AG2-125 Phase I Study Report

v1.00 released 2025-10-29 22:11

Camden-Crystal 69 kV

15.44 MW Capacity / 0.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Alamo Solar I, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is The Dayton Power and Light Company.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the The Dayton Power and Light Company zone — Preble County, Ohio. This project is an increase to the developer’s AC2-067/AC2-068 project(s), which will share the same Point of Interconnection. The AG2-125 project is a 15.44 MW Capacity only uprate to the previous project(s). The total installed facilities will have a capability of 69.9 MW with 41.94 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-125
Project Name:
Camden-Crystal 69 kV
Project Developer Name:
Alamo Solar I, LLC
State:
Ohio
County:
Preble
Transmission Owner:
The Dayton Power and Light Company
MFO:
69.9
MWE:
0.0
MWC:
15.44
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-125 will interconnect on the The Dayton Power and Light Company transmission system tapping the Camden - Crystal 69 kV line .

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-125 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-125Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$0$0

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-125

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-125 Project due at DP1
ABA - B
AG2-125$0$61,760$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

No TO Interconnection Facilities or Physical Network Upgrades are required for this project.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dayton interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-125 was evaluated as a 0.0 MW (15.44 MW Capacity) injection in the Dayton area.

AG2-125 was evaluated as part of a plant. The plant consists of AG2-125. The total Energy output of the plant was evaluated at its maximum seasonal capability of 69.9 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC120.65 %3792.0B4574.961.75
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC120.64 %3792.0B4574.631.75
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC139.36 %3792.0B5284.611.7
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC139.32 %3792.0B5282.911.7
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC130.62 %3729.0B4870.981.95
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.1 %3729.0B4627.61.88
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.92 %3792.0B5002.281.95
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.38 %3792.0B4754.331.88
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.76 %4142.0B4919.182.27
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC115.67 %5523.0B6388.322.43
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC108.86 %4558.0A4961.851.65
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.56 %5523.0B5885.341.99
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC145.41 %1540.0B2239.271.39
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#309_15_SRT-A
SingleAC141.78 %1540.0B2183.341.47
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
Base Case
SingleAC131.72 %1189.0A1566.091.36
GD2AEP/OVEC
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC101.36 %1540.0B1561.021.09
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P1-2_#762_8072_SRT-A
SingleAC102.19 %1203.0B1229.312.18

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.96
MW Contribution:1.75
Bus #Bus NameTypeMW Contribution
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.928
25194408D.CRK1
Adder
7.324
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
926881AC1-175 GEN
Solar/Wind Harmer
0.001
960971AF2-388 GEN
Solar/Wind Harmer
3.871
24721705FLATG2
Adder
24.202
970155AG2-107 GEN
Solar/Wind Harmer
19.471
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24686105CER G3
Adder
8.419
253343AC1-166 GEN
Solar/Wind Harmer
0.003
24723205RIVRG3
Adder
18.885
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
960071AF2-298 GEN
Solar/Wind Harmer
3.39
25194608D.CRK4
Adder
1.592
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970291AG2-192 GEN
Solar/Wind Harmer
0.853
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
24639705ELKHART HY
Adder
0.142
270449AD2-020 GEN
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.006
23751101LEADS_P59
Solar/Wind Helper
1.597
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
237030AB1-096 C
Solar/Wind Helper
0.061
962771AG1-126 GEN
Solar/Wind Harmer
30.492
970689AG2-444 GEN
Solar/Wind Harmer
14.59
972203AH1-686 GEN
Adder
2.352
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
25306009OHH W.
Adder
2.812
252524AE2-267 GEN
Solar/Wind Harmer
0.002
270302AB2-170 GEN
Solar/Wind Harmer
0.004
971653AH1-327 GEN
Solar/Wind Harmer
0.947
270024AE2-089 GEN
Solar/Wind Harmer
0.007
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
1.959
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
971655AH1-328 GEN
Solar/Wind Harmer
2.415
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
276820AF1-078_GEN
Solar/Wind Harmer
0.002
247621Y3-024
Adder
0.228
971613AH1-306 GEN
Solar/Wind Harmer
3.153
965681AG1-436 GEN
Solar/Wind Harmer
8.059
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
971125AH1-004 GEN
Solar/Wind Harmer
2.546
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
238120AE2-309 GEN
Solar/Wind Helper
0.483
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
23559001PLEAS1
50/50
11.891
23562401OGROV2
50/50
2.277
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
25196608WSDLE5
Adder
8.301
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
958821AF2-173 GEN
Solar/Wind Harmer
9.221
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
274752CRETE EC ;2U
Adder
7.553
970193AG2-126 GEN
Solar/Wind Harmer
9.564
972228AH1-698 GEN2
Adder
3.385
23559101PLEAS2
50/50
11.891
23562301OGROV1
50/50
2.291
970149AG2-104 GEN
Solar/Wind Harmer
32.932
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.575
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970091AG2-072 GEN
Adder
72.107
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
970373AG2-245 GEN
Solar/Wind Harmer
13.568
963741AG1-226 GEN
Solar/Wind Harmer
15.2
943021AE2-325 GEN
Solar/Wind Harmer
3.342
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
23562501BACKB
Solar/Wind Helper
1.042
235054AD2-180 GEN
Solar/Wind Helper
1.935
23684201S70BUS2
50/50
0.305
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
252510AF1-249 C
Solar/Wind Harmer
0.052
270485AE1-090_GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
972167AH1-666 GEN
Solar/Wind Harmer
5.306
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
270043AE2-236 GEN
Solar/Wind Harmer
4.199
965021AG1-366 GEN
Solar/Wind Harmer
2.178
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
961821AG1-024 GEN
Solar/Wind Harmer
4.271
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
253400AC2-068 GEN
Solar/Wind Harmer
0.859
25196508WSDLE4
Adder
8.216
972163AH1-664 GEN
Solar/Wind Harmer
7.37
965101AG1-375 GEN
Solar/Wind Harmer
6.597
970115AG2-085 GEN
Solar/Wind Harmer
2.631
971609AH1-304 GEN
Solar/Wind Harmer
1.074
24699105WLD G1 C
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
6.496
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
274776LINCOLN ;7U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.739
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
23546401DTGZ2-030
Solar/Wind Helper
0.077
3138216PACIFIC
Solar/Wind Helper
0.038
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
270186AC1-089 GEN
Solar/Wind Harmer
0.004
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.293
942221AE2-234 GEN
Solar/Wind Harmer
0.033
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
972259AH1-714 GEN
Adder
17.426
970107AG2-081 GEN
Solar/Wind Harmer
1.909
960161AF2-307 GEN
Solar/Wind Harmer
4.195
238175AF1-290_GEN
Solar/Wind Helper
0.13
235020AA1-095 C
Solar/Wind Helper
0.045
962691AG1-118 GEN
Solar/Wind Harmer
7.548
971073AG2-665 GEN
Solar/Wind Harmer
6.448
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
25326109MON D
Adder
1.288
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194508D.CRK3
Adder
1.369
24728805RICHG1
Adder
3.587
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.442
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270031AE2-169
Solar/Wind Harmer
3.616
945421AF1-207 GEN
Solar/Wind Harmer
0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
965791AG1-447 GEN
Solar/Wind Harmer
5.91
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.206
958011AF2-095 GEN
Solar/Wind Harmer
9.182
241960AC2-195 GEN
Solar/Wind Harmer
0.005
944971AF1-162 GEN
Solar/Wind Harmer
6.345
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
235063AE1-101 C2
Solar/Wind Helper
1.433
237001AB1-127_GEN
Solar/Wind Helper
0.381
23684101S70BUS1
50/50
0.299
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
25196808ZIMRHP
Adder
73.247
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
965011AG1-365 GEN
Solar/Wind Harmer
6.533
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
274801UNIV PARK;4U
Adder
5.327
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751201ROTHROCK
Solar/Wind Helper
0.849
23583801GRNGAP
Solar/Wind Helper
4.948
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
237034AC2-136 C
Solar/Wind Helper
0.194
24318805MLG1
50/50
6.637
972173AH1-669 GEN
Solar/Wind Harmer
3.569
24686405CER G5
Adder
8.342
253338AC1-165 GEN
Solar/Wind Harmer
0.003
970191AG2-125 GEN
Solar/Wind Harmer
1.745
270222AC2-111 GEN
Solar/Wind Harmer
3.385
270004AE1-209 GEN
Solar/Wind Harmer
1.427
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
959331AF2-224 GEN
Solar/Wind Harmer
4.573
270191TR4_S_V150
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274826FISK ;BP
Adder
10.003
962761AG1-125 GEN
Solar/Wind Harmer
30.492
24686505CER G6
Adder
8.408
25326309TAIT D
Adder
1.071
252507AC2-088 GEN
Solar/Wind Harmer
0.308
270462AD2-086
Solar/Wind Harmer
0.014
247536S-71 GEN
Solar/Wind Harmer
0.266
970245AG2-165 GEN
Solar/Wind Harmer
2.844
276903AD2-071 C
Solar/Wind Harmer
7.32
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
274754CRETE EC ;4U
Adder
7.553
274732ELWOOD EC;7P
Adder
8.75
939401AE1-172 GEN
Solar/Wind Harmer
4.75
944231AF1-091 GEN
Solar/Wind Harmer
1.688
238117U2-030
Solar/Wind Helper
0.318
238147AE2-230_GEN1
Solar/Wind Helper
0.427
235067AD1-061 GEN
Solar/Wind Helper
0.427
270459AD2-067 GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
6.448
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270367AC2-061_GEN
Solar/Wind Harmer
0.005
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
270435AC2-044 GEN
Solar/Wind Harmer
0.821
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
274728ELWOOD EC;5P
Adder
14.987
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.764
237085AD2-009_GEN
Solar/Wind Helper
1.425
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
8.918
971985AH1-537 GEN
Solar/Wind Harmer
2.087
253349AC2-067 GEN
Solar/Wind Harmer
2.136
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972165AH1-665 GEN
Solar/Wind Harmer
5.903
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
971611AH1-305 GEN
Solar/Wind Harmer
3.852
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
276868AE1-113 GEN
Solar/Wind Harmer
1.267
238208AF1-136 C
Solar/Wind Helper
0.19
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.817
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238127S14_GEN_2
Solar/Wind Helper
0.764
235062AE1-101 C1
Solar/Wind Helper
1.433
24642205MAYFLWER
Adder
0.585
274753CRETE EC ;3U
Adder
7.553
270258AD1-119 GEN
Solar/Wind Harmer
0.002
972038AH1-567 GEN2
Adder
0.333
270053AF1-130 C
Solar/Wind Harmer
1.432
238118U2-030_1
Solar/Wind Helper
0.318
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237038AE2-054 C
Solar/Wind Helper
0.235
23779801AA1-109
Solar/Wind Helper
0.166
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
241955AC1-078 GEN
Solar/Wind Harmer
0.006
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
25194608D.CRK4
Adder
1.592
946031AF1-268 GEN
Solar/Wind Harmer
6.268
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.565
24755605MDL-5G
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
3.613
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
237080AD1-060 GEN
Solar/Wind Helper
0.294
270599AE1-208 GEN
Solar/Wind Harmer
6.026
970627AG2-408 GEN
Solar/Wind Harmer
1.96
966841AG1-555 GEN
Solar/Wind Harmer
0.73
270216AD2-079_GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.674
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274803UNIV PARK;6U
Adder
5.329
274887GEN-1.85
Solar/Wind Harmer
0.168
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
23777901MDS_W4-102
Solar/Wind Helper
0.151
237002AB1-128_GEN
Solar/Wind Helper
0.382
237006AB1-125 GEN
Solar/Wind Helper
0.106
274724RIVER EC ;11
Adder
16.226
274802UNIV PARK;5U
Adder
5.329
970941AG2-585 GEN
Solar/Wind Harmer
7.971
276897AD1-100 C
Solar/Wind Harmer
0.008
274800UNIV PARK;3U
Adder
5.327
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.17
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
970289AG2-191 GEN
Solar/Wind Harmer
1.247
963791AG1-232 GEN
Solar/Wind Harmer
8.837
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
274811UNIV PK N;7U
Adder
4.584
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274735ELWOOD EC;4P
Adder
14.987
970169AG2-114 GEN
Solar/Wind Harmer
6.327
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
957141AF2-008_MTX
Adder
53.261
944201AF1-088_MTX
Adder
106.522
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LGEELTFEXP_LGEE->PJM
CLTF
6.272
MECLTFEXP_MEC->PJM
CLTF
14.465
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
WECLTFEXP_WEC->PJM
CLTF
3.434
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
NYPJM->LTFIMP_NY
CLTF
4.491
TVALTFEXP_TVA->PJM
CLTF
7.036
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
CPLELTFEXP_CPLE->PJM
CLTF
1.288
SIGELTFEXP_SIGE->PJM
CLTF
0.467

