
971157AH1-035 GEN
Solar/Wind Harmer
3.489
315737AD1-076 GEN
Solar/Wind Harmer
3.717
3146206CASHIE
Solar/Wind Harmer
0.282
970661AG2-428 GEN
Solar/Wind Harmer
5.945
962971AG1-146 GEN
Solar/Wind Harmer
4.47
3156081AA2-088 GEN
Solar/Wind Harmer
0.007
970009AG2-005 GEN
Solar/Wind Harmer
2.047
3156021HOLLOMANSOL
Solar/Wind Harmer
1.237
3145893MURPHYS
Solar/Wind Harmer
0.455
3145893MURPHYS
Solar/Wind Harmer
0.271
3142433PROV 92
Adder
0.504
970087AG2-069 GEN
Solar/Wind Harmer
20.664
3141726DUNNSVL
Solar/Wind Harmer
1.028
3145823KELFORD
Solar/Wind Harmer
0.257
316458AB2-190 GEN2
Solar/Wind Harmer
1.358
970129AG2-093 GEN
Solar/Wind Harmer
7.142
3150351NORNECKC2
Adder
2.498
3146293MARTNCO
Solar/Wind Harmer
0.23
316190AA2-174 GEN
Solar/Wind Harmer
0
316023GEN1_S
Solar/Wind Harmer
0.55
316011AB1-132 GEN
Solar/Wind Harmer
4.417
962571AG1-106 GEN
Solar/Wind Harmer
3.457
3145783HORNRTN
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
316212AC1-099_GEN
Solar/Wind Harmer
1.238
3145796HORNRTN
Solar/Wind Harmer
0.788
3145796HORNRTN
Solar/Wind Harmer
0.239
960081AF2-299 GEN
Solar/Wind Harmer
2.276
944631AF1-128 GEN
Adder
111.457
957481AF2-042 GEN
Solar/Wind Harmer
61.861
316494AC1-189 GEN
Solar/Wind Harmer
0.781
971795AH1-408 GEN
Solar/Wind Harmer
15.163
316337AD2-073 GEN
Solar/Wind Harmer
0.197
315722AD1-056 GEN
Solar/Wind Harmer
1.431
961671AG1-007 GEN
Solar/Wind Harmer
0.034
3146083TARBORO
Solar/Wind Harmer
0.224
3145493TOT1
Solar/Wind Harmer
0.997
3147043LAWRENC
Adder
2.017
3146233WITAKRS
Solar/Wind Harmer
0.88
315693AD1-088 GEN
Solar/Wind Harmer
10.438
316129AC1-054 GEN
Solar/Wind Harmer
0.818
3145543BTLEBRO
Solar/Wind Harmer
0.216
3145543BTLEBRO
Solar/Wind Harmer
0.172
316359AB2-059 GEN
Solar/Wind Harmer
0.775
316049AB1-081 GEN
Solar/Wind Harmer
1.235
3142053HEARTS
Solar/Wind Harmer
0.38
971065AG2-659 GEN
Solar/Wind Harmer
9.183
962491AG1-098 GEN
Solar/Wind Harmer
12.255
315687AD1-152 GEN
Solar/Wind Harmer
0.007
315671AE2-027_GEN
Solar/Wind Harmer
13.142
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970401AG2-262 GEN
Solar/Wind Harmer
1.076
3143096IRON208
Adder
0.724
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
12.471
972135AH1-637 GEN
Solar/Wind Harmer
1.379
963171AG1-166 GEN
Solar/Wind Harmer
0.854
971563AH1-280 GEN
Solar/Wind Harmer
1.708
3144293JTRSVLE
Adder
0.51
3142543TWELFTH
Solar/Wind Harmer
0.014
3142416OLDCHRC
Solar/Wind Harmer
0.367
3142416OLDCHRC
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.076
3150851SPRUNCC
Adder
0.53
316083AB2-161 GEN
Solar/Wind Harmer
0.004
957521AF2-046 GEN
Solar/Wind Harmer
20.157
961681AG1-008 GEN
Solar/Wind Harmer
20.157
3146173TUNIS
Solar/Wind Harmer
0.269
970659AG2-427 GEN
Solar/Wind Harmer
2.833
316463AE2-346 GEN
Solar/Wind Harmer
0.23
316140AB2-099
Solar/Wind Harmer
0.096
962331AG1-082 GEN
Solar/Wind Harmer
2.855
3145963POPLR C
Solar/Wind Harmer
0.267
315778AD1-151 GEN
Solar/Wind Harmer
21.272
316404AE1-155 C
Solar/Wind Harmer
0.06
3146263WOODLND
Solar/Wind Harmer
0.259
970917AG2-570 GEN
Solar/Wind Harmer
23.07
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
3142946ENON
Solar/Wind Harmer
0.086
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.257
970129AG2-093 GEN
Solar/Wind Harmer
15.176
3150351NORNECKC2
Adder
2.54
315813AE1-149 C
Solar/Wind Harmer
13.315
3145933PARMELE
Solar/Wind Harmer
0.248
966801AG1-551 GEN
Solar/Wind Harmer
2.89
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
316365GEN2_N
Solar/Wind Harmer
0.55
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
316210AC1-098 GEN
Solar/Wind Harmer
2.22
313506AB2-031 GEN
Solar/Wind Harmer
0.739
3145796HORNRTN
Solar/Wind Harmer
0.956
3145796HORNRTN
Solar/Wind Harmer
0.239
970133AG2-095 GEN
Solar/Wind Harmer
2.211
316327AA2-057 GEN
Solar/Wind Harmer
0.342
315724AD1-057 GEN
Solar/Wind Harmer
0.849
3146073TAR RVR
Solar/Wind Harmer
0.224
3146083TARBORO
Solar/Wind Harmer
0.224
3147043LAWRENC
Solar/Wind Harmer
0.134
3146233WITAKRS
Solar/Wind Harmer
1.11
3146233WITAKRS
Solar/Wind Harmer
0.15
3138543CONSLDL
Solar/Wind Harmer
0.145
316478AD1-087 GEN
Solar/Wind Harmer
0.767
316486AD2-202 GEN
Solar/Wind Harmer
0.225
961601AG1-000A GEN
Solar/Wind Harmer
15.354
3145543BTLEBRO
Solar/Wind Harmer
0.216
3145543BTLEBRO
Solar/Wind Harmer
0.216
971623AH1-311 GEN
Solar/Wind Harmer
0.431
965281AG1-393 GEN
Solar/Wind Harmer
2.229
315839AE2-212 C
Solar/Wind Harmer
0.002
3141906WESTMOR
Solar/Wind Harmer
0.08
970293AG2-193 GEN
Solar/Wind Harmer
2.109
316131AB2-060 GEN
Solar/Wind Harmer
0.596
964241AG1-285 GEN
Solar/Wind Harmer
12.329
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.602
315785AD2-033 C
Solar/Wind Harmer
1.441
970737AG2-469 GEN
Solar/Wind Harmer
7.562
970257AG2-171 GEN
Solar/Wind Harmer
5.579
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.71
959311AF2-222 GEN
Solar/Wind Harmer
15.31
316283AC2-100 C
Solar/Wind Harmer
0.323
970909AG2-566 GEN
Solar/Wind Harmer
1.761
963181AG1-167 GEN
Solar/Wind Harmer
0.641
3144293JTRSVLE
Adder
0.51
971683AH1-343 GEN
Solar/Wind Harmer
5.822
3147133PAMPLIN
Solar/Wind Harmer
0.487
971193AH1-056 GEN
Solar/Wind Harmer
9.458
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3142416OLDCHRC
Solar/Wind Harmer
1.369
3146926FARMVIL
Solar/Wind Harmer
0.076
3150861SPRUNCD
Adder
0.53
CPLELTFEXP_CPLE->PJM
CLTF
12.886
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.58
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.522
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.042
MECLTFEXP_MEC->PJM
CLTF
2.857
SIGELTFEXP_SIGE->PJM
CLTF
0.082
NYPJM->LTFIMP_NY
CLTF
2.077
LGEELTFEXP_LGEE->PJM
CLTF
0.931
WECLTFEXP_WEC->PJM
CLTF
0.469
LAGNLTFEXP_LAGN->PJM
CLTF
7.278
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.541
TVALTFEXP_TVA->PJM
CLTF
3.613

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:173.01 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:7041.78
MW Contribution:1.68
Bus #Bus NameTypeMW Contribution
971645AH1-323 GEN
50/50
34.852
3151161SURRY 1
50/50
14.066
3142416OLDCHRC
Solar/Wind Harmer
3.771
970293AG2-193 GEN
Solar/Wind Harmer
4.092
3142946ENON
Solar/Wind Harmer
0.127
316382AG1-145 C
Solar/Wind Harmer
0.003
3143096IRON208
Adder
1.57
3143096IRON208
Adder
1.539
3150921YORKTN3
Adder
9.356
3144216WINCHST
Adder
1.402
315773AC2-141 GEN
Solar/Wind Harmer
13.538
970133AG2-095 GEN
Solar/Wind Harmer
3.544
970129AG2-093 GEN
Solar/Wind Harmer
22.266
315778AD1-151 GEN
Solar/Wind Harmer
29.426
961611AG1-000B GEN
Solar/Wind Harmer
9.778
3151221GRAVEL6
Adder
26.624
3151171GRAVELC
Adder
5.122
3150861SPRUNCD
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
0.146
3144536CHRHLND
Solar/Wind Harmer
0.054
944581AF1-123 GEN
Solar/Wind Harmer
81.792
944601AF1-125 GEN
Solar/Wind Harmer
80.532
3151101ELIZAR3
Adder
33.706
3144873MCLAUGH
Solar/Wind Harmer
0.009
965281AG1-393 GEN
Solar/Wind Harmer
3.845
315839AE2-212 C
Solar/Wind Harmer
0.003
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.358
971153AH1-033 GEN
Solar/Wind Harmer
4.14
316473AC1-191 GEN
Solar/Wind Harmer
1.209
315813AE1-149 C
Solar/Wind Harmer
19.023
970659AG2-427 GEN
Solar/Wind Harmer
3.767
316083AB2-161 GEN
Solar/Wind Harmer
0.005
970661AG2-428 GEN
Solar/Wind Harmer
7.524
316320Y1-086
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
4.656
3146516WINFALL
Solar/Wind Harmer
0.349
3141843SHACKLE
Adder
1.778
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3146626S HERTFORD
Solar/Wind Harmer
0.346
316280AD1-041 GEN
Solar/Wind Harmer
0.007
3145273HOLLAND
Solar/Wind Harmer
0.258
316156AD2-030 GEN
Solar/Wind Harmer
0.254
3141873WAN 176
Solar/Wind Harmer
6.098
3146376EDENTON
Solar/Wind Harmer
0.338
315614AA2-178 GEN
Solar/Wind Harmer
1.889
971157AH1-035 GEN
Solar/Wind Harmer
3.886
315737AD1-076 GEN
Solar/Wind Harmer
4.152
972255AH1-712 GEN
Adder
164.714
3156081AA2-088 GEN
Solar/Wind Harmer
0.008
3146206CASHIE
Solar/Wind Harmer
0.318
3145893MURPHYS
Solar/Wind Harmer
0.528
3145893MURPHYS
Solar/Wind Harmer
0.316
957521AF2-046 GEN
Solar/Wind Harmer
23.434
961681AG1-008 GEN
Solar/Wind Harmer
23.434
962971AG1-146 GEN
Solar/Wind Harmer
5.016
3156021HOLLOMANSOL
Solar/Wind Harmer
1.422
3146173TUNIS
Solar/Wind Harmer
0.313
316365GEN2_N
Solar/Wind Harmer
0.699
316463AE2-346 GEN
Solar/Wind Harmer
0.267
316140AB2-099
Solar/Wind Harmer
0.111
962331AG1-082 GEN
Solar/Wind Harmer
3.322
970009AG2-005 GEN
Solar/Wind Harmer
2.291
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
970917AG2-570 GEN
Solar/Wind Harmer
27.198
316317KELFORD C
Solar/Wind Harmer
0.029
3145823KELFORD
Solar/Wind Harmer
0.303
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
313506AB2-031 GEN
Solar/Wind Harmer
0.929
3145796HORNRTN
Solar/Wind Harmer
1.185
3152331SURRY 2
50/50
15.859
3142416OLDCHRC
Solar/Wind Harmer
1.011
3142416OLDCHRC
Solar/Wind Harmer
0.387
316159AE1-175 C
Solar/Wind Harmer
0.327
944631AF1-128 GEN
Adder
179.515
3143096IRON208
Adder
1.57
3138126ROCKLANDING
Solar/Wind Harmer
0.171
971317AH1-138 GEN
Solar/Wind Harmer
2.773
316294AC1-161 GEN
Solar/Wind Harmer
6.422
3142543TWELFTH
Solar/Wind Harmer
0.035
970129AG2-093 GEN
Solar/Wind Harmer
10.478
316458AB2-190 GEN2
Solar/Wind Harmer
1.976
971069AG2-661 GEN
Solar/Wind Harmer
6.539
971647AH1-324 GEN
Solar/Wind Harmer
15.662
961611AG1-000B GEN
Solar/Wind Harmer
19.23
3151171GRAVELC
Adder
3.895
3150851SPRUNCC
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
1.459
944591AF1-124 GEN
Solar/Wind Harmer
82.083
316375AC2-012 GEN
Solar/Wind Harmer
0.009
3150981CHESPKA
Adder
4.531
315671AE2-027_GEN
Solar/Wind Harmer
23.135
316072AD1-144
Solar/Wind Harmer
0.13
316388AE2-253 GEN
Solar/Wind Harmer
1.126
3142433PROV 92
Solar/Wind Harmer
1.432
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.358
316246AF1-032 C
Solar/Wind Harmer
0.161
970659AG2-427 GEN
Solar/Wind Harmer
17.218
316381AD1-082 GEN
Solar/Wind Harmer
0.371
970661AG2-428 GEN
Solar/Wind Harmer
35.374
3143526WINTERP
Solar/Wind Harmer
1.841
316093AE2-104_GEN
Solar/Wind Harmer
5.955
3141766HARMONY
Solar/Wind Harmer
0.07
3146516WINFALL
Solar/Wind Harmer
1.13
3146516WINFALL
Solar/Wind Harmer
0.349
971777AH1-397 GEN
Solar/Wind Harmer
0.918
3141843SHACKLE
Adder
1.778
939411AE1-173 GEN
Solar/Wind Harmer
148.397
3143226MDLTHAN
Solar/Wind Harmer
0.343
940641AE2-051 GEN
Solar/Wind Harmer
27.456
315800Z1-036_GEN1
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.338
3138133OCRAN
Solar/Wind Harmer
0.198
3145663CRESWEL
Solar/Wind Harmer
0.924
971163AH1-040 GEN
Solar/Wind Harmer
26.412
972277AH1-723 GEN
Adder
191.941
3146206CASHIE
Solar/Wind Harmer
0.318
971547AH1-271 GEN
Solar/Wind Harmer
6.801
3145893MURPHYS
Solar/Wind Harmer
1.262
3145893MURPHYS
Solar/Wind Harmer
1.404
3146173TUNIS
Solar/Wind Harmer
0.313
316023GEN1_S
Solar/Wind Harmer
0.699
3145683EARLEYS
Solar/Wind Harmer
0.31
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
970919AG2-571 GEN
Solar/Wind Harmer
10.879
970087AG2-069 GEN
Solar/Wind Harmer
24.391
316174AB2-169 GEN
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.303
960081AF2-299 GEN
Solar/Wind Harmer
2.907
316011AB1-132 GEN
Solar/Wind Harmer
5.469
962571AG1-106 GEN
Solar/Wind Harmer
4.28
316190AA2-174 GEN
Solar/Wind Harmer
0.001
962861AG1-135 GEN
Solar/Wind Harmer
9.564
3142296MT RD221
50/50
1.311
3150691DARBY 3
50/50
29.113
3150701DARBY 4
50/50
29.046
3150681DARBY 2
50/50
29.012
3150671DARBY 1
50/50
28.978
3142366NRTHEST
50/50
1.317
316075AC2-137 C
Solar/Wind Harmer
0.106
3142946ENON
Solar/Wind Harmer
0.038
316033AB2-134 GEN
Solar/Wind Harmer
0.022
315697AD1-025 GEN
Solar/Wind Harmer
0.413
944641AF1-129 GEN
Adder
174.18
316236AE1-162_GEN
Solar/Wind Harmer
0.003
316240AF1-291 C
Solar/Wind Harmer
0.003
316036AC1-147 C
Solar/Wind Harmer
0.067
3150991CHESPKB
Adder
3.801
3150991CHESPKB
Adder
3.71
316316AC1-027 C
Solar/Wind Harmer
0.347
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.01
3145506HICKORY
Solar/Wind Harmer
1.442
3145506HICKORY
Solar/Wind Harmer
0.865
3145506HICKORY
Solar/Wind Harmer
0.217
316339AD2-160 GEN
Solar/Wind Harmer
0.583
316018AA1-139 ULT2
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.2
3137176SLIGO L2192
Solar/Wind Harmer
1.425
3146456SLIGO L269
Solar/Wind Harmer
6.337
966871AG1-558 GEN
Solar/Wind Harmer
0.414
3130086AYDLETT
Solar/Wind Harmer
1.43
970657AG2-426 GEN
Solar/Wind Harmer
12.462
970657AG2-426 GEN
Solar/Wind Harmer
2.613
3143526WINTERP
Solar/Wind Harmer
1.841
3146386ELIZ CT
Solar/Wind Harmer
0.354
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.349
3146516WINFALL
Solar/Wind Harmer
0.349
3146516WINFALL
Solar/Wind Harmer
0.349
3146626S HERTFORD
Solar/Wind Harmer
0.346
3146626S HERTFORD
Solar/Wind Harmer
0.346
971223AH1-071 GEN
Solar/Wind Harmer
3.664
315742AE1-103 GEN
Solar/Wind Harmer
0.004
3146376EDENTON
Solar/Wind Harmer
1.504
3146376EDENTON
Solar/Wind Harmer
1.504
3144356SAPONY
Solar/Wind Harmer
2.786
316065AD1-022 GEN
Solar/Wind Harmer
14.743
972185AH1-677 GEN
Adder
17.914
3145893MURPHYS
Solar/Wind Harmer
2.113
3145893MURPHYS
Solar/Wind Harmer
0.568
972187AH1-678 GEN
Adder
8.995
3146173TUNIS
Solar/Wind Harmer
0.313
3146173TUNIS
Solar/Wind Harmer
0.313
970933AG2-581 GEN
Solar/Wind Harmer
24.83
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.181
316181AB2-040 GEN
Solar/Wind Harmer
0.436
316426AA2-053 GEN
Solar/Wind Harmer
1.013
3145593CAROLNA
Solar/Wind Harmer
0.298
3145593CAROLNA
Solar/Wind Harmer
0.298
966811AG1-552 GEN
Solar/Wind Harmer
3.231
3145593CAROLNA
Solar/Wind Harmer
0.371
972263AH1-716 GEN
50/50
220.54
316312AB1-027
Solar/Wind Harmer
0.696
315976AC1-164 GENA
Solar/Wind Harmer
40.142
316169AC1-164_GENC
Solar/Wind Harmer
34.679
315975AC1-164 GENB
Solar/Wind Harmer
1.188
316132AB2-190 GEN1
Solar/Wind Harmer
1.976
316369SG1_INVT
Solar/Wind Harmer
0.014
972265AH1-717 GEN
Adder
28.433
3151201GRAVEL4
Adder
26.654
3151191GRAVEL3
Adder
26.317
3151211GRAVEL5
Adder
26.317
971445AH1-216 GEN
Solar/Wind Harmer
25.708
971285AH1-108 GEN
Adder
2.752
3151081ELIZAR1
Adder
33.28
3151091ELIZAR2
Adder
32.702
3152611GOSPORTB
Adder
4.621
3152621GOSPORTC
Adder
3.922
3152601GOSPORTA
Adder
3.618
971167AH1-042 GEN
Solar/Wind Harmer
31.907
957871AF2-081 GEN
Solar/Wind Harmer
17.869
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3138283WHITEMARSH
Solar/Wind Harmer
0.083
319010AE1-072 C
Solar/Wind Harmer
1.802
3146406KITTY HAWK
Solar/Wind Harmer
0.045
316305AF2-043 C
Solar/Wind Harmer
0.003
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.243
316311AC2-079 GEN
Solar/Wind Harmer
10.187
3143873LANEXA
Solar/Wind Harmer
0.213
316233AE1-074 FULL
Solar/Wind Harmer
0.283
971281AH1-106 GEN
Solar/Wind Harmer
4.913
971283AH1-107 GEN
Solar/Wind Harmer
4.913
315835AF2-110_GEN
Solar/Wind Harmer
2.43
313526AB2-022
Solar/Wind Harmer
0.192
316314AB2-024 C
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.352
3146486SUNBURY
Solar/Wind Harmer
0.352
3143316POE
Solar/Wind Harmer
1.396
316321Z2-027
Solar/Wind Harmer
0.065
3146396TANGLEW
Solar/Wind Harmer
0.971
3145176PASQUOTANK
Solar/Wind Harmer
0.218
316059AD1-063 C
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
10.307
315662AE1-191 GEN
Solar/Wind Harmer
0.011
315666AE1-190 GEN
Solar/Wind Harmer
0.003
3141873WAN 176
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.338
3130156CHOWAN
Solar/Wind Harmer
0.338
3141913WHIT STONE
Solar/Wind Harmer
0.333
316315AB2-025 C
Solar/Wind Harmer
0.269
315814AE2-033 C
Solar/Wind Harmer
26.26
3138133OCRAN
Solar/Wind Harmer
0.099
315816AE2-034 GEN
Solar/Wind Harmer
1.417
941031AE2-094 GEN
Solar/Wind Harmer
60.194
944011AF1-069 GEN
Solar/Wind Harmer
19.668
3141783LANCAST
Solar/Wind Harmer
0.195
3141783LANCAST
Solar/Wind Harmer
0.13
3130546PLYMOUTH
Solar/Wind Harmer
0.324
315732AD1-074 GEN1
Solar/Wind Harmer
1.854
315733AD1-074 GEN2
Solar/Wind Harmer
1.854
315735AD1-075 GEN1
Solar/Wind Harmer
0.928
972193AH1-681 GEN
Adder
7.36
970673AG2-436 GEN
Solar/Wind Harmer
68.642
970673AG2-436 GEN
Solar/Wind Harmer
45.761
3146206CASHIE
Solar/Wind Harmer
0.318
970601AG2-382 GEN
Solar/Wind Harmer
11.901
965291AG1-394 GEN
Solar/Wind Harmer
1.416
971967AH1-528 GEN
Solar/Wind Harmer
50.838
3145893MURPHYS
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.316
962981AG1-147 GEN
Solar/Wind Harmer
11.703
3145513AHOSKIE
Solar/Wind Harmer
0.651
3145513AHOSKIE
Solar/Wind Harmer
0.311
3145683EARLEYS
Solar/Wind Harmer
0.62
3145683EARLEYS
Solar/Wind Harmer
0.31
3145683EARLEYS
Solar/Wind Harmer
0.31
3146043SEABORD
Solar/Wind Harmer
0.307
970327AG2-215 GEN
Solar/Wind Harmer
10.069
315607AA1-063A GEN
Solar/Wind Harmer
0.625
970085AG2-068 GEN
Solar/Wind Harmer
16.26
970581AG2-369 GEN
Solar/Wind Harmer
13.984
316087AB2-174 GEN
Solar/Wind Harmer
0.009
315652AC1-086 GEN
Solar/Wind Harmer
33.087
3137643SOCKMAN
Solar/Wind Harmer
1.194
3145796HORNRTN
Solar/Wind Harmer
0.889
3145783HORNRTN
Solar/Wind Harmer
5.27
3145783HORNRTN
Solar/Wind Harmer
4.216
3145783HORNRTN
Solar/Wind Harmer
1.317
3145783HORNRTN
Solar/Wind Harmer
0.527
958261AF2-120 GEN
Solar/Wind Harmer
9.788
3145933PARMELE
Solar/Wind Harmer
0.585
3145933PARMELE
Solar/Wind Harmer
0.292
970099AG2-077 GEN
Solar/Wind Harmer
31.087
316274AC1-208 GEN
Solar/Wind Harmer
1.496
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.897
3150341NORNECKC1
Adder
2.874
3145493TOT1
Solar/Wind Harmer
0.64
3145453TOT5
Solar/Wind Harmer
0.384
3145603CNETO
Solar/Wind Harmer
0.256
961601AG1-000A GEN
Solar/Wind Harmer
4.81
316263AC1-034 GEN
Solar/Wind Harmer
10.275
939181AE1-148 GEN
Solar/Wind Harmer
12.944
971741AH1-377 GEN
Solar/Wind Harmer
26.49
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970301AG2-198 GEN
Solar/Wind Harmer
11.171
970323AG2-213 GEN
Solar/Wind Harmer
11.115
971775AH1-396 GEN
Solar/Wind Harmer
0.417
316034AC1-036 C
Solar/Wind Harmer
0.019
962561AG1-105 GEN
Solar/Wind Harmer
12.3
958211AF2-115 GEN
Solar/Wind Harmer
3.071
963191AG1-168 GEN
Solar/Wind Harmer
1.024
3144293JTRSVLE
Adder
0.815
3144293JTRSVLE
Adder
0.686
964791AG1-342 GEN
Solar/Wind Harmer
4.887
3146843MT LREL
Solar/Wind Harmer
0.254
3146843MT LREL
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.203
316468AD1-105 GEN
Solar/Wind Harmer
-0.081
3146776BUCKING
Solar/Wind Harmer
0.914
3146776BUCKING
Solar/Wind Harmer
0.074
316222AC1-221 GEN
Solar/Wind Harmer
0.945
971489AH1-241 GEN
Solar/Wind Harmer
10.629
942751AE2-291 GEN
Solar/Wind Harmer
10.765
315821AE2-092 GEN
Solar/Wind Harmer
0.011
270013AE1-250 PV
Solar/Wind Harmer
0.005
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.945
316447AC1-158 HLD
Solar/Wind Helper
5.508
315651AD1-115 GEN
Solar/Wind Helper
1.146
226929AD2-058 GEN
Solar/Wind Helper
0.127
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.12
237034AC2-136 C
Solar/Wind Helper
0.207
23777901MDS_W4-102
Solar/Wind Helper
0.152
235020AA1-095 C
Solar/Wind Helper
0.045
237001AB1-127_GEN
Solar/Wind Helper
0.385
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237002AB1-128_GEN
Solar/Wind Helper
0.384
235063AE1-101 C2
Solar/Wind Helper
1.423
205916AD1-020 GEN
Solar/Wind Helper
1.645
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
232424Y1-079 C
Solar/Wind Helper
0.112
233987AB2-037 GEN
Solar/Wind Helper
2.265
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
3145796HORNRTN
Solar/Wind Harmer
0.948
3145796HORNRTN
Solar/Wind Harmer
0.119
3146033SCOT NK
Solar/Wind Harmer
1.185
316005AA1-067
Solar/Wind Harmer
0.307
3145746EVERETS
Solar/Wind Harmer
1.138
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
970181AG2-120 GEN
Solar/Wind Harmer
3.56
970831AG2-522 GEN
Solar/Wind Harmer
12.024
957861AF2-080 GEN
Solar/Wind Harmer
12.104
316420AA1-050 GEN
Solar/Wind Harmer
0.009
3141813NORNECK
Solar/Wind Harmer
0.276
3145573BETHELC
Solar/Wind Harmer
0.276
3145573BETHELC
Solar/Wind Harmer
0.276
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.38
3144303KENBRDG
Solar/Wind Harmer
0.208
972189AH1-679 GEN
Adder
4.36
970683AG2-441 GEN
Solar/Wind Harmer
17.21
970681AG2-440 GEN
Solar/Wind Harmer
13.768
946301AF1-294 GEN
Solar/Wind Harmer
5.05
961791AG1-021 GEN
Solar/Wind Harmer
2.457
315657AE1-056 GEN
Solar/Wind Harmer
8.773
316118AC1-105 GEN
Solar/Wind Harmer
0.646
3147173SINAI
Solar/Wind Harmer
0.246
3147243WELCO
Solar/Wind Harmer
0.154
970285AG2-188 GEN
Solar/Wind Harmer
18.408
971845AH1-439 GEN
Solar/Wind Harmer
10.428
970865AG2-541 GEN
Solar/Wind Harmer
7.734
972205AH1-687 GEN
Adder
8.917
316223AC1-118
Solar/Wind Harmer
0.15
316123AC1-075 GEN
Solar/Wind Harmer
0.284
970165AG2-112 GEN
Solar/Wind Harmer
1.683
970163AG2-111 GEN
Solar/Wind Harmer
1.606
971447AH1-217 GEN
Solar/Wind Harmer
5.953
270494AE1-108_GEN
Solar/Wind Harmer
2.206
3148133STUARTS
Solar/Wind Harmer
0.092
3148013FISHERV
Solar/Wind Harmer
0.088
3148463FAIRFLD
Solar/Wind Harmer
0.15
3151881LOWMORC
Adder
1.595
3151881LOWMORC
Adder
1.57
3151861LOWMORA
Adder
1.545
270069AE2-166 C O1
Solar/Wind Harmer
0.005
944491AF1-114 GEN
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.845
316411AF1-147_GEN1
Solar/Wind Helper
1.079
316415AF1-147_GEN2
Solar/Wind Helper
1.079
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
237085AD2-009_GEN
Solar/Wind Helper
1.388
960921AF2-383 GEN
Solar/Wind Helper
0.352
233935AB2-179 C
Solar/Wind Helper
1.229
205943AE1-185 GEN
Solar/Wind Helper
0.491
232436AB1-176 C
Solar/Wind Helper
0.043
205932AD2-116_GEN
Solar/Wind Helper
0.491
205956AE1-196_GEN
Solar/Wind Helper
0.491
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
232432Z2-076 GEN
Solar/Wind Helper
0.065
234033AF1-007_GEN
Solar/Wind Helper
6.788
238208AF1-136 C
Solar/Wind Helper
0.173
964001AG1-254 GEN
Solar/Wind Helper
0.917
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
3145796HORNRTN
Solar/Wind Harmer
0.978
3145796HORNRTN
Solar/Wind Harmer
0.296
316404AE1-155 C
Solar/Wind Harmer
0.067
3145933PARMELE
Solar/Wind Harmer
0.292
966801AG1-551 GEN
Solar/Wind Harmer
3.408
3147043LAWRENC
Solar/Wind Harmer
0.175
316210AC1-098 GEN
Solar/Wind Harmer
2.699
316313AB2-026
Solar/Wind Harmer
0.183
316258AE1-075 C
Solar/Wind Harmer
0.219
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.377
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
315724AD1-057 GEN
Solar/Wind Harmer
1.059
316478AD1-087 GEN
Solar/Wind Harmer
0.983
316486AD2-202 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.423
3150351NORNECKC2
Adder
2.804
3146073TAR RVR
Solar/Wind Harmer
0.276
3146083TARBORO
Solar/Wind Harmer
0.276
3146233WITAKRS
Solar/Wind Harmer
1.382
3146233WITAKRS
Solar/Wind Harmer
0.187
3138543CONSLDL
Solar/Wind Harmer
0.181
961601AG1-000A GEN
Solar/Wind Harmer
19.24
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.27
971623AH1-311 GEN
Solar/Wind Harmer
0.541
316131AB2-060 GEN
Solar/Wind Harmer
0.835
964241AG1-285 GEN
Solar/Wind Harmer
17.596
970909AG2-566 GEN
Solar/Wind Harmer
2.793
315785AD2-033 C
Solar/Wind Harmer
2.125
970257AG2-171 GEN
Solar/Wind Harmer
8.336
959311AF2-222 GEN
Solar/Wind Harmer
23.097
963181AG1-167 GEN
Solar/Wind Harmer
1.024
3144293JTRSVLE
Adder
0.815
3147133PAMPLIN
Solar/Wind Harmer
0.798
971193AH1-056 GEN
Solar/Wind Harmer
15.489
971781AH1-399 GEN
Solar/Wind Harmer
0.329
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
10.514
3146926FARMVIL
Solar/Wind Harmer
0.147
971683AH1-343 GEN
Solar/Wind Harmer
8.489
3146776BUCKING
Solar/Wind Harmer
0.082
316283AC2-100 C
Solar/Wind Harmer
0.444
3141906WESTMOR
Solar/Wind Harmer
0.083
232408W1-005 C
Solar/Wind Helper
0.491
232410W1-006 C
Solar/Wind Helper
0.491
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
238175AF1-290_GEN
Solar/Wind Helper
0.118
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
970221AG2-151 GEN
Solar/Wind Harmer
10.629
970737AG2-469 GEN
Solar/Wind Harmer
7.511
270197AD1-017 GEN1
Solar/Wind Harmer
1.056
3147312GRETNA
Solar/Wind Harmer
0.032
941821AE2-187 GEN
Solar/Wind Harmer
5.072
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3148013FISHERV
Solar/Wind Harmer
0.154
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.607
958131AF2-107 GEN
Solar/Wind Harmer
4.297
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
971367AH1-164 GEN
Solar/Wind Harmer
2.405
316044AC1-158 PL1
Solar/Wind Helper
2.503
316450AC1-158 RIC
Solar/Wind Helper
0.667
3141196NOKESVL
Solar/Wind Helper
1.389
316170AC1-121 GEN2
Solar/Wind Helper
0.521
3147666LOUISA
Solar/Wind Helper
0.737
227287AC2-120 GEN
Solar/Wind Helper
0.432
226910AB2-157 C
Solar/Wind Helper
0.018
223402AF1-300 C
Solar/Wind Helper
0.393
3132273ORANGE
Solar/Wind Helper
0.053
237030AB1-096 C
Solar/Wind Helper
0.069
238221AF1-254 C O1
Solar/Wind Helper
0.238
235067AD1-061 GEN
Solar/Wind Helper
0.424
205917AD1-020 ES
Solar/Wind Helper
0.354
233918AB1-142 GEN
Solar/Wind Helper
0.486
233982AB2-133 GEN
Solar/Wind Helper
0.346
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.491
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
230430AE1-229_GEN
Solar/Wind Helper
3.238
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.106
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.052
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219914AD2-027 C
Solar/Wind Helper
0.11
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
3145796HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.296
971795AH1-408 GEN
Solar/Wind Harmer
19.673
3146293MARTNCO
Solar/Wind Harmer
0.271
3147043LAWRENC
Adder
2.638
957481AF2-042 GEN
Solar/Wind Harmer
77.718
316212AC1-099_GEN
Solar/Wind Harmer
1.505
3143336POWHATN
Solar/Wind Harmer
5.15
3141726DUNNSVL
Solar/Wind Harmer
1.146
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
315693AD1-088 GEN
Solar/Wind Harmer
13.658
962491AG1-098 GEN
Solar/Wind Harmer
16.171
315722AD1-056 GEN
Solar/Wind Harmer
1.786
316494AC1-189 GEN
Solar/Wind Harmer
0.948
316129AC1-054 GEN
Solar/Wind Harmer
1.053
971065AG2-659 GEN
Solar/Wind Harmer
11.883
3150351NORNECKC2
Adder
2.758
961671AG1-007 GEN
Solar/Wind Harmer
0.042
3146083TARBORO
Solar/Wind Harmer
0.276
3145493TOT1
Solar/Wind Harmer
1.227
316336AC2-165 C
Solar/Wind Harmer
0.011
3146233WITAKRS
Solar/Wind Harmer
1.096
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.216
316359AB2-059 GEN
Solar/Wind Harmer
0.971
316049AB1-081 GEN
Solar/Wind Harmer
1.547
3142053HEARTS
Solar/Wind Harmer
0.476
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
19.275
963171AG1-166 GEN
Solar/Wind Harmer
1.365
971563AH1-280 GEN
Solar/Wind Harmer
2.73
3144293JTRSVLE
Adder
0.815
970401AG2-262 GEN
Solar/Wind Harmer
1.493
3146926FARMVIL
Solar/Wind Harmer
0.147
316337AD2-073 GEN
Solar/Wind Harmer
0.212
970937AG2-583 GEN
Solar/Wind Harmer
14.682
316003AC1-222 GEN
Solar/Wind Harmer
0.006
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.091
972003AH1-546 GEN
Solar/Wind Harmer
9.023
971377AH1-170 GEN
Solar/Wind Harmer
2.126
3147623JAMES R
Solar/Wind Harmer
0.462
970223AG2-152 GEN
Solar/Wind Harmer
12.134
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.1
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.127
3146802CHATHAM
Solar/Wind Harmer
0.119
941801AE2-185 GEN
Solar/Wind Harmer
5.072
972135AH1-637 GEN
Solar/Wind Harmer
1.317
270173AC1-122 GEN
Solar/Wind Harmer
0.358
270030AE2-140 GEN
Solar/Wind Harmer
15.132
962751AG1-124 GEN
Solar/Wind Harmer
6.367
315705AF1-075 GEN
Solar/Wind Harmer
5.115
316045AC1-158 PL2
Solar/Wind Helper
8.011
316006AB2-029 C
Solar/Wind Helper
0.164
316254AC1-120 GEN1
Solar/Wind Helper
1.563
3147666LOUISA
Solar/Wind Helper
1.282
316192AB2-158 GEN
Solar/Wind Helper
2.104
223401AF1-299 GEN
Solar/Wind Helper
0.393
23779801AA1-109
Solar/Wind Helper
0.185
237080AD1-060 GEN
Solar/Wind Helper
0.295
237038AE2-054 C
Solar/Wind Helper
0.233
235062AE1-101 C1
Solar/Wind Helper
1.423
966131AG1-482 GEN
Solar/Wind Helper
0.131
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
233964AF2-378 GEN
Solar/Wind Helper
0.04
232426Y1-080 FULL
Solar/Wind Helper
0.038
232428Y3-058 C
Solar/Wind Helper
0.327
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.491
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.221
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.032
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
CPLELTFEXP_CPLE->PJM
CLTF
17.713
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.377
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.563
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.762
MECLTFEXP_MEC->PJM
CLTF
7.835
SIGELTFEXP_SIGE->PJM
CLTF
0.242
NYPJM->LTFIMP_NY
CLTF
4.634
LGEELTFEXP_LGEE->PJM
CLTF
3.014
WECLTFEXP_WEC->PJM
CLTF
1.525
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.126
LAGNLTFEXP_LAGN->PJM
CLTF
14.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.998
TVALTFEXP_TVA->PJM
CLTF
7.404

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:153.9 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:6264.0
MW Contribution:1.42
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
13.991
971353AH1-157 GEN
50/50
28.65
970017AG2-010 GEN
50/50
21.737
3150981CHESPKA
50/50
4.162
3142416OLDCHRC
Solar/Wind Harmer
0.86
3142416OLDCHRC
Solar/Wind Harmer
0.33
316159AE1-175 C
Solar/Wind Harmer
0.283
316294AC1-161 GEN
Solar/Wind Harmer
5.617
971317AH1-138 GEN
Solar/Wind Harmer
2.41
3138126ROCKLANDING
Solar/Wind Harmer
0.148
944591AF1-124 GEN
Solar/Wind Harmer
71.262
316375AC2-012 GEN
Solar/Wind Harmer
0.008
3145336SMITFLD
Solar/Wind Harmer
1.25
3151171GRAVELC
Adder
3.316
316388AE2-253 GEN
Solar/Wind Harmer
0.975
316072AD1-144
Solar/Wind Harmer
0.112
3146456SLIGO L269
Solar/Wind Harmer
0.31
961611AG1-000B GEN
Solar/Wind Harmer
16.269
971647AH1-324 GEN
Solar/Wind Harmer
13.184
316246AF1-032 C
Solar/Wind Harmer
0.139
944631AF1-128 GEN
Adder
146.833
972277AH1-723 GEN
Adder
183.583
971069AG2-661 GEN
Solar/Wind Harmer
5.456
316458AB2-190 GEN2
Solar/Wind Harmer
1.639
970129AG2-093 GEN
Solar/Wind Harmer
8.684
316093AE2-104_GEN
Solar/Wind Harmer
5.127
3146516WINFALL
Solar/Wind Harmer
0.976
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Solar/Wind Harmer
1.2
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
970661AG2-428 GEN
Solar/Wind Harmer
29.836
3141766HARMONY
Solar/Wind Harmer
0.06
939411AE1-173 GEN
Solar/Wind Harmer
127.601
316381AD1-082 GEN
Solar/Wind Harmer
0.311
970659AG2-427 GEN
Solar/Wind Harmer
14.437
971777AH1-397 GEN
Solar/Wind Harmer
0.785
3141843SHACKLE
Adder
1.519
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
315671AE2-027_GEN
Solar/Wind Harmer
18.84
940641AE2-051 GEN
Solar/Wind Harmer
23.538
3143096IRON208
Adder
1.226
3130156CHOWAN
Solar/Wind Harmer
0.292
3145663CRESWEL
Solar/Wind Harmer
0.795
971163AH1-040 GEN
Solar/Wind Harmer
22.732
3138133OCRAN
Solar/Wind Harmer
0.17
3142543TWELFTH
Solar/Wind Harmer
0.027
3146206CASHIE
Solar/Wind Harmer
0.273
971547AH1-271 GEN
Solar/Wind Harmer
5.835
3145893MURPHYS
Solar/Wind Harmer
1.078
3145893MURPHYS
Solar/Wind Harmer
1.199
3146173TUNIS
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.265
316023GEN1_S
Solar/Wind Harmer
0.59
3145963POPLR C
Solar/Wind Harmer
0.263
3146263WOODLND
Solar/Wind Harmer
0.261
316174AB2-169 GEN
Solar/Wind Harmer
0.007
970919AG2-571 GEN
Solar/Wind Harmer
9.256
970087AG2-069 GEN
Solar/Wind Harmer
20.752
3145823KELFORD
Solar/Wind Harmer
0.259
962861AG1-135 GEN
Solar/Wind Harmer
8.175
316011AB1-132 GEN
Solar/Wind Harmer
4.638
971645AH1-323 GEN
50/50
29.723
3150921YORKTN3
50/50
8.624
3144216WINCHST
50/50
1.289
3151101ELIZAR3
50/50
30.975
3151161SURRY 1
50/50
11.975
3142416OLDCHRC
Solar/Wind Harmer
3.208
316382AG1-145 C
Solar/Wind Harmer
0.003
315773AC2-141 GEN
Solar/Wind Harmer
11.84
970293AG2-193 GEN
Solar/Wind Harmer
3.398
944581AF1-123 GEN
Solar/Wind Harmer
71.01
944601AF1-125 GEN
Solar/Wind Harmer
69.916
3142946ENON
Solar/Wind Harmer
0.105
3144873MCLAUGH
Solar/Wind Harmer
0.008
3144536CHRHLND
Solar/Wind Harmer
0.047
3145336SMITFLD
Solar/Wind Harmer
0.125
3151221GRAVEL6
Adder
22.664
3151171GRAVELC
Adder
4.361
3146456SLIGO L269
Solar/Wind Harmer
0.31
971153AH1-033 GEN
Solar/Wind Harmer
3.585
961611AG1-000B GEN
Solar/Wind Harmer
8.272
972255AH1-712 GEN
Adder
157.541
315778AD1-151 GEN
Solar/Wind Harmer
24.551
316320Y1-086
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
18.454
970133AG2-095 GEN
Solar/Wind Harmer
2.91
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
316473AC1-191 GEN
Solar/Wind Harmer
1.014
970661AG2-428 GEN
Solar/Wind Harmer
6.346
3141766HARMONY
Solar/Wind Harmer
3.995
3146626S HERTFORD
Solar/Wind Harmer
0.299
316083AB2-161 GEN
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
3.158
3141843SHACKLE
Adder
1.519
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
315813AE1-149 C
Solar/Wind Harmer
15.819
316280AD1-041 GEN
Solar/Wind Harmer
0.006
3145273HOLLAND
Solar/Wind Harmer
0.221
316156AD2-030 GEN
Solar/Wind Harmer
0.218
3141873WAN 176
Solar/Wind Harmer
5.232
965281AG1-393 GEN
Solar/Wind Harmer
3.137
315839AE2-212 C
Solar/Wind Harmer
0.002
3143096IRON208
Adder
1.226
3143096IRON208
Adder
1.201
3146376EDENTON
Solar/Wind Harmer
0.291
315614AA2-178 GEN
Solar/Wind Harmer
1.626
971157AH1-035 GEN
Solar/Wind Harmer
3.34
315737AD1-076 GEN
Solar/Wind Harmer
3.567
3146206CASHIE
Solar/Wind Harmer
0.273
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3145893MURPHYS
Solar/Wind Harmer
0.451
3145893MURPHYS
Solar/Wind Harmer
0.269
957521AF2-046 GEN
Solar/Wind Harmer
20.016
961681AG1-008 GEN
Solar/Wind Harmer
20.016
962971AG1-146 GEN
Solar/Wind Harmer
4.293
3156021HOLLOMANSOL
Solar/Wind Harmer
1.218
3146173TUNIS
Solar/Wind Harmer
0.267
316463AE2-346 GEN
Solar/Wind Harmer
0.229
316140AB2-099
Solar/Wind Harmer
0.095
962331AG1-082 GEN
Solar/Wind Harmer
2.839
316365GEN2_N
Solar/Wind Harmer
0.59
3145963POPLR C
Solar/Wind Harmer
0.263
970009AG2-005 GEN
Solar/Wind Harmer
1.96
3146263WOODLND
Solar/Wind Harmer
0.261
962571AG1-106 GEN
Solar/Wind Harmer
3.63
960081AF2-299 GEN
Solar/Wind Harmer
2.448
316190AA2-174 GEN
Solar/Wind Harmer
0
3150851SPRUNCC
Adder
1.161
3145796HORNRTN
Solar/Wind Harmer
0.83
3145796HORNRTN
Solar/Wind Harmer
0.251
3145783HORNRTN
Solar/Wind Harmer
0.251
3146293MARTNCO
Solar/Wind Harmer
0.232
316212AC1-099_GEN
Solar/Wind Harmer
1.281
971795AH1-408 GEN
Solar/Wind Harmer
16.501
3141726DUNNSVL
Solar/Wind Harmer
0.979
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
957481AF2-042 GEN
Solar/Wind Harmer
65.115
3147043LAWRENC
Adder
2.208
315722AD1-056 GEN
Solar/Wind Harmer
1.518
316494AC1-189 GEN
Solar/Wind Harmer
0.81
3150351NORNECKC2
Adder
2.352
315693AD1-088 GEN
Solar/Wind Harmer
11.318
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.235
3145493TOT1
Solar/Wind Harmer
1.047
316129AC1-054 GEN
Solar/Wind Harmer
0.885
3146233WITAKRS
Solar/Wind Harmer
0.932
962491AG1-098 GEN
Solar/Wind Harmer
13.368
971065AG2-659 GEN
Solar/Wind Harmer
9.97
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.184
316359AB2-059 GEN
Solar/Wind Harmer
0.827
316049AB1-081 GEN
Solar/Wind Harmer
1.317
3142053HEARTS
Solar/Wind Harmer
0.405
315687AD1-152 GEN
Solar/Wind Harmer
0.007
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970401AG2-262 GEN
Solar/Wind Harmer
1.243
316337AD2-073 GEN
Solar/Wind Harmer
0.18
970685AG2-442 GEN
Solar/Wind Harmer
15.398
963171AG1-166 GEN
Solar/Wind Harmer
1.08
971563AH1-280 GEN
Solar/Wind Harmer
2.16
3144293JTRSVLE
Adder
0.645
316003AC1-222 GEN
Solar/Wind Harmer
0.005
3143526WINTERP
Solar/Wind Harmer
0.968
3146926FARMVIL
Solar/Wind Harmer
0.111
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
970223AG2-152 GEN
Solar/Wind Harmer
10.425
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.085
972003AH1-546 GEN
Solar/Wind Harmer
5.963
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.109
3146802CHATHAM
Solar/Wind Harmer
0.102
941801AE2-185 GEN
Solar/Wind Harmer
4.349
970937AG2-583 GEN
Solar/Wind Harmer
8.286
316336AC2-165 C
Solar/Wind Harmer
0.005
3143336POWHATN
Solar/Wind Harmer
2.393
3143226MDLTHAN
Solar/Wind Harmer
0.134
971377AH1-170 GEN
Solar/Wind Harmer
1.425
3147623JAMES R
Solar/Wind Harmer
0.31
972135AH1-637 GEN
Solar/Wind Harmer
1.098
270173AC1-122 GEN
Solar/Wind Harmer
0.31
270030AE2-140 GEN
Solar/Wind Harmer
13.116
315705AF1-075 GEN
Solar/Wind Harmer
4.718
962751AG1-124 GEN
Solar/Wind Harmer
5.402
316045AC1-158 PL2
Solar/Wind Helper
6.543
316006AB2-029 C
Solar/Wind Helper
0.142
316254AC1-120 GEN1
Solar/Wind Helper
1.333
3147666LOUISA
Solar/Wind Helper
1.029
316192AB2-158 GEN
Solar/Wind Helper
1.689
223401AF1-299 GEN
Solar/Wind Helper
0.346
23779801AA1-109
Solar/Wind Helper
0.161
970917AG2-570 GEN
Solar/Wind Harmer
23.14
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.259
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
313506AB2-031 GEN
Solar/Wind Harmer
0.784
316404AE1-155 C
Solar/Wind Harmer
0.057
3150861SPRUNCD
Adder
1.161
3145796HORNRTN
Solar/Wind Harmer
1.006
3145796HORNRTN
Solar/Wind Harmer
0.251
3145933PARMELE
Solar/Wind Harmer
0.25
966801AG1-551 GEN
Solar/Wind Harmer
2.916
316210AC1-098 GEN
Solar/Wind Harmer
2.297
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3147043LAWRENC
Solar/Wind Harmer
0.146
315724AD1-057 GEN
Solar/Wind Harmer
0.9
316327AA2-057 GEN
Solar/Wind Harmer
0.36
3150351NORNECKC2
Adder
2.392
316478AD1-087 GEN
Solar/Wind Harmer
0.823
316486AD2-202 GEN
Solar/Wind Harmer
0.242
3146073TAR RVR
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
0.235
3146233WITAKRS
Solar/Wind Harmer
1.176
3146233WITAKRS
Solar/Wind Harmer
0.159
3138543CONSLDL
Solar/Wind Harmer
0.154
961601AG1-000A GEN
Solar/Wind Harmer
16.379
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.23
971623AH1-311 GEN
Solar/Wind Harmer
0.46
316131AB2-060 GEN
Solar/Wind Harmer
0.687
964241AG1-285 GEN
Solar/Wind Harmer
14.393
315785AD2-033 C
Solar/Wind Harmer
1.721
970257AG2-171 GEN
Solar/Wind Harmer
6.725
959311AF2-222 GEN
Solar/Wind Harmer
18.581
971781AH1-399 GEN
Solar/Wind Harmer
0.272
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.82
970909AG2-566 GEN
Solar/Wind Harmer
2.199
963181AG1-167 GEN
Solar/Wind Harmer
0.81
3144293JTRSVLE
Adder
0.645
3147133PAMPLIN
Solar/Wind Harmer
0.627
971193AH1-056 GEN
Solar/Wind Harmer
12.172
971683AH1-343 GEN
Solar/Wind Harmer
7.141
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316283AC2-100 C
Solar/Wind Harmer
0.376
3146926FARMVIL
Solar/Wind Harmer
0.111
3141906WESTMOR
Solar/Wind Harmer
0.07
3146776BUCKING
Solar/Wind Harmer
0.058
970737AG2-469 GEN
Solar/Wind Harmer
6.299
270197AD1-017 GEN1
Solar/Wind Harmer
0.911
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.478
3147312GRETNA
Solar/Wind Harmer
0.027
941821AE2-187 GEN
Solar/Wind Harmer
4.349
3148013FISHERV
Solar/Wind Harmer
0.135
316313AB2-026
Solar/Wind Harmer
0.085
316258AE1-075 C
Solar/Wind Harmer
0.102
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.034
970221AG2-151 GEN
Solar/Wind Harmer
7.125
270018AE2-047 C O1
Solar/Wind Harmer
0.003
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
958131AF2-107 GEN
Solar/Wind Harmer
3.424
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
2.104
316044AC1-158 PL1
Solar/Wind Helper
2.044
316450AC1-158 RIC
Solar/Wind Helper
0.545
3141196NOKESVL
Solar/Wind Helper
1.216
316170AC1-121 GEN2
Solar/Wind Helper
0.444
227287AC2-120 GEN
Solar/Wind Helper
0.383
226910AB2-157 C
Solar/Wind Helper
0.016
3147666LOUISA
Solar/Wind Helper
0.591
223402AF1-300 C
Solar/Wind Helper
0.346
237030AB1-096 C
Solar/Wind Helper
0.06
972263AH1-716 GEN
50/50
194.204
3151081ELIZAR1
50/50
30.584
3151091ELIZAR2
50/50
30.053
941591AE2-156 GEN
50/50
27.947
3152611GOSPORTB
50/50
4.245
3152621GOSPORTC
50/50
3.603
3152601GOSPORTA
50/50
3.323
315976AC1-164 GENA
Solar/Wind Harmer
34.449
316169AC1-164_GENC
Solar/Wind Harmer
29.761
315975AC1-164 GENB
Solar/Wind Harmer
1.019
316312AB1-027
Solar/Wind Harmer
0.592
971445AH1-216 GEN
Solar/Wind Harmer
22.015
972265AH1-717 GEN
Adder
24.205
3151201GRAVEL4
Adder
22.69
3151191GRAVEL3
Adder
22.403
3151211GRAVEL5
Adder
22.403
957871AF2-081 GEN
Solar/Wind Harmer
15.477
319010AE1-072 C
Solar/Wind Harmer
1.561
3146406KITTY HAWK
Solar/Wind Harmer
0.039
3138283WHITEMARSH
Solar/Wind Harmer
0.072
316305AF2-043 C
Solar/Wind Harmer
0.002
316369SG1_INVT
Solar/Wind Harmer
0.011
972193AH1-681 GEN
Adder
7.039
313526AB2-022
Solar/Wind Harmer
0.166
316132AB2-190 GEN1
Solar/Wind Harmer
1.639
3146486SUNBURY
Solar/Wind Harmer
0.305
3146486SUNBURY
Solar/Wind Harmer
0.305
315835AF2-110_GEN
Solar/Wind Harmer
2.092
316321Z2-027
Solar/Wind Harmer
0.057
3146396TANGLEW
Solar/Wind Harmer
0.839
3145176PASQUOTANK
Solar/Wind Harmer
0.189
316314AB2-024 C
Solar/Wind Harmer
0.001
316311AC2-079 GEN
Solar/Wind Harmer
8.688
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.207
3143873LANEXA
Solar/Wind Harmer
0.181
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
971167AH1-042 GEN
Solar/Wind Harmer
26.63
316059AD1-063 C
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
8.811
315662AE1-191 GEN
Solar/Wind Harmer
0.01
315666AE1-190 GEN
Solar/Wind Harmer
0.002
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.292
3130156CHOWAN
Solar/Wind Harmer
0.292
3143316POE
Solar/Wind Harmer
1.153
3141913WHIT STONE
Solar/Wind Harmer
0.285
315816AE2-034 GEN
Solar/Wind Harmer
1.219
3138133OCRAN
Solar/Wind Harmer
0.085
316315AB2-025 C
Solar/Wind Harmer
0.226
315814AE2-033 C
Solar/Wind Harmer
22.041
941031AE2-094 GEN
Solar/Wind Harmer
51.279
944011AF1-069 GEN
Solar/Wind Harmer
16.755
3141783LANCAST
Solar/Wind Harmer
0.167
3141783LANCAST
Solar/Wind Harmer
0.111
3130546PLYMOUTH
Solar/Wind Harmer
0.278
315732AD1-074 GEN1
Solar/Wind Harmer
1.593
315733AD1-074 GEN2
Solar/Wind Harmer
1.593
315735AD1-075 GEN1
Solar/Wind Harmer
0.797
970673AG2-436 GEN
Solar/Wind Harmer
58.436
970673AG2-436 GEN
Solar/Wind Harmer
38.957
3146206CASHIE
Solar/Wind Harmer
0.273
970601AG2-382 GEN
Solar/Wind Harmer
10.212
965291AG1-394 GEN
Solar/Wind Harmer
1.209
971967AH1-528 GEN
Solar/Wind Harmer
43.16
3145893MURPHYS
Solar/Wind Harmer
0.728
3145893MURPHYS
Solar/Wind Harmer
0.269
962981AG1-147 GEN
Solar/Wind Harmer
10.018
3145513AHOSKIE
Solar/Wind Harmer
0.556
3145513AHOSKIE
Solar/Wind Harmer
0.266
3145683EARLEYS
Solar/Wind Harmer
0.53
3145683EARLEYS
Solar/Wind Harmer
0.265
3145683EARLEYS
Solar/Wind Harmer
0.265
970327AG2-215 GEN
Solar/Wind Harmer
8.614
3146043SEABORD
Solar/Wind Harmer
0.261
315607AA1-063A GEN
Solar/Wind Harmer
0.531
970085AG2-068 GEN
Solar/Wind Harmer
13.834
970581AG2-369 GEN
Solar/Wind Harmer
11.898
315652AC1-086 GEN
Solar/Wind Harmer
28.063
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3137643SOCKMAN
Solar/Wind Harmer
1.011
3146033SCOT NK
Solar/Wind Harmer
1.01
971285AH1-108 GEN
Adder
1.899
3145796HORNRTN
Solar/Wind Harmer
0.805
3145796HORNRTN
Solar/Wind Harmer
0.101
316005AA1-067
Solar/Wind Harmer
0.262
3145746EVERETS
Solar/Wind Harmer
0.973
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
970181AG2-120 GEN
Solar/Wind Harmer
3.044
957861AF2-080 GEN
Solar/Wind Harmer
10.333
316420AA1-050 GEN
Solar/Wind Harmer
0.008
970831AG2-522 GEN
Solar/Wind Harmer
10.106
3141813NORNECK
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.235
3145573BETHELC
Solar/Wind Harmer
0.235
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
972189AH1-679 GEN
Adder
3.657
971443AH1-215 GEN
Solar/Wind Harmer
3.537
3144303KENBRDG
Solar/Wind Harmer
0.168
316118AC1-105 GEN
Solar/Wind Harmer
0.54
3147173SINAI
Solar/Wind Harmer
0.207
3147243WELCO
Solar/Wind Harmer
0.129
970683AG2-441 GEN
Solar/Wind Harmer
13.748
970681AG2-440 GEN
Solar/Wind Harmer
10.999
946301AF1-294 GEN
Solar/Wind Harmer
3.996
961791AG1-021 GEN
Solar/Wind Harmer
1.944
315657AE1-056 GEN
Solar/Wind Harmer
6.894
970865AG2-541 GEN
Solar/Wind Harmer
6.515
316233AE1-074 FULL
Solar/Wind Harmer
0.149
971281AH1-106 GEN
Solar/Wind Harmer
2.583
971283AH1-107 GEN
Solar/Wind Harmer
2.583
316223AC1-118
Solar/Wind Harmer
0.126
316123AC1-075 GEN
Solar/Wind Harmer
0.24
970165AG2-112 GEN
Solar/Wind Harmer
1.423
970163AG2-111 GEN
Solar/Wind Harmer
1.357
970285AG2-188 GEN
Solar/Wind Harmer
13.264
971845AH1-439 GEN
Solar/Wind Harmer
7.44
3148463FAIRFLD
Solar/Wind Harmer
0.138
3151881LOWMORC
Adder
1.466
3151881LOWMORC
Adder
1.443
3151861LOWMORA
Adder
1.42
3148133STUARTS
Solar/Wind Harmer
0.081
3148013FISHERV
Solar/Wind Harmer
0.078
972205AH1-687 GEN
Adder
5.785
971447AH1-217 GEN
Solar/Wind Harmer
4.064
270494AE1-108_GEN
Solar/Wind Harmer
1.551
270069AE2-166 C O1
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Helper
1.573
316411AF1-147_GEN1
Solar/Wind Helper
0.945
316415AF1-147_GEN2
Solar/Wind Helper
0.945
3138216PACIFIC
Solar/Wind Helper
0.046
3141426STAFORD
Solar/Wind Helper
0.055
3142296MT RD221
50/50
1.096
3150991CHESPKB
50/50
3.492
3150991CHESPKB
50/50
3.408
316075AC2-137 C
Solar/Wind Harmer
0.09
3142946ENON
Solar/Wind Harmer
0.031
316036AC1-147 C
Solar/Wind Harmer
0.058
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.301
316185AD1-033 GEN
Solar/Wind Harmer
0.009
316236AE1-162_GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
1.25
3145506HICKORY
Solar/Wind Harmer
0.75
3145506HICKORY
Solar/Wind Harmer
0.188
316339AD2-160 GEN
Solar/Wind Harmer
0.505
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.174
3150691DARBY 3
Adder
22.343
3150701DARBY 4
Adder
22.291
3150681DARBY 2
Adder
22.265
3150671DARBY 1
Adder
22.239
3137176SLIGO L2192
Solar/Wind Harmer
1.234
3146456SLIGO L269
Solar/Wind Harmer
5.488
3130086AYDLETT
Solar/Wind Harmer
1.238
316033AB2-134 GEN
Solar/Wind Harmer
0.018
315697AD1-025 GEN
Solar/Wind Harmer
0.346
3146386ELIZ CT
Solar/Wind Harmer
0.306
3142366NRTHEST
Adder
1
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
966871AG1-558 GEN
Solar/Wind Harmer
0.347
970657AG2-426 GEN
Solar/Wind Harmer
10.482
970657AG2-426 GEN
Solar/Wind Harmer
2.198
3146626S HERTFORD
Solar/Wind Harmer
0.299
3146626S HERTFORD
Solar/Wind Harmer
0.299
944641AF1-129 GEN
Adder
140.632
316240AF1-291 C
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
1.297
3146376EDENTON
Solar/Wind Harmer
1.297
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3144356SAPONY
Solar/Wind Harmer
2.337
316065AD1-022 GEN
Solar/Wind Harmer
12.657
972185AH1-677 GEN
Adder
15.245
3145893MURPHYS
Solar/Wind Harmer
1.804
3145893MURPHYS
Solar/Wind Harmer
0.485
972187AH1-678 GEN
Adder
7.651
3146173TUNIS
Solar/Wind Harmer
0.267
3146173TUNIS
Solar/Wind Harmer
0.267
970933AG2-581 GEN
Solar/Wind Harmer
21
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
316426AA2-053 GEN
Solar/Wind Harmer
0.86
316181AB2-040 GEN
Solar/Wind Harmer
0.368
958261AF2-120 GEN
Solar/Wind Harmer
8.365
3145593CAROLNA
Solar/Wind Harmer
0.252
3145593CAROLNA
Solar/Wind Harmer
0.252
966811AG1-552 GEN
Solar/Wind Harmer
2.738
3145593CAROLNA
Solar/Wind Harmer
0.314
3145796HORNRTN
Solar/Wind Harmer
0.754
3145783HORNRTN
Solar/Wind Harmer
4.467
3145783HORNRTN
Solar/Wind Harmer
3.574
3145783HORNRTN
Solar/Wind Harmer
1.117
3145783HORNRTN
Solar/Wind Harmer
0.447
3145933PARMELE
Solar/Wind Harmer
0.501
3145933PARMELE
Solar/Wind Harmer
0.25
316274AC1-208 GEN
Solar/Wind Harmer
1.272
970099AG2-077 GEN
Solar/Wind Harmer
26.046
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.471
3150341NORNECKC1
Adder
2.451
3145493TOT1
Solar/Wind Harmer
0.546
3145453TOT5
Solar/Wind Harmer
0.327
3145603CNETO
Solar/Wind Harmer
0.218
961601AG1-000A GEN
Solar/Wind Harmer
4.095
316263AC1-034 GEN
Solar/Wind Harmer
8.746
939181AE1-148 GEN
Solar/Wind Harmer
10.786
313527AB2-043 GEN
Solar/Wind Harmer
0.003
971741AH1-377 GEN
Solar/Wind Harmer
21.126
962561AG1-105 GEN
Solar/Wind Harmer
10.222
964791AG1-342 GEN
Solar/Wind Harmer
4.068
3146843MT LREL
Solar/Wind Harmer
0.212
3146843MT LREL
Solar/Wind Harmer
0.212
970323AG2-213 GEN
Solar/Wind Harmer
8.967
971775AH1-396 GEN
Solar/Wind Harmer
0.336
316034AC1-036 C
Solar/Wind Harmer
0.015
316468AD1-105 GEN
Solar/Wind Harmer
-0.067
970301AG2-198 GEN
Solar/Wind Harmer
8.797
958211AF2-115 GEN
Solar/Wind Harmer
2.43
963191AG1-168 GEN
Solar/Wind Harmer
0.81
3144293JTRSVLE
Adder
0.645
3144293JTRSVLE
Adder
0.543
3147133PAMPLIN
Solar/Wind Harmer
0.2
3147133PAMPLIN
Solar/Wind Harmer
0.16
316222AC1-221 GEN
Solar/Wind Harmer
0.802
3143526WINTERP
Solar/Wind Harmer
0.968
942751AE2-291 GEN
Solar/Wind Harmer
9.118
3146776BUCKING
Solar/Wind Harmer
0.649
3146776BUCKING
Solar/Wind Harmer
0.052
270013AE1-250 PV
Solar/Wind Harmer
0.004
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.383
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971223AH1-071 GEN
Solar/Wind Harmer
1.43
971489AH1-241 GEN
Solar/Wind Harmer
7.125
316447AC1-158 HLD
Solar/Wind Helper
4.499
315651AD1-115 GEN
Solar/Wind Helper
0.98
226929AD2-058 GEN
Solar/Wind Helper
0.113
23777801MSM_W1-116
Solar/Wind Helper
0.096
237025AB1-124 C
Solar/Wind Helper
0.14
237006AB1-125 GEN
Solar/Wind Helper
0.105
CPLELTFEXP_CPLE->PJM
CLTF
15.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
70.159
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.437
MECLTFEXP_MEC->PJM
CLTF
6.883
SIGELTFEXP_SIGE->PJM
CLTF
0.213
NYPJM->LTFIMP_NY
CLTF
4.044
LGEELTFEXP_LGEE->PJM
CLTF
2.658
WECLTFEXP_WEC->PJM
CLTF
1.346
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
12.709
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.309
TVALTFEXP_TVA->PJM
CLTF
6.437

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.98 %
Rating:4070.2 MVA
Rating Type:A
MVA to Mitigate:4842.75
MW Contribution:1.05
Bus #Bus NameTypeMW Contribution
3152181CUNINGC
50/50
2.565
972193AH1-681 GEN
50/50
7.545
316312AB1-027
Solar/Wind Harmer
0.575
315976AC1-164 GENA
Solar/Wind Harmer
32.144
316169AC1-164_GENC
Solar/Wind Harmer
27.769
315975AC1-164 GENB
Solar/Wind Harmer
0.951
316314AB2-024 C
Solar/Wind Harmer
0.001
971167AH1-042 GEN
Solar/Wind Harmer
24.413
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3143873LANEXA
Solar/Wind Harmer
0.165
316059AD1-063 C
Solar/Wind Harmer
0.002
3138283WHITEMARSH
Solar/Wind Harmer
0.062
970189AG2-124 GEN
Solar/Wind Harmer
7.953
315662AE1-191 GEN
Solar/Wind Harmer
0.009
315666AE1-190 GEN
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
1.424
3141873WAN 176
Solar/Wind Harmer
0.053
316369SG1_INVT
Solar/Wind Harmer
0.01
972265AH1-717 GEN
Adder
20.019
3151201GRAVEL4
Adder
18.766
3151191GRAVEL3
Adder
18.528
3151211GRAVEL5
Adder
18.528
3141913WHIT STONE
Solar/Wind Harmer
0.256
3138133OCRAN
Solar/Wind Harmer
0.076
971445AH1-216 GEN
Solar/Wind Harmer
17.851
971285AH1-108 GEN
Adder
1.911
3141783LANCAST
Solar/Wind Harmer
0.15
3141783LANCAST
Solar/Wind Harmer
0.1
3151081ELIZAR1
Adder
22.486
3151091ELIZAR2
Adder
22.095
3152611GOSPORTB
Adder
3.124
3152621GOSPORTC
Adder
2.651
3152601GOSPORTA
Adder
2.446
962981AG1-147 GEN
Solar/Wind Harmer
9.042
957871AF2-081 GEN
Solar/Wind Harmer
12.005
319010AE1-072 C
Solar/Wind Harmer
1.21
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
316311AC2-079 GEN
Solar/Wind Harmer
6.837
970327AG2-215 GEN
Solar/Wind Harmer
7.789
315835AF2-110_GEN
Solar/Wind Harmer
1.628
313526AB2-022
Solar/Wind Harmer
0.128
3146486SUNBURY
Solar/Wind Harmer
0.236
3146486SUNBURY
Solar/Wind Harmer
0.236
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.649
3145176PASQUOTANK
Solar/Wind Harmer
0.146
3143316POE
Solar/Wind Harmer
0.911
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.224
3130156CHOWAN
Solar/Wind Harmer
0.224
972189AH1-679 GEN
Adder
3.73
315816AE2-034 GEN
Solar/Wind Harmer
0.93
316233AE1-074 FULL
Solar/Wind Harmer
0.173
971281AH1-106 GEN
Solar/Wind Harmer
3.003
971283AH1-107 GEN
Solar/Wind Harmer
3.003
3141813NORNECK
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
0.211
315732AD1-074 GEN1
Solar/Wind Harmer
1.209
315733AD1-074 GEN2
Solar/Wind Harmer
1.209
315735AD1-075 GEN1
Solar/Wind Harmer
0.605
3146206CASHIE
Solar/Wind Harmer
0.207
970601AG2-382 GEN
Solar/Wind Harmer
7.721
965291AG1-394 GEN
Solar/Wind Harmer
0.911
3145893MURPHYS
Solar/Wind Harmer
0.548
3145893MURPHYS
Solar/Wind Harmer
0.203
316315AB2-025 C
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
16.008
3145513AHOSKIE
Solar/Wind Harmer
0.417
3145513AHOSKIE
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.397
3145683EARLEYS
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.198
3146043SEABORD
Solar/Wind Harmer
0.194
315607AA1-063A GEN
Solar/Wind Harmer
0.395
315652AC1-086 GEN
Solar/Wind Harmer
20.636
3146033SCOT NK
Solar/Wind Harmer
0.749
316087AB2-174 GEN
Solar/Wind Harmer
0.005
3137643SOCKMAN
Solar/Wind Harmer
0.742
3145796HORNRTN
Solar/Wind Harmer
0.591
3145796HORNRTN
Solar/Wind Harmer
0.074
316005AA1-067
Solar/Wind Harmer
0.194
3145746EVERETS
Solar/Wind Harmer
0.72
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
970181AG2-120 GEN
Solar/Wind Harmer
2.254
957861AF2-080 GEN
Solar/Wind Harmer
7.61
941031AE2-094 GEN
Solar/Wind Harmer
32.353
944011AF1-069 GEN
Solar/Wind Harmer
10.571
316420AA1-050 GEN
Solar/Wind Harmer
0.006
970673AG2-436 GEN
Solar/Wind Harmer
37.059
970673AG2-436 GEN
Solar/Wind Harmer
24.706
3145573BETHELC
Solar/Wind Harmer
0.172
3145573BETHELC
Solar/Wind Harmer
0.172
971967AH1-528 GEN
Solar/Wind Harmer
27.582
970831AG2-522 GEN
Solar/Wind Harmer
7.305
316319Z2-044 C
Solar/Wind Harmer
0
970085AG2-068 GEN
Solar/Wind Harmer
8.909
970581AG2-369 GEN
Solar/Wind Harmer
7.662
316223AC1-118
Solar/Wind Harmer
0.117
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.618
3144303KENBRDG
Solar/Wind Harmer
0.124
970683AG2-441 GEN
Solar/Wind Harmer
10.305
970681AG2-440 GEN
Solar/Wind Harmer
8.244
946301AF1-294 GEN
Solar/Wind Harmer
3.029
961791AG1-021 GEN
Solar/Wind Harmer
1.473
315657AE1-056 GEN
Solar/Wind Harmer
5.267
316118AC1-105 GEN
Solar/Wind Harmer
0.384
3142296MT RD221
50/50
1.091
3150691DARBY 3
50/50
22.95
3150701DARBY 4
50/50
22.896
3150681DARBY 2
50/50
22.869
3150671DARBY 1
50/50
22.843
3142366NRTHEST
50/50
1.033
316075AC2-137 C
Solar/Wind Harmer
0.085
966871AG1-558 GEN
Solar/Wind Harmer
0.344
3142946ENON
Solar/Wind Harmer
0.029
316033AB2-134 GEN
Solar/Wind Harmer
0.015
315697AD1-025 GEN
Solar/Wind Harmer
0.295
944641AF1-129 GEN
Adder
124.433
316240AF1-291 C
Solar/Wind Harmer
0.002
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.046
3150991CHESPKB
Adder
2.57
3150991CHESPKB
Adder
2.508
316316AC1-027 C
Solar/Wind Harmer
0.234
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.97
3145506HICKORY
Solar/Wind Harmer
0.582
3145506HICKORY
Solar/Wind Harmer
0.146
316339AD2-160 GEN
Solar/Wind Harmer
0.392
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.135
3137176SLIGO L2192
Solar/Wind Harmer
0.957
3146456SLIGO L269
Solar/Wind Harmer
4.255
3130086AYDLETT
Solar/Wind Harmer
0.96
970657AG2-426 GEN
Solar/Wind Harmer
8.387
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3146386ELIZ CT
Solar/Wind Harmer
0.237
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.23
3146626S HERTFORD
Solar/Wind Harmer
0.23
958261AF2-120 GEN
Solar/Wind Harmer
7.587
3146376EDENTON
Solar/Wind Harmer
0.994
3146376EDENTON
Solar/Wind Harmer
0.994
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
1.125
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.255
3150341NORNECKC1
Adder
2.237
316468AD1-105 GEN
Solar/Wind Harmer
-0.068
316065AD1-022 GEN
Solar/Wind Harmer
9.583
3145893MURPHYS
Solar/Wind Harmer
1.358
3145893MURPHYS
Solar/Wind Harmer
0.365
3144356SAPONY
Solar/Wind Harmer
1.697
3146173TUNIS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.114
316426AA2-053 GEN
Solar/Wind Harmer
0.635
3145933PARMELE
Solar/Wind Harmer
0.373
3145933PARMELE
Solar/Wind Harmer
0.186
316181AB2-040 GEN
Solar/Wind Harmer
0.27
3145593CAROLNA
Solar/Wind Harmer
0.186
3145593CAROLNA
Solar/Wind Harmer
0.186
966811AG1-552 GEN
Solar/Wind Harmer
2.014
3145593CAROLNA
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
3.287
3145783HORNRTN
Solar/Wind Harmer
2.629
3145783HORNRTN
Solar/Wind Harmer
0.822
3145783HORNRTN
Solar/Wind Harmer
0.329
3145796HORNRTN
Solar/Wind Harmer
0.554
971223AH1-071 GEN
Solar/Wind Harmer
1.938
316274AC1-208 GEN
Solar/Wind Harmer
0.935
972185AH1-677 GEN
Adder
9.694
3145493TOT1
Solar/Wind Harmer
0.4
3145453TOT5
Solar/Wind Harmer
0.24
3145603CNETO
Solar/Wind Harmer
0.16
972187AH1-678 GEN
Adder
4.882
970933AG2-581 GEN
Solar/Wind Harmer
13.585
961601AG1-000A GEN
Solar/Wind Harmer
2.983
316263AC1-034 GEN
Solar/Wind Harmer
6.369
970099AG2-077 GEN
Solar/Wind Harmer
17.402
939181AE1-148 GEN
Solar/Wind Harmer
7.706
313527AB2-043 GEN
Solar/Wind Harmer
0.002
970323AG2-213 GEN
Solar/Wind Harmer
6.645
971775AH1-396 GEN
Solar/Wind Harmer
0.249
316034AC1-036 C
Solar/Wind Harmer
0.011
971741AH1-377 GEN
Solar/Wind Harmer
15.41
970301AG2-198 GEN
Solar/Wind Harmer
6.555
958211AF2-115 GEN
Solar/Wind Harmer
1.842
963191AG1-168 GEN
Solar/Wind Harmer
0.614
3144293JTRSVLE
Adder
0.489
3144293JTRSVLE
Adder
0.411
3147133PAMPLIN
Solar/Wind Harmer
0.153
3147133PAMPLIN
Solar/Wind Harmer
0.122
962561AG1-105 GEN
Solar/Wind Harmer
7.312
964791AG1-342 GEN
Solar/Wind Harmer
2.904
3146843MT LREL
Solar/Wind Harmer
0.151
3146843MT LREL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.569
3146776BUCKING
Solar/Wind Harmer
0.046
316222AC1-221 GEN
Solar/Wind Harmer
0.567
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971489AH1-241 GEN
Solar/Wind Harmer
7.112
942751AE2-291 GEN
Solar/Wind Harmer
6.853
316447AC1-158 HLD
Solar/Wind Helper
3.611
226929AD2-058 GEN
Solar/Wind Helper
0.096
315651AD1-115 GEN
Solar/Wind Helper
0.797
3147173SINAI
Solar/Wind Harmer
0.146
3147243WELCO
Solar/Wind Harmer
0.091
970285AG2-188 GEN
Solar/Wind Harmer
11.379
971845AH1-439 GEN
Solar/Wind Harmer
6.479
3148133STUARTS
Solar/Wind Harmer
0.084
3148013FISHERV
Solar/Wind Harmer
0.081
3148463FAIRFLD
Solar/Wind Harmer
0.139
3151881LOWMORC
Adder
1.484
3151881LOWMORC
Adder
1.461
3151861LOWMORA
Adder
1.437
970865AG2-541 GEN
Solar/Wind Harmer
4.73
972205AH1-687 GEN
Adder
5.79
971447AH1-217 GEN
Solar/Wind Harmer
4.07
316123AC1-075 GEN
Solar/Wind Harmer
0.178
970165AG2-112 GEN
Solar/Wind Harmer
1.054
970163AG2-111 GEN
Solar/Wind Harmer
1.006
270494AE1-108_GEN
Solar/Wind Harmer
1.506
316164AC1-076 GEN
Solar/Wind Helper
1.291
316411AF1-147_GEN1
Solar/Wind Helper
0.798
316415AF1-147_GEN2
Solar/Wind Helper
0.798
3138216PACIFIC
Solar/Wind Helper
0.039
971645AH1-323 GEN
50/50
29.668
3152191CUNINGD
50/50
5.586
3152171CUNINGB
50/50
2.411
972255AH1-712 GEN
50/50
168.86
3142416OLDCHRC
Solar/Wind Harmer
3.115
970293AG2-193 GEN
Solar/Wind Harmer
3.254
316473AC1-191 GEN
Solar/Wind Harmer
1.006
3142946ENON
Solar/Wind Harmer
0.098
316382AG1-145 C
Solar/Wind Harmer
0.002
3143096IRON208
Adder
1.181
3143096IRON208
Adder
1.157
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3150921YORKTN3
Adder
6.858
3144216WINCHST
Adder
1.022
3141766HARMONY
Solar/Wind Harmer
3.615
3141843SHACKLE
Adder
1.372
970133AG2-095 GEN
Solar/Wind Harmer
2.576
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
970129AG2-093 GEN
Solar/Wind Harmer
16.057
316156AD2-030 GEN
Solar/Wind Harmer
0.195
3141873WAN 176
Solar/Wind Harmer
4.689
315778AD1-151 GEN
Solar/Wind Harmer
21.096
961611AG1-000B GEN
Solar/Wind Harmer
6.924
3151221GRAVEL6
Adder
18.744
3151171GRAVELC
Adder
3.606
3150861SPRUNCD
Adder
1.168
3145336SMITFLD
Solar/Wind Harmer
0.101
315773AC2-141 GEN
Solar/Wind Harmer
9.204
965281AG1-393 GEN
Solar/Wind Harmer
2.675
3144536CHRHLND
Solar/Wind Harmer
0.037
315839AE2-212 C
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
22.773
3144873MCLAUGH
Solar/Wind Harmer
0.006
944581AF1-123 GEN
Solar/Wind Harmer
54.983
944601AF1-125 GEN
Solar/Wind Harmer
54.137
962971AG1-146 GEN
Solar/Wind Harmer
3.875
315813AE1-149 C
Solar/Wind Harmer
12.831
3146456SLIGO L269
Solar/Wind Harmer
0.24
971153AH1-033 GEN
Solar/Wind Harmer
2.78
970659AG2-427 GEN
Solar/Wind Harmer
2.536
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970661AG2-428 GEN
Solar/Wind Harmer
5.061
970009AG2-005 GEN
Solar/Wind Harmer
1.772
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.23
316404AE1-155 C
Solar/Wind Harmer
0.052
3145273HOLLAND
Solar/Wind Harmer
0.171
3146376EDENTON
Solar/Wind Harmer
0.224
315614AA2-178 GEN
Solar/Wind Harmer
1.24
3150351NORNECKC2
Adder
2.183
971157AH1-035 GEN
Solar/Wind Harmer
2.537
315737AD1-076 GEN
Solar/Wind Harmer
2.707
971781AH1-399 GEN
Solar/Wind Harmer
0.275
3146206CASHIE
Solar/Wind Harmer
0.207
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3145893MURPHYS
Solar/Wind Harmer
0.34
3145893MURPHYS
Solar/Wind Harmer
0.203
957521AF2-046 GEN
Solar/Wind Harmer
15.055
961681AG1-008 GEN
Solar/Wind Harmer
15.055
3156021HOLLOMANSOL
Solar/Wind Harmer
0.916
3146173TUNIS
Solar/Wind Harmer
0.201
316463AE2-346 GEN
Solar/Wind Harmer
0.171
316140AB2-099
Solar/Wind Harmer
0.071
962331AG1-082 GEN
Solar/Wind Harmer
2.13
3145963POPLR C
Solar/Wind Harmer
0.197
3146263WOODLND
Solar/Wind Harmer
0.195
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.193
316365GEN2_N
Solar/Wind Harmer
0.432
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145933PARMELE
Solar/Wind Harmer
0.186
966801AG1-551 GEN
Solar/Wind Harmer
2.17
313506AB2-031 GEN
Solar/Wind Harmer
0.575
3145796HORNRTN
Solar/Wind Harmer
0.739
3145796HORNRTN
Solar/Wind Harmer
0.185
316210AC1-098 GEN
Solar/Wind Harmer
1.695
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3147043LAWRENC
Solar/Wind Harmer
0.107
315724AD1-057 GEN
Solar/Wind Harmer
0.658
316327AA2-057 GEN
Solar/Wind Harmer
0.264
3146073TAR RVR
Solar/Wind Harmer
0.172
3146083TARBORO
Solar/Wind Harmer
0.172
3146233WITAKRS
Solar/Wind Harmer
0.859
3146233WITAKRS
Solar/Wind Harmer
0.116
3138543CONSLDL
Solar/Wind Harmer
0.113
961601AG1-000A GEN
Solar/Wind Harmer
11.93
3145543BTLEBRO
Solar/Wind Harmer
0.167
3145543BTLEBRO
Solar/Wind Harmer
0.167
971623AH1-311 GEN
Solar/Wind Harmer
0.335
970917AG2-570 GEN
Solar/Wind Harmer
14.887
316313AB2-026
Solar/Wind Harmer
0.103
316258AE1-075 C
Solar/Wind Harmer
0.123
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.467
3141906WESTMOR
Solar/Wind Harmer
0.065
316478AD1-087 GEN
Solar/Wind Harmer
0.557
316486AD2-202 GEN
Solar/Wind Harmer
0.164
316131AB2-060 GEN
Solar/Wind Harmer
0.497
964241AG1-285 GEN
Solar/Wind Harmer
10.495
315785AD2-033 C
Solar/Wind Harmer
1.27
970257AG2-171 GEN
Solar/Wind Harmer
4.984
959311AF2-222 GEN
Solar/Wind Harmer
13.814
970909AG2-566 GEN
Solar/Wind Harmer
1.639
963181AG1-167 GEN
Solar/Wind Harmer
0.614
3144293JTRSVLE
Adder
0.489
3147133PAMPLIN
Solar/Wind Harmer
0.479
971193AH1-056 GEN
Solar/Wind Harmer
9.299
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.089
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.236
3146776BUCKING
Solar/Wind Harmer
0.051
3148013FISHERV
Solar/Wind Harmer
0.14
971683AH1-343 GEN
Solar/Wind Harmer
5.137
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.496
970737AG2-469 GEN
Solar/Wind Harmer
5.853
316283AC2-100 C
Solar/Wind Harmer
0.266
970221AG2-151 GEN
Solar/Wind Harmer
7.112
316044AC1-158 PL1
Solar/Wind Helper
1.64
316450AC1-158 RIC
Solar/Wind Helper
0.438
3141196NOKESVL
Solar/Wind Helper
1.029
227287AC2-120 GEN
Solar/Wind Helper
0.327
226910AB2-157 C
Solar/Wind Helper
0.013
316170AC1-121 GEN2
Solar/Wind Helper
0.36
3152161CUNINGA
50/50
2.401
972277AH1-723 GEN
50/50
196.773
3142416OLDCHRC
Solar/Wind Harmer
0.835
3142416OLDCHRC
Solar/Wind Harmer
0.32
316159AE1-175 C
Solar/Wind Harmer
0.248
944631AF1-128 GEN
Adder
136.402
3143096IRON208
Adder
1.181
971317AH1-138 GEN
Solar/Wind Harmer
2.064
3142433PROV 92
Solar/Wind Harmer
1.099
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3138126ROCKLANDING
Solar/Wind Harmer
0.125
3141766HARMONY
Solar/Wind Harmer
0.054
3142543TWELFTH
Solar/Wind Harmer
0.026
971777AH1-397 GEN
Solar/Wind Harmer
0.709
3141843SHACKLE
Adder
1.372
970129AG2-093 GEN
Solar/Wind Harmer
7.556
316458AB2-190 GEN2
Solar/Wind Harmer
1.424
971069AG2-661 GEN
Solar/Wind Harmer
4.688
971647AH1-324 GEN
Solar/Wind Harmer
11.14
961611AG1-000B GEN
Solar/Wind Harmer
13.616
3151171GRAVELC
Adder
2.743
3138133OCRAN
Solar/Wind Harmer
0.153
315671AE2-027_GEN
Solar/Wind Harmer
16.232
3150851SPRUNCC
Adder
1.168
3145336SMITFLD
Solar/Wind Harmer
1.012
316294AC1-161 GEN
Solar/Wind Harmer
4.367
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3.063
316072AD1-144
Solar/Wind Harmer
0.089
944591AF1-124 GEN
Solar/Wind Harmer
55.179
316388AE2-253 GEN
Solar/Wind Harmer
0.757
3146456SLIGO L269
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
11.595
316246AF1-032 C
Solar/Wind Harmer
0.108
316381AD1-082 GEN
Solar/Wind Harmer
0.25
970661AG2-428 GEN
Solar/Wind Harmer
23.793
316093AE2-104_GEN
Solar/Wind Harmer
3.989
3146516WINFALL
Solar/Wind Harmer
0.754
3146516WINFALL
Solar/Wind Harmer
0.232
962861AG1-135 GEN
Solar/Wind Harmer
7.409
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3141726DUNNSVL
Solar/Wind Harmer
0.895
3130156CHOWAN
Solar/Wind Harmer
0.224
3145663CRESWEL
Solar/Wind Harmer
0.606
971163AH1-040 GEN
Solar/Wind Harmer
17.339
3143526WINTERP
Solar/Wind Harmer
1.125
3150351NORNECKC2
Adder
2.147
3146206CASHIE
Solar/Wind Harmer
0.207
971547AH1-271 GEN
Solar/Wind Harmer
4.412
939411AE1-173 GEN
Solar/Wind Harmer
87.698
3145893MURPHYS
Solar/Wind Harmer
0.811
3145893MURPHYS
Solar/Wind Harmer
0.902
3146173TUNIS
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.198
3145963POPLR C
Solar/Wind Harmer
0.197
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3146263WOODLND
Solar/Wind Harmer
0.195
3145823KELFORD
Solar/Wind Harmer
0.193
940641AE2-051 GEN
Solar/Wind Harmer
15.435
316023GEN1_S
Solar/Wind Harmer
0.432
316337AD2-073 GEN
Solar/Wind Harmer
0.166
316190AA2-174 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
3.411
962571AG1-106 GEN
Solar/Wind Harmer
2.669
960081AF2-299 GEN
Solar/Wind Harmer
1.79
3146293MARTNCO
Solar/Wind Harmer
0.173
3145783HORNRTN
Solar/Wind Harmer
0.185
3145796HORNRTN
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.185
316212AC1-099_GEN
Solar/Wind Harmer
0.945
3143226MDLTHAN
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
971795AH1-408 GEN
Solar/Wind Harmer
12.042
3147043LAWRENC
Adder
1.61
316494AC1-189 GEN
Solar/Wind Harmer
0.596
315722AD1-056 GEN
Solar/Wind Harmer
1.11
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.172
3145493TOT1
Solar/Wind Harmer
0.767
3146233WITAKRS
Solar/Wind Harmer
0.681
316129AC1-054 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
7.177
3145543BTLEBRO
Solar/Wind Harmer
0.167
3145543BTLEBRO
Solar/Wind Harmer
0.134
316359AB2-059 GEN
Solar/Wind Harmer
0.602
316049AB1-081 GEN
Solar/Wind Harmer
0.959
3142053HEARTS
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
5.955
970087AG2-069 GEN
Solar/Wind Harmer
13.364
3143336POWHATN
Solar/Wind Harmer
2.903
957481AF2-042 GEN
Solar/Wind Harmer
43.505
315693AD1-088 GEN
Solar/Wind Harmer
7.732
962491AG1-098 GEN
Solar/Wind Harmer
9.171
316336AC2-165 C
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
11.542
315687AD1-152 GEN
Solar/Wind Harmer
0.005
963171AG1-166 GEN
Solar/Wind Harmer
0.819
971563AH1-280 GEN
Solar/Wind Harmer
1.637
3144293JTRSVLE
Adder
0.489
970401AG2-262 GEN
Solar/Wind Harmer
0.887
3146926FARMVIL
Solar/Wind Harmer
0.089
970937AG2-583 GEN
Solar/Wind Harmer
8.957
316003AC1-222 GEN
Solar/Wind Harmer
0.004
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.057
972003AH1-546 GEN
Solar/Wind Harmer
5.812
971377AH1-170 GEN
Solar/Wind Harmer
1.422
3147623JAMES R
Solar/Wind Harmer
0.309
315705AF1-075 GEN
Solar/Wind Harmer
4.935
972135AH1-637 GEN
Solar/Wind Harmer
1.026
970223AG2-152 GEN
Solar/Wind Harmer
7.945
3147123OTTER R
Solar/Wind Harmer
0.068
316045AC1-158 PL2
Solar/Wind Helper
5.251
316006AB2-029 C
Solar/Wind Helper
0.117
316254AC1-120 GEN1
Solar/Wind Helper
1.08
CPLELTFEXP_CPLE->PJM
CLTF
10.807
CBM West 2LTFEXP_CBM-W2->PJM
CBM
55.119
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.714
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.519
MECLTFEXP_MEC->PJM
CLTF
5.527
SIGELTFEXP_SIGE->PJM
CLTF
0.173
NYPJM->LTFIMP_NY
CLTF
3.366
LGEELTFEXP_LGEE->PJM
CLTF
2.175
WECLTFEXP_WEC->PJM
CLTF
1.097
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
LAGNLTFEXP_LAGN->PJM
CLTF
9.82
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.055
TVALTFEXP_TVA->PJM
CLTF
4.995

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.22 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5137.22
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
14.825
970497AG2-320 GEN
50/50
26.932
3150401LDYSMT4
50/50
38.285
3150371LDYSMT1
50/50
36.994
315051AA1-145 CT1
50/50
2.076
3150411LDYSMT5
50/50
38.405
3150381LDYSMT2
50/50
36.755
972213AH1-691 GEN
50/50
6.217
972215AH1-692 GEN
50/50
6.217
963051AG1-154 GEN
50/50
4.783
972189AH1-679 GEN
50/50
4.654
316312AB1-027
Solar/Wind Harmer
0.455
316233AE1-074 FULL
Solar/Wind Harmer
0.199
971281AH1-106 GEN
Solar/Wind Harmer
3.456
971283AH1-107 GEN
Solar/Wind Harmer
3.456
971285AH1-108 GEN
Adder
1.878
315976AC1-164 GENA
Solar/Wind Harmer
25.718
316169AC1-164_GENC
Solar/Wind Harmer
22.218
315975AC1-164 GENB
Solar/Wind Harmer
0.761
316132AB2-190 GEN1
Solar/Wind Harmer
1.305
316369SG1_INVT
Solar/Wind Harmer
0.009
971167AH1-042 GEN
Solar/Wind Harmer
21.453
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
972265AH1-717 GEN
Adder
18.63
3151201GRAVEL4
Adder
17.465
3151191GRAVEL3
Adder
17.243
3151211GRAVEL5
Adder
17.243
971445AH1-216 GEN
Solar/Wind Harmer
16.824
3143873LANEXA
Solar/Wind Harmer
0.143
3143316POE
Solar/Wind Harmer
0.945
3138283WHITEMARSH
Solar/Wind Harmer
0.055
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
21.73
3151091ELIZAR2
Adder
21.353
3152611GOSPORTB
Adder
3.018
3152621GOSPORTC
Adder
2.561
3152601GOSPORTA
Adder
2.363
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
7.011
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.047
957871AF2-081 GEN
Solar/Wind Harmer
11.676
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.161
316311AC2-079 GEN
Solar/Wind Harmer
6.724
319010AE1-072 C
Solar/Wind Harmer
1.178
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.595
3141913WHIT STONE
Solar/Wind Harmer
0.232
313526AB2-022
Solar/Wind Harmer
0.125
3138133OCRAN
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.231
3146486SUNBURY
Solar/Wind Harmer
0.231
316321Z2-027
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
3141783LANCAST
Solar/Wind Harmer
0.138
3141783LANCAST
Solar/Wind Harmer
0.092
962981AG1-147 GEN
Solar/Wind Harmer
8.47
316315AB2-025 C
Solar/Wind Harmer
0.183
941031AE2-094 GEN
Solar/Wind Harmer
41.622
944011AF1-069 GEN
Solar/Wind Harmer
13.599
315814AE2-033 C
Solar/Wind Harmer
17.851
970327AG2-215 GEN
Solar/Wind Harmer
7.386
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
47.408
970673AG2-436 GEN
Solar/Wind Harmer
31.605
3130156CHOWAN
Solar/Wind Harmer
0.222
3130156CHOWAN
Solar/Wind Harmer
0.222
971967AH1-528 GEN
Solar/Wind Harmer
35.12
315816AE2-034 GEN
Solar/Wind Harmer
0.932
3141813NORNECK
Solar/Wind Harmer
0.217
3130546PLYMOUTH
Solar/Wind Harmer
0.213
315732AD1-074 GEN1
Solar/Wind Harmer
1.221
315733AD1-074 GEN2
Solar/Wind Harmer
1.221
315735AD1-075 GEN1
Solar/Wind Harmer
0.611
965291AG1-394 GEN
Solar/Wind Harmer
0.939
3146206CASHIE
Solar/Wind Harmer
0.21
970601AG2-382 GEN
Solar/Wind Harmer
7.851
970085AG2-068 GEN
Solar/Wind Harmer
11.171
970581AG2-369 GEN
Solar/Wind Harmer
9.607
3145893MURPHYS
Solar/Wind Harmer
0.565
3145893MURPHYS
Solar/Wind Harmer
0.209
3145513AHOSKIE
Solar/Wind Harmer
0.431
3145513AHOSKIE
Solar/Wind Harmer
0.206
3145683EARLEYS
Solar/Wind Harmer
0.411
3145683EARLEYS
Solar/Wind Harmer
0.205
3145683EARLEYS
Solar/Wind Harmer
0.205
3146043SEABORD
Solar/Wind Harmer
0.205
315607AA1-063A GEN
Solar/Wind Harmer
0.417
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.128
3137643SOCKMAN
Solar/Wind Harmer
0.801
3145796HORNRTN
Solar/Wind Harmer
0.634
3145796HORNRTN
Solar/Wind Harmer
0.079
316223AC1-118
Solar/Wind Harmer
0.142
3146033SCOT NK
Solar/Wind Harmer
0.787
970831AG2-522 GEN
Solar/Wind Harmer
8.114
316005AA1-067
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
0.753
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
970181AG2-120 GEN
Solar/Wind Harmer
2.355
957861AF2-080 GEN
Solar/Wind Harmer
8.016
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.183
3145573BETHELC
Solar/Wind Harmer
0.183
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
3.031
3144303KENBRDG
Solar/Wind Harmer
0.144
970683AG2-441 GEN
Solar/Wind Harmer
11.977
970681AG2-440 GEN
Solar/Wind Harmer
9.582
946301AF1-294 GEN
Solar/Wind Harmer
3.532
961791AG1-021 GEN
Solar/Wind Harmer
1.718
315657AE1-056 GEN
Solar/Wind Harmer
6.158
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
13.414
316118AC1-105 GEN
Solar/Wind Harmer
0.437
971845AH1-439 GEN
Solar/Wind Harmer
7.626
972193AH1-681 GEN
Adder
3.818
3147173SINAI
Solar/Wind Harmer
0.166
3147243WELCO
Solar/Wind Harmer
0.104
972205AH1-687 GEN
Adder
6.726
3150391LDYSMT3
50/50
38.213
972195AH1-682 GEN
50/50
5.022
315673AE1-157 GEN
Solar/Wind Harmer
18.457
957411AF2-035 GEN
Solar/Wind Harmer
11.334
970317AG2-208 GEN
Solar/Wind Harmer
10.501
3142296MT RD221
Adder
0.82
3142366NRTHEST
Adder
0.825
3150691DARBY 3
Adder
18.133
3150701DARBY 4
Adder
18.091
3150681DARBY 2
Adder
18.07
3150671DARBY 1
Adder
18.049
316075AC2-137 C
Solar/Wind Harmer
0.069
3143526WINTERP
Solar/Wind Harmer
1.295
966871AG1-558 GEN
Solar/Wind Harmer
0.287
971223AH1-071 GEN
Solar/Wind Harmer
2.646
3142946ENON
Solar/Wind Harmer
0.025
944641AF1-129 GEN
Adder
116.855
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.272
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.044
3150991CHESPKB
Adder
2.482
3150991CHESPKB
Adder
2.423
970657AG2-426 GEN
Solar/Wind Harmer
8.291
970657AG2-426 GEN
Solar/Wind Harmer
1.738
316316AC1-027 C
Solar/Wind Harmer
0.227
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.942
3145506HICKORY
Solar/Wind Harmer
0.565
3145506HICKORY
Solar/Wind Harmer
0.141
316339AD2-160 GEN
Solar/Wind Harmer
0.381
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.131
3137176SLIGO L2192
Solar/Wind Harmer
0.931
3146456SLIGO L269
Solar/Wind Harmer
4.141
3130086AYDLETT
Solar/Wind Harmer
0.934
3146386ELIZ CT
Solar/Wind Harmer
0.231
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
3144356SAPONY
Solar/Wind Harmer
1.894
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.987
3146376EDENTON
Solar/Wind Harmer
0.987
958261AF2-120 GEN
Solar/Wind Harmer
7.345
972185AH1-677 GEN
Adder
12.364
972187AH1-678 GEN
Adder
6.203
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.271
3150341NORNECKC1
Adder
2.253
316468AD1-105 GEN
Solar/Wind Harmer
-0.071
970933AG2-581 GEN
Solar/Wind Harmer
17.147
316065AD1-022 GEN
Solar/Wind Harmer
9.721
3145893MURPHYS
Solar/Wind Harmer
1.401
3145893MURPHYS
Solar/Wind Harmer
0.376
3146173TUNIS
Solar/Wind Harmer
0.207
3146173TUNIS
Solar/Wind Harmer
0.207
316181AB2-040 GEN
Solar/Wind Harmer
0.293
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
3142666NORTHAMPTON
Solar/Wind Harmer
0.121
970099AG2-077 GEN
Solar/Wind Harmer
21.434
316426AA2-053 GEN
Solar/Wind Harmer
0.677
3145593CAROLNA
Solar/Wind Harmer
0.199
3145593CAROLNA
Solar/Wind Harmer
0.199
966811AG1-552 GEN
Solar/Wind Harmer
2.162
3145593CAROLNA
Solar/Wind Harmer
0.248
3145783HORNRTN
Solar/Wind Harmer
3.524
3145783HORNRTN
Solar/Wind Harmer
2.819
3145783HORNRTN
Solar/Wind Harmer
0.881
3145783HORNRTN
Solar/Wind Harmer
0.352
3145796HORNRTN
Solar/Wind Harmer
0.594
3145933PARMELE
Solar/Wind Harmer
0.387
3145933PARMELE
Solar/Wind Harmer
0.193
316274AC1-208 GEN
Solar/Wind Harmer
0.996
971741AH1-377 GEN
Solar/Wind Harmer
18.605
970301AG2-198 GEN
Solar/Wind Harmer
7.883
939181AE1-148 GEN
Solar/Wind Harmer
8.803
3145493TOT1
Solar/Wind Harmer
0.424
3145453TOT5
Solar/Wind Harmer
0.255
3145603CNETO
Solar/Wind Harmer
0.17
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.695
971775AH1-396 GEN
Solar/Wind Harmer
0.289
961601AG1-000A GEN
Solar/Wind Harmer
3.194
316263AC1-034 GEN
Solar/Wind Harmer
6.824
958211AF2-115 GEN
Solar/Wind Harmer
2.148
3152251N ANNA1
50/50
14.826
972197AH1-683 GEN
50/50
5.978
972219AH1-694 GEN
50/50
4.304
315052AA1-145 CT2
50/50
2.085
966881AG1-559 GEN
Solar/Wind Harmer
0.307
3142416OLDCHRC
Solar/Wind Harmer
0.661
3142416OLDCHRC
Solar/Wind Harmer
0.253
3143096IRON208
Adder
1.045
3143526WINTERP
Solar/Wind Harmer
1.295
3150851SPRUNCC
Adder
1.148
3142543TWELFTH
Solar/Wind Harmer
0.024
3143226MDLTHAN
Solar/Wind Harmer
0.248
944631AF1-128 GEN
Adder
117.965
316159AE1-175 C
Solar/Wind Harmer
0.21
970129AG2-093 GEN
Solar/Wind Harmer
6.924
316458AB2-190 GEN2
Solar/Wind Harmer
1.305
315671AE2-027_GEN
Solar/Wind Harmer
15.554
971069AG2-661 GEN
Solar/Wind Harmer
4.312
971647AH1-324 GEN
Solar/Wind Harmer
10.299
971317AH1-138 GEN
Solar/Wind Harmer
1.8
3142433PROV 92
Solar/Wind Harmer
0.964
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
3138126ROCKLANDING
Solar/Wind Harmer
0.111
961611AG1-000B GEN
Solar/Wind Harmer
12.625
3151171GRAVELC
Adder
2.552
316294AC1-161 GEN
Solar/Wind Harmer
4.156
3145336SMITFLD
Solar/Wind Harmer
0.955
970659AG2-427 GEN
Solar/Wind Harmer
11.475
944591AF1-124 GEN
Solar/Wind Harmer
53.557
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.959
316381AD1-082 GEN
Solar/Wind Harmer
0.247
3141766HARMONY
Solar/Wind Harmer
0.047
971777AH1-397 GEN
Solar/Wind Harmer
0.625
3141843SHACKLE
Adder
1.209
970661AG2-428 GEN
Solar/Wind Harmer
23.497
316072AD1-144
Solar/Wind Harmer
0.085
939411AE1-173 GEN
Solar/Wind Harmer
100.291
316388AE2-253 GEN
Solar/Wind Harmer
0.736
940641AE2-051 GEN
Solar/Wind Harmer
18.777
3146456SLIGO L269
Solar/Wind Harmer
0.234
316246AF1-032 C
Solar/Wind Harmer
0.105
316093AE2-104_GEN
Solar/Wind Harmer
3.91
3138133OCRAN
Solar/Wind Harmer
0.139
3146516WINFALL
Solar/Wind Harmer
0.74
3146516WINFALL
Solar/Wind Harmer
0.228
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
962861AG1-135 GEN
Solar/Wind Harmer
7.133
3130156CHOWAN
Solar/Wind Harmer
0.222
3141726DUNNSVL
Solar/Wind Harmer
0.878
3145663CRESWEL
Solar/Wind Harmer
0.608
971163AH1-040 GEN
Solar/Wind Harmer
17.369
3150351NORNECKC2
Adder
2.162
3143336POWHATN
Solar/Wind Harmer
3.766
970919AG2-571 GEN
Solar/Wind Harmer
7.477
3146206CASHIE
Solar/Wind Harmer
0.21
971547AH1-271 GEN
Solar/Wind Harmer
4.486
316023GEN1_S
Solar/Wind Harmer
0.471
970087AG2-069 GEN
Solar/Wind Harmer
16.757
3145893MURPHYS
Solar/Wind Harmer
0.837
3145893MURPHYS
Solar/Wind Harmer
0.931
316337AD2-073 GEN
Solar/Wind Harmer
0.181
3146173TUNIS
Solar/Wind Harmer
0.207
3145683EARLEYS
Solar/Wind Harmer
0.205
960081AF2-299 GEN
Solar/Wind Harmer
1.959
3146263WOODLND
Solar/Wind Harmer
0.204
316336AC2-165 C
Solar/Wind Harmer
0.008
3145963POPLR C
Solar/Wind Harmer
0.202
316011AB1-132 GEN
Solar/Wind Harmer
3.658
962571AG1-106 GEN
Solar/Wind Harmer
2.862
3145823KELFORD
Solar/Wind Harmer
0.201
957481AF2-042 GEN
Solar/Wind Harmer
53.584
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
13.299
3145783HORNRTN
Solar/Wind Harmer
0.198
3145796HORNRTN
Solar/Wind Harmer
0.653
3145796HORNRTN
Solar/Wind Harmer
0.198
3147043LAWRENC
Adder
1.785
315693AD1-088 GEN
Solar/Wind Harmer
9.451
962491AG1-098 GEN
Solar/Wind Harmer
11.2
316212AC1-099_GEN
Solar/Wind Harmer
1.001
3146293MARTNCO
Solar/Wind Harmer
0.179
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
316129AC1-054 GEN
Solar/Wind Harmer
0.711
971065AG2-659 GEN
Solar/Wind Harmer
8.033
315722AD1-056 GEN
Solar/Wind Harmer
1.189
316494AC1-189 GEN
Solar/Wind Harmer
0.628
972135AH1-637 GEN
Solar/Wind Harmer
1.564
961671AG1-007 GEN
Solar/Wind Harmer
0.028
3146083TARBORO
Solar/Wind Harmer
0.183
3145493TOT1
Solar/Wind Harmer
0.814
3146233WITAKRS
Solar/Wind Harmer
0.728
315687AD1-152 GEN
Solar/Wind Harmer
0.006
3147666LOUISA
Solar/Wind Harmer
0.73
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
13.415
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.144
316359AB2-059 GEN
Solar/Wind Harmer
0.645
316049AB1-081 GEN
Solar/Wind Harmer
1.028
3142053HEARTS
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
0.955
971563AH1-280 GEN
Solar/Wind Harmer
1.909
3144293JTRSVLE
Adder
0.57
970937AG2-583 GEN
Solar/Wind Harmer
10.92
316192AB2-158 GEN
Solar/Wind Harmer
1.002
3146926FARMVIL
Solar/Wind Harmer
0.105
970401AG2-262 GEN
Solar/Wind Harmer
1.013
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.067
972277AH1-723 GEN
Adder
99.579
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972003AH1-546 GEN
Solar/Wind Harmer
6.768
963191AG1-168 GEN
Solar/Wind Harmer
0.716
3144293JTRSVLE
Adder
0.57
3144293JTRSVLE
Adder
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.178
3147133PAMPLIN
Solar/Wind Harmer
0.143
962561AG1-105 GEN
Solar/Wind Harmer
8.357
964791AG1-342 GEN
Solar/Wind Harmer
3.316
3146843MT LREL
Solar/Wind Harmer
0.172
3146843MT LREL
Solar/Wind Harmer
0.172
3146776BUCKING
Solar/Wind Harmer
0.67
3146776BUCKING
Solar/Wind Harmer
0.054
316222AC1-221 GEN
Solar/Wind Harmer
0.627
971489AH1-241 GEN
Solar/Wind Harmer
7.9
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.989
316447AC1-158 HLD
Solar/Wind Helper
4.858
315651AD1-115 GEN
Solar/Wind Helper
0.961
3142416OLDCHRC
Solar/Wind Harmer
2.465
970293AG2-193 GEN
Solar/Wind Harmer
2.678
3143096IRON208
Adder
1.045
3143096IRON208
Adder
1.024
3150861SPRUNCD
Adder
1.148
316473AC1-191 GEN
Solar/Wind Harmer
0.839
3142946ENON
Solar/Wind Harmer
0.083
970133AG2-095 GEN
Solar/Wind Harmer
2.349
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.714
315778AD1-151 GEN
Solar/Wind Harmer
19.405
965281AG1-393 GEN
Solar/Wind Harmer
2.587
315839AE2-212 C
Solar/Wind Harmer
0.002
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
3150921YORKTN3
Adder
6.055
3144216WINCHST
Adder
0.908
961611AG1-000B GEN
Solar/Wind Harmer
6.42
3151221GRAVEL6
Adder
17.444
3151171GRAVELC
Adder
3.356
315773AC2-141 GEN
Solar/Wind Harmer
8.761
3145336SMITFLD
Solar/Wind Harmer
0.096
315813AE1-149 C
Solar/Wind Harmer
12.736
3144536CHRHLND
Solar/Wind Harmer
0.035
970659AG2-427 GEN
Solar/Wind Harmer
2.51
944581AF1-123 GEN
Solar/Wind Harmer
53.367
944601AF1-125 GEN
Solar/Wind Harmer
52.545
3151101ELIZAR3
Adder
22.008
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.157
3141843SHACKLE
Adder
1.209
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
970661AG2-428 GEN
Solar/Wind Harmer
4.998
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.174
3141873WAN 176
Solar/Wind Harmer
4.175
3146456SLIGO L269
Solar/Wind Harmer
0.234
971153AH1-033 GEN
Solar/Wind Harmer
2.705
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.227
962971AG1-146 GEN
Solar/Wind Harmer
3.63
3145273HOLLAND
Solar/Wind Harmer
0.17
970009AG2-005 GEN
Solar/Wind Harmer
1.68
3146376EDENTON
Solar/Wind Harmer
0.222
316404AE1-155 C
Solar/Wind Harmer
0.05
315614AA2-178 GEN
Solar/Wind Harmer
1.242
3150351NORNECKC2
Adder
2.198
971781AH1-399 GEN
Solar/Wind Harmer
0.285
971157AH1-035 GEN
Solar/Wind Harmer
2.559
315737AD1-076 GEN
Solar/Wind Harmer
2.735
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316313AB2-026
Solar/Wind Harmer
0.134
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.201
970917AG2-570 GEN
Solar/Wind Harmer
18.693
3146206CASHIE
Solar/Wind Harmer
0.21
316365GEN2_N
Solar/Wind Harmer
0.471
3145893MURPHYS
Solar/Wind Harmer
0.35
3145893MURPHYS
Solar/Wind Harmer
0.209
957521AF2-046 GEN
Solar/Wind Harmer
15.533
961681AG1-008 GEN
Solar/Wind Harmer
15.533
3146173TUNIS
Solar/Wind Harmer
0.207
3156021HOLLOMANSOL
Solar/Wind Harmer
0.94
316463AE2-346 GEN
Solar/Wind Harmer
0.177
316140AB2-099
Solar/Wind Harmer
0.074
962331AG1-082 GEN
Solar/Wind Harmer
2.201
3146263WOODLND
Solar/Wind Harmer
0.204
3145963POPLR C
Solar/Wind Harmer
0.202
313506AB2-031 GEN
Solar/Wind Harmer
0.624
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.792
3145796HORNRTN
Solar/Wind Harmer
0.198
3141906WESTMOR
Solar/Wind Harmer
0.079
3147043LAWRENC
Solar/Wind Harmer
0.118
316478AD1-087 GEN
Solar/Wind Harmer
0.676
316486AD2-202 GEN
Solar/Wind Harmer
0.198
316210AC1-098 GEN
Solar/Wind Harmer
1.795
3145933PARMELE
Solar/Wind Harmer
0.193
966801AG1-551 GEN
Solar/Wind Harmer
2.252
970737AG2-469 GEN
Solar/Wind Harmer
8.074
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
315724AD1-057 GEN
Solar/Wind Harmer
0.705
316327AA2-057 GEN
Solar/Wind Harmer
0.281
970909AG2-566 GEN
Solar/Wind Harmer
1.971
3146073TAR RVR
Solar/Wind Harmer
0.183
3146083TARBORO
Solar/Wind Harmer
0.183
3146233WITAKRS
Solar/Wind Harmer
0.919
3146233WITAKRS
Solar/Wind Harmer
0.124
3138543CONSLDL
Solar/Wind Harmer
0.12
3147666LOUISA
Solar/Wind Harmer
0.42
316131AB2-060 GEN
Solar/Wind Harmer
0.572
964241AG1-285 GEN
Solar/Wind Harmer
12.091
315785AD2-033 C
Solar/Wind Harmer
1.468
970257AG2-171 GEN
Solar/Wind Harmer
5.771
959311AF2-222 GEN
Solar/Wind Harmer
16.014
961601AG1-000A GEN
Solar/Wind Harmer
12.778
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
971623AH1-311 GEN
Solar/Wind Harmer
0.359
963181AG1-167 GEN
Solar/Wind Harmer
0.716
3144293JTRSVLE
Adder
0.57
3147133PAMPLIN
Solar/Wind Harmer
0.56
971193AH1-056 GEN
Solar/Wind Harmer
10.872
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.105
3146776BUCKING
Solar/Wind Harmer
0.06
972255AH1-712 GEN
Adder
85.454
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.086
971683AH1-343 GEN
Solar/Wind Harmer
5.663
316283AC2-100 C
Solar/Wind Harmer
0.294
970865AG2-541 GEN
Solar/Wind Harmer
5.131
971447AH1-217 GEN
Solar/Wind Harmer
4.386
316123AC1-075 GEN
Solar/Wind Harmer
0.186
970165AG2-112 GEN
Solar/Wind Harmer
1.103
970163AG2-111 GEN
Solar/Wind Harmer
1.052
270494AE1-108_GEN
Solar/Wind Harmer
1.582
316164AC1-076 GEN
Solar/Wind Helper
1.947
316411AF1-147_GEN1
Solar/Wind Helper
0.8
971377AH1-170 GEN
Solar/Wind Harmer
1.58
3147623JAMES R
Solar/Wind Harmer
0.343
316045AC1-158 PL2
Solar/Wind Helper
7.066
316006AB2-029 C
Solar/Wind Helper
0.145
316254AC1-120 GEN1
Solar/Wind Helper
1.294
970221AG2-151 GEN
Solar/Wind Harmer
7.9
3141316ARNOLDS
Adder
0.336
3150331BIRCHWDA
Adder
22.127
316044AC1-158 PL1
Solar/Wind Helper
2.207
316450AC1-158 RIC
Solar/Wind Helper
0.589
3141196NOKESVL
Solar/Wind Helper
1.25
316170AC1-121 GEN2
Solar/Wind Helper
0.431
316415AF1-147_GEN2
Solar/Wind Helper
0.8
3138216PACIFIC
Solar/Wind Helper
0.039
CPLELTFEXP_CPLE->PJM
CLTF
11.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.47
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.182
MECLTFEXP_MEC->PJM
CLTF
3.753
SIGELTFEXP_SIGE->PJM
CLTF
0.114
NYPJM->LTFIMP_NY
CLTF
3.205
LGEELTFEXP_LGEE->PJM
CLTF
1.386
WECLTFEXP_WEC->PJM
CLTF
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
8.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.425
TVALTFEXP_TVA->PJM
CLTF
4.163

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.64 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5073.15
MW Contribution:1.06
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
13.89
970497AG2-320 GEN
50/50
26.316
3150401LDYSMT4
50/50
37.387
3150371LDYSMT1
50/50
36.126
315051AA1-145 CT1
50/50
2.017
316044AC1-158 PL1
Solar/Wind Harmer
1.37
316450AC1-158 RIC
Solar/Wind Harmer
0.365
3142416OLDCHRC
Solar/Wind Harmer
2.389
970293AG2-193 GEN
Solar/Wind Harmer
2.592
3143096IRON208
Adder
1.01
3143096IRON208
Adder
0.989
316473AC1-191 GEN
Solar/Wind Harmer
0.814
3150861SPRUNCD
Adder
1.107
3142946ENON
Solar/Wind Harmer
0.08
970133AG2-095 GEN
Solar/Wind Harmer
2.267
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.202
315778AD1-151 GEN
Solar/Wind Harmer
18.726
965281AG1-393 GEN
Solar/Wind Harmer
2.495
315839AE2-212 C
Solar/Wind Harmer
0.002
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
3150921YORKTN3
Adder
5.845
3144216WINCHST
Adder
0.877
961611AG1-000B GEN
Solar/Wind Harmer
6.193
3151221GRAVEL6
Adder
16.824
3151171GRAVELC
Adder
3.237
315773AC2-141 GEN
Solar/Wind Harmer
8.441
3145336SMITFLD
Solar/Wind Harmer
0.092
315813AE1-149 C
Solar/Wind Harmer
12.273
3144536CHRHLND
Solar/Wind Harmer
0.034
3141766HARMONY
Solar/Wind Harmer
3.053
3141843SHACKLE
Adder
1.169
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.419
3151101ELIZAR3
Adder
21.202
944581AF1-123 GEN
Solar/Wind Harmer
51.405
944601AF1-125 GEN
Solar/Wind Harmer
50.613
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
316280AD1-041 GEN
Solar/Wind Harmer
0.005
970661AG2-428 GEN
Solar/Wind Harmer
4.815
316156AD2-030 GEN
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
4.037
3146456SLIGO L269
Solar/Wind Harmer
0.225
971153AH1-033 GEN
Solar/Wind Harmer
2.606
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.22
3150411LDYSMT5
50/50
37.503
3150381LDYSMT2
50/50
35.892
972213AH1-691 GEN
50/50
6.072
972215AH1-692 GEN
50/50
6.072
963051AG1-154 GEN
50/50
4.67
972189AH1-679 GEN
50/50
4.522
316312AB1-027
Solar/Wind Harmer
0.441
971285AH1-108 GEN
Adder
1.812
315976AC1-164 GENA
Solar/Wind Harmer
24.889
316169AC1-164_GENC
Solar/Wind Harmer
21.501
315975AC1-164 GENB
Solar/Wind Harmer
0.736
316233AE1-074 FULL
Solar/Wind Harmer
0.192
971281AH1-106 GEN
Solar/Wind Harmer
3.326
971283AH1-107 GEN
Solar/Wind Harmer
3.326
316132AB2-190 GEN1
Solar/Wind Harmer
1.26
971167AH1-042 GEN
Solar/Wind Harmer
20.74
316369SG1_INVT
Solar/Wind Harmer
0.009
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
972265AH1-717 GEN
Adder
17.968
3151201GRAVEL4
Adder
16.844
3151191GRAVEL3
Adder
16.63
3151211GRAVEL5
Adder
16.63
3143873LANEXA
Solar/Wind Harmer
0.139
971445AH1-216 GEN
Solar/Wind Harmer
16.22
316314AB2-024 C
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143316POE
Solar/Wind Harmer
0.91
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.779
3151081ELIZAR1
Adder
20.934
3151091ELIZAR2
Adder
20.57
3152611GOSPORTB
Adder
2.907
3152621GOSPORTC
Adder
2.467
3152601GOSPORTA
Adder
2.276
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
957871AF2-081 GEN
Solar/Wind Harmer
11.247
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.155
316311AC2-079 GEN
Solar/Wind Harmer
6.478
319010AE1-072 C
Solar/Wind Harmer
1.135
3146406KITTY HAWK
Solar/Wind Harmer
0.028
316305AF2-043 C
Solar/Wind Harmer
0.002
3141913WHIT STONE
Solar/Wind Harmer
0.224
315835AF2-110_GEN
Solar/Wind Harmer
1.537
3138133OCRAN
Solar/Wind Harmer
0.067
313526AB2-022
Solar/Wind Harmer
0.121
3146486SUNBURY
Solar/Wind Harmer
0.222
3146486SUNBURY
Solar/Wind Harmer
0.222
3141783LANCAST
Solar/Wind Harmer
0.133
3141783LANCAST
Solar/Wind Harmer
0.089
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.612
3145176PASQUOTANK
Solar/Wind Harmer
0.138
962981AG1-147 GEN
Solar/Wind Harmer
8.191
316315AB2-025 C
Solar/Wind Harmer
0.176
970327AG2-215 GEN
Solar/Wind Harmer
7.143
315814AE2-033 C
Solar/Wind Harmer
17.164
941031AE2-094 GEN
Solar/Wind Harmer
39.927
944011AF1-069 GEN
Solar/Wind Harmer
13.046
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.214
3130156CHOWAN
Solar/Wind Harmer
0.214
970673AG2-436 GEN
Solar/Wind Harmer
45.48
970673AG2-436 GEN
Solar/Wind Harmer
30.32
971967AH1-528 GEN
Solar/Wind Harmer
33.699
3141813NORNECK
Solar/Wind Harmer
0.21
315816AE2-034 GEN
Solar/Wind Harmer
0.897
3130546PLYMOUTH
Solar/Wind Harmer
0.205
315732AD1-074 GEN1
Solar/Wind Harmer
1.176
315733AD1-074 GEN2
Solar/Wind Harmer
1.176
315735AD1-075 GEN1
Solar/Wind Harmer
0.588
965291AG1-394 GEN
Solar/Wind Harmer
0.904
3146206CASHIE
Solar/Wind Harmer
0.202
970601AG2-382 GEN
Solar/Wind Harmer
7.556
3145893MURPHYS
Solar/Wind Harmer
0.544
3145893MURPHYS
Solar/Wind Harmer
0.201
970085AG2-068 GEN
Solar/Wind Harmer
10.719
970581AG2-369 GEN
Solar/Wind Harmer
9.218
3145513AHOSKIE
Solar/Wind Harmer
0.415
3145513AHOSKIE
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.395
3145683EARLEYS
Solar/Wind Harmer
0.197
3145683EARLEYS
Solar/Wind Harmer
0.197
3146043SEABORD
Solar/Wind Harmer
0.197
315607AA1-063A GEN
Solar/Wind Harmer
0.401
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
21.282
3137643SOCKMAN
Solar/Wind Harmer
0.77
316223AC1-118
Solar/Wind Harmer
0.138
3145796HORNRTN
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.076
3146033SCOT NK
Solar/Wind Harmer
0.757
970831AG2-522 GEN
Solar/Wind Harmer
7.803
316005AA1-067
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.724
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
3150391LDYSMT3
50/50
37.317
972195AH1-682 GEN
50/50
4.904
316447AC1-158 HLD
Solar/Wind Harmer
3.012
315673AE1-157 GEN
Solar/Wind Harmer
17.997
957411AF2-035 GEN
Solar/Wind Harmer
11.043
970317AG2-208 GEN
Solar/Wind Harmer
10.231
3142296MT RD221
Adder
0.795
3142366NRTHEST
Adder
0.798
3150691DARBY 3
Adder
17.546
3150701DARBY 4
Adder
17.506
3150681DARBY 2
Adder
17.485
3150671DARBY 1
Adder
17.465
316075AC2-137 C
Solar/Wind Harmer
0.066
966871AG1-558 GEN
Solar/Wind Harmer
0.278
3143526WINTERP
Solar/Wind Harmer
1.246
3142946ENON
Solar/Wind Harmer
0.024
971223AH1-071 GEN
Solar/Wind Harmer
2.54
944641AF1-129 GEN
Adder
112.782
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.263
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.042
3150991CHESPKB
Adder
2.391
3150991CHESPKB
Adder
2.334
970657AG2-426 GEN
Solar/Wind Harmer
7.988
970657AG2-426 GEN
Solar/Wind Harmer
1.675
316316AC1-027 C
Solar/Wind Harmer
0.219
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.907
3145506HICKORY
Solar/Wind Harmer
0.544
3145506HICKORY
Solar/Wind Harmer
0.136
316339AD2-160 GEN
Solar/Wind Harmer
0.367
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.126
3137176SLIGO L2192
Solar/Wind Harmer
0.897
3146456SLIGO L269
Solar/Wind Harmer
3.989
3130086AYDLETT
Solar/Wind Harmer
0.9
3146386ELIZ CT
Solar/Wind Harmer
0.223
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.22
3152251N ANNA1
50/50
13.891
972197AH1-683 GEN
50/50
5.838
972219AH1-694 GEN
50/50
4.203
315052AA1-145 CT2
50/50
2.026
316045AC1-158 PL2
Solar/Wind Harmer
4.381
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
0.641
3142416OLDCHRC
Solar/Wind Harmer
0.245
3143096IRON208
Adder
1.01
3150851SPRUNCC
Adder
1.107
3142543TWELFTH
Solar/Wind Harmer
0.023
3143526WINTERP
Solar/Wind Harmer
1.246
944631AF1-128 GEN
Adder
114.018
3143226MDLTHAN
Solar/Wind Harmer
0.238
316159AE1-175 C
Solar/Wind Harmer
0.203
970129AG2-093 GEN
Solar/Wind Harmer
6.683
316458AB2-190 GEN2
Solar/Wind Harmer
1.26
315671AE2-027_GEN
Solar/Wind Harmer
15.005
971069AG2-661 GEN
Solar/Wind Harmer
4.161
3142433PROV 92
Solar/Wind Harmer
0.932
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
971647AH1-324 GEN
Solar/Wind Harmer
9.937
971317AH1-138 GEN
Solar/Wind Harmer
1.739
3138126ROCKLANDING
Solar/Wind Harmer
0.107
961611AG1-000B GEN
Solar/Wind Harmer
12.179
3151171GRAVELC
Adder
2.462
316294AC1-161 GEN
Solar/Wind Harmer
4.004
3145336SMITFLD
Solar/Wind Harmer
0.921
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.604
3141843SHACKLE
Adder
1.169
970659AG2-427 GEN
Solar/Wind Harmer
11.057
944591AF1-124 GEN
Solar/Wind Harmer
51.588
316381AD1-082 GEN
Solar/Wind Harmer
0.238
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.851
970661AG2-428 GEN
Solar/Wind Harmer
22.639
316072AD1-144
Solar/Wind Harmer
0.082
316388AE2-253 GEN
Solar/Wind Harmer
0.708
939411AE1-173 GEN
Solar/Wind Harmer
96.357
3146456SLIGO L269
Solar/Wind Harmer
0.225
940641AE2-051 GEN
Solar/Wind Harmer
18.025
316246AF1-032 C
Solar/Wind Harmer
0.101
316093AE2-104_GEN
Solar/Wind Harmer
3.766
3138133OCRAN
Solar/Wind Harmer
0.134
3146516WINFALL
Solar/Wind Harmer
0.713
3146516WINFALL
Solar/Wind Harmer
0.22
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
962861AG1-135 GEN
Solar/Wind Harmer
6.899
3130156CHOWAN
Solar/Wind Harmer
0.214
3141726DUNNSVL
Solar/Wind Harmer
0.85
3150351NORNECKC2
Adder
2.092
3145663CRESWEL
Solar/Wind Harmer
0.585
971163AH1-040 GEN
Solar/Wind Harmer
16.721
3143336POWHATN
Solar/Wind Harmer
3.631
3146206CASHIE
Solar/Wind Harmer
0.202
971547AH1-271 GEN
Solar/Wind Harmer
4.318
970919AG2-571 GEN
Solar/Wind Harmer
7.174
316023GEN1_S
Solar/Wind Harmer
0.453
3145893MURPHYS
Solar/Wind Harmer
0.805
3145893MURPHYS
Solar/Wind Harmer
0.896
316337AD2-073 GEN
Solar/Wind Harmer
0.175
970087AG2-069 GEN
Solar/Wind Harmer
16.078
3146173TUNIS
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.197
960081AF2-299 GEN
Solar/Wind Harmer
1.885
3146263WOODLND
Solar/Wind Harmer
0.196
316336AC2-165 C
Solar/Wind Harmer
0.008
3145963POPLR C
Solar/Wind Harmer
0.194
316011AB1-132 GEN
Solar/Wind Harmer
3.518
962571AG1-106 GEN
Solar/Wind Harmer
2.753
3145823KELFORD
Solar/Wind Harmer
0.193
957481AF2-042 GEN
Solar/Wind Harmer
51.474
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
12.793
3145783HORNRTN
Solar/Wind Harmer
0.19
3145796HORNRTN
Solar/Wind Harmer
0.628
3145796HORNRTN
Solar/Wind Harmer
0.19
3147043LAWRENC
Adder
1.718
315693AD1-088 GEN
Solar/Wind Harmer
9.086
962491AG1-098 GEN
Solar/Wind Harmer
10.769
316212AC1-099_GEN
Solar/Wind Harmer
0.963
3146293MARTNCO
Solar/Wind Harmer
0.172
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
316129AC1-054 GEN
Solar/Wind Harmer
0.684
971065AG2-659 GEN
Solar/Wind Harmer
7.725
315722AD1-056 GEN
Solar/Wind Harmer
1.144
3147666LOUISA
Solar/Wind Harmer
0.717
316494AC1-189 GEN
Solar/Wind Harmer
0.604
972135AH1-637 GEN
Solar/Wind Harmer
1.514
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.176
3145493TOT1
Solar/Wind Harmer
0.783
3146233WITAKRS
Solar/Wind Harmer
0.7
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316192AB2-158 GEN
Solar/Wind Harmer
0.987
970685AG2-442 GEN
Solar/Wind Harmer
12.932
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.138
963171AG1-166 GEN
Solar/Wind Harmer
0.921
971563AH1-280 GEN
Solar/Wind Harmer
1.842
3144293JTRSVLE
Adder
0.55
316359AB2-059 GEN
Solar/Wind Harmer
0.62
316049AB1-081 GEN
Solar/Wind Harmer
0.988
3142053HEARTS
Solar/Wind Harmer
0.304
970937AG2-583 GEN
Solar/Wind Harmer
10.585
3146926FARMVIL
Solar/Wind Harmer
0.102
970401AG2-262 GEN
Solar/Wind Harmer
0.974
972277AH1-723 GEN
Adder
97.135
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
972003AH1-546 GEN
Solar/Wind Harmer
6.584
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.539
3147623JAMES R
Solar/Wind Harmer
0.334
316006AB2-029 C
Solar/Wind Helper
0.12
3146516WINFALL
Solar/Wind Harmer
0.22
3146516WINFALL
Solar/Wind Harmer
0.22
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
3144356SAPONY
Solar/Wind Harmer
1.822
315742AE1-103 GEN
Solar/Wind Harmer
0.002
958261AF2-120 GEN
Solar/Wind Harmer
7.105
3146376EDENTON
Solar/Wind Harmer
0.951
3146376EDENTON
Solar/Wind Harmer
0.951
972185AH1-677 GEN
Adder
11.862
316468AD1-105 GEN
Solar/Wind Harmer
-0.068
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.197
3150341NORNECKC1
Adder
2.18
972187AH1-678 GEN
Adder
5.952
970933AG2-581 GEN
Solar/Wind Harmer
16.459
316065AD1-022 GEN
Solar/Wind Harmer
9.356
3145893MURPHYS
Solar/Wind Harmer
1.348
3145893MURPHYS
Solar/Wind Harmer
0.362
3146173TUNIS
Solar/Wind Harmer
0.199
3146173TUNIS
Solar/Wind Harmer
0.199
316181AB2-040 GEN
Solar/Wind Harmer
0.282
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.116
970099AG2-077 GEN
Solar/Wind Harmer
20.59
316426AA2-053 GEN
Solar/Wind Harmer
0.651
3145593CAROLNA
Solar/Wind Harmer
0.192
3145593CAROLNA
Solar/Wind Harmer
0.192
966811AG1-552 GEN
Solar/Wind Harmer
2.08
3145593CAROLNA
Solar/Wind Harmer
0.239
3145783HORNRTN
Solar/Wind Harmer
3.389
3145783HORNRTN
Solar/Wind Harmer
2.711
3145783HORNRTN
Solar/Wind Harmer
0.847
3145783HORNRTN
Solar/Wind Harmer
0.339
3145796HORNRTN
Solar/Wind Harmer
0.571
3145933PARMELE
Solar/Wind Harmer
0.372
3145933PARMELE
Solar/Wind Harmer
0.186
316274AC1-208 GEN
Solar/Wind Harmer
0.958
962971AG1-146 GEN
Solar/Wind Harmer
3.51
3146626S HERTFORD
Solar/Wind Harmer
0.218
3145273HOLLAND
Solar/Wind Harmer
0.163
970009AG2-005 GEN
Solar/Wind Harmer
1.625
316404AE1-155 C
Solar/Wind Harmer
0.048
3146376EDENTON
Solar/Wind Harmer
0.214
971781AH1-399 GEN
Solar/Wind Harmer
0.276
3150351NORNECKC2
Adder
2.127
315614AA2-178 GEN
Solar/Wind Harmer
1.196
971157AH1-035 GEN
Solar/Wind Harmer
2.463
315737AD1-076 GEN
Solar/Wind Harmer
2.632
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316313AB2-026
Solar/Wind Harmer
0.129
316258AE1-075 C
Solar/Wind Harmer
0.154
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.087
3146206CASHIE
Solar/Wind Harmer
0.202
970917AG2-570 GEN
Solar/Wind Harmer
17.936
316365GEN2_N
Solar/Wind Harmer
0.453
3145893MURPHYS
Solar/Wind Harmer
0.337
3145893MURPHYS
Solar/Wind Harmer
0.201
957521AF2-046 GEN
Solar/Wind Harmer
14.949
961681AG1-008 GEN
Solar/Wind Harmer
14.949
3146173TUNIS
Solar/Wind Harmer
0.199
3156021HOLLOMANSOL
Solar/Wind Harmer
0.905
316463AE2-346 GEN
Solar/Wind Harmer
0.17
316140AB2-099
Solar/Wind Harmer
0.071
962331AG1-082 GEN
Solar/Wind Harmer
2.118
3146263WOODLND
Solar/Wind Harmer
0.196
3145963POPLR C
Solar/Wind Harmer
0.194
313506AB2-031 GEN
Solar/Wind Harmer
0.6
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.193
3141906WESTMOR
Solar/Wind Harmer
0.077
3145796HORNRTN
Solar/Wind Harmer
0.762
3145796HORNRTN
Solar/Wind Harmer
0.19
3147043LAWRENC
Solar/Wind Harmer
0.114
316210AC1-098 GEN
Solar/Wind Harmer
1.726
316478AD1-087 GEN
Solar/Wind Harmer
0.649
316486AD2-202 GEN
Solar/Wind Harmer
0.191
3145933PARMELE
Solar/Wind Harmer
0.186
966801AG1-551 GEN
Solar/Wind Harmer
2.166
970737AG2-469 GEN
Solar/Wind Harmer
7.816
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
315724AD1-057 GEN
Solar/Wind Harmer
0.678
3147666LOUISA
Solar/Wind Harmer
0.412
316327AA2-057 GEN
Solar/Wind Harmer
0.27
970909AG2-566 GEN
Solar/Wind Harmer
1.901
3146073TAR RVR
Solar/Wind Harmer
0.176
3146083TARBORO
Solar/Wind Harmer
0.176
3146233WITAKRS
Solar/Wind Harmer
0.883
3146233WITAKRS
Solar/Wind Harmer
0.12
3138543CONSLDL
Solar/Wind Harmer
0.116
316131AB2-060 GEN
Solar/Wind Harmer
0.55
964241AG1-285 GEN
Solar/Wind Harmer
11.64
315785AD2-033 C
Solar/Wind Harmer
1.415
970257AG2-171 GEN
Solar/Wind Harmer
5.56
959311AF2-222 GEN
Solar/Wind Harmer
15.432
961601AG1-000A GEN
Solar/Wind Harmer
12.283
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.172
963181AG1-167 GEN
Solar/Wind Harmer
0.691
3144293JTRSVLE
Adder
0.55
971623AH1-311 GEN
Solar/Wind Harmer
0.345
3147133PAMPLIN
Solar/Wind Harmer
0.541
971193AH1-056 GEN
Solar/Wind Harmer
10.489
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.102
972255AH1-712 GEN
Adder
83.356
3146776BUCKING
Solar/Wind Harmer
0.058
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.812
971683AH1-343 GEN
Solar/Wind Harmer
5.445
316283AC2-100 C
Solar/Wind Harmer
0.283
970221AG2-151 GEN
Solar/Wind Harmer
7.696
3141316ARNOLDS
Adder
0.326
3150331BIRCHWDA
Adder
21.467
3141196NOKESVL
Solar/Wind Helper
1.224
970181AG2-120 GEN
Solar/Wind Harmer
2.265
957861AF2-080 GEN
Solar/Wind Harmer
7.708
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.176
3145573BETHELC
Solar/Wind Harmer
0.176
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.92
3144303KENBRDG
Solar/Wind Harmer
0.139
970683AG2-441 GEN
Solar/Wind Harmer
11.546
970681AG2-440 GEN
Solar/Wind Harmer
9.237
946301AF1-294 GEN
Solar/Wind Harmer
3.407
961791AG1-021 GEN
Solar/Wind Harmer
1.657
315657AE1-056 GEN
Solar/Wind Harmer
5.941
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
12.999
971845AH1-439 GEN
Solar/Wind Harmer
7.393
972193AH1-681 GEN
Adder
3.724
316118AC1-105 GEN
Solar/Wind Harmer
0.42
3147173SINAI
Solar/Wind Harmer
0.16
3147243WELCO
Solar/Wind Harmer
0.1
972205AH1-687 GEN
Adder
6.548
970865AG2-541 GEN
Solar/Wind Harmer
4.934
971447AH1-217 GEN
Solar/Wind Harmer
4.275
316123AC1-075 GEN
Solar/Wind Harmer
0.179
970165AG2-112 GEN
Solar/Wind Harmer
1.061
970163AG2-111 GEN
Solar/Wind Harmer
1.012
270494AE1-108_GEN
Solar/Wind Harmer
1.539
316411AF1-147_GEN1
Solar/Wind Helper
0.785
316415AF1-147_GEN2
Solar/Wind Helper
0.785
3138216PACIFIC
Solar/Wind Helper
0.038
971741AH1-377 GEN
Solar/Wind Harmer
17.929
970301AG2-198 GEN
Solar/Wind Harmer
7.603
939181AE1-148 GEN
Solar/Wind Harmer
8.466
3145493TOT1
Solar/Wind Harmer
0.408
3145453TOT5
Solar/Wind Harmer
0.245
3145603CNETO
Solar/Wind Harmer
0.163
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.414
971775AH1-396 GEN
Solar/Wind Harmer
0.278
961601AG1-000A GEN
Solar/Wind Harmer
3.071
958211AF2-115 GEN
Solar/Wind Harmer
2.072
963191AG1-168 GEN
Solar/Wind Harmer
0.691
3144293JTRSVLE
Adder
0.55
3144293JTRSVLE
Adder
0.463
316263AC1-034 GEN
Solar/Wind Harmer
6.56
3147133PAMPLIN
Solar/Wind Harmer
0.172
3147133PAMPLIN
Solar/Wind Harmer
0.138
962561AG1-105 GEN
Solar/Wind Harmer
8.039
964791AG1-342 GEN
Solar/Wind Harmer
3.189
3146843MT LREL
Solar/Wind Harmer
0.166
3146843MT LREL
Solar/Wind Harmer
0.166
3146776BUCKING
Solar/Wind Harmer
0.649
3146776BUCKING
Solar/Wind Harmer
0.053
316222AC1-221 GEN
Solar/Wind Harmer
0.603
971489AH1-241 GEN
Solar/Wind Harmer
7.696
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.723
CPLELTFEXP_CPLE->PJM
CLTF
11.118
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.426
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.913
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.507
MECLTFEXP_MEC->PJM
CLTF
3.537
SIGELTFEXP_SIGE->PJM
CLTF
0.108
NYPJM->LTFIMP_NY
CLTF
3.157
LGEELTFEXP_LGEE->PJM
CLTF
1.303
WECLTFEXP_WEC->PJM
CLTF
0.629
LAGNLTFEXP_LAGN->PJM
CLTF
7.83
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.391
TVALTFEXP_TVA->PJM
CLTF
3.97

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5650.14
MW Contribution:1.55
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
49.132
315243AE2-183_GT3
50/50
5.558
3151051BRUNSWICKS1
50/50
9.077
3151021BRUNSWICKG1
50/50
4.373
971451AH1-221 GEN
50/50
13.283
3150981CHESPKA
50/50
4.07
3150851SPRUNCC
50/50
1.461
3152331SURRY 2
50/50
12.331
3143226MDLTHAN
Solar/Wind Harmer
0.368
940641AE2-051 GEN
Solar/Wind Harmer
28.054
939411AE1-173 GEN
Solar/Wind Harmer
145.057
3143526WINTERP
Solar/Wind Harmer
1.742
970919AG2-571 GEN
Solar/Wind Harmer
11.363
970087AG2-069 GEN
Solar/Wind Harmer
25.456
316294AC1-161 GEN
Solar/Wind Harmer
5.4
944591AF1-124 GEN
Solar/Wind Harmer
69.98
316375AC2-012 GEN
Solar/Wind Harmer
0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.96
3146456SLIGO L269
Solar/Wind Harmer
0.306
316246AF1-032 C
Solar/Wind Harmer
0.137
316093AE2-104_GEN
Solar/Wind Harmer
5.099
970661AG2-428 GEN
Solar/Wind Harmer
30.138
316381AD1-082 GEN
Solar/Wind Harmer
0.316
970659AG2-427 GEN
Solar/Wind Harmer
14.649
316072AD1-144
Solar/Wind Harmer
0.109
3146516WINFALL
Solar/Wind Harmer
0.972
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
1.197
957481AF2-042 GEN
Solar/Wind Harmer
79.695
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
5.25
3130156CHOWAN
Solar/Wind Harmer
0.294
3151171GRAVELC
Adder
3.13
961611AG1-000B GEN
Solar/Wind Harmer
15.335
315671AE2-027_GEN
Solar/Wind Harmer
18.679
316023GEN1_S
Solar/Wind Harmer
0.655
971647AH1-324 GEN
Solar/Wind Harmer
12.413
3145663CRESWEL
Solar/Wind Harmer
0.81
971163AH1-040 GEN
Solar/Wind Harmer
23.157
315693AD1-088 GEN
Solar/Wind Harmer
13.873
971069AG2-661 GEN
Solar/Wind Harmer
5.126
962491AG1-098 GEN
Solar/Wind Harmer
16.401
316458AB2-190 GEN2
Solar/Wind Harmer
1.538
970129AG2-093 GEN
Solar/Wind Harmer
8.145
960081AF2-299 GEN
Solar/Wind Harmer
2.73
3138126ROCKLANDING
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
1.134
3145893MURPHYS
Solar/Wind Harmer
1.26
3146206CASHIE
Solar/Wind Harmer
0.283
971547AH1-271 GEN
Solar/Wind Harmer
6.043
3146173TUNIS
Solar/Wind Harmer
0.281
3142543TWELFTH
Solar/Wind Harmer
0.027
3145683EARLEYS
Solar/Wind Harmer
0.279
316011AB1-132 GEN
Solar/Wind Harmer
5.071
962571AG1-106 GEN
Solar/Wind Harmer
3.968
971795AH1-408 GEN
Solar/Wind Harmer
18.591
3146263WOODLND
Solar/Wind Harmer
0.278
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
2.5
316336AC2-165 C
Solar/Wind Harmer
0.011
971317AH1-138 GEN
Solar/Wind Harmer
2.057
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
0.275
3145783HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
316174AB2-169 GEN
Solar/Wind Harmer
0.007
316159AE1-175 C
Solar/Wind Harmer
0.235
944631AF1-128 GEN
Adder
128.871
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.386
316129AC1-054 GEN
Solar/Wind Harmer
1.006
971065AG2-659 GEN
Solar/Wind Harmer
11.378
3146293MARTNCO
Solar/Wind Harmer
0.246
315722AD1-056 GEN
Solar/Wind Harmer
1.662
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316494AC1-189 GEN
Solar/Wind Harmer
0.872
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
1.019
961671AG1-007 GEN
Solar/Wind Harmer
0.039
3146083TARBORO
Solar/Wind Harmer
0.255
3145493TOT1
Solar/Wind Harmer
1.136
3142433PROV 92
Solar/Wind Harmer
1.012
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
316359AB2-059 GEN
Solar/Wind Harmer
0.906
316049AB1-081 GEN
Solar/Wind Harmer
1.444
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.202
3142053HEARTS
Solar/Wind Harmer
0.444
970685AG2-442 GEN
Solar/Wind Harmer
18.609
970401AG2-262 GEN
Solar/Wind Harmer
1.452
963171AG1-166 GEN
Solar/Wind Harmer
1.316
971563AH1-280 GEN
Solar/Wind Harmer
2.632
3144293JTRSVLE
Adder
0.785
971777AH1-397 GEN
Solar/Wind Harmer
0.643
3141843SHACKLE
Adder
1.244
3141766HARMONY
Solar/Wind Harmer
0.048
3142416OLDCHRC
Solar/Wind Harmer
0.623
3142416OLDCHRC
Solar/Wind Harmer
0.239
3146926FARMVIL
Solar/Wind Harmer
0.141
3138133OCRAN
Solar/Wind Harmer
0.139
316003AC1-222 GEN
Solar/Wind Harmer
0.006
970937AG2-583 GEN
Solar/Wind Harmer
13.92
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.085
962861AG1-135 GEN
Solar/Wind Harmer
6.647
3141726DUNNSVL
Solar/Wind Harmer
0.786
3150351NORNECKC2
Adder
1.901
972003AH1-546 GEN
Solar/Wind Harmer
8.083
971377AH1-170 GEN
Solar/Wind Harmer
1.823
3147623JAMES R
Solar/Wind Harmer
0.396
316337AD2-073 GEN
Solar/Wind Harmer
0.146
970223AG2-152 GEN
Solar/Wind Harmer
10.672
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.084
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.176
316303AF2-085
50/50
6.551
315244AE2-183_ST
50/50
9.609
963041AG1-153 GEN
50/50
8.856
315779AE2-040
50/50
4.414
3151081ELIZAR1
50/50
29.922
3151091ELIZAR2
50/50
29.403
941591AE2-156 GEN
50/50
27.332
3152611GOSPORTB
50/50
4.152
3152621GOSPORTC
50/50
3.523
3152601GOSPORTA
50/50
3.25
971285AH1-108 GEN
50/50
2.391
972263AH1-716 GEN
50/50
170.662
941031AE2-094 GEN
Solar/Wind Harmer
63.788
944011AF1-069 GEN
Solar/Wind Harmer
20.842
970673AG2-436 GEN
Solar/Wind Harmer
72.487
970673AG2-436 GEN
Solar/Wind Harmer
48.325
316233AE1-074 FULL
Solar/Wind Harmer
0.268
971281AH1-106 GEN
Solar/Wind Harmer
4.649
971283AH1-107 GEN
Solar/Wind Harmer
4.649
971967AH1-528 GEN
Solar/Wind Harmer
53.477
970085AG2-068 GEN
Solar/Wind Harmer
16.971
970581AG2-369 GEN
Solar/Wind Harmer
14.595
316315AB2-025 C
Solar/Wind Harmer
0.256
315814AE2-033 C
Solar/Wind Harmer
24.917
3143316POE
Solar/Wind Harmer
1.232
957871AF2-081 GEN
Solar/Wind Harmer
15.244
319010AE1-072 C
Solar/Wind Harmer
1.539
3146406KITTY HAWK
Solar/Wind Harmer
0.038
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.164
315835AF2-110_GEN
Solar/Wind Harmer
2.081
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.208
316311AC2-079 GEN
Solar/Wind Harmer
8.702
3146486SUNBURY
Solar/Wind Harmer
0.302
3146486SUNBURY
Solar/Wind Harmer
0.302
316321Z2-027
Solar/Wind Harmer
0.056
3146396TANGLEW
Solar/Wind Harmer
0.833
3145176PASQUOTANK
Solar/Wind Harmer
0.187
971445AH1-216 GEN
Solar/Wind Harmer
21.042
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.294
3130156CHOWAN
Solar/Wind Harmer
0.294
972265AH1-717 GEN
Adder
22.85
3151201GRAVEL4
Adder
21.42
3151191GRAVEL3
Adder
21.149
3151211GRAVEL5
Adder
21.149
316369SG1_INVT
Solar/Wind Harmer
0.011
315816AE2-034 GEN
Solar/Wind Harmer
1.242
316132AB2-190 GEN1
Solar/Wind Harmer
1.538
3130546PLYMOUTH
Solar/Wind Harmer
0.286
965291AG1-394 GEN
Solar/Wind Harmer
1.269
315732AD1-074 GEN1
Solar/Wind Harmer
1.639
315733AD1-074 GEN2
Solar/Wind Harmer
1.639
315735AD1-075 GEN1
Solar/Wind Harmer
0.82
3145893MURPHYS
Solar/Wind Harmer
0.765
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
970601AG2-382 GEN
Solar/Wind Harmer
10.575
316087AB2-174 GEN
Solar/Wind Harmer
0.008
3146043SEABORD
Solar/Wind Harmer
0.28
3145513AHOSKIE
Solar/Wind Harmer
0.586
3145513AHOSKIE
Solar/Wind Harmer
0.28
315607AA1-063A GEN
Solar/Wind Harmer
0.572
3145683EARLEYS
Solar/Wind Harmer
0.558
3145683EARLEYS
Solar/Wind Harmer
0.279
3145683EARLEYS
Solar/Wind Harmer
0.279
315652AC1-086 GEN
Solar/Wind Harmer
30.678
3137643SOCKMAN
Solar/Wind Harmer
1.111
3145796HORNRTN
Solar/Wind Harmer
0.88
3145796HORNRTN
Solar/Wind Harmer
0.11
3146033SCOT NK
Solar/Wind Harmer
1.084
970831AG2-522 GEN
Solar/Wind Harmer
11.448
3138283WHITEMARSH
Solar/Wind Harmer
0.061
316005AA1-067
Solar/Wind Harmer
0.28
3145746EVERETS
Solar/Wind Harmer
1.039
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
970181AG2-120 GEN
Solar/Wind Harmer
3.25
957861AF2-080 GEN
Solar/Wind Harmer
11.129
316239AB2-077_GEN
Solar/Wind Harmer
0.002
972277AH1-723 GEN
Adder
76.921
270030AE2-140 GEN
Solar/Wind Harmer
12.711
316045AC1-158 PL2
Solar/Wind Helper
7.036
3147666LOUISA
Solar/Wind Helper
1.244
316192AB2-158 GEN
Solar/Wind Helper
2.045
316254AC1-120 GEN1
Solar/Wind Helper
1.287
316006AB2-029 C
Solar/Wind Helper
0.13
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.255
3145573BETHELC
Solar/Wind Harmer
0.255
971167AH1-042 GEN
Solar/Wind Harmer
22.645
315976AC1-164 GENA
Solar/Wind Harmer
26.291
316169AC1-164_GENC
Solar/Wind Harmer
22.713
315975AC1-164 GENB
Solar/Wind Harmer
0.778
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
971443AH1-215 GEN
Solar/Wind Harmer
4.236
3144303KENBRDG
Solar/Wind Harmer
0.201
970683AG2-441 GEN
Solar/Wind Harmer
16.616
970681AG2-440 GEN
Solar/Wind Harmer
13.292
946301AF1-294 GEN
Solar/Wind Harmer
4.868
961791AG1-021 GEN
Solar/Wind Harmer
2.368
3143873LANEXA
Solar/Wind Harmer
0.148
315657AE1-056 GEN
Solar/Wind Harmer
8.449
316118AC1-105 GEN
Solar/Wind Harmer
0.629
970189AG2-124 GEN
Solar/Wind Harmer
7.213
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.048
3147173SINAI
Solar/Wind Harmer
0.24
3147243WELCO
Solar/Wind Harmer
0.15
316312AB1-027
Solar/Wind Harmer
0.429
3141913WHIT STONE
Solar/Wind Harmer
0.234
3138133OCRAN
Solar/Wind Harmer
0.069
3141783LANCAST
Solar/Wind Harmer
0.137
3141783LANCAST
Solar/Wind Harmer
0.091
962981AG1-147 GEN
Solar/Wind Harmer
8.172
970285AG2-188 GEN
Solar/Wind Harmer
17.223
971845AH1-439 GEN
Solar/Wind Harmer
9.707
970327AG2-215 GEN
Solar/Wind Harmer
7.016
970865AG2-541 GEN
Solar/Wind Harmer
7.314
316123AC1-075 GEN
Solar/Wind Harmer
0.262
970165AG2-112 GEN
Solar/Wind Harmer
1.554
970163AG2-111 GEN
Solar/Wind Harmer
1.483
3141813NORNECK
Solar/Wind Harmer
0.191
972205AH1-687 GEN
Adder
7.916
971447AH1-217 GEN
Solar/Wind Harmer
4.969
270494AE1-108_GEN
Solar/Wind Harmer
1.845
972189AH1-679 GEN
Adder
2.488
316223AC1-118
Solar/Wind Harmer
0.103
972193AH1-681 GEN
Adder
2.949
316164AC1-076 GEN
Solar/Wind Helper
1.496
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
970533AG2-339 GEN
50/50
30.786
970531AG2-338 GEN
50/50
12.314
315242AE2-183_GT2
50/50
5.558
315241AE2-183_GT1
50/50
5.524
972185AH1-677 GEN
50/50
20.036
3151041BRUNSWICKG3
50/50
4.373
972187AH1-678 GEN
50/50
10.036
3150991CHESPKB
50/50
3.415
3150991CHESPKB
50/50
3.333
971223AH1-071 GEN
Solar/Wind Harmer
3.931
3143526WINTERP
Solar/Wind Harmer
1.742
970933AG2-581 GEN
Solar/Wind Harmer
25.944
3144356SAPONY
Solar/Wind Harmer
2.645
316185AD1-033 GEN
Solar/Wind Harmer
0.009
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.295
3145506HICKORY
Solar/Wind Harmer
1.229
3145506HICKORY
Solar/Wind Harmer
0.737
3145506HICKORY
Solar/Wind Harmer
0.184
316036AC1-147 C
Solar/Wind Harmer
0.057
316339AD2-160 GEN
Solar/Wind Harmer
0.497
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.171
3137176SLIGO L2192
Solar/Wind Harmer
1.217
3146456SLIGO L269
Solar/Wind Harmer
5.409
3130086AYDLETT
Solar/Wind Harmer
1.221
3146386ELIZ CT
Solar/Wind Harmer
0.303
970657AG2-426 GEN
Solar/Wind Harmer
10.611
970657AG2-426 GEN
Solar/Wind Harmer
2.224
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3146626S HERTFORD
Solar/Wind Harmer
0.299
3146626S HERTFORD
Solar/Wind Harmer
0.299
970099AG2-077 GEN
Solar/Wind Harmer
31.878
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.308
3146376EDENTON
Solar/Wind Harmer
1.308
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.017
315697AD1-025 GEN
Solar/Wind Harmer
0.325
944641AF1-129 GEN
Adder
137.21
316065AD1-022 GEN
Solar/Wind Harmer
13.074
3145893MURPHYS
Solar/Wind Harmer
1.897
3145893MURPHYS
Solar/Wind Harmer
0.51
3146173TUNIS
Solar/Wind Harmer
0.281
3146173TUNIS
Solar/Wind Harmer
0.281
316181AB2-040 GEN
Solar/Wind Harmer
0.407
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.167
316426AA2-053 GEN
Solar/Wind Harmer
0.935
3145593CAROLNA
Solar/Wind Harmer
0.276
3145593CAROLNA
Solar/Wind Harmer
0.276
966811AG1-552 GEN
Solar/Wind Harmer
2.997
3145593CAROLNA
Solar/Wind Harmer
0.344
3145796HORNRTN
Solar/Wind Harmer
0.825
3145783HORNRTN
Solar/Wind Harmer
4.886
3145783HORNRTN
Solar/Wind Harmer
3.909
3145783HORNRTN
Solar/Wind Harmer
1.222
3145783HORNRTN
Solar/Wind Harmer
0.489
316274AC1-208 GEN
Solar/Wind Harmer
1.384
3145933PARMELE
Solar/Wind Harmer
0.531
3145933PARMELE
Solar/Wind Harmer
0.265
3142946ENON
Solar/Wind Harmer
0.026
971741AH1-377 GEN
Solar/Wind Harmer
26.27
939181AE1-148 GEN
Solar/Wind Harmer
12.567
3142366NRTHEST
Adder
0.844
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970301AG2-198 GEN
Solar/Wind Harmer
10.992
3150691DARBY 3
Adder
18.496
3150701DARBY 4
Adder
18.453
3150681DARBY 2
Adder
18.432
3150671DARBY 1
Adder
18.41
3145493TOT1
Solar/Wind Harmer
0.592
3145453TOT5
Solar/Wind Harmer
0.355
3145603CNETO
Solar/Wind Harmer
0.237
961601AG1-000A GEN
Solar/Wind Harmer
4.486
316263AC1-034 GEN
Solar/Wind Harmer
9.586
316075AC2-137 C
Solar/Wind Harmer
0.069
970323AG2-213 GEN
Solar/Wind Harmer
10.747
971775AH1-396 GEN
Solar/Wind Harmer
0.403
316034AC1-036 C
Solar/Wind Harmer
0.018
962561AG1-105 GEN
Solar/Wind Harmer
11.957
964791AG1-342 GEN
Solar/Wind Harmer
4.752
3146843MT LREL
Solar/Wind Harmer
0.247
3146843MT LREL
Solar/Wind Harmer
0.247
958211AF2-115 GEN
Solar/Wind Harmer
2.961
963191AG1-168 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3144293JTRSVLE
Adder
0.661
3147133PAMPLIN
Solar/Wind Harmer
0.245
3147133PAMPLIN
Solar/Wind Harmer
0.196
3142296MT RD221
Adder
0.748
316222AC1-221 GEN
Solar/Wind Harmer
0.912
966871AG1-558 GEN
Solar/Wind Harmer
0.251
3146776BUCKING
Solar/Wind Harmer
0.848
3146776BUCKING
Solar/Wind Harmer
0.069
958261AF2-120 GEN
Solar/Wind Harmer
6.796
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.997
3150341NORNECKC1
Adder
1.981
942751AE2-291 GEN
Solar/Wind Harmer
9.768
971489AH1-241 GEN
Solar/Wind Harmer
9.113
316468AD1-105 GEN
Solar/Wind Harmer
-0.049
270013AE1-250 PV
Solar/Wind Harmer
0.004
315821AE2-092 GEN
Solar/Wind Harmer
0.008
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.248
316447AC1-158 HLD
Solar/Wind Helper
4.837
315651AD1-115 GEN
Solar/Wind Helper
0.937
226929AD2-058 GEN
Solar/Wind Helper
0.091
3151031BRUNSWICKG2
50/50
4.373
3151101ELIZAR3
50/50
30.305
3150861SPRUNCD
50/50
1.461
3151161SURRY 1
50/50
11.304
970917AG2-570 GEN
Solar/Wind Harmer
28.408
315773AC2-141 GEN
Solar/Wind Harmer
11.382
944581AF1-123 GEN
Solar/Wind Harmer
69.733
944601AF1-125 GEN
Solar/Wind Harmer
68.658
3144873MCLAUGH
Solar/Wind Harmer
0.008
3146456SLIGO L269
Solar/Wind Harmer
0.306
971153AH1-033 GEN
Solar/Wind Harmer
3.534
3144536CHRHLND
Solar/Wind Harmer
0.046
316320Y1-086
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
6.41
316083AB2-161 GEN
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
3.204
315813AE1-149 C
Solar/Wind Harmer
16.153
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
0.12
3146626S HERTFORD
Solar/Wind Harmer
0.299
315839AE2-212 C
Solar/Wind Harmer
0.002
3145273HOLLAND
Solar/Wind Harmer
0.223
316313AB2-026
Solar/Wind Harmer
0.186
316258AE1-075 C
Solar/Wind Harmer
0.223
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.463
965281AG1-393 GEN
Solar/Wind Harmer
3.139
3151221GRAVEL6
Adder
21.396
3151171GRAVELC
Adder
4.116
3146376EDENTON
Solar/Wind Harmer
0.294
961611AG1-000B GEN
Solar/Wind Harmer
7.797
316365GEN2_N
Solar/Wind Harmer
0.655
315614AA2-178 GEN
Solar/Wind Harmer
1.657
315778AD1-151 GEN
Solar/Wind Harmer
23.065
3156081AA2-088 GEN
Solar/Wind Harmer
0.007
970129AG2-093 GEN
Solar/Wind Harmer
17.309
316478AD1-087 GEN
Solar/Wind Harmer
0.999
316486AD2-202 GEN
Solar/Wind Harmer
0.293
971157AH1-035 GEN
Solar/Wind Harmer
3.43
315737AD1-076 GEN
Solar/Wind Harmer
3.669
3144216WINCHST
Adder
1.072
970133AG2-095 GEN
Solar/Wind Harmer
2.723
3145893MURPHYS
Solar/Wind Harmer
0.474
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
957521AF2-046 GEN
Solar/Wind Harmer
21.052
961681AG1-008 GEN
Solar/Wind Harmer
21.052
3150921YORKTN3
Adder
7.103
3146173TUNIS
Solar/Wind Harmer
0.281
313506AB2-031 GEN
Solar/Wind Harmer
0.867
3156021HOLLOMANSOL
Solar/Wind Harmer
1.274
316463AE2-346 GEN
Solar/Wind Harmer
0.241
316140AB2-099
Solar/Wind Harmer
0.1
962331AG1-082 GEN
Solar/Wind Harmer
2.99
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3146263WOODLND
Solar/Wind Harmer
0.278
3147043LAWRENC
Solar/Wind Harmer
0.166
316317KELFORD C
Solar/Wind Harmer
0.027
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
1.1
3145796HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
3143096IRON208
Adder
1.124
316382AG1-145 C
Solar/Wind Harmer
0.002
316210AC1-098 GEN
Solar/Wind Harmer
2.485
3145933PARMELE
Solar/Wind Harmer
0.265
966801AG1-551 GEN
Solar/Wind Harmer
3.091
3142946ENON
Solar/Wind Harmer
0.089
315724AD1-057 GEN
Solar/Wind Harmer
0.985
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316327AA2-057 GEN
Solar/Wind Harmer
0.393
970909AG2-566 GEN
Solar/Wind Harmer
2.748
316131AB2-060 GEN
Solar/Wind Harmer
0.81
3146233WITAKRS
Solar/Wind Harmer
1.286
3146233WITAKRS
Solar/Wind Harmer
0.174
3138543CONSLDL
Solar/Wind Harmer
0.169
964241AG1-285 GEN
Solar/Wind Harmer
17.051
3146073TAR RVR
Solar/Wind Harmer
0.255
3146083TARBORO
Solar/Wind Harmer
0.255
970293AG2-193 GEN
Solar/Wind Harmer
2.717
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
315785AD2-033 C
Solar/Wind Harmer
2.056
961601AG1-000A GEN
Solar/Wind Harmer
17.946
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.252
971623AH1-311 GEN
Solar/Wind Harmer
0.505
970257AG2-171 GEN
Solar/Wind Harmer
8.061
959311AF2-222 GEN
Solar/Wind Harmer
22.323
963181AG1-167 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3147133PAMPLIN
Solar/Wind Harmer
0.769
971193AH1-056 GEN
Solar/Wind Harmer
14.916
3141843SHACKLE
Adder
1.244
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3141766HARMONY
Solar/Wind Harmer
3.224
316156AD2-030 GEN
Solar/Wind Harmer
0.179
3141873WAN 176
Solar/Wind Harmer
4.293
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
10.242
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3142416OLDCHRC
Solar/Wind Harmer
2.323
3146926FARMVIL
Solar/Wind Harmer
0.141
971683AH1-343 GEN
Solar/Wind Harmer
8.112
962971AG1-146 GEN
Solar/Wind Harmer
3.502
316283AC2-100 C
Solar/Wind Harmer
0.428
316473AC1-191 GEN
Solar/Wind Harmer
0.734
970009AG2-005 GEN
Solar/Wind Harmer
1.596
3146776BUCKING
Solar/Wind Harmer
0.076
316404AE1-155 C
Solar/Wind Harmer
0.046
3150351NORNECKC2
Adder
1.933
970221AG2-151 GEN
Solar/Wind Harmer
9.113
971781AH1-399 GEN
Solar/Wind Harmer
0.197
3141906WESTMOR
Solar/Wind Harmer
0.057
270197AD1-017 GEN1
Solar/Wind Harmer
0.888
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.176
972255AH1-712 GEN
Adder
66.009
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
970737AG2-469 GEN
Solar/Wind Harmer
5.167
958131AF2-107 GEN
Solar/Wind Harmer
3.333
316044AC1-158 PL1
Solar/Wind Helper
2.198
316450AC1-158 RIC
Solar/Wind Helper
0.586
3147666LOUISA
Solar/Wind Helper
0.715
316170AC1-121 GEN2
Solar/Wind Helper
0.429
3141196NOKESVL
Solar/Wind Helper
1.038
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.311
226910AB2-157 C
Solar/Wind Helper
0.013
CPLELTFEXP_CPLE->PJM
CLTF
16.793
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.855
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.654
MECLTFEXP_MEC->PJM
CLTF
6.28
SIGELTFEXP_SIGE->PJM
CLTF
0.191
NYPJM->LTFIMP_NY
CLTF
3.567
LGEELTFEXP_LGEE->PJM
CLTF
2.341
WECLTFEXP_WEC->PJM
CLTF
1.189
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
LAGNLTFEXP_LAGN->PJM
CLTF
12.487
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.918
TVALTFEXP_TVA->PJM
CLTF
6.285