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.63
MW Contribution:1.75
Bus #Bus NameTypeMW Contribution
24721705FLATG2
Adder
24.202
970155AG2-107 GEN
Solar/Wind Harmer
19.471
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24686105CER G3
Adder
8.419
253343AC1-166 GEN
Solar/Wind Harmer
0.003
24723205RIVRG3
Adder
18.885
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
960071AF2-298 GEN
Solar/Wind Harmer
3.39
25194608D.CRK4
Adder
1.592
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970291AG2-192 GEN
Solar/Wind Harmer
0.853
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
24639705ELKHART HY
Adder
0.142
270449AD2-020 GEN
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
961821AG1-024 GEN
Solar/Wind Harmer
4.271
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
270186AC1-089 GEN
Solar/Wind Harmer
0.004
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.293
942221AE2-234 GEN
Solar/Wind Harmer
0.033
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
972259AH1-714 GEN
Adder
17.426
970107AG2-081 GEN
Solar/Wind Harmer
1.909
960161AF2-307 GEN
Solar/Wind Harmer
4.195
238175AF1-290_GEN
Solar/Wind Helper
0.13
235020AA1-095 C
Solar/Wind Helper
0.045
962691AG1-118 GEN
Solar/Wind Harmer
7.548
23684101S70BUS1
50/50
0.299
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
25196808ZIMRHP
Adder
73.247
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
965011AG1-365 GEN
Solar/Wind Harmer
6.533
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
971073AG2-665 GEN
Solar/Wind Harmer
6.448
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
25326109MON D
Adder
1.288
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194508D.CRK3
Adder
1.369
24728805RICHG1
Adder
3.587
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.442
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270031AE2-169
Solar/Wind Harmer
3.616
945421AF1-207 GEN
Solar/Wind Harmer
0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
965791AG1-447 GEN
Solar/Wind Harmer
5.91
962761AG1-125 GEN
Solar/Wind Harmer
30.492
24686505CER G6
Adder
8.408
25326309TAIT D
Adder
1.071
252507AC2-088 GEN
Solar/Wind Harmer
0.308
270462AD2-086
Solar/Wind Harmer
0.014
247536S-71 GEN
Solar/Wind Harmer
0.266
970245AG2-165 GEN
Solar/Wind Harmer
2.844
276903AD2-071 C
Solar/Wind Harmer
7.32
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
274754CRETE EC ;4U
Adder
7.553
274732ELWOOD EC;7P
Adder
8.75
939401AE1-172 GEN
Solar/Wind Harmer
4.75
944231AF1-091 GEN
Solar/Wind Harmer
1.688
238117U2-030
Solar/Wind Helper
0.318
238147AE2-230_GEN1
Solar/Wind Helper
0.427
235067AD1-061 GEN
Solar/Wind Helper
0.427
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
274801UNIV PARK;4U
Adder
5.327
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751201ROTHROCK
Solar/Wind Helper
0.849
23583801GRNGAP
Solar/Wind Helper
4.948
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
270459AD2-067 GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
6.448
940611AE2-048 GEN
Solar/Wind Harmer
17.483
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
8.918
971985AH1-537 GEN
Solar/Wind Harmer
2.087
253349AC2-067 GEN
Solar/Wind Harmer
2.136
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972165AH1-665 GEN
Solar/Wind Harmer
5.903
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
971611AH1-305 GEN
Solar/Wind Harmer
3.852
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
276868AE1-113 GEN
Solar/Wind Harmer
1.267
238208AF1-136 C
Solar/Wind Helper
0.19
23559001PLEAS1
50/50
11.891
23562401OGROV2
50/50
2.277
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
25196608WSDLE5
Adder
8.301
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
958821AF2-173 GEN
Solar/Wind Harmer
9.221
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
274752CRETE EC ;2U
Adder
7.553
970193AG2-126 GEN
Solar/Wind Harmer
9.564
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.817
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238127S14_GEN_2
Solar/Wind Helper
0.764
235062AE1-101 C1
Solar/Wind Helper
1.433
24318805MLG1
50/50
6.637
972173AH1-669 GEN
Solar/Wind Harmer
3.569
24686405CER G5
Adder
8.342
253338AC1-165 GEN
Solar/Wind Harmer
0.003
970191AG2-125 GEN
Solar/Wind Harmer
1.745
270222AC2-111 GEN
Solar/Wind Harmer
3.385
270004AE1-209 GEN
Solar/Wind Harmer
1.427
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
959331AF2-224 GEN
Solar/Wind Harmer
4.573
270191TR4_S_V150
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24642205MAYFLWER
Adder
0.585
274753CRETE EC ;3U
Adder
7.553
270258AD1-119 GEN
Solar/Wind Harmer
0.002
972038AH1-567 GEN2
Adder
0.333
270053AF1-130 C
Solar/Wind Harmer
1.432
238118U2-030_1
Solar/Wind Helper
0.318
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237038AE2-054 C
Solar/Wind Helper
0.235
23779801AA1-109
Solar/Wind Helper
0.166
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
253400AC2-068 GEN
Solar/Wind Harmer
0.859
25196508WSDLE4
Adder
8.216
972163AH1-664 GEN
Solar/Wind Harmer
7.37
965101AG1-375 GEN
Solar/Wind Harmer
6.597
970115AG2-085 GEN
Solar/Wind Harmer
2.631
971609AH1-304 GEN
Solar/Wind Harmer
1.074
24699105WLD G1 C
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
6.496
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
274776LINCOLN ;7U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.739
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
23546401DTGZ2-030
Solar/Wind Helper
0.077
3138216PACIFIC
Solar/Wind Helper
0.038
276901AD2-066 C O1
Solar/Wind Harmer
0.006
23751101LEADS_P59
Solar/Wind Helper
1.597
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
237030AB1-096 C
Solar/Wind Helper
0.061
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
241955AC1-078 GEN
Solar/Wind Harmer
0.006
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
25194608D.CRK4
Adder
1.592
946031AF1-268 GEN
Solar/Wind Harmer
6.268
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.565
24755605MDL-5G
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
3.613
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
237080AD1-060 GEN
Solar/Wind Helper
0.294
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
1.959
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
971655AH1-328 GEN
Solar/Wind Harmer
2.415
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
276820AF1-078_GEN
Solar/Wind Harmer
0.002
247621Y3-024
Adder
0.228
971613AH1-306 GEN
Solar/Wind Harmer
3.153
965681AG1-436 GEN
Solar/Wind Harmer
8.059
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
971125AH1-004 GEN
Solar/Wind Harmer
2.546
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
238120AE2-309 GEN
Solar/Wind Helper
0.483
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.928
25194408D.CRK1
Adder
7.324
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
926881AC1-175 GEN
Solar/Wind Harmer
0.001
960971AF2-388 GEN
Solar/Wind Harmer
3.871
270599AE1-208 GEN
Solar/Wind Harmer
6.026
970627AG2-408 GEN
Solar/Wind Harmer
1.96
966841AG1-555 GEN
Solar/Wind Harmer
0.73
270216AD2-079_GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.674
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274803UNIV PARK;6U
Adder
5.329
274887GEN-1.85
Solar/Wind Harmer
0.168
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
23777901MDS_W4-102
Solar/Wind Helper
0.151
237002AB1-128_GEN
Solar/Wind Helper
0.382
237006AB1-125 GEN
Solar/Wind Helper
0.106
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.206
958011AF2-095 GEN
Solar/Wind Harmer
9.182
241960AC2-195 GEN
Solar/Wind Harmer
0.005
944971AF1-162 GEN
Solar/Wind Harmer
6.345
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
235063AE1-101 C2
Solar/Wind Helper
1.433
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270367AC2-061_GEN
Solar/Wind Harmer
0.005
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
270435AC2-044 GEN
Solar/Wind Harmer
0.821
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
274728ELWOOD EC;5P
Adder
14.987
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.764
237085AD2-009_GEN
Solar/Wind Helper
1.425
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
23684201S70BUS2
50/50
0.305
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
252510AF1-249 C
Solar/Wind Harmer
0.052
270485AE1-090_GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
972167AH1-666 GEN
Solar/Wind Harmer
5.306
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
270043AE2-236 GEN
Solar/Wind Harmer
4.199
965021AG1-366 GEN
Solar/Wind Harmer
2.178
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274724RIVER EC ;11
Adder
16.226
274802UNIV PARK;5U
Adder
5.329
970941AG2-585 GEN
Solar/Wind Harmer
7.971
276897AD1-100 C
Solar/Wind Harmer
0.008
274800UNIV PARK;3U
Adder
5.327
23559101PLEAS2
50/50
11.891
23562301OGROV1
50/50
2.291
970149AG2-104 GEN
Solar/Wind Harmer
32.932
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.575
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970091AG2-072 GEN
Adder
72.107
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
970373AG2-245 GEN
Solar/Wind Harmer
13.568
963741AG1-226 GEN
Solar/Wind Harmer
15.2
943021AE2-325 GEN
Solar/Wind Harmer
3.342
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
23562501BACKB
Solar/Wind Helper
1.042
235054AD2-180 GEN
Solar/Wind Helper
1.935
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
962771AG1-126 GEN
Solar/Wind Harmer
30.492
970689AG2-444 GEN
Solar/Wind Harmer
14.59
972203AH1-686 GEN
Adder
2.352
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
25306009OHH W.
Adder
2.812
252524AE2-267 GEN
Solar/Wind Harmer
0.002
270302AB2-170 GEN
Solar/Wind Harmer
0.004
971653AH1-327 GEN
Solar/Wind Harmer
0.947
270024AE2-089 GEN
Solar/Wind Harmer
0.007
970289AG2-191 GEN
Solar/Wind Harmer
1.247
963791AG1-232 GEN
Solar/Wind Harmer
8.837
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
274811UNIV PK N;7U
Adder
4.584
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274735ELWOOD EC;4P
Adder
14.987
970169AG2-114 GEN
Solar/Wind Harmer
6.327
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.17
957141AF2-008_MTX
Adder
53.261
944201AF1-088_MTX
Adder
106.522
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
CPLELTFEXP_CPLE->PJM
CLTF
1.288
SIGELTFEXP_SIGE->PJM
CLTF
0.467
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
NYPJM->LTFIMP_NY
CLTF
4.491
TVALTFEXP_TVA->PJM
CLTF
7.036
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
WECLTFEXP_WEC->PJM
CLTF
3.434
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LGEELTFEXP_LGEE->PJM
CLTF
6.272
MECLTFEXP_MEC->PJM
CLTF
14.465
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.36 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5284.61
MW Contribution:1.7
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270367AC2-061_GEN
Solar/Wind Harmer
0.005
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
971673AH1-337 GEN
Solar/Wind Harmer
4.191
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
24691005MDL-2G C
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.796
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
961821AG1-024 GEN
Solar/Wind Harmer
4.145
270432AC2-029 GEN
Solar/Wind Harmer
3.085
270269AC2-059
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253400AC2-068 GEN
Solar/Wind Harmer
0.835
25196508WSDLE4
Adder
8
972163AH1-664 GEN
Solar/Wind Harmer
7.187
965101AG1-375 GEN
Solar/Wind Harmer
6.406
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
24699105WLD G1 C
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
274776LINCOLN ;7U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
270400AC1-102 GEN
Solar/Wind Harmer
1.957
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
23559101PLEAS2
50/50
11.213
23562301OGROV1
50/50
2.427
970149AG2-104 GEN
Solar/Wind Harmer
31.855
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.698
270159DARBY CT4
Adder
8.691
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.131
970091AG2-072 GEN
Adder
70.193
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
970373AG2-245 GEN
Solar/Wind Harmer
13.169
963741AG1-226 GEN
Solar/Wind Harmer
14.772
943021AE2-325 GEN
Solar/Wind Harmer
3.241
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
238108AE1-109 GEN1
Solar/Wind Helper
0.088
235531U2-073 GEN
Solar/Wind Helper
2.523
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270158DARBY CT3
Adder
8.67
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253349AC2-067 GEN
Solar/Wind Harmer
2.077
270317AD1-130_GEN
Solar/Wind Harmer
0.009
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971029AG2-637 GEN
Solar/Wind Harmer
9.664
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
276868AE1-113 GEN
Solar/Wind Harmer
1.231
238208AF1-136 C
Solar/Wind Helper
0.18
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
25194408D.CRK1
Adder
7.132
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
926881AC1-175 GEN
Solar/Wind Harmer
0.001
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270599AE1-208 GEN
Solar/Wind Harmer
5.854
970627AG2-408 GEN
Solar/Wind Harmer
1.9
972043AH1-570 GEN
Solar/Wind Harmer
1.633
966841AG1-555 GEN
Solar/Wind Harmer
0.709
270216AD2-079_GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274887GEN-1.85
Solar/Wind Harmer
0.163
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
274879MINONK ;1U
Solar/Wind Harmer
0.259
23777901MDS_W4-102
Solar/Wind Helper
0.146
237002AB1-128_GEN
Solar/Wind Helper
0.369
962771AG1-126 GEN
Solar/Wind Harmer
29.494
972203AH1-686 GEN
Adder
2.298
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
252524AE2-267 GEN
Solar/Wind Harmer
0.002
270302AB2-170 GEN
Solar/Wind Harmer
0.004
971653AH1-327 GEN
Solar/Wind Harmer
0.917
270024AE2-089 GEN
Solar/Wind Harmer
0.007
970289AG2-191 GEN
Solar/Wind Harmer
1.211
963791AG1-232 GEN
Solar/Wind Harmer
8.573
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
274811UNIV PK N;7U
Adder
0.697
970179AG2-119 GEN
Solar/Wind Harmer
5.506
970169AG2-114 GEN
Solar/Wind Harmer
6.145
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
24721705FLATG2
Adder
23.442
970155AG2-107 GEN
Solar/Wind Harmer
18.834
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24686105CER G3
Adder
8.253
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
960071AF2-298 GEN
Solar/Wind Harmer
3.297
25194608D.CRK4
Adder
1.55
945681AF1-233 GEN
Solar/Wind Harmer
12.186
970613AG2-401 GEN
Solar/Wind Harmer
4.707
965651AG1-433 GEN
Solar/Wind Harmer
1.879
971995AH1-542 GEN
Solar/Wind Harmer
2.347
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970291AG2-192 GEN
Solar/Wind Harmer
0.829
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
965421AG1-410 GEN
Solar/Wind Harmer
18.858
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
24639705ELKHART HY
Adder
0.137
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
270449AD2-020 GEN
Solar/Wind Harmer
0
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
23684101S70BUS1
50/50
0.313
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
25196808ZIMRHP
Adder
71.347
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.387
970825AG2-519 GEN
Solar/Wind Harmer
2.27
270032AE2-172
Solar/Wind Harmer
4.254
965011AG1-365 GEN
Solar/Wind Harmer
6.333
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.228
972269AH1-719 GEN
Adder
2.268
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
253378AE2-206_GEN
Solar/Wind Harmer
0.003
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.086
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
970623AG2-406 GEN
Solar/Wind Harmer
1.132
238175AF1-290_GEN
Solar/Wind Helper
0.126
235020AA1-095 C
Solar/Wind Helper
0.044
962691AG1-118 GEN
Solar/Wind Harmer
3.447
23684201S70BUS2
50/50
0.319
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
252510AF1-249 C
Solar/Wind Harmer
0.051
270485AE1-090_GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
972167AH1-666 GEN
Solar/Wind Harmer
5.174
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270043AE2-236 GEN
Solar/Wind Harmer
4.072
965021AG1-366 GEN
Solar/Wind Harmer
2.111
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274724RIVER EC ;11
Adder
15.751
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276776AD2-060 GEN
Solar/Wind Harmer
0.646
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.006
316095T157 G97
Solar/Wind Helper
1.299
238185AF2-356 C
Solar/Wind Helper
1.996
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.34
276820AF1-078_GEN
Solar/Wind Harmer
0.002
247621Y3-024
Adder
0.222
971613AH1-306 GEN
Solar/Wind Harmer
3.063
965681AG1-436 GEN
Solar/Wind Harmer
7.82
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
971125AH1-004 GEN
Solar/Wind Harmer
2.483
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
238120AE2-309 GEN
Solar/Wind Helper
0.406
23777801MSM_W1-116
Solar/Wind Helper
0.096
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
241955AC1-078 GEN
Solar/Wind Harmer
0.006
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25194608D.CRK4
Adder
1.55
946031AF1-268 GEN
Solar/Wind Harmer
6.09
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.466
24755605MDL-5G
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
3.508
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
237080AD1-060 GEN
Solar/Wind Helper
0.284
23559001PLEAS1
50/50
11.213
23562401OGROV2
50/50
2.411
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
24686205CER G4
Adder
8.21
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253333AC1-068 GEN
Solar/Wind Harmer
0.011
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
25196608WSDLE5
Adder
8.083
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
958821AF2-173 GEN
Solar/Wind Harmer
8.959
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
970031AG2-029 GEN
Solar/Wind Harmer
4.079
274752CRETE EC ;2U
Adder
7.332
970193AG2-126 GEN
Solar/Wind Harmer
9.3
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
23750701CROSSCHOOL
Solar/Wind Helper
1.155
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
962761AG1-125 GEN
Solar/Wind Harmer
29.494
24686505CER G6
Adder
8.242
25326309TAIT D
Adder
1.041
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270462AD2-086
Solar/Wind Harmer
0.014
247536S-71 GEN
Solar/Wind Harmer
0.258
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
339216AC1-074 GEN
Solar/Wind Harmer
0.172
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
7.332
939401AE1-172 GEN
Solar/Wind Harmer
4.613
944231AF1-091 GEN
Solar/Wind Harmer
1.635
238147AE2-230_GEN1
Solar/Wind Helper
0.415
235067AD1-061 GEN
Solar/Wind Helper
0.412
238117U2-030
Solar/Wind Helper
0.26
971073AG2-665 GEN
Solar/Wind Harmer
6.304
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
972159AH1-661 GEN
Adder
0.952
25326109MON D
Adder
1.252
25183208HLCRTG
Solar/Wind Harmer
0.01
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25194508D.CRK3
Adder
1.333
970329AG2-216 GEN
Solar/Wind Harmer
2.833
24728805RICHG1
Adder
3.489
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.429
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270031AE2-169
Solar/Wind Harmer
3.512
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
972045AH1-571 GEN
Solar/Wind Harmer
1.308
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965791AG1-447 GEN
Solar/Wind Harmer
5.734
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
241960AC2-195 GEN
Solar/Wind Harmer
0.005
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
237034AC2-136 C
Solar/Wind Helper
0.189
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
24318805MLG1
50/50
6.319
972173AH1-669 GEN
Solar/Wind Harmer
3.478
24686405CER G5
Adder
8.177
253338AC1-165 GEN
Solar/Wind Harmer
0.003
970191AG2-125 GEN
Solar/Wind Harmer
1.697
270222AC2-111 GEN
Solar/Wind Harmer
3.293
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
959331AF2-224 GEN
Solar/Wind Harmer
4.433
270191TR4_S_V150
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
1.414
24642205MAYFLWER
Adder
0.568
274753CRETE EC ;3U
Adder
7.332
270258AD1-119 GEN
Solar/Wind Harmer
0.002
238148AE2-230_GEN2
Solar/Wind Helper
0.417
237038AE2-054 C
Solar/Wind Helper
0.226
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
957141AF2-008_MTX
Adder
51.82
944201AF1-088_MTX
Adder
103.64
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
CPLELTFEXP_CPLE->PJM
CLTF
1.286
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
NYPJM->LTFIMP_NY
CLTF
4.417
TVALTFEXP_TVA->PJM
CLTF
6.876
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
WECLTFEXP_WEC->PJM
CLTF
3.336
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LGEELTFEXP_LGEE->PJM
CLTF
6.111
MECLTFEXP_MEC->PJM
CLTF
14.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.32 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5282.91
MW Contribution:1.7
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270367AC2-061_GEN
Solar/Wind Harmer
0.005
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
971673AH1-337 GEN
Solar/Wind Harmer
4.191
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
24691005MDL-2G C
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.796
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
961821AG1-024 GEN
Solar/Wind Harmer
4.145
270432AC2-029 GEN
Solar/Wind Harmer
3.085
270269AC2-059
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253400AC2-068 GEN
Solar/Wind Harmer
0.835
25196508WSDLE4
Adder
8
972163AH1-664 GEN
Solar/Wind Harmer
7.187
965101AG1-375 GEN
Solar/Wind Harmer
6.406
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
24699105WLD G1 C
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
274776LINCOLN ;7U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
270400AC1-102 GEN
Solar/Wind Harmer
1.957
276882AE2-255 GEN
Solar/Wind Harmer
0.717
23559101PLEAS2
50/50
11.213
23562301OGROV1
50/50
2.427
970149AG2-104 GEN
Solar/Wind Harmer
31.855
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.698
270159DARBY CT4
Adder
8.691
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.131
970091AG2-072 GEN
Adder
70.193
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270158DARBY CT3
Adder
8.67
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253349AC2-067 GEN
Solar/Wind Harmer
2.077
270317AD1-130_GEN
Solar/Wind Harmer
0.009
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971029AG2-637 GEN
Solar/Wind Harmer
9.664
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
276868AE1-113 GEN
Solar/Wind Harmer
1.231
238208AF1-136 C
Solar/Wind Helper
0.18
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
962771AG1-126 GEN
Solar/Wind Harmer
29.494
972203AH1-686 GEN
Adder
2.298
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
252524AE2-267 GEN
Solar/Wind Harmer
0.002
270302AB2-170 GEN
Solar/Wind Harmer
0.004
971653AH1-327 GEN
Solar/Wind Harmer
0.917
270024AE2-089 GEN
Solar/Wind Harmer
0.007
970289AG2-191 GEN
Solar/Wind Harmer
1.211
963791AG1-232 GEN
Solar/Wind Harmer
8.573
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
274811UNIV PK N;7U
Adder
0.697
970179AG2-119 GEN
Solar/Wind Harmer
5.506
970169AG2-114 GEN
Solar/Wind Harmer
6.145
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
25194408D.CRK1
Adder
7.132
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
926881AC1-175 GEN
Solar/Wind Harmer
0.001
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270599AE1-208 GEN
Solar/Wind Harmer
5.854
970627AG2-408 GEN
Solar/Wind Harmer
1.9
972043AH1-570 GEN
Solar/Wind Harmer
1.633
966841AG1-555 GEN
Solar/Wind Harmer
0.709
270216AD2-079_GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274887GEN-1.85
Solar/Wind Harmer
0.163
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
274879MINONK ;1U
Solar/Wind Harmer
0.259
23777901MDS_W4-102
Solar/Wind Helper
0.146
237002AB1-128_GEN
Solar/Wind Helper
0.369
23684101S70BUS1
50/50
0.313
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
25196808ZIMRHP
Adder
71.347
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.387
970825AG2-519 GEN
Solar/Wind Harmer
2.27
270032AE2-172
Solar/Wind Harmer
4.254
965011AG1-365 GEN
Solar/Wind Harmer
6.333
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.228
972269AH1-719 GEN
Adder
2.268
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
253378AE2-206_GEN
Solar/Wind Harmer
0.003
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.086
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
970623AG2-406 GEN
Solar/Wind Harmer
1.132
238175AF1-290_GEN
Solar/Wind Helper
0.126
235020AA1-095 C
Solar/Wind Helper
0.044
962691AG1-118 GEN
Solar/Wind Harmer
3.447
23684201S70BUS2
50/50
0.319
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
252510AF1-249 C
Solar/Wind Harmer
0.051
270485AE1-090_GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
972167AH1-666 GEN
Solar/Wind Harmer
5.174
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270043AE2-236 GEN
Solar/Wind Harmer
4.072
965021AG1-366 GEN
Solar/Wind Harmer
2.111
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274724RIVER EC ;11
Adder
15.751
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.002
970373AG2-245 GEN
Solar/Wind Harmer
13.169
963741AG1-226 GEN
Solar/Wind Harmer
14.772
943021AE2-325 GEN
Solar/Wind Harmer
3.241
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
238108AE1-109 GEN1
Solar/Wind Helper
0.088
235531U2-073 GEN
Solar/Wind Helper
2.523
24721705FLATG2
Adder
23.442
970155AG2-107 GEN
Solar/Wind Harmer
18.834
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24686105CER G3
Adder
8.253
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
960071AF2-298 GEN
Solar/Wind Harmer
3.297
25194608D.CRK4
Adder
1.55
945681AF1-233 GEN
Solar/Wind Harmer
12.186
970613AG2-401 GEN
Solar/Wind Harmer
4.707
965651AG1-433 GEN
Solar/Wind Harmer
1.879
971995AH1-542 GEN
Solar/Wind Harmer
2.347
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970291AG2-192 GEN
Solar/Wind Harmer
0.829
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
965421AG1-410 GEN
Solar/Wind Harmer
18.858
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
24639705ELKHART HY
Adder
0.137
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
270449AD2-020 GEN
Solar/Wind Harmer
0
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.006
316095T157 G97
Solar/Wind Helper
1.299
238185AF2-356 C
Solar/Wind Helper
1.996
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.34
276820AF1-078_GEN
Solar/Wind Harmer
0.002
247621Y3-024
Adder
0.222
971613AH1-306 GEN
Solar/Wind Harmer
3.063
965681AG1-436 GEN
Solar/Wind Harmer
7.82
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
971125AH1-004 GEN
Solar/Wind Harmer
2.483
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
238120AE2-309 GEN
Solar/Wind Helper
0.406
23777801MSM_W1-116
Solar/Wind Helper
0.096
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
241955AC1-078 GEN
Solar/Wind Harmer
0.006
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25194608D.CRK4
Adder
1.55
946031AF1-268 GEN
Solar/Wind Harmer
6.09
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.466
24755605MDL-5G
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
3.508
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
237080AD1-060 GEN
Solar/Wind Helper
0.284
23559001PLEAS1
50/50
11.213
23562401OGROV2
50/50
2.411
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
24686205CER G4
Adder
8.21
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253333AC1-068 GEN
Solar/Wind Harmer
0.011
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
25196608WSDLE5
Adder
8.083
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
958821AF2-173 GEN
Solar/Wind Harmer
8.959
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
970031AG2-029 GEN
Solar/Wind Harmer
4.079
274752CRETE EC ;2U
Adder
7.332
970193AG2-126 GEN
Solar/Wind Harmer
9.3
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
23750701CROSSCHOOL
Solar/Wind Helper
1.155
235062AE1-101 C1
Solar/Wind Helper
1.38
962761AG1-125 GEN
Solar/Wind Harmer
29.494
24686505CER G6
Adder
8.242
25326309TAIT D
Adder
1.041
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270462AD2-086
Solar/Wind Harmer
0.014
247536S-71 GEN
Solar/Wind Harmer
0.258
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
339216AC1-074 GEN
Solar/Wind Harmer
0.172
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
7.332
939401AE1-172 GEN
Solar/Wind Harmer
4.613
944231AF1-091 GEN
Solar/Wind Harmer
1.635
238147AE2-230_GEN1
Solar/Wind Helper
0.415
235067AD1-061 GEN
Solar/Wind Helper
0.412
238117U2-030
Solar/Wind Helper
0.26
238127S14_GEN_2
Solar/Wind Helper
0.641
971073AG2-665 GEN
Solar/Wind Harmer
6.304
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
972159AH1-661 GEN
Adder
0.952
25326109MON D
Adder
1.252
25183208HLCRTG
Solar/Wind Harmer
0.01
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25194508D.CRK3
Adder
1.333
970329AG2-216 GEN
Solar/Wind Harmer
2.833
24728805RICHG1
Adder
3.489
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.429
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270031AE2-169
Solar/Wind Harmer
3.512
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
972045AH1-571 GEN
Solar/Wind Harmer
1.308
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965791AG1-447 GEN
Solar/Wind Harmer
5.734
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24318805MLG1
50/50
6.319
972173AH1-669 GEN
Solar/Wind Harmer
3.478
24686405CER G5
Adder
8.177
253338AC1-165 GEN
Solar/Wind Harmer
0.003
970191AG2-125 GEN
Solar/Wind Harmer
1.697
270222AC2-111 GEN
Solar/Wind Harmer
3.293
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
959331AF2-224 GEN
Solar/Wind Harmer
4.433
270191TR4_S_V150
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
1.414
24642205MAYFLWER
Adder
0.568
274753CRETE EC ;3U
Adder
7.332
270258AD1-119 GEN
Solar/Wind Harmer
0.002
238148AE2-230_GEN2
Solar/Wind Helper
0.417
237038AE2-054 C
Solar/Wind Helper
0.226
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
24441505OLIV SLR
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
241960AC2-195 GEN
Solar/Wind Harmer
0.005
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
237034AC2-136 C
Solar/Wind Helper
0.189
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
957141AF2-008_MTX
Adder
51.82
944201AF1-088_MTX
Adder
103.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LGEELTFEXP_LGEE->PJM
CLTF
6.111
MECLTFEXP_MEC->PJM
CLTF
14.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
WECLTFEXP_WEC->PJM
CLTF
3.336
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
NYPJM->LTFIMP_NY
CLTF
4.417
TVALTFEXP_TVA->PJM
CLTF
6.876
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
CPLELTFEXP_CPLE->PJM
CLTF
1.286
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.62 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4870.98
MW Contribution:1.95
Bus #Bus NameTypeMW Contribution
962761AG1-125 GEN
Solar/Wind Harmer
34.524
270462AD2-086
Solar/Wind Harmer
0.017
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
247536S-71 GEN
Solar/Wind Harmer
0.297
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
944231AF1-091 GEN
Solar/Wind Harmer
1.953
276903AD2-071 C
Solar/Wind Harmer
8.137
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.477
24385905FR-11G C
Solar/Wind Harmer
0.002
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
939401AE1-172 GEN
Solar/Wind Harmer
5.301
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
235067AD1-061 GEN
Solar/Wind Helper
0.496
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
219276PARKLANDSO C
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.028
23559001PLEAS1
50/50
6.1
961921AG1-034 GEN
Solar/Wind Harmer
7.615
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270273AD2-016 GEN
Solar/Wind Harmer
0.821
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.563
270377AD1-106 GEN
Solar/Wind Harmer
2.855
270247TR4_N_V136
Solar/Wind Harmer
0.048
944531AF1-118 GEN
Solar/Wind Harmer
33.395
25196608WSDLE5
Adder
9.077
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270437AC2-090 C
Solar/Wind Harmer
0.003
247604X1-042
Adder
0.433
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
24728705AND G3
Adder
8.214
274826FISK ;BP
Adder
11.205
972228AH1-698 GEN2
Adder
3.79
270119AB2-067 GEN1
50/50
7.059
970077AG2-063 GEN
Solar/Wind Harmer
4.631
972269AH1-719 GEN
Adder
2.584
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.451
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
970611AG2-400 GEN
Solar/Wind Harmer
7.488
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
970621AG2-405 GEN
Solar/Wind Harmer
1.351
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
274808UNIV PK N;4U
Adder
5.117
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
972259AH1-714 GEN
Adder
19.507
970241AG2-163 GEN
Solar/Wind Harmer
4.144
274696ROCKY RD ;4P
Adder
11.537
274697ROCKY RD ;3P
Adder
3.062
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
233946AB2-136 GEN
Solar/Wind Helper
0.568
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20716928W4-060COL
Solar/Wind Helper
0.051
20673828FLE_V3-070
Solar/Wind Helper
0.09
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.168
20676228FRD_X1-012
Solar/Wind Helper
0.092
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
970879AG2-548 GEN
Solar/Wind Harmer
6.898
270435AC2-044 GEN
Solar/Wind Harmer
0.953
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.804
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
8.194
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971769AH1-391 GEN
Solar/Wind Harmer
8.134
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
16.768
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.827
237085AD2-009_GEN
Solar/Wind Helper
1.649
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
209116AE2-175 GEN
Solar/Wind Helper
1.778
24318805MLG1
50/50
10.095
270475AD2-096_GEN
50/50
7.141
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.952
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.242
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
270222AC2-111 GEN
Solar/Wind Harmer
3.739
270004AE1-209 GEN
Solar/Wind Harmer
1.59
24642205MAYFLWER
Adder
0.665
270356AE2-297 GEN
Solar/Wind Harmer
0.01
972239AH1-704 GEN
Adder
2.689
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
270340AC2-060 GEN
Solar/Wind Harmer
0.009
253400AC2-068 GEN
Solar/Wind Harmer
0.958
965041AG1-368 GEN
Solar/Wind Harmer
7.471
965101AG1-375 GEN
Solar/Wind Harmer
7.401
25196508WSDLE4
Adder
8.984
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274746AC1-111 G10
Adder
5.679
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238152AF2-075_GEN
Solar/Wind Helper
0.707
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.638
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.029
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274730ELWOOD EC;6P
Adder
16.768
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238127S14_GEN_2
Solar/Wind Helper
0.827
235062AE1-101 C1
Solar/Wind Helper
1.659
223401AF1-299 GEN
Solar/Wind Helper
0.367
233915AB1-141 GEN
Solar/Wind Helper
0.502
232428Y3-058 C
Solar/Wind Helper
0.338
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.059
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.571
270120AB2-067 GEN2
50/50
7.059
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
971201AH1-060 GEN
Solar/Wind Harmer
1.52
970627AG2-408 GEN
Solar/Wind Harmer
2.246
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970883AG2-550 GEN
Solar/Wind Harmer
7.389
25194408D.CRK1
Adder
8.004
270599AE1-208 GEN
Solar/Wind Harmer
6.737
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
24728905RICHG2
Adder
3.964
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274803UNIV PARK;6U
Adder
5.97
274887GEN-1.85
Solar/Wind Harmer
0.188
274674JOLIET 9 ;6U
Adder
15.704
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
274693ROCKY RD ;1P
Adder
11.16
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.116
233970AC1-092 C
Solar/Wind Helper
0.35
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.098
966111AG1-480 GEN
Solar/Wind Helper
0.074
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
10.218
270317AD1-130_GEN
Solar/Wind Harmer
0.011
253349AC2-067 GEN
Solar/Wind Harmer
2.381
965051AG1-369 GEN
Solar/Wind Harmer
3.739
971985AH1-537 GEN
Solar/Wind Harmer
2.206
971029AG2-637 GEN
Solar/Wind Harmer
11.085
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
11.025
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
3.285
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386405FR-21G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
972165AH1-665 GEN
Solar/Wind Harmer
6.354
270166AC1-044 GEN3
50/50
7.059
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965011AG1-365 GEN
Solar/Wind Harmer
7.488
958861AF2-177 GEN
Solar/Wind Harmer
3.207
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.59
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.877
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
253343AC1-166 GEN
Solar/Wind Harmer
0.003
971995AH1-542 GEN
Solar/Wind Harmer
2.906
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
965421AG1-410 GEN
Solar/Wind Harmer
22.57
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
25194608D.CRK4
Adder
1.74
970947AG2-589 GEN
Solar/Wind Harmer
0.245
965031AG1-367 GEN
Solar/Wind Harmer
7.338
970613AG2-401 GEN
Solar/Wind Harmer
5.378
24639705ELKHART HY
Adder
0.161
970291AG2-192 GEN
Solar/Wind Harmer
0.95
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274676JOLIET 29;8U
Adder
31.303
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.679
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
238185AF2-356 C
Solar/Wind Helper
2.646
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.346
233996TM1833_GEN
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
942861AE2-305 GEN
Solar/Wind Harmer
6.335
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972159AH1-661 GEN
Adder
1.118
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
971231AH1-075 GEN
Solar/Wind Harmer
0.861
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.496
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
270031AE2-169
Solar/Wind Harmer
4.042
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
24728805RICHG1
Adder
3.964
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274695ROCKY RD ;2P
Adder
11.271
958491AF2-143 GEN
Solar/Wind Harmer
10.588
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.342
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.232
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
23559101PLEAS2
50/50
6.1
970149AG2-104 GEN
Solar/Wind Harmer
37.287
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
927014AC1-188 GEN
Solar/Wind Harmer
0.005
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.805
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
24791305MDL-5G
Solar/Wind Harmer
0.001
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
23562501BACKB
Solar/Wind Helper
1.007
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233994AC2-023 GEN
Solar/Wind Helper
0.961
233997TMININ_4.2
Solar/Wind Helper
0.261
233971AC1-093 C
Solar/Wind Helper
0.357
228729W2-030 C
Solar/Wind Helper
0.11
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
20674628WNG_W3-110
Solar/Wind Helper
0.089
962771AG1-126 GEN
Solar/Wind Harmer
34.524
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270302AB2-170 GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
1.117
970179AG2-119 GEN
Solar/Wind Harmer
6.883
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
957201AF2-014 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
270024AE2-089 GEN
Solar/Wind Harmer
0.008
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
1.389
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
5.139
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
274735ELWOOD EC;4P
Adder
16.768
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.357
960921AF2-383 GEN
Solar/Wind Helper
0.364
205932AD2-116_GEN
Solar/Wind Helper
0.509
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
203975AE1-071-GEN
Solar/Wind Helper
2.498
966261AG1-495 GEN
Solar/Wind Helper
0.081
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.854
276820AF1-078_GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
253370AE2-315 SEC1
Adder
2.182
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
971613AH1-306 GEN
Solar/Wind Harmer
3.512
965681AG1-436 GEN
Solar/Wind Harmer
9.095
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
238120AE2-309 GEN
Solar/Wind Helper
0.525
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230407AD2-065 C
Solar/Wind Helper
0.04
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
970153AG2-106 GEN
Solar/Wind Harmer
22.046
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270588AE1-091_GEN
Solar/Wind Harmer
5.845
25194608D.CRK4
Adder
1.74
946031AF1-268 GEN
Solar/Wind Harmer
6.992
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
24755605MDL-5G
Solar/Wind Harmer
0.001
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
274676JOLIET 29;8U
Adder
30.185
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
274682WAUKEGAN ;7U
Adder
9.728
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
237080AD1-060 GEN
Solar/Wind Helper
0.342
966131AG1-482 GEN
Solar/Wind Helper
0.137
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
219904AC1-010 C
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
217208PARK ELE C
Solar/Wind Helper
0.004
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
276868AE1-113 GEN
Solar/Wind Harmer
1.414
238208AF1-136 C
Solar/Wind Helper
0.22
205943AE1-185 GEN
Solar/Wind Helper
0.509
233990AG1-397 GEN
Solar/Wind Helper
0.27
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24387305FR-4G C
Solar/Wind Harmer
0.003
274801UNIV PARK;4U
Adder
5.966
23583801GRNGAP
Solar/Wind Helper
5.601
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.274
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.367
233982AB2-133 GEN
Solar/Wind Helper
0.358
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.232
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
971997AH1-543 GEN
Solar/Wind Harmer
2.724
270051AF1-062 GEN
50/50
11.821
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
971191AH1-055 GEN
Solar/Wind Harmer
19.26
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270043AE2-236 GEN
Solar/Wind Harmer
4.777
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
945111AF1-176 GEN
Solar/Wind Harmer
5.919
25196008MFTGT1
Adder
1.405
24441205WTRV SLR C
Solar/Wind Harmer
0
970243AG2-164 GEN
Solar/Wind Harmer
4.205
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
274802UNIV PARK;5U
Adder
5.97
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274800UNIV PARK;3U
Adder
5.966
276897AD1-100 C
Solar/Wind Harmer
0.009
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.177
233930AB2-032 GEN
Solar/Wind Helper
0.381
233954AC2-188 GEN
Solar/Wind Helper
0.232
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
274753CRETE EC ;3U
Adder
8.477
972038AH1-567 GEN2
Adder
0.373
238118U2-030_1
Solar/Wind Helper
0.341
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237038AE2-054 C
Solar/Wind Helper
0.272
23779801AA1-109
Solar/Wind Helper
0.193
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.138
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
207445AB1-138_GEN
Solar/Wind Helper
0.104
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
CPLELTFEXP_CPLE->PJM
CLTF
0.624
SIGELTFEXP_SIGE->PJM
CLTF
0.505
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
NYPJM->LTFIMP_NY
CLTF
4.797
TVALTFEXP_TVA->PJM
CLTF
7.293
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
WECLTFEXP_WEC->PJM
CLTF
3.825
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
LGEELTFEXP_LGEE->PJM
CLTF
6.749
MECLTFEXP_MEC->PJM
CLTF
15.901
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.1 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4627.6
MW Contribution:1.88
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
971201AH1-060 GEN
Solar/Wind Harmer
1.471
970627AG2-408 GEN
Solar/Wind Harmer
2.167
960971AF2-388 GEN
Solar/Wind Harmer
4.192
970883AG2-550 GEN
Solar/Wind Harmer
7.123
25194408D.CRK1
Adder
7.711
270599AE1-208 GEN
Solar/Wind Harmer
6.495
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
24728905RICHG2
Adder
3.82
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274887GEN-1.85
Solar/Wind Harmer
0.181
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
274879MINONK ;1U
Solar/Wind Harmer
0.287
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237002AB1-128_GEN
Solar/Wind Helper
0.427
237006AB1-125 GEN
Solar/Wind Helper
0.119
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
232424Y1-079 C
Solar/Wind Helper
0.112
233970AC1-092 C
Solar/Wind Helper
0.338
230433AD2-135 GEN
Solar/Wind Helper
0.016
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
970879AG2-548 GEN
Solar/Wind Harmer
6.645
270435AC2-044 GEN
Solar/Wind Harmer
0.92
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
270543AE2-219 C
Solar/Wind Harmer
0.004
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
7.898
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
253343AC1-166 GEN
Solar/Wind Harmer
0.003
971995AH1-542 GEN
Solar/Wind Harmer
2.81
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
25194608D.CRK4
Adder
1.676
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
970613AG2-401 GEN
Solar/Wind Harmer
5.183
24639705ELKHART HY
Adder
0.155
970291AG2-192 GEN
Solar/Wind Harmer
0.916
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.005
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
238185AF2-356 C
Solar/Wind Helper
2.425
237030AB1-096 C
Solar/Wind Helper
0.068
227287AC2-120 GEN
Solar/Wind Helper
0.335
233996TM1833_GEN
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714528FRN_Y2-051
Solar/Wind Helper
0.055
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270302AB2-170 GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
1.08
970179AG2-119 GEN
Solar/Wind Harmer
6.658
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
957201AF2-014 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
270024AE2-089 GEN
Solar/Wind Harmer
0.008
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
1.339
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
4.954
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
274735ELWOOD EC;4P
Adder
16.163
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
959381AF2-229 GEN
Solar/Wind Helper
0.345
960921AF2-383 GEN
Solar/Wind Helper
0.352
205932AD2-116_GEN
Solar/Wind Helper
0.492
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
203975AE1-071-GEN
Solar/Wind Helper
2.41
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.758
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970935AG2-582 GEN
Adder
242.403
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
247621Y3-024
Adder
0.246
971613AH1-306 GEN
Solar/Wind Harmer
3.385
965681AG1-436 GEN
Solar/Wind Harmer
8.77
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971677AH1-339 GEN
Solar/Wind Harmer
0.768
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230407AD2-065 C
Solar/Wind Helper
0.039
20714928UPF_X1-085
Solar/Wind Helper
0.005
970153AG2-106 GEN
Solar/Wind Harmer
21.245
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
24721905FLATG4
Adder
22.865
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
270588AE1-091_GEN
Solar/Wind Harmer
5.649
25194608D.CRK4
Adder
1.676
946031AF1-268 GEN
Solar/Wind Harmer
6.74
247643Z2-116 C
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
9.866
270317AD1-130_GEN
Solar/Wind Harmer
0.011
253349AC2-067 GEN
Solar/Wind Harmer
2.296
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971985AH1-537 GEN
Solar/Wind Harmer
2.123
971029AG2-637 GEN
Solar/Wind Harmer
10.686
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
3.169
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
24386405FR-21G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
23559001PLEAS1
50/50
5.385
961921AG1-034 GEN
Solar/Wind Harmer
7.364
942051AE2-217 GEN
Solar/Wind Harmer
14.169
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270273AD2-016 GEN
Solar/Wind Harmer
0.792
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270247TR4_N_V136
Solar/Wind Harmer
0.047
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
970031AG2-029 GEN
Solar/Wind Harmer
4.625
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270437AC2-090 C
Solar/Wind Harmer
0.003
247604X1-042
Adder
0.418
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
972228AH1-698 GEN2
Adder
3.654
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274730ELWOOD EC;6P
Adder
13.491
270541AE2-072 C
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238127S14_GEN_2
Solar/Wind Helper
0.766
235062AE1-101 C1
Solar/Wind Helper
1.6
223401AF1-299 GEN
Solar/Wind Helper
0.355
233915AB1-141 GEN
Solar/Wind Helper
0.486
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
228728W1-130C
Solar/Wind Helper
0.052
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
316254AC1-120 GEN1
Solar/Wind Helper
1.026
963711AG1-223 GEN
Solar/Wind Helper
0.062
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
970149AG2-104 GEN
Solar/Wind Harmer
35.932
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
927014AC1-188 GEN
Solar/Wind Harmer
0.004
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.67
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
971917AH1-482 GEN
Solar/Wind Harmer
9.071
24791305MDL-5G
Solar/Wind Harmer
0.001
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
238108AE1-109 GEN1
Solar/Wind Helper
0.106
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233997TMININ_4.2
Solar/Wind Helper
0.253
233971AC1-093 C
Solar/Wind Helper
0.346
228729W2-030 C
Solar/Wind Helper
0.107
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715028HAN_X4-015
Solar/Wind Helper
0.055
270166AC1-044 GEN3
50/50
6.869
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965011AG1-365 GEN
Solar/Wind Harmer
7.225
958861AF2-177 GEN
Solar/Wind Harmer
3.092
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.532
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.509
270051AF1-062 GEN
50/50
11.434
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
970065AG2-057 GEN
Solar/Wind Harmer
0.735
965021AG1-366 GEN
Solar/Wind Harmer
2.408
971191AH1-055 GEN
Solar/Wind Harmer
18.515
270043AE2-236 GEN
Solar/Wind Harmer
4.607
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
252510AF1-249 C
Solar/Wind Harmer
0.055
945111AF1-176 GEN
Solar/Wind Harmer
5.709
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
970243AG2-164 GEN
Solar/Wind Harmer
4.047
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
274802UNIV PARK;5U
Adder
5.755
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274800UNIV PARK;3U
Adder
5.751
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
274729ELWOOD EC;1P
Adder
16.163
276893AG1-478 C
Solar/Wind Harmer
0.272
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233954AC2-188 GEN
Solar/Wind Helper
0.225
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219907AC1-030 C
Solar/Wind Helper
0.033
970077AG2-063 GEN
Solar/Wind Harmer
4.471
972239AH1-704 GEN
50/50
2.78
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
270432AC2-029 GEN
Solar/Wind Harmer
3.428
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
270340AC2-060 GEN
Solar/Wind Harmer
0.009
253400AC2-068 GEN
Solar/Wind Harmer
0.923
965041AG1-368 GEN
Solar/Wind Harmer
7.21
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
25196508WSDLE4
Adder
8.656
971609AH1-304 GEN
Solar/Wind Harmer
1.157
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
24386205FR-12G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
972163AH1-664 GEN
Solar/Wind Harmer
7.639
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
3138216PACIFIC
Solar/Wind Helper
0.043
23750501ELLIOTTS
Solar/Wind Helper
0.571
205956AE1-196_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
219914AD2-027 C
Solar/Wind Helper
0.111
219607WPEMNERT C
Solar/Wind Helper
0.077
20715728PEM_W1-119
Solar/Wind Helper
0.093
316164AC1-076 GEN
Solar/Wind Helper
1.062
972269AH1-719 GEN
Adder
2.501
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.4
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
970611AG2-400 GEN
Solar/Wind Harmer
7.225
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.036
970621AG2-405 GEN
Solar/Wind Harmer
1.305
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
972259AH1-714 GEN
Adder
18.805
970241AG2-163 GEN
Solar/Wind Harmer
3.993
238175AF1-290_GEN
Solar/Wind Helper
0.148
235020AA1-095 C
Solar/Wind Helper
0.051
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
942861AE2-305 GEN
Solar/Wind Harmer
6.118
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972159AH1-661 GEN
Adder
1.082
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971231AH1-075 GEN
Solar/Wind Harmer
0.833
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
960441AF2-335 GEN
Solar/Wind Harmer
7.065
24728805RICHG1
Adder
3.82
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.271
958491AF2-143 GEN
Solar/Wind Harmer
10.205
237034AC2-136 C
Solar/Wind Helper
0.219
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
226929AD2-058 GEN
Solar/Wind Helper
0.096
233987AB2-037 GEN
Solar/Wind Helper
2.264
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
20720628TIN_W1-124
Solar/Wind Helper
0.183
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
247522W1-056 GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.397
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
24387305FR-4G C
Solar/Wind Harmer
0.003
274801UNIV PARK;4U
Adder
5.751
23583801GRNGAP
Solar/Wind Helper
5.418
238149AF1-291A_GEN
Solar/Wind Helper
0.137
237061AD1-155 GEN
Solar/Wind Helper
0.051
238221AF1-254 C O1
Solar/Wind Helper
0.265
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
233982AB2-133 GEN
Solar/Wind Helper
0.346
233940AF2-379 C
Solar/Wind Helper
0.06
233952AC2-187 GEN
Solar/Wind Helper
0.225
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.018
971997AH1-543 GEN
Solar/Wind Harmer
1.86
24318805MLG1
50/50
9.842
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.811
970191AG2-125 GEN
Solar/Wind Harmer
1.876
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.057
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
270222AC2-111 GEN
Solar/Wind Harmer
3.603
270004AE1-209 GEN
Solar/Wind Harmer
1.532
24642205MAYFLWER
Adder
0.641
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274753CRETE EC ;3U
Adder
8.172
972038AH1-567 GEN2
Adder
0.36
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238118U2-030_1
Solar/Wind Helper
0.314
237038AE2-054 C
Solar/Wind Helper
0.262
23779801AA1-109
Solar/Wind Helper
0.187
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.009
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
207445AB1-138_GEN
Solar/Wind Helper
0.101
962761AG1-125 GEN
Solar/Wind Harmer
33.269
270462AD2-086
Solar/Wind Harmer
0.016
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
247536S-71 GEN
Solar/Wind Harmer
0.287
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
276903AD2-071 C
Solar/Wind Harmer
7.842
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.172
24385905FR-11G C
Solar/Wind Harmer
0.002
939401AE1-172 GEN
Solar/Wind Harmer
5.109
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238117U2-030
Solar/Wind Helper
0.314
235067AD1-061 GEN
Solar/Wind Helper
0.478
234015AF2-250 C
Solar/Wind Helper
0.037
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
219276PARKLANDSO C
Solar/Wind Helper
0.086
20720528MAN_W1-024
Solar/Wind Helper
0.027
971771AH1-392 GEN
Solar/Wind Harmer
7.046
971769AH1-391 GEN
Solar/Wind Harmer
7.844
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
16.163
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
3141426STAFORD
Solar/Wind Helper
0.051
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
972165AH1-665 GEN
Solar/Wind Harmer
6.118
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.363
238208AF1-136 C
Solar/Wind Helper
0.211
205943AE1-185 GEN
Solar/Wind Helper
0.492
233990AG1-397 GEN
Solar/Wind Helper
0.261
964001AG1-254 GEN
Solar/Wind Helper
0.924
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
219620RIDERU C
Solar/Wind Helper
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
24755605MDL-5G
Solar/Wind Harmer
0.001
276806AD2-047 C O1
Solar/Wind Harmer
3.901
24728505AND G1
Adder
3.784
274676JOLIET 29;8U
Adder
29.097
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
237080AD1-060 GEN
Solar/Wind Helper
0.33
966131AG1-482 GEN
Solar/Wind Helper
0.132
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
232434Z2-077 GEN
Solar/Wind Helper
0.123
219904AC1-010 C
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.055
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
CPLELTFEXP_CPLE->PJM
CLTF
0.567
SIGELTFEXP_SIGE->PJM
CLTF
0.486
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
NYPJM->LTFIMP_NY
CLTF
4.628
TVALTFEXP_TVA->PJM
CLTF
7.011
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
WECLTFEXP_WEC->PJM
CLTF
3.686
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
LGEELTFEXP_LGEE->PJM
CLTF
6.497
MECLTFEXP_MEC->PJM
CLTF
15.319
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.92 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5002.28
MW Contribution:1.95
Bus #Bus NameTypeMW Contribution
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
10.218
270317AD1-130_GEN
Solar/Wind Harmer
0.011
253349AC2-067 GEN
Solar/Wind Harmer
2.381
965051AG1-369 GEN
Solar/Wind Harmer
3.739
971985AH1-537 GEN
Solar/Wind Harmer
2.206
971029AG2-637 GEN
Solar/Wind Harmer
11.085
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
11.025
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
3.285
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386405FR-21G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
972165AH1-665 GEN
Solar/Wind Harmer
6.354
962771AG1-126 GEN
Solar/Wind Harmer
34.524
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270302AB2-170 GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
1.117
970179AG2-119 GEN
Solar/Wind Harmer
6.883
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
957201AF2-014 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
270024AE2-089 GEN
Solar/Wind Harmer
0.008
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
1.389
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
5.139
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
274735ELWOOD EC;4P
Adder
16.768
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.357
960921AF2-383 GEN
Solar/Wind Helper
0.364
205932AD2-116_GEN
Solar/Wind Helper
0.509
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
203975AE1-071-GEN
Solar/Wind Helper
2.498
966261AG1-495 GEN
Solar/Wind Helper
0.081
270120AB2-067 GEN2
50/50
7.059
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
971201AH1-060 GEN
Solar/Wind Harmer
1.52
970627AG2-408 GEN
Solar/Wind Harmer
2.246
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970883AG2-550 GEN
Solar/Wind Harmer
7.389
25194408D.CRK1
Adder
8.004
270599AE1-208 GEN
Solar/Wind Harmer
6.737
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
24728905RICHG2
Adder
3.964
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274803UNIV PARK;6U
Adder
5.97
274887GEN-1.85
Solar/Wind Harmer
0.188
274674JOLIET 9 ;6U
Adder
15.704
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
274693ROCKY RD ;1P
Adder
11.16
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.116
233970AC1-092 C
Solar/Wind Helper
0.35
230433AD2-135 GEN
Solar/Wind Helper
0.017
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
970879AG2-548 GEN
Solar/Wind Harmer
6.898
270435AC2-044 GEN
Solar/Wind Harmer
0.953
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.804
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
8.194
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971769AH1-391 GEN
Solar/Wind Harmer
8.134
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24691005MDL-2G C
Solar/Wind Harmer
0.001
270166AC1-044 GEN3
50/50
7.059
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965011AG1-365 GEN
Solar/Wind Harmer
7.488
958861AF2-177 GEN
Solar/Wind Harmer
3.207
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.59
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.877
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
270119AB2-067 GEN1
50/50
7.059
970077AG2-063 GEN
Solar/Wind Harmer
4.631
972269AH1-719 GEN
Adder
2.584
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.451
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
970611AG2-400 GEN
Solar/Wind Harmer
7.488
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
970621AG2-405 GEN
Solar/Wind Harmer
1.351
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
270051AF1-062 GEN
50/50
11.821
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
971191AH1-055 GEN
Solar/Wind Harmer
19.26
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270043AE2-236 GEN
Solar/Wind Harmer
4.777
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
945111AF1-176 GEN
Solar/Wind Harmer
5.919
25196008MFTGT1
Adder
1.405
24441205WTRV SLR C
Solar/Wind Harmer
0
970243AG2-164 GEN
Solar/Wind Harmer
4.205
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
274802UNIV PARK;5U
Adder
5.97
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274800UNIV PARK;3U
Adder
5.966
276897AD1-100 C
Solar/Wind Harmer
0.009
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.177
233930AB2-032 GEN
Solar/Wind Helper
0.381
233954AC2-188 GEN
Solar/Wind Helper
0.232
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
23559101PLEAS2
50/50
6.1
970149AG2-104 GEN
Solar/Wind Harmer
37.287
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
927014AC1-188 GEN
Solar/Wind Harmer
0.005
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.805
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
24791305MDL-5G
Solar/Wind Harmer
0.001
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
23562501BACKB
Solar/Wind Helper
1.007
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233994AC2-023 GEN
Solar/Wind Helper
0.961
233997TMININ_4.2
Solar/Wind Helper
0.261
233971AC1-093 C
Solar/Wind Helper
0.357
228729W2-030 C
Solar/Wind Helper
0.11
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
253343AC1-166 GEN
Solar/Wind Harmer
0.003
971995AH1-542 GEN
Solar/Wind Harmer
2.906
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
965421AG1-410 GEN
Solar/Wind Harmer
22.57
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.854
276820AF1-078_GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
253370AE2-315 SEC1
Adder
2.182
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
971613AH1-306 GEN
Solar/Wind Harmer
3.512
965681AG1-436 GEN
Solar/Wind Harmer
9.095
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
238120AE2-309 GEN
Solar/Wind Helper
0.525
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230407AD2-065 C
Solar/Wind Helper
0.04
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
970153AG2-106 GEN
Solar/Wind Harmer
22.046
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270588AE1-091_GEN
Solar/Wind Harmer
5.845
25194608D.CRK4
Adder
1.74
946031AF1-268 GEN
Solar/Wind Harmer
6.992
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
24755605MDL-5G
Solar/Wind Harmer
0.001
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
274676JOLIET 29;8U
Adder
30.185
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
274682WAUKEGAN ;7U
Adder
9.728
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
237080AD1-060 GEN
Solar/Wind Helper
0.342
966131AG1-482 GEN
Solar/Wind Helper
0.137
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
219904AC1-010 C
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
962761AG1-125 GEN
Solar/Wind Harmer
34.524
270462AD2-086
Solar/Wind Harmer
0.017
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
247536S-71 GEN
Solar/Wind Harmer
0.297
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
944231AF1-091 GEN
Solar/Wind Harmer
1.953
276903AD2-071 C
Solar/Wind Harmer
8.137
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.477
24385905FR-11G C
Solar/Wind Harmer
0.002
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
939401AE1-172 GEN
Solar/Wind Harmer
5.301
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
235067AD1-061 GEN
Solar/Wind Helper
0.496
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
219276PARKLANDSO C
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
23559001PLEAS1
50/50
6.1
961921AG1-034 GEN
Solar/Wind Harmer
7.615
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270273AD2-016 GEN
Solar/Wind Harmer
0.821
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.563
270377AD1-106 GEN
Solar/Wind Harmer
2.855
270247TR4_N_V136
Solar/Wind Harmer
0.048
944531AF1-118 GEN
Solar/Wind Harmer
33.395
25196608WSDLE5
Adder
9.077
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270437AC2-090 C
Solar/Wind Harmer
0.003
247604X1-042
Adder
0.433
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
24728705AND G3
Adder
8.214
274826FISK ;BP
Adder
11.205
972228AH1-698 GEN2
Adder
3.79
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274730ELWOOD EC;6P
Adder
16.768
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238127S14_GEN_2
Solar/Wind Helper
0.827
235062AE1-101 C1
Solar/Wind Helper
1.659
223401AF1-299 GEN
Solar/Wind Helper
0.367
233915AB1-141 GEN
Solar/Wind Helper
0.502
232428Y3-058 C
Solar/Wind Helper
0.338
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.059
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.571
219258KINSLEYDEP C
Solar/Wind Helper
0.077
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
274808UNIV PK N;4U
Adder
5.117
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
972259AH1-714 GEN
Adder
19.507
970241AG2-163 GEN
Solar/Wind Harmer
4.144
274696ROCKY RD ;4P
Adder
11.537
274697ROCKY RD ;3P
Adder
3.062
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
233946AB2-136 GEN
Solar/Wind Helper
0.568
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20716928W4-060COL
Solar/Wind Helper
0.051
20673828FLE_V3-070
Solar/Wind Helper
0.09
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.168
20676228FRD_X1-012
Solar/Wind Helper
0.092
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
16.768
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.827
237085AD2-009_GEN
Solar/Wind Helper
1.649
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
209116AE2-175 GEN
Solar/Wind Helper
1.778
24318805MLG1
50/50
10.095
270475AD2-096_GEN
50/50
7.141
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.952
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.242
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
270222AC2-111 GEN
Solar/Wind Harmer
3.739
270004AE1-209 GEN
Solar/Wind Harmer
1.59
24642205MAYFLWER
Adder
0.665
270356AE2-297 GEN
Solar/Wind Harmer
0.01
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
274753CRETE EC ;3U
Adder
8.477
972038AH1-567 GEN2
Adder
0.373
238118U2-030_1
Solar/Wind Helper
0.341
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237038AE2-054 C
Solar/Wind Helper
0.272
23779801AA1-109
Solar/Wind Helper
0.193
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.138
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
207445AB1-138_GEN
Solar/Wind Helper
0.104
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
972239AH1-704 GEN
Adder
2.689
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
270340AC2-060 GEN
Solar/Wind Harmer
0.009
253400AC2-068 GEN
Solar/Wind Harmer
0.958
965041AG1-368 GEN
Solar/Wind Harmer
7.471
965101AG1-375 GEN
Solar/Wind Harmer
7.401
25196508WSDLE4
Adder
8.984
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274746AC1-111 G10
Adder
5.679
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238152AF2-075_GEN
Solar/Wind Helper
0.707
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.638
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.029
942861AE2-305 GEN
Solar/Wind Harmer
6.335
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972159AH1-661 GEN
Adder
1.118
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
971231AH1-075 GEN
Solar/Wind Harmer
0.861
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.496
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
270031AE2-169
Solar/Wind Harmer
4.042
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
24728805RICHG1
Adder
3.964
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274695ROCKY RD ;2P
Adder
11.271
958491AF2-143 GEN
Solar/Wind Harmer
10.588
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.342
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.232
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.098
966111AG1-480 GEN
Solar/Wind Helper
0.074
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
276868AE1-113 GEN
Solar/Wind Harmer
1.414
238208AF1-136 C
Solar/Wind Helper
0.22
205943AE1-185 GEN
Solar/Wind Helper
0.509
233990AG1-397 GEN
Solar/Wind Helper
0.27
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24387305FR-4G C
Solar/Wind Harmer
0.003
274801UNIV PARK;4U
Adder
5.966
23583801GRNGAP
Solar/Wind Helper
5.601
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.274
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.367
233982AB2-133 GEN
Solar/Wind Helper
0.358
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.232
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
971997AH1-543 GEN
Solar/Wind Harmer
2.724
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
217208PARK ELE C
Solar/Wind Helper
0.004
25194608D.CRK4
Adder
1.74
970947AG2-589 GEN
Solar/Wind Harmer
0.245
965031AG1-367 GEN
Solar/Wind Harmer
7.338
970613AG2-401 GEN
Solar/Wind Harmer
5.378
24639705ELKHART HY
Adder
0.161
970291AG2-192 GEN
Solar/Wind Harmer
0.95
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274676JOLIET 29;8U
Adder
31.303
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.679
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
238185AF2-356 C
Solar/Wind Helper
2.646
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.346
233996TM1833_GEN
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
CPLELTFEXP_CPLE->PJM
CLTF
0.624
SIGELTFEXP_SIGE->PJM
CLTF
0.505
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
NYPJM->LTFIMP_NY
CLTF
4.797
TVALTFEXP_TVA->PJM
CLTF
7.293
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
WECLTFEXP_WEC->PJM
CLTF
3.825
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
LGEELTFEXP_LGEE->PJM
CLTF
6.749
MECLTFEXP_MEC->PJM
CLTF
15.901
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4754.33
MW Contribution:1.88
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
6.869
970077AG2-063 GEN
Solar/Wind Harmer
4.471
972269AH1-719 GEN
Adder
2.501
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.4
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
970611AG2-400 GEN
Solar/Wind Harmer
7.225
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.036
970621AG2-405 GEN
Solar/Wind Harmer
1.305
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
972259AH1-714 GEN
Adder
18.805
970241AG2-163 GEN
Solar/Wind Harmer
3.993
238175AF1-290_GEN
Solar/Wind Helper
0.148
235020AA1-095 C
Solar/Wind Helper
0.051
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
940611AE2-048 GEN
Solar/Wind Harmer
18.967
972239AH1-704 GEN
50/50
2.78
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
270432AC2-029 GEN
Solar/Wind Harmer
3.428
23559001PLEAS1
50/50
5.385
961921AG1-034 GEN
Solar/Wind Harmer
7.364
942051AE2-217 GEN
Solar/Wind Harmer
14.169
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270120AB2-067 GEN2
50/50
6.869
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
971201AH1-060 GEN
Solar/Wind Harmer
1.471
970627AG2-408 GEN
Solar/Wind Harmer
2.167
960971AF2-388 GEN
Solar/Wind Harmer
4.192
970883AG2-550 GEN
Solar/Wind Harmer
7.123
25194408D.CRK1
Adder
7.711
270599AE1-208 GEN
Solar/Wind Harmer
6.495
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
24728905RICHG2
Adder
3.82
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274887GEN-1.85
Solar/Wind Harmer
0.181
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
274879MINONK ;1U
Solar/Wind Harmer
0.287
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237002AB1-128_GEN
Solar/Wind Helper
0.427
237006AB1-125 GEN
Solar/Wind Helper
0.119
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
232424Y1-079 C
Solar/Wind Helper
0.112
233970AC1-092 C
Solar/Wind Helper
0.338
230433AD2-135 GEN
Solar/Wind Helper
0.016
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
941391AE2-136 GEN
Solar/Wind Harmer
10.684
970879AG2-548 GEN
Solar/Wind Harmer
6.645
270435AC2-044 GEN
Solar/Wind Harmer
0.92
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
270543AE2-219 C
Solar/Wind Harmer
0.004
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
971769AH1-391 GEN
Solar/Wind Harmer
7.844
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
16.163
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
3141426STAFORD
Solar/Wind Helper
0.051
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
942861AE2-305 GEN
Solar/Wind Harmer
6.118
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972159AH1-661 GEN
Adder
1.082
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
970149AG2-104 GEN
Solar/Wind Harmer
35.932
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
927014AC1-188 GEN
Solar/Wind Harmer
0.004
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.67
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
253343AC1-166 GEN
Solar/Wind Harmer
0.003
971995AH1-542 GEN
Solar/Wind Harmer
2.81
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
25194608D.CRK4
Adder
1.676
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
970613AG2-401 GEN
Solar/Wind Harmer
5.183
24639705ELKHART HY
Adder
0.155
970291AG2-192 GEN
Solar/Wind Harmer
0.916
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.005
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
238185AF2-356 C
Solar/Wind Helper
2.425
237030AB1-096 C
Solar/Wind Helper
0.068
227287AC2-120 GEN
Solar/Wind Helper
0.335
233996TM1833_GEN
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714528FRN_Y2-051
Solar/Wind Helper
0.055
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270302AB2-170 GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
1.08
970179AG2-119 GEN
Solar/Wind Harmer
6.658
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
957201AF2-014 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
270024AE2-089 GEN
Solar/Wind Harmer
0.008
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
1.339
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
4.954
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
274735ELWOOD EC;4P
Adder
16.163
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
959381AF2-229 GEN
Solar/Wind Helper
0.345
960921AF2-383 GEN
Solar/Wind Helper
0.352
205932AD2-116_GEN
Solar/Wind Helper
0.492
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
203975AE1-071-GEN
Solar/Wind Helper
2.41
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.758
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970935AG2-582 GEN
Adder
242.403
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
247621Y3-024
Adder
0.246
971613AH1-306 GEN
Solar/Wind Harmer
3.385
965681AG1-436 GEN
Solar/Wind Harmer
8.77
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971677AH1-339 GEN
Solar/Wind Harmer
0.768
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230407AD2-065 C
Solar/Wind Helper
0.039
20714928UPF_X1-085
Solar/Wind Helper
0.005
970153AG2-106 GEN
Solar/Wind Harmer
21.245
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
24721905FLATG4
Adder
22.865
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
270588AE1-091_GEN
Solar/Wind Harmer
5.649
25194608D.CRK4
Adder
1.676
946031AF1-268 GEN
Solar/Wind Harmer
6.74
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
24755605MDL-5G
Solar/Wind Harmer
0.001
276806AD2-047 C O1
Solar/Wind Harmer
3.901
24728505AND G1
Adder
3.784
274676JOLIET 29;8U
Adder
29.097
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
237080AD1-060 GEN
Solar/Wind Helper
0.33
966131AG1-482 GEN
Solar/Wind Helper
0.132
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
232434Z2-077 GEN
Solar/Wind Helper
0.123
219904AC1-010 C
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.055
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
9.866
270317AD1-130_GEN
Solar/Wind Harmer
0.011
253349AC2-067 GEN
Solar/Wind Harmer
2.296
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971985AH1-537 GEN
Solar/Wind Harmer
2.123
971029AG2-637 GEN
Solar/Wind Harmer
10.686
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
3.169
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
24386405FR-21G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972165AH1-665 GEN
Solar/Wind Harmer
6.118
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.363
238208AF1-136 C
Solar/Wind Helper
0.211
205943AE1-185 GEN
Solar/Wind Helper
0.492
233990AG1-397 GEN
Solar/Wind Helper
0.261
964001AG1-254 GEN
Solar/Wind Helper
0.924
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
219620RIDERU C
Solar/Wind Helper
0.001
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270273AD2-016 GEN
Solar/Wind Harmer
0.792
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270247TR4_N_V136
Solar/Wind Harmer
0.047
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
970031AG2-029 GEN
Solar/Wind Harmer
4.625
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270437AC2-090 C
Solar/Wind Harmer
0.003
247604X1-042
Adder
0.418
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
972228AH1-698 GEN2
Adder
3.654
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274730ELWOOD EC;6P
Adder
13.491
270541AE2-072 C
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238127S14_GEN_2
Solar/Wind Helper
0.766
235062AE1-101 C1
Solar/Wind Helper
1.6
223401AF1-299 GEN
Solar/Wind Helper
0.355
233915AB1-141 GEN
Solar/Wind Helper
0.486
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
228728W1-130C
Solar/Wind Helper
0.052
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
316254AC1-120 GEN1
Solar/Wind Helper
1.026
963711AG1-223 GEN
Solar/Wind Helper
0.062
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
971917AH1-482 GEN
Solar/Wind Harmer
9.071
24791305MDL-5G
Solar/Wind Harmer
0.001
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
238108AE1-109 GEN1
Solar/Wind Helper
0.106
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233997TMININ_4.2
Solar/Wind Helper
0.253
233971AC1-093 C
Solar/Wind Helper
0.346
228729W2-030 C
Solar/Wind Helper
0.107
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715028HAN_X4-015
Solar/Wind Helper
0.055
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
270340AC2-060 GEN
Solar/Wind Harmer
0.009
253400AC2-068 GEN
Solar/Wind Harmer
0.923
965041AG1-368 GEN
Solar/Wind Harmer
7.21
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
25196508WSDLE4
Adder
8.656
971609AH1-304 GEN
Solar/Wind Harmer
1.157
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
24386205FR-12G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
972163AH1-664 GEN
Solar/Wind Harmer
7.639
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
270166AC1-044 GEN3
50/50
6.869
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965011AG1-365 GEN
Solar/Wind Harmer
7.225
958861AF2-177 GEN
Solar/Wind Harmer
3.092
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.532
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.509
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
247522W1-056 GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.397
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
24387305FR-4G C
Solar/Wind Harmer
0.003
274801UNIV PARK;4U
Adder
5.751
23583801GRNGAP
Solar/Wind Helper
5.418
238149AF1-291A_GEN
Solar/Wind Helper
0.137
237061AD1-155 GEN
Solar/Wind Helper
0.051
238221AF1-254 C O1
Solar/Wind Helper
0.265
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
233982AB2-133 GEN
Solar/Wind Helper
0.346
233940AF2-379 C
Solar/Wind Helper
0.06
233952AC2-187 GEN
Solar/Wind Helper
0.225
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.018
971997AH1-543 GEN
Solar/Wind Harmer
1.86
270051AF1-062 GEN
50/50
11.434
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
970065AG2-057 GEN
Solar/Wind Harmer
0.735
965021AG1-366 GEN
Solar/Wind Harmer
2.408
971191AH1-055 GEN
Solar/Wind Harmer
18.515
270043AE2-236 GEN
Solar/Wind Harmer
4.607
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
252510AF1-249 C
Solar/Wind Harmer
0.055
945111AF1-176 GEN
Solar/Wind Harmer
5.709
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
970243AG2-164 GEN
Solar/Wind Harmer
4.047
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
274802UNIV PARK;5U
Adder
5.755
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274800UNIV PARK;3U
Adder
5.751
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
274729ELWOOD EC;1P
Adder
16.163
276893AG1-478 C
Solar/Wind Harmer
0.272
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233954AC2-188 GEN
Solar/Wind Helper
0.225
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219907AC1-030 C
Solar/Wind Helper
0.033
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
3138216PACIFIC
Solar/Wind Helper
0.043
23750501ELLIOTTS
Solar/Wind Helper
0.571
205956AE1-196_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
219914AD2-027 C
Solar/Wind Helper
0.111
219607WPEMNERT C
Solar/Wind Helper
0.077
20715728PEM_W1-119
Solar/Wind Helper
0.093
316164AC1-076 GEN
Solar/Wind Helper
1.062
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971231AH1-075 GEN
Solar/Wind Harmer
0.833
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
960441AF2-335 GEN
Solar/Wind Harmer
7.065
24728805RICHG1
Adder
3.82
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.271
958491AF2-143 GEN
Solar/Wind Harmer
10.205
237034AC2-136 C
Solar/Wind Helper
0.219
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
226929AD2-058 GEN
Solar/Wind Helper
0.096
233987AB2-037 GEN
Solar/Wind Helper
2.264
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
20720628TIN_W1-124
Solar/Wind Helper
0.183
24318805MLG1
50/50
9.842
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.811
970191AG2-125 GEN
Solar/Wind Harmer
1.876
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.057
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
270222AC2-111 GEN
Solar/Wind Harmer
3.603
270004AE1-209 GEN
Solar/Wind Harmer
1.532
24642205MAYFLWER
Adder
0.641
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274753CRETE EC ;3U
Adder
8.172
972038AH1-567 GEN2
Adder
0.36
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238118U2-030_1
Solar/Wind Helper
0.314
237038AE2-054 C
Solar/Wind Helper
0.262
23779801AA1-109
Solar/Wind Helper
0.187
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.009
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
207445AB1-138_GEN
Solar/Wind Helper
0.101
962761AG1-125 GEN
Solar/Wind Harmer
33.269
270462AD2-086
Solar/Wind Harmer
0.016
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
247536S-71 GEN
Solar/Wind Harmer
0.287
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
276903AD2-071 C
Solar/Wind Harmer
7.842
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.172
24385905FR-11G C
Solar/Wind Harmer
0.002
939401AE1-172 GEN
Solar/Wind Harmer
5.109
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238117U2-030
Solar/Wind Helper
0.314
235067AD1-061 GEN
Solar/Wind Helper
0.478
234015AF2-250 C
Solar/Wind Helper
0.037
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
219276PARKLANDSO C
Solar/Wind Helper
0.086
20720528MAN_W1-024
Solar/Wind Helper
0.027
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
LGEELTFEXP_LGEE->PJM
CLTF
6.497
MECLTFEXP_MEC->PJM
CLTF
15.319
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
WECLTFEXP_WEC->PJM
CLTF
3.686
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
NYPJM->LTFIMP_NY
CLTF
4.628
TVALTFEXP_TVA->PJM
CLTF
7.011
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
CPLELTFEXP_CPLE->PJM
CLTF
0.567
SIGELTFEXP_SIGE->PJM
CLTF
0.486