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.69 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4402.07
MW Contribution:1.36
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
29.471
970531AG2-338 GEN
50/50
11.789
315242AE2-183_GT2
50/50
5.306
315241AE2-183_GT1
50/50
5.273
972185AH1-677 GEN
50/50
19.129
3151041BRUNSWICKG3
50/50
4.17
972187AH1-678 GEN
50/50
9.57
3150991CHESPKB
50/50
3.24
3150991CHESPKB
50/50
3.162
971223AH1-071 GEN
Solar/Wind Harmer
3.471
970933AG2-581 GEN
Solar/Wind Harmer
24.629
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.168
3145506HICKORY
Solar/Wind Harmer
0.701
3145506HICKORY
Solar/Wind Harmer
0.175
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.28
316036AC1-147 C
Solar/Wind Harmer
0.054
316339AD2-160 GEN
Solar/Wind Harmer
0.472
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.162
3137176SLIGO L2192
Solar/Wind Harmer
1.156
3146456SLIGO L269
Solar/Wind Harmer
5.139
3130086AYDLETT
Solar/Wind Harmer
1.16
3144356SAPONY
Solar/Wind Harmer
2.426
3146386ELIZ CT
Solar/Wind Harmer
0.287
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3143526WINTERP
Solar/Wind Harmer
1.47
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
970099AG2-077 GEN
Solar/Wind Harmer
29.918
3146376EDENTON
Solar/Wind Harmer
1.233
3146376EDENTON
Solar/Wind Harmer
1.233
316236AE1-162_GEN
Solar/Wind Harmer
0.002
315742AE1-103 GEN
Solar/Wind Harmer
0.003
970657AG2-426 GEN
Solar/Wind Harmer
9.567
970657AG2-426 GEN
Solar/Wind Harmer
2.006
316065AD1-022 GEN
Solar/Wind Harmer
12.243
3145893MURPHYS
Solar/Wind Harmer
1.767
3145893MURPHYS
Solar/Wind Harmer
0.475
3146173TUNIS
Solar/Wind Harmer
0.262
3146173TUNIS
Solar/Wind Harmer
0.262
316181AB2-040 GEN
Solar/Wind Harmer
0.376
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
316426AA2-053 GEN
Solar/Wind Harmer
0.866
3145593CAROLNA
Solar/Wind Harmer
0.255
3145593CAROLNA
Solar/Wind Harmer
0.255
966811AG1-552 GEN
Solar/Wind Harmer
2.773
3145593CAROLNA
Solar/Wind Harmer
0.318
316033AB2-134 GEN
Solar/Wind Harmer
0.015
315697AD1-025 GEN
Solar/Wind Harmer
0.287
3145783HORNRTN
Solar/Wind Harmer
4.52
3145783HORNRTN
Solar/Wind Harmer
3.616
3145783HORNRTN
Solar/Wind Harmer
1.13
3145783HORNRTN
Solar/Wind Harmer
0.452
3145796HORNRTN
Solar/Wind Harmer
0.762
3145933PARMELE
Solar/Wind Harmer
0.493
3145933PARMELE
Solar/Wind Harmer
0.247
316274AC1-208 GEN
Solar/Wind Harmer
1.28
971741AH1-377 GEN
Solar/Wind Harmer
23.908
939181AE1-148 GEN
Solar/Wind Harmer
11.558
316240AF1-291 C
Solar/Wind Harmer
0.002
3145493TOT1
Solar/Wind Harmer
0.547
3145453TOT5
Solar/Wind Harmer
0.328
3145603CNETO
Solar/Wind Harmer
0.219
313527AB2-043 GEN
Solar/Wind Harmer
0.003
944641AF1-129 GEN
Adder
111.535
970301AG2-198 GEN
Solar/Wind Harmer
9.924
316303AF2-085
50/50
5.785
315244AE2-183_ST
50/50
9.174
963041AG1-153 GEN
50/50
8.444
3151081ELIZAR1
50/50
28.413
3151091ELIZAR2
50/50
27.92
941591AE2-156 GEN
50/50
25.939
3152611GOSPORTB
50/50
3.939
3152621GOSPORTC
50/50
3.343
3152601GOSPORTA
50/50
3.084
315779AE2-040
50/50
4.048
972263AH1-716 GEN
50/50
164.964
941031AE2-094 GEN
Solar/Wind Harmer
61.065
944011AF1-069 GEN
Solar/Wind Harmer
19.952
970673AG2-436 GEN
Solar/Wind Harmer
69.269
970673AG2-436 GEN
Solar/Wind Harmer
46.179
971967AH1-528 GEN
Solar/Wind Harmer
50.977
970085AG2-068 GEN
Solar/Wind Harmer
16.126
970581AG2-369 GEN
Solar/Wind Harmer
13.869
957871AF2-081 GEN
Solar/Wind Harmer
14.487
319010AE1-072 C
Solar/Wind Harmer
1.462
3146406KITTY HAWK
Solar/Wind Harmer
0.036
316315AB2-025 C
Solar/Wind Harmer
0.234
315814AE2-033 C
Solar/Wind Harmer
22.859
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.156
316321Z2-027
Solar/Wind Harmer
0.053
3146396TANGLEW
Solar/Wind Harmer
0.789
3145176PASQUOTANK
Solar/Wind Harmer
0.177
3146486SUNBURY
Solar/Wind Harmer
0.286
3146486SUNBURY
Solar/Wind Harmer
0.286
315835AF2-110_GEN
Solar/Wind Harmer
1.956
316233AE1-074 FULL
Solar/Wind Harmer
0.226
971281AH1-106 GEN
Solar/Wind Harmer
3.922
971283AH1-107 GEN
Solar/Wind Harmer
3.922
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316311AC2-079 GEN
Solar/Wind Harmer
8.046
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.192
3130156CHOWAN
Solar/Wind Harmer
0.277
3130156CHOWAN
Solar/Wind Harmer
0.277
971445AH1-216 GEN
Solar/Wind Harmer
19.461
970119AG2-088 GEN
50/50
43.39
315243AE2-183_GT3
50/50
5.306
3151051BRUNSWICKS1
50/50
8.655
3151021BRUNSWICKG1
50/50
4.17
971451AH1-221 GEN
50/50
12.666
3150981CHESPKA
50/50
3.862
3152331SURRY 2
50/50
11.978
940641AE2-051 GEN
Solar/Wind Harmer
26.972
939411AE1-173 GEN
Solar/Wind Harmer
139.157
3143226MDLTHAN
Solar/Wind Harmer
0.325
970919AG2-571 GEN
Solar/Wind Harmer
10.802
970087AG2-069 GEN
Solar/Wind Harmer
24.19
316294AC1-161 GEN
Solar/Wind Harmer
5.215
944591AF1-124 GEN
Solar/Wind Harmer
66.808
316375AC2-012 GEN
Solar/Wind Harmer
0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.912
3146456SLIGO L269
Solar/Wind Harmer
0.29
316246AF1-032 C
Solar/Wind Harmer
0.13
316093AE2-104_GEN
Solar/Wind Harmer
4.794
3146516WINFALL
Solar/Wind Harmer
0.92
3146516WINFALL
Solar/Wind Harmer
0.284
316072AD1-144
Solar/Wind Harmer
0.103
3143526WINTERP
Solar/Wind Harmer
1.47
957481AF2-042 GEN
Solar/Wind Harmer
74.795
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
1.108
970661AG2-428 GEN
Solar/Wind Harmer
27.311
316381AD1-082 GEN
Solar/Wind Harmer
0.284
3145663CRESWEL
Solar/Wind Harmer
0.761
971163AH1-040 GEN
Solar/Wind Harmer
21.769
970659AG2-427 GEN
Solar/Wind Harmer
13.13
315693AD1-088 GEN
Solar/Wind Harmer
12.923
316023GEN1_S
Solar/Wind Harmer
0.603
3151171GRAVELC
Adder
2.853
962491AG1-098 GEN
Solar/Wind Harmer
15.256
3146206CASHIE
Solar/Wind Harmer
0.265
971547AH1-271 GEN
Solar/Wind Harmer
5.655
3138126ROCKLANDING
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
1.056
3145893MURPHYS
Solar/Wind Harmer
1.174
961611AG1-000B GEN
Solar/Wind Harmer
13.793
3146173TUNIS
Solar/Wind Harmer
0.262
960081AF2-299 GEN
Solar/Wind Harmer
2.514
3145683EARLEYS
Solar/Wind Harmer
0.26
3146263WOODLND
Solar/Wind Harmer
0.259
971647AH1-324 GEN
Solar/Wind Harmer
11.046
316011AB1-132 GEN
Solar/Wind Harmer
4.685
962571AG1-106 GEN
Solar/Wind Harmer
3.666
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
17.096
3145963POPLR C
Solar/Wind Harmer
0.256
971317AH1-138 GEN
Solar/Wind Harmer
1.913
3145823KELFORD
Solar/Wind Harmer
0.256
3143336POWHATN
Solar/Wind Harmer
4.523
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3145783HORNRTN
Solar/Wind Harmer
0.254
3145796HORNRTN
Solar/Wind Harmer
0.838
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Adder
2.297
971069AG2-661 GEN
Solar/Wind Harmer
4.473
315687AD1-152 GEN
Solar/Wind Harmer
0.008
316159AE1-175 C
Solar/Wind Harmer
0.215
316212AC1-099_GEN
Solar/Wind Harmer
1.283
316458AB2-190 GEN2
Solar/Wind Harmer
1.325
3146293MARTNCO
Solar/Wind Harmer
0.229
316129AC1-054 GEN
Solar/Wind Harmer
0.928
970129AG2-093 GEN
Solar/Wind Harmer
7.001
971065AG2-659 GEN
Solar/Wind Harmer
10.492
315671AE2-027_GEN
Solar/Wind Harmer
15.643
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315722AD1-056 GEN
Solar/Wind Harmer
1.533
3150851SPRUNCC
Adder
1.101
316494AC1-189 GEN
Solar/Wind Harmer
0.807
3146233WITAKRS
Solar/Wind Harmer
0.94
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.049
316336AC2-165 C
Solar/Wind Harmer
0.009
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.186
316359AB2-059 GEN
Solar/Wind Harmer
0.835
316049AB1-081 GEN
Solar/Wind Harmer
1.331
3142053HEARTS
Solar/Wind Harmer
0.409
970401AG2-262 GEN
Solar/Wind Harmer
1.326
970685AG2-442 GEN
Solar/Wind Harmer
16.767
944631AF1-128 GEN
Adder
106.166
963171AG1-166 GEN
Solar/Wind Harmer
1.18
971563AH1-280 GEN
Solar/Wind Harmer
2.361
3144293JTRSVLE
Adder
0.705
3142543TWELFTH
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.569
3141843SHACKLE
Adder
1.102
3143096IRON208
Adder
0.902
3141766HARMONY
Solar/Wind Harmer
0.043
3143316POE
Solar/Wind Harmer
1.085
315816AE2-034 GEN
Solar/Wind Harmer
1.168
972265AH1-717 GEN
Adder
20.825
3151201GRAVEL4
Adder
19.522
3151191GRAVEL3
Adder
19.275
3151211GRAVEL5
Adder
19.275
3130546PLYMOUTH
Solar/Wind Harmer
0.268
315732AD1-074 GEN1
Solar/Wind Harmer
1.536
315733AD1-074 GEN2
Solar/Wind Harmer
1.536
315735AD1-075 GEN1
Solar/Wind Harmer
0.769
965291AG1-394 GEN
Solar/Wind Harmer
1.182
3146206CASHIE
Solar/Wind Harmer
0.265
970601AG2-382 GEN
Solar/Wind Harmer
9.896
3145893MURPHYS
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
0.264
3145513AHOSKIE
Solar/Wind Harmer
0.546
3145513AHOSKIE
Solar/Wind Harmer
0.261
3146043SEABORD
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.52
3145683EARLEYS
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.26
316087AB2-174 GEN
Solar/Wind Harmer
0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.531
315652AC1-086 GEN
Solar/Wind Harmer
28.344
3137643SOCKMAN
Solar/Wind Harmer
1.027
316369SG1_INVT
Solar/Wind Harmer
0.01
3145796HORNRTN
Solar/Wind Harmer
0.813
3145796HORNRTN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
1.006
970831AG2-522 GEN
Solar/Wind Harmer
10.563
316132AB2-190 GEN1
Solar/Wind Harmer
1.325
316005AA1-067
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.964
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
970181AG2-120 GEN
Solar/Wind Harmer
3.014
3138283WHITEMARSH
Solar/Wind Harmer
0.056
971285AH1-108 GEN
Adder
1.802
957861AF2-080 GEN
Solar/Wind Harmer
10.3
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.835
3144303KENBRDG
Solar/Wind Harmer
0.182
970683AG2-441 GEN
Solar/Wind Harmer
14.971
970681AG2-440 GEN
Solar/Wind Harmer
11.976
316118AC1-105 GEN
Solar/Wind Harmer
0.574
946301AF1-294 GEN
Solar/Wind Harmer
4.367
961791AG1-021 GEN
Solar/Wind Harmer
2.125
315657AE1-056 GEN
Solar/Wind Harmer
7.556
3147173SINAI
Solar/Wind Harmer
0.219
3147243WELCO
Solar/Wind Harmer
0.137
315976AC1-164 GENA
Solar/Wind Harmer
22.6
316169AC1-164_GENC
Solar/Wind Harmer
19.524
315975AC1-164 GENB
Solar/Wind Harmer
0.669
3141873WAN 176
Solar/Wind Harmer
0.043
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
6.392
971167AH1-042 GEN
Solar/Wind Harmer
19.104
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
3143873LANEXA
Solar/Wind Harmer
0.129
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.21
3138133OCRAN
Solar/Wind Harmer
0.062
3141783LANCAST
Solar/Wind Harmer
0.123
3141783LANCAST
Solar/Wind Harmer
0.082
962981AG1-147 GEN
Solar/Wind Harmer
7.345
970327AG2-215 GEN
Solar/Wind Harmer
6.31
970865AG2-541 GEN
Solar/Wind Harmer
6.523
970285AG2-188 GEN
Solar/Wind Harmer
14.703
971845AH1-439 GEN
Solar/Wind Harmer
8.235
3141813NORNECK
Solar/Wind Harmer
0.172
316123AC1-075 GEN
Solar/Wind Harmer
0.229
970165AG2-112 GEN
Solar/Wind Harmer
1.36
970163AG2-111 GEN
Solar/Wind Harmer
1.297
316312AB1-027
Solar/Wind Harmer
0.286
3151031BRUNSWICKG2
50/50
4.17
3151101ELIZAR3
50/50
28.777
3151161SURRY 1
50/50
10.302
970917AG2-570 GEN
Solar/Wind Harmer
27.004
315773AC2-141 GEN
Solar/Wind Harmer
10.994
944581AF1-123 GEN
Solar/Wind Harmer
66.571
944601AF1-125 GEN
Solar/Wind Harmer
65.546
3144873MCLAUGH
Solar/Wind Harmer
0.007
3146456SLIGO L269
Solar/Wind Harmer
0.29
971153AH1-033 GEN
Solar/Wind Harmer
3.357
316320Y1-086
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.043
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146626S HERTFORD
Solar/Wind Harmer
0.282
3145273HOLLAND
Solar/Wind Harmer
0.209
3146376EDENTON
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
0.111
970661AG2-428 GEN
Solar/Wind Harmer
5.809
316083AB2-161 GEN
Solar/Wind Harmer
0.004
315614AA2-178 GEN
Solar/Wind Harmer
1.557
970659AG2-427 GEN
Solar/Wind Harmer
2.872
316365GEN2_N
Solar/Wind Harmer
0.603
3151221GRAVEL6
Adder
19.5
3151171GRAVELC
Adder
3.752
971157AH1-035 GEN
Solar/Wind Harmer
3.217
315813AE1-149 C
Solar/Wind Harmer
14.26
315737AD1-076 GEN
Solar/Wind Harmer
3.44
316478AD1-087 GEN
Solar/Wind Harmer
0.932
316486AD2-202 GEN
Solar/Wind Harmer
0.274
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3146206CASHIE
Solar/Wind Harmer
0.265
3144216WINCHST
Adder
0.999
3145893MURPHYS
Solar/Wind Harmer
0.442
3145893MURPHYS
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
6.638
957521AF2-046 GEN
Solar/Wind Harmer
19.613
961681AG1-008 GEN
Solar/Wind Harmer
19.613
961611AG1-000B GEN
Solar/Wind Harmer
7.014
3146173TUNIS
Solar/Wind Harmer
0.262
3156021HOLLOMANSOL
Solar/Wind Harmer
1.189
316463AE2-346 GEN
Solar/Wind Harmer
0.224
316140AB2-099
Solar/Wind Harmer
0.093
962331AG1-082 GEN
Solar/Wind Harmer
2.786
3146263WOODLND
Solar/Wind Harmer
0.259
313506AB2-031 GEN
Solar/Wind Harmer
0.8
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3145963POPLR C
Solar/Wind Harmer
0.256
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.256
316313AB2-026
Solar/Wind Harmer
0.16
316258AE1-075 C
Solar/Wind Harmer
0.192
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.845
3145796HORNRTN
Solar/Wind Harmer
1.016
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Solar/Wind Harmer
0.152
315839AE2-212 C
Solar/Wind Harmer
0.002
315778AD1-151 GEN
Solar/Wind Harmer
20.127
316382AG1-145 C
Solar/Wind Harmer
0.002
965281AG1-393 GEN
Solar/Wind Harmer
2.647
316210AC1-098 GEN
Solar/Wind Harmer
2.301
3145933PARMELE
Solar/Wind Harmer
0.247
966801AG1-551 GEN
Solar/Wind Harmer
2.873
970129AG2-093 GEN
Solar/Wind Harmer
14.877
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315724AD1-057 GEN
Solar/Wind Harmer
0.909
316327AA2-057 GEN
Solar/Wind Harmer
0.363
3150861SPRUNCD
Adder
1.101
970133AG2-095 GEN
Solar/Wind Harmer
2.289
3146233WITAKRS
Solar/Wind Harmer
1.186
3146233WITAKRS
Solar/Wind Harmer
0.161
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
3138543CONSLDL
Solar/Wind Harmer
0.156
316131AB2-060 GEN
Solar/Wind Harmer
0.739
964241AG1-285 GEN
Solar/Wind Harmer
15.529
970909AG2-566 GEN
Solar/Wind Harmer
2.481
961601AG1-000A GEN
Solar/Wind Harmer
16.539
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.232
971623AH1-311 GEN
Solar/Wind Harmer
0.465
315785AD2-033 C
Solar/Wind Harmer
1.864
970257AG2-171 GEN
Solar/Wind Harmer
7.295
959311AF2-222 GEN
Solar/Wind Harmer
20.178
3142946ENON
Solar/Wind Harmer
0.074
963181AG1-167 GEN
Solar/Wind Harmer
0.885
3144293JTRSVLE
Adder
0.705
3147133PAMPLIN
Solar/Wind Harmer
0.687
971193AH1-056 GEN
Solar/Wind Harmer
13.34
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.346
316156AD2-030 GEN
Solar/Wind Harmer
0.16
3141873WAN 176
Solar/Wind Harmer
3.848
316280AD1-041 GEN
Solar/Wind Harmer
0.004
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.102
3143096IRON208
Adder
0.902
3143096IRON208
Adder
0.884
3141766HARMONY
Solar/Wind Harmer
2.867
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.123
316283AC2-100 C
Solar/Wind Harmer
0.389
971683AH1-343 GEN
Solar/Wind Harmer
7.294
962971AG1-146 GEN
Solar/Wind Harmer
3.148
970293AG2-193 GEN
Solar/Wind Harmer
2.064
970009AG2-005 GEN
Solar/Wind Harmer
1.436
316404AE1-155 C
Solar/Wind Harmer
0.042
3146776BUCKING
Solar/Wind Harmer
0.065
3150351NORNECKC2
Adder
1.745
3142433PROV 92
Solar/Wind Harmer
0.86
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
3138133OCRAN
Solar/Wind Harmer
0.125
316003AC1-222 GEN
Solar/Wind Harmer
0.006
3146926FARMVIL
Solar/Wind Harmer
0.123
970937AG2-583 GEN
Solar/Wind Harmer
11.537
962861AG1-135 GEN
Solar/Wind Harmer
5.983
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
3141726DUNNSVL
Solar/Wind Harmer
0.706
3150351NORNECKC2
Adder
1.716
961601AG1-000A GEN
Solar/Wind Harmer
4.135
316263AC1-034 GEN
Solar/Wind Harmer
8.835
970323AG2-213 GEN
Solar/Wind Harmer
9.727
971775AH1-396 GEN
Solar/Wind Harmer
0.365
316034AC1-036 C
Solar/Wind Harmer
0.017
962561AG1-105 GEN
Solar/Wind Harmer
10.919
964791AG1-342 GEN
Solar/Wind Harmer
4.339
3146843MT LREL
Solar/Wind Harmer
0.226
3146843MT LREL
Solar/Wind Harmer
0.226
3142946ENON
Solar/Wind Harmer
0.022
958211AF2-115 GEN
Solar/Wind Harmer
2.656
963191AG1-168 GEN
Solar/Wind Harmer
0.885
3144293JTRSVLE
Adder
0.705
3144293JTRSVLE
Adder
0.593
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
316075AC2-137 C
Solar/Wind Harmer
0.055
316222AC1-221 GEN
Solar/Wind Harmer
0.83
3150691DARBY 3
Adder
13.407
3150701DARBY 4
Adder
13.376
3150681DARBY 2
Adder
13.36
3150671DARBY 1
Adder
13.345
958261AF2-120 GEN
Solar/Wind Harmer
6.119
3142366NRTHEST
Adder
0.595
3146776BUCKING
Solar/Wind Harmer
0.717
3146776BUCKING
Solar/Wind Harmer
0.058
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.803
3150341NORNECKC1
Adder
1.788
3142416OLDCHRC
Solar/Wind Harmer
1.55
3141906WESTMOR
Solar/Wind Harmer
0.053
970221AG2-151 GEN
Solar/Wind Harmer
7.048
316473AC1-191 GEN
Solar/Wind Harmer
0.412
970737AG2-469 GEN
Solar/Wind Harmer
4.87
316044AC1-158 PL1
Solar/Wind Helper
1.723
316450AC1-158 RIC
Solar/Wind Helper
0.459
3147666LOUISA
Solar/Wind Helper
0.596
942751AE2-291 GEN
Solar/Wind Harmer
8.42
971489AH1-241 GEN
Solar/Wind Harmer
7.048
3142296MT RD221
Adder
0.414
270013AE1-250 PV
Solar/Wind Harmer
0.004
966871AG1-558 GEN
Solar/Wind Harmer
0.141
316447AC1-158 HLD
Solar/Wind Helper
3.792
972205AH1-687 GEN
Adder
6.309
316223AC1-118
Solar/Wind Harmer
0.095
971447AH1-217 GEN
Solar/Wind Harmer
3.746
270494AE1-108_GEN
Solar/Wind Harmer
1.403
316164AC1-076 GEN
Solar/Wind Helper
1.139
3142416OLDCHRC
Solar/Wind Harmer
0.416
3142416OLDCHRC
Solar/Wind Harmer
0.159
972003AH1-546 GEN
Solar/Wind Harmer
6.522
316337AD2-073 GEN
Solar/Wind Harmer
0.133
971377AH1-170 GEN
Solar/Wind Harmer
1.41
3147623JAMES R
Solar/Wind Harmer
0.306
970223AG2-152 GEN
Solar/Wind Harmer
9.004
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.068
316045AC1-158 PL2
Solar/Wind Helper
5.515
3147666LOUISA
Solar/Wind Helper
1.037
316192AB2-158 GEN
Solar/Wind Helper
1.708
CPLELTFEXP_CPLE->PJM
CLTF
15.205
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.962
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.385
MECLTFEXP_MEC->PJM
CLTF
4.747
SIGELTFEXP_SIGE->PJM
CLTF
0.142
NYPJM->LTFIMP_NY
CLTF
2.749
LGEELTFEXP_LGEE->PJM
CLTF
1.702
WECLTFEXP_WEC->PJM
CLTF
0.865
LAGNLTFEXP_LAGN->PJM
CLTF
10.194
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.592
TVALTFEXP_TVA->PJM
CLTF
5.103

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.34 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3619.13
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
3.255
970933AG2-581 GEN
Solar/Wind Harmer
21.207
3143526WINTERP
Solar/Wind Harmer
1.35
3144356SAPONY
Solar/Wind Harmer
2.053
970099AG2-077 GEN
Solar/Wind Harmer
25.81
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.89
3145506HICKORY
Solar/Wind Harmer
0.534
3145506HICKORY
Solar/Wind Harmer
0.134
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.213
316339AD2-160 GEN
Solar/Wind Harmer
0.36
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.124
3137176SLIGO L2192
Solar/Wind Harmer
0.883
3146456SLIGO L269
Solar/Wind Harmer
3.926
316036AC1-147 C
Solar/Wind Harmer
0.041
3130086AYDLETT
Solar/Wind Harmer
0.886
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
7.686
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.961
3146376EDENTON
Solar/Wind Harmer
0.961
316181AB2-040 GEN
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
3145893MURPHYS
Solar/Wind Harmer
1.424
3145893MURPHYS
Solar/Wind Harmer
0.383
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.211
966811AG1-552 GEN
Solar/Wind Harmer
2.295
3145593CAROLNA
Solar/Wind Harmer
0.263
3146173TUNIS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.211
316065AD1-022 GEN
Solar/Wind Harmer
9.733
316426AA2-053 GEN
Solar/Wind Harmer
0.714
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3145796HORNRTN
Solar/Wind Harmer
0.632
971741AH1-377 GEN
Solar/Wind Harmer
20.897
3145783HORNRTN
Solar/Wind Harmer
3.74
3145783HORNRTN
Solar/Wind Harmer
2.992
3145783HORNRTN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.374
939181AE1-148 GEN
Solar/Wind Harmer
9.88
970301AG2-198 GEN
Solar/Wind Harmer
8.706
316274AC1-208 GEN
Solar/Wind Harmer
1.058
313527AB2-043 GEN
Solar/Wind Harmer
0.003
316240AF1-291 C
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.401
3145933PARMELE
Solar/Wind Harmer
0.2
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.223
970323AG2-213 GEN
Solar/Wind Harmer
8.431
971775AH1-396 GEN
Solar/Wind Harmer
0.316
316034AC1-036 C
Solar/Wind Harmer
0.014
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
9.407
3145493TOT1
Solar/Wind Harmer
0.453
3145453TOT5
Solar/Wind Harmer
0.272
3145603CNETO
Solar/Wind Harmer
0.181
964791AG1-342 GEN
Solar/Wind Harmer
3.74
3146843MT LREL
Solar/Wind Harmer
0.195
3146843MT LREL
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
3.447
316263AC1-034 GEN
Solar/Wind Harmer
7.365
958211AF2-115 GEN
Solar/Wind Harmer
2.318
963191AG1-168 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.153
316222AC1-221 GEN
Solar/Wind Harmer
0.714
3142946ENON
Solar/Wind Harmer
0.016
3146776BUCKING
Solar/Wind Harmer
0.65
3146776BUCKING
Solar/Wind Harmer
0.053
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
316075AC2-137 C
Solar/Wind Harmer
0.04
942751AE2-291 GEN
Solar/Wind Harmer
7.378
958261AF2-120 GEN
Solar/Wind Harmer
4.15
971489AH1-241 GEN
Solar/Wind Harmer
6.633
3142296MT RD221
Adder
0.39
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
966871AG1-558 GEN
Solar/Wind Harmer
0.131
316447AC1-158 HLD
Solar/Wind Helper
3.579
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
52.507
944011AF1-069 GEN
Solar/Wind Harmer
17.156
970673AG2-436 GEN
Solar/Wind Harmer
59.565
970673AG2-436 GEN
Solar/Wind Harmer
39.71
971967AH1-528 GEN
Solar/Wind Harmer
43.86
970085AG2-068 GEN
Solar/Wind Harmer
13.865
970581AG2-369 GEN
Solar/Wind Harmer
11.924
316233AE1-074 FULL
Solar/Wind Harmer
0.208
971281AH1-106 GEN
Solar/Wind Harmer
3.602
971283AH1-107 GEN
Solar/Wind Harmer
3.602
316315AB2-025 C
Solar/Wind Harmer
0.198
315814AE2-033 C
Solar/Wind Harmer
19.336
3143316POE
Solar/Wind Harmer
0.915
957871AF2-081 GEN
Solar/Wind Harmer
11.058
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
1.117
3146406KITTY HAWK
Solar/Wind Harmer
0.028
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.119
315835AF2-110_GEN
Solar/Wind Harmer
1.513
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.607
3145176PASQUOTANK
Solar/Wind Harmer
0.136
3146486SUNBURY
Solar/Wind Harmer
0.22
3146486SUNBURY
Solar/Wind Harmer
0.22
316311AC2-079 GEN
Solar/Wind Harmer
6.318
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.151
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316087AB2-174 GEN
Solar/Wind Harmer
0.006
3130156CHOWAN
Solar/Wind Harmer
0.216
3130156CHOWAN
Solar/Wind Harmer
0.216
965291AG1-394 GEN
Solar/Wind Harmer
0.951
315816AE2-034 GEN
Solar/Wind Harmer
0.918
315652AC1-086 GEN
Solar/Wind Harmer
23.483
3137643SOCKMAN
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.574
3145893MURPHYS
Solar/Wind Harmer
0.213
3146043SEABORD
Solar/Wind Harmer
0.213
315607AA1-063A GEN
Solar/Wind Harmer
0.434
3130546PLYMOUTH
Solar/Wind Harmer
0.212
315732AD1-074 GEN1
Solar/Wind Harmer
1.217
315733AD1-074 GEN2
Solar/Wind Harmer
1.217
315735AD1-075 GEN1
Solar/Wind Harmer
0.609
3146206CASHIE
Solar/Wind Harmer
0.211
970601AG2-382 GEN
Solar/Wind Harmer
7.883
3145513AHOSKIE
Solar/Wind Harmer
0.441
3145513AHOSKIE
Solar/Wind Harmer
0.211
3145796HORNRTN
Solar/Wind Harmer
0.674
3145796HORNRTN
Solar/Wind Harmer
0.084
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.817
3145683EARLEYS
Solar/Wind Harmer
0.42
3145683EARLEYS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
970831AG2-522 GEN
Solar/Wind Harmer
8.902
3146033SCOT NK
Solar/Wind Harmer
0.823
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316005AA1-067
Solar/Wind Harmer
0.212
3145746EVERETS
Solar/Wind Harmer
0.788
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970181AG2-120 GEN
Solar/Wind Harmer
2.464
316369SG1_INVT
Solar/Wind Harmer
0.007
971443AH1-215 GEN
Solar/Wind Harmer
3.323
3144303KENBRDG
Solar/Wind Harmer
0.158
957861AF2-080 GEN
Solar/Wind Harmer
8.475
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.195
3145573BETHELC
Solar/Wind Harmer
0.195
970683AG2-441 GEN
Solar/Wind Harmer
13.022
970681AG2-440 GEN
Solar/Wind Harmer
10.418
316132AB2-190 GEN1
Solar/Wind Harmer
1.041
946301AF1-294 GEN
Solar/Wind Harmer
3.812
961791AG1-021 GEN
Solar/Wind Harmer
1.855
316118AC1-105 GEN
Solar/Wind Harmer
0.495
315657AE1-056 GEN
Solar/Wind Harmer
6.612
3147173SINAI
Solar/Wind Harmer
0.189
3147243WELCO
Solar/Wind Harmer
0.118
3138283WHITEMARSH
Solar/Wind Harmer
0.039
970285AG2-188 GEN
Solar/Wind Harmer
13.256
971845AH1-439 GEN
Solar/Wind Harmer
7.448
970865AG2-541 GEN
Solar/Wind Harmer
5.665
971167AH1-042 GEN
Solar/Wind Harmer
14.133
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3143873LANEXA
Solar/Wind Harmer
0.09
970189AG2-124 GEN
Solar/Wind Harmer
4.44
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.03
316059AD1-063 C
Solar/Wind Harmer
0.001
316123AC1-075 GEN
Solar/Wind Harmer
0.2
970165AG2-112 GEN
Solar/Wind Harmer
1.187
970163AG2-111 GEN
Solar/Wind Harmer
1.132
316314AB2-024 C
Solar/Wind Harmer
0.001
315976AC1-164 GENA
Solar/Wind Harmer
15.083
316169AC1-164_GENC
Solar/Wind Harmer
13.031
315975AC1-164 GENB
Solar/Wind Harmer
0.446
3141913WHIT STONE
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.043
3141783LANCAST
Solar/Wind Harmer
0.084
3141783LANCAST
Solar/Wind Harmer
0.056
972205AH1-687 GEN
Adder
5.897
962981AG1-147 GEN
Solar/Wind Harmer
5.019
970327AG2-215 GEN
Solar/Wind Harmer
4.3
316312AB1-027
Solar/Wind Harmer
0.228
971447AH1-217 GEN
Solar/Wind Harmer
3.55
3141813NORNECK
Solar/Wind Harmer
0.116
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
23.218
316313AB2-026
Solar/Wind Harmer
0.15
316258AE1-075 C
Solar/Wind Harmer
0.18
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.602
316478AD1-087 GEN
Solar/Wind Harmer
0.805
316486AD2-202 GEN
Solar/Wind Harmer
0.236
316365GEN2_N
Solar/Wind Harmer
0.504
944581AF1-123 GEN
Solar/Wind Harmer
50.561
944601AF1-125 GEN
Solar/Wind Harmer
49.783
315773AC2-141 GEN
Solar/Wind Harmer
8.172
3146456SLIGO L269
Solar/Wind Harmer
0.222
971153AH1-033 GEN
Solar/Wind Harmer
2.565
3144873MCLAUGH
Solar/Wind Harmer
0.006
316320Y1-086
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
0.001
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
0.219
315813AE1-149 C
Solar/Wind Harmer
11.679
3144536CHRHLND
Solar/Wind Harmer
0.033
3145273HOLLAND
Solar/Wind Harmer
0.164
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146376EDENTON
Solar/Wind Harmer
0.216
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3147043LAWRENC
Solar/Wind Harmer
0.129
315614AA2-178 GEN
Solar/Wind Harmer
1.224
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3145893MURPHYS
Solar/Wind Harmer
0.356
3145893MURPHYS
Solar/Wind Harmer
0.213
315839AE2-212 C
Solar/Wind Harmer
0.002
957521AF2-046 GEN
Solar/Wind Harmer
15.803
961681AG1-008 GEN
Solar/Wind Harmer
15.803
971157AH1-035 GEN
Solar/Wind Harmer
2.546
315737AD1-076 GEN
Solar/Wind Harmer
2.725
3146173TUNIS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
3145336SMITFLD
Solar/Wind Harmer
0.084
316463AE2-346 GEN
Solar/Wind Harmer
0.181
316140AB2-099
Solar/Wind Harmer
0.075
962331AG1-082 GEN
Solar/Wind Harmer
2.248
3145796HORNRTN
Solar/Wind Harmer
0.842
3145796HORNRTN
Solar/Wind Harmer
0.211
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
0.305
940641AE2-051 GEN
Solar/Wind Harmer
22.672
939411AE1-173 GEN
Solar/Wind Harmer
114.479
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
20.797
3143526WINTERP
Solar/Wind Harmer
1.35
957481AF2-042 GEN
Solar/Wind Harmer
64.526
3143336POWHATN
Solar/Wind Harmer
4.238
315693AD1-088 GEN
Solar/Wind Harmer
11.177
962491AG1-098 GEN
Solar/Wind Harmer
13.203
316023GEN1_S
Solar/Wind Harmer
0.504
944591AF1-124 GEN
Solar/Wind Harmer
50.741
316294AC1-161 GEN
Solar/Wind Harmer
3.877
316388AE2-253 GEN
Solar/Wind Harmer
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.222
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.1
316336AC2-165 C
Solar/Wind Harmer
0.009
316093AE2-104_GEN
Solar/Wind Harmer
3.708
970661AG2-428 GEN
Solar/Wind Harmer
21.842
316381AD1-082 GEN
Solar/Wind Harmer
0.229
960081AF2-299 GEN
Solar/Wind Harmer
2.106
970659AG2-427 GEN
Solar/Wind Harmer
10.606
3146516WINFALL
Solar/Wind Harmer
0.71
3146516WINFALL
Solar/Wind Harmer
0.219
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.216
971795AH1-408 GEN
Solar/Wind Harmer
14.392
316072AD1-144
Solar/Wind Harmer
0.078
315687AD1-152 GEN
Solar/Wind Harmer
0.007
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
0.599
971163AH1-040 GEN
Solar/Wind Harmer
17.112
316011AB1-132 GEN
Solar/Wind Harmer
3.881
962571AG1-106 GEN
Solar/Wind Harmer
3.037
3145893MURPHYS
Solar/Wind Harmer
0.851
3145893MURPHYS
Solar/Wind Harmer
0.946
3146173TUNIS
Solar/Wind Harmer
0.211
316190AA2-174 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.211
971547AH1-271 GEN
Solar/Wind Harmer
4.504
3145336SMITFLD
Solar/Wind Harmer
0.844
3145796HORNRTN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
0.211
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
316129AC1-054 GEN
Solar/Wind Harmer
0.783
971065AG2-659 GEN
Solar/Wind Harmer
8.875
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.206
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
1.056
315671AE2-027_GEN
Solar/Wind Harmer
13.019
316237AB2-079_GEN
Solar/Wind Harmer
0.002
961611AG1-000B GEN
Solar/Wind Harmer
10.587
315722AD1-056 GEN
Solar/Wind Harmer
1.275
3146293MARTNCO
Solar/Wind Harmer
0.186
971647AH1-324 GEN
Solar/Wind Harmer
8.529
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
316494AC1-189 GEN
Solar/Wind Harmer
0.664
3146233WITAKRS
Solar/Wind Harmer
0.782
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.195
3145493TOT1
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
14.585
970401AG2-262 GEN
Solar/Wind Harmer
1.143
316458AB2-190 GEN2
Solar/Wind Harmer
1.041
316359AB2-059 GEN
Solar/Wind Harmer
0.696
316049AB1-081 GEN
Solar/Wind Harmer
1.109
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.155
3142053HEARTS
Solar/Wind Harmer
0.341
970129AG2-093 GEN
Solar/Wind Harmer
5.511
963171AG1-166 GEN
Solar/Wind Harmer
1.03
971563AH1-280 GEN
Solar/Wind Harmer
2.061
3144293JTRSVLE
Adder
0.615
3138126ROCKLANDING
Solar/Wind Harmer
0.087
3142543TWELFTH
Solar/Wind Harmer
0.018
3146926FARMVIL
Solar/Wind Harmer
0.11
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971317AH1-138 GEN
Solar/Wind Harmer
1.337
970937AG2-583 GEN
Solar/Wind Harmer
10.797
3143096IRON208
Adder
0.735
316159AE1-175 C
Solar/Wind Harmer
0.149
944631AF1-128 GEN
Adder
81.311
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
3142433PROV 92
Solar/Wind Harmer
0.629
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
971777AH1-397 GEN
Solar/Wind Harmer
0.396
3141843SHACKLE
Adder
0.766
3141766HARMONY
Solar/Wind Harmer
0.029
3138133OCRAN
Solar/Wind Harmer
0.086
972003AH1-546 GEN
Solar/Wind Harmer
6.056
3142416OLDCHRC
Solar/Wind Harmer
0.332
3142416OLDCHRC
Solar/Wind Harmer
0.127
962861AG1-135 GEN
Solar/Wind Harmer
4.063
971377AH1-170 GEN
Solar/Wind Harmer
1.327
3147623JAMES R
Solar/Wind Harmer
0.288
3141726DUNNSVL
Solar/Wind Harmer
0.474
3150351NORNECKC2
Adder
1.153
970223AG2-152 GEN
Solar/Wind Harmer
7.902
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.954
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
965281AG1-393 GEN
Solar/Wind Harmer
2.207
3145963POPLR C
Solar/Wind Harmer
0.206
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
1.894
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
0.636
961611AG1-000B GEN
Solar/Wind Harmer
5.383
315724AD1-057 GEN
Solar/Wind Harmer
0.756
964241AG1-285 GEN
Solar/Wind Harmer
13.392
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.335
316327AA2-057 GEN
Solar/Wind Harmer
0.301
315785AD2-033 C
Solar/Wind Harmer
1.614
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970257AG2-171 GEN
Solar/Wind Harmer
6.323
959311AF2-222 GEN
Solar/Wind Harmer
17.507
3146233WITAKRS
Solar/Wind Harmer
0.986
3146233WITAKRS
Solar/Wind Harmer
0.134
315778AD1-151 GEN
Solar/Wind Harmer
15.709
3138543CONSLDL
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.195
3146083TARBORO
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
13.786
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.194
971623AH1-311 GEN
Solar/Wind Harmer
0.388
970129AG2-093 GEN
Solar/Wind Harmer
11.71
963181AG1-167 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3147133PAMPLIN
Solar/Wind Harmer
0.602
971193AH1-056 GEN
Solar/Wind Harmer
11.673
970133AG2-095 GEN
Solar/Wind Harmer
1.824
3144216WINCHST
Adder
0.716
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.068
3150921YORKTN3
Adder
4.712
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.11
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
316382AG1-145 C
Solar/Wind Harmer
0.001
971683AH1-343 GEN
Solar/Wind Harmer
6.321
316283AC2-100 C
Solar/Wind Harmer
0.335
3142946ENON
Solar/Wind Harmer
0.055
3146776BUCKING
Solar/Wind Harmer
0.059
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316156AD2-030 GEN
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
2.658
970293AG2-193 GEN
Solar/Wind Harmer
1.582
3141766HARMONY
Solar/Wind Harmer
1.964
962971AG1-146 GEN
Solar/Wind Harmer
2.151
970009AG2-005 GEN
Solar/Wind Harmer
0.978
3142416OLDCHRC
Solar/Wind Harmer
1.237
316404AE1-155 C
Solar/Wind Harmer
0.028
970221AG2-151 GEN
Solar/Wind Harmer
6.633
3150351NORNECKC2
Adder
1.172
316473AC1-191 GEN
Solar/Wind Harmer
0.383
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
2.393
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:147.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4748.6
MW Contribution:0.91
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.114
315244AE2-183_ST
50/50
5.93
963041AG1-153 GEN
50/50
5.461
3147346CASHSCORNER
Solar/Wind Harmer
0.597
941031AE2-094 GEN
Solar/Wind Harmer
39.425
944011AF1-069 GEN
Solar/Wind Harmer
12.882
970673AG2-436 GEN
Solar/Wind Harmer
44.756
970673AG2-436 GEN
Solar/Wind Harmer
29.837
971967AH1-528 GEN
Solar/Wind Harmer
33.079
970085AG2-068 GEN
Solar/Wind Harmer
10.416
970581AG2-369 GEN
Solar/Wind Harmer
8.958
316233AE1-074 FULL
Solar/Wind Harmer
0.15
971281AH1-106 GEN
Solar/Wind Harmer
2.6
971283AH1-107 GEN
Solar/Wind Harmer
2.6
316315AB2-025 C
Solar/Wind Harmer
0.143
315814AE2-033 C
Solar/Wind Harmer
13.959
315657AE1-056 GEN
Solar/Wind Harmer
5.562
946301AF1-294 GEN
Solar/Wind Harmer
3.175
961791AG1-021 GEN
Solar/Wind Harmer
1.544
3143316POE
Solar/Wind Harmer
0.635
970683AG2-441 GEN
Solar/Wind Harmer
10.688
970681AG2-440 GEN
Solar/Wind Harmer
8.55
3144303KENBRDG
Solar/Wind Harmer
0.128
971443AH1-215 GEN
Solar/Wind Harmer
2.682
970285AG2-188 GEN
Solar/Wind Harmer
12.58
316087AB2-174 GEN
Solar/Wind Harmer
0.005
971845AH1-439 GEN
Solar/Wind Harmer
7.164
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
970831AG2-522 GEN
Solar/Wind Harmer
6.67
3137643SOCKMAN
Solar/Wind Harmer
0.622
315652AC1-086 GEN
Solar/Wind Harmer
16.994
315607AA1-063A GEN
Solar/Wind Harmer
0.314
3146043SEABORD
Solar/Wind Harmer
0.153
957871AF2-081 GEN
Solar/Wind Harmer
7.61
319010AE1-072 C
Solar/Wind Harmer
0.769
3146406KITTY HAWK
Solar/Wind Harmer
0.019
3145796HORNRTN
Solar/Wind Harmer
0.488
3145796HORNRTN
Solar/Wind Harmer
0.061
965291AG1-394 GEN
Solar/Wind Harmer
0.678
313526AB2-022
Solar/Wind Harmer
0.082
316305AF2-043 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
13.946
3151091ELIZAR2
Adder
13.704
316321Z2-027
Solar/Wind Harmer
0.028
3146396TANGLEW
Solar/Wind Harmer
0.419
3145176PASQUOTANK
Solar/Wind Harmer
0.094
315835AF2-110_GEN
Solar/Wind Harmer
1.043
3146486SUNBURY
Solar/Wind Harmer
0.152
3146486SUNBURY
Solar/Wind Harmer
0.152
3152611GOSPORTB
Adder
1.933
3152621GOSPORTC
Adder
1.641
3152601GOSPORTA
Adder
1.513
3145893MURPHYS
Solar/Wind Harmer
0.41
3145893MURPHYS
Solar/Wind Harmer
0.152
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
971133AH1-012 GEN
50/50
10.162
3151731LOISA B
50/50
19.381
3151721LOISA A
50/50
19.281
970533AG2-339 GEN
50/50
19.027
970531AG2-338 GEN
50/50
7.611
315242AE2-183_GT2
50/50
3.43
315241AE2-183_GT1
50/50
3.409
972185AH1-677 GEN
50/50
12.365
3151041BRUNSWICKG3
50/50
2.697
972187AH1-678 GEN
50/50
6.189
966001AG1-469 GEN
Solar/Wind Harmer
0.142
971223AH1-071 GEN
Solar/Wind Harmer
2.468
970933AG2-581 GEN
Solar/Wind Harmer
16.076
3143526WINTERP
Solar/Wind Harmer
0.974
970099AG2-077 GEN
Solar/Wind Harmer
19.819
3144356SAPONY
Solar/Wind Harmer
1.482
971741AH1-377 GEN
Solar/Wind Harmer
17.227
970301AG2-198 GEN
Solar/Wind Harmer
7.308
3147133PAMPLIN
Solar/Wind Harmer
0.161
3147133PAMPLIN
Solar/Wind Harmer
0.129
958211AF2-115 GEN
Solar/Wind Harmer
1.931
963191AG1-168 GEN
Solar/Wind Harmer
0.644
3144293JTRSVLE
Adder
0.512
3144293JTRSVLE
Adder
0.431
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
6.815
971775AH1-396 GEN
Solar/Wind Harmer
0.256
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
7.578
316181AB2-040 GEN
Solar/Wind Harmer
0.229
3146776BUCKING
Solar/Wind Harmer
0.63
3146776BUCKING
Solar/Wind Harmer
0.051
3145593CAROLNA
Solar/Wind Harmer
0.154
3145593CAROLNA
Solar/Wind Harmer
0.154
966811AG1-552 GEN
Solar/Wind Harmer
1.673
3145593CAROLNA
Solar/Wind Harmer
0.192
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.518
3145783HORNRTN
Solar/Wind Harmer
2.725
3145783HORNRTN
Solar/Wind Harmer
2.18
3145783HORNRTN
Solar/Wind Harmer
0.681
3145783HORNRTN
Solar/Wind Harmer
0.273
316185AD1-033 GEN
Solar/Wind Harmer
0.004
3145506HICKORY
Solar/Wind Harmer
0.612
3145506HICKORY
Solar/Wind Harmer
0.367
3145506HICKORY
Solar/Wind Harmer
0.092
316339AD2-160 GEN
Solar/Wind Harmer
0.248
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.085
3137176SLIGO L2192
Solar/Wind Harmer
0.608
3146456SLIGO L269
Solar/Wind Harmer
2.703
3130086AYDLETT
Solar/Wind Harmer
0.61
3145796HORNRTN
Solar/Wind Harmer
0.458
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.146
3146386ELIZ CT
Solar/Wind Harmer
0.152
315742AE1-103 GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.028
3150991CHESPKB
Adder
1.59
3150991CHESPKB
Adder
1.552
962561AG1-105 GEN
Solar/Wind Harmer
7.287
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
1.015
3145893MURPHYS
Solar/Wind Harmer
0.273
3146516WINFALL
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146626S HERTFORD
Solar/Wind Harmer
0.151
3146626S HERTFORD
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146376EDENTON
Solar/Wind Harmer
0.67
3146376EDENTON
Solar/Wind Harmer
0.67
964791AG1-342 GEN
Solar/Wind Harmer
2.892
3146843MT LREL
Solar/Wind Harmer
0.15
3146843MT LREL
Solar/Wind Harmer
0.15
970657AG2-426 GEN
Solar/Wind Harmer
5.253
970657AG2-426 GEN
Solar/Wind Harmer
1.101
316065AD1-022 GEN
Solar/Wind Harmer
6.875
316274AC1-208 GEN
Solar/Wind Harmer
0.769
3145933PARMELE
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.144
3152251N ANNA1
50/50
36.46
3151791S ANNAG2
50/50
1.04
3151781S ANNAS1
50/50
0.534
3151741LOISA C
50/50
1.06
3151751LOISA D
50/50
19.381
970119AG2-088 GEN
50/50
30.855
315243AE2-183_GT3
50/50
3.43
3151051BRUNSWICKS1
50/50
5.597
3151021BRUNSWICKG1
50/50
2.697
971451AH1-221 GEN
50/50
8.191
3147666LOUISA
Solar/Wind Harmer
1.943
316192AB2-158 GEN
Solar/Wind Harmer
2.682
3143226MDLTHAN
Solar/Wind Harmer
0.231
940641AE2-051 GEN
Solar/Wind Harmer
16.781
3143336POWHATN
Solar/Wind Harmer
3.536
970919AG2-571 GEN
Solar/Wind Harmer
6.978
939411AE1-173 GEN
Solar/Wind Harmer
83.474
970087AG2-069 GEN
Solar/Wind Harmer
15.624
316336AC2-165 C
Solar/Wind Harmer
0.007
3143526WINTERP
Solar/Wind Harmer
0.974
957481AF2-042 GEN
Solar/Wind Harmer
49.548
315693AD1-088 GEN
Solar/Wind Harmer
8.718
962491AG1-098 GEN
Solar/Wind Harmer
10.335
970937AG2-583 GEN
Solar/Wind Harmer
10.339
315687AD1-152 GEN
Solar/Wind Harmer
0.005
3146926FARMVIL
Solar/Wind Harmer
0.098
316023GEN1_S
Solar/Wind Harmer
0.365
963171AG1-166 GEN
Solar/Wind Harmer
0.858
971563AH1-280 GEN
Solar/Wind Harmer
1.716
3144293JTRSVLE
Adder
0.512
960081AF2-299 GEN
Solar/Wind Harmer
1.543
970685AG2-442 GEN
Solar/Wind Harmer
11.971
971795AH1-408 GEN
Solar/Wind Harmer
10.682
3147043LAWRENC
Adder
1.448
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.063
971065AG2-659 GEN
Solar/Wind Harmer
6.688
316129AC1-054 GEN
Solar/Wind Harmer
0.589
316011AB1-132 GEN
Solar/Wind Harmer
2.809
962571AG1-106 GEN
Solar/Wind Harmer
2.198
944591AF1-124 GEN
Solar/Wind Harmer
34.895
316190AA2-174 GEN
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
0.153
316311AC2-079 GEN
Solar/Wind Harmer
4.34
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.104
3130156CHOWAN
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
0.151
3145513AHOSKIE
Solar/Wind Harmer
0.314
3145513AHOSKIE
Solar/Wind Harmer
0.15
972205AH1-687 GEN
Adder
6.411
3145683EARLEYS
Solar/Wind Harmer
0.3
3145683EARLEYS
Solar/Wind Harmer
0.15
3145683EARLEYS
Solar/Wind Harmer
0.15
315816AE2-034 GEN
Solar/Wind Harmer
0.644
3130546PLYMOUTH
Solar/Wind Harmer
0.149
3146206CASHIE
Solar/Wind Harmer
0.149
970601AG2-382 GEN
Solar/Wind Harmer
5.575
315732AD1-074 GEN1
Solar/Wind Harmer
0.858
315733AD1-074 GEN2
Solar/Wind Harmer
0.858
315735AD1-075 GEN1
Solar/Wind Harmer
0.429
3146033SCOT NK
Solar/Wind Harmer
0.593
316118AC1-105 GEN
Solar/Wind Harmer
0.382
3147173SINAI
Solar/Wind Harmer
0.145
3147243WELCO
Solar/Wind Harmer
0.091
316319Z2-044 C
Solar/Wind Harmer
0
316005AA1-067
Solar/Wind Harmer
0.153
3145746EVERETS
Solar/Wind Harmer
0.567
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
970181AG2-120 GEN
Solar/Wind Harmer
1.773
957861AF2-080 GEN
Solar/Wind Harmer
6.125
316420AA1-050 GEN
Solar/Wind Harmer
0.005
3152261N ANNA2
50/50
36.457
3151771S ANNAG1
50/50
1.04
3151801S ANNAS2
50/50
0.534
3151761LOISA E
50/50
39.513
972183AH1-676 GEN
50/50
307.587
3151031BRUNSWICKG2
50/50
2.697
3147666LOUISA
Solar/Wind Harmer
1.117
316313AB2-026
Solar/Wind Harmer
0.125
316258AE1-075 C
Solar/Wind Harmer
0.15
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.006
970917AG2-570 GEN
Solar/Wind Harmer
17.445
316478AD1-087 GEN
Solar/Wind Harmer
0.619
316486AD2-202 GEN
Solar/Wind Harmer
0.182
970909AG2-566 GEN
Solar/Wind Harmer
1.827
3146926FARMVIL
Solar/Wind Harmer
0.098
316365GEN2_N
Solar/Wind Harmer
0.365
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.506
971193AH1-056 GEN
Solar/Wind Harmer
9.82
963181AG1-167 GEN
Solar/Wind Harmer
0.644
3144293JTRSVLE
Adder
0.512
3147043LAWRENC
Solar/Wind Harmer
0.096
959311AF2-222 GEN
Solar/Wind Harmer
14.213
970257AG2-171 GEN
Solar/Wind Harmer
5.111
315785AD2-033 C
Solar/Wind Harmer
1.297
964241AG1-285 GEN
Solar/Wind Harmer
10.591
316131AB2-060 GEN
Solar/Wind Harmer
0.498
313506AB2-031 GEN
Solar/Wind Harmer
0.487
3146776BUCKING
Solar/Wind Harmer
0.057
944581AF1-123 GEN
Solar/Wind Harmer
34.771
944601AF1-125 GEN
Solar/Wind Harmer
34.236
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3132273ORANGE
Solar/Wind Harmer
0.031
315773AC2-141 GEN
Solar/Wind Harmer
5.584
3146456SLIGO L269
Solar/Wind Harmer
0.153
971153AH1-033 GEN
Solar/Wind Harmer
1.766
3145796HORNRTN
Solar/Wind Harmer
0.61
3145796HORNRTN
Solar/Wind Harmer
0.152
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
316320Y1-086
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
14.124
3145273HOLLAND
Solar/Wind Harmer
0.114
3144873MCLAUGH
Solar/Wind Harmer
0.004
316435W1029_GEN3
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.254
3145893MURPHYS
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146626S HERTFORD
Solar/Wind Harmer
0.151
957521AF2-046 GEN
Solar/Wind Harmer
11.271
961681AG1-008 GEN
Solar/Wind Harmer
11.271
3146263WOODLND
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146376EDENTON
Solar/Wind Harmer
0.151
316463AE2-346 GEN
Solar/Wind Harmer
0.129
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
1.604
970661AG2-428 GEN
Solar/Wind Harmer
3.178
315614AA2-178 GEN
Solar/Wind Harmer
0.858
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970659AG2-427 GEN
Solar/Wind Harmer
1.584
3156021HOLLOMANSOL
Solar/Wind Harmer
0.678
971157AH1-035 GEN
Solar/Wind Harmer
1.793
3146206CASHIE
Solar/Wind Harmer
0.149
315737AD1-076 GEN
Solar/Wind Harmer
1.921
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.149
315813AE1-149 C
Solar/Wind Harmer
7.948
3144536CHRHLND
Solar/Wind Harmer
0.022
316210AC1-098 GEN
Solar/Wind Harmer
1.371
315724AD1-057 GEN
Solar/Wind Harmer
0.549
3145963POPLR C
Solar/Wind Harmer
0.146
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.188
316327AA2-057 GEN
Solar/Wind Harmer
0.219
3145933PARMELE
Solar/Wind Harmer
0.144
966801AG1-551 GEN
Solar/Wind Harmer
1.673
3146233WITAKRS
Solar/Wind Harmer
0.718
3146233WITAKRS
Solar/Wind Harmer
0.097
3138543CONSLDL
Solar/Wind Harmer
0.094
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
315839AE2-212 C
Solar/Wind Harmer
0.001
316388AE2-253 GEN
Solar/Wind Harmer
0.479
316294AC1-161 GEN
Solar/Wind Harmer
2.649
3146456SLIGO L269
Solar/Wind Harmer
0.153
3145796HORNRTN
Solar/Wind Harmer
0.503
3145796HORNRTN
Solar/Wind Harmer
0.152
315683AE1-153 C
Solar/Wind Harmer
12.128
316246AF1-032 C
Solar/Wind Harmer
0.069
316093AE2-104_GEN
Solar/Wind Harmer
2.556
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
1.895
3145893MURPHYS
Solar/Wind Harmer
0.607
3145893MURPHYS
Solar/Wind Harmer
0.674
3146516WINFALL
Solar/Wind Harmer
0.491
3146516WINFALL
Solar/Wind Harmer
0.152
972003AH1-546 GEN
Solar/Wind Harmer
6.434
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146263WOODLND
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
0.151
970401AG2-262 GEN
Solar/Wind Harmer
0.884
970661AG2-428 GEN
Solar/Wind Harmer
14.943
3145683EARLEYS
Solar/Wind Harmer
0.15
3145663CRESWEL
Solar/Wind Harmer
0.42
971163AH1-040 GEN
Solar/Wind Harmer
11.998
316381AD1-082 GEN
Solar/Wind Harmer
0.156
970659AG2-427 GEN
Solar/Wind Harmer
7.24
3146206CASHIE
Solar/Wind Harmer
0.149
971547AH1-271 GEN
Solar/Wind Harmer
3.186
3145823KELFORD
Solar/Wind Harmer
0.149
316212AC1-099_GEN
Solar/Wind Harmer
0.765
316072AD1-144
Solar/Wind Harmer
0.053
315722AD1-056 GEN
Solar/Wind Harmer
0.927
3145963POPLR C
Solar/Wind Harmer
0.146
316174AB2-169 GEN
Solar/Wind Harmer
0.004
3146293MARTNCO
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
0.569
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
316494AC1-189 GEN
Solar/Wind Harmer
0.48
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3145573BETHELC
Solar/Wind Harmer
0.142
3145573BETHELC
Solar/Wind Harmer
0.142
971445AH1-216 GEN
Solar/Wind Harmer
9.913
971285AH1-108 GEN
Adder
1.055
972265AH1-717 GEN
Adder
10.474
3151201GRAVEL4
Adder
9.819
3151191GRAVEL3
Adder
9.695
3151211GRAVEL5
Adder
9.695
971447AH1-217 GEN
Solar/Wind Harmer
3.983
316369SG1_INVT
Solar/Wind Harmer
0.005
3146073TAR RVR
Solar/Wind Harmer
0.142
3146083TARBORO
Solar/Wind Harmer
0.142
3145336SMITFLD
Solar/Wind Harmer
0.057
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.141
971623AH1-311 GEN
Solar/Wind Harmer
0.283
961601AG1-000A GEN
Solar/Wind Harmer
10.046
3150861SPRUNCD
Adder
0.645
970221AG2-151 GEN
Solar/Wind Harmer
7.325
965281AG1-393 GEN
Solar/Wind Harmer
1.459
3151221GRAVEL6
Adder
9.808
3151171GRAVELC
Adder
1.887
961611AG1-000B GEN
Solar/Wind Harmer
3.53
971683AH1-343 GEN
Solar/Wind Harmer
4.854
316283AC2-100 C
Solar/Wind Harmer
0.252
315778AD1-151 GEN
Solar/Wind Harmer
10.15
970129AG2-093 GEN
Solar/Wind Harmer
7.509
3144216WINCHST
Adder
0.455
970133AG2-095 GEN
Solar/Wind Harmer
1.157
3150921YORKTN3
Adder
2.978
3145493TOT1
Solar/Wind Harmer
0.328
3145453TOT5
Solar/Wind Harmer
0.197
3145603CNETO
Solar/Wind Harmer
0.131
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316263AC1-034 GEN
Solar/Wind Harmer
5.37
961601AG1-000A GEN
Solar/Wind Harmer
2.512
971489AH1-241 GEN
Solar/Wind Harmer
7.325
316240AF1-291 C
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.537
316033AB2-134 GEN
Solar/Wind Harmer
0.008
315697AD1-025 GEN
Solar/Wind Harmer
0.144
944641AF1-129 GEN
Adder
60.502
3146083TARBORO
Solar/Wind Harmer
0.142
3145493TOT1
Solar/Wind Harmer
0.63
3145336SMITFLD
Solar/Wind Harmer
0.565
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.113
316359AB2-059 GEN
Solar/Wind Harmer
0.508
316049AB1-081 GEN
Solar/Wind Harmer
0.809
3142053HEARTS
Solar/Wind Harmer
0.249
3150851SPRUNCC
Adder
0.645
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.465
3147623JAMES R
Solar/Wind Harmer
0.318
3151171GRAVELC
Adder
1.435
315671AE2-027_GEN
Solar/Wind Harmer
8.542
961611AG1-000B GEN
Solar/Wind Harmer
6.943
971647AH1-324 GEN
Solar/Wind Harmer
5.564
971069AG2-661 GEN
Solar/Wind Harmer
2.256
316458AB2-190 GEN2
Solar/Wind Harmer
0.669
970129AG2-093 GEN
Solar/Wind Harmer
3.534
3138126ROCKLANDING
Solar/Wind Harmer
0.055
3142543TWELFTH
Solar/Wind Harmer
0.011
970865AG2-541 GEN
Solar/Wind Harmer
4.353
316132AB2-190 GEN1
Solar/Wind Harmer
0.669
270494AE1-108_GEN
Solar/Wind Harmer
1.404
316123AC1-075 GEN
Solar/Wind Harmer
0.154
970165AG2-112 GEN
Solar/Wind Harmer
0.913
970163AG2-111 GEN
Solar/Wind Harmer
0.871
CPLELTFEXP_CPLE->PJM
CLTF
9.633
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.022
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.582
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.459
MECLTFEXP_MEC->PJM
CLTF
2.598
SIGELTFEXP_SIGE->PJM
CLTF
0.077
NYPJM->LTFIMP_NY
CLTF
2.601
LGEELTFEXP_LGEE->PJM
CLTF
0.913
WECLTFEXP_WEC->PJM
CLTF
0.444
LAGNLTFEXP_LAGN->PJM
CLTF
6.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.668
TVALTFEXP_TVA->PJM
CLTF
3.105

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:172.64 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5559.88
MW Contribution:1.15
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
20.32
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.056
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3152251N ANNA1
50/50
20.321
970119AG2-088 GEN
50/50
35.422
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.99
3150771HOPHCF1
50/50
0.977
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.342
3147666LOUISA
Solar/Wind Harmer
1.028
316192AB2-158 GEN
Solar/Wind Harmer
1.415
940641AE2-051 GEN
Solar/Wind Harmer
19.964
939411AE1-173 GEN
Solar/Wind Harmer
105.426
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.211
315671AE2-027_GEN
Solar/Wind Harmer
15.496
944591AF1-124 GEN
Solar/Wind Harmer
54.408
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
971069AG2-661 GEN
Solar/Wind Harmer
4.274
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3
970659AG2-427 GEN
Solar/Wind Harmer
11.613
971647AH1-324 GEN
Solar/Wind Harmer
10.242
3145336SMITFLD
Solar/Wind Harmer
0.959
316381AD1-082 GEN
Solar/Wind Harmer
0.25
944631AF1-128 GEN
Adder
114.357
961611AG1-000B GEN
Solar/Wind Harmer
12.579
3151171GRAVELC
Adder
2.549
970661AG2-428 GEN
Solar/Wind Harmer
23.801
316388AE2-253 GEN
Solar/Wind Harmer
0.747
3146456SLIGO L269
Solar/Wind Harmer
0.238
3142416OLDCHRC
Solar/Wind Harmer
0.618
3142416OLDCHRC
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.086
3138126ROCKLANDING
Solar/Wind Harmer
0.109
316246AF1-032 C
Solar/Wind Harmer
0.107
316159AE1-175 C
Solar/Wind Harmer
0.205
316093AE2-104_GEN
Solar/Wind Harmer
3.974
971317AH1-138 GEN
Solar/Wind Harmer
1.762
3146516WINFALL
Solar/Wind Harmer
0.754
3146516WINFALL
Solar/Wind Harmer
0.233
3142433PROV 92
Solar/Wind Harmer
0.928
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141843SHACKLE
Adder
1.16
3143336POWHATN
Solar/Wind Harmer
4.034
3130156CHOWAN
Solar/Wind Harmer
0.227
3141766HARMONY
Solar/Wind Harmer
0.045
970919AG2-571 GEN
Solar/Wind Harmer
8.004
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
17.934
3145663CRESWEL
Solar/Wind Harmer
0.622
971163AH1-040 GEN
Solar/Wind Harmer
17.772
3138133OCRAN
Solar/Wind Harmer
0.133
316023GEN1_S
Solar/Wind Harmer
0.489
972197AH1-683 GEN
Adder
4.553
972219AH1-694 GEN
Adder
3.278
316336AC2-165 C
Solar/Wind Harmer
0.008
3146206CASHIE
Solar/Wind Harmer
0.216
971547AH1-271 GEN
Solar/Wind Harmer
4.607
3145893MURPHYS
Solar/Wind Harmer
0.862
3145893MURPHYS
Solar/Wind Harmer
0.958
957481AF2-042 GEN
Solar/Wind Harmer
57.247
3146173TUNIS
Solar/Wind Harmer
0.213
960081AF2-299 GEN
Solar/Wind Harmer
2.041
962861AG1-135 GEN
Solar/Wind Harmer
6.774
3145683EARLEYS
Solar/Wind Harmer
0.211
3146263WOODLND
Solar/Wind Harmer
0.21
315693AD1-088 GEN
Solar/Wind Harmer
10.091
962491AG1-098 GEN
Solar/Wind Harmer
11.959
316011AB1-132 GEN
Solar/Wind Harmer
3.796
962571AG1-106 GEN
Solar/Wind Harmer
2.971
971795AH1-408 GEN
Solar/Wind Harmer
13.893
3145963POPLR C
Solar/Wind Harmer
0.208
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.208
3141726DUNNSVL
Solar/Wind Harmer
0.83
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3147043LAWRENC
Adder
1.868
3145783HORNRTN
Solar/Wind Harmer
0.206
3145796HORNRTN
Solar/Wind Harmer
0.678
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.04
316212AC1-099_GEN
Solar/Wind Harmer
1.038
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.434
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
315722AD1-056 GEN
Solar/Wind Harmer
1.237
316337AD2-073 GEN
Solar/Wind Harmer
0.169
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.651
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970937AG2-583 GEN
Solar/Wind Harmer
11.696
970685AG2-442 GEN
Solar/Wind Harmer
14.234
3146233WITAKRS
Solar/Wind Harmer
0.757
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.19
3145493TOT1
Solar/Wind Harmer
0.845
963171AG1-166 GEN
Solar/Wind Harmer
1.014
971563AH1-280 GEN
Solar/Wind Harmer
2.028
3144293JTRSVLE
Adder
0.605
3146926FARMVIL
Solar/Wind Harmer
0.113
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.672
316049AB1-081 GEN
Solar/Wind Harmer
1.07
3142053HEARTS
Solar/Wind Harmer
0.329
970401AG2-262 GEN
Solar/Wind Harmer
1.071
316303AF2-085
50/50
4.723
971285AH1-108 GEN
50/50
1.99
970603AG2-384 GEN
50/50
5.178
972263AH1-716 GEN
50/50
139.063
316233AE1-074 FULL
Solar/Wind Harmer
0.207
971281AH1-106 GEN
Solar/Wind Harmer
3.58
971283AH1-107 GEN
Solar/Wind Harmer
3.58
3143316POE
Solar/Wind Harmer
0.964
941031AE2-094 GEN
Solar/Wind Harmer
44.68
944011AF1-069 GEN
Solar/Wind Harmer
14.599
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
3151081ELIZAR1
Adder
22.034
3151091ELIZAR2
Adder
21.652
3152611GOSPORTB
Adder
3.059
3152621GOSPORTC
Adder
2.596
3152601GOSPORTA
Adder
2.395
316369SG1_INVT
Solar/Wind Harmer
0.009
971445AH1-216 GEN
Solar/Wind Harmer
16.89
972265AH1-717 GEN
Adder
18.606
3151201GRAVEL4
Adder
17.442
3151191GRAVEL3
Adder
17.221
3151211GRAVEL5
Adder
17.221
970673AG2-436 GEN
Solar/Wind Harmer
50.858
970673AG2-436 GEN
Solar/Wind Harmer
33.905
957871AF2-081 GEN
Solar/Wind Harmer
11.862
316312AB1-027
Solar/Wind Harmer
0.425
319010AE1-072 C
Solar/Wind Harmer
1.197
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
316311AC2-079 GEN
Solar/Wind Harmer
6.823
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.621
316315AB2-025 C
Solar/Wind Harmer
0.191
315976AC1-164 GENA
Solar/Wind Harmer
24.444
316169AC1-164_GENC
Solar/Wind Harmer
21.117
315975AC1-164 GENB
Solar/Wind Harmer
0.723
313526AB2-022
Solar/Wind Harmer
0.128
971967AH1-528 GEN
Solar/Wind Harmer
37.658
315814AE2-033 C
Solar/Wind Harmer
18.587
3146486SUNBURY
Solar/Wind Harmer
0.235
3146486SUNBURY
Solar/Wind Harmer
0.235
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.646
3145176PASQUOTANK
Solar/Wind Harmer
0.145
972189AH1-679 GEN
Adder
3.913
971167AH1-042 GEN
Solar/Wind Harmer
20.686
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3138283WHITEMARSH
Solar/Wind Harmer
0.054
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3143873LANEXA
Solar/Wind Harmer
0.137
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.729
3130156CHOWAN
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
970085AG2-068 GEN
Solar/Wind Harmer
11.956
970581AG2-369 GEN
Solar/Wind Harmer
10.282
3141913WHIT STONE
Solar/Wind Harmer
0.222
315816AE2-034 GEN
Solar/Wind Harmer
0.953
3138133OCRAN
Solar/Wind Harmer
0.066
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.252
315733AD1-074 GEN2
Solar/Wind Harmer
1.252
315735AD1-075 GEN1
Solar/Wind Harmer
0.627
965291AG1-394 GEN
Solar/Wind Harmer
0.966
3150411LDYSMT5
Adder
29.247
3150381LDYSMT2
Adder
27.99
972213AH1-691 GEN
Adder
4.735
972215AH1-692 GEN
Adder
4.735
962981AG1-147 GEN
Solar/Wind Harmer
8.075
3146206CASHIE
Solar/Wind Harmer
0.216
970601AG2-382 GEN
Solar/Wind Harmer
8.061
3145893MURPHYS
Solar/Wind Harmer
0.582
3145893MURPHYS
Solar/Wind Harmer
0.215
970327AG2-215 GEN
Solar/Wind Harmer
7.029
3145513AHOSKIE
Solar/Wind Harmer
0.444
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.212
3145683EARLEYS
Solar/Wind Harmer
0.423
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.431
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.967
3137643SOCKMAN
Solar/Wind Harmer
0.832
3145796HORNRTN
Solar/Wind Harmer
0.658
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
0.815
970831AG2-522 GEN
Solar/Wind Harmer
8.503
316005AA1-067
Solar/Wind Harmer
0.21
3145746EVERETS
Solar/Wind Harmer
0.779
3145746EVERETS
Solar/Wind Harmer
0.196
3151101ELIZAR3
50/50
23.68
3151161SURRY 1
50/50
9.205
3147666LOUISA
Solar/Wind Harmer
0.591
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.876
965281AG1-393 GEN
Solar/Wind Harmer
2.585
315813AE1-149 C
Solar/Wind Harmer
12.873
970133AG2-095 GEN
Solar/Wind Harmer
2.314
944581AF1-123 GEN
Solar/Wind Harmer
54.216
944601AF1-125 GEN
Solar/Wind Harmer
53.381
970129AG2-093 GEN
Solar/Wind Harmer
14.547
315778AD1-151 GEN
Solar/Wind Harmer
19.233
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.54
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
961611AG1-000B GEN
Solar/Wind Harmer
6.396
3151221GRAVEL6
Adder
17.422
3151171GRAVELC
Adder
3.352
970661AG2-428 GEN
Solar/Wind Harmer
5.062
970293AG2-193 GEN
Solar/Wind Harmer
2.548
3142946ENON
Solar/Wind Harmer
0.08
3146456SLIGO L269
Solar/Wind Harmer
0.238
971153AH1-033 GEN
Solar/Wind Harmer
2.749
3142416OLDCHRC
Solar/Wind Harmer
2.305
3144216WINCHST
Adder
0.896
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.233
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316473AC1-191 GEN
Solar/Wind Harmer
0.778
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.143
316258AE1-075 C
Solar/Wind Harmer
0.171
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.429
3146376EDENTON
Solar/Wind Harmer
0.227
3141766HARMONY
Solar/Wind Harmer
3.024
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
4.011
970917AG2-570 GEN
Solar/Wind Harmer
20.009
315614AA2-178 GEN
Solar/Wind Harmer
1.271
971157AH1-035 GEN
Solar/Wind Harmer
2.623
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.489
315737AD1-076 GEN
Solar/Wind Harmer
2.804
3150401LDYSMT4
Adder
29.156
3150371LDYSMT1
Adder
28.172
962971AG1-146 GEN
Solar/Wind Harmer
3.461
3146206CASHIE
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
0.361
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.996
961681AG1-008 GEN
Solar/Wind Harmer
15.996
970009AG2-005 GEN
Solar/Wind Harmer
1.599
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.967
316463AE2-346 GEN
Solar/Wind Harmer
0.183
316140AB2-099
Solar/Wind Harmer
0.076
962331AG1-082 GEN
Solar/Wind Harmer
2.268
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.21
313506AB2-031 GEN
Solar/Wind Harmer
0.649
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145963POPLR C
Solar/Wind Harmer
0.208
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
316478AD1-087 GEN
Solar/Wind Harmer
0.721
316486AD2-202 GEN
Solar/Wind Harmer
0.212
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.822
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.861
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.326
971781AH1-399 GEN
Solar/Wind Harmer
0.26
970909AG2-566 GEN
Solar/Wind Harmer
2.105
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
315724AD1-057 GEN
Solar/Wind Harmer
0.733
316327AA2-057 GEN
Solar/Wind Harmer
0.292
316131AB2-060 GEN
Solar/Wind Harmer
0.604
964241AG1-285 GEN
Solar/Wind Harmer
12.793
315785AD2-033 C
Solar/Wind Harmer
1.556
970257AG2-171 GEN
Solar/Wind Harmer
6.117
959311AF2-222 GEN
Solar/Wind Harmer
16.978
3146233WITAKRS
Solar/Wind Harmer
0.955
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.19
3146083TARBORO
Solar/Wind Harmer
0.19
963181AG1-167 GEN
Solar/Wind Harmer
0.761
3144293JTRSVLE
Adder
0.605
3138543CONSLDL
Solar/Wind Harmer
0.125
3147133PAMPLIN
Solar/Wind Harmer
0.596
971193AH1-056 GEN
Solar/Wind Harmer
11.558
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.113
961601AG1-000A GEN
Solar/Wind Harmer
13.299
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.187
971623AH1-311 GEN
Solar/Wind Harmer
0.374
3141906WESTMOR
Solar/Wind Harmer
0.074
971133AH1-012 GEN
50/50
5.491
944641AF1-129 GEN
50/50
122.767
970533AG2-339 GEN
50/50
21.564
970531AG2-338 GEN
50/50
8.626
3142366NRTHEST
50/50
0.836
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
971223AH1-071 GEN
Solar/Wind Harmer
2.834
3143526WINTERP
Solar/Wind Harmer
1.342
316240AF1-291 C
Solar/Wind Harmer
0.002
3150691DARBY 3
Adder
17.296
3150701DARBY 4
Adder
17.255
3150681DARBY 2
Adder
17.235
3150671DARBY 1
Adder
17.215
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.516
3150991CHESPKB
Adder
2.456
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.27
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.23
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.395
970657AG2-426 GEN
Solar/Wind Harmer
1.76
3142296MT RD221
Adder
0.763
3145506HICKORY
Solar/Wind Harmer
0.957
3145506HICKORY
Solar/Wind Harmer
0.574
3145506HICKORY
Solar/Wind Harmer
0.144
3142946ENON
Solar/Wind Harmer
0.024
316339AD2-160 GEN
Solar/Wind Harmer
0.387
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
3137176SLIGO L2192
Solar/Wind Harmer
0.946
3146456SLIGO L269
Solar/Wind Harmer
4.208
3130086AYDLETT
Solar/Wind Harmer
0.95
316075AC2-137 C
Solar/Wind Harmer
0.065
972185AH1-677 GEN
Adder
13.26
3144356SAPONY
Solar/Wind Harmer
1.973
3146386ELIZ CT
Solar/Wind Harmer
0.235
972187AH1-678 GEN
Adder
6.65
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
18.37
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.008
3146376EDENTON
Solar/Wind Harmer
1.008
957411AF2-035 GEN
Solar/Wind Harmer
9.597
970317AG2-208 GEN
Solar/Wind Harmer
8.892
315673AE1-157 GEN
Solar/Wind Harmer
15.364
3150391LDYSMT3
Adder
29.101
972195AH1-682 GEN
Adder
3.824
316065AD1-022 GEN
Solar/Wind Harmer
9.976
3145893MURPHYS
Solar/Wind Harmer
1.442
3145893MURPHYS
Solar/Wind Harmer
0.388
970099AG2-077 GEN
Solar/Wind Harmer
22.899
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.97
316181AB2-040 GEN
Solar/Wind Harmer
0.305
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.126
316426AA2-053 GEN
Solar/Wind Harmer
0.702
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
966811AG1-552 GEN
Solar/Wind Harmer
2.246
3145593CAROLNA
Solar/Wind Harmer
0.258
3145783HORNRTN
Solar/Wind Harmer
3.66
3145783HORNRTN
Solar/Wind Harmer
2.928
3145783HORNRTN
Solar/Wind Harmer
0.915
3145783HORNRTN
Solar/Wind Harmer
0.366
3145796HORNRTN
Solar/Wind Harmer
0.617
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.143
3150341NORNECKC1
Adder
2.126
971741AH1-377 GEN
Solar/Wind Harmer
19.869
3145933PARMELE
Solar/Wind Harmer
0.399
3145933PARMELE
Solar/Wind Harmer
0.2
316274AC1-208 GEN
Solar/Wind Harmer
1.034
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
970301AG2-198 GEN
Solar/Wind Harmer
8.419
939181AE1-148 GEN
Solar/Wind Harmer
9.29
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.155
971775AH1-396 GEN
Solar/Wind Harmer
0.306
3145493TOT1
Solar/Wind Harmer
0.441
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.282
963191AG1-168 GEN
Solar/Wind Harmer
0.761
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
970181AG2-120 GEN
Solar/Wind Harmer
2.436
957861AF2-080 GEN
Solar/Wind Harmer
8.31
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.006
971443AH1-215 GEN
Solar/Wind Harmer
3.212
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
12.709
970681AG2-440 GEN
Solar/Wind Harmer
10.167
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.19
3145573BETHELC
Solar/Wind Harmer
0.19
946301AF1-294 GEN
Solar/Wind Harmer
3.752
961791AG1-021 GEN
Solar/Wind Harmer
1.825
315657AE1-056 GEN
Solar/Wind Harmer
6.547
316223AC1-118
Solar/Wind Harmer
0.132
970285AG2-188 GEN
Solar/Wind Harmer
14.341
971845AH1-439 GEN
Solar/Wind Harmer
8.154
3144293JTRSVLE
Adder
0.605
3144293JTRSVLE
Adder
0.51
3147133PAMPLIN
Solar/Wind Harmer
0.19
3147133PAMPLIN
Solar/Wind Harmer
0.152
961601AG1-000A GEN
Solar/Wind Harmer
3.325
316263AC1-034 GEN
Solar/Wind Harmer
7.104
962561AG1-105 GEN
Solar/Wind Harmer
8.835
964791AG1-342 GEN
Solar/Wind Harmer
3.505
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.247
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.431
971377AH1-170 GEN
Solar/Wind Harmer
1.683
3147623JAMES R
Solar/Wind Harmer
0.366
972277AH1-723 GEN
Adder
87.353
3151751LOISA D
Adder
8.676
970223AG2-152 GEN
Solar/Wind Harmer
7.908
316045AC1-158 PL2
Solar/Wind Helper
16.699
316006AB2-029 C
Solar/Wind Helper
0.14
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.204
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
5.394
971447AH1-217 GEN
Solar/Wind Harmer
4.654
972193AH1-681 GEN
Adder
3.349
316123AC1-075 GEN
Solar/Wind Harmer
0.195
970165AG2-112 GEN
Solar/Wind Harmer
1.154
970163AG2-111 GEN
Solar/Wind Harmer
1.101
270494AE1-108_GEN
Solar/Wind Harmer
1.672
3147346CASHSCORNER
Solar/Wind Harmer
0.293
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.38
316411AF1-147_GEN1
Solar/Wind Helper
0.79
316415AF1-147_GEN2
Solar/Wind Helper
0.79
3138216PACIFIC
Solar/Wind Helper
0.038
3146776BUCKING
Solar/Wind Harmer
0.064
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.491
970737AG2-469 GEN
Solar/Wind Harmer
7.435
971683AH1-343 GEN
Solar/Wind Harmer
5.965
316283AC2-100 C
Solar/Wind Harmer
0.31
970221AG2-151 GEN
Solar/Wind Harmer
8.416
972255AH1-712 GEN
Adder
74.962
3151761LOISA E
Adder
17.688
972183AH1-676 GEN
Adder
136.298
3141316ARNOLDS
Adder
0.29
316044AC1-158 PL1
Solar/Wind Helper
5.216
316450AC1-158 RIC
Solar/Wind Helper
1.391
3141196NOKESVL
Solar/Wind Helper
1.131
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Harmer
0.661
971489AH1-241 GEN
Solar/Wind Harmer
8.416
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.289
3151731LOISA B
Adder
8.676
3151721LOISA A
Adder
8.631
316447AC1-158 HLD
Solar/Wind Helper
11.481
CPLELTFEXP_CPLE->PJM
CLTF
12.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.163
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.441
MECLTFEXP_MEC->PJM
CLTF
3.751
SIGELTFEXP_SIGE->PJM
CLTF
0.114
NYPJM->LTFIMP_NY
CLTF
3.266
LGEELTFEXP_LGEE->PJM
CLTF
1.371
WECLTFEXP_WEC->PJM
CLTF
0.662
LAGNLTFEXP_LAGN->PJM
CLTF
8.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.505
TVALTFEXP_TVA->PJM
CLTF
4.252