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.76 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4919.18
MW Contribution:2.27
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
18.401
970077AG2-063 GEN
Solar/Wind Harmer
5.8
253378AE2-206_GEN
Solar/Wind Harmer
0.005
25326509SID D
Adder
1.713
970611AG2-400 GEN
Solar/Wind Harmer
8.881
970321AG2-212 GEN
Solar/Wind Harmer
3.83
942221AE2-234 GEN
Solar/Wind Harmer
0.044
246938BC-WTG3
Solar/Wind Harmer
0.316
246937BC-WTG2
Solar/Wind Harmer
0.353
253394AE2-221_GEN
Solar/Wind Harmer
0.011
253398AE2-221_GEN2
Solar/Wind Harmer
0.011
970825AG2-519 GEN
Solar/Wind Harmer
9.566
270209AC1-174_GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
10.354
274771LINCOLN ;2U
Adder
10.354
270007AE1-245 C
Solar/Wind Harmer
0.002
274808UNIV PK N;4U
Adder
6.08
274888KELLY CRK;1U
Solar/Wind Harmer
0.499
972259AH1-714 GEN
Adder
23.234
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
274696ROCKY RD ;4P
Adder
13.733
274697ROCKY RD ;3P
Adder
3.645
962691AG1-118 GEN
Solar/Wind Harmer
25.162
970623AG2-406 GEN
Solar/Wind Harmer
1.522
970241AG2-163 GEN
Solar/Wind Harmer
4.844
241985AE1-237 GEN
Solar/Wind Helper
0.242
962761AG1-125 GEN
Solar/Wind Harmer
50.586
270462AD2-086
Solar/Wind Harmer
0.021
25326309TAIT D
Adder
1.4
970245AG2-165 GEN
Solar/Wind Harmer
3.83
247536S-71 GEN
Solar/Wind Harmer
0.349
270063AE2-323 C
Solar/Wind Harmer
0.007
276903AD2-071 C
Solar/Wind Harmer
9.56
274754CRETE EC ;4U
Adder
10.063
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
18.689
274732ELWOOD EC;7P
Adder
19.951
939401AE1-172 GEN
Solar/Wind Harmer
6.298
24385905FR-11G C
Solar/Wind Harmer
0.002
962781AG1-127 GEN
Solar/Wind Harmer
7.975
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
3.003
20088826HIGHLAND
Solar/Wind Helper
0.847
238117U2-030
Solar/Wind Helper
0.269
964391AG1-301 GEN
Solar/Wind Helper
0.446
270166AC1-044 GEN3
50/50
18.401
965011AG1-365 GEN
Solar/Wind Harmer
8.881
958861AF2-177 GEN
Solar/Wind Harmer
3.827
945371AF1-202 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.353
270489AE1-102 GEN1
Solar/Wind Harmer
1.132
270005AE1-210 C O1
Solar/Wind Harmer
1.875
970825AG2-519 GEN
Solar/Wind Harmer
3.064
270032AE2-172
Solar/Wind Harmer
5.743
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
10.354
274774LINCOLN ;5U
Adder
10.354
274723RIVER EC ;12
Adder
21.894
274751CRETE EC ;1U
Adder
10.063
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
274801UNIV PARK;4U
Adder
7.097
945111AF1-176 GEN
Solar/Wind Harmer
15.149
270505AE1-170 C O1
Solar/Wind Harmer
8.915
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.609
24387305FR-4G C
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
4.396
276861AD2-134 GEN
Solar/Wind Harmer
0.15
970569AG2-363 GEN
Solar/Wind Harmer
24.96
25196808ZIMRHP
Adder
58.315
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.463
20089226LOOKOUT
Solar/Wind Helper
0.542
23751201ROTHROCK
Solar/Wind Helper
0.652
270158DARBY CT3
50/50
13.461
270036AE2-216 BAT
50/50
8.994
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.017
270054AF2-122 C O1
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0.014
253349AC2-067 GEN
Solar/Wind Harmer
2.778
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
13.153
965051AG1-369 GEN
Solar/Wind Harmer
4.367
971029AG2-637 GEN
Solar/Wind Harmer
12.951
274775LINCOLN ;6U
Adder
10.354
274777LINCOLN ;8U
Adder
10.354
24725505WLD G2 C
Solar/Wind Harmer
0.002
960591AF2-350 GEN
Solar/Wind Harmer
8.497
972037AH1-567 GEN1
Adder
0.223
971619AH1-309 GEN
Solar/Wind Harmer
3.821
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274675JOLIET 29;7U
Adder
37.252
274675JOLIET 29;7U
Adder
35.922
970833AG2-524 GEN
Solar/Wind Harmer
9.313
970833AG2-524 GEN
Solar/Wind Harmer
6.209
24697605MDL-3G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.681
971675AH1-338 GEN
Solar/Wind Harmer
3.256
971411AH1-196 GEN
Solar/Wind Harmer
12.519
971171AH1-044 GEN
Solar/Wind Harmer
16.66
274823ROCKFORD ;21
Adder
23.229
20092526R32
Solar/Wind Helper
1.098
203846AF2-130 C
Solar/Wind Helper
0.425
203855AF2-088 C
Solar/Wind Helper
0.144
961921AG1-034 GEN
Solar/Wind Harmer
9.935
942051AE2-217 GEN
Solar/Wind Harmer
18.548
270391AF1-285 GEN3
Solar/Wind Harmer
0.678
970605AG2-385 GEN
Solar/Wind Harmer
6.136
253333AC1-068 GEN
Solar/Wind Harmer
0.015
270475AD2-096_GEN
50/50
10.066
253338AC1-165 GEN
Solar/Wind Harmer
0.004
972173AH1-669 GEN
Solar/Wind Harmer
4.474
959331AF2-224 GEN
Solar/Wind Harmer
6.217
970191AG2-125 GEN
Solar/Wind Harmer
2.269
270191TR4_S_V150
Solar/Wind Harmer
0.001
971617AH1-308 GEN
Solar/Wind Harmer
7.263
270491AE1-102 GEN2
Solar/Wind Harmer
1.132
270004AE1-209 GEN
Solar/Wind Harmer
1.875
270222AC2-111 GEN
Solar/Wind Harmer
4.32
274753CRETE EC ;3U
Adder
10.063
24642205MAYFLWER
Adder
0.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972038AH1-567 GEN2
Adder
0.444
270356AE2-297 GEN
Solar/Wind Harmer
0.011
274872LEEDK;1U
Solar/Wind Harmer
0.307
270258AD1-119 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
2.611
20089126CSLMN_L13
Solar/Wind Helper
0.557
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
961821AG1-024 GEN
Solar/Wind Harmer
6.623
270578AF1-285 GEN2
Solar/Wind Harmer
0.678
945631AF1-228 GEN
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Harmer
1.032
270432AC2-029 GEN
Solar/Wind Harmer
4.134
270269AC2-059
Solar/Wind Harmer
0.005
965101AG1-375 GEN
Solar/Wind Harmer
8.831
253400AC2-068 GEN
Solar/Wind Harmer
1.117
965041AG1-368 GEN
Solar/Wind Harmer
8.719
270340AC2-060 GEN
Solar/Wind Harmer
0.01
971609AH1-304 GEN
Solar/Wind Harmer
1.419
970115AG2-085 GEN
Solar/Wind Harmer
3.451
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
10.354
24699105WLD G1 C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
6.16
274807UNIV PK N;3U
Adder
6.147
274805UNIV PK N;1U
Adder
6.12
274687WILL CNTY;4U
Adder
33.939
274687WILL CNTY;4U
Adder
33.939
970155AG2-107 GEN
Solar/Wind Harmer
32.303
270349AD2-093_GEN
Solar/Wind Harmer
0.009
253343AC1-166 GEN
Solar/Wind Harmer
0.004
960071AF2-298 GEN
Solar/Wind Harmer
4.426
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
965651AG1-433 GEN
Solar/Wind Harmer
2.599
971995AH1-542 GEN
Solar/Wind Harmer
3.236
247521TR3_G114
Solar/Wind Harmer
0.319
270246TR4_N_V150
Solar/Wind Harmer
0.056
24721705FLATG2
Adder
25.369
965421AG1-410 GEN
Solar/Wind Harmer
26.181
965031AG1-367 GEN
Solar/Wind Harmer
8.654
24695305TIMB G C
Solar/Wind Harmer
0.002
970291AG2-192 GEN
Solar/Wind Harmer
1.119
970613AG2-401 GEN
Solar/Wind Harmer
6.306
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.568
24639705ELKHART HY
Adder
0.188
270055AF2-134 C O1
Solar/Wind Harmer
0.007
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
6.107
276776AD2-060 GEN
Solar/Wind Harmer
0.887
274676JOLIET 29;8U
Adder
37.252
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
6.762
270449AD2-020 GEN
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
21.642
274828WAUKEGAN ;BP
Adder
13.296
276901AD2-066 C O1
Solar/Wind Harmer
0.008
25194608D.CRK4
Adder
1.973
957471AF2-041 GEN
Solar/Wind Harmer
24.989
24728605AND G2
Adder
4.573
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.025
964201AG1-281 GEN
Solar/Wind Helper
0.457
238206AE2-263_GEN
Solar/Wind Helper
0.858
970153AG2-106 GEN
Solar/Wind Harmer
32.303
241955AC1-078 GEN
Solar/Wind Harmer
0.009
241974AD2-163_GEN2
Solar/Wind Harmer
0.008
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
24721905FLATG4
Adder
25.369
946031AF1-268 GEN
Solar/Wind Harmer
8.226
970289AG2-191 GEN
Solar/Wind Harmer
0.947
970291AG2-192 GEN
Solar/Wind Harmer
0.861
247642Z2-115 C
Solar/Wind Harmer
0.004
247643Z2-116 C
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.138
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
276806AD2-047 C O1
Solar/Wind Harmer
4.815
274676JOLIET 29;8U
Adder
35.922
274734ELWOOD EC;8P
Adder
19.951
274736ELWOOD EC;9P
Adder
19.951
943121AE2-341 GEN
Solar/Wind Harmer
14.16
943591AF1-030 GEN
Solar/Wind Harmer
9.416
24755605MDL-5G
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
21.642
25194608D.CRK4
Adder
1.973
959091AF2-200 GEN
Solar/Wind Harmer
16.66
24728505AND G1
Adder
4.573
235058AG1-386 C
Solar/Wind Helper
0.453
964991AG1-363 GEN
Solar/Wind Helper
3.577
203818AF1-086 GEN
Solar/Wind Helper
1.594
270471AD2-092_GEN
Solar/Wind Harmer
0.009
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
3.428
276820AF1-078_GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
12.455
25322209TAIT E
Adder
12.175
253370AE2-315 SEC1
Adder
2.545
247621Y3-024
Adder
0.3
971613AH1-306 GEN
Solar/Wind Harmer
4.135
965681AG1-436 GEN
Solar/Wind Harmer
10.743
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
252519AF1-045_GEN
Solar/Wind Harmer
7.283
252516AE2-318_GEN
Solar/Wind Harmer
6.46
971341AH1-150 GEN
Solar/Wind Harmer
16.66
971343AH1-151 GEN
Solar/Wind Harmer
16.66
241801AE1-079 GEN
Solar/Wind Helper
0.242
20303426NA_O38_P22
Solar/Wind Helper
0.94
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.447
238120AE2-309 GEN
Solar/Wind Helper
0.401
270273AD2-016 GEN
Solar/Wind Harmer
0.935
944531AF1-118 GEN
Solar/Wind Harmer
40.219
970513AG2-328 GEN
Solar/Wind Harmer
3.83
970517AG2-330 GEN
Solar/Wind Harmer
22.981
253415AE1-040 GEN
Solar/Wind Harmer
0.004
970349AG2-230 GEN
Solar/Wind Harmer
13.153
270247TR4_N_V136
Solar/Wind Harmer
0.056
970031AG2-029 GEN
Solar/Wind Harmer
5.627
958821AF2-173 GEN
Solar/Wind Harmer
12.116
253406AD2-031_GEN
Solar/Wind Harmer
0.643
270437AC2-090 C
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
10.063
970707AG2-453 GEN
Solar/Wind Harmer
27.781
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
972228AH1-698 GEN2
Adder
4.511
274826FISK ;BP
Adder
13.329
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274730ELWOOD EC;6P
Adder
19.951
970781AG2-491 GEN
Solar/Wind Harmer
8.438
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
25196608WSDLE5
Adder
10.305
274855GSG-6 ;RU
Solar/Wind Harmer
0.306
24728705AND G3
Adder
9.564
254305AE2-115 C
Solar/Wind Helper
0.214
202652Y1-033 WT C
Solar/Wind Helper
0.525
20089026BF_G21_K23
Solar/Wind Helper
0.441
23750701CROSSCHOOL
Solar/Wind Helper
1.122
238127S14_GEN_2
Solar/Wind Helper
0.64
238202AE2-262_GEN
Solar/Wind Helper
0.902
270120AB2-067 GEN2
50/50
18.401
270160DARBY CT5
50/50
0.735
270466AD2-091
50/50
8.176
270224U2-072_GEN2
Solar/Wind Harmer
0.001
964601AG1-323 GEN
Solar/Wind Harmer
3.902
964601AG1-323 GEN
Solar/Wind Harmer
2.601
938701AE1-092 GEN
Solar/Wind Harmer
15.513
970627AG2-408 GEN
Solar/Wind Harmer
2.664
960971AF2-388 GEN
Solar/Wind Harmer
5.197
270599AE1-208 GEN
Solar/Wind Harmer
7.961
970883AG2-550 GEN
Solar/Wind Harmer
8.648
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
274887GEN-1.85
Solar/Wind Harmer
0.224
274803UNIV PARK;6U
Adder
7.1
24728905RICHG2
Adder
4.598
274674JOLIET 9 ;6U
Adder
18.689
961051AF2-396 GEN
Solar/Wind Harmer
16.913
961051AF2-396 GEN
Solar/Wind Harmer
11.276
958481AF2-142 GEN
Solar/Wind Harmer
12.626
274862TOP CROP ;2U
Solar/Wind Harmer
1.139
274693ROCKY RD ;1P
Adder
13.284
274683WAUKEGAN ;8U
Adder
25.365
274683WAUKEGAN ;8U
Adder
21.381
966841AG1-555 GEN
Solar/Wind Harmer
0.948
970921AG2-575 GEN
Solar/Wind Harmer
8.38
970921AG2-575 GEN
Solar/Wind Harmer
2.793
274879MINONK ;1U
Solar/Wind Harmer
0.353
25194408D.CRK1
Adder
9.077
971335AH1-147 GEN
Solar/Wind Harmer
16.689
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
946071AF1-272 GEN
Solar/Wind Helper
2.567
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.346
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20398826ARMNA MT
Solar/Wind Helper
1.407
274731ELWOOD EC;2P
Adder
19.951
274733ELWOOD EC;3P
Adder
19.951
274746AC1-111 G10
Adder
6.762
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
25196508WSDLE4
Adder
10.2
24386205FR-12G C
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.979
963841AG1-237 GEN
Solar/Wind Harmer
3.615
926823AC1-168 GEN
Solar/Wind Harmer
1.415
254304AE2-114 C
Solar/Wind Helper
0.214
241982AE2-343 S C
Solar/Wind Helper
0.217
23750501ELLIOTTS
Solar/Wind Helper
0.61
203961AE2-224 GEN
Solar/Wind Helper
2.278
270161DARBY CT6
50/50
0.725
942861AE2-305 GEN
Solar/Wind Harmer
8.094
270518AE2-148 GEN
Solar/Wind Harmer
0.847
970329AG2-216 GEN
Solar/Wind Harmer
4.005
25326109MON D
Adder
1.698
944541AF1-119 GEN
Solar/Wind Harmer
0.594
270031AE2-169
Solar/Wind Harmer
4.777
270201AC2-176 GEN
Solar/Wind Harmer
0.002
964611AG1-324 GEN
Solar/Wind Harmer
0.65
970885AG2-551 GEN
Solar/Wind Harmer
2.883
960441AF2-335 GEN
Solar/Wind Harmer
8.628
270383AD1-128 GEN
Solar/Wind Harmer
0.005
24379505HDWTR1G C
Solar/Wind Harmer
0.003
965791AG1-447 GEN
Solar/Wind Harmer
7.878
247620Y3-023
Adder
0.565
270526AF1-158 GEN
Solar/Wind Harmer
0.011
270156DARBY CT1
50/50
13.713
270157DARBY CT2
50/50
13.679
270459AD2-067 GEN
Solar/Wind Harmer
0
24729505KEY G4
Adder
8.316
270071AF1-092 GEN
Solar/Wind Harmer
17.084
270435AC2-044 GEN
Solar/Wind Harmer
1.103
270543AE2-219 C
Solar/Wind Harmer
0.005
971673AH1-337 GEN
Solar/Wind Harmer
5.609
270594AE1-207 GEN
Solar/Wind Harmer
9.648
270240V3-007_GEN2
Solar/Wind Harmer
0.003
971771AH1-392 GEN
Solar/Wind Harmer
8.573
971769AH1-391 GEN
Solar/Wind Harmer
9.561
247607V1-011 GEN
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
19.951
24691005MDL-2G C
Solar/Wind Harmer
0.002
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.608
25196308WSDLE2
Adder
10.516
25196208WSDLE1
Adder
10.49
25196708WSDLE6
Adder
10.463
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
5.154
238126S14_GEN_1
Solar/Wind Helper
0.64
941231AE2-117 GEN
Solar/Wind Helper
0.447
24441505OLIV SLR
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.275
958011AF2-095 GEN
Solar/Wind Harmer
12.235
24728805RICHG1
Adder
4.598
945421AF1-207 GEN
Solar/Wind Harmer
0.001
971573AH1-285 GEN
Solar/Wind Harmer
1.571
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274695ROCKY RD ;2P
Adder
13.416
25183208HLCRTG
Solar/Wind Harmer
0.013
958491AF2-143 GEN
Solar/Wind Harmer
12.583
25194508D.CRK3
Adder
1.697
942991AE2-321 GEN
Solar/Wind Harmer
9.334
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
16.689
20088926STNY CRK
Solar/Wind Helper
0.77
20088626ARWF_N39
Solar/Wind Helper
1.147
946381AF1-302 GEN
Solar/Wind Helper
0.21
203946AE2-131 C
Solar/Wind Helper
0.448
238217AF1-153 C O1
Solar/Wind Helper
0.223
270159DARBY CT4
50/50
13.494
970149AG2-104 GEN
Solar/Wind Harmer
54.635
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970593AG2-378 GEN
Solar/Wind Harmer
2.27
253325AC1-069 GEN
Solar/Wind Harmer
0.015
270263AC1-001 GEN
Solar/Wind Harmer
0.865
970373AG2-245 GEN
Solar/Wind Harmer
17.958
971917AH1-482 GEN
Solar/Wind Harmer
11.064
941551AE2-152 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.492
24791305MDL-5G
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.404
276691AA1-018 GEN1
Solar/Wind Harmer
1.02
274872LEEDK;1U
Solar/Wind Harmer
0.005
959081AF2-199 GEN
Solar/Wind Harmer
8.33
971067AG2-660 GEN
Solar/Wind Harmer
2.777
274822ROCKFORD ;11
Adder
23.399
963741AG1-226 GEN
Solar/Wind Harmer
19.652
20094526CT_V3-030
Solar/Wind Helper
0.446
235054AD2-180 GEN
Solar/Wind Helper
1.566
235531U2-073 GEN
Solar/Wind Helper
2.545
203954AE2-126 C
Solar/Wind Helper
0.443
970819AG2-516 GEN
Solar/Wind Harmer
7.858
962771AG1-126 GEN
Solar/Wind Harmer
50.586
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
253383AE2-342_GEN
Solar/Wind Harmer
0.004
241973AD2-163_GEN1
Solar/Wind Harmer
0.008
943861AF1-054 GEN
Solar/Wind Harmer
3.995
943851AF1-053 GEN
Solar/Wind Harmer
2.767
270302AB2-170 GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
1.38
970689AG2-444 GEN
Solar/Wind Harmer
19.097
253372AE2-315 SEC3
Adder
2.407
253372AE2-315 SEC3
Adder
2.407
25306009OHH W.
Adder
3.647
963791AG1-232 GEN
Solar/Wind Harmer
11.841
270024AE2-089 GEN
Solar/Wind Harmer
0.009
957201AF2-014 GEN
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
1.635
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
274811UNIV PK N;7U
Adder
6.107
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972227AH1-698 GEN1
Adder
3.176
274827FISK ;RP
Adder
9.447
274735ELWOOD EC;4P
Adder
19.951
274744AC1-111 GEN8
Adder
6.762
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970169AG2-114 GEN
Solar/Wind Harmer
8.358
241997AF1-093 GEN
Solar/Wind Helper
0.248
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.985
203993AD2-133_GEN1
Solar/Wind Helper
0.985
203804AE2-113_GEN
Solar/Wind Helper
1.639
270051AF1-062 GEN
50/50
17.076
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
5.712
965021AG1-366 GEN
Solar/Wind Harmer
2.96
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.019
274772LINCOLN ;3U
Adder
10.354
274724RIVER EC ;11
Adder
21.639
970941AG2-585 GEN
Solar/Wind Harmer
10.621
274802UNIV PARK;5U
Adder
7.1
274800UNIV PARK;3U
Adder
7.097
276897AD1-100 C
Solar/Wind Harmer
0.011
945111AF1-176 GEN
Solar/Wind Harmer
6.882
274729ELWOOD EC;1P
Adder
19.951
276893AG1-478 C
Solar/Wind Harmer
0.336
276805AD2-038 GEN
Solar/Wind Harmer
0.002
252510AF1-249 C
Solar/Wind Harmer
0.065
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.891
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274850MENDOTA H;RU
Solar/Wind Harmer
0.098
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.15
24441205WTRV SLR C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
16.64
237048AF1-022 C
Solar/Wind Helper
0.176
237043AE2-125 C
Solar/Wind Helper
0.172
962101AG1-054 GEN
Solar/Wind Helper
0.632
944781AF1-143 GEN
Solar/Wind Helper
2.312
203940AF1-140 C
Solar/Wind Helper
0.374
238118U2-030_1
Solar/Wind Helper
0.269
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.268
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.737
LGEELTFEXP_LGEE->PJM
CLTF
7.674
MECLTFEXP_MEC->PJM
CLTF
18.875
AH1-155LTFEXP_AH1-155->PJM
LTF
0.424
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.409
WECLTFEXP_WEC->PJM
CLTF
4.549
LAGNLTFEXP_LAGN->PJM
CLTF
17.886
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.754
NYPJM->LTFIMP_NY
CLTF
5.332
TVALTFEXP_TVA->PJM
CLTF
8.721
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.768
CPLELTFEXP_CPLE->PJM
CLTF
2.705
SIGELTFEXP_SIGE->PJM
CLTF
0.583

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6388.32
MW Contribution:2.43
Bus #Bus NameTypeMW Contribution
24686505CER G6
Adder
15.608
962761AG1-125 GEN
Solar/Wind Harmer
46.194
24318705GVG2
50/50
11.615
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
971315AH1-136 GEN
Solar/Wind Harmer
2.232
971687AH1-348 GEN
Solar/Wind Harmer
1.067
970333AG2-219 GEN
Solar/Wind Harmer
7.406
25196808ZIMRHP
Adder
109.116
25196008MFTGT1
Adder
1.989
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
6.831
252507AC2-088 GEN
Solar/Wind Harmer
0.46
339216AC1-074 GEN
Solar/Wind Harmer
0.274
3429241JKCT 3G
Adder
16.894
276903AD2-071 C
Solar/Wind Harmer
10.574
25326309TAIT D
Adder
1.481
24385905FR-11G C
Solar/Wind Harmer
0.002
970245AG2-165 GEN
Solar/Wind Harmer
4.056
962241AG1-070 GEN
Solar/Wind Harmer
5.098
965911AG1-460 GEN
Solar/Wind Harmer
1.861
247536S-71 GEN
Solar/Wind Harmer
0.374
276615X2-022 GEN
Solar/Wind Harmer
0.098
963831AG1-236 GEN
Solar/Wind Harmer
3.623
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.864
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274766LEE CO EC;7U
Adder
12.032
238117U2-030
Solar/Wind Helper
0.343
20088826HIGHLAND
Solar/Wind Helper
1.011
964391AG1-301 GEN
Solar/Wind Helper
0.529
961331AF2-424 GEN
Solar/Wind Helper
0.499
963161AG1-165 GEN
Solar/Wind Helper
0.496
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
20720528MAN_W1-024
Solar/Wind Helper
0.03
219276PARKLANDSO C
Solar/Wind Helper
0.095
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270399AC1-101 GEN
Solar/Wind Harmer
3.805
972143AH1-644 GEN
Solar/Wind Harmer
11.827
971985AH1-537 GEN
Solar/Wind Harmer
3.245
972165AH1-665 GEN
Solar/Wind Harmer
9.085
24734705WLF1G3
Adder
8.198
24734905WLF1G5
Adder
8.198
339211AE2-254 GEN
Solar/Wind Harmer
0.004
965401AG1-405 GEN
Solar/Wind Harmer
5.522
24725505WLD G2 C
Solar/Wind Harmer
0.002
253349AC2-067 GEN
Solar/Wind Harmer
2.978
24386405FR-21G C
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
14.095
24697605MDL-3G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
5.525
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
7.695
966391AG1-508 GEN
Solar/Wind Harmer
1.427
276868AE1-113 GEN
Solar/Wind Harmer
1.835
274775LINCOLN ;6U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
970833AG2-524 GEN
Solar/Wind Harmer
10.052
970833AG2-524 GEN
Solar/Wind Harmer
6.701
971675AH1-338 GEN
Solar/Wind Harmer
3.562
20092526R32
Solar/Wind Helper
1.311
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
243186AF1-051 GEN
50/50
12.478
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
970947AG2-589 GEN
Solar/Wind Harmer
0.412
970155AG2-107 GEN
Solar/Wind Harmer
29.498
945681AF1-233 GEN
Solar/Wind Harmer
19.197
25194608D.CRK4
Adder
2.348
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.904
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
971821AH1-427 GEN
Solar/Wind Harmer
9.786
24735205WLF2G2
Adder
8.08
24728605AND G2
Adder
5.27
970613AG2-401 GEN
Solar/Wind Harmer
6.984
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970291AG2-192 GEN
Solar/Wind Harmer
1.228
965031AG1-367 GEN
Solar/Wind Harmer
9.442
964901AG1-354 GEN
Solar/Wind Harmer
14.138
960071AF2-298 GEN
Solar/Wind Harmer
4.694
965651AG1-433 GEN
Solar/Wind Harmer
2.727
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274877BISHOP HL;1U
Solar/Wind Harmer
0.308
253343AC1-166 GEN
Solar/Wind Harmer
0.004
276901AD2-066 C O1
Solar/Wind Harmer
0.009
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.316
238185AF2-356 C
Solar/Wind Helper
2.612
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
964201AG1-281 GEN
Solar/Wind Helper
0.544
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
963071AG1-156 GEN
Solar/Wind Helper
1.625
316095T157 G97
Solar/Wind Helper
1.154
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
20714528FRN_Y2-051
Solar/Wind Helper
0.061
20720828JCB_W4-025
Solar/Wind Helper
0.067
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233996TM1833_GEN
Solar/Wind Helper
0.27
232406W1-004 FULL
Solar/Wind Helper
0.523
237030AB1-096 C
Solar/Wind Helper
0.063
957471AF2-041 GEN
Solar/Wind Harmer
5.997
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
970153AG2-106 GEN
Solar/Wind Harmer
29.498
972103AH1-617 GEN
Solar/Wind Harmer
21.835
960911AF2-382 GEN
Solar/Wind Harmer
8.035
25194608D.CRK4
Adder
2.348
253316AC1-085 GEN3
Solar/Wind Harmer
0.006
253433AC1-085 GEN1
Solar/Wind Harmer
0.005
946181AF1-283 GEN
Solar/Wind Harmer
12.875
24728505AND G1
Adder
5.27
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
960741AF2-365 GEN
Solar/Wind Harmer
4.731
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
946031AF1-268 GEN
Solar/Wind Harmer
8.936
24755605MDL-5G
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
10.922
276668AB2-070 GEN1
Solar/Wind Harmer
0.339
943031AE2-326 GEN
Solar/Wind Harmer
4.828
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
943121AE2-341 GEN
Solar/Wind Harmer
15.314
943591AF1-030 GEN
Solar/Wind Harmer
10.184
274767LEE CO EC;8U
Adder
12.032
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
203818AF1-086 GEN
Solar/Wind Helper
1.887
200917MEHOOPANY_G
Solar/Wind Helper
2.428
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
217208PARK ELE C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
20742028HF_AC1-207
Solar/Wind Helper
0.15
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20714828MDF_W3-079
Solar/Wind Helper
0.139
20720728JCB_W1-129
Solar/Wind Helper
0.061
219904AC1-010 C
Solar/Wind Helper
0.064
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
966131AG1-482 GEN
Solar/Wind Helper
0.139
237080AD1-060 GEN
Solar/Wind Helper
0.296
959091AF2-200 GEN
Solar/Wind Harmer
3.998
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
971225AH1-072 GEN
Solar/Wind Harmer
2.13
971227AH1-073 GEN
Solar/Wind Harmer
2.13
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
7.729
971125AH1-004 GEN
Solar/Wind Harmer
3.992
253317AC1-085 GEN4
Solar/Wind Harmer
0.006
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.197
253370AE2-315 SEC1
Adder
2.733
971613AH1-306 GEN
Solar/Wind Harmer
4.531
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
276916AD2-100_GEN
Solar/Wind Harmer
19.555
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.32
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.325
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
238120AE2-309 GEN
Solar/Wind Helper
0.507
241801AE1-079 GEN
Solar/Wind Helper
0.271
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
203952AE2-129 C
Solar/Wind Helper
0.529
209054AE2-059 GEN
Solar/Wind Helper
0.09
203979AG1-198 GEN
Solar/Wind Helper
0.297
203980AG1-197 GEN
Solar/Wind Helper
0.369
964851AG1-348 GEN
Solar/Wind Helper
0.088
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20714928UPF_X1-085
Solar/Wind Helper
0.005
230407AD2-065 C
Solar/Wind Helper
0.042
237025AB1-124 C
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
971341AH1-150 GEN
Solar/Wind Harmer
3.998
971343AH1-151 GEN
Solar/Wind Harmer
3.998
24686205CER G4
Adder
15.547
971461AH1-227 GEN
Solar/Wind Harmer
5.464
970519AG2-331 GEN
Solar/Wind Harmer
26.931
970699AG2-449 GEN
Solar/Wind Harmer
2.59
958171AF2-111 GEN
Solar/Wind Harmer
25.128
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
253406AD2-031_GEN
Solar/Wind Harmer
0.735
270291AC1-194 GEN
Solar/Wind Harmer
7.771
253415AE1-040 GEN
Solar/Wind Harmer
0.004
270273AD2-016 GEN
Solar/Wind Harmer
0.998
24728705AND G3
Adder
11.022
970193AG2-126 GEN
Solar/Wind Harmer
14.303
270437AC2-090 C
Solar/Wind Harmer
0.004
270346AE1-212 GEN
Solar/Wind Harmer
8.4
958821AF2-173 GEN
Solar/Wind Harmer
13.219
970781AG2-491 GEN
Solar/Wind Harmer
9.369
970513AG2-328 GEN
Solar/Wind Harmer
4.056
970517AG2-330 GEN
Solar/Wind Harmer
24.338
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
959611AF2-252 GEN
Solar/Wind Harmer
3.082
944531AF1-118 GEN
Solar/Wind Harmer
41.286
253333AC1-068 GEN
Solar/Wind Harmer
0.014
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
29.848
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.335
23750701CROSSCHOOL
Solar/Wind Helper
1.427
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
238202AE2-262_GEN
Solar/Wind Helper
1.063
941421AE2-139 GEN
Solar/Wind Helper
2.573
209071AE2-133 GEN
Solar/Wind Helper
0.09
212266LOR1
Solar/Wind Helper
0.054
207518AF1-320_GEN
Solar/Wind Helper
1.718
20675428EAM_W2-061
Solar/Wind Helper
0.017
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
963711AG1-223 GEN
Solar/Wind Helper
0.068
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
228728W1-130C
Solar/Wind Helper
0.057
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
233915AB1-141 GEN
Solar/Wind Helper
0.518
972043AH1-570 GEN
Solar/Wind Harmer
2.614
25194408D.CRK1
Adder
10.799
942891AE2-308 GEN
Solar/Wind Harmer
9.954
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
7.154
945391AF1-204 GEN
Solar/Wind Harmer
10.131
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
1.065
971485AH1-239 GEN
Solar/Wind Harmer
7.489
964781AG1-341 GEN
Solar/Wind Harmer
9.922
970883AG2-550 GEN
Solar/Wind Harmer
9.347
270599AE1-208 GEN
Solar/Wind Harmer
8.564
960971AF2-388 GEN
Solar/Wind Harmer
5.453
960611AF2-352 GEN
Solar/Wind Harmer
3.082
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.386
276708O09 GEN2
Solar/Wind Harmer
0.325
274862TOP CROP ;2U
Solar/Wind Harmer
1.236
958481AF2-142 GEN
Solar/Wind Harmer
13.701
972267AH1-718 GEN
Adder
5.45
274693ROCKY RD ;1P
Adder
14.427
274764LEE CO EC;5U
Adder
12.204
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.696
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
208972BECR K09
Solar/Wind Helper
0.372
966111AG1-480 GEN
Solar/Wind Helper
0.082
20674928WA_W3-044
Solar/Wind Helper
0.107
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230433AD2-135 GEN
Solar/Wind Helper
0.018
233970AC1-092 C
Solar/Wind Helper
0.361
232424Y1-079 C
Solar/Wind Helper
0.12
237002AB1-128_GEN
Solar/Wind Helper
0.388
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237006AB1-125 GEN
Solar/Wind Helper
0.109
24721605FLATG1
50/50
2.756
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270400AC1-102 GEN
Solar/Wind Harmer
3.805
24477305BRIDGE
Adder
0.588
941621AE2-160 GEN
Adder
5.057
972163AH1-664 GEN
Solar/Wind Harmer
11.344
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
3429211JKCT 2G
Adder
16.676
25196508WSDLE4
Adder
12.095
24734805WLF1G4
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
0.011
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
6.495
270269AC2-059
Solar/Wind Harmer
0.006
24699105WLD G1 C
Solar/Wind Harmer
0.001
253400AC2-068 GEN
Solar/Wind Harmer
1.198
963841AG1-237 GEN
Solar/Wind Harmer
4.089
970115AG2-085 GEN
Solar/Wind Harmer
3.766
24386205FR-12G C
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.526
270432AC2-029 GEN
Solar/Wind Harmer
4.141
944221AF1-090 GEN
Solar/Wind Harmer
5.475
965101AG1-375 GEN
Solar/Wind Harmer
9.315
276655WTG1_EQ
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
1.003
926823AC1-168 GEN
Solar/Wind Harmer
1.557
276882AE2-255 GEN
Solar/Wind Harmer
1.069
274776LINCOLN ;7U
Adder
11.055
274746AC1-111 G10
Adder
7.316
274731ELWOOD EC;2P
Adder
21.509
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
254304AE2-114 C
Solar/Wind Helper
0.239
241982AE2-343 S C
Solar/Wind Helper
0.243
203961AE2-224 GEN
Solar/Wind Helper
2.707
959421AF2-233 GEN
Solar/Wind Helper
0.5
20675128HRM_W1-127
Solar/Wind Helper
0.032
207530AG1-191 GEN
Solar/Wind Helper
0.072
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
20715728PEM_W1-119
Solar/Wind Helper
0.102
219607WPEMNERT C
Solar/Wind Helper
0.085
219914AD2-027 C
Solar/Wind Helper
0.121
233923SMA
Solar/Wind Helper
0.989
205956AE1-196_GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.307
971313AH1-133 GEN
Solar/Wind Harmer
10.378
270367AC2-061_GEN
Solar/Wind Harmer
0.008
970879AG2-548 GEN
Solar/Wind Harmer
9.191
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
270132AB1-180 C
Adder
0.17
965411AG1-406 GEN
Solar/Wind Harmer
3.552
971061AG2-657 GEN
Solar/Wind Harmer
6.031
270240V3-007_GEN2
Solar/Wind Harmer
0.003
270594AE1-207 GEN
Solar/Wind Harmer
10.572
971673AH1-337 GEN
Solar/Wind Harmer
6.118
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
24691005MDL-2G C
Solar/Wind Harmer
0.002
270543AE2-219 C
Solar/Wind Harmer
0.006
276174W4-005 GEN2
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
8.586
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
957751AF2-069 GEN
Solar/Wind Harmer
0.302
944971AF1-162 GEN
Solar/Wind Harmer
12.174
24728205BUCHG1
Adder
6.831
971073AG2-665 GEN
Solar/Wind Harmer
9.191
252509AD1-136 GEN
Solar/Wind Harmer
0.051
339221AD2-048_GEN
Solar/Wind Harmer
0.006
972045AH1-571 GEN
Solar/Wind Harmer
2.094
25183208HLCRTG
Solar/Wind Harmer
0.016
25194508D.CRK3
Adder
2.019
964571AG1-320 GEN
Solar/Wind Harmer
8.854
970653AG2-424 GEN
Solar/Wind Harmer
4.654
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270383AD1-128 GEN
Solar/Wind Harmer
0.006
960441AF2-335 GEN
Solar/Wind Harmer
9.416
339255AE2-071 GEN
Solar/Wind Harmer
-0.154
966021AG1-471 GEN
Solar/Wind Harmer
5.054
25326109MON D
Adder
1.763
970885AG2-551 GEN
Solar/Wind Harmer
3.116
945421AF1-207 GEN
Solar/Wind Harmer
0.001
270031AE2-169
Solar/Wind Harmer
5.138
276911AD2-131_GEN
Solar/Wind Harmer
1.288
944541AF1-119 GEN
Solar/Wind Harmer
0.623
964611AG1-324 GEN
Solar/Wind Harmer
0.696
270201AC2-176 GEN
Solar/Wind Harmer
0.002
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
958491AF2-143 GEN
Solar/Wind Harmer
13.709
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.702
274695ROCKY RD ;2P
Adder
14.57
274765LEE CO EC;6U
Adder
12.204
274763LEE CO EC;4U
Adder
12.06
20088926STNY CRK
Solar/Wind Helper
0.928
20088626ARWF_N39
Solar/Wind Helper
1.362
946381AF1-302 GEN
Solar/Wind Helper
0.246
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
946751AF1-339 GEN
Solar/Wind Helper
0.5
209029WAYMART-WD
Solar/Wind Helper
0.937
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
20674128FR_U2-059
Solar/Wind Helper
0.004
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20720628TIN_W1-124
Solar/Wind Helper
0.203
233901CHERRYDALE C
Solar/Wind Helper
0.24
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
235063AE1-101 C2
Solar/Wind Helper
1.463
237001AB1-127_GEN
Solar/Wind Helper
0.388
237034AC2-136 C
Solar/Wind Helper
0.194
24289405MTG1
50/50
11.351
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
971403AH1-188 GEN
Solar/Wind Harmer
16.785
970149AG2-104 GEN
Solar/Wind Harmer
49.891
927014AC1-188 GEN
Solar/Wind Harmer
0.007
970091AG2-072 GEN
Adder
113.581
3429421JKCT 10G
Adder
11.865
270263AC1-001 GEN
Solar/Wind Harmer
0.987
971565AH1-281 GEN
Solar/Wind Harmer
1.958
970773AG2-487 GEN
Solar/Wind Harmer
1.7
970273AG2-179 GEN
Solar/Wind Harmer
3.322
963741AG1-226 GEN
Solar/Wind Harmer
22.385
24791305MDL-5G
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
276726Z2-087_GEN
Solar/Wind Harmer
0.003
971917AH1-482 GEN
Solar/Wind Harmer
11.983
253325AC1-069 GEN
Solar/Wind Harmer
0.014
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274872LEEDK;1U
Solar/Wind Harmer
0.006
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
235531U2-073 GEN
Solar/Wind Helper
3.23
20094526CT_V3-030
Solar/Wind Helper
0.53
238108AE1-109 GEN1
Solar/Wind Helper
0.102
203954AE2-126 C
Solar/Wind Helper
0.522
957921AF2-086 GEN
Solar/Wind Helper
0.493
217211CAMDEN ST C
Solar/Wind Helper
0.005
219249CENTRALDIV C
Solar/Wind Helper
0.011
20715028HAN_X4-015
Solar/Wind Helper
0.061
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
228729W2-030 C
Solar/Wind Helper
0.116
233971AC1-093 C
Solar/Wind Helper
0.369
233997TMININ_4.2
Solar/Wind Helper
0.27
233994AC2-023 GEN
Solar/Wind Helper
0.992
233918AB1-142 GEN
Solar/Wind Helper
0.518
205917AD1-020 ES
Solar/Wind Helper
0.368
959081AF2-199 GEN
Solar/Wind Harmer
1.999
971067AG2-660 GEN
Solar/Wind Harmer
0.666
972203AH1-686 GEN
Adder
4.425
962771AG1-126 GEN
Solar/Wind Harmer
46.194
970281AG2-184 GEN
Solar/Wind Harmer
22.926
252524AE2-267 GEN
Solar/Wind Harmer
0.004
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
970289AG2-191 GEN
Solar/Wind Harmer
1.794
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.339
276848AB2-070 GEN3
Solar/Wind Harmer
0.337
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
9.696
970169AG2-114 GEN
Solar/Wind Harmer
9.2
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
274744AC1-111 GEN8
Adder
7.316
961011AF2-392 GEN
Solar/Wind Harmer
5.358
241997AF1-093 GEN
Solar/Wind Helper
0.28
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
203804AE2-113_GEN
Solar/Wind Helper
1.924
207408W3-077 C
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
966261AG1-495 GEN
Solar/Wind Helper
0.088
959381AF2-229 GEN
Solar/Wind Helper
0.364
234033AF1-007_GEN
Solar/Wind Helper
7.245
24318705GVG2
50/50
11.615
971191AH1-055 GEN
Solar/Wind Harmer
30.005
970243AG2-164 GEN
Solar/Wind Harmer
6.06
972167AH1-666 GEN
Solar/Wind Harmer
8.145
252510AF1-249 C
Solar/Wind Harmer
0.077
25196008MFTGT1
Adder
1.926
970093AG2-073 GEN
Solar/Wind Harmer
9.929
966571AG1-526 GEN
Solar/Wind Harmer
21.864
972273AH1-721 GEN
Adder
114.731
942481AE2-261 GEN
Solar/Wind Harmer
27.825
276621W2-048 GEN
Solar/Wind Harmer
0.469
276838X2-022 GEN2
Solar/Wind Harmer
0.523
971993AH1-541 GEN
Solar/Wind Harmer
4.291
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.864
942111AE2-223 GEN
Solar/Wind Harmer
3.001
970571AG2-364 GEN
Solar/Wind Harmer
18.307
276889AE2-281 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.012
274772LINCOLN ;3U
Adder
11.055
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276157O29GEN1
Solar/Wind Harmer
1.478
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.974
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
946731AF1-337 GEN
Solar/Wind Helper
0.5
20671928W4-073
Solar/Wind Helper
0.098
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
219907AC1-030 C
Solar/Wind Helper
0.036
219258KINSLEYDEP C
Solar/Wind Helper
0.081
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233954AC2-188 GEN
Solar/Wind Helper
0.24
233930AB2-032 GEN
Solar/Wind Helper
0.392
970239AG2-162 GEN
Solar/Wind Harmer
2.59
270186AC1-089 GEN
Solar/Wind Harmer
0.006
962581AG1-107 GEN
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
6.771
970235AG2-159 GEN
Solar/Wind Harmer
6.108
970235AG2-159 GEN
Solar/Wind Harmer
3.504
970107AG2-081 GEN
Solar/Wind Harmer
2.994
253394AE2-221_GEN
Solar/Wind Harmer
0.012
253398AE2-221_GEN2
Solar/Wind Harmer
0.012
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
5.517
970825AG2-519 GEN
Solar/Wind Harmer
10.439
970321AG2-212 GEN
Solar/Wind Harmer
4.056
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
972259AH1-714 GEN
Adder
24.976
276603SUBLETTE C
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.914
274762LEE CO EC;3U
Adder
12.175
274697ROCKY RD ;3P
Adder
3.958
944781AF1-143 GEN
Solar/Wind Helper
2.836
962101AG1-054 GEN
Solar/Wind Helper
0.715
241985AE1-237 GEN
Solar/Wind Helper
0.271
203940AF1-140 C
Solar/Wind Helper
0.446
961431AF2-434 GEN
Solar/Wind Helper
0.499
207471AF2-354 C
Solar/Wind Helper
0.184
20676228FRD_X1-012
Solar/Wind Helper
0.1
217081WEATEXAS C
Solar/Wind Helper
0.014
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
20716928W4-060COL
Solar/Wind Helper
0.055
963391AG1-188 GEN
Solar/Wind Helper
0.088
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
233939AC1-091 C
Solar/Wind Helper
0.361
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
233944AB2-135 GEN
Solar/Wind Helper
0.607
233933AB2-153 GEN
Solar/Wind Helper
0.24
205916AD1-020 GEN
Solar/Wind Helper
1.711
235020AA1-095 C
Solar/Wind Helper
0.045
238175AF1-290_GEN
Solar/Wind Helper
0.123
238126S14_GEN_1
Solar/Wind Helper
0.81
941231AE2-117 GEN
Solar/Wind Helper
0.53
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
20675928HOL_W4-097
Solar/Wind Helper
0.055
219272CLEANLIGHT C
Solar/Wind Helper
0.027
228754AB1-001 C
Solar/Wind Helper
0.027
237085AD2-009_GEN
Solar/Wind Helper
1.449
959431AF2-234 GEN
Solar/Wind Helper
1
961261AF2-417 GEN
Solar/Wind Helper
0.495
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
227927V4-067C
Solar/Wind Helper
0.011
964001AG1-254 GEN
Solar/Wind Helper
1.003
233990AG1-397 GEN
Solar/Wind Helper
0.279
205943AE1-185 GEN
Solar/Wind Helper
0.523
971171AH1-044 GEN
Solar/Wind Harmer
3.998
235062AE1-101 C1
Solar/Wind Helper
1.463
223401AF1-299 GEN
Solar/Wind Helper
0.338
24289405MTG1
50/50
11.351
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
2.748
970913AG2-568 GEN
Solar/Wind Harmer
8.769
972173AH1-669 GEN
Solar/Wind Harmer
4.843
270222AC2-111 GEN
Solar/Wind Harmer
4.893
270356AE2-297 GEN
Solar/Wind Harmer
0.013
970273AG2-179 GEN
Solar/Wind Harmer
5.694
970191AG2-125 GEN
Solar/Wind Harmer
2.433
270004AE1-209 GEN
Solar/Wind Harmer
2.046
339250AF1-203 GEN
Solar/Wind Harmer
0.001
962251AG1-071 GEN
Solar/Wind Harmer
5.847
276686W4-005 GEN3
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
27.736
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274878BISHOP HL;2U
Solar/Wind Harmer
0.308
253338AC1-165 GEN
Solar/Wind Harmer
0.004
274760LEE CO EC;1U
Adder
12.175
238118U2-030_1
Solar/Wind Helper
0.343
20089126CSLMN_L13
Solar/Wind Helper
0.683
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
959441AF2-235 GEN
Solar/Wind Helper
0.255
232432Z2-076 GEN
Solar/Wind Helper
0.069
205932AD2-116_GEN
Solar/Wind Helper
0.523
960921AF2-383 GEN
Solar/Wind Helper
0.373
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
961301AF2-421 GEN
Solar/Wind Helper
0.496
963151AG1-164 GEN
Solar/Wind Helper
0.496
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
962511AG1-100 GEN
Solar/Wind Helper
0.488
207445AB1-138_GEN
Solar/Wind Helper
0.111
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
237038AE2-054 C
Solar/Wind Helper
0.238
23779801AA1-109
Solar/Wind Helper
0.168
234015AF2-250 C
Solar/Wind Helper
0.039
235067AD1-061 GEN
Solar/Wind Helper
0.433
270239V3-007_GEN1
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
2.046
270032AE2-172
Solar/Wind Harmer
6.293
970825AG2-519 GEN
Solar/Wind Harmer
3.343
24387305FR-4G C
Solar/Wind Harmer
0.004
945371AF1-202 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
4.037
274880W4-005 GEN4
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.601
972175AH1-670 GEN
Solar/Wind Harmer
7.662
939741AE1-205 GEN
Solar/Wind Harmer
12.928
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
970569AG2-363 GEN
Solar/Wind Harmer
27.46
971997AH1-543 GEN
Solar/Wind Harmer
4.802
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.164
274761LEE CO EC;2U
Adder
12.175
237046AF1-021 C
Solar/Wind Helper
0.577
23751201ROTHROCK
Solar/Wind Helper
0.878
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
946691AF1-333 GEN
Solar/Wind Helper
0.5
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
207510AF2-138 C
Solar/Wind Helper
0.088
20673728F2S_V4-070
Solar/Wind Helper
0.032
219908AB1-139 C
Solar/Wind Helper
0.079
219612MATRIX C
Solar/Wind Helper
0.025
20716028EGP_W2-019
Solar/Wind Helper
0.02
219623KINSLEYBEA C
Solar/Wind Helper
0.002
233952AC2-187 GEN
Solar/Wind Helper
0.24
233940AF2-379 C
Solar/Wind Helper
0.064
233982AB2-133 GEN
Solar/Wind Helper
0.369
238221AF1-254 C O1
Solar/Wind Helper
0.236
223402AF1-300 C
Solar/Wind Helper
0.338
957141AF2-008_MTX
Adder
81.782
944201AF1-088_MTX
Adder
163.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
CPLELTFEXP_CPLE->PJM
CLTF
6.557
SIGELTFEXP_SIGE->PJM
CLTF
0.729
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
NYPJM->LTFIMP_NY
CLTF
6.276
TVALTFEXP_TVA->PJM
CLTF
12.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
WECLTFEXP_WEC->PJM
CLTF
5.002
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156
LGEELTFEXP_LGEE->PJM
CLTF
9.844
MECLTFEXP_MEC->PJM
CLTF
21.939
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.86 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4961.85
MW Contribution:1.65
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
11.679
24721805FLATG3
50/50
2.473
24721705FLATG2
50/50
45.331
24723205RIVRG3
Adder
32.794
24686105CER G3
Adder
14.139
970947AG2-589 GEN
Solar/Wind Harmer
0.368
24735205WLF2G2
Adder
7.162
945681AF1-233 GEN
Solar/Wind Harmer
14.563
971821AH1-427 GEN
Solar/Wind Harmer
7.658
964901AG1-354 GEN
Solar/Wind Harmer
11.154
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
1.71
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.086
970155AG2-107 GEN
Solar/Wind Harmer
17.538
270336AE1-100 GEN
Solar/Wind Harmer
0.004
24728605AND G2
Adder
3.761
971367AH1-164 GEN
Solar/Wind Harmer
2.344
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
970613AG2-401 GEN
Solar/Wind Harmer
4.849
970291AG2-192 GEN
Solar/Wind Harmer
0.846
965031AG1-367 GEN
Solar/Wind Harmer
6.485
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
274877BISHOP HL;1U
Solar/Wind Harmer
0.214
960071AF2-298 GEN
Solar/Wind Harmer
3.157
957471AF2-041 GEN
Solar/Wind Harmer
18.878
274828WAUKEGAN ;BP
Adder
9.895
274682WAUKEGAN ;7U
Adder
16.093
274745AC1-111 GEN9
Adder
4.992
238185AF2-356 C
Solar/Wind Helper
1.954
24722005FLATG5
50/50
2.473
24721905FLATG4
50/50
45.331
960911AF2-382 GEN
Solar/Wind Harmer
7.284
972103AH1-617 GEN
Solar/Wind Harmer
19.189
943031AE2-326 GEN
Solar/Wind Harmer
4.498
960741AF2-365 GEN
Solar/Wind Harmer
3.705
971155AH1-034 GEN
Solar/Wind Harmer
8.639
25194608D.CRK4
Adder
1.71
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.211
970153AG2-106 GEN
Solar/Wind Harmer
17.538
24728505AND G1
Adder
3.761
270030AE2-140 GEN
Solar/Wind Harmer
13.595
276668AB2-070 GEN1
Solar/Wind Harmer
0.24
247642Z2-115 C
Solar/Wind Harmer
0.003
24755605MDL-5G
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.716
243186AF1-051 GEN
50/50
11.679
24723005RIVRG1
Adder
32.794
24723105RIVRG2
Adder
32.794
24685805CER G1
Adder
14.046
24685905CER G2
Adder
14.046
971225AH1-072 GEN
Solar/Wind Harmer
1.893
971227AH1-073 GEN
Solar/Wind Harmer
1.893
270583AD2-179 GEN
Solar/Wind Harmer
7.911
971125AH1-004 GEN
Solar/Wind Harmer
3.056
252519AF1-045_GEN
Solar/Wind Harmer
6.373
252516AE2-318_GEN
Solar/Wind Harmer
5.653
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.336
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276916AD2-100_GEN
Solar/Wind Harmer
14.016
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.122
253370AE2-315 SEC1
Adder
1.856
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.226
25322209TAIT E
Adder
8.86
25322209TAIT E
Adder
8.661
971341AH1-150 GEN
Solar/Wind Harmer
12.585
971343AH1-151 GEN
Solar/Wind Harmer
12.585
247621Y3-024
Adder
0.216
942891AE2-308 GEN
Solar/Wind Harmer
7.714
972043AH1-570 GEN
Solar/Wind Harmer
1.999
971485AH1-239 GEN
Solar/Wind Harmer
5.998
24721605FLATG1
50/50
2.473
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
24477305BRIDGE
Adder
0.546
270400AC1-102 GEN
Solar/Wind Harmer
3.444
941621AE2-160 GEN
Adder
4.703
24734805WLF1G4
Adder
7.306
24735105WLF2G1
Adder
7.162
972163AH1-664 GEN
Solar/Wind Harmer
8.62
944971AF1-162 GEN
Solar/Wind Harmer
11.031
24728205BUCHG1
Adder
6.221
971277AH1-098 GEN
Solar/Wind Harmer
3.403
971073AG2-665 GEN
Solar/Wind Harmer
7.21
972045AH1-571 GEN
Solar/Wind Harmer
1.602
339221AD2-048_GEN
Solar/Wind Harmer
0.005
966021AG1-471 GEN
Solar/Wind Harmer
4.054
252509AD1-136 GEN
Solar/Wind Harmer
0.038
970653AG2-424 GEN
Solar/Wind Harmer
3.613
970653AG2-424 GEN
Solar/Wind Harmer
1.872
964571AG1-320 GEN
Solar/Wind Harmer
6.819
339255AE2-071 GEN
Solar/Wind Harmer
-0.122
25183208HLCRTG
Solar/Wind Harmer
0.011
25194508D.CRK3
Adder
1.471
24728805RICHG1
Adder
3.669
276911AD2-131_GEN
Solar/Wind Harmer
0.923
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
6.468
970885AG2-551 GEN
Solar/Wind Harmer
2.125
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.25
270031AE2-169
Solar/Wind Harmer
3.492
274765LEE CO EC;6U
Adder
8.452
274763LEE CO EC;4U
Adder
8.352
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274695ROCKY RD ;2P
Adder
9.971
24289405MTG1
50/50
10.907
971403AH1-188 GEN
Solar/Wind Harmer
15.305
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.005
971329AH1-144 GEN
Solar/Wind Harmer
6.901
970091AG2-072 GEN
Adder
86.947
3429421JKCT 10G
Adder
9.139
970273AG2-179 GEN
Solar/Wind Harmer
2.644
971565AH1-281 GEN
Solar/Wind Harmer
1.508
970149AG2-104 GEN
Solar/Wind Harmer
29.663
270263AC1-001 GEN
Solar/Wind Harmer
0.699
970773AG2-487 GEN
Solar/Wind Harmer
1.204
963741AG1-226 GEN
Solar/Wind Harmer
15.844
24791305MDL-5G
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
971475AH1-234 GEN
Solar/Wind Harmer
3.061
970819AG2-516 GEN
Solar/Wind Harmer
7.565
274822ROCKFORD ;11
Adder
17.71
24318705GVG2
50/50
10.872
971191AH1-055 GEN
Solar/Wind Harmer
25.624
970243AG2-164 GEN
Solar/Wind Harmer
4.588
970093AG2-073 GEN
Solar/Wind Harmer
7.734
972167AH1-666 GEN
Solar/Wind Harmer
6.174
972273AH1-721 GEN
Adder
91.659
966571AG1-526 GEN
Solar/Wind Harmer
17.032
25196008MFTGT1
Adder
1.418
252510AF1-249 C
Solar/Wind Harmer
0.056
942481AE2-261 GEN
Solar/Wind Harmer
19.91
276621W2-048 GEN
Solar/Wind Harmer
0.333
276838X2-022 GEN2
Solar/Wind Harmer
0.372
971993AH1-541 GEN
Solar/Wind Harmer
3.038
942111AE2-223 GEN
Solar/Wind Harmer
2.091
276157O29GEN1
Solar/Wind Harmer
1.026
970571AG2-364 GEN
Solar/Wind Harmer
12.648
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274729ELWOOD EC;1P
Adder
6.64
237048AF1-022 C
Solar/Wind Helper
0.172
237043AE2-125 C
Solar/Wind Helper
0.155
960161AF2-307 GEN
Solar/Wind Harmer
5.337
270186AC1-089 GEN
Solar/Wind Harmer
0.005
970239AG2-162 GEN
Solar/Wind Harmer
1.961
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970107AG2-081 GEN
Solar/Wind Harmer
2.292
970235AG2-159 GEN
Solar/Wind Harmer
4.628
970235AG2-159 GEN
Solar/Wind Harmer
2.656
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
970241AG2-163 GEN
Solar/Wind Harmer
3.905
270209AC1-174_GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.169
276645AC1-214 GEN1
Solar/Wind Harmer
0.25
276603SUBLETTE C
Solar/Wind Harmer
0
274762LEE CO EC;3U
Adder
8.432
938861AE1-114 GEN
Solar/Wind Harmer
3.58
274856ECOGROVE ;U1
Solar/Wind Harmer
0.149
276611AD2-172 GEN
Solar/Wind Harmer
0.002
274696ROCKY RD ;4P
Adder
10.207
274697ROCKY RD ;3P
Adder
2.709
970321AG2-212 GEN
Solar/Wind Harmer
1.358
971313AH1-133 GEN
Solar/Wind Harmer
9.492
270132AB1-180 C
Adder
0.159
971061AG2-657 GEN
Solar/Wind Harmer
5.654
970879AG2-548 GEN
Solar/Wind Harmer
7.21
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965411AG1-406 GEN
Solar/Wind Harmer
2.821
25196108MFTGT2
Adder
1.614
25196108MFTGT2
Adder
1.499
25196408WSDLE3
Adder
9.147
25196308WSDLE2
Adder
9.067
25196208WSDLE1
Adder
9.045
25196708WSDLE6
Adder
9.022
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.284
971673AH1-337 GEN
Solar/Wind Harmer
4.2
270543AE2-219 C
Solar/Wind Harmer
0.004
957751AF2-069 GEN
Solar/Wind Harmer
0.21
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
10.171
276612AE2-035 GEN
Solar/Wind Harmer
0.002
971081AG2-670 GEN
Solar/Wind Harmer
5.621
964781AG1-341 GEN
Solar/Wind Harmer
7.848
25194408D.CRK1
Adder
7.868
945391AF1-204 GEN
Solar/Wind Harmer
7.288
24728905RICHG2
Adder
3.669
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.746
960611AF2-352 GEN
Solar/Wind Harmer
2.156
970883AG2-550 GEN
Solar/Wind Harmer
6.374
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
5.819
276708O09 GEN2
Solar/Wind Harmer
0.226
972267AH1-718 GEN
Adder
3.783
274764LEE CO EC;5U
Adder
8.452
274683WAUKEGAN ;8U
Adder
18.876
274683WAUKEGAN ;8U
Adder
15.912
274693ROCKY RD ;1P
Adder
9.873
23652301WDPWR_K20
Solar/Wind Helper
0.126
23585401KL_K28_T16
Solar/Wind Helper
1.149
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270399AC1-101 GEN
Solar/Wind Harmer
3.444
972143AH1-644 GEN
Solar/Wind Harmer
10.394
24734705WLF1G3
Adder
7.306
24734905WLF1G5
Adder
7.306
971985AH1-537 GEN
Solar/Wind Harmer
2.617
966391AG1-508 GEN
Solar/Wind Harmer
1.328
971981AH1-535 GEN
Solar/Wind Harmer
5.272
972165AH1-665 GEN
Solar/Wind Harmer
6.904
965401AG1-405 GEN
Solar/Wind Harmer
4.386
339211AE2-254 GEN
Solar/Wind Harmer
0.003
270069AE2-166 C O1
Solar/Wind Harmer
0.005
24386405FR-21G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.661
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
5.363
253349AC2-067 GEN
Solar/Wind Harmer
2.02
946321AF1-296 GEN
Solar/Wind Harmer
3.573
971611AH1-305 GEN
Solar/Wind Harmer
3.799
945581AF1-223 GEN
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.581
971171AH1-044 GEN
Solar/Wind Harmer
12.585
24686205CER G4
Adder
14.065
971461AH1-227 GEN
Solar/Wind Harmer
4.855
270346AE1-212 GEN
Solar/Wind Harmer
7.86
971331AH1-145 GEN
Solar/Wind Harmer
10.953
247619Y1-049
Adder
0.497
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970519AG2-331 GEN
Solar/Wind Harmer
20.392
970699AG2-449 GEN
Solar/Wind Harmer
1.961
3429391JKCT 9G
Adder
9.139
270291AC1-194 GEN
Solar/Wind Harmer
5.957
958171AF2-111 GEN
Solar/Wind Harmer
18.792
25196608WSDLE5
Adder
8.886
253406AD2-031_GEN
Solar/Wind Harmer
0.522
970193AG2-126 GEN
Solar/Wind Harmer
10.289
24728705AND G3
Adder
7.865
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270437AC2-090 C
Solar/Wind Harmer
0.003
970781AG2-491 GEN
Solar/Wind Harmer
6.514
270273AD2-016 GEN
Solar/Wind Harmer
0.675
958821AF2-173 GEN
Solar/Wind Harmer
9.079
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.156
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970513AG2-328 GEN
Solar/Wind Harmer
1.358
970517AG2-330 GEN
Solar/Wind Harmer
8.151
959081AF2-199 GEN
Solar/Wind Harmer
6.293
971067AG2-660 GEN
Solar/Wind Harmer
2.098
971917AH1-482 GEN
Solar/Wind Harmer
8.18
235054AD2-180 GEN
Solar/Wind Helper
1.52
23562501BACKB
Solar/Wind Helper
0.806
3429211JKCT 2G
Adder
12.898
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
5.018
25196508WSDLE4
Adder
8.795
270340AC2-060 GEN
Solar/Wind Harmer
0.008
944221AF1-090 GEN
Solar/Wind Harmer
3.946
963841AG1-237 GEN
Solar/Wind Harmer
2.88
24386205FR-12G C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
2.587
276655WTG1_EQ
Solar/Wind Harmer
0.003
253400AC2-068 GEN
Solar/Wind Harmer
0.812
971609AH1-304 GEN
Solar/Wind Harmer
1.037
926823AC1-168 GEN
Solar/Wind Harmer
1.076
274746AC1-111 G10
Adder
4.992
23750501ELLIOTTS
Solar/Wind Helper
0.594
972203AH1-686 GEN
Adder
3.978
970281AG2-184 GEN
Solar/Wind Harmer
20.149
252524AE2-267 GEN
Solar/Wind Harmer
0.003
962771AG1-126 GEN
Solar/Wind Harmer
27.465
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.24
276848AB2-070 GEN3
Solar/Wind Harmer
0.239
970289AG2-191 GEN
Solar/Wind Harmer
1.237
25306009OHH W.
Adder
2.673
253372AE2-315 SEC3
Adder
1.755
253372AE2-315 SEC3
Adder
1.755
959341AF2-225 GEN
Solar/Wind Harmer
6.757
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
6.359
961011AF2-392 GEN
Solar/Wind Harmer
3.717
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274744AC1-111 GEN8
Adder
4.992
970291AG2-192 GEN
Solar/Wind Harmer
0.651
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
946031AF1-268 GEN
Solar/Wind Harmer
6.117
274767LEE CO EC;8U
Adder
8.332
959091AF2-200 GEN
Solar/Wind Harmer
12.585
274682WAUKEGAN ;7U
Adder
16.093
235058AG1-386 C
Solar/Wind Helper
0.383
24289405MTG1
50/50
10.907
24686405CER G5
Adder
14.009
270053AF1-130 C
Solar/Wind Harmer
2.49
970913AG2-568 GEN
Solar/Wind Harmer
8.136
970273AG2-179 GEN
Solar/Wind Harmer
4.533
339250AF1-203 GEN
Solar/Wind Harmer
0.001
962251AG1-071 GEN
Solar/Wind Harmer
4.615
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270222AC2-111 GEN
Solar/Wind Harmer
3.451
972173AH1-669 GEN
Solar/Wind Harmer
3.31
276686W4-005 GEN3
Solar/Wind Harmer
0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.405
965091AG1-374 GEN
Solar/Wind Harmer
19.404
970191AG2-125 GEN
Solar/Wind Harmer
1.65
965931AG1-462 GEN
Solar/Wind Harmer
16.291
274878BISHOP HL;2U
Solar/Wind Harmer
0.214
274760LEE CO EC;1U
Adder
8.432
972236AH1-702 GEN2
Adder
1.979
24686505CER G6
Adder
14.12
24728305BUCHG2
Adder
6.221
3429241JKCT 3G
Adder
13.068
339216AC1-074 GEN
Solar/Wind Harmer
0.209
252507AC2-088 GEN
Solar/Wind Harmer
0.341
962241AG1-070 GEN
Solar/Wind Harmer
4.025
962761AG1-125 GEN
Solar/Wind Harmer
27.465
965911AG1-460 GEN
Solar/Wind Harmer
1.332
276615X2-022 GEN
Solar/Wind Harmer
0.069
24385905FR-11G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.568
276903AD2-071 C
Solar/Wind Harmer
7.334
25326309TAIT D
Adder
0.995
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
8.332
247536S-71 GEN
Solar/Wind Harmer
0.254
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.276
939401AE1-172 GEN
Solar/Wind Harmer
4.71
970245AG2-165 GEN
Solar/Wind Harmer
1.358
24318705GVG2
50/50
10.872
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
971315AH1-136 GEN
Solar/Wind Harmer
1.928
971687AH1-348 GEN
Solar/Wind Harmer
0.947
970333AG2-219 GEN
Solar/Wind Harmer
5.608
25196808ZIMRHP
Adder
80.408
25196008MFTGT1
Adder
1.465
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0.002
274880W4-005 GEN4
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
5.394
270032AE2-172
Solar/Wind Harmer
4.336
270005AE1-210 C O1
Solar/Wind Harmer
1.405
970825AG2-519 GEN
Solar/Wind Harmer
2.296
939741AE1-205 GEN
Solar/Wind Harmer
9.009
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.976
276158O29GEN2
Solar/Wind Harmer
0.001
970569AG2-363 GEN
Solar/Wind Harmer
18.972
274761LEE CO EC;2U
Adder
8.432
945371AF1-202 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971997AH1-543 GEN
Solar/Wind Harmer
3.301
237046AF1-021 C
Solar/Wind Helper
0.433
23751201ROTHROCK
Solar/Wind Helper
0.662
957141AF2-008_MTX
Adder
60.637
944201AF1-088_MTX
Adder
121.273
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.776
LGEELTFEXP_LGEE->PJM
CLTF
7.503
MECLTFEXP_MEC->PJM
CLTF
15.75
AH1-155LTFEXP_AH1-155->PJM
LTF
0.313
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.98
WECLTFEXP_WEC->PJM
CLTF
3.454
LAGNLTFEXP_LAGN->PJM
CLTF
19.803
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.498
NYPJM->LTFIMP_NY
CLTF
4.59
TVALTFEXP_TVA->PJM
CLTF
10.26
AG2-052LTFEXP_AG2-052->PJM
LTF
0.209
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.164
CPLELTFEXP_CPLE->PJM
CLTF
6.38
SIGELTFEXP_SIGE->PJM
CLTF
0.547