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.66 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5528.27
MW Contribution:1.17
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
5.467
944641AF1-129 GEN
50/50
125.042
3142366NRTHEST
50/50
0.853
970533AG2-339 GEN
50/50
21.877
970531AG2-338 GEN
50/50
8.751
3150781HOPHCF2
50/50
0.996
3150791HOPHCF3
50/50
0.996
3150761HOPPOLC
50/50
0.631
971213AH1-066 GEN
50/50
0.873
3150691DARBY 3
50/50
18.729
3150701DARBY 4
50/50
18.685
971223AH1-071 GEN
Solar/Wind Harmer
2.875
3143526WINTERP
Solar/Wind Harmer
1.363
316240AF1-291 C
Solar/Wind Harmer
0.002
3150681DARBY 2
Adder
17.588
3150671DARBY 1
Adder
17.568
3142296MT RD221
Adder
0.779
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.275
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.56
3150991CHESPKB
Adder
2.499
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.234
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.541
970657AG2-426 GEN
Solar/Wind Harmer
1.79
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.973
3145506HICKORY
Solar/Wind Harmer
0.584
3145506HICKORY
Solar/Wind Harmer
0.146
316339AD2-160 GEN
Solar/Wind Harmer
0.393
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.135
316075AC2-137 C
Solar/Wind Harmer
0.066
3137176SLIGO L2192
Solar/Wind Harmer
0.963
3146456SLIGO L269
Solar/Wind Harmer
4.28
3130086AYDLETT
Solar/Wind Harmer
0.966
972185AH1-677 GEN
Adder
13.452
3144356SAPONY
Solar/Wind Harmer
2.004
3146386ELIZ CT
Solar/Wind Harmer
0.239
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.746
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
966871AG1-558 GEN
Solar/Wind Harmer
0.272
3146626S HERTFORD
Solar/Wind Harmer
0.235
3146626S HERTFORD
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
18.633
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.864
970317AG2-208 GEN
Solar/Wind Harmer
9.139
3146376EDENTON
Solar/Wind Harmer
1.025
3146376EDENTON
Solar/Wind Harmer
1.025
315673AE1-157 GEN
Solar/Wind Harmer
15.809
3150391LDYSMT3
Adder
30.003
972195AH1-682 GEN
Adder
3.943
316065AD1-022 GEN
Solar/Wind Harmer
10.141
3145893MURPHYS
Solar/Wind Harmer
1.466
3145893MURPHYS
Solar/Wind Harmer
0.394
970099AG2-077 GEN
Solar/Wind Harmer
23.222
3146173TUNIS
Solar/Wind Harmer
0.217
3146173TUNIS
Solar/Wind Harmer
0.217
958261AF2-120 GEN
Solar/Wind Harmer
7.118
316181AB2-040 GEN
Solar/Wind Harmer
0.309
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
316426AA2-053 GEN
Solar/Wind Harmer
0.713
3145593CAROLNA
Solar/Wind Harmer
0.21
3145593CAROLNA
Solar/Wind Harmer
0.21
966811AG1-552 GEN
Solar/Wind Harmer
2.282
3145593CAROLNA
Solar/Wind Harmer
0.262
3145783HORNRTN
Solar/Wind Harmer
3.718
3145783HORNRTN
Solar/Wind Harmer
2.974
3145783HORNRTN
Solar/Wind Harmer
0.93
3145783HORNRTN
Solar/Wind Harmer
0.372
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.19
3150341NORNECKC1
Adder
2.172
3145796HORNRTN
Solar/Wind Harmer
0.626
3145933PARMELE
Solar/Wind Harmer
0.406
3145933PARMELE
Solar/Wind Harmer
0.203
3152261N ANNA2
50/50
20.433
3150861SPRUNCD
50/50
1.238
3143096IRON208
50/50
1.099
3143096IRON208
50/50
1.077
3150801HOPHCF4
50/50
1.448
971211AH1-065 GEN
50/50
1.746
3151161SURRY 1
50/50
9.371
3147666LOUISA
Solar/Wind Harmer
0.585
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
9.03
965281AG1-393 GEN
Solar/Wind Harmer
2.631
315813AE1-149 C
Solar/Wind Harmer
13.098
970133AG2-095 GEN
Solar/Wind Harmer
2.358
970129AG2-093 GEN
Solar/Wind Harmer
14.818
944581AF1-123 GEN
Solar/Wind Harmer
55.15
944601AF1-125 GEN
Solar/Wind Harmer
54.301
315778AD1-151 GEN
Solar/Wind Harmer
19.588
3151101ELIZAR3
Adder
22.703
3144536CHRHLND
Solar/Wind Harmer
0.037
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.585
3145336SMITFLD
Solar/Wind Harmer
0.098
961611AG1-000B GEN
Solar/Wind Harmer
6.513
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.737
3151171GRAVELC
Adder
3.413
970293AG2-193 GEN
Solar/Wind Harmer
2.6
3142946ENON
Solar/Wind Harmer
0.081
970661AG2-428 GEN
Solar/Wind Harmer
5.15
3142416OLDCHRC
Solar/Wind Harmer
2.354
3144216WINCHST
Adder
0.913
3146456SLIGO L269
Solar/Wind Harmer
0.242
971153AH1-033 GEN
Solar/Wind Harmer
2.796
3150921YORKTN3
Adder
6.079
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.236
316473AC1-191 GEN
Solar/Wind Harmer
0.795
3146626S HERTFORD
Solar/Wind Harmer
0.235
3145273HOLLAND
Solar/Wind Harmer
0.176
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
3.085
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.23
316156AD2-030 GEN
Solar/Wind Harmer
0.17
3141873WAN 176
Solar/Wind Harmer
4.092
316313AB2-026
Solar/Wind Harmer
0.145
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.472
316303AF2-085
50/50
4.791
971285AH1-108 GEN
50/50
2.026
970603AG2-384 GEN
50/50
5.274
316233AE1-074 FULL
Solar/Wind Harmer
0.21
971281AH1-106 GEN
Solar/Wind Harmer
3.638
971283AH1-107 GEN
Solar/Wind Harmer
3.638
3143316POE
Solar/Wind Harmer
0.98
941031AE2-094 GEN
Solar/Wind Harmer
45.33
944011AF1-069 GEN
Solar/Wind Harmer
14.811
316132AB2-190 GEN1
Solar/Wind Harmer
1.315
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
22.416
3151091ELIZAR2
Adder
22.027
3152251N ANNA1
50/50
20.435
970119AG2-088 GEN
50/50
35.934
3150851SPRUNCC
50/50
1.238
3143096IRON208
50/50
1.099
3152331SURRY 2
50/50
10.173
3150771HOPHCF1
50/50
0.996
3143226MDLTHAN
Solar/Wind Harmer
0.269
3143526WINTERP
Solar/Wind Harmer
1.363
3147666LOUISA
Solar/Wind Harmer
1.017
940641AE2-051 GEN
Solar/Wind Harmer
20.264
939411AE1-173 GEN
Solar/Wind Harmer
107.071
3142543TWELFTH
Solar/Wind Harmer
0.024
316192AB2-158 GEN
Solar/Wind Harmer
1.397
316294AC1-161 GEN
Solar/Wind Harmer
4.284
315671AE2-027_GEN
Solar/Wind Harmer
15.779
970129AG2-093 GEN
Solar/Wind Harmer
6.973
316458AB2-190 GEN2
Solar/Wind Harmer
1.315
944591AF1-124 GEN
Solar/Wind Harmer
55.346
971069AG2-661 GEN
Solar/Wind Harmer
4.353
944631AF1-128 GEN
Adder
116.602
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3.052
971647AH1-324 GEN
Solar/Wind Harmer
10.43
970659AG2-427 GEN
Solar/Wind Harmer
11.815
3145336SMITFLD
Solar/Wind Harmer
0.976
961611AG1-000B GEN
Solar/Wind Harmer
12.808
316381AD1-082 GEN
Solar/Wind Harmer
0.254
3151171GRAVELC
Adder
2.595
970661AG2-428 GEN
Solar/Wind Harmer
24.214
3142416OLDCHRC
Solar/Wind Harmer
0.631
3142416OLDCHRC
Solar/Wind Harmer
0.242
316388AE2-253 GEN
Solar/Wind Harmer
0.76
3138126ROCKLANDING
Solar/Wind Harmer
0.111
3146456SLIGO L269
Solar/Wind Harmer
0.242
316072AD1-144
Solar/Wind Harmer
0.088
316159AE1-175 C
Solar/Wind Harmer
0.209
316246AF1-032 C
Solar/Wind Harmer
0.109
971317AH1-138 GEN
Solar/Wind Harmer
1.796
316093AE2-104_GEN
Solar/Wind Harmer
4.042
3142433PROV 92
Solar/Wind Harmer
0.947
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.766
3146516WINFALL
Solar/Wind Harmer
0.236
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
971777AH1-397 GEN
Solar/Wind Harmer
0.612
3141843SHACKLE
Adder
1.184
3141766HARMONY
Solar/Wind Harmer
0.046
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3130156CHOWAN
Solar/Wind Harmer
0.23
3143336POWHATN
Solar/Wind Harmer
4.084
970919AG2-571 GEN
Solar/Wind Harmer
8.12
970087AG2-069 GEN
Solar/Wind Harmer
18.195
3138133OCRAN
Solar/Wind Harmer
0.136
3145663CRESWEL
Solar/Wind Harmer
0.632
971163AH1-040 GEN
Solar/Wind Harmer
18.07
972197AH1-683 GEN
Adder
4.694
972219AH1-694 GEN
Adder
3.38
316023GEN1_S
Solar/Wind Harmer
0.497
3146206CASHIE
Solar/Wind Harmer
0.219
971547AH1-271 GEN
Solar/Wind Harmer
4.683
316336AC2-165 C
Solar/Wind Harmer
0.009
3145893MURPHYS
Solar/Wind Harmer
0.876
3145893MURPHYS
Solar/Wind Harmer
0.974
957481AF2-042 GEN
Solar/Wind Harmer
58.056
3146173TUNIS
Solar/Wind Harmer
0.217
962861AG1-135 GEN
Solar/Wind Harmer
6.917
960081AF2-299 GEN
Solar/Wind Harmer
2.073
3145683EARLEYS
Solar/Wind Harmer
0.215
3146263WOODLND
Solar/Wind Harmer
0.214
315693AD1-088 GEN
Solar/Wind Harmer
10.231
962491AG1-098 GEN
Solar/Wind Harmer
12.124
316011AB1-132 GEN
Solar/Wind Harmer
3.856
962571AG1-106 GEN
Solar/Wind Harmer
3.018
3141726DUNNSVL
Solar/Wind Harmer
0.847
3145963POPLR C
Solar/Wind Harmer
0.211
971795AH1-408 GEN
Solar/Wind Harmer
14.105
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.211
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3147043LAWRENC
Adder
1.896
3145783HORNRTN
Solar/Wind Harmer
0.209
3150351NORNECKC2
Adder
2.084
3145796HORNRTN
Solar/Wind Harmer
0.689
3145796HORNRTN
Solar/Wind Harmer
0.209
316212AC1-099_GEN
Solar/Wind Harmer
1.054
3152611GOSPORTB
Adder
3.112
3152621GOSPORTC
Adder
2.641
3152601GOSPORTA
Adder
2.437
971445AH1-216 GEN
Solar/Wind Harmer
17.191
972265AH1-717 GEN
Adder
18.943
3151201GRAVEL4
Adder
17.758
3151191GRAVEL3
Adder
17.533
3151211GRAVEL5
Adder
17.533
316312AB1-027
Solar/Wind Harmer
0.435
957871AF2-081 GEN
Solar/Wind Harmer
12.066
970673AG2-436 GEN
Solar/Wind Harmer
51.597
970673AG2-436 GEN
Solar/Wind Harmer
34.398
319010AE1-072 C
Solar/Wind Harmer
1.218
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.166
316311AC2-079 GEN
Solar/Wind Harmer
6.941
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.95
316169AC1-164_GENC
Solar/Wind Harmer
21.555
315975AC1-164 GENB
Solar/Wind Harmer
0.738
315835AF2-110_GEN
Solar/Wind Harmer
1.649
316315AB2-025 C
Solar/Wind Harmer
0.194
313526AB2-022
Solar/Wind Harmer
0.13
972189AH1-679 GEN
Adder
4.009
3146486SUNBURY
Solar/Wind Harmer
0.239
3146486SUNBURY
Solar/Wind Harmer
0.239
971967AH1-528 GEN
Solar/Wind Harmer
38.202
315814AE2-033 C
Solar/Wind Harmer
18.884
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.658
3145176PASQUOTANK
Solar/Wind Harmer
0.148
971167AH1-042 GEN
Solar/Wind Harmer
21.1
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3138283WHITEMARSH
Solar/Wind Harmer
0.055
3143873LANEXA
Solar/Wind Harmer
0.14
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.866
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.23
3130156CHOWAN
Solar/Wind Harmer
0.23
3141873WAN 176
Solar/Wind Harmer
0.046
970085AG2-068 GEN
Solar/Wind Harmer
12.13
970581AG2-369 GEN
Solar/Wind Harmer
10.432
3141913WHIT STONE
Solar/Wind Harmer
0.227
3138133OCRAN
Solar/Wind Harmer
0.068
315816AE2-034 GEN
Solar/Wind Harmer
0.969
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
3150411LDYSMT5
Adder
30.153
3150381LDYSMT2
Adder
28.858
972213AH1-691 GEN
Adder
4.882
972215AH1-692 GEN
Adder
4.882
3130546PLYMOUTH
Solar/Wind Harmer
0.222
315732AD1-074 GEN1
Solar/Wind Harmer
1.273
315733AD1-074 GEN2
Solar/Wind Harmer
1.273
315735AD1-075 GEN1
Solar/Wind Harmer
0.637
965291AG1-394 GEN
Solar/Wind Harmer
0.982
962981AG1-147 GEN
Solar/Wind Harmer
8.243
3146206CASHIE
Solar/Wind Harmer
0.219
970601AG2-382 GEN
Solar/Wind Harmer
8.195
3145893MURPHYS
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
0.219
970327AG2-215 GEN
Solar/Wind Harmer
7.177
3145513AHOSKIE
Solar/Wind Harmer
0.452
3145513AHOSKIE
Solar/Wind Harmer
0.216
3146043SEABORD
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.43
3145683EARLEYS
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.215
315607AA1-063A GEN
Solar/Wind Harmer
0.438
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
23.331
3137643SOCKMAN
Solar/Wind Harmer
0.845
3141813NORNECK
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.668
3145796HORNRTN
Solar/Wind Harmer
0.084
3146033SCOT NK
Solar/Wind Harmer
0.828
970917AG2-570 GEN
Solar/Wind Harmer
20.3
315614AA2-178 GEN
Solar/Wind Harmer
1.293
3150401LDYSMT4
Adder
30.059
3150371LDYSMT1
Adder
29.045
971157AH1-035 GEN
Solar/Wind Harmer
2.667
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315737AD1-076 GEN
Solar/Wind Harmer
2.851
316365GEN2_N
Solar/Wind Harmer
0.497
962971AG1-146 GEN
Solar/Wind Harmer
3.533
3146206CASHIE
Solar/Wind Harmer
0.219
3145893MURPHYS
Solar/Wind Harmer
0.367
3145893MURPHYS
Solar/Wind Harmer
0.219
970009AG2-005 GEN
Solar/Wind Harmer
1.633
957521AF2-046 GEN
Solar/Wind Harmer
16.257
961681AG1-008 GEN
Solar/Wind Harmer
16.257
3146173TUNIS
Solar/Wind Harmer
0.217
3156021HOLLOMANSOL
Solar/Wind Harmer
0.983
316463AE2-346 GEN
Solar/Wind Harmer
0.186
316140AB2-099
Solar/Wind Harmer
0.077
962331AG1-082 GEN
Solar/Wind Harmer
2.305
316404AE1-155 C
Solar/Wind Harmer
0.048
3146263WOODLND
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.659
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3145963POPLR C
Solar/Wind Harmer
0.211
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Harmer
0.731
316486AD2-202 GEN
Solar/Wind Harmer
0.215
3150351NORNECKC2
Adder
2.12
3145796HORNRTN
Solar/Wind Harmer
0.835
3145796HORNRTN
Solar/Wind Harmer
0.209
316210AC1-098 GEN
Solar/Wind Harmer
1.891
3145933PARMELE
Solar/Wind Harmer
0.203
966801AG1-551 GEN
Solar/Wind Harmer
2.363
971781AH1-399 GEN
Solar/Wind Harmer
0.266
970909AG2-566 GEN
Solar/Wind Harmer
2.131
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
315724AD1-057 GEN
Solar/Wind Harmer
0.745
316327AA2-057 GEN
Solar/Wind Harmer
0.297
316131AB2-060 GEN
Solar/Wind Harmer
0.613
964241AG1-285 GEN
Solar/Wind Harmer
12.969
315785AD2-033 C
Solar/Wind Harmer
1.576
970257AG2-171 GEN
Solar/Wind Harmer
6.198
959311AF2-222 GEN
Solar/Wind Harmer
17.202
3146233WITAKRS
Solar/Wind Harmer
0.97
3146233WITAKRS
Solar/Wind Harmer
0.131
3146073TAR RVR
Solar/Wind Harmer
0.193
3146083TARBORO
Solar/Wind Harmer
0.193
3138543CONSLDL
Solar/Wind Harmer
0.127
963181AG1-167 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.613
3147133PAMPLIN
Solar/Wind Harmer
0.603
971193AH1-056 GEN
Solar/Wind Harmer
11.702
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
13.507
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.19
971623AH1-311 GEN
Solar/Wind Harmer
0.38
3141906WESTMOR
Solar/Wind Harmer
0.075
3146776BUCKING
Solar/Wind Harmer
0.065
970737AG2-469 GEN
Solar/Wind Harmer
7.61
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.598
971683AH1-343 GEN
Solar/Wind Harmer
6.05
316283AC2-100 C
Solar/Wind Harmer
0.314
970221AG2-151 GEN
Solar/Wind Harmer
8.483
972255AH1-712 GEN
Adder
76.646
3151761LOISA E
Adder
16.829
3141316ARNOLDS
Adder
0.299
972183AH1-676 GEN
Adder
129.168
3150331BIRCHWDA
Adder
19.249
316044AC1-158 PL1
Solar/Wind Helper
5.254
316450AC1-158 RIC
Solar/Wind Helper
1.401
316170AC1-121 GEN2
Solar/Wind Helper
0.463
3141196NOKESVL
Solar/Wind Helper
1.151
3146293MARTNCO
Solar/Wind Harmer
0.188
316129AC1-054 GEN
Solar/Wind Harmer
0.758
971065AG2-659 GEN
Solar/Wind Harmer
8.56
316337AD2-073 GEN
Solar/Wind Harmer
0.173
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
315722AD1-056 GEN
Solar/Wind Harmer
1.256
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.661
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
0.769
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.193
3145493TOT1
Solar/Wind Harmer
0.859
970685AG2-442 GEN
Solar/Wind Harmer
14.419
970937AG2-583 GEN
Solar/Wind Harmer
11.813
963171AG1-166 GEN
Solar/Wind Harmer
1.027
971563AH1-280 GEN
Solar/Wind Harmer
2.054
3144293JTRSVLE
Adder
0.613
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.152
316359AB2-059 GEN
Solar/Wind Harmer
0.682
316049AB1-081 GEN
Solar/Wind Harmer
1.086
3142053HEARTS
Solar/Wind Harmer
0.334
970401AG2-262 GEN
Solar/Wind Harmer
1.086
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.307
972135AH1-637 GEN
Solar/Wind Harmer
1.466
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971377AH1-170 GEN
Solar/Wind Harmer
1.697
3147623JAMES R
Solar/Wind Harmer
0.369
972277AH1-723 GEN
Adder
89.316
3151751LOISA D
Adder
8.255
970223AG2-152 GEN
Solar/Wind Harmer
8.023
316045AC1-158 PL2
Solar/Wind Helper
16.818
316006AB2-029 C
Solar/Wind Helper
0.152
316254AC1-120 GEN1
Solar/Wind Helper
1.388
971741AH1-377 GEN
Solar/Wind Harmer
20.122
316274AC1-208 GEN
Solar/Wind Harmer
1.051
316468AD1-105 GEN
Solar/Wind Harmer
-0.066
970301AG2-198 GEN
Solar/Wind Harmer
8.524
939181AE1-148 GEN
Solar/Wind Harmer
9.423
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.264
971775AH1-396 GEN
Solar/Wind Harmer
0.31
3145493TOT1
Solar/Wind Harmer
0.448
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.179
958211AF2-115 GEN
Solar/Wind Harmer
2.311
963191AG1-168 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.154
961601AG1-000A GEN
Solar/Wind Harmer
3.377
316263AC1-034 GEN
Solar/Wind Harmer
7.215
962561AG1-105 GEN
Solar/Wind Harmer
8.959
964791AG1-342 GEN
Solar/Wind Harmer
3.555
3146843MT LREL
Solar/Wind Harmer
0.185
3146843MT LREL
Solar/Wind Harmer
0.185
3146776BUCKING
Solar/Wind Harmer
0.723
3146776BUCKING
Solar/Wind Harmer
0.059
316222AC1-221 GEN
Solar/Wind Harmer
0.67
971489AH1-241 GEN
Solar/Wind Harmer
8.483
942751AE2-291 GEN
Solar/Wind Harmer
7.393
315821AE2-092 GEN
Solar/Wind Harmer
0.008
3151731LOISA B
Adder
8.255
3151721LOISA A
Adder
8.212
316447AC1-158 HLD
Solar/Wind Helper
11.564
315651AD1-115 GEN
Solar/Wind Helper
1.026
970831AG2-522 GEN
Solar/Wind Harmer
8.631
316005AA1-067
Solar/Wind Harmer
0.213
3145746EVERETS
Solar/Wind Harmer
0.791
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
970181AG2-120 GEN
Solar/Wind Harmer
2.475
957861AF2-080 GEN
Solar/Wind Harmer
8.442
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.006
971443AH1-215 GEN
Solar/Wind Harmer
3.255
3144303KENBRDG
Solar/Wind Harmer
0.155
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.193
3145573BETHELC
Solar/Wind Harmer
0.193
970683AG2-441 GEN
Solar/Wind Harmer
12.874
970681AG2-440 GEN
Solar/Wind Harmer
10.299
946301AF1-294 GEN
Solar/Wind Harmer
3.8
961791AG1-021 GEN
Solar/Wind Harmer
1.849
315657AE1-056 GEN
Solar/Wind Harmer
6.628
316223AC1-118
Solar/Wind Harmer
0.135
970285AG2-188 GEN
Solar/Wind Harmer
14.487
971845AH1-439 GEN
Solar/Wind Harmer
8.236
316118AC1-105 GEN
Solar/Wind Harmer
0.469
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
972205AH1-687 GEN
Adder
7.261
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
5.471
971447AH1-217 GEN
Solar/Wind Harmer
4.69
972193AH1-681 GEN
Adder
3.425
316123AC1-075 GEN
Solar/Wind Harmer
0.197
970165AG2-112 GEN
Solar/Wind Harmer
1.171
970163AG2-111 GEN
Solar/Wind Harmer
1.117
270494AE1-108_GEN
Solar/Wind Harmer
1.686
3147346CASHSCORNER
Solar/Wind Harmer
0.279
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
2.196
316411AF1-147_GEN1
Solar/Wind Helper
0.801
316415AF1-147_GEN2
Solar/Wind Helper
0.801
3138216PACIFIC
Solar/Wind Helper
0.039
CPLELTFEXP_CPLE->PJM
CLTF
12.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.813
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.369
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.657
MECLTFEXP_MEC->PJM
CLTF
3.808
SIGELTFEXP_SIGE->PJM
CLTF
0.116
NYPJM->LTFIMP_NY
CLTF
3.309
LGEELTFEXP_LGEE->PJM
CLTF
1.392
WECLTFEXP_WEC->PJM
CLTF
0.673
LAGNLTFEXP_LAGN->PJM
CLTF
8.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.899
TVALTFEXP_TVA->PJM
CLTF
4.316

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.73 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5687.33
MW Contribution:2.08
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
109.53
970673AG2-436 GEN
Solar/Wind Harmer
137.75
970673AG2-436 GEN
Solar/Wind Harmer
91.833
941031AE2-094 GEN
Solar/Wind Harmer
118.914
944011AF1-069 GEN
Solar/Wind Harmer
38.854
970085AG2-068 GEN
Solar/Wind Harmer
32.15
970581AG2-369 GEN
Solar/Wind Harmer
27.649
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
316118AC1-105 GEN
Solar/Wind Harmer
0.86
970865AG2-541 GEN
Solar/Wind Harmer
10.119
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.678
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
18.278
970681AG2-440 GEN
Solar/Wind Harmer
14.623
946301AF1-294 GEN
Solar/Wind Harmer
5.338
961791AG1-021 GEN
Solar/Wind Harmer
2.597
315657AE1-056 GEN
Solar/Wind Harmer
9.239
316123AC1-075 GEN
Solar/Wind Harmer
0.351
970165AG2-112 GEN
Solar/Wind Harmer
2.08
970163AG2-111 GEN
Solar/Wind Harmer
1.985
970831AG2-522 GEN
Solar/Wind Harmer
8.286
970285AG2-188 GEN
Solar/Wind Harmer
14.461
971845AH1-439 GEN
Solar/Wind Harmer
7.612
270069AE2-166 C O1
Solar/Wind Harmer
0.005
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
53.965
316478AD1-087 GEN
Solar/Wind Harmer
1.733
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
14.727
971683AH1-343 GEN
Solar/Wind Harmer
11.379
316283AC2-100 C
Solar/Wind Harmer
0.592
316131AB2-060 GEN
Solar/Wind Harmer
0.901
964241AG1-285 GEN
Solar/Wind Harmer
18.92
315785AD2-033 C
Solar/Wind Harmer
2.274
970257AG2-171 GEN
Solar/Wind Harmer
8.9
959311AF2-222 GEN
Solar/Wind Harmer
24.62
963181AG1-167 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.841
971193AH1-056 GEN
Solar/Wind Harmer
16.311
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.058
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
1.012
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.622
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.123
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.544
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
970533AG2-339 GEN
50/50
57.391
970531AG2-338 GEN
50/50
22.956
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
51.542
970099AG2-077 GEN
Solar/Wind Harmer
57.884
971741AH1-377 GEN
Solar/Wind Harmer
38.437
970301AG2-198 GEN
Solar/Wind Harmer
15.165
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.159
962561AG1-105 GEN
Solar/Wind Harmer
15.15
316222AC1-221 GEN
Solar/Wind Harmer
1.267
939181AE1-148 GEN
Solar/Wind Harmer
13.97
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
11.867
971775AH1-396 GEN
Solar/Wind Harmer
0.445
316034AC1-036 C
Solar/Wind Harmer
0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.246
963191AG1-168 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.744
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.052
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.595
316263AC1-034 GEN
Solar/Wind Harmer
4.676
961601AG1-000A GEN
Solar/Wind Harmer
2.136
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
48.225
957481AF2-042 GEN
Solar/Wind Harmer
144.711
315693AD1-088 GEN
Solar/Wind Harmer
23.762
962491AG1-098 GEN
Solar/Wind Harmer
27.839
315687AD1-152 GEN
Solar/Wind Harmer
0.015
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.882
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
20.472
963171AG1-166 GEN
Solar/Wind Harmer
1.443
971563AH1-280 GEN
Solar/Wind Harmer
2.885
3146926FARMVIL
Solar/Wind Harmer
0.151
971065AG2-659 GEN
Solar/Wind Harmer
9.511
316129AC1-054 GEN
Solar/Wind Harmer
0.786
970223AG2-152 GEN
Solar/Wind Harmer
12.908
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.097
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.064
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.115
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.622
270030AE2-140 GEN
Solar/Wind Harmer
14.688
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.442
316049AB1-081 GEN
Solar/Wind Harmer
0.704
3142053HEARTS
Solar/Wind Harmer
0.217
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.78 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5445.28
MW Contribution:2.08
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
109.53
970673AG2-436 GEN
Solar/Wind Harmer
137.75
970673AG2-436 GEN
Solar/Wind Harmer
91.833
970085AG2-068 GEN
Solar/Wind Harmer
32.15
970581AG2-369 GEN
Solar/Wind Harmer
27.649
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
316118AC1-105 GEN
Solar/Wind Harmer
0.86
970865AG2-541 GEN
Solar/Wind Harmer
10.119
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.678
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
18.278
970681AG2-440 GEN
Solar/Wind Harmer
14.623
946301AF1-294 GEN
Solar/Wind Harmer
5.338
961791AG1-021 GEN
Solar/Wind Harmer
2.597
315657AE1-056 GEN
Solar/Wind Harmer
9.239
316123AC1-075 GEN
Solar/Wind Harmer
0.351
970165AG2-112 GEN
Solar/Wind Harmer
2.08
970163AG2-111 GEN
Solar/Wind Harmer
1.985
970831AG2-522 GEN
Solar/Wind Harmer
8.286
970285AG2-188 GEN
Solar/Wind Harmer
14.461
971845AH1-439 GEN
Solar/Wind Harmer
7.612
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
48.225
957481AF2-042 GEN
Solar/Wind Harmer
144.711
315693AD1-088 GEN
Solar/Wind Harmer
23.762
962491AG1-098 GEN
Solar/Wind Harmer
27.839
315687AD1-152 GEN
Solar/Wind Harmer
0.015
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.882
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
20.472
963171AG1-166 GEN
Solar/Wind Harmer
1.443
971563AH1-280 GEN
Solar/Wind Harmer
2.885
3146926FARMVIL
Solar/Wind Harmer
0.151
971065AG2-659 GEN
Solar/Wind Harmer
9.511
316129AC1-054 GEN
Solar/Wind Harmer
0.786
970223AG2-152 GEN
Solar/Wind Harmer
12.908
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.097
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.064
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.115
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.622
270030AE2-140 GEN
Solar/Wind Harmer
14.688
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
51.542
970099AG2-077 GEN
Solar/Wind Harmer
57.884
971741AH1-377 GEN
Solar/Wind Harmer
38.437
970301AG2-198 GEN
Solar/Wind Harmer
15.165
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.159
962561AG1-105 GEN
Solar/Wind Harmer
15.15
316222AC1-221 GEN
Solar/Wind Harmer
1.267
939181AE1-148 GEN
Solar/Wind Harmer
13.97
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
11.867
971775AH1-396 GEN
Solar/Wind Harmer
0.445
316034AC1-036 C
Solar/Wind Harmer
0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.246
963191AG1-168 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.744
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.052
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.595
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
53.965
316478AD1-087 GEN
Solar/Wind Harmer
1.733
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
14.727
971683AH1-343 GEN
Solar/Wind Harmer
11.379
316283AC2-100 C
Solar/Wind Harmer
0.592
316131AB2-060 GEN
Solar/Wind Harmer
0.901
964241AG1-285 GEN
Solar/Wind Harmer
18.92
315785AD2-033 C
Solar/Wind Harmer
2.274
970257AG2-171 GEN
Solar/Wind Harmer
8.9
959311AF2-222 GEN
Solar/Wind Harmer
24.62
963181AG1-167 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.841
971193AH1-056 GEN
Solar/Wind Harmer
16.311
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.058
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
1.012
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.622
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.442
316049AB1-081 GEN
Solar/Wind Harmer
0.704
3142053HEARTS
Solar/Wind Harmer
0.217
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
270336AE1-100 GEN
Solar/Wind Harmer
0.004
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.123
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.544
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
270069AE2-166 C O1
Solar/Wind Harmer
0.005
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
316263AC1-034 GEN
Solar/Wind Harmer
4.676
961601AG1-000A GEN
Solar/Wind Harmer
2.136
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 58572_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 58572_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.04 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6196.95
MW Contribution:2.74
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
170.53
316478AD1-087 GEN
Solar/Wind Harmer
4.831
316486AD2-202 GEN
Solar/Wind Harmer
1.415
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
1.169
960061AF2-297 GEN
Solar/Wind Harmer
19.391
971683AH1-343 GEN
Solar/Wind Harmer
14.982
316283AC2-100 C
Solar/Wind Harmer
3.205
316131AB2-060 GEN
Solar/Wind Harmer
3.471
964241AG1-285 GEN
Solar/Wind Harmer
24.911
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.718
959311AF2-222 GEN
Solar/Wind Harmer
32.481
963181AG1-167 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.811
942461AE2-259 GEN
Solar/Wind Harmer
4.399
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.466
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.086
943811AF1-049 GEN
Solar/Wind Harmer
4.09
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.373
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
63.496
957481AF2-042 GEN
Solar/Wind Harmer
190.536
315693AD1-088 GEN
Solar/Wind Harmer
27.811
962491AG1-098 GEN
Solar/Wind Harmer
36.654
315687AD1-152 GEN
Solar/Wind Harmer
6.022
316003AC1-222 GEN
Solar/Wind Harmer
3.575
970401AG2-262 GEN
Solar/Wind Harmer
2.352
316237AB2-079_GEN
Solar/Wind Harmer
0.978
970685AG2-442 GEN
Solar/Wind Harmer
26.954
963171AG1-166 GEN
Solar/Wind Harmer
3.799
971563AH1-280 GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.523
316129AC1-054 GEN
Solar/Wind Harmer
2.059
970223AG2-152 GEN
Solar/Wind Harmer
18.408
270016AE1-250 BESS
Solar/Wind Harmer
3.042
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.605
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.998
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.086
270030AE2-140 GEN
Solar/Wind Harmer
21.053
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.864
316049AB1-081 GEN
Solar/Wind Harmer
1.492
3142053HEARTS
Solar/Wind Harmer
0.163
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
144.6
970673AG2-436 GEN
Solar/Wind Harmer
152.413
970673AG2-436 GEN
Solar/Wind Harmer
77.171
941031AE2-094 GEN
Solar/Wind Harmer
136.017
944011AF1-069 GEN
Solar/Wind Harmer
42.619
970085AG2-068 GEN
Solar/Wind Harmer
42.331
970581AG2-369 GEN
Solar/Wind Harmer
36.404
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.575
970865AG2-541 GEN
Solar/Wind Harmer
13.323
316239AB2-077_GEN
Solar/Wind Harmer
0.978
316238AB2-078_GEN
Solar/Wind Harmer
0.978
971443AH1-215 GEN
Solar/Wind Harmer
6.159
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.066
970681AG2-440 GEN
Solar/Wind Harmer
19.253
946301AF1-294 GEN
Solar/Wind Harmer
7.788
961791AG1-021 GEN
Solar/Wind Harmer
3.799
315657AE1-056 GEN
Solar/Wind Harmer
11.287
316123AC1-075 GEN
Solar/Wind Harmer
3.111
970165AG2-112 GEN
Solar/Wind Harmer
2.739
970163AG2-111 GEN
Solar/Wind Harmer
2.613
270455AD2-022 GEN
Solar/Wind Harmer
5.008
270457AD2-023 GEN
Solar/Wind Harmer
2.539
970831AG2-522 GEN
Solar/Wind Harmer
10.909
970285AG2-188 GEN
Solar/Wind Harmer
17.971
971845AH1-439 GEN
Solar/Wind Harmer
10.023
270069AE2-166 C O1
Solar/Wind Harmer
2.578
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
970533AG2-339 GEN
50/50
57.391
970531AG2-338 GEN
50/50
22.956
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
67.863
970099AG2-077 GEN
Solar/Wind Harmer
76.214
971741AH1-377 GEN
Solar/Wind Harmer
50.609
970301AG2-198 GEN
Solar/Wind Harmer
19.968
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.699
962561AG1-105 GEN
Solar/Wind Harmer
19.948
316222AC1-221 GEN
Solar/Wind Harmer
3.472
939181AE1-148 GEN
Solar/Wind Harmer
18.394
313527AB2-043 GEN
Solar/Wind Harmer
5.237
970323AG2-213 GEN
Solar/Wind Harmer
15.625
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.748
963191AG1-168 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.78
270013AE1-250 PV
Solar/Wind Harmer
3.042
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.634
316197AC1-042 GEN
Solar/Wind Harmer
1.997
942671AE2-283 GEN
Solar/Wind Harmer
5.376
316263AC1-034 GEN
Solar/Wind Harmer
6.481
961601AG1-000A GEN
Solar/Wind Harmer
5.306
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-5: W72_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: W72_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.43 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6166.56
MW Contribution:2.73
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.095
315244AE2-183_ST
50/50
18.308
3151541CLOVER2
50/50
10.527
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
143.519
970673AG2-436 GEN
Solar/Wind Harmer
151.3
970673AG2-436 GEN
Solar/Wind Harmer
76.608
941031AE2-094 GEN
Solar/Wind Harmer
135.024
944011AF1-069 GEN
Solar/Wind Harmer
42.308
970085AG2-068 GEN
Solar/Wind Harmer
42.031
970581AG2-369 GEN
Solar/Wind Harmer
36.147
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.567
970865AG2-541 GEN
Solar/Wind Harmer
13.271
316239AB2-077_GEN
Solar/Wind Harmer
0.98
316238AB2-078_GEN
Solar/Wind Harmer
0.98
971443AH1-215 GEN
Solar/Wind Harmer
6.158
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.044
3151031BRUNSWICKG2
50/50
8.442
970413AG2-270 GEN
50/50
46.159
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.912
970917AG2-570 GEN
Solar/Wind Harmer
169.32
316478AD1-087 GEN
Solar/Wind Harmer
4.801
316486AD2-202 GEN
Solar/Wind Harmer
1.406
970909AG2-566 GEN
Solar/Wind Harmer
3.769
3151051BRUNSWICKS1
50/50
17.522
3151021BRUNSWICKG1
50/50
8.442
971451AH1-221 GEN
50/50
25.642
315243AE2-183_GT3
50/50
10.589
3151531CLOVER1
50/50
10.578
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.912
971629AH1-314 GEN
50/50
18.997
3151561HALLBR1
50/50
0.403
970919AG2-571 GEN
Solar/Wind Harmer
21.433
970087AG2-069 GEN
Solar/Wind Harmer
63.047
957481AF2-042 GEN
Solar/Wind Harmer
189.269
315693AD1-088 GEN
Solar/Wind Harmer
27.634
962491AG1-098 GEN
Solar/Wind Harmer
36.422
315687AD1-152 GEN
Solar/Wind Harmer
5.988
316003AC1-222 GEN
Solar/Wind Harmer
3.561
970401AG2-262 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.98
970685AG2-442 GEN
Solar/Wind Harmer
26.929
963171AG1-166 GEN
Solar/Wind Harmer
3.793
971563AH1-280 GEN
Solar/Wind Harmer
3.793
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.621
316129AC1-054 GEN
Solar/Wind Harmer
2.079
970223AG2-152 GEN
Solar/Wind Harmer
18.347
270016AE1-250 BESS
Solar/Wind Harmer
3.032
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.602
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.978
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.064
270030AE2-140 GEN
Solar/Wind Harmer
20.984
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.909
316049AB1-081 GEN
Solar/Wind Harmer
1.528
3142053HEARTS
Solar/Wind Harmer
0.166
316294AC1-161 GEN
Solar/Wind Helper
8.246
316375AC2-012 GEN
Solar/Wind Helper
1.074
3145336SMITFLD
Solar/Wind Helper
1.568
316388AE2-253 GEN
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.38
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.426
316159AE1-175 C
Solar/Wind Helper
0.559
316381AD1-082 GEN
Solar/Wind Helper
1.857
316458AB2-190 GEN2
Solar/Wind Helper
2.041
3141766HARMONY
Solar/Wind Helper
0.068
3138133OCRAN
Solar/Wind Helper
0.204
3142433PROV 92
Solar/Wind Helper
1.345
3142543TWELFTH
Solar/Wind Helper
0.031
964211AG1-282 GEN
Solar/Wind Helper
0.434
3141726DUNNSVL
Solar/Wind Helper
1.289
3146516WINFALL
Solar/Wind Helper
1.017
3146516WINFALL
Solar/Wind Helper
0.314
316337AD2-073 GEN
Solar/Wind Helper
0.473
3142416OLDCHRC
Solar/Wind Helper
0.799
3142416OLDCHRC
Solar/Wind Helper
0.306
3143526WINTERP
Solar/Wind Helper
1.573
970681AG2-440 GEN
Solar/Wind Harmer
19.235
946301AF1-294 GEN
Solar/Wind Harmer
7.775
961791AG1-021 GEN
Solar/Wind Harmer
3.793
315657AE1-056 GEN
Solar/Wind Harmer
11.263
316123AC1-075 GEN
Solar/Wind Harmer
3.099
970165AG2-112 GEN
Solar/Wind Harmer
2.728
970163AG2-111 GEN
Solar/Wind Harmer
2.603
270455AD2-022 GEN
Solar/Wind Harmer
4.991
270457AD2-023 GEN
Solar/Wind Harmer
2.531
970831AG2-522 GEN
Solar/Wind Harmer
11.041
970285AG2-188 GEN
Solar/Wind Harmer
17.881
971845AH1-439 GEN
Solar/Wind Harmer
9.974
270069AE2-166 C O1
Solar/Wind Harmer
2.569
319010AE1-072 C
Solar/Wind Helper
4.32
3143316POE
Solar/Wind Helper
1.486
316305AF2-043 C
Solar/Wind Helper
0.5
316369SG1_INVT
Solar/Wind Helper
1.758
957831AF2-077 GEN
Solar/Wind Helper
0.492
316132AB2-190 GEN1
Solar/Wind Helper
2.041
316349AD2-085 GEN
Solar/Wind Helper
1.61
313526AB2-022
Solar/Wind Helper
0.535
957601AF2-054 GEN
Solar/Wind Helper
0.462
3141873WAN 176
Solar/Wind Helper
0.069
315662AE1-191 GEN
Solar/Wind Helper
1.844
315666AE1-190 GEN
Solar/Wind Helper
0.461
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316059AD1-063 C
Solar/Wind Helper
0.344
3141913WHIT STONE
Solar/Wind Helper
0.341
3138133OCRAN
Solar/Wind Helper
0.102
3143873LANEXA
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.135
316321Z2-027
Solar/Wind Helper
0.515
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.321
316312AB1-027
Solar/Wind Helper
0.585
316223AC1-118
Solar/Wind Helper
0.461
316233AE1-074 FULL
Solar/Wind Helper
0.462
316248AF1-058 C
Solar/Wind Harmer
1.164
960061AF2-297 GEN
Solar/Wind Harmer
19.314
971683AH1-343 GEN
Solar/Wind Harmer
14.923
316283AC2-100 C
Solar/Wind Harmer
3.192
316131AB2-060 GEN
Solar/Wind Harmer
3.475
964241AG1-285 GEN
Solar/Wind Harmer
24.93
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.716
959311AF2-222 GEN
Solar/Wind Harmer
32.468
963181AG1-167 GEN
Solar/Wind Harmer
2.845
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.772
942461AE2-259 GEN
Solar/Wind Harmer
4.384
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.461
270197AD1-017 GEN1
Solar/Wind Harmer
1.796
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.064
943811AF1-049 GEN
Solar/Wind Harmer
4.077
270336AE1-100 GEN
Solar/Wind Harmer
1.664
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.512
3138543CONSLDL
Solar/Wind Harmer
-0.008
315773AC2-141 GEN
Solar/Wind Helper
9.706
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
3146456SLIGO L269
Solar/Wind Helper
0.38
316382AG1-145 C
Solar/Wind Helper
0.496
315839AE2-212 C
Solar/Wind Helper
0.483
316320Y1-086
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.52
316280AD1-041 GEN
Solar/Wind Helper
1.152
3142946ENON
Solar/Wind Helper
0.111
316484AD2-074 GEN
Solar/Wind Helper
0.641
316404AE1-155 C
Solar/Wind Helper
2.769
316435W1029_GEN3
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.121
3151041BRUNSWICKG3
50/50
8.442
972187AH1-678 GEN
50/50
19.374
315242AE2-183_GT2
50/50
10.589
315241AE2-183_GT1
50/50
10.524
972185AH1-677 GEN
50/50
38.176
970533AG2-339 GEN
50/50
56.972
970531AG2-338 GEN
50/50
22.789
3152661PLYWOOD A
50/50
0.749
970535AG2-341 GEN
50/50
5.154
3144293JTRSVLE
50/50
0.912
3144293JTRSVLE
50/50
0.768
970933AG2-581 GEN
Solar/Wind Harmer
67.369
970099AG2-077 GEN
Solar/Wind Harmer
75.708
971741AH1-377 GEN
Solar/Wind Harmer
50.305
970301AG2-198 GEN
Solar/Wind Harmer
19.85
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.683
962561AG1-105 GEN
Solar/Wind Harmer
19.916
316222AC1-221 GEN
Solar/Wind Harmer
3.458
939181AE1-148 GEN
Solar/Wind Harmer
18.413
313527AB2-043 GEN
Solar/Wind Harmer
5.244
970323AG2-213 GEN
Solar/Wind Harmer
15.621
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.741
963191AG1-168 GEN
Solar/Wind Harmer
2.845
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.715
270013AE1-250 PV
Solar/Wind Harmer
3.032
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.625
316197AC1-042 GEN
Solar/Wind Harmer
1.99
942671AE2-283 GEN
Solar/Wind Harmer
5.357
316263AC1-034 GEN
Solar/Wind Harmer
6.638
961601AG1-000A GEN
Solar/Wind Harmer
5.443
316036AC1-147 C
Solar/Wind Helper
0.624
3142956BIRDNECK
Solar/Wind Helper
0.274
316316AC1-027 C
Solar/Wind Helper
0.642
316185AD1-033 GEN
Solar/Wind Helper
1.905
3145506HICKORY
Solar/Wind Helper
1.596
3145506HICKORY
Solar/Wind Helper
0.958
3145506HICKORY
Solar/Wind Helper
0.239
316236AE1-162_GEN
Solar/Wind Helper
0.527
316339AD2-160 GEN
Solar/Wind Helper
1.48
316018AA1-139 ULT2
Solar/Wind Helper
1.659
316017AA1-139 ULT1
Solar/Wind Helper
1.763
3137176SLIGO L2192
Solar/Wind Helper
1.516
3130086AYDLETT
Solar/Wind Helper
1.505
316033AB2-134 GEN
Solar/Wind Helper
1.257
315697AD1-025 GEN
Solar/Wind Helper
4.177
3146386ELIZ CT
Solar/Wind Helper
0.351
316240AF1-291 C
Solar/Wind Helper
0.468
3142946ENON
Solar/Wind Helper
0.033
316487AF1-042 GEN
Solar/Wind Helper
0.335
316075AC2-137 C
Solar/Wind Helper
0.492
316077AC2-138 C
Solar/Wind Helper
0.302
316431W1029_GEN1
Solar/Wind Helper
1.297
316433W1029_GEN2
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.573
316315AB2-025 C
Solar/Wind Helper
0.44
315611Z1-036_GEN2
Solar/Wind Helper
1.494
3130156CHOWAN
Solar/Wind Helper
0.24
3130156CHOWAN
Solar/Wind Helper
0.24
3146626S HERTFORD
Solar/Wind Helper
0.296
316473AC1-191 GEN
Solar/Wind Helper
1.785
3145273HOLLAND
Solar/Wind Helper
0.198
966881AG1-559 GEN
Solar/Wind Helper
0.346
3146376EDENTON
Solar/Wind Helper
0.239
3143226MDLTHAN
Solar/Wind Helper
0.298
315800Z1-036_GEN1
Solar/Wind Helper
1.494
3130156CHOWAN
Solar/Wind Helper
0.24
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
966871AG1-558 GEN
Solar/Wind Helper
0.394
3144356SAPONY
Solar/Wind Helper
0.518
316468AD1-105 GEN
Solar/Wind Helper
1.373
315742AE1-103 GEN
Solar/Wind Helper
0.362
CPLELTFEXP_CPLE->PJM
CLTF
20.587
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.354
MECLTFEXP_MEC->PJM
CLTF
7.751
SIGELTFEXP_SIGE->PJM
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
2.481
LGEELTFEXP_LGEE->PJM
CLTF
2.822
WECLTFEXP_WEC->PJM
CLTF
1.476
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
LAGNLTFEXP_LAGN->PJM
CLTF
15.349
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.145
TVALTFEXP_TVA->PJM
CLTF
7.657

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: XT585_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT585_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.16 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5703.66
MW Contribution:2.74
Bus #Bus NameTypeMW Contribution
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
63.496
957481AF2-042 GEN
Solar/Wind Harmer
190.536
315693AD1-088 GEN
Solar/Wind Harmer
27.811
962491AG1-098 GEN
Solar/Wind Harmer
36.654
315687AD1-152 GEN
Solar/Wind Harmer
6.022
316003AC1-222 GEN
Solar/Wind Harmer
3.575
970401AG2-262 GEN
Solar/Wind Harmer
2.352
316237AB2-079_GEN
Solar/Wind Harmer
0.978
970685AG2-442 GEN
Solar/Wind Harmer
26.954
963171AG1-166 GEN
Solar/Wind Harmer
3.799
971563AH1-280 GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.523
316129AC1-054 GEN
Solar/Wind Harmer
2.059
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
144.6
970085AG2-068 GEN
Solar/Wind Harmer
42.331
970581AG2-369 GEN
Solar/Wind Harmer
36.404
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.575
970865AG2-541 GEN
Solar/Wind Harmer
13.323
316239AB2-077_GEN
Solar/Wind Harmer
0.978
316238AB2-078_GEN
Solar/Wind Harmer
0.978
971443AH1-215 GEN
Solar/Wind Harmer
6.159
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.066
970681AG2-440 GEN
Solar/Wind Harmer
19.253
946301AF1-294 GEN
Solar/Wind Harmer
7.788
961791AG1-021 GEN
Solar/Wind Harmer
3.799
315657AE1-056 GEN
Solar/Wind Harmer
11.287
316123AC1-075 GEN
Solar/Wind Harmer
3.111
970165AG2-112 GEN
Solar/Wind Harmer
2.739
970163AG2-111 GEN
Solar/Wind Harmer
2.613
270455AD2-022 GEN
Solar/Wind Harmer
5.008
270457AD2-023 GEN
Solar/Wind Harmer
2.539
970831AG2-522 GEN
Solar/Wind Harmer
10.909
970285AG2-188 GEN
Solar/Wind Harmer
17.971
971845AH1-439 GEN
Solar/Wind Harmer
10.023
270069AE2-166 C O1
Solar/Wind Harmer
2.578
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
67.863
970099AG2-077 GEN
Solar/Wind Harmer
76.214
971741AH1-377 GEN
Solar/Wind Harmer
50.609
970301AG2-198 GEN
Solar/Wind Harmer
19.968
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.699
962561AG1-105 GEN
Solar/Wind Harmer
19.948
316222AC1-221 GEN
Solar/Wind Harmer
3.472
939181AE1-148 GEN
Solar/Wind Harmer
18.394
313527AB2-043 GEN
Solar/Wind Harmer
5.237
970323AG2-213 GEN
Solar/Wind Harmer
15.625
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.748
963191AG1-168 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.78
270013AE1-250 PV
Solar/Wind Harmer
3.042
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.634
316197AC1-042 GEN
Solar/Wind Harmer
1.997
942671AE2-283 GEN
Solar/Wind Harmer
5.376
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
170.53
316478AD1-087 GEN
Solar/Wind Harmer
4.831
316486AD2-202 GEN
Solar/Wind Harmer
1.415
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
1.169
960061AF2-297 GEN
Solar/Wind Harmer
19.391
971683AH1-343 GEN
Solar/Wind Harmer
14.982
316283AC2-100 C
Solar/Wind Harmer
3.205
316131AB2-060 GEN
Solar/Wind Harmer
3.471
964241AG1-285 GEN
Solar/Wind Harmer
24.911
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.718
959311AF2-222 GEN
Solar/Wind Harmer
32.481
963181AG1-167 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.811
942461AE2-259 GEN
Solar/Wind Harmer
4.399
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.466
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.086
943811AF1-049 GEN
Solar/Wind Harmer
4.09
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
970223AG2-152 GEN
Solar/Wind Harmer
18.408
270016AE1-250 BESS
Solar/Wind Harmer
3.042
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.605
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.998
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.086
270030AE2-140 GEN
Solar/Wind Harmer
21.053
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.864
316049AB1-081 GEN
Solar/Wind Harmer
1.492
3142053HEARTS
Solar/Wind Harmer
0.163
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.373
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
316263AC1-034 GEN
Solar/Wind Harmer
6.481
961601AG1-000A GEN
Solar/Wind Harmer
5.306
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 54472_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 54472_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.74 %
Rating:2858.0 MVA
Rating Type:C
MVA to Mitigate:3193.49
MW Contribution:1.93
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
7.93
963041AG1-153 GEN
50/50
8.365
315244AE2-183_ST
50/50
6.698
3151611KERR 4
50/50
0.44
3151621KERR 5
50/50
0.44
3151631KERR 6
50/50
0.44
3151641KERR 7
50/50
0.44
971967AH1-528 GEN
Solar/Wind Harmer
110.812
970085AG2-068 GEN
Solar/Wind Harmer
20.738
970581AG2-369 GEN
Solar/Wind Harmer
17.835
3147173SINAI
Solar/Wind Harmer
-0.028
3147243WELCO
Solar/Wind Harmer
-0.017
316118AC1-105 GEN
Solar/Wind Harmer
1.848
316239AB2-077_GEN
Solar/Wind Harmer
0.722
316238AB2-078_GEN
Solar/Wind Harmer
0.722
971443AH1-215 GEN
Solar/Wind Harmer
4.604
3144303KENBRDG
Solar/Wind Harmer
-0.019
970865AG2-541 GEN
Solar/Wind Harmer
9.435
970683AG2-441 GEN
Solar/Wind Harmer
18.098
970413AG2-270 GEN
50/50
34.77
3151031BRUNSWICKG2
50/50
4.131
3151591KERR 2
50/50
0.44
3144293JTRSVLE
50/50
0.691
316478AD1-087 GEN
Solar/Wind Harmer
3.615
316486AD2-202 GEN
Solar/Wind Harmer
1.059
970917AG2-570 GEN
Solar/Wind Harmer
83.468
970909AG2-566 GEN
Solar/Wind Harmer
2.9
316248AF1-058 C
Solar/Wind Harmer
0.833
960061AF2-297 GEN
Solar/Wind Harmer
13.826
971683AH1-343 GEN
Solar/Wind Harmer
10.636
316131AB2-060 GEN
Solar/Wind Harmer
2.567
964241AG1-285 GEN
Solar/Wind Harmer
18.486
315785AD2-033 C
Solar/Wind Harmer
5.315
970257AG2-171 GEN
Solar/Wind Harmer
8.764
959311AF2-222 GEN
Solar/Wind Harmer
24.33
963181AG1-167 GEN
Solar/Wind Harmer
2.154
3147133PAMPLIN
Solar/Wind Harmer
-0.071
971193AH1-056 GEN
Solar/Wind Harmer
14.275
942461AE2-259 GEN
Solar/Wind Harmer
3.375
3146926FARMVIL
Solar/Wind Harmer
-0.013
316283AC2-100 C
Solar/Wind Harmer
2.04
3146776BUCKING
Solar/Wind Harmer
-0.005
315773AC2-141 GEN
Solar/Wind Helper
5.476
315839AE2-212 C
Solar/Wind Helper
0.317
3151531CLOVER1
50/50
7.968
3151051BRUNSWICKS1
50/50
8.574
3151021BRUNSWICKG1
50/50
4.131
971451AH1-221 GEN
50/50
12.548
315243AE2-183_GT3
50/50
3.874
3151601KERR 3
50/50
0.44
3151581KERR 1
50/50
0.157
3144293JTRSVLE
50/50
0.691
971629AH1-314 GEN
50/50
11.594
957481AF2-042 GEN
Solar/Wind Harmer
144.035
315693AD1-088 GEN
Solar/Wind Harmer
21.036
962491AG1-098 GEN
Solar/Wind Harmer
27.737
315687AD1-152 GEN
Solar/Wind Harmer
4.411
970919AG2-571 GEN
Solar/Wind Harmer
10.566
970087AG2-069 GEN
Solar/Wind Harmer
31.107
970401AG2-262 GEN
Solar/Wind Harmer
1.7
316003AC1-222 GEN
Solar/Wind Harmer
2.544
316237AB2-079_GEN
Solar/Wind Harmer
0.722
970685AG2-442 GEN
Solar/Wind Harmer
20.27
963171AG1-166 GEN
Solar/Wind Harmer
2.872
971563AH1-280 GEN
Solar/Wind Harmer
2.872
3146926FARMVIL
Solar/Wind Harmer
-0.013
971065AG2-659 GEN
Solar/Wind Harmer
9.218
316129AC1-054 GEN
Solar/Wind Harmer
1.52
316322AB2-045
Solar/Wind Harmer
0.488
3146776BUCKING
Solar/Wind Harmer
-0.006
970223AG2-152 GEN
Solar/Wind Harmer
11.343
316294AC1-161 GEN
Solar/Wind Helper
4.653
3151041BRUNSWICKG3
50/50
4.131
972187AH1-678 GEN
50/50
9.481
3152661PLYWOOD A
50/50
0.538
315242AE2-183_GT2
50/50
3.874
315241AE2-183_GT1
50/50
3.85
972185AH1-677 GEN
50/50
13.967
970535AG2-341 GEN
50/50
3.778
3144293JTRSVLE
50/50
0.691
3144293JTRSVLE
50/50
0.582
970933AG2-581 GEN
Solar/Wind Harmer
51.852
970099AG2-077 GEN
Solar/Wind Harmer
57.614
971741AH1-377 GEN
Solar/Wind Harmer
38.586
970301AG2-198 GEN
Solar/Wind Harmer
15.274
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.564
962561AG1-105 GEN
Solar/Wind Harmer
14.462
939181AE1-148 GEN
Solar/Wind Harmer
13.444
313527AB2-043 GEN
Solar/Wind Harmer
3.87
970323AG2-213 GEN
Solar/Wind Harmer
11.685
971775AH1-396 GEN
Solar/Wind Harmer
1.664
316034AC1-036 C
Solar/Wind Harmer
0.433
958211AF2-115 GEN
Solar/Wind Harmer
3.59
963191AG1-168 GEN
Solar/Wind Harmer
2.154
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
316222AC1-221 GEN
Solar/Wind Harmer
2.218
942751AE2-291 GEN
Solar/Wind Harmer
11.754
3146776BUCKING
Solar/Wind Harmer
-0.058
3146776BUCKING
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Helper
0.299
970681AG2-440 GEN
Solar/Wind Harmer
14.478
946301AF1-294 GEN
Solar/Wind Harmer
5.887
961791AG1-021 GEN
Solar/Wind Harmer
2.872
315657AE1-056 GEN
Solar/Wind Harmer
8.565
316123AC1-075 GEN
Solar/Wind Harmer
2.19
970165AG2-112 GEN
Solar/Wind Harmer
1.928
970163AG2-111 GEN
Solar/Wind Harmer
1.839
970673AG2-436 GEN
Solar/Wind Harmer
40.956
970673AG2-436 GEN
Solar/Wind Harmer
20.737
270455AD2-022 GEN
Solar/Wind Harmer
3.036
270457AD2-023 GEN
Solar/Wind Harmer
1.539
970285AG2-188 GEN
Solar/Wind Harmer
14.324
970831AG2-522 GEN
Solar/Wind Harmer
8.077
971845AH1-439 GEN
Solar/Wind Harmer
8.053
3143316POE
Solar/Wind Helper
1.004
CPLELTFEXP_CPLE->PJM
CLTF
11.786
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.401
MECLTFEXP_MEC->PJM
CLTF
4.601
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
1.417
LGEELTFEXP_LGEE->PJM
CLTF
1.692
WECLTFEXP_WEC->PJM
CLTF
0.884
LAGNLTFEXP_LAGN->PJM
CLTF
8.928
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.434
TVALTFEXP_TVA->PJM
CLTF
4.461

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.06 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5008.65
MW Contribution:1.87
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.25 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5458.06
MW Contribution:2.46
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.79 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5435.07
MW Contribution:2.46
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.19 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5355.19
MW Contribution:2.43
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.87 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3044.37
MW Contribution:1.22
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
4.325
3151051BRUNSWICKS1
50/50
7.027
3151021BRUNSWICKG1
50/50
3.386
971451AH1-221 GEN
50/50
10.283
3151531CLOVER1
50/50
4.285
316294AC1-161 GEN
Solar/Wind Harmer
21.297
940641AE2-051 GEN
Solar/Wind Harmer
36.033
970919AG2-571 GEN
Solar/Wind Harmer
8.694
970087AG2-069 GEN
Solar/Wind Harmer
25.61
944591AF1-124 GEN
Solar/Wind Harmer
110.068
957481AF2-042 GEN
Solar/Wind Harmer
75.055
939411AE1-173 GEN
Solar/Wind Harmer
119.429
315693AD1-088 GEN
Solar/Wind Harmer
11.114
962491AG1-098 GEN
Solar/Wind Harmer
14.661
315687AD1-152 GEN
Solar/Wind Harmer
2.497
316375AC2-012 GEN
Solar/Wind Harmer
7.148
3150981CHESPKA
Adder
2.295
316388AE2-253 GEN
Solar/Wind Harmer
1.388
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971065AG2-659 GEN
Solar/Wind Harmer
8.623
970401AG2-262 GEN
Solar/Wind Harmer
1.122
316129AC1-054 GEN
Solar/Wind Harmer
1.501
316237AB2-079_GEN
Solar/Wind Harmer
0.514
3146516WINFALL
Solar/Wind Harmer
-0.053
3146516WINFALL
Solar/Wind Harmer
-0.016
316003AC1-222 GEN
Solar/Wind Harmer
1.598
3147043LAWRENC
Adder
1.308
315800Z1-036_GEN1
Solar/Wind Harmer
4.001
971795AH1-408 GEN
Solar/Wind Harmer
12.102
3130156CHOWAN
Solar/Wind Harmer
-0.016
960081AF2-299 GEN
Solar/Wind Harmer
1.79
316023GEN1_S
Solar/Wind Harmer
1.06
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.733
3145783HORNRTN
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.191
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316359AB2-059 GEN
Solar/Wind Harmer
2.091
316049AB1-081 GEN
Solar/Wind Harmer
1.673
3142053HEARTS
Solar/Wind Harmer
0.182
316011AB1-132 GEN
Solar/Wind Harmer
3.244
962571AG1-106 GEN
Solar/Wind Harmer
2.229
3145796HORNRTN
Solar/Wind Harmer
-0.051
3145796HORNRTN
Solar/Wind Harmer
-0.015
315722AD1-056 GEN
Solar/Wind Harmer
1.622
3146233WITAKRS
Solar/Wind Harmer
-0.061
961671AG1-007 GEN
Solar/Wind Harmer
0.194
3146083TARBORO
Solar/Wind Harmer
-0.015
3145493TOT1
Solar/Wind Harmer
0.456
316212AC1-099_GEN
Solar/Wind Harmer
1.34
3145963POPLR C
Solar/Wind Harmer
-0.015
316174AB2-169 GEN
Solar/Wind Harmer
2.357
316494AC1-189 GEN
Solar/Wind Harmer
1.643
3146293MARTNCO
Solar/Wind Harmer
0.094
3145746EVERETS
Solar/Wind Harmer
-0.015
3151031BRUNSWICKG2
50/50
3.386
970413AG2-270 GEN
50/50
18.7
3151101ELIZAR3
50/50
18.555
315773AC2-141 GEN
Solar/Wind Harmer
27.544
970917AG2-570 GEN
Solar/Wind Harmer
68.686
944581AF1-123 GEN
Solar/Wind Harmer
109.673
944601AF1-125 GEN
Solar/Wind Harmer
107.961
316478AD1-087 GEN
Solar/Wind Harmer
1.946
316486AD2-202 GEN
Solar/Wind Harmer
0.57
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.454
316320Y1-086
Solar/Wind Harmer
1.083
3144536CHRHLND
Solar/Wind Harmer
-0.003
316248AF1-058 C
Solar/Wind Harmer
0.522
960061AF2-297 GEN
Solar/Wind Harmer
8.669
316131AB2-060 GEN
Solar/Wind Harmer
1.825
964241AG1-285 GEN
Solar/Wind Harmer
12.927
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
970909AG2-566 GEN
Solar/Wind Harmer
1.549
3147043LAWRENC
Solar/Wind Harmer
-0.01
3146376EDENTON
Solar/Wind Harmer
-0.016
315785AD2-033 C
Solar/Wind Harmer
3.613
316435W1029_GEN3
Solar/Wind Harmer
2.886
966621AG1-532 GEN
Solar/Wind Harmer
0.323
316283AC2-100 C
Solar/Wind Harmer
1.496
313506AB2-031 GEN
Solar/Wind Harmer
1.271
316365GEN2_N
Solar/Wind Harmer
1.06
315614AA2-178 GEN
Solar/Wind Harmer
1.696
3145746EVERETS
Solar/Wind Harmer
-0.015
3146206CASHIE
Solar/Wind Harmer
-0.015
971547AH1-271 GEN
Solar/Wind Harmer
3.788
970685AG2-442 GEN
Solar/Wind Harmer
13.246
3146263WOODLND
Solar/Wind Harmer
-0.015
3145823KELFORD
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
963171AG1-166 GEN
Solar/Wind Harmer
1.825
971563AH1-280 GEN
Solar/Wind Harmer
1.825
3144293JTRSVLE
Adder
0.414
3145893MURPHYS
Solar/Wind Harmer
-0.058
3145893MURPHYS
Solar/Wind Harmer
0.431
316159AE1-175 C
Solar/Wind Helper
0.509
3141766HARMONY
Solar/Wind Helper
0.049
3138133OCRAN
Solar/Wind Helper
0.148
964211AG1-282 GEN
Solar/Wind Helper
0.305
3141726DUNNSVL
Solar/Wind Helper
0.905
970533AG2-339 GEN
50/50
24.232
970531AG2-338 GEN
50/50
9.693
315242AE2-183_GT2
50/50
4.325
315241AE2-183_GT1
50/50
4.299
972185AH1-677 GEN
50/50
15.592
3151041BRUNSWICKG3
50/50
3.386
972187AH1-678 GEN
50/50
7.769
970933AG2-581 GEN
Solar/Wind Harmer
25.842
970099AG2-077 GEN
Solar/Wind Harmer
30.022
316185AD1-033 GEN
Solar/Wind Harmer
2.257
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.051
3145506HICKORY
Solar/Wind Harmer
-0.013
3142956BIRDNECK
Solar/Wind Harmer
1.119
316316AC1-027 C
Solar/Wind Harmer
0.638
316036AC1-147 C
Solar/Wind Harmer
0.557
3150991CHESPKB
Adder
1.926
3150991CHESPKB
Adder
1.879
316339AD2-160 GEN
Solar/Wind Harmer
1.388
316018AA1-139 ULT2
Solar/Wind Harmer
1.75
316017AA1-139 ULT1
Solar/Wind Harmer
1.653
3137176SLIGO L2192
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.378
3130086AYDLETT
Solar/Wind Harmer
-0.079
3146386ELIZ CT
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.967
971741AH1-377 GEN
Solar/Wind Harmer
20.543
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
964791AG1-342 GEN
Solar/Wind Harmer
3.674
962561AG1-105 GEN
Solar/Wind Harmer
9.657
313527AB2-043 GEN
Solar/Wind Harmer
2.762
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
970301AG2-198 GEN
Solar/Wind Harmer
8.157
3146376EDENTON
Solar/Wind Harmer
0.475
3146376EDENTON
Solar/Wind Harmer
0.475
3144356SAPONY
Solar/Wind Harmer
0.557
316222AC1-221 GEN
Solar/Wind Harmer
1.617
316431W1029_GEN1
Solar/Wind Harmer
2.886
316433W1029_GEN2
Solar/Wind Harmer
2.886
316181AB2-040 GEN
Solar/Wind Harmer
2.206
970323AG2-213 GEN
Solar/Wind Harmer
7.857
971775AH1-396 GEN
Solar/Wind Harmer
1.119
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.767
3145593CAROLNA
Solar/Wind Harmer
0.13
316034AC1-036 C
Solar/Wind Harmer
0.291
3145783HORNRTN
Solar/Wind Harmer
1.86
3145783HORNRTN
Solar/Wind Harmer
1.488
3145783HORNRTN
Solar/Wind Harmer
0.465
3145783HORNRTN
Solar/Wind Harmer
0.186
316426AA2-053 GEN
Solar/Wind Harmer
1.572
316263AC1-034 GEN
Solar/Wind Harmer
7.27
3145796HORNRTN
Solar/Wind Harmer
-0.046
961601AG1-000A GEN
Solar/Wind Harmer
6.09
316274AC1-208 GEN
Solar/Wind Harmer
1.672
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
315244AE2-183_ST
50/50
7.478
963041AG1-153 GEN
50/50
6.855
3151541CLOVER2
50/50
4.265
3151081ELIZAR1
50/50
18.321
941031AE2-094 GEN
Solar/Wind Harmer
57.43
944011AF1-069 GEN
Solar/Wind Harmer
17.995
970673AG2-436 GEN
Solar/Wind Harmer
62.661
970673AG2-436 GEN
Solar/Wind Harmer
31.727
971967AH1-528 GEN
Solar/Wind Harmer
54.485
970085AG2-068 GEN
Solar/Wind Harmer
17.073
970581AG2-369 GEN
Solar/Wind Harmer
14.683
3151091ELIZAR2
Adder
16.966
3152611GOSPORTB
Adder
2.331
3152621GOSPORTC
Adder
1.978
3152601GOSPORTA
Adder
1.825
957871AF2-081 GEN
Solar/Wind Harmer
10.216
319010AE1-072 C
Solar/Wind Harmer
4.045
3146406KITTY HAWK
Solar/Wind Harmer
0.017
313526AB2-022
Solar/Wind Harmer
0.498
316321Z2-027
Solar/Wind Harmer
0.479
3146396TANGLEW
Solar/Wind Harmer
0.327
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3147173SINAI
Solar/Wind Harmer
-0.017
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.188
316239AB2-077_GEN
Solar/Wind Harmer
0.514
316238AB2-078_GEN
Solar/Wind Harmer
0.514
970831AG2-522 GEN
Solar/Wind Harmer
8.491
315611Z1-036_GEN2
Solar/Wind Harmer
4.001
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
316315AB2-025 C
Solar/Wind Harmer
0.431
315814AE2-033 C
Solar/Wind Harmer
14.87
946281AF1-292 GEN
Solar/Wind Harmer
0.356
316087AB2-174 GEN
Solar/Wind Harmer
2.26
971443AH1-215 GEN
Solar/Wind Harmer
3.103
3137643SOCKMAN
Solar/Wind Harmer
-0.063
315816AE2-034 GEN
Solar/Wind Harmer
1.272
3144303KENBRDG
Solar/Wind Harmer
-0.013
315652AC1-086 GEN
Solar/Wind Harmer
17.441
3145796HORNRTN
Solar/Wind Harmer
-0.049
3145796HORNRTN
Solar/Wind Harmer
-0.006
316319Z2-044 C
Solar/Wind Harmer
0.856
3130546PLYMOUTH
Solar/Wind Harmer
-0.015
315732AD1-074 GEN1
Solar/Wind Harmer
3.122
315733AD1-074 GEN2
Solar/Wind Harmer
3.122
315735AD1-075 GEN1
Solar/Wind Harmer
1.561
3145573BETHELC
Solar/Wind Harmer
-0.015
3145573BETHELC
Solar/Wind Harmer
-0.015
316420AA1-050 GEN
Solar/Wind Harmer
1.751
957861AF2-080 GEN
Solar/Wind Harmer
6.681
3146033SCOT NK
Solar/Wind Harmer
-0.061
315607AA1-063A GEN
Solar/Wind Harmer
1.534
316005AA1-067
Solar/Wind Harmer
0.307
3145746EVERETS
Solar/Wind Harmer
-0.06
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
1.989
3146206CASHIE
Solar/Wind Harmer
-0.015
970601AG2-382 GEN
Solar/Wind Harmer
6.629
970683AG2-441 GEN
Solar/Wind Harmer
11.827
970681AG2-440 GEN
Solar/Wind Harmer
9.461
3146043SEABORD
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145513AHOSKIE
Solar/Wind Harmer
0.129
961941AG1-037 GEN
Solar/Wind Harmer
0.111
3145513AHOSKIE
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
5.947
946301AF1-294 GEN
Solar/Wind Harmer
3.74
961791AG1-021 GEN
Solar/Wind Harmer
1.825
316318V4-068
Solar/Wind Harmer
0.362
3145893MURPHYS
Solar/Wind Harmer
-0.039
3145893MURPHYS
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
965291AG1-394 GEN
Solar/Wind Harmer
1.275
315657AE1-056 GEN
Solar/Wind Harmer
5.332
270455AD2-022 GEN
Solar/Wind Harmer
2.402
270457AD2-023 GEN
Solar/Wind Harmer
1.218
316123AC1-075 GEN
Solar/Wind Harmer
1.387
970165AG2-112 GEN
Solar/Wind Harmer
1.221
970163AG2-111 GEN
Solar/Wind Harmer
1.165
957831AF2-077 GEN
Solar/Wind Helper
0.39
957601AF2-054 GEN
Solar/Wind Helper
0.337
3141873WAN 176
Solar/Wind Helper
0.05
3141913WHIT STONE
Solar/Wind Helper
0.247
316059AD1-063 C
Solar/Wind Helper
0.249
3138133OCRAN
Solar/Wind Helper
0.074
3141783LANCAST
Solar/Wind Helper
0.146
3141783LANCAST
Solar/Wind Helper
0.098
315662AE1-191 GEN
Solar/Wind Helper
1.31
315666AE1-190 GEN
Solar/Wind Helper
0.327
3141813NORNECK
Solar/Wind Helper
0.225
3145493TOT1
Solar/Wind Harmer
0.238
3145453TOT5
Solar/Wind Harmer
0.143
3145603CNETO
Solar/Wind Harmer
0.095
316065AD1-022 GEN
Solar/Wind Harmer
7.628
3145933PARMELE
Solar/Wind Harmer
-0.03
3145933PARMELE
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
958211AF2-115 GEN
Solar/Wind Harmer
2.281
963191AG1-168 GEN
Solar/Wind Harmer
1.368
3144293JTRSVLE
Adder
0.414
3144293JTRSVLE
Adder
0.348
3145893MURPHYS
Solar/Wind Harmer
0.405
3145893MURPHYS
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
315742AE1-103 GEN
Solar/Wind Harmer
1.368
316487AF1-042 GEN
Solar/Wind Helper
0.24
316077AC2-138 C
Solar/Wind Helper
0.212
970257AG2-171 GEN
Solar/Wind Harmer
5.892
959311AF2-222 GEN
Solar/Wind Harmer
16.228
971683AH1-343 GEN
Solar/Wind Harmer
6.691
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.062
3145796HORNRTN
Solar/Wind Harmer
-0.015
315724AD1-057 GEN
Solar/Wind Harmer
0.892
3138543CONSLDL
Solar/Wind Harmer
-0.01
3146233WITAKRS
Solar/Wind Harmer
0.324
3146233WITAKRS
Solar/Wind Harmer
-0.01
961601AG1-000A GEN
Solar/Wind Harmer
6.167
316327AA2-057 GEN
Solar/Wind Harmer
1.564
971157AH1-035 GEN
Solar/Wind Harmer
1.935
315737AD1-076 GEN
Solar/Wind Harmer
2.934
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.015
3146083TARBORO
Solar/Wind Harmer
-0.015
316210AC1-098 GEN
Solar/Wind Harmer
2.411
3145963POPLR C
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.9
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146206CASHIE
Solar/Wind Harmer
-0.015
3146263WOODLND
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
0.709
3145823KELFORD
Solar/Wind Harmer
-0.015
316463AE2-346 GEN
Solar/Wind Harmer
0.239
316140AB2-099
Solar/Wind Harmer
0.1
962331AG1-082 GEN
Solar/Wind Harmer
1.848
3156021HOLLOMANSOL
Solar/Wind Harmer
1.987
3146173TUNIS
Solar/Wind Harmer
-0.015
963181AG1-167 GEN
Solar/Wind Harmer
1.368
3144293JTRSVLE
Adder
0.414
957521AF2-046 GEN
Solar/Wind Harmer
11.482
961681AG1-008 GEN
Solar/Wind Harmer
11.482
3145893MURPHYS
Solar/Wind Harmer
0.101
3145893MURPHYS
Solar/Wind Harmer
-0.014
3156081AA2-088 GEN
Solar/Wind Harmer
4.63
3147133PAMPLIN
Solar/Wind Harmer
-0.044
971193AH1-056 GEN
Solar/Wind Harmer
8.887
942461AE2-259 GEN
Solar/Wind Harmer
1.975
3145273HOLLAND
Solar/Wind Harmer
-0.01
316382AG1-145 C
Solar/Wind Helper
0.451
316156AD2-030 GEN
Solar/Wind Helper
0.379
316280AD1-041 GEN
Solar/Wind Helper
0.819
316484AD2-074 GEN
Solar/Wind Helper
0.458
316404AE1-155 C
Solar/Wind Helper
1.965
CPLELTFEXP_CPLE->PJM
CLTF
10.589
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.328
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.129
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.134
MECLTFEXP_MEC->PJM
CLTF
3.403
SIGELTFEXP_SIGE->PJM
CLTF
0.101
NYPJM->LTFIMP_NY
CLTF
1.354
LGEELTFEXP_LGEE->PJM
CLTF
1.211
WECLTFEXP_WEC->PJM
CLTF
0.63
LAGNLTFEXP_LAGN->PJM
CLTF
7.136
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.765
TVALTFEXP_TVA->PJM
CLTF
3.554

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.85 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5791.82
MW Contribution:1.15
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
19.951
971507AH1-251 GEN
50/50
16.627
970119AG2-088 GEN
50/50
35.342
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.079
3152331SURRY 2
50/50
9.986
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
9.742
3147666LOUISA
Solar/Wind Harmer
1.096
316192AB2-158 GEN
Solar/Wind Harmer
1.516
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.34
940641AE2-051 GEN
Solar/Wind Harmer
19.885
939411AE1-173 GEN
Solar/Wind Harmer
105.071
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.205
315671AE2-027_GEN
Solar/Wind Harmer
15.49
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
944591AF1-124 GEN
Solar/Wind Harmer
54.321
971069AG2-661 GEN
Solar/Wind Harmer
4.273
944631AF1-128 GEN
Adder
114.478
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.995
971647AH1-324 GEN
Solar/Wind Harmer
10.238
970659AG2-427 GEN
Solar/Wind Harmer
11.598
961611AG1-000B GEN
Solar/Wind Harmer
12.573
3145336SMITFLD
Solar/Wind Harmer
0.958
316381AD1-082 GEN
Solar/Wind Harmer
0.25
3151171GRAVELC
Adder
2.547
970661AG2-428 GEN
Solar/Wind Harmer
23.769
3142416OLDCHRC
Solar/Wind Harmer
0.62
3142416OLDCHRC
Solar/Wind Harmer
0.237
316388AE2-253 GEN
Solar/Wind Harmer
0.746
3138126ROCKLANDING
Solar/Wind Harmer
0.109
3146456SLIGO L269
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.086
316159AE1-175 C
Solar/Wind Harmer
0.205
316246AF1-032 C
Solar/Wind Harmer
0.107
971317AH1-138 GEN
Solar/Wind Harmer
1.763
316093AE2-104_GEN
Solar/Wind Harmer
3.967
3142433PROV 92
Solar/Wind Harmer
0.929
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
0.752
971531AH1-263 GEN
50/50
60.398
316303AF2-085
50/50
4.712
971285AH1-108 GEN
50/50
1.991
970603AG2-384 GEN
50/50
5.178
316164AC1-076 GEN
Solar/Wind Harmer
0.448
316233AE1-074 FULL
Solar/Wind Harmer
0.206
971281AH1-106 GEN
Solar/Wind Harmer
3.576
971283AH1-107 GEN
Solar/Wind Harmer
3.576
3143316POE
Solar/Wind Harmer
0.962
941031AE2-094 GEN
Solar/Wind Harmer
44.489
944011AF1-069 GEN
Solar/Wind Harmer
14.536
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
22.001
3151091ELIZAR2
Adder
21.619
3152611GOSPORTB
Adder
3.055
3152621GOSPORTC
Adder
2.593
3152601GOSPORTA
Adder
2.392
971445AH1-216 GEN
Solar/Wind Harmer
16.874
972265AH1-717 GEN
Adder
18.594
3151201GRAVEL4
Adder
17.43
3151191GRAVEL3
Adder
17.21
3151211GRAVEL5
Adder
17.21
316312AB1-027
Solar/Wind Harmer
0.427
957871AF2-081 GEN
Solar/Wind Harmer
11.843
970673AG2-436 GEN
Solar/Wind Harmer
50.646
970673AG2-436 GEN
Solar/Wind Harmer
33.764
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
319010AE1-072 C
Solar/Wind Harmer
1.195
316311AC2-079 GEN
Solar/Wind Harmer
6.813
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.491
316169AC1-164_GENC
Solar/Wind Harmer
21.158
315975AC1-164 GENB
Solar/Wind Harmer
0.725
315835AF2-110_GEN
Solar/Wind Harmer
1.619
316315AB2-025 C
Solar/Wind Harmer
0.19
313526AB2-022
Solar/Wind Harmer
0.127
3146516WINFALL
Solar/Wind Harmer
0.232
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.063
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141843SHACKLE
Adder
1.161
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.226
966881AG1-559 GEN
Solar/Wind Harmer
0.262
970919AG2-571 GEN
Solar/Wind Harmer
7.971
970087AG2-069 GEN
Solar/Wind Harmer
17.86
3138133OCRAN
Solar/Wind Harmer
0.133
3145663CRESWEL
Solar/Wind Harmer
0.62
971163AH1-040 GEN
Solar/Wind Harmer
17.736
972197AH1-683 GEN
Adder
4.589
972219AH1-694 GEN
Adder
3.304
316336AC2-165 C
Solar/Wind Harmer
0.009
316023GEN1_S
Solar/Wind Harmer
0.488
3146206CASHIE
Solar/Wind Harmer
0.215
971547AH1-271 GEN
Solar/Wind Harmer
4.597
3145893MURPHYS
Solar/Wind Harmer
0.86
3145893MURPHYS
Solar/Wind Harmer
0.956
957481AF2-042 GEN
Solar/Wind Harmer
57.154
3146173TUNIS
Solar/Wind Harmer
0.213
960081AF2-299 GEN
Solar/Wind Harmer
2.037
962861AG1-135 GEN
Solar/Wind Harmer
6.776
3145683EARLEYS
Solar/Wind Harmer
0.211
315693AD1-088 GEN
Solar/Wind Harmer
10.092
3146263WOODLND
Solar/Wind Harmer
0.21
962491AG1-098 GEN
Solar/Wind Harmer
11.964
316011AB1-132 GEN
Solar/Wind Harmer
3.787
962571AG1-106 GEN
Solar/Wind Harmer
2.963
971795AH1-408 GEN
Solar/Wind Harmer
13.875
3145963POPLR C
Solar/Wind Harmer
0.207
3141726DUNNSVL
Solar/Wind Harmer
0.83
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.207
3147043LAWRENC
Adder
1.866
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3145783HORNRTN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.677
3152261N ANNA2
50/50
19.95
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.079
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.199
316044AC1-158 PL1
Solar/Wind Harmer
3.047
316450AC1-158 RIC
Solar/Wind Harmer
0.812
3147666LOUISA
Solar/Wind Harmer
0.63
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.863
965281AG1-393 GEN
Solar/Wind Harmer
2.583
970133AG2-095 GEN
Solar/Wind Harmer
2.314
315813AE1-149 C
Solar/Wind Harmer
12.857
970129AG2-093 GEN
Solar/Wind Harmer
14.547
944581AF1-123 GEN
Solar/Wind Harmer
54.129
944601AF1-125 GEN
Solar/Wind Harmer
53.295
315778AD1-151 GEN
Solar/Wind Harmer
19.229
3151101ELIZAR3
Adder
22.283
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.537
961611AG1-000B GEN
Solar/Wind Harmer
6.393
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.41
3151171GRAVELC
Adder
3.35
970293AG2-193 GEN
Solar/Wind Harmer
2.553
3142946ENON
Solar/Wind Harmer
0.08
970661AG2-428 GEN
Solar/Wind Harmer
5.055
3142416OLDCHRC
Solar/Wind Harmer
2.311
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
0.237
971153AH1-033 GEN
Solar/Wind Harmer
2.744
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
0.232
316473AC1-191 GEN
Solar/Wind Harmer
0.781
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.172
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.453
3141843SHACKLE
Adder
1.161
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
3.026
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.226
316156AD2-030 GEN
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
4.013
970917AG2-570 GEN
Solar/Wind Harmer
19.927
315614AA2-178 GEN
Solar/Wind Harmer
1.269
3150401LDYSMT4
Adder
29.389
3150371LDYSMT1
Adder
28.398
971157AH1-035 GEN
Solar/Wind Harmer
2.618
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.488
315737AD1-076 GEN
Solar/Wind Harmer
2.798
962971AG1-146 GEN
Solar/Wind Harmer
3.462
3146206CASHIE
Solar/Wind Harmer
0.215
3145893MURPHYS
Solar/Wind Harmer
0.36
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.963
961681AG1-008 GEN
Solar/Wind Harmer
15.963
970009AG2-005 GEN
Solar/Wind Harmer
1.6
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.965
316463AE2-346 GEN
Solar/Wind Harmer
0.182
316140AB2-099
Solar/Wind Harmer
0.076
962331AG1-082 GEN
Solar/Wind Harmer
2.263
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.21
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.041
316212AC1-099_GEN
Solar/Wind Harmer
1.035
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.425
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315722AD1-056 GEN
Solar/Wind Harmer
1.233
316337AD2-073 GEN
Solar/Wind Harmer
0.169
970937AG2-583 GEN
Solar/Wind Harmer
11.922
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.649
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
14.314
963171AG1-166 GEN
Solar/Wind Harmer
1.021
971563AH1-280 GEN
Solar/Wind Harmer
2.042
3144293JTRSVLE
Adder
0.609
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.755
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.189
3145493TOT1
Solar/Wind Harmer
0.843
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.669
316049AB1-081 GEN
Solar/Wind Harmer
1.066
3142053HEARTS
Solar/Wind Harmer
0.328
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.073
313506AB2-031 GEN
Solar/Wind Harmer
0.648
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145963POPLR C
Solar/Wind Harmer
0.207
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.207
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.82
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.857
3145933PARMELE
Solar/Wind Harmer
0.199
966801AG1-551 GEN
Solar/Wind Harmer
2.319
970909AG2-566 GEN
Solar/Wind Harmer
2.12
971781AH1-399 GEN
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315724AD1-057 GEN
Solar/Wind Harmer
0.731
316327AA2-057 GEN
Solar/Wind Harmer
0.292
316131AB2-060 GEN
Solar/Wind Harmer
0.605
964241AG1-285 GEN
Solar/Wind Harmer
12.823
315785AD2-033 C
Solar/Wind Harmer
1.561
970257AG2-171 GEN
Solar/Wind Harmer
6.143
959311AF2-222 GEN
Solar/Wind Harmer
17.057
963181AG1-167 GEN
Solar/Wind Harmer
0.766
3144293JTRSVLE
Adder
0.609
3147133PAMPLIN
Solar/Wind Harmer
0.6
971193AH1-056 GEN
Solar/Wind Harmer
11.648
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.953
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.189
3146083TARBORO
Solar/Wind Harmer
0.189
3138543CONSLDL
Solar/Wind Harmer
0.125
3132273ORANGE
Solar/Wind Harmer
0.038
961601AG1-000A GEN
Solar/Wind Harmer
13.257
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.186
971623AH1-311 GEN
Solar/Wind Harmer
0.373
3141906WESTMOR
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.066
972189AH1-679 GEN
Adder
3.932
3146486SUNBURY
Solar/Wind Harmer
0.234
3146486SUNBURY
Solar/Wind Harmer
0.234
971967AH1-528 GEN
Solar/Wind Harmer
37.517
315814AE2-033 C
Solar/Wind Harmer
18.537
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.645
3145176PASQUOTANK
Solar/Wind Harmer
0.145
971167AH1-042 GEN
Solar/Wind Harmer
20.705
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3138283WHITEMARSH
Solar/Wind Harmer
0.054
3143873LANEXA
Solar/Wind Harmer
0.138
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.735
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.226
3130156CHOWAN
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
0.045
970085AG2-068 GEN
Solar/Wind Harmer
11.907
970581AG2-369 GEN
Solar/Wind Harmer
10.24
3141913WHIT STONE
Solar/Wind Harmer
0.222
3138133OCRAN
Solar/Wind Harmer
0.066
315816AE2-034 GEN
Solar/Wind Harmer
0.951
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3150411LDYSMT5
Adder
29.481
3150381LDYSMT2
Adder
28.214
972213AH1-691 GEN
Adder
4.773
972215AH1-692 GEN
Adder
4.773
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.25
315733AD1-074 GEN2
Solar/Wind Harmer
1.25
315735AD1-075 GEN1
Solar/Wind Harmer
0.626
965291AG1-394 GEN
Solar/Wind Harmer
0.964
962981AG1-147 GEN
Solar/Wind Harmer
8.079
3146206CASHIE
Solar/Wind Harmer
0.215
970601AG2-382 GEN
Solar/Wind Harmer
8.044
3145893MURPHYS
Solar/Wind Harmer
0.581
3145893MURPHYS
Solar/Wind Harmer
0.215
970327AG2-215 GEN
Solar/Wind Harmer
7.032
3145513AHOSKIE
Solar/Wind Harmer
0.443
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.422
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.431
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.91
3137643SOCKMAN
Solar/Wind Harmer
0.831
3145796HORNRTN
Solar/Wind Harmer
0.656
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
0.813
970831AG2-522 GEN
Solar/Wind Harmer
8.493
316005AA1-067
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.776
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
970181AG2-120 GEN
Solar/Wind Harmer
2.429
957861AF2-080 GEN
Solar/Wind Harmer
8.286
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.225
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
12.781
970681AG2-440 GEN
Solar/Wind Harmer
10.225
946301AF1-294 GEN
Solar/Wind Harmer
3.778
961791AG1-021 GEN
Solar/Wind Harmer
1.838
315657AE1-056 GEN
Solar/Wind Harmer
6.598
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.189
3145573BETHELC
Solar/Wind Harmer
0.189
970285AG2-188 GEN
Solar/Wind Harmer
14.603
316223AC1-118
Solar/Wind Harmer
0.132
971845AH1-439 GEN
Solar/Wind Harmer
8.313
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.481
970737AG2-469 GEN
Solar/Wind Harmer
7.427
316170AC1-121 GEN2
Solar/Wind Harmer
0.183
3151761LOISA E
Adder
22.218
972183AH1-676 GEN
Adder
173.787
970221AG2-151 GEN
Solar/Wind Harmer
8.67
971683AH1-343 GEN
Solar/Wind Harmer
5.958
316283AC2-100 C
Solar/Wind Harmer
0.309
972255AH1-712 GEN
Adder
76.037
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.164
970401AG2-262 GEN
Solar/Wind Harmer
1.071
972003AH1-546 GEN
Solar/Wind Harmer
7.446
316254AC1-120 GEN1
Solar/Wind Harmer
0.366
316003AC1-222 GEN
Solar/Wind Harmer
0.004
3151751LOISA D
Adder
10.898
972135AH1-637 GEN
Solar/Wind Harmer
1.429
971377AH1-170 GEN
Solar/Wind Harmer
1.734
3147623JAMES R
Solar/Wind Harmer
0.377
972277AH1-723 GEN
Adder
88.606
971133AH1-012 GEN
50/50
5.665
944641AF1-129 GEN
50/50
122.768
3142366NRTHEST
50/50
0.838
970533AG2-339 GEN
50/50
21.472
970531AG2-338 GEN
50/50
8.589
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.39
316447AC1-158 HLD
Solar/Wind Harmer
6.696
971223AH1-071 GEN
Solar/Wind Harmer
2.827
3143526WINTERP
Solar/Wind Harmer
1.34
316240AF1-291 C
Solar/Wind Harmer
0.002
3150701DARBY 4
Adder
17.29
3150681DARBY 2
Adder
17.27
3150671DARBY 1
Adder
17.25
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.27
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.513
3150991CHESPKB
Adder
2.452
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.23
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.383
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.955
3145506HICKORY
Solar/Wind Harmer
0.573
3145506HICKORY
Solar/Wind Harmer
0.143
316339AD2-160 GEN
Solar/Wind Harmer
0.386
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
316075AC2-137 C
Solar/Wind Harmer
0.065
3137176SLIGO L2192
Solar/Wind Harmer
0.945
3146456SLIGO L269
Solar/Wind Harmer
4.201
3130086AYDLETT
Solar/Wind Harmer
0.948
972185AH1-677 GEN
Adder
13.205
3144356SAPONY
Solar/Wind Harmer
1.967
3146386ELIZ CT
Solar/Wind Harmer
0.235
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.623
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
970933AG2-581 GEN
Solar/Wind Harmer
18.312
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.66
970317AG2-208 GEN
Solar/Wind Harmer
8.949
3146376EDENTON
Solar/Wind Harmer
1.006
3146376EDENTON
Solar/Wind Harmer
1.006
315673AE1-157 GEN
Solar/Wind Harmer
15.472
3150391LDYSMT3
Adder
29.334
972195AH1-682 GEN
Adder
3.855
316065AD1-022 GEN
Solar/Wind Harmer
9.955
3145893MURPHYS
Solar/Wind Harmer
1.439
3145893MURPHYS
Solar/Wind Harmer
0.387
970099AG2-077 GEN
Solar/Wind Harmer
22.861
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.972
316181AB2-040 GEN
Solar/Wind Harmer
0.304
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.125
316426AA2-053 GEN
Solar/Wind Harmer
0.701
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
966811AG1-552 GEN
Solar/Wind Harmer
2.242
3145593CAROLNA
Solar/Wind Harmer
0.257
3145783HORNRTN
Solar/Wind Harmer
3.653
3145783HORNRTN
Solar/Wind Harmer
2.922
3145783HORNRTN
Solar/Wind Harmer
0.913
3145783HORNRTN
Solar/Wind Harmer
0.365
3145796HORNRTN
Solar/Wind Harmer
0.615
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.144
3150341NORNECKC1
Adder
2.127
971741AH1-377 GEN
Solar/Wind Harmer
19.978
3145933PARMELE
Solar/Wind Harmer
0.398
3145933PARMELE
Solar/Wind Harmer
0.199
316274AC1-208 GEN
Solar/Wind Harmer
1.032
970301AG2-198 GEN
Solar/Wind Harmer
8.48
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
939181AE1-148 GEN
Solar/Wind Harmer
9.287
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.19
971775AH1-396 GEN
Solar/Wind Harmer
0.307
958211AF2-115 GEN
Solar/Wind Harmer
2.298
963191AG1-168 GEN
Solar/Wind Harmer
0.766
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.153
3145493TOT1
Solar/Wind Harmer
0.439
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
961601AG1-000A GEN
Solar/Wind Harmer
3.314
316263AC1-034 GEN
Solar/Wind Harmer
7.082
962561AG1-105 GEN
Solar/Wind Harmer
8.835
3146776BUCKING
Solar/Wind Harmer
0.73
3146776BUCKING
Solar/Wind Harmer
0.059
964791AG1-342 GEN
Solar/Wind Harmer
3.505
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
966001AG1-469 GEN
Solar/Wind Harmer
0.098
3151731LOISA B
Adder
10.898
3151721LOISA A
Adder
10.842
971489AH1-241 GEN
Solar/Wind Harmer
8.67
316222AC1-221 GEN
Solar/Wind Harmer
0.658
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.283
315651AD1-115 GEN
Solar/Wind Harmer
0.004
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.416
3147346CASHSCORNER
Solar/Wind Harmer
0.37
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971447AH1-217 GEN
Solar/Wind Harmer
4.798
970865AG2-541 GEN
Solar/Wind Harmer
5.388
972193AH1-681 GEN
Adder
3.397
270494AE1-108_GEN
Solar/Wind Harmer
1.716
316123AC1-075 GEN
Solar/Wind Harmer
0.194
970165AG2-112 GEN
Solar/Wind Harmer
1.153
970163AG2-111 GEN
Solar/Wind Harmer
1.1
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.82
316415AF1-147_GEN2
Solar/Wind Helper
0.82
3138216PACIFIC
Solar/Wind Helper
0.04
CPLELTFEXP_CPLE->PJM
CLTF
12.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.739
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.068
MECLTFEXP_MEC->PJM
CLTF
3.555
SIGELTFEXP_SIGE->PJM
CLTF
0.108
NYPJM->LTFIMP_NY
CLTF
3.433
LGEELTFEXP_LGEE->PJM
CLTF
1.291
WECLTFEXP_WEC->PJM
CLTF
0.616
LAGNLTFEXP_LAGN->PJM
CLTF
8.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
4.157