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.56 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5885.34
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.748
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
971225AH1-072 GEN
Solar/Wind Harmer
2.323
971227AH1-073 GEN
Solar/Wind Harmer
2.323
270583AD2-179 GEN
Solar/Wind Harmer
11.403
971125AH1-004 GEN
Solar/Wind Harmer
3.667
252519AF1-045_GEN
Solar/Wind Harmer
7.591
944971AF1-162 GEN
Solar/Wind Harmer
13.01
252516AE2-318_GEN
Solar/Wind Harmer
6.733
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
6.388
24318705GVG2
50/50
11.866
971191AH1-055 GEN
Solar/Wind Harmer
29.418
972273AH1-721 GEN
Adder
111.61
970093AG2-073 GEN
Solar/Wind Harmer
9.318
970243AG2-164 GEN
Solar/Wind Harmer
5.432
966571AG1-526 GEN
Solar/Wind Harmer
20.57
960161AF2-307 GEN
Solar/Wind Harmer
6.387
270186AC1-089 GEN
Solar/Wind Harmer
0.006
970239AG2-162 GEN
Solar/Wind Harmer
2.322
970107AG2-081 GEN
Solar/Wind Harmer
2.751
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970235AG2-159 GEN
Solar/Wind Harmer
5.533
970235AG2-159 GEN
Solar/Wind Harmer
3.174
253394AE2-221_GEN
Solar/Wind Harmer
0.01
253398AE2-221_GEN2
Solar/Wind Harmer
0.01
970241AG2-163 GEN
Solar/Wind Harmer
4.709
270209AC1-174_GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970825AG2-519 GEN
Solar/Wind Harmer
8.658
276645AC1-214 GEN1
Solar/Wind Harmer
0.304
276603SUBLETTE C
Solar/Wind Harmer
0
274762LEE CO EC;3U
Adder
10.252
938861AE1-114 GEN
Solar/Wind Harmer
4.353
274856ECOGROVE ;U1
Solar/Wind Harmer
0.181
276611AD2-172 GEN
Solar/Wind Harmer
0.002
270013AE1-250 PV
Solar/Wind Harmer
0.004
274696ROCKY RD ;4P
Adder
12.409
274697ROCKY RD ;3P
Adder
3.293
944781AF1-143 GEN
Solar/Wind Helper
2.298
203940AF1-140 C
Solar/Wind Helper
0.359
971313AH1-133 GEN
Solar/Wind Harmer
12.016
270132AB1-180 C
Adder
0.198
971061AG2-657 GEN
Solar/Wind Harmer
6.864
970879AG2-548 GEN
Solar/Wind Harmer
8.448
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
0.007
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
270240V3-007_GEN2
Solar/Wind Harmer
0.002
276174W4-005 GEN2
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
8.791
971673AH1-337 GEN
Solar/Wind Harmer
5.07
957751AF2-069 GEN
Solar/Wind Harmer
0.255
270543AE2-219 C
Solar/Wind Harmer
0.005
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
12.366
276612AE2-035 GEN
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.687
942891AE2-308 GEN
Solar/Wind Harmer
9.282
972043AH1-570 GEN
Solar/Wind Harmer
2.394
971485AH1-239 GEN
Solar/Wind Harmer
7.325
971081AG2-670 GEN
Solar/Wind Harmer
6.822
964781AG1-341 GEN
Solar/Wind Harmer
9.557
25194408D.CRK1
Adder
9.381
945391AF1-204 GEN
Solar/Wind Harmer
8.776
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.83
24728905RICHG2
Adder
4.412
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.9
960611AF2-352 GEN
Solar/Wind Harmer
2.614
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276708O09 GEN2
Solar/Wind Harmer
0.275
972267AH1-718 GEN
Adder
4.6
970883AG2-550 GEN
Solar/Wind Harmer
7.705
274764LEE CO EC;5U
Adder
10.276
270599AE1-208 GEN
Solar/Wind Harmer
7.04
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274693ROCKY RD ;1P
Adder
12.003
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
203955AF1-039 C O1
Solar/Wind Helper
0.352
20083426SW_E13_K22
Solar/Wind Helper
0.051
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
270399AC1-101 GEN
Solar/Wind Harmer
4.077
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
966391AG1-508 GEN
Solar/Wind Harmer
1.802
972143AH1-644 GEN
Solar/Wind Harmer
12.573
24734705WLF1G3
Adder
9.185
24734905WLF1G5
Adder
9.185
971985AH1-537 GEN
Solar/Wind Harmer
3.047
971981AH1-535 GEN
Solar/Wind Harmer
6.609
270069AE2-166 C O1
Solar/Wind Harmer
0.007
965401AG1-405 GEN
Solar/Wind Harmer
5.328
339211AE2-254 GEN
Solar/Wind Harmer
0.004
972165AH1-665 GEN
Solar/Wind Harmer
8.229
24386405FR-21G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
6.503
971029AG2-637 GEN
Solar/Wind Harmer
11.666
946321AF1-296 GEN
Solar/Wind Harmer
4.345
253349AC2-067 GEN
Solar/Wind Harmer
2.438
971611AH1-305 GEN
Solar/Wind Harmer
4.596
274823ROCKFORD ;21
Adder
21.377
971171AH1-044 GEN
Solar/Wind Harmer
15.301
971675AH1-338 GEN
Solar/Wind Harmer
2.979
945581AF1-223 GEN
Solar/Wind Harmer
0.001
20092526R32
Solar/Wind Helper
1.053
24686205CER G4
Adder
16.139
971461AH1-227 GEN
Solar/Wind Harmer
5.958
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
270346AE1-212 GEN
Solar/Wind Harmer
10.08
24289405MTG1
50/50
11.79
971403AH1-188 GEN
Solar/Wind Harmer
18.202
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
971329AH1-144 GEN
Solar/Wind Harmer
9.676
927014AC1-188 GEN
Solar/Wind Harmer
0.006
970091AG2-072 GEN
Adder
103.033
3429421JKCT 10G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
3.221
971565AH1-281 GEN
Solar/Wind Harmer
1.817
270263AC1-001 GEN
Solar/Wind Harmer
0.833
970149AG2-104 GEN
Solar/Wind Harmer
34.791
970773AG2-487 GEN
Solar/Wind Harmer
1.447
963741AG1-226 GEN
Solar/Wind Harmer
19.103
24791305MDL-5G
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.003
971475AH1-234 GEN
Solar/Wind Harmer
3.722
24728205BUCHG1
Adder
7.763
971277AH1-098 GEN
Solar/Wind Harmer
4.634
971073AG2-665 GEN
Solar/Wind Harmer
8.448
972045AH1-571 GEN
Solar/Wind Harmer
1.918
339221AD2-048_GEN
Solar/Wind Harmer
0.006
966021AG1-471 GEN
Solar/Wind Harmer
4.953
970653AG2-424 GEN
Solar/Wind Harmer
4.368
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
-0.148
964571AG1-320 GEN
Solar/Wind Harmer
8.226
252509AD1-136 GEN
Solar/Wind Harmer
0.045
25183208HLCRTG
Solar/Wind Harmer
0.014
25194508D.CRK3
Adder
1.754
24728805RICHG1
Adder
4.412
276911AD2-131_GEN
Solar/Wind Harmer
1.118
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270383AD1-128 GEN
Solar/Wind Harmer
0.005
945421AF1-207 GEN
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
7.811
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.304
970885AG2-551 GEN
Solar/Wind Harmer
2.568
274765LEE CO EC;6U
Adder
10.276
274763LEE CO EC;4U
Adder
10.155
270031AE2-169
Solar/Wind Harmer
4.224
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274695ROCKY RD ;2P
Adder
12.123
20088926STNY CRK
Solar/Wind Helper
0.747
24721605FLATG1
50/50
2.714
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270400AC1-102 GEN
Solar/Wind Harmer
4.077
24477305BRIDGE
Adder
0.637
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
941621AE2-160 GEN
Adder
5.66
24734805WLF1G4
Adder
9.185
24735105WLF2G1
Adder
9.002
3429211JKCT 2G
Adder
15.52
972163AH1-664 GEN
Solar/Wind Harmer
10.275
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
6.053
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
0.01
944221AF1-090 GEN
Solar/Wind Harmer
4.776
963841AG1-237 GEN
Solar/Wind Harmer
3.474
24386205FR-12G C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
3.124
276655WTG1_EQ
Solar/Wind Harmer
0.003
253400AC2-068 GEN
Solar/Wind Harmer
0.981
926823AC1-168 GEN
Solar/Wind Harmer
1.307
971609AH1-304 GEN
Solar/Wind Harmer
1.254
274746AC1-111 G10
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
972203AH1-686 GEN
Adder
4.544
970281AG2-184 GEN
Solar/Wind Harmer
24.373
252524AE2-267 GEN
Solar/Wind Harmer
0.003
962771AG1-126 GEN
Solar/Wind Harmer
32.213
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.29
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
970289AG2-191 GEN
Solar/Wind Harmer
1.493
959341AF2-225 GEN
Solar/Wind Harmer
8.194
25306009OHH W.
Adder
3.223
253372AE2-315 SEC3
Adder
2.117
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
276916AD2-100_GEN
Solar/Wind Harmer
16.969
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.767
253370AE2-315 SEC1
Adder
2.238
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.275
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
971341AH1-150 GEN
Solar/Wind Harmer
15.301
971343AH1-151 GEN
Solar/Wind Harmer
15.301
247621Y3-024
Adder
0.262
238120AE2-309 GEN
Solar/Wind Helper
0.43
253372AE2-315 SEC3
Adder
2.117
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
7.718
961011AF2-392 GEN
Solar/Wind Harmer
4.519
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274744AC1-111 GEN8
Adder
6.069
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
960911AF2-382 GEN
Solar/Wind Harmer
9.021
943031AE2-326 GEN
Solar/Wind Harmer
6.109
972103AH1-617 GEN
Solar/Wind Harmer
23.212
270030AE2-140 GEN
Solar/Wind Harmer
18.75
971155AH1-034 GEN
Solar/Wind Harmer
10.521
960741AF2-365 GEN
Solar/Wind Harmer
4.499
25194608D.CRK4
Adder
2.039
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.009
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
20.57
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.29
24755605MDL-5G
Solar/Wind Harmer
0.001
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.864
970291AG2-192 GEN
Solar/Wind Harmer
0.786
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
946031AF1-268 GEN
Solar/Wind Harmer
7.391
3147123OTTER R
Solar/Wind Harmer
0.087
274767LEE CO EC;8U
Adder
10.131
959091AF2-200 GEN
Solar/Wind Harmer
15.301
274682WAUKEGAN ;7U
Adder
19.567
964991AG1-363 GEN
Solar/Wind Helper
3.709
316097T157 G90
Solar/Wind Helper
1.094
970947AG2-589 GEN
Solar/Wind Harmer
0.42
24735205WLF2G2
Adder
9.002
971367AH1-164 GEN
Solar/Wind Harmer
3.536
270336AE1-100 GEN
Solar/Wind Harmer
0.005
971821AH1-427 GEN
Solar/Wind Harmer
9.259
945681AF1-233 GEN
Solar/Wind Harmer
17.357
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
964901AG1-354 GEN
Solar/Wind Harmer
13.566
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
25194608D.CRK4
Adder
2.039
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.469
24728605AND G2
Adder
4.525
970155AG2-107 GEN
Solar/Wind Harmer
20.57
270197AD1-017 GEN1
Solar/Wind Harmer
1.016
941821AE2-187 GEN
Solar/Wind Harmer
4.925
970613AG2-401 GEN
Solar/Wind Harmer
5.842
970291AG2-192 GEN
Solar/Wind Harmer
1.021
965031AG1-367 GEN
Solar/Wind Harmer
7.829
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274877BISHOP HL;1U
Solar/Wind Harmer
0.26
960071AF2-298 GEN
Solar/Wind Harmer
3.815
957471AF2-041 GEN
Solar/Wind Harmer
22.952
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
316095T157 G97
Solar/Wind Helper
1.094
24289405MTG1
50/50
11.79
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
2.937
970913AG2-568 GEN
Solar/Wind Harmer
9.858
270173AC1-122 GEN
Solar/Wind Harmer
0.435
970273AG2-179 GEN
Solar/Wind Harmer
5.522
339250AF1-203 GEN
Solar/Wind Harmer
0.001
962251AG1-071 GEN
Solar/Wind Harmer
5.619
941801AE2-185 GEN
Solar/Wind Harmer
4.925
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.144
276686W4-005 GEN3
Solar/Wind Harmer
0.001
972173AH1-669 GEN
Solar/Wind Harmer
3.965
965091AG1-374 GEN
Solar/Wind Harmer
23.525
270004AE1-209 GEN
Solar/Wind Harmer
1.696
965931AG1-462 GEN
Solar/Wind Harmer
19.808
274878BISHOP HL;2U
Solar/Wind Harmer
0.26
970191AG2-125 GEN
Solar/Wind Harmer
1.992
274760LEE CO EC;1U
Adder
10.252
972236AH1-702 GEN2
Adder
2.406
238118U2-030_1
Solar/Wind Helper
0.288
20089126CSLMN_L13
Solar/Wind Helper
0.554
970819AG2-516 GEN
Solar/Wind Harmer
9.198
274822ROCKFORD ;11
Adder
21.533
959081AF2-199 GEN
Solar/Wind Harmer
7.651
971067AG2-660 GEN
Solar/Wind Harmer
2.55
235054AD2-180 GEN
Solar/Wind Helper
1.695
235531U2-073 GEN
Solar/Wind Helper
2.733
23562501BACKB
Solar/Wind Helper
0.864
238108AE1-109 GEN1
Solar/Wind Helper
0.088
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970519AG2-331 GEN
Solar/Wind Harmer
24.144
970699AG2-449 GEN
Solar/Wind Harmer
2.322
3429391JKCT 9G
Adder
10.993
958171AF2-111 GEN
Solar/Wind Harmer
22.442
270291AC1-194 GEN
Solar/Wind Harmer
7.02
25196608WSDLE5
Adder
10.598
253406AD2-031_GEN
Solar/Wind Harmer
0.624
970193AG2-126 GEN
Solar/Wind Harmer
12.39
24728705AND G3
Adder
9.464
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270437AC2-090 C
Solar/Wind Harmer
0.004
970781AG2-491 GEN
Solar/Wind Harmer
7.866
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.614
958821AF2-173 GEN
Solar/Wind Harmer
10.961
270273AD2-016 GEN
Solar/Wind Harmer
0.81
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274855GSG-6 ;RU
Solar/Wind Harmer
0.28
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238127S14_GEN_2
Solar/Wind Helper
0.687
202652Y1-033 WT C
Solar/Wind Helper
0.534
20089026BF_G21_K23
Solar/Wind Helper
0.438
24686505CER G6
Adder
16.203
24728305BUCHG2
Adder
7.763
3429241JKCT 3G
Adder
15.723
339216AC1-074 GEN
Solar/Wind Harmer
0.25
962241AG1-070 GEN
Solar/Wind Harmer
4.9
252507AC2-088 GEN
Solar/Wind Harmer
0.405
270018AE2-047 C O1
Solar/Wind Harmer
0.004
962761AG1-125 GEN
Solar/Wind Harmer
32.213
965911AG1-460 GEN
Solar/Wind Harmer
1.613
276615X2-022 GEN
Solar/Wind Harmer
0.084
963831AG1-236 GEN
Solar/Wind Harmer
3.11
24385905FR-11G C
Solar/Wind Harmer
0.002
276903AD2-071 C
Solar/Wind Harmer
8.845
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274766LEE CO EC;7U
Adder
10.131
972235AH1-702 GEN1
Adder
2.767
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
25326309TAIT D
Adder
1.202
939401AE1-172 GEN
Solar/Wind Harmer
5.72
238117U2-030
Solar/Wind Helper
0.288
20088826HIGHLAND
Solar/Wind Helper
0.812
972167AH1-666 GEN
Solar/Wind Harmer
7.359
962751AG1-124 GEN
Solar/Wind Harmer
8.092
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.067
3147312GRETNA
Solar/Wind Harmer
0.123
3146802CHATHAM
Solar/Wind Harmer
0.115
942481AE2-261 GEN
Solar/Wind Harmer
24.109
276621W2-048 GEN
Solar/Wind Harmer
0.403
276838X2-022 GEN2
Solar/Wind Harmer
0.45
971993AH1-541 GEN
Solar/Wind Harmer
3.68
942111AE2-223 GEN
Solar/Wind Harmer
2.536
276157O29GEN1
Solar/Wind Harmer
1.248
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
970571AG2-364 GEN
Solar/Wind Harmer
15.368
276889AE2-281 GEN
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
274850MENDOTA H;RU
Solar/Wind Harmer
0.09
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.137
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
237043AE2-125 C
Solar/Wind Helper
0.163
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.329
24318705GVG2
50/50
11.866
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
971687AH1-348 GEN
Solar/Wind Harmer
1.161
971315AH1-136 GEN
Solar/Wind Harmer
2.301
970333AG2-219 GEN
Solar/Wind Harmer
6.64
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
3147312GRETNA
Solar/Wind Harmer
0.031
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.537
270032AE2-172
Solar/Wind Harmer
5.233
270005AE1-210 C O1
Solar/Wind Harmer
1.696
970825AG2-519 GEN
Solar/Wind Harmer
2.773
939741AE1-205 GEN
Solar/Wind Harmer
10.926
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.649
276158O29GEN2
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
10.252
970569AG2-363 GEN
Solar/Wind Harmer
23.052
971997AH1-543 GEN
Solar/Wind Harmer
4.011
276861AD2-134 GEN
Solar/Wind Harmer
0.137
945371AF1-202 GEN
Solar/Wind Harmer
0.001
237046AF1-021 C
Solar/Wind Helper
0.457
23751201ROTHROCK
Solar/Wind Helper
0.71
23583801GRNGAP
Solar/Wind Helper
4.088
20089226LOOKOUT
Solar/Wind Helper
0.539
957141AF2-008_MTX
Adder
72.592
944201AF1-088_MTX
Adder
145.184
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
CPLELTFEXP_CPLE->PJM
CLTF
7.791
SIGELTFEXP_SIGE->PJM
CLTF
0.659
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
NYPJM->LTFIMP_NY
CLTF
5.271
TVALTFEXP_TVA->PJM
CLTF
12.655
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
WECLTFEXP_WEC->PJM
CLTF
4.2
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
LGEELTFEXP_LGEE->PJM
CLTF
8.989
MECLTFEXP_MEC->PJM
CLTF
19.173
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.41 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2239.27
MW Contribution:1.39
Bus #Bus NameTypeMW Contribution
24803506KYGER 5LP
50/50
2.38
25196408WSDLE3
Adder
9.062
25196308WSDLE2
Adder
8.983
25196208WSDLE1
Adder
8.961
25196708WSDLE6
Adder
8.938
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.402
270367AC2-061_GEN
Solar/Wind Harmer
0.005
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971673AH1-337 GEN
Solar/Wind Harmer
3.282
270543AE2-219 C
Solar/Wind Harmer
0.003
270594AE1-207 GEN
Solar/Wind Harmer
5.001
24729505KEY G4
Adder
3.892
965411AG1-406 GEN
Solar/Wind Harmer
1.432
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
7.101
276174W4-005 GEN2
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
8.308
957751AF2-069 GEN
Solar/Wind Harmer
0.116
971177AH1-047 GEN
Solar/Wind Harmer
2.154
25183008BIOENL
50/50
0.03
25196508WSDLE4
Adder
8.713
972163AH1-664 GEN
Solar/Wind Harmer
7.031
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.007
270269AC2-059
Solar/Wind Harmer
0.003
253400AC2-068 GEN
Solar/Wind Harmer
0.683
3429211JKCT 2G
Adder
8.726
970115AG2-085 GEN
Solar/Wind Harmer
1.879
24699105WLD G1 C
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
3.046
270432AC2-029 GEN
Solar/Wind Harmer
2.004
971609AH1-304 GEN
Solar/Wind Harmer
0.735
241972AD1-140 GEN
Solar/Wind Harmer
0.486
965101AG1-375 GEN
Solar/Wind Harmer
4.42
963841AG1-237 GEN
Solar/Wind Harmer
1.679
24386205FR-12G C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
2.159
276655WTG1_EQ
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
4.276
926823AC1-168 GEN
Solar/Wind Harmer
0.6
274731ELWOOD EC;2P
Adder
8.308
274733ELWOOD EC;3P
Adder
8.308
276882AE2-255 GEN
Solar/Wind Harmer
0.412
274687WILL CNTY;4U
Adder
14.101
274687WILL CNTY;4U
Adder
7.883
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270329AC1-082 GEN1
Solar/Wind Helper
0.206
24803206KYGER 4HP
50/50
4.08
270263AC1-001 GEN
Solar/Wind Harmer
0.584
3429421JKCT 10G
Adder
6.399
970773AG2-487 GEN
Solar/Wind Harmer
0.938
971565AH1-281 GEN
Solar/Wind Harmer
0.942
970091AG2-072 GEN
Adder
45.505
253325AC1-069 GEN
Solar/Wind Harmer
0.006
963741AG1-226 GEN
Solar/Wind Harmer
9.27
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.754
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
7.519
970273AG2-179 GEN
Solar/Wind Harmer
1.245
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.427
274872LEEDK;1U
Solar/Wind Harmer
0.002
959081AF2-199 GEN
Solar/Wind Harmer
3.49
971067AG2-660 GEN
Solar/Wind Harmer
1.163
960001AF2-291 GEN
Solar/Wind Helper
1.722
971985AH1-537 GEN
Solar/Wind Harmer
5.764
972165AH1-665 GEN
Solar/Wind Harmer
5.631
253349AC2-067 GEN
Solar/Wind Harmer
1.699
971029AG2-637 GEN
Solar/Wind Harmer
7.495
24725505WLD G2 C
Solar/Wind Harmer
0.001
339211AE2-254 GEN
Solar/Wind Harmer
0.002
945581AF1-223 GEN
Solar/Wind Harmer
0
965401AG1-405 GEN
Solar/Wind Harmer
2.225
24386405FR-21G C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.203
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
3.019
274775LINCOLN ;6U
Adder
4.276
274777LINCOLN ;8U
Adder
4.276
970833AG2-524 GEN
Solar/Wind Harmer
3.883
970833AG2-524 GEN
Solar/Wind Harmer
2.589
960591AF2-350 GEN
Solar/Wind Harmer
3.529
972037AH1-567 GEN1
Adder
0.092
276868AE1-113 GEN
Solar/Wind Harmer
0.707
274675JOLIET 29;7U
Adder
15.482
274675JOLIET 29;7U
Adder
14.929
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971411AH1-196 GEN
Solar/Wind Harmer
5.236
971171AH1-044 GEN
Solar/Wind Harmer
6.979
270330AC1-082 GEN2
Solar/Wind Helper
0.043
971347AH1-153 GEN
Solar/Wind Harmer
0.971
25194408D.CRK1
Adder
7.772
972043AH1-570 GEN
Solar/Wind Harmer
1.516
24728905RICHG2
Adder
2.949
926881AC1-175 GEN
Solar/Wind Harmer
0
942891AE2-308 GEN
Solar/Wind Harmer
5.114
970883AG2-550 GEN
Solar/Wind Harmer
4.843
270599AE1-208 GEN
Solar/Wind Harmer
4.125
960971AF2-388 GEN
Solar/Wind Harmer
2.559
945391AF1-204 GEN
Solar/Wind Harmer
4.315
971081AG2-670 GEN
Solar/Wind Harmer
2.933
966841AG1-555 GEN
Solar/Wind Harmer
0.433
960611AF2-352 GEN
Solar/Wind Harmer
1.21
274887GEN-1.85
Solar/Wind Harmer
0.093
274674JOLIET 9 ;6U
Adder
7.776
958481AF2-142 GEN
Solar/Wind Harmer
5.285
274803UNIV PARK;6U
Adder
2.944
274879MINONK ;1U
Solar/Wind Harmer
0.149
274862TOP CROP ;2U
Solar/Wind Harmer
0.477
276782AC1-033 GEN
Solar/Wind Harmer
0.001
970921AG2-575 GEN
Solar/Wind Harmer
3.5
970921AG2-575 GEN
Solar/Wind Harmer
1.167
964781AG1-341 GEN
Solar/Wind Harmer
3.707
971335AH1-147 GEN
Solar/Wind Harmer
6.981
237033AB1-150 GEN
Solar/Wind Helper
0.4
24802606KYGER 1HP
50/50
4.153
24802706KYGER 1LP
50/50
2.437
25016408BKJDB1
50/50
0.276
252524AE2-267 GEN
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
1.517
253372AE2-315 SEC3
Adder
1.517
25306009OHH W.
Adder
2.274
970689AG2-444 GEN
Solar/Wind Harmer
10.333
970289AG2-191 GEN
Solar/Wind Harmer
0.831
270024AE2-089 GEN
Solar/Wind Harmer
0.005
963791AG1-232 GEN
Solar/Wind Harmer
5.01
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.134
276848AB2-070 GEN3
Solar/Wind Harmer
0.133
959341AF2-225 GEN
Solar/Wind Harmer
3.804
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
970169AG2-114 GEN
Solar/Wind Harmer
3.59
972227AH1-698 GEN1
Adder
1.32
274735ELWOOD EC;4P
Adder
8.308
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
3.916
25194608D.CRK4
Adder
1.69
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.992
945681AF1-233 GEN
Solar/Wind Harmer
12.039
253370AE2-315 SEC1
Adder
1.603
253371AE2-315 SEC2
Adder
1.517
960071AF2-298 GEN
Solar/Wind Harmer
2.664
970613AG2-401 GEN
Solar/Wind Harmer
3.753
965031AG1-367 GEN
Solar/Wind Harmer
4.789
24728605AND G2
Adder
2.624
971821AH1-427 GEN
Solar/Wind Harmer
4.468
970291AG2-192 GEN
Solar/Wind Harmer
0.569
965651AG1-433 GEN
Solar/Wind Harmer
1.28
253343AC1-166 GEN
Solar/Wind Harmer
0.002
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
964901AG1-354 GEN
Solar/Wind Harmer
5.476
270055AF2-134 C O1
Solar/Wind Harmer
0.003
276901AD2-066 C O1
Solar/Wind Harmer
0.003
274871GR RIDGE ;2U
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.368
276164X3-005 C
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
15.482
274877BISHOP HL;1U
Solar/Wind Harmer
0.118
957471AF2-041 GEN
Solar/Wind Harmer
10.469
24803106KYGER 3LP
50/50
2.431
24803306KYGER 4LP
50/50
2.38
25196608WSDLE5
Adder
8.803
958171AF2-111 GEN
Solar/Wind Harmer
17.035
253406AD2-031_GEN
Solar/Wind Harmer
0.461
270273AD2-016 GEN
Solar/Wind Harmer
0.603
253415AE1-040 GEN
Solar/Wind Harmer
0.002
3429391JKCT 9G
Adder
6.399
270437AC2-090 C
Solar/Wind Harmer
0.002
958821AF2-173 GEN
Solar/Wind Harmer
6.704
24728705AND G3
Adder
5.489
944531AF1-118 GEN
Solar/Wind Harmer
18.471
253333AC1-068 GEN
Solar/Wind Harmer
0.006
970193AG2-126 GEN
Solar/Wind Harmer
6.091
970519AG2-331 GEN
Solar/Wind Harmer
10.553
970699AG2-449 GEN
Solar/Wind Harmer
1.015
970781AG2-491 GEN
Solar/Wind Harmer
3.773
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970513AG2-328 GEN
Solar/Wind Harmer
1.581
970517AG2-330 GEN
Solar/Wind Harmer
9.486
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
959611AF2-252 GEN
Solar/Wind Harmer
1.21
939351AE1-166 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
1.875
274730ELWOOD EC;6P
Adder
8.308
970707AG2-453 GEN
Solar/Wind Harmer
11.517
276694AA1-018 GEN2
Solar/Wind Harmer
0
274826FISK ;BP
Adder
5.526
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
235780M24_1
Solar/Wind Helper
0.99
970349AG2-230 GEN
Solar/Wind Harmer
0.971
24803406KYGER 5HP
50/50
4.083
25196808ZIMRHP
Adder
79.423
25196008MFTGT1
Adder
1.369
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.038
970825AG2-519 GEN
Solar/Wind Harmer
1.675
945371AF1-202 GEN
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
2.977
958861AF2-177 GEN
Solar/Wind Harmer
1.915
970333AG2-219 GEN
Solar/Wind Harmer
2.902
24387305FR-4G C
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.626
274880W4-005 GEN4
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
972175AH1-670 GEN
Solar/Wind Harmer
3.016
939741AE1-205 GEN
Solar/Wind Harmer
5.072
274773LINCOLN ;4U
Adder
4.276
274774LINCOLN ;5U
Adder
4.276
971997AH1-543 GEN
Solar/Wind Harmer
1.852
274801UNIV PARK;4U
Adder
2.945
970569AG2-363 GEN
Solar/Wind Harmer
10.571
276861AD2-134 GEN
Solar/Wind Harmer
0.063
270331AC1-082 GEN3
Solar/Wind Helper
0.205
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
3.745
970235AG2-159 GEN
Solar/Wind Harmer
2.149
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970107AG2-081 GEN
Solar/Wind Harmer
1.704
270209AC1-174_GEN
Solar/Wind Harmer
0
960161AF2-307 GEN
Solar/Wind Harmer
3.166
970825AG2-519 GEN
Solar/Wind Harmer
5.23
942221AE2-234 GEN
Solar/Wind Harmer
0.02
970239AG2-162 GEN
Solar/Wind Harmer
1.015
970241AG2-163 GEN
Solar/Wind Harmer
2.285
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
25326509SID D
Adder
0.697
970321AG2-212 GEN
Solar/Wind Harmer
1.581
274770LINCOLN ;1U
Adder
4.276
274771LINCOLN ;2U
Adder
4.276
274888KELLY CRK;1U
Solar/Wind Harmer
0.207
972259AH1-714 GEN
Adder
9.649
276645AC1-214 GEN1
Solar/Wind Harmer
0.139
962691AG1-118 GEN
Solar/Wind Harmer
10.504
971191AH1-055 GEN
Solar/Wind Harmer
68.697
252510AF1-249 C
Solar/Wind Harmer
0.055
25196008MFTGT1
Adder
1.326
972167AH1-666 GEN
Solar/Wind Harmer
5.13
970093AG2-073 GEN
Solar/Wind Harmer
4.888
966571AG1-526 GEN
Solar/Wind Harmer
10.492
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.776
970243AG2-164 GEN
Solar/Wind Harmer
2.375
971993AH1-541 GEN
Solar/Wind Harmer
1.693
276621W2-048 GEN
Solar/Wind Harmer
0.185
276838X2-022 GEN2
Solar/Wind Harmer
0.206
942481AE2-261 GEN
Solar/Wind Harmer
10.947
972273AH1-721 GEN
Adder
43.396
942111AE2-223 GEN
Solar/Wind Harmer
1.177
276897AD1-100 C
Solar/Wind Harmer
0.005
274772LINCOLN ;3U
Adder
4.276
970941AG2-585 GEN
Solar/Wind Harmer
4.411
274729ELWOOD EC;1P
Adder
8.308
276893AG1-478 C
Solar/Wind Harmer
0.14
274800UNIV PARK;3U
Adder
2.945
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
7.047
274802UNIV PARK;5U
Adder
2.944
270043AE2-236 GEN
Solar/Wind Harmer
2.261
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.063
24803006KYGER 3HP
50/50
4.129
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0.012
25194508D.CRK3
Adder
1.453
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972045AH1-571 GEN
Solar/Wind Harmer
1.215
24728805RICHG1
Adder
2.949
25326109MON D
Adder
0.986
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970885AG2-551 GEN
Solar/Wind Harmer
1.614
960441AF2-335 GEN
Solar/Wind Harmer
4.696
964611AG1-324 GEN
Solar/Wind Harmer
0.342
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270031AE2-169
Solar/Wind Harmer
2.475
964571AG1-320 GEN
Solar/Wind Harmer
4.08
944541AF1-119 GEN
Solar/Wind Harmer
0.292
970653AG2-424 GEN
Solar/Wind Harmer
2.067
970653AG2-424 GEN
Solar/Wind Harmer
1.071
945421AF1-207 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Harmer
0.321
276911AD2-131_GEN
Solar/Wind Harmer
0.507
276843GEN-1.7
Solar/Wind Harmer
0.114
958011AF2-095 GEN
Solar/Wind Harmer
5.082
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
958491AF2-143 GEN
Solar/Wind Harmer
5.285
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.139
971573AH1-285 GEN
Solar/Wind Harmer
0.654
339255AE2-071 GEN
Solar/Wind Harmer
-0.058
942991AE2-321 GEN
Solar/Wind Harmer
3.901
971333AH1-146 GEN
Solar/Wind Harmer
6.981
24802806KYGER 2HP
50/50
4.105
24802906KYGER 2LP
50/50
2.413
252519AF1-045_GEN
Solar/Wind Harmer
6.438
252516AE2-318_GEN
Solar/Wind Harmer
5.71
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
971125AH1-004 GEN
Solar/Wind Harmer
2.272
253370AE2-315 SEC1
Adder
1.603
25322209TAIT E
Adder
7.54
25322209TAIT E
Adder
7.371
247621Y3-024
Adder
0.159
971613AH1-306 GEN
Solar/Wind Harmer
2.143
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.992
276916AD2-100_GEN
Solar/Wind Harmer
7.697
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.979
971343AH1-151 GEN
Solar/Wind Harmer
6.979
25194608D.CRK4
Adder
1.69
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.09
253370AE2-315 SEC1
Adder
1.603
253371AE2-315 SEC2
Adder
1.517
24728505AND G1
Adder
2.624
946031AF1-268 GEN
Solar/Wind Harmer
4.488
970289AG2-191 GEN
Solar/Wind Harmer
0.481
970291AG2-192 GEN
Solar/Wind Harmer
0.437
247642Z2-115 C
Solar/Wind Harmer
0.002
960741AF2-365 GEN
Solar/Wind Harmer
1.902
24755605MDL-5G
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.134
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
276806AD2-047 C O1
Solar/Wind Harmer
2
274734ELWOOD EC;8P
Adder
8.308
274736ELWOOD EC;9P
Adder
8.308
274676JOLIET 29;8U
Adder
14.929
943121AE2-341 GEN
Solar/Wind Harmer
5.891
943591AF1-030 GEN
Solar/Wind Harmer
3.917
971155AH1-034 GEN
Solar/Wind Harmer
4.077
959091AF2-200 GEN
Solar/Wind Harmer
6.979
252507AC2-088 GEN
Solar/Wind Harmer
0.36
339216AC1-074 GEN
Solar/Wind Harmer
0.167
25326309TAIT D
Adder
0.846
3429241JKCT 3G
Adder
8.84
247536S-71 GEN
Solar/Wind Harmer
0.189
276903AD2-071 C
Solar/Wind Harmer
5.056
24385905FR-11G C
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.429
276615X2-022 GEN
Solar/Wind Harmer
0.038
965911AG1-460 GEN
Solar/Wind Harmer
0.732
958381AF2-132 GEN
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
1.581
939401AE1-172 GEN
Solar/Wind Harmer
2.671
274732ELWOOD EC;7P
Adder
8.308
274674JOLIET 9 ;6U
Adder
7.776
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
962241AG1-070 GEN
Solar/Wind Harmer
1.916
962781AG1-127 GEN
Solar/Wind Harmer
3.331
972173AH1-669 GEN
Solar/Wind Harmer
3.047
270222AC2-111 GEN
Solar/Wind Harmer
2.955
970191AG2-125 GEN
Solar/Wind Harmer
1.388
270356AE2-297 GEN
Solar/Wind Harmer
0.007
270004AE1-209 GEN
Solar/Wind Harmer
1.038
971617AH1-308 GEN
Solar/Wind Harmer
3.507
253338AC1-165 GEN
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.888
970273AG2-179 GEN
Solar/Wind Harmer
2.134
972038AH1-567 GEN2
Adder
0.184
962251AG1-071 GEN
Solar/Wind Harmer
2.197
274878BISHOP HL;2U
Solar/Wind Harmer
0.118
339250AF1-203 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.128
957141AF2-008_MTX
Adder
33.999
944201AF1-088_MTX
Adder
67.999
NYPJM->LTFIMP_NY
CLTF
1.661
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.042
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.325
LGEELTFEXP_LGEE->PJM
CLTF
5.141
TVALTFEXP_TVA->PJM
CLTF
3.109
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.636
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.285
LAGNLTFEXP_LAGN->PJM
CLTF
6.556
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.397
WECLTFEXP_WEC->PJM
CLTF
1.904
MECLTFEXP_MEC->PJM
CLTF
8.008
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#309_15_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#309_15_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.78 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2183.34
MW Contribution:1.47
Bus #Bus NameTypeMW Contribution
24803506KYGER 5LP
50/50
2.41
25196408WSDLE3
Adder
9.532
25196308WSDLE2
Adder
9.449
25196208WSDLE1
Adder
9.426
25196708WSDLE6
Adder
9.402
25196108MFTGT2
Adder
1.577
25196108MFTGT2
Adder
1.464
270367AC2-061_GEN
Solar/Wind Harmer
0.005
971673AH1-337 GEN
Solar/Wind Harmer
3.274
270240V3-007_GEN2
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.003
270594AE1-207 GEN
Solar/Wind Harmer
4.766
965411AG1-406 GEN
Solar/Wind Harmer
1.415
270156DARBY CT1
Adder
4.836
270157DARBY CT2
Adder
4.825
24729505KEY G4
Adder
3.463
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
6.133
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.103
274728ELWOOD EC;5P
Adder
7.212
971681AH1-341 GEN
Solar/Wind Harmer
4.912
25183008BIOENL
50/50
0.032
25196508WSDLE4
Adder
9.165
972163AH1-664 GEN
Solar/Wind Harmer
7.374
270269AC2-059
Solar/Wind Harmer
0.004
270340AC2-060 GEN
Solar/Wind Harmer
0.007
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
253400AC2-068 GEN
Solar/Wind Harmer
0.725
3429211JKCT 2G
Adder
8.965
270432AC2-029 GEN
Solar/Wind Harmer
2.302
241972AD1-140 GEN
Solar/Wind Harmer
0.537
970455AG2-298 GEN
Solar/Wind Harmer
3.084
970115AG2-085 GEN
Solar/Wind Harmer
1.802
24699105WLD G1 C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.693
965101AG1-375 GEN
Solar/Wind Harmer
4.056
963841AG1-237 GEN
Solar/Wind Harmer
1.584
945631AF1-228 GEN
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
2.022
276655WTG1_EQ
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.529
276882AE2-255 GEN
Solar/Wind Harmer
0.361
274731ELWOOD EC;2P
Adder
7.212
274733ELWOOD EC;3P
Adder
7.212
274687WILL CNTY;4U
Adder
12.222
274687WILL CNTY;4U
Adder
12.222
274746AC1-111 G10
Adder
2.444
270329AC1-082 GEN1
Solar/Wind Helper
0.199
24803206KYGER 4HP
50/50
4.13
270263AC1-001 GEN
Solar/Wind Harmer
0.653
3429421JKCT 10G
Adder
6.595
970773AG2-487 GEN
Solar/Wind Harmer
0.935
971565AH1-281 GEN
Solar/Wind Harmer
0.959
253325AC1-069 GEN
Solar/Wind Harmer
0.007
970091AG2-072 GEN
Adder
49.379
270159DARBY CT4
Adder
4.759
963741AG1-226 GEN
Solar/Wind Harmer
8.802
970593AG2-378 GEN
Solar/Wind Harmer
0.808
24791305MDL-5G
Solar/Wind Harmer
0
970273AG2-179 GEN
Solar/Wind Harmer
1.212
971917AH1-482 GEN
Solar/Wind Harmer
4.279
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
6.619
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.372
959081AF2-199 GEN
Solar/Wind Harmer
3.05
971067AG2-660 GEN
Solar/Wind Harmer
1.017
274872LEEDK;1U
Solar/Wind Harmer
0.002
960001AF2-291 GEN
Solar/Wind Helper
1.676
971985AH1-537 GEN
Solar/Wind Harmer
5.902
972165AH1-665 GEN
Solar/Wind Harmer
5.906
253349AC2-067 GEN
Solar/Wind Harmer
1.803
971029AG2-637 GEN
Solar/Wind Harmer
7.455
339211AE2-254 GEN
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
965401AG1-405 GEN
Solar/Wind Harmer
2.199
270158DARBY CT3
Adder
4.747
24386405FR-21G C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.007
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
2.716
276868AE1-113 GEN
Solar/Wind Harmer
0.619
970833AG2-524 GEN
Solar/Wind Harmer
3.372
970833AG2-524 GEN
Solar/Wind Harmer
2.248
960591AF2-350 GEN
Solar/Wind Harmer
3.057
274675JOLIET 29;7U
Adder
13.422
274675JOLIET 29;7U
Adder
12.942
971171AH1-044 GEN
Solar/Wind Harmer
6.1
971675AH1-338 GEN
Solar/Wind Harmer
1.189
972037AH1-567 GEN1
Adder
0.08
946321AF1-296 GEN
Solar/Wind Harmer
1.708
270330AC1-082 GEN2
Solar/Wind Helper
0.041
25194408D.CRK1
Adder
8.173
972043AH1-570 GEN
Solar/Wind Harmer
1.576
24728905RICHG2
Adder
2.986
942891AE2-308 GEN
Solar/Wind Harmer
5.244
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.773
270599AE1-208 GEN
Solar/Wind Harmer
3.89
960971AF2-388 GEN
Solar/Wind Harmer
2.332
945391AF1-204 GEN
Solar/Wind Harmer
4.178
971081AG2-670 GEN
Solar/Wind Harmer
2.902
966841AG1-555 GEN
Solar/Wind Harmer
0.406
964781AG1-341 GEN
Solar/Wind Harmer
3.601
960611AF2-352 GEN
Solar/Wind Harmer
1.093
971485AH1-239 GEN
Solar/Wind Harmer
2.495
276782AC1-033 GEN
Solar/Wind Harmer
0
274879MINONK ;1U
Solar/Wind Harmer
0.13
274862TOP CROP ;2U
Solar/Wind Harmer
0.416
958481AF2-142 GEN
Solar/Wind Harmer
4.61
276708O09 GEN2
Solar/Wind Harmer
0.109
274887GEN-1.85
Solar/Wind Harmer
0.08
274674JOLIET 9 ;6U
Adder
6.747
972267AH1-718 GEN
Adder
1.821
274803UNIV PARK;6U
Adder
2.549
274764LEE CO EC;5U
Adder
4.075
970921AG2-575 GEN
Solar/Wind Harmer
3.048
970921AG2-575 GEN
Solar/Wind Harmer
1.016
237033AB1-150 GEN
Solar/Wind Helper
0.403
971335AH1-147 GEN
Solar/Wind Harmer
3.002
24802606KYGER 1HP
50/50
4.205
24802706KYGER 1LP
50/50
2.468
25016408BKJDB1
50/50
0.29
252524AE2-267 GEN
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
1.625
253372AE2-315 SEC3
Adder
1.625
25306009OHH W.
Adder
2.427
970689AG2-444 GEN
Solar/Wind Harmer
11.775
970289AG2-191 GEN
Solar/Wind Harmer
0.789
270024AE2-089 GEN
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
1.225
276785W4-005 GEN1
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.122
963791AG1-232 GEN
Solar/Wind Harmer
4.535
958391AF2-133 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
1.276
943851AF1-053 GEN
Solar/Wind Harmer
0.884
959341AF2-225 GEN
Solar/Wind Harmer
3.422
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
970169AG2-114 GEN
Solar/Wind Harmer
3.189
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
274735ELWOOD EC;4P
Adder
7.212
972227AH1-698 GEN1
Adder
1.144
961011AF2-392 GEN
Solar/Wind Harmer
1.791
274744AC1-111 GEN8
Adder
2.444
25194608D.CRK4
Adder
1.777
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.481
945681AF1-233 GEN
Solar/Wind Harmer
12.638
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
960071AF2-298 GEN
Solar/Wind Harmer
2.849
970613AG2-401 GEN
Solar/Wind Harmer
3.657
24728605AND G2
Adder
2.584
253343AC1-166 GEN
Solar/Wind Harmer
0.002
965031AG1-367 GEN
Solar/Wind Harmer
4.578
971821AH1-427 GEN
Solar/Wind Harmer
4.505
970291AG2-192 GEN
Solar/Wind Harmer
0.54
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.166
964901AG1-354 GEN
Solar/Wind Harmer
5.358
270055AF2-134 C O1
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.105
276901AD2-066 C O1
Solar/Wind Harmer
0.003
274871GR RIDGE ;2U
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.319
274676JOLIET 29;8U
Adder
13.422
274745AC1-111 GEN9
Adder
2.444
957471AF2-041 GEN
Solar/Wind Harmer
9.15
24803106KYGER 3LP
50/50
2.461
24803306KYGER 4LP
50/50
2.41
25196608WSDLE5
Adder
9.26
958171AF2-111 GEN
Solar/Wind Harmer
17.961
253406AD2-031_GEN
Solar/Wind Harmer
0.496
270273AD2-016 GEN
Solar/Wind Harmer
0.676
253415AE1-040 GEN
Solar/Wind Harmer
0.003
3429391JKCT 9G
Adder
6.595
270437AC2-090 C
Solar/Wind Harmer
0.002
24728705AND G3
Adder
5.404
253333AC1-068 GEN
Solar/Wind Harmer
0.007
958821AF2-173 GEN
Solar/Wind Harmer
6.409
970519AG2-331 GEN
Solar/Wind Harmer
11.364
970699AG2-449 GEN
Solar/Wind Harmer
1.093
970193AG2-126 GEN
Solar/Wind Harmer
5.898
944531AF1-118 GEN
Solar/Wind Harmer
16.287
970605AG2-385 GEN
Solar/Wind Harmer
2.184
970781AG2-491 GEN
Solar/Wind Harmer
3.498
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
24803406KYGER 5HP
50/50
4.134
25196808ZIMRHP
Adder
83.68
25196008MFTGT1
Adder
1.431
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
0.992
970825AG2-519 GEN
Solar/Wind Harmer
1.608
970333AG2-219 GEN
Solar/Wind Harmer
3.125
270032AE2-172
Solar/Wind Harmer
2.837
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.758
24387305FR-4G C
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.214
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.749
964861AG1-349 GEN
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.562
970569AG2-363 GEN
Solar/Wind Harmer
9.313
971997AH1-543 GEN
Solar/Wind Harmer
1.624
276158O29GEN2
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.55
276861AD2-134 GEN
Solar/Wind Harmer
0.055
270331AC1-082 GEN3
Solar/Wind Helper
0.198
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.893
970235AG2-159 GEN
Solar/Wind Harmer
2.234
970107AG2-081 GEN
Solar/Wind Harmer
1.765
270209AC1-174_GEN
Solar/Wind Harmer
0
960161AF2-307 GEN
Solar/Wind Harmer
3.231
970825AG2-519 GEN
Solar/Wind Harmer
5.021
970239AG2-162 GEN
Solar/Wind Harmer
1.093
25326509SID D
Adder
0.76
942221AE2-234 GEN
Solar/Wind Harmer
0.019
253378AE2-206_GEN
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
2.169
970077AG2-063 GEN
Solar/Wind Harmer
2.064
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970321AG2-212 GEN
Solar/Wind Harmer
1.366
276645AC1-214 GEN1
Solar/Wind Harmer
0.123
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
972259AH1-714 GEN
Adder
8.351
276603SUBLETTE C
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
1.728
962691AG1-118 GEN
Solar/Wind Harmer
9.146
971191AH1-055 GEN
Solar/Wind Harmer
70.447
252510AF1-249 C
Solar/Wind Harmer
0.058
25196008MFTGT1
Adder
1.385
972167AH1-666 GEN
Solar/Wind Harmer
5.387
970093AG2-073 GEN
Solar/Wind Harmer
4.986
966571AG1-526 GEN
Solar/Wind Harmer
10.654
970243AG2-164 GEN
Solar/Wind Harmer
2.557
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.542
972273AH1-721 GEN
Adder
42.389
942481AE2-261 GEN
Solar/Wind Harmer
10.156
276621W2-048 GEN
Solar/Wind Harmer
0.17
276838X2-022 GEN2
Solar/Wind Harmer
0.19
971993AH1-541 GEN
Solar/Wind Harmer
1.555
942111AE2-223 GEN
Solar/Wind Harmer
1.059
970571AG2-364 GEN
Solar/Wind Harmer
6.209
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.004
276157O29GEN1
Solar/Wind Harmer
0.496
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.212
970941AG2-585 GEN
Solar/Wind Harmer
3.821
274800UNIV PARK;3U
Adder
2.55
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.325
274802UNIV PARK;5U
Adder
2.549
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
24803006KYGER 3HP
50/50
4.181
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0.012
25194508D.CRK3
Adder
1.528
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972045AH1-571 GEN
Solar/Wind Harmer
1.263
25326109MON D
Adder
1.064
24728805RICHG1
Adder
2.986
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970885AG2-551 GEN
Solar/Wind Harmer
1.591
964571AG1-320 GEN
Solar/Wind Harmer
4.118
960441AF2-335 GEN
Solar/Wind Harmer
4.504
964611AG1-324 GEN
Solar/Wind Harmer
0.33
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
2.075
970653AG2-424 GEN
Solar/Wind Harmer
1.075
270518AE2-148 GEN
Solar/Wind Harmer
0.367
270031AE2-169
Solar/Wind Harmer
2.334
24802806KYGER 2HP
50/50
4.156
24802906KYGER 2LP
50/50
2.443
252519AF1-045_GEN
Solar/Wind Harmer
6.799
252516AE2-318_GEN
Solar/Wind Harmer
6.03
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
253370AE2-315 SEC1
Adder
1.718
971125AH1-004 GEN
Solar/Wind Harmer
2.354
25322209TAIT E
Adder
8.088
25322209TAIT E
Adder
7.906
247621Y3-024
Adder
0.155
971613AH1-306 GEN
Solar/Wind Harmer
2.042
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.032
276820AF1-078_GEN
Solar/Wind Harmer
0.001
276916AD2-100_GEN
Solar/Wind Harmer
7.156
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.109
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
6.1
971343AH1-151 GEN
Solar/Wind Harmer
6.1
25194608D.CRK4
Adder
1.777
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.726
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
24728505AND G1
Adder
2.584
946031AF1-268 GEN
Solar/Wind Harmer
4.321
970289AG2-191 GEN
Solar/Wind Harmer
0.457
970291AG2-192 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.002
960741AF2-365 GEN
Solar/Wind Harmer
1.874
24755605MDL-5G
Solar/Wind Harmer
0
971155AH1-034 GEN
Solar/Wind Harmer
3.958
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274734ELWOOD EC;8P
Adder
7.212
274736ELWOOD EC;9P
Adder
7.212
276806AD2-047 C O1
Solar/Wind Harmer
1.732
274676JOLIET 29;8U
Adder
12.942
959091AF2-200 GEN
Solar/Wind Harmer
6.1
959611AF2-252 GEN
Solar/Wind Harmer
1.093
970513AG2-328 GEN
Solar/Wind Harmer
1.366
970517AG2-330 GEN
Solar/Wind Harmer
8.195
942051AE2-217 GEN
Solar/Wind Harmer
5.584
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.212
972228AH1-698 GEN2
Adder
1.624
274855GSG-6 ;RU
Solar/Wind Harmer
0.112
235780M24_1
Solar/Wind Helper
0.999
252507AC2-088 GEN
Solar/Wind Harmer
0.38
339216AC1-074 GEN
Solar/Wind Harmer
0.174
25326309TAIT D
Adder
0.908
3429241JKCT 3G
Adder
9.082
247536S-71 GEN
Solar/Wind Harmer
0.185
276903AD2-071 C
Solar/Wind Harmer
4.849
24385905FR-11G C
Solar/Wind Harmer
0.001
962241AG1-070 GEN
Solar/Wind Harmer
1.862
965911AG1-460 GEN
Solar/Wind Harmer
0.679
276615X2-022 GEN
Solar/Wind Harmer
0.035
963831AG1-236 GEN
Solar/Wind Harmer
1.313
958381AF2-132 GEN
Solar/Wind Harmer
0
970245AG2-165 GEN
Solar/Wind Harmer
1.366
939401AE1-172 GEN
Solar/Wind Harmer
2.35
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
7.212
274674JOLIET 9 ;6U
Adder
6.747
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
2.901
944541AF1-119 GEN
Solar/Wind Harmer
0.266
970329AG2-216 GEN
Solar/Wind Harmer
1.613
945421AF1-207 GEN
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
0.471
339255AE2-071 GEN
Solar/Wind Harmer
-0.056
942861AE2-305 GEN
Solar/Wind Harmer
2.586
274851PROVIDENC;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.123
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
958491AF2-143 GEN
Solar/Wind Harmer
4.624
966021AG1-471 GEN
Solar/Wind Harmer
1.664
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.402
274765LEE CO EC;6U
Adder
2.574
971573AH1-285 GEN
Solar/Wind Harmer
0.568
971333AH1-146 GEN
Solar/Wind Harmer
3.002
972173AH1-669 GEN
Solar/Wind Harmer
3.407
270222AC2-111 GEN
Solar/Wind Harmer
3.033
970191AG2-125 GEN
Solar/Wind Harmer
1.473
270356AE2-297 GEN
Solar/Wind Harmer
0.007
253338AC1-165 GEN
Solar/Wind Harmer
0.002
270004AE1-209 GEN
Solar/Wind Harmer
0.992
971617AH1-308 GEN
Solar/Wind Harmer
3.313
970273AG2-179 GEN
Solar/Wind Harmer
2.077
962251AG1-071 GEN
Solar/Wind Harmer
2.135
339250AF1-203 GEN
Solar/Wind Harmer
0.001
276686W4-005 GEN3
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
9.838
274878BISHOP HL;2U
Solar/Wind Harmer
0.105
972038AH1-567 GEN2
Adder
0.16
965931AG1-462 GEN
Solar/Wind Harmer
7.774
274872LEEDK;1U
Solar/Wind Harmer
0.112
957141AF2-008_MTX
Adder
34.455
944201AF1-088_MTX
Adder
68.911
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.937
WECLTFEXP_WEC->PJM
CLTF
1.664
MECLTFEXP_MEC->PJM
CLTF
7.145
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.454
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.623
LAGNLTFEXP_LAGN->PJM
CLTF
5.672
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.759
LGEELTFEXP_LGEE->PJM
CLTF
5.309
TVALTFEXP_TVA->PJM
CLTF
2.671
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
NYPJM->LTFIMP_NY
CLTF
1.591
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.271
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.72 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1566.09
MW Contribution:1.36
Bus #Bus NameTypeMW Contribution
24803206KYGER 4HP
50/50
4.099
270263AC1-001 GEN
Solar/Wind Harmer
0.606
3429421JKCT 10G
Adder
6.235
970773AG2-487 GEN
Solar/Wind Harmer
0.849
971565AH1-281 GEN
Solar/Wind Harmer
0.891
253325AC1-069 GEN
Solar/Wind Harmer
0.007
970091AG2-072 GEN
Adder
40.612
270159DARBY CT4
Adder
4.344
970273AG2-179 GEN
Solar/Wind Harmer
1.177
24802806KYGER 2HP
50/50
4.125
24802906KYGER 2LP
50/50
2.425
252507AC2-088 GEN
Solar/Wind Harmer
0.356
339216AC1-074 GEN
Solar/Wind Harmer
0.163
25326309TAIT D
Adder
0.84
3429241JKCT 3G
Adder
8.606
247536S-71 GEN
Solar/Wind Harmer
0.167
276903AD2-071 C
Solar/Wind Harmer
4.31
962241AG1-070 GEN
Solar/Wind Harmer
1.783
24385905FR-11G C
Solar/Wind Harmer
0.001
24803106KYGER 3LP
50/50
2.442
24803306KYGER 4LP
50/50
2.392
25196608WSDLE5
Adder
8.625
958171AF2-111 GEN
Solar/Wind Harmer
16.854
253406AD2-031_GEN
Solar/Wind Harmer
0.462
270273AD2-016 GEN
Solar/Wind Harmer
0.628
253415AE1-040 GEN
Solar/Wind Harmer
0.002
3429391JKCT 9G
Adder
6.235
270437AC2-090 C
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
24728705AND G3
Adder
4.853
958821AF2-173 GEN
Solar/Wind Harmer
5.771
970519AG2-331 GEN
Solar/Wind Harmer
9.199
970699AG2-449 GEN
Solar/Wind Harmer
0.884
970193AG2-126 GEN
Solar/Wind Harmer
5.147
970605AG2-385 GEN
Solar/Wind Harmer
1.988
944531AF1-118 GEN
Solar/Wind Harmer
14.426
235780M24_1
Solar/Wind Helper
0.923
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.613
970235AG2-159 GEN
Solar/Wind Harmer
2.073
970107AG2-081 GEN
Solar/Wind Harmer
1.662
960161AF2-307 GEN
Solar/Wind Harmer
3.112
270209AC1-174_GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
4.514
25326509SID D
Adder
0.693
970239AG2-162 GEN
Solar/Wind Harmer
0.884
253378AE2-206_GEN
Solar/Wind Harmer
0.002
942221AE2-234 GEN
Solar/Wind Harmer
0.017
970077AG2-063 GEN
Solar/Wind Harmer
1.879
970241AG2-163 GEN
Solar/Wind Harmer
1.873
24803506KYGER 5LP
50/50
2.392
25196408WSDLE3
Adder
8.879
25196308WSDLE2
Adder
8.801
25196208WSDLE1
Adder
8.779
25196708WSDLE6
Adder
8.757
25196108MFTGT2
Adder
1.463
25196108MFTGT2
Adder
1.358
270367AC2-061_GEN
Solar/Wind Harmer
0.005
971673AH1-337 GEN
Solar/Wind Harmer
2.979
270240V3-007_GEN2
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.003
270594AE1-207 GEN
Solar/Wind Harmer
4.227
965411AG1-406 GEN
Solar/Wind Harmer
1.371
270156DARBY CT1
Adder
4.415
270157DARBY CT2
Adder
4.404
24729505KEY G4
Adder
3.073
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
972173AH1-669 GEN
Solar/Wind Harmer
3.165
270222AC2-111 GEN
Solar/Wind Harmer
2.79
970191AG2-125 GEN
Solar/Wind Harmer
1.36
270356AE2-297 GEN
Solar/Wind Harmer
0.006
253338AC1-165 GEN
Solar/Wind Harmer
0.002
270004AE1-209 GEN
Solar/Wind Harmer
0.893
971617AH1-308 GEN
Solar/Wind Harmer
2.961
970273AG2-179 GEN
Solar/Wind Harmer
2.017
339250AF1-203 GEN
Solar/Wind Harmer
0
962251AG1-071 GEN
Solar/Wind Harmer
2.045
25183008BIOENL
50/50
0.03
25196508WSDLE4
Adder
8.537
972163AH1-664 GEN
Solar/Wind Harmer
6.955
270269AC2-059
Solar/Wind Harmer
0.003
270340AC2-060 GEN
Solar/Wind Harmer
0.007
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
253400AC2-068 GEN
Solar/Wind Harmer
0.67
3429211JKCT 2G
Adder
8.494
270432AC2-029 GEN
Solar/Wind Harmer
2.121
241972AD1-140 GEN
Solar/Wind Harmer
0.495
970455AG2-298 GEN
Solar/Wind Harmer
2.878
970115AG2-085 GEN
Solar/Wind Harmer
1.619
24699105WLD G1 C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.62
965101AG1-375 GEN
Solar/Wind Harmer
3.623
945631AF1-228 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.363
24386205FR-12G C
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
1.779
270329AC1-082 GEN1
Solar/Wind Helper
0.199
24803006KYGER 3HP
50/50
4.149
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0.012
25194508D.CRK3
Adder
1.424
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972045AH1-571 GEN
Solar/Wind Harmer
1.189
25326109MON D
Adder
0.984
24728805RICHG1
Adder
2.73
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970885AG2-551 GEN
Solar/Wind Harmer
1.442
964571AG1-320 GEN
Solar/Wind Harmer
3.821
960441AF2-335 GEN
Solar/Wind Harmer
4.047
970653AG2-424 GEN
Solar/Wind Harmer
1.943
970653AG2-424 GEN
Solar/Wind Harmer
1.007
964611AG1-324 GEN
Solar/Wind Harmer
0.297
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270518AE2-148 GEN
Solar/Wind Harmer
0.337
270031AE2-169
Solar/Wind Harmer
2.087
944541AF1-119 GEN
Solar/Wind Harmer
0.237
970329AG2-216 GEN
Solar/Wind Harmer
1.467
339255AE2-071 GEN
Solar/Wind Harmer
-0.054
966021AG1-471 GEN
Solar/Wind Harmer
1.637
25194408D.CRK1
Adder
7.616
972043AH1-570 GEN
Solar/Wind Harmer
1.484
24728905RICHG2
Adder
2.73
942891AE2-308 GEN
Solar/Wind Harmer
4.97
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.325
270599AE1-208 GEN
Solar/Wind Harmer
3.479
971081AG2-670 GEN
Solar/Wind Harmer
2.763
960971AF2-388 GEN
Solar/Wind Harmer
2.079
945391AF1-204 GEN
Solar/Wind Harmer
3.646
964781AG1-341 GEN
Solar/Wind Harmer
3.457
966841AG1-555 GEN
Solar/Wind Harmer
0.348
971485AH1-239 GEN
Solar/Wind Harmer
2.448
237033AB1-150 GEN
Solar/Wind Helper
0.372
971985AH1-537 GEN
Solar/Wind Harmer
5.759
972165AH1-665 GEN
Solar/Wind Harmer
5.57
253349AC2-067 GEN
Solar/Wind Harmer
1.665
971029AG2-637 GEN
Solar/Wind Harmer
6.776
339211AE2-254 GEN
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
965401AG1-405 GEN
Solar/Wind Harmer
2.132
270158DARBY CT3
Adder
4.334
24386405FR-21G C
Solar/Wind Harmer
0
270330AC1-082 GEN2
Solar/Wind Helper
0.041
24803406KYGER 5HP
50/50
4.102
25196808ZIMRHP
Adder
78.156
25196008MFTGT1
Adder
1.327
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
0.893
970825AG2-519 GEN
Solar/Wind Harmer
1.446
270032AE2-172
Solar/Wind Harmer
2.516
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.57
970333AG2-219 GEN
Solar/Wind Harmer
2.53
24387305FR-4G C
Solar/Wind Harmer
0.001
270331AC1-082 GEN3
Solar/Wind Helper
0.198
25194608D.CRK4
Adder
1.656
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.99
945681AF1-233 GEN
Solar/Wind Harmer
11.914
253370AE2-315 SEC1
Adder
1.592
253371AE2-315 SEC2
Adder
1.506
960071AF2-298 GEN
Solar/Wind Harmer
2.635
970613AG2-401 GEN
Solar/Wind Harmer
3.314
253343AC1-166 GEN
Solar/Wind Harmer
0.002
971821AH1-427 GEN
Solar/Wind Harmer
4.286
24728605AND G2
Adder
2.32
965031AG1-367 GEN
Solar/Wind Harmer
4.122
970291AG2-192 GEN
Solar/Wind Harmer
0.477
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.04
964901AG1-354 GEN
Solar/Wind Harmer
5.126
942861AE2-305 GEN
Solar/Wind Harmer
2.346
970593AG2-378 GEN
Solar/Wind Harmer
0.735
963741AG1-226 GEN
Solar/Wind Harmer
7.599
960001AF2-291 GEN
Solar/Wind Helper
1.682
24802606KYGER 1HP
50/50
4.173
24802706KYGER 1LP
50/50
2.449
25016408BKJDB1
50/50
0.272
252524AE2-267 GEN
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
1.506
253372AE2-315 SEC3
Adder
1.506
25306009OHH W.
Adder
2.247
970689AG2-444 GEN
Solar/Wind Harmer
10.893
970289AG2-191 GEN
Solar/Wind Harmer
0.697
270024AE2-089 GEN
Solar/Wind Harmer
0.004
943861AF1-054 GEN
Solar/Wind Harmer
1.158
943851AF1-053 GEN
Solar/Wind Harmer
0.802
252519AF1-045_GEN
Solar/Wind Harmer
6.35
252516AE2-318_GEN
Solar/Wind Harmer
5.632
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
1.592
971125AH1-004 GEN
Solar/Wind Harmer
2.215
25322209TAIT E
Adder
7.486
25322209TAIT E
Adder
7.317
247621Y3-024
Adder
0.139
971613AH1-306 GEN
Solar/Wind Harmer
1.811
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.6
276820AF1-078_GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.656
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.086
253370AE2-315 SEC1
Adder
1.592
253371AE2-315 SEC2
Adder
1.506
24728505AND G1
Adder
2.32
946031AF1-268 GEN
Solar/Wind Harmer
3.889
970289AG2-191 GEN
Solar/Wind Harmer
0.403
970291AG2-192 GEN
Solar/Wind Harmer
0.367
247642Z2-115 C
Solar/Wind Harmer
0.002
960741AF2-365 GEN
Solar/Wind Harmer
1.775
971155AH1-034 GEN
Solar/Wind Harmer
3.802
971191AH1-055 GEN
Solar/Wind Harmer
69.07
252510AF1-249 C
Solar/Wind Harmer
0.054
25196008MFTGT1
Adder
1.285
972167AH1-666 GEN
Solar/Wind Harmer
5.077
970093AG2-073 GEN
Solar/Wind Harmer
4.742
966571AG1-526 GEN
Solar/Wind Harmer
10.106
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.885
970243AG2-164 GEN
Solar/Wind Harmer
2.07
972273AH1-721 GEN
Adder
41.409
957141AF2-008_MTX
Adder
29.541
944201AF1-088_MTX
Adder
59.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.459
WECLTFEXP_WEC->PJM
CLTF
1.45
MECLTFEXP_MEC->PJM
CLTF
6.369
AH1-155LTFEXP_AH1-155->PJM
LTF
0.141
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.324
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
LAGNLTFEXP_LAGN->PJM
CLTF
5.678
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.512
LGEELTFEXP_LGEE->PJM
CLTF
4.851
TVALTFEXP_TVA->PJM
CLTF
2.775
AG2-052LTFEXP_AG2-052->PJM
LTF
0.094
NYPJM->LTFIMP_NY
CLTF
1.447
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.02
SIGELTFEXP_SIGE->PJM
CLTF
0.3