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.06 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5637.7
MW Contribution:1.13
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
19.719
970119AG2-088 GEN
50/50
34.806
3150851SPRUNCC
50/50
1.197
3143096IRON208
50/50
1.062
3152331SURRY 2
50/50
9.829
3150771HOPHCF1
50/50
0.962
316045AC1-158 PL2
Solar/Wind Harmer
9.665
3147666LOUISA
Solar/Wind Harmer
1.067
3143226MDLTHAN
Solar/Wind Harmer
0.261
316192AB2-158 GEN
Solar/Wind Harmer
1.475
3143526WINTERP
Solar/Wind Harmer
1.319
940641AE2-051 GEN
Solar/Wind Harmer
19.587
939411AE1-173 GEN
Solar/Wind Harmer
103.486
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.14
315671AE2-027_GEN
Solar/Wind Harmer
15.248
970129AG2-093 GEN
Solar/Wind Harmer
6.738
316458AB2-190 GEN2
Solar/Wind Harmer
1.271
944591AF1-124 GEN
Solar/Wind Harmer
53.482
971069AG2-661 GEN
Solar/Wind Harmer
4.206
944631AF1-128 GEN
Adder
112.66
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.949
971647AH1-324 GEN
Solar/Wind Harmer
10.078
970659AG2-427 GEN
Solar/Wind Harmer
11.419
3145336SMITFLD
Solar/Wind Harmer
0.943
961611AG1-000B GEN
Solar/Wind Harmer
12.376
316381AD1-082 GEN
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
2.508
970661AG2-428 GEN
Solar/Wind Harmer
23.401
3142416OLDCHRC
Solar/Wind Harmer
0.61
3142416OLDCHRC
Solar/Wind Harmer
0.234
316388AE2-253 GEN
Solar/Wind Harmer
0.734
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3146456SLIGO L269
Solar/Wind Harmer
0.234
316072AD1-144
Solar/Wind Harmer
0.085
316159AE1-175 C
Solar/Wind Harmer
0.201
316246AF1-032 C
Solar/Wind Harmer
0.105
971317AH1-138 GEN
Solar/Wind Harmer
1.735
316093AE2-104_GEN
Solar/Wind Harmer
3.906
3142433PROV 92
Solar/Wind Harmer
0.914
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3146516WINFALL
Solar/Wind Harmer
0.741
3146516WINFALL
Solar/Wind Harmer
0.229
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.993
971777AH1-397 GEN
Solar/Wind Harmer
0.591
3141843SHACKLE
Adder
1.143
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.223
966881AG1-559 GEN
Solar/Wind Harmer
0.257
970919AG2-571 GEN
Solar/Wind Harmer
7.85
970087AG2-069 GEN
Solar/Wind Harmer
17.59
3138133OCRAN
Solar/Wind Harmer
0.131
3145663CRESWEL
Solar/Wind Harmer
0.611
971163AH1-040 GEN
Solar/Wind Harmer
17.461
972197AH1-683 GEN
Adder
4.512
972219AH1-694 GEN
Adder
3.248
316336AC2-165 C
Solar/Wind Harmer
0.008
316023GEN1_S
Solar/Wind Harmer
0.481
3146206CASHIE
Solar/Wind Harmer
0.212
971547AH1-271 GEN
Solar/Wind Harmer
4.525
3145893MURPHYS
Solar/Wind Harmer
0.847
3145893MURPHYS
Solar/Wind Harmer
0.941
957481AF2-042 GEN
Solar/Wind Harmer
56.258
3146173TUNIS
Solar/Wind Harmer
0.21
960081AF2-299 GEN
Solar/Wind Harmer
2.005
962861AG1-135 GEN
Solar/Wind Harmer
6.67
3145683EARLEYS
Solar/Wind Harmer
0.208
315693AD1-088 GEN
Solar/Wind Harmer
9.93
3146263WOODLND
Solar/Wind Harmer
0.207
962491AG1-098 GEN
Solar/Wind Harmer
11.772
316011AB1-132 GEN
Solar/Wind Harmer
3.728
962571AG1-106 GEN
Solar/Wind Harmer
2.917
971795AH1-408 GEN
Solar/Wind Harmer
13.656
3145963POPLR C
Solar/Wind Harmer
0.204
3141726DUNNSVL
Solar/Wind Harmer
0.817
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.204
3147043LAWRENC
Adder
1.836
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3145783HORNRTN
Solar/Wind Harmer
0.202
3145796HORNRTN
Solar/Wind Harmer
0.666
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.009
316212AC1-099_GEN
Solar/Wind Harmer
1.019
3146293MARTNCO
Solar/Wind Harmer
0.182
316303AF2-085
50/50
4.641
971285AH1-108 GEN
50/50
1.959
970603AG2-384 GEN
50/50
5.097
316233AE1-074 FULL
Solar/Wind Harmer
0.203
971281AH1-106 GEN
Solar/Wind Harmer
3.521
971283AH1-107 GEN
Solar/Wind Harmer
3.521
3143316POE
Solar/Wind Harmer
0.947
941031AE2-094 GEN
Solar/Wind Harmer
43.824
944011AF1-069 GEN
Solar/Wind Harmer
14.319
316132AB2-190 GEN1
Solar/Wind Harmer
1.271
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
21.661
3151091ELIZAR2
Adder
21.285
3152611GOSPORTB
Adder
3.008
3152621GOSPORTC
Adder
2.552
3152601GOSPORTA
Adder
2.355
971445AH1-216 GEN
Solar/Wind Harmer
16.611
972265AH1-717 GEN
Adder
18.304
3151201GRAVEL4
Adder
17.158
3151191GRAVEL3
Adder
16.941
3151211GRAVEL5
Adder
16.941
316312AB1-027
Solar/Wind Harmer
0.42
957871AF2-081 GEN
Solar/Wind Harmer
11.66
316164AC1-076 GEN
Solar/Wind Harmer
0.329
970673AG2-436 GEN
Solar/Wind Harmer
49.886
970673AG2-436 GEN
Solar/Wind Harmer
33.257
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.16
319010AE1-072 C
Solar/Wind Harmer
1.177
971133AH1-012 GEN
50/50
5.548
944641AF1-129 GEN
50/50
120.841
970533AG2-339 GEN
50/50
21.15
970531AG2-338 GEN
50/50
8.46
3142366NRTHEST
50/50
0.824
3150781HOPHCF2
50/50
0.962
3150791HOPHCF3
50/50
0.962
3150761HOPPOLC
50/50
0.61
971213AH1-066 GEN
50/50
0.844
3150691DARBY 3
50/50
18.094
3150701DARBY 4
50/50
18.052
316447AC1-158 HLD
Solar/Wind Harmer
6.644
971223AH1-071 GEN
Solar/Wind Harmer
2.784
3143526WINTERP
Solar/Wind Harmer
1.319
316240AF1-291 C
Solar/Wind Harmer
0.002
3150681DARBY 2
Adder
16.992
3150671DARBY 1
Adder
16.973
3142296MT RD221
Adder
0.753
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.266
316036AC1-147 C
Solar/Wind Harmer
0.044
3150991CHESPKB
Adder
2.474
3150991CHESPKB
Adder
2.414
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.226
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.254
970657AG2-426 GEN
Solar/Wind Harmer
1.73
3145506HICKORY
Solar/Wind Harmer
0.94
316311AC2-079 GEN
Solar/Wind Harmer
6.708
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.098
316169AC1-164_GENC
Solar/Wind Harmer
20.818
315975AC1-164 GENB
Solar/Wind Harmer
0.713
315835AF2-110_GEN
Solar/Wind Harmer
1.594
316315AB2-025 C
Solar/Wind Harmer
0.187
313526AB2-022
Solar/Wind Harmer
0.125
971967AH1-528 GEN
Solar/Wind Harmer
36.95
3146486SUNBURY
Solar/Wind Harmer
0.231
3146486SUNBURY
Solar/Wind Harmer
0.231
972189AH1-679 GEN
Adder
3.867
315814AE2-033 C
Solar/Wind Harmer
18.254
316321Z2-027
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
971167AH1-042 GEN
Solar/Wind Harmer
20.377
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143873LANEXA
Solar/Wind Harmer
0.135
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.628
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.223
3130156CHOWAN
Solar/Wind Harmer
0.223
3141873WAN 176
Solar/Wind Harmer
0.044
970085AG2-068 GEN
Solar/Wind Harmer
11.727
970581AG2-369 GEN
Solar/Wind Harmer
10.085
3141913WHIT STONE
Solar/Wind Harmer
0.219
3138133OCRAN
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.937
3141783LANCAST
Solar/Wind Harmer
0.13
3141783LANCAST
Solar/Wind Harmer
0.087
3150411LDYSMT5
Adder
28.983
3150381LDYSMT2
Adder
27.738
972213AH1-691 GEN
Adder
4.692
972215AH1-692 GEN
Adder
4.692
3130546PLYMOUTH
Solar/Wind Harmer
0.215
315732AD1-074 GEN1
Solar/Wind Harmer
1.23
315733AD1-074 GEN2
Solar/Wind Harmer
1.23
315735AD1-075 GEN1
Solar/Wind Harmer
0.616
965291AG1-394 GEN
Solar/Wind Harmer
0.949
962981AG1-147 GEN
Solar/Wind Harmer
7.952
3146206CASHIE
Solar/Wind Harmer
0.212
970601AG2-382 GEN
Solar/Wind Harmer
7.919
3145893MURPHYS
Solar/Wind Harmer
0.572
3145893MURPHYS
Solar/Wind Harmer
0.212
970327AG2-215 GEN
Solar/Wind Harmer
6.922
3145513AHOSKIE
Solar/Wind Harmer
0.437
3145513AHOSKIE
Solar/Wind Harmer
0.209
3146043SEABORD
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.416
3145683EARLEYS
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.208
315607AA1-063A GEN
Solar/Wind Harmer
0.424
316087AB2-174 GEN
Solar/Wind Harmer
0.006
3152261N ANNA2
50/50
19.717
3150861SPRUNCD
50/50
1.197
3143096IRON208
50/50
1.062
3143096IRON208
50/50
1.041
3150801HOPHCF4
50/50
1.399
971211AH1-065 GEN
50/50
1.687
3151161SURRY 1
50/50
9.055
316044AC1-158 PL1
Solar/Wind Harmer
3.023
316450AC1-158 RIC
Solar/Wind Harmer
0.806
3147666LOUISA
Solar/Wind Harmer
0.614
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.726
965281AG1-393 GEN
Solar/Wind Harmer
2.543
315813AE1-149 C
Solar/Wind Harmer
12.658
970133AG2-095 GEN
Solar/Wind Harmer
2.278
970129AG2-093 GEN
Solar/Wind Harmer
14.319
944581AF1-123 GEN
Solar/Wind Harmer
53.293
944601AF1-125 GEN
Solar/Wind Harmer
52.472
315778AD1-151 GEN
Solar/Wind Harmer
18.928
3151101ELIZAR3
Adder
21.938
3144536CHRHLND
Solar/Wind Harmer
0.035
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.498
3145336SMITFLD
Solar/Wind Harmer
0.094
961611AG1-000B GEN
Solar/Wind Harmer
6.293
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.139
3151171GRAVELC
Adder
3.297
970293AG2-193 GEN
Solar/Wind Harmer
2.512
970661AG2-428 GEN
Solar/Wind Harmer
4.977
3142946ENON
Solar/Wind Harmer
0.079
3142416OLDCHRC
Solar/Wind Harmer
2.274
3144216WINCHST
Adder
0.882
3146456SLIGO L269
Solar/Wind Harmer
0.234
971153AH1-033 GEN
Solar/Wind Harmer
2.702
3150921YORKTN3
Adder
5.872
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3146516WINFALL
Solar/Wind Harmer
0.229
316473AC1-191 GEN
Solar/Wind Harmer
0.768
3146626S HERTFORD
Solar/Wind Harmer
0.227
3145273HOLLAND
Solar/Wind Harmer
0.17
316313AB2-026
Solar/Wind Harmer
0.142
316258AE1-075 C
Solar/Wind Harmer
0.17
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.394
3141843SHACKLE
Adder
1.143
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.978
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.223
316156AD2-030 GEN
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
3.95
970917AG2-570 GEN
Solar/Wind Harmer
19.626
315614AA2-178 GEN
Solar/Wind Harmer
1.249
3150401LDYSMT4
Adder
28.893
3150371LDYSMT1
Adder
27.918
971157AH1-035 GEN
Solar/Wind Harmer
2.577
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.481
315737AD1-076 GEN
Solar/Wind Harmer
2.755
962971AG1-146 GEN
Solar/Wind Harmer
3.408
3146206CASHIE
Solar/Wind Harmer
0.212
3145893MURPHYS
Solar/Wind Harmer
0.354
3145893MURPHYS
Solar/Wind Harmer
0.212
957521AF2-046 GEN
Solar/Wind Harmer
15.715
961681AG1-008 GEN
Solar/Wind Harmer
15.715
970009AG2-005 GEN
Solar/Wind Harmer
1.575
3146173TUNIS
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.95
316463AE2-346 GEN
Solar/Wind Harmer
0.179
316140AB2-099
Solar/Wind Harmer
0.075
962331AG1-082 GEN
Solar/Wind Harmer
2.227
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.207
313506AB2-031 GEN
Solar/Wind Harmer
0.638
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3145963POPLR C
Solar/Wind Harmer
0.204
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.204
316478AD1-087 GEN
Solar/Wind Harmer
0.708
316486AD2-202 GEN
Solar/Wind Harmer
0.208
3147043LAWRENC
Solar/Wind Harmer
0.122
3145796HORNRTN
Solar/Wind Harmer
0.807
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.043
316210AC1-098 GEN
Solar/Wind Harmer
1.828
3145933PARMELE
Solar/Wind Harmer
0.196
966801AG1-551 GEN
Solar/Wind Harmer
2.283
315652AC1-086 GEN
Solar/Wind Harmer
22.553
3137643SOCKMAN
Solar/Wind Harmer
0.818
3145796HORNRTN
Solar/Wind Harmer
0.646
3145796HORNRTN
Solar/Wind Harmer
0.081
3141813NORNECK
Solar/Wind Harmer
0.201
3146033SCOT NK
Solar/Wind Harmer
0.8
970831AG2-522 GEN
Solar/Wind Harmer
8.358
3145506HICKORY
Solar/Wind Harmer
0.564
3145506HICKORY
Solar/Wind Harmer
0.141
3142946ENON
Solar/Wind Harmer
0.023
316339AD2-160 GEN
Solar/Wind Harmer
0.38
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.131
3137176SLIGO L2192
Solar/Wind Harmer
0.93
316075AC2-137 C
Solar/Wind Harmer
0.064
3146456SLIGO L269
Solar/Wind Harmer
4.136
3130086AYDLETT
Solar/Wind Harmer
0.933
972185AH1-677 GEN
Adder
13.007
3144356SAPONY
Solar/Wind Harmer
1.937
3146386ELIZ CT
Solar/Wind Harmer
0.231
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.523
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
966871AG1-558 GEN
Solar/Wind Harmer
0.263
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
970933AG2-581 GEN
Solar/Wind Harmer
18.033
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.99
3146376EDENTON
Solar/Wind Harmer
0.99
957411AF2-035 GEN
Solar/Wind Harmer
9.498
970317AG2-208 GEN
Solar/Wind Harmer
8.8
315673AE1-157 GEN
Solar/Wind Harmer
15.213
3150391LDYSMT3
Adder
28.839
972195AH1-682 GEN
Adder
3.79
316065AD1-022 GEN
Solar/Wind Harmer
9.8
3145893MURPHYS
Solar/Wind Harmer
1.417
3145893MURPHYS
Solar/Wind Harmer
0.381
970099AG2-077 GEN
Solar/Wind Harmer
22.503
3146173TUNIS
Solar/Wind Harmer
0.21
3146173TUNIS
Solar/Wind Harmer
0.21
958261AF2-120 GEN
Solar/Wind Harmer
6.863
316181AB2-040 GEN
Solar/Wind Harmer
0.299
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.123
316426AA2-053 GEN
Solar/Wind Harmer
0.69
3145593CAROLNA
Solar/Wind Harmer
0.203
3145593CAROLNA
Solar/Wind Harmer
0.203
966811AG1-552 GEN
Solar/Wind Harmer
2.207
3145593CAROLNA
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
3.596
3145783HORNRTN
Solar/Wind Harmer
2.876
3145783HORNRTN
Solar/Wind Harmer
0.899
3145783HORNRTN
Solar/Wind Harmer
0.36
3145796HORNRTN
Solar/Wind Harmer
0.606
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.11
3150341NORNECKC1
Adder
2.093
971741AH1-377 GEN
Solar/Wind Harmer
19.637
3145933PARMELE
Solar/Wind Harmer
0.392
3145933PARMELE
Solar/Wind Harmer
0.196
316129AC1-054 GEN
Solar/Wind Harmer
0.734
971065AG2-659 GEN
Solar/Wind Harmer
8.291
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315722AD1-056 GEN
Solar/Wind Harmer
1.214
316337AD2-073 GEN
Solar/Wind Harmer
0.167
315687AD1-152 GEN
Solar/Wind Harmer
0.006
970937AG2-583 GEN
Solar/Wind Harmer
11.689
316494AC1-189 GEN
Solar/Wind Harmer
0.639
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
14.068
963171AG1-166 GEN
Solar/Wind Harmer
1.003
971563AH1-280 GEN
Solar/Wind Harmer
2.007
3144293JTRSVLE
Adder
0.599
3146233WITAKRS
Solar/Wind Harmer
0.743
3146926FARMVIL
Solar/Wind Harmer
0.112
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.186
3145493TOT1
Solar/Wind Harmer
0.829
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.147
316359AB2-059 GEN
Solar/Wind Harmer
0.659
316049AB1-081 GEN
Solar/Wind Harmer
1.05
3142053HEARTS
Solar/Wind Harmer
0.323
970401AG2-262 GEN
Solar/Wind Harmer
1.053
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.289
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.408
3151751LOISA D
Adder
10.327
971377AH1-170 GEN
Solar/Wind Harmer
1.696
3147623JAMES R
Solar/Wind Harmer
0.368
972277AH1-723 GEN
Adder
86.868
316254AC1-120 GEN1
Solar/Wind Harmer
0.26
316005AA1-067
Solar/Wind Harmer
0.206
3145746EVERETS
Solar/Wind Harmer
0.764
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
970181AG2-120 GEN
Solar/Wind Harmer
2.391
957861AF2-080 GEN
Solar/Wind Harmer
8.156
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.171
3144303KENBRDG
Solar/Wind Harmer
0.151
970683AG2-441 GEN
Solar/Wind Harmer
12.561
970681AG2-440 GEN
Solar/Wind Harmer
10.049
946301AF1-294 GEN
Solar/Wind Harmer
3.712
961791AG1-021 GEN
Solar/Wind Harmer
1.806
315657AE1-056 GEN
Solar/Wind Harmer
6.482
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.186
3145573BETHELC
Solar/Wind Harmer
0.186
970285AG2-188 GEN
Solar/Wind Harmer
14.319
316223AC1-118
Solar/Wind Harmer
0.13
971845AH1-439 GEN
Solar/Wind Harmer
8.149
316118AC1-105 GEN
Solar/Wind Harmer
0.454
3147173SINAI
Solar/Wind Harmer
0.172
3147243WELCO
Solar/Wind Harmer
0.108
972205AH1-687 GEN
Adder
7.256
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971447AH1-217 GEN
Solar/Wind Harmer
4.692
970865AG2-541 GEN
Solar/Wind Harmer
5.299
3147346CASHSCORNER
Solar/Wind Harmer
0.35
972193AH1-681 GEN
Adder
3.331
316123AC1-075 GEN
Solar/Wind Harmer
0.191
970165AG2-112 GEN
Solar/Wind Harmer
1.134
970163AG2-111 GEN
Solar/Wind Harmer
1.081
270494AE1-108_GEN
Solar/Wind Harmer
1.679
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.804
316415AF1-147_GEN2
Solar/Wind Helper
0.804
3138216PACIFIC
Solar/Wind Helper
0.039
970909AG2-566 GEN
Solar/Wind Harmer
2.083
971781AH1-399 GEN
Solar/Wind Harmer
0.256
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315724AD1-057 GEN
Solar/Wind Harmer
0.72
316327AA2-057 GEN
Solar/Wind Harmer
0.287
316131AB2-060 GEN
Solar/Wind Harmer
0.595
964241AG1-285 GEN
Solar/Wind Harmer
12.61
315785AD2-033 C
Solar/Wind Harmer
1.535
970257AG2-171 GEN
Solar/Wind Harmer
6.039
959311AF2-222 GEN
Solar/Wind Harmer
16.767
963181AG1-167 GEN
Solar/Wind Harmer
0.752
3144293JTRSVLE
Adder
0.599
3147133PAMPLIN
Solar/Wind Harmer
0.59
971193AH1-056 GEN
Solar/Wind Harmer
11.443
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.938
3146233WITAKRS
Solar/Wind Harmer
0.127
3146926FARMVIL
Solar/Wind Harmer
0.112
3146073TAR RVR
Solar/Wind Harmer
0.186
3146083TARBORO
Solar/Wind Harmer
0.186
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.049
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.183
971623AH1-311 GEN
Solar/Wind Harmer
0.367
3141906WESTMOR
Solar/Wind Harmer
0.072
3146776BUCKING
Solar/Wind Harmer
0.064
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.36
970737AG2-469 GEN
Solar/Wind Harmer
7.314
971683AH1-343 GEN
Solar/Wind Harmer
5.86
3151761LOISA E
Adder
21.054
970221AG2-151 GEN
Solar/Wind Harmer
8.48
3132273ORANGE
Solar/Wind Harmer
0.031
316283AC2-100 C
Solar/Wind Harmer
0.304
972183AH1-676 GEN
Adder
164.313
972255AH1-712 GEN
Adder
74.545
316170AC1-121 GEN2
Solar/Wind Harmer
0.13
3141316ARNOLDS
Adder
0.285
3141196NOKESVL
Solar/Wind Helper
1.139
316274AC1-208 GEN
Solar/Wind Harmer
1.016
970301AG2-198 GEN
Solar/Wind Harmer
8.333
316468AD1-105 GEN
Solar/Wind Harmer
-0.063
939181AE1-148 GEN
Solar/Wind Harmer
9.137
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.051
971775AH1-396 GEN
Solar/Wind Harmer
0.302
958211AF2-115 GEN
Solar/Wind Harmer
2.257
963191AG1-168 GEN
Solar/Wind Harmer
0.752
3144293JTRSVLE
Adder
0.599
3144293JTRSVLE
Adder
0.504
3147133PAMPLIN
Solar/Wind Harmer
0.188
3147133PAMPLIN
Solar/Wind Harmer
0.15
3145493TOT1
Solar/Wind Harmer
0.432
3145453TOT5
Solar/Wind Harmer
0.259
3145603CNETO
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
3.262
316263AC1-034 GEN
Solar/Wind Harmer
6.97
962561AG1-105 GEN
Solar/Wind Harmer
8.691
964791AG1-342 GEN
Solar/Wind Harmer
3.448
3146843MT LREL
Solar/Wind Harmer
0.179
3146843MT LREL
Solar/Wind Harmer
0.179
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
3151731LOISA B
Adder
10.327
3151721LOISA A
Adder
10.274
971489AH1-241 GEN
Solar/Wind Harmer
8.48
316222AC1-221 GEN
Solar/Wind Harmer
0.648
966001AG1-469 GEN
Solar/Wind Harmer
0.09
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.158
CPLELTFEXP_CPLE->PJM
CLTF
11.88
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.966
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.76
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.813
MECLTFEXP_MEC->PJM
CLTF
3.485
SIGELTFEXP_SIGE->PJM
CLTF
0.106
NYPJM->LTFIMP_NY
CLTF
3.369
LGEELTFEXP_LGEE->PJM
CLTF
1.264
WECLTFEXP_WEC->PJM
CLTF
0.603
LAGNLTFEXP_LAGN->PJM
CLTF
8.056
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.878
TVALTFEXP_TVA->PJM
CLTF
4.082

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.47 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3088.52
MW Contribution:0.95
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
230.289
3151081ELIZAR1
50/50
31.355
3151091ELIZAR2
50/50
30.811
941591AE2-156 GEN
50/50
28.547
3152611GOSPORTB
50/50
4.325
3152621GOSPORTC
50/50
3.671
3152601GOSPORTA
50/50
3.386
3151151S HAMPT1
50/50
0.676
957871AF2-081 GEN
Solar/Wind Harmer
15.948
319010AE1-072 C
Solar/Wind Harmer
1.603
3146406KITTY HAWK
Solar/Wind Harmer
0.04
313526AB2-022
Solar/Wind Harmer
0.168
316305AF2-043 C
Solar/Wind Harmer
0.002
316321Z2-027
Solar/Wind Harmer
0.057
3146396TANGLEW
Solar/Wind Harmer
0.848
3145176PASQUOTANK
Solar/Wind Harmer
0.191
3146486SUNBURY
Solar/Wind Harmer
0.305
3146486SUNBURY
Solar/Wind Harmer
0.305
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
2.004
3130156CHOWAN
Solar/Wind Harmer
0.285
3130156CHOWAN
Solar/Wind Harmer
0.285
315816AE2-034 GEN
Solar/Wind Harmer
1.171
971445AH1-216 GEN
Solar/Wind Harmer
18.76
3130546PLYMOUTH
Solar/Wind Harmer
0.263
315732AD1-074 GEN1
Solar/Wind Harmer
1.502
315733AD1-074 GEN2
Solar/Wind Harmer
1.502
315735AD1-075 GEN1
Solar/Wind Harmer
0.752
316311AC2-079 GEN
Solar/Wind Harmer
7.464
3152331SURRY 2
50/50
17.368
3150981CHESPKA
50/50
4.243
970017AG2-010 GEN
50/50
18.294
316294AC1-161 GEN
Solar/Wind Harmer
6.51
944591AF1-124 GEN
Solar/Wind Harmer
75.711
316388AE2-253 GEN
Solar/Wind Harmer
1.006
316375AC2-012 GEN
Solar/Wind Harmer
0.008
3146456SLIGO L269
Solar/Wind Harmer
0.319
316246AF1-032 C
Solar/Wind Harmer
0.139
3146516WINFALL
Solar/Wind Harmer
0.976
3146516WINFALL
Solar/Wind Harmer
0.301
939411AE1-173 GEN
Solar/Wind Harmer
127.856
316072AD1-144
Solar/Wind Harmer
0.107
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
316093AE2-104_GEN
Solar/Wind Harmer
4.912
940641AE2-051 GEN
Solar/Wind Harmer
23.236
3130156CHOWAN
Solar/Wind Harmer
0.285
3145663CRESWEL
Solar/Wind Harmer
0.763
971163AH1-040 GEN
Solar/Wind Harmer
21.824
3145336SMITFLD
Solar/Wind Harmer
1.077
3138126ROCKLANDING
Solar/Wind Harmer
0.123
3150991CHESPKB
50/50
3.559
3150991CHESPKB
50/50
3.474
970533AG2-339 GEN
50/50
23.054
970531AG2-338 GEN
50/50
9.222
316185AD1-033 GEN
Solar/Wind Harmer
0.009
3145506HICKORY
Solar/Wind Harmer
1.295
3145506HICKORY
Solar/Wind Harmer
0.777
3145506HICKORY
Solar/Wind Harmer
0.194
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.309
316339AD2-160 GEN
Solar/Wind Harmer
0.521
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.179
316036AC1-147 C
Solar/Wind Harmer
0.06
3137176SLIGO L2192
Solar/Wind Harmer
1.269
3146456SLIGO L269
Solar/Wind Harmer
5.642
3130086AYDLETT
Solar/Wind Harmer
1.271
3146386ELIZ CT
Solar/Wind Harmer
0.311
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146626S HERTFORD
Solar/Wind Harmer
0.297
3146626S HERTFORD
Solar/Wind Harmer
0.297
3146376EDENTON
Solar/Wind Harmer
1.268
3146376EDENTON
Solar/Wind Harmer
1.268
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316236AE1-162_GEN
Solar/Wind Harmer
0.002
941031AE2-094 GEN
Solar/Wind Harmer
47.768
944011AF1-069 GEN
Solar/Wind Harmer
15.607
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.178
3151101ELIZAR3
50/50
31.757
3150921YORKTN3
50/50
7.207
3144216WINCHST
50/50
1.069
3151161SURRY 1
50/50
9.11
315773AC2-141 GEN
Solar/Wind Harmer
13.721
944581AF1-123 GEN
Solar/Wind Harmer
75.443
944601AF1-125 GEN
Solar/Wind Harmer
74.281
3144873MCLAUGH
Solar/Wind Harmer
0.008
3146456SLIGO L269
Solar/Wind Harmer
0.319
971153AH1-033 GEN
Solar/Wind Harmer
3.686
316320Y1-086
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.046
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.301
3146626S HERTFORD
Solar/Wind Harmer
0.297
3146376EDENTON
Solar/Wind Harmer
0.285
3145273HOLLAND
Solar/Wind Harmer
0.208
315614AA2-178 GEN
Solar/Wind Harmer
1.561
3145336SMITFLD
Solar/Wind Harmer
0.108
971157AH1-035 GEN
Solar/Wind Harmer
3.159
315737AD1-076 GEN
Solar/Wind Harmer
3.364
3146206CASHIE
Solar/Wind Harmer
0.254
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.109
3145893MURPHYS
Solar/Wind Harmer
0.405
3145893MURPHYS
Solar/Wind Harmer
0.242
957521AF2-046 GEN
Solar/Wind Harmer
17.957
961681AG1-008 GEN
Solar/Wind Harmer
17.957
3145963POPLR C
Solar/Wind Harmer
0.241
3146173TUNIS
Solar/Wind Harmer
0.24
316463AE2-346 GEN
Solar/Wind Harmer
0.205
316140AB2-099
Solar/Wind Harmer
0.085
962331AG1-082 GEN
Solar/Wind Harmer
2.55
3151221GRAVEL6
Adder
17.243
3151171GRAVELC
Adder
3.318
970917AG2-570 GEN
Solar/Wind Harmer
21.013
3146263WOODLND
Solar/Wind Harmer
0.231
316317KELFORD C
Solar/Wind Harmer
0.022
3145823KELFORD
Solar/Wind Harmer
0.229
3145933PARMELE
Solar/Wind Harmer
0.223
966801AG1-551 GEN
Solar/Wind Harmer
2.598
970661AG2-428 GEN
Solar/Wind Harmer
4.701
3142666NORTHAMPTON
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.215
3145746EVERETS
Solar/Wind Harmer
0.215
961611AG1-000B GEN
Solar/Wind Harmer
5.702
316210AC1-098 GEN
Solar/Wind Harmer
1.973
3145796HORNRTN
Solar/Wind Harmer
0.836
3145796HORNRTN
Solar/Wind Harmer
0.209
316365GEN2_N
Solar/Wind Harmer
0.469
313506AB2-031 GEN
Solar/Wind Harmer
0.643
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.136
316327AA2-057 GEN
Solar/Wind Harmer
0.304
3146206CASHIE
Solar/Wind Harmer
0.254
971547AH1-271 GEN
Solar/Wind Harmer
5.427
971317AH1-138 GEN
Solar/Wind Harmer
1.823
3145893MURPHYS
Solar/Wind Harmer
0.967
3145893MURPHYS
Solar/Wind Harmer
1.075
3145963POPLR C
Solar/Wind Harmer
0.241
3146173TUNIS
Solar/Wind Harmer
0.24
3146206CASHIE
Solar/Wind Harmer
0.254
970601AG2-382 GEN
Solar/Wind Harmer
9.497
970673AG2-436 GEN
Solar/Wind Harmer
54.074
970673AG2-436 GEN
Solar/Wind Harmer
36.049
971967AH1-528 GEN
Solar/Wind Harmer
39.527
965291AG1-394 GEN
Solar/Wind Harmer
1.083
3145893MURPHYS
Solar/Wind Harmer
0.653
3145893MURPHYS
Solar/Wind Harmer
0.242
3145513AHOSKIE
Solar/Wind Harmer
0.5
3145513AHOSKIE
Solar/Wind Harmer
0.239
3145683EARLEYS
Solar/Wind Harmer
0.476
3145683EARLEYS
Solar/Wind Harmer
0.238
3145683EARLEYS
Solar/Wind Harmer
0.238
972265AH1-717 GEN
Adder
18.416
3151201GRAVEL4
Adder
17.263
3151191GRAVEL3
Adder
17.045
3151211GRAVEL5
Adder
17.045
970085AG2-068 GEN
Solar/Wind Harmer
12.547
970581AG2-369 GEN
Solar/Wind Harmer
10.791
3146043SEABORD
Solar/Wind Harmer
0.227
315607AA1-063A GEN
Solar/Wind Harmer
0.459
3146033SCOT NK
Solar/Wind Harmer
0.88
316005AA1-067
Solar/Wind Harmer
0.23
3145746EVERETS
Solar/Wind Harmer
0.854
3145746EVERETS
Solar/Wind Harmer
0.215
3145746EVERETS
Solar/Wind Harmer
0.215
3145746EVERETS
Solar/Wind Harmer
0.215
970181AG2-120 GEN
Solar/Wind Harmer
2.673
315652AC1-086 GEN
Solar/Wind Harmer
23.319
3137643SOCKMAN
Solar/Wind Harmer
0.841
3145796HORNRTN
Solar/Wind Harmer
0.669
3145796HORNRTN
Solar/Wind Harmer
0.084
316087AB2-174 GEN
Solar/Wind Harmer
0.006
957861AF2-080 GEN
Solar/Wind Harmer
8.925
315814AE2-033 C
Solar/Wind Harmer
16.342
316315AB2-025 C
Solar/Wind Harmer
0.167
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.2
3145573BETHELC
Solar/Wind Harmer
0.2
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
8.311
3138283WHITEMARSH
Solar/Wind Harmer
0.045
316369SG1_INVT
Solar/Wind Harmer
0.007
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3143316POE
Solar/Wind Harmer
0.643
316118AC1-105 GEN
Solar/Wind Harmer
0.419
3147173SINAI
Solar/Wind Harmer
0.161
3147243WELCO
Solar/Wind Harmer
0.1
971443AH1-215 GEN
Solar/Wind Harmer
2.584
3144303KENBRDG
Solar/Wind Harmer
0.122
970683AG2-441 GEN
Solar/Wind Harmer
9.746
970681AG2-440 GEN
Solar/Wind Harmer
7.797
316132AB2-190 GEN1
Solar/Wind Harmer
0.757
946301AF1-294 GEN
Solar/Wind Harmer
2.754
961791AG1-021 GEN
Solar/Wind Harmer
1.34
315657AE1-056 GEN
Solar/Wind Harmer
4.655
970865AG2-541 GEN
Solar/Wind Harmer
4.665
316123AC1-075 GEN
Solar/Wind Harmer
0.16
970165AG2-112 GEN
Solar/Wind Harmer
0.951
970163AG2-111 GEN
Solar/Wind Harmer
0.907
3146073TAR RVR
Solar/Wind Harmer
0.2
3146083TARBORO
Solar/Wind Harmer
0.2
315724AD1-057 GEN
Solar/Wind Harmer
0.749
316478AD1-087 GEN
Solar/Wind Harmer
0.693
316486AD2-202 GEN
Solar/Wind Harmer
0.204
3146233WITAKRS
Solar/Wind Harmer
0.987
3146233WITAKRS
Solar/Wind Harmer
0.134
3138543CONSLDL
Solar/Wind Harmer
0.129
3147043LAWRENC
Solar/Wind Harmer
0.116
961601AG1-000A GEN
Solar/Wind Harmer
13.669
3145543BTLEBRO
Solar/Wind Harmer
0.192
3145543BTLEBRO
Solar/Wind Harmer
0.192
971623AH1-311 GEN
Solar/Wind Harmer
0.384
316382AG1-145 C
Solar/Wind Harmer
0.001
315813AE1-149 C
Solar/Wind Harmer
9.286
316131AB2-060 GEN
Solar/Wind Harmer
0.528
964241AG1-285 GEN
Solar/Wind Harmer
10.893
315778AD1-151 GEN
Solar/Wind Harmer
12.979
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.855
315785AD2-033 C
Solar/Wind Harmer
1.268
970257AG2-171 GEN
Solar/Wind Harmer
4.903
959311AF2-222 GEN
Solar/Wind Harmer
13.44
316283AC2-100 C
Solar/Wind Harmer
0.293
970909AG2-566 GEN
Solar/Wind Harmer
1.544
971683AH1-343 GEN
Solar/Wind Harmer
5.265
963181AG1-167 GEN
Solar/Wind Harmer
0.558
3144293JTRSVLE
Adder
0.444
970129AG2-093 GEN
Solar/Wind Harmer
8.316
3147133PAMPLIN
Solar/Wind Harmer
0.423
971193AH1-056 GEN
Solar/Wind Harmer
8.217
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
315839AE2-212 C
Solar/Wind Harmer
0.001
316065AD1-022 GEN
Solar/Wind Harmer
11.831
972185AH1-677 GEN
Adder
14.057
972187AH1-678 GEN
Adder
7.022
3145893MURPHYS
Solar/Wind Harmer
1.618
3145893MURPHYS
Solar/Wind Harmer
0.435
3146173TUNIS
Solar/Wind Harmer
0.24
3146173TUNIS
Solar/Wind Harmer
0.24
970933AG2-581 GEN
Solar/Wind Harmer
18.911
3145933PARMELE
Solar/Wind Harmer
0.446
3145933PARMELE
Solar/Wind Harmer
0.223
316426AA2-053 GEN
Solar/Wind Harmer
0.733
3142666NORTHAMPTON
Solar/Wind Harmer
0.216
3142666NORTHAMPTON
Solar/Wind Harmer
0.216
3142666NORTHAMPTON
Solar/Wind Harmer
0.216
3142666NORTHAMPTON
Solar/Wind Harmer
0.13
970657AG2-426 GEN
Solar/Wind Harmer
7.454
970657AG2-426 GEN
Solar/Wind Harmer
1.563
3145593CAROLNA
Solar/Wind Harmer
0.213
3145593CAROLNA
Solar/Wind Harmer
0.213
966811AG1-552 GEN
Solar/Wind Harmer
2.307
3145593CAROLNA
Solar/Wind Harmer
0.265
3145783HORNRTN
Solar/Wind Harmer
3.768
3145783HORNRTN
Solar/Wind Harmer
3.015
3145783HORNRTN
Solar/Wind Harmer
0.942
3145783HORNRTN
Solar/Wind Harmer
0.377
970099AG2-077 GEN
Solar/Wind Harmer
22.381
3145796HORNRTN
Solar/Wind Harmer
0.627
316181AB2-040 GEN
Solar/Wind Harmer
0.302
316274AC1-208 GEN
Solar/Wind Harmer
1.08
3144356SAPONY
Solar/Wind Harmer
1.726
3145493TOT1
Solar/Wind Harmer
0.464
3145453TOT5
Solar/Wind Harmer
0.279
3145603CNETO
Solar/Wind Harmer
0.186
961601AG1-000A GEN
Solar/Wind Harmer
3.417
316263AC1-034 GEN
Solar/Wind Harmer
7.3
939181AE1-148 GEN
Solar/Wind Harmer
8.634
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.199
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.914
964791AG1-342 GEN
Solar/Wind Harmer
3.152
3146843MT LREL
Solar/Wind Harmer
0.164
3146843MT LREL
Solar/Wind Harmer
0.164
971741AH1-377 GEN
Solar/Wind Harmer
15.521
970323AG2-213 GEN
Solar/Wind Harmer
6.537
971775AH1-396 GEN
Solar/Wind Harmer
0.245
316034AC1-036 C
Solar/Wind Harmer
0.011
316222AC1-221 GEN
Solar/Wind Harmer
0.625
970301AG2-198 GEN
Solar/Wind Harmer
6.178
958211AF2-115 GEN
Solar/Wind Harmer
1.675
963191AG1-168 GEN
Solar/Wind Harmer
0.558
3144293JTRSVLE
Adder
0.444
3144293JTRSVLE
Adder
0.374
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
3145683EARLEYS
Solar/Wind Harmer
0.238
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3151171GRAVELC
Adder
2.523
970919AG2-571 GEN
Solar/Wind Harmer
8.405
970087AG2-069 GEN
Solar/Wind Harmer
18.821
3146263WOODLND
Solar/Wind Harmer
0.231
3145823KELFORD
Solar/Wind Harmer
0.229
3146293MARTNCO
Solar/Wind Harmer
0.207
970661AG2-428 GEN
Solar/Wind Harmer
22.103
316190AA2-174 GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.215
3145746EVERETS
Solar/Wind Harmer
0.215
961611AG1-000B GEN
Solar/Wind Harmer
11.214
316212AC1-099_GEN
Solar/Wind Harmer
1.1
316011AB1-132 GEN
Solar/Wind Harmer
3.854
962571AG1-106 GEN
Solar/Wind Harmer
3.016
3145783HORNRTN
Solar/Wind Harmer
0.212
957481AF2-042 GEN
Solar/Wind Harmer
55.952
3145796HORNRTN
Solar/Wind Harmer
0.69
3145796HORNRTN
Solar/Wind Harmer
0.209
316023GEN1_S
Solar/Wind Harmer
0.469
316381AD1-082 GEN
Solar/Wind Harmer
0.216
316494AC1-189 GEN
Solar/Wind Harmer
0.699
960081AF2-299 GEN
Solar/Wind Harmer
1.961
970659AG2-427 GEN
Solar/Wind Harmer
9.765
961671AG1-007 GEN
Solar/Wind Harmer
0.031
3146083TARBORO
Solar/Wind Harmer
0.2
3145493TOT1
Solar/Wind Harmer
0.891
315722AD1-056 GEN
Solar/Wind Harmer
1.264
971795AH1-408 GEN
Solar/Wind Harmer
13.128
3146233WITAKRS
Solar/Wind Harmer
0.783
315693AD1-088 GEN
Solar/Wind Harmer
9.393
971647AH1-324 GEN
Solar/Wind Harmer
8.33
3147043LAWRENC
Adder
1.751
962491AG1-098 GEN
Solar/Wind Harmer
11.017
316129AC1-054 GEN
Solar/Wind Harmer
0.725
3145543BTLEBRO
Solar/Wind Harmer
0.192
3145543BTLEBRO
Solar/Wind Harmer
0.154
316359AB2-059 GEN
Solar/Wind Harmer
0.69
316049AB1-081 GEN
Solar/Wind Harmer
1.099
3142053HEARTS
Solar/Wind Harmer
0.338
971065AG2-659 GEN
Solar/Wind Harmer
8.154
316159AE1-175 C
Solar/Wind Harmer
0.162
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.963
971069AG2-661 GEN
Solar/Wind Harmer
2.884
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
10.916
316458AB2-190 GEN2
Solar/Wind Harmer
0.757
963171AG1-166 GEN
Solar/Wind Harmer
0.744
971563AH1-280 GEN
Solar/Wind Harmer
1.489
3144293JTRSVLE
Adder
0.444
970129AG2-093 GEN
Solar/Wind Harmer
3.913
CPLELTFEXP_CPLE->PJM
CLTF
11.714
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.575
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.74
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.561
MECLTFEXP_MEC->PJM
CLTF
2.893
SIGELTFEXP_SIGE->PJM
CLTF
0.084
NYPJM->LTFIMP_NY
CLTF
1.821
LGEELTFEXP_LGEE->PJM
CLTF
0.973
WECLTFEXP_WEC->PJM
CLTF
0.495
LAGNLTFEXP_LAGN->PJM
CLTF
6.928
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.334
TVALTFEXP_TVA->PJM
CLTF
3.444

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.0 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1248.61
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.758
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.223
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.765
971967AH1-528 GEN
Solar/Wind Harmer
100.698
970865AG2-541 GEN
Solar/Wind Harmer
19.076
316123AC1-075 GEN
Solar/Wind Harmer
4.171
970165AG2-112 GEN
Solar/Wind Harmer
3.672
970163AG2-111 GEN
Solar/Wind Harmer
3.503
316239AB2-077_GEN
Solar/Wind Harmer
1.108
316238AB2-078_GEN
Solar/Wind Harmer
1.108
971443AH1-215 GEN
Solar/Wind Harmer
6.88
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.727
970681AG2-440 GEN
Solar/Wind Harmer
21.381
946301AF1-294 GEN
Solar/Wind Harmer
8.604
961791AG1-021 GEN
Solar/Wind Harmer
4.197
315657AE1-056 GEN
Solar/Wind Harmer
12.423
970285AG2-188 GEN
Solar/Wind Harmer
21.434
971845AH1-439 GEN
Solar/Wind Harmer
12.337
970831AG2-522 GEN
Solar/Wind Harmer
10.013
3151531CLOVER1
50/50
10.81
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.435
970413AG2-270 GEN
50/50
47.174
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.071
316248AF1-058 C
Solar/Wind Harmer
1.793
960061AF2-297 GEN
Solar/Wind Harmer
29.749
316478AD1-087 GEN
Solar/Wind Harmer
4.929
316486AD2-202 GEN
Solar/Wind Harmer
1.444
971683AH1-343 GEN
Solar/Wind Harmer
22.008
970909AG2-566 GEN
Solar/Wind Harmer
3.699
316131AB2-060 GEN
Solar/Wind Harmer
3.917
964241AG1-285 GEN
Solar/Wind Harmer
28.021
315785AD2-033 C
Solar/Wind Harmer
7.969
970257AG2-171 GEN
Solar/Wind Harmer
13.085
959311AF2-222 GEN
Solar/Wind Harmer
36.211
963181AG1-167 GEN
Solar/Wind Harmer
3.148
3147133PAMPLIN
Solar/Wind Harmer
-0.104
971193AH1-056 GEN
Solar/Wind Harmer
20.705
942461AE2-259 GEN
Solar/Wind Harmer
4.788
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.525
970221AG2-151 GEN
Solar/Wind Harmer
7.265
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.614
316313AB2-026
Solar/Wind Harmer
0.176
316258AE1-075 C
Solar/Wind Harmer
0.158
316405AF2-144 C
Solar/Wind Harmer
0.167
3143336POWHATN
Solar/Wind Harmer
0.657
316283AC2-100 C
Solar/Wind Helper
2.324
3152661PLYWOOD A
50/50
1.086
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.15
316222AC1-221 GEN
Solar/Wind Harmer
10.229
970099AG2-077 GEN
Solar/Wind Harmer
67.902
970933AG2-581 GEN
Solar/Wind Harmer
50.214
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.644
962561AG1-105 GEN
Solar/Wind Harmer
26.877
971741AH1-377 GEN
Solar/Wind Harmer
48.375
970301AG2-198 GEN
Solar/Wind Harmer
19.484
313527AB2-043 GEN
Solar/Wind Harmer
5.914
970323AG2-213 GEN
Solar/Wind Harmer
17.447
971775AH1-396 GEN
Solar/Wind Harmer
2.485
316034AC1-036 C
Solar/Wind Harmer
0.647
958211AF2-115 GEN
Solar/Wind Harmer
5.246
963191AG1-168 GEN
Solar/Wind Harmer
3.148
942751AE2-291 GEN
Solar/Wind Harmer
21.29
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.128
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.959
316197AC1-042 GEN
Solar/Wind Harmer
1.485
942671AE2-283 GEN
Solar/Wind Harmer
3.997
971489AH1-241 GEN
Solar/Wind Harmer
6.897
315821AE2-092 GEN
Solar/Wind Harmer
1.796
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.786
3145593CAROLNA
Solar/Wind Harmer
0.058
971447AH1-217 GEN
Solar/Wind Harmer
3.92
270494AE1-108_GEN
Solar/Wind Harmer
2.506
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.115
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.376
270457AD2-023 GEN
Solar/Wind Helper
0.907
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
315687AD1-152 GEN
Solar/Wind Harmer
7.754
316003AC1-222 GEN
Solar/Wind Harmer
5.366
957481AF2-042 GEN
Solar/Wind Harmer
169.755
315693AD1-088 GEN
Solar/Wind Harmer
25.249
962491AG1-098 GEN
Solar/Wind Harmer
33.372
970401AG2-262 GEN
Solar/Wind Harmer
3.252
316237AB2-079_GEN
Solar/Wind Harmer
1.108
970685AG2-442 GEN
Solar/Wind Harmer
29.934
963171AG1-166 GEN
Solar/Wind Harmer
4.197
971563AH1-280 GEN
Solar/Wind Harmer
4.197
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.353
316322AB2-045
Solar/Wind Harmer
0.758
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.877
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.335
971795AH1-408 GEN
Solar/Wind Harmer
10.57
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.525
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.555
960081AF2-299 GEN
Solar/Wind Harmer
0.925
316336AC2-165 C
Solar/Wind Harmer
1.327
3143336POWHATN
Solar/Wind Harmer
0.773
G-007ALTFEXP_G-007A->PJM
CMTX
0.429
VTFLTFEXP_VFT->PJM
CMTX
1.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.809
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.962
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.375
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.85
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.677
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.45 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1220.46
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.738
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.237
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.757
971967AH1-528 GEN
Solar/Wind Harmer
100.512
970865AG2-541 GEN
Solar/Wind Harmer
19.031
316123AC1-075 GEN
Solar/Wind Harmer
4.16
970165AG2-112 GEN
Solar/Wind Harmer
3.663
970163AG2-111 GEN
Solar/Wind Harmer
3.494
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.867
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.682
970681AG2-440 GEN
Solar/Wind Harmer
21.345
946301AF1-294 GEN
Solar/Wind Harmer
8.59
961791AG1-021 GEN
Solar/Wind Harmer
4.19
315657AE1-056 GEN
Solar/Wind Harmer
12.405
970285AG2-188 GEN
Solar/Wind Harmer
21.428
971845AH1-439 GEN
Solar/Wind Harmer
12.335
970831AG2-522 GEN
Solar/Wind Harmer
9.984
971447AH1-217 GEN
Solar/Wind Harmer
3.931
270494AE1-108_GEN
Solar/Wind Harmer
2.509
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.116
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.395
270457AD2-023 GEN
Solar/Wind Helper
0.919
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.137
316222AC1-221 GEN
Solar/Wind Harmer
10.209
970099AG2-077 GEN
Solar/Wind Harmer
67.776
970933AG2-581 GEN
Solar/Wind Harmer
50.121
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.622
962561AG1-105 GEN
Solar/Wind Harmer
26.822
971741AH1-377 GEN
Solar/Wind Harmer
48.301
970301AG2-198 GEN
Solar/Wind Harmer
19.456
313527AB2-043 GEN
Solar/Wind Harmer
5.902
970323AG2-213 GEN
Solar/Wind Harmer
17.415
971775AH1-396 GEN
Solar/Wind Harmer
2.48
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.238
963191AG1-168 GEN
Solar/Wind Harmer
3.143
942751AE2-291 GEN
Solar/Wind Harmer
21.229
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.08
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.947
316197AC1-042 GEN
Solar/Wind Harmer
1.476
942671AE2-283 GEN
Solar/Wind Harmer
3.973
971489AH1-241 GEN
Solar/Wind Harmer
6.915
315821AE2-092 GEN
Solar/Wind Harmer
1.803
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
970413AG2-270 GEN
50/50
47.085
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.074
316248AF1-058 C
Solar/Wind Harmer
1.789
960061AF2-297 GEN
Solar/Wind Harmer
29.687
316478AD1-087 GEN
Solar/Wind Harmer
4.92
316486AD2-202 GEN
Solar/Wind Harmer
1.441
971683AH1-343 GEN
Solar/Wind Harmer
21.959
970909AG2-566 GEN
Solar/Wind Harmer
3.694
316131AB2-060 GEN
Solar/Wind Harmer
3.909
964241AG1-285 GEN
Solar/Wind Harmer
27.966
315785AD2-033 C
Solar/Wind Harmer
7.954
970257AG2-171 GEN
Solar/Wind Harmer
13.061
959311AF2-222 GEN
Solar/Wind Harmer
36.146
963181AG1-167 GEN
Solar/Wind Harmer
3.143
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.674
942461AE2-259 GEN
Solar/Wind Harmer
4.782
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.498
970221AG2-151 GEN
Solar/Wind Harmer
7.284
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.615
316313AB2-026
Solar/Wind Harmer
0.178
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.169
3143336POWHATN
Solar/Wind Harmer
0.666
316283AC2-100 C
Solar/Wind Helper
2.343
270018AE2-047 C O1
Solar/Wind Helper
0.4
3151531CLOVER1
50/50
10.79
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.434
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.386
3151911BEARGRDN G1
50/50
1.074
315687AD1-152 GEN
Solar/Wind Harmer
7.739
316003AC1-222 GEN
Solar/Wind Harmer
5.355
957481AF2-042 GEN
Solar/Wind Harmer
169.439
315693AD1-088 GEN
Solar/Wind Harmer
25.203
962491AG1-098 GEN
Solar/Wind Harmer
33.312
970401AG2-262 GEN
Solar/Wind Harmer
3.246
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.883
963171AG1-166 GEN
Solar/Wind Harmer
4.19
971563AH1-280 GEN
Solar/Wind Harmer
4.19
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.32
316322AB2-045
Solar/Wind Harmer
0.758
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.872
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.349
971795AH1-408 GEN
Solar/Wind Harmer
10.568
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.498
971377AH1-170 GEN
Solar/Wind Harmer
1.457
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.594
960081AF2-299 GEN
Solar/Wind Harmer
0.927
316336AC2-165 C
Solar/Wind Harmer
1.341
3143336POWHATN
Solar/Wind Harmer
0.784
G-007ALTFEXP_G-007A->PJM
CMTX
0.522
VTFLTFEXP_VFT->PJM
CMTX
1.375
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.857
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.505
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.08
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.476
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.869
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.738
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.42 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1220.19
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.738
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.237
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.757
971967AH1-528 GEN
Solar/Wind Harmer
100.512
970865AG2-541 GEN
Solar/Wind Harmer
19.031
316123AC1-075 GEN
Solar/Wind Harmer
4.16
970165AG2-112 GEN
Solar/Wind Harmer
3.663
970163AG2-111 GEN
Solar/Wind Harmer
3.494
316239AB2-077_GEN
Solar/Wind Harmer
1.105
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.137
316222AC1-221 GEN
Solar/Wind Harmer
10.209
970099AG2-077 GEN
Solar/Wind Harmer
67.776
970933AG2-581 GEN
Solar/Wind Harmer
50.121
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.622
962561AG1-105 GEN
Solar/Wind Harmer
26.822
971741AH1-377 GEN
Solar/Wind Harmer
48.301
970301AG2-198 GEN
Solar/Wind Harmer
19.456
313527AB2-043 GEN
Solar/Wind Harmer
5.902
970323AG2-213 GEN
Solar/Wind Harmer
17.415
971775AH1-396 GEN
Solar/Wind Harmer
2.48
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.238
963191AG1-168 GEN
Solar/Wind Harmer
3.143
942751AE2-291 GEN
Solar/Wind Harmer
21.229
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.08
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.947
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.867
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.682
970681AG2-440 GEN
Solar/Wind Harmer
21.345
946301AF1-294 GEN
Solar/Wind Harmer
8.59
961791AG1-021 GEN
Solar/Wind Harmer
4.19
315657AE1-056 GEN
Solar/Wind Harmer
12.405
970285AG2-188 GEN
Solar/Wind Harmer
21.428
971845AH1-439 GEN
Solar/Wind Harmer
12.335
970831AG2-522 GEN
Solar/Wind Harmer
9.984
970413AG2-270 GEN
50/50
47.085
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.074
316248AF1-058 C
Solar/Wind Harmer
1.789
960061AF2-297 GEN
Solar/Wind Harmer
29.687
316478AD1-087 GEN
Solar/Wind Harmer
4.92
316486AD2-202 GEN
Solar/Wind Harmer
1.441
971683AH1-343 GEN
Solar/Wind Harmer
21.959
970909AG2-566 GEN
Solar/Wind Harmer
3.694
316131AB2-060 GEN
Solar/Wind Harmer
3.909
964241AG1-285 GEN
Solar/Wind Harmer
27.966
315785AD2-033 C
Solar/Wind Harmer
7.954
970257AG2-171 GEN
Solar/Wind Harmer
13.061
959311AF2-222 GEN
Solar/Wind Harmer
36.146
963181AG1-167 GEN
Solar/Wind Harmer
3.143
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.674
942461AE2-259 GEN
Solar/Wind Harmer
4.782
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3151531CLOVER1
50/50
10.79
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.434
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.386
3151911BEARGRDN G1
50/50
1.074
315687AD1-152 GEN
Solar/Wind Harmer
7.739
316003AC1-222 GEN
Solar/Wind Harmer
5.355
957481AF2-042 GEN
Solar/Wind Harmer
169.439
315693AD1-088 GEN
Solar/Wind Harmer
25.203
962491AG1-098 GEN
Solar/Wind Harmer
33.312
970401AG2-262 GEN
Solar/Wind Harmer
3.246
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.883
963171AG1-166 GEN
Solar/Wind Harmer
4.19
971563AH1-280 GEN
Solar/Wind Harmer
4.19
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.32
316322AB2-045
Solar/Wind Harmer
0.758
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.872
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.349
971795AH1-408 GEN
Solar/Wind Harmer
10.568
971447AH1-217 GEN
Solar/Wind Harmer
3.931
270494AE1-108_GEN
Solar/Wind Harmer
2.509
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.116
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.395
270457AD2-023 GEN
Solar/Wind Helper
0.919
316197AC1-042 GEN
Solar/Wind Harmer
1.476
942671AE2-283 GEN
Solar/Wind Harmer
3.973
971489AH1-241 GEN
Solar/Wind Harmer
6.915
315821AE2-092 GEN
Solar/Wind Harmer
1.803
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.498
970221AG2-151 GEN
Solar/Wind Harmer
7.284
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.615
316313AB2-026
Solar/Wind Harmer
0.178
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.169
3143336POWHATN
Solar/Wind Harmer
0.666
316283AC2-100 C
Solar/Wind Helper
2.343
270018AE2-047 C O1
Solar/Wind Helper
0.4
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.498
971377AH1-170 GEN
Solar/Wind Harmer
1.457
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.594
960081AF2-299 GEN
Solar/Wind Harmer
0.927
316336AC2-165 C
Solar/Wind Harmer
1.341
3143336POWHATN
Solar/Wind Harmer
0.784
G-007ALTFEXP_G-007A->PJM
CMTX
0.522
VTFLTFEXP_VFT->PJM
CMTX
1.375
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.857
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.505
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.08
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.476
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.869
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.738
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1202.69
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.86
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.155
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.776
970865AG2-541 GEN
Solar/Wind Harmer
19.147
316123AC1-075 GEN
Solar/Wind Harmer
4.187
970165AG2-112 GEN
Solar/Wind Harmer
3.686
970163AG2-111 GEN
Solar/Wind Harmer
3.517
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.851
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.58
970681AG2-440 GEN
Solar/Wind Harmer
21.264
946301AF1-294 GEN
Solar/Wind Harmer
8.547
961791AG1-021 GEN
Solar/Wind Harmer
4.169
315657AE1-056 GEN
Solar/Wind Harmer
12.33
970285AG2-188 GEN
Solar/Wind Harmer
21.156
971845AH1-439 GEN
Solar/Wind Harmer
12.177
970831AG2-522 GEN
Solar/Wind Harmer
9.991
971447AH1-217 GEN
Solar/Wind Harmer
3.869
270494AE1-108_GEN
Solar/Wind Harmer
2.477
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.113
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.367
270457AD2-023 GEN
Solar/Wind Helper
0.901
970413AG2-270 GEN
50/50
47.618
3144293JTRSVLE
50/50
1.003
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.057
316248AF1-058 C
Solar/Wind Harmer
1.799
960061AF2-297 GEN
Solar/Wind Harmer
29.857
316478AD1-087 GEN
Solar/Wind Harmer
4.976
316486AD2-202 GEN
Solar/Wind Harmer
1.457
971683AH1-343 GEN
Solar/Wind Harmer
22.089
970909AG2-566 GEN
Solar/Wind Harmer
3.648
316131AB2-060 GEN
Solar/Wind Harmer
3.91
964241AG1-285 GEN
Solar/Wind Harmer
27.945
315785AD2-033 C
Solar/Wind Harmer
7.938
970257AG2-171 GEN
Solar/Wind Harmer
13.028
959311AF2-222 GEN
Solar/Wind Harmer
36.042
963181AG1-167 GEN
Solar/Wind Harmer
3.127
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.003
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.14
316222AC1-221 GEN
Solar/Wind Harmer
10.244
970099AG2-077 GEN
Solar/Wind Harmer
69.159
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.665
962561AG1-105 GEN
Solar/Wind Harmer
26.917
971741AH1-377 GEN
Solar/Wind Harmer
47.685
970301AG2-198 GEN
Solar/Wind Harmer
19.211
313527AB2-043 GEN
Solar/Wind Harmer
5.903
970323AG2-213 GEN
Solar/Wind Harmer
17.371
971775AH1-396 GEN
Solar/Wind Harmer
2.474
316034AC1-036 C
Solar/Wind Harmer
0.644
942751AE2-291 GEN
Solar/Wind Harmer
21.373
958211AF2-115 GEN
Solar/Wind Harmer
5.211
963191AG1-168 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.09
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.968
316197AC1-042 GEN
Solar/Wind Harmer
1.492
942671AE2-283 GEN
Solar/Wind Harmer
4.017
971489AH1-241 GEN
Solar/Wind Harmer
6.809
315821AE2-092 GEN
Solar/Wind Harmer
1.772
316181AB2-040 GEN
Solar/Wind Harmer
1.064
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.55
942461AE2-259 GEN
Solar/Wind Harmer
4.741
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.548
970221AG2-151 GEN
Solar/Wind Harmer
7.172
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.613
316313AB2-026
Solar/Wind Harmer
0.173
316258AE1-075 C
Solar/Wind Harmer
0.156
316405AF2-144 C
Solar/Wind Harmer
0.165
3143336POWHATN
Solar/Wind Harmer
0.648
316283AC2-100 C
Solar/Wind Helper
2.31
3151531CLOVER1
50/50
10.912
3144293JTRSVLE
50/50
1.003
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.433
3151561HALLBR1
50/50
0.349
3151931BEARGRDN S1
50/50
1.364
3151911BEARGRDN G1
50/50
1.057
315687AD1-152 GEN
Solar/Wind Harmer
7.805
957481AF2-042 GEN
Solar/Wind Harmer
172.899
316003AC1-222 GEN
Solar/Wind Harmer
5.386
970401AG2-262 GEN
Solar/Wind Harmer
3.259
315693AD1-088 GEN
Solar/Wind Harmer
24.873
962491AG1-098 GEN
Solar/Wind Harmer
32.876
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.769
963171AG1-166 GEN
Solar/Wind Harmer
4.169
971563AH1-280 GEN
Solar/Wind Harmer
4.169
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.328
316322AB2-045
Solar/Wind Harmer
0.749
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.873
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.24
971795AH1-408 GEN
Solar/Wind Harmer
10.551
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.548
971377AH1-170 GEN
Solar/Wind Harmer
1.434
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.455
960081AF2-299 GEN
Solar/Wind Harmer
0.924
316336AC2-165 C
Solar/Wind Harmer
1.309
3143336POWHATN
Solar/Wind Harmer
0.763
G-007ALTFEXP_G-007A->PJM
CMTX
0.408
VTFLTFEXP_VFT->PJM
CMTX
1.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.798
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.306
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.933
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.353
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.845
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.662
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1202.63
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.859
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.156
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.775
970865AG2-541 GEN
Solar/Wind Harmer
19.147
316123AC1-075 GEN
Solar/Wind Harmer
4.187
970165AG2-112 GEN
Solar/Wind Harmer
3.686
970163AG2-111 GEN
Solar/Wind Harmer
3.517
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.851
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.581
970681AG2-440 GEN
Solar/Wind Harmer
21.265
946301AF1-294 GEN
Solar/Wind Harmer
8.547
961791AG1-021 GEN
Solar/Wind Harmer
4.169
315657AE1-056 GEN
Solar/Wind Harmer
12.331
970285AG2-188 GEN
Solar/Wind Harmer
21.159
971845AH1-439 GEN
Solar/Wind Harmer
12.178
970831AG2-522 GEN
Solar/Wind Harmer
9.991
970413AG2-270 GEN
50/50
47.615
3144293JTRSVLE
50/50
1.003
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.057
316248AF1-058 C
Solar/Wind Harmer
1.799
960061AF2-297 GEN
Solar/Wind Harmer
29.856
316478AD1-087 GEN
Solar/Wind Harmer
4.975
316486AD2-202 GEN
Solar/Wind Harmer
1.457
971683AH1-343 GEN
Solar/Wind Harmer
22.089
970909AG2-566 GEN
Solar/Wind Harmer
3.648
316131AB2-060 GEN
Solar/Wind Harmer
3.91
964241AG1-285 GEN
Solar/Wind Harmer
27.945
315785AD2-033 C
Solar/Wind Harmer
7.938
970257AG2-171 GEN
Solar/Wind Harmer
13.029
959311AF2-222 GEN
Solar/Wind Harmer
36.043
963181AG1-167 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.551
942461AE2-259 GEN
Solar/Wind Harmer
4.741
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.548
970221AG2-151 GEN
Solar/Wind Harmer
7.173
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.613
316313AB2-026
Solar/Wind Harmer
0.173
316258AE1-075 C
Solar/Wind Harmer
0.156
316405AF2-144 C
Solar/Wind Harmer
0.165
3143336POWHATN
Solar/Wind Harmer
0.648
316283AC2-100 C
Solar/Wind Helper
2.31
971447AH1-217 GEN
Solar/Wind Harmer
3.87
270494AE1-108_GEN
Solar/Wind Harmer
2.477
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.113
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.367
270457AD2-023 GEN
Solar/Wind Helper
0.901
3151531CLOVER1
50/50
10.911
3144293JTRSVLE
50/50
1.003
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.433
3151561HALLBR1
50/50
0.349
3151931BEARGRDN S1
50/50
1.364
3151911BEARGRDN G1
50/50
1.057
315687AD1-152 GEN
Solar/Wind Harmer
7.805
957481AF2-042 GEN
Solar/Wind Harmer
172.875
316003AC1-222 GEN
Solar/Wind Harmer
5.386
970401AG2-262 GEN
Solar/Wind Harmer
3.259
315693AD1-088 GEN
Solar/Wind Harmer
24.876
962491AG1-098 GEN
Solar/Wind Harmer
32.88
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.77
963171AG1-166 GEN
Solar/Wind Harmer
4.169
971563AH1-280 GEN
Solar/Wind Harmer
4.169
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.328
316322AB2-045
Solar/Wind Harmer
0.749
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.873
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.24
971795AH1-408 GEN
Solar/Wind Harmer
10.551
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.548
971377AH1-170 GEN
Solar/Wind Harmer
1.435
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.456
960081AF2-299 GEN
Solar/Wind Harmer
0.924
316336AC2-165 C
Solar/Wind Harmer
1.309
3143336POWHATN
Solar/Wind Harmer
0.763
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.003
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.14
316222AC1-221 GEN
Solar/Wind Harmer
10.244
970099AG2-077 GEN
Solar/Wind Harmer
69.15
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.664
962561AG1-105 GEN
Solar/Wind Harmer
26.917
971741AH1-377 GEN
Solar/Wind Harmer
47.691
970301AG2-198 GEN
Solar/Wind Harmer
19.213
313527AB2-043 GEN
Solar/Wind Harmer
5.903
970323AG2-213 GEN
Solar/Wind Harmer
17.372
971775AH1-396 GEN
Solar/Wind Harmer
2.474
316034AC1-036 C
Solar/Wind Harmer
0.644
942751AE2-291 GEN
Solar/Wind Harmer
21.372
958211AF2-115 GEN
Solar/Wind Harmer
5.212
963191AG1-168 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.09
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.968
316197AC1-042 GEN
Solar/Wind Harmer
1.492
942671AE2-283 GEN
Solar/Wind Harmer
4.017
971489AH1-241 GEN
Solar/Wind Harmer
6.81
315821AE2-092 GEN
Solar/Wind Harmer
1.772
316181AB2-040 GEN
Solar/Wind Harmer
1.064
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
G-007ALTFEXP_G-007A->PJM
CMTX
0.409
VTFLTFEXP_VFT->PJM
CMTX
1.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.798
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.307
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.933
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.353
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.845
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.662
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.96 %
Rating:903.34 MVA
Rating Type:B
MVA to Mitigate:939.11
MW Contribution:2.79
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.758
970413AG2-270 GEN
50/50
47.174
3144293JTRSVLE
50/50
1.009
3151531CLOVER1
50/50
10.81
3144293JTRSVLE
50/50
1.009
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.223
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.258
971967AH1-528 GEN
Solar/Wind Harmer
76.276
970865AG2-541 GEN
Solar/Wind Harmer
14.488
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.789
970163AG2-111 GEN
Solar/Wind Harmer
2.661
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.225
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.299
970681AG2-440 GEN
Solar/Wind Harmer
16.239
946301AF1-294 GEN
Solar/Wind Harmer
5.897
961791AG1-021 GEN
Solar/Wind Harmer
2.869
315657AE1-056 GEN
Solar/Wind Harmer
10.169
970285AG2-188 GEN
Solar/Wind Harmer
17.248
971845AH1-439 GEN
Solar/Wind Harmer
9.37
970831AG2-522 GEN
Solar/Wind Harmer
7.605
971447AH1-217 GEN
Solar/Wind Harmer
2.977
270494AE1-108_GEN
Solar/Wind Harmer
1.028
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.259
270455AD2-022 GEN
Solar/Wind Helper
1.376
270457AD2-023 GEN
Solar/Wind Helper
0.907
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.071
3151261ROARAP2
50/50
0.076
24728405LEESVG
50/50
0.073
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.594
316478AD1-087 GEN
Solar/Wind Harmer
1.768
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.715
970909AG2-566 GEN
Solar/Wind Harmer
3.699
316131AB2-060 GEN
Solar/Wind Harmer
1.016
964241AG1-285 GEN
Solar/Wind Harmer
21.282
315785AD2-033 C
Solar/Wind Harmer
2.544
970257AG2-171 GEN
Solar/Wind Harmer
9.938
959311AF2-222 GEN
Solar/Wind Harmer
27.447
963181AG1-167 GEN
Solar/Wind Harmer
1.195
3147133PAMPLIN
Solar/Wind Harmer
0.925
971193AH1-056 GEN
Solar/Wind Harmer
17.953
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.163
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.437
970221AG2-151 GEN
Solar/Wind Harmer
5.518
313506AB2-031 GEN
Solar/Wind Harmer
0.21
316313AB2-026
Solar/Wind Harmer
0.037
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.876
316283AC2-100 C
Solar/Wind Helper
2.324
3152661PLYWOOD A
50/50
1.086
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.15
316222AC1-221 GEN
Solar/Wind Harmer
3.734
970099AG2-077 GEN
Solar/Wind Harmer
51.571
970933AG2-581 GEN
Solar/Wind Harmer
38.137
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.515
962561AG1-105 GEN
Solar/Wind Harmer
20.413
971741AH1-377 GEN
Solar/Wind Harmer
36.74
970301AG2-198 GEN
Solar/Wind Harmer
14.798
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.251
971775AH1-396 GEN
Solar/Wind Harmer
0.497
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.586
963191AG1-168 GEN
Solar/Wind Harmer
1.195
942751AE2-291 GEN
Solar/Wind Harmer
16.169
3147133PAMPLIN
Solar/Wind Harmer
0.295
3147133PAMPLIN
Solar/Wind Harmer
0.236
939181AE1-148 GEN
Solar/Wind Harmer
13.009
3146776BUCKING
Solar/Wind Harmer
0.802
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.673
971489AH1-241 GEN
Solar/Wind Harmer
5.518
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.099
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.073
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.928
315693AD1-088 GEN
Solar/Wind Harmer
21.573
962491AG1-098 GEN
Solar/Wind Harmer
25.346
970401AG2-262 GEN
Solar/Wind Harmer
2.602
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.735
963171AG1-166 GEN
Solar/Wind Harmer
1.594
971563AH1-280 GEN
Solar/Wind Harmer
3.188
3146926FARMVIL
Solar/Wind Harmer
0.163
971065AG2-659 GEN
Solar/Wind Harmer
8.623
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.717
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.562
971795AH1-408 GEN
Solar/Wind Harmer
8.362
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.437
971377AH1-170 GEN
Solar/Wind Harmer
1.104
3147623JAMES R
Solar/Wind Harmer
0.24
970937AG2-583 GEN
Solar/Wind Harmer
5.738
960081AF2-299 GEN
Solar/Wind Harmer
0.703
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.031
G-007ALTFEXP_G-007A->PJM
CMTX
0.429
VTFLTFEXP_VFT->PJM
CMTX
1.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.809
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.962
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.375
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.85
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.677
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:903.34 MVA
Rating Type:B
MVA to Mitigate:921.89
MW Contribution:2.79
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
47.174
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.071
3151261ROARAP2
50/50
0.076
24728405LEESVG
50/50
0.073
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.594
316478AD1-087 GEN
Solar/Wind Harmer
1.768
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.715
3151531CLOVER1
50/50
10.81
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.073
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.928
315693AD1-088 GEN
Solar/Wind Harmer
21.573
962491AG1-098 GEN
Solar/Wind Harmer
25.346
970401AG2-262 GEN
Solar/Wind Harmer
2.602
970909AG2-566 GEN
Solar/Wind Harmer
3.699
316131AB2-060 GEN
Solar/Wind Harmer
1.016
964241AG1-285 GEN
Solar/Wind Harmer
21.282
315785AD2-033 C
Solar/Wind Harmer
2.544
970257AG2-171 GEN
Solar/Wind Harmer
9.938
959311AF2-222 GEN
Solar/Wind Harmer
27.447
963181AG1-167 GEN
Solar/Wind Harmer
1.195
3147133PAMPLIN
Solar/Wind Harmer
0.925
971193AH1-056 GEN
Solar/Wind Harmer
17.953
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.163
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.437
970221AG2-151 GEN
Solar/Wind Harmer
5.518
313506AB2-031 GEN
Solar/Wind Harmer
0.21
316313AB2-026
Solar/Wind Harmer
0.037
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.876
316283AC2-100 C
Solar/Wind Helper
2.324
3151541CLOVER2
50/50
10.758
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.223
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.258
970865AG2-541 GEN
Solar/Wind Harmer
14.488
316123AC1-075 GEN
Solar/Wind Harmer
0.47
3152661PLYWOOD A
50/50
1.086
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.15
316222AC1-221 GEN
Solar/Wind Harmer
3.734
970099AG2-077 GEN
Solar/Wind Harmer
51.571
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.515
970165AG2-112 GEN
Solar/Wind Harmer
2.789
970163AG2-111 GEN
Solar/Wind Harmer
2.661
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.225
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.299
970681AG2-440 GEN
Solar/Wind Harmer
16.239
946301AF1-294 GEN
Solar/Wind Harmer
5.897
961791AG1-021 GEN
Solar/Wind Harmer
2.869
315657AE1-056 GEN
Solar/Wind Harmer
10.169
970285AG2-188 GEN
Solar/Wind Harmer
17.248
971845AH1-439 GEN
Solar/Wind Harmer
9.37
970831AG2-522 GEN
Solar/Wind Harmer
7.605
971447AH1-217 GEN
Solar/Wind Harmer
2.977
270494AE1-108_GEN
Solar/Wind Harmer
1.028
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.259
270455AD2-022 GEN
Solar/Wind Helper
1.376
270457AD2-023 GEN
Solar/Wind Helper
0.907
962561AG1-105 GEN
Solar/Wind Harmer
20.413
971741AH1-377 GEN
Solar/Wind Harmer
36.74
970301AG2-198 GEN
Solar/Wind Harmer
14.798
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.251
971775AH1-396 GEN
Solar/Wind Harmer
0.497
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.586
963191AG1-168 GEN
Solar/Wind Harmer
1.195
942751AE2-291 GEN
Solar/Wind Harmer
16.169
3147133PAMPLIN
Solar/Wind Harmer
0.295
3147133PAMPLIN
Solar/Wind Harmer
0.236
939181AE1-148 GEN
Solar/Wind Harmer
13.009
3146776BUCKING
Solar/Wind Harmer
0.802
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.673
971489AH1-241 GEN
Solar/Wind Harmer
5.518
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.099
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.735
963171AG1-166 GEN
Solar/Wind Harmer
1.594
971563AH1-280 GEN
Solar/Wind Harmer
3.188
3146926FARMVIL
Solar/Wind Harmer
0.163
971065AG2-659 GEN
Solar/Wind Harmer
8.623
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.717
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.562
971795AH1-408 GEN
Solar/Wind Harmer
8.362
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.437
971377AH1-170 GEN
Solar/Wind Harmer
1.104
3147623JAMES R
Solar/Wind Harmer
0.24
970937AG2-583 GEN
Solar/Wind Harmer
5.738
960081AF2-299 GEN
Solar/Wind Harmer
0.703
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.031
G-007ALTFEXP_G-007A->PJM
CMTX
0.429
VTFLTFEXP_VFT->PJM
CMTX
1.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.809
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.962
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.375
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.85
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.677
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.6 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:338.91
MW Contribution:5.28
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
27.019
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
5.281
970163AG2-111 GEN
Solar/Wind Harmer
5.037
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.038
316239AB2-077_GEN
Solar/Wind Helper
0.189
316238AB2-078_GEN
Solar/Wind Helper
0.189
3144303KENBRDG
Solar/Wind Helper
0.094
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.206
24684605SMG4
50/50
0.898
24288905REUSENS
50/50
0.018
966251AG1-494 GEN
50/50
1.295
971683AH1-343 GEN
Solar/Wind Harmer
30.996
3147312GRETNA
Solar/Wind Harmer
0.048
24684405SMG2
50/50
0.892
24684505SMG3
50/50
0.552
24684305SMG1
50/50
0.323
942751AE2-291 GEN
Solar/Wind Harmer
31.022
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.003
942671AE2-283 GEN
Solar/Wind Harmer
6.023
3146843MT LREL
Solar/Wind Helper
0.233
3146843MT LREL
Solar/Wind Helper
0.233
316034AC1-036 C
Solar/Wind Helper
0.123
24728405LEESVG
50/50
0.205
24684705SMG5
50/50
0.344
970481AG2-311 GEN
50/50
4.788
316003AC1-222 GEN
Solar/Wind Harmer
0.024
3147123OTTER R
Solar/Wind Harmer
0.184
3147312GRETNA
Solar/Wind Harmer
0.193
3146802CHATHAM
Solar/Wind Harmer
0.181
941801AE2-185 GEN
Solar/Wind Harmer
7.744
270173AC1-122 GEN
Solar/Wind Harmer
0.243
962751AG1-124 GEN
Solar/Wind Harmer
3.509
270574AD1-017 GEN2
Solar/Wind Harmer
0
316237AB2-079_GEN
Solar/Wind Helper
0.189
315687AD1-152 GEN
Solar/Wind Helper
0.648
941821AE2-187 GEN
Solar/Wind Harmer
7.744
270197AD1-017 GEN1
Solar/Wind Harmer
0.467
958131AF2-107 GEN
Solar/Wind Harmer
1.702
316248AF1-058 C
Solar/Wind Helper
0.405
316131AB2-060 GEN
Solar/Wind Helper
0.826
315785AD2-033 C
Solar/Wind Helper
1.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.748
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.233
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.894
MECLTFEXP_MEC->PJM
CLTF
0.944
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.2
LGEELTFEXP_LGEE->PJM
CLTF
0.454
WECLTFEXP_WEC->PJM
CLTF
0.224
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.472
LAGNLTFEXP_LAGN->PJM
CLTF
0.838
TVALTFEXP_TVA->PJM
CLTF
0.47

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.54 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:400.88
MW Contribution:6.95
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
316003AC1-222 GEN
Solar/Wind Harmer
9.904
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.196
270173AC1-122 GEN
Solar/Wind Harmer
1.176
962751AG1-124 GEN
Solar/Wind Harmer
5.122
270574AD1-017 GEN2
Solar/Wind Harmer
2.771
316237AB2-079_GEN
Solar/Wind Helper
0.189
315687AD1-152 GEN
Solar/Wind Helper
0.648
970865AG2-541 GEN
Solar/Wind Harmer
35.574
316123AC1-075 GEN
Solar/Wind Harmer
7.896
970165AG2-112 GEN
Solar/Wind Harmer
6.953
970163AG2-111 GEN
Solar/Wind Harmer
6.633
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.038
316239AB2-077_GEN
Solar/Wind Helper
0.189
316238AB2-078_GEN
Solar/Wind Helper
0.189
3144303KENBRDG
Solar/Wind Helper
0.095
24728405LEESVG
50/50
0.206
971683AH1-343 GEN
Solar/Wind Harmer
40.81
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.196
270197AD1-017 GEN1
Solar/Wind Harmer
0.833
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.405
316131AB2-060 GEN
Solar/Wind Helper
0.827
315785AD2-033 C
Solar/Wind Helper
1.416
942751AE2-291 GEN
Solar/Wind Harmer
40.845
316217AC1-145 GEN
Solar/Wind Harmer
4.413
316197AC1-042 GEN
Solar/Wind Harmer
3.345
942671AE2-283 GEN
Solar/Wind Harmer
9.006
3146843MT LREL
Solar/Wind Helper
0.233
3146843MT LREL
Solar/Wind Helper
0.233
316034AC1-036 C
Solar/Wind Helper
0.123
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.741
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.228
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.892
MECLTFEXP_MEC->PJM
CLTF
0.944
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.2
LGEELTFEXP_LGEE->PJM
CLTF
0.454
WECLTFEXP_WEC->PJM
CLTF
0.224
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.472
LAGNLTFEXP_LAGN->PJM
CLTF
0.837
TVALTFEXP_TVA->PJM
CLTF
0.469

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.18 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:399.63
MW Contribution:6.95
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.575
316123AC1-075 GEN
Solar/Wind Harmer
7.897
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
316003AC1-222 GEN
Solar/Wind Harmer
9.905
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.197
270173AC1-122 GEN
Solar/Wind Harmer
1.176
962751AG1-124 GEN
Solar/Wind Harmer
5.123
270574AD1-017 GEN2
Solar/Wind Harmer
2.771
316237AB2-079_GEN
Solar/Wind Helper
0.189
315687AD1-152 GEN
Solar/Wind Helper
0.648
970165AG2-112 GEN
Solar/Wind Harmer
6.953
970163AG2-111 GEN
Solar/Wind Harmer
6.633
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.038
316239AB2-077_GEN
Solar/Wind Helper
0.189
316238AB2-078_GEN
Solar/Wind Helper
0.189
3144303KENBRDG
Solar/Wind Helper
0.094
942751AE2-291 GEN
Solar/Wind Harmer
40.846
316217AC1-145 GEN
Solar/Wind Harmer
4.413
316197AC1-042 GEN
Solar/Wind Harmer
3.345
942671AE2-283 GEN
Solar/Wind Harmer
9.007
3146843MT LREL
Solar/Wind Helper
0.233
3146843MT LREL
Solar/Wind Helper
0.233
316034AC1-036 C
Solar/Wind Helper
0.123
24728405LEESVG
50/50
0.206
971683AH1-343 GEN
Solar/Wind Harmer
40.811
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.197
270197AD1-017 GEN1
Solar/Wind Harmer
0.833
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.405
316131AB2-060 GEN
Solar/Wind Helper
0.826
315785AD2-033 C
Solar/Wind Helper
1.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.747
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.233
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.894
MECLTFEXP_MEC->PJM
CLTF
0.944
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.2
LGEELTFEXP_LGEE->PJM
CLTF
0.454
WECLTFEXP_WEC->PJM
CLTF
0.224
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.472
LAGNLTFEXP_LAGN->PJM
CLTF
0.838
TVALTFEXP_TVA->PJM
CLTF
0.47