Details for 06PIERCE-05MARQUI 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.36 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1561.02
MW Contribution:1.09
Bus #Bus NameTypeMW Contribution
970235AG2-159 GEN
Solar/Wind Harmer
3.613
970235AG2-159 GEN
Solar/Wind Harmer
2.073
970239AG2-162 GEN
Solar/Wind Harmer
1.269
270209AC1-174_GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.005
970241AG2-163 GEN
Solar/Wind Harmer
2.29
942221AE2-234 GEN
Solar/Wind Harmer
0.018
970107AG2-081 GEN
Solar/Wind Harmer
1.102
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970321AG2-212 GEN
Solar/Wind Harmer
1.448
276645AC1-214 GEN1
Solar/Wind Harmer
0.127
274888KELLY CRK;1U
Solar/Wind Harmer
0.186
972259AH1-714 GEN
Adder
8.636
274808UNIV PK N;4U
Adder
2.251
274696ROCKY RD ;4P
Adder
5.14
274697ROCKY RD ;3P
Adder
1.364
962691AG1-118 GEN
Solar/Wind Harmer
9.438
274770LINCOLN ;1U
Adder
3.805
274771LINCOLN ;2U
Adder
3.805
276603SUBLETTE C
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
1.78
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
25196108MFTGT2
Adder
1.559
25196108MFTGT2
Adder
1.448
25196408WSDLE3
Adder
8.856
25196308WSDLE2
Adder
8.779
25196208WSDLE1
Adder
8.757
25196708WSDLE6
Adder
8.735
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971673AH1-337 GEN
Solar/Wind Harmer
3.056
270543AE2-219 C
Solar/Wind Harmer
0.003
270594AE1-207 GEN
Solar/Wind Harmer
4.833
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.46
24691005MDL-2G C
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.477
24728905RICHG2
Adder
2.818
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.51
270599AE1-208 GEN
Solar/Wind Harmer
3.883
945391AF1-204 GEN
Solar/Wind Harmer
4.382
960971AF2-388 GEN
Solar/Wind Harmer
2.335
966841AG1-555 GEN
Solar/Wind Harmer
0.43
972043AH1-570 GEN
Solar/Wind Harmer
0.949
960611AF2-352 GEN
Solar/Wind Harmer
1.133
942891AE2-308 GEN
Solar/Wind Harmer
3.277
971081AG2-670 GEN
Solar/Wind Harmer
2.441
276782AC1-033 GEN
Solar/Wind Harmer
0
274879MINONK ;1U
Solar/Wind Harmer
0.134
274862TOP CROP ;2U
Solar/Wind Harmer
0.43
958481AF2-142 GEN
Solar/Wind Harmer
4.764
274887GEN-1.85
Solar/Wind Harmer
0.083
274674JOLIET 9 ;6U
Adder
6.975
276708O09 GEN2
Solar/Wind Harmer
0.113
274803UNIV PARK;6U
Adder
2.636
274693ROCKY RD ;1P
Adder
4.972
970921AG2-575 GEN
Solar/Wind Harmer
3.145
970921AG2-575 GEN
Solar/Wind Harmer
1.048
971335AH1-147 GEN
Solar/Wind Harmer
6.283
971985AH1-537 GEN
Solar/Wind Harmer
2.063
971029AG2-637 GEN
Solar/Wind Harmer
6.982
24725505WLD G2 C
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
1.341
945581AF1-223 GEN
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.122
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
2.815
339211AE2-254 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
0.639
970833AG2-524 GEN
Solar/Wind Harmer
3.487
970833AG2-524 GEN
Solar/Wind Harmer
2.324
960591AF2-350 GEN
Solar/Wind Harmer
3.162
274675JOLIET 29;7U
Adder
13.874
274675JOLIET 29;7U
Adder
13.378
972037AH1-567 GEN1
Adder
0.083
274775LINCOLN ;6U
Adder
3.805
274777LINCOLN ;8U
Adder
1.515
971675AH1-338 GEN
Solar/Wind Harmer
1.227
971171AH1-044 GEN
Solar/Wind Harmer
6.288
971411AH1-196 GEN
Solar/Wind Harmer
4.711
946321AF1-296 GEN
Solar/Wind Harmer
1.755
971347AH1-153 GEN
Solar/Wind Harmer
4.502
270330AC1-082 GEN2
Solar/Wind Helper
0.021
25194508D.CRK3
Adder
1.398
252509AD1-136 GEN
Solar/Wind Harmer
0.034
24728805RICHG1
Adder
2.818
24379505HDWTR1G C
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.007
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970885AG2-551 GEN
Solar/Wind Harmer
1.503
960441AF2-335 GEN
Solar/Wind Harmer
4.495
964611AG1-324 GEN
Solar/Wind Harmer
0.32
270031AE2-169
Solar/Wind Harmer
2.33
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964571AG1-320 GEN
Solar/Wind Harmer
3.758
944541AF1-119 GEN
Solar/Wind Harmer
0.267
25326109MON D
Adder
0.742
339221AD2-048_GEN
Solar/Wind Harmer
0.002
970653AG2-424 GEN
Solar/Wind Harmer
1.834
970653AG2-424 GEN
Solar/Wind Harmer
0.95
945421AF1-207 GEN
Solar/Wind Harmer
0
972045AH1-571 GEN
Solar/Wind Harmer
0.76
276911AD2-131_GEN
Solar/Wind Harmer
0.489
274851PROVIDENC;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.127
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
958491AF2-143 GEN
Solar/Wind Harmer
4.777
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.553
971573AH1-285 GEN
Solar/Wind Harmer
0.586
274695ROCKY RD ;2P
Adder
5.022
942991AE2-321 GEN
Solar/Wind Harmer
3.508
971333AH1-146 GEN
Solar/Wind Harmer
6.283
965791AG1-447 GEN
Solar/Wind Harmer
2.834
24441505OLIV SLR
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0.004
25196508WSDLE4
Adder
8.515
970115AG2-085 GEN
Solar/Wind Harmer
1.798
24699105WLD G1 C
Solar/Wind Harmer
0.001
253400AC2-068 GEN
Solar/Wind Harmer
0.539
971609AH1-304 GEN
Solar/Wind Harmer
0.692
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
965101AG1-375 GEN
Solar/Wind Harmer
4.064
970455AG2-298 GEN
Solar/Wind Harmer
2.674
963841AG1-237 GEN
Solar/Wind Harmer
1.675
24386205FR-12G C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
2.096
276655WTG1_EQ
Solar/Wind Harmer
0.001
3429211JKCT 2G
Adder
5.399
926823AC1-168 GEN
Solar/Wind Harmer
0.547
276882AE2-255 GEN
Solar/Wind Harmer
0.373
274731ELWOOD EC;2P
Adder
7.457
274733ELWOOD EC;3P
Adder
7.457
274687WILL CNTY;4U
Adder
12.634
274687WILL CNTY;4U
Adder
12.634
274746AC1-111 G10
Adder
2.525
274814UNIV PK N;0U
Adder
2.28
274807UNIV PK N;3U
Adder
2.275
274805UNIV PK N;1U
Adder
2.265
274776LINCOLN ;7U
Adder
3.805
241972AD1-140 GEN
Solar/Wind Harmer
0.34
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270329AC1-082 GEN1
Solar/Wind Helper
0.099
252519AF1-045_GEN
Solar/Wind Harmer
5.274
252516AE2-318_GEN
Solar/Wind Harmer
4.678
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.281
971613AH1-306 GEN
Solar/Wind Harmer
2.071
247621Y3-024
Adder
0.148
253370AE2-315 SEC1
Adder
1.177
25322209TAIT E
Adder
5.698
25322209TAIT E
Adder
5.57
971125AH1-004 GEN
Solar/Wind Harmer
1.469
276916AD2-100_GEN
Solar/Wind Harmer
7.418
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.113
971341AH1-150 GEN
Solar/Wind Harmer
6.288
971343AH1-151 GEN
Solar/Wind Harmer
6.288
965681AG1-436 GEN
Solar/Wind Harmer
3.864
25016408BKJDB1
50/50
0.315
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.806
25306009OHH W.
Adder
1.706
253372AE2-315 SEC3
Adder
1.113
253372AE2-315 SEC3
Adder
1.113
270024AE2-089 GEN
Solar/Wind Harmer
0.004
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.127
276848AB2-070 GEN3
Solar/Wind Harmer
0.127
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
959341AF2-225 GEN
Solar/Wind Harmer
3.547
970169AG2-114 GEN
Solar/Wind Harmer
3.303
963791AG1-232 GEN
Solar/Wind Harmer
4.381
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
274735ELWOOD EC;4P
Adder
7.457
972227AH1-698 GEN1
Adder
1.183
274827FISK ;RP
Adder
3.505
274744AC1-111 GEN8
Adder
2.525
274811UNIV PK N;7U
Adder
2.261
961011AF2-392 GEN
Solar/Wind Harmer
1.844
25194608D.CRK4
Adder
1.625
24728505AND G1
Adder
2.615
946031AF1-268 GEN
Solar/Wind Harmer
4.275
970289AG2-191 GEN
Solar/Wind Harmer
0.466
970291AG2-192 GEN
Solar/Wind Harmer
0.424
247642Z2-115 C
Solar/Wind Harmer
0.002
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
24755605MDL-5G
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.127
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
960741AF2-365 GEN
Solar/Wind Harmer
1.664
274734ELWOOD EC;8P
Adder
7.457
274736ELWOOD EC;9P
Adder
7.457
276806AD2-047 C O1
Solar/Wind Harmer
1.792
274676JOLIET 29;8U
Adder
13.378
943121AE2-341 GEN
Solar/Wind Harmer
5.278
943591AF1-030 GEN
Solar/Wind Harmer
3.51
959091AF2-200 GEN
Solar/Wind Harmer
6.288
25194608D.CRK4
Adder
1.625
970613AG2-401 GEN
Solar/Wind Harmer
3.697
24728605AND G2
Adder
2.615
965031AG1-367 GEN
Solar/Wind Harmer
4.603
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970291AG2-192 GEN
Solar/Wind Harmer
0.551
960071AF2-298 GEN
Solar/Wind Harmer
2.043
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
965651AG1-433 GEN
Solar/Wind Harmer
1.167
270055AF2-134 C O1
Solar/Wind Harmer
0.003
971821AH1-427 GEN
Solar/Wind Harmer
3.331
274877BISHOP HL;1U
Solar/Wind Harmer
0.108
276901AD2-066 C O1
Solar/Wind Harmer
0.003
274871GR RIDGE ;2U
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.33
274676JOLIET 29;8U
Adder
13.874
274745AC1-111 GEN9
Adder
2.525
274812UNIV PK N;8U
Adder
2.261
276164X3-005 C
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
9.432
964901AG1-354 GEN
Solar/Wind Harmer
4.633
270222AC2-111 GEN
Solar/Wind Harmer
2.803
270356AE2-297 GEN
Solar/Wind Harmer
0.007
270004AE1-209 GEN
Solar/Wind Harmer
0.997
970191AG2-125 GEN
Solar/Wind Harmer
1.095
971617AH1-308 GEN
Solar/Wind Harmer
3.198
276686W4-005 GEN3
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.199
274878BISHOP HL;2U
Solar/Wind Harmer
0.108
972038AH1-567 GEN2
Adder
0.165
274872LEEDK;1U
Solar/Wind Harmer
0.115
965931AG1-462 GEN
Solar/Wind Harmer
7.987
962251AG1-071 GEN
Solar/Wind Harmer
1.885
970773AG2-487 GEN
Solar/Wind Harmer
0.942
970091AG2-072 GEN
Adder
56.565
971565AH1-281 GEN
Solar/Wind Harmer
0.847
963741AG1-226 GEN
Solar/Wind Harmer
9.29
24791305MDL-5G
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.508
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
6.927
3429421JKCT 10G
Adder
3.902
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274872LEEDK;1U
Solar/Wind Harmer
0.002
959081AF2-199 GEN
Solar/Wind Harmer
3.144
971067AG2-660 GEN
Solar/Wind Harmer
1.048
970819AG2-516 GEN
Solar/Wind Harmer
3.764
971475AH1-234 GEN
Solar/Wind Harmer
1.52
927014AC1-188 GEN
Solar/Wind Helper
0.876
270263AC1-001 GEN
Solar/Wind Helper
0.622
960001AF2-291 GEN
Solar/Wind Helper
0.551
25196608WSDLE5
Adder
8.603
970519AG2-331 GEN
Solar/Wind Harmer
13.197
970699AG2-449 GEN
Solar/Wind Harmer
1.269
270437AC2-090 C
Solar/Wind Harmer
0.002
24728705AND G3
Adder
5.469
958821AF2-173 GEN
Solar/Wind Harmer
6.444
970193AG2-126 GEN
Solar/Wind Harmer
6.187
970781AG2-491 GEN
Solar/Wind Harmer
3.711
944531AF1-118 GEN
Solar/Wind Harmer
16.26
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
959611AF2-252 GEN
Solar/Wind Harmer
1.133
970513AG2-328 GEN
Solar/Wind Harmer
1.448
970517AG2-330 GEN
Solar/Wind Harmer
8.688
3429391JKCT 9G
Adder
3.902
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
1.68
274730ELWOOD EC;6P
Adder
7.457
274826FISK ;BP
Adder
4.945
970707AG2-453 GEN
Solar/Wind Harmer
10.286
274855GSG-6 ;RU
Solar/Wind Harmer
0.115
958171AF2-111 GEN
Solar/Wind Harmer
7.532
970349AG2-230 GEN
Solar/Wind Harmer
4.502
957541AF2-048 GEN
Solar/Wind Helper
0.879
270273AD2-016 GEN
Solar/Wind Helper
1.449
252507AC2-088 GEN
Solar/Wind Harmer
0.307
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
6.208
957751AF2-069 GEN
Solar/Wind Harmer
0.106
274728ELWOOD EC;5P
Adder
7.457
971681AH1-341 GEN
Solar/Wind Harmer
5.059
971177AH1-047 GEN
Solar/Wind Harmer
1.937
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971769AH1-391 GEN
Solar/Wind Harmer
3.38
25196008MFTGT1
Adder
1.37
252510AF1-249 C
Solar/Wind Harmer
0.052
970243AG2-164 GEN
Solar/Wind Harmer
2.969
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.308
942481AE2-261 GEN
Solar/Wind Harmer
10.525
276621W2-048 GEN
Solar/Wind Harmer
0.176
276838X2-022 GEN2
Solar/Wind Harmer
0.197
971993AH1-541 GEN
Solar/Wind Harmer
1.613
966571AG1-526 GEN
Solar/Wind Harmer
7.577
942111AE2-223 GEN
Solar/Wind Harmer
1.098
970571AG2-364 GEN
Solar/Wind Harmer
6.41
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.004
970093AG2-073 GEN
Solar/Wind Harmer
3.181
276893AG1-478 C
Solar/Wind Harmer
0.125
274729ELWOOD EC;1P
Adder
7.457
970941AG2-585 GEN
Solar/Wind Harmer
3.953
276157O29GEN1
Solar/Wind Harmer
0.511
274800UNIV PARK;3U
Adder
2.637
274802UNIV PARK;5U
Adder
2.636
274772LINCOLN ;3U
Adder
3.805
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.056
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.335
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
4.926
247536S-71 GEN
Solar/Wind Harmer
0.176
339216AC1-074 GEN
Solar/Wind Harmer
0.113
25326309TAIT D
Adder
0.64
24385905FR-11G C
Solar/Wind Harmer
0.001
965911AG1-460 GEN
Solar/Wind Harmer
0.704
276615X2-022 GEN
Solar/Wind Harmer
0.037
963831AG1-236 GEN
Solar/Wind Harmer
1.362
958381AF2-132 GEN
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
1.448
939401AE1-172 GEN
Solar/Wind Harmer
2.433
3429241JKCT 3G
Adder
5.47
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
7.457
274674JOLIET 9 ;6U
Adder
6.975
962781AG1-127 GEN
Solar/Wind Harmer
2.993
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
962241AG1-070 GEN
Solar/Wind Harmer
1.643
25196008MFTGT1
Adder
1.414
25196808ZIMRHP
Adder
62.29
970333AG2-219 GEN
Solar/Wind Harmer
3.629
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
0.997
970825AG2-519 GEN
Solar/Wind Harmer
1.603
270032AE2-172
Solar/Wind Harmer
2.877
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.761
24387305FR-4G C
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.455
274880W4-005 GEN4
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.851
939741AE1-205 GEN
Solar/Wind Harmer
4.729
970569AG2-363 GEN
Solar/Wind Harmer
9.614
971997AH1-543 GEN
Solar/Wind Harmer
1.678
276158O29GEN2
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.637
274773LINCOLN ;4U
Adder
3.805
274774LINCOLN ;5U
Adder
3.805
276861AD2-134 GEN
Solar/Wind Harmer
0.056
270331AC1-082 GEN3
Solar/Wind Helper
0.099
957141AF2-008_MTX
Adder
37.28
944201AF1-088_MTX
Adder
74.561
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.307
WECLTFEXP_WEC->PJM
CLTF
1.713
MECLTFEXP_MEC->PJM
CLTF
7.273
AH1-155LTFEXP_AH1-155->PJM
LTF
0.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.478
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.651
LAGNLTFEXP_LAGN->PJM
CLTF
5.322
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.91
LGEELTFEXP_LGEE->PJM
CLTF
5.218
TVALTFEXP_TVA->PJM
CLTF
2.383
AG2-052LTFEXP_AG2-052->PJM
LTF
0.113
NYPJM->LTFIMP_NY
CLTF
1.072
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.331
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#762_8072_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#762_8072_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1229.31
MW Contribution:2.18
Bus #Bus NameTypeMW Contribution
253394AE2-221_GEN
Solar/Wind Harmer
0.012
253398AE2-221_GEN2
Solar/Wind Harmer
0.012
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
0.981
270186AC1-089 GEN
Solar/Wind Harmer
0.003
253378AE2-206_GEN
Solar/Wind Harmer
0.002
970107AG2-081 GEN
Solar/Wind Harmer
1.157
970235AG2-159 GEN
Solar/Wind Harmer
2.31
970235AG2-159 GEN
Solar/Wind Harmer
1.325
960161AF2-307 GEN
Solar/Wind Harmer
2.281
25196408WSDLE3
Adder
7.973
25196308WSDLE2
Adder
7.904
25196208WSDLE1
Adder
7.884
25196708WSDLE6
Adder
7.864
270156DARBY CT1
Adder
7.416
270157DARBY CT2
Adder
7.397
25196108MFTGT2
Adder
1.081
25196108MFTGT2
Adder
1.004
270367AC2-061_GEN
Solar/Wind Harmer
0.004
971673AH1-337 GEN
Solar/Wind Harmer
2.635
270543AE2-219 C
Solar/Wind Harmer
0.002
25194408D.CRK1
Adder
6.692
24728905RICHG2
Adder
2.343
972043AH1-570 GEN
Solar/Wind Harmer
1.039
970883AG2-550 GEN
Solar/Wind Harmer
3.593
942891AE2-308 GEN
Solar/Wind Harmer
3.483
25322309TAIT W
50/50
0.723
253349AC2-067 GEN
Solar/Wind Harmer
2.666
270158DARBY CT3
Adder
7.279
972165AH1-665 GEN
Solar/Wind Harmer
4.068
971029AG2-637 GEN
Solar/Wind Harmer
5.898
270520AE2-214 GEN
Solar/Wind Helper
6.734
270054AF2-122 C O1
Solar/Wind Helper
0.911
25326109MON D
50/50
2.074
270518AE2-148 GEN
Solar/Wind Harmer
2.944
25183208HLCRTG
Solar/Wind Harmer
0.01
25194508D.CRK3
Adder
1.251
252509AD1-136 GEN
Solar/Wind Harmer
0.028
970329AG2-216 GEN
Solar/Wind Harmer
1.963
24728805RICHG1
Adder
2.343
339221AD2-048_GEN
Solar/Wind Harmer
0.002
972045AH1-571 GEN
Solar/Wind Harmer
0.833
970885AG2-551 GEN
Solar/Wind Harmer
1.198
270383AD1-128 GEN
Solar/Wind Harmer
0.002
946101AF1-275 GEN
Solar/Wind Helper
0.844
945631AF1-228 GEN
Solar/Wind Harmer
0
253400AC2-068 GEN
Solar/Wind Harmer
1.072
241972AD1-140 GEN
Solar/Wind Harmer
0.856
25196508WSDLE4
Adder
7.666
972163AH1-664 GEN
Solar/Wind Harmer
5.08
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
3429211JKCT 2G
Adder
5.988
270340AC2-060 GEN
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
50/50
3.051
25322209TAIT E
50/50
14.556
25322209TAIT E
50/50
14.229
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
252519AF1-045_GEN
Solar/Wind Harmer
5.411
252516AE2-318_GEN
Solar/Wind Harmer
4.799
276820AF1-078_GEN
Solar/Wind Harmer
0.001
971125AH1-004 GEN
Solar/Wind Harmer
1.542
247621Y3-024
Adder
0.107
253372AE2-315 SEC3
50/50
2.886
253372AE2-315 SEC3
50/50
2.886
963581AG1-207 GEN
50/50
13.114
25306009OHH W.
50/50
4.038
252524AE2-267 GEN
Solar/Wind Harmer
0.002
253370AE2-315 SEC1
50/50
3.051
253371AE2-315 SEC2
50/50
2.886
25322209TAIT E
50/50
0.706
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
10.473
25194608D.CRK4
Adder
1.455
241955AC1-078 GEN
Solar/Wind Helper
1.673
253370AE2-315 SEC1
50/50
3.051
253371AE2-315 SEC2
50/50
2.886
25322209TAIT E
50/50
0.715
960071AF2-298 GEN
Solar/Wind Harmer
4.595
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.056
25194608D.CRK4
Adder
1.455
253343AC1-166 GEN
Solar/Wind Harmer
0.003
945681AF1-233 GEN
Solar/Wind Harmer
8.713
970191AG2-125 GEN
Solar/Wind Harmer
2.178
253338AC1-165 GEN
Solar/Wind Harmer
0.003
270222AC2-111 GEN
Solar/Wind Harmer
2.609
270356AE2-297 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.009
270159DARBY CT4
Adder
7.297
3429421JKCT 10G
Adder
4.399
970773AG2-487 GEN
Solar/Wind Harmer
0.586
25322309TAIT W
50/50
0.715
253406AD2-031_GEN
Solar/Wind Harmer
0.612
25196608WSDLE5
Adder
7.745
253333AC1-068 GEN
Solar/Wind Harmer
0.009
958171AF2-111 GEN
Solar/Wind Harmer
12.35
253415AE1-040 GEN
Solar/Wind Harmer
0.002
3429391JKCT 9G
Adder
4.399
270273AD2-016 GEN
Solar/Wind Helper
1.465
25322309TAIT W
50/50
0.715
25326309TAIT D
50/50
1.635
252507AC2-088 GEN
Solar/Wind Harmer
0.247
339216AC1-074 GEN
Solar/Wind Harmer
0.112
3429241JKCT 3G
Adder
6.066
247536S-71 GEN
Solar/Wind Harmer
0.132
252510AF1-249 C
Solar/Wind Harmer
0.047
25196008MFTGT1
Adder
0.95
972167AH1-666 GEN
Solar/Wind Harmer
3.713
970093AG2-073 GEN
Solar/Wind Harmer
3.322
966571AG1-526 GEN
Solar/Wind Harmer
6.932
960801AF2-371 GEN
Solar/Wind Helper
0.866
964871AG1-351 GEN
Solar/Wind Helper
0.598
25196808ZIMRHP
Adder
60.434
25196008MFTGT1
Adder
0.981
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.151
LGEELTFEXP_LGEE->PJM
CLTF
2.957
MECLTFEXP_MEC->PJM
CLTF
3.173
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.743
WECLTFEXP_WEC->PJM
CLTF
0.648
LAGNLTFEXP_LAGN->PJM
CLTF
3.644
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.756
NYPJM->LTFIMP_NY
CLTF
0.877
TVALTFEXP_TVA->PJM
CLTF
1.893
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.43
CPLELTFEXP_CPLE->PJM
CLTF
0.155
SIGELTFEXP_SIGE->PJM
CLTF
0.18
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P1-2_#309_15_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P1-2_#762_8072_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 245769 CKT 1   /*05BEATTY     345.0 - 05ADKINS     345.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
242925 to 235117 ckt 1
290623 to 242925 ckt Z1
242516 to 242920 ckt 1
248005 to 242528 ckt 1
248013 to 242938 ckt 1
945630 to 243453 ckt 1

Winter Peak Analysis

The New Service Request AG2-125 was evaluated as a 0.0 MW (15.44 MW Capacity) injection in the Dayton area.

AG2-125 was evaluated as part of a plant. The plant consists of AG2-125. The total Energy output of the plant was evaluated at its maximum seasonal capability of 69.9 MW (0.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-125 was evaluated as a 0.0 MW injection

AG2-125 was evaluated as part of a plant. The plant consists of AG2-125. The total Energy output of the plant was evaluated at its maximum seasonal capability of 69.9 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-150Grassy Falls 138kVIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB1-180Pine View 12kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-049Gloucester Township 12kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-093Ormet 138kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-111Aurora 138kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-157Sullivan 345 kVUnder Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-035Lena 138 kVIn Service
AE2-042Milton 69 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-216Hardin Switch 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-285Maysville 69 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-308Three Forks-Dale 138 kVActive
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-051Gavin 765 kVIn Service
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-122Cardington-Liberty 69 kVSuspended
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-382Hurley 69 kVEngineering & Procurement
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-207Vandalia 69 kVEngineering & Procurement
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Glendale-Stephensburg 69 kVActive
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVActive
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-471Up Church-Wayne County 69 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-526West Garrard 345 kVActive
AG1-555Dequine 345 kVEngineering & Procurement
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-126Eugene 345 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-582Flint Run 500 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Prairie 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-339West Crawford 69 kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-348Pound 34.5 kVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-644Spicewood Metering 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-704Hannibal 138 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-719Beverly 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-049Wurno 34.5kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b3877.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3877.1
Title
Replace station conductor and switches in the 345 kV yard at Beatty
Description
Replace station conductor and switches in the 345 kV yard at Beatty that are currently limiting the 345 kV lines to Adkins and Chenoweth.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05BEATTY-AF1-228 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18819
Title
06PIERCE 345kV to 05MARQUIS 345kV ckt 1 - Replace Equipment
Description
At Pierce replace the following equipment: Switch 444, 446, 447, and 449, Bus, Risers, Jumpers, Wave Trap, and Line Relay At Don Marquis 345kV replace the following equipment: Circuit Breaker B2, Risers, and Line Reactor.
Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-125 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-125 could receive cost allocation. Although AG2-125 may not presently have cost responsibility for this upgrade, AG2-125 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)

System Reinforcement: s2213.9
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s2213.9 / (Pending)
Title
Six-wire 71.5 miles of the Pierce-Don Marquis line. Construct 0.13 miles of line to tie into Don Marquis station.
Description
Six-wire 71.5 miles of the Pierce-Don Marquis line. Construct 0.13 miles of line to tie into Don Marquis station.
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG2-125 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-125 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-125 could receive cost allocation. Although AG2-125 may not presently have cost responsibility for this upgrade, AG2-125 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Nov 18 2027

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AG2-125 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-125 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

Attachments

The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.