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.17 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:399.59
MW Contribution:6.95
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
316003AC1-222 GEN
Solar/Wind Harmer
9.905
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.197
270173AC1-122 GEN
Solar/Wind Harmer
1.176
962751AG1-124 GEN
Solar/Wind Harmer
5.123
270574AD1-017 GEN2
Solar/Wind Harmer
2.771
316237AB2-079_GEN
Solar/Wind Helper
0.189
315687AD1-152 GEN
Solar/Wind Helper
0.648
970865AG2-541 GEN
Solar/Wind Harmer
35.575
316123AC1-075 GEN
Solar/Wind Harmer
7.897
970165AG2-112 GEN
Solar/Wind Harmer
6.953
970163AG2-111 GEN
Solar/Wind Harmer
6.633
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.038
316239AB2-077_GEN
Solar/Wind Helper
0.189
316238AB2-078_GEN
Solar/Wind Helper
0.189
3144303KENBRDG
Solar/Wind Helper
0.094
942751AE2-291 GEN
Solar/Wind Harmer
40.846
316217AC1-145 GEN
Solar/Wind Harmer
4.413
316197AC1-042 GEN
Solar/Wind Harmer
3.346
942671AE2-283 GEN
Solar/Wind Harmer
9.007
3146843MT LREL
Solar/Wind Helper
0.233
3146843MT LREL
Solar/Wind Helper
0.233
316034AC1-036 C
Solar/Wind Helper
0.123
24728405LEESVG
50/50
0.206
971683AH1-343 GEN
Solar/Wind Harmer
40.811
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.197
270197AD1-017 GEN1
Solar/Wind Harmer
0.833
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.405
316131AB2-060 GEN
Solar/Wind Helper
0.826
315785AD2-033 C
Solar/Wind Helper
1.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.748
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.233
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.894
MECLTFEXP_MEC->PJM
CLTF
0.944
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.2
LGEELTFEXP_LGEE->PJM
CLTF
0.454
WECLTFEXP_WEC->PJM
CLTF
0.224
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.472
LAGNLTFEXP_LAGN->PJM
CLTF
0.838
TVALTFEXP_TVA->PJM
CLTF
0.47

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.44 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:397.05
MW Contribution:6.96
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.473
316123AC1-075 GEN
Solar/Wind Harmer
7.906
970165AG2-112 GEN
Solar/Wind Harmer
6.961
970163AG2-111 GEN
Solar/Wind Harmer
6.641
3147173SINAI
Solar/Wind Helper
0.315
3147243WELCO
Solar/Wind Helper
0.197
316118AC1-105 GEN
Solar/Wind Helper
1.088
316239AB2-077_GEN
Solar/Wind Helper
0.203
316238AB2-078_GEN
Solar/Wind Helper
0.203
3144303KENBRDG
Solar/Wind Helper
0.101
3151561HALLBR1
50/50
0.769
24728405LEESVG
50/50
0.228
24684705SMG5
50/50
0.436
970481AG2-311 GEN
50/50
6.074
316003AC1-222 GEN
Solar/Wind Harmer
9.848
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.654
270574AD1-017 GEN2
Solar/Wind Harmer
5.091
270016AE1-250 BESS
Solar/Wind Harmer
2.26
970223AG2-152 GEN
Solar/Wind Harmer
13.033
270173AC1-122 GEN
Solar/Wind Harmer
1.398
962751AG1-124 GEN
Solar/Wind Harmer
5.091
316237AB2-079_GEN
Solar/Wind Helper
0.203
315687AD1-152 GEN
Solar/Wind Helper
0.727
24728405LEESVG
50/50
0.229
24684605SMG4
50/50
1.139
971683AH1-343 GEN
Solar/Wind Harmer
40.631
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.654
270197AD1-017 GEN1
Solar/Wind Harmer
1.53
958131AF2-107 GEN
Solar/Wind Harmer
2.297
316248AF1-058 C
Solar/Wind Helper
0.423
316131AB2-060 GEN
Solar/Wind Helper
0.889
315785AD2-033 C
Solar/Wind Helper
1.513
24684405SMG2
50/50
1.132
24684505SMG3
50/50
0.7
24684305SMG1
50/50
0.41
942751AE2-291 GEN
Solar/Wind Harmer
41.038
316217AC1-145 GEN
Solar/Wind Harmer
4.611
316197AC1-042 GEN
Solar/Wind Harmer
3.495
942671AE2-283 GEN
Solar/Wind Harmer
9.411
270013AE1-250 PV
Solar/Wind Harmer
2.26
3146843MT LREL
Solar/Wind Helper
0.245
3146843MT LREL
Solar/Wind Helper
0.245
316034AC1-036 C
Solar/Wind Helper
0.132
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.384
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.316
MECLTFEXP_MEC->PJM
CLTF
0.433
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.113
LGEELTFEXP_LGEE->PJM
CLTF
0.256
WECLTFEXP_WEC->PJM
CLTF
0.121
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.011
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.95 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:391.83
MW Contribution:6.98
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.382
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:111.69 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:390.93
MW Contribution:6.98
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.382
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.69 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:390.91
MW Contribution:6.98
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
24684405SMG2
50/50
1.116
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.383
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.445
316034AC1-036 C
Solar/Wind Helper
0.126
3144303KENBRDG
Solar/Wind Helper
0.096
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.019
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.82 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:313.83
MW Contribution:5.24
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
0.816
24684505SMG3
50/50
0.505
24684305SMG1
50/50
0.296
942751AE2-291 GEN
Solar/Wind Harmer
30.733
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.824
3146843MT LREL
Solar/Wind Helper
0.236
3146843MT LREL
Solar/Wind Helper
0.236
316034AC1-036 C
Solar/Wind Helper
0.122
970865AG2-541 GEN
Solar/Wind Harmer
26.894
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
5.243
970163AG2-111 GEN
Solar/Wind Harmer
5.001
3147173SINAI
Solar/Wind Helper
0.305
3147243WELCO
Solar/Wind Helper
0.191
316118AC1-105 GEN
Solar/Wind Helper
1.051
316239AB2-077_GEN
Solar/Wind Helper
0.19
316238AB2-078_GEN
Solar/Wind Helper
0.19
3144303KENBRDG
Solar/Wind Helper
0.094
3151561HALLBR1
50/50
0.725
24728405LEESVG
50/50
0.195
24684705SMG5
50/50
0.314
970481AG2-311 GEN
50/50
4.381
316003AC1-222 GEN
Solar/Wind Harmer
0.024
3147123OTTER R
Solar/Wind Harmer
0.179
3147312GRETNA
Solar/Wind Harmer
0.187
3146802CHATHAM
Solar/Wind Harmer
0.175
941801AE2-185 GEN
Solar/Wind Harmer
7.488
270173AC1-122 GEN
Solar/Wind Harmer
0.22
962751AG1-124 GEN
Solar/Wind Harmer
3.082
270574AD1-017 GEN2
Solar/Wind Harmer
0
316237AB2-079_GEN
Solar/Wind Helper
0.19
315687AD1-152 GEN
Solar/Wind Helper
0.658
24728405LEESVG
50/50
0.195
24684605SMG4
50/50
0.822
24288905REUSENS
50/50
0.016
966251AG1-494 GEN
50/50
1.151
971683AH1-343 GEN
Solar/Wind Harmer
30.882
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.488
270197AD1-017 GEN1
Solar/Wind Harmer
0.418
316248AF1-058 C
Solar/Wind Helper
0.41
316131AB2-060 GEN
Solar/Wind Helper
0.829
315785AD2-033 C
Solar/Wind Helper
1.406
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.22
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.709
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.664
MECLTFEXP_MEC->PJM
CLTF
0.482
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.114
LGEELTFEXP_LGEE->PJM
CLTF
0.255
WECLTFEXP_WEC->PJM
CLTF
0.124
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.654
LAGNLTFEXP_LAGN->PJM
CLTF
0.196
TVALTFEXP_TVA->PJM
CLTF
0.134

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.51 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:376.28
MW Contribution:7.43
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
37.085
316123AC1-075 GEN
Solar/Wind Harmer
8.439
970165AG2-112 GEN
Solar/Wind Harmer
7.43
970163AG2-111 GEN
Solar/Wind Harmer
7.088
3147173SINAI
Solar/Wind Helper
0.271
3147243WELCO
Solar/Wind Helper
0.169
316118AC1-105 GEN
Solar/Wind Helper
0.93
316239AB2-077_GEN
Solar/Wind Helper
0.166
316238AB2-078_GEN
Solar/Wind Helper
0.166
24684405SMG2
50/50
1.04
24684505SMG3
50/50
0.643
24684305SMG1
50/50
0.377
942751AE2-291 GEN
Solar/Wind Harmer
44.58
316217AC1-145 GEN
Solar/Wind Harmer
5.995
316197AC1-042 GEN
Solar/Wind Harmer
4.545
942671AE2-283 GEN
Solar/Wind Harmer
12.236
3146843MT LREL
Solar/Wind Helper
0.208
3146843MT LREL
Solar/Wind Helper
0.208
24728405LEESVG
50/50
0.267
24684605SMG4
50/50
1.047
971683AH1-343 GEN
Solar/Wind Harmer
42.136
3147312GRETNA
Solar/Wind Harmer
-0.007
941821AE2-187 GEN
Solar/Wind Harmer
13.852
270197AD1-017 GEN1
Solar/Wind Harmer
0.973
316248AF1-058 C
Solar/Wind Helper
0.364
316131AB2-060 GEN
Solar/Wind Helper
0.725
3151561HALLBR1
50/50
0.945
24728405LEESVG
50/50
0.266
24684705SMG5
50/50
0.401
970481AG2-311 GEN
50/50
5.583
316003AC1-222 GEN
Solar/Wind Harmer
10.144
3147123OTTER R
Solar/Wind Harmer
-0.025
3147312GRETNA
Solar/Wind Harmer
-0.03
3146802CHATHAM
Solar/Wind Harmer
-0.028
941801AE2-185 GEN
Solar/Wind Harmer
13.852
270173AC1-122 GEN
Solar/Wind Harmer
1.159
270574AD1-017 GEN2
Solar/Wind Harmer
3.24
316237AB2-079_GEN
Solar/Wind Helper
0.166
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.175
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.905
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.465
MECLTFEXP_MEC->PJM
CLTF
0.347
SIGELTFEXP_SIGE->PJM
CLTF
0.013
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.187
WECLTFEXP_WEC->PJM
CLTF
0.09
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.518
LAGNLTFEXP_LAGN->PJM
CLTF
0.125
TVALTFEXP_TVA->PJM
CLTF
0.091

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P7-1_#10781___SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10781___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.72 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:366.51
MW Contribution:6.9
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.21
971683AH1-343 GEN
Solar/Wind Harmer
40.466
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.198
270197AD1-017 GEN1
Solar/Wind Harmer
1.082
958131AF2-107 GEN
Solar/Wind Harmer
2.161
316248AF1-058 C
Solar/Wind Helper
0.428
316131AB2-060 GEN
Solar/Wind Helper
0.9
315785AD2-033 C
Solar/Wind Helper
1.533
3151561HALLBR1
50/50
0.743
24728405LEESVG
50/50
0.21
316003AC1-222 GEN
Solar/Wind Harmer
9.819
942751AE2-291 GEN
Solar/Wind Harmer
40.562
316217AC1-145 GEN
Solar/Wind Harmer
4.414
970865AG2-541 GEN
Solar/Wind Harmer
35.284
316123AC1-075 GEN
Solar/Wind Harmer
7.837
970165AG2-112 GEN
Solar/Wind Harmer
6.901
970163AG2-111 GEN
Solar/Wind Harmer
6.583
3147173SINAI
Solar/Wind Helper
0.318
3147243WELCO
Solar/Wind Helper
0.199
316118AC1-105 GEN
Solar/Wind Helper
1.1
316239AB2-077_GEN
Solar/Wind Helper
0.205
316238AB2-078_GEN
Solar/Wind Helper
0.205
3144303KENBRDG
Solar/Wind Helper
0.102
316197AC1-042 GEN
Solar/Wind Harmer
3.346
942671AE2-283 GEN
Solar/Wind Harmer
9.009
270013AE1-250 PV
Solar/Wind Harmer
1.363
3146843MT LREL
Solar/Wind Helper
0.248
3146843MT LREL
Solar/Wind Helper
0.248
316034AC1-036 C
Solar/Wind Helper
0.133
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.198
270173AC1-122 GEN
Solar/Wind Harmer
1.218
270574AD1-017 GEN2
Solar/Wind Harmer
3.601
270016AE1-250 BESS
Solar/Wind Harmer
1.363
970223AG2-152 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
4.804
316237AB2-079_GEN
Solar/Wind Helper
0.205
315687AD1-152 GEN
Solar/Wind Helper
0.735
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.373
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.967
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.446
MECLTFEXP_MEC->PJM
CLTF
0.486
SIGELTFEXP_SIGE->PJM
CLTF
0.019
NYPJM->LTFIMP_NY
CLTF
0.114
LGEELTFEXP_LGEE->PJM
CLTF
0.278
WECLTFEXP_WEC->PJM
CLTF
0.133
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.003
LAGNLTFEXP_LAGN->PJM
CLTF
0.016
TVALTFEXP_TVA->PJM
CLTF
0.056
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P2-2_#17572_05MUSEVILLE 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#17572_05MUSEVILLE 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.61 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:352.15
MW Contribution:6.99
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.617
316123AC1-075 GEN
Solar/Wind Harmer
7.933
970165AG2-112 GEN
Solar/Wind Harmer
6.985
970163AG2-111 GEN
Solar/Wind Harmer
6.663
3147173SINAI
Solar/Wind Helper
0.306
3147243WELCO
Solar/Wind Helper
0.191
316118AC1-105 GEN
Solar/Wind Helper
1.054
316239AB2-077_GEN
Solar/Wind Helper
0.192
316238AB2-078_GEN
Solar/Wind Helper
0.192
3144303KENBRDG
Solar/Wind Helper
0.095
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.429
970481AG2-311 GEN
50/50
5.974
316003AC1-222 GEN
Solar/Wind Harmer
9.893
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.62
24728405LEESVG
50/50
0.227
24684605SMG4
50/50
1.121
971683AH1-343 GEN
Solar/Wind Harmer
40.806
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.62
958131AF2-107 GEN
Solar/Wind Harmer
2.264
316248AF1-058 C
Solar/Wind Helper
0.411
316131AB2-060 GEN
Solar/Wind Helper
0.841
315785AD2-033 C
Solar/Wind Helper
1.428
270173AC1-122 GEN
Solar/Wind Harmer
1.374
962751AG1-124 GEN
Solar/Wind Harmer
4.989
316237AB2-079_GEN
Solar/Wind Helper
0.192
315687AD1-152 GEN
Solar/Wind Helper
0.677
24684405SMG2
50/50
1.113
24684505SMG3
50/50
0.689
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.154
316217AC1-145 GEN
Solar/Wind Harmer
4.596
316197AC1-042 GEN
Solar/Wind Harmer
3.484
942671AE2-283 GEN
Solar/Wind Harmer
9.381
3146843MT LREL
Solar/Wind Helper
0.237
3146843MT LREL
Solar/Wind Helper
0.237
316034AC1-036 C
Solar/Wind Helper
0.124
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.305
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.734
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.041
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.35
MECLTFEXP_MEC->PJM
CLTF
0.394
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.097
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.817
LAGNLTFEXP_LAGN->PJM
CLTF
0.006
TVALTFEXP_TVA->PJM
CLTF
0.041
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:239.46 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1295.46
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.752
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.21
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.763
971967AH1-528 GEN
Solar/Wind Harmer
100.637
970865AG2-541 GEN
Solar/Wind Harmer
19.063
316123AC1-075 GEN
Solar/Wind Harmer
4.167
970165AG2-112 GEN
Solar/Wind Harmer
3.669
970163AG2-111 GEN
Solar/Wind Harmer
3.5
316239AB2-077_GEN
Solar/Wind Harmer
1.107
316238AB2-078_GEN
Solar/Wind Harmer
1.107
971443AH1-215 GEN
Solar/Wind Harmer
6.874
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.701
970681AG2-440 GEN
Solar/Wind Harmer
21.361
946301AF1-294 GEN
Solar/Wind Harmer
8.596
961791AG1-021 GEN
Solar/Wind Harmer
4.193
315657AE1-056 GEN
Solar/Wind Harmer
12.411
970285AG2-188 GEN
Solar/Wind Harmer
21.406
971845AH1-439 GEN
Solar/Wind Harmer
12.319
970831AG2-522 GEN
Solar/Wind Harmer
9.997
971447AH1-217 GEN
Solar/Wind Harmer
3.908
270494AE1-108_GEN
Solar/Wind Harmer
2.497
946281AF1-292 GEN
Solar/Wind Harmer
0.183
316087AB2-174 GEN
Solar/Wind Harmer
1.111
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.379
270457AD2-023 GEN
Solar/Wind Helper
0.909
970413AG2-270 GEN
50/50
47.147
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.068
316283AC2-100 C
Solar/Wind Harmer
9.573
316248AF1-058 C
Solar/Wind Harmer
1.792
960061AF2-297 GEN
Solar/Wind Harmer
29.732
316478AD1-087 GEN
Solar/Wind Harmer
4.927
316486AD2-202 GEN
Solar/Wind Harmer
1.443
971683AH1-343 GEN
Solar/Wind Harmer
21.994
970909AG2-566 GEN
Solar/Wind Harmer
3.696
316131AB2-060 GEN
Solar/Wind Harmer
3.914
964241AG1-285 GEN
Solar/Wind Harmer
27.996
315785AD2-033 C
Solar/Wind Harmer
7.961
970257AG2-171 GEN
Solar/Wind Harmer
13.073
959311AF2-222 GEN
Solar/Wind Harmer
36.177
963181AG1-167 GEN
Solar/Wind Harmer
3.145
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.685
942461AE2-259 GEN
Solar/Wind Harmer
4.783
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.513
970221AG2-151 GEN
Solar/Wind Harmer
7.245
966621AG1-532 GEN
Solar/Wind Harmer
0.166
313506AB2-031 GEN
Solar/Wind Harmer
0.612
316313AB2-026
Solar/Wind Harmer
0.175
316258AE1-075 C
Solar/Wind Harmer
0.157
316405AF2-144 C
Solar/Wind Harmer
0.166
3143336POWHATN
Solar/Wind Harmer
0.654
270018AE2-047 C O1
Solar/Wind Helper
0.395
3152661PLYWOOD A
50/50
1.085
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.145
316222AC1-221 GEN
Solar/Wind Harmer
10.226
970099AG2-077 GEN
Solar/Wind Harmer
67.861
970933AG2-581 GEN
Solar/Wind Harmer
50.184
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.637
962561AG1-105 GEN
Solar/Wind Harmer
26.859
971741AH1-377 GEN
Solar/Wind Harmer
48.337
970301AG2-198 GEN
Solar/Wind Harmer
19.467
313527AB2-043 GEN
Solar/Wind Harmer
5.909
970323AG2-213 GEN
Solar/Wind Harmer
17.431
971775AH1-396 GEN
Solar/Wind Harmer
2.482
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.241
963191AG1-168 GEN
Solar/Wind Harmer
3.145
942751AE2-291 GEN
Solar/Wind Harmer
21.269
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.11
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.953
316197AC1-042 GEN
Solar/Wind Harmer
1.481
942671AE2-283 GEN
Solar/Wind Harmer
3.987
971489AH1-241 GEN
Solar/Wind Harmer
6.878
315821AE2-092 GEN
Solar/Wind Harmer
1.789
316181AB2-040 GEN
Solar/Wind Harmer
1.061
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.783
3145593CAROLNA
Solar/Wind Harmer
0.058
3151531CLOVER1
50/50
10.804
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.432
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.379
3151911BEARGRDN G1
50/50
1.068
315687AD1-152 GEN
Solar/Wind Harmer
7.75
316003AC1-222 GEN
Solar/Wind Harmer
5.363
957481AF2-042 GEN
Solar/Wind Harmer
169.654
315693AD1-088 GEN
Solar/Wind Harmer
25.233
962491AG1-098 GEN
Solar/Wind Harmer
33.35
970401AG2-262 GEN
Solar/Wind Harmer
3.25
316237AB2-079_GEN
Solar/Wind Harmer
1.107
970685AG2-442 GEN
Solar/Wind Harmer
29.906
963171AG1-166 GEN
Solar/Wind Harmer
4.193
971563AH1-280 GEN
Solar/Wind Harmer
4.193
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.337
316322AB2-045
Solar/Wind Harmer
0.757
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.874
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.319
971795AH1-408 GEN
Solar/Wind Harmer
10.545
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.513
971377AH1-170 GEN
Solar/Wind Harmer
1.449
3147623JAMES R
Solar/Wind Harmer
0.179
970937AG2-583 GEN
Solar/Wind Harmer
7.531
960081AF2-299 GEN
Solar/Wind Harmer
0.921
316336AC2-165 C
Solar/Wind Harmer
1.321
3143336POWHATN
Solar/Wind Harmer
0.769
G-007ALTFEXP_G-007A->PJM
CMTX
0.368
VTFLTFEXP_VFT->PJM
CMTX
0.961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.028
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.39
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.722
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:234.05 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1266.23
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.732
3151611KERR 4
50/50
0.534
3151531CLOVER1
50/50
10.784
3144293JTRSVLE
50/50
1.007
3151601KERR 3
50/50
0.534
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.431
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
315687AD1-152 GEN
Solar/Wind Harmer
7.735
316003AC1-222 GEN
Solar/Wind Harmer
5.352
957481AF2-042 GEN
Solar/Wind Harmer
169.338
315693AD1-088 GEN
Solar/Wind Harmer
25.187
962491AG1-098 GEN
Solar/Wind Harmer
33.29
970401AG2-262 GEN
Solar/Wind Harmer
3.243
316237AB2-079_GEN
Solar/Wind Harmer
1.104
970685AG2-442 GEN
Solar/Wind Harmer
29.855
963171AG1-166 GEN
Solar/Wind Harmer
4.186
971563AH1-280 GEN
Solar/Wind Harmer
4.186
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.304
316322AB2-045
Solar/Wind Harmer
0.757
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.869
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.333
971795AH1-408 GEN
Solar/Wind Harmer
10.544
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.485
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3152661PLYWOOD A
50/50
1.083
3144293JTRSVLE
50/50
1.007
3144293JTRSVLE
50/50
0.848
970535AG2-341 GEN
50/50
5.132
316222AC1-221 GEN
Solar/Wind Harmer
10.206
970099AG2-077 GEN
Solar/Wind Harmer
67.735
970933AG2-581 GEN
Solar/Wind Harmer
50.091
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.615
962561AG1-105 GEN
Solar/Wind Harmer
26.803
971741AH1-377 GEN
Solar/Wind Harmer
48.264
970301AG2-198 GEN
Solar/Wind Harmer
19.44
313527AB2-043 GEN
Solar/Wind Harmer
5.897
970323AG2-213 GEN
Solar/Wind Harmer
17.399
971775AH1-396 GEN
Solar/Wind Harmer
2.478
316034AC1-036 C
Solar/Wind Harmer
0.645
958211AF2-115 GEN
Solar/Wind Harmer
5.233
963191AG1-168 GEN
Solar/Wind Harmer
3.14
942751AE2-291 GEN
Solar/Wind Harmer
21.208
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.061
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.941
316197AC1-042 GEN
Solar/Wind Harmer
1.472
942671AE2-283 GEN
Solar/Wind Harmer
3.962
971489AH1-241 GEN
Solar/Wind Harmer
6.896
315821AE2-092 GEN
Solar/Wind Harmer
1.796
316181AB2-040 GEN
Solar/Wind Harmer
1.062
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
3151621KERR 5
50/50
0.534
3151631KERR 6
50/50
0.534
3151641KERR 7
50/50
0.534
972205AH1-687 GEN
50/50
5.224
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.755
971967AH1-528 GEN
Solar/Wind Harmer
100.451
970865AG2-541 GEN
Solar/Wind Harmer
19.018
316123AC1-075 GEN
Solar/Wind Harmer
4.156
970165AG2-112 GEN
Solar/Wind Harmer
3.66
970163AG2-111 GEN
Solar/Wind Harmer
3.491
316239AB2-077_GEN
Solar/Wind Harmer
1.104
316238AB2-078_GEN
Solar/Wind Harmer
1.104
971443AH1-215 GEN
Solar/Wind Harmer
6.861
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.656
970681AG2-440 GEN
Solar/Wind Harmer
21.325
946301AF1-294 GEN
Solar/Wind Harmer
8.582
961791AG1-021 GEN
Solar/Wind Harmer
4.186
315657AE1-056 GEN
Solar/Wind Harmer
12.392
970285AG2-188 GEN
Solar/Wind Harmer
21.4
971845AH1-439 GEN
Solar/Wind Harmer
12.318
970831AG2-522 GEN
Solar/Wind Harmer
9.968
971447AH1-217 GEN
Solar/Wind Harmer
3.919
270494AE1-108_GEN
Solar/Wind Harmer
2.5
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.112
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.399
270457AD2-023 GEN
Solar/Wind Helper
0.922
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.571
960081AF2-299 GEN
Solar/Wind Harmer
0.923
316336AC2-165 C
Solar/Wind Harmer
1.335
3143336POWHATN
Solar/Wind Harmer
0.78
970413AG2-270 GEN
50/50
47.058
3144293JTRSVLE
50/50
1.007
3151591KERR 2
50/50
0.534
3151921BEARGRDN G2
50/50
1.071
316283AC2-100 C
Solar/Wind Harmer
9.554
316248AF1-058 C
Solar/Wind Harmer
1.788
960061AF2-297 GEN
Solar/Wind Harmer
29.671
316478AD1-087 GEN
Solar/Wind Harmer
4.917
316486AD2-202 GEN
Solar/Wind Harmer
1.44
971683AH1-343 GEN
Solar/Wind Harmer
21.945
970909AG2-566 GEN
Solar/Wind Harmer
3.691
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.94
315785AD2-033 C
Solar/Wind Harmer
7.947
970257AG2-171 GEN
Solar/Wind Harmer
13.049
959311AF2-222 GEN
Solar/Wind Harmer
36.112
963181AG1-167 GEN
Solar/Wind Harmer
3.14
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.654
942461AE2-259 GEN
Solar/Wind Harmer
4.777
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.485
970221AG2-151 GEN
Solar/Wind Harmer
7.264
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.612
316313AB2-026
Solar/Wind Harmer
0.177
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.168
3143336POWHATN
Solar/Wind Harmer
0.663
270018AE2-047 C O1
Solar/Wind Helper
0.402
G-007ALTFEXP_G-007A->PJM
CMTX
0.461
VTFLTFEXP_VFT->PJM
CMTX
1.209
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.866
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.38
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.147
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.491
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.883
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.782
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:234.0 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1265.96
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.732
3151611KERR 4
50/50
0.534
3151621KERR 5
50/50
0.534
3151631KERR 6
50/50
0.534
3151641KERR 7
50/50
0.534
972205AH1-687 GEN
50/50
5.224
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.755
971967AH1-528 GEN
Solar/Wind Harmer
100.451
970865AG2-541 GEN
Solar/Wind Harmer
19.018
316123AC1-075 GEN
Solar/Wind Harmer
4.156
970165AG2-112 GEN
Solar/Wind Harmer
3.66
970163AG2-111 GEN
Solar/Wind Harmer
3.491
316239AB2-077_GEN
Solar/Wind Harmer
1.104
316238AB2-078_GEN
Solar/Wind Harmer
1.104
971443AH1-215 GEN
Solar/Wind Harmer
6.861
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.656
970681AG2-440 GEN
Solar/Wind Harmer
21.325
946301AF1-294 GEN
Solar/Wind Harmer
8.582
961791AG1-021 GEN
Solar/Wind Harmer
4.186
970413AG2-270 GEN
50/50
47.058
3144293JTRSVLE
50/50
1.007
3151591KERR 2
50/50
0.534
3151921BEARGRDN G2
50/50
1.071
316283AC2-100 C
Solar/Wind Harmer
9.554
316248AF1-058 C
Solar/Wind Harmer
1.788
960061AF2-297 GEN
Solar/Wind Harmer
29.671
316478AD1-087 GEN
Solar/Wind Harmer
4.917
316486AD2-202 GEN
Solar/Wind Harmer
1.44
971683AH1-343 GEN
Solar/Wind Harmer
21.945
970909AG2-566 GEN
Solar/Wind Harmer
3.691
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.94
315785AD2-033 C
Solar/Wind Harmer
7.947
970257AG2-171 GEN
Solar/Wind Harmer
13.049
959311AF2-222 GEN
Solar/Wind Harmer
36.112
3152661PLYWOOD A
50/50
1.083
3144293JTRSVLE
50/50
1.007
3144293JTRSVLE
50/50
0.848
970535AG2-341 GEN
50/50
5.132
316222AC1-221 GEN
Solar/Wind Harmer
10.206
970099AG2-077 GEN
Solar/Wind Harmer
67.735
970933AG2-581 GEN
Solar/Wind Harmer
50.091
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.615
962561AG1-105 GEN
Solar/Wind Harmer
26.803
971741AH1-377 GEN
Solar/Wind Harmer
48.264
970301AG2-198 GEN
Solar/Wind Harmer
19.44
313527AB2-043 GEN
Solar/Wind Harmer
5.897
970323AG2-213 GEN
Solar/Wind Harmer
17.399
971775AH1-396 GEN
Solar/Wind Harmer
2.478
316034AC1-036 C
Solar/Wind Harmer
0.645
958211AF2-115 GEN
Solar/Wind Harmer
5.233
3151531CLOVER1
50/50
10.784
3144293JTRSVLE
50/50
1.007
3151601KERR 3
50/50
0.534
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.431
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
315687AD1-152 GEN
Solar/Wind Harmer
7.735
316003AC1-222 GEN
Solar/Wind Harmer
5.352
957481AF2-042 GEN
Solar/Wind Harmer
169.338
315693AD1-088 GEN
Solar/Wind Harmer
25.187
962491AG1-098 GEN
Solar/Wind Harmer
33.29
970401AG2-262 GEN
Solar/Wind Harmer
3.243
316237AB2-079_GEN
Solar/Wind Harmer
1.104
970685AG2-442 GEN
Solar/Wind Harmer
29.855
963191AG1-168 GEN
Solar/Wind Harmer
3.14
942751AE2-291 GEN
Solar/Wind Harmer
21.208
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.061
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.941
316197AC1-042 GEN
Solar/Wind Harmer
1.472
942671AE2-283 GEN
Solar/Wind Harmer
3.962
971489AH1-241 GEN
Solar/Wind Harmer
6.896
315821AE2-092 GEN
Solar/Wind Harmer
1.796
316181AB2-040 GEN
Solar/Wind Harmer
1.062
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
315657AE1-056 GEN
Solar/Wind Harmer
12.392
970285AG2-188 GEN
Solar/Wind Harmer
21.4
971845AH1-439 GEN
Solar/Wind Harmer
12.318
970831AG2-522 GEN
Solar/Wind Harmer
9.968
971447AH1-217 GEN
Solar/Wind Harmer
3.919
270494AE1-108_GEN
Solar/Wind Harmer
2.5
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.112
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.399
270457AD2-023 GEN
Solar/Wind Helper
0.922
963171AG1-166 GEN
Solar/Wind Harmer
4.186
971563AH1-280 GEN
Solar/Wind Harmer
4.186
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.304
316322AB2-045
Solar/Wind Harmer
0.757
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.869
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.333
971795AH1-408 GEN
Solar/Wind Harmer
10.544
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.485
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.571
960081AF2-299 GEN
Solar/Wind Harmer
0.923
316336AC2-165 C
Solar/Wind Harmer
1.335
3143336POWHATN
Solar/Wind Harmer
0.78
963181AG1-167 GEN
Solar/Wind Harmer
3.14
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.654
942461AE2-259 GEN
Solar/Wind Harmer
4.777
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.485
970221AG2-151 GEN
Solar/Wind Harmer
7.264
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.612
316313AB2-026
Solar/Wind Harmer
0.177
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.168
3143336POWHATN
Solar/Wind Harmer
0.663
270018AE2-047 C O1
Solar/Wind Helper
0.402
G-007ALTFEXP_G-007A->PJM
CMTX
0.461
VTFLTFEXP_VFT->PJM
CMTX
1.209
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.866
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.147
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.38
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.491
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.883
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.782
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:231.01 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1249.79
MW Contribution:3.68
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
47.591
3144293JTRSVLE
50/50
1.002
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.054
316283AC2-100 C
Solar/Wind Harmer
9.587
316248AF1-058 C
Solar/Wind Harmer
1.798
960061AF2-297 GEN
Solar/Wind Harmer
29.84
316478AD1-087 GEN
Solar/Wind Harmer
4.973
3151541CLOVER2
50/50
10.854
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.142
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.773
970865AG2-541 GEN
Solar/Wind Harmer
19.134
316123AC1-075 GEN
Solar/Wind Harmer
4.183
970165AG2-112 GEN
Solar/Wind Harmer
3.683
970163AG2-111 GEN
Solar/Wind Harmer
3.514
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.844
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.554
970681AG2-440 GEN
Solar/Wind Harmer
21.243
946301AF1-294 GEN
Solar/Wind Harmer
8.538
961791AG1-021 GEN
Solar/Wind Harmer
4.165
315657AE1-056 GEN
Solar/Wind Harmer
12.318
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.002
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.134
316222AC1-221 GEN
Solar/Wind Harmer
10.241
970099AG2-077 GEN
Solar/Wind Harmer
69.119
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.658
962561AG1-105 GEN
Solar/Wind Harmer
26.899
971741AH1-377 GEN
Solar/Wind Harmer
47.648
970301AG2-198 GEN
Solar/Wind Harmer
19.194
313527AB2-043 GEN
Solar/Wind Harmer
5.898
970323AG2-213 GEN
Solar/Wind Harmer
17.355
971775AH1-396 GEN
Solar/Wind Harmer
2.471
316034AC1-036 C
Solar/Wind Harmer
0.643
942751AE2-291 GEN
Solar/Wind Harmer
21.352
958211AF2-115 GEN
Solar/Wind Harmer
5.206
963191AG1-168 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3151531CLOVER1
50/50
10.906
3144293JTRSVLE
50/50
1.002
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.43
3151561HALLBR1
50/50
0.348
3151931BEARGRDN S1
50/50
1.361
3151911BEARGRDN G1
50/50
1.054
315687AD1-152 GEN
Solar/Wind Harmer
7.801
957481AF2-042 GEN
Solar/Wind Harmer
172.797
316003AC1-222 GEN
Solar/Wind Harmer
5.383
970401AG2-262 GEN
Solar/Wind Harmer
3.256
315693AD1-088 GEN
Solar/Wind Harmer
24.857
962491AG1-098 GEN
Solar/Wind Harmer
32.854
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.741
963171AG1-166 GEN
Solar/Wind Harmer
4.165
971563AH1-280 GEN
Solar/Wind Harmer
4.165
316486AD2-202 GEN
Solar/Wind Harmer
1.456
971683AH1-343 GEN
Solar/Wind Harmer
22.075
970909AG2-566 GEN
Solar/Wind Harmer
3.645
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.919
315785AD2-033 C
Solar/Wind Harmer
7.93
970257AG2-171 GEN
Solar/Wind Harmer
13.016
959311AF2-222 GEN
Solar/Wind Harmer
36.008
963181AG1-167 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.53
942461AE2-259 GEN
Solar/Wind Harmer
4.736
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
939181AE1-148 GEN
Solar/Wind Harmer
17.072
3146776BUCKING
Solar/Wind Harmer
-0.088
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.963
316197AC1-042 GEN
Solar/Wind Harmer
1.488
942671AE2-283 GEN
Solar/Wind Harmer
4.007
971489AH1-241 GEN
Solar/Wind Harmer
6.79
315821AE2-092 GEN
Solar/Wind Harmer
1.766
316181AB2-040 GEN
Solar/Wind Harmer
1.06
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
970285AG2-188 GEN
Solar/Wind Harmer
21.128
971845AH1-439 GEN
Solar/Wind Harmer
12.16
970831AG2-522 GEN
Solar/Wind Harmer
9.974
971447AH1-217 GEN
Solar/Wind Harmer
3.858
270494AE1-108_GEN
Solar/Wind Harmer
2.469
946281AF1-292 GEN
Solar/Wind Harmer
0.183
316087AB2-174 GEN
Solar/Wind Harmer
1.109
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.37
270457AD2-023 GEN
Solar/Wind Helper
0.903
941821AE2-187 GEN
Solar/Wind Harmer
4.536
970221AG2-151 GEN
Solar/Wind Harmer
7.152
966621AG1-532 GEN
Solar/Wind Harmer
0.166
313506AB2-031 GEN
Solar/Wind Harmer
0.611
316313AB2-026
Solar/Wind Harmer
0.172
316258AE1-075 C
Solar/Wind Harmer
0.155
316405AF2-144 C
Solar/Wind Harmer
0.164
3143336POWHATN
Solar/Wind Harmer
0.645
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.312
316322AB2-045
Solar/Wind Harmer
0.748
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.87
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.224
971795AH1-408 GEN
Solar/Wind Harmer
10.527
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.536
971377AH1-170 GEN
Solar/Wind Harmer
1.43
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.432
960081AF2-299 GEN
Solar/Wind Harmer
0.92
316336AC2-165 C
Solar/Wind Harmer
1.303
3143336POWHATN
Solar/Wind Harmer
0.759
G-007ALTFEXP_G-007A->PJM
CMTX
0.347
VTFLTFEXP_VFT->PJM
CMTX
0.905
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.807
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.181
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.999
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.368
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.859
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.707
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:231.0 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1249.74
MW Contribution:3.68
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.002
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.134
316222AC1-221 GEN
Solar/Wind Harmer
10.241
3151541CLOVER2
50/50
10.853
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.143
3151531CLOVER1
50/50
10.905
3144293JTRSVLE
50/50
1.002
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.43
3151561HALLBR1
50/50
0.348
3151931BEARGRDN S1
50/50
1.361
3151911BEARGRDN G1
50/50
1.054
315687AD1-152 GEN
Solar/Wind Harmer
7.801
970413AG2-270 GEN
50/50
47.588
3144293JTRSVLE
50/50
1.002
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.054
316283AC2-100 C
Solar/Wind Harmer
9.586
316248AF1-058 C
Solar/Wind Harmer
1.798
960061AF2-297 GEN
Solar/Wind Harmer
29.84
316478AD1-087 GEN
Solar/Wind Harmer
4.972
316486AD2-202 GEN
Solar/Wind Harmer
1.456
971683AH1-343 GEN
Solar/Wind Harmer
22.075
970909AG2-566 GEN
Solar/Wind Harmer
3.645
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.92
315785AD2-033 C
Solar/Wind Harmer
7.931
970257AG2-171 GEN
Solar/Wind Harmer
13.017
959311AF2-222 GEN
Solar/Wind Harmer
36.009
963181AG1-167 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.531
942461AE2-259 GEN
Solar/Wind Harmer
4.736
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.536
970221AG2-151 GEN
Solar/Wind Harmer
7.153
966621AG1-532 GEN
Solar/Wind Harmer
0.166
313506AB2-031 GEN
Solar/Wind Harmer
0.611
316313AB2-026
Solar/Wind Harmer
0.173
316258AE1-075 C
Solar/Wind Harmer
0.155
316405AF2-144 C
Solar/Wind Harmer
0.164
3143336POWHATN
Solar/Wind Harmer
0.645
970099AG2-077 GEN
Solar/Wind Harmer
69.109
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.657
962561AG1-105 GEN
Solar/Wind Harmer
26.899
971741AH1-377 GEN
Solar/Wind Harmer
47.653
970301AG2-198 GEN
Solar/Wind Harmer
19.197
313527AB2-043 GEN
Solar/Wind Harmer
5.898
970323AG2-213 GEN
Solar/Wind Harmer
17.355
971775AH1-396 GEN
Solar/Wind Harmer
2.471
316034AC1-036 C
Solar/Wind Harmer
0.644
942751AE2-291 GEN
Solar/Wind Harmer
21.351
958211AF2-115 GEN
Solar/Wind Harmer
5.207
963191AG1-168 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.072
3146776BUCKING
Solar/Wind Harmer
-0.088
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.963
316197AC1-042 GEN
Solar/Wind Harmer
1.488
942671AE2-283 GEN
Solar/Wind Harmer
4.007
971489AH1-241 GEN
Solar/Wind Harmer
6.79
315821AE2-092 GEN
Solar/Wind Harmer
1.766
316181AB2-040 GEN
Solar/Wind Harmer
1.06
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.773
970865AG2-541 GEN
Solar/Wind Harmer
19.133
316123AC1-075 GEN
Solar/Wind Harmer
4.183
970165AG2-112 GEN
Solar/Wind Harmer
3.683
970163AG2-111 GEN
Solar/Wind Harmer
3.514
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.845
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.555
970681AG2-440 GEN
Solar/Wind Harmer
21.244
946301AF1-294 GEN
Solar/Wind Harmer
8.539
961791AG1-021 GEN
Solar/Wind Harmer
4.165
315657AE1-056 GEN
Solar/Wind Harmer
12.319
970285AG2-188 GEN
Solar/Wind Harmer
21.13
971845AH1-439 GEN
Solar/Wind Harmer
12.161
970831AG2-522 GEN
Solar/Wind Harmer
9.975
971447AH1-217 GEN
Solar/Wind Harmer
3.858
270494AE1-108_GEN
Solar/Wind Harmer
2.469
946281AF1-292 GEN
Solar/Wind Harmer
0.183
316087AB2-174 GEN
Solar/Wind Harmer
1.109
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.37
270457AD2-023 GEN
Solar/Wind Helper
0.903
957481AF2-042 GEN
Solar/Wind Harmer
172.774
316003AC1-222 GEN
Solar/Wind Harmer
5.383
970401AG2-262 GEN
Solar/Wind Harmer
3.256
315693AD1-088 GEN
Solar/Wind Harmer
24.86
962491AG1-098 GEN
Solar/Wind Harmer
32.858
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.742
963171AG1-166 GEN
Solar/Wind Harmer
4.165
971563AH1-280 GEN
Solar/Wind Harmer
4.165
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.312
316322AB2-045
Solar/Wind Harmer
0.748
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.87
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.224
971795AH1-408 GEN
Solar/Wind Harmer
10.527
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.536
971377AH1-170 GEN
Solar/Wind Harmer
1.431
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.433
960081AF2-299 GEN
Solar/Wind Harmer
0.92
316336AC2-165 C
Solar/Wind Harmer
1.304
3143336POWHATN
Solar/Wind Harmer
0.759
G-007ALTFEXP_G-007A->PJM
CMTX
0.347
VTFLTFEXP_VFT->PJM
CMTX
0.906
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.807
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.181
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.999
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.368
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.859
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.707
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:192.41 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:978.46
MW Contribution:2.79
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
47.147
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.068
3151261ROARAP2
50/50
0.075
24728405LEESVG
50/50
0.073
316283AC2-100 C
Solar/Wind Harmer
1.77
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.582
316478AD1-087 GEN
Solar/Wind Harmer
1.767
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.704
970909AG2-566 GEN
Solar/Wind Harmer
3.696
316131AB2-060 GEN
Solar/Wind Harmer
1.015
964241AG1-285 GEN
Solar/Wind Harmer
21.263
3151541CLOVER2
50/50
10.752
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.21
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.257
971967AH1-528 GEN
Solar/Wind Harmer
76.23
970865AG2-541 GEN
Solar/Wind Harmer
14.478
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.787
970163AG2-111 GEN
Solar/Wind Harmer
2.658
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.22
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.28
970681AG2-440 GEN
Solar/Wind Harmer
16.224
946301AF1-294 GEN
Solar/Wind Harmer
5.891
961791AG1-021 GEN
Solar/Wind Harmer
2.866
315657AE1-056 GEN
Solar/Wind Harmer
10.159
970285AG2-188 GEN
Solar/Wind Harmer
17.225
971845AH1-439 GEN
Solar/Wind Harmer
9.357
970831AG2-522 GEN
Solar/Wind Harmer
7.592
971447AH1-217 GEN
Solar/Wind Harmer
2.968
270494AE1-108_GEN
Solar/Wind Harmer
1.024
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.258
270455AD2-022 GEN
Solar/Wind Helper
1.379
270457AD2-023 GEN
Solar/Wind Helper
0.909
3151531CLOVER1
50/50
10.804
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.432
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.379
3151911BEARGRDN G1
50/50
1.068
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.072
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.851
315693AD1-088 GEN
Solar/Wind Harmer
21.559
962491AG1-098 GEN
Solar/Wind Harmer
25.329
970401AG2-262 GEN
Solar/Wind Harmer
2.6
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.713
963171AG1-166 GEN
Solar/Wind Harmer
1.592
971563AH1-280 GEN
Solar/Wind Harmer
3.185
3146926FARMVIL
Solar/Wind Harmer
0.162
971065AG2-659 GEN
Solar/Wind Harmer
8.611
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.716
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.549
971795AH1-408 GEN
Solar/Wind Harmer
8.343
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.428
971377AH1-170 GEN
Solar/Wind Harmer
1.1
3147623JAMES R
Solar/Wind Harmer
0.239
970937AG2-583 GEN
Solar/Wind Harmer
5.72
960081AF2-299 GEN
Solar/Wind Harmer
0.7
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.026
3152661PLYWOOD A
50/50
1.085
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.145
316222AC1-221 GEN
Solar/Wind Harmer
3.733
970099AG2-077 GEN
Solar/Wind Harmer
51.54
970933AG2-581 GEN
Solar/Wind Harmer
38.114
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.51
962561AG1-105 GEN
Solar/Wind Harmer
20.399
971741AH1-377 GEN
Solar/Wind Harmer
36.712
970301AG2-198 GEN
Solar/Wind Harmer
14.785
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.238
971775AH1-396 GEN
Solar/Wind Harmer
0.496
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.583
963191AG1-168 GEN
Solar/Wind Harmer
1.194
942751AE2-291 GEN
Solar/Wind Harmer
16.154
3147133PAMPLIN
Solar/Wind Harmer
0.294
3147133PAMPLIN
Solar/Wind Harmer
0.235
939181AE1-148 GEN
Solar/Wind Harmer
12.995
3146776BUCKING
Solar/Wind Harmer
0.801
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.666
971489AH1-241 GEN
Solar/Wind Harmer
5.502
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.098
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.671
3145593CAROLNA
Solar/Wind Harmer
0.077
315785AD2-033 C
Solar/Wind Harmer
2.542
970257AG2-171 GEN
Solar/Wind Harmer
9.929
959311AF2-222 GEN
Solar/Wind Harmer
27.421
963181AG1-167 GEN
Solar/Wind Harmer
1.194
3147133PAMPLIN
Solar/Wind Harmer
0.924
971193AH1-056 GEN
Solar/Wind Harmer
17.935
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.162
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.428
970221AG2-151 GEN
Solar/Wind Harmer
5.502
313506AB2-031 GEN
Solar/Wind Harmer
0.209
316313AB2-026
Solar/Wind Harmer
0.036
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.872
270018AE2-047 C O1
Solar/Wind Helper
0.395
G-007ALTFEXP_G-007A->PJM
CMTX
0.368
VTFLTFEXP_VFT->PJM
CMTX
0.961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.028
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.39
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.722
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:189.13 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:961.81
MW Contribution:2.79
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.752
3151611KERR 4
50/50
0.536
3151531CLOVER1
50/50
10.804
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.432
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.379
3151911BEARGRDN G1
50/50
1.068
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.072
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.851
315693AD1-088 GEN
Solar/Wind Harmer
21.559
962491AG1-098 GEN
Solar/Wind Harmer
25.329
970401AG2-262 GEN
Solar/Wind Harmer
2.6
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.713
963171AG1-166 GEN
Solar/Wind Harmer
1.592
971563AH1-280 GEN
Solar/Wind Harmer
3.185
3146926FARMVIL
Solar/Wind Harmer
0.162
971065AG2-659 GEN
Solar/Wind Harmer
8.611
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.716
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.549
971795AH1-408 GEN
Solar/Wind Harmer
8.343
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.428
971377AH1-170 GEN
Solar/Wind Harmer
1.1
3147623JAMES R
Solar/Wind Harmer
0.239
970937AG2-583 GEN
Solar/Wind Harmer
5.72
960081AF2-299 GEN
Solar/Wind Harmer
0.7
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.026
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.21
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.257
970865AG2-541 GEN
Solar/Wind Harmer
14.478
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.787
970163AG2-111 GEN
Solar/Wind Harmer
2.658
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.22
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.28
970681AG2-440 GEN
Solar/Wind Harmer
16.224
946301AF1-294 GEN
Solar/Wind Harmer
5.891
961791AG1-021 GEN
Solar/Wind Harmer
2.866
315657AE1-056 GEN
Solar/Wind Harmer
10.159
970285AG2-188 GEN
Solar/Wind Harmer
17.225
971845AH1-439 GEN
Solar/Wind Harmer
9.357
970831AG2-522 GEN
Solar/Wind Harmer
7.592
971447AH1-217 GEN
Solar/Wind Harmer
2.968
270494AE1-108_GEN
Solar/Wind Harmer
1.024
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.258
270455AD2-022 GEN
Solar/Wind Helper
1.379
270457AD2-023 GEN
Solar/Wind Helper
0.909
3152661PLYWOOD A
50/50
1.085
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.145
316222AC1-221 GEN
Solar/Wind Harmer
3.733
970099AG2-077 GEN
Solar/Wind Harmer
51.54
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.51
962561AG1-105 GEN
Solar/Wind Harmer
20.399
971741AH1-377 GEN
Solar/Wind Harmer
36.712
970413AG2-270 GEN
50/50
47.147
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.068
3151261ROARAP2
50/50
0.075
24728405LEESVG
50/50
0.073
316283AC2-100 C
Solar/Wind Harmer
1.77
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.582
316478AD1-087 GEN
Solar/Wind Harmer
1.767
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.704
970909AG2-566 GEN
Solar/Wind Harmer
3.696
316131AB2-060 GEN
Solar/Wind Harmer
1.015
964241AG1-285 GEN
Solar/Wind Harmer
21.263
315785AD2-033 C
Solar/Wind Harmer
2.542
970257AG2-171 GEN
Solar/Wind Harmer
9.929
959311AF2-222 GEN
Solar/Wind Harmer
27.421
963181AG1-167 GEN
Solar/Wind Harmer
1.194
3147133PAMPLIN
Solar/Wind Harmer
0.924
971193AH1-056 GEN
Solar/Wind Harmer
17.935
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.162
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.428
970221AG2-151 GEN
Solar/Wind Harmer
5.502
313506AB2-031 GEN
Solar/Wind Harmer
0.209
316313AB2-026
Solar/Wind Harmer
0.036
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.872
270018AE2-047 C O1
Solar/Wind Helper
0.395
970301AG2-198 GEN
Solar/Wind Harmer
14.785
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.238
971775AH1-396 GEN
Solar/Wind Harmer
0.496
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.583
963191AG1-168 GEN
Solar/Wind Harmer
1.194
942751AE2-291 GEN
Solar/Wind Harmer
16.154
3147133PAMPLIN
Solar/Wind Harmer
0.294
3147133PAMPLIN
Solar/Wind Harmer
0.235
939181AE1-148 GEN
Solar/Wind Harmer
12.995
3146776BUCKING
Solar/Wind Harmer
0.801
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.666
971489AH1-241 GEN
Solar/Wind Harmer
5.502
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.098
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.671
3145593CAROLNA
Solar/Wind Harmer
0.077
G-007ALTFEXP_G-007A->PJM
CMTX
0.368
VTFLTFEXP_VFT->PJM
CMTX
0.961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.028
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.39
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.722
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.04 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:552.01
MW Contribution:2.63
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
5.491
3151611KERR 4
50/50
0.291
3151621KERR 5
50/50
0.291
3151631KERR 6
50/50
0.291
3151641KERR 7
50/50
0.291
3147173SINAI
Solar/Wind Harmer
-0.044
3147243WELCO
Solar/Wind Harmer
-0.027
316118AC1-105 GEN
Solar/Wind Harmer
2.738
970865AG2-541 GEN
Solar/Wind Harmer
13.887
316123AC1-075 GEN
Solar/Wind Harmer
2.983
970165AG2-112 GEN
Solar/Wind Harmer
2.626
970163AG2-111 GEN
Solar/Wind Harmer
2.505
3152661PLYWOOD A
50/50
0.786
3144293JTRSVLE
50/50
0.694
3144293JTRSVLE
50/50
0.585
970535AG2-341 GEN
50/50
3.063
316222AC1-221 GEN
Solar/Wind Harmer
9.436
3146843MT LREL
Solar/Wind Harmer
-0.035
3146843MT LREL
Solar/Wind Harmer
-0.035
964791AG1-342 GEN
Solar/Wind Harmer
7.565
3151531CLOVER1
50/50
5.517
3144293JTRSVLE
50/50
0.694
3151601KERR 3
50/50
0.291
3151581KERR 1
50/50
0.104
315687AD1-152 GEN
Solar/Wind Harmer
5.005
316003AC1-222 GEN
Solar/Wind Harmer
3.954
970401AG2-262 GEN
Solar/Wind Harmer
2.311
316237AB2-079_GEN
Solar/Wind Harmer
0.713
970685AG2-442 GEN
Solar/Wind Harmer
20.268
963171AG1-166 GEN
Solar/Wind Harmer
2.887
971563AH1-280 GEN
Solar/Wind Harmer
2.887
972003AH1-546 GEN
Solar/Wind Harmer
11.349
316322AB2-045
Solar/Wind Harmer
0.765
3146776BUCKING
Solar/Wind Harmer
-0.009
3146926FARMVIL
Solar/Wind Harmer
-0.013
962491AG1-098 GEN
Solar/Wind Harmer
15.104
315693AD1-088 GEN
Solar/Wind Harmer
11.29
957481AF2-042 GEN
Solar/Wind Harmer
70.478
971065AG2-659 GEN
Solar/Wind Harmer
6.314
316129AC1-054 GEN
Solar/Wind Harmer
1.051
3147043LAWRENC
Adder
0.955
971795AH1-408 GEN
Solar/Wind Harmer
7.701
3147123OTTER R
Solar/Wind Harmer
-0.006
960081AF2-299 GEN
Solar/Wind Harmer
0.766
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.507
940641AE2-051 GEN
Solar/Wind Harmer
5.976
939411AE1-173 GEN
Solar/Wind Harmer
30.063
270016AE1-250 BESS
Solar/Wind Helper
0.571
316239AB2-077_GEN
Solar/Wind Harmer
0.713
316238AB2-078_GEN
Solar/Wind Harmer
0.713
3144303KENBRDG
Solar/Wind Harmer
-0.019
971443AH1-215 GEN
Solar/Wind Harmer
4.576
970683AG2-441 GEN
Solar/Wind Harmer
18.096
970681AG2-440 GEN
Solar/Wind Harmer
14.477
946301AF1-294 GEN
Solar/Wind Harmer
5.918
961791AG1-021 GEN
Solar/Wind Harmer
2.887
315657AE1-056 GEN
Solar/Wind Harmer
8.642
971845AH1-439 GEN
Solar/Wind Harmer
12.087
970285AG2-188 GEN
Solar/Wind Harmer
19.908
970831AG2-522 GEN
Solar/Wind Harmer
5.656
971967AH1-528 GEN
Solar/Wind Harmer
18.182
970673AG2-436 GEN
Solar/Wind Harmer
14.386
970673AG2-436 GEN
Solar/Wind Harmer
7.284
946281AF1-292 GEN
Solar/Wind Harmer
0.153
941031AE2-094 GEN
Solar/Wind Harmer
12.694
944011AF1-069 GEN
Solar/Wind Harmer
3.977
270455AD2-022 GEN
Solar/Wind Helper
1.808
270457AD2-023 GEN
Solar/Wind Helper
1.191
270069AE2-166 C O1
Solar/Wind Helper
0.543
970413AG2-270 GEN
50/50
24.076
3144293JTRSVLE
50/50
0.694
3151591KERR 2
50/50
0.291
316283AC2-100 C
Solar/Wind Harmer
8.862
316248AF1-058 C
Solar/Wind Harmer
1.328
960061AF2-297 GEN
Solar/Wind Harmer
22.033
971683AH1-343 GEN
Solar/Wind Harmer
16.127
316478AD1-087 GEN
Solar/Wind Harmer
2.53
316486AD2-202 GEN
Solar/Wind Harmer
0.741
316131AB2-060 GEN
Solar/Wind Harmer
2.525
964241AG1-285 GEN
Solar/Wind Harmer
18.238
315785AD2-033 C
Solar/Wind Harmer
5.274
970257AG2-171 GEN
Solar/Wind Harmer
8.716
959311AF2-222 GEN
Solar/Wind Harmer
24.232
963181AG1-167 GEN
Solar/Wind Harmer
2.165
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.403
942461AE2-259 GEN
Solar/Wind Harmer
3.442
3146776BUCKING
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.013
970909AG2-566 GEN
Solar/Wind Harmer
2.153
3147043LAWRENC
Solar/Wind Harmer
-0.007
966621AG1-532 GEN
Solar/Wind Harmer
0.138
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.507
270018AE2-047 C O1
Solar/Wind Helper
0.567
943811AF1-049 GEN
Solar/Wind Helper
0.923
962561AG1-105 GEN
Solar/Wind Harmer
18.89
942751AE2-291 GEN
Solar/Wind Harmer
14.981
313527AB2-043 GEN
Solar/Wind Harmer
3.802
970323AG2-213 GEN
Solar/Wind Harmer
11.621
971775AH1-396 GEN
Solar/Wind Harmer
1.655
316034AC1-036 C
Solar/Wind Harmer
0.431
958211AF2-115 GEN
Solar/Wind Harmer
3.609
963191AG1-168 GEN
Solar/Wind Harmer
2.165
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.091
3146776BUCKING
Solar/Wind Harmer
-0.007
970301AG2-198 GEN
Solar/Wind Harmer
11.339
971741AH1-377 GEN
Solar/Wind Harmer
26.337
970099AG2-077 GEN
Solar/Wind Harmer
28.191
939181AE1-148 GEN
Solar/Wind Harmer
9.651
970933AG2-581 GEN
Solar/Wind Harmer
12.282
972187AH1-678 GEN
Adder
1.759
972185AH1-677 GEN
Adder
3.44
316217AC1-145 GEN
Solar/Wind Harmer
1.085
316197AC1-042 GEN
Solar/Wind Harmer
0.823
942671AE2-283 GEN
Solar/Wind Harmer
2.215
270013AE1-250 PV
Solar/Wind Helper
0.571
270336AE1-100 GEN
Solar/Wind Helper
0.558
G-007ALTFEXP_G-007A->PJM
CMTX
1.744
VTFLTFEXP_VFT->PJM
CMTX
4.632
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.206
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.484
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
6.697
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.87
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.198
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.768
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.65 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:1006.31
MW Contribution:0.46
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
2.963
3144293JTRSVLE
50/50
0.501
970413AG2-270 GEN
50/50
9.511
966251AG1-494 GEN
50/50
1.191
3151591KERR 2
50/50
0.134
970221AG2-151 GEN
Solar/Wind Harmer
15.115
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.865
3147133PAMPLIN
Solar/Wind Harmer
0.496
971193AH1-056 GEN
Solar/Wind Harmer
9.619
963181AG1-167 GEN
Solar/Wind Harmer
0.594
959311AF2-222 GEN
Solar/Wind Harmer
11.056
970257AG2-171 GEN
Solar/Wind Harmer
3.847
315785AD2-033 C
Solar/Wind Harmer
0.931
958131AF2-107 GEN
Solar/Wind Harmer
2.944
316478AD1-087 GEN
Solar/Wind Harmer
0.355
316486AD2-202 GEN
Solar/Wind Harmer
0.104
964241AG1-285 GEN
Solar/Wind Harmer
6.611
316131AB2-060 GEN
Solar/Wind Harmer
0.283
3148013FISHERV
Solar/Wind Harmer
0.07
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.916
971683AH1-343 GEN
Solar/Wind Harmer
2.335
316313AB2-026
Solar/Wind Helper
1.246
316258AE1-075 C
Solar/Wind Helper
1.121
316405AF2-144 C
Solar/Wind Helper
0.934
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.714
315839AE2-212 C
Solar/Wind Helper
0.156
972205AH1-687 GEN
50/50
14.45
3151541CLOVER2
50/50
2.169
3151611KERR 4
50/50
0.134
3151621KERR 5
50/50
0.134
3151631KERR 6
50/50
0.134
3151641KERR 7
50/50
0.134
971447AH1-217 GEN
Solar/Wind Harmer
8.134
971845AH1-439 GEN
Solar/Wind Harmer
11.699
970285AG2-188 GEN
Solar/Wind Harmer
19.821
270494AE1-108_GEN
Solar/Wind Harmer
2.719
315657AE1-056 GEN
Solar/Wind Harmer
5.448
946301AF1-294 GEN
Solar/Wind Harmer
2.929
961791AG1-021 GEN
Solar/Wind Harmer
1.425
970683AG2-441 GEN
Solar/Wind Harmer
8.983
970681AG2-440 GEN
Solar/Wind Harmer
7.186
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
1.998
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.187
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.068
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.117
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.456
970163AG2-111 GEN
Solar/Wind Harmer
0.435
316233AE1-074 FULL
Solar/Wind Helper
0.381
316312AB1-027
Solar/Wind Helper
0.218
316132AB2-190 GEN1
Solar/Wind Helper
0.644
3144293JTRSVLE
50/50
0.501
3144293JTRSVLE
50/50
0.422
970535AG2-341 GEN
50/50
1.342
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.115
3146776BUCKING
Solar/Wind Harmer
1.047
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.012
970301AG2-198 GEN
Solar/Wind Harmer
7.46
971741AH1-377 GEN
Solar/Wind Harmer
16.096
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.781
963191AG1-168 GEN
Solar/Wind Harmer
0.594
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.129
971775AH1-396 GEN
Solar/Wind Harmer
0.192
970099AG2-077 GEN
Solar/Wind Harmer
11.625
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.75
964791AG1-342 GEN
Solar/Wind Harmer
1.467
3146843MT LREL
Solar/Wind Harmer
0.076
3146843MT LREL
Solar/Wind Harmer
0.076
939181AE1-148 GEN
Solar/Wind Harmer
3.307
3143526WINTERP
Solar/Wind Helper
1.298
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316075AC2-137 C
Solar/Wind Helper
0.174
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.963
3144293JTRSVLE
50/50
0.501
3151531CLOVER1
50/50
2.179
3151601KERR 3
50/50
0.134
3151581KERR 1
50/50
0.048
316336AC2-165 C
Solar/Wind Harmer
0.025
970937AG2-583 GEN
Solar/Wind Harmer
28.676
972003AH1-546 GEN
Solar/Wind Harmer
13.102
971377AH1-170 GEN
Solar/Wind Harmer
3.023
3147623JAMES R
Solar/Wind Harmer
0.657
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.792
971563AH1-280 GEN
Solar/Wind Harmer
1.583
970685AG2-442 GEN
Solar/Wind Harmer
10.06
962491AG1-098 GEN
Solar/Wind Harmer
7.008
315693AD1-088 GEN
Solar/Wind Harmer
5.758
957481AF2-042 GEN
Solar/Wind Harmer
29.062
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.448
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3143226MDLTHAN
Solar/Wind Helper
0.301
3143526WINTERP
Solar/Wind Helper
1.298
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.298
3142416OLDCHRC
Solar/Wind Helper
0.114
316458AB2-190 GEN2
Solar/Wind Helper
0.644
3142433PROV 92
Solar/Wind Helper
0.447
CPLELTFEXP_CPLE->PJM
CLTF
0.579
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.662
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.157
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.592
MECLTFEXP_MEC->PJM
CLTF
1.02
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.35
LGEELTFEXP_LGEE->PJM
CLTF
0.439
WECLTFEXP_WEC->PJM
CLTF
0.224
LAGNLTFEXP_LAGN->PJM
CLTF
1.347
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.952
TVALTFEXP_TVA->PJM
CLTF
0.702

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.22 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:1002.88
MW Contribution:0.46
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.963
3144293JTRSVLE
50/50
0.501
3151531CLOVER1
50/50
2.179
3151601KERR 3
50/50
0.134
3151581KERR 1
50/50
0.048
316336AC2-165 C
Solar/Wind Harmer
0.025
970937AG2-583 GEN
Solar/Wind Harmer
28.676
972003AH1-546 GEN
Solar/Wind Harmer
13.102
971377AH1-170 GEN
Solar/Wind Harmer
3.023
3147623JAMES R
Solar/Wind Harmer
0.657
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.792
971563AH1-280 GEN
Solar/Wind Harmer
1.583
970685AG2-442 GEN
Solar/Wind Harmer
10.06
962491AG1-098 GEN
Solar/Wind Harmer
7.008
315693AD1-088 GEN
Solar/Wind Harmer
5.758
957481AF2-042 GEN
Solar/Wind Harmer
29.062
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.448
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3143226MDLTHAN
Solar/Wind Helper
0.301
3143526WINTERP
Solar/Wind Helper
1.298
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.298
3142416OLDCHRC
Solar/Wind Helper
0.114
316458AB2-190 GEN2
Solar/Wind Helper
0.644
3142433PROV 92
Solar/Wind Helper
0.447
3151921BEARGRDN G2
50/50
2.963
3144293JTRSVLE
50/50
0.501
970413AG2-270 GEN
50/50
9.511
966251AG1-494 GEN
50/50
1.191
3151591KERR 2
50/50
0.134
970221AG2-151 GEN
Solar/Wind Harmer
15.115
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.865
3147133PAMPLIN
Solar/Wind Harmer
0.496
971193AH1-056 GEN
Solar/Wind Harmer
9.619
963181AG1-167 GEN
Solar/Wind Harmer
0.594
959311AF2-222 GEN
Solar/Wind Harmer
11.056
970257AG2-171 GEN
Solar/Wind Harmer
3.847
315785AD2-033 C
Solar/Wind Harmer
0.931
958131AF2-107 GEN
Solar/Wind Harmer
2.944
316478AD1-087 GEN
Solar/Wind Harmer
0.355
316486AD2-202 GEN
Solar/Wind Harmer
0.104
964241AG1-285 GEN
Solar/Wind Harmer
6.611
316131AB2-060 GEN
Solar/Wind Harmer
0.283
3148013FISHERV
Solar/Wind Harmer
0.07
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.916
971683AH1-343 GEN
Solar/Wind Harmer
2.335
316313AB2-026
Solar/Wind Helper
1.246
316258AE1-075 C
Solar/Wind Helper
1.121
316405AF2-144 C
Solar/Wind Helper
0.934
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.714
315839AE2-212 C
Solar/Wind Helper
0.156
972205AH1-687 GEN
50/50
14.45
3151541CLOVER2
50/50
2.169
3151611KERR 4
50/50
0.134
3151621KERR 5
50/50
0.134
3151631KERR 6
50/50
0.134
3151641KERR 7
50/50
0.134
971447AH1-217 GEN
Solar/Wind Harmer
8.134
971845AH1-439 GEN
Solar/Wind Harmer
11.699
970285AG2-188 GEN
Solar/Wind Harmer
19.821
270494AE1-108_GEN
Solar/Wind Harmer
2.719
315657AE1-056 GEN
Solar/Wind Harmer
5.448
946301AF1-294 GEN
Solar/Wind Harmer
2.929
961791AG1-021 GEN
Solar/Wind Harmer
1.425
970683AG2-441 GEN
Solar/Wind Harmer
8.983
970681AG2-440 GEN
Solar/Wind Harmer
7.186
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
1.998
971967AH1-528 GEN
Solar/Wind Harmer
17.782
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.187
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.068
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.117
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.456
970163AG2-111 GEN
Solar/Wind Harmer
0.435
316233AE1-074 FULL
Solar/Wind Helper
0.381
316312AB1-027
Solar/Wind Helper
0.218
316132AB2-190 GEN1
Solar/Wind Helper
0.644
3144293JTRSVLE
50/50
0.501
3144293JTRSVLE
50/50
0.422
970535AG2-341 GEN
50/50
1.342
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.115
3146776BUCKING
Solar/Wind Harmer
1.047
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.012
970301AG2-198 GEN
Solar/Wind Harmer
7.46
971741AH1-377 GEN
Solar/Wind Harmer
16.096
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.781
963191AG1-168 GEN
Solar/Wind Harmer
0.594
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.129
971775AH1-396 GEN
Solar/Wind Harmer
0.192
970933AG2-581 GEN
Solar/Wind Harmer
8.892
970099AG2-077 GEN
Solar/Wind Harmer
11.625
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.75
964791AG1-342 GEN
Solar/Wind Harmer
1.467
3146843MT LREL
Solar/Wind Harmer
0.076
3146843MT LREL
Solar/Wind Harmer
0.076
939181AE1-148 GEN
Solar/Wind Harmer
3.307
3143526WINTERP
Solar/Wind Helper
1.298
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316075AC2-137 C
Solar/Wind Helper
0.174
CPLELTFEXP_CPLE->PJM
CLTF
0.579
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.662
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.157
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.592
MECLTFEXP_MEC->PJM
CLTF
1.02
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.35
LGEELTFEXP_LGEE->PJM
CLTF
0.439
WECLTFEXP_WEC->PJM
CLTF
0.224
LAGNLTFEXP_LAGN->PJM
CLTF
1.347
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.952
TVALTFEXP_TVA->PJM
CLTF
0.702

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.1 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5539.41
MW Contribution:1.87
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
941031AE2-094 GEN
Solar/Wind Harmer
138.271
944011AF1-069 GEN
Solar/Wind Harmer
45.178
970673AG2-436 GEN
Solar/Wind Harmer
149.315
970673AG2-436 GEN
Solar/Wind Harmer
99.544
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
970533AG2-339 GEN
50/50
66.733
970531AG2-338 GEN
50/50
26.693
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
3130156CHOWAN
Solar/Wind Helper
0.227
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.36 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6013.11
MW Contribution:2.46
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
970533AG2-339 GEN
50/50
66.733
970531AG2-338 GEN
50/50
26.693
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
941031AE2-094 GEN
Solar/Wind Harmer
158.157
944011AF1-069 GEN
Solar/Wind Harmer
49.556
970673AG2-436 GEN
Solar/Wind Harmer
165.209
970673AG2-436 GEN
Solar/Wind Harmer
83.65
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.82 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5986.29
MW Contribution:2.46
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
941031AE2-094 GEN
Solar/Wind Harmer
157.012
944011AF1-069 GEN
Solar/Wind Harmer
49.197
970673AG2-436 GEN
Solar/Wind Harmer
164.043
970673AG2-436 GEN
Solar/Wind Harmer
83.06
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
970533AG2-339 GEN
50/50
66.25
970531AG2-338 GEN
50/50
26.5
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.15 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5902.9
MW Contribution:2.43
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
941031AE2-094 GEN
Solar/Wind Harmer
155.676
944011AF1-069 GEN
Solar/Wind Harmer
48.778
970673AG2-436 GEN
Solar/Wind Harmer
162.646
970673AG2-436 GEN
Solar/Wind Harmer
82.352
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
970533AG2-339 GEN
50/50
65.686
970531AG2-338 GEN
50/50
26.274
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.76 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:673.04
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.2 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:658.38
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.07 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:797.37
MW Contribution:1.2
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.03 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:797.08
MW Contribution:1.2
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.84 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:774.79
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
3152661PLYWOOD A
50/50
0.346
970933AG2-581 GEN
Solar/Wind Harmer
36.681
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
73.556
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P4_#10213_05CLOVRD 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.79 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:450.0
MW Contribution:0.89
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
3.133
24684405SMG2
50/50
3.112
24684505SMG3
50/50
1.925
24684305SMG1
50/50
1.128
316123AC1-075 GEN
Solar/Wind Harmer
1.01
970165AG2-112 GEN
Solar/Wind Harmer
0.889
970163AG2-111 GEN
Solar/Wind Harmer
0.849
270455AD2-022 GEN
Solar/Wind Helper
0.935
270457AD2-023 GEN
Solar/Wind Helper
0.616
24684705SMG5
50/50
1.198
970481AG2-311 GEN
50/50
16.703
24728405LEESVG
50/50
0.334
3151561HALLBR1
50/50
0.448
970223AG2-152 GEN
Solar/Wind Harmer
78.334
270016AE1-250 BESS
Solar/Wind Harmer
12.518
270574AD1-017 GEN2
Solar/Wind Harmer
22.147
270173AC1-122 GEN
Solar/Wind Harmer
3.243
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
8.005
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.228
24728405LEESVG
50/50
0.336
270197AD1-017 GEN1
Solar/Wind Harmer
6.655
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
8.005
958131AF2-107 GEN
Solar/Wind Harmer
2.397
270013AE1-250 PV
Solar/Wind Harmer
12.518
316217AC1-145 GEN
Solar/Wind Harmer
3.465
316197AC1-042 GEN
Solar/Wind Harmer
2.627
942671AE2-283 GEN
Solar/Wind Harmer
7.071
942751AE2-291 GEN
Solar/Wind Harmer
7.417
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.589
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.768
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.079
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.234
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.225
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P4_#10210_05CLOVRD 138_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.54 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:449.01
MW Contribution:0.89
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
1.197
970481AG2-311 GEN
50/50
16.68
24728405LEESVG
50/50
0.334
3151561HALLBR1
50/50
0.448
970223AG2-152 GEN
Solar/Wind Harmer
78.303
270016AE1-250 BESS
Solar/Wind Harmer
12.513
270574AD1-017 GEN2
Solar/Wind Harmer
22.132
270173AC1-122 GEN
Solar/Wind Harmer
3.239
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
7.991
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.215
316123AC1-075 GEN
Solar/Wind Harmer
1.008
970165AG2-112 GEN
Solar/Wind Harmer
0.887
970163AG2-111 GEN
Solar/Wind Harmer
0.846
270455AD2-022 GEN
Solar/Wind Helper
0.937
270457AD2-023 GEN
Solar/Wind Helper
0.617
24684605SMG4
50/50
3.128
24728405LEESVG
50/50
0.335
270197AD1-017 GEN1
Solar/Wind Harmer
6.65
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
7.991
958131AF2-107 GEN
Solar/Wind Harmer
2.391
24684405SMG2
50/50
3.108
24684505SMG3
50/50
1.922
24684305SMG1
50/50
1.127
270013AE1-250 PV
Solar/Wind Harmer
12.513
316217AC1-145 GEN
Solar/Wind Harmer
3.459
316197AC1-042 GEN
Solar/Wind Harmer
2.622
942671AE2-283 GEN
Solar/Wind Harmer
7.059
942751AE2-291 GEN
Solar/Wind Harmer
7.401
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.59
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.771
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.078
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.237
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.226
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.11 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:443.41
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
0.962
970481AG2-311 GEN
50/50
13.411
24728405LEESVG
50/50
0.291
3151561HALLBR1
50/50
0.484
970223AG2-152 GEN
Solar/Wind Harmer
74.821
270016AE1-250 BESS
Solar/Wind Harmer
11.82
270574AD1-017 GEN2
Solar/Wind Harmer
20.069
24684605SMG4
50/50
2.515
24728405LEESVG
50/50
0.292
316123AC1-075 GEN
Solar/Wind Harmer
2.274
270173AC1-122 GEN
Solar/Wind Harmer
2.676
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
8.047
3147123OTTER R
Solar/Wind Harmer
-0.013
316003AC1-222 GEN
Solar/Wind Harmer
2.058
962751AG1-124 GEN
Solar/Wind Harmer
5.305
970165AG2-112 GEN
Solar/Wind Harmer
2.002
970163AG2-111 GEN
Solar/Wind Harmer
1.91
970865AG2-541 GEN
Solar/Wind Harmer
8.563
270455AD2-022 GEN
Solar/Wind Helper
1.103
270457AD2-023 GEN
Solar/Wind Helper
0.727
24684405SMG2
50/50
2.499
24684505SMG3
50/50
1.545
24684305SMG1
50/50
0.906
270013AE1-250 PV
Solar/Wind Harmer
11.82
316217AC1-145 GEN
Solar/Wind Harmer
3.483
316197AC1-042 GEN
Solar/Wind Harmer
2.64
942671AE2-283 GEN
Solar/Wind Harmer
7.108
942751AE2-291 GEN
Solar/Wind Harmer
13.438
316222AC1-221 GEN
Solar/Wind Helper
0.638
270197AD1-017 GEN1
Solar/Wind Harmer
6.03
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
8.047
971683AH1-343 GEN
Solar/Wind Harmer
9.09
958131AF2-107 GEN
Solar/Wind Harmer
2.414
316283AC2-100 C
Solar/Wind Helper
0.6
943811AF1-049 GEN
Solar/Wind Helper
0.69
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.72
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.52
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
0.005
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.563
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.98 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:442.88
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
2.515
24728405LEESVG
50/50
0.292
270197AD1-017 GEN1
Solar/Wind Harmer
6.031
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
8.047
971683AH1-343 GEN
Solar/Wind Harmer
9.091
958131AF2-107 GEN
Solar/Wind Harmer
2.414
316283AC2-100 C
Solar/Wind Helper
0.599
943811AF1-049 GEN
Solar/Wind Helper
0.69
24684405SMG2
50/50
2.499
24684505SMG3
50/50
1.546
24684305SMG1
50/50
0.906
270013AE1-250 PV
Solar/Wind Harmer
11.821
316217AC1-145 GEN
Solar/Wind Harmer
3.483
316197AC1-042 GEN
Solar/Wind Harmer
2.64
942671AE2-283 GEN
Solar/Wind Harmer
7.108
942751AE2-291 GEN
Solar/Wind Harmer
13.439
316123AC1-075 GEN
Solar/Wind Harmer
2.275
970865AG2-541 GEN
Solar/Wind Harmer
8.564
970165AG2-112 GEN
Solar/Wind Harmer
2.003
970163AG2-111 GEN
Solar/Wind Harmer
1.91
270455AD2-022 GEN
Solar/Wind Helper
1.103
270457AD2-023 GEN
Solar/Wind Helper
0.727
24684705SMG5
50/50
0.962
970481AG2-311 GEN
50/50
13.412
24728405LEESVG
50/50
0.291
3151561HALLBR1
50/50
0.484
970223AG2-152 GEN
Solar/Wind Harmer
74.825
270016AE1-250 BESS
Solar/Wind Harmer
11.821
270574AD1-017 GEN2
Solar/Wind Harmer
20.07
270173AC1-122 GEN
Solar/Wind Harmer
2.677
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
8.047
3147123OTTER R
Solar/Wind Harmer
-0.013
316003AC1-222 GEN
Solar/Wind Harmer
2.058
962751AG1-124 GEN
Solar/Wind Harmer
5.305
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.719
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.517
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
0.006
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.562
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.67 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:433.83
MW Contribution:0.66
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
0.932
970481AG2-311 GEN
50/50
12.994
24728405LEESVG
50/50
0.263
3151561HALLBR1
50/50
0.36
970223AG2-152 GEN
Solar/Wind Harmer
74.853
270016AE1-250 BESS
Solar/Wind Harmer
11.803
270574AD1-017 GEN2
Solar/Wind Harmer
19.897
270173AC1-122 GEN
Solar/Wind Harmer
2.59
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.442
316123AC1-075 GEN
Solar/Wind Harmer
0.751
970165AG2-112 GEN
Solar/Wind Harmer
0.661
970163AG2-111 GEN
Solar/Wind Harmer
0.63
270455AD2-022 GEN
Solar/Wind Helper
1.03
270457AD2-023 GEN
Solar/Wind Helper
0.678
24684405SMG2
50/50
2.421
24684505SMG3
50/50
1.497
24684305SMG1
50/50
0.878
270013AE1-250 PV
Solar/Wind Harmer
11.803
316217AC1-145 GEN
Solar/Wind Harmer
2.788
316197AC1-042 GEN
Solar/Wind Harmer
2.114
942671AE2-283 GEN
Solar/Wind Harmer
5.691
942751AE2-291 GEN
Solar/Wind Harmer
5.679
24684605SMG4
50/50
2.437
24728405LEESVG
50/50
0.264
270197AD1-017 GEN1
Solar/Wind Harmer
5.979
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.442
958131AF2-107 GEN
Solar/Wind Harmer
2.282
3147123OTTER R
Solar/Wind Harmer
-0.009
962751AG1-124 GEN
Solar/Wind Harmer
5.14
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.539
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.087
MECLTFEXP_MEC->PJM
CLTF
0.24
SIGELTFEXP_SIGE->PJM
CLTF
0.011
NYPJM->LTFIMP_NY
CLTF
0.163
LGEELTFEXP_LGEE->PJM
CLTF
0.191
WECLTFEXP_WEC->PJM
CLTF
0.083
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.268
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P7-1_#10830___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10830___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.56 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:413.78
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
316123AC1-075 GEN
Solar/Wind Harmer
0.835
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P2-2_#6213_05WLAKE 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.51 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:413.6
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
0.835
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P2-2_#6212_05WLAKE 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6212_05WLAKE 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.18 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:404.45
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
316123AC1-075 GEN
Solar/Wind Harmer
0.835
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:211.67 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1447.79
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3151541CLOVER2
50/50
6.835
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:211.61 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1447.4
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:207.99 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1422.62
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970933AG2-581 GEN
Solar/Wind Harmer
36.495
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
971967AH1-528 GEN
Solar/Wind Harmer
73.183
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3138266HYDRAULIC
Solar/Wind Helper
0.005
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:206.17 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1153.12
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970933AG2-581 GEN
Solar/Wind Harmer
27.718
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
971967AH1-528 GEN
Solar/Wind Harmer
55.434
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:203.59 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1138.68
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.95 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1381.35
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963181AG1-167 GEN
Solar/Wind Harmer
4.787
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.95 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1381.35
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:128.21 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:876.96
MW Contribution:0.75
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3151541CLOVER2
50/50
2.829
970285AG2-188 GEN
Solar/Wind Harmer
63.51
315657AE1-056 GEN
Solar/Wind Harmer
15.784
946301AF1-294 GEN
Solar/Wind Harmer
10.059
961791AG1-021 GEN
Solar/Wind Harmer
4.907
970683AG2-441 GEN
Solar/Wind Harmer
27.489
970681AG2-440 GEN
Solar/Wind Harmer
21.992
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.004
316239AB2-077_GEN
Solar/Wind Harmer
0.621
316238AB2-078_GEN
Solar/Wind Harmer
0.621
316118AC1-105 GEN
Solar/Wind Harmer
0.972
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.033
970865AG2-541 GEN
Solar/Wind Harmer
3.923
946281AF1-292 GEN
Solar/Wind Harmer
0.19
316087AB2-174 GEN
Solar/Wind Harmer
1.178
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.853
970165AG2-112 GEN
Solar/Wind Harmer
0.751
970163AG2-111 GEN
Solar/Wind Harmer
0.717
971967AH1-528 GEN
Solar/Wind Harmer
14.188
315607AA1-063A GEN
Solar/Wind Harmer
0.715
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.499
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.18
3144293JTRSVLE
50/50
0.994
970535AG2-341 GEN
50/50
2.836
3152661PLYWOOD A
50/50
0.267
970301AG2-198 GEN
Solar/Wind Harmer
21.257
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.133
963191AG1-168 GEN
Solar/Wind Harmer
3.68
971741AH1-377 GEN
Solar/Wind Harmer
43.417
316034AC1-036 C
Solar/Wind Harmer
0.574
970323AG2-213 GEN
Solar/Wind Harmer
15.434
971775AH1-396 GEN
Solar/Wind Harmer
2.198
313527AB2-043 GEN
Solar/Wind Harmer
3.442
962561AG1-105 GEN
Solar/Wind Harmer
9.457
939181AE1-148 GEN
Solar/Wind Harmer
9.083
964791AG1-342 GEN
Solar/Wind Harmer
3.423
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.098
970933AG2-581 GEN
Solar/Wind Harmer
9.079
316181AB2-040 GEN
Solar/Wind Harmer
1.138
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.878
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.905
3145783HORNRTN
Solar/Wind Harmer
0.724
3145783HORNRTN
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.769
316426AA2-053 GEN
Solar/Wind Harmer
0.748
942751AE2-291 GEN
Solar/Wind Harmer
4.333
316274AC1-208 GEN
Solar/Wind Harmer
0.717
972187AH1-678 GEN
Adder
1.63
3146776BUCKING
Solar/Wind Helper
3.482
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.994
3144293JTRSVLE
50/50
1.18
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.405
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.535
970909AG2-566 GEN
Solar/Wind Harmer
4.036
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.307
963181AG1-167 GEN
Solar/Wind Harmer
3.68
959311AF2-222 GEN
Solar/Wind Harmer
33.514
970257AG2-171 GEN
Solar/Wind Harmer
11.575
315785AD2-033 C
Solar/Wind Harmer
6.609
964241AG1-285 GEN
Solar/Wind Harmer
19.233
316131AB2-060 GEN
Solar/Wind Harmer
2.359
316478AD1-087 GEN
Solar/Wind Harmer
1.29
316486AD2-202 GEN
Solar/Wind Harmer
0.378
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.371
960061AF2-297 GEN
Solar/Wind Harmer
6.151
971683AH1-343 GEN
Solar/Wind Harmer
4.535
966621AG1-532 GEN
Solar/Wind Harmer
0.172
313506AB2-031 GEN
Solar/Wind Harmer
0.656
316283AC2-100 C
Solar/Wind Harmer
0.705
316210AC1-098 GEN
Solar/Wind Harmer
0.995
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.306
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.125
3144293JTRSVLE
50/50
1.18
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.843
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.907
971563AH1-280 GEN
Solar/Wind Harmer
4.907
970685AG2-442 GEN
Solar/Wind Harmer
30.788
962491AG1-098 GEN
Solar/Wind Harmer
14.151
316237AB2-079_GEN
Solar/Wind Harmer
0.621
315693AD1-088 GEN
Solar/Wind Harmer
9.998
970401AG2-262 GEN
Solar/Wind Harmer
1.046
957481AF2-042 GEN
Solar/Wind Harmer
45.244
315687AD1-152 GEN
Solar/Wind Harmer
1.611
971065AG2-659 GEN
Solar/Wind Harmer
6.471
316129AC1-054 GEN
Solar/Wind Harmer
1.098
3147043LAWRENC
Adder
0.994
316003AC1-222 GEN
Solar/Wind Harmer
1.108
971795AH1-408 GEN
Solar/Wind Harmer
8.341
960081AF2-299 GEN
Solar/Wind Harmer
0.953
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316212AC1-099_GEN
Solar/Wind Harmer
0.553
316322AB2-045
Solar/Wind Helper
0.97
3146776BUCKING
Solar/Wind Helper
0.348
316336AC2-165 C
Solar/Wind Helper
1.454
CPLELTFEXP_CPLE->PJM
CLTF
3.717
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.651
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.966
MECLTFEXP_MEC->PJM
CLTF
0.645
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.186
WECLTFEXP_WEC->PJM
CLTF
0.097
LAGNLTFEXP_LAGN->PJM
CLTF
1.842
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.457
TVALTFEXP_TVA->PJM
CLTF
0.904

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.06 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:875.95
MW Contribution:0.79
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.289
3151621KERR 5
50/50
0.289
3151631KERR 6
50/50
0.289
3151641KERR 7
50/50
0.289
3151541CLOVER2
50/50
2.941
970285AG2-188 GEN
Solar/Wind Harmer
63.831
315657AE1-056 GEN
Solar/Wind Harmer
15.969
946301AF1-294 GEN
Solar/Wind Harmer
10.188
961791AG1-021 GEN
Solar/Wind Harmer
4.97
970683AG2-441 GEN
Solar/Wind Harmer
27.899
970681AG2-440 GEN
Solar/Wind Harmer
22.32
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.111
316239AB2-077_GEN
Solar/Wind Harmer
0.639
316238AB2-078_GEN
Solar/Wind Harmer
0.639
316118AC1-105 GEN
Solar/Wind Harmer
1.014
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.355
970865AG2-541 GEN
Solar/Wind Harmer
4.115
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.265
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
0.787
970163AG2-111 GEN
Solar/Wind Harmer
0.751
971967AH1-528 GEN
Solar/Wind Harmer
15.203
315607AA1-063A GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.007
970535AG2-341 GEN
50/50
2.934
3152661PLYWOOD A
50/50
0.28
970301AG2-198 GEN
Solar/Wind Harmer
21.495
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.212
963191AG1-168 GEN
Solar/Wind Harmer
3.727
971741AH1-377 GEN
Solar/Wind Harmer
43.991
316034AC1-036 C
Solar/Wind Harmer
0.584
970323AG2-213 GEN
Solar/Wind Harmer
15.706
971775AH1-396 GEN
Solar/Wind Harmer
2.237
313527AB2-043 GEN
Solar/Wind Harmer
3.538
962561AG1-105 GEN
Solar/Wind Harmer
9.795
939181AE1-148 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.552
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.81
970933AG2-581 GEN
Solar/Wind Harmer
9.592
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316222AC1-221 GEN
Solar/Wind Harmer
0.857
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.951
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.982
3145783HORNRTN
Solar/Wind Harmer
0.786
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
0.793
942751AE2-291 GEN
Solar/Wind Harmer
4.536
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.289
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.955
3147043LAWRENC
50/50
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.97
971563AH1-280 GEN
Solar/Wind Harmer
4.97
970685AG2-442 GEN
Solar/Wind Harmer
31.247
962491AG1-098 GEN
Solar/Wind Harmer
14.52
316237AB2-079_GEN
Solar/Wind Harmer
0.639
315693AD1-088 GEN
Solar/Wind Harmer
10.276
970401AG2-262 GEN
Solar/Wind Harmer
1.085
957481AF2-042 GEN
Solar/Wind Harmer
47.025
315687AD1-152 GEN
Solar/Wind Harmer
1.689
971065AG2-659 GEN
Solar/Wind Harmer
6.793
316129AC1-054 GEN
Solar/Wind Harmer
1.154
316003AC1-222 GEN
Solar/Wind Harmer
1.163
971795AH1-408 GEN
Solar/Wind Harmer
8.792
960081AF2-299 GEN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.099
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.289
970413AG2-270 GEN
50/50
12.897
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.604
970909AG2-566 GEN
Solar/Wind Harmer
4.081
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.615
963181AG1-167 GEN
Solar/Wind Harmer
3.727
959311AF2-222 GEN
Solar/Wind Harmer
34.076
970257AG2-171 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
6.734
964241AG1-285 GEN
Solar/Wind Harmer
19.68
316131AB2-060 GEN
Solar/Wind Harmer
2.422
316478AD1-087 GEN
Solar/Wind Harmer
1.342
316486AD2-202 GEN
Solar/Wind Harmer
0.393
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.458
971683AH1-343 GEN
Solar/Wind Harmer
4.759
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.706
316283AC2-100 C
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.105
316327AA2-057 GEN
Solar/Wind Harmer
0.707
970917AG2-570 GEN
Solar/Wind Harmer
17.327
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.382
316365GEN2_N
Solar/Wind Harmer
0.443
961601AG1-000A GEN
Solar/Wind Harmer
2.615
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.09
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.039
961681AG1-008 GEN
Solar/Wind Harmer
5.039
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.332
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.123
316212AC1-099_GEN
Solar/Wind Harmer
0.614
970919AG2-571 GEN
Solar/Wind Harmer
2.193
970087AG2-069 GEN
Solar/Wind Harmer
6.491
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.406
962571AG1-106 GEN
Solar/Wind Harmer
0.966
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.899
316049AB1-081 GEN
Solar/Wind Harmer
0.72
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.694
316023GEN1_S
Solar/Wind Harmer
0.443
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.346
972187AH1-678 GEN
Adder
1.773
972185AH1-677 GEN
Adder
3.35
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.126
961601AG1-000A GEN
Solar/Wind Harmer
2.583
3145893MURPHYS
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
3146776BUCKING
Solar/Wind Helper
3.457
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.963
316336AC2-165 C
Solar/Wind Helper
1.425
970085AG2-068 GEN
Solar/Wind Harmer
4.327
970581AG2-369 GEN
Solar/Wind Harmer
3.722
316319Z2-044 C
Solar/Wind Harmer
0.378
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.562
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.582
970673AG2-436 GEN
Solar/Wind Harmer
13.618
970673AG2-436 GEN
Solar/Wind Harmer
6.895
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.464
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
CPLELTFEXP_CPLE->PJM
CLTF
4.543
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.552
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.96
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.219
WECLTFEXP_WEC->PJM
CLTF
0.123
LAGNLTFEXP_LAGN->PJM
CLTF
2.505
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.252
TVALTFEXP_TVA->PJM
CLTF
1.216

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:124.48 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:851.47
MW Contribution:0.78
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.903
970285AG2-188 GEN
Solar/Wind Harmer
63.671
315657AE1-056 GEN
Solar/Wind Harmer
15.898
946301AF1-294 GEN
Solar/Wind Harmer
10.139
961791AG1-021 GEN
Solar/Wind Harmer
4.946
970683AG2-441 GEN
Solar/Wind Harmer
27.748
970681AG2-440 GEN
Solar/Wind Harmer
22.198
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.073
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.997
3144293JTRSVLE
50/50
1.19
3144293JTRSVLE
50/50
1.002
970535AG2-341 GEN
50/50
2.898
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.406
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.183
963191AG1-168 GEN
Solar/Wind Harmer
3.71
971741AH1-377 GEN
Solar/Wind Harmer
43.786
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.608
971775AH1-396 GEN
Solar/Wind Harmer
2.223
313527AB2-043 GEN
Solar/Wind Harmer
3.505
962561AG1-105 GEN
Solar/Wind Harmer
9.664
939181AE1-148 GEN
Solar/Wind Harmer
9.308
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.602
3144293JTRSVLE
50/50
1.19
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.729
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.576
970909AG2-566 GEN
Solar/Wind Harmer
4.064
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.496
963181AG1-167 GEN
Solar/Wind Harmer
3.71
959311AF2-222 GEN
Solar/Wind Harmer
33.872
970257AG2-171 GEN
Solar/Wind Harmer
11.706
315785AD2-033 C
Solar/Wind Harmer
6.689
964241AG1-285 GEN
Solar/Wind Harmer
19.525
316131AB2-060 GEN
Solar/Wind Harmer
2.4
316478AD1-087 GEN
Solar/Wind Harmer
1.324
316486AD2-202 GEN
Solar/Wind Harmer
0.388
3144293JTRSVLE
50/50
1.19
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.102
3151531CLOVER1
50/50
2.917
3147043LAWRENC
50/50
1.102
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.946
971563AH1-280 GEN
Solar/Wind Harmer
4.946
970685AG2-442 GEN
Solar/Wind Harmer
31.078
962491AG1-098 GEN
Solar/Wind Harmer
14.404
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.19
970401AG2-262 GEN
Solar/Wind Harmer
1.07
957481AF2-042 GEN
Solar/Wind Harmer
46.506
315687AD1-152 GEN
Solar/Wind Harmer
1.657
971065AG2-659 GEN
Solar/Wind Harmer
6.686
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.381
960061AF2-297 GEN
Solar/Wind Harmer
6.325
971683AH1-343 GEN
Solar/Wind Harmer
4.674
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.702
316283AC2-100 C
Solar/Wind Harmer
0.736
316210AC1-098 GEN
Solar/Wind Harmer
1.064
970917AG2-570 GEN
Solar/Wind Harmer
16.885
316365GEN2_N
Solar/Wind Harmer
0.452
316327AA2-057 GEN
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.367
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.124
316129AC1-054 GEN
Solar/Wind Harmer
1.136
971795AH1-408 GEN
Solar/Wind Harmer
8.781
316003AC1-222 GEN
Solar/Wind Harmer
1.14
960081AF2-299 GEN
Solar/Wind Harmer
1.025
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.591
970919AG2-571 GEN
Solar/Wind Harmer
2.137
970087AG2-069 GEN
Solar/Wind Harmer
6.318
316023GEN1_S
Solar/Wind Harmer
0.452
316011AB1-132 GEN
Solar/Wind Harmer
1.389
962571AG1-106 GEN
Solar/Wind Harmer
0.954
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.667
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.456
970933AG2-581 GEN
Solar/Wind Harmer
9.49
316181AB2-040 GEN
Solar/Wind Harmer
1.218
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.963
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.802
316426AA2-053 GEN
Solar/Wind Harmer
0.797
316274AC1-208 GEN
Solar/Wind Harmer
0.766
942751AE2-291 GEN
Solar/Wind Harmer
4.503
972187AH1-678 GEN
Adder
1.745
972185AH1-677 GEN
Adder
3.302
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.47
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.982
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.254
970865AG2-541 GEN
Solar/Wind Harmer
4.048
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
0.778
970163AG2-111 GEN
Solar/Wind Harmer
0.742
971967AH1-528 GEN
Solar/Wind Harmer
15.039
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.212
970581AG2-369 GEN
Solar/Wind Harmer
3.623
315652AC1-086 GEN
Solar/Wind Harmer
7.469
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.36
970673AG2-436 GEN
Solar/Wind Harmer
13.449
970673AG2-436 GEN
Solar/Wind Harmer
6.81
965291AG1-394 GEN
Solar/Wind Harmer
0.565
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
CPLELTFEXP_CPLE->PJM
CLTF
3.951
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.023
NYPJM->LTFIMP_NY
CLTF
0.315
LGEELTFEXP_LGEE->PJM
CLTF
0.251
WECLTFEXP_WEC->PJM
CLTF
0.133
LAGNLTFEXP_LAGN->PJM
CLTF
2.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.001
TVALTFEXP_TVA->PJM
CLTF
1.025

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.8 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:792.06
MW Contribution:0.85
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.579
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.561
970909AG2-566 GEN
Solar/Wind Harmer
4.052
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.429
963181AG1-167 GEN
Solar/Wind Harmer
3.699
959311AF2-222 GEN
Solar/Wind Harmer
33.746
970257AG2-171 GEN
Solar/Wind Harmer
11.66
315785AD2-033 C
Solar/Wind Harmer
6.661
964241AG1-285 GEN
Solar/Wind Harmer
19.423
316131AB2-060 GEN
Solar/Wind Harmer
2.386
316478AD1-087 GEN
Solar/Wind Harmer
1.308
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.384
960061AF2-297 GEN
Solar/Wind Harmer
6.368
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.838
966621AG1-532 GEN
Solar/Wind Harmer
0.176
313506AB2-031 GEN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Harmer
0.725
316210AC1-098 GEN
Solar/Wind Harmer
1.021
970917AG2-570 GEN
Solar/Wind Harmer
16.174
316327AA2-057 GEN
Solar/Wind Harmer
0.648
3146263WOODLND
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.882
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.932
971563AH1-280 GEN
Solar/Wind Harmer
4.932
970685AG2-442 GEN
Solar/Wind Harmer
30.976
962491AG1-098 GEN
Solar/Wind Harmer
14.277
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.093
970401AG2-262 GEN
Solar/Wind Harmer
1.069
957481AF2-042 GEN
Solar/Wind Harmer
45.841
315687AD1-152 GEN
Solar/Wind Harmer
1.641
971065AG2-659 GEN
Solar/Wind Harmer
6.575
316129AC1-054 GEN
Solar/Wind Harmer
1.116
3147043LAWRENC
Adder
1.01
316003AC1-222 GEN
Solar/Wind Harmer
1.164
971795AH1-408 GEN
Solar/Wind Harmer
8.484
960081AF2-299 GEN
Solar/Wind Harmer
0.973
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.567
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
6.053
3146263WOODLND
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.999
970535AG2-341 GEN
50/50
2.873
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.341
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.165
963191AG1-168 GEN
Solar/Wind Harmer
3.699
971741AH1-377 GEN
Solar/Wind Harmer
43.617
316034AC1-036 C
Solar/Wind Harmer
0.578
970323AG2-213 GEN
Solar/Wind Harmer
15.547
971775AH1-396 GEN
Solar/Wind Harmer
2.214
313527AB2-043 GEN
Solar/Wind Harmer
3.483
962561AG1-105 GEN
Solar/Wind Harmer
9.649
964791AG1-342 GEN
Solar/Wind Harmer
3.499
939181AE1-148 GEN
Solar/Wind Harmer
9.211
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.337
970933AG2-581 GEN
Solar/Wind Harmer
9.235
316181AB2-040 GEN
Solar/Wind Harmer
1.163
942751AE2-291 GEN
Solar/Wind Harmer
5.136
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.898
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.791
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.765
316274AC1-208 GEN
Solar/Wind Harmer
0.735
972187AH1-678 GEN
Adder
1.669
3146776BUCKING
Solar/Wind Helper
3.473
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.981
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.869
970285AG2-188 GEN
Solar/Wind Harmer
63.627
315657AE1-056 GEN
Solar/Wind Harmer
15.857
946301AF1-294 GEN
Solar/Wind Harmer
10.111
961791AG1-021 GEN
Solar/Wind Harmer
4.932
970683AG2-441 GEN
Solar/Wind Harmer
27.657
970681AG2-440 GEN
Solar/Wind Harmer
22.126
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.048
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.134
970865AG2-541 GEN
Solar/Wind Harmer
4.26
316123AC1-075 GEN
Solar/Wind Harmer
0.971
970165AG2-112 GEN
Solar/Wind Harmer
0.855
970163AG2-111 GEN
Solar/Wind Harmer
0.816
946281AF1-292 GEN
Solar/Wind Harmer
0.194
316087AB2-174 GEN
Solar/Wind Harmer
1.202
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.485
315607AA1-063A GEN
Solar/Wind Harmer
0.732
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.036
970581AG2-369 GEN
Solar/Wind Harmer
3.471
270494AE1-108_GEN
Solar/Wind Helper
4.511
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
316336AC2-165 C
Solar/Wind Helper
1.444
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
3.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.48
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.023
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.205
MECLTFEXP_MEC->PJM
CLTF
0.743
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.299
LGEELTFEXP_LGEE->PJM
CLTF
0.225
WECLTFEXP_WEC->PJM
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
1.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.732
TVALTFEXP_TVA->PJM
CLTF
0.969

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.37 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:617.32
MW Contribution:0.58
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
970285AG2-188 GEN
Solar/Wind Harmer
51.175
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.79 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:758.93
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.22 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:744.24
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.97 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:908.5
MW Contribution:1.2
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
970909AG2-566 GEN
Solar/Wind Harmer
6.35
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.445
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.93 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:908.21
MW Contribution:1.2
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.445
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
970909AG2-566 GEN
Solar/Wind Harmer
6.35
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.73 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:885.86
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
73.556
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3152661PLYWOOD A
50/50
0.346
970301AG2-198 GEN
Solar/Wind Harmer
33.428
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970933AG2-581 GEN
Solar/Wind Harmer
36.681
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.78 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:844.27
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.346
970301AG2-198 GEN
Solar/Wind Harmer
33.428
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.78 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:844.27
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.346
970301AG2-198 GEN
Solar/Wind Harmer
33.428
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.2 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5258.72
MW Contribution:1.87
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
970673AG2-436 GEN
Solar/Wind Harmer
149.315
970673AG2-436 GEN
Solar/Wind Harmer
99.544
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.25 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5708.12
MW Contribution:2.46
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
970673AG2-436 GEN
Solar/Wind Harmer
165.209
970673AG2-436 GEN
Solar/Wind Harmer
83.65
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.76 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5683.44
MW Contribution:2.46
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
970673AG2-436 GEN
Solar/Wind Harmer
164.043
970673AG2-436 GEN
Solar/Wind Harmer
83.06
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.13 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5601.8
MW Contribution:2.43
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
970673AG2-436 GEN
Solar/Wind Harmer
162.646
970673AG2-436 GEN
Solar/Wind Harmer
82.352
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.99 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:969.01
MW Contribution:0.46
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
970937AG2-583 GEN
Solar/Wind Harmer
28.699
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.59 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:965.75
MW Contribution:0.46
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
970937AG2-583 GEN
Solar/Wind Harmer
28.699
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970933AG2-581 GEN
Solar/Wind Harmer
8.922
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
971443AH1-215 GEN
Solar/Wind Harmer
2.005
971967AH1-528 GEN
Solar/Wind Harmer
17.843
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.29 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:312.32
MW Contribution:5.28
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
24684705SMG5
50/50
0.344
970481AG2-311 GEN
50/50
4.8
3147123OTTER R
Solar/Wind Harmer
0.184
3147312GRETNA
Solar/Wind Harmer
0.194
3146802CHATHAM
Solar/Wind Harmer
0.182
941801AE2-185 GEN
Solar/Wind Harmer
7.752
270173AC1-122 GEN
Solar/Wind Harmer
0.243
962751AG1-124 GEN
Solar/Wind Harmer
3.521
24728405LEESVG
50/50
0.206
24684605SMG4
50/50
0.9
24288905REUSENS
50/50
0.018
966251AG1-494 GEN
50/50
1.299
971683AH1-343 GEN
Solar/Wind Harmer
31.005
3147312GRETNA
Solar/Wind Harmer
0.048
941821AE2-187 GEN
Solar/Wind Harmer
7.752
270197AD1-017 GEN1
Solar/Wind Harmer
0.469
958131AF2-107 GEN
Solar/Wind Harmer
1.71
316248AF1-058 C
Solar/Wind Helper
0.404
316131AB2-060 GEN
Solar/Wind Helper
0.823
315785AD2-033 C
Solar/Wind Helper
1.409
270574AD1-017 GEN2
Solar/Wind Harmer
0
316003AC1-222 GEN
Solar/Wind Helper
1.905
316237AB2-079_GEN
Solar/Wind Helper
0.188
315687AD1-152 GEN
Solar/Wind Helper
0.645
970865AG2-541 GEN
Solar/Wind Harmer
27.028
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
5.283
970163AG2-111 GEN
Solar/Wind Harmer
5.039
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.036
316239AB2-077_GEN
Solar/Wind Helper
0.188
316238AB2-078_GEN
Solar/Wind Helper
0.188
3144303KENBRDG
Solar/Wind Helper
0.094
24684405SMG2
50/50
0.894
24684505SMG3
50/50
0.553
24684305SMG1
50/50
0.324
942751AE2-291 GEN
Solar/Wind Harmer
31.036
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.003
942671AE2-283 GEN
Solar/Wind Harmer
6.03
3146843MT LREL
Solar/Wind Helper
0.232
3146843MT LREL
Solar/Wind Helper
0.232
316034AC1-036 C
Solar/Wind Helper
0.123
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.077
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.522
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.969
MECLTFEXP_MEC->PJM
CLTF
0.978
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.468
WECLTFEXP_WEC->PJM
CLTF
0.232
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.458
LAGNLTFEXP_LAGN->PJM
CLTF
0.878
TVALTFEXP_TVA->PJM
CLTF
0.49

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.12 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:364.42
MW Contribution:6.96
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.206
971683AH1-343 GEN
Solar/Wind Harmer
40.822
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.207
270197AD1-017 GEN1
Solar/Wind Harmer
0.836
958131AF2-107 GEN
Solar/Wind Harmer
2.275
316248AF1-058 C
Solar/Wind Helper
0.404
316131AB2-060 GEN
Solar/Wind Helper
0.823
315785AD2-033 C
Solar/Wind Helper
1.41
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.207
270173AC1-122 GEN
Solar/Wind Harmer
1.179
962751AG1-124 GEN
Solar/Wind Harmer
5.14
270574AD1-017 GEN2
Solar/Wind Harmer
2.781
316003AC1-222 GEN
Solar/Wind Helper
1.905
316237AB2-079_GEN
Solar/Wind Helper
0.188
315687AD1-152 GEN
Solar/Wind Helper
0.645
942751AE2-291 GEN
Solar/Wind Harmer
40.863
316217AC1-145 GEN
Solar/Wind Harmer
4.418
316197AC1-042 GEN
Solar/Wind Harmer
3.349
942671AE2-283 GEN
Solar/Wind Harmer
9.016
3146843MT LREL
Solar/Wind Helper
0.233
3146843MT LREL
Solar/Wind Helper
0.233
316034AC1-036 C
Solar/Wind Helper
0.123
970865AG2-541 GEN
Solar/Wind Harmer
35.586
316123AC1-075 GEN
Solar/Wind Harmer
7.9
970165AG2-112 GEN
Solar/Wind Harmer
6.955
970163AG2-111 GEN
Solar/Wind Harmer
6.635
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.036
316239AB2-077_GEN
Solar/Wind Helper
0.188
316238AB2-078_GEN
Solar/Wind Helper
0.188
3144303KENBRDG
Solar/Wind Helper
0.094
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.077
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.517
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.967
MECLTFEXP_MEC->PJM
CLTF
0.977
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.468
WECLTFEXP_WEC->PJM
CLTF
0.231
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.459
LAGNLTFEXP_LAGN->PJM
CLTF
0.877
TVALTFEXP_TVA->PJM
CLTF
0.489

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.76 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:363.16
MW Contribution:6.96
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.206
971683AH1-343 GEN
Solar/Wind Harmer
40.823
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.207
270197AD1-017 GEN1
Solar/Wind Harmer
0.836
958131AF2-107 GEN
Solar/Wind Harmer
2.276
316248AF1-058 C
Solar/Wind Helper
0.404
316131AB2-060 GEN
Solar/Wind Helper
0.823
315785AD2-033 C
Solar/Wind Helper
1.409
970865AG2-541 GEN
Solar/Wind Harmer
35.587
316123AC1-075 GEN
Solar/Wind Harmer
7.9
970165AG2-112 GEN
Solar/Wind Harmer
6.956
970163AG2-111 GEN
Solar/Wind Harmer
6.635
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.036
316239AB2-077_GEN
Solar/Wind Helper
0.188
316238AB2-078_GEN
Solar/Wind Helper
0.188
3144303KENBRDG
Solar/Wind Helper
0.094
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.207
270173AC1-122 GEN
Solar/Wind Harmer
1.179
962751AG1-124 GEN
Solar/Wind Harmer
5.141
270574AD1-017 GEN2
Solar/Wind Harmer
2.781
316003AC1-222 GEN
Solar/Wind Helper
1.905
316237AB2-079_GEN
Solar/Wind Helper
0.188
315687AD1-152 GEN
Solar/Wind Helper
0.645
942751AE2-291 GEN
Solar/Wind Harmer
40.865
316217AC1-145 GEN
Solar/Wind Harmer
4.418
316197AC1-042 GEN
Solar/Wind Harmer
3.349
942671AE2-283 GEN
Solar/Wind Harmer
9.017
3146843MT LREL
Solar/Wind Helper
0.232
3146843MT LREL
Solar/Wind Helper
0.232
316034AC1-036 C
Solar/Wind Helper
0.123
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.077
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.521
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.969
MECLTFEXP_MEC->PJM
CLTF
0.978
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.468
WECLTFEXP_WEC->PJM
CLTF
0.232
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.458
LAGNLTFEXP_LAGN->PJM
CLTF
0.878
TVALTFEXP_TVA->PJM
CLTF
0.49

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.75 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:363.12
MW Contribution:6.96
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.587
316123AC1-075 GEN
Solar/Wind Harmer
7.9
970165AG2-112 GEN
Solar/Wind Harmer
6.956
970163AG2-111 GEN
Solar/Wind Harmer
6.635
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.036
316239AB2-077_GEN
Solar/Wind Helper
0.188
316238AB2-078_GEN
Solar/Wind Helper
0.188
3144303KENBRDG
Solar/Wind Helper
0.094
942751AE2-291 GEN
Solar/Wind Harmer
40.865
316217AC1-145 GEN
Solar/Wind Harmer
4.418
316197AC1-042 GEN
Solar/Wind Harmer
3.349
942671AE2-283 GEN
Solar/Wind Harmer
9.017
3146843MT LREL
Solar/Wind Helper
0.232
3146843MT LREL
Solar/Wind Helper
0.232
316034AC1-036 C
Solar/Wind Helper
0.123
24728405LEESVG
50/50
0.206
971683AH1-343 GEN
Solar/Wind Harmer
40.823
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.207
270197AD1-017 GEN1
Solar/Wind Harmer
0.836
958131AF2-107 GEN
Solar/Wind Harmer
2.276
316248AF1-058 C
Solar/Wind Helper
0.404
316131AB2-060 GEN
Solar/Wind Helper
0.823
315785AD2-033 C
Solar/Wind Helper
1.409
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.207
270173AC1-122 GEN
Solar/Wind Harmer
1.179
962751AG1-124 GEN
Solar/Wind Harmer
5.141
270574AD1-017 GEN2
Solar/Wind Harmer
2.781
316003AC1-222 GEN
Solar/Wind Helper
1.905
316237AB2-079_GEN
Solar/Wind Helper
0.188
315687AD1-152 GEN
Solar/Wind Helper
0.645
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.077
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.522
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.969
MECLTFEXP_MEC->PJM
CLTF
0.978
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.468
WECLTFEXP_WEC->PJM
CLTF
0.232
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.458
LAGNLTFEXP_LAGN->PJM
CLTF
0.878
TVALTFEXP_TVA->PJM
CLTF
0.49

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.04 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:360.64
MW Contribution:6.96
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.769
24728405LEESVG
50/50
0.229
24684705SMG5
50/50
0.437
970481AG2-311 GEN
50/50
6.086
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.665
270574AD1-017 GEN2
Solar/Wind Harmer
5.101
270016AE1-250 BESS
Solar/Wind Harmer
2.264
970223AG2-152 GEN
Solar/Wind Harmer
13.058
270173AC1-122 GEN
Solar/Wind Harmer
1.401
962751AG1-124 GEN
Solar/Wind Harmer
5.108
316003AC1-222 GEN
Solar/Wind Helper
1.949
316237AB2-079_GEN
Solar/Wind Helper
0.202
315687AD1-152 GEN
Solar/Wind Helper
0.724
970865AG2-541 GEN
Solar/Wind Harmer
35.485
316123AC1-075 GEN
Solar/Wind Harmer
7.909
970165AG2-112 GEN
Solar/Wind Harmer
6.964
970163AG2-111 GEN
Solar/Wind Harmer
6.643
3147173SINAI
Solar/Wind Helper
0.314
3147243WELCO
Solar/Wind Helper
0.196
316118AC1-105 GEN
Solar/Wind Helper
1.086
316239AB2-077_GEN
Solar/Wind Helper
0.202
316238AB2-078_GEN
Solar/Wind Helper
0.202
3144303KENBRDG
Solar/Wind Helper
0.1
24684405SMG2
50/50
1.134
24684505SMG3
50/50
0.701
24684305SMG1
50/50
0.411
942751AE2-291 GEN
Solar/Wind Harmer
41.056
316217AC1-145 GEN
Solar/Wind Harmer
4.616
316197AC1-042 GEN
Solar/Wind Harmer
3.499
942671AE2-283 GEN
Solar/Wind Harmer
9.42
270013AE1-250 PV
Solar/Wind Harmer
2.264
3146843MT LREL
Solar/Wind Helper
0.245
3146843MT LREL
Solar/Wind Helper
0.245
316034AC1-036 C
Solar/Wind Helper
0.131
24728405LEESVG
50/50
0.23
24684605SMG4
50/50
1.141
971683AH1-343 GEN
Solar/Wind Harmer
40.643
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.665
270197AD1-017 GEN1
Solar/Wind Harmer
1.533
958131AF2-107 GEN
Solar/Wind Harmer
2.307
316248AF1-058 C
Solar/Wind Helper
0.422
316131AB2-060 GEN
Solar/Wind Helper
0.886
315785AD2-033 C
Solar/Wind Helper
1.508
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.376
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.996
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.824
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.391
MECLTFEXP_MEC->PJM
CLTF
0.467
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.1
LGEELTFEXP_LGEE->PJM
CLTF
0.269
WECLTFEXP_WEC->PJM
CLTF
0.129
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.998
TVALTFEXP_TVA->PJM
CLTF
0.041
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.53 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:355.37
MW Contribution:6.98
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.125
971683AH1-343 GEN
Solar/Wind Harmer
40.784
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.632
270197AD1-017 GEN1
Solar/Wind Harmer
1.511
958131AF2-107 GEN
Solar/Wind Harmer
2.276
316248AF1-058 C
Solar/Wind Helper
0.412
316131AB2-060 GEN
Solar/Wind Helper
0.847
315785AD2-033 C
Solar/Wind Helper
1.439
3151561HALLBR1
50/50
0.768
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.999
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.632
270574AD1-017 GEN2
Solar/Wind Harmer
5.028
270016AE1-250 BESS
Solar/Wind Harmer
2.232
970223AG2-152 GEN
Solar/Wind Harmer
12.873
270173AC1-122 GEN
Solar/Wind Harmer
1.38
962751AG1-124 GEN
Solar/Wind Harmer
5.018
316003AC1-222 GEN
Solar/Wind Helper
1.921
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.683
24684405SMG2
50/50
1.118
24684505SMG3
50/50
0.691
24684305SMG1
50/50
0.405
942751AE2-291 GEN
Solar/Wind Harmer
41.146
316217AC1-145 GEN
Solar/Wind Harmer
4.602
316197AC1-042 GEN
Solar/Wind Harmer
3.489
942671AE2-283 GEN
Solar/Wind Harmer
9.392
270013AE1-250 PV
Solar/Wind Harmer
2.232
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.125
970865AG2-541 GEN
Solar/Wind Harmer
35.6
316123AC1-075 GEN
Solar/Wind Harmer
7.93
970165AG2-112 GEN
Solar/Wind Harmer
6.982
970163AG2-111 GEN
Solar/Wind Harmer
6.661
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.058
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.313
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.902
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.307
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.392
MECLTFEXP_MEC->PJM
CLTF
0.422
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.092
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.841
LAGNLTFEXP_LAGN->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.051
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.27 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:354.46
MW Contribution:6.98
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.118
24684505SMG3
50/50
0.691
24684305SMG1
50/50
0.405
942751AE2-291 GEN
Solar/Wind Harmer
41.146
316217AC1-145 GEN
Solar/Wind Harmer
4.602
316197AC1-042 GEN
Solar/Wind Harmer
3.489
942671AE2-283 GEN
Solar/Wind Harmer
9.392
270013AE1-250 PV
Solar/Wind Harmer
2.232
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
3151561HALLBR1
50/50
0.768
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.999
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.632
970865AG2-541 GEN
Solar/Wind Harmer
35.6
316123AC1-075 GEN
Solar/Wind Harmer
7.93
970165AG2-112 GEN
Solar/Wind Harmer
6.982
970163AG2-111 GEN
Solar/Wind Harmer
6.661
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.058
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
270574AD1-017 GEN2
Solar/Wind Harmer
5.028
270016AE1-250 BESS
Solar/Wind Harmer
2.232
970223AG2-152 GEN
Solar/Wind Harmer
12.873
270173AC1-122 GEN
Solar/Wind Harmer
1.38
962751AG1-124 GEN
Solar/Wind Harmer
5.018
316003AC1-222 GEN
Solar/Wind Helper
1.921
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.683
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.125
971683AH1-343 GEN
Solar/Wind Harmer
40.784
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.632
270197AD1-017 GEN1
Solar/Wind Harmer
1.511
958131AF2-107 GEN
Solar/Wind Harmer
2.276
316248AF1-058 C
Solar/Wind Helper
0.412
316131AB2-060 GEN
Solar/Wind Helper
0.847
315785AD2-033 C
Solar/Wind Helper
1.439
316034AC1-036 C
Solar/Wind Helper
0.125
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.313
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.902
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.307
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.392
MECLTFEXP_MEC->PJM
CLTF
0.422
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.092
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.841
LAGNLTFEXP_LAGN->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.051
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.27 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:354.44
MW Contribution:6.98
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.6
316123AC1-075 GEN
Solar/Wind Harmer
7.93
970165AG2-112 GEN
Solar/Wind Harmer
6.982
970163AG2-111 GEN
Solar/Wind Harmer
6.661
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.058
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24684405SMG2
50/50
1.118
24684505SMG3
50/50
0.691
24684305SMG1
50/50
0.405
942751AE2-291 GEN
Solar/Wind Harmer
41.146
316217AC1-145 GEN
Solar/Wind Harmer
4.602
316197AC1-042 GEN
Solar/Wind Harmer
3.489
942671AE2-283 GEN
Solar/Wind Harmer
9.392
270013AE1-250 PV
Solar/Wind Harmer
2.232
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.125
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.125
971683AH1-343 GEN
Solar/Wind Harmer
40.784
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.633
270197AD1-017 GEN1
Solar/Wind Harmer
1.511
958131AF2-107 GEN
Solar/Wind Harmer
2.276
316248AF1-058 C
Solar/Wind Helper
0.412
316131AB2-060 GEN
Solar/Wind Helper
0.847
315785AD2-033 C
Solar/Wind Helper
1.439
3151561HALLBR1
50/50
0.768
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.999
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.633
270574AD1-017 GEN2
Solar/Wind Harmer
5.028
270016AE1-250 BESS
Solar/Wind Harmer
2.232
970223AG2-152 GEN
Solar/Wind Harmer
12.873
270173AC1-122 GEN
Solar/Wind Harmer
1.38
962751AG1-124 GEN
Solar/Wind Harmer
5.018
316003AC1-222 GEN
Solar/Wind Helper
1.921
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.683
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.313
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.902
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.307
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.392
MECLTFEXP_MEC->PJM
CLTF
0.422
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.092
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.842
LAGNLTFEXP_LAGN->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.051
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.5 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:287.19
MW Contribution:5.25
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.726
24728405LEESVG
50/50
0.195
970865AG2-541 GEN
Solar/Wind Harmer
26.903
316123AC1-075 GEN
Solar/Wind Harmer
0.885
970165AG2-112 GEN
Solar/Wind Harmer
5.245
970163AG2-111 GEN
Solar/Wind Harmer
5.003
3147173SINAI
Solar/Wind Helper
0.305
3147243WELCO
Solar/Wind Helper
0.19
316118AC1-105 GEN
Solar/Wind Helper
1.049
316239AB2-077_GEN
Solar/Wind Helper
0.189
316238AB2-078_GEN
Solar/Wind Helper
0.189
3144303KENBRDG
Solar/Wind Helper
0.093
24684405SMG2
50/50
0.818
24684505SMG3
50/50
0.506
24684305SMG1
50/50
0.297
942751AE2-291 GEN
Solar/Wind Harmer
30.747
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.831
3146843MT LREL
Solar/Wind Helper
0.235
3146843MT LREL
Solar/Wind Helper
0.235
316034AC1-036 C
Solar/Wind Helper
0.122
24684705SMG5
50/50
0.315
970481AG2-311 GEN
50/50
4.393
3147123OTTER R
Solar/Wind Harmer
0.179
3147312GRETNA
Solar/Wind Harmer
0.187
3146802CHATHAM
Solar/Wind Harmer
0.176
941801AE2-185 GEN
Solar/Wind Harmer
7.497
270173AC1-122 GEN
Solar/Wind Harmer
0.22
962751AG1-124 GEN
Solar/Wind Harmer
3.094
270574AD1-017 GEN2
Solar/Wind Harmer
0
316003AC1-222 GEN
Solar/Wind Helper
1.927
316237AB2-079_GEN
Solar/Wind Helper
0.189
315687AD1-152 GEN
Solar/Wind Helper
0.655
24728405LEESVG
50/50
0.196
24684605SMG4
50/50
0.824
24288905REUSENS
50/50
0.016
966251AG1-494 GEN
50/50
1.156
971683AH1-343 GEN
Solar/Wind Harmer
30.891
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.497
270197AD1-017 GEN1
Solar/Wind Harmer
0.42
316248AF1-058 C
Solar/Wind Helper
0.409
316131AB2-060 GEN
Solar/Wind Helper
0.826
315785AD2-033 C
Solar/Wind Helper
1.4
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.975
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.92
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.739
MECLTFEXP_MEC->PJM
CLTF
0.515
SIGELTFEXP_SIGE->PJM
CLTF
0.019
NYPJM->LTFIMP_NY
CLTF
0.101
LGEELTFEXP_LGEE->PJM
CLTF
0.269
WECLTFEXP_WEC->PJM
CLTF
0.132
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.641
LAGNLTFEXP_LAGN->PJM
CLTF
0.236
TVALTFEXP_TVA->PJM
CLTF
0.154

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.24 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:727.2
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.67 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:712.52
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.28 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:868.71
MW Contribution:1.2
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.24 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:868.41
MW Contribution:1.2
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.04 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:846.09
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
3.05
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
73.556
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
3152661PLYWOOD A
50/50
0.346
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970933AG2-581 GEN
Solar/Wind Harmer
36.681
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
316336AC2-165 C
Solar/Wind Helper
0.999
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.09 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:804.51
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
315821AE2-092 GEN
Solar/Wind Helper
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.09 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:804.51
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
3.05
3152661PLYWOOD A
50/50
0.346
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:218.2 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1492.5
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.839
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:218.14 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1492.11
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.839
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:214.52 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1467.34
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.838
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
971967AH1-528 GEN
Solar/Wind Harmer
73.183
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970933AG2-581 GEN
Solar/Wind Harmer
36.495
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:212.24 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1187.04
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
971845AH1-439 GEN
Solar/Wind Harmer
34.055
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
971967AH1-528 GEN
Solar/Wind Harmer
55.434
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970933AG2-581 GEN
Solar/Wind Harmer
27.718
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:209.65 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1172.59
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
971845AH1-439 GEN
Solar/Wind Harmer
34.055
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:208.48 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1426.03
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.838
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:208.48 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1426.03
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.838
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:134.05 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:916.91
MW Contribution:0.75
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3151541CLOVER2
50/50
2.829
971845AH1-439 GEN
Solar/Wind Harmer
40.087
970285AG2-188 GEN
Solar/Wind Harmer
63.51
315657AE1-056 GEN
Solar/Wind Harmer
15.784
946301AF1-294 GEN
Solar/Wind Harmer
10.059
961791AG1-021 GEN
Solar/Wind Harmer
4.907
970683AG2-441 GEN
Solar/Wind Harmer
27.489
970681AG2-440 GEN
Solar/Wind Harmer
21.992
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.004
316239AB2-077_GEN
Solar/Wind Harmer
0.621
316238AB2-078_GEN
Solar/Wind Harmer
0.621
316118AC1-105 GEN
Solar/Wind Harmer
0.972
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.033
970865AG2-541 GEN
Solar/Wind Harmer
3.923
946281AF1-292 GEN
Solar/Wind Harmer
0.19
316087AB2-174 GEN
Solar/Wind Harmer
1.178
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.853
970165AG2-112 GEN
Solar/Wind Harmer
0.751
970163AG2-111 GEN
Solar/Wind Harmer
0.717
971967AH1-528 GEN
Solar/Wind Harmer
14.188
315607AA1-063A GEN
Solar/Wind Harmer
0.715
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.499
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.18
3144293JTRSVLE
50/50
0.994
970535AG2-341 GEN
50/50
2.836
3152661PLYWOOD A
50/50
0.267
970301AG2-198 GEN
Solar/Wind Harmer
21.257
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.133
963191AG1-168 GEN
Solar/Wind Harmer
3.68
971741AH1-377 GEN
Solar/Wind Harmer
43.417
316034AC1-036 C
Solar/Wind Harmer
0.574
970323AG2-213 GEN
Solar/Wind Harmer
15.434
971775AH1-396 GEN
Solar/Wind Harmer
2.198
313527AB2-043 GEN
Solar/Wind Harmer
3.442
962561AG1-105 GEN
Solar/Wind Harmer
9.457
939181AE1-148 GEN
Solar/Wind Harmer
9.083
964791AG1-342 GEN
Solar/Wind Harmer
3.423
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.098
970933AG2-581 GEN
Solar/Wind Harmer
9.079
316181AB2-040 GEN
Solar/Wind Harmer
1.138
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.878
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.905
3145783HORNRTN
Solar/Wind Harmer
0.724
3145783HORNRTN
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.769
316426AA2-053 GEN
Solar/Wind Harmer
0.748
942751AE2-291 GEN
Solar/Wind Harmer
4.333
316274AC1-208 GEN
Solar/Wind Harmer
0.717
972187AH1-678 GEN
Adder
1.63
3146776BUCKING
Solar/Wind Helper
3.482
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.994
3144293JTRSVLE
50/50
1.18
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.405
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.535
970909AG2-566 GEN
Solar/Wind Harmer
4.036
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.307
963181AG1-167 GEN
Solar/Wind Harmer
3.68
959311AF2-222 GEN
Solar/Wind Harmer
33.514
970257AG2-171 GEN
Solar/Wind Harmer
11.575
315785AD2-033 C
Solar/Wind Harmer
6.609
964241AG1-285 GEN
Solar/Wind Harmer
19.233
316131AB2-060 GEN
Solar/Wind Harmer
2.359
316478AD1-087 GEN
Solar/Wind Harmer
1.29
316486AD2-202 GEN
Solar/Wind Harmer
0.378
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.371
960061AF2-297 GEN
Solar/Wind Harmer
6.151
971683AH1-343 GEN
Solar/Wind Harmer
4.535
966621AG1-532 GEN
Solar/Wind Harmer
0.172
313506AB2-031 GEN
Solar/Wind Harmer
0.656
316283AC2-100 C
Solar/Wind Harmer
0.705
316210AC1-098 GEN
Solar/Wind Harmer
0.995
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.306
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.125
3144293JTRSVLE
50/50
1.18
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.843
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.907
971563AH1-280 GEN
Solar/Wind Harmer
4.907
970685AG2-442 GEN
Solar/Wind Harmer
30.788
962491AG1-098 GEN
Solar/Wind Harmer
14.151
316237AB2-079_GEN
Solar/Wind Harmer
0.621
315693AD1-088 GEN
Solar/Wind Harmer
9.998
970401AG2-262 GEN
Solar/Wind Harmer
1.046
957481AF2-042 GEN
Solar/Wind Harmer
45.244
315687AD1-152 GEN
Solar/Wind Harmer
1.611
971065AG2-659 GEN
Solar/Wind Harmer
6.471
316129AC1-054 GEN
Solar/Wind Harmer
1.098
3147043LAWRENC
Adder
0.994
316003AC1-222 GEN
Solar/Wind Harmer
1.108
971795AH1-408 GEN
Solar/Wind Harmer
8.341
960081AF2-299 GEN
Solar/Wind Harmer
0.953
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316212AC1-099_GEN
Solar/Wind Harmer
0.553
316322AB2-045
Solar/Wind Helper
0.97
3146776BUCKING
Solar/Wind Helper
0.348
316336AC2-165 C
Solar/Wind Helper
1.454
CPLELTFEXP_CPLE->PJM
CLTF
3.717
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.651
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.966
MECLTFEXP_MEC->PJM
CLTF
0.645
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.186
WECLTFEXP_WEC->PJM
CLTF
0.097
LAGNLTFEXP_LAGN->PJM
CLTF
1.842
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.457
TVALTFEXP_TVA->PJM
CLTF
0.904

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.94 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:916.12
MW Contribution:0.79
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.289
3151621KERR 5
50/50
0.289
3151631KERR 6
50/50
0.289
3151641KERR 7
50/50
0.289
3151541CLOVER2
50/50
2.941
971845AH1-439 GEN
Solar/Wind Harmer
40.276
970285AG2-188 GEN
Solar/Wind Harmer
63.831
315657AE1-056 GEN
Solar/Wind Harmer
15.969
946301AF1-294 GEN
Solar/Wind Harmer
10.188
961791AG1-021 GEN
Solar/Wind Harmer
4.97
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.289
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.955
3147043LAWRENC
50/50
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.97
971563AH1-280 GEN
Solar/Wind Harmer
4.97
970685AG2-442 GEN
Solar/Wind Harmer
31.247
970683AG2-441 GEN
Solar/Wind Harmer
27.899
970681AG2-440 GEN
Solar/Wind Harmer
22.32
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.111
316239AB2-077_GEN
Solar/Wind Harmer
0.639
316238AB2-078_GEN
Solar/Wind Harmer
0.639
316118AC1-105 GEN
Solar/Wind Harmer
1.014
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.355
970865AG2-541 GEN
Solar/Wind Harmer
4.115
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.265
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
0.787
970163AG2-111 GEN
Solar/Wind Harmer
0.751
971967AH1-528 GEN
Solar/Wind Harmer
15.203
315607AA1-063A GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.327
970581AG2-369 GEN
Solar/Wind Harmer
3.722
316319Z2-044 C
Solar/Wind Harmer
0.378
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.562
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.582
970673AG2-436 GEN
Solar/Wind Harmer
13.618
970673AG2-436 GEN
Solar/Wind Harmer
6.895
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.464
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.007
970535AG2-341 GEN
50/50
2.934
3152661PLYWOOD A
50/50
0.28
970301AG2-198 GEN
Solar/Wind Harmer
21.495
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.212
963191AG1-168 GEN
Solar/Wind Harmer
3.727
971741AH1-377 GEN
Solar/Wind Harmer
43.991
316034AC1-036 C
Solar/Wind Harmer
0.584
970323AG2-213 GEN
Solar/Wind Harmer
15.706
971775AH1-396 GEN
Solar/Wind Harmer
2.237
313527AB2-043 GEN
Solar/Wind Harmer
3.538
962561AG1-105 GEN
Solar/Wind Harmer
9.795
939181AE1-148 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.552
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.81
970933AG2-581 GEN
Solar/Wind Harmer
9.592
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316222AC1-221 GEN
Solar/Wind Harmer
0.857
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.951
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.982
3145783HORNRTN
Solar/Wind Harmer
0.786
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
0.793
942751AE2-291 GEN
Solar/Wind Harmer
4.536
972187AH1-678 GEN
Adder
1.773
972185AH1-677 GEN
Adder
3.35
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.126
961601AG1-000A GEN
Solar/Wind Harmer
2.583
3145893MURPHYS
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
3146776BUCKING
Solar/Wind Helper
3.457
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.963
962491AG1-098 GEN
Solar/Wind Harmer
14.52
316237AB2-079_GEN
Solar/Wind Harmer
0.639
315693AD1-088 GEN
Solar/Wind Harmer
10.276
970401AG2-262 GEN
Solar/Wind Harmer
1.085
957481AF2-042 GEN
Solar/Wind Harmer
47.025
315687AD1-152 GEN
Solar/Wind Harmer
1.689
971065AG2-659 GEN
Solar/Wind Harmer
6.793
316129AC1-054 GEN
Solar/Wind Harmer
1.154
316003AC1-222 GEN
Solar/Wind Harmer
1.163
971795AH1-408 GEN
Solar/Wind Harmer
8.792
960081AF2-299 GEN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.099
316212AC1-099_GEN
Solar/Wind Harmer
0.614
970919AG2-571 GEN
Solar/Wind Harmer
2.193
970087AG2-069 GEN
Solar/Wind Harmer
6.491
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.406
962571AG1-106 GEN
Solar/Wind Harmer
0.966
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.899
316049AB1-081 GEN
Solar/Wind Harmer
0.72
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.694
316023GEN1_S
Solar/Wind Harmer
0.443
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.346
316336AC2-165 C
Solar/Wind Helper
1.425
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.289
970413AG2-270 GEN
50/50
12.897
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.604
970909AG2-566 GEN
Solar/Wind Harmer
4.081
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.615
963181AG1-167 GEN
Solar/Wind Harmer
3.727
959311AF2-222 GEN
Solar/Wind Harmer
34.076
970257AG2-171 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
6.734
964241AG1-285 GEN
Solar/Wind Harmer
19.68
316131AB2-060 GEN
Solar/Wind Harmer
2.422
316478AD1-087 GEN
Solar/Wind Harmer
1.342
316486AD2-202 GEN
Solar/Wind Harmer
0.393
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.458
971683AH1-343 GEN
Solar/Wind Harmer
4.759
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.706
316283AC2-100 C
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.105
316327AA2-057 GEN
Solar/Wind Harmer
0.707
970917AG2-570 GEN
Solar/Wind Harmer
17.327
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.382
316365GEN2_N
Solar/Wind Harmer
0.443
961601AG1-000A GEN
Solar/Wind Harmer
2.615
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.09
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.039
961681AG1-008 GEN
Solar/Wind Harmer
5.039
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.332
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.123
CPLELTFEXP_CPLE->PJM
CLTF
4.543
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.552
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.96
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.219
WECLTFEXP_WEC->PJM
CLTF
0.123
LAGNLTFEXP_LAGN->PJM
CLTF
2.505
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.252
TVALTFEXP_TVA->PJM
CLTF
1.216

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:130.34 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:891.54
MW Contribution:0.78
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.903
971845AH1-439 GEN
Solar/Wind Harmer
40.178
970285AG2-188 GEN
Solar/Wind Harmer
63.671
315657AE1-056 GEN
Solar/Wind Harmer
15.898
946301AF1-294 GEN
Solar/Wind Harmer
10.139
961791AG1-021 GEN
Solar/Wind Harmer
4.946
970683AG2-441 GEN
Solar/Wind Harmer
27.748
970681AG2-440 GEN
Solar/Wind Harmer
22.198
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.073
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.997
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.254
970865AG2-541 GEN
Solar/Wind Harmer
4.048
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
0.778
970163AG2-111 GEN
Solar/Wind Harmer
0.742
971967AH1-528 GEN
Solar/Wind Harmer
15.039
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.212
970581AG2-369 GEN
Solar/Wind Harmer
3.623
315652AC1-086 GEN
Solar/Wind Harmer
7.469
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.36
970673AG2-436 GEN
Solar/Wind Harmer
13.449
970673AG2-436 GEN
Solar/Wind Harmer
6.81
965291AG1-394 GEN
Solar/Wind Harmer
0.565
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.19
3144293JTRSVLE
50/50
1.002
970535AG2-341 GEN
50/50
2.898
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.406
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.183
963191AG1-168 GEN
Solar/Wind Harmer
3.71
971741AH1-377 GEN
Solar/Wind Harmer
43.786
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.608
971775AH1-396 GEN
Solar/Wind Harmer
2.223
313527AB2-043 GEN
Solar/Wind Harmer
3.505
962561AG1-105 GEN
Solar/Wind Harmer
9.664
939181AE1-148 GEN
Solar/Wind Harmer
9.308
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.602
970933AG2-581 GEN
Solar/Wind Harmer
9.49
316181AB2-040 GEN
Solar/Wind Harmer
1.218
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.963
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.802
316426AA2-053 GEN
Solar/Wind Harmer
0.797
316274AC1-208 GEN
Solar/Wind Harmer
0.766
942751AE2-291 GEN
Solar/Wind Harmer
4.503
972187AH1-678 GEN
Adder
1.745
972185AH1-677 GEN
Adder
3.302
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.47
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.982
3144293JTRSVLE
50/50
1.19
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.102
3151531CLOVER1
50/50
2.917
3147043LAWRENC
50/50
1.102
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.946
971563AH1-280 GEN
Solar/Wind Harmer
4.946
970685AG2-442 GEN
Solar/Wind Harmer
31.078
962491AG1-098 GEN
Solar/Wind Harmer
14.404
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.19
970401AG2-262 GEN
Solar/Wind Harmer
1.07
957481AF2-042 GEN
Solar/Wind Harmer
46.506
315687AD1-152 GEN
Solar/Wind Harmer
1.657
971065AG2-659 GEN
Solar/Wind Harmer
6.686
316129AC1-054 GEN
Solar/Wind Harmer
1.136
971795AH1-408 GEN
Solar/Wind Harmer
8.781
316003AC1-222 GEN
Solar/Wind Harmer
1.14
960081AF2-299 GEN
Solar/Wind Harmer
1.025
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.591
970919AG2-571 GEN
Solar/Wind Harmer
2.137
970087AG2-069 GEN
Solar/Wind Harmer
6.318
316023GEN1_S
Solar/Wind Harmer
0.452
316011AB1-132 GEN
Solar/Wind Harmer
1.389
962571AG1-106 GEN
Solar/Wind Harmer
0.954
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.667
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.456
3144293JTRSVLE
50/50
1.19
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.729
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.576
970909AG2-566 GEN
Solar/Wind Harmer
4.064
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.496
963181AG1-167 GEN
Solar/Wind Harmer
3.71
959311AF2-222 GEN
Solar/Wind Harmer
33.872
970257AG2-171 GEN
Solar/Wind Harmer
11.706
315785AD2-033 C
Solar/Wind Harmer
6.689
964241AG1-285 GEN
Solar/Wind Harmer
19.525
316131AB2-060 GEN
Solar/Wind Harmer
2.4
316478AD1-087 GEN
Solar/Wind Harmer
1.324
316486AD2-202 GEN
Solar/Wind Harmer
0.388
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.381
960061AF2-297 GEN
Solar/Wind Harmer
6.325
971683AH1-343 GEN
Solar/Wind Harmer
4.674
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.702
316283AC2-100 C
Solar/Wind Harmer
0.736
316210AC1-098 GEN
Solar/Wind Harmer
1.064
970917AG2-570 GEN
Solar/Wind Harmer
16.885
316365GEN2_N
Solar/Wind Harmer
0.452
316327AA2-057 GEN
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.367
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
3.951
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.023
NYPJM->LTFIMP_NY
CLTF
0.315
LGEELTFEXP_LGEE->PJM
CLTF
0.251
WECLTFEXP_WEC->PJM
CLTF
0.133
LAGNLTFEXP_LAGN->PJM
CLTF
2.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.001
TVALTFEXP_TVA->PJM
CLTF
1.025

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.65 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:832.11
MW Contribution:0.85
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.579
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.561
970909AG2-566 GEN
Solar/Wind Harmer
4.052
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.429
963181AG1-167 GEN
Solar/Wind Harmer
3.699
959311AF2-222 GEN
Solar/Wind Harmer
33.746
970257AG2-171 GEN
Solar/Wind Harmer
11.66
315785AD2-033 C
Solar/Wind Harmer
6.661
964241AG1-285 GEN
Solar/Wind Harmer
19.423
316131AB2-060 GEN
Solar/Wind Harmer
2.386
316478AD1-087 GEN
Solar/Wind Harmer
1.308
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.384
960061AF2-297 GEN
Solar/Wind Harmer
6.368
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.838
966621AG1-532 GEN
Solar/Wind Harmer
0.176
313506AB2-031 GEN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Harmer
0.725
316210AC1-098 GEN
Solar/Wind Harmer
1.021
970917AG2-570 GEN
Solar/Wind Harmer
16.174
316327AA2-057 GEN
Solar/Wind Harmer
0.648
3146263WOODLND
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.882
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.932
971563AH1-280 GEN
Solar/Wind Harmer
4.932
970685AG2-442 GEN
Solar/Wind Harmer
30.976
962491AG1-098 GEN
Solar/Wind Harmer
14.277
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.093
970401AG2-262 GEN
Solar/Wind Harmer
1.069
957481AF2-042 GEN
Solar/Wind Harmer
45.841
315687AD1-152 GEN
Solar/Wind Harmer
1.641
971065AG2-659 GEN
Solar/Wind Harmer
6.575
316129AC1-054 GEN
Solar/Wind Harmer
1.116
3147043LAWRENC
Adder
1.01
316003AC1-222 GEN
Solar/Wind Harmer
1.164
971795AH1-408 GEN
Solar/Wind Harmer
8.484
960081AF2-299 GEN
Solar/Wind Harmer
0.973
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.567
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
6.053
3146263WOODLND
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.444
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.999
970535AG2-341 GEN
50/50
2.873
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.341
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.165
963191AG1-168 GEN
Solar/Wind Harmer
3.699
971741AH1-377 GEN
Solar/Wind Harmer
43.617
316034AC1-036 C
Solar/Wind Harmer
0.578
970323AG2-213 GEN
Solar/Wind Harmer
15.547
971775AH1-396 GEN
Solar/Wind Harmer
2.214
313527AB2-043 GEN
Solar/Wind Harmer
3.483
962561AG1-105 GEN
Solar/Wind Harmer
9.649
964791AG1-342 GEN
Solar/Wind Harmer
3.499
939181AE1-148 GEN
Solar/Wind Harmer
9.211
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.337
970933AG2-581 GEN
Solar/Wind Harmer
9.235
316181AB2-040 GEN
Solar/Wind Harmer
1.163
942751AE2-291 GEN
Solar/Wind Harmer
5.136
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.898
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.791
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.765
316274AC1-208 GEN
Solar/Wind Harmer
0.735
972187AH1-678 GEN
Adder
1.669
3146776BUCKING
Solar/Wind Helper
3.473
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.981
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.869
971845AH1-439 GEN
Solar/Wind Harmer
40.155
970285AG2-188 GEN
Solar/Wind Harmer
63.627
315657AE1-056 GEN
Solar/Wind Harmer
15.857
946301AF1-294 GEN
Solar/Wind Harmer
10.111
961791AG1-021 GEN
Solar/Wind Harmer
4.932
970683AG2-441 GEN
Solar/Wind Harmer
27.657
970681AG2-440 GEN
Solar/Wind Harmer
22.126
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.048
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.134
970865AG2-541 GEN
Solar/Wind Harmer
4.26
316123AC1-075 GEN
Solar/Wind Harmer
0.971
970165AG2-112 GEN
Solar/Wind Harmer
0.855
970163AG2-111 GEN
Solar/Wind Harmer
0.816
946281AF1-292 GEN
Solar/Wind Harmer
0.194
316087AB2-174 GEN
Solar/Wind Harmer
1.202
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.485
315607AA1-063A GEN
Solar/Wind Harmer
0.732
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.036
970581AG2-369 GEN
Solar/Wind Harmer
3.471
270494AE1-108_GEN
Solar/Wind Helper
4.511
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
CPLELTFEXP_CPLE->PJM
CLTF
3.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.48
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.023
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.205
MECLTFEXP_MEC->PJM
CLTF
0.743
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.299
LGEELTFEXP_LGEE->PJM
CLTF
0.225
WECLTFEXP_WEC->PJM
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
1.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.732
TVALTFEXP_TVA->PJM
CLTF
0.969

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:647.7
MW Contribution:0.58
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
971845AH1-439 GEN
Solar/Wind Harmer
30.485
970285AG2-188 GEN
Solar/Wind Harmer
51.175
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:219.98 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1537.65
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.83
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
972003AH1-546 GEN
Solar/Wind Harmer
49.791
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:219.92 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1537.26
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
972003AH1-546 GEN
Solar/Wind Harmer
49.791
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:216.35 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1512.31
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970933AG2-581 GEN
Solar/Wind Harmer
36.473
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
971967AH1-528 GEN
Solar/Wind Harmer
73.139
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
972003AH1-546 GEN
Solar/Wind Harmer
49.802
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:213.74 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1221.6
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
972003AH1-546 GEN
Solar/Wind Harmer
37.761
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
971967AH1-528 GEN
Solar/Wind Harmer
55.401
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970933AG2-581 GEN
Solar/Wind Harmer
27.701
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:211.19 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1206.97
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
972003AH1-546 GEN
Solar/Wind Harmer
37.761
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.43 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1470.9
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
972003AH1-546 GEN
Solar/Wind Harmer
49.802
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.43 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1470.9
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
972003AH1-546 GEN
Solar/Wind Harmer
49.802
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:137.05 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:957.97
MW Contribution:0.79
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.288
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.951
3147043LAWRENC
50/50
1.104
972003AH1-546 GEN
Solar/Wind Harmer
47.347
316322AB2-045
Solar/Wind Harmer
2.6
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.967
971563AH1-280 GEN
Solar/Wind Harmer
4.967
970685AG2-442 GEN
Solar/Wind Harmer
31.227
962491AG1-098 GEN
Solar/Wind Harmer
14.504
316237AB2-079_GEN
Solar/Wind Harmer
0.638
315693AD1-088 GEN
Solar/Wind Harmer
10.264
970401AG2-262 GEN
Solar/Wind Harmer
1.084
3151611KERR 4
50/50
0.288
3151621KERR 5
50/50
0.288
3151631KERR 6
50/50
0.288
3151641KERR 7
50/50
0.288
3151541CLOVER2
50/50
2.937
971845AH1-439 GEN
Solar/Wind Harmer
40.264
970285AG2-188 GEN
Solar/Wind Harmer
63.811
315657AE1-056 GEN
Solar/Wind Harmer
15.96
946301AF1-294 GEN
Solar/Wind Harmer
10.183
961791AG1-021 GEN
Solar/Wind Harmer
4.967
970683AG2-441 GEN
Solar/Wind Harmer
27.881
970681AG2-440 GEN
Solar/Wind Harmer
22.305
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.107
316239AB2-077_GEN
Solar/Wind Harmer
0.638
316238AB2-078_GEN
Solar/Wind Harmer
0.638
316118AC1-105 GEN
Solar/Wind Harmer
1.013
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.344
970865AG2-541 GEN
Solar/Wind Harmer
4.105
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
0.785
970163AG2-111 GEN
Solar/Wind Harmer
0.749
971967AH1-528 GEN
Solar/Wind Harmer
15.159
315607AA1-063A GEN
Solar/Wind Harmer
0.776
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.313
970581AG2-369 GEN
Solar/Wind Harmer
3.709
316319Z2-044 C
Solar/Wind Harmer
0.377
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.536
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.58
970673AG2-436 GEN
Solar/Wind Harmer
13.57
970673AG2-436 GEN
Solar/Wind Harmer
6.871
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.47
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
957481AF2-042 GEN
Solar/Wind Harmer
46.952
315687AD1-152 GEN
Solar/Wind Harmer
1.686
971065AG2-659 GEN
Solar/Wind Harmer
6.782
316129AC1-054 GEN
Solar/Wind Harmer
1.152
316003AC1-222 GEN
Solar/Wind Harmer
1.16
971795AH1-408 GEN
Solar/Wind Harmer
8.774
960081AF2-299 GEN
Solar/Wind Harmer
1.019
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
316212AC1-099_GEN
Solar/Wind Harmer
0.612
970919AG2-571 GEN
Solar/Wind Harmer
2.186
970087AG2-069 GEN
Solar/Wind Harmer
6.469
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.401
962571AG1-106 GEN
Solar/Wind Harmer
0.963
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.896
316049AB1-081 GEN
Solar/Wind Harmer
0.717
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.692
316023GEN1_S
Solar/Wind Harmer
0.442
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.19
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Helper
1.427
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.006
970535AG2-341 GEN
50/50
2.93
3152661PLYWOOD A
50/50
0.279
3146776BUCKING
Solar/Wind Harmer
-0.308
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.483
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.209
963191AG1-168 GEN
Solar/Wind Harmer
3.725
971741AH1-377 GEN
Solar/Wind Harmer
43.964
316034AC1-036 C
Solar/Wind Harmer
0.583
970323AG2-213 GEN
Solar/Wind Harmer
15.694
971775AH1-396 GEN
Solar/Wind Harmer
2.235
313527AB2-043 GEN
Solar/Wind Harmer
3.534
962561AG1-105 GEN
Solar/Wind Harmer
9.782
939181AE1-148 GEN
Solar/Wind Harmer
9.427
964791AG1-342 GEN
Solar/Wind Harmer
3.547
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.781
970933AG2-581 GEN
Solar/Wind Harmer
9.57
316181AB2-040 GEN
Solar/Wind Harmer
1.222
316222AC1-221 GEN
Solar/Wind Harmer
0.854
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.948
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.979
3145783HORNRTN
Solar/Wind Harmer
0.783
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.288
970413AG2-270 GEN
50/50
12.878
3146776BUCKING
Solar/Wind Harmer
-0.028
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.6
970909AG2-566 GEN
Solar/Wind Harmer
4.079
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.601
963181AG1-167 GEN
Solar/Wind Harmer
3.725
959311AF2-222 GEN
Solar/Wind Harmer
34.052
970257AG2-171 GEN
Solar/Wind Harmer
11.771
315785AD2-033 C
Solar/Wind Harmer
6.728
964241AG1-285 GEN
Solar/Wind Harmer
19.662
316131AB2-060 GEN
Solar/Wind Harmer
2.419
316478AD1-087 GEN
Solar/Wind Harmer
1.34
316486AD2-202 GEN
Solar/Wind Harmer
0.392
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.446
971683AH1-343 GEN
Solar/Wind Harmer
4.749
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.704
316283AC2-100 C
Solar/Wind Harmer
0.785
316210AC1-098 GEN
Solar/Wind Harmer
1.101
316327AA2-057 GEN
Solar/Wind Harmer
0.705
970917AG2-570 GEN
Solar/Wind Harmer
17.269
316426AA2-053 GEN
Solar/Wind Harmer
0.81
316274AC1-208 GEN
Solar/Wind Harmer
0.791
942751AE2-291 GEN
Solar/Wind Harmer
4.521
972187AH1-678 GEN
Adder
1.767
972185AH1-677 GEN
Adder
3.338
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.115
961601AG1-000A GEN
Solar/Wind Harmer
2.573
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
315821AE2-092 GEN
Solar/Wind Helper
2.966
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.38
316365GEN2_N
Solar/Wind Harmer
0.442
961601AG1-000A GEN
Solar/Wind Harmer
2.606
316317KELFORD C
Solar/Wind Harmer
0.305
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.082
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.021
961681AG1-008 GEN
Solar/Wind Harmer
5.021
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.333
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
4.525
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.338
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.871
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.899
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.305
LGEELTFEXP_LGEE->PJM
CLTF
0.208
WECLTFEXP_WEC->PJM
CLTF
0.117
LAGNLTFEXP_LAGN->PJM
CLTF
2.472
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.204
TVALTFEXP_TVA->PJM
CLTF
1.2

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:136.87 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:956.69
MW Contribution:0.75
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3151541CLOVER2
50/50
2.825
971845AH1-439 GEN
Solar/Wind Harmer
40.074
970285AG2-188 GEN
Solar/Wind Harmer
63.49
315657AE1-056 GEN
Solar/Wind Harmer
15.775
946301AF1-294 GEN
Solar/Wind Harmer
10.053
961791AG1-021 GEN
Solar/Wind Harmer
4.904
970683AG2-441 GEN
Solar/Wind Harmer
27.471
970681AG2-440 GEN
Solar/Wind Harmer
21.977
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
5.999
316239AB2-077_GEN
Solar/Wind Harmer
0.62
316238AB2-078_GEN
Solar/Wind Harmer
0.62
316118AC1-105 GEN
Solar/Wind Harmer
0.971
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.022
970865AG2-541 GEN
Solar/Wind Harmer
3.914
946281AF1-292 GEN
Solar/Wind Harmer
0.189
316087AB2-174 GEN
Solar/Wind Harmer
1.174
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.851
970165AG2-112 GEN
Solar/Wind Harmer
0.749
970163AG2-111 GEN
Solar/Wind Harmer
0.714
971967AH1-528 GEN
Solar/Wind Harmer
14.144
315607AA1-063A GEN
Solar/Wind Harmer
0.713
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.505
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.179
3144293JTRSVLE
50/50
0.993
970535AG2-341 GEN
50/50
2.832
3152661PLYWOOD A
50/50
0.267
3146776BUCKING
Solar/Wind Harmer
-0.306
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.246
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.13
963191AG1-168 GEN
Solar/Wind Harmer
3.678
971741AH1-377 GEN
Solar/Wind Harmer
43.39
316034AC1-036 C
Solar/Wind Harmer
0.573
970323AG2-213 GEN
Solar/Wind Harmer
15.422
971775AH1-396 GEN
Solar/Wind Harmer
2.196
313527AB2-043 GEN
Solar/Wind Harmer
3.438
962561AG1-105 GEN
Solar/Wind Harmer
9.444
939181AE1-148 GEN
Solar/Wind Harmer
9.07
964791AG1-342 GEN
Solar/Wind Harmer
3.418
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.069
970933AG2-581 GEN
Solar/Wind Harmer
9.057
316181AB2-040 GEN
Solar/Wind Harmer
1.135
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.876
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.902
3145783HORNRTN
Solar/Wind Harmer
0.721
3145783HORNRTN
Solar/Wind Harmer
0.225
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.766
316426AA2-053 GEN
Solar/Wind Harmer
0.746
942751AE2-291 GEN
Solar/Wind Harmer
4.318
316274AC1-208 GEN
Solar/Wind Harmer
0.714
972187AH1-678 GEN
Adder
1.624
315821AE2-092 GEN
Solar/Wind Helper
2.997
3144293JTRSVLE
50/50
1.179
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.838
972003AH1-546 GEN
Solar/Wind Harmer
47.205
316322AB2-045
Solar/Wind Harmer
2.588
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.904
971563AH1-280 GEN
Solar/Wind Harmer
4.904
970685AG2-442 GEN
Solar/Wind Harmer
30.768
962491AG1-098 GEN
Solar/Wind Harmer
14.136
316237AB2-079_GEN
Solar/Wind Harmer
0.62
315693AD1-088 GEN
Solar/Wind Harmer
9.987
970401AG2-262 GEN
Solar/Wind Harmer
1.044
957481AF2-042 GEN
Solar/Wind Harmer
45.172
315687AD1-152 GEN
Solar/Wind Harmer
1.609
971065AG2-659 GEN
Solar/Wind Harmer
6.46
316129AC1-054 GEN
Solar/Wind Harmer
1.096
3147043LAWRENC
Adder
0.992
316003AC1-222 GEN
Solar/Wind Harmer
1.105
971795AH1-408 GEN
Solar/Wind Harmer
8.324
960081AF2-299 GEN
Solar/Wind Harmer
0.951
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316336AC2-165 C
Solar/Wind Helper
1.456
3144293JTRSVLE
50/50
1.179
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.386
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.532
970909AG2-566 GEN
Solar/Wind Harmer
4.034
3147133PAMPLIN
Solar/Wind Harmer
-0.131
971193AH1-056 GEN
Solar/Wind Harmer
26.292
963181AG1-167 GEN
Solar/Wind Harmer
3.678
959311AF2-222 GEN
Solar/Wind Harmer
33.489
970257AG2-171 GEN
Solar/Wind Harmer
11.567
315785AD2-033 C
Solar/Wind Harmer
6.603
964241AG1-285 GEN
Solar/Wind Harmer
19.215
316131AB2-060 GEN
Solar/Wind Harmer
2.356
316478AD1-087 GEN
Solar/Wind Harmer
1.288
316486AD2-202 GEN
Solar/Wind Harmer
0.377
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.37
960061AF2-297 GEN
Solar/Wind Harmer
6.139
971683AH1-343 GEN
Solar/Wind Harmer
4.525
966621AG1-532 GEN
Solar/Wind Harmer
0.171
313506AB2-031 GEN
Solar/Wind Harmer
0.654
316283AC2-100 C
Solar/Wind Harmer
0.703
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.125
CPLELTFEXP_CPLE->PJM
CLTF
3.699
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.437
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.959
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.906
MECLTFEXP_MEC->PJM
CLTF
0.618
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.351
LGEELTFEXP_LGEE->PJM
CLTF
0.175
WECLTFEXP_WEC->PJM
CLTF
0.091
LAGNLTFEXP_LAGN->PJM
CLTF
1.81
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.409
TVALTFEXP_TVA->PJM
CLTF
0.888

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:133.52 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:933.31
MW Contribution:0.78
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.899
971845AH1-439 GEN
Solar/Wind Harmer
40.166
970285AG2-188 GEN
Solar/Wind Harmer
63.65
315657AE1-056 GEN
Solar/Wind Harmer
15.889
946301AF1-294 GEN
Solar/Wind Harmer
10.133
961791AG1-021 GEN
Solar/Wind Harmer
4.943
970683AG2-441 GEN
Solar/Wind Harmer
27.73
970681AG2-440 GEN
Solar/Wind Harmer
22.184
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.068
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.995
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.242
970865AG2-541 GEN
Solar/Wind Harmer
4.039
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.259
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.881
970165AG2-112 GEN
Solar/Wind Harmer
0.776
970163AG2-111 GEN
Solar/Wind Harmer
0.74
971967AH1-528 GEN
Solar/Wind Harmer
14.996
315607AA1-063A GEN
Solar/Wind Harmer
0.76
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.198
970581AG2-369 GEN
Solar/Wind Harmer
3.61
315652AC1-086 GEN
Solar/Wind Harmer
7.443
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.358
970673AG2-436 GEN
Solar/Wind Harmer
13.401
970673AG2-436 GEN
Solar/Wind Harmer
6.785
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
4.481
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.189
3144293JTRSVLE
50/50
1.001
970535AG2-341 GEN
50/50
2.895
3152661PLYWOOD A
50/50
0.274
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.395
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.179
963191AG1-168 GEN
Solar/Wind Harmer
3.707
971741AH1-377 GEN
Solar/Wind Harmer
43.759
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.596
971775AH1-396 GEN
Solar/Wind Harmer
2.221
313527AB2-043 GEN
Solar/Wind Harmer
3.501
962561AG1-105 GEN
Solar/Wind Harmer
9.651
939181AE1-148 GEN
Solar/Wind Harmer
9.294
964791AG1-342 GEN
Solar/Wind Harmer
3.496
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.573
970933AG2-581 GEN
Solar/Wind Harmer
9.469
316181AB2-040 GEN
Solar/Wind Harmer
1.215
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.932
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.96
3145783HORNRTN
Solar/Wind Harmer
0.768
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.8
316426AA2-053 GEN
Solar/Wind Harmer
0.794
316274AC1-208 GEN
Solar/Wind Harmer
0.763
942751AE2-291 GEN
Solar/Wind Harmer
4.488
972187AH1-678 GEN
Adder
1.739
972185AH1-677 GEN
Adder
3.291
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
315821AE2-092 GEN
Solar/Wind Helper
2.986
3144293JTRSVLE
50/50
1.189
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.71
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.572
970909AG2-566 GEN
Solar/Wind Harmer
4.062
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.482
963181AG1-167 GEN
Solar/Wind Harmer
3.707
959311AF2-222 GEN
Solar/Wind Harmer
33.848
970257AG2-171 GEN
Solar/Wind Harmer
11.697
315785AD2-033 C
Solar/Wind Harmer
6.684
964241AG1-285 GEN
Solar/Wind Harmer
19.507
316131AB2-060 GEN
Solar/Wind Harmer
2.398
316478AD1-087 GEN
Solar/Wind Harmer
1.322
316486AD2-202 GEN
Solar/Wind Harmer
0.387
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.38
960061AF2-297 GEN
Solar/Wind Harmer
6.313
971683AH1-343 GEN
Solar/Wind Harmer
4.664
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.7
316283AC2-100 C
Solar/Wind Harmer
0.734
316210AC1-098 GEN
Solar/Wind Harmer
1.061
970917AG2-570 GEN
Solar/Wind Harmer
16.827
316365GEN2_N
Solar/Wind Harmer
0.451
316327AA2-057 GEN
Solar/Wind Harmer
0.674
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.366
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.189
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.101
3151531CLOVER1
50/50
2.913
3147043LAWRENC
50/50
1.1
972003AH1-546 GEN
Solar/Wind Harmer
47.254
316322AB2-045
Solar/Wind Harmer
2.593
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.943
971563AH1-280 GEN
Solar/Wind Harmer
4.943
970685AG2-442 GEN
Solar/Wind Harmer
31.058
962491AG1-098 GEN
Solar/Wind Harmer
14.389
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.178
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
46.433
315687AD1-152 GEN
Solar/Wind Harmer
1.654
971065AG2-659 GEN
Solar/Wind Harmer
6.674
316129AC1-054 GEN
Solar/Wind Harmer
1.134
971795AH1-408 GEN
Solar/Wind Harmer
8.763
316003AC1-222 GEN
Solar/Wind Harmer
1.138
960081AF2-299 GEN
Solar/Wind Harmer
1.022
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.589
970919AG2-571 GEN
Solar/Wind Harmer
2.13
970087AG2-069 GEN
Solar/Wind Harmer
6.297
316023GEN1_S
Solar/Wind Harmer
0.451
316011AB1-132 GEN
Solar/Wind Harmer
1.384
962571AG1-106 GEN
Solar/Wind Harmer
0.951
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.665
316336AC2-165 C
Solar/Wind Helper
1.458
CPLELTFEXP_CPLE->PJM
CLTF
3.934
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.902
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.343
MECLTFEXP_MEC->PJM
CLTF
0.782
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.325
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.127
LAGNLTFEXP_LAGN->PJM
CLTF
2.053
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.953
TVALTFEXP_TVA->PJM
CLTF
1.009

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:125.05 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:874.1
MW Contribution:0.85
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.559
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.558
970909AG2-566 GEN
Solar/Wind Harmer
4.05
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.415
963181AG1-167 GEN
Solar/Wind Harmer
3.697
959311AF2-222 GEN
Solar/Wind Harmer
33.722
970257AG2-171 GEN
Solar/Wind Harmer
11.651
315785AD2-033 C
Solar/Wind Harmer
6.656
964241AG1-285 GEN
Solar/Wind Harmer
19.405
316131AB2-060 GEN
Solar/Wind Harmer
2.383
316478AD1-087 GEN
Solar/Wind Harmer
1.306
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.383
960061AF2-297 GEN
Solar/Wind Harmer
6.356
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.828
966621AG1-532 GEN
Solar/Wind Harmer
0.175
313506AB2-031 GEN
Solar/Wind Harmer
0.668
316283AC2-100 C
Solar/Wind Harmer
0.723
316210AC1-098 GEN
Solar/Wind Harmer
1.017
970917AG2-570 GEN
Solar/Wind Harmer
16.116
316327AA2-057 GEN
Solar/Wind Harmer
0.646
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.998
970535AG2-341 GEN
50/50
2.87
3152661PLYWOOD A
50/50
0.275
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.329
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.162
963191AG1-168 GEN
Solar/Wind Harmer
3.697
971741AH1-377 GEN
Solar/Wind Harmer
43.59
316034AC1-036 C
Solar/Wind Harmer
0.577
970323AG2-213 GEN
Solar/Wind Harmer
15.535
971775AH1-396 GEN
Solar/Wind Harmer
2.212
313527AB2-043 GEN
Solar/Wind Harmer
3.479
962561AG1-105 GEN
Solar/Wind Harmer
9.636
964791AG1-342 GEN
Solar/Wind Harmer
3.494
939181AE1-148 GEN
Solar/Wind Harmer
9.198
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.308
970933AG2-581 GEN
Solar/Wind Harmer
9.214
316181AB2-040 GEN
Solar/Wind Harmer
1.159
942751AE2-291 GEN
Solar/Wind Harmer
5.121
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.895
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.788
3145783HORNRTN
Solar/Wind Harmer
0.922
3145783HORNRTN
Solar/Wind Harmer
0.738
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.763
316274AC1-208 GEN
Solar/Wind Harmer
0.732
972187AH1-678 GEN
Adder
1.663
315821AE2-092 GEN
Solar/Wind Helper
2.985
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.878
972003AH1-546 GEN
Solar/Wind Harmer
47.257
316322AB2-045
Solar/Wind Harmer
2.592
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.929
971563AH1-280 GEN
Solar/Wind Harmer
4.929
970685AG2-442 GEN
Solar/Wind Harmer
30.955
962491AG1-098 GEN
Solar/Wind Harmer
14.261
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.081
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
45.769
315687AD1-152 GEN
Solar/Wind Harmer
1.638
971065AG2-659 GEN
Solar/Wind Harmer
6.564
316129AC1-054 GEN
Solar/Wind Harmer
1.114
3147043LAWRENC
Adder
1.008
316003AC1-222 GEN
Solar/Wind Harmer
1.162
971795AH1-408 GEN
Solar/Wind Harmer
8.467
960081AF2-299 GEN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.565
970919AG2-571 GEN
Solar/Wind Harmer
2.04
970087AG2-069 GEN
Solar/Wind Harmer
6.032
316336AC2-165 C
Solar/Wind Helper
1.446
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.864
971845AH1-439 GEN
Solar/Wind Harmer
40.143
970285AG2-188 GEN
Solar/Wind Harmer
63.606
315657AE1-056 GEN
Solar/Wind Harmer
15.849
946301AF1-294 GEN
Solar/Wind Harmer
10.105
961791AG1-021 GEN
Solar/Wind Harmer
4.929
970683AG2-441 GEN
Solar/Wind Harmer
27.639
970681AG2-440 GEN
Solar/Wind Harmer
22.111
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.044
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
0.998
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.123
970865AG2-541 GEN
Solar/Wind Harmer
4.251
316123AC1-075 GEN
Solar/Wind Harmer
0.968
970165AG2-112 GEN
Solar/Wind Harmer
0.853
970163AG2-111 GEN
Solar/Wind Harmer
0.813
946281AF1-292 GEN
Solar/Wind Harmer
0.193
316087AB2-174 GEN
Solar/Wind Harmer
1.199
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.441
315607AA1-063A GEN
Solar/Wind Harmer
0.73
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.021
970581AG2-369 GEN
Solar/Wind Harmer
3.458
270494AE1-108_GEN
Solar/Wind Helper
4.516
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
CPLELTFEXP_CPLE->PJM
CLTF
3.818
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.266
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.791
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.144
MECLTFEXP_MEC->PJM
CLTF
0.716
SIGELTFEXP_SIGE->PJM
CLTF
0.02
NYPJM->LTFIMP_NY
CLTF
0.309
LGEELTFEXP_LGEE->PJM
CLTF
0.214
WECLTFEXP_WEC->PJM
CLTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
1.942
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.684
TVALTFEXP_TVA->PJM
CLTF
0.953

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.94 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:679.77
MW Contribution:0.58
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.182
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.848
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.762
972187AH1-678 GEN
50/50
1.749
3146776BUCKING
Solar/Wind Harmer
2.741
3146776BUCKING
Solar/Wind Harmer
0.222
970301AG2-198 GEN
Solar/Wind Harmer
16.173
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.2
963191AG1-168 GEN
Solar/Wind Harmer
1.4
971741AH1-377 GEN
Solar/Wind Harmer
33.04
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.75
971775AH1-396 GEN
Solar/Wind Harmer
0.441
3151611KERR 4
50/50
0.278
3151621KERR 5
50/50
0.278
3151631KERR 6
50/50
0.278
3151641KERR 7
50/50
0.278
3151541CLOVER2
50/50
2.843
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.079
963041AG1-153 GEN
50/50
1.544
971845AH1-439 GEN
Solar/Wind Harmer
30.475
970285AG2-188 GEN
Solar/Wind Harmer
51.158
315657AE1-056 GEN
Solar/Wind Harmer
12.943
3144293JTRSVLE
50/50
1.182
3151591KERR 2
50/50
0.278
970413AG2-270 GEN
50/50
12.466
3151261ROARAP2
50/50
0.085
3151031BRUNSWICKG2
50/50
0.762
3146776BUCKING
Solar/Wind Harmer
0.247
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.043
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.85
963181AG1-167 GEN
Solar/Wind Harmer
1.4
959311AF2-222 GEN
Solar/Wind Harmer
25.461
970257AG2-171 GEN
Solar/Wind Harmer
8.812
315785AD2-033 C
Solar/Wind Harmer
2.115
964241AG1-285 GEN
Solar/Wind Harmer
14.651
316131AB2-060 GEN
Solar/Wind Harmer
0.614
316478AD1-087 GEN
Solar/Wind Harmer
0.465
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.214
939181AE1-148 GEN
Solar/Wind Harmer
6.93
964791AG1-342 GEN
Solar/Wind Harmer
2.751
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.815
970933AG2-581 GEN
Solar/Wind Harmer
6.948
316181AB2-040 GEN
Solar/Wind Harmer
0.106
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.761
3145593CAROLNA
Solar/Wind Harmer
0.087
3145783HORNRTN
Solar/Wind Harmer
1.218
3145783HORNRTN
Solar/Wind Harmer
0.974
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.327
316274AC1-208 GEN
Solar/Wind Harmer
0.31
315821AE2-092 GEN
Solar/Wind Helper
2.982
946301AF1-294 GEN
Solar/Wind Harmer
6.907
961791AG1-021 GEN
Solar/Wind Harmer
3.36
970683AG2-441 GEN
Solar/Wind Harmer
20.922
970681AG2-440 GEN
Solar/Wind Harmer
16.737
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.571
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.326
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.61
970865AG2-541 GEN
Solar/Wind Harmer
3.002
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.286
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.576
970163AG2-111 GEN
Solar/Wind Harmer
0.549
971967AH1-528 GEN
Solar/Wind Harmer
10.852
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.026
970581AG2-369 GEN
Solar/Wind Harmer
2.602
270494AE1-108_GEN
Solar/Wind Helper
4.482
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.699
971683AH1-343 GEN
Solar/Wind Harmer
3.468
313506AB2-031 GEN
Solar/Wind Harmer
0.226
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.53
970917AG2-570 GEN
Solar/Wind Harmer
5.054
316327AA2-057 GEN
Solar/Wind Harmer
0.085
316313AB2-026
Solar/Wind Helper
0.339
316258AE1-075 C
Solar/Wind Helper
0.305
316405AF2-144 C
Solar/Wind Helper
0.254
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.182
3151601KERR 3
50/50
0.278
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.857
3147043LAWRENC
50/50
1.061
3151261ROARAP2
50/50
0.087
3151051BRUNSWICKS1
50/50
1.582
3151021BRUNSWICKG1
50/50
0.762
971451AH1-221 GEN
50/50
2.315
972003AH1-546 GEN
Solar/Wind Harmer
35.828
316322AB2-045
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.867
971563AH1-280 GEN
Solar/Wind Harmer
3.734
970685AG2-442 GEN
Solar/Wind Harmer
23.432
962491AG1-098 GEN
Solar/Wind Harmer
10.785
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.574
970401AG2-262 GEN
Solar/Wind Harmer
0.841
957481AF2-042 GEN
Solar/Wind Harmer
34.537
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.943
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.643
960081AF2-299 GEN
Solar/Wind Harmer
0.73
3145783HORNRTN
Solar/Wind Harmer
0.068
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
2.021
970087AG2-069 GEN
Solar/Wind Harmer
4.539
316336AC2-165 C
Solar/Wind Helper
1.447
CPLELTFEXP_CPLE->PJM
CLTF
3.771
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.922
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.157
MECLTFEXP_MEC->PJM
CLTF
0.729
SIGELTFEXP_SIGE->PJM
CLTF
0.02
NYPJM->LTFIMP_NY
CLTF
0.308
LGEELTFEXP_LGEE->PJM
CLTF
0.221
WECLTFEXP_WEC->PJM
CLTF
0.117
LAGNLTFEXP_LAGN->PJM
CLTF
1.944
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.608
TVALTFEXP_TVA->PJM
CLTF
0.955
CONTINGENCY 'AEP_P4_#10213_05CLOVRD 138_A_SRT-A'
 OPEN BRANCH FROM BUS 242560 TO BUS 242607 CKT 1    /*05BONSCK     138.0 - 05CLOVRD     138.0
 OPEN BRANCH FROM BUS 242560 TO BUS 242840 CKT 1    /*05BONSCK     138.0 - 05VINTON     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243892 CKT 1    /*05CLOVRD     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 242775 CKT 1    /*05MONETA     138.0 - 05ROCKCAS SS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 243892 CKT 1    /*05MONETA     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242773 TO BUS 242840 CKT 1    /*05ROANO1     138.0 - 05VINTON     138.0
 OPEN BRANCH FROM BUS 242775 TO BUS 242802 CKT 1    /*05ROCKCAS SS 138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242775 TO BUS 245675 CKT Z1   /*05ROCKCAS SS 138.0 - 05WHITEHOUS8 138.0
 OPEN BRANCH FROM BUS 243892 TO BUS 290923 CKT Z1   /*05MEADSTORSS 138.0 - 05MEADSTOR8  138.0
END
CONTINGENCY 'AEP_P4_#10210_05CLOVRD 138_A2_SRT-A'
 OPEN BRANCH FROM BUS 242607 TO BUS 243892 CKT 1    /*05CLOVRD     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 242775 CKT 1    /*05MONETA     138.0 - 05ROCKCAS SS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 243892 CKT 1    /*05MONETA     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242775 TO BUS 242802 CKT 1    /*05ROCKCAS SS 138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 243892 TO BUS 290923 CKT Z1   /*05MEADSTORSS 138.0 - 05MEADSTOR8  138.0
 REMOVE LOAD D8 FROM BUS 242607                     /*05CLOVRD     138.0
END
CONTINGENCY 'DVP_P4-2: 151T1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 313825 TO BUS 314696 CKT 1   /*3PLYWOOD     115.0 - 3SEDGE HILL  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
END
CONTINGENCY 'DVP_P4-2: 104702_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 314520                                   /*3SEDGE_1     115.0
END
CONTINGENCY 'DVP_P4-2: 547T566_SRT-S'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314901 TO BUS 314987 CKT 1   /*8BATH CO     500.0 - 8LEXINGTN SC 500.0
 OPEN BRANCH FROM BUS 314912 TO BUS 314987 CKT 1   /*8LEXNGTN     500.0 - 8LEXINGTN SC 500.0
 OPEN BUS 314987                                   /*8LEXINGTN SC 500.0
END
CONTINGENCY 'AEP_P7-1_#10830___SRT-A'
 OPEN BRANCH FROM BUS 242555 TO BUS 242843 CKT 1   /*05BLAINE     138.0 - 05WLAKE      138.0
 OPEN BRANCH FROM BUS 242748 TO BUS 242802 CKT 1   /*05PENHOOK    138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242748 TO BUS 243951 CKT 1   /*05PENHOOK    138.0 - 05REDWOOD    138.0
 OPEN BRANCH FROM BUS 242843 TO BUS 243951 CKT 1   /*05WLAKE      138.0 - 05REDWOOD    138.0
END
CONTINGENCY 'AEP_P2-2_#6213_05WLAKE 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242748 TO BUS 242802 CKT 1   /*05PENHOOK    138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242748 TO BUS 243951 CKT 1   /*05PENHOOK    138.0 - 05REDWOOD    138.0
 OPEN BRANCH FROM BUS 242843 TO BUS 243951 CKT 1   /*05WLAKE      138.0 - 05REDWOOD    138.0
END
CONTINGENCY 'AEP_P2-2_#6212_05WLAKE 138_2_SRT-A'
 OPEN BRANCH FROM BUS 242555 TO BUS 242843 CKT 1   /*05BLAINE     138.0 - 05WLAKE      138.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'DVP_P4-2: 1016T1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 316000 CKT 1   /*3CRSTL HILL  115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 971682 CKT 1   /*3CRSTL HILL  115.0 - AH1-343 TP   115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 314688                                   /*3CRSTL HILL  115.0
 OPEN BUS 316000                                   /*AC1-222 TAP  115.0
 OPEN BUS 316001                                   /*AC1-222 MAIN 115.0
 OPEN BUS 316002                                   /*AC1-222 COL   34.5
 OPEN BUS 316003                                   /*AC1-222 GEN    0.6
END
CONTINGENCY 'DVP_P4-2: 101672_SRT-A'
 OPEN BRANCH FROM BUS 314688 TO BUS 316000 CKT 1   /*3CRSTL HILL  115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 971682 CKT 1   /*3CRSTL HILL  115.0 - AH1-343 TP   115.0
 OPEN BUS 314688                                   /*3CRSTL HILL  115.0
 OPEN BUS 316000                                   /*AC1-222 TAP  115.0
 OPEN BUS 316001                                   /*AC1-222 MAIN 115.0
 OPEN BUS 316002                                   /*AC1-222 COL   34.5
 OPEN BUS 316003                                   /*AC1-222 GEN    0.6
END
CONTINGENCY 'DVP_P4-2: 104772_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 316000                                   /*AC1-222 TAP  115.0
 OPEN BUS 316001                                   /*AC1-222 MAIN 115.0
 OPEN BUS 316002                                   /*AC1-222 COL   34.5
 OPEN BUS 316003                                   /*AC1-222 GEN    0.6
END
CONTINGENCY 'DVP_P1-2: LN 1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
END
CONTINGENCY 'DVP_P1-2: LN 1016_SRT-A-1'
 OPEN BRANCH FROM BUS 314688 TO BUS 316000 CKT 1   /*3CRSTL HILL  115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 971682 CKT 1   /*3CRSTL HILL  115.0 - AH1-343 TP   115.0
 OPEN BUS 314688                                   /*3CRSTL HILL  115.0
END
CONTINGENCY 'AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
END
CONTINGENCY 'AEP_P7-1_#10778___SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242770 CKT 1    /*05E.MONU     138.0 - 05RIGIS      138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 243948 CKT 3    /*05E.MONU     138.0 - 05BRANTLY     69.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242770 TO BUS 243988 CKT 1    /*05RIGIS      138.0 - 05RIGIS       69.0
 OPEN BRANCH FROM BUS 243974 TO BUS 243988 CKT 1    /*05GOODYEAR1   69.0 - 05RIGIS       69.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 56602_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1   /*6LEXNGT2     230.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P4_#10162_05EDAN 1 138_P_SRT-A'
 OPEN BRANCH FROM BUS 242530 TO BUS 242631 CKT 5    /*05EDANV1     230.0 - 05EDAN 1     138.0
 OPEN BRANCH FROM BUS 242530 TO BUS 270450 CKT 1    /*05EDANV1     230.0 - AD2-022 TAP  230.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242620 TO BUS 242631 CKT 1    /*05DANVL2     138.0 - 05EDAN 1     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 243962 CKT 1    /*05EDAN 1     138.0 - 05EDANV1EQ     1.0
 OPEN BRANCH FROM BUS 242631 TO BUS 246972 CKT 1    /*05EDAN 1     138.0 - 05ROCKSP     138.0
 OPEN BRANCH FROM BUS 243960 TO BUS 243962 CKT 1    /*05E.DANVIL    69.0 - 05EDANV1EQ     1.0
 OPEN BRANCH FROM BUS 243961 TO BUS 243962 CKT 1    /*05EDANVILL    12.0 - 05EDANV1EQ     1.0
 REMOVE SWSHUNT FROM BUS 242631                     /*05EDAN 1     138.0
 REMOVE SWSHUNT FROM BUS 243960                     /*05E.DANVIL    69.0
END
CONTINGENCY 'AEP_P4_#10164_05EDAN 2 138_M_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 314668 CKT Z1   /*05BANSTR     138.0 - 4BANISTR     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 970222 CKT 1    /*05BANSTR     138.0 - AG2-152 TP   138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
END
CONTINGENCY 'DVP_P1-2: LN 553_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1                /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1   /*05BRUSHT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1   /*05FOREST     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
END
CONTINGENCY 'AEP_P7-1_#10781___SRT-A-1'
 OPEN BRANCH FROM BUS 242530 TO BUS 270450 CKT 1   /*05EDANV1     230.0 - AD2-022 TAP  230.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1   /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304095 CKT 1   /*6YANCY TAP   230.0 - 6YANCYVILLE  230.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304097 CKT 1   /*6YANCY TAP   230.0 - 6CONCD2230TT 230.0
END
CONTINGENCY 'DVP_P4-2: H2T296_SRT-A'
 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 2   /*3SEDGE HILL  115.0 - 6SEDGE HILL  230.0
 OPEN BRANCH FROM BUS 314697 TO BUS 316218 CKT 1   /*6SEDGE HILL  230.0 - AC1-221 TAP  230.0
END
CONTINGENCY 'DVP_P4-6: SEDGE H T452_SRT-A'
 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 2   /*3SEDGE HILL  115.0 - 6SEDGE HILL  230.0
 OPEN BUS 314520                                   /*3SEDGE_1     115.0
END
CONTINGENCY 'DVP_P4-5: SEDGE H L202_SRT-A'
 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 2   /*3SEDGE HILL  115.0 - 6SEDGE HILL  230.0
END
CONTINGENCY 'DVP_P1-3: 6SEDGE HILL-TX#2_SRT-A'
 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 2   /*3SEDGE HILL  115.0 - 6SEDGE HILL  230.0
END
CONTINGENCY 'DVP_P4-2: 3202_SRT-A'
 OPEN BRANCH FROM BUS 313852 TO BUS 314716 CKT 1   /*3WELCOTAP    115.0 - 3REEDY C     115.0
 OPEN BRANCH FROM BUS 313852 TO BUS 314718 CKT 1   /*3WELCOTAP    115.0 - 3S BOSTN     115.0
 OPEN BRANCH FROM BUS 313852 TO BUS 314724 CKT 1   /*3WELCOTAP    115.0 - 3WELCO       115.0
 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 1   /*3SEDGE HILL  115.0 - 6SEDGE HILL  230.0
 OPEN BRANCH FROM BUS 314696 TO BUS 314717 CKT 1   /*3SEDGE HILL  115.0 - 3SINAI       115.0
 OPEN BRANCH FROM BUS 314717 TO BUS 314718 CKT 1   /*3SINAI       115.0 - 3S BOSTN     115.0
 OPEN BUS 313852                                   /*3WELCOTAP    115.0
 OPEN BUS 314717                                   /*3SINAI       115.0
 OPEN BUS 314718                                   /*3S BOSTN     115.0
 OPEN BUS 314724                                   /*3WELCO       115.0
 OPEN BUS 316248                                   /*AF1-058 C    115.0
END
CONTINGENCY 'DVP_P4-2: H1T296_SRT-A'
 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 1   /*3SEDGE HILL  115.0 - 6SEDGE HILL  230.0
 OPEN BRANCH FROM BUS 314697 TO BUS 316218 CKT 1   /*6SEDGE HILL  230.0 - AC1-221 TAP  230.0
END
CONTINGENCY 'DVP_P4-5: SEDGE H L102_SRT-A'
 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 1   /*3SEDGE HILL  115.0 - 6SEDGE HILL  230.0
END
CONTINGENCY 'DVP_P4-2: 15102_SRT-A'
 OPEN BRANCH FROM BUS 313825 TO BUS 314696 CKT 1   /*3PLYWOOD     115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 1   /*3SEDGE HILL  115.0 - 6SEDGE HILL  230.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 2027_SRT-A-3'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026      230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
END
CONTINGENCY 'DVP_P4-2: 242T2027_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026      230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 587T591_SRT-S'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 202712_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1                /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1                /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                                /*6POWHATN     230.0
 OPEN BUS 316258                                                /*AE1-075 C    230.0
 OPEN BUS 316313                                                /*AB2-026      230.0
 OPEN BUS 316405                                                /*AF2-144 C    230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
END
CONTINGENCY 'DVP_P4-2: 55692_SRT-S'
 OPEN BRANCH FROM BUS 314936 TO BUS 971966 CKT 1                /*8RAWLINGS    500.0 - AH1-528 TP   500.0
 OPEN BUS 314920                                                /*8RAWLIN_STC1 500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: H2T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 2   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H1T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 1   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'AEP_P2-2_#1377_05J.FERR 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242514 TO BUS 290022 CKT 1   /*05J.FERR     765.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 290022 CKT 1   /*05J.FERR     500.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1   /*05J.FERR     500.0 - 8ANTIOCH     500.0
 OPEN BRANCH FROM BUS 290022 TO BUS 290023 CKT 1   /*05J.FERR 1EQ   1.0 - 05J.FERR T1   13.8
END
CONTINGENCY 'DVP_P7-1: LN 2106-2111_SRT-A'
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
END
CONTINGENCY 'DVP_P7-1: LN 2003-205_SRT-S'
 OPEN BRANCH FROM BUS 314263 TO BUS 314287 CKT 1                /*6TYLER1      230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314263 TO BUS 314331 CKT 1                /*6TYLER1      230.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314287 TO BUS 314346 CKT 1                /*6CHESTF B    230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314316 CKT 1                /*6HARR205     230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314346 CKT 1                /*6HARR205     230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 1                /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 2                /*3POE         115.0 - 6POE         230.0
 OPEN BUS 314263                                                /*6TYLER1      230.0
 OPEN BUS 314301                                                /*6HARR205     230.0
 OPEN BUS 314346                                                /*6TYLER       230.0
 OPEN BUS 315839                                                /*AE2-212 C    230.0
 OPEN BUS 316240                                                /*AF1-291 C    230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1   /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'PEPCO_P1_5070_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 57062_SRT-S'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1                /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET POSTCONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P2-2: ALTAVISTA 115KV_SRT-A'
 OPEN BUS 313162   /*3HALL BR TAP 115.0
 OPEN BUS 314515   /*3ALTVS_1     115.0
 OPEN BUS 314666   /*3ALTVSTA     115.0
 OPEN BUS 314700   /*3HALL BR     115.0
 OPEN BUS 314705   /*3HURT        115.0
 OPEN BUS 315156   /*1HALLBR1      13.8
END
CONTINGENCY 'DVP_P4-5: 556X2_SRT-S'
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 313995 TO BUS 957480 CKT 1   /*8FINNEYWOOD  500.0 - AF2-042 TP   500.0
END
CONTINGENCY 'DVP_P4-5: 556X1_SRT-S'
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 313995 TO BUS 957480 CKT 1   /*8FINNEYWOOD  500.0 - AF2-042 TP   500.0
END
CONTINGENCY 'DVP_P4-2: WT576_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P7-1: LN 39-91_SRT-A-2'
 OPEN BRANCH FROM BUS 313179 TO BUS 313271 CKT 1   /*3TURKEYRUN   115.0 - 3TRANSCO TAP 115.0
 OPEN BRANCH FROM BUS 313179 TO BUS 313783 CKT 1   /*3TURKEYRUN   115.0 - 3WALNUT CRK  115.0
 OPEN BRANCH FROM BUS 313270 TO BUS 313271 CKT 1   /*3TRANSCO DP  115.0 - 3TRANSCO TAP 115.0
 OPEN BRANCH FROM BUS 313271 TO BUS 314763 CKT 1   /*3TRANSCO TAP 115.0 - 3KIDDSTO     115.0
 OPEN BRANCH FROM BUS 313783 TO BUS 314773 CKT 1   /*3WALNUT CRK  115.0 - 3RED HIL     115.0
 OPEN BRANCH FROM BUS 314767 TO BUS 314773 CKT 1   /*3MIDWAY      115.0 - 3RED HIL     115.0
 OPEN BRANCH FROM BUS 314767 TO BUS 314793 CKT 1   /*3MIDWAY      115.0 - 3DOOMS       115.0
 OPEN BRANCH FROM BUS 971446 TO BUS 314763 CKT 1   /*AH1-217 TP   115.0 - 3KIDDSTO     115.0
 OPEN BUS 247086                                   /*05REDHIL     115.0
 OPEN BUS 313179                                   /*3TURKEYRUN   115.0
 OPEN BUS 313270                                   /*3TRANSCO DP  115.0
 OPEN BUS 313271                                   /*3TRANSCO TAP 115.0
 OPEN BUS 314763                                   /*3KIDDSTO     115.0
 OPEN BUS 314767                                   /*3MIDWAY      115.0
 OPEN BUS 314773                                   /*3RED HIL     115.0
 OPEN BUS 315817                                   /*AE2-092 MAIN 115.0
 OPEN BUS 315818                                   /*AE2-092 COL   34.5
 OPEN BUS 315819                                   /*AE2-092 TER   13.8
 OPEN BUS 315820                                   /*AE2-092 GSU   34.5
 OPEN BUS 315821                                   /*AE2-092 GEN    0.6
END
CONTINGENCY 'DVP_P2-2: DOOMS B2_SRT-A'
 OPEN BRANCH FROM BUS 313286 TO BUS 314793 CKT 1   /*3WAYNESBORO  115.0 - 3DOOMS       115.0
 OPEN BRANCH FROM BUS 314767 TO BUS 314793 CKT 1   /*3MIDWAY      115.0 - 3DOOMS       115.0
 OPEN BRANCH FROM BUS 314791 TO BUS 314793 CKT 1   /*3BRAND TAP   115.0 - 3DOOMS       115.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-5: 593X1_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-5: 593X2_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P1-2: LN 9344_SRT-A'
 OPEN BRANCH FROM BUS 313393 TO BUS 313905 CKT 1   /*8MARS        500.0 - 8WSHNGSTAR   500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56272_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P7-1: LN 158-235_SRT-A'
 OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1   /*3FLAT CREEK  115.0 - 3LONEPN      115.0
 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1   /*3FLAT CREEK  115.0 - 3MORAN       115.0
 OPEN BRANCH FROM BUS 314268 TO BUS 314692 CKT 1   /*6BRIERY      230.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1   /*3LONEPINE_1  115.0 - 3LONEPN      115.0
 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1   /*3FARMVIL     115.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1   /*3FARMVIL     115.0 - 3MORAN       115.0
 OPEN BRANCH FROM BUS 970300 TO BUS 314268 CKT 1   /*AG2-198 TP   230.0 - 6BRIERY      230.0
 OPEN BUS 313755                                   /*3FLAT CREEK  115.0
 OPEN BUS 314268                                   /*6BRIERY      230.0
 OPEN BUS 314519                                   /*3LONEPINE_1  115.0
 OPEN BUS 314707                                   /*3MORAN       115.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-S'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 941030 TO BUS 970672 CKT 1   /*AE2-094 TP   500.0 - AG2-436 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 58572_SRT-A'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-5: W72_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1   /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-2: XT585_SRT-S'
 OPEN BRANCH FROM BUS 970672 TO BUS 314940 CKT 1                /*AG2-436 TP   500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
END
CONTINGENCY 'DVP_P4-2: 54472_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51192_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BUS 314921                                                /*8RAWLIN_STC2 500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51172_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T544_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'AEP_P2-2_#17572_05MUSEVILLE 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242802 TO BUS 290234 CKT 1   /*05SMITHMTN   138.0 - 05MUSEVILLE  138.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
242549 to 242632 ckt 1
242519 to 314912 ckt 1
242687 to 242734 ckt 1
242741 to 242687 ckt 1
314688 to 316000 ckt 1
313168 to 314696 ckt 1
314696 to 314697 ckt 1
314696 to 314697 ckt 2
314667 to 242741 ckt 1
314747 to 313867 ckt 1
314747 to 970936 ckt 1
313867 to 313707 ckt 1
314268 to 314692 ckt 1
314677 to 972002 ckt 1
314282 to 314285 ckt 1
313868 to 316335 ckt 1
314285 to 314316 ckt 1
314563 to 313994 ckt 1
314290 to 223938 ckt 1
315684 to 314690 ckt 1
313178 to 314435 ckt 1
314692 to 970284 ckt 1
313996 to 313995 ckt 1
313996 to 313995 ckt 2
313996 to 962490 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314322 to 314914 ckt 1
314765 to 314749 ckt 1
313994 to 313178 ckt 1
314435 to 314282 ckt 1
314697 to 315684 ckt 1
314697 to 316218 ckt 1
313911 to 314290 ckt 1
314933 to 972284 ckt 1
314902 to 314914 ckt 1
314905 to 314900 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 314905 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314936 to 314902 ckt 1
314940 to 970672 ckt 1
314923 to 314924 ckt 1
314934 to 314916 ckt 1
314924 to 314903 ckt 1
316218 to 316281 ckt 1
316000 to 313168 ckt 1
316281 to 304070 ckt 1
316335 to 314333 ckt 1
941030 to 314902 ckt 1
962490 to 971740 ckt 1
970222 to 242549 ckt 1
970284 to 971844 ckt 1
970300 to 314268 ckt 1
970672 to 941030 ckt 1
970936 to 313868 ckt 1
971682 to 314688 ckt 1
971740 to 970300 ckt 1
971844 to 314677 ckt 1
972002 to 314747 ckt 1

Winter Peak Analysis

The New Service Request AG2-112 was evaluated as a 15.2 MW (9.12 MW Capacity) injection in the Dominion area.

AG2-112 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 15.2 MW (15.2 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-112 was evaluated as a 15.2 MW injection

AG2-112 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 15.2 MW (15.2 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#10294_05NEWLDN 138_D_SRT-A
BreakerAC110.7 %255.0B282.292.55
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#10293_05NEWLDN 138_C_SRT-A
BreakerAC110.51 %255.0B281.792.55
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#10292_05NEWLDN 138_E_SRT-A
BreakerAC110.5 %255.0B281.782.55
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC110.5 %255.0B281.782.55
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC106.71 %255.0B272.14.03
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC106.67 %255.0B272.014.03
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
DVP_P1-2: LN 13_SRT-A
SingleAC105.36 %255.0B268.672.55
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P1-2_#375_5201_SRT-A
SingleAC105.36 %255.0B268.672.55
GD2DVP
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer
DVP_P1-3: 4ALTVSTA-TX#4_SRT-A
SingleAC119.84 %139.4B167.062.92
GD2DVP
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer
DVP_P1-3: 4ALTVSTA-TX#3_SRT-A
SingleAC105.36 %168.45B177.483.1
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC118.15 %508.54B600.821.74
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-1
SingleAC115.23 %508.54B585.981.74
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC108.28 %541.0B585.782.71
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC108.27 %541.0B585.752.71
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC107.54 %541.0B581.782.7
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC107.54 %541.0B581.782.7

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#10294_05NEWLDN 138_D_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10294_05NEWLDN 138_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.7 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:282.29
MW Contribution:2.55
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
8.612
962561AG1-105 GEN
Solar/Wind Harmer
3.278
3147312GRETNA
Solar/Wind Harmer
1.315
960061AF2-297 GEN
Solar/Wind Harmer
4.119
970401AG2-262 GEN
Solar/Wind Harmer
0.43
3146802CHATHAM
Solar/Wind Harmer
1.233
3147312GRETNA
Solar/Wind Harmer
0.329
970865AG2-541 GEN
Solar/Wind Harmer
4.995
971683AH1-343 GEN
Solar/Wind Harmer
6.809
270013AE1-250 PV
Solar/Wind Helper
1.498
270016AE1-250 BESS
Solar/Wind Helper
1.498
941821AE2-187 GEN
Solar/Wind Harmer
19.724
3147123OTTER R
Solar/Wind Harmer
0.878
970165AG2-112 GEN
Solar/Wind Harmer
2.549
3147173SINAI
Solar/Wind Harmer
0.257
3147243WELCO
Solar/Wind Harmer
0.161
3146843MT LREL
Solar/Wind Harmer
0.196
3146843MT LREL
Solar/Wind Harmer
0.196
270197AD1-017 GEN1
Solar/Wind Helper
1.89
270574AD1-017 GEN2
Solar/Wind Helper
1.701
970481AG2-311 GEN
50/50
Charging
11.011
970163AG2-111 GEN
Solar/Wind Harmer
2.432
964791AG1-342 GEN
Solar/Wind Harmer
1.406
941801AE2-185 GEN
Solar/Wind Harmer
19.724
270173AC1-122 GEN
Solar/Wind Helper
1.998
942751AE2-291 GEN
Solar/Wind Harmer
20.098
961131AF2-404 GEN
Solar/Wind Harmer
11.336
942671AE2-283 GEN
Solar/Wind Harmer
17.423
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.064
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.266
MDUPJM->LTFIMP_MDU
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.607
NYPJM->LTFIMP_NY
CLTF
0.044
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.095
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.826

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#10293_05NEWLDN 138_C_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10293_05NEWLDN 138_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.51 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:281.79
MW Contribution:2.55
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
8.612
962561AG1-105 GEN
Solar/Wind Harmer
3.278
3147312GRETNA
Solar/Wind Harmer
1.315
960061AF2-297 GEN
Solar/Wind Harmer
4.119
970401AG2-262 GEN
Solar/Wind Harmer
0.43
3146802CHATHAM
Solar/Wind Harmer
1.233
3147312GRETNA
Solar/Wind Harmer
0.329
970865AG2-541 GEN
Solar/Wind Harmer
4.995
971683AH1-343 GEN
Solar/Wind Harmer
6.809
270013AE1-250 PV
Solar/Wind Helper
1.498
270016AE1-250 BESS
Solar/Wind Helper
1.498
941821AE2-187 GEN
Solar/Wind Harmer
19.724
3147123OTTER R
Solar/Wind Harmer
0.878
970165AG2-112 GEN
Solar/Wind Harmer
2.549
3147173SINAI
Solar/Wind Harmer
0.257
3147243WELCO
Solar/Wind Harmer
0.161
3146843MT LREL
Solar/Wind Harmer
0.196
3146843MT LREL
Solar/Wind Harmer
0.196
270197AD1-017 GEN1
Solar/Wind Helper
1.89
270574AD1-017 GEN2
Solar/Wind Helper
1.701
970481AG2-311 GEN
50/50
Charging
11.011
970163AG2-111 GEN
Solar/Wind Harmer
2.432
964791AG1-342 GEN
Solar/Wind Harmer
1.406
941801AE2-185 GEN
Solar/Wind Harmer
19.724
270173AC1-122 GEN
Solar/Wind Helper
1.998
942751AE2-291 GEN
Solar/Wind Harmer
20.098
961131AF2-404 GEN
Solar/Wind Harmer
11.336
942671AE2-283 GEN
Solar/Wind Harmer
17.423
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.064
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.266
MDUPJM->LTFIMP_MDU
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.607
NYPJM->LTFIMP_NY
CLTF
0.044
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.095
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.826

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#10292_05NEWLDN 138_E_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10292_05NEWLDN 138_E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.5 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:281.78
MW Contribution:2.55
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
8.612
962561AG1-105 GEN
Solar/Wind Harmer
3.278
3147312GRETNA
Solar/Wind Harmer
1.315
960061AF2-297 GEN
Solar/Wind Harmer
4.119
970401AG2-262 GEN
Solar/Wind Harmer
0.43
3146802CHATHAM
Solar/Wind Harmer
1.233
3147312GRETNA
Solar/Wind Harmer
0.329
970865AG2-541 GEN
Solar/Wind Harmer
4.995
971683AH1-343 GEN
Solar/Wind Harmer
6.809
270013AE1-250 PV
Solar/Wind Helper
1.498
270016AE1-250 BESS
Solar/Wind Helper
1.498
941821AE2-187 GEN
Solar/Wind Harmer
19.724
3147123OTTER R
Solar/Wind Harmer
0.878
970165AG2-112 GEN
Solar/Wind Harmer
2.549
3147173SINAI
Solar/Wind Harmer
0.257
3147243WELCO
Solar/Wind Harmer
0.161
3146843MT LREL
Solar/Wind Harmer
0.196
3146843MT LREL
Solar/Wind Harmer
0.196
270197AD1-017 GEN1
Solar/Wind Helper
1.89
270574AD1-017 GEN2
Solar/Wind Helper
1.701
970481AG2-311 GEN
50/50
Charging
11.011
970163AG2-111 GEN
Solar/Wind Harmer
2.432
964791AG1-342 GEN
Solar/Wind Harmer
1.406
941801AE2-185 GEN
Solar/Wind Harmer
19.724
270173AC1-122 GEN
Solar/Wind Helper
1.998
942751AE2-291 GEN
Solar/Wind Harmer
20.098
961131AF2-404 GEN
Solar/Wind Harmer
11.336
942671AE2-283 GEN
Solar/Wind Harmer
17.423
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.064
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.266
MDUPJM->LTFIMP_MDU
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.607
NYPJM->LTFIMP_NY
CLTF
0.044
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.095
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.826

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.5 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:281.78
MW Contribution:2.55
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
8.612
962561AG1-105 GEN
Solar/Wind Harmer
3.278
3147312GRETNA
Solar/Wind Harmer
1.315
960061AF2-297 GEN
Solar/Wind Harmer
4.119
970401AG2-262 GEN
Solar/Wind Harmer
0.43
3146802CHATHAM
Solar/Wind Harmer
1.233
3147312GRETNA
Solar/Wind Harmer
0.329
970865AG2-541 GEN
Solar/Wind Harmer
4.995
971683AH1-343 GEN
Solar/Wind Harmer
6.809
270013AE1-250 PV
Solar/Wind Helper
1.498
270016AE1-250 BESS
Solar/Wind Helper
1.498
941821AE2-187 GEN
Solar/Wind Harmer
19.724
3147123OTTER R
Solar/Wind Harmer
0.878
970165AG2-112 GEN
Solar/Wind Harmer
2.549
3147173SINAI
Solar/Wind Harmer
0.257
3147243WELCO
Solar/Wind Harmer
0.161
3146843MT LREL
Solar/Wind Harmer
0.196
3146843MT LREL
Solar/Wind Harmer
0.196
270197AD1-017 GEN1
Solar/Wind Helper
1.89
270574AD1-017 GEN2
Solar/Wind Helper
1.701
970481AG2-311 GEN
50/50
Charging
11.011
970163AG2-111 GEN
Solar/Wind Harmer
2.432
964791AG1-342 GEN
Solar/Wind Harmer
1.406
941801AE2-185 GEN
Solar/Wind Harmer
19.724
270173AC1-122 GEN
Solar/Wind Helper
1.998
942751AE2-291 GEN
Solar/Wind Harmer
20.098
961131AF2-404 GEN
Solar/Wind Harmer
11.336
942671AE2-283 GEN
Solar/Wind Harmer
17.423
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.064
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.266
MDUPJM->LTFIMP_MDU
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.607
NYPJM->LTFIMP_NY
CLTF
0.044
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.095
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.826

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.71 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:272.1
MW Contribution:4.03
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
18.825
3147312GRETNA
Solar/Wind Harmer
1.091
962751AG1-124 GEN
Solar/Wind Harmer
3.544
3146802CHATHAM
Solar/Wind Harmer
1.023
3147312GRETNA
Solar/Wind Harmer
0.273
971683AH1-343 GEN
Solar/Wind Harmer
18.313
970865AG2-541 GEN
Solar/Wind Harmer
10.918
270013AE1-250 PV
Solar/Wind Helper
1.772
270016AE1-250 BESS
Solar/Wind Helper
1.772
941821AE2-187 GEN
Solar/Wind Harmer
16.371
3147123OTTER R
Solar/Wind Harmer
0.796
970165AG2-112 GEN
Solar/Wind Harmer
4.034
270197AD1-017 GEN1
Solar/Wind Helper
2.145
270574AD1-017 GEN2
Solar/Wind Helper
1.931
970481AG2-311 GEN
50/50
Charging
12.136
970163AG2-111 GEN
Solar/Wind Harmer
3.848
941801AE2-185 GEN
Solar/Wind Harmer
16.371
270173AC1-122 GEN
Solar/Wind Helper
1.614
942751AE2-291 GEN
Solar/Wind Harmer
27.071
958131AF2-107 GEN
Solar/Wind Harmer
1.778
961131AF2-404 GEN
Solar/Wind Harmer
9.408
942671AE2-283 GEN
Solar/Wind Harmer
14.461
NYPJM->LTFIMP_NY
CLTF
0.042
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.365
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.16
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.194
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.05
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.67 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:272.01
MW Contribution:4.03
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
18.825
3147312GRETNA
Solar/Wind Harmer
1.091
962751AG1-124 GEN
Solar/Wind Harmer
3.544
3146802CHATHAM
Solar/Wind Harmer
1.023
3147312GRETNA
Solar/Wind Harmer
0.273
971683AH1-343 GEN
Solar/Wind Harmer
18.313
970865AG2-541 GEN
Solar/Wind Harmer
10.918
270013AE1-250 PV
Solar/Wind Helper
1.772
270016AE1-250 BESS
Solar/Wind Helper
1.772
941821AE2-187 GEN
Solar/Wind Harmer
16.371
3147123OTTER R
Solar/Wind Harmer
0.796
970165AG2-112 GEN
Solar/Wind Harmer
4.034
270197AD1-017 GEN1
Solar/Wind Helper
2.145
270574AD1-017 GEN2
Solar/Wind Helper
1.931
970481AG2-311 GEN
50/50
Charging
12.135
970163AG2-111 GEN
Solar/Wind Harmer
3.848
941801AE2-185 GEN
Solar/Wind Harmer
16.371
270173AC1-122 GEN
Solar/Wind Helper
1.614
942751AE2-291 GEN
Solar/Wind Harmer
27.071
958131AF2-107 GEN
Solar/Wind Harmer
1.778
961131AF2-404 GEN
Solar/Wind Harmer
9.409
942671AE2-283 GEN
Solar/Wind Harmer
14.461
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.399
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.042
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.363
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.05
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.194
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 13_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 13_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:268.67
MW Contribution:2.55
Bus #Bus NameTypeMW Contribution
962561AG1-105 GEN
Solar/Wind Harmer
3.278
3147312GRETNA
Solar/Wind Harmer
1.315
960061AF2-297 GEN
Solar/Wind Harmer
4.119
970401AG2-262 GEN
Solar/Wind Harmer
0.43
3146802CHATHAM
Solar/Wind Harmer
1.233
3147312GRETNA
Solar/Wind Harmer
0.329
971683AH1-343 GEN
Solar/Wind Harmer
6.809
270013AE1-250 PV
Solar/Wind Helper
1.497
270016AE1-250 BESS
Solar/Wind Helper
1.497
941821AE2-187 GEN
Solar/Wind Harmer
19.725
3147123OTTER R
Solar/Wind Harmer
0.878
970165AG2-112 GEN
Solar/Wind Harmer
2.549
3147173SINAI
Solar/Wind Harmer
0.257
3147243WELCO
Solar/Wind Harmer
0.161
3146843MT LREL
Solar/Wind Harmer
0.196
3146843MT LREL
Solar/Wind Harmer
0.196
270197AD1-017 GEN1
Solar/Wind Helper
1.89
270574AD1-017 GEN2
Solar/Wind Helper
1.701
970481AG2-311 GEN
50/50
Charging
11.01
970163AG2-111 GEN
Solar/Wind Harmer
2.432
964791AG1-342 GEN
Solar/Wind Harmer
1.406
941801AE2-185 GEN
Solar/Wind Harmer
19.725
270173AC1-122 GEN
Solar/Wind Helper
1.997
942751AE2-291 GEN
Solar/Wind Harmer
20.099
961131AF2-404 GEN
Solar/Wind Harmer
11.336
942671AE2-283 GEN
Solar/Wind Harmer
17.424
NYPJM->LTFIMP_NY
CLTF
0.044
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.095
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.826
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.607
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.064
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.266
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P1-2_#375_5201_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#375_5201_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:268.67
MW Contribution:2.55
Bus #Bus NameTypeMW Contribution
962561AG1-105 GEN
Solar/Wind Harmer
3.278
3147312GRETNA
Solar/Wind Harmer
1.315
960061AF2-297 GEN
Solar/Wind Harmer
4.119
970401AG2-262 GEN
Solar/Wind Harmer
0.43
3146802CHATHAM
Solar/Wind Harmer
1.233
3147312GRETNA
Solar/Wind Harmer
0.329
971683AH1-343 GEN
Solar/Wind Harmer
6.809
270013AE1-250 PV
Solar/Wind Helper
1.497
270016AE1-250 BESS
Solar/Wind Helper
1.497
941821AE2-187 GEN
Solar/Wind Harmer
19.725
3147123OTTER R
Solar/Wind Harmer
0.878
970165AG2-112 GEN
Solar/Wind Harmer
2.549
3147173SINAI
Solar/Wind Harmer
0.257
3147243WELCO
Solar/Wind Harmer
0.161
3146843MT LREL
Solar/Wind Harmer
0.196
3146843MT LREL
Solar/Wind Harmer
0.196
270197AD1-017 GEN1
Solar/Wind Helper
1.89
270574AD1-017 GEN2
Solar/Wind Helper
1.701
970481AG2-311 GEN
50/50
Charging
11.01
970163AG2-111 GEN
Solar/Wind Harmer
2.432
964791AG1-342 GEN
Solar/Wind Harmer
1.406
941801AE2-185 GEN
Solar/Wind Harmer
19.725
270173AC1-122 GEN
Solar/Wind Helper
1.997
942751AE2-291 GEN
Solar/Wind Harmer
20.099
961131AF2-404 GEN
Solar/Wind Harmer
11.336
942671AE2-283 GEN
Solar/Wind Harmer
17.424
NYPJM->LTFIMP_NY
CLTF
0.044
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.095
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.826
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.607
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.064
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.266
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-3: 4ALTVSTA-TX#4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.84 %
Rating:139.4 MVA
Rating Type:B
MVA to Mitigate:167.06
MW Contribution:2.92
Bus #Bus NameTypeMW Contribution
962561AG1-105 GEN
Solar/Wind Harmer
3.891
960061AF2-297 GEN
Solar/Wind Harmer
4.846
970401AG2-262 GEN
Solar/Wind Harmer
0.509
970099AG2-077 GEN
Solar/Wind Harmer
2.96
944591AF1-124 GEN
Solar/Wind Harmer
5.534
971683AH1-343 GEN
Solar/Wind Harmer
7.864
3147123OTTER R
Solar/Wind Harmer
1
970165AG2-112 GEN
Solar/Wind Harmer
2.919
3147173SINAI
Solar/Wind Harmer
0.303
3147243WELCO
Solar/Wind Harmer
0.189
3146843MT LREL
Solar/Wind Harmer
0.232
3146843MT LREL
Solar/Wind Harmer
0.232
270197AD1-017 GEN1
Solar/Wind Helper
1.188
270574AD1-017 GEN2
Solar/Wind Helper
1.069
970481AG2-311 GEN
50/50
Charging
7.092
970163AG2-111 GEN
Solar/Wind Harmer
2.785
964791AG1-342 GEN
Solar/Wind Harmer
1.665
270173AC1-122 GEN
Solar/Wind Helper
1.539
942751AE2-291 GEN
Solar/Wind Harmer
22.975
961131AF2-404 GEN
50/50
Charging
5.142
316217AC1-145 GEN
Solar/Wind Helper
3.471
957481AF2-042 GEN
Solar/Wind Harmer
7.4
316197AC1-042 GEN
Solar/Wind Helper
2.7
VFTLTFEXP_VFT->PJM
CMTX
0.26
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.959
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.784
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.835
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.245
G-007ALTFEXP_G-007A->PJM
CMTX
0.102
CPLELTFEXP_CPLE->PJM
CLTF
0.709
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.253
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-3: 4ALTVSTA-TX#3_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:168.45 MVA
Rating Type:B
MVA to Mitigate:177.48
MW Contribution:3.1
Bus #Bus NameTypeMW Contribution
962561AG1-105 GEN
Solar/Wind Harmer
4.135
960061AF2-297 GEN
Solar/Wind Harmer
5.15
970401AG2-262 GEN
Solar/Wind Harmer
0.541
970099AG2-077 GEN
Solar/Wind Harmer
3.146
944591AF1-124 GEN
Solar/Wind Harmer
5.881
971683AH1-343 GEN
Solar/Wind Harmer
8.357
3147123OTTER R
Solar/Wind Harmer
1.063
970165AG2-112 GEN
Solar/Wind Harmer
3.102
3147173SINAI
Solar/Wind Harmer
0.322
3147243WELCO
Solar/Wind Harmer
0.201
3146843MT LREL
Solar/Wind Harmer
0.247
3146843MT LREL
Solar/Wind Harmer
0.247
270197AD1-017 GEN1
Solar/Wind Helper
1.263
270574AD1-017 GEN2
Solar/Wind Helper
1.136
970481AG2-311 GEN
50/50
Charging
7.537
970163AG2-111 GEN
Solar/Wind Harmer
2.96
964791AG1-342 GEN
Solar/Wind Harmer
1.77
270173AC1-122 GEN
Solar/Wind Helper
1.635
942751AE2-291 GEN
Solar/Wind Harmer
24.417
961131AF2-404 GEN
50/50
Charging
5.465
316217AC1-145 GEN
Solar/Wind Helper
3.689
957481AF2-042 GEN
Solar/Wind Harmer
7.864
316197AC1-042 GEN
Solar/Wind Helper
2.869
G-007ALTFEXP_G-007A->PJM
CMTX
0.108
CPLELTFEXP_CPLE->PJM
CLTF
0.754
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.006
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.269
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.888
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.324
VFTLTFEXP_VFT->PJM
CMTX
0.276
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.019
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.833

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.15 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:600.82
MW Contribution:1.74
Bus #Bus NameTypeMW Contribution
962561AG1-105 GEN
Solar/Wind Harmer
12.558
972185AH1-677 GEN
50/50
6.349
944641AF1-129 GEN
50/50
8.974
960061AF2-297 GEN
Solar/Wind Harmer
15.055
970401AG2-262 GEN
Solar/Wind Harmer
1.628
970099AG2-077 GEN
Solar/Wind Harmer
21.178
964241AG1-285 GEN
Solar/Wind Harmer
11.266
970413AG2-270 GEN
50/50
33.803
971683AH1-343 GEN
Solar/Wind Harmer
10.923
270013AE1-250 PV
Solar/Wind Helper
2.088
270016AE1-250 BESS
Solar/Wind Helper
2.088
971629AH1-314 GEN
50/50
Charging
15.608
3147043LAWRENC
50/50
0.859
943811AF1-049 GEN
Solar/Wind Helper
3.28
316319Z2-044 C
Solar/Wind Helper
0.172
3147173SINAI
Solar/Wind Harmer
0.941
3147243WELCO
Solar/Wind Harmer
0.588
970165AG2-112 GEN
Solar/Wind Harmer
1.742
270455AD2-022 GEN
Solar/Wind Helper
4.93
270336AE1-100 GEN
Solar/Wind Helper
1.52
316359AB2-059 GEN
Solar/Wind Helper
1.805
3146843MT LREL
Solar/Wind Harmer
0.742
3146843MT LREL
Solar/Wind Harmer
0.742
959311AF2-222 GEN
Solar/Wind Harmer
14.262
270197AD1-017 GEN1
Solar/Wind Helper
1.326
270574AD1-017 GEN2
Solar/Wind Helper
1.193
316420AA1-050 GEN
Solar/Wind Helper
1.199
963041AG1-153 GEN
50/50
7.315
970163AG2-111 GEN
Solar/Wind Harmer
1.662
970535AG2-341 GEN
50/50
6.451
972187AH1-678 GEN
50/50
3.316
964791AG1-342 GEN
Solar/Wind Harmer
5.329
270457AD2-023 GEN
Solar/Wind Helper
2.773
962491AG1-098 GEN
Solar/Wind Harmer
10.652
3150921YORKTN3
50/50
1.678
942751AE2-291 GEN
Solar/Wind Harmer
9.796
316494AC1-189 GEN
Solar/Wind Helper
1.105
970919AG2-571 GEN
50/50
Charging
15.537
970531AG2-338 GEN
50/50
3.538
961601AG1-000A GEN
50/50
Charging
5.465
315693AD1-088 GEN
Solar/Wind Harmer
8.041
971741AH1-377 GEN
Solar/Wind Harmer
16.042
3144303KENBRDG
Solar/Wind Harmer
0.345
972263AH1-716 GEN
50/50
38.484
970257AG2-171 GEN
Solar/Wind Harmer
5.172
270069AE2-166 C O1
Solar/Wind Helper
1.986
970533AG2-339 GEN
50/50
8.846
972205AH1-687 GEN
50/50
3.283
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
6.896
970417AG2-272 GEN
50/50
Charging
5.345
941591AE2-156 GEN
50/50
5.817
957481AF2-042 GEN
Solar/Wind Harmer
52.946
971775AH1-396 GEN
Solar/Wind Harmer
1.034
270018AE2-047 C O1
Solar/Wind Helper
1.413
316049AB1-081 GEN
Solar/Wind Helper
1.444
970685AG2-442 GEN
Solar/Wind Harmer
6.971
G-007ALTFEXP_G-007A->PJM
CMTX
2.959
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.892
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.063
MDUPJM->LTFIMP_MDU
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.232
HAMLETPJM->LTFIMP_HAMLET
CLTF
7.441
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
7.862
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
11.676
BlueGrassPJM->LTFIMP_BlueG
CLTF
6.491

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-1


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.23 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:585.98
MW Contribution:1.74
Bus #Bus NameTypeMW Contribution
962561AG1-105 GEN
Solar/Wind Harmer
12.558
972185AH1-677 GEN
50/50
6.349
944641AF1-129 GEN
50/50
3.386
960061AF2-297 GEN
Solar/Wind Harmer
15.055
970401AG2-262 GEN
Solar/Wind Harmer
1.628
970099AG2-077 GEN
Solar/Wind Harmer
21.178
964241AG1-285 GEN
Solar/Wind Harmer
11.266
970413AG2-270 GEN
50/50
33.803
971683AH1-343 GEN
Solar/Wind Harmer
10.923
270013AE1-250 PV
Solar/Wind Helper
2.088
270016AE1-250 BESS
Solar/Wind Helper
2.088
971629AH1-314 GEN
50/50
Charging
15.608
3147043LAWRENC
50/50
0.859
943811AF1-049 GEN
Solar/Wind Helper
3.28
316319Z2-044 C
Solar/Wind Helper
0.172
3147173SINAI
Solar/Wind Harmer
0.941
3147243WELCO
Solar/Wind Harmer
0.588
970165AG2-112 GEN
Solar/Wind Harmer
1.742
270455AD2-022 GEN
Solar/Wind Helper
4.93
270336AE1-100 GEN
Solar/Wind Helper
1.52
316359AB2-059 GEN
Solar/Wind Helper
1.805
3146843MT LREL
Solar/Wind Harmer
0.742
3146843MT LREL
Solar/Wind Harmer
0.742
959311AF2-222 GEN
Solar/Wind Harmer
14.262
270197AD1-017 GEN1
Solar/Wind Helper
1.326
270574AD1-017 GEN2
Solar/Wind Helper
1.193
316420AA1-050 GEN
Solar/Wind Helper
1.199
963041AG1-153 GEN
50/50
7.315
970163AG2-111 GEN
Solar/Wind Harmer
1.662
970535AG2-341 GEN
50/50
6.451
972187AH1-678 GEN
50/50
3.316
964791AG1-342 GEN
Solar/Wind Harmer
5.329
270457AD2-023 GEN
Solar/Wind Helper
2.773
962491AG1-098 GEN
Solar/Wind Harmer
10.652
3150921YORKTN3
50/50
1.678
942751AE2-291 GEN
Solar/Wind Harmer
9.796
316494AC1-189 GEN
Solar/Wind Helper
1.105
970531AG2-338 GEN
50/50
3.538
961601AG1-000A GEN
50/50
Charging
5.465
315693AD1-088 GEN
Solar/Wind Harmer
8.041
971741AH1-377 GEN
Solar/Wind Harmer
16.042
3144303KENBRDG
Solar/Wind Harmer
0.345
972263AH1-716 GEN
50/50
38.484
970257AG2-171 GEN
Solar/Wind Harmer
5.172
270069AE2-166 C O1
Solar/Wind Helper
1.986
970533AG2-339 GEN
50/50
8.846
972205AH1-687 GEN
50/50
3.283
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
6.896
970417AG2-272 GEN
50/50
Charging
5.345
941591AE2-156 GEN
50/50
5.817
957481AF2-042 GEN
Solar/Wind Harmer
52.946
971775AH1-396 GEN
Solar/Wind Harmer
1.034
270018AE2-047 C O1
Solar/Wind Helper
1.413
316049AB1-081 GEN
Solar/Wind Helper
1.444
970685AG2-442 GEN
Solar/Wind Harmer
6.971
G-007ALTFEXP_G-007A->PJM
CMTX
2.959
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.892
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.063
MDUPJM->LTFIMP_MDU
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.232
HAMLETPJM->LTFIMP_HAMLET
CLTF
7.441
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
7.862
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
11.676
BlueGrassPJM->LTFIMP_BlueG
CLTF
6.491

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.28 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:585.78
MW Contribution:2.71
Bus #Bus NameTypeMW Contribution
962561AG1-105 GEN
Solar/Wind Harmer
19.777
970865AG2-541 GEN
Solar/Wind Harmer
15.351
960061AF2-297 GEN
Solar/Wind Harmer
21.933
970099AG2-077 GEN
Solar/Wind Harmer
50.807
970401AG2-262 GEN
Solar/Wind Harmer
2.522
970909AG2-566 GEN
Solar/Wind Harmer
9.127
964241AG1-285 GEN
Solar/Wind Harmer
20.536
970413AG2-270 GEN
50/50
68.067
971683AH1-343 GEN
Solar/Wind Harmer
16.229
970865AG2-541 GEN
Solar/Wind Harmer
8.904
3147043LAWRENC
50/50
1.436
3147173SINAI
Solar/Wind Harmer
1.371
3147243WELCO
Solar/Wind Harmer
0.857
970165AG2-112 GEN
Solar/Wind Harmer
2.709
270455AD2-022 GEN
Solar/Wind Helper
2.726
3146843MT LREL
Solar/Wind Harmer
1.148
3146843MT LREL
Solar/Wind Harmer
1.148
959311AF2-222 GEN
Solar/Wind Harmer
8.633
970163AG2-111 GEN
Solar/Wind Harmer
2.584
970535AG2-341 GEN
50/50
12.863
964791AG1-342 GEN
Solar/Wind Harmer
8.253
971443AH1-215 GEN
Solar/Wind Harmer
4.414
270457AD2-023 GEN
Solar/Wind Helper
1.534
962491AG1-098 GEN
Solar/Wind Harmer
24.154
971443AH1-215 GEN
Solar/Wind Harmer
4.267
315693AD1-088 GEN
Solar/Wind Harmer
18.274
971741AH1-377 GEN
Solar/Wind Harmer
35.039
3144303KENBRDG
Solar/Wind Harmer
0.638
970257AG2-171 GEN
Solar/Wind Harmer
9.575
972205AH1-687 GEN
50/50
5.169
970301AG2-198 GEN
Solar/Wind Harmer
14.117
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
12.766
957481AF2-042 GEN
Solar/Wind Harmer
127.018
971775AH1-396 GEN
Solar/Wind Harmer
1.915
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.442
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
1.251
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.476
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.27 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:585.75
MW Contribution:2.71
Bus #Bus NameTypeMW Contribution
962561AG1-105 GEN
Solar/Wind Harmer
19.776
970865AG2-541 GEN
Solar/Wind Harmer
15.351
960061AF2-297 GEN
Solar/Wind Harmer
21.932
970099AG2-077 GEN
Solar/Wind Harmer
50.8
970401AG2-262 GEN
Solar/Wind Harmer
2.522
970909AG2-566 GEN
Solar/Wind Harmer
9.128
964241AG1-285 GEN
Solar/Wind Harmer
20.537
970413AG2-270 GEN
50/50
68.062
971683AH1-343 GEN
Solar/Wind Harmer
16.228
970865AG2-541 GEN
Solar/Wind Harmer
8.903
3147043LAWRENC
50/50
1.436
3147173SINAI
Solar/Wind Harmer
1.371
3147243WELCO
Solar/Wind Harmer
0.857
970165AG2-112 GEN
Solar/Wind Harmer
2.709
270455AD2-022 GEN
Solar/Wind Helper
2.726
3146843MT LREL
Solar/Wind Harmer
1.148
3146843MT LREL
Solar/Wind Harmer
1.148
959311AF2-222 GEN
Solar/Wind Harmer
8.633
970163AG2-111 GEN
Solar/Wind Harmer
2.584
970535AG2-341 GEN
50/50
12.863
964791AG1-342 GEN
Solar/Wind Harmer
8.253
971443AH1-215 GEN
Solar/Wind Harmer
4.414
270457AD2-023 GEN
Solar/Wind Helper
1.534
962491AG1-098 GEN
Solar/Wind Harmer
24.157
971443AH1-215 GEN
Solar/Wind Harmer
4.267
315693AD1-088 GEN
Solar/Wind Harmer
18.276
971741AH1-377 GEN
Solar/Wind Harmer
35.043
3144303KENBRDG
Solar/Wind Harmer
0.638
970257AG2-171 GEN
Solar/Wind Harmer
9.575
972205AH1-687 GEN
50/50
5.17
970301AG2-198 GEN
Solar/Wind Harmer
14.118
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
12.767
957481AF2-042 GEN
Solar/Wind Harmer
127.001
971775AH1-396 GEN
Solar/Wind Harmer
1.915
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.442
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
1.252
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.476
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.54 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:581.78
MW Contribution:2.7
Bus #Bus NameTypeMW Contribution
962561AG1-105 GEN
Solar/Wind Harmer
19.746
970865AG2-541 GEN
Solar/Wind Harmer
15.293
960061AF2-297 GEN
Solar/Wind Harmer
21.853
970099AG2-077 GEN
Solar/Wind Harmer
49.882
970401AG2-262 GEN
Solar/Wind Harmer
2.517
970909AG2-566 GEN
Solar/Wind Harmer
9.256
964241AG1-285 GEN
Solar/Wind Harmer
20.591
970413AG2-270 GEN
50/50
67.43
971683AH1-343 GEN
Solar/Wind Harmer
16.168
970865AG2-541 GEN
Solar/Wind Harmer
8.87
3147043LAWRENC
50/50
1.438
3147173SINAI
Solar/Wind Harmer
1.366
3147243WELCO
Solar/Wind Harmer
0.854
970165AG2-112 GEN
Solar/Wind Harmer
2.698
270455AD2-022 GEN
Solar/Wind Helper
2.745
3146843MT LREL
Solar/Wind Harmer
1.146
3146843MT LREL
Solar/Wind Harmer
1.146
959311AF2-222 GEN
Solar/Wind Harmer
8.672
970163AG2-111 GEN
Solar/Wind Harmer
2.574
970535AG2-341 GEN
50/50
12.889
964791AG1-342 GEN
Solar/Wind Harmer
8.237
971443AH1-215 GEN
Solar/Wind Harmer
4.432
270457AD2-023 GEN
Solar/Wind Helper
1.544
962491AG1-098 GEN
Solar/Wind Harmer
24.516
971443AH1-215 GEN
Solar/Wind Harmer
4.285
315693AD1-088 GEN
Solar/Wind Harmer
18.549
971741AH1-377 GEN
Solar/Wind Harmer
35.543
3144303KENBRDG
Solar/Wind Harmer
0.641
970257AG2-171 GEN
Solar/Wind Harmer
9.616
972205AH1-687 GEN
50/50
5.236
970301AG2-198 GEN
Solar/Wind Harmer
14.316
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
12.821
957481AF2-042 GEN
Solar/Wind Harmer
124.704
971775AH1-396 GEN
Solar/Wind Harmer
1.923
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.469
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.36
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
1.294
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.898
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.634
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.836
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.492
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.8
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.54 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:581.78
MW Contribution:2.7
Bus #Bus NameTypeMW Contribution
962561AG1-105 GEN
Solar/Wind Harmer
19.746
970865AG2-541 GEN
Solar/Wind Harmer
15.293
960061AF2-297 GEN
Solar/Wind Harmer
21.853
970099AG2-077 GEN
Solar/Wind Harmer
49.882
970401AG2-262 GEN
Solar/Wind Harmer
2.517
970909AG2-566 GEN
Solar/Wind Harmer
9.256
964241AG1-285 GEN
Solar/Wind Harmer
20.591
970413AG2-270 GEN
50/50
67.43
971683AH1-343 GEN
Solar/Wind Harmer
16.168
970865AG2-541 GEN
Solar/Wind Harmer
8.87
3147043LAWRENC
50/50
1.438
3147173SINAI
Solar/Wind Harmer
1.366
3147243WELCO
Solar/Wind Harmer
0.854
970165AG2-112 GEN
Solar/Wind Harmer
2.698
270455AD2-022 GEN
Solar/Wind Helper
2.745
3146843MT LREL
Solar/Wind Harmer
1.146
3146843MT LREL
Solar/Wind Harmer
1.146
959311AF2-222 GEN
Solar/Wind Harmer
8.672
970163AG2-111 GEN
Solar/Wind Harmer
2.574
970535AG2-341 GEN
50/50
12.889
964791AG1-342 GEN
Solar/Wind Harmer
8.237
971443AH1-215 GEN
Solar/Wind Harmer
4.432
270457AD2-023 GEN
Solar/Wind Helper
1.544
962491AG1-098 GEN
Solar/Wind Harmer
24.516
971443AH1-215 GEN
Solar/Wind Harmer
4.285
315693AD1-088 GEN
Solar/Wind Harmer
18.549
971741AH1-377 GEN
Solar/Wind Harmer
35.543
3144303KENBRDG
Solar/Wind Harmer
0.641
970257AG2-171 GEN
Solar/Wind Harmer
9.616
972205AH1-687 GEN
50/50
5.236
970301AG2-198 GEN
Solar/Wind Harmer
14.316
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
12.821
957481AF2-042 GEN
Solar/Wind Harmer
124.704
971775AH1-396 GEN
Solar/Wind Harmer
1.923
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.469
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.36
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
1.294
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.898
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.634
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.836
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.492
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.8
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CONTINGENCY 'AEP_P4_#10294_05NEWLDN 138_D_SRT-A'
 OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1   /*05BRUSHT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1   /*05FOREST     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242741 CKT 1   /*05JOHNMT     138.0 - 05OTTER      138.0
 OPEN BRANCH FROM BUS 242741 TO BUS 314667 CKT 1   /*05OTTER      138.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'AEP_P4_#10293_05NEWLDN 138_C_SRT-A'
 OPEN BRANCH FROM BUS 242561 TO BUS 242641 CKT 1   /*05BOONSBORO  138.0 - 05FOREST     138.0
 OPEN BRANCH FROM BUS 242561 TO BUS 242765 CKT 1   /*05BOONSBORO  138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1   /*05BRUSHT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1   /*05FOREST     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
END
CONTINGENCY 'AEP_P4_#10292_05NEWLDN 138_E_SRT-A'
 OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1   /*05BRUSHT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1   /*05FOREST     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
END
CONTINGENCY 'AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1   /*05BRUSHT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1   /*05FOREST     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
END
CONTINGENCY 'DVP_P4-2: 151T1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 313825 TO BUS 314696 CKT 1   /*3PLYWOOD     115.0 - 3SEDGE HILL  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
END
CONTINGENCY 'DVP_P4-2: 104702_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 314520                                   /*3SEDGE_1     115.0
END
CONTINGENCY 'DVP_P1-2: LN 13_SRT-A'
 OPEN BRANCH FROM BUS 242741 TO BUS 314667 CKT 1   /*05OTTER      138.0 - 4ALTVSTA     138.0
 OPEN BUS 242687                                   /*05JOHNMT     138.0
 OPEN BUS 242741                                   /*05OTTER      138.0
END
CONTINGENCY 'AEP_P1-2_#375_5201_SRT-A'
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242741 CKT 1   /*05JOHNMT     138.0 - 05OTTER      138.0
 OPEN BRANCH FROM BUS 242741 TO BUS 314667 CKT 1   /*05OTTER      138.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'DVP_P1-3: 4ALTVSTA-TX#4_SRT-A'
 OPEN BRANCH FROM BUS 314666 TO BUS 314667 CKT 2   /*3ALTVSTA     115.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'DVP_P1-3: 4ALTVSTA-TX#3_SRT-A'
 OPEN BRANCH FROM BUS 314666 TO BUS 314667 CKT 1   /*3ALTVSTA     115.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-1'
 OPEN BRANCH FROM BUS 304183 TO BUS 970084 CKT 1   /*8WAKE 500 TT 500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P4-5: 593X1_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-5: 593X2_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-2: H1T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 1   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H2T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 2   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
242701 to 242802 ckt 1
314666 to 314667 ckt 1
314666 to 314667 ckt 2
316281 to 304070 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability Analysis is Not Required.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA1-145Four Rivers 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-132Thelma 230kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB1-180Pine View 12kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-086Thelma 230kVSuspended
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-214Crescent RidgeIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-100Halifax-Person 230kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-157Sullivan 345 kVUnder Construction
AC2-165Bremo-Powhatan 230kVSuspended
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-136South Bethel-Brown 69 kVIn Service
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-081Landing 12.47 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-153Remington-Gordonsville 230 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-172Loretto-Wilton CenterActive
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-019New Road 230 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-035Lena 138 kVIn Service
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-042Milton 69 kVIn Service
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-140Axton-Danville 138 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-183Rogers Road 500 kVIn Service
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-253Hickory-Moyock 230 kVIn Service
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-308Three Forks-Dale 138 kVActive
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-030Sandwich-Plano 138 kVActive
AF1-032Suffolk 34.5 kVIn Service
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-075Harrisburg-Endless Caverns 230 kVSuspended
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-162Inez 138 kVEngineering & Procurement
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-035St. Johns 115 kVActive
AF2-041Nelson-Electric Junction 345 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-111North Clark-Spurlock 345 kVActive
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-173Desoto 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-311Gilboa-Jones Branch 138 kVEngineering & Procurement
AF2-316Gilboa-Jones Branch 138 kV IIEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-382Hurley 69 kVEngineering & Procurement
AF2-383Tolna 115 kVWithdrawn
AF2-392Nelson-Dixon 138 kVActive
AF2-404Gladys DP-Stonemill 69 kVActive
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-127Crego Rd 138 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-153Heritage 500 kVActive
AG1-154Ladysmith CT 230 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-221Poland Rd-Runway DP 230 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-320Glendale-Stephensburg 69 kVActive
AG1-341Summer Shade 161 kVActive
AG1-342Dryburg 115 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-354Summershade-Green County 161 kVActive
AG1-367DeSoto 345 kVActive
AG1-374Blue Mound 345 kVActive
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-397Walston 12 kVWithdrawn
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-494Boxwood-Riverville 138 kVActive
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-526West Garrard 345 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-010Peninsula-Whealton 115 kVActive
AG2-049Van Dorn 34.5 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-086Mt. Jackson DP-Mt. Jackson 115 kVActive
AG2-088Midlothian 230 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-126Eugene 345 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-272Berry Hill 138 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-304Liberty 230 kVActive
AG2-310Matt Funk 138 kVActive
AG2-311Smith Mountain 138 kVActive
AG2-320Ladysmith 230 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-338Rogers Road - Carson 500 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-384Chesterfield 230 kVActive
AG2-401Losantville 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-012Louisa - North Anna 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-056Red House DP 115kVActive
AH1-065Hopewell 34.5kVActive
AH1-066Hopewell 34.5kVActive
AH1-071Midlothian 34.5 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-086Morrisville 230kVActive
AH1-087Morrisville 230kVActive
AH1-088Morrisville 230kVActive
AH1-089Morrisville 230kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-138Penniman 34.5 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-157Penniman - Waller 230 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-170Columbia DP 115kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Prairie 345 kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-221Heritage 500 kVActive
AH1-223Poland Rd-Runway DP 230 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-269Claytor 138 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-314East Danville 138 kVActive
AH1-323Elmont 230 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-345Remington 324 34.5 kVActive
AH1-348Pound 34.5 kVActive
AH1-377Clover- Farmville 230kVActive
AH1-387Meadowbrook-Greenland Gap 500kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-644Spicewood Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-676Gordonsville 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-684Remington CT 230 kVActive
AH1-685Remington CT 230 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-687Bear Garden 230kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-693Remington CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-696Possum Point 230kVActive
AH1-702Byron 345 kVActive
AH1-712Cunningham 500 kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
AH1-723Cunningham 500 kVActive
AH1-729Ocean Court 230 kVActive
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-068Murphy's 34.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
X3-066Church Hill 69kVIn Service
Y1-049Wurno 34.5kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0001
Title
Person - VP Hendrick 230kV Line (Existing Line Uprate)
Description
Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 48 Months

Info

Note: AG2-112 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0002
Title
Person - VP Hendrick 230kV line (New Line)
Description
This project is to add second line that would be built to 1195MVA. Assumed ~5 mile 230kV line with bundled conductor and can utilize last remaining CB bay at Person (no fence expansion). Estimated ISD Assumed 5 years from Kick off to complete work (Site & acquire ROW, engineering, construction) and assuming no other outage constraints (DEP or PJM) from previous projects already planned. The new line will also be bundled 795 ACSS/TW.
Total Cost ($USD)
$28,300,000
Allocated Cost ($USD)
$0
Time Estimate
0 to 60 Months

Info

Note: AG2-112 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Study Pending
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-112 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
AEP(Pending) / AEP-TC2-1870405SMITHMTN 138.0 kV to 05LEESVI 138.0 kV ckt 1 - Rebuild$1,793,537
Dominionn9132.0 / dom-122Add 3rd 138/115 kV transformer at Altavista substation$1,554,135
Dominion(Pending) / TC1-PH1-DOM-096Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C$541,145
Dominion(Pending) / TC2-PH1-DOM-2001Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$513,936
Dominionn7687 / dom-046-TC2Add a 3rd 230/115 kV transformer at Sedge Hill Substation and associated breakers (230 kV and 115 kV).$420,554
Dominion(Pending) / dom-184Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C$187,468
AEP(Pending) / AEPAPRJV004Replace wavetrap @ New London$19,267
Dominion(Pending) / TC2-PH1-DOM-2043Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.$15,830
Dominionn8423 / dom-119Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$11,593
Grand Total:$5,057,465

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18704
Title
05SMITHMTN 138.0 kV to 05LEESVI 138.0 kV ckt 1 - Rebuild
Description
Rebuild ~8.2 miles of 138 kV line between Smith Mountain and Leesville, upgrade 795 AAC station conductor at Smith Mountain and Leesville.
Total Cost ($USD)
$32,000,000
Allocated Cost ($USD)
$1,793,537
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
3.8 MW5.3%$1,710,840
AG2-112
4.0 MW5.6%$1,793,537
AG2-152
29.8 MW41.4%$13,245,672
AG2-311
13.9 MW19.3%$6,172,896
AG2-541
13.6 MW18.9%$6,049,740
AH1-343
6.8 MW9.5%$3,027,315

System Reinforcement: n9132.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9132.0 / dom-122
Title
Add 3rd 138/115 kV transformer at Altavista substation
Description
Add 3rd 138/115 kV transformer at Altavista substation
Total Cost ($USD)
$11,000,000
Allocated Cost ($USD)
$1,554,135
Time Estimate
42 to 44 Months

Contributor

FacilityContingency
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer(Any)
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.7 MW13.5%$1,482,894
AG2-112
6.0 MW14.1%$1,554,135
AG2-311
14.6 MW34.3%$3,776,023
AH1-343
16.2 MW38.1%$4,186,949

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH1-DOM-096
Title
Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Description
Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Total Cost ($USD)
$8,960,000
Allocated Cost ($USD)
$541,145
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.0 MW5.8%$516,143
AG2-112
5.3 MW6.0%$541,145
AG2-152
13.0 MW14.9%$1,335,495
AG2-311
6.1 MW6.9%$622,404
AG2-541
27.0 MW30.9%$2,768,644
AH1-343
31.0 MW35.4%$3,176,168

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2001
Title
Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$8,512,000
Allocated Cost ($USD)
$513,936
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3CRSTL HILL-AH1-343 TP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.0 MW5.8%$490,200
AG2-112
5.3 MW6.0%$513,936
AG2-152
13.1 MW14.9%$1,270,297
AG2-311
6.1 MW7.0%$592,053
AG2-541
27.0 MW30.9%$2,629,314
AH1-343
31.0 MW35.4%$3,016,201

System Reinforcement: n7687
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7687 / dom-046-TC2
Title
Add a 3rd 230/115 kV transformer at Sedge Hill Substation and associated breakers (230 kV and 115 kV).
Description
Add a 3rd 230/115 kV transformer at Sedge Hill Substation and associated breakers (230 kV and 115 kV).
Total Cost ($USD)
$10,595,849
Allocated Cost ($USD)
$420,554
Time Estimate
Jun 01 2029

Contributor

FacilityContingency
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer(Any)
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
8.0 MW3.8%$401,172
AG2-112
8.4 MW4.0%$420,554
AG2-171
11.7 MW5.6%$588,191
AG2-213
13.8 MW6.5%$693,355
AG2-440
14.6 MW6.9%$732,873
AG2-441
18.2 MW8.6%$916,066
AG2-442
20.4 MW9.7%$1,026,062
AG2-541
42.9 MW20.4%$2,157,893
AH1-056
12.4 MW5.9%$623,682
AH1-343
49.2 MW23.4%$2,478,216
AH1-408
11.1 MW5.3%$557,785

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / dom-184
Title
Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Description
Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Total Cost ($USD)
$3,104,000
Allocated Cost ($USD)
$187,468
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3HUBER DP-AC1-222 TAP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.0 MW5.8%$178,807
AG2-112
5.3 MW6.0%$187,468
AG2-152
13.0 MW14.9%$462,654
AG2-311
6.1 MW6.9%$215,619
AG2-541
27.0 MW30.9%$959,137
AH1-343
31.0 MW35.4%$1,100,315

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEPAPRJV004
Title
Replace wavetrap @ New London
Description
Replace wavetrap @ New London
Total Cost ($USD)
$260,000
Allocated Cost ($USD)
$19,267
Time Estimate
18 to 24 Months

Contributor

FacilityContingency
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
4.7 MW7.1%$18,378
AG2-112
4.9 MW7.4%$19,267
AG2-152
6.6 MW10.0%$25,960
AG2-311
6.8 MW10.2%$26,550
AG2-541
20.9 MW31.7%$82,388
AH1-343
22.2 MW33.6%$87,457

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2043
Title
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Description
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Total Cost ($USD)
$3,534,000
Allocated Cost ($USD)
$15,830
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
9.2 MW1.1%$39,652
AG2-069
13.8 MW1.7%$59,477
AG2-077
67.9 MW8.3%$292,796
AG2-111
3.5 MW0.4%$15,101
AG2-112
3.7 MW0.4%$15,830
AG2-151
7.2 MW0.9%$31,260
AG2-152
14.7 MW1.8%$63,434
AG2-171
13.1 MW1.6%$56,405
AG2-188
21.4 MW2.6%$92,359
AG2-198
19.5 MW2.4%$83,993
AG2-213
17.4 MW2.1%$75,209
AG2-270
47.1 MW5.8%$203,423
AG2-272
5.3 MW0.7%$23,062
AG2-341
6.5 MW0.8%$27,834
AG2-369
7.9 MW1.0%$34,099
AG2-440
21.4 MW2.6%$92,165
AG2-441
26.7 MW3.3%$115,205
AG2-442
29.9 MW3.7%$129,034
AG2-522
10.0 MW1.2%$43,134
AG2-541
19.1 MW2.3%$82,250
AG2-566
9.3 MW1.1%$39,936
AG2-570
35.7 MW4.4%$154,059
AG2-571
15.5 MW1.9%$67,037
AG2-581
50.2 MW6.1%$216,526
AG2-583
7.5 MW0.9%$32,494
AG2-659
11.3 MW1.4%$48,915
AH1-056
20.7 MW2.5%$89,249
AH1-215
8.7 MW1.1%$37,455
AH1-241
6.9 MW0.8%$29,676
AH1-314
15.6 MW1.9%$67,343
AH1-343
22.0 MW2.7%$94,896
AH1-377
48.3 MW5.9%$208,557
AH1-408
10.5 MW1.3%$45,498
AH1-439
12.3 MW1.5%$53,152
AH1-528
100.6 MW12.3%$434,213
AH1-535
6.0 MW0.7%$25,767
AH1-546
7.3 MW0.9%$31,579
AH1-687
5.2 MW0.6%$22,479
AH1-690
28.7 MW3.5%$123,688
AH1-721
31.5 MW3.8%$135,756

System Reinforcement: n8423
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8423 / dom-119
Title
Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$192,000
Allocated Cost ($USD)
$11,593
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.0 MW5.8%$11,057
AG2-112
5.3 MW6.0%$11,593
AG2-152
13.1 MW14.9%$28,653
AG2-311
6.1 MW7.0%$13,355
AG2-541
27.0 MW30.9%$59,308
AH1-343
31.0 MW35.4%$68,035

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18717
Title
05BANSTR 138.0 kV to 05EDAN 2 138.0 kV ckt 1 - Sag Study and Replace Equipment
Description
Replace first overhead conductor span from East Danville to Structure 18-135 (1033 ACSR); Conduct sag clearance study on 10.7 miles between Structure 18-135 and Banister; Replace 1590 AAC station conductor at Banister; Replace 2000 AAC station conductor at East Danville
Total Cost ($USD)
$1,700,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 may need this upgrade in-service to be deliverable to the PJM system. If AG2-112 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18709
Title
AG2-152 TP 138.0 kV to 05BANSTR 138.0 kV ckt 1 - Sag Study and Upgrade Equipment
Description
Upgrade 1590 AAC station conductor at Banister. Perform sag clearance study for ~0.5 mile of 138 kV line between AG2-152 and Banister to determine any potential mitigation required to operate at a higher temperature.
Total Cost ($USD)
$50,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.211
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.211
Title
Rebuild 6.5 miles of Johnson Mountain - New London 138 kV line
Description
Rebuild 6.5 miles of Johnson Mountain - New London 138 kV line Projected In Service Date: 06/01/2029
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 may need this upgrade in-service to be deliverable to the PJM system. If AG2-112 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.210
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.210
Title
Rebuild 7 miles of Otter - Johnson Mountain 138 kV line.
Description
Rebuild 7 miles of Otter - Johnson Mountain 138 kV line.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 may need this upgrade in-service to be deliverable to the PJM system. If AG2-112 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOHNMT-05OTTER 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
Most limiting rating on the Dominion side is the Wave Trap and Lead at Altavista: 363 / 382 /420 MVA.
Description
Most limiting rating on the Dominion side is the Wave Trap and Lead at Altavista: 363 / 382 /420 MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
99 Months

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
05OTTER-4ALTVSTA 138.0 kV Ckt 1 line(Any)

System Reinforcement: n5613
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n5613 / AEPA0014a
Title
Rebuild 0.9 miles of the Otter - Alta Vista 138 kV line.
Description
Rebuild 0.9 miles of the Otter - Alta Vista 138 kV line.
Total Cost ($USD)
$2,740,849
Allocated Cost ($USD)
$0
Time Estimate
Nov 21 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-112 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-112 may not have cost responsibility for this upgrade, AG2-112 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-112 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05OTTER-4ALTVSTA 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0044
Title
Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$17,100,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-0012
Title
Wreck and rebuild 8.1 miles of 230 kV Line 2027 (future Line 2323) between Bremo and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 8.1 miles of 230 kV Line 2027 (future Line 2323) between Bremo and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$30,780,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2076
Title
Replace wave trap 298 WT at Bremo 230 kV
Description
Replace wave trap 298 WT at Bremo 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2078
Title
Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
Description
Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2079
Title
Replace 3 1/2 " AL Pipe line lead on line 298 at Bremo 230 kV
Description
Replace 3 1/2 " AL Pipe line lead on line 298 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2077
Title
Replace switches 29824 and 29825 at Bremo 230 kV
Description
Replace switches 29824 and 29825 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2065
Title
Replace switches 219324 and 219325 at Bremo 230 kV
Description
Replace switches 219324 and 219325 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2066
Title
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Description
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2067
Title
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Description
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1031
Title
Wreck and rebuild 12.94 miles of 230 kV Line 235 from Briery to Farmville with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Description
Wreck and rebuild 12.94 miles of 230 kV Line 235 from Briery to Farmville with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Total Cost ($USD)
$49,172,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9376.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9376.0 / TC1-PH3-DOM-003-TC2
Title
Wreck and Rebuild 22.98 miles of 230 kV Line 235 from Briery to AG1-098 with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" at 250 C.
Description
Wreck and Rebuild 22.98 miles of 230 kV Line 235 from Briery to AG1-098 with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" at 250 C.
Total Cost ($USD)
$69,323,785
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line(Any)
AG2-198 TP-AH1-377 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line(Any)
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9221.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9221.0 / TC1-PH3-DOM-015-TC2
Title
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Description
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Total Cost ($USD)
$2,057,335
Allocated Cost ($USD)
$0
Time Estimate
38 to 39 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6BUCKING-AH1-439 TP 230.0 kV Ckt 1 line(Any)
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1572 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1572 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9200.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9200.0 / TC1-PH2-DOM-005
Title
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" conductors.
Description
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$38,691,326
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9201.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9201.0 / TC1-PH2-DOM-006
Title
Replace wave trap at Carson 230 kV (Carson - Sapony).
Description
Replace wave trap at Carson 230 kV (Carson - Sapony).
Total Cost ($USD)
$521,941
Allocated Cost ($USD)
$0
Time Estimate
14 to 15 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)

System Reinforcement: n8256
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8256 / dom-277
Title
Wreck and rebuild 5.9 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AC2-165 (Sallee Creek) with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 5.9 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AC2-165 (Sallee Creek) with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$22,420,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0013
Title
Wreck and rebuild 1.51 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 1.51 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$5,738,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2072
Title
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Description
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n7568
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7568 / dom-369-TC2
Title
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Description
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Total Cost ($USD)
$36,802,018
Allocated Cost ($USD)
$0
Time Estimate
43 to 44 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2073
Title
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH3-DOM-007
Title
Replace Wave Trap 2028WT at Charlottesville
Description
Replace Wave Trap 2028WT at Charlottesville
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n6872
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6872 / dom-047
Title
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C.
Description
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C
Total Cost ($USD)
$59,572,939
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6OTTERDAM-6CLUBHSE 230.0 kV Ckt 1 line(Any)
6ENCLAVE-6OTTERDAM 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9204.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9204.0 / TC1-PH2-DOM-014
Title
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C
Total Cost ($USD)
$6,764,273
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2086
Title
Replace 3 1/2' AL Pipe line lead on line 298 at Farmville 230 kV
Description
Replace 3 1/2' AL Pipe line lead on line 298 at Farmville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2087
Title
Replace 2-1590 AAC 61 line lead on line 298 at Farmville 230 kV
Description
Replace 2-1590 AAC 61 line lead on line 298 at Farmville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2085
Title
Replace wavetrap 298WT at Farmville 230 kV
Description
Replace wavetrap 298WT at Farmville 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1032
Title
Wreck and rebuild 0.73 miles of 230 kV line 235 between AG1-098 and Finneywood with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Description
Wreck and rebuild 0.73 miles of 230 kV line 235 between AG1-098 and Finneywood with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Total Cost ($USD)
$2,774,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9199.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9199.0 / TC1-PH2-DOM-004
Title
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Description
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Total Cost ($USD)
$7,947,612
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2064
Title
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Description
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2063
Title
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$418,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9198.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9198.0 / TC1-PH2-DOM-003-TC2
Title
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Description
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Total Cost ($USD)
$2,113,879
Allocated Cost ($USD)
$0
Time Estimate
40 to 41 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0080
Title
Replace switch 219326 at Bremo 230 kV
Description
Replace switch 219326 at Bremo 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9203.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9203.0 / TC1-PH2-DOM-008-TC2
Title
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Description
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Total Cost ($USD)
$29,539,973
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2070
Title
Replace wave trap 2028WT at Fork Union 230 kV
Description
Replace wave trap 2028WT at Fork Union 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2069
Title
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Description
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2068
Title
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$456,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9644.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9644.0 / TC1-PH3-DOM-006-TC2
Title
Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.
Description
Rebuild a 2.73 mile segment of 230kV line 2028 between Mt. Eagle and Grape Vinew with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @250 degrees C.
Total Cost ($USD)
$8,415,380
Allocated Cost ($USD)
$0
Time Estimate
Mar 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n7569
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7569 / dom-490-TC2
Title
Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.
Description
Uograde 3.78 miles of transmission line 2028 between Mt. Eagle and Grape Vine with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"". The segment runs from Mt Eagle to structure 2080/73.
Total Cost ($USD)
$13,360,242
Allocated Cost ($USD)
$0
Time Estimate
43 to 44 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2071
Title
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
DVP Rating: 961/961/1106 MVA
Description
DVP Rating: 961/961/1106 MVA
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
Dominion work to accomodate new Person - Hendrick 230 kV tie line
Description
Add a breaker to existing three-breaker ring bus at Hendrick and construct 0.93 miles of new 230 kV line between Pesrons - Hendrick
Total Cost ($USD)
$8,894,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n8243
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8243 / dom-389
Title
Wreck and rebuild 5.8 miles of 230 kV Line 2027 between AC2-165 (Sallee Creek) and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 5.8 miles of 230 kV Line 2027 between AC2-165 (Sallee Creek) and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$22,040,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0045
Title
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$31,540,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)

System Reinforcement: n6215
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6215
Title
Wreck and rebuild 18.56 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 18.56 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$70,528,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0051
Title
Wreck and rebuild 0.003 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 0.003 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$11,400
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.343
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.343
Title
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Description
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Cost Information
Time Estimate
Nov 28 2025

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1037
Title
Replace Breaker 56372 at Carson 500 kV with 5000 Amp device
Description
Replace Breaker 56372 at Carson 500 kV with 5000 Amp device
Total Cost ($USD)
$2,750,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1036
Title
Wreck and rebuild 37.41 mi of 500 kV line 563 between Carson and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C
Description
Wreck and rebuild 37.41 mi of 500 kV line 563 between Carson and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C
Total Cost ($USD)
$157,122,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9249.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9249.0 / TC1-PH2-DOM-043
Title
Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line.
Description
Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line. New Rating = 4356/4356/5009 MVA
Total Cost ($USD)
$231,012,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S

System Reinforcement: b3692
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3692
Title
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.
Description
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy with current 500 kV standards construction practices to achieve a summer rating of 4330 MVA. Projected ISD: 06/01/2026
Cost Information
Time Estimate
Jun 01 2026

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH1-DOM-079
Title
Replace Wave Trap 567 WT at Surry 500 kV
Description
Replace Wave Trap 567 WT at Surry 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9264.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9264.0 / TC1-PH1-DOM-080
Title
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Description
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Total Cost ($USD)
$582,006
Allocated Cost ($USD)
$0
Time Estimate
12 to 13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9248.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9248.0 / TC1-PH2-DOM-042
Title
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Description
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Total Cost ($USD)
$345,766,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 557T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 557_SRT-S

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2091
Title
Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated device
Description
Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated device
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8FINNEYWOOD-6FINNEYWOOD 500.0/230.0 kV Ckt 1 transformer(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2092
Title
Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated device
Description
Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated device
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8FINNEYWOOD-6FINNEYWOOD 500.0/230.0 kV Ckt 2 transformer(Any)

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S

System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0075
Title
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Description
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Total Cost ($USD)
$110,625,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P2-2: MORRISVILLE B1_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 545T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H1T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H3T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 550_SRT-A

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0076
Title
Replace Wave Trap 594WT at Morrisville 500 KV
Description
Replace Wave Trap 594WT at Morrisville 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0077
Title
Replace Wave Trap 594WT at Spotsylvania 500 KV
Description
Replace Wave Trap 594WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0078
Title
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Description
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0072
Title
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Description
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0073
Title
Replace Wave Trap 573WT at Spotsylvania 500 KV
Description
Replace Wave Trap 573WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0071
Title
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Description
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Total Cost ($USD)
$82,718,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2008
Title
Wreck and rebuild 0.47 miles of 230 kV Line 2241 between Hendrick and Alton Post with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 0.47 miles of 230 kV Line 2241 between Hendrick and Alton Post with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$1,786,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2097
Title
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Description
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Total Cost ($USD)
$33,230,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
DICKH230-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P1-2_PE-500-406T_SRT-A

System Reinforcement: b3800.242
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.242
Title
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Description
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Cost Information
Time Estimate
Sep 13 2030

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
(Pending) / (Pending)
Title
Additional Aspen to Dickerson H 230 kV line
Description
PEPCO’s substation cost to accommodate an additional circuit at Dickerson H to be approximately $7.86 million. The cost for the remaining 7.25 miles of 230 kV transmission line is estimated at $78.62 million.
Total Cost ($USD)
$86,480,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-112 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-112 could receive cost allocation. Although AG2-112 may not presently have cost responsibility for this upgrade, AG2-112 is a potential Aggregate Pool Contributor.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.244
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.244
Title
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Description
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-112 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-112 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
          Perth 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-111, AG2-112
        
          AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-440, AG2-441, AG2-442
        
          AG2-068 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-068, AG2-069, AG2-369
        
          AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-198, AG2-566
        
          AG2-570 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-570, AG2-571
        

Attachments

AG2-112 One Line Diagram

AG2-112 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.